AH1-314 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:56

East Danville 138 kV

100.0 MW Capacity / 100.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Pittsylvania Energy Storage LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request meets the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposits refunded. See Readiness Deposit calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $17,717,597 $7,291,754 = 2.43 AND ( $17,717,597 - $7,291,754 ) 100.0 = $104,258 per MW

General

The Project Developer has proposed a Storage facility located in the American Electric Power zone — Pittsylvania County, Virginia. The installed facilities will have a total capability of 100.0 MW with 100.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-314
Project Name:
East Danville 138 kV
Project Developer Name:
Pittsylvania Energy Storage LLC
State:
Virginia
County:
Pittsylvania
Transmission Owner:
American Electric Power
MFO:
100.0
MWE:
100.0
MWC:
100.0
Battery Storage Specification:
400.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-314 will interconnect on the American Electric Power transmission system at the East Danville 138 kV Station.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-314 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-314Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$2,092,968$0$0
Other Scope$1,183,174$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$17,679,077$17,679,077$17,679,077
System Reliability Network Upgrades
Steady State Thermal & Voltage$38,520$38,520$38,520
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$20,993,739$17,717,597$17,717,597

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-314

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-314
Project ID: AH1-314
20% of cost allocation for Phase II Network Upgrades:(A) $3,543,519
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $729,175
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $2,814,344
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

The existing 69kV Danville - East Danville will need to relocate the line from structures 479-54 to 479-58 to accommodate room for the station expansion for the interconnect. Three (3) new H-frames and two (2) new monopoles will be installed off center line to the north of the existing line. Single circuit vertical and horizontal framing will be used for this design. APCO will tie the proposed AH1-314 138 kV project into the existing East Danville 138 kV station by completing the following construction tasks: • Major Equipment • Installation of one (1) new box bay. • Installation of (3) 138KV RCVTs with (1) three-phase 138KV RCVT structures & foundations. • Expansion of the ground grid with 20' spacing by 6,000 square feet. • Installation of one 1 breaker control at the EAST DANVILLE 138 kV Station. • Appalachian Power Company will review and revise (as needed) the protective relay settings at the EAST DANVILLE 138 kV Station. • Installation of Direct Fiber at the EAST DANVILLE 138 kV Station. • Installation of one (1) Multiplexor Fiber Protection panel at the EAST DANVILLE 138 kV Station. • Appalachian Power Company will install 1 mile of 144 count all dielectric self-supporting (ADSS) fiber-optic cable. • Appalachian Power Company will transition existing OPGW fiber-optic shield wire from the cut-in dead ends into the AH1-314 New Station 138 kV Station. • Appalachian Power Company will install 1 mile of 144 count all dielectric loose tube (ADLT) underground fiber-optic cable.

$11,835,450$2,278,021$2,943,256$622,350$17,679,077$17,679,077
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Installation of a standard revenue metering package, including three (3) single phase current transformers (CT), three (3) single phase voltage transformers (VT), associated structures and foundations, one (1) ethernet switch, and one (1) DICM-installed metering panel, for the generation lead circuit at the EAST DANVILLE 138 kV Station.

$566,778$358,502$159,099$98,795$1,183,174$1,183,174
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

A 138 kV dead-end structure and foundation outside the fence of the Interconnection Substation, to terminate the Project Developer’s generator lead line. Line conductor from the dead-end structure to the bus position in the switchyard of the interconnection substation. Line will be built in parallel; 138 kV structures 18-134 and 18-135 will be replaced and raised for crossing.

$1,372,801$282,744$362,711$74,712$2,092,968$2,092,968
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$20,955,219$20,955,219
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-314 was evaluated as a 100.0 MW (100.0 MW Capacity) injection in the AEP area.

AH1-314 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 100.0 MW (100.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC137.85 %571.52B787.83
5.73
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC135.0 %571.52B771.57
5.73
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC135.03 %559.3B755.23
5.75
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC132.38 %559.3B740.38
5.75
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC158.88 %541.0B859.54
14.7
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC133.56 %508.54B679.23
14.77
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC129.43 %508.54B658.18
14.77
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC141.02 %559.3B788.75
5.75
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC138.34 %559.3B773.73
5.75
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC143.16 %571.52B818.17
5.73
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC140.31 %571.52B801.9
5.73

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.85 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:787.83
MW Contribution:
5.73
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:166.8 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:953.32
MW Contribution:
5.95
Bus #Bus NameTypeMW Contribution
946301AF1-294 GEN
Solar/Wind Harmer
9.009
3144303KENBRDG
Solar/Wind Harmer
0.308
971967AH1-528 GEN
Solar/Wind Harmer
54.853
3137643SOCKMAN
Solar/Wind Harmer
0.378
316426AA2-053 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315652AC1-086 GEN
Solar/Wind Harmer
6.661
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3151561HALLBR1
50/50
0.157
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.304
315607AA1-063A GEN
Solar/Wind Harmer
0.161
3151541CLOVER2
50/50
6.751
3151631KERR 6
50/50
0.481
3151281ROARAP4
50/50
0.105
970683AG2-441 GEN
Solar/Wind Harmer
23.63
970681AG2-440 GEN
Solar/Wind Harmer
15.684
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
33.974
961791AG1-021 GEN
Solar/Wind Harmer
4.383
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.385
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.274
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.396
316011AB1-132 GEN
Solar/Wind Harmer
1.098
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
270494AE1-108_GEN
Solar/Wind Helper
3.726
970535AG2-341 GEN
50/50
4.743
3151381ROSEMG2
50/50
0.102
3146776BUCKING
Solar/Wind Harmer
3.039
3146776BUCKING
Solar/Wind Harmer
0.246
964791AG1-342 GEN
Solar/Wind Harmer
4.862
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.862
961601AG1-000A GEN
Solar/Wind Harmer
1.099
3145453TOT5
Solar/Wind Harmer
0.08
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
0.103
316313AB2-026
Solar/Wind Helper
0.311
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3151261ROARAP2
50/50
0.115
942461AE2-259 GEN
Solar/Wind Harmer
0.001
964241AG1-285 GEN
Solar/Wind Harmer
23.019
971683AH1-343 GEN
Solar/Wind Harmer
6.767
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316212AC1-099_GEN
Solar/Wind Harmer
0.356
315722AD1-056 GEN
Solar/Wind Harmer
2.125
3145796HORNRTN
Solar/Wind Harmer
0.243
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
315821AE2-092 GEN
Solar/Wind Helper
2.532
3144293JTRSVLE
50/50
1.157
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.219
3151371ROSEMS1
50/50
0.136
970099AG2-077 GEN
Solar/Wind Harmer
35.928
962561AG1-105 GEN
Solar/Wind Harmer
12.514
3145783HORNRTN
Solar/Wind Harmer
1.613
3145783HORNRTN
Solar/Wind Harmer
1.291
3145783HORNRTN
Solar/Wind Harmer
0.403
3145783HORNRTN
Solar/Wind Harmer
0.161
316263AC1-034 GEN
Solar/Wind Harmer
2.419
315724AD1-057 GEN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.182
962571AG1-106 GEN
Solar/Wind Harmer
0.862
3145603CNETO
Solar/Wind Harmer
0.054
3147043LAWRENC
50/50
1.533
971629AH1-314 GEN
50/50
5.731
316131AB2-060 GEN
Solar/Wind Harmer
0.958
3147123OTTER R
Solar/Wind Harmer
0.04
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.112
3146083TARBORO
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
1.452
959311AF2-222 GEN
Solar/Wind Harmer
33.641
316478AD1-087 GEN
Solar/Wind Harmer
1.096
3147043LAWRENC
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.507
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.044
971623AH1-311 GEN
Solar/Wind Harmer
0.127
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3151391GASTONA
50/50
0.162
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.87
970685AG2-442 GEN
Solar/Wind Harmer
30.706
315785AD2-033 C
Solar/Wind Harmer
2.995
315693AD1-088 GEN
Solar/Wind Harmer
17.617
957481AF2-042 GEN
Solar/Wind Harmer
89.82
3146233WITAKRS
Solar/Wind Harmer
0.265
3145493TOT1
Solar/Wind Harmer
0.257
3151391GASTONA
50/50
0.162
3146926FARMVIL
Solar/Wind Harmer
0.379
970257AG2-171 GEN
Solar/Wind Harmer
12.316
971775AH1-396 GEN
Solar/Wind Harmer
0.616
3146233WITAKRS
Solar/Wind Harmer
0.334
3146233WITAKRS
Solar/Wind Harmer
0.045
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
22.145
970323AG2-213 GEN
Solar/Wind Harmer
16.421
313506AB2-031 GEN
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.253
3151601KERR 3
50/50
0.481
3146033SCOT NK
Solar/Wind Harmer
0.257
316405AF2-144 C
Solar/Wind Helper
0.233
970831AG2-522 GEN
Solar/Wind Harmer
7.484
316210AC1-098 GEN
Solar/Wind Harmer
0.638
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.024
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
316258AE1-075 C
Solar/Wind Helper
0.28
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151281ROARAP4
50/50
0.112
316034AC1-036 C
Solar/Wind Harmer
0.025
970401AG2-262 GEN
Solar/Wind Harmer
1.486
971065AG2-659 GEN
Solar/Wind Harmer
8.296
316129AC1-054 GEN
Solar/Wind Harmer
0.695
960081AF2-299 GEN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.091
3145796HORNRTN
Solar/Wind Harmer
0.2
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.479
970933AG2-581 GEN
Solar/Wind Harmer
27.427
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.0 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:771.57
MW Contribution:
5.73
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:164.25 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:938.71
MW Contribution:
5.95
Bus #Bus NameTypeMW Contribution
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.274
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.396
316011AB1-132 GEN
Solar/Wind Harmer
1.098
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
270494AE1-108_GEN
Solar/Wind Helper
3.726
970535AG2-341 GEN
50/50
4.743
3151381ROSEMG2
50/50
0.102
3146776BUCKING
Solar/Wind Harmer
3.039
3146776BUCKING
Solar/Wind Harmer
0.246
964791AG1-342 GEN
Solar/Wind Harmer
4.862
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.862
961601AG1-000A GEN
Solar/Wind Harmer
1.099
3145453TOT5
Solar/Wind Harmer
0.08
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
0.103
316313AB2-026
Solar/Wind Helper
0.311
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3151261ROARAP2
50/50
0.115
942461AE2-259 GEN
Solar/Wind Harmer
0.001
964241AG1-285 GEN
Solar/Wind Harmer
23.019
971683AH1-343 GEN
Solar/Wind Harmer
6.767
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316212AC1-099_GEN
Solar/Wind Harmer
0.356
315722AD1-056 GEN
Solar/Wind Harmer
2.125
3145796HORNRTN
Solar/Wind Harmer
0.243
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
315821AE2-092 GEN
Solar/Wind Helper
2.532
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.219
3151371ROSEMS1
50/50
0.136
970099AG2-077 GEN
Solar/Wind Harmer
35.928
962561AG1-105 GEN
Solar/Wind Harmer
12.514
3145783HORNRTN
Solar/Wind Harmer
1.613
3145783HORNRTN
Solar/Wind Harmer
1.291
3145783HORNRTN
Solar/Wind Harmer
0.403
3145783HORNRTN
Solar/Wind Harmer
0.161
316263AC1-034 GEN
Solar/Wind Harmer
2.419
315724AD1-057 GEN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.182
962571AG1-106 GEN
Solar/Wind Harmer
0.862
3145603CNETO
Solar/Wind Harmer
0.054
3147043LAWRENC
50/50
1.533
971629AH1-314 GEN
50/50
5.731
316131AB2-060 GEN
Solar/Wind Harmer
0.958
3147123OTTER R
Solar/Wind Harmer
0.04
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.112
3146083TARBORO
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
1.452
959311AF2-222 GEN
Solar/Wind Harmer
33.641
316478AD1-087 GEN
Solar/Wind Harmer
1.096
3147043LAWRENC
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.507
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.044
971623AH1-311 GEN
Solar/Wind Harmer
0.127
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3151391GASTONA
50/50
0.162
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.87
970685AG2-442 GEN
Solar/Wind Harmer
30.706
315785AD2-033 C
Solar/Wind Harmer
2.995
315693AD1-088 GEN
Solar/Wind Harmer
17.617
957481AF2-042 GEN
Solar/Wind Harmer
89.82
3151391GASTONA
50/50
0.162
3146926FARMVIL
Solar/Wind Harmer
0.379
970257AG2-171 GEN
Solar/Wind Harmer
12.316
971775AH1-396 GEN
Solar/Wind Harmer
0.616
3146233WITAKRS
Solar/Wind Harmer
0.334
3146233WITAKRS
Solar/Wind Harmer
0.045
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
22.145
970323AG2-213 GEN
Solar/Wind Harmer
16.421
313506AB2-031 GEN
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
946301AF1-294 GEN
Solar/Wind Harmer
9.009
3144303KENBRDG
Solar/Wind Harmer
0.308
3137643SOCKMAN
Solar/Wind Harmer
0.378
316426AA2-053 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315652AC1-086 GEN
Solar/Wind Harmer
6.661
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3151561HALLBR1
50/50
0.157
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.304
315607AA1-063A GEN
Solar/Wind Harmer
0.161
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.253
3151601KERR 3
50/50
0.481
3146033SCOT NK
Solar/Wind Harmer
0.257
316405AF2-144 C
Solar/Wind Helper
0.233
3146233WITAKRS
Solar/Wind Harmer
0.265
3145493TOT1
Solar/Wind Harmer
0.257
3151541CLOVER2
50/50
6.751
3151631KERR 6
50/50
0.481
3151281ROARAP4
50/50
0.105
970683AG2-441 GEN
Solar/Wind Harmer
23.63
970681AG2-440 GEN
Solar/Wind Harmer
15.684
970831AG2-522 GEN
Solar/Wind Harmer
7.484
316210AC1-098 GEN
Solar/Wind Harmer
0.638
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.024
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
316258AE1-075 C
Solar/Wind Helper
0.28
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151281ROARAP4
50/50
0.112
316034AC1-036 C
Solar/Wind Harmer
0.025
970401AG2-262 GEN
Solar/Wind Harmer
1.486
971065AG2-659 GEN
Solar/Wind Harmer
8.296
316129AC1-054 GEN
Solar/Wind Harmer
0.695
960081AF2-299 GEN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.091
3145796HORNRTN
Solar/Wind Harmer
0.2
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.479
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
33.974
961791AG1-021 GEN
Solar/Wind Harmer
4.383
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.385
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
TVALTFEXP_TVA->PJM
CLTF
1.278
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.03 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:755.23
MW Contribution:
5.75
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:164.92 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:922.4
MW Contribution:
5.97
Bus #Bus NameTypeMW Contribution
946301AF1-294 GEN
Solar/Wind Harmer
9.014
3144303KENBRDG
Solar/Wind Harmer
0.308
971967AH1-528 GEN
Solar/Wind Harmer
54.886
3137643SOCKMAN
Solar/Wind Harmer
0.379
316426AA2-053 GEN
Solar/Wind Harmer
0.29
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315652AC1-086 GEN
Solar/Wind Harmer
6.683
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
961791AG1-021 GEN
Solar/Wind Harmer
4.385
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.386
3138266HYDRAULIC
Solar/Wind Helper
0.007
3151411GASTONB
50/50
0.163
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.411
316011AB1-132 GEN
Solar/Wind Harmer
1.102
3145893MURPHYS
Solar/Wind Harmer
0.096
3145893MURPHYS
Solar/Wind Harmer
0.057
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
970535AG2-341 GEN
50/50
4.746
3151381ROSEMG2
50/50
0.103
964791AG1-342 GEN
Solar/Wind Harmer
4.866
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.873
961601AG1-000A GEN
Solar/Wind Harmer
1.103
3145453TOT5
Solar/Wind Harmer
0.081
3145893MURPHYS
Solar/Wind Harmer
0.383
3145893MURPHYS
Solar/Wind Harmer
0.103
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3151261ROARAP2
50/50
0.116
942461AE2-259 GEN
Solar/Wind Harmer
0.001
964241AG1-285 GEN
Solar/Wind Harmer
23.033
971683AH1-343 GEN
Solar/Wind Harmer
6.774
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316212AC1-099_GEN
Solar/Wind Harmer
0.357
315722AD1-056 GEN
Solar/Wind Harmer
2.132
3145796HORNRTN
Solar/Wind Harmer
0.244
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
315821AE2-092 GEN
Solar/Wind Helper
2.528
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.22
3151371ROSEMS1
50/50
0.136
970099AG2-077 GEN
Solar/Wind Harmer
35.95
962561AG1-105 GEN
Solar/Wind Harmer
12.524
3145783HORNRTN
Solar/Wind Harmer
1.617
3145783HORNRTN
Solar/Wind Harmer
1.294
3145783HORNRTN
Solar/Wind Harmer
0.404
3145783HORNRTN
Solar/Wind Harmer
0.162
316263AC1-034 GEN
Solar/Wind Harmer
2.427
315724AD1-057 GEN
Solar/Wind Harmer
1.189
3145796HORNRTN
Solar/Wind Harmer
0.183
962571AG1-106 GEN
Solar/Wind Harmer
0.864
3145603CNETO
Solar/Wind Harmer
0.054
3147043LAWRENC
50/50
1.535
971629AH1-314 GEN
50/50
5.749
316131AB2-060 GEN
Solar/Wind Harmer
0.958
3147123OTTER R
Solar/Wind Harmer
0.04
316359AB2-059 GEN
Solar/Wind Harmer
0.227
3142053HEARTS
Solar/Wind Harmer
0.112
3146083TARBORO
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
1.453
959311AF2-222 GEN
Solar/Wind Harmer
33.659
316478AD1-087 GEN
Solar/Wind Harmer
1.097
3147043LAWRENC
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.508
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.044
971623AH1-311 GEN
Solar/Wind Harmer
0.128
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3151391GASTONA
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.872
970685AG2-442 GEN
Solar/Wind Harmer
30.722
315785AD2-033 C
Solar/Wind Harmer
2.997
315693AD1-088 GEN
Solar/Wind Harmer
17.627
957481AF2-042 GEN
Solar/Wind Harmer
89.874
3146233WITAKRS
Solar/Wind Harmer
0.266
3145493TOT1
Solar/Wind Harmer
0.257
3151391GASTONA
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
970257AG2-171 GEN
Solar/Wind Harmer
12.322
971775AH1-396 GEN
Solar/Wind Harmer
0.616
3146233WITAKRS
Solar/Wind Harmer
0.335
3146233WITAKRS
Solar/Wind Harmer
0.045
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
22.154
970323AG2-213 GEN
Solar/Wind Harmer
16.429
313506AB2-031 GEN
Solar/Wind Harmer
0.294
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
316049AB1-081 GEN
Solar/Wind Harmer
0.363
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3151561HALLBR1
50/50
0.158
3151411GASTONB
50/50
0.163
315607AA1-063A GEN
Solar/Wind Harmer
0.162
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.229
3145893MURPHYS
Solar/Wind Harmer
0.254
3146776BUCKING
Solar/Wind Helper
0.288
3151601KERR 3
50/50
0.482
3146033SCOT NK
Solar/Wind Harmer
0.257
316405AF2-144 C
Solar/Wind Helper
0.233
3151541CLOVER2
50/50
6.756
3151631KERR 6
50/50
0.482
3151281ROARAP4
50/50
0.105
970683AG2-441 GEN
Solar/Wind Harmer
23.642
970681AG2-440 GEN
Solar/Wind Harmer
15.692
970831AG2-522 GEN
Solar/Wind Harmer
7.493
316210AC1-098 GEN
Solar/Wind Harmer
0.64
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.024
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151281ROARAP4
50/50
0.112
316034AC1-036 C
Solar/Wind Harmer
0.025
970401AG2-262 GEN
Solar/Wind Harmer
1.487
971065AG2-659 GEN
Solar/Wind Harmer
8.305
316129AC1-054 GEN
Solar/Wind Harmer
0.696
960081AF2-299 GEN
Solar/Wind Harmer
0.937
3145783HORNRTN
Solar/Wind Harmer
0.091
3145796HORNRTN
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
0.463
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.481
970933AG2-581 GEN
Solar/Wind Harmer
27.443
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
3138266HYDRAULIC
Solar/Wind Helper
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
TVALTFEXP_TVA->PJM
CLTF
1.294
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.38 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:740.38
MW Contribution:
5.75
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:162.31 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:907.81
MW Contribution:
5.97
Bus #Bus NameTypeMW Contribution
3151411GASTONB
50/50
0.163
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.411
316011AB1-132 GEN
Solar/Wind Harmer
1.102
3145893MURPHYS
Solar/Wind Harmer
0.096
3145893MURPHYS
Solar/Wind Harmer
0.057
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
970535AG2-341 GEN
50/50
4.746
3151381ROSEMG2
50/50
0.103
964791AG1-342 GEN
Solar/Wind Harmer
4.866
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.873
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3151261ROARAP2
50/50
0.116
942461AE2-259 GEN
Solar/Wind Harmer
0.001
964241AG1-285 GEN
Solar/Wind Harmer
23.033
971683AH1-343 GEN
Solar/Wind Harmer
6.774
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316212AC1-099_GEN
Solar/Wind Harmer
0.357
315722AD1-056 GEN
Solar/Wind Harmer
2.132
3145796HORNRTN
Solar/Wind Harmer
0.244
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
315821AE2-092 GEN
Solar/Wind Helper
2.528
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.22
3151371ROSEMS1
50/50
0.136
970099AG2-077 GEN
Solar/Wind Harmer
35.95
3147043LAWRENC
50/50
1.535
971629AH1-314 GEN
50/50
5.749
316131AB2-060 GEN
Solar/Wind Harmer
0.958
3147123OTTER R
Solar/Wind Harmer
0.04
316359AB2-059 GEN
Solar/Wind Harmer
0.227
3142053HEARTS
Solar/Wind Harmer
0.112
3146083TARBORO
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
1.453
959311AF2-222 GEN
Solar/Wind Harmer
33.659
316478AD1-087 GEN
Solar/Wind Harmer
1.097
3147043LAWRENC
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.508
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.044
971623AH1-311 GEN
Solar/Wind Harmer
0.128
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3151391GASTONA
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
970257AG2-171 GEN
Solar/Wind Harmer
12.322
971775AH1-396 GEN
Solar/Wind Harmer
0.616
3146233WITAKRS
Solar/Wind Harmer
0.335
3146233WITAKRS
Solar/Wind Harmer
0.045
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
22.154
970323AG2-213 GEN
Solar/Wind Harmer
16.429
313506AB2-031 GEN
Solar/Wind Harmer
0.294
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
316049AB1-081 GEN
Solar/Wind Harmer
0.363
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
961601AG1-000A GEN
Solar/Wind Harmer
1.103
3145453TOT5
Solar/Wind Harmer
0.081
3145893MURPHYS
Solar/Wind Harmer
0.383
3145893MURPHYS
Solar/Wind Harmer
0.103
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
946301AF1-294 GEN
Solar/Wind Harmer
9.014
3144303KENBRDG
Solar/Wind Harmer
0.308
3137643SOCKMAN
Solar/Wind Harmer
0.379
316426AA2-053 GEN
Solar/Wind Harmer
0.29
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315652AC1-086 GEN
Solar/Wind Harmer
6.683
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3151561HALLBR1
50/50
0.158
3151411GASTONB
50/50
0.163
315607AA1-063A GEN
Solar/Wind Harmer
0.162
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.229
3145893MURPHYS
Solar/Wind Harmer
0.254
3146776BUCKING
Solar/Wind Helper
0.288
3151601KERR 3
50/50
0.482
3146033SCOT NK
Solar/Wind Harmer
0.257
316405AF2-144 C
Solar/Wind Helper
0.233
3151391GASTONA
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.872
970685AG2-442 GEN
Solar/Wind Harmer
30.722
315785AD2-033 C
Solar/Wind Harmer
2.997
315693AD1-088 GEN
Solar/Wind Harmer
17.627
957481AF2-042 GEN
Solar/Wind Harmer
89.874
3146233WITAKRS
Solar/Wind Harmer
0.266
3145493TOT1
Solar/Wind Harmer
0.257
962561AG1-105 GEN
Solar/Wind Harmer
12.524
3145783HORNRTN
Solar/Wind Harmer
1.617
3145783HORNRTN
Solar/Wind Harmer
1.294
3145783HORNRTN
Solar/Wind Harmer
0.404
3145783HORNRTN
Solar/Wind Harmer
0.162
316263AC1-034 GEN
Solar/Wind Harmer
2.427
315724AD1-057 GEN
Solar/Wind Harmer
1.189
3145796HORNRTN
Solar/Wind Harmer
0.183
962571AG1-106 GEN
Solar/Wind Harmer
0.864
3145603CNETO
Solar/Wind Harmer
0.054
3151541CLOVER2
50/50
6.756
3151631KERR 6
50/50
0.482
3151281ROARAP4
50/50
0.105
970683AG2-441 GEN
Solar/Wind Harmer
23.642
970681AG2-440 GEN
Solar/Wind Harmer
15.692
970831AG2-522 GEN
Solar/Wind Harmer
7.493
316210AC1-098 GEN
Solar/Wind Harmer
0.64
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.024
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151281ROARAP4
50/50
0.112
316034AC1-036 C
Solar/Wind Harmer
0.025
970401AG2-262 GEN
Solar/Wind Harmer
1.487
971065AG2-659 GEN
Solar/Wind Harmer
8.305
316129AC1-054 GEN
Solar/Wind Harmer
0.696
960081AF2-299 GEN
Solar/Wind Harmer
0.937
3145783HORNRTN
Solar/Wind Harmer
0.091
3145796HORNRTN
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
0.463
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.481
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
961791AG1-021 GEN
Solar/Wind Harmer
4.385
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.386
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
TVALTFEXP_TVA->PJM
CLTF
1.294
MECLTFEXP_MEC->PJM
CLTF
0.996
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:158.88 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:859.54
MW Contribution:
14.7
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:198.91 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1076.12
MW Contribution:
15.32
Bus #Bus NameTypeMW Contribution
961601AG1-000A GEN
Solar/Wind Harmer
3.454
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Helper
0.071
316123AC1-075 GEN
Solar/Wind Helper
2.791
942461AE2-259 GEN
Solar/Wind Helper
1.921
3147312GRETNA
Solar/Wind Helper
0.023
971629AH1-314 GEN
50/50
14.704
270030AE2-140 GEN
Solar/Wind Harmer
13.925
316359AB2-059 GEN
Solar/Wind Harmer
1.142
3142053HEARTS
Solar/Wind Harmer
0.1
3146083TARBORO
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.377
274734ELWOOD EC;8P
Adder
3.258
943811AF1-049 GEN
Solar/Wind Harmer
2.747
270336AE1-100 GEN
Solar/Wind Harmer
1.062
270574AD1-017 GEN2
Solar/Wind Harmer
2.646
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
316420AA1-050 GEN
Solar/Wind Harmer
0.816
3138543CONSLDL
Solar/Wind Harmer
-0.005
316283AC2-100 C
Solar/Wind Helper
8.329
316222AC1-221 GEN
Solar/Wind Helper
8.844
316003AC1-222 GEN
Solar/Wind Helper
2.9
316478AD1-087 GEN
Solar/Wind Helper
2.406
3147133PAMPLIN
Solar/Wind Helper
1.004
3147043LAWRENC
Solar/Wind Helper
0.102
970917AG2-570 GEN
Solar/Wind Harmer
47.291
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
274732ELWOOD EC;7P
Adder
3.258
3146926FARMVIL
Solar/Wind Helper
0.151
316197AC1-042 GEN
Solar/Wind Helper
0.107
316049AB1-081 GEN
Solar/Wind Harmer
0.913
3145493TOT1
Solar/Wind Harmer
0.117
961601AG1-000A GEN
Solar/Wind Harmer
3.411
3145453TOT5
Solar/Wind Harmer
0.07
316118AC1-105 GEN
Solar/Wind Helper
2.529
3146776BUCKING
Solar/Wind Helper
0.794
3146776BUCKING
Solar/Wind Helper
0.064
270457AD2-023 GEN
Solar/Wind Harmer
2.095
970085AG2-068 GEN
Solar/Wind Harmer
11.823
274731ELWOOD EC;2P
Adder
3.258
274733ELWOOD EC;3P
Adder
3.258
3144303KENBRDG
Solar/Wind Helper
0.266
970919AG2-571 GEN
Solar/Wind Harmer
5.986
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.096
316494AC1-189 GEN
Solar/Wind Harmer
0.715
3146776BUCKING
Solar/Wind Helper
0.079
315773AC2-141 GEN
Solar/Wind Helper
2.494
970581AG2-369 GEN
Solar/Wind Harmer
10.168
270069AE2-166 C O1
Solar/Wind Harmer
5.276
970087AG2-069 GEN
Solar/Wind Harmer
17.735
970223AG2-152 GEN
Solar/Wind Harmer
11.598
270018AE2-047 C O1
Solar/Wind Harmer
0.982
3145493TOT1
Solar/Wind Harmer
0.224
3146233WITAKRS
Solar/Wind Harmer
-0.027
274730ELWOOD EC;6P
Adder
3.258
315785AD2-033 C
Solar/Wind Helper
3.937
3146926FARMVIL
Solar/Wind Helper
0.151
270013AE1-250 PV
Solar/Wind Harmer
1.778
316263AC1-034 GEN
Solar/Wind Harmer
3.979
3145603CNETO
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Helper
0.977
315687AD1-152 GEN
Solar/Wind Helper
3.728
316237AB2-079_GEN
Solar/Wind Helper
0.489
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
957861AF2-080 GEN
Solar/Wind Harmer
2.909
274728ELWOOD EC;5P
Adder
3.258
316238AB2-078_GEN
Solar/Wind Helper
0.489
316239AB2-077_GEN
Solar/Wind Helper
0.489
316322AB2-045
Solar/Wind Helper
0.222
270016AE1-250 BESS
Solar/Wind Harmer
1.778
274729ELWOOD EC;1P
Adder
3.258
316034AC1-036 C
Solar/Wind Helper
0.371
316129AC1-054 GEN
Solar/Wind Helper
0.805
3147312GRETNA
Solar/Wind Helper
0.091
3146802CHATHAM
Solar/Wind Helper
0.085
3146843MT LREL
Solar/Wind Helper
0.573
3146843MT LREL
Solar/Wind Helper
0.573
3147133PAMPLIN
Solar/Wind Helper
0.32
3147133PAMPLIN
Solar/Wind Helper
0.256
316294AC1-161 GEN
Solar/Wind Helper
2.119
270455AD2-022 GEN
Solar/Wind Harmer
4.132
270197AD1-017 GEN1
Solar/Wind Harmer
0.794
274735ELWOOD EC;4P
Adder
3.258
3147173SINAI
Solar/Wind Helper
0.725
3147243WELCO
Solar/Wind Helper
0.453
316486AD2-202 GEN
Solar/Wind Helper
0.705
274736ELWOOD EC;9P
Adder
3.258
316131AB2-060 GEN
Solar/Wind Helper
2.179
3147123OTTER R
Solar/Wind Helper
0.101
900033ID_568986
External Queue
3.9371731281280518
LAGNLTFEXP_LAGN->PJM
CLTF
8.754
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.297
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.858
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.874
CPLELTFEXP_CPLE->PJM
CLTF
13.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.28
TVALTFEXP_TVA->PJM
CLTF
4.34
MECLTFEXP_MEC->PJM
CLTF
4.325
SIGELTFEXP_SIGE->PJM
CLTF
0.128
NYPJM->LTFIMP_NY
CLTF
0.325
LGEELTFEXP_LGEE->PJM
CLTF
1.535
WECLTFEXP_WEC->PJM
CLTF
0.818

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.56 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:679.23
MW Contribution:
14.77
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:169.55 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:862.23
MW Contribution:
15.39
Bus #Bus NameTypeMW Contribution
270197AD1-017 GEN1
Solar/Wind Harmer
0.45
274735ELWOOD EC;4P
Adder
3.35
3147173SINAI
Solar/Wind Helper
0.724
3147243WELCO
Solar/Wind Helper
0.452
316486AD2-202 GEN
Solar/Wind Helper
0.703
970085AG2-068 GEN
Solar/Wind Harmer
9.019
274731ELWOOD EC;2P
Adder
3.35
274733ELWOOD EC;3P
Adder
3.35
3144303KENBRDG
Solar/Wind Helper
0.265
970919AG2-571 GEN
Solar/Wind Harmer
6.012
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.061
961671AG1-007 GEN
Solar/Wind Harmer
0.01
316494AC1-189 GEN
Solar/Wind Harmer
0.202
3146776BUCKING
Solar/Wind Helper
0.079
315773AC2-141 GEN
Solar/Wind Helper
2.463
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
957861AF2-080 GEN
Solar/Wind Harmer
2.583
274728ELWOOD EC;5P
Adder
3.35
316238AB2-078_GEN
Solar/Wind Helper
0.487
316239AB2-077_GEN
Solar/Wind Helper
0.487
316322AB2-045
Solar/Wind Helper
0.22
274729ELWOOD EC;1P
Adder
3.35
316034AC1-036 C
Solar/Wind Helper
0.37
316129AC1-054 GEN
Solar/Wind Helper
0.798
3147312GRETNA
Solar/Wind Helper
0.09
3146802CHATHAM
Solar/Wind Helper
0.084
970417AG2-272 GEN
50/50
1.814
970087AG2-069 GEN
Solar/Wind Harmer
13.528
970223AG2-152 GEN
Solar/Wind Harmer
8.184
3145493TOT1
Solar/Wind Harmer
0.302
3146233WITAKRS
Solar/Wind Harmer
0.244
274730ELWOOD EC;6P
Adder
3.35
315785AD2-033 C
Solar/Wind Helper
3.92
971629AH1-314 GEN
50/50
14.769
270030AE2-140 GEN
Solar/Wind Harmer
9.794
316359AB2-059 GEN
Solar/Wind Harmer
0.271
3142053HEARTS
Solar/Wind Harmer
0.134
3146083TARBORO
Solar/Wind Harmer
0.068
274734ELWOOD EC;8P
Adder
3.35
274736ELWOOD EC;9P
Adder
3.35
316131AB2-060 GEN
Solar/Wind Helper
2.17
3147123OTTER R
Solar/Wind Helper
0.1
961601AG1-000A GEN
Solar/Wind Harmer
5.544
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.076
3146776BUCKING
Solar/Wind Helper
0.071
961601AG1-000A GEN
Solar/Wind Harmer
1.386
3145453TOT5
Solar/Wind Harmer
0.095
316118AC1-105 GEN
Solar/Wind Helper
2.523
3146776BUCKING
Solar/Wind Helper
0.788
3146776BUCKING
Solar/Wind Helper
0.064
316263AC1-034 GEN
Solar/Wind Harmer
2.899
3145603CNETO
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Helper
0.975
315687AD1-152 GEN
Solar/Wind Helper
3.72
316237AB2-079_GEN
Solar/Wind Helper
0.487
316123AC1-075 GEN
Solar/Wind Helper
2.782
942461AE2-259 GEN
Solar/Wind Helper
1.911
3147312GRETNA
Solar/Wind Helper
0.022
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
971623AH1-311 GEN
Solar/Wind Harmer
0.153
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3138543CONSLDL
Solar/Wind Harmer
0.042
316283AC2-100 C
Solar/Wind Helper
8.321
316222AC1-221 GEN
Solar/Wind Helper
8.836
316003AC1-222 GEN
Solar/Wind Helper
2.894
316478AD1-087 GEN
Solar/Wind Helper
2.399
3147133PAMPLIN
Solar/Wind Helper
0.999
3147043LAWRENC
Solar/Wind Helper
0.101
3146926FARMVIL
Solar/Wind Helper
0.15
970917AG2-570 GEN
Solar/Wind Harmer
15.031
3146233WITAKRS
Solar/Wind Harmer
0.308
3146233WITAKRS
Solar/Wind Harmer
0.042
274732ELWOOD EC;7P
Adder
3.35
3146926FARMVIL
Solar/Wind Helper
0.15
316197AC1-042 GEN
Solar/Wind Helper
0.106
316049AB1-081 GEN
Solar/Wind Harmer
0.434
3145493TOT1
Solar/Wind Harmer
0.158
970581AG2-369 GEN
Solar/Wind Harmer
7.756
270069AE2-166 C O1
Solar/Wind Harmer
3.716
3146843MT LREL
Solar/Wind Helper
0.571
3146843MT LREL
Solar/Wind Helper
0.571
3147133PAMPLIN
Solar/Wind Helper
0.318
3147133PAMPLIN
Solar/Wind Helper
0.255
316294AC1-161 GEN
Solar/Wind Helper
2.092
900033ID_568986
External Queue
3.9371731281280518
LAGNLTFEXP_LAGN->PJM
CLTF
8.868
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.468
TVALTFEXP_TVA->PJM
CLTF
4.397
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.68
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.088
MECLTFEXP_MEC->PJM
CLTF
4.419
CPLELTFEXP_CPLE->PJM
CLTF
13.173
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.038
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
0.289
LGEELTFEXP_LGEE->PJM
CLTF
1.573
WECLTFEXP_WEC->PJM
CLTF
0.84

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.43 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:658.18
MW Contribution:
14.77
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:165.33 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:840.79
MW Contribution:
15.39
Bus #Bus NameTypeMW Contribution
970085AG2-068 GEN
Solar/Wind Harmer
9.019
274731ELWOOD EC;2P
Adder
3.35
274733ELWOOD EC;3P
Adder
3.35
3144303KENBRDG
Solar/Wind Helper
0.265
270197AD1-017 GEN1
Solar/Wind Harmer
0.45
274735ELWOOD EC;4P
Adder
3.35
3147173SINAI
Solar/Wind Helper
0.724
3147243WELCO
Solar/Wind Helper
0.452
316486AD2-202 GEN
Solar/Wind Helper
0.703
961601AG1-000A GEN
Solar/Wind Harmer
5.544
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.076
3146776BUCKING
Solar/Wind Helper
0.071
961601AG1-000A GEN
Solar/Wind Harmer
1.386
3145453TOT5
Solar/Wind Harmer
0.095
316118AC1-105 GEN
Solar/Wind Helper
2.523
3146776BUCKING
Solar/Wind Helper
0.788
3146776BUCKING
Solar/Wind Helper
0.064
316123AC1-075 GEN
Solar/Wind Helper
2.782
942461AE2-259 GEN
Solar/Wind Helper
1.911
3147312GRETNA
Solar/Wind Helper
0.022
316263AC1-034 GEN
Solar/Wind Harmer
2.899
3145603CNETO
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Helper
0.975
315687AD1-152 GEN
Solar/Wind Helper
3.72
316237AB2-079_GEN
Solar/Wind Helper
0.487
971629AH1-314 GEN
50/50
14.769
270030AE2-140 GEN
Solar/Wind Harmer
9.794
316359AB2-059 GEN
Solar/Wind Harmer
0.271
3142053HEARTS
Solar/Wind Harmer
0.134
3146083TARBORO
Solar/Wind Harmer
0.068
274734ELWOOD EC;8P
Adder
3.35
274736ELWOOD EC;9P
Adder
3.35
316131AB2-060 GEN
Solar/Wind Helper
2.17
3147123OTTER R
Solar/Wind Helper
0.1
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
971623AH1-311 GEN
Solar/Wind Harmer
0.153
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3138543CONSLDL
Solar/Wind Harmer
0.042
316283AC2-100 C
Solar/Wind Helper
8.321
316222AC1-221 GEN
Solar/Wind Helper
8.836
316003AC1-222 GEN
Solar/Wind Helper
2.894
316478AD1-087 GEN
Solar/Wind Helper
2.399
3147133PAMPLIN
Solar/Wind Helper
0.999
3147043LAWRENC
Solar/Wind Helper
0.101
970417AG2-272 GEN
50/50
1.814
970087AG2-069 GEN
Solar/Wind Harmer
13.528
970223AG2-152 GEN
Solar/Wind Harmer
8.184
3145493TOT1
Solar/Wind Harmer
0.302
3146233WITAKRS
Solar/Wind Harmer
0.244
274730ELWOOD EC;6P
Adder
3.35
315785AD2-033 C
Solar/Wind Helper
3.92
3146926FARMVIL
Solar/Wind Helper
0.15
3146233WITAKRS
Solar/Wind Harmer
0.308
3146233WITAKRS
Solar/Wind Harmer
0.042
274732ELWOOD EC;7P
Adder
3.35
3146926FARMVIL
Solar/Wind Helper
0.15
316197AC1-042 GEN
Solar/Wind Helper
0.106
316049AB1-081 GEN
Solar/Wind Harmer
0.434
3145493TOT1
Solar/Wind Harmer
0.158
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.061
961671AG1-007 GEN
Solar/Wind Harmer
0.01
316494AC1-189 GEN
Solar/Wind Harmer
0.202
3146776BUCKING
Solar/Wind Helper
0.079
315773AC2-141 GEN
Solar/Wind Helper
2.463
970581AG2-369 GEN
Solar/Wind Harmer
7.756
270069AE2-166 C O1
Solar/Wind Harmer
3.716
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
957861AF2-080 GEN
Solar/Wind Harmer
2.583
274728ELWOOD EC;5P
Adder
3.35
316238AB2-078_GEN
Solar/Wind Helper
0.487
316239AB2-077_GEN
Solar/Wind Helper
0.487
316322AB2-045
Solar/Wind Helper
0.22
274729ELWOOD EC;1P
Adder
3.35
316034AC1-036 C
Solar/Wind Helper
0.37
316129AC1-054 GEN
Solar/Wind Helper
0.798
3147312GRETNA
Solar/Wind Helper
0.09
3146802CHATHAM
Solar/Wind Helper
0.084
3146843MT LREL
Solar/Wind Helper
0.571
3146843MT LREL
Solar/Wind Helper
0.571
3147133PAMPLIN
Solar/Wind Helper
0.318
3147133PAMPLIN
Solar/Wind Helper
0.255
316294AC1-161 GEN
Solar/Wind Helper
2.092
900033ID_568986
External Queue
3.9371731281280518
LAGNLTFEXP_LAGN->PJM
CLTF
8.868
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.468
TVALTFEXP_TVA->PJM
CLTF
4.397
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.68
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.088
MECLTFEXP_MEC->PJM
CLTF
4.419
CPLELTFEXP_CPLE->PJM
CLTF
13.173
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.038
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
0.289
LGEELTFEXP_LGEE->PJM
CLTF
1.573
WECLTFEXP_WEC->PJM
CLTF
0.84

