AH1-306 Phase II System Impact Study Report

v1.00 released 2026-06-03 17:48

Mississinewa-Gaston 138 kV

28.8 MW Capacity / 0.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Golden Aster Solar Energy LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is AEP Indiana Michigan Transmission Company, Inc..

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $0 $0 = ∞ AND ( $0 - $0 ) 28.8 = $0 per MW

General

The Project Developer has proposed an uprate to a planned/existing Solar/Storage facility located in the AEP Indiana Michigan Transmission Company, Inc. zone — Grant County, Indiana. This project is an increase to the developer’s AE1-207/AE2-172 project(s), which will share the same Point of Interconnection. The AH1-306 project is a 28.8 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 200.0 MW with 136.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-306
Project Name:
Mississinewa-Gaston 138 kV
Project Developer Name:
Golden Aster Solar Energy LLC
State:
Indiana
County:
Grant
Transmission Owner:
AEP Indiana Michigan Transmission Company, Inc.
MFO:
200.0
MWE:
0.0
MWC:
28.8
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Not Required

A Physical Interconnection Facilities Study is not required for this project.

Point of Interconnection

AH1-306 will interconnect on the American Electric Power transmission system by tapping the Mississinewa-Gaston 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-306 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-306Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$0$0$0
Other Scope$0$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$0$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$0$0$0

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-306

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-306
Project ID: AH1-306
20% of cost allocation for Phase II Network Upgrades:(A) $0
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $115,200
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

no interconnections facilities required to support the interconnection

(Pending Facilities Study)$0$0
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$0$0
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 0 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-306 was evaluated as a 0.0 MW (28.8 MW Capacity) injection in the AEP area.

AH1-306 was evaluated as part of a plant. The plant consists of AH1-306. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC102.09 %5523.0B5638.63
3.15
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC102.08 %5523.0B5637.94
3.15
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC123.36 %4571.0B5638.63
3.15
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC123.34 %4571.0B5637.94
3.15
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC104.85 %4142.0B4342.78
4.36
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC104.04 %4142.0B4309.27
4.9
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.48 %4571.0B4638.62
4.23
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.94 %4571.0B4659.48
4.23
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS
SingleAC120.92 %4142.0B5008.41
4.61
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#9287_1679_SRT-A
SingleAC103.12 %4142.0B4271.28
3.1
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC107.72 %1189.0A1280.85
1.67

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
3.15
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
3.15
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.36 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
3.15
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
3.15
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4342.78
MW Contribution:
4.36
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.43 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4946.71
MW Contribution:
4.12
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
13.691
962761AG1-125 GEN
Solar/Wind Harmer
51.21
970149AG2-104 GEN
Solar/Wind Harmer
27.654
970155AG2-107 GEN
Solar/Wind Harmer
32.701
270520AE2-214 GEN
Solar/Wind Harmer
0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
270273AD2-016 GEN
Solar/Wind Harmer
1.001
25326309TAIT D
Adder
1.474
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.673
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.387
971995AH1-542 GEN
Solar/Wind Harmer
3.337
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.826
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270051AF1-062 GEN
50/50
18.043
270475AD2-096_GEN
50/50
10.581
962771AG1-126 GEN
Solar/Wind Harmer
51.21
970153AG2-106 GEN
Solar/Wind Harmer
32.701
961921AG1-034 GEN
Solar/Wind Harmer
11.241
270284AF1-227 GEN1
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Harmer
20.261
270518AE2-148 GEN
Solar/Wind Harmer
0.888
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
970191AG2-125 GEN
Solar/Wind Harmer
2.379
944531AF1-118 GEN
Solar/Wind Harmer
41.277
270043AE2-236 GEN
Solar/Wind Harmer
5.885
247642Z2-115 C
Solar/Wind Harmer
0.004
971347AH1-153 GEN
Solar/Wind Harmer
4.578
970289AG2-191 GEN
Solar/Wind Harmer
1.003
253394AE2-221_GEN
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
3.029
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.079
24386205FR-12G C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
10.86
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.441
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.642
946031AF1-268 GEN
Solar/Wind Harmer
8.511
970825AG2-519 GEN
Solar/Wind Harmer
6.737
270004AE1-209 GEN
Solar/Wind Harmer
1.936
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
22.661
274752CRETE EC ;2U
Adder
10.545
274753CRETE EC ;3U
Adder
10.545
274814UNIV PK N;0U
Adder
6.452
274807UNIV PK N;3U
Adder
6.438
274811UNIV PK N;7U
Adder
6.396
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.288
276806AD2-047 C O1
Solar/Wind Harmer
5.041
970707AG2-453 GEN
Solar/Wind Harmer
29.056
274803UNIV PARK;6U
Adder
7.433
274826FISK ;BP
Adder
13.952
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
24.311
972038AH1-567 GEN2
Adder
0.465
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.319
270491AE1-102 GEN2
Solar/Wind Harmer
1.154
274676JOLIET 29;8U
Adder
37.578
274729ELWOOD EC;1P
Adder
20.872
274730ELWOOD EC;6P
Adder
20.872
274734ELWOOD EC;8P
Adder
20.872
274736ELWOOD EC;9P
Adder
20.872
270505AE1-170 C O1
Solar/Wind Harmer
9.267
270156DARBY CT1
50/50
0.841
270157DARBY CT2
50/50
0.839
270159DARBY CT4
50/50
0.828
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.265
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
7.494
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
4.282
943851AF1-053 GEN
Solar/Wind Harmer
2.966
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
4.521
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.422
241972AD1-140 GEN
Solar/Wind Harmer
1.102
253372AE2-315 SEC3
Adder
2.534
253372AE2-315 SEC3
Adder
2.534
270071AF1-092 GEN
Solar/Wind Harmer
17.821
25306009OHH W.
Adder
3.829
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.92
24729505KEY G4
Adder
8.54
970289AG2-191 GEN
Solar/Wind Harmer
1.733
971611AH1-305 GEN
Solar/Wind Harmer
5.423
959141AF2-205 GEN
Solar/Wind Harmer
0.001
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
6.362
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.671
945581AF1-223 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963791AG1-232 GEN
Solar/Wind Harmer
12.161
971609AH1-304 GEN
Solar/Wind Harmer
1.469
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
10.86
274776LINCOLN ;7U
Adder
10.86
274777LINCOLN ;8U
Adder
10.86
270526AF1-158 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
3.493
247536S-71 GEN
Solar/Wind Harmer
0.358
247521TR3_G114
Solar/Wind Harmer
0.324
965051AG1-369 GEN
Solar/Wind Harmer
4.466
270543AE2-219 C
Solar/Wind Harmer
6.262
970031AG2-029 GEN
Solar/Wind Harmer
4.844
971771AH1-392 GEN
Solar/Wind Harmer
8.94
971029AG2-637 GEN
Solar/Wind Harmer
13.408
965041AG1-368 GEN
Solar/Wind Harmer
8.914
963841AG1-237 GEN
Solar/Wind Harmer
3.86
960591AF2-350 GEN
Solar/Wind Harmer
8.895
972228AH1-698 GEN2
Adder
4.722
972227AH1-698 GEN1
Adder
3.325
972037AH1-567 GEN1
Adder
0.233
274827FISK ;RP
Adder
9.888
274800UNIV PARK;3U
Adder
7.429
274801UNIV PARK;4U
Adder
7.429
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.124
274687WILL CNTY;4U
Adder
35.509
274687WILL CNTY;4U
Adder
35.509
274675JOLIET 29;7U
Adder
38.97
274675JOLIET 29;7U
Adder
37.578
274728ELWOOD EC;5P
Adder
20.872
274731ELWOOD EC;2P
Adder
20.872
274733ELWOOD EC;3P
Adder
20.872
274735ELWOOD EC;4P
Adder
20.872
970833AG2-524 GEN
Solar/Wind Harmer
9.741
970833AG2-524 GEN
Solar/Wind Harmer
6.494
274744AC1-111 GEN8
Adder
7.068
274746AC1-111 G10
Adder
7.068
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.922
270356AE2-297 GEN
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
8.736
971675AH1-338 GEN
Solar/Wind Harmer
3.397
276861AD2-134 GEN
Solar/Wind Harmer
0.155
276863AD2-134 GEN
Solar/Wind Harmer
0.155
971411AH1-196 GEN
Solar/Wind Harmer
13.063
25196408WSDLE3
Adder
10.988
971171AH1-044 GEN
Solar/Wind Harmer
17.379
926823AC1-168 GEN
Solar/Wind Harmer
1.477
270007AE1-245 C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
24.227
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.098
274856ECOGROVE ;U1
Solar/Wind Harmer
0.202
971681AH1-341 GEN
Solar/Wind Harmer
13.904
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
276741O09 GEN1
Solar/Wind Harmer
0.303
972267AH1-718 GEN
Adder
5.127
276668AB2-070 GEN1
Solar/Wind Harmer
0.334
276848AB2-070 GEN3
Solar/Wind Harmer
0.333
276849AB2-070 GEN2
Solar/Wind Harmer
0.334
25196108MFTGT2
Adder
1.87
25196108MFTGT2
Adder
1.736
946321AF1-296 GEN
Solar/Wind Harmer
4.758
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
241985AE1-237 GEN
Solar/Wind Helper
0.309
241982AE2-343 S C
Solar/Wind Helper
0.277
241997AF1-093 GEN
Solar/Wind Helper
0.312
23652301WDPWR_K20
Solar/Wind Helper
0.16
23750501ELLIOTTS
Solar/Wind Helper
0.695
203846AF2-130 C
Solar/Wind Helper
0.498
20089126CSLMN_L13
Solar/Wind Helper
0.613
20089226LOOKOUT
Solar/Wind Helper
0.611
20088926STNY CRK
Solar/Wind Helper
0.849
20094526CT_V3-030
Solar/Wind Helper
0.494
203955AF1-039 C O1
Solar/Wind Helper
0.38
203940AF1-140 C
Solar/Wind Helper
0.411
20088626ARWF_N39
Solar/Wind Helper
1.24
20334926Z1-069 C
Solar/Wind Helper
1.403
23750701CROSSCHOOL
Solar/Wind Helper
1.182
238118U2-030_1
Solar/Wind Helper
0.283
270119AB2-067 GEN1
50/50
13.691
270120AB2-067 GEN2
50/50
13.691
270160DARBY CT5
50/50
0.825
270161DARBY CT6
50/50
0.813
270466AD2-091
50/50
8.422
25326109MON D
50/50
1.903
25326509SID D
50/50
1.895
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
8.674
938701AE1-092 GEN
Solar/Wind Harmer
16.303
971655AH1-328 GEN
Solar/Wind Harmer
3.602
270462AD2-086
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
4.181
25322209TAIT E
Adder
13.115
25322209TAIT E
Adder
12.82
253370AE2-315 SEC1
Adder
2.679
970349AG2-230 GEN
Solar/Wind Harmer
13.735
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.186
970291AG2-192 GEN
Solar/Wind Harmer
0.547
944541AF1-119 GEN
Solar/Wind Harmer
0.609
960971AF2-388 GEN
Solar/Wind Harmer
5.346
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
4.358
942221AE2-234 GEN
Solar/Wind Harmer
3.637
965681AG1-436 GEN
Solar/Wind Harmer
11.293
965791AG1-447 GEN
Solar/Wind Harmer
8.281
270031AE2-169
Solar/Wind Harmer
4.946
270599AE1-208 GEN
Solar/Wind Harmer
8.243
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.019
274770LINCOLN ;1U
Adder
10.86
274771LINCOLN ;2U
Adder
10.86
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.31
964611AG1-324 GEN
Solar/Wind Harmer
0.672
270246TR4_N_V150
Solar/Wind Harmer
0.057
270247TR4_N_V136
Solar/Wind Harmer
0.057
970883AG2-550 GEN
Solar/Wind Harmer
8.946
970885AG2-551 GEN
Solar/Wind Harmer
2.982
270383AD1-128 GEN
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
6.41
274808UNIV PK N;4U
Adder
6.368
274888KELLY CRK;1U
Solar/Wind Harmer
0.519
276776AD2-060 GEN
Solar/Wind Harmer
0.949
958011AF2-095 GEN
Solar/Wind Harmer
12.809
970941AG2-585 GEN
Solar/Wind Harmer
4.892
276897AD1-100 C
Solar/Wind Harmer
22.228
247620Y3-023
Adder
0.586
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.358
274674JOLIET 9 ;6U
Adder
19.549
276893AG1-478 C
Solar/Wind Harmer
0.591
970241AG2-163 GEN
Solar/Wind Harmer
5.155
958481AF2-142 GEN
Solar/Wind Harmer
13.2
961051AF2-396 GEN
Solar/Wind Harmer
17.567
961051AF2-396 GEN
Solar/Wind Harmer
11.711
274695ROCKY RD ;2P
Adder
14.015
274693ROCKY RD ;1P
Adder
13.877
274697ROCKY RD ;3P
Adder
3.807
274696ROCKY RD ;4P
Adder
14.346
274683WAUKEGAN ;8U
Adder
26.494
274683WAUKEGAN ;8U
Adder
22.333
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
13.148
962691AG1-118 GEN
Solar/Wind Harmer
26.273
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
17.379
971343AH1-151 GEN
Solar/Wind Harmer
17.379
247607V1-011 GEN
Solar/Wind Harmer
0
25194408D.CRK1
Adder
9.396
25194508D.CRK3
Adder
1.757
972235AH1-702 GEN1
Adder
3.131
972236AH1-702 GEN2
Adder
2.723
942111AE2-223 GEN
Solar/Wind Harmer
2.816
938861AE1-114 GEN
Solar/Wind Harmer
4.893
960611AF2-352 GEN
Solar/Wind Harmer
2.874
276645AC1-214 GEN1
Solar/Wind Harmer
0.338
274764LEE CO EC;5U
Adder
11.523
274765LEE CO EC;6U
Adder
11.523
274762LEE CO EC;3U
Adder
11.496
274763LEE CO EC;4U
Adder
11.388
945391AF1-204 GEN
Solar/Wind Harmer
9.138
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.387
252509AD1-136 GEN
Solar/Wind Harmer
0.043
276615X2-022 GEN
Solar/Wind Harmer
0.088
276838X2-022 GEN2
Solar/Wind Harmer
0.476
970623AG2-406 GEN
Solar/Wind Harmer
1.547
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.129
276916AD2-100_GEN
Solar/Wind Harmer
17.538
276911AD2-131_GEN
Solar/Wind Harmer
1.155
254304AE2-114 C
Solar/Wind Helper
0.274
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
241801AE1-079 GEN
Solar/Wind Helper
0.309
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
946071AF1-272 GEN
Solar/Wind Helper
2.879
203835AF1-098 GEN
Solar/Wind Helper
2.053
946381AF1-302 GEN
Solar/Wind Helper
0.237
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
203818AF1-086 GEN
Solar/Wind Helper
1.772
23585401KL_K28_T16
Solar/Wind Helper
1.267
203853AF1-134 C O1
Solar/Wind Helper
0.497
203804AE2-113_GEN
Solar/Wind Helper
1.84
23751201ROTHROCK
Solar/Wind Helper
0.733
203961AE2-224 GEN
Solar/Wind Helper
2.479
940863AE2-074 GEN
Solar/Wind Helper
0.479
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.672
203946AE2-131 C
Solar/Wind Helper
0.488
238117U2-030
Solar/Wind Helper
0.283
235531U2-073 GEN
Solar/Wind Helper
2.67
958861AF2-177 GEN
Solar/Wind Harmer
3.938
965011AG1-365 GEN
Solar/Wind Harmer
9.088
270055AF2-134 C O1
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
10.169
270032AE2-172
Solar/Wind Harmer
6.053
970373AG2-245 GEN
Solar/Wind Harmer
19.061
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
10.066
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
10.86
274774LINCOLN ;5U
Adder
10.86
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.955
970825AG2-519 GEN
Solar/Wind Harmer
3.175
270005AE1-210 C O1
Solar/Wind Harmer
1.936
274723RIVER EC ;12
Adder
22.929
274751CRETE EC ;1U
Adder
10.545
274754CRETE EC ;4U
Adder
10.545
274812UNIV PK N;8U
Adder
6.396
24639705ELKHART HY
Adder
0.196
965421AG1-410 GEN
Solar/Wind Harmer
26.684
274802UNIV PARK;5U
Adder
7.433
941551AE2-152 GEN
Solar/Wind Harmer
0.001
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.512
246936BC-WTG1
Solar/Wind Harmer
0.358
270489AE1-102 GEN1
Solar/Wind Harmer
1.154
274676JOLIET 29;8U
Adder
38.97
274732ELWOOD EC;7P
Adder
20.872
274674JOLIET 9 ;6U
Adder
19.549
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
20.916
957891AF2-083 GEN
Solar/Wind Harmer
14.717
274745AC1-111 GEN9
Adder
7.068
945111AF1-176 GEN
Solar/Wind Harmer
15.739
939401AE1-172 GEN
Solar/Wind Harmer
6.59
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.43
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.607
274828WAUKEGAN ;BP
Adder
13.888
276805AD2-038 GEN
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
1.548
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.573
971997AH1-543 GEN
Solar/Wind Harmer
4.591
276882AE2-255 GEN
Solar/Wind Harmer
1.021
962781AG1-127 GEN
Solar/Wind Harmer
8.326
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
26.068
959081AF2-199 GEN
Solar/Wind Harmer
8.689
971067AG2-660 GEN
Solar/Wind Harmer
2.896
970569AG2-363 GEN
Solar/Wind Harmer
26.052
274822ROCKFORD ;11
Adder
24.404
24728605AND G2
Adder
4.768
25194608D.CRK4
Adder
2.043
252516AE2-318_GEN
Solar/Wind Harmer
9.707
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.131
970819AG2-516 GEN
Solar/Wind Harmer
10.388
252510AF1-249 C
Solar/Wind Harmer
0.065
276646AC1-214 GEN2
Solar/Wind Harmer
0.338
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.496
274766LEE CO EC;7U
Adder
11.361
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.303
25196808ZIMRHP
Adder
93.029
25196008MFTGT1
Adder
1.696
276621W2-048 GEN
Solar/Wind Harmer
0.423
965911AG1-460 GEN
Solar/Wind Harmer
1.674
970091AG2-072 GEN
Adder
16.07
254303AC2-168 GEN
Solar/Wind Helper
0.198
241966AE1-183 GEN
Solar/Wind Helper
0.312
961971AG1-040 GEN
Solar/Wind Helper
0.519
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.485
964201AG1-281 GEN
Solar/Wind Helper
0.498
238185AF2-356 C
Solar/Wind Helper
2.178
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.055
203952AE2-129 C
Solar/Wind Helper
0.488
203855AF2-088 C
Solar/Wind Helper
0.158
238126S14_GEN_1
Solar/Wind Helper
0.662
238120AE2-309 GEN
Solar/Wind Helper
0.416
23751101LEADS_P59
Solar/Wind Helper
1.832
943121AE2-341 GEN
Solar/Wind Harmer
14.798
943591AF1-030 GEN
Solar/Wind Harmer
9.841
945111AF1-176 GEN
Solar/Wind Harmer
7.15
24695305TIMB G C
Solar/Wind Harmer
0.747
274862TOP CROP ;2U
Solar/Wind Harmer
1.188
274682WAUKEGAN ;7U
Adder
22.607
276868AE1-113 GEN
Solar/Wind Harmer
1.751
274879MINONK ;1U
Solar/Wind Harmer
0.365
946671AF1-331 GEN
Solar/Wind Harmer
0.929
274855GSG-6 ;RU
Solar/Wind Harmer
0.318
274850MENDOTA H;RU
Solar/Wind Harmer
0.101
25196608WSDLE5
Adder
10.674
959091AF2-200 GEN
Solar/Wind Harmer
17.379
970571AG2-364 GEN
Solar/Wind Harmer
17.368
24728505AND G1
Adder
4.768
25194608D.CRK4
Adder
2.043
252519AF1-045_GEN
Solar/Wind Harmer
4.521
965091AG1-374 GEN
Solar/Wind Harmer
25.867
959611AF2-252 GEN
Solar/Wind Harmer
2.874
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.496
274767LEE CO EC;8U
Adder
11.361
970193AG2-126 GEN
Solar/Wind Harmer
12.901
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
252507AC2-088 GEN
Solar/Wind Harmer
0.384
971993AH1-541 GEN
Solar/Wind Harmer
3.929
25196008MFTGT1
Adder
1.643
965931AG1-462 GEN
Solar/Wind Harmer
21.621
971087AG2-675 GEN
Solar/Wind Harmer
4.522
957381AF2-032 GEN
Solar/Wind Harmer
1.898
942481AE2-261 GEN
Solar/Wind Harmer
25.023
270367AC2-061_GEN
Solar/Wind Harmer
-0.001
235058AG1-386 C
Solar/Wind Helper
0.575
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
962511AG1-100 GEN
Solar/Wind Helper
0.518
202652Y1-033 WT C
Solar/Wind Helper
0.576
20092526R32
Solar/Wind Helper
1.21
964991AG1-363 GEN
Solar/Wind Helper
3.728
20303426NA_O38_P22
Solar/Wind Helper
1.017
23562501BACKB
Solar/Wind Helper
0.893
203993AD2-133_GEN1
Solar/Wind Helper
1.055
203854AF2-039 C
Solar/Wind Helper
0.327
20398826ARMNA MT
Solar/Wind Helper
1.511
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.259
958171AF2-111 GEN
Solar/Wind Harmer
13.887
CPLELTFEXP_CPLE->PJM
CLTF
2.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.056
NYPJM->LTFIMP_NY
CLTF
5.162
LGEELTFEXP_LGEE->PJM
CLTF
7.836
WECLTFEXP_WEC->PJM
CLTF
4.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.297
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.765
MECLTFEXP_MEC->PJM
CLTF
19.491
SIGELTFEXP_SIGE->PJM
CLTF
0.599
LAGNLTFEXP_LAGN->PJM
CLTF
17.61
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.111
TVALTFEXP_TVA->PJM
CLTF
8.46

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4309.27
MW Contribution:
4.9
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:92.06 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3813.12
MW Contribution:
3.85
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
3.319
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
9.821
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.932
945631AF1-228 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
5.259
943851AF1-053 GEN
Solar/Wind Harmer
3.643
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.888
241972AD1-140 GEN
Solar/Wind Harmer
1.272
270432AC2-029 GEN
Solar/Wind Harmer
5.04
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.43
959331AF2-224 GEN
Solar/Wind Harmer
7.844
247521TR3_G114
Solar/Wind Harmer
0.403
965051AG1-369 GEN
Solar/Wind Harmer
5.558
270071AF1-092 GEN
Solar/Wind Harmer
21.261
965041AG1-368 GEN
Solar/Wind Harmer
11.063
270007AE1-245 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
5.889
970179AG2-119 GEN
Solar/Wind Harmer
9.709
971771AH1-392 GEN
Solar/Wind Harmer
10.756
963791AG1-232 GEN
Solar/Wind Harmer
14.514
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
9.953
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.264
274775LINCOLN ;6U
Adder
12.619
274776LINCOLN ;7U
Adder
12.619
274777LINCOLN ;8U
Adder
12.619
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.956
972037AH1-567 GEN1
Adder
0.27
274827FISK ;RP
Adder
11.436
960591AF2-350 GEN
Solar/Wind Harmer
10.28
274800UNIV PARK;3U
Adder
8.587
274801UNIV PARK;4U
Adder
8.587
972228AH1-698 GEN2
Adder
5.454
972227AH1-698 GEN1
Adder
3.84
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
40.93
274687WILL CNTY;4U
Adder
40.93
274675JOLIET 29;7U
Adder
44.89
274675JOLIET 29;7U
Adder
43.287
274728ELWOOD EC;5P
Adder
24.024
274731ELWOOD EC;2P
Adder
24.024
274733ELWOOD EC;3P
Adder
24.024
274735ELWOOD EC;4P
Adder
24.024
970833AG2-524 GEN
Solar/Wind Harmer
11.198
970833AG2-524 GEN
Solar/Wind Harmer
7.465
270377AD1-106 GEN
Solar/Wind Harmer
3.864
971609AH1-304 GEN
Solar/Wind Harmer
1.657
971549AH1-272 GEN
Solar/Wind Harmer
20.903
274744AC1-111 GEN8
Adder
8.105
274746AC1-111 G10
Adder
8.105
253372AE2-315 SEC3
Adder
2.747
253372AE2-315 SEC3
Adder
2.747
24386405FR-21G C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.923
25306009OHH W.
Adder
4.15
247536S-71 GEN
Solar/Wind Harmer
0.4
970073AG2-061 GEN
Solar/Wind Harmer
3.33
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.303
270543AE2-219 C
Solar/Wind Harmer
6.944
971675AH1-338 GEN
Solar/Wind Harmer
3.854
971411AH1-196 GEN
Solar/Wind Harmer
14.823
276861AD2-134 GEN
Solar/Wind Harmer
0.176
276863AD2-134 GEN
Solar/Wind Harmer
0.176
970169AG2-114 GEN
Solar/Wind Harmer
9.859
971171AH1-044 GEN
Solar/Wind Harmer
19.677
971029AG2-637 GEN
Solar/Wind Harmer
14.756
274823ROCKFORD ;21
Adder
27.402
926823AC1-168 GEN
Solar/Wind Harmer
1.667
274856ECOGROVE ;U1
Solar/Wind Harmer
0.228
971681AH1-341 GEN
Solar/Wind Harmer
15.659
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.156
972267AH1-718 GEN
Adder
5.748
276741O09 GEN1
Solar/Wind Harmer
0.34
274877BISHOP HL;1U
Solar/Wind Harmer
0.321
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.283
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.365
276848AB2-070 GEN3
Solar/Wind Harmer
0.363
276849AB2-070 GEN2
Solar/Wind Harmer
0.365
270263AC1-001 GEN
Solar/Wind Harmer
0.924
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.684
25196408WSDLE3
Adder
10.931
25196108MFTGT2
Adder
1.832
25196108MFTGT2
Adder
1.701
23750501ELLIOTTS
Solar/Wind Helper
0.6
23652301WDPWR_K20
Solar/Wind Helper
0.129
23750701CROSSCHOOL
Solar/Wind Helper
1.119
238118U2-030_1
Solar/Wind Helper
0.267
203955AF1-039 C O1
Solar/Wind Helper
0.331
270119AB2-067 GEN1
50/50
17.244
270120AB2-067 GEN2
50/50
17.244
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
270166AC1-044 GEN3
50/50
17.244
24721705FLATG2
50/50
3.319
24721805FLATG3
50/50
3.319
962761AG1-125 GEN
Solar/Wind Harmer
73.48
970149AG2-104 GEN
Solar/Wind Harmer
39.681
970155AG2-107 GEN
Solar/Wind Harmer
46.922
270520AE2-214 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.014
971995AH1-542 GEN
Solar/Wind Harmer
4.575
246936BC-WTG1
Solar/Wind Harmer
0.455
270489AE1-102 GEN1
Solar/Wind Harmer
1.468
965421AG1-410 GEN
Solar/Wind Harmer
33.842
965011AG1-365 GEN
Solar/Wind Harmer
11.206
24639705ELKHART HY
Adder
0.237
957891AF2-083 GEN
Solar/Wind Harmer
17.821
945111AF1-176 GEN
Solar/Wind Harmer
19.076
970373AG2-245 GEN
Solar/Wind Harmer
22.382
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.553
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.746
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
13.152
965651AG1-433 GEN
Solar/Wind Harmer
3.072
274773LINCOLN ;4U
Adder
12.619
274774LINCOLN ;5U
Adder
12.619
958861AF2-177 GEN
Solar/Wind Harmer
4.506
274751CRETE EC ;1U
Adder
12.279
274754CRETE EC ;4U
Adder
12.279
270273AD2-016 GEN
Solar/Wind Harmer
1.064
274723RIVER EC ;12
Adder
26.668
270024AE2-089 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.423
25326309TAIT D
Adder
1.618
274802UNIV PARK;5U
Adder
8.599
945371AF1-202 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
44.89
270594AE1-207 GEN
Solar/Wind Harmer
11.433
270032AE2-172
Solar/Wind Harmer
6.805
274674JOLIET 9 ;6U
Adder
22.504
274732ELWOOD EC;7P
Adder
24.024
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
4.544
971201AH1-060 GEN
Solar/Wind Harmer
2.029
274745AC1-111 GEN9
Adder
8.105
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.636
274861TOP CROP ;1U
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
11.216
939401AE1-172 GEN
Solar/Wind Harmer
7.51
274682WAUKEGAN ;7U
Adder
25.826
274828WAUKEGAN ;BP
Adder
15.858
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.482
276882AE2-255 GEN
Solar/Wind Harmer
1.162
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.217
970825AG2-519 GEN
Solar/Wind Harmer
3.528
270005AE1-210 C O1
Solar/Wind Harmer
2.149
957471AF2-041 GEN
Solar/Wind Harmer
29.515
959081AF2-199 GEN
Solar/Wind Harmer
9.838
971067AG2-660 GEN
Solar/Wind Harmer
3.279
274822ROCKFORD ;11
Adder
27.602
970569AG2-363 GEN
Solar/Wind Harmer
29.408
970819AG2-516 GEN
Solar/Wind Harmer
11.727
963741AG1-226 GEN
Solar/Wind Harmer
23.101
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.93
274766LEE CO EC;7U
Adder
12.777
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.109
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
13.541
276646AC1-214 GEN2
Solar/Wind Harmer
0.379
276708O09 GEN2
Solar/Wind Harmer
0.34
274848CAMPGROVE;RU
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.647
24728605AND G2
Adder
5.071
276621W2-048 GEN
Solar/Wind Harmer
0.459
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.029
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.662
23906502RICHG2&3
Adder
1.439
25196808ZIMRHP
Adder
90.149
970091AG2-072 GEN
Adder
20.654
238185AF2-356 C
Solar/Wind Helper
2.037
23751101LEADS_P59
Solar/Wind Helper
1.839
238120AE2-309 GEN
Solar/Wind Helper
0.401
238126S14_GEN_1
Solar/Wind Helper
0.635
965911AG1-460 GEN
Solar/Wind Harmer
1.103
24721905FLATG4
50/50
3.319
24722005FLATG5
50/50
3.319
270051AF1-062 GEN
50/50
23.559
270475AD2-096_GEN
50/50
14.072
962771AG1-126 GEN
Solar/Wind Harmer
73.48
970153AG2-106 GEN
Solar/Wind Harmer
46.922
961921AG1-034 GEN
Solar/Wind Harmer
14.732
270284AF1-227 GEN1
Solar/Wind Harmer
0
270391AF1-285 GEN3
Solar/Wind Harmer
0.932
942051AE2-217 GEN
Solar/Wind Harmer
25.116
270518AE2-148 GEN
Solar/Wind Harmer
1.063
253325AC1-069 GEN
Solar/Wind Harmer
0.014
246938BC-WTG3
Solar/Wind Harmer
0.406
270491AE1-102 GEN2
Solar/Wind Harmer
1.468
965021AG1-366 GEN
Solar/Wind Harmer
3.735
270043AE2-236 GEN
Solar/Wind Harmer
7.125
24695305TIMB G C
Solar/Wind Harmer
0.934
971347AH1-153 GEN
Solar/Wind Harmer
5.488
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
48.343
971199AH1-059 GEN
Solar/Wind Harmer
2.255
270505AE1-170 C O1
Solar/Wind Harmer
11.228
945111AF1-176 GEN
Solar/Wind Harmer
8.665
964401AG1-302 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
8.236
274772LINCOLN ;3U
Adder
12.619
274752CRETE EC ;2U
Adder
12.279
274753CRETE EC ;3U
Adder
12.279
274724RIVER EC ;11
Adder
26.355
247642Z2-115 C
Solar/Wind Harmer
0.004
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.354
274814UNIV PK N;0U
Adder
7.488
274807UNIV PK N;3U
Adder
7.472
274811UNIV PK N;7U
Adder
7.423
970289AG2-191 GEN
Solar/Wind Harmer
1.133
274803UNIV PARK;6U
Adder
8.599
274826FISK ;BP
Adder
16.137
274887GEN-1.85
Solar/Wind Harmer
0.267
276843GEN-1.7
Solar/Wind Harmer
0.332
276806AD2-047 C O1
Solar/Wind Harmer
5.825
972038AH1-567 GEN2
Adder
0.538
970707AG2-453 GEN
Solar/Wind Harmer
33.528
972259AH1-714 GEN
Adder
28.051
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
43.287
274730ELWOOD EC;6P
Adder
24.024
274734ELWOOD EC;8P
Adder
24.024
274736ELWOOD EC;9P
Adder
24.024
274729ELWOOD EC;1P
Adder
24.024
970065AG2-057 GEN
Solar/Wind Harmer
1.014
943121AE2-341 GEN
Solar/Wind Harmer
16.972
943591AF1-030 GEN
Solar/Wind Harmer
11.286
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
24386205FR-12G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
2.597
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.132
274862TOP CROP ;2U
Solar/Wind Harmer
1.359
274682WAUKEGAN ;7U
Adder
25.826
276868AE1-113 GEN
Solar/Wind Harmer
1.991
274879MINONK ;1U
Solar/Wind Harmer
0.415
946031AF1-268 GEN
Solar/Wind Harmer
9.47
970825AG2-519 GEN
Solar/Wind Harmer
7.486
270004AE1-209 GEN
Solar/Wind Harmer
2.149
946671AF1-331 GEN
Solar/Wind Harmer
1.054
274855GSG-6 ;RU
Solar/Wind Harmer
0.361
274850MENDOTA H;RU
Solar/Wind Harmer
0.115
959091AF2-200 GEN
Solar/Wind Harmer
19.677
970571AG2-364 GEN
Solar/Wind Harmer
19.606
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.93
274767LEE CO EC;8U
Adder
12.777
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.321
965091AG1-374 GEN
Solar/Wind Harmer
28.713
959611AF2-252 GEN
Solar/Wind Harmer
3.19
253394AE2-221_GEN
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
23.963
971087AG2-675 GEN
Solar/Wind Harmer
5.012
971993AH1-541 GEN
Solar/Wind Harmer
4.285
24728505AND G1
Adder
5.071
970193AG2-126 GEN
Solar/Wind Harmer
13.784
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.737
270541AE2-072 C
Solar/Wind Harmer
0.001
957381AF2-032 GEN
Solar/Wind Harmer
2.038
25196608WSDLE5
Adder
10.619
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.61
23906502RICHG2&3
Adder
1.439
23906402RICHG1
Adder
1.437
237048AF1-022 C
Solar/Wind Helper
0.174
237046AF1-021 C
Solar/Wind Helper
0.304
964991AG1-363 GEN
Solar/Wind Helper
3.522
23562501BACKB
Solar/Wind Helper
0.847
235058AG1-386 C
Solar/Wind Helper
0.4
238127S14_GEN_2
Solar/Wind Helper
0.635
202652Y1-033 WT C
Solar/Wind Helper
0.501
942481AE2-261 GEN
Solar/Wind Harmer
16.491
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
10.655
270462AD2-086
Solar/Wind Harmer
0.002
938701AE1-092 GEN
Solar/Wind Harmer
21.46
971655AH1-328 GEN
Solar/Wind Harmer
4.742
970329AG2-216 GEN
Solar/Wind Harmer
5.083
25326509SID D
Adder
2.143
246937BC-WTG2
Solar/Wind Harmer
0.455
270246TR4_N_V150
Solar/Wind Harmer
0.071
270247TR4_N_V136
Solar/Wind Harmer
0.071
247607V1-011 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
16.464
247620Y3-023
Adder
0.71
965681AG1-436 GEN
Solar/Wind Harmer
13.426
965791AG1-447 GEN
Solar/Wind Harmer
9.845
970623AG2-406 GEN
Solar/Wind Harmer
1.96
961051AF2-396 GEN
Solar/Wind Harmer
21.315
961051AF2-396 GEN
Solar/Wind Harmer
14.21
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.994
942221AE2-234 GEN
Solar/Wind Harmer
4.232
944541AF1-119 GEN
Solar/Wind Harmer
0.7
960971AF2-388 GEN
Solar/Wind Harmer
6.145
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.914
944231AF1-091 GEN
Solar/Wind Harmer
24.097
274770LINCOLN ;1U
Adder
12.619
274771LINCOLN ;2U
Adder
12.619
270269AC2-059
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
7.439
274808UNIV PK N;4U
Adder
7.391
25322209TAIT E
Adder
14.396
25322209TAIT E
Adder
14.072
970291AG2-192 GEN
Solar/Wind Harmer
1.338
970291AG2-192 GEN
Solar/Wind Harmer
0.618
274888KELLY CRK;1U
Solar/Wind Harmer
0.6
276776AD2-060 GEN
Solar/Wind Harmer
1.097
958011AF2-095 GEN
Solar/Wind Harmer
14.803
970941AG2-585 GEN
Solar/Wind Harmer
5.654
276897AD1-100 C
Solar/Wind Harmer
25.624
971613AH1-306 GEN
Solar/Wind Harmer
4.9
274674JOLIET 9 ;6U
Adder
22.504
276893AG1-478 C
Solar/Wind Harmer
0.68
270031AE2-169
Solar/Wind Harmer
5.58
270599AE1-208 GEN
Solar/Wind Harmer
9.3
253370AE2-315 SEC1
Adder
2.904
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.147
270201AC2-176 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
15.103
247621Y3-024
Adder
0.348
964611AG1-324 GEN
Solar/Wind Harmer
0.754
274696ROCKY RD ;4P
Adder
16.391
274695ROCKY RD ;2P
Adder
16.014
274693ROCKY RD ;1P
Adder
15.856
274697ROCKY RD ;3P
Adder
4.35
274683WAUKEGAN ;8U
Adder
30.253
274683WAUKEGAN ;8U
Adder
25.502
958491AF2-143 GEN
Solar/Wind Harmer
14.984
962691AG1-118 GEN
Solar/Wind Harmer
29.945
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
9.92
970885AG2-551 GEN
Solar/Wind Harmer
3.307
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
19.677
971343AH1-151 GEN
Solar/Wind Harmer
19.677
972235AH1-702 GEN1
Adder
3.539
972236AH1-702 GEN2
Adder
3.077
270383AD1-128 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.694
938861AE1-114 GEN
Solar/Wind Harmer
5.51
274764LEE CO EC;5U
Adder
12.96
274765LEE CO EC;6U
Adder
12.96
274762LEE CO EC;3U
Adder
12.93
274763LEE CO EC;4U
Adder
12.808
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
3.143
276645AC1-214 GEN1
Solar/Wind Harmer
0.379
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.554
960611AF2-352 GEN
Solar/Wind Harmer
3.19
945391AF1-204 GEN
Solar/Wind Harmer
9.764
276615X2-022 GEN
Solar/Wind Harmer
0.095
276838X2-022 GEN2
Solar/Wind Harmer
0.516
25194408D.CRK1
Adder
9.313
25194508D.CRK3
Adder
1.741
972159AH1-661 GEN
Adder
1.225
23751201ROTHROCK
Solar/Wind Helper
0.691
23585401KL_K28_T16
Solar/Wind Helper
1.178
237043AE2-125 C
Solar/Wind Helper
0.16
235054AD2-180 GEN
Solar/Wind Helper
1.576
238117U2-030
Solar/Wind Helper
0.267
235531U2-073 GEN
Solar/Wind Helper
2.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
124.415
NYPJM->LTFIMP_NY
CLTF
4.821
LGEELTFEXP_LGEE->PJM
CLTF
7.242
WECLTFEXP_WEC->PJM
CLTF
5.355
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.468
AG2-052LTFEXP_AG2-052->PJM
LTF
0.342
AH1-155LTFEXP_AH1-155->PJM
LTF
0.513
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.5
MECLTFEXP_MEC->PJM
CLTF
20.741
SIGELTFEXP_SIGE->PJM
CLTF
0.579
LAGNLTFEXP_LAGN->PJM
CLTF
14.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
TVALTFEXP_TVA->PJM
CLTF
6.29

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.48 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4638.62
MW Contribution:
4.23
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
93.339
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970155AG2-107 GEN
Solar/Wind Harmer
59.604
957891AF2-083 GEN
Solar/Wind Harmer
17.358
970373AG2-245 GEN
Solar/Wind Harmer
21.825
945111AF1-176 GEN
Solar/Wind Harmer
18.541
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
274754CRETE EC ;4U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
7.225
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.154
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
28.375
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276708O09 GEN2
Solar/Wind Harmer
0.324
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.763
274848CAMPGROVE;RU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
963741AG1-226 GEN
Solar/Wind Harmer
21.176
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.571
276621W2-048 GEN
Solar/Wind Harmer
0.421
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
10.525
270526AF1-158 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274776LINCOLN ;7U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959331AF2-224 GEN
Solar/Wind Harmer
7.14
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
10.005
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
965041AG1-368 GEN
Solar/Wind Harmer
9.581
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
965051AG1-369 GEN
Solar/Wind Harmer
4.689
963791AG1-232 GEN
Solar/Wind Harmer
12.673
926823AC1-168 GEN
Solar/Wind Harmer
1.594
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
963841AG1-237 GEN
Solar/Wind Harmer
3.99
972267AH1-718 GEN
Adder
5.487
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
1.719
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
247536S-71 GEN
Solar/Wind Harmer
0.309
270543AE2-219 C
Solar/Wind Harmer
5.183
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.57
270356AE2-297 GEN
Solar/Wind Harmer
0
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274752CRETE EC ;2U
Adder
11.974
274753CRETE EC ;3U
Adder
11.974
274724RIVER EC ;11
Adder
25.717
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
276843GEN-1.7
Solar/Wind Harmer
0.323
276806AD2-047 C O1
Solar/Wind Harmer
5.669
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
44.295
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.86
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
24386205FR-12G C
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
18.917
970571AG2-364 GEN
Solar/Wind Harmer
18.75
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
246938BC-WTG3
Solar/Wind Harmer
0.328
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
0.995
965091AG1-374 GEN
Solar/Wind Harmer
26.927
959611AF2-252 GEN
Solar/Wind Harmer
2.992
965931AG1-462 GEN
Solar/Wind Harmer
22.694
971087AG2-675 GEN
Solar/Wind Harmer
4.746
971993AH1-541 GEN
Solar/Wind Harmer
3.947
957381AF2-032 GEN
Solar/Wind Harmer
1.851
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
270004AE1-209 GEN
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
6.118
946031AF1-268 GEN
Solar/Wind Harmer
7.675
970193AG2-126 GEN
Solar/Wind Harmer
12.093
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270541AE2-072 C
Solar/Wind Harmer
0
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.401
965681AG1-436 GEN
Solar/Wind Harmer
13.215
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
276776AD2-060 GEN
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
14.407
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.66
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
28.923
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
270246TR4_N_V150
Solar/Wind Harmer
0.06
270247TR4_N_V136
Solar/Wind Harmer
0.06
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.429
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
960611AF2-352 GEN
Solar/Wind Harmer
2.992
970241AG2-163 GEN
Solar/Wind Harmer
5.219
971613AH1-306 GEN
Solar/Wind Harmer
4.231
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
270031AE2-169
Solar/Wind Harmer
4.725
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
276838X2-022 GEN2
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276916AD2-100_GEN
Solar/Wind Harmer
16.976
276911AD2-131_GEN
Solar/Wind Harmer
1.118
945391AF1-204 GEN
Solar/Wind Harmer
8.566
247621Y3-024
Adder
0.274
926881AC1-175 GEN
Solar/Wind Harmer
0
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
970885AG2-551 GEN
Solar/Wind Harmer
2.468
971587AH1-292 GEN
Solar/Wind Harmer
5.199
270054AF2-122 C O1
Solar/Wind Helper
1.203
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.94 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4659.48
MW Contribution:
4.23
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
10.525
270526AF1-158 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.58
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274752CRETE EC ;2U
Adder
11.974
274753CRETE EC ;3U
Adder
11.974
274724RIVER EC ;11
Adder
25.717
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
93.339
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970155AG2-107 GEN
Solar/Wind Harmer
59.604
957891AF2-083 GEN
Solar/Wind Harmer
17.358
970373AG2-245 GEN
Solar/Wind Harmer
21.825
945111AF1-176 GEN
Solar/Wind Harmer
18.541
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
274754CRETE EC ;4U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
7.225
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.154
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
28.375
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276708O09 GEN2
Solar/Wind Harmer
0.324
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.763
274848CAMPGROVE;RU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
963741AG1-226 GEN
Solar/Wind Harmer
21.176
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.571
276621W2-048 GEN
Solar/Wind Harmer
0.421
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
274775LINCOLN ;6U
Adder
12.383
274776LINCOLN ;7U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959331AF2-224 GEN
Solar/Wind Harmer
7.14
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
10.005
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
965041AG1-368 GEN
Solar/Wind Harmer
9.581
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
965051AG1-369 GEN
Solar/Wind Harmer
4.689
963791AG1-232 GEN
Solar/Wind Harmer
12.673
926823AC1-168 GEN
Solar/Wind Harmer
1.594
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
963841AG1-237 GEN
Solar/Wind Harmer
3.99
972267AH1-718 GEN
Adder
5.487
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
1.719
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
247536S-71 GEN
Solar/Wind Harmer
0.309
270543AE2-219 C
Solar/Wind Harmer
5.183
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.57
270356AE2-297 GEN
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
276843GEN-1.7
Solar/Wind Harmer
0.323
276806AD2-047 C O1
Solar/Wind Harmer
5.669
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
44.295
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.86
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
24386205FR-12G C
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
18.917
970571AG2-364 GEN
Solar/Wind Harmer
18.75
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
246938BC-WTG3
Solar/Wind Harmer
0.328
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
0.995
965091AG1-374 GEN
Solar/Wind Harmer
26.927
959611AF2-252 GEN
Solar/Wind Harmer
2.992
965931AG1-462 GEN
Solar/Wind Harmer
22.694
971087AG2-675 GEN
Solar/Wind Harmer
4.746
971993AH1-541 GEN
Solar/Wind Harmer
3.947
957381AF2-032 GEN
Solar/Wind Harmer
1.851
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
270004AE1-209 GEN
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
6.118
946031AF1-268 GEN
Solar/Wind Harmer
7.675
970193AG2-126 GEN
Solar/Wind Harmer
12.093
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270541AE2-072 C
Solar/Wind Harmer
0
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.401
965681AG1-436 GEN
Solar/Wind Harmer
13.215
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
276776AD2-060 GEN
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
14.407
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.66
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
28.923
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
270246TR4_N_V150
Solar/Wind Harmer
0.06
270247TR4_N_V136
Solar/Wind Harmer
0.06
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.429
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
960611AF2-352 GEN
Solar/Wind Harmer
2.992
970241AG2-163 GEN
Solar/Wind Harmer
5.219
971613AH1-306 GEN
Solar/Wind Harmer
4.231
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
270031AE2-169
Solar/Wind Harmer
4.725
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
276838X2-022 GEN2
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276916AD2-100_GEN
Solar/Wind Harmer
16.976
276911AD2-131_GEN
Solar/Wind Harmer
1.118
945391AF1-204 GEN
Solar/Wind Harmer
8.566
247621Y3-024
Adder
0.274
926881AC1-175 GEN
Solar/Wind Harmer
0
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
970885AG2-551 GEN
Solar/Wind Harmer
2.468
971587AH1-292 GEN
Solar/Wind Harmer
5.199
270054AF2-122 C O1
Solar/Wind Helper
1.203
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.92 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5008.41
MW Contribution:
4.61
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
15.733
270143AC1-141 CT2_
50/50
4.53
24639705ELKHART HY
50/50
0.302
274773LINCOLN ;4U
50/50
16.554
274774LINCOLN ;5U
50/50
16.554
970521AG2-332 GEN
50/50
21.475
24307105BERRINSP G
50/50
0.04
957891AF2-083 GEN
Solar/Wind Harmer
21.685
945111AF1-176 GEN
Solar/Wind Harmer
23.109
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.729
274723RIVER EC ;12
Adder
32.481
274751CRETE EC ;1U
Adder
14.913
274754CRETE EC ;4U
Adder
14.913
274812UNIV PK N;8U
Adder
9.011
274802UNIV PARK;5U
Adder
10.432
970373AG2-245 GEN
Solar/Wind Harmer
26.204
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
54.332
274674JOLIET 9 ;6U
Adder
27.209
274732ELWOOD EC;7P
Adder
29.026
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.782
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.958
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
30.998
274828WAUKEGAN ;BP
Adder
19.024
958381AF2-132 GEN
Solar/Wind Harmer
0.002
962781AG1-127 GEN
Solar/Wind Harmer
11.346
939401AE1-172 GEN
Solar/Wind Harmer
8.909
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
15.475
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.379
971997AH1-543 GEN
Solar/Wind Harmer
6.189
957471AF2-041 GEN
Solar/Wind Harmer
35.035
959081AF2-199 GEN
Solar/Wind Harmer
11.678
971067AG2-660 GEN
Solar/Wind Harmer
3.893
274822ROCKFORD ;11
Adder
32.73
965011AG1-365 GEN
Solar/Wind Harmer
11.618
970819AG2-516 GEN
Solar/Wind Harmer
13.872
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
14.433
970569AG2-363 GEN
Solar/Wind Harmer
34.504
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
15.212
274766LEE CO EC;7U
Adder
15.033
965651AG1-433 GEN
Solar/Wind Harmer
3.328
276708O09 GEN2
Solar/Wind Harmer
0.397
276646AC1-214 GEN2
Solar/Wind Harmer
0.44
274848CAMPGROVE;RU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.79
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
15.389
945371AF1-202 GEN
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.492
963741AG1-226 GEN
Solar/Wind Harmer
23.2
270594AE1-207 GEN
Solar/Wind Harmer
10.763
270032AE2-172
Solar/Wind Harmer
6.407
270024AE2-089 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.887
276903AD2-071 C
Solar/Wind Harmer
10.328
270005AE1-210 C O1
Solar/Wind Harmer
1.995
970825AG2-519 GEN
Solar/Wind Harmer
3.188
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.023
24728605AND G2
Adder
4.166
965421AG1-410 GEN
Solar/Wind Harmer
22.186
246936BC-WTG1
Solar/Wind Harmer
0.28
270489AE1-102 GEN1
Solar/Wind Harmer
0.903
970773AG2-487 GEN
Solar/Wind Harmer
1.206
970091AG2-072 GEN
Adder
67.129
270520AE2-214 GEN
Solar/Wind Helper
2.6
270286AF1-227 GEN2
Solar/Wind Helper
0.817
270142AC1-141 CT1_
50/50
4.53
24642205MAYFLWER
50/50
0.069
274772LINCOLN ;3U
50/50
16.554
944961AF1-161 GEN
50/50
5.371
962601AG1-109 GEN
50/50
5.371
971347AH1-153 GEN
Solar/Wind Harmer
7.007
270043AE2-236 GEN
Solar/Wind Harmer
8.609
270505AE1-170 C O1
Solar/Wind Harmer
13.688
945111AF1-176 GEN
Solar/Wind Harmer
10.497
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
32.107
274752CRETE EC ;2U
Adder
14.913
274753CRETE EC ;3U
Adder
14.913
274814UNIV PK N;0U
Adder
9.09
274807UNIV PK N;3U
Adder
9.07
274811UNIV PK N;7U
Adder
9.011
944531AF1-118 GEN
Solar/Wind Harmer
56.246
970707AG2-453 GEN
Solar/Wind Harmer
40.893
274803UNIV PARK;6U
Adder
10.432
274826FISK ;BP
Adder
19.587
274887GEN-1.85
Solar/Wind Harmer
0.324
276843GEN-1.7
Solar/Wind Harmer
0.403
276806AD2-047 C O1
Solar/Wind Harmer
7.069
972259AH1-714 GEN
Adder
34.103
972038AH1-567 GEN2
Adder
0.652
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
52.392
274730ELWOOD EC;6P
Adder
29.026
274734ELWOOD EC;8P
Adder
29.026
274736ELWOOD EC;9P
Adder
29.026
274729ELWOOD EC;1P
Adder
29.025
943121AE2-341 GEN
Solar/Wind Harmer
20.51
943591AF1-030 GEN
Solar/Wind Harmer
13.64
274862TOP CROP ;2U
Solar/Wind Harmer
1.626
274682WAUKEGAN ;7U
Adder
30.998
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
2.364
274879MINONK ;1U
Solar/Wind Harmer
0.493
946671AF1-331 GEN
Solar/Wind Harmer
1.255
274855GSG-6 ;RU
Solar/Wind Harmer
0.429
274850MENDOTA H;RU
Solar/Wind Harmer
0.137
959091AF2-200 GEN
Solar/Wind Harmer
23.357
965021AG1-366 GEN
Solar/Wind Harmer
3.873
970571AG2-364 GEN
Solar/Wind Harmer
23.003
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
15.212
274767LEE CO EC;8U
Adder
15.033
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.946
965931AG1-462 GEN
Solar/Wind Harmer
27.64
971087AG2-675 GEN
Solar/Wind Harmer
5.781
965091AG1-374 GEN
Solar/Wind Harmer
32.301
959611AF2-252 GEN
Solar/Wind Harmer
3.589
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
4.642
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.081
957381AF2-032 GEN
Solar/Wind Harmer
2.147
942481AE2-261 GEN
Solar/Wind Harmer
28.217
270004AE1-209 GEN
Solar/Wind Harmer
1.995
970825AG2-519 GEN
Solar/Wind Harmer
6.765
946031AF1-268 GEN
Solar/Wind Harmer
8.435
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.208
24695305TIMB G C
Solar/Wind Harmer
0.74
970193AG2-126 GEN
Solar/Wind Harmer
13.057
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.166
246938BC-WTG3
Solar/Wind Harmer
0.25
270491AE1-102 GEN2
Solar/Wind Harmer
0.903
270284AF1-227 GEN1
Solar/Wind Helper
2.228
270287AF1-227 GEN3
Solar/Wind Helper
0.817
24344005CKG1
50/50
12.247
270144AC1-141 ST1_
50/50
4.015
24641605TWIN BRNCH
50/50
0.032
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
16.554
274776LINCOLN ;7U
50/50
16.554
274777LINCOLN ;8U
50/50
16.554
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
13.194
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
24.953
970031AG2-029 GEN
Solar/Wind Harmer
6.772
972037AH1-567 GEN1
Adder
0.327
274827FISK ;RP
Adder
13.882
960591AF2-350 GEN
Solar/Wind Harmer
12.474
274800UNIV PARK;3U
Adder
10.418
274801UNIV PARK;4U
Adder
10.418
972228AH1-698 GEN2
Adder
6.619
972227AH1-698 GEN1
Adder
4.661
274687WILL CNTY;4U
Adder
49.553
274687WILL CNTY;4U
Adder
49.553
274675JOLIET 29;7U
Adder
54.333
274675JOLIET 29;7U
Adder
52.393
274728ELWOOD EC;5P
Adder
29.026
274731ELWOOD EC;2P
Adder
29.025
274733ELWOOD EC;3P
Adder
29.025
274735ELWOOD EC;4P
Adder
29.025
970833AG2-524 GEN
Solar/Wind Harmer
13.528
970833AG2-524 GEN
Solar/Wind Harmer
9.019
24729505KEY G4
Adder
11.373
274744AC1-111 GEN8
Adder
9.782
274746AC1-111 G10
Adder
9.782
970073AG2-061 GEN
Solar/Wind Harmer
3.962
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971411AH1-196 GEN
Solar/Wind Harmer
17.649
971675AH1-338 GEN
Solar/Wind Harmer
4.588
276861AD2-134 GEN
Solar/Wind Harmer
0.21
276863AD2-134 GEN
Solar/Wind Harmer
0.21
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
23.357
971549AH1-272 GEN
Solar/Wind Harmer
24.093
274823ROCKFORD ;21
Adder
32.492
959331AF2-224 GEN
Solar/Wind Harmer
8.133
971611AH1-305 GEN
Solar/Wind Harmer
6.874
274856ECOGROVE ;U1
Solar/Wind Harmer
0.27
926823AC1-168 GEN
Solar/Wind Harmer
1.955
970169AG2-114 GEN
Solar/Wind Harmer
11.475
971681AH1-341 GEN
Solar/Wind Harmer
18.454
972267AH1-718 GEN
Adder
6.732
276741O09 GEN1
Solar/Wind Harmer
0.397
274877BISHOP HL;1U
Solar/Wind Harmer
0.372
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
11.542
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.109
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
14.195
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.388
276668AB2-070 GEN1
Solar/Wind Harmer
0.395
276848AB2-070 GEN3
Solar/Wind Harmer
0.393
276849AB2-070 GEN2
Solar/Wind Harmer
0.395
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
9.911
970289AG2-191 GEN
Solar/Wind Harmer
1.868
971609AH1-304 GEN
Solar/Wind Harmer
1.601
247521TR3_G114
Solar/Wind Harmer
0.327
965051AG1-369 GEN
Solar/Wind Harmer
4.503
944221AF1-090 GEN
Solar/Wind Harmer
5.281
964611AG1-324 GEN
Solar/Wind Harmer
3.439
247536S-71 GEN
Solar/Wind Harmer
0.321
270543AE2-219 C
Solar/Wind Harmer
5.19
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.88
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.12
270102X2-052 ST
50/50
3.058
270100X2-052 CT1
50/50
2.825
270101X2-052 CT2
50/50
2.825
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
16.554
274771LINCOLN ;2U
50/50
16.554
247620Y3-023
50/50
0.898
970349AG2-230 GEN
Solar/Wind Harmer
21.02
965681AG1-436 GEN
Solar/Wind Harmer
16.554
965791AG1-447 GEN
Solar/Wind Harmer
12.14
961051AF2-396 GEN
Solar/Wind Harmer
25.827
961051AF2-396 GEN
Solar/Wind Harmer
17.218
274805UNIV PK N;1U
Adder
9.031
274808UNIV PK N;4U
Adder
8.972
274888KELLY CRK;1U
Solar/Wind Harmer
0.727
276776AD2-060 GEN
Solar/Wind Harmer
1.331
958011AF2-095 GEN
Solar/Wind Harmer
17.963
970941AG2-585 GEN
Solar/Wind Harmer
6.861
276897AD1-100 C
Solar/Wind Harmer
31.049
274674JOLIET 9 ;6U
Adder
27.209
276893AG1-478 C
Solar/Wind Harmer
0.821
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274695ROCKY RD ;2P
Adder
19.235
274693ROCKY RD ;1P
Adder
19.046
274697ROCKY RD ;3P
Adder
5.225
274696ROCKY RD ;4P
Adder
19.689
958481AF2-142 GEN
Solar/Wind Harmer
18.073
274683WAUKEGAN ;8U
Adder
36.293
274683WAUKEGAN ;8U
Adder
30.593
962691AG1-118 GEN
Solar/Wind Harmer
35.867
958491AF2-143 GEN
Solar/Wind Harmer
17.827
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
23.357
971343AH1-151 GEN
Solar/Wind Harmer
23.357
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
4.192
972236AH1-702 GEN2
Adder
3.645
938861AE1-114 GEN
Solar/Wind Harmer
6.492
274764LEE CO EC;5U
Adder
15.248
274765LEE CO EC;6U
Adder
15.248
274762LEE CO EC;3U
Adder
15.212
274763LEE CO EC;4U
Adder
15.069
944541AF1-119 GEN
Solar/Wind Harmer
0.758
960971AF2-388 GEN
Solar/Wind Harmer
6.656
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.814
276645AC1-214 GEN1
Solar/Wind Harmer
0.44
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
3.572
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
3.589
942221AE2-234 GEN
Solar/Wind Harmer
4.268
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.188
944231AF1-091 GEN
Solar/Wind Harmer
23.789
276615X2-022 GEN
Solar/Wind Harmer
0.102
276838X2-022 GEN2
Solar/Wind Harmer
0.554
970291AG2-192 GEN
Solar/Wind Harmer
1.278
970291AG2-192 GEN
Solar/Wind Harmer
0.59
970241AG2-163 GEN
Solar/Wind Harmer
5.718
270031AE2-169
Solar/Wind Harmer
5.389
270599AE1-208 GEN
Solar/Wind Harmer
8.982
971613AH1-306 GEN
Solar/Wind Harmer
4.613
276916AD2-100_GEN
Solar/Wind Harmer
19.611
276911AD2-131_GEN
Solar/Wind Harmer
1.292
270246TR4_N_V150
Solar/Wind Harmer
0.058
270247TR4_N_V136
Solar/Wind Harmer
0.058
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.661
270201AC2-176 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
9.248
247621Y3-024
Adder
0.288
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.371
970883AG2-550 GEN
Solar/Wind Harmer
7.415
970885AG2-551 GEN
Solar/Wind Harmer
2.472
971587AH1-292 GEN
Solar/Wind Harmer
5.408
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.28
270349AD2-093_GEN
Solar/Wind Helper
1.835
270471AD2-092_GEN
Solar/Wind Helper
1.835
946101AF1-275 GEN
Solar/Wind Helper
0.65
270054AF2-122 C O1
Solar/Wind Helper
1.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.518
NYPJM->LTFIMP_NY
CLTF
2.831
LGEELTFEXP_LGEE->PJM
CLTF
3.802
WECLTFEXP_WEC->PJM
CLTF
6.34
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.778
AG2-052LTFEXP_AG2-052->PJM
LTF
0.395
AH1-155LTFEXP_AH1-155->PJM
LTF
0.593
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.577
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.817
MECLTFEXP_MEC->PJM
CLTF
22.833
SIGELTFEXP_SIGE->PJM
CLTF
0.424
LAGNLTFEXP_LAGN->PJM
CLTF
12.121
TVALTFEXP_TVA->PJM
CLTF
4.571

