AH1-341 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:12

ESS-H445 3B 138kv

96.6 MW Capacity / 150.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is ibV Energy Partners LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Commonwealth Edison Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request meets the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposits refunded. See Readiness Deposit calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $90,163,185 $38,165,900 = 2.36 AND ( $90,163,185 - $38,165,900 ) 150.0 = $346,649 per MW

General

The Project Developer has proposed a Solar generating facility located in the Commonwealth Edison Company zone — Ogle County, Illinois. The installed facilities will have a total capability of 150.0 MW with 96.6 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-341
Project Name:
ESS-H445 3B 138kv
Project Developer Name:
ibV Energy Partners LLC
State:
Illinois
County:
Ogle
Transmission Owner:
Commonwealth Edison Company
MFO:
150.0
MWE:
150.0
MWC:
96.6
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-341 will interconnect on the Commonwealth Edison Company  transmission system by tapping the Stillman - Dixon 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-341 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-341Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$461,623$0$0
Other Scope$443,478$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$29,114,498$29,114,498$29,114,498
Network Upgrades$6,561,221$6,561,221$6,561,221
System Reliability Network Upgrades
Steady State Thermal & Voltage$54,393,063$54,393,063$54,393,063
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$60,305$0$60,305
AFS - Non-PJM Violations$34,098$0$34,098
Total$91,068,286$90,068,782$90,163,185

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-341

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-341
Project ID: AH1-341
20% of cost allocation for Phase II Network Upgrades:(A) $18,013,756
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $3,812,195
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $14,201,561
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

If your project relies on Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and/or Network Upgrades that will be constructed by another New Service Request and the other New Service Request withdraws, the scope and costs will be allocated to your project.

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Cut into existing L10721 138 Kv transmission line between str 73 and 76 to tie into TSS920 Flagg rd substation via a break in to new line L92002

$3,393,671$870,248$482,757$49,103$4,795,779$4,795,779
(Pending)

Relay and communication work at TSS 107 REMOTE END

$241,716$104,196$34,385$5,879$386,176$386,176
(Pending)

Install approx 3 miles of fiber

$564,171$297,518$80,254$16,787$958,730$958,730
(Pending)

Relay and communication work at TSS176 -REMOTE END.

$260,636$116,264$37,076$6,560$420,536$420,536
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install new AMI and Meter - TSS920

$92,035$320,279$13,092$18,072$443,478$443,478
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Build a new breaker and a half substation TSS 920 Flagg Rd along the existing ComEd 138 KV line L10721

$16,400,164$9,826,899$2,332,957$554,478$29,114,498$29,114,498
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install one 138 KV dead end str and 138 KV line conductor from the dead end str to the point of interconnection

$140,893$284,628$20,042$16,060$461,623$461,623
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Cut into existing L10721 138 Kv transmission line between str 73 and 76 to tie into TSS920 Flagg rd substation via a break in to new line L92002

$3,393,671$870,248$482,757$49,103$4,795,779$4,795,779
(Pending)

Relay and communication work at TSS 107 REMOTE END

$241,716$104,196$34,385$5,879$386,176$386,176
(Pending)

Install approx 3 miles of fiber

$564,171$297,518$80,254$16,787$958,730$958,730
(Pending)

Relay and communication work at TSS176 -REMOTE END.

$260,636$116,264$37,076$6,560$420,536$420,536
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Option to build oversight for TOIF

$73,136$0$13,915$0$87,051$87,051
(Pending)

Option to build oversight for Stand-Alone Network Upgrade to build new TSS 920 Flagg Rd.

$1,908,544$760,393$363,127$42,265$3,074,329$3,074,329
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$36,580,820$36,580,820
Developer Build Option$9,722,601$9,722,601

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 1 to 48 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Notes on Cost Estimate:

  1. These estimates are order-of-magnitude estimates of the costs that ComEd would bill to the Project Developer for this interconnection. These estimates are based on a one-line electrical diagram of the project and the information provided by the Project Developer.
  2. There were no site visits performed for these estimates. There may be costs related to specific site related issues that are not identified in these estimates. The site reviews will be performed during the Facilities Study or during detailed engineering.
  3. These estimates are not a guarantee of the maximum amount payable by the Project Developer and the actual costs of ComEd's work may differ significantly from these estimates. The Project Developer will be responsible for paying actual costs of ComEd's work in accordance with the PJM Open Access Transmission Tariff.
  4. The Project Developer is responsible for all engineering, procurement, testing and construction of all equipment on the Project Developer’s side of the Point of Change in Ownership.

 

 

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. ComEd interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-341 was evaluated as a 150.0 MW (96.6 MW Capacity) injection in the ComEd area.

AH1-341 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
14.37
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC103.15 %5523.0B5696.85
14.37
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
14.37
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.46
14.37
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
BreakerAC103.14 %5523.0B5696.16
14.37
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC102.09 %5523.0B5638.63
10.76
GD2AEP
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC102.08 %5523.0B5637.94
10.76
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#GREENTOWN-TEDDY_SRT-A_SENS
BreakerAC103.08 %5001.0B5155.25
23.47
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#2979_05DUMONT 765_B2_SRT-A
BreakerAC101.9 %5001.0B5096.22
25.27
GD2AEP
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
TowerAC100.24 %5523.0B5536.23
40.0
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
14.37
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
BreakerAC124.63 %4571.0B5696.85
14.37
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
14.37
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.46
14.37
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
BreakerAC124.62 %4571.0B5696.16
14.37
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
SingleAC123.36 %4571.0B5638.63
10.76
GD2AEP
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
SingleAC123.34 %4571.0B5637.94
10.76
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC104.85 %4142.0B4342.78
13.9
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC104.04 %4142.0B4309.27
15.66
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.48 %4571.0B4638.62
15.0
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
SingleAC101.94 %4571.0B4659.48
15.0
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#GREENTOWN-TEDDY_SRT-A_SENS
BreakerAC130.7 %4142.0B5413.79
24.64
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS
SingleAC120.92 %4142.0B5008.41
18.45
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC114.91 %4142.0B4759.65
21.98
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#2979_05DUMONT 765_B2_SRT-A
BreakerAC114.85 %4142.0B4756.98
23.86
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#TEDDY MARY_SRT-A_SENS
BreakerAC110.67 %4142.0B4583.78
21.73
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_05MARYSV 765_C2_SRT-A_SENS
BreakerAC110.05 %4142.0B4558.43
21.74
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC109.64 %4142.0B4541.17
21.18
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC108.44 %4142.0B4491.48
21.23
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC107.56 %4142.0B4455.3
21.52
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P7-1_#11010___SRT-A
TowerAC103.94 %4142.0B4305.0
20.88
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#9287_1679_SRT-A
SingleAC103.12 %4142.0B4271.28
17.87
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P7-1_#11087___SRT-A-1
TowerAC103.11 %4142.0B4270.92
20.05
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC100.58 %4142.0B4166.12
19.43
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
BusAC100.54 %4142.0B4164.42
19.68
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC146.02 %971.0B1417.86
11.87
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC146.02 %971.0B1417.85
11.87
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC144.13 %971.0B1399.5
11.76
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC141.33 %971.0B1372.34
11.59
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC111.37 %971.0B1081.42
8.89
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC111.37 %971.0B1081.39
8.89
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
BreakerAC101.51 %971.0B985.66
8.39
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#8805_05OLIVE 345_D_SRT-A-1
BreakerAC101.08 %971.0B981.49
8.4
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC143.68 %1841.0B2645.11
17.03
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC143.68 %1841.0B2645.11
17.03
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC137.76 %1841.0B2536.22
16.42
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC134.79 %1841.0B2481.49
16.16
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC118.61 %1841.0B2183.54
12.76
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC118.6 %1841.0B2183.51
12.76
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P7-1_#11009___SRT-A-1
TowerAC115.04 %1841.0B2117.86
12.9
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P7-1_#11009___SRT-A-2
TowerAC113.57 %1841.0B2090.79
12.91
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#18494_05LARRISN DR 345_CB1_SRT-A_SENS
BreakerAC105.62 %1841.0B1944.43
10.28
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A_SENS
BusAC105.62 %1841.0B1944.43
10.28
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC101.87 %1841.0B1875.38
11.27
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Base Case
SingleAC100.17 %1385.0A1387.41
7.09
GD2AEP/NIPS
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC133.26 %1046.0B1393.9
11.62
GD2AEP/NIPS
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC133.26 %1046.0B1393.9
11.62
GD2AEP/NIPS
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC131.6 %1046.0B1376.55
11.51
GD2AEP/NIPS
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC128.95 %1046.0B1348.78
11.35
GD2ATSI/METC
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-022T_SRT-A_SENS
TowerAC116.55 %1793.0B2089.8
7.02
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC112.69 %1635.0B1842.48
10.28
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC110.19 %1635.0B1801.56
10.09
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC109.34 %1635.0B1787.63
9.99
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC109.34 %1635.0B1787.63
9.99
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
AEP_P4_#3128_05EUGENE 345_A2_SRT-A
BreakerAC108.74 %1635.0B1777.86
9.3
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
BusAC107.29 %1635.0B1754.14
9.41
GD2CE
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC108.25 %2107.0STE2280.86
8.74
GD2CE
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
COMED_P4_023-65-BT2-3___SRT-A
BreakerAC108.17 %2107.0STE2279.11
8.74
GD2CE
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
COMED_P4_023-65-BT4-5___SRT-A
BreakerAC108.12 %2107.0STE2278.11
8.74
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P4_006-45-BT3-8___SRT-A
BreakerAC116.83 %1837.0STE2146.19
22.77
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P4_006-45-BT3-4___SRT-A
BreakerAC116.53 %1837.0STE2140.62
22.58
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P4-6_006-345-BT78___SRT-A
BreakerAC115.34 %1837.0STE2118.87
22.76
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Base Case
SingleAC114.81 %1334.0A1531.63
14.65
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P4_144-45-BT5-8___SRT-A
BreakerAC113.84 %1837.0STE2091.24
22.5
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P4_144-45-BT7-8___SRT-A
BreakerAC112.78 %1837.0STE2071.79
22.51
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P2-2_154_LV-345R__3_SRT-A
BusAC100.01 %1837.0STE1837.27
19.78
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P4_144-45-BT7-8___SRT-A
BreakerAC111.49 %1568.0STE1748.1
21.45
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P4_144-45-BT5-8___SRT-A
BreakerAC111.3 %1568.0STE1745.18
21.36
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P4-6_006-345-BT78___SRT-A
BreakerAC109.88 %1568.0STE1722.95
21.21
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P4_111-45-TR81____SRT-A
BreakerAC102.15 %1568.0STE1601.72
19.58
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P4_111-45-L11124__SRT-A
BreakerAC102.15 %1568.0STE1601.72
19.58
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P2-2_111_EJ-345B__1_SRT-A
BusAC102.15 %1568.0STE1601.72
19.58
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P1-2_345-L0626__B-R_SRT-A
SingleAC102.07 %1568.0STE1600.48
16.04
GD2AEP
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC154.08 %1046.0B1611.63
11.56
GD2AEP
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC154.07 %1046.0B1611.62
11.56
GD2AEP
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC152.46 %1046.0B1594.7
11.45
GD2AEP
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC149.78 %1046.0B1566.69
11.29
GD2AEP
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC111.8 %1046.0B1169.44
8.66
GD2AEP
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC111.79 %1046.0B1169.28
8.66
GD2AEP
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
BreakerAC110.57 %1046.0B1156.57
8.1
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC111.3 %1441.0B1603.8
10.83
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC111.29 %1441.0B1603.7
10.83
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC110.45 %1441.0B1591.55
10.75
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC109.53 %1441.0B1578.35
10.67
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
TowerAC108.38 %1441.0B1561.79
10.12
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
TowerAC106.24 %1441.0B1530.88
10.12
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
TowerAC116.9 %1591.0B1859.87
13.39
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
TowerAC114.54 %1591.0B1822.27
13.39
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC109.71 %1591.0B1745.45
13.47
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC109.71 %1591.0B1745.44
13.47
GD2CE
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
COMED_P4_144-45-BT7-8___SRT-A
BreakerAC107.42 %1568.0STE1684.35
21.45
GD2CE
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
COMED_P4_144-45-BT5-8___SRT-A
BreakerAC107.28 %1568.0STE1682.12
21.36
GD2CE
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
COMED_P4-6_006-345-BT78___SRT-A
BreakerAC105.77 %1568.0STE1658.52
21.21
GD2CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC114.12 %2112.0B2410.19
16.39
GD2CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC114.12 %2112.0B2410.15
16.39
GD2CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC113.41 %2112.0B2395.13
16.28
GD2CE/NIPS
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC112.45 %2112.0B2374.91
16.16
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Base Case
SingleAC105.07 %1201.0A1261.88
6.47
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P4-6_111-345-R______SRT-A
BreakerAC102.29 %1568.0STE1603.94
10.39
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P2-2_111_EJ-345R__3_SRT-A
BusAC101.11 %1568.0STE1585.33
8.89
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P4_120-45-L12002__SRT-A
BreakerAC101.04 %1568.0STE1584.26
9.52
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P4_111-45-L11120__SRT-A
BreakerAC100.85 %1568.0STE1581.28
8.89
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P4_120-45-L10322__SRT-A
BreakerAC100.68 %1568.0STE1578.61
9.51
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P2-2_120_LO-345R__2_SRT-A
BusAC100.68 %1568.0STE1578.61
9.51
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P4_120-45-L11120__SRT-A
BreakerAC100.67 %1568.0STE1578.44
9.51
GD2CE
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
COMED_P4-6_111-345-B______SRT-A
BreakerAC103.37 %455.0STE470.34
11.87
GD2CE
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
COMED_P4_111-45-TR81____SRT-A
BreakerAC100.42 %455.0STE456.9
11.98
GD2CE
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
COMED_P4_111-45-L11124__SRT-A
BreakerAC100.42 %455.0STE456.9
11.98
GD2CE
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
COMED_P2-2_111_EJ-345B__1_SRT-A
BusAC100.42 %455.0STE456.9
11.98
GD2CE/NIPS
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC111.02 %2004.0B2224.79
15.24
GD2CE/NIPS
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC111.02 %2004.0B2224.77
15.24
GD2CE/NIPS
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC110.33 %2004.0B2210.98
15.14
GD2CE/NIPS
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC109.39 %2004.0B2192.13
15.02
GD2CE
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-2
TowerAC106.6 %381.0ALDR406.13
10.24
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
TowerAC125.66 %4460.0B5604.3
40.0
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
TowerAC123.83 %4460.0B5522.64
40.0
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
BreakerAC114.05 %4460.0B5086.61
36.48
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
AEP_P4_#2976_05DUMONT 345_F_SRT-A
BreakerAC113.94 %4460.0B5081.51
36.43
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A_SENS
BusAC109.68 %4460.0B4891.59
34.62
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
BusAC108.96 %4460.0B4859.78
34.88

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
14.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
14.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
14.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
14.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.14 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
14.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
10.76
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJA-05CLOVRD 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.08 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
10.76
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#GREENTOWN-TEDDY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#GREENTOWN-TEDDY_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.08 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5155.25
MW Contribution:
23.47
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
12.188
274771LINCOLN ;2U
50/50
12.188
970349AG2-230 GEN
Solar/Wind Harmer
27.999
276897AD1-100 C
Solar/Wind Harmer
80.13
958011AF2-095 GEN
Solar/Wind Harmer
24.681
274888KELLY CRK;1U
Solar/Wind Harmer
10.114
276776AD2-060 GEN
Solar/Wind Harmer
0.717
970941AG2-585 GEN
Solar/Wind Harmer
9.427
965681AG1-436 GEN
Solar/Wind Harmer
21.402
965791AG1-447 GEN
Solar/Wind Harmer
10.95
274674JOLIET 9 ;6U
Adder
26.158
274805UNIV PK N;1U
Adder
8.498
274808UNIV PK N;4U
Adder
8.443
276893AG1-478 C
Solar/Wind Harmer
0.742
274695ROCKY RD ;2P
Adder
18.549
274693ROCKY RD ;1P
Adder
18.367
274697ROCKY RD ;3P
Adder
5.039
274696ROCKY RD ;4P
Adder
18.986
274683WAUKEGAN ;8U
Adder
34.893
274683WAUKEGAN ;8U
Adder
29.413
962691AG1-118 GEN
Solar/Wind Harmer
49.559
960751AF2-366 GEN
Solar/Wind Harmer
4.723
958481AF2-142 GEN
Solar/Wind Harmer
24.651
276901AD2-066 C O1
Solar/Wind Harmer
5.67
958491AF2-143 GEN
Solar/Wind Harmer
24.25
971341AH1-150 GEN
Solar/Wind Harmer
32.052
971343AH1-151 GEN
Solar/Wind Harmer
32.052
972235AH1-702 GEN1
Adder
4.006
972236AH1-702 GEN2
Adder
3.484
276872AE1-163_GEN1
Solar/Wind Harmer
10.607
276876AE1-163_GEN2
Solar/Wind Harmer
10.607
938861AE1-114 GEN
Solar/Wind Harmer
12.821
274764LEE CO EC;5U
Adder
14.508
274765LEE CO EC;6U
Adder
14.508
274762LEE CO EC;3U
Adder
14.473
274763LEE CO EC;4U
Adder
14.337
276158O29GEN2
Solar/Wind Harmer
7.629
276157O29GEN1
Solar/Wind Harmer
5.801
270535AF1-215 GEN1
Solar/Wind Harmer
6.889
24344105CKG2
50/50
17.156
274773LINCOLN ;4U
50/50
12.188
274774LINCOLN ;5U
50/50
12.188
972207SS24-0001
Solar/Wind Harmer
40.838
941551AE2-152 GEN
Solar/Wind Harmer
7.823
274723RIVER EC ;12
Adder
30.543
274871GR RIDGE ;2U
Solar/Wind Harmer
13.101
274847GR RIDGE ;BU
Solar/Wind Harmer
8.615
274802UNIV PARK;5U
Adder
9.93
274676JOLIET 29;8U
Adder
52.221
274674JOLIET 9 ;6U
Adder
26.158
274732ELWOOD EC;7P
Adder
27.869
274745AC1-111 GEN9
Adder
9.474
274812UNIV PK N;8U
Adder
8.48
274751CRETE EC ;1U
Adder
8.214
274754CRETE EC ;4U
Adder
8.214
274682WAUKEGAN ;7U
Adder
29.811
274828WAUKEGAN ;BP
Adder
18.29
962781AG1-127 GEN
Solar/Wind Harmer
15.656
276694AA1-018 GEN2
Solar/Wind Harmer
10.37
276691AA1-018 GEN1
Solar/Wind Harmer
1.239
274861TOP CROP ;1U
Solar/Wind Harmer
9.944
274872LEEDK;1U
Solar/Wind Harmer
13.471
939401AE1-172 GEN
Solar/Wind Harmer
22.743
276805AD2-038 GEN
Solar/Wind Harmer
8.29
971997AH1-543 GEN
Solar/Wind Harmer
25.393
276882AE2-255 GEN
Solar/Wind Harmer
5.43
957471AF2-041 GEN
Solar/Wind Harmer
48.078
959081AF2-199 GEN
Solar/Wind Harmer
16.026
971067AG2-660 GEN
Solar/Wind Harmer
3.727
274822ROCKFORD ;11
Adder
31.298
970819AG2-516 GEN
Solar/Wind Harmer
18.984
970373AG2-245 GEN
Solar/Wind Harmer
32.909
274858EASY ROAD;U2
Solar/Wind Harmer
7.453
274761LEE CO EC;2U
Adder
14.473
274766LEE CO EC;7U
Adder
14.303
970569AG2-363 GEN
Solar/Wind Harmer
46.62
276708O09 GEN2
Solar/Wind Harmer
5.447
270055AF2-134 C O1
Solar/Wind Harmer
4.593
276646AC1-214 GEN2
Solar/Wind Harmer
2.018
274848CAMPGROVE;RU
Solar/Wind Harmer
9.597
958381AF2-132 GEN
Solar/Wind Harmer
13.325
964861AG1-349 GEN
Solar/Wind Harmer
11.505
971917AH1-482 GEN
Solar/Wind Harmer
13.275
276655WTG1_EQ
Solar/Wind Harmer
12.676
276656WTG2_EQ
Solar/Wind Harmer
1.678
939741AE1-205 GEN
Solar/Wind Harmer
29.048
24441205WTRV SLR C
Solar/Wind Harmer
0.195
270449AD2-020 GEN
Solar/Wind Harmer
3.995
943021AE2-325 GEN
Solar/Wind Harmer
5.193
957891AF2-083 GEN
Solar/Wind Harmer
21.35
24639705ELKHART HY
Adder
0.181
274775LINCOLN ;6U
50/50
12.188
274776LINCOLN ;7U
50/50
12.188
274777LINCOLN ;8U
50/50
12.188
274660LASCO STA;1U
50/50
12.495
274661LASCO STA;2U
50/50
9.673
972228AH1-698 GEN2
Adder
6.377
972227AH1-698 GEN1
Adder
4.49
960591AF2-350 GEN
Solar/Wind Harmer
17.14
960681AF2-359 GEN
Solar/Wind Harmer
6.469
274827FISK ;RP
Adder
13.247
274800UNIV PARK;3U
Adder
9.951
274801UNIV PARK;4U
Adder
9.951
970833AG2-524 GEN
Solar/Wind Harmer
14.877
970833AG2-524 GEN
Solar/Wind Harmer
6.92
972037AH1-567 GEN1
Adder
0.312
274675JOLIET 29;7U
Adder
52.223
274675JOLIET 29;7U
Adder
50.358
274687WILL CNTY;4U
Adder
47.54
274687WILL CNTY;4U
Adder
47.54
274731ELWOOD EC;2P
Adder
27.869
274733ELWOOD EC;3P
Adder
27.869
274735ELWOOD EC;4P
Adder
27.869
274728ELWOOD EC;5P
Adder
27.869
274744AC1-111 GEN8
Adder
9.474
274746AC1-111 G10
Adder
9.474
276893AG1-478 C
Solar/Wind Harmer
0.931
971675AH1-338 GEN
Solar/Wind Harmer
29.13
276861AD2-134 GEN
Solar/Wind Harmer
2.888
276863AD2-134 GEN
Solar/Wind Harmer
2.888
971411AH1-196 GEN
Solar/Wind Harmer
24.251
970073AG2-061 GEN
Solar/Wind Harmer
3.76
971171AH1-044 GEN
Solar/Wind Harmer
32.052
274823ROCKFORD ;21
Adder
31.071
274863CRW1-WTG
Solar/Wind Harmer
8.879
274864CRW2-WTG
Solar/Wind Harmer
8.879
270526AF1-158 GEN
Solar/Wind Harmer
7.164
276889AE2-281 GEN
Solar/Wind Harmer
3.03
274856ECOGROVE ;U1
Solar/Wind Harmer
5.322
276611AD2-172 GEN
Solar/Wind Harmer
4.037
276612AE2-035 GEN
Solar/Wind Harmer
4.037
971681AH1-341 GEN
Solar/Wind Harmer
23.47
926823AC1-168 GEN
Solar/Wind Harmer
6.697
970169AG2-114 GEN
Solar/Wind Harmer
15.473
972267AH1-718 GEN
Adder
6.385
276741O09 GEN1
Solar/Wind Harmer
5.447
274877BISHOP HL;1U
Solar/Wind Harmer
5.049
971771AH1-392 GEN
Solar/Wind Harmer
13.399
946321AF1-296 GEN
Solar/Wind Harmer
15.338
276726Z2-087_GEN
Solar/Wind Harmer
11.484
959341AF2-225 GEN
Solar/Wind Harmer
21.786
958391AF2-133 GEN
Solar/Wind Harmer
13.088
944161AF1-084 GEN
Solar/Wind Harmer
3.159
959141AF2-205 GEN
Solar/Wind Harmer
8.608
274853TWINGROVE;U1
Solar/Wind Harmer
10.168
274854TWINGROVE;U2
Solar/Wind Harmer
8.611
274772LINCOLN ;3U
50/50
12.188
972259AH1-714 GEN
50/50
35.18
971347AH1-153 GEN
Solar/Wind Harmer
9.333
970707AG2-453 GEN
Solar/Wind Harmer
49.335
939351AE1-166 GEN
Solar/Wind Harmer
10.23
276164X3-005 C
Solar/Wind Harmer
1.206
274887GEN-1.85
Solar/Wind Harmer
9.132
276772AC2-154 GEN
Solar/Wind Harmer
4.783
276843GEN-1.7
Solar/Wind Harmer
0.983
276806AD2-047 C O1
Solar/Wind Harmer
18.336
274826FISK ;BP
Adder
18.691
972038AH1-567 GEN2
Adder
0.623
274724RIVER EC ;11
Adder
30.22
943121AE2-341 GEN
Solar/Wind Harmer
25.561
943591AF1-030 GEN
Solar/Wind Harmer
17.041
274803UNIV PARK;6U
Adder
9.93
274676JOLIET 29;8U
Adder
50.356
274729ELWOOD EC;1P
Adder
27.869
274730ELWOOD EC;6P
Adder
27.869
274734ELWOOD EC;8P
Adder
27.869
274736ELWOOD EC;9P
Adder
27.869
274814UNIV PK N;0U
Adder
8.554
274807UNIV PK N;3U
Adder
8.536
274811UNIV PK N;7U
Adder
8.48
972231SS25-0005
Solar/Wind Harmer
15.948
972181SS23-001
Solar/Wind Harmer
9.968
274752CRETE EC ;2U
Adder
8.214
274753CRETE EC ;3U
Adder
8.214
274682WAUKEGAN ;7U
Adder
29.811
274862TOP CROP ;2U
Solar/Wind Harmer
8.303
276799AD1-013 GEN
Solar/Wind Harmer
3.578
946671AF1-331 GEN
Solar/Wind Harmer
0.678
274855GSG-6 ;RU
Solar/Wind Harmer
5.972
274850MENDOTA H;RU
Solar/Wind Harmer
4.152
276602WESTBROOK C
Solar/Wind Harmer
3.438
276868AE1-113 GEN
Solar/Wind Harmer
16.291
274879MINONK ;1U
Solar/Wind Harmer
10.861
959091AF2-200 GEN
Solar/Wind Harmer
32.052
24441505OLIV SLR
Solar/Wind Harmer
0.214
274857EASY ROAD;U1
Solar/Wind Harmer
7.453
274760LEE CO EC;1U
Adder
14.473
274767LEE CO EC;8U
Adder
14.303
970571AG2-364 GEN
Solar/Wind Harmer
31.08
276603SUBLETTE C
Solar/Wind Harmer
1.628
274851PROVIDENC;RU
Solar/Wind Harmer
4.291
274849CRESCENT ;1U
Solar/Wind Harmer
2.785
276782AC1-033 GEN
Solar/Wind Harmer
5.968
274878BISHOP HL;2U
Solar/Wind Harmer
5.049
964401AG1-302 GEN
Solar/Wind Harmer
13.325
965931AG1-462 GEN
Solar/Wind Harmer
37.189
971087AG2-675 GEN
Solar/Wind Harmer
5.427
270505AE1-170 C O1
Solar/Wind Harmer
21.692
965091AG1-374 GEN
Solar/Wind Harmer
42.339
959611AF2-252 GEN
Solar/Wind Harmer
3.282
270536AF1-215 GEN2
Solar/Wind Harmer
6.889
276645AC1-214 GEN1
Solar/Wind Harmer
2.018
942111AE2-223 GEN
Solar/Wind Harmer
11.906
247620Y3-023
Adder
0.484
270349AD2-093_GEN
Solar/Wind Helper
1.355
270471AD2-092_GEN
Solar/Wind Helper
1.355
960611AF2-352 GEN
Solar/Wind Harmer
2.839
NYPJM->LTFIMP_NY
CLTF
2.318
LGEELTFEXP_LGEE->PJM
CLTF
1.824
WECLTFEXP_WEC->PJM
CLTF
6.05
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.706
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.293
CBM West 1LTFEXP_CBM-W1->PJM
CBM
162.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.225
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.922
MECLTFEXP_MEC->PJM
CLTF
20.835
SIGELTFEXP_SIGE->PJM
CLTF
0.246
AG2-052LTFEXP_AG2-052->PJM
LTF
0.341
AH1-155LTFEXP_AH1-155->PJM
LTF
0.512
LAGNLTFEXP_LAGN->PJM
CLTF
9.594
TVALTFEXP_TVA->PJM
CLTF
3.289

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#2979_05DUMONT 765_B2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2979_05DUMONT 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.9 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5096.22
MW Contribution:
25.27
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
13.735
274771LINCOLN ;2U
50/50
13.735
270102X2-052 ST
50/50
3.072
270100X2-052 CT1
50/50
2.838
270101X2-052 CT2
50/50
2.838
970349AG2-230 GEN
Solar/Wind Harmer
32.81
276897AD1-100 C
Solar/Wind Harmer
88.29
965681AG1-436 GEN
Solar/Wind Harmer
23.688
965791AG1-447 GEN
Solar/Wind Harmer
12.12
274888KELLY CRK;1U
Solar/Wind Harmer
11.148
276776AD2-060 GEN
Solar/Wind Harmer
0.791
958011AF2-095 GEN
Solar/Wind Harmer
27.203
970941AG2-585 GEN
Solar/Wind Harmer
10.39
274674JOLIET 9 ;6U
Adder
28.766
274805UNIV PK N;1U
Adder
9.337
274808UNIV PK N;4U
Adder
9.276
276893AG1-478 C
Solar/Wind Harmer
0.815
274695ROCKY RD ;2P
Adder
20.321
274693ROCKY RD ;1P
Adder
20.121
274697ROCKY RD ;3P
Adder
5.52
274696ROCKY RD ;4P
Adder
20.799
274683WAUKEGAN ;8U
Adder
38.171
274683WAUKEGAN ;8U
Adder
32.177
962691AG1-118 GEN
Solar/Wind Harmer
54.174
960751AF2-366 GEN
Solar/Wind Harmer
5.158
958481AF2-142 GEN
Solar/Wind Harmer
26.819
958491AF2-143 GEN
Solar/Wind Harmer
26.235
276901AD2-066 C O1
Solar/Wind Harmer
6.125
971341AH1-150 GEN
Solar/Wind Harmer
34.748
971343AH1-151 GEN
Solar/Wind Harmer
34.748
972235AH1-702 GEN1
Adder
4.335
972236AH1-702 GEN2
Adder
3.77
276872AE1-163_GEN1
Solar/Wind Harmer
11.383
276876AE1-163_GEN2
Solar/Wind Harmer
11.383
938861AE1-114 GEN
Solar/Wind Harmer
13.805
274764LEE CO EC;5U
Adder
15.601
274765LEE CO EC;6U
Adder
15.601
274762LEE CO EC;3U
Adder
15.564
274763LEE CO EC;4U
Adder
15.417
276158O29GEN2
Solar/Wind Harmer
8.134
276157O29GEN1
Solar/Wind Harmer
6.184
961051AF2-396 GEN
Solar/Wind Harmer
25.769
961051AF2-396 GEN
Solar/Wind Harmer
11.985
276645AC1-214 GEN1
Solar/Wind Harmer
2.128
942111AE2-223 GEN
Solar/Wind Harmer
12.128
247620Y3-023
Adder
0.561
274772LINCOLN ;3U
50/50
13.735
972259AH1-714 GEN
50/50
38.928
971347AH1-153 GEN
Solar/Wind Harmer
10.937
970707AG2-453 GEN
Solar/Wind Harmer
54.845
939351AE1-166 GEN
Solar/Wind Harmer
11.272
276164X3-005 C
Solar/Wind Harmer
1.332
274887GEN-1.85
Solar/Wind Harmer
10.065
276772AC2-154 GEN
Solar/Wind Harmer
5.272
276843GEN-1.7
Solar/Wind Harmer
1.083
276806AD2-047 C O1
Solar/Wind Harmer
20.209
274724RIVER EC ;11
Adder
33.374
274826FISK ;BP
Adder
20.603
972038AH1-567 GEN2
Adder
0.686
943121AE2-341 GEN
Solar/Wind Harmer
28.173
943591AF1-030 GEN
Solar/Wind Harmer
18.782
274803UNIV PARK;6U
Adder
10.93
274676JOLIET 29;8U
Adder
55.433
274729ELWOOD EC;1P
Adder
30.614
274730ELWOOD EC;6P
Adder
30.613
274734ELWOOD EC;8P
Adder
30.613
274736ELWOOD EC;9P
Adder
30.613
274814UNIV PK N;0U
Adder
9.398
274807UNIV PK N;3U
Adder
9.378
274811UNIV PK N;7U
Adder
9.317
972231SS25-0005
Solar/Wind Harmer
17.483
972181SS23-001
Solar/Wind Harmer
10.927
274752CRETE EC ;2U
Adder
9.004
274753CRETE EC ;3U
Adder
9.004
274682WAUKEGAN ;7U
Adder
32.625
24441505OLIV SLR
Solar/Wind Harmer
0.24
274862TOP CROP ;2U
Solar/Wind Harmer
9.03
276799AD1-013 GEN
Solar/Wind Harmer
3.89
946671AF1-331 GEN
Solar/Wind Harmer
0.737
274855GSG-6 ;RU
Solar/Wind Harmer
6.491
274850MENDOTA H;RU
Solar/Wind Harmer
4.513
276602WESTBROOK C
Solar/Wind Harmer
3.737
276868AE1-113 GEN
Solar/Wind Harmer
17.601
274879MINONK ;1U
Solar/Wind Harmer
11.735
959091AF2-200 GEN
Solar/Wind Harmer
34.748
270505AE1-170 C O1
Solar/Wind Harmer
25.155
274857EASY ROAD;U1
Solar/Wind Harmer
8.014
274760LEE CO EC;1U
Adder
15.564
274767LEE CO EC;8U
Adder
15.381
276603SUBLETTE C
Solar/Wind Harmer
1.748
970571AG2-364 GEN
Solar/Wind Harmer
33.16
274851PROVIDENC;RU
Solar/Wind Harmer
4.524
274849CRESCENT ;1U
Solar/Wind Harmer
2.937
276782AC1-033 GEN
Solar/Wind Harmer
6.287
274878BISHOP HL;2U
Solar/Wind Harmer
5.319
945111AF1-176 GEN
Solar/Wind Harmer
8.899
965931AG1-462 GEN
Solar/Wind Harmer
39.241
971087AG2-675 GEN
Solar/Wind Harmer
5.726
247643Z2-116 C
Solar/Wind Harmer
0.107
965091AG1-374 GEN
Solar/Wind Harmer
42.222
274775LINCOLN ;6U
50/50
13.735
274776LINCOLN ;7U
50/50
13.735
274777LINCOLN ;8U
50/50
13.735
24344005CKG1
50/50
12.627
274661LASCO STA;2U
50/50
10.703
274660LASCO STA;1U
50/50
13.826
972227AH1-698 GEN1
Adder
4.953
972228AH1-698 GEN2
Adder
7.034
960681AF2-359 GEN
Solar/Wind Harmer
7.16
960591AF2-350 GEN
Solar/Wind Harmer
18.891
274827FISK ;RP
Adder
14.602
274800UNIV PARK;3U
Adder
10.964
274801UNIV PARK;4U
Adder
10.964
972037AH1-567 GEN1
Adder
0.343
274675JOLIET 29;7U
Adder
57.489
274675JOLIET 29;7U
Adder
55.436
970833AG2-524 GEN
Solar/Wind Harmer
16.357
970833AG2-524 GEN
Solar/Wind Harmer
7.608
274687WILL CNTY;4U
Adder
52.33
274687WILL CNTY;4U
Adder
52.33
274744AC1-111 GEN8
Adder
10.422
274746AC1-111 G10
Adder
10.422
274728ELWOOD EC;5P
Adder
30.613
274731ELWOOD EC;2P
Adder
30.614
274733ELWOOD EC;3P
Adder
30.614
274735ELWOOD EC;4P
Adder
30.614
276893AG1-478 C
Solar/Wind Harmer
1.022
270526AF1-158 GEN
Solar/Wind Harmer
8.061
971675AH1-338 GEN
Solar/Wind Harmer
31.664
276861AD2-134 GEN
Solar/Wind Harmer
3.139
276863AD2-134 GEN
Solar/Wind Harmer
3.139
971411AH1-196 GEN
Solar/Wind Harmer
26.364
970073AG2-061 GEN
Solar/Wind Harmer
4.067
971171AH1-044 GEN
Solar/Wind Harmer
34.748
274823ROCKFORD ;21
Adder
33.657
274856ECOGROVE ;U1
Solar/Wind Harmer
5.747
276611AD2-172 GEN
Solar/Wind Harmer
4.36
276612AE2-035 GEN
Solar/Wind Harmer
4.36
971771AH1-392 GEN
Solar/Wind Harmer
15.314
276889AE2-281 GEN
Solar/Wind Harmer
3.252
274863CRW1-WTG
Solar/Wind Harmer
9.452
274864CRW2-WTG
Solar/Wind Harmer
9.452
971681AH1-341 GEN
Solar/Wind Harmer
25.271
926823AC1-168 GEN
Solar/Wind Harmer
7.138
944161AF1-084 GEN
Solar/Wind Harmer
3.664
972267AH1-718 GEN
Adder
6.837
970169AG2-114 GEN
Solar/Wind Harmer
16.278
276741O09 GEN1
Solar/Wind Harmer
5.807
274877BISHOP HL;1U
Solar/Wind Harmer
5.319
946321AF1-296 GEN
Solar/Wind Harmer
16.221
276726Z2-087_GEN
Solar/Wind Harmer
11.699
959341AF2-225 GEN
Solar/Wind Harmer
22.192
971549AH1-272 GEN
Solar/Wind Harmer
26.725
274853TWINGROVE;U1
Solar/Wind Harmer
10.227
274854TWINGROVE;U2
Solar/Wind Harmer
10.013
24344105CKG2
50/50
20.648
274773LINCOLN ;4U
50/50
13.735
274774LINCOLN ;5U
50/50
13.735
972207SS24-0001
Solar/Wind Harmer
46.022
941551AE2-152 GEN
Solar/Wind Harmer
8.62
274723RIVER EC ;12
Adder
33.711
274802UNIV PARK;5U
Adder
10.93
274871GR RIDGE ;2U
Solar/Wind Harmer
14.405
274847GR RIDGE ;BU
Solar/Wind Harmer
9.472
274676JOLIET 29;8U
Adder
57.487
274674JOLIET 9 ;6U
Adder
28.766
274745AC1-111 GEN9
Adder
10.422
274732ELWOOD EC;7P
Adder
30.613
274812UNIV PK N;8U
Adder
9.317
274751CRETE EC ;1U
Adder
9.004
274754CRETE EC ;4U
Adder
9.004
274682WAUKEGAN ;7U
Adder
32.625
274828WAUKEGAN ;BP
Adder
20.009
962781AG1-127 GEN
Solar/Wind Harmer
17.098
274872LEEDK;1U
Solar/Wind Harmer
14.699
276694AA1-018 GEN2
Solar/Wind Harmer
11.281
276691AA1-018 GEN1
Solar/Wind Harmer
1.348
274861TOP CROP ;1U
Solar/Wind Harmer
10.814
939401AE1-172 GEN
Solar/Wind Harmer
24.479
276805AD2-038 GEN
Solar/Wind Harmer
8.969
971997AH1-543 GEN
Solar/Wind Harmer
27.414
276882AE2-255 GEN
Solar/Wind Harmer
5.867
957471AF2-041 GEN
Solar/Wind Harmer
52.122
959081AF2-199 GEN
Solar/Wind Harmer
17.374
971067AG2-660 GEN
Solar/Wind Harmer
4.04
274822ROCKFORD ;11
Adder
33.903
970819AG2-516 GEN
Solar/Wind Harmer
20.52
24441205WTRV SLR C
Solar/Wind Harmer
0.226
274858EASY ROAD;U2
Solar/Wind Harmer
8.014
274761LEE CO EC;2U
Adder
15.564
274766LEE CO EC;7U
Adder
15.381
970569AG2-363 GEN
Solar/Wind Harmer
49.74
270449AD2-020 GEN
Solar/Wind Harmer
4.631
943021AE2-325 GEN
Solar/Wind Harmer
6.02
957891AF2-083 GEN
Solar/Wind Harmer
24.69
276708O09 GEN2
Solar/Wind Harmer
5.807
276646AC1-214 GEN2
Solar/Wind Harmer
2.128
945111AF1-176 GEN
Solar/Wind Harmer
28.079
274848CAMPGROVE;RU
Solar/Wind Harmer
10.071
270216AD2-079_GEN
Solar/Wind Harmer
0.917
276655WTG1_EQ
Solar/Wind Harmer
12.913
276656WTG2_EQ
Solar/Wind Harmer
1.71
939741AE1-205 GEN
Solar/Wind Harmer
29.59
970373AG2-245 GEN
Solar/Wind Harmer
30.409
24639705ELKHART HY
Adder
0.208
NYPJM->LTFIMP_NY
CLTF
2.275
WECLTFEXP_WEC->PJM
CLTF
6.547
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.201
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
174.519
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.708
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.552
MECLTFEXP_MEC->PJM
CLTF
21.076
SIGELTFEXP_SIGE->PJM
CLTF
0.094
AG2-052LTFEXP_AG2-052->PJM
LTF
0.338
AH1-155LTFEXP_AH1-155->PJM
LTF
0.506
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.249
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.529
LAGNLTFEXP_LAGN->PJM
CLTF
7.188
TVALTFEXP_TVA->PJM
CLTF
1.859
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.24 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5536.23
MW Contribution:
40.0
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:97.12 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5363.88
MW Contribution:
38.9
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
23.785
274771LINCOLN ;2U
50/50
23.785
274711KENDALL ;4S
50/50
2.402
274709KENDALL ;3S
50/50
2.402
276897AD1-100 C
Solar/Wind Harmer
140.988
274695ROCKY RD ;2P
Adder
32.477
274693ROCKY RD ;1P
Adder
32.158
274697ROCKY RD ;3P
Adder
8.823
274696ROCKY RD ;4P
Adder
33.24
962691AG1-118 GEN
Solar/Wind Harmer
87.001
960751AF2-366 GEN
Solar/Wind Harmer
8.279
274674JOLIET 9 ;6U
Adder
44.223
274683WAUKEGAN ;8U
Adder
60.368
274683WAUKEGAN ;8U
Adder
50.887
274805UNIV PK N;1U
Adder
14.348
274808UNIV PK N;4U
Adder
14.254
276893AG1-478 C
Solar/Wind Harmer
1.242
274888KELLY CRK;1U
Solar/Wind Harmer
16.531
276776AD2-060 GEN
Solar/Wind Harmer
1.173
958011AF2-095 GEN
Solar/Wind Harmer
40.34
970941AG2-585 GEN
Solar/Wind Harmer
15.408
971341AH1-150 GEN
Solar/Wind Harmer
55.322
971343AH1-151 GEN
Solar/Wind Harmer
55.322
972235AH1-702 GEN1
Adder
6.879
972236AH1-702 GEN2
Adder
5.982
958481AF2-142 GEN
Solar/Wind Harmer
40.871
276901AD2-066 C O1
Solar/Wind Harmer
9.494
958491AF2-143 GEN
Solar/Wind Harmer
40.076
938861AE1-114 GEN
Solar/Wind Harmer
21.844
274764LEE CO EC;5U
Adder
24.669
274765LEE CO EC;6U
Adder
24.669
274762LEE CO EC;3U
Adder
24.611
274763LEE CO EC;4U
Adder
24.379
276872AE1-163_GEN1
Solar/Wind Harmer
17.448
276876AE1-163_GEN2
Solar/Wind Harmer
17.448
276158O29GEN2
Solar/Wind Harmer
12.769
276157O29GEN1
Solar/Wind Harmer
9.709
276645AC1-214 GEN1
Solar/Wind Harmer
3.292
942111AE2-223 GEN
Solar/Wind Harmer
18.498
960611AF2-352 GEN
Solar/Wind Harmer
4.993
274880W4-005 GEN4
Solar/Wind Harmer
5.289
276174W4-005 GEN2
Solar/Wind Harmer
5.289
276615X2-022 GEN
Solar/Wind Harmer
3.254
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276916AD2-100_GEN
Solar/Wind Harmer
30.3
276911AD2-131_GEN
Solar/Wind Harmer
6.124
274773LINCOLN ;4U
50/50
23.785
274774LINCOLN ;5U
50/50
23.785
274710KENDALL ;4C
50/50
3.594
274705KENDALL ;1S
50/50
2.233
972207SS24-0001
Solar/Wind Harmer
79.696
941551AE2-152 GEN
Solar/Wind Harmer
13.765
274871GR RIDGE ;2U
Solar/Wind Harmer
23.136
274847GR RIDGE ;BU
Solar/Wind Harmer
15.212
274745AC1-111 GEN9
Adder
16.783
274676JOLIET 29;8U
Adder
89.061
274732ELWOOD EC;7P
Adder
47.507
962781AG1-127 GEN
Solar/Wind Harmer
27.442
274872LEEDK;1U
Solar/Wind Harmer
23.583
274674JOLIET 9 ;6U
Adder
44.223
274682WAUKEGAN ;7U
Adder
51.601
274751CRETE EC ;1U
Adder
14.031
274754CRETE EC ;4U
Adder
14.031
274828WAUKEGAN ;BP
Adder
31.644
274812UNIV PK N;8U
Adder
14.317
939401AE1-172 GEN
Solar/Wind Harmer
38.947
274802UNIV PARK;5U
Adder
16.231
957471AF2-041 GEN
Solar/Wind Harmer
82.983
959081AF2-199 GEN
Solar/Wind Harmer
27.661
971067AG2-660 GEN
Solar/Wind Harmer
6.433
971997AH1-543 GEN
Solar/Wind Harmer
43.252
274822ROCKFORD ;11
Adder
53.804
274861TOP CROP ;1U
Solar/Wind Harmer
16.513
276694AA1-018 GEN2
Solar/Wind Harmer
17.192
276691AA1-018 GEN1
Solar/Wind Harmer
2.055
970819AG2-516 GEN
Solar/Wind Harmer
32.522
276882AE2-255 GEN
Solar/Wind Harmer
9.076
276805AD2-038 GEN
Solar/Wind Harmer
13.7
274858EASY ROAD;U2
Solar/Wind Harmer
12.673
274761LEE CO EC;2U
Adder
24.611
274766LEE CO EC;7U
Adder
24.321
276708O09 GEN2
Solar/Wind Harmer
9.117
970569AG2-363 GEN
Solar/Wind Harmer
76.437
276646AC1-214 GEN2
Solar/Wind Harmer
3.292
274848CAMPGROVE;RU
Solar/Wind Harmer
15.542
276655WTG1_EQ
Solar/Wind Harmer
19.694
276656WTG2_EQ
Solar/Wind Harmer
2.608
939741AE1-205 GEN
Solar/Wind Harmer
45.129
274723RIVER EC ;12
Adder
38.445
276686W4-005 GEN3
Solar/Wind Harmer
5.289
276621W2-048 GEN
Solar/Wind Harmer
10.362
965911AG1-460 GEN
Solar/Wind Harmer
2.079
274775LINCOLN ;6U
50/50
23.785
274776LINCOLN ;7U
50/50
23.785
274777LINCOLN ;8U
50/50
23.785
274661LASCO STA;2U
50/50
17.331
274660LASCO STA;1U
50/50
22.388
274708KENDALL ;3C
50/50
3.635
274704KENDALL ;1C
50/50
3.34
274706KENDALL ;2C
50/50
3.34
274744AC1-111 GEN8
Adder
16.783
274746AC1-111 G10
Adder
16.783
970833AG2-524 GEN
Solar/Wind Harmer
26.188
970833AG2-524 GEN
Solar/Wind Harmer
12.18
972227AH1-698 GEN1
Adder
7.774
972228AH1-698 GEN2
Adder
11.037
274675JOLIET 29;7U
Adder
89.067
274675JOLIET 29;7U
Adder
85.886
274731ELWOOD EC;2P
Adder
47.515
274733ELWOOD EC;3P
Adder
47.515
274735ELWOOD EC;4P
Adder
47.515
274728ELWOOD EC;5P
Adder
47.507
274687WILL CNTY;4U
Adder
79.889
274687WILL CNTY;4U
Adder
79.889
276893AG1-478 C
Solar/Wind Harmer
1.559
971675AH1-338 GEN
Solar/Wind Harmer
50.62
276861AD2-134 GEN
Solar/Wind Harmer
5.017
276863AD2-134 GEN
Solar/Wind Harmer
5.017
960591AF2-350 GEN
Solar/Wind Harmer
28.014
971411AH1-196 GEN
Solar/Wind Harmer
41.893
972037AH1-567 GEN1
Adder
0.51
971171AH1-044 GEN
Solar/Wind Harmer
55.322
274823ROCKFORD ;21
Adder
53.414
274800UNIV PARK;3U
Adder
15.784
274801UNIV PARK;4U
Adder
15.784
274856ECOGROVE ;U1
Solar/Wind Harmer
9.106
276611AD2-172 GEN
Solar/Wind Harmer
6.907
276612AE2-035 GEN
Solar/Wind Harmer
6.907
274827FISK ;RP
Adder
20.945
274863CRW1-WTG
Solar/Wind Harmer
14.917
274864CRW2-WTG
Solar/Wind Harmer
14.917
970073AG2-061 GEN
Solar/Wind Harmer
6.213
971681AH1-341 GEN
Solar/Wind Harmer
39.998
276889AE2-281 GEN
Solar/Wind Harmer
4.985
926823AC1-168 GEN
Solar/Wind Harmer
11.142
972267AH1-718 GEN
Adder
10.786
276741O09 GEN1
Solar/Wind Harmer
9.117
970169AG2-114 GEN
Solar/Wind Harmer
25.441
274877BISHOP HL;1U
Solar/Wind Harmer
8.236
946321AF1-296 GEN
Solar/Wind Harmer
25.388
276726Z2-087_GEN
Solar/Wind Harmer
17.842
959341AF2-225 GEN
Solar/Wind Harmer
33.847
274853TWINGROVE;U1
Solar/Wind Harmer
15.468
274854TWINGROVE;U2
Solar/Wind Harmer
15.144
276668AB2-070 GEN1
Solar/Wind Harmer
3.859
276848AB2-070 GEN3
Solar/Wind Harmer
3.859
276849AB2-070 GEN2
Solar/Wind Harmer
3.859
276763AC1-053 GEN1
Solar/Wind Harmer
6.787
276764AC1-053 GEN2
Solar/Wind Harmer
6.787
274772LINCOLN ;3U
50/50
23.785
972259AH1-714 GEN
50/50
63.035
274707KENDALL ;2S
50/50
2.233
970707AG2-453 GEN
Solar/Wind Harmer
91.639
943121AE2-341 GEN
Solar/Wind Harmer
45.899
943591AF1-030 GEN
Solar/Wind Harmer
30.599
939351AE1-166 GEN
Solar/Wind Harmer
17.999
274676JOLIET 29;8U
Adder
85.88
274729ELWOOD EC;1P
Adder
47.515
274730ELWOOD EC;6P
Adder
47.507
274734ELWOOD EC;8P
Adder
47.507
274736ELWOOD EC;9P
Adder
47.507
274682WAUKEGAN ;7U
Adder
51.601
972231SS25-0005
Solar/Wind Harmer
27.243
972181SS23-001
Solar/Wind Harmer
17.027
274752CRETE EC ;2U
Adder
14.031
274753CRETE EC ;3U
Adder
14.031
274814UNIV PK N;0U
Adder
14.442
274807UNIV PK N;3U
Adder
14.411
274811UNIV PK N;7U
Adder
14.317
276799AD1-013 GEN
Solar/Wind Harmer
6.219
946671AF1-331 GEN
Solar/Wind Harmer
1.178
274855GSG-6 ;RU
Solar/Wind Harmer
10.375
274850MENDOTA H;RU
Solar/Wind Harmer
7.214
276602WESTBROOK C
Solar/Wind Harmer
5.973
274887GEN-1.85
Solar/Wind Harmer
14.926
276772AC2-154 GEN
Solar/Wind Harmer
7.818
276843GEN-1.7
Solar/Wind Harmer
1.606
276806AD2-047 C O1
Solar/Wind Harmer
29.969
274803UNIV PARK;6U
Adder
16.231
959091AF2-200 GEN
Solar/Wind Harmer
55.322
274862TOP CROP ;2U
Solar/Wind Harmer
13.788
972038AH1-567 GEN2
Adder
0.988
274826FISK ;BP
Adder
29.553
276868AE1-113 GEN
Solar/Wind Harmer
27.226
274879MINONK ;1U
Solar/Wind Harmer
18.151
274857EASY ROAD;U1
Solar/Wind Harmer
12.673
274760LEE CO EC;1U
Adder
24.611
274767LEE CO EC;8U
Adder
24.321
276603SUBLETTE C
Solar/Wind Harmer
2.764
970571AG2-364 GEN
Solar/Wind Harmer
50.958
276164X3-005 C
Solar/Wind Harmer
1.742
274851PROVIDENC;RU
Solar/Wind Harmer
7.001
274849CRESCENT ;1U
Solar/Wind Harmer
4.545
276782AC1-033 GEN
Solar/Wind Harmer
9.734
274878BISHOP HL;2U
Solar/Wind Harmer
8.236
965931AG1-462 GEN
Solar/Wind Harmer
61.337
971087AG2-675 GEN
Solar/Wind Harmer
8.95
274724RIVER EC ;11
Adder
38.453
965091AG1-374 GEN
Solar/Wind Harmer
64.41
959611AF2-252 GEN
Solar/Wind Harmer
4.993
276785W4-005 GEN1
Solar/Wind Harmer
5.289
971993AH1-541 GEN
Solar/Wind Harmer
16.161
957381AF2-032 GEN
Solar/Wind Harmer
3.014
942481AE2-261 GEN
Solar/Wind Harmer
44.542
991777J1629 G
External Queue
30.850322723388672
990512J1326
External Queue
13.68272590637207
990117J1214
External Queue
47.068572998046875
990727J1377 G
External Queue
15.952624320983887
991092J1477
External Queue
7.281757831573486
991303J1755 G
External Queue
11.446473121643066
990407J1304
External Queue
10.605093955993652
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.534
NYPJM->LTFIMP_NY
CLTF
2.529
WECLTFEXP_WEC->PJM
CLTF
10.324
CBM West 1LTFEXP_CBM-W1->PJM
CBM
172.893
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.394
MECLTFEXP_MEC->PJM
CLTF
32.345
SIGELTFEXP_SIGE->PJM
CLTF
0.045
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.074
AG2-052LTFEXP_AG2-052->PJM
LTF
0.082
AH1-155LTFEXP_AH1-155->PJM
LTF
0.122
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.868
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.148
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.22
LAGNLTFEXP_LAGN->PJM
CLTF
10.658
TVALTFEXP_TVA->PJM
CLTF
2.709

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
14.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.63 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.85
MW Contribution:
14.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
14.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.46
MW Contribution:
14.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
961491AF2-440 GEN
Solar/Wind Harmer
2.092
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
959091AF2-200 GEN
Solar/Wind Harmer
5.775
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.62 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5696.16
MW Contribution:
14.37
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728205BUCHG1
50/50
8.141
270214AC2-123 GEN
Solar/Wind Harmer
5.192
971277AH1-098 GEN
Solar/Wind Harmer
7.595
971225AH1-072 GEN
Solar/Wind Harmer
3.123
971227AH1-073 GEN
Solar/Wind Harmer
3.123
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
6.598
971485AH1-239 GEN
Solar/Wind Harmer
9.749
339231AF1-038_GEN
Solar/Wind Harmer
2.185
964781AG1-341 GEN
Solar/Wind Harmer
12.421
339236AF1-050_GEN
Solar/Wind Harmer
2.114
942891AE2-308 GEN
Solar/Wind Harmer
11.292
964571AG1-320 GEN
Solar/Wind Harmer
9.075
971125AH1-004 GEN
Solar/Wind Harmer
4.396
970107AG2-081 GEN
Solar/Wind Harmer
3.297
972043AH1-570 GEN
Solar/Wind Harmer
2.711
972045AH1-571 GEN
Solar/Wind Harmer
2.168
970913AG2-568 GEN
Solar/Wind Harmer
7.344
962581AG1-107 GEN
Solar/Wind Harmer
5.033
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
6.454
971313AH1-133 GEN
Solar/Wind Harmer
10.065
971981AH1-535 GEN
Solar/Wind Harmer
15.391
970281AG2-184 GEN
Solar/Wind Harmer
30.514
962211AG1-066 GEN
Solar/Wind Harmer
3.399
270399AC1-101 GEN
Solar/Wind Harmer
5.964
270400AC1-102 GEN
Solar/Wind Harmer
5.964
957241AF2-018 GEN
Solar/Wind Harmer
6.157
270053AF1-130 C
Solar/Wind Harmer
24.596
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
9.695
339216AC1-074 GEN
Solar/Wind Harmer
1.798
972163AH1-664 GEN
Solar/Wind Harmer
10.556
972165AH1-665 GEN
Solar/Wind Harmer
8.445
270444AC2-157 GEN1
Solar/Wind Harmer
5.636
270445AC2-157 GEN2
Solar/Wind Harmer
5.636
961491AF2-440 GEN
Solar/Wind Harmer
2.092
252509AD1-136 GEN
Solar/Wind Harmer
0.254
276916AD2-100_GEN
Solar/Wind Harmer
20.818
276911AD2-131_GEN
Solar/Wind Harmer
4.207
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
12.361
971461AH1-227 GEN
Solar/Wind Harmer
8.01
972103AH1-617 GEN
Solar/Wind Harmer
29.061
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
23.688
339255AE2-071 GEN
Solar/Wind Harmer
1.379
339250AF1-203 GEN
Solar/Wind Harmer
0.71
339206AE1-143 GEN
Solar/Wind Harmer
2.481
970093AG2-073 GEN
Solar/Wind Harmer
6.065
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.91
339243AC2-075 GEN1
Solar/Wind Harmer
0.487
972167AH1-666 GEN
Solar/Wind Harmer
8.411
958171AF2-111 GEN
Solar/Wind Harmer
25.937
270186AC1-089 GEN
Solar/Wind Harmer
6.203
270330AC1-082 GEN2
Solar/Wind Harmer
0.478
270329AC1-082 GEN1
Solar/Wind Harmer
0.478
270367AC2-061_GEN
Solar/Wind Harmer
3.192
971191AH1-055 GEN
Solar/Wind Harmer
18.679
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
1.781
942481AE2-261 GEN
Solar/Wind Harmer
29.588
957381AF2-032 GEN
Solar/Wind Harmer
1.978
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
14.742
252524AE2-267 GEN
Solar/Wind Harmer
1.546
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
276785W4-005 GEN1
Solar/Wind Harmer
2.955
971993AH1-541 GEN
Solar/Wind Harmer
9.03
253317AC1-085 GEN4
Solar/Wind Harmer
8.176
946181AF1-283 GEN
Solar/Wind Harmer
12.696
965931AG1-462 GEN
Solar/Wind Harmer
24.757
971087AG2-675 GEN
Solar/Wind Harmer
3.613
957541AF2-048 GEN
Solar/Wind Harmer
1.534
965091AG1-374 GEN
Solar/Wind Harmer
28.952
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
4.374
276782AC1-033 GEN
Solar/Wind Harmer
3.835
274878BISHOP HL;2U
Solar/Wind Harmer
3.245
274851PROVIDENC;RU
Solar/Wind Harmer
2.734
274849CRESCENT ;1U
Solar/Wind Harmer
1.775
276603SUBLETTE C
Solar/Wind Harmer
1.006
274857EASY ROAD;U1
Solar/Wind Harmer
4.594
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
19.092
274682WAUKEGAN ;7U
Adder
16.992
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
972259AH1-714 GEN
Adder
8.841
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.552
971403AH1-188 GEN
Solar/Wind Harmer
20.001
944971AF1-162 GEN
Solar/Wind Harmer
9.695
270336AE1-100 GEN
Solar/Wind Harmer
2.207
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
17.489
339241AF1-083 GEN
Solar/Wind Harmer
1.932
339211AE2-254 GEN
Solar/Wind Harmer
1.749
970653AG2-424 GEN
Solar/Wind Harmer
5.448
943811AF1-049 GEN
Solar/Wind Harmer
4.26
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
943111AE2-339 GEN
Solar/Wind Harmer
0.973
339221AD2-048_GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
19.84
970091AG2-072 GEN
Adder
78.951
270331AC1-082 GEN3
Solar/Wind Harmer
0.479
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
9.863
252510AF1-249 C
Solar/Wind Harmer
0.41
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
6.123
24728605AND G2
Adder
3.754
276686W4-005 GEN3
Solar/Wind Harmer
2.955
253316AC1-085 GEN3
Solar/Wind Harmer
8.176
946171AF1-282 GEN
Solar/Wind Harmer
9.766
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
960001AF2-291 GEN
Solar/Wind Harmer
2.912
274848CAMPGROVE;RU
Solar/Wind Harmer
6.214
270222AC2-111 GEN
Solar/Wind Harmer
4.299
944031AF1-071 GEN
Solar/Wind Harmer
0.967
276708O09 GEN2
Solar/Wind Harmer
3.437
963741AG1-226 GEN
Solar/Wind Harmer
43.256
276655WTG1_EQ
Solar/Wind Harmer
8.387
276656WTG2_EQ
Solar/Wind Harmer
1.11
939741AE1-205 GEN
Solar/Wind Harmer
19.219
276646AC1-214 GEN2
Solar/Wind Harmer
1.286
274858EASY ROAD;U2
Solar/Wind Harmer
4.594
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
11.469
970569AG2-363 GEN
Solar/Wind Harmer
28.638
274822ROCKFORD ;11
Adder
18.727
274828WAUKEGAN ;BP
Adder
10.448
274682WAUKEGAN ;7U
Adder
16.992
274745AC1-111 GEN9
Adder
5.265
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
25183208HLCRTG
Solar/Wind Harmer
5.972
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
13.696
276615X2-022 GEN
Solar/Wind Harmer
1.923
276838X2-022 GEN2
Solar/Wind Harmer
0.228
274880W4-005 GEN4
Solar/Wind Harmer
2.955
276174W4-005 GEN2
Solar/Wind Harmer
2.955
927014AC1-188 GEN
Solar/Wind Harmer
1.534
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
4.814
276157O29GEN1
Solar/Wind Harmer
3.66
970241AG2-163 GEN
Solar/Wind Harmer
24.031
942111AE2-223 GEN
Solar/Wind Harmer
7.877
276645AC1-214 GEN1
Solar/Wind Harmer
1.286
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
7.852
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
253370AE2-315 SEC1
Adder
1.882
274674JOLIET 9 ;6U
Adder
14.448
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
971341AH1-150 GEN
Solar/Wind Harmer
5.775
971343AH1-151 GEN
Solar/Wind Harmer
5.775
959091AF2-200 GEN
Solar/Wind Harmer
5.775
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
957471AF2-041 GEN
Solar/Wind Harmer
8.663
959081AF2-199 GEN
Solar/Wind Harmer
2.888
971067AG2-660 GEN
Solar/Wind Harmer
0.672
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
10.902
971985AH1-537 GEN
Solar/Wind Harmer
17.677
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
3.869
276764AC1-053 GEN2
Solar/Wind Harmer
3.869
276668AB2-070 GEN1
Solar/Wind Harmer
2.164
276848AB2-070 GEN3
Solar/Wind Harmer
2.164
276849AB2-070 GEN2
Solar/Wind Harmer
2.164
253433AC1-085 GEN1
Solar/Wind Harmer
5.19
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
946321AF1-296 GEN
Solar/Wind Harmer
10.113
270356AE2-297 GEN
Solar/Wind Harmer
4.461
274853TWINGROVE;U1
Solar/Wind Harmer
6.953
274854TWINGROVE;U2
Solar/Wind Harmer
6.807
253406AD2-031_GEN
Solar/Wind Harmer
1.232
274877BISHOP HL;1U
Solar/Wind Harmer
3.245
276741O09 GEN1
Solar/Wind Harmer
3.437
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
7.598
959341AF2-225 GEN
Solar/Wind Harmer
14.414
971681AH1-341 GEN
Solar/Wind Harmer
14.366
274856ECOGROVE ;U1
Solar/Wind Harmer
3.225
276611AD2-172 GEN
Solar/Wind Harmer
2.446
276612AE2-035 GEN
Solar/Wind Harmer
2.446
963841AG1-237 GEN
Solar/Wind Harmer
10.438
926823AC1-168 GEN
Solar/Wind Harmer
4.104
274823ROCKFORD ;21
Adder
18.591
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
25306009OHH W.
Adder
2.709
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
971171AH1-044 GEN
Solar/Wind Harmer
5.775
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-237805-237806_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-237805-237806_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.36 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5638.63
MW Contribution:
10.76
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line l/o AP_P1-2_PE-765-242508-237805_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-765-242508-237805_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5637.94
MW Contribution:
10.76
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24728305BUCHG2
50/50
8.141
24735205WLF2G2
50/50
10.407
971687AH1-348 GEN
Solar/Wind Harmer
1.083
971403AH1-188 GEN
Solar/Wind Harmer
13.954
944971AF1-162 GEN
Solar/Wind Harmer
9.695
972203AH1-686 GEN
Adder
2.845
24686505CER G6
Adder
10.257
964901AG1-354 GEN
Solar/Wind Harmer
12.202
970653AG2-424 GEN
Solar/Wind Harmer
3.801
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
13.348
3429421JKCT 10G
Adder
9.312
945681AF1-233 GEN
Solar/Wind Harmer
13.842
970091AG2-072 GEN
Adder
78.951
25196808ZIMRHP
Adder
75.837
25196008MFTGT1
Adder
1.389
965911AG1-460 GEN
Solar/Wind Harmer
1.381
252516AE2-318_GEN
Solar/Wind Harmer
7.707
252510AF1-249 C
Solar/Wind Harmer
0.052
25194608D.CRK4
Adder
1.616
276621W2-048 GEN
Solar/Wind Harmer
0.343
24728605AND G2
Adder
3.754
253316AC1-085 GEN3
Solar/Wind Harmer
0
24728205BUCHG1
50/50
8.141
971277AH1-098 GEN
Solar/Wind Harmer
5.299
971225AH1-072 GEN
Solar/Wind Harmer
2.179
971227AH1-073 GEN
Solar/Wind Harmer
2.179
24723105RIVRG2
Adder
24.569
966021AG1-471 GEN
Solar/Wind Harmer
4.603
971485AH1-239 GEN
Solar/Wind Harmer
6.802
964781AG1-341 GEN
Solar/Wind Harmer
8.666
942891AE2-308 GEN
Solar/Wind Harmer
7.878
964571AG1-320 GEN
Solar/Wind Harmer
7.052
971125AH1-004 GEN
Solar/Wind Harmer
3.067
970107AG2-081 GEN
Solar/Wind Harmer
2.3
972043AH1-570 GEN
Solar/Wind Harmer
1.967
972045AH1-571 GEN
Solar/Wind Harmer
1.576
970913AG2-568 GEN
Solar/Wind Harmer
6.036
971587AH1-292 GEN
Solar/Wind Harmer
5.167
962581AG1-107 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.035
276916AD2-100_GEN
Solar/Wind Harmer
14.524
276911AD2-131_GEN
Solar/Wind Harmer
0.957
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.436
25194508D.CRK3
Adder
1.39
945391AF1-204 GEN
Solar/Wind Harmer
7.285
276615X2-022 GEN
Solar/Wind Harmer
0.071
276838X2-022 GEN2
Solar/Wind Harmer
0.386
960611AF2-352 GEN
Solar/Wind Harmer
2.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.083
946171AF1-282 GEN
Solar/Wind Harmer
6.813
970773AG2-487 GEN
Solar/Wind Harmer
1.193
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.237
963741AG1-226 GEN
Solar/Wind Harmer
15.872
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.386
276646AC1-214 GEN2
Solar/Wind Harmer
0.263
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.921
274766LEE CO EC;7U
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
8.002
970569AG2-363 GEN
Solar/Wind Harmer
19.98
274822ROCKFORD ;11
Adder
18.727
957471AF2-041 GEN
Solar/Wind Harmer
19.952
959081AF2-199 GEN
Solar/Wind Harmer
6.651
971067AG2-660 GEN
Solar/Wind Harmer
2.217
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.873
971997AH1-543 GEN
Solar/Wind Harmer
3.474
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.772
962781AG1-127 GEN
Solar/Wind Harmer
6.296
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.38
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
10.448
939401AE1-172 GEN
Solar/Wind Harmer
4.936
270005AE1-210 C O1
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
2.341
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274745AC1-111 GEN9
Adder
5.265
971073AG2-665 GEN
Solar/Wind Harmer
1.095
270594AE1-207 GEN
Solar/Wind Harmer
7.354
270032AE2-172
Solar/Wind Harmer
4.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
274732ELWOOD EC;7P
Adder
15.424
274674JOLIET 9 ;6U
Adder
14.448
274676JOLIET 29;8U
Adder
28.777
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.106
958861AF2-177 GEN
Solar/Wind Harmer
2.806
965651AG1-433 GEN
Solar/Wind Harmer
1.894
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
8.385
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
13.428
270273AD2-016 GEN
Solar/Wind Harmer
0.654
253333AC1-068 GEN
Solar/Wind Harmer
0.007
957891AF2-083 GEN
Solar/Wind Harmer
10.316
270173AC1-122 GEN
Solar/Wind Helper
2.9
3148013FISHERV
Solar/Wind Helper
0.399
316197AC1-042 GEN
Solar/Wind Helper
0.373
3147312GRETNA
Solar/Wind Helper
0.079
270494AE1-108_GEN
Solar/Wind Helper
5.248
316499AE2-029_GEN
Solar/Wind Helper
1.294
315821AE2-092 GEN
Solar/Wind Helper
3.335
3147666LOUISA
Solar/Wind Helper
0.737
3132273ORANGE
Solar/Wind Helper
0.063
966881AG1-559 GEN
Solar/Wind Helper
0.396
316473AC1-191 GEN
Solar/Wind Helper
1.748
3141196NOKESVL
Solar/Wind Helper
1.125
3146776BUCKING
Solar/Wind Helper
0.099
316075AC2-137 C
Solar/Wind Helper
0.419
316223AC1-118
Solar/Wind Helper
0.414
3141906WESTMOR
Solar/Wind Helper
0.108
316077AC2-138 C
Solar/Wind Helper
0.253
3142946ENON
Solar/Wind Helper
0.089
316484AD2-074 GEN
Solar/Wind Helper
0.513
23546401DTGZ2-030
Solar/Wind Helper
0.079
316458AB2-190 GEN2
Solar/Wind Helper
1.421
316123AC1-075 GEN
Solar/Wind Helper
1.507
3146926FARMVIL
Solar/Wind Helper
0.144
227287AC2-120 GEN
Solar/Wind Helper
0.324
226910AB2-157 C
Solar/Wind Helper
0.013
3145336SMITFLD
Solar/Wind Helper
0.094
3144536CHRHLND
Solar/Wind Helper
0.035
3144873MCLAUGH
Solar/Wind Helper
0.006
3142956BIRDNECK
Solar/Wind Helper
0.153
945111AF1-176 GEN
Solar/Wind Harmer
1.916
24416005BYLLESBY
50/50
0.031
24734705WLF1G3
50/50
10.494
24734805WLF1G4
50/50
10.494
24734905WLF1G5
50/50
10.494
24735105WLF2G1
50/50
10.407
966391AG1-508 GEN
Solar/Wind Harmer
2.018
971313AH1-133 GEN
Solar/Wind Harmer
5.791
971981AH1-535 GEN
Solar/Wind Harmer
7.159
970281AG2-184 GEN
Solar/Wind Harmer
21.289
270399AC1-101 GEN
Solar/Wind Harmer
3.105
270400AC1-102 GEN
Solar/Wind Harmer
3.105
957241AF2-018 GEN
Solar/Wind Harmer
0.001
270053AF1-130 C
Solar/Wind Harmer
21.636
3429211JKCT 2G
Adder
13.175
270069AE2-166 C O1
Solar/Wind Harmer
6.764
339216AC1-074 GEN
Solar/Wind Harmer
0.2
972163AH1-664 GEN
Solar/Wind Harmer
8.2
972165AH1-665 GEN
Solar/Wind Harmer
6.567
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.531
25196108MFTGT2
Adder
1.422
944221AF1-090 GEN
Solar/Wind Harmer
4.083
971985AH1-537 GEN
Solar/Wind Harmer
2.055
25196408WSDLE3
Adder
8.661
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.268
276848AB2-070 GEN3
Solar/Wind Harmer
0.267
276849AB2-070 GEN2
Solar/Wind Harmer
0.268
946321AF1-296 GEN
Solar/Wind Harmer
3.787
270356AE2-297 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.499
274877BISHOP HL;1U
Solar/Wind Harmer
0.224
276741O09 GEN1
Solar/Wind Harmer
0.237
972267AH1-718 GEN
Adder
4.004
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.039
971681AH1-341 GEN
Solar/Wind Harmer
10.757
274856ECOGROVE ;U1
Solar/Wind Harmer
0.156
963841AG1-237 GEN
Solar/Wind Harmer
2.887
926823AC1-168 GEN
Solar/Wind Harmer
1.132
274823ROCKFORD ;21
Adder
18.591
971171AH1-044 GEN
Solar/Wind Harmer
13.301
970169AG2-114 GEN
Solar/Wind Harmer
6.65
276861AD2-134 GEN
Solar/Wind Harmer
0.118
276863AD2-134 GEN
Solar/Wind Harmer
0.118
971675AH1-338 GEN
Solar/Wind Harmer
2.589
971411AH1-196 GEN
Solar/Wind Harmer
9.957
270340AC2-060 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.202
971029AG2-637 GEN
Solar/Wind Harmer
9.878
274744AC1-111 GEN8
Adder
5.265
274746AC1-111 G10
Adder
5.265
270543AE2-219 C
Solar/Wind Harmer
4.594
25306009OHH W.
Adder
2.709
970289AG2-191 GEN
Solar/Wind Harmer
1.246
253372AE2-315 SEC3
Adder
1.78
253372AE2-315 SEC3
Adder
1.78
970833AG2-524 GEN
Solar/Wind Harmer
7.211
970833AG2-524 GEN
Solar/Wind Harmer
4.807
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
15.424
274731ELWOOD EC;2P
Adder
15.424
274733ELWOOD EC;3P
Adder
15.424
274735ELWOOD EC;4P
Adder
15.424
274675JOLIET 29;7U
Adder
28.777
274675JOLIET 29;7U
Adder
27.749
247536S-71 GEN
Solar/Wind Harmer
0.262
274687WILL CNTY;4U
Adder
26.19
274687WILL CNTY;4U
Adder
26.19
971609AH1-304 GEN
Solar/Wind Harmer
1.067
964611AG1-324 GEN
Solar/Wind Harmer
2.547
960591AF2-350 GEN
Solar/Wind Harmer
6.521
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.649
971611AH1-305 GEN
Solar/Wind Harmer
3.861
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270291AC1-194 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.689
270071AF1-092 GEN
Solar/Wind Harmer
12.068
270526AF1-158 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.768
971771AH1-392 GEN
Solar/Wind Harmer
6.242
963791AG1-232 GEN
Solar/Wind Harmer
8.419
315616AA1-038_C
Solar/Wind Helper
2.173
3148463FAIRFLD
Solar/Wind Helper
0.479
3148133STUARTS
Solar/Wind Helper
0.239
3148013FISHERV
Solar/Wind Helper
0.229
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.01
316164AC1-076 GEN
Solar/Wind Helper
1.46
315651AD1-115 GEN
Solar/Wind Helper
1.023
316258AE1-075 C
Solar/Wind Helper
0.414
316405AF2-144 C
Solar/Wind Helper
0.345
316233AE1-074 FULL
Solar/Wind Helper
0.437
316468AD1-105 GEN
Solar/Wind Helper
1.372
3141426STAFORD
Solar/Wind Helper
0.062
316322AB2-045
Solar/Wind Helper
0.308
3141813NORNECK
Solar/Wind Helper
0.268
3143873LANEXA
Solar/Wind Helper
0.159
316059AD1-063 C
Solar/Wind Helper
0.267
3141783LANCAST
Solar/Wind Helper
0.158
3141783LANCAST
Solar/Wind Helper
0.106
3138133OCRAN
Solar/Wind Helper
0.079
3141913WHIT STONE
Solar/Wind Helper
0.263
957601AF2-054 GEN
Solar/Wind Helper
0.352
3141873WAN 176
Solar/Wind Helper
0.052
3138216PACIFIC
Solar/Wind Helper
0.043
316382AG1-145 C
Solar/Wind Helper
0.345
316159AE1-175 C
Solar/Wind Helper
0.389
957831AF2-077 GEN
Solar/Wind Helper
0.343
315839AE2-212 C
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.802
3143316POE
Solar/Wind Helper
0.966
226929AD2-058 GEN
Solar/Wind Helper
0.095
316236AE1-162_GEN
Solar/Wind Helper
0.317
238169AE2-226 GEN1
Solar/Wind Helper
0.563
238170AE2-226 GEN2
Solar/Wind Helper
0.563
316316AC1-027 C
Solar/Wind Helper
0.36
970241AG2-163 GEN
Solar/Wind Harmer
3.912
942111AE2-223 GEN
Solar/Wind Harmer
2.179
276645AC1-214 GEN1
Solar/Wind Harmer
0.263
274764LEE CO EC;5U
Adder
8.942
274765LEE CO EC;6U
Adder
8.942
274762LEE CO EC;3U
Adder
8.921
274763LEE CO EC;4U
Adder
8.837
938861AE1-114 GEN
Solar/Wind Harmer
3.787
972235AH1-702 GEN1
Adder
2.407
972236AH1-702 GEN2
Adder
2.093
971341AH1-150 GEN
Solar/Wind Harmer
13.301
971343AH1-151 GEN
Solar/Wind Harmer
13.301
926881AC1-175 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.75
962691AG1-118 GEN
Solar/Wind Harmer
19.833
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
9.908
274683WAUKEGAN ;8U
Adder
19.933
274683WAUKEGAN ;8U
Adder
16.802
274696ROCKY RD ;4P
Adder
10.774
274695ROCKY RD ;2P
Adder
10.525
274693ROCKY RD ;1P
Adder
10.421
274697ROCKY RD ;3P
Adder
2.859
958481AF2-142 GEN
Solar/Wind Harmer
9.873
971073AG2-665 GEN
Solar/Wind Harmer
4.818
970879AG2-548 GEN
Solar/Wind Harmer
1.095
971613AH1-306 GEN
Solar/Wind Harmer
3.152
970883AG2-550 GEN
Solar/Wind Harmer
6.563
970885AG2-551 GEN
Solar/Wind Harmer
2.188
253370AE2-315 SEC1
Adder
1.882
970291AG2-192 GEN
Solar/Wind Harmer
0.852
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
14.448
276893AG1-478 C
Solar/Wind Harmer
0.436
276897AD1-100 C
Solar/Wind Harmer
16.341
270031AE2-169
Solar/Wind Harmer
3.594
270599AE1-208 GEN
Solar/Wind Harmer
5.99
964611AG1-324 GEN
Solar/Wind Harmer
0.49
274888KELLY CRK;1U
Solar/Wind Harmer
0.38
276776AD2-060 GEN
Solar/Wind Harmer
0.696
958011AF2-095 GEN
Solar/Wind Harmer
9.391
970941AG2-585 GEN
Solar/Wind Harmer
3.587
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.431
960971AF2-388 GEN
Solar/Wind Harmer
3.788
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
2.563
965681AG1-436 GEN
Solar/Wind Harmer
7.912
965791AG1-447 GEN
Solar/Wind Harmer
5.802
970349AG2-230 GEN
Solar/Wind Harmer
9.433
3132123MT JACKSON
Solar/Wind Helper
1.089
966001AG1-469 GEN
Solar/Wind Helper
0.348
316045AC1-158 PL2
Solar/Wind Helper
5.375
316450AC1-158 RIC
Solar/Wind Helper
0.448
316313AB2-026
Solar/Wind Helper
0.46
316006AB2-029 C
Solar/Wind Helper
0.141
3143526WINTERP
Solar/Wind Helper
1.488
966871AG1-558 GEN
Solar/Wind Helper
0.386
316312AB1-027
Solar/Wind Helper
0.538
3146776BUCKING
Solar/Wind Helper
1.101
3146776BUCKING
Solar/Wind Helper
0.089
315976AC1-164 GENA
Solar/Wind Helper
3.495
316169AC1-164_GENC
Solar/Wind Helper
3.018
3142946ENON
Solar/Wind Helper
0.027
316487AF1-042 GEN
Solar/Wind Helper
0.269
316411AF1-147_GEN1
Solar/Wind Helper
0.888
315666AE1-190 GEN
Solar/Wind Helper
0.355
970563AG2-360 GEN
50/50
55.223
24415905BUCK
50/50
0.034
24689505VACITY
50/50
6.512
943031AE2-326 GEN
Solar/Wind Harmer
8.172
960911AF2-382 GEN
Solar/Wind Harmer
8.624
971461AH1-227 GEN
Solar/Wind Harmer
5.589
972103AH1-617 GEN
Solar/Wind Harmer
20.275
24686405CER G5
Adder
10.176
972273AH1-721 GEN
Adder
102.336
270030AE2-140 GEN
Solar/Wind Harmer
16.527
970093AG2-073 GEN
Solar/Wind Harmer
6.77
970653AG2-424 GEN
Solar/Wind Harmer
0.788
3429391JKCT 9G
Adder
9.312
970455AG2-298 GEN
Solar/Wind Harmer
3.03
972167AH1-666 GEN
Solar/Wind Harmer
5.868
958171AF2-111 GEN
Solar/Wind Harmer
18.095
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
17.911
25196008MFTGT1
Adder
1.345
252507AC2-088 GEN
Solar/Wind Harmer
0.312
942481AE2-261 GEN
Solar/Wind Harmer
20.643
957381AF2-032 GEN
Solar/Wind Harmer
1.564
252519AF1-045_GEN
Solar/Wind Harmer
3.59
25194608D.CRK4
Adder
1.616
970193AG2-126 GEN
Solar/Wind Harmer
10.285
25196608WSDLE5
Adder
8.414
24728505AND G1
Adder
3.754
971993AH1-541 GEN
Solar/Wind Harmer
3.15
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.857
965931AG1-462 GEN
Solar/Wind Harmer
17.272
971087AG2-675 GEN
Solar/Wind Harmer
3.613
965091AG1-374 GEN
Solar/Wind Harmer
20.199
959611AF2-252 GEN
Solar/Wind Harmer
2.244
253394AE2-221_GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.224
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.921
274767LEE CO EC;8U
Adder
8.816
970571AG2-364 GEN
Solar/Wind Harmer
13.32
959091AF2-200 GEN
Solar/Wind Harmer
13.301
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274855GSG-6 ;RU
Solar/Wind Harmer
0.242
274850MENDOTA H;RU
Solar/Wind Harmer
0.077
946671AF1-331 GEN
Solar/Wind Harmer
0.708
276868AE1-113 GEN
Solar/Wind Harmer
1.324
274879MINONK ;1U
Solar/Wind Harmer
0.276
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.43
274682WAUKEGAN ;7U
Adder
16.992
970825AG2-519 GEN
Solar/Wind Harmer
4.967
274862TOP CROP ;2U
Solar/Wind Harmer
0.889
946031AF1-268 GEN
Solar/Wind Harmer
6.263
943121AE2-341 GEN
Solar/Wind Harmer
11.021
943591AF1-030 GEN
Solar/Wind Harmer
7.329
970879AG2-548 GEN
Solar/Wind Harmer
4.818
253370AE2-315 SEC1
Adder
1.882
253371AE2-315 SEC2
Adder
1.78
970289AG2-191 GEN
Solar/Wind Harmer
0.721
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.551
247642Z2-115 C
Solar/Wind Harmer
0.003
274729ELWOOD EC;1P
Adder
15.424
274730ELWOOD EC;6P
Adder
15.424
274734ELWOOD EC;8P
Adder
15.424
274736ELWOOD EC;9P
Adder
15.424
274676JOLIET 29;8U
Adder
27.749
970191AG2-125 GEN
Solar/Wind Harmer
1.683
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
21.35
972259AH1-714 GEN
Adder
8.841
274887GEN-1.85
Solar/Wind Harmer
0.17
276843GEN-1.7
Solar/Wind Harmer
0.211
276806AD2-047 C O1
Solar/Wind Harmer
3.695
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
28.575
971347AH1-153 GEN
Solar/Wind Harmer
3.144
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270043AE2-236 GEN
Solar/Wind Harmer
3.982
270505AE1-170 C O1
Solar/Wind Harmer
6.495
3147312GRETNA
Solar/Wind Helper
0.316
3146802CHATHAM
Solar/Wind Helper
0.296
3147983MERCK5
Solar/Wind Helper
0.15
3147123OTTER R
Solar/Wind Helper
0.225
316192AB2-158 GEN
Solar/Wind Helper
2.162
3147666LOUISA
Solar/Wind Helper
1.282
316447AC1-158 HLD
Solar/Wind Helper
3.697
316044AC1-158 PL1
Solar/Wind Helper
1.68
3143226MDLTHAN
Solar/Wind Helper
0.29
3143526WINTERP
Solar/Wind Helper
1.488
3142416OLDCHRC
Solar/Wind Helper
0.732
3142416OLDCHRC
Solar/Wind Helper
0.28
3146776BUCKING
Solar/Wind Helper
0.11
3142543TWELFTH
Solar/Wind Helper
0.026
315975AC1-164 GENB
Solar/Wind Helper
0.103
316337AD2-073 GEN
Solar/Wind Helper
0.41
964211AG1-282 GEN
Solar/Wind Helper
0.361
3141726DUNNSVL
Solar/Wind Helper
1.072
316404AE1-155 C
Solar/Wind Helper
2.284
3142433PROV 92
Solar/Wind Helper
1.063
3141766HARMONY
Solar/Wind Helper
0.053
316415AF1-147_GEN2
Solar/Wind Helper
0.888
3138133OCRAN
Solar/Wind Helper
0.158
315662AE1-191 GEN
Solar/Wind Helper
1.419
316280AD1-041 GEN
Solar/Wind Helper
0.887
315671AE2-027_GEN
Solar/Wind Helper
2.046
238152AF2-075_GEN
Solar/Wind Helper
0.614
316132AB2-190 GEN1
Solar/Wind Helper
1.421
316369SG1_INVT
Solar/Wind Helper
1.181
3146926FARMVIL
Solar/Wind Helper
0.144
315773AC2-141 GEN
Solar/Wind Helper
5.077
3145336SMITFLD
Solar/Wind Helper
0.939
316381AD1-082 GEN
Solar/Wind Helper
1.199
316375AC2-012 GEN
Solar/Wind Helper
0.602
316036AC1-147 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.257
945111AF1-176 GEN
Solar/Wind Harmer
0.87
316156AD2-030 GEN
Solar/Wind Helper
0.397
237061AD1-155 GEN
Solar/Wind Helper
1.625
316240AF1-291 C
Solar/Wind Helper
0.345
238147AE2-230_GEN1
Solar/Wind Helper
0.43
238148AE2-230_GEN2
Solar/Wind Helper
0.43
238149AF1-291A_GEN
Solar/Wind Helper
0.123
316033AB2-134 GEN
Solar/Wind Helper
0.848
316294AC1-161 GEN
Solar/Wind Helper
4.313
316185AD1-033 GEN
Solar/Wind Helper
1.07
3145506HICKORY
Solar/Wind Helper
0.9
3145506HICKORY
Solar/Wind Helper
0.54
3145506HICKORY
Solar/Wind Helper
0.135
NYPJM->LTFIMP_NY
CLTF
3.354
LGEELTFEXP_LGEE->PJM
CLTF
7.385
WECLTFEXP_WEC->PJM
CLTF
3.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
133.236
CPLELTFEXP_CPLE->PJM
CLTF
4.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
44.745
CBM West 2LTFEXP_CBM-W2->PJM
CBM
145.987
MECLTFEXP_MEC->PJM
CLTF
16.891
SIGELTFEXP_SIGE->PJM
CLTF
0.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.326
LAGNLTFEXP_LAGN->PJM
CLTF
22.903
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.531
TVALTFEXP_TVA->PJM
CLTF
12.171

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4342.78
MW Contribution:
13.9
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.43 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4946.71
MW Contribution:
13.29
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
13.691
270120AB2-067 GEN2
50/50
13.691
270160DARBY CT5
50/50
0.825
270161DARBY CT6
50/50
0.813
270466AD2-091
50/50
8.422
25326109MON D
50/50
1.903
25326509SID D
50/50
1.895
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
8.674
938701AE1-092 GEN
Solar/Wind Harmer
16.303
971655AH1-328 GEN
Solar/Wind Harmer
3.602
270462AD2-086
Solar/Wind Harmer
0.001
270269AC2-059
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
4.181
25322209TAIT E
Adder
13.115
25322209TAIT E
Adder
12.82
253370AE2-315 SEC1
Adder
2.679
970349AG2-230 GEN
Solar/Wind Harmer
13.735
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.186
970291AG2-192 GEN
Solar/Wind Harmer
0.547
944541AF1-119 GEN
Solar/Wind Harmer
0.609
960971AF2-388 GEN
Solar/Wind Harmer
5.346
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
4.358
942221AE2-234 GEN
Solar/Wind Harmer
3.637
965681AG1-436 GEN
Solar/Wind Harmer
11.293
965791AG1-447 GEN
Solar/Wind Harmer
8.281
270031AE2-169
Solar/Wind Harmer
4.946
270599AE1-208 GEN
Solar/Wind Harmer
8.243
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.019
274770LINCOLN ;1U
Adder
10.86
274771LINCOLN ;2U
Adder
10.86
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270156DARBY CT1
50/50
0.841
270157DARBY CT2
50/50
0.839
270159DARBY CT4
50/50
0.828
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.265
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
7.494
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
4.282
943851AF1-053 GEN
Solar/Wind Harmer
2.966
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
4.521
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.422
241972AD1-140 GEN
Solar/Wind Harmer
1.102
253372AE2-315 SEC3
Adder
2.534
253372AE2-315 SEC3
Adder
2.534
270071AF1-092 GEN
Solar/Wind Harmer
17.821
25306009OHH W.
Adder
3.829
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.92
24729505KEY G4
Adder
8.54
970289AG2-191 GEN
Solar/Wind Harmer
1.733
971611AH1-305 GEN
Solar/Wind Harmer
5.423
959141AF2-205 GEN
Solar/Wind Harmer
0.001
958391AF2-133 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
6.362
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.671
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270051AF1-062 GEN
50/50
18.043
270475AD2-096_GEN
50/50
10.581
962771AG1-126 GEN
Solar/Wind Harmer
51.21
970153AG2-106 GEN
Solar/Wind Harmer
32.701
961921AG1-034 GEN
Solar/Wind Harmer
11.241
270284AF1-227 GEN1
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Harmer
20.261
270518AE2-148 GEN
Solar/Wind Harmer
0.888
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
970191AG2-125 GEN
Solar/Wind Harmer
2.379
944531AF1-118 GEN
Solar/Wind Harmer
41.277
270043AE2-236 GEN
Solar/Wind Harmer
5.885
247642Z2-115 C
Solar/Wind Harmer
0.004
971347AH1-153 GEN
Solar/Wind Harmer
4.578
970289AG2-191 GEN
Solar/Wind Harmer
1.003
253394AE2-221_GEN
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
3.029
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.079
24386205FR-12G C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
10.86
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.441
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.642
946031AF1-268 GEN
Solar/Wind Harmer
8.511
970825AG2-519 GEN
Solar/Wind Harmer
6.737
270004AE1-209 GEN
Solar/Wind Harmer
1.936
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
22.661
274752CRETE EC ;2U
Adder
10.545
274753CRETE EC ;3U
Adder
10.545
274814UNIV PK N;0U
Adder
6.452
274807UNIV PK N;3U
Adder
6.438
274811UNIV PK N;7U
Adder
6.396
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.288
276806AD2-047 C O1
Solar/Wind Harmer
5.041
970707AG2-453 GEN
Solar/Wind Harmer
29.056
274803UNIV PARK;6U
Adder
7.433
274826FISK ;BP
Adder
13.952
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
24.311
972038AH1-567 GEN2
Adder
0.465
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.319
270491AE1-102 GEN2
Solar/Wind Harmer
1.154
274676JOLIET 29;8U
Adder
37.578
274729ELWOOD EC;1P
Adder
20.872
274730ELWOOD EC;6P
Adder
20.872
274734ELWOOD EC;8P
Adder
20.872
274736ELWOOD EC;9P
Adder
20.872
270505AE1-170 C O1
Solar/Wind Harmer
9.267
943121AE2-341 GEN
Solar/Wind Harmer
14.798
943591AF1-030 GEN
Solar/Wind Harmer
9.841
945111AF1-176 GEN
Solar/Wind Harmer
7.15
24695305TIMB G C
Solar/Wind Harmer
0.747
274862TOP CROP ;2U
Solar/Wind Harmer
1.188
274682WAUKEGAN ;7U
Adder
22.607
276868AE1-113 GEN
Solar/Wind Harmer
1.751
274879MINONK ;1U
Solar/Wind Harmer
0.365
946671AF1-331 GEN
Solar/Wind Harmer
0.929
274855GSG-6 ;RU
Solar/Wind Harmer
0.318
274850MENDOTA H;RU
Solar/Wind Harmer
0.101
25196608WSDLE5
Adder
10.674
959091AF2-200 GEN
Solar/Wind Harmer
17.379
970571AG2-364 GEN
Solar/Wind Harmer
17.368
24728505AND G1
Adder
4.768
25194608D.CRK4
Adder
2.043
252519AF1-045_GEN
Solar/Wind Harmer
4.521
965091AG1-374 GEN
Solar/Wind Harmer
25.867
959611AF2-252 GEN
Solar/Wind Harmer
2.874
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.496
274767LEE CO EC;8U
Adder
11.361
970193AG2-126 GEN
Solar/Wind Harmer
12.901
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
252507AC2-088 GEN
Solar/Wind Harmer
0.384
971993AH1-541 GEN
Solar/Wind Harmer
3.929
25196008MFTGT1
Adder
1.643
965931AG1-462 GEN
Solar/Wind Harmer
21.621
971087AG2-675 GEN
Solar/Wind Harmer
4.522
957381AF2-032 GEN
Solar/Wind Harmer
1.898
942481AE2-261 GEN
Solar/Wind Harmer
25.023
270367AC2-061_GEN
Solar/Wind Harmer
-0.001
235058AG1-386 C
Solar/Wind Helper
0.575
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
962511AG1-100 GEN
Solar/Wind Helper
0.518
202652Y1-033 WT C
Solar/Wind Helper
0.576
20092526R32
Solar/Wind Helper
1.21
964991AG1-363 GEN
Solar/Wind Helper
3.728
20303426NA_O38_P22
Solar/Wind Helper
1.017
23562501BACKB
Solar/Wind Helper
0.893
203993AD2-133_GEN1
Solar/Wind Helper
1.055
203854AF2-039 C
Solar/Wind Helper
0.327
20398826ARMNA MT
Solar/Wind Helper
1.511
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.259
958171AF2-111 GEN
Solar/Wind Harmer
13.887
270201AC2-176 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.31
964611AG1-324 GEN
Solar/Wind Harmer
0.672
270246TR4_N_V150
Solar/Wind Harmer
0.057
270247TR4_N_V136
Solar/Wind Harmer
0.057
970883AG2-550 GEN
Solar/Wind Harmer
8.946
970885AG2-551 GEN
Solar/Wind Harmer
2.982
270383AD1-128 GEN
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
6.41
274808UNIV PK N;4U
Adder
6.368
274888KELLY CRK;1U
Solar/Wind Harmer
0.519
276776AD2-060 GEN
Solar/Wind Harmer
0.949
958011AF2-095 GEN
Solar/Wind Harmer
12.809
970941AG2-585 GEN
Solar/Wind Harmer
4.892
276897AD1-100 C
Solar/Wind Harmer
22.228
247620Y3-023
Adder
0.586
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.358
274674JOLIET 9 ;6U
Adder
19.549
276893AG1-478 C
Solar/Wind Harmer
0.591
970241AG2-163 GEN
Solar/Wind Harmer
5.155
958481AF2-142 GEN
Solar/Wind Harmer
13.2
961051AF2-396 GEN
Solar/Wind Harmer
17.567
961051AF2-396 GEN
Solar/Wind Harmer
11.711
274695ROCKY RD ;2P
Adder
14.015
274693ROCKY RD ;1P
Adder
13.877
274697ROCKY RD ;3P
Adder
3.807
274696ROCKY RD ;4P
Adder
14.346
274683WAUKEGAN ;8U
Adder
26.494
274683WAUKEGAN ;8U
Adder
22.333
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
13.148
962691AG1-118 GEN
Solar/Wind Harmer
26.273
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
17.379
971343AH1-151 GEN
Solar/Wind Harmer
17.379
247607V1-011 GEN
Solar/Wind Harmer
0
25194408D.CRK1
Adder
9.396
25194508D.CRK3
Adder
1.757
972235AH1-702 GEN1
Adder
3.131
972236AH1-702 GEN2
Adder
2.723
942111AE2-223 GEN
Solar/Wind Harmer
2.816
938861AE1-114 GEN
Solar/Wind Harmer
4.893
960611AF2-352 GEN
Solar/Wind Harmer
2.874
276645AC1-214 GEN1
Solar/Wind Harmer
0.338
274764LEE CO EC;5U
Adder
11.523
274765LEE CO EC;6U
Adder
11.523
274762LEE CO EC;3U
Adder
11.496
274763LEE CO EC;4U
Adder
11.388
945391AF1-204 GEN
Solar/Wind Harmer
9.138
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.387
252509AD1-136 GEN
Solar/Wind Harmer
0.043
276615X2-022 GEN
Solar/Wind Harmer
0.088
276838X2-022 GEN2
Solar/Wind Harmer
0.476
970623AG2-406 GEN
Solar/Wind Harmer
1.547
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.129
276916AD2-100_GEN
Solar/Wind Harmer
17.538
276911AD2-131_GEN
Solar/Wind Harmer
1.155
254304AE2-114 C
Solar/Wind Helper
0.274
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
241801AE1-079 GEN
Solar/Wind Helper
0.309
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
946071AF1-272 GEN
Solar/Wind Helper
2.879
203835AF1-098 GEN
Solar/Wind Helper
2.053
946381AF1-302 GEN
Solar/Wind Helper
0.237
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
203818AF1-086 GEN
Solar/Wind Helper
1.772
23585401KL_K28_T16
Solar/Wind Helper
1.267
203853AF1-134 C O1
Solar/Wind Helper
0.497
203804AE2-113_GEN
Solar/Wind Helper
1.84
23751201ROTHROCK
Solar/Wind Helper
0.733
203961AE2-224 GEN
Solar/Wind Helper
2.479
940863AE2-074 GEN
Solar/Wind Helper
0.479
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.672
203946AE2-131 C
Solar/Wind Helper
0.488
238117U2-030
Solar/Wind Helper
0.283
235531U2-073 GEN
Solar/Wind Helper
2.67
270166AC1-044 GEN3
50/50
13.691
962761AG1-125 GEN
Solar/Wind Harmer
51.21
970149AG2-104 GEN
Solar/Wind Harmer
27.654
970155AG2-107 GEN
Solar/Wind Harmer
32.701
270520AE2-214 GEN
Solar/Wind Harmer
0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
270273AD2-016 GEN
Solar/Wind Harmer
1.001
25326309TAIT D
Adder
1.474
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.673
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.387
971995AH1-542 GEN
Solar/Wind Harmer
3.337
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.826
958381AF2-132 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.938
965011AG1-365 GEN
Solar/Wind Harmer
9.088
270055AF2-134 C O1
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
10.169
270032AE2-172
Solar/Wind Harmer
6.053
970373AG2-245 GEN
Solar/Wind Harmer
19.061
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
10.066
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
10.86
274774LINCOLN ;5U
Adder
10.86
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.955
970825AG2-519 GEN
Solar/Wind Harmer
3.175
270005AE1-210 C O1
Solar/Wind Harmer
1.936
274723RIVER EC ;12
Adder
22.929
274751CRETE EC ;1U
Adder
10.545
274754CRETE EC ;4U
Adder
10.545
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963791AG1-232 GEN
Solar/Wind Harmer
12.161
971609AH1-304 GEN
Solar/Wind Harmer
1.469
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
10.86
274776LINCOLN ;7U
Adder
10.86
274777LINCOLN ;8U
Adder
10.86
270526AF1-158 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
3.493
247536S-71 GEN
Solar/Wind Harmer
0.358
247521TR3_G114
Solar/Wind Harmer
0.324
965051AG1-369 GEN
Solar/Wind Harmer
4.466
270543AE2-219 C
Solar/Wind Harmer
6.262
970031AG2-029 GEN
Solar/Wind Harmer
4.844
971771AH1-392 GEN
Solar/Wind Harmer
8.94
971029AG2-637 GEN
Solar/Wind Harmer
13.408
965041AG1-368 GEN
Solar/Wind Harmer
8.914
963841AG1-237 GEN
Solar/Wind Harmer
3.86
960591AF2-350 GEN
Solar/Wind Harmer
8.895
972228AH1-698 GEN2
Adder
4.722
972227AH1-698 GEN1
Adder
3.325
972037AH1-567 GEN1
Adder
0.233
274827FISK ;RP
Adder
9.888
274800UNIV PARK;3U
Adder
7.429
274801UNIV PARK;4U
Adder
7.429
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.124
274687WILL CNTY;4U
Adder
35.509
274687WILL CNTY;4U
Adder
35.509
274675JOLIET 29;7U
Adder
38.97
274675JOLIET 29;7U
Adder
37.578
274728ELWOOD EC;5P
Adder
20.872
274731ELWOOD EC;2P
Adder
20.872
274733ELWOOD EC;3P
Adder
20.872
274735ELWOOD EC;4P
Adder
20.872
970833AG2-524 GEN
Solar/Wind Harmer
9.741
970833AG2-524 GEN
Solar/Wind Harmer
6.494
274744AC1-111 GEN8
Adder
7.068
274746AC1-111 G10
Adder
7.068
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.922
270356AE2-297 GEN
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
8.736
971675AH1-338 GEN
Solar/Wind Harmer
3.397
276861AD2-134 GEN
Solar/Wind Harmer
0.155
276863AD2-134 GEN
Solar/Wind Harmer
0.155
971411AH1-196 GEN
Solar/Wind Harmer
13.063
25196408WSDLE3
Adder
10.988
971171AH1-044 GEN
Solar/Wind Harmer
17.379
926823AC1-168 GEN
Solar/Wind Harmer
1.477
270007AE1-245 C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
24.227
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.098
274856ECOGROVE ;U1
Solar/Wind Harmer
0.202
971681AH1-341 GEN
Solar/Wind Harmer
13.904
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
276741O09 GEN1
Solar/Wind Harmer
0.303
972267AH1-718 GEN
Adder
5.127
276668AB2-070 GEN1
Solar/Wind Harmer
0.334
276848AB2-070 GEN3
Solar/Wind Harmer
0.333
276849AB2-070 GEN2
Solar/Wind Harmer
0.334
25196108MFTGT2
Adder
1.87
25196108MFTGT2
Adder
1.736
946321AF1-296 GEN
Solar/Wind Harmer
4.758
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
241985AE1-237 GEN
Solar/Wind Helper
0.309
241982AE2-343 S C
Solar/Wind Helper
0.277
241997AF1-093 GEN
Solar/Wind Helper
0.312
23652301WDPWR_K20
Solar/Wind Helper
0.16
23750501ELLIOTTS
Solar/Wind Helper
0.695
203846AF2-130 C
Solar/Wind Helper
0.498
20089126CSLMN_L13
Solar/Wind Helper
0.613
20089226LOOKOUT
Solar/Wind Helper
0.611
20088926STNY CRK
Solar/Wind Helper
0.849
20094526CT_V3-030
Solar/Wind Helper
0.494
203955AF1-039 C O1
Solar/Wind Helper
0.38
203940AF1-140 C
Solar/Wind Helper
0.411
20088626ARWF_N39
Solar/Wind Helper
1.24
20334926Z1-069 C
Solar/Wind Helper
1.403
23750701CROSSCHOOL
Solar/Wind Helper
1.182
238118U2-030_1
Solar/Wind Helper
0.283
274812UNIV PK N;8U
Adder
6.396
24639705ELKHART HY
Adder
0.196
965421AG1-410 GEN
Solar/Wind Harmer
26.684
274802UNIV PARK;5U
Adder
7.433
941551AE2-152 GEN
Solar/Wind Harmer
0.001
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.512
246936BC-WTG1
Solar/Wind Harmer
0.358
270489AE1-102 GEN1
Solar/Wind Harmer
1.154
274676JOLIET 29;8U
Adder
38.97
274732ELWOOD EC;7P
Adder
20.872
274674JOLIET 9 ;6U
Adder
19.549
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
20.916
957891AF2-083 GEN
Solar/Wind Harmer
14.717
274745AC1-111 GEN9
Adder
7.068
945111AF1-176 GEN
Solar/Wind Harmer
15.739
939401AE1-172 GEN
Solar/Wind Harmer
6.59
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.43
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.607
274828WAUKEGAN ;BP
Adder
13.888
276805AD2-038 GEN
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
1.548
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.573
971997AH1-543 GEN
Solar/Wind Harmer
4.591
276882AE2-255 GEN
Solar/Wind Harmer
1.021
962781AG1-127 GEN
Solar/Wind Harmer
8.326
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
26.068
959081AF2-199 GEN
Solar/Wind Harmer
8.689
971067AG2-660 GEN
Solar/Wind Harmer
2.896
970569AG2-363 GEN
Solar/Wind Harmer
26.052
274822ROCKFORD ;11
Adder
24.404
24728605AND G2
Adder
4.768
25194608D.CRK4
Adder
2.043
252516AE2-318_GEN
Solar/Wind Harmer
9.707
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.131
970819AG2-516 GEN
Solar/Wind Harmer
10.388
252510AF1-249 C
Solar/Wind Harmer
0.065
276646AC1-214 GEN2
Solar/Wind Harmer
0.338
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.496
274766LEE CO EC;7U
Adder
11.361
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.303
25196808ZIMRHP
Adder
93.029
25196008MFTGT1
Adder
1.696
276621W2-048 GEN
Solar/Wind Harmer
0.423
965911AG1-460 GEN
Solar/Wind Harmer
1.674
970091AG2-072 GEN
Adder
16.07
254303AC2-168 GEN
Solar/Wind Helper
0.198
241966AE1-183 GEN
Solar/Wind Helper
0.312
961971AG1-040 GEN
Solar/Wind Helper
0.519
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.485
964201AG1-281 GEN
Solar/Wind Helper
0.498
238185AF2-356 C
Solar/Wind Helper
2.178
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.055
203952AE2-129 C
Solar/Wind Helper
0.488
203855AF2-088 C
Solar/Wind Helper
0.158
238126S14_GEN_1
Solar/Wind Helper
0.662
238120AE2-309 GEN
Solar/Wind Helper
0.416
23751101LEADS_P59
Solar/Wind Helper
1.832
NYPJM->LTFIMP_NY
CLTF
5.162
LGEELTFEXP_LGEE->PJM
CLTF
7.836
WECLTFEXP_WEC->PJM
CLTF
4.743
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.575
CPLELTFEXP_CPLE->PJM
CLTF
2.319
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.765
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.056
MECLTFEXP_MEC->PJM
CLTF
19.491
SIGELTFEXP_SIGE->PJM
CLTF
0.599
AG2-052LTFEXP_AG2-052->PJM
LTF
0.297
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446
LAGNLTFEXP_LAGN->PJM
CLTF
17.61
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.111
TVALTFEXP_TVA->PJM
CLTF
8.46

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4309.27
MW Contribution:
15.66
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:92.06 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3813.12
MW Contribution:
12.48
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
17.244
270120AB2-067 GEN2
50/50
17.244
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
270054AF2-122 C O1
Solar/Wind Harmer
0
942861AE2-305 GEN
Solar/Wind Harmer
10.655
270462AD2-086
Solar/Wind Harmer
0.002
938701AE1-092 GEN
Solar/Wind Harmer
21.46
971655AH1-328 GEN
Solar/Wind Harmer
4.742
970329AG2-216 GEN
Solar/Wind Harmer
5.083
25326509SID D
Adder
2.143
246937BC-WTG2
Solar/Wind Harmer
0.455
270246TR4_N_V150
Solar/Wind Harmer
0.071
270247TR4_N_V136
Solar/Wind Harmer
0.071
247607V1-011 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
16.464
247620Y3-023
Adder
0.71
965681AG1-436 GEN
Solar/Wind Harmer
13.426
965791AG1-447 GEN
Solar/Wind Harmer
9.845
970623AG2-406 GEN
Solar/Wind Harmer
1.96
961051AF2-396 GEN
Solar/Wind Harmer
21.315
961051AF2-396 GEN
Solar/Wind Harmer
14.21
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.994
942221AE2-234 GEN
Solar/Wind Harmer
4.232
944541AF1-119 GEN
Solar/Wind Harmer
0.7
960971AF2-388 GEN
Solar/Wind Harmer
6.145
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.914
944231AF1-091 GEN
Solar/Wind Harmer
24.097
274770LINCOLN ;1U
Adder
12.619
274771LINCOLN ;2U
Adder
12.619
270269AC2-059
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
7.439
274808UNIV PK N;4U
Adder
7.391
25322209TAIT E
Adder
14.396
25322209TAIT E
Adder
14.072
970291AG2-192 GEN
Solar/Wind Harmer
1.338
970291AG2-192 GEN
Solar/Wind Harmer
0.618
274888KELLY CRK;1U
Solar/Wind Harmer
0.6
276776AD2-060 GEN
Solar/Wind Harmer
1.097
958011AF2-095 GEN
Solar/Wind Harmer
14.803
970941AG2-585 GEN
Solar/Wind Harmer
5.654
276897AD1-100 C
Solar/Wind Harmer
25.624
971613AH1-306 GEN
Solar/Wind Harmer
4.9
274674JOLIET 9 ;6U
Adder
22.504
276893AG1-478 C
Solar/Wind Harmer
0.68
270031AE2-169
Solar/Wind Harmer
5.58
270599AE1-208 GEN
Solar/Wind Harmer
9.3
253370AE2-315 SEC1
Adder
2.904
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.147
270201AC2-176 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
15.103
247621Y3-024
Adder
0.348
964611AG1-324 GEN
Solar/Wind Harmer
0.754
274696ROCKY RD ;4P
Adder
16.391
274695ROCKY RD ;2P
Adder
16.014
274693ROCKY RD ;1P
Adder
15.856
274697ROCKY RD ;3P
Adder
4.35
274683WAUKEGAN ;8U
Adder
30.253
274683WAUKEGAN ;8U
Adder
25.502
958491AF2-143 GEN
Solar/Wind Harmer
14.984
962691AG1-118 GEN
Solar/Wind Harmer
29.945
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
9.92
970885AG2-551 GEN
Solar/Wind Harmer
3.307
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
19.677
971343AH1-151 GEN
Solar/Wind Harmer
19.677
972235AH1-702 GEN1
Adder
3.539
972236AH1-702 GEN2
Adder
3.077
270383AD1-128 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.694
938861AE1-114 GEN
Solar/Wind Harmer
5.51
274764LEE CO EC;5U
Adder
12.96
274765LEE CO EC;6U
Adder
12.96
274762LEE CO EC;3U
Adder
12.93
274763LEE CO EC;4U
Adder
12.808
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
3.143
276645AC1-214 GEN1
Solar/Wind Harmer
0.379
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.554
960611AF2-352 GEN
Solar/Wind Harmer
3.19
945391AF1-204 GEN
Solar/Wind Harmer
9.764
276615X2-022 GEN
Solar/Wind Harmer
0.095
276838X2-022 GEN2
Solar/Wind Harmer
0.516
25194408D.CRK1
Adder
9.313
25194508D.CRK3
Adder
1.741
972159AH1-661 GEN
Adder
1.225
23751201ROTHROCK
Solar/Wind Helper
0.691
23585401KL_K28_T16
Solar/Wind Helper
1.178
237043AE2-125 C
Solar/Wind Helper
0.16
24721605FLATG1
50/50
3.319
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
9.821
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.932
945631AF1-228 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
5.259
943851AF1-053 GEN
Solar/Wind Harmer
3.643
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.888
241972AD1-140 GEN
Solar/Wind Harmer
1.272
270432AC2-029 GEN
Solar/Wind Harmer
5.04
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.43
959331AF2-224 GEN
Solar/Wind Harmer
7.844
247521TR3_G114
Solar/Wind Harmer
0.403
965051AG1-369 GEN
Solar/Wind Harmer
5.558
270071AF1-092 GEN
Solar/Wind Harmer
21.261
965041AG1-368 GEN
Solar/Wind Harmer
11.063
270007AE1-245 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
5.889
970179AG2-119 GEN
Solar/Wind Harmer
9.709
971771AH1-392 GEN
Solar/Wind Harmer
10.756
963791AG1-232 GEN
Solar/Wind Harmer
14.514
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
9.953
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.264
274775LINCOLN ;6U
Adder
12.619
274776LINCOLN ;7U
Adder
12.619
274777LINCOLN ;8U
Adder
12.619
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.956
972037AH1-567 GEN1
Adder
0.27
274827FISK ;RP
Adder
11.436
960591AF2-350 GEN
Solar/Wind Harmer
10.28
274800UNIV PARK;3U
Adder
8.587
274801UNIV PARK;4U
Adder
8.587
972228AH1-698 GEN2
Adder
5.454
972227AH1-698 GEN1
Adder
3.84
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
40.93
274687WILL CNTY;4U
Adder
40.93
274675JOLIET 29;7U
Adder
44.89
274675JOLIET 29;7U
Adder
43.287
274728ELWOOD EC;5P
Adder
24.024
274731ELWOOD EC;2P
Adder
24.024
274733ELWOOD EC;3P
Adder
24.024
274735ELWOOD EC;4P
Adder
24.024
970833AG2-524 GEN
Solar/Wind Harmer
11.198
970833AG2-524 GEN
Solar/Wind Harmer
7.465
270377AD1-106 GEN
Solar/Wind Harmer
3.864
971609AH1-304 GEN
Solar/Wind Harmer
1.657
971549AH1-272 GEN
Solar/Wind Harmer
20.903
274744AC1-111 GEN8
Adder
8.105
274746AC1-111 G10
Adder
8.105
253372AE2-315 SEC3
Adder
2.747
253372AE2-315 SEC3
Adder
2.747
24386405FR-21G C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.923
25306009OHH W.
Adder
4.15
247536S-71 GEN
Solar/Wind Harmer
0.4
970073AG2-061 GEN
Solar/Wind Harmer
3.33
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.303
270543AE2-219 C
Solar/Wind Harmer
6.944
971675AH1-338 GEN
Solar/Wind Harmer
3.854
971411AH1-196 GEN
Solar/Wind Harmer
14.823
276861AD2-134 GEN
Solar/Wind Harmer
0.176
276863AD2-134 GEN
Solar/Wind Harmer
0.176
970169AG2-114 GEN
Solar/Wind Harmer
9.859
971171AH1-044 GEN
Solar/Wind Harmer
19.677
971029AG2-637 GEN
Solar/Wind Harmer
14.756
274823ROCKFORD ;21
Adder
27.402
926823AC1-168 GEN
Solar/Wind Harmer
1.667
274856ECOGROVE ;U1
Solar/Wind Harmer
0.228
971681AH1-341 GEN
Solar/Wind Harmer
15.659
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.156
972267AH1-718 GEN
Adder
5.748
276741O09 GEN1
Solar/Wind Harmer
0.34
274877BISHOP HL;1U
Solar/Wind Harmer
0.321
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.283
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.365
276848AB2-070 GEN3
Solar/Wind Harmer
0.363
276849AB2-070 GEN2
Solar/Wind Harmer
0.365
270263AC1-001 GEN
Solar/Wind Harmer
0.924
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.684
25196408WSDLE3
Adder
10.931
25196108MFTGT2
Adder
1.832
25196108MFTGT2
Adder
1.701
23750501ELLIOTTS
Solar/Wind Helper
0.6
23652301WDPWR_K20
Solar/Wind Helper
0.129
23750701CROSSCHOOL
Solar/Wind Helper
1.119
238118U2-030_1
Solar/Wind Helper
0.267
203955AF1-039 C O1
Solar/Wind Helper
0.331
235054AD2-180 GEN
Solar/Wind Helper
1.576
238117U2-030
Solar/Wind Helper
0.267
235531U2-073 GEN
Solar/Wind Helper
2.548
24721905FLATG4
50/50
3.319
24722005FLATG5
50/50
3.319
270051AF1-062 GEN
50/50
23.559
270475AD2-096_GEN
50/50
14.072
962771AG1-126 GEN
Solar/Wind Harmer
73.48
970153AG2-106 GEN
Solar/Wind Harmer
46.922
961921AG1-034 GEN
Solar/Wind Harmer
14.732
270284AF1-227 GEN1
Solar/Wind Harmer
0
270391AF1-285 GEN3
Solar/Wind Harmer
0.932
942051AE2-217 GEN
Solar/Wind Harmer
25.116
270518AE2-148 GEN
Solar/Wind Harmer
1.063
253325AC1-069 GEN
Solar/Wind Harmer
0.014
246938BC-WTG3
Solar/Wind Harmer
0.406
270491AE1-102 GEN2
Solar/Wind Harmer
1.468
965021AG1-366 GEN
Solar/Wind Harmer
3.735
270043AE2-236 GEN
Solar/Wind Harmer
7.125
24695305TIMB G C
Solar/Wind Harmer
0.934
971347AH1-153 GEN
Solar/Wind Harmer
5.488
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
48.343
971199AH1-059 GEN
Solar/Wind Harmer
2.255
270505AE1-170 C O1
Solar/Wind Harmer
11.228
945111AF1-176 GEN
Solar/Wind Harmer
8.665
964401AG1-302 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
8.236
274772LINCOLN ;3U
Adder
12.619
274752CRETE EC ;2U
Adder
12.279
274753CRETE EC ;3U
Adder
12.279
274724RIVER EC ;11
Adder
26.355
247642Z2-115 C
Solar/Wind Harmer
0.004
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.354
274814UNIV PK N;0U
Adder
7.488
274807UNIV PK N;3U
Adder
7.472
274811UNIV PK N;7U
Adder
7.423
970289AG2-191 GEN
Solar/Wind Harmer
1.133
274803UNIV PARK;6U
Adder
8.599
274826FISK ;BP
Adder
16.137
274887GEN-1.85
Solar/Wind Harmer
0.267
276843GEN-1.7
Solar/Wind Harmer
0.332
276806AD2-047 C O1
Solar/Wind Harmer
5.825
972038AH1-567 GEN2
Adder
0.538
970707AG2-453 GEN
Solar/Wind Harmer
33.528
972259AH1-714 GEN
Adder
28.051
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
43.287
274730ELWOOD EC;6P
Adder
24.024
274734ELWOOD EC;8P
Adder
24.024
274736ELWOOD EC;9P
Adder
24.024
274729ELWOOD EC;1P
Adder
24.024
970065AG2-057 GEN
Solar/Wind Harmer
1.014
943121AE2-341 GEN
Solar/Wind Harmer
16.972
943591AF1-030 GEN
Solar/Wind Harmer
11.286
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
24386205FR-12G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
2.597
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.132
274862TOP CROP ;2U
Solar/Wind Harmer
1.359
274682WAUKEGAN ;7U
Adder
25.826
276868AE1-113 GEN
Solar/Wind Harmer
1.991
274879MINONK ;1U
Solar/Wind Harmer
0.415
946031AF1-268 GEN
Solar/Wind Harmer
9.47
970825AG2-519 GEN
Solar/Wind Harmer
7.486
270004AE1-209 GEN
Solar/Wind Harmer
2.149
946671AF1-331 GEN
Solar/Wind Harmer
1.054
274855GSG-6 ;RU
Solar/Wind Harmer
0.361
274850MENDOTA H;RU
Solar/Wind Harmer
0.115
959091AF2-200 GEN
Solar/Wind Harmer
19.677
970571AG2-364 GEN
Solar/Wind Harmer
19.606
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.93
274767LEE CO EC;8U
Adder
12.777
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.321
965091AG1-374 GEN
Solar/Wind Harmer
28.713
959611AF2-252 GEN
Solar/Wind Harmer
3.19
253394AE2-221_GEN
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
23.963
971087AG2-675 GEN
Solar/Wind Harmer
5.012
971993AH1-541 GEN
Solar/Wind Harmer
4.285
24728505AND G1
Adder
5.071
970193AG2-126 GEN
Solar/Wind Harmer
13.784
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.737
270541AE2-072 C
Solar/Wind Harmer
0.001
957381AF2-032 GEN
Solar/Wind Harmer
2.038
25196608WSDLE5
Adder
10.619
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.61
23906502RICHG2&3
Adder
1.439
23906402RICHG1
Adder
1.437
237048AF1-022 C
Solar/Wind Helper
0.174
237046AF1-021 C
Solar/Wind Helper
0.304
964991AG1-363 GEN
Solar/Wind Helper
3.522
23562501BACKB
Solar/Wind Helper
0.847
235058AG1-386 C
Solar/Wind Helper
0.4
238127S14_GEN_2
Solar/Wind Helper
0.635
270166AC1-044 GEN3
50/50
17.244
24721705FLATG2
50/50
3.319
24721805FLATG3
50/50
3.319
962761AG1-125 GEN
Solar/Wind Harmer
73.48
970149AG2-104 GEN
Solar/Wind Harmer
39.681
970155AG2-107 GEN
Solar/Wind Harmer
46.922
270520AE2-214 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.014
971995AH1-542 GEN
Solar/Wind Harmer
4.575
246936BC-WTG1
Solar/Wind Harmer
0.455
270489AE1-102 GEN1
Solar/Wind Harmer
1.468
965421AG1-410 GEN
Solar/Wind Harmer
33.842
965011AG1-365 GEN
Solar/Wind Harmer
11.206
24639705ELKHART HY
Adder
0.237
957891AF2-083 GEN
Solar/Wind Harmer
17.821
945111AF1-176 GEN
Solar/Wind Harmer
19.076
970373AG2-245 GEN
Solar/Wind Harmer
22.382
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.553
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.746
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
13.152
965651AG1-433 GEN
Solar/Wind Harmer
3.072
274773LINCOLN ;4U
Adder
12.619
274774LINCOLN ;5U
Adder
12.619
958861AF2-177 GEN
Solar/Wind Harmer
4.506
274751CRETE EC ;1U
Adder
12.279
274754CRETE EC ;4U
Adder
12.279
270273AD2-016 GEN
Solar/Wind Harmer
1.064
274723RIVER EC ;12
Adder
26.668
270024AE2-089 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.423
25326309TAIT D
Adder
1.618
274802UNIV PARK;5U
Adder
8.599
945371AF1-202 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
44.89
270594AE1-207 GEN
Solar/Wind Harmer
11.433
270032AE2-172
Solar/Wind Harmer
6.805
274674JOLIET 9 ;6U
Adder
22.504
274732ELWOOD EC;7P
Adder
24.024
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
4.544
971201AH1-060 GEN
Solar/Wind Harmer
2.029
274745AC1-111 GEN9
Adder
8.105
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.636
274861TOP CROP ;1U
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
11.216
939401AE1-172 GEN
Solar/Wind Harmer
7.51
274682WAUKEGAN ;7U
Adder
25.826
274828WAUKEGAN ;BP
Adder
15.858
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.482
276882AE2-255 GEN
Solar/Wind Harmer
1.162
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.217
970825AG2-519 GEN
Solar/Wind Harmer
3.528
270005AE1-210 C O1
Solar/Wind Harmer
2.149
957471AF2-041 GEN
Solar/Wind Harmer
29.515
959081AF2-199 GEN
Solar/Wind Harmer
9.838
971067AG2-660 GEN
Solar/Wind Harmer
3.279
274822ROCKFORD ;11
Adder
27.602
970569AG2-363 GEN
Solar/Wind Harmer
29.408
970819AG2-516 GEN
Solar/Wind Harmer
11.727
963741AG1-226 GEN
Solar/Wind Harmer
23.101
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.93
274766LEE CO EC;7U
Adder
12.777
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.109
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
13.541
276646AC1-214 GEN2
Solar/Wind Harmer
0.379
276708O09 GEN2
Solar/Wind Harmer
0.34
274848CAMPGROVE;RU
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.647
24728605AND G2
Adder
5.071
276621W2-048 GEN
Solar/Wind Harmer
0.459
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.029
25194608D.CRK4
Adder
2.025
25196008MFTGT1
Adder
1.662
23906502RICHG2&3
Adder
1.439
25196808ZIMRHP
Adder
90.149
970091AG2-072 GEN
Adder
20.654
238185AF2-356 C
Solar/Wind Helper
2.037
23751101LEADS_P59
Solar/Wind Helper
1.839
238120AE2-309 GEN
Solar/Wind Helper
0.401
238126S14_GEN_1
Solar/Wind Helper
0.635
965911AG1-460 GEN
Solar/Wind Harmer
1.103
202652Y1-033 WT C
Solar/Wind Helper
0.501
942481AE2-261 GEN
Solar/Wind Harmer
16.491
NYPJM->LTFIMP_NY
CLTF
4.821
LGEELTFEXP_LGEE->PJM
CLTF
7.242
WECLTFEXP_WEC->PJM
CLTF
5.355
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.5
CBM West 2LTFEXP_CBM-W2->PJM
CBM
124.415
MECLTFEXP_MEC->PJM
CLTF
20.741
SIGELTFEXP_SIGE->PJM
CLTF
0.579
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.468
AG2-052LTFEXP_AG2-052->PJM
LTF
0.342
AH1-155LTFEXP_AH1-155->PJM
LTF
0.513
LAGNLTFEXP_LAGN->PJM
CLTF
14.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
TVALTFEXP_TVA->PJM
CLTF
6.29