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.02 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:788.75
MW Contribution:
5.75
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:170.87 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:955.68
MW Contribution:
5.97
Bus #Bus NameTypeMW Contribution
3147133PAMPLIN
Solar/Wind Harmer
1.453
959311AF2-222 GEN
Solar/Wind Harmer
33.659
316478AD1-087 GEN
Solar/Wind Harmer
1.097
3147043LAWRENC
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.508
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.044
971623AH1-311 GEN
Solar/Wind Harmer
0.128
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
33.983
961791AG1-021 GEN
Solar/Wind Harmer
4.385
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.386
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
946301AF1-294 GEN
Solar/Wind Harmer
9.014
3144303KENBRDG
Solar/Wind Harmer
0.308
971967AH1-528 GEN
Solar/Wind Harmer
54.886
3137643SOCKMAN
Solar/Wind Harmer
0.379
316426AA2-053 GEN
Solar/Wind Harmer
0.29
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315652AC1-086 GEN
Solar/Wind Harmer
6.683
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3151561HALLBR1
50/50
0.158
3151411GASTONB
50/50
0.163
315607AA1-063A GEN
Solar/Wind Harmer
0.162
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.229
3145893MURPHYS
Solar/Wind Harmer
0.254
3146776BUCKING
Solar/Wind Helper
0.288
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3151261ROARAP2
50/50
0.116
942461AE2-259 GEN
Solar/Wind Harmer
0.001
964241AG1-285 GEN
Solar/Wind Harmer
23.033
971683AH1-343 GEN
Solar/Wind Harmer
6.774
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316212AC1-099_GEN
Solar/Wind Harmer
0.357
315722AD1-056 GEN
Solar/Wind Harmer
2.132
3145796HORNRTN
Solar/Wind Harmer
0.244
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
315821AE2-092 GEN
Solar/Wind Helper
2.528
3151541CLOVER2
50/50
6.756
3151631KERR 6
50/50
0.482
3151281ROARAP4
50/50
0.105
970683AG2-441 GEN
Solar/Wind Harmer
23.642
970681AG2-440 GEN
Solar/Wind Harmer
15.692
970831AG2-522 GEN
Solar/Wind Harmer
7.493
316210AC1-098 GEN
Solar/Wind Harmer
0.64
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.024
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151281ROARAP4
50/50
0.112
316034AC1-036 C
Solar/Wind Harmer
0.025
970401AG2-262 GEN
Solar/Wind Harmer
1.487
971065AG2-659 GEN
Solar/Wind Harmer
8.305
316129AC1-054 GEN
Solar/Wind Harmer
0.696
960081AF2-299 GEN
Solar/Wind Harmer
0.937
3145783HORNRTN
Solar/Wind Harmer
0.091
3145796HORNRTN
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
3151391GASTONA
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
970257AG2-171 GEN
Solar/Wind Harmer
12.322
971775AH1-396 GEN
Solar/Wind Harmer
0.616
3146233WITAKRS
Solar/Wind Harmer
0.335
3151391GASTONA
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.872
970685AG2-442 GEN
Solar/Wind Harmer
30.722
315785AD2-033 C
Solar/Wind Harmer
2.997
315693AD1-088 GEN
Solar/Wind Harmer
17.627
957481AF2-042 GEN
Solar/Wind Harmer
89.874
3146233WITAKRS
Solar/Wind Harmer
0.266
3145493TOT1
Solar/Wind Harmer
0.257
3147043LAWRENC
50/50
1.535
971629AH1-314 GEN
50/50
5.749
316131AB2-060 GEN
Solar/Wind Harmer
0.958
3147123OTTER R
Solar/Wind Harmer
0.04
316359AB2-059 GEN
Solar/Wind Harmer
0.227
3142053HEARTS
Solar/Wind Harmer
0.112
3146083TARBORO
Solar/Wind Harmer
0.058
3151411GASTONB
50/50
0.163
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.411
316011AB1-132 GEN
Solar/Wind Harmer
1.102
3145893MURPHYS
Solar/Wind Harmer
0.096
3145893MURPHYS
Solar/Wind Harmer
0.057
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
970535AG2-341 GEN
50/50
4.746
3151381ROSEMG2
50/50
0.103
964791AG1-342 GEN
Solar/Wind Harmer
4.866
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.873
961601AG1-000A GEN
Solar/Wind Harmer
1.103
3145453TOT5
Solar/Wind Harmer
0.081
3145893MURPHYS
Solar/Wind Harmer
0.383
3145893MURPHYS
Solar/Wind Harmer
0.103
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.22
3151371ROSEMS1
50/50
0.136
970099AG2-077 GEN
Solar/Wind Harmer
35.95
962561AG1-105 GEN
Solar/Wind Harmer
12.524
3145783HORNRTN
Solar/Wind Harmer
1.617
3145783HORNRTN
Solar/Wind Harmer
1.294
3145783HORNRTN
Solar/Wind Harmer
0.404
3145783HORNRTN
Solar/Wind Harmer
0.162
316263AC1-034 GEN
Solar/Wind Harmer
2.427
315724AD1-057 GEN
Solar/Wind Harmer
1.189
3145796HORNRTN
Solar/Wind Harmer
0.183
962571AG1-106 GEN
Solar/Wind Harmer
0.864
3145603CNETO
Solar/Wind Harmer
0.054
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3146233WITAKRS
Solar/Wind Harmer
0.045
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
22.154
970323AG2-213 GEN
Solar/Wind Harmer
16.429
313506AB2-031 GEN
Solar/Wind Harmer
0.294
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
316049AB1-081 GEN
Solar/Wind Harmer
0.363
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3151601KERR 3
50/50
0.482
3146033SCOT NK
Solar/Wind Harmer
0.257
316405AF2-144 C
Solar/Wind Helper
0.233
3147133PAMPLIN
Solar/Wind Harmer
0.463
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.481
970933AG2-581 GEN
Solar/Wind Harmer
27.443
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.34 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:773.73
MW Contribution:
5.75
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:168.25 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:941.05
MW Contribution:
5.97
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
33.983
961791AG1-021 GEN
Solar/Wind Harmer
4.385
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.386
946301AF1-294 GEN
Solar/Wind Harmer
9.014
3144303KENBRDG
Solar/Wind Harmer
0.308
3137643SOCKMAN
Solar/Wind Harmer
0.379
316426AA2-053 GEN
Solar/Wind Harmer
0.29
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315652AC1-086 GEN
Solar/Wind Harmer
6.683
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3151561HALLBR1
50/50
0.158
3151411GASTONB
50/50
0.163
315607AA1-063A GEN
Solar/Wind Harmer
0.162
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.229
3145893MURPHYS
Solar/Wind Harmer
0.254
3146776BUCKING
Solar/Wind Helper
0.288
3151541CLOVER2
50/50
6.756
3151631KERR 6
50/50
0.482
3151281ROARAP4
50/50
0.105
970683AG2-441 GEN
Solar/Wind Harmer
23.642
970681AG2-440 GEN
Solar/Wind Harmer
15.692
970831AG2-522 GEN
Solar/Wind Harmer
7.493
316210AC1-098 GEN
Solar/Wind Harmer
0.64
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.024
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
316322AB2-045
Solar/Wind Helper
0.807
316258AE1-075 C
Solar/Wind Helper
0.279
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3151411GASTONB
50/50
0.163
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.411
316011AB1-132 GEN
Solar/Wind Harmer
1.102
3145893MURPHYS
Solar/Wind Harmer
0.096
3145893MURPHYS
Solar/Wind Harmer
0.057
3146776BUCKING
Solar/Wind Helper
0.259
270494AE1-108_GEN
Solar/Wind Helper
3.721
970535AG2-341 GEN
50/50
4.746
3151381ROSEMG2
50/50
0.103
964791AG1-342 GEN
Solar/Wind Harmer
4.866
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.873
961601AG1-000A GEN
Solar/Wind Harmer
1.103
3145453TOT5
Solar/Wind Harmer
0.081
3145893MURPHYS
Solar/Wind Harmer
0.383
3145893MURPHYS
Solar/Wind Harmer
0.103
3146776BUCKING
Solar/Wind Helper
2.884
3146776BUCKING
Solar/Wind Helper
0.234
316313AB2-026
Solar/Wind Helper
0.31
970909AG2-566 GEN
50/50
5.538
3144293JTRSVLE
50/50
1.157
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.22
3151371ROSEMS1
50/50
0.136
970099AG2-077 GEN
Solar/Wind Harmer
35.95
962561AG1-105 GEN
Solar/Wind Harmer
12.524
3145783HORNRTN
Solar/Wind Harmer
1.617
3145783HORNRTN
Solar/Wind Harmer
1.294
3145783HORNRTN
Solar/Wind Harmer
0.404
3145783HORNRTN
Solar/Wind Harmer
0.162
316263AC1-034 GEN
Solar/Wind Harmer
2.427
315724AD1-057 GEN
Solar/Wind Harmer
1.189
3145796HORNRTN
Solar/Wind Harmer
0.183
962571AG1-106 GEN
Solar/Wind Harmer
0.864
3145603CNETO
Solar/Wind Harmer
0.054
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.637
3151261ROARAP2
50/50
0.116
942461AE2-259 GEN
Solar/Wind Harmer
0.001
964241AG1-285 GEN
Solar/Wind Harmer
23.033
971683AH1-343 GEN
Solar/Wind Harmer
6.774
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316212AC1-099_GEN
Solar/Wind Harmer
0.357
315722AD1-056 GEN
Solar/Wind Harmer
2.132
3145796HORNRTN
Solar/Wind Harmer
0.244
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
315821AE2-092 GEN
Solar/Wind Helper
2.528
3147043LAWRENC
50/50
1.535
971629AH1-314 GEN
50/50
5.749
316131AB2-060 GEN
Solar/Wind Harmer
0.958
3147123OTTER R
Solar/Wind Harmer
0.04
316359AB2-059 GEN
Solar/Wind Harmer
0.227
3142053HEARTS
Solar/Wind Harmer
0.112
3146083TARBORO
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
1.453
959311AF2-222 GEN
Solar/Wind Harmer
33.659
316478AD1-087 GEN
Solar/Wind Harmer
1.097
3147043LAWRENC
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.508
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.044
971623AH1-311 GEN
Solar/Wind Harmer
0.128
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3151391GASTONA
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.872
970685AG2-442 GEN
Solar/Wind Harmer
30.722
315785AD2-033 C
Solar/Wind Harmer
2.997
315693AD1-088 GEN
Solar/Wind Harmer
17.627
957481AF2-042 GEN
Solar/Wind Harmer
89.874
3146233WITAKRS
Solar/Wind Harmer
0.266
3145493TOT1
Solar/Wind Harmer
0.257
3151391GASTONA
50/50
0.163
3146926FARMVIL
Solar/Wind Harmer
0.379
970257AG2-171 GEN
Solar/Wind Harmer
12.322
971775AH1-396 GEN
Solar/Wind Harmer
0.616
3146233WITAKRS
Solar/Wind Harmer
0.335
3146233WITAKRS
Solar/Wind Harmer
0.045
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
22.154
970323AG2-213 GEN
Solar/Wind Harmer
16.429
313506AB2-031 GEN
Solar/Wind Harmer
0.294
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
316049AB1-081 GEN
Solar/Wind Harmer
0.363
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3151601KERR 3
50/50
0.482
3146033SCOT NK
Solar/Wind Harmer
0.257
316405AF2-144 C
Solar/Wind Helper
0.233
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.805
3151281ROARAP4
50/50
0.112
316034AC1-036 C
Solar/Wind Harmer
0.025
970401AG2-262 GEN
Solar/Wind Harmer
1.487
971065AG2-659 GEN
Solar/Wind Harmer
8.305
316129AC1-054 GEN
Solar/Wind Harmer
0.696
960081AF2-299 GEN
Solar/Wind Harmer
0.937
3145783HORNRTN
Solar/Wind Harmer
0.091
3145796HORNRTN
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
0.463
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.481
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
LAGNLTFEXP_LAGN->PJM
CLTF
2.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.133
TVALTFEXP_TVA->PJM
CLTF
1.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.294
MECLTFEXP_MEC->PJM
CLTF
0.996
CPLELTFEXP_CPLE->PJM
CLTF
5.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.629
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.387
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.16 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:818.17
MW Contribution:
5.73
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.07 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:983.41
MW Contribution:
5.95
Bus #Bus NameTypeMW Contribution
3147133PAMPLIN
Solar/Wind Harmer
1.452
959311AF2-222 GEN
Solar/Wind Harmer
33.641
316478AD1-087 GEN
Solar/Wind Harmer
1.096
3147043LAWRENC
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.507
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.044
971623AH1-311 GEN
Solar/Wind Harmer
0.127
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.274
3145543BTLEBRO
Solar/Wind Harmer
0.064
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
33.974
961791AG1-021 GEN
Solar/Wind Harmer
4.383
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.385
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
946301AF1-294 GEN
Solar/Wind Harmer
9.009
3144303KENBRDG
Solar/Wind Harmer
0.308
971967AH1-528 GEN
Solar/Wind Harmer
54.853
3137643SOCKMAN
Solar/Wind Harmer
0.378
316426AA2-053 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315652AC1-086 GEN
Solar/Wind Harmer
6.661
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3151561HALLBR1
50/50
0.157
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.304
315607AA1-063A GEN
Solar/Wind Harmer
0.161
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.253
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3151261ROARAP2
50/50
0.115
972003AH1-546 GEN
Solar/Wind Harmer
31.155
942461AE2-259 GEN
Solar/Wind Harmer
0.001
964241AG1-285 GEN
Solar/Wind Harmer
23.019
971683AH1-343 GEN
Solar/Wind Harmer
6.767
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316212AC1-099_GEN
Solar/Wind Harmer
0.356
315722AD1-056 GEN
Solar/Wind Harmer
2.125
3145796HORNRTN
Solar/Wind Harmer
0.243
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
315821AE2-092 GEN
Solar/Wind Helper
2.532
3151541CLOVER2
50/50
6.751
3151631KERR 6
50/50
0.481
3151281ROARAP4
50/50
0.105
970683AG2-441 GEN
Solar/Wind Harmer
23.63
970681AG2-440 GEN
Solar/Wind Harmer
15.684
970831AG2-522 GEN
Solar/Wind Harmer
7.484
316210AC1-098 GEN
Solar/Wind Harmer
0.638
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.024
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
316258AE1-075 C
Solar/Wind Helper
0.28
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151281ROARAP4
50/50
0.112
316034AC1-036 C
Solar/Wind Harmer
0.025
970401AG2-262 GEN
Solar/Wind Harmer
1.486
971065AG2-659 GEN
Solar/Wind Harmer
8.296
316129AC1-054 GEN
Solar/Wind Harmer
0.695
960081AF2-299 GEN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.091
3145796HORNRTN
Solar/Wind Harmer
0.2
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
3151391GASTONA
50/50
0.162
3146926FARMVIL
Solar/Wind Harmer
0.379
970257AG2-171 GEN
Solar/Wind Harmer
12.316
971775AH1-396 GEN
Solar/Wind Harmer
0.616
3146233WITAKRS
Solar/Wind Harmer
0.334
3146233WITAKRS
Solar/Wind Harmer
0.045
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0
3151391GASTONA
50/50
0.162
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.87
970685AG2-442 GEN
Solar/Wind Harmer
30.706
315785AD2-033 C
Solar/Wind Harmer
2.995
315693AD1-088 GEN
Solar/Wind Harmer
17.617
957481AF2-042 GEN
Solar/Wind Harmer
89.82
3146233WITAKRS
Solar/Wind Harmer
0.265
3145493TOT1
Solar/Wind Harmer
0.257
3147043LAWRENC
50/50
1.533
971629AH1-314 GEN
50/50
5.731
316131AB2-060 GEN
Solar/Wind Harmer
0.958
3147123OTTER R
Solar/Wind Harmer
0.04
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.112
3146083TARBORO
Solar/Wind Harmer
0.058
970535AG2-341 GEN
50/50
4.743
3151381ROSEMG2
50/50
0.102
3146776BUCKING
Solar/Wind Harmer
3.039
3146776BUCKING
Solar/Wind Harmer
0.246
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.396
316011AB1-132 GEN
Solar/Wind Harmer
1.098
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
270494AE1-108_GEN
Solar/Wind Helper
3.726
964791AG1-342 GEN
Solar/Wind Harmer
4.862
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.862
961601AG1-000A GEN
Solar/Wind Harmer
1.099
3145453TOT5
Solar/Wind Harmer
0.08
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
0.103
316313AB2-026
Solar/Wind Helper
0.311
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.219
3151371ROSEMS1
50/50
0.136
970099AG2-077 GEN
Solar/Wind Harmer
35.928
962561AG1-105 GEN
Solar/Wind Harmer
12.514
3145783HORNRTN
Solar/Wind Harmer
1.613
3145783HORNRTN
Solar/Wind Harmer
1.291
3145783HORNRTN
Solar/Wind Harmer
0.403
3145783HORNRTN
Solar/Wind Harmer
0.161
316263AC1-034 GEN
Solar/Wind Harmer
2.419
315724AD1-057 GEN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.182
962571AG1-106 GEN
Solar/Wind Harmer
0.862
3145603CNETO
Solar/Wind Harmer
0.054
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
22.145
970323AG2-213 GEN
Solar/Wind Harmer
16.421
313506AB2-031 GEN
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3151601KERR 3
50/50
0.481
3146033SCOT NK
Solar/Wind Harmer
0.257
316405AF2-144 C
Solar/Wind Helper
0.233
3147133PAMPLIN
Solar/Wind Harmer
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.479
970933AG2-581 GEN
Solar/Wind Harmer
27.427
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.31 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:801.9
MW Contribution:
5.73
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:169.49 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:968.67
MW Contribution:
5.95
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
33.974
961791AG1-021 GEN
Solar/Wind Harmer
4.383
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.385
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
946301AF1-294 GEN
Solar/Wind Harmer
9.009
3144303KENBRDG
Solar/Wind Harmer
0.308
3137643SOCKMAN
Solar/Wind Harmer
0.378
316426AA2-053 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315652AC1-086 GEN
Solar/Wind Harmer
6.661
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3151561HALLBR1
50/50
0.157
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.304
315607AA1-063A GEN
Solar/Wind Harmer
0.161
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.253
3151541CLOVER2
50/50
6.751
3151631KERR 6
50/50
0.481
3151281ROARAP4
50/50
0.105
970683AG2-441 GEN
Solar/Wind Harmer
23.63
970681AG2-440 GEN
Solar/Wind Harmer
15.684
970831AG2-522 GEN
Solar/Wind Harmer
7.484
316210AC1-098 GEN
Solar/Wind Harmer
0.638
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.024
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
316258AE1-075 C
Solar/Wind Helper
0.28
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151281ROARAP4
50/50
0.112
316034AC1-036 C
Solar/Wind Harmer
0.025
970401AG2-262 GEN
Solar/Wind Harmer
1.486
971065AG2-659 GEN
Solar/Wind Harmer
8.296
316129AC1-054 GEN
Solar/Wind Harmer
0.695
960081AF2-299 GEN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.091
3145796HORNRTN
Solar/Wind Harmer
0.2
3147043LAWRENC
50/50
1.533
971629AH1-314 GEN
50/50
5.731
316131AB2-060 GEN
Solar/Wind Harmer
0.958
3147123OTTER R
Solar/Wind Harmer
0.04
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.112
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.274
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.396
316011AB1-132 GEN
Solar/Wind Harmer
1.098
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
270494AE1-108_GEN
Solar/Wind Helper
3.726
970535AG2-341 GEN
50/50
4.743
3151381ROSEMG2
50/50
0.102
3146776BUCKING
Solar/Wind Harmer
3.039
3146776BUCKING
Solar/Wind Harmer
0.246
964791AG1-342 GEN
Solar/Wind Harmer
4.862
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.862
961601AG1-000A GEN
Solar/Wind Harmer
1.099
3145453TOT5
Solar/Wind Harmer
0.08
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
0.103
316313AB2-026
Solar/Wind Helper
0.311
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.219
3151371ROSEMS1
50/50
0.136
970099AG2-077 GEN
Solar/Wind Harmer
35.928
962561AG1-105 GEN
Solar/Wind Harmer
12.514
3145783HORNRTN
Solar/Wind Harmer
1.613
3145783HORNRTN
Solar/Wind Harmer
1.291
3145783HORNRTN
Solar/Wind Harmer
0.403
3145783HORNRTN
Solar/Wind Harmer
0.161
316263AC1-034 GEN
Solar/Wind Harmer
2.419
315724AD1-057 GEN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.182
962571AG1-106 GEN
Solar/Wind Harmer
0.862
3145603CNETO
Solar/Wind Harmer
0.054
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3151261ROARAP2
50/50
0.115
972003AH1-546 GEN
Solar/Wind Harmer
31.155
942461AE2-259 GEN
Solar/Wind Harmer
0.001
964241AG1-285 GEN
Solar/Wind Harmer
23.019
971683AH1-343 GEN
Solar/Wind Harmer
6.767
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316212AC1-099_GEN
Solar/Wind Harmer
0.356
315722AD1-056 GEN
Solar/Wind Harmer
2.125
3145796HORNRTN
Solar/Wind Harmer
0.243
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
315821AE2-092 GEN
Solar/Wind Helper
2.532
3146083TARBORO
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
1.452
959311AF2-222 GEN
Solar/Wind Harmer
33.641
316478AD1-087 GEN
Solar/Wind Harmer
1.096
3147043LAWRENC
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.507
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.044
971623AH1-311 GEN
Solar/Wind Harmer
0.127
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3151391GASTONA
50/50
0.162
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.87
970685AG2-442 GEN
Solar/Wind Harmer
30.706
315785AD2-033 C
Solar/Wind Harmer
2.995
315693AD1-088 GEN
Solar/Wind Harmer
17.617
957481AF2-042 GEN
Solar/Wind Harmer
89.82
3146233WITAKRS
Solar/Wind Harmer
0.265
3145493TOT1
Solar/Wind Harmer
0.257
3151391GASTONA
50/50
0.162
3146926FARMVIL
Solar/Wind Harmer
0.379
970257AG2-171 GEN
Solar/Wind Harmer
12.316
971775AH1-396 GEN
Solar/Wind Harmer
0.616
3146233WITAKRS
Solar/Wind Harmer
0.334
3146233WITAKRS
Solar/Wind Harmer
0.045
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
970301AG2-198 GEN
Solar/Wind Harmer
22.145
970323AG2-213 GEN
Solar/Wind Harmer
16.421
313506AB2-031 GEN
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3151601KERR 3
50/50
0.481
3146033SCOT NK
Solar/Wind Harmer
0.257
316405AF2-144 C
Solar/Wind Helper
0.233
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.479
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
314677 to 972002 ckt 1
314692 to 971844 ckt 1
304070 to 316281 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC115.17 %571.52B658.25
5.0
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC112.6 %571.52B643.52
5.0
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC109.54 %997.0C1092.15
13.5
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC102.99 %814.98B839.35
13.59
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC100.81 %814.98B821.61
13.59
GD2DVP
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC110.56 %571.52B631.87
5.0
GD2DVP
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC107.99 %571.52B617.19
5.0
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC104.49 %997.0C1041.75
13.53
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC130.61 %4070.2B5316.1
19.08
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC125.49 %4070.2B5107.87
19.08
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 58572_SRT-A
BreakerAC117.11 %4996.0C5851.06
19.08
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-5: W72_SRT-A
BreakerAC116.55 %4996.0C5822.84
19.02
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: XT585_SRT-S
BreakerAC109.34 %4996.0C5462.74
19.08
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 54472_SRT-S
BreakerAC104.29 %2858.0C2980.61
11.61
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC118.98 %4070.2B4842.86
17.94
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC105.0 %4996.0C5245.63
17.94
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC104.56 %4996.0C5223.84
17.89
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC103.0 %4996.0C5145.98
17.75
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC127.1 %4070.2B5173.4
17.94
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC113.85 %4996.0C5687.87
17.94
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC113.35 %4996.0C5662.94
17.89
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC111.73 %4996.0C5581.87
17.75
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 591_SRT-S
SingleAC101.31 %4070.2B4123.45
11.74
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC116.16 %571.52B663.9
5.0
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC113.59 %571.52B649.19
5.0
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC121.2 %4070.2B4933.15
17.94
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC108.55 %4996.0C5423.36
17.94
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC108.09 %4996.0C5400.34
17.89
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC106.51 %4996.0C5321.19
17.75

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.17 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:658.25
MW Contribution:
5.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
1.086
316222AC1-221 GEN
Solar/Wind Harmer
0.443
316283AC2-100 C
Solar/Wind Harmer
0.206
3147133PAMPLIN
Solar/Wind Helper
1.064
970535AG2-341 GEN
50/50
1.993
316118AC1-105 GEN
Solar/Wind Harmer
0.373
964791AG1-342 GEN
Solar/Wind Harmer
2.429
942751AE2-291 GEN
Solar/Wind Harmer
5.335
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
316313AB2-026
Solar/Wind Helper
0.242
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.319
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970301AG2-198 GEN
Solar/Wind Harmer
25.388
3151601KERR 3
50/50
0.297
316405AF2-144 C
Solar/Wind Helper
0.182
3151541CLOVER2
50/50
6.689
3151631KERR 6
50/50
0.297
970831AG2-522 GEN
Solar/Wind Harmer
4.544
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
3151531CLOVER1
50/50
6.741
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.07
316129AC1-054 GEN
Solar/Wind Harmer
0.424
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
3146776BUCKING
Solar/Wind Helper
0.217
971629AH1-314 GEN
50/50
5.005
316131AB2-060 GEN
Solar/Wind Harmer
0.206
970909AG2-566 GEN
50/50
6.347
970099AG2-077 GEN
Solar/Wind Harmer
36.297
962561AG1-105 GEN
Solar/Wind Harmer
5.688
315693AD1-088 GEN
Solar/Wind Harmer
18.249
957481AF2-042 GEN
Solar/Wind Harmer
90.743
3146926FARMVIL
Solar/Wind Helper
0.441
3146926FARMVIL
Solar/Wind Helper
0.441
970933AG2-581 GEN
Solar/Wind Harmer
27.858
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
3146776BUCKING
Solar/Wind Helper
0.196
270494AE1-108_GEN
Solar/Wind Helper
2.774
971967AH1-528 GEN
Solar/Wind Harmer
55.714
970413AG2-270 GEN
50/50
29.357
971683AH1-343 GEN
Solar/Wind Harmer
5.14
316123AC1-075 GEN
Solar/Wind Harmer
0.149
942461AE2-259 GEN
Solar/Wind Helper
3.543
315821AE2-092 GEN
Solar/Wind Helper
1.922
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.6 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:643.52
MW Contribution:
5.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
1.086
316222AC1-221 GEN
Solar/Wind Harmer
0.443
316283AC2-100 C
Solar/Wind Harmer
0.206
3147133PAMPLIN
Solar/Wind Helper
1.064
970535AG2-341 GEN
50/50
1.993
316118AC1-105 GEN
Solar/Wind Harmer
0.373
964791AG1-342 GEN
Solar/Wind Harmer
2.429
942751AE2-291 GEN
Solar/Wind Harmer
5.335
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970301AG2-198 GEN
Solar/Wind Harmer
25.388
3151601KERR 3
50/50
0.297
316405AF2-144 C
Solar/Wind Helper
0.182
3151541CLOVER2
50/50
6.689
3151631KERR 6
50/50
0.297
970831AG2-522 GEN
Solar/Wind Harmer
4.544
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
3151531CLOVER1
50/50
6.741
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.07
316129AC1-054 GEN
Solar/Wind Harmer
0.424
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
316313AB2-026
Solar/Wind Helper
0.242
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.319
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
971629AH1-314 GEN
50/50
5.005
316131AB2-060 GEN
Solar/Wind Harmer
0.206
970909AG2-566 GEN
50/50
6.347
970099AG2-077 GEN
Solar/Wind Harmer
36.297
962561AG1-105 GEN
Solar/Wind Harmer
5.688
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
3146776BUCKING
Solar/Wind Helper
0.217
315693AD1-088 GEN
Solar/Wind Harmer
18.249
957481AF2-042 GEN
Solar/Wind Harmer
90.743
3146926FARMVIL
Solar/Wind Helper
0.441
3146926FARMVIL
Solar/Wind Helper
0.441
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
3146776BUCKING
Solar/Wind Helper
0.196
270494AE1-108_GEN
Solar/Wind Helper
2.774
970413AG2-270 GEN
50/50
29.357
971683AH1-343 GEN
Solar/Wind Harmer
5.14
316123AC1-075 GEN
Solar/Wind Harmer
0.149
942461AE2-259 GEN
Solar/Wind Helper
3.543
315821AE2-092 GEN
Solar/Wind Helper
1.922
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.54 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1092.15
MW Contribution:
13.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.135
24728405LEESVG
50/50
0.135
316003AC1-222 GEN
Solar/Wind Harmer
3.847
316222AC1-221 GEN
Solar/Wind Harmer
3.092
316283AC2-100 C
Solar/Wind Harmer
2.821
270574AD1-017 GEN2
Solar/Wind Harmer
4.505
943811AF1-049 GEN
Solar/Wind Harmer
2.871
270336AE1-100 GEN
Solar/Wind Harmer
1.165
316478AD1-087 GEN
Solar/Wind Helper
3.088
3145336SMITFLD
Solar/Wind Helper
0.06
316017AA1-139 ULT1
Solar/Wind Helper
0.662
3146456SLIGO L269
Solar/Wind Helper
0.142
3142946ENON
Solar/Wind Helper
0.045
316473AC1-191 GEN
Solar/Wind Helper
0.745
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
270455AD2-022 GEN
Solar/Wind Harmer
3.533
270197AD1-017 GEN1
Solar/Wind Harmer
1.351
316486AD2-202 GEN
Solar/Wind Helper
0.904
316059AD1-063 C
Solar/Wind Helper
0.137
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.054
313526AB2-022
Solar/Wind Helper
0.2
3152661PLYWOOD A
50/50
0.676
942671AE2-283 GEN
Solar/Wind Harmer
4.827
316049AB1-081 GEN
Solar/Wind Harmer
0.749
3145506HICKORY
Solar/Wind Helper
0.598
3145506HICKORY
Solar/Wind Helper
0.359
3145506HICKORY
Solar/Wind Helper
0.09
316033AB2-134 GEN
Solar/Wind Helper
0.505
316339AD2-160 GEN
Solar/Wind Helper
0.556
316388AE2-253 GEN
Solar/Wind Helper
0.556
3137176SLIGO L2192
Solar/Wind Helper
0.568
3130086AYDLETT
Solar/Wind Helper
0.563
316487AF1-042 GEN
Solar/Wind Helper
0.133
970581AG2-369 GEN
Solar/Wind Harmer
8.554
270069AE2-166 C O1
Solar/Wind Harmer
5.959
971981AH1-535 GEN
Solar/Wind Harmer
4.612
3143316POE
Solar/Wind Helper
0.633
316236AE1-162_GEN
Solar/Wind Helper
0.203
316382AG1-145 C
Solar/Wind Helper
0.194
316159AE1-175 C
Solar/Wind Helper
0.218
316405AF2-144 C
Solar/Wind Helper
0.16
3141873WAN 176
Solar/Wind Helper
0.027
3143873LANEXA
Solar/Wind Helper
0.081
3138133OCRAN
Solar/Wind Helper
0.04
3146486SUNBURY
Solar/Wind Helper
0.128
3146486SUNBURY
Solar/Wind Helper
0.128
3145176PASQUOTANK
Solar/Wind Helper
0.078
970087AG2-069 GEN
Solar/Wind Harmer
14.92
970223AG2-152 GEN
Solar/Wind Harmer
13.344
270018AE2-047 C O1
Solar/Wind Harmer
1.017
3146926FARMVIL
Solar/Wind Helper
0.145
316381AD1-082 GEN
Solar/Wind Helper
0.759
316369SG1_INVT
Solar/Wind Helper
0.703
319010AE1-072 C
Solar/Wind Helper
1.621
3143226MDLTHAN
Solar/Wind Helper
0.141
3142543TWELFTH
Solar/Wind Helper
0.013
315662AE1-191 GEN
Solar/Wind Helper
0.733
316280AD1-041 GEN
Solar/Wind Helper
0.458
3138133OCRAN
Solar/Wind Helper
0.081
316404AE1-155 C
Solar/Wind Helper
1.113
316118AC1-105 GEN
Solar/Wind Harmer
2.349
942751AE2-291 GEN
Solar/Wind Harmer
17.164
964791AG1-342 GEN
Solar/Wind Harmer
5.581
961601AG1-000A GEN
Solar/Wind Harmer
2.753
3146776BUCKING
Solar/Wind Helper
0.778
3146776BUCKING
Solar/Wind Helper
0.063
316240AF1-291 C
Solar/Wind Helper
0.198
316313AB2-026
Solar/Wind Helper
0.213
316156AD2-030 GEN
Solar/Wind Helper
0.206
315666AE1-190 GEN
Solar/Wind Helper
0.183
966871AG1-558 GEN
Solar/Wind Helper
0.164
316435W1029_GEN3
Solar/Wind Helper
0.484
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
270457AD2-023 GEN
Solar/Wind Harmer
1.791
970085AG2-068 GEN
Solar/Wind Harmer
9.947
316018AA1-139 ULT2
Solar/Wind Helper
0.623
316233AE1-074 FULL
Solar/Wind Helper
0.211
957601AF2-054 GEN
Solar/Wind Helper
0.183
3141813NORNECK
Solar/Wind Helper
0.128
3151561HALLBR1
50/50
0.369
970919AG2-571 GEN
Solar/Wind Harmer
5.036
941801AE2-185 GEN
Solar/Wind Harmer
5.465
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.078
315773AC2-141 GEN
Solar/Wind Helper
3.625
316036AC1-147 C
Solar/Wind Helper
0.236
316132AB2-190 GEN1
Solar/Wind Helper
0.827
3141726DUNNSVL
Solar/Wind Helper
0.513
316337AD2-073 GEN
Solar/Wind Helper
0.188
3146516WINFALL
Solar/Wind Helper
0.379
3146516WINFALL
Solar/Wind Helper
0.117
316322AB2-045
Solar/Wind Helper
0.218
316316AC1-027 C
Solar/Wind Helper
0.242
315839AE2-212 C
Solar/Wind Helper
0.205
315697AD1-025 GEN
Solar/Wind Helper
1.667
957831AF2-077 GEN
Solar/Wind Helper
0.192
316258AE1-075 C
Solar/Wind Helper
0.192
3141913WHIT STONE
Solar/Wind Helper
0.135
316468AD1-105 GEN
Solar/Wind Helper
0.549
971629AH1-314 GEN
50/50
13.497
3147123OTTER R
Solar/Wind Harmer
-0.01
270030AE2-140 GEN
Solar/Wind Harmer
14.76
316359AB2-059 GEN
Solar/Wind Harmer
0.936
3142053HEARTS
Solar/Wind Harmer
0.082
316375AC2-012 GEN
Solar/Wind Helper
0.406
3145336SMITFLD
Solar/Wind Helper
0.602
3146456SLIGO L269
Solar/Wind Helper
0.142
3142433PROV 92
Solar/Wind Helper
0.545
3141766HARMONY
Solar/Wind Helper
0.027
315975AC1-164 GENB
Solar/Wind Helper
0.051
3142416OLDCHRC
Solar/Wind Helper
0.329
3142416OLDCHRC
Solar/Wind Helper
0.126
970401AG2-262 GEN
Solar/Wind Harmer
1.705
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
270016AE1-250 BESS
Solar/Wind Harmer
2.224
315671AE2-027_GEN
Solar/Wind Helper
1.203
316072AD1-144
Solar/Wind Helper
0.163
3143526WINTERP
Solar/Wind Helper
0.717
964211AG1-282 GEN
Solar/Wind Helper
0.173
315687AD1-152 GEN
Solar/Wind Harmer
8.923
316248AF1-058 C
Solar/Wind Harmer
1.267
962561AG1-105 GEN
Solar/Wind Harmer
12.789
270013AE1-250 PV
Solar/Wind Harmer
2.224
316263AC1-034 GEN
Solar/Wind Harmer
3.262
316185AD1-033 GEN
Solar/Wind Helper
0.717
3143526WINTERP
Solar/Wind Helper
0.717
3144356SAPONY
Solar/Wind Helper
0.233
316315AB2-025 C
Solar/Wind Helper
0.199
270173AC1-122 GEN
Solar/Wind Harmer
1.092
961601AG1-000A GEN
Solar/Wind Harmer
2.787
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Helper
0.07
3144536CHRHLND
Solar/Wind Helper
0.023
3142956BIRDNECK
Solar/Wind Helper
0.103
316305AF2-043 C
Solar/Wind Helper
0.189
316320Y1-086
Solar/Wind Helper
0.059
316223AC1-118
Solar/Wind Helper
0.184
3146516WINFALL
Solar/Wind Helper
0.117
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
316294AC1-161 GEN
Solar/Wind Helper
3.081
316349AD2-085 GEN
Solar/Wind Helper
0.637
3142946ENON
Solar/Wind Helper
0.014
315976AC1-164 GENA
Solar/Wind Helper
1.72
316169AC1-164_GENC
Solar/Wind Helper
1.486
3146386ELIZ CT
Solar/Wind Helper
0.131
316431W1029_GEN1
Solar/Wind Helper
0.484
316433W1029_GEN2
Solar/Wind Helper
0.484
970917AG2-570 GEN
Solar/Wind Harmer
39.781
316217AC1-145 GEN
Solar/Wind Harmer
2.363
316197AC1-042 GEN
Solar/Wind Harmer
1.792
3146926FARMVIL
Solar/Wind Helper
0.145
3144873MCLAUGH
Solar/Wind Helper
0.004
316458AB2-190 GEN2
Solar/Wind Helper
0.827
316246AF1-032 C
Solar/Wind Helper
0.161
316321Z2-027
Solar/Wind Helper
0.193
3141906WESTMOR
Solar/Wind Helper
0.048
316312AB1-027
Solar/Wind Helper
0.242
971683AH1-343 GEN
Solar/Wind Harmer
15.734
316123AC1-075 GEN
Solar/Wind Harmer
3.227
3147312GRETNA
Solar/Wind Harmer
-0.003
942461AE2-259 GEN
Solar/Wind Helper
1.132
316075AC2-137 C
Solar/Wind Helper
0.201
316484AD2-074 GEN
Solar/Wind Helper
0.254
316077AC2-138 C
Solar/Wind Helper
0.12
LAGNLTFEXP_LAGN->PJM
CLTF
9.216
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.314
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.172
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.161
CPLELTFEXP_CPLE->PJM
CLTF
11.158
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.64
TVALTFEXP_TVA->PJM
CLTF
4.614
MECLTFEXP_MEC->PJM
CLTF
5.236
SIGELTFEXP_SIGE->PJM
CLTF
0.16
NYPJM->LTFIMP_NY
CLTF
0.751
LGEELTFEXP_LGEE->PJM
CLTF
1.985
WECLTFEXP_WEC->PJM
CLTF
1.051

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.99 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:839.35
MW Contribution:
13.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.136
24728405LEESVG
50/50
0.136
316222AC1-221 GEN
Solar/Wind Harmer
1.127
316283AC2-100 C
Solar/Wind Harmer
0.523
943811AF1-049 GEN
Solar/Wind Harmer
0
971623AH1-311 GEN
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Helper
3.078
3145336SMITFLD
Solar/Wind Helper
0.059
316017AA1-139 ULT1
Solar/Wind Helper
0.653
3146456SLIGO L269
Solar/Wind Helper
0.141
3142946ENON
Solar/Wind Helper
0.045
316473AC1-191 GEN
Solar/Wind Helper
0.733
3152661PLYWOOD A
50/50
0.678
942671AE2-283 GEN
Solar/Wind Harmer
3.253
316049AB1-081 GEN
Solar/Wind Harmer
0.358
3145506HICKORY
Solar/Wind Helper
0.59
3145506HICKORY
Solar/Wind Helper
0.354
3145506HICKORY
Solar/Wind Helper
0.089
316033AB2-134 GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
0.548
316388AE2-253 GEN
Solar/Wind Helper
0.548
3137176SLIGO L2192
Solar/Wind Helper
0.56
3130086AYDLETT
Solar/Wind Helper
0.556
316487AF1-042 GEN
Solar/Wind Helper
0.131
970581AG2-369 GEN
Solar/Wind Harmer
6.542
270069AE2-166 C O1
Solar/Wind Harmer
4.205
971981AH1-535 GEN
Solar/Wind Harmer
2.18
3143316POE
Solar/Wind Helper
0.625
316236AE1-162_GEN
Solar/Wind Helper
0.2
316382AG1-145 C
Solar/Wind Helper
0.191
316159AE1-175 C
Solar/Wind Helper
0.215
316405AF2-144 C
Solar/Wind Helper
0.158
3141873WAN 176
Solar/Wind Helper
0.027
3143873LANEXA
Solar/Wind Helper
0.08
3138133OCRAN
Solar/Wind Helper
0.04
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3145176PASQUOTANK
Solar/Wind Helper
0.077
24684705SMG5
50/50
0.326
316322AB2-045
Solar/Wind Helper
0.215
316316AC1-027 C
Solar/Wind Helper
0.238
315839AE2-212 C
Solar/Wind Helper
0.203
315697AD1-025 GEN
Solar/Wind Helper
1.645
957831AF2-077 GEN
Solar/Wind Helper
0.189
316258AE1-075 C
Solar/Wind Helper
0.189
3141913WHIT STONE
Solar/Wind Helper
0.133
316468AD1-105 GEN
Solar/Wind Helper
0.539
24684605SMG4
50/50
0.852
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
315671AE2-027_GEN
Solar/Wind Helper
1.187
316072AD1-144
Solar/Wind Helper
0.161
3143526WINTERP
Solar/Wind Helper
0.707
964211AG1-282 GEN
Solar/Wind Helper
0.17
316118AC1-105 GEN
Solar/Wind Harmer
0.783
942751AE2-291 GEN
Solar/Wind Harmer
13.09
964791AG1-342 GEN
Solar/Wind Harmer
4.484
961601AG1-000A GEN
Solar/Wind Harmer
1.126
3146776BUCKING
Solar/Wind Helper
0.77
3146776BUCKING
Solar/Wind Helper
0.062
316240AF1-291 C
Solar/Wind Helper
0.196
316313AB2-026
Solar/Wind Helper
0.21
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
270197AD1-017 GEN1
Solar/Wind Harmer
0.764
316486AD2-202 GEN
Solar/Wind Helper
0.901
316059AD1-063 C
Solar/Wind Helper
0.135
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
971629AH1-314 GEN
50/50
13.585
3147123OTTER R
Solar/Wind Harmer
0.091
270030AE2-140 GEN
Solar/Wind Harmer
10.404
316359AB2-059 GEN
Solar/Wind Harmer
0.224
3142053HEARTS
Solar/Wind Harmer
0.111
316375AC2-012 GEN
Solar/Wind Helper
0.401
3145336SMITFLD
Solar/Wind Helper
0.594
3146456SLIGO L269
Solar/Wind Helper
0.141
3142433PROV 92
Solar/Wind Helper
0.537
3141766HARMONY
Solar/Wind Helper
0.027
315975AC1-164 GENB
Solar/Wind Helper
0.05
3142416OLDCHRC
Solar/Wind Helper
0.324
3142416OLDCHRC
Solar/Wind Helper
0.124
962561AG1-105 GEN
Solar/Wind Harmer
9.76
316263AC1-034 GEN
Solar/Wind Harmer
2.392
316185AD1-033 GEN
Solar/Wind Helper
0.708
3143526WINTERP
Solar/Wind Helper
0.707
3144356SAPONY
Solar/Wind Helper
0.23
316315AB2-025 C
Solar/Wind Helper
0.196
316312AB1-027
Solar/Wind Helper
0.238
3151561HALLBR1
50/50
0.371
970919AG2-571 GEN
Solar/Wind Harmer
5.071
941801AE2-185 GEN
Solar/Wind Harmer
4.182
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146776BUCKING
Solar/Wind Helper
0.077
315773AC2-141 GEN
Solar/Wind Helper
3.583
316036AC1-147 C
Solar/Wind Helper
0.233
316132AB2-190 GEN1
Solar/Wind Helper
0.816
3141726DUNNSVL
Solar/Wind Helper
0.505
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.372
3146516WINFALL
Solar/Wind Helper
0.115
970417AG2-272 GEN
50/50
1.9
24288905REUSENS
50/50
0.013
970087AG2-069 GEN
Solar/Wind Harmer
11.411
970223AG2-152 GEN
Solar/Wind Harmer
9.427
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
0.748
316369SG1_INVT
Solar/Wind Helper
0.693
319010AE1-072 C
Solar/Wind Helper
1.598
3143226MDLTHAN
Solar/Wind Helper
0.139
3142543TWELFTH
Solar/Wind Helper
0.013
24684405SMG2
50/50
0.846
970917AG2-570 GEN
Solar/Wind Harmer
12.677
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.004
316458AB2-190 GEN2
Solar/Wind Helper
0.816
316246AF1-032 C
Solar/Wind Helper
0.159
316321Z2-027
Solar/Wind Helper
0.19
3141906WESTMOR
Solar/Wind Helper
0.047
315662AE1-191 GEN
Solar/Wind Helper
0.723
316280AD1-041 GEN
Solar/Wind Helper
0.452
3138133OCRAN
Solar/Wind Helper
0.08
316404AE1-155 C
Solar/Wind Helper
1.096
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
316294AC1-161 GEN
Solar/Wind Helper
3.045
316349AD2-085 GEN
Solar/Wind Helper
0.628
3142946ENON
Solar/Wind Helper
0.013
315976AC1-164 GENA
Solar/Wind Helper
1.695
316169AC1-164_GENC
Solar/Wind Helper
1.464
3146386ELIZ CT
Solar/Wind Helper
0.129
316431W1029_GEN1
Solar/Wind Helper
0.476
316433W1029_GEN2
Solar/Wind Helper
0.476
961601AG1-000A GEN
Solar/Wind Harmer
4.503
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3146776BUCKING
Solar/Wind Helper
0.069
3144536CHRHLND
Solar/Wind Helper
0.023
3142956BIRDNECK
Solar/Wind Helper
0.102
316305AF2-043 C
Solar/Wind Helper
0.187
316320Y1-086
Solar/Wind Helper
0.058
316223AC1-118
Solar/Wind Helper
0.181
3146516WINFALL
Solar/Wind Helper
0.115
316156AD2-030 GEN
Solar/Wind Helper
0.203
315666AE1-190 GEN
Solar/Wind Helper
0.181
966871AG1-558 GEN
Solar/Wind Helper
0.162
316435W1029_GEN3
Solar/Wind Helper
0.476
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
24684305SMG1
50/50
0.307
970085AG2-068 GEN
Solar/Wind Harmer
7.608
316018AA1-139 ULT2
Solar/Wind Helper
0.615
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141813NORNECK
Solar/Wind Helper
0.126
24684505SMG3
50/50
0.517
971683AH1-343 GEN
Solar/Wind Harmer
11.986
316123AC1-075 GEN
Solar/Wind Harmer
0.357
3147312GRETNA
Solar/Wind Harmer
0.026
942461AE2-259 GEN
Solar/Wind Helper
1.118
316075AC2-137 C
Solar/Wind Helper
0.198
316484AD2-074 GEN
Solar/Wind Helper
0.25
316077AC2-138 C
Solar/Wind Helper
0.118
LAGNLTFEXP_LAGN->PJM
CLTF
9.371
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.544
TVALTFEXP_TVA->PJM
CLTF
4.691
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.451
MECLTFEXP_MEC->PJM
CLTF
5.364
CPLELTFEXP_CPLE->PJM
CLTF
11.241
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.665
SIGELTFEXP_SIGE->PJM
CLTF
0.164
NYPJM->LTFIMP_NY
CLTF
0.702
LGEELTFEXP_LGEE->PJM
CLTF
2.038
WECLTFEXP_WEC->PJM
CLTF
1.08
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.81 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:821.61
MW Contribution:
13.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.136
24728405LEESVG
50/50
0.136
316222AC1-221 GEN
Solar/Wind Harmer
1.127
316283AC2-100 C
Solar/Wind Harmer
0.523
943811AF1-049 GEN
Solar/Wind Harmer
0
971623AH1-311 GEN
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Helper
3.078
3145336SMITFLD
Solar/Wind Helper
0.059
316017AA1-139 ULT1
Solar/Wind Helper
0.653
3146456SLIGO L269
Solar/Wind Helper
0.141
3142946ENON
Solar/Wind Helper
0.045
3152661PLYWOOD A
50/50
0.678
942671AE2-283 GEN
Solar/Wind Harmer
3.253
316049AB1-081 GEN
Solar/Wind Harmer
0.358
3145506HICKORY
Solar/Wind Helper
0.59
3145506HICKORY
Solar/Wind Helper
0.354
3145506HICKORY
Solar/Wind Helper
0.089
970581AG2-369 GEN
Solar/Wind Harmer
6.542
270069AE2-166 C O1
Solar/Wind Harmer
4.205
971981AH1-535 GEN
Solar/Wind Harmer
2.18
3143316POE
Solar/Wind Helper
0.625
316236AE1-162_GEN
Solar/Wind Helper
0.2
316382AG1-145 C
Solar/Wind Helper
0.191
316159AE1-175 C
Solar/Wind Helper
0.215
316405AF2-144 C
Solar/Wind Helper
0.158
3141873WAN 176
Solar/Wind Helper
0.027
3143873LANEXA
Solar/Wind Helper
0.08
3138133OCRAN
Solar/Wind Helper
0.04
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3145176PASQUOTANK
Solar/Wind Helper
0.077
24684705SMG5
50/50
0.326
316322AB2-045
Solar/Wind Helper
0.215
316316AC1-027 C
Solar/Wind Helper
0.238
315839AE2-212 C
Solar/Wind Helper
0.203
315697AD1-025 GEN
Solar/Wind Helper
1.645
957831AF2-077 GEN
Solar/Wind Helper
0.189
316258AE1-075 C
Solar/Wind Helper
0.189
3141913WHIT STONE
Solar/Wind Helper
0.133
316468AD1-105 GEN
Solar/Wind Helper
0.539
24684605SMG4
50/50
0.852
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
315671AE2-027_GEN
Solar/Wind Helper
1.187
316072AD1-144
Solar/Wind Helper
0.161
3143526WINTERP
Solar/Wind Helper
0.707
964211AG1-282 GEN
Solar/Wind Helper
0.17
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
270197AD1-017 GEN1
Solar/Wind Harmer
0.764
316486AD2-202 GEN
Solar/Wind Helper
0.901
316059AD1-063 C
Solar/Wind Helper
0.135
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
971629AH1-314 GEN
50/50
13.585
3147123OTTER R
Solar/Wind Harmer
0.091
270030AE2-140 GEN
Solar/Wind Harmer
10.404
316359AB2-059 GEN
Solar/Wind Harmer
0.224
3142053HEARTS
Solar/Wind Harmer
0.111
316375AC2-012 GEN
Solar/Wind Helper
0.401
3145336SMITFLD
Solar/Wind Helper
0.594
3146456SLIGO L269
Solar/Wind Helper
0.141
3142433PROV 92
Solar/Wind Helper
0.537
3141766HARMONY
Solar/Wind Helper
0.027
315975AC1-164 GENB
Solar/Wind Helper
0.05
3142416OLDCHRC
Solar/Wind Helper
0.324
3142416OLDCHRC
Solar/Wind Helper
0.124
962561AG1-105 GEN
Solar/Wind Harmer
9.76
316263AC1-034 GEN
Solar/Wind Harmer
2.392
316185AD1-033 GEN
Solar/Wind Helper
0.708
3143526WINTERP
Solar/Wind Helper
0.707
3144356SAPONY
Solar/Wind Helper
0.23
316315AB2-025 C
Solar/Wind Helper
0.196
316312AB1-027
Solar/Wind Helper
0.238
3151561HALLBR1
50/50
0.371
941801AE2-185 GEN
Solar/Wind Harmer
4.182
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146776BUCKING
Solar/Wind Helper
0.077
315773AC2-141 GEN
Solar/Wind Helper
3.583
316036AC1-147 C
Solar/Wind Helper
0.233
316132AB2-190 GEN1
Solar/Wind Helper
0.816
3141726DUNNSVL
Solar/Wind Helper
0.505
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.372
3146516WINFALL
Solar/Wind Helper
0.115
24684405SMG2
50/50
0.846
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.004
316458AB2-190 GEN2
Solar/Wind Helper
0.816
316246AF1-032 C
Solar/Wind Helper
0.159
316321Z2-027
Solar/Wind Helper
0.19
3141906WESTMOR
Solar/Wind Helper
0.047
970417AG2-272 GEN
50/50
1.9
24288905REUSENS
50/50
0.013
970087AG2-069 GEN
Solar/Wind Harmer
11.411
970223AG2-152 GEN
Solar/Wind Harmer
9.427
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
0.748
316369SG1_INVT
Solar/Wind Helper
0.693
319010AE1-072 C
Solar/Wind Helper
1.598
3143226MDLTHAN
Solar/Wind Helper
0.139
3142543TWELFTH
Solar/Wind Helper
0.013
315662AE1-191 GEN
Solar/Wind Helper
0.723
316280AD1-041 GEN
Solar/Wind Helper
0.452
3138133OCRAN
Solar/Wind Helper
0.08
316404AE1-155 C
Solar/Wind Helper
1.096
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
316294AC1-161 GEN
Solar/Wind Helper
3.045
316349AD2-085 GEN
Solar/Wind Helper
0.628
3142946ENON
Solar/Wind Helper
0.013
315976AC1-164 GENA
Solar/Wind Helper
1.695
316169AC1-164_GENC
Solar/Wind Helper
1.464
3146386ELIZ CT
Solar/Wind Helper
0.129
316431W1029_GEN1
Solar/Wind Helper
0.476
316433W1029_GEN2
Solar/Wind Helper
0.476
316473AC1-191 GEN
Solar/Wind Helper
0.733
316033AB2-134 GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
0.548
316388AE2-253 GEN
Solar/Wind Helper
0.548
3137176SLIGO L2192
Solar/Wind Helper
0.56
3130086AYDLETT
Solar/Wind Helper
0.556
316487AF1-042 GEN
Solar/Wind Helper
0.131
961601AG1-000A GEN
Solar/Wind Harmer
4.503
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3146776BUCKING
Solar/Wind Helper
0.069
3144536CHRHLND
Solar/Wind Helper
0.023
3142956BIRDNECK
Solar/Wind Helper
0.102
316305AF2-043 C
Solar/Wind Helper
0.187
316320Y1-086
Solar/Wind Helper
0.058
316223AC1-118
Solar/Wind Helper
0.181
3146516WINFALL
Solar/Wind Helper
0.115
316118AC1-105 GEN
Solar/Wind Harmer
0.783
942751AE2-291 GEN
Solar/Wind Harmer
13.09
964791AG1-342 GEN
Solar/Wind Harmer
4.484
961601AG1-000A GEN
Solar/Wind Harmer
1.126
3146776BUCKING
Solar/Wind Helper
0.77
3146776BUCKING
Solar/Wind Helper
0.062
316240AF1-291 C
Solar/Wind Helper
0.196
316313AB2-026
Solar/Wind Helper
0.21
316156AD2-030 GEN
Solar/Wind Helper
0.203
315666AE1-190 GEN
Solar/Wind Helper
0.181
966871AG1-558 GEN
Solar/Wind Helper
0.162
316435W1029_GEN3
Solar/Wind Helper
0.476
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
24684305SMG1
50/50
0.307
970085AG2-068 GEN
Solar/Wind Harmer
7.608
316018AA1-139 ULT2
Solar/Wind Helper
0.615
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141813NORNECK
Solar/Wind Helper
0.126
24684505SMG3
50/50
0.517
971683AH1-343 GEN
Solar/Wind Harmer
11.986
316123AC1-075 GEN
Solar/Wind Harmer
0.357
3147312GRETNA
Solar/Wind Harmer
0.026
942461AE2-259 GEN
Solar/Wind Helper
1.118
316075AC2-137 C
Solar/Wind Helper
0.198
316484AD2-074 GEN
Solar/Wind Helper
0.25
316077AC2-138 C
Solar/Wind Helper
0.118
LAGNLTFEXP_LAGN->PJM
CLTF
9.371
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.544
TVALTFEXP_TVA->PJM
CLTF
4.691
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.451
CPLELTFEXP_CPLE->PJM
CLTF
11.241
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.665
MECLTFEXP_MEC->PJM
CLTF
5.364
SIGELTFEXP_SIGE->PJM
CLTF
0.164
NYPJM->LTFIMP_NY
CLTF
0.702
LGEELTFEXP_LGEE->PJM
CLTF
2.038
WECLTFEXP_WEC->PJM
CLTF
1.08
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091