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#9287_1679_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#9287_1679_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.12 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4271.28
MW Contribution:
3.1
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
17.101
270143AC1-141 CT2_
50/50
4.628
274773LINCOLN ;4U
50/50
16.742
274774LINCOLN ;5U
50/50
16.742
24307105BERRINSP G
50/50
0.04
24639705ELKHART HY
50/50
0.302
247604X1-042
50/50
0.044
970521AG2-332 GEN
50/50
21.337
957891AF2-083 GEN
Solar/Wind Harmer
21.973
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.836
945111AF1-176 GEN
Solar/Wind Harmer
23.345
274723RIVER EC ;12
Adder
32.119
274751CRETE EC ;1U
Adder
14.651
274754CRETE EC ;4U
Adder
14.651
274812UNIV PK N;8U
Adder
8.876
274802UNIV PARK;5U
Adder
10.298
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.66
274674JOLIET 9 ;6U
Adder
26.849
274732ELWOOD EC;7P
Adder
28.611
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.659
274682WAUKEGAN ;7U
Adder
30.457
274828WAUKEGAN ;BP
Adder
18.685
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.913
274861TOP CROP ;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
11.128
274872LEEDK;1U
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
11.556
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
8.623
276882AE2-255 GEN
Solar/Wind Harmer
1.339
971997AH1-543 GEN
Solar/Wind Harmer
6.007
957471AF2-041 GEN
Solar/Wind Harmer
34.131
959081AF2-199 GEN
Solar/Wind Harmer
11.377
971067AG2-660 GEN
Solar/Wind Harmer
3.792
274822ROCKFORD ;11
Adder
31.861
970819AG2-516 GEN
Solar/Wind Harmer
13.478
970569AG2-363 GEN
Solar/Wind Harmer
33.131
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
14.712
274766LEE CO EC;7U
Adder
14.538
276708O09 GEN2
Solar/Wind Harmer
0.381
970373AG2-245 GEN
Solar/Wind Harmer
22.393
276646AC1-214 GEN2
Solar/Wind Harmer
0.418
965651AG1-433 GEN
Solar/Wind Harmer
3.089
274848CAMPGROVE;RU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.409
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
14.202
270055AF2-134 C O1
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.626
276621W2-048 GEN
Solar/Wind Harmer
0.426
270024AE2-089 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.598
270005AE1-210 C O1
Solar/Wind Harmer
1.716
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
9.838
965421AG1-410 GEN
Solar/Wind Harmer
22.84
970825AG2-519 GEN
Solar/Wind Harmer
2.631
246936BC-WTG1
Solar/Wind Harmer
0.29
270489AE1-102 GEN1
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.078
270594AE1-207 GEN
Solar/Wind Harmer
7.228
270032AE2-172
Solar/Wind Harmer
4.303
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
6.868
963741AG1-226 GEN
Solar/Wind Harmer
14.404
270142AC1-141 CT1_
50/50
4.628
24642205MAYFLWER
50/50
0.07
944961AF1-161 GEN
50/50
5.457
962601AG1-109 GEN
50/50
5.457
274772LINCOLN ;3U
50/50
16.742
971347AH1-153 GEN
Solar/Wind Harmer
7.293
270505AE1-170 C O1
Solar/Wind Harmer
13.912
945111AF1-176 GEN
Solar/Wind Harmer
10.605
270043AE2-236 GEN
Solar/Wind Harmer
8.283
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
31.767
970707AG2-453 GEN
Solar/Wind Harmer
40.791
274752CRETE EC ;2U
Adder
14.651
274753CRETE EC ;3U
Adder
14.651
972259AH1-714 GEN
Adder
33.857
274814UNIV PK N;0U
Adder
8.953
274807UNIV PK N;3U
Adder
8.934
274811UNIV PK N;7U
Adder
8.876
274826FISK ;BP
Adder
19.361
274887GEN-1.85
Solar/Wind Harmer
0.321
276843GEN-1.7
Solar/Wind Harmer
0.399
276806AD2-047 C O1
Solar/Wind Harmer
6.988
274803UNIV PARK;6U
Adder
10.298
972038AH1-567 GEN2
Adder
0.644
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
51.744
274729ELWOOD EC;1P
Adder
28.61
274730ELWOOD EC;6P
Adder
28.611
274734ELWOOD EC;8P
Adder
28.611
274736ELWOOD EC;9P
Adder
28.611
943121AE2-341 GEN
Solar/Wind Harmer
20.29
943591AF1-030 GEN
Solar/Wind Harmer
13.493
944531AF1-118 GEN
Solar/Wind Harmer
53.775
274682WAUKEGAN ;7U
Adder
30.457
274862TOP CROP ;2U
Solar/Wind Harmer
1.588
965021AG1-366 GEN
Solar/Wind Harmer
3.852
946671AF1-331 GEN
Solar/Wind Harmer
1.226
274855GSG-6 ;RU
Solar/Wind Harmer
0.419
274850MENDOTA H;RU
Solar/Wind Harmer
0.133
276868AE1-113 GEN
Solar/Wind Harmer
2.296
274879MINONK ;1U
Solar/Wind Harmer
0.479
959091AF2-200 GEN
Solar/Wind Harmer
22.754
970571AG2-364 GEN
Solar/Wind Harmer
22.087
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
14.712
274767LEE CO EC;8U
Adder
14.538
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.353
965931AG1-462 GEN
Solar/Wind Harmer
26.286
971087AG2-675 GEN
Solar/Wind Harmer
5.498
965091AG1-374 GEN
Solar/Wind Harmer
29.5
959611AF2-252 GEN
Solar/Wind Harmer
3.278
964401AG1-302 GEN
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.055
24695305TIMB G C
Solar/Wind Harmer
0.742
957381AF2-032 GEN
Solar/Wind Harmer
1.822
942481AE2-261 GEN
Solar/Wind Harmer
23.884
270004AE1-209 GEN
Solar/Wind Harmer
1.716
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.272
946031AF1-268 GEN
Solar/Wind Harmer
7.057
970825AG2-519 GEN
Solar/Wind Harmer
5.584
246938BC-WTG3
Solar/Wind Harmer
0.259
270491AE1-102 GEN2
Solar/Wind Harmer
0.935
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.599
24386205FR-12G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.679
24344005CKG1
50/50
12.668
270144AC1-141 ST1_
50/50
4.102
24641605TWIN BRNCH
50/50
0.033
274775LINCOLN ;6U
50/50
16.742
274776LINCOLN ;7U
50/50
16.742
274777LINCOLN ;8U
50/50
16.742
24653605MOTTVILLE
50/50
0.007
971771AH1-392 GEN
Solar/Wind Harmer
13.283
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274827FISK ;RP
Adder
13.721
972228AH1-698 GEN2
Adder
6.549
972227AH1-698 GEN1
Adder
4.611
960591AF2-350 GEN
Solar/Wind Harmer
12.332
972037AH1-567 GEN1
Adder
0.323
274800UNIV PARK;3U
Adder
10.294
274801UNIV PARK;4U
Adder
10.294
274687WILL CNTY;4U
Adder
48.934
274687WILL CNTY;4U
Adder
48.934
274675JOLIET 29;7U
Adder
53.662
274675JOLIET 29;7U
Adder
51.745
274728ELWOOD EC;5P
Adder
28.611
274731ELWOOD EC;2P
Adder
28.61
274733ELWOOD EC;3P
Adder
28.61
274735ELWOOD EC;4P
Adder
28.61
970833AG2-524 GEN
Solar/Wind Harmer
13.35
970833AG2-524 GEN
Solar/Wind Harmer
8.9
274744AC1-111 GEN8
Adder
9.659
274746AC1-111 G10
Adder
9.659
970031AG2-029 GEN
Solar/Wind Harmer
6.498
971549AH1-272 GEN
Solar/Wind Harmer
24.686
24729505KEY G4
Adder
10.795
959331AF2-224 GEN
Solar/Wind Harmer
8.089
970073AG2-061 GEN
Solar/Wind Harmer
3.851
971411AH1-196 GEN
Solar/Wind Harmer
17.237
971675AH1-338 GEN
Solar/Wind Harmer
4.48
276861AD2-134 GEN
Solar/Wind Harmer
0.205
276863AD2-134 GEN
Solar/Wind Harmer
0.205
971171AH1-044 GEN
Solar/Wind Harmer
22.754
274823ROCKFORD ;21
Adder
31.63
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.262
971681AH1-341 GEN
Solar/Wind Harmer
17.867
926823AC1-168 GEN
Solar/Wind Harmer
1.875
270071AF1-092 GEN
Solar/Wind Harmer
21.116
970169AG2-114 GEN
Solar/Wind Harmer
10.885
972267AH1-718 GEN
Adder
6.485
276741O09 GEN1
Solar/Wind Harmer
0.381
274877BISHOP HL;1U
Solar/Wind Harmer
0.353
946321AF1-296 GEN
Solar/Wind Harmer
5.822
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.652
963791AG1-232 GEN
Solar/Wind Harmer
13.422
965041AG1-368 GEN
Solar/Wind Harmer
9.865
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.327
965051AG1-369 GEN
Solar/Wind Harmer
4.508
276668AB2-070 GEN1
Solar/Wind Harmer
0.345
276848AB2-070 GEN3
Solar/Wind Harmer
0.343
276849AB2-070 GEN2
Solar/Wind Harmer
0.345
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.357
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.686
964611AG1-324 GEN
Solar/Wind Harmer
2.923
944221AF1-090 GEN
Solar/Wind Harmer
4.332
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.911
270007AE1-245 C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.271
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.694
270543AE2-219 C
Solar/Wind Harmer
4.339
970289AG2-191 GEN
Solar/Wind Harmer
1.173
270102X2-052 ST
50/50
3.04
270100X2-052 CT1
50/50
2.808
270101X2-052 CT2
50/50
2.808
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
16.742
274771LINCOLN ;2U
50/50
16.742
247620Y3-023
50/50
0.894
970349AG2-230 GEN
Solar/Wind Harmer
21.879
965681AG1-436 GEN
Solar/Wind Harmer
16.375
965791AG1-447 GEN
Solar/Wind Harmer
12.008
961051AF2-396 GEN
Solar/Wind Harmer
26.182
961051AF2-396 GEN
Solar/Wind Harmer
17.455
274805UNIV PK N;1U
Adder
8.895
274808UNIV PK N;4U
Adder
8.837
274888KELLY CRK;1U
Solar/Wind Harmer
0.719
276776AD2-060 GEN
Solar/Wind Harmer
1.315
958011AF2-095 GEN
Solar/Wind Harmer
17.758
970941AG2-585 GEN
Solar/Wind Harmer
6.782
276897AD1-100 C
Solar/Wind Harmer
30.703
274674JOLIET 9 ;6U
Adder
26.849
276893AG1-478 C
Solar/Wind Harmer
0.809
274695ROCKY RD ;2P
Adder
18.919
274693ROCKY RD ;1P
Adder
18.733
274697ROCKY RD ;3P
Adder
5.139
274696ROCKY RD ;4P
Adder
19.364
274683WAUKEGAN ;8U
Adder
35.646
274683WAUKEGAN ;8U
Adder
30.048
958481AF2-142 GEN
Solar/Wind Harmer
17.657
962691AG1-118 GEN
Solar/Wind Harmer
35.208
958491AF2-143 GEN
Solar/Wind Harmer
17.33
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
22.754
971343AH1-151 GEN
Solar/Wind Harmer
22.754
972235AH1-702 GEN1
Adder
4.077
972236AH1-702 GEN2
Adder
3.545
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
6.286
274764LEE CO EC;5U
Adder
14.746
274765LEE CO EC;6U
Adder
14.746
274762LEE CO EC;3U
Adder
14.712
274763LEE CO EC;4U
Adder
14.573
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.741
276645AC1-214 GEN1
Solar/Wind Harmer
0.418
944541AF1-119 GEN
Solar/Wind Harmer
0.704
960971AF2-388 GEN
Solar/Wind Harmer
6.177
944231AF1-091 GEN
Solar/Wind Harmer
23.61
942111AE2-223 GEN
Solar/Wind Harmer
3.297
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
3.278
942221AE2-234 GEN
Solar/Wind Harmer
3.817
270246TR4_N_V150
Solar/Wind Harmer
0.058
270247TR4_N_V136
Solar/Wind Harmer
0.058
276615X2-022 GEN
Solar/Wind Harmer
0.088
276838X2-022 GEN2
Solar/Wind Harmer
0.479
270031AE2-169
Solar/Wind Harmer
4.571
270599AE1-208 GEN
Solar/Wind Harmer
7.618
276916AD2-100_GEN
Solar/Wind Harmer
16.489
276911AD2-131_GEN
Solar/Wind Harmer
1.086
970623AG2-406 GEN
Solar/Wind Harmer
1.389
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.562
246937BC-WTG2
Solar/Wind Harmer
0.29
247607V1-011 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.098
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.721
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
6.198
970885AG2-551 GEN
Solar/Wind Harmer
2.066
970291AG2-192 GEN
Solar/Wind Harmer
0.802
970291AG2-192 GEN
Solar/Wind Harmer
0.37
970241AG2-163 GEN
Solar/Wind Harmer
3.55
270349AD2-093_GEN
Solar/Wind Helper
1.46
270471AD2-092_GEN
Solar/Wind Helper
1.46
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.536
NYPJM->LTFIMP_NY
CLTF
2.551
LGEELTFEXP_LGEE->PJM
CLTF
1.869
WECLTFEXP_WEC->PJM
CLTF
6.165
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.118
AG2-052LTFEXP_AG2-052->PJM
LTF
0.357
AH1-155LTFEXP_AH1-155->PJM
LTF
0.535
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
184.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.09
MECLTFEXP_MEC->PJM
CLTF
20.956
SIGELTFEXP_SIGE->PJM
CLTF
0.265
LAGNLTFEXP_LAGN->PJM
CLTF
9.08
TVALTFEXP_TVA->PJM
CLTF
3.004

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1280.85
MW Contribution:
1.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.63 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1362.91
MW Contribution:
1.81
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.172
24802706KYGER 1LP
50/50
2.446
24803506KYGER 5LP
50/50
2.389
971985AH1-537 GEN
Solar/Wind Harmer
5.716
25196408WSDLE3
Adder
8.602
25196108MFTGT2
Adder
1.414
25196108MFTGT2
Adder
1.313
972163AH1-664 GEN
Solar/Wind Harmer
6.737
972165AH1-665 GEN
Solar/Wind Harmer
5.396
253406AD2-031_GEN
Solar/Wind Harmer
0.443
270263AC1-001 GEN
Solar/Wind Harmer
0.582
270340AC2-060 GEN
Solar/Wind Harmer
0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.154
253372AE2-315 SEC3
Adder
1.444
253372AE2-315 SEC3
Adder
1.444
25306009OHH W.
Adder
2.154
3429211JKCT 2G
Adder
8.179
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.01
971029AG2-637 GEN
Solar/Wind Harmer
6.48
241972AD1-140 GEN
Solar/Wind Harmer
0.472
270543AE2-219 C
Solar/Wind Harmer
2.892
247536S-71 GEN
Solar/Wind Harmer
0.158
964611AG1-324 GEN
Solar/Wind Harmer
1.472
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.584
970289AG2-191 GEN
Solar/Wind Harmer
0.636
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
2.909
24803006KYGER 3HP
50/50
4.142
24802806KYGER 2HP
50/50
4.127
24802906KYGER 2LP
50/50
2.422
25183008BIOENL
50/50
0.029
252509AD1-136 GEN
Solar/Wind Harmer
0.038
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.38
25194508D.CRK3
Adder
1.38
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.433
972045AH1-571 GEN
Solar/Wind Harmer
1.148
253370AE2-315 SEC1
Adder
1.526
971125AH1-004 GEN
Solar/Wind Harmer
2.112
970107AG2-081 GEN
Solar/Wind Harmer
1.584
25322209TAIT E
Adder
7.169
25322209TAIT E
Adder
7.008
25326109MON D
Adder
0.942
942891AE2-308 GEN
Solar/Wind Harmer
4.783
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.132
970885AG2-551 GEN
Solar/Wind Harmer
1.377
964571AG1-320 GEN
Solar/Wind Harmer
3.631
247621Y3-024
Adder
0.133
964611AG1-324 GEN
Solar/Wind Harmer
0.283
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.967
270599AE1-208 GEN
Solar/Wind Harmer
3.278
25326509SID D
Adder
0.66
971613AH1-306 GEN
Solar/Wind Harmer
1.669
944541AF1-119 GEN
Solar/Wind Harmer
0.224
960971AF2-388 GEN
Solar/Wind Harmer
1.97
970291AG2-192 GEN
Solar/Wind Harmer
0.435
970291AG2-192 GEN
Solar/Wind Harmer
0.201
971587AH1-292 GEN
Solar/Wind Harmer
2.382
970329AG2-216 GEN
Solar/Wind Harmer
1.4
942221AE2-234 GEN
Solar/Wind Harmer
1.259
945391AF1-204 GEN
Solar/Wind Harmer
3.307
964781AG1-341 GEN
Solar/Wind Harmer
3.276
24803406KYGER 5HP
50/50
4.094
24803206KYGER 4HP
50/50
4.085
252516AE2-318_GEN
Solar/Wind Harmer
7.932
25196808ZIMRHP
Adder
75.812
25194608D.CRK4
Adder
1.604
252510AF1-249 C
Solar/Wind Harmer
0.051
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.761
25196008MFTGT1
Adder
1.283
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
11.543
270273AD2-016 GEN
Solar/Wind Harmer
0.596
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
25326309TAIT D
Adder
0.805
3429421JKCT 10G
Adder
6.006
3429241JKCT 3G
Adder
8.287
970773AG2-487 GEN
Solar/Wind Harmer
0.807
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.158
24728605AND G2
Adder
2.173
253333AC1-068 GEN
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
0.848
970825AG2-519 GEN
Solar/Wind Harmer
1.367
970653AG2-424 GEN
Solar/Wind Harmer
1.845
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
3.979
270594AE1-207 GEN
Solar/Wind Harmer
3.893
270032AE2-172
Solar/Wind Harmer
2.318
958861AF2-177 GEN
Solar/Wind Harmer
1.487
970091AG2-072 GEN
Adder
37.335
270024AE2-089 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.985
964901AG1-354 GEN
Solar/Wind Harmer
4.987
960001AF2-291 GEN
Solar/Wind Helper
1.682
270331AC1-082 GEN3
Solar/Wind Helper
0.187
24803106KYGER 3LP
50/50
2.439
24803306KYGER 4LP
50/50
2.389
971191AH1-055 GEN
Solar/Wind Harmer
68.884
252507AC2-088 GEN
Solar/Wind Harmer
0.343
252519AF1-045_GEN
Solar/Wind Harmer
3.694
25194608D.CRK4
Adder
1.604
25196608WSDLE5
Adder
8.356
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.789
958171AF2-111 GEN
Solar/Wind Harmer
16.332
25196008MFTGT1
Adder
1.242
253394AE2-221_GEN
Solar/Wind Harmer
0.001
972167AH1-666 GEN
Solar/Wind Harmer
4.919
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.526
253371AE2-315 SEC2
Adder
1.444
970191AG2-125 GEN
Solar/Wind Harmer
1.303
3429391JKCT 9G
Adder
6.006
970093AG2-073 GEN
Solar/Wind Harmer
3.867
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970455AG2-298 GEN
Solar/Wind Harmer
1.6
24728505AND G1
Adder
2.173
253325AC1-069 GEN
Solar/Wind Harmer
0.004
270004AE1-209 GEN
Solar/Wind Harmer
0.848
946031AF1-268 GEN
Solar/Wind Harmer
3.69
970825AG2-519 GEN
Solar/Wind Harmer
2.902
970653AG2-424 GEN
Solar/Wind Harmer
0.382
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.618
270518AE2-148 GEN
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
0.368
972273AH1-721 GEN
Adder
39.663
247642Z2-115 C
Solar/Wind Harmer
0.001
970193AG2-126 GEN
Solar/Wind Harmer
4.669
944531AF1-118 GEN
Solar/Wind Harmer
13.648
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.509
NYPJM->LTFIMP_NY
CLTF
1.348
LGEELTFEXP_LGEE->PJM
CLTF
4.627
WECLTFEXP_WEC->PJM
CLTF
1.3
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.242
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.475
MECLTFEXP_MEC->PJM
CLTF
5.763
SIGELTFEXP_SIGE->PJM
CLTF
0.281
LAGNLTFEXP_LAGN->PJM
CLTF
5.22
TVALTFEXP_TVA->PJM
CLTF
2.571
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS'
 OPEN BRANCH FROM BUS 962760 TO BUS 248125 CKT 1   /*AG1-125 TP   765.0 - 05ADKINS     765.0
END
CONTINGENCY 'AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 243207 TO BUS 248105 CKT 1   /*05GRNTWN     765.0 - 05GREENTW_RM 765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248102 CKT 1   /*05TEDDY_RG   765.0 - 05TEDDY      765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248105 CKT 1   /*05TEDDY_RG   765.0 - 05GREENTW_RM 765.0
END
CONTINGENCY 'AEP_P1-2_#9287_1679_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290597 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290597 CKT 1    /*05GRNTWN     765.0 - 05DUMONT_RG  765.0
END
290610 to 242512 ckt Z1
242514 to 290610 ckt 1
290623 to 242925 ckt Z1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
248005 to 242528 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC122.65 %3792.0B4650.99
3.13
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC122.64 %3792.0B4650.57
3.13
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC138.45 %3792.0B5250.02
3.07
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC138.41 %3792.0B5248.4
3.07
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.87 %3729.0B4917.49
3.49
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.24 %3729.0B4632.89
3.37
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC113.4 %1683.0B1908.5
1.59
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC110.65 %1737.0B1922.03
2.51
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-2_MP-500-028_SRT-A
SingleAC100.79 %4000.0B4031.79
3.26
GD2AEP/AP
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
AP_P1-3_MP-765-502T_SRT-A
SingleAC100.79 %4000.0B4031.62
3.26
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC104.78 %2320.0B2430.97
1.51
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
2.94
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#709_546_SRT-A
SingleAC105.58 %3039.0B3208.68
1.45
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC113.16 %2826.0B3197.84
1.45
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC133.22 %3792.0B5051.83
3.49
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.57 %3792.0B4761.71
3.37
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC111.91 %2246.0B2513.45
2.42
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC127.9 %4142.0B5297.56
3.79
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC108.0 %4142.0B4473.55
3.95
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.31 %4571.0B5773.71
3.7
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Base Case
SingleAC110.62 %4047.0A4476.89
2.97
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC110.01 %4571.0B5028.49
3.95
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.34 %4571.0B5774.92
3.7
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Base Case
SingleAC110.76 %4047.0A4482.29
2.97
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC110.28 %4571.0B5040.8
3.95
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Base Case
SingleAC120.76 %4047.0A4887.22
4.66
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC116.4 %5523.0B6428.58
4.51
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC109.18 %4558.0A4976.63
3.11
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.76 %5523.0B5896.19
3.76
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC122.25 %1868.0B2283.58
2.44
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P1-2_#7442_200545_SRT-A
SingleAC103.01 %3097.0B3190.2
4.3
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.53 %5523.0B5607.44
5.42
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC112.63 %2317.0B2609.67
3.05
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC141.94 %1540.0B2185.8
2.15
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC133.27 %1540.0B2052.4
2.04
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC128.82 %1868.0B2406.35
2.44

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.99
MW Contribution:
3.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
30.328
970149AG2-104 GEN
Solar/Wind Harmer
16.378
970155AG2-107 GEN
Solar/Wind Harmer
19.366
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
270520AE2-214 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
0.726
972203AH1-686 GEN
Adder
2.339
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
7.551
252510AF1-249 C
Solar/Wind Harmer
0.051
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
7.272
965011AG1-365 GEN
Solar/Wind Harmer
6.491
965421AG1-410 GEN
Solar/Wind Harmer
19.339
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
24728605AND G2
Adder
3.541
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.351
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.48
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
963741AG1-226 GEN
Solar/Wind Harmer
15.1
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.32
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.718
944971AF1-162 GEN
Solar/Wind Harmer
6.303
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
961921AG1-034 GEN
Solar/Wind Harmer
6.37
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.608
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.304
252519AF1-045_GEN
Solar/Wind Harmer
3.517
970191AG2-125 GEN
Solar/Wind Harmer
1.734
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970825AG2-519 GEN
Solar/Wind Harmer
4.924
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
3.227
246938BC-WTG3
Solar/Wind Harmer
0.232
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274887GEN-1.85
Solar/Wind Harmer
0.165
276843GEN-1.7
Solar/Wind Harmer
0.205
276806AD2-047 C O1
Solar/Wind Harmer
3.589
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
274682WAUKEGAN ;7U
Adder
16.174
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
946671AF1-331 GEN
Solar/Wind Harmer
0.667
965091AG1-374 GEN
Solar/Wind Harmer
18.751
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
270588AE1-091_GEN
Solar/Wind Harmer
4.882
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
959091AF2-200 GEN
Solar/Wind Harmer
3.185
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270291AC1-194 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
2.075
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
253406AD2-031_GEN
Solar/Wind Harmer
0.507
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972163AH1-664 GEN
Solar/Wind Harmer
7.323
972165AH1-665 GEN
Solar/Wind Harmer
5.865
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
12.517
971609AH1-304 GEN
Solar/Wind Harmer
1.067
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
959331AF2-224 GEN
Solar/Wind Harmer
4.543
247521TR3_G114
Solar/Wind Harmer
0.234
965051AG1-369 GEN
Solar/Wind Harmer
3.226
965041AG1-368 GEN
Solar/Wind Harmer
6.455
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.816
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.285
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.578
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.438
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.224
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
10.862
971655AH1-328 GEN
Solar/Wind Harmer
2.4
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
0
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
960971AF2-388 GEN
Solar/Wind Harmer
3.846
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
270599AE1-208 GEN
Solar/Wind Harmer
5.986
942221AE2-234 GEN
Solar/Wind Harmer
2.621
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.041
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
246937BC-WTG2
Solar/Wind Harmer
0.26
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
965681AG1-436 GEN
Solar/Wind Harmer
8.006
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.422
972043AH1-570 GEN
Solar/Wind Harmer
1.663
972045AH1-571 GEN
Solar/Wind Harmer
1.333
970241AG2-163 GEN
Solar/Wind Harmer
3.722
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
971587AH1-292 GEN
Solar/Wind Harmer
4.656
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
276776AD2-060 GEN
Solar/Wind Harmer
0.676
958011AF2-095 GEN
Solar/Wind Harmer
9.122
970941AG2-585 GEN
Solar/Wind Harmer
3.484
945391AF1-204 GEN
Solar/Wind Harmer
6.73
276897AD1-100 C
Solar/Wind Harmer
15.831
274674JOLIET 9 ;6U
Adder
13.943
276893AG1-478 C
Solar/Wind Harmer
0.421
971125AH1-004 GEN
Solar/Wind Harmer
2.523
970107AG2-081 GEN
Solar/Wind Harmer
1.892
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
958491AF2-143 GEN
Solar/Wind Harmer
9.422
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
971171AH1-044 GEN
Solar/Wind Harmer
3.185
276805AD2-038 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
971997AH1-543 GEN
Solar/Wind Harmer
3.293
276882AE2-255 GEN
Solar/Wind Harmer
0.732
962781AG1-127 GEN
Solar/Wind Harmer
5.964
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.771
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.57
MW Contribution:
3.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
24318805MLG1
50/50
6.603
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
961921AG1-034 GEN
Solar/Wind Harmer
6.37
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.608
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
270186AC1-089 GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.304
252519AF1-045_GEN
Solar/Wind Harmer
3.517
23684101S70BUS1
50/50
0.295
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.224
970879AG2-548 GEN
Solar/Wind Harmer
1.187
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.28
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
938701AE1-092 GEN
Solar/Wind Harmer
10.862
971655AH1-328 GEN
Solar/Wind Harmer
2.4
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194408D.CRK1
Adder
7.279
25194508D.CRK3
Adder
1.361
270462AD2-086
Solar/Wind Harmer
0
25326509SID D
Adder
1.261
24728805RICHG1
Adder
3.564
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
960971AF2-388 GEN
Solar/Wind Harmer
3.846
247621Y3-024
Adder
0.226
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
270599AE1-208 GEN
Solar/Wind Harmer
5.986
942221AE2-234 GEN
Solar/Wind Harmer
2.621
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970191AG2-125 GEN
Solar/Wind Harmer
1.734
25196608WSDLE5
Adder
8.25
25194608D.CRK4
Adder
1.582
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970825AG2-519 GEN
Solar/Wind Harmer
4.924
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
971347AH1-153 GEN
Solar/Wind Harmer
3.227
246938BC-WTG3
Solar/Wind Harmer
0.232
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
24728705AND G3
Adder
7.406
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274752CRETE EC ;2U
Adder
7.503
274753CRETE EC ;3U
Adder
7.503
274724RIVER EC ;11
Adder
16.119
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274811UNIV PK N;7U
Adder
4.553
274803UNIV PARK;6U
Adder
5.293
274887GEN-1.85
Solar/Wind Harmer
0.165
276843GEN-1.7
Solar/Wind Harmer
0.205
276806AD2-047 C O1
Solar/Wind Harmer
3.589
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
972038AH1-567 GEN2
Adder
0.331
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
274730ELWOOD EC;6P
Adder
14.887
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
274682WAUKEGAN ;7U
Adder
16.174
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
946671AF1-331 GEN
Solar/Wind Harmer
0.667
965091AG1-374 GEN
Solar/Wind Harmer
18.751
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
270588AE1-091_GEN
Solar/Wind Harmer
4.882
23562501BACKB
Solar/Wind Helper
1.049
964991AG1-363 GEN
Solar/Wind Helper
4.289
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
238127S14_GEN_2
Solar/Wind Helper
0.769
237048AF1-022 C
Solar/Wind Helper
0.176
238152AF2-075_GEN
Solar/Wind Helper
0.617
238175AF1-290_GEN
Solar/Wind Helper
0.135
23777901MDS_W4-102
Solar/Wind Helper
0.153
235063AE1-101 C2
Solar/Wind Helper
1.447
237001AB1-127_GEN
Solar/Wind Helper
0.384
316415AF1-147_GEN2
Solar/Wind Helper
0.762
959091AF2-200 GEN
Solar/Wind Harmer
3.185
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270291AC1-194 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
971985AH1-537 GEN
Solar/Wind Harmer
2.075
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
253406AD2-031_GEN
Solar/Wind Harmer
0.507
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25306009OHH W.
Adder
2.794
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196508WSDLE4
Adder
8.165
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972163AH1-664 GEN
Solar/Wind Harmer
7.323
972165AH1-665 GEN
Solar/Wind Harmer
5.865
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
12.517
971609AH1-304 GEN
Solar/Wind Harmer
1.067
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
959331AF2-224 GEN
Solar/Wind Harmer
4.543
247521TR3_G114
Solar/Wind Harmer
0.234
965051AG1-369 GEN
Solar/Wind Harmer
3.226
965041AG1-368 GEN
Solar/Wind Harmer
6.455
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.816
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274775LINCOLN ;6U
Adder
7.689
274776LINCOLN ;7U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274728ELWOOD EC;5P
Adder
14.887
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274735ELWOOD EC;4P
Adder
14.887
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274744AC1-111 GEN8
Adder
5.047
274746AC1-111 G10
Adder
5.047
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.285
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.578
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.438
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
23779801AA1-109
Solar/Wind Helper
0.168
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
3138216PACIFIC
Solar/Wind Helper
0.038
971171AH1-044 GEN
Solar/Wind Harmer
3.185
970291AG2-192 GEN
Solar/Wind Harmer
0.391
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.041
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
246937BC-WTG2
Solar/Wind Harmer
0.26
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
965681AG1-436 GEN
Solar/Wind Harmer
8.006
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.422
972043AH1-570 GEN
Solar/Wind Harmer
1.663
972045AH1-571 GEN
Solar/Wind Harmer
1.333
970241AG2-163 GEN
Solar/Wind Harmer
3.722
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
971587AH1-292 GEN
Solar/Wind Harmer
4.656
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274808UNIV PK N;4U
Adder
4.533
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
276776AD2-060 GEN
Solar/Wind Harmer
0.676
958011AF2-095 GEN
Solar/Wind Harmer
9.122
970941AG2-585 GEN
Solar/Wind Harmer
3.484
945391AF1-204 GEN
Solar/Wind Harmer
6.73
276897AD1-100 C
Solar/Wind Harmer
15.831
274674JOLIET 9 ;6U
Adder
13.943
276893AG1-478 C
Solar/Wind Harmer
0.421
971125AH1-004 GEN
Solar/Wind Harmer
2.523
970107AG2-081 GEN
Solar/Wind Harmer
1.892
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.261
274695ROCKY RD ;2P
Adder
10.024
274693ROCKY RD ;1P
Adder
9.926
274697ROCKY RD ;3P
Adder
2.723
958491AF2-143 GEN
Solar/Wind Harmer
9.422
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
23585401KL_K28_T16
Solar/Wind Helper
1.451
316097T157 G90
Solar/Wind Helper
1.331
235054AD2-180 GEN
Solar/Wind Helper
1.948
238117U2-030
Solar/Wind Helper
0.32
235531U2-073 GEN
Solar/Wind Helper
3.079
238147AE2-230_GEN1
Solar/Wind Helper
0.432
238148AE2-230_GEN2
Solar/Wind Helper
0.432
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
316411AF1-147_GEN1
Solar/Wind Helper
0.762
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
23559101PLEAS2
50/50
11.898
23684201S70BUS2
50/50
0.3
23562301OGROV1
50/50
2.293
962761AG1-125 GEN
Solar/Wind Harmer
30.328
970149AG2-104 GEN
Solar/Wind Harmer
16.378
970155AG2-107 GEN
Solar/Wind Harmer
19.366
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
270520AE2-214 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270273AD2-016 GEN
Solar/Wind Harmer
0.726
972203AH1-686 GEN
Adder
2.339
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
24723205RIVRG3
Adder
18.772
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
25326309TAIT D
Adder
1.064
252516AE2-318_GEN
Solar/Wind Harmer
7.551
252510AF1-249 C
Solar/Wind Harmer
0.051
25194608D.CRK4
Adder
1.582
25196808ZIMRHP
Adder
72.791
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.323
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
970091AG2-072 GEN
Adder
71.643
276903AD2-071 C
Solar/Wind Harmer
7.272
965011AG1-365 GEN
Solar/Wind Harmer
6.491
965421AG1-410 GEN
Solar/Wind Harmer
19.339
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
24728605AND G2
Adder
3.541
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.351
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.48
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
963741AG1-226 GEN
Solar/Wind Harmer
15.1
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.32
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274754CRETE EC ;4U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
274812UNIV PK N;8U
Adder
4.553
274802UNIV PARK;5U
Adder
5.293
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.887
274676JOLIET 29;8U
Adder
27.787
274674JOLIET 9 ;6U
Adder
13.943
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.718
944971AF1-162 GEN
Solar/Wind Harmer
6.303
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
971997AH1-543 GEN
Solar/Wind Harmer
3.293
276882AE2-255 GEN
Solar/Wind Harmer
0.732
962781AG1-127 GEN
Solar/Wind Harmer
5.964
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.771
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23751101LEADS_P59
Solar/Wind Helper
2.413
23583801GRNGAP
Solar/Wind Helper
4.978
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
238126S14_GEN_1
Solar/Wind Helper
0.769
23546401DTGZ2-030
Solar/Wind Helper
0.078
237085AD2-009_GEN
Solar/Wind Helper
1.438
235067AD1-061 GEN
Solar/Wind Helper
0.388
237038AE2-054 C
Solar/Wind Helper
0.237
237002AB1-128_GEN
Solar/Wind Helper
0.386
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5250.02
MW Contribution:
3.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
29.52
970149AG2-104 GEN
Solar/Wind Harmer
15.941
970155AG2-107 GEN
Solar/Wind Harmer
18.85
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
7.407
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
12.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970825AG2-519 GEN
Solar/Wind Harmer
2.272
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.119
965011AG1-365 GEN
Solar/Wind Harmer
6.339
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.17
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.272
24639705ELKHART HY
Adder
0.138
963741AG1-226 GEN
Solar/Wind Harmer
14.786
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.244
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.617
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.588
962781AG1-127 GEN
Solar/Wind Harmer
5.837
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
961921AG1-034 GEN
Solar/Wind Harmer
6.223
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.329
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252507AC2-088 GEN
Solar/Wind Harmer
0.298
252519AF1-045_GEN
Solar/Wind Harmer
3.45
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
970191AG2-125 GEN
Solar/Wind Harmer
1.699
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
958171AF2-111 GEN
Solar/Wind Harmer
16.173
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
28.761
270004AE1-209 GEN
Solar/Wind Harmer
1.388
946031AF1-268 GEN
Solar/Wind Harmer
6.094
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
3.154
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.226
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.532
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274887GEN-1.85
Solar/Wind Harmer
0.161
276843GEN-1.7
Solar/Wind Harmer
0.2
276806AD2-047 C O1
Solar/Wind Harmer
3.512
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
970707AG2-453 GEN
Solar/Wind Harmer
20.232
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
965091AG1-374 GEN
Solar/Wind Harmer
18.362
959611AF2-252 GEN
Solar/Wind Harmer
2.04
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
959091AF2-200 GEN
Solar/Wind Harmer
2.06
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270291AC1-194 GEN
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
971985AH1-537 GEN
Solar/Wind Harmer
2.039
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
253406AD2-031_GEN
Solar/Wind Harmer
0.497
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
7.194
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
270543AE2-219 C
Solar/Wind Harmer
4.502
247536S-71 GEN
Solar/Wind Harmer
0.257
24729505KEY G4
Adder
5.966
945581AF1-223 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
270071AF1-092 GEN
Solar/Wind Harmer
12.235
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
959331AF2-224 GEN
Solar/Wind Harmer
4.437
247521TR3_G114
Solar/Wind Harmer
0.229
965051AG1-369 GEN
Solar/Wind Harmer
3.151
965041AG1-368 GEN
Solar/Wind Harmer
6.303
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270526AF1-158 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
270399AC1-101 GEN
Solar/Wind Harmer
1.959
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
970179AG2-119 GEN
Solar/Wind Harmer
5.512
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.152
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.441
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971171AH1-044 GEN
Solar/Wind Harmer
2.06
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.141
970879AG2-548 GEN
Solar/Wind Harmer
1.168
270269AC2-059
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
942861AE2-305 GEN
Solar/Wind Harmer
5.328
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
938701AE1-092 GEN
Solar/Wind Harmer
10.602
971655AH1-328 GEN
Solar/Wind Harmer
2.343
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
960971AF2-388 GEN
Solar/Wind Harmer
3.762
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
270599AE1-208 GEN
Solar/Wind Harmer
5.858
971613AH1-306 GEN
Solar/Wind Harmer
3.066
942221AE2-234 GEN
Solar/Wind Harmer
2.563
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.04
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
972045AH1-571 GEN
Solar/Wind Harmer
1.309
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.711
965681AG1-436 GEN
Solar/Wind Harmer
7.827
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
971587AH1-292 GEN
Solar/Wind Harmer
4.565
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
971125AH1-004 GEN
Solar/Wind Harmer
2.48
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
8.924
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
958481AF2-142 GEN
Solar/Wind Harmer
9.241
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.221
944231AF1-091 GEN
Solar/Wind Harmer
14.169
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.41 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5248.4
MW Contribution:
3.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.247
23684201S70BUS2
50/50
0.315
23562301OGROV1
50/50
2.436
962761AG1-125 GEN
Solar/Wind Harmer
29.52
970149AG2-104 GEN
Solar/Wind Harmer
15.941
970155AG2-107 GEN
Solar/Wind Harmer
18.85
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270520AE2-214 GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.3
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
972269AH1-719 GEN
Adder
2.27
24723205RIVRG3
Adder
18.491
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
961921AG1-034 GEN
Solar/Wind Harmer
6.223
24686405CER G5
Adder
8.185
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
12.329
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270291AC1-194 GEN
Solar/Wind Harmer
0
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
971985AH1-537 GEN
Solar/Wind Harmer
2.039
943861AF1-054 GEN
Solar/Wind Harmer
2.63
970935AG2-582 GEN
50/50
1217.29
23684101S70BUS1
50/50
0.309
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
5.141
970879AG2-548 GEN
Solar/Wind Harmer
1.168
270269AC2-059
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
942861AE2-305 GEN
Solar/Wind Harmer
5.328
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.298
252519AF1-045_GEN
Solar/Wind Harmer
3.45
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
970191AG2-125 GEN
Solar/Wind Harmer
1.699
25196608WSDLE5
Adder
8.09
25194608D.CRK4
Adder
1.552
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
958171AF2-111 GEN
Solar/Wind Harmer
16.173
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
28.761
270004AE1-209 GEN
Solar/Wind Harmer
1.388
946031AF1-268 GEN
Solar/Wind Harmer
6.094
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
24728705AND G3
Adder
7.256
24728505AND G1
Adder
3.47
971347AH1-153 GEN
Solar/Wind Harmer
3.154
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.226
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.532
270063AE2-323 C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274752CRETE EC ;2U
Adder
7.339
274753CRETE EC ;3U
Adder
7.339
274724RIVER EC ;11
Adder
15.767
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274811UNIV PK N;7U
Adder
4.454
274803UNIV PARK;6U
Adder
5.179
274887GEN-1.85
Solar/Wind Harmer
0.161
276843GEN-1.7
Solar/Wind Harmer
0.2
276806AD2-047 C O1
Solar/Wind Harmer
3.512
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
972038AH1-567 GEN2
Adder
0.324
970707AG2-453 GEN
Solar/Wind Harmer
20.232
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
274730ELWOOD EC;6P
Adder
14.566
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
965091AG1-374 GEN
Solar/Wind Harmer
18.362
959611AF2-252 GEN
Solar/Wind Harmer
2.04
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
964991AG1-363 GEN
Solar/Wind Helper
4.131
238152AF2-075_GEN
Solar/Wind Helper
0.595
238175AF1-290_GEN
Solar/Wind Helper
0.13
238108AE1-109 GEN1
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
23777901MDS_W4-102
Solar/Wind Helper
0.147
235063AE1-101 C2
Solar/Wind Helper
1.383
237001AB1-127_GEN
Solar/Wind Helper
0.369
238127S14_GEN_2
Solar/Wind Helper
0.641
959091AF2-200 GEN
Solar/Wind Harmer
2.06
943851AF1-053 GEN
Solar/Wind Harmer
1.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
253406AD2-031_GEN
Solar/Wind Harmer
0.497
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196508WSDLE4
Adder
8.008
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
972163AH1-664 GEN
Solar/Wind Harmer
7.194
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
270543AE2-219 C
Solar/Wind Harmer
4.502
247536S-71 GEN
Solar/Wind Harmer
0.257
24729505KEY G4
Adder
5.966
945581AF1-223 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
270071AF1-092 GEN
Solar/Wind Harmer
12.235
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
959331AF2-224 GEN
Solar/Wind Harmer
4.437
247521TR3_G114
Solar/Wind Harmer
0.229
965051AG1-369 GEN
Solar/Wind Harmer
3.151
965041AG1-368 GEN
Solar/Wind Harmer
6.303
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270526AF1-158 GEN
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274776LINCOLN ;7U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
270399AC1-101 GEN
Solar/Wind Harmer
1.959
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274728ELWOOD EC;5P
Adder
14.566
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
274735ELWOOD EC;4P
Adder
14.566
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
970179AG2-119 GEN
Solar/Wind Harmer
5.512
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.152
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.441
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971171AH1-044 GEN
Solar/Wind Harmer
2.06
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
938701AE1-092 GEN
Solar/Wind Harmer
10.602
971655AH1-328 GEN
Solar/Wind Harmer
2.343
25194408D.CRK1
Adder
7.139
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
25326509SID D
Adder
1.233
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.492
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
960971AF2-388 GEN
Solar/Wind Harmer
3.762
247621Y3-024
Adder
0.222
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
270599AE1-208 GEN
Solar/Wind Harmer
5.858
971613AH1-306 GEN
Solar/Wind Harmer
3.066
942221AE2-234 GEN
Solar/Wind Harmer
2.563
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.04
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
972045AH1-571 GEN
Solar/Wind Harmer
1.309
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.711
965681AG1-436 GEN
Solar/Wind Harmer
7.827
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
971587AH1-292 GEN
Solar/Wind Harmer
4.565
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274805UNIV PK N;1U
Adder
4.464
274808UNIV PK N;4U
Adder
4.435
971125AH1-004 GEN
Solar/Wind Harmer
2.48
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
8.924
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
958481AF2-142 GEN
Solar/Wind Harmer
9.241
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.221
944231AF1-091 GEN
Solar/Wind Harmer
14.169
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
238148AE2-230_GEN2
Solar/Wind Helper
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.119
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
237080AD1-060 GEN
Solar/Wind Helper
0.284
235062AE1-101 C1
Solar/Wind Helper
1.383
235531U2-073 GEN
Solar/Wind Helper
2.544
238117U2-030
Solar/Wind Helper
0.26
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
25326309TAIT D
Adder
1.043
252516AE2-318_GEN
Solar/Wind Harmer
7.407
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.552
25196808ZIMRHP
Adder
71.417
270317AD1-130_GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.297
945681AF1-233 GEN
Solar/Wind Harmer
12.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970825AG2-519 GEN
Solar/Wind Harmer
2.272
970091AG2-072 GEN
Adder
70.262
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.119
965011AG1-365 GEN
Solar/Wind Harmer
6.339
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.17
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.272
24639705ELKHART HY
Adder
0.138
963741AG1-226 GEN
Solar/Wind Harmer
14.786
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.244
274751CRETE EC ;1U
Adder
7.339
274754CRETE EC ;4U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
274812UNIV PK N;8U
Adder
4.454
274802UNIV PARK;5U
Adder
5.179
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.566
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
4.617
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.588
962781AG1-127 GEN
Solar/Wind Harmer
5.837
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
316095T157 G97
Solar/Wind Helper
1.299
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
237038AE2-054 C
Solar/Wind Helper
0.227
235067AD1-061 GEN
Solar/Wind Helper
0.371
237085AD2-009_GEN
Solar/Wind Helper
1.37
238120AE2-309 GEN
Solar/Wind Helper
0.408
237002AB1-128_GEN
Solar/Wind Helper
0.369
238126S14_GEN_1
Solar/Wind Helper
0.641
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.87 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4917.49
MW Contribution:
3.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.065
23559001PLEAS1
50/50
6.097
270051AF1-062 GEN
50/50
11.777
270475AD2-096_GEN
50/50
7.114
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
961921AG1-034 GEN
Solar/Wind Harmer
7.586
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
970191AG2-125 GEN
Solar/Wind Harmer
1.937
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
971191AH1-055 GEN
Solar/Wind Harmer
19.175
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
944531AF1-118 GEN
Solar/Wind Harmer
33.233
270043AE2-236 GEN
Solar/Wind Harmer
4.754
252519AF1-045_GEN
Solar/Wind Harmer
3.844
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
9.036
25194608D.CRK4
Adder
1.732
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
971347AH1-153 GEN
Solar/Wind Harmer
3.658
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.95
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
970289AG2-191 GEN
Solar/Wind Harmer
0.8
945111AF1-176 GEN
Solar/Wind Harmer
5.891
247642Z2-115 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
274753CRETE EC ;3U
Adder
8.436
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274811UNIV PK N;7U
Adder
5.114
972167AH1-666 GEN
Solar/Wind Harmer
5.69
274803UNIV PARK;6U
Adder
5.941
24728705AND G3
Adder
8.173
24728505AND G1
Adder
3.908
274887GEN-1.85
Solar/Wind Harmer
0.185
276843GEN-1.7
Solar/Wind Harmer
0.23
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274826FISK ;BP
Adder
11.151
972038AH1-567 GEN2
Adder
0.372
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
972259AH1-714 GEN
Adder
19.413
274676JOLIET 29;8U
Adder
30.039
274729ELWOOD EC;1P
Adder
16.687
274730ELWOOD EC;6P
Adder
16.687
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
274682WAUKEGAN ;7U
Adder
18.096
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970193AG2-126 GEN
Solar/Wind Harmer
10.468
970571AG2-364 GEN
Solar/Wind Harmer
13.944
964991AG1-363 GEN
Solar/Wind Helper
5.155
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.831
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
23562501BACKB
Solar/Wind Helper
1.012
235063AE1-101 C2
Solar/Wind Helper
1.672
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.512
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.594
270166AC1-044 GEN3
50/50
7.069
23559101PLEAS2
50/50
6.097
962761AG1-125 GEN
Solar/Wind Harmer
34.394
970149AG2-104 GEN
Solar/Wind Harmer
18.573
970155AG2-107 GEN
Solar/Wind Harmer
21.963
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.894
270273AD2-016 GEN
Solar/Wind Harmer
0.807
972269AH1-719 GEN
Adder
2.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965421AG1-410 GEN
Solar/Wind Harmer
22.47
960001AF2-291 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965011AG1-365 GEN
Solar/Wind Harmer
7.453
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
958861AF2-177 GEN
Solar/Wind Harmer
3.191
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.732
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.351
970825AG2-519 GEN
Solar/Wind Harmer
2.589
24639705ELKHART HY
Adder
0.16
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
276903AD2-071 C
Solar/Wind Harmer
8.095
25196008MFTGT1
Adder
1.443
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.365
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274754CRETE EC ;4U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
274802UNIV PARK;5U
Adder
5.941
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
31.151
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
939401AE1-172 GEN
Solar/Wind Harmer
5.275
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
274682WAUKEGAN ;7U
Adder
18.096
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.818
971997AH1-543 GEN
Solar/Wind Harmer
3.68
962781AG1-127 GEN
Solar/Wind Harmer
6.668
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
316095T157 G97
Solar/Wind Helper
1.51
23583801GRNGAP
Solar/Wind Helper
5.626
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
238126S14_GEN_1
Solar/Wind Helper
0.831
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.661
237038AE2-054 C
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.792
211065PSPA IPP
Solar/Wind Helper
0.152
963161AG1-165 GEN
Solar/Wind Helper
0.441
957471AF2-041 GEN
Solar/Wind Harmer
13.586
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.868
316044AC1-158 PL1
Solar/Wind Helper
1.303
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.516
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.58
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
202652Y1-033 WT C
Solar/Wind Helper
0.5
959091AF2-200 GEN
Solar/Wind Harmer
9.057
972239AH1-704 GEN
Adder
2.678
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270291AC1-194 GEN
Solar/Wind Harmer
0
970179AG2-119 GEN
Solar/Wind Harmer
6.854
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
253406AD2-031_GEN
Solar/Wind Harmer
0.559
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270377AD1-106 GEN
Solar/Wind Harmer
2.842
247521TR3_G114
Solar/Wind Harmer
0.27
965051AG1-369 GEN
Solar/Wind Harmer
3.723
959331AF2-224 GEN
Solar/Wind Harmer
5.217
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.438
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
963791AG1-232 GEN
Solar/Wind Harmer
9.987
270071AF1-092 GEN
Solar/Wind Harmer
14.177
971985AH1-537 GEN
Solar/Wind Harmer
2.196
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
25196508WSDLE4
Adder
8.944
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
270543AE2-219 C
Solar/Wind Harmer
5.137
247536S-71 GEN
Solar/Wind Harmer
0.293
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
970289AG2-191 GEN
Solar/Wind Harmer
1.382
971771AH1-392 GEN
Solar/Wind Harmer
7.271
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
971549AH1-272 GEN
Solar/Wind Harmer
14.794
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.634
274776LINCOLN ;7U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972228AH1-698 GEN2
Adder
3.772
972227AH1-698 GEN1
Adder
2.656
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
274728ELWOOD EC;5P
Adder
16.687
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274735ELWOOD EC;4P
Adder
16.687
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
274744AC1-111 GEN8
Adder
5.652
274746AC1-111 G10
Adder
5.652
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
970169AG2-114 GEN
Solar/Wind Harmer
7.011
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
971411AH1-196 GEN
Solar/Wind Harmer
10.47
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.32
23750701CROSSCHOOL
Solar/Wind Helper
1.509
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.512
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.062
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.057
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.031
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
270119AB2-067 GEN1
50/50
7.069
270120AB2-067 GEN2
50/50
7.069
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.31
938701AE1-092 GEN
Solar/Wind Harmer
12.867
971655AH1-328 GEN
Solar/Wind Harmer
2.843
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
25326509SID D
Adder
1.446
971073AG2-665 GEN
Solar/Wind Harmer
5.597
970879AG2-548 GEN
Solar/Wind Harmer
1.272
25326109MON D
Adder
1.437
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
246937BC-WTG2
Solar/Wind Harmer
0.302
270246TR4_N_V150
Solar/Wind Harmer
0.048
270247TR4_N_V136
Solar/Wind Harmer
0.048
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.351
944541AF1-119 GEN
Solar/Wind Harmer
0.492
960971AF2-388 GEN
Solar/Wind Harmer
4.326
942221AE2-234 GEN
Solar/Wind Harmer
2.958
25194408D.CRK1
Adder
7.968
25194508D.CRK3
Adder
1.49
970621AG2-405 GEN
Solar/Wind Harmer
1.345
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970885AG2-551 GEN
Solar/Wind Harmer
2.446
247621Y3-024
Adder
0.253
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270031AE2-169
Solar/Wind Harmer
4.021
270599AE1-208 GEN
Solar/Wind Harmer
6.701
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728805RICHG1
Adder
3.944
24728905RICHG2
Adder
3.944
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.052
965791AG1-447 GEN
Solar/Wind Harmer
6.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274805UNIV PK N;1U
Adder
5.126
274808UNIV PK N;4U
Adder
5.092
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
276776AD2-060 GEN
Solar/Wind Harmer
0.758
958011AF2-095 GEN
Solar/Wind Harmer
10.234
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
274674JOLIET 9 ;6U
Adder
15.628
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274696ROCKY RD ;4P
Adder
11.481
274695ROCKY RD ;2P
Adder
11.216
274693ROCKY RD ;1P
Adder
11.106
274697ROCKY RD ;3P
Adder
3.047
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276901AD2-066 C O1
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
962691AG1-118 GEN
Solar/Wind Harmer
21.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
942111AE2-223 GEN
Solar/Wind Harmer
2.266
316097T157 G90
Solar/Wind Helper
1.51
235054AD2-180 GEN
Solar/Wind Helper
2.04
23585401KL_K28_T16
Solar/Wind Helper
1.489
235531U2-073 GEN
Solar/Wind Helper
3.327
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.344
235062AE1-101 C1
Solar/Wind Helper
1.672
316411AF1-147_GEN1
Solar/Wind Helper
0.895
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.17
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4632.89
MW Contribution:
3.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.4 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:1908.5
MW Contribution:
1.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
1.525
23888602TROY G2
50/50
1.525
945411AF1-206 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.522
270575GUS2 35KV
Solar/Wind Harmer
4.522
270499AE1-146 GEN
Solar/Wind Harmer
0.021
971549AH1-272 GEN
Solar/Wind Harmer
11.979
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.588
270007AE1-245 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.388
971771AH1-392 GEN
Solar/Wind Harmer
4.384
965041AG1-368 GEN
Solar/Wind Harmer
4.372
247521TR3_G114
Solar/Wind Harmer
0.157
965051AG1-369 GEN
Solar/Wind Harmer
2.168
270526AF1-158 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.976
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.581
960681AF2-359 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.317
971567AH1-282 GEN
Solar/Wind Harmer
3.005
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
270071AF1-092 GEN
Solar/Wind Harmer
7.265
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
274800UNIV PARK;3U
Adder
3.125
274801UNIV PARK;4U
Adder
3.125
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.514
274776LINCOLN ;7U
Adder
4.514
274777LINCOLN ;8U
Adder
4.514
971611AH1-305 GEN
Solar/Wind Harmer
2.221
972228AH1-698 GEN2
Adder
1.977
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.866
274687WILL CNTY;4U
Adder
14.866
274675JOLIET 29;7U
Adder
16.29
274675JOLIET 29;7U
Adder
15.708
274728ELWOOD EC;5P
Adder
8.713
274731ELWOOD EC;2P
Adder
8.712
274733ELWOOD EC;3P
Adder
8.712
274735ELWOOD EC;4P
Adder
8.712
970833AG2-524 GEN
Solar/Wind Harmer
4.048
970833AG2-524 GEN
Solar/Wind Harmer
2.699
274744AC1-111 GEN8
Adder
2.931
274746AC1-111 G10
Adder
2.931
970073AG2-061 GEN
Solar/Wind Harmer
1.208
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
5.374
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.396
276861AD2-134 GEN
Solar/Wind Harmer
0.064
276863AD2-134 GEN
Solar/Wind Harmer
0.064
971171AH1-044 GEN
Solar/Wind Harmer
7.132
274823ROCKFORD ;21
Adder
9.94
926823AC1-168 GEN
Solar/Wind Harmer
0.603
970169AG2-114 GEN
Solar/Wind Harmer
3.545
274856ECOGROVE ;U1
Solar/Wind Harmer
0.083
24729505KEY G4
Adder
3.292
971681AH1-341 GEN
Solar/Wind Harmer
5.682
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
2.087
276741O09 GEN1
Solar/Wind Harmer
0.123
274877BISHOP HL;1U
Solar/Wind Harmer
0.116
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.643
963841AG1-237 GEN
Solar/Wind Harmer
1.491
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.921
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.549
970289AG2-191 GEN
Solar/Wind Harmer
0.635
964611AG1-324 GEN
Solar/Wind Harmer
1.3
276668AB2-070 GEN1
Solar/Wind Harmer
0.13
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.13
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
1.251
247536S-71 GEN
Solar/Wind Harmer
0.131
270543AE2-219 C
Solar/Wind Harmer
2.237
944221AF1-090 GEN
Solar/Wind Harmer
1.843
971029AG2-637 GEN
Solar/Wind Harmer
4.677
241886AC2-103 GEN2
Solar/Wind Helper
6.847
241985AE1-237 GEN
Solar/Wind Helper
0.134
241982AE2-343 S C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
20334926Z1-069 C
Solar/Wind Helper
0.646
23929302BS-PKR
50/50
2.775
958321AF2-126 GEN
Solar/Wind Harmer
1.137
23906402RICHG1
Adder
1.346
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.167
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
270505AE1-170 C O1
Solar/Wind Harmer
4.855
945111AF1-176 GEN
Solar/Wind Harmer
3.748
270588AE1-091_GEN
Solar/Wind Harmer
3.596
24695305TIMB G C
Solar/Wind Harmer
0.378
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.417
971347AH1-153 GEN
Solar/Wind Harmer
2.049
270043AE2-236 GEN
Solar/Wind Harmer
2.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
9.665
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274811UNIV PK N;7U
Adder
2.722
274803UNIV PARK;6U
Adder
3.135
274826FISK ;BP
Adder
5.877
972038AH1-567 GEN2
Adder
0.196
274887GEN-1.85
Solar/Wind Harmer
0.097
276843GEN-1.7
Solar/Wind Harmer
0.121
276806AD2-047 C O1
Solar/Wind Harmer
2.116
274772LINCOLN ;3U
Adder
4.514
972259AH1-714 GEN
Adder
10.137
274676JOLIET 29;8U
Adder
15.708
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
8.712
274730ELWOOD EC;6P
Adder
8.713
274734ELWOOD EC;8P
Adder
8.713
274736ELWOOD EC;9P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.078
943121AE2-341 GEN
Solar/Wind Harmer
6.131
943591AF1-030 GEN
Solar/Wind Harmer
4.077
274862TOP CROP ;2U
Solar/Wind Harmer
0.494
274682WAUKEGAN ;7U
Adder
9.362
276868AE1-113 GEN
Solar/Wind Harmer
0.722
274879MINONK ;1U
Solar/Wind Harmer
0.151
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.598
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
944531AF1-118 GEN
Solar/Wind Harmer
16.015
959091AF2-200 GEN
Solar/Wind Harmer
7.132
970571AG2-364 GEN
Solar/Wind Harmer
7.106
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
4.638
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.116
965091AG1-374 GEN
Solar/Wind Harmer
10.297
959611AF2-252 GEN
Solar/Wind Harmer
1.144
965931AG1-462 GEN
Solar/Wind Harmer
8.718
971087AG2-675 GEN
Solar/Wind Harmer
1.823
247642Z2-115 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.032
970289AG2-191 GEN
Solar/Wind Harmer
0.367
971993AH1-541 GEN
Solar/Wind Harmer
1.533
946031AF1-268 GEN
Solar/Wind Harmer
3.094
970825AG2-519 GEN
Solar/Wind Harmer
2.443
270004AE1-209 GEN
Solar/Wind Harmer
0.699
957381AF2-032 GEN
Solar/Wind Harmer
0.73
942481AE2-261 GEN
Solar/Wind Harmer
9.607
970193AG2-126 GEN
Solar/Wind Harmer
4.752
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728705AND G3
Adder
3.474
24728505AND G1
Adder
1.661
962511AG1-100 GEN
Solar/Wind Helper
0.35
24189902OREGON_CT2
50/50
4.122
23856402BAYSG1
50/50
1.575
23888702TROY G3
50/50
1.525
972253AH1-711 GEN
50/50
46.615
23920202STRYCT
50/50
1.928
241858AF1-205_GEN
Solar/Wind Harmer
3.781
23906502RICHG2&3
Adder
1.343
960841AF2-375 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
0.187
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.25
957891AF2-083 GEN
Solar/Wind Harmer
7.68
965421AG1-410 GEN
Solar/Wind Harmer
13.812
24639705ELKHART HY
Adder
0.098
965011AG1-365 GEN
Solar/Wind Harmer
4.252
270317AD1-130_GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.303
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
4.532
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.781
274812UNIV PK N;8U
Adder
2.722
274802UNIV PARK;5U
Adder
3.135
274773LINCOLN ;4U
Adder
4.514
274774LINCOLN ;5U
Adder
4.514
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.29
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.713
274674JOLIET 9 ;6U
Adder
8.16
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.594
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.362
274828WAUKEGAN ;BP
Adder
5.749
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.702
276882AE2-255 GEN
Solar/Wind Harmer
0.421
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.886
270024AE2-089 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
10.699
959081AF2-199 GEN
Solar/Wind Harmer
3.566
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.012
970569AG2-363 GEN
Solar/Wind Harmer
10.659
970819AG2-516 GEN
Solar/Wind Harmer
4.255
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276708O09 GEN2
Solar/Wind Harmer
0.123
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.858
965651AG1-433 GEN
Solar/Wind Harmer
1.011
958861AF2-177 GEN
Solar/Wind Harmer
1.481
963741AG1-226 GEN
Solar/Wind Harmer
7.998
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
3.712
270032AE2-172
Solar/Wind Harmer
2.209
276621W2-048 GEN
Solar/Wind Harmer
0.164
276903AD2-071 C
Solar/Wind Harmer
3.645
970825AG2-519 GEN
Solar/Wind Harmer
1.151
270005AE1-210 C O1
Solar/Wind Harmer
0.699
965911AG1-460 GEN
Solar/Wind Harmer
0.643
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.285
24728605AND G2
Adder
1.661
241885AC2-103 GEN1
Solar/Wind Helper
6.847
241807AE2-176_GEN
Solar/Wind Helper
1.645
203947AF1-006 C
Solar/Wind Helper
0.391
961971AG1-040 GEN
Solar/Wind Helper
0.342
203830AF1-094 GEN
Solar/Wind Helper
0.331
203979AG1-198 GEN
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
24190002OREGON_ST1
50/50
5.546
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.525
970621AG2-405 GEN
Solar/Wind Harmer
0.945
944231AF1-091 GEN
Solar/Wind Harmer
11.69
970623AG2-406 GEN
Solar/Wind Harmer
0.886
961051AF2-396 GEN
Solar/Wind Harmer
9.383
961051AF2-396 GEN
Solar/Wind Harmer
6.256
246937BC-WTG2
Solar/Wind Harmer
0.187
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.296
270246TR4_N_V150
Solar/Wind Harmer
0.028
270247TR4_N_V136
Solar/Wind Harmer
0.028
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
5.151
965791AG1-447 GEN
Solar/Wind Harmer
3.777
970349AG2-230 GEN
Solar/Wind Harmer
6.147
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.728
274808UNIV PK N;4U
Adder
2.71
274888KELLY CRK;1U
Solar/Wind Harmer
0.218
276776AD2-060 GEN
Solar/Wind Harmer
0.398
958011AF2-095 GEN
Solar/Wind Harmer
5.377
970941AG2-585 GEN
Solar/Wind Harmer
2.054
274770LINCOLN ;1U
Adder
4.514
274771LINCOLN ;2U
Adder
4.514
276897AD1-100 C
Solar/Wind Harmer
9.25
276893AG1-478 C
Solar/Wind Harmer
0.247
274674JOLIET 9 ;6U
Adder
8.16
958481AF2-142 GEN
Solar/Wind Harmer
5.484
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
1.462
274696ROCKY RD ;4P
Adder
5.935
274695ROCKY RD ;2P
Adder
5.798
274693ROCKY RD ;1P
Adder
5.741
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.968
274683WAUKEGAN ;8U
Adder
9.245
958491AF2-143 GEN
Solar/Wind Harmer
5.438
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
10.839
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
7.132
971343AH1-151 GEN
Solar/Wind Harmer
7.132
972235AH1-702 GEN1
Adder
1.284
972236AH1-702 GEN2
Adder
1.116
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.397
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.564
942111AE2-223 GEN
Solar/Wind Harmer
1.128
944541AF1-119 GEN
Solar/Wind Harmer
0.23
960971AF2-388 GEN
Solar/Wind Harmer
2.023
960611AF2-352 GEN
Solar/Wind Harmer
1.144
970241AG2-163 GEN
Solar/Wind Harmer
1.971
270031AE2-169
Solar/Wind Harmer
1.849
270599AE1-208 GEN
Solar/Wind Harmer
3.081
270201AC2-176 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.434
970291AG2-192 GEN
Solar/Wind Harmer
0.2
964611AG1-324 GEN
Solar/Wind Harmer
0.25
247621Y3-024
Adder
0.115
971613AH1-306 GEN
Solar/Wind Harmer
1.591
276615X2-022 GEN
Solar/Wind Harmer
0.034
276838X2-022 GEN2
Solar/Wind Harmer
0.185
25326509SID D
Adder
0.616
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
1.397
276916AD2-100_GEN
Solar/Wind Harmer
6.713
276911AD2-131_GEN
Solar/Wind Harmer
0.442
970883AG2-550 GEN
Solar/Wind Harmer
3.196
970885AG2-551 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
3.366
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
203835AF1-098 GEN
Solar/Wind Helper
1.351
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.135
254304AE2-114 C
Solar/Wind Helper
0.114
254305AE2-115 C
Solar/Wind Helper
0.114
962101AG1-054 GEN
Solar/Wind Helper
0.331
203804AE2-113_GEN
Solar/Wind Helper
0.87
940863AE2-074 GEN
Solar/Wind Helper
0.226
946381AF1-302 GEN
Solar/Wind Helper
0.105
990142J1224
External Queue
14.793254852294922
990527J1329
External Queue
2.0237011909484863
991177J1571 G
External Queue
15.794994354248047
991182J1586 G
External Queue
28.12165069580078
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.534
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.945
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.632
SIGELTFEXP_SIGE->PJM
CLTF
0.2
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.401
TVALTFEXP_TVA->PJM
CLTF
2.775