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.48 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4638.62
MW Contribution:
15.0
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.435
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.401
965681AG1-436 GEN
Solar/Wind Harmer
13.215
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
276776AD2-060 GEN
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
14.407
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.66
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
28.923
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
270246TR4_N_V150
Solar/Wind Harmer
0.06
270247TR4_N_V136
Solar/Wind Harmer
0.06
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.429
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
960611AF2-352 GEN
Solar/Wind Harmer
2.992
970241AG2-163 GEN
Solar/Wind Harmer
5.219
971613AH1-306 GEN
Solar/Wind Harmer
4.231
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
270031AE2-169
Solar/Wind Harmer
4.725
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
276838X2-022 GEN2
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276916AD2-100_GEN
Solar/Wind Harmer
16.976
276911AD2-131_GEN
Solar/Wind Harmer
1.118
945391AF1-204 GEN
Solar/Wind Harmer
8.566
247621Y3-024
Adder
0.274
926881AC1-175 GEN
Solar/Wind Harmer
0
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
970885AG2-551 GEN
Solar/Wind Harmer
2.468
971587AH1-292 GEN
Solar/Wind Harmer
5.199
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
10.525
270526AF1-158 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274776LINCOLN ;7U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959331AF2-224 GEN
Solar/Wind Harmer
7.14
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
10.005
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
965041AG1-368 GEN
Solar/Wind Harmer
9.581
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
965051AG1-369 GEN
Solar/Wind Harmer
4.689
963791AG1-232 GEN
Solar/Wind Harmer
12.673
926823AC1-168 GEN
Solar/Wind Harmer
1.594
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
963841AG1-237 GEN
Solar/Wind Harmer
3.99
972267AH1-718 GEN
Adder
5.487
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
1.719
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
247536S-71 GEN
Solar/Wind Harmer
0.309
270543AE2-219 C
Solar/Wind Harmer
5.183
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.57
270356AE2-297 GEN
Solar/Wind Harmer
0
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274752CRETE EC ;2U
Adder
11.974
274753CRETE EC ;3U
Adder
11.974
274724RIVER EC ;11
Adder
25.717
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
276843GEN-1.7
Solar/Wind Harmer
0.323
276806AD2-047 C O1
Solar/Wind Harmer
5.669
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
44.295
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.86
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
24386205FR-12G C
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
18.917
970571AG2-364 GEN
Solar/Wind Harmer
18.75
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
246938BC-WTG3
Solar/Wind Harmer
0.328
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
0.995
965091AG1-374 GEN
Solar/Wind Harmer
26.927
959611AF2-252 GEN
Solar/Wind Harmer
2.992
965931AG1-462 GEN
Solar/Wind Harmer
22.694
971087AG2-675 GEN
Solar/Wind Harmer
4.746
971993AH1-541 GEN
Solar/Wind Harmer
3.947
957381AF2-032 GEN
Solar/Wind Harmer
1.851
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
270004AE1-209 GEN
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
6.118
946031AF1-268 GEN
Solar/Wind Harmer
7.675
970193AG2-126 GEN
Solar/Wind Harmer
12.093
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270541AE2-072 C
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
1.203
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
93.339
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970155AG2-107 GEN
Solar/Wind Harmer
59.604
957891AF2-083 GEN
Solar/Wind Harmer
17.358
970373AG2-245 GEN
Solar/Wind Harmer
21.825
945111AF1-176 GEN
Solar/Wind Harmer
18.541
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
274754CRETE EC ;4U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
7.225
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.154
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
28.375
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276708O09 GEN2
Solar/Wind Harmer
0.324
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.763
274848CAMPGROVE;RU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
963741AG1-226 GEN
Solar/Wind Harmer
21.176
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.571
276621W2-048 GEN
Solar/Wind Harmer
0.421
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.94 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4659.48
MW Contribution:
15.0
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
9.997
270142AC1-141 CT1_
50/50
3.606
24642205MAYFLWER
50/50
0.055
944961AF1-161 GEN
50/50
4.308
962601AG1-109 GEN
50/50
4.308
962771AG1-126 GEN
Solar/Wind Harmer
93.339
970153AG2-106 GEN
Solar/Wind Harmer
59.604
270284AF1-227 GEN1
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
5.467
270043AE2-236 GEN
Solar/Wind Harmer
6.82
270505AE1-170 C O1
Solar/Wind Harmer
10.944
945111AF1-176 GEN
Solar/Wind Harmer
8.423
270063AE2-323 C
Solar/Wind Harmer
0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274772LINCOLN ;3U
Adder
12.383
965021AG1-366 GEN
Solar/Wind Harmer
3.4
274752CRETE EC ;2U
Adder
11.974
274753CRETE EC ;3U
Adder
11.974
274724RIVER EC ;11
Adder
25.717
274814UNIV PK N;0U
Adder
7.296
274807UNIV PK N;3U
Adder
7.28
274811UNIV PK N;7U
Adder
7.232
274803UNIV PARK;6U
Adder
8.371
274826FISK ;BP
Adder
15.709
970707AG2-453 GEN
Solar/Wind Harmer
32.686
274887GEN-1.85
Solar/Wind Harmer
0.26
276843GEN-1.7
Solar/Wind Harmer
0.323
276806AD2-047 C O1
Solar/Wind Harmer
5.669
972038AH1-567 GEN2
Adder
0.523
972259AH1-714 GEN
Adder
27.313
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
42.062
274730ELWOOD EC;6P
Adder
23.325
274734ELWOOD EC;8P
Adder
23.325
274736ELWOOD EC;9P
Adder
23.325
274729ELWOOD EC;1P
Adder
23.324
944531AF1-118 GEN
Solar/Wind Harmer
44.295
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.86
943121AE2-341 GEN
Solar/Wind Harmer
16.469
943591AF1-030 GEN
Solar/Wind Harmer
10.952
274862TOP CROP ;2U
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.647
274682WAUKEGAN ;7U
Adder
24.977
276868AE1-113 GEN
Solar/Wind Harmer
1.916
274879MINONK ;1U
Solar/Wind Harmer
0.4
946671AF1-331 GEN
Solar/Wind Harmer
1.015
274855GSG-6 ;RU
Solar/Wind Harmer
0.347
274850MENDOTA H;RU
Solar/Wind Harmer
0.11
24386205FR-12G C
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
18.917
970571AG2-364 GEN
Solar/Wind Harmer
18.75
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.373
274767LEE CO EC;8U
Adder
12.227
247642Z2-115 C
Solar/Wind Harmer
0.004
24695305TIMB G C
Solar/Wind Harmer
0.78
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.305
246938BC-WTG3
Solar/Wind Harmer
0.328
270491AE1-102 GEN2
Solar/Wind Harmer
1.184
970289AG2-191 GEN
Solar/Wind Harmer
0.995
965091AG1-374 GEN
Solar/Wind Harmer
26.927
959611AF2-252 GEN
Solar/Wind Harmer
2.992
965931AG1-462 GEN
Solar/Wind Harmer
22.694
971087AG2-675 GEN
Solar/Wind Harmer
4.746
971993AH1-541 GEN
Solar/Wind Harmer
3.947
270102X2-052 ST
50/50
2.435
957381AF2-032 GEN
Solar/Wind Harmer
1.851
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.219
942481AE2-261 GEN
Solar/Wind Harmer
24.353
270004AE1-209 GEN
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
6.118
946031AF1-268 GEN
Solar/Wind Harmer
7.675
970193AG2-126 GEN
Solar/Wind Harmer
12.093
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.035
23906402RICHG1
Adder
1.058
23906502RICHG2&3
Adder
1.056
270541AE2-072 C
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
2.25
270101X2-052 CT2
50/50
2.25
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.727
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
16.401
965681AG1-436 GEN
Solar/Wind Harmer
13.215
965791AG1-447 GEN
Solar/Wind Harmer
9.691
961051AF2-396 GEN
Solar/Wind Harmer
20.719
961051AF2-396 GEN
Solar/Wind Harmer
13.812
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274770LINCOLN ;1U
Adder
12.383
274771LINCOLN ;2U
Adder
12.383
274805UNIV PK N;1U
Adder
7.248
274808UNIV PK N;4U
Adder
7.201
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.583
276776AD2-060 GEN
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
14.407
970941AG2-585 GEN
Solar/Wind Harmer
5.503
276897AD1-100 C
Solar/Wind Harmer
24.912
274674JOLIET 9 ;6U
Adder
21.855
276893AG1-478 C
Solar/Wind Harmer
0.66
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.593
274696ROCKY RD ;4P
Adder
15.857
274695ROCKY RD ;2P
Adder
15.492
274693ROCKY RD ;1P
Adder
15.339
274697ROCKY RD ;3P
Adder
4.208
274683WAUKEGAN ;8U
Adder
29.25
274683WAUKEGAN ;8U
Adder
24.656
962691AG1-118 GEN
Solar/Wind Harmer
28.923
958491AF2-143 GEN
Solar/Wind Harmer
14.434
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.076
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
18.917
971343AH1-151 GEN
Solar/Wind Harmer
18.917
972235AH1-702 GEN1
Adder
3.399
972236AH1-702 GEN2
Adder
2.955
270246TR4_N_V150
Solar/Wind Harmer
0.06
270247TR4_N_V136
Solar/Wind Harmer
0.06
938861AE1-114 GEN
Solar/Wind Harmer
5.277
274764LEE CO EC;5U
Adder
12.402
274765LEE CO EC;6U
Adder
12.402
274762LEE CO EC;3U
Adder
12.373
274763LEE CO EC;4U
Adder
12.256
944231AF1-091 GEN
Solar/Wind Harmer
21.381
270462AD2-086
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.618
24344105CKG2
50/50
12.076
270143AC1-141 CT2_
50/50
3.606
24639705ELKHART HY
50/50
0.243
970521AG2-332 GEN
50/50
17.34
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
93.339
970149AG2-104 GEN
Solar/Wind Harmer
50.405
970155AG2-107 GEN
Solar/Wind Harmer
59.604
957891AF2-083 GEN
Solar/Wind Harmer
17.358
970373AG2-245 GEN
Solar/Wind Harmer
21.825
945111AF1-176 GEN
Solar/Wind Harmer
18.541
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.398
270055AF2-134 C O1
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274773LINCOLN ;4U
Adder
12.383
274774LINCOLN ;5U
Adder
12.383
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.304
965011AG1-365 GEN
Solar/Wind Harmer
10.2
274751CRETE EC ;1U
Adder
11.974
274754CRETE EC ;4U
Adder
11.974
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
12.669
274723RIVER EC ;12
Adder
26.022
274812UNIV PK N;8U
Adder
7.232
274802UNIV PARK;5U
Adder
8.371
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
43.62
274674JOLIET 9 ;6U
Adder
21.855
274732ELWOOD EC;7P
Adder
23.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.861
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.581
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
24.977
274828WAUKEGAN ;BP
Adder
15.332
939401AE1-172 GEN
Solar/Wind Harmer
7.225
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
9.154
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.118
971997AH1-543 GEN
Solar/Wind Harmer
5.017
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
28.375
959081AF2-199 GEN
Solar/Wind Harmer
9.458
971067AG2-660 GEN
Solar/Wind Harmer
3.153
274822ROCKFORD ;11
Adder
26.521
970819AG2-516 GEN
Solar/Wind Harmer
11.253
970569AG2-363 GEN
Solar/Wind Harmer
28.125
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.373
274766LEE CO EC;7U
Adder
12.227
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.714
965421AG1-410 GEN
Solar/Wind Harmer
27.632
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276708O09 GEN2
Solar/Wind Harmer
0.324
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.763
274848CAMPGROVE;RU
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.367
270489AE1-102 GEN1
Solar/Wind Harmer
1.184
958861AF2-177 GEN
Solar/Wind Harmer
3.944
963741AG1-226 GEN
Solar/Wind Harmer
21.176
270594AE1-207 GEN
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
5.877
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
9.571
276621W2-048 GEN
Solar/Wind Harmer
0.421
965911AG1-460 GEN
Solar/Wind Harmer
1.629
270005AE1-210 C O1
Solar/Wind Harmer
1.763
970825AG2-519 GEN
Solar/Wind Harmer
2.883
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.555
24728605AND G2
Adder
4.035
970773AG2-487 GEN
Solar/Wind Harmer
1.216
970091AG2-072 GEN
Adder
69.079
23906502RICHG2&3
Adder
1.056
24344005CKG1
50/50
9.721
270144AC1-141 ST1_
50/50
3.196
24641605TWIN BRNCH
50/50
0.026
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
20.308
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
10.525
270526AF1-158 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.58
274775LINCOLN ;6U
Adder
12.383
274776LINCOLN ;7U
Adder
12.383
274777LINCOLN ;8U
Adder
12.383
958391AF2-133 GEN
Solar/Wind Harmer
0.002
959331AF2-224 GEN
Solar/Wind Harmer
7.14
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.034
972037AH1-567 GEN1
Adder
0.263
274827FISK ;RP
Adder
11.133
960591AF2-350 GEN
Solar/Wind Harmer
10.005
274800UNIV PARK;3U
Adder
8.357
274801UNIV PARK;4U
Adder
8.357
972228AH1-698 GEN2
Adder
5.307
972227AH1-698 GEN1
Adder
3.737
274687WILL CNTY;4U
Adder
39.781
274687WILL CNTY;4U
Adder
39.781
274675JOLIET 29;7U
Adder
43.621
274675JOLIET 29;7U
Adder
42.063
274728ELWOOD EC;5P
Adder
23.325
274731ELWOOD EC;2P
Adder
23.324
274733ELWOOD EC;3P
Adder
23.324
274735ELWOOD EC;4P
Adder
23.324
970833AG2-524 GEN
Solar/Wind Harmer
10.869
970833AG2-524 GEN
Solar/Wind Harmer
7.246
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274744AC1-111 GEN8
Adder
7.861
274746AC1-111 G10
Adder
7.861
24729505KEY G4
Adder
9.035
270578AF1-285 GEN2
Solar/Wind Harmer
0.647
970073AG2-061 GEN
Solar/Wind Harmer
3.208
971549AH1-272 GEN
Solar/Wind Harmer
19.814
965041AG1-368 GEN
Solar/Wind Harmer
9.581
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
14.274
971675AH1-338 GEN
Solar/Wind Harmer
3.711
276861AD2-134 GEN
Solar/Wind Harmer
0.169
276863AD2-134 GEN
Solar/Wind Harmer
0.169
24386405FR-21G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
18.917
274823ROCKFORD ;21
Adder
26.328
970169AG2-114 GEN
Solar/Wind Harmer
9.398
247521TR3_G114
Solar/Wind Harmer
0.34
965051AG1-369 GEN
Solar/Wind Harmer
4.689
963791AG1-232 GEN
Solar/Wind Harmer
12.673
926823AC1-168 GEN
Solar/Wind Harmer
1.594
274856ECOGROVE ;U1
Solar/Wind Harmer
0.219
971681AH1-341 GEN
Solar/Wind Harmer
14.998
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.303
963841AG1-237 GEN
Solar/Wind Harmer
3.99
972267AH1-718 GEN
Adder
5.487
276741O09 GEN1
Solar/Wind Harmer
0.324
274877BISHOP HL;1U
Solar/Wind Harmer
0.305
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.573
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.153
970289AG2-191 GEN
Solar/Wind Harmer
1.719
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.01
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.403
276668AB2-070 GEN1
Solar/Wind Harmer
0.336
276848AB2-070 GEN3
Solar/Wind Harmer
0.334
276849AB2-070 GEN2
Solar/Wind Harmer
0.336
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
3.17
944221AF1-090 GEN
Solar/Wind Harmer
4.619
247536S-71 GEN
Solar/Wind Harmer
0.309
270543AE2-219 C
Solar/Wind Harmer
5.183
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.57
270356AE2-297 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
5.429
942221AE2-234 GEN
Solar/Wind Harmer
3.695
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.481
942111AE2-223 GEN
Solar/Wind Harmer
2.963
246937BC-WTG2
Solar/Wind Harmer
0.367
970291AG2-192 GEN
Solar/Wind Harmer
1.176
970291AG2-192 GEN
Solar/Wind Harmer
0.543
960611AF2-352 GEN
Solar/Wind Harmer
2.992
970241AG2-163 GEN
Solar/Wind Harmer
5.219
971613AH1-306 GEN
Solar/Wind Harmer
4.231
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.574
270031AE2-169
Solar/Wind Harmer
4.725
270599AE1-208 GEN
Solar/Wind Harmer
7.874
276615X2-022 GEN
Solar/Wind Harmer
0.087
276838X2-022 GEN2
Solar/Wind Harmer
0.473
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.61
276916AD2-100_GEN
Solar/Wind Harmer
16.976
276911AD2-131_GEN
Solar/Wind Harmer
1.118
945391AF1-204 GEN
Solar/Wind Harmer
8.566
247621Y3-024
Adder
0.274
926881AC1-175 GEN
Solar/Wind Harmer
0
970621AG2-405 GEN
Solar/Wind Harmer
1.383
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.404
970885AG2-551 GEN
Solar/Wind Harmer
2.468
971587AH1-292 GEN
Solar/Wind Harmer
5.199
270054AF2-122 C O1
Solar/Wind Helper
1.203
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.087
NYPJM->LTFIMP_NY
CLTF
2.802
LGEELTFEXP_LGEE->PJM
CLTF
4.631
WECLTFEXP_WEC->PJM
CLTF
5.141
CBM West 1LTFEXP_CBM-W1->PJM
CBM
165.647
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.96
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.539
MECLTFEXP_MEC->PJM
CLTF
19.157
SIGELTFEXP_SIGE->PJM
CLTF
0.435
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.467
AG2-052LTFEXP_AG2-052->PJM
LTF
0.327
AH1-155LTFEXP_AH1-155->PJM
LTF
0.491
LAGNLTFEXP_LAGN->PJM
CLTF
11.508
TVALTFEXP_TVA->PJM
CLTF
4.677

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#GREENTOWN-TEDDY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#GREENTOWN-TEDDY_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.7 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5413.79
MW Contribution:
24.64
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.058
270100X2-052 CT1
50/50
2.825
270101X2-052 CT2
50/50
2.825
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
12.161
274771LINCOLN ;2U
50/50
12.161
247620Y3-023
50/50
0.898
970349AG2-230 GEN
Solar/Wind Harmer
30.128
965681AG1-436 GEN
Solar/Wind Harmer
23.727
965791AG1-447 GEN
Solar/Wind Harmer
12.14
961051AF2-396 GEN
Solar/Wind Harmer
29.38
961051AF2-396 GEN
Solar/Wind Harmer
13.665
274805UNIV PK N;1U
Adder
9.031
274808UNIV PK N;4U
Adder
8.972
274888KELLY CRK;1U
Solar/Wind Harmer
10.551
276776AD2-060 GEN
Solar/Wind Harmer
0.748
958011AF2-095 GEN
Solar/Wind Harmer
25.746
970941AG2-585 GEN
Solar/Wind Harmer
9.834
276897AD1-100 C
Solar/Wind Harmer
82.695
274674JOLIET 9 ;6U
Adder
27.209
276893AG1-478 C
Solar/Wind Harmer
0.774
270535AF1-215 GEN1
Solar/Wind Harmer
7.938
270536AF1-215 GEN2
Solar/Wind Harmer
7.938
274695ROCKY RD ;2P
Adder
19.235
274693ROCKY RD ;1P
Adder
19.046
274697ROCKY RD ;3P
Adder
5.225
274696ROCKY RD ;4P
Adder
19.689
958481AF2-142 GEN
Solar/Wind Harmer
25.905
274683WAUKEGAN ;8U
Adder
36.293
274683WAUKEGAN ;8U
Adder
30.593
962691AG1-118 GEN
Solar/Wind Harmer
51.409
960751AF2-366 GEN
Solar/Wind Harmer
4.903
958491AF2-143 GEN
Solar/Wind Harmer
25.552
276901AD2-066 C O1
Solar/Wind Harmer
5.96
971341AH1-150 GEN
Solar/Wind Harmer
33.478
971343AH1-151 GEN
Solar/Wind Harmer
33.478
276872AE1-163_GEN1
Solar/Wind Harmer
11.22
276876AE1-163_GEN2
Solar/Wind Harmer
11.22
972235AH1-702 GEN1
Adder
4.192
972236AH1-702 GEN2
Adder
3.645
938861AE1-114 GEN
Solar/Wind Harmer
13.462
274764LEE CO EC;5U
Adder
15.248
274765LEE CO EC;6U
Adder
15.248
274762LEE CO EC;3U
Adder
15.212
274763LEE CO EC;4U
Adder
15.069
247621Y3-024
Adder
0.288
270349AD2-093_GEN
Solar/Wind Helper
1.835
270471AD2-092_GEN
Solar/Wind Helper
1.835
946101AF1-275 GEN
Solar/Wind Helper
0.65
270054AF2-122 C O1
Solar/Wind Helper
1.32
270142AC1-141 CT1_
50/50
4.53
24642205MAYFLWER
50/50
0.069
274772LINCOLN ;3U
50/50
12.161
944961AF1-161 GEN
50/50
5.371
962601AG1-109 GEN
50/50
5.371
971347AH1-153 GEN
Solar/Wind Harmer
10.043
270043AE2-236 GEN
Solar/Wind Harmer
10.577
24441505OLIV SLR
Solar/Wind Harmer
0.252
247643Z2-116 C
Solar/Wind Harmer
0.131
270505AE1-170 C O1
Solar/Wind Harmer
28.028
945111AF1-176 GEN
Solar/Wind Harmer
10.497
270063AE2-323 C
Solar/Wind Harmer
3.999
274724RIVER EC ;11
Adder
32.107
972231SS25-0005
Solar/Wind Harmer
17.176
972181SS23-001
Solar/Wind Harmer
10.735
274752CRETE EC ;2U
Adder
8.846
274753CRETE EC ;3U
Adder
8.846
276164X3-005 C
Solar/Wind Harmer
1.268
274814UNIV PK N;0U
Adder
9.09
274807UNIV PK N;3U
Adder
9.07
274811UNIV PK N;7U
Adder
9.011
944531AF1-118 GEN
Solar/Wind Harmer
62.961
970707AG2-453 GEN
Solar/Wind Harmer
50.24
274803UNIV PARK;6U
Adder
10.432
274826FISK ;BP
Adder
19.587
274887GEN-1.85
Solar/Wind Harmer
9.526
276772AC2-154 GEN
Solar/Wind Harmer
4.99
276843GEN-1.7
Solar/Wind Harmer
1.025
276806AD2-047 C O1
Solar/Wind Harmer
19.127
972259AH1-714 GEN
Adder
34.103
972038AH1-567 GEN2
Adder
0.652
939351AE1-166 GEN
Solar/Wind Harmer
10.557
274676JOLIET 29;8U
Adder
52.392
274730ELWOOD EC;6P
Adder
29.026
274734ELWOOD EC;8P
Adder
29.026
274736ELWOOD EC;9P
Adder
29.026
274729ELWOOD EC;1P
Adder
29.025
943121AE2-341 GEN
Solar/Wind Harmer
26.3
943591AF1-030 GEN
Solar/Wind Harmer
17.534
274862TOP CROP ;2U
Solar/Wind Harmer
8.73
274682WAUKEGAN ;7U
Adder
30.998
964401AG1-302 GEN
Solar/Wind Harmer
15.516
276868AE1-113 GEN
Solar/Wind Harmer
17.138
274879MINONK ;1U
Solar/Wind Harmer
11.426
276799AD1-013 GEN
Solar/Wind Harmer
3.727
946671AF1-331 GEN
Solar/Wind Harmer
0.706
274855GSG-6 ;RU
Solar/Wind Harmer
6.223
274850MENDOTA H;RU
Solar/Wind Harmer
4.327
276602WESTBROOK C
Solar/Wind Harmer
3.583
959091AF2-200 GEN
Solar/Wind Harmer
33.478
965021AG1-366 GEN
Solar/Wind Harmer
3.873
970571AG2-364 GEN
Solar/Wind Harmer
32.97
274760LEE CO EC;1U
Adder
15.212
274767LEE CO EC;8U
Adder
15.033
24728505AND G1
Adder
4.166
270284AF1-227 GEN1
Solar/Wind Helper
2.228
270287AF1-227 GEN3
Solar/Wind Helper
0.817
274857EASY ROAD;U1
Solar/Wind Harmer
7.817
24344105CKG2
50/50
15.733
270143AC1-141 CT2_
50/50
4.53
24639705ELKHART HY
50/50
0.302
274773LINCOLN ;4U
50/50
12.161
274774LINCOLN ;5U
50/50
12.161
970521AG2-332 GEN
50/50
21.475
24307105BERRINSP G
50/50
0.04
270216AD2-079_GEN
Solar/Wind Harmer
1.137
957891AF2-083 GEN
Solar/Wind Harmer
27.973
945111AF1-176 GEN
Solar/Wind Harmer
33.122
972207SS24-0001
Solar/Wind Harmer
40.749
270449AD2-020 GEN
Solar/Wind Harmer
5.177
943021AE2-325 GEN
Solar/Wind Harmer
6.729
24441205WTRV SLR C
Solar/Wind Harmer
0.244
274723RIVER EC ;12
Adder
32.481
274751CRETE EC ;1U
Adder
8.846
274754CRETE EC ;4U
Adder
8.846
274812UNIV PK N;8U
Adder
9.011
274802UNIV PARK;5U
Adder
10.432
970373AG2-245 GEN
Solar/Wind Harmer
37.559
941551AE2-152 GEN
Solar/Wind Harmer
8.074
274676JOLIET 29;8U
Adder
54.332
274674JOLIET 9 ;6U
Adder
27.209
274732ELWOOD EC;7P
Adder
29.026
274871GR RIDGE ;2U
Solar/Wind Harmer
13.547
274847GR RIDGE ;BU
Solar/Wind Harmer
8.907
270055AF2-134 C O1
Solar/Wind Harmer
5.292
274745AC1-111 GEN9
Adder
9.782
276694AA1-018 GEN2
Solar/Wind Harmer
10.897
276691AA1-018 GEN1
Solar/Wind Harmer
1.302
274861TOP CROP ;1U
Solar/Wind Harmer
10.456
274682WAUKEGAN ;7U
Adder
30.998
274828WAUKEGAN ;BP
Adder
19.024
958381AF2-132 GEN
Solar/Wind Harmer
15.516
962781AG1-127 GEN
Solar/Wind Harmer
16.251
939401AE1-172 GEN
Solar/Wind Harmer
23.79
964861AG1-349 GEN
Solar/Wind Harmer
13.413
971917AH1-482 GEN
Solar/Wind Harmer
15.475
274872LEEDK;1U
Solar/Wind Harmer
13.992
276805AD2-038 GEN
Solar/Wind Harmer
8.735
276882AE2-255 GEN
Solar/Wind Harmer
5.713
971997AH1-543 GEN
Solar/Wind Harmer
26.614
957471AF2-041 GEN
Solar/Wind Harmer
50.217
959081AF2-199 GEN
Solar/Wind Harmer
16.739
971067AG2-660 GEN
Solar/Wind Harmer
3.893
274822ROCKFORD ;11
Adder
32.73
965011AG1-365 GEN
Solar/Wind Harmer
16.653
970819AG2-516 GEN
Solar/Wind Harmer
19.884
940581AE2-045 GEN
Solar/Wind Harmer
16.88
971605AH1-302 GEN
Solar/Wind Harmer
14.433
970569AG2-363 GEN
Solar/Wind Harmer
49.456
274761LEE CO EC;2U
Adder
15.212
274766LEE CO EC;7U
Adder
15.033
24728605AND G2
Adder
4.166
970091AG2-072 GEN
Adder
67.129
270520AE2-214 GEN
Solar/Wind Helper
2.6
270286AF1-227 GEN2
Solar/Wind Helper
0.817
274858EASY ROAD;U2
Solar/Wind Harmer
7.817
24344005CKG1
50/50
12.247
270144AC1-141 ST1_
50/50
4.015
24641605TWIN BRNCH
50/50
0.032
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
12.161
274776LINCOLN ;7U
50/50
12.161
274777LINCOLN ;8U
50/50
12.161
960681AF2-359 GEN
Solar/Wind Harmer
7.172
971771AH1-392 GEN
Solar/Wind Harmer
17.021
270526AF1-158 GEN
Solar/Wind Harmer
8.553
270071AF1-092 GEN
Solar/Wind Harmer
27.991
944161AF1-084 GEN
Solar/Wind Harmer
4.059
970031AG2-029 GEN
Solar/Wind Harmer
44.798
972037AH1-567 GEN1
Adder
0.327
274827FISK ;RP
Adder
13.882
960591AF2-350 GEN
Solar/Wind Harmer
17.879
274800UNIV PARK;3U
Adder
10.418
274801UNIV PARK;4U
Adder
10.418
972228AH1-698 GEN2
Adder
6.619
972227AH1-698 GEN1
Adder
4.661
274687WILL CNTY;4U
Adder
49.553
274687WILL CNTY;4U
Adder
49.553
274675JOLIET 29;7U
Adder
54.333
274675JOLIET 29;7U
Adder
52.393
274728ELWOOD EC;5P
Adder
29.026
274731ELWOOD EC;2P
Adder
29.025
274733ELWOOD EC;3P
Adder
29.025
274735ELWOOD EC;4P
Adder
29.025
276893AG1-478 C
Solar/Wind Harmer
0.971
970833AG2-524 GEN
Solar/Wind Harmer
15.389
970833AG2-524 GEN
Solar/Wind Harmer
7.158
24729505KEY G4
Adder
11.373
274744AC1-111 GEN8
Adder
9.782
274746AC1-111 G10
Adder
9.782
970073AG2-061 GEN
Solar/Wind Harmer
3.962
958391AF2-133 GEN
Solar/Wind Harmer
15.328
971411AH1-196 GEN
Solar/Wind Harmer
25.298
971675AH1-338 GEN
Solar/Wind Harmer
30.351
276861AD2-134 GEN
Solar/Wind Harmer
3.009
276863AD2-134 GEN
Solar/Wind Harmer
3.009
274863CRW1-WTG
Solar/Wind Harmer
9.359
274864CRW2-WTG
Solar/Wind Harmer
9.359
959141AF2-205 GEN
Solar/Wind Harmer
10.125
971171AH1-044 GEN
Solar/Wind Harmer
33.478
971549AH1-272 GEN
Solar/Wind Harmer
30.938
276889AE2-281 GEN
Solar/Wind Harmer
3.206
274823ROCKFORD ;21
Adder
32.492
959331AF2-224 GEN
Solar/Wind Harmer
16.653
274856ECOGROVE ;U1
Solar/Wind Harmer
5.577
276611AD2-172 GEN
Solar/Wind Harmer
4.231
276612AE2-035 GEN
Solar/Wind Harmer
4.231
926823AC1-168 GEN
Solar/Wind Harmer
7.084
970169AG2-114 GEN
Solar/Wind Harmer
16.447
971681AH1-341 GEN
Solar/Wind Harmer
24.643
972267AH1-718 GEN
Adder
6.732
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.291
NYPJM->LTFIMP_NY
CLTF
2.831
LGEELTFEXP_LGEE->PJM
CLTF
3.802
WECLTFEXP_WEC->PJM
CLTF
6.34
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.577
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.518
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.817
MECLTFEXP_MEC->PJM
CLTF
22.833
SIGELTFEXP_SIGE->PJM
CLTF
0.424
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.778
AG2-052LTFEXP_AG2-052->PJM
LTF
0.395
AH1-155LTFEXP_AH1-155->PJM
LTF
0.593
LAGNLTFEXP_LAGN->PJM
CLTF
12.121
TVALTFEXP_TVA->PJM
CLTF
4.571

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.92 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5008.41
MW Contribution:
18.45
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.058
270100X2-052 CT1
50/50
2.825
270101X2-052 CT2
50/50
2.825
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
16.554
274771LINCOLN ;2U
50/50
16.554
247620Y3-023
50/50
0.898
970349AG2-230 GEN
Solar/Wind Harmer
21.02
965681AG1-436 GEN
Solar/Wind Harmer
16.554
965791AG1-447 GEN
Solar/Wind Harmer
12.14
961051AF2-396 GEN
Solar/Wind Harmer
25.827
961051AF2-396 GEN
Solar/Wind Harmer
17.218
274805UNIV PK N;1U
Adder
9.031
274808UNIV PK N;4U
Adder
8.972
274888KELLY CRK;1U
Solar/Wind Harmer
0.727
276776AD2-060 GEN
Solar/Wind Harmer
1.331
958011AF2-095 GEN
Solar/Wind Harmer
17.963
970941AG2-585 GEN
Solar/Wind Harmer
6.861
276897AD1-100 C
Solar/Wind Harmer
31.049
274674JOLIET 9 ;6U
Adder
27.209
276893AG1-478 C
Solar/Wind Harmer
0.821
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274695ROCKY RD ;2P
Adder
19.235
274693ROCKY RD ;1P
Adder
19.046
274697ROCKY RD ;3P
Adder
5.225
274696ROCKY RD ;4P
Adder
19.689
958481AF2-142 GEN
Solar/Wind Harmer
18.073
274683WAUKEGAN ;8U
Adder
36.293
274683WAUKEGAN ;8U
Adder
30.593
962691AG1-118 GEN
Solar/Wind Harmer
35.867
958491AF2-143 GEN
Solar/Wind Harmer
17.827
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
23.357
971343AH1-151 GEN
Solar/Wind Harmer
23.357
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
4.192
972236AH1-702 GEN2
Adder
3.645
938861AE1-114 GEN
Solar/Wind Harmer
6.492
274764LEE CO EC;5U
Adder
15.248
274765LEE CO EC;6U
Adder
15.248
274762LEE CO EC;3U
Adder
15.212
274763LEE CO EC;4U
Adder
15.069
944541AF1-119 GEN
Solar/Wind Harmer
0.758
960971AF2-388 GEN
Solar/Wind Harmer
6.656
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.814
276645AC1-214 GEN1
Solar/Wind Harmer
0.44
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
3.572
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
3.589
942221AE2-234 GEN
Solar/Wind Harmer
4.268
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.188
944231AF1-091 GEN
Solar/Wind Harmer
23.789
276615X2-022 GEN
Solar/Wind Harmer
0.102
276838X2-022 GEN2
Solar/Wind Harmer
0.554
970291AG2-192 GEN
Solar/Wind Harmer
1.278
970291AG2-192 GEN
Solar/Wind Harmer
0.59
970241AG2-163 GEN
Solar/Wind Harmer
5.718
270031AE2-169
Solar/Wind Harmer
5.389
270599AE1-208 GEN
Solar/Wind Harmer
8.982
971613AH1-306 GEN
Solar/Wind Harmer
4.613
276916AD2-100_GEN
Solar/Wind Harmer
19.611
276911AD2-131_GEN
Solar/Wind Harmer
1.292
270246TR4_N_V150
Solar/Wind Harmer
0.058
270247TR4_N_V136
Solar/Wind Harmer
0.058
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.661
270201AC2-176 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
9.248
247621Y3-024
Adder
0.288
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.371
270142AC1-141 CT1_
50/50
4.53
24642205MAYFLWER
50/50
0.069
274772LINCOLN ;3U
50/50
16.554
944961AF1-161 GEN
50/50
5.371
962601AG1-109 GEN
50/50
5.371
971347AH1-153 GEN
Solar/Wind Harmer
7.007
270043AE2-236 GEN
Solar/Wind Harmer
8.609
270505AE1-170 C O1
Solar/Wind Harmer
13.688
945111AF1-176 GEN
Solar/Wind Harmer
10.497
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
32.107
274752CRETE EC ;2U
Adder
14.913
274753CRETE EC ;3U
Adder
14.913
274814UNIV PK N;0U
Adder
9.09
274807UNIV PK N;3U
Adder
9.07
274811UNIV PK N;7U
Adder
9.011
944531AF1-118 GEN
Solar/Wind Harmer
56.246
970707AG2-453 GEN
Solar/Wind Harmer
40.893
274803UNIV PARK;6U
Adder
10.432
274826FISK ;BP
Adder
19.587
274887GEN-1.85
Solar/Wind Harmer
0.324
276843GEN-1.7
Solar/Wind Harmer
0.403
276806AD2-047 C O1
Solar/Wind Harmer
7.069
972259AH1-714 GEN
Adder
34.103
972038AH1-567 GEN2
Adder
0.652
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
52.392
274730ELWOOD EC;6P
Adder
29.026
274734ELWOOD EC;8P
Adder
29.026
274736ELWOOD EC;9P
Adder
29.026
274729ELWOOD EC;1P
Adder
29.025
943121AE2-341 GEN
Solar/Wind Harmer
20.51
943591AF1-030 GEN
Solar/Wind Harmer
13.64
274862TOP CROP ;2U
Solar/Wind Harmer
1.626
274682WAUKEGAN ;7U
Adder
30.998
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
2.364
274879MINONK ;1U
Solar/Wind Harmer
0.493
946671AF1-331 GEN
Solar/Wind Harmer
1.255
274855GSG-6 ;RU
Solar/Wind Harmer
0.429
274850MENDOTA H;RU
Solar/Wind Harmer
0.137
959091AF2-200 GEN
Solar/Wind Harmer
23.357
965021AG1-366 GEN
Solar/Wind Harmer
3.873
970571AG2-364 GEN
Solar/Wind Harmer
23.003
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
15.212
274767LEE CO EC;8U
Adder
15.033
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.946
965931AG1-462 GEN
Solar/Wind Harmer
27.64
971087AG2-675 GEN
Solar/Wind Harmer
5.781
965091AG1-374 GEN
Solar/Wind Harmer
32.301
959611AF2-252 GEN
Solar/Wind Harmer
3.589
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
4.642
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.081
957381AF2-032 GEN
Solar/Wind Harmer
2.147
942481AE2-261 GEN
Solar/Wind Harmer
28.217
270004AE1-209 GEN
Solar/Wind Harmer
1.995
970825AG2-519 GEN
Solar/Wind Harmer
6.765
24344105CKG2
50/50
15.733
270143AC1-141 CT2_
50/50
4.53
24639705ELKHART HY
50/50
0.302
274773LINCOLN ;4U
50/50
16.554
274774LINCOLN ;5U
50/50
16.554
970521AG2-332 GEN
50/50
21.475
24307105BERRINSP G
50/50
0.04
957891AF2-083 GEN
Solar/Wind Harmer
21.685
945111AF1-176 GEN
Solar/Wind Harmer
23.109
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.729
274723RIVER EC ;12
Adder
32.481
274751CRETE EC ;1U
Adder
14.913
274754CRETE EC ;4U
Adder
14.913
274812UNIV PK N;8U
Adder
9.011
274802UNIV PARK;5U
Adder
10.432
970373AG2-245 GEN
Solar/Wind Harmer
26.204
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
54.332
274674JOLIET 9 ;6U
Adder
27.209
274732ELWOOD EC;7P
Adder
29.026
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.782
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.958
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
30.998
274828WAUKEGAN ;BP
Adder
19.024
958381AF2-132 GEN
Solar/Wind Harmer
0.002
962781AG1-127 GEN
Solar/Wind Harmer
11.346
939401AE1-172 GEN
Solar/Wind Harmer
8.909
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
15.475
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.379
971997AH1-543 GEN
Solar/Wind Harmer
6.189
957471AF2-041 GEN
Solar/Wind Harmer
35.035
959081AF2-199 GEN
Solar/Wind Harmer
11.678
971067AG2-660 GEN
Solar/Wind Harmer
3.893
274822ROCKFORD ;11
Adder
32.73
965011AG1-365 GEN
Solar/Wind Harmer
11.618
970819AG2-516 GEN
Solar/Wind Harmer
13.872
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
14.433
970569AG2-363 GEN
Solar/Wind Harmer
34.504
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
15.212
274766LEE CO EC;7U
Adder
15.033
965651AG1-433 GEN
Solar/Wind Harmer
3.328
276708O09 GEN2
Solar/Wind Harmer
0.397
276646AC1-214 GEN2
Solar/Wind Harmer
0.44
274848CAMPGROVE;RU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.79
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
15.389
945371AF1-202 GEN
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.492
963741AG1-226 GEN
Solar/Wind Harmer
23.2
270594AE1-207 GEN
Solar/Wind Harmer
10.763
270032AE2-172
Solar/Wind Harmer
6.407
270024AE2-089 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.887
276903AD2-071 C
Solar/Wind Harmer
10.328
270005AE1-210 C O1
Solar/Wind Harmer
1.995
970825AG2-519 GEN
Solar/Wind Harmer
3.188
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.023
24728605AND G2
Adder
4.166
965421AG1-410 GEN
Solar/Wind Harmer
22.186
246936BC-WTG1
Solar/Wind Harmer
0.28
270489AE1-102 GEN1
Solar/Wind Harmer
0.903
970773AG2-487 GEN
Solar/Wind Harmer
1.206
970091AG2-072 GEN
Adder
67.129
270520AE2-214 GEN
Solar/Wind Helper
2.6
270286AF1-227 GEN2
Solar/Wind Helper
0.817
970883AG2-550 GEN
Solar/Wind Harmer
7.415
970885AG2-551 GEN
Solar/Wind Harmer
2.472
971587AH1-292 GEN
Solar/Wind Harmer
5.408
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.28
270349AD2-093_GEN
Solar/Wind Helper
1.835
270471AD2-092_GEN
Solar/Wind Helper
1.835
946101AF1-275 GEN
Solar/Wind Helper
0.65
270054AF2-122 C O1
Solar/Wind Helper
1.32
24344005CKG1
50/50
12.247
270144AC1-141 ST1_
50/50
4.015
24641605TWIN BRNCH
50/50
0.032
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
16.554
274776LINCOLN ;7U
50/50
16.554
274777LINCOLN ;8U
50/50
16.554
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
13.194
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
24.953
970031AG2-029 GEN
Solar/Wind Harmer
6.772
972037AH1-567 GEN1
Adder
0.327
274827FISK ;RP
Adder
13.882
960591AF2-350 GEN
Solar/Wind Harmer
12.474
274800UNIV PARK;3U
Adder
10.418
274801UNIV PARK;4U
Adder
10.418
972228AH1-698 GEN2
Adder
6.619
972227AH1-698 GEN1
Adder
4.661
274687WILL CNTY;4U
Adder
49.553
274687WILL CNTY;4U
Adder
49.553
274675JOLIET 29;7U
Adder
54.333
274675JOLIET 29;7U
Adder
52.393
274728ELWOOD EC;5P
Adder
29.026
274731ELWOOD EC;2P
Adder
29.025
274733ELWOOD EC;3P
Adder
29.025
274735ELWOOD EC;4P
Adder
29.025
970833AG2-524 GEN
Solar/Wind Harmer
13.528
970833AG2-524 GEN
Solar/Wind Harmer
9.019
24729505KEY G4
Adder
11.373
274744AC1-111 GEN8
Adder
9.782
274746AC1-111 G10
Adder
9.782
970073AG2-061 GEN
Solar/Wind Harmer
3.962
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971411AH1-196 GEN
Solar/Wind Harmer
17.649
971675AH1-338 GEN
Solar/Wind Harmer
4.588
276861AD2-134 GEN
Solar/Wind Harmer
0.21
276863AD2-134 GEN
Solar/Wind Harmer
0.21
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
23.357
971549AH1-272 GEN
Solar/Wind Harmer
24.093
274823ROCKFORD ;21
Adder
32.492
959331AF2-224 GEN
Solar/Wind Harmer
8.133
971611AH1-305 GEN
Solar/Wind Harmer
6.874
274856ECOGROVE ;U1
Solar/Wind Harmer
0.27
926823AC1-168 GEN
Solar/Wind Harmer
1.955
970169AG2-114 GEN
Solar/Wind Harmer
11.475
971681AH1-341 GEN
Solar/Wind Harmer
18.454
972267AH1-718 GEN
Adder
6.732
276741O09 GEN1
Solar/Wind Harmer
0.397
274877BISHOP HL;1U
Solar/Wind Harmer
0.372
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
11.542
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.109
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
14.195
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.388
276668AB2-070 GEN1
Solar/Wind Harmer
0.395
276848AB2-070 GEN3
Solar/Wind Harmer
0.393
276849AB2-070 GEN2
Solar/Wind Harmer
0.395
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
9.911
970289AG2-191 GEN
Solar/Wind Harmer
1.868
971609AH1-304 GEN
Solar/Wind Harmer
1.601
247521TR3_G114
Solar/Wind Harmer
0.327
965051AG1-369 GEN
Solar/Wind Harmer
4.503
944221AF1-090 GEN
Solar/Wind Harmer
5.281
964611AG1-324 GEN
Solar/Wind Harmer
3.439
247536S-71 GEN
Solar/Wind Harmer
0.321
270543AE2-219 C
Solar/Wind Harmer
5.19
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.88
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.12
946031AF1-268 GEN
Solar/Wind Harmer
8.435
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.208
24695305TIMB G C
Solar/Wind Harmer
0.74
970193AG2-126 GEN
Solar/Wind Harmer
13.057
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728505AND G1
Adder
4.166
246938BC-WTG3
Solar/Wind Harmer
0.25
270491AE1-102 GEN2
Solar/Wind Harmer
0.903
270284AF1-227 GEN1
Solar/Wind Helper
2.228
270287AF1-227 GEN3
Solar/Wind Helper
0.817
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.291
NYPJM->LTFIMP_NY
CLTF
2.831
LGEELTFEXP_LGEE->PJM
CLTF
3.802
WECLTFEXP_WEC->PJM
CLTF
6.34
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.577
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.817
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.518
MECLTFEXP_MEC->PJM
CLTF
22.833
SIGELTFEXP_SIGE->PJM
CLTF
0.424
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.778
AG2-052LTFEXP_AG2-052->PJM
LTF
0.395
AH1-155LTFEXP_AH1-155->PJM
LTF
0.593
LAGNLTFEXP_LAGN->PJM
CLTF
12.121
TVALTFEXP_TVA->PJM
CLTF
4.571

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.91 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4759.65
MW Contribution:
21.98
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:160.5 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6648.0
MW Contribution:
11.09
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
11.061
270144AC1-141 ST1_
50/50
3.636
24641605TWIN BRNCH
50/50
0.029
24653605MOTTVILLE
50/50
0.006
24729505KEY G4
50/50
11.404
971771AH1-392 GEN
Solar/Wind Harmer
15.361
270071AF1-092 GEN
Solar/Wind Harmer
25.452
960681AF2-359 GEN
Solar/Wind Harmer
6.402
270526AF1-158 GEN
Solar/Wind Harmer
7.683
944161AF1-084 GEN
Solar/Wind Harmer
3.677
970031AG2-029 GEN
Solar/Wind Harmer
41.499
274775LINCOLN ;6U
Adder
10.256
274776LINCOLN ;7U
Adder
10.256
274777LINCOLN ;8U
Adder
10.256
959331AF2-224 GEN
Solar/Wind Harmer
16.013
972037AH1-567 GEN1
Adder
0.293
274827FISK ;RP
Adder
12.403
960591AF2-350 GEN
Solar/Wind Harmer
15.977
972228AH1-698 GEN2
Adder
5.915
972227AH1-698 GEN1
Adder
4.165
274800UNIV PARK;3U
Adder
9.308
274801UNIV PARK;4U
Adder
9.308
274687WILL CNTY;4U
Adder
44.271
274687WILL CNTY;4U
Adder
44.271
274675JOLIET 29;7U
Adder
48.542
274675JOLIET 29;7U
Adder
46.808
274728ELWOOD EC;5P
Adder
25.932
274731ELWOOD EC;2P
Adder
25.931
274733ELWOOD EC;3P
Adder
25.931
274735ELWOOD EC;4P
Adder
25.931
276893AG1-478 C
Solar/Wind Harmer
0.867
970833AG2-524 GEN
Solar/Wind Harmer
13.751
970833AG2-524 GEN
Solar/Wind Harmer
6.396
274744AC1-111 GEN8
Adder
8.739
274746AC1-111 G10
Adder
8.739
971549AH1-272 GEN
Solar/Wind Harmer
28.236
958711AF2-162 GEN
Solar/Wind Harmer
1.543
270142AC1-141 CT1_
50/50
4.103
24642205MAYFLWER
50/50
0.062
944961AF1-161 GEN
50/50
4.866
962601AG1-109 GEN
50/50
4.866
971347AH1-153 GEN
Solar/Wind Harmer
9.045
270043AE2-236 GEN
Solar/Wind Harmer
9.926
247643Z2-116 C
Solar/Wind Harmer
0.119
944531AF1-118 GEN
Solar/Wind Harmer
59.639
270505AE1-170 C O1
Solar/Wind Harmer
25.381
24441505OLIV SLR
Solar/Wind Harmer
0.226
945111AF1-176 GEN
Solar/Wind Harmer
9.517
270063AE2-323 C
Solar/Wind Harmer
3.694
274772LINCOLN ;3U
Adder
10.256
274724RIVER EC ;11
Adder
28.691
972231SS25-0005
Solar/Wind Harmer
15.332
972181SS23-001
Solar/Wind Harmer
9.583
274752CRETE EC ;2U
Adder
7.897
274753CRETE EC ;3U
Adder
7.897
276164X3-005 C
Solar/Wind Harmer
1.134
274814UNIV PK N;0U
Adder
8.117
274807UNIV PK N;3U
Adder
8.1
274811UNIV PK N;7U
Adder
8.047
970707AG2-453 GEN
Solar/Wind Harmer
44.915
965021AG1-366 GEN
Solar/Wind Harmer
3.724
274803UNIV PARK;6U
Adder
9.32
274826FISK ;BP
Adder
17.501
274887GEN-1.85
Solar/Wind Harmer
8.512
276772AC2-154 GEN
Solar/Wind Harmer
4.459
276843GEN-1.7
Solar/Wind Harmer
0.916
276806AD2-047 C O1
Solar/Wind Harmer
17.091
972259AH1-714 GEN
Adder
30.481
972038AH1-567 GEN2
Adder
0.583
939351AE1-166 GEN
Solar/Wind Harmer
9.436
274676JOLIET 29;8U
Adder
46.808
274729ELWOOD EC;1P
Adder
25.931
274730ELWOOD EC;6P
Adder
25.932
274734ELWOOD EC;8P
Adder
25.932
274736ELWOOD EC;9P
Adder
25.932
943121AE2-341 GEN
Solar/Wind Harmer
23.498
943591AF1-030 GEN
Solar/Wind Harmer
15.666
274862TOP CROP ;2U
Solar/Wind Harmer
7.796
274682WAUKEGAN ;7U
Adder
27.68
276868AE1-113 GEN
Solar/Wind Harmer
15.302
274879MINONK ;1U
Solar/Wind Harmer
10.201
970073AG2-061 GEN
Solar/Wind Harmer
3.537
971411AH1-196 GEN
Solar/Wind Harmer
22.579
971675AH1-338 GEN
Solar/Wind Harmer
27.091
276861AD2-134 GEN
Solar/Wind Harmer
2.686
276863AD2-134 GEN
Solar/Wind Harmer
2.686
274863CRW1-WTG
Solar/Wind Harmer
8.359
274864CRW2-WTG
Solar/Wind Harmer
8.359
971171AH1-044 GEN
Solar/Wind Harmer
29.877
276889AE2-281 GEN
Solar/Wind Harmer
2.861
274823ROCKFORD ;21
Adder
28.993
274856ECOGROVE ;U1
Solar/Wind Harmer
4.976
276611AD2-172 GEN
Solar/Wind Harmer
3.774
276612AE2-035 GEN
Solar/Wind Harmer
3.774
926823AC1-168 GEN
Solar/Wind Harmer
6.322
970169AG2-114 GEN
Solar/Wind Harmer
14.684
971681AH1-341 GEN
Solar/Wind Harmer
21.982
972267AH1-718 GEN
Adder
6.003
276799AD1-013 GEN
Solar/Wind Harmer
3.327
946671AF1-331 GEN
Solar/Wind Harmer
0.63
274855GSG-6 ;RU
Solar/Wind Harmer
5.555
274850MENDOTA H;RU
Solar/Wind Harmer
3.862
276602WESTBROOK C
Solar/Wind Harmer
3.198
959091AF2-200 GEN
Solar/Wind Harmer
29.877
970571AG2-364 GEN
Solar/Wind Harmer
29.423
274857EASY ROAD;U1
Solar/Wind Harmer
6.987
274760LEE CO EC;1U
Adder
13.568
274767LEE CO EC;8U
Adder
13.409
276603SUBLETTE C
Solar/Wind Harmer
1.527
964401AG1-302 GEN
Solar/Wind Harmer
13.125
24728505AND G1
Adder
3.588
270102X2-052 ST
50/50
2.731
270100X2-052 CT1
50/50
2.523
270101X2-052 CT2
50/50
2.523
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.819
24729405KEY G3
50/50
0.623
24729305KEY G2
50/50
0.612
24729205KEY G1
50/50
0.609
970349AG2-230 GEN
Solar/Wind Harmer
27.136
965681AG1-436 GEN
Solar/Wind Harmer
21.178
965791AG1-447 GEN
Solar/Wind Harmer
10.836
961051AF2-396 GEN
Solar/Wind Harmer
26.623
961051AF2-396 GEN
Solar/Wind Harmer
12.383
274770LINCOLN ;1U
Adder
10.256
274771LINCOLN ;2U
Adder
10.256
274805UNIV PK N;1U
Adder
8.064
274808UNIV PK N;4U
Adder
8.012
274888KELLY CRK;1U
Solar/Wind Harmer
9.428
276776AD2-060 GEN
Solar/Wind Harmer
0.669
958011AF2-095 GEN
Solar/Wind Harmer
23.007
970941AG2-585 GEN
Solar/Wind Harmer
8.787
276897AD1-100 C
Solar/Wind Harmer
73.913
274674JOLIET 9 ;6U
Adder
24.31
276893AG1-478 C
Solar/Wind Harmer
0.691
274695ROCKY RD ;2P
Adder
17.178
274693ROCKY RD ;1P
Adder
17.009
274697ROCKY RD ;3P
Adder
4.667
274696ROCKY RD ;4P
Adder
17.583
958481AF2-142 GEN
Solar/Wind Harmer
23.134
274683WAUKEGAN ;8U
Adder
32.408
274683WAUKEGAN ;8U
Adder
27.318
962691AG1-118 GEN
Solar/Wind Harmer
45.905
960751AF2-366 GEN
Solar/Wind Harmer
4.378
944541AF1-119 GEN
Solar/Wind Harmer
6.387
960971AF2-388 GEN
Solar/Wind Harmer
16.674
958491AF2-143 GEN
Solar/Wind Harmer
22.814
276901AD2-066 C O1
Solar/Wind Harmer
5.321
270535AF1-215 GEN1
Solar/Wind Harmer
6.796
270536AF1-215 GEN2
Solar/Wind Harmer
6.796
971341AH1-150 GEN
Solar/Wind Harmer
29.877
971343AH1-151 GEN
Solar/Wind Harmer
29.877
276872AE1-163_GEN1
Solar/Wind Harmer
10.015
276876AE1-163_GEN2
Solar/Wind Harmer
10.015
972235AH1-702 GEN1
Adder
3.74
972236AH1-702 GEN2
Adder
3.253
938861AE1-114 GEN
Solar/Wind Harmer
12.009
274764LEE CO EC;5U
Adder
13.6
274765LEE CO EC;6U
Adder
13.6
274762LEE CO EC;3U
Adder
13.568
274763LEE CO EC;4U
Adder
13.441
247621Y3-024
Adder
0.264
270349AD2-093_GEN
Solar/Wind Helper
1.336
270471AD2-092_GEN
Solar/Wind Helper
1.336
276158O29GEN2
Solar/Wind Harmer
0.363
276157O29GEN1
Solar/Wind Harmer
0.276
24344105CKG2
50/50
14.17
270143AC1-141 CT2_
50/50
4.103
24639705ELKHART HY
50/50
0.275
970521AG2-332 GEN
50/50
19.534
24307105BERRINSP G
50/50
0.036
270216AD2-079_GEN
Solar/Wind Harmer
1.031
957891AF2-083 GEN
Solar/Wind Harmer
25.331
945111AF1-176 GEN
Solar/Wind Harmer
30.029
270449AD2-020 GEN
Solar/Wind Harmer
4.69
943021AE2-325 GEN
Solar/Wind Harmer
6.096
972207SS24-0001
Solar/Wind Harmer
36.463
274773LINCOLN ;4U
Adder
10.256
274774LINCOLN ;5U
Adder
10.256
24441205WTRV SLR C
Solar/Wind Harmer
0.221
274723RIVER EC ;12
Adder
29.023
274751CRETE EC ;1U
Adder
7.897
274754CRETE EC ;4U
Adder
7.897
274812UNIV PK N;8U
Adder
8.047
965011AG1-365 GEN
Solar/Wind Harmer
16.013
274802UNIV PARK;5U
Adder
9.32
941551AE2-152 GEN
Solar/Wind Harmer
7.216
274676JOLIET 29;8U
Adder
48.541
274674JOLIET 9 ;6U
Adder
24.31
274732ELWOOD EC;7P
Adder
25.932
274871GR RIDGE ;2U
Solar/Wind Harmer
12.105
274847GR RIDGE ;BU
Solar/Wind Harmer
7.959
274745AC1-111 GEN9
Adder
8.739
970373AG2-245 GEN
Solar/Wind Harmer
32.504
276694AA1-018 GEN2
Solar/Wind Harmer
9.731
276691AA1-018 GEN1
Solar/Wind Harmer
1.163
274861TOP CROP ;1U
Solar/Wind Harmer
9.337
274682WAUKEGAN ;7U
Adder
27.68
274828WAUKEGAN ;BP
Adder
16.987
962781AG1-127 GEN
Solar/Wind Harmer
14.51
965651AG1-433 GEN
Solar/Wind Harmer
8.337
939401AE1-172 GEN
Solar/Wind Harmer
21.253
274872LEEDK;1U
Solar/Wind Harmer
12.493
276805AD2-038 GEN
Solar/Wind Harmer
7.799
276882AE2-255 GEN
Solar/Wind Harmer
5.101
971997AH1-543 GEN
Solar/Wind Harmer
23.764
270055AF2-134 C O1
Solar/Wind Harmer
4.53
957471AF2-041 GEN
Solar/Wind Harmer
44.816
959081AF2-199 GEN
Solar/Wind Harmer
14.939
971067AG2-660 GEN
Solar/Wind Harmer
3.474
274822ROCKFORD ;11
Adder
29.205
958861AF2-177 GEN
Solar/Wind Harmer
16.204
970819AG2-516 GEN
Solar/Wind Harmer
17.74
970569AG2-363 GEN
Solar/Wind Harmer
44.135
274858EASY ROAD;U2
Solar/Wind Harmer
6.987
274761LEE CO EC;2U
Adder
13.568
274766LEE CO EC;7U
Adder
13.409
958381AF2-132 GEN
Solar/Wind Harmer
13.125
964861AG1-349 GEN
Solar/Wind Harmer
11.331
971917AH1-482 GEN
Solar/Wind Harmer
13.073
970091AG2-072 GEN
Adder
79.856
24728605AND G2
Adder
3.588
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.48
NYPJM->LTFIMP_NY
CLTF
2.521
LGEELTFEXP_LGEE->PJM
CLTF
2.734
WECLTFEXP_WEC->PJM
CLTF
5.656
CBM West 1LTFEXP_CBM-W1->PJM
CBM
172.315
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.846
CBM West 2LTFEXP_CBM-W2->PJM
CBM
93.961
MECLTFEXP_MEC->PJM
CLTF
20.244
SIGELTFEXP_SIGE->PJM
CLTF
0.357
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.033
AG2-052LTFEXP_AG2-052->PJM
LTF
0.348
AH1-155LTFEXP_AH1-155->PJM
LTF
0.523
LAGNLTFEXP_LAGN->PJM
CLTF
10.079
TVALTFEXP_TVA->PJM
CLTF
3.622

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#2979_05DUMONT 765_B2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2979_05DUMONT 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.85 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4756.98
MW Contribution:
23.86
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.628
24642205MAYFLWER
50/50
0.07
944961AF1-161 GEN
50/50
5.457
962601AG1-109 GEN
50/50
5.457
274772LINCOLN ;3U
50/50
12.299
971347AH1-153 GEN
Solar/Wind Harmer
10.453
270505AE1-170 C O1
Solar/Wind Harmer
28.486
247643Z2-116 C
Solar/Wind Harmer
0.132
24441505OLIV SLR
Solar/Wind Harmer
0.251
945111AF1-176 GEN
Solar/Wind Harmer
10.605
270043AE2-236 GEN
Solar/Wind Harmer
10.177
270063AE2-323 C
Solar/Wind Harmer
3.996
274724RIVER EC ;11
Adder
31.767
970707AG2-453 GEN
Solar/Wind Harmer
50.114
276164X3-005 C
Solar/Wind Harmer
1.256
972231SS25-0005
Solar/Wind Harmer
16.875
972181SS23-001
Solar/Wind Harmer
10.547
274752CRETE EC ;2U
Adder
8.691
274753CRETE EC ;3U
Adder
8.691
972259AH1-714 GEN
Adder
33.857
274814UNIV PK N;0U
Adder
8.953
274807UNIV PK N;3U
Adder
8.934
274811UNIV PK N;7U
Adder
8.876
274826FISK ;BP
Adder
19.361
274887GEN-1.85
Solar/Wind Harmer
9.417
276772AC2-154 GEN
Solar/Wind Harmer
4.933
276843GEN-1.7
Solar/Wind Harmer
1.013
276806AD2-047 C O1
Solar/Wind Harmer
18.909
274803UNIV PARK;6U
Adder
10.298
972038AH1-567 GEN2
Adder
0.644
939351AE1-166 GEN
Solar/Wind Harmer
10.439
274676JOLIET 29;8U
Adder
51.744
274729ELWOOD EC;1P
Adder
28.61
274730ELWOOD EC;6P
Adder
28.611
274734ELWOOD EC;8P
Adder
28.611
274736ELWOOD EC;9P
Adder
28.611
943121AE2-341 GEN
Solar/Wind Harmer
26.017
943591AF1-030 GEN
Solar/Wind Harmer
17.345
944531AF1-118 GEN
Solar/Wind Harmer
60.194
274682WAUKEGAN ;7U
Adder
30.457
274862TOP CROP ;2U
Solar/Wind Harmer
8.526
965021AG1-366 GEN
Solar/Wind Harmer
3.852
276799AD1-013 GEN
Solar/Wind Harmer
3.64
946671AF1-331 GEN
Solar/Wind Harmer
0.69
274855GSG-6 ;RU
Solar/Wind Harmer
6.077
270102X2-052 ST
50/50
3.04
270100X2-052 CT1
50/50
2.808
270101X2-052 CT2
50/50
2.808
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
12.299
274771LINCOLN ;2U
50/50
12.299
247620Y3-023
50/50
0.894
970349AG2-230 GEN
Solar/Wind Harmer
31.359
965681AG1-436 GEN
Solar/Wind Harmer
23.471
965791AG1-447 GEN
Solar/Wind Harmer
12.008
961051AF2-396 GEN
Solar/Wind Harmer
29.784
24344005CKG1
50/50
12.668
270144AC1-141 ST1_
50/50
4.102
24641605TWIN BRNCH
50/50
0.033
274775LINCOLN ;6U
50/50
12.299
274776LINCOLN ;7U
50/50
12.299
274777LINCOLN ;8U
50/50
12.299
24653605MOTTVILLE
50/50
0.007
971771AH1-392 GEN
Solar/Wind Harmer
17.135
270526AF1-158 GEN
Solar/Wind Harmer
8.541
960681AF2-359 GEN
Solar/Wind Harmer
7.094
944161AF1-084 GEN
Solar/Wind Harmer
4.127
274827FISK ;RP
Adder
13.721
972228AH1-698 GEN2
Adder
6.549
972227AH1-698 GEN1
Adder
4.611
960591AF2-350 GEN
Solar/Wind Harmer
17.675
972037AH1-567 GEN1
Adder
0.323
274800UNIV PARK;3U
Adder
10.294
274801UNIV PARK;4U
Adder
10.294
274687WILL CNTY;4U
Adder
48.934
274687WILL CNTY;4U
Adder
48.934
274675JOLIET 29;7U
Adder
53.662
274675JOLIET 29;7U
Adder
51.745
274728ELWOOD EC;5P
Adder
28.611
274731ELWOOD EC;2P
Adder
28.61
274733ELWOOD EC;3P
Adder
28.61
274735ELWOOD EC;4P
Adder
28.61
970833AG2-524 GEN
Solar/Wind Harmer
15.187
961051AF2-396 GEN
Solar/Wind Harmer
13.853
274805UNIV PK N;1U
Adder
8.895
274808UNIV PK N;4U
Adder
8.837
274888KELLY CRK;1U
Solar/Wind Harmer
10.43
276776AD2-060 GEN
Solar/Wind Harmer
0.74
958011AF2-095 GEN
Solar/Wind Harmer
25.453
970941AG2-585 GEN
Solar/Wind Harmer
9.721
276897AD1-100 C
Solar/Wind Harmer
81.771
274674JOLIET 9 ;6U
Adder
26.849
276893AG1-478 C
Solar/Wind Harmer
0.762
274695ROCKY RD ;2P
Adder
18.919
274693ROCKY RD ;1P
Adder
18.733
274697ROCKY RD ;3P
Adder
5.139
274696ROCKY RD ;4P
Adder
19.364
274683WAUKEGAN ;8U
Adder
35.646
274683WAUKEGAN ;8U
Adder
30.048
958481AF2-142 GEN
Solar/Wind Harmer
25.309
962691AG1-118 GEN
Solar/Wind Harmer
50.464
960751AF2-366 GEN
Solar/Wind Harmer
4.809
958491AF2-143 GEN
Solar/Wind Harmer
24.84
276901AD2-066 C O1
Solar/Wind Harmer
5.786
971341AH1-150 GEN
Solar/Wind Harmer
32.614
971343AH1-151 GEN
Solar/Wind Harmer
32.614
972235AH1-702 GEN1
Adder
4.077
972236AH1-702 GEN2
Adder
3.545
276872AE1-163_GEN1
Solar/Wind Harmer
10.83
276876AE1-163_GEN2
Solar/Wind Harmer
10.83
938861AE1-114 GEN
Solar/Wind Harmer
13.035
274764LEE CO EC;5U
Adder
14.746
274765LEE CO EC;6U
Adder
14.746
274762LEE CO EC;3U
Adder
14.712
274763LEE CO EC;4U
Adder
14.573
276158O29GEN2
Solar/Wind Harmer
7.743
276157O29GEN1
Solar/Wind Harmer
5.887
276645AC1-214 GEN1
Solar/Wind Harmer
2.044
944541AF1-119 GEN
Solar/Wind Harmer
6.319
960971AF2-388 GEN
Solar/Wind Harmer
16.496
247621Y3-024
Adder
0.245
270349AD2-093_GEN
Solar/Wind Helper
1.46
24344105CKG2
50/50
17.101
270143AC1-141 CT2_
50/50
4.628
274773LINCOLN ;4U
50/50
12.299
274774LINCOLN ;5U
50/50
12.299
24307105BERRINSP G
50/50
0.04
24639705ELKHART HY
50/50
0.302
247604X1-042
50/50
0.044
970521AG2-332 GEN
50/50
21.337
270216AD2-079_GEN
Solar/Wind Harmer
1.143
957891AF2-083 GEN
Solar/Wind Harmer
28.345
270449AD2-020 GEN
Solar/Wind Harmer
5.259
943021AE2-325 GEN
Solar/Wind Harmer
6.836
945111AF1-176 GEN
Solar/Wind Harmer
33.461
972207SS24-0001
Solar/Wind Harmer
41.211
24441205WTRV SLR C
Solar/Wind Harmer
0.249
274723RIVER EC ;12
Adder
32.119
274751CRETE EC ;1U
Adder
8.691
274754CRETE EC ;4U
Adder
8.691
274812UNIV PK N;8U
Adder
8.876
274802UNIV PARK;5U
Adder
10.298
941551AE2-152 GEN
Solar/Wind Harmer
7.984
274676JOLIET 29;8U
Adder
53.66
274674JOLIET 9 ;6U
Adder
26.849
274732ELWOOD EC;7P
Adder
28.611
274871GR RIDGE ;2U
Solar/Wind Harmer
13.369
274847GR RIDGE ;BU
Solar/Wind Harmer
8.79
274745AC1-111 GEN9
Adder
9.659
274682WAUKEGAN ;7U
Adder
30.457
274828WAUKEGAN ;BP
Adder
18.685
276694AA1-018 GEN2
Solar/Wind Harmer
10.646
276691AA1-018 GEN1
Solar/Wind Harmer
1.273
274861TOP CROP ;1U
Solar/Wind Harmer
10.212
962781AG1-127 GEN
Solar/Wind Harmer
15.939
274872LEEDK;1U
Solar/Wind Harmer
13.713
965011AG1-365 GEN
Solar/Wind Harmer
16.564
276805AD2-038 GEN
Solar/Wind Harmer
8.492
939401AE1-172 GEN
Solar/Wind Harmer
23.028
276882AE2-255 GEN
Solar/Wind Harmer
5.548
971997AH1-543 GEN
Solar/Wind Harmer
25.828
957471AF2-041 GEN
Solar/Wind Harmer
48.921
959081AF2-199 GEN
Solar/Wind Harmer
16.307
971067AG2-660 GEN
Solar/Wind Harmer
3.792
274822ROCKFORD ;11
Adder
31.861
970819AG2-516 GEN
Solar/Wind Harmer
19.318
970569AG2-363 GEN
Solar/Wind Harmer
47.488
274858EASY ROAD;U2
Solar/Wind Harmer
7.576
274761LEE CO EC;2U
Adder
14.712
274766LEE CO EC;7U
Adder
14.538
276708O09 GEN2
Solar/Wind Harmer
5.528
970373AG2-245 GEN
Solar/Wind Harmer
32.096
276646AC1-214 GEN2
Solar/Wind Harmer
2.044
965651AG1-433 GEN
Solar/Wind Harmer
8.248
274848CAMPGROVE;RU
Solar/Wind Harmer
9.713
270471AD2-092_GEN
Solar/Wind Helper
1.46
970833AG2-524 GEN
Solar/Wind Harmer
7.064
276893AG1-478 C
Solar/Wind Harmer
0.956
274744AC1-111 GEN8
Adder
9.659
274746AC1-111 G10
Adder
9.659
970031AG2-029 GEN
Solar/Wind Harmer
42.986
971549AH1-272 GEN
Solar/Wind Harmer
31.699
24729505KEY G4
Adder
10.795
959331AF2-224 GEN
Solar/Wind Harmer
16.564
970073AG2-061 GEN
Solar/Wind Harmer
3.851
971411AH1-196 GEN
Solar/Wind Harmer
24.707
971675AH1-338 GEN
Solar/Wind Harmer
29.639
276861AD2-134 GEN
Solar/Wind Harmer
2.938
276863AD2-134 GEN
Solar/Wind Harmer
2.938
971171AH1-044 GEN
Solar/Wind Harmer
32.614
274823ROCKFORD ;21
Adder
31.63
276889AE2-281 GEN
Solar/Wind Harmer
3.094
274863CRW1-WTG
Solar/Wind Harmer
8.971
274864CRW2-WTG
Solar/Wind Harmer
8.971
274856ECOGROVE ;U1
Solar/Wind Harmer
5.414
276611AD2-172 GEN
Solar/Wind Harmer
4.107
276612AE2-035 GEN
Solar/Wind Harmer
4.107
971681AH1-341 GEN
Solar/Wind Harmer
23.859
926823AC1-168 GEN
Solar/Wind Harmer
6.797
270071AF1-092 GEN
Solar/Wind Harmer
23.687
970169AG2-114 GEN
Solar/Wind Harmer
15.602
972267AH1-718 GEN
Adder
6.485
276741O09 GEN1
Solar/Wind Harmer
5.528
274877BISHOP HL;1U
Solar/Wind Harmer
5.114
958711AF2-162 GEN
Solar/Wind Harmer
1.527
946321AF1-296 GEN
Solar/Wind Harmer
15.545
274850MENDOTA H;RU
Solar/Wind Harmer
4.225
276602WESTBROOK C
Solar/Wind Harmer
3.498
276868AE1-113 GEN
Solar/Wind Harmer
16.642
274879MINONK ;1U
Solar/Wind Harmer
11.095
959091AF2-200 GEN
Solar/Wind Harmer
32.614
970571AG2-364 GEN
Solar/Wind Harmer
31.659
274857EASY ROAD;U1
Solar/Wind Harmer
7.576
274760LEE CO EC;1U
Adder
14.712
274767LEE CO EC;8U
Adder
14.538
276603SUBLETTE C
Solar/Wind Harmer
1.654
274851PROVIDENC;RU
Solar/Wind Harmer
4.346
274849CRESCENT ;1U
Solar/Wind Harmer
2.821
276782AC1-033 GEN
Solar/Wind Harmer
6.044
274878BISHOP HL;2U
Solar/Wind Harmer
5.114
965931AG1-462 GEN
Solar/Wind Harmer
9.79
971087AG2-675 GEN
Solar/Wind Harmer
1.429
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.54
NYPJM->LTFIMP_NY
CLTF
2.551
LGEELTFEXP_LGEE->PJM
CLTF
1.869
WECLTFEXP_WEC->PJM
CLTF
6.165
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.118
CBM West 1LTFEXP_CBM-W1->PJM
CBM
184.697
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.536
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.09
MECLTFEXP_MEC->PJM
CLTF
20.956
SIGELTFEXP_SIGE->PJM
CLTF
0.265
AG2-052LTFEXP_AG2-052->PJM
LTF
0.357
AH1-155LTFEXP_AH1-155->PJM
LTF
0.535
LAGNLTFEXP_LAGN->PJM
CLTF
9.08
TVALTFEXP_TVA->PJM
CLTF
3.004

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#TEDDY MARY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#TEDDY MARY_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.67 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4583.78
MW Contribution:
21.73
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.706
270100X2-052 CT1
50/50
2.499
270101X2-052 CT2
50/50
2.499
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.805
274770LINCOLN ;1U
50/50
10.763
274771LINCOLN ;2U
50/50
10.763
970349AG2-230 GEN
Solar/Wind Harmer
26.84
965681AG1-436 GEN
Solar/Wind Harmer
20.979
965791AG1-447 GEN
Solar/Wind Harmer
10.734
961051AF2-396 GEN
Solar/Wind Harmer
26.235
961051AF2-396 GEN
Solar/Wind Harmer
12.202
274805UNIV PK N;1U
Adder
7.977
274808UNIV PK N;4U
Adder
7.925
274888KELLY CRK;1U
Solar/Wind Harmer
9.321
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
22.746
970941AG2-585 GEN
Solar/Wind Harmer
8.688
276897AD1-100 C
Solar/Wind Harmer
73.044
274674JOLIET 9 ;6U
Adder
24.034
276893AG1-478 C
Solar/Wind Harmer
0.683
274695ROCKY RD ;2P
Adder
16.985
274693ROCKY RD ;1P
Adder
16.818
274697ROCKY RD ;3P
Adder
4.614
274696ROCKY RD ;4P
Adder
17.386
958481AF2-142 GEN
Solar/Wind Harmer
22.862
274683WAUKEGAN ;8U
Adder
32.045
274683WAUKEGAN ;8U
Adder
27.013
962691AG1-118 GEN
Solar/Wind Harmer
45.388
944541AF1-119 GEN
Solar/Wind Harmer
6.322
960971AF2-388 GEN
Solar/Wind Harmer
16.503
960751AF2-366 GEN
Solar/Wind Harmer
4.328
958491AF2-143 GEN
Solar/Wind Harmer
22.54
270535AF1-215 GEN1
Solar/Wind Harmer
6.807
270536AF1-215 GEN2
Solar/Wind Harmer
6.807
276901AD2-066 C O1
Solar/Wind Harmer
5.256
971341AH1-150 GEN
Solar/Wind Harmer
29.539
971343AH1-151 GEN
Solar/Wind Harmer
29.539
276872AE1-163_GEN1
Solar/Wind Harmer
9.891
276876AE1-163_GEN2
Solar/Wind Harmer
9.891
972235AH1-702 GEN1
Adder
3.698
972236AH1-702 GEN2
Adder
3.216
938861AE1-114 GEN
Solar/Wind Harmer
11.872
274764LEE CO EC;5U
Adder
13.446
274765LEE CO EC;6U
Adder
13.446
274762LEE CO EC;3U
Adder
13.415
274763LEE CO EC;4U
Adder
13.288
247621Y3-024
Adder
0.267
270349AD2-093_GEN
Solar/Wind Helper
1.727
270471AD2-092_GEN
Solar/Wind Helper
1.727
270142AC1-141 CT1_
50/50
4.046
24642205MAYFLWER
50/50
0.061
944961AF1-161 GEN
50/50
4.795
962601AG1-109 GEN
50/50
4.795
274772LINCOLN ;3U
50/50
10.763
971347AH1-153 GEN
Solar/Wind Harmer
8.947
270043AE2-236 GEN
Solar/Wind Harmer
9.698
247643Z2-116 C
Solar/Wind Harmer
0.117
944531AF1-118 GEN
Solar/Wind Harmer
58.604
24441505OLIV SLR
Solar/Wind Harmer
0.224
270505AE1-170 C O1
Solar/Wind Harmer
25.022
945111AF1-176 GEN
Solar/Wind Harmer
9.378
270063AE2-323 C
Solar/Wind Harmer
3.618
274724RIVER EC ;11
Adder
28.38
972231SS25-0005
Solar/Wind Harmer
15.171
972181SS23-001
Solar/Wind Harmer
9.482
274752CRETE EC ;2U
Adder
7.813
274753CRETE EC ;3U
Adder
7.813
276164X3-005 C
Solar/Wind Harmer
1.121
274814UNIV PK N;0U
Adder
8.029
274807UNIV PK N;3U
Adder
8.012
274811UNIV PK N;7U
Adder
7.96
970707AG2-453 GEN
Solar/Wind Harmer
44.413
274826FISK ;BP
Adder
17.307
274803UNIV PARK;6U
Adder
9.216
274887GEN-1.85
Solar/Wind Harmer
8.416
276772AC2-154 GEN
Solar/Wind Harmer
4.408
276843GEN-1.7
Solar/Wind Harmer
0.906
276806AD2-047 C O1
Solar/Wind Harmer
16.898
972259AH1-714 GEN
Adder
30.137
972038AH1-567 GEN2
Adder
0.576
939351AE1-166 GEN
Solar/Wind Harmer
9.325
274676JOLIET 29;8U
Adder
46.282
274729ELWOOD EC;1P
Adder
25.635
274730ELWOOD EC;6P
Adder
25.635
274734ELWOOD EC;8P
Adder
25.635
274736ELWOOD EC;9P
Adder
25.635
943121AE2-341 GEN
Solar/Wind Harmer
23.235
943591AF1-030 GEN
Solar/Wind Harmer
15.49
965021AG1-366 GEN
Solar/Wind Harmer
3.589
274862TOP CROP ;2U
Solar/Wind Harmer
7.704
274682WAUKEGAN ;7U
Adder
27.371
276868AE1-113 GEN
Solar/Wind Harmer
15.116
274879MINONK ;1U
Solar/Wind Harmer
10.078
276799AD1-013 GEN
Solar/Wind Harmer
3.289
946671AF1-331 GEN
Solar/Wind Harmer
0.623
274855GSG-6 ;RU
Solar/Wind Harmer
5.492
274850MENDOTA H;RU
Solar/Wind Harmer
3.818
276602WESTBROOK C
Solar/Wind Harmer
3.162
959091AF2-200 GEN
Solar/Wind Harmer
29.539
964401AG1-302 GEN
Solar/Wind Harmer
13.188
970571AG2-364 GEN
Solar/Wind Harmer
29.049
274857EASY ROAD;U1
Solar/Wind Harmer
6.908
274760LEE CO EC;1U
Adder
13.415
274767LEE CO EC;8U
Adder
13.257
276603SUBLETTE C
Solar/Wind Harmer
1.51
24728505AND G1
Adder
3.684
270284AF1-227 GEN1
Solar/Wind Helper
2.091
270287AF1-227 GEN3
Solar/Wind Helper
0.767
24344105CKG2
50/50
14.029
270143AC1-141 CT2_
50/50
4.046
24639705ELKHART HY
50/50
0.271
970521AG2-332 GEN
50/50
19.228
274773LINCOLN ;4U
50/50
10.763
274774LINCOLN ;5U
50/50
10.763
24307105BERRINSP G
50/50
0.035
270216AD2-079_GEN
Solar/Wind Harmer
1.016
957891AF2-083 GEN
Solar/Wind Harmer
24.972
945111AF1-176 GEN
Solar/Wind Harmer
29.59
270449AD2-020 GEN
Solar/Wind Harmer
4.622
943021AE2-325 GEN
Solar/Wind Harmer
6.007
972207SS24-0001
Solar/Wind Harmer
36.063
24441205WTRV SLR C
Solar/Wind Harmer
0.218
274723RIVER EC ;12
Adder
28.708
274751CRETE EC ;1U
Adder
7.813
274754CRETE EC ;4U
Adder
7.813
274812UNIV PK N;8U
Adder
7.96
274802UNIV PARK;5U
Adder
9.216
941551AE2-152 GEN
Solar/Wind Harmer
7.132
274676JOLIET 29;8U
Adder
47.996
274674JOLIET 9 ;6U
Adder
24.034
274732ELWOOD EC;7P
Adder
25.635
274871GR RIDGE ;2U
Solar/Wind Harmer
11.964
274847GR RIDGE ;BU
Solar/Wind Harmer
7.867
274745AC1-111 GEN9
Adder
8.641
970373AG2-245 GEN
Solar/Wind Harmer
32.464
965011AG1-365 GEN
Solar/Wind Harmer
15.433
276694AA1-018 GEN2
Solar/Wind Harmer
9.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.149
274861TOP CROP ;1U
Solar/Wind Harmer
9.227
274682WAUKEGAN ;7U
Adder
27.371
274828WAUKEGAN ;BP
Adder
16.798
965651AG1-433 GEN
Solar/Wind Harmer
8.251
962781AG1-127 GEN
Solar/Wind Harmer
14.347
274872LEEDK;1U
Solar/Wind Harmer
12.352
939401AE1-172 GEN
Solar/Wind Harmer
20.968
276805AD2-038 GEN
Solar/Wind Harmer
7.705
270055AF2-134 C O1
Solar/Wind Harmer
4.538
276882AE2-255 GEN
Solar/Wind Harmer
5.039
971997AH1-543 GEN
Solar/Wind Harmer
23.469
957471AF2-041 GEN
Solar/Wind Harmer
44.308
959081AF2-199 GEN
Solar/Wind Harmer
14.769
971067AG2-660 GEN
Solar/Wind Harmer
3.435
274822ROCKFORD ;11
Adder
28.877
958861AF2-177 GEN
Solar/Wind Harmer
16.07
970819AG2-516 GEN
Solar/Wind Harmer
17.541
958381AF2-132 GEN
Solar/Wind Harmer
13.188
970569AG2-363 GEN
Solar/Wind Harmer
43.574
964861AG1-349 GEN
Solar/Wind Harmer
11.39
971917AH1-482 GEN
Solar/Wind Harmer
13.141
274858EASY ROAD;U2
Solar/Wind Harmer
6.908
274761LEE CO EC;2U
Adder
13.415
274766LEE CO EC;7U
Adder
13.257
24728605AND G2
Adder
3.684
270286AF1-227 GEN2
Solar/Wind Helper
0.767
24344005CKG1
50/50
10.917
270144AC1-141 ST1_
50/50
3.585
24641605TWIN BRNCH
50/50
0.029
24653605MOTTVILLE
50/50
0.006
274775LINCOLN ;6U
50/50
10.763
274776LINCOLN ;7U
50/50
10.763
274777LINCOLN ;8U
50/50
10.763
971771AH1-392 GEN
Solar/Wind Harmer
15.164
960681AF2-359 GEN
Solar/Wind Harmer
6.341
270071AF1-092 GEN
Solar/Wind Harmer
25.17
270526AF1-158 GEN
Solar/Wind Harmer
7.595
944161AF1-084 GEN
Solar/Wind Harmer
3.623
24729505KEY G4
Adder
10.579
970031AG2-029 GEN
Solar/Wind Harmer
40.589
274827FISK ;RP
Adder
12.265
972037AH1-567 GEN1
Adder
0.289
960591AF2-350 GEN
Solar/Wind Harmer
15.796
274800UNIV PARK;3U
Adder
9.204
274801UNIV PARK;4U
Adder
9.204
972228AH1-698 GEN2
Adder
5.848
972227AH1-698 GEN1
Adder
4.117
274687WILL CNTY;4U
Adder
43.775
274687WILL CNTY;4U
Adder
43.775
274675JOLIET 29;7U
Adder
47.997
274675JOLIET 29;7U
Adder
46.283
274728ELWOOD EC;5P
Adder
25.635
274731ELWOOD EC;2P
Adder
25.635
274733ELWOOD EC;3P
Adder
25.635
274735ELWOOD EC;4P
Adder
25.635
276893AG1-478 C
Solar/Wind Harmer
0.857
970833AG2-524 GEN
Solar/Wind Harmer
13.592
970833AG2-524 GEN
Solar/Wind Harmer
6.322
274744AC1-111 GEN8
Adder
8.641
274746AC1-111 G10
Adder
8.641
959331AF2-224 GEN
Solar/Wind Harmer
15.433
958711AF2-162 GEN
Solar/Wind Harmer
1.527
970073AG2-061 GEN
Solar/Wind Harmer
3.495
971549AH1-272 GEN
Solar/Wind Harmer
27.69
971411AH1-196 GEN
Solar/Wind Harmer
22.326
971675AH1-338 GEN
Solar/Wind Harmer
26.785
276861AD2-134 GEN
Solar/Wind Harmer
2.656
276863AD2-134 GEN
Solar/Wind Harmer
2.656
971171AH1-044 GEN
Solar/Wind Harmer
29.539
274863CRW1-WTG
Solar/Wind Harmer
8.241
274864CRW2-WTG
Solar/Wind Harmer
8.241
276889AE2-281 GEN
Solar/Wind Harmer
2.826
274823ROCKFORD ;21
Adder
28.668
274856ECOGROVE ;U1
Solar/Wind Harmer
4.92
276611AD2-172 GEN
Solar/Wind Harmer
3.732
276612AE2-035 GEN
Solar/Wind Harmer
3.732
926823AC1-168 GEN
Solar/Wind Harmer
6.24
971681AH1-341 GEN
Solar/Wind Harmer
21.732
970169AG2-114 GEN
Solar/Wind Harmer
14.468
972267AH1-718 GEN
Adder
5.934
958391AF2-133 GEN
Solar/Wind Harmer
0.636
NYPJM->LTFIMP_NY
CLTF
2.548
LGEELTFEXP_LGEE->PJM
CLTF
3.406
WECLTFEXP_WEC->PJM
CLTF
5.594
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.738
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.286
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
95.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.604
MECLTFEXP_MEC->PJM
CLTF
20.061
SIGELTFEXP_SIGE->PJM
CLTF
0.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.346
AH1-155LTFEXP_AH1-155->PJM
LTF
0.518
LAGNLTFEXP_LAGN->PJM
CLTF
10.559
TVALTFEXP_TVA->PJM
CLTF
3.978

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_05MARYSV 765_C2_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_05MARYSV 765_C2_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.05 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4558.43
MW Contribution:
21.74
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.051
24642205MAYFLWER
50/50
0.062
944961AF1-161 GEN
50/50
4.803
962601AG1-109 GEN
50/50
4.803
274772LINCOLN ;3U
50/50
10.761
971347AH1-153 GEN
Solar/Wind Harmer
8.946
270043AE2-236 GEN
Solar/Wind Harmer
9.722
247643Z2-116 C
Solar/Wind Harmer
0.117
944531AF1-118 GEN
Solar/Wind Harmer
58.718
24441505OLIV SLR
Solar/Wind Harmer
0.224
270505AE1-170 C O1
Solar/Wind Harmer
25.058
945111AF1-176 GEN
Solar/Wind Harmer
9.393
270063AE2-323 C
Solar/Wind Harmer
3.63
274724RIVER EC ;11
Adder
28.386
972231SS25-0005
Solar/Wind Harmer
15.175
972181SS23-001
Solar/Wind Harmer
9.485
274752CRETE EC ;2U
Adder
7.816
274753CRETE EC ;3U
Adder
7.816
276164X3-005 C
Solar/Wind Harmer
1.121
274814UNIV PK N;0U
Adder
8.031
274807UNIV PK N;3U
Adder
8.014
274811UNIV PK N;7U
Adder
7.962
970707AG2-453 GEN
Solar/Wind Harmer
44.413
274826FISK ;BP
Adder
17.309
274803UNIV PARK;6U
Adder
9.218
274887GEN-1.85
Solar/Wind Harmer
8.417
276772AC2-154 GEN
Solar/Wind Harmer
4.409
276843GEN-1.7
Solar/Wind Harmer
0.906
276806AD2-047 C O1
Solar/Wind Harmer
16.9
972259AH1-714 GEN
Adder
30.138
972038AH1-567 GEN2
Adder
0.576
939351AE1-166 GEN
Solar/Wind Harmer
9.326
274676JOLIET 29;8U
Adder
46.288
274730ELWOOD EC;6P
Adder
25.639
274734ELWOOD EC;8P
Adder
25.639
274736ELWOOD EC;9P
Adder
25.639
274729ELWOOD EC;1P
Adder
25.638
965021AG1-366 GEN
Solar/Wind Harmer
3.621
943121AE2-341 GEN
Solar/Wind Harmer
23.236
943591AF1-030 GEN
Solar/Wind Harmer
15.491
274862TOP CROP ;2U
Solar/Wind Harmer
7.706
270102X2-052 ST
50/50
2.707
270100X2-052 CT1
50/50
2.5
270101X2-052 CT2
50/50
2.5
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.807
274770LINCOLN ;1U
50/50
10.761
274771LINCOLN ;2U
50/50
10.761
970349AG2-230 GEN
Solar/Wind Harmer
26.838
965681AG1-436 GEN
Solar/Wind Harmer
20.988
965791AG1-447 GEN
Solar/Wind Harmer
10.738
961051AF2-396 GEN
Solar/Wind Harmer
26.277
961051AF2-396 GEN
Solar/Wind Harmer
12.222
274805UNIV PK N;1U
Adder
7.979
274808UNIV PK N;4U
Adder
7.927
274888KELLY CRK;1U
Solar/Wind Harmer
9.323
276776AD2-060 GEN
Solar/Wind Harmer
0.661
958011AF2-095 GEN
Solar/Wind Harmer
22.75
970941AG2-585 GEN
Solar/Wind Harmer
8.689
276897AD1-100 C
Solar/Wind Harmer
73.051
274674JOLIET 9 ;6U
Adder
24.037
276893AG1-478 C
Solar/Wind Harmer
0.683
274695ROCKY RD ;2P
Adder
16.987
274693ROCKY RD ;1P
Adder
16.82
274697ROCKY RD ;3P
Adder
4.615
274696ROCKY RD ;4P
Adder
17.388
958481AF2-142 GEN
Solar/Wind Harmer
22.866
274683WAUKEGAN ;8U
Adder
32.05
274683WAUKEGAN ;8U
Adder
27.017
944541AF1-119 GEN
Solar/Wind Harmer
6.339
960971AF2-388 GEN
Solar/Wind Harmer
16.546
962691AG1-118 GEN
Solar/Wind Harmer
45.394
960751AF2-366 GEN
Solar/Wind Harmer
4.329
958491AF2-143 GEN
Solar/Wind Harmer
22.545
270535AF1-215 GEN1
Solar/Wind Harmer
6.814
270536AF1-215 GEN2
Solar/Wind Harmer
6.814
276901AD2-066 C O1
Solar/Wind Harmer
5.257
971341AH1-150 GEN
Solar/Wind Harmer
29.544
971343AH1-151 GEN
Solar/Wind Harmer
29.544
276872AE1-163_GEN1
Solar/Wind Harmer
9.894
276876AE1-163_GEN2
Solar/Wind Harmer
9.894
972235AH1-702 GEN1
Adder
3.699
972236AH1-702 GEN2
Adder
3.217
938861AE1-114 GEN
Solar/Wind Harmer
11.875
274764LEE CO EC;5U
Adder
13.449
274765LEE CO EC;6U
Adder
13.449
274762LEE CO EC;3U
Adder
13.418
274763LEE CO EC;4U
Adder
13.291
247621Y3-024
Adder
0.269
270349AD2-093_GEN
Solar/Wind Helper
1.483
270471AD2-092_GEN
Solar/Wind Helper
1.483
24344105CKG2
50/50
14.019
270143AC1-141 CT2_
50/50
4.051
24639705ELKHART HY
50/50
0.271
970521AG2-332 GEN
50/50
19.267
24307105BERRINSP G
50/50
0.035
274773LINCOLN ;4U
50/50
10.761
274774LINCOLN ;5U
50/50
10.761
270216AD2-079_GEN
Solar/Wind Harmer
1.018
957891AF2-083 GEN
Solar/Wind Harmer
25.008
945111AF1-176 GEN
Solar/Wind Harmer
29.638
270449AD2-020 GEN
Solar/Wind Harmer
4.629
943021AE2-325 GEN
Solar/Wind Harmer
6.017
972207SS24-0001
Solar/Wind Harmer
36.058
24441205WTRV SLR C
Solar/Wind Harmer
0.218
274723RIVER EC ;12
Adder
28.715
274751CRETE EC ;1U
Adder
7.816
274754CRETE EC ;4U
Adder
7.816
274812UNIV PK N;8U
Adder
7.962
274802UNIV PARK;5U
Adder
9.218
941551AE2-152 GEN
Solar/Wind Harmer
7.132
274676JOLIET 29;8U
Adder
48.002
274674JOLIET 9 ;6U
Adder
24.037
274732ELWOOD EC;7P
Adder
25.639
965011AG1-365 GEN
Solar/Wind Harmer
15.569
274871GR RIDGE ;2U
Solar/Wind Harmer
11.966
274847GR RIDGE ;BU
Solar/Wind Harmer
7.868
970373AG2-245 GEN
Solar/Wind Harmer
32.493
274745AC1-111 GEN9
Adder
8.641
276694AA1-018 GEN2
Solar/Wind Harmer
9.619
276691AA1-018 GEN1
Solar/Wind Harmer
1.15
274861TOP CROP ;1U
Solar/Wind Harmer
9.229
274682WAUKEGAN ;7U
Adder
27.375
274828WAUKEGAN ;BP
Adder
16.8
965651AG1-433 GEN
Solar/Wind Harmer
8.273
962781AG1-127 GEN
Solar/Wind Harmer
14.349
939401AE1-172 GEN
Solar/Wind Harmer
20.973
274872LEEDK;1U
Solar/Wind Harmer
12.354
276805AD2-038 GEN
Solar/Wind Harmer
7.707
270055AF2-134 C O1
Solar/Wind Harmer
4.543
276882AE2-255 GEN
Solar/Wind Harmer
5.04
971997AH1-543 GEN
Solar/Wind Harmer
23.475
957471AF2-041 GEN
Solar/Wind Harmer
44.316
959081AF2-199 GEN
Solar/Wind Harmer
14.772
971067AG2-660 GEN
Solar/Wind Harmer
3.435
958861AF2-177 GEN
Solar/Wind Harmer
16.115
274822ROCKFORD ;11
Adder
28.883
970819AG2-516 GEN
Solar/Wind Harmer
17.544
958381AF2-132 GEN
Solar/Wind Harmer
13.205
970569AG2-363 GEN
Solar/Wind Harmer
43.588
964861AG1-349 GEN
Solar/Wind Harmer
11.404
971917AH1-482 GEN
Solar/Wind Harmer
13.158
274858EASY ROAD;U2
Solar/Wind Harmer
6.909
274761LEE CO EC;2U
Adder
13.418
274766LEE CO EC;7U
Adder
13.26
24728605AND G2
Adder
3.703
24344005CKG1
50/50
10.928
270144AC1-141 ST1_
50/50
3.59
24641605TWIN BRNCH
50/50
0.029
24653605MOTTVILLE
50/50
0.006
274775LINCOLN ;6U
50/50
10.761
274776LINCOLN ;7U
50/50
10.761
274777LINCOLN ;8U
50/50
10.761
971771AH1-392 GEN
Solar/Wind Harmer
15.181
270071AF1-092 GEN
Solar/Wind Harmer
25.227
960681AF2-359 GEN
Solar/Wind Harmer
6.344
270526AF1-158 GEN
Solar/Wind Harmer
7.601
944161AF1-084 GEN
Solar/Wind Harmer
3.629
24729505KEY G4
Adder
10.601
970031AG2-029 GEN
Solar/Wind Harmer
40.745
274827FISK ;RP
Adder
12.267
972037AH1-567 GEN1
Adder
0.289
960591AF2-350 GEN
Solar/Wind Harmer
15.798
274800UNIV PARK;3U
Adder
9.206
274801UNIV PARK;4U
Adder
9.206
972228AH1-698 GEN2
Adder
5.848
972227AH1-698 GEN1
Adder
4.118
274687WILL CNTY;4U
Adder
43.781
274687WILL CNTY;4U
Adder
43.781
274675JOLIET 29;7U
Adder
48.003
274675JOLIET 29;7U
Adder
46.289
274728ELWOOD EC;5P
Adder
25.639
274731ELWOOD EC;2P
Adder
25.638
274733ELWOOD EC;3P
Adder
25.638
274735ELWOOD EC;4P
Adder
25.638
276893AG1-478 C
Solar/Wind Harmer
0.857
970833AG2-524 GEN
Solar/Wind Harmer
13.593
970833AG2-524 GEN
Solar/Wind Harmer
6.322
959331AF2-224 GEN
Solar/Wind Harmer
15.569
274744AC1-111 GEN8
Adder
8.641
274746AC1-111 G10
Adder
8.641
958711AF2-162 GEN
Solar/Wind Harmer
1.531
970073AG2-061 GEN
Solar/Wind Harmer
3.495
971549AH1-272 GEN
Solar/Wind Harmer
27.785
971411AH1-196 GEN
Solar/Wind Harmer
22.33
971675AH1-338 GEN
Solar/Wind Harmer
26.789
276861AD2-134 GEN
Solar/Wind Harmer
2.656
276863AD2-134 GEN
Solar/Wind Harmer
2.656
971171AH1-044 GEN
Solar/Wind Harmer
29.544
274863CRW1-WTG
Solar/Wind Harmer
8.244
274864CRW2-WTG
Solar/Wind Harmer
8.244
276889AE2-281 GEN
Solar/Wind Harmer
2.827
274823ROCKFORD ;21
Adder
28.673
274856ECOGROVE ;U1
Solar/Wind Harmer
4.921
276611AD2-172 GEN
Solar/Wind Harmer
3.733
276612AE2-035 GEN
Solar/Wind Harmer
3.733
926823AC1-168 GEN
Solar/Wind Harmer
6.242
971681AH1-341 GEN
Solar/Wind Harmer
21.737
970169AG2-114 GEN
Solar/Wind Harmer
14.474
972267AH1-718 GEN
Adder
5.936
958391AF2-133 GEN
Solar/Wind Harmer
0.637
274682WAUKEGAN ;7U
Adder
27.375
276868AE1-113 GEN
Solar/Wind Harmer
15.119
274879MINONK ;1U
Solar/Wind Harmer
10.08
276799AD1-013 GEN
Solar/Wind Harmer
3.29
946671AF1-331 GEN
Solar/Wind Harmer
0.623
274855GSG-6 ;RU
Solar/Wind Harmer
5.493
274850MENDOTA H;RU
Solar/Wind Harmer
3.819
276602WESTBROOK C
Solar/Wind Harmer
3.162
959091AF2-200 GEN
Solar/Wind Harmer
29.544
964401AG1-302 GEN
Solar/Wind Harmer
13.205
970571AG2-364 GEN
Solar/Wind Harmer
29.059
274857EASY ROAD;U1
Solar/Wind Harmer
6.909
274760LEE CO EC;1U
Adder
13.418
274767LEE CO EC;8U
Adder
13.26
276603SUBLETTE C
Solar/Wind Harmer
1.51
24728505AND G1
Adder
3.703
NYPJM->LTFIMP_NY
CLTF
2.562
LGEELTFEXP_LGEE->PJM
CLTF
3.44
WECLTFEXP_WEC->PJM
CLTF
5.595
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.756
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.297
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
95.453
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.645
MECLTFEXP_MEC->PJM
CLTF
20.072
SIGELTFEXP_SIGE->PJM
CLTF
0.372
AG2-052LTFEXP_AG2-052->PJM
LTF
0.346
AH1-155LTFEXP_AH1-155->PJM
LTF
0.519
LAGNLTFEXP_LAGN->PJM
CLTF
10.564
TVALTFEXP_TVA->PJM
CLTF
3.981

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.64 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4541.17
MW Contribution:
21.18
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.88 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6125.38
MW Contribution:
27.72
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
3.969
24642205MAYFLWER
50/50
0.06
944961AF1-161 GEN
50/50
4.707
962601AG1-109 GEN
50/50
4.707
270043AE2-236 GEN
Solar/Wind Harmer
9.708
971347AH1-153 GEN
Solar/Wind Harmer
8.745
944531AF1-118 GEN
Solar/Wind Harmer
59.074
247643Z2-116 C
Solar/Wind Harmer
0.115
270505AE1-170 C O1
Solar/Wind Harmer
24.553
270063AE2-323 C
Solar/Wind Harmer
3.592
24441505OLIV SLR
Solar/Wind Harmer
0.218
945111AF1-176 GEN
Solar/Wind Harmer
9.209
274772LINCOLN ;3U
Adder
9.889
965021AG1-366 GEN
Solar/Wind Harmer
3.65
274724RIVER EC ;11
Adder
27.655
972231SS25-0005
Solar/Wind Harmer
14.775
972181SS23-001
Solar/Wind Harmer
9.234
274752CRETE EC ;2U
Adder
7.609
274753CRETE EC ;3U
Adder
7.609
276164X3-005 C
Solar/Wind Harmer
1.093
274814UNIV PK N;0U
Adder
7.822
274807UNIV PK N;3U
Adder
7.805
274811UNIV PK N;7U
Adder
7.754
970707AG2-453 GEN
Solar/Wind Harmer
43.293
274826FISK ;BP
Adder
16.866
274803UNIV PARK;6U
Adder
8.981
972259AH1-714 GEN
Adder
29.375
274887GEN-1.85
Solar/Wind Harmer
8.202
276772AC2-154 GEN
Solar/Wind Harmer
4.296
276843GEN-1.7
Solar/Wind Harmer
0.883
276806AD2-047 C O1
Solar/Wind Harmer
16.469
972038AH1-567 GEN2
Adder
0.561
939351AE1-166 GEN
Solar/Wind Harmer
9.09
274676JOLIET 29;8U
Adder
45.107
274730ELWOOD EC;6P
Adder
24.985
274734ELWOOD EC;8P
Adder
24.985
274736ELWOOD EC;9P
Adder
24.985
274729ELWOOD EC;1P
Adder
24.985
943121AE2-341 GEN
Solar/Wind Harmer
22.647
943591AF1-030 GEN
Solar/Wind Harmer
15.098
274862TOP CROP ;2U
Solar/Wind Harmer
7.509
274682WAUKEGAN ;7U
Adder
26.676
276868AE1-113 GEN
Solar/Wind Harmer
14.735
274879MINONK ;1U
Solar/Wind Harmer
9.824
276799AD1-013 GEN
Solar/Wind Harmer
3.206
946671AF1-331 GEN
Solar/Wind Harmer
0.607
274855GSG-6 ;RU
Solar/Wind Harmer
5.353
274850MENDOTA H;RU
Solar/Wind Harmer
3.722
276602WESTBROOK C
Solar/Wind Harmer
3.082
959091AF2-200 GEN
Solar/Wind Harmer
28.79
970571AG2-364 GEN
Solar/Wind Harmer
28.322
274857EASY ROAD;U1
Solar/Wind Harmer
6.732
274760LEE CO EC;1U
Adder
13.074
274767LEE CO EC;8U
Adder
12.92
276603SUBLETTE C
Solar/Wind Harmer
1.471
24728505AND G1
Adder
3.591
270102X2-052 ST
50/50
2.634
270100X2-052 CT1
50/50
2.433
270101X2-052 CT2
50/50
2.433
24729405KEY G3
50/50
0.617
24729305KEY G2
50/50
0.607
24729205KEY G1
50/50
0.604
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.794
970349AG2-230 GEN
Solar/Wind Harmer
26.234
965681AG1-436 GEN
Solar/Wind Harmer
20.418
965791AG1-447 GEN
Solar/Wind Harmer
10.446
961051AF2-396 GEN
Solar/Wind Harmer
25.755
961051AF2-396 GEN
Solar/Wind Harmer
11.979
274770LINCOLN ;1U
Adder
9.889
274771LINCOLN ;2U
Adder
9.889
274805UNIV PK N;1U
Adder
7.771
274808UNIV PK N;4U
Adder
7.72
274888KELLY CRK;1U
Solar/Wind Harmer
9.085
276776AD2-060 GEN
Solar/Wind Harmer
0.644
958011AF2-095 GEN
Solar/Wind Harmer
22.169
970941AG2-585 GEN
Solar/Wind Harmer
8.467
276897AD1-100 C
Solar/Wind Harmer
71.205
274674JOLIET 9 ;6U
Adder
23.424
276893AG1-478 C
Solar/Wind Harmer
0.666
944541AF1-119 GEN
Solar/Wind Harmer
6.354
960971AF2-388 GEN
Solar/Wind Harmer
16.587
274695ROCKY RD ;2P
Adder
16.555
274693ROCKY RD ;1P
Adder
16.392
274697ROCKY RD ;3P
Adder
4.497
274696ROCKY RD ;4P
Adder
16.945
958481AF2-142 GEN
Solar/Wind Harmer
22.283
274683WAUKEGAN ;8U
Adder
31.232
274683WAUKEGAN ;8U
Adder
26.327
962691AG1-118 GEN
Solar/Wind Harmer
44.239
960751AF2-366 GEN
Solar/Wind Harmer
4.219
958491AF2-143 GEN
Solar/Wind Harmer
21.971
276901AD2-066 C O1
Solar/Wind Harmer
5.123
971341AH1-150 GEN
Solar/Wind Harmer
28.79
971343AH1-151 GEN
Solar/Wind Harmer
28.79
276872AE1-163_GEN1
Solar/Wind Harmer
9.642
276876AE1-163_GEN2
Solar/Wind Harmer
9.642
972235AH1-702 GEN1
Adder
3.605
972236AH1-702 GEN2
Adder
3.134
270535AF1-215 GEN1
Solar/Wind Harmer
6.477
270536AF1-215 GEN2
Solar/Wind Harmer
6.477
938861AE1-114 GEN
Solar/Wind Harmer
11.571
274764LEE CO EC;5U
Adder
13.105
274765LEE CO EC;6U
Adder
13.105
274762LEE CO EC;3U
Adder
13.074
274763LEE CO EC;4U
Adder
12.951
942221AE2-234 GEN
Solar/Wind Harmer
4.887
247621Y3-024
Adder
0.265
270349AD2-093_GEN
Solar/Wind Helper
1.354
270471AD2-092_GEN
Solar/Wind Helper
1.354
276158O29GEN2
Solar/Wind Harmer
5.508
276157O29GEN1
Solar/Wind Harmer
4.188
24344105CKG2
50/50
13.703
270143AC1-141 CT2_
50/50
3.969
24639705ELKHART HY
50/50
0.266
970521AG2-332 GEN
50/50
18.921
24307105BERRINSP G
50/50
0.035
270216AD2-079_GEN
Solar/Wind Harmer
0.998
957891AF2-083 GEN
Solar/Wind Harmer
24.504
945111AF1-176 GEN
Solar/Wind Harmer
29.057
270449AD2-020 GEN
Solar/Wind Harmer
4.536
943021AE2-325 GEN
Solar/Wind Harmer
5.896
972207SS24-0001
Solar/Wind Harmer
35.159
274773LINCOLN ;4U
Adder
9.889
274774LINCOLN ;5U
Adder
9.889
24441205WTRV SLR C
Solar/Wind Harmer
0.214
965011AG1-365 GEN
Solar/Wind Harmer
15.695
274723RIVER EC ;12
Adder
27.973
274751CRETE EC ;1U
Adder
7.609
274754CRETE EC ;4U
Adder
7.609
274812UNIV PK N;8U
Adder
7.754
274802UNIV PARK;5U
Adder
8.981
941551AE2-152 GEN
Solar/Wind Harmer
6.952
274676JOLIET 29;8U
Adder
46.777
274674JOLIET 9 ;6U
Adder
23.424
274732ELWOOD EC;7P
Adder
24.985
965651AG1-433 GEN
Solar/Wind Harmer
8.293
274871GR RIDGE ;2U
Solar/Wind Harmer
11.662
274847GR RIDGE ;BU
Solar/Wind Harmer
7.668
274745AC1-111 GEN9
Adder
8.422
276694AA1-018 GEN2
Solar/Wind Harmer
9.373
276691AA1-018 GEN1
Solar/Wind Harmer
1.12
274861TOP CROP ;1U
Solar/Wind Harmer
8.994
274682WAUKEGAN ;7U
Adder
26.676
274828WAUKEGAN ;BP
Adder
16.371
970373AG2-245 GEN
Solar/Wind Harmer
31.076
958861AF2-177 GEN
Solar/Wind Harmer
16.139
962781AG1-127 GEN
Solar/Wind Harmer
13.983
939401AE1-172 GEN
Solar/Wind Harmer
20.448
274872LEEDK;1U
Solar/Wind Harmer
12.039
276805AD2-038 GEN
Solar/Wind Harmer
7.511
276882AE2-255 GEN
Solar/Wind Harmer
4.912
971997AH1-543 GEN
Solar/Wind Harmer
22.881
957471AF2-041 GEN
Solar/Wind Harmer
43.185
959081AF2-199 GEN
Solar/Wind Harmer
14.395
971067AG2-660 GEN
Solar/Wind Harmer
3.348
274822ROCKFORD ;11
Adder
28.144
270055AF2-134 C O1
Solar/Wind Harmer
4.318
970819AG2-516 GEN
Solar/Wind Harmer
17.095
970569AG2-363 GEN
Solar/Wind Harmer
42.484
274858EASY ROAD;U2
Solar/Wind Harmer
6.732
274761LEE CO EC;2U
Adder
13.074
274766LEE CO EC;7U
Adder
12.92
945371AF1-202 GEN
Solar/Wind Harmer
9.756
24728605AND G2
Adder
3.591
270144AC1-141 ST1_
50/50
3.518
24344005CKG1
50/50
10.694
24641605TWIN BRNCH
50/50
0.028
24729505KEY G4
50/50
11.308
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
24.785
971771AH1-392 GEN
Solar/Wind Harmer
14.851
270526AF1-158 GEN
Solar/Wind Harmer
7.418
960681AF2-359 GEN
Solar/Wind Harmer
6.172
970031AG2-029 GEN
Solar/Wind Harmer
40.379
944161AF1-084 GEN
Solar/Wind Harmer
3.556
274775LINCOLN ;6U
Adder
9.889
274776LINCOLN ;7U
Adder
9.889
274777LINCOLN ;8U
Adder
9.889
959331AF2-224 GEN
Solar/Wind Harmer
15.695
274827FISK ;RP
Adder
11.953
972037AH1-567 GEN1
Adder
0.282
960591AF2-350 GEN
Solar/Wind Harmer
15.395
972228AH1-698 GEN2
Adder
5.699
972227AH1-698 GEN1
Adder
4.013
274800UNIV PARK;3U
Adder
8.97
274801UNIV PARK;4U
Adder
8.97
274687WILL CNTY;4U
Adder
42.663
274687WILL CNTY;4U
Adder
42.663
274675JOLIET 29;7U
Adder
46.778
274675JOLIET 29;7U
Adder
45.107
274728ELWOOD EC;5P
Adder
24.985
274731ELWOOD EC;2P
Adder
24.985
274733ELWOOD EC;3P
Adder
24.985
274735ELWOOD EC;4P
Adder
24.985
276893AG1-478 C
Solar/Wind Harmer
0.836
970833AG2-524 GEN
Solar/Wind Harmer
13.249
970833AG2-524 GEN
Solar/Wind Harmer
6.162
958711AF2-162 GEN
Solar/Wind Harmer
1.535
274744AC1-111 GEN8
Adder
8.422
274746AC1-111 G10
Adder
8.422
971549AH1-272 GEN
Solar/Wind Harmer
27.315
970073AG2-061 GEN
Solar/Wind Harmer
3.406
971411AH1-196 GEN
Solar/Wind Harmer
21.759
971675AH1-338 GEN
Solar/Wind Harmer
26.106
276861AD2-134 GEN
Solar/Wind Harmer
2.589
276863AD2-134 GEN
Solar/Wind Harmer
2.589
274863CRW1-WTG
Solar/Wind Harmer
8.038
274864CRW2-WTG
Solar/Wind Harmer
8.038
971171AH1-044 GEN
Solar/Wind Harmer
28.79
276889AE2-281 GEN
Solar/Wind Harmer
2.755
274823ROCKFORD ;21
Adder
27.94
274856ECOGROVE ;U1
Solar/Wind Harmer
4.795
276611AD2-172 GEN
Solar/Wind Harmer
3.637
276612AE2-035 GEN
Solar/Wind Harmer
3.637
926823AC1-168 GEN
Solar/Wind Harmer
6.084
971681AH1-341 GEN
Solar/Wind Harmer
21.181
970169AG2-114 GEN
Solar/Wind Harmer
14.112
963791AG1-232 GEN
Solar/Wind Harmer
18.963
945581AF1-223 GEN
Solar/Wind Harmer
6.342
972267AH1-718 GEN
Adder
5.784
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.433
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
3.498
WECLTFEXP_WEC->PJM
CLTF
5.451
CBM West 1LTFEXP_CBM-W1->PJM
CBM
166.786
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.792
CBM West 2LTFEXP_CBM-W2->PJM
CBM
92.071
MECLTFEXP_MEC->PJM
CLTF
19.53
SIGELTFEXP_SIGE->PJM
CLTF
0.368
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.96
AG2-052LTFEXP_AG2-052->PJM
LTF
0.335
AH1-155LTFEXP_AH1-155->PJM
LTF
0.502
LAGNLTFEXP_LAGN->PJM
CLTF
9.979
TVALTFEXP_TVA->PJM
CLTF
3.685

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.44 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4491.48
MW Contribution:
21.23
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.29 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6059.51
MW Contribution:
27.79
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
3.977
24642205MAYFLWER
50/50
0.06
944961AF1-161 GEN
50/50
4.716
962601AG1-109 GEN
50/50
4.716
270043AE2-236 GEN
Solar/Wind Harmer
9.725
971347AH1-153 GEN
Solar/Wind Harmer
8.761
944531AF1-118 GEN
Solar/Wind Harmer
59.186
247643Z2-116 C
Solar/Wind Harmer
0.115
270505AE1-170 C O1
Solar/Wind Harmer
24.601
270063AE2-323 C
Solar/Wind Harmer
3.599
24441505OLIV SLR
Solar/Wind Harmer
0.219
945111AF1-176 GEN
Solar/Wind Harmer
9.227
274772LINCOLN ;3U
Adder
9.909
965021AG1-366 GEN
Solar/Wind Harmer
3.658
270102X2-052 ST
50/50
2.639
270100X2-052 CT1
50/50
2.438
270101X2-052 CT2
50/50
2.438
24729405KEY G3
50/50
0.619
24729305KEY G2
50/50
0.608
24729205KEY G1
50/50
0.605
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.795
970349AG2-230 GEN
Solar/Wind Harmer
26.283
965681AG1-436 GEN
Solar/Wind Harmer
20.458
965791AG1-447 GEN
Solar/Wind Harmer
10.467
961051AF2-396 GEN
Solar/Wind Harmer
25.806
961051AF2-396 GEN
Solar/Wind Harmer
12.003
274770LINCOLN ;1U
Adder
9.909
274771LINCOLN ;2U
Adder
9.909
274805UNIV PK N;1U
Adder
7.787
274808UNIV PK N;4U
Adder
7.736
274888KELLY CRK;1U
Solar/Wind Harmer
9.104
276776AD2-060 GEN
Solar/Wind Harmer
0.646
958011AF2-095 GEN
Solar/Wind Harmer
22.215
970941AG2-585 GEN
Solar/Wind Harmer
8.485
276897AD1-100 C
Solar/Wind Harmer
71.354
274674JOLIET 9 ;6U
Adder
23.474
276893AG1-478 C
Solar/Wind Harmer
0.667
944541AF1-119 GEN
Solar/Wind Harmer
6.368
960971AF2-388 GEN
Solar/Wind Harmer
16.622
274695ROCKY RD ;2P
Adder
16.591
274693ROCKY RD ;1P
Adder
16.427
274697ROCKY RD ;3P
Adder
4.507
274696ROCKY RD ;4P
Adder
16.982
958481AF2-142 GEN
Solar/Wind Harmer
22.332
274683WAUKEGAN ;8U
Adder
31.299
274683WAUKEGAN ;8U
Adder
26.384
962691AG1-118 GEN
Solar/Wind Harmer
44.335
960751AF2-366 GEN
Solar/Wind Harmer
4.228
958491AF2-143 GEN
Solar/Wind Harmer
22.019
276901AD2-066 C O1
Solar/Wind Harmer
5.135
971341AH1-150 GEN
Solar/Wind Harmer
28.854
971343AH1-151 GEN
Solar/Wind Harmer
28.854
276872AE1-163_GEN1
Solar/Wind Harmer
9.664
276876AE1-163_GEN2
Solar/Wind Harmer
9.664
972235AH1-702 GEN1
Adder
3.613
972236AH1-702 GEN2
Adder
3.141
270535AF1-215 GEN1
Solar/Wind Harmer
6.492
270536AF1-215 GEN2
Solar/Wind Harmer
6.492
938861AE1-114 GEN
Solar/Wind Harmer
11.597
274764LEE CO EC;5U
Adder
13.135
274765LEE CO EC;6U
Adder
13.135
274762LEE CO EC;3U
Adder
13.104
274763LEE CO EC;4U
Adder
12.98
942221AE2-234 GEN
Solar/Wind Harmer
4.898
247621Y3-024
Adder
0.266
270349AD2-093_GEN
Solar/Wind Helper
1.349
270471AD2-092_GEN
Solar/Wind Helper
1.349
276158O29GEN2
Solar/Wind Harmer
5.521
276157O29GEN1
Solar/Wind Harmer
4.198
274724RIVER EC ;11
Adder
27.711
972231SS25-0005
Solar/Wind Harmer
14.805
972181SS23-001
Solar/Wind Harmer
9.253
274752CRETE EC ;2U
Adder
7.625
274753CRETE EC ;3U
Adder
7.625
276164X3-005 C
Solar/Wind Harmer
1.095
274814UNIV PK N;0U
Adder
7.838
274807UNIV PK N;3U
Adder
7.821
274811UNIV PK N;7U
Adder
7.77
970707AG2-453 GEN
Solar/Wind Harmer
43.383
274826FISK ;BP
Adder
16.901
274803UNIV PARK;6U
Adder
9
972259AH1-714 GEN
Adder
29.436
274887GEN-1.85
Solar/Wind Harmer
8.22
276772AC2-154 GEN
Solar/Wind Harmer
4.305
276843GEN-1.7
Solar/Wind Harmer
0.884
276806AD2-047 C O1
Solar/Wind Harmer
16.503
972038AH1-567 GEN2
Adder
0.563
939351AE1-166 GEN
Solar/Wind Harmer
9.109
274676JOLIET 29;8U
Adder
45.202
274730ELWOOD EC;6P
Adder
25.038
274734ELWOOD EC;8P
Adder
25.038
274736ELWOOD EC;9P
Adder
25.038
274729ELWOOD EC;1P
Adder
25.038
943121AE2-341 GEN
Solar/Wind Harmer
22.695
943591AF1-030 GEN
Solar/Wind Harmer
15.13
274862TOP CROP ;2U
Solar/Wind Harmer
7.526
274682WAUKEGAN ;7U
Adder
26.734
276868AE1-113 GEN
Solar/Wind Harmer
14.768
274879MINONK ;1U
Solar/Wind Harmer
9.846
276799AD1-013 GEN
Solar/Wind Harmer
3.213
946671AF1-331 GEN
Solar/Wind Harmer
0.609
274855GSG-6 ;RU
Solar/Wind Harmer
5.365
274850MENDOTA H;RU
Solar/Wind Harmer
3.73
276602WESTBROOK C
Solar/Wind Harmer
3.088
959091AF2-200 GEN
Solar/Wind Harmer
28.854
970571AG2-364 GEN
Solar/Wind Harmer
28.387
274857EASY ROAD;U1
Solar/Wind Harmer
6.748
274760LEE CO EC;1U
Adder
13.104
274767LEE CO EC;8U
Adder
12.95
276603SUBLETTE C
Solar/Wind Harmer
1.475
24728505AND G1
Adder
3.604
24344105CKG2
50/50
13.727
270143AC1-141 CT2_
50/50
3.977
24639705ELKHART HY
50/50
0.267
970521AG2-332 GEN
50/50
18.959
24307105BERRINSP G
50/50
0.035
270216AD2-079_GEN
Solar/Wind Harmer
1
957891AF2-083 GEN
Solar/Wind Harmer
24.552
945111AF1-176 GEN
Solar/Wind Harmer
29.114
270449AD2-020 GEN
Solar/Wind Harmer
4.545
943021AE2-325 GEN
Solar/Wind Harmer
5.908
972207SS24-0001
Solar/Wind Harmer
35.229
274773LINCOLN ;4U
Adder
9.909
274774LINCOLN ;5U
Adder
9.909
24441205WTRV SLR C
Solar/Wind Harmer
0.214
965011AG1-365 GEN
Solar/Wind Harmer
15.727
274723RIVER EC ;12
Adder
28.031
274751CRETE EC ;1U
Adder
7.625
274754CRETE EC ;4U
Adder
7.625
274812UNIV PK N;8U
Adder
7.77
274802UNIV PARK;5U
Adder
9
941551AE2-152 GEN
Solar/Wind Harmer
6.967
274676JOLIET 29;8U
Adder
46.876
274674JOLIET 9 ;6U
Adder
23.474
274732ELWOOD EC;7P
Adder
25.038
965651AG1-433 GEN
Solar/Wind Harmer
8.311
274871GR RIDGE ;2U
Solar/Wind Harmer
11.687
274847GR RIDGE ;BU
Solar/Wind Harmer
7.685
274745AC1-111 GEN9
Adder
8.44
276694AA1-018 GEN2
Solar/Wind Harmer
9.394
276691AA1-018 GEN1
Solar/Wind Harmer
1.123
274861TOP CROP ;1U
Solar/Wind Harmer
9.013
274682WAUKEGAN ;7U
Adder
26.734
274828WAUKEGAN ;BP
Adder
16.407
970373AG2-245 GEN
Solar/Wind Harmer
31.143
958861AF2-177 GEN
Solar/Wind Harmer
16.174
962781AG1-127 GEN
Solar/Wind Harmer
14.014
939401AE1-172 GEN
Solar/Wind Harmer
20.492
274872LEEDK;1U
Solar/Wind Harmer
12.065
276805AD2-038 GEN
Solar/Wind Harmer
7.527
276882AE2-255 GEN
Solar/Wind Harmer
4.923
971997AH1-543 GEN
Solar/Wind Harmer
22.932
957471AF2-041 GEN
Solar/Wind Harmer
43.281
959081AF2-199 GEN
Solar/Wind Harmer
14.427
971067AG2-660 GEN
Solar/Wind Harmer
3.355
274822ROCKFORD ;11
Adder
28.207
270055AF2-134 C O1
Solar/Wind Harmer
4.328
970819AG2-516 GEN
Solar/Wind Harmer
17.133
970569AG2-363 GEN
Solar/Wind Harmer
42.58
274858EASY ROAD;U2
Solar/Wind Harmer
6.748
274761LEE CO EC;2U
Adder
13.104
274766LEE CO EC;7U
Adder
12.95
945371AF1-202 GEN
Solar/Wind Harmer
9.778
24728605AND G2
Adder
3.604
270144AC1-141 ST1_
50/50
3.524
24344005CKG1
50/50
10.714
24641605TWIN BRNCH
50/50
0.028
24729505KEY G4
50/50
11.33
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
24.834
971771AH1-392 GEN
Solar/Wind Harmer
14.88
270526AF1-158 GEN
Solar/Wind Harmer
7.433
960681AF2-359 GEN
Solar/Wind Harmer
6.184
970031AG2-029 GEN
Solar/Wind Harmer
40.46
944161AF1-084 GEN
Solar/Wind Harmer
3.563
274775LINCOLN ;6U
Adder
9.909
274776LINCOLN ;7U
Adder
9.909
274777LINCOLN ;8U
Adder
9.909
959331AF2-224 GEN
Solar/Wind Harmer
15.727
274827FISK ;RP
Adder
11.978
972037AH1-567 GEN1
Adder
0.283
960591AF2-350 GEN
Solar/Wind Harmer
15.427
972228AH1-698 GEN2
Adder
5.711
972227AH1-698 GEN1
Adder
4.021
274800UNIV PARK;3U
Adder
8.989
274801UNIV PARK;4U
Adder
8.989
274687WILL CNTY;4U
Adder
42.752
274687WILL CNTY;4U
Adder
42.752
274675JOLIET 29;7U
Adder
46.876
274675JOLIET 29;7U
Adder
45.202
274728ELWOOD EC;5P
Adder
25.038
274731ELWOOD EC;2P
Adder
25.038
274733ELWOOD EC;3P
Adder
25.038
274735ELWOOD EC;4P
Adder
25.038
276893AG1-478 C
Solar/Wind Harmer
0.837
958711AF2-162 GEN
Solar/Wind Harmer
1.538
970833AG2-524 GEN
Solar/Wind Harmer
13.277
970833AG2-524 GEN
Solar/Wind Harmer
6.175
274744AC1-111 GEN8
Adder
8.44
274746AC1-111 G10
Adder
8.44
971549AH1-272 GEN
Solar/Wind Harmer
27.374
970073AG2-061 GEN
Solar/Wind Harmer
3.414
971411AH1-196 GEN
Solar/Wind Harmer
21.807
971675AH1-338 GEN
Solar/Wind Harmer
26.164
276861AD2-134 GEN
Solar/Wind Harmer
2.594
276863AD2-134 GEN
Solar/Wind Harmer
2.594
274863CRW1-WTG
Solar/Wind Harmer
8.055
274864CRW2-WTG
Solar/Wind Harmer
8.055
971171AH1-044 GEN
Solar/Wind Harmer
28.854
276889AE2-281 GEN
Solar/Wind Harmer
2.761
274823ROCKFORD ;21
Adder
28.002
274856ECOGROVE ;U1
Solar/Wind Harmer
4.806
276611AD2-172 GEN
Solar/Wind Harmer
3.645
276612AE2-035 GEN
Solar/Wind Harmer
3.645
926823AC1-168 GEN
Solar/Wind Harmer
6.098
971681AH1-341 GEN
Solar/Wind Harmer
21.229
970169AG2-114 GEN
Solar/Wind Harmer
14.144
963791AG1-232 GEN
Solar/Wind Harmer
19.006
945581AF1-223 GEN
Solar/Wind Harmer
6.356
972267AH1-718 GEN
Adder
5.797
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.42
NYPJM->LTFIMP_NY
CLTF
2.463
LGEELTFEXP_LGEE->PJM
CLTF
3.52
WECLTFEXP_WEC->PJM
CLTF
5.463
CBM West 1LTFEXP_CBM-W1->PJM
CBM
167.255
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.914
CBM West 2LTFEXP_CBM-W2->PJM
CBM
92.505
MECLTFEXP_MEC->PJM
CLTF
19.584
SIGELTFEXP_SIGE->PJM
CLTF
0.37
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.938
AG2-052LTFEXP_AG2-052->PJM
LTF
0.336
AH1-155LTFEXP_AH1-155->PJM
LTF
0.503
LAGNLTFEXP_LAGN->PJM
CLTF
10.044
TVALTFEXP_TVA->PJM
CLTF
3.718