Details for 6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.56 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:631.87
MW Contribution:
5.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
1.086
316222AC1-221 GEN
Solar/Wind Harmer
0.443
316283AC2-100 C
Solar/Wind Harmer
0.206
3147133PAMPLIN
Solar/Wind Helper
1.064
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
3151601KERR 3
50/50
0.297
316405AF2-144 C
Solar/Wind Helper
0.182
3151541CLOVER2
50/50
6.689
3151631KERR 6
50/50
0.297
970831AG2-522 GEN
Solar/Wind Harmer
4.544
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
3151531CLOVER1
50/50
6.741
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.07
316129AC1-054 GEN
Solar/Wind Harmer
0.424
970535AG2-341 GEN
50/50
1.993
316118AC1-105 GEN
Solar/Wind Harmer
0.373
964791AG1-342 GEN
Solar/Wind Harmer
2.429
942751AE2-291 GEN
Solar/Wind Harmer
5.335
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
316313AB2-026
Solar/Wind Helper
0.242
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.319
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
971629AH1-314 GEN
50/50
5.005
316131AB2-060 GEN
Solar/Wind Harmer
0.206
970099AG2-077 GEN
Solar/Wind Harmer
36.297
962561AG1-105 GEN
Solar/Wind Harmer
5.688
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
3146776BUCKING
Solar/Wind Helper
0.217
315693AD1-088 GEN
Solar/Wind Harmer
18.249
957481AF2-042 GEN
Solar/Wind Harmer
90.743
3146926FARMVIL
Solar/Wind Helper
0.441
3146926FARMVIL
Solar/Wind Helper
0.441
970933AG2-581 GEN
Solar/Wind Harmer
27.858
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
3146776BUCKING
Solar/Wind Helper
0.196
270494AE1-108_GEN
Solar/Wind Helper
2.774
971967AH1-528 GEN
Solar/Wind Harmer
55.714
970413AG2-270 GEN
50/50
29.357
971683AH1-343 GEN
Solar/Wind Harmer
5.14
316123AC1-075 GEN
Solar/Wind Harmer
0.149
942461AE2-259 GEN
Solar/Wind Helper
3.543
315821AE2-092 GEN
Solar/Wind Helper
1.922
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.99 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:617.19
MW Contribution:
5.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
1.086
316222AC1-221 GEN
Solar/Wind Harmer
0.443
316283AC2-100 C
Solar/Wind Harmer
0.206
3147133PAMPLIN
Solar/Wind Helper
1.064
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
3151601KERR 3
50/50
0.297
316405AF2-144 C
Solar/Wind Helper
0.182
3151541CLOVER2
50/50
6.689
3151631KERR 6
50/50
0.297
970831AG2-522 GEN
Solar/Wind Harmer
4.544
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
3151531CLOVER1
50/50
6.741
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.07
316129AC1-054 GEN
Solar/Wind Harmer
0.424
970535AG2-341 GEN
50/50
1.993
316118AC1-105 GEN
Solar/Wind Harmer
0.373
964791AG1-342 GEN
Solar/Wind Harmer
2.429
942751AE2-291 GEN
Solar/Wind Harmer
5.335
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
316313AB2-026
Solar/Wind Helper
0.242
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.319
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
971629AH1-314 GEN
50/50
5.005
316131AB2-060 GEN
Solar/Wind Harmer
0.206
970099AG2-077 GEN
Solar/Wind Harmer
36.297
962561AG1-105 GEN
Solar/Wind Harmer
5.688
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
3146776BUCKING
Solar/Wind Helper
0.217
315693AD1-088 GEN
Solar/Wind Harmer
18.249
957481AF2-042 GEN
Solar/Wind Harmer
90.743
3146926FARMVIL
Solar/Wind Helper
0.441
3146926FARMVIL
Solar/Wind Helper
0.441
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
3146776BUCKING
Solar/Wind Helper
0.196
270494AE1-108_GEN
Solar/Wind Helper
2.774
970413AG2-270 GEN
50/50
29.357
971683AH1-343 GEN
Solar/Wind Harmer
5.14
316123AC1-075 GEN
Solar/Wind Harmer
0.149
942461AE2-259 GEN
Solar/Wind Helper
3.543
315821AE2-092 GEN
Solar/Wind Helper
1.922
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.49 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1041.75
MW Contribution:
13.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.135
24728405LEESVG
50/50
0.135
316003AC1-222 GEN
Solar/Wind Harmer
3.851
316222AC1-221 GEN
Solar/Wind Harmer
3.095
316283AC2-100 C
Solar/Wind Harmer
2.824
270574AD1-017 GEN2
Solar/Wind Harmer
4.517
943811AF1-049 GEN
Solar/Wind Harmer
2.88
270336AE1-100 GEN
Solar/Wind Harmer
1.169
316478AD1-087 GEN
Solar/Wind Helper
3.085
3145336SMITFLD
Solar/Wind Helper
0.06
316017AA1-139 ULT1
Solar/Wind Helper
0.659
3146456SLIGO L269
Solar/Wind Helper
0.142
3142946ENON
Solar/Wind Helper
0.045
316473AC1-191 GEN
Solar/Wind Helper
0.741
270173AC1-122 GEN
Solar/Wind Harmer
1.096
961601AG1-000A GEN
Solar/Wind Harmer
2.802
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Helper
0.07
3144536CHRHLND
Solar/Wind Helper
0.023
3142956BIRDNECK
Solar/Wind Helper
0.103
316305AF2-043 C
Solar/Wind Helper
0.189
316320Y1-086
Solar/Wind Helper
0.059
316223AC1-118
Solar/Wind Helper
0.183
3146516WINFALL
Solar/Wind Helper
0.116
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
270455AD2-022 GEN
Solar/Wind Harmer
3.539
270197AD1-017 GEN1
Solar/Wind Harmer
1.355
316486AD2-202 GEN
Solar/Wind Helper
0.903
316059AD1-063 C
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.199
270457AD2-023 GEN
Solar/Wind Harmer
1.795
970085AG2-068 GEN
Solar/Wind Harmer
9.969
316018AA1-139 ULT2
Solar/Wind Helper
0.62
316233AE1-074 FULL
Solar/Wind Helper
0.21
957601AF2-054 GEN
Solar/Wind Helper
0.182
3141813NORNECK
Solar/Wind Helper
0.127
3151561HALLBR1
50/50
0.37
970919AG2-571 GEN
Solar/Wind Harmer
5.047
941801AE2-185 GEN
Solar/Wind Harmer
5.478
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.078
315773AC2-141 GEN
Solar/Wind Helper
3.611
316036AC1-147 C
Solar/Wind Helper
0.235
316132AB2-190 GEN1
Solar/Wind Helper
0.824
3141726DUNNSVL
Solar/Wind Helper
0.51
316337AD2-073 GEN
Solar/Wind Helper
0.187
3146516WINFALL
Solar/Wind Helper
0.377
3146516WINFALL
Solar/Wind Helper
0.116
3152661PLYWOOD A
50/50
0.677
942671AE2-283 GEN
Solar/Wind Harmer
4.839
316049AB1-081 GEN
Solar/Wind Harmer
0.753
3145506HICKORY
Solar/Wind Helper
0.596
3145506HICKORY
Solar/Wind Helper
0.358
3145506HICKORY
Solar/Wind Helper
0.089
316033AB2-134 GEN
Solar/Wind Helper
0.502
316339AD2-160 GEN
Solar/Wind Helper
0.554
316388AE2-253 GEN
Solar/Wind Helper
0.554
3137176SLIGO L2192
Solar/Wind Helper
0.565
3130086AYDLETT
Solar/Wind Helper
0.561
316487AF1-042 GEN
Solar/Wind Helper
0.132
970917AG2-570 GEN
Solar/Wind Harmer
39.871
316217AC1-145 GEN
Solar/Wind Harmer
2.369
316197AC1-042 GEN
Solar/Wind Harmer
1.796
3146926FARMVIL
Solar/Wind Helper
0.144
3144873MCLAUGH
Solar/Wind Helper
0.004
316458AB2-190 GEN2
Solar/Wind Helper
0.824
316246AF1-032 C
Solar/Wind Helper
0.16
316321Z2-027
Solar/Wind Helper
0.192
3141906WESTMOR
Solar/Wind Helper
0.048
971683AH1-343 GEN
Solar/Wind Harmer
15.749
316123AC1-075 GEN
Solar/Wind Harmer
3.231
3147312GRETNA
Solar/Wind Harmer
-0.003
942461AE2-259 GEN
Solar/Wind Helper
1.127
316075AC2-137 C
Solar/Wind Helper
0.2
316484AD2-074 GEN
Solar/Wind Helper
0.253
316077AC2-138 C
Solar/Wind Helper
0.12
316322AB2-045
Solar/Wind Helper
0.217
316316AC1-027 C
Solar/Wind Helper
0.241
315839AE2-212 C
Solar/Wind Helper
0.205
315697AD1-025 GEN
Solar/Wind Helper
1.66
957831AF2-077 GEN
Solar/Wind Helper
0.191
316258AE1-075 C
Solar/Wind Helper
0.191
3141913WHIT STONE
Solar/Wind Helper
0.134
316468AD1-105 GEN
Solar/Wind Helper
0.546
970401AG2-262 GEN
Solar/Wind Harmer
1.708
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
270016AE1-250 BESS
Solar/Wind Harmer
2.229
315671AE2-027_GEN
Solar/Wind Helper
1.198
316072AD1-144
Solar/Wind Helper
0.162
3143526WINTERP
Solar/Wind Helper
0.714
964211AG1-282 GEN
Solar/Wind Helper
0.172
316118AC1-105 GEN
Solar/Wind Harmer
2.352
942751AE2-291 GEN
Solar/Wind Harmer
17.187
964791AG1-342 GEN
Solar/Wind Harmer
5.589
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146776BUCKING
Solar/Wind Helper
0.776
3146776BUCKING
Solar/Wind Helper
0.063
316240AF1-291 C
Solar/Wind Helper
0.197
316313AB2-026
Solar/Wind Helper
0.212
316156AD2-030 GEN
Solar/Wind Helper
0.205
315666AE1-190 GEN
Solar/Wind Helper
0.182
966871AG1-558 GEN
Solar/Wind Helper
0.163
316435W1029_GEN3
Solar/Wind Helper
0.482
3146516WINFALL
Solar/Wind Helper
0.116
316248AF1-058 C
Solar/Wind Harmer
1.268
962561AG1-105 GEN
Solar/Wind Harmer
12.809
270013AE1-250 PV
Solar/Wind Harmer
2.229
316263AC1-034 GEN
Solar/Wind Harmer
3.279
315687AD1-152 GEN
Solar/Wind Helper
4.952
316185AD1-033 GEN
Solar/Wind Helper
0.714
3143526WINTERP
Solar/Wind Helper
0.714
3144356SAPONY
Solar/Wind Helper
0.232
316315AB2-025 C
Solar/Wind Helper
0.198
316312AB1-027
Solar/Wind Helper
0.241
970087AG2-069 GEN
Solar/Wind Harmer
14.954
970223AG2-152 GEN
Solar/Wind Harmer
13.376
270018AE2-047 C O1
Solar/Wind Harmer
1.02
3146926FARMVIL
Solar/Wind Helper
0.144
316381AD1-082 GEN
Solar/Wind Helper
0.755
316369SG1_INVT
Solar/Wind Helper
0.7
319010AE1-072 C
Solar/Wind Helper
1.614
3143226MDLTHAN
Solar/Wind Helper
0.14
3142543TWELFTH
Solar/Wind Helper
0.013
315662AE1-191 GEN
Solar/Wind Helper
0.73
316280AD1-041 GEN
Solar/Wind Helper
0.456
3138133OCRAN
Solar/Wind Helper
0.08
316404AE1-155 C
Solar/Wind Helper
1.108
971629AH1-314 GEN
50/50
13.525
3147123OTTER R
Solar/Wind Harmer
-0.01
270030AE2-140 GEN
Solar/Wind Harmer
14.809
316359AB2-059 GEN
Solar/Wind Harmer
0.941
3142053HEARTS
Solar/Wind Harmer
0.082
316375AC2-012 GEN
Solar/Wind Helper
0.404
3145336SMITFLD
Solar/Wind Helper
0.599
3146456SLIGO L269
Solar/Wind Helper
0.142
3142433PROV 92
Solar/Wind Helper
0.542
3141766HARMONY
Solar/Wind Helper
0.027
315975AC1-164 GENB
Solar/Wind Helper
0.051
3142416OLDCHRC
Solar/Wind Helper
0.328
3142416OLDCHRC
Solar/Wind Helper
0.125
3146516WINFALL
Solar/Wind Helper
0.116
3146516WINFALL
Solar/Wind Helper
0.116
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
316294AC1-161 GEN
Solar/Wind Helper
3.069
316349AD2-085 GEN
Solar/Wind Helper
0.634
3142946ENON
Solar/Wind Helper
0.014
315976AC1-164 GENA
Solar/Wind Helper
1.712
316169AC1-164_GENC
Solar/Wind Helper
1.479
3146386ELIZ CT
Solar/Wind Helper
0.13
316431W1029_GEN1
Solar/Wind Helper
0.482
316433W1029_GEN2
Solar/Wind Helper
0.482
970581AG2-369 GEN
Solar/Wind Harmer
8.574
270069AE2-166 C O1
Solar/Wind Harmer
5.981
971981AH1-535 GEN
Solar/Wind Harmer
4.636
3143316POE
Solar/Wind Helper
0.63
316236AE1-162_GEN
Solar/Wind Helper
0.202
316382AG1-145 C
Solar/Wind Helper
0.193
316159AE1-175 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.159
3141873WAN 176
Solar/Wind Helper
0.027
3143873LANEXA
Solar/Wind Helper
0.081
3138133OCRAN
Solar/Wind Helper
0.04
3146486SUNBURY
Solar/Wind Helper
0.127
3146486SUNBURY
Solar/Wind Helper
0.127
3145176PASQUOTANK
Solar/Wind Helper
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
9.266
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.388
TVALTFEXP_TVA->PJM
CLTF
4.639
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.529
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.254
MECLTFEXP_MEC->PJM
CLTF
5.278
CPLELTFEXP_CPLE->PJM
CLTF
11.185
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.97
SIGELTFEXP_SIGE->PJM
CLTF
0.161
NYPJM->LTFIMP_NY
CLTF
0.735
LGEELTFEXP_LGEE->PJM
CLTF
2.002
WECLTFEXP_WEC->PJM
CLTF
1.06

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.61 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5316.1
MW Contribution:
19.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
1.721
316222AC1-221 GEN
Solar/Wind Harmer
1.259
316283AC2-100 C
Solar/Wind Harmer
0.593
959311AF2-222 GEN
Solar/Wind Harmer
24.64
3147133PAMPLIN
Solar/Wind Harmer
0.841
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
971623AH1-311 GEN
Solar/Wind Harmer
0.246
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
3142946ENON
Solar/Wind Helper
0.114
316473AC1-191 GEN
Solar/Wind Helper
1.826
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
972187AH1-678 GEN
50/50
19.524
970535AG2-341 GEN
50/50
5.153
316118AC1-105 GEN
Solar/Wind Harmer
0.853
964791AG1-342 GEN
Solar/Wind Harmer
6.163
942751AE2-291 GEN
Solar/Wind Harmer
12.756
3146776BUCKING
Solar/Wind Harmer
0.641
3146776BUCKING
Solar/Wind Harmer
0.052
961601AG1-000A GEN
Solar/Wind Harmer
2.139
316240AF1-291 C
Solar/Wind Helper
0.501
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
316435W1029_GEN3
Solar/Wind Helper
1.293
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
966871AG1-558 GEN
Solar/Wind Helper
0.403
963041AG1-153 GEN
50/50
17.227
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
316486AD2-202 GEN
Solar/Wind Harmer
0.505
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
961791AG1-021 GEN
Solar/Wind Harmer
2.599
971845AH1-439 GEN
Solar/Wind Harmer
7.623
270197AD1-017 GEN1
Solar/Wind Harmer
1.01
313526AB2-022
Solar/Wind Helper
0.533
316059AD1-063 C
Solar/Wind Helper
0.348
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3151041BRUNSWICKG3
50/50
8.509
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970301AG2-198 GEN
Solar/Wind Harmer
15.175
970323AG2-213 GEN
Solar/Wind Harmer
11.876
942671AE2-283 GEN
Solar/Wind Harmer
3.601
316049AB1-081 GEN
Solar/Wind Harmer
0.701
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316487AF1-042 GEN
Solar/Wind Helper
0.338
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
3151601KERR 3
50/50
0.597
970533AG2-339 GEN
Solar/Wind Harmer
48.8
970581AG2-369 GEN
Solar/Wind Harmer
27.249
270069AE2-166 C O1
Solar/Wind Harmer
5.95
3143316POE
Solar/Wind Helper
1.638
316236AE1-162_GEN
Solar/Wind Helper
0.53
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
3141873WAN 176
Solar/Wind Helper
0.07
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151021BRUNSWICKG1
50/50
8.509
970087AG2-069 GEN
Solar/Wind Harmer
47.528
957481AF2-042 GEN
Solar/Wind Harmer
144.773
315693AD1-088 GEN
Solar/Wind Harmer
23.773
315785AD2-033 C
Solar/Wind Harmer
2.263
970685AG2-442 GEN
Solar/Wind Harmer
20.361
971563AH1-280 GEN
Solar/Wind Harmer
2.888
3146926FARMVIL
Solar/Wind Harmer
0.152
970223AG2-152 GEN
Solar/Wind Harmer
12.898
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316369SG1_INVT
Solar/Wind Helper
1.805
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151631KERR 6
50/50
0.597
970673AG2-436 GEN
Solar/Wind Harmer
80.381
970683AG2-441 GEN
Solar/Wind Harmer
16.537
970681AG2-440 GEN
Solar/Wind Harmer
10.976
970831AG2-522 GEN
Solar/Wind Harmer
8.162
316316AC1-027 C
Solar/Wind Helper
0.639
315839AE2-212 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
4.281
957831AF2-077 GEN
Solar/Wind Helper
0.494
3141913WHIT STONE
Solar/Wind Helper
0.344
316468AD1-105 GEN
Solar/Wind Helper
1.353
3151051BRUNSWICKS1
50/50
17.665
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
941031AE2-094 GEN
Solar/Wind Harmer
118.958
970401AG2-262 GEN
Solar/Wind Harmer
1.883
316034AC1-036 C
Solar/Wind Harmer
0.019
971065AG2-659 GEN
Solar/Wind Harmer
9.521
316129AC1-054 GEN
Solar/Wind Harmer
0.781
3147312GRETNA
Solar/Wind Harmer
0.116
3146802CHATHAM
Solar/Wind Harmer
0.108
315671AE2-027_GEN
Solar/Wind Helper
3.055
316072AD1-144
Solar/Wind Helper
0.428
964211AG1-282 GEN
Solar/Wind Helper
0.439
3143526WINTERP
Solar/Wind Helper
1.594
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3144293JTRSVLE
50/50
0.686
970099AG2-077 GEN
Solar/Wind Harmer
57.909
962561AG1-105 GEN
Solar/Wind Harmer
15.161
316263AC1-034 GEN
Solar/Wind Harmer
4.683
316185AD1-033 GEN
Solar/Wind Helper
1.897
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316312AB1-027
Solar/Wind Helper
0.598
3143526WINTERP
Solar/Wind Helper
1.594
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3151561HALLBR1
50/50
0.4
970919AG2-571 GEN
Solar/Wind Harmer
21.594
3146776BUCKING
Solar/Wind Harmer
0.064
941801AE2-185 GEN
Solar/Wind Harmer
4.63
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.099
315773AC2-141 GEN
Solar/Wind Helper
9.603
316036AC1-147 C
Solar/Wind Helper
0.622
316132AB2-190 GEN1
Solar/Wind Helper
2.11
3141726DUNNSVL
Solar/Wind Helper
1.302
316337AD2-073 GEN
Solar/Wind Helper
0.479
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
971629AH1-314 GEN
50/50
19.08
316131AB2-060 GEN
Solar/Wind Harmer
0.892
3147123OTTER R
Solar/Wind Harmer
0.097
270030AE2-140 GEN
Solar/Wind Harmer
14.713
316359AB2-059 GEN
Solar/Wind Harmer
0.438
3142053HEARTS
Solar/Wind Harmer
0.217
316375AC2-012 GEN
Solar/Wind Helper
1.073
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142416OLDCHRC
Solar/Wind Helper
0.814
3142416OLDCHRC
Solar/Wind Helper
0.312
970933AG2-581 GEN
Solar/Wind Harmer
51.56
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
958211AF2-115 GEN
Solar/Wind Harmer
3.249
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
316294AC1-161 GEN
Solar/Wind Helper
8.161
316349AD2-085 GEN
Solar/Wind Helper
1.65
3146386ELIZ CT
Solar/Wind Helper
0.349
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
971683AH1-343 GEN
Solar/Wind Harmer
11.193
964241AG1-285 GEN
Solar/Wind Harmer
18.935
942461AE2-259 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Harmer
0.342
3147312GRETNA
Solar/Wind Harmer
0.029
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.306
3151031BRUNSWICKG2
50/50
8.509
944011AF1-069 GEN
Solar/Wind Harmer
38.868
3146776BUCKING
Solar/Wind Harmer
0.058
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.124
961601AG1-000A GEN
Solar/Wind Harmer
8.558
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
316305AF2-043 C
Solar/Wind Helper
0.5
316320Y1-086
Solar/Wind Helper
0.157
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
970917AG2-570 GEN
Solar/Wind Harmer
53.986
970257AG2-171 GEN
Solar/Wind Harmer
8.907
971775AH1-396 GEN
Solar/Wind Harmer
0.445
3146926FARMVIL
Solar/Wind Harmer
0.152
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
316321Z2-027
Solar/Wind Helper
0.514
3141906WESTMOR
Solar/Wind Helper
0.122
3146626S HERTFORD
Solar/Wind Helper
0.296
971967AH1-528 GEN
Solar/Wind Harmer
108.333
970085AG2-068 GEN
Solar/Wind Harmer
31.685
3144303KENBRDG
Solar/Wind Harmer
0.222
946301AF1-294 GEN
Solar/Wind Harmer
5.342
316018AA1-139 ULT2
Solar/Wind Helper
1.653
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
315800Z1-036_GEN1
Solar/Wind Helper
1.395
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
TVALTFEXP_TVA->PJM
CLTF
7.703
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
MECLTFEXP_MEC->PJM
CLTF
7.813
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
SIGELTFEXP_SIGE->PJM
CLTF
0.234
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.49 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5107.87
MW Contribution:
19.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
1.721
316222AC1-221 GEN
Solar/Wind Harmer
1.259
316283AC2-100 C
Solar/Wind Harmer
0.593
959311AF2-222 GEN
Solar/Wind Harmer
24.64
3147133PAMPLIN
Solar/Wind Harmer
0.841
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
971623AH1-311 GEN
Solar/Wind Harmer
0.246
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
3142946ENON
Solar/Wind Helper
0.114
316473AC1-191 GEN
Solar/Wind Helper
1.826
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
972187AH1-678 GEN
50/50
19.524
970535AG2-341 GEN
50/50
5.153
316118AC1-105 GEN
Solar/Wind Harmer
0.853
964791AG1-342 GEN
Solar/Wind Harmer
6.163
942751AE2-291 GEN
Solar/Wind Harmer
12.756
3146776BUCKING
Solar/Wind Harmer
0.641
3146776BUCKING
Solar/Wind Harmer
0.052
961601AG1-000A GEN
Solar/Wind Harmer
2.139
316240AF1-291 C
Solar/Wind Helper
0.501
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
316435W1029_GEN3
Solar/Wind Helper
1.293
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
966871AG1-558 GEN
Solar/Wind Helper
0.403
963041AG1-153 GEN
50/50
17.227
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
316486AD2-202 GEN
Solar/Wind Harmer
0.505
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
961791AG1-021 GEN
Solar/Wind Harmer
2.599
971845AH1-439 GEN
Solar/Wind Harmer
7.623
270197AD1-017 GEN1
Solar/Wind Harmer
1.01
313526AB2-022
Solar/Wind Helper
0.533
316059AD1-063 C
Solar/Wind Helper
0.348
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3151041BRUNSWICKG3
50/50
8.509
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970301AG2-198 GEN
Solar/Wind Harmer
15.175
970323AG2-213 GEN
Solar/Wind Harmer
11.876
942671AE2-283 GEN
Solar/Wind Harmer
3.601
316049AB1-081 GEN
Solar/Wind Harmer
0.701
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316487AF1-042 GEN
Solar/Wind Helper
0.338
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
3151601KERR 3
50/50
0.597
970581AG2-369 GEN
Solar/Wind Harmer
27.249
270069AE2-166 C O1
Solar/Wind Harmer
5.95
3143316POE
Solar/Wind Helper
1.638
316236AE1-162_GEN
Solar/Wind Helper
0.53
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
3141873WAN 176
Solar/Wind Helper
0.07
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151021BRUNSWICKG1
50/50
8.509
970087AG2-069 GEN
Solar/Wind Harmer
47.528
957481AF2-042 GEN
Solar/Wind Harmer
144.773
315693AD1-088 GEN
Solar/Wind Harmer
23.773
315785AD2-033 C
Solar/Wind Harmer
2.263
970685AG2-442 GEN
Solar/Wind Harmer
20.361
971563AH1-280 GEN
Solar/Wind Harmer
2.888
3146926FARMVIL
Solar/Wind Harmer
0.152
970223AG2-152 GEN
Solar/Wind Harmer
12.898
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316369SG1_INVT
Solar/Wind Helper
1.805
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151631KERR 6
50/50
0.597
970673AG2-436 GEN
Solar/Wind Harmer
80.381
970683AG2-441 GEN
Solar/Wind Harmer
16.537
970681AG2-440 GEN
Solar/Wind Harmer
10.976
970831AG2-522 GEN
Solar/Wind Harmer
8.162
316316AC1-027 C
Solar/Wind Helper
0.639
315839AE2-212 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
4.281
957831AF2-077 GEN
Solar/Wind Helper
0.494
3141913WHIT STONE
Solar/Wind Helper
0.344
316468AD1-105 GEN
Solar/Wind Helper
1.353
3151051BRUNSWICKS1
50/50
17.665
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
970401AG2-262 GEN
Solar/Wind Harmer
1.883
316034AC1-036 C
Solar/Wind Harmer
0.019
971065AG2-659 GEN
Solar/Wind Harmer
9.521
316129AC1-054 GEN
Solar/Wind Harmer
0.781
3147312GRETNA
Solar/Wind Harmer
0.116
3146802CHATHAM
Solar/Wind Harmer
0.108
315671AE2-027_GEN
Solar/Wind Helper
3.055
316072AD1-144
Solar/Wind Helper
0.428
964211AG1-282 GEN
Solar/Wind Helper
0.439
3143526WINTERP
Solar/Wind Helper
1.594
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3144293JTRSVLE
50/50
0.686
970099AG2-077 GEN
Solar/Wind Harmer
57.909
962561AG1-105 GEN
Solar/Wind Harmer
15.161
316263AC1-034 GEN
Solar/Wind Harmer
4.683
316185AD1-033 GEN
Solar/Wind Helper
1.897
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316312AB1-027
Solar/Wind Helper
0.598
3143526WINTERP
Solar/Wind Helper
1.594
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3151561HALLBR1
50/50
0.4
970919AG2-571 GEN
Solar/Wind Harmer
21.594
3146776BUCKING
Solar/Wind Harmer
0.064
941801AE2-185 GEN
Solar/Wind Harmer
4.63
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.099
315773AC2-141 GEN
Solar/Wind Helper
9.603
316036AC1-147 C
Solar/Wind Helper
0.622
316132AB2-190 GEN1
Solar/Wind Helper
2.11
3141726DUNNSVL
Solar/Wind Helper
1.302
316337AD2-073 GEN
Solar/Wind Helper
0.479
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
971629AH1-314 GEN
50/50
19.08
316131AB2-060 GEN
Solar/Wind Harmer
0.892
3147123OTTER R
Solar/Wind Harmer
0.097
270030AE2-140 GEN
Solar/Wind Harmer
14.713
316359AB2-059 GEN
Solar/Wind Harmer
0.438
3142053HEARTS
Solar/Wind Harmer
0.217
316375AC2-012 GEN
Solar/Wind Helper
1.073
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142416OLDCHRC
Solar/Wind Helper
0.814
3142416OLDCHRC
Solar/Wind Helper
0.312
970933AG2-581 GEN
Solar/Wind Harmer
51.56
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
958211AF2-115 GEN
Solar/Wind Harmer
3.249
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
971683AH1-343 GEN
Solar/Wind Harmer
11.193
964241AG1-285 GEN
Solar/Wind Harmer
18.935
942461AE2-259 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Harmer
0.342
3147312GRETNA
Solar/Wind Harmer
0.029
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
3151031BRUNSWICKG2
50/50
8.509
3146776BUCKING
Solar/Wind Harmer
0.058
3145543BTLEBRO
Solar/Wind Harmer
0.124
3145543BTLEBRO
Solar/Wind Harmer
0.124
961601AG1-000A GEN
Solar/Wind Harmer
8.558
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
316305AF2-043 C
Solar/Wind Helper
0.5
316320Y1-086
Solar/Wind Helper
0.157
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
970917AG2-570 GEN
Solar/Wind Harmer
53.986
970257AG2-171 GEN
Solar/Wind Harmer
8.907
971775AH1-396 GEN
Solar/Wind Harmer
0.445
3146926FARMVIL
Solar/Wind Harmer
0.152
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
316321Z2-027
Solar/Wind Helper
0.514
3141906WESTMOR
Solar/Wind Helper
0.122
3146626S HERTFORD
Solar/Wind Helper
0.296
316294AC1-161 GEN
Solar/Wind Helper
8.161
316349AD2-085 GEN
Solar/Wind Helper
1.65
3146386ELIZ CT
Solar/Wind Helper
0.349
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
971967AH1-528 GEN
Solar/Wind Harmer
108.333
970085AG2-068 GEN
Solar/Wind Harmer
31.685
3144303KENBRDG
Solar/Wind Harmer
0.222
946301AF1-294 GEN
Solar/Wind Harmer
5.342
316018AA1-139 ULT2
Solar/Wind Helper
1.653
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
315800Z1-036_GEN1
Solar/Wind Helper
1.395
316077AC2-138 C
Solar/Wind Helper
0.306
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
TVALTFEXP_TVA->PJM
CLTF
7.703
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
MECLTFEXP_MEC->PJM
CLTF
7.813
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
SIGELTFEXP_SIGE->PJM
CLTF
0.234
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 58572_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 58572_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.11 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5851.06
MW Contribution:
19.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.597
970533AG2-339 GEN
Solar/Wind Harmer
48.8
970581AG2-369 GEN
Solar/Wind Harmer
35.878
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151631KERR 6
50/50
0.597
970673AG2-436 GEN
Solar/Wind Harmer
158.752
316238AB2-078_GEN
Solar/Wind Harmer
0.977
316239AB2-077_GEN
Solar/Wind Harmer
0.977
970683AG2-441 GEN
Solar/Wind Harmer
21.774
970681AG2-440 GEN
Solar/Wind Harmer
14.452
970831AG2-522 GEN
Solar/Wind Harmer
10.747
316322AB2-045
Solar/Wind Harmer
0.605
316316AC1-027 C
Solar/Wind Helper
0.639
315839AE2-212 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
4.281
957831AF2-077 GEN
Solar/Wind Helper
0.494
3151051BRUNSWICKS1
50/50
17.665
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
941031AE2-094 GEN
Solar/Wind Harmer
136.066
970401AG2-262 GEN
Solar/Wind Harmer
2.354
963041AG1-153 GEN
50/50
17.227
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
316486AD2-202 GEN
Solar/Wind Harmer
1.412
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
971629AH1-314 GEN
50/50
19.08
316131AB2-060 GEN
Solar/Wind Harmer
3.464
3147123OTTER R
Solar/Wind Harmer
-0.011
270030AE2-140 GEN
Solar/Wind Harmer
21.088
316359AB2-059 GEN
Solar/Wind Harmer
1.862
3142053HEARTS
Solar/Wind Harmer
0.163
316375AC2-012 GEN
Solar/Wind Helper
1.073
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142416OLDCHRC
Solar/Wind Helper
0.814
3142416OLDCHRC
Solar/Wind Helper
0.312
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3144293JTRSVLE
50/50
0.686
970099AG2-077 GEN
Solar/Wind Harmer
76.247
315687AD1-152 GEN
Solar/Wind Harmer
6.011
316248AF1-058 C
Solar/Wind Harmer
1.167
962561AG1-105 GEN
Solar/Wind Harmer
19.962
316237AB2-079_GEN
Solar/Wind Harmer
0.977
270013AE1-250 PV
Solar/Wind Harmer
3.04
316263AC1-034 GEN
Solar/Wind Harmer
6.491
316185AD1-033 GEN
Solar/Wind Helper
1.897
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316312AB1-027
Solar/Wind Helper
0.598
3143526WINTERP
Solar/Wind Helper
1.594
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3151561HALLBR1
50/50
0.4
970919AG2-571 GEN
Solar/Wind Harmer
21.594
3146776BUCKING
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
6.096
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
9.603
316036AC1-147 C
Solar/Wind Helper
0.622
316132AB2-190 GEN1
Solar/Wind Helper
2.11
970917AG2-570 GEN
Solar/Wind Harmer
170.595
970257AG2-171 GEN
Solar/Wind Harmer
11.728
971775AH1-396 GEN
Solar/Wind Harmer
2.207
3146926FARMVIL
Solar/Wind Harmer
-0.017
316217AC1-145 GEN
Solar/Wind Harmer
2.636
316197AC1-042 GEN
Solar/Wind Harmer
1.998
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
316321Z2-027
Solar/Wind Helper
0.514
3141906WESTMOR
Solar/Wind Helper
0.122
3146626S HERTFORD
Solar/Wind Helper
0.296
3151021BRUNSWICKG1
50/50
8.509
970087AG2-069 GEN
Solar/Wind Harmer
62.578
957481AF2-042 GEN
Solar/Wind Harmer
190.618
315693AD1-088 GEN
Solar/Wind Harmer
27.824
315785AD2-033 C
Solar/Wind Harmer
7.115
970685AG2-442 GEN
Solar/Wind Harmer
26.809
971563AH1-280 GEN
Solar/Wind Harmer
3.802
3146926FARMVIL
Solar/Wind Harmer
-0.017
970223AG2-152 GEN
Solar/Wind Harmer
18.394
270018AE2-047 C O1
Solar/Wind Harmer
1.464
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316369SG1_INVT
Solar/Wind Helper
1.805
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
970933AG2-581 GEN
Solar/Wind Harmer
67.888
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
958211AF2-115 GEN
Solar/Wind Harmer
4.752
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
316294AC1-161 GEN
Solar/Wind Helper
8.161
316478AD1-087 GEN
Solar/Wind Harmer
4.82
316003AC1-222 GEN
Solar/Wind Harmer
3.569
316222AC1-221 GEN
Solar/Wind Harmer
3.464
316283AC2-100 C
Solar/Wind Harmer
3.207
959311AF2-222 GEN
Solar/Wind Harmer
32.508
3147133PAMPLIN
Solar/Wind Harmer
-0.094
270574AD1-017 GEN2
Solar/Wind Harmer
6.006
943811AF1-049 GEN
Solar/Wind Harmer
4.097
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
3142946ENON
Solar/Wind Helper
0.114
316473AC1-191 GEN
Solar/Wind Helper
1.826
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
961791AG1-021 GEN
Solar/Wind Harmer
3.802
270455AD2-022 GEN
Solar/Wind Harmer
5.012
971845AH1-439 GEN
Solar/Wind Harmer
10.037
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
313526AB2-022
Solar/Wind Helper
0.533
316059AD1-063 C
Solar/Wind Helper
0.348
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3151041BRUNSWICKG3
50/50
8.509
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970301AG2-198 GEN
Solar/Wind Harmer
19.981
313527AB2-043 GEN
Solar/Wind Harmer
5.238
970323AG2-213 GEN
Solar/Wind Harmer
15.637
942671AE2-283 GEN
Solar/Wind Harmer
5.385
316049AB1-081 GEN
Solar/Wind Harmer
1.49
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316487AF1-042 GEN
Solar/Wind Helper
0.338
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
270069AE2-166 C O1
Solar/Wind Harmer
8.528
3143316POE
Solar/Wind Helper
1.638
316236AE1-162_GEN
Solar/Wind Helper
0.53
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
3141873WAN 176
Solar/Wind Helper
0.07
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.509
944011AF1-069 GEN
Solar/Wind Harmer
42.634
3146776BUCKING
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.382
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
316305AF2-043 C
Solar/Wind Helper
0.5
316320Y1-086
Solar/Wind Helper
0.157
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
972187AH1-678 GEN
50/50
19.524
970535AG2-341 GEN
50/50
5.153
316118AC1-105 GEN
Solar/Wind Harmer
2.569
964791AG1-342 GEN
Solar/Wind Harmer
7.704
942751AE2-291 GEN
Solar/Wind Harmer
16.796
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
5.315
316240AF1-291 C
Solar/Wind Helper
0.501
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
316435W1029_GEN3
Solar/Wind Helper
1.293
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
966871AG1-558 GEN
Solar/Wind Helper
0.403
971967AH1-528 GEN
Solar/Wind Harmer
143.019
970085AG2-068 GEN
Solar/Wind Harmer
41.719
3144303KENBRDG
Solar/Wind Harmer
-0.025
946301AF1-294 GEN
Solar/Wind Harmer
7.794
270457AD2-023 GEN
Solar/Wind Harmer
2.542
316018AA1-139 ULT2
Solar/Wind Helper
1.653
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
315800Z1-036_GEN1
Solar/Wind Helper
1.395
3141726DUNNSVL
Solar/Wind Helper
1.302
316337AD2-073 GEN
Solar/Wind Helper
0.479
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
971683AH1-343 GEN
Solar/Wind Harmer
14.738
964241AG1-285 GEN
Solar/Wind Harmer
24.931
942461AE2-259 GEN
Solar/Wind Harmer
4.405
316123AC1-075 GEN
Solar/Wind Harmer
3.105
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.306
3141913WHIT STONE
Solar/Wind Helper
0.344
316468AD1-105 GEN
Solar/Wind Helper
1.353
316034AC1-036 C
Solar/Wind Harmer
0.578
971065AG2-659 GEN
Solar/Wind Harmer
12.535
316129AC1-054 GEN
Solar/Wind Harmer
2.056
270016AE1-250 BESS
Solar/Wind Harmer
3.04
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
315671AE2-027_GEN
Solar/Wind Helper
3.055
316072AD1-144
Solar/Wind Helper
0.428
964211AG1-282 GEN
Solar/Wind Helper
0.439
3143526WINTERP
Solar/Wind Helper
1.594
316349AD2-085 GEN
Solar/Wind Helper
1.65
3146386ELIZ CT
Solar/Wind Helper
0.349
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
TVALTFEXP_TVA->PJM
CLTF
7.703
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
MECLTFEXP_MEC->PJM
CLTF
7.813
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
SIGELTFEXP_SIGE->PJM
CLTF
0.234
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-5: W72_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: W72_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.55 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5822.84
MW Contribution:
19.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971629AH1-314 GEN
50/50
19.016
316131AB2-060 GEN
Solar/Wind Harmer
3.468
315242AE2-183_GT2
50/50
10.565
315241AE2-183_GT1
50/50
10.537
972185AH1-677 GEN
50/50
38.19
970909AG2-566 GEN
50/50
3.771
3144293JTRSVLE
50/50
0.685
970099AG2-077 GEN
Solar/Wind Harmer
75.739
315687AD1-152 GEN
Solar/Wind Harmer
5.976
316248AF1-058 C
Solar/Wind Harmer
1.162
962561AG1-105 GEN
Solar/Wind Harmer
19.93
316237AB2-079_GEN
Solar/Wind Harmer
0.978
270013AE1-250 PV
Solar/Wind Harmer
3.03
316263AC1-034 GEN
Solar/Wind Harmer
6.648
316185AD1-033 GEN
Solar/Wind Helper
1.908
316312AB1-027
Solar/Wind Helper
0.586
3143526WINTERP
Solar/Wind Helper
1.571
3144356SAPONY
Solar/Wind Helper
0.518
316315AB2-025 C
Solar/Wind Helper
0.441
970917AG2-570 GEN
Solar/Wind Harmer
169.383
970257AG2-171 GEN
Solar/Wind Harmer
11.725
971775AH1-396 GEN
Solar/Wind Harmer
2.206
3146926FARMVIL
Solar/Wind Harmer
-0.017
316217AC1-145 GEN
Solar/Wind Harmer
2.627
316197AC1-042 GEN
Solar/Wind Harmer
1.991
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.426
316458AB2-190 GEN2
Solar/Wind Helper
2.044
316321Z2-027
Solar/Wind Helper
0.516
3141906WESTMOR
Solar/Wind Helper
0.121
3146626S HERTFORD
Solar/Wind Helper
0.296
3151021BRUNSWICKG1
50/50
8.447
970087AG2-069 GEN
Solar/Wind Harmer
62.138
957481AF2-042 GEN
Solar/Wind Harmer
189.348
315693AD1-088 GEN
Solar/Wind Harmer
27.647
315785AD2-033 C
Solar/Wind Harmer
7.115
970685AG2-442 GEN
Solar/Wind Harmer
26.775
971563AH1-280 GEN
Solar/Wind Harmer
3.796
3146926FARMVIL
Solar/Wind Harmer
-0.017
970223AG2-152 GEN
Solar/Wind Harmer
18.332
270018AE2-047 C O1
Solar/Wind Harmer
1.459
319010AE1-072 C
Solar/Wind Helper
4.323
316369SG1_INVT
Solar/Wind Helper
1.762
316381AD1-082 GEN
Solar/Wind Helper
1.86
315662AE1-191 GEN
Solar/Wind Helper
1.847
316280AD1-041 GEN
Solar/Wind Helper
1.154
3138133OCRAN
Solar/Wind Helper
0.204
316404AE1-155 C
Solar/Wind Helper
2.803
3142543TWELFTH
Solar/Wind Helper
0.031
3143226MDLTHAN
Solar/Wind Helper
0.297
315611Z1-036_GEN2
Solar/Wind Helper
1.391
3130156CHOWAN
Solar/Wind Helper
0.24
316478AD1-087 GEN
Solar/Wind Harmer
4.79
316003AC1-222 GEN
Solar/Wind Harmer
3.555
316222AC1-221 GEN
Solar/Wind Harmer
3.451
316283AC2-100 C
Solar/Wind Harmer
3.195
959311AF2-222 GEN
Solar/Wind Harmer
32.493
3147133PAMPLIN
Solar/Wind Harmer
-0.094
270574AD1-017 GEN2
Solar/Wind Harmer
5.986
943811AF1-049 GEN
Solar/Wind Harmer
4.084
270336AE1-100 GEN
Solar/Wind Harmer
1.663
3138543CONSLDL
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.765
3146456SLIGO L269
Solar/Wind Helper
0.38
3142946ENON
Solar/Wind Helper
0.111
316473AC1-191 GEN
Solar/Wind Helper
1.782
3145273HOLLAND
Solar/Wind Helper
0.198
966881AG1-559 GEN
Solar/Wind Helper
0.345
3146376EDENTON
Solar/Wind Helper
0.239
963041AG1-153 GEN
50/50
17.101
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
316486AD2-202 GEN
Solar/Wind Harmer
1.403
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
961791AG1-021 GEN
Solar/Wind Harmer
3.796
270455AD2-022 GEN
Solar/Wind Harmer
4.996
971845AH1-439 GEN
Solar/Wind Harmer
9.987
270197AD1-017 GEN1
Solar/Wind Harmer
1.796
313526AB2-022
Solar/Wind Helper
0.535
316059AD1-063 C
Solar/Wind Helper
0.344
3141783LANCAST
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.135
3151041BRUNSWICKG3
50/50
8.447
3152661PLYWOOD A
50/50
0.739
3151581KERR 1
50/50
0.213
970301AG2-198 GEN
Solar/Wind Harmer
19.863
313527AB2-043 GEN
Solar/Wind Harmer
5.244
970323AG2-213 GEN
Solar/Wind Harmer
15.633
942671AE2-283 GEN
Solar/Wind Harmer
5.365
316049AB1-081 GEN
Solar/Wind Harmer
1.526
3145506HICKORY
Solar/Wind Helper
1.594
3145506HICKORY
Solar/Wind Helper
0.956
3145506HICKORY
Solar/Wind Helper
0.239
316339AD2-160 GEN
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.482
3137176SLIGO L2192
Solar/Wind Helper
1.514
3130086AYDLETT
Solar/Wind Helper
1.503
316033AB2-134 GEN
Solar/Wind Helper
1.265
316487AF1-042 GEN
Solar/Wind Helper
0.335
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
3151601KERR 3
50/50
0.597
970533AG2-339 GEN
Solar/Wind Harmer
48.444
970581AG2-369 GEN
Solar/Wind Harmer
35.626
270069AE2-166 C O1
Solar/Wind Harmer
8.499
316236AE1-162_GEN
Solar/Wind Helper
0.528
3143316POE
Solar/Wind Helper
1.484
316382AG1-145 C
Solar/Wind Helper
0.496
316159AE1-175 C
Solar/Wind Helper
0.56
3141873WAN 176
Solar/Wind Helper
0.069
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
3138133OCRAN
Solar/Wind Helper
0.102
3143873LANEXA
Solar/Wind Helper
0.203
3145176PASQUOTANK
Solar/Wind Helper
0.209
3130156CHOWAN
Solar/Wind Helper
0.24
3130156CHOWAN
Solar/Wind Helper
0.24
3151031BRUNSWICKG2
50/50
8.447
944011AF1-069 GEN
Solar/Wind Harmer
42.323
3146776BUCKING
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.52
3142956BIRDNECK
Solar/Wind Helper
0.274
3144536CHRHLND
Solar/Wind Helper
0.061
316305AF2-043 C
Solar/Wind Helper
0.501
316320Y1-086
Solar/Wind Helper
0.157
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.462
972187AH1-678 GEN
50/50
19.381
970535AG2-341 GEN
50/50
5.158
316118AC1-105 GEN
Solar/Wind Harmer
2.561
964791AG1-342 GEN
Solar/Wind Harmer
7.689
942751AE2-291 GEN
Solar/Wind Harmer
16.731
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
5.451
316240AF1-291 C
Solar/Wind Helper
0.469
316156AD2-030 GEN
Solar/Wind Helper
0.52
315666AE1-190 GEN
Solar/Wind Helper
0.462
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
966871AG1-558 GEN
Solar/Wind Helper
0.393
971967AH1-528 GEN
Solar/Wind Harmer
141.954
970085AG2-068 GEN
Solar/Wind Harmer
41.425
3144303KENBRDG
Solar/Wind Harmer
-0.025
946301AF1-294 GEN
Solar/Wind Harmer
7.781
270457AD2-023 GEN
Solar/Wind Harmer
2.533
316018AA1-139 ULT2
Solar/Wind Helper
1.661
957601AF2-054 GEN
Solar/Wind Helper
0.461
3141813NORNECK
Solar/Wind Helper
0.321
316233AE1-074 FULL
Solar/Wind Helper
0.461
315800Z1-036_GEN1
Solar/Wind Helper
1.391
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3151561HALLBR1
50/50
0.398
970919AG2-571 GEN
Solar/Wind Harmer
21.441
3146776BUCKING
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
6.074
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
9.714
316036AC1-147 C
Solar/Wind Helper
0.625
316132AB2-190 GEN1
Solar/Wind Helper
2.044
3141726DUNNSVL
Solar/Wind Helper
1.287
3146516WINFALL
Solar/Wind Helper
1.015
3146516WINFALL
Solar/Wind Helper
0.313
316337AD2-073 GEN
Solar/Wind Helper
0.473
970413AG2-270 GEN
50/50
46.18
3144293JTRSVLE
50/50
0.685
971683AH1-343 GEN
Solar/Wind Harmer
14.679
964241AG1-285 GEN
Solar/Wind Harmer
24.949
942461AE2-259 GEN
Solar/Wind Harmer
4.389
316123AC1-075 GEN
Solar/Wind Harmer
3.093
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.64
316075AC2-137 C
Solar/Wind Helper
0.493
316077AC2-138 C
Solar/Wind Helper
0.302
315244AE2-183_ST
50/50
18.346
3151541CLOVER2
50/50
10.523
3151631KERR 6
50/50
0.597
970673AG2-436 GEN
Solar/Wind Harmer
157.592
316238AB2-078_GEN
Solar/Wind Harmer
0.978
316239AB2-077_GEN
Solar/Wind Harmer
0.978
970683AG2-441 GEN
Solar/Wind Harmer
21.753
970681AG2-440 GEN
Solar/Wind Harmer
14.438
970831AG2-522 GEN
Solar/Wind Harmer
10.881
316322AB2-045
Solar/Wind Harmer
0.602
316316AC1-027 C
Solar/Wind Helper
0.642
315697AD1-025 GEN
Solar/Wind Helper
4.181
957831AF2-077 GEN
Solar/Wind Helper
0.492
315839AE2-212 C
Solar/Wind Helper
0.483
3141913WHIT STONE
Solar/Wind Helper
0.341
316468AD1-105 GEN
Solar/Wind Helper
1.325
3147123OTTER R
Solar/Wind Harmer
-0.011
270030AE2-140 GEN
Solar/Wind Harmer
21.018
316359AB2-059 GEN
Solar/Wind Harmer
1.907
3142053HEARTS
Solar/Wind Harmer
0.167
316375AC2-012 GEN
Solar/Wind Helper
1.078
3145336SMITFLD
Solar/Wind Helper
1.566
3146456SLIGO L269
Solar/Wind Helper
0.38
3141766HARMONY
Solar/Wind Helper
0.068
3142433PROV 92
Solar/Wind Helper
1.343
315975AC1-164 GENB
Solar/Wind Helper
0.126
3142416OLDCHRC
Solar/Wind Helper
0.798
3142416OLDCHRC
Solar/Wind Helper
0.306
3151051BRUNSWICKS1
50/50
17.536
971451AH1-221 GEN
50/50
25.651
315243AE2-183_GT3
50/50
10.565
3151531CLOVER1
50/50
10.604
3144293JTRSVLE
50/50
0.685
3144293JTRSVLE
50/50
0.541
941031AE2-094 GEN
Solar/Wind Harmer
135.072
970401AG2-262 GEN
Solar/Wind Harmer
2.349
316034AC1-036 C
Solar/Wind Harmer
0.578
971065AG2-659 GEN
Solar/Wind Harmer
12.632
316129AC1-054 GEN
Solar/Wind Harmer
2.075
270016AE1-250 BESS
Solar/Wind Harmer
3.03
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
316072AD1-144
Solar/Wind Helper
0.429
315671AE2-027_GEN
Solar/Wind Helper
2.846
964211AG1-282 GEN
Solar/Wind Helper
0.434
3143526WINTERP
Solar/Wind Helper
1.571
970933AG2-581 GEN
Solar/Wind Harmer
67.393
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
958211AF2-115 GEN
Solar/Wind Harmer
4.745
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
316294AC1-161 GEN
Solar/Wind Helper
8.256
316349AD2-085 GEN
Solar/Wind Helper
1.611
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.033
315976AC1-164 GENA
Solar/Wind Helper
4.26
316169AC1-164_GENC
Solar/Wind Helper
3.68
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
LAGNLTFEXP_LAGN->PJM
CLTF
15.386
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.197
TVALTFEXP_TVA->PJM
CLTF
7.676
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.758
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.424
MECLTFEXP_MEC->PJM
CLTF
7.783
CPLELTFEXP_CPLE->PJM
CLTF
20.605
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.302
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.47
LGEELTFEXP_LGEE->PJM
CLTF
2.835
WECLTFEXP_WEC->PJM
CLTF
1.484
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: XT585_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT585_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.34 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5462.74
MW Contribution:
19.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
4.82
316003AC1-222 GEN
Solar/Wind Harmer
3.569
316222AC1-221 GEN
Solar/Wind Harmer
3.464
316283AC2-100 C
Solar/Wind Harmer
3.207
959311AF2-222 GEN
Solar/Wind Harmer
32.508
3147133PAMPLIN
Solar/Wind Harmer
-0.094
270574AD1-017 GEN2
Solar/Wind Harmer
6.006
943811AF1-049 GEN
Solar/Wind Harmer
4.097
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145336SMITFLD
Solar/Wind Helper
0.157
316017AA1-139 ULT1
Solar/Wind Helper
1.756
3146456SLIGO L269
Solar/Wind Helper
0.378
3142946ENON
Solar/Wind Helper
0.114
316473AC1-191 GEN
Solar/Wind Helper
1.826
3145273HOLLAND
Solar/Wind Helper
0.2
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.241
963041AG1-153 GEN
50/50
17.227
3151611KERR 4
50/50
0.597
3151621KERR 5
50/50
0.597
316486AD2-202 GEN
Solar/Wind Harmer
1.412
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
961791AG1-021 GEN
Solar/Wind Harmer
3.802
270455AD2-022 GEN
Solar/Wind Harmer
5.012
971845AH1-439 GEN
Solar/Wind Harmer
10.037
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
313526AB2-022
Solar/Wind Helper
0.533
316059AD1-063 C
Solar/Wind Helper
0.348
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.136
3151041BRUNSWICKG3
50/50
8.509
3152661PLYWOOD A
50/50
0.742
3151581KERR 1
50/50
0.213
970301AG2-198 GEN
Solar/Wind Harmer
19.981
313527AB2-043 GEN
Solar/Wind Harmer
5.238
970323AG2-213 GEN
Solar/Wind Harmer
15.637
942671AE2-283 GEN
Solar/Wind Harmer
5.385
316049AB1-081 GEN
Solar/Wind Harmer
1.49
3145506HICKORY
Solar/Wind Helper
1.584
3145506HICKORY
Solar/Wind Helper
0.951
3145506HICKORY
Solar/Wind Helper
0.238
316339AD2-160 GEN
Solar/Wind Helper
1.474
316388AE2-253 GEN
Solar/Wind Helper
1.474
3137176SLIGO L2192
Solar/Wind Helper
1.506
3130086AYDLETT
Solar/Wind Helper
1.496
316033AB2-134 GEN
Solar/Wind Helper
1.296
316487AF1-042 GEN
Solar/Wind Helper
0.338
3146626S HERTFORD
Solar/Wind Helper
0.296
3151601KERR 3
50/50
0.597
970581AG2-369 GEN
Solar/Wind Harmer
35.878
270069AE2-166 C O1
Solar/Wind Harmer
8.528
3143316POE
Solar/Wind Helper
1.638
316236AE1-162_GEN
Solar/Wind Helper
0.53
316382AG1-145 C
Solar/Wind Helper
0.499
316159AE1-175 C
Solar/Wind Helper
0.563
3141873WAN 176
Solar/Wind Helper
0.07
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3146486SUNBURY
Solar/Wind Helper
0.34
3146486SUNBURY
Solar/Wind Helper
0.34
3145176PASQUOTANK
Solar/Wind Helper
0.209
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151021BRUNSWICKG1
50/50
8.509
970087AG2-069 GEN
Solar/Wind Harmer
62.578
957481AF2-042 GEN
Solar/Wind Harmer
190.618
315693AD1-088 GEN
Solar/Wind Harmer
27.824
315785AD2-033 C
Solar/Wind Harmer
7.115
970685AG2-442 GEN
Solar/Wind Harmer
26.809
971563AH1-280 GEN
Solar/Wind Harmer
3.802
3146926FARMVIL
Solar/Wind Harmer
-0.017
970223AG2-152 GEN
Solar/Wind Harmer
18.394
270018AE2-047 C O1
Solar/Wind Harmer
1.464
316381AD1-082 GEN
Solar/Wind Helper
1.958
319010AE1-072 C
Solar/Wind Helper
4.302
316369SG1_INVT
Solar/Wind Helper
1.805
315662AE1-191 GEN
Solar/Wind Helper
1.869
316280AD1-041 GEN
Solar/Wind Helper
1.168
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
316404AE1-155 C
Solar/Wind Helper
2.833
3143226MDLTHAN
Solar/Wind Helper
0.3
315611Z1-036_GEN2
Solar/Wind Helper
1.395
3130156CHOWAN
Solar/Wind Helper
0.241
972187AH1-678 GEN
50/50
19.524
970535AG2-341 GEN
50/50
5.153
316118AC1-105 GEN
Solar/Wind Harmer
2.569
964791AG1-342 GEN
Solar/Wind Harmer
7.704
942751AE2-291 GEN
Solar/Wind Harmer
16.796
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
5.315
971967AH1-528 GEN
Solar/Wind Harmer
143.019
970085AG2-068 GEN
Solar/Wind Harmer
41.719
3144303KENBRDG
Solar/Wind Harmer
-0.025
946301AF1-294 GEN
Solar/Wind Harmer
7.794
270457AD2-023 GEN
Solar/Wind Harmer
2.542
316018AA1-139 ULT2
Solar/Wind Helper
1.653
957601AF2-054 GEN
Solar/Wind Helper
0.466
3141813NORNECK
Solar/Wind Helper
0.324
316233AE1-074 FULL
Solar/Wind Helper
0.468
3151591KERR 2
50/50
0.597
3151641KERR 7
50/50
0.597
3151561HALLBR1
50/50
0.4
970919AG2-571 GEN
Solar/Wind Harmer
21.594
3146776BUCKING
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
6.096
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
9.603
316036AC1-147 C
Solar/Wind Helper
0.622
316132AB2-190 GEN1
Solar/Wind Helper
2.11
3141726DUNNSVL
Solar/Wind Helper
1.302
316337AD2-073 GEN
Solar/Wind Helper
0.479
3146516WINFALL
Solar/Wind Helper
1.014
3146516WINFALL
Solar/Wind Helper
0.313
315244AE2-183_ST
50/50
18.481
3151541CLOVER2
50/50
10.589
3151631KERR 6
50/50
0.597
316238AB2-078_GEN
Solar/Wind Harmer
0.977
316239AB2-077_GEN
Solar/Wind Harmer
0.977
970683AG2-441 GEN
Solar/Wind Harmer
21.774
970681AG2-440 GEN
Solar/Wind Harmer
14.452
970831AG2-522 GEN
Solar/Wind Harmer
10.747
316322AB2-045
Solar/Wind Harmer
0.605
316316AC1-027 C
Solar/Wind Helper
0.639
315839AE2-212 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
4.281
957831AF2-077 GEN
Solar/Wind Helper
0.494
3141913WHIT STONE
Solar/Wind Helper
0.344
316468AD1-105 GEN
Solar/Wind Helper
1.353
971629AH1-314 GEN
50/50
19.08
3151051BRUNSWICKS1
50/50
17.665
971451AH1-221 GEN
50/50
25.84
315243AE2-183_GT3
50/50
10.643
3151531CLOVER1
50/50
10.671
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.541
970401AG2-262 GEN
Solar/Wind Harmer
2.354
316034AC1-036 C
Solar/Wind Harmer
0.578
971065AG2-659 GEN
Solar/Wind Harmer
12.535
316129AC1-054 GEN
Solar/Wind Harmer
2.056
270016AE1-250 BESS
Solar/Wind Harmer
3.04
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
315671AE2-027_GEN
Solar/Wind Helper
3.055
316072AD1-144
Solar/Wind Helper
0.428
964211AG1-282 GEN
Solar/Wind Helper
0.439
3143526WINTERP
Solar/Wind Helper
1.594
316131AB2-060 GEN
Solar/Wind Harmer
3.464
3147123OTTER R
Solar/Wind Harmer
-0.011
270030AE2-140 GEN
Solar/Wind Harmer
21.088
316359AB2-059 GEN
Solar/Wind Harmer
1.862
3142053HEARTS
Solar/Wind Harmer
0.163
316375AC2-012 GEN
Solar/Wind Helper
1.073
3145336SMITFLD
Solar/Wind Helper
1.573
3146456SLIGO L269
Solar/Wind Helper
0.378
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.374
315975AC1-164 GENB
Solar/Wind Helper
0.128
3142416OLDCHRC
Solar/Wind Helper
0.814
3142416OLDCHRC
Solar/Wind Helper
0.312
3151031BRUNSWICKG2
50/50
8.509
3146776BUCKING
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.382
3144536CHRHLND
Solar/Wind Helper
0.061
3142956BIRDNECK
Solar/Wind Helper
0.272
316305AF2-043 C
Solar/Wind Helper
0.5
316320Y1-086
Solar/Wind Helper
0.157
3146516WINFALL
Solar/Wind Helper
0.313
316223AC1-118
Solar/Wind Helper
0.467
970933AG2-581 GEN
Solar/Wind Harmer
67.888
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
958211AF2-115 GEN
Solar/Wind Harmer
4.752
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
316294AC1-161 GEN
Solar/Wind Helper
8.161
316349AD2-085 GEN
Solar/Wind Helper
1.65
3146386ELIZ CT
Solar/Wind Helper
0.349
3142946ENON
Solar/Wind Helper
0.034
315976AC1-164 GENA
Solar/Wind Helper
4.331
316169AC1-164_GENC
Solar/Wind Helper
3.741
316431W1029_GEN1
Solar/Wind Helper
1.293
316433W1029_GEN2
Solar/Wind Helper
1.293
315800Z1-036_GEN1
Solar/Wind Helper
1.395
3146626S HERTFORD
Solar/Wind Helper
0.296
970917AG2-570 GEN
Solar/Wind Harmer
170.595
970257AG2-171 GEN
Solar/Wind Harmer
11.728
971775AH1-396 GEN
Solar/Wind Harmer
2.207
3146926FARMVIL
Solar/Wind Harmer
-0.017
316217AC1-145 GEN
Solar/Wind Harmer
2.636
316197AC1-042 GEN
Solar/Wind Harmer
1.998
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.425
316458AB2-190 GEN2
Solar/Wind Helper
2.11
316321Z2-027
Solar/Wind Helper
0.514
3141906WESTMOR
Solar/Wind Helper
0.122
3146626S HERTFORD
Solar/Wind Helper
0.296
315242AE2-183_GT2
50/50
10.643
315241AE2-183_GT1
50/50
10.614
972185AH1-677 GEN
50/50
38.471
970909AG2-566 GEN
50/50
3.794
3144293JTRSVLE
50/50
0.686
970099AG2-077 GEN
Solar/Wind Harmer
76.247
315687AD1-152 GEN
Solar/Wind Harmer
6.011
316248AF1-058 C
Solar/Wind Harmer
1.167
962561AG1-105 GEN
Solar/Wind Harmer
19.962
316237AB2-079_GEN
Solar/Wind Harmer
0.977
270013AE1-250 PV
Solar/Wind Harmer
3.04
316263AC1-034 GEN
Solar/Wind Harmer
6.491
316185AD1-033 GEN
Solar/Wind Helper
1.897
3144356SAPONY
Solar/Wind Helper
0.596
316315AB2-025 C
Solar/Wind Helper
0.508
316312AB1-027
Solar/Wind Helper
0.598
3143526WINTERP
Solar/Wind Helper
1.594
970413AG2-270 GEN
50/50
46.471
3144293JTRSVLE
50/50
0.686
971683AH1-343 GEN
Solar/Wind Harmer
14.738
964241AG1-285 GEN
Solar/Wind Harmer
24.931
942461AE2-259 GEN
Solar/Wind Harmer
4.405
316123AC1-075 GEN
Solar/Wind Harmer
3.105
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.647
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.306
316240AF1-291 C
Solar/Wind Helper
0.501
316156AD2-030 GEN
Solar/Wind Helper
0.526
315666AE1-190 GEN
Solar/Wind Helper
0.467
316435W1029_GEN3
Solar/Wind Helper
1.293
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
3146516WINFALL
Solar/Wind Helper
0.313
966871AG1-558 GEN
Solar/Wind Helper
0.403
LAGNLTFEXP_LAGN->PJM
CLTF
15.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.341
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.519
CPLELTFEXP_CPLE->PJM
CLTF
20.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.605
TVALTFEXP_TVA->PJM
CLTF
7.703
MECLTFEXP_MEC->PJM
CLTF
7.813
SIGELTFEXP_SIGE->PJM
CLTF
0.234
NYPJM->LTFIMP_NY
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
2.846
WECLTFEXP_WEC->PJM
CLTF
1.49
AG2-052LTFEXP_AG2-052->PJM
LTF
0.081
AH1-155LTFEXP_AH1-155->PJM
LTF
0.121