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.65 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:1922.03
MW Contribution:
2.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.382
24729305KEY G2
50/50
0.375
24729205KEY G1
50/50
0.374
247620Y3-023
50/50
0.478
960851AF2-376 GEN
50/50
2.145
24643105BUCHANAN
50/50
0.011
270102X2-052 ST
50/50
1.316
970583AG2-370 GEN
50/50
2.865
270142AC1-141 CT1_
50/50
2.081
24642205MAYFLWER
50/50
0.032
944961AF1-161 GEN
50/50
2.458
962601AG1-109 GEN
50/50
2.458
965021AG1-366 GEN
Solar/Wind Harmer
4.658
270043AE2-236 GEN
Solar/Wind Harmer
5.337
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
32.656
24695305TIMB G C
Solar/Wind Harmer
0.545
945111AF1-176 GEN
Solar/Wind Harmer
4.975
971347AH1-153 GEN
Solar/Wind Harmer
3.002
270505AE1-170 C O1
Solar/Wind Harmer
6.29
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.571
274752CRETE EC ;2U
Adder
6.49
274753CRETE EC ;3U
Adder
6.49
274724RIVER EC ;11
Adder
13.897
274814UNIV PK N;0U
Adder
3.935
274807UNIV PK N;3U
Adder
3.926
274811UNIV PK N;7U
Adder
3.9
274772LINCOLN ;3U
Adder
6.547
274803UNIV PARK;6U
Adder
4.495
274826FISK ;BP
Adder
8.431
972038AH1-567 GEN2
Adder
0.281
274887GEN-1.85
Solar/Wind Harmer
0.139
276843GEN-1.7
Solar/Wind Harmer
0.173
276806AD2-047 C O1
Solar/Wind Harmer
3.036
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.564
970707AG2-453 GEN
Solar/Wind Harmer
17.395
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.491
274729ELWOOD EC;1P
Adder
12.464
274730ELWOOD EC;6P
Adder
12.465
274734ELWOOD EC;8P
Adder
12.465
274736ELWOOD EC;9P
Adder
12.465
970289AG2-191 GEN
Solar/Wind Harmer
0.58
946031AF1-268 GEN
Solar/Wind Harmer
4.982
943121AE2-341 GEN
Solar/Wind Harmer
8.771
943591AF1-030 GEN
Solar/Wind Harmer
5.832
270004AE1-209 GEN
Solar/Wind Harmer
1.133
274862TOP CROP ;2U
Solar/Wind Harmer
0.701
970825AG2-519 GEN
Solar/Wind Harmer
3.908
274682WAUKEGAN ;7U
Adder
13.321
276868AE1-113 GEN
Solar/Wind Harmer
1.021
274879MINONK ;1U
Solar/Wind Harmer
0.213
946671AF1-331 GEN
Solar/Wind Harmer
0.54
274855GSG-6 ;RU
Solar/Wind Harmer
0.185
274850MENDOTA H;RU
Solar/Wind Harmer
0.059
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
5.046
959091AF2-200 GEN
Solar/Wind Harmer
10.069
970571AG2-364 GEN
Solar/Wind Harmer
9.976
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.581
274767LEE CO EC;8U
Adder
6.504
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.162
965091AG1-374 GEN
Solar/Wind Harmer
14.177
959611AF2-252 GEN
Solar/Wind Harmer
1.575
965931AG1-462 GEN
Solar/Wind Harmer
12.05
971087AG2-675 GEN
Solar/Wind Harmer
2.52
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.067
957381AF2-032 GEN
Solar/Wind Harmer
0.966
942481AE2-261 GEN
Solar/Wind Harmer
12.705
970193AG2-126 GEN
Solar/Wind Harmer
6.182
24728705AND G3
Adder
4.563
24728505AND G1
Adder
2.182
246938BC-WTG3
Solar/Wind Helper
11.03
942871AE2-306 GEN
Solar/Wind Helper
0.436
270284AF1-227 GEN1
Solar/Wind Helper
1.841
270287AF1-227 GEN3
Solar/Wind Helper
0.675
276820AF1-078_GEN
Solar/Wind Helper
0.321
270541AE2-072 C
Solar/Wind Helper
0.902
24729505KEY G4
50/50
6.995
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.016
270144AC1-141 ST1_
50/50
1.838
24344005CKG1
50/50
5.28
959331AF2-224 GEN
Solar/Wind Harmer
9.781
963791AG1-232 GEN
Solar/Wind Harmer
12.238
970031AG2-029 GEN
Solar/Wind Harmer
4.668
965041AG1-368 GEN
Solar/Wind Harmer
8.594
270071AF1-092 GEN
Solar/Wind Harmer
14.854
247521TR3_G114
Solar/Wind Harmer
0.267
965051AG1-369 GEN
Solar/Wind Harmer
3.677
971771AH1-392 GEN
Solar/Wind Harmer
6.058
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.946
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.189
274775LINCOLN ;6U
Adder
6.547
274776LINCOLN ;7U
Adder
6.547
274777LINCOLN ;8U
Adder
6.547
972037AH1-567 GEN1
Adder
0.141
274827FISK ;RP
Adder
5.975
274800UNIV PARK;3U
Adder
4.482
274801UNIV PARK;4U
Adder
4.482
960591AF2-350 GEN
Solar/Wind Harmer
5.357
972228AH1-698 GEN2
Adder
2.836
972227AH1-698 GEN1
Adder
1.997
274687WILL CNTY;4U
Adder
21.288
274687WILL CNTY;4U
Adder
21.288
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
23.324
274675JOLIET 29;7U
Adder
22.491
274728ELWOOD EC;5P
Adder
12.465
274731ELWOOD EC;2P
Adder
12.464
274733ELWOOD EC;3P
Adder
12.464
274735ELWOOD EC;4P
Adder
12.464
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.003
970833AG2-524 GEN
Solar/Wind Harmer
5.794
970833AG2-524 GEN
Solar/Wind Harmer
3.862
971611AH1-305 GEN
Solar/Wind Harmer
3.121
274744AC1-111 GEN8
Adder
4.189
274746AC1-111 G10
Adder
4.189
970073AG2-061 GEN
Solar/Wind Harmer
1.711
247536S-71 GEN
Solar/Wind Harmer
0.205
971411AH1-196 GEN
Solar/Wind Harmer
7.602
971675AH1-338 GEN
Solar/Wind Harmer
1.975
276861AD2-134 GEN
Solar/Wind Harmer
0.09
276863AD2-134 GEN
Solar/Wind Harmer
0.09
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
10.069
274823ROCKFORD ;21
Adder
14.017
274856ECOGROVE ;U1
Solar/Wind Harmer
0.116
926823AC1-168 GEN
Solar/Wind Harmer
0.847
970169AG2-114 GEN
Solar/Wind Harmer
4.974
971681AH1-341 GEN
Solar/Wind Harmer
7.978
971549AH1-272 GEN
Solar/Wind Harmer
10.208
972267AH1-718 GEN
Adder
2.917
276741O09 GEN1
Solar/Wind Harmer
0.172
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.162
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
5.047
946321AF1-296 GEN
Solar/Wind Harmer
2.661
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.041
270543AE2-219 C
Solar/Wind Harmer
3.242
276668AB2-070 GEN1
Solar/Wind Harmer
0.176
276848AB2-070 GEN3
Solar/Wind Harmer
0.175
276849AB2-070 GEN2
Solar/Wind Harmer
0.176
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
6.154
944221AF1-090 GEN
Solar/Wind Harmer
2.4
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.567
270223U2-072_GEN1
Solar/Wind Helper
0.859
270224U2-072_GEN2
Solar/Wind Helper
0.859
270227U2-072_GEN3
Solar/Wind Helper
0.859
270228U2-072_GEN4
Solar/Wind Helper
0.859
270231U2-072_GEN5
Solar/Wind Helper
0.859
966831AG1-554 GEN
Solar/Wind Helper
0.861
270499AE1-146 GEN
Solar/Wind Helper
1.911
945641AF1-229 GEN
Solar/Wind Helper
0.907
270100X2-052 CT1
50/50
1.216
270101X2-052 CT2
50/50
1.216
270246TR4_N_V150
Solar/Wind Harmer
0.047
270247TR4_N_V136
Solar/Wind Harmer
0.047
942221AE2-234 GEN
Solar/Wind Harmer
2.915
944231AF1-091 GEN
Solar/Wind Harmer
16.486
944541AF1-119 GEN
Solar/Wind Harmer
0.437
960971AF2-388 GEN
Solar/Wind Harmer
3.84
970349AG2-230 GEN
Solar/Wind Harmer
9.006
961051AF2-396 GEN
Solar/Wind Harmer
11.975
961051AF2-396 GEN
Solar/Wind Harmer
7.983
270031AE2-169
Solar/Wind Harmer
3.187
270599AE1-208 GEN
Solar/Wind Harmer
5.311
965681AG1-436 GEN
Solar/Wind Harmer
7.151
965791AG1-447 GEN
Solar/Wind Harmer
5.244
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.421
247621Y3-024
Adder
0.188
274805UNIV PK N;1U
Adder
3.909
274808UNIV PK N;4U
Adder
3.883
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.547
274771LINCOLN ;2U
Adder
6.547
274888KELLY CRK;1U
Solar/Wind Harmer
0.312
276776AD2-060 GEN
Solar/Wind Harmer
0.571
958011AF2-095 GEN
Solar/Wind Harmer
7.714
970941AG2-585 GEN
Solar/Wind Harmer
2.946
276897AD1-100 C
Solar/Wind Harmer
13.263
274674JOLIET 9 ;6U
Adder
11.68
276893AG1-478 C
Solar/Wind Harmer
0.353
970291AG2-192 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.317
971613AH1-306 GEN
Solar/Wind Harmer
2.514
958481AF2-142 GEN
Solar/Wind Harmer
7.796
274696ROCKY RD ;4P
Adder
8.451
274695ROCKY RD ;2P
Adder
8.256
274693ROCKY RD ;1P
Adder
8.175
274697ROCKY RD ;3P
Adder
2.243
274683WAUKEGAN ;8U
Adder
15.599
274683WAUKEGAN ;8U
Adder
13.149
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
15.403
958491AF2-143 GEN
Solar/Wind Harmer
7.702
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
10.069
971343AH1-151 GEN
Solar/Wind Harmer
10.069
972235AH1-702 GEN1
Adder
1.809
972236AH1-702 GEN2
Adder
1.573
938861AE1-114 GEN
Solar/Wind Harmer
2.807
274764LEE CO EC;5U
Adder
6.597
274765LEE CO EC;6U
Adder
6.597
274762LEE CO EC;3U
Adder
6.581
274763LEE CO EC;4U
Adder
6.519
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.787
276645AC1-214 GEN1
Solar/Wind Harmer
0.191
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.55
942111AE2-223 GEN
Solar/Wind Harmer
1.562
960611AF2-352 GEN
Solar/Wind Harmer
1.575
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.631
970885AG2-551 GEN
Solar/Wind Harmer
1.544
970241AG2-163 GEN
Solar/Wind Harmer
2.669
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.046
276838X2-022 GEN2
Solar/Wind Harmer
0.248
276916AD2-100_GEN
Solar/Wind Harmer
8.848
276911AD2-131_GEN
Solar/Wind Harmer
0.583
945391AF1-204 GEN
Solar/Wind Harmer
4.379
970623AG2-406 GEN
Solar/Wind Harmer
0.684
971587AH1-292 GEN
Solar/Wind Harmer
2.578
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.844
270462AD2-086
Solar/Wind Helper
3.683
247522W1-056 GEN
Solar/Wind Helper
1.146
253378AE2-206_GEN
Solar/Wind Helper
0.688
270349AD2-093_GEN
Solar/Wind Helper
0.824
270471AD2-092_GEN
Solar/Wind Helper
0.824
241960AC2-195 GEN
Solar/Wind Helper
0.664
960861AF2-377 GEN
50/50
2.456
970521AG2-332 GEN
50/50
11.157
24639705ELKHART HY
50/50
0.154
270143AC1-141 CT2_
50/50
2.081
24344105CKG2
50/50
6.284
24307105BERRINSP G
50/50
0.018
965011AG1-365 GEN
Solar/Wind Harmer
13.973
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.92
958861AF2-177 GEN
Solar/Wind Harmer
2.759
945111AF1-176 GEN
Solar/Wind Harmer
10.951
957891AF2-083 GEN
Solar/Wind Harmer
10.053
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.079
970373AG2-245 GEN
Solar/Wind Harmer
11.559
274751CRETE EC ;1U
Adder
6.49
274754CRETE EC ;4U
Adder
6.49
274723RIVER EC ;12
Adder
14.067
274812UNIV PK N;8U
Adder
3.9
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.547
274774LINCOLN ;5U
Adder
6.547
274802UNIV PARK;5U
Adder
4.495
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.946
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
23.324
274674JOLIET 9 ;6U
Adder
11.68
274732ELWOOD EC;7P
Adder
12.465
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.552
270594AE1-207 GEN
Solar/Wind Harmer
5.867
270032AE2-172
Solar/Wind Harmer
3.492
270005AE1-210 C O1
Solar/Wind Harmer
1.133
274745AC1-111 GEN9
Adder
4.189
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.845
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.842
274682WAUKEGAN ;7U
Adder
13.321
274828WAUKEGAN ;BP
Adder
8.177
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.874
939401AE1-172 GEN
Solar/Wind Harmer
3.83
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.596
971997AH1-543 GEN
Solar/Wind Harmer
2.669
957471AF2-041 GEN
Solar/Wind Harmer
15.103
959081AF2-199 GEN
Solar/Wind Harmer
5.034
971067AG2-660 GEN
Solar/Wind Harmer
1.678
274822ROCKFORD ;11
Adder
14.119
276903AD2-071 C
Solar/Wind Harmer
5.594
970819AG2-516 GEN
Solar/Wind Harmer
5.99
970569AG2-363 GEN
Solar/Wind Harmer
14.964
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.581
274766LEE CO EC;7U
Adder
6.504
276708O09 GEN2
Solar/Wind Harmer
0.172
276646AC1-214 GEN2
Solar/Wind Harmer
0.191
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.73
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.397
963741AG1-226 GEN
Solar/Wind Harmer
10.829
276621W2-048 GEN
Solar/Wind Harmer
0.22
965911AG1-460 GEN
Solar/Wind Harmer
0.85
24728605AND G2
Adder
2.182
970773AG2-487 GEN
Solar/Wind Harmer
0.657
246936BC-WTG1
Solar/Wind Helper
10.844
270317AD1-130_GEN
Solar/Wind Helper
4.072
270485AE1-090_GEN
Solar/Wind Helper
0.32
270391AF1-285 GEN3
Solar/Wind Helper
0.582
270578AF1-285 GEN2
Solar/Wind Helper
0.582
270286AF1-227 GEN2
Solar/Wind Helper
0.675
960841AF2-375 GEN
Solar/Wind Helper
1.143
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.75
NYPJM->LTFIMP_NY
CLTF
1.125
LGEELTFEXP_LGEE->PJM
CLTF
1.97
WECLTFEXP_WEC->PJM
CLTF
2.738
AG2-052LTFEXP_AG2-052->PJM
LTF
0.177
AH1-155LTFEXP_AH1-155->PJM
LTF
0.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.411
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.755
MECLTFEXP_MEC->PJM
CLTF
10.148
SIGELTFEXP_SIGE->PJM
CLTF
0.212
LAGNLTFEXP_LAGN->PJM
CLTF
6.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.165
TVALTFEXP_TVA->PJM
CLTF
2.538

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.79
MW Contribution:
3.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
24686405CER G5
Adder
8.833
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270367AC2-061_GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
5.121
942051AE2-217 GEN
Solar/Wind Harmer
12.564
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Harmer
0.57
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252507AC2-088 GEN
Solar/Wind Harmer
0.312
253394AE2-221_GEN
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
6.169
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
970191AG2-125 GEN
Solar/Wind Harmer
1.771
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
30.627
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
270004AE1-209 GEN
Solar/Wind Harmer
1.475
946031AF1-268 GEN
Solar/Wind Harmer
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.122
971985AH1-537 GEN
Solar/Wind Harmer
2.118
270263AC1-001 GEN
Solar/Wind Harmer
0.702
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.516
241972AD1-140 GEN
Solar/Wind Harmer
0.757
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.113
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
247536S-71 GEN
Solar/Wind Harmer
0.272
972163AH1-664 GEN
Solar/Wind Harmer
7.573
972165AH1-665 GEN
Solar/Wind Harmer
6.065
970289AG2-191 GEN
Solar/Wind Harmer
1.292
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
963791AG1-232 GEN
Solar/Wind Harmer
9.106
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.711
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.242
965051AG1-369 GEN
Solar/Wind Harmer
3.331
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270399AC1-101 GEN
Solar/Wind Harmer
2.112
270400AC1-102 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274744AC1-111 GEN8
Adder
5.296
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971073AG2-665 GEN
Solar/Wind Harmer
5.121
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
270054AF2-122 C O1
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
4.003
970329AG2-216 GEN
Solar/Wind Harmer
2.946
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
3.738
270599AE1-208 GEN
Solar/Wind Harmer
6.229
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.725
970349AG2-230 GEN
Solar/Wind Harmer
10.122
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.761
965681AG1-436 GEN
Solar/Wind Harmer
8.373
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
32.401
970149AG2-104 GEN
Solar/Wind Harmer
17.497
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
253398AE2-221_GEN2
Solar/Wind Harmer
0
252516AE2-318_GEN
Solar/Wind Harmer
7.753
252510AF1-249 C
Solar/Wind Harmer
0.052
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
965651AG1-433 GEN
Solar/Wind Harmer
2.002
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5
945371AF1-202 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270317AD1-130_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
970773AG2-487 GEN
Solar/Wind Harmer
1.2
276903AD2-071 C
Solar/Wind Harmer
7.58
270024AE2-089 GEN
Solar/Wind Harmer
0.001
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.743
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
941551AE2-152 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.463
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
939401AE1-172 GEN
Solar/Wind Harmer
4.951
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.213
962781AG1-127 GEN
Solar/Wind Harmer
6.263
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
19.691
971403AH1-188 GEN
Solar/Wind Harmer
9.18
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
16.585
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
958171AF2-111 GEN
Solar/Wind Harmer
16.988
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
971347AH1-153 GEN
Solar/Wind Harmer
3.374
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.73
965021AG1-366 GEN
Solar/Wind Harmer
2.244
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
24386205FR-12G C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
276843GEN-1.7
Solar/Wind Harmer
0.215
276806AD2-047 C O1
Solar/Wind Harmer
3.764
274803UNIV PARK;6U
Adder
5.55
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
970707AG2-453 GEN
Solar/Wind Harmer
21.689
972259AH1-714 GEN
Adder
18.154
24695305TIMB G C
Solar/Wind Harmer
0.562
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
246938BC-WTG3
Solar/Wind Harmer
0.239
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
274682WAUKEGAN ;7U
Adder
3.428
276868AE1-113 GEN
Solar/Wind Harmer
1.318
274879MINONK ;1U
Solar/Wind Harmer
0.275
965091AG1-374 GEN
Solar/Wind Harmer
19.702
959611AF2-252 GEN
Solar/Wind Harmer
2.189
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
959091AF2-200 GEN
Solar/Wind Harmer
11.056
274746AC1-111 G10
Adder
5.296
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.598
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270007AE1-245 C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.91
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
971171AH1-044 GEN
Solar/Wind Harmer
11.056
965791AG1-447 GEN
Solar/Wind Harmer
6.14
970241AG2-163 GEN
Solar/Wind Harmer
3.903
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
270247TR4_N_V136
Solar/Wind Harmer
0.043
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
972043AH1-570 GEN
Solar/Wind Harmer
1.73
972045AH1-571 GEN
Solar/Wind Harmer
1.386
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
276776AD2-060 GEN
Solar/Wind Harmer
0.708
958011AF2-095 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
958481AF2-142 GEN
Solar/Wind Harmer
9.909
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
958491AF2-143 GEN
Solar/Wind Harmer
9.89
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
971125AH1-004 GEN
Solar/Wind Harmer
2.63
970107AG2-081 GEN
Solar/Wind Harmer
1.973
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601

Details for 05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05BELMON-01BELMNT 765.0/500.0 kV Ckt 5 transformer
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.79 %
Rating:4000.0 MVA
Rating Type:B
MVA to Mitigate:4031.62
MW Contribution:
3.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
5.522
24289405MTG1
50/50
6.078
243186AF1-051 GEN
50/50
6.83
962761AG1-125 GEN
Solar/Wind Harmer
32.401
970149AG2-104 GEN
Solar/Wind Harmer
17.497
970155AG2-107 GEN
Solar/Wind Harmer
20.69
972203AH1-686 GEN
Adder
2.528
24723205RIVRG3
Adder
20.281
24686505CER G6
Adder
8.903
960001AF2-291 GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.719
971073AG2-665 GEN
Solar/Wind Harmer
1.164
253333AC1-068 GEN
Solar/Wind Harmer
0.008
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.935
253398AE2-221_GEN2
Solar/Wind Harmer
0
252516AE2-318_GEN
Solar/Wind Harmer
7.753
252510AF1-249 C
Solar/Wind Harmer
0.052
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25326309TAIT D
Adder
1.084
25196808ZIMRHP
Adder
74.904
970091AG2-072 GEN
Adder
75.485
25196008MFTGT1
Adder
1.367
965651AG1-433 GEN
Solar/Wind Harmer
2.002
958861AF2-177 GEN
Solar/Wind Harmer
2.956
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5
945371AF1-202 GEN
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.835
270317AD1-130_GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.475
270594AE1-207 GEN
Solar/Wind Harmer
7.616
270032AE2-172
Solar/Wind Harmer
4.533
970825AG2-519 GEN
Solar/Wind Harmer
2.414
970773AG2-487 GEN
Solar/Wind Harmer
1.2
276903AD2-071 C
Solar/Wind Harmer
7.58
270024AE2-089 GEN
Solar/Wind Harmer
0.001
944971AF1-162 GEN
Solar/Wind Harmer
6.766
940581AE2-045 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
6.731
971605AH1-302 GEN
Solar/Wind Harmer
8.413
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.743
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.696
270055AF2-134 C O1
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
14.104
963741AG1-226 GEN
Solar/Wind Harmer
15.834
24639705ELKHART HY
Adder
0.147
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
7.861
274754CRETE EC ;4U
Adder
7.861
274723RIVER EC ;12
Adder
17.091
957891AF2-083 GEN
Solar/Wind Harmer
11.089
945111AF1-176 GEN
Solar/Wind Harmer
11.868
274812UNIV PK N;8U
Adder
4.772
274802UNIV PARK;5U
Adder
5.55
941551AE2-152 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.463
965421AG1-410 GEN
Solar/Wind Harmer
19.9
274732ELWOOD EC;7P
Adder
15.615
274676JOLIET 29;8U
Adder
29.146
274674JOLIET 9 ;6U
Adder
14.625
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.267
270489AE1-102 GEN1
Solar/Wind Harmer
0.861
939401AE1-172 GEN
Solar/Wind Harmer
4.951
274745AC1-111 GEN9
Adder
5.296
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.073
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.457
276882AE2-255 GEN
Solar/Wind Harmer
0.769
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.213
962781AG1-127 GEN
Solar/Wind Harmer
6.263
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
19.691
971403AH1-188 GEN
Solar/Wind Harmer
9.18
23751101LEADS_P59
Solar/Wind Helper
2.597
238185AF2-356 C
Solar/Wind Helper
2.387
23583801GRNGAP
Solar/Wind Helper
4.45
238120AE2-309 GEN
Solar/Wind Helper
0.461
316095T157 G97
Solar/Wind Helper
1.19
238126S14_GEN_1
Solar/Wind Helper
0.726
238109AE1-109 GEN2
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
16.585
959081AF2-199 GEN
Solar/Wind Harmer
5.528
971067AG2-660 GEN
Solar/Wind Harmer
1.843
24318805MLG1
50/50
7.624
24289405MTG1
50/50
6.078
24721905FLATG4
Adder
26.83
962771AG1-126 GEN
Solar/Wind Harmer
32.401
970153AG2-106 GEN
Solar/Wind Harmer
20.69
24686405CER G5
Adder
8.833
971191AH1-055 GEN
Solar/Wind Harmer
18.814
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270367AC2-061_GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
5.121
942051AE2-217 GEN
Solar/Wind Harmer
12.564
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Harmer
0.57
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.015
252507AC2-088 GEN
Solar/Wind Harmer
0.312
253394AE2-221_GEN
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
3.611
961921AG1-034 GEN
Solar/Wind Harmer
6.169
253370AE2-315 SEC1
Adder
1.983
253371AE2-315 SEC2
Adder
1.876
25194608D.CRK4
Adder
1.627
25196608WSDLE5
Adder
8.482
270391AF1-285 GEN3
Solar/Wind Harmer
0.46
970191AG2-125 GEN
Solar/Wind Harmer
1.771
25196008MFTGT1
Adder
1.324
944531AF1-118 GEN
Solar/Wind Harmer
30.627
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.449
270004AE1-209 GEN
Solar/Wind Harmer
1.475
946031AF1-268 GEN
Solar/Wind Harmer
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.748
247642Z2-115 C
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.122
958171AF2-111 GEN
Solar/Wind Harmer
16.988
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.19
270043AE2-236 GEN
Solar/Wind Harmer
4.345
971347AH1-153 GEN
Solar/Wind Harmer
3.374
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.73
965021AG1-366 GEN
Solar/Wind Harmer
2.244
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
24386205FR-12G C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
8.061
274752CRETE EC ;2U
Adder
7.861
274753CRETE EC ;3U
Adder
7.861
274724RIVER EC ;11
Adder
16.891
270505AE1-170 C O1
Solar/Wind Harmer
6.985
945111AF1-176 GEN
Solar/Wind Harmer
5.391
274814UNIV PK N;0U
Adder
4.814
274807UNIV PK N;3U
Adder
4.804
274811UNIV PK N;7U
Adder
4.772
970193AG2-126 GEN
Solar/Wind Harmer
9.971
274887GEN-1.85
Solar/Wind Harmer
0.173
276843GEN-1.7
Solar/Wind Harmer
0.215
276806AD2-047 C O1
Solar/Wind Harmer
3.764
274803UNIV PARK;6U
Adder
5.55
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
10.419
972038AH1-567 GEN2
Adder
0.347
970707AG2-453 GEN
Solar/Wind Harmer
21.689
972259AH1-714 GEN
Adder
18.154
24695305TIMB G C
Solar/Wind Harmer
0.562
274729ELWOOD EC;1P
Adder
15.615
274730ELWOOD EC;6P
Adder
15.615
274734ELWOOD EC;8P
Adder
15.615
274736ELWOOD EC;9P
Adder
15.615
274676JOLIET 29;8U
Adder
28.105
246938BC-WTG3
Solar/Wind Harmer
0.239
270491AE1-102 GEN2
Solar/Wind Harmer
0.861
943121AE2-341 GEN
Solar/Wind Harmer
11.086
943591AF1-030 GEN
Solar/Wind Harmer
7.372
274862TOP CROP ;2U
Solar/Wind Harmer
0.892
274682WAUKEGAN ;7U
Adder
3.428
276868AE1-113 GEN
Solar/Wind Harmer
1.318
274879MINONK ;1U
Solar/Wind Harmer
0.275
965091AG1-374 GEN
Solar/Wind Harmer
19.702
959611AF2-252 GEN
Solar/Wind Harmer
2.189
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274855GSG-6 ;RU
Solar/Wind Harmer
0.24
274850MENDOTA H;RU
Solar/Wind Harmer
0.076
970571AG2-364 GEN
Solar/Wind Harmer
13.127
23562501BACKB
Solar/Wind Helper
1.069
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.896
238127S14_GEN_2
Solar/Wind Helper
0.726
238108AE1-109 GEN1
Solar/Wind Helper
0.096
238110AE1-109 GEN3
Solar/Wind Helper
0.096
238175AF1-290_GEN
Solar/Wind Helper
0.12
959091AF2-200 GEN
Solar/Wind Harmer
11.056
971985AH1-537 GEN
Solar/Wind Harmer
2.118
270263AC1-001 GEN
Solar/Wind Harmer
0.702
943861AF1-054 GEN
Solar/Wind Harmer
2.699
943851AF1-053 GEN
Solar/Wind Harmer
1.869
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270432AC2-029 GEN
Solar/Wind Harmer
3.104
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.516
241972AD1-140 GEN
Solar/Wind Harmer
0.757
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.113
253372AE2-315 SEC3
Adder
1.876
253372AE2-315 SEC3
Adder
1.876
25196408WSDLE3
Adder
8.732
25196308WSDLE2
Adder
8.656
25196208WSDLE1
Adder
8.634
25196708WSDLE6
Adder
8.613
25196508WSDLE4
Adder
8.396
25306009OHH W.
Adder
2.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.46
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.399
24729505KEY G4
Adder
6.352
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.224
270071AF1-092 GEN
Solar/Wind Harmer
13.05
270543AE2-219 C
Solar/Wind Harmer
4.766
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.957
247536S-71 GEN
Solar/Wind Harmer
0.272
972163AH1-664 GEN
Solar/Wind Harmer
7.573
972165AH1-665 GEN
Solar/Wind Harmer
6.065
970289AG2-191 GEN
Solar/Wind Harmer
1.292
971609AH1-304 GEN
Solar/Wind Harmer
1.11
964611AG1-324 GEN
Solar/Wind Harmer
2.65
270356AE2-297 GEN
Solar/Wind Harmer
0
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
15.098
963791AG1-232 GEN
Solar/Wind Harmer
9.106
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.711
971611AH1-305 GEN
Solar/Wind Harmer
4.007
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.905
960681AF2-359 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.625
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.682
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.242
965051AG1-369 GEN
Solar/Wind Harmer
3.331
965041AG1-368 GEN
Solar/Wind Harmer
6.672
270399AC1-101 GEN
Solar/Wind Harmer
2.112
270400AC1-102 GEN
Solar/Wind Harmer
2.112
339216AC1-074 GEN
Solar/Wind Harmer
0.178
274775LINCOLN ;6U
Adder
8.061
274776LINCOLN ;7U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
960591AF2-350 GEN
Solar/Wind Harmer
6.642
972228AH1-698 GEN2
Adder
3.526
972227AH1-698 GEN1
Adder
2.483
972037AH1-567 GEN1
Adder
0.174
274827FISK ;RP
Adder
7.384
274800UNIV PARK;3U
Adder
5.548
274801UNIV PARK;4U
Adder
5.548
274687WILL CNTY;4U
Adder
26.551
274687WILL CNTY;4U
Adder
26.551
274728ELWOOD EC;5P
Adder
15.615
274731ELWOOD EC;2P
Adder
15.615
274733ELWOOD EC;3P
Adder
15.615
274735ELWOOD EC;4P
Adder
15.615
274675JOLIET 29;7U
Adder
29.146
274675JOLIET 29;7U
Adder
28.105
970833AG2-524 GEN
Solar/Wind Harmer
7.29
970833AG2-524 GEN
Solar/Wind Harmer
4.86
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.839
274744AC1-111 GEN8
Adder
5.296
274746AC1-111 G10
Adder
5.296
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
6.598
970073AG2-061 GEN
Solar/Wind Harmer
2.198
270119AB2-067 GEN1
50/50
5.522
270120AB2-067 GEN2
50/50
5.522
243186AF1-051 GEN
50/50
6.83
24318905MLG2
50/50
4.385
24723005RIVRG1
Adder
20.281
24723105RIVRG2
Adder
20.281
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.467
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971073AG2-665 GEN
Solar/Wind Harmer
5.121
970879AG2-548 GEN
Solar/Wind Harmer
1.164
252509AD1-136 GEN
Solar/Wind Harmer
0.035
25183208HLCRTG
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.983
25194408D.CRK1
Adder
7.485
25194508D.CRK3
Adder
1.399
25326109MON D
Adder
1.301
25322209TAIT E
Adder
9.645
25322209TAIT E
Adder
9.428
270054AF2-122 C O1
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
4.003
970329AG2-216 GEN
Solar/Wind Harmer
2.946
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.69
24728905RICHG2
Adder
3.69
970883AG2-550 GEN
Solar/Wind Harmer
6.808
970885AG2-551 GEN
Solar/Wind Harmer
2.269
270462AD2-086
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.264
970291AG2-192 GEN
Solar/Wind Harmer
0.884
25326509SID D
Adder
1.282
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247621Y3-024
Adder
0.235
270031AE2-169
Solar/Wind Harmer
3.738
270599AE1-208 GEN
Solar/Wind Harmer
6.229
964611AG1-324 GEN
Solar/Wind Harmer
0.51
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.725
970349AG2-230 GEN
Solar/Wind Harmer
10.122
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.804
971655AH1-328 GEN
Solar/Wind Harmer
2.387
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.761
965681AG1-436 GEN
Solar/Wind Harmer
8.373
965791AG1-447 GEN
Solar/Wind Harmer
6.14
970241AG2-163 GEN
Solar/Wind Harmer
3.903
971587AH1-292 GEN
Solar/Wind Harmer
4.898
270246TR4_N_V150
Solar/Wind Harmer
0.043
270247TR4_N_V136
Solar/Wind Harmer
0.043
270007AE1-245 C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.91
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.116
276861AD2-134 GEN
Solar/Wind Harmer
0.117
276863AD2-134 GEN
Solar/Wind Harmer
0.117
971675AH1-338 GEN
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
9.845
23750701CROSSCHOOL
Solar/Wind Helper
1.294
238118U2-030_1
Solar/Wind Helper
0.306
23750501ELLIOTTS
Solar/Wind Helper
0.628
971171AH1-044 GEN
Solar/Wind Harmer
11.056
247620Y3-023
Adder
0.44
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
972043AH1-570 GEN
Solar/Wind Harmer
1.73
972045AH1-571 GEN
Solar/Wind Harmer
1.386
274805UNIV PK N;1U
Adder
4.783
274808UNIV PK N;4U
Adder
4.751
945391AF1-204 GEN
Solar/Wind Harmer
7.062
274888KELLY CRK;1U
Solar/Wind Harmer
0.387
276776AD2-060 GEN
Solar/Wind Harmer
0.708
958011AF2-095 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
3.653
276897AD1-100 C
Solar/Wind Harmer
16.602
961051AF2-396 GEN
Solar/Wind Harmer
13.281
961051AF2-396 GEN
Solar/Wind Harmer
8.854
274674JOLIET 9 ;6U
Adder
14.625
276893AG1-478 C
Solar/Wind Harmer
0.442
246937BC-WTG2
Solar/Wind Harmer
0.267
958481AF2-142 GEN
Solar/Wind Harmer
9.909
276901AD2-066 C O1
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
10.771
274695ROCKY RD ;2P
Adder
10.523
274693ROCKY RD ;1P
Adder
10.419
274697ROCKY RD ;3P
Adder
2.859
958491AF2-143 GEN
Solar/Wind Harmer
9.89
962691AG1-118 GEN
Solar/Wind Harmer
19.752
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.139
971125AH1-004 GEN
Solar/Wind Harmer
2.63
970107AG2-081 GEN
Solar/Wind Harmer
1.973
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.189
23751201ROTHROCK
Solar/Wind Helper
0.867
23585401KL_K28_T16
Solar/Wind Helper
1.41
235054AD2-180 GEN
Solar/Wind Helper
1.875
238117U2-030
Solar/Wind Helper
0.306
235531U2-073 GEN
Solar/Wind Helper
2.924
316097T157 G90
Solar/Wind Helper
1.19
971341AH1-150 GEN
Solar/Wind Harmer
11.056
971343AH1-151 GEN
Solar/Wind Harmer
11.056
CPLELTFEXP_CPLE->PJM
CLTF
2.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.961
NYPJM->LTFIMP_NY
CLTF
4.02
LGEELTFEXP_LGEE->PJM
CLTF
6.53
WECLTFEXP_WEC->PJM
CLTF
3.585
AG2-052LTFEXP_AG2-052->PJM
LTF
0.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.334
CBM West 1LTFEXP_CBM-W1->PJM
CBM
131.169
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.834
MECLTFEXP_MEC->PJM
CLTF
15.181
SIGELTFEXP_SIGE->PJM
CLTF
0.488
LAGNLTFEXP_LAGN->PJM
CLTF
15.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.297
TVALTFEXP_TVA->PJM
CLTF
7.601

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2430.97
MW Contribution:
1.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971277AH1-098 GEN
Solar/Wind Harmer
2.311
24728205BUCHG1
Adder
3.63
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
966021AG1-471 GEN
Solar/Wind Harmer
2.29
971485AH1-239 GEN
Solar/Wind Harmer
3.377
964781AG1-341 GEN
Solar/Wind Harmer
4.305
942891AE2-308 GEN
Solar/Wind Harmer
3.798
964571AG1-320 GEN
Solar/Wind Harmer
3.443
971125AH1-004 GEN
Solar/Wind Harmer
1.471
970107AG2-081 GEN
Solar/Wind Harmer
1.103
972043AH1-570 GEN
Solar/Wind Harmer
0.938
972045AH1-571 GEN
Solar/Wind Harmer
0.751
971587AH1-292 GEN
Solar/Wind Harmer
2.505
276916AD2-100_GEN
Solar/Wind Harmer
7.095
276911AD2-131_GEN
Solar/Wind Harmer
0.467
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.188
945391AF1-204 GEN
Solar/Wind Harmer
3.538
960611AF2-352 GEN
Solar/Wind Harmer
1.092
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.528
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274764LEE CO EC;5U
Adder
4.358
274765LEE CO EC;6U
Adder
4.358
274762LEE CO EC;3U
Adder
4.348
274763LEE CO EC;4U
Adder
4.307
970241AG2-163 GEN
Solar/Wind Harmer
1.901
938861AE1-114 GEN
Solar/Wind Harmer
1.845
972235AH1-702 GEN1
Adder
1.172
972236AH1-702 GEN2
Adder
1.019
971341AH1-150 GEN
Solar/Wind Harmer
6.475
971343AH1-151 GEN
Solar/Wind Harmer
6.475
252509AD1-136 GEN
Solar/Wind Harmer
0.016
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.364
962691AG1-118 GEN
Solar/Wind Harmer
9.643
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.815
25183208HLCRTG
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
25194508D.CRK3
Adder
0.65
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.064
274697ROCKY RD ;3P
Adder
1.389
958481AF2-142 GEN
Solar/Wind Harmer
4.795
24728805RICHG1
Adder
1.729
24728905RICHG2
Adder
1.729
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.01
276893AG1-478 C
Solar/Wind Harmer
0.212
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
7.927
274888KELLY CRK;1U
Solar/Wind Harmer
0.184
276776AD2-060 GEN
Solar/Wind Harmer
0.337
958011AF2-095 GEN
Solar/Wind Harmer
4.553
970941AG2-585 GEN
Solar/Wind Harmer
1.739
926881AC1-175 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.41
970291AG2-192 GEN
Solar/Wind Harmer
0.189
971613AH1-306 GEN
Solar/Wind Harmer
1.512
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.712
270599AE1-208 GEN
Solar/Wind Harmer
2.854
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
3.108
970885AG2-551 GEN
Solar/Wind Harmer
1.036
964611AG1-324 GEN
Solar/Wind Harmer
0.233
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.205
960971AF2-388 GEN
Solar/Wind Harmer
1.8
965681AG1-436 GEN
Solar/Wind Harmer
3.818
965791AG1-447 GEN
Solar/Wind Harmer
2.8
942221AE2-234 GEN
Solar/Wind Harmer
1.218
970349AG2-230 GEN
Solar/Wind Harmer
4.536
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
237061AD1-155 GEN
Solar/Wind Helper
0.84
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238147AE2-230_GEN1
Solar/Wind Helper
0.214
238148AE2-230_GEN2
Solar/Wind Helper
0.214
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316312AB1-027
Solar/Wind Helper
0.234
316097T157 G90
Solar/Wind Helper
0.557
316045AC1-158 PL2
Solar/Wind Helper
2.117
316450AC1-158 RIC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.609
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
316487AF1-042 GEN
Solar/Wind Helper
0.113
24735205WLF2G2
50/50
5.207
24728305BUCHG2
Adder
3.63
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971403AH1-188 GEN
Solar/Wind Harmer
6.407
944971AF1-162 GEN
Solar/Wind Harmer
4.503
24723205RIVRG3
Adder
11.612
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
6.034
24686505CER G6
Adder
4.748
970653AG2-424 GEN
Solar/Wind Harmer
1.862
3429241JKCT 3G
Adder
6.43
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.003
943811AF1-049 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
38.065
945681AF1-233 GEN
Solar/Wind Harmer
6.517
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
0.167
25196008MFTGT1
Adder
0.654
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.116
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
25196808ZIMRHP
Adder
35.505
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.566
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.348
274766LEE CO EC;7U
Adder
4.297
963741AG1-226 GEN
Solar/Wind Harmer
7.714
970819AG2-516 GEN
Solar/Wind Harmer
3.898
274822ROCKFORD ;11
Adder
9.119
970569AG2-363 GEN
Solar/Wind Harmer
9.723
957471AF2-041 GEN
Solar/Wind Harmer
9.712
959081AF2-199 GEN
Solar/Wind Harmer
3.237
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.689
276882AE2-255 GEN
Solar/Wind Harmer
0.375
962781AG1-127 GEN
Solar/Wind Harmer
3.062
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
0.568
276805AD2-038 GEN
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.024
252516AE2-318_GEN
Solar/Wind Harmer
3.594
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
939401AE1-172 GEN
Solar/Wind Harmer
2.397
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
274745AC1-111 GEN9
Adder
2.557
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
274676JOLIET 29;8U
Adder
13.963
276903AD2-071 C
Solar/Wind Harmer
3.542
941551AE2-152 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.159
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.314
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
3.938
270594AE1-207 GEN
Solar/Wind Harmer
3.528
270032AE2-172
Solar/Wind Harmer
2.1
970825AG2-519 GEN
Solar/Wind Harmer
1.115
270005AE1-210 C O1
Solar/Wind Harmer
0.68
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.068
958381AF2-132 GEN
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.5
958861AF2-177 GEN
Solar/Wind Harmer
1.334
965651AG1-433 GEN
Solar/Wind Harmer
0.9
270024AE2-089 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Helper
0.287
316499AE2-029_GEN
Solar/Wind Helper
0.937
315821AE2-092 GEN
Solar/Wind Helper
1.831
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
23583801GRNGAP
Solar/Wind Helper
2.128
316095T157 G97
Solar/Wind Helper
0.557
316075AC2-137 C
Solar/Wind Helper
0.18
316223AC1-118
Solar/Wind Helper
0.174
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
970563AG2-360 GEN
50/50
26.903
24689505VACITY
50/50
3.164
943031AE2-326 GEN
Solar/Wind Harmer
3.912
962751AG1-124 GEN
Solar/Wind Harmer
6.205
960911AF2-382 GEN
Solar/Wind Harmer
4.078
971461AH1-227 GEN
Solar/Wind Harmer
2.687
972103AH1-617 GEN
Solar/Wind Harmer
9.709
972273AH1-721 GEN
Adder
50.356
24686405CER G5
Adder
4.71
970093AG2-073 GEN
Solar/Wind Harmer
3.273
970653AG2-424 GEN
Solar/Wind Harmer
0.386
270030AE2-140 GEN
Solar/Wind Harmer
7.666
970455AG2-298 GEN
Solar/Wind Harmer
1.477
3429391JKCT 9G
Adder
4.482
972167AH1-666 GEN
Solar/Wind Harmer
2.762
958171AF2-111 GEN
Solar/Wind Harmer
8.524
942481AE2-261 GEN
Solar/Wind Harmer
10.082
957381AF2-032 GEN
Solar/Wind Harmer
0.764
970193AG2-126 GEN
Solar/Wind Harmer
4.994
971993AH1-541 GEN
Solar/Wind Harmer
1.535
965931AG1-462 GEN
Solar/Wind Harmer
8.44
971087AG2-675 GEN
Solar/Wind Harmer
1.765
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.771
24728505AND G1
Adder
1.803
965091AG1-374 GEN
Solar/Wind Harmer
9.832
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.109
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.348
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
270367AC2-061_GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.482
959091AF2-200 GEN
Solar/Wind Harmer
6.475
252507AC2-088 GEN
Solar/Wind Harmer
0.146
274855GSG-6 ;RU
Solar/Wind Harmer
0.118
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276868AE1-113 GEN
Solar/Wind Harmer
0.643
274879MINONK ;1U
Solar/Wind Harmer
0.134
24386205FR-12G C
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
1.674
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
25196608WSDLE5
Adder
3.933
274862TOP CROP ;2U
Solar/Wind Harmer
0.432
943121AE2-341 GEN
Solar/Wind Harmer
5.351
943591AF1-030 GEN
Solar/Wind Harmer
3.559
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.187
274729ELWOOD EC;1P
Adder
7.484
274730ELWOOD EC;6P
Adder
7.484
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
3.003
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.354
274887GEN-1.85
Solar/Wind Harmer
0.082
276843GEN-1.7
Solar/Wind Harmer
0.102
276806AD2-047 C O1
Solar/Wind Harmer
1.792
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
4.107
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970825AG2-519 GEN
Solar/Wind Harmer
2.365
270004AE1-209 GEN
Solar/Wind Harmer
0.68
946031AF1-268 GEN
Solar/Wind Harmer
2.979
964401AG1-302 GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
7.973
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.643
970191AG2-125 GEN
Solar/Wind Harmer
0.781
944531AF1-118 GEN
Solar/Wind Harmer
13.572
24735105WLF2G1
50/50
5.207
24734705WLF1G3
50/50
5.196
24734805WLF1G4
50/50
5.196
24734905WLF1G5
50/50
5.196
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.671
971313AH1-133 GEN
Solar/Wind Harmer
2.637
970281AG2-184 GEN
Solar/Wind Harmer
10.194
270399AC1-101 GEN
Solar/Wind Harmer
1.444
270400AC1-102 GEN
Solar/Wind Harmer
1.444
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
10.049
3429211JKCT 2G
Adder
6.347
339216AC1-074 GEN
Solar/Wind Harmer
0.095
972163AH1-664 GEN
Solar/Wind Harmer
3.863
972165AH1-665 GEN
Solar/Wind Harmer
3.094
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.131
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.131
946321AF1-296 GEN
Solar/Wind Harmer
1.85
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
274854TWINGROVE;U2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.109
276741O09 GEN1
Solar/Wind Harmer
0.116
972267AH1-718 GEN
Adder
1.953
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.424
971681AH1-341 GEN
Solar/Wind Harmer
5.242
274856ECOGROVE ;U1
Solar/Wind Harmer
0.076
274823ROCKFORD ;21
Adder
9.053
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
971171AH1-044 GEN
Solar/Wind Harmer
6.475
970169AG2-114 GEN
Solar/Wind Harmer
3.232
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276863AD2-134 GEN
Solar/Wind Harmer
0.058
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
25196508WSDLE4
Adder
3.893
274744AC1-111 GEN8
Adder
2.557
274746AC1-111 G10
Adder
2.557
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.499
970833AG2-524 GEN
Solar/Wind Harmer
2.333
274728ELWOOD EC;5P
Adder
7.484
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
274735ELWOOD EC;4P
Adder
7.484
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
960591AF2-350 GEN
Solar/Wind Harmer
3.162
970289AG2-191 GEN
Solar/Wind Harmer
0.599
971611AH1-305 GEN
Solar/Wind Harmer
1.876
971985AH1-537 GEN
Solar/Wind Harmer
0.936
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
4.672
971609AH1-304 GEN
Solar/Wind Harmer
0.508
270543AE2-219 C
Solar/Wind Harmer
2.176
253406AD2-031_GEN
Solar/Wind Harmer
0.23
964611AG1-324 GEN
Solar/Wind Harmer
1.21
247536S-71 GEN
Solar/Wind Harmer
0.124
945581AF1-223 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
5.772
315616AA1-038_C
Solar/Wind Helper
1.809
3148463FAIRFLD
Solar/Wind Helper
0.399
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316258AE1-075 C
Solar/Wind Helper
0.181
316405AF2-144 C
Solar/Wind Helper
0.151
316164AC1-076 GEN
Solar/Wind Helper
0.62
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.113
971347AH1-153 GEN
Solar/Wind Harmer
1.512
3147983MERCK5
Solar/Wind Helper
0.108
316192AB2-158 GEN
Solar/Wind Helper
0.989
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
3146776BUCKING
Solar/Wind Helper
0.05
238152AF2-075_GEN
Solar/Wind Helper
0.306
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.173
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.959
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
WECLTFEXP_WEC->PJM
CLTF
1.782
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
TVALTFEXP_TVA->PJM
CLTF
6.216