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.56 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4455.3
MW Contribution:
21.52
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.65 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6115.5
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
4.07
24642205MAYFLWER
50/50
0.062
944961AF1-161 GEN
50/50
4.826
962601AG1-109 GEN
50/50
4.826
270043AE2-236 GEN
Solar/Wind Harmer
9.883
971347AH1-153 GEN
Solar/Wind Harmer
8.969
944531AF1-118 GEN
Solar/Wind Harmer
59.59
247643Z2-116 C
Solar/Wind Harmer
0.118
270505AE1-170 C O1
Solar/Wind Harmer
25.173
24441505OLIV SLR
Solar/Wind Harmer
0.224
270063AE2-323 C
Solar/Wind Harmer
3.671
945111AF1-176 GEN
Solar/Wind Harmer
9.44
274772LINCOLN ;3U
Adder
10.099
965021AG1-366 GEN
Solar/Wind Harmer
3.714
270102X2-052 ST
50/50
2.703
270100X2-052 CT1
50/50
2.497
270101X2-052 CT2
50/50
2.497
24643105BUCHANAN
50/50
0.021
247620Y3-023
50/50
0.813
24729405KEY G3
50/50
0.622
24729305KEY G2
50/50
0.612
24729205KEY G1
50/50
0.609
970349AG2-230 GEN
Solar/Wind Harmer
26.907
965681AG1-436 GEN
Solar/Wind Harmer
20.943
965791AG1-447 GEN
Solar/Wind Harmer
10.715
24344105CKG2
50/50
14.069
270143AC1-141 CT2_
50/50
4.07
24639705ELKHART HY
50/50
0.273
970521AG2-332 GEN
50/50
19.38
24307105BERRINSP G
50/50
0.036
270216AD2-079_GEN
Solar/Wind Harmer
1.023
957891AF2-083 GEN
Solar/Wind Harmer
25.121
945111AF1-176 GEN
Solar/Wind Harmer
29.785
270449AD2-020 GEN
Solar/Wind Harmer
4.651
943021AE2-325 GEN
Solar/Wind Harmer
6.046
24441205WTRV SLR C
Solar/Wind Harmer
0.219
972207SS24-0001
Solar/Wind Harmer
35.905
274773LINCOLN ;4U
Adder
10.099
274774LINCOLN ;5U
Adder
10.099
965011AG1-365 GEN
Solar/Wind Harmer
15.97
274723RIVER EC ;12
Adder
28.574
274751CRETE EC ;1U
Adder
7.776
274754CRETE EC ;4U
Adder
7.776
274812UNIV PK N;8U
Adder
7.918
274802UNIV PARK;5U
Adder
9.165
941551AE2-152 GEN
Solar/Wind Harmer
7.087
274676JOLIET 29;8U
Adder
47.698
274674JOLIET 9 ;6U
Adder
23.881
274732ELWOOD EC;7P
Adder
25.471
274871GR RIDGE ;2U
Solar/Wind Harmer
11.885
274847GR RIDGE ;BU
Solar/Wind Harmer
7.815
274745AC1-111 GEN9
Adder
8.582
965651AG1-433 GEN
Solar/Wind Harmer
8.339
970373AG2-245 GEN
Solar/Wind Harmer
31.999
276694AA1-018 GEN2
Solar/Wind Harmer
9.544
276691AA1-018 GEN1
Solar/Wind Harmer
1.141
274682WAUKEGAN ;7U
Adder
27.167
274861TOP CROP ;1U
Solar/Wind Harmer
9.157
274828WAUKEGAN ;BP
Adder
16.671
962781AG1-127 GEN
Solar/Wind Harmer
14.233
274872LEEDK;1U
Solar/Wind Harmer
12.252
939401AE1-172 GEN
Solar/Wind Harmer
20.783
276805AD2-038 GEN
Solar/Wind Harmer
7.642
958861AF2-177 GEN
Solar/Wind Harmer
16.213
276882AE2-255 GEN
Solar/Wind Harmer
4.996
971997AH1-543 GEN
Solar/Wind Harmer
23.262
270055AF2-134 C O1
Solar/Wind Harmer
4.452
957471AF2-041 GEN
Solar/Wind Harmer
43.912
959081AF2-199 GEN
Solar/Wind Harmer
14.637
971067AG2-660 GEN
Solar/Wind Harmer
3.404
274822ROCKFORD ;11
Adder
28.615
970819AG2-516 GEN
Solar/Wind Harmer
17.376
970569AG2-363 GEN
Solar/Wind Harmer
43.135
274858EASY ROAD;U2
Solar/Wind Harmer
6.838
274761LEE CO EC;2U
Adder
13.28
274766LEE CO EC;7U
Adder
13.123
958381AF2-132 GEN
Solar/Wind Harmer
12.872
24728605AND G2
Adder
3.549
964861AG1-349 GEN
Solar/Wind Harmer
2.543
971917AH1-482 GEN
Solar/Wind Harmer
2.934
24344005CKG1
50/50
10.972
270144AC1-141 ST1_
50/50
3.606
24641605TWIN BRNCH
50/50
0.029
24653605MOTTVILLE
50/50
0.006
24729505KEY G4
50/50
11.397
971771AH1-392 GEN
Solar/Wind Harmer
15.224
270071AF1-092 GEN
Solar/Wind Harmer
25.344
270526AF1-158 GEN
Solar/Wind Harmer
7.606
960681AF2-359 GEN
Solar/Wind Harmer
6.33
944161AF1-084 GEN
Solar/Wind Harmer
3.647
970031AG2-029 GEN
Solar/Wind Harmer
41.238
274775LINCOLN ;6U
Adder
10.099
274776LINCOLN ;7U
Adder
10.099
274777LINCOLN ;8U
Adder
10.099
959331AF2-224 GEN
Solar/Wind Harmer
15.97
274827FISK ;RP
Adder
12.197
972037AH1-567 GEN1
Adder
0.288
960591AF2-350 GEN
Solar/Wind Harmer
15.705
274800UNIV PARK;3U
Adder
9.152
274801UNIV PARK;4U
Adder
9.152
972228AH1-698 GEN2
Adder
5.813
972227AH1-698 GEN1
Adder
4.093
274687WILL CNTY;4U
Adder
43.508
274687WILL CNTY;4U
Adder
43.508
274675JOLIET 29;7U
Adder
47.699
274675JOLIET 29;7U
Adder
45.996
274728ELWOOD EC;5P
Adder
25.471
274731ELWOOD EC;2P
Adder
25.47
274733ELWOOD EC;3P
Adder
25.47
274735ELWOOD EC;4P
Adder
25.47
276893AG1-478 C
Solar/Wind Harmer
0.852
970833AG2-524 GEN
Solar/Wind Harmer
13.502
970833AG2-524 GEN
Solar/Wind Harmer
6.28
274744AC1-111 GEN8
Adder
8.582
274746AC1-111 G10
Adder
8.582
958711AF2-162 GEN
Solar/Wind Harmer
1.544
971549AH1-272 GEN
Solar/Wind Harmer
28.027
970073AG2-061 GEN
Solar/Wind Harmer
3.466
971411AH1-196 GEN
Solar/Wind Harmer
22.136
971675AH1-338 GEN
Solar/Wind Harmer
26.555
276861AD2-134 GEN
Solar/Wind Harmer
2.633
276863AD2-134 GEN
Solar/Wind Harmer
2.633
971171AH1-044 GEN
Solar/Wind Harmer
29.275
274863CRW1-WTG
Solar/Wind Harmer
8.159
274864CRW2-WTG
Solar/Wind Harmer
8.159
276889AE2-281 GEN
Solar/Wind Harmer
2.8
274823ROCKFORD ;21
Adder
28.408
274856ECOGROVE ;U1
Solar/Wind Harmer
4.873
276611AD2-172 GEN
Solar/Wind Harmer
3.697
276612AE2-035 GEN
Solar/Wind Harmer
3.697
926823AC1-168 GEN
Solar/Wind Harmer
6.176
971681AH1-341 GEN
Solar/Wind Harmer
21.518
970169AG2-114 GEN
Solar/Wind Harmer
14.308
963791AG1-232 GEN
Solar/Wind Harmer
19.213
972267AH1-718 GEN
Adder
5.871
961051AF2-396 GEN
Solar/Wind Harmer
26.405
961051AF2-396 GEN
Solar/Wind Harmer
12.281
274770LINCOLN ;1U
Adder
10.099
274771LINCOLN ;2U
Adder
10.099
274805UNIV PK N;1U
Adder
7.935
274808UNIV PK N;4U
Adder
7.883
274888KELLY CRK;1U
Solar/Wind Harmer
9.268
276776AD2-060 GEN
Solar/Wind Harmer
0.657
958011AF2-095 GEN
Solar/Wind Harmer
22.615
970941AG2-585 GEN
Solar/Wind Harmer
8.638
276897AD1-100 C
Solar/Wind Harmer
72.59
274674JOLIET 9 ;6U
Adder
23.881
276893AG1-478 C
Solar/Wind Harmer
0.679
944541AF1-119 GEN
Solar/Wind Harmer
6.389
960971AF2-388 GEN
Solar/Wind Harmer
16.678
274695ROCKY RD ;2P
Adder
16.86
274693ROCKY RD ;1P
Adder
16.694
274697ROCKY RD ;3P
Adder
4.58
274696ROCKY RD ;4P
Adder
17.257
958481AF2-142 GEN
Solar/Wind Harmer
22.69
274683WAUKEGAN ;8U
Adder
31.805
274683WAUKEGAN ;8U
Adder
26.81
962691AG1-118 GEN
Solar/Wind Harmer
45.034
960751AF2-366 GEN
Solar/Wind Harmer
4.294
958491AF2-143 GEN
Solar/Wind Harmer
22.353
276901AD2-066 C O1
Solar/Wind Harmer
5.211
270535AF1-215 GEN1
Solar/Wind Harmer
6.678
270536AF1-215 GEN2
Solar/Wind Harmer
6.678
971341AH1-150 GEN
Solar/Wind Harmer
29.275
971343AH1-151 GEN
Solar/Wind Harmer
29.275
276872AE1-163_GEN1
Solar/Wind Harmer
9.799
276876AE1-163_GEN2
Solar/Wind Harmer
9.799
972235AH1-702 GEN1
Adder
3.664
972236AH1-702 GEN2
Adder
3.186
938861AE1-114 GEN
Solar/Wind Harmer
11.755
274764LEE CO EC;5U
Adder
13.311
274765LEE CO EC;6U
Adder
13.311
274762LEE CO EC;3U
Adder
13.28
274763LEE CO EC;4U
Adder
13.154
247621Y3-024
Adder
0.265
270349AD2-093_GEN
Solar/Wind Helper
1.323
270471AD2-092_GEN
Solar/Wind Helper
1.323
274724RIVER EC ;11
Adder
28.247
972231SS25-0005
Solar/Wind Harmer
15.097
972181SS23-001
Solar/Wind Harmer
9.436
274752CRETE EC ;2U
Adder
7.776
274753CRETE EC ;3U
Adder
7.776
276164X3-005 C
Solar/Wind Harmer
1.115
274814UNIV PK N;0U
Adder
7.987
274807UNIV PK N;3U
Adder
7.97
274811UNIV PK N;7U
Adder
7.918
970707AG2-453 GEN
Solar/Wind Harmer
44.159
274826FISK ;BP
Adder
17.21
274803UNIV PARK;6U
Adder
9.165
274887GEN-1.85
Solar/Wind Harmer
8.368
276772AC2-154 GEN
Solar/Wind Harmer
4.383
276843GEN-1.7
Solar/Wind Harmer
0.9
276806AD2-047 C O1
Solar/Wind Harmer
16.801
972259AH1-714 GEN
Adder
29.959
972038AH1-567 GEN2
Adder
0.573
939351AE1-166 GEN
Solar/Wind Harmer
9.267
274676JOLIET 29;8U
Adder
45.995
274730ELWOOD EC;6P
Adder
25.471
274734ELWOOD EC;8P
Adder
25.471
274736ELWOOD EC;9P
Adder
25.471
274729ELWOOD EC;1P
Adder
25.47
943121AE2-341 GEN
Solar/Wind Harmer
23.078
943591AF1-030 GEN
Solar/Wind Harmer
15.385
274682WAUKEGAN ;7U
Adder
27.167
274862TOP CROP ;2U
Solar/Wind Harmer
7.646
276868AE1-113 GEN
Solar/Wind Harmer
14.986
274879MINONK ;1U
Solar/Wind Harmer
9.991
276799AD1-013 GEN
Solar/Wind Harmer
3.261
946671AF1-331 GEN
Solar/Wind Harmer
0.618
274855GSG-6 ;RU
Solar/Wind Harmer
5.445
274850MENDOTA H;RU
Solar/Wind Harmer
3.786
276602WESTBROOK C
Solar/Wind Harmer
3.134
959091AF2-200 GEN
Solar/Wind Harmer
29.275
970571AG2-364 GEN
Solar/Wind Harmer
28.757
274857EASY ROAD;U1
Solar/Wind Harmer
6.838
274760LEE CO EC;1U
Adder
13.28
274767LEE CO EC;8U
Adder
13.123
276603SUBLETTE C
Solar/Wind Harmer
1.494
964401AG1-302 GEN
Solar/Wind Harmer
12.872
24728505AND G1
Adder
3.549
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.458
NYPJM->LTFIMP_NY
CLTF
2.449
LGEELTFEXP_LGEE->PJM
CLTF
3.05
WECLTFEXP_WEC->PJM
CLTF
5.542
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.374
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.832
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.964
MECLTFEXP_MEC->PJM
CLTF
19.669
SIGELTFEXP_SIGE->PJM
CLTF
0.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.992
AG2-052LTFEXP_AG2-052->PJM
LTF
0.341
AH1-155LTFEXP_AH1-155->PJM
LTF
0.512
LAGNLTFEXP_LAGN->PJM
CLTF
9.729
TVALTFEXP_TVA->PJM
CLTF
3.517

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11010___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11010___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.94 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4305.0
MW Contribution:
20.88
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11010___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:136.03 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5634.35
MW Contribution:
No Reportable Contribution
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.651
24729305KEY G2
50/50
0.64
24729205KEY G1
50/50
0.637
247620Y3-023
50/50
0.813
270142AC1-141 CT1_
50/50
4
24642205MAYFLWER
50/50
0.061
944961AF1-161 GEN
50/50
4.736
962601AG1-109 GEN
50/50
4.736
270043AE2-236 GEN
Solar/Wind Harmer
10.297
965021AG1-366 GEN
Solar/Wind Harmer
4.197
944531AF1-118 GEN
Solar/Wind Harmer
62.429
971347AH1-153 GEN
Solar/Wind Harmer
8.762
270063AE2-323 C
Solar/Wind Harmer
3.738
247643Z2-116 C
Solar/Wind Harmer
0.117
270505AE1-170 C O1
Solar/Wind Harmer
24.73
945111AF1-176 GEN
Solar/Wind Harmer
9.304
24441505OLIV SLR
Solar/Wind Harmer
0.219
274772LINCOLN ;3U
Adder
9.8
274724RIVER EC ;11
Adder
27.457
972231SS25-0005
Solar/Wind Harmer
14.674
972181SS23-001
Solar/Wind Harmer
9.171
274752CRETE EC ;2U
Adder
7.558
274753CRETE EC ;3U
Adder
7.558
276164X3-005 C
Solar/Wind Harmer
1.084
274814UNIV PK N;0U
Adder
7.76
274807UNIV PK N;3U
Adder
7.743
274811UNIV PK N;7U
Adder
7.693
970707AG2-453 GEN
Solar/Wind Harmer
42.855
274826FISK ;BP
Adder
16.714
274803UNIV PARK;6U
Adder
8.901
274887GEN-1.85
Solar/Wind Harmer
8.124
276772AC2-154 GEN
Solar/Wind Harmer
4.255
276843GEN-1.7
Solar/Wind Harmer
0.874
276806AD2-047 C O1
Solar/Wind Harmer
16.312
972038AH1-567 GEN2
Adder
0.556
972259AH1-714 GEN
Adder
29.077
939351AE1-166 GEN
Solar/Wind Harmer
8.991
274676JOLIET 29;8U
Adder
44.652
274730ELWOOD EC;6P
Adder
24.723
274734ELWOOD EC;8P
Adder
24.723
274736ELWOOD EC;9P
Adder
24.723
274729ELWOOD EC;1P
Adder
24.722
943121AE2-341 GEN
Solar/Wind Harmer
22.397
943591AF1-030 GEN
Solar/Wind Harmer
14.931
274682WAUKEGAN ;7U
Adder
26.369
274862TOP CROP ;2U
Solar/Wind Harmer
7.42
276868AE1-113 GEN
Solar/Wind Harmer
14.537
274879MINONK ;1U
Solar/Wind Harmer
9.692
276799AD1-013 GEN
Solar/Wind Harmer
3.164
946671AF1-331 GEN
Solar/Wind Harmer
0.6
274855GSG-6 ;RU
Solar/Wind Harmer
5.284
274850MENDOTA H;RU
Solar/Wind Harmer
3.673
276602WESTBROOK C
Solar/Wind Harmer
3.042
959091AF2-200 GEN
Solar/Wind Harmer
28.407
970571AG2-364 GEN
Solar/Wind Harmer
27.882
274760LEE CO EC;1U
Adder
12.885
274767LEE CO EC;8U
Adder
12.734
24728505AND G1
Adder
3.46
270102X2-052 ST
50/50
2.629
270100X2-052 CT1
50/50
2.429
270101X2-052 CT2
50/50
2.429
24643105BUCHANAN
50/50
0.021
970349AG2-230 GEN
Solar/Wind Harmer
26.286
961051AF2-396 GEN
Solar/Wind Harmer
25.955
961051AF2-396 GEN
Solar/Wind Harmer
12.072
965681AG1-436 GEN
Solar/Wind Harmer
20.368
965791AG1-447 GEN
Solar/Wind Harmer
10.421
944541AF1-119 GEN
Solar/Wind Harmer
6.65
960971AF2-388 GEN
Solar/Wind Harmer
17.358
274770LINCOLN ;1U
Adder
9.8
274771LINCOLN ;2U
Adder
9.8
274805UNIV PK N;1U
Adder
7.71
274808UNIV PK N;4U
Adder
7.659
274888KELLY CRK;1U
Solar/Wind Harmer
8.998
276776AD2-060 GEN
Solar/Wind Harmer
0.638
958011AF2-095 GEN
Solar/Wind Harmer
21.958
970941AG2-585 GEN
Solar/Wind Harmer
8.387
276897AD1-100 C
Solar/Wind Harmer
70.43
274674JOLIET 9 ;6U
Adder
23.181
276893AG1-478 C
Solar/Wind Harmer
0.659
942221AE2-234 GEN
Solar/Wind Harmer
5.15
274695ROCKY RD ;2P
Adder
16.363
274693ROCKY RD ;1P
Adder
16.202
274697ROCKY RD ;3P
Adder
4.445
274696ROCKY RD ;4P
Adder
16.748
958481AF2-142 GEN
Solar/Wind Harmer
22.019
274683WAUKEGAN ;8U
Adder
30.87
274683WAUKEGAN ;8U
Adder
26.022
962691AG1-118 GEN
Solar/Wind Harmer
43.703
944231AF1-091 GEN
Solar/Wind Harmer
26.155
960751AF2-366 GEN
Solar/Wind Harmer
4.167
958491AF2-143 GEN
Solar/Wind Harmer
21.687
276901AD2-066 C O1
Solar/Wind Harmer
5.054
971341AH1-150 GEN
Solar/Wind Harmer
28.407
971343AH1-151 GEN
Solar/Wind Harmer
28.407
276872AE1-163_GEN1
Solar/Wind Harmer
9.503
276876AE1-163_GEN2
Solar/Wind Harmer
9.503
972235AH1-702 GEN1
Adder
3.556
972236AH1-702 GEN2
Adder
3.092
270535AF1-215 GEN1
Solar/Wind Harmer
6.365
270536AF1-215 GEN2
Solar/Wind Harmer
6.365
274764LEE CO EC;5U
Adder
12.916
274765LEE CO EC;6U
Adder
12.916
274762LEE CO EC;3U
Adder
12.885
274763LEE CO EC;4U
Adder
12.764
247621Y3-024
Adder
0.272
270349AD2-093_GEN
Solar/Wind Helper
1.489
270471AD2-092_GEN
Solar/Wind Helper
1.489
938861AE1-114 GEN
Solar/Wind Harmer
10.898
24729505KEY G4
50/50
11.921
24641605TWIN BRNCH
50/50
0.029
270144AC1-141 ST1_
50/50
3.545
24344005CKG1
50/50
10.701
24653605MOTTVILLE
50/50
0.006
959331AF2-224 GEN
Solar/Wind Harmer
18.046
270071AF1-092 GEN
Solar/Wind Harmer
26.047
970031AG2-029 GEN
Solar/Wind Harmer
42.785
971771AH1-392 GEN
Solar/Wind Harmer
14.954
270526AF1-158 GEN
Solar/Wind Harmer
7.436
960681AF2-359 GEN
Solar/Wind Harmer
6.157
944161AF1-084 GEN
Solar/Wind Harmer
3.574
958711AF2-162 GEN
Solar/Wind Harmer
1.607
274775LINCOLN ;6U
Adder
9.8
274776LINCOLN ;7U
Adder
9.8
274777LINCOLN ;8U
Adder
9.8
274827FISK ;RP
Adder
11.846
972037AH1-567 GEN1
Adder
0.279
960591AF2-350 GEN
Solar/Wind Harmer
15.248
274800UNIV PARK;3U
Adder
8.887
274801UNIV PARK;4U
Adder
8.887
972228AH1-698 GEN2
Adder
5.643
972227AH1-698 GEN1
Adder
3.973
963791AG1-232 GEN
Solar/Wind Harmer
20.548
274687WILL CNTY;4U
Adder
42.241
274687WILL CNTY;4U
Adder
42.241
274675JOLIET 29;7U
Adder
46.307
274675JOLIET 29;7U
Adder
44.653
274728ELWOOD EC;5P
Adder
24.723
274731ELWOOD EC;2P
Adder
24.722
274733ELWOOD EC;3P
Adder
24.722
274735ELWOOD EC;4P
Adder
24.722
276893AG1-478 C
Solar/Wind Harmer
0.827
970833AG2-524 GEN
Solar/Wind Harmer
13.102
970833AG2-524 GEN
Solar/Wind Harmer
6.094
274744AC1-111 GEN8
Adder
8.328
274746AC1-111 G10
Adder
8.328
971549AH1-272 GEN
Solar/Wind Harmer
27.198
945581AF1-223 GEN
Solar/Wind Harmer
6.582
965041AG1-368 GEN
Solar/Wind Harmer
14.485
970073AG2-061 GEN
Solar/Wind Harmer
3.362
971411AH1-196 GEN
Solar/Wind Harmer
21.482
971675AH1-338 GEN
Solar/Wind Harmer
25.768
276861AD2-134 GEN
Solar/Wind Harmer
2.555
276863AD2-134 GEN
Solar/Wind Harmer
2.555
971171AH1-044 GEN
Solar/Wind Harmer
28.407
274863CRW1-WTG
Solar/Wind Harmer
7.901
274864CRW2-WTG
Solar/Wind Harmer
7.901
276889AE2-281 GEN
Solar/Wind Harmer
2.715
274823ROCKFORD ;21
Adder
27.568
274856ECOGROVE ;U1
Solar/Wind Harmer
4.729
276611AD2-172 GEN
Solar/Wind Harmer
3.587
276612AE2-035 GEN
Solar/Wind Harmer
3.587
926823AC1-168 GEN
Solar/Wind Harmer
5.986
971681AH1-341 GEN
Solar/Wind Harmer
20.879
972267AH1-718 GEN
Adder
5.696
24344105CKG2
50/50
13.662
270143AC1-141 CT2_
50/50
4
24639705ELKHART HY
50/50
0.271
970521AG2-332 GEN
50/50
19.317
24307105BERRINSP G
50/50
0.035
965011AG1-365 GEN
Solar/Wind Harmer
18.046
270216AD2-079_GEN
Solar/Wind Harmer
1.012
957891AF2-083 GEN
Solar/Wind Harmer
24.7
945111AF1-176 GEN
Solar/Wind Harmer
29.357
270449AD2-020 GEN
Solar/Wind Harmer
4.565
943021AE2-325 GEN
Solar/Wind Harmer
5.933
24441205WTRV SLR C
Solar/Wind Harmer
0.214
965651AG1-433 GEN
Solar/Wind Harmer
8.679
972207SS24-0001
Solar/Wind Harmer
34.843
274773LINCOLN ;4U
Adder
9.8
274774LINCOLN ;5U
Adder
9.8
274723RIVER EC ;12
Adder
27.774
274751CRETE EC ;1U
Adder
7.558
274754CRETE EC ;4U
Adder
7.558
958861AF2-177 GEN
Solar/Wind Harmer
16.844
274812UNIV PK N;8U
Adder
7.693
274802UNIV PARK;5U
Adder
8.901
941551AE2-152 GEN
Solar/Wind Harmer
6.876
274676JOLIET 29;8U
Adder
46.306
274674JOLIET 9 ;6U
Adder
23.181
274732ELWOOD EC;7P
Adder
24.723
274871GR RIDGE ;2U
Solar/Wind Harmer
11.532
274847GR RIDGE ;BU
Solar/Wind Harmer
7.583
274745AC1-111 GEN9
Adder
8.328
276694AA1-018 GEN2
Solar/Wind Harmer
9.262
276691AA1-018 GEN1
Solar/Wind Harmer
1.107
274682WAUKEGAN ;7U
Adder
26.369
274861TOP CROP ;1U
Solar/Wind Harmer
8.887
274828WAUKEGAN ;BP
Adder
16.181
970373AG2-245 GEN
Solar/Wind Harmer
30.663
962781AG1-127 GEN
Solar/Wind Harmer
13.812
945371AF1-202 GEN
Solar/Wind Harmer
10.125
274872LEEDK;1U
Solar/Wind Harmer
11.89
276805AD2-038 GEN
Solar/Wind Harmer
7.414
939401AE1-172 GEN
Solar/Wind Harmer
20.136
276882AE2-255 GEN
Solar/Wind Harmer
4.846
971997AH1-543 GEN
Solar/Wind Harmer
22.557
957471AF2-041 GEN
Solar/Wind Harmer
42.611
959081AF2-199 GEN
Solar/Wind Harmer
14.204
971067AG2-660 GEN
Solar/Wind Harmer
3.303
274822ROCKFORD ;11
Adder
27.77
970819AG2-516 GEN
Solar/Wind Harmer
16.862
270055AF2-134 C O1
Solar/Wind Harmer
4.243
970569AG2-363 GEN
Solar/Wind Harmer
41.823
274761LEE CO EC;2U
Adder
12.885
274766LEE CO EC;7U
Adder
12.734
24728605AND G2
Adder
3.46
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.271
NYPJM->LTFIMP_NY
CLTF
2.337
LGEELTFEXP_LGEE->PJM
CLTF
2.867
WECLTFEXP_WEC->PJM
CLTF
5.379
CBM West 1LTFEXP_CBM-W1->PJM
CBM
160.996
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.967
MECLTFEXP_MEC->PJM
CLTF
19.101
SIGELTFEXP_SIGE->PJM
CLTF
0.332
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.687
AG2-052LTFEXP_AG2-052->PJM
LTF
0.33
AH1-155LTFEXP_AH1-155->PJM
LTF
0.495
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.977
LAGNLTFEXP_LAGN->PJM
CLTF
9.779
TVALTFEXP_TVA->PJM
CLTF
3.619

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#9287_1679_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#9287_1679_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.12 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4271.28
MW Contribution:
17.87
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
12.668
270144AC1-141 ST1_
50/50
4.102
24641605TWIN BRNCH
50/50
0.033
274775LINCOLN ;6U
50/50
16.742
274776LINCOLN ;7U
50/50
16.742
274777LINCOLN ;8U
50/50
16.742
24653605MOTTVILLE
50/50
0.007
971771AH1-392 GEN
Solar/Wind Harmer
13.283
270102X2-052 ST
50/50
3.04
270100X2-052 CT1
50/50
2.808
270101X2-052 CT2
50/50
2.808
24643105BUCHANAN
50/50
0.024
274770LINCOLN ;1U
50/50
16.742
274771LINCOLN ;2U
50/50
16.742
247620Y3-023
50/50
0.894
970349AG2-230 GEN
Solar/Wind Harmer
21.879
965681AG1-436 GEN
Solar/Wind Harmer
16.375
965791AG1-447 GEN
Solar/Wind Harmer
12.008
961051AF2-396 GEN
Solar/Wind Harmer
26.182
961051AF2-396 GEN
Solar/Wind Harmer
17.455
274805UNIV PK N;1U
Adder
8.895
274808UNIV PK N;4U
Adder
8.837
274888KELLY CRK;1U
Solar/Wind Harmer
0.719
276776AD2-060 GEN
Solar/Wind Harmer
1.315
958011AF2-095 GEN
Solar/Wind Harmer
17.758
970941AG2-585 GEN
Solar/Wind Harmer
6.782
276897AD1-100 C
Solar/Wind Harmer
30.703
274674JOLIET 9 ;6U
Adder
26.849
276893AG1-478 C
Solar/Wind Harmer
0.809
274695ROCKY RD ;2P
Adder
18.919
274693ROCKY RD ;1P
Adder
18.733
274697ROCKY RD ;3P
Adder
5.139
274696ROCKY RD ;4P
Adder
19.364
274683WAUKEGAN ;8U
Adder
35.646
274683WAUKEGAN ;8U
Adder
30.048
958481AF2-142 GEN
Solar/Wind Harmer
17.657
962691AG1-118 GEN
Solar/Wind Harmer
35.208
958491AF2-143 GEN
Solar/Wind Harmer
17.33
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
22.754
971343AH1-151 GEN
Solar/Wind Harmer
22.754
972235AH1-702 GEN1
Adder
4.077
972236AH1-702 GEN2
Adder
3.545
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
6.286
274764LEE CO EC;5U
Adder
14.746
274765LEE CO EC;6U
Adder
14.746
274762LEE CO EC;3U
Adder
14.712
274763LEE CO EC;4U
Adder
14.573
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.741
276645AC1-214 GEN1
Solar/Wind Harmer
0.418
944541AF1-119 GEN
Solar/Wind Harmer
0.704
960971AF2-388 GEN
Solar/Wind Harmer
6.177
944231AF1-091 GEN
Solar/Wind Harmer
23.61
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274827FISK ;RP
Adder
13.721
972228AH1-698 GEN2
Adder
6.549
972227AH1-698 GEN1
Adder
4.611
960591AF2-350 GEN
Solar/Wind Harmer
12.332
972037AH1-567 GEN1
Adder
0.323
274800UNIV PARK;3U
Adder
10.294
274801UNIV PARK;4U
Adder
10.294
274687WILL CNTY;4U
Adder
48.934
274687WILL CNTY;4U
Adder
48.934
274675JOLIET 29;7U
Adder
53.662
274675JOLIET 29;7U
Adder
51.745
274728ELWOOD EC;5P
Adder
28.611
274731ELWOOD EC;2P
Adder
28.61
274733ELWOOD EC;3P
Adder
28.61
274735ELWOOD EC;4P
Adder
28.61
970833AG2-524 GEN
Solar/Wind Harmer
13.35
970833AG2-524 GEN
Solar/Wind Harmer
8.9
274744AC1-111 GEN8
Adder
9.659
274746AC1-111 G10
Adder
9.659
970031AG2-029 GEN
Solar/Wind Harmer
6.498
971549AH1-272 GEN
Solar/Wind Harmer
24.686
24729505KEY G4
Adder
10.795
959331AF2-224 GEN
Solar/Wind Harmer
8.089
970073AG2-061 GEN
Solar/Wind Harmer
3.851
971411AH1-196 GEN
Solar/Wind Harmer
17.237
971675AH1-338 GEN
Solar/Wind Harmer
4.48
276861AD2-134 GEN
Solar/Wind Harmer
0.205
276863AD2-134 GEN
Solar/Wind Harmer
0.205
971171AH1-044 GEN
Solar/Wind Harmer
22.754
274823ROCKFORD ;21
Adder
31.63
274863CRW1-WTG
Solar/Wind Harmer
0
24344105CKG2
50/50
17.101
270143AC1-141 CT2_
50/50
4.628
274773LINCOLN ;4U
50/50
16.742
274774LINCOLN ;5U
50/50
16.742
24307105BERRINSP G
50/50
0.04
24639705ELKHART HY
50/50
0.302
247604X1-042
50/50
0.044
970521AG2-332 GEN
50/50
21.337
957891AF2-083 GEN
Solar/Wind Harmer
21.973
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.836
945111AF1-176 GEN
Solar/Wind Harmer
23.345
274723RIVER EC ;12
Adder
32.119
274751CRETE EC ;1U
Adder
14.651
274754CRETE EC ;4U
Adder
14.651
274812UNIV PK N;8U
Adder
8.876
274802UNIV PARK;5U
Adder
10.298
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.66
274674JOLIET 9 ;6U
Adder
26.849
274732ELWOOD EC;7P
Adder
28.611
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.659
274682WAUKEGAN ;7U
Adder
30.457
274828WAUKEGAN ;BP
Adder
18.685
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.913
274861TOP CROP ;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
11.128
274872LEEDK;1U
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
11.556
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
8.623
276882AE2-255 GEN
Solar/Wind Harmer
1.339
971997AH1-543 GEN
Solar/Wind Harmer
6.007
957471AF2-041 GEN
Solar/Wind Harmer
34.131
959081AF2-199 GEN
Solar/Wind Harmer
11.377
971067AG2-660 GEN
Solar/Wind Harmer
3.792
270142AC1-141 CT1_
50/50
4.628
24642205MAYFLWER
50/50
0.07
944961AF1-161 GEN
50/50
5.457
962601AG1-109 GEN
50/50
5.457
274772LINCOLN ;3U
50/50
16.742
971347AH1-153 GEN
Solar/Wind Harmer
7.293
270505AE1-170 C O1
Solar/Wind Harmer
13.912
945111AF1-176 GEN
Solar/Wind Harmer
10.605
270043AE2-236 GEN
Solar/Wind Harmer
8.283
270063AE2-323 C
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
31.767
970707AG2-453 GEN
Solar/Wind Harmer
40.791
274752CRETE EC ;2U
Adder
14.651
274753CRETE EC ;3U
Adder
14.651
972259AH1-714 GEN
Adder
33.857
274814UNIV PK N;0U
Adder
8.953
274807UNIV PK N;3U
Adder
8.934
274811UNIV PK N;7U
Adder
8.876
274826FISK ;BP
Adder
19.361
274887GEN-1.85
Solar/Wind Harmer
0.321
276843GEN-1.7
Solar/Wind Harmer
0.399
276806AD2-047 C O1
Solar/Wind Harmer
6.988
274803UNIV PARK;6U
Adder
10.298
972038AH1-567 GEN2
Adder
0.644
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
51.744
274729ELWOOD EC;1P
Adder
28.61
274730ELWOOD EC;6P
Adder
28.611
274734ELWOOD EC;8P
Adder
28.611
274736ELWOOD EC;9P
Adder
28.611
943121AE2-341 GEN
Solar/Wind Harmer
20.29
943591AF1-030 GEN
Solar/Wind Harmer
13.493
944531AF1-118 GEN
Solar/Wind Harmer
53.775
274682WAUKEGAN ;7U
Adder
30.457
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.262
971681AH1-341 GEN
Solar/Wind Harmer
17.867
926823AC1-168 GEN
Solar/Wind Harmer
1.875
270071AF1-092 GEN
Solar/Wind Harmer
21.116
970169AG2-114 GEN
Solar/Wind Harmer
10.885
972267AH1-718 GEN
Adder
6.485
276741O09 GEN1
Solar/Wind Harmer
0.381
274877BISHOP HL;1U
Solar/Wind Harmer
0.353
946321AF1-296 GEN
Solar/Wind Harmer
5.822
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.652
963791AG1-232 GEN
Solar/Wind Harmer
13.422
965041AG1-368 GEN
Solar/Wind Harmer
9.865
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.327
965051AG1-369 GEN
Solar/Wind Harmer
4.508
276668AB2-070 GEN1
Solar/Wind Harmer
0.345
276848AB2-070 GEN3
Solar/Wind Harmer
0.343
276849AB2-070 GEN2
Solar/Wind Harmer
0.345
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.357
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.686
964611AG1-324 GEN
Solar/Wind Harmer
2.923
944221AF1-090 GEN
Solar/Wind Harmer
4.332
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.911
270007AE1-245 C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.271
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.694
274862TOP CROP ;2U
Solar/Wind Harmer
1.588
965021AG1-366 GEN
Solar/Wind Harmer
3.852
946671AF1-331 GEN
Solar/Wind Harmer
1.226
274855GSG-6 ;RU
Solar/Wind Harmer
0.419
274850MENDOTA H;RU
Solar/Wind Harmer
0.133
276868AE1-113 GEN
Solar/Wind Harmer
2.296
274879MINONK ;1U
Solar/Wind Harmer
0.479
959091AF2-200 GEN
Solar/Wind Harmer
22.754
970571AG2-364 GEN
Solar/Wind Harmer
22.087
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
14.712
274767LEE CO EC;8U
Adder
14.538
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.353
965931AG1-462 GEN
Solar/Wind Harmer
26.286
971087AG2-675 GEN
Solar/Wind Harmer
5.498
965091AG1-374 GEN
Solar/Wind Harmer
29.5
959611AF2-252 GEN
Solar/Wind Harmer
3.278
964401AG1-302 GEN
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.055
24695305TIMB G C
Solar/Wind Harmer
0.742
957381AF2-032 GEN
Solar/Wind Harmer
1.822
942481AE2-261 GEN
Solar/Wind Harmer
23.884
270004AE1-209 GEN
Solar/Wind Harmer
1.716
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.272
946031AF1-268 GEN
Solar/Wind Harmer
7.057
970825AG2-519 GEN
Solar/Wind Harmer
5.584
246938BC-WTG3
Solar/Wind Harmer
0.259
270491AE1-102 GEN2
Solar/Wind Harmer
0.935
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.599
24386205FR-12G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.679
942111AE2-223 GEN
Solar/Wind Harmer
3.297
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
3.278
942221AE2-234 GEN
Solar/Wind Harmer
3.817
270246TR4_N_V150
Solar/Wind Harmer
0.058
270247TR4_N_V136
Solar/Wind Harmer
0.058
276615X2-022 GEN
Solar/Wind Harmer
0.088
276838X2-022 GEN2
Solar/Wind Harmer
0.479
270031AE2-169
Solar/Wind Harmer
4.571
270599AE1-208 GEN
Solar/Wind Harmer
7.618
276916AD2-100_GEN
Solar/Wind Harmer
16.489
276911AD2-131_GEN
Solar/Wind Harmer
1.086
970623AG2-406 GEN
Solar/Wind Harmer
1.389
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.562
246937BC-WTG2
Solar/Wind Harmer
0.29
247607V1-011 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.098
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.721
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
6.198
970885AG2-551 GEN
Solar/Wind Harmer
2.066
970291AG2-192 GEN
Solar/Wind Harmer
0.802
970291AG2-192 GEN
Solar/Wind Harmer
0.37
970241AG2-163 GEN
Solar/Wind Harmer
3.55
270349AD2-093_GEN
Solar/Wind Helper
1.46
270471AD2-092_GEN
Solar/Wind Helper
1.46
274822ROCKFORD ;11
Adder
31.861
970819AG2-516 GEN
Solar/Wind Harmer
13.478
970569AG2-363 GEN
Solar/Wind Harmer
33.131
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
14.712
274766LEE CO EC;7U
Adder
14.538
276708O09 GEN2
Solar/Wind Harmer
0.381
970373AG2-245 GEN
Solar/Wind Harmer
22.393
276646AC1-214 GEN2
Solar/Wind Harmer
0.418
965651AG1-433 GEN
Solar/Wind Harmer
3.089
274848CAMPGROVE;RU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.409
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
14.202
270055AF2-134 C O1
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.626
276621W2-048 GEN
Solar/Wind Harmer
0.426
270024AE2-089 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.598
270005AE1-210 C O1
Solar/Wind Harmer
1.716
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
9.838
965421AG1-410 GEN
Solar/Wind Harmer
22.84
970825AG2-519 GEN
Solar/Wind Harmer
2.631
246936BC-WTG1
Solar/Wind Harmer
0.29
270489AE1-102 GEN1
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.078
270594AE1-207 GEN
Solar/Wind Harmer
7.228
270032AE2-172
Solar/Wind Harmer
4.303
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
6.868
963741AG1-226 GEN
Solar/Wind Harmer
14.404
270543AE2-219 C
Solar/Wind Harmer
4.339
970289AG2-191 GEN
Solar/Wind Harmer
1.173
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.54
NYPJM->LTFIMP_NY
CLTF
2.551
LGEELTFEXP_LGEE->PJM
CLTF
1.869
WECLTFEXP_WEC->PJM
CLTF
6.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
184.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.09
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.536
MECLTFEXP_MEC->PJM
CLTF
20.956
SIGELTFEXP_SIGE->PJM
CLTF
0.265
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.118
AG2-052LTFEXP_AG2-052->PJM
LTF
0.357
AH1-155LTFEXP_AH1-155->PJM
LTF
0.535
LAGNLTFEXP_LAGN->PJM
CLTF
9.08
TVALTFEXP_TVA->PJM
CLTF
3.004

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11087___SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11087___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.11 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4270.92
MW Contribution:
20.05
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.843
24729305KEY G2
50/50
0.829
24729205KEY G1
50/50
0.824
247620Y3-023
50/50
0.804
270102X2-052 ST
50/50
2.593
270100X2-052 CT1
50/50
2.396
270101X2-052 CT2
50/50
2.396
24643105BUCHANAN
50/50
0.021
944541AF1-119 GEN
Solar/Wind Harmer
9.386
960971AF2-388 GEN
Solar/Wind Harmer
24.501
970349AG2-230 GEN
Solar/Wind Harmer
26.041
961051AF2-396 GEN
Solar/Wind Harmer
25.785
961051AF2-396 GEN
Solar/Wind Harmer
11.993
965681AG1-436 GEN
Solar/Wind Harmer
20.057
965791AG1-447 GEN
Solar/Wind Harmer
10.262
274770LINCOLN ;1U
Adder
9.548
274771LINCOLN ;2U
Adder
9.548
274805UNIV PK N;1U
Adder
7.501
274808UNIV PK N;4U
Adder
7.452
274888KELLY CRK;1U
Solar/Wind Harmer
8.737
276776AD2-060 GEN
Solar/Wind Harmer
0.62
958011AF2-095 GEN
Solar/Wind Harmer
21.32
970941AG2-585 GEN
Solar/Wind Harmer
8.143
276897AD1-100 C
Solar/Wind Harmer
68.272
274674JOLIET 9 ;6U
Adder
22.471
944231AF1-091 GEN
Solar/Wind Harmer
26.227
276893AG1-478 C
Solar/Wind Harmer
0.639
274696ROCKY RD ;4P
Adder
16.191
274695ROCKY RD ;2P
Adder
15.818
274693ROCKY RD ;1P
Adder
15.663
274697ROCKY RD ;3P
Adder
4.297
958481AF2-142 GEN
Solar/Wind Harmer
21.274
274683WAUKEGAN ;8U
Adder
29.837
274683WAUKEGAN ;8U
Adder
25.151
962691AG1-118 GEN
Solar/Wind Harmer
42.204
960751AF2-366 GEN
Solar/Wind Harmer
4.023
958491AF2-143 GEN
Solar/Wind Harmer
20.909
276901AD2-066 C O1
Solar/Wind Harmer
4.868
971341AH1-150 GEN
Solar/Wind Harmer
27.351
971343AH1-151 GEN
Solar/Wind Harmer
27.351
276872AE1-163_GEN1
Solar/Wind Harmer
9.134
276876AE1-163_GEN2
Solar/Wind Harmer
9.134
270535AF1-215 GEN1
Solar/Wind Harmer
6.165
270536AF1-215 GEN2
Solar/Wind Harmer
6.165
972235AH1-702 GEN1
Adder
3.422
972236AH1-702 GEN2
Adder
2.975
938861AE1-114 GEN
Solar/Wind Harmer
10.955
274764LEE CO EC;5U
Adder
12.398
274765LEE CO EC;6U
Adder
12.398
274762LEE CO EC;3U
Adder
12.369
274763LEE CO EC;4U
Adder
12.252
270349AD2-093_GEN
Solar/Wind Helper
1.352
270471AD2-092_GEN
Solar/Wind Helper
1.352
24344105CKG2
50/50
13.551
270143AC1-141 CT2_
50/50
3.972
24639705ELKHART HY
50/50
0.268
970521AG2-332 GEN
50/50
19.098
24307105BERRINSP G
50/50
0.034
247604X1-042
50/50
0.038
965651AG1-433 GEN
Solar/Wind Harmer
12.251
958861AF2-177 GEN
Solar/Wind Harmer
24.497
945371AF1-202 GEN
Solar/Wind Harmer
15.631
965011AG1-365 GEN
Solar/Wind Harmer
16.808
270216AD2-079_GEN
Solar/Wind Harmer
1.003
957891AF2-083 GEN
Solar/Wind Harmer
24.519
945111AF1-176 GEN
Solar/Wind Harmer
29.132
270449AD2-020 GEN
Solar/Wind Harmer
4.538
943021AE2-325 GEN
Solar/Wind Harmer
5.899
24441205WTRV SLR C
Solar/Wind Harmer
0.214
972207SS24-0001
Solar/Wind Harmer
33.946
274773LINCOLN ;4U
Adder
9.548
274774LINCOLN ;5U
Adder
9.548
274723RIVER EC ;12
Adder
27.053
274751CRETE EC ;1U
Adder
7.364
274754CRETE EC ;4U
Adder
7.364
274812UNIV PK N;8U
Adder
7.484
274802UNIV PARK;5U
Adder
8.648
941551AE2-152 GEN
Solar/Wind Harmer
6.666
274676JOLIET 29;8U
Adder
44.91
274674JOLIET 9 ;6U
Adder
22.471
274732ELWOOD EC;7P
Adder
23.961
274871GR RIDGE ;2U
Solar/Wind Harmer
11.169
274847GR RIDGE ;BU
Solar/Wind Harmer
7.344
274745AC1-111 GEN9
Adder
8.063
970373AG2-245 GEN
Solar/Wind Harmer
29.843
274682WAUKEGAN ;7U
Adder
25.491
276694AA1-018 GEN2
Solar/Wind Harmer
8.949
276691AA1-018 GEN1
Solar/Wind Harmer
1.07
274861TOP CROP ;1U
Solar/Wind Harmer
8.586
274828WAUKEGAN ;BP
Adder
15.64
962781AG1-127 GEN
Solar/Wind Harmer
13.334
274872LEEDK;1U
Solar/Wind Harmer
11.474
276805AD2-038 GEN
Solar/Wind Harmer
7.148
939401AE1-172 GEN
Solar/Wind Harmer
19.364
276882AE2-255 GEN
Solar/Wind Harmer
4.668
971997AH1-543 GEN
Solar/Wind Harmer
21.709
957471AF2-041 GEN
Solar/Wind Harmer
41.026
959081AF2-199 GEN
Solar/Wind Harmer
13.675
971067AG2-660 GEN
Solar/Wind Harmer
3.18
274822ROCKFORD ;11
Adder
26.729
270055AF2-134 C O1
Solar/Wind Harmer
4.11
970819AG2-516 GEN
Solar/Wind Harmer
16.217
970569AG2-363 GEN
Solar/Wind Harmer
40.109
274858EASY ROAD;U2
Solar/Wind Harmer
6.369
274761LEE CO EC;2U
Adder
12.369
274766LEE CO EC;7U
Adder
12.223
24729505KEY G4
50/50
15.44
270144AC1-141 ST1_
50/50
3.52
24641605TWIN BRNCH
50/50
0.029
24344005CKG1
50/50
10.642
24653605MOTTVILLE
50/50
0.006
958711AF2-162 GEN
Solar/Wind Harmer
2.268
945581AF1-223 GEN
Solar/Wind Harmer
10.161
270071AF1-092 GEN
Solar/Wind Harmer
25.377
959331AF2-224 GEN
Solar/Wind Harmer
16.808
970031AG2-029 GEN
Solar/Wind Harmer
41.911
971771AH1-392 GEN
Solar/Wind Harmer
14.805
270526AF1-158 GEN
Solar/Wind Harmer
7.346
944161AF1-084 GEN
Solar/Wind Harmer
3.556
960681AF2-359 GEN
Solar/Wind Harmer
6.063
274775LINCOLN ;6U
Adder
9.548
274776LINCOLN ;7U
Adder
9.548
274777LINCOLN ;8U
Adder
9.548
971549AH1-272 GEN
Solar/Wind Harmer
27.449
274827FISK ;RP
Adder
11.509
972037AH1-567 GEN1
Adder
0.271
274800UNIV PARK;3U
Adder
8.632
274801UNIV PARK;4U
Adder
8.632
960591AF2-350 GEN
Solar/Wind Harmer
14.805
972228AH1-698 GEN2
Adder
5.477
972227AH1-698 GEN1
Adder
3.857
274687WILL CNTY;4U
Adder
40.979
274687WILL CNTY;4U
Adder
40.979
274675JOLIET 29;7U
Adder
44.911
274675JOLIET 29;7U
Adder
43.307
274728ELWOOD EC;5P
Adder
23.961
274731ELWOOD EC;2P
Adder
23.96
274733ELWOOD EC;3P
Adder
23.96
274735ELWOOD EC;4P
Adder
23.96
276893AG1-478 C
Solar/Wind Harmer
0.801
970833AG2-524 GEN
Solar/Wind Harmer
12.689
970833AG2-524 GEN
Solar/Wind Harmer
5.902
274744AC1-111 GEN8
Adder
8.063
274746AC1-111 G10
Adder
8.063
965041AG1-368 GEN
Solar/Wind Harmer
14.212
970073AG2-061 GEN
Solar/Wind Harmer
3.242
971411AH1-196 GEN
Solar/Wind Harmer
20.707
971675AH1-338 GEN
Solar/Wind Harmer
24.832
276861AD2-134 GEN
Solar/Wind Harmer
2.462
276863AD2-134 GEN
Solar/Wind Harmer
2.462
971171AH1-044 GEN
Solar/Wind Harmer
27.351
274823ROCKFORD ;21
Adder
26.536
276889AE2-281 GEN
Solar/Wind Harmer
2.61
274863CRW1-WTG
Solar/Wind Harmer
7.572
274864CRW2-WTG
Solar/Wind Harmer
7.572
274856ECOGROVE ;U1
Solar/Wind Harmer
4.546
276611AD2-172 GEN
Solar/Wind Harmer
3.449
276612AE2-035 GEN
Solar/Wind Harmer
3.449
971681AH1-341 GEN
Solar/Wind Harmer
20.052
926823AC1-168 GEN
Solar/Wind Harmer
5.737
972267AH1-718 GEN
Adder
5.459
970169AG2-114 GEN
Solar/Wind Harmer
7.94
270142AC1-141 CT1_
50/50
3.972
24642205MAYFLWER
50/50
0.06
944961AF1-161 GEN
50/50
4.708
962601AG1-109 GEN
50/50
4.708
944531AF1-118 GEN
Solar/Wind Harmer
78.519
270043AE2-236 GEN
Solar/Wind Harmer
10.234
971347AH1-153 GEN
Solar/Wind Harmer
8.68
965021AG1-366 GEN
Solar/Wind Harmer
3.909
270063AE2-323 C
Solar/Wind Harmer
3.683
247643Z2-116 C
Solar/Wind Harmer
0.115
270505AE1-170 C O1
Solar/Wind Harmer
24.563
945111AF1-176 GEN
Solar/Wind Harmer
9.233
24441505OLIV SLR
Solar/Wind Harmer
0.216
274772LINCOLN ;3U
Adder
9.548
274724RIVER EC ;11
Adder
26.744
972231SS25-0005
Solar/Wind Harmer
14.298
972181SS23-001
Solar/Wind Harmer
8.936
274752CRETE EC ;2U
Adder
7.364
274753CRETE EC ;3U
Adder
7.364
276164X3-005 C
Solar/Wind Harmer
1.055
274814UNIV PK N;0U
Adder
7.55
274807UNIV PK N;3U
Adder
7.533
274811UNIV PK N;7U
Adder
7.484
970707AG2-453 GEN
Solar/Wind Harmer
41.611
274826FISK ;BP
Adder
16.239
274803UNIV PARK;6U
Adder
8.648
972038AH1-567 GEN2
Adder
0.54
274887GEN-1.85
Solar/Wind Harmer
7.888
276772AC2-154 GEN
Solar/Wind Harmer
4.132
276843GEN-1.7
Solar/Wind Harmer
0.849
276806AD2-047 C O1
Solar/Wind Harmer
15.838
972259AH1-714 GEN
Adder
28.221
939351AE1-166 GEN
Solar/Wind Harmer
8.716
274676JOLIET 29;8U
Adder
43.306
274730ELWOOD EC;6P
Adder
23.961
274734ELWOOD EC;8P
Adder
23.961
274736ELWOOD EC;9P
Adder
23.961
274729ELWOOD EC;1P
Adder
23.96
943121AE2-341 GEN
Solar/Wind Harmer
21.689
943591AF1-030 GEN
Solar/Wind Harmer
14.459
274682WAUKEGAN ;7U
Adder
25.491
274862TOP CROP ;2U
Solar/Wind Harmer
7.169
276868AE1-113 GEN
Solar/Wind Harmer
14.002
274879MINONK ;1U
Solar/Wind Harmer
9.335
276799AD1-013 GEN
Solar/Wind Harmer
3.05
946671AF1-331 GEN
Solar/Wind Harmer
0.578
274855GSG-6 ;RU
Solar/Wind Harmer
5.091
274850MENDOTA H;RU
Solar/Wind Harmer
3.54
276602WESTBROOK C
Solar/Wind Harmer
2.931
959091AF2-200 GEN
Solar/Wind Harmer
27.351
970571AG2-364 GEN
Solar/Wind Harmer
26.739
274857EASY ROAD;U1
Solar/Wind Harmer
6.369
274760LEE CO EC;1U
Adder
12.369
274767LEE CO EC;8U
Adder
12.223
276603SUBLETTE C
Solar/Wind Harmer
1.391
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.417
NYPJM->LTFIMP_NY
CLTF
2.22
LGEELTFEXP_LGEE->PJM
CLTF
1.872
WECLTFEXP_WEC->PJM
CLTF
5.176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.531
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.443
MECLTFEXP_MEC->PJM
CLTF
17.903
SIGELTFEXP_SIGE->PJM
CLTF
0.245
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.893
AG2-052LTFEXP_AG2-052->PJM
LTF
0.316
AH1-155LTFEXP_AH1-155->PJM
LTF
0.474
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.447
LAGNLTFEXP_LAGN->PJM
CLTF
8.172
TVALTFEXP_TVA->PJM
CLTF
2.793

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.58 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4166.12
MW Contribution:
19.43
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.51 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5405.77
MW Contribution:
22.61
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.579
24729305KEY G2
50/50
0.569
24729205KEY G1
50/50
0.566
270102X2-052 ST
50/50
2.448
270100X2-052 CT1
50/50
2.261
270101X2-052 CT2
50/50
2.261
24643105BUCHANAN
50/50
0.019
247620Y3-023
50/50
0.742
970349AG2-230 GEN
Solar/Wind Harmer
24.512
965681AG1-436 GEN
Solar/Wind Harmer
18.953
965791AG1-447 GEN
Solar/Wind Harmer
9.697
961051AF2-396 GEN
Solar/Wind Harmer
24.029
961051AF2-396 GEN
Solar/Wind Harmer
11.176
274770LINCOLN ;1U
Adder
9.151
274771LINCOLN ;2U
Adder
9.151
274805UNIV PK N;1U
Adder
7.175
274808UNIV PK N;4U
Adder
7.128
274888KELLY CRK;1U
Solar/Wind Harmer
8.381
276776AD2-060 GEN
Solar/Wind Harmer
0.595
958011AF2-095 GEN
Solar/Wind Harmer
20.452
970941AG2-585 GEN
Solar/Wind Harmer
7.812
944541AF1-119 GEN
Solar/Wind Harmer
5.917
960971AF2-388 GEN
Solar/Wind Harmer
15.445
276897AD1-100 C
Solar/Wind Harmer
65.634
274674JOLIET 9 ;6U
Adder
21.593
276893AG1-478 C
Solar/Wind Harmer
0.614
274695ROCKY RD ;2P
Adder
15.241
274693ROCKY RD ;1P
Adder
15.091
274697ROCKY RD ;3P
Adder
4.14
274696ROCKY RD ;4P
Adder
15.6
958481AF2-142 GEN
Solar/Wind Harmer
20.495
274683WAUKEGAN ;8U
Adder
28.748
274683WAUKEGAN ;8U
Adder
24.233
962691AG1-118 GEN
Solar/Wind Harmer
40.703
960751AF2-366 GEN
Solar/Wind Harmer
3.881
958491AF2-143 GEN
Solar/Wind Harmer
20.181
276901AD2-066 C O1
Solar/Wind Harmer
4.703
971341AH1-150 GEN
Solar/Wind Harmer
26.442
971343AH1-151 GEN
Solar/Wind Harmer
26.442
276872AE1-163_GEN1
Solar/Wind Harmer
8.84
276876AE1-163_GEN2
Solar/Wind Harmer
8.84
972235AH1-702 GEN1
Adder
3.31
972236AH1-702 GEN2
Adder
2.878
270535AF1-215 GEN1
Solar/Wind Harmer
5.891
270536AF1-215 GEN2
Solar/Wind Harmer
5.891
944231AF1-091 GEN
Solar/Wind Harmer
23.318
938861AE1-114 GEN
Solar/Wind Harmer
10.612
942221AE2-234 GEN
Solar/Wind Harmer
4.526
274764LEE CO EC;5U
Adder
12.016
274765LEE CO EC;6U
Adder
12.016
24344105CKG2
50/50
12.842
270143AC1-141 CT2_
50/50
3.706
24639705ELKHART HY
50/50
0.248
970521AG2-332 GEN
50/50
17.662
24307105BERRINSP G
50/50
0.032
270216AD2-079_GEN
Solar/Wind Harmer
0.932
957891AF2-083 GEN
Solar/Wind Harmer
22.862
945111AF1-176 GEN
Solar/Wind Harmer
27.114
270449AD2-020 GEN
Solar/Wind Harmer
4.232
943021AE2-325 GEN
Solar/Wind Harmer
5.501
24441205WTRV SLR C
Solar/Wind Harmer
0.199
965011AG1-365 GEN
Solar/Wind Harmer
14.791
972207SS24-0001
Solar/Wind Harmer
32.535
274773LINCOLN ;4U
Adder
9.151
274774LINCOLN ;5U
Adder
9.151
274723RIVER EC ;12
Adder
25.85
274751CRETE EC ;1U
Adder
7.03
274754CRETE EC ;4U
Adder
7.03
274812UNIV PK N;8U
Adder
7.16
274802UNIV PARK;5U
Adder
8.288
965651AG1-433 GEN
Solar/Wind Harmer
7.723
941551AE2-152 GEN
Solar/Wind Harmer
6.408
274676JOLIET 29;8U
Adder
43.134
274674JOLIET 9 ;6U
Adder
21.593
274732ELWOOD EC;7P
Adder
23.027
274871GR RIDGE ;2U
Solar/Wind Harmer
10.745
274847GR RIDGE ;BU
Solar/Wind Harmer
7.065
274745AC1-111 GEN9
Adder
7.76
958861AF2-177 GEN
Solar/Wind Harmer
14.991
274682WAUKEGAN ;7U
Adder
24.557
276694AA1-018 GEN2
Solar/Wind Harmer
8.621
276691AA1-018 GEN1
Solar/Wind Harmer
1.03
274861TOP CROP ;1U
Solar/Wind Harmer
8.272
274828WAUKEGAN ;BP
Adder
15.069
970373AG2-245 GEN
Solar/Wind Harmer
28.422
962781AG1-127 GEN
Solar/Wind Harmer
12.863
274872LEEDK;1U
Solar/Wind Harmer
11.072
276805AD2-038 GEN
Solar/Wind Harmer
6.899
939401AE1-172 GEN
Solar/Wind Harmer
18.745
276882AE2-255 GEN
Solar/Wind Harmer
4.509
971997AH1-543 GEN
Solar/Wind Harmer
20.995
957471AF2-041 GEN
Solar/Wind Harmer
39.664
959081AF2-199 GEN
Solar/Wind Harmer
13.221
274762LEE CO EC;3U
Adder
11.987
274763LEE CO EC;4U
Adder
11.875
247621Y3-024
Adder
0.24
270349AD2-093_GEN
Solar/Wind Helper
1.399
270471AD2-092_GEN
Solar/Wind Helper
1.399
971067AG2-660 GEN
Solar/Wind Harmer
3.075
274822ROCKFORD ;11
Adder
25.846
970819AG2-516 GEN
Solar/Wind Harmer
15.692
270055AF2-134 C O1
Solar/Wind Harmer
3.927
970569AG2-363 GEN
Solar/Wind Harmer
38.894
945371AF1-202 GEN
Solar/Wind Harmer
9.015
274858EASY ROAD;U2
Solar/Wind Harmer
6.173
274761LEE CO EC;2U
Adder
11.987
274766LEE CO EC;7U
Adder
11.846
270142AC1-141 CT1_
50/50
3.706
24642205MAYFLWER
50/50
0.056
944961AF1-161 GEN
50/50
4.391
962601AG1-109 GEN
50/50
4.391
270043AE2-236 GEN
Solar/Wind Harmer
9.148
971347AH1-153 GEN
Solar/Wind Harmer
8.171
944531AF1-118 GEN
Solar/Wind Harmer
55.502
247643Z2-116 C
Solar/Wind Harmer
0.107
270063AE2-323 C
Solar/Wind Harmer
3.364
270505AE1-170 C O1
Solar/Wind Harmer
22.912
945111AF1-176 GEN
Solar/Wind Harmer
8.593
24441505OLIV SLR
Solar/Wind Harmer
0.203
965021AG1-366 GEN
Solar/Wind Harmer
3.44
274772LINCOLN ;3U
Adder
9.151
274724RIVER EC ;11
Adder
25.556
972231SS25-0005
Solar/Wind Harmer
13.649
972181SS23-001
Solar/Wind Harmer
8.531
274752CRETE EC ;2U
Adder
7.03
274753CRETE EC ;3U
Adder
7.03
276164X3-005 C
Solar/Wind Harmer
1.009
274814UNIV PK N;0U
Adder
7.222
274807UNIV PK N;3U
Adder
7.207
274811UNIV PK N;7U
Adder
7.16
970707AG2-453 GEN
Solar/Wind Harmer
39.966
274826FISK ;BP
Adder
15.565
274803UNIV PARK;6U
Adder
8.288
972259AH1-714 GEN
Adder
27.103
274887GEN-1.85
Solar/Wind Harmer
7.567
276772AC2-154 GEN
Solar/Wind Harmer
3.964
276843GEN-1.7
Solar/Wind Harmer
0.814
276806AD2-047 C O1
Solar/Wind Harmer
15.194
972038AH1-567 GEN2
Adder
0.518
939351AE1-166 GEN
Solar/Wind Harmer
8.379
274676JOLIET 29;8U
Adder
41.593
274729ELWOOD EC;1P
Adder
23.027
274730ELWOOD EC;6P
Adder
23.027
274734ELWOOD EC;8P
Adder
23.027
274736ELWOOD EC;9P
Adder
23.027
943121AE2-341 GEN
Solar/Wind Harmer
20.872
943591AF1-030 GEN
Solar/Wind Harmer
13.915
274682WAUKEGAN ;7U
Adder
24.557
274862TOP CROP ;2U
Solar/Wind Harmer
6.907
276868AE1-113 GEN
Solar/Wind Harmer
13.528
274879MINONK ;1U
Solar/Wind Harmer
9.019
276799AD1-013 GEN
Solar/Wind Harmer
2.946
946671AF1-331 GEN
Solar/Wind Harmer
0.558
274855GSG-6 ;RU
Solar/Wind Harmer
4.919
274850MENDOTA H;RU
Solar/Wind Harmer
3.42
276602WESTBROOK C
Solar/Wind Harmer
2.832
959091AF2-200 GEN
Solar/Wind Harmer
26.442
970571AG2-364 GEN
Solar/Wind Harmer
25.929
274857EASY ROAD;U1
Solar/Wind Harmer
6.173
274760LEE CO EC;1U
Adder
11.987
274767LEE CO EC;8U
Adder
11.846
270144AC1-141 ST1_
50/50
3.285
24344005CKG1
50/50
9.982
24641605TWIN BRNCH
50/50
0.027
24729505KEY G4
50/50
10.601
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
23.135
971771AH1-392 GEN
Solar/Wind Harmer
13.843
270526AF1-158 GEN
Solar/Wind Harmer
6.901
960681AF2-359 GEN
Solar/Wind Harmer
5.729
970031AG2-029 GEN
Solar/Wind Harmer
37.809
944161AF1-084 GEN
Solar/Wind Harmer
3.317
959331AF2-224 GEN
Solar/Wind Harmer
14.791
274775LINCOLN ;6U
Adder
9.151
274776LINCOLN ;7U
Adder
9.151
274777LINCOLN ;8U
Adder
9.151
274827FISK ;RP
Adder
11.031
972037AH1-567 GEN1
Adder
0.26
960591AF2-350 GEN
Solar/Wind Harmer
14.203
274800UNIV PARK;3U
Adder
8.277
274801UNIV PARK;4U
Adder
8.277
972228AH1-698 GEN2
Adder
5.257
972227AH1-698 GEN1
Adder
3.702
958711AF2-162 GEN
Solar/Wind Harmer
1.429
274687WILL CNTY;4U
Adder
39.344
274687WILL CNTY;4U
Adder
39.344
274675JOLIET 29;7U
Adder
43.134
274675JOLIET 29;7U
Adder
41.594
274728ELWOOD EC;5P
Adder
23.027
274731ELWOOD EC;2P
Adder
23.027
274733ELWOOD EC;3P
Adder
23.027
274735ELWOOD EC;4P
Adder
23.027
276893AG1-478 C
Solar/Wind Harmer
0.77
970833AG2-524 GEN
Solar/Wind Harmer
12.207
970833AG2-524 GEN
Solar/Wind Harmer
5.678
274744AC1-111 GEN8
Adder
7.76
274746AC1-111 G10
Adder
7.76
971549AH1-272 GEN
Solar/Wind Harmer
25.468
970073AG2-061 GEN
Solar/Wind Harmer
3.129
971411AH1-196 GEN
Solar/Wind Harmer
19.999
971675AH1-338 GEN
Solar/Wind Harmer
23.99
276861AD2-134 GEN
Solar/Wind Harmer
2.379
276863AD2-134 GEN
Solar/Wind Harmer
2.379
971171AH1-044 GEN
Solar/Wind Harmer
26.442
274863CRW1-WTG
Solar/Wind Harmer
7.351
274864CRW2-WTG
Solar/Wind Harmer
7.351
274823ROCKFORD ;21
Adder
25.659
276889AE2-281 GEN
Solar/Wind Harmer
2.526
963791AG1-232 GEN
Solar/Wind Harmer
17.669
274856ECOGROVE ;U1
Solar/Wind Harmer
4.4
276611AD2-172 GEN
Solar/Wind Harmer
3.338
276612AE2-035 GEN
Solar/Wind Harmer
3.338
926823AC1-168 GEN
Solar/Wind Harmer
5.568
971681AH1-341 GEN
Solar/Wind Harmer
19.426
945581AF1-223 GEN
Solar/Wind Harmer
5.86
972267AH1-718 GEN
Adder
5.298
970169AG2-114 GEN
Solar/Wind Harmer
0.069
NYPJM->LTFIMP_NY
CLTF
2.224
LGEELTFEXP_LGEE->PJM
CLTF
2.572
WECLTFEXP_WEC->PJM
CLTF
5.005
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.748
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.319
CBM West 1LTFEXP_CBM-W1->PJM
CBM
152.254
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.129
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.46
MECLTFEXP_MEC->PJM
CLTF
17.697
SIGELTFEXP_SIGE->PJM
CLTF
0.3
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.458
LAGNLTFEXP_LAGN->PJM
CLTF
8.841
TVALTFEXP_TVA->PJM
CLTF
3.224

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.54 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4164.42
MW Contribution:
19.68
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.92 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5422.72
MW Contribution:
23.04
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.593
24729305KEY G2
50/50
0.582
24729205KEY G1
50/50
0.579
247620Y3-023
50/50
0.762
270102X2-052 ST
50/50
2.487
270100X2-052 CT1
50/50
2.298
270101X2-052 CT2
50/50
2.298
24643105BUCHANAN
50/50
0.02
970349AG2-230 GEN
Solar/Wind Harmer
24.878
961051AF2-396 GEN
Solar/Wind Harmer
24.588
961051AF2-396 GEN
Solar/Wind Harmer
11.436
965681AG1-436 GEN
Solar/Wind Harmer
19.26
965791AG1-447 GEN
Solar/Wind Harmer
9.854
274770LINCOLN ;1U
Adder
9.268
274771LINCOLN ;2U
Adder
9.268
274805UNIV PK N;1U
Adder
7.278
274808UNIV PK N;4U
Adder
7.231
944541AF1-119 GEN
Solar/Wind Harmer
6.059
960971AF2-388 GEN
Solar/Wind Harmer
15.817
274888KELLY CRK;1U
Solar/Wind Harmer
8.497
958011AF2-095 GEN
Solar/Wind Harmer
20.735
970941AG2-585 GEN
Solar/Wind Harmer
7.919
276776AD2-060 GEN
Solar/Wind Harmer
0.603
276897AD1-100 C
Solar/Wind Harmer
66.515
274674JOLIET 9 ;6U
Adder
21.887
276893AG1-478 C
Solar/Wind Harmer
0.622
274695ROCKY RD ;2P
Adder
15.445
274693ROCKY RD ;1P
Adder
15.293
274697ROCKY RD ;3P
Adder
4.196
274696ROCKY RD ;4P
Adder
15.809
958481AF2-142 GEN
Solar/Wind Harmer
20.777
274683WAUKEGAN ;8U
Adder
29.135
274683WAUKEGAN ;8U
Adder
24.56
944231AF1-091 GEN
Solar/Wind Harmer
24.809
962691AG1-118 GEN
Solar/Wind Harmer
41.245
960751AF2-366 GEN
Solar/Wind Harmer
3.932
958491AF2-143 GEN
Solar/Wind Harmer
20.457
276901AD2-066 C O1
Solar/Wind Harmer
4.767
971341AH1-150 GEN
Solar/Wind Harmer
26.795
971343AH1-151 GEN
Solar/Wind Harmer
26.795
942221AE2-234 GEN
Solar/Wind Harmer
4.687
276872AE1-163_GEN1
Solar/Wind Harmer
8.96
276876AE1-163_GEN2
Solar/Wind Harmer
8.96
24344105CKG2
50/50
12.998
270143AC1-141 CT2_
50/50
3.786
24639705ELKHART HY
50/50
0.255
970521AG2-332 GEN
50/50
18.115
24307105BERRINSP G
50/50
0.033
247604X1-042
50/50
0.036
270216AD2-079_GEN
Solar/Wind Harmer
0.953
965011AG1-365 GEN
Solar/Wind Harmer
15.718
957891AF2-083 GEN
Solar/Wind Harmer
23.376
945111AF1-176 GEN
Solar/Wind Harmer
27.748
270449AD2-020 GEN
Solar/Wind Harmer
4.33
943021AE2-325 GEN
Solar/Wind Harmer
5.628
24441205WTRV SLR C
Solar/Wind Harmer
0.204
972207SS24-0001
Solar/Wind Harmer
32.952
274773LINCOLN ;4U
Adder
9.268
274774LINCOLN ;5U
Adder
9.268
274723RIVER EC ;12
Adder
26.223
274751CRETE EC ;1U
Adder
7.134
274754CRETE EC ;4U
Adder
7.134
274812UNIV PK N;8U
Adder
7.263
965651AG1-433 GEN
Solar/Wind Harmer
7.909
274802UNIV PARK;5U
Adder
8.404
941551AE2-152 GEN
Solar/Wind Harmer
6.494
274676JOLIET 29;8U
Adder
43.723
274674JOLIET 9 ;6U
Adder
21.887
274732ELWOOD EC;7P
Adder
23.342
274871GR RIDGE ;2U
Solar/Wind Harmer
10.889
274847GR RIDGE ;BU
Solar/Wind Harmer
7.16
274745AC1-111 GEN9
Adder
7.864
958861AF2-177 GEN
Solar/Wind Harmer
15.354
276694AA1-018 GEN2
Solar/Wind Harmer
8.74
276691AA1-018 GEN1
Solar/Wind Harmer
1.045
274682WAUKEGAN ;7U
Adder
24.888
274861TOP CROP ;1U
Solar/Wind Harmer
8.385
274828WAUKEGAN ;BP
Adder
15.272
970373AG2-245 GEN
Solar/Wind Harmer
28.867
962781AG1-127 GEN
Solar/Wind Harmer
13.035
274872LEEDK;1U
Solar/Wind Harmer
11.22
276805AD2-038 GEN
Solar/Wind Harmer
6.993
939401AE1-172 GEN
Solar/Wind Harmer
18.996
276882AE2-255 GEN
Solar/Wind Harmer
4.571
971997AH1-543 GEN
Solar/Wind Harmer
21.278
957471AF2-041 GEN
Solar/Wind Harmer
40.193
959081AF2-199 GEN
Solar/Wind Harmer
13.398
971067AG2-660 GEN
Solar/Wind Harmer
3.116
274822ROCKFORD ;11
Adder
26.192
970819AG2-516 GEN
Solar/Wind Harmer
15.902
945371AF1-202 GEN
Solar/Wind Harmer
9.236
270055AF2-134 C O1
Solar/Wind Harmer
3.988
970569AG2-363 GEN
Solar/Wind Harmer
39.422
270142AC1-141 CT1_
50/50
3.786
24642205MAYFLWER
50/50
0.057
944961AF1-161 GEN
50/50
4.493
962601AG1-109 GEN
50/50
4.493
270043AE2-236 GEN
Solar/Wind Harmer
9.415
971347AH1-153 GEN
Solar/Wind Harmer
8.293
944531AF1-118 GEN
Solar/Wind Harmer
56.817
270063AE2-323 C
Solar/Wind Harmer
3.473
247643Z2-116 C
Solar/Wind Harmer
0.11
965021AG1-366 GEN
Solar/Wind Harmer
3.655
270505AE1-170 C O1
Solar/Wind Harmer
23.422
945111AF1-176 GEN
Solar/Wind Harmer
8.794
24441505OLIV SLR
Solar/Wind Harmer
0.207
274772LINCOLN ;3U
Adder
9.268
274724RIVER EC ;11
Adder
25.925
972231SS25-0005
Solar/Wind Harmer
13.851
972181SS23-001
Solar/Wind Harmer
8.657
972235AH1-702 GEN1
Adder
3.354
972236AH1-702 GEN2
Adder
2.916
270535AF1-215 GEN1
Solar/Wind Harmer
5.982
270536AF1-215 GEN2
Solar/Wind Harmer
5.982
274764LEE CO EC;5U
Adder
12.176
274765LEE CO EC;6U
Adder
12.176
274762LEE CO EC;3U
Adder
12.147
274763LEE CO EC;4U
Adder
12.033
247621Y3-024
Adder
0.249
270349AD2-093_GEN
Solar/Wind Helper
1.583
270471AD2-092_GEN
Solar/Wind Helper
1.583
938861AE1-114 GEN
Solar/Wind Harmer
10.275
274761LEE CO EC;2U
Adder
12.147
274766LEE CO EC;7U
Adder
12.004
270286AF1-227 GEN2
Solar/Wind Helper
0.904
274752CRETE EC ;2U
Adder
7.134
274753CRETE EC ;3U
Adder
7.134
276164X3-005 C
Solar/Wind Harmer
1.023
274814UNIV PK N;0U
Adder
7.326
274807UNIV PK N;3U
Adder
7.31
274811UNIV PK N;7U
Adder
7.263
970707AG2-453 GEN
Solar/Wind Harmer
40.492
274826FISK ;BP
Adder
15.782
274803UNIV PARK;6U
Adder
8.404
274887GEN-1.85
Solar/Wind Harmer
7.672
276843GEN-1.7
Solar/Wind Harmer
0.825
276772AC2-154 GEN
Solar/Wind Harmer
4.018
276806AD2-047 C O1
Solar/Wind Harmer
15.404
972259AH1-714 GEN
Adder
27.466
972038AH1-567 GEN2
Adder
0.525
939351AE1-166 GEN
Solar/Wind Harmer
8.492
274676JOLIET 29;8U
Adder
42.161
274730ELWOOD EC;6P
Adder
23.342
274734ELWOOD EC;8P
Adder
23.342
274736ELWOOD EC;9P
Adder
23.342
274729ELWOOD EC;1P
Adder
23.341
943121AE2-341 GEN
Solar/Wind Harmer
21.149
943591AF1-030 GEN
Solar/Wind Harmer
14.099
274682WAUKEGAN ;7U
Adder
24.888
274862TOP CROP ;2U
Solar/Wind Harmer
7.001
276868AE1-113 GEN
Solar/Wind Harmer
13.712
274879MINONK ;1U
Solar/Wind Harmer
9.142
276799AD1-013 GEN
Solar/Wind Harmer
2.985
946671AF1-331 GEN
Solar/Wind Harmer
0.566
274855GSG-6 ;RU
Solar/Wind Harmer
4.985
274850MENDOTA H;RU
Solar/Wind Harmer
3.466
276602WESTBROOK C
Solar/Wind Harmer
2.869
959091AF2-200 GEN
Solar/Wind Harmer
26.795
970571AG2-364 GEN
Solar/Wind Harmer
26.281
274760LEE CO EC;1U
Adder
12.147
274767LEE CO EC;8U
Adder
12.004
270284AF1-227 GEN1
Solar/Wind Helper
2.463
270287AF1-227 GEN3
Solar/Wind Helper
0.904
270144AC1-141 ST1_
50/50
3.355
24344005CKG1
50/50
10.183
24729505KEY G4
50/50
10.853
24641605TWIN BRNCH
50/50
0.027
24653605MOTTVILLE
50/50
0.006
270071AF1-092 GEN
Solar/Wind Harmer
23.728
959331AF2-224 GEN
Solar/Wind Harmer
15.718
971771AH1-392 GEN
Solar/Wind Harmer
14.124
970031AG2-029 GEN
Solar/Wind Harmer
39.158
270526AF1-158 GEN
Solar/Wind Harmer
7.03
960681AF2-359 GEN
Solar/Wind Harmer
5.822
944161AF1-084 GEN
Solar/Wind Harmer
3.395
274775LINCOLN ;6U
Adder
9.268
274776LINCOLN ;7U
Adder
9.268
274777LINCOLN ;8U
Adder
9.268
958711AF2-162 GEN
Solar/Wind Harmer
1.464
274827FISK ;RP
Adder
11.185
972037AH1-567 GEN1
Adder
0.264
960591AF2-350 GEN
Solar/Wind Harmer
14.399
274800UNIV PARK;3U
Adder
8.392
274801UNIV PARK;4U
Adder
8.392
972228AH1-698 GEN2
Adder
5.329
972227AH1-698 GEN1
Adder
3.752
274687WILL CNTY;4U
Adder
39.884
274687WILL CNTY;4U
Adder
39.884
274675JOLIET 29;7U
Adder
43.724
274675JOLIET 29;7U
Adder
42.162
971549AH1-272 GEN
Solar/Wind Harmer
26.288
274728ELWOOD EC;5P
Adder
23.342
274731ELWOOD EC;2P
Adder
23.341
274733ELWOOD EC;3P
Adder
23.341
274735ELWOOD EC;4P
Adder
23.341
276893AG1-478 C
Solar/Wind Harmer
0.781
970833AG2-524 GEN
Solar/Wind Harmer
12.371
970833AG2-524 GEN
Solar/Wind Harmer
5.754
274744AC1-111 GEN8
Adder
7.864
274746AC1-111 G10
Adder
7.864
963791AG1-232 GEN
Solar/Wind Harmer
18.586
965041AG1-368 GEN
Solar/Wind Harmer
13.667
970073AG2-061 GEN
Solar/Wind Harmer
3.172
971411AH1-196 GEN
Solar/Wind Harmer
20.266
971675AH1-338 GEN
Solar/Wind Harmer
24.31
276861AD2-134 GEN
Solar/Wind Harmer
2.41
276863AD2-134 GEN
Solar/Wind Harmer
2.41
971171AH1-044 GEN
Solar/Wind Harmer
26.795
274863CRW1-WTG
Solar/Wind Harmer
7.45
274864CRW2-WTG
Solar/Wind Harmer
7.45
274823ROCKFORD ;21
Adder
26.002
276889AE2-281 GEN
Solar/Wind Harmer
2.56
945581AF1-223 GEN
Solar/Wind Harmer
6.004
274856ECOGROVE ;U1
Solar/Wind Harmer
4.459
276611AD2-172 GEN
Solar/Wind Harmer
3.383
276612AE2-035 GEN
Solar/Wind Harmer
3.383
926823AC1-168 GEN
Solar/Wind Harmer
5.643
971681AH1-341 GEN
Solar/Wind Harmer
19.685
972267AH1-718 GEN
Adder
5.369
NYPJM->LTFIMP_NY
CLTF
2.259
LGEELTFEXP_LGEE->PJM
CLTF
2.616
WECLTFEXP_WEC->PJM
CLTF
5.072
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.348
CBM West 1LTFEXP_CBM-W1->PJM
CBM
157.25
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.085
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.547
MECLTFEXP_MEC->PJM
CLTF
17.928
SIGELTFEXP_SIGE->PJM
CLTF
0.305
AG2-052LTFEXP_AG2-052->PJM
LTF
0.31
AH1-155LTFEXP_AH1-155->PJM
LTF
0.466
LAGNLTFEXP_LAGN->PJM
CLTF
8.91
TVALTFEXP_TVA->PJM
CLTF
3.239

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.02 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1417.86
MW Contribution:
11.87
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.16 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1360.93
MW Contribution:
11.53
Bus #Bus NameTypeMW Contribution
274814UNIV PK N;0U
50/50
7.733
274807UNIV PK N;3U
50/50
7.717
274811UNIV PK N;7U
50/50
7.666
274803UNIV PARK;6U
50/50
6.752
972038AH1-567 GEN2
50/50
0.364
274654BRAIDWOOD;1U
50/50
3.559
274826FISK ;BP
50/50
10.736
276772AC2-154 GEN
Solar/Wind Harmer
2.6
276806AD2-047 C O1
Solar/Wind Harmer
9.966
274887GEN-1.85
Solar/Wind Harmer
4.964
276843GEN-1.7
Solar/Wind Harmer
0.534
274676JOLIET 29;8U
Adder
27.236
972259AH1-714 GEN
Adder
17.518
274729ELWOOD EC;1P
Adder
15.004
274730ELWOOD EC;6P
Adder
14.998
274734ELWOOD EC;8P
Adder
14.998
274736ELWOOD EC;9P
Adder
14.998
970707AG2-453 GEN
Solar/Wind Harmer
25.281
274772LINCOLN ;3U
Adder
5.579
939351AE1-166 GEN
Solar/Wind Harmer
5.315
276164X3-005 C
Solar/Wind Harmer
0.629
943121AE2-341 GEN
Solar/Wind Harmer
13.162
943591AF1-030 GEN
Solar/Wind Harmer
8.775
274682WAUKEGAN ;7U
Adder
15.584
274724RIVER EC ;11
Adder
15.136
274862TOP CROP ;2U
Solar/Wind Harmer
4.3
276868AE1-113 GEN
Solar/Wind Harmer
8.464
274879MINONK ;1U
Solar/Wind Harmer
5.643
276799AD1-013 GEN
Solar/Wind Harmer
1.827
946671AF1-331 GEN
Solar/Wind Harmer
0.346
274855GSG-6 ;RU
Solar/Wind Harmer
3.049
274850MENDOTA H;RU
Solar/Wind Harmer
2.12
276602WESTBROOK C
Solar/Wind Harmer
1.755
959091AF2-200 GEN
Solar/Wind Harmer
16.347
970571AG2-364 GEN
Solar/Wind Harmer
15.832
274857EASY ROAD;U1
Solar/Wind Harmer
3.765
274760LEE CO EC;1U
Adder
7.312
274767LEE CO EC;8U
Adder
7.226
276603SUBLETTE C
Solar/Wind Harmer
0.82
972231SS25-0005
Solar/Wind Harmer
7.079
972181SS23-001
Solar/Wind Harmer
4.424
274752CRETE EC ;2U
Adder
3.646
274753CRETE EC ;3U
Adder
3.646
274851PROVIDENC;RU
Solar/Wind Harmer
2.112
274849CRESCENT ;1U
Solar/Wind Harmer
1.371
276782AC1-033 GEN
Solar/Wind Harmer
2.933
274878BISHOP HL;2U
Solar/Wind Harmer
2.481
965931AG1-462 GEN
Solar/Wind Harmer
18.3
971087AG2-675 GEN
Solar/Wind Harmer
2.67
965091AG1-374 GEN
Solar/Wind Harmer
18.709
959611AF2-252 GEN
Solar/Wind Harmer
1.45
276785W4-005 GEN1
Solar/Wind Harmer
1.542
971993AH1-541 GEN
Solar/Wind Harmer
4.713
274815UNIV PK N;XU
50/50
0.421
274813UNIV PK N;9U
50/50
0.42
274816UNIV PK N;YU
50/50
0.42
274809UNIV PK N;5U
50/50
0.418
274805UNIV PK N;1U
50/50
7.683
274808UNIV PK N;4U
50/50
7.633
274798UNIV PARK;1U
50/50
0.253
276776AD2-060 GEN
Solar/Wind Harmer
0.39
274888KELLY CRK;1U
Solar/Wind Harmer
5.498
958011AF2-095 GEN
Solar/Wind Harmer
13.415
970941AG2-585 GEN
Solar/Wind Harmer
5.124
958481AF2-142 GEN
Solar/Wind Harmer
13.7
276893AG1-478 C
Solar/Wind Harmer
0.4
274674JOLIET 9 ;6U
Adder
14.03
274770LINCOLN ;1U
Adder
5.579
274771LINCOLN ;2U
Adder
5.579
276897AD1-100 C
Solar/Wind Harmer
41.633
958491AF2-143 GEN
Solar/Wind Harmer
13.153
274683WAUKEGAN ;8U
Adder
18.228
274683WAUKEGAN ;8U
Adder
15.365
274695ROCKY RD ;2P
Adder
9.62
274693ROCKY RD ;1P
Adder
9.525
274697ROCKY RD ;3P
Adder
2.613
274696ROCKY RD ;4P
Adder
9.847
962691AG1-118 GEN
Solar/Wind Harmer
25.473
960751AF2-366 GEN
Solar/Wind Harmer
2.425
276901AD2-066 C O1
Solar/Wind Harmer
2.944
276872AE1-163_GEN1
Solar/Wind Harmer
5.549
276876AE1-163_GEN2
Solar/Wind Harmer
5.549
971341AH1-150 GEN
Solar/Wind Harmer
16.347
971343AH1-151 GEN
Solar/Wind Harmer
16.347
972235AH1-702 GEN1
Adder
2.043
972236AH1-702 GEN2
Adder
1.777
938861AE1-114 GEN
Solar/Wind Harmer
6.489
274764LEE CO EC;5U
Adder
7.33
274765LEE CO EC;6U
Adder
7.33
274762LEE CO EC;3U
Adder
7.312
274763LEE CO EC;4U
Adder
7.244
276158O29GEN2
Solar/Wind Harmer
3.808
276157O29GEN1
Solar/Wind Harmer
2.895
276645AC1-214 GEN1
Solar/Wind Harmer
0.993
942111AE2-223 GEN
Solar/Wind Harmer
5.369
960611AF2-352 GEN
Solar/Wind Harmer
1.45
274880W4-005 GEN4
Solar/Wind Harmer
1.542
276174W4-005 GEN2
Solar/Wind Harmer
1.542
276615X2-022 GEN
Solar/Wind Harmer
0.952
276838X2-022 GEN2
Solar/Wind Harmer
0.113
274806UNIV PK N;2U
50/50
0.428
274810UNIV PK N;6U
50/50
0.419
274812UNIV PK N;8U
50/50
7.666
274802UNIV PARK;5U
50/50
6.752
274676JOLIET 29;8U
Adder
28.245
276694AA1-018 GEN2
Solar/Wind Harmer
5.763
276691AA1-018 GEN1
Solar/Wind Harmer
0.689
274732ELWOOD EC;7P
Adder
14.998
274674JOLIET 9 ;6U
Adder
14.03
972207SS24-0001
Solar/Wind Harmer
19.835
274773LINCOLN ;4U
Adder
5.579
274774LINCOLN ;5U
Adder
5.579
941551AE2-152 GEN
Solar/Wind Harmer
4.065
274871GR RIDGE ;2U
Solar/Wind Harmer
6.869
274847GR RIDGE ;BU
Solar/Wind Harmer
4.517
274745AC1-111 GEN9
Adder
4.917
274723RIVER EC ;12
Adder
15.725
276805AD2-038 GEN
Solar/Wind Harmer
4.496
274682WAUKEGAN ;7U
Adder
15.584
274828WAUKEGAN ;BP
Adder
9.555
274861TOP CROP ;1U
Solar/Wind Harmer
5.15
962781AG1-127 GEN
Solar/Wind Harmer
8.038
274872LEEDK;1U
Solar/Wind Harmer
6.906
276882AE2-255 GEN
Solar/Wind Harmer
2.821
971997AH1-543 GEN
Solar/Wind Harmer
12.918
957471AF2-041 GEN
Solar/Wind Harmer
24.52
959081AF2-199 GEN
Solar/Wind Harmer
8.173
971067AG2-660 GEN
Solar/Wind Harmer
1.901
274822ROCKFORD ;11
Adder
15.99
970819AG2-516 GEN
Solar/Wind Harmer
9.67
939401AE1-172 GEN
Solar/Wind Harmer
11.197
970569AG2-363 GEN
Solar/Wind Harmer
23.748
274858EASY ROAD;U2
Solar/Wind Harmer
3.765
274761LEE CO EC;2U
Adder
7.312
274766LEE CO EC;7U
Adder
7.226
276708O09 GEN2
Solar/Wind Harmer
2.719
274751CRETE EC ;1U
Adder
3.646
274754CRETE EC ;4U
Adder
3.646
276646AC1-214 GEN2
Solar/Wind Harmer
0.993
274848CAMPGROVE;RU
Solar/Wind Harmer
4.687
276655WTG1_EQ
Solar/Wind Harmer
5.716
276656WTG2_EQ
Solar/Wind Harmer
0.757
939741AE1-205 GEN
Solar/Wind Harmer
13.099
276686W4-005 GEN3
Solar/Wind Harmer
1.542
276621W2-048 GEN
Solar/Wind Harmer
3.032
972037AH1-567 GEN1
50/50
0.212
274799UNIV PARK;2U
50/50
0.261
274800UNIV PARK;3U
50/50
5.818
274801UNIV PARK;4U
50/50
5.818
274655BRAIDWOOD;2U
50/50
3.459
972228AH1-698 GEN2
50/50
3.695
972227AH1-698 GEN1
50/50
2.598
274827FISK ;RP
50/50
7.609
960591AF2-350 GEN
Solar/Wind Harmer
9.316
274675JOLIET 29;7U
Adder
28.251
274675JOLIET 29;7U
Adder
27.242
274731ELWOOD EC;2P
Adder
15.004
274733ELWOOD EC;3P
Adder
15.004
274735ELWOOD EC;4P
Adder
15.004
276893AG1-478 C
Solar/Wind Harmer
0.502
274728ELWOOD EC;5P
Adder
14.998
274687WILL CNTY;4U
Adder
25.432
274687WILL CNTY;4U
Adder
25.432
274775LINCOLN ;6U
Adder
5.579
274776LINCOLN ;7U
Adder
5.579
274777LINCOLN ;8U
Adder
5.579
970833AG2-524 GEN
Solar/Wind Harmer
7.818
970833AG2-524 GEN
Solar/Wind Harmer
3.636
274744AC1-111 GEN8
Adder
4.917
274746AC1-111 G10
Adder
4.917
970073AG2-061 GEN
Solar/Wind Harmer
2.039
971411AH1-196 GEN
Solar/Wind Harmer
12.461
276889AE2-281 GEN
Solar/Wind Harmer
1.585
971675AH1-338 GEN
Solar/Wind Harmer
14.872
276861AD2-134 GEN
Solar/Wind Harmer
1.474
276863AD2-134 GEN
Solar/Wind Harmer
1.474
971171AH1-044 GEN
Solar/Wind Harmer
16.347
274823ROCKFORD ;21
Adder
15.874
274856ECOGROVE ;U1
Solar/Wind Harmer
2.706
276611AD2-172 GEN
Solar/Wind Harmer
2.053
276612AE2-035 GEN
Solar/Wind Harmer
2.053
971681AH1-341 GEN
Solar/Wind Harmer
11.874
926823AC1-168 GEN
Solar/Wind Harmer
3.354
274863CRW1-WTG
Solar/Wind Harmer
4.3
274864CRW2-WTG
Solar/Wind Harmer
4.3
972267AH1-718 GEN
Adder
3.205
276741O09 GEN1
Solar/Wind Harmer
2.719
970169AG2-114 GEN
Solar/Wind Harmer
7.391
274877BISHOP HL;1U
Solar/Wind Harmer
2.481
946321AF1-296 GEN
Solar/Wind Harmer
7.572
276726Z2-087_GEN
Solar/Wind Harmer
5.179
959341AF2-225 GEN
Solar/Wind Harmer
9.824
274853TWINGROVE;U1
Solar/Wind Harmer
4.493
274854TWINGROVE;U2
Solar/Wind Harmer
4.399
276668AB2-070 GEN1
Solar/Wind Harmer
1.127
276848AB2-070 GEN3
Solar/Wind Harmer
1.127
276849AB2-070 GEN2
Solar/Wind Harmer
1.127
276763AC1-053 GEN1
Solar/Wind Harmer
1.983
276764AC1-053 GEN2
Solar/Wind Harmer
1.983
960681AF2-359 GEN
Solar/Wind Helper
0.812
990577J1339
External Queue
13.02728271484375
991247J1684 G
External Queue
11.30065631866455
990582J1340
External Queue
13.02728271484375
990512J1326
External Queue
4.174625396728516
990117J1214
External Queue
14.360710144042969
990727J1377 G
External Queue
4.850825309753418
990552J1334 G
External Queue
2.7086491172667593e-05
990762J1386
External Queue
10.741739273071289
990547J1333 G
External Queue
7.9084696769714355
990407J1304
External Queue
3.2305617332458496
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
0.728
WECLTFEXP_WEC->PJM
CLTF
3.105
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.18
MECLTFEXP_MEC->PJM
CLTF
9.676
SIGELTFEXP_SIGE->PJM
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.287
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.317
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.886
LAGNLTFEXP_LAGN->PJM
CLTF
3.217
TVALTFEXP_TVA->PJM
CLTF
0.831

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.02 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1417.85
MW Contribution:
11.87
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.16 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1360.91
MW Contribution:
11.53
Bus #Bus NameTypeMW Contribution
274814UNIV PK N;0U
50/50
7.733
274807UNIV PK N;3U
50/50
7.717
274811UNIV PK N;7U
50/50
7.666
274803UNIV PARK;6U
50/50
6.752
972038AH1-567 GEN2
50/50
0.364
274654BRAIDWOOD;1U
50/50
3.559
274826FISK ;BP
50/50
10.736
276772AC2-154 GEN
Solar/Wind Harmer
2.6
276806AD2-047 C O1
Solar/Wind Harmer
9.966
274887GEN-1.85
Solar/Wind Harmer
4.964
276843GEN-1.7
Solar/Wind Harmer
0.534
274676JOLIET 29;8U
Adder
27.236
972259AH1-714 GEN
Adder
17.518
274729ELWOOD EC;1P
Adder
15.004
274730ELWOOD EC;6P
Adder
14.998
274734ELWOOD EC;8P
Adder
14.998
274736ELWOOD EC;9P
Adder
14.998
970707AG2-453 GEN
Solar/Wind Harmer
25.281
274772LINCOLN ;3U
Adder
5.579
939351AE1-166 GEN
Solar/Wind Harmer
5.315
276164X3-005 C
Solar/Wind Harmer
0.629
943121AE2-341 GEN
Solar/Wind Harmer
13.162
943591AF1-030 GEN
Solar/Wind Harmer
8.775
274682WAUKEGAN ;7U
Adder
15.584
274724RIVER EC ;11
Adder
15.136
274862TOP CROP ;2U
Solar/Wind Harmer
4.3
276868AE1-113 GEN
Solar/Wind Harmer
8.464
274879MINONK ;1U
Solar/Wind Harmer
5.643
276799AD1-013 GEN
Solar/Wind Harmer
1.827
946671AF1-331 GEN
Solar/Wind Harmer
0.346
274855GSG-6 ;RU
Solar/Wind Harmer
3.049
274850MENDOTA H;RU
Solar/Wind Harmer
2.12
276602WESTBROOK C
Solar/Wind Harmer
1.755
959091AF2-200 GEN
Solar/Wind Harmer
16.347
970571AG2-364 GEN
Solar/Wind Harmer
15.832
274857EASY ROAD;U1
Solar/Wind Harmer
3.765
274760LEE CO EC;1U
Adder
7.312
274767LEE CO EC;8U
Adder
7.226
276603SUBLETTE C
Solar/Wind Harmer
0.82
972231SS25-0005
Solar/Wind Harmer
7.079
972181SS23-001
Solar/Wind Harmer
4.424
274752CRETE EC ;2U
Adder
3.646
274753CRETE EC ;3U
Adder
3.646
274851PROVIDENC;RU
Solar/Wind Harmer
2.112
274849CRESCENT ;1U
Solar/Wind Harmer
1.371
276782AC1-033 GEN
Solar/Wind Harmer
2.933
274878BISHOP HL;2U
Solar/Wind Harmer
2.481
965931AG1-462 GEN
Solar/Wind Harmer
18.3
971087AG2-675 GEN
Solar/Wind Harmer
2.67
965091AG1-374 GEN
Solar/Wind Harmer
18.709
959611AF2-252 GEN
Solar/Wind Harmer
1.45
276785W4-005 GEN1
Solar/Wind Harmer
1.542
971993AH1-541 GEN
Solar/Wind Harmer
4.713
274815UNIV PK N;XU
50/50
0.421
274813UNIV PK N;9U
50/50
0.42
274816UNIV PK N;YU
50/50
0.42
274809UNIV PK N;5U
50/50
0.418
274805UNIV PK N;1U
50/50
7.683
274808UNIV PK N;4U
50/50
7.633
274798UNIV PARK;1U
50/50
0.253
276776AD2-060 GEN
Solar/Wind Harmer
0.39
274806UNIV PK N;2U
50/50
0.428
274810UNIV PK N;6U
50/50
0.419
274812UNIV PK N;8U
50/50
7.666
274802UNIV PARK;5U
50/50
6.752
274676JOLIET 29;8U
Adder
28.245
276694AA1-018 GEN2
Solar/Wind Harmer
5.763
276691AA1-018 GEN1
Solar/Wind Harmer
0.689
972037AH1-567 GEN1
50/50
0.212
274799UNIV PARK;2U
50/50
0.261
274800UNIV PARK;3U
50/50
5.818
274801UNIV PARK;4U
50/50
5.818
274655BRAIDWOOD;2U
50/50
3.459
972228AH1-698 GEN2
50/50
3.695
972227AH1-698 GEN1
50/50
2.598
274827FISK ;RP
50/50
7.609
960591AF2-350 GEN
Solar/Wind Harmer
9.316
274675JOLIET 29;7U
Adder
28.251
274675JOLIET 29;7U
Adder
27.242
274731ELWOOD EC;2P
Adder
15.004
274733ELWOOD EC;3P
Adder
15.004
274735ELWOOD EC;4P
Adder
15.004
276893AG1-478 C
Solar/Wind Harmer
0.502
274728ELWOOD EC;5P
Adder
14.998
274687WILL CNTY;4U
Adder
25.432
274687WILL CNTY;4U
Adder
25.432
274775LINCOLN ;6U
Adder
5.579
274776LINCOLN ;7U
Adder
5.579
274777LINCOLN ;8U
Adder
5.579
970833AG2-524 GEN
Solar/Wind Harmer
7.818
970833AG2-524 GEN
Solar/Wind Harmer
3.636
274744AC1-111 GEN8
Adder
4.917
274746AC1-111 G10
Adder
4.917
970073AG2-061 GEN
Solar/Wind Harmer
2.039
971411AH1-196 GEN
Solar/Wind Harmer
12.461
276889AE2-281 GEN
Solar/Wind Harmer
1.585
971675AH1-338 GEN
Solar/Wind Harmer
14.872
276861AD2-134 GEN
Solar/Wind Harmer
1.474
276863AD2-134 GEN
Solar/Wind Harmer
1.474
971171AH1-044 GEN
Solar/Wind Harmer
16.347
274823ROCKFORD ;21
Adder
15.873
274856ECOGROVE ;U1
Solar/Wind Harmer
2.706
276611AD2-172 GEN
Solar/Wind Harmer
2.053
276612AE2-035 GEN
Solar/Wind Harmer
2.053
971681AH1-341 GEN
Solar/Wind Harmer
11.874
926823AC1-168 GEN
Solar/Wind Harmer
3.354
274863CRW1-WTG
Solar/Wind Harmer
4.3
274864CRW2-WTG
Solar/Wind Harmer
4.3
972267AH1-718 GEN
Adder
3.205
276741O09 GEN1
Solar/Wind Harmer
2.719
970169AG2-114 GEN
Solar/Wind Harmer
7.391
274877BISHOP HL;1U
Solar/Wind Harmer
2.481
946321AF1-296 GEN
Solar/Wind Harmer
7.572
276726Z2-087_GEN
Solar/Wind Harmer
5.179
959341AF2-225 GEN
Solar/Wind Harmer
9.824
274853TWINGROVE;U1
Solar/Wind Harmer
4.493
274854TWINGROVE;U2
Solar/Wind Harmer
4.399
276668AB2-070 GEN1
Solar/Wind Harmer
1.127
276848AB2-070 GEN3
Solar/Wind Harmer
1.127
276849AB2-070 GEN2
Solar/Wind Harmer
1.127
276763AC1-053 GEN1
Solar/Wind Harmer
1.983
276764AC1-053 GEN2
Solar/Wind Harmer
1.983
960681AF2-359 GEN
Solar/Wind Helper
0.812
274888KELLY CRK;1U
Solar/Wind Harmer
5.498
958011AF2-095 GEN
Solar/Wind Harmer
13.415
970941AG2-585 GEN
Solar/Wind Harmer
5.124
958481AF2-142 GEN
Solar/Wind Harmer
13.7
276893AG1-478 C
Solar/Wind Harmer
0.4
274674JOLIET 9 ;6U
Adder
14.029
274770LINCOLN ;1U
Adder
5.579
274771LINCOLN ;2U
Adder
5.579
276897AD1-100 C
Solar/Wind Harmer
41.634
958491AF2-143 GEN
Solar/Wind Harmer
13.153
274683WAUKEGAN ;8U
Adder
18.228
274683WAUKEGAN ;8U
Adder
15.365
274695ROCKY RD ;2P
Adder
9.62
274693ROCKY RD ;1P
Adder
9.525
274697ROCKY RD ;3P
Adder
2.613
274696ROCKY RD ;4P
Adder
9.847
962691AG1-118 GEN
Solar/Wind Harmer
25.473
960751AF2-366 GEN
Solar/Wind Harmer
2.425
276901AD2-066 C O1
Solar/Wind Harmer
2.944
276872AE1-163_GEN1
Solar/Wind Harmer
5.549
276876AE1-163_GEN2
Solar/Wind Harmer
5.549
971341AH1-150 GEN
Solar/Wind Harmer
16.347
971343AH1-151 GEN
Solar/Wind Harmer
16.347
972235AH1-702 GEN1
Adder
2.043
972236AH1-702 GEN2
Adder
1.777
938861AE1-114 GEN
Solar/Wind Harmer
6.489
274764LEE CO EC;5U
Adder
7.33
274765LEE CO EC;6U
Adder
7.33
274762LEE CO EC;3U
Adder
7.312
274763LEE CO EC;4U
Adder
7.243
276158O29GEN2
Solar/Wind Harmer
3.808
276157O29GEN1
Solar/Wind Harmer
2.895
276645AC1-214 GEN1
Solar/Wind Harmer
0.993
942111AE2-223 GEN
Solar/Wind Harmer
5.369
960611AF2-352 GEN
Solar/Wind Harmer
1.45
274880W4-005 GEN4
Solar/Wind Harmer
1.542
276174W4-005 GEN2
Solar/Wind Harmer
1.542
276615X2-022 GEN
Solar/Wind Harmer
0.952
276838X2-022 GEN2
Solar/Wind Harmer
0.113
274732ELWOOD EC;7P
Adder
14.998
274674JOLIET 9 ;6U
Adder
14.029
972207SS24-0001
Solar/Wind Harmer
19.836
274773LINCOLN ;4U
Adder
5.579
274774LINCOLN ;5U
Adder
5.579
941551AE2-152 GEN
Solar/Wind Harmer
4.065
274871GR RIDGE ;2U
Solar/Wind Harmer
6.869
274847GR RIDGE ;BU
Solar/Wind Harmer
4.517
274745AC1-111 GEN9
Adder
4.917
274723RIVER EC ;12
Adder
15.725
276805AD2-038 GEN
Solar/Wind Harmer
4.496
274682WAUKEGAN ;7U
Adder
15.584
274828WAUKEGAN ;BP
Adder
9.555
274861TOP CROP ;1U
Solar/Wind Harmer
5.15
962781AG1-127 GEN
Solar/Wind Harmer
8.038
274872LEEDK;1U
Solar/Wind Harmer
6.906
276882AE2-255 GEN
Solar/Wind Harmer
2.821
971997AH1-543 GEN
Solar/Wind Harmer
12.917
957471AF2-041 GEN
Solar/Wind Harmer
24.52
959081AF2-199 GEN
Solar/Wind Harmer
8.173
971067AG2-660 GEN
Solar/Wind Harmer
1.901
274822ROCKFORD ;11
Adder
15.989
970819AG2-516 GEN
Solar/Wind Harmer
9.67
939401AE1-172 GEN
Solar/Wind Harmer
11.197
970569AG2-363 GEN
Solar/Wind Harmer
23.748
274858EASY ROAD;U2
Solar/Wind Harmer
3.765
274761LEE CO EC;2U
Adder
7.312
274766LEE CO EC;7U
Adder
7.226
276708O09 GEN2
Solar/Wind Harmer
2.719
274751CRETE EC ;1U
Adder
3.646
274754CRETE EC ;4U
Adder
3.646
276646AC1-214 GEN2
Solar/Wind Harmer
0.993
274848CAMPGROVE;RU
Solar/Wind Harmer
4.687
276655WTG1_EQ
Solar/Wind Harmer
5.716
276656WTG2_EQ
Solar/Wind Harmer
0.757
939741AE1-205 GEN
Solar/Wind Harmer
13.099
276686W4-005 GEN3
Solar/Wind Harmer
1.542
276621W2-048 GEN
Solar/Wind Harmer
3.032
990577J1339
External Queue
13.027382850646973
991247J1684 G
External Queue
11.300759315490723
990582J1340
External Queue
13.027382850646973
990512J1326
External Queue
4.174581050872803
990117J1214
External Queue
14.36055850982666
990727J1377 G
External Queue
4.850771427154541
990552J1334 G
External Queue
2.708679676288739e-05
990762J1386
External Queue
10.741793632507324
990547J1333 G
External Queue
7.908559322357178
990407J1304
External Queue
3.230527400970459
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
0.728
WECLTFEXP_WEC->PJM
CLTF
3.105
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.18
MECLTFEXP_MEC->PJM
CLTF
9.676
SIGELTFEXP_SIGE->PJM
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.287
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.317
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.886
LAGNLTFEXP_LAGN->PJM
CLTF
3.216
TVALTFEXP_TVA->PJM
CLTF
0.831

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.13 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1399.5
MW Contribution:
11.76
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.11 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1350.72
MW Contribution:
11.46
Bus #Bus NameTypeMW Contribution
274815UNIV PK N;XU
50/50
0.418
274813UNIV PK N;9U
50/50
0.417
274816UNIV PK N;YU
50/50
0.417
274809UNIV PK N;5U
50/50
0.415
274805UNIV PK N;1U
50/50
7.63
274808UNIV PK N;4U
50/50
7.58
274798UNIV PARK;1U
50/50
0.251
274888KELLY CRK;1U
Solar/Wind Harmer
5.442
276776AD2-060 GEN
Solar/Wind Harmer
0.386
958011AF2-095 GEN
Solar/Wind Harmer
13.278
970941AG2-585 GEN
Solar/Wind Harmer
5.072
958481AF2-142 GEN
Solar/Wind Harmer
13.567
274814UNIV PK N;0U
50/50
7.68
274807UNIV PK N;3U
50/50
7.664
274811UNIV PK N;7U
50/50
7.614
274803UNIV PARK;6U
50/50
6.692
972038AH1-567 GEN2
50/50
0.36
274654BRAIDWOOD;1U
50/50
3.524
274826FISK ;BP
50/50
10.624
274887GEN-1.85
Solar/Wind Harmer
4.913
276772AC2-154 GEN
Solar/Wind Harmer
2.573
276843GEN-1.7
Solar/Wind Harmer
0.529
276806AD2-047 C O1
Solar/Wind Harmer
9.865
274676JOLIET 29;8U
Adder
26.964
972259AH1-714 GEN
Adder
17.345
274729ELWOOD EC;1P
Adder
14.855
274730ELWOOD EC;6P
Adder
14.848
274734ELWOOD EC;8P
Adder
14.848
274736ELWOOD EC;9P
Adder
14.848
970707AG2-453 GEN
Solar/Wind Harmer
25.033
274772LINCOLN ;3U
Adder
5.52
939351AE1-166 GEN
Solar/Wind Harmer
5.261
276164X3-005 C
Solar/Wind Harmer
0.622
943121AE2-341 GEN
Solar/Wind Harmer
13.032
943591AF1-030 GEN
Solar/Wind Harmer
8.688
274682WAUKEGAN ;7U
Adder
15.429
274724RIVER EC ;11
Adder
14.953
274862TOP CROP ;2U
Solar/Wind Harmer
4.255
276868AE1-113 GEN
Solar/Wind Harmer
8.379
274879MINONK ;1U
Solar/Wind Harmer
5.586
276799AD1-013 GEN
Solar/Wind Harmer
1.809
946671AF1-331 GEN
Solar/Wind Harmer
0.343
274855GSG-6 ;RU
Solar/Wind Harmer
3.018
274850MENDOTA H;RU
Solar/Wind Harmer
2.099
276602WESTBROOK C
Solar/Wind Harmer
1.738
959091AF2-200 GEN
Solar/Wind Harmer
16.184
970571AG2-364 GEN
Solar/Wind Harmer
15.672
274857EASY ROAD;U1
Solar/Wind Harmer
3.728
274760LEE CO EC;1U
Adder
7.239
274767LEE CO EC;8U
Adder
7.154
276603SUBLETTE C
Solar/Wind Harmer
0.812
972231SS25-0005
Solar/Wind Harmer
6.981
972181SS23-001
Solar/Wind Harmer
4.363
274752CRETE EC ;2U
Adder
3.595
274753CRETE EC ;3U
Adder
3.595
274851PROVIDENC;RU
Solar/Wind Harmer
2.091
274849CRESCENT ;1U
Solar/Wind Harmer
1.357
276782AC1-033 GEN
Solar/Wind Harmer
2.903
274878BISHOP HL;2U
Solar/Wind Harmer
2.456
965931AG1-462 GEN
Solar/Wind Harmer
18.116
971087AG2-675 GEN
Solar/Wind Harmer
2.643
965091AG1-374 GEN
Solar/Wind Harmer
18.513
959611AF2-252 GEN
Solar/Wind Harmer
1.435
276785W4-005 GEN1
Solar/Wind Harmer
1.526
971993AH1-541 GEN
Solar/Wind Harmer
4.662
276893AG1-478 C
Solar/Wind Harmer
0.396
274674JOLIET 9 ;6U
Adder
13.889
274770LINCOLN ;1U
Adder
5.52
274771LINCOLN ;2U
Adder
5.52
276897AD1-100 C
Solar/Wind Harmer
41.209
958491AF2-143 GEN
Solar/Wind Harmer
13.024
274683WAUKEGAN ;8U
Adder
18.046
274683WAUKEGAN ;8U
Adder
15.212
274695ROCKY RD ;2P
Adder
9.524
274693ROCKY RD ;1P
Adder
9.431
274697ROCKY RD ;3P
Adder
2.587
274696ROCKY RD ;4P
Adder
9.749
962691AG1-118 GEN
Solar/Wind Harmer
25.22
960751AF2-366 GEN
Solar/Wind Harmer
2.401
276901AD2-066 C O1
Solar/Wind Harmer
2.915
276872AE1-163_GEN1
Solar/Wind Harmer
5.494
276876AE1-163_GEN2
Solar/Wind Harmer
5.494
971341AH1-150 GEN
Solar/Wind Harmer
16.184
971343AH1-151 GEN
Solar/Wind Harmer
16.184
972235AH1-702 GEN1
Adder
2.023
972236AH1-702 GEN2
Adder
1.759
938861AE1-114 GEN
Solar/Wind Harmer
6.424
274764LEE CO EC;5U
Adder
7.256
274765LEE CO EC;6U
Adder
7.256
274762LEE CO EC;3U
Adder
7.239
274763LEE CO EC;4U
Adder
7.171
276158O29GEN2
Solar/Wind Harmer
3.77
276157O29GEN1
Solar/Wind Harmer
2.866
276645AC1-214 GEN1
Solar/Wind Harmer
0.983
942111AE2-223 GEN
Solar/Wind Harmer
5.313
960611AF2-352 GEN
Solar/Wind Harmer
1.435
274880W4-005 GEN4
Solar/Wind Harmer
1.526
276174W4-005 GEN2
Solar/Wind Harmer
1.526
276615X2-022 GEN
Solar/Wind Harmer
0.942
276838X2-022 GEN2
Solar/Wind Harmer
0.112
274806UNIV PK N;2U
50/50
0.425
274810UNIV PK N;6U
50/50
0.416
274812UNIV PK N;8U
50/50
7.614
274802UNIV PARK;5U
50/50
6.692
274676JOLIET 29;8U
Adder
27.963
276694AA1-018 GEN2
Solar/Wind Harmer
5.707
276691AA1-018 GEN1
Solar/Wind Harmer
0.682
274732ELWOOD EC;7P
Adder
14.848
274674JOLIET 9 ;6U
Adder
13.889
972207SS24-0001
Solar/Wind Harmer
19.625
274773LINCOLN ;4U
Adder
5.52
274774LINCOLN ;5U
Adder
5.52
941551AE2-152 GEN
Solar/Wind Harmer
4.023
274871GR RIDGE ;2U
Solar/Wind Harmer
6.801
274847GR RIDGE ;BU
Solar/Wind Harmer
4.472
274745AC1-111 GEN9
Adder
4.868
276805AD2-038 GEN
Solar/Wind Harmer
4.452
274723RIVER EC ;12
Adder
15.54
274682WAUKEGAN ;7U
Adder
15.429
274828WAUKEGAN ;BP
Adder
9.459
274861TOP CROP ;1U
Solar/Wind Harmer
5.097
962781AG1-127 GEN
Solar/Wind Harmer
7.958
274872LEEDK;1U
Solar/Wind Harmer
6.837
276882AE2-255 GEN
Solar/Wind Harmer
2.793
971997AH1-543 GEN
Solar/Wind Harmer
12.788
957471AF2-041 GEN
Solar/Wind Harmer
24.276
959081AF2-199 GEN
Solar/Wind Harmer
8.092
971067AG2-660 GEN
Solar/Wind Harmer
1.882
274822ROCKFORD ;11
Adder
15.83
970819AG2-516 GEN
Solar/Wind Harmer
9.574
939401AE1-172 GEN
Solar/Wind Harmer
11.082
970569AG2-363 GEN
Solar/Wind Harmer
23.508
274858EASY ROAD;U2
Solar/Wind Harmer
3.728
274761LEE CO EC;2U
Adder
7.239
274766LEE CO EC;7U
Adder
7.154
276708O09 GEN2
Solar/Wind Harmer
2.692
274751CRETE EC ;1U
Adder
3.595
274754CRETE EC ;4U
Adder
3.595
276646AC1-214 GEN2
Solar/Wind Harmer
0.983
274848CAMPGROVE;RU
Solar/Wind Harmer
4.64
276655WTG1_EQ
Solar/Wind Harmer
5.657
276656WTG2_EQ
Solar/Wind Harmer
0.749
939741AE1-205 GEN
Solar/Wind Harmer
12.962
276686W4-005 GEN3
Solar/Wind Harmer
1.526
276621W2-048 GEN
Solar/Wind Harmer
2.999
972037AH1-567 GEN1
50/50
0.21
274799UNIV PARK;2U
50/50
0.259
274800UNIV PARK;3U
50/50
5.759
274801UNIV PARK;4U
50/50
5.759
274655BRAIDWOOD;2U
50/50
3.425
972228AH1-698 GEN2
50/50
3.658
972227AH1-698 GEN1
50/50
2.572
274827FISK ;RP
50/50
7.53
960591AF2-350 GEN
Solar/Wind Harmer
9.221
274675JOLIET 29;7U
Adder
27.969
274675JOLIET 29;7U
Adder
26.97
274731ELWOOD EC;2P
Adder
14.855
274733ELWOOD EC;3P
Adder
14.855
274735ELWOOD EC;4P
Adder
14.855
276893AG1-478 C
Solar/Wind Harmer
0.497
274728ELWOOD EC;5P
Adder
14.848
274687WILL CNTY;4U
Adder
25.173
274687WILL CNTY;4U
Adder
25.173
274775LINCOLN ;6U
Adder
5.52
274776LINCOLN ;7U
Adder
5.52
274777LINCOLN ;8U
Adder
5.52
970833AG2-524 GEN
Solar/Wind Harmer
7.74
970833AG2-524 GEN
Solar/Wind Harmer
3.6
274744AC1-111 GEN8
Adder
4.868
274746AC1-111 G10
Adder
4.868
970073AG2-061 GEN
Solar/Wind Harmer
2.019
971411AH1-196 GEN
Solar/Wind Harmer
12.337
276889AE2-281 GEN
Solar/Wind Harmer
1.57
971675AH1-338 GEN
Solar/Wind Harmer
14.724
276861AD2-134 GEN
Solar/Wind Harmer
1.46
276863AD2-134 GEN
Solar/Wind Harmer
1.46
971171AH1-044 GEN
Solar/Wind Harmer
16.184
274823ROCKFORD ;21
Adder
15.715
274856ECOGROVE ;U1
Solar/Wind Harmer
2.679
276611AD2-172 GEN
Solar/Wind Harmer
2.032
276612AE2-035 GEN
Solar/Wind Harmer
2.032
971681AH1-341 GEN
Solar/Wind Harmer
11.756
926823AC1-168 GEN
Solar/Wind Harmer
3.32
274863CRW1-WTG
Solar/Wind Harmer
4.256
274864CRW2-WTG
Solar/Wind Harmer
4.256
972267AH1-718 GEN
Adder
3.173
276741O09 GEN1
Solar/Wind Harmer
2.692
970169AG2-114 GEN
Solar/Wind Harmer
7.315
274877BISHOP HL;1U
Solar/Wind Harmer
2.456
946321AF1-296 GEN
Solar/Wind Harmer
7.496
276726Z2-087_GEN
Solar/Wind Harmer
5.125
959341AF2-225 GEN
Solar/Wind Harmer
9.722
274853TWINGROVE;U1
Solar/Wind Harmer
4.446
274854TWINGROVE;U2
Solar/Wind Harmer
4.353
276668AB2-070 GEN1
Solar/Wind Harmer
1.115
276848AB2-070 GEN3
Solar/Wind Harmer
1.115
276849AB2-070 GEN2
Solar/Wind Harmer
1.115
276763AC1-053 GEN1
Solar/Wind Harmer
1.962
276764AC1-053 GEN2
Solar/Wind Harmer
1.962
960681AF2-359 GEN
Solar/Wind Helper
0.834
990577J1339
External Queue
12.909603118896484
991777J1629 G
External Queue
7.800808906555176
991247J1684 G
External Queue
11.171548843383789
990582J1340
External Queue
12.909603118896484
990512J1326
External Queue
4.147134304046631
990117J1214
External Queue
14.266140937805176
990727J1377 G
External Queue
4.818482875823975
990762J1386
External Queue
10.677118301391602
990547J1333 G
External Queue
2.6688376237871125e-05
990407J1304
External Queue
3.2089223861694336
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.136
NYPJM->LTFIMP_NY
CLTF
0.719
WECLTFEXP_WEC->PJM
CLTF
3.074
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.283
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.936
MECLTFEXP_MEC->PJM
CLTF
9.578
SIGELTFEXP_SIGE->PJM
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.281
AG2-052LTFEXP_AG2-052->PJM
LTF
0.065
AH1-155LTFEXP_AH1-155->PJM
LTF
0.097
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.311
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.871
LAGNLTFEXP_LAGN->PJM
CLTF
3.187
TVALTFEXP_TVA->PJM
CLTF
0.824