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 54472_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 54472_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.29 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:2980.61
MW Contribution:
11.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
3.607
316003AC1-222 GEN
Solar/Wind Harmer
2.539
959311AF2-222 GEN
Solar/Wind Harmer
24.346
3147133PAMPLIN
Solar/Wind Harmer
-0.071
316222AC1-221 GEN
Solar/Wind Harmer
2.214
316283AC2-100 C
Solar/Wind Harmer
2.042
3151031BRUNSWICKG2
50/50
4.134
3146776BUCKING
Solar/Wind Harmer
-0.005
963041AG1-153 GEN
50/50
8.369
3151611KERR 4
50/50
0.435
3151621KERR 5
50/50
0.435
316486AD2-202 GEN
Solar/Wind Harmer
1.056
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
961791AG1-021 GEN
Solar/Wind Harmer
2.874
270455AD2-022 GEN
Solar/Wind Harmer
3.038
971845AH1-439 GEN
Solar/Wind Harmer
8.061
971967AH1-528 GEN
Solar/Wind Harmer
109.533
970085AG2-068 GEN
Solar/Wind Harmer
20.479
3144303KENBRDG
Solar/Wind Harmer
-0.019
946301AF1-294 GEN
Solar/Wind Harmer
5.891
270457AD2-023 GEN
Solar/Wind Harmer
1.541
3151591KERR 2
50/50
0.435
3151641KERR 7
50/50
0.435
970919AG2-571 GEN
Solar/Wind Harmer
10.571
3146776BUCKING
Solar/Wind Harmer
-0.006
315773AC2-141 GEN
Solar/Wind Helper
5.481
3151041BRUNSWICKG3
50/50
4.134
3152661PLYWOOD A
50/50
0.531
3151581KERR 1
50/50
0.155
970301AG2-198 GEN
Solar/Wind Harmer
15.282
313527AB2-043 GEN
Solar/Wind Harmer
3.87
970323AG2-213 GEN
Solar/Wind Harmer
11.693
970917AG2-570 GEN
Solar/Wind Harmer
83.508
970413AG2-270 GEN
50/50
34.783
3144293JTRSVLE
50/50
0.518
971683AH1-343 GEN
Solar/Wind Harmer
10.454
964241AG1-285 GEN
Solar/Wind Harmer
18.498
942461AE2-259 GEN
Solar/Wind Harmer
3.379
316123AC1-075 GEN
Solar/Wind Harmer
2.185
3151541CLOVER2
50/50
7.926
315244AE2-183_ST
50/50
6.714
3151631KERR 6
50/50
0.435
316238AB2-078_GEN
Solar/Wind Harmer
0.72
316239AB2-077_GEN
Solar/Wind Harmer
0.72
970683AG2-441 GEN
Solar/Wind Harmer
16.371
970681AG2-440 GEN
Solar/Wind Harmer
10.866
970831AG2-522 GEN
Solar/Wind Harmer
7.961
316322AB2-045
Solar/Wind Harmer
0.488
970673AG2-436 GEN
Solar/Wind Harmer
30.81
315839AE2-212 C
Solar/Wind Helper
0.317
3151531CLOVER1
50/50
7.987
3151051BRUNSWICKS1
50/50
8.582
971451AH1-221 GEN
50/50
12.554
315243AE2-183_GT3
50/50
3.866
3144293JTRSVLE
50/50
0.518
3144293JTRSVLE
50/50
0.409
970401AG2-262 GEN
Solar/Wind Harmer
1.701
316034AC1-036 C
Solar/Wind Harmer
0.432
971065AG2-659 GEN
Solar/Wind Harmer
9.225
316129AC1-054 GEN
Solar/Wind Harmer
1.517
315671AE2-027_GEN
Solar/Wind Helper
1.833
970909AG2-566 GEN
50/50
2.902
315242AE2-183_GT2
50/50
3.866
315241AE2-183_GT1
50/50
3.856
972185AH1-677 GEN
50/50
13.975
3144293JTRSVLE
50/50
0.518
970099AG2-077 GEN
Solar/Wind Harmer
57.634
315687AD1-152 GEN
Solar/Wind Harmer
4.402
316248AF1-058 C
Solar/Wind Harmer
0.832
962561AG1-105 GEN
Solar/Wind Harmer
14.47
316237AB2-079_GEN
Solar/Wind Harmer
0.72
970257AG2-171 GEN
Solar/Wind Harmer
8.769
971775AH1-396 GEN
Solar/Wind Harmer
1.65
3146926FARMVIL
Solar/Wind Harmer
-0.013
3151021BRUNSWICKG1
50/50
4.134
957481AF2-042 GEN
Solar/Wind Harmer
144.085
315693AD1-088 GEN
Solar/Wind Harmer
21.044
970087AG2-069 GEN
Solar/Wind Harmer
30.719
315785AD2-033 C
Solar/Wind Harmer
5.309
970685AG2-442 GEN
Solar/Wind Harmer
20.206
971563AH1-280 GEN
Solar/Wind Harmer
2.874
3146926FARMVIL
Solar/Wind Harmer
-0.013
970223AG2-152 GEN
Solar/Wind Harmer
11.336
971629AH1-314 GEN
50/50
11.606
316131AB2-060 GEN
Solar/Wind Harmer
2.562
972187AH1-678 GEN
50/50
9.485
970535AG2-341 GEN
50/50
3.78
316118AC1-105 GEN
Solar/Wind Harmer
1.844
964791AG1-342 GEN
Solar/Wind Harmer
5.568
942751AE2-291 GEN
Solar/Wind Harmer
11.764
3146776BUCKING
Solar/Wind Harmer
-0.058
3146776BUCKING
Solar/Wind Harmer
-0.005
970933AG2-581 GEN
Solar/Wind Harmer
51.867
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
958211AF2-115 GEN
Solar/Wind Harmer
3.592
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
316294AC1-161 GEN
Solar/Wind Helper
4.658
3151601KERR 3
50/50
0.435
970581AG2-369 GEN
Solar/Wind Harmer
17.612
3143316POE
Solar/Wind Helper
1.003
LAGNLTFEXP_LAGN->PJM
CLTF
8.951
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.467
TVALTFEXP_TVA->PJM
CLTF
4.473
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.693
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.444
MECLTFEXP_MEC->PJM
CLTF
4.621
CPLELTFEXP_CPLE->PJM
CLTF
11.798
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.275
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
1.41
LGEELTFEXP_LGEE->PJM
CLTF
1.7
WECLTFEXP_WEC->PJM
CLTF
0.889