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
2.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
3147312GRETNA
Solar/Wind Harmer
0.047
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
5.335
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
0.947
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
960001AF2-291 GEN
Solar/Wind Harmer
0
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
945681AF1-233 GEN
Solar/Wind Harmer
12.766
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
7.186
252510AF1-249 C
Solar/Wind Harmer
0.048
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
276621W2-048 GEN
Solar/Wind Harmer
0.315
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.798
253398AE2-221_GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24385905FR-11G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
276903AD2-071 C
Solar/Wind Harmer
6.875
970819AG2-516 GEN
Solar/Wind Harmer
7.371
970569AG2-363 GEN
Solar/Wind Harmer
18.425
274822ROCKFORD ;11
Adder
17.258
957471AF2-041 GEN
Solar/Wind Harmer
18.391
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
274745AC1-111 GEN9
Adder
4.865
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
941551AE2-152 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
7.838
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
6.744
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
270069AE2-166 C O1
Solar/Wind Harmer
10.375
971313AH1-133 GEN
Solar/Wind Harmer
5.363
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
2.889
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
970281AG2-184 GEN
Solar/Wind Harmer
18.909
971981AH1-535 GEN
Solar/Wind Harmer
5.838
971061AG2-657 GEN
Solar/Wind Harmer
5.362
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972163AH1-664 GEN
Solar/Wind Harmer
7.559
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
12.886
958121AF2-106 GEN
Solar/Wind Harmer
0.001
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
941801AE2-185 GEN
Solar/Wind Harmer
7.447
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.535
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
972103AH1-617 GEN
Solar/Wind Harmer
18.009
24686405CER G5
Adder
9.787
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
970093AG2-073 GEN
Solar/Wind Harmer
6.071
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.034
970455AG2-298 GEN
Solar/Wind Harmer
2.725
972167AH1-666 GEN
Solar/Wind Harmer
5.413
958171AF2-111 GEN
Solar/Wind Harmer
16.661
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
4.688
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
942481AE2-261 GEN
Solar/Wind Harmer
18.979
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
15.863
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
18.636
959611AF2-252 GEN
Solar/Wind Harmer
2.071
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
970571AG2-364 GEN
Solar/Wind Harmer
12.283
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946671AF1-331 GEN
Solar/Wind Harmer
0.653
270004AE1-209 GEN
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
4.603
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
276843GEN-1.7
Solar/Wind Harmer
0.195
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
270356AE2-297 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.464
963841AG1-237 GEN
Solar/Wind Harmer
2.696
946321AF1-296 GEN
Solar/Wind Harmer
3.479
274854TWINGROVE;U2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.498
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
276741O09 GEN1
Solar/Wind Harmer
0.218
972267AH1-718 GEN
Adder
3.684
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
926823AC1-168 GEN
Solar/Wind Harmer
1.044
970169AG2-114 GEN
Solar/Wind Harmer
6.143
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
270263AC1-001 GEN
Solar/Wind Harmer
0.61
970073AG2-061 GEN
Solar/Wind Harmer
2.033
971029AG2-637 GEN
Solar/Wind Harmer
9.145
270543AE2-219 C
Solar/Wind Harmer
4.252
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
247536S-71 GEN
Solar/Wind Harmer
0.242
25306009OHH W.
Adder
2.5
971609AH1-304 GEN
Solar/Wind Harmer
0.988
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
964611AG1-324 GEN
Solar/Wind Harmer
2.357
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
276806AD2-047 C O1
Solar/Wind Harmer
3.42
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
970191AG2-125 GEN
Solar/Wind Harmer
1.552
964401AG1-302 GEN
Solar/Wind Harmer
0.001
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971277AH1-098 GEN
Solar/Wind Harmer
5.174
942671AE2-283 GEN
Solar/Wind Harmer
5.792
970913AG2-568 GEN
Solar/Wind Harmer
7.67
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
964571AG1-320 GEN
Solar/Wind Harmer
6.355
971125AH1-004 GEN
Solar/Wind Harmer
2.78
970107AG2-081 GEN
Solar/Wind Harmer
2.085
972043AH1-570 GEN
Solar/Wind Harmer
1.794
972045AH1-571 GEN
Solar/Wind Harmer
1.437
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
4.796
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276916AD2-100_GEN
Solar/Wind Harmer
13.351
276911AD2-131_GEN
Solar/Wind Harmer
0.879
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960201AF2-311 GEN
Solar/Wind Harmer
5.7
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
938861AE1-114 GEN
Solar/Wind Harmer
3.487
270383AD1-128 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
971613AH1-306 GEN
Solar/Wind Harmer
2.938
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
970885AG2-551 GEN
Solar/Wind Harmer
2.025
276893AG1-478 C
Solar/Wind Harmer
0.404
274674JOLIET 9 ;6U
Adder
13.36
270031AE2-169
Solar/Wind Harmer
3.328
270599AE1-208 GEN
Solar/Wind Harmer
5.547
276897AD1-100 C
Solar/Wind Harmer
15.124
964611AG1-324 GEN
Solar/Wind Harmer
0.453
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
276776AD2-060 GEN
Solar/Wind Harmer
0.644
958011AF2-095 GEN
Solar/Wind Harmer
8.691
970941AG2-585 GEN
Solar/Wind Harmer
3.319
270201AC2-176 GEN
Solar/Wind Harmer
0
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
CPLELTFEXP_CPLE->PJM
CLTF
6.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.58 %
Rating:3039.0 MVA
Rating Type:B
MVA to Mitigate:3208.68
MW Contribution:
1.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344305RKG2
50/50
11.018
270406AB1-088 CT1
50/50
2.513
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.082
24386205FR-12G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970193AG2-126 GEN
Solar/Wind Harmer
9.249
971347AH1-153 GEN
Solar/Wind Harmer
3.046
274772LINCOLN ;3U
Adder
7.265
274752CRETE EC ;2U
Adder
7.074
274753CRETE EC ;3U
Adder
7.074
274724RIVER EC ;11
Adder
15.124
274814UNIV PK N;0U
Adder
4.311
274807UNIV PK N;3U
Adder
4.302
274811UNIV PK N;7U
Adder
4.274
939351AE1-166 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
0.154
276843GEN-1.7
Solar/Wind Harmer
0.191
276806AD2-047 C O1
Solar/Wind Harmer
3.355
274803UNIV PARK;6U
Adder
4.947
972038AH1-567 GEN2
Adder
0.309
972259AH1-714 GEN
Adder
16.155
274826FISK ;BP
Adder
9.27
970707AG2-453 GEN
Solar/Wind Harmer
19.288
274729ELWOOD EC;1P
Adder
13.819
274730ELWOOD EC;6P
Adder
13.819
274734ELWOOD EC;8P
Adder
13.819
274736ELWOOD EC;9P
Adder
13.819
274676JOLIET 29;8U
Adder
24.844
943121AE2-341 GEN
Solar/Wind Harmer
9.707
943591AF1-030 GEN
Solar/Wind Harmer
6.455
274862TOP CROP ;2U
Solar/Wind Harmer
0.78
965091AG1-374 GEN
Solar/Wind Harmer
17.188
959611AF2-252 GEN
Solar/Wind Harmer
1.91
276868AE1-113 GEN
Solar/Wind Harmer
1.141
274879MINONK ;1U
Solar/Wind Harmer
0.238
274682WAUKEGAN ;7U
Adder
14.697
971993AH1-541 GEN
Solar/Wind Harmer
2.606
970571AG2-364 GEN
Solar/Wind Harmer
11.227
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.065
270505AE1-170 C O1
Solar/Wind Harmer
5.856
959091AF2-200 GEN
Solar/Wind Harmer
11.115
945111AF1-176 GEN
Solar/Wind Harmer
4.457
24344205RKG1
50/50
11.252
24344205RKG1
50/50
11.252
24344305RKG2
50/50
11.213
270393AB1-087 CT1
50/50
2.513
942601AE2-276 GEN
50/50
8.364
270102X2-052 ST
50/50
1.428
270100X2-052 CT1
50/50
1.319
270101X2-052 CT2
50/50
1.319
971587AH1-292 GEN
Solar/Wind Harmer
7.361
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.892
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.216
965681AG1-436 GEN
Solar/Wind Harmer
7.77
965791AG1-447 GEN
Solar/Wind Harmer
5.698
945391AF1-204 GEN
Solar/Wind Harmer
6.551
970349AG2-230 GEN
Solar/Wind Harmer
9.139
274770LINCOLN ;1U
Adder
7.265
274771LINCOLN ;2U
Adder
7.265
274805UNIV PK N;1U
Adder
4.283
274808UNIV PK N;4U
Adder
4.255
276897AD1-100 C
Solar/Wind Harmer
14.818
274888KELLY CRK;1U
Solar/Wind Harmer
0.345
276776AD2-060 GEN
Solar/Wind Harmer
0.632
958011AF2-095 GEN
Solar/Wind Harmer
8.526
970941AG2-585 GEN
Solar/Wind Harmer
3.257
276893AG1-478 C
Solar/Wind Harmer
0.391
274674JOLIET 9 ;6U
Adder
12.932
958481AF2-142 GEN
Solar/Wind Harmer
8.668
942111AE2-223 GEN
Solar/Wind Harmer
1.876
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
8.594
960611AF2-352 GEN
Solar/Wind Harmer
1.91
274695ROCKY RD ;2P
Adder
9.123
274693ROCKY RD ;1P
Adder
9.033
274697ROCKY RD ;3P
Adder
2.478
274696ROCKY RD ;4P
Adder
9.338
274683WAUKEGAN ;8U
Adder
17.208
274683WAUKEGAN ;8U
Adder
14.506
962691AG1-118 GEN
Solar/Wind Harmer
17.022
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.058
276838X2-022 GEN2
Solar/Wind Harmer
0.314
971341AH1-150 GEN
Solar/Wind Harmer
11.115
971343AH1-151 GEN
Solar/Wind Harmer
11.115
276645AC1-214 GEN1
Solar/Wind Harmer
0.217
972235AH1-702 GEN1
Adder
1.993
972236AH1-702 GEN2
Adder
1.733
961051AF2-396 GEN
Solar/Wind Harmer
11.03
961051AF2-396 GEN
Solar/Wind Harmer
7.353
276916AD2-100_GEN
Solar/Wind Harmer
11.472
276911AD2-131_GEN
Solar/Wind Harmer
0.756
938861AE1-114 GEN
Solar/Wind Harmer
3.095
274764LEE CO EC;5U
Adder
7.269
274765LEE CO EC;6U
Adder
7.269
274762LEE CO EC;3U
Adder
7.252
274763LEE CO EC;4U
Adder
7.183
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.873
247620Y3-023
Adder
0.342
970291AG2-192 GEN
Solar/Wind Harmer
0.495
970291AG2-192 GEN
Solar/Wind Harmer
0.229
944231AF1-091 GEN
Solar/Wind Harmer
7.025
971613AH1-306 GEN
Solar/Wind Harmer
1.445
252509AD1-136 GEN
Solar/Wind Helper
0.21
25183208HLCRTG
Solar/Wind Helper
2.03
962581AG1-107 GEN
Solar/Wind Helper
0.905
961491AF2-440 GEN
Solar/Wind Helper
0.037
253349AC2-067 GEN
Solar/Wind Helper
0.213
253400AC2-068 GEN
Solar/Wind Helper
0.086
339236AF1-050_GEN
Solar/Wind Helper
0.404
253415AE1-040 GEN
Solar/Wind Helper
0.484
339231AF1-038_GEN
Solar/Wind Helper
0.394
970091AG2-072 GEN
50/50
218.725
270407AB1-088 ST1
50/50
2.513
970023AG2-014 GEN
50/50
2.694
970783AG2-492 GEN
50/50
2.694
24344105CKG2
50/50
6.799
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.786
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.763
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
17.105
970373AG2-245 GEN
Solar/Wind Harmer
14.697
274773LINCOLN ;4U
Adder
7.265
274774LINCOLN ;5U
Adder
7.265
274751CRETE EC ;1U
Adder
7.074
274754CRETE EC ;4U
Adder
7.074
274723RIVER EC ;12
Adder
15.309
274812UNIV PK N;8U
Adder
4.274
941551AE2-152 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
4.947
939401AE1-172 GEN
Solar/Wind Harmer
4.39
274732ELWOOD EC;7P
Adder
13.819
274674JOLIET 9 ;6U
Adder
12.932
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
25.765
274745AC1-111 GEN9
Adder
4.638
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.939
274861TOP CROP ;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.081
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3
276882AE2-255 GEN
Solar/Wind Harmer
0.666
274682WAUKEGAN ;7U
Adder
14.697
274828WAUKEGAN ;BP
Adder
9.02
962781AG1-127 GEN
Solar/Wind Harmer
5.386
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
16.84
276621W2-048 GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
9.279
957471AF2-041 GEN
Solar/Wind Harmer
16.672
959081AF2-199 GEN
Solar/Wind Harmer
5.557
971067AG2-660 GEN
Solar/Wind Harmer
1.852
274822ROCKFORD ;11
Adder
15.554
276646AC1-214 GEN2
Solar/Wind Harmer
0.217
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.884
945111AF1-176 GEN
Solar/Wind Harmer
9.811
970819AG2-516 GEN
Solar/Wind Harmer
6.595
274848CAMPGROVE;RU
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.094
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.252
274766LEE CO EC;7U
Adder
7.166
276708O09 GEN2
Solar/Wind Harmer
0.191
24639705ELKHART HY
Adder
0.118
965011AG1-365 GEN
Solar/Wind Harmer
3.067
270594AE1-207 GEN
Solar/Wind Harmer
3.372
270032AE2-172
Solar/Wind Harmer
2.007
252510AF1-249 C
Solar/Wind Helper
0.376
339221AD2-048_GEN
Solar/Wind Helper
1.206
943111AE2-339 GEN
Solar/Wind Helper
0.641
339211AE2-254 GEN
Solar/Wind Helper
0.448
253398AE2-221_GEN2
Solar/Wind Helper
1.24
339241AF1-083 GEN
Solar/Wind Helper
0.404
253333AC1-068 GEN
Solar/Wind Helper
0.484
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
957381AF2-032 GEN
Solar/Wind Harmer
1.241
942481AE2-261 GEN
Solar/Wind Harmer
16.362
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
7.252
274767LEE CO EC;8U
Adder
7.166
965931AG1-462 GEN
Solar/Wind Harmer
13.235
971087AG2-675 GEN
Solar/Wind Harmer
2.768
270063AE2-323 C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.002
270043AE2-236 GEN
Solar/Wind Harmer
2.578
970289AG2-191 GEN
Solar/Wind Harmer
0.419
965021AG1-366 GEN
Solar/Wind Harmer
1.022
252507AC2-088 GEN
Solar/Wind Helper
1.471
252524AE2-267 GEN
Solar/Wind Helper
0.466
339243AC2-075 GEN1
Solar/Wind Helper
0.336
270186AC1-089 GEN
Solar/Wind Helper
0.822
270367AC2-061_GEN
Solar/Wind Helper
1.691
253394AE2-221_GEN
Solar/Wind Helper
1.24
339206AE1-143 GEN
Solar/Wind Helper
1.206
960071AF2-298 GEN
Solar/Wind Helper
0.355
339255AE2-071 GEN
Solar/Wind Helper
0.153
339250AF1-203 GEN
Solar/Wind Helper
0.118
270518AE2-148 GEN
Solar/Wind Helper
5.631
253325AC1-069 GEN
Solar/Wind Helper
0.484
270394AB1-087 ST1
50/50
2.513
970539AG2-343 GEN
50/50
9.396
970543AG2-345 GEN
50/50
4.698
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.661
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.267
960681AF2-359 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.265
274776LINCOLN ;7U
Adder
7.265
274777LINCOLN ;8U
Adder
7.265
270526AF1-158 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.144
972227AH1-698 GEN1
Adder
2.214
960591AF2-350 GEN
Solar/Wind Harmer
5.921
972037AH1-567 GEN1
Adder
0.155
274800UNIV PARK;3U
Adder
4.938
274801UNIV PARK;4U
Adder
4.938
274827FISK ;RP
Adder
6.57
274687WILL CNTY;4U
Adder
23.495
274687WILL CNTY;4U
Adder
23.495
274731ELWOOD EC;2P
Adder
13.819
274733ELWOOD EC;3P
Adder
13.819
274735ELWOOD EC;4P
Adder
13.819
274728ELWOOD EC;5P
Adder
13.819
970833AG2-524 GEN
Solar/Wind Harmer
6.449
970833AG2-524 GEN
Solar/Wind Harmer
4.299
274675JOLIET 29;7U
Adder
25.765
274675JOLIET 29;7U
Adder
24.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
5.808
274744AC1-111 GEN8
Adder
4.638
274746AC1-111 G10
Adder
4.638
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.06
971771AH1-392 GEN
Solar/Wind Harmer
5.748
274854TWINGROVE;U2
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.91
276668AB2-070 GEN1
Solar/Wind Harmer
0.222
276848AB2-070 GEN3
Solar/Wind Harmer
0.221
276849AB2-070 GEN2
Solar/Wind Harmer
0.222
926823AC1-168 GEN
Solar/Wind Harmer
0.958
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.182
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276863AD2-134 GEN
Solar/Wind Harmer
0.1
971411AH1-196 GEN
Solar/Wind Harmer
8.382
971171AH1-044 GEN
Solar/Wind Harmer
11.115
274823ROCKFORD ;21
Adder
15.441
274856ECOGROVE ;U1
Solar/Wind Harmer
0.128
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971681AH1-341 GEN
Solar/Wind Harmer
8.802
944221AF1-090 GEN
Solar/Wind Harmer
3.186
276741O09 GEN1
Solar/Wind Harmer
0.191
972267AH1-718 GEN
Adder
3.215
946321AF1-296 GEN
Solar/Wind Harmer
2.925
971549AH1-272 GEN
Solar/Wind Harmer
10.203
270071AF1-092 GEN
Solar/Wind Harmer
8.932
970031AG2-029 GEN
Solar/Wind Harmer
2.434
970289AG2-191 GEN
Solar/Wind Harmer
0.724
959331AF2-224 GEN
Solar/Wind Harmer
2.147
339216AC1-074 GEN
Solar/Wind Helper
1.461
253406AD2-031_GEN
Solar/Wind Helper
0.712
270340AC2-060 GEN
Solar/Wind Helper
1.095
241972AD1-140 GEN
Solar/Wind Helper
2.071
253338AC1-165 GEN
Solar/Wind Helper
0.467
253343AC1-166 GEN
Solar/Wind Helper
0.467
955142J992
External Queue
11.419598579406738
990742J1381
External Queue
17.560279846191406
991082J1475 G
External Queue
6.164829730987549
991312J1772
External Queue
12.36315631866455
950011AG9-010
External Queue
6.200752258300781
950051AG9-018
External Queue
4.865413665771484
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.591
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
1.033
WECLTFEXP_WEC->PJM
CLTF
3.003
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.212
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.737
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.546
MECLTFEXP_MEC->PJM
CLTF
10.638
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.962
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.555
LAGNLTFEXP_LAGN->PJM
CLTF
2.301
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.16 %
Rating:2826.0 MVA
Rating Type:B
MVA to Mitigate:3197.84
MW Contribution:
1.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344205RKG1
50/50
11.252
24344205RKG1
50/50
11.252
24344305RKG2
50/50
11.213
270393AB1-087 CT1
50/50
2.513
270394AB1-087 ST1
50/50
2.513
970539AG2-343 GEN
50/50
9.396
970543AG2-345 GEN
50/50
4.698
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.661
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.267
960681AF2-359 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.265
274776LINCOLN ;7U
Adder
7.265
274777LINCOLN ;8U
Adder
7.265
270526AF1-158 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.144
972227AH1-698 GEN1
Adder
2.214
960591AF2-350 GEN
Solar/Wind Harmer
5.921
972037AH1-567 GEN1
Adder
0.155
274800UNIV PARK;3U
Adder
4.938
274801UNIV PARK;4U
Adder
4.938
274827FISK ;RP
Adder
6.57
274687WILL CNTY;4U
Adder
23.495
274687WILL CNTY;4U
Adder
23.495
274731ELWOOD EC;2P
Adder
13.819
274733ELWOOD EC;3P
Adder
13.819
274735ELWOOD EC;4P
Adder
13.819
274728ELWOOD EC;5P
Adder
13.819
970833AG2-524 GEN
Solar/Wind Harmer
6.449
970833AG2-524 GEN
Solar/Wind Harmer
4.299
274675JOLIET 29;7U
Adder
25.765
274675JOLIET 29;7U
Adder
24.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
5.808
274744AC1-111 GEN8
Adder
4.638
274746AC1-111 G10
Adder
4.638
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.06
971771AH1-392 GEN
Solar/Wind Harmer
5.748
274854TWINGROVE;U2
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.91
276668AB2-070 GEN1
Solar/Wind Harmer
0.222
276848AB2-070 GEN3
Solar/Wind Harmer
0.221
276849AB2-070 GEN2
Solar/Wind Harmer
0.222
926823AC1-168 GEN
Solar/Wind Harmer
0.958
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.182
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276863AD2-134 GEN
Solar/Wind Harmer
0.1
971411AH1-196 GEN
Solar/Wind Harmer
8.382
971171AH1-044 GEN
Solar/Wind Harmer
11.115
274823ROCKFORD ;21
Adder
15.441
274856ECOGROVE ;U1
Solar/Wind Harmer
0.128
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971681AH1-341 GEN
Solar/Wind Harmer
8.802
944221AF1-090 GEN
Solar/Wind Harmer
3.186
276741O09 GEN1
Solar/Wind Harmer
0.191
972267AH1-718 GEN
Adder
3.215
946321AF1-296 GEN
Solar/Wind Harmer
2.925
971549AH1-272 GEN
Solar/Wind Harmer
10.203
270071AF1-092 GEN
Solar/Wind Harmer
8.932
970031AG2-029 GEN
Solar/Wind Harmer
2.434
970289AG2-191 GEN
Solar/Wind Harmer
0.724
959331AF2-224 GEN
Solar/Wind Harmer
2.147
339216AC1-074 GEN
Solar/Wind Helper
1.461
253406AD2-031_GEN
Solar/Wind Helper
0.712
270340AC2-060 GEN
Solar/Wind Helper
1.095
241972AD1-140 GEN
Solar/Wind Helper
2.071
253338AC1-165 GEN
Solar/Wind Helper
0.467
253343AC1-166 GEN
Solar/Wind Helper
0.467
24344305RKG2
50/50
11.018
270406AB1-088 CT1
50/50
2.513
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.082
24386205FR-12G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970193AG2-126 GEN
Solar/Wind Harmer
9.249
971347AH1-153 GEN
Solar/Wind Harmer
3.046
274772LINCOLN ;3U
Adder
7.265
274752CRETE EC ;2U
Adder
7.074
274753CRETE EC ;3U
Adder
7.074
274724RIVER EC ;11
Adder
15.124
274814UNIV PK N;0U
Adder
4.311
274807UNIV PK N;3U
Adder
4.302
274811UNIV PK N;7U
Adder
4.274
939351AE1-166 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
0.154
276843GEN-1.7
Solar/Wind Harmer
0.191
276806AD2-047 C O1
Solar/Wind Harmer
3.355
274803UNIV PARK;6U
Adder
4.947
972038AH1-567 GEN2
Adder
0.309
972259AH1-714 GEN
Adder
16.155
274826FISK ;BP
Adder
9.27
970707AG2-453 GEN
Solar/Wind Harmer
19.288
274729ELWOOD EC;1P
Adder
13.819
274730ELWOOD EC;6P
Adder
13.819
274734ELWOOD EC;8P
Adder
13.819
274736ELWOOD EC;9P
Adder
13.819
274676JOLIET 29;8U
Adder
24.844
943121AE2-341 GEN
Solar/Wind Harmer
9.707
943591AF1-030 GEN
Solar/Wind Harmer
6.455
274862TOP CROP ;2U
Solar/Wind Harmer
0.78
965091AG1-374 GEN
Solar/Wind Harmer
17.188
959611AF2-252 GEN
Solar/Wind Harmer
1.91
276868AE1-113 GEN
Solar/Wind Harmer
1.141
274879MINONK ;1U
Solar/Wind Harmer
0.238
274682WAUKEGAN ;7U
Adder
14.697
971993AH1-541 GEN
Solar/Wind Harmer
2.606
970571AG2-364 GEN
Solar/Wind Harmer
11.227
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.065
270505AE1-170 C O1
Solar/Wind Harmer
5.856
959091AF2-200 GEN
Solar/Wind Harmer
11.115
945111AF1-176 GEN
Solar/Wind Harmer
4.457
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
957381AF2-032 GEN
Solar/Wind Harmer
1.241
942481AE2-261 GEN
Solar/Wind Harmer
16.362
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
7.252
274767LEE CO EC;8U
Adder
7.166
965931AG1-462 GEN
Solar/Wind Harmer
13.235
971087AG2-675 GEN
Solar/Wind Harmer
2.768
270063AE2-323 C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.002
270043AE2-236 GEN
Solar/Wind Harmer
2.578
970289AG2-191 GEN
Solar/Wind Harmer
0.419
965021AG1-366 GEN
Solar/Wind Harmer
1.022
252507AC2-088 GEN
Solar/Wind Helper
1.471
252524AE2-267 GEN
Solar/Wind Helper
0.466
339243AC2-075 GEN1
Solar/Wind Helper
0.336
270186AC1-089 GEN
Solar/Wind Helper
0.822
270367AC2-061_GEN
Solar/Wind Helper
1.691
253394AE2-221_GEN
Solar/Wind Helper
1.24
339206AE1-143 GEN
Solar/Wind Helper
1.206
960071AF2-298 GEN
Solar/Wind Helper
0.355
339255AE2-071 GEN
Solar/Wind Helper
0.153
339250AF1-203 GEN
Solar/Wind Helper
0.118
270518AE2-148 GEN
Solar/Wind Helper
5.631
253325AC1-069 GEN
Solar/Wind Helper
0.484
970091AG2-072 GEN
50/50
218.725
270407AB1-088 ST1
50/50
2.513
970023AG2-014 GEN
50/50
2.694
970783AG2-492 GEN
50/50
2.694
24344105CKG2
50/50
6.799
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.786
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.763
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
17.105
970373AG2-245 GEN
Solar/Wind Harmer
14.697
274773LINCOLN ;4U
Adder
7.265
274774LINCOLN ;5U
Adder
7.265
274751CRETE EC ;1U
Adder
7.074
274754CRETE EC ;4U
Adder
7.074
274723RIVER EC ;12
Adder
15.309
274812UNIV PK N;8U
Adder
4.274
941551AE2-152 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
4.947
939401AE1-172 GEN
Solar/Wind Harmer
4.39
274732ELWOOD EC;7P
Adder
13.819
274674JOLIET 9 ;6U
Adder
12.932
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
25.765
274745AC1-111 GEN9
Adder
4.638
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.939
274861TOP CROP ;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.081
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3
276882AE2-255 GEN
Solar/Wind Harmer
0.666
274682WAUKEGAN ;7U
Adder
14.697
274828WAUKEGAN ;BP
Adder
9.02
962781AG1-127 GEN
Solar/Wind Harmer
5.386
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
16.84
276621W2-048 GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
9.279
957471AF2-041 GEN
Solar/Wind Harmer
16.672
959081AF2-199 GEN
Solar/Wind Harmer
5.557
971067AG2-660 GEN
Solar/Wind Harmer
1.852
274822ROCKFORD ;11
Adder
15.554
276646AC1-214 GEN2
Solar/Wind Harmer
0.217
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.884
945111AF1-176 GEN
Solar/Wind Harmer
9.811
970819AG2-516 GEN
Solar/Wind Harmer
6.595
274848CAMPGROVE;RU
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.094
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.252
274766LEE CO EC;7U
Adder
7.166
276708O09 GEN2
Solar/Wind Harmer
0.191
24639705ELKHART HY
Adder
0.118
965011AG1-365 GEN
Solar/Wind Harmer
3.067
270594AE1-207 GEN
Solar/Wind Harmer
3.372
270032AE2-172
Solar/Wind Harmer
2.007
252510AF1-249 C
Solar/Wind Helper
0.376
339221AD2-048_GEN
Solar/Wind Helper
1.206
943111AE2-339 GEN
Solar/Wind Helper
0.641
339211AE2-254 GEN
Solar/Wind Helper
0.448
253398AE2-221_GEN2
Solar/Wind Helper
1.24
339241AF1-083 GEN
Solar/Wind Helper
0.404
253333AC1-068 GEN
Solar/Wind Helper
0.484
942601AE2-276 GEN
50/50
8.364
270102X2-052 ST
50/50
1.428
270100X2-052 CT1
50/50
1.319
270101X2-052 CT2
50/50
1.319
971587AH1-292 GEN
Solar/Wind Harmer
7.361
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.892
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.216
965681AG1-436 GEN
Solar/Wind Harmer
7.77
965791AG1-447 GEN
Solar/Wind Harmer
5.698
945391AF1-204 GEN
Solar/Wind Harmer
6.551
970349AG2-230 GEN
Solar/Wind Harmer
9.139
274770LINCOLN ;1U
Adder
7.265
274771LINCOLN ;2U
Adder
7.265
274805UNIV PK N;1U
Adder
4.283
274808UNIV PK N;4U
Adder
4.255
276897AD1-100 C
Solar/Wind Harmer
14.818
274888KELLY CRK;1U
Solar/Wind Harmer
0.345
276776AD2-060 GEN
Solar/Wind Harmer
0.632
958011AF2-095 GEN
Solar/Wind Harmer
8.526
970941AG2-585 GEN
Solar/Wind Harmer
3.257
276893AG1-478 C
Solar/Wind Harmer
0.391
274674JOLIET 9 ;6U
Adder
12.932
958481AF2-142 GEN
Solar/Wind Harmer
8.668
942111AE2-223 GEN
Solar/Wind Harmer
1.876
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
8.594
960611AF2-352 GEN
Solar/Wind Harmer
1.91
274695ROCKY RD ;2P
Adder
9.123
274693ROCKY RD ;1P
Adder
9.033
274697ROCKY RD ;3P
Adder
2.478
274696ROCKY RD ;4P
Adder
9.338
274683WAUKEGAN ;8U
Adder
17.208
274683WAUKEGAN ;8U
Adder
14.506
962691AG1-118 GEN
Solar/Wind Harmer
17.022
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.058
276838X2-022 GEN2
Solar/Wind Harmer
0.314
971341AH1-150 GEN
Solar/Wind Harmer
11.115
971343AH1-151 GEN
Solar/Wind Harmer
11.115
276645AC1-214 GEN1
Solar/Wind Harmer
0.217
972235AH1-702 GEN1
Adder
1.993
972236AH1-702 GEN2
Adder
1.733
961051AF2-396 GEN
Solar/Wind Harmer
11.03
961051AF2-396 GEN
Solar/Wind Harmer
7.353
276916AD2-100_GEN
Solar/Wind Harmer
11.472
276911AD2-131_GEN
Solar/Wind Harmer
0.756
938861AE1-114 GEN
Solar/Wind Harmer
3.095
274764LEE CO EC;5U
Adder
7.269
274765LEE CO EC;6U
Adder
7.269
274762LEE CO EC;3U
Adder
7.252
274763LEE CO EC;4U
Adder
7.183
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.873
247620Y3-023
Adder
0.342
970291AG2-192 GEN
Solar/Wind Harmer
0.495
970291AG2-192 GEN
Solar/Wind Harmer
0.229
944231AF1-091 GEN
Solar/Wind Harmer
7.025
971613AH1-306 GEN
Solar/Wind Harmer
1.445
252509AD1-136 GEN
Solar/Wind Helper
0.21
25183208HLCRTG
Solar/Wind Helper
2.03
962581AG1-107 GEN
Solar/Wind Helper
0.905
961491AF2-440 GEN
Solar/Wind Helper
0.037
253349AC2-067 GEN
Solar/Wind Helper
0.213
253400AC2-068 GEN
Solar/Wind Helper
0.086
339236AF1-050_GEN
Solar/Wind Helper
0.404
253415AE1-040 GEN
Solar/Wind Helper
0.484
339231AF1-038_GEN
Solar/Wind Helper
0.394
955142J992
External Queue
11.419598579406738
990742J1381
External Queue
17.560279846191406
991082J1475 G
External Queue
6.164829730987549
991312J1772
External Queue
12.36315631866455
950011AG9-010
External Queue
6.200752258300781
950051AG9-018
External Queue
4.865413665771484
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.591
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
1.033
WECLTFEXP_WEC->PJM
CLTF
3.003
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.212
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.737
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.546
MECLTFEXP_MEC->PJM
CLTF
10.638
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.962
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.555
LAGNLTFEXP_LAGN->PJM
CLTF
2.301
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.83
MW Contribution:
3.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.065
23559001PLEAS1
50/50
6.097
270051AF1-062 GEN
50/50
11.777
270475AD2-096_GEN
50/50
7.114
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
961921AG1-034 GEN
Solar/Wind Harmer
7.586
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
970191AG2-125 GEN
Solar/Wind Harmer
1.937
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
971191AH1-055 GEN
Solar/Wind Harmer
19.175
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
944531AF1-118 GEN
Solar/Wind Harmer
33.233
270043AE2-236 GEN
Solar/Wind Harmer
4.754
252519AF1-045_GEN
Solar/Wind Harmer
3.844
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
9.036
25194608D.CRK4
Adder
1.732
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
971347AH1-153 GEN
Solar/Wind Harmer
3.658
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.95
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
970289AG2-191 GEN
Solar/Wind Harmer
0.8
945111AF1-176 GEN
Solar/Wind Harmer
5.891
247642Z2-115 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
274753CRETE EC ;3U
Adder
8.436
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274811UNIV PK N;7U
Adder
5.114
972167AH1-666 GEN
Solar/Wind Harmer
5.69
274803UNIV PARK;6U
Adder
5.941
24728705AND G3
Adder
8.173
24728505AND G1
Adder
3.908
274887GEN-1.85
Solar/Wind Harmer
0.185
276843GEN-1.7
Solar/Wind Harmer
0.23
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274826FISK ;BP
Adder
11.151
972038AH1-567 GEN2
Adder
0.372
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
972259AH1-714 GEN
Adder
19.413
274676JOLIET 29;8U
Adder
30.039
274729ELWOOD EC;1P
Adder
16.687
274730ELWOOD EC;6P
Adder
16.687
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
274682WAUKEGAN ;7U
Adder
18.096
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970193AG2-126 GEN
Solar/Wind Harmer
10.468
970571AG2-364 GEN
Solar/Wind Harmer
13.944
964991AG1-363 GEN
Solar/Wind Helper
5.155
238108AE1-109 GEN1
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238127S14_GEN_2
Solar/Wind Helper
0.831
238175AF1-290_GEN
Solar/Wind Helper
0.158
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
23562501BACKB
Solar/Wind Helper
1.012
235063AE1-101 C2
Solar/Wind Helper
1.672
237001AB1-127_GEN
Solar/Wind Helper
0.445
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
208835TUHI V3-051
Solar/Wind Helper
0.022
205932AD2-116_GEN
Solar/Wind Helper
0.512
233918AB1-142 GEN
Solar/Wind Helper
0.506
233944AB2-135 GEN
Solar/Wind Helper
0.594
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
232408W1-005 C
Solar/Wind Helper
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.868
316044AC1-158 PL1
Solar/Wind Helper
1.303
228729W2-030 C
Solar/Wind Helper
0.111
219766PARADISE C
Solar/Wind Helper
0.055
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
203975AE1-071-GEN
Solar/Wind Helper
2.516
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
218440SUMMTASSOC C
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
20676328BVR_Y1-020
Solar/Wind Helper
0.027
207484AF2-139 C O1
Solar/Wind Helper
0.085
20674928WA_W3-044
Solar/Wind Helper
0.099
20674628WNG_W3-110
Solar/Wind Helper
0.09
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
207518AF1-320_GEN
Solar/Wind Helper
1.58
20675828AU_W4-064
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
202652Y1-033 WT C
Solar/Wind Helper
0.5
959091AF2-200 GEN
Solar/Wind Harmer
9.057
972239AH1-704 GEN
Adder
2.678
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270291AC1-194 GEN
Solar/Wind Harmer
0
970179AG2-119 GEN
Solar/Wind Harmer
6.854
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
253406AD2-031_GEN
Solar/Wind Harmer
0.559
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270377AD1-106 GEN
Solar/Wind Harmer
2.842
247521TR3_G114
Solar/Wind Harmer
0.27
965051AG1-369 GEN
Solar/Wind Harmer
3.723
959331AF2-224 GEN
Solar/Wind Harmer
5.217
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.438
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
270166AC1-044 GEN3
50/50
7.069
23559101PLEAS2
50/50
6.097
962761AG1-125 GEN
Solar/Wind Harmer
34.394
970149AG2-104 GEN
Solar/Wind Harmer
18.573
970155AG2-107 GEN
Solar/Wind Harmer
21.963
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.894
270273AD2-016 GEN
Solar/Wind Harmer
0.807
972269AH1-719 GEN
Adder
2.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965421AG1-410 GEN
Solar/Wind Harmer
22.47
960001AF2-291 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965011AG1-365 GEN
Solar/Wind Harmer
7.453
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
958861AF2-177 GEN
Solar/Wind Harmer
3.191
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.732
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.351
970825AG2-519 GEN
Solar/Wind Harmer
2.589
24639705ELKHART HY
Adder
0.16
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
276903AD2-071 C
Solar/Wind Harmer
8.095
25196008MFTGT1
Adder
1.443
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.365
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274754CRETE EC ;4U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
274802UNIV PARK;5U
Adder
5.941
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
31.151
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
939401AE1-172 GEN
Solar/Wind Harmer
5.275
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
274682WAUKEGAN ;7U
Adder
18.096
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.818
971997AH1-543 GEN
Solar/Wind Harmer
3.68
962781AG1-127 GEN
Solar/Wind Harmer
6.668
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
316095T157 G97
Solar/Wind Helper
1.51
23583801GRNGAP
Solar/Wind Helper
5.626
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
238126S14_GEN_1
Solar/Wind Helper
0.831
23546401DTGZ2-030
Solar/Wind Helper
0.09
237085AD2-009_GEN
Solar/Wind Helper
1.661
237038AE2-054 C
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.349
208835TUHI V3-051
Solar/Wind Helper
0.022
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
233933AB2-153 GEN
Solar/Wind Helper
0.234
232422X3-066 FULL
Solar/Wind Helper
0.115
232417X3-008 C
Solar/Wind Helper
0.234
233964AF2-378 GEN
Solar/Wind Helper
0.042
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
233950AC2-186 GEN
Solar/Wind Helper
0.117
230415AB2-049 C
Solar/Wind Helper
0.031
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
219291REEVESSOUT C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
205941AD2-115 GEN
Solar/Wind Helper
0.499
20716928W4-060COL
Solar/Wind Helper
0.052
219249CENTRALDIV C
Solar/Wind Helper
0.01
217213AMBOY SO C
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.328
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Helper
0.027
20671928W4-073
Solar/Wind Helper
0.09
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.792
211065PSPA IPP
Solar/Wind Helper
0.152
963161AG1-165 GEN
Solar/Wind Helper
0.441
957471AF2-041 GEN
Solar/Wind Harmer
13.586
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
963791AG1-232 GEN
Solar/Wind Harmer
9.987
270071AF1-092 GEN
Solar/Wind Harmer
14.177
971985AH1-537 GEN
Solar/Wind Harmer
2.196
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
25196508WSDLE4
Adder
8.944
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
270543AE2-219 C
Solar/Wind Harmer
5.137
247536S-71 GEN
Solar/Wind Harmer
0.293
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
970289AG2-191 GEN
Solar/Wind Harmer
1.382
971771AH1-392 GEN
Solar/Wind Harmer
7.271
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
971549AH1-272 GEN
Solar/Wind Harmer
14.794
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.634
274776LINCOLN ;7U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972228AH1-698 GEN2
Adder
3.772
972227AH1-698 GEN1
Adder
2.656
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
274728ELWOOD EC;5P
Adder
16.687
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274735ELWOOD EC;4P
Adder
16.687
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
274744AC1-111 GEN8
Adder
5.652
274746AC1-111 G10
Adder
5.652
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
970169AG2-114 GEN
Solar/Wind Harmer
7.011
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
971411AH1-196 GEN
Solar/Wind Harmer
10.47
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.32
23750701CROSSCHOOL
Solar/Wind Helper
1.509
238118U2-030_1
Solar/Wind Helper
0.343
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
959381AF2-229 GEN
Solar/Wind Helper
0.359
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
205943AE1-185 GEN
Solar/Wind Helper
0.513
205956AE1-196_GEN
Solar/Wind Helper
0.512
233915AB1-141 GEN
Solar/Wind Helper
0.506
233901CHERRYDALE C
Solar/Wind Helper
0.234
233940AF2-379 C
Solar/Wind Helper
0.062
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
230407AD2-065 C
Solar/Wind Helper
0.041
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219615MILLCREEK C
Solar/Wind Helper
0.027
20715028HAN_X4-015
Solar/Wind Helper
0.057
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
20676428JCR_X2-075
Solar/Wind Helper
0.068
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
20675128HRM_W1-127
Solar/Wind Helper
0.03
209027LOR2_Q27
Solar/Wind Helper
1.031
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
270119AB2-067 GEN1
50/50
7.069
270120AB2-067 GEN2
50/50
7.069
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.31
938701AE1-092 GEN
Solar/Wind Harmer
12.867
971655AH1-328 GEN
Solar/Wind Harmer
2.843
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
25326509SID D
Adder
1.446
971073AG2-665 GEN
Solar/Wind Harmer
5.597
970879AG2-548 GEN
Solar/Wind Harmer
1.272
25326109MON D
Adder
1.437
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
246937BC-WTG2
Solar/Wind Harmer
0.302
270246TR4_N_V150
Solar/Wind Harmer
0.048
270247TR4_N_V136
Solar/Wind Harmer
0.048
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.351
944541AF1-119 GEN
Solar/Wind Harmer
0.492
960971AF2-388 GEN
Solar/Wind Harmer
4.326
942221AE2-234 GEN
Solar/Wind Harmer
2.958
25194408D.CRK1
Adder
7.968
25194508D.CRK3
Adder
1.49
970621AG2-405 GEN
Solar/Wind Harmer
1.345
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970885AG2-551 GEN
Solar/Wind Harmer
2.446
247621Y3-024
Adder
0.253
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270031AE2-169
Solar/Wind Harmer
4.021
270599AE1-208 GEN
Solar/Wind Harmer
6.701
270383AD1-128 GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728805RICHG1
Adder
3.944
24728905RICHG2
Adder
3.944
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.052
965791AG1-447 GEN
Solar/Wind Harmer
6.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274805UNIV PK N;1U
Adder
5.126
274808UNIV PK N;4U
Adder
5.092
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
276776AD2-060 GEN
Solar/Wind Harmer
0.758
958011AF2-095 GEN
Solar/Wind Harmer
10.234
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
274674JOLIET 9 ;6U
Adder
15.628
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274696ROCKY RD ;4P
Adder
11.481
274695ROCKY RD ;2P
Adder
11.216
274693ROCKY RD ;1P
Adder
11.106
274697ROCKY RD ;3P
Adder
3.047
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276901AD2-066 C O1
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
962691AG1-118 GEN
Solar/Wind Harmer
21.036
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
942111AE2-223 GEN
Solar/Wind Harmer
2.266
316097T157 G90
Solar/Wind Helper
1.51
235054AD2-180 GEN
Solar/Wind Helper
2.04
23585401KL_K28_T16
Solar/Wind Helper
1.489
235531U2-073 GEN
Solar/Wind Helper
3.327
238117U2-030
Solar/Wind Helper
0.343
238147AE2-230_GEN1
Solar/Wind Helper
0.499
238148AE2-230_GEN2
Solar/Wind Helper
0.499
238149AF1-291A_GEN
Solar/Wind Helper
0.143
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
237080AD1-060 GEN
Solar/Wind Helper
0.344
235062AE1-101 C1
Solar/Wind Helper
1.672
316411AF1-147_GEN1
Solar/Wind Helper
0.895
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
223402AF1-300 C
Solar/Wind Helper
0.37
316006AB2-029 C
Solar/Wind Helper
0.118
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
232424Y1-079 C
Solar/Wind Helper
0.117
232436AB1-176 C
Solar/Wind Helper
0.045
233946AB2-136 GEN
Solar/Wind Helper
0.573
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
232410W1-006 C
Solar/Wind Helper
0.511
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
316045AC1-158 PL2
Solar/Wind Helper
4.17
316450AC1-158 RIC
Solar/Wind Helper
0.348
230511AF1-262
Solar/Wind Helper
0.015
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.026
219904AC1-010 C
Solar/Wind Helper
0.061
219912AD2-042 GEN
Solar/Wind Helper
0.151
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219906AC1-017 C
Solar/Wind Helper
0.042
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.064
207459AE1-142 C O1
Solar/Wind Helper
0.292
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
20675428EAM_W2-061
Solar/Wind Helper
0.016
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.023
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4761.71
MW Contribution:
3.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
9.823
23559001PLEAS1
50/50
5.39
270051AF1-062 GEN
50/50
11.411
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
961921AG1-034 GEN
Solar/Wind Harmer
7.349
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
942051AE2-217 GEN
Solar/Wind Harmer
14.139
24721905FLATG4
Adder
22.814
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
970191AG2-125 GEN
Solar/Wind Harmer
1.872
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
24695305TIMB G C
Solar/Wind Harmer
0.609
944531AF1-118 GEN
Solar/Wind Harmer
32.112
270043AE2-236 GEN
Solar/Wind Harmer
4.595
252519AF1-045_GEN
Solar/Wind Harmer
3.711
270367AC2-061_GEN
Solar/Wind Harmer
0
25196608WSDLE5
Adder
8.723
25194608D.CRK4
Adder
1.672
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
971347AH1-153 GEN
Solar/Wind Harmer
3.535
270186AC1-089 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
6.713
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
970289AG2-191 GEN
Solar/Wind Harmer
0.773
270505AE1-170 C O1
Solar/Wind Harmer
7.374
247642Z2-115 C
Solar/Wind Harmer
0.003
25196008MFTGT1
Adder
1.349
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
274753CRETE EC ;3U
Adder
8.15
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
274811UNIV PK N;7U
Adder
4.941
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
274887GEN-1.85
Solar/Wind Harmer
0.178
276843GEN-1.7
Solar/Wind Harmer
0.222
276806AD2-047 C O1
Solar/Wind Harmer
3.89
274826FISK ;BP
Adder
10.773
972038AH1-567 GEN2
Adder
0.359
972167AH1-666 GEN
Solar/Wind Harmer
5.491
24728705AND G3
Adder
7.891
24728505AND G1
Adder
3.773
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
18.754
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274676JOLIET 29;8U
Adder
29.018
274729ELWOOD EC;1P
Adder
16.119
274730ELWOOD EC;6P
Adder
16.119
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970193AG2-126 GEN
Solar/Wind Harmer
10.106
970571AG2-364 GEN
Solar/Wind Harmer
13.468
964991AG1-363 GEN
Solar/Wind Helper
4.979
238108AE1-109 GEN1
Solar/Wind Helper
0.107
238110AE1-109 GEN3
Solar/Wind Helper
0.107
238175AF1-290_GEN
Solar/Wind Helper
0.152
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
235063AE1-101 C2
Solar/Wind Helper
1.608
237001AB1-127_GEN
Solar/Wind Helper
0.428
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
23562501BACKB
Solar/Wind Helper
0.845
205916AD1-020 GEN
Solar/Wind Helper
1.664
208835TUHI V3-051
Solar/Wind Helper
0.021
205932AD2-116_GEN
Solar/Wind Helper
0.494
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
316447AC1-158 HLD
Solar/Wind Helper
2.771
316044AC1-158 PL1
Solar/Wind Helper
1.259
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
203975AE1-071-GEN
Solar/Wind Helper
2.421
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
959091AF2-200 GEN
Solar/Wind Harmer
8.748
270166AC1-044 GEN3
50/50
6.887
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
962761AG1-125 GEN
Solar/Wind Harmer
33.201
970149AG2-104 GEN
Solar/Wind Harmer
17.929
970155AG2-107 GEN
Solar/Wind Harmer
21.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
971995AH1-542 GEN
Solar/Wind Harmer
2.804
270273AD2-016 GEN
Solar/Wind Harmer
0.78
972269AH1-719 GEN
Adder
2.495
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965011AG1-365 GEN
Solar/Wind Harmer
7.206
960001AF2-291 GEN
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.09
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.054
25194608D.CRK4
Adder
1.672
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
276903AD2-071 C
Solar/Wind Harmer
7.818
25196008MFTGT1
Adder
1.393
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.046
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274754CRETE EC ;4U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
274812UNIV PK N;8U
Adder
4.941
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.093
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
939401AE1-172 GEN
Solar/Wind Harmer
5.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
971997AH1-543 GEN
Solar/Wind Harmer
3.554
962781AG1-127 GEN
Solar/Wind Harmer
6.441
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
20.202
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.427
316095T157 G97
Solar/Wind Helper
1.459
23583801GRNGAP
Solar/Wind Helper
5.433
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23546401DTGZ2-030
Solar/Wind Helper
0.086
238126S14_GEN_1
Solar/Wind Helper
0.769
237038AE2-054 C
Solar/Wind Helper
0.264
235067AD1-061 GEN
Solar/Wind Helper
0.432
237085AD2-009_GEN
Solar/Wind Helper
1.596
237002AB1-128_GEN
Solar/Wind Helper
0.43
23777801MSM_W1-116
Solar/Wind Helper
0.111
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.337
208835TUHI V3-051
Solar/Wind Helper
0.021
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.301
219612MATRIX C
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.481
20716928W4-060COL
Solar/Wind Helper
0.05
957471AF2-041 GEN
Solar/Wind Harmer
13.123
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
972239AH1-704 GEN
50/50
2.774
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.899
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
970179AG2-119 GEN
Solar/Wind Harmer
6.643
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.918
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971567AH1-282 GEN
Solar/Wind Harmer
5.517
959331AF2-224 GEN
Solar/Wind Harmer
5.044
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.193
24729505KEY G4
Adder
6.652
963791AG1-232 GEN
Solar/Wind Harmer
9.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
971985AH1-537 GEN
Solar/Wind Harmer
2.117
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
25196508WSDLE4
Adder
8.634
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
270543AE2-219 C
Solar/Wind Harmer
4.962
247536S-71 GEN
Solar/Wind Harmer
0.283
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
971771AH1-392 GEN
Solar/Wind Harmer
7.027
970289AG2-191 GEN
Solar/Wind Harmer
1.334
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
270356AE2-297 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
971549AH1-272 GEN
Solar/Wind Harmer
14.305
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.341
274776LINCOLN ;7U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972228AH1-698 GEN2
Adder
3.644
972227AH1-698 GEN1
Adder
2.566
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
274728ELWOOD EC;5P
Adder
16.119
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
274735ELWOOD EC;4P
Adder
16.119
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
970169AG2-114 GEN
Solar/Wind Harmer
6.772
971675AH1-338 GEN
Solar/Wind Harmer
2.63
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
971411AH1-196 GEN
Solar/Wind Harmer
10.113
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.07
23750701CROSSCHOOL
Solar/Wind Helper
1.401
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
959381AF2-229 GEN
Solar/Wind Helper
0.346
20390526W1-045 C
Solar/Wind Helper
0.339
23750501ELLIOTTS
Solar/Wind Helper
0.573
3141426STAFORD
Solar/Wind Helper
0.051
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230434AG1-499 GEN
Solar/Wind Helper
0.223
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.075
219615MILLCREEK C
Solar/Wind Helper
0.026
20715028HAN_X4-015
Solar/Wind Helper
0.055
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.184
971171AH1-044 GEN
Solar/Wind Harmer
8.748
270119AB2-067 GEN1
50/50
6.887
270120AB2-067 GEN2
50/50
6.887
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
6.105
938701AE1-092 GEN
Solar/Wind Harmer
12.459
971655AH1-328 GEN
Solar/Wind Harmer
2.753
270462AD2-086
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
970935AG2-582 GEN
Adder
241.832
25326509SID D
Adder
1.398
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
970879AG2-548 GEN
Solar/Wind Harmer
1.228
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
246937BC-WTG2
Solar/Wind Harmer
0.292
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
960971AF2-388 GEN
Solar/Wind Harmer
4.179
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
25194408D.CRK1
Adder
7.692
25194508D.CRK3
Adder
1.438
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970885AG2-551 GEN
Solar/Wind Harmer
2.363
247621Y3-024
Adder
0.245
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270031AE2-169
Solar/Wind Harmer
3.884
270599AE1-208 GEN
Solar/Wind Harmer
6.473
270383AD1-128 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.273
247620Y3-023
Adder
0.465
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.374
24728805RICHG1
Adder
3.809
24728905RICHG2
Adder
3.809
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
965681AG1-436 GEN
Solar/Wind Harmer
8.747
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
274808UNIV PK N;4U
Adder
4.919
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.78
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
276776AD2-060 GEN
Solar/Wind Harmer
0.732
958011AF2-095 GEN
Solar/Wind Harmer
9.886
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
10.177
962691AG1-118 GEN
Solar/Wind Harmer
20.32
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
942111AE2-223 GEN
Solar/Wind Harmer
2.188
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235020AA1-095 C
Solar/Wind Helper
0.051
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
237061AD1-155 GEN
Solar/Wind Helper
1.703
238117U2-030
Solar/Wind Helper
0.315
238221AF1-254 C O1
Solar/Wind Helper
0.267
237080AD1-060 GEN
Solar/Wind Helper
0.332
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
316411AF1-147_GEN1
Solar/Wind Helper
0.865
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
223402AF1-300 C
Solar/Wind Helper
0.357
316006AB2-029 C
Solar/Wind Helper
0.114
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.113
232436AB1-176 C
Solar/Wind Helper
0.043
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
316045AC1-158 PL2
Solar/Wind Helper
4.03
316450AC1-158 RIC
Solar/Wind Helper
0.336
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.146
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.061
207459AE1-142 C O1
Solar/Wind Helper
0.282
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.91 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2513.45
MW Contribution:
2.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
3.291
24729505KEY G4
50/50
6.793
24653605MOTTVILLE
50/50
0.003
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.776
957201AF2-014 GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
3.627
959331AF2-224 GEN
Solar/Wind Harmer
9.638
963791AG1-232 GEN
Solar/Wind Harmer
11.962
970031AG2-029 GEN
Solar/Wind Harmer
4.557
965041AG1-368 GEN
Solar/Wind Harmer
8.389
270071AF1-092 GEN
Solar/Wind Harmer
14.462
247521TR3_G114
Solar/Wind Harmer
0.259
965051AG1-369 GEN
Solar/Wind Harmer
3.575
971771AH1-392 GEN
Solar/Wind Harmer
5.853
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.913
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.109
274775LINCOLN ;6U
Adder
6.299
274776LINCOLN ;7U
Adder
6.299
274777LINCOLN ;8U
Adder
6.299
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.748
274800UNIV PARK;3U
Adder
4.311
274801UNIV PARK;4U
Adder
4.311
960591AF2-350 GEN
Solar/Wind Harmer
5.152
972228AH1-698 GEN2
Adder
2.728
972227AH1-698 GEN1
Adder
1.92
274687WILL CNTY;4U
Adder
20.467
274687WILL CNTY;4U
Adder
20.467
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.423
274675JOLIET 29;7U
Adder
21.622
274728ELWOOD EC;5P
Adder
11.982
274731ELWOOD EC;2P
Adder
11.982
274733ELWOOD EC;3P
Adder
11.982
274735ELWOOD EC;4P
Adder
11.982
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.964
970833AG2-524 GEN
Solar/Wind Harmer
5.568
970833AG2-524 GEN
Solar/Wind Harmer
3.712
971611AH1-305 GEN
Solar/Wind Harmer
2.999
274744AC1-111 GEN8
Adder
4.025
274746AC1-111 G10
Adder
4.025
965431AG1-411 GEN
50/50
45.352
24727105RPMNG2
50/50
3.311
970583AG2-370 GEN
50/50
2.796
270142AC1-141 CT1_
50/50
2.011
24642205MAYFLWER
50/50
0.03
246938BC-WTG3
Solar/Wind Harmer
1.031
270491AE1-102 GEN2
Solar/Wind Harmer
3.723
965021AG1-366 GEN
Solar/Wind Harmer
4.589
270043AE2-236 GEN
Solar/Wind Harmer
5.206
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.738
24695305TIMB G C
Solar/Wind Harmer
0.527
945111AF1-176 GEN
Solar/Wind Harmer
4.809
971347AH1-153 GEN
Solar/Wind Harmer
2.9
270505AE1-170 C O1
Solar/Wind Harmer
6.075
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.264
274752CRETE EC ;2U
Adder
6.248
274753CRETE EC ;3U
Adder
6.248
274724RIVER EC ;11
Adder
13.377
274814UNIV PK N;0U
Adder
3.786
274807UNIV PK N;3U
Adder
3.778
274811UNIV PK N;7U
Adder
3.753
274772LINCOLN ;3U
Adder
6.299
274803UNIV PARK;6U
Adder
4.324
274826FISK ;BP
Adder
8.11
972038AH1-567 GEN2
Adder
0.27
274887GEN-1.85
Solar/Wind Harmer
0.134
276843GEN-1.7
Solar/Wind Harmer
0.167
276806AD2-047 C O1
Solar/Wind Harmer
2.92
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.004
970707AG2-453 GEN
Solar/Wind Harmer
16.726
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.622
274729ELWOOD EC;1P
Adder
11.982
274730ELWOOD EC;6P
Adder
11.982
274734ELWOOD EC;8P
Adder
11.982
274736ELWOOD EC;9P
Adder
11.982
970289AG2-191 GEN
Solar/Wind Harmer
0.558
946031AF1-268 GEN
Solar/Wind Harmer
4.787
943121AE2-341 GEN
Solar/Wind Harmer
8.427
943591AF1-030 GEN
Solar/Wind Harmer
5.604
270004AE1-209 GEN
Solar/Wind Harmer
1.089
274862TOP CROP ;2U
Solar/Wind Harmer
0.674
970825AG2-519 GEN
Solar/Wind Harmer
3.754
274682WAUKEGAN ;7U
Adder
12.793
276868AE1-113 GEN
Solar/Wind Harmer
0.98
274879MINONK ;1U
Solar/Wind Harmer
0.204
946671AF1-331 GEN
Solar/Wind Harmer
0.519
274855GSG-6 ;RU
Solar/Wind Harmer
0.177
274850MENDOTA H;RU
Solar/Wind Harmer
0.056
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.841
959091AF2-200 GEN
Solar/Wind Harmer
9.659
970571AG2-364 GEN
Solar/Wind Harmer
9.566
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.308
274767LEE CO EC;8U
Adder
6.234
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.155
965091AG1-374 GEN
Solar/Wind Harmer
13.563
965931AG1-462 GEN
Solar/Wind Harmer
11.528
971087AG2-675 GEN
Solar/Wind Harmer
2.411
959611AF2-252 GEN
Solar/Wind Harmer
1.507
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.973
957381AF2-032 GEN
Solar/Wind Harmer
0.92
942481AE2-261 GEN
Solar/Wind Harmer
12.093
970193AG2-126 GEN
Solar/Wind Harmer
5.875
24728705AND G3
Adder
4.327
24728505AND G1
Adder
2.069
942871AE2-306 GEN
Solar/Wind Helper
0.448
270284AF1-227 GEN1
Solar/Wind Helper
1.912
270287AF1-227 GEN3
Solar/Wind Helper
0.701
276820AF1-078_GEN
Solar/Wind Helper
0.338
270541AE2-072 C
Solar/Wind Helper
0.958
24727005RPMNG1
50/50
3.31
960861AF2-377 GEN
50/50
2.388
970521AG2-332 GEN
50/50
10.816
24639705ELKHART HY
50/50
0.149
270143AC1-141 CT2_
50/50
2.011
246936BC-WTG1
Solar/Wind Harmer
1.154
270489AE1-102 GEN1
Solar/Wind Harmer
3.723
965421AG1-410 GEN
Solar/Wind Harmer
81.634
965011AG1-365 GEN
Solar/Wind Harmer
13.768
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.86
958861AF2-177 GEN
Solar/Wind Harmer
2.67
945111AF1-176 GEN
Solar/Wind Harmer
10.586
957891AF2-083 GEN
Solar/Wind Harmer
9.711
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.972
970373AG2-245 GEN
Solar/Wind Harmer
11.129
274751CRETE EC ;1U
Adder
6.248
274754CRETE EC ;4U
Adder
6.248
274723RIVER EC ;12
Adder
13.542
274812UNIV PK N;8U
Adder
3.753
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.299
274774LINCOLN ;5U
Adder
6.299
274802UNIV PARK;5U
Adder
4.324
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.679
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.423
274674JOLIET 9 ;6U
Adder
11.228
274732ELWOOD EC;7P
Adder
11.982
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.296
270594AE1-207 GEN
Solar/Wind Harmer
5.638
270032AE2-172
Solar/Wind Harmer
3.356
270005AE1-210 C O1
Solar/Wind Harmer
1.089
274745AC1-111 GEN9
Adder
4.025
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.811
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.769
274682WAUKEGAN ;7U
Adder
12.793
274828WAUKEGAN ;BP
Adder
7.853
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.68
939401AE1-172 GEN
Solar/Wind Harmer
3.677
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971997AH1-543 GEN
Solar/Wind Harmer
2.561
957471AF2-041 GEN
Solar/Wind Harmer
14.489
959081AF2-199 GEN
Solar/Wind Harmer
4.83
971067AG2-660 GEN
Solar/Wind Harmer
1.61
274822ROCKFORD ;11
Adder
13.543
276903AD2-071 C
Solar/Wind Harmer
5.365
970819AG2-516 GEN
Solar/Wind Harmer
5.744
970569AG2-363 GEN
Solar/Wind Harmer
14.349
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.308
274766LEE CO EC;7U
Adder
6.234
276708O09 GEN2
Solar/Wind Harmer
0.165
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.443
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.247
963741AG1-226 GEN
Solar/Wind Harmer
10.345
276621W2-048 GEN
Solar/Wind Harmer
0.21
965911AG1-460 GEN
Solar/Wind Harmer
0.809
24728605AND G2
Adder
2.069
970773AG2-487 GEN
Solar/Wind Harmer
0.62
270317AD1-130_GEN
Solar/Wind Helper
4.168
270485AE1-090_GEN
Solar/Wind Helper
0.328
270391AF1-285 GEN3
Solar/Wind Helper
0.597
270578AF1-285 GEN2
Solar/Wind Helper
0.597
270286AF1-227 GEN2
Solar/Wind Helper
0.701
960841AF2-375 GEN
Solar/Wind Helper
1.192
24729405KEY G3
50/50
0.371
24729305KEY G2
50/50
0.365
24729205KEY G1
50/50
0.363
247620Y3-023
50/50
0.463
960851AF2-376 GEN
50/50
2.077
24643105BUCHANAN
50/50
0.01
246937BC-WTG2
Solar/Wind Harmer
1.154
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.833
944231AF1-091 GEN
Solar/Wind Harmer
16.013
944541AF1-119 GEN
Solar/Wind Harmer
0.423
960971AF2-388 GEN
Solar/Wind Harmer
3.72
970349AG2-230 GEN
Solar/Wind Harmer
8.699
961051AF2-396 GEN
Solar/Wind Harmer
11.565
961051AF2-396 GEN
Solar/Wind Harmer
7.71
270031AE2-169
Solar/Wind Harmer
3.074
270599AE1-208 GEN
Solar/Wind Harmer
5.123
965681AG1-436 GEN
Solar/Wind Harmer
6.895
965791AG1-447 GEN
Solar/Wind Harmer
5.056
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.406
247621Y3-024
Adder
0.181
274805UNIV PK N;1U
Adder
3.762
274808UNIV PK N;4U
Adder
3.737
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.299
274771LINCOLN ;2U
Adder
6.299
274888KELLY CRK;1U
Solar/Wind Harmer
0.3
276776AD2-060 GEN
Solar/Wind Harmer
0.55
958011AF2-095 GEN
Solar/Wind Harmer
7.42
970941AG2-585 GEN
Solar/Wind Harmer
2.834
276897AD1-100 C
Solar/Wind Harmer
12.751
274674JOLIET 9 ;6U
Adder
11.228
276893AG1-478 C
Solar/Wind Harmer
0.339
970291AG2-192 GEN
Solar/Wind Harmer
0.659
970291AG2-192 GEN
Solar/Wind Harmer
0.304
971613AH1-306 GEN
Solar/Wind Harmer
2.416
958481AF2-142 GEN
Solar/Wind Harmer
7.489
274696ROCKY RD ;4P
Adder
8.116
274695ROCKY RD ;2P
Adder
7.929
274693ROCKY RD ;1P
Adder
7.851
274697ROCKY RD ;3P
Adder
2.154
274683WAUKEGAN ;8U
Adder
14.981
274683WAUKEGAN ;8U
Adder
12.628
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
7.394
962691AG1-118 GEN
Solar/Wind Harmer
14.789
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.659
971343AH1-151 GEN
Solar/Wind Harmer
9.659
972235AH1-702 GEN1
Adder
1.735
972236AH1-702 GEN2
Adder
1.509
938861AE1-114 GEN
Solar/Wind Harmer
2.691
274764LEE CO EC;5U
Adder
6.323
274765LEE CO EC;6U
Adder
6.323
274762LEE CO EC;3U
Adder
6.308
274763LEE CO EC;4U
Adder
6.249
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.754
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.527
942111AE2-223 GEN
Solar/Wind Harmer
1.496
960611AF2-352 GEN
Solar/Wind Harmer
1.507
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.427
970885AG2-551 GEN
Solar/Wind Harmer
1.476
970241AG2-163 GEN
Solar/Wind Harmer
2.55
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.043
276838X2-022 GEN2
Solar/Wind Harmer
0.236
276916AD2-100_GEN
Solar/Wind Harmer
8.418
276911AD2-131_GEN
Solar/Wind Harmer
0.555
945391AF1-204 GEN
Solar/Wind Harmer
4.161
970623AG2-406 GEN
Solar/Wind Harmer
0.646
971587AH1-292 GEN
Solar/Wind Harmer
2.428
247607V1-011 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
3.77
247522W1-056 GEN
Solar/Wind Helper
1.187
253378AE2-206_GEN
Solar/Wind Helper
0.725
270349AD2-093_GEN
Solar/Wind Helper
0.869
270471AD2-092_GEN
Solar/Wind Helper
0.869
241960AC2-195 GEN
Solar/Wind Helper
0.709
970073AG2-061 GEN
Solar/Wind Harmer
1.643
247536S-71 GEN
Solar/Wind Harmer
0.197
971411AH1-196 GEN
Solar/Wind Harmer
7.295
971675AH1-338 GEN
Solar/Wind Harmer
1.895
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276863AD2-134 GEN
Solar/Wind Harmer
0.087
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.659
274823ROCKFORD ;21
Adder
13.445
274856ECOGROVE ;U1
Solar/Wind Harmer
0.112
926823AC1-168 GEN
Solar/Wind Harmer
0.812
970169AG2-114 GEN
Solar/Wind Harmer
4.769
971681AH1-341 GEN
Solar/Wind Harmer
7.649
971549AH1-272 GEN
Solar/Wind Harmer
9.785
972267AH1-718 GEN
Adder
2.795
276741O09 GEN1
Solar/Wind Harmer
0.165
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.155
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.832
946321AF1-296 GEN
Solar/Wind Harmer
2.546
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.952
270543AE2-219 C
Solar/Wind Harmer
3.099
276668AB2-070 GEN1
Solar/Wind Harmer
0.168
276848AB2-070 GEN3
Solar/Wind Harmer
0.167
276849AB2-070 GEN2
Solar/Wind Harmer
0.168
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.847
944221AF1-090 GEN
Solar/Wind Harmer
2.28
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
0.881
270224U2-072_GEN2
Solar/Wind Helper
0.881
270227U2-072_GEN3
Solar/Wind Helper
0.881
270228U2-072_GEN4
Solar/Wind Helper
0.881
270231U2-072_GEN5
Solar/Wind Helper
0.881
966831AG1-554 GEN
Solar/Wind Helper
0.889
270499AE1-146 GEN
Solar/Wind Helper
1.989
945641AF1-229 GEN
Solar/Wind Helper
0.952
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.784
NYPJM->LTFIMP_NY
CLTF
1.314
LGEELTFEXP_LGEE->PJM
CLTF
1.767
WECLTFEXP_WEC->PJM
CLTF
2.626
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.114
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.636
MECLTFEXP_MEC->PJM
CLTF
9.653
SIGELTFEXP_SIGE->PJM
CLTF
0.197
LAGNLTFEXP_LAGN->PJM
CLTF
5.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.274
TVALTFEXP_TVA->PJM
CLTF
2.24