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.33 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1372.34
MW Contribution:
11.59
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.0 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1359.38
MW Contribution:
11.44
Bus #Bus NameTypeMW Contribution
274815UNIV PK N;XU
50/50
0.413
274813UNIV PK N;9U
50/50
0.412
274816UNIV PK N;YU
50/50
0.412
274809UNIV PK N;5U
50/50
0.41
274805UNIV PK N;1U
50/50
7.54
274808UNIV PK N;4U
50/50
7.49
274798UNIV PARK;1U
50/50
0.247
276776AD2-060 GEN
Solar/Wind Harmer
0.38
274888KELLY CRK;1U
Solar/Wind Harmer
5.351
958011AF2-095 GEN
Solar/Wind Harmer
13.059
970941AG2-585 GEN
Solar/Wind Harmer
4.988
958481AF2-142 GEN
Solar/Wind Harmer
13.364
276893AG1-478 C
Solar/Wind Harmer
0.39
274674JOLIET 9 ;6U
Adder
13.667
274770LINCOLN ;1U
Adder
5.429
274771LINCOLN ;2U
Adder
5.429
276897AD1-100 C
Solar/Wind Harmer
40.556
958491AF2-143 GEN
Solar/Wind Harmer
12.832
274683WAUKEGAN ;8U
Adder
17.767
274683WAUKEGAN ;8U
Adder
14.977
274695ROCKY RD ;2P
Adder
9.378
274693ROCKY RD ;1P
Adder
9.285
274697ROCKY RD ;3P
Adder
2.547
274696ROCKY RD ;4P
Adder
9.599
962691AG1-118 GEN
Solar/Wind Harmer
24.837
960751AF2-366 GEN
Solar/Wind Harmer
2.364
276901AD2-066 C O1
Solar/Wind Harmer
2.872
276872AE1-163_GEN1
Solar/Wind Harmer
5.415
276876AE1-163_GEN2
Solar/Wind Harmer
5.415
971341AH1-150 GEN
Solar/Wind Harmer
15.946
971343AH1-151 GEN
Solar/Wind Harmer
15.946
972235AH1-702 GEN1
Adder
1.993
972236AH1-702 GEN2
Adder
1.733
938861AE1-114 GEN
Solar/Wind Harmer
6.332
274764LEE CO EC;5U
Adder
7.153
274765LEE CO EC;6U
Adder
7.153
274762LEE CO EC;3U
Adder
7.136
274763LEE CO EC;4U
Adder
7.069
276158O29GEN2
Solar/Wind Harmer
3.718
276157O29GEN1
Solar/Wind Harmer
2.827
276645AC1-214 GEN1
Solar/Wind Harmer
0.97
942111AE2-223 GEN
Solar/Wind Harmer
5.256
960611AF2-352 GEN
Solar/Wind Harmer
1.421
274880W4-005 GEN4
Solar/Wind Harmer
1.517
276174W4-005 GEN2
Solar/Wind Harmer
1.517
276615X2-022 GEN
Solar/Wind Harmer
0.938
276838X2-022 GEN2
Solar/Wind Harmer
0.111
270535AF1-215 GEN1
Solar/Wind Helper
0.83
270536AF1-215 GEN2
Solar/Wind Helper
0.83
274814UNIV PK N;0U
50/50
7.589
274807UNIV PK N;3U
50/50
7.573
274811UNIV PK N;7U
50/50
7.523
274803UNIV PARK;6U
50/50
6.594
972038AH1-567 GEN2
50/50
0.354
274654BRAIDWOOD;1U
50/50
3.467
274826FISK ;BP
50/50
10.441
276772AC2-154 GEN
Solar/Wind Harmer
2.531
276806AD2-047 C O1
Solar/Wind Harmer
9.702
274887GEN-1.85
Solar/Wind Harmer
4.832
276843GEN-1.7
Solar/Wind Harmer
0.52
274676JOLIET 29;8U
Adder
26.53
972259AH1-714 GEN
Adder
17.069
274729ELWOOD EC;1P
Adder
14.618
274730ELWOOD EC;6P
Adder
14.611
274734ELWOOD EC;8P
Adder
14.611
274736ELWOOD EC;9P
Adder
14.611
970707AG2-453 GEN
Solar/Wind Harmer
24.637
274772LINCOLN ;3U
Adder
5.429
939351AE1-166 GEN
Solar/Wind Harmer
5.178
276164X3-005 C
Solar/Wind Harmer
0.61
943121AE2-341 GEN
Solar/Wind Harmer
12.829
943591AF1-030 GEN
Solar/Wind Harmer
8.553
274682WAUKEGAN ;7U
Adder
15.19
274862TOP CROP ;2U
Solar/Wind Harmer
4.187
274724RIVER EC ;11
Adder
14.64
276868AE1-113 GEN
Solar/Wind Harmer
8.254
274879MINONK ;1U
Solar/Wind Harmer
5.503
276799AD1-013 GEN
Solar/Wind Harmer
1.782
946671AF1-331 GEN
Solar/Wind Harmer
0.338
274855GSG-6 ;RU
Solar/Wind Harmer
2.974
274850MENDOTA H;RU
Solar/Wind Harmer
2.067
276602WESTBROOK C
Solar/Wind Harmer
1.712
959091AF2-200 GEN
Solar/Wind Harmer
15.946
970571AG2-364 GEN
Solar/Wind Harmer
15.451
274857EASY ROAD;U1
Solar/Wind Harmer
3.675
274760LEE CO EC;1U
Adder
7.136
274767LEE CO EC;8U
Adder
7.052
276603SUBLETTE C
Solar/Wind Harmer
0.801
274851PROVIDENC;RU
Solar/Wind Harmer
2.064
274849CRESCENT ;1U
Solar/Wind Harmer
1.34
276782AC1-033 GEN
Solar/Wind Harmer
2.865
274878BISHOP HL;2U
Solar/Wind Harmer
2.424
972231SS25-0005
Solar/Wind Harmer
6.807
972181SS23-001
Solar/Wind Harmer
4.255
274752CRETE EC ;2U
Adder
3.506
274753CRETE EC ;3U
Adder
3.506
965931AG1-462 GEN
Solar/Wind Harmer
17.88
971087AG2-675 GEN
Solar/Wind Harmer
2.609
965091AG1-374 GEN
Solar/Wind Harmer
18.33
959611AF2-252 GEN
Solar/Wind Harmer
1.421
276785W4-005 GEN1
Solar/Wind Harmer
1.517
971993AH1-541 GEN
Solar/Wind Harmer
4.637
274806UNIV PK N;2U
50/50
0.42
274810UNIV PK N;6U
50/50
0.411
274812UNIV PK N;8U
50/50
7.523
274802UNIV PARK;5U
50/50
6.594
274676JOLIET 29;8U
Adder
27.513
276694AA1-018 GEN2
Solar/Wind Harmer
5.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.672
274732ELWOOD EC;7P
Adder
14.611
274674JOLIET 9 ;6U
Adder
13.667
972207SS24-0001
Solar/Wind Harmer
19.302
274773LINCOLN ;4U
Adder
5.429
274774LINCOLN ;5U
Adder
5.429
941551AE2-152 GEN
Solar/Wind Harmer
3.96
274871GR RIDGE ;2U
Solar/Wind Harmer
6.696
274847GR RIDGE ;BU
Solar/Wind Harmer
4.403
274745AC1-111 GEN9
Adder
4.792
276805AD2-038 GEN
Solar/Wind Harmer
4.387
274723RIVER EC ;12
Adder
15.224
274682WAUKEGAN ;7U
Adder
15.19
274828WAUKEGAN ;BP
Adder
9.313
274861TOP CROP ;1U
Solar/Wind Harmer
5.015
962781AG1-127 GEN
Solar/Wind Harmer
7.837
274872LEEDK;1U
Solar/Wind Harmer
6.734
276882AE2-255 GEN
Solar/Wind Harmer
2.751
971997AH1-543 GEN
Solar/Wind Harmer
12.602
957471AF2-041 GEN
Solar/Wind Harmer
23.919
959081AF2-199 GEN
Solar/Wind Harmer
7.973
971067AG2-660 GEN
Solar/Wind Harmer
1.854
274822ROCKFORD ;11
Adder
15.597
970819AG2-516 GEN
Solar/Wind Harmer
9.434
939401AE1-172 GEN
Solar/Wind Harmer
10.923
970569AG2-363 GEN
Solar/Wind Harmer
23.176
274858EASY ROAD;U2
Solar/Wind Harmer
3.675
274761LEE CO EC;2U
Adder
7.136
274766LEE CO EC;7U
Adder
7.052
276708O09 GEN2
Solar/Wind Harmer
2.655
276646AC1-214 GEN2
Solar/Wind Harmer
0.97
274751CRETE EC ;1U
Adder
3.506
274754CRETE EC ;4U
Adder
3.506
274848CAMPGROVE;RU
Solar/Wind Harmer
4.58
276655WTG1_EQ
Solar/Wind Harmer
5.596
276656WTG2_EQ
Solar/Wind Harmer
0.741
939741AE1-205 GEN
Solar/Wind Harmer
12.822
276686W4-005 GEN3
Solar/Wind Harmer
1.517
276621W2-048 GEN
Solar/Wind Harmer
2.986
270055AF2-134 C O1
Solar/Wind Helper
0.553
972037AH1-567 GEN1
50/50
0.207
274655BRAIDWOOD;2U
50/50
3.37
972228AH1-698 GEN2
50/50
3.6
274799UNIV PARK;2U
50/50
0.254
274800UNIV PARK;3U
50/50
5.663
274801UNIV PARK;4U
50/50
5.663
972227AH1-698 GEN1
50/50
2.531
274827FISK ;RP
50/50
7.4
960591AF2-350 GEN
Solar/Wind Harmer
9.069
274675JOLIET 29;7U
Adder
27.519
274675JOLIET 29;7U
Adder
26.536
274731ELWOOD EC;2P
Adder
14.618
274733ELWOOD EC;3P
Adder
14.618
274735ELWOOD EC;4P
Adder
14.618
276893AG1-478 C
Solar/Wind Harmer
0.489
274728ELWOOD EC;5P
Adder
14.611
274687WILL CNTY;4U
Adder
24.758
274687WILL CNTY;4U
Adder
24.758
274775LINCOLN ;6U
Adder
5.429
274776LINCOLN ;7U
Adder
5.429
274777LINCOLN ;8U
Adder
5.429
970833AG2-524 GEN
Solar/Wind Harmer
7.62
970833AG2-524 GEN
Solar/Wind Harmer
3.544
274744AC1-111 GEN8
Adder
4.792
274746AC1-111 G10
Adder
4.792
970073AG2-061 GEN
Solar/Wind Harmer
1.989
971411AH1-196 GEN
Solar/Wind Harmer
12.152
276889AE2-281 GEN
Solar/Wind Harmer
1.547
971675AH1-338 GEN
Solar/Wind Harmer
14.506
276861AD2-134 GEN
Solar/Wind Harmer
1.438
276863AD2-134 GEN
Solar/Wind Harmer
1.438
971171AH1-044 GEN
Solar/Wind Harmer
15.946
274823ROCKFORD ;21
Adder
15.484
274856ECOGROVE ;U1
Solar/Wind Harmer
2.64
276611AD2-172 GEN
Solar/Wind Harmer
2.003
276612AE2-035 GEN
Solar/Wind Harmer
2.003
971681AH1-341 GEN
Solar/Wind Harmer
11.587
926823AC1-168 GEN
Solar/Wind Harmer
3.274
274863CRW1-WTG
Solar/Wind Harmer
4.198
274864CRW2-WTG
Solar/Wind Harmer
4.198
972267AH1-718 GEN
Adder
3.129
276741O09 GEN1
Solar/Wind Harmer
2.655
970169AG2-114 GEN
Solar/Wind Harmer
7.22
274877BISHOP HL;1U
Solar/Wind Harmer
2.424
946321AF1-296 GEN
Solar/Wind Harmer
7.397
276726Z2-087_GEN
Solar/Wind Harmer
5.069
959341AF2-225 GEN
Solar/Wind Harmer
9.617
274853TWINGROVE;U1
Solar/Wind Harmer
4.402
274854TWINGROVE;U2
Solar/Wind Harmer
4.31
276668AB2-070 GEN1
Solar/Wind Harmer
1.109
276848AB2-070 GEN3
Solar/Wind Harmer
1.109
276849AB2-070 GEN2
Solar/Wind Harmer
1.109
276763AC1-053 GEN1
Solar/Wind Harmer
1.952
276764AC1-053 GEN2
Solar/Wind Harmer
1.952
960681AF2-359 GEN
Solar/Wind Helper
0.881
990577J1339
External Queue
12.685364723205566
991777J1629 G
External Queue
7.748876094818115
991247J1684 G
External Queue
10.926641464233398
990582J1340
External Queue
12.685364723205566
990512J1326
External Queue
4.118803024291992
990117J1214
External Queue
14.168682098388672
990727J1377 G
External Queue
4.783022880554199
990762J1386
External Queue
10.550675392150879
990547J1333 G
External Queue
2.593603312561754e-05
990407J1304
External Queue
3.1846888065338135
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.115
NYPJM->LTFIMP_NY
CLTF
0.703
WECLTFEXP_WEC->PJM
CLTF
3.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.896
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.516
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.515
MECLTFEXP_MEC->PJM
CLTF
9.484
SIGELTFEXP_SIGE->PJM
CLTF
0.018
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.248
AG2-052LTFEXP_AG2-052->PJM
LTF
0.062
AH1-155LTFEXP_AH1-155->PJM
LTF
0.093
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.624
LAGNLTFEXP_LAGN->PJM
CLTF
3.257
TVALTFEXP_TVA->PJM
CLTF
0.876

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.37 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1081.42
MW Contribution:
8.89
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.44 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1023.79
MW Contribution:
8.63
Bus #Bus NameTypeMW Contribution
274815UNIV PK N;XU
50/50
0.421
274813UNIV PK N;9U
50/50
0.42
274816UNIV PK N;YU
50/50
0.42
274809UNIV PK N;5U
50/50
0.418
274805UNIV PK N;1U
50/50
7.683
274808UNIV PK N;4U
50/50
7.633
274798UNIV PARK;1U
50/50
0.253
274888KELLY CRK;1U
Solar/Wind Harmer
0.379
276776AD2-060 GEN
Solar/Wind Harmer
0.693
958011AF2-095 GEN
Solar/Wind Harmer
9.359
970941AG2-585 GEN
Solar/Wind Harmer
3.575
958481AF2-142 GEN
Solar/Wind Harmer
9.558
276893AG1-478 C
Solar/Wind Harmer
0.424
274674JOLIET 9 ;6U
Adder
14.03
274770LINCOLN ;1U
Adder
7.591
274771LINCOLN ;2U
Adder
7.591
276897AD1-100 C
Solar/Wind Harmer
15.631
958491AF2-143 GEN
Solar/Wind Harmer
9.176
274683WAUKEGAN ;8U
Adder
18.229
274683WAUKEGAN ;8U
Adder
15.367
274695ROCKY RD ;2P
Adder
9.621
274693ROCKY RD ;1P
Adder
9.526
274697ROCKY RD ;3P
Adder
2.614
274696ROCKY RD ;4P
Adder
9.848
962691AG1-118 GEN
Solar/Wind Harmer
17.774
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
11.406
971343AH1-151 GEN
Solar/Wind Harmer
11.406
972235AH1-702 GEN1
Adder
2.043
972236AH1-702 GEN2
Adder
1.777
938861AE1-114 GEN
Solar/Wind Harmer
3.13
274764LEE CO EC;5U
Adder
7.33
274765LEE CO EC;6U
Adder
7.33
274762LEE CO EC;3U
Adder
7.313
274763LEE CO EC;4U
Adder
7.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.856
276645AC1-214 GEN1
Solar/Wind Harmer
0.203
942111AE2-223 GEN
Solar/Wind Harmer
1.485
960611AF2-352 GEN
Solar/Wind Harmer
1.45
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.191
972037AH1-567 GEN1
50/50
0.212
274799UNIV PARK;2U
50/50
0.261
274800UNIV PARK;3U
50/50
5.818
274801UNIV PARK;4U
50/50
5.818
274655BRAIDWOOD;2U
50/50
3.459
972228AH1-698 GEN2
50/50
3.695
972227AH1-698 GEN1
50/50
2.598
274827FISK ;RP
50/50
7.609
960591AF2-350 GEN
Solar/Wind Harmer
6.499
274675JOLIET 29;7U
Adder
28.252
274675JOLIET 29;7U
Adder
27.243
274731ELWOOD EC;2P
Adder
15.005
274733ELWOOD EC;3P
Adder
15.005
274735ELWOOD EC;4P
Adder
15.005
274728ELWOOD EC;5P
Adder
14.998
274687WILL CNTY;4U
Adder
25.433
274687WILL CNTY;4U
Adder
25.433
274775LINCOLN ;6U
Adder
7.591
274776LINCOLN ;7U
Adder
7.591
274777LINCOLN ;8U
Adder
7.591
970833AG2-524 GEN
Solar/Wind Harmer
6.873
970833AG2-524 GEN
Solar/Wind Harmer
4.582
274744AC1-111 GEN8
Adder
4.918
274746AC1-111 G10
Adder
4.918
970073AG2-061 GEN
Solar/Wind Harmer
2.039
971411AH1-196 GEN
Solar/Wind Harmer
8.695
971675AH1-338 GEN
Solar/Wind Harmer
2.248
276861AD2-134 GEN
Solar/Wind Harmer
0.103
276863AD2-134 GEN
Solar/Wind Harmer
0.103
971171AH1-044 GEN
Solar/Wind Harmer
11.406
274823ROCKFORD ;21
Adder
15.875
274856ECOGROVE ;U1
Solar/Wind Harmer
0.131
971681AH1-341 GEN
Solar/Wind Harmer
8.893
926823AC1-168 GEN
Solar/Wind Harmer
0.925
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.206
276741O09 GEN1
Solar/Wind Harmer
0.187
970169AG2-114 GEN
Solar/Wind Harmer
5.156
274877BISHOP HL;1U
Solar/Wind Harmer
0.171
946321AF1-296 GEN
Solar/Wind Harmer
2.836
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.798
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.14
276848AB2-070 GEN3
Solar/Wind Harmer
0.139
276849AB2-070 GEN2
Solar/Wind Harmer
0.14
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Helper
0.812
274814UNIV PK N;0U
50/50
7.733
274807UNIV PK N;3U
50/50
7.717
274811UNIV PK N;7U
50/50
7.666
274803UNIV PARK;6U
50/50
6.752
972038AH1-567 GEN2
50/50
0.364
274654BRAIDWOOD;1U
50/50
3.559
274826FISK ;BP
50/50
10.736
274887GEN-1.85
Solar/Wind Harmer
0.169
276843GEN-1.7
Solar/Wind Harmer
0.21
276806AD2-047 C O1
Solar/Wind Harmer
3.683
274676JOLIET 29;8U
Adder
27.237
972259AH1-714 GEN
Adder
17.519
274729ELWOOD EC;1P
Adder
15.005
274730ELWOOD EC;6P
Adder
14.998
274734ELWOOD EC;8P
Adder
14.998
274736ELWOOD EC;9P
Adder
14.998
970707AG2-453 GEN
Solar/Wind Harmer
20.582
274772LINCOLN ;3U
Adder
7.591
939351AE1-166 GEN
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.266
943591AF1-030 GEN
Solar/Wind Harmer
6.827
274682WAUKEGAN ;7U
Adder
15.585
274724RIVER EC ;11
Adder
15.135
274862TOP CROP ;2U
Solar/Wind Harmer
0.801
276868AE1-113 GEN
Solar/Wind Harmer
1.168
274879MINONK ;1U
Solar/Wind Harmer
0.244
946671AF1-331 GEN
Solar/Wind Harmer
0.615
274855GSG-6 ;RU
Solar/Wind Harmer
0.21
274850MENDOTA H;RU
Solar/Wind Harmer
0.067
959091AF2-200 GEN
Solar/Wind Harmer
11.406
970571AG2-364 GEN
Solar/Wind Harmer
11.046
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
7.313
274767LEE CO EC;8U
Adder
7.227
274752CRETE EC ;2U
Adder
6.146
274753CRETE EC ;3U
Adder
6.146
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.171
965931AG1-462 GEN
Solar/Wind Harmer
12.768
971087AG2-675 GEN
Solar/Wind Harmer
2.671
965091AG1-374 GEN
Solar/Wind Harmer
13.052
959611AF2-252 GEN
Solar/Wind Harmer
1.45
971993AH1-541 GEN
Solar/Wind Harmer
1.644
957381AF2-032 GEN
Solar/Wind Harmer
0.699
942481AE2-261 GEN
Solar/Wind Harmer
9.113
274806UNIV PK N;2U
50/50
0.428
274810UNIV PK N;6U
50/50
0.419
274812UNIV PK N;8U
50/50
7.666
274802UNIV PARK;5U
50/50
6.752
274676JOLIET 29;8U
Adder
28.246
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.035
274732ELWOOD EC;7P
Adder
14.998
274674JOLIET 9 ;6U
Adder
14.03
274773LINCOLN ;4U
Adder
7.591
274774LINCOLN ;5U
Adder
7.591
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
4.918
274723RIVER EC ;12
Adder
15.724
276805AD2-038 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
15.585
274828WAUKEGAN ;BP
Adder
9.556
274861TOP CROP ;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.612
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.681
971997AH1-543 GEN
Solar/Wind Harmer
3.004
957471AF2-041 GEN
Solar/Wind Harmer
17.109
959081AF2-199 GEN
Solar/Wind Harmer
5.703
971067AG2-660 GEN
Solar/Wind Harmer
1.901
274822ROCKFORD ;11
Adder
15.991
970819AG2-516 GEN
Solar/Wind Harmer
6.747
939401AE1-172 GEN
Solar/Wind Harmer
4.193
970569AG2-363 GEN
Solar/Wind Harmer
16.569
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.313
274766LEE CO EC;7U
Adder
7.227
276708O09 GEN2
Solar/Wind Harmer
0.187
274751CRETE EC ;1U
Adder
6.146
274754CRETE EC ;4U
Adder
6.146
276646AC1-214 GEN2
Solar/Wind Harmer
0.203
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.397
276621W2-048 GEN
Solar/Wind Harmer
0.17
965911AG1-460 GEN
Solar/Wind Harmer
0.61
990577J1339
External Queue
13.026387214660645
991777J1629 G
External Queue
9.474555015563965
991247J1684 G
External Queue
11.299722671508789
990582J1340
External Queue
13.026387214660645
990512J1326
External Queue
4.175074577331543
990117J1214
External Queue
14.362256050109863
990727J1377 G
External Queue
4.8513665199279785
990552J1334 G
External Queue
9.516560554504395
990562J1336 G
External Queue
9.516560554504395
990762J1386
External Queue
10.741265296936035
990547J1333 G
External Queue
9.516560554504395
990557J1335 G
External Queue
9.516560554504395
991303J1755 G
External Queue
3.606649398803711
990407J1304
External Queue
3.230916738510132
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
0.728
WECLTFEXP_WEC->PJM
CLTF
3.106
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.687
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.181
MECLTFEXP_MEC->PJM
CLTF
9.677
SIGELTFEXP_SIGE->PJM
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.287
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.317
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.886
LAGNLTFEXP_LAGN->PJM
CLTF
3.217
TVALTFEXP_TVA->PJM
CLTF
0.831

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.37 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1081.39
MW Contribution:
8.89
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1023.77
MW Contribution:
8.63
Bus #Bus NameTypeMW Contribution
274814UNIV PK N;0U
50/50
7.733
274807UNIV PK N;3U
50/50
7.717
274811UNIV PK N;7U
50/50
7.666
274803UNIV PARK;6U
50/50
6.752
972038AH1-567 GEN2
50/50
0.364
274654BRAIDWOOD;1U
50/50
3.559
274826FISK ;BP
50/50
10.736
274887GEN-1.85
Solar/Wind Harmer
0.169
276843GEN-1.7
Solar/Wind Harmer
0.21
276806AD2-047 C O1
Solar/Wind Harmer
3.683
274676JOLIET 29;8U
Adder
27.237
972259AH1-714 GEN
Adder
17.519
274729ELWOOD EC;1P
Adder
15.005
274815UNIV PK N;XU
50/50
0.421
274813UNIV PK N;9U
50/50
0.42
274816UNIV PK N;YU
50/50
0.42
274809UNIV PK N;5U
50/50
0.418
274805UNIV PK N;1U
50/50
7.683
274808UNIV PK N;4U
50/50
7.633
274798UNIV PARK;1U
50/50
0.253
274888KELLY CRK;1U
Solar/Wind Harmer
0.379
276776AD2-060 GEN
Solar/Wind Harmer
0.693
958011AF2-095 GEN
Solar/Wind Harmer
9.359
970941AG2-585 GEN
Solar/Wind Harmer
3.575
958481AF2-142 GEN
Solar/Wind Harmer
9.558
276893AG1-478 C
Solar/Wind Harmer
0.424
274674JOLIET 9 ;6U
Adder
14.03
274770LINCOLN ;1U
Adder
7.591
274771LINCOLN ;2U
Adder
7.591
276897AD1-100 C
Solar/Wind Harmer
15.631
958491AF2-143 GEN
Solar/Wind Harmer
9.176
274683WAUKEGAN ;8U
Adder
18.229
274683WAUKEGAN ;8U
Adder
15.367
274695ROCKY RD ;2P
Adder
9.621
274693ROCKY RD ;1P
Adder
9.526
274697ROCKY RD ;3P
Adder
2.614
274696ROCKY RD ;4P
Adder
9.848
962691AG1-118 GEN
Solar/Wind Harmer
17.774
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
11.406
971343AH1-151 GEN
Solar/Wind Harmer
11.406
972235AH1-702 GEN1
Adder
2.043
972236AH1-702 GEN2
Adder
1.777
938861AE1-114 GEN
Solar/Wind Harmer
3.13
274764LEE CO EC;5U
Adder
7.33
274765LEE CO EC;6U
Adder
7.33
274762LEE CO EC;3U
Adder
7.313
274763LEE CO EC;4U
Adder
7.244
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.856
276645AC1-214 GEN1
Solar/Wind Harmer
0.203
942111AE2-223 GEN
Solar/Wind Harmer
1.485
960611AF2-352 GEN
Solar/Wind Harmer
1.45
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.191
274730ELWOOD EC;6P
Adder
14.998
274734ELWOOD EC;8P
Adder
14.998
274736ELWOOD EC;9P
Adder
14.998
970707AG2-453 GEN
Solar/Wind Harmer
20.582
274772LINCOLN ;3U
Adder
7.591
939351AE1-166 GEN
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.266
943591AF1-030 GEN
Solar/Wind Harmer
6.827
274682WAUKEGAN ;7U
Adder
15.585
274724RIVER EC ;11
Adder
15.135
274862TOP CROP ;2U
Solar/Wind Harmer
0.801
276868AE1-113 GEN
Solar/Wind Harmer
1.168
274879MINONK ;1U
Solar/Wind Harmer
0.244
946671AF1-331 GEN
Solar/Wind Harmer
0.615
274855GSG-6 ;RU
Solar/Wind Harmer
0.21
274850MENDOTA H;RU
Solar/Wind Harmer
0.067
959091AF2-200 GEN
Solar/Wind Harmer
11.406
970571AG2-364 GEN
Solar/Wind Harmer
11.046
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
7.313
274767LEE CO EC;8U
Adder
7.227
274752CRETE EC ;2U
Adder
6.146
274753CRETE EC ;3U
Adder
6.146
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.171
965931AG1-462 GEN
Solar/Wind Harmer
12.768
971087AG2-675 GEN
Solar/Wind Harmer
2.671
965091AG1-374 GEN
Solar/Wind Harmer
13.052
959611AF2-252 GEN
Solar/Wind Harmer
1.45
971993AH1-541 GEN
Solar/Wind Harmer
1.644
957381AF2-032 GEN
Solar/Wind Harmer
0.699
942481AE2-261 GEN
Solar/Wind Harmer
9.113
274806UNIV PK N;2U
50/50
0.428
274810UNIV PK N;6U
50/50
0.419
274812UNIV PK N;8U
50/50
7.666
274802UNIV PARK;5U
50/50
6.752
274676JOLIET 29;8U
Adder
28.246
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.035
274732ELWOOD EC;7P
Adder
14.998
274674JOLIET 9 ;6U
Adder
14.03
274773LINCOLN ;4U
Adder
7.591
274774LINCOLN ;5U
Adder
7.591
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
4.918
274723RIVER EC ;12
Adder
15.724
276805AD2-038 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
15.585
274828WAUKEGAN ;BP
Adder
9.556
274861TOP CROP ;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.612
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.681
971997AH1-543 GEN
Solar/Wind Harmer
3.004
957471AF2-041 GEN
Solar/Wind Harmer
17.109
959081AF2-199 GEN
Solar/Wind Harmer
5.703
971067AG2-660 GEN
Solar/Wind Harmer
1.901
274822ROCKFORD ;11
Adder
15.991
970819AG2-516 GEN
Solar/Wind Harmer
6.747
939401AE1-172 GEN
Solar/Wind Harmer
4.193
970569AG2-363 GEN
Solar/Wind Harmer
16.569
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.313
274766LEE CO EC;7U
Adder
7.227
276708O09 GEN2
Solar/Wind Harmer
0.187
274751CRETE EC ;1U
Adder
6.146
274754CRETE EC ;4U
Adder
6.146
276646AC1-214 GEN2
Solar/Wind Harmer
0.203
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.397
276621W2-048 GEN
Solar/Wind Harmer
0.17
965911AG1-460 GEN
Solar/Wind Harmer
0.61
972037AH1-567 GEN1
50/50
0.212
274799UNIV PARK;2U
50/50
0.261
274800UNIV PARK;3U
50/50
5.818
274801UNIV PARK;4U
50/50
5.818
274655BRAIDWOOD;2U
50/50
3.459
972228AH1-698 GEN2
50/50
3.695
972227AH1-698 GEN1
50/50
2.598
274827FISK ;RP
50/50
7.609
960591AF2-350 GEN
Solar/Wind Harmer
6.499
274675JOLIET 29;7U
Adder
28.252
274675JOLIET 29;7U
Adder
27.243
274731ELWOOD EC;2P
Adder
15.005
274733ELWOOD EC;3P
Adder
15.005
274735ELWOOD EC;4P
Adder
15.005
274728ELWOOD EC;5P
Adder
14.998
274687WILL CNTY;4U
Adder
25.433
274687WILL CNTY;4U
Adder
25.433
274775LINCOLN ;6U
Adder
7.591
274776LINCOLN ;7U
Adder
7.591
274777LINCOLN ;8U
Adder
7.591
970833AG2-524 GEN
Solar/Wind Harmer
6.873
970833AG2-524 GEN
Solar/Wind Harmer
4.582
274744AC1-111 GEN8
Adder
4.918
274746AC1-111 G10
Adder
4.918
970073AG2-061 GEN
Solar/Wind Harmer
2.039
971411AH1-196 GEN
Solar/Wind Harmer
8.695
971675AH1-338 GEN
Solar/Wind Harmer
2.248
276861AD2-134 GEN
Solar/Wind Harmer
0.103
276863AD2-134 GEN
Solar/Wind Harmer
0.103
971171AH1-044 GEN
Solar/Wind Harmer
11.406
274823ROCKFORD ;21
Adder
15.875
274856ECOGROVE ;U1
Solar/Wind Harmer
0.131
971681AH1-341 GEN
Solar/Wind Harmer
8.893
926823AC1-168 GEN
Solar/Wind Harmer
0.925
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.206
276741O09 GEN1
Solar/Wind Harmer
0.187
970169AG2-114 GEN
Solar/Wind Harmer
5.156
274877BISHOP HL;1U
Solar/Wind Harmer
0.171
946321AF1-296 GEN
Solar/Wind Harmer
2.836
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.798
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.14
276848AB2-070 GEN3
Solar/Wind Harmer
0.139
276849AB2-070 GEN2
Solar/Wind Harmer
0.14
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Helper
0.812
990577J1339
External Queue
13.026387214660645
991777J1629 G
External Queue
9.474555015563965
991247J1684 G
External Queue
11.299722671508789
990582J1340
External Queue
13.026387214660645
990512J1326
External Queue
4.175074577331543
990117J1214
External Queue
14.362256050109863
990727J1377 G
External Queue
4.8513665199279785
990552J1334 G
External Queue
9.516560554504395
990562J1336 G
External Queue
9.516560554504395
990762J1386
External Queue
10.741265296936035
990547J1333 G
External Queue
9.516560554504395
990557J1335 G
External Queue
9.516560554504395
991303J1755 G
External Queue
3.606649398803711
990407J1304
External Queue
3.230916738510132
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
0.728
WECLTFEXP_WEC->PJM
CLTF
3.106
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.687
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.181
MECLTFEXP_MEC->PJM
CLTF
9.677
SIGELTFEXP_SIGE->PJM
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.287
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.317
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.886
LAGNLTFEXP_LAGN->PJM
CLTF
3.217
TVALTFEXP_TVA->PJM
CLTF
0.831

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2973_05DUMONT 345_F1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.51 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:985.66
MW Contribution:
8.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
274806UNIV PK N;2U
50/50
0.379
274815UNIV PK N;XU
50/50
0.372
274813UNIV PK N;9U
50/50
0.372
274816UNIV PK N;YU
50/50
0.372
274809UNIV PK N;5U
50/50
0.37
274805UNIV PK N;1U
50/50
6.796
274808UNIV PK N;4U
50/50
6.752
274888KELLY CRK;1U
Solar/Wind Harmer
4.216
276776AD2-060 GEN
Solar/Wind Harmer
0.299
970941AG2-585 GEN
Solar/Wind Harmer
3.929
958011AF2-095 GEN
Solar/Wind Harmer
10.287
958481AF2-142 GEN
Solar/Wind Harmer
10.482
276893AG1-478 C
Solar/Wind Harmer
0.3
274674JOLIET 9 ;6U
Adder
10.41
958491AF2-143 GEN
Solar/Wind Harmer
9.955
276897AD1-100 C
Solar/Wind Harmer
29.223
274683WAUKEGAN ;8U
Adder
13.066
274683WAUKEGAN ;8U
Adder
11.014
276872AE1-163_GEN1
Solar/Wind Harmer
4.13
276876AE1-163_GEN2
Solar/Wind Harmer
4.13
276901AD2-066 C O1
Solar/Wind Harmer
2.152
274696ROCKY RD ;4P
Adder
6.94
274695ROCKY RD ;2P
Adder
6.78
274693ROCKY RD ;1P
Adder
6.713
274697ROCKY RD ;3P
Adder
1.842
962691AG1-118 GEN
Solar/Wind Harmer
17.761
960751AF2-366 GEN
Solar/Wind Harmer
1.691
971341AH1-150 GEN
Solar/Wind Harmer
11.498
971343AH1-151 GEN
Solar/Wind Harmer
11.498
972235AH1-702 GEN1
Adder
1.444
972236AH1-702 GEN2
Adder
1.256
938861AE1-114 GEN
Solar/Wind Harmer
4.587
274764LEE CO EC;5U
Adder
5.182
274765LEE CO EC;6U
Adder
5.182
274762LEE CO EC;3U
Adder
5.17
274763LEE CO EC;4U
Adder
5.121
276158O29GEN2
Solar/Wind Harmer
2.702
276157O29GEN1
Solar/Wind Harmer
2.054
276645AC1-214 GEN1
Solar/Wind Harmer
0.712
274770LINCOLN ;1U
Adder
3.27
274771LINCOLN ;2U
Adder
3.27
942111AE2-223 GEN
Solar/Wind Harmer
3.725
960611AF2-352 GEN
Solar/Wind Harmer
1.007
274810UNIV PK N;6U
50/50
0.371
274812UNIV PK N;8U
50/50
6.781
274802UNIV PARK;5U
50/50
5.544
274723RIVER EC ;12
Adder
13.64
276694AA1-018 GEN2
Solar/Wind Harmer
4.409
276691AA1-018 GEN1
Solar/Wind Harmer
0.527
274676JOLIET 29;8U
Adder
21.056
274732ELWOOD EC;7P
Adder
11.147
274674JOLIET 9 ;6U
Adder
10.41
276805AD2-038 GEN
Solar/Wind Harmer
3.403
274861TOP CROP ;1U
Solar/Wind Harmer
3.86
274871GR RIDGE ;2U
Solar/Wind Harmer
4.845
274847GR RIDGE ;BU
Solar/Wind Harmer
3.186
941551AE2-152 GEN
Solar/Wind Harmer
2.853
274682WAUKEGAN ;7U
Adder
11.173
274828WAUKEGAN ;BP
Adder
6.849
274751CRETE EC ;1U
Adder
3.025
274754CRETE EC ;4U
Adder
3.025
276882AE2-255 GEN
Solar/Wind Harmer
2.074
274745AC1-111 GEN9
Adder
3.429
962781AG1-127 GEN
Solar/Wind Harmer
5.606
274872LEEDK;1U
Solar/Wind Harmer
4.817
971997AH1-543 GEN
Solar/Wind Harmer
9.169
970569AG2-363 GEN
Solar/Wind Harmer
17.447
274822ROCKFORD ;11
Adder
11.305
957471AF2-041 GEN
Solar/Wind Harmer
17.247
959081AF2-199 GEN
Solar/Wind Harmer
5.749
971067AG2-660 GEN
Solar/Wind Harmer
1.337
970819AG2-516 GEN
Solar/Wind Harmer
6.841
274858EASY ROAD;U2
Solar/Wind Harmer
2.662
274761LEE CO EC;2U
Adder
5.17
274766LEE CO EC;7U
Adder
5.109
939401AE1-172 GEN
Solar/Wind Harmer
7.681
276708O09 GEN2
Solar/Wind Harmer
1.929
276646AC1-214 GEN2
Solar/Wind Harmer
0.712
972207SS24-0001
Solar/Wind Harmer
11.626
274773LINCOLN ;4U
Adder
3.27
274774LINCOLN ;5U
Adder
3.27
274848CAMPGROVE;RU
Solar/Wind Harmer
3.36
276655WTG1_EQ
Solar/Wind Harmer
3.966
276656WTG2_EQ
Solar/Wind Harmer
0.525
939741AE1-205 GEN
Solar/Wind Harmer
9.089
972037AH1-567 GEN1
50/50
0.174
274800UNIV PARK;3U
Adder
4.316
274801UNIV PARK;4U
Adder
4.316
274827FISK ;RP
Adder
5.652
960591AF2-350 GEN
Solar/Wind Harmer
7.144
972228AH1-698 GEN2
Adder
2.582
972227AH1-698 GEN1
Adder
1.814
274675JOLIET 29;7U
Adder
21.061
274675JOLIET 29;7U
Adder
20.308
276893AG1-478 C
Solar/Wind Harmer
0.377
274687WILL CNTY;4U
Adder
19.129
274687WILL CNTY;4U
Adder
19.129
274731ELWOOD EC;2P
Adder
11.151
274733ELWOOD EC;3P
Adder
11.151
274735ELWOOD EC;4P
Adder
11.151
274728ELWOOD EC;5P
Adder
11.147
970073AG2-061 GEN
Solar/Wind Harmer
1.543
970833AG2-524 GEN
Solar/Wind Harmer
5.536
970833AG2-524 GEN
Solar/Wind Harmer
2.575
276889AE2-281 GEN
Solar/Wind Harmer
1.18
274744AC1-111 GEN8
Adder
3.429
274746AC1-111 G10
Adder
3.429
971411AH1-196 GEN
Solar/Wind Harmer
8.816
971675AH1-338 GEN
Solar/Wind Harmer
10.405
276861AD2-134 GEN
Solar/Wind Harmer
1.032
276863AD2-134 GEN
Solar/Wind Harmer
1.032
274823ROCKFORD ;21
Adder
11.223
971171AH1-044 GEN
Solar/Wind Harmer
11.498
274856ECOGROVE ;U1
Solar/Wind Harmer
1.914
276611AD2-172 GEN
Solar/Wind Harmer
1.452
276612AE2-035 GEN
Solar/Wind Harmer
1.452
971681AH1-341 GEN
Solar/Wind Harmer
8.388
926823AC1-168 GEN
Solar/Wind Harmer
2.397
972267AH1-718 GEN
Adder
2.267
276741O09 GEN1
Solar/Wind Harmer
1.929
274863CRW1-WTG
Solar/Wind Harmer
2.958
274864CRW2-WTG
Solar/Wind Harmer
2.958
274775LINCOLN ;6U
Adder
3.27
274776LINCOLN ;7U
Adder
3.27
274777LINCOLN ;8U
Adder
3.27
274877BISHOP HL;1U
Solar/Wind Harmer
1.776
946321AF1-296 GEN
Solar/Wind Harmer
5.373
970169AG2-114 GEN
Solar/Wind Harmer
5.123
276726Z2-087_GEN
Solar/Wind Harmer
3.593
959341AF2-225 GEN
Solar/Wind Harmer
6.817
274853TWINGROVE;U1
Solar/Wind Harmer
3.121
274854TWINGROVE;U2
Solar/Wind Harmer
3.056
960681AF2-359 GEN
Solar/Wind Helper
0.839
274814UNIV PK N;0U
50/50
6.841
274807UNIV PK N;3U
50/50
6.826
274811UNIV PK N;7U
50/50
6.781
274803UNIV PARK;6U
50/50
5.544
274724RIVER EC ;11
Adder
13.111
972038AH1-567 GEN2
Adder
0.27
276164X3-005 C
Solar/Wind Harmer
0.513
274826FISK ;BP
Adder
7.975
274887GEN-1.85
Solar/Wind Harmer
3.806
276772AC2-154 GEN
Solar/Wind Harmer
1.994
276843GEN-1.7
Solar/Wind Harmer
0.41
276806AD2-047 C O1
Solar/Wind Harmer
7.643
274676JOLIET 29;8U
Adder
20.304
274729ELWOOD EC;1P
Adder
11.151
274730ELWOOD EC;6P
Adder
11.147
274734ELWOOD EC;8P
Adder
11.147
274736ELWOOD EC;9P
Adder
11.147
972259AH1-714 GEN
Adder
12.285
274862TOP CROP ;2U
Solar/Wind Harmer
3.223
939351AE1-166 GEN
Solar/Wind Harmer
3.731
274682WAUKEGAN ;7U
Adder
11.173
972231SS25-0005
Solar/Wind Harmer
5.874
972181SS23-001
Solar/Wind Harmer
3.671
274752CRETE EC ;2U
Adder
3.025
274753CRETE EC ;3U
Adder
3.025
276868AE1-113 GEN
Solar/Wind Harmer
6.221
274879MINONK ;1U
Solar/Wind Harmer
4.148
943121AE2-341 GEN
Solar/Wind Harmer
8.999
943591AF1-030 GEN
Solar/Wind Harmer
5.999
970707AG2-453 GEN
Solar/Wind Harmer
16.654
970571AG2-364 GEN
Solar/Wind Harmer
11.631
276799AD1-013 GEN
Solar/Wind Harmer
1.278
946671AF1-331 GEN
Solar/Wind Harmer
0.242
274855GSG-6 ;RU
Solar/Wind Harmer
2.133
274850MENDOTA H;RU
Solar/Wind Harmer
1.483
276602WESTBROOK C
Solar/Wind Harmer
1.228
959091AF2-200 GEN
Solar/Wind Harmer
11.498
274857EASY ROAD;U1
Solar/Wind Harmer
2.662
274760LEE CO EC;1U
Adder
5.17
274767LEE CO EC;8U
Adder
5.109
276603SUBLETTE C
Solar/Wind Harmer
0.58
274851PROVIDENC;RU
Solar/Wind Harmer
1.514
274849CRESCENT ;1U
Solar/Wind Harmer
0.983
274772LINCOLN ;3U
Adder
3.27
276782AC1-033 GEN
Solar/Wind Harmer
2.1
274878BISHOP HL;2U
Solar/Wind Harmer
1.776
965931AG1-462 GEN
Solar/Wind Harmer
12.992
971087AG2-675 GEN
Solar/Wind Harmer
1.896
965091AG1-374 GEN
Solar/Wind Harmer
12.996
959611AF2-252 GEN
Solar/Wind Harmer
1.007
990577J1339
External Queue
15.399553298950195
991247J1684 G
External Queue
14.467473983764648
990582J1340
External Queue
15.399553298950195
990552J1334 G
External Queue
13.463057518005371
990562J1336 G
External Queue
13.463057518005371
990762J1386
External Queue
11.34267807006836
990547J1333 G
External Queue
13.463057518005371
990557J1335 G
External Queue
13.463057518005371
NYPJM->LTFIMP_NY
CLTF
0.509
WECLTFEXP_WEC->PJM
CLTF
2.219
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.188
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.09
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.566
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.615
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.705
MECLTFEXP_MEC->PJM
CLTF
6.893
SIGELTFEXP_SIGE->PJM
CLTF
0.01
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.176
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.207
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.574
LAGNLTFEXP_LAGN->PJM
CLTF
2.317
TVALTFEXP_TVA->PJM
CLTF
0.608

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#8805_05OLIVE 345_D_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8805_05OLIVE 345_D_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.08 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:981.49
MW Contribution:
8.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8805_05OLIVE 345_D_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.48 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:975.67
MW Contribution:
8.42
Bus #Bus NameTypeMW Contribution
274815UNIV PK N;XU
50/50
0.366
274813UNIV PK N;9U
50/50
0.365
274816UNIV PK N;YU
50/50
0.365
274809UNIV PK N;5U
50/50
0.363
274805UNIV PK N;1U
50/50
6.67
274808UNIV PK N;4U
50/50
6.626
965681AG1-436 GEN
Solar/Wind Harmer
10.573
965791AG1-447 GEN
Solar/Wind Harmer
5.409
276776AD2-060 GEN
Solar/Wind Harmer
0.293
274888KELLY CRK;1U
Solar/Wind Harmer
4.134
958011AF2-095 GEN
Solar/Wind Harmer
10.089
970941AG2-585 GEN
Solar/Wind Harmer
3.853
958481AF2-142 GEN
Solar/Wind Harmer
10.407
276893AG1-478 C
Solar/Wind Harmer
0.298
274674JOLIET 9 ;6U
Adder
10.305
958491AF2-143 GEN
Solar/Wind Harmer
9.912
276897AD1-100 C
Solar/Wind Harmer
29.133
274683WAUKEGAN ;8U
Adder
13.078
274683WAUKEGAN ;8U
Adder
11.024
276872AE1-163_GEN1
Solar/Wind Harmer
4.13
276876AE1-163_GEN2
Solar/Wind Harmer
4.13
276901AD2-066 C O1
Solar/Wind Harmer
2.151
274696ROCKY RD ;4P
Adder
6.944
274695ROCKY RD ;2P
Adder
6.783
274693ROCKY RD ;1P
Adder
6.717
274697ROCKY RD ;3P
Adder
1.843
962691AG1-118 GEN
Solar/Wind Harmer
17.767
960751AF2-366 GEN
Solar/Wind Harmer
1.692
971341AH1-150 GEN
Solar/Wind Harmer
11.512
971343AH1-151 GEN
Solar/Wind Harmer
11.512
972235AH1-702 GEN1
Adder
1.446
972236AH1-702 GEN2
Adder
1.257
938861AE1-114 GEN
Solar/Wind Harmer
4.595
274764LEE CO EC;5U
Adder
5.192
274765LEE CO EC;6U
Adder
5.192
274762LEE CO EC;3U
Adder
5.18
274763LEE CO EC;4U
Adder
5.131
276158O29GEN2
Solar/Wind Harmer
2.709
276157O29GEN1
Solar/Wind Harmer
2.059
276645AC1-214 GEN1
Solar/Wind Harmer
0.714
274770LINCOLN ;1U
Adder
3.222
274771LINCOLN ;2U
Adder
3.222
942111AE2-223 GEN
Solar/Wind Harmer
3.741
960611AF2-352 GEN
Solar/Wind Harmer
1.013
270535AF1-215 GEN1
Solar/Wind Helper
0.868
270536AF1-215 GEN2
Solar/Wind Helper
0.868
274814UNIV PK N;0U
50/50
6.713
274807UNIV PK N;3U
50/50
6.699
274811UNIV PK N;7U
50/50
6.655
274803UNIV PARK;6U
50/50
5.425
972231SS25-0005
Solar/Wind Harmer
7.527
972181SS23-001
Solar/Wind Harmer
4.704
274752CRETE EC ;2U
Adder
3.876
274753CRETE EC ;3U
Adder
3.876
972038AH1-567 GEN2
Adder
0.262
274826FISK ;BP
Adder
7.81
276772AC2-154 GEN
Solar/Wind Harmer
1.955
276806AD2-047 C O1
Solar/Wind Harmer
7.495
274887GEN-1.85
Solar/Wind Harmer
3.733
276843GEN-1.7
Solar/Wind Harmer
0.402
276164X3-005 C
Solar/Wind Harmer
0.484
274676JOLIET 29;8U
Adder
20.32
274729ELWOOD EC;1P
Adder
11.172
274730ELWOOD EC;6P
Adder
11.171
274734ELWOOD EC;8P
Adder
11.171
274736ELWOOD EC;9P
Adder
11.171
274724RIVER EC ;11
Adder
11.964
274862TOP CROP ;2U
Solar/Wind Harmer
3.27
972259AH1-714 GEN
Adder
12.327
939351AE1-166 GEN
Solar/Wind Harmer
3.719
274682WAUKEGAN ;7U
Adder
11.183
276868AE1-113 GEN
Solar/Wind Harmer
6.239
274879MINONK ;1U
Solar/Wind Harmer
4.16
943121AE2-341 GEN
Solar/Wind Harmer
8.994
943591AF1-030 GEN
Solar/Wind Harmer
5.996
970707AG2-453 GEN
Solar/Wind Harmer
16.678
970571AG2-364 GEN
Solar/Wind Harmer
11.674
276799AD1-013 GEN
Solar/Wind Harmer
1.279
946671AF1-331 GEN
Solar/Wind Harmer
0.242
274855GSG-6 ;RU
Solar/Wind Harmer
2.135
274850MENDOTA H;RU
Solar/Wind Harmer
1.484
276602WESTBROOK C
Solar/Wind Harmer
1.229
959091AF2-200 GEN
Solar/Wind Harmer
11.512
274857EASY ROAD;U1
Solar/Wind Harmer
2.667
274760LEE CO EC;1U
Adder
5.18
274767LEE CO EC;8U
Adder
5.119
276603SUBLETTE C
Solar/Wind Harmer
0.581
274851PROVIDENC;RU
Solar/Wind Harmer
1.519
274849CRESCENT ;1U
Solar/Wind Harmer
0.986
276782AC1-033 GEN
Solar/Wind Harmer
2.107
274878BISHOP HL;2U
Solar/Wind Harmer
1.783
274772LINCOLN ;3U
Adder
3.222
965931AG1-462 GEN
Solar/Wind Harmer
13.033
971087AG2-675 GEN
Solar/Wind Harmer
1.902
965091AG1-374 GEN
Solar/Wind Harmer
13.065
959611AF2-252 GEN
Solar/Wind Harmer
1.013
24441505OLIV SLR
Solar/Wind Helper
0.049
274806UNIV PK N;2U
50/50
0.372
274810UNIV PK N;6U
50/50
0.364
274812UNIV PK N;8U
50/50
6.655
274802UNIV PARK;5U
50/50
5.425
274751CRETE EC ;1U
Adder
3.876
274754CRETE EC ;4U
Adder
3.876
274723RIVER EC ;12
Adder
12.526
276694AA1-018 GEN2
Solar/Wind Harmer
4.378
276691AA1-018 GEN1
Solar/Wind Harmer
0.523
274676JOLIET 29;8U
Adder
21.073
274732ELWOOD EC;7P
Adder
11.171
274674JOLIET 9 ;6U
Adder
10.305
276805AD2-038 GEN
Solar/Wind Harmer
3.388
274861TOP CROP ;1U
Solar/Wind Harmer
3.916
274871GR RIDGE ;2U
Solar/Wind Harmer
4.857
274847GR RIDGE ;BU
Solar/Wind Harmer
3.194
941551AE2-152 GEN
Solar/Wind Harmer
2.844
274682WAUKEGAN ;7U
Adder
11.183
274828WAUKEGAN ;BP
Adder
6.855
276882AE2-255 GEN
Solar/Wind Harmer
2.08
274745AC1-111 GEN9
Adder
3.429
962781AG1-127 GEN
Solar/Wind Harmer
5.609
274872LEEDK;1U
Solar/Wind Harmer
4.819
970569AG2-363 GEN
Solar/Wind Harmer
17.51
971997AH1-543 GEN
Solar/Wind Harmer
9.184
274822ROCKFORD ;11
Adder
11.32
957471AF2-041 GEN
Solar/Wind Harmer
17.268
959081AF2-199 GEN
Solar/Wind Harmer
5.756
971067AG2-660 GEN
Solar/Wind Harmer
1.339
970819AG2-516 GEN
Solar/Wind Harmer
6.851
274858EASY ROAD;U2
Solar/Wind Harmer
2.667
274761LEE CO EC;2U
Adder
5.18
274766LEE CO EC;7U
Adder
5.119
939401AE1-172 GEN
Solar/Wind Harmer
7.667
276708O09 GEN2
Solar/Wind Harmer
1.934
276646AC1-214 GEN2
Solar/Wind Harmer
0.714
274848CAMPGROVE;RU
Solar/Wind Harmer
3.372
972207SS24-0001
Solar/Wind Harmer
11.456
274773LINCOLN ;4U
Adder
3.222
274774LINCOLN ;5U
Adder
3.222
276655WTG1_EQ
Solar/Wind Harmer
3.983
276656WTG2_EQ
Solar/Wind Harmer
0.527
939741AE1-205 GEN
Solar/Wind Harmer
9.127
270055AF2-134 C O1
Solar/Wind Helper
0.579
972037AH1-567 GEN1
50/50
0.17
960681AF2-359 GEN
Solar/Wind Harmer
3.196
274800UNIV PARK;3U
Adder
4.188
274801UNIV PARK;4U
Adder
4.188
274827FISK ;RP
Adder
5.535
972228AH1-698 GEN2
Adder
2.595
960591AF2-350 GEN
Solar/Wind Harmer
7.006
972227AH1-698 GEN1
Adder
1.824
274675JOLIET 29;7U
Adder
21.076
274675JOLIET 29;7U
Adder
20.323
274687WILL CNTY;4U
Adder
19.135
274687WILL CNTY;4U
Adder
19.135
274731ELWOOD EC;2P
Adder
11.172
274733ELWOOD EC;3P
Adder
11.172
274735ELWOOD EC;4P
Adder
11.172
274728ELWOOD EC;5P
Adder
11.171
276893AG1-478 C
Solar/Wind Harmer
0.374
970073AG2-061 GEN
Solar/Wind Harmer
1.537
970833AG2-524 GEN
Solar/Wind Harmer
5.543
970833AG2-524 GEN
Solar/Wind Harmer
2.578
276889AE2-281 GEN
Solar/Wind Harmer
1.18
274744AC1-111 GEN8
Adder
3.429
274746AC1-111 G10
Adder
3.429
971411AH1-196 GEN
Solar/Wind Harmer
8.827
971675AH1-338 GEN
Solar/Wind Harmer
10.413
276861AD2-134 GEN
Solar/Wind Harmer
1.032
276863AD2-134 GEN
Solar/Wind Harmer
1.032
274823ROCKFORD ;21
Adder
11.238
971171AH1-044 GEN
Solar/Wind Harmer
11.512
274856ECOGROVE ;U1
Solar/Wind Harmer
1.917
276611AD2-172 GEN
Solar/Wind Harmer
1.454
276612AE2-035 GEN
Solar/Wind Harmer
1.454
971681AH1-341 GEN
Solar/Wind Harmer
8.403
926823AC1-168 GEN
Solar/Wind Harmer
2.404
972267AH1-718 GEN
Adder
2.272
276741O09 GEN1
Solar/Wind Harmer
1.934
274863CRW1-WTG
Solar/Wind Harmer
2.957
274864CRW2-WTG
Solar/Wind Harmer
2.957
274877BISHOP HL;1U
Solar/Wind Harmer
1.783
274775LINCOLN ;6U
Adder
3.222
274776LINCOLN ;7U
Adder
3.222
274777LINCOLN ;8U
Adder
3.222
946321AF1-296 GEN
Solar/Wind Harmer
5.389
970169AG2-114 GEN
Solar/Wind Harmer
5.131
276726Z2-087_GEN
Solar/Wind Harmer
3.608
959341AF2-225 GEN
Solar/Wind Harmer
6.845
274853TWINGROVE;U1
Solar/Wind Harmer
3.138
274854TWINGROVE;U2
Solar/Wind Harmer
3.072
270526AF1-158 GEN
Solar/Wind Helper
0.826
990577J1339
External Queue
14.502150535583496
991247J1684 G
External Queue
12.47774600982666
990582J1340
External Queue
14.502150535583496
990552J1334 G
External Queue
10.390953063964844
990562J1336 G
External Queue
10.390953063964844
990762J1386
External Queue
11.055398941040039
990547J1333 G
External Queue
10.390953063964844
990557J1335 G
External Queue
10.390953063964844
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
0.513
WECLTFEXP_WEC->PJM
CLTF
2.223
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
33.177
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.209
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.833
MECLTFEXP_MEC->PJM
CLTF
6.934
SIGELTFEXP_SIGE->PJM
CLTF
0.013
AG2-052LTFEXP_AG2-052->PJM
LTF
0.06
AH1-155LTFEXP_AH1-155->PJM
LTF
0.09
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.18
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.491
LAGNLTFEXP_LAGN->PJM
CLTF
2.382
TVALTFEXP_TVA->PJM
CLTF
0.641

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.68 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2645.11
MW Contribution:
17.03
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.48 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2715.19
MW Contribution:
17.39
Bus #Bus NameTypeMW Contribution
274723RIVER EC ;12
50/50
31.279
972179AH1-673 GEN
50/50
16.189
274802UNIV PARK;5U
Adder
7.896
961501AF2-441 GEN
50/50
14.87
274827FISK ;RP
50/50
11.657
274800UNIV PARK;3U
Adder
8.227
274801UNIV PARK;4U
Adder
8.227
960591AF2-350 GEN
Solar/Wind Harmer
13.795
972037AH1-567 GEN1
Adder
0.248
274775LINCOLN ;6U
Adder
8.335
274776LINCOLN ;7U
Adder
8.335
274777LINCOLN ;8U
Adder
8.335
274687WILL CNTY;4U
Adder
37.095
274687WILL CNTY;4U
Adder
37.095
276893AG1-478 C
Solar/Wind Harmer
0.724
972228AH1-698 GEN2
Adder
4.85
972227AH1-698 GEN1
Adder
3.414
274675JOLIET 29;7U
Adder
40.153
274675JOLIET 29;7U
Adder
38.719
274728ELWOOD EC;5P
Adder
21.292
274731ELWOOD EC;2P
Adder
21.288
274733ELWOOD EC;3P
Adder
21.288
274735ELWOOD EC;4P
Adder
21.288
970833AG2-524 GEN
Solar/Wind Harmer
11.058
970833AG2-524 GEN
Solar/Wind Harmer
5.143
274744AC1-111 GEN8
Adder
7.025
274746AC1-111 G10
Adder
7.025
970073AG2-061 GEN
Solar/Wind Harmer
2.83
274888KELLY CRK;1U
Solar/Wind Harmer
8.14
276776AD2-060 GEN
Solar/Wind Harmer
0.577
958011AF2-095 GEN
Solar/Wind Harmer
19.865
970941AG2-585 GEN
Solar/Wind Harmer
7.587
274770LINCOLN ;1U
Adder
8.335
274771LINCOLN ;2U
Adder
8.335
274674JOLIET 9 ;6U
Adder
20.273
276893AG1-478 C
Solar/Wind Harmer
0.577
276897AD1-100 C
Solar/Wind Harmer
60.056
274805UNIV PK N;1U
Adder
6.378
274808UNIV PK N;4U
Adder
6.336
958481AF2-142 GEN
Solar/Wind Harmer
18.791
274683WAUKEGAN ;8U
Adder
26.064
274683WAUKEGAN ;8U
Adder
21.971
274695ROCKY RD ;2P
Adder
13.753
274693ROCKY RD ;1P
Adder
13.618
274697ROCKY RD ;3P
Adder
3.736
274696ROCKY RD ;4P
Adder
14.077
958491AF2-143 GEN
Solar/Wind Harmer
18.255
962691AG1-118 GEN
Solar/Wind Harmer
36.437
960751AF2-366 GEN
Solar/Wind Harmer
3.469
276901AD2-066 C O1
Solar/Wind Harmer
4.2
971341AH1-150 GEN
Solar/Wind Harmer
23.41
971343AH1-151 GEN
Solar/Wind Harmer
23.41
276872AE1-163_GEN1
Solar/Wind Harmer
7.84
276876AE1-163_GEN2
Solar/Wind Harmer
7.84
972235AH1-702 GEN1
Adder
2.927
972236AH1-702 GEN2
Adder
2.545
938861AE1-114 GEN
Solar/Wind Harmer
9.305
274764LEE CO EC;5U
Adder
10.512
274765LEE CO EC;6U
Adder
10.512
274762LEE CO EC;3U
Adder
10.487
274763LEE CO EC;4U
Adder
10.388
276158O29GEN2
Solar/Wind Harmer
5.469
276157O29GEN1
Solar/Wind Harmer
4.158
276645AC1-214 GEN1
Solar/Wind Harmer
1.428
942111AE2-223 GEN
Solar/Wind Harmer
7.882
960611AF2-352 GEN
Solar/Wind Harmer
2.135
274880W4-005 GEN4
Solar/Wind Harmer
2.304
276174W4-005 GEN2
Solar/Wind Harmer
2.304
971411AH1-196 GEN
Solar/Wind Harmer
17.838
971675AH1-338 GEN
Solar/Wind Harmer
21.293
276861AD2-134 GEN
Solar/Wind Harmer
2.111
276863AD2-134 GEN
Solar/Wind Harmer
2.111
971171AH1-044 GEN
Solar/Wind Harmer
23.41
276889AE2-281 GEN
Solar/Wind Harmer
2.24
274823ROCKFORD ;21
Adder
22.737
274856ECOGROVE ;U1
Solar/Wind Harmer
3.879
276611AD2-172 GEN
Solar/Wind Harmer
2.942
276612AE2-035 GEN
Solar/Wind Harmer
2.942
971681AH1-341 GEN
Solar/Wind Harmer
17.026
274863CRW1-WTG
Solar/Wind Harmer
6.264
274864CRW2-WTG
Solar/Wind Harmer
6.264
926823AC1-168 GEN
Solar/Wind Harmer
4.798
972267AH1-718 GEN
Adder
4.601
276741O09 GEN1
Solar/Wind Harmer
3.905
970169AG2-114 GEN
Solar/Wind Harmer
10.739
274877BISHOP HL;1U
Solar/Wind Harmer
3.57
946321AF1-296 GEN
Solar/Wind Harmer
10.891
276726Z2-087_GEN
Solar/Wind Harmer
7.603
959341AF2-225 GEN
Solar/Wind Harmer
14.423
274853TWINGROVE;U1
Solar/Wind Harmer
6.613
274854TWINGROVE;U2
Solar/Wind Harmer
6.475
274724RIVER EC ;11
50/50
31.325
957371AF2-031 GEN
50/50
1.551
274826FISK ;BP
50/50
16.449
276164X3-005 C
Solar/Wind Harmer
1.084
972038AH1-567 GEN2
Adder
0.515
274887GEN-1.85
Solar/Wind Harmer
7.35
276772AC2-154 GEN
Solar/Wind Harmer
3.85
276843GEN-1.7
Solar/Wind Harmer
0.791
276806AD2-047 C O1
Solar/Wind Harmer
14.757
274803UNIV PARK;6U
Adder
7.896
274772LINCOLN ;3U
Adder
8.335
274676JOLIET 29;8U
Adder
38.718
274730ELWOOD EC;6P
Adder
21.292
274734ELWOOD EC;8P
Adder
21.292
274736ELWOOD EC;9P
Adder
21.292
274729ELWOOD EC;1P
Adder
21.288
939351AE1-166 GEN
Solar/Wind Harmer
7.667
972259AH1-714 GEN
Adder
24.662
970707AG2-453 GEN
Solar/Wind Harmer
35.929
274814UNIV PK N;0U
Adder
6.42
274807UNIV PK N;3U
Adder
6.406
274811UNIV PK N;7U
Adder
6.364
943121AE2-341 GEN
Solar/Wind Harmer
18.811
943591AF1-030 GEN
Solar/Wind Harmer
12.541
274862TOP CROP ;2U
Solar/Wind Harmer
6.315
274682WAUKEGAN ;7U
Adder
22.282
972231SS25-0005
Solar/Wind Harmer
11.472
972181SS23-001
Solar/Wind Harmer
7.17
274752CRETE EC ;2U
Adder
5.909
274753CRETE EC ;3U
Adder
5.909
276868AE1-113 GEN
Solar/Wind Harmer
12.102
274879MINONK ;1U
Solar/Wind Harmer
8.069
276799AD1-013 GEN
Solar/Wind Harmer
2.616
946671AF1-331 GEN
Solar/Wind Harmer
0.496
274855GSG-6 ;RU
Solar/Wind Harmer
4.365
274850MENDOTA H;RU
Solar/Wind Harmer
3.035
276602WESTBROOK C
Solar/Wind Harmer
2.513
959091AF2-200 GEN
Solar/Wind Harmer
23.41
970571AG2-364 GEN
Solar/Wind Harmer
22.668
274857EASY ROAD;U1
Solar/Wind Harmer
5.4
274760LEE CO EC;1U
Adder
10.487
274767LEE CO EC;8U
Adder
10.364
276603SUBLETTE C
Solar/Wind Harmer
1.177
274851PROVIDENC;RU
Solar/Wind Harmer
3.037
274849CRESCENT ;1U
Solar/Wind Harmer
1.972
276782AC1-033 GEN
Solar/Wind Harmer
4.219
274878BISHOP HL;2U
Solar/Wind Harmer
3.57
965931AG1-462 GEN
Solar/Wind Harmer
26.334
971087AG2-675 GEN
Solar/Wind Harmer
3.843
965091AG1-374 GEN
Solar/Wind Harmer
27.538
959611AF2-252 GEN
Solar/Wind Harmer
2.135
276785W4-005 GEN1
Solar/Wind Harmer
2.304
971993AH1-541 GEN
Solar/Wind Harmer
4.08
972207SS24-0001
Solar/Wind Harmer
29.635
274773LINCOLN ;4U
Adder
8.335
274774LINCOLN ;5U
Adder
8.335
274674JOLIET 9 ;6U
Adder
20.273
274676JOLIET 29;8U
Adder
40.152
274732ELWOOD EC;7P
Adder
21.292
941551AE2-152 GEN
Solar/Wind Harmer
5.863
274812UNIV PK N;8U
Adder
6.364
274871GR RIDGE ;2U
Solar/Wind Harmer
9.705
274847GR RIDGE ;BU
Solar/Wind Harmer
6.381
274745AC1-111 GEN9
Adder
7.025
276694AA1-018 GEN2
Solar/Wind Harmer
7.904
276691AA1-018 GEN1
Solar/Wind Harmer
0.945
274861TOP CROP ;1U
Solar/Wind Harmer
7.563
274682WAUKEGAN ;7U
Adder
22.282
274828WAUKEGAN ;BP
Adder
13.662
276805AD2-038 GEN
Solar/Wind Harmer
6.24
962781AG1-127 GEN
Solar/Wind Harmer
11.499
274751CRETE EC ;1U
Adder
5.909
274754CRETE EC ;4U
Adder
5.909
274872LEEDK;1U
Solar/Wind Harmer
9.882
276882AE2-255 GEN
Solar/Wind Harmer
4.034
971997AH1-543 GEN
Solar/Wind Harmer
18.485
957471AF2-041 GEN
Solar/Wind Harmer
35.114
959081AF2-199 GEN
Solar/Wind Harmer
11.705
971067AG2-660 GEN
Solar/Wind Harmer
2.722
939401AE1-172 GEN
Solar/Wind Harmer
16.296
274822ROCKFORD ;11
Adder
22.903
970819AG2-516 GEN
Solar/Wind Harmer
13.857
970569AG2-363 GEN
Solar/Wind Harmer
34.002
274858EASY ROAD;U2
Solar/Wind Harmer
5.4
274761LEE CO EC;2U
Adder
10.487
274766LEE CO EC;7U
Adder
10.364
276708O09 GEN2
Solar/Wind Harmer
3.905
276646AC1-214 GEN2
Solar/Wind Harmer
1.428
274848CAMPGROVE;RU
Solar/Wind Harmer
6.751
276655WTG1_EQ
Solar/Wind Harmer
8.392
276656WTG2_EQ
Solar/Wind Harmer
1.111
939741AE1-205 GEN
Solar/Wind Harmer
19.231
276686W4-005 GEN3
Solar/Wind Harmer
2.304
990577J1339
External Queue
21.486574172973633
990647J1355
External Queue
43.16754913330078
991247J1684 G
External Queue
27.83724021911621
990582J1340
External Queue
21.486574172973633
990662J1358
External Queue
14.847929000854492
990512J1326
External Queue
5.337338924407959
990552J1334 G
External Queue
34.048709869384766
990562J1336 G
External Queue
34.048709869384766
991092J1477
External Queue
2.80619215965271
990762J1386
External Queue
10.098306655883789
991332J1785
External Queue
11.874235153198242
990547J1333 G
External Queue
34.048709869384766
990557J1335 G
External Queue
34.048709869384766
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.198
NYPJM->LTFIMP_NY
CLTF
1.089
WECLTFEXP_WEC->PJM
CLTF
4.449
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.915
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.37
MECLTFEXP_MEC->PJM
CLTF
14.031
SIGELTFEXP_SIGE->PJM
CLTF
0.034
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.414
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.366
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.977
LAGNLTFEXP_LAGN->PJM
CLTF
4.88
TVALTFEXP_TVA->PJM
CLTF
1.32

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.68 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2645.11
MW Contribution:
17.03
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.48 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2715.18
MW Contribution:
17.39
Bus #Bus NameTypeMW Contribution
274724RIVER EC ;11
50/50
31.325
957371AF2-031 GEN
50/50
1.551
274826FISK ;BP
50/50
16.449
276164X3-005 C
Solar/Wind Harmer
1.084
972038AH1-567 GEN2
Adder
0.515
274887GEN-1.85
Solar/Wind Harmer
7.35
276772AC2-154 GEN
Solar/Wind Harmer
3.85
276843GEN-1.7
Solar/Wind Harmer
0.791
276806AD2-047 C O1
Solar/Wind Harmer
14.757
274803UNIV PARK;6U
Adder
7.896
274772LINCOLN ;3U
Adder
8.336
274676JOLIET 29;8U
Adder
38.718
274730ELWOOD EC;6P
Adder
21.292
274734ELWOOD EC;8P
Adder
21.292
274736ELWOOD EC;9P
Adder
21.292
274729ELWOOD EC;1P
Adder
21.288
939351AE1-166 GEN
Solar/Wind Harmer
7.667
972259AH1-714 GEN
Adder
24.661
970707AG2-453 GEN
Solar/Wind Harmer
35.928
274814UNIV PK N;0U
Adder
6.42
274807UNIV PK N;3U
Adder
6.406
274811UNIV PK N;7U
Adder
6.364
943121AE2-341 GEN
Solar/Wind Harmer
18.811
943591AF1-030 GEN
Solar/Wind Harmer
12.541
274862TOP CROP ;2U
Solar/Wind Harmer
6.315
274682WAUKEGAN ;7U
Adder
22.282
972231SS25-0005
Solar/Wind Harmer
11.472
972181SS23-001
Solar/Wind Harmer
7.17
274752CRETE EC ;2U
Adder
5.909
274753CRETE EC ;3U
Adder
5.909
276868AE1-113 GEN
Solar/Wind Harmer
12.102
274879MINONK ;1U
Solar/Wind Harmer
8.069
276799AD1-013 GEN
Solar/Wind Harmer
2.616
946671AF1-331 GEN
Solar/Wind Harmer
0.496
274855GSG-6 ;RU
Solar/Wind Harmer
4.365
274850MENDOTA H;RU
Solar/Wind Harmer
3.035
276602WESTBROOK C
Solar/Wind Harmer
2.513
959091AF2-200 GEN
Solar/Wind Harmer
23.409
970571AG2-364 GEN
Solar/Wind Harmer
22.668
274857EASY ROAD;U1
Solar/Wind Harmer
5.4
274760LEE CO EC;1U
Adder
10.487
274767LEE CO EC;8U
Adder
10.364
276603SUBLETTE C
Solar/Wind Harmer
1.177
274851PROVIDENC;RU
Solar/Wind Harmer
3.037
274849CRESCENT ;1U
Solar/Wind Harmer
1.972
276782AC1-033 GEN
Solar/Wind Harmer
4.219
274878BISHOP HL;2U
Solar/Wind Harmer
3.57
965931AG1-462 GEN
Solar/Wind Harmer
26.334
971087AG2-675 GEN
Solar/Wind Harmer
3.843
965091AG1-374 GEN
Solar/Wind Harmer
27.538
959611AF2-252 GEN
Solar/Wind Harmer
2.135
276785W4-005 GEN1
Solar/Wind Harmer
2.304
971993AH1-541 GEN
Solar/Wind Harmer
4.08
274888KELLY CRK;1U
Solar/Wind Harmer
8.14
276776AD2-060 GEN
Solar/Wind Harmer
0.577
958011AF2-095 GEN
Solar/Wind Harmer
19.865
970941AG2-585 GEN
Solar/Wind Harmer
7.587
274770LINCOLN ;1U
Adder
8.336
274771LINCOLN ;2U
Adder
8.336
274674JOLIET 9 ;6U
Adder
20.273
276893AG1-478 C
Solar/Wind Harmer
0.577
276897AD1-100 C
Solar/Wind Harmer
60.055
274805UNIV PK N;1U
Adder
6.378
274808UNIV PK N;4U
Adder
6.336
958481AF2-142 GEN
Solar/Wind Harmer
18.791
274683WAUKEGAN ;8U
Adder
26.064
274683WAUKEGAN ;8U
Adder
21.971
274695ROCKY RD ;2P
Adder
13.753
274693ROCKY RD ;1P
Adder
13.618
274697ROCKY RD ;3P
Adder
3.736
274696ROCKY RD ;4P
Adder
14.077
958491AF2-143 GEN
Solar/Wind Harmer
18.255
962691AG1-118 GEN
Solar/Wind Harmer
36.437
960751AF2-366 GEN
Solar/Wind Harmer
3.469
276901AD2-066 C O1
Solar/Wind Harmer
4.199
971341AH1-150 GEN
Solar/Wind Harmer
23.409
971343AH1-151 GEN
Solar/Wind Harmer
23.409
276872AE1-163_GEN1
Solar/Wind Harmer
7.84
276876AE1-163_GEN2
Solar/Wind Harmer
7.84
972235AH1-702 GEN1
Adder
2.927
972236AH1-702 GEN2
Adder
2.545
938861AE1-114 GEN
Solar/Wind Harmer
9.305
274764LEE CO EC;5U
Adder
10.512
274765LEE CO EC;6U
Adder
10.512
274762LEE CO EC;3U
Adder
10.487
274763LEE CO EC;4U
Adder
10.388
276158O29GEN2
Solar/Wind Harmer
5.469
276157O29GEN1
Solar/Wind Harmer
4.158
276645AC1-214 GEN1
Solar/Wind Harmer
1.428
942111AE2-223 GEN
Solar/Wind Harmer
7.882
960611AF2-352 GEN
Solar/Wind Harmer
2.135
274880W4-005 GEN4
Solar/Wind Harmer
2.304
276174W4-005 GEN2
Solar/Wind Harmer
2.304
274723RIVER EC ;12
50/50
31.279
972179AH1-673 GEN
50/50
16.189
274802UNIV PARK;5U
Adder
7.896
972207SS24-0001
Solar/Wind Harmer
29.637
274773LINCOLN ;4U
Adder
8.336
274774LINCOLN ;5U
Adder
8.336
274674JOLIET 9 ;6U
Adder
20.273
274676JOLIET 29;8U
Adder
40.152
274732ELWOOD EC;7P
Adder
21.292
941551AE2-152 GEN
Solar/Wind Harmer
5.863
274812UNIV PK N;8U
Adder
6.364
274871GR RIDGE ;2U
Solar/Wind Harmer
9.705
274847GR RIDGE ;BU
Solar/Wind Harmer
6.381
274745AC1-111 GEN9
Adder
7.025
276694AA1-018 GEN2
Solar/Wind Harmer
7.905
276691AA1-018 GEN1
Solar/Wind Harmer
0.945
274861TOP CROP ;1U
Solar/Wind Harmer
7.563
274682WAUKEGAN ;7U
Adder
22.282
274828WAUKEGAN ;BP
Adder
13.662
276805AD2-038 GEN
Solar/Wind Harmer
6.24
962781AG1-127 GEN
Solar/Wind Harmer
11.499
274751CRETE EC ;1U
Adder
5.909
274754CRETE EC ;4U
Adder
5.909
274872LEEDK;1U
Solar/Wind Harmer
9.882
276882AE2-255 GEN
Solar/Wind Harmer
4.034
971997AH1-543 GEN
Solar/Wind Harmer
18.485
957471AF2-041 GEN
Solar/Wind Harmer
35.114
959081AF2-199 GEN
Solar/Wind Harmer
11.705
971067AG2-660 GEN
Solar/Wind Harmer
2.722
939401AE1-172 GEN
Solar/Wind Harmer
16.296
274822ROCKFORD ;11
Adder
22.903
970819AG2-516 GEN
Solar/Wind Harmer
13.857
970569AG2-363 GEN
Solar/Wind Harmer
34.002
274858EASY ROAD;U2
Solar/Wind Harmer
5.4
274761LEE CO EC;2U
Adder
10.487
274766LEE CO EC;7U
Adder
10.364
276708O09 GEN2
Solar/Wind Harmer
3.905
276646AC1-214 GEN2
Solar/Wind Harmer
1.428
274848CAMPGROVE;RU
Solar/Wind Harmer
6.751
276655WTG1_EQ
Solar/Wind Harmer
8.392
276656WTG2_EQ
Solar/Wind Harmer
1.111
939741AE1-205 GEN
Solar/Wind Harmer
19.231
276686W4-005 GEN3
Solar/Wind Harmer
2.304
961501AF2-441 GEN
50/50
14.87
274827FISK ;RP
50/50
11.657
274800UNIV PARK;3U
Adder
8.227
274801UNIV PARK;4U
Adder
8.227
960591AF2-350 GEN
Solar/Wind Harmer
13.795
972037AH1-567 GEN1
Adder
0.248
274775LINCOLN ;6U
Adder
8.336
274776LINCOLN ;7U
Adder
8.336
274777LINCOLN ;8U
Adder
8.336
274687WILL CNTY;4U
Adder
37.095
274687WILL CNTY;4U
Adder
37.095
276893AG1-478 C
Solar/Wind Harmer
0.724
972228AH1-698 GEN2
Adder
4.85
972227AH1-698 GEN1
Adder
3.414
274675JOLIET 29;7U
Adder
40.153
274675JOLIET 29;7U
Adder
38.719
274728ELWOOD EC;5P
Adder
21.292
274731ELWOOD EC;2P
Adder
21.288
274733ELWOOD EC;3P
Adder
21.288
274735ELWOOD EC;4P
Adder
21.288
970833AG2-524 GEN
Solar/Wind Harmer
11.057
970833AG2-524 GEN
Solar/Wind Harmer
5.143
274744AC1-111 GEN8
Adder
7.025
274746AC1-111 G10
Adder
7.025
970073AG2-061 GEN
Solar/Wind Harmer
2.83
971411AH1-196 GEN
Solar/Wind Harmer
17.838
971675AH1-338 GEN
Solar/Wind Harmer
21.293
276861AD2-134 GEN
Solar/Wind Harmer
2.111
276863AD2-134 GEN
Solar/Wind Harmer
2.111
971171AH1-044 GEN
Solar/Wind Harmer
23.409
276889AE2-281 GEN
Solar/Wind Harmer
2.24
274823ROCKFORD ;21
Adder
22.737
274856ECOGROVE ;U1
Solar/Wind Harmer
3.879
276611AD2-172 GEN
Solar/Wind Harmer
2.942
276612AE2-035 GEN
Solar/Wind Harmer
2.942
971681AH1-341 GEN
Solar/Wind Harmer
17.026
274863CRW1-WTG
Solar/Wind Harmer
6.264
274864CRW2-WTG
Solar/Wind Harmer
6.264
926823AC1-168 GEN
Solar/Wind Harmer
4.798
972267AH1-718 GEN
Adder
4.601
276741O09 GEN1
Solar/Wind Harmer
3.905
970169AG2-114 GEN
Solar/Wind Harmer
10.739
274877BISHOP HL;1U
Solar/Wind Harmer
3.57
946321AF1-296 GEN
Solar/Wind Harmer
10.891
276726Z2-087_GEN
Solar/Wind Harmer
7.603
959341AF2-225 GEN
Solar/Wind Harmer
14.423
274853TWINGROVE;U1
Solar/Wind Harmer
6.613
274854TWINGROVE;U2
Solar/Wind Harmer
6.475
990577J1339
External Queue
21.48668098449707
990647J1355
External Queue
43.167606353759766
991247J1684 G
External Queue
27.83734703063965
990582J1340
External Queue
21.48668098449707
990662J1358
External Queue
14.848005294799805
990512J1326
External Queue
5.337319850921631
990552J1334 G
External Queue
34.048828125
990562J1336 G
External Queue
34.048828125
991092J1477
External Queue
2.8061811923980713
990762J1386
External Queue
10.098369598388672
991332J1785
External Queue
11.874279022216797
990547J1333 G
External Queue
34.048828125
990557J1335 G
External Queue
34.048828125
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.198
NYPJM->LTFIMP_NY
CLTF
1.089
WECLTFEXP_WEC->PJM
CLTF
4.449
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.915
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.369
MECLTFEXP_MEC->PJM
CLTF
14.031
SIGELTFEXP_SIGE->PJM
CLTF
0.034
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.414
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.366
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.977
LAGNLTFEXP_LAGN->PJM
CLTF
4.88
TVALTFEXP_TVA->PJM
CLTF
1.32

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.76 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2536.22
MW Contribution:
16.42
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.06 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2615.34
MW Contribution:
16.79
Bus #Bus NameTypeMW Contribution
274888KELLY CRK;1U
Solar/Wind Harmer
7.855
276776AD2-060 GEN
Solar/Wind Harmer
0.557
958011AF2-095 GEN
Solar/Wind Harmer
19.168
970941AG2-585 GEN
Solar/Wind Harmer
7.321
274770LINCOLN ;1U
Adder
8.029
274771LINCOLN ;2U
Adder
8.029
274674JOLIET 9 ;6U
Adder
19.56
276893AG1-478 C
Solar/Wind Harmer
0.556
276897AD1-100 C
Solar/Wind Harmer
57.882
274805UNIV PK N;1U
Adder
6.124
274808UNIV PK N;4U
Adder
6.084
958481AF2-142 GEN
Solar/Wind Harmer
18.117
274683WAUKEGAN ;8U
Adder
25.142
274683WAUKEGAN ;8U
Adder
21.194
274695ROCKY RD ;2P
Adder
13.268
274693ROCKY RD ;1P
Adder
13.137
274697ROCKY RD ;3P
Adder
3.604
274696ROCKY RD ;4P
Adder
13.581
958491AF2-143 GEN
Solar/Wind Harmer
17.6
962691AG1-118 GEN
Solar/Wind Harmer
35.155
960751AF2-366 GEN
Solar/Wind Harmer
3.347
276901AD2-066 C O1
Solar/Wind Harmer
4.05
971341AH1-150 GEN
Solar/Wind Harmer
22.584
971343AH1-151 GEN
Solar/Wind Harmer
22.584
276872AE1-163_GEN1
Solar/Wind Harmer
7.559
276876AE1-163_GEN2
Solar/Wind Harmer
7.559
972235AH1-702 GEN1
Adder
2.824
972236AH1-702 GEN2
Adder
2.455
938861AE1-114 GEN
Solar/Wind Harmer
8.976
274764LEE CO EC;5U
Adder
10.141
274765LEE CO EC;6U
Adder
10.141
274762LEE CO EC;3U
Adder
10.117
274763LEE CO EC;4U
Adder
10.021
276158O29GEN2
Solar/Wind Harmer
5.275
276157O29GEN1
Solar/Wind Harmer
4.011
276645AC1-214 GEN1
Solar/Wind Harmer
1.377
942111AE2-223 GEN
Solar/Wind Harmer
7.596
960611AF2-352 GEN
Solar/Wind Harmer
2.057
274880W4-005 GEN4
Solar/Wind Harmer
2.22
276174W4-005 GEN2
Solar/Wind Harmer
2.22
274724RIVER EC ;11
50/50
30.331
957371AF2-031 GEN
50/50
1.502
274826FISK ;BP
50/50
15.878
276164X3-005 C
Solar/Wind Harmer
1.048
972038AH1-567 GEN2
Adder
0.497
274887GEN-1.85
Solar/Wind Harmer
7.092
276772AC2-154 GEN
Solar/Wind Harmer
3.715
276843GEN-1.7
Solar/Wind Harmer
0.763
276806AD2-047 C O1
Solar/Wind Harmer
14.239
274803UNIV PARK;6U
Adder
7.609
274772LINCOLN ;3U
Adder
8.029
274676JOLIET 29;8U
Adder
37.336
274730ELWOOD EC;6P
Adder
20.53
274734ELWOOD EC;8P
Adder
20.53
274736ELWOOD EC;9P
Adder
20.53
274729ELWOOD EC;1P
Adder
20.527
972259AH1-714 GEN
Adder
23.783
939351AE1-166 GEN
Solar/Wind Harmer
7.389
970707AG2-453 GEN
Solar/Wind Harmer
34.674
274814UNIV PK N;0U
Adder
6.164
274807UNIV PK N;3U
Adder
6.15
274811UNIV PK N;7U
Adder
6.11
943121AE2-341 GEN
Solar/Wind Harmer
18.152
943591AF1-030 GEN
Solar/Wind Harmer
12.102
274862TOP CROP ;2U
Solar/Wind Harmer
6.088
274682WAUKEGAN ;7U
Adder
21.493
972231SS25-0005
Solar/Wind Harmer
10.973
972181SS23-001
Solar/Wind Harmer
6.858
274752CRETE EC ;2U
Adder
5.651
274753CRETE EC ;3U
Adder
5.651
276868AE1-113 GEN
Solar/Wind Harmer
11.67
274879MINONK ;1U
Solar/Wind Harmer
7.78
276799AD1-013 GEN
Solar/Wind Harmer
2.524
946671AF1-331 GEN
Solar/Wind Harmer
0.478
274855GSG-6 ;RU
Solar/Wind Harmer
4.211
274850MENDOTA H;RU
Solar/Wind Harmer
2.928
276602WESTBROOK C
Solar/Wind Harmer
2.424
959091AF2-200 GEN
Solar/Wind Harmer
22.584
970571AG2-364 GEN
Solar/Wind Harmer
21.856
274857EASY ROAD;U1
Solar/Wind Harmer
5.209
274760LEE CO EC;1U
Adder
10.117
274767LEE CO EC;8U
Adder
9.998
276603SUBLETTE C
Solar/Wind Harmer
1.135
274851PROVIDENC;RU
Solar/Wind Harmer
2.929
274849CRESCENT ;1U
Solar/Wind Harmer
1.901
276782AC1-033 GEN
Solar/Wind Harmer
4.069
274878BISHOP HL;2U
Solar/Wind Harmer
3.442
965931AG1-462 GEN
Solar/Wind Harmer
25.402
971087AG2-675 GEN
Solar/Wind Harmer
3.707
965091AG1-374 GEN
Solar/Wind Harmer
26.538
959611AF2-252 GEN
Solar/Wind Harmer
2.057
276785W4-005 GEN1
Solar/Wind Harmer
2.22
971993AH1-541 GEN
Solar/Wind Harmer
3.931
274723RIVER EC ;12
50/50
30.275
972179AH1-673 GEN
50/50
15.668
274802UNIV PARK;5U
Adder
7.609
972207SS24-0001
Solar/Wind Harmer
28.546
274773LINCOLN ;4U
Adder
8.029
274774LINCOLN ;5U
Adder
8.029
274674JOLIET 9 ;6U
Adder
19.56
274676JOLIET 29;8U
Adder
38.719
274732ELWOOD EC;7P
Adder
20.53
941551AE2-152 GEN
Solar/Wind Harmer
5.651
274812UNIV PK N;8U
Adder
6.11
274871GR RIDGE ;2U
Solar/Wind Harmer
9.359
274847GR RIDGE ;BU
Solar/Wind Harmer
6.154
274745AC1-111 GEN9
Adder
6.778
276694AA1-018 GEN2
Solar/Wind Harmer
7.621
276691AA1-018 GEN1
Solar/Wind Harmer
0.911
274861TOP CROP ;1U
Solar/Wind Harmer
7.291
274682WAUKEGAN ;7U
Adder
21.493
274828WAUKEGAN ;BP
Adder
13.179
276805AD2-038 GEN
Solar/Wind Harmer
6.017
962781AG1-127 GEN
Solar/Wind Harmer
11.095
274872LEEDK;1U
Solar/Wind Harmer
9.534
274751CRETE EC ;1U
Adder
5.651
274754CRETE EC ;4U
Adder
5.651
276882AE2-255 GEN
Solar/Wind Harmer
3.89
971997AH1-543 GEN
Solar/Wind Harmer
17.829
957471AF2-041 GEN
Solar/Wind Harmer
33.876
959081AF2-199 GEN
Solar/Wind Harmer
11.292
971067AG2-660 GEN
Solar/Wind Harmer
2.626
939401AE1-172 GEN
Solar/Wind Harmer
15.706
274822ROCKFORD ;11
Adder
22.095
970819AG2-516 GEN
Solar/Wind Harmer
13.367
970569AG2-363 GEN
Solar/Wind Harmer
32.785
274858EASY ROAD;U2
Solar/Wind Harmer
5.209
274761LEE CO EC;2U
Adder
10.117
274766LEE CO EC;7U
Adder
9.998
276708O09 GEN2
Solar/Wind Harmer
3.767
276646AC1-214 GEN2
Solar/Wind Harmer
1.377
274848CAMPGROVE;RU
Solar/Wind Harmer
6.51
276655WTG1_EQ
Solar/Wind Harmer
8.088
276656WTG2_EQ
Solar/Wind Harmer
1.071
939741AE1-205 GEN
Solar/Wind Harmer
18.533
276686W4-005 GEN3
Solar/Wind Harmer
2.22
961501AF2-441 GEN
50/50
14.388
274827FISK ;RP
50/50
11.253
274800UNIV PARK;3U
Adder
7.943
274801UNIV PARK;4U
Adder
7.943
960591AF2-350 GEN
Solar/Wind Harmer
13.311
972037AH1-567 GEN1
Adder
0.239
274775LINCOLN ;6U
Adder
8.029
274776LINCOLN ;7U
Adder
8.029
274777LINCOLN ;8U
Adder
8.029
274687WILL CNTY;4U
Adder
35.777
274687WILL CNTY;4U
Adder
35.777
276893AG1-478 C
Solar/Wind Harmer
0.698
972228AH1-698 GEN2
Adder
4.674
274675JOLIET 29;7U
Adder
38.72
274675JOLIET 29;7U
Adder
37.337
972227AH1-698 GEN1
Adder
3.291
274728ELWOOD EC;5P
Adder
20.53
274731ELWOOD EC;2P
Adder
20.527
274733ELWOOD EC;3P
Adder
20.527
274735ELWOOD EC;4P
Adder
20.527
970833AG2-524 GEN
Solar/Wind Harmer
10.665
970833AG2-524 GEN
Solar/Wind Harmer
4.96
274744AC1-111 GEN8
Adder
6.778
274746AC1-111 G10
Adder
6.778
970073AG2-061 GEN
Solar/Wind Harmer
2.729
971411AH1-196 GEN
Solar/Wind Harmer
17.208
971675AH1-338 GEN
Solar/Wind Harmer
20.543
276861AD2-134 GEN
Solar/Wind Harmer
2.036
276863AD2-134 GEN
Solar/Wind Harmer
2.036
971171AH1-044 GEN
Solar/Wind Harmer
22.584
274823ROCKFORD ;21
Adder
21.934
276889AE2-281 GEN
Solar/Wind Harmer
2.16
274856ECOGROVE ;U1
Solar/Wind Harmer
3.742
276611AD2-172 GEN
Solar/Wind Harmer
2.838
276612AE2-035 GEN
Solar/Wind Harmer
2.838
971681AH1-341 GEN
Solar/Wind Harmer
16.424
274863CRW1-WTG
Solar/Wind Harmer
6.037
274864CRW2-WTG
Solar/Wind Harmer
6.037
926823AC1-168 GEN
Solar/Wind Harmer
4.627
972267AH1-718 GEN
Adder
4.438
276741O09 GEN1
Solar/Wind Harmer
3.767
970169AG2-114 GEN
Solar/Wind Harmer
10.353
274877BISHOP HL;1U
Solar/Wind Harmer
3.442
946321AF1-296 GEN
Solar/Wind Harmer
10.506
276726Z2-087_GEN
Solar/Wind Harmer
7.327
959341AF2-225 GEN
Solar/Wind Harmer
13.9
274853TWINGROVE;U1
Solar/Wind Harmer
6.373
274854TWINGROVE;U2
Solar/Wind Harmer
6.24
990577J1339
External Queue
20.88433265686035
990647J1355
External Queue
42.49855422973633
991247J1684 G
External Queue
27.17664337158203
990582J1340
External Queue
20.88433265686035
990662J1358
External Queue
14.320621490478516
990512J1326
External Queue
5.198352336883545
990552J1334 G
External Queue
33.333072662353516
990562J1336 G
External Queue
33.333072662353516
991092J1477
External Queue
2.7395448684692383
990762J1386
External Queue
9.767641067504883
991332J1785
External Queue
11.481666564941406
990547J1333 G
External Queue
33.333072662353516
990557J1335 G
External Queue
33.333072662353516
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.182
NYPJM->LTFIMP_NY
CLTF
1.041
WECLTFEXP_WEC->PJM
CLTF
4.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.737
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.706
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.125
MECLTFEXP_MEC->PJM
CLTF
13.536
SIGELTFEXP_SIGE->PJM
CLTF
0.033
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.384
AG2-052LTFEXP_AG2-052->PJM
LTF
0.544
AH1-155LTFEXP_AH1-155->PJM
LTF
0.816
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.339
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.903
LAGNLTFEXP_LAGN->PJM
CLTF
4.728
TVALTFEXP_TVA->PJM
CLTF
1.286

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.79 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2481.49
MW Contribution:
16.16
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.24 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2692.19
MW Contribution:
17.04
Bus #Bus NameTypeMW Contribution
274724RIVER EC ;11
50/50
29.724
957371AF2-031 GEN
50/50
1.472
274826FISK ;BP
50/50
15.553
276164X3-005 C
Solar/Wind Harmer
1.027
972038AH1-567 GEN2
Adder
0.487
274887GEN-1.85
Solar/Wind Harmer
6.949
276772AC2-154 GEN
Solar/Wind Harmer
3.64
276843GEN-1.7
Solar/Wind Harmer
0.748
276806AD2-047 C O1
Solar/Wind Harmer
13.952
274803UNIV PARK;6U
Adder
7.444
274772LINCOLN ;3U
Adder
7.871
274676JOLIET 29;8U
Adder
36.583
274730ELWOOD EC;6P
Adder
20.122
274734ELWOOD EC;8P
Adder
20.122
274736ELWOOD EC;9P
Adder
20.122
274729ELWOOD EC;1P
Adder
20.119
939351AE1-166 GEN
Solar/Wind Harmer
7.247
972259AH1-714 GEN
Adder
23.308
970707AG2-453 GEN
Solar/Wind Harmer
33.994
274814UNIV PK N;0U
Adder
6.007
274807UNIV PK N;3U
Adder
5.994
274811UNIV PK N;7U
Adder
5.955
943121AE2-341 GEN
Solar/Wind Harmer
17.81
943591AF1-030 GEN
Solar/Wind Harmer
11.874
274862TOP CROP ;2U
Solar/Wind Harmer
5.972
274682WAUKEGAN ;7U
Adder
21.093
276868AE1-113 GEN
Solar/Wind Harmer
11.467
274879MINONK ;1U
Solar/Wind Harmer
7.645
276799AD1-013 GEN
Solar/Wind Harmer
2.48
946671AF1-331 GEN
Solar/Wind Harmer
0.47
972231SS25-0005
Solar/Wind Harmer
10.649
972181SS23-001
Solar/Wind Harmer
6.655
274752CRETE EC ;2U
Adder
5.484
274753CRETE EC ;3U
Adder
5.484
274855GSG-6 ;RU
Solar/Wind Harmer
4.139
274850MENDOTA H;RU
Solar/Wind Harmer
2.878
276602WESTBROOK C
Solar/Wind Harmer
2.383
959091AF2-200 GEN
Solar/Wind Harmer
22.201
970571AG2-364 GEN
Solar/Wind Harmer
21.515
274857EASY ROAD;U1
Solar/Wind Harmer
5.127
274760LEE CO EC;1U
Adder
9.956
274767LEE CO EC;8U
Adder
9.839
276603SUBLETTE C
Solar/Wind Harmer
1.117
274851PROVIDENC;RU
Solar/Wind Harmer
2.89
274849CRESCENT ;1U
Solar/Wind Harmer
1.876
276782AC1-033 GEN
Solar/Wind Harmer
4.015
274878BISHOP HL;2U
Solar/Wind Harmer
3.397
274723RIVER EC ;12
50/50
29.663
972179AH1-673 GEN
50/50
15.351
274802UNIV PARK;5U
Adder
7.444
972207SS24-0001
Solar/Wind Harmer
27.986
274773LINCOLN ;4U
Adder
7.871
274774LINCOLN ;5U
Adder
7.871
274674JOLIET 9 ;6U
Adder
19.176
274676JOLIET 29;8U
Adder
37.938
274732ELWOOD EC;7P
Adder
20.122
941551AE2-152 GEN
Solar/Wind Harmer
5.543
274871GR RIDGE ;2U
Solar/Wind Harmer
9.18
274847GR RIDGE ;BU
Solar/Wind Harmer
6.036
274745AC1-111 GEN9
Adder
6.65
274812UNIV PK N;8U
Adder
5.955
276694AA1-018 GEN2
Solar/Wind Harmer
7.477
276691AA1-018 GEN1
Solar/Wind Harmer
0.894
274861TOP CROP ;1U
Solar/Wind Harmer
7.153
274682WAUKEGAN ;7U
Adder
21.093
274828WAUKEGAN ;BP
Adder
12.934
276805AD2-038 GEN
Solar/Wind Harmer
5.909
962781AG1-127 GEN
Solar/Wind Harmer
10.896
274872LEEDK;1U
Solar/Wind Harmer
9.365
276882AE2-255 GEN
Solar/Wind Harmer
3.822
274751CRETE EC ;1U
Adder
5.484
274754CRETE EC ;4U
Adder
5.484
971997AH1-543 GEN
Solar/Wind Harmer
17.533
957471AF2-041 GEN
Solar/Wind Harmer
33.301
959081AF2-199 GEN
Solar/Wind Harmer
11.1
971067AG2-660 GEN
Solar/Wind Harmer
2.582
939401AE1-172 GEN
Solar/Wind Harmer
15.46
274822ROCKFORD ;11
Adder
21.721
970819AG2-516 GEN
Solar/Wind Harmer
13.145
970569AG2-363 GEN
Solar/Wind Harmer
32.273
274858EASY ROAD;U2
Solar/Wind Harmer
5.127
274761LEE CO EC;2U
Adder
9.956
274766LEE CO EC;7U
Adder
9.839
276708O09 GEN2
Solar/Wind Harmer
3.711
276646AC1-214 GEN2
Solar/Wind Harmer
1.359
274848CAMPGROVE;RU
Solar/Wind Harmer
6.427
276655WTG1_EQ
Solar/Wind Harmer
8.026
276656WTG2_EQ
Solar/Wind Harmer
1.063
939741AE1-205 GEN
Solar/Wind Harmer
18.39
276686W4-005 GEN3
Solar/Wind Harmer
2.229
270216AD2-079_GEN
Solar/Wind Helper
0.124
270449AD2-020 GEN
Solar/Wind Helper
0.718
24441205WTRV SLR C
Solar/Wind Helper
0.042
274888KELLY CRK;1U
Solar/Wind Harmer
7.697
276776AD2-060 GEN
Solar/Wind Harmer
0.546
958011AF2-095 GEN
Solar/Wind Harmer
18.781
970941AG2-585 GEN
Solar/Wind Harmer
7.173
274770LINCOLN ;1U
Adder
7.871
274771LINCOLN ;2U
Adder
7.871
274674JOLIET 9 ;6U
Adder
19.176
276893AG1-478 C
Solar/Wind Harmer
0.545
276897AD1-100 C
Solar/Wind Harmer
56.769
274805UNIV PK N;1U
Adder
5.968
274808UNIV PK N;4U
Adder
5.929
958481AF2-142 GEN
Solar/Wind Harmer
17.775
274683WAUKEGAN ;8U
Adder
24.675
274683WAUKEGAN ;8U
Adder
20.8
274696ROCKY RD ;4P
Adder
13.329
274695ROCKY RD ;2P
Adder
13.023
274693ROCKY RD ;1P
Adder
12.894
274697ROCKY RD ;3P
Adder
3.538
958491AF2-143 GEN
Solar/Wind Harmer
17.284
962691AG1-118 GEN
Solar/Wind Harmer
34.523
960751AF2-366 GEN
Solar/Wind Harmer
3.287
276901AD2-066 C O1
Solar/Wind Harmer
3.98
971341AH1-150 GEN
Solar/Wind Harmer
22.201
971343AH1-151 GEN
Solar/Wind Harmer
22.201
276872AE1-163_GEN1
Solar/Wind Harmer
7.433
276876AE1-163_GEN2
Solar/Wind Harmer
7.433
972235AH1-702 GEN1
Adder
2.776
972236AH1-702 GEN2
Adder
2.414
938861AE1-114 GEN
Solar/Wind Harmer
8.832
274764LEE CO EC;5U
Adder
9.98
274765LEE CO EC;6U
Adder
9.98
274762LEE CO EC;3U
Adder
9.956
274763LEE CO EC;4U
Adder
9.863
276158O29GEN2
Solar/Wind Harmer
5.198
276157O29GEN1
Solar/Wind Harmer
3.952
276645AC1-214 GEN1
Solar/Wind Harmer
1.359
942111AE2-223 GEN
Solar/Wind Harmer
7.538
960611AF2-352 GEN
Solar/Wind Harmer
2.046
274880W4-005 GEN4
Solar/Wind Harmer
2.229
276174W4-005 GEN2
Solar/Wind Harmer
2.229
961501AF2-441 GEN
50/50
14.1
274827FISK ;RP
50/50
11.023
274800UNIV PARK;3U
Adder
7.783
274801UNIV PARK;4U
Adder
7.783
960591AF2-350 GEN
Solar/Wind Harmer
13.043
972037AH1-567 GEN1
Adder
0.234
274775LINCOLN ;6U
Adder
7.871
274776LINCOLN ;7U
Adder
7.871
274777LINCOLN ;8U
Adder
7.871
274687WILL CNTY;4U
Adder
35.052
274687WILL CNTY;4U
Adder
35.052
276893AG1-478 C
Solar/Wind Harmer
0.684
274675JOLIET 29;7U
Adder
37.938
274675JOLIET 29;7U
Adder
36.583
972228AH1-698 GEN2
Adder
4.578
972227AH1-698 GEN1
Adder
3.223
274728ELWOOD EC;5P
Adder
20.122
274731ELWOOD EC;2P
Adder
20.119
274733ELWOOD EC;3P
Adder
20.119
274735ELWOOD EC;4P
Adder
20.119
970833AG2-524 GEN
Solar/Wind Harmer
10.46
970833AG2-524 GEN
Solar/Wind Harmer
4.865
274744AC1-111 GEN8
Adder
6.65
274746AC1-111 G10
Adder
6.65
970073AG2-061 GEN
Solar/Wind Harmer
2.68
971411AH1-196 GEN
Solar/Wind Harmer
16.908
971675AH1-338 GEN
Solar/Wind Harmer
20.189
276861AD2-134 GEN
Solar/Wind Harmer
2.001
276863AD2-134 GEN
Solar/Wind Harmer
2.001
971171AH1-044 GEN
Solar/Wind Harmer
22.201
276889AE2-281 GEN
Solar/Wind Harmer
2.124
274823ROCKFORD ;21
Adder
21.563
274856ECOGROVE ;U1
Solar/Wind Harmer
3.68
276611AD2-172 GEN
Solar/Wind Harmer
2.792
276612AE2-035 GEN
Solar/Wind Harmer
2.792
971681AH1-341 GEN
Solar/Wind Harmer
16.161
274863CRW1-WTG
Solar/Wind Harmer
5.952
274864CRW2-WTG
Solar/Wind Harmer
5.952
926823AC1-168 GEN
Solar/Wind Harmer
4.558
972267AH1-718 GEN
Adder
4.37
276741O09 GEN1
Solar/Wind Harmer
3.711
970169AG2-114 GEN
Solar/Wind Harmer
10.223
274877BISHOP HL;1U
Solar/Wind Harmer
3.397
946321AF1-296 GEN
Solar/Wind Harmer
10.365
276726Z2-087_GEN
Solar/Wind Harmer
7.271
959341AF2-225 GEN
Solar/Wind Harmer
13.793
274853TWINGROVE;U1
Solar/Wind Harmer
6.337
274854TWINGROVE;U2
Solar/Wind Harmer
6.204
944161AF1-084 GEN
Solar/Wind Helper
0.681
965931AG1-462 GEN
Solar/Wind Harmer
25.07
971087AG2-675 GEN
Solar/Wind Harmer
3.658
965091AG1-374 GEN
Solar/Wind Harmer
26.387
959611AF2-252 GEN
Solar/Wind Harmer
2.046
276785W4-005 GEN1
Solar/Wind Harmer
2.229
247643Z2-116 C
Solar/Wind Helper
0.028
971993AH1-541 GEN
Solar/Wind Harmer
3.946
990577J1339
External Queue
20.445016860961914
990647J1355
External Queue
41.982242584228516
991247J1684 G
External Queue
26.698122024536133
990582J1340
External Queue
20.445016860961914
990662J1358
External Queue
13.787203788757324
990512J1326
External Queue
5.1700615882873535
990552J1334 G
External Queue
32.8177375793457
990562J1336 G
External Queue
32.8177375793457
991092J1477
External Queue
2.7550487518310547
990762J1386
External Queue
9.516397476196289
991332J1785
External Queue
11.050836563110352
990547J1333 G
External Queue
32.8177375793457
990557J1335 G
External Queue
32.8177375793457
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.125
NYPJM->LTFIMP_NY
CLTF
1.012
WECLTFEXP_WEC->PJM
CLTF
4.219
CBM West 1LTFEXP_CBM-W1->PJM
CBM
76.482
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.389
MECLTFEXP_MEC->PJM
CLTF
13.451
SIGELTFEXP_SIGE->PJM
CLTF
0.049
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.295
AG2-052LTFEXP_AG2-052->PJM
LTF
0.54
AH1-155LTFEXP_AH1-155->PJM
LTF
0.81
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.102
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.185
LAGNLTFEXP_LAGN->PJM
CLTF
5.003
TVALTFEXP_TVA->PJM
CLTF
1.456

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.61 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2183.54
MW Contribution:
12.76
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.77 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2241.7
MW Contribution:
13.04
Bus #Bus NameTypeMW Contribution
274723RIVER EC ;12
50/50
31.272
972179AH1-673 GEN
50/50
16.185
274802UNIV PARK;5U
Adder
7.895
274773LINCOLN ;4U
Adder
11.327
274774LINCOLN ;5U
Adder
11.327
274674JOLIET 9 ;6U
Adder
20.278
274676JOLIET 29;8U
Adder
40.16
274732ELWOOD EC;7P
Adder
21.296
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
6.364
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.03
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.42
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.292
274828WAUKEGAN ;BP
Adder
13.669
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
8.034
274751CRETE EC ;1U
Adder
9.959
274754CRETE EC ;4U
Adder
9.959
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.974
971997AH1-543 GEN
Solar/Wind Harmer
4.301
957471AF2-041 GEN
Solar/Wind Harmer
24.513
959081AF2-199 GEN
Solar/Wind Harmer
8.171
971067AG2-660 GEN
Solar/Wind Harmer
2.724
939401AE1-172 GEN
Solar/Wind Harmer
6.1
274822ROCKFORD ;11
Adder
22.916
970819AG2-516 GEN
Solar/Wind Harmer
9.673
970569AG2-363 GEN
Solar/Wind Harmer
23.727
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.493
274766LEE CO EC;7U
Adder
10.369
276708O09 GEN2
Solar/Wind Harmer
0.269
276646AC1-214 GEN2
Solar/Wind Harmer
0.292
274888KELLY CRK;1U
Solar/Wind Harmer
0.561
958011AF2-095 GEN
Solar/Wind Harmer
13.857
970941AG2-585 GEN
Solar/Wind Harmer
5.293
276776AD2-060 GEN
Solar/Wind Harmer
1.026
274770LINCOLN ;1U
Adder
11.327
274771LINCOLN ;2U
Adder
11.327
274674JOLIET 9 ;6U
Adder
20.278
276893AG1-478 C
Solar/Wind Harmer
0.612
276897AD1-100 C
Solar/Wind Harmer
22.537
274805UNIV PK N;1U
Adder
6.378
274808UNIV PK N;4U
Adder
6.336
958481AF2-142 GEN
Solar/Wind Harmer
13.111
274683WAUKEGAN ;8U
Adder
26.077
274683WAUKEGAN ;8U
Adder
21.981
274695ROCKY RD ;2P
Adder
13.761
274693ROCKY RD ;1P
Adder
13.626
274697ROCKY RD ;3P
Adder
3.738
274696ROCKY RD ;4P
Adder
14.085
958491AF2-143 GEN
Solar/Wind Harmer
12.737
962691AG1-118 GEN
Solar/Wind Harmer
25.438
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
16.342
971343AH1-151 GEN
Solar/Wind Harmer
16.342
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.929
972236AH1-702 GEN2
Adder
2.547
938861AE1-114 GEN
Solar/Wind Harmer
4.49
274764LEE CO EC;5U
Adder
10.518
274765LEE CO EC;6U
Adder
10.518
274762LEE CO EC;3U
Adder
10.493
274763LEE CO EC;4U
Adder
10.394
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.23
276645AC1-214 GEN1
Solar/Wind Harmer
0.292
942111AE2-223 GEN
Solar/Wind Harmer
2.18
960611AF2-352 GEN
Solar/Wind Harmer
2.135
276615X2-022 GEN
Solar/Wind Harmer
0.053
276838X2-022 GEN2
Solar/Wind Harmer
0.286
276916AD2-100_GEN
Solar/Wind Harmer
9.37
276911AD2-131_GEN
Solar/Wind Harmer
0.617
961501AF2-441 GEN
50/50
14.867
274827FISK ;RP
50/50
11.656
274800UNIV PARK;3U
Adder
8.227
274801UNIV PARK;4U
Adder
8.227
960591AF2-350 GEN
Solar/Wind Harmer
9.623
972037AH1-567 GEN1
Adder
0.248
274775LINCOLN ;6U
Adder
11.327
274776LINCOLN ;7U
Adder
11.327
274777LINCOLN ;8U
Adder
11.327
274687WILL CNTY;4U
Adder
37.1
274687WILL CNTY;4U
Adder
37.1
972228AH1-698 GEN2
Adder
4.85
972227AH1-698 GEN1
Adder
3.414
274675JOLIET 29;7U
Adder
40.161
274675JOLIET 29;7U
Adder
38.727
274728ELWOOD EC;5P
Adder
21.296
274731ELWOOD EC;2P
Adder
21.293
274733ELWOOD EC;3P
Adder
21.293
274735ELWOOD EC;4P
Adder
21.293
970833AG2-524 GEN
Solar/Wind Harmer
9.725
970833AG2-524 GEN
Solar/Wind Harmer
6.483
274744AC1-111 GEN8
Adder
7.03
274746AC1-111 G10
Adder
7.03
970073AG2-061 GEN
Solar/Wind Harmer
2.831
971411AH1-196 GEN
Solar/Wind Harmer
12.452
971675AH1-338 GEN
Solar/Wind Harmer
3.221
276861AD2-134 GEN
Solar/Wind Harmer
0.147
276863AD2-134 GEN
Solar/Wind Harmer
0.147
971171AH1-044 GEN
Solar/Wind Harmer
16.342
274823ROCKFORD ;21
Adder
22.75
274856ECOGROVE ;U1
Solar/Wind Harmer
0.188
971681AH1-341 GEN
Solar/Wind Harmer
12.757
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.325
972267AH1-718 GEN
Adder
4.603
276741O09 GEN1
Solar/Wind Harmer
0.269
970169AG2-114 GEN
Solar/Wind Harmer
7.493
274877BISHOP HL;1U
Solar/Wind Harmer
0.246
946321AF1-296 GEN
Solar/Wind Harmer
4.081
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.043
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.209
276848AB2-070 GEN3
Solar/Wind Harmer
0.208
276849AB2-070 GEN2
Solar/Wind Harmer
0.209
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.348
274724RIVER EC ;11
50/50
31.319
957371AF2-031 GEN
50/50
1.55
274826FISK ;BP
50/50
16.447
972038AH1-567 GEN2
Adder
0.515
274887GEN-1.85
Solar/Wind Harmer
0.25
276843GEN-1.7
Solar/Wind Harmer
0.311
276806AD2-047 C O1
Solar/Wind Harmer
5.453
274803UNIV PARK;6U
Adder
7.895
274772LINCOLN ;3U
Adder
11.327
274676JOLIET 29;8U
Adder
38.726
274730ELWOOD EC;6P
Adder
21.296
274734ELWOOD EC;8P
Adder
21.296
274736ELWOOD EC;9P
Adder
21.296
274729ELWOOD EC;1P
Adder
21.293
972259AH1-714 GEN
Adder
24.673
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
29.274
274814UNIV PK N;0U
Adder
6.419
274807UNIV PK N;3U
Adder
6.405
274811UNIV PK N;7U
Adder
6.364
943121AE2-341 GEN
Solar/Wind Harmer
14.682
943591AF1-030 GEN
Solar/Wind Harmer
9.763
274862TOP CROP ;2U
Solar/Wind Harmer
1.176
274682WAUKEGAN ;7U
Adder
22.292
274752CRETE EC ;2U
Adder
9.959
274753CRETE EC ;3U
Adder
9.959
276868AE1-113 GEN
Solar/Wind Harmer
1.67
274879MINONK ;1U
Solar/Wind Harmer
0.348
946671AF1-331 GEN
Solar/Wind Harmer
0.882
274855GSG-6 ;RU
Solar/Wind Harmer
0.301
274850MENDOTA H;RU
Solar/Wind Harmer
0.096
959091AF2-200 GEN
Solar/Wind Harmer
16.342
970571AG2-364 GEN
Solar/Wind Harmer
15.818
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
10.493
274767LEE CO EC;8U
Adder
10.369
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.246
965931AG1-462 GEN
Solar/Wind Harmer
18.382
971087AG2-675 GEN
Solar/Wind Harmer
3.845
965091AG1-374 GEN
Solar/Wind Harmer
19.211
959611AF2-252 GEN
Solar/Wind Harmer
2.135
971993AH1-541 GEN
Solar/Wind Harmer
2.456
957381AF2-032 GEN
Solar/Wind Harmer
1.053
942481AE2-261 GEN
Solar/Wind Harmer
13.741
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.391
276621W2-048 GEN
Solar/Wind Harmer
0.254
965911AG1-460 GEN
Solar/Wind Harmer
0.919
990577J1339
External Queue
21.47968864440918
990647J1355
External Queue
43.162841796875
991777J1629 G
External Queue
12.10804271697998
991247J1684 G
External Queue
27.830068588256836
990582J1340
External Queue
21.47968864440918
990662J1358
External Queue
14.842607498168945
990512J1326
External Queue
5.34079122543335
991337J1802
External Queue
7.773519515991211
990117J1214
External Queue
18.3723201751709
990727J1377 G
External Queue
6.2205705642700195
990552J1334 G
External Queue
34.041297912597656
990562J1336 G
External Queue
34.041297912597656
991092J1477
External Queue
2.807737350463867
990762J1386
External Queue
10.094657897949219
991332J1785
External Queue
11.870986938476562
990547J1333 G
External Queue
34.041297912597656
990557J1335 G
External Queue
34.041297912597656
991303J1755 G
External Queue
4.588634490966797
990407J1304
External Queue
4.146153450012207
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.198
NYPJM->LTFIMP_NY
CLTF
1.09
WECLTFEXP_WEC->PJM
CLTF
4.451
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.949
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.376
MECLTFEXP_MEC->PJM
CLTF
14.037
SIGELTFEXP_SIGE->PJM
CLTF
0.034
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.415
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.366
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.978
LAGNLTFEXP_LAGN->PJM
CLTF
4.881
TVALTFEXP_TVA->PJM
CLTF
1.32

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.6 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2183.51
MW Contribution:
12.76
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.76 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2241.57
MW Contribution:
13.04
Bus #Bus NameTypeMW Contribution
274723RIVER EC ;12
50/50
31.272
972179AH1-673 GEN
50/50
16.185
274802UNIV PARK;5U
Adder
7.895
274773LINCOLN ;4U
Adder
11.327
274888KELLY CRK;1U
Solar/Wind Harmer
0.561
958011AF2-095 GEN
Solar/Wind Harmer
13.857
970941AG2-585 GEN
Solar/Wind Harmer
5.293
276776AD2-060 GEN
Solar/Wind Harmer
1.026
274770LINCOLN ;1U
Adder
11.327
274771LINCOLN ;2U
Adder
11.327
274674JOLIET 9 ;6U
Adder
20.278
276893AG1-478 C
Solar/Wind Harmer
0.612
276897AD1-100 C
Solar/Wind Harmer
22.537
274805UNIV PK N;1U
Adder
6.378
274808UNIV PK N;4U
Adder
6.336
958481AF2-142 GEN
Solar/Wind Harmer
13.111
274683WAUKEGAN ;8U
Adder
26.077
274683WAUKEGAN ;8U
Adder
21.981
274695ROCKY RD ;2P
Adder
13.761
274693ROCKY RD ;1P
Adder
13.626
274697ROCKY RD ;3P
Adder
3.738
274696ROCKY RD ;4P
Adder
14.085
958491AF2-143 GEN
Solar/Wind Harmer
12.737
962691AG1-118 GEN
Solar/Wind Harmer
25.438
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
16.342
971343AH1-151 GEN
Solar/Wind Harmer
16.342
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.929
972236AH1-702 GEN2
Adder
2.547
938861AE1-114 GEN
Solar/Wind Harmer
4.49
274764LEE CO EC;5U
Adder
10.518
274765LEE CO EC;6U
Adder
10.518
274762LEE CO EC;3U
Adder
10.493
274724RIVER EC ;11
50/50
31.319
957371AF2-031 GEN
50/50
1.55
274826FISK ;BP
50/50
16.447
972038AH1-567 GEN2
Adder
0.515
274774LINCOLN ;5U
Adder
11.327
274674JOLIET 9 ;6U
Adder
20.278
274676JOLIET 29;8U
Adder
40.16
274732ELWOOD EC;7P
Adder
21.296
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
6.364
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.03
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.42
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.292
274828WAUKEGAN ;BP
Adder
13.669
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
8.034
274751CRETE EC ;1U
Adder
9.959
274754CRETE EC ;4U
Adder
9.959
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.974
971997AH1-543 GEN
Solar/Wind Harmer
4.301
957471AF2-041 GEN
Solar/Wind Harmer
24.513
959081AF2-199 GEN
Solar/Wind Harmer
8.171
971067AG2-660 GEN
Solar/Wind Harmer
2.724
939401AE1-172 GEN
Solar/Wind Harmer
6.1
274822ROCKFORD ;11
Adder
22.916
970819AG2-516 GEN
Solar/Wind Harmer
9.673
970569AG2-363 GEN
Solar/Wind Harmer
23.727
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.493
274766LEE CO EC;7U
Adder
10.369
276708O09 GEN2
Solar/Wind Harmer
0.269
276646AC1-214 GEN2
Solar/Wind Harmer
0.292
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.391
276621W2-048 GEN
Solar/Wind Harmer
0.254
965911AG1-460 GEN
Solar/Wind Harmer
0.919
274763LEE CO EC;4U
Adder
10.394
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.23
276645AC1-214 GEN1
Solar/Wind Harmer
0.292
942111AE2-223 GEN
Solar/Wind Harmer
2.18
960611AF2-352 GEN
Solar/Wind Harmer
2.135
276615X2-022 GEN
Solar/Wind Harmer
0.053
276838X2-022 GEN2
Solar/Wind Harmer
0.286
276916AD2-100_GEN
Solar/Wind Harmer
9.37
276911AD2-131_GEN
Solar/Wind Harmer
0.617
961501AF2-441 GEN
50/50
14.867
274827FISK ;RP
50/50
11.656
274800UNIV PARK;3U
Adder
8.227
274801UNIV PARK;4U
Adder
8.227
960591AF2-350 GEN
Solar/Wind Harmer
9.623
972037AH1-567 GEN1
Adder
0.248
274775LINCOLN ;6U
Adder
11.327
274776LINCOLN ;7U
Adder
11.327
274777LINCOLN ;8U
Adder
11.327
274687WILL CNTY;4U
Adder
37.1
274687WILL CNTY;4U
Adder
37.1
972228AH1-698 GEN2
Adder
4.85
972227AH1-698 GEN1
Adder
3.414
274675JOLIET 29;7U
Adder
40.161
274675JOLIET 29;7U
Adder
38.727
274728ELWOOD EC;5P
Adder
21.296
274731ELWOOD EC;2P
Adder
21.293
274733ELWOOD EC;3P
Adder
21.293
274735ELWOOD EC;4P
Adder
21.293
970833AG2-524 GEN
Solar/Wind Harmer
9.725
970833AG2-524 GEN
Solar/Wind Harmer
6.483
274744AC1-111 GEN8
Adder
7.03
274746AC1-111 G10
Adder
7.03
970073AG2-061 GEN
Solar/Wind Harmer
2.831
971411AH1-196 GEN
Solar/Wind Harmer
12.452
971675AH1-338 GEN
Solar/Wind Harmer
3.221
276861AD2-134 GEN
Solar/Wind Harmer
0.147
276863AD2-134 GEN
Solar/Wind Harmer
0.147
971171AH1-044 GEN
Solar/Wind Harmer
16.342
274823ROCKFORD ;21
Adder
22.75
274856ECOGROVE ;U1
Solar/Wind Harmer
0.188
971681AH1-341 GEN
Solar/Wind Harmer
12.757
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.325
972267AH1-718 GEN
Adder
4.603
276741O09 GEN1
Solar/Wind Harmer
0.269
970169AG2-114 GEN
Solar/Wind Harmer
7.493
274877BISHOP HL;1U
Solar/Wind Harmer
0.246
946321AF1-296 GEN
Solar/Wind Harmer
4.081
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.043
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.209
276848AB2-070 GEN3
Solar/Wind Harmer
0.208
276849AB2-070 GEN2
Solar/Wind Harmer
0.209
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.348
274887GEN-1.85
Solar/Wind Harmer
0.25
276843GEN-1.7
Solar/Wind Harmer
0.311
276806AD2-047 C O1
Solar/Wind Harmer
5.453
274803UNIV PARK;6U
Adder
7.895
274772LINCOLN ;3U
Adder
11.327
274676JOLIET 29;8U
Adder
38.726
274730ELWOOD EC;6P
Adder
21.296
274734ELWOOD EC;8P
Adder
21.296
274736ELWOOD EC;9P
Adder
21.296
274729ELWOOD EC;1P
Adder
21.293
972259AH1-714 GEN
Adder
24.673
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
29.274
274814UNIV PK N;0U
Adder
6.419
274807UNIV PK N;3U
Adder
6.405
274811UNIV PK N;7U
Adder
6.364
943121AE2-341 GEN
Solar/Wind Harmer
14.682
943591AF1-030 GEN
Solar/Wind Harmer
9.763
274862TOP CROP ;2U
Solar/Wind Harmer
1.176
274682WAUKEGAN ;7U
Adder
22.292
274752CRETE EC ;2U
Adder
9.959
274753CRETE EC ;3U
Adder
9.959
276868AE1-113 GEN
Solar/Wind Harmer
1.67
274879MINONK ;1U
Solar/Wind Harmer
0.348
946671AF1-331 GEN
Solar/Wind Harmer
0.882
274855GSG-6 ;RU
Solar/Wind Harmer
0.301
274850MENDOTA H;RU
Solar/Wind Harmer
0.096
959091AF2-200 GEN
Solar/Wind Harmer
16.342
970571AG2-364 GEN
Solar/Wind Harmer
15.818
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
10.493
274767LEE CO EC;8U
Adder
10.369
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.246
965931AG1-462 GEN
Solar/Wind Harmer
18.382
971087AG2-675 GEN
Solar/Wind Harmer
3.845
965091AG1-374 GEN
Solar/Wind Harmer
19.211
959611AF2-252 GEN
Solar/Wind Harmer
2.135
971993AH1-541 GEN
Solar/Wind Harmer
2.456
957381AF2-032 GEN
Solar/Wind Harmer
1.053
942481AE2-261 GEN
Solar/Wind Harmer
13.741
990577J1339
External Queue
21.47968864440918
990647J1355
External Queue
43.162841796875
991777J1629 G
External Queue
12.10804271697998
991247J1684 G
External Queue
27.830068588256836
990582J1340
External Queue
21.47968864440918
990662J1358
External Queue
14.842607498168945
990512J1326
External Queue
5.34079122543335
991337J1802
External Queue
7.773519515991211
990117J1214
External Queue
18.3723201751709
990727J1377 G
External Queue
6.2205705642700195
990552J1334 G
External Queue
34.041297912597656
990562J1336 G
External Queue
34.041297912597656
991092J1477
External Queue
2.807737350463867
990762J1386
External Queue
10.094657897949219
991332J1785
External Queue
11.870986938476562
990547J1333 G
External Queue
34.041297912597656
990557J1335 G
External Queue
34.041297912597656
991303J1755 G
External Queue
4.588634490966797
990407J1304
External Queue
4.146153450012207
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.198
NYPJM->LTFIMP_NY
CLTF
1.09
WECLTFEXP_WEC->PJM
CLTF
4.451
CBM West 1LTFEXP_CBM-W1->PJM
CBM
84.949
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.376
MECLTFEXP_MEC->PJM
CLTF
14.037
SIGELTFEXP_SIGE->PJM
CLTF
0.034
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.415
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.366
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.978
LAGNLTFEXP_LAGN->PJM
CLTF
4.881
TVALTFEXP_TVA->PJM
CLTF
1.32