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.98 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4842.86
MW Contribution:
17.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
1.514
316222AC1-221 GEN
Solar/Wind Harmer
1.167
316283AC2-100 C
Solar/Wind Harmer
0.55
959311AF2-222 GEN
Solar/Wind Harmer
21.675
3147133PAMPLIN
Solar/Wind Harmer
0.736
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
971623AH1-311 GEN
Solar/Wind Harmer
0.235
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
3142946ENON
Solar/Wind Helper
0.108
316473AC1-191 GEN
Solar/Wind Helper
1.733
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
972187AH1-678 GEN
50/50
19.356
970535AG2-341 GEN
50/50
4.57
316118AC1-105 GEN
Solar/Wind Harmer
0.762
964791AG1-342 GEN
Solar/Wind Harmer
5.492
942751AE2-291 GEN
Solar/Wind Harmer
11.487
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
961601AG1-000A GEN
Solar/Wind Harmer
2.039
316240AF1-291 C
Solar/Wind Helper
0.475
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
316435W1029_GEN3
Solar/Wind Helper
1.221
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
966871AG1-558 GEN
Solar/Wind Helper
0.382
963041AG1-153 GEN
50/50
17.078
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
316486AD2-202 GEN
Solar/Wind Harmer
0.444
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
961791AG1-021 GEN
Solar/Wind Harmer
2.278
971845AH1-439 GEN
Solar/Wind Harmer
6.517
270197AD1-017 GEN1
Solar/Wind Harmer
0.942
313526AB2-022
Solar/Wind Helper
0.503
316059AD1-063 C
Solar/Wind Helper
0.33
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3151041BRUNSWICKG3
50/50
8.436
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970301AG2-198 GEN
Solar/Wind Harmer
13.237
970323AG2-213 GEN
Solar/Wind Harmer
10.454
942671AE2-283 GEN
Solar/Wind Harmer
3.281
316049AB1-081 GEN
Solar/Wind Harmer
0.667
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316487AF1-042 GEN
Solar/Wind Helper
0.321
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
3151601KERR 3
50/50
0.53
970581AG2-369 GEN
Solar/Wind Harmer
26.958
270069AE2-166 C O1
Solar/Wind Harmer
5.589
3143316POE
Solar/Wind Helper
1.548
316236AE1-162_GEN
Solar/Wind Helper
0.501
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
3141873WAN 176
Solar/Wind Helper
0.066
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.288
3151541CLOVER2
50/50
9.313
3151631KERR 6
50/50
0.53
970683AG2-441 GEN
Solar/Wind Harmer
14.525
970681AG2-440 GEN
Solar/Wind Harmer
9.64
970831AG2-522 GEN
Solar/Wind Harmer
7.24
316316AC1-027 C
Solar/Wind Helper
0.603
315839AE2-212 C
Solar/Wind Helper
0.496
315697AD1-025 GEN
Solar/Wind Helper
4.048
957831AF2-077 GEN
Solar/Wind Helper
0.468
3141913WHIT STONE
Solar/Wind Helper
0.326
316468AD1-105 GEN
Solar/Wind Helper
1.285
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
970401AG2-262 GEN
Solar/Wind Harmer
1.678
316034AC1-036 C
Solar/Wind Harmer
0.016
971065AG2-659 GEN
Solar/Wind Harmer
8.454
316129AC1-054 GEN
Solar/Wind Harmer
0.693
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
315671AE2-027_GEN
Solar/Wind Helper
2.891
316072AD1-144
Solar/Wind Helper
0.405
964211AG1-282 GEN
Solar/Wind Helper
0.416
3143526WINTERP
Solar/Wind Helper
1.518
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
970909AG2-566 GEN
50/50
3.309
3144293JTRSVLE
50/50
0.601
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
3146776BUCKING
Solar/Wind Harmer
0.055
941801AE2-185 GEN
Solar/Wind Harmer
4.219
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.094
315773AC2-141 GEN
Solar/Wind Helper
9.062
316036AC1-147 C
Solar/Wind Helper
0.587
316132AB2-190 GEN1
Solar/Wind Helper
1.996
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
971629AH1-314 GEN
50/50
17.942
316131AB2-060 GEN
Solar/Wind Harmer
0.788
3147123OTTER R
Solar/Wind Harmer
0.088
270030AE2-140 GEN
Solar/Wind Harmer
13.827
316359AB2-059 GEN
Solar/Wind Harmer
0.417
3142053HEARTS
Solar/Wind Harmer
0.206
316375AC2-012 GEN
Solar/Wind Helper
1.012
3145336SMITFLD
Solar/Wind Helper
1.485
3146456SLIGO L269
Solar/Wind Helper
0.357
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
970099AG2-077 GEN
Solar/Wind Harmer
50.746
962561AG1-105 GEN
Solar/Wind Harmer
13.495
316263AC1-034 GEN
Solar/Wind Harmer
4.456
316185AD1-033 GEN
Solar/Wind Helper
1.79
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316312AB1-027
Solar/Wind Helper
0.567
3143526WINTERP
Solar/Wind Helper
1.518
3151031BRUNSWICKG2
50/50
8.436
3146776BUCKING
Solar/Wind Harmer
0.049
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.118
961601AG1-000A GEN
Solar/Wind Harmer
8.154
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
316305AF2-043 C
Solar/Wind Helper
0.472
316320Y1-086
Solar/Wind Helper
0.148
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3151021BRUNSWICKG1
50/50
8.436
970087AG2-069 GEN
Solar/Wind Harmer
47.021
957481AF2-042 GEN
Solar/Wind Harmer
126.864
315693AD1-088 GEN
Solar/Wind Harmer
20.828
315785AD2-033 C
Solar/Wind Harmer
1.994
970685AG2-442 GEN
Solar/Wind Harmer
17.866
971563AH1-280 GEN
Solar/Wind Harmer
2.531
3146926FARMVIL
Solar/Wind Harmer
0.131
970223AG2-152 GEN
Solar/Wind Harmer
12.084
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
970917AG2-570 GEN
Solar/Wind Harmer
53.44
970257AG2-171 GEN
Solar/Wind Harmer
7.84
971775AH1-396 GEN
Solar/Wind Harmer
0.392
3146926FARMVIL
Solar/Wind Harmer
0.131
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316321Z2-027
Solar/Wind Helper
0.485
3141906WESTMOR
Solar/Wind Helper
0.116
3146626S HERTFORD
Solar/Wind Helper
0.279
970933AG2-581 GEN
Solar/Wind Harmer
44.999
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
958211AF2-115 GEN
Solar/Wind Harmer
2.847
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.188
316294AC1-161 GEN
Solar/Wind Helper
7.701
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
971967AH1-528 GEN
Solar/Wind Harmer
94.459
970085AG2-068 GEN
Solar/Wind Harmer
31.347
3144303KENBRDG
Solar/Wind Harmer
0.196
946301AF1-294 GEN
Solar/Wind Harmer
4.682
316018AA1-139 ULT2
Solar/Wind Helper
1.56
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
315800Z1-036_GEN1
Solar/Wind Helper
1.317
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
971683AH1-343 GEN
Solar/Wind Harmer
10.037
964241AG1-285 GEN
Solar/Wind Harmer
16.717
316123AC1-075 GEN
Solar/Wind Harmer
0.308
942461AE2-259 GEN
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.026
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
TVALTFEXP_TVA->PJM
CLTF
7.333
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.0 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5245.63
MW Contribution:
17.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.078
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
971629AH1-314 GEN
50/50
17.942
316131AB2-060 GEN
Solar/Wind Harmer
3.062
3147123OTTER R
Solar/Wind Harmer
-0.01
270030AE2-140 GEN
Solar/Wind Harmer
19.819
316359AB2-059 GEN
Solar/Wind Harmer
1.772
3142053HEARTS
Solar/Wind Harmer
0.155
316478AD1-087 GEN
Solar/Wind Harmer
4.24
316003AC1-222 GEN
Solar/Wind Harmer
3.197
316222AC1-221 GEN
Solar/Wind Harmer
3.212
316283AC2-100 C
Solar/Wind Harmer
2.976
959311AF2-222 GEN
Solar/Wind Harmer
28.596
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270574AD1-017 GEN2
Solar/Wind Harmer
5.599
943811AF1-049 GEN
Solar/Wind Harmer
3.851
270336AE1-100 GEN
Solar/Wind Harmer
1.568
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
3142946ENON
Solar/Wind Helper
0.108
316473AC1-191 GEN
Solar/Wind Helper
1.733
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.436
3146776BUCKING
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.128
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
316305AF2-043 C
Solar/Wind Helper
0.472
316320Y1-086
Solar/Wind Helper
0.148
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
971967AH1-528 GEN
Solar/Wind Harmer
124.702
970085AG2-068 GEN
Solar/Wind Harmer
41.274
3144303KENBRDG
Solar/Wind Harmer
-0.022
946301AF1-294 GEN
Solar/Wind Harmer
6.831
270457AD2-023 GEN
Solar/Wind Harmer
2.392
316018AA1-139 ULT2
Solar/Wind Helper
1.56
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
315800Z1-036_GEN1
Solar/Wind Helper
1.317
316486AD2-202 GEN
Solar/Wind Harmer
1.242
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.022
961791AG1-021 GEN
Solar/Wind Harmer
3.332
270455AD2-022 GEN
Solar/Wind Harmer
4.718
971845AH1-439 GEN
Solar/Wind Harmer
8.58
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
313526AB2-022
Solar/Wind Helper
0.503
316059AD1-063 C
Solar/Wind Helper
0.33
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
3146776BUCKING
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
5.554
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
9.062
316036AC1-147 C
Solar/Wind Helper
0.587
316132AB2-190 GEN1
Solar/Wind Helper
1.996
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3151021BRUNSWICKG1
50/50
8.436
970087AG2-069 GEN
Solar/Wind Harmer
61.91
957481AF2-042 GEN
Solar/Wind Harmer
167.038
315693AD1-088 GEN
Solar/Wind Harmer
24.377
315785AD2-033 C
Solar/Wind Harmer
6.268
970685AG2-442 GEN
Solar/Wind Harmer
23.524
971563AH1-280 GEN
Solar/Wind Harmer
3.332
3146926FARMVIL
Solar/Wind Harmer
-0.015
970223AG2-152 GEN
Solar/Wind Harmer
17.233
270018AE2-047 C O1
Solar/Wind Harmer
1.377
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3151041BRUNSWICKG3
50/50
8.436
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970301AG2-198 GEN
Solar/Wind Harmer
17.428
313527AB2-043 GEN
Solar/Wind Harmer
4.632
970323AG2-213 GEN
Solar/Wind Harmer
13.764
942671AE2-283 GEN
Solar/Wind Harmer
4.906
316049AB1-081 GEN
Solar/Wind Harmer
1.418
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316487AF1-042 GEN
Solar/Wind Helper
0.321
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
970917AG2-570 GEN
Solar/Wind Harmer
168.871
970257AG2-171 GEN
Solar/Wind Harmer
10.323
971775AH1-396 GEN
Solar/Wind Harmer
1.942
3146926FARMVIL
Solar/Wind Harmer
-0.015
316217AC1-145 GEN
Solar/Wind Harmer
2.402
316197AC1-042 GEN
Solar/Wind Harmer
1.821
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316321Z2-027
Solar/Wind Helper
0.485
3141906WESTMOR
Solar/Wind Helper
0.116
3146626S HERTFORD
Solar/Wind Helper
0.279
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
970909AG2-566 GEN
50/50
3.309
3144293JTRSVLE
50/50
0.601
970099AG2-077 GEN
Solar/Wind Harmer
66.815
315687AD1-152 GEN
Solar/Wind Harmer
5.329
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
971683AH1-343 GEN
Solar/Wind Harmer
13.215
964241AG1-285 GEN
Solar/Wind Harmer
22.01
316123AC1-075 GEN
Solar/Wind Harmer
2.792
942461AE2-259 GEN
Solar/Wind Harmer
3.838
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
315244AE2-183_ST
50/50
19.288
3151541CLOVER2
50/50
9.313
3151631KERR 6
50/50
0.53
316238AB2-078_GEN
Solar/Wind Harmer
0.865
316239AB2-077_GEN
Solar/Wind Harmer
0.865
970683AG2-441 GEN
Solar/Wind Harmer
19.124
970681AG2-440 GEN
Solar/Wind Harmer
12.693
970831AG2-522 GEN
Solar/Wind Harmer
9.533
316322AB2-045
Solar/Wind Harmer
0.516
316316AC1-027 C
Solar/Wind Helper
0.603
315839AE2-212 C
Solar/Wind Helper
0.496
315697AD1-025 GEN
Solar/Wind Helper
4.048
957831AF2-077 GEN
Solar/Wind Helper
0.468
3141913WHIT STONE
Solar/Wind Helper
0.326
316468AD1-105 GEN
Solar/Wind Helper
1.285
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
970401AG2-262 GEN
Solar/Wind Harmer
2.098
316034AC1-036 C
Solar/Wind Harmer
0.509
971065AG2-659 GEN
Solar/Wind Harmer
11.131
316129AC1-054 GEN
Solar/Wind Harmer
1.825
270016AE1-250 BESS
Solar/Wind Harmer
2.845
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
315671AE2-027_GEN
Solar/Wind Helper
2.891
316072AD1-144
Solar/Wind Helper
0.405
964211AG1-282 GEN
Solar/Wind Helper
0.416
3143526WINTERP
Solar/Wind Helper
1.518
972187AH1-678 GEN
50/50
19.356
970535AG2-341 GEN
50/50
4.57
316118AC1-105 GEN
Solar/Wind Harmer
2.295
964791AG1-342 GEN
Solar/Wind Harmer
6.865
942751AE2-291 GEN
Solar/Wind Harmer
15.125
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
5.064
316240AF1-291 C
Solar/Wind Helper
0.475
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
316435W1029_GEN3
Solar/Wind Helper
1.221
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
966871AG1-558 GEN
Solar/Wind Helper
0.382
316248AF1-058 C
Solar/Wind Harmer
1.044
962561AG1-105 GEN
Solar/Wind Harmer
17.768
316237AB2-079_GEN
Solar/Wind Harmer
0.865
270013AE1-250 PV
Solar/Wind Harmer
2.845
316263AC1-034 GEN
Solar/Wind Harmer
6.176
316185AD1-033 GEN
Solar/Wind Helper
1.79
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316312AB1-027
Solar/Wind Helper
0.567
3143526WINTERP
Solar/Wind Helper
1.518
316375AC2-012 GEN
Solar/Wind Helper
1.012
3145336SMITFLD
Solar/Wind Helper
1.485
3146456SLIGO L269
Solar/Wind Helper
0.357
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
970933AG2-581 GEN
Solar/Wind Harmer
59.249
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
958211AF2-115 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316294AC1-161 GEN
Solar/Wind Helper
7.701
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
3151601KERR 3
50/50
0.53
970581AG2-369 GEN
Solar/Wind Harmer
35.495
270069AE2-166 C O1
Solar/Wind Harmer
8.011
3143316POE
Solar/Wind Helper
1.548
316236AE1-162_GEN
Solar/Wind Helper
0.501
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
3141873WAN 176
Solar/Wind Helper
0.066
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
TVALTFEXP_TVA->PJM
CLTF
7.333
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
MECLTFEXP_MEC->PJM
CLTF
7.397
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.56 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5223.84
MW Contribution:
17.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
4.218
316003AC1-222 GEN
Solar/Wind Harmer
3.188
316222AC1-221 GEN
Solar/Wind Harmer
3.202
316283AC2-100 C
Solar/Wind Harmer
2.967
959311AF2-222 GEN
Solar/Wind Harmer
28.621
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270574AD1-017 GEN2
Solar/Wind Harmer
5.584
943811AF1-049 GEN
Solar/Wind Harmer
3.841
270336AE1-100 GEN
Solar/Wind Harmer
1.564
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.667
3146456SLIGO L269
Solar/Wind Helper
0.359
3142946ENON
Solar/Wind Helper
0.105
316473AC1-191 GEN
Solar/Wind Helper
1.693
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146376EDENTON
Solar/Wind Helper
0.226
3151031BRUNSWICKG2
50/50
8.378
3146776BUCKING
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.26
3142956BIRDNECK
Solar/Wind Helper
0.258
3144536CHRHLND
Solar/Wind Helper
0.058
316305AF2-043 C
Solar/Wind Helper
0.474
316320Y1-086
Solar/Wind Helper
0.149
3146516WINFALL
Solar/Wind Helper
0.296
316223AC1-118
Solar/Wind Helper
0.438
971967AH1-528 GEN
Solar/Wind Harmer
123.886
970085AG2-068 GEN
Solar/Wind Harmer
41.004
3144303KENBRDG
Solar/Wind Harmer
-0.022
946301AF1-294 GEN
Solar/Wind Harmer
6.829
963041AG1-153 GEN
50/50
16.962
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
316486AD2-202 GEN
Solar/Wind Harmer
1.235
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
961791AG1-021 GEN
Solar/Wind Harmer
3.331
270455AD2-022 GEN
Solar/Wind Harmer
4.705
971845AH1-439 GEN
Solar/Wind Harmer
8.548
270197AD1-017 GEN1
Solar/Wind Harmer
1.675
313526AB2-022
Solar/Wind Helper
0.505
316059AD1-063 C
Solar/Wind Helper
0.326
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
270457AD2-023 GEN
Solar/Wind Harmer
2.386
316018AA1-139 ULT2
Solar/Wind Helper
1.569
957601AF2-054 GEN
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.304
316233AE1-074 FULL
Solar/Wind Helper
0.44
315800Z1-036_GEN1
Solar/Wind Helper
1.313
3151021BRUNSWICKG1
50/50
8.378
970087AG2-069 GEN
Solar/Wind Harmer
61.506
957481AF2-042 GEN
Solar/Wind Harmer
166.083
315693AD1-088 GEN
Solar/Wind Harmer
24.245
315785AD2-033 C
Solar/Wind Harmer
6.277
970685AG2-442 GEN
Solar/Wind Harmer
23.525
971563AH1-280 GEN
Solar/Wind Harmer
3.331
3146926FARMVIL
Solar/Wind Harmer
-0.015
970223AG2-152 GEN
Solar/Wind Harmer
17.186
270018AE2-047 C O1
Solar/Wind Harmer
1.373
3151591KERR 2
50/50
0.532
3151641KERR 7
50/50
0.532
3151561HALLBR1
50/50
0.362
970919AG2-571 GEN
Solar/Wind Harmer
21.235
3146776BUCKING
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
5.539
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
9.171
316036AC1-147 C
Solar/Wind Helper
0.591
316132AB2-190 GEN1
Solar/Wind Helper
1.935
3141726DUNNSVL
Solar/Wind Helper
1.22
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
316337AD2-073 GEN
Solar/Wind Helper
0.449
3151041BRUNSWICKG3
50/50
8.378
3152661PLYWOOD A
50/50
0.662
3151581KERR 1
50/50
0.19
970301AG2-198 GEN
Solar/Wind Harmer
17.344
313527AB2-043 GEN
Solar/Wind Harmer
4.644
970323AG2-213 GEN
Solar/Wind Harmer
13.779
942671AE2-283 GEN
Solar/Wind Harmer
4.893
316049AB1-081 GEN
Solar/Wind Harmer
1.452
3145506HICKORY
Solar/Wind Helper
1.505
3145506HICKORY
Solar/Wind Helper
0.903
3145506HICKORY
Solar/Wind Helper
0.226
316339AD2-160 GEN
Solar/Wind Helper
1.399
316388AE2-253 GEN
Solar/Wind Helper
1.399
3137176SLIGO L2192
Solar/Wind Helper
1.43
3130086AYDLETT
Solar/Wind Helper
1.419
316033AB2-134 GEN
Solar/Wind Helper
1.198
316487AF1-042 GEN
Solar/Wind Helper
0.317
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
970917AG2-570 GEN
Solar/Wind Harmer
167.755
970257AG2-171 GEN
Solar/Wind Harmer
10.334
971775AH1-396 GEN
Solar/Wind Harmer
1.944
3146926FARMVIL
Solar/Wind Harmer
-0.015
316217AC1-145 GEN
Solar/Wind Harmer
2.396
316197AC1-042 GEN
Solar/Wind Harmer
1.816
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
1.935
316321Z2-027
Solar/Wind Helper
0.487
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.279
970413AG2-270 GEN
50/50
40.656
3144293JTRSVLE
50/50
0.601
971683AH1-343 GEN
Solar/Wind Harmer
13.175
964241AG1-285 GEN
Solar/Wind Harmer
22.056
316123AC1-075 GEN
Solar/Wind Harmer
2.783
942461AE2-259 GEN
Solar/Wind Harmer
3.829
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.606
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.287
315244AE2-183_ST
50/50
19.154
3151541CLOVER2
50/50
9.264
3151631KERR 6
50/50
0.532
316238AB2-078_GEN
Solar/Wind Harmer
0.867
316239AB2-077_GEN
Solar/Wind Harmer
0.867
970683AG2-441 GEN
Solar/Wind Harmer
19.131
970681AG2-440 GEN
Solar/Wind Harmer
12.698
970831AG2-522 GEN
Solar/Wind Harmer
9.671
316322AB2-045
Solar/Wind Harmer
0.514
316316AC1-027 C
Solar/Wind Helper
0.607
315697AD1-025 GEN
Solar/Wind Helper
3.957
957831AF2-077 GEN
Solar/Wind Helper
0.465
315839AE2-212 C
Solar/Wind Helper
0.458
3141913WHIT STONE
Solar/Wind Helper
0.323
316468AD1-105 GEN
Solar/Wind Helper
1.26
315243AE2-183_GT3
50/50
11.03
3151051BRUNSWICKS1
50/50
17.394
971451AH1-221 GEN
50/50
25.443
3151531CLOVER1
50/50
9.336
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.474
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316034AC1-036 C
Solar/Wind Harmer
0.509
971065AG2-659 GEN
Solar/Wind Harmer
11.235
316129AC1-054 GEN
Solar/Wind Harmer
1.845
270016AE1-250 BESS
Solar/Wind Harmer
2.837
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
316072AD1-144
Solar/Wind Helper
0.405
315671AE2-027_GEN
Solar/Wind Helper
2.696
964211AG1-282 GEN
Solar/Wind Helper
0.411
3143526WINTERP
Solar/Wind Helper
1.497
972187AH1-678 GEN
50/50
19.224
970535AG2-341 GEN
50/50
4.581
316118AC1-105 GEN
Solar/Wind Harmer
2.29
964791AG1-342 GEN
Solar/Wind Harmer
6.859
942751AE2-291 GEN
Solar/Wind Harmer
15.08
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
5.194
316240AF1-291 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.493
315666AE1-190 GEN
Solar/Wind Helper
0.437
316435W1029_GEN3
Solar/Wind Helper
1.223
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
966871AG1-558 GEN
Solar/Wind Helper
0.374
315242AE2-183_GT2
50/50
11.03
315241AE2-183_GT1
50/50
11.001
972185AH1-677 GEN
50/50
39.871
970909AG2-566 GEN
50/50
3.293
3144293JTRSVLE
50/50
0.601
970099AG2-077 GEN
Solar/Wind Harmer
66.433
315687AD1-152 GEN
Solar/Wind Harmer
5.303
316248AF1-058 C
Solar/Wind Harmer
1.041
962561AG1-105 GEN
Solar/Wind Harmer
17.76
316237AB2-079_GEN
Solar/Wind Harmer
0.867
270013AE1-250 PV
Solar/Wind Harmer
2.837
316263AC1-034 GEN
Solar/Wind Harmer
6.326
316185AD1-033 GEN
Solar/Wind Helper
1.802
316312AB1-027
Solar/Wind Helper
0.557
3143526WINTERP
Solar/Wind Helper
1.497
3144356SAPONY
Solar/Wind Helper
0.491
316315AB2-025 C
Solar/Wind Helper
0.418
319010AE1-072 C
Solar/Wind Helper
4.082
316369SG1_INVT
Solar/Wind Helper
1.668
316381AD1-082 GEN
Solar/Wind Helper
1.76
315662AE1-191 GEN
Solar/Wind Helper
1.75
316280AD1-041 GEN
Solar/Wind Helper
1.093
3138133OCRAN
Solar/Wind Helper
0.193
316404AE1-155 C
Solar/Wind Helper
2.656
3142543TWELFTH
Solar/Wind Helper
0.029
3143226MDLTHAN
Solar/Wind Helper
0.284
315611Z1-036_GEN2
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
971629AH1-314 GEN
50/50
17.894
316131AB2-060 GEN
Solar/Wind Harmer
3.07
3147123OTTER R
Solar/Wind Harmer
-0.01
270030AE2-140 GEN
Solar/Wind Harmer
19.766
316359AB2-059 GEN
Solar/Wind Harmer
1.815
3142053HEARTS
Solar/Wind Harmer
0.159
316375AC2-012 GEN
Solar/Wind Helper
1.018
3145336SMITFLD
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.359
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.273
315975AC1-164 GENB
Solar/Wind Helper
0.119
3142416OLDCHRC
Solar/Wind Helper
0.758
3142416OLDCHRC
Solar/Wind Helper
0.29
970933AG2-581 GEN
Solar/Wind Harmer
58.871
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
958211AF2-115 GEN
Solar/Wind Harmer
4.164
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316294AC1-161 GEN
Solar/Wind Helper
7.794
316349AD2-085 GEN
Solar/Wind Helper
1.524
3146386ELIZ CT
Solar/Wind Helper
0.331
3142946ENON
Solar/Wind Helper
0.031
315976AC1-164 GENA
Solar/Wind Helper
4.039
316169AC1-164_GENC
Solar/Wind Helper
3.489
316431W1029_GEN1
Solar/Wind Helper
1.223
316433W1029_GEN2
Solar/Wind Helper
1.223
3151601KERR 3
50/50
0.532
970581AG2-369 GEN
Solar/Wind Harmer
35.263
270069AE2-166 C O1
Solar/Wind Harmer
7.989
316236AE1-162_GEN
Solar/Wind Helper
0.499
3143316POE
Solar/Wind Helper
1.405
316382AG1-145 C
Solar/Wind Helper
0.47
316159AE1-175 C
Solar/Wind Helper
0.53
3141873WAN 176
Solar/Wind Helper
0.065
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3145176PASQUOTANK
Solar/Wind Helper
0.197
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.661
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.209
TVALTFEXP_TVA->PJM
CLTF
7.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.147
CPLELTFEXP_CPLE->PJM
CLTF
19.725
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.242
MECLTFEXP_MEC->PJM
CLTF
7.373
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.679
WECLTFEXP_WEC->PJM
CLTF
1.402
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.0 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5145.98
MW Contribution:
17.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
4.179
316003AC1-222 GEN
Solar/Wind Harmer
3.156
316222AC1-221 GEN
Solar/Wind Harmer
3.175
316283AC2-100 C
Solar/Wind Harmer
2.943
959311AF2-222 GEN
Solar/Wind Harmer
28.221
3147133PAMPLIN
Solar/Wind Harmer
-0.081
270574AD1-017 GEN2
Solar/Wind Harmer
5.536
943811AF1-049 GEN
Solar/Wind Harmer
3.808
270336AE1-100 GEN
Solar/Wind Harmer
1.55
3145336SMITFLD
Solar/Wind Helper
0.133
316017AA1-139 ULT1
Solar/Wind Helper
1.432
3142946ENON
Solar/Wind Helper
0.104
3146456SLIGO L269
Solar/Wind Helper
0.308
316473AC1-191 GEN
Solar/Wind Helper
1.701
966881AG1-559 GEN
Solar/Wind Helper
0.328
3151031BRUNSWICKG2
50/50
8.307
3146776BUCKING
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.233
3144536CHRHLND
Solar/Wind Helper
0.05
3142956BIRDNECK
Solar/Wind Helper
0.223
316305AF2-043 C
Solar/Wind Helper
0.402
316320Y1-086
Solar/Wind Helper
0.127
316223AC1-118
Solar/Wind Helper
0.424
3146516WINFALL
Solar/Wind Helper
0.25
963041AG1-153 GEN
50/50
16.818
3151611KERR 4
50/50
0.526
3151621KERR 5
50/50
0.526
316486AD2-202 GEN
Solar/Wind Harmer
1.224
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
961791AG1-021 GEN
Solar/Wind Harmer
3.286
270455AD2-022 GEN
Solar/Wind Harmer
4.668
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
971845AH1-439 GEN
Solar/Wind Harmer
8.41
316059AD1-063 C
Solar/Wind Helper
0.313
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.122
313526AB2-022
Solar/Wind Helper
0.431
971967AH1-528 GEN
Solar/Wind Harmer
122.813
970085AG2-068 GEN
Solar/Wind Harmer
40.657
3144303KENBRDG
Solar/Wind Harmer
-0.022
946301AF1-294 GEN
Solar/Wind Harmer
6.735
270457AD2-023 GEN
Solar/Wind Harmer
2.367
316018AA1-139 ULT2
Solar/Wind Helper
1.348
957601AF2-054 GEN
Solar/Wind Helper
0.417
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.445
3151591KERR 2
50/50
0.526
3151641KERR 7
50/50
0.526
3151561HALLBR1
50/50
0.359
970919AG2-571 GEN
Solar/Wind Harmer
21.055
3146776BUCKING
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
5.486
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
8.532
316036AC1-147 C
Solar/Wind Helper
0.512
316132AB2-190 GEN1
Solar/Wind Helper
1.896
3141726DUNNSVL
Solar/Wind Helper
1.177
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.811
3146516WINFALL
Solar/Wind Helper
0.25
3151041BRUNSWICKG3
50/50
8.307
3152661PLYWOOD A
50/50
0.655
3151581KERR 1
50/50
0.188
970301AG2-198 GEN
Solar/Wind Harmer
17.157
313527AB2-043 GEN
Solar/Wind Harmer
4.577
970323AG2-213 GEN
Solar/Wind Harmer
13.586
942671AE2-283 GEN
Solar/Wind Harmer
4.846
316049AB1-081 GEN
Solar/Wind Harmer
1.446
316033AB2-134 GEN
Solar/Wind Helper
1.145
3145506HICKORY
Solar/Wind Helper
1.296
3145506HICKORY
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.194
316339AD2-160 GEN
Solar/Wind Helper
1.203
316388AE2-253 GEN
Solar/Wind Helper
1.203
3137176SLIGO L2192
Solar/Wind Helper
1.227
3130086AYDLETT
Solar/Wind Helper
1.217
316487AF1-042 GEN
Solar/Wind Helper
0.305
970413AG2-270 GEN
50/50
40.285
3144293JTRSVLE
50/50
0.593
971683AH1-343 GEN
Solar/Wind Harmer
13.046
964241AG1-285 GEN
Solar/Wind Harmer
21.742
316123AC1-075 GEN
Solar/Wind Harmer
2.756
942461AE2-259 GEN
Solar/Wind Harmer
3.778
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.582
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
315244AE2-183_ST
50/50
18.991
3151541CLOVER2
50/50
9.18
3151631KERR 6
50/50
0.526
316238AB2-078_GEN
Solar/Wind Harmer
0.854
316239AB2-077_GEN
Solar/Wind Harmer
0.854
970683AG2-441 GEN
Solar/Wind Harmer
18.866
970681AG2-440 GEN
Solar/Wind Harmer
12.522
970831AG2-522 GEN
Solar/Wind Harmer
9.555
316322AB2-045
Solar/Wind Harmer
0.505
315839AE2-212 C
Solar/Wind Helper
0.498
316316AC1-027 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
3.782
957831AF2-077 GEN
Solar/Wind Helper
0.436
3141913WHIT STONE
Solar/Wind Helper
0.309
316468AD1-105 GEN
Solar/Wind Helper
1.263
315243AE2-183_GT3
50/50
10.936
3151051BRUNSWICKS1
50/50
17.246
971451AH1-221 GEN
50/50
25.226
3151531CLOVER1
50/50
9.25
3144293JTRSVLE
50/50
0.593
3144293JTRSVLE
50/50
0.468
970401AG2-262 GEN
Solar/Wind Harmer
2.072
316034AC1-036 C
Solar/Wind Harmer
0.502
971065AG2-659 GEN
Solar/Wind Harmer
11.105
316129AC1-054 GEN
Solar/Wind Harmer
1.824
270016AE1-250 BESS
Solar/Wind Harmer
2.814
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
315671AE2-027_GEN
Solar/Wind Helper
2.884
316072AD1-144
Solar/Wind Helper
0.351
964211AG1-282 GEN
Solar/Wind Helper
0.397
3143526WINTERP
Solar/Wind Helper
1.516
315242AE2-183_GT2
50/50
10.936
315241AE2-183_GT1
50/50
10.907
972185AH1-677 GEN
50/50
39.531
970909AG2-566 GEN
50/50
3.258
3144293JTRSVLE
50/50
0.593
970099AG2-077 GEN
Solar/Wind Harmer
65.833
315687AD1-152 GEN
Solar/Wind Harmer
5.255
316248AF1-058 C
Solar/Wind Harmer
1.031
962561AG1-105 GEN
Solar/Wind Harmer
17.549
316237AB2-079_GEN
Solar/Wind Harmer
0.854
270013AE1-250 PV
Solar/Wind Harmer
2.814
316263AC1-034 GEN
Solar/Wind Harmer
6.299
316185AD1-033 GEN
Solar/Wind Helper
1.553
3144356SAPONY
Solar/Wind Helper
0.58
316315AB2-025 C
Solar/Wind Helper
0.494
3143526WINTERP
Solar/Wind Helper
1.516
316312AB1-027
Solar/Wind Helper
0.551
970917AG2-570 GEN
Solar/Wind Harmer
166.334
970257AG2-171 GEN
Solar/Wind Harmer
10.19
971775AH1-396 GEN
Solar/Wind Harmer
1.917
3146926FARMVIL
Solar/Wind Harmer
-0.014
316217AC1-145 GEN
Solar/Wind Harmer
2.372
316197AC1-042 GEN
Solar/Wind Harmer
1.798
3144873MCLAUGH
Solar/Wind Helper
0.008
316458AB2-190 GEN2
Solar/Wind Helper
1.896
316246AF1-032 C
Solar/Wind Helper
0.342
3141906WESTMOR
Solar/Wind Helper
0.111
316321Z2-027
Solar/Wind Helper
0.414
3146626S HERTFORD
Solar/Wind Helper
0.235
3151021BRUNSWICKG1
50/50
8.307
970087AG2-069 GEN
Solar/Wind Harmer
60.986
957481AF2-042 GEN
Solar/Wind Harmer
164.583
315693AD1-088 GEN
Solar/Wind Harmer
24.018
315785AD2-033 C
Solar/Wind Harmer
6.188
970685AG2-442 GEN
Solar/Wind Harmer
23.201
971563AH1-280 GEN
Solar/Wind Harmer
3.286
3146926FARMVIL
Solar/Wind Harmer
-0.014
970223AG2-152 GEN
Solar/Wind Harmer
17.044
270018AE2-047 C O1
Solar/Wind Harmer
1.362
316381AD1-082 GEN
Solar/Wind Helper
1.75
316369SG1_INVT
Solar/Wind Helper
1.594
3142543TWELFTH
Solar/Wind Helper
0.03
315662AE1-191 GEN
Solar/Wind Helper
1.677
316280AD1-041 GEN
Solar/Wind Helper
1.048
3138133OCRAN
Solar/Wind Helper
0.185
319010AE1-072 C
Solar/Wind Helper
3.502
316404AE1-155 C
Solar/Wind Helper
2.553
3143226MDLTHAN
Solar/Wind Helper
0.289
971629AH1-314 GEN
50/50
17.75
316131AB2-060 GEN
Solar/Wind Harmer
3.026
3147123OTTER R
Solar/Wind Harmer
-0.01
270030AE2-140 GEN
Solar/Wind Harmer
19.599
316359AB2-059 GEN
Solar/Wind Harmer
1.807
3142053HEARTS
Solar/Wind Harmer
0.158
316375AC2-012 GEN
Solar/Wind Helper
0.883
3145336SMITFLD
Solar/Wind Helper
1.329
3142433PROV 92
Solar/Wind Helper
1.252
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
315975AC1-164 GENB
Solar/Wind Helper
0.116
3142416OLDCHRC
Solar/Wind Helper
0.75
3142416OLDCHRC
Solar/Wind Helper
0.287
972187AH1-678 GEN
50/50
19.06
970535AG2-341 GEN
50/50
4.523
316118AC1-105 GEN
Solar/Wind Harmer
2.266
964791AG1-342 GEN
Solar/Wind Harmer
6.78
942751AE2-291 GEN
Solar/Wind Harmer
14.933
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
5.168
316240AF1-291 C
Solar/Wind Helper
0.472
316156AD2-030 GEN
Solar/Wind Helper
0.471
315666AE1-190 GEN
Solar/Wind Helper
0.419
966871AG1-558 GEN
Solar/Wind Helper
0.375
316435W1029_GEN3
Solar/Wind Helper
1.035
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
970933AG2-581 GEN
Solar/Wind Harmer
58.356
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
958211AF2-115 GEN
Solar/Wind Harmer
4.107
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316294AC1-161 GEN
Solar/Wind Helper
7.251
3142946ENON
Solar/Wind Helper
0.031
3146626S HERTFORD
Solar/Wind Helper
0.235
3146626S HERTFORD
Solar/Wind Helper
0.235
3151601KERR 3
50/50
0.526
970581AG2-369 GEN
Solar/Wind Harmer
34.965
270069AE2-166 C O1
Solar/Wind Harmer
7.921
3143316POE
Solar/Wind Helper
1.568
316236AE1-162_GEN
Solar/Wind Helper
0.448
316382AG1-145 C
Solar/Wind Helper
0.442
316159AE1-175 C
Solar/Wind Helper
0.498
3141873WAN 176
Solar/Wind Helper
0.062
3143873LANEXA
Solar/Wind Helper
0.186
3138133OCRAN
Solar/Wind Helper
0.092
3146486SUNBURY
Solar/Wind Helper
0.273
3146486SUNBURY
Solar/Wind Helper
0.273
3145176PASQUOTANK
Solar/Wind Helper
0.168
316349AD2-085 GEN
Solar/Wind Helper
1.397
315976AC1-164 GENA
Solar/Wind Helper
3.933
316169AC1-164_GENC
Solar/Wind Helper
3.397
3146386ELIZ CT
Solar/Wind Helper
0.282
316431W1029_GEN1
Solar/Wind Helper
1.035
316433W1029_GEN2
Solar/Wind Helper
1.035
LAGNLTFEXP_LAGN->PJM
CLTF
14.534
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.89
TVALTFEXP_TVA->PJM
CLTF
7.248
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.924
MECLTFEXP_MEC->PJM
CLTF
7.297
CPLELTFEXP_CPLE->PJM
CLTF
19.597
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.518
SIGELTFEXP_SIGE->PJM
CLTF
0.219
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.65
WECLTFEXP_WEC->PJM
CLTF
1.386
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.1 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5173.4
MW Contribution:
17.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
1.514
316222AC1-221 GEN
Solar/Wind Harmer
1.167
316283AC2-100 C
Solar/Wind Harmer
0.55
959311AF2-222 GEN
Solar/Wind Harmer
21.675
3147133PAMPLIN
Solar/Wind Harmer
0.736
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
971623AH1-311 GEN
Solar/Wind Harmer
0.235
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
3142946ENON
Solar/Wind Helper
0.108
316473AC1-191 GEN
Solar/Wind Helper
1.733
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
972187AH1-678 GEN
50/50
19.356
970535AG2-341 GEN
50/50
4.57
316118AC1-105 GEN
Solar/Wind Harmer
0.762
964791AG1-342 GEN
Solar/Wind Harmer
5.492
942751AE2-291 GEN
Solar/Wind Harmer
11.487
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
961601AG1-000A GEN
Solar/Wind Harmer
2.039
316240AF1-291 C
Solar/Wind Helper
0.475
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
316435W1029_GEN3
Solar/Wind Helper
1.221
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
966871AG1-558 GEN
Solar/Wind Helper
0.382
963041AG1-153 GEN
50/50
17.078
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
316486AD2-202 GEN
Solar/Wind Harmer
0.444
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
961791AG1-021 GEN
Solar/Wind Harmer
2.278
971845AH1-439 GEN
Solar/Wind Harmer
6.517
270197AD1-017 GEN1
Solar/Wind Harmer
0.942
313526AB2-022
Solar/Wind Helper
0.503
316059AD1-063 C
Solar/Wind Helper
0.33
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3151041BRUNSWICKG3
50/50
8.436
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970301AG2-198 GEN
Solar/Wind Harmer
13.237
970323AG2-213 GEN
Solar/Wind Harmer
10.454
942671AE2-283 GEN
Solar/Wind Harmer
3.281
316049AB1-081 GEN
Solar/Wind Harmer
0.667
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316487AF1-042 GEN
Solar/Wind Helper
0.321
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
3151601KERR 3
50/50
0.53
970533AG2-339 GEN
Solar/Wind Harmer
56.74
970581AG2-369 GEN
Solar/Wind Harmer
26.958
270069AE2-166 C O1
Solar/Wind Harmer
5.589
3143316POE
Solar/Wind Helper
1.548
316236AE1-162_GEN
Solar/Wind Helper
0.501
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
3141873WAN 176
Solar/Wind Helper
0.066
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151021BRUNSWICKG1
50/50
8.436
970087AG2-069 GEN
Solar/Wind Harmer
47.021
957481AF2-042 GEN
Solar/Wind Harmer
126.864
315693AD1-088 GEN
Solar/Wind Harmer
20.828
315785AD2-033 C
Solar/Wind Harmer
1.994
970685AG2-442 GEN
Solar/Wind Harmer
17.866
971563AH1-280 GEN
Solar/Wind Harmer
2.531
3146926FARMVIL
Solar/Wind Harmer
0.131
970223AG2-152 GEN
Solar/Wind Harmer
12.084
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.288
3151541CLOVER2
50/50
9.313
3151631KERR 6
50/50
0.53
970673AG2-436 GEN
Solar/Wind Harmer
89.687
970683AG2-441 GEN
Solar/Wind Harmer
14.525
970681AG2-440 GEN
Solar/Wind Harmer
9.64
970831AG2-522 GEN
Solar/Wind Harmer
7.24
316316AC1-027 C
Solar/Wind Helper
0.603
315839AE2-212 C
Solar/Wind Helper
0.496
315697AD1-025 GEN
Solar/Wind Helper
4.048
957831AF2-077 GEN
Solar/Wind Helper
0.468
3141913WHIT STONE
Solar/Wind Helper
0.326
316468AD1-105 GEN
Solar/Wind Helper
1.285
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
941031AE2-094 GEN
Solar/Wind Harmer
138.312
970401AG2-262 GEN
Solar/Wind Harmer
1.678
316034AC1-036 C
Solar/Wind Harmer
0.016
971065AG2-659 GEN
Solar/Wind Harmer
8.454
316129AC1-054 GEN
Solar/Wind Harmer
0.693
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
315671AE2-027_GEN
Solar/Wind Helper
2.891
316072AD1-144
Solar/Wind Helper
0.405
964211AG1-282 GEN
Solar/Wind Helper
0.416
3143526WINTERP
Solar/Wind Helper
1.518
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
970909AG2-566 GEN
50/50
3.309
3144293JTRSVLE
50/50
0.601
970099AG2-077 GEN
Solar/Wind Harmer
50.746
962561AG1-105 GEN
Solar/Wind Harmer
13.495
316263AC1-034 GEN
Solar/Wind Harmer
4.456
316185AD1-033 GEN
Solar/Wind Helper
1.79
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316312AB1-027
Solar/Wind Helper
0.567
3143526WINTERP
Solar/Wind Helper
1.518
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
3146776BUCKING
Solar/Wind Harmer
0.055
941801AE2-185 GEN
Solar/Wind Harmer
4.219
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.094
315773AC2-141 GEN
Solar/Wind Helper
9.062
316036AC1-147 C
Solar/Wind Helper
0.587
316132AB2-190 GEN1
Solar/Wind Helper
1.996
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
971629AH1-314 GEN
50/50
17.942
316131AB2-060 GEN
Solar/Wind Harmer
0.788
3147123OTTER R
Solar/Wind Harmer
0.088
270030AE2-140 GEN
Solar/Wind Harmer
13.827
316359AB2-059 GEN
Solar/Wind Harmer
0.417
3142053HEARTS
Solar/Wind Harmer
0.206
316375AC2-012 GEN
Solar/Wind Helper
1.012
3145336SMITFLD
Solar/Wind Helper
1.485
3146456SLIGO L269
Solar/Wind Helper
0.357
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
970933AG2-581 GEN
Solar/Wind Harmer
44.999
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
958211AF2-115 GEN
Solar/Wind Harmer
2.847
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.188
316294AC1-161 GEN
Solar/Wind Helper
7.701
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
971683AH1-343 GEN
Solar/Wind Harmer
10.037
964241AG1-285 GEN
Solar/Wind Harmer
16.717
316123AC1-075 GEN
Solar/Wind Harmer
0.308
942461AE2-259 GEN
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.026
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
3151031BRUNSWICKG2
50/50
8.436
944011AF1-069 GEN
Solar/Wind Harmer
45.192
3146776BUCKING
Solar/Wind Harmer
0.049
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.118
961601AG1-000A GEN
Solar/Wind Harmer
8.154
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
316305AF2-043 C
Solar/Wind Helper
0.472
316320Y1-086
Solar/Wind Helper
0.148
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
970917AG2-570 GEN
Solar/Wind Harmer
53.44
970257AG2-171 GEN
Solar/Wind Harmer
7.84
971775AH1-396 GEN
Solar/Wind Harmer
0.392
3146926FARMVIL
Solar/Wind Harmer
0.131
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316321Z2-027
Solar/Wind Helper
0.485
3141906WESTMOR
Solar/Wind Helper
0.116
3146626S HERTFORD
Solar/Wind Helper
0.279
971967AH1-528 GEN
Solar/Wind Harmer
94.459
970085AG2-068 GEN
Solar/Wind Harmer
31.347
3144303KENBRDG
Solar/Wind Harmer
0.196
946301AF1-294 GEN
Solar/Wind Harmer
4.682
316018AA1-139 ULT2
Solar/Wind Helper
1.56
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
315800Z1-036_GEN1
Solar/Wind Helper
1.317
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
TVALTFEXP_TVA->PJM
CLTF
7.333
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
MECLTFEXP_MEC->PJM
CLTF
7.397
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.85 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5687.87
MW Contribution:
17.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
970917AG2-570 GEN
Solar/Wind Harmer
168.871
970257AG2-171 GEN
Solar/Wind Harmer
10.323
971775AH1-396 GEN
Solar/Wind Harmer
1.942
3146926FARMVIL
Solar/Wind Harmer
-0.015
316217AC1-145 GEN
Solar/Wind Harmer
2.402
316197AC1-042 GEN
Solar/Wind Harmer
1.821
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316321Z2-027
Solar/Wind Helper
0.485
3141906WESTMOR
Solar/Wind Helper
0.116
3146626S HERTFORD
Solar/Wind Helper
0.279
3151021BRUNSWICKG1
50/50
8.436
970087AG2-069 GEN
Solar/Wind Harmer
61.91
957481AF2-042 GEN
Solar/Wind Harmer
167.038
315693AD1-088 GEN
Solar/Wind Harmer
24.377
315785AD2-033 C
Solar/Wind Harmer
6.268
970685AG2-442 GEN
Solar/Wind Harmer
23.524
971563AH1-280 GEN
Solar/Wind Harmer
3.332
3146926FARMVIL
Solar/Wind Harmer
-0.015
970223AG2-152 GEN
Solar/Wind Harmer
17.233
270018AE2-047 C O1
Solar/Wind Harmer
1.377
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
316478AD1-087 GEN
Solar/Wind Harmer
4.24
316003AC1-222 GEN
Solar/Wind Harmer
3.197
316222AC1-221 GEN
Solar/Wind Harmer
3.212
316283AC2-100 C
Solar/Wind Harmer
2.976
959311AF2-222 GEN
Solar/Wind Harmer
28.596
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270574AD1-017 GEN2
Solar/Wind Harmer
5.599
943811AF1-049 GEN
Solar/Wind Harmer
3.851
270336AE1-100 GEN
Solar/Wind Harmer
1.568
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
3142946ENON
Solar/Wind Helper
0.108
316473AC1-191 GEN
Solar/Wind Helper
1.733
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
963041AG1-153 GEN
50/50
17.078
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
316486AD2-202 GEN
Solar/Wind Harmer
1.242
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.022
961791AG1-021 GEN
Solar/Wind Harmer
3.332
270455AD2-022 GEN
Solar/Wind Harmer
4.718
971845AH1-439 GEN
Solar/Wind Harmer
8.58
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
313526AB2-022
Solar/Wind Helper
0.503
316059AD1-063 C
Solar/Wind Helper
0.33
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3151041BRUNSWICKG3
50/50
8.436
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970301AG2-198 GEN
Solar/Wind Harmer
17.428
313527AB2-043 GEN
Solar/Wind Harmer
4.632
970323AG2-213 GEN
Solar/Wind Harmer
13.764
942671AE2-283 GEN
Solar/Wind Harmer
4.906
316049AB1-081 GEN
Solar/Wind Harmer
1.418
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316487AF1-042 GEN
Solar/Wind Helper
0.321
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
3151601KERR 3
50/50
0.53
970533AG2-339 GEN
Solar/Wind Harmer
56.74
970581AG2-369 GEN
Solar/Wind Harmer
35.495
270069AE2-166 C O1
Solar/Wind Harmer
8.011
3143316POE
Solar/Wind Helper
1.548
316236AE1-162_GEN
Solar/Wind Helper
0.501
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
3141873WAN 176
Solar/Wind Helper
0.066
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.436
944011AF1-069 GEN
Solar/Wind Harmer
49.571
3146776BUCKING
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.128
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
316305AF2-043 C
Solar/Wind Helper
0.472
316320Y1-086
Solar/Wind Helper
0.148
3146516WINFALL
Solar/Wind Helper
0.295
972187AH1-678 GEN
50/50
19.356
970535AG2-341 GEN
50/50
4.57
316118AC1-105 GEN
Solar/Wind Harmer
2.295
964791AG1-342 GEN
Solar/Wind Harmer
6.865
942751AE2-291 GEN
Solar/Wind Harmer
15.125
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
5.064
316240AF1-291 C
Solar/Wind Helper
0.475
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
316435W1029_GEN3
Solar/Wind Helper
1.221
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
966871AG1-558 GEN
Solar/Wind Helper
0.382
971967AH1-528 GEN
Solar/Wind Harmer
124.702
970085AG2-068 GEN
Solar/Wind Harmer
41.274
3144303KENBRDG
Solar/Wind Harmer
-0.022
946301AF1-294 GEN
Solar/Wind Harmer
6.831
270457AD2-023 GEN
Solar/Wind Harmer
2.392
316018AA1-139 ULT2
Solar/Wind Helper
1.56
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
315800Z1-036_GEN1
Solar/Wind Helper
1.317
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
3146776BUCKING
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
5.554
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
9.062
316036AC1-147 C
Solar/Wind Helper
0.587
316132AB2-190 GEN1
Solar/Wind Helper
1.996
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
971683AH1-343 GEN
Solar/Wind Harmer
13.215
964241AG1-285 GEN
Solar/Wind Harmer
22.01
316123AC1-075 GEN
Solar/Wind Harmer
2.792
942461AE2-259 GEN
Solar/Wind Harmer
3.838
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
315244AE2-183_ST
50/50
19.288
3151541CLOVER2
50/50
9.313
3151631KERR 6
50/50
0.53
970673AG2-436 GEN
Solar/Wind Harmer
177.133
316238AB2-078_GEN
Solar/Wind Harmer
0.865
316239AB2-077_GEN
Solar/Wind Harmer
0.865
970683AG2-441 GEN
Solar/Wind Harmer
19.124
970681AG2-440 GEN
Solar/Wind Harmer
12.693
970831AG2-522 GEN
Solar/Wind Harmer
9.533
316322AB2-045
Solar/Wind Harmer
0.516
316316AC1-027 C
Solar/Wind Helper
0.603
315839AE2-212 C
Solar/Wind Helper
0.496
315697AD1-025 GEN
Solar/Wind Helper
4.048
957831AF2-077 GEN
Solar/Wind Helper
0.468
3141913WHIT STONE
Solar/Wind Helper
0.326
316468AD1-105 GEN
Solar/Wind Helper
1.285
971629AH1-314 GEN
50/50
17.942
316131AB2-060 GEN
Solar/Wind Harmer
3.062
3147123OTTER R
Solar/Wind Harmer
-0.01
270030AE2-140 GEN
Solar/Wind Harmer
19.819
316359AB2-059 GEN
Solar/Wind Harmer
1.772
3142053HEARTS
Solar/Wind Harmer
0.155
316375AC2-012 GEN
Solar/Wind Helper
1.012
3145336SMITFLD
Solar/Wind Helper
1.485
3146456SLIGO L269
Solar/Wind Helper
0.357
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
941031AE2-094 GEN
Solar/Wind Harmer
158.204
970401AG2-262 GEN
Solar/Wind Harmer
2.098
316034AC1-036 C
Solar/Wind Harmer
0.509
971065AG2-659 GEN
Solar/Wind Harmer
11.131
316129AC1-054 GEN
Solar/Wind Harmer
1.825
270016AE1-250 BESS
Solar/Wind Harmer
2.845
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
315671AE2-027_GEN
Solar/Wind Helper
2.891
316072AD1-144
Solar/Wind Helper
0.405
964211AG1-282 GEN
Solar/Wind Helper
0.416
3143526WINTERP
Solar/Wind Helper
1.518
972185AH1-677 GEN
50/50
40.15
970909AG2-566 GEN
50/50
3.309
3144293JTRSVLE
50/50
0.601
970099AG2-077 GEN
Solar/Wind Harmer
66.815
315687AD1-152 GEN
Solar/Wind Harmer
5.329
316248AF1-058 C
Solar/Wind Harmer
1.044
962561AG1-105 GEN
Solar/Wind Harmer
17.768
316237AB2-079_GEN
Solar/Wind Harmer
0.865
270013AE1-250 PV
Solar/Wind Harmer
2.845
316263AC1-034 GEN
Solar/Wind Harmer
6.176
316185AD1-033 GEN
Solar/Wind Helper
1.79
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316312AB1-027
Solar/Wind Helper
0.567
3143526WINTERP
Solar/Wind Helper
1.518
970933AG2-581 GEN
Solar/Wind Harmer
59.249
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
958211AF2-115 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316294AC1-161 GEN
Solar/Wind Helper
7.701
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
316223AC1-118
Solar/Wind Helper
0.442
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
TVALTFEXP_TVA->PJM
CLTF
7.333
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
MECLTFEXP_MEC->PJM
CLTF
7.397
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.35 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5662.94
MW Contribution:
17.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970917AG2-570 GEN
Solar/Wind Harmer
167.755
970257AG2-171 GEN
Solar/Wind Harmer
10.334
971775AH1-396 GEN
Solar/Wind Harmer
1.944
3146926FARMVIL
Solar/Wind Harmer
-0.015
316217AC1-145 GEN
Solar/Wind Harmer
2.396
316197AC1-042 GEN
Solar/Wind Harmer
1.816
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
1.935
316321Z2-027
Solar/Wind Helper
0.487
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.279
3151021BRUNSWICKG1
50/50
8.378
970087AG2-069 GEN
Solar/Wind Harmer
61.506
957481AF2-042 GEN
Solar/Wind Harmer
166.083
315693AD1-088 GEN
Solar/Wind Harmer
24.245
315785AD2-033 C
Solar/Wind Harmer
6.277
970685AG2-442 GEN
Solar/Wind Harmer
23.525
971563AH1-280 GEN
Solar/Wind Harmer
3.331
3146926FARMVIL
Solar/Wind Harmer
-0.015
970223AG2-152 GEN
Solar/Wind Harmer
17.186
270018AE2-047 C O1
Solar/Wind Harmer
1.373
319010AE1-072 C
Solar/Wind Helper
4.082
316369SG1_INVT
Solar/Wind Helper
1.668
316381AD1-082 GEN
Solar/Wind Helper
1.76
315662AE1-191 GEN
Solar/Wind Helper
1.75
316280AD1-041 GEN
Solar/Wind Helper
1.093
3138133OCRAN
Solar/Wind Helper
0.193
316404AE1-155 C
Solar/Wind Helper
2.656
3142543TWELFTH
Solar/Wind Helper
0.029
3143226MDLTHAN
Solar/Wind Helper
0.284
315611Z1-036_GEN2
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
316478AD1-087 GEN
Solar/Wind Harmer
4.218
316003AC1-222 GEN
Solar/Wind Harmer
3.188
316222AC1-221 GEN
Solar/Wind Harmer
3.202
316283AC2-100 C
Solar/Wind Harmer
2.967
959311AF2-222 GEN
Solar/Wind Harmer
28.621
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270574AD1-017 GEN2
Solar/Wind Harmer
5.584
943811AF1-049 GEN
Solar/Wind Harmer
3.841
270336AE1-100 GEN
Solar/Wind Harmer
1.564
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.667
3146456SLIGO L269
Solar/Wind Helper
0.359
3142946ENON
Solar/Wind Helper
0.105
316473AC1-191 GEN
Solar/Wind Helper
1.693
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146376EDENTON
Solar/Wind Helper
0.226
963041AG1-153 GEN
50/50
16.962
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
316486AD2-202 GEN
Solar/Wind Harmer
1.235
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
961791AG1-021 GEN
Solar/Wind Harmer
3.331
270455AD2-022 GEN
Solar/Wind Harmer
4.705
971845AH1-439 GEN
Solar/Wind Harmer
8.548
270197AD1-017 GEN1
Solar/Wind Harmer
1.675
313526AB2-022
Solar/Wind Helper
0.505
316059AD1-063 C
Solar/Wind Helper
0.326
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
3151041BRUNSWICKG3
50/50
8.378
3152661PLYWOOD A
50/50
0.662
3151581KERR 1
50/50
0.19
970301AG2-198 GEN
Solar/Wind Harmer
17.344
313527AB2-043 GEN
Solar/Wind Harmer
4.644
970323AG2-213 GEN
Solar/Wind Harmer
13.779
942671AE2-283 GEN
Solar/Wind Harmer
4.893
316049AB1-081 GEN
Solar/Wind Harmer
1.452
3145506HICKORY
Solar/Wind Helper
1.505
3145506HICKORY
Solar/Wind Helper
0.903
3145506HICKORY
Solar/Wind Helper
0.226
316339AD2-160 GEN
Solar/Wind Helper
1.399
316388AE2-253 GEN
Solar/Wind Helper
1.399
3137176SLIGO L2192
Solar/Wind Helper
1.43
3130086AYDLETT
Solar/Wind Helper
1.419
316033AB2-134 GEN
Solar/Wind Helper
1.198
316487AF1-042 GEN
Solar/Wind Helper
0.317
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
3151601KERR 3
50/50
0.532
970533AG2-339 GEN
Solar/Wind Harmer
56.328
970581AG2-369 GEN
Solar/Wind Harmer
35.263
270069AE2-166 C O1
Solar/Wind Harmer
7.989
316236AE1-162_GEN
Solar/Wind Helper
0.499
3143316POE
Solar/Wind Helper
1.405
316382AG1-145 C
Solar/Wind Helper
0.47
316159AE1-175 C
Solar/Wind Helper
0.53
3141873WAN 176
Solar/Wind Helper
0.065
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3145176PASQUOTANK
Solar/Wind Helper
0.197
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
972187AH1-678 GEN
50/50
19.224
970535AG2-341 GEN
50/50
4.581
316118AC1-105 GEN
Solar/Wind Harmer
2.29
964791AG1-342 GEN
Solar/Wind Harmer
6.859
942751AE2-291 GEN
Solar/Wind Harmer
15.08
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
5.194
316240AF1-291 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.493
315666AE1-190 GEN
Solar/Wind Helper
0.437
316435W1029_GEN3
Solar/Wind Helper
1.223
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
966871AG1-558 GEN
Solar/Wind Helper
0.374
971967AH1-528 GEN
Solar/Wind Harmer
123.886
970085AG2-068 GEN
Solar/Wind Harmer
41.004
3144303KENBRDG
Solar/Wind Harmer
-0.022
946301AF1-294 GEN
Solar/Wind Harmer
6.829
270457AD2-023 GEN
Solar/Wind Harmer
2.386
316018AA1-139 ULT2
Solar/Wind Helper
1.569
957601AF2-054 GEN
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.304
316233AE1-074 FULL
Solar/Wind Helper
0.44
315800Z1-036_GEN1
Solar/Wind Helper
1.313
3151591KERR 2
50/50
0.532
3151641KERR 7
50/50
0.532
3151561HALLBR1
50/50
0.362
970919AG2-571 GEN
Solar/Wind Harmer
21.235
3146776BUCKING
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
5.539
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
9.171
316036AC1-147 C
Solar/Wind Helper
0.591
316132AB2-190 GEN1
Solar/Wind Helper
1.935
3141726DUNNSVL
Solar/Wind Helper
1.22
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
316337AD2-073 GEN
Solar/Wind Helper
0.449
970413AG2-270 GEN
50/50
40.656
3144293JTRSVLE
50/50
0.601
971683AH1-343 GEN
Solar/Wind Harmer
13.175
964241AG1-285 GEN
Solar/Wind Harmer
22.056
316123AC1-075 GEN
Solar/Wind Harmer
2.783
942461AE2-259 GEN
Solar/Wind Harmer
3.829
315244AE2-183_ST
50/50
19.154
3151541CLOVER2
50/50
9.264
3151631KERR 6
50/50
0.532
970673AG2-436 GEN
Solar/Wind Harmer
175.868
316238AB2-078_GEN
Solar/Wind Harmer
0.867
316239AB2-077_GEN
Solar/Wind Harmer
0.867
970683AG2-441 GEN
Solar/Wind Harmer
19.131
970681AG2-440 GEN
Solar/Wind Harmer
12.698
970831AG2-522 GEN
Solar/Wind Harmer
9.671
316322AB2-045
Solar/Wind Harmer
0.514
316316AC1-027 C
Solar/Wind Helper
0.607
315697AD1-025 GEN
Solar/Wind Helper
3.957
957831AF2-077 GEN
Solar/Wind Helper
0.465
315839AE2-212 C
Solar/Wind Helper
0.458
3141913WHIT STONE
Solar/Wind Helper
0.323
316468AD1-105 GEN
Solar/Wind Helper
1.26
971629AH1-314 GEN
50/50
17.894
316131AB2-060 GEN
Solar/Wind Harmer
3.07
3147123OTTER R
Solar/Wind Harmer
-0.01
270030AE2-140 GEN
Solar/Wind Harmer
19.766
316359AB2-059 GEN
Solar/Wind Harmer
1.815
3142053HEARTS
Solar/Wind Harmer
0.159
316375AC2-012 GEN
Solar/Wind Helper
1.018
3145336SMITFLD
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.359
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.273
315975AC1-164 GENB
Solar/Wind Helper
0.119
3142416OLDCHRC
Solar/Wind Helper
0.758
3142416OLDCHRC
Solar/Wind Helper
0.29
315243AE2-183_GT3
50/50
11.03
3151051BRUNSWICKS1
50/50
17.394
971451AH1-221 GEN
50/50
25.443
3151531CLOVER1
50/50
9.336
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.474
941031AE2-094 GEN
Solar/Wind Harmer
157.057
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316034AC1-036 C
Solar/Wind Harmer
0.509
971065AG2-659 GEN
Solar/Wind Harmer
11.235
316129AC1-054 GEN
Solar/Wind Harmer
1.845
270016AE1-250 BESS
Solar/Wind Harmer
2.837
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
316072AD1-144
Solar/Wind Helper
0.405
315671AE2-027_GEN
Solar/Wind Helper
2.696
964211AG1-282 GEN
Solar/Wind Helper
0.411
3143526WINTERP
Solar/Wind Helper
1.497
315242AE2-183_GT2
50/50
11.03
315241AE2-183_GT1
50/50
11.001
972185AH1-677 GEN
50/50
39.871
970909AG2-566 GEN
50/50
3.293
3144293JTRSVLE
50/50
0.601
970099AG2-077 GEN
Solar/Wind Harmer
66.433
315687AD1-152 GEN
Solar/Wind Harmer
5.303
316248AF1-058 C
Solar/Wind Harmer
1.041
962561AG1-105 GEN
Solar/Wind Harmer
17.76
316237AB2-079_GEN
Solar/Wind Harmer
0.867
270013AE1-250 PV
Solar/Wind Harmer
2.837
316263AC1-034 GEN
Solar/Wind Harmer
6.326
316185AD1-033 GEN
Solar/Wind Helper
1.802
316312AB1-027
Solar/Wind Helper
0.557
3143526WINTERP
Solar/Wind Helper
1.497
3144356SAPONY
Solar/Wind Helper
0.491
316315AB2-025 C
Solar/Wind Helper
0.418
970933AG2-581 GEN
Solar/Wind Harmer
58.871
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
958211AF2-115 GEN
Solar/Wind Harmer
4.164
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316294AC1-161 GEN
Solar/Wind Helper
7.794
316349AD2-085 GEN
Solar/Wind Helper
1.524
3151031BRUNSWICKG2
50/50
8.378
944011AF1-069 GEN
Solar/Wind Harmer
49.211
3146776BUCKING
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.26
3142956BIRDNECK
Solar/Wind Helper
0.258
3144536CHRHLND
Solar/Wind Helper
0.058
316305AF2-043 C
Solar/Wind Helper
0.474
316320Y1-086
Solar/Wind Helper
0.149
3146516WINFALL
Solar/Wind Helper
0.296
316223AC1-118
Solar/Wind Helper
0.438
3146386ELIZ CT
Solar/Wind Helper
0.331
3142946ENON
Solar/Wind Helper
0.031
315976AC1-164 GENA
Solar/Wind Helper
4.039
316169AC1-164_GENC
Solar/Wind Helper
3.489
316431W1029_GEN1
Solar/Wind Helper
1.223
316433W1029_GEN2
Solar/Wind Helper
1.223
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.606
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.287
LAGNLTFEXP_LAGN->PJM
CLTF
14.661
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.209
TVALTFEXP_TVA->PJM
CLTF
7.311
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.147
CPLELTFEXP_CPLE->PJM
CLTF
19.725
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.242
MECLTFEXP_MEC->PJM
CLTF
7.373
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.679
WECLTFEXP_WEC->PJM
CLTF
1.402
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.73 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5581.87
MW Contribution:
17.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970917AG2-570 GEN
Solar/Wind Harmer
166.334
970257AG2-171 GEN
Solar/Wind Harmer
10.19
971775AH1-396 GEN
Solar/Wind Harmer
1.917
3146926FARMVIL
Solar/Wind Harmer
-0.014
3151021BRUNSWICKG1
50/50
8.307
970087AG2-069 GEN
Solar/Wind Harmer
60.986
957481AF2-042 GEN
Solar/Wind Harmer
164.583
315693AD1-088 GEN
Solar/Wind Harmer
24.018
315785AD2-033 C
Solar/Wind Harmer
6.188
316478AD1-087 GEN
Solar/Wind Harmer
4.179
316003AC1-222 GEN
Solar/Wind Harmer
3.156
316222AC1-221 GEN
Solar/Wind Harmer
3.175
316283AC2-100 C
Solar/Wind Harmer
2.943
959311AF2-222 GEN
Solar/Wind Harmer
28.221
3147133PAMPLIN
Solar/Wind Harmer
-0.081
270574AD1-017 GEN2
Solar/Wind Harmer
5.536
943811AF1-049 GEN
Solar/Wind Harmer
3.808
270336AE1-100 GEN
Solar/Wind Harmer
1.55
3145336SMITFLD
Solar/Wind Helper
0.133
316017AA1-139 ULT1
Solar/Wind Helper
1.432
3142946ENON
Solar/Wind Helper
0.104
3146456SLIGO L269
Solar/Wind Helper
0.308
316473AC1-191 GEN
Solar/Wind Helper
1.701
966881AG1-559 GEN
Solar/Wind Helper
0.328
963041AG1-153 GEN
50/50
16.818
3151611KERR 4
50/50
0.526
3151621KERR 5
50/50
0.526
316486AD2-202 GEN
Solar/Wind Harmer
1.224
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
961791AG1-021 GEN
Solar/Wind Harmer
3.286
270455AD2-022 GEN
Solar/Wind Harmer
4.668
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
971845AH1-439 GEN
Solar/Wind Harmer
8.41
316059AD1-063 C
Solar/Wind Helper
0.313
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.122
313526AB2-022
Solar/Wind Helper
0.431
970685AG2-442 GEN
Solar/Wind Harmer
23.201
971563AH1-280 GEN
Solar/Wind Harmer
3.286
3146926FARMVIL
Solar/Wind Harmer
-0.014
970223AG2-152 GEN
Solar/Wind Harmer
17.044
270018AE2-047 C O1
Solar/Wind Harmer
1.362
316381AD1-082 GEN
Solar/Wind Helper
1.75
316369SG1_INVT
Solar/Wind Helper
1.594
3142543TWELFTH
Solar/Wind Helper
0.03
315662AE1-191 GEN
Solar/Wind Helper
1.677
316280AD1-041 GEN
Solar/Wind Helper
1.048
3138133OCRAN
Solar/Wind Helper
0.185
319010AE1-072 C
Solar/Wind Helper
3.502
3151041BRUNSWICKG3
50/50
8.307
3152661PLYWOOD A
50/50
0.655
3151581KERR 1
50/50
0.188
970301AG2-198 GEN
Solar/Wind Harmer
17.157
313527AB2-043 GEN
Solar/Wind Harmer
4.577
970323AG2-213 GEN
Solar/Wind Harmer
13.586
942671AE2-283 GEN
Solar/Wind Harmer
4.846
316049AB1-081 GEN
Solar/Wind Harmer
1.446
316033AB2-134 GEN
Solar/Wind Helper
1.145
3145506HICKORY
Solar/Wind Helper
1.296
3145506HICKORY
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.194
316339AD2-160 GEN
Solar/Wind Helper
1.203
316388AE2-253 GEN
Solar/Wind Helper
1.203
3137176SLIGO L2192
Solar/Wind Helper
1.227
3130086AYDLETT
Solar/Wind Helper
1.217
316487AF1-042 GEN
Solar/Wind Helper
0.305
3146626S HERTFORD
Solar/Wind Helper
0.235
3146626S HERTFORD
Solar/Wind Helper
0.235
3151601KERR 3
50/50
0.526
970533AG2-339 GEN
Solar/Wind Harmer
55.849
970581AG2-369 GEN
Solar/Wind Harmer
34.965
270069AE2-166 C O1
Solar/Wind Harmer
7.921
3143316POE
Solar/Wind Helper
1.568
316236AE1-162_GEN
Solar/Wind Helper
0.448
316382AG1-145 C
Solar/Wind Helper
0.442
316159AE1-175 C
Solar/Wind Helper
0.498
3141873WAN 176
Solar/Wind Helper
0.062
3143873LANEXA
Solar/Wind Helper
0.186
3138133OCRAN
Solar/Wind Helper
0.092
3146486SUNBURY
Solar/Wind Helper
0.273
3146486SUNBURY
Solar/Wind Helper
0.273
3145176PASQUOTANK
Solar/Wind Helper
0.168
316404AE1-155 C
Solar/Wind Helper
2.553
3143226MDLTHAN
Solar/Wind Helper
0.289
972187AH1-678 GEN
50/50
19.06
970535AG2-341 GEN
50/50
4.523
316118AC1-105 GEN
Solar/Wind Harmer
2.266
964791AG1-342 GEN
Solar/Wind Harmer
6.78
942751AE2-291 GEN
Solar/Wind Harmer
14.933
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
5.168
316240AF1-291 C
Solar/Wind Helper
0.472
316156AD2-030 GEN
Solar/Wind Helper
0.471
315666AE1-190 GEN
Solar/Wind Helper
0.419
966871AG1-558 GEN
Solar/Wind Helper
0.375
316435W1029_GEN3
Solar/Wind Helper
1.035
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
971967AH1-528 GEN
Solar/Wind Harmer
122.813
970085AG2-068 GEN
Solar/Wind Harmer
40.657
3144303KENBRDG
Solar/Wind Harmer
-0.022
946301AF1-294 GEN
Solar/Wind Harmer
6.735
270457AD2-023 GEN
Solar/Wind Harmer
2.367
316018AA1-139 ULT2
Solar/Wind Helper
1.348
957601AF2-054 GEN
Solar/Wind Helper
0.417
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.445
3151591KERR 2
50/50
0.526
3151641KERR 7
50/50
0.526
3151561HALLBR1
50/50
0.359
970919AG2-571 GEN
Solar/Wind Harmer
21.055
3146776BUCKING
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
5.486
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
8.532
316036AC1-147 C
Solar/Wind Helper
0.512
316132AB2-190 GEN1
Solar/Wind Helper
1.896
3141726DUNNSVL
Solar/Wind Helper
1.177
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.811
3146516WINFALL
Solar/Wind Helper
0.25
315244AE2-183_ST
50/50
18.991
3151541CLOVER2
50/50
9.18
3151631KERR 6
50/50
0.526
970673AG2-436 GEN
Solar/Wind Harmer
174.37
316238AB2-078_GEN
Solar/Wind Harmer
0.854
316239AB2-077_GEN
Solar/Wind Harmer
0.854
970683AG2-441 GEN
Solar/Wind Harmer
18.866
970681AG2-440 GEN
Solar/Wind Harmer
12.522
970831AG2-522 GEN
Solar/Wind Harmer
9.555
316322AB2-045
Solar/Wind Harmer
0.505
315839AE2-212 C
Solar/Wind Helper
0.498
316316AC1-027 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
3.782
957831AF2-077 GEN
Solar/Wind Helper
0.436
3141913WHIT STONE
Solar/Wind Helper
0.309
316468AD1-105 GEN
Solar/Wind Helper
1.263
971629AH1-314 GEN
50/50
17.75
316131AB2-060 GEN
Solar/Wind Harmer
3.026
3147123OTTER R
Solar/Wind Harmer
-0.01
270030AE2-140 GEN
Solar/Wind Harmer
19.599
316359AB2-059 GEN
Solar/Wind Harmer
1.807
3142053HEARTS
Solar/Wind Harmer
0.158
316375AC2-012 GEN
Solar/Wind Helper
0.883
3145336SMITFLD
Solar/Wind Helper
1.329
3142433PROV 92
Solar/Wind Helper
1.252
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
315975AC1-164 GENB
Solar/Wind Helper
0.116
3142416OLDCHRC
Solar/Wind Helper
0.75
3142416OLDCHRC
Solar/Wind Helper
0.287
315243AE2-183_GT3
50/50
10.936
3151051BRUNSWICKS1
50/50
17.246
971451AH1-221 GEN
50/50
25.226
3151531CLOVER1
50/50
9.25
3144293JTRSVLE
50/50
0.593
3144293JTRSVLE
50/50
0.468
941031AE2-094 GEN
Solar/Wind Harmer
155.721
970401AG2-262 GEN
Solar/Wind Harmer
2.072
316034AC1-036 C
Solar/Wind Harmer
0.502
971065AG2-659 GEN
Solar/Wind Harmer
11.105
316129AC1-054 GEN
Solar/Wind Harmer
1.824
270016AE1-250 BESS
Solar/Wind Harmer
2.814
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
315671AE2-027_GEN
Solar/Wind Helper
2.884
316072AD1-144
Solar/Wind Helper
0.351
964211AG1-282 GEN
Solar/Wind Helper
0.397
3143526WINTERP
Solar/Wind Helper
1.516
315242AE2-183_GT2
50/50
10.936
315241AE2-183_GT1
50/50
10.907
972185AH1-677 GEN
50/50
39.531
970909AG2-566 GEN
50/50
3.258
3144293JTRSVLE
50/50
0.593
970099AG2-077 GEN
Solar/Wind Harmer
65.833
315687AD1-152 GEN
Solar/Wind Harmer
5.255
316248AF1-058 C
Solar/Wind Harmer
1.031
962561AG1-105 GEN
Solar/Wind Harmer
17.549
316237AB2-079_GEN
Solar/Wind Harmer
0.854
270013AE1-250 PV
Solar/Wind Harmer
2.814
316263AC1-034 GEN
Solar/Wind Harmer
6.299
316185AD1-033 GEN
Solar/Wind Helper
1.553
3144356SAPONY
Solar/Wind Helper
0.58
316315AB2-025 C
Solar/Wind Helper
0.494
3143526WINTERP
Solar/Wind Helper
1.516
316312AB1-027
Solar/Wind Helper
0.551
3151031BRUNSWICKG2
50/50
8.307
944011AF1-069 GEN
Solar/Wind Harmer
48.793
3146776BUCKING
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.233
3144536CHRHLND
Solar/Wind Helper
0.05
3142956BIRDNECK
Solar/Wind Helper
0.223
316305AF2-043 C
Solar/Wind Helper
0.402
316320Y1-086
Solar/Wind Helper
0.127
316223AC1-118
Solar/Wind Helper
0.424
3146516WINFALL
Solar/Wind Helper
0.25
970933AG2-581 GEN
Solar/Wind Harmer
58.356
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
958211AF2-115 GEN
Solar/Wind Harmer
4.107
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316294AC1-161 GEN
Solar/Wind Helper
7.251
3142946ENON
Solar/Wind Helper
0.031
316349AD2-085 GEN
Solar/Wind Helper
1.397
315976AC1-164 GENA
Solar/Wind Helper
3.933
316169AC1-164_GENC
Solar/Wind Helper
3.397
3146386ELIZ CT
Solar/Wind Helper
0.282
316431W1029_GEN1
Solar/Wind Helper
1.035
316433W1029_GEN2
Solar/Wind Helper
1.035
316217AC1-145 GEN
Solar/Wind Harmer
2.372
316197AC1-042 GEN
Solar/Wind Harmer
1.798
3144873MCLAUGH
Solar/Wind Helper
0.008
316458AB2-190 GEN2
Solar/Wind Helper
1.896
316246AF1-032 C
Solar/Wind Helper
0.342
3141906WESTMOR
Solar/Wind Helper
0.111
316321Z2-027
Solar/Wind Helper
0.414
3146626S HERTFORD
Solar/Wind Helper
0.235
970413AG2-270 GEN
50/50
40.285
3144293JTRSVLE
50/50
0.593
971683AH1-343 GEN
Solar/Wind Harmer
13.046
964241AG1-285 GEN
Solar/Wind Harmer
21.742
316123AC1-075 GEN
Solar/Wind Harmer
2.756
942461AE2-259 GEN
Solar/Wind Harmer
3.778
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.582
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
LAGNLTFEXP_LAGN->PJM
CLTF
14.534
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.89
TVALTFEXP_TVA->PJM
CLTF
7.248
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.924
MECLTFEXP_MEC->PJM
CLTF
7.297
CPLELTFEXP_CPLE->PJM
CLTF
19.597
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.518
SIGELTFEXP_SIGE->PJM
CLTF
0.219
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.65
WECLTFEXP_WEC->PJM
CLTF
1.386
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 591_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 591_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.31 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4123.45
MW Contribution:
11.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316283AC2-100 C
Solar/Wind Harmer
0.276
316222AC1-221 GEN
Solar/Wind Harmer
0.57
3145336SMITFLD
Solar/Wind Helper
0.1
316017AA1-139 ULT1
Solar/Wind Helper
1.096
3146456SLIGO L269
Solar/Wind Helper
0.236
3142946ENON
Solar/Wind Helper
0.075
3151041BRUNSWICKG3
50/50
10.302
3145506HICKORY
Solar/Wind Helper
0.99
3145506HICKORY
Solar/Wind Helper
0.594
3145506HICKORY
Solar/Wind Helper
0.148
316033AB2-134 GEN
Solar/Wind Helper
0.835
316339AD2-160 GEN
Solar/Wind Helper
0.92
316388AE2-253 GEN
Solar/Wind Helper
0.92
3137176SLIGO L2192
Solar/Wind Helper
0.94
3130086AYDLETT
Solar/Wind Helper
0.933
970533AG2-339 GEN
Solar/Wind Harmer
65.672
970581AG2-369 GEN
Solar/Wind Harmer
32.335
3143316POE
Solar/Wind Helper
1.045
316236AE1-162_GEN
Solar/Wind Helper
0.335
316382AG1-145 C
Solar/Wind Helper
0.322
316159AE1-175 C
Solar/Wind Helper
0.363
3141873WAN 176
Solar/Wind Helper
0.045
3143873LANEXA
Solar/Wind Helper
0.135
3138133OCRAN
Solar/Wind Helper
0.068
315244AE2-183_ST
50/50
23.137
970673AG2-436 GEN
Solar/Wind Harmer
105.198
316316AC1-027 C
Solar/Wind Helper
0.4
315839AE2-212 C
Solar/Wind Helper
0.339
315697AD1-025 GEN
Solar/Wind Helper
2.76
957831AF2-077 GEN
Solar/Wind Helper
0.319
3141913WHIT STONE
Solar/Wind Helper
0.225
315243AE2-183_GT3
50/50
13.323
3151051BRUNSWICKS1
50/50
21.387
971451AH1-221 GEN
50/50
31.284
941031AE2-094 GEN
Solar/Wind Harmer
160.084
315671AE2-027_GEN
Solar/Wind Helper
1.989
316072AD1-144
Solar/Wind Helper
0.27
963041AG1-153 GEN
50/50
20.856
316059AD1-063 C
Solar/Wind Helper
0.228
3141783LANCAST
Solar/Wind Helper
0.134
3141783LANCAST
Solar/Wind Helper
0.09
971629AH1-314 GEN
50/50
11.743
316375AC2-012 GEN
Solar/Wind Helper
0.672
3145336SMITFLD
Solar/Wind Helper
0.995
3146456SLIGO L269
Solar/Wind Helper
0.236
3142433PROV 92
Solar/Wind Helper
0.907
3141766HARMONY
Solar/Wind Helper
0.045
315242AE2-183_GT2
50/50
13.323
315241AE2-183_GT1
50/50
13.288
972185AH1-677 GEN
50/50
48.161
316185AD1-033 GEN
Solar/Wind Helper
1.186
970919AG2-571 GEN
Solar/Wind Harmer
25.766
315773AC2-141 GEN
Solar/Wind Helper
5.99
316036AC1-147 C
Solar/Wind Helper
0.39
316132AB2-190 GEN1
Solar/Wind Helper
1.37
970917AG2-570 GEN
Solar/Wind Harmer
64.414
3144873MCLAUGH
Solar/Wind Helper
0.006
316458AB2-190 GEN2
Solar/Wind Helper
1.37
316246AF1-032 C
Solar/Wind Helper
0.267
3151021BRUNSWICKG1
50/50
10.302
970087AG2-069 GEN
Solar/Wind Harmer
56.398
316381AD1-082 GEN
Solar/Wind Helper
1.255
316369SG1_INVT
Solar/Wind Helper
1.164
319010AE1-072 C
Solar/Wind Helper
2.684
315662AE1-191 GEN
Solar/Wind Helper
1.224
316280AD1-041 GEN
Solar/Wind Helper
0.765
3142543TWELFTH
Solar/Wind Helper
0.022
3138133OCRAN
Solar/Wind Helper
0.135
316294AC1-161 GEN
Solar/Wind Helper
5.09
316349AD2-085 GEN
Solar/Wind Helper
1.055
3142946ENON
Solar/Wind Helper
0.023
3151031BRUNSWICKG2
50/50
10.302
944011AF1-069 GEN
Solar/Wind Harmer
52.305
3144536CHRHLND
Solar/Wind Helper
0.038
3142956BIRDNECK
Solar/Wind Helper
0.17
316305AF2-043 C
Solar/Wind Helper
0.314
972187AH1-678 GEN
50/50
23.637
316240AF1-291 C
Solar/Wind Helper
0.328
316156AD2-030 GEN
Solar/Wind Helper
0.344
315666AE1-190 GEN
Solar/Wind Helper
0.306
970085AG2-068 GEN
Solar/Wind Harmer
37.599
316018AA1-139 ULT2
Solar/Wind Helper
1.032
957601AF2-054 GEN
Solar/Wind Helper
0.305
LAGNLTFEXP_LAGN->PJM
CLTF
11.977
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.441
TVALTFEXP_TVA->PJM
CLTF
5.94
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.271
CPLELTFEXP_CPLE->PJM
CLTF
16.709
CBM West 2LTFEXP_CBM-W2->PJM
CBM
62.589
MECLTFEXP_MEC->PJM
CLTF
5.717
SIGELTFEXP_SIGE->PJM
CLTF
0.169
NYPJM->LTFIMP_NY
CLTF
1.873
LGEELTFEXP_LGEE->PJM
CLTF
2.014
WECLTFEXP_WEC->PJM
CLTF
1.061