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.9 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5297.56
MW Contribution:
3.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.726
24721905FLATG4
50/50
31.534
962771AG1-126 GEN
Solar/Wind Harmer
74.4
970153AG2-106 GEN
Solar/Wind Harmer
47.51
971347AH1-153 GEN
Solar/Wind Harmer
4.619
270043AE2-236 GEN
Solar/Wind Harmer
5.83
944531AF1-118 GEN
Solar/Wind Harmer
39.701
274772LINCOLN ;3U
Adder
10.701
274724RIVER EC ;11
Adder
22.258
274752CRETE EC ;2U
Adder
10.338
274753CRETE EC ;3U
Adder
10.338
970707AG2-453 GEN
Solar/Wind Harmer
28.587
274814UNIV PK N;0U
Adder
6.326
274807UNIV PK N;3U
Adder
6.312
274811UNIV PK N;7U
Adder
6.271
270063AE2-323 C
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
9.169
972259AH1-714 GEN
Adder
23.869
274826FISK ;BP
Adder
13.684
274803UNIV PARK;6U
Adder
7.287
274887GEN-1.85
Solar/Wind Harmer
0.227
276843GEN-1.7
Solar/Wind Harmer
0.282
276806AD2-047 C O1
Solar/Wind Harmer
4.941
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.059
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
36.827
274729ELWOOD EC;1P
Adder
20.436
274730ELWOOD EC;6P
Adder
20.437
274734ELWOOD EC;8P
Adder
20.437
274736ELWOOD EC;9P
Adder
20.437
943121AE2-341 GEN
Solar/Wind Harmer
14.508
943591AF1-030 GEN
Solar/Wind Harmer
9.648
965021AG1-366 GEN
Solar/Wind Harmer
2.872
274862TOP CROP ;2U
Solar/Wind Harmer
1.159
274682WAUKEGAN ;7U
Adder
22.104
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.703
274879MINONK ;1U
Solar/Wind Harmer
0.355
946671AF1-331 GEN
Solar/Wind Harmer
0.906
274855GSG-6 ;RU
Solar/Wind Harmer
0.31
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
16.931
970571AG2-364 GEN
Solar/Wind Harmer
16.823
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.167
274767LEE CO EC;8U
Adder
11.036
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.328
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
965091AG1-374 GEN
Solar/Wind Harmer
24.6
959611AF2-252 GEN
Solar/Wind Harmer
2.733
24386205FR-12G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
20.87
971087AG2-675 GEN
Solar/Wind Harmer
4.365
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.879
971993AH1-541 GEN
Solar/Wind Harmer
3.686
957381AF2-032 GEN
Solar/Wind Harmer
1.767
942481AE2-261 GEN
Solar/Wind Harmer
23.27
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.678
970825AG2-519 GEN
Solar/Wind Harmer
5.778
24695305TIMB G C
Solar/Wind Harmer
0.648
946031AF1-268 GEN
Solar/Wind Harmer
7.259
970193AG2-126 GEN
Solar/Wind Harmer
11.441
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.403
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.266
270491AE1-102 GEN2
Solar/Wind Harmer
0.958
24728705AND G3
Adder
8.312
24728505AND G1
Adder
3.974
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
24721605FLATG1
50/50
1.726
270071AF1-092 GEN
Solar/Wind Harmer
17.295
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
10.701
274776LINCOLN ;7U
Adder
10.701
274777LINCOLN ;8U
Adder
10.701
971771AH1-392 GEN
Solar/Wind Harmer
8.847
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
8.138
274827FISK ;RP
Adder
9.698
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
8.72
972228AH1-698 GEN2
Adder
4.629
972227AH1-698 GEN1
Adder
3.26
274800UNIV PARK;3U
Adder
7.284
274801UNIV PARK;4U
Adder
7.284
970031AG2-029 GEN
Solar/Wind Harmer
4.711
274687WILL CNTY;4U
Adder
34.799
274687WILL CNTY;4U
Adder
34.799
274675JOLIET 29;7U
Adder
38.191
274675JOLIET 29;7U
Adder
36.827
274728ELWOOD EC;5P
Adder
20.437
274731ELWOOD EC;2P
Adder
20.436
274733ELWOOD EC;3P
Adder
20.436
274735ELWOOD EC;4P
Adder
20.436
970833AG2-524 GEN
Solar/Wind Harmer
9.54
970833AG2-524 GEN
Solar/Wind Harmer
6.36
274744AC1-111 GEN8
Adder
6.924
274746AC1-111 G10
Adder
6.924
959331AF2-224 GEN
Solar/Wind Harmer
6.031
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
2.844
959141AF2-205 GEN
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
3.313
971411AH1-196 GEN
Solar/Wind Harmer
12.74
276861AD2-134 GEN
Solar/Wind Harmer
0.151
276863AD2-134 GEN
Solar/Wind Harmer
0.151
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
5.051
971171AH1-044 GEN
Solar/Wind Harmer
16.931
274823ROCKFORD ;21
Adder
23.596
970169AG2-114 GEN
Solar/Wind Harmer
8.419
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.43
971681AH1-341 GEN
Solar/Wind Harmer
13.512
972267AH1-718 GEN
Adder
4.973
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.294
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.684
946321AF1-296 GEN
Solar/Wind Harmer
4.596
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
11.059
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.499
965041AG1-368 GEN
Solar/Wind Harmer
8.029
970289AG2-191 GEN
Solar/Wind Harmer
1.518
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.297
971549AH1-272 GEN
Solar/Wind Harmer
16.346
247521TR3_G114
Solar/Wind Harmer
0.284
965051AG1-369 GEN
Solar/Wind Harmer
3.91
944221AF1-090 GEN
Solar/Wind Harmer
4.487
964611AG1-324 GEN
Solar/Wind Harmer
2.967
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.934
247536S-71 GEN
Solar/Wind Harmer
0.293
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.979
270007AE1-245 C
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
971029AG2-637 GEN
Solar/Wind Harmer
10.316
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.938
24721705FLATG2
50/50
25.639
270102X2-052 ST
50/50
2.04
270100X2-052 CT1
50/50
1.885
270101X2-052 CT2
50/50
1.885
970349AG2-230 GEN
Solar/Wind Harmer
13.856
965681AG1-436 GEN
Solar/Wind Harmer
11.105
965791AG1-447 GEN
Solar/Wind Harmer
8.144
274770LINCOLN ;1U
Adder
10.701
274771LINCOLN ;2U
Adder
10.701
274805UNIV PK N;1U
Adder
6.285
274808UNIV PK N;4U
Adder
6.243
247620Y3-023
Adder
0.576
274888KELLY CRK;1U
Solar/Wind Harmer
0.509
276776AD2-060 GEN
Solar/Wind Harmer
0.93
958011AF2-095 GEN
Solar/Wind Harmer
12.557
970941AG2-585 GEN
Solar/Wind Harmer
4.796
276897AD1-100 C
Solar/Wind Harmer
21.761
274674JOLIET 9 ;6U
Adder
19.151
961051AF2-396 GEN
Solar/Wind Harmer
17.344
961051AF2-396 GEN
Solar/Wind Harmer
11.563
276893AG1-478 C
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.031
274695ROCKY RD ;2P
Adder
13.708
274693ROCKY RD ;1P
Adder
13.573
274697ROCKY RD ;3P
Adder
3.724
958481AF2-142 GEN
Solar/Wind Harmer
12.877
274683WAUKEGAN ;8U
Adder
25.9
274683WAUKEGAN ;8U
Adder
21.833
962691AG1-118 GEN
Solar/Wind Harmer
25.676
958491AF2-143 GEN
Solar/Wind Harmer
12.799
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
16.931
971343AH1-151 GEN
Solar/Wind Harmer
16.931
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.565
960971AF2-388 GEN
Solar/Wind Harmer
4.962
972235AH1-702 GEN1
Adder
3.049
972236AH1-702 GEN2
Adder
2.651
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
4.755
274764LEE CO EC;5U
Adder
11.194
274765LEE CO EC;6U
Adder
11.194
274762LEE CO EC;3U
Adder
11.167
274763LEE CO EC;4U
Adder
11.062
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.343
276645AC1-214 GEN1
Solar/Wind Harmer
0.326
942111AE2-223 GEN
Solar/Wind Harmer
2.688
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
3.3
24721805FLATG3
50/50
1.726
24344105CKG2
50/50
10.12
962761AG1-125 GEN
Solar/Wind Harmer
74.4
970149AG2-104 GEN
Solar/Wind Harmer
40.177
970155AG2-107 GEN
Solar/Wind Harmer
47.51
274773LINCOLN ;4U
Adder
10.701
274774LINCOLN ;5U
Adder
10.701
274723RIVER EC ;12
Adder
22.518
24639705ELKHART HY
Adder
0.193
274751CRETE EC ;1U
Adder
10.338
274754CRETE EC ;4U
Adder
10.338
274812UNIV PK N;8U
Adder
6.271
957891AF2-083 GEN
Solar/Wind Harmer
14.548
274802UNIV PARK;5U
Adder
7.287
945111AF1-176 GEN
Solar/Wind Harmer
15.539
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.275
274676JOLIET 29;8U
Adder
38.191
274674JOLIET 9 ;6U
Adder
19.151
274732ELWOOD EC;7P
Adder
20.437
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.515
274745AC1-111 GEN9
Adder
6.924
270055AF2-134 C O1
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.615
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.395
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.104
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
13.576
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.138
939401AE1-172 GEN
Solar/Wind Harmer
6.395
962781AG1-127 GEN
Solar/Wind Harmer
8.134
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.993
971997AH1-543 GEN
Solar/Wind Harmer
4.466
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.605
957471AF2-041 GEN
Solar/Wind Harmer
25.396
959081AF2-199 GEN
Solar/Wind Harmer
8.465
971067AG2-660 GEN
Solar/Wind Harmer
2.822
965651AG1-433 GEN
Solar/Wind Harmer
2.481
274822ROCKFORD ;11
Adder
23.769
970819AG2-516 GEN
Solar/Wind Harmer
10.109
970569AG2-363 GEN
Solar/Wind Harmer
25.234
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.167
274766LEE CO EC;7U
Adder
11.036
958861AF2-177 GEN
Solar/Wind Harmer
3.623
276708O09 GEN2
Solar/Wind Harmer
0.294
276646AC1-214 GEN2
Solar/Wind Harmer
0.326
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.579
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.871
276621W2-048 GEN
Solar/Wind Harmer
0.396
270594AE1-207 GEN
Solar/Wind Harmer
8.855
270032AE2-172
Solar/Wind Harmer
5.271
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.696
965911AG1-460 GEN
Solar/Wind Harmer
1.557
270005AE1-210 C O1
Solar/Wind Harmer
1.678
970825AG2-519 GEN
Solar/Wind Harmer
2.723
965421AG1-410 GEN
Solar/Wind Harmer
22.474
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.436
246936BC-WTG1
Solar/Wind Harmer
0.297
270489AE1-102 GEN1
Solar/Wind Harmer
0.958
24728605AND G2
Adder
3.974
970091AG2-072 GEN
Adder
78.436
970773AG2-487 GEN
Solar/Wind Harmer
1.228
270317AD1-130_GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.059
24723205RIVRG3
Adder
16.391
960611AF2-352 GEN
Solar/Wind Harmer
2.733
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.927
970291AG2-192 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.479
970241AG2-163 GEN
Solar/Wind Harmer
4.651
270031AE2-169
Solar/Wind Harmer
4.369
270599AE1-208 GEN
Solar/Wind Harmer
7.282
276615X2-022 GEN
Solar/Wind Harmer
0.082
276838X2-022 GEN2
Solar/Wind Harmer
0.445
971613AH1-306 GEN
Solar/Wind Harmer
3.795
270246TR4_N_V150
Solar/Wind Harmer
0.05
270247TR4_N_V136
Solar/Wind Harmer
0.05
276916AD2-100_GEN
Solar/Wind Harmer
16.28
276911AD2-131_GEN
Solar/Wind Harmer
1.072
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
17.757
945391AF1-204 GEN
Solar/Wind Harmer
8.104
964611AG1-324 GEN
Solar/Wind Harmer
0.571
270201AC2-176 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.257
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.297
971587AH1-292 GEN
Solar/Wind Harmer
5.361
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.112
970885AG2-551 GEN
Solar/Wind Harmer
2.371
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.29
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.474
24728905RICHG2
Adder
3.474
24723005RIVRG1
Adder
16.391
24723105RIVRG2
Adder
16.391
CPLELTFEXP_CPLE->PJM
CLTF
3.255
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.551
NYPJM->LTFIMP_NY
CLTF
3.901
LGEELTFEXP_LGEE->PJM
CLTF
5.998
WECLTFEXP_WEC->PJM
CLTF
4.618
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.416
MECLTFEXP_MEC->PJM
CLTF
18.61
SIGELTFEXP_SIGE->PJM
CLTF
0.498
LAGNLTFEXP_LAGN->PJM
CLTF
16.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.242
TVALTFEXP_TVA->PJM
CLTF
7.96

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4473.55
MW Contribution:
3.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
4.711
270144AC1-141 ST1_
50/50
3.051
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.268
24653605MOTTVILLE
50/50
0.005
959331AF2-224 GEN
Solar/Wind Harmer
7.224
270578AF1-285 GEN2
Solar/Wind Harmer
0.682
270071AF1-092 GEN
Solar/Wind Harmer
19.599
970031AG2-029 GEN
Solar/Wind Harmer
5.461
971771AH1-392 GEN
Solar/Wind Harmer
10.022
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24729505KEY G4
Adder
9.105
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.376
965041AG1-368 GEN
Solar/Wind Harmer
9.736
274775LINCOLN ;6U
Adder
11.612
274776LINCOLN ;7U
Adder
11.612
274777LINCOLN ;8U
Adder
11.612
247521TR3_G114
Solar/Wind Harmer
0.347
965051AG1-369 GEN
Solar/Wind Harmer
4.782
963791AG1-232 GEN
Solar/Wind Harmer
12.72
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.469
960591AF2-350 GEN
Solar/Wind Harmer
9.405
274800UNIV PARK;3U
Adder
7.859
274801UNIV PARK;4U
Adder
7.859
972228AH1-698 GEN2
Adder
4.989
972227AH1-698 GEN1
Adder
3.513
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.188
274687WILL CNTY;4U
Adder
37.422
274687WILL CNTY;4U
Adder
37.422
274675JOLIET 29;7U
Adder
41.04
274675JOLIET 29;7U
Adder
39.575
274728ELWOOD EC;5P
Adder
21.94
274731ELWOOD EC;2P
Adder
21.939
274733ELWOOD EC;3P
Adder
21.939
274735ELWOOD EC;4P
Adder
21.939
970833AG2-524 GEN
Solar/Wind Harmer
10.228
970833AG2-524 GEN
Solar/Wind Harmer
6.819
971549AH1-272 GEN
Solar/Wind Harmer
19.166
274744AC1-111 GEN8
Adder
7.404
274746AC1-111 G10
Adder
7.404
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
3.016
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.448
971675AH1-338 GEN
Solar/Wind Harmer
3.496
276861AD2-134 GEN
Solar/Wind Harmer
0.16
276863AD2-134 GEN
Solar/Wind Harmer
0.16
971611AH1-305 GEN
Solar/Wind Harmer
5.334
270007AE1-245 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.823
274823ROCKFORD ;21
Adder
24.808
274856ECOGROVE ;U1
Solar/Wind Harmer
0.206
945581AF1-223 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.499
970169AG2-114 GEN
Solar/Wind Harmer
8.815
971681AH1-341 GEN
Solar/Wind Harmer
14.132
972267AH1-718 GEN
Adder
5.171
276741O09 GEN1
Solar/Wind Harmer
0.306
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.961
971609AH1-304 GEN
Solar/Wind Harmer
1.381
946321AF1-296 GEN
Solar/Wind Harmer
4.723
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.58
963841AG1-237 GEN
Solar/Wind Harmer
3.532
964611AG1-324 GEN
Solar/Wind Harmer
3.142
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.308
270543AE2-219 C
Solar/Wind Harmer
5.181
944221AF1-090 GEN
Solar/Wind Harmer
4.314
971029AG2-637 GEN
Solar/Wind Harmer
10.609
24721805FLATG3
50/50
4.711
24344105CKG2
50/50
11.483
270143AC1-141 CT2_
50/50
3.456
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.675
24307105BERRINSP G
50/50
0.03
962761AG1-125 GEN
Solar/Wind Harmer
109.537
970149AG2-104 GEN
Solar/Wind Harmer
59.152
970155AG2-107 GEN
Solar/Wind Harmer
69.947
965011AG1-365 GEN
Solar/Wind Harmer
10.32
957891AF2-083 GEN
Solar/Wind Harmer
16.606
945111AF1-176 GEN
Solar/Wind Harmer
17.763
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
5.166
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
274773LINCOLN ;4U
Adder
11.612
274774LINCOLN ;5U
Adder
11.612
274723RIVER EC ;12
Adder
24.471
274751CRETE EC ;1U
Adder
11.245
274754CRETE EC ;4U
Adder
11.245
965421AG1-410 GEN
Solar/Wind Harmer
28.412
970373AG2-245 GEN
Solar/Wind Harmer
19.884
274812UNIV PK N;8U
Adder
6.795
274802UNIV PARK;5U
Adder
7.869
246936BC-WTG1
Solar/Wind Harmer
0.378
270489AE1-102 GEN1
Solar/Wind Harmer
1.219
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
41.04
270055AF2-134 C O1
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
20.564
274732ELWOOD EC;7P
Adder
21.94
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.726
274745AC1-111 GEN9
Adder
7.404
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.902
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.486
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
23.522
958861AF2-177 GEN
Solar/Wind Harmer
3.956
274828WAUKEGAN ;BP
Adder
14.44
962781AG1-127 GEN
Solar/Wind Harmer
8.625
939401AE1-172 GEN
Solar/Wind Harmer
6.778
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.051
971997AH1-543 GEN
Solar/Wind Harmer
4.72
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.201
957471AF2-041 GEN
Solar/Wind Harmer
26.735
959081AF2-199 GEN
Solar/Wind Harmer
8.912
971067AG2-660 GEN
Solar/Wind Harmer
2.971
274822ROCKFORD ;11
Adder
24.99
970819AG2-516 GEN
Solar/Wind Harmer
10.604
945371AF1-202 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
26.447
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.659
274766LEE CO EC;7U
Adder
11.522
276708O09 GEN2
Solar/Wind Harmer
0.306
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.948
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.214
270032AE2-172
Solar/Wind Harmer
5.485
270005AE1-210 C O1
Solar/Wind Harmer
1.752
276903AD2-071 C
Solar/Wind Harmer
8.936
970825AG2-519 GEN
Solar/Wind Harmer
2.836
963741AG1-226 GEN
Solar/Wind Harmer
18.848
276621W2-048 GEN
Solar/Wind Harmer
0.393
965911AG1-460 GEN
Solar/Wind Harmer
1.522
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.54
24728605AND G2
Adder
3.831
970773AG2-487 GEN
Solar/Wind Harmer
1.192
23906502RICHG2&3
Adder
1.11
24722005FLATG5
50/50
4.711
24721905FLATG4
50/50
86.05
270475AD2-096_GEN
50/50
10.483
270142AC1-141 CT1_
50/50
3.456
24642205MAYFLWER
50/50
0.053
944961AF1-161 GEN
50/50
4.124
962601AG1-109 GEN
50/50
4.124
962771AG1-126 GEN
Solar/Wind Harmer
109.537
970153AG2-106 GEN
Solar/Wind Harmer
69.947
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270043AE2-236 GEN
Solar/Wind Harmer
6.765
971347AH1-153 GEN
Solar/Wind Harmer
5.221
965021AG1-366 GEN
Solar/Wind Harmer
3.44
270391AF1-285 GEN3
Solar/Wind Harmer
0.682
270063AE2-323 C
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
10.472
944531AF1-118 GEN
Solar/Wind Harmer
44.69
945111AF1-176 GEN
Solar/Wind Harmer
8.069
274772LINCOLN ;3U
Adder
11.612
274724RIVER EC ;11
Adder
24.187
274752CRETE EC ;2U
Adder
11.245
274753CRETE EC ;3U
Adder
11.245
274814UNIV PK N;0U
Adder
6.855
274807UNIV PK N;3U
Adder
6.84
274811UNIV PK N;7U
Adder
6.795
970707AG2-453 GEN
Solar/Wind Harmer
30.807
24695305TIMB G C
Solar/Wind Harmer
0.797
274803UNIV PARK;6U
Adder
7.869
274826FISK ;BP
Adder
14.772
274887GEN-1.85
Solar/Wind Harmer
0.244
276843GEN-1.7
Solar/Wind Harmer
0.304
276806AD2-047 C O1
Solar/Wind Harmer
5.33
972038AH1-567 GEN2
Adder
0.492
972259AH1-714 GEN
Adder
25.709
246938BC-WTG3
Solar/Wind Harmer
0.338
270491AE1-102 GEN2
Solar/Wind Harmer
1.219
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
39.574
274729ELWOOD EC;1P
Adder
21.939
274730ELWOOD EC;6P
Adder
21.94
274734ELWOOD EC;8P
Adder
21.94
274736ELWOOD EC;9P
Adder
21.94
943121AE2-341 GEN
Solar/Wind Harmer
15.518
943591AF1-030 GEN
Solar/Wind Harmer
10.32
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
1.234
274682WAUKEGAN ;7U
Adder
23.522
276868AE1-113 GEN
Solar/Wind Harmer
1.802
274879MINONK ;1U
Solar/Wind Harmer
0.376
946671AF1-331 GEN
Solar/Wind Harmer
0.957
274855GSG-6 ;RU
Solar/Wind Harmer
0.327
274850MENDOTA H;RU
Solar/Wind Harmer
0.104
959091AF2-200 GEN
Solar/Wind Harmer
17.823
970571AG2-364 GEN
Solar/Wind Harmer
17.631
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.659
274767LEE CO EC;8U
Adder
11.522
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.625
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
965091AG1-374 GEN
Solar/Wind Harmer
25.202
959611AF2-252 GEN
Solar/Wind Harmer
2.8
247642Z2-115 C
Solar/Wind Harmer
0.003
965931AG1-462 GEN
Solar/Wind Harmer
21.395
971087AG2-675 GEN
Solar/Wind Harmer
4.475
24386205FR-12G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.915
270004AE1-209 GEN
Solar/Wind Harmer
1.752
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.121
970825AG2-519 GEN
Solar/Wind Harmer
6.019
971993AH1-541 GEN
Solar/Wind Harmer
3.688
946031AF1-268 GEN
Solar/Wind Harmer
7.583
957381AF2-032 GEN
Solar/Wind Harmer
1.73
942481AE2-261 GEN
Solar/Wind Harmer
22.758
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.995
24728705AND G3
Adder
8.012
24728505AND G1
Adder
3.831
270541AE2-072 C
Solar/Wind Harmer
0
23906402RICHG1
Adder
1.111
23906502RICHG2&3
Adder
1.11
24721705FLATG2
50/50
69.962
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.277
270100X2-052 CT1
50/50
2.104
270101X2-052 CT2
50/50
2.104
24643105BUCHANAN
50/50
0.018
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
15.664
961051AF2-396 GEN
Solar/Wind Harmer
19.838
961051AF2-396 GEN
Solar/Wind Harmer
13.225
965681AG1-436 GEN
Solar/Wind Harmer
12.356
965791AG1-447 GEN
Solar/Wind Harmer
9.061
270462AD2-086
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
11.612
274771LINCOLN ;2U
Adder
11.612
270246TR4_N_V150
Solar/Wind Harmer
0.061
270247TR4_N_V136
Solar/Wind Harmer
0.061
274805UNIV PK N;1U
Adder
6.81
274808UNIV PK N;4U
Adder
6.766
274888KELLY CRK;1U
Solar/Wind Harmer
0.548
276776AD2-060 GEN
Solar/Wind Harmer
1.003
958011AF2-095 GEN
Solar/Wind Harmer
13.543
970941AG2-585 GEN
Solar/Wind Harmer
5.173
246937BC-WTG2
Solar/Wind Harmer
0.378
276897AD1-100 C
Solar/Wind Harmer
23.396
944231AF1-091 GEN
Solar/Wind Harmer
21.57
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
20.564
276893AG1-478 C
Solar/Wind Harmer
0.621
944541AF1-119 GEN
Solar/Wind Harmer
0.62
960971AF2-388 GEN
Solar/Wind Harmer
5.451
958481AF2-142 GEN
Solar/Wind Harmer
13.721
274695ROCKY RD ;2P
Adder
14.592
274693ROCKY RD ;1P
Adder
14.449
274697ROCKY RD ;3P
Adder
3.964
274696ROCKY RD ;4P
Adder
14.936
942221AE2-234 GEN
Solar/Wind Harmer
3.664
274683WAUKEGAN ;8U
Adder
27.547
274683WAUKEGAN ;8U
Adder
23.221
962691AG1-118 GEN
Solar/Wind Harmer
27.25
958491AF2-143 GEN
Solar/Wind Harmer
13.572
276901AD2-066 C O1
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.823
971343AH1-151 GEN
Solar/Wind Harmer
17.823
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.202
972236AH1-702 GEN2
Adder
2.785
970623AG2-406 GEN
Solar/Wind Harmer
1.615
938861AE1-114 GEN
Solar/Wind Harmer
4.972
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274764LEE CO EC;5U
Adder
11.687
274765LEE CO EC;6U
Adder
11.687
274762LEE CO EC;3U
Adder
11.659
274763LEE CO EC;4U
Adder
11.55
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.395
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.774
270031AE2-169
Solar/Wind Harmer
4.65
270599AE1-208 GEN
Solar/Wind Harmer
7.749
960611AF2-352 GEN
Solar/Wind Harmer
2.8
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.946
970291AG2-192 GEN
Solar/Wind Harmer
1.081
970291AG2-192 GEN
Solar/Wind Harmer
0.499
971613AH1-306 GEN
Solar/Wind Harmer
3.949
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.604
970241AG2-163 GEN
Solar/Wind Harmer
4.646
970621AG2-405 GEN
Solar/Wind Harmer
1.449
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
247621Y3-024
Adder
0.272
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
926881AC1-175 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
15.862
276911AD2-131_GEN
Solar/Wind Harmer
1.045
970883AG2-550 GEN
Solar/Wind Harmer
7.401
970885AG2-551 GEN
Solar/Wind Harmer
2.467
270383AD1-128 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.788
971587AH1-292 GEN
Solar/Wind Harmer
4.757
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.35
24728905RICHG2
Adder
3.35
970329AG2-216 GEN
Solar/Wind Harmer
2.663
25326509SID D
Adder
1.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.889
NYPJM->LTFIMP_NY
CLTF
3.074
LGEELTFEXP_LGEE->PJM
CLTF
4.556
WECLTFEXP_WEC->PJM
CLTF
4.845
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.158
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.375
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.313
MECLTFEXP_MEC->PJM
CLTF
18.13
SIGELTFEXP_SIGE->PJM
CLTF
0.416
LAGNLTFEXP_LAGN->PJM
CLTF
11.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.981
TVALTFEXP_TVA->PJM
CLTF
4.815

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.31 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5773.71
MW Contribution:
3.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
971347AH1-153 GEN
Solar/Wind Harmer
4.684
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274753CRETE EC ;3U
Adder
10.415
270505AE1-170 C O1
Solar/Wind Harmer
9.246
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
0.228
276843GEN-1.7
Solar/Wind Harmer
0.284
276806AD2-047 C O1
Solar/Wind Harmer
4.976
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
17.002
970571AG2-364 GEN
Solar/Wind Harmer
16.871
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
965931AG1-462 GEN
Solar/Wind Harmer
20.885
971087AG2-675 GEN
Solar/Wind Harmer
4.368
965091AG1-374 GEN
Solar/Wind Harmer
24.551
959611AF2-252 GEN
Solar/Wind Harmer
2.728
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.663
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
957381AF2-032 GEN
Solar/Wind Harmer
1.75
942481AE2-261 GEN
Solar/Wind Harmer
23.05
270004AE1-209 GEN
Solar/Wind Harmer
1.624
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24695305TIMB G C
Solar/Wind Harmer
0.627
970825AG2-519 GEN
Solar/Wind Harmer
5.579
946031AF1-268 GEN
Solar/Wind Harmer
6.994
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
17.36
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274775LINCOLN ;6U
Adder
10.797
274776LINCOLN ;7U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
80.774
970149AG2-104 GEN
Solar/Wind Harmer
43.619
970155AG2-107 GEN
Solar/Wind Harmer
51.58
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
10.415
274754CRETE EC ;4U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
945111AF1-176 GEN
Solar/Wind Harmer
15.659
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
6.422
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971997AH1-543 GEN
Solar/Wind Harmer
4.485
957471AF2-041 GEN
Solar/Wind Harmer
25.504
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
970569AG2-363 GEN
Solar/Wind Harmer
25.306
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
965651AG1-433 GEN
Solar/Wind Harmer
2.449
276708O09 GEN2
Solar/Wind Harmer
0.295
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
965911AG1-460 GEN
Solar/Wind Harmer
1.542
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.459
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
965421AG1-410 GEN
Solar/Wind Harmer
21.55
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.196
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
972203AH1-686 GEN
Adder
1.998
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
5.989
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.434
970169AG2-114 GEN
Solar/Wind Harmer
8.435
971681AH1-341 GEN
Solar/Wind Harmer
13.557
972267AH1-718 GEN
Adder
4.986
276741O09 GEN1
Solar/Wind Harmer
0.295
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.677
946321AF1-296 GEN
Solar/Wind Harmer
4.601
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
10.858
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
971549AH1-272 GEN
Solar/Wind Harmer
16.367
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.859
970289AG2-191 GEN
Solar/Wind Harmer
1.486
971609AH1-304 GEN
Solar/Wind Harmer
1.264
247521TR3_G114
Solar/Wind Harmer
0.275
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.891
247536S-71 GEN
Solar/Wind Harmer
0.278
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.586
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
14.053
965681AG1-436 GEN
Solar/Wind Harmer
11.209
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
276776AD2-060 GEN
Solar/Wind Harmer
0.937
958011AF2-095 GEN
Solar/Wind Harmer
12.646
970941AG2-585 GEN
Solar/Wind Harmer
4.83
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
21.908
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.582
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
25.814
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
972236AH1-702 GEN2
Adder
2.662
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.897
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.686
960611AF2-352 GEN
Solar/Wind Harmer
2.728
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.921
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
270031AE2-169
Solar/Wind Harmer
4.257
270599AE1-208 GEN
Solar/Wind Harmer
7.096
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
276911AD2-131_GEN
Solar/Wind Harmer
1.062
270246TR4_N_V150
Solar/Wind Harmer
0.049
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.284
270383AD1-128 GEN
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
970883AG2-550 GEN
Solar/Wind Harmer
6.689
970885AG2-551 GEN
Solar/Wind Harmer
2.23
270054AF2-122 C O1
Solar/Wind Helper
1.547
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.62 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4476.89
MW Contribution:
2.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.617
24642205MAYFLWER
50/50
0.04
274772LINCOLN ;3U
50/50
9.616
944961AF1-161 GEN
50/50
3.109
962601AG1-109 GEN
50/50
3.109
962771AG1-126 GEN
Solar/Wind Harmer
74.627
970153AG2-106 GEN
Solar/Wind Harmer
47.655
971347AH1-153 GEN
Solar/Wind Harmer
4.014
270043AE2-236 GEN
Solar/Wind Harmer
5.048
270505AE1-170 C O1
Solar/Wind Harmer
7.914
270063AE2-323 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.088
944531AF1-118 GEN
Solar/Wind Harmer
33.371
274724RIVER EC ;11
Adder
18.817
274752CRETE EC ;2U
Adder
8.738
274753CRETE EC ;3U
Adder
8.738
270144AC1-141 ST1_
50/50
2.311
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.028
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.616
274776LINCOLN ;7U
50/50
9.616
274777LINCOLN ;8U
50/50
9.616
270071AF1-092 GEN
Solar/Wind Harmer
14.768
971771AH1-392 GEN
Solar/Wind Harmer
7.622
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
4.047
959331AF2-224 GEN
Solar/Wind Harmer
5.169
274827FISK ;RP
Adder
8.169
972037AH1-567 GEN1
Adder
0.193
960591AF2-350 GEN
Solar/Wind Harmer
7.341
274800UNIV PARK;3U
Adder
6.134
274801UNIV PARK;4U
Adder
6.134
972228AH1-698 GEN2
Adder
3.896
972227AH1-698 GEN1
Adder
2.744
24729505KEY G4
Adder
6.793
274687WILL CNTY;4U
Adder
29.249
274687WILL CNTY;4U
Adder
29.249
274675JOLIET 29;7U
Adder
32.088
274675JOLIET 29;7U
Adder
30.942
274728ELWOOD EC;5P
Adder
17.157
274731ELWOOD EC;2P
Adder
17.157
274733ELWOOD EC;3P
Adder
17.157
274735ELWOOD EC;4P
Adder
17.157
970833AG2-524 GEN
Solar/Wind Harmer
8.005
970833AG2-524 GEN
Solar/Wind Harmer
5.336
274744AC1-111 GEN8
Adder
5.803
274746AC1-111 G10
Adder
5.803
970073AG2-061 GEN
Solar/Wind Harmer
2.368
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.753
971411AH1-196 GEN
Solar/Wind Harmer
10.588
276861AD2-134 GEN
Solar/Wind Harmer
0.126
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
14.045
274823ROCKFORD ;21
Adder
19.56
971611AH1-305 GEN
Solar/Wind Harmer
4.163
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
926823AC1-168 GEN
Solar/Wind Harmer
1.181
970169AG2-114 GEN
Solar/Wind Harmer
6.939
971681AH1-341 GEN
Solar/Wind Harmer
11.162
972267AH1-718 GEN
Adder
4.093
276741O09 GEN1
Solar/Wind Harmer
0.242
971549AH1-272 GEN
Solar/Wind Harmer
14.066
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
9.126
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.079
965041AG1-368 GEN
Solar/Wind Harmer
6.739
946321AF1-296 GEN
Solar/Wind Harmer
3.754
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.235
965051AG1-369 GEN
Solar/Wind Harmer
3.245
963841AG1-237 GEN
Solar/Wind Harmer
2.784
276668AB2-070 GEN1
Solar/Wind Harmer
0.25
276848AB2-070 GEN3
Solar/Wind Harmer
0.249
276849AB2-070 GEN2
Solar/Wind Harmer
0.25
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.194
971609AH1-304 GEN
Solar/Wind Harmer
1.022
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.766
965021AG1-366 GEN
Solar/Wind Harmer
2.462
970707AG2-453 GEN
Solar/Wind Harmer
24.09
274814UNIV PK N;0U
Adder
5.338
274807UNIV PK N;3U
Adder
5.326
274811UNIV PK N;7U
Adder
5.291
972259AH1-714 GEN
Adder
20.093
274826FISK ;BP
Adder
11.527
274803UNIV PARK;6U
Adder
6.138
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.237
276806AD2-047 C O1
Solar/Wind Harmer
4.16
972038AH1-567 GEN2
Adder
0.384
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.942
274729ELWOOD EC;1P
Adder
17.157
274730ELWOOD EC;6P
Adder
17.157
274734ELWOOD EC;8P
Adder
17.157
274736ELWOOD EC;9P
Adder
17.157
943121AE2-341 GEN
Solar/Wind Harmer
12.163
943591AF1-030 GEN
Solar/Wind Harmer
8.088
274682WAUKEGAN ;7U
Adder
18.463
274862TOP CROP ;2U
Solar/Wind Harmer
0.968
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.416
274879MINONK ;1U
Solar/Wind Harmer
0.295
946671AF1-331 GEN
Solar/Wind Harmer
0.753
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
959091AF2-200 GEN
Solar/Wind Harmer
14.045
970571AG2-364 GEN
Solar/Wind Harmer
13.895
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.215
274767LEE CO EC;8U
Adder
9.107
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
24690905MDL-1G C
Solar/Wind Harmer
0
24721905FLATG4
Adder
19.661
970781AG2-491 GEN
Solar/Wind Harmer
6.766
965931AG1-462 GEN
Solar/Wind Harmer
17.022
971087AG2-675 GEN
Solar/Wind Harmer
3.56
965091AG1-374 GEN
Solar/Wind Harmer
19.952
959611AF2-252 GEN
Solar/Wind Harmer
2.217
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
971993AH1-541 GEN
Solar/Wind Harmer
2.938
24695305TIMB G C
Solar/Wind Harmer
0.537
970289AG2-191 GEN
Solar/Wind Harmer
0.691
957381AF2-032 GEN
Solar/Wind Harmer
1.388
942481AE2-261 GEN
Solar/Wind Harmer
18.271
246938BC-WTG3
Solar/Wind Harmer
0.218
270491AE1-102 GEN2
Solar/Wind Harmer
0.786
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270102X2-052 ST
50/50
1.749
270100X2-052 CT1
50/50
1.616
270101X2-052 CT2
50/50
1.616
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.526
274770LINCOLN ;1U
50/50
9.616
274771LINCOLN ;2U
50/50
9.616
970349AG2-230 GEN
Solar/Wind Harmer
12.041
965681AG1-436 GEN
Solar/Wind Harmer
9.504
965791AG1-447 GEN
Solar/Wind Harmer
6.97
961051AF2-396 GEN
Solar/Wind Harmer
14.959
961051AF2-396 GEN
Solar/Wind Harmer
9.973
274805UNIV PK N;1U
Adder
5.303
274808UNIV PK N;4U
Adder
5.268
274888KELLY CRK;1U
Solar/Wind Harmer
0.428
276776AD2-060 GEN
Solar/Wind Harmer
0.783
958011AF2-095 GEN
Solar/Wind Harmer
10.572
970941AG2-585 GEN
Solar/Wind Harmer
4.038
276897AD1-100 C
Solar/Wind Harmer
18.287
24344105CKG2
50/50
8.859
270143AC1-141 CT2_
50/50
2.617
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.55
274773LINCOLN ;4U
50/50
9.616
274774LINCOLN ;5U
50/50
9.616
962761AG1-125 GEN
Solar/Wind Harmer
74.627
970149AG2-104 GEN
Solar/Wind Harmer
40.3
970155AG2-107 GEN
Solar/Wind Harmer
47.655
957891AF2-083 GEN
Solar/Wind Harmer
12.55
945111AF1-176 GEN
Solar/Wind Harmer
13.401
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.895
274723RIVER EC ;12
Adder
19.037
274751CRETE EC ;1U
Adder
8.738
274754CRETE EC ;4U
Adder
8.738
965011AG1-365 GEN
Solar/Wind Harmer
7.385
274812UNIV PK N;8U
Adder
5.291
274802UNIV PARK;5U
Adder
6.138
970373AG2-245 GEN
Solar/Wind Harmer
15.385
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.088
274674JOLIET 9 ;6U
Adder
16.082
274732ELWOOD EC;7P
Adder
17.157
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.803
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.165
274682WAUKEGAN ;7U
Adder
18.463
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
11.336
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.78
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.257
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.318
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.826
971997AH1-543 GEN
Solar/Wind Harmer
3.71
957471AF2-041 GEN
Solar/Wind Harmer
21.068
959081AF2-199 GEN
Solar/Wind Harmer
7.023
971067AG2-660 GEN
Solar/Wind Harmer
2.341
274822ROCKFORD ;11
Adder
19.703
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.741
970819AG2-516 GEN
Solar/Wind Harmer
8.368
970569AG2-363 GEN
Solar/Wind Harmer
20.843
965651AG1-433 GEN
Solar/Wind Harmer
2.028
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.215
274766LEE CO EC;7U
Adder
9.107
276708O09 GEN2
Solar/Wind Harmer
0.242
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
958861AF2-177 GEN
Solar/Wind Harmer
2.941
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.439
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
14.886
276621W2-048 GEN
Solar/Wind Harmer
0.314
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
6.922
270032AE2-172
Solar/Wind Harmer
4.12
965421AG1-410 GEN
Solar/Wind Harmer
18.52
965911AG1-460 GEN
Solar/Wind Harmer
1.222
246936BC-WTG1
Solar/Wind Harmer
0.244
270489AE1-102 GEN1
Solar/Wind Harmer
0.786
276903AD2-071 C
Solar/Wind Harmer
6.725
274674JOLIET 9 ;6U
Adder
16.082
276893AG1-478 C
Solar/Wind Harmer
0.485
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
11.454
274693ROCKY RD ;1P
Adder
11.341
274697ROCKY RD ;3P
Adder
3.111
274696ROCKY RD ;4P
Adder
11.724
958481AF2-142 GEN
Solar/Wind Harmer
10.754
274683WAUKEGAN ;8U
Adder
21.627
274683WAUKEGAN ;8U
Adder
18.23
962691AG1-118 GEN
Solar/Wind Harmer
21.414
958491AF2-143 GEN
Solar/Wind Harmer
10.655
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.045
971343AH1-151 GEN
Solar/Wind Harmer
14.045
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.526
972236AH1-702 GEN2
Adder
2.196
938861AE1-114 GEN
Solar/Wind Harmer
3.928
944541AF1-119 GEN
Solar/Wind Harmer
0.462
960971AF2-388 GEN
Solar/Wind Harmer
4.056
274764LEE CO EC;5U
Adder
9.237
274765LEE CO EC;6U
Adder
9.237
274762LEE CO EC;3U
Adder
9.215
274763LEE CO EC;4U
Adder
9.128
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.104
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.191
942221AE2-234 GEN
Solar/Wind Harmer
2.684
960611AF2-352 GEN
Solar/Wind Harmer
2.217
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.745
944231AF1-091 GEN
Solar/Wind Harmer
15.08
270246TR4_N_V150
Solar/Wind Harmer
0.042
270247TR4_N_V136
Solar/Wind Harmer
0.042
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.669
970291AG2-192 GEN
Solar/Wind Harmer
0.817
970291AG2-192 GEN
Solar/Wind Harmer
0.377
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.353
270031AE2-169
Solar/Wind Harmer
3.44
270599AE1-208 GEN
Solar/Wind Harmer
5.734
971613AH1-306 GEN
Solar/Wind Harmer
2.966
276916AD2-100_GEN
Solar/Wind Harmer
12.749
276911AD2-131_GEN
Solar/Wind Harmer
0.84
246937BC-WTG2
Solar/Wind Harmer
0.244
270054AF2-122 C O1
Solar/Wind Helper
1.656
CPLELTFEXP_CPLE->PJM
CLTF
1.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.349
NYPJM->LTFIMP_NY
CLTF
2.583
LGEELTFEXP_LGEE->PJM
CLTF
3.675
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.237
AH1-155LTFEXP_AH1-155->PJM
LTF
0.356
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.267
MECLTFEXP_MEC->PJM
CLTF
14.733
SIGELTFEXP_SIGE->PJM
CLTF
0.34
LAGNLTFEXP_LAGN->PJM
CLTF
11.281
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.712
TVALTFEXP_TVA->PJM
CLTF
5.082

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.01 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5028.49
MW Contribution:
3.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
5.165
270144AC1-141 ST1_
50/50
3.155
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.587
24653605MOTTVILLE
50/50
0.006
959331AF2-224 GEN
Solar/Wind Harmer
7.385
270071AF1-092 GEN
Solar/Wind Harmer
20.17
970031AG2-029 GEN
Solar/Wind Harmer
5.617
971771AH1-392 GEN
Solar/Wind Harmer
10.358
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24729505KEY G4
Adder
9.292
274775LINCOLN ;6U
Adder
11.987
274776LINCOLN ;7U
Adder
11.987
274777LINCOLN ;8U
Adder
11.987
965041AG1-368 GEN
Solar/Wind Harmer
9.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
972037AH1-567 GEN1
Adder
0.255
274827FISK ;RP
Adder
10.79
274800UNIV PARK;3U
Adder
8.099
274801UNIV PARK;4U
Adder
8.099
960591AF2-350 GEN
Solar/Wind Harmer
9.692
972228AH1-698 GEN2
Adder
5.142
972227AH1-698 GEN1
Adder
3.62
247521TR3_G114
Solar/Wind Harmer
0.349
965051AG1-369 GEN
Solar/Wind Harmer
4.809
274687WILL CNTY;4U
Adder
38.553
274687WILL CNTY;4U
Adder
38.553
274675JOLIET 29;7U
Adder
42.278
274675JOLIET 29;7U
Adder
40.768
274728ELWOOD EC;5P
Adder
22.596
274731ELWOOD EC;2P
Adder
22.596
274733ELWOOD EC;3P
Adder
22.596
274735ELWOOD EC;4P
Adder
22.596
970833AG2-524 GEN
Solar/Wind Harmer
10.534
970833AG2-524 GEN
Solar/Wind Harmer
7.023
971549AH1-272 GEN
Solar/Wind Harmer
19.703
963791AG1-232 GEN
Solar/Wind Harmer
12.868
274744AC1-111 GEN8
Adder
7.624
274746AC1-111 G10
Adder
7.624
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.313
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
3.1
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.821
971675AH1-338 GEN
Solar/Wind Harmer
3.593
276861AD2-134 GEN
Solar/Wind Harmer
0.164
276863AD2-134 GEN
Solar/Wind Harmer
0.164
971611AH1-305 GEN
Solar/Wind Harmer
5.462
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.31
274823ROCKFORD ;21
Adder
25.482
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
926823AC1-168 GEN
Solar/Wind Harmer
1.537
970169AG2-114 GEN
Solar/Wind Harmer
9.036
971681AH1-341 GEN
Solar/Wind Harmer
14.503
972267AH1-718 GEN
Adder
5.303
270007AE1-245 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.313
274877BISHOP HL;1U
Solar/Wind Harmer
0.294
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.159
946321AF1-296 GEN
Solar/Wind Harmer
4.834
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.383
970289AG2-191 GEN
Solar/Wind Harmer
1.586
963841AG1-237 GEN
Solar/Wind Harmer
3.581
276668AB2-070 GEN1
Solar/Wind Harmer
0.319
276848AB2-070 GEN3
Solar/Wind Harmer
0.317
276849AB2-070 GEN2
Solar/Wind Harmer
0.319
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.111
247536S-71 GEN
Solar/Wind Harmer
0.301
944221AF1-090 GEN
Solar/Wind Harmer
4.35
270543AE2-219 C
Solar/Wind Harmer
5.021
971029AG2-637 GEN
Solar/Wind Harmer
10.16
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24721805FLATG3
50/50
5.165
24344105CKG2
50/50
11.949
270143AC1-141 CT2_
50/50
3.573
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.205
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
120.056
970149AG2-104 GEN
Solar/Wind Harmer
64.832
970155AG2-107 GEN
Solar/Wind Harmer
76.664
965011AG1-365 GEN
Solar/Wind Harmer
10.55
957891AF2-083 GEN
Solar/Wind Harmer
17.154
945111AF1-176 GEN
Solar/Wind Harmer
18.343
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
5.335
274773LINCOLN ;4U
Adder
11.987
274774LINCOLN ;5U
Adder
11.987
274723RIVER EC ;12
Adder
25.237
274751CRETE EC ;1U
Adder
11.595
274754CRETE EC ;4U
Adder
11.595
274812UNIV PK N;8U
Adder
7.005
970373AG2-245 GEN
Solar/Wind Harmer
20.466
274802UNIV PARK;5U
Adder
8.11
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.277
274674JOLIET 9 ;6U
Adder
21.182
274732ELWOOD EC;7P
Adder
22.596
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.624
965421AG1-410 GEN
Solar/Wind Harmer
28.373
965651AG1-433 GEN
Solar/Wind Harmer
2.763
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.529
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.202
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.213
274828WAUKEGAN ;BP
Adder
14.856
246936BC-WTG1
Solar/Wind Harmer
0.377
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.87
939401AE1-172 GEN
Solar/Wind Harmer
6.964
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.08
971997AH1-543 GEN
Solar/Wind Harmer
4.85
958861AF2-177 GEN
Solar/Wind Harmer
4.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.469
957471AF2-041 GEN
Solar/Wind Harmer
27.465
959081AF2-199 GEN
Solar/Wind Harmer
9.155
971067AG2-660 GEN
Solar/Wind Harmer
3.052
274822ROCKFORD ;11
Adder
25.668
970819AG2-516 GEN
Solar/Wind Harmer
10.889
970569AG2-363 GEN
Solar/Wind Harmer
27.133
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.963
274766LEE CO EC;7U
Adder
11.822
945371AF1-202 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.313
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.212
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.223
270032AE2-172
Solar/Wind Harmer
5.49
963741AG1-226 GEN
Solar/Wind Harmer
19.06
270005AE1-210 C O1
Solar/Wind Harmer
1.741
276903AD2-071 C
Solar/Wind Harmer
8.916
276621W2-048 GEN
Solar/Wind Harmer
0.399
970825AG2-519 GEN
Solar/Wind Harmer
2.813
965911AG1-460 GEN
Solar/Wind Harmer
1.54
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.437
24728605AND G2
Adder
3.753
970773AG2-487 GEN
Solar/Wind Harmer
1.148
23906502RICHG2&3
Adder
1.085
24722005FLATG5
50/50
5.165
24721905FLATG4
50/50
94.337
270475AD2-096_GEN
50/50
10.024
270142AC1-141 CT1_
50/50
3.573
24642205MAYFLWER
50/50
0.054
944961AF1-161 GEN
50/50
4.258
962601AG1-109 GEN
50/50
4.258
962771AG1-126 GEN
Solar/Wind Harmer
120.056
970153AG2-106 GEN
Solar/Wind Harmer
76.664
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270043AE2-236 GEN
Solar/Wind Harmer
6.98
971347AH1-153 GEN
Solar/Wind Harmer
5.418
965021AG1-366 GEN
Solar/Wind Harmer
3.517
270063AE2-323 C
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
10.819
945111AF1-176 GEN
Solar/Wind Harmer
8.333
944531AF1-118 GEN
Solar/Wind Harmer
45.71
274772LINCOLN ;3U
Adder
11.987
274724RIVER EC ;11
Adder
24.945
274752CRETE EC ;2U
Adder
11.595
274753CRETE EC ;3U
Adder
11.595
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.066
274807UNIV PK N;3U
Adder
7.051
274811UNIV PK N;7U
Adder
7.005
970707AG2-453 GEN
Solar/Wind Harmer
31.765
274803UNIV PARK;6U
Adder
8.11
274826FISK ;BP
Adder
15.225
972038AH1-567 GEN2
Adder
0.507
274887GEN-1.85
Solar/Wind Harmer
0.252
276843GEN-1.7
Solar/Wind Harmer
0.313
276806AD2-047 C O1
Solar/Wind Harmer
5.492
972259AH1-714 GEN
Adder
26.498
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
40.767
274730ELWOOD EC;6P
Adder
22.596
274734ELWOOD EC;8P
Adder
22.596
274736ELWOOD EC;9P
Adder
22.596
274729ELWOOD EC;1P
Adder
22.596
943121AE2-341 GEN
Solar/Wind Harmer
15.981
943591AF1-030 GEN
Solar/Wind Harmer
10.628
24695305TIMB G C
Solar/Wind Harmer
0.801
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
1.27
274682WAUKEGAN ;7U
Adder
24.202
246938BC-WTG3
Solar/Wind Harmer
0.336
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
276868AE1-113 GEN
Solar/Wind Harmer
1.852
274879MINONK ;1U
Solar/Wind Harmer
0.386
946671AF1-331 GEN
Solar/Wind Harmer
0.983
274855GSG-6 ;RU
Solar/Wind Harmer
0.336
274850MENDOTA H;RU
Solar/Wind Harmer
0.107
959091AF2-200 GEN
Solar/Wind Harmer
18.31
970571AG2-364 GEN
Solar/Wind Harmer
18.089
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.963
274767LEE CO EC;8U
Adder
11.822
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.294
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.799
965931AG1-462 GEN
Solar/Wind Harmer
21.892
971087AG2-675 GEN
Solar/Wind Harmer
4.579
965091AG1-374 GEN
Solar/Wind Harmer
25.724
959611AF2-252 GEN
Solar/Wind Harmer
2.858
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.918
971993AH1-541 GEN
Solar/Wind Harmer
3.746
270004AE1-209 GEN
Solar/Wind Harmer
1.741
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.999
970825AG2-519 GEN
Solar/Wind Harmer
5.97
946031AF1-268 GEN
Solar/Wind Harmer
7.51
957381AF2-032 GEN
Solar/Wind Harmer
1.751
942481AE2-261 GEN
Solar/Wind Harmer
23.025
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
11.007
24728705AND G3
Adder
7.849
24728505AND G1
Adder
3.753
23906402RICHG1
Adder
1.086
23906502RICHG2&3
Adder
1.085
270541AE2-072 C
Solar/Wind Harmer
0
24721705FLATG2
50/50
76.7
247620Y3-023
50/50
0.723
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.175
270101X2-052 CT2
50/50
2.175
24643105BUCHANAN
50/50
0.019
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.255
961051AF2-396 GEN
Solar/Wind Harmer
20.485
961051AF2-396 GEN
Solar/Wind Harmer
13.656
965681AG1-436 GEN
Solar/Wind Harmer
12.767
965791AG1-447 GEN
Solar/Wind Harmer
9.363
274770LINCOLN ;1U
Adder
11.987
274771LINCOLN ;2U
Adder
11.987
274805UNIV PK N;1U
Adder
7.02
274808UNIV PK N;4U
Adder
6.974
274888KELLY CRK;1U
Solar/Wind Harmer
0.565
276776AD2-060 GEN
Solar/Wind Harmer
1.034
958011AF2-095 GEN
Solar/Wind Harmer
13.957
970941AG2-585 GEN
Solar/Wind Harmer
5.331
276897AD1-100 C
Solar/Wind Harmer
24.102
270246TR4_N_V150
Solar/Wind Harmer
0.062
270247TR4_N_V136
Solar/Wind Harmer
0.062
274674JOLIET 9 ;6U
Adder
21.182
276893AG1-478 C
Solar/Wind Harmer
0.639
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
21.933
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.526
958481AF2-142 GEN
Solar/Wind Harmer
14.114
274695ROCKY RD ;2P
Adder
15.016
274693ROCKY RD ;1P
Adder
14.868
274697ROCKY RD ;3P
Adder
4.079
274696ROCKY RD ;4P
Adder
15.37
274683WAUKEGAN ;8U
Adder
28.341
274683WAUKEGAN ;8U
Adder
23.89
962691AG1-118 GEN
Solar/Wind Harmer
28.03
246937BC-WTG2
Solar/Wind Harmer
0.377
270462AD2-086
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
13.95
276901AD2-066 C O1
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
3.701
971341AH1-150 GEN
Solar/Wind Harmer
18.31
971343AH1-151 GEN
Solar/Wind Harmer
18.31
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.289
972236AH1-702 GEN2
Adder
2.86
938861AE1-114 GEN
Solar/Wind Harmer
5.103
274764LEE CO EC;5U
Adder
11.991
274765LEE CO EC;6U
Adder
11.991
274762LEE CO EC;3U
Adder
11.963
274763LEE CO EC;4U
Adder
11.851
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.43
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.607
942111AE2-223 GEN
Solar/Wind Harmer
2.835
960611AF2-352 GEN
Solar/Wind Harmer
2.858
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.962
270031AE2-169
Solar/Wind Harmer
4.656
270599AE1-208 GEN
Solar/Wind Harmer
7.759
970291AG2-192 GEN
Solar/Wind Harmer
1.085
970291AG2-192 GEN
Solar/Wind Harmer
0.501
971613AH1-306 GEN
Solar/Wind Harmer
3.953
970241AG2-163 GEN
Solar/Wind Harmer
4.698
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.598
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.449
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
247621Y3-024
Adder
0.268
970621AG2-405 GEN
Solar/Wind Harmer
1.408
276916AD2-100_GEN
Solar/Wind Harmer
16.036
276911AD2-131_GEN
Solar/Wind Harmer
1.056
926881AC1-175 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.796
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.172
970885AG2-551 GEN
Solar/Wind Harmer
2.391
971587AH1-292 GEN
Solar/Wind Harmer
4.706
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.213
NYPJM->LTFIMP_NY
CLTF
2.987
LGEELTFEXP_LGEE->PJM
CLTF
4.166
WECLTFEXP_WEC->PJM
CLTF
4.975
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.28
AG2-052LTFEXP_AG2-052->PJM
LTF
0.313
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.612
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.183
MECLTFEXP_MEC->PJM
CLTF
18.423
SIGELTFEXP_SIGE->PJM
CLTF
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
11.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.355
TVALTFEXP_TVA->PJM
CLTF
4.573