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P7-1_#11009___SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11009___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.04 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2117.86
MW Contribution:
12.9
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11009___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.2 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2157.66
MW Contribution:
13.05
Bus #Bus NameTypeMW Contribution
274815UNIV PK N;XU
50/50
0.362
274723RIVER EC ;12
50/50
28.342
972179AH1-673 GEN
50/50
14.634
274751CRETE EC ;1U
50/50
6.871
274754CRETE EC ;4U
50/50
6.871
274806UNIV PK N;2U
50/50
0.368
274810UNIV PK N;6U
50/50
0.36
274812UNIV PK N;8U
50/50
6.587
274802UNIV PARK;5U
Adder
6.905
274676JOLIET 29;8U
Adder
32.342
274674JOLIET 9 ;6U
Adder
16.144
274732ELWOOD EC;7P
Adder
17.101
274861TOP CROP ;1U
Solar/Wind Harmer
6.222
276694AA1-018 GEN2
Solar/Wind Harmer
6.475
276691AA1-018 GEN1
Solar/Wind Harmer
0.774
276805AD2-038 GEN
Solar/Wind Harmer
5.065
941551AE2-152 GEN
Solar/Wind Harmer
4.403
274682WAUKEGAN ;7U
Adder
17.174
274871GR RIDGE ;2U
Solar/Wind Harmer
7.331
961501AF2-441 GEN
50/50
13.121
274827FISK ;RP
50/50
9.918
960681AF2-359 GEN
Solar/Wind Harmer
5.46
274800UNIV PARK;3U
Adder
6.924
274801UNIV PARK;4U
Adder
6.924
972037AH1-567 GEN1
Adder
0.217
960591AF2-350 GEN
Solar/Wind Harmer
11.356
274687WILL CNTY;4U
Adder
30.297
274687WILL CNTY;4U
Adder
30.297
276893AG1-478 C
Solar/Wind Harmer
0.584
274675JOLIET 29;7U
Adder
32.34
274675JOLIET 29;7U
Adder
31.185
972228AH1-698 GEN2
Adder
3.882
972227AH1-698 GEN1
Adder
2.732
274728ELWOOD EC;5P
Adder
17.101
274731ELWOOD EC;2P
Adder
17.092
274733ELWOOD EC;3P
Adder
17.092
274735ELWOOD EC;4P
Adder
17.092
970073AG2-061 GEN
Solar/Wind Harmer
2.297
970833AG2-524 GEN
Solar/Wind Harmer
8.385
970833AG2-524 GEN
Solar/Wind Harmer
3.9
274744AC1-111 GEN8
Adder
5.242
274746AC1-111 G10
Adder
5.242
276889AE2-281 GEN
Solar/Wind Harmer
1.793
971411AH1-196 GEN
Solar/Wind Harmer
13.539
971675AH1-338 GEN
Solar/Wind Harmer
15.949
276861AD2-134 GEN
Solar/Wind Harmer
1.581
276863AD2-134 GEN
Solar/Wind Harmer
1.581
274823ROCKFORD ;21
Adder
17.242
971171AH1-044 GEN
Solar/Wind Harmer
17.645
274856ECOGROVE ;U1
Solar/Wind Harmer
2.942
276611AD2-172 GEN
Solar/Wind Harmer
2.231
276612AE2-035 GEN
Solar/Wind Harmer
2.231
971681AH1-341 GEN
Solar/Wind Harmer
12.898
926823AC1-168 GEN
Solar/Wind Harmer
3.681
972267AH1-718 GEN
Adder
3.49
276741O09 GEN1
Solar/Wind Harmer
2.972
274775LINCOLN ;6U
Adder
5.134
274776LINCOLN ;7U
Adder
5.134
274777LINCOLN ;8U
Adder
5.134
274813UNIV PK N;9U
50/50
0.361
274816UNIV PK N;YU
50/50
0.361
274809UNIV PK N;5U
50/50
0.359
274805UNIV PK N;1U
50/50
6.601
274808UNIV PK N;4U
50/50
6.558
965681AG1-436 GEN
Solar/Wind Harmer
18.063
965791AG1-447 GEN
Solar/Wind Harmer
9.242
274888KELLY CRK;1U
Solar/Wind Harmer
6.701
958011AF2-095 GEN
Solar/Wind Harmer
16.353
970941AG2-585 GEN
Solar/Wind Harmer
6.246
276776AD2-060 GEN
Solar/Wind Harmer
0.475
276893AG1-478 C
Solar/Wind Harmer
0.466
274674JOLIET 9 ;6U
Adder
16.144
958481AF2-142 GEN
Solar/Wind Harmer
15.393
958491AF2-143 GEN
Solar/Wind Harmer
14.818
276897AD1-100 C
Solar/Wind Harmer
45.102
274683WAUKEGAN ;8U
Adder
20.085
274683WAUKEGAN ;8U
Adder
16.931
276901AD2-066 C O1
Solar/Wind Harmer
3.299
276872AE1-163_GEN1
Solar/Wind Harmer
6.276
276876AE1-163_GEN2
Solar/Wind Harmer
6.276
274696ROCKY RD ;4P
Adder
10.636
274695ROCKY RD ;2P
Adder
10.391
274693ROCKY RD ;1P
Adder
10.289
274697ROCKY RD ;3P
Adder
2.823
962691AG1-118 GEN
Solar/Wind Harmer
27.185
960751AF2-366 GEN
Solar/Wind Harmer
2.59
971341AH1-150 GEN
Solar/Wind Harmer
17.645
971343AH1-151 GEN
Solar/Wind Harmer
17.645
972235AH1-702 GEN1
Adder
2.218
972236AH1-702 GEN2
Adder
1.929
938861AE1-114 GEN
Solar/Wind Harmer
7.054
274764LEE CO EC;5U
Adder
7.971
274765LEE CO EC;6U
Adder
7.971
274762LEE CO EC;3U
Adder
7.952
274763LEE CO EC;4U
Adder
7.877
276158O29GEN2
Solar/Wind Harmer
4.163
276157O29GEN1
Solar/Wind Harmer
3.165
274770LINCOLN ;1U
Adder
5.134
274771LINCOLN ;2U
Adder
5.134
276645AC1-214 GEN1
Solar/Wind Harmer
1.099
942111AE2-223 GEN
Solar/Wind Harmer
5.849
274847GR RIDGE ;BU
Solar/Wind Harmer
4.82
274828WAUKEGAN ;BP
Adder
10.528
276882AE2-255 GEN
Solar/Wind Harmer
3.2
274745AC1-111 GEN9
Adder
5.242
962781AG1-127 GEN
Solar/Wind Harmer
8.583
274872LEEDK;1U
Solar/Wind Harmer
7.375
970569AG2-363 GEN
Solar/Wind Harmer
26.944
971997AH1-543 GEN
Solar/Wind Harmer
14.072
274822ROCKFORD ;11
Adder
17.368
957471AF2-041 GEN
Solar/Wind Harmer
26.468
959081AF2-199 GEN
Solar/Wind Harmer
8.823
971067AG2-660 GEN
Solar/Wind Harmer
2.052
970819AG2-516 GEN
Solar/Wind Harmer
10.514
939401AE1-172 GEN
Solar/Wind Harmer
11.93
274858EASY ROAD;U2
Solar/Wind Harmer
4.095
274761LEE CO EC;2U
Adder
7.952
274766LEE CO EC;7U
Adder
7.859
276708O09 GEN2
Solar/Wind Harmer
2.972
972207SS24-0001
Solar/Wind Harmer
18.254
274773LINCOLN ;4U
Adder
5.134
274774LINCOLN ;5U
Adder
5.134
276646AC1-214 GEN2
Solar/Wind Harmer
1.099
274848CAMPGROVE;RU
Solar/Wind Harmer
5.197
276655WTG1_EQ
Solar/Wind Harmer
6.227
276656WTG2_EQ
Solar/Wind Harmer
0.825
939741AE1-205 GEN
Solar/Wind Harmer
14.269
274863CRW1-WTG
Solar/Wind Harmer
4.602
274864CRW2-WTG
Solar/Wind Harmer
4.602
274877BISHOP HL;1U
Solar/Wind Harmer
2.744
970169AG2-114 GEN
Solar/Wind Harmer
7.957
946321AF1-296 GEN
Solar/Wind Harmer
8.293
276726Z2-087_GEN
Solar/Wind Harmer
5.641
959341AF2-225 GEN
Solar/Wind Harmer
10.702
274853TWINGROVE;U1
Solar/Wind Harmer
4.914
274854TWINGROVE;U2
Solar/Wind Harmer
4.811
274724RIVER EC ;11
50/50
28.296
957371AF2-031 GEN
50/50
1.401
274752CRETE EC ;2U
50/50
6.871
274753CRETE EC ;3U
50/50
6.871
274814UNIV PK N;0U
50/50
6.645
274807UNIV PK N;3U
50/50
6.63
274811UNIV PK N;7U
50/50
6.587
274826FISK ;BP
50/50
13.994
276164X3-005 C
Solar/Wind Harmer
0.941
972231SS25-0005
Solar/Wind Harmer
12.572
972181SS23-001
Solar/Wind Harmer
7.858
972038AH1-567 GEN2
Adder
0.433
274803UNIV PARK;6U
Adder
6.905
274887GEN-1.85
Solar/Wind Harmer
6.051
276843GEN-1.7
Solar/Wind Harmer
0.651
276772AC2-154 GEN
Solar/Wind Harmer
3.169
276806AD2-047 C O1
Solar/Wind Harmer
12.149
274676JOLIET 29;8U
Adder
31.187
274730ELWOOD EC;6P
Adder
17.101
274734ELWOOD EC;8P
Adder
17.101
274736ELWOOD EC;9P
Adder
17.101
274729ELWOOD EC;1P
Adder
17.092
274862TOP CROP ;2U
Solar/Wind Harmer
5.195
939351AE1-166 GEN
Solar/Wind Harmer
5.758
972259AH1-714 GEN
Adder
18.513
274682WAUKEGAN ;7U
Adder
17.174
276868AE1-113 GEN
Solar/Wind Harmer
9.6
274879MINONK ;1U
Solar/Wind Harmer
6.4
943121AE2-341 GEN
Solar/Wind Harmer
13.719
943591AF1-030 GEN
Solar/Wind Harmer
9.146
970571AG2-364 GEN
Solar/Wind Harmer
17.963
970707AG2-453 GEN
Solar/Wind Harmer
25.113
276799AD1-013 GEN
Solar/Wind Harmer
1.959
946671AF1-331 GEN
Solar/Wind Harmer
0.371
274855GSG-6 ;RU
Solar/Wind Harmer
3.27
274850MENDOTA H;RU
Solar/Wind Harmer
2.274
276602WESTBROOK C
Solar/Wind Harmer
1.882
959091AF2-200 GEN
Solar/Wind Harmer
17.645
274857EASY ROAD;U1
Solar/Wind Harmer
4.095
274760LEE CO EC;1U
Adder
7.952
274767LEE CO EC;8U
Adder
7.859
276603SUBLETTE C
Solar/Wind Harmer
0.891
274772LINCOLN ;3U
Adder
5.134
274851PROVIDENC;RU
Solar/Wind Harmer
2.337
274849CRESCENT ;1U
Solar/Wind Harmer
1.517
276782AC1-033 GEN
Solar/Wind Harmer
3.244
274878BISHOP HL;2U
Solar/Wind Harmer
2.744
965931AG1-462 GEN
Solar/Wind Harmer
20.063
971087AG2-675 GEN
Solar/Wind Harmer
2.928
965091AG1-374 GEN
Solar/Wind Harmer
20.071
990577J1339
External Queue
26.58072280883789
990647J1355
External Queue
44.69670867919922
991247J1684 G
External Queue
32.17827224731445
990582J1340
External Queue
26.58072280883789
990662J1358
External Queue
16.01173210144043
990512J1326
External Queue
4.03797721862793
990552J1334 G
External Queue
37.614933013916016
990562J1336 G
External Queue
37.614933013916016
990762J1386
External Queue
12.96505069732666
991332J1785
External Queue
12.403820037841797
990547J1333 G
External Queue
37.614933013916016
990557J1335 G
External Queue
37.614933013916016
NYPJM->LTFIMP_NY
CLTF
0.821
WECLTFEXP_WEC->PJM
CLTF
3.416
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.294
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.952
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.996
MECLTFEXP_MEC->PJM
CLTF
10.73
SIGELTFEXP_SIGE->PJM
CLTF
0.027
AG2-052LTFEXP_AG2-052->PJM
LTF
0.554
AH1-155LTFEXP_AH1-155->PJM
LTF
0.831
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.25
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.66
LAGNLTFEXP_LAGN->PJM
CLTF
3.768
TVALTFEXP_TVA->PJM
CLTF
1.032

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P7-1_#11009___SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11009___SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.57 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2090.79
MW Contribution:
12.91
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11009___SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.56 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2127.5
MW Contribution:
13.06
Bus #Bus NameTypeMW Contribution
274815UNIV PK N;XU
50/50
0.362
274813UNIV PK N;9U
50/50
0.361
274816UNIV PK N;YU
50/50
0.361
961501AF2-441 GEN
50/50
13.13
274827FISK ;RP
50/50
9.925
274800UNIV PARK;3U
Adder
6.93
274801UNIV PARK;4U
Adder
6.93
972037AH1-567 GEN1
Adder
0.217
960591AF2-350 GEN
Solar/Wind Harmer
11.365
274687WILL CNTY;4U
Adder
30.322
274687WILL CNTY;4U
Adder
30.322
276893AG1-478 C
Solar/Wind Harmer
0.585
274675JOLIET 29;7U
Adder
32.367
274675JOLIET 29;7U
Adder
31.211
972228AH1-698 GEN2
Adder
3.885
972227AH1-698 GEN1
Adder
2.734
274728ELWOOD EC;5P
Adder
17.116
274731ELWOOD EC;2P
Adder
17.107
274733ELWOOD EC;3P
Adder
17.107
274735ELWOOD EC;4P
Adder
17.107
970073AG2-061 GEN
Solar/Wind Harmer
2.299
274809UNIV PK N;5U
50/50
0.36
274805UNIV PK N;1U
50/50
6.606
274808UNIV PK N;4U
50/50
6.563
274888KELLY CRK;1U
Solar/Wind Harmer
6.707
276776AD2-060 GEN
Solar/Wind Harmer
0.476
958011AF2-095 GEN
Solar/Wind Harmer
16.366
970941AG2-585 GEN
Solar/Wind Harmer
6.251
276893AG1-478 C
Solar/Wind Harmer
0.466
274674JOLIET 9 ;6U
Adder
16.158
958481AF2-142 GEN
Solar/Wind Harmer
15.407
958491AF2-143 GEN
Solar/Wind Harmer
14.831
276897AD1-100 C
Solar/Wind Harmer
45.144
274683WAUKEGAN ;8U
Adder
20.104
274683WAUKEGAN ;8U
Adder
16.946
276901AD2-066 C O1
Solar/Wind Harmer
3.302
276872AE1-163_GEN1
Solar/Wind Harmer
6.282
276876AE1-163_GEN2
Solar/Wind Harmer
6.282
274696ROCKY RD ;4P
Adder
10.647
274695ROCKY RD ;2P
Adder
10.401
274693ROCKY RD ;1P
Adder
10.298
274697ROCKY RD ;3P
Adder
2.825
962691AG1-118 GEN
Solar/Wind Harmer
27.212
960751AF2-366 GEN
Solar/Wind Harmer
2.592
971341AH1-150 GEN
Solar/Wind Harmer
17.663
971343AH1-151 GEN
Solar/Wind Harmer
17.663
972235AH1-702 GEN1
Adder
2.221
972236AH1-702 GEN2
Adder
1.931
938861AE1-114 GEN
Solar/Wind Harmer
7.061
274764LEE CO EC;5U
Adder
7.979
274765LEE CO EC;6U
Adder
7.979
274762LEE CO EC;3U
Adder
7.961
274763LEE CO EC;4U
Adder
7.886
276158O29GEN2
Solar/Wind Harmer
4.168
276157O29GEN1
Solar/Wind Harmer
3.169
274770LINCOLN ;1U
Adder
5.14
274771LINCOLN ;2U
Adder
5.14
276645AC1-214 GEN1
Solar/Wind Harmer
1.1
942111AE2-223 GEN
Solar/Wind Harmer
5.856
960611AF2-352 GEN
Solar/Wind Harmer
1.588
274880W4-005 GEN4
Solar/Wind Harmer
0.35
276174W4-005 GEN2
Solar/Wind Harmer
0.35
274723RIVER EC ;12
50/50
28.359
972179AH1-673 GEN
50/50
14.643
274751CRETE EC ;1U
50/50
6.876
274754CRETE EC ;4U
50/50
6.876
274806UNIV PK N;2U
50/50
0.368
274810UNIV PK N;6U
50/50
0.36
274812UNIV PK N;8U
50/50
6.592
274802UNIV PARK;5U
Adder
6.91
274676JOLIET 29;8U
Adder
32.369
274674JOLIET 9 ;6U
Adder
16.158
274732ELWOOD EC;7P
Adder
17.116
274861TOP CROP ;1U
Solar/Wind Harmer
6.227
276694AA1-018 GEN2
Solar/Wind Harmer
6.481
276691AA1-018 GEN1
Solar/Wind Harmer
0.775
276805AD2-038 GEN
Solar/Wind Harmer
5.07
941551AE2-152 GEN
Solar/Wind Harmer
4.408
274682WAUKEGAN ;7U
Adder
17.19
274871GR RIDGE ;2U
Solar/Wind Harmer
7.337
274847GR RIDGE ;BU
Solar/Wind Harmer
4.825
274828WAUKEGAN ;BP
Adder
10.538
276882AE2-255 GEN
Solar/Wind Harmer
3.203
274745AC1-111 GEN9
Adder
5.247
962781AG1-127 GEN
Solar/Wind Harmer
8.592
274872LEEDK;1U
Solar/Wind Harmer
7.382
970569AG2-363 GEN
Solar/Wind Harmer
26.971
971997AH1-543 GEN
Solar/Wind Harmer
14.086
274822ROCKFORD ;11
Adder
17.386
957471AF2-041 GEN
Solar/Wind Harmer
26.495
959081AF2-199 GEN
Solar/Wind Harmer
8.832
971067AG2-660 GEN
Solar/Wind Harmer
2.054
970819AG2-516 GEN
Solar/Wind Harmer
10.525
939401AE1-172 GEN
Solar/Wind Harmer
11.942
274858EASY ROAD;U2
Solar/Wind Harmer
4.099
274761LEE CO EC;2U
Adder
7.961
274766LEE CO EC;7U
Adder
7.867
276708O09 GEN2
Solar/Wind Harmer
2.976
972207SS24-0001
Solar/Wind Harmer
18.274
274773LINCOLN ;4U
Adder
5.14
274774LINCOLN ;5U
Adder
5.14
276646AC1-214 GEN2
Solar/Wind Harmer
1.1
274848CAMPGROVE;RU
Solar/Wind Harmer
5.203
276655WTG1_EQ
Solar/Wind Harmer
6.235
276656WTG2_EQ
Solar/Wind Harmer
0.826
939741AE1-205 GEN
Solar/Wind Harmer
14.287
276686W4-005 GEN3
Solar/Wind Harmer
0.35
970833AG2-524 GEN
Solar/Wind Harmer
8.393
970833AG2-524 GEN
Solar/Wind Harmer
3.904
274744AC1-111 GEN8
Adder
5.247
274746AC1-111 G10
Adder
5.247
276889AE2-281 GEN
Solar/Wind Harmer
1.795
971411AH1-196 GEN
Solar/Wind Harmer
13.552
971675AH1-338 GEN
Solar/Wind Harmer
15.965
276861AD2-134 GEN
Solar/Wind Harmer
1.583
276863AD2-134 GEN
Solar/Wind Harmer
1.583
274823ROCKFORD ;21
Adder
17.259
971171AH1-044 GEN
Solar/Wind Harmer
17.663
274856ECOGROVE ;U1
Solar/Wind Harmer
2.945
276611AD2-172 GEN
Solar/Wind Harmer
2.234
276612AE2-035 GEN
Solar/Wind Harmer
2.234
971681AH1-341 GEN
Solar/Wind Harmer
12.911
926823AC1-168 GEN
Solar/Wind Harmer
3.684
972267AH1-718 GEN
Adder
3.494
276741O09 GEN1
Solar/Wind Harmer
2.976
274775LINCOLN ;6U
Adder
5.14
274776LINCOLN ;7U
Adder
5.14
274777LINCOLN ;8U
Adder
5.14
274863CRW1-WTG
Solar/Wind Harmer
4.607
274864CRW2-WTG
Solar/Wind Harmer
4.607
274877BISHOP HL;1U
Solar/Wind Harmer
2.747
970169AG2-114 GEN
Solar/Wind Harmer
7.966
946321AF1-296 GEN
Solar/Wind Harmer
8.303
276726Z2-087_GEN
Solar/Wind Harmer
5.648
959341AF2-225 GEN
Solar/Wind Harmer
10.715
274853TWINGROVE;U1
Solar/Wind Harmer
4.92
274854TWINGROVE;U2
Solar/Wind Harmer
4.817
960681AF2-359 GEN
Solar/Wind Helper
0.965
274724RIVER EC ;11
50/50
28.313
957371AF2-031 GEN
50/50
1.402
274752CRETE EC ;2U
50/50
6.876
274753CRETE EC ;3U
50/50
6.876
274814UNIV PK N;0U
50/50
6.649
274807UNIV PK N;3U
50/50
6.635
274811UNIV PK N;7U
50/50
6.592
274826FISK ;BP
50/50
14.005
276164X3-005 C
Solar/Wind Harmer
0.942
972231SS25-0005
Solar/Wind Harmer
12.581
972181SS23-001
Solar/Wind Harmer
7.863
972038AH1-567 GEN2
Adder
0.434
274803UNIV PARK;6U
Adder
6.91
274887GEN-1.85
Solar/Wind Harmer
6.055
276772AC2-154 GEN
Solar/Wind Harmer
3.172
276843GEN-1.7
Solar/Wind Harmer
0.652
276806AD2-047 C O1
Solar/Wind Harmer
12.158
274676JOLIET 29;8U
Adder
31.213
274730ELWOOD EC;6P
Adder
17.116
274734ELWOOD EC;8P
Adder
17.116
274736ELWOOD EC;9P
Adder
17.116
274729ELWOOD EC;1P
Adder
17.107
274862TOP CROP ;2U
Solar/Wind Harmer
5.199
939351AE1-166 GEN
Solar/Wind Harmer
5.763
972259AH1-714 GEN
Adder
18.53
274682WAUKEGAN ;7U
Adder
17.19
276868AE1-113 GEN
Solar/Wind Harmer
9.609
274879MINONK ;1U
Solar/Wind Harmer
6.406
943121AE2-341 GEN
Solar/Wind Harmer
13.732
943591AF1-030 GEN
Solar/Wind Harmer
9.155
970571AG2-364 GEN
Solar/Wind Harmer
17.981
970707AG2-453 GEN
Solar/Wind Harmer
25.138
276799AD1-013 GEN
Solar/Wind Harmer
1.961
946671AF1-331 GEN
Solar/Wind Harmer
0.372
274855GSG-6 ;RU
Solar/Wind Harmer
3.273
274850MENDOTA H;RU
Solar/Wind Harmer
2.276
276602WESTBROOK C
Solar/Wind Harmer
1.884
959091AF2-200 GEN
Solar/Wind Harmer
17.663
274857EASY ROAD;U1
Solar/Wind Harmer
4.099
274760LEE CO EC;1U
Adder
7.961
274767LEE CO EC;8U
Adder
7.867
276603SUBLETTE C
Solar/Wind Harmer
0.892
274772LINCOLN ;3U
Adder
5.14
274851PROVIDENC;RU
Solar/Wind Harmer
2.34
274849CRESCENT ;1U
Solar/Wind Harmer
1.519
276782AC1-033 GEN
Solar/Wind Harmer
3.247
274878BISHOP HL;2U
Solar/Wind Harmer
2.747
965931AG1-462 GEN
Solar/Wind Harmer
20.086
971087AG2-675 GEN
Solar/Wind Harmer
2.931
965091AG1-374 GEN
Solar/Wind Harmer
20.489
959611AF2-252 GEN
Solar/Wind Harmer
1.588
276785W4-005 GEN1
Solar/Wind Harmer
0.35
990577J1339
External Queue
26.58072280883789
990647J1355
External Queue
44.69670867919922
991247J1684 G
External Queue
32.17827224731445
990582J1340
External Queue
26.58072280883789
990662J1358
External Queue
16.01173210144043
990512J1326
External Queue
4.03797721862793
991337J1802
External Queue
9.807985305786133
990552J1334 G
External Queue
37.614933013916016
990562J1336 G
External Queue
37.614933013916016
990762J1386
External Queue
12.96505069732666
991332J1785
External Queue
12.403820037841797
990547J1333 G
External Queue
37.614933013916016
990557J1335 G
External Queue
37.614933013916016
NYPJM->LTFIMP_NY
CLTF
0.815
WECLTFEXP_WEC->PJM
CLTF
3.419
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.288
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.073
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.03
MECLTFEXP_MEC->PJM
CLTF
10.745
SIGELTFEXP_SIGE->PJM
CLTF
0.028
AG2-052LTFEXP_AG2-052->PJM
LTF
0.554
AH1-155LTFEXP_AH1-155->PJM
LTF
0.831
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.244
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.642
LAGNLTFEXP_LAGN->PJM
CLTF
3.787
TVALTFEXP_TVA->PJM
CLTF
1.042

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#18494_05LARRISN DR 345_CB1_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#18494_05LARRISN DR 345_CB1_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.62 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:1944.43
MW Contribution:
10.28
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
961501AF2-441 GEN
50/50
11.164
274827FISK ;RP
50/50
8.107
274800UNIV PARK;3U
Adder
5.669
274801UNIV PARK;4U
Adder
5.669
972037AH1-567 GEN1
Adder
0.173
960591AF2-350 GEN
Solar/Wind Harmer
9.216
274687WILL CNTY;4U
Adder
24.286
274687WILL CNTY;4U
Adder
24.286
276893AG1-478 C
Solar/Wind Harmer
0.47
274675JOLIET 29;7U
Adder
25.79
274675JOLIET 29;7U
Adder
24.869
972228AH1-698 GEN2
Adder
3.077
972227AH1-698 GEN1
Adder
2.165
274728ELWOOD EC;5P
Adder
13.63
274731ELWOOD EC;2P
Adder
13.623
274733ELWOOD EC;3P
Adder
13.623
274735ELWOOD EC;4P
Adder
13.623
970073AG2-061 GEN
Solar/Wind Harmer
1.839
970833AG2-524 GEN
Solar/Wind Harmer
6.644
970833AG2-524 GEN
Solar/Wind Harmer
3.09
276889AE2-281 GEN
Solar/Wind Harmer
1.437
274744AC1-111 GEN8
Adder
4.155
274746AC1-111 G10
Adder
4.155
971411AH1-196 GEN
Solar/Wind Harmer
10.771
274823ROCKFORD ;21
Adder
13.727
971675AH1-338 GEN
Solar/Wind Harmer
12.676
276861AD2-134 GEN
Solar/Wind Harmer
1.257
276863AD2-134 GEN
Solar/Wind Harmer
1.257
971171AH1-044 GEN
Solar/Wind Harmer
14.038
274856ECOGROVE ;U1
Solar/Wind Harmer
2.344
276611AD2-172 GEN
Solar/Wind Harmer
1.778
276612AE2-035 GEN
Solar/Wind Harmer
1.778
971681AH1-341 GEN
Solar/Wind Harmer
10.282
926823AC1-168 GEN
Solar/Wind Harmer
2.946
972267AH1-718 GEN
Adder
2.786
276741O09 GEN1
Solar/Wind Harmer
2.376
274863CRW1-WTG
Solar/Wind Harmer
3.691
274864CRW2-WTG
Solar/Wind Harmer
3.691
274877BISHOP HL;1U
Solar/Wind Harmer
2.204
274775LINCOLN ;6U
Adder
4.013
274776LINCOLN ;7U
Adder
4.013
274777LINCOLN ;8U
Adder
4.013
970169AG2-114 GEN
Solar/Wind Harmer
6.401
946321AF1-296 GEN
Solar/Wind Harmer
6.64
276726Z2-087_GEN
Solar/Wind Harmer
4.589
959341AF2-225 GEN
Solar/Wind Harmer
8.705
274853TWINGROVE;U1
Solar/Wind Harmer
4.011
274854TWINGROVE;U2
Solar/Wind Harmer
3.927
276668AB2-070 GEN1
Solar/Wind Harmer
0.388
274805UNIV PK N;1U
Adder
4.767
274808UNIV PK N;4U
Adder
4.735
274888KELLY CRK;1U
Solar/Wind Harmer
5.438
276776AD2-060 GEN
Solar/Wind Harmer
0.386
958011AF2-095 GEN
Solar/Wind Harmer
13.271
970941AG2-585 GEN
Solar/Wind Harmer
5.069
276893AG1-478 C
Solar/Wind Harmer
0.374
274674JOLIET 9 ;6U
Adder
12.968
958481AF2-142 GEN
Solar/Wind Harmer
12.319
958491AF2-143 GEN
Solar/Wind Harmer
11.865
276897AD1-100 C
Solar/Wind Harmer
35.876
274683WAUKEGAN ;8U
Adder
15.98
274683WAUKEGAN ;8U
Adder
13.47
276901AD2-066 C O1
Solar/Wind Harmer
2.64
276872AE1-163_GEN1
Solar/Wind Harmer
5.03
276876AE1-163_GEN2
Solar/Wind Harmer
5.03
274696ROCKY RD ;4P
Adder
8.445
274695ROCKY RD ;2P
Adder
8.25
274693ROCKY RD ;1P
Adder
8.169
274697ROCKY RD ;3P
Adder
2.241
962691AG1-118 GEN
Solar/Wind Harmer
21.572
960751AF2-366 GEN
Solar/Wind Harmer
2.055
971341AH1-150 GEN
Solar/Wind Harmer
14.038
971343AH1-151 GEN
Solar/Wind Harmer
14.038
972235AH1-702 GEN1
Adder
1.766
972236AH1-702 GEN2
Adder
1.536
938861AE1-114 GEN
Solar/Wind Harmer
5.623
274764LEE CO EC;5U
Adder
6.356
274765LEE CO EC;6U
Adder
6.356
274762LEE CO EC;3U
Adder
6.341
274763LEE CO EC;4U
Adder
6.281
276158O29GEN2
Solar/Wind Harmer
3.328
276157O29GEN1
Solar/Wind Harmer
2.531
276645AC1-214 GEN1
Solar/Wind Harmer
0.883
274770LINCOLN ;1U
Adder
4.013
274771LINCOLN ;2U
Adder
4.013
942111AE2-223 GEN
Solar/Wind Harmer
4.757
960611AF2-352 GEN
Solar/Wind Harmer
1.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
276849AB2-070 GEN2
Solar/Wind Harmer
0.388
274724RIVER EC ;11
50/50
24.394
957371AF2-031 GEN
50/50
1.208
274752CRETE EC ;2U
50/50
5.119
274753CRETE EC ;3U
50/50
5.119
274826FISK ;BP
50/50
11.439
276164X3-005 C
Solar/Wind Harmer
0.791
972231SS25-0005
Solar/Wind Harmer
9.366
972181SS23-001
Solar/Wind Harmer
5.854
972038AH1-567 GEN2
Adder
0.355
274814UNIV PK N;0U
Adder
4.798
274807UNIV PK N;3U
Adder
4.788
274811UNIV PK N;7U
Adder
4.756
274803UNIV PARK;6U
Adder
5.518
274887GEN-1.85
Solar/Wind Harmer
4.91
276772AC2-154 GEN
Solar/Wind Harmer
2.572
276843GEN-1.7
Solar/Wind Harmer
0.528
276806AD2-047 C O1
Solar/Wind Harmer
9.859
274676JOLIET 29;8U
Adder
24.871
274730ELWOOD EC;6P
Adder
13.63
274734ELWOOD EC;8P
Adder
13.63
274736ELWOOD EC;9P
Adder
13.63
274729ELWOOD EC;1P
Adder
13.623
274862TOP CROP ;2U
Solar/Wind Harmer
4.153
939351AE1-166 GEN
Solar/Wind Harmer
4.58
972259AH1-714 GEN
Adder
14.6
274682WAUKEGAN ;7U
Adder
13.663
276868AE1-113 GEN
Solar/Wind Harmer
7.677
274879MINONK ;1U
Solar/Wind Harmer
5.118
943121AE2-341 GEN
Solar/Wind Harmer
10.843
943591AF1-030 GEN
Solar/Wind Harmer
7.229
970571AG2-364 GEN
Solar/Wind Harmer
14.404
276799AD1-013 GEN
Solar/Wind Harmer
1.557
946671AF1-331 GEN
Solar/Wind Harmer
0.295
274855GSG-6 ;RU
Solar/Wind Harmer
2.599
274850MENDOTA H;RU
Solar/Wind Harmer
1.807
276602WESTBROOK C
Solar/Wind Harmer
1.496
970707AG2-453 GEN
Solar/Wind Harmer
19.673
959091AF2-200 GEN
Solar/Wind Harmer
14.038
274857EASY ROAD;U1
Solar/Wind Harmer
3.265
274760LEE CO EC;1U
Adder
6.341
274767LEE CO EC;8U
Adder
6.267
276603SUBLETTE C
Solar/Wind Harmer
0.711
274851PROVIDENC;RU
Solar/Wind Harmer
1.877
274849CRESCENT ;1U
Solar/Wind Harmer
1.219
276782AC1-033 GEN
Solar/Wind Harmer
2.605
274878BISHOP HL;2U
Solar/Wind Harmer
2.204
274772LINCOLN ;3U
Adder
4.013
965931AG1-462 GEN
Solar/Wind Harmer
16.071
971087AG2-675 GEN
Solar/Wind Harmer
2.345
965091AG1-374 GEN
Solar/Wind Harmer
16.701
959611AF2-252 GEN
Solar/Wind Harmer
1.295
274723RIVER EC ;12
50/50
24.332
972179AH1-673 GEN
50/50
12.545
274751CRETE EC ;1U
50/50
5.119
274754CRETE EC ;4U
50/50
5.119
274812UNIV PK N;8U
Adder
4.756
274802UNIV PARK;5U
Adder
5.518
274674JOLIET 9 ;6U
Adder
12.968
274676JOLIET 29;8U
Adder
25.792
274732ELWOOD EC;7P
Adder
13.63
276694AA1-018 GEN2
Solar/Wind Harmer
5.182
276691AA1-018 GEN1
Solar/Wind Harmer
0.619
274861TOP CROP ;1U
Solar/Wind Harmer
4.973
276805AD2-038 GEN
Solar/Wind Harmer
4.056
941551AE2-152 GEN
Solar/Wind Harmer
3.503
274682WAUKEGAN ;7U
Adder
13.663
276882AE2-255 GEN
Solar/Wind Harmer
2.559
274828WAUKEGAN ;BP
Adder
8.376
274871GR RIDGE ;2U
Solar/Wind Harmer
5.801
274847GR RIDGE ;BU
Solar/Wind Harmer
3.814
274745AC1-111 GEN9
Adder
4.155
970569AG2-363 GEN
Solar/Wind Harmer
21.606
962781AG1-127 GEN
Solar/Wind Harmer
6.813
274872LEEDK;1U
Solar/Wind Harmer
5.855
971997AH1-543 GEN
Solar/Wind Harmer
11.224
274822ROCKFORD ;11
Adder
13.827
957471AF2-041 GEN
Solar/Wind Harmer
21.057
959081AF2-199 GEN
Solar/Wind Harmer
7.019
971067AG2-660 GEN
Solar/Wind Harmer
1.632
970819AG2-516 GEN
Solar/Wind Harmer
8.375
939401AE1-172 GEN
Solar/Wind Harmer
9.539
274858EASY ROAD;U2
Solar/Wind Harmer
3.265
274761LEE CO EC;2U
Adder
6.341
274766LEE CO EC;7U
Adder
6.267
276708O09 GEN2
Solar/Wind Harmer
2.376
276646AC1-214 GEN2
Solar/Wind Harmer
0.883
274848CAMPGROVE;RU
Solar/Wind Harmer
4.179
972207SS24-0001
Solar/Wind Harmer
14.266
274773LINCOLN ;4U
Adder
4.013
274774LINCOLN ;5U
Adder
4.013
276655WTG1_EQ
Solar/Wind Harmer
5.065
276656WTG2_EQ
Solar/Wind Harmer
0.671
939741AE1-205 GEN
Solar/Wind Harmer
11.607
990577J1339
External Queue
22.606393814086914
990647J1355
External Queue
45.02376174926758
991247J1684 G
External Queue
28.46610450744629
990582J1340
External Queue
22.606393814086914
990662J1358
External Queue
16.966588973999023
991337J1802
External Queue
10.915008544921875
990552J1334 G
External Queue
34.18348693847656
990562J1336 G
External Queue
34.18348693847656
990762J1386
External Queue
10.307926177978516
991332J1785
External Queue
14.42030143737793
990547J1333 G
External Queue
34.18348693847656
990557J1335 G
External Queue
34.18348693847656
NYPJM->LTFIMP_NY
CLTF
0.719
WECLTFEXP_WEC->PJM
CLTF
2.723
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.266
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.506
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.227
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.612
MECLTFEXP_MEC->PJM
CLTF
8.664
SIGELTFEXP_SIGE->PJM
CLTF
0.032
AG2-052LTFEXP_AG2-052->PJM
LTF
0.531
AH1-155LTFEXP_AH1-155->PJM
LTF
0.796
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.164
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.402
LAGNLTFEXP_LAGN->PJM
CLTF
3.143
TVALTFEXP_TVA->PJM
CLTF
0.883

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A_SENS
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.62 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:1944.43
MW Contribution:
10.28
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
274723RIVER EC ;12
50/50
24.332
972179AH1-673 GEN
50/50
12.545
274751CRETE EC ;1U
50/50
5.119
274754CRETE EC ;4U
50/50
5.119
274812UNIV PK N;8U
Adder
4.756
274802UNIV PARK;5U
Adder
5.518
274674JOLIET 9 ;6U
Adder
12.968
274676JOLIET 29;8U
Adder
25.792
274732ELWOOD EC;7P
Adder
13.63
276694AA1-018 GEN2
Solar/Wind Harmer
5.182
276691AA1-018 GEN1
Solar/Wind Harmer
0.619
274861TOP CROP ;1U
Solar/Wind Harmer
4.973
276805AD2-038 GEN
Solar/Wind Harmer
4.056
941551AE2-152 GEN
Solar/Wind Harmer
3.503
274682WAUKEGAN ;7U
Adder
13.663
276882AE2-255 GEN
Solar/Wind Harmer
2.559
274828WAUKEGAN ;BP
Adder
8.376
274871GR RIDGE ;2U
Solar/Wind Harmer
5.801
274847GR RIDGE ;BU
Solar/Wind Harmer
3.814
274745AC1-111 GEN9
Adder
4.155
970569AG2-363 GEN
Solar/Wind Harmer
21.606
962781AG1-127 GEN
Solar/Wind Harmer
6.813
274872LEEDK;1U
Solar/Wind Harmer
5.855
971997AH1-543 GEN
Solar/Wind Harmer
11.224
274822ROCKFORD ;11
Adder
13.827
957471AF2-041 GEN
Solar/Wind Harmer
21.057
959081AF2-199 GEN
Solar/Wind Harmer
7.019
971067AG2-660 GEN
Solar/Wind Harmer
1.632
970819AG2-516 GEN
Solar/Wind Harmer
8.375
939401AE1-172 GEN
Solar/Wind Harmer
9.539
274858EASY ROAD;U2
Solar/Wind Harmer
3.265
274761LEE CO EC;2U
Adder
6.341
274766LEE CO EC;7U
Adder
6.267
276708O09 GEN2
Solar/Wind Harmer
2.376
276646AC1-214 GEN2
Solar/Wind Harmer
0.883
274848CAMPGROVE;RU
Solar/Wind Harmer
4.179
972207SS24-0001
Solar/Wind Harmer
14.266
274773LINCOLN ;4U
Adder
4.013
274774LINCOLN ;5U
Adder
4.013
276655WTG1_EQ
Solar/Wind Harmer
5.065
276656WTG2_EQ
Solar/Wind Harmer
0.671
939741AE1-205 GEN
Solar/Wind Harmer
11.607
274805UNIV PK N;1U
Adder
4.767
274808UNIV PK N;4U
Adder
4.735
274888KELLY CRK;1U
Solar/Wind Harmer
5.438
276776AD2-060 GEN
Solar/Wind Harmer
0.386
958011AF2-095 GEN
Solar/Wind Harmer
13.271
970941AG2-585 GEN
Solar/Wind Harmer
5.069
276893AG1-478 C
Solar/Wind Harmer
0.374
274674JOLIET 9 ;6U
Adder
12.968
958481AF2-142 GEN
Solar/Wind Harmer
12.319
958491AF2-143 GEN
Solar/Wind Harmer
11.865
276897AD1-100 C
Solar/Wind Harmer
35.876
274683WAUKEGAN ;8U
Adder
15.98
274683WAUKEGAN ;8U
Adder
13.47
276901AD2-066 C O1
Solar/Wind Harmer
2.64
276872AE1-163_GEN1
Solar/Wind Harmer
5.03
276876AE1-163_GEN2
Solar/Wind Harmer
5.03
274696ROCKY RD ;4P
Adder
8.445
274695ROCKY RD ;2P
Adder
8.25
274693ROCKY RD ;1P
Adder
8.169
274697ROCKY RD ;3P
Adder
2.241
962691AG1-118 GEN
Solar/Wind Harmer
21.572
960751AF2-366 GEN
Solar/Wind Harmer
2.055
971341AH1-150 GEN
Solar/Wind Harmer
14.038
971343AH1-151 GEN
Solar/Wind Harmer
14.038
972235AH1-702 GEN1
Adder
1.766
972236AH1-702 GEN2
Adder
1.536
938861AE1-114 GEN
Solar/Wind Harmer
5.623
274764LEE CO EC;5U
Adder
6.356
274765LEE CO EC;6U
Adder
6.356
274762LEE CO EC;3U
Adder
6.341
274763LEE CO EC;4U
Adder
6.281
276158O29GEN2
Solar/Wind Harmer
3.328
276157O29GEN1
Solar/Wind Harmer
2.531
276645AC1-214 GEN1
Solar/Wind Harmer
0.883
274770LINCOLN ;1U
Adder
4.013
274771LINCOLN ;2U
Adder
4.013
942111AE2-223 GEN
Solar/Wind Harmer
4.757
960611AF2-352 GEN
Solar/Wind Harmer
1.295
961501AF2-441 GEN
50/50
11.164
274827FISK ;RP
50/50
8.107
274800UNIV PARK;3U
Adder
5.669
274801UNIV PARK;4U
Adder
5.669
972037AH1-567 GEN1
Adder
0.173
960591AF2-350 GEN
Solar/Wind Harmer
9.216
274687WILL CNTY;4U
Adder
24.286
274687WILL CNTY;4U
Adder
24.286
276893AG1-478 C
Solar/Wind Harmer
0.47
274675JOLIET 29;7U
Adder
25.79
274675JOLIET 29;7U
Adder
24.869
972228AH1-698 GEN2
Adder
3.077
972227AH1-698 GEN1
Adder
2.165
274728ELWOOD EC;5P
Adder
13.63
274731ELWOOD EC;2P
Adder
13.623
274733ELWOOD EC;3P
Adder
13.623
274735ELWOOD EC;4P
Adder
13.623
970073AG2-061 GEN
Solar/Wind Harmer
1.839
970833AG2-524 GEN
Solar/Wind Harmer
6.644
970833AG2-524 GEN
Solar/Wind Harmer
3.09
276889AE2-281 GEN
Solar/Wind Harmer
1.437
274744AC1-111 GEN8
Adder
4.155
274746AC1-111 G10
Adder
4.155
971411AH1-196 GEN
Solar/Wind Harmer
10.771
274823ROCKFORD ;21
Adder
13.727
971675AH1-338 GEN
Solar/Wind Harmer
12.676
276861AD2-134 GEN
Solar/Wind Harmer
1.257
276863AD2-134 GEN
Solar/Wind Harmer
1.257
971171AH1-044 GEN
Solar/Wind Harmer
14.038
274856ECOGROVE ;U1
Solar/Wind Harmer
2.344
276611AD2-172 GEN
Solar/Wind Harmer
1.778
276612AE2-035 GEN
Solar/Wind Harmer
1.778
971681AH1-341 GEN
Solar/Wind Harmer
10.282
926823AC1-168 GEN
Solar/Wind Harmer
2.946
972267AH1-718 GEN
Adder
2.786
276741O09 GEN1
Solar/Wind Harmer
2.376
274863CRW1-WTG
Solar/Wind Harmer
3.691
274864CRW2-WTG
Solar/Wind Harmer
3.691
274877BISHOP HL;1U
Solar/Wind Harmer
2.204
274775LINCOLN ;6U
Adder
4.013
274776LINCOLN ;7U
Adder
4.013
274777LINCOLN ;8U
Adder
4.013
970169AG2-114 GEN
Solar/Wind Harmer
6.401
946321AF1-296 GEN
Solar/Wind Harmer
6.64
276726Z2-087_GEN
Solar/Wind Harmer
4.589
959341AF2-225 GEN
Solar/Wind Harmer
8.705
274853TWINGROVE;U1
Solar/Wind Harmer
4.011
274854TWINGROVE;U2
Solar/Wind Harmer
3.927
276668AB2-070 GEN1
Solar/Wind Harmer
0.388
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
276849AB2-070 GEN2
Solar/Wind Harmer
0.388
274724RIVER EC ;11
50/50
24.394
957371AF2-031 GEN
50/50
1.208
274752CRETE EC ;2U
50/50
5.119
274753CRETE EC ;3U
50/50
5.119
274826FISK ;BP
50/50
11.439
276164X3-005 C
Solar/Wind Harmer
0.791
972231SS25-0005
Solar/Wind Harmer
9.366
972181SS23-001
Solar/Wind Harmer
5.854
972038AH1-567 GEN2
Adder
0.355
274814UNIV PK N;0U
Adder
4.798
274807UNIV PK N;3U
Adder
4.788
274811UNIV PK N;7U
Adder
4.756
274803UNIV PARK;6U
Adder
5.518
274887GEN-1.85
Solar/Wind Harmer
4.91
276772AC2-154 GEN
Solar/Wind Harmer
2.572
276843GEN-1.7
Solar/Wind Harmer
0.528
276806AD2-047 C O1
Solar/Wind Harmer
9.859
274676JOLIET 29;8U
Adder
24.871
274730ELWOOD EC;6P
Adder
13.63
274734ELWOOD EC;8P
Adder
13.63
274736ELWOOD EC;9P
Adder
13.63
274729ELWOOD EC;1P
Adder
13.623
274862TOP CROP ;2U
Solar/Wind Harmer
4.153
939351AE1-166 GEN
Solar/Wind Harmer
4.58
972259AH1-714 GEN
Adder
14.6
274682WAUKEGAN ;7U
Adder
13.663
276868AE1-113 GEN
Solar/Wind Harmer
7.677
274879MINONK ;1U
Solar/Wind Harmer
5.118
943121AE2-341 GEN
Solar/Wind Harmer
10.843
943591AF1-030 GEN
Solar/Wind Harmer
7.229
970571AG2-364 GEN
Solar/Wind Harmer
14.404
276799AD1-013 GEN
Solar/Wind Harmer
1.557
946671AF1-331 GEN
Solar/Wind Harmer
0.295
274855GSG-6 ;RU
Solar/Wind Harmer
2.599
274850MENDOTA H;RU
Solar/Wind Harmer
1.807
276602WESTBROOK C
Solar/Wind Harmer
1.496
970707AG2-453 GEN
Solar/Wind Harmer
19.673
959091AF2-200 GEN
Solar/Wind Harmer
14.038
274857EASY ROAD;U1
Solar/Wind Harmer
3.265
274760LEE CO EC;1U
Adder
6.341
274767LEE CO EC;8U
Adder
6.267
276603SUBLETTE C
Solar/Wind Harmer
0.711
274851PROVIDENC;RU
Solar/Wind Harmer
1.877
274849CRESCENT ;1U
Solar/Wind Harmer
1.219
276782AC1-033 GEN
Solar/Wind Harmer
2.605
274878BISHOP HL;2U
Solar/Wind Harmer
2.204
274772LINCOLN ;3U
Adder
4.013
965931AG1-462 GEN
Solar/Wind Harmer
16.071
971087AG2-675 GEN
Solar/Wind Harmer
2.345
965091AG1-374 GEN
Solar/Wind Harmer
16.701
959611AF2-252 GEN
Solar/Wind Harmer
1.295
990577J1339
External Queue
22.606393814086914
990647J1355
External Queue
45.02376174926758
991247J1684 G
External Queue
28.46610450744629
990582J1340
External Queue
22.606393814086914
990662J1358
External Queue
16.966588973999023
991337J1802
External Queue
10.915008544921875
990552J1334 G
External Queue
34.18348693847656
990562J1336 G
External Queue
34.18348693847656
990762J1386
External Queue
10.307926177978516
991332J1785
External Queue
14.42030143737793
990547J1333 G
External Queue
34.18348693847656
990557J1335 G
External Queue
34.18348693847656
NYPJM->LTFIMP_NY
CLTF
0.719
WECLTFEXP_WEC->PJM
CLTF
2.723
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.266
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.506
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.227
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.612
MECLTFEXP_MEC->PJM
CLTF
8.664
SIGELTFEXP_SIGE->PJM
CLTF
0.032
AG2-052LTFEXP_AG2-052->PJM
LTF
0.531
AH1-155LTFEXP_AH1-155->PJM
LTF
0.796
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.164
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.402
LAGNLTFEXP_LAGN->PJM
CLTF
3.143
TVALTFEXP_TVA->PJM
CLTF
0.883

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.87 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:1875.38
MW Contribution:
11.27
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.11 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:1990.35
MW Contribution:
12.01
Bus #Bus NameTypeMW Contribution
274888KELLY CRK;1U
Solar/Wind Harmer
5.455
276776AD2-060 GEN
Solar/Wind Harmer
0.387
958011AF2-095 GEN
Solar/Wind Harmer
13.313
970941AG2-585 GEN
Solar/Wind Harmer
5.085
274805UNIV PK N;1U
Adder
4.499
274808UNIV PK N;4U
Adder
4.47
274674JOLIET 9 ;6U
Adder
13.651
276893AG1-478 C
Solar/Wind Harmer
0.386
958481AF2-142 GEN
Solar/Wind Harmer
12.558
274683WAUKEGAN ;8U
Adder
17.328
274683WAUKEGAN ;8U
Adder
14.607
274695ROCKY RD ;2P
Adder
9.116
274693ROCKY RD ;1P
Adder
9.027
274697ROCKY RD ;3P
Adder
2.477
274696ROCKY RD ;4P
Adder
9.331
958491AF2-143 GEN
Solar/Wind Harmer
12.172
962691AG1-118 GEN
Solar/Wind Harmer
24.113
960751AF2-366 GEN
Solar/Wind Harmer
2.296
276901AD2-066 C O1
Solar/Wind Harmer
2.783
276872AE1-163_GEN1
Solar/Wind Harmer
5.21
276876AE1-163_GEN2
Solar/Wind Harmer
5.21
971341AH1-150 GEN
Solar/Wind Harmer
15.496
971343AH1-151 GEN
Solar/Wind Harmer
15.496
972235AH1-702 GEN1
Adder
1.939
972236AH1-702 GEN2
Adder
1.686
276897AD1-100 C
Solar/Wind Harmer
35.533
938861AE1-114 GEN
Solar/Wind Harmer
6.159
274764LEE CO EC;5U
Adder
6.958
274765LEE CO EC;6U
Adder
6.958
274762LEE CO EC;3U
Adder
6.941
274763LEE CO EC;4U
Adder
6.876
276158O29GEN2
Solar/Wind Harmer
3.613
276157O29GEN1
Solar/Wind Harmer
2.747
276645AC1-214 GEN1
Solar/Wind Harmer
0.939
942111AE2-223 GEN
Solar/Wind Harmer
4.867
274770LINCOLN ;1U
Adder
3.612
274771LINCOLN ;2U
Adder
3.612
960611AF2-352 GEN
Solar/Wind Harmer
1.322
961501AF2-441 GEN
50/50
11.022
274827FISK ;RP
50/50
8.118
274800UNIV PARK;3U
Adder
5.721
274801UNIV PARK;4U
Adder
5.721
972037AH1-567 GEN1
Adder
0.171
960591AF2-350 GEN
Solar/Wind Harmer
9.245
274687WILL CNTY;4U
Adder
24.997
274687WILL CNTY;4U
Adder
24.997
276893AG1-478 C
Solar/Wind Harmer
0.484
274675JOLIET 29;7U
Adder
26.876
274675JOLIET 29;7U
Adder
25.916
274728ELWOOD EC;5P
Adder
14.192
274731ELWOOD EC;2P
Adder
14.189
274733ELWOOD EC;3P
Adder
14.189
274735ELWOOD EC;4P
Adder
14.189
972228AH1-698 GEN2
Adder
3.122
972227AH1-698 GEN1
Adder
2.196
274744AC1-111 GEN8
Adder
4.65
274746AC1-111 G10
Adder
4.65
970833AG2-524 GEN
Solar/Wind Harmer
7.223
970833AG2-524 GEN
Solar/Wind Harmer
3.36
970073AG2-061 GEN
Solar/Wind Harmer
1.887
971411AH1-196 GEN
Solar/Wind Harmer
11.823
971675AH1-338 GEN
Solar/Wind Harmer
14.088
276861AD2-134 GEN
Solar/Wind Harmer
1.397
276863AD2-134 GEN
Solar/Wind Harmer
1.397
276889AE2-281 GEN
Solar/Wind Harmer
1.488
971171AH1-044 GEN
Solar/Wind Harmer
15.496
274823ROCKFORD ;21
Adder
15.064
274856ECOGROVE ;U1
Solar/Wind Harmer
2.569
276611AD2-172 GEN
Solar/Wind Harmer
1.948
276612AE2-035 GEN
Solar/Wind Harmer
1.948
971681AH1-341 GEN
Solar/Wind Harmer
11.268
926823AC1-168 GEN
Solar/Wind Harmer
3.145
972267AH1-718 GEN
Adder
3.044
276741O09 GEN1
Solar/Wind Harmer
2.58
274877BISHOP HL;1U
Solar/Wind Harmer
2.349
946321AF1-296 GEN
Solar/Wind Harmer
7.2
970169AG2-114 GEN
Solar/Wind Harmer
6.68
274863CRW1-WTG
Solar/Wind Harmer
3.724
274864CRW2-WTG
Solar/Wind Harmer
3.724
276726Z2-087_GEN
Solar/Wind Harmer
4.694
959341AF2-225 GEN
Solar/Wind Harmer
8.905
274775LINCOLN ;6U
Adder
3.612
274776LINCOLN ;7U
Adder
3.612
274777LINCOLN ;8U
Adder
3.612
274853TWINGROVE;U1
Solar/Wind Harmer
4.095
274854TWINGROVE;U2
Solar/Wind Harmer
4.009
276668AB2-070 GEN1
Solar/Wind Harmer
0.392
276848AB2-070 GEN3
Solar/Wind Harmer
0.392
276849AB2-070 GEN2
Solar/Wind Harmer
0.392
274724RIVER EC ;11
50/50
24.026
957371AF2-031 GEN
50/50
1.189
274826FISK ;BP
50/50
11.455
276164X3-005 C
Solar/Wind Harmer
0.781
972038AH1-567 GEN2
Adder
0.358
274803UNIV PARK;6U
Adder
5.461
274887GEN-1.85
Solar/Wind Harmer
4.926
276772AC2-154 GEN
Solar/Wind Harmer
2.58
276843GEN-1.7
Solar/Wind Harmer
0.53
276806AD2-047 C O1
Solar/Wind Harmer
9.89
274814UNIV PK N;0U
Adder
4.529
274807UNIV PK N;3U
Adder
4.519
274811UNIV PK N;7U
Adder
4.49
972231SS25-0005
Solar/Wind Harmer
8.412
972181SS23-001
Solar/Wind Harmer
5.257
274752CRETE EC ;2U
Adder
4.332
274753CRETE EC ;3U
Adder
4.332
274676JOLIET 29;8U
Adder
25.915
274730ELWOOD EC;6P
Adder
14.192
274734ELWOOD EC;8P
Adder
14.192
274736ELWOOD EC;9P
Adder
14.192
274729ELWOOD EC;1P
Adder
14.189
972259AH1-714 GEN
Adder
15.976
970707AG2-453 GEN
Solar/Wind Harmer
23.405
274862TOP CROP ;2U
Solar/Wind Harmer
4.222
943121AE2-341 GEN
Solar/Wind Harmer
12.425
943591AF1-030 GEN
Solar/Wind Harmer
8.283
274682WAUKEGAN ;7U
Adder
14.814
276868AE1-113 GEN
Solar/Wind Harmer
8.043
274879MINONK ;1U
Solar/Wind Harmer
5.362
276799AD1-013 GEN
Solar/Wind Harmer
1.731
946671AF1-331 GEN
Solar/Wind Harmer
0.328
274855GSG-6 ;RU
Solar/Wind Harmer
2.888
274850MENDOTA H;RU
Solar/Wind Harmer
2.008
276602WESTBROOK C
Solar/Wind Harmer
1.662
959091AF2-200 GEN
Solar/Wind Harmer
15.496
939351AE1-166 GEN
Solar/Wind Harmer
4.536
970571AG2-364 GEN
Solar/Wind Harmer
15.025
274857EASY ROAD;U1
Solar/Wind Harmer
3.574
274760LEE CO EC;1U
Adder
6.941
274767LEE CO EC;8U
Adder
6.86
276603SUBLETTE C
Solar/Wind Harmer
0.779
274851PROVIDENC;RU
Solar/Wind Harmer
1.997
274849CRESCENT ;1U
Solar/Wind Harmer
1.296
276782AC1-033 GEN
Solar/Wind Harmer
2.776
274878BISHOP HL;2U
Solar/Wind Harmer
2.349
965931AG1-462 GEN
Solar/Wind Harmer
17.409
971087AG2-675 GEN
Solar/Wind Harmer
2.54
274772LINCOLN ;3U
Adder
3.612
965091AG1-374 GEN
Solar/Wind Harmer
17.051
959611AF2-252 GEN
Solar/Wind Harmer
1.322
274723RIVER EC ;12
50/50
23.912
972179AH1-673 GEN
50/50
12.332
274802UNIV PARK;5U
Adder
5.461
274812UNIV PK N;8U
Adder
4.49
274674JOLIET 9 ;6U
Adder
13.651
274751CRETE EC ;1U
Adder
4.332
274754CRETE EC ;4U
Adder
4.332
274676JOLIET 29;8U
Adder
26.875
274732ELWOOD EC;7P
Adder
14.192
276694AA1-018 GEN2
Solar/Wind Harmer
5.282
276691AA1-018 GEN1
Solar/Wind Harmer
0.631
274861TOP CROP ;1U
Solar/Wind Harmer
5.056
274745AC1-111 GEN9
Adder
4.65
274682WAUKEGAN ;7U
Adder
14.814
274828WAUKEGAN ;BP
Adder
9.083
274871GR RIDGE ;2U
Solar/Wind Harmer
6.315
274847GR RIDGE ;BU
Solar/Wind Harmer
4.152
276805AD2-038 GEN
Solar/Wind Harmer
4.161
962781AG1-127 GEN
Solar/Wind Harmer
7.609
274872LEEDK;1U
Solar/Wind Harmer
6.538
276882AE2-255 GEN
Solar/Wind Harmer
2.681
957471AF2-041 GEN
Solar/Wind Harmer
23.243
959081AF2-199 GEN
Solar/Wind Harmer
7.748
971067AG2-660 GEN
Solar/Wind Harmer
1.802
274822ROCKFORD ;11
Adder
15.174
971997AH1-543 GEN
Solar/Wind Harmer
12.17
941551AE2-152 GEN
Solar/Wind Harmer
3.469
970819AG2-516 GEN
Solar/Wind Harmer
9.179
970569AG2-363 GEN
Solar/Wind Harmer
22.538
274858EASY ROAD;U2
Solar/Wind Harmer
3.574
274761LEE CO EC;2U
Adder
6.941
274766LEE CO EC;7U
Adder
6.86
276708O09 GEN2
Solar/Wind Harmer
2.58
276646AC1-214 GEN2
Solar/Wind Harmer
0.939
274848CAMPGROVE;RU
Solar/Wind Harmer
4.439
939401AE1-172 GEN
Solar/Wind Harmer
9.534
276655WTG1_EQ
Solar/Wind Harmer
5.182
276656WTG2_EQ
Solar/Wind Harmer
0.686
939741AE1-205 GEN
Solar/Wind Harmer
11.874
972207SS24-0001
Solar/Wind Harmer
12.842
274773LINCOLN ;4U
Adder
3.612
274774LINCOLN ;5U
Adder
3.612
990577J1339
External Queue
20.67680549621582
990647J1355
External Queue
45.41110610961914
991247J1684 G
External Queue
27.007545471191406
990582J1340
External Queue
20.67680549621582
990662J1358
External Queue
15.003209114074707
991337J1802
External Queue
9.998335838317871
990552J1334 G
External Queue
33.20325469970703
990562J1336 G
External Queue
33.20325469970703
990762J1386
External Queue
9.109322547912598
991332J1785
External Queue
12.988174438476562
990547J1333 G
External Queue
33.20325469970703
990557J1335 G
External Queue
33.20325469970703
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.12
NYPJM->LTFIMP_NY
CLTF
0.71
WECLTFEXP_WEC->PJM
CLTF
2.954
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.101
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.227
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.606
MECLTFEXP_MEC->PJM
CLTF
9.274
SIGELTFEXP_SIGE->PJM
CLTF
0.025
AG2-052LTFEXP_AG2-052->PJM
LTF
0.532
AH1-155LTFEXP_AH1-155->PJM
LTF
0.798
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.207
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.54
LAGNLTFEXP_LAGN->PJM
CLTF
3.256
TVALTFEXP_TVA->PJM
CLTF
0.894

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.17 %
Rating:1385.0 MVA
Rating Type:A
MVA to Mitigate:1387.41
MW Contribution:
7.09
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:1385.0 MVA
Rating Type:A
MVA to Mitigate:1441.0
MW Contribution:
7.33
Bus #Bus NameTypeMW Contribution
274724RIVER EC ;11
50/50
23.142
957371AF2-031 GEN
50/50
1.146
274826FISK ;BP
50/50
10.611
972038AH1-567 GEN2
Adder
0.33
274803UNIV PARK;6U
Adder
5.03
274887GEN-1.85
Solar/Wind Harmer
0.155
276843GEN-1.7
Solar/Wind Harmer
0.193
276806AD2-047 C O1
Solar/Wind Harmer
3.377
274752CRETE EC ;2U
Adder
6.871
274753CRETE EC ;3U
Adder
6.871
274814UNIV PK N;0U
Adder
4.203
274807UNIV PK N;3U
Adder
4.194
274811UNIV PK N;7U
Adder
4.167
274676JOLIET 29;8U
Adder
22.857
274730ELWOOD EC;6P
Adder
12.517
274734ELWOOD EC;8P
Adder
12.517
274736ELWOOD EC;9P
Adder
12.517
274729ELWOOD EC;1P
Adder
12.511
274862TOP CROP ;2U
Solar/Wind Harmer
0.708
939351AE1-166 GEN
Solar/Wind Harmer
0
972259AH1-714 GEN
Adder
13.462
274888KELLY CRK;1U
Solar/Wind Harmer
0.348
276776AD2-060 GEN
Solar/Wind Harmer
0.636
958011AF2-095 GEN
Solar/Wind Harmer
8.581
970941AG2-585 GEN
Solar/Wind Harmer
3.277
274805UNIV PK N;1U
Adder
4.176
274808UNIV PK N;4U
Adder
4.149
276893AG1-478 C
Solar/Wind Harmer
0.366
274674JOLIET 9 ;6U
Adder
11.983
961501AF2-441 GEN
50/50
10.553
274827FISK ;RP
50/50
7.52
274800UNIV PARK;3U
Adder
5.268
274801UNIV PARK;4U
Adder
5.268
972037AH1-567 GEN1
Adder
0.158
960591AF2-350 GEN
Solar/Wind Harmer
5.959
274687WILL CNTY;4U
Adder
22.352
274687WILL CNTY;4U
Adder
22.352
274675JOLIET 29;7U
Adder
23.702
274675JOLIET 29;7U
Adder
22.856
274728ELWOOD EC;5P
Adder
12.517
972228AH1-698 GEN2
Adder
2.82
274731ELWOOD EC;2P
Adder
12.511
274733ELWOOD EC;3P
Adder
12.511
274735ELWOOD EC;4P
Adder
12.511
972227AH1-698 GEN1
Adder
1.984
970073AG2-061 GEN
Solar/Wind Harmer
1.685
970833AG2-524 GEN
Solar/Wind Harmer
5.383
970833AG2-524 GEN
Solar/Wind Harmer
3.589
274744AC1-111 GEN8
Adder
3.84
274746AC1-111 G10
Adder
3.84
971411AH1-196 GEN
Solar/Wind Harmer
6.926
971675AH1-338 GEN
Solar/Wind Harmer
1.768
276861AD2-134 GEN
Solar/Wind Harmer
0.081
276863AD2-134 GEN
Solar/Wind Harmer
0.081
274823ROCKFORD ;21
Adder
12.647
971171AH1-044 GEN
Solar/Wind Harmer
9.028
274856ECOGROVE ;U1
Solar/Wind Harmer
0.104
971681AH1-341 GEN
Solar/Wind Harmer
7.088
926823AC1-168 GEN
Solar/Wind Harmer
0.745
972267AH1-718 GEN
Adder
2.562
274775LINCOLN ;6U
Adder
5.187
274776LINCOLN ;7U
Adder
5.187
274777LINCOLN ;8U
Adder
5.187
276741O09 GEN1
Solar/Wind Harmer
0.151
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.139
970169AG2-114 GEN
Solar/Wind Harmer
4.098
946321AF1-296 GEN
Solar/Wind Harmer
2.283
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.877
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
7.876
958491AF2-143 GEN
Solar/Wind Harmer
7.584
276897AD1-100 C
Solar/Wind Harmer
12.462
274683WAUKEGAN ;8U
Adder
14.724
274683WAUKEGAN ;8U
Adder
12.412
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
7.793
274695ROCKY RD ;2P
Adder
7.613
274693ROCKY RD ;1P
Adder
7.538
274697ROCKY RD ;3P
Adder
2.068
962691AG1-118 GEN
Solar/Wind Harmer
13.899
971341AH1-150 GEN
Solar/Wind Harmer
9.028
971343AH1-151 GEN
Solar/Wind Harmer
9.028
972235AH1-702 GEN1
Adder
1.627
972236AH1-702 GEN2
Adder
1.415
938861AE1-114 GEN
Solar/Wind Harmer
2.497
274764LEE CO EC;5U
Adder
5.851
274765LEE CO EC;6U
Adder
5.851
274762LEE CO EC;3U
Adder
5.837
274763LEE CO EC;4U
Adder
5.782
274770LINCOLN ;1U
Adder
5.187
274771LINCOLN ;2U
Adder
5.187
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.688
276645AC1-214 GEN1
Solar/Wind Harmer
0.165
942111AE2-223 GEN
Solar/Wind Harmer
1.2
960611AF2-352 GEN
Solar/Wind Harmer
1.178
274682WAUKEGAN ;7U
Adder
12.59
276868AE1-113 GEN
Solar/Wind Harmer
0.972
274879MINONK ;1U
Solar/Wind Harmer
0.203
943121AE2-341 GEN
Solar/Wind Harmer
7.831
943591AF1-030 GEN
Solar/Wind Harmer
5.208
970571AG2-364 GEN
Solar/Wind Harmer
9.202
970707AG2-453 GEN
Solar/Wind Harmer
14.873
946671AF1-331 GEN
Solar/Wind Harmer
0.484
274855GSG-6 ;RU
Solar/Wind Harmer
0.165
274850MENDOTA H;RU
Solar/Wind Harmer
0.053
959091AF2-200 GEN
Solar/Wind Harmer
9.028
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
5.837
274767LEE CO EC;8U
Adder
5.768
274772LINCOLN ;3U
Adder
5.187
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.139
965931AG1-462 GEN
Solar/Wind Harmer
10.292
971087AG2-675 GEN
Solar/Wind Harmer
2.153
965091AG1-374 GEN
Solar/Wind Harmer
10.604
959611AF2-252 GEN
Solar/Wind Harmer
1.178
274723RIVER EC ;12
50/50
23.018
972179AH1-673 GEN
50/50
11.863
274802UNIV PARK;5U
Adder
5.03
274751CRETE EC ;1U
Adder
6.871
274754CRETE EC ;4U
Adder
6.871
274812UNIV PK N;8U
Adder
4.167
274674JOLIET 9 ;6U
Adder
11.983
274676JOLIET 29;8U
Adder
23.703
274732ELWOOD EC;7P
Adder
12.517
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.853
274861TOP CROP ;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
12.59
274828WAUKEGAN ;BP
Adder
7.718
276882AE2-255 GEN
Solar/Wind Harmer
0.567
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
3.84
962781AG1-127 GEN
Solar/Wind Harmer
4.392
970569AG2-363 GEN
Solar/Wind Harmer
13.804
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
2.401
274822ROCKFORD ;11
Adder
12.739
957471AF2-041 GEN
Solar/Wind Harmer
13.541
959081AF2-199 GEN
Solar/Wind Harmer
4.514
971067AG2-660 GEN
Solar/Wind Harmer
1.505
970819AG2-516 GEN
Solar/Wind Harmer
5.382
939401AE1-172 GEN
Solar/Wind Harmer
3.298
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
5.837
274766LEE CO EC;7U
Adder
5.768
274773LINCOLN ;4U
Adder
5.187
274774LINCOLN ;5U
Adder
5.187
276708O09 GEN2
Solar/Wind Harmer
0.151
276646AC1-214 GEN2
Solar/Wind Harmer
0.165
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
5.17
990577J1339
External Queue
21.050790786743164
990647J1355
External Queue
46.19844055175781
991247J1684 G
External Queue
27.399545669555664
990582J1340
External Queue
21.050790786743164
990662J1358
External Queue
15.440608978271484
991337J1802
External Queue
10.749092102050781
990552J1334 G
External Queue
33.61130142211914
990562J1336 G
External Queue
33.61130142211914
990762J1386
External Queue
9.201155662536621
991332J1785
External Queue
13.4489107131958
990547J1333 G
External Queue
33.61130142211914
990557J1335 G
External Queue
33.61130142211914
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.097
NYPJM->LTFIMP_NY
CLTF
0.611
WECLTFEXP_WEC->PJM
CLTF
2.506
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.602
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.35
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.397
MECLTFEXP_MEC->PJM
CLTF
7.92
SIGELTFEXP_SIGE->PJM
CLTF
0.025
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
AG2-052LTFEXP_AG2-052->PJM
LTF
0.53
AH1-155LTFEXP_AH1-155->PJM
LTF
0.795
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.156
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.394
LAGNLTFEXP_LAGN->PJM
CLTF
2.846
TVALTFEXP_TVA->PJM
CLTF
0.797

Details for 17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.26 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1393.9
MW Contribution:
11.62
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.06 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1339.5
MW Contribution:
11.29
Bus #Bus NameTypeMW Contribution
274752CRETE EC ;2U
50/50
9.139
274753CRETE EC ;3U
50/50
9.139
274654BRAIDWOOD;1U
50/50
3.492
959351AF2-226 GEN
50/50
2.102
972231SS25-0005
Solar/Wind Harmer
16.722
972181SS23-001
Solar/Wind Harmer
10.451
274862TOP CROP ;2U
Solar/Wind Harmer
4.572
274676JOLIET 29;8U
Adder
26.722
274826FISK ;BP
Adder
9.838
972259AH1-714 GEN
Adder
17.133
274730ELWOOD EC;6P
Adder
14.752
274734ELWOOD EC;8P
Adder
14.752
274736ELWOOD EC;9P
Adder
14.752
274729ELWOOD EC;1P
Adder
14.737
970707AG2-453 GEN
Solar/Wind Harmer
24.696
274887GEN-1.85
Solar/Wind Harmer
4.678
276772AC2-154 GEN
Solar/Wind Harmer
2.45
276843GEN-1.7
Solar/Wind Harmer
0.503
276806AD2-047 C O1
Solar/Wind Harmer
9.393
274772LINCOLN ;3U
Adder
5.42
939351AE1-166 GEN
Solar/Wind Harmer
5.18
972038AH1-567 GEN2
Adder
0.313
276164X3-005 C
Solar/Wind Harmer
0.601
943121AE2-341 GEN
Solar/Wind Harmer
12.823
943591AF1-030 GEN
Solar/Wind Harmer
8.548
274682WAUKEGAN ;7U
Adder
15.291
274803UNIV PARK;6U
Adder
4.903
276868AE1-113 GEN
Solar/Wind Harmer
8.336
274879MINONK ;1U
Solar/Wind Harmer
5.558
274724RIVER EC ;11
Adder
14.448
276799AD1-013 GEN
Solar/Wind Harmer
1.785
946671AF1-331 GEN
Solar/Wind Harmer
0.338
274855GSG-6 ;RU
Solar/Wind Harmer
2.979
274850MENDOTA H;RU
Solar/Wind Harmer
2.071
276602WESTBROOK C
Solar/Wind Harmer
1.715
959091AF2-200 GEN
Solar/Wind Harmer
15.99
970571AG2-364 GEN
Solar/Wind Harmer
15.569
274814UNIV PK N;0U
Adder
3.929
274807UNIV PK N;3U
Adder
3.92
274811UNIV PK N;7U
Adder
3.895
274857EASY ROAD;U1
Solar/Wind Harmer
3.686
274760LEE CO EC;1U
Adder
7.157
972227AH1-698 GEN1
50/50
2.549
274655BRAIDWOOD;2U
50/50
3.385
972228AH1-698 GEN2
50/50
3.616
274687WILL CNTY;4U
50/50
27.13
274687WILL CNTY;4U
50/50
27.13
274675JOLIET 29;7U
Adder
27.705
274675JOLIET 29;7U
Adder
26.716
274827FISK ;RP
Adder
6.972
274728ELWOOD EC;5P
Adder
14.752
274731ELWOOD EC;2P
Adder
14.737
274733ELWOOD EC;3P
Adder
14.737
274735ELWOOD EC;4P
Adder
14.737
960591AF2-350 GEN
Solar/Wind Harmer
8.781
274775LINCOLN ;6U
Adder
5.42
274776LINCOLN ;7U
Adder
5.42
274777LINCOLN ;8U
Adder
5.42
276893AG1-478 C
Solar/Wind Harmer
0.48
970833AG2-524 GEN
Solar/Wind Harmer
7.6
970833AG2-524 GEN
Solar/Wind Harmer
3.535
274800UNIV PARK;3U
Adder
5.006
274801UNIV PARK;4U
Adder
5.006
274744AC1-111 GEN8
Adder
4.799
274746AC1-111 G10
Adder
4.799
972037AH1-567 GEN1
Adder
0.154
970073AG2-061 GEN
Solar/Wind Harmer
1.899
971411AH1-196 GEN
Solar/Wind Harmer
12.202
971675AH1-338 GEN
Solar/Wind Harmer
14.53
276861AD2-134 GEN
Solar/Wind Harmer
1.44
276863AD2-134 GEN
Solar/Wind Harmer
1.44
971171AH1-044 GEN
Solar/Wind Harmer
15.99
274823ROCKFORD ;21
Adder
15.54
276889AE2-281 GEN
Solar/Wind Harmer
1.523
274856ECOGROVE ;U1
Solar/Wind Harmer
2.649
276611AD2-172 GEN
Solar/Wind Harmer
2.01
276612AE2-035 GEN
Solar/Wind Harmer
2.01
971681AH1-341 GEN
Solar/Wind Harmer
11.62
926823AC1-168 GEN
Solar/Wind Harmer
3.274
972267AH1-718 GEN
Adder
3.137
274863CRW1-WTG
Solar/Wind Harmer
4.189
274864CRW2-WTG
Solar/Wind Harmer
4.189
276741O09 GEN1
Solar/Wind Harmer
2.661
970169AG2-114 GEN
Solar/Wind Harmer
7.199
274877BISHOP HL;1U
Solar/Wind Harmer
2.427
946321AF1-296 GEN
Solar/Wind Harmer
7.412
276726Z2-087_GEN
Solar/Wind Harmer
5.047
959341AF2-225 GEN
Solar/Wind Harmer
9.574
274853TWINGROVE;U1
Solar/Wind Harmer
4.379
274854TWINGROVE;U2
Solar/Wind Harmer
4.288
276668AB2-070 GEN1
Solar/Wind Harmer
1.1
276848AB2-070 GEN3
Solar/Wind Harmer
1.1
276849AB2-070 GEN2
Solar/Wind Harmer
1.1
276763AC1-053 GEN1
Solar/Wind Harmer
1.935
276764AC1-053 GEN2
Solar/Wind Harmer
1.935
960681AF2-359 GEN
Solar/Wind Helper
2.286
274888KELLY CRK;1U
Solar/Wind Harmer
5.181
276776AD2-060 GEN
Solar/Wind Harmer
0.368
958011AF2-095 GEN
Solar/Wind Harmer
12.644
970941AG2-585 GEN
Solar/Wind Harmer
4.829
274770LINCOLN ;1U
Adder
5.42
274771LINCOLN ;2U
Adder
5.42
276897AD1-100 C
Solar/Wind Harmer
40.574
276893AG1-478 C
Solar/Wind Harmer
0.383
274674JOLIET 9 ;6U
Adder
13.371
274683WAUKEGAN ;8U
Adder
17.885
274683WAUKEGAN ;8U
Adder
15.076
274696ROCKY RD ;4P
Adder
9.637
274695ROCKY RD ;2P
Adder
9.415
274693ROCKY RD ;1P
Adder
9.323
274697ROCKY RD ;3P
Adder
2.558
958481AF2-142 GEN
Solar/Wind Harmer
12.495
962691AG1-118 GEN
Solar/Wind Harmer
24.872
960751AF2-366 GEN
Solar/Wind Harmer
2.368
958491AF2-143 GEN
Solar/Wind Harmer
12.25
276901AD2-066 C O1
Solar/Wind Harmer
2.851
971341AH1-150 GEN
Solar/Wind Harmer
15.99
971343AH1-151 GEN
Solar/Wind Harmer
15.99
276872AE1-163_GEN1
Solar/Wind Harmer
5.332
276876AE1-163_GEN2
Solar/Wind Harmer
5.332
972235AH1-702 GEN1
Adder
2
972236AH1-702 GEN2
Adder
1.739
274805UNIV PK N;1U
Adder
3.903
274808UNIV PK N;4U
Adder
3.878
938861AE1-114 GEN
Solar/Wind Harmer
6.351
274764LEE CO EC;5U
Adder
7.174
274765LEE CO EC;6U
Adder
7.174
274762LEE CO EC;3U
Adder
7.157
274763LEE CO EC;4U
Adder
7.09
276158O29GEN2
Solar/Wind Harmer
3.726
276157O29GEN1
Solar/Wind Harmer
2.833
276645AC1-214 GEN1
Solar/Wind Harmer
0.971
942111AE2-223 GEN
Solar/Wind Harmer
5.232
960611AF2-352 GEN
Solar/Wind Harmer
1.414
274880W4-005 GEN4
Solar/Wind Harmer
1.505
276174W4-005 GEN2
Solar/Wind Harmer
1.505
276615X2-022 GEN
Solar/Wind Harmer
0.929
276838X2-022 GEN2
Solar/Wind Harmer
0.11
274767LEE CO EC;8U
Adder
7.073
276603SUBLETTE C
Solar/Wind Harmer
0.803
274851PROVIDENC;RU
Solar/Wind Harmer
2.064
274849CRESCENT ;1U
Solar/Wind Harmer
1.34
276782AC1-033 GEN
Solar/Wind Harmer
2.868
274878BISHOP HL;2U
Solar/Wind Harmer
2.427
965931AG1-462 GEN
Solar/Wind Harmer
17.917
971087AG2-675 GEN
Solar/Wind Harmer
2.614
965091AG1-374 GEN
Solar/Wind Harmer
18.236
959611AF2-252 GEN
Solar/Wind Harmer
1.414
276785W4-005 GEN1
Solar/Wind Harmer
1.505
971993AH1-541 GEN
Solar/Wind Harmer
4.598
274751CRETE EC ;1U
50/50
9.139
274754CRETE EC ;4U
50/50
9.139
960281AF2-319 GEN
50/50
2.102
274861TOP CROP ;1U
Solar/Wind Harmer
5.476
274676JOLIET 29;8U
Adder
27.712
274732ELWOOD EC;7P
Adder
14.752
972207SS24-0001
Solar/Wind Harmer
19.271
274773LINCOLN ;4U
Adder
5.42
274774LINCOLN ;5U
Adder
5.42
941551AE2-152 GEN
Solar/Wind Harmer
3.961
274871GR RIDGE ;2U
Solar/Wind Harmer
6.701
274847GR RIDGE ;BU
Solar/Wind Harmer
4.406
274674JOLIET 9 ;6U
Adder
13.371
274745AC1-111 GEN9
Adder
4.799
274682WAUKEGAN ;7U
Adder
15.291
274828WAUKEGAN ;BP
Adder
9.375
274802UNIV PARK;5U
Adder
4.903
276694AA1-018 GEN2
Solar/Wind Harmer
5.256
276691AA1-018 GEN1
Solar/Wind Harmer
0.628
962781AG1-127 GEN
Solar/Wind Harmer
7.849
276882AE2-255 GEN
Solar/Wind Harmer
2.779
274872LEEDK;1U
Solar/Wind Harmer
6.744
276805AD2-038 GEN
Solar/Wind Harmer
4.188
274723RIVER EC ;12
Adder
14.605
971997AH1-543 GEN
Solar/Wind Harmer
12.616
957471AF2-041 GEN
Solar/Wind Harmer
23.986
959081AF2-199 GEN
Solar/Wind Harmer
7.995
971067AG2-660 GEN
Solar/Wind Harmer
1.859
274822ROCKFORD ;11
Adder
15.654
970819AG2-516 GEN
Solar/Wind Harmer
9.467
939401AE1-172 GEN
Solar/Wind Harmer
10.908
970569AG2-363 GEN
Solar/Wind Harmer
23.353
274812UNIV PK N;8U
Adder
3.895
274858EASY ROAD;U2
Solar/Wind Harmer
3.686
274761LEE CO EC;2U
Adder
7.157
274766LEE CO EC;7U
Adder
7.073
276708O09 GEN2
Solar/Wind Harmer
2.661
276646AC1-214 GEN2
Solar/Wind Harmer
0.971
274848CAMPGROVE;RU
Solar/Wind Harmer
4.586
276655WTG1_EQ
Solar/Wind Harmer
5.571
276656WTG2_EQ
Solar/Wind Harmer
0.738
939741AE1-205 GEN
Solar/Wind Harmer
12.766
276686W4-005 GEN3
Solar/Wind Harmer
1.505
276621W2-048 GEN
Solar/Wind Harmer
2.959
990577J1339
External Queue
10.413921356201172
991777J1629 G
External Queue
9.27670669555664
991247J1684 G
External Queue
7.4839606285095215
990582J1340
External Queue
10.413921356201172
990512J1326
External Queue
4.084519386291504
990117J1214
External Queue
14.050745964050293
990727J1377 G
External Queue
4.744733810424805
990762J1386
External Queue
5.9100422859191895
990407J1304
External Queue
3.1608264446258545
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.132
NYPJM->LTFIMP_NY
CLTF
0.704
WECLTFEXP_WEC->PJM
CLTF
3.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.814
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.273
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.721
MECLTFEXP_MEC->PJM
CLTF
9.478
SIGELTFEXP_SIGE->PJM
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.274
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.305
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.854
LAGNLTFEXP_LAGN->PJM
CLTF
3.159
TVALTFEXP_TVA->PJM
CLTF
0.819

Details for 17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.26 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1393.9
MW Contribution:
11.62
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.06 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1339.5
MW Contribution:
11.29
Bus #Bus NameTypeMW Contribution
972227AH1-698 GEN1
50/50
2.549
274655BRAIDWOOD;2U
50/50
3.385
972228AH1-698 GEN2
50/50
3.616
274687WILL CNTY;4U
50/50
27.13
274687WILL CNTY;4U
50/50
27.13
274675JOLIET 29;7U
Adder
27.705
274675JOLIET 29;7U
Adder
26.715
274827FISK ;RP
Adder
6.972
274728ELWOOD EC;5P
Adder
14.752
274731ELWOOD EC;2P
Adder
14.737
274733ELWOOD EC;3P
Adder
14.737
274735ELWOOD EC;4P
Adder
14.737
960591AF2-350 GEN
Solar/Wind Harmer
8.781
274775LINCOLN ;6U
Adder
5.42
274776LINCOLN ;7U
Adder
5.42
274777LINCOLN ;8U
Adder
5.42
274888KELLY CRK;1U
Solar/Wind Harmer
5.181
276776AD2-060 GEN
Solar/Wind Harmer
0.368
958011AF2-095 GEN
Solar/Wind Harmer
12.644
970941AG2-585 GEN
Solar/Wind Harmer
4.829
274770LINCOLN ;1U
Adder
5.42
274771LINCOLN ;2U
Adder
5.42
276897AD1-100 C
Solar/Wind Harmer
40.574
276893AG1-478 C
Solar/Wind Harmer
0.383
274674JOLIET 9 ;6U
Adder
13.371
274683WAUKEGAN ;8U
Adder
17.885
274683WAUKEGAN ;8U
Adder
15.076
274696ROCKY RD ;4P
Adder
9.637
274695ROCKY RD ;2P
Adder
9.415
274693ROCKY RD ;1P
Adder
9.323
274697ROCKY RD ;3P
Adder
2.558
958481AF2-142 GEN
Solar/Wind Harmer
12.495
962691AG1-118 GEN
Solar/Wind Harmer
24.872
960751AF2-366 GEN
Solar/Wind Harmer
2.368
958491AF2-143 GEN
Solar/Wind Harmer
12.25
276901AD2-066 C O1
Solar/Wind Harmer
2.851
971341AH1-150 GEN
Solar/Wind Harmer
15.99
971343AH1-151 GEN
Solar/Wind Harmer
15.99
276872AE1-163_GEN1
Solar/Wind Harmer
5.332
276876AE1-163_GEN2
Solar/Wind Harmer
5.332
972235AH1-702 GEN1
Adder
2
972236AH1-702 GEN2
Adder
1.739
274805UNIV PK N;1U
Adder
3.903
274808UNIV PK N;4U
Adder
3.878
938861AE1-114 GEN
Solar/Wind Harmer
6.351
274764LEE CO EC;5U
Adder
7.174
274765LEE CO EC;6U
Adder
7.174
274762LEE CO EC;3U
Adder
7.157
274763LEE CO EC;4U
Adder
7.09
276158O29GEN2
Solar/Wind Harmer
3.726
276157O29GEN1
Solar/Wind Harmer
2.833
276645AC1-214 GEN1
Solar/Wind Harmer
0.971
942111AE2-223 GEN
Solar/Wind Harmer
5.232
960611AF2-352 GEN
Solar/Wind Harmer
1.414
274880W4-005 GEN4
Solar/Wind Harmer
1.505
276174W4-005 GEN2
Solar/Wind Harmer
1.505
276615X2-022 GEN
Solar/Wind Harmer
0.929
276838X2-022 GEN2
Solar/Wind Harmer
0.11
274752CRETE EC ;2U
50/50
9.139
274753CRETE EC ;3U
50/50
9.139
274654BRAIDWOOD;1U
50/50
3.492
959351AF2-226 GEN
50/50
2.102
972231SS25-0005
Solar/Wind Harmer
16.722
972181SS23-001
Solar/Wind Harmer
10.451
274862TOP CROP ;2U
Solar/Wind Harmer
4.572
274676JOLIET 29;8U
Adder
26.722
274826FISK ;BP
Adder
9.838
972259AH1-714 GEN
Adder
17.133
274730ELWOOD EC;6P
Adder
14.752
274734ELWOOD EC;8P
Adder
14.752
274736ELWOOD EC;9P
Adder
14.752
274729ELWOOD EC;1P
Adder
14.737
970707AG2-453 GEN
Solar/Wind Harmer
24.696
274887GEN-1.85
Solar/Wind Harmer
4.678
276772AC2-154 GEN
Solar/Wind Harmer
2.45
276843GEN-1.7
Solar/Wind Harmer
0.503
276806AD2-047 C O1
Solar/Wind Harmer
9.393
274772LINCOLN ;3U
Adder
5.42
939351AE1-166 GEN
Solar/Wind Harmer
5.18
972038AH1-567 GEN2
Adder
0.313
276164X3-005 C
Solar/Wind Harmer
0.601
943121AE2-341 GEN
Solar/Wind Harmer
12.823
943591AF1-030 GEN
Solar/Wind Harmer
8.548
274682WAUKEGAN ;7U
Adder
15.291
274803UNIV PARK;6U
Adder
4.903
276868AE1-113 GEN
Solar/Wind Harmer
8.336
274879MINONK ;1U
Solar/Wind Harmer
5.558
274724RIVER EC ;11
Adder
14.448
276799AD1-013 GEN
Solar/Wind Harmer
1.785
946671AF1-331 GEN
Solar/Wind Harmer
0.338
274855GSG-6 ;RU
Solar/Wind Harmer
2.979
274850MENDOTA H;RU
Solar/Wind Harmer
2.071
276602WESTBROOK C
Solar/Wind Harmer
1.715
959091AF2-200 GEN
Solar/Wind Harmer
15.99
970571AG2-364 GEN
Solar/Wind Harmer
15.569
274814UNIV PK N;0U
Adder
3.929
274807UNIV PK N;3U
Adder
3.92
274811UNIV PK N;7U
Adder
3.895
274857EASY ROAD;U1
Solar/Wind Harmer
3.686
274760LEE CO EC;1U
Adder
7.157
274767LEE CO EC;8U
Adder
7.073
276603SUBLETTE C
Solar/Wind Harmer
0.803
274851PROVIDENC;RU
Solar/Wind Harmer
2.064
274849CRESCENT ;1U
Solar/Wind Harmer
1.34
276782AC1-033 GEN
Solar/Wind Harmer
2.868
274878BISHOP HL;2U
Solar/Wind Harmer
2.427
965931AG1-462 GEN
Solar/Wind Harmer
17.916
971087AG2-675 GEN
Solar/Wind Harmer
2.614
965091AG1-374 GEN
Solar/Wind Harmer
18.236
959611AF2-252 GEN
Solar/Wind Harmer
1.414
276785W4-005 GEN1
Solar/Wind Harmer
1.505
971993AH1-541 GEN
Solar/Wind Harmer
4.598
274751CRETE EC ;1U
50/50
9.139
274754CRETE EC ;4U
50/50
9.139
960281AF2-319 GEN
50/50
2.102
274861TOP CROP ;1U
Solar/Wind Harmer
5.476
274676JOLIET 29;8U
Adder
27.711
274732ELWOOD EC;7P
Adder
14.752
972207SS24-0001
Solar/Wind Harmer
19.271
274773LINCOLN ;4U
Adder
5.42
274774LINCOLN ;5U
Adder
5.42
941551AE2-152 GEN
Solar/Wind Harmer
3.961
274871GR RIDGE ;2U
Solar/Wind Harmer
6.701
274847GR RIDGE ;BU
Solar/Wind Harmer
4.406
274674JOLIET 9 ;6U
Adder
13.371
274745AC1-111 GEN9
Adder
4.799
274682WAUKEGAN ;7U
Adder
15.291
274828WAUKEGAN ;BP
Adder
9.375
274802UNIV PARK;5U
Adder
4.903
276694AA1-018 GEN2
Solar/Wind Harmer
5.256
276691AA1-018 GEN1
Solar/Wind Harmer
0.628
962781AG1-127 GEN
Solar/Wind Harmer
7.849
276882AE2-255 GEN
Solar/Wind Harmer
2.779
274872LEEDK;1U
Solar/Wind Harmer
6.744
276805AD2-038 GEN
Solar/Wind Harmer
4.188
274723RIVER EC ;12
Adder
14.605
971997AH1-543 GEN
Solar/Wind Harmer
12.616
957471AF2-041 GEN
Solar/Wind Harmer
23.986
959081AF2-199 GEN
Solar/Wind Harmer
7.995
971067AG2-660 GEN
Solar/Wind Harmer
1.859
274822ROCKFORD ;11
Adder
15.654
970819AG2-516 GEN
Solar/Wind Harmer
9.467
939401AE1-172 GEN
Solar/Wind Harmer
10.908
970569AG2-363 GEN
Solar/Wind Harmer
23.353
274812UNIV PK N;8U
Adder
3.895
274858EASY ROAD;U2
Solar/Wind Harmer
3.686
274761LEE CO EC;2U
Adder
7.157
274766LEE CO EC;7U
Adder
7.073
276708O09 GEN2
Solar/Wind Harmer
2.661
276646AC1-214 GEN2
Solar/Wind Harmer
0.971
274848CAMPGROVE;RU
Solar/Wind Harmer
4.586
276655WTG1_EQ
Solar/Wind Harmer
5.571
276656WTG2_EQ
Solar/Wind Harmer
0.738
939741AE1-205 GEN
Solar/Wind Harmer
12.766
276686W4-005 GEN3
Solar/Wind Harmer
1.505
276621W2-048 GEN
Solar/Wind Harmer
2.959
276893AG1-478 C
Solar/Wind Harmer
0.48
970833AG2-524 GEN
Solar/Wind Harmer
7.6
970833AG2-524 GEN
Solar/Wind Harmer
3.535
274800UNIV PARK;3U
Adder
5.006
274801UNIV PARK;4U
Adder
5.006
274744AC1-111 GEN8
Adder
4.799
274746AC1-111 G10
Adder
4.799
972037AH1-567 GEN1
Adder
0.154
970073AG2-061 GEN
Solar/Wind Harmer
1.899
971411AH1-196 GEN
Solar/Wind Harmer
12.202
971675AH1-338 GEN
Solar/Wind Harmer
14.53
276861AD2-134 GEN
Solar/Wind Harmer
1.44
276863AD2-134 GEN
Solar/Wind Harmer
1.44
971171AH1-044 GEN
Solar/Wind Harmer
15.99
274823ROCKFORD ;21
Adder
15.54
276889AE2-281 GEN
Solar/Wind Harmer
1.523
274856ECOGROVE ;U1
Solar/Wind Harmer
2.649
276611AD2-172 GEN
Solar/Wind Harmer
2.01
276612AE2-035 GEN
Solar/Wind Harmer
2.01
971681AH1-341 GEN
Solar/Wind Harmer
11.62
926823AC1-168 GEN
Solar/Wind Harmer
3.274
972267AH1-718 GEN
Adder
3.137
274863CRW1-WTG
Solar/Wind Harmer
4.189
274864CRW2-WTG
Solar/Wind Harmer
4.189
276741O09 GEN1
Solar/Wind Harmer
2.661
970169AG2-114 GEN
Solar/Wind Harmer
7.199
274877BISHOP HL;1U
Solar/Wind Harmer
2.427
946321AF1-296 GEN
Solar/Wind Harmer
7.412
276726Z2-087_GEN
Solar/Wind Harmer
5.047
959341AF2-225 GEN
Solar/Wind Harmer
9.574
274853TWINGROVE;U1
Solar/Wind Harmer
4.379
274854TWINGROVE;U2
Solar/Wind Harmer
4.288
276668AB2-070 GEN1
Solar/Wind Harmer
1.1
276848AB2-070 GEN3
Solar/Wind Harmer
1.1
276849AB2-070 GEN2
Solar/Wind Harmer
1.1
276763AC1-053 GEN1
Solar/Wind Harmer
1.935
276764AC1-053 GEN2
Solar/Wind Harmer
1.935
960681AF2-359 GEN
Solar/Wind Helper
2.286
990577J1339
External Queue
10.413962364196777
991777J1629 G
External Queue
9.276653289794922
991247J1684 G
External Queue
7.483994960784912
990582J1340
External Queue
10.413962364196777
990512J1326
External Queue
4.084494590759277
990117J1214
External Queue
14.050661087036133
990727J1377 G
External Queue
4.744704723358154
990762J1386
External Queue
5.910062789916992
990407J1304
External Queue
3.160806655883789
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.132
NYPJM->LTFIMP_NY
CLTF
0.704
WECLTFEXP_WEC->PJM
CLTF
3.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.813
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.273
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.721
MECLTFEXP_MEC->PJM
CLTF
9.478
SIGELTFEXP_SIGE->PJM
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.274
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.305
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.854
LAGNLTFEXP_LAGN->PJM
CLTF
3.159
TVALTFEXP_TVA->PJM
CLTF
0.819

Details for 17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.6 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1376.55
MW Contribution:
11.51
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.13 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1329.81
MW Contribution:
11.22
Bus #Bus NameTypeMW Contribution
274888KELLY CRK;1U
Solar/Wind Harmer
5.129
276776AD2-060 GEN
Solar/Wind Harmer
0.364
958011AF2-095 GEN
Solar/Wind Harmer
12.515
970941AG2-585 GEN
Solar/Wind Harmer
4.78
274770LINCOLN ;1U
Adder
5.364
274771LINCOLN ;2U
Adder
5.364
276897AD1-100 C
Solar/Wind Harmer
40.173
276893AG1-478 C
Solar/Wind Harmer
0.379
274674JOLIET 9 ;6U
Adder
13.238
274683WAUKEGAN ;8U
Adder
17.714
274683WAUKEGAN ;8U
Adder
14.932
274695ROCKY RD ;2P
Adder
9.325
274693ROCKY RD ;1P
Adder
9.233
274697ROCKY RD ;3P
Adder
2.533
274696ROCKY RD ;4P
Adder
9.545
958481AF2-142 GEN
Solar/Wind Harmer
12.37
962691AG1-118 GEN
Solar/Wind Harmer
24.633
960751AF2-366 GEN
Solar/Wind Harmer
2.345
958491AF2-143 GEN
Solar/Wind Harmer
12.128
276901AD2-066 C O1
Solar/Wind Harmer
2.823
971341AH1-150 GEN
Solar/Wind Harmer
15.837
971343AH1-151 GEN
Solar/Wind Harmer
15.837
276872AE1-163_GEN1
Solar/Wind Harmer
5.28
276876AE1-163_GEN2
Solar/Wind Harmer
5.28
972235AH1-702 GEN1
Adder
1.981
972236AH1-702 GEN2
Adder
1.723
274805UNIV PK N;1U
Adder
3.856
274808UNIV PK N;4U
Adder
3.831
938861AE1-114 GEN
Solar/Wind Harmer
6.29
274764LEE CO EC;5U
Adder
7.105
274765LEE CO EC;6U
Adder
7.105
274762LEE CO EC;3U
Adder
7.089
274763LEE CO EC;4U
Adder
7.022
276158O29GEN2
Solar/Wind Harmer
3.69
276157O29GEN1
Solar/Wind Harmer
2.806
276645AC1-214 GEN1
Solar/Wind Harmer
0.961
942111AE2-223 GEN
Solar/Wind Harmer
5.179
960611AF2-352 GEN
Solar/Wind Harmer
1.399
274880W4-005 GEN4
Solar/Wind Harmer
1.489
276174W4-005 GEN2
Solar/Wind Harmer
1.489
276615X2-022 GEN
Solar/Wind Harmer
0.92
276838X2-022 GEN2
Solar/Wind Harmer
0.109
972227AH1-698 GEN1
50/50
2.525
274655BRAIDWOOD;2U
50/50
3.353
972228AH1-698 GEN2
50/50
3.582
274687WILL CNTY;4U
50/50
26.87
274687WILL CNTY;4U
50/50
26.87
274675JOLIET 29;7U
Adder
27.439
274675JOLIET 29;7U
Adder
26.459
274827FISK ;RP
Adder
6.902
274728ELWOOD EC;5P
Adder
14.61
274731ELWOOD EC;2P
Adder
14.596
274733ELWOOD EC;3P
Adder
14.596
274735ELWOOD EC;4P
Adder
14.596
960591AF2-350 GEN
Solar/Wind Harmer
8.691
274775LINCOLN ;6U
Adder
5.364
274776LINCOLN ;7U
Adder
5.364
274777LINCOLN ;8U
Adder
5.364
276893AG1-478 C
Solar/Wind Harmer
0.475
970833AG2-524 GEN
Solar/Wind Harmer
7.527
970833AG2-524 GEN
Solar/Wind Harmer
3.501
274744AC1-111 GEN8
Adder
4.753
274746AC1-111 G10
Adder
4.753
274800UNIV PARK;3U
Adder
4.953
274801UNIV PARK;4U
Adder
4.953
972037AH1-567 GEN1
Adder
0.152
970073AG2-061 GEN
Solar/Wind Harmer
1.88
971411AH1-196 GEN
Solar/Wind Harmer
12.085
971675AH1-338 GEN
Solar/Wind Harmer
14.391
276861AD2-134 GEN
Solar/Wind Harmer
1.427
276863AD2-134 GEN
Solar/Wind Harmer
1.427
971171AH1-044 GEN
Solar/Wind Harmer
15.837
274823ROCKFORD ;21
Adder
15.391
276889AE2-281 GEN
Solar/Wind Harmer
1.508
274856ECOGROVE ;U1
Solar/Wind Harmer
2.624
276611AD2-172 GEN
Solar/Wind Harmer
1.99
276612AE2-035 GEN
Solar/Wind Harmer
1.99
971681AH1-341 GEN
Solar/Wind Harmer
11.508
926823AC1-168 GEN
Solar/Wind Harmer
3.242
972267AH1-718 GEN
Adder
3.107
274863CRW1-WTG
Solar/Wind Harmer
4.147
274864CRW2-WTG
Solar/Wind Harmer
4.147
276741O09 GEN1
Solar/Wind Harmer
2.635
970169AG2-114 GEN
Solar/Wind Harmer
7.127
274877BISHOP HL;1U
Solar/Wind Harmer
2.403
946321AF1-296 GEN
Solar/Wind Harmer
7.341
276726Z2-087_GEN
Solar/Wind Harmer
4.996
959341AF2-225 GEN
Solar/Wind Harmer
9.477
274853TWINGROVE;U1
Solar/Wind Harmer
4.335
274854TWINGROVE;U2
Solar/Wind Harmer
4.244
276668AB2-070 GEN1
Solar/Wind Harmer
1.088
276848AB2-070 GEN3
Solar/Wind Harmer
1.088
276849AB2-070 GEN2
Solar/Wind Harmer
1.088
276763AC1-053 GEN1
Solar/Wind Harmer
1.915
276764AC1-053 GEN2
Solar/Wind Harmer
1.915
960681AF2-359 GEN
Solar/Wind Helper
2.306
274752CRETE EC ;2U
50/50
9.088
274753CRETE EC ;3U
50/50
9.088
274654BRAIDWOOD;1U
50/50
3.459
959351AF2-226 GEN
50/50
2.083
972231SS25-0005
Solar/Wind Harmer
16.629
972181SS23-001
Solar/Wind Harmer
10.393
274862TOP CROP ;2U
Solar/Wind Harmer
4.53
274676JOLIET 29;8U
Adder
26.465
972259AH1-714 GEN
Adder
16.97
274826FISK ;BP
Adder
9.738
274730ELWOOD EC;6P
Adder
14.61
274734ELWOOD EC;8P
Adder
14.61
274736ELWOOD EC;9P
Adder
14.61
274729ELWOOD EC;1P
Adder
14.596
970707AG2-453 GEN
Solar/Wind Harmer
24.462
274887GEN-1.85
Solar/Wind Harmer
4.631
276772AC2-154 GEN
Solar/Wind Harmer
2.425
276843GEN-1.7
Solar/Wind Harmer
0.498
276806AD2-047 C O1
Solar/Wind Harmer
9.297
274772LINCOLN ;3U
Adder
5.364
939351AE1-166 GEN
Solar/Wind Harmer
5.129
972038AH1-567 GEN2
Adder
0.31
943121AE2-341 GEN
Solar/Wind Harmer
12.7
943591AF1-030 GEN
Solar/Wind Harmer
8.467
276164X3-005 C
Solar/Wind Harmer
0.594
274682WAUKEGAN ;7U
Adder
15.144
274803UNIV PARK;6U
Adder
4.849
276868AE1-113 GEN
Solar/Wind Harmer
8.256
274879MINONK ;1U
Solar/Wind Harmer
5.504
274724RIVER EC ;11
Adder
14.275
276799AD1-013 GEN
Solar/Wind Harmer
1.768
946671AF1-331 GEN
Solar/Wind Harmer
0.335
274855GSG-6 ;RU
Solar/Wind Harmer
2.95
274850MENDOTA H;RU
Solar/Wind Harmer
2.051
276602WESTBROOK C
Solar/Wind Harmer
1.698
959091AF2-200 GEN
Solar/Wind Harmer
15.837
970571AG2-364 GEN
Solar/Wind Harmer
15.418
274814UNIV PK N;0U
Adder
3.881
274807UNIV PK N;3U
Adder
3.873
274811UNIV PK N;7U
Adder
3.848
274857EASY ROAD;U1
Solar/Wind Harmer
3.65
274760LEE CO EC;1U
Adder
7.089
274767LEE CO EC;8U
Adder
7.005
276603SUBLETTE C
Solar/Wind Harmer
0.795
274851PROVIDENC;RU
Solar/Wind Harmer
2.044
274849CRESCENT ;1U
Solar/Wind Harmer
1.327
276782AC1-033 GEN
Solar/Wind Harmer
2.84
274878BISHOP HL;2U
Solar/Wind Harmer
2.403
965931AG1-462 GEN
Solar/Wind Harmer
17.743
971087AG2-675 GEN
Solar/Wind Harmer
2.589
965091AG1-374 GEN
Solar/Wind Harmer
18.051
959611AF2-252 GEN
Solar/Wind Harmer
1.399
276785W4-005 GEN1
Solar/Wind Harmer
1.489
971993AH1-541 GEN
Solar/Wind Harmer
4.55
274751CRETE EC ;1U
50/50
9.088
274754CRETE EC ;4U
50/50
9.088
960281AF2-319 GEN
50/50
2.083
274861TOP CROP ;1U
Solar/Wind Harmer
5.425
274676JOLIET 29;8U
Adder
27.446
274732ELWOOD EC;7P
Adder
14.61
972207SS24-0001
Solar/Wind Harmer
19.072
274773LINCOLN ;4U
Adder
5.364
274774LINCOLN ;5U
Adder
5.364
941551AE2-152 GEN
Solar/Wind Harmer
3.922
274871GR RIDGE ;2U
Solar/Wind Harmer
6.637
274847GR RIDGE ;BU
Solar/Wind Harmer
4.364
274674JOLIET 9 ;6U
Adder
13.238
274745AC1-111 GEN9
Adder
4.753
274682WAUKEGAN ;7U
Adder
15.144
274828WAUKEGAN ;BP
Adder
9.285
274802UNIV PARK;5U
Adder
4.849
276694AA1-018 GEN2
Solar/Wind Harmer
5.203
276691AA1-018 GEN1
Solar/Wind Harmer
0.622
962781AG1-127 GEN
Solar/Wind Harmer
7.774
276882AE2-255 GEN
Solar/Wind Harmer
2.752
274872LEEDK;1U
Solar/Wind Harmer
6.679
276805AD2-038 GEN
Solar/Wind Harmer
4.146
274723RIVER EC ;12
Adder
14.43
971997AH1-543 GEN
Solar/Wind Harmer
12.494
957471AF2-041 GEN
Solar/Wind Harmer
23.755
959081AF2-199 GEN
Solar/Wind Harmer
7.918
971067AG2-660 GEN
Solar/Wind Harmer
1.841
274822ROCKFORD ;11
Adder
15.503
970819AG2-516 GEN
Solar/Wind Harmer
9.376
939401AE1-172 GEN
Solar/Wind Harmer
10.799
970569AG2-363 GEN
Solar/Wind Harmer
23.127
274812UNIV PK N;8U
Adder
3.848
274858EASY ROAD;U2
Solar/Wind Harmer
3.65
274761LEE CO EC;2U
Adder
7.089
274766LEE CO EC;7U
Adder
7.005
276708O09 GEN2
Solar/Wind Harmer
2.635
276646AC1-214 GEN2
Solar/Wind Harmer
0.961
274848CAMPGROVE;RU
Solar/Wind Harmer
4.541
276655WTG1_EQ
Solar/Wind Harmer
5.515
276656WTG2_EQ
Solar/Wind Harmer
0.73
939741AE1-205 GEN
Solar/Wind Harmer
12.636
276686W4-005 GEN3
Solar/Wind Harmer
1.489
276621W2-048 GEN
Solar/Wind Harmer
2.928
990577J1339
External Queue
10.302718162536621
991777J1629 G
External Queue
9.21812629699707
991247J1684 G
External Queue
7.382841110229492
990582J1340
External Queue
10.302718162536621
990512J1326
External Queue
4.058592796325684
990117J1214
External Queue
13.96155834197998
990727J1377 G
External Queue
4.714233875274658
990762J1386
External Queue
5.8489766120910645
990407J1304
External Queue
3.14041805267334
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.695
WECLTFEXP_WEC->PJM
CLTF
3.016
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.038
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.49
MECLTFEXP_MEC->PJM
CLTF
9.386
SIGELTFEXP_SIGE->PJM
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.268
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.301
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.84
LAGNLTFEXP_LAGN->PJM
CLTF
3.131
TVALTFEXP_TVA->PJM
CLTF
0.813

Details for 17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.95 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1348.78
MW Contribution:
11.35
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.9 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1337.83
MW Contribution:
11.2
Bus #Bus NameTypeMW Contribution
274752CRETE EC ;2U
50/50
8.999
274753CRETE EC ;3U
50/50
8.999
274654BRAIDWOOD;1U
50/50
3.406
959351AF2-226 GEN
50/50
2.053
972231SS25-0005
Solar/Wind Harmer
16.466
972181SS23-001
Solar/Wind Harmer
10.291
274862TOP CROP ;2U
Solar/Wind Harmer
4.465
274676JOLIET 29;8U
Adder
26.057
972259AH1-714 GEN
Adder
16.711
274730ELWOOD EC;6P
Adder
14.388
274734ELWOOD EC;8P
Adder
14.388
274736ELWOOD EC;9P
Adder
14.388
274826FISK ;BP
Adder
9.576
274729ELWOOD EC;1P
Adder
14.373
970707AG2-453 GEN
Solar/Wind Harmer
24.089
274887GEN-1.85
Solar/Wind Harmer
4.554
276772AC2-154 GEN
Solar/Wind Harmer
2.385
276843GEN-1.7
Solar/Wind Harmer
0.49
276806AD2-047 C O1
Solar/Wind Harmer
9.144
274772LINCOLN ;3U
Adder
5.279
939351AE1-166 GEN
Solar/Wind Harmer
5.05
972038AH1-567 GEN2
Adder
0.305
943121AE2-341 GEN
Solar/Wind Harmer
12.509
943591AF1-030 GEN
Solar/Wind Harmer
8.339
274682WAUKEGAN ;7U
Adder
14.92
276164X3-005 C
Solar/Wind Harmer
0.583
274803UNIV PARK;6U
Adder
4.762
276868AE1-113 GEN
Solar/Wind Harmer
8.139
274879MINONK ;1U
Solar/Wind Harmer
5.426
274724RIVER EC ;11
Adder
13.981
276799AD1-013 GEN
Solar/Wind Harmer
1.742
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.908
274850MENDOTA H;RU
Solar/Wind Harmer
2.022
276602WESTBROOK C
Solar/Wind Harmer
1.674
959091AF2-200 GEN
Solar/Wind Harmer
15.613
970571AG2-364 GEN
Solar/Wind Harmer
15.21
274814UNIV PK N;0U
Adder
3.801
274807UNIV PK N;3U
Adder
3.792
274811UNIV PK N;7U
Adder
3.768
274857EASY ROAD;U1
Solar/Wind Harmer
3.6
274760LEE CO EC;1U
Adder
6.992
274767LEE CO EC;8U
Adder
6.909
276603SUBLETTE C
Solar/Wind Harmer
0.784
274851PROVIDENC;RU
Solar/Wind Harmer
2.018
274849CRESCENT ;1U
Solar/Wind Harmer
1.31
276782AC1-033 GEN
Solar/Wind Harmer
2.805
274878BISHOP HL;2U
Solar/Wind Harmer
2.373
965931AG1-462 GEN
Solar/Wind Harmer
17.522
971087AG2-675 GEN
Solar/Wind Harmer
2.557
965091AG1-374 GEN
Solar/Wind Harmer
17.879
959611AF2-252 GEN
Solar/Wind Harmer
1.386
276785W4-005 GEN1
Solar/Wind Harmer
1.481
971993AH1-541 GEN
Solar/Wind Harmer
4.526
274888KELLY CRK;1U
Solar/Wind Harmer
5.044
276776AD2-060 GEN
Solar/Wind Harmer
0.358
958011AF2-095 GEN
Solar/Wind Harmer
12.308
970941AG2-585 GEN
Solar/Wind Harmer
4.701
274770LINCOLN ;1U
Adder
5.279
274771LINCOLN ;2U
Adder
5.279
276897AD1-100 C
Solar/Wind Harmer
39.558
276893AG1-478 C
Solar/Wind Harmer
0.373
274674JOLIET 9 ;6U
Adder
13.029
274683WAUKEGAN ;8U
Adder
17.451
274683WAUKEGAN ;8U
Adder
14.711
274695ROCKY RD ;2P
Adder
9.187
274693ROCKY RD ;1P
Adder
9.097
274697ROCKY RD ;3P
Adder
2.496
274696ROCKY RD ;4P
Adder
9.404
958481AF2-142 GEN
Solar/Wind Harmer
12.179
962691AG1-118 GEN
Solar/Wind Harmer
24.273
960751AF2-366 GEN
Solar/Wind Harmer
2.311
958491AF2-143 GEN
Solar/Wind Harmer
11.948
276901AD2-066 C O1
Solar/Wind Harmer
2.782
971341AH1-150 GEN
Solar/Wind Harmer
15.613
971343AH1-151 GEN
Solar/Wind Harmer
15.613
276872AE1-163_GEN1
Solar/Wind Harmer
5.205
276876AE1-163_GEN2
Solar/Wind Harmer
5.205
972235AH1-702 GEN1
Adder
1.953
972236AH1-702 GEN2
Adder
1.698
938861AE1-114 GEN
Solar/Wind Harmer
6.203
274805UNIV PK N;1U
Adder
3.776
274808UNIV PK N;4U
Adder
3.751
274764LEE CO EC;5U
Adder
7.008
274765LEE CO EC;6U
Adder
7.008
274762LEE CO EC;3U
Adder
6.992
274763LEE CO EC;4U
Adder
6.926
276158O29GEN2
Solar/Wind Harmer
3.642
276157O29GEN1
Solar/Wind Harmer
2.769
276645AC1-214 GEN1
Solar/Wind Harmer
0.949
942111AE2-223 GEN
Solar/Wind Harmer
5.126
960611AF2-352 GEN
Solar/Wind Harmer
1.386
274880W4-005 GEN4
Solar/Wind Harmer
1.481
276174W4-005 GEN2
Solar/Wind Harmer
1.481
276615X2-022 GEN
Solar/Wind Harmer
0.916
276838X2-022 GEN2
Solar/Wind Harmer
0.109
274751CRETE EC ;1U
50/50
8.999
274754CRETE EC ;4U
50/50
8.999
960281AF2-319 GEN
50/50
2.053
274861TOP CROP ;1U
Solar/Wind Harmer
5.348
274676JOLIET 29;8U
Adder
27.022
274732ELWOOD EC;7P
Adder
14.388
972207SS24-0001
Solar/Wind Harmer
18.768
274773LINCOLN ;4U
Adder
5.279
274774LINCOLN ;5U
Adder
5.279
941551AE2-152 GEN
Solar/Wind Harmer
3.862
274871GR RIDGE ;2U
Solar/Wind Harmer
6.538
274847GR RIDGE ;BU
Solar/Wind Harmer
4.299
274674JOLIET 9 ;6U
Adder
13.029
274745AC1-111 GEN9
Adder
4.682
274682WAUKEGAN ;7U
Adder
14.92
274828WAUKEGAN ;BP
Adder
9.148
274802UNIV PARK;5U
Adder
4.762
276694AA1-018 GEN2
Solar/Wind Harmer
5.123
276691AA1-018 GEN1
Solar/Wind Harmer
0.612
962781AG1-127 GEN
Solar/Wind Harmer
7.661
276882AE2-255 GEN
Solar/Wind Harmer
2.713
274872LEEDK;1U
Solar/Wind Harmer
6.583
276805AD2-038 GEN
Solar/Wind Harmer
4.084
274723RIVER EC ;12
Adder
14.134
971997AH1-543 GEN
Solar/Wind Harmer
12.319
957471AF2-041 GEN
Solar/Wind Harmer
23.419
959081AF2-199 GEN
Solar/Wind Harmer
7.806
971067AG2-660 GEN
Solar/Wind Harmer
1.815
274822ROCKFORD ;11
Adder
15.284
970819AG2-516 GEN
Solar/Wind Harmer
9.245
939401AE1-172 GEN
Solar/Wind Harmer
10.65
970569AG2-363 GEN
Solar/Wind Harmer
22.815
274812UNIV PK N;8U
Adder
3.768
274858EASY ROAD;U2
Solar/Wind Harmer
3.6
274761LEE CO EC;2U
Adder
6.992
274766LEE CO EC;7U
Adder
6.909
276708O09 GEN2
Solar/Wind Harmer
2.6
276646AC1-214 GEN2
Solar/Wind Harmer
0.949
274848CAMPGROVE;RU
Solar/Wind Harmer
4.485
276655WTG1_EQ
Solar/Wind Harmer
5.457
276656WTG2_EQ
Solar/Wind Harmer
0.723
939741AE1-205 GEN
Solar/Wind Harmer
12.505
276686W4-005 GEN3
Solar/Wind Harmer
1.481
276621W2-048 GEN
Solar/Wind Harmer
2.916
972227AH1-698 GEN1
50/50
2.486
274655BRAIDWOOD;2U
50/50
3.301
972228AH1-698 GEN2
50/50
3.527
274687WILL CNTY;4U
50/50
26.456
274687WILL CNTY;4U
50/50
26.456
274675JOLIET 29;7U
Adder
27.016
274675JOLIET 29;7U
Adder
26.051
274728ELWOOD EC;5P
Adder
14.388
274827FISK ;RP
Adder
6.786
274731ELWOOD EC;2P
Adder
14.373
274733ELWOOD EC;3P
Adder
14.373
274735ELWOOD EC;4P
Adder
14.373
960591AF2-350 GEN
Solar/Wind Harmer
8.547
274775LINCOLN ;6U
Adder
5.279
274776LINCOLN ;7U
Adder
5.279
274777LINCOLN ;8U
Adder
5.279
276893AG1-478 C
Solar/Wind Harmer
0.468
970833AG2-524 GEN
Solar/Wind Harmer
7.414
970833AG2-524 GEN
Solar/Wind Harmer
3.448
274744AC1-111 GEN8
Adder
4.682
274746AC1-111 G10
Adder
4.682
274800UNIV PARK;3U
Adder
4.868
274801UNIV PARK;4U
Adder
4.868
972037AH1-567 GEN1
Adder
0.149
970073AG2-061 GEN
Solar/Wind Harmer
1.852
971411AH1-196 GEN
Solar/Wind Harmer
11.912
971675AH1-338 GEN
Solar/Wind Harmer
14.185
276861AD2-134 GEN
Solar/Wind Harmer
1.406
276863AD2-134 GEN
Solar/Wind Harmer
1.406
971171AH1-044 GEN
Solar/Wind Harmer
15.613
274823ROCKFORD ;21
Adder
15.174
276889AE2-281 GEN
Solar/Wind Harmer
1.487
274856ECOGROVE ;U1
Solar/Wind Harmer
2.587
276611AD2-172 GEN
Solar/Wind Harmer
1.963
276612AE2-035 GEN
Solar/Wind Harmer
1.963
971681AH1-341 GEN
Solar/Wind Harmer
11.349
926823AC1-168 GEN
Solar/Wind Harmer
3.199
972267AH1-718 GEN
Adder
3.065
274863CRW1-WTG
Solar/Wind Harmer
4.093
274864CRW2-WTG
Solar/Wind Harmer
4.093
276741O09 GEN1
Solar/Wind Harmer
2.6
970169AG2-114 GEN
Solar/Wind Harmer
7.039
274877BISHOP HL;1U
Solar/Wind Harmer
2.373
946321AF1-296 GEN
Solar/Wind Harmer
7.248
276726Z2-087_GEN
Solar/Wind Harmer
4.944
959341AF2-225 GEN
Solar/Wind Harmer
9.379
274853TWINGROVE;U1
Solar/Wind Harmer
4.294
274854TWINGROVE;U2
Solar/Wind Harmer
4.204
276668AB2-070 GEN1
Solar/Wind Harmer
1.082
276848AB2-070 GEN3
Solar/Wind Harmer
1.082
276849AB2-070 GEN2
Solar/Wind Harmer
1.082
276763AC1-053 GEN1
Solar/Wind Harmer
1.905
276764AC1-053 GEN2
Solar/Wind Harmer
1.905
960681AF2-359 GEN
Solar/Wind Helper
2.351
990577J1339
External Queue
10.091670036315918
991777J1629 G
External Queue
9.159218788146973
991247J1684 G
External Queue
7.1917877197265625
990582J1340
External Queue
10.091670036315918
990512J1326
External Queue
4.031956195831299
990117J1214
External Queue
13.869928359985352
990727J1377 G
External Queue
4.68088960647583
990762J1386
External Queue
5.7299675941467285
990407J1304
External Queue
3.1176300048828125
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.11
NYPJM->LTFIMP_NY
CLTF
0.68
WECLTFEXP_WEC->PJM
CLTF
2.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.189
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.478
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.037
MECLTFEXP_MEC->PJM
CLTF
9.297
SIGELTFEXP_SIGE->PJM
CLTF
0.017
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.237
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.224
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.608
LAGNLTFEXP_LAGN->PJM
CLTF
3.197
TVALTFEXP_TVA->PJM
CLTF
0.862