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.16 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:663.9
MW Contribution:
5.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
1.086
316222AC1-221 GEN
Solar/Wind Harmer
0.443
316283AC2-100 C
Solar/Wind Harmer
0.206
3147133PAMPLIN
Solar/Wind Helper
1.064
970535AG2-341 GEN
50/50
1.993
316118AC1-105 GEN
Solar/Wind Harmer
0.373
964791AG1-342 GEN
Solar/Wind Harmer
2.429
942751AE2-291 GEN
Solar/Wind Harmer
5.335
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
316313AB2-026
Solar/Wind Helper
0.242
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.319
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970301AG2-198 GEN
Solar/Wind Harmer
25.388
3151601KERR 3
50/50
0.297
316405AF2-144 C
Solar/Wind Helper
0.182
3151541CLOVER2
50/50
6.689
3151631KERR 6
50/50
0.297
970831AG2-522 GEN
Solar/Wind Harmer
4.544
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
3151531CLOVER1
50/50
6.741
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.07
316129AC1-054 GEN
Solar/Wind Harmer
0.424
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
3146776BUCKING
Solar/Wind Helper
0.217
971629AH1-314 GEN
50/50
5.005
316131AB2-060 GEN
Solar/Wind Harmer
0.206
970909AG2-566 GEN
50/50
6.347
970099AG2-077 GEN
Solar/Wind Harmer
36.297
962561AG1-105 GEN
Solar/Wind Harmer
5.688
3146776BUCKING
Solar/Wind Helper
0.196
315693AD1-088 GEN
Solar/Wind Harmer
18.249
957481AF2-042 GEN
Solar/Wind Harmer
90.743
3146926FARMVIL
Solar/Wind Helper
0.441
3146926FARMVIL
Solar/Wind Helper
0.441
970933AG2-581 GEN
Solar/Wind Harmer
27.858
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
270494AE1-108_GEN
Solar/Wind Helper
2.774
971967AH1-528 GEN
Solar/Wind Harmer
55.714
970413AG2-270 GEN
50/50
29.357
971683AH1-343 GEN
Solar/Wind Harmer
5.14
316123AC1-075 GEN
Solar/Wind Harmer
0.149
942461AE2-259 GEN
Solar/Wind Helper
3.543
315821AE2-092 GEN
Solar/Wind Helper
1.922
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.59 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:649.19
MW Contribution:
5.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
1.086
316222AC1-221 GEN
Solar/Wind Harmer
0.443
316283AC2-100 C
Solar/Wind Harmer
0.206
3147133PAMPLIN
Solar/Wind Helper
1.064
970535AG2-341 GEN
50/50
1.993
316118AC1-105 GEN
Solar/Wind Harmer
0.373
964791AG1-342 GEN
Solar/Wind Harmer
2.429
942751AE2-291 GEN
Solar/Wind Harmer
5.335
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
316313AB2-026
Solar/Wind Helper
0.242
3151611KERR 4
50/50
0.297
3151621KERR 5
50/50
0.297
316486AD2-202 GEN
Solar/Wind Harmer
0.319
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
3138266HYDRAULIC
Solar/Wind Helper
0.006
3152661PLYWOOD A
50/50
0.342
3151581KERR 1
50/50
0.106
970301AG2-198 GEN
Solar/Wind Harmer
25.388
3151601KERR 3
50/50
0.297
316405AF2-144 C
Solar/Wind Helper
0.182
3151541CLOVER2
50/50
6.689
3151631KERR 6
50/50
0.297
970831AG2-522 GEN
Solar/Wind Harmer
4.544
316322AB2-045
Solar/Wind Helper
0.608
316258AE1-075 C
Solar/Wind Helper
0.218
3151531CLOVER1
50/50
6.741
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.07
316129AC1-054 GEN
Solar/Wind Harmer
0.424
3151591KERR 2
50/50
0.297
3151641KERR 7
50/50
0.297
3138266HYDRAULIC
Solar/Wind Helper
0.004
971629AH1-314 GEN
50/50
5.005
316131AB2-060 GEN
Solar/Wind Harmer
0.206
970909AG2-566 GEN
50/50
6.347
970099AG2-077 GEN
Solar/Wind Harmer
36.297
962561AG1-105 GEN
Solar/Wind Harmer
5.688
3146776BUCKING
Solar/Wind Helper
0.217
315693AD1-088 GEN
Solar/Wind Harmer
18.249
957481AF2-042 GEN
Solar/Wind Harmer
90.743
3146926FARMVIL
Solar/Wind Helper
0.441
3146926FARMVIL
Solar/Wind Helper
0.441
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
3146776BUCKING
Solar/Wind Helper
0.196
270494AE1-108_GEN
Solar/Wind Helper
2.774
970413AG2-270 GEN
50/50
29.357
971683AH1-343 GEN
Solar/Wind Harmer
5.14
316123AC1-075 GEN
Solar/Wind Harmer
0.149
942461AE2-259 GEN
Solar/Wind Helper
3.543
315821AE2-092 GEN
Solar/Wind Helper
1.922
LAGNLTFEXP_LAGN->PJM
CLTF
2.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.684
TVALTFEXP_TVA->PJM
CLTF
1.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.467
MECLTFEXP_MEC->PJM
CLTF
1.258
CPLELTFEXP_CPLE->PJM
CLTF
4.127
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.752
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.385
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.2 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4933.15
MW Contribution:
17.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
1.514
316222AC1-221 GEN
Solar/Wind Harmer
1.167
316283AC2-100 C
Solar/Wind Harmer
0.55
959311AF2-222 GEN
Solar/Wind Harmer
21.675
3147133PAMPLIN
Solar/Wind Harmer
0.736
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
971623AH1-311 GEN
Solar/Wind Harmer
0.235
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
3146456SLIGO L269
Solar/Wind Helper
0.357
3142946ENON
Solar/Wind Helper
0.108
316473AC1-191 GEN
Solar/Wind Helper
1.733
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
972187AH1-678 GEN
50/50
19.356
970535AG2-341 GEN
50/50
4.57
316118AC1-105 GEN
Solar/Wind Harmer
0.762
964791AG1-342 GEN
Solar/Wind Harmer
5.492
942751AE2-291 GEN
Solar/Wind Harmer
11.487
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
961601AG1-000A GEN
Solar/Wind Harmer
2.039
316240AF1-291 C
Solar/Wind Helper
0.475
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
316435W1029_GEN3
Solar/Wind Helper
1.221
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
966871AG1-558 GEN
Solar/Wind Helper
0.382
963041AG1-153 GEN
50/50
17.078
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
316486AD2-202 GEN
Solar/Wind Harmer
0.444
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
961791AG1-021 GEN
Solar/Wind Harmer
2.278
971845AH1-439 GEN
Solar/Wind Harmer
6.517
270197AD1-017 GEN1
Solar/Wind Harmer
0.942
313526AB2-022
Solar/Wind Helper
0.503
316059AD1-063 C
Solar/Wind Helper
0.33
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3151041BRUNSWICKG3
50/50
8.436
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970301AG2-198 GEN
Solar/Wind Harmer
13.237
970323AG2-213 GEN
Solar/Wind Harmer
10.454
942671AE2-283 GEN
Solar/Wind Harmer
3.281
316049AB1-081 GEN
Solar/Wind Harmer
0.667
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316487AF1-042 GEN
Solar/Wind Helper
0.321
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
3151601KERR 3
50/50
0.53
970581AG2-369 GEN
Solar/Wind Harmer
26.958
270069AE2-166 C O1
Solar/Wind Harmer
5.589
3143316POE
Solar/Wind Helper
1.548
316236AE1-162_GEN
Solar/Wind Helper
0.501
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
3141873WAN 176
Solar/Wind Helper
0.066
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.288
3151541CLOVER2
50/50
9.313
3151631KERR 6
50/50
0.53
970673AG2-436 GEN
Solar/Wind Harmer
89.687
970683AG2-441 GEN
Solar/Wind Harmer
14.525
970681AG2-440 GEN
Solar/Wind Harmer
9.64
970831AG2-522 GEN
Solar/Wind Harmer
7.24
316316AC1-027 C
Solar/Wind Helper
0.603
315839AE2-212 C
Solar/Wind Helper
0.496
315697AD1-025 GEN
Solar/Wind Helper
4.048
957831AF2-077 GEN
Solar/Wind Helper
0.468
3141913WHIT STONE
Solar/Wind Helper
0.326
316468AD1-105 GEN
Solar/Wind Helper
1.285
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
970401AG2-262 GEN
Solar/Wind Harmer
1.678
316034AC1-036 C
Solar/Wind Harmer
0.016
971065AG2-659 GEN
Solar/Wind Harmer
8.454
316129AC1-054 GEN
Solar/Wind Harmer
0.693
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
315671AE2-027_GEN
Solar/Wind Helper
2.891
316072AD1-144
Solar/Wind Helper
0.405
964211AG1-282 GEN
Solar/Wind Helper
0.416
3143526WINTERP
Solar/Wind Helper
1.518
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
970909AG2-566 GEN
50/50
3.309
3144293JTRSVLE
50/50
0.601
970099AG2-077 GEN
Solar/Wind Harmer
50.746
962561AG1-105 GEN
Solar/Wind Harmer
13.495
316263AC1-034 GEN
Solar/Wind Harmer
4.456
316185AD1-033 GEN
Solar/Wind Helper
1.79
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316312AB1-027
Solar/Wind Helper
0.567
3143526WINTERP
Solar/Wind Helper
1.518
3151591KERR 2
50/50
0.53
3151641KERR 7
50/50
0.53
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
3146776BUCKING
Solar/Wind Harmer
0.055
941801AE2-185 GEN
Solar/Wind Harmer
4.219
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.094
315773AC2-141 GEN
Solar/Wind Helper
9.062
316036AC1-147 C
Solar/Wind Helper
0.587
316132AB2-190 GEN1
Solar/Wind Helper
1.996
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
971629AH1-314 GEN
50/50
17.942
316131AB2-060 GEN
Solar/Wind Harmer
0.788
3147123OTTER R
Solar/Wind Harmer
0.088
270030AE2-140 GEN
Solar/Wind Harmer
13.827
316359AB2-059 GEN
Solar/Wind Harmer
0.417
3142053HEARTS
Solar/Wind Harmer
0.206
316375AC2-012 GEN
Solar/Wind Helper
1.012
3145336SMITFLD
Solar/Wind Helper
1.485
3146456SLIGO L269
Solar/Wind Helper
0.357
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3151031BRUNSWICKG2
50/50
8.436
3146776BUCKING
Solar/Wind Harmer
0.049
3145543BTLEBRO
Solar/Wind Harmer
0.118
3145543BTLEBRO
Solar/Wind Harmer
0.118
961601AG1-000A GEN
Solar/Wind Harmer
8.154
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
316305AF2-043 C
Solar/Wind Helper
0.472
316320Y1-086
Solar/Wind Helper
0.148
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
3151021BRUNSWICKG1
50/50
8.436
970087AG2-069 GEN
Solar/Wind Harmer
47.021
957481AF2-042 GEN
Solar/Wind Harmer
126.864
315693AD1-088 GEN
Solar/Wind Harmer
20.828
315785AD2-033 C
Solar/Wind Harmer
1.994
970685AG2-442 GEN
Solar/Wind Harmer
17.866
971563AH1-280 GEN
Solar/Wind Harmer
2.531
3146926FARMVIL
Solar/Wind Harmer
0.131
970223AG2-152 GEN
Solar/Wind Harmer
12.084
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
970917AG2-570 GEN
Solar/Wind Harmer
53.44
970257AG2-171 GEN
Solar/Wind Harmer
7.84
971775AH1-396 GEN
Solar/Wind Harmer
0.392
3146926FARMVIL
Solar/Wind Harmer
0.131
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316321Z2-027
Solar/Wind Helper
0.485
3141906WESTMOR
Solar/Wind Helper
0.116
3146626S HERTFORD
Solar/Wind Helper
0.279
970933AG2-581 GEN
Solar/Wind Harmer
44.999
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
958211AF2-115 GEN
Solar/Wind Harmer
2.847
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.188
316294AC1-161 GEN
Solar/Wind Helper
7.701
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
971967AH1-528 GEN
Solar/Wind Harmer
94.459
970085AG2-068 GEN
Solar/Wind Harmer
31.347
3144303KENBRDG
Solar/Wind Harmer
0.196
946301AF1-294 GEN
Solar/Wind Harmer
4.682
316018AA1-139 ULT2
Solar/Wind Helper
1.56
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
315800Z1-036_GEN1
Solar/Wind Helper
1.317
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
971683AH1-343 GEN
Solar/Wind Harmer
10.037
964241AG1-285 GEN
Solar/Wind Harmer
16.717
316123AC1-075 GEN
Solar/Wind Harmer
0.308
942461AE2-259 GEN
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.026
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
TVALTFEXP_TVA->PJM
CLTF
7.333
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
MECLTFEXP_MEC->PJM
CLTF
7.397
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.55 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5423.36
MW Contribution:
17.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316478AD1-087 GEN
Solar/Wind Harmer
4.24
316003AC1-222 GEN
Solar/Wind Harmer
3.197
316222AC1-221 GEN
Solar/Wind Harmer
3.212
316283AC2-100 C
Solar/Wind Harmer
2.976
959311AF2-222 GEN
Solar/Wind Harmer
28.596
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270574AD1-017 GEN2
Solar/Wind Harmer
5.599
943811AF1-049 GEN
Solar/Wind Harmer
3.851
270336AE1-100 GEN
Solar/Wind Harmer
1.568
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.657
963041AG1-153 GEN
50/50
17.078
3151611KERR 4
50/50
0.53
3151621KERR 5
50/50
0.53
316486AD2-202 GEN
Solar/Wind Harmer
1.242
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.022
961791AG1-021 GEN
Solar/Wind Harmer
3.332
3151601KERR 3
50/50
0.53
970581AG2-369 GEN
Solar/Wind Harmer
35.495
270069AE2-166 C O1
Solar/Wind Harmer
8.011
3143316POE
Solar/Wind Helper
1.548
316236AE1-162_GEN
Solar/Wind Helper
0.501
316382AG1-145 C
Solar/Wind Helper
0.472
316159AE1-175 C
Solar/Wind Helper
0.532
3141873WAN 176
Solar/Wind Helper
0.066
3143873LANEXA
Solar/Wind Helper
0.195
3138133OCRAN
Solar/Wind Helper
0.098
3146486SUNBURY
Solar/Wind Helper
0.321
3146486SUNBURY
Solar/Wind Helper
0.321
3145176PASQUOTANK
Solar/Wind Helper
0.197
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151021BRUNSWICKG1
50/50
8.436
970087AG2-069 GEN
Solar/Wind Harmer
61.91
957481AF2-042 GEN
Solar/Wind Harmer
167.038
315693AD1-088 GEN
Solar/Wind Harmer
24.377
315785AD2-033 C
Solar/Wind Harmer
6.268
970685AG2-442 GEN
Solar/Wind Harmer
23.524
971563AH1-280 GEN
Solar/Wind Harmer
3.332
3146926FARMVIL
Solar/Wind Harmer
-0.015
970223AG2-152 GEN
Solar/Wind Harmer
17.233
3151591KERR 2
50/50
0.53
315244AE2-183_ST
50/50
19.288
3151541CLOVER2
50/50
9.313
3151631KERR 6
50/50
0.53
970673AG2-436 GEN
Solar/Wind Harmer
177.133
316238AB2-078_GEN
Solar/Wind Harmer
0.865
316239AB2-077_GEN
Solar/Wind Harmer
0.865
970683AG2-441 GEN
Solar/Wind Harmer
19.124
970681AG2-440 GEN
Solar/Wind Harmer
12.693
970831AG2-522 GEN
Solar/Wind Harmer
9.533
316322AB2-045
Solar/Wind Harmer
0.516
316316AC1-027 C
Solar/Wind Helper
0.603
315839AE2-212 C
Solar/Wind Helper
0.496
315697AD1-025 GEN
Solar/Wind Helper
4.048
957831AF2-077 GEN
Solar/Wind Helper
0.468
3141913WHIT STONE
Solar/Wind Helper
0.326
316468AD1-105 GEN
Solar/Wind Helper
1.285
270455AD2-022 GEN
Solar/Wind Harmer
4.718
971845AH1-439 GEN
Solar/Wind Harmer
8.58
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
313526AB2-022
Solar/Wind Helper
0.503
316059AD1-063 C
Solar/Wind Helper
0.33
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
315243AE2-183_GT3
50/50
11.107
3151051BRUNSWICKS1
50/50
17.513
971451AH1-221 GEN
50/50
25.618
3151531CLOVER1
50/50
9.385
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.475
970401AG2-262 GEN
Solar/Wind Harmer
2.098
316034AC1-036 C
Solar/Wind Harmer
0.509
971065AG2-659 GEN
Solar/Wind Harmer
11.131
316129AC1-054 GEN
Solar/Wind Harmer
1.825
270016AE1-250 BESS
Solar/Wind Harmer
2.845
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
315671AE2-027_GEN
Solar/Wind Helper
2.891
316072AD1-144
Solar/Wind Helper
0.405
964211AG1-282 GEN
Solar/Wind Helper
0.416
3143526WINTERP
Solar/Wind Helper
1.518
971629AH1-314 GEN
50/50
17.942
316131AB2-060 GEN
Solar/Wind Harmer
3.062
3147123OTTER R
Solar/Wind Harmer
-0.01
270030AE2-140 GEN
Solar/Wind Harmer
19.819
316359AB2-059 GEN
Solar/Wind Harmer
1.772
3142053HEARTS
Solar/Wind Harmer
0.155
316375AC2-012 GEN
Solar/Wind Helper
1.012
3145336SMITFLD
Solar/Wind Helper
1.485
3146456SLIGO L269
Solar/Wind Helper
0.357
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.301
315975AC1-164 GENB
Solar/Wind Helper
0.121
3142416OLDCHRC
Solar/Wind Helper
0.773
3142416OLDCHRC
Solar/Wind Helper
0.296
3151641KERR 7
50/50
0.53
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.376
3146776BUCKING
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
5.554
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
9.062
316036AC1-147 C
Solar/Wind Helper
0.587
316132AB2-190 GEN1
Solar/Wind Helper
1.996
3141726DUNNSVL
Solar/Wind Helper
1.234
316337AD2-073 GEN
Solar/Wind Helper
0.454
3146516WINFALL
Solar/Wind Helper
0.957
3146516WINFALL
Solar/Wind Helper
0.295
3151031BRUNSWICKG2
50/50
8.436
3146776BUCKING
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.128
3144536CHRHLND
Solar/Wind Helper
0.057
3142956BIRDNECK
Solar/Wind Helper
0.257
316305AF2-043 C
Solar/Wind Helper
0.472
316320Y1-086
Solar/Wind Helper
0.148
3146516WINFALL
Solar/Wind Helper
0.295
316223AC1-118
Solar/Wind Helper
0.442
970933AG2-581 GEN
Solar/Wind Harmer
59.249
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
958211AF2-115 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316294AC1-161 GEN
Solar/Wind Helper
7.701
316349AD2-085 GEN
Solar/Wind Helper
1.56
3146386ELIZ CT
Solar/Wind Helper
0.329
3142946ENON
Solar/Wind Helper
0.032
315976AC1-164 GENA
Solar/Wind Helper
4.103
316169AC1-164_GENC
Solar/Wind Helper
3.544
316431W1029_GEN1
Solar/Wind Helper
1.221
316433W1029_GEN2
Solar/Wind Helper
1.221
3146456SLIGO L269
Solar/Wind Helper
0.357
3142946ENON
Solar/Wind Helper
0.108
316473AC1-191 GEN
Solar/Wind Helper
1.733
3145273HOLLAND
Solar/Wind Helper
0.19
966881AG1-559 GEN
Solar/Wind Helper
0.332
3146376EDENTON
Solar/Wind Helper
0.227
971967AH1-528 GEN
Solar/Wind Harmer
124.702
970085AG2-068 GEN
Solar/Wind Harmer
41.274
3144303KENBRDG
Solar/Wind Harmer
-0.022
946301AF1-294 GEN
Solar/Wind Harmer
6.831
270457AD2-023 GEN
Solar/Wind Harmer
2.392
316018AA1-139 ULT2
Solar/Wind Helper
1.56
957601AF2-054 GEN
Solar/Wind Helper
0.441
3141813NORNECK
Solar/Wind Helper
0.307
316233AE1-074 FULL
Solar/Wind Helper
0.446
315800Z1-036_GEN1
Solar/Wind Helper
1.317
270018AE2-047 C O1
Solar/Wind Harmer
1.377
316381AD1-082 GEN
Solar/Wind Helper
1.851
319010AE1-072 C
Solar/Wind Helper
4.06
316369SG1_INVT
Solar/Wind Helper
1.706
315662AE1-191 GEN
Solar/Wind Helper
1.769
316280AD1-041 GEN
Solar/Wind Helper
1.106
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
316404AE1-155 C
Solar/Wind Helper
2.683
3143226MDLTHAN
Solar/Wind Helper
0.286
315611Z1-036_GEN2
Solar/Wind Helper
1.317
3130156CHOWAN
Solar/Wind Helper
0.227
3151041BRUNSWICKG3
50/50
8.436
3152661PLYWOOD A
50/50
0.663
3151581KERR 1
50/50
0.189
970301AG2-198 GEN
Solar/Wind Harmer
17.428
313527AB2-043 GEN
Solar/Wind Harmer
4.632
970323AG2-213 GEN
Solar/Wind Harmer
13.764
942671AE2-283 GEN
Solar/Wind Harmer
4.906
316049AB1-081 GEN
Solar/Wind Harmer
1.418
3145506HICKORY
Solar/Wind Helper
1.495
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.224
316339AD2-160 GEN
Solar/Wind Helper
1.391
316388AE2-253 GEN
Solar/Wind Helper
1.391
3137176SLIGO L2192
Solar/Wind Helper
1.422
316033AB2-134 GEN
Solar/Wind Helper
1.225
3130086AYDLETT
Solar/Wind Helper
1.412
316487AF1-042 GEN
Solar/Wind Helper
0.321
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
970917AG2-570 GEN
Solar/Wind Harmer
168.871
970257AG2-171 GEN
Solar/Wind Harmer
10.323
971775AH1-396 GEN
Solar/Wind Harmer
1.942
3146926FARMVIL
Solar/Wind Harmer
-0.015
316217AC1-145 GEN
Solar/Wind Harmer
2.402
316197AC1-042 GEN
Solar/Wind Harmer
1.821
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.401
316458AB2-190 GEN2
Solar/Wind Helper
1.996
316321Z2-027
Solar/Wind Helper
0.485
3141906WESTMOR
Solar/Wind Helper
0.116
3146626S HERTFORD
Solar/Wind Helper
0.279
315242AE2-183_GT2
50/50
11.107
315241AE2-183_GT1
50/50
11.078
972185AH1-677 GEN
50/50
40.15
970909AG2-566 GEN
50/50
3.309
3144293JTRSVLE
50/50
0.601
970099AG2-077 GEN
Solar/Wind Harmer
66.815
315687AD1-152 GEN
Solar/Wind Harmer
5.329
316248AF1-058 C
Solar/Wind Harmer
1.044
962561AG1-105 GEN
Solar/Wind Harmer
17.768
316237AB2-079_GEN
Solar/Wind Harmer
0.865
270013AE1-250 PV
Solar/Wind Harmer
2.845
316263AC1-034 GEN
Solar/Wind Harmer
6.176
316185AD1-033 GEN
Solar/Wind Helper
1.79
3144356SAPONY
Solar/Wind Helper
0.564
316315AB2-025 C
Solar/Wind Helper
0.481
316312AB1-027
Solar/Wind Helper
0.567
3143526WINTERP
Solar/Wind Helper
1.518
970413AG2-270 GEN
50/50
40.873
3144293JTRSVLE
50/50
0.601
971683AH1-343 GEN
Solar/Wind Harmer
13.215
964241AG1-285 GEN
Solar/Wind Harmer
22.01
316123AC1-075 GEN
Solar/Wind Harmer
2.792
942461AE2-259 GEN
Solar/Wind Harmer
3.838
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.613
316075AC2-137 C
Solar/Wind Helper
0.476
316077AC2-138 C
Solar/Wind Helper
0.29
972187AH1-678 GEN
50/50
19.356
970535AG2-341 GEN
50/50
4.57
316118AC1-105 GEN
Solar/Wind Harmer
2.295
964791AG1-342 GEN
Solar/Wind Harmer
6.865
942751AE2-291 GEN
Solar/Wind Harmer
15.125
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
5.064
316240AF1-291 C
Solar/Wind Helper
0.475
316156AD2-030 GEN
Solar/Wind Helper
0.498
315666AE1-190 GEN
Solar/Wind Helper
0.442
316435W1029_GEN3
Solar/Wind Helper
1.221
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
3146516WINFALL
Solar/Wind Helper
0.295
966871AG1-558 GEN
Solar/Wind Helper
0.382
LAGNLTFEXP_LAGN->PJM
CLTF
14.705
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.324
TVALTFEXP_TVA->PJM
CLTF
7.333
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.984
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.223
MECLTFEXP_MEC->PJM
CLTF
7.397
CPLELTFEXP_CPLE->PJM
CLTF
19.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.485
SIGELTFEXP_SIGE->PJM
CLTF
0.222
NYPJM->LTFIMP_NY
CLTF
2.372
LGEELTFEXP_LGEE->PJM
CLTF
2.687
WECLTFEXP_WEC->PJM
CLTF
1.407
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.114