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5774.92
MW Contribution:
3.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
971347AH1-153 GEN
Solar/Wind Harmer
4.684
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274753CRETE EC ;3U
Adder
10.415
270505AE1-170 C O1
Solar/Wind Harmer
9.246
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
0.228
276843GEN-1.7
Solar/Wind Harmer
0.284
276806AD2-047 C O1
Solar/Wind Harmer
4.976
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
17.002
970571AG2-364 GEN
Solar/Wind Harmer
16.871
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
965931AG1-462 GEN
Solar/Wind Harmer
20.885
971087AG2-675 GEN
Solar/Wind Harmer
4.368
965091AG1-374 GEN
Solar/Wind Harmer
24.551
959611AF2-252 GEN
Solar/Wind Harmer
2.728
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.663
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
957381AF2-032 GEN
Solar/Wind Harmer
1.75
942481AE2-261 GEN
Solar/Wind Harmer
23.05
270004AE1-209 GEN
Solar/Wind Harmer
1.624
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24695305TIMB G C
Solar/Wind Harmer
0.627
970825AG2-519 GEN
Solar/Wind Harmer
5.579
946031AF1-268 GEN
Solar/Wind Harmer
6.994
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
17.36
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274775LINCOLN ;6U
Adder
10.797
274776LINCOLN ;7U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
5.989
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.434
970169AG2-114 GEN
Solar/Wind Harmer
8.435
971681AH1-341 GEN
Solar/Wind Harmer
13.557
972267AH1-718 GEN
Adder
4.986
276741O09 GEN1
Solar/Wind Harmer
0.295
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.677
946321AF1-296 GEN
Solar/Wind Harmer
4.601
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
10.858
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
971549AH1-272 GEN
Solar/Wind Harmer
16.367
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.859
970289AG2-191 GEN
Solar/Wind Harmer
1.486
971609AH1-304 GEN
Solar/Wind Harmer
1.264
247521TR3_G114
Solar/Wind Harmer
0.275
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.891
247536S-71 GEN
Solar/Wind Harmer
0.278
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.586
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
80.774
970149AG2-104 GEN
Solar/Wind Harmer
43.619
970155AG2-107 GEN
Solar/Wind Harmer
51.58
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
10.415
274754CRETE EC ;4U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
945111AF1-176 GEN
Solar/Wind Harmer
15.659
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
6.422
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971997AH1-543 GEN
Solar/Wind Harmer
4.485
957471AF2-041 GEN
Solar/Wind Harmer
25.504
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
970569AG2-363 GEN
Solar/Wind Harmer
25.306
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
965651AG1-433 GEN
Solar/Wind Harmer
2.449
276708O09 GEN2
Solar/Wind Harmer
0.295
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
965911AG1-460 GEN
Solar/Wind Harmer
1.542
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.459
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
965421AG1-410 GEN
Solar/Wind Harmer
21.55
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.196
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
972203AH1-686 GEN
Adder
1.998
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
14.053
965681AG1-436 GEN
Solar/Wind Harmer
11.209
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
276776AD2-060 GEN
Solar/Wind Harmer
0.937
958011AF2-095 GEN
Solar/Wind Harmer
12.646
970941AG2-585 GEN
Solar/Wind Harmer
4.83
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
21.908
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.582
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
25.814
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
972236AH1-702 GEN2
Adder
2.662
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.897
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.686
960611AF2-352 GEN
Solar/Wind Harmer
2.728
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.921
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
270031AE2-169
Solar/Wind Harmer
4.257
270599AE1-208 GEN
Solar/Wind Harmer
7.096
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
276911AD2-131_GEN
Solar/Wind Harmer
1.062
270246TR4_N_V150
Solar/Wind Harmer
0.049
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.284
270383AD1-128 GEN
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
970883AG2-550 GEN
Solar/Wind Harmer
6.689
970885AG2-551 GEN
Solar/Wind Harmer
2.23
270054AF2-122 C O1
Solar/Wind Helper
1.547
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.76 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4482.29
MW Contribution:
2.97
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.617
24642205MAYFLWER
50/50
0.04
274772LINCOLN ;3U
50/50
9.616
944961AF1-161 GEN
50/50
3.109
962601AG1-109 GEN
50/50
3.109
962771AG1-126 GEN
Solar/Wind Harmer
74.627
970153AG2-106 GEN
Solar/Wind Harmer
47.655
971347AH1-153 GEN
Solar/Wind Harmer
4.014
270043AE2-236 GEN
Solar/Wind Harmer
5.048
270505AE1-170 C O1
Solar/Wind Harmer
7.914
270063AE2-323 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.088
944531AF1-118 GEN
Solar/Wind Harmer
33.371
274724RIVER EC ;11
Adder
18.817
274752CRETE EC ;2U
Adder
8.738
274753CRETE EC ;3U
Adder
8.738
965021AG1-366 GEN
Solar/Wind Harmer
2.462
970707AG2-453 GEN
Solar/Wind Harmer
24.09
274814UNIV PK N;0U
Adder
5.338
274807UNIV PK N;3U
Adder
5.326
274811UNIV PK N;7U
Adder
5.291
972259AH1-714 GEN
Adder
20.093
274826FISK ;BP
Adder
11.527
274803UNIV PARK;6U
Adder
6.138
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.237
276806AD2-047 C O1
Solar/Wind Harmer
4.16
972038AH1-567 GEN2
Adder
0.384
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.942
274729ELWOOD EC;1P
Adder
17.157
274730ELWOOD EC;6P
Adder
17.157
274734ELWOOD EC;8P
Adder
17.157
274736ELWOOD EC;9P
Adder
17.157
943121AE2-341 GEN
Solar/Wind Harmer
12.163
943591AF1-030 GEN
Solar/Wind Harmer
8.088
274682WAUKEGAN ;7U
Adder
18.463
274862TOP CROP ;2U
Solar/Wind Harmer
0.968
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.416
274879MINONK ;1U
Solar/Wind Harmer
0.295
946671AF1-331 GEN
Solar/Wind Harmer
0.753
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
959091AF2-200 GEN
Solar/Wind Harmer
14.045
970571AG2-364 GEN
Solar/Wind Harmer
13.895
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.215
274767LEE CO EC;8U
Adder
9.107
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
24690905MDL-1G C
Solar/Wind Harmer
0
24721905FLATG4
Adder
19.661
970781AG2-491 GEN
Solar/Wind Harmer
6.766
965931AG1-462 GEN
Solar/Wind Harmer
17.022
971087AG2-675 GEN
Solar/Wind Harmer
3.56
24344105CKG2
50/50
8.859
270143AC1-141 CT2_
50/50
2.617
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.55
274773LINCOLN ;4U
50/50
9.616
274774LINCOLN ;5U
50/50
9.616
962761AG1-125 GEN
Solar/Wind Harmer
74.627
970149AG2-104 GEN
Solar/Wind Harmer
40.3
970155AG2-107 GEN
Solar/Wind Harmer
47.655
957891AF2-083 GEN
Solar/Wind Harmer
12.55
945111AF1-176 GEN
Solar/Wind Harmer
13.401
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.895
274723RIVER EC ;12
Adder
19.037
274751CRETE EC ;1U
Adder
8.738
274754CRETE EC ;4U
Adder
8.738
965011AG1-365 GEN
Solar/Wind Harmer
7.385
274812UNIV PK N;8U
Adder
5.291
274802UNIV PARK;5U
Adder
6.138
970373AG2-245 GEN
Solar/Wind Harmer
15.385
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.088
274674JOLIET 9 ;6U
Adder
16.082
274732ELWOOD EC;7P
Adder
17.157
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.803
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.165
274682WAUKEGAN ;7U
Adder
18.463
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
11.336
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.78
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.257
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.318
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.826
971997AH1-543 GEN
Solar/Wind Harmer
3.71
957471AF2-041 GEN
Solar/Wind Harmer
21.068
959081AF2-199 GEN
Solar/Wind Harmer
7.023
971067AG2-660 GEN
Solar/Wind Harmer
2.341
274822ROCKFORD ;11
Adder
19.703
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.741
970819AG2-516 GEN
Solar/Wind Harmer
8.368
970569AG2-363 GEN
Solar/Wind Harmer
20.843
965651AG1-433 GEN
Solar/Wind Harmer
2.028
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.215
274766LEE CO EC;7U
Adder
9.107
276708O09 GEN2
Solar/Wind Harmer
0.242
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
958861AF2-177 GEN
Solar/Wind Harmer
2.941
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.439
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
14.886
276621W2-048 GEN
Solar/Wind Harmer
0.314
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270102X2-052 ST
50/50
1.749
270100X2-052 CT1
50/50
1.616
270101X2-052 CT2
50/50
1.616
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.526
274770LINCOLN ;1U
50/50
9.616
274771LINCOLN ;2U
50/50
9.616
970349AG2-230 GEN
Solar/Wind Harmer
12.041
965681AG1-436 GEN
Solar/Wind Harmer
9.504
965791AG1-447 GEN
Solar/Wind Harmer
6.97
961051AF2-396 GEN
Solar/Wind Harmer
14.959
961051AF2-396 GEN
Solar/Wind Harmer
9.973
274805UNIV PK N;1U
Adder
5.303
274808UNIV PK N;4U
Adder
5.268
274888KELLY CRK;1U
Solar/Wind Harmer
0.428
276776AD2-060 GEN
Solar/Wind Harmer
0.783
958011AF2-095 GEN
Solar/Wind Harmer
10.572
970941AG2-585 GEN
Solar/Wind Harmer
4.038
276897AD1-100 C
Solar/Wind Harmer
18.287
274674JOLIET 9 ;6U
Adder
16.082
276893AG1-478 C
Solar/Wind Harmer
0.485
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
11.454
274693ROCKY RD ;1P
Adder
11.341
274697ROCKY RD ;3P
Adder
3.111
274696ROCKY RD ;4P
Adder
11.724
958481AF2-142 GEN
Solar/Wind Harmer
10.754
274683WAUKEGAN ;8U
Adder
21.627
274683WAUKEGAN ;8U
Adder
18.23
962691AG1-118 GEN
Solar/Wind Harmer
21.414
958491AF2-143 GEN
Solar/Wind Harmer
10.655
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.045
971343AH1-151 GEN
Solar/Wind Harmer
14.045
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.526
972236AH1-702 GEN2
Adder
2.196
938861AE1-114 GEN
Solar/Wind Harmer
3.928
944541AF1-119 GEN
Solar/Wind Harmer
0.462
960971AF2-388 GEN
Solar/Wind Harmer
4.056
274764LEE CO EC;5U
Adder
9.237
274765LEE CO EC;6U
Adder
9.237
274762LEE CO EC;3U
Adder
9.215
274763LEE CO EC;4U
Adder
9.128
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.104
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.191
942221AE2-234 GEN
Solar/Wind Harmer
2.684
960611AF2-352 GEN
Solar/Wind Harmer
2.217
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.745
944231AF1-091 GEN
Solar/Wind Harmer
15.08
270246TR4_N_V150
Solar/Wind Harmer
0.042
270247TR4_N_V136
Solar/Wind Harmer
0.042
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.669
970291AG2-192 GEN
Solar/Wind Harmer
0.817
970291AG2-192 GEN
Solar/Wind Harmer
0.377
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.353
270031AE2-169
Solar/Wind Harmer
3.44
270599AE1-208 GEN
Solar/Wind Harmer
5.734
971613AH1-306 GEN
Solar/Wind Harmer
2.966
276916AD2-100_GEN
Solar/Wind Harmer
12.749
276911AD2-131_GEN
Solar/Wind Harmer
0.84
246937BC-WTG2
Solar/Wind Harmer
0.244
270054AF2-122 C O1
Solar/Wind Helper
1.656
270144AC1-141 ST1_
50/50
2.311
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.028
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.616
274776LINCOLN ;7U
50/50
9.616
274777LINCOLN ;8U
50/50
9.616
270071AF1-092 GEN
Solar/Wind Harmer
14.768
971771AH1-392 GEN
Solar/Wind Harmer
7.622
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
4.047
959331AF2-224 GEN
Solar/Wind Harmer
5.169
274827FISK ;RP
Adder
8.169
972037AH1-567 GEN1
Adder
0.193
960591AF2-350 GEN
Solar/Wind Harmer
7.341
274800UNIV PARK;3U
Adder
6.134
274801UNIV PARK;4U
Adder
6.134
972228AH1-698 GEN2
Adder
3.896
972227AH1-698 GEN1
Adder
2.744
24729505KEY G4
Adder
6.793
274687WILL CNTY;4U
Adder
29.249
274687WILL CNTY;4U
Adder
29.249
274675JOLIET 29;7U
Adder
32.088
274675JOLIET 29;7U
Adder
30.942
274728ELWOOD EC;5P
Adder
17.157
274731ELWOOD EC;2P
Adder
17.157
274733ELWOOD EC;3P
Adder
17.157
274735ELWOOD EC;4P
Adder
17.157
970833AG2-524 GEN
Solar/Wind Harmer
8.005
970833AG2-524 GEN
Solar/Wind Harmer
5.336
274744AC1-111 GEN8
Adder
5.803
274746AC1-111 G10
Adder
5.803
970073AG2-061 GEN
Solar/Wind Harmer
2.368
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.753
971411AH1-196 GEN
Solar/Wind Harmer
10.588
276861AD2-134 GEN
Solar/Wind Harmer
0.126
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
14.045
274823ROCKFORD ;21
Adder
19.56
971611AH1-305 GEN
Solar/Wind Harmer
4.163
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
926823AC1-168 GEN
Solar/Wind Harmer
1.181
970169AG2-114 GEN
Solar/Wind Harmer
6.939
971681AH1-341 GEN
Solar/Wind Harmer
11.162
972267AH1-718 GEN
Adder
4.093
276741O09 GEN1
Solar/Wind Harmer
0.242
971549AH1-272 GEN
Solar/Wind Harmer
14.066
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
9.126
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.079
965041AG1-368 GEN
Solar/Wind Harmer
6.739
946321AF1-296 GEN
Solar/Wind Harmer
3.754
965091AG1-374 GEN
Solar/Wind Harmer
19.952
959611AF2-252 GEN
Solar/Wind Harmer
2.217
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
971993AH1-541 GEN
Solar/Wind Harmer
2.938
24695305TIMB G C
Solar/Wind Harmer
0.537
970289AG2-191 GEN
Solar/Wind Harmer
0.691
957381AF2-032 GEN
Solar/Wind Harmer
1.388
942481AE2-261 GEN
Solar/Wind Harmer
18.271
246938BC-WTG3
Solar/Wind Harmer
0.218
270491AE1-102 GEN2
Solar/Wind Harmer
0.786
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.235
965051AG1-369 GEN
Solar/Wind Harmer
3.245
963841AG1-237 GEN
Solar/Wind Harmer
2.784
276668AB2-070 GEN1
Solar/Wind Harmer
0.25
276848AB2-070 GEN3
Solar/Wind Harmer
0.249
276849AB2-070 GEN2
Solar/Wind Harmer
0.25
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.194
971609AH1-304 GEN
Solar/Wind Harmer
1.022
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.766
270594AE1-207 GEN
Solar/Wind Harmer
6.922
270032AE2-172
Solar/Wind Harmer
4.12
965421AG1-410 GEN
Solar/Wind Harmer
18.52
965911AG1-460 GEN
Solar/Wind Harmer
1.222
246936BC-WTG1
Solar/Wind Harmer
0.244
270489AE1-102 GEN1
Solar/Wind Harmer
0.786
276903AD2-071 C
Solar/Wind Harmer
6.725
CPLELTFEXP_CPLE->PJM
CLTF
1.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.349
NYPJM->LTFIMP_NY
CLTF
2.583
LGEELTFEXP_LGEE->PJM
CLTF
3.675
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.237
AH1-155LTFEXP_AH1-155->PJM
LTF
0.356
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.267
MECLTFEXP_MEC->PJM
CLTF
14.733
SIGELTFEXP_SIGE->PJM
CLTF
0.34
LAGNLTFEXP_LAGN->PJM
CLTF
11.281
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.712
TVALTFEXP_TVA->PJM
CLTF
5.082

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.28 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5040.8
MW Contribution:
3.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
5.165
270144AC1-141 ST1_
50/50
3.155
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.587
24653605MOTTVILLE
50/50
0.006
959331AF2-224 GEN
Solar/Wind Harmer
7.385
270071AF1-092 GEN
Solar/Wind Harmer
20.17
970031AG2-029 GEN
Solar/Wind Harmer
5.617
971771AH1-392 GEN
Solar/Wind Harmer
10.358
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24729505KEY G4
Adder
9.292
274775LINCOLN ;6U
Adder
11.987
274776LINCOLN ;7U
Adder
11.987
274777LINCOLN ;8U
Adder
11.987
965041AG1-368 GEN
Solar/Wind Harmer
9.85
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
972037AH1-567 GEN1
Adder
0.255
274827FISK ;RP
Adder
10.79
274800UNIV PARK;3U
Adder
8.099
274801UNIV PARK;4U
Adder
8.099
960591AF2-350 GEN
Solar/Wind Harmer
9.692
972228AH1-698 GEN2
Adder
5.142
972227AH1-698 GEN1
Adder
3.62
247521TR3_G114
Solar/Wind Harmer
0.349
965051AG1-369 GEN
Solar/Wind Harmer
4.809
274687WILL CNTY;4U
Adder
38.553
274687WILL CNTY;4U
Adder
38.553
274675JOLIET 29;7U
Adder
42.278
274675JOLIET 29;7U
Adder
40.768
274728ELWOOD EC;5P
Adder
22.596
274731ELWOOD EC;2P
Adder
22.596
274733ELWOOD EC;3P
Adder
22.596
274735ELWOOD EC;4P
Adder
22.596
970833AG2-524 GEN
Solar/Wind Harmer
10.534
970833AG2-524 GEN
Solar/Wind Harmer
7.023
971549AH1-272 GEN
Solar/Wind Harmer
19.703
963791AG1-232 GEN
Solar/Wind Harmer
12.868
274744AC1-111 GEN8
Adder
7.624
274746AC1-111 G10
Adder
7.624
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.313
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
3.1
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.821
971675AH1-338 GEN
Solar/Wind Harmer
3.593
276861AD2-134 GEN
Solar/Wind Harmer
0.164
276863AD2-134 GEN
Solar/Wind Harmer
0.164
971611AH1-305 GEN
Solar/Wind Harmer
5.462
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.31
274823ROCKFORD ;21
Adder
25.482
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
926823AC1-168 GEN
Solar/Wind Harmer
1.537
970169AG2-114 GEN
Solar/Wind Harmer
9.036
971681AH1-341 GEN
Solar/Wind Harmer
14.503
972267AH1-718 GEN
Adder
5.303
270007AE1-245 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.313
274877BISHOP HL;1U
Solar/Wind Harmer
0.294
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.159
946321AF1-296 GEN
Solar/Wind Harmer
4.834
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.383
970289AG2-191 GEN
Solar/Wind Harmer
1.586
963841AG1-237 GEN
Solar/Wind Harmer
3.581
276668AB2-070 GEN1
Solar/Wind Harmer
0.319
276848AB2-070 GEN3
Solar/Wind Harmer
0.317
276849AB2-070 GEN2
Solar/Wind Harmer
0.319
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.111
247536S-71 GEN
Solar/Wind Harmer
0.301
944221AF1-090 GEN
Solar/Wind Harmer
4.35
270543AE2-219 C
Solar/Wind Harmer
5.021
971029AG2-637 GEN
Solar/Wind Harmer
10.16
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24722005FLATG5
50/50
5.165
24721905FLATG4
50/50
94.337
270475AD2-096_GEN
50/50
10.024
270142AC1-141 CT1_
50/50
3.573
24642205MAYFLWER
50/50
0.054
944961AF1-161 GEN
50/50
4.258
962601AG1-109 GEN
50/50
4.258
962771AG1-126 GEN
Solar/Wind Harmer
120.056
970153AG2-106 GEN
Solar/Wind Harmer
76.664
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270043AE2-236 GEN
Solar/Wind Harmer
6.98
971347AH1-153 GEN
Solar/Wind Harmer
5.418
965021AG1-366 GEN
Solar/Wind Harmer
3.517
270063AE2-323 C
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
10.819
945111AF1-176 GEN
Solar/Wind Harmer
8.333
944531AF1-118 GEN
Solar/Wind Harmer
45.71
274772LINCOLN ;3U
Adder
11.987
274724RIVER EC ;11
Adder
24.945
274752CRETE EC ;2U
Adder
11.595
274753CRETE EC ;3U
Adder
11.595
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.066
274807UNIV PK N;3U
Adder
7.051
274811UNIV PK N;7U
Adder
7.005
970707AG2-453 GEN
Solar/Wind Harmer
31.765
274803UNIV PARK;6U
Adder
8.11
274826FISK ;BP
Adder
15.225
972038AH1-567 GEN2
Adder
0.507
274887GEN-1.85
Solar/Wind Harmer
0.252
276843GEN-1.7
Solar/Wind Harmer
0.313
276806AD2-047 C O1
Solar/Wind Harmer
5.492
972259AH1-714 GEN
Adder
26.498
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
40.767
274730ELWOOD EC;6P
Adder
22.596
274734ELWOOD EC;8P
Adder
22.596
274736ELWOOD EC;9P
Adder
22.596
274729ELWOOD EC;1P
Adder
22.596
943121AE2-341 GEN
Solar/Wind Harmer
15.981
943591AF1-030 GEN
Solar/Wind Harmer
10.628
24695305TIMB G C
Solar/Wind Harmer
0.801
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
1.27
274682WAUKEGAN ;7U
Adder
24.202
246938BC-WTG3
Solar/Wind Harmer
0.336
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
276868AE1-113 GEN
Solar/Wind Harmer
1.852
274879MINONK ;1U
Solar/Wind Harmer
0.386
946671AF1-331 GEN
Solar/Wind Harmer
0.983
274855GSG-6 ;RU
Solar/Wind Harmer
0.336
274850MENDOTA H;RU
Solar/Wind Harmer
0.107
959091AF2-200 GEN
Solar/Wind Harmer
18.31
970571AG2-364 GEN
Solar/Wind Harmer
18.089
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.963
24721805FLATG3
50/50
5.165
24344105CKG2
50/50
11.949
270143AC1-141 CT2_
50/50
3.573
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.205
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
120.056
970149AG2-104 GEN
Solar/Wind Harmer
64.832
970155AG2-107 GEN
Solar/Wind Harmer
76.664
965011AG1-365 GEN
Solar/Wind Harmer
10.55
957891AF2-083 GEN
Solar/Wind Harmer
17.154
945111AF1-176 GEN
Solar/Wind Harmer
18.343
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
5.335
274773LINCOLN ;4U
Adder
11.987
274774LINCOLN ;5U
Adder
11.987
274723RIVER EC ;12
Adder
25.237
274751CRETE EC ;1U
Adder
11.595
274754CRETE EC ;4U
Adder
11.595
274812UNIV PK N;8U
Adder
7.005
970373AG2-245 GEN
Solar/Wind Harmer
20.466
274802UNIV PARK;5U
Adder
8.11
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.277
274674JOLIET 9 ;6U
Adder
21.182
274732ELWOOD EC;7P
Adder
22.596
270055AF2-134 C O1
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.624
965421AG1-410 GEN
Solar/Wind Harmer
28.373
965651AG1-433 GEN
Solar/Wind Harmer
2.763
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.529
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.202
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.213
274828WAUKEGAN ;BP
Adder
14.856
246936BC-WTG1
Solar/Wind Harmer
0.377
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.87
939401AE1-172 GEN
Solar/Wind Harmer
6.964
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.08
971997AH1-543 GEN
Solar/Wind Harmer
4.85
958861AF2-177 GEN
Solar/Wind Harmer
4.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.469
957471AF2-041 GEN
Solar/Wind Harmer
27.465
959081AF2-199 GEN
Solar/Wind Harmer
9.155
971067AG2-660 GEN
Solar/Wind Harmer
3.052
274822ROCKFORD ;11
Adder
25.668
970819AG2-516 GEN
Solar/Wind Harmer
10.889
970569AG2-363 GEN
Solar/Wind Harmer
27.133
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.963
274766LEE CO EC;7U
Adder
11.822
945371AF1-202 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.313
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.212
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.223
270032AE2-172
Solar/Wind Harmer
5.49
963741AG1-226 GEN
Solar/Wind Harmer
19.06
270005AE1-210 C O1
Solar/Wind Harmer
1.741
276903AD2-071 C
Solar/Wind Harmer
8.916
276621W2-048 GEN
Solar/Wind Harmer
0.399
970825AG2-519 GEN
Solar/Wind Harmer
2.813
965911AG1-460 GEN
Solar/Wind Harmer
1.54
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.437
24728605AND G2
Adder
3.753
970773AG2-487 GEN
Solar/Wind Harmer
1.148
23906502RICHG2&3
Adder
1.085
274767LEE CO EC;8U
Adder
11.822
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.294
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.799
965931AG1-462 GEN
Solar/Wind Harmer
21.892
971087AG2-675 GEN
Solar/Wind Harmer
4.579
965091AG1-374 GEN
Solar/Wind Harmer
25.724
959611AF2-252 GEN
Solar/Wind Harmer
2.858
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.918
971993AH1-541 GEN
Solar/Wind Harmer
3.746
270004AE1-209 GEN
Solar/Wind Harmer
1.741
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.999
970825AG2-519 GEN
Solar/Wind Harmer
5.97
946031AF1-268 GEN
Solar/Wind Harmer
7.51
957381AF2-032 GEN
Solar/Wind Harmer
1.751
942481AE2-261 GEN
Solar/Wind Harmer
23.025
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
11.007
24728705AND G3
Adder
7.849
24728505AND G1
Adder
3.753
23906402RICHG1
Adder
1.086
23906502RICHG2&3
Adder
1.085
270541AE2-072 C
Solar/Wind Harmer
0
24721705FLATG2
50/50
76.7
247620Y3-023
50/50
0.723
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.175
270101X2-052 CT2
50/50
2.175
24643105BUCHANAN
50/50
0.019
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.255
961051AF2-396 GEN
Solar/Wind Harmer
20.485
961051AF2-396 GEN
Solar/Wind Harmer
13.656
965681AG1-436 GEN
Solar/Wind Harmer
12.767
965791AG1-447 GEN
Solar/Wind Harmer
9.363
274770LINCOLN ;1U
Adder
11.987
274771LINCOLN ;2U
Adder
11.987
274805UNIV PK N;1U
Adder
7.02
274808UNIV PK N;4U
Adder
6.974
274888KELLY CRK;1U
Solar/Wind Harmer
0.565
276776AD2-060 GEN
Solar/Wind Harmer
1.034
958011AF2-095 GEN
Solar/Wind Harmer
13.957
970941AG2-585 GEN
Solar/Wind Harmer
5.331
276897AD1-100 C
Solar/Wind Harmer
24.102
270246TR4_N_V150
Solar/Wind Harmer
0.062
270247TR4_N_V136
Solar/Wind Harmer
0.062
274674JOLIET 9 ;6U
Adder
21.182
276893AG1-478 C
Solar/Wind Harmer
0.639
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
21.933
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.526
958481AF2-142 GEN
Solar/Wind Harmer
14.114
274695ROCKY RD ;2P
Adder
15.016
274693ROCKY RD ;1P
Adder
14.868
274697ROCKY RD ;3P
Adder
4.079
274696ROCKY RD ;4P
Adder
15.37
274683WAUKEGAN ;8U
Adder
28.341
274683WAUKEGAN ;8U
Adder
23.89
962691AG1-118 GEN
Solar/Wind Harmer
28.03
246937BC-WTG2
Solar/Wind Harmer
0.377
270462AD2-086
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
13.95
276901AD2-066 C O1
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
3.701
971341AH1-150 GEN
Solar/Wind Harmer
18.31
971343AH1-151 GEN
Solar/Wind Harmer
18.31
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.289
972236AH1-702 GEN2
Adder
2.86
938861AE1-114 GEN
Solar/Wind Harmer
5.103
274764LEE CO EC;5U
Adder
11.991
274765LEE CO EC;6U
Adder
11.991
274762LEE CO EC;3U
Adder
11.963
274763LEE CO EC;4U
Adder
11.851
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.43
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.607
942111AE2-223 GEN
Solar/Wind Harmer
2.835
960611AF2-352 GEN
Solar/Wind Harmer
2.858
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.962
270031AE2-169
Solar/Wind Harmer
4.656
270599AE1-208 GEN
Solar/Wind Harmer
7.759
970291AG2-192 GEN
Solar/Wind Harmer
1.085
970291AG2-192 GEN
Solar/Wind Harmer
0.501
971613AH1-306 GEN
Solar/Wind Harmer
3.953
970241AG2-163 GEN
Solar/Wind Harmer
4.698
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.598
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.449
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
247621Y3-024
Adder
0.268
970621AG2-405 GEN
Solar/Wind Harmer
1.408
276916AD2-100_GEN
Solar/Wind Harmer
16.036
276911AD2-131_GEN
Solar/Wind Harmer
1.056
926881AC1-175 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.796
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.172
970885AG2-551 GEN
Solar/Wind Harmer
2.391
971587AH1-292 GEN
Solar/Wind Harmer
4.706
CBM West 2LTFEXP_CBM-W2->PJM
CBM
97.213
NYPJM->LTFIMP_NY
CLTF
2.987
LGEELTFEXP_LGEE->PJM
CLTF
4.166
WECLTFEXP_WEC->PJM
CLTF
4.975
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.28
AG2-052LTFEXP_AG2-052->PJM
LTF
0.313
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.612
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.183
MECLTFEXP_MEC->PJM
CLTF
18.423
SIGELTFEXP_SIGE->PJM
CLTF
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
11.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.355
TVALTFEXP_TVA->PJM
CLTF
4.573

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.76 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4887.22
MW Contribution:
4.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.509
24642205MAYFLWER
50/50
0.068
944961AF1-161 GEN
50/50
5.338
962601AG1-109 GEN
50/50
5.338
274772LINCOLN ;3U
50/50
16.29
971347AH1-153 GEN
Solar/Wind Harmer
6.994
270043AE2-236 GEN
Solar/Wind Harmer
8.579
270505AE1-170 C O1
Solar/Wind Harmer
13.603
945111AF1-176 GEN
Solar/Wind Harmer
10.436
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
56.263
274724RIVER EC ;11
Adder
31.767
274752CRETE EC ;2U
Adder
14.744
274753CRETE EC ;3U
Adder
14.744
274814UNIV PK N;0U
Adder
8.99
274807UNIV PK N;3U
Adder
8.97
274811UNIV PK N;7U
Adder
8.912
970707AG2-453 GEN
Solar/Wind Harmer
40.554
972259AH1-714 GEN
Adder
33.781
274803UNIV PARK;6U
Adder
10.322
274826FISK ;BP
Adder
19.382
274887GEN-1.85
Solar/Wind Harmer
0.321
276843GEN-1.7
Solar/Wind Harmer
0.399
276806AD2-047 C O1
Solar/Wind Harmer
6.993
972038AH1-567 GEN2
Adder
0.645
939351AE1-166 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
51.877
274729ELWOOD EC;1P
Adder
28.741
274730ELWOOD EC;6P
Adder
28.742
274734ELWOOD EC;8P
Adder
28.742
274736ELWOOD EC;9P
Adder
28.742
943121AE2-341 GEN
Solar/Wind Harmer
20.341
943591AF1-030 GEN
Solar/Wind Harmer
13.527
274682WAUKEGAN ;7U
Adder
30.726
274862TOP CROP ;2U
Solar/Wind Harmer
1.61
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
2.344
274879MINONK ;1U
Solar/Wind Harmer
0.489
946671AF1-331 GEN
Solar/Wind Harmer
1.245
274855GSG-6 ;RU
Solar/Wind Harmer
0.426
274850MENDOTA H;RU
Solar/Wind Harmer
0.136
965021AG1-366 GEN
Solar/Wind Harmer
3.887
959091AF2-200 GEN
Solar/Wind Harmer
23.171
970571AG2-364 GEN
Solar/Wind Harmer
22.813
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
15.096
274767LEE CO EC;8U
Adder
14.918
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.369
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.899
965931AG1-462 GEN
Solar/Wind Harmer
27.452
971087AG2-675 GEN
Solar/Wind Harmer
5.742
965091AG1-374 GEN
Solar/Wind Harmer
32.089
959611AF2-252 GEN
Solar/Wind Harmer
3.565
24344005CKG1
50/50
12.151
270144AC1-141 ST1_
50/50
3.981
24641605TWIN BRNCH
50/50
0.032
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
16.29
274776LINCOLN ;7U
50/50
16.29
274777LINCOLN ;8U
50/50
16.29
270102X2-052 ST
50/50
3
270100X2-052 CT1
50/50
2.772
270101X2-052 CT2
50/50
2.772
24643105BUCHANAN
50/50
0.023
247620Y3-023
50/50
0.894
274770LINCOLN ;1U
50/50
16.29
274771LINCOLN ;2U
50/50
16.29
970349AG2-230 GEN
Solar/Wind Harmer
20.983
965681AG1-436 GEN
Solar/Wind Harmer
16.258
965791AG1-447 GEN
Solar/Wind Harmer
11.923
961051AF2-396 GEN
Solar/Wind Harmer
25.67
961051AF2-396 GEN
Solar/Wind Harmer
17.113
274805UNIV PK N;1U
Adder
8.931
274808UNIV PK N;4U
Adder
8.873
274888KELLY CRK;1U
Solar/Wind Harmer
0.72
276776AD2-060 GEN
Solar/Wind Harmer
1.316
958011AF2-095 GEN
Solar/Wind Harmer
17.77
970941AG2-585 GEN
Solar/Wind Harmer
6.787
276897AD1-100 C
Solar/Wind Harmer
30.687
274674JOLIET 9 ;6U
Adder
26.949
276893AG1-478 C
Solar/Wind Harmer
0.813
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274695ROCKY RD ;2P
Adder
19.071
274693ROCKY RD ;1P
Adder
18.884
274697ROCKY RD ;3P
Adder
5.181
274696ROCKY RD ;4P
Adder
19.521
958481AF2-142 GEN
Solar/Wind Harmer
17.9
274683WAUKEGAN ;8U
Adder
35.976
274683WAUKEGAN ;8U
Adder
30.326
962691AG1-118 GEN
Solar/Wind Harmer
35.572
958491AF2-143 GEN
Solar/Wind Harmer
17.663
276901AD2-066 C O1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
23.171
971343AH1-151 GEN
Solar/Wind Harmer
23.171
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
4.159
972236AH1-702 GEN2
Adder
3.616
944541AF1-119 GEN
Solar/Wind Harmer
0.761
960971AF2-388 GEN
Solar/Wind Harmer
6.685
938861AE1-114 GEN
Solar/Wind Harmer
6.442
274764LEE CO EC;5U
Adder
15.132
274765LEE CO EC;6U
Adder
15.132
274762LEE CO EC;3U
Adder
15.096
274763LEE CO EC;4U
Adder
14.954
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.801
276645AC1-214 GEN1
Solar/Wind Harmer
0.437
24344105CKG2
50/50
15.609
270143AC1-141 CT2_
50/50
4.509
24639705ELKHART HY
50/50
0.301
970521AG2-332 GEN
50/50
21.375
24307105BERRINSP G
50/50
0.039
274773LINCOLN ;4U
50/50
16.29
274774LINCOLN ;5U
50/50
16.29
957891AF2-083 GEN
Solar/Wind Harmer
21.547
945111AF1-176 GEN
Solar/Wind Harmer
22.973
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
6.687
274723RIVER EC ;12
Adder
32.136
274751CRETE EC ;1U
Adder
14.744
274754CRETE EC ;4U
Adder
14.744
274812UNIV PK N;8U
Adder
8.912
274802UNIV PARK;5U
Adder
10.322
970373AG2-245 GEN
Solar/Wind Harmer
25.838
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.799
274674JOLIET 9 ;6U
Adder
26.949
274732ELWOOD EC;7P
Adder
28.742
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.698
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.939
274682WAUKEGAN ;7U
Adder
30.726
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
18.858
962781AG1-127 GEN
Solar/Wind Harmer
11.253
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
8.816
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
15.316
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.367
971997AH1-543 GEN
Solar/Wind Harmer
6.138
965011AG1-365 GEN
Solar/Wind Harmer
11.662
957471AF2-041 GEN
Solar/Wind Harmer
34.756
959081AF2-199 GEN
Solar/Wind Harmer
11.585
971067AG2-660 GEN
Solar/Wind Harmer
3.862
274822ROCKFORD ;11
Adder
32.468
970819AG2-516 GEN
Solar/Wind Harmer
13.763
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
14.32
970569AG2-363 GEN
Solar/Wind Harmer
34.22
965651AG1-433 GEN
Solar/Wind Harmer
3.342
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
15.096
274766LEE CO EC;7U
Adder
14.918
276708O09 GEN2
Solar/Wind Harmer
0.394
276646AC1-214 GEN2
Solar/Wind Harmer
0.437
958861AF2-177 GEN
Solar/Wind Harmer
4.817
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
15.28
945371AF1-202 GEN
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.491
963741AG1-226 GEN
Solar/Wind Harmer
23.192
270594AE1-207 GEN
Solar/Wind Harmer
10.875
270032AE2-172
Solar/Wind Harmer
6.473
270024AE2-089 GEN
Solar/Wind Harmer
0.002
965911AG1-460 GEN
Solar/Wind Harmer
1.883
276903AD2-071 C
Solar/Wind Harmer
10.45
270005AE1-210 C O1
Solar/Wind Harmer
2.023
970825AG2-519 GEN
Solar/Wind Harmer
3.238
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.152
24728605AND G2
Adder
4.25
965421AG1-410 GEN
Solar/Wind Harmer
22.891
246936BC-WTG1
Solar/Wind Harmer
0.29
270489AE1-102 GEN1
Solar/Wind Harmer
0.936
970773AG2-487 GEN
Solar/Wind Harmer
1.245
970091AG2-072 GEN
Adder
68.038
971771AH1-392 GEN
Solar/Wind Harmer
13.087
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
24.893
970031AG2-029 GEN
Solar/Wind Harmer
6.756
972037AH1-567 GEN1
Adder
0.324
274827FISK ;RP
Adder
13.736
960591AF2-350 GEN
Solar/Wind Harmer
12.34
274800UNIV PARK;3U
Adder
10.31
274801UNIV PARK;4U
Adder
10.31
972228AH1-698 GEN2
Adder
6.548
972227AH1-698 GEN1
Adder
4.611
274687WILL CNTY;4U
Adder
49.058
274687WILL CNTY;4U
Adder
49.058
24729505KEY G4
Adder
11.387
274675JOLIET 29;7U
Adder
53.8
274675JOLIET 29;7U
Adder
51.878
274728ELWOOD EC;5P
Adder
28.742
274731ELWOOD EC;2P
Adder
28.741
274733ELWOOD EC;3P
Adder
28.741
274735ELWOOD EC;4P
Adder
28.741
970833AG2-524 GEN
Solar/Wind Harmer
13.404
970833AG2-524 GEN
Solar/Wind Harmer
8.936
274744AC1-111 GEN8
Adder
9.698
274746AC1-111 G10
Adder
9.698
970073AG2-061 GEN
Solar/Wind Harmer
3.925
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
4.551
971411AH1-196 GEN
Solar/Wind Harmer
17.505
276861AD2-134 GEN
Solar/Wind Harmer
0.208
276863AD2-134 GEN
Solar/Wind Harmer
0.208
959331AF2-224 GEN
Solar/Wind Harmer
8.163
971549AH1-272 GEN
Solar/Wind Harmer
24.049
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
23.171
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
32.233
971611AH1-305 GEN
Solar/Wind Harmer
6.82
274856ECOGROVE ;U1
Solar/Wind Harmer
0.267
926823AC1-168 GEN
Solar/Wind Harmer
1.939
970169AG2-114 GEN
Solar/Wind Harmer
11.381
971681AH1-341 GEN
Solar/Wind Harmer
18.311
972267AH1-718 GEN
Adder
6.682
276741O09 GEN1
Solar/Wind Harmer
0.394
274877BISHOP HL;1U
Solar/Wind Harmer
0.369
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
11.46
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.067
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
14.314
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.381
965041AG1-368 GEN
Solar/Wind Harmer
10.029
276668AB2-070 GEN1
Solar/Wind Harmer
0.393
276848AB2-070 GEN3
Solar/Wind Harmer
0.392
276849AB2-070 GEN2
Solar/Wind Harmer
0.393
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.884
971609AH1-304 GEN
Solar/Wind Harmer
1.618
247521TR3_G114
Solar/Wind Harmer
0.333
965051AG1-369 GEN
Solar/Wind Harmer
4.586
944221AF1-090 GEN
Solar/Wind Harmer
5.276
964611AG1-324 GEN
Solar/Wind Harmer
3.501
247536S-71 GEN
Solar/Wind Harmer
0.329
270543AE2-219 C
Solar/Wind Harmer
5.36
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.912
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.541
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.004
971993AH1-541 GEN
Solar/Wind Harmer
4.623
970289AG2-191 GEN
Solar/Wind Harmer
1.091
957381AF2-032 GEN
Solar/Wind Harmer
2.142
942481AE2-261 GEN
Solar/Wind Harmer
28.148
270004AE1-209 GEN
Solar/Wind Harmer
2.023
970825AG2-519 GEN
Solar/Wind Harmer
6.871
946031AF1-268 GEN
Solar/Wind Harmer
8.578
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.45
24695305TIMB G C
Solar/Wind Harmer
0.754
970193AG2-126 GEN
Solar/Wind Harmer
13.114
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728705AND G3
Adder
8.888
24728505AND G1
Adder
4.25
246938BC-WTG3
Solar/Wind Harmer
0.259
270491AE1-102 GEN2
Solar/Wind Harmer
0.936
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
3.547
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
4.299
960611AF2-352 GEN
Solar/Wind Harmer
3.565
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.183
944231AF1-091 GEN
Solar/Wind Harmer
23.934
970291AG2-192 GEN
Solar/Wind Harmer
1.289
970291AG2-192 GEN
Solar/Wind Harmer
0.595
270031AE2-169
Solar/Wind Harmer
5.447
270599AE1-208 GEN
Solar/Wind Harmer
9.078
276615X2-022 GEN
Solar/Wind Harmer
0.102
276838X2-022 GEN2
Solar/Wind Harmer
0.552
970241AG2-163 GEN
Solar/Wind Harmer
5.716
971613AH1-306 GEN
Solar/Wind Harmer
4.661
276916AD2-100_GEN
Solar/Wind Harmer
19.57
276911AD2-131_GEN
Solar/Wind Harmer
1.289
270246TR4_N_V150
Solar/Wind Harmer
0.059
270247TR4_N_V136
Solar/Wind Harmer
0.059
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.673
270201AC2-176 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
9.289
247621Y3-024
Adder
0.295
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.411
970883AG2-550 GEN
Solar/Wind Harmer
7.657
970885AG2-551 GEN
Solar/Wind Harmer
2.552
971587AH1-292 GEN
Solar/Wind Harmer
5.454
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.29
270349AD2-093_GEN
Solar/Wind Helper
1.569
270471AD2-092_GEN
Solar/Wind Helper
1.569
CBM West 2LTFEXP_CBM-W2->PJM
CBM
110.466
NYPJM->LTFIMP_NY
CLTF
2.94
LGEELTFEXP_LGEE->PJM
CLTF
4.042
WECLTFEXP_WEC->PJM
CLTF
6.289
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.78
AG2-052LTFEXP_AG2-052->PJM
LTF
0.393
AH1-155LTFEXP_AH1-155->PJM
LTF
0.59
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.285
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.325
MECLTFEXP_MEC->PJM
CLTF
22.729
SIGELTFEXP_SIGE->PJM
CLTF
0.435
LAGNLTFEXP_LAGN->PJM
CLTF
12.231
TVALTFEXP_TVA->PJM
CLTF
4.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.4 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6428.58
MW Contribution:
4.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
16.719
962761AG1-125 GEN
Solar/Wind Harmer
46.005
970149AG2-104 GEN
Solar/Wind Harmer
24.844
970155AG2-107 GEN
Solar/Wind Harmer
29.378
971687AH1-348 GEN
Solar/Wind Harmer
1.062
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
19.107
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
11.165
252510AF1-249 C
Solar/Wind Harmer
0.075
25196008MFTGT1
Adder
1.98
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.854
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
4.631
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
27.062
270399AC1-101 GEN
Solar/Wind Harmer
3.79
270400AC1-102 GEN
Solar/Wind Harmer
3.79
970281AG2-184 GEN
Solar/Wind Harmer
22.827
971985AH1-537 GEN
Solar/Wind Harmer
3.231
941621AE2-160 GEN
Adder
5.034
971313AH1-133 GEN
Solar/Wind Harmer
5.062
972163AH1-664 GEN
Solar/Wind Harmer
11.291
972165AH1-665 GEN
Solar/Wind Harmer
9.043
339216AC1-074 GEN
Solar/Wind Harmer
0.266
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.728
270263AC1-001 GEN
Solar/Wind Harmer
0.978
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971061AG2-657 GEN
Solar/Wind Harmer
6.001
253372AE2-315 SEC3
Adder
2.57
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
962771AG1-126 GEN
Solar/Wind Harmer
46.005
970153AG2-106 GEN
Solar/Wind Harmer
29.378
971191AH1-055 GEN
Solar/Wind Harmer
29.882
972103AH1-617 GEN
Solar/Wind Harmer
21.74
960911AF2-382 GEN
Solar/Wind Harmer
7.999
971461AH1-227 GEN
Solar/Wind Harmer
5.44
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
7.453
972167AH1-666 GEN
Solar/Wind Harmer
8.106
252507AC2-088 GEN
Solar/Wind Harmer
0.453
958171AF2-111 GEN
Solar/Wind Harmer
25.009
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
8.38
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
12.81
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.77
970653AG2-424 GEN
Solar/Wind Harmer
0.96
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
14.237
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
8.358
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
2.038
970191AG2-125 GEN
Solar/Wind Harmer
2.419
970825AG2-519 GEN
Solar/Wind Harmer
7.074
946031AF1-268 GEN
Solar/Wind Harmer
8.922
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.325
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.91
942481AE2-261 GEN
Solar/Wind Harmer
27.692
957381AF2-032 GEN
Solar/Wind Harmer
2.099
971993AH1-541 GEN
Solar/Wind Harmer
4.271
943031AE2-326 GEN
Solar/Wind Harmer
4.803
965091AG1-374 GEN
Solar/Wind Harmer
27.602
959611AF2-252 GEN
Solar/Wind Harmer
3.067
944531AF1-118 GEN
Solar/Wind Harmer
41.107
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.304
970571AG2-364 GEN
Solar/Wind Harmer
18.217
253325AC1-069 GEN
Solar/Wind Harmer
0.01
276868AE1-113 GEN
Solar/Wind Harmer
1.82
274879MINONK ;1U
Solar/Wind Harmer
0.38
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.001
970707AG2-453 GEN
Solar/Wind Harmer
29.702
943121AE2-341 GEN
Solar/Wind Harmer
15.239
943591AF1-030 GEN
Solar/Wind Harmer
10.134
274862TOP CROP ;2U
Solar/Wind Harmer
1.227
972259AH1-714 GEN
Adder
24.853
274855GSG-6 ;RU
Solar/Wind Harmer
0.332
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
946671AF1-331 GEN
Solar/Wind Harmer
0.969
959091AF2-200 GEN
Solar/Wind Harmer
18.173
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
965931AG1-462 GEN
Solar/Wind Harmer
23.167
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
971087AG2-675 GEN
Solar/Wind Harmer
4.845
274682WAUKEGAN ;7U
Adder
7.239
274887GEN-1.85
Solar/Wind Harmer
0.236
276843GEN-1.7
Solar/Wind Harmer
0.294
276806AD2-047 C O1
Solar/Wind Harmer
5.144
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
970913AG2-568 GEN
Solar/Wind Harmer
8.731
971225AH1-072 GEN
Solar/Wind Harmer
2.121
971227AH1-073 GEN
Solar/Wind Harmer
2.121
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971073AG2-665 GEN
Solar/Wind Harmer
7.453
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.05
972043AH1-570 GEN
Solar/Wind Harmer
2.601
972045AH1-571 GEN
Solar/Wind Harmer
2.084
25183208HLCRTG
Solar/Wind Harmer
0.001
971125AH1-004 GEN
Solar/Wind Harmer
3.97
970107AG2-081 GEN
Solar/Wind Harmer
2.978
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
9.908
971587AH1-292 GEN
Solar/Wind Harmer
7.164
964571AG1-320 GEN
Solar/Wind Harmer
8.813
270269AC2-059
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
10.085
926881AC1-175 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.492
970291AG2-192 GEN
Solar/Wind Harmer
1.223
970291AG2-192 GEN
Solar/Wind Harmer
0.565
971613AH1-306 GEN
Solar/Wind Harmer
4.515
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.061
970883AG2-550 GEN
Solar/Wind Harmer
9.352
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971485AH1-239 GEN
Solar/Wind Harmer
7.452
964781AG1-341 GEN
Solar/Wind Harmer
9.873
966021AG1-471 GEN
Solar/Wind Harmer
5.029
270031AE2-169
Solar/Wind Harmer
5.121
270599AE1-208 GEN
Solar/Wind Harmer
8.535
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
19.462
276911AD2-131_GEN
Solar/Wind Harmer
1.282
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.431
276615X2-022 GEN
Solar/Wind Harmer
0.096
276838X2-022 GEN2
Solar/Wind Harmer
0.521
960611AF2-352 GEN
Solar/Wind Harmer
3.067
942111AE2-223 GEN
Solar/Wind Harmer
2.987
276645AC1-214 GEN1
Solar/Wind Harmer
0.358
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
22.743
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
1.788
963841AG1-237 GEN
Solar/Wind Harmer
4.07
971029AG2-637 GEN
Solar/Wind Harmer
14.087
24386405FR-21G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.546
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.372
971609AH1-304 GEN
Solar/Wind Harmer
1.521
964611AG1-324 GEN
Solar/Wind Harmer
3.625
270432AC2-029 GEN
Solar/Wind Harmer
4.119
944221AF1-090 GEN
Solar/Wind Harmer
5.449
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.362
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
971611AH1-305 GEN
Solar/Wind Harmer
5.499
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.649
966391AG1-508 GEN
Solar/Wind Harmer
1.42
970169AG2-114 GEN
Solar/Wind Harmer
9.156
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
0.996
274877BISHOP HL;1U
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
1.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
970073AG2-061 GEN
Solar/Wind Harmer
3.032
276741O09 GEN1
Solar/Wind Harmer
0.321
970833AG2-524 GEN
Solar/Wind Harmer
10.003
970833AG2-524 GEN
Solar/Wind Harmer
6.669
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
276861AD2-134 GEN
Solar/Wind Harmer
0.162
276863AD2-134 GEN
Solar/Wind Harmer
0.162
971675AH1-338 GEN
Solar/Wind Harmer
3.544
971171AH1-044 GEN
Solar/Wind Harmer
18.173
971681AH1-341 GEN
Solar/Wind Harmer
14.63
972267AH1-718 GEN
Adder
5.423
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
274823ROCKFORD ;21
Adder
25.367
971411AH1-196 GEN
Solar/Wind Harmer
13.626
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
960591AF2-350 GEN
Solar/Wind Harmer
9.078
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
970773AG2-487 GEN
Solar/Wind Harmer
1.693
270273AD2-016 GEN
Solar/Wind Harmer
0.98
24728605AND G2
Adder
5.248
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.957
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
10.535
963741AG1-226 GEN
Solar/Wind Harmer
22.28
964901AG1-354 GEN
Solar/Wind Harmer
14.121
270594AE1-207 GEN
Solar/Wind Harmer
10.536
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
2.038
970825AG2-519 GEN
Solar/Wind Harmer
3.334
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.02
965911AG1-460 GEN
Solar/Wind Harmer
1.852
965651AG1-433 GEN
Solar/Wind Harmer
2.715
276621W2-048 GEN
Solar/Wind Harmer
0.463
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.546
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.866
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.925
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.831
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.358
270055AF2-134 C O1
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
27.326
971997AH1-543 GEN
Solar/Wind Harmer
4.779
253333AC1-068 GEN
Solar/Wind Harmer
0.01
276882AE2-255 GEN
Solar/Wind Harmer
1.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
276805AD2-038 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.321
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.477
274861TOP CROP ;1U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.28
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
27.26
959081AF2-199 GEN
Solar/Wind Harmer
9.087
962781AG1-127 GEN
Solar/Wind Harmer
8.648
971067AG2-660 GEN
Solar/Wind Harmer
3.029
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
970819AG2-516 GEN
Solar/Wind Harmer
10.9
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
970373AG2-245 GEN
Solar/Wind Harmer
16.807
958491AF2-143 GEN
Solar/Wind Harmer
13.642
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.467
958481AF2-142 GEN
Solar/Wind Harmer
13.633
962691AG1-118 GEN
Solar/Wind Harmer
27.261
971341AH1-150 GEN
Solar/Wind Harmer
18.173
971343AH1-151 GEN
Solar/Wind Harmer
18.173
938861AE1-114 GEN
Solar/Wind Harmer
5.149
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
276893AG1-478 C
Solar/Wind Harmer
0.606
274674JOLIET 9 ;6U
Adder
20.046
942221AE2-234 GEN
Solar/Wind Harmer
3.648
274683WAUKEGAN ;8U
Adder
27.432
971277AH1-098 GEN
Solar/Wind Harmer
3.633
274888KELLY CRK;1U
Solar/Wind Harmer
0.529
276776AD2-060 GEN
Solar/Wind Harmer
0.968
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
CPLELTFEXP_CPLE->PJM
CLTF
6.482
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4976.63
MW Contribution:
3.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.475
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
24.531
270399AC1-101 GEN
Solar/Wind Harmer
3.431
270400AC1-102 GEN
Solar/Wind Harmer
3.431
941621AE2-160 GEN
Adder
4.685
970281AG2-184 GEN
Solar/Wind Harmer
20.069
971313AH1-133 GEN
Solar/Wind Harmer
4.633
971061AG2-657 GEN
Solar/Wind Harmer
5.63
24734705WLF1G3
Adder
7.275
24734805WLF1G4
Adder
7.275
24734905WLF1G5
Adder
7.275
971985AH1-537 GEN
Solar/Wind Harmer
2.606
24735105WLF2G1
Adder
7.131
966391AG1-508 GEN
Solar/Wind Harmer
1.323
971331AH1-145 GEN
Solar/Wind Harmer
10.902
971329AH1-144 GEN
Solar/Wind Harmer
4.007
971981AH1-535 GEN
Solar/Wind Harmer
5.247
972163AH1-664 GEN
Solar/Wind Harmer
8.578
972165AH1-665 GEN
Solar/Wind Harmer
6.87
3429211JKCT 2G
Adder
12.836
339216AC1-074 GEN
Solar/Wind Harmer
0.202
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.606
25196108MFTGT2
Adder
1.492
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
9.098
25196308WSDLE2
Adder
9.019
25196208WSDLE1
Adder
8.997
25196708WSDLE6
Adder
8.974
25196508WSDLE4
Adder
8.748
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.692
270069AE2-166 C O1
Solar/Wind Harmer
6.22
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.926
963841AG1-237 GEN
Solar/Wind Harmer
2.866
24386405FR-21G C
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.257
276848AB2-070 GEN3
Solar/Wind Harmer
0.256
276849AB2-070 GEN2
Solar/Wind Harmer
0.257
970289AG2-191 GEN
Solar/Wind Harmer
1.233
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.69
274854TWINGROVE;U2
Solar/Wind Harmer
0
25306009OHH W.
Adder
2.654
253372AE2-315 SEC3
Adder
1.743
253372AE2-315 SEC3
Adder
1.743
270543AE2-219 C
Solar/Wind Harmer
4.484
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.721
247536S-71 GEN
Solar/Wind Harmer
0.254
971611AH1-305 GEN
Solar/Wind Harmer
3.778
946321AF1-296 GEN
Solar/Wind Harmer
3.554
274877BISHOP HL;1U
Solar/Wind Harmer
0.211
971609AH1-304 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
2.468
970169AG2-114 GEN
Solar/Wind Harmer
6.325
276741O09 GEN1
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.763
926823AC1-168 GEN
Solar/Wind Harmer
1.07
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.116
274856ECOGROVE ;U1
Solar/Wind Harmer
0.147
274823ROCKFORD ;21
Adder
17.485
971171AH1-044 GEN
Solar/Wind Harmer
12.516
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971675AH1-338 GEN
Solar/Wind Harmer
2.437
971411AH1-196 GEN
Solar/Wind Harmer
9.369
970073AG2-061 GEN
Solar/Wind Harmer
2.078
274744AC1-111 GEN8
Adder
4.965
274746AC1-111 G10
Adder
4.965
970833AG2-524 GEN
Solar/Wind Harmer
6.809
970833AG2-524 GEN
Solar/Wind Harmer
4.54
274728ELWOOD EC;5P
Adder
14.558
274731ELWOOD EC;2P
Adder
14.558
274733ELWOOD EC;3P
Adder
14.558
274735ELWOOD EC;4P
Adder
14.558
274675JOLIET 29;7U
Adder
27.142
960591AF2-350 GEN
Solar/Wind Harmer
6.155
23750501ELLIOTTS
Solar/Wind Helper
0.598
23652301WDPWR_K20
Solar/Wind Helper
0.127
24289405MTG1
50/50
10.896
243186AF1-051 GEN
50/50
11.683
24318705GVG2
50/50
10.829
24721805FLATG3
50/50
2.475
24723205RIVRG3
Adder
32.69
972203AH1-686 GEN
Adder
3.965
24686505CER G6
Adder
14.074
944971AF1-162 GEN
Solar/Wind Harmer
10.992
971403AH1-188 GEN
Solar/Wind Harmer
15.251
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
6.196
971687AH1-348 GEN
Solar/Wind Harmer
0.943
24735205WLF2G2
Adder
7.131
971073AG2-665 GEN
Solar/Wind Harmer
1.329
970091AG2-072 GEN
Adder
86.562
945681AF1-233 GEN
Solar/Wind Harmer
14.491
3429241JKCT 3G
Adder
13.004
3429421JKCT 10G
Adder
9.095
970653AG2-424 GEN
Solar/Wind Harmer
3.596
964901AG1-354 GEN
Solar/Wind Harmer
11.126
25196808ZIMRHP
Adder
79.991
25196008MFTGT1
Adder
1.457
252516AE2-318_GEN
Solar/Wind Harmer
8.161
252510AF1-249 C
Solar/Wind Harmer
0.055
25194608D.CRK4
Adder
1.702
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.045
962761AG1-125 GEN
Solar/Wind Harmer
27.311
970149AG2-104 GEN
Solar/Wind Harmer
14.748
970155AG2-107 GEN
Solar/Wind Harmer
17.44
253398AE2-221_GEN2
Solar/Wind Harmer
0
24728605AND G2
Adder
3.745
970773AG2-487 GEN
Solar/Wind Harmer
1.199
963741AG1-226 GEN
Solar/Wind Harmer
15.765
965911AG1-460 GEN
Solar/Wind Harmer
1.325
943811AF1-049 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.832
276621W2-048 GEN
Solar/Wind Harmer
0.329
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.31
270594AE1-207 GEN
Solar/Wind Harmer
7.264
270032AE2-172
Solar/Wind Harmer
4.324
270273AD2-016 GEN
Solar/Wind Harmer
0.662
270005AE1-210 C O1
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
2.292
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.961
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.933
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.248
276708O09 GEN2
Solar/Wind Harmer
0.223
970569AG2-363 GEN
Solar/Wind Harmer
18.869
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.386
274766LEE CO EC;7U
Adder
8.287
25326309TAIT D
Adder
0.988
945371AF1-202 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
7.523
939401AE1-172 GEN
Solar/Wind Harmer
4.684
274822ROCKFORD ;11
Adder
17.613
957471AF2-041 GEN
Solar/Wind Harmer
18.774
959081AF2-199 GEN
Solar/Wind Harmer
6.258
971067AG2-660 GEN
Solar/Wind Harmer
2.086
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.135
971997AH1-543 GEN
Solar/Wind Harmer
3.283
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.729
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.929
274828WAUKEGAN ;BP
Adder
9.84
274682WAUKEGAN ;7U
Adder
16.004
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.692
276691AA1-018 GEN1
Solar/Wind Harmer
1.009
274745AC1-111 GEN9
Adder
4.965
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.558
274674JOLIET 9 ;6U
Adder
13.632
965651AG1-433 GEN
Solar/Wind Harmer
1.811
274676JOLIET 29;8U
Adder
9.572
238185AF2-356 C
Solar/Wind Helper
1.975
970373AG2-245 GEN
Solar/Wind Harmer
5.443
24289405MTG1
50/50
10.896
24318705GVG2
50/50
10.829
24722005FLATG5
50/50
2.475
24721905FLATG4
50/50
45.211
24686405CER G5
Adder
13.963
971191AH1-055 GEN
Solar/Wind Harmer
25.524
960911AF2-382 GEN
Solar/Wind Harmer
7.256
972103AH1-617 GEN
Solar/Wind Harmer
19.113
971461AH1-227 GEN
Solar/Wind Harmer
4.836
270346AE1-212 GEN
Solar/Wind Harmer
7.826
943031AE2-326 GEN
Solar/Wind Harmer
4.478
970879AG2-548 GEN
Solar/Wind Harmer
5.846
958121AF2-106 GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
6.527
972167AH1-666 GEN
Solar/Wind Harmer
6.143
972273AH1-721 GEN
Adder
91.222
3429391JKCT 9G
Adder
9.095
970455AG2-298 GEN
Solar/Wind Harmer
2.913
958171AF2-111 GEN
Solar/Wind Harmer
18.695
252507AC2-088 GEN
Solar/Wind Harmer
0.336
970653AG2-424 GEN
Solar/Wind Harmer
0.745
25196008MFTGT1
Adder
1.411
252519AF1-045_GEN
Solar/Wind Harmer
3.801
25194608D.CRK4
Adder
1.702
25196608WSDLE5
Adder
8.838
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.158
962771AG1-126 GEN
Solar/Wind Harmer
27.311
970153AG2-106 GEN
Solar/Wind Harmer
17.44
253394AE2-221_GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.239
24728705AND G3
Adder
7.833
24728505AND G1
Adder
3.745
270030AE2-140 GEN
Solar/Wind Harmer
13.518
942481AE2-261 GEN
Solar/Wind Harmer
19.808
957381AF2-032 GEN
Solar/Wind Harmer
1.5
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.022
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.714
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.48
270004AE1-209 GEN
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
4.865
965091AG1-374 GEN
Solar/Wind Harmer
19.301
946031AF1-268 GEN
Solar/Wind Harmer
6.123
959611AF2-252 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
970191AG2-125 GEN
Solar/Wind Harmer
1.638
965931AG1-462 GEN
Solar/Wind Harmer
16.203
971087AG2-675 GEN
Solar/Wind Harmer
3.389
274878BISHOP HL;2U
Solar/Wind Harmer
0.211
276782AC1-033 GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.45
970571AG2-364 GEN
Solar/Wind Harmer
12.579
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.386
274767LEE CO EC;8U
Adder
8.287
959091AF2-200 GEN
Solar/Wind Harmer
12.516
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
946671AF1-331 GEN
Solar/Wind Harmer
0.666
276868AE1-113 GEN
Solar/Wind Harmer
1.25
274879MINONK ;1U
Solar/Wind Harmer
0.261
274682WAUKEGAN ;7U
Adder
16.004
274862TOP CROP ;2U
Solar/Wind Harmer
0.839
943121AE2-341 GEN
Solar/Wind Harmer
10.39
943591AF1-030 GEN
Solar/Wind Harmer
6.91
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
14.558
274730ELWOOD EC;6P
Adder
14.558
274734ELWOOD EC;8P
Adder
14.558
274736ELWOOD EC;9P
Adder
14.558
970707AG2-453 GEN
Solar/Wind Harmer
20.15
274887GEN-1.85
Solar/Wind Harmer
0.16
276843GEN-1.7
Solar/Wind Harmer
0.199
276806AD2-047 C O1
Solar/Wind Harmer
3.488
237048AF1-022 C
Solar/Wind Helper
0.175
237046AF1-021 C
Solar/Wind Helper
0.301
235058AG1-386 C
Solar/Wind Helper
0.387
23562501BACKB
Solar/Wind Helper
0.811
243186AF1-051 GEN
50/50
11.683
24721705FLATG2
50/50
36.759
24723005RIVRG1
Adder
32.69
24723105RIVRG2
Adder
32.69
970913AG2-568 GEN
Solar/Wind Harmer
8.105
24728205BUCHG1
Adder
6.196
971225AH1-072 GEN
Solar/Wind Harmer
1.885
971227AH1-073 GEN
Solar/Wind Harmer
1.885
971277AH1-098 GEN
Solar/Wind Harmer
3.388
971073AG2-665 GEN
Solar/Wind Harmer
5.846
970879AG2-548 GEN
Solar/Wind Harmer
1.329
270583AD2-179 GEN
Solar/Wind Harmer
7.872
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942891AE2-308 GEN
Solar/Wind Harmer
7.677
972043AH1-570 GEN
Solar/Wind Harmer
1.99
972045AH1-571 GEN
Solar/Wind Harmer
1.594
971125AH1-004 GEN
Solar/Wind Harmer
3.042
970107AG2-081 GEN
Solar/Wind Harmer
2.281
966021AG1-471 GEN
Solar/Wind Harmer
4.034
252509AD1-136 GEN
Solar/Wind Harmer
0.037
971485AH1-239 GEN
Solar/Wind Harmer
5.968
964571AG1-320 GEN
Solar/Wind Harmer
6.787
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25183208HLCRTG
Solar/Wind Harmer
0
971587AH1-292 GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
7.827
25194508D.CRK3
Adder
1.463
945391AF1-204 GEN
Solar/Wind Harmer
7.253
24728805RICHG1
Adder
3.656
24728905RICHG2
Adder
3.656
970241AG2-163 GEN
Solar/Wind Harmer
3.886
276916AD2-100_GEN
Solar/Wind Harmer
13.944
276911AD2-131_GEN
Solar/Wind Harmer
0.919
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.068
276838X2-022 GEN2
Solar/Wind Harmer
0.37
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.743
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.844
970291AG2-192 GEN
Solar/Wind Harmer
0.389
971613AH1-306 GEN
Solar/Wind Harmer
3.113
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
970883AG2-550 GEN
Solar/Wind Harmer
6.406
970885AG2-551 GEN
Solar/Wind Harmer
2.135
942111AE2-223 GEN
Solar/Wind Harmer
2.08
270031AE2-169
Solar/Wind Harmer
3.483
270599AE1-208 GEN
Solar/Wind Harmer
5.804
276645AC1-214 GEN1
Solar/Wind Harmer
0.248
964611AG1-324 GEN
Solar/Wind Harmer
0.475
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.019
247621Y3-024
Adder
0.218
270201AC2-176 GEN
Solar/Wind Harmer
0
25322209TAIT E
Adder
8.794
25322209TAIT E
Adder
8.596
274764LEE CO EC;5U
Adder
8.405
274765LEE CO EC;6U
Adder
8.405
274762LEE CO EC;3U
Adder
8.386
274763LEE CO EC;4U
Adder
8.307
938861AE1-114 GEN
Solar/Wind Harmer
3.56
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.263
972236AH1-702 GEN2
Adder
1.968
971341AH1-150 GEN
Solar/Wind Harmer
12.516
971343AH1-151 GEN
Solar/Wind Harmer
12.516
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.353
962691AG1-118 GEN
Solar/Wind Harmer
18.68
274683WAUKEGAN ;8U
Adder
18.772
274683WAUKEGAN ;8U
Adder
15.824
274696ROCKY RD ;4P
Adder
10.15
274695ROCKY RD ;2P
Adder
9.916
274693ROCKY RD ;1P
Adder
9.818
274697ROCKY RD ;3P
Adder
2.694
958481AF2-142 GEN
Solar/Wind Harmer
9.318
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
15.453
276893AG1-478 C
Solar/Wind Harmer
0.412
274674JOLIET 9 ;6U
Adder
13.632
944541AF1-119 GEN
Solar/Wind Harmer
0.412
960971AF2-388 GEN
Solar/Wind Harmer
3.621
274888KELLY CRK;1U
Solar/Wind Harmer
0.359
276776AD2-060 GEN
Solar/Wind Harmer
0.657
958011AF2-095 GEN
Solar/Wind Harmer
8.864
970941AG2-585 GEN
Solar/Wind Harmer
3.385
23585401KL_K28_T16
Solar/Wind Helper
1.157
237043AE2-125 C
Solar/Wind Helper
0.157
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.531
CPLELTFEXP_CPLE->PJM
CLTF
6.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.098
NYPJM->LTFIMP_NY
CLTF
4.626
LGEELTFEXP_LGEE->PJM
CLTF
7.468
WECLTFEXP_WEC->PJM
CLTF
3.435
AG2-052LTFEXP_AG2-052->PJM
LTF
0.207
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
115.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.783
MECLTFEXP_MEC->PJM
CLTF
15.666
SIGELTFEXP_SIGE->PJM
CLTF
0.545
LAGNLTFEXP_LAGN->PJM
CLTF
19.698
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23
TVALTFEXP_TVA->PJM
CLTF
10.208