Details for 18MOROCCO-02ALLEN 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-022T_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:ATSI/METC
Facility Description:
18MOROCCO-02ALLEN 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-022T_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.55 %
Rating:1793.0 MVA
Rating Type:B
MVA to Mitigate:2089.8
MW Contribution:
7.02
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
944961AF1-161 GEN
50/50
2.637
962601AG1-109 GEN
50/50
2.637
270505AE1-170 C O1
Solar/Wind Harmer
12.905
945111AF1-176 GEN
Solar/Wind Harmer
4.799
247643Z2-116 C
Solar/Wind Harmer
0.053
24441505OLIV SLR
Solar/Wind Harmer
0.098
971347AH1-153 GEN
Solar/Wind Harmer
3.328
270063AE2-323 C
Solar/Wind Harmer
1.303
972231SS25-0005
Solar/Wind Harmer
5.592
972181SS23-001
Solar/Wind Harmer
3.495
274752CRETE EC ;2U
Adder
2.88
274753CRETE EC ;3U
Adder
2.88
274724RIVER EC ;11
Adder
10.289
274814UNIV PK N;0U
Adder
2.914
274807UNIV PK N;3U
Adder
2.908
274811UNIV PK N;7U
Adder
2.889
276164X3-005 C
Solar/Wind Harmer
0.402
274803UNIV PARK;6U
Adder
3.299
274826FISK ;BP
Adder
6.177
964401AG1-302 GEN
Solar/Wind Harmer
5.114
972038AH1-567 GEN2
Adder
0.205
274887GEN-1.85
Solar/Wind Harmer
2.987
276772AC2-154 GEN
Solar/Wind Harmer
1.565
276843GEN-1.7
Solar/Wind Harmer
0.321
276806AD2-047 C O1
Solar/Wind Harmer
5.998
274772LINCOLN ;3U
Adder
3.459
274676JOLIET 29;8U
Adder
16.383
972259AH1-714 GEN
Adder
10.554
274729ELWOOD EC;1P
Adder
9.071
274730ELWOOD EC;6P
Adder
9.072
274734ELWOOD EC;8P
Adder
9.072
274736ELWOOD EC;9P
Adder
9.072
939351AE1-166 GEN
Solar/Wind Harmer
3.267
970707AG2-453 GEN
Solar/Wind Harmer
15.412
274862TOP CROP ;2U
Solar/Wind Harmer
2.742
943121AE2-341 GEN
Solar/Wind Harmer
8.126
943591AF1-030 GEN
Solar/Wind Harmer
5.417
274682WAUKEGAN ;7U
Adder
9.659
276868AE1-113 GEN
Solar/Wind Harmer
5.362
274879MINONK ;1U
Solar/Wind Harmer
3.575
276799AD1-013 GEN
Solar/Wind Harmer
1.159
946671AF1-331 GEN
Solar/Wind Harmer
0.22
274855GSG-6 ;RU
Solar/Wind Harmer
1.936
274850MENDOTA H;RU
Solar/Wind Harmer
1.346
276602WESTBROOK C
Solar/Wind Harmer
1.115
959091AF2-200 GEN
Solar/Wind Harmer
10.43
970571AG2-364 GEN
Solar/Wind Harmer
10.332
274760LEE CO EC;1U
Adder
4.753
274767LEE CO EC;8U
Adder
4.697
241832AE2-181_GEN
Solar/Wind Helper
1.209
270541AE2-072 C
Solar/Wind Helper
1.802
961051AF2-396 GEN
Solar/Wind Harmer
14.056
961051AF2-396 GEN
Solar/Wind Harmer
6.538
247620Y3-023
Adder
0.331
965681AG1-436 GEN
Solar/Wind Harmer
8.463
965791AG1-447 GEN
Solar/Wind Harmer
4.33
970349AG2-230 GEN
Solar/Wind Harmer
9.984
270535AF1-215 GEN1
Solar/Wind Harmer
2.67
270536AF1-215 GEN2
Solar/Wind Harmer
2.67
274805UNIV PK N;1U
Adder
2.895
274808UNIV PK N;4U
Adder
2.876
274888KELLY CRK;1U
Solar/Wind Harmer
3.309
276776AD2-060 GEN
Solar/Wind Harmer
0.235
958011AF2-095 GEN
Solar/Wind Harmer
8.074
970941AG2-585 GEN
Solar/Wind Harmer
3.084
274770LINCOLN ;1U
Adder
3.459
274771LINCOLN ;2U
Adder
3.459
276893AG1-478 C
Solar/Wind Harmer
0.242
274674JOLIET 9 ;6U
Adder
8.497
276897AD1-100 C
Solar/Wind Harmer
25.593
958481AF2-142 GEN
Solar/Wind Harmer
8.131
274696ROCKY RD ;4P
Adder
6.118
274695ROCKY RD ;2P
Adder
5.977
274693ROCKY RD ;1P
Adder
5.918
274697ROCKY RD ;3P
Adder
1.624
274683WAUKEGAN ;8U
Adder
11.31
274683WAUKEGAN ;8U
Adder
9.534
958491AF2-143 GEN
Solar/Wind Harmer
8.016
962691AG1-118 GEN
Solar/Wind Harmer
15.961
276901AD2-066 C O1
Solar/Wind Harmer
1.861
960751AF2-366 GEN
Solar/Wind Harmer
1.523
276872AE1-163_GEN1
Solar/Wind Harmer
3.518
276876AE1-163_GEN2
Solar/Wind Harmer
3.518
971341AH1-150 GEN
Solar/Wind Harmer
10.43
971343AH1-151 GEN
Solar/Wind Harmer
10.43
972235AH1-702 GEN1
Adder
1.308
972236AH1-702 GEN2
Adder
1.137
274764LEE CO EC;5U
Adder
4.765
274765LEE CO EC;6U
Adder
4.765
274762LEE CO EC;3U
Adder
4.753
274763LEE CO EC;4U
Adder
4.709
241996AE2-282_GEN
Solar/Wind Helper
2.772
241808AF1-120 C
Solar/Wind Helper
1.549
247522W1-056 GEN
Solar/Wind Helper
0.794
247604X1-042
50/50
0.026
24307105BERRINSP G
50/50
0.02
24441205WTRV SLR C
Solar/Wind Harmer
0.137
270449AD2-020 GEN
Solar/Wind Harmer
2.542
943021AE2-325 GEN
Solar/Wind Harmer
3.304
957891AF2-083 GEN
Solar/Wind Harmer
12.756
945111AF1-176 GEN
Solar/Wind Harmer
15.144
270216AD2-079_GEN
Solar/Wind Harmer
0.459
24639705ELKHART HY
Adder
0.115
970373AG2-245 GEN
Solar/Wind Harmer
12.863
274751CRETE EC ;1U
Adder
2.88
274754CRETE EC ;4U
Adder
2.88
270055AF2-134 C O1
Solar/Wind Harmer
1.78
274723RIVER EC ;12
Adder
10.412
274812UNIV PK N;8U
Adder
2.889
274802UNIV PARK;5U
Adder
3.299
958381AF2-132 GEN
Solar/Wind Harmer
5.114
964861AG1-349 GEN
Solar/Wind Harmer
4.411
971917AH1-482 GEN
Solar/Wind Harmer
5.089
972207SS24-0001
Solar/Wind Harmer
12.298
274773LINCOLN ;4U
Adder
3.459
274774LINCOLN ;5U
Adder
3.459
274676JOLIET 29;8U
Adder
16.99
274732ELWOOD EC;7P
Adder
9.072
274674JOLIET 9 ;6U
Adder
8.497
941551AE2-152 GEN
Solar/Wind Harmer
2.499
274871GR RIDGE ;2U
Solar/Wind Harmer
4.2
274847GR RIDGE ;BU
Solar/Wind Harmer
2.761
274745AC1-111 GEN9
Adder
3.031
274861TOP CROP ;1U
Solar/Wind Harmer
3.284
276694AA1-018 GEN2
Solar/Wind Harmer
3.42
276691AA1-018 GEN1
Solar/Wind Harmer
0.409
274682WAUKEGAN ;7U
Adder
9.659
274828WAUKEGAN ;BP
Adder
5.929
276805AD2-038 GEN
Solar/Wind Harmer
2.74
962781AG1-127 GEN
Solar/Wind Harmer
5.047
276882AE2-255 GEN
Solar/Wind Harmer
1.787
274872LEEDK;1U
Solar/Wind Harmer
4.347
940581AE2-045 GEN
Solar/Wind Harmer
5.396
971605AH1-302 GEN
Solar/Wind Harmer
4.614
939401AE1-172 GEN
Solar/Wind Harmer
7.352
971997AH1-543 GEN
Solar/Wind Harmer
8.282
957471AF2-041 GEN
Solar/Wind Harmer
15.644
959081AF2-199 GEN
Solar/Wind Harmer
5.215
971067AG2-660 GEN
Solar/Wind Harmer
1.213
274822ROCKFORD ;11
Adder
10.209
970819AG2-516 GEN
Solar/Wind Harmer
6.206
970569AG2-363 GEN
Solar/Wind Harmer
15.499
274761LEE CO EC;2U
Adder
4.753
274766LEE CO EC;7U
Adder
4.697
241840AF1-064_GEN
Solar/Wind Helper
1.561
241807AE2-176_GEN
Solar/Wind Helper
1.818
241885AC2-103 GEN1
Solar/Wind Helper
2.422
960841AF2-375 GEN
Solar/Wind Helper
1.504
958961AF2-187 GEN
Solar/Wind Helper
1.052
24344005CKG1
50/50
5.708
971549AH1-272 GEN
Solar/Wind Harmer
25.846
944161AF1-084 GEN
Solar/Wind Harmer
2.074
971771AH1-392 GEN
Solar/Wind Harmer
6.841
270526AF1-158 GEN
Solar/Wind Harmer
3.349
960681AF2-359 GEN
Solar/Wind Harmer
2.558
970031AG2-029 GEN
Solar/Wind Harmer
15.55
972037AH1-567 GEN1
Adder
0.104
274827FISK ;RP
Adder
4.378
274800UNIV PARK;3U
Adder
3.28
274801UNIV PARK;4U
Adder
3.28
960591AF2-350 GEN
Solar/Wind Harmer
5.607
274775LINCOLN ;6U
Adder
3.459
274776LINCOLN ;7U
Adder
3.459
274777LINCOLN ;8U
Adder
3.459
972228AH1-698 GEN2
Adder
2.066
972227AH1-698 GEN1
Adder
1.454
274687WILL CNTY;4U
Adder
15.527
274687WILL CNTY;4U
Adder
15.527
274675JOLIET 29;7U
Adder
16.99
274675JOLIET 29;7U
Adder
16.383
276893AG1-478 C
Solar/Wind Harmer
0.304
274728ELWOOD EC;5P
Adder
9.072
274731ELWOOD EC;2P
Adder
9.071
274733ELWOOD EC;3P
Adder
9.071
274735ELWOOD EC;4P
Adder
9.071
958391AF2-133 GEN
Solar/Wind Harmer
4.996
970833AG2-524 GEN
Solar/Wind Harmer
4.773
970833AG2-524 GEN
Solar/Wind Harmer
2.22
274744AC1-111 GEN8
Adder
3.031
274746AC1-111 G10
Adder
3.031
959141AF2-205 GEN
Solar/Wind Harmer
3.272
970073AG2-061 GEN
Solar/Wind Harmer
1.243
971411AH1-196 GEN
Solar/Wind Harmer
7.883
971675AH1-338 GEN
Solar/Wind Harmer
9.442
276861AD2-134 GEN
Solar/Wind Harmer
0.936
276863AD2-134 GEN
Solar/Wind Harmer
0.936
276889AE2-281 GEN
Solar/Wind Harmer
1.005
971171AH1-044 GEN
Solar/Wind Harmer
10.43
274823ROCKFORD ;21
Adder
10.135
274863CRW1-WTG
Solar/Wind Harmer
2.896
274864CRW2-WTG
Solar/Wind Harmer
2.896
274856ECOGROVE ;U1
Solar/Wind Harmer
1.741
276611AD2-172 GEN
Solar/Wind Harmer
1.321
276612AE2-035 GEN
Solar/Wind Harmer
1.321
926823AC1-168 GEN
Solar/Wind Harmer
2.21
972267AH1-718 GEN
Adder
2.106
945411AF1-206 GEN
Solar/Wind Helper
5.235
241886AC2-103 GEN2
Solar/Wind Helper
2.422
945641AF1-229 GEN
Solar/Wind Helper
1.376
270499AE1-146 GEN
Solar/Wind Helper
2.296
971681AH1-341 GEN
Solar/Wind Harmer
7.02
991177J1571 G
External Queue
65.40199279785156
991182J1586 G
External Queue
85.20255279541016
991227J1663 G
External Queue
17.943559646606445
990527J1329
External Queue
6.745199680328369
990142J1224
External Queue
49.30740737915039
NYPJM->LTFIMP_NY
CLTF
0.965
LGEELTFEXP_LGEE->PJM
CLTF
1.446
WECLTFEXP_WEC->PJM
CLTF
1.982
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.659
CPLELTFEXP_CPLE->PJM
CLTF
0.359
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.015
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.508
MECLTFEXP_MEC->PJM
CLTF
7.305
SIGELTFEXP_SIGE->PJM
CLTF
0.142
AG2-052LTFEXP_AG2-052->PJM
LTF
0.129
AH1-155LTFEXP_AH1-155->PJM
LTF
0.193
LAGNLTFEXP_LAGN->PJM
CLTF
4.718
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.835
TVALTFEXP_TVA->PJM
CLTF
1.976

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.69 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1842.48
MW Contribution:
10.28
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.08 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1750.69
MW Contribution:
9.91
Bus #Bus NameTypeMW Contribution
274650KINCAID ;1U
50/50
4.61
274651KINCAID ;2U
50/50
4.609
276916AD2-100_GEN
Solar/Wind Harmer
28.636
276911AD2-131_GEN
Solar/Wind Harmer
5.787
276615X2-022 GEN
Solar/Wind Harmer
2.299
276838X2-022 GEN2
Solar/Wind Harmer
0.273
274880W4-005 GEN4
Solar/Wind Harmer
3.367
276174W4-005 GEN2
Solar/Wind Harmer
3.367
960611AF2-352 GEN
Solar/Wind Harmer
2.21
942111AE2-223 GEN
Solar/Wind Harmer
7.25
276645AC1-214 GEN1
Solar/Wind Harmer
1.021
276158O29GEN2
Solar/Wind Harmer
3.612
276157O29GEN1
Solar/Wind Harmer
2.746
276872AE1-163_GEN1
Solar/Wind Harmer
4.645
276876AE1-163_GEN2
Solar/Wind Harmer
4.645
274764LEE CO EC;5U
Adder
6.427
274765LEE CO EC;6U
Adder
6.427
274762LEE CO EC;3U
Adder
6.412
274763LEE CO EC;4U
Adder
6.351
938861AE1-114 GEN
Solar/Wind Harmer
5.613
972235AH1-702 GEN1
Adder
1.678
972236AH1-702 GEN2
Adder
1.459
276901AD2-066 C O1
Solar/Wind Harmer
2.329
971341AH1-150 GEN
Solar/Wind Harmer
13.267
971343AH1-151 GEN
Solar/Wind Harmer
13.267
958491AF2-143 GEN
Solar/Wind Harmer
9.761
960751AF2-366 GEN
Solar/Wind Harmer
1.833
962691AG1-118 GEN
Solar/Wind Harmer
19.071
274696ROCKY RD ;4P
Adder
7.081
274695ROCKY RD ;2P
Adder
6.918
274693ROCKY RD ;1P
Adder
6.85
274697ROCKY RD ;3P
Adder
1.879
958481AF2-142 GEN
Solar/Wind Harmer
9.317
274683WAUKEGAN ;8U
Adder
13.014
274683WAUKEGAN ;8U
Adder
10.97
276897AD1-100 C
Solar/Wind Harmer
27.975
276893AG1-478 C
Solar/Wind Harmer
0.256
274674JOLIET 9 ;6U
Adder
8.968
274805UNIV PK N;1U
Adder
2.429
274808UNIV PK N;4U
Adder
2.413
274770LINCOLN ;1U
Solar/Wind Harmer
2.542
274771LINCOLN ;2U
Solar/Wind Harmer
2.542
944221AF1-090 GEN
Solar/Wind Harmer
16.507
276763AC1-053 GEN1
Solar/Wind Harmer
4.451
276764AC1-053 GEN2
Solar/Wind Harmer
4.451
276668AB2-070 GEN1
Solar/Wind Harmer
2.443
276848AB2-070 GEN3
Solar/Wind Harmer
2.443
276849AB2-070 GEN2
Solar/Wind Harmer
2.443
274853TWINGROVE;U1
Solar/Wind Harmer
6.845
274854TWINGROVE;U2
Solar/Wind Harmer
6.702
276726Z2-087_GEN
Solar/Wind Harmer
6.993
959341AF2-225 GEN
Solar/Wind Harmer
13.266
970169AG2-114 GEN
Solar/Wind Harmer
7.904
274877BISHOP HL;1U
Solar/Wind Harmer
2.588
274863CRW1-WTG
Solar/Wind Harmer
4.196
274864CRW2-WTG
Solar/Wind Harmer
4.196
946321AF1-296 GEN
Solar/Wind Harmer
7.739
926823AC1-168 GEN
Solar/Wind Harmer
3.121
276741O09 GEN1
Solar/Wind Harmer
2.579
972267AH1-718 GEN
Adder
2.934
276889AE2-281 GEN
Solar/Wind Harmer
1.327
971681AH1-341 GEN
Solar/Wind Harmer
10.284
274856ECOGROVE ;U1
Solar/Wind Harmer
2.27
276611AD2-172 GEN
Solar/Wind Harmer
1.722
276612AE2-035 GEN
Solar/Wind Harmer
1.722
971171AH1-044 GEN
Solar/Wind Harmer
13.267
274823ROCKFORD ;21
Adder
12.892
276861AD2-134 GEN
Solar/Wind Harmer
1.172
276863AD2-134 GEN
Solar/Wind Harmer
1.172
971675AH1-338 GEN
Solar/Wind Harmer
11.806
970073AG2-061 GEN
Solar/Wind Harmer
1.513
971411AH1-196 GEN
Solar/Wind Harmer
9.725
274744AC1-111 GEN8
Adder
3.411
274746AC1-111 G10
Adder
3.411
970833AG2-524 GEN
Solar/Wind Harmer
5.303
970833AG2-524 GEN
Solar/Wind Harmer
2.466
274731ELWOOD EC;2P
Adder
9.615
274733ELWOOD EC;3P
Adder
9.615
274735ELWOOD EC;4P
Adder
9.615
274728ELWOOD EC;5P
Adder
9.611
276893AG1-478 C
Solar/Wind Harmer
0.321
274675JOLIET 29;7U
Adder
17.572
274675JOLIET 29;7U
Adder
16.944
972227AH1-698 GEN1
Adder
1.481
972228AH1-698 GEN2
Adder
2.102
274687WILL CNTY;4U
Adder
15.801
274687WILL CNTY;4U
Adder
15.801
274800UNIV PARK;3U
Adder
3.159
274801UNIV PARK;4U
Adder
3.159
274827FISK ;RP
Adder
4.141
972037AH1-567 GEN1
Adder
0.097
274775LINCOLN ;6U
Solar/Wind Harmer
2.542
274776LINCOLN ;7U
Solar/Wind Harmer
2.542
274777LINCOLN ;8U
Solar/Wind Harmer
2.542
965911AG1-460 GEN
Solar/Wind Harmer
1.843
276621W2-048 GEN
Solar/Wind Harmer
7.321
276686W4-005 GEN3
Solar/Wind Harmer
3.367
276655WTG1_EQ
Solar/Wind Harmer
7.719
276656WTG2_EQ
Solar/Wind Harmer
1.022
939741AE1-205 GEN
Solar/Wind Harmer
17.688
274848CAMPGROVE;RU
Solar/Wind Harmer
5.049
276646AC1-214 GEN2
Solar/Wind Harmer
1.021
276708O09 GEN2
Solar/Wind Harmer
2.579
970569AG2-363 GEN
Solar/Wind Harmer
21.597
939401AE1-172 GEN
Solar/Wind Harmer
9.915
274858EASY ROAD;U2
Solar/Wind Harmer
3.302
274761LEE CO EC;2U
Adder
6.412
274766LEE CO EC;7U
Adder
6.336
971997AH1-543 GEN
Solar/Wind Harmer
10.833
970819AG2-516 GEN
Solar/Wind Harmer
8.028
276882AE2-255 GEN
Solar/Wind Harmer
2.249
957471AF2-041 GEN
Solar/Wind Harmer
19.901
959081AF2-199 GEN
Solar/Wind Harmer
6.634
971067AG2-660 GEN
Solar/Wind Harmer
1.543
274822ROCKFORD ;11
Adder
12.987
276805AD2-038 GEN
Solar/Wind Harmer
3.337
274872LEEDK;1U
Solar/Wind Harmer
5.275
962781AG1-127 GEN
Solar/Wind Harmer
6.076
276694AA1-018 GEN2
Solar/Wind Harmer
3.919
276691AA1-018 GEN1
Solar/Wind Harmer
0.468
274861TOP CROP ;1U
Solar/Wind Harmer
3.762
274828WAUKEGAN ;BP
Adder
6.821
274682WAUKEGAN ;7U
Adder
11.069
274745AC1-111 GEN9
Adder
3.411
274871GR RIDGE ;2U
Solar/Wind Harmer
4.683
274847GR RIDGE ;BU
Solar/Wind Harmer
3.079
941551AE2-152 GEN
Solar/Wind Harmer
2.731
274732ELWOOD EC;7P
Adder
9.611
274674JOLIET 9 ;6U
Adder
8.968
274676JOLIET 29;8U
Adder
17.572
274802UNIV PARK;5U
Adder
3.082
274812UNIV PK N;8U
Adder
2.424
274723RIVER EC ;12
Adder
8.388
274751CRETE EC ;1U
Adder
3.574
274754CRETE EC ;4U
Adder
3.574
972207SS24-0001
Solar/Wind Harmer
9.04
274773LINCOLN ;4U
Solar/Wind Harmer
2.542
274774LINCOLN ;5U
Solar/Wind Harmer
2.542
942481AE2-261 GEN
Solar/Wind Harmer
39.494
957381AF2-032 GEN
Solar/Wind Harmer
2.61
276785W4-005 GEN1
Solar/Wind Harmer
3.367
971993AH1-541 GEN
Solar/Wind Harmer
10.287
965091AG1-374 GEN
Solar/Wind Harmer
28.503
959611AF2-252 GEN
Solar/Wind Harmer
2.21
274878BISHOP HL;2U
Solar/Wind Harmer
2.588
276782AC1-033 GEN
Solar/Wind Harmer
3.058
274851PROVIDENC;RU
Solar/Wind Harmer
2.17
274849CRESCENT ;1U
Solar/Wind Harmer
1.409
965931AG1-462 GEN
Solar/Wind Harmer
19.099
971087AG2-675 GEN
Solar/Wind Harmer
2.787
970571AG2-364 GEN
Solar/Wind Harmer
14.398
276603SUBLETTE C
Solar/Wind Harmer
0.729
274857EASY ROAD;U1
Solar/Wind Harmer
3.302
274760LEE CO EC;1U
Adder
6.412
274767LEE CO EC;8U
Adder
6.336
276868AE1-113 GEN
Solar/Wind Harmer
6.746
274879MINONK ;1U
Solar/Wind Harmer
4.498
959091AF2-200 GEN
Solar/Wind Harmer
13.267
274855GSG-6 ;RU
Solar/Wind Harmer
2.424
274850MENDOTA H;RU
Solar/Wind Harmer
1.685
276602WESTBROOK C
Solar/Wind Harmer
1.395
276799AD1-013 GEN
Solar/Wind Harmer
1.448
946671AF1-331 GEN
Solar/Wind Harmer
0.274
274862TOP CROP ;2U
Solar/Wind Harmer
3.141
274682WAUKEGAN ;7U
Adder
11.069
943121AE2-341 GEN
Solar/Wind Harmer
9.181
943591AF1-030 GEN
Solar/Wind Harmer
6.12
939351AE1-166 GEN
Solar/Wind Harmer
3.571
970707AG2-453 GEN
Solar/Wind Harmer
16.585
274729ELWOOD EC;1P
Adder
9.615
274730ELWOOD EC;6P
Adder
9.611
274734ELWOOD EC;8P
Adder
9.611
274736ELWOOD EC;9P
Adder
9.611
972259AH1-714 GEN
Adder
11.125
274676JOLIET 29;8U
Adder
16.945
972038AH1-567 GEN2
Adder
0.198
274826FISK ;BP
Adder
5.844
274803UNIV PARK;6U
Adder
3.082
274814UNIV PK N;0U
Adder
2.445
274807UNIV PK N;3U
Adder
2.439
274811UNIV PK N;7U
Adder
2.424
274724RIVER EC ;11
Adder
8.316
274752CRETE EC ;2U
Adder
3.574
274753CRETE EC ;3U
Adder
3.574
274772LINCOLN ;3U
Solar/Wind Harmer
2.542
991197J1626
External Queue
21.400691986083984
991267J1714
External Queue
14.267128944396973
991192J1610 G
External Queue
6.472771167755127
990353J1289
External Queue
6.685102939605713
991037J1464 G
External Queue
40.380802154541016
990272J1263 G
External Queue
55.527957916259766
990272J1263 G
External Queue
31.858911514282227
991082J1475 G
External Queue
40.63506317138672
NYPJM->LTFIMP_NY
CLTF
0.395
WECLTFEXP_WEC->PJM
CLTF
2.51
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.415
CPLELTFEXP_CPLE->PJM
CLTF
0.664
CBM West 2LTFEXP_CBM-W2->PJM
CBM
85.93
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.709
MECLTFEXP_MEC->PJM
CLTF
13.648
SIGELTFEXP_SIGE->PJM
CLTF
0.045
AG2-052LTFEXP_AG2-052->PJM
LTF
0.069
AH1-155LTFEXP_AH1-155->PJM
LTF
0.104
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.781
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.055
LAGNLTFEXP_LAGN->PJM
CLTF
11.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.196
TVALTFEXP_TVA->PJM
CLTF
4.256

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.19 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1801.56
MW Contribution:
10.09
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.06 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1766.85
MW Contribution:
9.88
Bus #Bus NameTypeMW Contribution
274650KINCAID ;1U
50/50
4.604
274651KINCAID ;2U
50/50
4.603
276916AD2-100_GEN
Solar/Wind Harmer
28.612
276911AD2-131_GEN
Solar/Wind Harmer
5.783
276615X2-022 GEN
Solar/Wind Harmer
2.293
276838X2-022 GEN2
Solar/Wind Harmer
0.272
274880W4-005 GEN4
Solar/Wind Harmer
3.355
276174W4-005 GEN2
Solar/Wind Harmer
3.355
960611AF2-352 GEN
Solar/Wind Harmer
2.192
942111AE2-223 GEN
Solar/Wind Harmer
7.181
276645AC1-214 GEN1
Solar/Wind Harmer
1.006
276158O29GEN2
Solar/Wind Harmer
3.552
944221AF1-090 GEN
Solar/Wind Harmer
16.512
276763AC1-053 GEN1
Solar/Wind Harmer
4.437
276764AC1-053 GEN2
Solar/Wind Harmer
4.437
276668AB2-070 GEN1
Solar/Wind Harmer
2.435
276848AB2-070 GEN3
Solar/Wind Harmer
2.435
276849AB2-070 GEN2
Solar/Wind Harmer
2.435
274853TWINGROVE;U1
Solar/Wind Harmer
6.791
274854TWINGROVE;U2
Solar/Wind Harmer
6.649
276726Z2-087_GEN
Solar/Wind Harmer
6.926
959341AF2-225 GEN
Solar/Wind Harmer
13.14
970169AG2-114 GEN
Solar/Wind Harmer
7.793
274877BISHOP HL;1U
Solar/Wind Harmer
2.55
274863CRW1-WTG
Solar/Wind Harmer
4.128
274864CRW2-WTG
Solar/Wind Harmer
4.128
946321AF1-296 GEN
Solar/Wind Harmer
7.624
926823AC1-168 GEN
Solar/Wind Harmer
3.067
276741O09 GEN1
Solar/Wind Harmer
2.536
972267AH1-718 GEN
Adder
2.882
276889AE2-281 GEN
Solar/Wind Harmer
1.301
971681AH1-341 GEN
Solar/Wind Harmer
10.088
274856ECOGROVE ;U1
Solar/Wind Harmer
2.225
276611AD2-172 GEN
Solar/Wind Harmer
1.688
276612AE2-035 GEN
Solar/Wind Harmer
1.688
971171AH1-044 GEN
Solar/Wind Harmer
12.992
274823ROCKFORD ;21
Adder
12.625
276861AD2-134 GEN
Solar/Wind Harmer
1.147
276863AD2-134 GEN
Solar/Wind Harmer
1.147
971675AH1-338 GEN
Solar/Wind Harmer
11.554
970073AG2-061 GEN
Solar/Wind Harmer
1.479
971411AH1-196 GEN
Solar/Wind Harmer
9.512
274744AC1-111 GEN8
Adder
3.324
274746AC1-111 G10
Adder
3.324
970833AG2-524 GEN
Solar/Wind Harmer
5.164
970833AG2-524 GEN
Solar/Wind Harmer
2.402
274731ELWOOD EC;2P
Adder
9.343
942481AE2-261 GEN
Solar/Wind Harmer
39.447
957381AF2-032 GEN
Solar/Wind Harmer
2.607
276785W4-005 GEN1
Solar/Wind Harmer
3.355
971993AH1-541 GEN
Solar/Wind Harmer
10.252
965091AG1-374 GEN
Solar/Wind Harmer
28.28
959611AF2-252 GEN
Solar/Wind Harmer
2.192
274878BISHOP HL;2U
Solar/Wind Harmer
2.55
276782AC1-033 GEN
Solar/Wind Harmer
3.014
965911AG1-460 GEN
Solar/Wind Harmer
1.841
276621W2-048 GEN
Solar/Wind Harmer
7.302
276686W4-005 GEN3
Solar/Wind Harmer
3.355
276655WTG1_EQ
Solar/Wind Harmer
7.645
276656WTG2_EQ
Solar/Wind Harmer
1.012
939741AE1-205 GEN
Solar/Wind Harmer
17.52
274848CAMPGROVE;RU
Solar/Wind Harmer
4.979
276646AC1-214 GEN2
Solar/Wind Harmer
1.006
276708O09 GEN2
Solar/Wind Harmer
2.536
970569AG2-363 GEN
Solar/Wind Harmer
21.211
274851PROVIDENC;RU
Solar/Wind Harmer
2.138
274849CRESCENT ;1U
Solar/Wind Harmer
1.388
965931AG1-462 GEN
Solar/Wind Harmer
18.822
971087AG2-675 GEN
Solar/Wind Harmer
2.747
970571AG2-364 GEN
Solar/Wind Harmer
14.141
276603SUBLETTE C
Solar/Wind Harmer
0.715
274857EASY ROAD;U1
Solar/Wind Harmer
3.24
274760LEE CO EC;1U
Adder
6.292
274767LEE CO EC;8U
Adder
6.218
276868AE1-113 GEN
Solar/Wind Harmer
6.602
274879MINONK ;1U
Solar/Wind Harmer
4.401
959091AF2-200 GEN
Solar/Wind Harmer
12.992
274855GSG-6 ;RU
Solar/Wind Harmer
2.372
274850MENDOTA H;RU
Solar/Wind Harmer
1.649
276602WESTBROOK C
Solar/Wind Harmer
1.365
276799AD1-013 GEN
Solar/Wind Harmer
1.417
946671AF1-331 GEN
Solar/Wind Harmer
0.268
274862TOP CROP ;2U
Solar/Wind Harmer
3.062
274682WAUKEGAN ;7U
Adder
10.794
943121AE2-341 GEN
Solar/Wind Harmer
8.947
943591AF1-030 GEN
Solar/Wind Harmer
5.965
939351AE1-166 GEN
Solar/Wind Harmer
3.476
970707AG2-453 GEN
Solar/Wind Harmer
16.13
274729ELWOOD EC;1P
Adder
9.343
274730ELWOOD EC;6P
Adder
9.339
274734ELWOOD EC;8P
Adder
9.339
274736ELWOOD EC;9P
Adder
9.339
972259AH1-714 GEN
Adder
10.81
274676JOLIET 29;8U
Adder
16.447
972038AH1-567 GEN2
Adder
0.191
274826FISK ;BP
Adder
5.646
274803UNIV PARK;6U
Adder
2.976
274814UNIV PK N;0U
Adder
2.347
274807UNIV PK N;3U
Adder
2.342
274811UNIV PK N;7U
Adder
2.327
274724RIVER EC ;11
Adder
7.96
274772LINCOLN ;3U
Solar/Wind Harmer
2.468
276157O29GEN1
Solar/Wind Harmer
2.701
276872AE1-163_GEN1
Solar/Wind Harmer
4.553
276876AE1-163_GEN2
Solar/Wind Harmer
4.553
274764LEE CO EC;5U
Adder
6.307
274765LEE CO EC;6U
Adder
6.307
274762LEE CO EC;3U
Adder
6.292
274763LEE CO EC;4U
Adder
6.233
938861AE1-114 GEN
Solar/Wind Harmer
5.506
972235AH1-702 GEN1
Adder
1.644
972236AH1-702 GEN2
Adder
1.429
276901AD2-066 C O1
Solar/Wind Harmer
2.279
971341AH1-150 GEN
Solar/Wind Harmer
12.992
971343AH1-151 GEN
Solar/Wind Harmer
12.992
958491AF2-143 GEN
Solar/Wind Harmer
9.54
960751AF2-366 GEN
Solar/Wind Harmer
1.791
962691AG1-118 GEN
Solar/Wind Harmer
18.629
274696ROCKY RD ;4P
Adder
6.909
274695ROCKY RD ;2P
Adder
6.749
274693ROCKY RD ;1P
Adder
6.682
274697ROCKY RD ;3P
Adder
1.833
958481AF2-142 GEN
Solar/Wind Harmer
9.084
274683WAUKEGAN ;8U
Adder
12.693
274683WAUKEGAN ;8U
Adder
10.699
276897AD1-100 C
Solar/Wind Harmer
27.225
276893AG1-478 C
Solar/Wind Harmer
0.248
274674JOLIET 9 ;6U
Adder
8.713
274805UNIV PK N;1U
Adder
2.332
274808UNIV PK N;4U
Adder
2.317
274770LINCOLN ;1U
Solar/Wind Harmer
2.468
274771LINCOLN ;2U
Solar/Wind Harmer
2.468
274733ELWOOD EC;3P
Adder
9.343
274735ELWOOD EC;4P
Adder
9.343
274728ELWOOD EC;5P
Adder
9.339
276893AG1-478 C
Solar/Wind Harmer
0.312
274675JOLIET 29;7U
Adder
17.056
274675JOLIET 29;7U
Adder
16.447
972227AH1-698 GEN1
Adder
1.437
972228AH1-698 GEN2
Adder
2.039
274687WILL CNTY;4U
Adder
15.325
274687WILL CNTY;4U
Adder
15.325
274800UNIV PARK;3U
Adder
3.056
274801UNIV PARK;4U
Adder
3.056
274827FISK ;RP
Adder
4.002
972037AH1-567 GEN1
Adder
0.093
274775LINCOLN ;6U
Solar/Wind Harmer
2.468
274776LINCOLN ;7U
Solar/Wind Harmer
2.468
274777LINCOLN ;8U
Solar/Wind Harmer
2.468
939401AE1-172 GEN
Solar/Wind Harmer
9.731
274858EASY ROAD;U2
Solar/Wind Harmer
3.24
274761LEE CO EC;2U
Adder
6.292
274766LEE CO EC;7U
Adder
6.218
971997AH1-543 GEN
Solar/Wind Harmer
10.617
970819AG2-516 GEN
Solar/Wind Harmer
7.867
276882AE2-255 GEN
Solar/Wind Harmer
2.201
957471AF2-041 GEN
Solar/Wind Harmer
19.487
959081AF2-199 GEN
Solar/Wind Harmer
6.496
971067AG2-660 GEN
Solar/Wind Harmer
1.511
274822ROCKFORD ;11
Adder
12.717
276805AD2-038 GEN
Solar/Wind Harmer
3.261
274872LEEDK;1U
Solar/Wind Harmer
5.156
962781AG1-127 GEN
Solar/Wind Harmer
5.937
276694AA1-018 GEN2
Solar/Wind Harmer
3.821
276691AA1-018 GEN1
Solar/Wind Harmer
0.457
274861TOP CROP ;1U
Solar/Wind Harmer
3.668
274828WAUKEGAN ;BP
Adder
6.653
274682WAUKEGAN ;7U
Adder
10.794
274745AC1-111 GEN9
Adder
3.324
274871GR RIDGE ;2U
Solar/Wind Harmer
4.561
274847GR RIDGE ;BU
Solar/Wind Harmer
2.999
941551AE2-152 GEN
Solar/Wind Harmer
2.658
274732ELWOOD EC;7P
Adder
9.339
274674JOLIET 9 ;6U
Adder
8.713
274676JOLIET 29;8U
Adder
17.056
274802UNIV PARK;5U
Adder
2.976
274812UNIV PK N;8U
Adder
2.327
274723RIVER EC ;12
Adder
8.029
972207SS24-0001
Solar/Wind Harmer
8.776
274773LINCOLN ;4U
Solar/Wind Harmer
2.468
274774LINCOLN ;5U
Solar/Wind Harmer
2.468
991197J1626
External Queue
21.58866310119629
991267J1714
External Queue
14.39244270324707
991192J1610 G
External Queue
6.5306715965271
990353J1289
External Queue
6.74416446685791
991037J1464 G
External Queue
40.75094223022461
990272J1263 G
External Queue
55.988975524902344
990272J1263 G
External Queue
32.123416900634766
991082J1475 G
External Queue
40.801170349121094
NYPJM->LTFIMP_NY
CLTF
0.377
WECLTFEXP_WEC->PJM
CLTF
2.458
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.235
CPLELTFEXP_CPLE->PJM
CLTF
0.722
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.487
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.948
MECLTFEXP_MEC->PJM
CLTF
13.533
SIGELTFEXP_SIGE->PJM
CLTF
0.05
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.099
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.695
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.797
LAGNLTFEXP_LAGN->PJM
CLTF
11.171
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.36
TVALTFEXP_TVA->PJM
CLTF
4.308

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.34 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1787.63
MW Contribution:
9.99
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.44 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1740.28
MW Contribution:
9.79
Bus #Bus NameTypeMW Contribution
942481AE2-261 GEN
Solar/Wind Harmer
39.326
957381AF2-032 GEN
Solar/Wind Harmer
2.599
276785W4-005 GEN1
Solar/Wind Harmer
3.341
971993AH1-541 GEN
Solar/Wind Harmer
10.208
965091AG1-374 GEN
Solar/Wind Harmer
28.11
959611AF2-252 GEN
Solar/Wind Harmer
2.179
274878BISHOP HL;2U
Solar/Wind Harmer
2.529
276782AC1-033 GEN
Solar/Wind Harmer
2.989
274851PROVIDENC;RU
Solar/Wind Harmer
2.12
274849CRESCENT ;1U
Solar/Wind Harmer
1.376
965931AG1-462 GEN
Solar/Wind Harmer
18.668
971087AG2-675 GEN
Solar/Wind Harmer
2.724
970571AG2-364 GEN
Solar/Wind Harmer
14.005
276603SUBLETTE C
Solar/Wind Harmer
0.709
274857EASY ROAD;U1
Solar/Wind Harmer
3.208
274760LEE CO EC;1U
Adder
6.23
274767LEE CO EC;8U
Adder
6.157
276868AE1-113 GEN
Solar/Wind Harmer
6.529
274879MINONK ;1U
Solar/Wind Harmer
4.353
959091AF2-200 GEN
Solar/Wind Harmer
12.855
274855GSG-6 ;RU
Solar/Wind Harmer
2.347
274850MENDOTA H;RU
Solar/Wind Harmer
1.632
276602WESTBROOK C
Solar/Wind Harmer
1.351
276799AD1-013 GEN
Solar/Wind Harmer
1.401
274650KINCAID ;1U
50/50
4.59
274651KINCAID ;2U
50/50
4.588
276916AD2-100_GEN
Solar/Wind Harmer
28.529
276911AD2-131_GEN
Solar/Wind Harmer
5.766
276615X2-022 GEN
Solar/Wind Harmer
2.284
276838X2-022 GEN2
Solar/Wind Harmer
0.271
274880W4-005 GEN4
Solar/Wind Harmer
3.341
276174W4-005 GEN2
Solar/Wind Harmer
3.341
960611AF2-352 GEN
Solar/Wind Harmer
2.179
942111AE2-223 GEN
Solar/Wind Harmer
7.133
276645AC1-214 GEN1
Solar/Wind Harmer
0.997
276158O29GEN2
Solar/Wind Harmer
3.52
276157O29GEN1
Solar/Wind Harmer
2.676
276872AE1-163_GEN1
Solar/Wind Harmer
4.506
276876AE1-163_GEN2
Solar/Wind Harmer
4.506
274764LEE CO EC;5U
Adder
6.245
274765LEE CO EC;6U
Adder
6.245
274762LEE CO EC;3U
Adder
6.23
274763LEE CO EC;4U
Adder
6.172
938861AE1-114 GEN
Solar/Wind Harmer
5.452
972235AH1-702 GEN1
Adder
1.627
972236AH1-702 GEN2
Adder
1.414
276901AD2-066 C O1
Solar/Wind Harmer
2.254
971341AH1-150 GEN
Solar/Wind Harmer
12.855
971343AH1-151 GEN
Solar/Wind Harmer
12.855
958491AF2-143 GEN
Solar/Wind Harmer
9.429
960751AF2-366 GEN
Solar/Wind Harmer
1.771
962691AG1-118 GEN
Solar/Wind Harmer
18.418
274696ROCKY RD ;4P
Adder
6.827
274695ROCKY RD ;2P
Adder
6.669
274693ROCKY RD ;1P
Adder
6.603
274697ROCKY RD ;3P
Adder
1.812
958481AF2-142 GEN
Solar/Wind Harmer
8.97
274683WAUKEGAN ;8U
Adder
12.54
274683WAUKEGAN ;8U
Adder
10.57
276897AD1-100 C
Solar/Wind Harmer
26.851
276893AG1-478 C
Solar/Wind Harmer
0.245
274674JOLIET 9 ;6U
Adder
8.594
274805UNIV PK N;1U
Adder
2.289
274808UNIV PK N;4U
Adder
2.274
274770LINCOLN ;1U
Solar/Wind Harmer
2.429
274771LINCOLN ;2U
Solar/Wind Harmer
2.429
944221AF1-090 GEN
Solar/Wind Harmer
16.473
276763AC1-053 GEN1
Solar/Wind Harmer
4.419
276764AC1-053 GEN2
Solar/Wind Harmer
4.419
276668AB2-070 GEN1
Solar/Wind Harmer
2.425
276848AB2-070 GEN3
Solar/Wind Harmer
2.425
276849AB2-070 GEN2
Solar/Wind Harmer
2.425
274853TWINGROVE;U1
Solar/Wind Harmer
6.751
274854TWINGROVE;U2
Solar/Wind Harmer
6.609
276726Z2-087_GEN
Solar/Wind Harmer
6.88
959341AF2-225 GEN
Solar/Wind Harmer
13.051
970169AG2-114 GEN
Solar/Wind Harmer
7.728
274877BISHOP HL;1U
Solar/Wind Harmer
2.529
274863CRW1-WTG
Solar/Wind Harmer
4.089
274864CRW2-WTG
Solar/Wind Harmer
4.089
946321AF1-296 GEN
Solar/Wind Harmer
7.56
926823AC1-168 GEN
Solar/Wind Harmer
3.039
276741O09 GEN1
Solar/Wind Harmer
2.513
972267AH1-718 GEN
Adder
2.855
276889AE2-281 GEN
Solar/Wind Harmer
1.288
971681AH1-341 GEN
Solar/Wind Harmer
9.989
274856ECOGROVE ;U1
Solar/Wind Harmer
2.202
276611AD2-172 GEN
Solar/Wind Harmer
1.671
276612AE2-035 GEN
Solar/Wind Harmer
1.671
971171AH1-044 GEN
Solar/Wind Harmer
12.855
274823ROCKFORD ;21
Adder
12.492
276861AD2-134 GEN
Solar/Wind Harmer
1.135
276863AD2-134 GEN
Solar/Wind Harmer
1.135
971675AH1-338 GEN
Solar/Wind Harmer
11.43
970073AG2-061 GEN
Solar/Wind Harmer
1.462
971411AH1-196 GEN
Solar/Wind Harmer
9.408
274744AC1-111 GEN8
Adder
3.283
274746AC1-111 G10
Adder
3.283
970833AG2-524 GEN
Solar/Wind Harmer
5.099
970833AG2-524 GEN
Solar/Wind Harmer
2.372
274731ELWOOD EC;2P
Adder
9.216
274733ELWOOD EC;3P
Adder
9.216
274735ELWOOD EC;4P
Adder
9.216
274728ELWOOD EC;5P
Adder
9.212
276893AG1-478 C
Solar/Wind Harmer
0.307
274675JOLIET 29;7U
Adder
16.816
274675JOLIET 29;7U
Adder
16.216
972227AH1-698 GEN1
Adder
1.416
972228AH1-698 GEN2
Adder
2.01
274687WILL CNTY;4U
Adder
15.103
274687WILL CNTY;4U
Adder
15.103
274800UNIV PARK;3U
Adder
3.008
274801UNIV PARK;4U
Adder
3.008
274827FISK ;RP
Adder
3.937
972037AH1-567 GEN1
Adder
0.092
274775LINCOLN ;6U
Solar/Wind Harmer
2.429
274776LINCOLN ;7U
Solar/Wind Harmer
2.429
274777LINCOLN ;8U
Solar/Wind Harmer
2.429
946671AF1-331 GEN
Solar/Wind Harmer
0.266
274862TOP CROP ;2U
Solar/Wind Harmer
3.024
274682WAUKEGAN ;7U
Adder
10.664
943121AE2-341 GEN
Solar/Wind Harmer
8.839
943591AF1-030 GEN
Solar/Wind Harmer
5.893
939351AE1-166 GEN
Solar/Wind Harmer
3.428
970707AG2-453 GEN
Solar/Wind Harmer
15.926
274729ELWOOD EC;1P
Adder
9.216
274730ELWOOD EC;6P
Adder
9.212
274734ELWOOD EC;8P
Adder
9.212
274736ELWOOD EC;9P
Adder
9.212
972259AH1-714 GEN
Adder
10.664
274676JOLIET 29;8U
Adder
16.216
972038AH1-567 GEN2
Adder
0.188
274826FISK ;BP
Adder
5.555
274803UNIV PARK;6U
Adder
2.928
274814UNIV PK N;0U
Adder
2.304
274807UNIV PK N;3U
Adder
2.299
274811UNIV PK N;7U
Adder
2.284
274724RIVER EC ;11
Adder
7.8
274772LINCOLN ;3U
Solar/Wind Harmer
2.429
965911AG1-460 GEN
Solar/Wind Harmer
1.835
276621W2-048 GEN
Solar/Wind Harmer
7.274
276686W4-005 GEN3
Solar/Wind Harmer
3.341
276655WTG1_EQ
Solar/Wind Harmer
7.594
276656WTG2_EQ
Solar/Wind Harmer
1.005
939741AE1-205 GEN
Solar/Wind Harmer
17.401
274848CAMPGROVE;RU
Solar/Wind Harmer
4.938
276646AC1-214 GEN2
Solar/Wind Harmer
0.997
276708O09 GEN2
Solar/Wind Harmer
2.513
970569AG2-363 GEN
Solar/Wind Harmer
21.007
939401AE1-172 GEN
Solar/Wind Harmer
9.629
274858EASY ROAD;U2
Solar/Wind Harmer
3.208
274761LEE CO EC;2U
Adder
6.23
274766LEE CO EC;7U
Adder
6.157
971997AH1-543 GEN
Solar/Wind Harmer
10.508
970819AG2-516 GEN
Solar/Wind Harmer
7.786
276882AE2-255 GEN
Solar/Wind Harmer
2.177
957471AF2-041 GEN
Solar/Wind Harmer
19.283
959081AF2-199 GEN
Solar/Wind Harmer
6.428
971067AG2-660 GEN
Solar/Wind Harmer
1.495
274822ROCKFORD ;11
Adder
12.583
276805AD2-038 GEN
Solar/Wind Harmer
3.223
274872LEEDK;1U
Solar/Wind Harmer
5.099
962781AG1-127 GEN
Solar/Wind Harmer
5.87
276694AA1-018 GEN2
Solar/Wind Harmer
3.773
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
274861TOP CROP ;1U
Solar/Wind Harmer
3.622
274828WAUKEGAN ;BP
Adder
6.573
274682WAUKEGAN ;7U
Adder
10.664
274745AC1-111 GEN9
Adder
3.283
274871GR RIDGE ;2U
Solar/Wind Harmer
4.504
274847GR RIDGE ;BU
Solar/Wind Harmer
2.961
941551AE2-152 GEN
Solar/Wind Harmer
2.622
274732ELWOOD EC;7P
Adder
9.212
274674JOLIET 9 ;6U
Adder
8.594
274676JOLIET 29;8U
Adder
16.816
274802UNIV PARK;5U
Adder
2.928
274812UNIV PK N;8U
Adder
2.284
274723RIVER EC ;12
Adder
7.868
972207SS24-0001
Solar/Wind Harmer
8.637
274773LINCOLN ;4U
Solar/Wind Harmer
2.429
274774LINCOLN ;5U
Solar/Wind Harmer
2.429
991197J1626
External Queue
21.60757827758789
991267J1714
External Queue
14.405052185058594
991192J1610 G
External Queue
6.5262579917907715
990353J1289
External Queue
6.739100933074951
991037J1464 G
External Queue
40.73297882080078
990272J1263 G
External Queue
56.045440673828125
990272J1263 G
External Queue
32.15581512451172
991082J1475 G
External Queue
40.82402801513672
NYPJM->LTFIMP_NY
CLTF
0.369
WECLTFEXP_WEC->PJM
CLTF
2.431
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.537
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.934
MECLTFEXP_MEC->PJM
CLTF
13.451
SIGELTFEXP_SIGE->PJM
CLTF
0.05
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.69
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.785
LAGNLTFEXP_LAGN->PJM
CLTF
11.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.379
TVALTFEXP_TVA->PJM
CLTF
4.303

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.34 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1787.63
MW Contribution:
9.99
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.44 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1740.26
MW Contribution:
9.79
Bus #Bus NameTypeMW Contribution
942481AE2-261 GEN
Solar/Wind Harmer
39.326
957381AF2-032 GEN
Solar/Wind Harmer
2.599
276785W4-005 GEN1
Solar/Wind Harmer
3.341
971993AH1-541 GEN
Solar/Wind Harmer
10.208
965091AG1-374 GEN
Solar/Wind Harmer
28.11
959611AF2-252 GEN
Solar/Wind Harmer
2.179
274878BISHOP HL;2U
Solar/Wind Harmer
2.529
276782AC1-033 GEN
Solar/Wind Harmer
2.989
274851PROVIDENC;RU
Solar/Wind Harmer
2.12
274849CRESCENT ;1U
Solar/Wind Harmer
1.376
965931AG1-462 GEN
Solar/Wind Harmer
18.668
971087AG2-675 GEN
Solar/Wind Harmer
2.724
970571AG2-364 GEN
Solar/Wind Harmer
14.005
276603SUBLETTE C
Solar/Wind Harmer
0.709
274857EASY ROAD;U1
Solar/Wind Harmer
3.208
274760LEE CO EC;1U
Adder
6.23
274767LEE CO EC;8U
Adder
6.157
276868AE1-113 GEN
Solar/Wind Harmer
6.529
274879MINONK ;1U
Solar/Wind Harmer
4.353
959091AF2-200 GEN
Solar/Wind Harmer
12.855
274855GSG-6 ;RU
Solar/Wind Harmer
2.347
274850MENDOTA H;RU
Solar/Wind Harmer
1.631
276602WESTBROOK C
Solar/Wind Harmer
1.351
276799AD1-013 GEN
Solar/Wind Harmer
1.401
946671AF1-331 GEN
Solar/Wind Harmer
0.266
274862TOP CROP ;2U
Solar/Wind Harmer
3.024
274682WAUKEGAN ;7U
Adder
10.663
943121AE2-341 GEN
Solar/Wind Harmer
8.839
274650KINCAID ;1U
50/50
4.59
274651KINCAID ;2U
50/50
4.588
276916AD2-100_GEN
Solar/Wind Harmer
28.529
276911AD2-131_GEN
Solar/Wind Harmer
5.766
276615X2-022 GEN
Solar/Wind Harmer
2.284
276838X2-022 GEN2
Solar/Wind Harmer
0.271
274880W4-005 GEN4
Solar/Wind Harmer
3.341
276174W4-005 GEN2
Solar/Wind Harmer
3.341
960611AF2-352 GEN
Solar/Wind Harmer
2.179
942111AE2-223 GEN
Solar/Wind Harmer
7.133
276645AC1-214 GEN1
Solar/Wind Harmer
0.997
276158O29GEN2
Solar/Wind Harmer
3.52
276157O29GEN1
Solar/Wind Harmer
2.676
276872AE1-163_GEN1
Solar/Wind Harmer
4.506
276876AE1-163_GEN2
Solar/Wind Harmer
4.506
274764LEE CO EC;5U
Adder
6.245
274765LEE CO EC;6U
Adder
6.245
274762LEE CO EC;3U
Adder
6.23
274763LEE CO EC;4U
Adder
6.172
938861AE1-114 GEN
Solar/Wind Harmer
5.451
972235AH1-702 GEN1
Adder
1.627
965911AG1-460 GEN
Solar/Wind Harmer
1.835
276621W2-048 GEN
Solar/Wind Harmer
7.274
276686W4-005 GEN3
Solar/Wind Harmer
3.341
276655WTG1_EQ
Solar/Wind Harmer
7.594
276656WTG2_EQ
Solar/Wind Harmer
1.005
939741AE1-205 GEN
Solar/Wind Harmer
17.401
274848CAMPGROVE;RU
Solar/Wind Harmer
4.938
276646AC1-214 GEN2
Solar/Wind Harmer
0.997
276708O09 GEN2
Solar/Wind Harmer
2.513
970569AG2-363 GEN
Solar/Wind Harmer
21.007
939401AE1-172 GEN
Solar/Wind Harmer
9.629
274858EASY ROAD;U2
Solar/Wind Harmer
3.208
274761LEE CO EC;2U
Adder
6.23
274766LEE CO EC;7U
Adder
6.157
971997AH1-543 GEN
Solar/Wind Harmer
10.508
970819AG2-516 GEN
Solar/Wind Harmer
7.786
276882AE2-255 GEN
Solar/Wind Harmer
2.177
957471AF2-041 GEN
Solar/Wind Harmer
19.283
959081AF2-199 GEN
Solar/Wind Harmer
6.428
971067AG2-660 GEN
Solar/Wind Harmer
1.495
274822ROCKFORD ;11
Adder
12.583
276805AD2-038 GEN
Solar/Wind Harmer
3.223
274872LEEDK;1U
Solar/Wind Harmer
5.099
962781AG1-127 GEN
Solar/Wind Harmer
5.87
276694AA1-018 GEN2
Solar/Wind Harmer
3.773
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
274861TOP CROP ;1U
Solar/Wind Harmer
3.622
274828WAUKEGAN ;BP
Adder
6.573
274682WAUKEGAN ;7U
Adder
10.663
274745AC1-111 GEN9
Adder
3.283
274871GR RIDGE ;2U
Solar/Wind Harmer
4.504
274847GR RIDGE ;BU
Solar/Wind Harmer
2.961
941551AE2-152 GEN
Solar/Wind Harmer
2.622
274732ELWOOD EC;7P
Adder
9.212
274674JOLIET 9 ;6U
Adder
8.594
274676JOLIET 29;8U
Adder
16.816
274802UNIV PARK;5U
Adder
2.928
274812UNIV PK N;8U
Adder
2.284
274723RIVER EC ;12
Adder
7.868
972207SS24-0001
Solar/Wind Harmer
8.638
274773LINCOLN ;4U
Solar/Wind Harmer
2.429
274774LINCOLN ;5U
Solar/Wind Harmer
2.429
944221AF1-090 GEN
Solar/Wind Harmer
16.473
276763AC1-053 GEN1
Solar/Wind Harmer
4.419
276764AC1-053 GEN2
Solar/Wind Harmer
4.419
276668AB2-070 GEN1
Solar/Wind Harmer
2.425
276848AB2-070 GEN3
Solar/Wind Harmer
2.425
276849AB2-070 GEN2
Solar/Wind Harmer
2.425
274853TWINGROVE;U1
Solar/Wind Harmer
6.751
274854TWINGROVE;U2
Solar/Wind Harmer
6.609
276726Z2-087_GEN
Solar/Wind Harmer
6.88
959341AF2-225 GEN
Solar/Wind Harmer
13.051
970169AG2-114 GEN
Solar/Wind Harmer
7.728
274877BISHOP HL;1U
Solar/Wind Harmer
2.529
274863CRW1-WTG
Solar/Wind Harmer
4.089
274864CRW2-WTG
Solar/Wind Harmer
4.089
946321AF1-296 GEN
Solar/Wind Harmer
7.56
926823AC1-168 GEN
Solar/Wind Harmer
3.039
276741O09 GEN1
Solar/Wind Harmer
2.513
972267AH1-718 GEN
Adder
2.855
276889AE2-281 GEN
Solar/Wind Harmer
1.287
971681AH1-341 GEN
Solar/Wind Harmer
9.989
274856ECOGROVE ;U1
Solar/Wind Harmer
2.202
276611AD2-172 GEN
Solar/Wind Harmer
1.671
276612AE2-035 GEN
Solar/Wind Harmer
1.671
971171AH1-044 GEN
Solar/Wind Harmer
12.855
274823ROCKFORD ;21
Adder
12.492
276861AD2-134 GEN
Solar/Wind Harmer
1.135
276863AD2-134 GEN
Solar/Wind Harmer
1.135
971675AH1-338 GEN
Solar/Wind Harmer
11.43
970073AG2-061 GEN
Solar/Wind Harmer
1.462
971411AH1-196 GEN
Solar/Wind Harmer
9.408
274744AC1-111 GEN8
Adder
3.283
274746AC1-111 G10
Adder
3.283
970833AG2-524 GEN
Solar/Wind Harmer
5.099
970833AG2-524 GEN
Solar/Wind Harmer
2.372
274731ELWOOD EC;2P
Adder
9.216
274733ELWOOD EC;3P
Adder
9.216
274735ELWOOD EC;4P
Adder
9.216
274728ELWOOD EC;5P
Adder
9.212
276893AG1-478 C
Solar/Wind Harmer
0.307
274675JOLIET 29;7U
Adder
16.816
274675JOLIET 29;7U
Adder
16.216
972227AH1-698 GEN1
Adder
1.416
972228AH1-698 GEN2
Adder
2.01
274687WILL CNTY;4U
Adder
15.103
274687WILL CNTY;4U
Adder
15.103
274800UNIV PARK;3U
Adder
3.008
274801UNIV PARK;4U
Adder
3.008
274827FISK ;RP
Adder
3.937
972037AH1-567 GEN1
Adder
0.092
274775LINCOLN ;6U
Solar/Wind Harmer
2.429
274776LINCOLN ;7U
Solar/Wind Harmer
2.429
274777LINCOLN ;8U
Solar/Wind Harmer
2.429
972236AH1-702 GEN2
Adder
1.414
276901AD2-066 C O1
Solar/Wind Harmer
2.254
971341AH1-150 GEN
Solar/Wind Harmer
12.855
971343AH1-151 GEN
Solar/Wind Harmer
12.855
958491AF2-143 GEN
Solar/Wind Harmer
9.429
960751AF2-366 GEN
Solar/Wind Harmer
1.771
962691AG1-118 GEN
Solar/Wind Harmer
18.418
274696ROCKY RD ;4P
Adder
6.826
274695ROCKY RD ;2P
Adder
6.669
274693ROCKY RD ;1P
Adder
6.603
274697ROCKY RD ;3P
Adder
1.812
958481AF2-142 GEN
Solar/Wind Harmer
8.97
274683WAUKEGAN ;8U
Adder
12.539
274683WAUKEGAN ;8U
Adder
10.57
276897AD1-100 C
Solar/Wind Harmer
26.851
276893AG1-478 C
Solar/Wind Harmer
0.245
274674JOLIET 9 ;6U
Adder
8.594
274805UNIV PK N;1U
Adder
2.289
274808UNIV PK N;4U
Adder
2.274
274770LINCOLN ;1U
Solar/Wind Harmer
2.429
274771LINCOLN ;2U
Solar/Wind Harmer
2.429
943591AF1-030 GEN
Solar/Wind Harmer
5.893
939351AE1-166 GEN
Solar/Wind Harmer
3.428
970707AG2-453 GEN
Solar/Wind Harmer
15.925
274729ELWOOD EC;1P
Adder
9.216
274730ELWOOD EC;6P
Adder
9.212
274734ELWOOD EC;8P
Adder
9.212
274736ELWOOD EC;9P
Adder
9.212
972259AH1-714 GEN
Adder
10.664
274676JOLIET 29;8U
Adder
16.216
972038AH1-567 GEN2
Adder
0.188
274826FISK ;BP
Adder
5.555
274803UNIV PARK;6U
Adder
2.928
274814UNIV PK N;0U
Adder
2.304
274807UNIV PK N;3U
Adder
2.299
274811UNIV PK N;7U
Adder
2.284
274724RIVER EC ;11
Adder
7.8
274772LINCOLN ;3U
Solar/Wind Harmer
2.429
991197J1626
External Queue
21.607580184936523
991267J1714
External Queue
14.40505313873291
991192J1610 G
External Queue
6.526251792907715
990353J1289
External Queue
6.7390947341918945
991037J1464 G
External Queue
40.732948303222656
990272J1263 G
External Queue
56.04545593261719
990272J1263 G
External Queue
32.15582275390625
991082J1475 G
External Queue
40.82403564453125
NYPJM->LTFIMP_NY
CLTF
0.369
WECLTFEXP_WEC->PJM
CLTF
2.431
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.536
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.934
MECLTFEXP_MEC->PJM
CLTF
13.451
SIGELTFEXP_SIGE->PJM
CLTF
0.05
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.69
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.785
LAGNLTFEXP_LAGN->PJM
CLTF
11.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.379
TVALTFEXP_TVA->PJM
CLTF
4.303

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3128_05EUGENE 345_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.74 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1777.86
MW Contribution:
9.3
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3128_05EUGENE 345_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.69 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1727.97
MW Contribution:
9.02
Bus #Bus NameTypeMW Contribution
942481AE2-261 GEN
Solar/Wind Harmer
45.686
957381AF2-032 GEN
Solar/Wind Harmer
3.024
276785W4-005 GEN1
Solar/Wind Harmer
4.034
971993AH1-541 GEN
Solar/Wind Harmer
12.327
965091AG1-374 GEN
Solar/Wind Harmer
32.37
959611AF2-252 GEN
Solar/Wind Harmer
2.509
274878BISHOP HL;2U
Solar/Wind Harmer
2.568
276782AC1-033 GEN
Solar/Wind Harmer
3.034
274851PROVIDENC;RU
Solar/Wind Harmer
2.161
274849CRESCENT ;1U
Solar/Wind Harmer
1.403
965931AG1-462 GEN
Solar/Wind Harmer
18.275
971087AG2-675 GEN
Solar/Wind Harmer
2.667
970571AG2-364 GEN
Solar/Wind Harmer
13.721
276603SUBLETTE C
Solar/Wind Harmer
0.666
274857EASY ROAD;U1
Solar/Wind Harmer
2.996
274760LEE CO EC;1U
Adder
5.818
274767LEE CO EC;8U
Adder
5.75
276868AE1-113 GEN
Solar/Wind Harmer
6.119
274879MINONK ;1U
Solar/Wind Harmer
4.08
959091AF2-200 GEN
Solar/Wind Harmer
11.685
274855GSG-6 ;RU
Solar/Wind Harmer
2.114
274850MENDOTA H;RU
Solar/Wind Harmer
1.47
276602WESTBROOK C
Solar/Wind Harmer
1.217
276799AD1-013 GEN
Solar/Wind Harmer
1.261
946671AF1-331 GEN
Solar/Wind Harmer
0.239
274862TOP CROP ;2U
Solar/Wind Harmer
2.749
274682WAUKEGAN ;7U
Adder
9.302
939351AE1-166 GEN
Solar/Wind Harmer
2.954
943121AE2-341 GEN
Solar/Wind Harmer
7.45
943591AF1-030 GEN
Solar/Wind Harmer
4.967
274729ELWOOD EC;1P
Adder
7.948
274730ELWOOD EC;6P
Adder
7.943
274734ELWOOD EC;8P
Adder
7.943
274736ELWOOD EC;9P
Adder
7.943
274676JOLIET 29;8U
Adder
13.712
972259AH1-714 GEN
Adder
8.799
972038AH1-567 GEN2
Adder
0.158
24386205FR-12G C
Solar/Wind Helper
0.834
970707AG2-453 GEN
Solar/Wind Harmer
10.875
274650KINCAID ;1U
50/50
5.341
274651KINCAID ;2U
50/50
5.34
276916AD2-100_GEN
Solar/Wind Harmer
32.994
276911AD2-131_GEN
Solar/Wind Harmer
6.668
276615X2-022 GEN
Solar/Wind Harmer
2.722
276838X2-022 GEN2
Solar/Wind Harmer
0.323
274880W4-005 GEN4
Solar/Wind Harmer
4.034
276174W4-005 GEN2
Solar/Wind Harmer
4.034
960611AF2-352 GEN
Solar/Wind Harmer
2.509
942111AE2-223 GEN
Solar/Wind Harmer
8.197
276645AC1-214 GEN1
Solar/Wind Harmer
1.016
276158O29GEN2
Solar/Wind Harmer
3.402
276157O29GEN1
Solar/Wind Harmer
2.586
276872AE1-163_GEN1
Solar/Wind Harmer
4.332
276876AE1-163_GEN2
Solar/Wind Harmer
4.332
274764LEE CO EC;5U
Adder
5.832
274765LEE CO EC;6U
Adder
5.832
274762LEE CO EC;3U
Adder
5.818
274763LEE CO EC;4U
Adder
5.763
938861AE1-114 GEN
Solar/Wind Harmer
5.074
276901AD2-066 C O1
Solar/Wind Harmer
2.138
972235AH1-702 GEN1
Adder
1.486
972236AH1-702 GEN2
Adder
1.292
958491AF2-143 GEN
Solar/Wind Harmer
8.783
971341AH1-150 GEN
Solar/Wind Harmer
11.685
971343AH1-151 GEN
Solar/Wind Harmer
11.685
960751AF2-366 GEN
Solar/Wind Harmer
1.562
958481AF2-142 GEN
Solar/Wind Harmer
8.139
962691AG1-118 GEN
Solar/Wind Harmer
16.181
274696ROCKY RD ;4P
Adder
5.935
274695ROCKY RD ;2P
Adder
5.798
274693ROCKY RD ;1P
Adder
5.741
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.958
274683WAUKEGAN ;8U
Adder
9.237
276897AD1-100 C
Solar/Wind Harmer
23.136
276893AG1-478 C
Solar/Wind Harmer
0.212
274674JOLIET 9 ;6U
Adder
7.356
24387305FR-4G C
Solar/Wind Helper
1.831
966841AG1-555 GEN
Solar/Wind Helper
1.558
944221AF1-090 GEN
Solar/Wind Harmer
18.792
276763AC1-053 GEN1
Solar/Wind Harmer
5.324
276764AC1-053 GEN2
Solar/Wind Harmer
5.324
276668AB2-070 GEN1
Solar/Wind Harmer
2.937
276848AB2-070 GEN3
Solar/Wind Harmer
2.937
276849AB2-070 GEN2
Solar/Wind Harmer
2.937
274853TWINGROVE;U1
Solar/Wind Harmer
7.774
274854TWINGROVE;U2
Solar/Wind Harmer
7.611
276726Z2-087_GEN
Solar/Wind Harmer
7.907
959341AF2-225 GEN
Solar/Wind Harmer
15
970169AG2-114 GEN
Solar/Wind Harmer
8.227
274877BISHOP HL;1U
Solar/Wind Harmer
2.568
274863CRW1-WTG
Solar/Wind Harmer
4.208
274864CRW2-WTG
Solar/Wind Harmer
4.208
946321AF1-296 GEN
Solar/Wind Harmer
7.371
926823AC1-168 GEN
Solar/Wind Harmer
3.018
276741O09 GEN1
Solar/Wind Harmer
2.429
972267AH1-718 GEN
Adder
2.702
276889AE2-281 GEN
Solar/Wind Harmer
1.238
971681AH1-341 GEN
Solar/Wind Harmer
9.303
274856ECOGROVE ;U1
Solar/Wind Harmer
2.028
276611AD2-172 GEN
Solar/Wind Harmer
1.538
276612AE2-035 GEN
Solar/Wind Harmer
1.538
970073AG2-061 GEN
Solar/Wind Harmer
1.362
971171AH1-044 GEN
Solar/Wind Harmer
11.685
274823ROCKFORD ;21
Adder
11.371
276861AD2-134 GEN
Solar/Wind Harmer
1.022
276863AD2-134 GEN
Solar/Wind Harmer
1.022
971675AH1-338 GEN
Solar/Wind Harmer
10.289
971411AH1-196 GEN
Solar/Wind Harmer
8.449
970833AG2-524 GEN
Solar/Wind Harmer
4.405
970833AG2-524 GEN
Solar/Wind Harmer
2.049
274744AC1-111 GEN8
Adder
2.8
274746AC1-111 G10
Adder
2.8
276893AG1-478 C
Solar/Wind Harmer
0.266
274731ELWOOD EC;2P
Adder
7.948
274733ELWOOD EC;3P
Adder
7.948
274735ELWOOD EC;4P
Adder
7.948
274728ELWOOD EC;5P
Adder
7.943
274675JOLIET 29;7U
Adder
14.219
274675JOLIET 29;7U
Adder
13.711
274687WILL CNTY;4U
Adder
12.766
274687WILL CNTY;4U
Adder
12.766
972227AH1-698 GEN1
Adder
1.192
972228AH1-698 GEN2
Adder
1.691
274800UNIV PARK;3U
Adder
2.528
274801UNIV PARK;4U
Adder
2.528
24386405FR-21G C
Solar/Wind Helper
0.683
24387005FR-3G C
Solar/Wind Helper
0.854
965911AG1-460 GEN
Solar/Wind Harmer
2.132
276621W2-048 GEN
Solar/Wind Harmer
8.668
276686W4-005 GEN3
Solar/Wind Harmer
4.034
276655WTG1_EQ
Solar/Wind Harmer
8.728
276656WTG2_EQ
Solar/Wind Harmer
1.156
939741AE1-205 GEN
Solar/Wind Harmer
20
274848CAMPGROVE;RU
Solar/Wind Harmer
5.073
276646AC1-214 GEN2
Solar/Wind Harmer
1.016
970569AG2-363 GEN
Solar/Wind Harmer
20.581
939401AE1-172 GEN
Solar/Wind Harmer
9.509
276708O09 GEN2
Solar/Wind Harmer
2.429
971997AH1-543 GEN
Solar/Wind Harmer
9.936
274858EASY ROAD;U2
Solar/Wind Harmer
2.996
274761LEE CO EC;2U
Adder
5.818
274766LEE CO EC;7U
Adder
5.75
276882AE2-255 GEN
Solar/Wind Harmer
2.04
970819AG2-516 GEN
Solar/Wind Harmer
7.14
276805AD2-038 GEN
Solar/Wind Harmer
3.003
957471AF2-041 GEN
Solar/Wind Harmer
17.527
959081AF2-199 GEN
Solar/Wind Harmer
5.842
971067AG2-660 GEN
Solar/Wind Harmer
1.359
274822ROCKFORD ;11
Adder
11.454
274872LEEDK;1U
Solar/Wind Harmer
4.516
962781AG1-127 GEN
Solar/Wind Harmer
5.177
274861TOP CROP ;1U
Solar/Wind Harmer
3.292
276694AA1-018 GEN2
Solar/Wind Harmer
3.424
276691AA1-018 GEN1
Solar/Wind Harmer
0.409
274828WAUKEGAN ;BP
Adder
5.744
274682WAUKEGAN ;7U
Adder
9.302
274871GR RIDGE ;2U
Solar/Wind Harmer
3.891
274847GR RIDGE ;BU
Solar/Wind Harmer
2.558
274745AC1-111 GEN9
Adder
2.8
941551AE2-152 GEN
Solar/Wind Harmer
2.259
274732ELWOOD EC;7P
Adder
7.943
274674JOLIET 9 ;6U
Adder
7.356
274676JOLIET 29;8U
Adder
14.22
24385905FR-11G C
Solar/Wind Helper
1.428
24386605FR-22G C
Solar/Wind Helper
0.683
991197J1626
External Queue
23.65094566345215
991267J1714
External Queue
15.767295837402344
991278J1725 G
External Queue
2.496783971786499
991192J1610 G
External Queue
8.002534866333008
990353J1289
External Queue
8.008524894714355
991037J1464 G
External Queue
49.14597702026367
990272J1263 G
External Queue
62.02096939086914
990272J1263 G
External Queue
35.58424758911133
991082J1475 G
External Queue
39.401187896728516
NYPJM->LTFIMP_NY
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
2.213
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.587
CPLELTFEXP_CPLE->PJM
CLTF
0.976
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.779
MECLTFEXP_MEC->PJM
CLTF
13.757
SIGELTFEXP_SIGE->PJM
CLTF
0.086
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.507
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.151
LAGNLTFEXP_LAGN->PJM
CLTF
12.215
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.167
TVALTFEXP_TVA->PJM
CLTF
4.823

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.29 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1754.14
MW Contribution:
9.41
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.54 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1709.18
MW Contribution:
9.21
Bus #Bus NameTypeMW Contribution
274650KINCAID ;1U
50/50
5.27
274651KINCAID ;2U
50/50
5.269
276916AD2-100_GEN
Solar/Wind Harmer
32.55
276911AD2-131_GEN
Solar/Wind Harmer
6.578
276615X2-022 GEN
Solar/Wind Harmer
2.687
276838X2-022 GEN2
Solar/Wind Harmer
0.319
274880W4-005 GEN4
Solar/Wind Harmer
3.983
276174W4-005 GEN2
Solar/Wind Harmer
3.983
960611AF2-352 GEN
Solar/Wind Harmer
2.491
942111AE2-223 GEN
Solar/Wind Harmer
8.154
276645AC1-214 GEN1
Solar/Wind Harmer
1.02
276158O29GEN2
Solar/Wind Harmer
3.427
276157O29GEN1
Solar/Wind Harmer
2.605
276872AE1-163_GEN1
Solar/Wind Harmer
4.388
276876AE1-163_GEN2
Solar/Wind Harmer
4.388
274764LEE CO EC;5U
Adder
5.897
274765LEE CO EC;6U
Adder
5.897
274762LEE CO EC;3U
Adder
5.883
274763LEE CO EC;4U
Adder
5.828
938861AE1-114 GEN
Solar/Wind Harmer
5.135
276901AD2-066 C O1
Solar/Wind Harmer
2.171
972235AH1-702 GEN1
Adder
1.508
972236AH1-702 GEN2
Adder
1.311
958491AF2-143 GEN
Solar/Wind Harmer
8.947
971341AH1-150 GEN
Solar/Wind Harmer
11.868
971343AH1-151 GEN
Solar/Wind Harmer
11.868
960751AF2-366 GEN
Solar/Wind Harmer
1.594
958481AF2-142 GEN
Solar/Wind Harmer
8.331
962691AG1-118 GEN
Solar/Wind Harmer
16.523
274696ROCKY RD ;4P
Adder
6.077
274695ROCKY RD ;2P
Adder
5.936
274693ROCKY RD ;1P
Adder
5.877
274697ROCKY RD ;3P
Adder
1.612
274683WAUKEGAN ;8U
Adder
11.22
274683WAUKEGAN ;8U
Adder
9.458
276897AD1-100 C
Solar/Wind Harmer
23.805
276893AG1-478 C
Solar/Wind Harmer
0.219
274674JOLIET 9 ;6U
Adder
7.591
965911AG1-460 GEN
Solar/Wind Harmer
2.104
276621W2-048 GEN
Solar/Wind Harmer
8.558
276686W4-005 GEN3
Solar/Wind Harmer
3.983
276655WTG1_EQ
Solar/Wind Harmer
8.681
276656WTG2_EQ
Solar/Wind Harmer
1.149
939741AE1-205 GEN
Solar/Wind Harmer
19.893
274848CAMPGROVE;RU
Solar/Wind Harmer
5.084
276646AC1-214 GEN2
Solar/Wind Harmer
1.02
970569AG2-363 GEN
Solar/Wind Harmer
20.776
939401AE1-172 GEN
Solar/Wind Harmer
9.607
276708O09 GEN2
Solar/Wind Harmer
2.447
971997AH1-543 GEN
Solar/Wind Harmer
10.072
274858EASY ROAD;U2
Solar/Wind Harmer
3.03
274761LEE CO EC;2U
Adder
5.883
274766LEE CO EC;7U
Adder
5.814
276882AE2-255 GEN
Solar/Wind Harmer
2.073
970819AG2-516 GEN
Solar/Wind Harmer
7.241
276805AD2-038 GEN
Solar/Wind Harmer
3.059
957471AF2-041 GEN
Solar/Wind Harmer
17.802
959081AF2-199 GEN
Solar/Wind Harmer
5.934
971067AG2-660 GEN
Solar/Wind Harmer
1.38
274822ROCKFORD ;11
Adder
11.631
274872LEEDK;1U
Solar/Wind Harmer
4.605
274861TOP CROP ;1U
Solar/Wind Harmer
3.369
962781AG1-127 GEN
Solar/Wind Harmer
5.283
276694AA1-018 GEN2
Solar/Wind Harmer
3.504
276691AA1-018 GEN1
Solar/Wind Harmer
0.419
274828WAUKEGAN ;BP
Adder
5.882
274682WAUKEGAN ;7U
Adder
9.528
274871GR RIDGE ;2U
Solar/Wind Harmer
3.996
274847GR RIDGE ;BU
Solar/Wind Harmer
2.628
274745AC1-111 GEN9
Adder
2.875
941551AE2-152 GEN
Solar/Wind Harmer
2.324
274732ELWOOD EC;7P
Adder
8.192
274674JOLIET 9 ;6U
Adder
7.591
274676JOLIET 29;8U
Adder
14.706
274802UNIV PARK;5U
Adder
2.562
942481AE2-261 GEN
Solar/Wind Harmer
45.077
957381AF2-032 GEN
Solar/Wind Harmer
2.984
276785W4-005 GEN1
Solar/Wind Harmer
3.983
971993AH1-541 GEN
Solar/Wind Harmer
12.17
965091AG1-374 GEN
Solar/Wind Harmer
32.138
959611AF2-252 GEN
Solar/Wind Harmer
2.491
274878BISHOP HL;2U
Solar/Wind Harmer
2.577
276782AC1-033 GEN
Solar/Wind Harmer
3.045
274851PROVIDENC;RU
Solar/Wind Harmer
2.169
274849CRESCENT ;1U
Solar/Wind Harmer
1.408
965931AG1-462 GEN
Solar/Wind Harmer
18.334
971087AG2-675 GEN
Solar/Wind Harmer
2.675
970571AG2-364 GEN
Solar/Wind Harmer
13.851
276603SUBLETTE C
Solar/Wind Harmer
0.673
274857EASY ROAD;U1
Solar/Wind Harmer
3.03
274760LEE CO EC;1U
Adder
5.883
274767LEE CO EC;8U
Adder
5.814
276868AE1-113 GEN
Solar/Wind Harmer
6.219
274879MINONK ;1U
Solar/Wind Harmer
4.146
959091AF2-200 GEN
Solar/Wind Harmer
11.868
274855GSG-6 ;RU
Solar/Wind Harmer
2.15
274850MENDOTA H;RU
Solar/Wind Harmer
1.495
276602WESTBROOK C
Solar/Wind Harmer
1.237
276799AD1-013 GEN
Solar/Wind Harmer
1.282
946671AF1-331 GEN
Solar/Wind Harmer
0.243
274862TOP CROP ;2U
Solar/Wind Harmer
2.813
274682WAUKEGAN ;7U
Adder
9.528
939351AE1-166 GEN
Solar/Wind Harmer
3.039
943121AE2-341 GEN
Solar/Wind Harmer
7.651
943591AF1-030 GEN
Solar/Wind Harmer
5.101
274729ELWOOD EC;1P
Adder
8.197
274730ELWOOD EC;6P
Adder
8.192
274734ELWOOD EC;8P
Adder
8.192
274736ELWOOD EC;9P
Adder
8.192
274676JOLIET 29;8U
Adder
14.181
972259AH1-714 GEN
Adder
9.097
972038AH1-567 GEN2
Adder
0.165
274826FISK ;BP
Adder
4.828
274803UNIV PARK;6U
Adder
2.562
970707AG2-453 GEN
Solar/Wind Harmer
11.24
944221AF1-090 GEN
Solar/Wind Harmer
18.532
276763AC1-053 GEN1
Solar/Wind Harmer
5.257
276764AC1-053 GEN2
Solar/Wind Harmer
5.257
276668AB2-070 GEN1
Solar/Wind Harmer
2.9
276848AB2-070 GEN3
Solar/Wind Harmer
2.9
276849AB2-070 GEN2
Solar/Wind Harmer
2.9
274853TWINGROVE;U1
Solar/Wind Harmer
7.718
274854TWINGROVE;U2
Solar/Wind Harmer
7.556
276726Z2-087_GEN
Solar/Wind Harmer
7.865
959341AF2-225 GEN
Solar/Wind Harmer
14.92
970169AG2-114 GEN
Solar/Wind Harmer
8.244
274877BISHOP HL;1U
Solar/Wind Harmer
2.577
274863CRW1-WTG
Solar/Wind Harmer
4.232
274864CRW2-WTG
Solar/Wind Harmer
4.232
946321AF1-296 GEN
Solar/Wind Harmer
7.401
926823AC1-168 GEN
Solar/Wind Harmer
3.042
276741O09 GEN1
Solar/Wind Harmer
2.447
972267AH1-718 GEN
Adder
2.726
276889AE2-281 GEN
Solar/Wind Harmer
1.254
971681AH1-341 GEN
Solar/Wind Harmer
9.413
274856ECOGROVE ;U1
Solar/Wind Harmer
2.056
276611AD2-172 GEN
Solar/Wind Harmer
1.559
276612AE2-035 GEN
Solar/Wind Harmer
1.559
970073AG2-061 GEN
Solar/Wind Harmer
1.387
971171AH1-044 GEN
Solar/Wind Harmer
11.868
274823ROCKFORD ;21
Adder
11.546
276861AD2-134 GEN
Solar/Wind Harmer
1.039
276863AD2-134 GEN
Solar/Wind Harmer
1.039
971675AH1-338 GEN
Solar/Wind Harmer
10.465
971411AH1-196 GEN
Solar/Wind Harmer
8.601
970833AG2-524 GEN
Solar/Wind Harmer
4.526
970833AG2-524 GEN
Solar/Wind Harmer
2.105
274744AC1-111 GEN8
Adder
2.875
274746AC1-111 G10
Adder
2.875
276893AG1-478 C
Solar/Wind Harmer
0.274
274731ELWOOD EC;2P
Adder
8.197
274733ELWOOD EC;3P
Adder
8.197
274735ELWOOD EC;4P
Adder
8.197
274728ELWOOD EC;5P
Adder
8.192
274675JOLIET 29;7U
Adder
14.706
274675JOLIET 29;7U
Adder
14.181
972227AH1-698 GEN1
Adder
1.234
274687WILL CNTY;4U
Adder
13.22
274687WILL CNTY;4U
Adder
13.22
972228AH1-698 GEN2
Adder
1.752
274800UNIV PARK;3U
Adder
2.631
274801UNIV PARK;4U
Adder
2.631
274827FISK ;RP
Adder
3.422
972037AH1-567 GEN1
Adder
0.08
991197J1626
External Queue
23.864316940307617
991267J1714
External Queue
15.909544944763184
991278J1725 G
External Queue
2.6333394050598145
991192J1610 G
External Queue
8.150732040405273
990353J1289
External Queue
8.186351776123047
991037J1464 G
External Queue
49.9865608215332
990272J1263 G
External Queue
61.87783432006836
990272J1263 G
External Queue
35.50212478637695
991082J1475 G
External Queue
40.68184280395508
NYPJM->LTFIMP_NY
CLTF
0.321
WECLTFEXP_WEC->PJM
CLTF
2.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.108
CPLELTFEXP_CPLE->PJM
CLTF
0.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.467
MECLTFEXP_MEC->PJM
CLTF
13.646
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.576
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.803
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.144
LAGNLTFEXP_LAGN->PJM
CLTF
11.685
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.705
TVALTFEXP_TVA->PJM
CLTF
4.512

Details for AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.25 %
Rating:2107.0 MVA
Rating Type:STE
MVA to Mitigate:2280.86
MW Contribution:
8.74
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:99.93 %
Rating:2107.0 MVA
Rating Type:STE
MVA to Mitigate:2105.61
MW Contribution:
7.83
Bus #Bus NameTypeMW Contribution
972227AH1-698 GEN1
50/50
4.403
274655BRAIDWOOD;2U
50/50
5.817
972228AH1-698 GEN2
50/50
6.214
274661LASCO STA;2U
50/50
7.16
274660LASCO STA;1U
50/50
9.248
274863CRW1-WTG
Solar/Wind Harmer
12.437
274864CRW2-WTG
Solar/Wind Harmer
12.437
970169AG2-114 GEN
Solar/Wind Harmer
14.807
276726Z2-087_GEN
Solar/Wind Harmer
11.587
959341AF2-225 GEN
Solar/Wind Harmer
21.981
274853TWINGROVE;U1
Solar/Wind Harmer
9.903
274854TWINGROVE;U2
Solar/Wind Harmer
9.695
960591AF2-350 GEN
Solar/Wind Harmer
12.286
970833AG2-524 GEN
Solar/Wind Harmer
9.139
970833AG2-524 GEN
Solar/Wind Harmer
4.251
276668AB2-070 GEN1
Solar/Wind Harmer
2.184
276848AB2-070 GEN3
Solar/Wind Harmer
2.184
276849AB2-070 GEN2
Solar/Wind Harmer
2.184
276763AC1-053 GEN1
Solar/Wind Harmer
3.795
276764AC1-053 GEN2
Solar/Wind Harmer
3.795
276893AG1-478 C
Solar/Wind Harmer
0.448
926823AC1-168 GEN
Solar/Wind Harmer
3.5
274877BISHOP HL;1U
Solar/Wind Harmer
2.238
944221AF1-090 GEN
Solar/Wind Harmer
7.108
274800UNIV PARK;3U
Adder
3.742
274801UNIV PARK;4U
Adder
3.742
274744AC1-111 GEN8
Adder
3.5
274746AC1-111 G10
Adder
3.5
971675AH1-338 GEN
Solar/Wind Harmer
11.004
276861AD2-134 GEN
Solar/Wind Harmer
1.091
276863AD2-134 GEN
Solar/Wind Harmer
1.091
276741O09 GEN1
Solar/Wind Harmer
2.148
971171AH1-044 GEN
Solar/Wind Harmer
11.828
972037AH1-567 GEN1
Adder
0.107
971681AH1-341 GEN
Solar/Wind Harmer
8.737
972267AH1-718 GEN
Adder
2.399
274856ECOGROVE ;U1
Solar/Wind Harmer
1.934
276611AD2-172 GEN
Solar/Wind Harmer
1.467
276612AE2-035 GEN
Solar/Wind Harmer
1.467
274823ROCKFORD ;21
Adder
11.139
971411AH1-196 GEN
Solar/Wind Harmer
8.543
946321AF1-296 GEN
Solar/Wind Harmer
5.894
276889AE2-281 GEN
Solar/Wind Harmer
0.919
274731ELWOOD EC;2P
Adder
7.163
274733ELWOOD EC;3P
Adder
7.163
274735ELWOOD EC;4P
Adder
7.163
274728ELWOOD EC;5P
Adder
7.143
276897AD1-100 C
Solar/Wind Harmer
128.737
942111AE2-223 GEN
Solar/Wind Harmer
12.013
960611AF2-352 GEN
Solar/Wind Harmer
3.197
274888KELLY CRK;1U
Solar/Wind Harmer
7.25
276776AD2-060 GEN
Solar/Wind Harmer
0.514
958011AF2-095 GEN
Solar/Wind Harmer
17.693
970941AG2-585 GEN
Solar/Wind Harmer
6.758
274880W4-005 GEN4
Solar/Wind Harmer
3.065
276174W4-005 GEN2
Solar/Wind Harmer
3.065
276615X2-022 GEN
Solar/Wind Harmer
1.772
276838X2-022 GEN2
Solar/Wind Harmer
0.21
276893AG1-478 C
Solar/Wind Harmer
0.357
276916AD2-100_GEN
Solar/Wind Harmer
15.524
276911AD2-131_GEN
Solar/Wind Harmer
3.137
276645AC1-214 GEN1
Solar/Wind Harmer
0.93
276901AD2-066 C O1
Solar/Wind Harmer
2.396
274674JOLIET 9 ;6U
Adder
9.763
962691AG1-118 GEN
Solar/Wind Harmer
18.64
960751AF2-366 GEN
Solar/Wind Harmer
1.777
276158O29GEN2
Solar/Wind Harmer
3.009
276157O29GEN1
Solar/Wind Harmer
2.288
971341AH1-150 GEN
Solar/Wind Harmer
11.828
971343AH1-151 GEN
Solar/Wind Harmer
11.828
274695ROCKY RD ;2P
Adder
6.505
274693ROCKY RD ;1P
Adder
6.441
274697ROCKY RD ;3P
Adder
1.767
274696ROCKY RD ;4P
Adder
6.656
938861AE1-114 GEN
Solar/Wind Harmer
4.745
274764LEE CO EC;5U
Adder
5.363
274765LEE CO EC;6U
Adder
5.363
274762LEE CO EC;3U
Adder
5.35
274763LEE CO EC;4U
Adder
5.3
972235AH1-702 GEN1
Adder
1.445
972236AH1-702 GEN2
Adder
1.257
274683WAUKEGAN ;8U
Adder
11.079
274683WAUKEGAN ;8U
Adder
9.339
276872AE1-163_GEN1
Solar/Wind Harmer
3.216
276876AE1-163_GEN2
Solar/Wind Harmer
3.216
274805UNIV PK N;1U
Adder
2.261
274808UNIV PK N;4U
Adder
2.246
274654BRAIDWOOD;1U
50/50
6.032
972259AH1-714 GEN
50/50
26.042
939351AE1-166 GEN
Solar/Wind Harmer
16.435
965091AG1-374 GEN
Solar/Wind Harmer
41.235
959611AF2-252 GEN
Solar/Wind Harmer
3.197
274887GEN-1.85
Solar/Wind Harmer
6.546
276772AC2-154 GEN
Solar/Wind Harmer
3.429
276843GEN-1.7
Solar/Wind Harmer
0.704
276806AD2-047 C O1
Solar/Wind Harmer
13.144
970707AG2-453 GEN
Solar/Wind Harmer
28.743
276785W4-005 GEN1
Solar/Wind Harmer
3.065
971993AH1-541 GEN
Solar/Wind Harmer
9.366
957381AF2-032 GEN
Solar/Wind Harmer
1.549
942481AE2-261 GEN
Solar/Wind Harmer
22.879
274851PROVIDENC;RU
Solar/Wind Harmer
1.978
274849CRESCENT ;1U
Solar/Wind Harmer
1.284
943121AE2-341 GEN
Solar/Wind Harmer
10.234
943591AF1-030 GEN
Solar/Wind Harmer
6.823
276782AC1-033 GEN
Solar/Wind Harmer
2.645
274878BISHOP HL;2U
Solar/Wind Harmer
2.238
972038AH1-567 GEN2
Adder
0.234
276799AD1-013 GEN
Solar/Wind Harmer
1.352
946671AF1-331 GEN
Solar/Wind Harmer
0.256
274855GSG-6 ;RU
Solar/Wind Harmer
2.256
274850MENDOTA H;RU
Solar/Wind Harmer
1.569
276602WESTBROOK C
Solar/Wind Harmer
1.299
959091AF2-200 GEN
Solar/Wind Harmer
11.828
276603SUBLETTE C
Solar/Wind Harmer
0.614
274803UNIV PARK;6U
Adder
3.398
274857EASY ROAD;U1
Solar/Wind Harmer
2.755
274760LEE CO EC;1U
Adder
5.35
274767LEE CO EC;8U
Adder
5.287
965931AG1-462 GEN
Solar/Wind Harmer
14.27
971087AG2-675 GEN
Solar/Wind Harmer
2.082
274682WAUKEGAN ;7U
Adder
9.442
970571AG2-364 GEN
Solar/Wind Harmer
10.437
276868AE1-113 GEN
Solar/Wind Harmer
5.124
274879MINONK ;1U
Solar/Wind Harmer
3.416
274814UNIV PK N;0U
Adder
2.276
274807UNIV PK N;3U
Adder
2.271
274811UNIV PK N;7U
Adder
2.256
274729ELWOOD EC;1P
Adder
7.163
274730ELWOOD EC;6P
Adder
7.143
274734ELWOOD EC;8P
Adder
7.143
274736ELWOOD EC;9P
Adder
7.143
276173Z2-081
50/50
0.056
941551AE2-152 GEN
Solar/Wind Harmer
12.569
939401AE1-172 GEN
Solar/Wind Harmer
35.575
276655WTG1_EQ
Solar/Wind Harmer
12.79
276656WTG2_EQ
Solar/Wind Harmer
1.694
939741AE1-205 GEN
Solar/Wind Harmer
29.309
274871GR RIDGE ;2U
Solar/Wind Harmer
8.755
274847GR RIDGE ;BU
Solar/Wind Harmer
5.757
276686W4-005 GEN3
Solar/Wind Harmer
3.065
276621W2-048 GEN
Solar/Wind Harmer
5.642
965911AG1-460 GEN
Solar/Wind Harmer
1.068
276646AC1-214 GEN2
Solar/Wind Harmer
0.93
274848CAMPGROVE;RU
Solar/Wind Harmer
4.284
274674JOLIET 9 ;6U
Adder
9.763
971997AH1-543 GEN
Solar/Wind Harmer
9.949
274745AC1-111 GEN9
Adder
3.5
274872LEEDK;1U
Solar/Wind Harmer
5.092
962781AG1-127 GEN
Solar/Wind Harmer
5.89
276708O09 GEN2
Solar/Wind Harmer
2.148
957471AF2-041 GEN
Solar/Wind Harmer
17.743
959081AF2-199 GEN
Solar/Wind Harmer
5.914
971067AG2-660 GEN
Solar/Wind Harmer
1.375
274802UNIV PARK;5U
Adder
3.398
274858EASY ROAD;U2
Solar/Wind Harmer
2.755
274761LEE CO EC;2U
Adder
5.35
274766LEE CO EC;7U
Adder
5.287
274822ROCKFORD ;11
Adder
11.22
970819AG2-516 GEN
Solar/Wind Harmer
6.841
274828WAUKEGAN ;BP
Adder
5.808
274682WAUKEGAN ;7U
Adder
9.442
970569AG2-363 GEN
Solar/Wind Harmer
15.655
276882AE2-255 GEN
Solar/Wind Harmer
1.708
274812UNIV PK N;8U
Adder
2.256
274732ELWOOD EC;7P
Adder
7.143
991278J1725 G
External Queue
2.4502456188201904
991192J1610 G
External Queue
4.759671211242676
991303J1755 G
External Queue
3.537081241607666
991037J1464 G
External Queue
26.341489791870117
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.091
NYPJM->LTFIMP_NY
CLTF
0.73
WECLTFEXP_WEC->PJM
CLTF
2.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.211
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.53
MECLTFEXP_MEC->PJM
CLTF
8.132
SIGELTFEXP_SIGE->PJM
CLTF
0.045
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.133
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.278
LAGNLTFEXP_LAGN->PJM
CLTF
3.702
TVALTFEXP_TVA->PJM
CLTF
1.163

Details for AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.17 %
Rating:2107.0 MVA
Rating Type:STE
MVA to Mitigate:2279.11
MW Contribution:
8.74
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:99.85 %
Rating:2107.0 MVA
Rating Type:STE
MVA to Mitigate:2103.86
MW Contribution:
7.83
Bus #Bus NameTypeMW Contribution
276897AD1-100 C
Solar/Wind Harmer
128.737
942111AE2-223 GEN
Solar/Wind Harmer
12.013
960611AF2-352 GEN
Solar/Wind Harmer
3.197
274888KELLY CRK;1U
Solar/Wind Harmer
7.25
276776AD2-060 GEN
Solar/Wind Harmer
0.514
958011AF2-095 GEN
Solar/Wind Harmer
17.693
970941AG2-585 GEN
Solar/Wind Harmer
6.758
274880W4-005 GEN4
Solar/Wind Harmer
3.065
276174W4-005 GEN2
Solar/Wind Harmer
3.065
276615X2-022 GEN
Solar/Wind Harmer
1.772
276838X2-022 GEN2
Solar/Wind Harmer
0.21
276893AG1-478 C
Solar/Wind Harmer
0.357
276916AD2-100_GEN
Solar/Wind Harmer
15.524
276911AD2-131_GEN
Solar/Wind Harmer
3.137
276645AC1-214 GEN1
Solar/Wind Harmer
0.93
276901AD2-066 C O1
Solar/Wind Harmer
2.396
274674JOLIET 9 ;6U
Adder
9.763
962691AG1-118 GEN
Solar/Wind Harmer
18.64
960751AF2-366 GEN
Solar/Wind Harmer
1.777
276158O29GEN2
Solar/Wind Harmer
3.009
276173Z2-081
50/50
0.056
941551AE2-152 GEN
Solar/Wind Harmer
12.569
939401AE1-172 GEN
Solar/Wind Harmer
35.575
276655WTG1_EQ
Solar/Wind Harmer
12.79
276656WTG2_EQ
Solar/Wind Harmer
1.694
939741AE1-205 GEN
Solar/Wind Harmer
29.309
274871GR RIDGE ;2U
Solar/Wind Harmer
8.755
274847GR RIDGE ;BU
Solar/Wind Harmer
5.757
276686W4-005 GEN3
Solar/Wind Harmer
3.065
276621W2-048 GEN
Solar/Wind Harmer
5.642
965911AG1-460 GEN
Solar/Wind Harmer
1.068
276646AC1-214 GEN2
Solar/Wind Harmer
0.93
274848CAMPGROVE;RU
Solar/Wind Harmer
4.284
274674JOLIET 9 ;6U
Adder
9.763
971997AH1-543 GEN
Solar/Wind Harmer
9.949
274745AC1-111 GEN9
Adder
3.5
274654BRAIDWOOD;1U
50/50
6.032
972259AH1-714 GEN
50/50
26.042
939351AE1-166 GEN
Solar/Wind Harmer
16.435
965091AG1-374 GEN
Solar/Wind Harmer
41.235
959611AF2-252 GEN
Solar/Wind Harmer
3.197
274887GEN-1.85
Solar/Wind Harmer
6.546
276772AC2-154 GEN
Solar/Wind Harmer
3.429
276843GEN-1.7
Solar/Wind Harmer
0.704
276806AD2-047 C O1
Solar/Wind Harmer
13.144
970707AG2-453 GEN
Solar/Wind Harmer
28.744
276785W4-005 GEN1
Solar/Wind Harmer
3.065
276157O29GEN1
Solar/Wind Harmer
2.288
971341AH1-150 GEN
Solar/Wind Harmer
11.828
971343AH1-151 GEN
Solar/Wind Harmer
11.828
274695ROCKY RD ;2P
Adder
6.505
274693ROCKY RD ;1P
Adder
6.441
274697ROCKY RD ;3P
Adder
1.767
274696ROCKY RD ;4P
Adder
6.656
938861AE1-114 GEN
Solar/Wind Harmer
4.745
274764LEE CO EC;5U
Adder
5.363
274765LEE CO EC;6U
Adder
5.363
274762LEE CO EC;3U
Adder
5.35
274763LEE CO EC;4U
Adder
5.3
972235AH1-702 GEN1
Adder
1.445
972236AH1-702 GEN2
Adder
1.257
274683WAUKEGAN ;8U
Adder
11.079
274683WAUKEGAN ;8U
Adder
9.339
276872AE1-163_GEN1
Solar/Wind Harmer
3.216
276876AE1-163_GEN2
Solar/Wind Harmer
3.216
274805UNIV PK N;1U
Adder
2.261
274808UNIV PK N;4U
Adder
2.246
274872LEEDK;1U
Solar/Wind Harmer
5.092
962781AG1-127 GEN
Solar/Wind Harmer
5.89
276708O09 GEN2
Solar/Wind Harmer
2.148
957471AF2-041 GEN
Solar/Wind Harmer
17.743
959081AF2-199 GEN
Solar/Wind Harmer
5.914
971067AG2-660 GEN
Solar/Wind Harmer
1.375
274802UNIV PARK;5U
Adder
3.398
274858EASY ROAD;U2
Solar/Wind Harmer
2.755
274761LEE CO EC;2U
Adder
5.35
274766LEE CO EC;7U
Adder
5.287
274822ROCKFORD ;11
Adder
11.22
970819AG2-516 GEN
Solar/Wind Harmer
6.841
274828WAUKEGAN ;BP
Adder
5.808
274682WAUKEGAN ;7U
Adder
9.442
970569AG2-363 GEN
Solar/Wind Harmer
15.655
276882AE2-255 GEN
Solar/Wind Harmer
1.708
274812UNIV PK N;8U
Adder
2.256
274732ELWOOD EC;7P
Adder
7.143
972227AH1-698 GEN1
50/50
4.403
274655BRAIDWOOD;2U
50/50
5.817
972228AH1-698 GEN2
50/50
6.214
274661LASCO STA;2U
50/50
7.16
274660LASCO STA;1U
50/50
9.248
274863CRW1-WTG
Solar/Wind Harmer
12.437
274864CRW2-WTG
Solar/Wind Harmer
12.437
970169AG2-114 GEN
Solar/Wind Harmer
14.807
276726Z2-087_GEN
Solar/Wind Harmer
11.587
959341AF2-225 GEN
Solar/Wind Harmer
21.981
274853TWINGROVE;U1
Solar/Wind Harmer
9.903
274854TWINGROVE;U2
Solar/Wind Harmer
9.695
960591AF2-350 GEN
Solar/Wind Harmer
12.286
970833AG2-524 GEN
Solar/Wind Harmer
9.139
970833AG2-524 GEN
Solar/Wind Harmer
4.251
276668AB2-070 GEN1
Solar/Wind Harmer
2.184
276848AB2-070 GEN3
Solar/Wind Harmer
2.184
276849AB2-070 GEN2
Solar/Wind Harmer
2.184
276763AC1-053 GEN1
Solar/Wind Harmer
3.795
276764AC1-053 GEN2
Solar/Wind Harmer
3.795
276893AG1-478 C
Solar/Wind Harmer
0.448
926823AC1-168 GEN
Solar/Wind Harmer
3.5
274877BISHOP HL;1U
Solar/Wind Harmer
2.238
944221AF1-090 GEN
Solar/Wind Harmer
7.108
274800UNIV PARK;3U
Adder
3.742
274801UNIV PARK;4U
Adder
3.742
274744AC1-111 GEN8
Adder
3.5
274746AC1-111 G10
Adder
3.5
971675AH1-338 GEN
Solar/Wind Harmer
11.004
276861AD2-134 GEN
Solar/Wind Harmer
1.091
276863AD2-134 GEN
Solar/Wind Harmer
1.091
276741O09 GEN1
Solar/Wind Harmer
2.148
971171AH1-044 GEN
Solar/Wind Harmer
11.828
972037AH1-567 GEN1
Adder
0.107
971681AH1-341 GEN
Solar/Wind Harmer
8.737
972267AH1-718 GEN
Adder
2.399
274856ECOGROVE ;U1
Solar/Wind Harmer
1.934
276611AD2-172 GEN
Solar/Wind Harmer
1.467
276612AE2-035 GEN
Solar/Wind Harmer
1.467
274823ROCKFORD ;21
Adder
11.139
971411AH1-196 GEN
Solar/Wind Harmer
8.543
946321AF1-296 GEN
Solar/Wind Harmer
5.894
276889AE2-281 GEN
Solar/Wind Harmer
0.919
274731ELWOOD EC;2P
Adder
7.163
274733ELWOOD EC;3P
Adder
7.163
274735ELWOOD EC;4P
Adder
7.163
274728ELWOOD EC;5P
Adder
7.143
971993AH1-541 GEN
Solar/Wind Harmer
9.366
957381AF2-032 GEN
Solar/Wind Harmer
1.549
942481AE2-261 GEN
Solar/Wind Harmer
22.879
274851PROVIDENC;RU
Solar/Wind Harmer
1.978
274849CRESCENT ;1U
Solar/Wind Harmer
1.284
943121AE2-341 GEN
Solar/Wind Harmer
10.234
943591AF1-030 GEN
Solar/Wind Harmer
6.823
276782AC1-033 GEN
Solar/Wind Harmer
2.645
274878BISHOP HL;2U
Solar/Wind Harmer
2.238
972038AH1-567 GEN2
Adder
0.234
276799AD1-013 GEN
Solar/Wind Harmer
1.352
946671AF1-331 GEN
Solar/Wind Harmer
0.256
274855GSG-6 ;RU
Solar/Wind Harmer
2.256
274850MENDOTA H;RU
Solar/Wind Harmer
1.569
276602WESTBROOK C
Solar/Wind Harmer
1.299
959091AF2-200 GEN
Solar/Wind Harmer
11.828
276603SUBLETTE C
Solar/Wind Harmer
0.614
274803UNIV PARK;6U
Adder
3.398
274857EASY ROAD;U1
Solar/Wind Harmer
2.755
274760LEE CO EC;1U
Adder
5.35
274767LEE CO EC;8U
Adder
5.287
965931AG1-462 GEN
Solar/Wind Harmer
14.27
971087AG2-675 GEN
Solar/Wind Harmer
2.082
274682WAUKEGAN ;7U
Adder
9.442
970571AG2-364 GEN
Solar/Wind Harmer
10.437
276868AE1-113 GEN
Solar/Wind Harmer
5.124
274879MINONK ;1U
Solar/Wind Harmer
3.416
274814UNIV PK N;0U
Adder
2.276
274807UNIV PK N;3U
Adder
2.271
274811UNIV PK N;7U
Adder
2.256
274729ELWOOD EC;1P
Adder
7.163
274730ELWOOD EC;6P
Adder
7.143
274734ELWOOD EC;8P
Adder
7.143
274736ELWOOD EC;9P
Adder
7.143
991278J1725 G
External Queue
2.4502456188201904
991192J1610 G
External Queue
4.759671211242676
991303J1755 G
External Queue
3.537081718444824
991037J1464 G
External Queue
26.341489791870117
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.091
NYPJM->LTFIMP_NY
CLTF
0.73
WECLTFEXP_WEC->PJM
CLTF
2.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.211
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.53
MECLTFEXP_MEC->PJM
CLTF
8.132
SIGELTFEXP_SIGE->PJM
CLTF
0.045
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.133
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.278
LAGNLTFEXP_LAGN->PJM
CLTF
3.702
TVALTFEXP_TVA->PJM
CLTF
1.163

Details for AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.12 %
Rating:2107.0 MVA
Rating Type:STE
MVA to Mitigate:2278.11
MW Contribution:
8.74
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:99.8 %
Rating:2107.0 MVA
Rating Type:STE
MVA to Mitigate:2102.87
MW Contribution:
7.83
Bus #Bus NameTypeMW Contribution
972227AH1-698 GEN1
50/50
4.403
274655BRAIDWOOD;2U
50/50
5.817
972228AH1-698 GEN2
50/50
6.214
274661LASCO STA;2U
50/50
7.16
274660LASCO STA;1U
50/50
9.248
274863CRW1-WTG
Solar/Wind Harmer
12.437
274864CRW2-WTG
Solar/Wind Harmer
12.437
970169AG2-114 GEN
Solar/Wind Harmer
14.807
276726Z2-087_GEN
Solar/Wind Harmer
11.587
959341AF2-225 GEN
Solar/Wind Harmer
21.981
274853TWINGROVE;U1
Solar/Wind Harmer
9.903
274854TWINGROVE;U2
Solar/Wind Harmer
9.695
960591AF2-350 GEN
Solar/Wind Harmer
12.286
970833AG2-524 GEN
Solar/Wind Harmer
9.139
970833AG2-524 GEN
Solar/Wind Harmer
4.251
276668AB2-070 GEN1
Solar/Wind Harmer
2.184
276848AB2-070 GEN3
Solar/Wind Harmer
2.184
276849AB2-070 GEN2
Solar/Wind Harmer
2.184
276763AC1-053 GEN1
Solar/Wind Harmer
3.795
276764AC1-053 GEN2
Solar/Wind Harmer
3.795
276893AG1-478 C
Solar/Wind Harmer
0.448
926823AC1-168 GEN
Solar/Wind Harmer
3.5
274877BISHOP HL;1U
Solar/Wind Harmer
2.238
944221AF1-090 GEN
Solar/Wind Harmer
7.108
274800UNIV PARK;3U
Adder
3.742
274801UNIV PARK;4U
Adder
3.742
274744AC1-111 GEN8
Adder
3.5
274746AC1-111 G10
Adder
3.5
971675AH1-338 GEN
Solar/Wind Harmer
11.004
276861AD2-134 GEN
Solar/Wind Harmer
1.091
276863AD2-134 GEN
Solar/Wind Harmer
1.091
276741O09 GEN1
Solar/Wind Harmer
2.148
276897AD1-100 C
Solar/Wind Harmer
128.737
942111AE2-223 GEN
Solar/Wind Harmer
12.013
960611AF2-352 GEN
Solar/Wind Harmer
3.197
274888KELLY CRK;1U
Solar/Wind Harmer
7.25
276776AD2-060 GEN
Solar/Wind Harmer
0.514
958011AF2-095 GEN
Solar/Wind Harmer
17.693
970941AG2-585 GEN
Solar/Wind Harmer
6.758
274880W4-005 GEN4
Solar/Wind Harmer
3.065
276174W4-005 GEN2
Solar/Wind Harmer
3.065
276615X2-022 GEN
Solar/Wind Harmer
1.772
276838X2-022 GEN2
Solar/Wind Harmer
0.21
276893AG1-478 C
Solar/Wind Harmer
0.357
276916AD2-100_GEN
Solar/Wind Harmer
15.524
276911AD2-131_GEN
Solar/Wind Harmer
3.137
276645AC1-214 GEN1
Solar/Wind Harmer
0.93
276901AD2-066 C O1
Solar/Wind Harmer
2.396
274674JOLIET 9 ;6U
Adder
9.763
962691AG1-118 GEN
Solar/Wind Harmer
18.64
960751AF2-366 GEN
Solar/Wind Harmer
1.777
276158O29GEN2
Solar/Wind Harmer
3.009
276157O29GEN1
Solar/Wind Harmer
2.288
971341AH1-150 GEN
Solar/Wind Harmer
11.828
971343AH1-151 GEN
Solar/Wind Harmer
11.828
274695ROCKY RD ;2P
Adder
6.505
274693ROCKY RD ;1P
Adder
6.441
274697ROCKY RD ;3P
Adder
1.767
274696ROCKY RD ;4P
Adder
6.656
938861AE1-114 GEN
Solar/Wind Harmer
4.745
274764LEE CO EC;5U
Adder
5.363
274765LEE CO EC;6U
Adder
5.363
274762LEE CO EC;3U
Adder
5.35
274763LEE CO EC;4U
Adder
5.3
972235AH1-702 GEN1
Adder
1.445
972236AH1-702 GEN2
Adder
1.257
274683WAUKEGAN ;8U
Adder
11.079
274683WAUKEGAN ;8U
Adder
9.339
276872AE1-163_GEN1
Solar/Wind Harmer
3.216
276876AE1-163_GEN2
Solar/Wind Harmer
3.216
274805UNIV PK N;1U
Adder
2.261
274808UNIV PK N;4U
Adder
2.246
274654BRAIDWOOD;1U
50/50
6.032
972259AH1-714 GEN
50/50
26.042
939351AE1-166 GEN
Solar/Wind Harmer
16.435
965091AG1-374 GEN
Solar/Wind Harmer
41.235
959611AF2-252 GEN
Solar/Wind Harmer
3.197
274887GEN-1.85
Solar/Wind Harmer
6.546
276772AC2-154 GEN
Solar/Wind Harmer
3.429
276843GEN-1.7
Solar/Wind Harmer
0.704
276806AD2-047 C O1
Solar/Wind Harmer
13.144
970707AG2-453 GEN
Solar/Wind Harmer
28.743
276785W4-005 GEN1
Solar/Wind Harmer
3.065
971993AH1-541 GEN
Solar/Wind Harmer
9.366
957381AF2-032 GEN
Solar/Wind Harmer
1.549
942481AE2-261 GEN
Solar/Wind Harmer
22.879
274851PROVIDENC;RU
Solar/Wind Harmer
1.978
274849CRESCENT ;1U
Solar/Wind Harmer
1.284
943121AE2-341 GEN
Solar/Wind Harmer
10.234
943591AF1-030 GEN
Solar/Wind Harmer
6.823
276782AC1-033 GEN
Solar/Wind Harmer
2.645
274878BISHOP HL;2U
Solar/Wind Harmer
2.238
972038AH1-567 GEN2
Adder
0.234
276799AD1-013 GEN
Solar/Wind Harmer
1.352
946671AF1-331 GEN
Solar/Wind Harmer
0.256
274855GSG-6 ;RU
Solar/Wind Harmer
2.256
274850MENDOTA H;RU
Solar/Wind Harmer
1.569
276602WESTBROOK C
Solar/Wind Harmer
1.299
959091AF2-200 GEN
Solar/Wind Harmer
11.828
276603SUBLETTE C
Solar/Wind Harmer
0.614
274803UNIV PARK;6U
Adder
3.398
274857EASY ROAD;U1
Solar/Wind Harmer
2.755
274760LEE CO EC;1U
Adder
5.35
274767LEE CO EC;8U
Adder
5.287
965931AG1-462 GEN
Solar/Wind Harmer
14.27
971087AG2-675 GEN
Solar/Wind Harmer
2.082
274682WAUKEGAN ;7U
Adder
9.442
970571AG2-364 GEN
Solar/Wind Harmer
10.437
276868AE1-113 GEN
Solar/Wind Harmer
5.124
274879MINONK ;1U
Solar/Wind Harmer
3.416
274814UNIV PK N;0U
Adder
2.276
274807UNIV PK N;3U
Adder
2.271
274811UNIV PK N;7U
Adder
2.256
274729ELWOOD EC;1P
Adder
7.163
274730ELWOOD EC;6P
Adder
7.143
274734ELWOOD EC;8P
Adder
7.143
274736ELWOOD EC;9P
Adder
7.143
276173Z2-081
50/50
0.056
941551AE2-152 GEN
Solar/Wind Harmer
12.569
939401AE1-172 GEN
Solar/Wind Harmer
35.575
276655WTG1_EQ
Solar/Wind Harmer
12.79
276656WTG2_EQ
Solar/Wind Harmer
1.694
939741AE1-205 GEN
Solar/Wind Harmer
29.309
274871GR RIDGE ;2U
Solar/Wind Harmer
8.755
274847GR RIDGE ;BU
Solar/Wind Harmer
5.757
276686W4-005 GEN3
Solar/Wind Harmer
3.065
276621W2-048 GEN
Solar/Wind Harmer
5.642
965911AG1-460 GEN
Solar/Wind Harmer
1.068
276646AC1-214 GEN2
Solar/Wind Harmer
0.93
274848CAMPGROVE;RU
Solar/Wind Harmer
4.284
274674JOLIET 9 ;6U
Adder
9.763
971997AH1-543 GEN
Solar/Wind Harmer
9.949
274745AC1-111 GEN9
Adder
3.5
274872LEEDK;1U
Solar/Wind Harmer
5.092
962781AG1-127 GEN
Solar/Wind Harmer
5.89
276708O09 GEN2
Solar/Wind Harmer
2.148
957471AF2-041 GEN
Solar/Wind Harmer
17.743
959081AF2-199 GEN
Solar/Wind Harmer
5.914
971067AG2-660 GEN
Solar/Wind Harmer
1.375
274802UNIV PARK;5U
Adder
3.398
274858EASY ROAD;U2
Solar/Wind Harmer
2.755
274761LEE CO EC;2U
Adder
5.35
274766LEE CO EC;7U
Adder
5.287
274822ROCKFORD ;11
Adder
11.22
970819AG2-516 GEN
Solar/Wind Harmer
6.841
274828WAUKEGAN ;BP
Adder
5.808
274682WAUKEGAN ;7U
Adder
9.442
970569AG2-363 GEN
Solar/Wind Harmer
15.655
276882AE2-255 GEN
Solar/Wind Harmer
1.708
274812UNIV PK N;8U
Adder
2.256
274732ELWOOD EC;7P
Adder
7.143
971171AH1-044 GEN
Solar/Wind Harmer
11.828
972037AH1-567 GEN1
Adder
0.107
971681AH1-341 GEN
Solar/Wind Harmer
8.737
972267AH1-718 GEN
Adder
2.399
274856ECOGROVE ;U1
Solar/Wind Harmer
1.934
276611AD2-172 GEN
Solar/Wind Harmer
1.467
276612AE2-035 GEN
Solar/Wind Harmer
1.467
274823ROCKFORD ;21
Adder
11.139
971411AH1-196 GEN
Solar/Wind Harmer
8.543
946321AF1-296 GEN
Solar/Wind Harmer
5.894
276889AE2-281 GEN
Solar/Wind Harmer
0.919
274731ELWOOD EC;2P
Adder
7.163
274733ELWOOD EC;3P
Adder
7.163
274735ELWOOD EC;4P
Adder
7.163
274728ELWOOD EC;5P
Adder
7.143
991278J1725 G
External Queue
2.4502456188201904
991192J1610 G
External Queue
4.759670257568359
991303J1755 G
External Queue
3.537081241607666
991037J1464 G
External Queue
26.341489791870117
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.091
NYPJM->LTFIMP_NY
CLTF
0.73
WECLTFEXP_WEC->PJM
CLTF
2.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.211
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.53
MECLTFEXP_MEC->PJM
CLTF
8.132
SIGELTFEXP_SIGE->PJM
CLTF
0.045
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.133
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.278
LAGNLTFEXP_LAGN->PJM
CLTF
3.702
TVALTFEXP_TVA->PJM
CLTF
1.163

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.83 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2146.19
MW Contribution:
22.77
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.81 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2145.86
MW Contribution:
22.69
Bus #Bus NameTypeMW Contribution
274761LEE CO EC;2U
50/50
28.348
274766LEE CO EC;7U
50/50
28.014
274663QUAD CITI;2U
50/50
11.742
957471AF2-041 GEN
Solar/Wind Harmer
151.684
959081AF2-199 GEN
Solar/Wind Harmer
50.561
971067AG2-660 GEN
Solar/Wind Harmer
11.758
274858EASY ROAD;U2
Solar/Wind Harmer
13.756
276708O09 GEN2
Solar/Wind Harmer
7.606
274848CAMPGROVE;RU
Solar/Wind Harmer
5.766
276646AC1-214 GEN2
Solar/Wind Harmer
1.102
274717NELSON EC;2C
50/50
3.21
274718NELSON EC;2S
50/50
2.347
274764LEE CO EC;5U
50/50
28.414
274765LEE CO EC;6U
50/50
28.414
274762LEE CO EC;3U
50/50
28.348
274763LEE CO EC;4U
50/50
28.08
971341AH1-150 GEN
Solar/Wind Harmer
101.123
971343AH1-151 GEN
Solar/Wind Harmer
101.123
276158O29GEN2
Solar/Wind Harmer
10.653
276157O29GEN1
Solar/Wind Harmer
8.099
938861AE1-114 GEN
Solar/Wind Harmer
11.384
276645AC1-214 GEN1
Solar/Wind Harmer
1.102
972267AH1-718 GEN
50/50
12.69
274701CORDOVA ;1S
50/50
2.32
274700CORDOVA ;2C
50/50
2.06
971171AH1-044 GEN
Solar/Wind Harmer
101.123
276741O09 GEN1
Solar/Wind Harmer
7.606
946321AF1-296 GEN
Solar/Wind Harmer
20.609
971681AH1-341 GEN
Solar/Wind Harmer
22.769
274877BISHOP HL;1U
Solar/Wind Harmer
3.387
276861AD2-134 GEN
Solar/Wind Harmer
1.367
276863AD2-134 GEN
Solar/Wind Harmer
1.367
971675AH1-338 GEN
Solar/Wind Harmer
13.49
274856ECOGROVE ;U1
Solar/Wind Harmer
2.43
276611AD2-172 GEN
Solar/Wind Harmer
1.843
276612AE2-035 GEN
Solar/Wind Harmer
1.843
274715NELSON EC;1C
50/50
3.21
274716NELSON EC;1S
50/50
2.347
274760LEE CO EC;1U
50/50
28.348
274767LEE CO EC;8U
50/50
28.014
274699CORDOVA ;1C
50/50
2.06
274662QUAD CITI;1U
50/50
11.679
959091AF2-200 GEN
Solar/Wind Harmer
101.123
274857EASY ROAD;U1
Solar/Wind Harmer
13.756
965931AG1-462 GEN
Solar/Wind Harmer
51.837
971087AG2-675 GEN
Solar/Wind Harmer
7.564
276603SUBLETTE C
Solar/Wind Harmer
2.1
276782AC1-033 GEN
Solar/Wind Harmer
4.005
274878BISHOP HL;2U
Solar/Wind Harmer
3.387
274851PROVIDENC;RU
Solar/Wind Harmer
2.343
274849CRESCENT ;1U
Solar/Wind Harmer
1.521
274855GSG-6 ;RU
Solar/Wind Harmer
2.827
274850MENDOTA H;RU
Solar/Wind Harmer
1.965
276602WESTBROOK C
Solar/Wind Harmer
1.627
276799AD1-013 GEN
Solar/Wind Harmer
1.612
946671AF1-331 GEN
Solar/Wind Harmer
0.305
991092J1477
External Queue
7.605059623718262
991303J1755 G
External Queue
3.903794765472412
NYPJM->LTFIMP_NY
CLTF
0.175
LGEELTFEXP_LGEE->PJM
CLTF
0.092
WECLTFEXP_WEC->PJM
CLTF
0.205
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.994
CPLELTFEXP_CPLE->PJM
CLTF
0.307
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.716
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.316
MECLTFEXP_MEC->PJM
CLTF
15.397
SIGELTFEXP_SIGE->PJM
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
4.966
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.36
TVALTFEXP_TVA->PJM
CLTF
1.503

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.53 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2140.62
MW Contribution:
22.58
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.52 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2140.42
MW Contribution:
22.5
Bus #Bus NameTypeMW Contribution
274761LEE CO EC;2U
50/50
28.288
274766LEE CO EC;7U
50/50
27.954
274663QUAD CITI;2U
50/50
11.698
957471AF2-041 GEN
Solar/Wind Harmer
151.639
959081AF2-199 GEN
Solar/Wind Harmer
50.546
971067AG2-660 GEN
Solar/Wind Harmer
11.755
274858EASY ROAD;U2
Solar/Wind Harmer
13.727
276708O09 GEN2
Solar/Wind Harmer
7.584
274848CAMPGROVE;RU
Solar/Wind Harmer
5.749
276646AC1-214 GEN2
Solar/Wind Harmer
1.099
274717NELSON EC;2C
50/50
3.203
274718NELSON EC;2S
50/50
2.342
274764LEE CO EC;5U
50/50
28.354
274765LEE CO EC;6U
50/50
28.354
274762LEE CO EC;3U
50/50
28.288
274763LEE CO EC;4U
50/50
28.021
971341AH1-150 GEN
Solar/Wind Harmer
101.092
971343AH1-151 GEN
Solar/Wind Harmer
101.092
276158O29GEN2
Solar/Wind Harmer
10.622
276157O29GEN1
Solar/Wind Harmer
8.076
938861AE1-114 GEN
Solar/Wind Harmer
11.227
276645AC1-214 GEN1
Solar/Wind Harmer
1.099
972267AH1-718 GEN
50/50
12.663
274701CORDOVA ;1S
50/50
2.311
274700CORDOVA ;2C
50/50
2.052
971171AH1-044 GEN
Solar/Wind Harmer
101.092
276741O09 GEN1
Solar/Wind Harmer
7.584
946321AF1-296 GEN
Solar/Wind Harmer
20.525
971681AH1-341 GEN
Solar/Wind Harmer
22.58
274877BISHOP HL;1U
Solar/Wind Harmer
3.377
276861AD2-134 GEN
Solar/Wind Harmer
1.355
276863AD2-134 GEN
Solar/Wind Harmer
1.355
971675AH1-338 GEN
Solar/Wind Harmer
13.375
274856ECOGROVE ;U1
Solar/Wind Harmer
2.333
276611AD2-172 GEN
Solar/Wind Harmer
1.77
276612AE2-035 GEN
Solar/Wind Harmer
1.77
274715NELSON EC;1C
50/50
3.203
274716NELSON EC;1S
50/50
2.342
274760LEE CO EC;1U
50/50
28.288
274767LEE CO EC;8U
50/50
27.954
274699CORDOVA ;1C
50/50
2.052
274662QUAD CITI;1U
50/50
11.635
959091AF2-200 GEN
Solar/Wind Harmer
101.092
274857EASY ROAD;U1
Solar/Wind Harmer
13.727
965931AG1-462 GEN
Solar/Wind Harmer
51.644
971087AG2-675 GEN
Solar/Wind Harmer
7.536
276603SUBLETTE C
Solar/Wind Harmer
2.09
276782AC1-033 GEN
Solar/Wind Harmer
3.993
274878BISHOP HL;2U
Solar/Wind Harmer
3.377
274851PROVIDENC;RU
Solar/Wind Harmer
2.336
274849CRESCENT ;1U
Solar/Wind Harmer
1.516
274855GSG-6 ;RU
Solar/Wind Harmer
2.803
274850MENDOTA H;RU
Solar/Wind Harmer
1.949
276602WESTBROOK C
Solar/Wind Harmer
1.614
276799AD1-013 GEN
Solar/Wind Harmer
1.597
946671AF1-331 GEN
Solar/Wind Harmer
0.303
991092J1477
External Queue
7.595851898193359
991303J1755 G
External Queue
3.9349989891052246
NYPJM->LTFIMP_NY
CLTF
0.174
LGEELTFEXP_LGEE->PJM
CLTF
0.09
WECLTFEXP_WEC->PJM
CLTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.774
CPLELTFEXP_CPLE->PJM
CLTF
0.302
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.669
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.056
MECLTFEXP_MEC->PJM
CLTF
15.237
SIGELTFEXP_SIGE->PJM
CLTF
0.027
LAGNLTFEXP_LAGN->PJM
CLTF
4.915
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.343
TVALTFEXP_TVA->PJM
CLTF
1.488