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.09 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5400.34
MW Contribution:
17.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.532
970581AG2-369 GEN
Solar/Wind Harmer
35.263
270069AE2-166 C O1
Solar/Wind Harmer
7.989
316236AE1-162_GEN
Solar/Wind Helper
0.499
3143316POE
Solar/Wind Helper
1.405
316382AG1-145 C
Solar/Wind Helper
0.47
316159AE1-175 C
Solar/Wind Helper
0.53
3141873WAN 176
Solar/Wind Helper
0.065
3146486SUNBURY
Solar/Wind Helper
0.322
315244AE2-183_ST
50/50
19.154
3151541CLOVER2
50/50
9.264
3151631KERR 6
50/50
0.532
970673AG2-436 GEN
Solar/Wind Harmer
175.868
963041AG1-153 GEN
50/50
16.962
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
316486AD2-202 GEN
Solar/Wind Harmer
1.235
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
961791AG1-021 GEN
Solar/Wind Harmer
3.331
270455AD2-022 GEN
Solar/Wind Harmer
4.705
971845AH1-439 GEN
Solar/Wind Harmer
8.548
270197AD1-017 GEN1
Solar/Wind Harmer
1.675
313526AB2-022
Solar/Wind Helper
0.505
316059AD1-063 C
Solar/Wind Helper
0.326
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316238AB2-078_GEN
Solar/Wind Harmer
0.867
316239AB2-077_GEN
Solar/Wind Harmer
0.867
970683AG2-441 GEN
Solar/Wind Harmer
19.131
970681AG2-440 GEN
Solar/Wind Harmer
12.698
970831AG2-522 GEN
Solar/Wind Harmer
9.671
316322AB2-045
Solar/Wind Harmer
0.514
316316AC1-027 C
Solar/Wind Helper
0.607
315697AD1-025 GEN
Solar/Wind Helper
3.957
957831AF2-077 GEN
Solar/Wind Helper
0.465
315839AE2-212 C
Solar/Wind Helper
0.458
3141913WHIT STONE
Solar/Wind Helper
0.323
316468AD1-105 GEN
Solar/Wind Helper
1.26
315243AE2-183_GT3
50/50
11.03
3151051BRUNSWICKS1
50/50
17.394
971451AH1-221 GEN
50/50
25.443
3151531CLOVER1
50/50
9.336
3144293JTRSVLE
50/50
0.601
3144293JTRSVLE
50/50
0.474
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316034AC1-036 C
Solar/Wind Harmer
0.509
971065AG2-659 GEN
Solar/Wind Harmer
11.235
316129AC1-054 GEN
Solar/Wind Harmer
1.845
270016AE1-250 BESS
Solar/Wind Harmer
2.837
971629AH1-314 GEN
50/50
17.894
316131AB2-060 GEN
Solar/Wind Harmer
3.07
3147123OTTER R
Solar/Wind Harmer
-0.01
270030AE2-140 GEN
Solar/Wind Harmer
19.766
316359AB2-059 GEN
Solar/Wind Harmer
1.815
3142053HEARTS
Solar/Wind Harmer
0.159
316375AC2-012 GEN
Solar/Wind Helper
1.018
3145336SMITFLD
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.359
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.273
315975AC1-164 GENB
Solar/Wind Helper
0.119
3142416OLDCHRC
Solar/Wind Helper
0.758
3142416OLDCHRC
Solar/Wind Helper
0.29
3151591KERR 2
50/50
0.532
3151641KERR 7
50/50
0.532
3151561HALLBR1
50/50
0.362
970919AG2-571 GEN
Solar/Wind Harmer
21.235
3146776BUCKING
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
5.539
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
9.171
316036AC1-147 C
Solar/Wind Helper
0.591
316132AB2-190 GEN1
Solar/Wind Helper
1.935
3141726DUNNSVL
Solar/Wind Helper
1.22
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
316337AD2-073 GEN
Solar/Wind Helper
0.449
3151031BRUNSWICKG2
50/50
8.378
3146776BUCKING
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.26
3142956BIRDNECK
Solar/Wind Helper
0.258
3144536CHRHLND
Solar/Wind Helper
0.058
316305AF2-043 C
Solar/Wind Helper
0.474
316320Y1-086
Solar/Wind Helper
0.149
3146516WINFALL
Solar/Wind Helper
0.296
970933AG2-581 GEN
Solar/Wind Harmer
58.871
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
958211AF2-115 GEN
Solar/Wind Harmer
4.164
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316294AC1-161 GEN
Solar/Wind Helper
7.794
316349AD2-085 GEN
Solar/Wind Helper
1.524
3146386ELIZ CT
Solar/Wind Helper
0.331
3142946ENON
Solar/Wind Helper
0.031
315976AC1-164 GENA
Solar/Wind Helper
4.039
316169AC1-164_GENC
Solar/Wind Helper
3.489
316431W1029_GEN1
Solar/Wind Helper
1.223
316433W1029_GEN2
Solar/Wind Helper
1.223
316478AD1-087 GEN
Solar/Wind Harmer
4.218
316003AC1-222 GEN
Solar/Wind Harmer
3.188
316222AC1-221 GEN
Solar/Wind Harmer
3.202
316283AC2-100 C
Solar/Wind Harmer
2.967
959311AF2-222 GEN
Solar/Wind Harmer
28.621
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270574AD1-017 GEN2
Solar/Wind Harmer
5.584
943811AF1-049 GEN
Solar/Wind Harmer
3.841
270336AE1-100 GEN
Solar/Wind Harmer
1.564
3145336SMITFLD
Solar/Wind Helper
0.148
316017AA1-139 ULT1
Solar/Wind Helper
1.667
3146456SLIGO L269
Solar/Wind Helper
0.359
3142946ENON
Solar/Wind Helper
0.105
316473AC1-191 GEN
Solar/Wind Helper
1.693
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146376EDENTON
Solar/Wind Helper
0.226
316223AC1-118
Solar/Wind Helper
0.438
971967AH1-528 GEN
Solar/Wind Harmer
123.886
970085AG2-068 GEN
Solar/Wind Harmer
41.004
3144303KENBRDG
Solar/Wind Harmer
-0.022
946301AF1-294 GEN
Solar/Wind Harmer
6.829
270457AD2-023 GEN
Solar/Wind Harmer
2.386
316018AA1-139 ULT2
Solar/Wind Helper
1.569
957601AF2-054 GEN
Solar/Wind Helper
0.437
3141813NORNECK
Solar/Wind Helper
0.304
316233AE1-074 FULL
Solar/Wind Helper
0.44
315800Z1-036_GEN1
Solar/Wind Helper
1.313
3151021BRUNSWICKG1
50/50
8.378
970087AG2-069 GEN
Solar/Wind Harmer
61.506
957481AF2-042 GEN
Solar/Wind Harmer
166.083
315693AD1-088 GEN
Solar/Wind Harmer
24.245
315785AD2-033 C
Solar/Wind Harmer
6.277
970685AG2-442 GEN
Solar/Wind Harmer
23.525
971563AH1-280 GEN
Solar/Wind Harmer
3.331
3146926FARMVIL
Solar/Wind Harmer
-0.015
970223AG2-152 GEN
Solar/Wind Harmer
17.186
270018AE2-047 C O1
Solar/Wind Harmer
1.373
319010AE1-072 C
Solar/Wind Helper
4.082
316369SG1_INVT
Solar/Wind Helper
1.668
316381AD1-082 GEN
Solar/Wind Helper
1.76
315662AE1-191 GEN
Solar/Wind Helper
1.75
316280AD1-041 GEN
Solar/Wind Helper
1.093
3138133OCRAN
Solar/Wind Helper
0.193
316404AE1-155 C
Solar/Wind Helper
2.656
3142543TWELFTH
Solar/Wind Helper
0.029
3143226MDLTHAN
Solar/Wind Helper
0.284
315611Z1-036_GEN2
Solar/Wind Helper
1.313
3130156CHOWAN
Solar/Wind Helper
0.227
3151041BRUNSWICKG3
50/50
8.378
3152661PLYWOOD A
50/50
0.662
3151581KERR 1
50/50
0.19
970301AG2-198 GEN
Solar/Wind Harmer
17.344
313527AB2-043 GEN
Solar/Wind Harmer
4.644
970323AG2-213 GEN
Solar/Wind Harmer
13.779
942671AE2-283 GEN
Solar/Wind Harmer
4.893
316049AB1-081 GEN
Solar/Wind Harmer
1.452
3145506HICKORY
Solar/Wind Helper
1.505
3145506HICKORY
Solar/Wind Helper
0.903
3145506HICKORY
Solar/Wind Helper
0.226
316339AD2-160 GEN
Solar/Wind Helper
1.399
316388AE2-253 GEN
Solar/Wind Helper
1.399
3137176SLIGO L2192
Solar/Wind Helper
1.43
3130086AYDLETT
Solar/Wind Helper
1.419
316033AB2-134 GEN
Solar/Wind Helper
1.198
316487AF1-042 GEN
Solar/Wind Helper
0.317
3146626S HERTFORD
Solar/Wind Helper
0.279
3146626S HERTFORD
Solar/Wind Helper
0.279
970917AG2-570 GEN
Solar/Wind Harmer
167.755
970257AG2-171 GEN
Solar/Wind Harmer
10.334
971775AH1-396 GEN
Solar/Wind Harmer
1.944
3146926FARMVIL
Solar/Wind Harmer
-0.015
316217AC1-145 GEN
Solar/Wind Harmer
2.396
316197AC1-042 GEN
Solar/Wind Harmer
1.816
3144873MCLAUGH
Solar/Wind Helper
0.01
316246AF1-032 C
Solar/Wind Helper
0.403
316458AB2-190 GEN2
Solar/Wind Helper
1.935
316321Z2-027
Solar/Wind Helper
0.487
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.279
315242AE2-183_GT2
50/50
11.03
315241AE2-183_GT1
50/50
11.001
972185AH1-677 GEN
50/50
39.871
970909AG2-566 GEN
50/50
3.293
3144293JTRSVLE
50/50
0.601
970099AG2-077 GEN
Solar/Wind Harmer
66.433
315687AD1-152 GEN
Solar/Wind Harmer
5.303
316248AF1-058 C
Solar/Wind Harmer
1.041
962561AG1-105 GEN
Solar/Wind Harmer
17.76
316237AB2-079_GEN
Solar/Wind Harmer
0.867
270013AE1-250 PV
Solar/Wind Harmer
2.837
316263AC1-034 GEN
Solar/Wind Harmer
6.326
316185AD1-033 GEN
Solar/Wind Helper
1.802
316312AB1-027
Solar/Wind Helper
0.557
3143526WINTERP
Solar/Wind Helper
1.497
3144356SAPONY
Solar/Wind Helper
0.491
316315AB2-025 C
Solar/Wind Helper
0.418
970413AG2-270 GEN
50/50
40.656
3144293JTRSVLE
50/50
0.601
971683AH1-343 GEN
Solar/Wind Harmer
13.175
964241AG1-285 GEN
Solar/Wind Harmer
22.056
316123AC1-075 GEN
Solar/Wind Harmer
2.783
942461AE2-259 GEN
Solar/Wind Harmer
3.829
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.606
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.287
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
316072AD1-144
Solar/Wind Helper
0.405
315671AE2-027_GEN
Solar/Wind Helper
2.696
964211AG1-282 GEN
Solar/Wind Helper
0.411
3143526WINTERP
Solar/Wind Helper
1.497
972187AH1-678 GEN
50/50
19.224
970535AG2-341 GEN
50/50
4.581
316118AC1-105 GEN
Solar/Wind Harmer
2.29
964791AG1-342 GEN
Solar/Wind Harmer
6.859
942751AE2-291 GEN
Solar/Wind Harmer
15.08
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
5.194
316240AF1-291 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.493
315666AE1-190 GEN
Solar/Wind Helper
0.437
316435W1029_GEN3
Solar/Wind Helper
1.223
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
966871AG1-558 GEN
Solar/Wind Helper
0.374
3146486SUNBURY
Solar/Wind Helper
0.322
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3145176PASQUOTANK
Solar/Wind Helper
0.197
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.661
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.209
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.147
CPLELTFEXP_CPLE->PJM
CLTF
19.725
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.242
TVALTFEXP_TVA->PJM
CLTF
7.311
MECLTFEXP_MEC->PJM
CLTF
7.373
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.679
WECLTFEXP_WEC->PJM
CLTF
1.402
AG2-052LTFEXP_AG2-052->PJM
LTF
0.076
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.51 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5321.19
MW Contribution:
17.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
16.818
3151611KERR 4
50/50
0.526
3151621KERR 5
50/50
0.526
316486AD2-202 GEN
Solar/Wind Harmer
1.224
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
961791AG1-021 GEN
Solar/Wind Harmer
3.286
270455AD2-022 GEN
Solar/Wind Harmer
4.668
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
971845AH1-439 GEN
Solar/Wind Harmer
8.41
316059AD1-063 C
Solar/Wind Helper
0.313
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.122
313526AB2-022
Solar/Wind Helper
0.431
315244AE2-183_ST
50/50
18.991
3151541CLOVER2
50/50
9.18
3151631KERR 6
50/50
0.526
970673AG2-436 GEN
Solar/Wind Harmer
174.37
316238AB2-078_GEN
Solar/Wind Harmer
0.854
316239AB2-077_GEN
Solar/Wind Harmer
0.854
970683AG2-441 GEN
Solar/Wind Harmer
18.866
970681AG2-440 GEN
Solar/Wind Harmer
12.522
970831AG2-522 GEN
Solar/Wind Harmer
9.555
316322AB2-045
Solar/Wind Harmer
0.505
971629AH1-314 GEN
50/50
17.75
316131AB2-060 GEN
Solar/Wind Harmer
3.026
3147123OTTER R
Solar/Wind Harmer
-0.01
270030AE2-140 GEN
Solar/Wind Harmer
19.599
316359AB2-059 GEN
Solar/Wind Harmer
1.807
3142053HEARTS
Solar/Wind Harmer
0.158
316375AC2-012 GEN
Solar/Wind Helper
0.883
3145336SMITFLD
Solar/Wind Helper
1.329
3142433PROV 92
Solar/Wind Helper
1.252
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
315975AC1-164 GENB
Solar/Wind Helper
0.116
3142416OLDCHRC
Solar/Wind Helper
0.75
3142416OLDCHRC
Solar/Wind Helper
0.287
3151591KERR 2
50/50
0.526
3151641KERR 7
50/50
0.526
3151561HALLBR1
50/50
0.359
970919AG2-571 GEN
Solar/Wind Harmer
21.055
3146776BUCKING
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
5.486
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Helper
8.532
316036AC1-147 C
Solar/Wind Helper
0.512
970933AG2-581 GEN
Solar/Wind Harmer
58.356
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
958211AF2-115 GEN
Solar/Wind Harmer
4.107
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316294AC1-161 GEN
Solar/Wind Helper
7.251
3142946ENON
Solar/Wind Helper
0.031
316349AD2-085 GEN
Solar/Wind Helper
1.397
315976AC1-164 GENA
Solar/Wind Helper
3.933
316169AC1-164_GENC
Solar/Wind Helper
3.397
3146386ELIZ CT
Solar/Wind Helper
0.282
316478AD1-087 GEN
Solar/Wind Harmer
4.179
316003AC1-222 GEN
Solar/Wind Harmer
3.156
316222AC1-221 GEN
Solar/Wind Harmer
3.175
316283AC2-100 C
Solar/Wind Harmer
2.943
959311AF2-222 GEN
Solar/Wind Harmer
28.221
3147133PAMPLIN
Solar/Wind Harmer
-0.081
270574AD1-017 GEN2
Solar/Wind Harmer
5.536
943811AF1-049 GEN
Solar/Wind Harmer
3.808
270336AE1-100 GEN
Solar/Wind Harmer
1.55
3145336SMITFLD
Solar/Wind Helper
0.133
316017AA1-139 ULT1
Solar/Wind Helper
1.432
3142946ENON
Solar/Wind Helper
0.104
3146456SLIGO L269
Solar/Wind Helper
0.308
316473AC1-191 GEN
Solar/Wind Helper
1.701
966881AG1-559 GEN
Solar/Wind Helper
0.328
3151031BRUNSWICKG2
50/50
8.307
3146776BUCKING
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.233
3144536CHRHLND
Solar/Wind Helper
0.05
3142956BIRDNECK
Solar/Wind Helper
0.223
316305AF2-043 C
Solar/Wind Helper
0.402
316320Y1-086
Solar/Wind Helper
0.127
316223AC1-118
Solar/Wind Helper
0.424
3146516WINFALL
Solar/Wind Helper
0.25
971967AH1-528 GEN
Solar/Wind Harmer
122.813
970085AG2-068 GEN
Solar/Wind Harmer
40.657
3144303KENBRDG
Solar/Wind Harmer
-0.022
946301AF1-294 GEN
Solar/Wind Harmer
6.735
270457AD2-023 GEN
Solar/Wind Harmer
2.367
316018AA1-139 ULT2
Solar/Wind Helper
1.348
957601AF2-054 GEN
Solar/Wind Helper
0.417
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.445
316132AB2-190 GEN1
Solar/Wind Helper
1.896
3141726DUNNSVL
Solar/Wind Helper
1.177
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.811
3146516WINFALL
Solar/Wind Helper
0.25
3151021BRUNSWICKG1
50/50
8.307
970087AG2-069 GEN
Solar/Wind Harmer
60.986
957481AF2-042 GEN
Solar/Wind Harmer
164.583
315693AD1-088 GEN
Solar/Wind Harmer
24.018
315785AD2-033 C
Solar/Wind Harmer
6.188
970685AG2-442 GEN
Solar/Wind Harmer
23.201
971563AH1-280 GEN
Solar/Wind Harmer
3.286
3146926FARMVIL
Solar/Wind Harmer
-0.014
970223AG2-152 GEN
Solar/Wind Harmer
17.044
270018AE2-047 C O1
Solar/Wind Harmer
1.362
316381AD1-082 GEN
Solar/Wind Helper
1.75
316369SG1_INVT
Solar/Wind Helper
1.594
3142543TWELFTH
Solar/Wind Helper
0.03
315662AE1-191 GEN
Solar/Wind Helper
1.677
316280AD1-041 GEN
Solar/Wind Helper
1.048
3138133OCRAN
Solar/Wind Helper
0.185
319010AE1-072 C
Solar/Wind Helper
3.502
316404AE1-155 C
Solar/Wind Helper
2.553
3143226MDLTHAN
Solar/Wind Helper
0.289
3151041BRUNSWICKG3
50/50
8.307
3152661PLYWOOD A
50/50
0.655
3151581KERR 1
50/50
0.188
970301AG2-198 GEN
Solar/Wind Harmer
17.157
313527AB2-043 GEN
Solar/Wind Harmer
4.577
970323AG2-213 GEN
Solar/Wind Harmer
13.586
942671AE2-283 GEN
Solar/Wind Harmer
4.846
316049AB1-081 GEN
Solar/Wind Harmer
1.446
316033AB2-134 GEN
Solar/Wind Helper
1.145
3145506HICKORY
Solar/Wind Helper
1.296
3145506HICKORY
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.194
316339AD2-160 GEN
Solar/Wind Helper
1.203
316388AE2-253 GEN
Solar/Wind Helper
1.203
3137176SLIGO L2192
Solar/Wind Helper
1.227
3130086AYDLETT
Solar/Wind Helper
1.217
316487AF1-042 GEN
Solar/Wind Helper
0.305
3146626S HERTFORD
Solar/Wind Helper
0.235
3146626S HERTFORD
Solar/Wind Helper
0.235
970917AG2-570 GEN
Solar/Wind Harmer
166.334
970257AG2-171 GEN
Solar/Wind Harmer
10.19
971775AH1-396 GEN
Solar/Wind Harmer
1.917
3146926FARMVIL
Solar/Wind Harmer
-0.014
316217AC1-145 GEN
Solar/Wind Harmer
2.372
316197AC1-042 GEN
Solar/Wind Harmer
1.798
3144873MCLAUGH
Solar/Wind Helper
0.008
316458AB2-190 GEN2
Solar/Wind Helper
1.896
316246AF1-032 C
Solar/Wind Helper
0.342
3141906WESTMOR
Solar/Wind Helper
0.111
316321Z2-027
Solar/Wind Helper
0.414
3146626S HERTFORD
Solar/Wind Helper
0.235
315242AE2-183_GT2
50/50
10.936
315241AE2-183_GT1
50/50
10.907
972185AH1-677 GEN
50/50
39.531
970909AG2-566 GEN
50/50
3.258
3144293JTRSVLE
50/50
0.593
970099AG2-077 GEN
Solar/Wind Harmer
65.833
315687AD1-152 GEN
Solar/Wind Harmer
5.255
316248AF1-058 C
Solar/Wind Harmer
1.031
962561AG1-105 GEN
Solar/Wind Harmer
17.549
316237AB2-079_GEN
Solar/Wind Harmer
0.854
270013AE1-250 PV
Solar/Wind Harmer
2.814
316263AC1-034 GEN
Solar/Wind Harmer
6.299
316185AD1-033 GEN
Solar/Wind Helper
1.553
3144356SAPONY
Solar/Wind Helper
0.58
316315AB2-025 C
Solar/Wind Helper
0.494
3143526WINTERP
Solar/Wind Helper
1.516
316312AB1-027
Solar/Wind Helper
0.551
970413AG2-270 GEN
50/50
40.285
3144293JTRSVLE
50/50
0.593
971683AH1-343 GEN
Solar/Wind Harmer
13.046
964241AG1-285 GEN
Solar/Wind Harmer
21.742
316123AC1-075 GEN
Solar/Wind Harmer
2.756
942461AE2-259 GEN
Solar/Wind Harmer
3.778
3147312GRETNA
Solar/Wind Harmer
-0.003
316484AD2-074 GEN
Solar/Wind Helper
0.582
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
315839AE2-212 C
Solar/Wind Helper
0.498
316316AC1-027 C
Solar/Wind Helper
0.524
315697AD1-025 GEN
Solar/Wind Helper
3.782
957831AF2-077 GEN
Solar/Wind Helper
0.436
3141913WHIT STONE
Solar/Wind Helper
0.309
316468AD1-105 GEN
Solar/Wind Helper
1.263
315243AE2-183_GT3
50/50
10.936
3151051BRUNSWICKS1
50/50
17.246
971451AH1-221 GEN
50/50
25.226
3151531CLOVER1
50/50
9.25
3144293JTRSVLE
50/50
0.593
3144293JTRSVLE
50/50
0.468
970401AG2-262 GEN
Solar/Wind Harmer
2.072
316034AC1-036 C
Solar/Wind Harmer
0.502
971065AG2-659 GEN
Solar/Wind Harmer
11.105
316129AC1-054 GEN
Solar/Wind Harmer
1.824
270016AE1-250 BESS
Solar/Wind Harmer
2.814
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
315671AE2-027_GEN
Solar/Wind Helper
2.884
316072AD1-144
Solar/Wind Helper
0.351
964211AG1-282 GEN
Solar/Wind Helper
0.397
3143526WINTERP
Solar/Wind Helper
1.516
972187AH1-678 GEN
50/50
19.06
970535AG2-341 GEN
50/50
4.523
316118AC1-105 GEN
Solar/Wind Harmer
2.266
964791AG1-342 GEN
Solar/Wind Harmer
6.78
942751AE2-291 GEN
Solar/Wind Harmer
14.933
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
961601AG1-000A GEN
Solar/Wind Harmer
5.168
316240AF1-291 C
Solar/Wind Helper
0.472
316156AD2-030 GEN
Solar/Wind Helper
0.471
315666AE1-190 GEN
Solar/Wind Helper
0.419
966871AG1-558 GEN
Solar/Wind Helper
0.375
316435W1029_GEN3
Solar/Wind Helper
1.035
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
3146516WINFALL
Solar/Wind Helper
0.25
316431W1029_GEN1
Solar/Wind Helper
1.035
316433W1029_GEN2
Solar/Wind Helper
1.035
3151601KERR 3
50/50
0.526
970581AG2-369 GEN
Solar/Wind Harmer
34.965
270069AE2-166 C O1
Solar/Wind Harmer
7.921
3143316POE
Solar/Wind Helper
1.568
316236AE1-162_GEN
Solar/Wind Helper
0.448
316382AG1-145 C
Solar/Wind Helper
0.442
316159AE1-175 C
Solar/Wind Helper
0.498
3141873WAN 176
Solar/Wind Helper
0.062
3143873LANEXA
Solar/Wind Helper
0.186
3138133OCRAN
Solar/Wind Helper
0.092
3146486SUNBURY
Solar/Wind Helper
0.273
3146486SUNBURY
Solar/Wind Helper
0.273
3145176PASQUOTANK
Solar/Wind Helper
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
14.534
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.89
TVALTFEXP_TVA->PJM
CLTF
7.248
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.924
CPLELTFEXP_CPLE->PJM
CLTF
19.597
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.518
MECLTFEXP_MEC->PJM
CLTF
7.297
SIGELTFEXP_SIGE->PJM
CLTF
0.219
NYPJM->LTFIMP_NY
CLTF
2.37
LGEELTFEXP_LGEE->PJM
CLTF
2.65
WECLTFEXP_WEC->PJM
CLTF
1.386
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 941030 TO BUS 970672 CKT 1   /*AE2-094 TP   500.0 - AG2-436 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 58572_SRT-A'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-5: W72_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1   /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-2: XT585_SRT-S'
 OPEN BRANCH FROM BUS 970672 TO BUS 314940 CKT 1                /*AG2-436 TP   500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
END
CONTINGENCY 'DVP_P4-2: 54472_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51192_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BUS 314921                                                /*8RAWLIN_STC2 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51172_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T544_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
314268 to 314692 ckt 1
315684 to 314690 ckt 1
313996 to 970300 ckt 1
314697 to 315684 ckt 1
314936 to 314902 ckt 1
314940 to 970672 ckt 1
941030 to 314902 ckt 1
970300 to 314268 ckt 1
970672 to 941030 ckt 1

Winter Peak Analysis

The New Service Request AH1-314 was evaluated as a 100.0 MW (100.0 MW Capacity) injection in the AEP area.

AH1-314 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 100.0 MW (100.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC132.79 %694.0B921.58
14.7
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC121.81 %652.36B794.66
14.79
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC120.43 %652.36B785.66
14.79
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 57062_SRT-W
BreakerAC114.25 %694.0B792.92
14.79
IPDCPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC103.96 %694.0B721.49
14.7

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.79 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:921.58
MW Contribution:
14.7
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.07 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:972.07
MW Contribution:
15.34
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.143
3147133PAMPLIN
Solar/Wind Helper
1.404
3147133PAMPLIN
Solar/Wind Helper
0.358
3147133PAMPLIN
Solar/Wind Helper
0.447
3146776BUCKING
Solar/Wind Helper
1.11
3146776BUCKING
Solar/Wind Helper
0.09
3146776BUCKING
Solar/Wind Helper
0.1
3146776BUCKING
Solar/Wind Helper
0.111
3146843MT LREL
Solar/Wind Helper
0.801
3146843MT LREL
Solar/Wind Helper
0.801
3146926FARMVIL
Solar/Wind Helper
0.212
3146926FARMVIL
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.141
3147312GRETNA
Solar/Wind Helper
0.032
3147312GRETNA
Solar/Wind Helper
0.127
316034AC1-036 C
Solar/Wind Helper
0.109
316248AF1-058 C
Solar/Wind Helper
0.326
3146802CHATHAM
Solar/Wind Helper
0.119
3147243WELCO
Solar/Wind Helper
0.633
3144303KENBRDG
Solar/Wind Helper
0.372
3147173SINAI
Solar/Wind Helper
1.013
316478AD1-087 GEN
Solar/Wind Helper
0.708
316486AD2-202 GEN
Solar/Wind Helper
0.207
315687AD1-152 GEN
Solar/Wind Helper
1.243
315785AD2-033 C
Solar/Wind Helper
0.984
270030AE2-140 GEN
Solar/Wind Harmer
0.81
270069AE2-166 C O1
Solar/Wind Harmer
0.307
313527AB2-043 GEN
Solar/Wind Helper
0.402
316322AB2-045
Solar/Wind Helper
0.088
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.641
316123AC1-075 GEN
Solar/Wind Helper
0.821
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
316197AC1-042 GEN
Solar/Wind Helper
0.107
3145543BTLEBRO
Solar/Wind Harmer
-0.153
3145543BTLEBRO
Solar/Wind Harmer
-0.191
3145543BTLEBRO
Solar/Wind Harmer
-0.191
3145543BTLEBRO
Solar/Wind Harmer
-0.191
3138543CONSLDL
Solar/Wind Harmer
-0.105
3142053HEARTS
Solar/Wind Harmer
0.007
3145453TOT5
Solar/Wind Harmer
0.005
3145493TOT1
Solar/Wind Harmer
0.015
3145493TOT1
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
-0.171
3145573BETHELC
Solar/Wind Harmer
-0.171
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.171
3146083TARBORO
Solar/Wind Harmer
-0.171
3146083TARBORO
Solar/Wind Harmer
-0.171
3146233WITAKRS
Solar/Wind Harmer
0.032
3146233WITAKRS
Solar/Wind Harmer
-0.615
3146233WITAKRS
Solar/Wind Harmer
-0.105
942461AE2-259 GEN
Solar/Wind Helper
0.64
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.343
961601AG1-000A GEN
Solar/Wind Harmer
5.492
970085AG2-068 GEN
Solar/Wind Harmer
0.748
970087AG2-069 GEN
Solar/Wind Harmer
1.123
970223AG2-152 GEN
Solar/Wind Harmer
0.674
970581AG2-369 GEN
Solar/Wind Harmer
0.644
970917AG2-570 GEN
Solar/Wind Harmer
2.993
970919AG2-571 GEN
Solar/Wind Harmer
5.986
971629AH1-314 GEN
50/50
14.704
940641AE2-051 GEN
Solar/Wind Helper
0.486
957861AF2-080 GEN
Solar/Wind Harmer
0.184
315773AC2-141 GEN
Solar/Wind Helper
0.623
316003AC1-222 GEN
Solar/Wind Helper
0.969
316118AC1-105 GEN
Solar/Wind Helper
0.744
316129AC1-054 GEN
Solar/Wind Helper
0.237
316217AC1-145 GEN
Solar/Wind Helper
0.128
316222AC1-221 GEN
Solar/Wind Helper
2.601
316263AC1-034 GEN
Solar/Wind Harmer
0.252
316283AC2-100 C
Solar/Wind Helper
2.45
316294AC1-161 GEN
Solar/Wind Helper
0.623
900033ID_568986
External Queue
0.23467768728733063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.833
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.276
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.915
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.82
NYPJM->LTFIMP_NY
CLTF
0.324
LGEELTFEXP_LGEE->PJM
CLTF
1.511
WECLTFEXP_WEC->PJM
CLTF
0.818
CPLELTFEXP_CPLE->PJM
CLTF
13.455
TVALTFEXP_TVA->PJM
CLTF
4.357
MECLTFEXP_MEC->PJM
CLTF
4.35
LAGNLTFEXP_LAGN->PJM
CLTF
8.827
SIGELTFEXP_SIGE->PJM
CLTF
0.128
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.217

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.81 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:794.66
MW Contribution:
14.79
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.46 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:824.95
MW Contribution:
15.43
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.142
3147133PAMPLIN
Solar/Wind Helper
1.396
3147133PAMPLIN
Solar/Wind Helper
0.356
3147133PAMPLIN
Solar/Wind Helper
0.444
3146776BUCKING
Solar/Wind Helper
1.099
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.798
3146843MT LREL
Solar/Wind Helper
0.798
3146926FARMVIL
Solar/Wind Helper
0.21
3146926FARMVIL
Solar/Wind Helper
0.21
3147123OTTER R
Solar/Wind Helper
0.14
3147312GRETNA
Solar/Wind Helper
0.031
3147312GRETNA
Solar/Wind Helper
0.125
316034AC1-036 C
Solar/Wind Helper
0.109
316248AF1-058 C
Solar/Wind Helper
0.325
3146802CHATHAM
Solar/Wind Helper
0.117
3147243WELCO
Solar/Wind Helper
0.632
3144303KENBRDG
Solar/Wind Helper
0.37
3147173SINAI
Solar/Wind Helper
1.011
316478AD1-087 GEN
Solar/Wind Helper
0.705
316486AD2-202 GEN
Solar/Wind Helper
0.206
315687AD1-152 GEN
Solar/Wind Helper
1.239
315785AD2-033 C
Solar/Wind Helper
0.979
270030AE2-140 GEN
Solar/Wind Harmer
0.818
270069AE2-166 C O1
Solar/Wind Harmer
0.31
313527AB2-043 GEN
Solar/Wind Helper
0.4
316322AB2-045
Solar/Wind Helper
0.087
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.638
316123AC1-075 GEN
Solar/Wind Helper
0.817
316239AB2-077_GEN
Solar/Wind Helper
0.162
316238AB2-078_GEN
Solar/Wind Helper
0.162
316237AB2-079_GEN
Solar/Wind Helper
0.162
316197AC1-042 GEN
Solar/Wind Helper
0.106
3145543BTLEBRO
Solar/Wind Harmer
-0.155
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3138543CONSLDL
Solar/Wind Harmer
-0.106
3142053HEARTS
Solar/Wind Harmer
0.007
3145453TOT5
Solar/Wind Harmer
0.005
3145493TOT1
Solar/Wind Harmer
0.015
3145493TOT1
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
-0.174
3145573BETHELC
Solar/Wind Harmer
-0.174
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146233WITAKRS
Solar/Wind Harmer
0.033
3146233WITAKRS
Solar/Wind Harmer
-0.624
3146233WITAKRS
Solar/Wind Harmer
-0.107
942461AE2-259 GEN
Solar/Wind Helper
0.636
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.347
961601AG1-000A GEN
Solar/Wind Harmer
5.558
970085AG2-068 GEN
Solar/Wind Harmer
0.752
970087AG2-069 GEN
Solar/Wind Harmer
1.129
970223AG2-152 GEN
Solar/Wind Harmer
0.68
970417AG2-272 GEN
50/50
1.818
970581AG2-369 GEN
Solar/Wind Harmer
0.647
970917AG2-570 GEN
Solar/Wind Harmer
3.01
970919AG2-571 GEN
Solar/Wind Harmer
6.019
971629AH1-314 GEN
50/50
14.786
940641AE2-051 GEN
Solar/Wind Helper
0.479
957861AF2-080 GEN
Solar/Wind Harmer
0.187
315773AC2-141 GEN
Solar/Wind Helper
0.613
316003AC1-222 GEN
Solar/Wind Helper
0.966
316118AC1-105 GEN
Solar/Wind Helper
0.742
316129AC1-054 GEN
Solar/Wind Helper
0.234
316217AC1-145 GEN
Solar/Wind Helper
0.126
316222AC1-221 GEN
Solar/Wind Helper
2.598
316263AC1-034 GEN
Solar/Wind Harmer
0.255
316283AC2-100 C
Solar/Wind Helper
2.447
316294AC1-161 GEN
Solar/Wind Helper
0.613
900033ID_568986
External Queue
0.23467768728733063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.232
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.184
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.034
NYPJM->LTFIMP_NY
CLTF
0.279
LGEELTFEXP_LGEE->PJM
CLTF
1.56
WECLTFEXP_WEC->PJM
CLTF
0.845
CPLELTFEXP_CPLE->PJM
CLTF
13.532
TVALTFEXP_TVA->PJM
CLTF
4.428
MECLTFEXP_MEC->PJM
CLTF
4.469
LAGNLTFEXP_LAGN->PJM
CLTF
8.971
SIGELTFEXP_SIGE->PJM
CLTF
0.132
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.217

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.43 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:785.66
MW Contribution:
14.79
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.53 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:812.37
MW Contribution:
15.43
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.142
3147133PAMPLIN
Solar/Wind Helper
1.396
3147133PAMPLIN
Solar/Wind Helper
0.356
3147133PAMPLIN
Solar/Wind Helper
0.444
3146776BUCKING
Solar/Wind Helper
1.099
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.798
3146843MT LREL
Solar/Wind Helper
0.798
3146926FARMVIL
Solar/Wind Helper
0.21
3146926FARMVIL
Solar/Wind Helper
0.21
3147123OTTER R
Solar/Wind Helper
0.14
3147312GRETNA
Solar/Wind Helper
0.031
3147312GRETNA
Solar/Wind Helper
0.125
316034AC1-036 C
Solar/Wind Helper
0.109
316248AF1-058 C
Solar/Wind Helper
0.325
3146802CHATHAM
Solar/Wind Helper
0.117
3147243WELCO
Solar/Wind Helper
0.632
3144303KENBRDG
Solar/Wind Helper
0.37
3147173SINAI
Solar/Wind Helper
1.011
316478AD1-087 GEN
Solar/Wind Helper
0.705
316486AD2-202 GEN
Solar/Wind Helper
0.206
315687AD1-152 GEN
Solar/Wind Helper
1.239
315785AD2-033 C
Solar/Wind Helper
0.979
270030AE2-140 GEN
Solar/Wind Harmer
0.818
270069AE2-166 C O1
Solar/Wind Harmer
0.31
313527AB2-043 GEN
Solar/Wind Helper
0.4
316322AB2-045
Solar/Wind Helper
0.087
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.638
316123AC1-075 GEN
Solar/Wind Helper
0.817
316239AB2-077_GEN
Solar/Wind Helper
0.162
316238AB2-078_GEN
Solar/Wind Helper
0.162
316237AB2-079_GEN
Solar/Wind Helper
0.162
316197AC1-042 GEN
Solar/Wind Helper
0.106
3145543BTLEBRO
Solar/Wind Harmer
-0.155
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3138543CONSLDL
Solar/Wind Harmer
-0.106
3142053HEARTS
Solar/Wind Harmer
0.007
3145453TOT5
Solar/Wind Harmer
0.005
3145493TOT1
Solar/Wind Harmer
0.015
3145493TOT1
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
-0.174
3145573BETHELC
Solar/Wind Harmer
-0.174
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146233WITAKRS
Solar/Wind Harmer
0.033
3146233WITAKRS
Solar/Wind Harmer
-0.624
3146233WITAKRS
Solar/Wind Harmer
-0.107
942461AE2-259 GEN
Solar/Wind Helper
0.636
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.347
961601AG1-000A GEN
Solar/Wind Harmer
5.558
970085AG2-068 GEN
Solar/Wind Harmer
0.752
970087AG2-069 GEN
Solar/Wind Harmer
1.129
970223AG2-152 GEN
Solar/Wind Harmer
0.68
970417AG2-272 GEN
50/50
1.818
970581AG2-369 GEN
Solar/Wind Harmer
0.647
971629AH1-314 GEN
50/50
14.786
940641AE2-051 GEN
Solar/Wind Helper
0.479
957861AF2-080 GEN
Solar/Wind Harmer
0.187
315773AC2-141 GEN
Solar/Wind Helper
0.613
316003AC1-222 GEN
Solar/Wind Helper
0.966
316118AC1-105 GEN
Solar/Wind Helper
0.742
316129AC1-054 GEN
Solar/Wind Helper
0.234
316217AC1-145 GEN
Solar/Wind Helper
0.126
316222AC1-221 GEN
Solar/Wind Helper
2.598
316263AC1-034 GEN
Solar/Wind Harmer
0.255
316283AC2-100 C
Solar/Wind Helper
2.447
316294AC1-161 GEN
Solar/Wind Helper
0.613
900033ID_568986
External Queue
0.23467768728733063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.232
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.184
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.034
NYPJM->LTFIMP_NY
CLTF
0.279
LGEELTFEXP_LGEE->PJM
CLTF
1.56
WECLTFEXP_WEC->PJM
CLTF
0.845
CPLELTFEXP_CPLE->PJM
CLTF
13.532
TVALTFEXP_TVA->PJM
CLTF
4.428
MECLTFEXP_MEC->PJM
CLTF
4.469
LAGNLTFEXP_LAGN->PJM
CLTF
8.971
SIGELTFEXP_SIGE->PJM
CLTF
0.132
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.217

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57062_SRT-W


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57062_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.25 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:792.92
MW Contribution:
14.79
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57062_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.41 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:821.74
MW Contribution:
15.43
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.142
3147133PAMPLIN
Solar/Wind Helper
1.396
3147133PAMPLIN
Solar/Wind Helper
0.356
3147133PAMPLIN
Solar/Wind Helper
0.444
3146776BUCKING
Solar/Wind Helper
1.099
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.798
3146843MT LREL
Solar/Wind Helper
0.798
3146926FARMVIL
Solar/Wind Helper
0.21
3146926FARMVIL
Solar/Wind Helper
0.21
3147123OTTER R
Solar/Wind Helper
0.14
3147312GRETNA
Solar/Wind Helper
0.031
3147312GRETNA
Solar/Wind Helper
0.125
316034AC1-036 C
Solar/Wind Helper
0.109
316248AF1-058 C
Solar/Wind Helper
0.325
3146802CHATHAM
Solar/Wind Helper
0.117
3147243WELCO
Solar/Wind Helper
0.632
3144303KENBRDG
Solar/Wind Helper
0.37
3147173SINAI
Solar/Wind Helper
1.011
316478AD1-087 GEN
Solar/Wind Helper
0.705
316486AD2-202 GEN
Solar/Wind Helper
0.206
315687AD1-152 GEN
Solar/Wind Helper
1.239
315785AD2-033 C
Solar/Wind Helper
0.979
270030AE2-140 GEN
Solar/Wind Harmer
0.818
270069AE2-166 C O1
Solar/Wind Harmer
0.31
313527AB2-043 GEN
Solar/Wind Helper
0.4
316322AB2-045
Solar/Wind Helper
0.087
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.638
316123AC1-075 GEN
Solar/Wind Helper
0.817
316239AB2-077_GEN
Solar/Wind Helper
0.162
316238AB2-078_GEN
Solar/Wind Helper
0.162
316237AB2-079_GEN
Solar/Wind Helper
0.162
316197AC1-042 GEN
Solar/Wind Helper
0.106
3145543BTLEBRO
Solar/Wind Harmer
-0.155
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3145543BTLEBRO
Solar/Wind Harmer
-0.193
3138543CONSLDL
Solar/Wind Harmer
-0.106
3142053HEARTS
Solar/Wind Harmer
0.007
3145453TOT5
Solar/Wind Harmer
0.005
3145493TOT1
Solar/Wind Harmer
0.015
3145493TOT1
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
-0.174
3145573BETHELC
Solar/Wind Harmer
-0.174
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146083TARBORO
Solar/Wind Harmer
-0.174
3146233WITAKRS
Solar/Wind Harmer
0.033
3146233WITAKRS
Solar/Wind Harmer
-0.624
3146233WITAKRS
Solar/Wind Harmer
-0.107
942461AE2-259 GEN
Solar/Wind Helper
0.636
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.347
961601AG1-000A GEN
Solar/Wind Harmer
5.558
970085AG2-068 GEN
Solar/Wind Harmer
0.752
970087AG2-069 GEN
Solar/Wind Harmer
1.129
970223AG2-152 GEN
Solar/Wind Harmer
0.68
970581AG2-369 GEN
Solar/Wind Harmer
0.647
970917AG2-570 GEN
Solar/Wind Harmer
3.01
970919AG2-571 GEN
Solar/Wind Harmer
6.019
971629AH1-314 GEN
50/50
14.786
940641AE2-051 GEN
Solar/Wind Helper
0.479
957861AF2-080 GEN
Solar/Wind Harmer
0.187
315773AC2-141 GEN
Solar/Wind Helper
0.613
316003AC1-222 GEN
Solar/Wind Helper
0.966
316118AC1-105 GEN
Solar/Wind Helper
0.742
316129AC1-054 GEN
Solar/Wind Helper
0.234
316217AC1-145 GEN
Solar/Wind Helper
0.126
316222AC1-221 GEN
Solar/Wind Helper
2.598
316263AC1-034 GEN
Solar/Wind Harmer
0.255
316283AC2-100 C
Solar/Wind Helper
2.447
316294AC1-161 GEN
Solar/Wind Helper
0.613
900033ID_568986
External Queue
0.23467768728733063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.869
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.232
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.184
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.034
NYPJM->LTFIMP_NY
CLTF
0.279
LGEELTFEXP_LGEE->PJM
CLTF
1.56
WECLTFEXP_WEC->PJM
CLTF
0.845
CPLELTFEXP_CPLE->PJM
CLTF
13.532
TVALTFEXP_TVA->PJM
CLTF
4.428
MECLTFEXP_MEC->PJM
CLTF
4.469
LAGNLTFEXP_LAGN->PJM
CLTF
8.971
SIGELTFEXP_SIGE->PJM
CLTF
0.132
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.217

Details for [AH1-314] 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.96 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:721.49
MW Contribution:
14.7
IPD Plant:AH1-314
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.46 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:731.92
MW Contribution:
15.34
IPD Plant:AH1-314
Bus #Bus NameTypeMW Contribution
971629AH1-314 GEN
PJM_IPD
14.704
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57062_SRT-W'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1                /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
304070 to 316281 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: XT591_SRT-W
BreakerAC102.09 %694.0B708.49
12.1
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 59162_SRT-W
BreakerAC102.09 %694.0B708.49
12.1
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 59192-2_SRT-W
BreakerAC102.08 %694.0B708.42
12.1

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: XT591_SRT-W


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT591_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:708.49
MW Contribution:
12.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.152
3147133PAMPLIN
Solar/Wind Helper
1.34
3147133PAMPLIN
Solar/Wind Helper
0.341
3147133PAMPLIN
Solar/Wind Helper
0.427
3146776BUCKING
Solar/Wind Helper
1.104
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.832
3146843MT LREL
Solar/Wind Helper
0.832
3146926FARMVIL
Solar/Wind Helper
0.213
3146926FARMVIL
Solar/Wind Helper
0.213
3147123OTTER R
Solar/Wind Helper
0.144
3147312GRETNA
Solar/Wind Helper
0.032
3147312GRETNA
Solar/Wind Helper
0.128
316034AC1-036 C
Solar/Wind Helper
0.105
316248AF1-058 C
Solar/Wind Helper
0.34
3146802CHATHAM
Solar/Wind Helper
0.12
3147243WELCO
Solar/Wind Helper
0.661
3144303KENBRDG
Solar/Wind Helper
0.38
3147173SINAI
Solar/Wind Helper
1.057
316478AD1-087 GEN
Solar/Wind Helper
0.731
316486AD2-202 GEN
Solar/Wind Helper
0.214
315687AD1-152 GEN
Solar/Wind Helper
1.292
315785AD2-033 C
Solar/Wind Helper
1.006
270030AE2-140 GEN
Solar/Wind Harmer
0.689
270069AE2-166 C O1
Solar/Wind Harmer
0.264
313527AB2-043 GEN
Solar/Wind Helper
0.413
316322AB2-045
Solar/Wind Helper
0.088
316131AB2-060 GEN
Solar/Wind Helper
0.659
316123AC1-075 GEN
Solar/Wind Helper
0.853
316239AB2-077_GEN
Solar/Wind Helper
0.168
316238AB2-078_GEN
Solar/Wind Helper
0.168
316237AB2-079_GEN
Solar/Wind Helper
0.168
316197AC1-042 GEN
Solar/Wind Helper
0.108
942461AE2-259 GEN
Solar/Wind Helper
0.631
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
0.555
971629AH1-314 GEN
50/50
12.096
316003AC1-222 GEN
Solar/Wind Helper
1.01
316118AC1-105 GEN
Solar/Wind Helper
0.775
316129AC1-054 GEN
Solar/Wind Helper
0.272
316217AC1-145 GEN
Solar/Wind Helper
0.129
316222AC1-221 GEN
Solar/Wind Helper
2.727
316283AC2-100 C
Solar/Wind Helper
2.568
900033ID_568986
External Queue
0.2580433189868927
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.679
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.857
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.392
NYPJM->LTFIMP_NY
CLTF
0.388
LGEELTFEXP_LGEE->PJM
CLTF
1.389
WECLTFEXP_WEC->PJM
CLTF
0.75
CPLELTFEXP_CPLE->PJM
CLTF
9.432
TVALTFEXP_TVA->PJM
CLTF
3.404
MECLTFEXP_MEC->PJM
CLTF
3.787
LAGNLTFEXP_LAGN->PJM
CLTF
6.849
SIGELTFEXP_SIGE->PJM
CLTF
0.114
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.925

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 59162_SRT-W


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 59162_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:708.49
MW Contribution:
12.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.152
3147133PAMPLIN
Solar/Wind Helper
1.34
3147133PAMPLIN
Solar/Wind Helper
0.341
3147133PAMPLIN
Solar/Wind Helper
0.427
3146776BUCKING
Solar/Wind Helper
1.104
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.832
3146843MT LREL
Solar/Wind Helper
0.832
3146926FARMVIL
Solar/Wind Helper
0.213
3146926FARMVIL
Solar/Wind Helper
0.213
3147123OTTER R
Solar/Wind Helper
0.144
3147312GRETNA
Solar/Wind Helper
0.032
3147312GRETNA
Solar/Wind Helper
0.128
316034AC1-036 C
Solar/Wind Helper
0.105
316248AF1-058 C
Solar/Wind Helper
0.34
3146802CHATHAM
Solar/Wind Helper
0.12
3147243WELCO
Solar/Wind Helper
0.661
3144303KENBRDG
Solar/Wind Helper
0.38
3147173SINAI
Solar/Wind Helper
1.057
316478AD1-087 GEN
Solar/Wind Helper
0.731
316486AD2-202 GEN
Solar/Wind Helper
0.214
315687AD1-152 GEN
Solar/Wind Helper
1.292
315785AD2-033 C
Solar/Wind Helper
1.006
270030AE2-140 GEN
Solar/Wind Harmer
0.689
270069AE2-166 C O1
Solar/Wind Harmer
0.264
313527AB2-043 GEN
Solar/Wind Helper
0.413
316322AB2-045
Solar/Wind Helper
0.088
316131AB2-060 GEN
Solar/Wind Helper
0.659
316123AC1-075 GEN
Solar/Wind Helper
0.853
316239AB2-077_GEN
Solar/Wind Helper
0.168
316238AB2-078_GEN
Solar/Wind Helper
0.168
316237AB2-079_GEN
Solar/Wind Helper
0.168
316197AC1-042 GEN
Solar/Wind Helper
0.108
942461AE2-259 GEN
Solar/Wind Helper
0.631
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
0.555
971629AH1-314 GEN
50/50
12.096
316003AC1-222 GEN
Solar/Wind Helper
1.01
316118AC1-105 GEN
Solar/Wind Helper
0.775
316129AC1-054 GEN
Solar/Wind Helper
0.272
316217AC1-145 GEN
Solar/Wind Helper
0.129
316222AC1-221 GEN
Solar/Wind Helper
2.727
316283AC2-100 C
Solar/Wind Helper
2.568
900033ID_568986
External Queue
0.2580433189868927
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.679
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.857
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.392
NYPJM->LTFIMP_NY
CLTF
0.388
LGEELTFEXP_LGEE->PJM
CLTF
1.389
WECLTFEXP_WEC->PJM
CLTF
0.75
CPLELTFEXP_CPLE->PJM
CLTF
9.432
TVALTFEXP_TVA->PJM
CLTF
3.404
MECLTFEXP_MEC->PJM
CLTF
3.787
LAGNLTFEXP_LAGN->PJM
CLTF
6.849
SIGELTFEXP_SIGE->PJM
CLTF
0.114
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.925

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 59192-2_SRT-W


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 59192-2_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:708.42
MW Contribution:
12.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.152
3147133PAMPLIN
Solar/Wind Helper
1.34
3147133PAMPLIN
Solar/Wind Helper
0.341
3147133PAMPLIN
Solar/Wind Helper
0.427
3146776BUCKING
Solar/Wind Helper
1.104
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.832
3146843MT LREL
Solar/Wind Helper
0.832
3146926FARMVIL
Solar/Wind Helper
0.213
3146926FARMVIL
Solar/Wind Helper
0.213
3147123OTTER R
Solar/Wind Helper
0.144
3147312GRETNA
Solar/Wind Helper
0.032
3147312GRETNA
Solar/Wind Helper
0.128
316034AC1-036 C
Solar/Wind Helper
0.105
316248AF1-058 C
Solar/Wind Helper
0.34
3146802CHATHAM
Solar/Wind Helper
0.12
3147243WELCO
Solar/Wind Helper
0.661
3144303KENBRDG
Solar/Wind Helper
0.38
3147173SINAI
Solar/Wind Helper
1.057
316478AD1-087 GEN
Solar/Wind Helper
0.731
316486AD2-202 GEN
Solar/Wind Helper
0.214
315687AD1-152 GEN
Solar/Wind Helper
1.292
315785AD2-033 C
Solar/Wind Helper
1.006
270030AE2-140 GEN
Solar/Wind Harmer
0.689
270069AE2-166 C O1
Solar/Wind Harmer
0.264
313527AB2-043 GEN
Solar/Wind Helper
0.413
316322AB2-045
Solar/Wind Helper
0.088
316131AB2-060 GEN
Solar/Wind Helper
0.659
316123AC1-075 GEN
Solar/Wind Helper
0.853
316239AB2-077_GEN
Solar/Wind Helper
0.168
316238AB2-078_GEN
Solar/Wind Helper
0.168
316237AB2-079_GEN
Solar/Wind Helper
0.168
316197AC1-042 GEN
Solar/Wind Helper
0.108
942461AE2-259 GEN
Solar/Wind Helper
0.631
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
0.555
971629AH1-314 GEN
50/50
12.096
316003AC1-222 GEN
Solar/Wind Helper
1.01
316118AC1-105 GEN
Solar/Wind Helper
0.775
316129AC1-054 GEN
Solar/Wind Helper
0.272
316217AC1-145 GEN
Solar/Wind Helper
0.129
316222AC1-221 GEN
Solar/Wind Helper
2.727
316283AC2-100 C
Solar/Wind Helper
2.568
900033ID_568986
External Queue
0.2580433189868927
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.679
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.857
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.392
NYPJM->LTFIMP_NY
CLTF
0.388
LGEELTFEXP_LGEE->PJM
CLTF
1.389
WECLTFEXP_WEC->PJM
CLTF
0.75
CPLELTFEXP_CPLE->PJM
CLTF
9.432
TVALTFEXP_TVA->PJM
CLTF
3.404
MECLTFEXP_MEC->PJM
CLTF
3.787
LAGNLTFEXP_LAGN->PJM
CLTF
6.849
SIGELTFEXP_SIGE->PJM
CLTF
0.114
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.925
CONTINGENCY 'DVP_P4-2: XT591_SRT-W'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 970916 TO BUS 314935 CKT 1 /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 970916 TO BUS 314935 CKT 1 /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 59162_SRT-W'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 59192-2_SRT-W'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BUS 314921                                                /*8RAWLIN_STC2 500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
304070 to 316281 ckt 1

Light Load Analysis

The New Service Request AH1-314 was evaluated as a 100.0 MW injection and 100.0 MW withdrawal in the AEP area.