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.76 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5896.19
MW Contribution:
3.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
18.148
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.157
24735205WLF2G2
Adder
8.97
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
3429241JKCT 3G
Adder
15.659
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
17.283
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
964901AG1-354 GEN
Solar/Wind Harmer
13.534
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
960911AF2-382 GEN
Solar/Wind Harmer
8.992
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
5.939
972103AH1-617 GEN
Solar/Wind Harmer
23.135
971191AH1-055 GEN
Solar/Wind Harmer
29.317
270346AE1-212 GEN
Solar/Wind Harmer
10.045
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
6.854
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
18.672
970093AG2-073 GEN
Solar/Wind Harmer
7.87
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
8.058
970455AG2-298 GEN
Solar/Wind Harmer
3.516
970653AG2-424 GEN
Solar/Wind Harmer
0.902
958171AF2-111 GEN
Solar/Wind Harmer
22.344
252507AC2-088 GEN
Solar/Wind Harmer
0.399
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
25196608WSDLE5
Adder
10.55
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
10.955
970193AG2-126 GEN
Solar/Wind Harmer
12.34
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
0
962771AG1-126 GEN
Solar/Wind Harmer
32.057
970153AG2-106 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.122
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.901
942481AE2-261 GEN
Solar/Wind Harmer
24.006
957381AF2-032 GEN
Solar/Wind Harmer
1.818
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.664
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.862
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.832
270004AE1-209 GEN
Solar/Wind Harmer
1.692
965091AG1-374 GEN
Solar/Wind Harmer
23.422
959611AF2-252 GEN
Solar/Wind Harmer
2.602
970825AG2-519 GEN
Solar/Wind Harmer
5.878
946031AF1-268 GEN
Solar/Wind Harmer
7.4
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
965931AG1-462 GEN
Solar/Wind Harmer
19.72
971087AG2-675 GEN
Solar/Wind Harmer
4.124
3147123OTTER R
Solar/Wind Harmer
0.087
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.257
970191AG2-125 GEN
Solar/Wind Harmer
1.979
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
970571AG2-364 GEN
Solar/Wind Harmer
15.299
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.443
959091AF2-200 GEN
Solar/Wind Harmer
15.232
274855GSG-6 ;RU
Solar/Wind Harmer
0.277
274850MENDOTA H;RU
Solar/Wind Harmer
0.088
946671AF1-331 GEN
Solar/Wind Harmer
0.811
276868AE1-113 GEN
Solar/Wind Harmer
1.52
274879MINONK ;1U
Solar/Wind Harmer
0.317
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
19.478
274862TOP CROP ;2U
Solar/Wind Harmer
1.021
943121AE2-341 GEN
Solar/Wind Harmer
12.644
943591AF1-030 GEN
Solar/Wind Harmer
8.409
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
970707AG2-453 GEN
Solar/Wind Harmer
24.521
274887GEN-1.85
Solar/Wind Harmer
0.195
276843GEN-1.7
Solar/Wind Harmer
0.242
276806AD2-047 C O1
Solar/Wind Harmer
4.245
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
28.948
270399AC1-101 GEN
Solar/Wind Harmer
4.065
270400AC1-102 GEN
Solar/Wind Harmer
4.065
971313AH1-133 GEN
Solar/Wind Harmer
5.869
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
1.796
970281AG2-184 GEN
Solar/Wind Harmer
24.292
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
5.625
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
6.84
971985AH1-537 GEN
Solar/Wind Harmer
3.035
971981AH1-535 GEN
Solar/Wind Harmer
6.584
270069AE2-166 C O1
Solar/Wind Harmer
8.709
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
10.231
972165AH1-665 GEN
Solar/Wind Harmer
8.194
339216AC1-074 GEN
Solar/Wind Harmer
0.242
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253406AD2-031_GEN
Solar/Wind Harmer
0.618
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.825
270197AD1-017 GEN1
Solar/Wind Harmer
1.008
270356AE2-297 GEN
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.756
963841AG1-237 GEN
Solar/Wind Harmer
3.459
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.489
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.702
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.158
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
270543AE2-219 C
Solar/Wind Harmer
5.421
946321AF1-296 GEN
Solar/Wind Harmer
4.325
274877BISHOP HL;1U
Solar/Wind Harmer
0.257
247536S-71 GEN
Solar/Wind Harmer
0.307
971611AH1-305 GEN
Solar/Wind Harmer
4.575
970169AG2-114 GEN
Solar/Wind Harmer
7.684
276741O09 GEN1
Solar/Wind Harmer
0.271
972267AH1-718 GEN
Adder
4.579
971609AH1-304 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
2.987
926823AC1-168 GEN
Solar/Wind Harmer
1.302
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
12.311
274856ECOGROVE ;U1
Solar/Wind Harmer
0.178
274823ROCKFORD ;21
Adder
21.28
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.232
945581AF1-223 GEN
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.136
276863AD2-134 GEN
Solar/Wind Harmer
0.136
971675AH1-338 GEN
Solar/Wind Harmer
2.966
971411AH1-196 GEN
Solar/Wind Harmer
11.402
970073AG2-061 GEN
Solar/Wind Harmer
2.528
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
970833AG2-524 GEN
Solar/Wind Harmer
8.285
970833AG2-524 GEN
Solar/Wind Harmer
5.523
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
960591AF2-350 GEN
Solar/Wind Harmer
7.491
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
9.827
24728205BUCHG1
Adder
7.739
971225AH1-072 GEN
Solar/Wind Harmer
2.315
971227AH1-073 GEN
Solar/Wind Harmer
2.315
971277AH1-098 GEN
Solar/Wind Harmer
4.618
270583AD2-179 GEN
Solar/Wind Harmer
11.364
971073AG2-665 GEN
Solar/Wind Harmer
6.854
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
9.244
972043AH1-570 GEN
Solar/Wind Harmer
2.384
972045AH1-571 GEN
Solar/Wind Harmer
1.91
971125AH1-004 GEN
Solar/Wind Harmer
3.655
970107AG2-081 GEN
Solar/Wind Harmer
2.741
966021AG1-471 GEN
Solar/Wind Harmer
4.933
971485AH1-239 GEN
Solar/Wind Harmer
7.296
962581AG1-107 GEN
Solar/Wind Harmer
0.002
964781AG1-341 GEN
Solar/Wind Harmer
9.518
964571AG1-320 GEN
Solar/Wind Harmer
8.194
252509AD1-136 GEN
Solar/Wind Harmer
0.044
25183208HLCRTG
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.363
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
8.741
942671AE2-283 GEN
Solar/Wind Harmer
3.812
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
276916AD2-100_GEN
Solar/Wind Harmer
16.897
276911AD2-131_GEN
Solar/Wind Harmer
1.113
970241AG2-163 GEN
Solar/Wind Harmer
4.689
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.448
926881AC1-175 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.897
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
1.019
970291AG2-192 GEN
Solar/Wind Harmer
0.47
971613AH1-306 GEN
Solar/Wind Harmer
3.76
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.602
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
2.525
253370AE2-315 SEC1
Adder
2.225
970883AG2-550 GEN
Solar/Wind Harmer
7.744
970885AG2-551 GEN
Solar/Wind Harmer
2.581
276645AC1-214 GEN1
Solar/Wind Harmer
0.302
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.239
270031AE2-169
Solar/Wind Harmer
4.216
270599AE1-208 GEN
Solar/Wind Harmer
7.027
964611AG1-324 GEN
Solar/Wind Harmer
0.575
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
938861AE1-114 GEN
Solar/Wind Harmer
4.333
247621Y3-024
Adder
0.264
270201AC2-176 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
15.232
971343AH1-151 GEN
Solar/Wind Harmer
15.232
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.378
962691AG1-118 GEN
Solar/Wind Harmer
22.733
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
958481AF2-142 GEN
Solar/Wind Harmer
11.337
276897AD1-100 C
Solar/Wind Harmer
18.8
276893AG1-478 C
Solar/Wind Harmer
0.501
274674JOLIET 9 ;6U
Adder
16.589
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.437
276776AD2-060 GEN
Solar/Wind Harmer
0.799
958011AF2-095 GEN
Solar/Wind Harmer
10.787
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
970941AG2-585 GEN
Solar/Wind Harmer
2.017
970653AG2-424 GEN
Solar/Wind Harmer
4.351
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
9.728
252510AF1-249 C
Solar/Wind Harmer
0.065
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.427
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
32.057
970149AG2-104 GEN
Solar/Wind Harmer
17.311
970155AG2-107 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.031
970773AG2-487 GEN
Solar/Wind Harmer
1.442
963741AG1-226 GEN
Solar/Wind Harmer
19.023
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
0.398
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.825
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.823
270594AE1-207 GEN
Solar/Wind Harmer
8.772
270032AE2-172
Solar/Wind Harmer
5.222
270005AE1-210 C O1
Solar/Wind Harmer
1.692
970825AG2-519 GEN
Solar/Wind Harmer
2.77
270273AD2-016 GEN
Solar/Wind Harmer
0.795
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
10.877
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.302
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.607
276708O09 GEN2
Solar/Wind Harmer
0.271
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
970569AG2-363 GEN
Solar/Wind Harmer
22.948
970819AG2-516 GEN
Solar/Wind Harmer
9.157
274822ROCKFORD ;11
Adder
21.436
957471AF2-041 GEN
Solar/Wind Harmer
22.848
959081AF2-199 GEN
Solar/Wind Harmer
7.616
971067AG2-660 GEN
Solar/Wind Harmer
2.539
945371AF1-202 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.694
971997AH1-543 GEN
Solar/Wind Harmer
3.993
25326309TAIT D
Adder
1.195
276882AE2-255 GEN
Solar/Wind Harmer
0.887
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.865
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.216
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.228
274745AC1-111 GEN9
Adder
6.042
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
3.264
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
270055AF2-134 C O1
Solar/Wind Harmer
0
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
CPLELTFEXP_CPLE->PJM
CLTF
7.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.25 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2283.58
MW Contribution:
2.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727105RPMNG2
50/50
3.318
970583AG2-370 GEN
50/50
2.814
270142AC1-141 CT1_
50/50
2.029
24642205MAYFLWER
50/50
0.031
944961AF1-161 GEN
50/50
2.395
962601AG1-109 GEN
50/50
2.395
965021AG1-366 GEN
Solar/Wind Harmer
4.607
270043AE2-236 GEN
Solar/Wind Harmer
5.241
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.981
24695305TIMB G C
Solar/Wind Harmer
0.532
945111AF1-176 GEN
Solar/Wind Harmer
4.853
971347AH1-153 GEN
Solar/Wind Harmer
2.927
270505AE1-170 C O1
Solar/Wind Harmer
6.132
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.345
274752CRETE EC ;2U
Adder
6.312
274753CRETE EC ;3U
Adder
6.312
274724RIVER EC ;11
Adder
13.515
274814UNIV PK N;0U
Adder
3.826
274807UNIV PK N;3U
Adder
3.817
274811UNIV PK N;7U
Adder
3.792
274772LINCOLN ;3U
Adder
6.365
274803UNIV PARK;6U
Adder
4.369
274826FISK ;BP
Adder
8.195
972038AH1-567 GEN2
Adder
0.273
274887GEN-1.85
Solar/Wind Harmer
0.135
276843GEN-1.7
Solar/Wind Harmer
0.168
276806AD2-047 C O1
Solar/Wind Harmer
2.951
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.153
970707AG2-453 GEN
Solar/Wind Harmer
16.903
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.852
274729ELWOOD EC;1P
Adder
12.11
274730ELWOOD EC;6P
Adder
12.11
274734ELWOOD EC;8P
Adder
12.11
274736ELWOOD EC;9P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.564
946031AF1-268 GEN
Solar/Wind Harmer
4.838
943121AE2-341 GEN
Solar/Wind Harmer
8.518
943591AF1-030 GEN
Solar/Wind Harmer
5.665
270004AE1-209 GEN
Solar/Wind Harmer
1.101
274862TOP CROP ;2U
Solar/Wind Harmer
0.681
970825AG2-519 GEN
Solar/Wind Harmer
3.795
274682WAUKEGAN ;7U
Adder
12.933
276868AE1-113 GEN
Solar/Wind Harmer
0.991
274879MINONK ;1U
Solar/Wind Harmer
0.207
946671AF1-331 GEN
Solar/Wind Harmer
0.524
274855GSG-6 ;RU
Solar/Wind Harmer
0.179
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.895
959091AF2-200 GEN
Solar/Wind Harmer
9.768
970571AG2-364 GEN
Solar/Wind Harmer
9.675
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.381
274767LEE CO EC;8U
Adder
6.306
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.157
965091AG1-374 GEN
Solar/Wind Harmer
13.726
965931AG1-462 GEN
Solar/Wind Harmer
11.666
971087AG2-675 GEN
Solar/Wind Harmer
2.44
959611AF2-252 GEN
Solar/Wind Harmer
1.525
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.998
957381AF2-032 GEN
Solar/Wind Harmer
0.932
942481AE2-261 GEN
Solar/Wind Harmer
12.255
970193AG2-126 GEN
Solar/Wind Harmer
5.956
24728705AND G3
Adder
4.39
24728505AND G1
Adder
2.099
246938BC-WTG3
Solar/Wind Helper
11.083
942871AE2-306 GEN
Solar/Wind Helper
0.445
270284AF1-227 GEN1
Solar/Wind Helper
1.893
270287AF1-227 GEN3
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.334
270541AE2-072 C
Solar/Wind Helper
0.943
24727205RPMNG3
50/50
3.298
24729505KEY G4
50/50
6.847
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.792
959331AF2-224 GEN
Solar/Wind Harmer
9.676
963791AG1-232 GEN
Solar/Wind Harmer
12.035
970031AG2-029 GEN
Solar/Wind Harmer
4.587
965041AG1-368 GEN
Solar/Wind Harmer
8.443
270071AF1-092 GEN
Solar/Wind Harmer
14.566
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.602
971771AH1-392 GEN
Solar/Wind Harmer
5.907
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.922
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.13
274775LINCOLN ;6U
Adder
6.365
274776LINCOLN ;7U
Adder
6.365
274777LINCOLN ;8U
Adder
6.365
972037AH1-567 GEN1
Adder
0.137
274827FISK ;RP
Adder
5.808
274800UNIV PARK;3U
Adder
4.357
274801UNIV PARK;4U
Adder
4.357
960591AF2-350 GEN
Solar/Wind Harmer
5.207
972228AH1-698 GEN2
Adder
2.756
972227AH1-698 GEN1
Adder
1.941
274687WILL CNTY;4U
Adder
20.685
274687WILL CNTY;4U
Adder
20.685
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.662
274675JOLIET 29;7U
Adder
21.853
274728ELWOOD EC;5P
Adder
12.11
274731ELWOOD EC;2P
Adder
12.11
274733ELWOOD EC;3P
Adder
12.11
274735ELWOOD EC;4P
Adder
12.11
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.974
970833AG2-524 GEN
Solar/Wind Harmer
5.628
970833AG2-524 GEN
Solar/Wind Harmer
3.752
971611AH1-305 GEN
Solar/Wind Harmer
3.031
274744AC1-111 GEN8
Adder
4.068
274746AC1-111 G10
Adder
4.068
970073AG2-061 GEN
Solar/Wind Harmer
1.661
247536S-71 GEN
Solar/Wind Harmer
0.199
971411AH1-196 GEN
Solar/Wind Harmer
7.376
971675AH1-338 GEN
Solar/Wind Harmer
1.916
276861AD2-134 GEN
Solar/Wind Harmer
0.088
276863AD2-134 GEN
Solar/Wind Harmer
0.088
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.768
274823ROCKFORD ;21
Adder
13.596
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
926823AC1-168 GEN
Solar/Wind Harmer
0.821
970169AG2-114 GEN
Solar/Wind Harmer
4.823
971681AH1-341 GEN
Solar/Wind Harmer
7.736
971549AH1-272 GEN
Solar/Wind Harmer
9.898
972267AH1-718 GEN
Adder
2.828
276741O09 GEN1
Solar/Wind Harmer
0.167
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.157
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.889
946321AF1-296 GEN
Solar/Wind Harmer
2.577
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.976
270543AE2-219 C
Solar/Wind Harmer
3.137
276668AB2-070 GEN1
Solar/Wind Harmer
0.17
276848AB2-070 GEN3
Solar/Wind Harmer
0.169
276849AB2-070 GEN2
Solar/Wind Harmer
0.17
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.928
944221AF1-090 GEN
Solar/Wind Harmer
2.312
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.609
270223U2-072_GEN1
Solar/Wind Helper
0.876
270224U2-072_GEN2
Solar/Wind Helper
0.876
270227U2-072_GEN3
Solar/Wind Helper
0.876
270228U2-072_GEN4
Solar/Wind Helper
0.876
270231U2-072_GEN5
Solar/Wind Helper
0.876
966831AG1-554 GEN
Solar/Wind Helper
0.882
270499AE1-146 GEN
Solar/Wind Helper
1.968
945641AF1-229 GEN
Solar/Wind Helper
0.94
24729405KEY G3
50/50
0.374
24729305KEY G2
50/50
0.367
24729205KEY G1
50/50
0.366
247620Y3-023
50/50
0.467
960851AF2-376 GEN
50/50
2.095
24643105BUCHANAN
50/50
0.01
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.855
944231AF1-091 GEN
Solar/Wind Harmer
16.139
944541AF1-119 GEN
Solar/Wind Harmer
0.427
960971AF2-388 GEN
Solar/Wind Harmer
3.752
970349AG2-230 GEN
Solar/Wind Harmer
8.78
961051AF2-396 GEN
Solar/Wind Harmer
11.674
961051AF2-396 GEN
Solar/Wind Harmer
7.782
270031AE2-169
Solar/Wind Harmer
3.104
270599AE1-208 GEN
Solar/Wind Harmer
5.173
965681AG1-436 GEN
Solar/Wind Harmer
6.963
965791AG1-447 GEN
Solar/Wind Harmer
5.106
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.41
247621Y3-024
Adder
0.183
274805UNIV PK N;1U
Adder
3.801
274808UNIV PK N;4U
Adder
3.776
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.365
274771LINCOLN ;2U
Adder
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
0.304
276776AD2-060 GEN
Solar/Wind Harmer
0.555
958011AF2-095 GEN
Solar/Wind Harmer
7.498
970941AG2-585 GEN
Solar/Wind Harmer
2.864
276897AD1-100 C
Solar/Wind Harmer
12.887
274674JOLIET 9 ;6U
Adder
11.348
276893AG1-478 C
Solar/Wind Harmer
0.343
970291AG2-192 GEN
Solar/Wind Harmer
0.666
970291AG2-192 GEN
Solar/Wind Harmer
0.308
971613AH1-306 GEN
Solar/Wind Harmer
2.442
958481AF2-142 GEN
Solar/Wind Harmer
7.57
274695ROCKY RD ;2P
Adder
8.016
274693ROCKY RD ;1P
Adder
7.937
274697ROCKY RD ;3P
Adder
2.178
274696ROCKY RD ;4P
Adder
8.205
274683WAUKEGAN ;8U
Adder
15.145
274683WAUKEGAN ;8U
Adder
12.766
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
14.951
958491AF2-143 GEN
Solar/Wind Harmer
7.476
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.768
971343AH1-151 GEN
Solar/Wind Harmer
9.768
972235AH1-702 GEN1
Adder
1.755
972236AH1-702 GEN2
Adder
1.526
938861AE1-114 GEN
Solar/Wind Harmer
2.722
274764LEE CO EC;5U
Adder
6.396
274765LEE CO EC;6U
Adder
6.396
274762LEE CO EC;3U
Adder
6.381
274763LEE CO EC;4U
Adder
6.321
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.763
276645AC1-214 GEN1
Solar/Wind Harmer
0.185
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.533
942111AE2-223 GEN
Solar/Wind Harmer
1.513
960611AF2-352 GEN
Solar/Wind Harmer
1.525
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.481
970885AG2-551 GEN
Solar/Wind Harmer
1.494
970241AG2-163 GEN
Solar/Wind Harmer
2.581
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.044
276838X2-022 GEN2
Solar/Wind Harmer
0.239
276916AD2-100_GEN
Solar/Wind Harmer
8.532
276911AD2-131_GEN
Solar/Wind Harmer
0.562
945391AF1-204 GEN
Solar/Wind Harmer
4.219
970623AG2-406 GEN
Solar/Wind Harmer
0.656
971587AH1-292 GEN
Solar/Wind Harmer
2.468
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.897
270462AD2-086
Solar/Wind Helper
3.747
247522W1-056 GEN
Solar/Wind Helper
1.177
253378AE2-206_GEN
Solar/Wind Helper
0.715
270349AD2-093_GEN
Solar/Wind Helper
0.857
270471AD2-092_GEN
Solar/Wind Helper
0.857
241960AC2-195 GEN
Solar/Wind Helper
0.697
24727005RPMNG1
50/50
3.317
960861AF2-377 GEN
50/50
2.406
970521AG2-332 GEN
50/50
10.906
24639705ELKHART HY
50/50
0.151
270143AC1-141 CT2_
50/50
2.029
965011AG1-365 GEN
Solar/Wind Harmer
13.822
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.876
958861AF2-177 GEN
Solar/Wind Harmer
2.694
945111AF1-176 GEN
Solar/Wind Harmer
10.683
957891AF2-083 GEN
Solar/Wind Harmer
9.802
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3
970373AG2-245 GEN
Solar/Wind Harmer
11.243
274751CRETE EC ;1U
Adder
6.312
274754CRETE EC ;4U
Adder
6.312
274723RIVER EC ;12
Adder
13.681
274812UNIV PK N;8U
Adder
3.792
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.365
274774LINCOLN ;5U
Adder
6.365
274802UNIV PARK;5U
Adder
4.369
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.75
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.662
274674JOLIET 9 ;6U
Adder
11.348
274732ELWOOD EC;7P
Adder
12.11
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.364
270594AE1-207 GEN
Solar/Wind Harmer
5.699
270032AE2-172
Solar/Wind Harmer
3.392
270005AE1-210 C O1
Solar/Wind Harmer
1.101
274745AC1-111 GEN9
Adder
4.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.82
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.788
274682WAUKEGAN ;7U
Adder
12.933
274828WAUKEGAN ;BP
Adder
7.939
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.731
939401AE1-172 GEN
Solar/Wind Harmer
3.718
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.578
971997AH1-543 GEN
Solar/Wind Harmer
2.59
957471AF2-041 GEN
Solar/Wind Harmer
14.651
959081AF2-199 GEN
Solar/Wind Harmer
4.884
971067AG2-660 GEN
Solar/Wind Harmer
1.628
274822ROCKFORD ;11
Adder
13.696
276903AD2-071 C
Solar/Wind Harmer
5.426
970819AG2-516 GEN
Solar/Wind Harmer
5.809
970569AG2-363 GEN
Solar/Wind Harmer
14.512
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.381
274766LEE CO EC;7U
Adder
6.306
276708O09 GEN2
Solar/Wind Harmer
0.167
276646AC1-214 GEN2
Solar/Wind Harmer
0.185
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.519
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.287
963741AG1-226 GEN
Solar/Wind Harmer
10.473
276621W2-048 GEN
Solar/Wind Harmer
0.213
965911AG1-460 GEN
Solar/Wind Harmer
0.82
24728605AND G2
Adder
2.099
970773AG2-487 GEN
Solar/Wind Harmer
0.63
246936BC-WTG1
Solar/Wind Helper
10.897
270317AD1-130_GEN
Solar/Wind Helper
4.143
270485AE1-090_GEN
Solar/Wind Helper
0.326
270391AF1-285 GEN3
Solar/Wind Helper
0.593
270578AF1-285 GEN2
Solar/Wind Helper
0.593
270286AF1-227 GEN2
Solar/Wind Helper
0.694
960841AF2-375 GEN
Solar/Wind Helper
1.179
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.835
NYPJM->LTFIMP_NY
CLTF
1.264
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042
AG2-052LTFEXP_AG2-052->PJM
LTF
0.172
AH1-155LTFEXP_AH1-155->PJM
LTF
0.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
70.253
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.933
MECLTFEXP_MEC->PJM
CLTF
9.784
SIGELTFEXP_SIGE->PJM
CLTF
0.201
LAGNLTFEXP_LAGN->PJM
CLTF
5.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.51
TVALTFEXP_TVA->PJM
CLTF
2.319

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P1-2_#7442_200545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P1-2_#7442_200545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.01 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3190.2
MW Contribution:
4.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.734
24729305KEY G2
50/50
0.721
24729205KEY G1
50/50
0.718
247620Y3-023
50/50
0.69
960851AF2-376 GEN
50/50
3.277
24643105BUCHANAN
50/50
0.016
247621Y3-024
50/50
0.324
944541AF1-119 GEN
Solar/Wind Harmer
0.834
960971AF2-388 GEN
Solar/Wind Harmer
7.331
942221AE2-234 GEN
Solar/Wind Harmer
4.522
944231AF1-091 GEN
Solar/Wind Harmer
24.786
270031AE2-169
Solar/Wind Harmer
5.613
270599AE1-208 GEN
Solar/Wind Harmer
9.355
270246TR4_N_V150
Solar/Wind Harmer
0.065
270247TR4_N_V136
Solar/Wind Harmer
0.065
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.696
961051AF2-396 GEN
Solar/Wind Harmer
17.945
961051AF2-396 GEN
Solar/Wind Harmer
11.963
971613AH1-306 GEN
Solar/Wind Harmer
4.3
970291AG2-192 GEN
Solar/Wind Harmer
1.152
970291AG2-192 GEN
Solar/Wind Harmer
0.532
970349AG2-230 GEN
Solar/Wind Harmer
13.187
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
960861AF2-377 GEN
50/50
3.382
970521AG2-332 GEN
50/50
16.165
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.308
270143AC1-141 CT2_
50/50
3.096
965011AG1-365 GEN
Solar/Wind Harmer
12.741
965651AG1-433 GEN
Solar/Wind Harmer
3.666
958861AF2-177 GEN
Solar/Wind Harmer
5.255
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.002
270005AE1-210 C O1
Solar/Wind Harmer
2.117
970825AG2-519 GEN
Solar/Wind Harmer
3.304
945111AF1-176 GEN
Solar/Wind Harmer
16.279
957891AF2-083 GEN
Solar/Wind Harmer
15.012
270594AE1-207 GEN
Solar/Wind Harmer
10.034
270032AE2-172
Solar/Wind Harmer
5.973
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.637
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.415
965421AG1-410 GEN
Solar/Wind Harmer
26.149
276903AD2-071 C
Solar/Wind Harmer
9.536
246936BC-WTG1
Solar/Wind Harmer
0.334
270489AE1-102 GEN1
Solar/Wind Harmer
1.078
970373AG2-245 GEN
Solar/Wind Harmer
16.897
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
9.326
274754CRETE EC ;4U
Adder
9.326
274723RIVER EC ;12
Adder
20.174
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
5.593
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
10.122
274802UNIV PARK;5U
Adder
6.433
274773LINCOLN ;4U
Adder
9.292
274774LINCOLN ;5U
Adder
9.292
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.53
274676JOLIET 29;8U
Adder
33.312
941551AE2-152 GEN
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
16.683
274732ELWOOD EC;7P
Adder
17.809
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.972
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.208
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
19.011
274828WAUKEGAN ;BP
Adder
11.67
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.485
962781AG1-127 GEN
Solar/Wind Harmer
6.953
276882AE2-255 GEN
Solar/Wind Harmer
0.852
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.817
957471AF2-041 GEN
Solar/Wind Harmer
21.562
959081AF2-199 GEN
Solar/Wind Harmer
7.187
971067AG2-660 GEN
Solar/Wind Harmer
2.396
274822ROCKFORD ;11
Adder
20.159
970569AG2-363 GEN
Solar/Wind Harmer
21.445
970819AG2-516 GEN
Solar/Wind Harmer
8.554
24729505KEY G4
50/50
13.443
24727205RPMNG3
50/50
1.301
24653605MOTTVILLE
50/50
0.005
24641605TWIN BRNCH
50/50
0.023
270144AC1-141 ST1_
50/50
2.734
270071AF1-092 GEN
Solar/Wind Harmer
25.488
959331AF2-224 GEN
Solar/Wind Harmer
8.919
970031AG2-029 GEN
Solar/Wind Harmer
6.248
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
15.281
965041AG1-368 GEN
Solar/Wind Harmer
10.96
971609AH1-304 GEN
Solar/Wind Harmer
1.667
247521TR3_G114
Solar/Wind Harmer
0.367
965051AG1-369 GEN
Solar/Wind Harmer
5.063
964611AG1-324 GEN
Solar/Wind Harmer
3.62
971771AH1-392 GEN
Solar/Wind Harmer
8.998
970289AG2-191 GEN
Solar/Wind Harmer
1.684
270526AF1-158 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.341
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.05
971549AH1-272 GEN
Solar/Wind Harmer
17.043
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.563
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.547
959141AF2-205 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
9.292
274776LINCOLN ;7U
Adder
9.292
274777LINCOLN ;8U
Adder
9.292
274800UNIV PARK;3U
Adder
6.411
274801UNIV PARK;4U
Adder
6.411
960591AF2-350 GEN
Solar/Wind Harmer
7.658
972228AH1-698 GEN2
Adder
4.051
972227AH1-698 GEN1
Adder
2.852
971611AH1-305 GEN
Solar/Wind Harmer
4.539
274687WILL CNTY;4U
Adder
30.416
274687WILL CNTY;4U
Adder
30.416
970583AG2-370 GEN
50/50
3.653
24727105RPMNG2
50/50
1.309
270142AC1-141 CT1_
50/50
3.096
24642205MAYFLWER
50/50
0.047
944961AF1-161 GEN
50/50
3.701
962601AG1-109 GEN
50/50
3.701
944531AF1-118 GEN
Solar/Wind Harmer
62.885
270043AE2-236 GEN
Solar/Wind Harmer
8.814
965021AG1-366 GEN
Solar/Wind Harmer
4.247
270063AE2-323 C
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.832
270004AE1-209 GEN
Solar/Wind Harmer
2.117
970825AG2-519 GEN
Solar/Wind Harmer
7.011
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.926
946031AF1-268 GEN
Solar/Wind Harmer
8.826
945111AF1-176 GEN
Solar/Wind Harmer
7.395
270505AE1-170 C O1
Solar/Wind Harmer
9.418
970289AG2-191 GEN
Solar/Wind Harmer
0.975
971347AH1-153 GEN
Solar/Wind Harmer
4.396
247642Z2-115 C
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.299
270491AE1-102 GEN2
Solar/Wind Harmer
1.078
274752CRETE EC ;2U
Adder
9.326
274753CRETE EC ;3U
Adder
9.326
274724RIVER EC ;11
Adder
19.931
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.641
274807UNIV PK N;3U
Adder
5.629
274811UNIV PK N;7U
Adder
5.593
274803UNIV PARK;6U
Adder
6.433
274826FISK ;BP
Adder
12.06
274772LINCOLN ;3U
Adder
9.292
972038AH1-567 GEN2
Adder
0.401
274887GEN-1.85
Solar/Wind Harmer
0.199
276843GEN-1.7
Solar/Wind Harmer
0.248
276806AD2-047 C O1
Solar/Wind Harmer
4.34
972259AH1-714 GEN
Adder
20.761
274676JOLIET 29;8U
Adder
32.122
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
24.739
274730ELWOOD EC;6P
Adder
17.809
274734ELWOOD EC;8P
Adder
17.809
274736ELWOOD EC;9P
Adder
17.809
274729ELWOOD EC;1P
Adder
17.808
943121AE2-341 GEN
Solar/Wind Harmer
12.495
943591AF1-030 GEN
Solar/Wind Harmer
8.309
274862TOP CROP ;2U
Solar/Wind Harmer
1.004
274682WAUKEGAN ;7U
Adder
19.011
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.342
276868AE1-113 GEN
Solar/Wind Harmer
1.461
274879MINONK ;1U
Solar/Wind Harmer
0.305
946671AF1-331 GEN
Solar/Wind Harmer
0.771
274855GSG-6 ;RU
Solar/Wind Harmer
0.264
274850MENDOTA H;RU
Solar/Wind Harmer
0.084
959091AF2-200 GEN
Solar/Wind Harmer
14.375
970571AG2-364 GEN
Solar/Wind Harmer
14.297
24386205FR-12G C
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.403
274767LEE CO EC;8U
Adder
9.292
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.232
965091AG1-374 GEN
Solar/Wind Harmer
20.486
959611AF2-252 GEN
Solar/Wind Harmer
2.276
24728705AND G3
Adder
7.836
24728505AND G1
Adder
3.747
965931AG1-462 GEN
Solar/Wind Harmer
17.242
971087AG2-675 GEN
Solar/Wind Harmer
3.606
971993AH1-541 GEN
Solar/Wind Harmer
3.006
970193AG2-126 GEN
Solar/Wind Harmer
9.362
957381AF2-032 GEN
Solar/Wind Harmer
1.409
942481AE2-261 GEN
Solar/Wind Harmer
18.539
23906402RICHG1
Adder
0.876
23906502RICHG2&3
Adder
0.869
270541AE2-072 C
Solar/Wind Harmer
0
958321AF2-126 GEN
Solar/Wind Harmer
0.443
270284AF1-227 GEN1
Solar/Wind Helper
1.175
270287AF1-227 GEN3
Solar/Wind Helper
0.431
274675JOLIET 29;7U
Adder
33.312
274675JOLIET 29;7U
Adder
32.122
274728ELWOOD EC;5P
Adder
17.809
274731ELWOOD EC;2P
Adder
17.808
274733ELWOOD EC;3P
Adder
17.808
274735ELWOOD EC;4P
Adder
17.808
970833AG2-524 GEN
Solar/Wind Harmer
8.267
970833AG2-524 GEN
Solar/Wind Harmer
5.511
274744AC1-111 GEN8
Adder
5.972
274746AC1-111 G10
Adder
5.972
970073AG2-061 GEN
Solar/Wind Harmer
2.45
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.958
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
10.852
971675AH1-338 GEN
Solar/Wind Harmer
2.819
276861AD2-134 GEN
Solar/Wind Harmer
0.129
276863AD2-134 GEN
Solar/Wind Harmer
0.129
971171AH1-044 GEN
Solar/Wind Harmer
14.375
274823ROCKFORD ;21
Adder
20.012
970169AG2-114 GEN
Solar/Wind Harmer
7.144
926823AC1-168 GEN
Solar/Wind Harmer
1.213
274856ECOGROVE ;U1
Solar/Wind Harmer
0.166
24386405FR-21G C
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
11.398
972267AH1-718 GEN
Adder
4.17
276741O09 GEN1
Solar/Wind Harmer
0.247
274877BISHOP HL;1U
Solar/Wind Harmer
0.232
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.282
963841AG1-237 GEN
Solar/Wind Harmer
3.005
274854TWINGROVE;U2
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
3.807
276668AB2-070 GEN1
Solar/Wind Harmer
0.256
276848AB2-070 GEN3
Solar/Wind Harmer
0.255
276849AB2-070 GEN2
Solar/Wind Harmer
0.256
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.516
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
945411AF1-206 GEN
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.54
965681AG1-436 GEN
Solar/Wind Harmer
10.47
965791AG1-447 GEN
Solar/Wind Harmer
7.678
246937BC-WTG2
Solar/Wind Harmer
0.334
247607V1-011 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.947
970885AG2-551 GEN
Solar/Wind Harmer
2.649
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.605
274808UNIV PK N;4U
Adder
5.568
274770LINCOLN ;1U
Adder
9.292
274771LINCOLN ;2U
Adder
9.292
274888KELLY CRK;1U
Solar/Wind Harmer
0.447
276776AD2-060 GEN
Solar/Wind Harmer
0.817
958011AF2-095 GEN
Solar/Wind Harmer
11.028
970941AG2-585 GEN
Solar/Wind Harmer
4.212
276897AD1-100 C
Solar/Wind Harmer
18.934
276893AG1-478 C
Solar/Wind Harmer
0.504
274674JOLIET 9 ;6U
Adder
16.683
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
11.155
274696ROCKY RD ;4P
Adder
12.055
274695ROCKY RD ;2P
Adder
11.777
274693ROCKY RD ;1P
Adder
11.662
274697ROCKY RD ;3P
Adder
3.199
274683WAUKEGAN ;8U
Adder
22.263
274683WAUKEGAN ;8U
Adder
18.767
958491AF2-143 GEN
Solar/Wind Harmer
11.026
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
21.97
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.375
971343AH1-151 GEN
Solar/Wind Harmer
14.375
972235AH1-702 GEN1
Adder
2.583
972236AH1-702 GEN2
Adder
2.246
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.805
938861AE1-114 GEN
Solar/Wind Harmer
4.01
274764LEE CO EC;5U
Adder
9.425
274765LEE CO EC;6U
Adder
9.425
274762LEE CO EC;3U
Adder
9.403
274763LEE CO EC;4U
Adder
9.314
276645AC1-214 GEN1
Solar/Wind Harmer
0.274
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.126
942111AE2-223 GEN
Solar/Wind Harmer
2.254
960611AF2-352 GEN
Solar/Wind Harmer
2.276
970241AG2-163 GEN
Solar/Wind Harmer
3.954
276615X2-022 GEN
Solar/Wind Harmer
0.066
276838X2-022 GEN2
Solar/Wind Harmer
0.361
945391AF1-204 GEN
Solar/Wind Harmer
6.631
276916AD2-100_GEN
Solar/Wind Harmer
12.922
276911AD2-131_GEN
Solar/Wind Harmer
0.851
24728805RICHG1
Adder
3.1
24728905RICHG2
Adder
3.1
970621AG2-405 GEN
Solar/Wind Harmer
1.034
971587AH1-292 GEN
Solar/Wind Harmer
3.867
964571AG1-320 GEN
Solar/Wind Harmer
2.864
270349AD2-093_GEN
Solar/Wind Helper
1.081
270471AD2-092_GEN
Solar/Wind Helper
1.081
270054AF2-122 C O1
Solar/Wind Helper
0.78
946101AF1-275 GEN
Solar/Wind Helper
0.301
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.403
274766LEE CO EC;7U
Adder
9.292
276646AC1-214 GEN2
Solar/Wind Harmer
0.274
276708O09 GEN2
Solar/Wind Harmer
0.247
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.71
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24728605AND G2
Adder
3.747
970773AG2-487 GEN
Solar/Wind Harmer
1.202
963741AG1-226 GEN
Solar/Wind Harmer
16.041
276621W2-048 GEN
Solar/Wind Harmer
0.32
965911AG1-460 GEN
Solar/Wind Harmer
1.24
23906502RICHG2&3
Adder
0.869
970091AG2-072 GEN
Adder
47.294
23920202STRYCT
Adder
0.781
241858AF1-205_GEN
Solar/Wind Harmer
1.344
270286AF1-227 GEN2
Solar/Wind Helper
0.431
270520AE2-214 GEN
Solar/Wind Helper
1.202
990792J1392
External Queue
6.545727729797363
990497J1323
External Queue
1.9028279781341553
991297J1743
External Queue
13.235071182250977
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.688
NYPJM->LTFIMP_NY
CLTF
1.989
LGEELTFEXP_LGEE->PJM
CLTF
3.263
WECLTFEXP_WEC->PJM
CLTF
3.91
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.333
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.471
MECLTFEXP_MEC->PJM
CLTF
14.518
SIGELTFEXP_SIGE->PJM
CLTF
0.335
LAGNLTFEXP_LAGN->PJM
CLTF
8.402
TVALTFEXP_TVA->PJM
CLTF
3.331

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.53 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5607.44
MW Contribution:
5.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
5.013
24642205MAYFLWER
50/50
0.076
274772LINCOLN ;3U
50/50
18.336
944961AF1-161 GEN
50/50
5.942
962601AG1-109 GEN
50/50
5.942
971347AH1-153 GEN
Solar/Wind Harmer
7.766
270043AE2-236 GEN
Solar/Wind Harmer
9.417
270505AE1-170 C O1
Solar/Wind Harmer
15.137
945111AF1-176 GEN
Solar/Wind Harmer
11.613
274724RIVER EC ;11
Adder
35.793
274752CRETE EC ;2U
Adder
16.621
274753CRETE EC ;3U
Adder
16.621
270063AE2-323 C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
10.141
274807UNIV PK N;3U
Adder
10.119
274811UNIV PK N;7U
Adder
10.053
970707AG2-453 GEN
Solar/Wind Harmer
45.738
972259AH1-714 GEN
Adder
38.13
274803UNIV PARK;6U
Adder
11.65
274826FISK ;BP
Adder
21.872
274887GEN-1.85
Solar/Wind Harmer
0.362
276843GEN-1.7
Solar/Wind Harmer
0.45
276806AD2-047 C O1
Solar/Wind Harmer
7.895
972038AH1-567 GEN2
Adder
0.728
939351AE1-166 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
61.966
274676JOLIET 29;8U
Adder
58.599
274729ELWOOD EC;1P
Adder
32.486
274730ELWOOD EC;6P
Adder
32.486
274734ELWOOD EC;8P
Adder
32.486
274736ELWOOD EC;9P
Adder
32.486
943121AE2-341 GEN
Solar/Wind Harmer
22.986
943591AF1-030 GEN
Solar/Wind Harmer
15.286
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.824
274682WAUKEGAN ;7U
Adder
34.771
276868AE1-113 GEN
Solar/Wind Harmer
2.661
274879MINONK ;1U
Solar/Wind Harmer
0.555
946671AF1-331 GEN
Solar/Wind Harmer
1.412
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.154
959091AF2-200 GEN
Solar/Wind Harmer
26.289
970571AG2-364 GEN
Solar/Wind Harmer
25.984
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
17.161
274767LEE CO EC;8U
Adder
16.958
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
12.865
965021AG1-366 GEN
Solar/Wind Harmer
4.261
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.422
24386205FR-12G C
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
37.086
959611AF2-252 GEN
Solar/Wind Harmer
4.121
965931AG1-462 GEN
Solar/Wind Harmer
31.345
971087AG2-675 GEN
Solar/Wind Harmer
6.556
247642Z2-115 C
Solar/Wind Harmer
0.005
971993AH1-541 GEN
Solar/Wind Harmer
5.405
970289AG2-191 GEN
Solar/Wind Harmer
1.271
957381AF2-032 GEN
Solar/Wind Harmer
2.525
942481AE2-261 GEN
Solar/Wind Harmer
33.208
270004AE1-209 GEN
Solar/Wind Harmer
2.315
970193AG2-126 GEN
Solar/Wind Harmer
16.03
970825AG2-519 GEN
Solar/Wind Harmer
7.905
946031AF1-268 GEN
Solar/Wind Harmer
9.859
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.395
24695305TIMB G C
Solar/Wind Harmer
0.837
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728705AND G3
Adder
10.702
24728505AND G1
Adder
5.117
246938BC-WTG3
Solar/Wind Harmer
0.29
270491AE1-102 GEN2
Solar/Wind Harmer
1.048
24344005CKG1
50/50
13.518
270144AC1-141 ST1_
50/50
4.427
24641605TWIN BRNCH
50/50
0.036
274775LINCOLN ;6U
50/50
18.336
274776LINCOLN ;7U
50/50
18.336
274777LINCOLN ;8U
50/50
18.336
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
14.587
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
27.676
972037AH1-567 GEN1
Adder
0.366
274827FISK ;RP
Adder
15.501
960591AF2-350 GEN
Solar/Wind Harmer
13.932
972228AH1-698 GEN2
Adder
7.394
972227AH1-698 GEN1
Adder
5.206
274800UNIV PARK;3U
Adder
11.637
274801UNIV PARK;4U
Adder
11.637
274687WILL CNTY;4U
Adder
55.408
274687WILL CNTY;4U
Adder
55.408
274675JOLIET 29;7U
Adder
60.77
274675JOLIET 29;7U
Adder
58.6
970031AG2-029 GEN
Solar/Wind Harmer
7.48
274728ELWOOD EC;5P
Adder
32.486
274731ELWOOD EC;2P
Adder
32.486
274733ELWOOD EC;3P
Adder
32.486
274735ELWOOD EC;4P
Adder
32.486
970833AG2-524 GEN
Solar/Wind Harmer
15.154
970833AG2-524 GEN
Solar/Wind Harmer
10.103
274744AC1-111 GEN8
Adder
10.963
274746AC1-111 G10
Adder
10.963
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.577
959141AF2-205 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
4.454
971611AH1-305 GEN
Solar/Wind Harmer
7.947
971675AH1-338 GEN
Solar/Wind Harmer
5.16
971411AH1-196 GEN
Solar/Wind Harmer
19.845
276861AD2-134 GEN
Solar/Wind Harmer
0.236
276863AD2-134 GEN
Solar/Wind Harmer
0.236
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
26.289
274823ROCKFORD ;21
Adder
36.573
970169AG2-114 GEN
Solar/Wind Harmer
13.017
274856ECOGROVE ;U1
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
2.21
971549AH1-272 GEN
Solar/Wind Harmer
26.772
971681AH1-341 GEN
Solar/Wind Harmer
20.809
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
8.949
972267AH1-718 GEN
Adder
7.604
276741O09 GEN1
Solar/Wind Harmer
0.449
274877BISHOP HL;1U
Solar/Wind Harmer
0.422
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
13.203
24386405FR-21G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.924
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
5.236
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
15.924
276668AB2-070 GEN1
Solar/Wind Harmer
0.46
276848AB2-070 GEN3
Solar/Wind Harmer
0.458
276849AB2-070 GEN2
Solar/Wind Harmer
0.46
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
2.196
971609AH1-304 GEN
Solar/Wind Harmer
1.842
965041AG1-368 GEN
Solar/Wind Harmer
11.074
944221AF1-090 GEN
Solar/Wind Harmer
6.279
964611AG1-324 GEN
Solar/Wind Harmer
4.011
247521TR3_G114
Solar/Wind Harmer
0.369
965051AG1-369 GEN
Solar/Wind Harmer
5.084
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.379
270543AE2-219 C
Solar/Wind Harmer
6.219
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
12.334
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.021
270102X2-052 ST
50/50
3.362
270100X2-052 CT1
50/50
3.107
270101X2-052 CT2
50/50
3.107
24643105BUCHANAN
50/50
0.026
274770LINCOLN ;1U
50/50
18.336
274771LINCOLN ;2U
50/50
18.336
247620Y3-023
50/50
0.993
970349AG2-230 GEN
Solar/Wind Harmer
23.297
965681AG1-436 GEN
Solar/Wind Harmer
18.242
965791AG1-447 GEN
Solar/Wind Harmer
13.377
961051AF2-396 GEN
Solar/Wind Harmer
28.57
961051AF2-396 GEN
Solar/Wind Harmer
19.046
274805UNIV PK N;1U
Adder
10.075
274808UNIV PK N;4U
Adder
10.009
274888KELLY CRK;1U
Solar/Wind Harmer
0.813
276776AD2-060 GEN
Solar/Wind Harmer
1.486
958011AF2-095 GEN
Solar/Wind Harmer
20.062
970941AG2-585 GEN
Solar/Wind Harmer
7.663
276897AD1-100 C
Solar/Wind Harmer
34.688
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
30.452
276893AG1-478 C
Solar/Wind Harmer
0.919
274695ROCKY RD ;2P
Adder
21.58
274693ROCKY RD ;1P
Adder
21.367
274697ROCKY RD ;3P
Adder
5.862
274696ROCKY RD ;4P
Adder
22.088
958481AF2-142 GEN
Solar/Wind Harmer
20.28
274683WAUKEGAN ;8U
Adder
40.715
274683WAUKEGAN ;8U
Adder
34.321
962691AG1-118 GEN
Solar/Wind Harmer
40.277
958491AF2-143 GEN
Solar/Wind Harmer
20.043
276901AD2-066 C O1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
26.289
971343AH1-151 GEN
Solar/Wind Harmer
26.289
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
4.72
972236AH1-702 GEN2
Adder
4.104
938861AE1-114 GEN
Solar/Wind Harmer
7.321
274764LEE CO EC;5U
Adder
17.201
274765LEE CO EC;6U
Adder
17.201
274762LEE CO EC;3U
Adder
17.161
274763LEE CO EC;4U
Adder
16.999
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
2.052
276645AC1-214 GEN1
Solar/Wind Harmer
0.499
944541AF1-119 GEN
Solar/Wind Harmer
0.848
960971AF2-388 GEN
Solar/Wind Harmer
7.448
942111AE2-223 GEN
Solar/Wind Harmer
4.087
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.408
960611AF2-352 GEN
Solar/Wind Harmer
4.121
942221AE2-234 GEN
Solar/Wind Harmer
4.822
970241AG2-163 GEN
Solar/Wind Harmer
6.864
970291AG2-192 GEN
Solar/Wind Harmer
1.502
970291AG2-192 GEN
Solar/Wind Harmer
0.693
276615X2-022 GEN
Solar/Wind Harmer
0.119
276838X2-022 GEN2
Solar/Wind Harmer
0.647
944231AF1-091 GEN
Solar/Wind Harmer
26.413
971613AH1-306 GEN
Solar/Wind Harmer
5.417
270031AE2-169
Solar/Wind Harmer
6.202
270599AE1-208 GEN
Solar/Wind Harmer
10.337
276916AD2-100_GEN
Solar/Wind Harmer
23.132
276911AD2-131_GEN
Solar/Wind Harmer
1.524
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
11.354
964611AG1-324 GEN
Solar/Wind Harmer
0.771
270201AC2-176 GEN
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.065
270247TR4_N_V136
Solar/Wind Harmer
0.065
971587AH1-292 GEN
Solar/Wind Harmer
7.235
247621Y3-024
Adder
0.338
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
8.884
970885AG2-551 GEN
Solar/Wind Harmer
2.961
970623AG2-406 GEN
Solar/Wind Harmer
1.577
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.325
24728805RICHG1
Adder
3.746
24728905RICHG2
Adder
3.746
270349AD2-093_GEN
Solar/Wind Helper
1.553
270471AD2-092_GEN
Solar/Wind Helper
1.553
24344105CKG2
50/50
17.278
270143AC1-141 CT2_
50/50
5.013
24639705ELKHART HY
50/50
0.334
274773LINCOLN ;4U
50/50
18.336
274774LINCOLN ;5U
50/50
18.336
970521AG2-332 GEN
50/50
23.772
24307105BERRINSP G
50/50
0.044
957891AF2-083 GEN
Solar/Wind Harmer
23.982
945111AF1-176 GEN
Solar/Wind Harmer
25.563
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
7.444
274723RIVER EC ;12
Adder
36.21
274751CRETE EC ;1U
Adder
16.621
274754CRETE EC ;4U
Adder
16.621
970373AG2-245 GEN
Solar/Wind Harmer
29.476
274812UNIV PK N;8U
Adder
10.053
274802UNIV PARK;5U
Adder
11.65
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
60.769
274674JOLIET 9 ;6U
Adder
30.452
274732ELWOOD EC;7P
Adder
32.486
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
10.963
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
17.697
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
2.197
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
34.771
274828WAUKEGAN ;BP
Adder
21.342
939401AE1-172 GEN
Solar/Wind Harmer
10.03
962781AG1-127 GEN
Solar/Wind Harmer
12.744
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
16.687
276882AE2-255 GEN
Solar/Wind Harmer
1.552
971997AH1-543 GEN
Solar/Wind Harmer
6.973
957471AF2-041 GEN
Solar/Wind Harmer
39.433
959081AF2-199 GEN
Solar/Wind Harmer
13.144
971067AG2-660 GEN
Solar/Wind Harmer
4.381
274822ROCKFORD ;11
Adder
36.841
970819AG2-516 GEN
Solar/Wind Harmer
15.625
970569AG2-363 GEN
Solar/Wind Harmer
38.976
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
17.161
274766LEE CO EC;7U
Adder
16.958
965011AG1-365 GEN
Solar/Wind Harmer
12.784
276708O09 GEN2
Solar/Wind Harmer
0.449
276646AC1-214 GEN2
Solar/Wind Harmer
0.499
965651AG1-433 GEN
Solar/Wind Harmer
3.724
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
17.604
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
5.383
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
27.848
276621W2-048 GEN
Solar/Wind Harmer
0.575
270594AE1-207 GEN
Solar/Wind Harmer
12.64
270032AE2-172
Solar/Wind Harmer
7.524
965911AG1-460 GEN
Solar/Wind Harmer
2.221
276903AD2-071 C
Solar/Wind Harmer
12.218
270024AE2-089 GEN
Solar/Wind Harmer
0.002
270005AE1-210 C O1
Solar/Wind Harmer
2.315
970825AG2-519 GEN
Solar/Wind Harmer
3.725
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.127
970091AG2-072 GEN
Adder
105.739
24728605AND G2
Adder
5.117
965421AG1-410 GEN
Solar/Wind Harmer
25.535
970773AG2-487 GEN
Solar/Wind Harmer
1.491
246936BC-WTG1
Solar/Wind Harmer
0.325
270489AE1-102 GEN1
Solar/Wind Harmer
1.048
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.166
NYPJM->LTFIMP_NY
CLTF
3.371
LGEELTFEXP_LGEE->PJM
CLTF
5.638
WECLTFEXP_WEC->PJM
CLTF
7.136
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.164
AG2-052LTFEXP_AG2-052->PJM
LTF
0.449
AH1-155LTFEXP_AH1-155->PJM
LTF
0.674
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5
CBM West 1LTFEXP_CBM-W1->PJM
CBM
218.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.394
MECLTFEXP_MEC->PJM
CLTF
26.166
SIGELTFEXP_SIGE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
14.281
TVALTFEXP_TVA->PJM
CLTF
5.469

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.63 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2609.67
MW Contribution:
3.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
5.175
24726605LAWG1S
50/50
5.173
24726705LAWG2A
50/50
3.469
24726505LAWG1B
50/50
3.445
24726805LAWG2B
50/50
3.43
24729505KEY G4
50/50
6.226
270356AE2-297 GEN
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.089
964611AG1-324 GEN
Solar/Wind Harmer
2.474
970289AG2-191 GEN
Solar/Wind Harmer
1.136
247536S-71 GEN
Solar/Wind Harmer
0.216
270543AE2-219 C
Solar/Wind Harmer
3.467
971029AG2-637 GEN
Solar/Wind Harmer
6.645
270071AF1-092 GEN
Solar/Wind Harmer
8.015
963791AG1-232 GEN
Solar/Wind Harmer
5.573
963841AG1-237 GEN
Solar/Wind Harmer
1.664
24386405FR-21G C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.16
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.138
276848AB2-070 GEN3
Solar/Wind Harmer
0.137
276849AB2-070 GEN2
Solar/Wind Harmer
0.138
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.675
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
3.478
274775LINCOLN ;6U
Adder
4.193
274776LINCOLN ;7U
Adder
4.193
274777LINCOLN ;8U
Adder
4.193
960681AF2-359 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
1.832
972227AH1-698 GEN1
Adder
1.29
960591AF2-350 GEN
Solar/Wind Harmer
3.45
944221AF1-090 GEN
Solar/Wind Harmer
2.022
972037AH1-567 GEN1
Adder
0.09
274800UNIV PARK;3U
Adder
2.879
274801UNIV PARK;4U
Adder
2.879
274827FISK ;RP
Adder
3.829
970833AG2-524 GEN
Solar/Wind Harmer
3.784
970833AG2-524 GEN
Solar/Wind Harmer
2.522
274728ELWOOD EC;5P
Adder
8.1
274731ELWOOD EC;2P
Adder
8.1
274733ELWOOD EC;3P
Adder
8.1
274735ELWOOD EC;4P
Adder
8.1
274687WILL CNTY;4U
Adder
13.754
274687WILL CNTY;4U
Adder
13.754
274675JOLIET 29;7U
Adder
15.095
274675JOLIET 29;7U
Adder
14.556
274744AC1-111 GEN8
Adder
2.736
274746AC1-111 G10
Adder
2.736
970073AG2-061 GEN
Solar/Wind Harmer
1.138
270526AF1-158 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.579
971771AH1-392 GEN
Solar/Wind Harmer
3.397
970031AG2-029 GEN
Solar/Wind Harmer
1.836
276861AD2-134 GEN
Solar/Wind Harmer
0.06
276863AD2-134 GEN
Solar/Wind Harmer
0.06
971675AH1-338 GEN
Solar/Wind Harmer
1.313
274877BISHOP HL;1U
Solar/Wind Harmer
0.112
971411AH1-196 GEN
Solar/Wind Harmer
5.046
971171AH1-044 GEN
Solar/Wind Harmer
6.717
274823ROCKFORD ;21
Adder
9.354
274856ECOGROVE ;U1
Solar/Wind Harmer
0.078
971681AH1-341 GEN
Solar/Wind Harmer
5.372
276741O09 GEN1
Solar/Wind Harmer
0.118
972267AH1-718 GEN
Adder
1.98
946321AF1-296 GEN
Solar/Wind Harmer
1.835
959331AF2-224 GEN
Solar/Wind Harmer
2.126
241972AD1-140 GEN
Solar/Wind Helper
3.462
253406AD2-031_GEN
Solar/Wind Helper
0.908
270340AC2-060 GEN
Solar/Wind Helper
1.186
253338AC1-165 GEN
Solar/Wind Helper
0.584
253343AC1-166 GEN
Solar/Wind Helper
0.584
241973AD2-163_GEN1
Solar/Wind Helper
1.034
241974AD2-163_GEN2
Solar/Wind Helper
1.034
945631AF1-228 GEN
Solar/Wind Helper
1.084
241955AC1-078 GEN
Solar/Wind Helper
0.981
961161AF2-407 GEN
50/50
36.206
24728705AND G3
50/50
7.209
24728505AND G1
50/50
3.447
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.847
970825AG2-519 GEN
Solar/Wind Harmer
5.553
946031AF1-268 GEN
Solar/Wind Harmer
6.921
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.138
944531AF1-118 GEN
Solar/Wind Harmer
27.23
970289AG2-191 GEN
Solar/Wind Harmer
0.658
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
6.211
270043AE2-236 GEN
Solar/Wind Harmer
2.461
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.696
964401AG1-302 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.619
971347AH1-153 GEN
Solar/Wind Harmer
1.751
965091AG1-374 GEN
Solar/Wind Harmer
10.482
959611AF2-252 GEN
Solar/Wind Harmer
1.165
274772LINCOLN ;3U
Adder
4.193
939351AE1-166 GEN
Solar/Wind Harmer
0
957381AF2-032 GEN
Solar/Wind Harmer
0.783
942481AE2-261 GEN
Solar/Wind Harmer
10.33
274724RIVER EC ;11
Adder
8.762
274752CRETE EC ;2U
Adder
4.076
274753CRETE EC ;3U
Adder
4.076
274887GEN-1.85
Solar/Wind Harmer
0.09
276843GEN-1.7
Solar/Wind Harmer
0.112
276806AD2-047 C O1
Solar/Wind Harmer
1.955
274814UNIV PK N;0U
Adder
2.497
274807UNIV PK N;3U
Adder
2.491
274811UNIV PK N;7U
Adder
2.475
972259AH1-714 GEN
Adder
9.423
274803UNIV PARK;6U
Adder
2.879
972038AH1-567 GEN2
Adder
0.18
274826FISK ;BP
Adder
5.402
970707AG2-453 GEN
Solar/Wind Harmer
11.245
274729ELWOOD EC;1P
Adder
8.1
274730ELWOOD EC;6P
Adder
8.1
274734ELWOOD EC;8P
Adder
8.1
274736ELWOOD EC;9P
Adder
8.1
274676JOLIET 29;8U
Adder
14.556
274862TOP CROP ;2U
Solar/Wind Harmer
0.462
943121AE2-341 GEN
Solar/Wind Harmer
5.725
943591AF1-030 GEN
Solar/Wind Harmer
3.807
276868AE1-113 GEN
Solar/Wind Harmer
0.682
274879MINONK ;1U
Solar/Wind Harmer
0.142
970571AG2-364 GEN
Solar/Wind Harmer
6.786
274682WAUKEGAN ;7U
Adder
8.741
946671AF1-331 GEN
Solar/Wind Harmer
0.359
274855GSG-6 ;RU
Solar/Wind Harmer
0.123
274850MENDOTA H;RU
Solar/Wind Harmer
0.039
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.112
959091AF2-200 GEN
Solar/Wind Harmer
6.717
270063AE2-323 C
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.439
274767LEE CO EC;8U
Adder
4.387
270505AE1-170 C O1
Solar/Wind Harmer
3.482
945111AF1-176 GEN
Solar/Wind Harmer
2.686
965931AG1-462 GEN
Solar/Wind Harmer
8.333
971087AG2-675 GEN
Solar/Wind Harmer
1.743
965021AG1-366 GEN
Solar/Wind Harmer
1.012
252524AE2-267 GEN
Solar/Wind Helper
1.058
960071AF2-298 GEN
Solar/Wind Helper
0.562
253394AE2-221_GEN
Solar/Wind Helper
1.605
252507AC2-088 GEN
Solar/Wind Helper
1.361
276820AF1-078_GEN
Solar/Wind Helper
0.471
270367AC2-061_GEN
Solar/Wind Helper
1.959
270186AC1-089 GEN
Solar/Wind Helper
0.816
270518AE2-148 GEN
Solar/Wind Helper
8.492
253325AC1-069 GEN
Solar/Wind Helper
0.605
24726405LAWG1A
50/50
3.345
961171AF2-408 GEN
50/50
9.629
24728605AND G2
50/50
3.447
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.823
970773AG2-487 GEN
Solar/Wind Harmer
1.792
270005AE1-210 C O1
Solar/Wind Harmer
1.847
945371AF1-202 GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.617
958861AF2-177 GEN
Solar/Wind Harmer
3.107
965651AG1-433 GEN
Solar/Wind Harmer
2.041
276903AD2-071 C
Solar/Wind Harmer
7.229
270594AE1-207 GEN
Solar/Wind Harmer
7.11
270032AE2-172
Solar/Wind Harmer
4.232
270024AE2-089 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
9.25
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.534
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.671
958381AF2-132 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.43
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.9
276621W2-048 GEN
Solar/Wind Harmer
0.174
939401AE1-172 GEN
Solar/Wind Harmer
2.598
274773LINCOLN ;4U
Adder
4.193
274774LINCOLN ;5U
Adder
4.193
941551AE2-152 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.691
274723RIVER EC ;12
Adder
8.866
274751CRETE EC ;1U
Adder
4.076
274754CRETE EC ;4U
Adder
4.076
274812UNIV PK N;8U
Adder
2.475
274802UNIV PARK;5U
Adder
2.879
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.1
274674JOLIET 9 ;6U
Adder
7.581
274676JOLIET 29;8U
Adder
15.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.556
274861TOP CROP ;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.792
274745AC1-111 GEN9
Adder
2.736
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.398
970569AG2-363 GEN
Solar/Wind Harmer
10.179
274682WAUKEGAN ;7U
Adder
8.741
274828WAUKEGAN ;BP
Adder
5.369
962781AG1-127 GEN
Solar/Wind Harmer
3.219
274872LEEDK;1U
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.133
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.074
957471AF2-041 GEN
Solar/Wind Harmer
10.076
959081AF2-199 GEN
Solar/Wind Harmer
3.359
971067AG2-660 GEN
Solar/Wind Harmer
1.12
970091AG2-072 GEN
Adder
36.89
274822ROCKFORD ;11
Adder
9.422
970819AG2-516 GEN
Solar/Wind Harmer
4.01
276708O09 GEN2
Solar/Wind Harmer
0.118
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.439
274766LEE CO EC;7U
Adder
4.387
957891AF2-083 GEN
Solar/Wind Harmer
5.533
945111AF1-176 GEN
Solar/Wind Harmer
5.913
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.71
965011AG1-365 GEN
Solar/Wind Harmer
3.036
252510AF1-249 C
Solar/Wind Helper
0.649
253398AE2-221_GEN2
Solar/Wind Helper
1.605
253333AC1-068 GEN
Solar/Wind Helper
0.605
25194708EBND2
50/50
6.282
24729405KEY G3
50/50
0.34
24729305KEY G2
50/50
0.334
24729205KEY G1
50/50
0.332
247621Y3-024
50/50
0.2
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.465
960971AF2-388 GEN
Solar/Wind Harmer
4.082
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.665
270599AE1-208 GEN
Solar/Wind Harmer
6.109
270383AD1-128 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.047
964611AG1-324 GEN
Solar/Wind Harmer
0.476
270201AC2-176 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.777
970291AG2-192 GEN
Solar/Wind Harmer
0.359
942221AE2-234 GEN
Solar/Wind Harmer
2.113
970883AG2-550 GEN
Solar/Wind Harmer
4.953
970885AG2-551 GEN
Solar/Wind Harmer
1.651
945391AF1-204 GEN
Solar/Wind Harmer
4.4
970241AG2-163 GEN
Solar/Wind Harmer
2.28
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.427
971587AH1-292 GEN
Solar/Wind Harmer
2.74
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24728805RICHG1
Adder
1.91
24728905RICHG2
Adder
1.91
970349AG2-230 GEN
Solar/Wind Harmer
5.254
942111AE2-223 GEN
Solar/Wind Harmer
1.137
960611AF2-352 GEN
Solar/Wind Harmer
1.165
276615X2-022 GEN
Solar/Wind Harmer
0.036
276838X2-022 GEN2
Solar/Wind Harmer
0.196
274770LINCOLN ;1U
Adder
4.193
274771LINCOLN ;2U
Adder
4.193
276897AD1-100 C
Solar/Wind Harmer
8.649
965681AG1-436 GEN
Solar/Wind Harmer
4.321
965791AG1-447 GEN
Solar/Wind Harmer
3.169
276916AD2-100_GEN
Solar/Wind Harmer
7.252
276911AD2-131_GEN
Solar/Wind Harmer
0.478
274888KELLY CRK;1U
Solar/Wind Harmer
0.201
276776AD2-060 GEN
Solar/Wind Harmer
0.368
958011AF2-095 GEN
Solar/Wind Harmer
4.968
970941AG2-585 GEN
Solar/Wind Harmer
1.898
274805UNIV PK N;1U
Adder
2.48
274808UNIV PK N;4U
Adder
2.464
276893AG1-478 C
Solar/Wind Harmer
0.229
274674JOLIET 9 ;6U
Adder
7.581
276901AD2-066 C O1
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
5.132
958491AF2-143 GEN
Solar/Wind Harmer
5.119
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.549
274695ROCKY RD ;2P
Adder
5.421
274693ROCKY RD ;1P
Adder
5.368
274697ROCKY RD ;3P
Adder
1.473
274683WAUKEGAN ;8U
Adder
10.242
274683WAUKEGAN ;8U
Adder
8.634
962691AG1-118 GEN
Solar/Wind Harmer
10.16
276645AC1-214 GEN1
Solar/Wind Harmer
0.133
971341AH1-150 GEN
Solar/Wind Harmer
6.717
971343AH1-151 GEN
Solar/Wind Harmer
6.717
972235AH1-702 GEN1
Adder
1.209
972236AH1-702 GEN2
Adder
1.051
247620Y3-023
Adder
0.221
938861AE1-114 GEN
Solar/Wind Harmer
1.89
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.537
274764LEE CO EC;5U
Adder
4.449
274765LEE CO EC;6U
Adder
4.449
274762LEE CO EC;3U
Adder
4.439
274763LEE CO EC;4U
Adder
4.397
961051AF2-396 GEN
Solar/Wind Harmer
6.579
961051AF2-396 GEN
Solar/Wind Harmer
4.386
25183208HLCRTG
Solar/Wind Helper
2.475
252509AD1-136 GEN
Solar/Wind Helper
0.194
253378AE2-206_GEN
Solar/Wind Helper
1.008
962581AG1-107 GEN
Solar/Wind Helper
1.008
961491AF2-440 GEN
Solar/Wind Helper
0.041
253349AC2-067 GEN
Solar/Wind Helper
0.267
253400AC2-068 GEN
Solar/Wind Helper
0.107
253415AE1-040 GEN
Solar/Wind Helper
0.551
253383AE2-342_GEN
Solar/Wind Helper
0.473
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.525
NYPJM->LTFIMP_NY
CLTF
0.654
LGEELTFEXP_LGEE->PJM
CLTF
1.45
WECLTFEXP_WEC->PJM
CLTF
1.827
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.493
MECLTFEXP_MEC->PJM
CLTF
7.337
SIGELTFEXP_SIGE->PJM
CLTF
0.239
LAGNLTFEXP_LAGN->PJM
CLTF
4.89
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.583
TVALTFEXP_TVA->PJM
CLTF
1.97