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P4-6_006-345-BT78___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_006-345-BT78___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.34 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2118.87
MW Contribution:
22.76
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_006-345-BT78___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.31 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2118.21
MW Contribution:
22.69
Bus #Bus NameTypeMW Contribution
274717NELSON EC;2C
50/50
2.641
274718NELSON EC;2S
50/50
1.931
274764LEE CO EC;5U
50/50
20.044
274765LEE CO EC;6U
50/50
20.044
274715NELSON EC;1C
50/50
2.641
274716NELSON EC;1S
50/50
1.931
274760LEE CO EC;1U
50/50
19.996
274767LEE CO EC;8U
50/50
19.761
274699CORDOVA ;1C
50/50
1.731
274662QUAD CITI;1U
50/50
9.824
959091AF2-200 GEN
Solar/Wind Harmer
95.425
274857EASY ROAD;U1
Solar/Wind Harmer
9.704
276603SUBLETTE C
Solar/Wind Harmer
1.857
965931AG1-462 GEN
Solar/Wind Harmer
43.57
971087AG2-675 GEN
Solar/Wind Harmer
6.358
276782AC1-033 GEN
Solar/Wind Harmer
3.325
274878BISHOP HL;2U
Solar/Wind Harmer
2.812
274855GSG-6 ;RU
Solar/Wind Harmer
2.841
274850MENDOTA H;RU
Solar/Wind Harmer
1.975
276602WESTBROOK C
Solar/Wind Harmer
1.635
276799AD1-013 GEN
Solar/Wind Harmer
1.635
946671AF1-331 GEN
Solar/Wind Harmer
0.31
274851PROVIDENC;RU
Solar/Wind Harmer
1.932
274849CRESCENT ;1U
Solar/Wind Harmer
1.254
274762LEE CO EC;3U
50/50
19.996
274763LEE CO EC;4U
50/50
19.808
971341AH1-150 GEN
Solar/Wind Harmer
95.425
971343AH1-151 GEN
Solar/Wind Harmer
95.425
276158O29GEN2
Solar/Wind Harmer
8.925
276157O29GEN1
Solar/Wind Harmer
6.786
972235AH1-702 GEN1
Adder
3.812
938861AE1-114 GEN
Solar/Wind Harmer
11.906
972236AH1-702 GEN2
Adder
1.776
276645AC1-214 GEN1
Solar/Wind Harmer
0.908
274761LEE CO EC;2U
50/50
19.996
274766LEE CO EC;7U
50/50
19.761
274663QUAD CITI;2U
50/50
9.877
957471AF2-041 GEN
Solar/Wind Harmer
143.137
959081AF2-199 GEN
Solar/Wind Harmer
47.712
971067AG2-660 GEN
Solar/Wind Harmer
11.096
274858EASY ROAD;U2
Solar/Wind Harmer
9.704
276708O09 GEN2
Solar/Wind Harmer
6.372
970819AG2-516 GEN
Solar/Wind Harmer
11.052
274822ROCKFORD ;11
Adder
15.935
274848CAMPGROVE;RU
Solar/Wind Harmer
4.777
276646AC1-214 GEN2
Solar/Wind Harmer
0.908
972267AH1-718 GEN
50/50
10.439
274701CORDOVA ;1S
50/50
1.95
274700CORDOVA ;2C
50/50
1.731
971171AH1-044 GEN
Solar/Wind Harmer
95.425
276741O09 GEN1
Solar/Wind Harmer
6.372
946321AF1-296 GEN
Solar/Wind Harmer
17.489
971681AH1-341 GEN
Solar/Wind Harmer
22.764
274856ECOGROVE ;U1
Solar/Wind Harmer
3.683
276611AD2-172 GEN
Solar/Wind Harmer
2.794
276612AE2-035 GEN
Solar/Wind Harmer
2.794
274877BISHOP HL;1U
Solar/Wind Harmer
2.812
274823ROCKFORD ;21
Adder
15.823
276861AD2-134 GEN
Solar/Wind Harmer
1.374
276863AD2-134 GEN
Solar/Wind Harmer
1.374
971675AH1-338 GEN
Solar/Wind Harmer
13.613
971411AH1-196 GEN
Solar/Wind Harmer
8.106
990727J1377 G
External Queue
4.346336364746094
991092J1477
External Queue
6.193061351776123
NYPJM->LTFIMP_NY
CLTF
0.244
WECLTFEXP_WEC->PJM
CLTF
0.872
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.785
CPLELTFEXP_CPLE->PJM
CLTF
0.136
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.805
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.966
MECLTFEXP_MEC->PJM
CLTF
14.096
SIGELTFEXP_SIGE->PJM
CLTF
0.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.15
LAGNLTFEXP_LAGN->PJM
CLTF
4.315
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.846
TVALTFEXP_TVA->PJM
CLTF
1.24

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.81 %
Rating:1334.0 MVA
Rating Type:A
MVA to Mitigate:1531.63
MW Contribution:
14.65
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.82 %
Rating:1334.0 MVA
Rating Type:A
MVA to Mitigate:1531.69
MW Contribution:
14.61
Bus #Bus NameTypeMW Contribution
274761LEE CO EC;2U
50/50
15.549
274766LEE CO EC;7U
50/50
15.365
274663QUAD CITI;2U
50/50
8.663
957471AF2-041 GEN
Solar/Wind Harmer
96.902
959081AF2-199 GEN
Solar/Wind Harmer
32.301
971067AG2-660 GEN
Solar/Wind Harmer
10.767
274858EASY ROAD;U2
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.384
970819AG2-516 GEN
Solar/Wind Harmer
6.596
274822ROCKFORD ;11
Adder
13.015
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.163
274717NELSON EC;2C
50/50
2.313
274718NELSON EC;2S
50/50
1.691
274764LEE CO EC;5U
50/50
15.585
274765LEE CO EC;6U
50/50
15.585
274762LEE CO EC;3U
50/50
15.549
274763LEE CO EC;4U
50/50
15.402
971341AH1-150 GEN
Solar/Wind Harmer
64.601
971343AH1-151 GEN
Solar/Wind Harmer
64.601
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.756
938861AE1-114 GEN
Solar/Wind Harmer
4.962
972235AH1-702 GEN1
Adder
2.073
972236AH1-702 GEN2
Adder
1.798
276645AC1-214 GEN1
Solar/Wind Harmer
0.163
972267AH1-718 GEN
50/50
9.143
274701CORDOVA ;1S
50/50
1.71
274700CORDOVA ;2C
50/50
1.519
971171AH1-044 GEN
Solar/Wind Harmer
64.601
276741O09 GEN1
Solar/Wind Harmer
0.384
946321AF1-296 GEN
Solar/Wind Harmer
5.74
971681AH1-341 GEN
Solar/Wind Harmer
14.653
274856ECOGROVE ;U1
Solar/Wind Harmer
0.152
274877BISHOP HL;1U
Solar/Wind Harmer
0.17
274823ROCKFORD ;21
Adder
12.923
276861AD2-134 GEN
Solar/Wind Harmer
0.081
276863AD2-134 GEN
Solar/Wind Harmer
0.081
971675AH1-338 GEN
Solar/Wind Harmer
1.749
274715NELSON EC;1C
50/50
2.313
274716NELSON EC;1S
50/50
1.691
274760LEE CO EC;1U
50/50
15.549
274767LEE CO EC;8U
50/50
15.365
274699CORDOVA ;1C
50/50
1.519
274662QUAD CITI;1U
50/50
8.617
959091AF2-200 GEN
Solar/Wind Harmer
64.601
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
26.66
971087AG2-675 GEN
Solar/Wind Harmer
5.576
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.17
274855GSG-6 ;RU
Solar/Wind Harmer
0.167
274850MENDOTA H;RU
Solar/Wind Harmer
0.053
946671AF1-331 GEN
Solar/Wind Harmer
0.468
991092J1477
External Queue
5.40650749206543
NYPJM->LTFIMP_NY
CLTF
0.197
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.839
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.17
CPLELTFEXP_CPLE->PJM
CLTF
0.15
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.447
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.428
MECLTFEXP_MEC->PJM
CLTF
12.437
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.077
LAGNLTFEXP_LAGN->PJM
CLTF
3.849
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.826
TVALTFEXP_TVA->PJM
CLTF
1.117

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT5-8___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT5-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.84 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2091.24
MW Contribution:
22.5
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT5-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.8 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2090.56
MW Contribution:
22.43
Bus #Bus NameTypeMW Contribution
274761LEE CO EC;2U
50/50
18.18
274766LEE CO EC;7U
50/50
17.966
274663QUAD CITI;2U
50/50
9.476
957471AF2-041 GEN
Solar/Wind Harmer
140.353
959081AF2-199 GEN
Solar/Wind Harmer
46.784
274717NELSON EC;2C
50/50
2.51
274718NELSON EC;2S
50/50
1.835
274764LEE CO EC;5U
50/50
18.223
274765LEE CO EC;6U
50/50
18.223
274762LEE CO EC;3U
50/50
18.18
274763LEE CO EC;4U
50/50
18.009
971341AH1-150 GEN
Solar/Wind Harmer
93.568
971343AH1-151 GEN
Solar/Wind Harmer
93.568
276158O29GEN2
Solar/Wind Harmer
8.524
276157O29GEN1
Solar/Wind Harmer
6.481
938861AE1-114 GEN
Solar/Wind Harmer
12.013
972235AH1-702 GEN1
Adder
3.091
972236AH1-702 GEN2
Adder
2.68
276645AC1-214 GEN1
Solar/Wind Harmer
0.866
972267AH1-718 GEN
50/50
9.922
274701CORDOVA ;1S
50/50
1.871
274700CORDOVA ;2C
50/50
1.661
971171AH1-044 GEN
Solar/Wind Harmer
93.568
276741O09 GEN1
Solar/Wind Harmer
6.086
946321AF1-296 GEN
Solar/Wind Harmer
16.814
971681AH1-341 GEN
Solar/Wind Harmer
22.497
274856ECOGROVE ;U1
Solar/Wind Harmer
3.978
276611AD2-172 GEN
Solar/Wind Harmer
3.018
276612AE2-035 GEN
Solar/Wind Harmer
3.018
274823ROCKFORD ;21
Adder
18.17
274877BISHOP HL;1U
Solar/Wind Harmer
2.685
276861AD2-134 GEN
Solar/Wind Harmer
1.339
276863AD2-134 GEN
Solar/Wind Harmer
1.339
971675AH1-338 GEN
Solar/Wind Harmer
13.275
971411AH1-196 GEN
Solar/Wind Harmer
9.746
971067AG2-660 GEN
Solar/Wind Harmer
10.88
274858EASY ROAD;U2
Solar/Wind Harmer
8.822
276708O09 GEN2
Solar/Wind Harmer
6.086
970819AG2-516 GEN
Solar/Wind Harmer
12.678
274822ROCKFORD ;11
Adder
18.301
274715NELSON EC;1C
50/50
2.51
274716NELSON EC;1S
50/50
1.835
274760LEE CO EC;1U
50/50
18.18
274767LEE CO EC;8U
50/50
17.966
274699CORDOVA ;1C
50/50
1.661
274662QUAD CITI;1U
50/50
9.426
959091AF2-200 GEN
Solar/Wind Harmer
93.568
274857EASY ROAD;U1
Solar/Wind Harmer
8.822
276603SUBLETTE C
Solar/Wind Harmer
1.794
965931AG1-462 GEN
Solar/Wind Harmer
41.789
971087AG2-675 GEN
Solar/Wind Harmer
6.098
276782AC1-033 GEN
Solar/Wind Harmer
3.175
274878BISHOP HL;2U
Solar/Wind Harmer
2.685
274855GSG-6 ;RU
Solar/Wind Harmer
2.77
274850MENDOTA H;RU
Solar/Wind Harmer
1.926
276602WESTBROOK C
Solar/Wind Harmer
1.594
276799AD1-013 GEN
Solar/Wind Harmer
1.595
946671AF1-331 GEN
Solar/Wind Harmer
0.302
274851PROVIDENC;RU
Solar/Wind Harmer
1.841
274849CRESCENT ;1U
Solar/Wind Harmer
1.195
274848CAMPGROVE;RU
Solar/Wind Harmer
4.562
276646AC1-214 GEN2
Solar/Wind Harmer
0.866
990512J1326
External Queue
4.5930256843566895
990117J1214
External Queue
15.800007820129395
990727J1377 G
External Queue
5.950633525848389
991092J1477
External Queue
5.853696346282959
990407J1304
External Queue
3.3800570964813232
NYPJM->LTFIMP_NY
CLTF
0.241
WECLTFEXP_WEC->PJM
CLTF
1.082
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.272
CPLELTFEXP_CPLE->PJM
CLTF
0.135
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.756
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.619
MECLTFEXP_MEC->PJM
CLTF
13.981
SIGELTFEXP_SIGE->PJM
CLTF
0.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.151
LAGNLTFEXP_LAGN->PJM
CLTF
4.273
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.837
TVALTFEXP_TVA->PJM
CLTF
1.224

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT7-8___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT7-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.78 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2071.79
MW Contribution:
22.51
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT7-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.74 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2071.12
MW Contribution:
22.43
Bus #Bus NameTypeMW Contribution
274717NELSON EC;2C
50/50
2.519
274718NELSON EC;2S
50/50
1.842
274764LEE CO EC;5U
50/50
18.237
274765LEE CO EC;6U
50/50
18.237
274762LEE CO EC;3U
50/50
18.194
274763LEE CO EC;4U
50/50
18.023
971341AH1-150 GEN
Solar/Wind Harmer
94.133
971343AH1-151 GEN
Solar/Wind Harmer
94.133
276158O29GEN2
Solar/Wind Harmer
8.553
276157O29GEN1
Solar/Wind Harmer
6.503
938861AE1-114 GEN
Solar/Wind Harmer
12.01
972235AH1-702 GEN1
Adder
3.07
972236AH1-702 GEN2
Adder
2.661
276645AC1-214 GEN1
Solar/Wind Harmer
0.869
972267AH1-718 GEN
50/50
9.957
274701CORDOVA ;1S
50/50
1.877
274700CORDOVA ;2C
50/50
1.667
971171AH1-044 GEN
Solar/Wind Harmer
94.133
276741O09 GEN1
Solar/Wind Harmer
6.107
946321AF1-296 GEN
Solar/Wind Harmer
16.876
971681AH1-341 GEN
Solar/Wind Harmer
22.506
274856ECOGROVE ;U1
Solar/Wind Harmer
3.96
276611AD2-172 GEN
Solar/Wind Harmer
3.004
276612AE2-035 GEN
Solar/Wind Harmer
3.004
274823ROCKFORD ;21
Adder
17.959
274877BISHOP HL;1U
Solar/Wind Harmer
2.695
276861AD2-134 GEN
Solar/Wind Harmer
1.355
276863AD2-134 GEN
Solar/Wind Harmer
1.355
971675AH1-338 GEN
Solar/Wind Harmer
13.431
971411AH1-196 GEN
Solar/Wind Harmer
9.259
274715NELSON EC;1C
50/50
2.519
274716NELSON EC;1S
50/50
1.842
274760LEE CO EC;1U
50/50
18.194
274767LEE CO EC;8U
50/50
17.98
274699CORDOVA ;1C
50/50
1.667
274662QUAD CITI;1U
50/50
9.461
959091AF2-200 GEN
Solar/Wind Harmer
94.133
274857EASY ROAD;U1
Solar/Wind Harmer
8.829
276603SUBLETTE C
Solar/Wind Harmer
1.799
965931AG1-462 GEN
Solar/Wind Harmer
41.945
971087AG2-675 GEN
Solar/Wind Harmer
6.121
276782AC1-033 GEN
Solar/Wind Harmer
3.187
274878BISHOP HL;2U
Solar/Wind Harmer
2.695
274855GSG-6 ;RU
Solar/Wind Harmer
2.801
274850MENDOTA H;RU
Solar/Wind Harmer
1.948
276602WESTBROOK C
Solar/Wind Harmer
1.613
276799AD1-013 GEN
Solar/Wind Harmer
1.614
946671AF1-331 GEN
Solar/Wind Harmer
0.306
274851PROVIDENC;RU
Solar/Wind Harmer
1.848
274849CRESCENT ;1U
Solar/Wind Harmer
1.2
274761LEE CO EC;2U
50/50
18.194
274766LEE CO EC;7U
50/50
17.98
274663QUAD CITI;2U
50/50
9.511
957471AF2-041 GEN
Solar/Wind Harmer
141.2
959081AF2-199 GEN
Solar/Wind Harmer
47.067
971067AG2-660 GEN
Solar/Wind Harmer
10.946
274858EASY ROAD;U2
Solar/Wind Harmer
8.829
276708O09 GEN2
Solar/Wind Harmer
6.107
970819AG2-516 GEN
Solar/Wind Harmer
12.589
274822ROCKFORD ;11
Adder
18.088
274848CAMPGROVE;RU
Solar/Wind Harmer
4.578
276646AC1-214 GEN2
Solar/Wind Harmer
0.869
990512J1326
External Queue
4.574029922485352
990117J1214
External Queue
15.734662055969238
990727J1377 G
External Queue
5.8897271156311035
991092J1477
External Queue
5.864866256713867
990407J1304
External Queue
3.3571062088012695
NYPJM->LTFIMP_NY
CLTF
0.241
WECLTFEXP_WEC->PJM
CLTF
1.146
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.94
CPLELTFEXP_CPLE->PJM
CLTF
0.136
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.768
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.693
MECLTFEXP_MEC->PJM
CLTF
14.053
SIGELTFEXP_SIGE->PJM
CLTF
0.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.07
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.153
LAGNLTFEXP_LAGN->PJM
CLTF
4.291
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.84
TVALTFEXP_TVA->PJM
CLTF
1.228

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P2-2_154_LV-345R__3_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_154_LV-345R__3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.01 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:1837.27
MW Contribution:
19.78
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_154_LV-345R__3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:99.98 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:1836.6
MW Contribution:
19.72
Bus #Bus NameTypeMW Contribution
274761LEE CO EC;2U
50/50
15.68
274766LEE CO EC;7U
50/50
15.495
274663QUAD CITI;2U
50/50
8.703
957471AF2-041 GEN
Solar/Wind Harmer
139.126
972267AH1-718 GEN
50/50
9.188
274701CORDOVA ;1S
50/50
1.718
274700CORDOVA ;2C
50/50
1.526
971171AH1-044 GEN
Solar/Wind Harmer
92.751
276741O09 GEN1
Solar/Wind Harmer
5.604
946321AF1-296 GEN
Solar/Wind Harmer
15.403
971681AH1-341 GEN
Solar/Wind Harmer
19.781
274856ECOGROVE ;U1
Solar/Wind Harmer
3.202
276611AD2-172 GEN
Solar/Wind Harmer
2.429
276612AE2-035 GEN
Solar/Wind Harmer
2.429
274877BISHOP HL;1U
Solar/Wind Harmer
2.478
274823ROCKFORD ;21
Adder
13.339
276861AD2-134 GEN
Solar/Wind Harmer
1.188
276863AD2-134 GEN
Solar/Wind Harmer
1.188
971675AH1-338 GEN
Solar/Wind Harmer
11.764
971411AH1-196 GEN
Solar/Wind Harmer
6.9
274715NELSON EC;1C
50/50
2.324
274716NELSON EC;1S
50/50
1.7
274760LEE CO EC;1U
50/50
15.68
274767LEE CO EC;8U
50/50
15.495
274699CORDOVA ;1C
50/50
1.526
274662QUAD CITI;1U
50/50
8.657
959091AF2-200 GEN
Solar/Wind Harmer
92.751
274857EASY ROAD;U1
Solar/Wind Harmer
7.609
276603SUBLETTE C
Solar/Wind Harmer
1.627
965931AG1-462 GEN
Solar/Wind Harmer
38.389
971087AG2-675 GEN
Solar/Wind Harmer
5.602
276782AC1-033 GEN
Solar/Wind Harmer
2.93
274878BISHOP HL;2U
Solar/Wind Harmer
2.478
274855GSG-6 ;RU
Solar/Wind Harmer
2.456
274850MENDOTA H;RU
Solar/Wind Harmer
1.708
276602WESTBROOK C
Solar/Wind Harmer
1.414
276799AD1-013 GEN
Solar/Wind Harmer
1.412
946671AF1-331 GEN
Solar/Wind Harmer
0.268
274851PROVIDENC;RU
Solar/Wind Harmer
1.703
274849CRESCENT ;1U
Solar/Wind Harmer
1.105
274717NELSON EC;2C
50/50
2.324
274718NELSON EC;2S
50/50
1.7
274764LEE CO EC;5U
50/50
15.717
274765LEE CO EC;6U
50/50
15.717
274762LEE CO EC;3U
50/50
15.68
274763LEE CO EC;4U
50/50
15.532
971341AH1-150 GEN
Solar/Wind Harmer
92.751
971343AH1-151 GEN
Solar/Wind Harmer
92.751
276158O29GEN2
Solar/Wind Harmer
7.849
276157O29GEN1
Solar/Wind Harmer
5.968
938861AE1-114 GEN
Solar/Wind Harmer
10.407
972235AH1-702 GEN1
Adder
2.119
972236AH1-702 GEN2
Adder
1.838
276645AC1-214 GEN1
Solar/Wind Harmer
0.801
959081AF2-199 GEN
Solar/Wind Harmer
46.375
971067AG2-660 GEN
Solar/Wind Harmer
10.785
274858EASY ROAD;U2
Solar/Wind Harmer
7.609
276708O09 GEN2
Solar/Wind Harmer
5.604
970819AG2-516 GEN
Solar/Wind Harmer
9.667
274822ROCKFORD ;11
Adder
13.434
274848CAMPGROVE;RU
Solar/Wind Harmer
4.211
276646AC1-214 GEN2
Solar/Wind Harmer
0.801
991092J1477
External Queue
5.443562984466553
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.006
WECLTFEXP_WEC->PJM
CLTF
0.78
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.917
CPLELTFEXP_CPLE->PJM
CLTF
0.147
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.468
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.449
MECLTFEXP_MEC->PJM
CLTF
12.472
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.083
LAGNLTFEXP_LAGN->PJM
CLTF
3.856
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.82
TVALTFEXP_TVA->PJM
CLTF
1.118

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT7-8___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT7-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.49 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1748.1
MW Contribution:
21.45
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT7-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.43 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1747.22
MW Contribution:
21.39
Bus #Bus NameTypeMW Contribution
274656BYRON ;1U
50/50
4.815
274824ROCKFORD ;12
50/50
34.364
274857EASY ROAD;U1
Solar/Wind Harmer
7.256
274760LEE CO EC;1U
Adder
14.092
274767LEE CO EC;8U
Adder
13.926
276603SUBLETTE C
Solar/Wind Harmer
1.213
965931AG1-462 GEN
Solar/Wind Harmer
21.963
971087AG2-675 GEN
Solar/Wind Harmer
3.205
274855GSG-6 ;RU
Solar/Wind Harmer
3.013
274850MENDOTA H;RU
Solar/Wind Harmer
2.095
276602WESTBROOK C
Solar/Wind Harmer
1.734
276799AD1-013 GEN
Solar/Wind Harmer
1.781
946671AF1-331 GEN
Solar/Wind Harmer
0.337
959091AF2-200 GEN
Solar/Wind Harmer
10.215
972236AH1-702 GEN2
50/50
5.054
972235AH1-702 GEN1
50/50
5.805
274764LEE CO EC;5U
Adder
14.125
274765LEE CO EC;6U
Adder
14.125
274762LEE CO EC;3U
Adder
14.092
274763LEE CO EC;4U
Adder
13.959
938861AE1-114 GEN
Solar/Wind Harmer
12.192
276158O29GEN2
Solar/Wind Harmer
4.553
276157O29GEN1
Solar/Wind Harmer
3.462
960751AF2-366 GEN
Solar/Wind Harmer
2.156
962691AG1-118 GEN
Solar/Wind Harmer
17.965
971341AH1-150 GEN
Solar/Wind Harmer
10.215
971343AH1-151 GEN
Solar/Wind Harmer
10.215
972031AH1-564 GEN
50/50
36.821
274822ROCKFORD ;11
50/50
43.963
970819AG2-516 GEN
Solar/Wind Harmer
23.288
274858EASY ROAD;U2
Solar/Wind Harmer
7.256
274761LEE CO EC;2U
Adder
14.092
274766LEE CO EC;7U
Adder
13.926
276708O09 GEN2
Solar/Wind Harmer
3.251
962781AG1-127 GEN
Solar/Wind Harmer
7.147
274872LEEDK;1U
Solar/Wind Harmer
5.695
957471AF2-041 GEN
Solar/Wind Harmer
15.322
959081AF2-199 GEN
Solar/Wind Harmer
5.107
971067AG2-660 GEN
Solar/Wind Harmer
1.188
274657BYRON ;2U
50/50
4.679
274823ROCKFORD ;21
50/50
43.646
971411AH1-196 GEN
Solar/Wind Harmer
63.756
274856ECOGROVE ;U1
Solar/Wind Harmer
6.106
276611AD2-172 GEN
Solar/Wind Harmer
4.632
276612AE2-035 GEN
Solar/Wind Harmer
4.632
971681AH1-341 GEN
Solar/Wind Harmer
21.445
972267AH1-718 GEN
Adder
4.513
276741O09 GEN1
Solar/Wind Harmer
3.251
946321AF1-296 GEN
Solar/Wind Harmer
9.257
276861AD2-134 GEN
Solar/Wind Harmer
1.457
276863AD2-134 GEN
Solar/Wind Harmer
1.457
971675AH1-338 GEN
Solar/Wind Harmer
14.608
971171AH1-044 GEN
Solar/Wind Harmer
10.215
991777J1629 G
External Queue
9.221789360046387
990512J1326
External Queue
9.45048999786377
990117J1214
External Queue
32.50968551635742
990727J1377 G
External Queue
13.989998817443848
991092J1477
External Queue
2.8669803142547607
990407J1304
External Queue
8.001517295837402
NYPJM->LTFIMP_NY
CLTF
0.245
WECLTFEXP_WEC->PJM
CLTF
0.771
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.04
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.914
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.315
MECLTFEXP_MEC->PJM
CLTF
9.276
SIGELTFEXP_SIGE->PJM
CLTF
0.002
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.142
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.401
LAGNLTFEXP_LAGN->PJM
CLTF
2.57
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.131
TVALTFEXP_TVA->PJM
CLTF
0.658

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT5-8___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT5-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.3 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1745.18
MW Contribution:
21.36
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT5-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.24 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1744.3
MW Contribution:
21.31
Bus #Bus NameTypeMW Contribution
274656BYRON ;1U
50/50
4.773
274824ROCKFORD ;12
50/50
33.97
274857EASY ROAD;U1
Solar/Wind Harmer
7.237
274760LEE CO EC;1U
Adder
14.055
274767LEE CO EC;8U
Adder
13.889
276603SUBLETTE C
Solar/Wind Harmer
1.214
965931AG1-462 GEN
Solar/Wind Harmer
22.033
971087AG2-675 GEN
Solar/Wind Harmer
3.215
274855GSG-6 ;RU
Solar/Wind Harmer
3.041
274850MENDOTA H;RU
Solar/Wind Harmer
2.114
276602WESTBROOK C
Solar/Wind Harmer
1.75
276799AD1-013 GEN
Solar/Wind Harmer
1.798
946671AF1-331 GEN
Solar/Wind Harmer
0.341
959091AF2-200 GEN
Solar/Wind Harmer
10.951
972236AH1-702 GEN2
50/50
5.01
972235AH1-702 GEN1
50/50
5.755
274764LEE CO EC;5U
Adder
14.088
274765LEE CO EC;6U
Adder
14.088
274762LEE CO EC;3U
Adder
14.055
274763LEE CO EC;4U
Adder
13.922
938861AE1-114 GEN
Solar/Wind Harmer
12.132
276158O29GEN2
Solar/Wind Harmer
4.571
276157O29GEN1
Solar/Wind Harmer
3.476
960751AF2-366 GEN
Solar/Wind Harmer
2.181
962691AG1-118 GEN
Solar/Wind Harmer
18.362
971341AH1-150 GEN
Solar/Wind Harmer
10.951
971343AH1-151 GEN
Solar/Wind Harmer
10.951
972031AH1-564 GEN
50/50
36.4
274822ROCKFORD ;11
50/50
43.459
970819AG2-516 GEN
Solar/Wind Harmer
23.055
274858EASY ROAD;U2
Solar/Wind Harmer
7.237
274761LEE CO EC;2U
Adder
14.055
274766LEE CO EC;7U
Adder
13.889
276708O09 GEN2
Solar/Wind Harmer
3.264
962781AG1-127 GEN
Solar/Wind Harmer
7.228
274872LEEDK;1U
Solar/Wind Harmer
5.774
957471AF2-041 GEN
Solar/Wind Harmer
16.426
959081AF2-199 GEN
Solar/Wind Harmer
5.475
971067AG2-660 GEN
Solar/Wind Harmer
1.273
274657BYRON ;2U
50/50
4.638
274823ROCKFORD ;21
50/50
43.146
971411AH1-196 GEN
Solar/Wind Harmer
63.057
274856ECOGROVE ;U1
Solar/Wind Harmer
6.052
276611AD2-172 GEN
Solar/Wind Harmer
4.591
276612AE2-035 GEN
Solar/Wind Harmer
4.591
971681AH1-341 GEN
Solar/Wind Harmer
21.364
972267AH1-718 GEN
Adder
4.537
276741O09 GEN1
Solar/Wind Harmer
3.264
946321AF1-296 GEN
Solar/Wind Harmer
9.281
276861AD2-134 GEN
Solar/Wind Harmer
1.47
276863AD2-134 GEN
Solar/Wind Harmer
1.47
971675AH1-338 GEN
Solar/Wind Harmer
14.744
971171AH1-044 GEN
Solar/Wind Harmer
10.951
991777J1629 G
External Queue
9.072366714477539
990512J1326
External Queue
9.348932266235352
990117J1214
External Queue
32.16032409667969
990727J1377 G
External Queue
13.844555854797363
991092J1477
External Queue
2.8871541023254395
990407J1304
External Queue
7.912186622619629
NYPJM->LTFIMP_NY
CLTF
0.244
WECLTFEXP_WEC->PJM
CLTF
0.738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.616
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.907
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.262
MECLTFEXP_MEC->PJM
CLTF
9.249
SIGELTFEXP_SIGE->PJM
CLTF
0.002
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.141
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
2.561
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.132
TVALTFEXP_TVA->PJM
CLTF
0.655

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4-6_006-345-BT78___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_006-345-BT78___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.88 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1722.95
MW Contribution:
21.21
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_006-345-BT78___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.83 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1722.08
MW Contribution:
21.16
Bus #Bus NameTypeMW Contribution
274824ROCKFORD ;12
50/50
35.423
274656BYRON ;1U
50/50
4.367
274857EASY ROAD;U1
Solar/Wind Harmer
6.657
274760LEE CO EC;1U
Adder
12.927
274767LEE CO EC;8U
Adder
12.775
276603SUBLETTE C
Solar/Wind Harmer
1.171
972236AH1-702 GEN2
50/50
5.664
972235AH1-702 GEN1
50/50
5.265
938861AE1-114 GEN
Solar/Wind Harmer
12.223
274764LEE CO EC;5U
Adder
12.958
274765LEE CO EC;6U
Adder
12.958
274762LEE CO EC;3U
Adder
12.927
274763LEE CO EC;4U
Adder
12.806
276158O29GEN2
Solar/Wind Harmer
4.296
276157O29GEN1
Solar/Wind Harmer
3.266
960751AF2-366 GEN
Solar/Wind Harmer
2.183
962691AG1-118 GEN
Solar/Wind Harmer
18.157
971341AH1-150 GEN
Solar/Wind Harmer
9.412
971343AH1-151 GEN
Solar/Wind Harmer
9.412
274822ROCKFORD ;11
50/50
45.318
972031AH1-564 GEN
50/50
37.955
970819AG2-516 GEN
Solar/Wind Harmer
24.222
274858EASY ROAD;U2
Solar/Wind Harmer
6.657
274761LEE CO EC;2U
Adder
12.927
274766LEE CO EC;7U
Adder
12.775
276708O09 GEN2
Solar/Wind Harmer
3.067
962781AG1-127 GEN
Solar/Wind Harmer
7.236
274872LEEDK;1U
Solar/Wind Harmer
5.712
957471AF2-041 GEN
Solar/Wind Harmer
14.118
959081AF2-199 GEN
Solar/Wind Harmer
4.706
971067AG2-660 GEN
Solar/Wind Harmer
1.094
274657BYRON ;2U
50/50
5.244
274823ROCKFORD ;21
50/50
44.99
971411AH1-196 GEN
Solar/Wind Harmer
64.429
274856ECOGROVE ;U1
Solar/Wind Harmer
6.268
276611AD2-172 GEN
Solar/Wind Harmer
4.755
276612AE2-035 GEN
Solar/Wind Harmer
4.755
971681AH1-341 GEN
Solar/Wind Harmer
21.212
972267AH1-718 GEN
Adder
4.202
276741O09 GEN1
Solar/Wind Harmer
3.067
946321AF1-296 GEN
Solar/Wind Harmer
8.818
276861AD2-134 GEN
Solar/Wind Harmer
1.441
276863AD2-134 GEN
Solar/Wind Harmer
1.441
971675AH1-338 GEN
Solar/Wind Harmer
14.455
971171AH1-044 GEN
Solar/Wind Harmer
9.412
965931AG1-462 GEN
Solar/Wind Harmer
20.81
971087AG2-675 GEN
Solar/Wind Harmer
3.037
274855GSG-6 ;RU
Solar/Wind Harmer
2.98
274850MENDOTA H;RU
Solar/Wind Harmer
2.072
276602WESTBROOK C
Solar/Wind Harmer
1.716
276799AD1-013 GEN
Solar/Wind Harmer
1.763
946671AF1-331 GEN
Solar/Wind Harmer
0.334
959091AF2-200 GEN
Solar/Wind Harmer
9.412
991777J1629 G
External Queue
9.970706939697266
990512J1326
External Queue
10.093079566955566
990117J1214
External Queue
34.720191955566406
990727J1377 G
External Queue
14.965534210205078
991092J1477
External Queue
2.653498649597168
990407J1304
External Queue
8.583191871643066
NYPJM->LTFIMP_NY
CLTF
0.242
WECLTFEXP_WEC->PJM
CLTF
0.882
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.876
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.042
MECLTFEXP_MEC->PJM
CLTF
9.175
SIGELTFEXP_SIGE->PJM
CLTF
0.002
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.011
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.141
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
2.534
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.126
TVALTFEXP_TVA->PJM
CLTF
0.645

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_111-45-TR81____SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-TR81____SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.15 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1601.72
MW Contribution:
19.58
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-TR81____SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1601.0
MW Contribution:
19.53
Bus #Bus NameTypeMW Contribution
972236AH1-702 GEN2
50/50
3.812
972235AH1-702 GEN1
50/50
4.371
938861AE1-114 GEN
Solar/Wind Harmer
10.922
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.176
274763LEE CO EC;4U
Adder
12.061
971341AH1-150 GEN
Solar/Wind Harmer
21.886
971343AH1-151 GEN
Solar/Wind Harmer
21.886
276158O29GEN2
Solar/Wind Harmer
4.511
276157O29GEN1
Solar/Wind Harmer
3.43
960751AF2-366 GEN
Solar/Wind Harmer
1.89
962691AG1-118 GEN
Solar/Wind Harmer
15.823
972031AH1-564 GEN
50/50
31.15
274822ROCKFORD ;11
50/50
37.189
970819AG2-516 GEN
Solar/Wind Harmer
19.552
274858EASY ROAD;U2
Solar/Wind Harmer
6.27
274761LEE CO EC;2U
Adder
12.176
274766LEE CO EC;7U
Adder
12.032
957471AF2-041 GEN
Solar/Wind Harmer
32.829
959081AF2-199 GEN
Solar/Wind Harmer
10.943
971067AG2-660 GEN
Solar/Wind Harmer
2.545
276708O09 GEN2
Solar/Wind Harmer
3.221
962781AG1-127 GEN
Solar/Wind Harmer
6.265
274872LEEDK;1U
Solar/Wind Harmer
5.086
274823ROCKFORD ;21
50/50
36.923
274657BYRON ;2U
50/50
3.529
971411AH1-196 GEN
Solar/Wind Harmer
59.992
274856ECOGROVE ;U1
Solar/Wind Harmer
5.239
276611AD2-172 GEN
Solar/Wind Harmer
3.974
276612AE2-035 GEN
Solar/Wind Harmer
3.974
971681AH1-341 GEN
Solar/Wind Harmer
19.582
972267AH1-718 GEN
Adder
4.559
971171AH1-044 GEN
Solar/Wind Harmer
21.886
276741O09 GEN1
Solar/Wind Harmer
3.221
946321AF1-296 GEN
Solar/Wind Harmer
9.048
276861AD2-134 GEN
Solar/Wind Harmer
1.334
276863AD2-134 GEN
Solar/Wind Harmer
1.334
971675AH1-338 GEN
Solar/Wind Harmer
13.364
274824ROCKFORD ;12
50/50
29.069
274656BYRON ;1U
50/50
3.625
274857EASY ROAD;U1
Solar/Wind Harmer
6.27
274760LEE CO EC;1U
Adder
12.176
274767LEE CO EC;8U
Adder
12.032
276603SUBLETTE C
Solar/Wind Harmer
1.156
959091AF2-200 GEN
Solar/Wind Harmer
21.886
965931AG1-462 GEN
Solar/Wind Harmer
21.652
971087AG2-675 GEN
Solar/Wind Harmer
3.159
274855GSG-6 ;RU
Solar/Wind Harmer
2.759
274850MENDOTA H;RU
Solar/Wind Harmer
1.918
276602WESTBROOK C
Solar/Wind Harmer
1.588
276799AD1-013 GEN
Solar/Wind Harmer
1.628
946671AF1-331 GEN
Solar/Wind Harmer
0.308
990512J1326
External Queue
7.592830657958984
990117J1214
External Queue
26.119335174560547
990727J1377 G
External Queue
11.233358383178711
991092J1477
External Queue
2.9201087951660156
990407J1304
External Queue
6.3769121170043945
NYPJM->LTFIMP_NY
CLTF
0.202
WECLTFEXP_WEC->PJM
CLTF
0.48
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.735
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.923
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.92
MECLTFEXP_MEC->PJM
CLTF
8.563
SIGELTFEXP_SIGE->PJM
CLTF
0.005
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.105
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.288
LAGNLTFEXP_LAGN->PJM
CLTF
2.444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.238
TVALTFEXP_TVA->PJM
CLTF
0.649

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_111-45-L11124__SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-L11124__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.15 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1601.72
MW Contribution:
19.58
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-L11124__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1601.0
MW Contribution:
19.53
Bus #Bus NameTypeMW Contribution
972236AH1-702 GEN2
50/50
3.812
972235AH1-702 GEN1
50/50
4.371
938861AE1-114 GEN
Solar/Wind Harmer
10.922
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.176
274763LEE CO EC;4U
Adder
12.061
971341AH1-150 GEN
Solar/Wind Harmer
21.886
971343AH1-151 GEN
Solar/Wind Harmer
21.886
276158O29GEN2
Solar/Wind Harmer
4.511
276157O29GEN1
Solar/Wind Harmer
3.43
960751AF2-366 GEN
Solar/Wind Harmer
1.89
962691AG1-118 GEN
Solar/Wind Harmer
15.823
274824ROCKFORD ;12
50/50
29.069
274656BYRON ;1U
50/50
3.625
274857EASY ROAD;U1
Solar/Wind Harmer
6.27
274760LEE CO EC;1U
Adder
12.176
274767LEE CO EC;8U
Adder
12.032
276603SUBLETTE C
Solar/Wind Harmer
1.156
959091AF2-200 GEN
Solar/Wind Harmer
21.886
965931AG1-462 GEN
Solar/Wind Harmer
21.652
971087AG2-675 GEN
Solar/Wind Harmer
3.159
274855GSG-6 ;RU
Solar/Wind Harmer
2.759
274850MENDOTA H;RU
Solar/Wind Harmer
1.918
276602WESTBROOK C
Solar/Wind Harmer
1.588
276799AD1-013 GEN
Solar/Wind Harmer
1.628
946671AF1-331 GEN
Solar/Wind Harmer
0.308
972031AH1-564 GEN
50/50
31.15
274822ROCKFORD ;11
50/50
37.189
970819AG2-516 GEN
Solar/Wind Harmer
19.552
274858EASY ROAD;U2
Solar/Wind Harmer
6.27
274761LEE CO EC;2U
Adder
12.176
274766LEE CO EC;7U
Adder
12.032
957471AF2-041 GEN
Solar/Wind Harmer
32.829
959081AF2-199 GEN
Solar/Wind Harmer
10.943
971067AG2-660 GEN
Solar/Wind Harmer
2.545
276708O09 GEN2
Solar/Wind Harmer
3.221
962781AG1-127 GEN
Solar/Wind Harmer
6.265
274872LEEDK;1U
Solar/Wind Harmer
5.086
274823ROCKFORD ;21
50/50
36.923
274657BYRON ;2U
50/50
3.529
971411AH1-196 GEN
Solar/Wind Harmer
59.992
274856ECOGROVE ;U1
Solar/Wind Harmer
5.239
276611AD2-172 GEN
Solar/Wind Harmer
3.974
276612AE2-035 GEN
Solar/Wind Harmer
3.974
971681AH1-341 GEN
Solar/Wind Harmer
19.582
972267AH1-718 GEN
Adder
4.559
971171AH1-044 GEN
Solar/Wind Harmer
21.886
276741O09 GEN1
Solar/Wind Harmer
3.221
946321AF1-296 GEN
Solar/Wind Harmer
9.048
276861AD2-134 GEN
Solar/Wind Harmer
1.334
276863AD2-134 GEN
Solar/Wind Harmer
1.334
971675AH1-338 GEN
Solar/Wind Harmer
13.364
990512J1326
External Queue
7.592830657958984
990117J1214
External Queue
26.119335174560547
990727J1377 G
External Queue
11.233358383178711
991092J1477
External Queue
2.9201087951660156
990407J1304
External Queue
6.3769121170043945
NYPJM->LTFIMP_NY
CLTF
0.202
WECLTFEXP_WEC->PJM
CLTF
0.48
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.735
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.923
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.92
MECLTFEXP_MEC->PJM
CLTF
8.563
SIGELTFEXP_SIGE->PJM
CLTF
0.005
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.105
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.288
LAGNLTFEXP_LAGN->PJM
CLTF
2.444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.238
TVALTFEXP_TVA->PJM
CLTF
0.649

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345B__1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345B__1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.15 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1601.72
MW Contribution:
19.58
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345B__1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1600.93
MW Contribution:
19.53
Bus #Bus NameTypeMW Contribution
972031AH1-564 GEN
50/50
31.15
274822ROCKFORD ;11
50/50
37.189
970819AG2-516 GEN
Solar/Wind Harmer
19.552
274858EASY ROAD;U2
Solar/Wind Harmer
6.27
274761LEE CO EC;2U
Adder
12.176
274766LEE CO EC;7U
Adder
12.032
957471AF2-041 GEN
Solar/Wind Harmer
32.829
959081AF2-199 GEN
Solar/Wind Harmer
10.943
971067AG2-660 GEN
Solar/Wind Harmer
2.545
276708O09 GEN2
Solar/Wind Harmer
3.221
962781AG1-127 GEN
Solar/Wind Harmer
6.265
274872LEEDK;1U
Solar/Wind Harmer
5.086
274823ROCKFORD ;21
50/50
36.923
274657BYRON ;2U
50/50
3.529
971411AH1-196 GEN
Solar/Wind Harmer
59.992
274856ECOGROVE ;U1
Solar/Wind Harmer
5.239
276611AD2-172 GEN
Solar/Wind Harmer
3.974
276612AE2-035 GEN
Solar/Wind Harmer
3.974
971681AH1-341 GEN
Solar/Wind Harmer
19.582
972267AH1-718 GEN
Adder
4.559
971171AH1-044 GEN
Solar/Wind Harmer
21.886
276741O09 GEN1
Solar/Wind Harmer
3.221
946321AF1-296 GEN
Solar/Wind Harmer
9.048
276861AD2-134 GEN
Solar/Wind Harmer
1.334
276863AD2-134 GEN
Solar/Wind Harmer
1.334
971675AH1-338 GEN
Solar/Wind Harmer
13.364
274824ROCKFORD ;12
50/50
29.069
274656BYRON ;1U
50/50
3.625
274857EASY ROAD;U1
Solar/Wind Harmer
6.27
274760LEE CO EC;1U
Adder
12.176
274767LEE CO EC;8U
Adder
12.032
276603SUBLETTE C
Solar/Wind Harmer
1.156
959091AF2-200 GEN
Solar/Wind Harmer
21.886
965931AG1-462 GEN
Solar/Wind Harmer
21.652
971087AG2-675 GEN
Solar/Wind Harmer
3.159
274855GSG-6 ;RU
Solar/Wind Harmer
2.759
274850MENDOTA H;RU
Solar/Wind Harmer
1.918
276602WESTBROOK C
Solar/Wind Harmer
1.588
276799AD1-013 GEN
Solar/Wind Harmer
1.628
946671AF1-331 GEN
Solar/Wind Harmer
0.308
972236AH1-702 GEN2
50/50
3.812
972235AH1-702 GEN1
50/50
4.371
938861AE1-114 GEN
Solar/Wind Harmer
10.922
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.176
274763LEE CO EC;4U
Adder
12.061
971341AH1-150 GEN
Solar/Wind Harmer
21.886
971343AH1-151 GEN
Solar/Wind Harmer
21.886
276158O29GEN2
Solar/Wind Harmer
4.511
276157O29GEN1
Solar/Wind Harmer
3.43
960751AF2-366 GEN
Solar/Wind Harmer
1.89
962691AG1-118 GEN
Solar/Wind Harmer
15.823
990512J1326
External Queue
7.592830657958984
990117J1214
External Queue
26.119335174560547
990727J1377 G
External Queue
11.233358383178711
991092J1477
External Queue
2.9201087951660156
990407J1304
External Queue
6.3769121170043945
NYPJM->LTFIMP_NY
CLTF
0.202
WECLTFEXP_WEC->PJM
CLTF
0.48
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.735
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.92
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.923
MECLTFEXP_MEC->PJM
CLTF
8.563
SIGELTFEXP_SIGE->PJM
CLTF
0.005
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.105
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.288
LAGNLTFEXP_LAGN->PJM
CLTF
2.444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.238
TVALTFEXP_TVA->PJM
CLTF
0.649

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0626__B-R_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.07 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1600.48
MW Contribution:
16.04
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1600.1
MW Contribution:
16.0
Bus #Bus NameTypeMW Contribution
274656BYRON ;1U
50/50
4.81
274824ROCKFORD ;12
50/50
34.321
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
14.08
274767LEE CO EC;8U
Adder
13.914
965931AG1-462 GEN
Solar/Wind Harmer
15.306
971087AG2-675 GEN
Solar/Wind Harmer
3.201
274855GSG-6 ;RU
Solar/Wind Harmer
0.208
274850MENDOTA H;RU
Solar/Wind Harmer
0.066
946671AF1-331 GEN
Solar/Wind Harmer
0.599
959091AF2-200 GEN
Solar/Wind Harmer
7.138
972236AH1-702 GEN2
50/50
5.049
972235AH1-702 GEN1
50/50
5.8
274764LEE CO EC;5U
Adder
14.113
274765LEE CO EC;6U
Adder
14.113
274762LEE CO EC;3U
Adder
14.08
274763LEE CO EC;4U
Adder
13.947
938861AE1-114 GEN
Solar/Wind Harmer
5.873
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.023
962691AG1-118 GEN
Solar/Wind Harmer
12.515
971341AH1-150 GEN
Solar/Wind Harmer
7.138
971343AH1-151 GEN
Solar/Wind Harmer
7.138
274657BYRON ;2U
50/50
4.675
274823ROCKFORD ;21
50/50
43.591
971411AH1-196 GEN
Solar/Wind Harmer
44.459
274856ECOGROVE ;U1
Solar/Wind Harmer
0.295
971681AH1-341 GEN
Solar/Wind Harmer
16.043
972267AH1-718 GEN
Adder
4.509
276741O09 GEN1
Solar/Wind Harmer
0.224
946321AF1-296 GEN
Solar/Wind Harmer
3.463
276861AD2-134 GEN
Solar/Wind Harmer
0.101
276863AD2-134 GEN
Solar/Wind Harmer
0.101
971675AH1-338 GEN
Solar/Wind Harmer
2.206
971171AH1-044 GEN
Solar/Wind Harmer
7.138
972031AH1-564 GEN
50/50
36.775
274822ROCKFORD ;11
50/50
43.907
970819AG2-516 GEN
Solar/Wind Harmer
16.227
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
14.08
274766LEE CO EC;7U
Adder
13.914
276708O09 GEN2
Solar/Wind Harmer
0.224
962781AG1-127 GEN
Solar/Wind Harmer
4.983
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
10.707
959081AF2-199 GEN
Solar/Wind Harmer
3.569
971067AG2-660 GEN
Solar/Wind Harmer
1.19
991777J1629 G
External Queue
9.16248893737793
990512J1326
External Queue
9.433289527893066
990117J1214
External Queue
32.45051574707031
990727J1377 G
External Queue
13.973295211791992
991092J1477
External Queue
2.8681230545043945
990407J1304
External Queue
7.987898826599121
NYPJM->LTFIMP_NY
CLTF
0.244
WECLTFEXP_WEC->PJM
CLTF
0.749
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.794
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.91
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.288
MECLTFEXP_MEC->PJM
CLTF
9.253
SIGELTFEXP_SIGE->PJM
CLTF
0.002
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.141
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
2.564
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.131
TVALTFEXP_TVA->PJM
CLTF
0.656

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.08 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1611.63
MW Contribution:
11.56
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.88 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1557.3
MW Contribution:
11.23
Bus #Bus NameTypeMW Contribution
274752CRETE EC ;2U
50/50
9.119
274753CRETE EC ;3U
50/50
9.119
274654BRAIDWOOD;1U
50/50
3.478
959351AF2-226 GEN
50/50
2.093
972231SS25-0005
Solar/Wind Harmer
16.686
972181SS23-001
Solar/Wind Harmer
10.429
274862TOP CROP ;2U
Solar/Wind Harmer
4.553
274676JOLIET 29;8U
Adder
26.611
274826FISK ;BP
Adder
9.797
972259AH1-714 GEN
Adder
17.062
274730ELWOOD EC;6P
Adder
14.69
274734ELWOOD EC;8P
Adder
14.69
274736ELWOOD EC;9P
Adder
14.69
274729ELWOOD EC;1P
Adder
14.676
970707AG2-453 GEN
Solar/Wind Harmer
24.591
274887GEN-1.85
Solar/Wind Harmer
4.658
276772AC2-154 GEN
Solar/Wind Harmer
2.44
276843GEN-1.7
Solar/Wind Harmer
0.501
276806AD2-047 C O1
Solar/Wind Harmer
9.353
274772LINCOLN ;3U
Adder
5.397
939351AE1-166 GEN
Solar/Wind Harmer
5.158
972038AH1-567 GEN2
Adder
0.312
276164X3-005 C
Solar/Wind Harmer
0.598
943121AE2-341 GEN
Solar/Wind Harmer
12.766
943591AF1-030 GEN
Solar/Wind Harmer
8.511
274682WAUKEGAN ;7U
Adder
15.223
274803UNIV PARK;6U
Adder
4.881
276868AE1-113 GEN
Solar/Wind Harmer
8.298
274879MINONK ;1U
Solar/Wind Harmer
5.532
274724RIVER EC ;11
Adder
14.382
276799AD1-013 GEN
Solar/Wind Harmer
1.777
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
2.965
274850MENDOTA H;RU
Solar/Wind Harmer
2.061
276602WESTBROOK C
Solar/Wind Harmer
1.707
959091AF2-200 GEN
Solar/Wind Harmer
15.915
970571AG2-364 GEN
Solar/Wind Harmer
15.494
274814UNIV PK N;0U
Adder
3.91
274807UNIV PK N;3U
Adder
3.901
274811UNIV PK N;7U
Adder
3.876
274857EASY ROAD;U1
Solar/Wind Harmer
3.668
274760LEE CO EC;1U
Adder
7.123
274767LEE CO EC;8U
Adder
7.039
276603SUBLETTE C
Solar/Wind Harmer
0.799
274851PROVIDENC;RU
Solar/Wind Harmer
2.053
274849CRESCENT ;1U
Solar/Wind Harmer
1.333
276782AC1-033 GEN
Solar/Wind Harmer
2.853
274878BISHOP HL;2U
Solar/Wind Harmer
2.414
965931AG1-462 GEN
Solar/Wind Harmer
17.821
971087AG2-675 GEN
Solar/Wind Harmer
2.6
965091AG1-374 GEN
Solar/Wind Harmer
18.123
959611AF2-252 GEN
Solar/Wind Harmer
1.405
276785W4-005 GEN1
Solar/Wind Harmer
1.493
971993AH1-541 GEN
Solar/Wind Harmer
4.563
965681AG1-436 GEN
Solar/Wind Harmer
89.59
965791AG1-447 GEN
Solar/Wind Harmer
45.837
274888KELLY CRK;1U
Solar/Wind Harmer
5.159
276776AD2-060 GEN
Solar/Wind Harmer
0.366
958011AF2-095 GEN
Solar/Wind Harmer
12.59
970941AG2-585 GEN
Solar/Wind Harmer
4.809
274770LINCOLN ;1U
Adder
5.397
274771LINCOLN ;2U
Adder
5.397
276897AD1-100 C
Solar/Wind Harmer
40.399
276893AG1-478 C
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
13.313
274683WAUKEGAN ;8U
Adder
17.806
274683WAUKEGAN ;8U
Adder
15.01
274696ROCKY RD ;4P
Adder
9.595
274695ROCKY RD ;2P
Adder
9.374
274693ROCKY RD ;1P
Adder
9.281
274697ROCKY RD ;3P
Adder
2.546
958481AF2-142 GEN
Solar/Wind Harmer
12.439
962691AG1-118 GEN
Solar/Wind Harmer
24.759
960751AF2-366 GEN
Solar/Wind Harmer
2.357
958491AF2-143 GEN
Solar/Wind Harmer
12.193
276901AD2-066 C O1
Solar/Wind Harmer
2.838
971341AH1-150 GEN
Solar/Wind Harmer
15.915
971343AH1-151 GEN
Solar/Wind Harmer
15.915
276872AE1-163_GEN1
Solar/Wind Harmer
5.307
276876AE1-163_GEN2
Solar/Wind Harmer
5.307
972235AH1-702 GEN1
Adder
1.991
972236AH1-702 GEN2
Adder
1.731
274805UNIV PK N;1U
Adder
3.884
274808UNIV PK N;4U
Adder
3.859
938861AE1-114 GEN
Solar/Wind Harmer
6.32
274764LEE CO EC;5U
Adder
7.139
274765LEE CO EC;6U
Adder
7.139
274762LEE CO EC;3U
Adder
7.123
274763LEE CO EC;4U
Adder
7.055
276158O29GEN2
Solar/Wind Harmer
3.708
276157O29GEN1
Solar/Wind Harmer
2.819
276645AC1-214 GEN1
Solar/Wind Harmer
0.966
942111AE2-223 GEN
Solar/Wind Harmer
5.202
960611AF2-352 GEN
Solar/Wind Harmer
1.405
274880W4-005 GEN4
Solar/Wind Harmer
1.493
276174W4-005 GEN2
Solar/Wind Harmer
1.493
276615X2-022 GEN
Solar/Wind Harmer
0.922
276838X2-022 GEN2
Solar/Wind Harmer
0.109
274751CRETE EC ;1U
50/50
9.119
274754CRETE EC ;4U
50/50
9.119
960281AF2-319 GEN
50/50
2.093
274861TOP CROP ;1U
Solar/Wind Harmer
5.453
274676JOLIET 29;8U
Adder
27.596
274732ELWOOD EC;7P
Adder
14.69
972207SS24-0001
Solar/Wind Harmer
19.188
274773LINCOLN ;4U
Adder
5.397
274774LINCOLN ;5U
Adder
5.397
941551AE2-152 GEN
Solar/Wind Harmer
3.944
274871GR RIDGE ;2U
Solar/Wind Harmer
6.673
274847GR RIDGE ;BU
Solar/Wind Harmer
4.387
274674JOLIET 9 ;6U
Adder
13.313
274745AC1-111 GEN9
Adder
4.778
274682WAUKEGAN ;7U
Adder
15.223
274828WAUKEGAN ;BP
Adder
9.334
274802UNIV PARK;5U
Adder
4.881
276694AA1-018 GEN2
Solar/Wind Harmer
5.232
276691AA1-018 GEN1
Solar/Wind Harmer
0.625
962781AG1-127 GEN
Solar/Wind Harmer
7.814
276882AE2-255 GEN
Solar/Wind Harmer
2.766
274872LEEDK;1U
Solar/Wind Harmer
6.713
276805AD2-038 GEN
Solar/Wind Harmer
4.168
274723RIVER EC ;12
Adder
14.538
971997AH1-543 GEN
Solar/Wind Harmer
12.557
957471AF2-041 GEN
Solar/Wind Harmer
23.873
959081AF2-199 GEN
Solar/Wind Harmer
7.958
971067AG2-660 GEN
Solar/Wind Harmer
1.851
274822ROCKFORD ;11
Adder
15.58
970819AG2-516 GEN
Solar/Wind Harmer
9.422
939401AE1-172 GEN
Solar/Wind Harmer
10.856
970569AG2-363 GEN
Solar/Wind Harmer
23.24
274812UNIV PK N;8U
Adder
3.876
274858EASY ROAD;U2
Solar/Wind Harmer
3.668
274761LEE CO EC;2U
Adder
7.123
274766LEE CO EC;7U
Adder
7.039
276708O09 GEN2
Solar/Wind Harmer
2.647
276646AC1-214 GEN2
Solar/Wind Harmer
0.966
274848CAMPGROVE;RU
Solar/Wind Harmer
4.562
276655WTG1_EQ
Solar/Wind Harmer
5.538
276656WTG2_EQ
Solar/Wind Harmer
0.733
939741AE1-205 GEN
Solar/Wind Harmer
12.69
276686W4-005 GEN3
Solar/Wind Harmer
1.493
276621W2-048 GEN
Solar/Wind Harmer
2.936
972227AH1-698 GEN1
50/50
2.539
274655BRAIDWOOD;2U
50/50
3.372
972228AH1-698 GEN2
50/50
3.601
274687WILL CNTY;4U
50/50
27.019
274687WILL CNTY;4U
50/50
27.019
960681AF2-359 GEN
Solar/Wind Harmer
27.08
274675JOLIET 29;7U
Adder
27.59
274675JOLIET 29;7U
Adder
26.604
274827FISK ;RP
Adder
6.943
274728ELWOOD EC;5P
Adder
14.69
274731ELWOOD EC;2P
Adder
14.676
274733ELWOOD EC;3P
Adder
14.676
274735ELWOOD EC;4P
Adder
14.676
960591AF2-350 GEN
Solar/Wind Harmer
8.743
274775LINCOLN ;6U
Adder
5.397
274776LINCOLN ;7U
Adder
5.397
274777LINCOLN ;8U
Adder
5.397
276893AG1-478 C
Solar/Wind Harmer
0.478
970833AG2-524 GEN
Solar/Wind Harmer
7.567
970833AG2-524 GEN
Solar/Wind Harmer
3.52
274800UNIV PARK;3U
Adder
4.984
274801UNIV PARK;4U
Adder
4.984
274744AC1-111 GEN8
Adder
4.778
274746AC1-111 G10
Adder
4.778
972037AH1-567 GEN1
Adder
0.153
970073AG2-061 GEN
Solar/Wind Harmer
1.89
971411AH1-196 GEN
Solar/Wind Harmer
12.146
971675AH1-338 GEN
Solar/Wind Harmer
14.463
276861AD2-134 GEN
Solar/Wind Harmer
1.434
276863AD2-134 GEN
Solar/Wind Harmer
1.434
971171AH1-044 GEN
Solar/Wind Harmer
15.915
274823ROCKFORD ;21
Adder
15.467
276889AE2-281 GEN
Solar/Wind Harmer
1.516
274856ECOGROVE ;U1
Solar/Wind Harmer
2.637
276611AD2-172 GEN
Solar/Wind Harmer
2
276612AE2-035 GEN
Solar/Wind Harmer
2
971681AH1-341 GEN
Solar/Wind Harmer
11.563
926823AC1-168 GEN
Solar/Wind Harmer
3.258
972267AH1-718 GEN
Adder
3.122
274863CRW1-WTG
Solar/Wind Harmer
4.168
274864CRW2-WTG
Solar/Wind Harmer
4.168
276741O09 GEN1
Solar/Wind Harmer
2.647
970169AG2-114 GEN
Solar/Wind Harmer
7.161
274877BISHOP HL;1U
Solar/Wind Harmer
2.414
946321AF1-296 GEN
Solar/Wind Harmer
7.373
276726Z2-087_GEN
Solar/Wind Harmer
5.017
959341AF2-225 GEN
Solar/Wind Harmer
9.518
274853TWINGROVE;U1
Solar/Wind Harmer
4.352
274854TWINGROVE;U2
Solar/Wind Harmer
4.261
276668AB2-070 GEN1
Solar/Wind Harmer
1.091
276848AB2-070 GEN3
Solar/Wind Harmer
1.091
276849AB2-070 GEN2
Solar/Wind Harmer
1.091
276763AC1-053 GEN1
Solar/Wind Harmer
1.92
276764AC1-053 GEN2
Solar/Wind Harmer
1.92
990577J1339
External Queue
10.413921356201172
991777J1629 G
External Queue
6.448946475982666
990582J1340
External Queue
10.413921356201172
990512J1326
External Queue
4.084519386291504
990117J1214
External Queue
14.050745964050293
990727J1377 G
External Queue
4.744733810424805
990762J1386
External Queue
5.9100422859191895
990407J1304
External Queue
3.1608264446258545
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.148
NYPJM->LTFIMP_NY
CLTF
0.728
WECLTFEXP_WEC->PJM
CLTF
3.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.263
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.214
MECLTFEXP_MEC->PJM
CLTF
9.415
SIGELTFEXP_SIGE->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.299
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.33
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.93
LAGNLTFEXP_LAGN->PJM
CLTF
3.083
TVALTFEXP_TVA->PJM
CLTF
0.781

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.07 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1611.62
MW Contribution:
11.56
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.88 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1557.3
MW Contribution:
11.23
Bus #Bus NameTypeMW Contribution
972227AH1-698 GEN1
50/50
2.539
274655BRAIDWOOD;2U
50/50
3.372
972228AH1-698 GEN2
50/50
3.601
274687WILL CNTY;4U
50/50
27.018
274687WILL CNTY;4U
50/50
27.018
960681AF2-359 GEN
Solar/Wind Harmer
27.08
274675JOLIET 29;7U
Adder
27.59
274675JOLIET 29;7U
Adder
26.604
274827FISK ;RP
Adder
6.943
274728ELWOOD EC;5P
Adder
14.69
274731ELWOOD EC;2P
Adder
14.676
274733ELWOOD EC;3P
Adder
14.676
274735ELWOOD EC;4P
Adder
14.676
960591AF2-350 GEN
Solar/Wind Harmer
8.743
274775LINCOLN ;6U
Adder
5.397
274776LINCOLN ;7U
Adder
5.397
274777LINCOLN ;8U
Adder
5.397
276893AG1-478 C
Solar/Wind Harmer
0.478
970833AG2-524 GEN
Solar/Wind Harmer
7.567
970833AG2-524 GEN
Solar/Wind Harmer
3.52
274800UNIV PARK;3U
Adder
4.984
274801UNIV PARK;4U
Adder
4.984
274744AC1-111 GEN8
Adder
4.778
274746AC1-111 G10
Adder
4.778
972037AH1-567 GEN1
Adder
0.153
970073AG2-061 GEN
Solar/Wind Harmer
1.89
971411AH1-196 GEN
Solar/Wind Harmer
12.146
971675AH1-338 GEN
Solar/Wind Harmer
14.462
276861AD2-134 GEN
Solar/Wind Harmer
1.434
276863AD2-134 GEN
Solar/Wind Harmer
1.434
971171AH1-044 GEN
Solar/Wind Harmer
15.915
274823ROCKFORD ;21
Adder
15.467
274752CRETE EC ;2U
50/50
9.119
274753CRETE EC ;3U
50/50
9.119
274654BRAIDWOOD;1U
50/50
3.478
959351AF2-226 GEN
50/50
2.093
972231SS25-0005
Solar/Wind Harmer
16.686
972181SS23-001
Solar/Wind Harmer
10.429
274862TOP CROP ;2U
Solar/Wind Harmer
4.553
274676JOLIET 29;8U
Adder
26.611
274826FISK ;BP
Adder
9.797
972259AH1-714 GEN
Adder
17.061
274730ELWOOD EC;6P
Adder
14.69
274734ELWOOD EC;8P
Adder
14.69
274736ELWOOD EC;9P
Adder
14.69
274729ELWOOD EC;1P
Adder
14.676
970707AG2-453 GEN
Solar/Wind Harmer
24.591
274887GEN-1.85
Solar/Wind Harmer
4.658
276772AC2-154 GEN
Solar/Wind Harmer
2.44
276843GEN-1.7
Solar/Wind Harmer
0.501
276806AD2-047 C O1
Solar/Wind Harmer
9.353
274772LINCOLN ;3U
Adder
5.397
939351AE1-166 GEN
Solar/Wind Harmer
5.158
972038AH1-567 GEN2
Adder
0.312
276164X3-005 C
Solar/Wind Harmer
0.598
943121AE2-341 GEN
Solar/Wind Harmer
12.766
943591AF1-030 GEN
Solar/Wind Harmer
8.511
274682WAUKEGAN ;7U
Adder
15.223
274803UNIV PARK;6U
Adder
4.881
276868AE1-113 GEN
Solar/Wind Harmer
8.298
274879MINONK ;1U
Solar/Wind Harmer
5.532
274724RIVER EC ;11
Adder
14.382
276799AD1-013 GEN
Solar/Wind Harmer
1.777
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
2.965
274850MENDOTA H;RU
Solar/Wind Harmer
2.061
276602WESTBROOK C
Solar/Wind Harmer
1.707
959091AF2-200 GEN
Solar/Wind Harmer
15.915
970571AG2-364 GEN
Solar/Wind Harmer
15.494
274814UNIV PK N;0U
Adder
3.91
274807UNIV PK N;3U
Adder
3.901
274811UNIV PK N;7U
Adder
3.876
274857EASY ROAD;U1
Solar/Wind Harmer
3.668
274760LEE CO EC;1U
Adder
7.122
274767LEE CO EC;8U
Adder
7.039
276603SUBLETTE C
Solar/Wind Harmer
0.799
274851PROVIDENC;RU
Solar/Wind Harmer
2.053
274849CRESCENT ;1U
Solar/Wind Harmer
1.333
276782AC1-033 GEN
Solar/Wind Harmer
2.853
274878BISHOP HL;2U
Solar/Wind Harmer
2.414
965931AG1-462 GEN
Solar/Wind Harmer
17.821
971087AG2-675 GEN
Solar/Wind Harmer
2.6
965091AG1-374 GEN
Solar/Wind Harmer
18.123
959611AF2-252 GEN
Solar/Wind Harmer
1.405
276785W4-005 GEN1
Solar/Wind Harmer
1.493
971993AH1-541 GEN
Solar/Wind Harmer
4.563
965681AG1-436 GEN
Solar/Wind Harmer
89.59
965791AG1-447 GEN
Solar/Wind Harmer
45.837
274888KELLY CRK;1U
Solar/Wind Harmer
5.159
276776AD2-060 GEN
Solar/Wind Harmer
0.366
958011AF2-095 GEN
Solar/Wind Harmer
12.59
970941AG2-585 GEN
Solar/Wind Harmer
4.809
274770LINCOLN ;1U
Adder
5.397
274771LINCOLN ;2U
Adder
5.397
276897AD1-100 C
Solar/Wind Harmer
40.399
276893AG1-478 C
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
13.313
274683WAUKEGAN ;8U
Adder
17.806
274683WAUKEGAN ;8U
Adder
15.01
274696ROCKY RD ;4P
Adder
9.595
274695ROCKY RD ;2P
Adder
9.374
274693ROCKY RD ;1P
Adder
9.281
274697ROCKY RD ;3P
Adder
2.546
958481AF2-142 GEN
Solar/Wind Harmer
12.439
962691AG1-118 GEN
Solar/Wind Harmer
24.759
960751AF2-366 GEN
Solar/Wind Harmer
2.357
958491AF2-143 GEN
Solar/Wind Harmer
12.193
276901AD2-066 C O1
Solar/Wind Harmer
2.838
971341AH1-150 GEN
Solar/Wind Harmer
15.915
971343AH1-151 GEN
Solar/Wind Harmer
15.915
276872AE1-163_GEN1
Solar/Wind Harmer
5.307
276876AE1-163_GEN2
Solar/Wind Harmer
5.307
972235AH1-702 GEN1
Adder
1.991
972236AH1-702 GEN2
Adder
1.731
274805UNIV PK N;1U
Adder
3.884
274808UNIV PK N;4U
Adder
3.859
938861AE1-114 GEN
Solar/Wind Harmer
6.32
274764LEE CO EC;5U
Adder
7.139
274765LEE CO EC;6U
Adder
7.139
274762LEE CO EC;3U
Adder
7.122
274763LEE CO EC;4U
Adder
7.055
276158O29GEN2
Solar/Wind Harmer
3.708
276157O29GEN1
Solar/Wind Harmer
2.819
276645AC1-214 GEN1
Solar/Wind Harmer
0.966
274751CRETE EC ;1U
50/50
9.119
274754CRETE EC ;4U
50/50
9.119
960281AF2-319 GEN
50/50
2.093
274861TOP CROP ;1U
Solar/Wind Harmer
5.453
274676JOLIET 29;8U
Adder
27.596
274732ELWOOD EC;7P
Adder
14.69
972207SS24-0001
Solar/Wind Harmer
19.188
274773LINCOLN ;4U
Adder
5.397
274774LINCOLN ;5U
Adder
5.397
941551AE2-152 GEN
Solar/Wind Harmer
3.944
274871GR RIDGE ;2U
Solar/Wind Harmer
6.672
274847GR RIDGE ;BU
Solar/Wind Harmer
4.387
274674JOLIET 9 ;6U
Adder
13.313
274745AC1-111 GEN9
Adder
4.778
274682WAUKEGAN ;7U
Adder
15.223
274828WAUKEGAN ;BP
Adder
9.334
274802UNIV PARK;5U
Adder
4.881
276694AA1-018 GEN2
Solar/Wind Harmer
5.232
276691AA1-018 GEN1
Solar/Wind Harmer
0.625
962781AG1-127 GEN
Solar/Wind Harmer
7.814
276882AE2-255 GEN
Solar/Wind Harmer
2.766
274872LEEDK;1U
Solar/Wind Harmer
6.713
276805AD2-038 GEN
Solar/Wind Harmer
4.168
274723RIVER EC ;12
Adder
14.538
971997AH1-543 GEN
Solar/Wind Harmer
12.557
957471AF2-041 GEN
Solar/Wind Harmer
23.873
959081AF2-199 GEN
Solar/Wind Harmer
7.958
971067AG2-660 GEN
Solar/Wind Harmer
1.851
274822ROCKFORD ;11
Adder
15.58
970819AG2-516 GEN
Solar/Wind Harmer
9.422
939401AE1-172 GEN
Solar/Wind Harmer
10.856
970569AG2-363 GEN
Solar/Wind Harmer
23.24
274812UNIV PK N;8U
Adder
3.876
274858EASY ROAD;U2
Solar/Wind Harmer
3.668
274761LEE CO EC;2U
Adder
7.122
274766LEE CO EC;7U
Adder
7.039
276708O09 GEN2
Solar/Wind Harmer
2.647
276646AC1-214 GEN2
Solar/Wind Harmer
0.966
274848CAMPGROVE;RU
Solar/Wind Harmer
4.562
276655WTG1_EQ
Solar/Wind Harmer
5.538
276656WTG2_EQ
Solar/Wind Harmer
0.733
939741AE1-205 GEN
Solar/Wind Harmer
12.69
276686W4-005 GEN3
Solar/Wind Harmer
1.493
276621W2-048 GEN
Solar/Wind Harmer
2.936
942111AE2-223 GEN
Solar/Wind Harmer
5.202
960611AF2-352 GEN
Solar/Wind Harmer
1.405
274880W4-005 GEN4
Solar/Wind Harmer
1.493
276174W4-005 GEN2
Solar/Wind Harmer
1.493
276615X2-022 GEN
Solar/Wind Harmer
0.922
276838X2-022 GEN2
Solar/Wind Harmer
0.109
276889AE2-281 GEN
Solar/Wind Harmer
1.516
274856ECOGROVE ;U1
Solar/Wind Harmer
2.637
276611AD2-172 GEN
Solar/Wind Harmer
2
276612AE2-035 GEN
Solar/Wind Harmer
2
971681AH1-341 GEN
Solar/Wind Harmer
11.563
926823AC1-168 GEN
Solar/Wind Harmer
3.258
972267AH1-718 GEN
Adder
3.122
274863CRW1-WTG
Solar/Wind Harmer
4.168
274864CRW2-WTG
Solar/Wind Harmer
4.168
276741O09 GEN1
Solar/Wind Harmer
2.647
970169AG2-114 GEN
Solar/Wind Harmer
7.161
274877BISHOP HL;1U
Solar/Wind Harmer
2.414
946321AF1-296 GEN
Solar/Wind Harmer
7.373
276726Z2-087_GEN
Solar/Wind Harmer
5.017
959341AF2-225 GEN
Solar/Wind Harmer
9.518
274853TWINGROVE;U1
Solar/Wind Harmer
4.352
274854TWINGROVE;U2
Solar/Wind Harmer
4.261
276668AB2-070 GEN1
Solar/Wind Harmer
1.091
276848AB2-070 GEN3
Solar/Wind Harmer
1.091
276849AB2-070 GEN2
Solar/Wind Harmer
1.091
276763AC1-053 GEN1
Solar/Wind Harmer
1.92
276764AC1-053 GEN2
Solar/Wind Harmer
1.92
990577J1339
External Queue
10.413962364196777
991777J1629 G
External Queue
6.448909282684326
990582J1340
External Queue
10.413962364196777
990512J1326
External Queue
4.084494590759277
990117J1214
External Queue
14.050661087036133
990727J1377 G
External Queue
4.744704723358154
990762J1386
External Queue
5.910062789916992
990407J1304
External Queue
3.160806655883789
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.148
NYPJM->LTFIMP_NY
CLTF
0.728
WECLTFEXP_WEC->PJM
CLTF
3.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.263
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.214
MECLTFEXP_MEC->PJM
CLTF
9.415
SIGELTFEXP_SIGE->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.299
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.33
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.93
LAGNLTFEXP_LAGN->PJM
CLTF
3.083
TVALTFEXP_TVA->PJM
CLTF
0.781

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.46 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1594.7
MW Contribution:
11.45
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.96 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1547.61
MW Contribution:
11.16
Bus #Bus NameTypeMW Contribution
972227AH1-698 GEN1
50/50
2.514
274655BRAIDWOOD;2U
50/50
3.339
972228AH1-698 GEN2
50/50
3.567
274687WILL CNTY;4U
50/50
26.759
274687WILL CNTY;4U
50/50
26.759
960681AF2-359 GEN
Solar/Wind Harmer
27.032
274675JOLIET 29;7U
Adder
27.324
274675JOLIET 29;7U
Adder
26.348
274827FISK ;RP
Adder
6.872
274728ELWOOD EC;5P
Adder
14.549
274731ELWOOD EC;2P
Adder
14.534
274733ELWOOD EC;3P
Adder
14.534
274735ELWOOD EC;4P
Adder
14.534
960591AF2-350 GEN
Solar/Wind Harmer
8.653
274775LINCOLN ;6U
Adder
5.341
274776LINCOLN ;7U
Adder
5.341
274777LINCOLN ;8U
Adder
5.341
276893AG1-478 C
Solar/Wind Harmer
0.473
970833AG2-524 GEN
Solar/Wind Harmer
7.494
970833AG2-524 GEN
Solar/Wind Harmer
3.486
274744AC1-111 GEN8
Adder
4.732
274746AC1-111 G10
Adder
4.732
274800UNIV PARK;3U
Adder
4.931
274801UNIV PARK;4U
Adder
4.931
972037AH1-567 GEN1
Adder
0.152
970073AG2-061 GEN
Solar/Wind Harmer
1.872
971411AH1-196 GEN
Solar/Wind Harmer
12.029
971675AH1-338 GEN
Solar/Wind Harmer
14.323
276861AD2-134 GEN
Solar/Wind Harmer
1.42
276863AD2-134 GEN
Solar/Wind Harmer
1.42
971171AH1-044 GEN
Solar/Wind Harmer
15.762
274823ROCKFORD ;21
Adder
15.318
276889AE2-281 GEN
Solar/Wind Harmer
1.501
274856ECOGROVE ;U1
Solar/Wind Harmer
2.611
276611AD2-172 GEN
Solar/Wind Harmer
1.981
276612AE2-035 GEN
Solar/Wind Harmer
1.981
971681AH1-341 GEN
Solar/Wind Harmer
11.451
926823AC1-168 GEN
Solar/Wind Harmer
3.226
972267AH1-718 GEN
Adder
3.091
274863CRW1-WTG
Solar/Wind Harmer
4.126
274864CRW2-WTG
Solar/Wind Harmer
4.126
276741O09 GEN1
Solar/Wind Harmer
2.621
970169AG2-114 GEN
Solar/Wind Harmer
7.09
274877BISHOP HL;1U
Solar/Wind Harmer
2.39
946321AF1-296 GEN
Solar/Wind Harmer
7.301
276726Z2-087_GEN
Solar/Wind Harmer
4.966
959341AF2-225 GEN
Solar/Wind Harmer
9.421
274853TWINGROVE;U1
Solar/Wind Harmer
4.308
274854TWINGROVE;U2
Solar/Wind Harmer
4.218
276668AB2-070 GEN1
Solar/Wind Harmer
1.08
274752CRETE EC ;2U
50/50
9.069
274753CRETE EC ;3U
50/50
9.069
274654BRAIDWOOD;1U
50/50
3.444
959351AF2-226 GEN
50/50
2.074
972231SS25-0005
Solar/Wind Harmer
16.594
972181SS23-001
Solar/Wind Harmer
10.371
274862TOP CROP ;2U
Solar/Wind Harmer
4.511
274676JOLIET 29;8U
Adder
26.354
274826FISK ;BP
Adder
9.697
972259AH1-714 GEN
Adder
16.898
274730ELWOOD EC;6P
Adder
14.549
274734ELWOOD EC;8P
Adder
14.549
274736ELWOOD EC;9P
Adder
14.549
274729ELWOOD EC;1P
Adder
14.534
970707AG2-453 GEN
Solar/Wind Harmer
24.357
274887GEN-1.85
Solar/Wind Harmer
4.61
276772AC2-154 GEN
Solar/Wind Harmer
2.415
276843GEN-1.7
Solar/Wind Harmer
0.496
276806AD2-047 C O1
Solar/Wind Harmer
9.257
274772LINCOLN ;3U
Adder
5.341
939351AE1-166 GEN
Solar/Wind Harmer
5.106
972038AH1-567 GEN2
Adder
0.309
943121AE2-341 GEN
Solar/Wind Harmer
12.644
943591AF1-030 GEN
Solar/Wind Harmer
8.429
276164X3-005 C
Solar/Wind Harmer
0.591
274682WAUKEGAN ;7U
Adder
15.077
274803UNIV PARK;6U
Adder
4.828
276868AE1-113 GEN
Solar/Wind Harmer
8.218
274879MINONK ;1U
Solar/Wind Harmer
5.479
274724RIVER EC ;11
Adder
14.208
276799AD1-013 GEN
Solar/Wind Harmer
1.759
946671AF1-331 GEN
Solar/Wind Harmer
0.333
274855GSG-6 ;RU
Solar/Wind Harmer
2.936
274850MENDOTA H;RU
Solar/Wind Harmer
2.041
276602WESTBROOK C
Solar/Wind Harmer
1.69
959091AF2-200 GEN
Solar/Wind Harmer
15.762
970571AG2-364 GEN
Solar/Wind Harmer
15.343
274814UNIV PK N;0U
Adder
3.862
274807UNIV PK N;3U
Adder
3.854
274811UNIV PK N;7U
Adder
3.829
274857EASY ROAD;U1
Solar/Wind Harmer
3.632
274760LEE CO EC;1U
Adder
7.054
274767LEE CO EC;8U
Adder
6.97
276603SUBLETTE C
Solar/Wind Harmer
0.791
274851PROVIDENC;RU
Solar/Wind Harmer
2.033
274849CRESCENT ;1U
Solar/Wind Harmer
1.32
276782AC1-033 GEN
Solar/Wind Harmer
2.825
274878BISHOP HL;2U
Solar/Wind Harmer
2.39
965931AG1-462 GEN
Solar/Wind Harmer
17.647
971087AG2-675 GEN
Solar/Wind Harmer
2.575
965091AG1-374 GEN
Solar/Wind Harmer
17.938
959611AF2-252 GEN
Solar/Wind Harmer
1.391
276785W4-005 GEN1
Solar/Wind Harmer
1.478
971993AH1-541 GEN
Solar/Wind Harmer
4.515
965681AG1-436 GEN
Solar/Wind Harmer
89.431
965791AG1-447 GEN
Solar/Wind Harmer
45.755
274888KELLY CRK;1U
Solar/Wind Harmer
5.106
276776AD2-060 GEN
Solar/Wind Harmer
0.362
958011AF2-095 GEN
Solar/Wind Harmer
12.461
970941AG2-585 GEN
Solar/Wind Harmer
4.759
274770LINCOLN ;1U
Adder
5.341
274771LINCOLN ;2U
Adder
5.341
276897AD1-100 C
Solar/Wind Harmer
39.998
276893AG1-478 C
Solar/Wind Harmer
0.377
274674JOLIET 9 ;6U
Adder
13.18
274683WAUKEGAN ;8U
Adder
17.635
274683WAUKEGAN ;8U
Adder
14.865
274696ROCKY RD ;4P
Adder
9.502
274695ROCKY RD ;2P
Adder
9.283
274693ROCKY RD ;1P
Adder
9.192
274697ROCKY RD ;3P
Adder
2.522
958481AF2-142 GEN
Solar/Wind Harmer
12.314
962691AG1-118 GEN
Solar/Wind Harmer
24.521
960751AF2-366 GEN
Solar/Wind Harmer
2.335
958491AF2-143 GEN
Solar/Wind Harmer
12.072
276901AD2-066 C O1
Solar/Wind Harmer
2.81
971341AH1-150 GEN
Solar/Wind Harmer
15.762
971343AH1-151 GEN
Solar/Wind Harmer
15.762
276872AE1-163_GEN1
Solar/Wind Harmer
5.255
276876AE1-163_GEN2
Solar/Wind Harmer
5.255
972235AH1-702 GEN1
Adder
1.971
972236AH1-702 GEN2
Adder
1.714
274805UNIV PK N;1U
Adder
3.837
274808UNIV PK N;4U
Adder
3.812
938861AE1-114 GEN
Solar/Wind Harmer
6.259
274764LEE CO EC;5U
Adder
7.07
274765LEE CO EC;6U
Adder
7.07
274762LEE CO EC;3U
Adder
7.054
274763LEE CO EC;4U
Adder
6.987
276158O29GEN2
Solar/Wind Harmer
3.672
276157O29GEN1
Solar/Wind Harmer
2.791
276645AC1-214 GEN1
Solar/Wind Harmer
0.956
942111AE2-223 GEN
Solar/Wind Harmer
5.149
960611AF2-352 GEN
Solar/Wind Harmer
1.391
274880W4-005 GEN4
Solar/Wind Harmer
1.478
276174W4-005 GEN2
Solar/Wind Harmer
1.478
276615X2-022 GEN
Solar/Wind Harmer
0.912
276838X2-022 GEN2
Solar/Wind Harmer
0.108
274751CRETE EC ;1U
50/50
9.069
274754CRETE EC ;4U
50/50
9.069
960281AF2-319 GEN
50/50
2.074
274861TOP CROP ;1U
Solar/Wind Harmer
5.402
274676JOLIET 29;8U
Adder
27.33
274732ELWOOD EC;7P
Adder
14.549
972207SS24-0001
Solar/Wind Harmer
18.989
274773LINCOLN ;4U
Adder
5.341
274774LINCOLN ;5U
Adder
5.341
941551AE2-152 GEN
Solar/Wind Harmer
3.905
274871GR RIDGE ;2U
Solar/Wind Harmer
6.608
274847GR RIDGE ;BU
Solar/Wind Harmer
4.345
274674JOLIET 9 ;6U
Adder
13.18
274745AC1-111 GEN9
Adder
4.732
274682WAUKEGAN ;7U
Adder
15.077
274828WAUKEGAN ;BP
Adder
9.244
274802UNIV PARK;5U
Adder
4.828
276694AA1-018 GEN2
Solar/Wind Harmer
5.18
276691AA1-018 GEN1
Solar/Wind Harmer
0.619
962781AG1-127 GEN
Solar/Wind Harmer
7.738
276882AE2-255 GEN
Solar/Wind Harmer
2.739
274872LEEDK;1U
Solar/Wind Harmer
6.649
276805AD2-038 GEN
Solar/Wind Harmer
4.127
274723RIVER EC ;12
Adder
14.363
971997AH1-543 GEN
Solar/Wind Harmer
12.435
957471AF2-041 GEN
Solar/Wind Harmer
23.642
959081AF2-199 GEN
Solar/Wind Harmer
7.881
971067AG2-660 GEN
Solar/Wind Harmer
1.833
274822ROCKFORD ;11
Adder
15.43
970819AG2-516 GEN
Solar/Wind Harmer
9.331
939401AE1-172 GEN
Solar/Wind Harmer
10.747
970569AG2-363 GEN
Solar/Wind Harmer
23.014
274812UNIV PK N;8U
Adder
3.829
274858EASY ROAD;U2
Solar/Wind Harmer
3.632
274761LEE CO EC;2U
Adder
7.054
274766LEE CO EC;7U
Adder
6.97
276708O09 GEN2
Solar/Wind Harmer
2.621
276646AC1-214 GEN2
Solar/Wind Harmer
0.956
274848CAMPGROVE;RU
Solar/Wind Harmer
4.517
276655WTG1_EQ
Solar/Wind Harmer
5.482
276656WTG2_EQ
Solar/Wind Harmer
0.726
939741AE1-205 GEN
Solar/Wind Harmer
12.561
276686W4-005 GEN3
Solar/Wind Harmer
1.478
276621W2-048 GEN
Solar/Wind Harmer
2.905
276848AB2-070 GEN3
Solar/Wind Harmer
1.08
276849AB2-070 GEN2
Solar/Wind Harmer
1.08
276763AC1-053 GEN1
Solar/Wind Harmer
1.9
276764AC1-053 GEN2
Solar/Wind Harmer
1.9
990577J1339
External Queue
10.302718162536621
991777J1629 G
External Queue
6.408222675323486
990582J1340
External Queue
10.302718162536621
990512J1326
External Queue
4.058592796325684
990117J1214
External Queue
13.96155834197998
990727J1377 G
External Queue
4.714233875274658
990762J1386
External Queue
5.8489766120910645
990407J1304
External Queue
3.14041805267334
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.145
NYPJM->LTFIMP_NY
CLTF
0.719
WECLTFEXP_WEC->PJM
CLTF
3.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.488
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.115
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.983
MECLTFEXP_MEC->PJM
CLTF
9.323
SIGELTFEXP_SIGE->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.294
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.325
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.916
LAGNLTFEXP_LAGN->PJM
CLTF
3.055
TVALTFEXP_TVA->PJM
CLTF
0.775

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.78 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1566.69
MW Contribution:
11.29
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.77 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1556.11
MW Contribution:
11.15
Bus #Bus NameTypeMW Contribution
274752CRETE EC ;2U
50/50
8.979
274753CRETE EC ;3U
50/50
8.979
274654BRAIDWOOD;1U
50/50
3.391
959351AF2-226 GEN
50/50
2.044
972231SS25-0005
Solar/Wind Harmer
16.43
972181SS23-001
Solar/Wind Harmer
10.269
274862TOP CROP ;2U
Solar/Wind Harmer
4.446
274676JOLIET 29;8U
Adder
25.946
972259AH1-714 GEN
Adder
16.639
274730ELWOOD EC;6P
Adder
14.326
274734ELWOOD EC;8P
Adder
14.326
274736ELWOOD EC;9P
Adder
14.326
274826FISK ;BP
Adder
9.535
274729ELWOOD EC;1P
Adder
14.312
970707AG2-453 GEN
Solar/Wind Harmer
23.984
274887GEN-1.85
Solar/Wind Harmer
4.534
276843GEN-1.7
Solar/Wind Harmer
0.488
276772AC2-154 GEN
Solar/Wind Harmer
2.375
276806AD2-047 C O1
Solar/Wind Harmer
9.103
939351AE1-166 GEN
Solar/Wind Harmer
5.028
274772LINCOLN ;3U
Adder
5.255
972038AH1-567 GEN2
Adder
0.303
943121AE2-341 GEN
Solar/Wind Harmer
12.453
943591AF1-030 GEN
Solar/Wind Harmer
8.302
274682WAUKEGAN ;7U
Adder
14.852
276164X3-005 C
Solar/Wind Harmer
0.58
274803UNIV PARK;6U
Adder
4.74
276868AE1-113 GEN
Solar/Wind Harmer
8.101
274879MINONK ;1U
Solar/Wind Harmer
5.401
274724RIVER EC ;11
Adder
13.914
276799AD1-013 GEN
Solar/Wind Harmer
1.734
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.894
274850MENDOTA H;RU
Solar/Wind Harmer
2.012
276602WESTBROOK C
Solar/Wind Harmer
1.666
959091AF2-200 GEN
Solar/Wind Harmer
15.538
970571AG2-364 GEN
Solar/Wind Harmer
15.135
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.773
274811UNIV PK N;7U
Adder
3.749
274857EASY ROAD;U1
Solar/Wind Harmer
3.582
274760LEE CO EC;1U
Adder
6.957
274767LEE CO EC;8U
Adder
6.875
276603SUBLETTE C
Solar/Wind Harmer
0.78
274851PROVIDENC;RU
Solar/Wind Harmer
2.007
274849CRESCENT ;1U
Solar/Wind Harmer
1.303
276782AC1-033 GEN
Solar/Wind Harmer
2.79
274878BISHOP HL;2U
Solar/Wind Harmer
2.36
965931AG1-462 GEN
Solar/Wind Harmer
17.426
971087AG2-675 GEN
Solar/Wind Harmer
2.543
965091AG1-374 GEN
Solar/Wind Harmer
17.766
959611AF2-252 GEN
Solar/Wind Harmer
1.377
276785W4-005 GEN1
Solar/Wind Harmer
1.47
971993AH1-541 GEN
Solar/Wind Harmer
4.491
274751CRETE EC ;1U
50/50
8.979
274754CRETE EC ;4U
50/50
8.979
960281AF2-319 GEN
50/50
2.044
274861TOP CROP ;1U
Solar/Wind Harmer
5.325
274676JOLIET 29;8U
Adder
26.907
274732ELWOOD EC;7P
Adder
14.326
941551AE2-152 GEN
Solar/Wind Harmer
3.845
972207SS24-0001
Solar/Wind Harmer
18.685
274773LINCOLN ;4U
Adder
5.255
274774LINCOLN ;5U
Adder
5.255
274871GR RIDGE ;2U
Solar/Wind Harmer
6.509
274847GR RIDGE ;BU
Solar/Wind Harmer
4.28
274674JOLIET 9 ;6U
Adder
12.971
274745AC1-111 GEN9
Adder
4.661
274682WAUKEGAN ;7U
Adder
14.852
274828WAUKEGAN ;BP
Adder
9.106
274802UNIV PARK;5U
Adder
4.74
276694AA1-018 GEN2
Solar/Wind Harmer
5.099
276691AA1-018 GEN1
Solar/Wind Harmer
0.61
962781AG1-127 GEN
Solar/Wind Harmer
7.625
276882AE2-255 GEN
Solar/Wind Harmer
2.7
274872LEEDK;1U
Solar/Wind Harmer
6.552
276805AD2-038 GEN
Solar/Wind Harmer
4.065
274723RIVER EC ;12
Adder
14.066
971997AH1-543 GEN
Solar/Wind Harmer
12.26
957471AF2-041 GEN
Solar/Wind Harmer
23.306
959081AF2-199 GEN
Solar/Wind Harmer
7.769
971067AG2-660 GEN
Solar/Wind Harmer
1.807
274822ROCKFORD ;11
Adder
15.211
972227AH1-698 GEN1
50/50
2.476
274655BRAIDWOOD;2U
50/50
3.288
972228AH1-698 GEN2
50/50
3.512
274687WILL CNTY;4U
50/50
26.344
274687WILL CNTY;4U
50/50
26.344
960681AF2-359 GEN
Solar/Wind Harmer
26.927
274675JOLIET 29;7U
Adder
26.9
274675JOLIET 29;7U
Adder
25.94
274728ELWOOD EC;5P
Adder
14.326
274827FISK ;RP
Adder
6.757
274731ELWOOD EC;2P
Adder
14.312
274733ELWOOD EC;3P
Adder
14.312
274735ELWOOD EC;4P
Adder
14.312
960591AF2-350 GEN
Solar/Wind Harmer
8.51
274775LINCOLN ;6U
Adder
5.255
274776LINCOLN ;7U
Adder
5.255
274777LINCOLN ;8U
Adder
5.255
276893AG1-478 C
Solar/Wind Harmer
0.466
970833AG2-524 GEN
Solar/Wind Harmer
7.381
970833AG2-524 GEN
Solar/Wind Harmer
3.433
274744AC1-111 GEN8
Adder
4.661
274746AC1-111 G10
Adder
4.661
274800UNIV PARK;3U
Adder
4.846
274801UNIV PARK;4U
Adder
4.846
972037AH1-567 GEN1
Adder
0.149
970073AG2-061 GEN
Solar/Wind Harmer
1.844
971411AH1-196 GEN
Solar/Wind Harmer
11.855
971675AH1-338 GEN
Solar/Wind Harmer
14.117
276861AD2-134 GEN
Solar/Wind Harmer
1.399
276863AD2-134 GEN
Solar/Wind Harmer
1.399
971171AH1-044 GEN
Solar/Wind Harmer
15.538
274823ROCKFORD ;21
Adder
15.1
276889AE2-281 GEN
Solar/Wind Harmer
1.48
274856ECOGROVE ;U1
Solar/Wind Harmer
2.575
276611AD2-172 GEN
Solar/Wind Harmer
1.953
276612AE2-035 GEN
Solar/Wind Harmer
1.953
971681AH1-341 GEN
Solar/Wind Harmer
11.293
926823AC1-168 GEN
Solar/Wind Harmer
3.183
972267AH1-718 GEN
Adder
3.05
274863CRW1-WTG
Solar/Wind Harmer
4.072
274864CRW2-WTG
Solar/Wind Harmer
4.072
965681AG1-436 GEN
Solar/Wind Harmer
89.084
965791AG1-447 GEN
Solar/Wind Harmer
45.578
274888KELLY CRK;1U
Solar/Wind Harmer
5.022
958011AF2-095 GEN
Solar/Wind Harmer
12.254
970941AG2-585 GEN
Solar/Wind Harmer
4.68
276776AD2-060 GEN
Solar/Wind Harmer
0.356
276897AD1-100 C
Solar/Wind Harmer
39.384
274770LINCOLN ;1U
Adder
5.255
274771LINCOLN ;2U
Adder
5.255
276893AG1-478 C
Solar/Wind Harmer
0.371
274674JOLIET 9 ;6U
Adder
12.971
274683WAUKEGAN ;8U
Adder
17.372
274683WAUKEGAN ;8U
Adder
14.644
274696ROCKY RD ;4P
Adder
9.361
274695ROCKY RD ;2P
Adder
9.145
274693ROCKY RD ;1P
Adder
9.055
274697ROCKY RD ;3P
Adder
2.484
958481AF2-142 GEN
Solar/Wind Harmer
12.123
962691AG1-118 GEN
Solar/Wind Harmer
24.161
960751AF2-366 GEN
Solar/Wind Harmer
2.3
958491AF2-143 GEN
Solar/Wind Harmer
11.892
276901AD2-066 C O1
Solar/Wind Harmer
2.769
971341AH1-150 GEN
Solar/Wind Harmer
15.538
971343AH1-151 GEN
Solar/Wind Harmer
15.538
276872AE1-163_GEN1
Solar/Wind Harmer
5.18
276876AE1-163_GEN2
Solar/Wind Harmer
5.18
972235AH1-702 GEN1
Adder
1.944
972236AH1-702 GEN2
Adder
1.69
938861AE1-114 GEN
Solar/Wind Harmer
6.173
274805UNIV PK N;1U
Adder
3.757
274808UNIV PK N;4U
Adder
3.732
274764LEE CO EC;5U
Adder
6.973
274765LEE CO EC;6U
Adder
6.973
274762LEE CO EC;3U
Adder
6.957
274763LEE CO EC;4U
Adder
6.891
276158O29GEN2
Solar/Wind Harmer
3.623
276157O29GEN1
Solar/Wind Harmer
2.754
276645AC1-214 GEN1
Solar/Wind Harmer
0.944
942111AE2-223 GEN
Solar/Wind Harmer
5.095
960611AF2-352 GEN
Solar/Wind Harmer
1.377
274880W4-005 GEN4
Solar/Wind Harmer
1.47
276174W4-005 GEN2
Solar/Wind Harmer
1.47
276615X2-022 GEN
Solar/Wind Harmer
0.908
276838X2-022 GEN2
Solar/Wind Harmer
0.108
970819AG2-516 GEN
Solar/Wind Harmer
9.2
939401AE1-172 GEN
Solar/Wind Harmer
10.598
970569AG2-363 GEN
Solar/Wind Harmer
22.702
274812UNIV PK N;8U
Adder
3.749
274858EASY ROAD;U2
Solar/Wind Harmer
3.582
274761LEE CO EC;2U
Adder
6.957
274766LEE CO EC;7U
Adder
6.875
276708O09 GEN2
Solar/Wind Harmer
2.587
276646AC1-214 GEN2
Solar/Wind Harmer
0.944
274848CAMPGROVE;RU
Solar/Wind Harmer
4.461
276655WTG1_EQ
Solar/Wind Harmer
5.424
276656WTG2_EQ
Solar/Wind Harmer
0.718
939741AE1-205 GEN
Solar/Wind Harmer
12.43
276686W4-005 GEN3
Solar/Wind Harmer
1.47
276621W2-048 GEN
Solar/Wind Harmer
2.893
276741O09 GEN1
Solar/Wind Harmer
2.587
970169AG2-114 GEN
Solar/Wind Harmer
7.001
274877BISHOP HL;1U
Solar/Wind Harmer
2.36
946321AF1-296 GEN
Solar/Wind Harmer
7.209
276726Z2-087_GEN
Solar/Wind Harmer
4.914
959341AF2-225 GEN
Solar/Wind Harmer
9.322
274853TWINGROVE;U1
Solar/Wind Harmer
4.267
274854TWINGROVE;U2
Solar/Wind Harmer
4.177
276668AB2-070 GEN1
Solar/Wind Harmer
1.074
276848AB2-070 GEN3
Solar/Wind Harmer
1.074
276849AB2-070 GEN2
Solar/Wind Harmer
1.074
276763AC1-053 GEN1
Solar/Wind Harmer
1.891
276764AC1-053 GEN2
Solar/Wind Harmer
1.891
990577J1339
External Queue
10.091670036315918
991777J1629 G
External Queue
6.367271423339844
990582J1340
External Queue
10.091670036315918
990512J1326
External Queue
4.031956195831299
990117J1214
External Queue
13.869928359985352
990727J1377 G
External Queue
4.68088960647583
990762J1386
External Queue
5.7299675941467285
990407J1304
External Queue
3.1176300048828125
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.125
NYPJM->LTFIMP_NY
CLTF
0.704
WECLTFEXP_WEC->PJM
CLTF
2.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.335
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.529
MECLTFEXP_MEC->PJM
CLTF
9.234
SIGELTFEXP_SIGE->PJM
CLTF
0.015
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.262
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.248
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.683
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
TVALTFEXP_TVA->PJM
CLTF
0.824

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.8 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1169.44
MW Contribution:
8.66
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.29 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1122.25
MW Contribution:
8.41
Bus #Bus NameTypeMW Contribution
965681AG1-436 GEN
Solar/Wind Harmer
62.504
965791AG1-447 GEN
Solar/Wind Harmer
45.836
274888KELLY CRK;1U
Solar/Wind Harmer
0.356
276776AD2-060 GEN
Solar/Wind Harmer
0.651
958011AF2-095 GEN
Solar/Wind Harmer
8.783
970941AG2-585 GEN
Solar/Wind Harmer
3.355
274770LINCOLN ;1U
Adder
7.344
274771LINCOLN ;2U
Adder
7.344
276897AD1-100 C
Solar/Wind Harmer
15.167
276893AG1-478 C
Solar/Wind Harmer
0.404
274674JOLIET 9 ;6U
Adder
13.314
274683WAUKEGAN ;8U
Adder
17.808
274683WAUKEGAN ;8U
Adder
15.011
274695ROCKY RD ;2P
Adder
9.375
274693ROCKY RD ;1P
Adder
9.282
274697ROCKY RD ;3P
Adder
2.547
274696ROCKY RD ;4P
Adder
9.596
958481AF2-142 GEN
Solar/Wind Harmer
8.678
962691AG1-118 GEN
Solar/Wind Harmer
17.276
958491AF2-143 GEN
Solar/Wind Harmer
8.507
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
11.105
971343AH1-151 GEN
Solar/Wind Harmer
11.105
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.991
972236AH1-702 GEN2
Adder
1.731
274805UNIV PK N;1U
Adder
3.884
274808UNIV PK N;4U
Adder
3.859
938861AE1-114 GEN
Solar/Wind Harmer
3.048
274764LEE CO EC;5U
Adder
7.14
274765LEE CO EC;6U
Adder
7.14
274762LEE CO EC;3U
Adder
7.123
274763LEE CO EC;4U
Adder
7.056
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.834
276645AC1-214 GEN1
Solar/Wind Harmer
0.197
942111AE2-223 GEN
Solar/Wind Harmer
1.439
960611AF2-352 GEN
Solar/Wind Harmer
1.405
276615X2-022 GEN
Solar/Wind Harmer
0.034
276838X2-022 GEN2
Solar/Wind Harmer
0.185
972227AH1-698 GEN1
50/50
2.539
274655BRAIDWOOD;2U
50/50
3.372
972228AH1-698 GEN2
50/50
3.601
274687WILL CNTY;4U
50/50
27.019
274687WILL CNTY;4U
50/50
27.019
960681AF2-359 GEN
Solar/Wind Harmer
-0.005
274675JOLIET 29;7U
Adder
27.591
274675JOLIET 29;7U
Adder
26.605
274827FISK ;RP
Adder
6.943
274728ELWOOD EC;5P
Adder
14.691
274731ELWOOD EC;2P
Adder
14.676
274733ELWOOD EC;3P
Adder
14.676
274735ELWOOD EC;4P
Adder
14.676
960591AF2-350 GEN
Solar/Wind Harmer
6.1
274775LINCOLN ;6U
Adder
7.344
274776LINCOLN ;7U
Adder
7.344
274777LINCOLN ;8U
Adder
7.344
970833AG2-524 GEN
Solar/Wind Harmer
6.653
970833AG2-524 GEN
Solar/Wind Harmer
4.435
274744AC1-111 GEN8
Adder
4.779
274746AC1-111 G10
Adder
4.779
274800UNIV PARK;3U
Adder
4.984
274801UNIV PARK;4U
Adder
4.984
972037AH1-567 GEN1
Adder
0.153
970073AG2-061 GEN
Solar/Wind Harmer
1.89
971411AH1-196 GEN
Solar/Wind Harmer
8.475
971675AH1-338 GEN
Solar/Wind Harmer
2.186
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276863AD2-134 GEN
Solar/Wind Harmer
0.1
971171AH1-044 GEN
Solar/Wind Harmer
11.105
274823ROCKFORD ;21
Adder
15.469
274856ECOGROVE ;U1
Solar/Wind Harmer
0.127
971681AH1-341 GEN
Solar/Wind Harmer
8.66
926823AC1-168 GEN
Solar/Wind Harmer
0.899
972267AH1-718 GEN
Adder
3.122
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.182
970169AG2-114 GEN
Solar/Wind Harmer
4.996
274877BISHOP HL;1U
Solar/Wind Harmer
0.167
946321AF1-296 GEN
Solar/Wind Harmer
2.761
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.648
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.135
276848AB2-070 GEN3
Solar/Wind Harmer
0.135
276849AB2-070 GEN2
Solar/Wind Harmer
0.135
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274752CRETE EC ;2U
50/50
15.372
274753CRETE EC ;3U
50/50
15.372
274654BRAIDWOOD;1U
50/50
3.478
959351AF2-226 GEN
50/50
2.093
274862TOP CROP ;2U
Solar/Wind Harmer
0.848
274676JOLIET 29;8U
Adder
26.612
274826FISK ;BP
Adder
9.796
972259AH1-714 GEN
Adder
17.063
274730ELWOOD EC;6P
Adder
14.691
274734ELWOOD EC;8P
Adder
14.691
274736ELWOOD EC;9P
Adder
14.691
274729ELWOOD EC;1P
Adder
14.676
970707AG2-453 GEN
Solar/Wind Harmer
20.02
274887GEN-1.85
Solar/Wind Harmer
0.159
276843GEN-1.7
Solar/Wind Harmer
0.197
276806AD2-047 C O1
Solar/Wind Harmer
3.456
274772LINCOLN ;3U
Adder
7.344
939351AE1-166 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.312
943121AE2-341 GEN
Solar/Wind Harmer
9.957
943591AF1-030 GEN
Solar/Wind Harmer
6.622
274682WAUKEGAN ;7U
Adder
15.225
274803UNIV PARK;6U
Adder
4.881
276868AE1-113 GEN
Solar/Wind Harmer
1.145
274879MINONK ;1U
Solar/Wind Harmer
0.239
274724RIVER EC ;11
Adder
14.381
946671AF1-331 GEN
Solar/Wind Harmer
0.599
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.065
959091AF2-200 GEN
Solar/Wind Harmer
11.105
970571AG2-364 GEN
Solar/Wind Harmer
10.81
274814UNIV PK N;0U
Adder
3.91
274807UNIV PK N;3U
Adder
3.901
274811UNIV PK N;7U
Adder
3.876
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
7.123
274767LEE CO EC;8U
Adder
7.039
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.167
965931AG1-462 GEN
Solar/Wind Harmer
12.434
971087AG2-675 GEN
Solar/Wind Harmer
2.601
965091AG1-374 GEN
Solar/Wind Harmer
12.644
959611AF2-252 GEN
Solar/Wind Harmer
1.405
971993AH1-541 GEN
Solar/Wind Harmer
1.592
274751CRETE EC ;1U
50/50
15.372
274754CRETE EC ;4U
50/50
15.372
960281AF2-319 GEN
50/50
2.093
274861TOP CROP ;1U
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
27.597
274732ELWOOD EC;7P
Adder
14.691
274773LINCOLN ;4U
Adder
7.344
274774LINCOLN ;5U
Adder
7.344
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
13.314
274745AC1-111 GEN9
Adder
4.779
274682WAUKEGAN ;7U
Adder
15.225
274828WAUKEGAN ;BP
Adder
9.334
274802UNIV PARK;5U
Adder
4.881
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.94
962781AG1-127 GEN
Solar/Wind Harmer
5.456
276882AE2-255 GEN
Solar/Wind Harmer
0.668
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
14.537
971997AH1-543 GEN
Solar/Wind Harmer
2.921
957471AF2-041 GEN
Solar/Wind Harmer
16.657
959081AF2-199 GEN
Solar/Wind Harmer
5.552
971067AG2-660 GEN
Solar/Wind Harmer
1.851
274822ROCKFORD ;11
Adder
15.582
970819AG2-516 GEN
Solar/Wind Harmer
6.574
939401AE1-172 GEN
Solar/Wind Harmer
4.065
970569AG2-363 GEN
Solar/Wind Harmer
16.215
274812UNIV PK N;8U
Adder
3.876
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.123
274766LEE CO EC;7U
Adder
7.039
276708O09 GEN2
Solar/Wind Harmer
0.182
276646AC1-214 GEN2
Solar/Wind Harmer
0.197
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.198
276621W2-048 GEN
Solar/Wind Harmer
0.164
990577J1339
External Queue
10.412999153137207
991777J1629 G
External Queue
9.277681350708008
991247J1684 G
External Queue
9.028225898742676
990582J1340
External Queue
10.412999153137207
990512J1326
External Queue
4.084977626800537
990117J1214
External Queue
14.052322387695312
990727J1377 G
External Queue
4.745286464691162
990762J1386
External Queue
5.909551620483398
991303J1755 G
External Queue
3.5140795707702637
990407J1304
External Queue
3.1611876487731934
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.148
NYPJM->LTFIMP_NY
CLTF
0.728
WECLTFEXP_WEC->PJM
CLTF
3.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.268
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.214
MECLTFEXP_MEC->PJM
CLTF
9.415
SIGELTFEXP_SIGE->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.299
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.33
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.93
LAGNLTFEXP_LAGN->PJM
CLTF
3.083
TVALTFEXP_TVA->PJM
CLTF
0.781

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.79 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1169.28
MW Contribution:
8.66
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.28 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1122.15
MW Contribution:
8.41
Bus #Bus NameTypeMW Contribution
965681AG1-436 GEN
Solar/Wind Harmer
62.504
965791AG1-447 GEN
Solar/Wind Harmer
45.836
274888KELLY CRK;1U
Solar/Wind Harmer
0.356
276776AD2-060 GEN
Solar/Wind Harmer
0.651
958011AF2-095 GEN
Solar/Wind Harmer
8.783
970941AG2-585 GEN
Solar/Wind Harmer
3.355
274770LINCOLN ;1U
Adder
7.344
274771LINCOLN ;2U
Adder
7.344
276897AD1-100 C
Solar/Wind Harmer
15.167
276893AG1-478 C
Solar/Wind Harmer
0.404
274674JOLIET 9 ;6U
Adder
13.314
274683WAUKEGAN ;8U
Adder
17.808
274683WAUKEGAN ;8U
Adder
15.011
274695ROCKY RD ;2P
Adder
9.375
274693ROCKY RD ;1P
Adder
9.282
274697ROCKY RD ;3P
Adder
2.547
274696ROCKY RD ;4P
Adder
9.596
958481AF2-142 GEN
Solar/Wind Harmer
8.678
962691AG1-118 GEN
Solar/Wind Harmer
17.276
958491AF2-143 GEN
Solar/Wind Harmer
8.507
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
11.105
971343AH1-151 GEN
Solar/Wind Harmer
11.105
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.991
972236AH1-702 GEN2
Adder
1.731
274805UNIV PK N;1U
Adder
3.884
274808UNIV PK N;4U
Adder
3.859
938861AE1-114 GEN
Solar/Wind Harmer
3.048
274764LEE CO EC;5U
Adder
7.14
274765LEE CO EC;6U
Adder
7.14
274762LEE CO EC;3U
Adder
7.123
274763LEE CO EC;4U
Adder
7.056
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.834
276645AC1-214 GEN1
Solar/Wind Harmer
0.197
942111AE2-223 GEN
Solar/Wind Harmer
1.439
960611AF2-352 GEN
Solar/Wind Harmer
1.405
276615X2-022 GEN
Solar/Wind Harmer
0.034
276838X2-022 GEN2
Solar/Wind Harmer
0.185
972227AH1-698 GEN1
50/50
2.539
274655BRAIDWOOD;2U
50/50
3.372
972228AH1-698 GEN2
50/50
3.601
274687WILL CNTY;4U
50/50
27.019
274687WILL CNTY;4U
50/50
27.019
960681AF2-359 GEN
Solar/Wind Harmer
-0.005
274675JOLIET 29;7U
Adder
27.591
274675JOLIET 29;7U
Adder
26.605
274827FISK ;RP
Adder
6.943
274728ELWOOD EC;5P
Adder
14.691
274731ELWOOD EC;2P
Adder
14.676
274733ELWOOD EC;3P
Adder
14.676
274735ELWOOD EC;4P
Adder
14.676
960591AF2-350 GEN
Solar/Wind Harmer
6.1
274775LINCOLN ;6U
Adder
7.344
274776LINCOLN ;7U
Adder
7.344
274777LINCOLN ;8U
Adder
7.344
970833AG2-524 GEN
Solar/Wind Harmer
6.653
970833AG2-524 GEN
Solar/Wind Harmer
4.435
274744AC1-111 GEN8
Adder
4.779
274746AC1-111 G10
Adder
4.779
274800UNIV PARK;3U
Adder
4.984
274801UNIV PARK;4U
Adder
4.984
972037AH1-567 GEN1
Adder
0.153
970073AG2-061 GEN
Solar/Wind Harmer
1.89
971411AH1-196 GEN
Solar/Wind Harmer
8.475
971675AH1-338 GEN
Solar/Wind Harmer
2.186
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276863AD2-134 GEN
Solar/Wind Harmer
0.1
971171AH1-044 GEN
Solar/Wind Harmer
11.105
274823ROCKFORD ;21
Adder
15.469
274856ECOGROVE ;U1
Solar/Wind Harmer
0.127
971681AH1-341 GEN
Solar/Wind Harmer
8.66
926823AC1-168 GEN
Solar/Wind Harmer
0.899
972267AH1-718 GEN
Adder
3.122
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.182
970169AG2-114 GEN
Solar/Wind Harmer
4.996
274877BISHOP HL;1U
Solar/Wind Harmer
0.167
946321AF1-296 GEN
Solar/Wind Harmer
2.761
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.648
274853TWINGROVE;U1
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.135
276848AB2-070 GEN3
Solar/Wind Harmer
0.135
276849AB2-070 GEN2
Solar/Wind Harmer
0.135
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274752CRETE EC ;2U
50/50
15.372
274753CRETE EC ;3U
50/50
15.372
274654BRAIDWOOD;1U
50/50
3.478
959351AF2-226 GEN
50/50
2.093
274862TOP CROP ;2U
Solar/Wind Harmer
0.848
274676JOLIET 29;8U
Adder
26.612
274826FISK ;BP
Adder
9.796
972259AH1-714 GEN
Adder
17.063
274730ELWOOD EC;6P
Adder
14.691
274734ELWOOD EC;8P
Adder
14.691
274736ELWOOD EC;9P
Adder
14.691
274729ELWOOD EC;1P
Adder
14.676
970707AG2-453 GEN
Solar/Wind Harmer
20.02
274887GEN-1.85
Solar/Wind Harmer
0.159
276843GEN-1.7
Solar/Wind Harmer
0.197
276806AD2-047 C O1
Solar/Wind Harmer
3.456
274772LINCOLN ;3U
Adder
7.344
939351AE1-166 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.312
943121AE2-341 GEN
Solar/Wind Harmer
9.957
943591AF1-030 GEN
Solar/Wind Harmer
6.622
274682WAUKEGAN ;7U
Adder
15.225
274803UNIV PARK;6U
Adder
4.881
276868AE1-113 GEN
Solar/Wind Harmer
1.145
274879MINONK ;1U
Solar/Wind Harmer
0.239
274724RIVER EC ;11
Adder
14.381
946671AF1-331 GEN
Solar/Wind Harmer
0.599
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.065
959091AF2-200 GEN
Solar/Wind Harmer
11.105
970571AG2-364 GEN
Solar/Wind Harmer
10.81
274814UNIV PK N;0U
Adder
3.91
274807UNIV PK N;3U
Adder
3.901
274811UNIV PK N;7U
Adder
3.876
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
7.123
274767LEE CO EC;8U
Adder
7.039
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.167
965931AG1-462 GEN
Solar/Wind Harmer
12.434
971087AG2-675 GEN
Solar/Wind Harmer
2.601
965091AG1-374 GEN
Solar/Wind Harmer
12.644
959611AF2-252 GEN
Solar/Wind Harmer
1.405
971993AH1-541 GEN
Solar/Wind Harmer
1.592
274751CRETE EC ;1U
50/50
15.372
274754CRETE EC ;4U
50/50
15.372
960281AF2-319 GEN
50/50
2.093
274861TOP CROP ;1U
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
27.597
274732ELWOOD EC;7P
Adder
14.691
274773LINCOLN ;4U
Adder
7.344
274774LINCOLN ;5U
Adder
7.344
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
13.314
274745AC1-111 GEN9
Adder
4.779
274682WAUKEGAN ;7U
Adder
15.225
274828WAUKEGAN ;BP
Adder
9.334
274802UNIV PARK;5U
Adder
4.881
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.94
962781AG1-127 GEN
Solar/Wind Harmer
5.456
276882AE2-255 GEN
Solar/Wind Harmer
0.668
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
14.537
971997AH1-543 GEN
Solar/Wind Harmer
2.921
957471AF2-041 GEN
Solar/Wind Harmer
16.657
959081AF2-199 GEN
Solar/Wind Harmer
5.552
971067AG2-660 GEN
Solar/Wind Harmer
1.851
274822ROCKFORD ;11
Adder
15.582
970819AG2-516 GEN
Solar/Wind Harmer
6.574
939401AE1-172 GEN
Solar/Wind Harmer
4.065
970569AG2-363 GEN
Solar/Wind Harmer
16.215
274812UNIV PK N;8U
Adder
3.876
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.123
274766LEE CO EC;7U
Adder
7.039
276708O09 GEN2
Solar/Wind Harmer
0.182
276646AC1-214 GEN2
Solar/Wind Harmer
0.197
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.198
276621W2-048 GEN
Solar/Wind Harmer
0.164
990577J1339
External Queue
10.412999153137207
991777J1629 G
External Queue
9.277681350708008
991247J1684 G
External Queue
9.028225898742676
990582J1340
External Queue
10.412999153137207
990512J1326
External Queue
4.084977626800537
990117J1214
External Queue
14.052322387695312
990727J1377 G
External Queue
4.745286464691162
990762J1386
External Queue
5.909551620483398
991303J1755 G
External Queue
3.5140795707702637
990407J1304
External Queue
3.1611876487731934
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.148
NYPJM->LTFIMP_NY
CLTF
0.728
WECLTFEXP_WEC->PJM
CLTF
3.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.268
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.214
MECLTFEXP_MEC->PJM
CLTF
9.415
SIGELTFEXP_SIGE->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.299
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.33
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.93
LAGNLTFEXP_LAGN->PJM
CLTF
3.083
TVALTFEXP_TVA->PJM
CLTF
0.781

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2973_05DUMONT 345_F1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.57 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1156.57
MW Contribution:
8.1
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.74 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1137.37
MW Contribution:
8.0
Bus #Bus NameTypeMW Contribution
965681AG1-436 GEN
Solar/Wind Harmer
89.404
965791AG1-447 GEN
Solar/Wind Harmer
45.742
274888KELLY CRK;1U
Solar/Wind Harmer
3.871
276776AD2-060 GEN
Solar/Wind Harmer
0.275
958011AF2-095 GEN
Solar/Wind Harmer
9.446
970941AG2-585 GEN
Solar/Wind Harmer
3.608
276893AG1-478 C
Solar/Wind Harmer
0.281
274674JOLIET 9 ;6U
Adder
9.696
958481AF2-142 GEN
Solar/Wind Harmer
9.217
274805UNIV PK N;1U
Adder
3.036
274808UNIV PK N;4U
Adder
3.016
276897AD1-100 C
Solar/Wind Harmer
28.071
274683WAUKEGAN ;8U
Adder
12.67
274683WAUKEGAN ;8U
Adder
10.68
958491AF2-143 GEN
Solar/Wind Harmer
8.995
274696ROCKY RD ;4P
Adder
6.707
274695ROCKY RD ;2P
Adder
6.552
274693ROCKY RD ;1P
Adder
6.487
274697ROCKY RD ;3P
Adder
1.78
276901AD2-066 C O1
Solar/Wind Harmer
2.048
276872AE1-163_GEN1
Solar/Wind Harmer
3.889
276876AE1-163_GEN2
Solar/Wind Harmer
3.889
962691AG1-118 GEN
Solar/Wind Harmer
17.105
960751AF2-366 GEN
Solar/Wind Harmer
1.629
971341AH1-150 GEN
Solar/Wind Harmer
11.099
971343AH1-151 GEN
Solar/Wind Harmer
11.099
972235AH1-702 GEN1
Adder
1.395
972236AH1-702 GEN2
Adder
1.213
938861AE1-114 GEN
Solar/Wind Harmer
4.43
274764LEE CO EC;5U
Adder
5.005
274765LEE CO EC;6U
Adder
5.005
274762LEE CO EC;3U
Adder
4.993
274763LEE CO EC;4U
Adder
4.946
276158O29GEN2
Solar/Wind Harmer
2.608
276157O29GEN1
Solar/Wind Harmer
1.983
276645AC1-214 GEN1
Solar/Wind Harmer
0.685
274770LINCOLN ;1U
Adder
3.125
274771LINCOLN ;2U
Adder
3.125
942111AE2-223 GEN
Solar/Wind Harmer
3.569
274751CRETE EC ;1U
50/50
8.441
274754CRETE EC ;4U
50/50
8.441
274723RIVER EC ;12
Adder
12.317
274861TOP CROP ;1U
Solar/Wind Harmer
4.161
274676JOLIET 29;8U
Adder
20.413
274732ELWOOD EC;7P
Adder
10.844
274802UNIV PARK;5U
Adder
3.731
274674JOLIET 9 ;6U
Adder
9.696
276694AA1-018 GEN2
Solar/Wind Harmer
3.877
276691AA1-018 GEN1
Solar/Wind Harmer
0.463
274871GR RIDGE ;2U
Solar/Wind Harmer
4.663
274847GR RIDGE ;BU
Solar/Wind Harmer
3.066
274812UNIV PK N;8U
Adder
3.029
941551AE2-152 GEN
Solar/Wind Harmer
2.741
274682WAUKEGAN ;7U
Adder
10.834
274828WAUKEGAN ;BP
Adder
6.641
276805AD2-038 GEN
Solar/Wind Harmer
3.075
276882AE2-255 GEN
Solar/Wind Harmer
2.02
274745AC1-111 GEN9
Adder
3.302
962781AG1-127 GEN
Solar/Wind Harmer
5.4
274872LEEDK;1U
Solar/Wind Harmer
4.639
970569AG2-363 GEN
Solar/Wind Harmer
16.954
960681AF2-359 GEN
Solar/Wind Harmer
27.024
274827FISK ;RP
Adder
5.406
274687WILL CNTY;4U
Adder
19.149
274687WILL CNTY;4U
Adder
19.149
972227AH1-698 GEN1
Adder
1.759
972228AH1-698 GEN2
Adder
2.496
274675JOLIET 29;7U
Adder
20.406
274675JOLIET 29;7U
Adder
19.677
274728ELWOOD EC;5P
Adder
10.844
274731ELWOOD EC;2P
Adder
10.827
274733ELWOOD EC;3P
Adder
10.827
274735ELWOOD EC;4P
Adder
10.827
960591AF2-350 GEN
Solar/Wind Harmer
6.56
274800UNIV PARK;3U
Adder
3.805
274801UNIV PARK;4U
Adder
3.805
276893AG1-478 C
Solar/Wind Harmer
0.353
972037AH1-567 GEN1
Adder
0.117
970833AG2-524 GEN
Solar/Wind Harmer
5.301
970833AG2-524 GEN
Solar/Wind Harmer
2.466
970073AG2-061 GEN
Solar/Wind Harmer
1.395
274744AC1-111 GEN8
Adder
3.302
274746AC1-111 G10
Adder
3.302
276889AE2-281 GEN
Solar/Wind Harmer
1.111
971411AH1-196 GEN
Solar/Wind Harmer
8.524
971675AH1-338 GEN
Solar/Wind Harmer
10.027
276861AD2-134 GEN
Solar/Wind Harmer
0.994
276863AD2-134 GEN
Solar/Wind Harmer
0.994
274823ROCKFORD ;21
Adder
10.845
971171AH1-044 GEN
Solar/Wind Harmer
11.099
274856ECOGROVE ;U1
Solar/Wind Harmer
1.849
276611AD2-172 GEN
Solar/Wind Harmer
1.402
276612AE2-035 GEN
Solar/Wind Harmer
1.402
971681AH1-341 GEN
Solar/Wind Harmer
8.099
926823AC1-168 GEN
Solar/Wind Harmer
2.306
972267AH1-718 GEN
Adder
2.189
276741O09 GEN1
Solar/Wind Harmer
1.862
274863CRW1-WTG
Solar/Wind Harmer
2.837
274864CRW2-WTG
Solar/Wind Harmer
2.837
274877BISHOP HL;1U
Solar/Wind Harmer
1.713
274775LINCOLN ;6U
Adder
3.125
274776LINCOLN ;7U
Adder
3.125
274777LINCOLN ;8U
Adder
3.125
946321AF1-296 GEN
Solar/Wind Harmer
5.187
970169AG2-114 GEN
Solar/Wind Harmer
4.911
276726Z2-087_GEN
Solar/Wind Harmer
3.443
959341AF2-225 GEN
Solar/Wind Harmer
6.531
274752CRETE EC ;2U
50/50
8.441
274753CRETE EC ;3U
50/50
8.441
972231SS25-0005
Solar/Wind Harmer
15.445
972181SS23-001
Solar/Wind Harmer
9.653
274826FISK ;BP
Adder
7.628
274724RIVER EC ;11
Adder
12.217
274862TOP CROP ;2U
Solar/Wind Harmer
3.474
276164X3-005 C
Solar/Wind Harmer
0.479
274676JOLIET 29;8U
Adder
19.684
274730ELWOOD EC;6P
Adder
10.844
274734ELWOOD EC;8P
Adder
10.844
274736ELWOOD EC;9P
Adder
10.844
274729ELWOOD EC;1P
Adder
10.827
274887GEN-1.85
Solar/Wind Harmer
3.495
276772AC2-154 GEN
Solar/Wind Harmer
1.831
276843GEN-1.7
Solar/Wind Harmer
0.376
276806AD2-047 C O1
Solar/Wind Harmer
7.017
972038AH1-567 GEN2
Adder
0.238
274803UNIV PARK;6U
Adder
3.731
972259AH1-714 GEN
Adder
11.868
274814UNIV PK N;0U
Adder
3.056
274807UNIV PK N;3U
Adder
3.049
274811UNIV PK N;7U
Adder
3.029
939351AE1-166 GEN
Solar/Wind Harmer
3.584
274682WAUKEGAN ;7U
Adder
10.834
276868AE1-113 GEN
Solar/Wind Harmer
6.061
274879MINONK ;1U
Solar/Wind Harmer
4.041
943121AE2-341 GEN
Solar/Wind Harmer
8.641
943591AF1-030 GEN
Solar/Wind Harmer
5.761
970707AG2-453 GEN
Solar/Wind Harmer
16.065
971997AH1-543 GEN
Solar/Wind Harmer
8.831
274822ROCKFORD ;11
Adder
10.924
957471AF2-041 GEN
Solar/Wind Harmer
16.648
959081AF2-199 GEN
Solar/Wind Harmer
5.549
971067AG2-660 GEN
Solar/Wind Harmer
1.291
970819AG2-516 GEN
Solar/Wind Harmer
6.61
274858EASY ROAD;U2
Solar/Wind Harmer
2.571
274761LEE CO EC;2U
Adder
4.993
274766LEE CO EC;7U
Adder
4.935
939401AE1-172 GEN
Solar/Wind Harmer
7.368
276708O09 GEN2
Solar/Wind Harmer
1.862
276646AC1-214 GEN2
Solar/Wind Harmer
0.685
972207SS24-0001
Solar/Wind Harmer
11.111
274773LINCOLN ;4U
Adder
3.125
274774LINCOLN ;5U
Adder
3.125
274848CAMPGROVE;RU
Solar/Wind Harmer
3.24
276655WTG1_EQ
Solar/Wind Harmer
3.8
276656WTG2_EQ
Solar/Wind Harmer
0.503
939741AE1-205 GEN
Solar/Wind Harmer
8.708
970571AG2-364 GEN
Solar/Wind Harmer
11.302
276799AD1-013 GEN
Solar/Wind Harmer
1.232
946671AF1-331 GEN
Solar/Wind Harmer
0.233
274855GSG-6 ;RU
Solar/Wind Harmer
2.056
274850MENDOTA H;RU
Solar/Wind Harmer
1.429
276602WESTBROOK C
Solar/Wind Harmer
1.183
959091AF2-200 GEN
Solar/Wind Harmer
11.099
274857EASY ROAD;U1
Solar/Wind Harmer
2.571
274760LEE CO EC;1U
Adder
4.993
274767LEE CO EC;8U
Adder
4.935
276603SUBLETTE C
Solar/Wind Harmer
0.559
274851PROVIDENC;RU
Solar/Wind Harmer
1.458
274849CRESCENT ;1U
Solar/Wind Harmer
0.946
276782AC1-033 GEN
Solar/Wind Harmer
2.024
274878BISHOP HL;2U
Solar/Wind Harmer
1.713
274772LINCOLN ;3U
Adder
3.125
965931AG1-462 GEN
Solar/Wind Harmer
12.543
971087AG2-675 GEN
Solar/Wind Harmer
1.83
990577J1339
External Queue
12.515169143676758
991247J1684 G
External Queue
11.840765953063965
990582J1340
External Queue
12.515169143676758
990552J1334 G
External Queue
11.107159614562988
990562J1336 G
External Queue
11.107159614562988
990762J1386
External Queue
6.406259536743164
990547J1333 G
External Queue
11.107159614562988
990557J1335 G
External Queue
11.107159614562988
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.098
NYPJM->LTFIMP_NY
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
2.149
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.202
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.656
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.533
MECLTFEXP_MEC->PJM
CLTF
6.646
SIGELTFEXP_SIGE->PJM
CLTF
0.008
AG2-052LTFEXP_AG2-052->PJM
LTF
0.107
AH1-155LTFEXP_AH1-155->PJM
LTF
0.16
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.222
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.625
LAGNLTFEXP_LAGN->PJM
CLTF
2.185
TVALTFEXP_TVA->PJM
CLTF
0.558