AH1-314 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 100.0 MW (100.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC116.71 %541.0B631.41
14.76
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC106.94 %508.54B543.83
14.88
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC123.01 %508.54B625.53
8.26
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC111.38 %508.54B566.4
8.26

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.71 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:631.41
MW Contribution:
14.76
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.84 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:615.89
MW Contribution:
15.37
Bus #Bus NameTypeMW Contribution
970535AG2-341 GEN
50/50
Charging
6.427
3145543BTLEBRO
Solar/Wind Harmer
0.195
3145543BTLEBRO
Solar/Wind Harmer
0.195
3145543BTLEBRO
Solar/Wind Harmer
0.156
961671AG1-007 GEN
Solar/Wind Harmer
0.329
3145453TOT5
Solar/Wind Harmer
0.055
3145543BTLEBRO
Solar/Wind Harmer
0.195
315773AC2-141 GEN
Solar/Wind Helper
3.082
970919AG2-571 GEN
Solar/Wind Harmer
15.025
961601AG1-000A GEN
Solar/Wind Harmer
2.91
961601AG1-000A GEN
Solar/Wind Harmer
4.014
316118AC1-105 GEN
Solar/Wind Helper
4.009
970085AG2-068 GEN
Solar/Wind Harmer
8.715
957861AF2-080 GEN
Solar/Wind Harmer
2.16
316248AF1-058 C
Solar/Wind Helper
1.755
316123AC1-075 GEN
Solar/Wind Helper
4.419
316322AB2-045
Solar/Wind Helper
0.473
316129AC1-054 GEN
Solar/Wind Helper
1.268
3145573BETHELC
Solar/Wind Harmer
0.175
315687AD1-152 GEN
Solar/Wind Helper
6.698
942461AE2-259 GEN
Solar/Wind Helper
3.443
970413AG2-270 GEN
50/50
Charging
32.717
970909AG2-566 GEN
50/50
Charging
4.037
316034AC1-036 C
Solar/Wind Helper
0.588
971629AH1-314 GEN
50/50
14.763
943811AF1-049 GEN
Solar/Wind Harmer
0
3146073TAR RVR
Solar/Wind Harmer
0.175
316003AC1-222 GEN
Solar/Wind Helper
5.22
316359AB2-059 GEN
Solar/Wind Harmer
0
3142053HEARTS
Solar/Wind Harmer
0.078
3146083TARBORO
Solar/Wind Harmer
0.175
316478AD1-087 GEN
Solar/Wind Helper
3.812
3146083TARBORO
Solar/Wind Harmer
0.175
3138543CONSLDL
Solar/Wind Harmer
0.107
316222AC1-221 GEN
Solar/Wind Helper
14.034
316486AD2-202 GEN
Solar/Wind Helper
1.116
316131AB2-060 GEN
Solar/Wind Helper
3.449
316263AC1-034 GEN
Solar/Wind Harmer
2.947
3145573BETHELC
Solar/Wind Harmer
0.175
3145603CNETO
Solar/Wind Harmer
0.037
316237AB2-079_GEN
Solar/Wind Helper
0.878
316238AB2-078_GEN
Solar/Wind Helper
0.878
316239AB2-077_GEN
Solar/Wind Helper
0.878
270030AE2-140 GEN
Solar/Wind Harmer
8.971
316283AC2-100 C
Solar/Wind Helper
13.217
316294AC1-161 GEN
Solar/Wind Helper
1.112
3146233WITAKRS
Solar/Wind Harmer
0.63
970917AG2-570 GEN
Solar/Wind Harmer
34.858
970581AG2-369 GEN
Solar/Wind Harmer
7.495
3146233WITAKRS
Solar/Wind Harmer
0.38
313527AB2-043 GEN
Solar/Wind Helper
2.161
270069AE2-166 C O1
Solar/Wind Harmer
3.403
3145493TOT1
Solar/Wind Harmer
0.175
3146233WITAKRS
Solar/Wind Harmer
0.108
316197AC1-042 GEN
Solar/Wind Helper
0.53
970087AG2-069 GEN
Solar/Wind Harmer
13.073
970223AG2-152 GEN
Solar/Wind Harmer
7.46
3145493TOT1
Solar/Wind Harmer
0.091
315785AD2-033 C
Solar/Wind Helper
4.903
316217AC1-145 GEN
Solar/Wind Helper
0.682
900033ID_568986
External Queue
3.581075668334961
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.096
NYPJM->LTFIMP_NY
CLTF
0.292
TVALTFEXP_TVA->PJM
CLTF
4.501
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
25.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.413
WECLTFEXP_WEC->PJM
CLTF
0.841
LAGNLTFEXP_LAGN->PJM
CLTF
8.852
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.447
CPLELTFEXP_CPLE->PJM
CLTF
11.761
SIGELTFEXP_SIGE->PJM
CLTF
0.131
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.125
LGEELTFEXP_LGEE->PJM
CLTF
1.54
MECLTFEXP_MEC->PJM
CLTF
4.438

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.94 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:543.83
MW Contribution:
14.88
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:98.78 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:502.35
MW Contribution:
15.52
Bus #Bus NameTypeMW Contribution
970535AG2-341 GEN
50/50
Charging
6.366
3145543BTLEBRO
Solar/Wind Harmer
0.199
3145543BTLEBRO
Solar/Wind Harmer
0.199
3145543BTLEBRO
Solar/Wind Harmer
0.159
961671AG1-007 GEN
Solar/Wind Harmer
0.336
3145453TOT5
Solar/Wind Harmer
0.056
3145543BTLEBRO
Solar/Wind Harmer
0.199
315773AC2-141 GEN
Solar/Wind Helper
3.009
970919AG2-571 GEN
Solar/Wind Harmer
15.147
316118AC1-105 GEN
Solar/Wind Helper
3.992
970085AG2-068 GEN
Solar/Wind Harmer
8.786
957861AF2-080 GEN
Solar/Wind Harmer
2.209
316248AF1-058 C
Solar/Wind Helper
1.749
316123AC1-075 GEN
Solar/Wind Helper
4.393
316322AB2-045
Solar/Wind Helper
0.467
316129AC1-054 GEN
Solar/Wind Helper
1.247
972287SS25-0012
50/50
Charging
12.035
3145573BETHELC
Solar/Wind Harmer
0.179
315687AD1-152 GEN
Solar/Wind Helper
6.672
942461AE2-259 GEN
Solar/Wind Helper
3.41
970413AG2-270 GEN
50/50
Charging
32.533
970909AG2-566 GEN
50/50
Charging
4
316034AC1-036 C
Solar/Wind Helper
0.583
971629AH1-314 GEN
50/50
14.885
943811AF1-049 GEN
Solar/Wind Harmer
0
3146073TAR RVR
Solar/Wind Harmer
0.179
316003AC1-222 GEN
Solar/Wind Helper
5.199
316359AB2-059 GEN
Solar/Wind Harmer
0
3142053HEARTS
Solar/Wind Harmer
0.079
3146083TARBORO
Solar/Wind Harmer
0.179
316478AD1-087 GEN
Solar/Wind Helper
3.79
963041AG1-153 GEN
50/50
Charging
6.303
3146083TARBORO
Solar/Wind Harmer
0.179
3138543CONSLDL
Solar/Wind Harmer
0.11
316222AC1-221 GEN
Solar/Wind Helper
14.01
316486AD2-202 GEN
Solar/Wind Helper
1.11
316131AB2-060 GEN
Solar/Wind Helper
3.422
316263AC1-034 GEN
Solar/Wind Harmer
3
3145573BETHELC
Solar/Wind Harmer
0.179
3145603CNETO
Solar/Wind Harmer
0.037
316237AB2-079_GEN
Solar/Wind Helper
0.871
316238AB2-078_GEN
Solar/Wind Helper
0.871
316239AB2-077_GEN
Solar/Wind Helper
0.871
270030AE2-140 GEN
Solar/Wind Harmer
9.106
316283AC2-100 C
Solar/Wind Helper
13.194
970533AG2-339 GEN
50/50
Charging
6.339
3146233WITAKRS
Solar/Wind Harmer
0.644
970581AG2-369 GEN
Solar/Wind Harmer
7.556
970917AG2-570 GEN
Solar/Wind Harmer
35.142
3146233WITAKRS
Solar/Wind Harmer
0.388
313527AB2-043 GEN
Solar/Wind Helper
2.145
970417AG2-272 GEN
50/50
4.749
270069AE2-166 C O1
Solar/Wind Harmer
3.464
3145493TOT1
Solar/Wind Harmer
0.179
3146233WITAKRS
Solar/Wind Harmer
0.11
970087AG2-069 GEN
Solar/Wind Harmer
13.179
970223AG2-152 GEN
Solar/Wind Harmer
7.548
3145493TOT1
Solar/Wind Harmer
0.093
315785AD2-033 C
Solar/Wind Helper
4.863
900033ID_568986
External Queue
3.581075668334961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.544
LGEELTFEXP_LGEE->PJM
CLTF
1.613
MECLTFEXP_MEC->PJM
CLTF
4.615
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.766
CPLELTFEXP_CPLE->PJM
CLTF
11.877
SIGELTFEXP_SIGE->PJM
CLTF
0.136
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.634
NYPJM->LTFIMP_NY
CLTF
0.225
TVALTFEXP_TVA->PJM
CLTF
4.608
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
25.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.814
WECLTFEXP_WEC->PJM
CLTF
0.882
LAGNLTFEXP_LAGN->PJM
CLTF
9.066

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.01 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:625.53
MW Contribution:
8.26
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.01 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:513.66
MW Contribution:
8.21
Bus #Bus NameTypeMW Contribution
970535AG2-341 GEN
50/50
13.807
964791AG1-342 GEN
Solar/Wind Harmer
8.522
270457AD2-023 GEN
Solar/Wind Helper
1.553
3144303KENBRDG
Solar/Wind Harmer
0.7
946301AF1-294 GEN
Solar/Wind Harmer
3.349
962561AG1-105 GEN
Solar/Wind Harmer
20.602
970681AG2-440 GEN
Solar/Wind Harmer
15.189
970099AG2-077 GEN
Solar/Wind Harmer
47.882
970401AG2-262 GEN
Solar/Wind Harmer
2.604
964241AG1-285 GEN
Solar/Wind Harmer
25.358
970413AG2-270 GEN
50/50
65.188
970909AG2-566 GEN
50/50
8.966
971683AH1-343 GEN
Solar/Wind Harmer
15.809
970683AG2-441 GEN
Solar/Wind Harmer
22.885
3147043LAWRENC
50/50
1.588
971629AH1-314 GEN
50/50
Charging
8.256
3147133PAMPLIN
Solar/Wind Harmer
0.729
961791AG1-021 GEN
Solar/Wind Harmer
1.633
3147173SINAI
Solar/Wind Harmer
1.368
3147243WELCO
Solar/Wind Harmer
0.855
3147133PAMPLIN
Solar/Wind Harmer
2.863
270455AD2-022 GEN
Solar/Wind Helper
2.761
3146843MT LREL
Solar/Wind Harmer
1.185
3146843MT LREL
Solar/Wind Harmer
1.185
959311AF2-222 GEN
Solar/Wind Harmer
33.838
3147133PAMPLIN
Solar/Wind Harmer
0.912
958211AF2-115 GEN
Solar/Wind Harmer
2.042
970257AG2-171 GEN
Solar/Wind Harmer
10.499
972205AH1-687 GEN
50/50
5.169
315693AD1-088 GEN
Solar/Wind Harmer
17.585
971775AH1-396 GEN
Solar/Wind Harmer
2.081
971563AH1-280 GEN
Solar/Wind Harmer
1.633
957481AF2-042 GEN
Solar/Wind Harmer
119.705
970685AG2-442 GEN
Solar/Wind Harmer
27.587
970301AG2-198 GEN
Solar/Wind Harmer
13.867
315785AD2-033 C
Solar/Wind Harmer
0
970323AG2-213 GEN
Solar/Wind Harmer
13.998
VFTLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.78
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.721
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.163
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.348
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.398
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.277

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.38 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:566.4
MW Contribution:
8.26
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:93.04 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:473.16
MW Contribution:
8.21
Bus #Bus NameTypeMW Contribution
970535AG2-341 GEN
50/50
13.807
964791AG1-342 GEN
Solar/Wind Harmer
8.522
270457AD2-023 GEN
Solar/Wind Helper
1.553
971967AH1-528 GEN
Solar/Wind Harmer
70.841
962561AG1-105 GEN
Solar/Wind Harmer
20.602
970681AG2-440 GEN
Solar/Wind Harmer
15.189
970099AG2-077 GEN
Solar/Wind Harmer
47.882
970401AG2-262 GEN
Solar/Wind Harmer
2.604
964241AG1-285 GEN
Solar/Wind Harmer
25.358
970413AG2-270 GEN
50/50
65.188
970909AG2-566 GEN
50/50
8.966
971683AH1-343 GEN
Solar/Wind Harmer
15.809
970683AG2-441 GEN
Solar/Wind Harmer
22.885
3147043LAWRENC
50/50
1.588
971629AH1-314 GEN
50/50
Charging
8.256
970933AG2-581 GEN
Solar/Wind Harmer
35.326
3147173SINAI
Solar/Wind Harmer
1.368
3147243WELCO
Solar/Wind Harmer
0.855
270455AD2-022 GEN
Solar/Wind Helper
2.761
3146843MT LREL
Solar/Wind Harmer
1.185
3146843MT LREL
Solar/Wind Harmer
1.185
959311AF2-222 GEN
Solar/Wind Harmer
33.838
972205AH1-687 GEN
50/50
5.169
315693AD1-088 GEN
Solar/Wind Harmer
17.585
957481AF2-042 GEN
Solar/Wind Harmer
119.705
970685AG2-442 GEN
Solar/Wind Harmer
0.394
G-007ALTFEXP_G-007A->PJM
CMTX
0.163
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.348
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.398
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.277
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.721
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.78
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
304070 to 316281 ckt 1
316281 to 304070 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC108.19 %698.42B755.61
5.91
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC100.05 %698.42B698.74
5.91
GD2DVP
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC105.31 %687.14B723.62
5.92
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC108.49 %687.14B745.46
5.92
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC100.39 %687.14B689.83
5.92
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.09 %698.42B775.9
5.91
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC102.61 %698.42B716.67
5.91

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.19 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:755.61
MW Contribution:
5.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970535AG2-341 GEN
50/50
11.523
3146776BUCKING
Solar/Wind Harmer
0.785
3146776BUCKING
Solar/Wind Harmer
0.707
270494AE1-108_GEN
Solar/Wind Helper
5.532
316313AB2-026
Solar/Wind Helper
0.506
3146776BUCKING
Solar/Wind Harmer
7.851
3146776BUCKING
Solar/Wind Harmer
0.636
946301AF1-294 GEN
Solar/Wind Harmer
9.591
3144303KENBRDG
Solar/Wind Harmer
0.779
970681AG2-440 GEN
Solar/Wind Harmer
16.124
962561AG1-105 GEN
Solar/Wind Harmer
7.071
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
35.023
964241AG1-285 GEN
Solar/Wind Harmer
20.715
970909AG2-566 GEN
50/50
13.916
970413AG2-270 GEN
50/50
42.63
970683AG2-441 GEN
Solar/Wind Harmer
24.293
316258AE1-075 C
Solar/Wind Helper
0.455
315821AE2-092 GEN
Solar/Wind Helper
4.587
3147043LAWRENC
50/50
1.472
971629AH1-314 GEN
50/50
5.91
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.679
971845AH1-439 GEN
Solar/Wind Harmer
32.89
3147133PAMPLIN
Solar/Wind Harmer
3.88
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.848
959311AF2-222 GEN
Solar/Wind Harmer
33.506
316405AF2-144 C
50/50
Charging
1.03
970257AG2-171 GEN
Solar/Wind Harmer
11.691
971563AH1-280 GEN
Solar/Wind Harmer
4.679
971775AH1-396 GEN
Solar/Wind Harmer
2.317
315693AD1-088 GEN
Solar/Wind Harmer
15.284
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.524
970685AG2-442 GEN
Solar/Wind Harmer
31.319
957481AF2-042 GEN
Solar/Wind Harmer
87.558
970323AG2-213 GEN
Solar/Wind Harmer
15.588
315785AD2-033 C
Solar/Wind Harmer
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.222
WECLTFEXP_WEC->PJM
CLTF
0.245
LAGNLTFEXP_LAGN->PJM
CLTF
3.015
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.645
NYPJM->LTFIMP_NY
CLTF
0.539
TVALTFEXP_TVA->PJM
CLTF
1.544
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.51
LGEELTFEXP_LGEE->PJM
CLTF
0.458
MECLTFEXP_MEC->PJM
CLTF
1.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.588
CPLELTFEXP_CPLE->PJM
CLTF
4.408
SIGELTFEXP_SIGE->PJM
CLTF
0.04

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.05 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:698.74
MW Contribution:
5.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970535AG2-341 GEN
50/50
11.523
3146776BUCKING
Solar/Wind Harmer
0.785
3146776BUCKING
Solar/Wind Harmer
0.707
270494AE1-108_GEN
Solar/Wind Helper
5.532
316313AB2-026
Solar/Wind Helper
0.506
3146776BUCKING
Solar/Wind Harmer
7.851
3146776BUCKING
Solar/Wind Harmer
0.636
946301AF1-294 GEN
Solar/Wind Harmer
9.591
3144303KENBRDG
Solar/Wind Harmer
0.779
971967AH1-528 GEN
Solar/Wind Harmer
53.625
970681AG2-440 GEN
Solar/Wind Harmer
16.124
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
21.42
970909AG2-566 GEN
50/50
13.916
970413AG2-270 GEN
50/50
42.63
970683AG2-441 GEN
Solar/Wind Harmer
24.293
316258AE1-075 C
Solar/Wind Helper
0.455
3147043LAWRENC
50/50
1.472
971629AH1-314 GEN
50/50
5.91
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.679
970933AG2-581 GEN
Solar/Wind Harmer
26.742
971845AH1-439 GEN
Solar/Wind Harmer
32.89
3147133PAMPLIN
Solar/Wind Harmer
3.88
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.848
959311AF2-222 GEN
Solar/Wind Harmer
33.506
315821AE2-092 GEN
Solar/Wind Helper
4.587
316405AF2-144 C
50/50
Charging
1.03
970257AG2-171 GEN
Solar/Wind Harmer
11.691
971563AH1-280 GEN
Solar/Wind Harmer
4.679
971775AH1-396 GEN
Solar/Wind Harmer
2.317
315693AD1-088 GEN
Solar/Wind Harmer
15.284
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.524
970685AG2-442 GEN
Solar/Wind Harmer
31.319
957481AF2-042 GEN
Solar/Wind Harmer
53.549
970323AG2-213 GEN
Solar/Wind Harmer
15.588
315785AD2-033 C
Solar/Wind Harmer
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.222
WECLTFEXP_WEC->PJM
CLTF
0.245
LAGNLTFEXP_LAGN->PJM
CLTF
3.015
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.645
NYPJM->LTFIMP_NY
CLTF
0.539
TVALTFEXP_TVA->PJM
CLTF
1.544
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.51
LGEELTFEXP_LGEE->PJM
CLTF
0.458
MECLTFEXP_MEC->PJM
CLTF
1.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.588
CPLELTFEXP_CPLE->PJM
CLTF
4.408
SIGELTFEXP_SIGE->PJM
CLTF
0.04

Details for 6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:723.62
MW Contribution:
5.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970535AG2-341 GEN
50/50
11.53
964791AG1-342 GEN
Solar/Wind Harmer
4.604
270494AE1-108_GEN
Solar/Wind Helper
5.526
316313AB2-026
Solar/Wind Helper
0.505
946301AF1-294 GEN
Solar/Wind Harmer
9.595
3144303KENBRDG
Solar/Wind Harmer
0.78
970681AG2-440 GEN
Solar/Wind Harmer
16.129
962561AG1-105 GEN
Solar/Wind Harmer
11.811
316322AB2-045
Solar/Wind Helper
1.727
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
35.038
964241AG1-285 GEN
Solar/Wind Harmer
20.725
970401AG2-262 GEN
Solar/Wind Harmer
1.407
970909AG2-566 GEN
50/50
13.92
970413AG2-270 GEN
50/50
42.65
970683AG2-441 GEN
Solar/Wind Harmer
24.301
316258AE1-075 C
Solar/Wind Helper
0.455
315821AE2-092 GEN
Solar/Wind Helper
4.582
971065AG2-659 GEN
Solar/Wind Harmer
0.906
3147043LAWRENC
50/50
1.473
971629AH1-314 GEN
50/50
5.923
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.68
3147133PAMPLIN
Solar/Wind Harmer
3.882
3147173SINAI
Solar/Wind Harmer
0.56
3147243WELCO
Solar/Wind Harmer
0.35
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.85
959311AF2-222 GEN
Solar/Wind Harmer
33.519
3146843MT LREL
Solar/Wind Harmer
0.639
3146843MT LREL
Solar/Wind Harmer
0.639
316405AF2-144 C
50/50
Charging
1.029
970257AG2-171 GEN
Solar/Wind Harmer
11.696
971563AH1-280 GEN
Solar/Wind Harmer
4.68
971775AH1-396 GEN
Solar/Wind Harmer
2.318
315693AD1-088 GEN
Solar/Wind Harmer
15.29
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.53
970685AG2-442 GEN
Solar/Wind Harmer
31.33
957481AF2-042 GEN
Solar/Wind Harmer
87.595
970323AG2-213 GEN
Solar/Wind Harmer
15.594
315785AD2-033 C
Solar/Wind Harmer
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.661
LGEELTFEXP_LGEE->PJM
CLTF
0.466
MECLTFEXP_MEC->PJM
CLTF
1.387
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.622
CPLELTFEXP_CPLE->PJM
CLTF
4.42
SIGELTFEXP_SIGE->PJM
CLTF
0.041
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.809
NYPJM->LTFIMP_NY
CLTF
0.532
TVALTFEXP_TVA->PJM
CLTF
1.555
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.264
WECLTFEXP_WEC->PJM
CLTF
0.249
LAGNLTFEXP_LAGN->PJM
CLTF
3.038

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.49 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:745.46
MW Contribution:
5.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970535AG2-341 GEN
50/50
11.53
270494AE1-108_GEN
Solar/Wind Helper
5.526
316313AB2-026
Solar/Wind Helper
0.505
946301AF1-294 GEN
Solar/Wind Harmer
9.595
3144303KENBRDG
Solar/Wind Harmer
0.78
970681AG2-440 GEN
Solar/Wind Harmer
16.129
316322AB2-045
Solar/Wind Helper
1.727
962561AG1-105 GEN
Solar/Wind Harmer
10.411
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
35.038
964241AG1-285 GEN
Solar/Wind Harmer
20.725
970909AG2-566 GEN
50/50
13.92
970413AG2-270 GEN
50/50
42.65
970683AG2-441 GEN
Solar/Wind Harmer
24.301
316258AE1-075 C
Solar/Wind Helper
0.455
315821AE2-092 GEN
Solar/Wind Helper
4.582
3147043LAWRENC
50/50
1.473
971629AH1-314 GEN
50/50
5.923
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.68
971845AH1-439 GEN
Solar/Wind Harmer
32.896
3147133PAMPLIN
Solar/Wind Harmer
3.882
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.85
959311AF2-222 GEN
Solar/Wind Harmer
33.519
316405AF2-144 C
50/50
Charging
1.029
970257AG2-171 GEN
Solar/Wind Harmer
11.696
971563AH1-280 GEN
Solar/Wind Harmer
4.68
971775AH1-396 GEN
Solar/Wind Harmer
2.318
315693AD1-088 GEN
Solar/Wind Harmer
15.29
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.53
970685AG2-442 GEN
Solar/Wind Harmer
31.33
957481AF2-042 GEN
Solar/Wind Harmer
87.595
970323AG2-213 GEN
Solar/Wind Harmer
15.594
315785AD2-033 C
Solar/Wind Harmer
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.622
CPLELTFEXP_CPLE->PJM
CLTF
4.42
SIGELTFEXP_SIGE->PJM
CLTF
0.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.661
LGEELTFEXP_LGEE->PJM
CLTF
0.466
MECLTFEXP_MEC->PJM
CLTF
1.387
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.264
WECLTFEXP_WEC->PJM
CLTF
0.249
LAGNLTFEXP_LAGN->PJM
CLTF
3.038
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.809
NYPJM->LTFIMP_NY
CLTF
0.532
TVALTFEXP_TVA->PJM
CLTF
1.555
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.39 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:689.83
MW Contribution:
5.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970535AG2-341 GEN
50/50
11.53
270494AE1-108_GEN
Solar/Wind Helper
5.526
316313AB2-026
Solar/Wind Helper
0.505
946301AF1-294 GEN
Solar/Wind Harmer
9.595
3144303KENBRDG
Solar/Wind Harmer
0.78
971967AH1-528 GEN
Solar/Wind Harmer
53.648
970681AG2-440 GEN
Solar/Wind Harmer
16.129
316322AB2-045
Solar/Wind Helper
1.727
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
22.701
970909AG2-566 GEN
50/50
13.92
970413AG2-270 GEN
50/50
42.65
970683AG2-441 GEN
Solar/Wind Harmer
24.301
316258AE1-075 C
Solar/Wind Helper
0.455
3147043LAWRENC
50/50
1.473
971629AH1-314 GEN
50/50
5.923
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.68
970933AG2-581 GEN
Solar/Wind Harmer
26.753
971845AH1-439 GEN
Solar/Wind Harmer
32.896
3147133PAMPLIN
Solar/Wind Harmer
3.882
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.85
959311AF2-222 GEN
Solar/Wind Harmer
33.519
315821AE2-092 GEN
Solar/Wind Helper
4.582
316405AF2-144 C
50/50
Charging
1.029
970257AG2-171 GEN
Solar/Wind Harmer
11.696
971563AH1-280 GEN
Solar/Wind Harmer
4.68
971775AH1-396 GEN
Solar/Wind Harmer
2.318
315693AD1-088 GEN
Solar/Wind Harmer
15.29
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.53
970685AG2-442 GEN
Solar/Wind Harmer
31.33
957481AF2-042 GEN
Solar/Wind Harmer
56.753
970323AG2-213 GEN
Solar/Wind Harmer
15.594
315785AD2-033 C
Solar/Wind Harmer
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.622
CPLELTFEXP_CPLE->PJM
CLTF
4.42
SIGELTFEXP_SIGE->PJM
CLTF
0.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.661
LGEELTFEXP_LGEE->PJM
CLTF
0.466
MECLTFEXP_MEC->PJM
CLTF
1.387
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.264
WECLTFEXP_WEC->PJM
CLTF
0.249
LAGNLTFEXP_LAGN->PJM
CLTF
3.038
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.809
NYPJM->LTFIMP_NY
CLTF
0.532
TVALTFEXP_TVA->PJM
CLTF
1.555
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.09 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:775.9
MW Contribution:
5.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970535AG2-341 GEN
50/50
11.523
3146776BUCKING
Solar/Wind Harmer
0.785
3146776BUCKING
Solar/Wind Harmer
0.707
270494AE1-108_GEN
Solar/Wind Helper
5.532
316313AB2-026
Solar/Wind Helper
0.506
3146776BUCKING
Solar/Wind Harmer
7.851
3146776BUCKING
Solar/Wind Harmer
0.636
946301AF1-294 GEN
Solar/Wind Harmer
9.591
3144303KENBRDG
Solar/Wind Harmer
0.779
970681AG2-440 GEN
Solar/Wind Harmer
16.124
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
35.023
964241AG1-285 GEN
Solar/Wind Harmer
18.877
970909AG2-566 GEN
50/50
13.916
970413AG2-270 GEN
50/50
42.63
970683AG2-441 GEN
Solar/Wind Harmer
24.293
316258AE1-075 C
Solar/Wind Helper
0.455
3147043LAWRENC
50/50
1.472
971629AH1-314 GEN
50/50
5.91
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.679
971845AH1-439 GEN
Solar/Wind Harmer
32.89
3147133PAMPLIN
Solar/Wind Harmer
3.88
972003AH1-546 GEN
Solar/Wind Harmer
30.103
315821AE2-092 GEN
Solar/Wind Helper
4.587
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.848
959311AF2-222 GEN
Solar/Wind Harmer
33.506
316405AF2-144 C
50/50
Charging
1.03
970257AG2-171 GEN
Solar/Wind Harmer
11.691
971563AH1-280 GEN
Solar/Wind Harmer
4.679
971775AH1-396 GEN
Solar/Wind Harmer
2.317
315693AD1-088 GEN
Solar/Wind Harmer
15.284
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.524
970685AG2-442 GEN
Solar/Wind Harmer
31.319
957481AF2-042 GEN
Solar/Wind Harmer
87.558
970323AG2-213 GEN
Solar/Wind Harmer
15.588
315785AD2-033 C
Solar/Wind Harmer
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.645
NYPJM->LTFIMP_NY
CLTF
0.539
TVALTFEXP_TVA->PJM
CLTF
1.544
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.222
WECLTFEXP_WEC->PJM
CLTF
0.245
LAGNLTFEXP_LAGN->PJM
CLTF
3.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.588
CPLELTFEXP_CPLE->PJM
CLTF
4.408
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.51
LGEELTFEXP_LGEE->PJM
CLTF
0.458
MECLTFEXP_MEC->PJM
CLTF
1.369

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.61 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:716.67
MW Contribution:
5.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970535AG2-341 GEN
50/50
11.523
3146776BUCKING
Solar/Wind Harmer
0.785
3146776BUCKING
Solar/Wind Harmer
0.707
270494AE1-108_GEN
Solar/Wind Helper
5.532
316313AB2-026
Solar/Wind Helper
0.506
3146776BUCKING
Solar/Wind Harmer
7.851
3146776BUCKING
Solar/Wind Harmer
0.636
946301AF1-294 GEN
Solar/Wind Harmer
9.591
3144303KENBRDG
Solar/Wind Harmer
0.779
971967AH1-528 GEN
Solar/Wind Harmer
53.625
970681AG2-440 GEN
Solar/Wind Harmer
16.124
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
18.167
970909AG2-566 GEN
50/50
13.916
970413AG2-270 GEN
50/50
42.63
970683AG2-441 GEN
Solar/Wind Harmer
24.293
316258AE1-075 C
Solar/Wind Helper
0.455
3147043LAWRENC
50/50
1.472
971629AH1-314 GEN
50/50
5.91
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.679
970933AG2-581 GEN
Solar/Wind Harmer
26.742
971845AH1-439 GEN
Solar/Wind Harmer
32.89
3147133PAMPLIN
Solar/Wind Harmer
3.88
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.848
959311AF2-222 GEN
Solar/Wind Harmer
33.506
972003AH1-546 GEN
Solar/Wind Harmer
30.103
315821AE2-092 GEN
Solar/Wind Helper
4.587
316405AF2-144 C
50/50
Charging
1.03
970257AG2-171 GEN
Solar/Wind Harmer
11.691
971563AH1-280 GEN
Solar/Wind Harmer
4.679
971775AH1-396 GEN
Solar/Wind Harmer
2.317
315693AD1-088 GEN
Solar/Wind Harmer
15.284
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.524
970685AG2-442 GEN
Solar/Wind Harmer
31.319
957481AF2-042 GEN
Solar/Wind Harmer
45.419
970323AG2-213 GEN
Solar/Wind Harmer
15.588
315785AD2-033 C
Solar/Wind Harmer
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.645
NYPJM->LTFIMP_NY
CLTF
0.539
TVALTFEXP_TVA->PJM
CLTF
1.544
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.222
WECLTFEXP_WEC->PJM
CLTF
0.245
LAGNLTFEXP_LAGN->PJM
CLTF
3.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.588
CPLELTFEXP_CPLE->PJM
CLTF
4.408
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.51
LGEELTFEXP_LGEE->PJM
CLTF
0.458
MECLTFEXP_MEC->PJM
CLTF
1.369
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
314677 to 972002 ckt 1
314692 to 971844 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-152, AG2-272, AG2-518, AH1-098, AH1-144, AH1-145, AH1-269 and AH1-314 in PJM Transition Cycle 2, Cluster 24 are listed in Table 1. below. This report will cover the dynamic analysis of Cluster 24 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 24 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

Cluster 24 projects were dispatched for stability analysis according to the following scenarios:

       a)       Scenario 1: AH1-098 dispatched at full MFO injection at the POI with PV MW contribution maxed out and no/reduced MW contribution from BESS.

       b)       Scenario 2: AH1-098 dispatched at full MFO injection at the POI with BESS MW contribution maxed out, and no/reduced PV MW injection.

       c)       Scenario 3: AH1-098 dispatched at full MFO injection at the POI with PV and BESS MW contribution proportional to their capacity.

       d)       Scenario 4: AH1-098 dispatched to full capacity with PV and BESS MW injection maxed out.

 

This report describes a dynamic simulation analysis of TC2 Cluster 24 for dispatch Scenario 3 as part of the overall system impact study.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 24 projects have been dispatched online at maximum power output, with 1.01 pu voltage at the terminal bus.

 

Transition Cycle 2 Cluster 24 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2);

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);

       f)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 24 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 peak load case:

       a)       Cluster 24 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 24 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

The IPCMD and IQCMD states in the REGCA1 models of all units of Cluster 24 showed erratic behavior for some contingencies in which queue project has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

Tripping was observed for several contingencies (P4.081, P4.082, P5.39, and P5.48) under the initial study conditions. Upon updating the fault impedance values based on Aspen short circuit case, the tripping issues were resolved, and the system remained stable for these contingencies.

 

AH1-098 both Solar and BESS units tripped under several contingencies. Upon updating Vdip to 0.8 (Original value was 0.9) and Vup to 1.2 (Original value was 1.1) for both units resolved all tripping issue.

 

Fictitious frequency response at AH1-145 generator bus tripped the queue project for several contingencies (P1.073, P1.075 and P1.076). Therefore, the frequency relay pickup times for were set to 20 seconds to avoid fictitious frequency tripping of the unit.

 

AG2-272 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.15 (original value was 0) which resolved the slow reactive power response.

 

AH1-269 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.1 (original value was 0) which resolved the slow reactive power response.

 

AH1-314 generating units exhibited slow reactive power recovery within the 20 second simulation window for several contingencies. This issue did not cause instability in the system. The reactive power droop compensation was enabled and tuned by updating Kc to 0.1 (original value was 0) which resolved the slow reactive power response.

 

The active power for AG2-152 did not recover to the pre fault value for contingency P7.21 due inadequate reactive power response. The reactive power droop compensation gain Kc parameter was updated to 0.1 which resolved the active power recovery issue.

 

Smith Mountain generators showed positively damped oscillations which did not settle during the 20 second simulation window. The selected contingencies were run for 30 seconds, and the oscillatory signals achieved a flat response at the end of the 30 second simulation time period.

 

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 Cluster 24 Queues

Table 1: Transition Cycle 2 Cluster 24 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-152

Solar

AEP

131

Banister – Bearskin 138 kV

AG2-272

Battery

AEP

55

Berry Hill substation 138 kV

AG2-518

Battery

AEP

80

Tech Drive substation 138 kV

AH1-098

Solar/Battery

AEP

40

West Carroll – Wolf Glade 138 kV

AH1-144

Solar

AEP

70

Peter’s Mountain Substation 138 kV

AH1-145

Battery

AEP

80

Peter’s Mountain Substation 138 kV

AH1-269

Battery

AEP

50

Claytor substation 138 kV

AH1-314

Battery

AEP

100

East Danville substation 138 kV

 

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AH1-314 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Analysis Complete - No Issues

Steady State Voltage Analysis complete, no voltage issues identified.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVEngineering & Procurement
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVUnder Construction
AC1-098Dawson-South Justice 115kVIn Service
AC1-099Dawson-South Justice 115kVIn Service
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-161Septa 500kVIn Service
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVUnder Construction
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-166Stockton 138 kVSuspended
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-294Jetersville-Ponton 115 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVEngineering & Procurement
AF2-080Chinquapin-Everetts 230 kVWithdrawn
AF2-115Jetersville-Ponton 115 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVEngineering & Procurement
AF2-299Fields 34.5 kVEngineering & Procurement
AG1-007Tar River 12.5 kVWithdrawn
AG1-021Jetersville-Ponton 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVUnder Construction
AG1-106Thelma 230 kVWithdrawn
AG1-153Heritage 500 kVUnder Construction
AG1-285Chase City-Central 115 kVEngineering & Procurement
AG1-342Dryburg 115 kVEngineering & Procurement
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg - Nutbush 115 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-272Berry Hill 138 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-522Five Forks DP - Littleton DP 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings - Unity 500 kVActive
AG2-659Palmer Springs - Hawtree 115 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-396Gary 24.94 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-687Bear Garden 230kVActive
Z2-044Whitakers 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AH1-314 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)No Impact
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AH1-314 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn9221.0Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).Cost Allocated$24,329N/A
Dominionn9730.0Replace switches 29824 and 29825 at Bremo 230 kVCost Allocated$9,460N/A
Dominionn9728.0Replace wave trap 298 WT at Bremo 230 kVCost Allocated$4,730N/A
AEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Contingent$0N/A
Dominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Contingent$0N/A
Dominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Contingent$0N/A
Dominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Contingent$0N/A
Dominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Contingent$0N/A
Dominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Contingent$0N/A
Dominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Contingent$0N/A
Dominionn9220.0Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.Contingent$0N/A
Dominionn9217.0Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.Contingent$0N/A
Grand Total:$38,519

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9630.0
Type
Stability
TO
Dominion
RTEP ID / TO ID
n9630.0 / TC1-PH3-DOM-013
Title
Construct a new 230 kV line from the AG1-285 substation to the Finneywood 230 kV Substation. Expand AG1-285 substation and add two (2) new 230/115 kV transformers.
Description
n9630.0 addresses both stability and load flow violations. Construct a new 230 kV Line from the AG1-285 substation to the 230 kV Finneywood substation following the Line 1012 ROW for approximately 1.0 miles, then following the Line 556 ROW for approximately 3.5 miles to terminate at Finneywood. Expand the AG1-285 115 kV substation to accommodate two (2) new 115/230 kV transformers. Build a 230 kV substation at AG1-285 to connect the 115/230 kV transformers and the new 230 kV line to Finneywood. Expand the Finneywood 230 kV substation to accommodate the new line. The existing 1.0 miles of 115 kV from AG1-285 to Chase City does not need to be rebuilt to accommodate a new structure in the same right of way and therefore will be unchanged. The existing 3.5 miles of 500 kV towers from Structure 556/46 to Finneywood substation will need to be rebuilt as a double circuit tower to accommodate the new 230 kV line.
Total Cost ($USD)
$71,697,833
Discounted Total Cost ($USD)
$71,697,833
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Not Contingent

Note: AH1-314 contributes to the loading of an overloaded facility that is being mitigated by a network upgrade that was securitized by a prior Queue/Cycle. AH1-314 is not contingent on this network upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9221.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9221.0 / TC1-PH3-DOM-015-TC2
Title
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Description
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Total Cost ($USD)
$2,057,335
Discounted Total Cost ($USD)
$2,057,335
Allocated Cost ($USD)
$24,329
Time Estimate
38 to 39 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1035.0 MVA
LLB1091.0 MVA
LLC1201.0 MVA
SUMA900.0 MVA
SUMB964.0 MVA
SUMC1115.0 MVA
WINA1067.0 MVA
WINB1123.0 MVA
WINC1219.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07747.4 MW9.8%$201,196
AG2-17116.2 MW3.3%$68,920
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
29.2 MW6.0%$123,866
AG2-21321.6 MW4.5%$91,895
AG2-27029.7 MW6.1%$125,997
AG2-3417.8 MW1.6%$33,027
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
20.7 MW4.3%$87,777
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
31.2 MW6.4%$132,254
AG2-44240.5 MW8.4%$171,840
AG2-5229.9 MW2.0%$41,934
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
10.4 MW2.2%$44,277
AG2-58136.2 MW7.5%$153,578
AG2-65910.9 MW2.3%$46,485
AH1-3145.7 MW1.2%$24,329
AH1-3438.9 MW1.8%$37,956
AH1-43944.7 MW9.2%$189,912
AH1-52872.5 MW15.0%$307,970
AH1-54641.0 MW8.5%$174,120

System Reinforcement: n9730.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9730.0 / TC2-PH1-DOM-2077
Title
Replace switches 29824 and 29825 at Bremo 230 kV
Description
Replace switches 29824 and 29825 at Bremo 230 kV
Total Cost ($USD)
$800,000
Discounted Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$9,460
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1145.0 MVA
LLB1183.0 MVA
LLC1201.0 MVA
SUMA1050.0 MVA
SUMB1094.0 MVA
SUMC1115.0 MVA
WINA1164.0 MVA
WINB1201.0 MVA
WINC1219.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07747.4 MW9.8%$78,236
AG2-17116.2 MW3.3%$26,800
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
29.2 MW6.0%$48,166
AG2-21321.6 MW4.5%$35,734
AG2-27029.7 MW6.1%$48,994
AG2-3417.8 MW1.6%$12,843
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
20.7 MW4.3%$34,133
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
31.2 MW6.4%$51,427
AG2-44240.5 MW8.4%$66,821
AG2-5229.9 MW2.0%$16,306
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
10.4 MW2.2%$17,217
AG2-58136.2 MW7.5%$59,719
AG2-65910.9 MW2.3%$18,076
AH1-3145.7 MW1.2%$9,460
AH1-3438.9 MW1.8%$14,759
AH1-43944.7 MW9.2%$73,848
AH1-52872.5 MW15.0%$119,755
AH1-54641.0 MW8.5%$67,707

System Reinforcement: n9728.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9728.0 / TC2-PH1-DOM-2076
Title
Replace wave trap 298 WT at Bremo 230 kV
Description
Replace wave trap 298 WT at Bremo 230 kV
Total Cost ($USD)
$400,000
Discounted Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$4,730
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA956.0 MVA
LLB1011.0 MVA
LLC1091.0 MVA
SUMA812.0 MVA
SUMB876.0 MVA
SUMC964.0 MVA
WINA979.0 MVA
WINB1043.0 MVA
WINC1115.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07747.4 MW9.8%$39,118
AG2-17116.2 MW3.3%$13,400
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
29.2 MW6.0%$24,083
AG2-21321.6 MW4.5%$17,867
AG2-27029.7 MW6.1%$24,497
AG2-3417.8 MW1.6%$6,421
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
20.7 MW4.3%$17,066
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
31.2 MW6.4%$25,714
AG2-44240.5 MW8.4%$33,410
AG2-5229.9 MW2.0%$8,153
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
10.4 MW2.2%$8,609
AG2-58136.2 MW7.5%$29,860
AG2-65910.9 MW2.3%$9,038
AH1-3145.7 MW1.2%$4,730
AH1-3438.9 MW1.8%$7,380
AH1-43944.7 MW9.2%$36,924
AH1-52872.5 MW15.0%$59,878
AH1-54641.0 MW8.5%$33,854

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-314 may not presently have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-AE2-094 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FINNEYWOOD-AG2-198 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-3
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 593_SRT-A
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 587_SRT-A-2
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 511T556_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P4-2: 587T591_SRT-S
No new ratings for this Flowgate.
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Discounted Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-314 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AH1-314 may not have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1553.0 MVA
LLB1634.0 MVA
LLC1879.0 MVA
SUMA1350.0 MVA
SUMB1446.0 MVA
SUMC1756.0 MVA
WINA1598.0 MVA
WINB1648.0 MVA
WINC1895.0 MVA
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA940.0 MVA
LLB987.0 MVA
LLC1091.0 MVA
SUMA812.0 MVA
SUMB868.0 MVA
SUMC964.0 MVA
WINA964.0 MVA
WINB1011.0 MVA
WINC1115.0 MVA

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Discounted Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-314 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AH1-314 may not have cost responsibility for this upgrade, AH1-314 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AH1-314 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BUCKING-AH1-439 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1553.0 MVA
LLB1634.0 MVA
LLC1879.0 MVA
SUMA1350.0 MVA
SUMB1446.0 MVA
SUMC1756.0 MVA
WINA1598.0 MVA
WINB1648.0 MVA
WINC1895.0 MVA
6FARMVIL-AH1-439 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA940.0 MVA
LLB987.0 MVA
LLC1163.0 MVA
SUMA812.0 MVA
SUMB868.0 MVA
SUMC1123.0 MVA
WINA964.0 MVA
WINB1011.0 MVA
WINC1171.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
DVP Rating: 961/961/1106 MVA
Description
DVP Rating: 961/961/1106 MVA
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A961.0 MVA
(All)B961.0 MVA
(All)C1106.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-314


AH1-314 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowAEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Topology-0.0%Contingent$0
Load FlowDominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Topology-0.0%Contingent$0
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Topology-0.0%Contingent$0
Load FlowDominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Topology-0.0%Contingent$0
Load FlowDominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Topology-0.0%Contingent$0
Load FlowDominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Topology-0.0%Contingent$0
Load FlowDominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-314 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-314 One Line Diagram

AH1-314 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.