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2185.8
MW Contribution:
2.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.083
24803206KYGER 4HP
50/50
4.079
252516AE2-318_GEN
Solar/Wind Harmer
8.283
25196808ZIMRHP
Adder
79.38
25194608D.CRK4
Adder
1.689
252510AF1-249 C
Solar/Wind Harmer
0.054
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.986
25196008MFTGT1
Adder
1.369
253398AE2-221_GEN2
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.031
270273AD2-016 GEN
Solar/Wind Harmer
0.594
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
25326309TAIT D
Adder
0.844
3429421JKCT 10G
Adder
6.396
970773AG2-487 GEN
Solar/Wind Harmer
0.939
3429241JKCT 3G
Adder
8.835
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.76
270005AE1-210 C O1
Solar/Wind Harmer
1.04
24728605AND G2
Adder
2.628
970825AG2-519 GEN
Solar/Wind Harmer
1.683
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
5.07
270594AE1-207 GEN
Solar/Wind Harmer
5.019
270032AE2-172
Solar/Wind Harmer
2.988
958861AF2-177 GEN
Solar/Wind Harmer
1.919
965651AG1-433 GEN
Solar/Wind Harmer
1.282
270024AE2-089 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.063
970091AG2-072 GEN
Adder
45.503
253333AC1-068 GEN
Solar/Wind Harmer
0.005
963741AG1-226 GEN
Solar/Wind Harmer
9.274
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
964901AG1-354 GEN
Solar/Wind Harmer
5.594
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.628
276621W2-048 GEN
Solar/Wind Harmer
0.183
965911AG1-460 GEN
Solar/Wind Harmer
0.732
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.756
958381AF2-132 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
5.074
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.536
939401AE1-172 GEN
Solar/Wind Harmer
2.672
941551AE2-152 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
4.277
274774LINCOLN ;5U
Adder
4.277
971997AH1-543 GEN
Solar/Wind Harmer
1.853
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.311
274674JOLIET 9 ;6U
Adder
7.779
276694AA1-018 GEN2
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
10.575
274802UNIV PARK;5U
Adder
2.945
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.411
276646AC1-214 GEN2
Solar/Wind Harmer
0.138
274848CAMPGROVE;RU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.488
274812UNIV PK N;8U
Adder
2.528
274723RIVER EC ;12
Adder
9.04
274751CRETE EC ;1U
Adder
4.155
274754CRETE EC ;4U
Adder
4.155
274745AC1-111 GEN9
Adder
2.817
962781AG1-127 GEN
Solar/Wind Harmer
3.332
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
10.473
959081AF2-199 GEN
Solar/Wind Harmer
3.491
971067AG2-660 GEN
Solar/Wind Harmer
1.164
276708O09 GEN2
Solar/Wind Harmer
0.123
970819AG2-516 GEN
Solar/Wind Harmer
4.177
274858EASY ROAD;U2
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
5.58
945111AF1-176 GEN
Solar/Wind Harmer
5.962
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.73
965011AG1-365 GEN
Solar/Wind Harmer
3.232
960001AF2-291 GEN
Solar/Wind Helper
1.722
270331AC1-082 GEN3
Solar/Wind Helper
0.193
235780M24_1
Solar/Wind Helper
0.496
24803106KYGER 3LP
50/50
2.43
24803306KYGER 4LP
50/50
2.38
971191AH1-055 GEN
Solar/Wind Harmer
68.684
252507AC2-088 GEN
Solar/Wind Harmer
0.357
252519AF1-045_GEN
Solar/Wind Harmer
3.858
25194608D.CRK4
Adder
1.689
25196608WSDLE5
Adder
8.798
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.081
25196008MFTGT1
Adder
1.326
958171AF2-111 GEN
Solar/Wind Harmer
17.024
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.127
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
970191AG2-125 GEN
Solar/Wind Harmer
1.385
3429391JKCT 9G
Adder
6.396
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.143
270004AE1-209 GEN
Solar/Wind Harmer
1.04
24728705AND G3
Adder
5.496
24728505AND G1
Adder
2.628
946031AF1-268 GEN
Solar/Wind Harmer
4.524
970825AG2-519 GEN
Solar/Wind Harmer
3.571
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.92
970455AG2-298 GEN
Solar/Wind Harmer
1.776
970289AG2-191 GEN
Solar/Wind Harmer
0.483
247642Z2-115 C
Solar/Wind Harmer
0.002
970653AG2-424 GEN
Solar/Wind Harmer
0.428
944531AF1-118 GEN
Solar/Wind Harmer
18.504
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970193AG2-126 GEN
Solar/Wind Harmer
6.094
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.775
270518AE2-148 GEN
Solar/Wind Harmer
0.304
971993AH1-541 GEN
Solar/Wind Harmer
1.694
942481AE2-261 GEN
Solar/Wind Harmer
10.95
957381AF2-032 GEN
Solar/Wind Harmer
0.83
964401AG1-302 GEN
Solar/Wind Harmer
0
972273AH1-721 GEN
Adder
43.369
965091AG1-374 GEN
Solar/Wind Harmer
10.891
959611AF2-252 GEN
Solar/Wind Harmer
1.21
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
4.277
274887GEN-1.85
Solar/Wind Harmer
0.092
276843GEN-1.7
Solar/Wind Harmer
0.114
276806AD2-047 C O1
Solar/Wind Harmer
2.001
972259AH1-714 GEN
Adder
9.653
274729ELWOOD EC;1P
Adder
8.311
274730ELWOOD EC;6P
Adder
8.311
274734ELWOOD EC;8P
Adder
8.311
274736ELWOOD EC;9P
Adder
8.311
970707AG2-453 GEN
Solar/Wind Harmer
11.521
270043AE2-236 GEN
Solar/Wind Harmer
2.263
972038AH1-567 GEN2
Adder
0.184
970571AG2-364 GEN
Solar/Wind Harmer
7.05
274803UNIV PARK;6U
Adder
2.945
276868AE1-113 GEN
Solar/Wind Harmer
0.705
274879MINONK ;1U
Solar/Wind Harmer
0.147
274862TOP CROP ;2U
Solar/Wind Harmer
0.476
274826FISK ;BP
Adder
5.528
274676JOLIET 29;8U
Adder
14.935
274814UNIV PK N;0U
Adder
2.55
274807UNIV PK N;3U
Adder
2.544
274811UNIV PK N;7U
Adder
2.528
274724RIVER EC ;11
Adder
8.935
274752CRETE EC ;2U
Adder
4.155
274753CRETE EC ;3U
Adder
4.155
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
943121AE2-341 GEN
Solar/Wind Harmer
5.893
943591AF1-030 GEN
Solar/Wind Harmer
3.919
274682WAUKEGAN ;7U
Adder
5.301
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
959091AF2-200 GEN
Solar/Wind Harmer
6.982
971347AH1-153 GEN
Solar/Wind Harmer
1.745
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
8.801
971087AG2-675 GEN
Solar/Wind Harmer
1.841
270063AE2-323 C
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
3.511
945111AF1-176 GEN
Solar/Wind Harmer
2.708
965021AG1-366 GEN
Solar/Wind Harmer
1.077
270330AC1-082 GEN2
Solar/Wind Helper
0.194
270329AC1-082 GEN1
Solar/Wind Helper
0.194
24802606KYGER 1HP
50/50
4.156
24802706KYGER 1LP
50/50
2.437
24803506KYGER 5LP
50/50
2.38
971985AH1-537 GEN
Solar/Wind Harmer
5.763
25196408WSDLE3
Adder
9.057
25196308WSDLE2
Adder
8.978
25196208WSDLE1
Adder
8.956
25196708WSDLE6
Adder
8.933
25196508WSDLE4
Adder
8.708
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.401
972163AH1-664 GEN
Solar/Wind Harmer
7.027
972165AH1-665 GEN
Solar/Wind Harmer
5.628
253406AD2-031_GEN
Solar/Wind Harmer
0.458
339216AC1-074 GEN
Solar/Wind Harmer
0.162
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.58
253372AE2-315 SEC3
Adder
1.514
253372AE2-315 SEC3
Adder
1.514
25306009OHH W.
Adder
2.27
270356AE2-297 GEN
Solar/Wind Harmer
0
3429211JKCT 2G
Adder
8.721
971029AG2-637 GEN
Solar/Wind Harmer
7.57
270543AE2-219 C
Solar/Wind Harmer
3.433
247536S-71 GEN
Solar/Wind Harmer
0.191
964611AG1-324 GEN
Solar/Wind Harmer
1.811
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.738
270432AC2-029 GEN
Solar/Wind Harmer
2.001
241972AD1-140 GEN
Solar/Wind Harmer
0.484
970289AG2-191 GEN
Solar/Wind Harmer
0.834
24729505KEY G4
Adder
3.899
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.68
24386405FR-21G C
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.053
270071AF1-092 GEN
Solar/Wind Harmer
7.11
971611AH1-305 GEN
Solar/Wind Harmer
2.204
959141AF2-205 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.16
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.144
276848AB2-070 GEN3
Solar/Wind Harmer
0.143
276849AB2-070 GEN2
Solar/Wind Harmer
0.144
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.806
970169AG2-114 GEN
Solar/Wind Harmer
3.591
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
4.277
274776LINCOLN ;7U
Adder
4.277
274777LINCOLN ;8U
Adder
4.277
926823AC1-168 GEN
Solar/Wind Harmer
0.6
972228AH1-698 GEN2
Adder
1.875
972227AH1-698 GEN1
Adder
1.321
970833AG2-524 GEN
Solar/Wind Harmer
3.884
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.53
274728ELWOOD EC;5P
Adder
8.311
274731ELWOOD EC;2P
Adder
8.311
274733ELWOOD EC;3P
Adder
8.311
274735ELWOOD EC;4P
Adder
8.311
274800UNIV PARK;3U
Adder
2.946
274801UNIV PARK;4U
Adder
2.946
970073AG2-061 GEN
Solar/Wind Harmer
1.175
972037AH1-567 GEN1
Adder
0.092
274827FISK ;RP
Adder
3.918
274675JOLIET 29;7U
Adder
15.488
274675JOLIET 29;7U
Adder
14.935
274687WILL CNTY;4U
Adder
14.106
274687WILL CNTY;4U
Adder
14.106
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
274744AC1-111 GEN8
Adder
2.817
274746AC1-111 G10
Adder
2.817
276861AD2-134 GEN
Solar/Wind Harmer
0.062
276863AD2-134 GEN
Solar/Wind Harmer
0.062
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971411AH1-196 GEN
Solar/Wind Harmer
5.237
971171AH1-044 GEN
Solar/Wind Harmer
6.982
960681AF2-359 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.123
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
971681AH1-341 GEN
Solar/Wind Harmer
5.605
946321AF1-296 GEN
Solar/Wind Harmer
1.935
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.411
970031AG2-029 GEN
Solar/Wind Harmer
1.822
959331AF2-224 GEN
Solar/Wind Harmer
2.262
965041AG1-368 GEN
Solar/Wind Harmer
3.099
247521TR3_G114
Solar/Wind Harmer
0.11
965051AG1-369 GEN
Solar/Wind Harmer
1.514
945631AF1-228 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
6.245
24803006KYGER 3HP
50/50
4.127
24802806KYGER 2HP
50/50
4.111
24802906KYGER 2LP
50/50
2.413
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.768
25194508D.CRK3
Adder
1.452
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.516
972045AH1-571 GEN
Solar/Wind Harmer
1.214
270269AC2-059
Solar/Wind Harmer
0
971125AH1-004 GEN
Solar/Wind Harmer
2.245
970107AG2-081 GEN
Solar/Wind Harmer
1.684
253370AE2-315 SEC1
Adder
1.601
24728805RICHG1
Adder
2.955
24728905RICHG2
Adder
2.955
25322209TAIT E
Adder
7.522
25322209TAIT E
Adder
7.353
25326109MON D
Adder
0.984
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.111
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.905
970885AG2-551 GEN
Solar/Wind Harmer
1.635
247621Y3-024
Adder
0.162
964611AG1-324 GEN
Solar/Wind Harmer
0.348
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
2.485
270599AE1-208 GEN
Solar/Wind Harmer
4.141
971613AH1-306 GEN
Solar/Wind Harmer
2.151
964571AG1-320 GEN
Solar/Wind Harmer
4.079
970291AG2-192 GEN
Solar/Wind Harmer
0.57
970291AG2-192 GEN
Solar/Wind Harmer
0.263
944541AF1-119 GEN
Solar/Wind Harmer
0.292
960971AF2-388 GEN
Solar/Wind Harmer
2.564
942221AE2-234 GEN
Solar/Wind Harmer
1.655
971587AH1-292 GEN
Solar/Wind Harmer
2.993
945391AF1-204 GEN
Solar/Wind Harmer
4.316
970241AG2-163 GEN
Solar/Wind Harmer
2.286
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.434
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
7.7
276911AD2-131_GEN
Solar/Wind Harmer
0.507
276615X2-022 GEN
Solar/Wind Harmer
0.038
276838X2-022 GEN2
Solar/Wind Harmer
0.206
25326509SID D
Adder
0.689
960611AF2-352 GEN
Solar/Wind Harmer
1.21
942111AE2-223 GEN
Solar/Wind Harmer
1.178
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
8.857
274770LINCOLN ;1U
Adder
4.277
274771LINCOLN ;2U
Adder
4.277
276901AD2-066 C O1
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.206
276776AD2-060 GEN
Solar/Wind Harmer
0.377
958011AF2-095 GEN
Solar/Wind Harmer
5.084
970941AG2-585 GEN
Solar/Wind Harmer
1.942
276893AG1-478 C
Solar/Wind Harmer
0.235
274674JOLIET 9 ;6U
Adder
7.779
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
5.287
958491AF2-143 GEN
Solar/Wind Harmer
5.287
276645AC1-214 GEN1
Solar/Wind Harmer
0.138
274805UNIV PK N;1U
Adder
2.533
274808UNIV PK N;4U
Adder
2.517
274696ROCKY RD ;4P
Adder
5.728
274695ROCKY RD ;2P
Adder
5.596
274693ROCKY RD ;1P
Adder
5.541
274697ROCKY RD ;3P
Adder
1.52
962691AG1-118 GEN
Solar/Wind Harmer
10.508
964781AG1-341 GEN
Solar/Wind Harmer
3.705
971341AH1-150 GEN
Solar/Wind Harmer
6.982
971343AH1-151 GEN
Solar/Wind Harmer
6.982
970349AG2-230 GEN
Solar/Wind Harmer
5.234
965681AG1-436 GEN
Solar/Wind Harmer
4.361
965791AG1-447 GEN
Solar/Wind Harmer
3.198
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.562
938861AE1-114 GEN
Solar/Wind Harmer
1.972
970329AG2-216 GEN
Solar/Wind Harmer
1.444
961051AF2-396 GEN
Solar/Wind Harmer
6.65
961051AF2-396 GEN
Solar/Wind Harmer
4.433
971485AH1-239 GEN
Solar/Wind Harmer
2.603
966021AG1-471 GEN
Solar/Wind Harmer
1.739
270246TR4_N_V150
Solar/Wind Harmer
0.019
270247TR4_N_V136
Solar/Wind Harmer
0.019
237033AB1-150 GEN
Solar/Wind Helper
0.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.393
NYPJM->LTFIMP_NY
CLTF
1.666
LGEELTFEXP_LGEE->PJM
CLTF
5.14
WECLTFEXP_WEC->PJM
CLTF
1.904
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.289
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.044
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.317
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.627
MECLTFEXP_MEC->PJM
CLTF
8.009
SIGELTFEXP_SIGE->PJM
CLTF
0.331
LAGNLTFEXP_LAGN->PJM
CLTF
6.552
TVALTFEXP_TVA->PJM
CLTF
3.106

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.27 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2052.4
MW Contribution:
2.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.46
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
70.432
252507AC2-088 GEN
Solar/Wind Harmer
0.376
252519AF1-045_GEN
Solar/Wind Harmer
4.074
25194608D.CRK4
Adder
1.776
25196608WSDLE5
Adder
9.253
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.717
958171AF2-111 GEN
Solar/Wind Harmer
17.947
25196008MFTGT1
Adder
1.385
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.382
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
970191AG2-125 GEN
Solar/Wind Harmer
1.47
3429391JKCT 9G
Adder
6.589
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.224
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970455AG2-298 GEN
Solar/Wind Harmer
1.797
270004AE1-209 GEN
Solar/Wind Harmer
0.992
946031AF1-268 GEN
Solar/Wind Harmer
4.337
970825AG2-519 GEN
Solar/Wind Harmer
3.419
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.615
970653AG2-424 GEN
Solar/Wind Harmer
0.429
270518AE2-148 GEN
Solar/Wind Harmer
0.348
970289AG2-191 GEN
Solar/Wind Harmer
0.457
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
5.894
944531AF1-118 GEN
Solar/Wind Harmer
16.286
24386205FR-12G C
Solar/Wind Harmer
0
972273AH1-721 GEN
Adder
42.335
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.495
942481AE2-261 GEN
Solar/Wind Harmer
10.146
957381AF2-032 GEN
Solar/Wind Harmer
0.768
971993AH1-541 GEN
Solar/Wind Harmer
1.554
964401AG1-302 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
9.828
959611AF2-252 GEN
Solar/Wind Harmer
1.092
274878BISHOP HL;2U
Solar/Wind Harmer
0.104
276782AC1-033 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.202
942051AE2-217 GEN
Solar/Wind Harmer
5.57
276868AE1-113 GEN
Solar/Wind Harmer
0.616
274879MINONK ;1U
Solar/Wind Harmer
0.129
939351AE1-166 GEN
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.415
274729ELWOOD EC;1P
Adder
7.204
274730ELWOOD EC;6P
Adder
7.204
274734ELWOOD EC;8P
Adder
7.204
274736ELWOOD EC;9P
Adder
7.204
274887GEN-1.85
Solar/Wind Harmer
0.079
276843GEN-1.7
Solar/Wind Harmer
0.099
276806AD2-047 C O1
Solar/Wind Harmer
1.73
972259AH1-714 GEN
Adder
8.342
274676JOLIET 29;8U
Adder
12.928
972038AH1-567 GEN2
Adder
0.159
274803UNIV PARK;6U
Adder
2.546
274855GSG-6 ;RU
Solar/Wind Harmer
0.111
274850MENDOTA H;RU
Solar/Wind Harmer
0.035
946671AF1-331 GEN
Solar/Wind Harmer
0.325
959091AF2-200 GEN
Solar/Wind Harmer
6.093
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
7.765
274760LEE CO EC;1U
Adder
4.061
274767LEE CO EC;8U
Adder
4.013
971087AG2-675 GEN
Solar/Wind Harmer
1.624
274826FISK ;BP
Adder
4.777
943121AE2-341 GEN
Solar/Wind Harmer
5.104
943591AF1-030 GEN
Solar/Wind Harmer
3.394
274682WAUKEGAN ;7U
Adder
7.839
970707AG2-453 GEN
Solar/Wind Harmer
9.937
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24802606KYGER 1HP
50/50
4.207
24802706KYGER 1LP
50/50
2.467
24803506KYGER 5LP
50/50
2.41
971985AH1-537 GEN
Solar/Wind Harmer
5.9
25196408WSDLE3
Adder
9.526
25196308WSDLE2
Adder
9.443
25196208WSDLE1
Adder
9.419
25196708WSDLE6
Adder
9.395
25196508WSDLE4
Adder
9.159
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
253406AD2-031_GEN
Solar/Wind Harmer
0.493
972163AH1-664 GEN
Solar/Wind Harmer
7.368
972165AH1-665 GEN
Solar/Wind Harmer
5.901
270263AC1-001 GEN
Solar/Wind Harmer
0.65
270340AC2-060 GEN
Solar/Wind Harmer
0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.169
253372AE2-315 SEC3
Adder
1.623
253372AE2-315 SEC3
Adder
1.623
25306009OHH W.
Adder
2.424
3429211JKCT 2G
Adder
8.956
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.299
971029AG2-637 GEN
Solar/Wind Harmer
7.492
241972AD1-140 GEN
Solar/Wind Harmer
0.535
270543AE2-219 C
Solar/Wind Harmer
3.362
247536S-71 GEN
Solar/Wind Harmer
0.185
964611AG1-324 GEN
Solar/Wind Harmer
1.732
971609AH1-304 GEN
Solar/Wind Harmer
0.694
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.79
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.463
963841AG1-237 GEN
Solar/Wind Harmer
1.583
945631AF1-228 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.02
963791AG1-232 GEN
Solar/Wind Harmer
4.554
971611AH1-305 GEN
Solar/Wind Harmer
2.005
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.132
276848AB2-070 GEN3
Solar/Wind Harmer
0.132
276849AB2-070 GEN2
Solar/Wind Harmer
0.132
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.273
943851AF1-053 GEN
Solar/Wind Harmer
0.882
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.418
270071AF1-092 GEN
Solar/Wind Harmer
6.13
970169AG2-114 GEN
Solar/Wind Harmer
3.185
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.104
926823AC1-168 GEN
Solar/Wind Harmer
0.529
970073AG2-061 GEN
Solar/Wind Harmer
1.026
276741O09 GEN1
Solar/Wind Harmer
0.108
970833AG2-524 GEN
Solar/Wind Harmer
3.368
970833AG2-524 GEN
Solar/Wind Harmer
2.246
274728ELWOOD EC;5P
Adder
7.204
274731ELWOOD EC;2P
Adder
7.204
274733ELWOOD EC;3P
Adder
7.204
274735ELWOOD EC;4P
Adder
7.204
972227AH1-698 GEN1
Adder
1.143
972228AH1-698 GEN2
Adder
1.623
960591AF2-350 GEN
Solar/Wind Harmer
3.054
274675JOLIET 29;7U
Adder
13.407
274675JOLIET 29;7U
Adder
12.928
274687WILL CNTY;4U
Adder
12.208
274687WILL CNTY;4U
Adder
12.208
274800UNIV PARK;3U
Adder
2.547
274801UNIV PARK;4U
Adder
2.547
971681AH1-341 GEN
Solar/Wind Harmer
4.906
274744AC1-111 GEN8
Adder
2.441
274746AC1-111 G10
Adder
2.441
972267AH1-718 GEN
Adder
1.819
972037AH1-567 GEN1
Adder
0.08
276861AD2-134 GEN
Solar/Wind Harmer
0.054
276863AD2-134 GEN
Solar/Wind Harmer
0.054
971171AH1-044 GEN
Solar/Wind Harmer
6.093
971675AH1-338 GEN
Solar/Wind Harmer
1.188
946321AF1-296 GEN
Solar/Wind Harmer
1.706
274827FISK ;RP
Adder
3.386
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
971411AH1-196 GEN
Solar/Wind Harmer
4.564
24803006KYGER 3HP
50/50
4.179
24802806KYGER 2HP
50/50
4.162
24802906KYGER 2LP
50/50
2.443
25183008BIOENL
50/50
0.032
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
8.168
25194508D.CRK3
Adder
1.527
270269AC2-059
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.575
972045AH1-571 GEN
Solar/Wind Harmer
1.262
253370AE2-315 SEC1
Adder
1.716
971125AH1-004 GEN
Solar/Wind Harmer
2.323
970107AG2-081 GEN
Solar/Wind Harmer
1.743
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252516AE2-318_GEN
Solar/Wind Harmer
8.746
25196808ZIMRHP
Adder
83.622
25194608D.CRK4
Adder
1.776
252510AF1-249 C
Solar/Wind Harmer
0.057
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.475
25196008MFTGT1
Adder
1.43
253398AE2-221_GEN2
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.627
270273AD2-016 GEN
Solar/Wind Harmer
0.667
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
25326309TAIT D
Adder
0.906
3429421JKCT 10G
Adder
6.589
3429241JKCT 3G
Adder
9.074
970773AG2-487 GEN
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.658
24728605AND G2
Adder
2.584
253333AC1-068 GEN
Solar/Wind Harmer
0.005
270005AE1-210 C O1
Solar/Wind Harmer
0.992
970825AG2-519 GEN
Solar/Wind Harmer
1.611
970091AG2-072 GEN
Adder
49.338
276903AD2-071 C
Solar/Wind Harmer
4.853
970653AG2-424 GEN
Solar/Wind Harmer
2.069
270594AE1-207 GEN
Solar/Wind Harmer
4.771
270032AE2-172
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.758
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.166
963741AG1-226 GEN
Solar/Wind Harmer
8.794
972203AH1-686 GEN
Adder
1.223
964901AG1-354 GEN
Solar/Wind Harmer
5.49
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276621W2-048 GEN
Solar/Wind Harmer
0.169
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.21
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.274
958381AF2-132 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.558
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.636
939401AE1-172 GEN
Solar/Wind Harmer
2.347
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.122
970569AG2-363 GEN
Solar/Wind Harmer
9.303
971997AH1-543 GEN
Solar/Wind Harmer
1.622
276882AE2-255 GEN
Solar/Wind Harmer
0.36
276805AD2-038 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.499
276708O09 GEN2
Solar/Wind Harmer
0.108
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.204
274674JOLIET 9 ;6U
Adder
6.739
274676JOLIET 29;8U
Adder
13.407
274802UNIV PARK;5U
Adder
2.546
274745AC1-111 GEN9
Adder
2.441
957471AF2-041 GEN
Solar/Wind Harmer
9.139
959081AF2-199 GEN
Solar/Wind Harmer
3.046
971067AG2-660 GEN
Solar/Wind Harmer
1.015
274872LEEDK;1U
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.061
274766LEE CO EC;7U
Adder
4.013
962781AG1-127 GEN
Solar/Wind Harmer
2.898
274682WAUKEGAN ;7U
Adder
7.839
274828WAUKEGAN ;BP
Adder
4.817
274822ROCKFORD ;11
Adder
2.437
970819AG2-516 GEN
Solar/Wind Harmer
3.649
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.501
25322209TAIT E
Adder
8.074
25322209TAIT E
Adder
7.893
25326109MON D
Adder
1.062
24728805RICHG1
Adder
2.987
24728905RICHG2
Adder
2.987
942891AE2-308 GEN
Solar/Wind Harmer
5.239
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.803
970885AG2-551 GEN
Solar/Wind Harmer
1.601
247621Y3-024
Adder
0.156
964571AG1-320 GEN
Solar/Wind Harmer
4.114
964611AG1-324 GEN
Solar/Wind Harmer
0.333
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
2.045
270031AE2-169
Solar/Wind Harmer
2.337
270599AE1-208 GEN
Solar/Wind Harmer
3.895
970291AG2-192 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.25
971587AH1-292 GEN
Solar/Wind Harmer
3.03
25326509SID D
Adder
0.755
944541AF1-119 GEN
Solar/Wind Harmer
0.265
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.175
942221AE2-234 GEN
Solar/Wind Harmer
1.514
970329AG2-216 GEN
Solar/Wind Harmer
1.606
970241AG2-163 GEN
Solar/Wind Harmer
2.168
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.406
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
7.149
276911AD2-131_GEN
Solar/Wind Harmer
0.471
964781AG1-341 GEN
Solar/Wind Harmer
3.596
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.19
942861AE2-305 GEN
Solar/Wind Harmer
2.579
960611AF2-352 GEN
Solar/Wind Harmer
1.092
942111AE2-223 GEN
Solar/Wind Harmer
1.058
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.122
971485AH1-239 GEN
Solar/Wind Harmer
2.492
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.619
966021AG1-471 GEN
Solar/Wind Harmer
1.662
276897AD1-100 C
Solar/Wind Harmer
7.68
958481AF2-142 GEN
Solar/Wind Harmer
4.605
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.494
276893AG1-478 C
Solar/Wind Harmer
0.204
274888KELLY CRK;1U
Solar/Wind Harmer
0.178
276776AD2-060 GEN
Solar/Wind Harmer
0.326
958011AF2-095 GEN
Solar/Wind Harmer
4.397
274674JOLIET 9 ;6U
Adder
6.739
970941AG2-585 GEN
Solar/Wind Harmer
1.679
971341AH1-150 GEN
Solar/Wind Harmer
6.093
971343AH1-151 GEN
Solar/Wind Harmer
6.093
938861AE1-114 GEN
Solar/Wind Harmer
1.726
962691AG1-118 GEN
Solar/Wind Harmer
9.136
274764LEE CO EC;5U
Adder
4.07
274765LEE CO EC;6U
Adder
4.07
274762LEE CO EC;3U
Adder
4.061
274763LEE CO EC;4U
Adder
4.023
274696ROCKY RD ;4P
Adder
4.974
274695ROCKY RD ;2P
Adder
4.859
274693ROCKY RD ;1P
Adder
4.811
274697ROCKY RD ;3P
Adder
1.32
274683WAUKEGAN ;8U
Adder
9.19
274683WAUKEGAN ;8U
Adder
7.747
972235AH1-702 GEN1
Adder
1.099
972236AH1-702 GEN2
Adder
0.956
237033AB1-150 GEN
Solar/Wind Helper
0.404
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.865
NYPJM->LTFIMP_NY
CLTF
1.597
LGEELTFEXP_LGEE->PJM
CLTF
5.305
WECLTFEXP_WEC->PJM
CLTF
1.662
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.274
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.431
MECLTFEXP_MEC->PJM
CLTF
7.137
SIGELTFEXP_SIGE->PJM
CLTF
0.33
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
TVALTFEXP_TVA->PJM
CLTF
2.665

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.82 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2406.35
MW Contribution:
2.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.317
960861AF2-377 GEN
50/50
2.406
970521AG2-332 GEN
50/50
10.906
24639705ELKHART HY
50/50
0.151
270143AC1-141 CT2_
50/50
2.029
965421AG1-410 GEN
Solar/Wind Harmer
81.797
965011AG1-365 GEN
Solar/Wind Harmer
13.822
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.876
958861AF2-177 GEN
Solar/Wind Harmer
2.694
945111AF1-176 GEN
Solar/Wind Harmer
10.683
957891AF2-083 GEN
Solar/Wind Harmer
9.802
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3
970373AG2-245 GEN
Solar/Wind Harmer
11.243
274751CRETE EC ;1U
Adder
6.312
274754CRETE EC ;4U
Adder
6.312
274723RIVER EC ;12
Adder
13.681
274812UNIV PK N;8U
Adder
3.792
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.365
274774LINCOLN ;5U
Adder
6.365
274802UNIV PARK;5U
Adder
4.369
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.75
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.662
274674JOLIET 9 ;6U
Adder
11.348
274732ELWOOD EC;7P
Adder
12.11
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.364
270594AE1-207 GEN
Solar/Wind Harmer
5.699
270032AE2-172
Solar/Wind Harmer
3.392
270005AE1-210 C O1
Solar/Wind Harmer
1.101
274745AC1-111 GEN9
Adder
4.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.82
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.788
274682WAUKEGAN ;7U
Adder
12.933
274828WAUKEGAN ;BP
Adder
7.939
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.731
939401AE1-172 GEN
Solar/Wind Harmer
3.718
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.578
971997AH1-543 GEN
Solar/Wind Harmer
2.59
965431AG1-411 GEN
50/50
45.443
24727105RPMNG2
50/50
3.318
970583AG2-370 GEN
50/50
2.814
270142AC1-141 CT1_
50/50
2.029
24642205MAYFLWER
50/50
0.031
965021AG1-366 GEN
Solar/Wind Harmer
4.607
270043AE2-236 GEN
Solar/Wind Harmer
5.241
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.981
24695305TIMB G C
Solar/Wind Harmer
0.532
945111AF1-176 GEN
Solar/Wind Harmer
4.853
971347AH1-153 GEN
Solar/Wind Harmer
2.927
270505AE1-170 C O1
Solar/Wind Harmer
6.132
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.345
274752CRETE EC ;2U
Adder
6.312
274753CRETE EC ;3U
Adder
6.312
274724RIVER EC ;11
Adder
13.515
274814UNIV PK N;0U
Adder
3.826
274807UNIV PK N;3U
Adder
3.817
274811UNIV PK N;7U
Adder
3.792
274772LINCOLN ;3U
Adder
6.365
274803UNIV PARK;6U
Adder
4.369
274826FISK ;BP
Adder
8.195
972038AH1-567 GEN2
Adder
0.273
274887GEN-1.85
Solar/Wind Harmer
0.135
276843GEN-1.7
Solar/Wind Harmer
0.168
276806AD2-047 C O1
Solar/Wind Harmer
2.951
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.153
970707AG2-453 GEN
Solar/Wind Harmer
16.903
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.852
274729ELWOOD EC;1P
Adder
12.11
274730ELWOOD EC;6P
Adder
12.11
274734ELWOOD EC;8P
Adder
12.11
274736ELWOOD EC;9P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.564
946031AF1-268 GEN
Solar/Wind Harmer
4.838
943121AE2-341 GEN
Solar/Wind Harmer
8.518
943591AF1-030 GEN
Solar/Wind Harmer
5.665
270004AE1-209 GEN
Solar/Wind Harmer
1.101
274862TOP CROP ;2U
Solar/Wind Harmer
0.681
970825AG2-519 GEN
Solar/Wind Harmer
3.795
274682WAUKEGAN ;7U
Adder
12.933
276868AE1-113 GEN
Solar/Wind Harmer
0.991
274879MINONK ;1U
Solar/Wind Harmer
0.207
946671AF1-331 GEN
Solar/Wind Harmer
0.524
274855GSG-6 ;RU
Solar/Wind Harmer
0.179
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.895
959091AF2-200 GEN
Solar/Wind Harmer
9.768
970571AG2-364 GEN
Solar/Wind Harmer
9.675
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.381
274767LEE CO EC;8U
Adder
6.306
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
24727205RPMNG3
50/50
3.298
24729505KEY G4
50/50
6.847
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.792
959331AF2-224 GEN
Solar/Wind Harmer
9.676
963791AG1-232 GEN
Solar/Wind Harmer
12.035
970031AG2-029 GEN
Solar/Wind Harmer
4.587
965041AG1-368 GEN
Solar/Wind Harmer
8.443
270071AF1-092 GEN
Solar/Wind Harmer
14.566
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.602
971771AH1-392 GEN
Solar/Wind Harmer
5.907
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.922
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.13
274775LINCOLN ;6U
Adder
6.365
274776LINCOLN ;7U
Adder
6.365
274777LINCOLN ;8U
Adder
6.365
972037AH1-567 GEN1
Adder
0.137
274827FISK ;RP
Adder
5.808
274800UNIV PARK;3U
Adder
4.357
274801UNIV PARK;4U
Adder
4.357
960591AF2-350 GEN
Solar/Wind Harmer
5.207
972228AH1-698 GEN2
Adder
2.756
972227AH1-698 GEN1
Adder
1.941
274687WILL CNTY;4U
Adder
20.685
274687WILL CNTY;4U
Adder
20.685
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.662
274675JOLIET 29;7U
Adder
21.853
274728ELWOOD EC;5P
Adder
12.11
274731ELWOOD EC;2P
Adder
12.11
274733ELWOOD EC;3P
Adder
12.11
274735ELWOOD EC;4P
Adder
12.11
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.974
970833AG2-524 GEN
Solar/Wind Harmer
5.628
970833AG2-524 GEN
Solar/Wind Harmer
3.752
971611AH1-305 GEN
Solar/Wind Harmer
3.031
274744AC1-111 GEN8
Adder
4.068
274746AC1-111 G10
Adder
4.068
970073AG2-061 GEN
Solar/Wind Harmer
1.661
247536S-71 GEN
Solar/Wind Harmer
0.199
971411AH1-196 GEN
Solar/Wind Harmer
7.376
971675AH1-338 GEN
Solar/Wind Harmer
1.916
276861AD2-134 GEN
Solar/Wind Harmer
0.088
276863AD2-134 GEN
Solar/Wind Harmer
0.088
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.768
274823ROCKFORD ;21
Adder
13.596
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
926823AC1-168 GEN
Solar/Wind Harmer
0.821
970169AG2-114 GEN
Solar/Wind Harmer
4.823
971681AH1-341 GEN
Solar/Wind Harmer
7.736
971549AH1-272 GEN
Solar/Wind Harmer
9.898
972267AH1-718 GEN
Adder
2.828
276741O09 GEN1
Solar/Wind Harmer
0.167
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.157
24729405KEY G3
50/50
0.374
24729305KEY G2
50/50
0.367
24729205KEY G1
50/50
0.366
247620Y3-023
50/50
0.467
960851AF2-376 GEN
50/50
2.095
24643105BUCHANAN
50/50
0.01
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.855
944231AF1-091 GEN
Solar/Wind Harmer
16.139
944541AF1-119 GEN
Solar/Wind Harmer
0.427
960971AF2-388 GEN
Solar/Wind Harmer
3.752
970349AG2-230 GEN
Solar/Wind Harmer
8.78
961051AF2-396 GEN
Solar/Wind Harmer
11.674
961051AF2-396 GEN
Solar/Wind Harmer
7.782
270031AE2-169
Solar/Wind Harmer
3.104
270599AE1-208 GEN
Solar/Wind Harmer
5.173
965681AG1-436 GEN
Solar/Wind Harmer
6.963
965791AG1-447 GEN
Solar/Wind Harmer
5.106
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.41
247621Y3-024
Adder
0.183
274805UNIV PK N;1U
Adder
3.801
274808UNIV PK N;4U
Adder
3.776
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.365
274771LINCOLN ;2U
Adder
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
0.304
276776AD2-060 GEN
Solar/Wind Harmer
0.555
958011AF2-095 GEN
Solar/Wind Harmer
7.498
970941AG2-585 GEN
Solar/Wind Harmer
2.864
276897AD1-100 C
Solar/Wind Harmer
12.887
274674JOLIET 9 ;6U
Adder
11.348
276893AG1-478 C
Solar/Wind Harmer
0.343
970291AG2-192 GEN
Solar/Wind Harmer
0.666
970291AG2-192 GEN
Solar/Wind Harmer
0.308
971613AH1-306 GEN
Solar/Wind Harmer
2.442
958481AF2-142 GEN
Solar/Wind Harmer
7.57
274695ROCKY RD ;2P
Adder
8.016
274693ROCKY RD ;1P
Adder
7.937
274697ROCKY RD ;3P
Adder
2.178
274878BISHOP HL;2U
Solar/Wind Harmer
0.157
965091AG1-374 GEN
Solar/Wind Harmer
13.726
965931AG1-462 GEN
Solar/Wind Harmer
11.666
971087AG2-675 GEN
Solar/Wind Harmer
2.44
959611AF2-252 GEN
Solar/Wind Harmer
1.525
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.998
957381AF2-032 GEN
Solar/Wind Harmer
0.932
942481AE2-261 GEN
Solar/Wind Harmer
12.255
970193AG2-126 GEN
Solar/Wind Harmer
5.956
24728705AND G3
Adder
4.39
24728505AND G1
Adder
2.099
246938BC-WTG3
Solar/Wind Helper
11.083
942871AE2-306 GEN
Solar/Wind Helper
0.445
270284AF1-227 GEN1
Solar/Wind Helper
1.893
270287AF1-227 GEN3
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.334
270541AE2-072 C
Solar/Wind Helper
0.943
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.889
946321AF1-296 GEN
Solar/Wind Harmer
2.577
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.976
270543AE2-219 C
Solar/Wind Harmer
3.137
276668AB2-070 GEN1
Solar/Wind Harmer
0.17
276848AB2-070 GEN3
Solar/Wind Harmer
0.169
276849AB2-070 GEN2
Solar/Wind Harmer
0.17
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.928
944221AF1-090 GEN
Solar/Wind Harmer
2.312
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.609
270223U2-072_GEN1
Solar/Wind Helper
0.876
270224U2-072_GEN2
Solar/Wind Helper
0.876
270227U2-072_GEN3
Solar/Wind Helper
0.876
270228U2-072_GEN4
Solar/Wind Helper
0.876
270231U2-072_GEN5
Solar/Wind Helper
0.876
966831AG1-554 GEN
Solar/Wind Helper
0.882
270499AE1-146 GEN
Solar/Wind Helper
1.968
945641AF1-229 GEN
Solar/Wind Helper
0.94
274696ROCKY RD ;4P
Adder
8.205
274683WAUKEGAN ;8U
Adder
15.145
274683WAUKEGAN ;8U
Adder
12.766
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
14.951
958491AF2-143 GEN
Solar/Wind Harmer
7.476
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.768
971343AH1-151 GEN
Solar/Wind Harmer
9.768
972235AH1-702 GEN1
Adder
1.755
972236AH1-702 GEN2
Adder
1.526
938861AE1-114 GEN
Solar/Wind Harmer
2.722
274764LEE CO EC;5U
Adder
6.396
274765LEE CO EC;6U
Adder
6.396
274762LEE CO EC;3U
Adder
6.381
274763LEE CO EC;4U
Adder
6.321
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.763
276645AC1-214 GEN1
Solar/Wind Harmer
0.185
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.533
942111AE2-223 GEN
Solar/Wind Harmer
1.513
960611AF2-352 GEN
Solar/Wind Harmer
1.525
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.481
970885AG2-551 GEN
Solar/Wind Harmer
1.494
970241AG2-163 GEN
Solar/Wind Harmer
2.581
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.044
276838X2-022 GEN2
Solar/Wind Harmer
0.239
276916AD2-100_GEN
Solar/Wind Harmer
8.532
276911AD2-131_GEN
Solar/Wind Harmer
0.562
945391AF1-204 GEN
Solar/Wind Harmer
4.219
970623AG2-406 GEN
Solar/Wind Harmer
0.656
971587AH1-292 GEN
Solar/Wind Harmer
2.468
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.897
270462AD2-086
Solar/Wind Helper
3.747
247522W1-056 GEN
Solar/Wind Helper
1.177
253378AE2-206_GEN
Solar/Wind Helper
0.715
270349AD2-093_GEN
Solar/Wind Helper
0.857
270471AD2-092_GEN
Solar/Wind Helper
0.857
241960AC2-195 GEN
Solar/Wind Helper
0.697
957471AF2-041 GEN
Solar/Wind Harmer
14.651
959081AF2-199 GEN
Solar/Wind Harmer
4.884
971067AG2-660 GEN
Solar/Wind Harmer
1.628
274822ROCKFORD ;11
Adder
13.696
276903AD2-071 C
Solar/Wind Harmer
5.426
970819AG2-516 GEN
Solar/Wind Harmer
5.809
970569AG2-363 GEN
Solar/Wind Harmer
14.512
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.381
274766LEE CO EC;7U
Adder
6.306
276708O09 GEN2
Solar/Wind Harmer
0.167
276646AC1-214 GEN2
Solar/Wind Harmer
0.185
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.519
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.287
963741AG1-226 GEN
Solar/Wind Harmer
10.473
276621W2-048 GEN
Solar/Wind Harmer
0.213
965911AG1-460 GEN
Solar/Wind Harmer
0.82
24728605AND G2
Adder
2.099
970773AG2-487 GEN
Solar/Wind Harmer
0.63
246936BC-WTG1
Solar/Wind Helper
10.897
270317AD1-130_GEN
Solar/Wind Helper
4.143
270485AE1-090_GEN
Solar/Wind Helper
0.326
270391AF1-285 GEN3
Solar/Wind Helper
0.593
270578AF1-285 GEN2
Solar/Wind Helper
0.593
270286AF1-227 GEN2
Solar/Wind Helper
0.694
960841AF2-375 GEN
Solar/Wind Helper
1.179
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.835
NYPJM->LTFIMP_NY
CLTF
1.264
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.656
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042
AG2-052LTFEXP_AG2-052->PJM
LTF
0.172
AH1-155LTFEXP_AH1-155->PJM
LTF
0.258
CBM West 1LTFEXP_CBM-W1->PJM
CBM
70.253
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.933
MECLTFEXP_MEC->PJM
CLTF
9.784
SIGELTFEXP_SIGE->PJM
CLTF
0.201
LAGNLTFEXP_LAGN->PJM
CLTF
5.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.51
TVALTFEXP_TVA->PJM
CLTF
2.319
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7442_200545_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
238563 to 238654 ckt 1
243211 to 242933 ckt 1
242920 to 235102 ckt 5
247977 to 242524 ckt 17
242519 to 314912 ckt 1
243208 to 242865 ckt 2
242865 to 248000 ckt 1
242925 to 235117 ckt 1
246929 to 242935 ckt 1
242926 to 246751 ckt 1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
242516 to 242920 ckt 1
242933 to 965420 ckt 1
243232 to 246999 ckt 3
246999 to 290607 ckt Z1
243233 to 249567 ckt 1
248005 to 242528 ckt 1
965420 to 246929 ckt 1

Winter Peak Analysis

The New Service Request AH1-306 was evaluated as a 0.0 MW (28.8 MW Capacity) injection in the AEP area.

AH1-306 was evaluated as part of a plant. The plant consists of AH1-306. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-306 was evaluated as a 0.0 MW injection

AH1-306 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 200.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Request AH1-306 in PJM Transition Cycle 2, is listed in Table 1 below. This report will cover the dynamic analysis of AH1-306 project.

 

This analysis is effectively a screening study to determine whether the addition of AH1-306 project will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. AH1-306 project has been dispatched online at maximum power output, with 1.01 voltage at the terminal bus.

 

Transition Cycle 2 AH1-306 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2);

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5).

       f)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 AH1-306 project.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 peak load case:

       a)       AH1-306 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with AH1-306 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

The IPCMD and IQCMD states in the REGCA1 models of AH1-306 showed erratic behavior for some contingencies in which AH1-306 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

For several contingencies AE2-297 unit has been disconnected for over voltage relay settings where clearing time was 0.001 second for that relay settings. Added two cycles to original pick up to prevent fictious post-fault overvoltage tripping. It should be noted that generic dynamic models for inverter-based generators tend to produce a short-duration (a cycle or shorter) voltage spike at fault inception or clearing. These spikes can be ignored in most cases as they do not represent the performance of the actual hardware. They are simply a consequence of the model’s limited bandwidth, integration time step, and the way current injection models interface with the network solution.

 

Fictitious frequency response at AH1-306 generator bus tripped the queue project due to the action of instantaneous under-frequency relay for P1.24 and P1.26 contingencies. Therefore, the relay pickup times for frequency relay instances 97161309 was set to 20 seconds to avoid fictitious frequency tripping of the unit.

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 AH1-306 CIR Uprate Change in Model

 

 

 

 

Queue Project

Gross Outputs (MW)

Aux + Station + Fictitious Load (MW)

MFO (MW)

Inverter Change

AE1-207

161.55

3.12 MW + 0.029 MVAr

160

Original solar facility

AE2-172

40.824

0.848 MW + 0.399 MVAr

40

BESS addition

AH1-306

161.55

0.16 MW + 0.1 MVAr

0

Change in inverter type

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AH1-306 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVPartially in Service - Under Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVEngineering & Procurement
AC1-214Crescent RidgeIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-120Ripley 69kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-106North Waldo-Wild Creek 138 kVWithdrawn
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVWithdrawn
AD2-093Marysville 345kVPartially in Service - Under Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVEngineering & Procurement
AE1-102Maddox Creek 345 kVSuspended
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-175Light Foot 34.5 kVIn Service
AE1-183Maysville-McDowell 69 kVUnder Construction
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVPartially in Service - Under Construction
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-089Pennville-Adams 138 kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-214Cole 345 kVUnder Construction
AE2-216Hardin Switch 345 kVSuspended
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-285Maysville 69 kVUnder Construction
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-308Three Forks-Dale 138 kVEngineering & Procurement
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-325Valley 138 kVWithdrawn
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVPartially in Service - Under Construction
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-093Henderson-Stoneboro 69 kVUnder Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVSuspended
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVUnder Construction
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVPartially in Service - Under Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVEngineering & Procurement
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVUnder Construction
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-302Brookville-Squab Hollow 138 kVUnder Construction
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-014Maddox Creek 345 kVUnder Construction
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVWithdrawn
AF2-039Shawville-Clearfield 34.5 kVUnder Construction
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-068Jay 138 kVEngineering & Procurement
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-122Kirk 138 kVPartially in Service - Under Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVPartially in Service - Under Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-396Stinger 138 kVEngineering & Procurement
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-109Valley 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-198Union City 34.5 kVIn Service
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Hodgenville-Stephensburg 69 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-410Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-471Up Church-Wayne County 69 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-508Point Lookout 69 kVWithdrawn
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-029Forest G. Hipple-Dunton Lake 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Avon - Renaker 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-332East Elkhart - Elcona Tap 138 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-424Summersville - Magnolia 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-348Pound 34.5 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Delaware Business Park 138kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Millersburg 69 kVActive
AH1-571Millersburg 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
W2-048Brokaw-LanesvilleIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01BELMNT-05BELMON 500.0/765.0 kV Ckt 5 transformer(Any)
No new ratings for this Flowgate.
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4068.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4068.1 / AEP-TC2-18693
Title
b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570
Description
b4068.1 through b4068.49: Affected Transmission Owners: AEP / Dayton / ATSI The objective of this project is to construct multiple transmission lines to address Ohio area violations. The total distance covered by the lines is approximately 359.54 miles. The first transmission line ranges from the existing Greentown Substation in Howard County, Indiana to the new Teddy Substation in Clark County, Ohio, the line then branches north towards the existing Marysville Substation in Union County, Ohio, and east to the existing Beatty Substation in Franklin County, Ohio, and then extends to the existing Cole Substation in Franklin County, Ohio. The second transmission line extends from the existing Adkins Substation in Pickaway County, Ohio, to the new West Millersport Substation in Fairfield County, Ohio, then continues to the existing Conesville Substation in Coshocton County, Ohio before finally extending to the existing Guernsey Substation in Guernsey County, Ohio. There is a total of five transmission lines that extend between unnamed substations (Hayden - Cole 345 kV, Hyatt - Maliszewski 345 kV [double circuit], Roberts - Kenny 138 kV, Wilson - 5th Avenue 138 kV, West Millersport-Kirk 345 kV). This project will traverse 4 counties (Howard, Grant, Blackford, Jay) in Indiana, and 13 counties (Darke, Shelby, Champaign, Clark, Madison, Franklin, Delaware, Pickaway, Fairfield, Licking, Muskingum, Coshocton, Guernsey) in Ohio. This proposal has a total of 38 components, including 16 substation upgrade components, two greenfield substation components, eight greenfield transmission line components covering approximately 336.2 miles, and 12 transmission line upgrade components covering approximately 23.34 miles. b4068.28/b4068.49 is dependent on b3919.1 Baseline completion.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b3919.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.1
Title
Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yard
Description
Reconfigure Maliszewski 765 kV station from 2 breakers to a 6 breaker ring bus. Install a new 765/345 kV transformer. Establish new 345 kV breaker yard with 3 string breaker and a half to include a line exit to Hyatt and a line exit to Corridor. Loop the existing Hyatt - West Millersport 345 kV line into the new established 345 kV yard at the Maliszewski station.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9769.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9769.0 / AEP-TC2-19070
Title
05CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBs
Description
Upgrade/replace Cloverdale 765 kV, 4000 A CBs "CC" and "CC2" to 5000 A
Total Cost ($USD)
$25,000,000
Discounted Total Cost ($USD)
$25,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05CLOVRD-05CLOVRD_RJA 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: n9763.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9763.0 / AEP-TC2-19060
Title
05J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace Wavetraps
Description
Replace wave trap on 765 kV Cloverdale line. Replace/upgrade CB's B and B2 with 5000A CBs.
Total Cost ($USD)
$3,300,000
Discounted Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: n9767.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9767.0 / AEP-TC2-19068
Title
05KAMMER_RG 765.0 kV to 05KAMMER 765.0 kV ckt Z1 - Replace Wavetraps
Description
Replace the existing 3000A wave trap at Kammer 765 station towards Guernsey with a 5000A wave trap. Additionally, replace the 3000A circuit breaker QQ1 with a 5000A circuit breaker. Disconnect switches and a relays will be upgraded as well.
Total Cost ($USD)
$4,500,000
Discounted Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3851.2
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.2
Title
Rebuild R.P. Mone – Maddox Creek 345kV line (9.4 miles).
Description
Rebuild R.P. Mone – Maddox Creek 345kV line (9.4 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA
(All)C3774.0 MVA
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA
(All)C3774.0 MVA

System Reinforcement: n9786.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9786.0 / AEP-TC2-19161
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Wave Traps
Description
Replace wave tap at Maliszewski towards Marysville
Total Cost ($USD)
$3,000,000
Discounted Total Cost ($USD)
$3,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B5523.0 MVA

System Reinforcement: n9766.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9766.0 / AEP-TC2_19067
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Wavetrap
Description
Replace 4000A Wavetrap towards Maliszewski with 5000A equivalent
Total Cost ($USD)
$1,100,000
Discounted Total Cost ($USD)
$1,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3878.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3878.1
Title
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
Description
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
Cost Information
Time Estimate
Nov 12 2027

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B6667.0 MVA
(All)C6868.0 MVA

System Reinforcement: b3851.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.1 / B3851.1
Title
Rebuild Allen-RP Mone 345kV
Description
Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Apr 03 2028

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1540.0 MVA

System Reinforcement: n9759.0
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
n9759.0 / OVEC-TC2-19030
Title
06KYGER 345.0 kV to 05SPORN 345.0 kV ckt 1 - Replace Equipment
Description
Sag study Sporn - Kyger Creek line and replace section #25 OVEC element conductor 12.51 Miles At Sporn replace the following equipment: 2 - 2000 KCM AAC, 91-Str., AA1S1, AA1S2, AAS1, AAS2, KYGER CREEK #1 - PH A, KYGER CREEK #1 - PH B At Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB
Total Cost ($USD)
$38,180,000
Discounted Total Cost ($USD)
$38,180,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1942.0 MVA
(All)B2837.0 MVA
LLA1942.0 MVA
LLB2837.0 MVA

System Reinforcement: n9753.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9753.0 / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Discounted Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-306 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-306 could receive cost allocation. Although AH1-306 may not presently have cost responsibility for this upgrade, AH1-306 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1944.0 MVA
(All)B2825.0 MVA
(All)C2468.0 MVA

System Reinforcement: b2831.2
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
b2831.2
Title
Rebuild the Tanner Creek – Miami Fort 345kV line (DEOK portion), Actual In-service date 5/14/2021
Description
Rebuild the Tanner Creek – Miami Fort 345kV line (DEOK portion) Actual In-service date 5/14/2021
Cost Information
Time Estimate
May 14 2021

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2390.0 MVA
(All)B2390.0 MVA
(All)C2390.0 MVA

System Reinforcement: s2019
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
s2019 / AEP Project Resolves Overload
Title
AEP Project s2019 Resolves DEOK Overload
Description
Install two (2) new 345 kV breakers and move the existing M2 breaker into the new N string at Tanners Creek station. Terminate the Dearborn line and the transformer into the new N string. Install a new 345 kV breaker “T” to complete the T string. Projected in-service date 5/23/2023.
Cost Information
Time Estimate
May 26 2021

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-306 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2403.0 MVA
(All)B2403.0 MVA

System Reinforcement: b2968
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b2968
Title
Upgrade existing 345kV terminal equipment at Tanners Creek station on Tanners Creek - Miami Fort 345kV line, Actual In-Service Date 12/22/2020
Description
Upgrade existing 345kV terminal equipment at Tanners Creek station on Tanners Creek - Miami Fort 345kV line, Actual In-Service Date 12/22/2020
Cost Information
Time Estimate
Dec 22 2020

Not Contingent

Note: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B2542.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AH1-306 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-306 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-306


AH1-306 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-306 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-306 One Line Diagram

AH1-306 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.