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.3 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1603.8
MW Contribution:
10.83
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.22 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1602.72
MW Contribution:
10.78
Bus #Bus NameTypeMW Contribution
274798UNIV PARK;1U
50/50
0.275
274888KELLY CRK;1U
Solar/Wind Harmer
5.468
958011AF2-095 GEN
Solar/Wind Harmer
13.344
970941AG2-585 GEN
Solar/Wind Harmer
5.096
276776AD2-060 GEN
Solar/Wind Harmer
0.388
274770LINCOLN ;1U
Adder
5.507
274771LINCOLN ;2U
Adder
5.507
274674JOLIET 9 ;6U
Adder
13.476
276893AG1-478 C
Solar/Wind Harmer
0.377
276897AD1-100 C
Solar/Wind Harmer
38.356
274683WAUKEGAN ;8U
Adder
16.703
274683WAUKEGAN ;8U
Adder
14.08
274696ROCKY RD ;4P
Adder
8.994
274695ROCKY RD ;2P
Adder
8.787
274693ROCKY RD ;1P
Adder
8.7
274697ROCKY RD ;3P
Adder
2.387
962691AG1-118 GEN
Solar/Wind Harmer
23.219
960751AF2-366 GEN
Solar/Wind Harmer
2.21
276901AD2-066 C O1
Solar/Wind Harmer
2.677
958481AF2-142 GEN
Solar/Wind Harmer
11.201
971341AH1-150 GEN
Solar/Wind Harmer
14.903
971343AH1-151 GEN
Solar/Wind Harmer
14.903
972235AH1-702 GEN1
Adder
1.865
972236AH1-702 GEN2
Adder
1.621
958491AF2-143 GEN
Solar/Wind Harmer
11.077
276872AE1-163_GEN1
Solar/Wind Harmer
4.882
276876AE1-163_GEN2
Solar/Wind Harmer
4.882
938861AE1-114 GEN
Solar/Wind Harmer
5.918
274764LEE CO EC;5U
Adder
6.684
274765LEE CO EC;6U
Adder
6.684
274762LEE CO EC;3U
Adder
6.668
274763LEE CO EC;4U
Adder
6.605
276158O29GEN2
Solar/Wind Harmer
3.467
276157O29GEN1
Solar/Wind Harmer
2.636
276645AC1-214 GEN1
Solar/Wind Harmer
0.9
942111AE2-223 GEN
Solar/Wind Harmer
4.918
960611AF2-352 GEN
Solar/Wind Harmer
1.327
274805UNIV PK N;1U
Adder
2.604
274808UNIV PK N;4U
Adder
2.587
274880W4-005 GEN4
Solar/Wind Harmer
1.404
276174W4-005 GEN2
Solar/Wind Harmer
1.404
276615X2-022 GEN
Solar/Wind Harmer
0.865
276838X2-022 GEN2
Solar/Wind Harmer
0.103
274827FISK ;RP
50/50
8.684
274799UNIV PARK;2U
50/50
0.284
274800UNIV PARK;3U
50/50
6.317
274801UNIV PARK;4U
50/50
6.317
274687WILL CNTY;4U
50/50
26.585
274687WILL CNTY;4U
50/50
26.585
960591AF2-350 GEN
Solar/Wind Harmer
9.266
274775LINCOLN ;6U
Adder
5.507
274776LINCOLN ;7U
Adder
5.507
274777LINCOLN ;8U
Adder
5.507
276893AG1-478 C
Solar/Wind Harmer
0.473
274675JOLIET 29;7U
Adder
25.747
274675JOLIET 29;7U
Adder
24.828
274728ELWOOD EC;5P
Adder
13.597
274731ELWOOD EC;2P
Adder
13.579
274733ELWOOD EC;3P
Adder
13.579
274735ELWOOD EC;4P
Adder
13.579
972037AH1-567 GEN1
Adder
0.151
972227AH1-698 GEN1
Adder
2.102
972228AH1-698 GEN2
Adder
2.985
274744AC1-111 GEN8
Adder
4.483
274746AC1-111 G10
Adder
4.483
970833AG2-524 GEN
Solar/Wind Harmer
6.954
970833AG2-524 GEN
Solar/Wind Harmer
3.234
971411AH1-196 GEN
Solar/Wind Harmer
11.381
971675AH1-338 GEN
Solar/Wind Harmer
13.555
276861AD2-134 GEN
Solar/Wind Harmer
1.344
276863AD2-134 GEN
Solar/Wind Harmer
1.344
971171AH1-044 GEN
Solar/Wind Harmer
14.903
274823ROCKFORD ;21
Adder
14.49
970073AG2-061 GEN
Solar/Wind Harmer
1.717
274856ECOGROVE ;U1
Solar/Wind Harmer
2.469
276611AD2-172 GEN
Solar/Wind Harmer
1.873
276612AE2-035 GEN
Solar/Wind Harmer
1.873
276889AE2-281 GEN
Solar/Wind Harmer
1.395
971681AH1-341 GEN
Solar/Wind Harmer
10.827
274863CRW1-WTG
Solar/Wind Harmer
3.972
274864CRW2-WTG
Solar/Wind Harmer
3.972
926823AC1-168 GEN
Solar/Wind Harmer
3.018
972267AH1-718 GEN
Adder
2.921
276741O09 GEN1
Solar/Wind Harmer
2.475
970169AG2-114 GEN
Solar/Wind Harmer
6.767
274877BISHOP HL;1U
Solar/Wind Harmer
2.251
946321AF1-296 GEN
Solar/Wind Harmer
6.896
276726Z2-087_GEN
Solar/Wind Harmer
4.743
959341AF2-225 GEN
Solar/Wind Harmer
8.998
274853TWINGROVE;U1
Solar/Wind Harmer
4.112
274854TWINGROVE;U2
Solar/Wind Harmer
4.026
276668AB2-070 GEN1
Solar/Wind Harmer
1.025
276848AB2-070 GEN3
Solar/Wind Harmer
1.025
276849AB2-070 GEN2
Solar/Wind Harmer
1.025
276763AC1-053 GEN1
Solar/Wind Harmer
1.803
276764AC1-053 GEN2
Solar/Wind Harmer
1.803
274826FISK ;BP
50/50
12.253
972038AH1-567 GEN2
50/50
0.395
274887GEN-1.85
Solar/Wind Harmer
4.937
276843GEN-1.7
Solar/Wind Harmer
0.531
276772AC2-154 GEN
Solar/Wind Harmer
2.586
276806AD2-047 C O1
Solar/Wind Harmer
9.912
274772LINCOLN ;3U
Adder
5.507
274862TOP CROP ;2U
Solar/Wind Harmer
4.268
274676JOLIET 29;8U
Adder
24.836
274730ELWOOD EC;6P
Adder
13.597
274734ELWOOD EC;8P
Adder
13.597
274736ELWOOD EC;9P
Adder
13.597
274729ELWOOD EC;1P
Adder
13.579
274803UNIV PARK;6U
Adder
4.814
939351AE1-166 GEN
Solar/Wind Harmer
4.897
970707AG2-453 GEN
Solar/Wind Harmer
22.598
972259AH1-714 GEN
Adder
15.354
943121AE2-341 GEN
Solar/Wind Harmer
11.979
943591AF1-030 GEN
Solar/Wind Harmer
7.986
274682WAUKEGAN ;7U
Adder
14.281
276868AE1-113 GEN
Solar/Wind Harmer
7.732
274879MINONK ;1U
Solar/Wind Harmer
5.155
276799AD1-013 GEN
Solar/Wind Harmer
1.665
946671AF1-331 GEN
Solar/Wind Harmer
0.315
274855GSG-6 ;RU
Solar/Wind Harmer
2.779
274850MENDOTA H;RU
Solar/Wind Harmer
1.932
276602WESTBROOK C
Solar/Wind Harmer
1.6
959091AF2-200 GEN
Solar/Wind Harmer
14.903
970571AG2-364 GEN
Solar/Wind Harmer
14.384
274857EASY ROAD;U1
Solar/Wind Harmer
3.434
274760LEE CO EC;1U
Adder
6.668
274767LEE CO EC;8U
Adder
6.59
276603SUBLETTE C
Solar/Wind Harmer
0.748
276164X3-005 C
Solar/Wind Harmer
0.477
274851PROVIDENC;RU
Solar/Wind Harmer
1.915
274849CRESCENT ;1U
Solar/Wind Harmer
1.243
276782AC1-033 GEN
Solar/Wind Harmer
2.661
274878BISHOP HL;2U
Solar/Wind Harmer
2.251
965931AG1-462 GEN
Solar/Wind Harmer
16.667
971087AG2-675 GEN
Solar/Wind Harmer
2.432
965091AG1-374 GEN
Solar/Wind Harmer
17.122
959611AF2-252 GEN
Solar/Wind Harmer
1.327
274814UNIV PK N;0U
Adder
2.621
274807UNIV PK N;3U
Adder
2.615
274811UNIV PK N;7U
Adder
2.598
276785W4-005 GEN1
Solar/Wind Harmer
1.404
971993AH1-541 GEN
Solar/Wind Harmer
4.291
972207SS24-0001
Solar/Wind Harmer
19.578
274773LINCOLN ;4U
Adder
5.507
274774LINCOLN ;5U
Adder
5.507
274674JOLIET 9 ;6U
Adder
13.476
274861TOP CROP ;1U
Solar/Wind Harmer
5.111
274676JOLIET 29;8U
Adder
25.756
274732ELWOOD EC;7P
Adder
13.597
274802UNIV PARK;5U
Adder
4.814
941551AE2-152 GEN
Solar/Wind Harmer
3.745
274745AC1-111 GEN9
Adder
4.483
274682WAUKEGAN ;7U
Adder
14.281
274828WAUKEGAN ;BP
Adder
8.755
274871GR RIDGE ;2U
Solar/Wind Harmer
6.072
274847GR RIDGE ;BU
Solar/Wind Harmer
3.993
962781AG1-127 GEN
Solar/Wind Harmer
7.327
274872LEEDK;1U
Solar/Wind Harmer
6.294
276882AE2-255 GEN
Solar/Wind Harmer
2.578
276694AA1-018 GEN2
Solar/Wind Harmer
4.712
276691AA1-018 GEN1
Solar/Wind Harmer
0.563
957471AF2-041 GEN
Solar/Wind Harmer
22.354
959081AF2-199 GEN
Solar/Wind Harmer
7.451
971067AG2-660 GEN
Solar/Wind Harmer
1.733
971997AH1-543 GEN
Solar/Wind Harmer
11.723
939401AE1-172 GEN
Solar/Wind Harmer
10.376
274822ROCKFORD ;11
Adder
14.596
276805AD2-038 GEN
Solar/Wind Harmer
3.787
970819AG2-516 GEN
Solar/Wind Harmer
8.826
970569AG2-363 GEN
Solar/Wind Harmer
21.575
274858EASY ROAD;U2
Solar/Wind Harmer
3.434
274761LEE CO EC;2U
Adder
6.668
274766LEE CO EC;7U
Adder
6.59
276708O09 GEN2
Solar/Wind Harmer
2.475
276646AC1-214 GEN2
Solar/Wind Harmer
0.9
274848CAMPGROVE;RU
Solar/Wind Harmer
4.254
276655WTG1_EQ
Solar/Wind Harmer
5.236
276656WTG2_EQ
Solar/Wind Harmer
0.693
939741AE1-205 GEN
Solar/Wind Harmer
11.997
274812UNIV PK N;8U
Adder
2.598
276686W4-005 GEN3
Solar/Wind Harmer
1.404
276621W2-048 GEN
Solar/Wind Harmer
2.755
991777J1629 G
External Queue
9.084226608276367
990512J1326
External Queue
3.9968831539154053
990117J1214
External Queue
13.749277114868164
990727J1377 G
External Queue
4.637833595275879
990407J1304
External Queue
3.088853359222412
NYPJM->LTFIMP_NY
CLTF
0.67
WECLTFEXP_WEC->PJM
CLTF
2.841
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.275
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.136
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.198
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.957
MECLTFEXP_MEC->PJM
CLTF
8.801
SIGELTFEXP_SIGE->PJM
CLTF
0.009
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.32
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.906
LAGNLTFEXP_LAGN->PJM
CLTF
2.871
TVALTFEXP_TVA->PJM
CLTF
0.724

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.29 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1603.7
MW Contribution:
10.83
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.21 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1602.6
MW Contribution:
10.77
Bus #Bus NameTypeMW Contribution
274826FISK ;BP
50/50
12.253
972038AH1-567 GEN2
50/50
0.395
274887GEN-1.85
Solar/Wind Harmer
4.937
276772AC2-154 GEN
Solar/Wind Harmer
2.586
276843GEN-1.7
Solar/Wind Harmer
0.531
276806AD2-047 C O1
Solar/Wind Harmer
9.912
274798UNIV PARK;1U
50/50
0.275
958011AF2-095 GEN
Solar/Wind Harmer
13.344
274888KELLY CRK;1U
Solar/Wind Harmer
5.468
276776AD2-060 GEN
Solar/Wind Harmer
0.388
970941AG2-585 GEN
Solar/Wind Harmer
5.097
274770LINCOLN ;1U
Adder
5.507
274771LINCOLN ;2U
Adder
5.507
274674JOLIET 9 ;6U
Adder
13.476
276893AG1-478 C
Solar/Wind Harmer
0.377
276897AD1-100 C
Solar/Wind Harmer
38.361
274683WAUKEGAN ;8U
Adder
16.701
274683WAUKEGAN ;8U
Adder
14.078
274696ROCKY RD ;4P
Adder
8.993
274695ROCKY RD ;2P
Adder
8.786
274693ROCKY RD ;1P
Adder
8.699
274697ROCKY RD ;3P
Adder
2.387
962691AG1-118 GEN
Solar/Wind Harmer
23.216
960751AF2-366 GEN
Solar/Wind Harmer
2.21
276901AD2-066 C O1
Solar/Wind Harmer
2.677
958481AF2-142 GEN
Solar/Wind Harmer
11.201
971341AH1-150 GEN
Solar/Wind Harmer
14.901
971343AH1-151 GEN
Solar/Wind Harmer
14.901
972235AH1-702 GEN1
Adder
1.864
972236AH1-702 GEN2
Adder
1.621
958491AF2-143 GEN
Solar/Wind Harmer
11.077
276872AE1-163_GEN1
Solar/Wind Harmer
4.882
276876AE1-163_GEN2
Solar/Wind Harmer
4.882
938861AE1-114 GEN
Solar/Wind Harmer
5.917
274764LEE CO EC;5U
Adder
6.683
274765LEE CO EC;6U
Adder
6.683
274762LEE CO EC;3U
Adder
6.668
274763LEE CO EC;4U
Adder
6.605
276158O29GEN2
Solar/Wind Harmer
3.466
276157O29GEN1
Solar/Wind Harmer
2.636
276645AC1-214 GEN1
Solar/Wind Harmer
0.9
942111AE2-223 GEN
Solar/Wind Harmer
4.918
960611AF2-352 GEN
Solar/Wind Harmer
1.327
274805UNIV PK N;1U
Adder
2.604
274808UNIV PK N;4U
Adder
2.587
274880W4-005 GEN4
Solar/Wind Harmer
1.404
276174W4-005 GEN2
Solar/Wind Harmer
1.404
276615X2-022 GEN
Solar/Wind Harmer
0.865
276838X2-022 GEN2
Solar/Wind Harmer
0.103
972207SS24-0001
Solar/Wind Harmer
19.58
274773LINCOLN ;4U
Adder
5.507
274774LINCOLN ;5U
Adder
5.507
274674JOLIET 9 ;6U
Adder
13.476
274861TOP CROP ;1U
Solar/Wind Harmer
5.111
274676JOLIET 29;8U
Adder
25.755
274732ELWOOD EC;7P
Adder
13.596
941551AE2-152 GEN
Solar/Wind Harmer
3.745
274802UNIV PARK;5U
Adder
4.814
274745AC1-111 GEN9
Adder
4.483
274682WAUKEGAN ;7U
Adder
14.279
274828WAUKEGAN ;BP
Adder
8.754
274871GR RIDGE ;2U
Solar/Wind Harmer
6.072
274847GR RIDGE ;BU
Solar/Wind Harmer
3.992
962781AG1-127 GEN
Solar/Wind Harmer
7.326
274872LEEDK;1U
Solar/Wind Harmer
6.293
276882AE2-255 GEN
Solar/Wind Harmer
2.577
276694AA1-018 GEN2
Solar/Wind Harmer
4.712
276691AA1-018 GEN1
Solar/Wind Harmer
0.563
957471AF2-041 GEN
Solar/Wind Harmer
22.351
959081AF2-199 GEN
Solar/Wind Harmer
7.45
971067AG2-660 GEN
Solar/Wind Harmer
1.733
971997AH1-543 GEN
Solar/Wind Harmer
11.722
939401AE1-172 GEN
Solar/Wind Harmer
10.378
274822ROCKFORD ;11
Adder
14.594
276805AD2-038 GEN
Solar/Wind Harmer
3.787
970819AG2-516 GEN
Solar/Wind Harmer
8.825
970569AG2-363 GEN
Solar/Wind Harmer
21.574
274858EASY ROAD;U2
Solar/Wind Harmer
3.433
274761LEE CO EC;2U
Adder
6.668
274766LEE CO EC;7U
Adder
6.589
276708O09 GEN2
Solar/Wind Harmer
2.475
276646AC1-214 GEN2
Solar/Wind Harmer
0.9
274848CAMPGROVE;RU
Solar/Wind Harmer
4.253
276655WTG1_EQ
Solar/Wind Harmer
5.236
276656WTG2_EQ
Solar/Wind Harmer
0.693
939741AE1-205 GEN
Solar/Wind Harmer
11.998
274812UNIV PK N;8U
Adder
2.598
276686W4-005 GEN3
Solar/Wind Harmer
1.404
276621W2-048 GEN
Solar/Wind Harmer
2.755
274827FISK ;RP
50/50
8.684
274799UNIV PARK;2U
50/50
0.284
274800UNIV PARK;3U
50/50
6.317
274801UNIV PARK;4U
50/50
6.317
274687WILL CNTY;4U
50/50
26.585
274687WILL CNTY;4U
50/50
26.585
960591AF2-350 GEN
Solar/Wind Harmer
9.266
274775LINCOLN ;6U
Adder
5.507
274776LINCOLN ;7U
Adder
5.507
274777LINCOLN ;8U
Adder
5.507
276893AG1-478 C
Solar/Wind Harmer
0.473
274675JOLIET 29;7U
Adder
25.746
274675JOLIET 29;7U
Adder
24.827
274728ELWOOD EC;5P
Adder
13.596
274731ELWOOD EC;2P
Adder
13.578
274733ELWOOD EC;3P
Adder
13.578
274735ELWOOD EC;4P
Adder
13.578
972037AH1-567 GEN1
Adder
0.151
972227AH1-698 GEN1
Adder
2.102
972228AH1-698 GEN2
Adder
2.985
274744AC1-111 GEN8
Adder
4.483
274746AC1-111 G10
Adder
4.483
970833AG2-524 GEN
Solar/Wind Harmer
6.953
970833AG2-524 GEN
Solar/Wind Harmer
3.234
971411AH1-196 GEN
Solar/Wind Harmer
11.38
971675AH1-338 GEN
Solar/Wind Harmer
13.553
276861AD2-134 GEN
Solar/Wind Harmer
1.343
276863AD2-134 GEN
Solar/Wind Harmer
1.343
971171AH1-044 GEN
Solar/Wind Harmer
14.901
274823ROCKFORD ;21
Adder
14.489
970073AG2-061 GEN
Solar/Wind Harmer
1.717
274856ECOGROVE ;U1
Solar/Wind Harmer
2.469
276611AD2-172 GEN
Solar/Wind Harmer
1.873
276612AE2-035 GEN
Solar/Wind Harmer
1.873
276889AE2-281 GEN
Solar/Wind Harmer
1.395
971681AH1-341 GEN
Solar/Wind Harmer
10.826
274863CRW1-WTG
Solar/Wind Harmer
3.973
274864CRW2-WTG
Solar/Wind Harmer
3.973
926823AC1-168 GEN
Solar/Wind Harmer
3.018
972267AH1-718 GEN
Adder
2.921
276741O09 GEN1
Solar/Wind Harmer
2.475
970169AG2-114 GEN
Solar/Wind Harmer
6.767
274877BISHOP HL;1U
Solar/Wind Harmer
2.251
946321AF1-296 GEN
Solar/Wind Harmer
6.895
276726Z2-087_GEN
Solar/Wind Harmer
4.743
959341AF2-225 GEN
Solar/Wind Harmer
8.998
274853TWINGROVE;U1
Solar/Wind Harmer
4.112
274854TWINGROVE;U2
Solar/Wind Harmer
4.026
276668AB2-070 GEN1
Solar/Wind Harmer
1.025
276848AB2-070 GEN3
Solar/Wind Harmer
1.025
276849AB2-070 GEN2
Solar/Wind Harmer
1.025
276763AC1-053 GEN1
Solar/Wind Harmer
1.803
276764AC1-053 GEN2
Solar/Wind Harmer
1.803
274772LINCOLN ;3U
Adder
5.507
274862TOP CROP ;2U
Solar/Wind Harmer
4.268
274676JOLIET 29;8U
Adder
24.835
274730ELWOOD EC;6P
Adder
13.596
274734ELWOOD EC;8P
Adder
13.596
274736ELWOOD EC;9P
Adder
13.596
274729ELWOOD EC;1P
Adder
13.578
939351AE1-166 GEN
Solar/Wind Harmer
4.897
274803UNIV PARK;6U
Adder
4.814
970707AG2-453 GEN
Solar/Wind Harmer
22.594
972259AH1-714 GEN
Adder
15.353
943121AE2-341 GEN
Solar/Wind Harmer
11.977
943591AF1-030 GEN
Solar/Wind Harmer
7.985
274682WAUKEGAN ;7U
Adder
14.279
276868AE1-113 GEN
Solar/Wind Harmer
7.732
274879MINONK ;1U
Solar/Wind Harmer
5.155
276799AD1-013 GEN
Solar/Wind Harmer
1.665
946671AF1-331 GEN
Solar/Wind Harmer
0.315
274855GSG-6 ;RU
Solar/Wind Harmer
2.778
274850MENDOTA H;RU
Solar/Wind Harmer
1.932
276602WESTBROOK C
Solar/Wind Harmer
1.599
959091AF2-200 GEN
Solar/Wind Harmer
14.901
970571AG2-364 GEN
Solar/Wind Harmer
14.383
274857EASY ROAD;U1
Solar/Wind Harmer
3.433
274760LEE CO EC;1U
Adder
6.668
274767LEE CO EC;8U
Adder
6.589
276603SUBLETTE C
Solar/Wind Harmer
0.748
276164X3-005 C
Solar/Wind Harmer
0.477
274851PROVIDENC;RU
Solar/Wind Harmer
1.915
274849CRESCENT ;1U
Solar/Wind Harmer
1.243
276782AC1-033 GEN
Solar/Wind Harmer
2.661
274878BISHOP HL;2U
Solar/Wind Harmer
2.251
965931AG1-462 GEN
Solar/Wind Harmer
16.665
971087AG2-675 GEN
Solar/Wind Harmer
2.432
965091AG1-374 GEN
Solar/Wind Harmer
17.122
959611AF2-252 GEN
Solar/Wind Harmer
1.327
274814UNIV PK N;0U
Adder
2.621
274807UNIV PK N;3U
Adder
2.615
274811UNIV PK N;7U
Adder
2.598
276785W4-005 GEN1
Solar/Wind Harmer
1.404
971993AH1-541 GEN
Solar/Wind Harmer
4.291
991777J1629 G
External Queue
9.08325481414795
990512J1326
External Queue
3.9964282512664795
990117J1214
External Queue
13.747712135314941
990727J1377 G
External Queue
4.637286186218262
990407J1304
External Queue
3.088493824005127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.136
NYPJM->LTFIMP_NY
CLTF
0.67
WECLTFEXP_WEC->PJM
CLTF
2.841
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.275
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.194
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.957
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.555
MECLTFEXP_MEC->PJM
CLTF
8.8
SIGELTFEXP_SIGE->PJM
CLTF
0.009
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.32
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.906
LAGNLTFEXP_LAGN->PJM
CLTF
2.871
TVALTFEXP_TVA->PJM
CLTF
0.724

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.45 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1591.55
MW Contribution:
10.75
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.81 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1596.7
MW Contribution:
10.72
Bus #Bus NameTypeMW Contribution
274827FISK ;RP
50/50
8.619
274799UNIV PARK;2U
50/50
0.282
274800UNIV PARK;3U
50/50
6.27
274801UNIV PARK;4U
50/50
6.27
274687WILL CNTY;4U
50/50
26.375
274687WILL CNTY;4U
50/50
26.375
960591AF2-350 GEN
Solar/Wind Harmer
9.187
274775LINCOLN ;6U
Adder
5.435
274776LINCOLN ;7U
Adder
5.435
274777LINCOLN ;8U
Adder
5.435
276893AG1-478 C
Solar/Wind Harmer
0.469
274675JOLIET 29;7U
Adder
25.538
274675JOLIET 29;7U
Adder
24.626
274728ELWOOD EC;5P
Adder
13.485
274731ELWOOD EC;2P
Adder
13.467
274733ELWOOD EC;3P
Adder
13.467
274735ELWOOD EC;4P
Adder
13.467
972037AH1-567 GEN1
Adder
0.15
972227AH1-698 GEN1
Adder
2.082
972228AH1-698 GEN2
Adder
2.957
274744AC1-111 GEN8
Adder
4.452
274746AC1-111 G10
Adder
4.452
274826FISK ;BP
50/50
12.162
972038AH1-567 GEN2
50/50
0.392
274887GEN-1.85
Solar/Wind Harmer
4.895
276843GEN-1.7
Solar/Wind Harmer
0.527
276772AC2-154 GEN
Solar/Wind Harmer
2.564
276806AD2-047 C O1
Solar/Wind Harmer
9.827
274772LINCOLN ;3U
Adder
5.435
274862TOP CROP ;2U
Solar/Wind Harmer
4.233
274676JOLIET 29;8U
Adder
24.634
274730ELWOOD EC;6P
Adder
13.485
274734ELWOOD EC;8P
Adder
13.485
274736ELWOOD EC;9P
Adder
13.485
274729ELWOOD EC;1P
Adder
13.467
274803UNIV PARK;6U
Adder
4.768
939351AE1-166 GEN
Solar/Wind Harmer
4.847
970707AG2-453 GEN
Solar/Wind Harmer
22.462
972259AH1-714 GEN
Adder
15.236
943121AE2-341 GEN
Solar/Wind Harmer
11.902
943591AF1-030 GEN
Solar/Wind Harmer
7.934
274682WAUKEGAN ;7U
Adder
14.175
276868AE1-113 GEN
Solar/Wind Harmer
7.67
274879MINONK ;1U
Solar/Wind Harmer
5.113
276799AD1-013 GEN
Solar/Wind Harmer
1.653
946671AF1-331 GEN
Solar/Wind Harmer
0.313
274855GSG-6 ;RU
Solar/Wind Harmer
2.759
274850MENDOTA H;RU
Solar/Wind Harmer
1.918
276602WESTBROOK C
Solar/Wind Harmer
1.588
959091AF2-200 GEN
Solar/Wind Harmer
14.797
970571AG2-364 GEN
Solar/Wind Harmer
14.265
274857EASY ROAD;U1
Solar/Wind Harmer
3.409
274760LEE CO EC;1U
Adder
6.62
274767LEE CO EC;8U
Adder
6.542
276603SUBLETTE C
Solar/Wind Harmer
0.742
276164X3-005 C
Solar/Wind Harmer
0.471
274851PROVIDENC;RU
Solar/Wind Harmer
1.9
274849CRESCENT ;1U
Solar/Wind Harmer
1.233
276782AC1-033 GEN
Solar/Wind Harmer
2.64
274878BISHOP HL;2U
Solar/Wind Harmer
2.234
965931AG1-462 GEN
Solar/Wind Harmer
16.542
971087AG2-675 GEN
Solar/Wind Harmer
2.414
965091AG1-374 GEN
Solar/Wind Harmer
16.963
959611AF2-252 GEN
Solar/Wind Harmer
1.315
274814UNIV PK N;0U
Adder
2.58
274807UNIV PK N;3U
Adder
2.575
274811UNIV PK N;7U
Adder
2.558
276785W4-005 GEN1
Solar/Wind Harmer
1.391
971993AH1-541 GEN
Solar/Wind Harmer
4.25
274798UNIV PARK;1U
50/50
0.273
958011AF2-095 GEN
Solar/Wind Harmer
13.23
274888KELLY CRK;1U
Solar/Wind Harmer
5.421
970941AG2-585 GEN
Solar/Wind Harmer
5.053
276776AD2-060 GEN
Solar/Wind Harmer
0.385
274770LINCOLN ;1U
Adder
5.435
274771LINCOLN ;2U
Adder
5.435
274674JOLIET 9 ;6U
Adder
13.374
276893AG1-478 C
Solar/Wind Harmer
0.374
276897AD1-100 C
Solar/Wind Harmer
37.967
274683WAUKEGAN ;8U
Adder
16.579
274683WAUKEGAN ;8U
Adder
13.975
274696ROCKY RD ;4P
Adder
8.93
274695ROCKY RD ;2P
Adder
8.724
274693ROCKY RD ;1P
Adder
8.638
274697ROCKY RD ;3P
Adder
2.37
962691AG1-118 GEN
Solar/Wind Harmer
23.059
960751AF2-366 GEN
Solar/Wind Harmer
2.195
276901AD2-066 C O1
Solar/Wind Harmer
2.655
971341AH1-150 GEN
Solar/Wind Harmer
14.797
971343AH1-151 GEN
Solar/Wind Harmer
14.797
958481AF2-142 GEN
Solar/Wind Harmer
11.098
972235AH1-702 GEN1
Adder
1.851
972236AH1-702 GEN2
Adder
1.61
958491AF2-143 GEN
Solar/Wind Harmer
10.978
276872AE1-163_GEN1
Solar/Wind Harmer
4.841
276876AE1-163_GEN2
Solar/Wind Harmer
4.841
938861AE1-114 GEN
Solar/Wind Harmer
5.875
274764LEE CO EC;5U
Adder
6.635
274765LEE CO EC;6U
Adder
6.635
274762LEE CO EC;3U
Adder
6.62
274763LEE CO EC;4U
Adder
6.557
276158O29GEN2
Solar/Wind Harmer
3.441
276157O29GEN1
Solar/Wind Harmer
2.616
276645AC1-214 GEN1
Solar/Wind Harmer
0.893
942111AE2-223 GEN
Solar/Wind Harmer
4.872
972207SS24-0001
Solar/Wind Harmer
19.322
274773LINCOLN ;4U
Adder
5.435
274774LINCOLN ;5U
Adder
5.435
274674JOLIET 9 ;6U
Adder
13.374
274861TOP CROP ;1U
Solar/Wind Harmer
5.069
274676JOLIET 29;8U
Adder
25.547
274732ELWOOD EC;7P
Adder
13.485
274802UNIV PARK;5U
Adder
4.768
941551AE2-152 GEN
Solar/Wind Harmer
3.707
274745AC1-111 GEN9
Adder
4.452
274682WAUKEGAN ;7U
Adder
14.175
274828WAUKEGAN ;BP
Adder
8.69
274871GR RIDGE ;2U
Solar/Wind Harmer
6.025
274847GR RIDGE ;BU
Solar/Wind Harmer
3.962
962781AG1-127 GEN
Solar/Wind Harmer
7.276
274872LEEDK;1U
Solar/Wind Harmer
6.251
276882AE2-255 GEN
Solar/Wind Harmer
2.557
276694AA1-018 GEN2
Solar/Wind Harmer
4.668
957471AF2-041 GEN
Solar/Wind Harmer
22.195
959081AF2-199 GEN
Solar/Wind Harmer
7.398
971067AG2-660 GEN
Solar/Wind Harmer
1.721
276691AA1-018 GEN1
Solar/Wind Harmer
0.558
971997AH1-543 GEN
Solar/Wind Harmer
11.634
274822ROCKFORD ;11
Adder
14.491
939401AE1-172 GEN
Solar/Wind Harmer
10.272
276805AD2-038 GEN
Solar/Wind Harmer
3.753
970819AG2-516 GEN
Solar/Wind Harmer
8.762
970569AG2-363 GEN
Solar/Wind Harmer
21.398
274858EASY ROAD;U2
Solar/Wind Harmer
3.409
274761LEE CO EC;2U
Adder
6.62
274766LEE CO EC;7U
Adder
6.542
276708O09 GEN2
Solar/Wind Harmer
2.457
276646AC1-214 GEN2
Solar/Wind Harmer
0.893
274848CAMPGROVE;RU
Solar/Wind Harmer
4.22
276655WTG1_EQ
Solar/Wind Harmer
5.187
276656WTG2_EQ
Solar/Wind Harmer
0.687
939741AE1-205 GEN
Solar/Wind Harmer
11.886
274812UNIV PK N;8U
Adder
2.558
276686W4-005 GEN3
Solar/Wind Harmer
1.391
276621W2-048 GEN
Solar/Wind Harmer
2.729
970833AG2-524 GEN
Solar/Wind Harmer
6.9
970833AG2-524 GEN
Solar/Wind Harmer
3.209
971411AH1-196 GEN
Solar/Wind Harmer
11.299
971675AH1-338 GEN
Solar/Wind Harmer
13.46
276861AD2-134 GEN
Solar/Wind Harmer
1.334
276863AD2-134 GEN
Solar/Wind Harmer
1.334
971171AH1-044 GEN
Solar/Wind Harmer
14.797
274823ROCKFORD ;21
Adder
14.386
970073AG2-061 GEN
Solar/Wind Harmer
1.702
274856ECOGROVE ;U1
Solar/Wind Harmer
2.452
276611AD2-172 GEN
Solar/Wind Harmer
1.86
276612AE2-035 GEN
Solar/Wind Harmer
1.86
276889AE2-281 GEN
Solar/Wind Harmer
1.383
971681AH1-341 GEN
Solar/Wind Harmer
10.748
274863CRW1-WTG
Solar/Wind Harmer
3.933
274864CRW2-WTG
Solar/Wind Harmer
3.933
926823AC1-168 GEN
Solar/Wind Harmer
2.994
972267AH1-718 GEN
Adder
2.9
276741O09 GEN1
Solar/Wind Harmer
2.457
970169AG2-114 GEN
Solar/Wind Harmer
6.707
274877BISHOP HL;1U
Solar/Wind Harmer
2.234
946321AF1-296 GEN
Solar/Wind Harmer
6.845
276726Z2-087_GEN
Solar/Wind Harmer
4.699
959341AF2-225 GEN
Solar/Wind Harmer
8.915
274853TWINGROVE;U1
Solar/Wind Harmer
4.074
274854TWINGROVE;U2
Solar/Wind Harmer
3.988
276668AB2-070 GEN1
Solar/Wind Harmer
1.016
276848AB2-070 GEN3
Solar/Wind Harmer
1.016
276849AB2-070 GEN2
Solar/Wind Harmer
1.016
276763AC1-053 GEN1
Solar/Wind Harmer
1.787
276764AC1-053 GEN2
Solar/Wind Harmer
1.787
960611AF2-352 GEN
Solar/Wind Harmer
1.315
274805UNIV PK N;1U
Adder
2.563
274808UNIV PK N;4U
Adder
2.547
274880W4-005 GEN4
Solar/Wind Harmer
1.391
276174W4-005 GEN2
Solar/Wind Harmer
1.391
276615X2-022 GEN
Solar/Wind Harmer
0.857
276838X2-022 GEN2
Solar/Wind Harmer
0.102
991777J1629 G
External Queue
9.047310829162598
990512J1326
External Queue
3.9808859825134277
990117J1214
External Queue
13.694247245788574
990727J1377 G
External Queue
4.619176864624023
990407J1304
External Queue
3.0762712955474854
NYPJM->LTFIMP_NY
CLTF
0.664
WECLTFEXP_WEC->PJM
CLTF
2.82
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.271
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
40.602
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.373
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.945
MECLTFEXP_MEC->PJM
CLTF
8.734
SIGELTFEXP_SIGE->PJM
CLTF
0.008
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.316
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.896
LAGNLTFEXP_LAGN->PJM
CLTF
2.849
TVALTFEXP_TVA->PJM
CLTF
0.719

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.53 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1578.35
MW Contribution:
10.67
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.68 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1609.25
MW Contribution:
10.74
Bus #Bus NameTypeMW Contribution
274798UNIV PARK;1U
50/50
0.271
274827FISK ;RP
50/50
8.554
274799UNIV PARK;2U
50/50
0.279
274800UNIV PARK;3U
50/50
6.221
274801UNIV PARK;4U
50/50
6.221
274687WILL CNTY;4U
50/50
26.153
274687WILL CNTY;4U
50/50
26.153
960591AF2-350 GEN
Solar/Wind Harmer
9.11
274826FISK ;BP
50/50
12.069
972038AH1-567 GEN2
50/50
0.389
274887GEN-1.85
Solar/Wind Harmer
4.854
276843GEN-1.7
Solar/Wind Harmer
0.522
276772AC2-154 GEN
Solar/Wind Harmer
2.542
276806AD2-047 C O1
Solar/Wind Harmer
9.745
274772LINCOLN ;3U
Adder
5.389
274862TOP CROP ;2U
Solar/Wind Harmer
4.199
274676JOLIET 29;8U
Adder
24.417
274730ELWOOD EC;6P
Adder
13.366
274734ELWOOD EC;8P
Adder
13.366
274736ELWOOD EC;9P
Adder
13.366
274729ELWOOD EC;1P
Adder
13.349
939351AE1-166 GEN
Solar/Wind Harmer
4.805
274803UNIV PARK;6U
Adder
4.722
970707AG2-453 GEN
Solar/Wind Harmer
22.263
972259AH1-714 GEN
Adder
15.098
943121AE2-341 GEN
Solar/Wind Harmer
11.801
943591AF1-030 GEN
Solar/Wind Harmer
7.867
274682WAUKEGAN ;7U
Adder
14.056
276868AE1-113 GEN
Solar/Wind Harmer
7.608
274879MINONK ;1U
Solar/Wind Harmer
5.072
276799AD1-013 GEN
Solar/Wind Harmer
1.64
946671AF1-331 GEN
Solar/Wind Harmer
0.311
274855GSG-6 ;RU
Solar/Wind Harmer
2.737
274850MENDOTA H;RU
Solar/Wind Harmer
1.903
276602WESTBROOK C
Solar/Wind Harmer
1.576
959091AF2-200 GEN
Solar/Wind Harmer
14.68
970571AG2-364 GEN
Solar/Wind Harmer
14.158
274857EASY ROAD;U1
Solar/Wind Harmer
3.383
274760LEE CO EC;1U
Adder
6.57
274767LEE CO EC;8U
Adder
6.492
276603SUBLETTE C
Solar/Wind Harmer
0.737
274851PROVIDENC;RU
Solar/Wind Harmer
1.886
274849CRESCENT ;1U
Solar/Wind Harmer
1.225
276164X3-005 C
Solar/Wind Harmer
0.465
276782AC1-033 GEN
Solar/Wind Harmer
2.622
274878BISHOP HL;2U
Solar/Wind Harmer
2.218
965931AG1-462 GEN
Solar/Wind Harmer
16.43
971087AG2-675 GEN
Solar/Wind Harmer
2.398
965091AG1-374 GEN
Solar/Wind Harmer
16.885
959611AF2-252 GEN
Solar/Wind Harmer
1.309
274814UNIV PK N;0U
Adder
2.536
274807UNIV PK N;3U
Adder
2.531
274811UNIV PK N;7U
Adder
2.514
276785W4-005 GEN1
Solar/Wind Harmer
1.389
971993AH1-541 GEN
Solar/Wind Harmer
4.244
274888KELLY CRK;1U
Solar/Wind Harmer
5.376
958011AF2-095 GEN
Solar/Wind Harmer
13.119
970941AG2-585 GEN
Solar/Wind Harmer
5.011
276776AD2-060 GEN
Solar/Wind Harmer
0.381
274770LINCOLN ;1U
Adder
5.389
274771LINCOLN ;2U
Adder
5.389
274674JOLIET 9 ;6U
Adder
13.263
276893AG1-478 C
Solar/Wind Harmer
0.371
276897AD1-100 C
Solar/Wind Harmer
37.641
274683WAUKEGAN ;8U
Adder
16.441
274683WAUKEGAN ;8U
Adder
13.859
274696ROCKY RD ;4P
Adder
8.855
274695ROCKY RD ;2P
Adder
8.651
274693ROCKY RD ;1P
Adder
8.566
274697ROCKY RD ;3P
Adder
2.35
962691AG1-118 GEN
Solar/Wind Harmer
22.869
960751AF2-366 GEN
Solar/Wind Harmer
2.177
276901AD2-066 C O1
Solar/Wind Harmer
2.634
971341AH1-150 GEN
Solar/Wind Harmer
14.68
971343AH1-151 GEN
Solar/Wind Harmer
14.68
958481AF2-142 GEN
Solar/Wind Harmer
10.997
972235AH1-702 GEN1
Adder
1.837
972236AH1-702 GEN2
Adder
1.597
958491AF2-143 GEN
Solar/Wind Harmer
10.883
276872AE1-163_GEN1
Solar/Wind Harmer
4.802
276876AE1-163_GEN2
Solar/Wind Harmer
4.802
938861AE1-114 GEN
Solar/Wind Harmer
5.83
274764LEE CO EC;5U
Adder
6.585
274765LEE CO EC;6U
Adder
6.585
274762LEE CO EC;3U
Adder
6.57
274763LEE CO EC;4U
Adder
6.508
276158O29GEN2
Solar/Wind Harmer
3.416
276157O29GEN1
Solar/Wind Harmer
2.597
276645AC1-214 GEN1
Solar/Wind Harmer
0.887
942111AE2-223 GEN
Solar/Wind Harmer
4.847
960611AF2-352 GEN
Solar/Wind Harmer
1.309
274805UNIV PK N;1U
Adder
2.52
274808UNIV PK N;4U
Adder
2.503
274880W4-005 GEN4
Solar/Wind Harmer
1.389
276174W4-005 GEN2
Solar/Wind Harmer
1.389
276615X2-022 GEN
Solar/Wind Harmer
0.856
276838X2-022 GEN2
Solar/Wind Harmer
0.102
972207SS24-0001
Solar/Wind Harmer
19.16
274773LINCOLN ;4U
Adder
5.389
274774LINCOLN ;5U
Adder
5.389
274674JOLIET 9 ;6U
Adder
13.263
274861TOP CROP ;1U
Solar/Wind Harmer
5.028
274676JOLIET 29;8U
Adder
25.321
274732ELWOOD EC;7P
Adder
13.366
941551AE2-152 GEN
Solar/Wind Harmer
3.675
274802UNIV PARK;5U
Adder
4.722
274745AC1-111 GEN9
Adder
4.415
274682WAUKEGAN ;7U
Adder
14.056
274828WAUKEGAN ;BP
Adder
8.618
274871GR RIDGE ;2U
Solar/Wind Harmer
5.973
274847GR RIDGE ;BU
Solar/Wind Harmer
3.927
962781AG1-127 GEN
Solar/Wind Harmer
7.216
274872LEEDK;1U
Solar/Wind Harmer
6.2
276882AE2-255 GEN
Solar/Wind Harmer
2.536
957471AF2-041 GEN
Solar/Wind Harmer
22.019
959081AF2-199 GEN
Solar/Wind Harmer
7.34
971067AG2-660 GEN
Solar/Wind Harmer
1.707
971997AH1-543 GEN
Solar/Wind Harmer
11.543
276694AA1-018 GEN2
Solar/Wind Harmer
4.626
276691AA1-018 GEN1
Solar/Wind Harmer
0.553
274822ROCKFORD ;11
Adder
14.376
939401AE1-172 GEN
Solar/Wind Harmer
10.195
276805AD2-038 GEN
Solar/Wind Harmer
3.721
970819AG2-516 GEN
Solar/Wind Harmer
8.694
970569AG2-363 GEN
Solar/Wind Harmer
21.237
274858EASY ROAD;U2
Solar/Wind Harmer
3.383
274761LEE CO EC;2U
Adder
6.57
274766LEE CO EC;7U
Adder
6.492
276708O09 GEN2
Solar/Wind Harmer
2.439
276646AC1-214 GEN2
Solar/Wind Harmer
0.887
274848CAMPGROVE;RU
Solar/Wind Harmer
4.192
276655WTG1_EQ
Solar/Wind Harmer
5.16
276656WTG2_EQ
Solar/Wind Harmer
0.683
939741AE1-205 GEN
Solar/Wind Harmer
11.825
274812UNIV PK N;8U
Adder
2.514
276686W4-005 GEN3
Solar/Wind Harmer
1.389
276621W2-048 GEN
Solar/Wind Harmer
2.727
274775LINCOLN ;6U
Adder
5.389
274776LINCOLN ;7U
Adder
5.389
274777LINCOLN ;8U
Adder
5.389
276893AG1-478 C
Solar/Wind Harmer
0.465
274675JOLIET 29;7U
Adder
25.312
274675JOLIET 29;7U
Adder
24.408
274728ELWOOD EC;5P
Adder
13.366
274731ELWOOD EC;2P
Adder
13.349
274733ELWOOD EC;3P
Adder
13.349
274735ELWOOD EC;4P
Adder
13.349
972037AH1-567 GEN1
Adder
0.148
972227AH1-698 GEN1
Adder
2.063
972228AH1-698 GEN2
Adder
2.929
274744AC1-111 GEN8
Adder
4.415
274746AC1-111 G10
Adder
4.415
970833AG2-524 GEN
Solar/Wind Harmer
6.84
970833AG2-524 GEN
Solar/Wind Harmer
3.181
971411AH1-196 GEN
Solar/Wind Harmer
11.208
971675AH1-338 GEN
Solar/Wind Harmer
13.352
276861AD2-134 GEN
Solar/Wind Harmer
1.324
276863AD2-134 GEN
Solar/Wind Harmer
1.324
971171AH1-044 GEN
Solar/Wind Harmer
14.68
274823ROCKFORD ;21
Adder
14.272
970073AG2-061 GEN
Solar/Wind Harmer
1.687
274856ECOGROVE ;U1
Solar/Wind Harmer
2.433
276611AD2-172 GEN
Solar/Wind Harmer
1.845
276612AE2-035 GEN
Solar/Wind Harmer
1.845
276889AE2-281 GEN
Solar/Wind Harmer
1.372
971681AH1-341 GEN
Solar/Wind Harmer
10.666
274863CRW1-WTG
Solar/Wind Harmer
3.906
274864CRW2-WTG
Solar/Wind Harmer
3.906
926823AC1-168 GEN
Solar/Wind Harmer
2.972
972267AH1-718 GEN
Adder
2.879
276741O09 GEN1
Solar/Wind Harmer
2.439
970169AG2-114 GEN
Solar/Wind Harmer
6.663
274877BISHOP HL;1U
Solar/Wind Harmer
2.218
946321AF1-296 GEN
Solar/Wind Harmer
6.798
276726Z2-087_GEN
Solar/Wind Harmer
4.675
959341AF2-225 GEN
Solar/Wind Harmer
8.869
274853TWINGROVE;U1
Solar/Wind Harmer
4.055
274854TWINGROVE;U2
Solar/Wind Harmer
3.97
276668AB2-070 GEN1
Solar/Wind Harmer
1.014
276848AB2-070 GEN3
Solar/Wind Harmer
1.014
276849AB2-070 GEN2
Solar/Wind Harmer
1.014
276763AC1-053 GEN1
Solar/Wind Harmer
1.784
276764AC1-053 GEN2
Solar/Wind Harmer
1.784
991777J1629 G
External Queue
9.02009391784668
990512J1326
External Queue
3.9684760570526123
990117J1214
External Queue
13.651556968688965
990727J1377 G
External Queue
4.603269577026367
990407J1304
External Queue
3.0653138160705566
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
NYPJM->LTFIMP_NY
CLTF
0.655
WECLTFEXP_WEC->PJM
CLTF
2.798
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.542
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.092
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.773
MECLTFEXP_MEC->PJM
CLTF
8.693
SIGELTFEXP_SIGE->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.252
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.267
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.747
LAGNLTFEXP_LAGN->PJM
CLTF
2.898
TVALTFEXP_TVA->PJM
CLTF
0.752

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.38 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1561.79
MW Contribution:
10.12
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.22 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1588.29
MW Contribution:
10.23
Bus #Bus NameTypeMW Contribution
274802UNIV PARK;5U
50/50
5.457
274751CRETE EC ;1U
Adder
4.318
274754CRETE EC ;4U
Adder
4.318
274861TOP CROP ;1U
Solar/Wind Harmer
5.174
274674JOLIET 9 ;6U
Adder
12.91
274676JOLIET 29;8U
Adder
25.414
274732ELWOOD EC;7P
Adder
13.414
274812UNIV PK N;8U
Adder
3.883
941551AE2-152 GEN
Solar/Wind Harmer
3.444
274682WAUKEGAN ;7U
Adder
13.565
274828WAUKEGAN ;BP
Adder
8.315
276694AA1-018 GEN2
Solar/Wind Harmer
4.699
276691AA1-018 GEN1
Solar/Wind Harmer
0.562
276882AE2-255 GEN
Solar/Wind Harmer
2.509
274871GR RIDGE ;2U
Solar/Wind Harmer
5.705
274847GR RIDGE ;BU
Solar/Wind Harmer
3.751
274745AC1-111 GEN9
Adder
4.144
276805AD2-038 GEN
Solar/Wind Harmer
3.749
962781AG1-127 GEN
Solar/Wind Harmer
6.771
274872LEEDK;1U
Solar/Wind Harmer
5.816
971997AH1-543 GEN
Solar/Wind Harmer
11.006
970569AG2-363 GEN
Solar/Wind Harmer
20.969
274822ROCKFORD ;11
Adder
13.663
957471AF2-041 GEN
Solar/Wind Harmer
20.823
959081AF2-199 GEN
Solar/Wind Harmer
6.941
971067AG2-660 GEN
Solar/Wind Harmer
1.614
970819AG2-516 GEN
Solar/Wind Harmer
8.265
972207SS24-0001
Solar/Wind Harmer
15.033
274773LINCOLN ;4U
Adder
4.228
274774LINCOLN ;5U
Adder
4.228
274858EASY ROAD;U2
Solar/Wind Harmer
3.212
274761LEE CO EC;2U
Adder
6.238
274766LEE CO EC;7U
Adder
6.164
939401AE1-172 GEN
Solar/Wind Harmer
9.306
276708O09 GEN2
Solar/Wind Harmer
2.321
276646AC1-214 GEN2
Solar/Wind Harmer
0.851
274848CAMPGROVE;RU
Solar/Wind Harmer
4.019
276655WTG1_EQ
Solar/Wind Harmer
4.736
276656WTG2_EQ
Solar/Wind Harmer
0.627
939741AE1-205 GEN
Solar/Wind Harmer
10.852
274798UNIV PARK;1U
50/50
0.265
274888KELLY CRK;1U
Solar/Wind Harmer
5.256
276776AD2-060 GEN
Solar/Wind Harmer
0.373
958011AF2-095 GEN
Solar/Wind Harmer
12.826
970941AG2-585 GEN
Solar/Wind Harmer
4.899
274674JOLIET 9 ;6U
Adder
12.91
276893AG1-478 C
Solar/Wind Harmer
0.365
274805UNIV PK N;1U
Adder
3.891
274808UNIV PK N;4U
Adder
3.866
276897AD1-100 C
Solar/Wind Harmer
35.271
274683WAUKEGAN ;8U
Adder
15.862
274683WAUKEGAN ;8U
Adder
13.371
958481AF2-142 GEN
Solar/Wind Harmer
11.172
274696ROCKY RD ;4P
Adder
8.403
274695ROCKY RD ;2P
Adder
8.209
274693ROCKY RD ;1P
Adder
8.128
274697ROCKY RD ;3P
Adder
2.23
276901AD2-066 C O1
Solar/Wind Harmer
2.574
958491AF2-143 GEN
Solar/Wind Harmer
10.966
962691AG1-118 GEN
Solar/Wind Harmer
21.45
276872AE1-163_GEN1
Solar/Wind Harmer
4.782
276876AE1-163_GEN2
Solar/Wind Harmer
4.782
960751AF2-366 GEN
Solar/Wind Harmer
2.043
971341AH1-150 GEN
Solar/Wind Harmer
13.882
971343AH1-151 GEN
Solar/Wind Harmer
13.882
972235AH1-702 GEN1
Adder
1.745
972236AH1-702 GEN2
Adder
1.517
274770LINCOLN ;1U
Adder
4.228
274771LINCOLN ;2U
Adder
4.228
938861AE1-114 GEN
Solar/Wind Harmer
5.535
274764LEE CO EC;5U
Adder
6.252
274765LEE CO EC;6U
Adder
6.252
274762LEE CO EC;3U
Adder
6.238
274763LEE CO EC;4U
Adder
6.179
276158O29GEN2
Solar/Wind Harmer
3.25
276157O29GEN1
Solar/Wind Harmer
2.471
276645AC1-214 GEN1
Solar/Wind Harmer
0.851
942111AE2-223 GEN
Solar/Wind Harmer
4.448
960611AF2-352 GEN
Solar/Wind Harmer
1.2
274826FISK ;BP
50/50
11.992
972038AH1-567 GEN2
50/50
0.382
274803UNIV PARK;6U
50/50
5.457
274887GEN-1.85
Solar/Wind Harmer
4.745
276772AC2-154 GEN
Solar/Wind Harmer
2.485
276843GEN-1.7
Solar/Wind Harmer
0.511
276806AD2-047 C O1
Solar/Wind Harmer
9.528
972231SS25-0005
Solar/Wind Harmer
8.384
972181SS23-001
Solar/Wind Harmer
5.24
274752CRETE EC ;2U
Adder
4.318
274753CRETE EC ;3U
Adder
4.318
274862TOP CROP ;2U
Solar/Wind Harmer
4.32
274676JOLIET 29;8U
Adder
24.506
274730ELWOOD EC;6P
Adder
13.414
274734ELWOOD EC;8P
Adder
13.414
274736ELWOOD EC;9P
Adder
13.414
274729ELWOOD EC;1P
Adder
13.39
274814UNIV PK N;0U
Adder
3.917
274807UNIV PK N;3U
Adder
3.908
274811UNIV PK N;7U
Adder
3.883
939351AE1-166 GEN
Solar/Wind Harmer
4.503
274682WAUKEGAN ;7U
Adder
13.565
972259AH1-714 GEN
Adder
14.397
276868AE1-113 GEN
Solar/Wind Harmer
7.528
274879MINONK ;1U
Solar/Wind Harmer
5.019
943121AE2-341 GEN
Solar/Wind Harmer
10.864
943591AF1-030 GEN
Solar/Wind Harmer
7.243
970707AG2-453 GEN
Solar/Wind Harmer
19.903
970571AG2-364 GEN
Solar/Wind Harmer
13.98
276799AD1-013 GEN
Solar/Wind Harmer
1.542
946671AF1-331 GEN
Solar/Wind Harmer
0.292
274855GSG-6 ;RU
Solar/Wind Harmer
2.575
274850MENDOTA H;RU
Solar/Wind Harmer
1.79
276602WESTBROOK C
Solar/Wind Harmer
1.482
959091AF2-200 GEN
Solar/Wind Harmer
13.882
274772LINCOLN ;3U
Adder
4.228
274857EASY ROAD;U1
Solar/Wind Harmer
3.212
274760LEE CO EC;1U
Adder
6.238
274767LEE CO EC;8U
Adder
6.164
276603SUBLETTE C
Solar/Wind Harmer
0.699
274851PROVIDENC;RU
Solar/Wind Harmer
1.809
274849CRESCENT ;1U
Solar/Wind Harmer
1.175
276782AC1-033 GEN
Solar/Wind Harmer
2.513
274878BISHOP HL;2U
Solar/Wind Harmer
2.126
965931AG1-462 GEN
Solar/Wind Harmer
15.623
971087AG2-675 GEN
Solar/Wind Harmer
2.28
276164X3-005 C
Solar/Wind Harmer
0.416
965091AG1-374 GEN
Solar/Wind Harmer
15.485
959611AF2-252 GEN
Solar/Wind Harmer
1.2
24441505OLIV SLR
Solar/Wind Helper
0.053
274827FISK ;RP
50/50
8.499
274799UNIV PARK;2U
50/50
0.274
274800UNIV PARK;3U
50/50
6.098
274801UNIV PARK;4U
50/50
6.098
274687WILL CNTY;4U
50/50
26.317
274687WILL CNTY;4U
50/50
26.317
972037AH1-567 GEN1
50/50
0.171
960591AF2-350 GEN
Solar/Wind Harmer
8.907
276893AG1-478 C
Solar/Wind Harmer
0.458
274675JOLIET 29;7U
Adder
25.403
274675JOLIET 29;7U
Adder
24.495
274728ELWOOD EC;5P
Adder
13.414
274731ELWOOD EC;2P
Adder
13.39
274733ELWOOD EC;3P
Adder
13.39
274735ELWOOD EC;4P
Adder
13.39
972228AH1-698 GEN2
Adder
2.968
972227AH1-698 GEN1
Adder
2.09
970833AG2-524 GEN
Solar/Wind Harmer
6.541
970833AG2-524 GEN
Solar/Wind Harmer
3.042
274744AC1-111 GEN8
Adder
4.144
274746AC1-111 G10
Adder
4.144
970073AG2-061 GEN
Solar/Wind Harmer
1.7
276889AE2-281 GEN
Solar/Wind Harmer
1.366
971411AH1-196 GEN
Solar/Wind Harmer
10.666
971675AH1-338 GEN
Solar/Wind Harmer
12.558
276861AD2-134 GEN
Solar/Wind Harmer
1.245
276863AD2-134 GEN
Solar/Wind Harmer
1.245
274823ROCKFORD ;21
Adder
13.564
971171AH1-044 GEN
Solar/Wind Harmer
13.882
274856ECOGROVE ;U1
Solar/Wind Harmer
2.311
276611AD2-172 GEN
Solar/Wind Harmer
1.753
276612AE2-035 GEN
Solar/Wind Harmer
1.753
274775LINCOLN ;6U
Adder
4.228
274776LINCOLN ;7U
Adder
4.228
274777LINCOLN ;8U
Adder
4.228
971681AH1-341 GEN
Solar/Wind Harmer
10.12
926823AC1-168 GEN
Solar/Wind Harmer
2.852
972267AH1-718 GEN
Adder
2.732
276741O09 GEN1
Solar/Wind Harmer
2.321
274863CRW1-WTG
Solar/Wind Harmer
3.573
274864CRW2-WTG
Solar/Wind Harmer
3.573
274877BISHOP HL;1U
Solar/Wind Harmer
2.126
946321AF1-296 GEN
Solar/Wind Harmer
6.463
970169AG2-114 GEN
Solar/Wind Harmer
6.147
276726Z2-087_GEN
Solar/Wind Harmer
4.29
959341AF2-225 GEN
Solar/Wind Harmer
8.139
274853TWINGROVE;U1
Solar/Wind Harmer
3.719
274854TWINGROVE;U2
Solar/Wind Harmer
3.641
270526AF1-158 GEN
Solar/Wind Helper
0.889
991777J1629 G
External Queue
8.881095886230469
990512J1326
External Queue
3.8879780769348145
990117J1214
External Queue
13.37464427947998
990727J1377 G
External Queue
4.499313831329346
990407J1304
External Queue
3.0006840229034424
NYPJM->LTFIMP_NY
CLTF
0.624
WECLTFEXP_WEC->PJM
CLTF
2.688
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.258
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.128
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.156
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.699
MECLTFEXP_MEC->PJM
CLTF
8.241
SIGELTFEXP_SIGE->PJM
CLTF
0.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.323
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.929
LAGNLTFEXP_LAGN->PJM
CLTF
2.623
TVALTFEXP_TVA->PJM
CLTF
0.643

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.24 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1530.88
MW Contribution:
10.12
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.3 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1560.67
MW Contribution:
10.23
Bus #Bus NameTypeMW Contribution
274802UNIV PARK;5U
50/50
5.457
274861TOP CROP ;1U
Solar/Wind Harmer
5.174
274674JOLIET 9 ;6U
Adder
12.91
274676JOLIET 29;8U
Adder
25.414
274732ELWOOD EC;7P
Adder
13.414
274812UNIV PK N;8U
Adder
3.883
941551AE2-152 GEN
Solar/Wind Harmer
3.444
274682WAUKEGAN ;7U
Adder
13.565
274828WAUKEGAN ;BP
Adder
8.315
276694AA1-018 GEN2
Solar/Wind Harmer
4.699
276691AA1-018 GEN1
Solar/Wind Harmer
0.562
276882AE2-255 GEN
Solar/Wind Harmer
2.509
274871GR RIDGE ;2U
Solar/Wind Harmer
5.705
274847GR RIDGE ;BU
Solar/Wind Harmer
3.751
274745AC1-111 GEN9
Adder
4.144
276805AD2-038 GEN
Solar/Wind Harmer
3.749
962781AG1-127 GEN
Solar/Wind Harmer
6.771
274872LEEDK;1U
Solar/Wind Harmer
5.816
971997AH1-543 GEN
Solar/Wind Harmer
11.006
970569AG2-363 GEN
Solar/Wind Harmer
20.969
274822ROCKFORD ;11
Adder
13.663
957471AF2-041 GEN
Solar/Wind Harmer
20.823
959081AF2-199 GEN
Solar/Wind Harmer
6.941
971067AG2-660 GEN
Solar/Wind Harmer
1.614
970819AG2-516 GEN
Solar/Wind Harmer
8.265
274798UNIV PARK;1U
50/50
0.265
274888KELLY CRK;1U
Solar/Wind Harmer
5.256
276776AD2-060 GEN
Solar/Wind Harmer
0.373
958011AF2-095 GEN
Solar/Wind Harmer
12.826
970941AG2-585 GEN
Solar/Wind Harmer
4.899
274674JOLIET 9 ;6U
Adder
12.91
276893AG1-478 C
Solar/Wind Harmer
0.365
274805UNIV PK N;1U
Adder
3.891
274808UNIV PK N;4U
Adder
3.866
276897AD1-100 C
Solar/Wind Harmer
35.271
274683WAUKEGAN ;8U
Adder
15.862
274683WAUKEGAN ;8U
Adder
13.371
958481AF2-142 GEN
Solar/Wind Harmer
11.172
274696ROCKY RD ;4P
Adder
8.403
274695ROCKY RD ;2P
Adder
8.209
274693ROCKY RD ;1P
Adder
8.128
274697ROCKY RD ;3P
Adder
2.23
276901AD2-066 C O1
Solar/Wind Harmer
2.574
958491AF2-143 GEN
Solar/Wind Harmer
10.966
962691AG1-118 GEN
Solar/Wind Harmer
21.45
276872AE1-163_GEN1
Solar/Wind Harmer
4.782
276876AE1-163_GEN2
Solar/Wind Harmer
4.782
960751AF2-366 GEN
Solar/Wind Harmer
2.043
971341AH1-150 GEN
Solar/Wind Harmer
13.882
971343AH1-151 GEN
Solar/Wind Harmer
13.882
972235AH1-702 GEN1
Adder
1.745
972236AH1-702 GEN2
Adder
1.517
274770LINCOLN ;1U
Adder
4.228
274771LINCOLN ;2U
Adder
4.228
938861AE1-114 GEN
Solar/Wind Harmer
5.535
274764LEE CO EC;5U
Adder
6.252
274765LEE CO EC;6U
Adder
6.252
274762LEE CO EC;3U
Adder
6.238
274763LEE CO EC;4U
Adder
6.179
276158O29GEN2
Solar/Wind Harmer
3.25
276157O29GEN1
Solar/Wind Harmer
2.471
276645AC1-214 GEN1
Solar/Wind Harmer
0.851
942111AE2-223 GEN
Solar/Wind Harmer
4.448
960611AF2-352 GEN
Solar/Wind Harmer
1.2
274826FISK ;BP
50/50
11.992
972038AH1-567 GEN2
50/50
0.382
274803UNIV PARK;6U
50/50
5.457
274887GEN-1.85
Solar/Wind Harmer
4.745
276772AC2-154 GEN
Solar/Wind Harmer
2.485
276843GEN-1.7
Solar/Wind Harmer
0.511
276806AD2-047 C O1
Solar/Wind Harmer
9.528
274862TOP CROP ;2U
Solar/Wind Harmer
4.32
274676JOLIET 29;8U
Adder
24.506
274730ELWOOD EC;6P
Adder
13.414
274734ELWOOD EC;8P
Adder
13.414
274736ELWOOD EC;9P
Adder
13.414
274729ELWOOD EC;1P
Adder
13.39
274814UNIV PK N;0U
Adder
3.917
274807UNIV PK N;3U
Adder
3.908
274811UNIV PK N;7U
Adder
3.883
939351AE1-166 GEN
Solar/Wind Harmer
4.503
274682WAUKEGAN ;7U
Adder
13.565
972259AH1-714 GEN
Adder
14.397
276868AE1-113 GEN
Solar/Wind Harmer
7.528
274879MINONK ;1U
Solar/Wind Harmer
5.019
943121AE2-341 GEN
Solar/Wind Harmer
10.864
943591AF1-030 GEN
Solar/Wind Harmer
7.243
970707AG2-453 GEN
Solar/Wind Harmer
19.903
970571AG2-364 GEN
Solar/Wind Harmer
13.98
276799AD1-013 GEN
Solar/Wind Harmer
1.542
946671AF1-331 GEN
Solar/Wind Harmer
0.292
274855GSG-6 ;RU
Solar/Wind Harmer
2.575
274850MENDOTA H;RU
Solar/Wind Harmer
1.79
276602WESTBROOK C
Solar/Wind Harmer
1.482
959091AF2-200 GEN
Solar/Wind Harmer
13.882
274772LINCOLN ;3U
Adder
4.228
274857EASY ROAD;U1
Solar/Wind Harmer
3.212
274760LEE CO EC;1U
Adder
6.238
274767LEE CO EC;8U
Adder
6.164
276603SUBLETTE C
Solar/Wind Harmer
0.699
274851PROVIDENC;RU
Solar/Wind Harmer
1.809
274849CRESCENT ;1U
Solar/Wind Harmer
1.175
276782AC1-033 GEN
Solar/Wind Harmer
2.513
274878BISHOP HL;2U
Solar/Wind Harmer
2.126
965931AG1-462 GEN
Solar/Wind Harmer
15.623
971087AG2-675 GEN
Solar/Wind Harmer
2.28
276164X3-005 C
Solar/Wind Harmer
0.416
965091AG1-374 GEN
Solar/Wind Harmer
15.485
959611AF2-252 GEN
Solar/Wind Harmer
1.2
24441505OLIV SLR
Solar/Wind Helper
0.053
274827FISK ;RP
50/50
8.499
274799UNIV PARK;2U
50/50
0.274
274800UNIV PARK;3U
50/50
6.098
274801UNIV PARK;4U
50/50
6.098
274687WILL CNTY;4U
50/50
26.317
274687WILL CNTY;4U
50/50
26.317
972037AH1-567 GEN1
50/50
0.171
960591AF2-350 GEN
Solar/Wind Harmer
8.907
276893AG1-478 C
Solar/Wind Harmer
0.458
274675JOLIET 29;7U
Adder
25.403
274675JOLIET 29;7U
Adder
24.495
274728ELWOOD EC;5P
Adder
13.414
274731ELWOOD EC;2P
Adder
13.39
274733ELWOOD EC;3P
Adder
13.39
274735ELWOOD EC;4P
Adder
13.39
972228AH1-698 GEN2
Adder
2.968
972227AH1-698 GEN1
Adder
2.09
970833AG2-524 GEN
Solar/Wind Harmer
6.541
970833AG2-524 GEN
Solar/Wind Harmer
3.042
274744AC1-111 GEN8
Adder
4.144
274746AC1-111 G10
Adder
4.144
970073AG2-061 GEN
Solar/Wind Harmer
1.7
276889AE2-281 GEN
Solar/Wind Harmer
1.366
971411AH1-196 GEN
Solar/Wind Harmer
10.666
971675AH1-338 GEN
Solar/Wind Harmer
12.558
276861AD2-134 GEN
Solar/Wind Harmer
1.245
276863AD2-134 GEN
Solar/Wind Harmer
1.245
274823ROCKFORD ;21
Adder
13.564
971171AH1-044 GEN
Solar/Wind Harmer
13.882
274856ECOGROVE ;U1
Solar/Wind Harmer
2.311
276611AD2-172 GEN
Solar/Wind Harmer
1.753
276612AE2-035 GEN
Solar/Wind Harmer
1.753
274775LINCOLN ;6U
Adder
4.228
274776LINCOLN ;7U
Adder
4.228
274777LINCOLN ;8U
Adder
4.228
971681AH1-341 GEN
Solar/Wind Harmer
10.12
926823AC1-168 GEN
Solar/Wind Harmer
2.852
972267AH1-718 GEN
Adder
2.732
276741O09 GEN1
Solar/Wind Harmer
2.321
274863CRW1-WTG
Solar/Wind Harmer
3.573
274864CRW2-WTG
Solar/Wind Harmer
3.573
274877BISHOP HL;1U
Solar/Wind Harmer
2.126
946321AF1-296 GEN
Solar/Wind Harmer
6.463
970169AG2-114 GEN
Solar/Wind Harmer
6.147
276726Z2-087_GEN
Solar/Wind Harmer
4.29
959341AF2-225 GEN
Solar/Wind Harmer
8.139
274853TWINGROVE;U1
Solar/Wind Harmer
3.719
274854TWINGROVE;U2
Solar/Wind Harmer
3.641
270526AF1-158 GEN
Solar/Wind Helper
0.889
972207SS24-0001
Solar/Wind Harmer
15.033
274773LINCOLN ;4U
Adder
4.228
274774LINCOLN ;5U
Adder
4.228
274858EASY ROAD;U2
Solar/Wind Harmer
3.212
274761LEE CO EC;2U
Adder
6.238
274766LEE CO EC;7U
Adder
6.164
939401AE1-172 GEN
Solar/Wind Harmer
9.306
276708O09 GEN2
Solar/Wind Harmer
2.321
276646AC1-214 GEN2
Solar/Wind Harmer
0.851
274848CAMPGROVE;RU
Solar/Wind Harmer
4.019
276655WTG1_EQ
Solar/Wind Harmer
4.736
276656WTG2_EQ
Solar/Wind Harmer
0.627
939741AE1-205 GEN
Solar/Wind Harmer
10.852
991777J1629 G
External Queue
8.881095886230469
990512J1326
External Queue
3.8879780769348145
990117J1214
External Queue
13.37464427947998
990727J1377 G
External Queue
4.499313831329346
990407J1304
External Queue
3.0006840229034424
NYPJM->LTFIMP_NY
CLTF
0.624
WECLTFEXP_WEC->PJM
CLTF
2.688
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.258
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.128
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.156
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.699
MECLTFEXP_MEC->PJM
CLTF
8.241
SIGELTFEXP_SIGE->PJM
CLTF
0.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.323
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.929
LAGNLTFEXP_LAGN->PJM
CLTF
2.623
TVALTFEXP_TVA->PJM
CLTF
0.643

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.9 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1859.87
MW Contribution:
13.39
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.12 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1895.21
MW Contribution:
13.54
Bus #Bus NameTypeMW Contribution
274826FISK ;BP
50/50
14.838
274814UNIV PK N;0U
50/50
6.348
274807UNIV PK N;3U
50/50
6.334
274811UNIV PK N;7U
50/50
6.292
274803UNIV PARK;6U
50/50
7.237
972038AH1-567 GEN2
50/50
0.444
276164X3-005 C
Solar/Wind Harmer
0.922
274887GEN-1.85
Solar/Wind Harmer
6.538
276772AC2-154 GEN
Solar/Wind Harmer
3.425
276843GEN-1.7
Solar/Wind Harmer
0.703
276806AD2-047 C O1
Solar/Wind Harmer
13.128
274676JOLIET 29;8U
Adder
32.327
274729ELWOOD EC;1P
Adder
17.678
274730ELWOOD EC;6P
Adder
17.673
274734ELWOOD EC;8P
Adder
17.673
274736ELWOOD EC;9P
Adder
17.673
972231SS25-0005
Solar/Wind Harmer
10.189
972181SS23-001
Solar/Wind Harmer
6.368
274752CRETE EC ;2U
Adder
5.248
274753CRETE EC ;3U
Adder
5.248
939351AE1-166 GEN
Solar/Wind Harmer
6.159
972259AH1-714 GEN
Adder
19.51
274862TOP CROP ;2U
Solar/Wind Harmer
5.118
274682WAUKEGAN ;7U
Adder
17.873
276868AE1-113 GEN
Solar/Wind Harmer
9.87
274879MINONK ;1U
Solar/Wind Harmer
6.58
943121AE2-341 GEN
Solar/Wind Harmer
14.474
943591AF1-030 GEN
Solar/Wind Harmer
9.649
970707AG2-453 GEN
Solar/Wind Harmer
26.823
274772LINCOLN ;3U
Adder
5.831
276799AD1-013 GEN
Solar/Wind Harmer
2.046
946671AF1-331 GEN
Solar/Wind Harmer
0.388
274855GSG-6 ;RU
Solar/Wind Harmer
3.415
274815UNIV PK N;XU
50/50
0.346
274813UNIV PK N;9U
50/50
0.345
274816UNIV PK N;YU
50/50
0.345
274809UNIV PK N;5U
50/50
0.343
274805UNIV PK N;1U
50/50
6.306
274808UNIV PK N;4U
50/50
6.265
274798UNIV PARK;1U
50/50
0.309
274888KELLY CRK;1U
Solar/Wind Harmer
7.242
276776AD2-060 GEN
Solar/Wind Harmer
0.514
958011AF2-095 GEN
Solar/Wind Harmer
17.671
970941AG2-585 GEN
Solar/Wind Harmer
6.749
276893AG1-478 C
Solar/Wind Harmer
0.49
958481AF2-142 GEN
Solar/Wind Harmer
16.445
274674JOLIET 9 ;6U
Adder
16.482
958491AF2-143 GEN
Solar/Wind Harmer
15.655
276897AD1-100 C
Solar/Wind Harmer
48.244
274683WAUKEGAN ;8U
Adder
20.901
274683WAUKEGAN ;8U
Adder
17.618
274696ROCKY RD ;4P
Adder
11.118
274695ROCKY RD ;2P
Adder
10.862
274693ROCKY RD ;1P
Adder
10.755
274697ROCKY RD ;3P
Adder
2.951
276901AD2-066 C O1
Solar/Wind Harmer
3.409
276872AE1-163_GEN1
Solar/Wind Harmer
6.519
276876AE1-163_GEN2
Solar/Wind Harmer
6.519
962691AG1-118 GEN
Solar/Wind Harmer
28.471
960751AF2-366 GEN
Solar/Wind Harmer
2.711
274770LINCOLN ;1U
Adder
5.831
274771LINCOLN ;2U
Adder
5.831
971341AH1-150 GEN
Solar/Wind Harmer
18.389
971343AH1-151 GEN
Solar/Wind Harmer
18.389
972235AH1-702 GEN1
Adder
2.308
972236AH1-702 GEN2
Adder
2.007
938861AE1-114 GEN
Solar/Wind Harmer
7.325
274764LEE CO EC;5U
Adder
8.274
274765LEE CO EC;6U
Adder
8.274
274762LEE CO EC;3U
Adder
8.254
274763LEE CO EC;4U
Adder
8.176
276158O29GEN2
Solar/Wind Harmer
4.304
276157O29GEN1
Solar/Wind Harmer
3.272
276645AC1-214 GEN1
Solar/Wind Harmer
1.129
942111AE2-223 GEN
Solar/Wind Harmer
5.983
960611AF2-352 GEN
Solar/Wind Harmer
1.613
274880W4-005 GEN4
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276615X2-022 GEN
Solar/Wind Harmer
1.046
276838X2-022 GEN2
Solar/Wind Harmer
0.124
276916AD2-100_GEN
Solar/Wind Harmer
9.648
276911AD2-131_GEN
Solar/Wind Harmer
1.95
972179AH1-673 GEN
50/50
14.005
274723RIVER EC ;12
50/50
25.915
274806UNIV PK N;2U
50/50
0.352
274810UNIV PK N;6U
50/50
0.344
274812UNIV PK N;8U
50/50
6.292
274802UNIV PARK;5U
50/50
7.237
276694AA1-018 GEN2
Solar/Wind Harmer
6.917
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
274676JOLIET 29;8U
Adder
33.524
274732ELWOOD EC;7P
Adder
17.673
274751CRETE EC ;1U
Adder
5.248
274754CRETE EC ;4U
Adder
5.248
274674JOLIET 9 ;6U
Adder
16.482
276805AD2-038 GEN
Solar/Wind Harmer
5.352
941551AE2-152 GEN
Solar/Wind Harmer
4.71
274861TOP CROP ;1U
Solar/Wind Harmer
6.13
274871GR RIDGE ;2U
Solar/Wind Harmer
7.69
274847GR RIDGE ;BU
Solar/Wind Harmer
5.056
274682WAUKEGAN ;7U
Adder
17.873
274828WAUKEGAN ;BP
Adder
10.956
274745AC1-111 GEN9
Adder
5.503
276882AE2-255 GEN
Solar/Wind Harmer
3.29
962781AG1-127 GEN
Solar/Wind Harmer
8.985
972207SS24-0001
Solar/Wind Harmer
20.734
274773LINCOLN ;4U
Adder
5.831
274774LINCOLN ;5U
Adder
5.831
274872LEEDK;1U
Solar/Wind Harmer
7.718
971997AH1-543 GEN
Solar/Wind Harmer
14.617
274822ROCKFORD ;11
Adder
18.073
970569AG2-363 GEN
Solar/Wind Harmer
27.619
957471AF2-041 GEN
Solar/Wind Harmer
27.583
959081AF2-199 GEN
Solar/Wind Harmer
9.194
971067AG2-660 GEN
Solar/Wind Harmer
2.138
970819AG2-516 GEN
Solar/Wind Harmer
10.931
939401AE1-172 GEN
Solar/Wind Harmer
12.646
274858EASY ROAD;U2
Solar/Wind Harmer
4.25
274761LEE CO EC;2U
Adder
8.254
274766LEE CO EC;7U
Adder
8.157
276708O09 GEN2
Solar/Wind Harmer
3.073
276646AC1-214 GEN2
Solar/Wind Harmer
1.129
274848CAMPGROVE;RU
Solar/Wind Harmer
5.326
276655WTG1_EQ
Solar/Wind Harmer
6.37
276656WTG2_EQ
Solar/Wind Harmer
0.843
939741AE1-205 GEN
Solar/Wind Harmer
14.596
276686W4-005 GEN3
Solar/Wind Harmer
1.697
276621W2-048 GEN
Solar/Wind Harmer
3.332
965911AG1-460 GEN
Solar/Wind Harmer
0.666
274827FISK ;RP
50/50
10.516
972037AH1-567 GEN1
50/50
0.227
274799UNIV PARK;2U
50/50
0.319
274800UNIV PARK;3U
50/50
7.098
274801UNIV PARK;4U
50/50
7.098
960591AF2-350 GEN
Solar/Wind Harmer
12.272
276893AG1-478 C
Solar/Wind Harmer
0.615
972228AH1-698 GEN2
Adder
4.049
274675JOLIET 29;7U
Adder
33.53
274675JOLIET 29;7U
Adder
32.333
274687WILL CNTY;4U
Adder
30.534
274687WILL CNTY;4U
Adder
30.534
972227AH1-698 GEN1
Adder
2.848
274731ELWOOD EC;2P
Adder
17.678
274733ELWOOD EC;3P
Adder
17.678
274735ELWOOD EC;4P
Adder
17.678
274728ELWOOD EC;5P
Adder
17.673
970073AG2-061 GEN
Solar/Wind Harmer
2.427
970833AG2-524 GEN
Solar/Wind Harmer
8.781
970833AG2-524 GEN
Solar/Wind Harmer
4.084
274744AC1-111 GEN8
Adder
5.503
274746AC1-111 G10
Adder
5.503
276889AE2-281 GEN
Solar/Wind Harmer
1.862
274775LINCOLN ;6U
Adder
5.831
274776LINCOLN ;7U
Adder
5.831
274777LINCOLN ;8U
Adder
5.831
971411AH1-196 GEN
Solar/Wind Harmer
14.102
971675AH1-338 GEN
Solar/Wind Harmer
16.657
276861AD2-134 GEN
Solar/Wind Harmer
1.651
276863AD2-134 GEN
Solar/Wind Harmer
1.651
274823ROCKFORD ;21
Adder
17.941
971171AH1-044 GEN
Solar/Wind Harmer
18.389
274856ECOGROVE ;U1
Solar/Wind Harmer
3.058
276611AD2-172 GEN
Solar/Wind Harmer
2.319
276612AE2-035 GEN
Solar/Wind Harmer
2.319
971681AH1-341 GEN
Solar/Wind Harmer
13.395
926823AC1-168 GEN
Solar/Wind Harmer
3.799
972267AH1-718 GEN
Adder
3.616
274863CRW1-WTG
Solar/Wind Harmer
4.841
274864CRW2-WTG
Solar/Wind Harmer
4.841
276741O09 GEN1
Solar/Wind Harmer
3.073
274877BISHOP HL;1U
Solar/Wind Harmer
2.818
970169AG2-114 GEN
Solar/Wind Harmer
8.266
946321AF1-296 GEN
Solar/Wind Harmer
8.551
276726Z2-087_GEN
Solar/Wind Harmer
5.77
959341AF2-225 GEN
Solar/Wind Harmer
10.947
274853TWINGROVE;U1
Solar/Wind Harmer
4.997
274854TWINGROVE;U2
Solar/Wind Harmer
4.893
276668AB2-070 GEN1
Solar/Wind Harmer
1.24
276848AB2-070 GEN3
Solar/Wind Harmer
1.24
276849AB2-070 GEN2
Solar/Wind Harmer
1.24
276763AC1-053 GEN1
Solar/Wind Harmer
2.181
276764AC1-053 GEN2
Solar/Wind Harmer
2.181
960681AF2-359 GEN
Solar/Wind Helper
0.967
270526AF1-158 GEN
Solar/Wind Helper
1.013
274850MENDOTA H;RU
Solar/Wind Harmer
2.374
276602WESTBROOK C
Solar/Wind Harmer
1.966
970571AG2-364 GEN
Solar/Wind Harmer
18.412
959091AF2-200 GEN
Solar/Wind Harmer
18.389
274857EASY ROAD;U1
Solar/Wind Harmer
4.25
274760LEE CO EC;1U
Adder
8.254
274767LEE CO EC;8U
Adder
8.157
276603SUBLETTE C
Solar/Wind Harmer
0.925
274851PROVIDENC;RU
Solar/Wind Harmer
2.4
274849CRESCENT ;1U
Solar/Wind Harmer
1.558
276782AC1-033 GEN
Solar/Wind Harmer
3.331
274878BISHOP HL;2U
Solar/Wind Harmer
2.818
965931AG1-462 GEN
Solar/Wind Harmer
20.667
971087AG2-675 GEN
Solar/Wind Harmer
3.016
965091AG1-374 GEN
Solar/Wind Harmer
20.81
959611AF2-252 GEN
Solar/Wind Harmer
1.613
276785W4-005 GEN1
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.187
274724RIVER EC ;11
Adder
9.258
957381AF2-032 GEN
Solar/Wind Harmer
0.967
942481AE2-261 GEN
Solar/Wind Harmer
14.28
24441505OLIV SLR
Solar/Wind Helper
0.06
991777J1629 G
External Queue
11.498458862304688
990512J1326
External Queue
5.040998458862305
990117J1214
External Queue
17.341033935546875
990727J1377 G
External Queue
5.839296817779541
991092J1477
External Queue
2.7281463146209717
991303J1755 G
External Queue
4.388484001159668
990407J1304
External Queue
3.893380880355835
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.174
NYPJM->LTFIMP_NY
CLTF
0.83
WECLTFEXP_WEC->PJM
CLTF
3.545
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.288
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.184
MECLTFEXP_MEC->PJM
CLTF
10.89
SIGELTFEXP_SIGE->PJM
CLTF
0.003
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.443
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.278
LAGNLTFEXP_LAGN->PJM
CLTF
3.443
TVALTFEXP_TVA->PJM
CLTF
0.836

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:114.54 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1822.27
MW Contribution:
13.39
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.71 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1856.8
MW Contribution:
13.54
Bus #Bus NameTypeMW Contribution
274815UNIV PK N;XU
50/50
0.346
972179AH1-673 GEN
50/50
14.005
274723RIVER EC ;12
50/50
25.915
274806UNIV PK N;2U
50/50
0.352
274810UNIV PK N;6U
50/50
0.344
274812UNIV PK N;8U
50/50
6.292
274802UNIV PARK;5U
50/50
7.237
276694AA1-018 GEN2
Solar/Wind Harmer
6.917
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
274676JOLIET 29;8U
Adder
33.524
274732ELWOOD EC;7P
Adder
17.673
274674JOLIET 9 ;6U
Adder
16.482
276805AD2-038 GEN
Solar/Wind Harmer
5.352
941551AE2-152 GEN
Solar/Wind Harmer
4.71
274861TOP CROP ;1U
Solar/Wind Harmer
6.13
274871GR RIDGE ;2U
Solar/Wind Harmer
7.69
274847GR RIDGE ;BU
Solar/Wind Harmer
5.056
274682WAUKEGAN ;7U
Adder
17.873
274828WAUKEGAN ;BP
Adder
10.956
274745AC1-111 GEN9
Adder
5.503
276882AE2-255 GEN
Solar/Wind Harmer
3.29
962781AG1-127 GEN
Solar/Wind Harmer
8.985
972207SS24-0001
Solar/Wind Harmer
20.734
274773LINCOLN ;4U
Adder
5.831
274774LINCOLN ;5U
Adder
5.831
274872LEEDK;1U
Solar/Wind Harmer
7.718
971997AH1-543 GEN
Solar/Wind Harmer
14.617
274822ROCKFORD ;11
Adder
18.073
970569AG2-363 GEN
Solar/Wind Harmer
27.619
957471AF2-041 GEN
Solar/Wind Harmer
27.583
959081AF2-199 GEN
Solar/Wind Harmer
9.194
971067AG2-660 GEN
Solar/Wind Harmer
2.138
970819AG2-516 GEN
Solar/Wind Harmer
10.931
939401AE1-172 GEN
Solar/Wind Harmer
12.646
274858EASY ROAD;U2
Solar/Wind Harmer
4.25
274761LEE CO EC;2U
Adder
8.254
274766LEE CO EC;7U
Adder
8.157
276708O09 GEN2
Solar/Wind Harmer
3.073
276646AC1-214 GEN2
Solar/Wind Harmer
1.129
274848CAMPGROVE;RU
Solar/Wind Harmer
5.326
276655WTG1_EQ
Solar/Wind Harmer
6.37
276656WTG2_EQ
Solar/Wind Harmer
0.843
939741AE1-205 GEN
Solar/Wind Harmer
14.596
276686W4-005 GEN3
Solar/Wind Harmer
1.697
276621W2-048 GEN
Solar/Wind Harmer
3.332
965911AG1-460 GEN
Solar/Wind Harmer
0.666
274813UNIV PK N;9U
50/50
0.345
274816UNIV PK N;YU
50/50
0.345
274809UNIV PK N;5U
50/50
0.343
274805UNIV PK N;1U
50/50
6.306
274808UNIV PK N;4U
50/50
6.265
274798UNIV PARK;1U
50/50
0.309
274888KELLY CRK;1U
Solar/Wind Harmer
7.242
276776AD2-060 GEN
Solar/Wind Harmer
0.514
958011AF2-095 GEN
Solar/Wind Harmer
17.671
970941AG2-585 GEN
Solar/Wind Harmer
6.749
276893AG1-478 C
Solar/Wind Harmer
0.49
958481AF2-142 GEN
Solar/Wind Harmer
16.445
274674JOLIET 9 ;6U
Adder
16.482
958491AF2-143 GEN
Solar/Wind Harmer
15.655
276897AD1-100 C
Solar/Wind Harmer
48.244
274683WAUKEGAN ;8U
Adder
20.901
274683WAUKEGAN ;8U
Adder
17.618
274696ROCKY RD ;4P
Adder
11.118
274695ROCKY RD ;2P
Adder
10.862
274693ROCKY RD ;1P
Adder
10.755
274697ROCKY RD ;3P
Adder
2.951
276901AD2-066 C O1
Solar/Wind Harmer
3.409
276872AE1-163_GEN1
Solar/Wind Harmer
6.519
276876AE1-163_GEN2
Solar/Wind Harmer
6.519
962691AG1-118 GEN
Solar/Wind Harmer
28.471
960751AF2-366 GEN
Solar/Wind Harmer
2.711
274770LINCOLN ;1U
Adder
5.831
274771LINCOLN ;2U
Adder
5.831
971341AH1-150 GEN
Solar/Wind Harmer
18.389
971343AH1-151 GEN
Solar/Wind Harmer
18.389
972235AH1-702 GEN1
Adder
2.308
972236AH1-702 GEN2
Adder
2.007
938861AE1-114 GEN
Solar/Wind Harmer
7.325
274764LEE CO EC;5U
Adder
8.274
274765LEE CO EC;6U
Adder
8.274
274762LEE CO EC;3U
Adder
8.254
274763LEE CO EC;4U
Adder
8.176
276158O29GEN2
Solar/Wind Harmer
4.304
276157O29GEN1
Solar/Wind Harmer
3.272
276645AC1-214 GEN1
Solar/Wind Harmer
1.129
942111AE2-223 GEN
Solar/Wind Harmer
5.983
960611AF2-352 GEN
Solar/Wind Harmer
1.613
274880W4-005 GEN4
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276615X2-022 GEN
Solar/Wind Harmer
1.046
276838X2-022 GEN2
Solar/Wind Harmer
0.124
276916AD2-100_GEN
Solar/Wind Harmer
9.689
276911AD2-131_GEN
Solar/Wind Harmer
1.958
274826FISK ;BP
50/50
14.838
274814UNIV PK N;0U
50/50
6.348
274807UNIV PK N;3U
50/50
6.334
274811UNIV PK N;7U
50/50
6.292
274803UNIV PARK;6U
50/50
7.237
972038AH1-567 GEN2
50/50
0.444
276164X3-005 C
Solar/Wind Harmer
0.922
274887GEN-1.85
Solar/Wind Harmer
6.538
276772AC2-154 GEN
Solar/Wind Harmer
3.425
276843GEN-1.7
Solar/Wind Harmer
0.703
276806AD2-047 C O1
Solar/Wind Harmer
13.128
274676JOLIET 29;8U
Adder
32.327
274729ELWOOD EC;1P
Adder
17.678
274730ELWOOD EC;6P
Adder
17.673
274734ELWOOD EC;8P
Adder
17.673
274736ELWOOD EC;9P
Adder
17.673
939351AE1-166 GEN
Solar/Wind Harmer
6.159
972259AH1-714 GEN
Adder
19.51
274862TOP CROP ;2U
Solar/Wind Harmer
5.118
274682WAUKEGAN ;7U
Adder
17.873
276868AE1-113 GEN
Solar/Wind Harmer
9.87
274879MINONK ;1U
Solar/Wind Harmer
6.58
943121AE2-341 GEN
Solar/Wind Harmer
14.474
943591AF1-030 GEN
Solar/Wind Harmer
9.649
970707AG2-453 GEN
Solar/Wind Harmer
26.823
274772LINCOLN ;3U
Adder
5.831
276799AD1-013 GEN
Solar/Wind Harmer
2.046
946671AF1-331 GEN
Solar/Wind Harmer
0.388
274855GSG-6 ;RU
Solar/Wind Harmer
3.415
274850MENDOTA H;RU
Solar/Wind Harmer
2.374
276602WESTBROOK C
Solar/Wind Harmer
1.966
970571AG2-364 GEN
Solar/Wind Harmer
18.412
959091AF2-200 GEN
Solar/Wind Harmer
18.389
274857EASY ROAD;U1
Solar/Wind Harmer
4.25
274760LEE CO EC;1U
Adder
8.254
274767LEE CO EC;8U
Adder
8.157
276603SUBLETTE C
Solar/Wind Harmer
0.925
274851PROVIDENC;RU
Solar/Wind Harmer
2.4
274849CRESCENT ;1U
Solar/Wind Harmer
1.558
276782AC1-033 GEN
Solar/Wind Harmer
3.331
274878BISHOP HL;2U
Solar/Wind Harmer
2.818
965931AG1-462 GEN
Solar/Wind Harmer
20.667
971087AG2-675 GEN
Solar/Wind Harmer
3.016
965091AG1-374 GEN
Solar/Wind Harmer
20.81
959611AF2-252 GEN
Solar/Wind Harmer
1.613
276785W4-005 GEN1
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.187
274724RIVER EC ;11
Adder
9.258
957381AF2-032 GEN
Solar/Wind Harmer
0.967
942481AE2-261 GEN
Solar/Wind Harmer
14.28
24441505OLIV SLR
Solar/Wind Helper
0.06
274827FISK ;RP
50/50
10.516
972037AH1-567 GEN1
50/50
0.227
274799UNIV PARK;2U
50/50
0.319
274800UNIV PARK;3U
50/50
7.098
274801UNIV PARK;4U
50/50
7.098
960591AF2-350 GEN
Solar/Wind Harmer
12.272
276893AG1-478 C
Solar/Wind Harmer
0.615
972228AH1-698 GEN2
Adder
4.049
274675JOLIET 29;7U
Adder
33.53
274675JOLIET 29;7U
Adder
32.333
274687WILL CNTY;4U
Adder
30.534
274687WILL CNTY;4U
Adder
30.534
972227AH1-698 GEN1
Adder
2.848
274731ELWOOD EC;2P
Adder
17.678
274733ELWOOD EC;3P
Adder
17.678
274735ELWOOD EC;4P
Adder
17.678
274728ELWOOD EC;5P
Adder
17.673
970073AG2-061 GEN
Solar/Wind Harmer
2.427
970833AG2-524 GEN
Solar/Wind Harmer
8.781
970833AG2-524 GEN
Solar/Wind Harmer
4.084
274744AC1-111 GEN8
Adder
5.503
274746AC1-111 G10
Adder
5.503
276889AE2-281 GEN
Solar/Wind Harmer
1.862
274775LINCOLN ;6U
Adder
5.831
274776LINCOLN ;7U
Adder
5.831
274777LINCOLN ;8U
Adder
5.831
971411AH1-196 GEN
Solar/Wind Harmer
14.102
971675AH1-338 GEN
Solar/Wind Harmer
16.657
276861AD2-134 GEN
Solar/Wind Harmer
1.651
276863AD2-134 GEN
Solar/Wind Harmer
1.651
274823ROCKFORD ;21
Adder
17.941
971171AH1-044 GEN
Solar/Wind Harmer
18.389
274856ECOGROVE ;U1
Solar/Wind Harmer
3.058
276611AD2-172 GEN
Solar/Wind Harmer
2.319
276612AE2-035 GEN
Solar/Wind Harmer
2.319
971681AH1-341 GEN
Solar/Wind Harmer
13.395
926823AC1-168 GEN
Solar/Wind Harmer
3.799
972267AH1-718 GEN
Adder
3.616
274863CRW1-WTG
Solar/Wind Harmer
4.841
274864CRW2-WTG
Solar/Wind Harmer
4.841
276741O09 GEN1
Solar/Wind Harmer
3.073
274877BISHOP HL;1U
Solar/Wind Harmer
2.818
970169AG2-114 GEN
Solar/Wind Harmer
8.266
946321AF1-296 GEN
Solar/Wind Harmer
8.551
276726Z2-087_GEN
Solar/Wind Harmer
5.77
959341AF2-225 GEN
Solar/Wind Harmer
10.947
274853TWINGROVE;U1
Solar/Wind Harmer
4.997
274854TWINGROVE;U2
Solar/Wind Harmer
4.893
276668AB2-070 GEN1
Solar/Wind Harmer
1.24
276848AB2-070 GEN3
Solar/Wind Harmer
1.24
276849AB2-070 GEN2
Solar/Wind Harmer
1.24
276763AC1-053 GEN1
Solar/Wind Harmer
2.181
276764AC1-053 GEN2
Solar/Wind Harmer
2.181
960681AF2-359 GEN
Solar/Wind Helper
0.967
270526AF1-158 GEN
Solar/Wind Helper
1.013
991777J1629 G
External Queue
11.498458862304688
990512J1326
External Queue
5.040998458862305
990117J1214
External Queue
17.341033935546875
990727J1377 G
External Queue
5.839296817779541
991092J1477
External Queue
2.7281463146209717
991303J1755 G
External Queue
4.388484001159668
990407J1304
External Queue
3.893380880355835
NYPJM->LTFIMP_NY
CLTF
0.83
WECLTFEXP_WEC->PJM
CLTF
3.545
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.348
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.174
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.184
MECLTFEXP_MEC->PJM
CLTF
10.89
SIGELTFEXP_SIGE->PJM
CLTF
0.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.443
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.278
LAGNLTFEXP_LAGN->PJM
CLTF
3.443
TVALTFEXP_TVA->PJM
CLTF
0.836

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.71 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1745.45
MW Contribution:
13.47
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.13 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1736.23
MW Contribution:
13.38
Bus #Bus NameTypeMW Contribution
274888KELLY CRK;1U
Solar/Wind Harmer
7.14
276776AD2-060 GEN
Solar/Wind Harmer
0.506
958011AF2-095 GEN
Solar/Wind Harmer
17.424
970941AG2-585 GEN
Solar/Wind Harmer
6.655
274770LINCOLN ;1U
Adder
7.212
274771LINCOLN ;2U
Adder
7.212
276893AG1-478 C
Solar/Wind Harmer
0.476
276897AD1-100 C
Solar/Wind Harmer
49.383
274674JOLIET 9 ;6U
Adder
16.221
958481AF2-142 GEN
Solar/Wind Harmer
15.417
958491AF2-143 GEN
Solar/Wind Harmer
14.786
274695ROCKY RD ;2P
Adder
10.932
274693ROCKY RD ;1P
Adder
10.824
274697ROCKY RD ;3P
Adder
2.97
274696ROCKY RD ;4P
Adder
11.189
274683WAUKEGAN ;8U
Adder
20.673
274683WAUKEGAN ;8U
Adder
17.426
962691AG1-118 GEN
Solar/Wind Harmer
28.996
960751AF2-366 GEN
Solar/Wind Harmer
2.76
276901AD2-066 C O1
Solar/Wind Harmer
3.326
971341AH1-150 GEN
Solar/Wind Harmer
18.564
971343AH1-151 GEN
Solar/Wind Harmer
18.564
276872AE1-163_GEN1
Solar/Wind Harmer
6.228
276876AE1-163_GEN2
Solar/Wind Harmer
6.228
972235AH1-702 GEN1
Adder
2.319
972236AH1-702 GEN2
Adder
2.017
938861AE1-114 GEN
Solar/Wind Harmer
7.363
274764LEE CO EC;5U
Adder
8.315
274765LEE CO EC;6U
Adder
8.315
274762LEE CO EC;3U
Adder
8.296
274763LEE CO EC;4U
Adder
8.218
276158O29GEN2
Solar/Wind Harmer
4.314
276157O29GEN1
Solar/Wind Harmer
3.28
276645AC1-214 GEN1
Solar/Wind Harmer
1.122
942111AE2-223 GEN
Solar/Wind Harmer
6.234
960611AF2-352 GEN
Solar/Wind Harmer
1.681
274805UNIV PK N;1U
Adder
3.463
274808UNIV PK N;4U
Adder
3.44
274880W4-005 GEN4
Solar/Wind Harmer
1.77
276174W4-005 GEN2
Solar/Wind Harmer
1.77
276615X2-022 GEN
Solar/Wind Harmer
1.088
276838X2-022 GEN2
Solar/Wind Harmer
0.129
276916AD2-100_GEN
Solar/Wind Harmer
10.091
276911AD2-131_GEN
Solar/Wind Harmer
2.039
274827FISK ;RP
50/50
10.237
960591AF2-350 GEN
Solar/Wind Harmer
12.1
274775LINCOLN ;6U
Adder
7.212
274776LINCOLN ;7U
Adder
7.212
274777LINCOLN ;8U
Adder
7.212
274800UNIV PARK;3U
Adder
6.592
274801UNIV PARK;4U
Adder
6.592
276893AG1-478 C
Solar/Wind Harmer
0.597
274675JOLIET 29;7U
Adder
31.815
274675JOLIET 29;7U
Adder
30.679
274687WILL CNTY;4U
Adder
28.936
274687WILL CNTY;4U
Adder
28.936
972228AH1-698 GEN2
Adder
3.795
972227AH1-698 GEN1
Adder
2.671
274731ELWOOD EC;2P
Adder
16.77
274733ELWOOD EC;3P
Adder
16.77
274735ELWOOD EC;4P
Adder
16.77
274728ELWOOD EC;5P
Adder
16.758
972037AH1-567 GEN1
Adder
0.184
970833AG2-524 GEN
Solar/Wind Harmer
8.753
970833AG2-524 GEN
Solar/Wind Harmer
4.071
274744AC1-111 GEN8
Adder
5.6
274746AC1-111 G10
Adder
5.6
970073AG2-061 GEN
Solar/Wind Harmer
2.292
971411AH1-196 GEN
Solar/Wind Harmer
14.147
971675AH1-338 GEN
Solar/Wind Harmer
16.913
276861AD2-134 GEN
Solar/Wind Harmer
1.676
276863AD2-134 GEN
Solar/Wind Harmer
1.676
971171AH1-044 GEN
Solar/Wind Harmer
18.564
276889AE2-281 GEN
Solar/Wind Harmer
1.78
274823ROCKFORD ;21
Adder
18.019
274856ECOGROVE ;U1
Solar/Wind Harmer
3.071
276611AD2-172 GEN
Solar/Wind Harmer
2.33
276612AE2-035 GEN
Solar/Wind Harmer
2.33
274863CRW1-WTG
Solar/Wind Harmer
5.075
274864CRW2-WTG
Solar/Wind Harmer
5.075
971681AH1-341 GEN
Solar/Wind Harmer
13.474
926823AC1-168 GEN
Solar/Wind Harmer
3.774
972267AH1-718 GEN
Adder
3.635
276741O09 GEN1
Solar/Wind Harmer
3.08
970169AG2-114 GEN
Solar/Wind Harmer
8.572
274877BISHOP HL;1U
Solar/Wind Harmer
2.802
946321AF1-296 GEN
Solar/Wind Harmer
8.577
276726Z2-087_GEN
Solar/Wind Harmer
6.013
959341AF2-225 GEN
Solar/Wind Harmer
11.407
274853TWINGROVE;U1
Solar/Wind Harmer
5.208
274854TWINGROVE;U2
Solar/Wind Harmer
5.099
276668AB2-070 GEN1
Solar/Wind Harmer
1.291
276848AB2-070 GEN3
Solar/Wind Harmer
1.291
276849AB2-070 GEN2
Solar/Wind Harmer
1.291
276763AC1-053 GEN1
Solar/Wind Harmer
2.27
276764AC1-053 GEN2
Solar/Wind Harmer
2.27
274826FISK ;BP
50/50
14.444
276164X3-005 C
Solar/Wind Harmer
0.971
274887GEN-1.85
Solar/Wind Harmer
6.447
276772AC2-154 GEN
Solar/Wind Harmer
3.377
276843GEN-1.7
Solar/Wind Harmer
0.694
276806AD2-047 C O1
Solar/Wind Harmer
12.944
274772LINCOLN ;3U
Adder
7.212
972038AH1-567 GEN2
Adder
0.413
939351AE1-166 GEN
Solar/Wind Harmer
6.305
274676JOLIET 29;8U
Adder
30.67
970707AG2-453 GEN
Solar/Wind Harmer
28.659
972259AH1-714 GEN
Adder
19.481
274729ELWOOD EC;1P
Adder
16.77
274730ELWOOD EC;6P
Adder
16.758
274734ELWOOD EC;8P
Adder
16.758
274736ELWOOD EC;9P
Adder
16.758
274803UNIV PARK;6U
Adder
5.847
943121AE2-341 GEN
Solar/Wind Harmer
15.03
943591AF1-030 GEN
Solar/Wind Harmer
10.02
274682WAUKEGAN ;7U
Adder
17.675
276799AD1-013 GEN
Solar/Wind Harmer
2.078
946671AF1-331 GEN
Solar/Wind Harmer
0.394
276868AE1-113 GEN
Solar/Wind Harmer
9.499
274879MINONK ;1U
Solar/Wind Harmer
6.333
274855GSG-6 ;RU
Solar/Wind Harmer
3.467
274850MENDOTA H;RU
Solar/Wind Harmer
2.41
276602WESTBROOK C
Solar/Wind Harmer
1.996
274862TOP CROP ;2U
Solar/Wind Harmer
4.705
959091AF2-200 GEN
Solar/Wind Harmer
18.564
274857EASY ROAD;U1
Solar/Wind Harmer
4.272
274760LEE CO EC;1U
Adder
8.296
274767LEE CO EC;8U
Adder
8.198
970571AG2-364 GEN
Solar/Wind Harmer
17.75
276603SUBLETTE C
Solar/Wind Harmer
0.931
274851PROVIDENC;RU
Solar/Wind Harmer
2.385
274849CRESCENT ;1U
Solar/Wind Harmer
1.548
276782AC1-033 GEN
Solar/Wind Harmer
3.312
274878BISHOP HL;2U
Solar/Wind Harmer
2.802
965931AG1-462 GEN
Solar/Wind Harmer
20.726
971087AG2-675 GEN
Solar/Wind Harmer
3.024
965091AG1-374 GEN
Solar/Wind Harmer
21.686
959611AF2-252 GEN
Solar/Wind Harmer
1.681
274814UNIV PK N;0U
Adder
3.486
274807UNIV PK N;3U
Adder
3.478
274811UNIV PK N;7U
Adder
3.455
274724RIVER EC ;11
Adder
11.438
276785W4-005 GEN1
Solar/Wind Harmer
1.77
971993AH1-541 GEN
Solar/Wind Harmer
5.408
957381AF2-032 GEN
Solar/Wind Harmer
1.005
942481AE2-261 GEN
Solar/Wind Harmer
14.853
972179AH1-673 GEN
50/50
15.358
274723RIVER EC ;12
50/50
28.604
972207SS24-0001
Solar/Wind Harmer
25.641
274773LINCOLN ;4U
Adder
7.212
274774LINCOLN ;5U
Adder
7.212
941551AE2-152 GEN
Solar/Wind Harmer
4.821
274674JOLIET 9 ;6U
Adder
16.221
274676JOLIET 29;8U
Adder
31.806
276694AA1-018 GEN2
Solar/Wind Harmer
6.485
276691AA1-018 GEN1
Solar/Wind Harmer
0.775
274732ELWOOD EC;7P
Adder
16.758
274802UNIV PARK;5U
Adder
5.847
274745AC1-111 GEN9
Adder
5.6
274871GR RIDGE ;2U
Solar/Wind Harmer
7.669
274847GR RIDGE ;BU
Solar/Wind Harmer
5.043
276805AD2-038 GEN
Solar/Wind Harmer
5.055
274682WAUKEGAN ;7U
Adder
17.675
274828WAUKEGAN ;BP
Adder
10.836
962781AG1-127 GEN
Solar/Wind Harmer
9.148
274872LEEDK;1U
Solar/Wind Harmer
7.86
939401AE1-172 GEN
Solar/Wind Harmer
13.297
276882AE2-255 GEN
Solar/Wind Harmer
3.166
274861TOP CROP ;1U
Solar/Wind Harmer
5.635
971997AH1-543 GEN
Solar/Wind Harmer
14.627
957471AF2-041 GEN
Solar/Wind Harmer
27.846
959081AF2-199 GEN
Solar/Wind Harmer
9.282
971067AG2-660 GEN
Solar/Wind Harmer
2.159
274822ROCKFORD ;11
Adder
18.15
970819AG2-516 GEN
Solar/Wind Harmer
10.975
274858EASY ROAD;U2
Solar/Wind Harmer
4.272
274761LEE CO EC;2U
Adder
8.296
274766LEE CO EC;7U
Adder
8.198
970569AG2-363 GEN
Solar/Wind Harmer
26.625
276708O09 GEN2
Solar/Wind Harmer
3.08
276646AC1-214 GEN2
Solar/Wind Harmer
1.122
274848CAMPGROVE;RU
Solar/Wind Harmer
5.294
276655WTG1_EQ
Solar/Wind Harmer
6.637
276656WTG2_EQ
Solar/Wind Harmer
0.879
939741AE1-205 GEN
Solar/Wind Harmer
15.209
274812UNIV PK N;8U
Adder
3.455
276686W4-005 GEN3
Solar/Wind Harmer
1.77
276621W2-048 GEN
Solar/Wind Harmer
3.465
965911AG1-460 GEN
Solar/Wind Harmer
0.693
991777J1629 G
External Queue
11.035294532775879
990512J1326
External Queue
4.86438512802124
990117J1214
External Queue
16.733484268188477
990727J1377 G
External Queue
5.651099681854248
991092J1477
External Queue
2.615652084350586
991303J1755 G
External Queue
4.176714897155762
990407J1304
External Queue
3.7622783184051514
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.173
NYPJM->LTFIMP_NY
CLTF
0.838
WECLTFEXP_WEC->PJM
CLTF
3.521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.395
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.462
MECLTFEXP_MEC->PJM
CLTF
10.935
SIGELTFEXP_SIGE->PJM
CLTF
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.348
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.409
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.163
LAGNLTFEXP_LAGN->PJM
CLTF
3.555
TVALTFEXP_TVA->PJM
CLTF
0.891

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.71 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1745.44
MW Contribution:
13.47
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.12 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1736.16
MW Contribution:
13.38
Bus #Bus NameTypeMW Contribution
274888KELLY CRK;1U
Solar/Wind Harmer
7.14
276776AD2-060 GEN
Solar/Wind Harmer
0.506
958011AF2-095 GEN
Solar/Wind Harmer
17.424
970941AG2-585 GEN
Solar/Wind Harmer
6.655
274770LINCOLN ;1U
Adder
7.215
274771LINCOLN ;2U
Adder
7.215
276893AG1-478 C
Solar/Wind Harmer
0.476
276897AD1-100 C
Solar/Wind Harmer
49.384
274674JOLIET 9 ;6U
Adder
16.22
958481AF2-142 GEN
Solar/Wind Harmer
15.417
958491AF2-143 GEN
Solar/Wind Harmer
14.786
274695ROCKY RD ;2P
Adder
10.931
274693ROCKY RD ;1P
Adder
10.824
274697ROCKY RD ;3P
Adder
2.969
274696ROCKY RD ;4P
Adder
11.189
274683WAUKEGAN ;8U
Adder
20.672
274683WAUKEGAN ;8U
Adder
17.425
274827FISK ;RP
50/50
10.237
960591AF2-350 GEN
Solar/Wind Harmer
12.1
274775LINCOLN ;6U
Adder
7.215
274776LINCOLN ;7U
Adder
7.215
274777LINCOLN ;8U
Adder
7.215
274800UNIV PARK;3U
Adder
6.592
274801UNIV PARK;4U
Adder
6.592
276893AG1-478 C
Solar/Wind Harmer
0.597
274675JOLIET 29;7U
Adder
31.815
274675JOLIET 29;7U
Adder
30.679
274687WILL CNTY;4U
Adder
28.936
274687WILL CNTY;4U
Adder
28.936
972228AH1-698 GEN2
Adder
3.795
972227AH1-698 GEN1
Adder
2.671
274731ELWOOD EC;2P
Adder
16.77
274733ELWOOD EC;3P
Adder
16.77
274735ELWOOD EC;4P
Adder
16.77
274728ELWOOD EC;5P
Adder
16.758
972037AH1-567 GEN1
Adder
0.184
970833AG2-524 GEN
Solar/Wind Harmer
8.752
970833AG2-524 GEN
Solar/Wind Harmer
4.071
274744AC1-111 GEN8
Adder
5.6
274746AC1-111 G10
Adder
5.6
970073AG2-061 GEN
Solar/Wind Harmer
2.292
971411AH1-196 GEN
Solar/Wind Harmer
14.146
971675AH1-338 GEN
Solar/Wind Harmer
16.911
276861AD2-134 GEN
Solar/Wind Harmer
1.676
276863AD2-134 GEN
Solar/Wind Harmer
1.676
971171AH1-044 GEN
Solar/Wind Harmer
18.562
276889AE2-281 GEN
Solar/Wind Harmer
1.78
274823ROCKFORD ;21
Adder
18.018
274856ECOGROVE ;U1
Solar/Wind Harmer
3.071
276611AD2-172 GEN
Solar/Wind Harmer
2.33
276612AE2-035 GEN
Solar/Wind Harmer
2.33
274863CRW1-WTG
Solar/Wind Harmer
5.075
274864CRW2-WTG
Solar/Wind Harmer
5.075
971681AH1-341 GEN
Solar/Wind Harmer
13.473
926823AC1-168 GEN
Solar/Wind Harmer
3.774
972267AH1-718 GEN
Adder
3.635
276741O09 GEN1
Solar/Wind Harmer
3.08
970169AG2-114 GEN
Solar/Wind Harmer
8.571
274877BISHOP HL;1U
Solar/Wind Harmer
2.802
946321AF1-296 GEN
Solar/Wind Harmer
8.576
276726Z2-087_GEN
Solar/Wind Harmer
6.013
959341AF2-225 GEN
Solar/Wind Harmer
11.406
274853TWINGROVE;U1
Solar/Wind Harmer
5.208
274854TWINGROVE;U2
Solar/Wind Harmer
5.099
276668AB2-070 GEN1
Solar/Wind Harmer
1.291
276848AB2-070 GEN3
Solar/Wind Harmer
1.291
276849AB2-070 GEN2
Solar/Wind Harmer
1.291
276763AC1-053 GEN1
Solar/Wind Harmer
2.27
276764AC1-053 GEN2
Solar/Wind Harmer
2.27
274826FISK ;BP
50/50
14.444
276164X3-005 C
Solar/Wind Harmer
0.971
274887GEN-1.85
Solar/Wind Harmer
6.447
276772AC2-154 GEN
Solar/Wind Harmer
3.377
276843GEN-1.7
Solar/Wind Harmer
0.694
276806AD2-047 C O1
Solar/Wind Harmer
12.944
274772LINCOLN ;3U
Adder
7.215
972038AH1-567 GEN2
Adder
0.413
939351AE1-166 GEN
Solar/Wind Harmer
6.305
274676JOLIET 29;8U
Adder
30.669
970707AG2-453 GEN
Solar/Wind Harmer
28.655
972259AH1-714 GEN
Adder
19.48
274729ELWOOD EC;1P
Adder
16.77
274730ELWOOD EC;6P
Adder
16.758
274734ELWOOD EC;8P
Adder
16.758
274736ELWOOD EC;9P
Adder
16.758
274803UNIV PARK;6U
Adder
5.847
943121AE2-341 GEN
Solar/Wind Harmer
15.029
943591AF1-030 GEN
Solar/Wind Harmer
10.019
274682WAUKEGAN ;7U
Adder
17.674
276799AD1-013 GEN
Solar/Wind Harmer
2.078
946671AF1-331 GEN
Solar/Wind Harmer
0.394
276868AE1-113 GEN
Solar/Wind Harmer
9.499
274879MINONK ;1U
Solar/Wind Harmer
6.333
274855GSG-6 ;RU
Solar/Wind Harmer
3.467
274850MENDOTA H;RU
Solar/Wind Harmer
2.41
276602WESTBROOK C
Solar/Wind Harmer
1.996
274862TOP CROP ;2U
Solar/Wind Harmer
4.705
959091AF2-200 GEN
Solar/Wind Harmer
18.562
274857EASY ROAD;U1
Solar/Wind Harmer
4.272
274760LEE CO EC;1U
Adder
8.295
274767LEE CO EC;8U
Adder
8.198
970571AG2-364 GEN
Solar/Wind Harmer
17.75
276603SUBLETTE C
Solar/Wind Harmer
0.931
274851PROVIDENC;RU
Solar/Wind Harmer
2.385
274849CRESCENT ;1U
Solar/Wind Harmer
1.548
276782AC1-033 GEN
Solar/Wind Harmer
3.312
274878BISHOP HL;2U
Solar/Wind Harmer
2.802
965931AG1-462 GEN
Solar/Wind Harmer
20.725
971087AG2-675 GEN
Solar/Wind Harmer
3.024
965091AG1-374 GEN
Solar/Wind Harmer
21.686
959611AF2-252 GEN
Solar/Wind Harmer
1.681
274814UNIV PK N;0U
Adder
3.486
274807UNIV PK N;3U
Adder
3.478
274811UNIV PK N;7U
Adder
3.455
274724RIVER EC ;11
Adder
11.439
276785W4-005 GEN1
Solar/Wind Harmer
1.77
971993AH1-541 GEN
Solar/Wind Harmer
5.408
957381AF2-032 GEN
Solar/Wind Harmer
1.005
942481AE2-261 GEN
Solar/Wind Harmer
14.853
962691AG1-118 GEN
Solar/Wind Harmer
28.994
960751AF2-366 GEN
Solar/Wind Harmer
2.76
276901AD2-066 C O1
Solar/Wind Harmer
3.326
971341AH1-150 GEN
Solar/Wind Harmer
18.562
971343AH1-151 GEN
Solar/Wind Harmer
18.562
276872AE1-163_GEN1
Solar/Wind Harmer
6.228
276876AE1-163_GEN2
Solar/Wind Harmer
6.228
972235AH1-702 GEN1
Adder
2.319
972236AH1-702 GEN2
Adder
2.017
938861AE1-114 GEN
Solar/Wind Harmer
7.363
274764LEE CO EC;5U
Adder
8.315
274765LEE CO EC;6U
Adder
8.315
274762LEE CO EC;3U
Adder
8.295
274763LEE CO EC;4U
Adder
8.217
276158O29GEN2
Solar/Wind Harmer
4.314
276157O29GEN1
Solar/Wind Harmer
3.28
276645AC1-214 GEN1
Solar/Wind Harmer
1.122
942111AE2-223 GEN
Solar/Wind Harmer
6.234
960611AF2-352 GEN
Solar/Wind Harmer
1.681
274805UNIV PK N;1U
Adder
3.463
274808UNIV PK N;4U
Adder
3.44
274880W4-005 GEN4
Solar/Wind Harmer
1.77
276174W4-005 GEN2
Solar/Wind Harmer
1.77
276615X2-022 GEN
Solar/Wind Harmer
1.088
276838X2-022 GEN2
Solar/Wind Harmer
0.129
276916AD2-100_GEN
Solar/Wind Harmer
10.091
276911AD2-131_GEN
Solar/Wind Harmer
2.039
972179AH1-673 GEN
50/50
15.358
274723RIVER EC ;12
50/50
28.605
972207SS24-0001
Solar/Wind Harmer
25.652
274773LINCOLN ;4U
Adder
7.215
274774LINCOLN ;5U
Adder
7.215
941551AE2-152 GEN
Solar/Wind Harmer
4.822
274674JOLIET 9 ;6U
Adder
16.22
274676JOLIET 29;8U
Adder
31.805
276694AA1-018 GEN2
Solar/Wind Harmer
6.485
276691AA1-018 GEN1
Solar/Wind Harmer
0.775
274732ELWOOD EC;7P
Adder
16.758
274802UNIV PARK;5U
Adder
5.847
274745AC1-111 GEN9
Adder
5.6
274871GR RIDGE ;2U
Solar/Wind Harmer
7.669
274847GR RIDGE ;BU
Solar/Wind Harmer
5.042
276805AD2-038 GEN
Solar/Wind Harmer
5.055
274682WAUKEGAN ;7U
Adder
17.674
274828WAUKEGAN ;BP
Adder
10.836
962781AG1-127 GEN
Solar/Wind Harmer
9.147
274872LEEDK;1U
Solar/Wind Harmer
7.859
939401AE1-172 GEN
Solar/Wind Harmer
13.297
276882AE2-255 GEN
Solar/Wind Harmer
3.166
274861TOP CROP ;1U
Solar/Wind Harmer
5.635
971997AH1-543 GEN
Solar/Wind Harmer
14.626
957471AF2-041 GEN
Solar/Wind Harmer
27.843
959081AF2-199 GEN
Solar/Wind Harmer
9.281
971067AG2-660 GEN
Solar/Wind Harmer
2.158
274822ROCKFORD ;11
Adder
18.149
970819AG2-516 GEN
Solar/Wind Harmer
10.974
274858EASY ROAD;U2
Solar/Wind Harmer
4.272
274761LEE CO EC;2U
Adder
8.295
274766LEE CO EC;7U
Adder
8.198
970569AG2-363 GEN
Solar/Wind Harmer
26.624
276708O09 GEN2
Solar/Wind Harmer
3.08
276646AC1-214 GEN2
Solar/Wind Harmer
1.122
274848CAMPGROVE;RU
Solar/Wind Harmer
5.293
276655WTG1_EQ
Solar/Wind Harmer
6.637
276656WTG2_EQ
Solar/Wind Harmer
0.879
939741AE1-205 GEN
Solar/Wind Harmer
15.209
274812UNIV PK N;8U
Adder
3.455
276686W4-005 GEN3
Solar/Wind Harmer
1.77
276621W2-048 GEN
Solar/Wind Harmer
3.465
965911AG1-460 GEN
Solar/Wind Harmer
0.693
991777J1629 G
External Queue
11.034590721130371
990512J1326
External Queue
4.864051818847656
990117J1214
External Queue
16.732337951660156
990727J1377 G
External Queue
5.650698184967041
991092J1477
External Queue
2.6154966354370117
991303J1755 G
External Queue
4.176537036895752
990407J1304
External Queue
3.7620158195495605
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.173
NYPJM->LTFIMP_NY
CLTF
0.838
WECLTFEXP_WEC->PJM
CLTF
3.521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.668
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.395
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.461
MECLTFEXP_MEC->PJM
CLTF
10.935
SIGELTFEXP_SIGE->PJM
CLTF
0.01
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.348
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.409
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.162
LAGNLTFEXP_LAGN->PJM
CLTF
3.555
TVALTFEXP_TVA->PJM
CLTF
0.891

Details for CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT7-8___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT7-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.42 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1684.35
MW Contribution:
21.45
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT7-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.37 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1683.52
MW Contribution:
21.39
Bus #Bus NameTypeMW Contribution
274657BYRON ;2U
50/50
4.679
274823ROCKFORD ;21
50/50
43.646
274856ECOGROVE ;U1
Solar/Wind Harmer
6.106
276611AD2-172 GEN
Solar/Wind Harmer
4.632
276612AE2-035 GEN
Solar/Wind Harmer
4.632
971681AH1-341 GEN
Solar/Wind Harmer
21.445
972267AH1-718 GEN
Adder
4.513
276741O09 GEN1
Solar/Wind Harmer
3.251
946321AF1-296 GEN
Solar/Wind Harmer
9.257
276861AD2-134 GEN
Solar/Wind Harmer
1.457
276863AD2-134 GEN
Solar/Wind Harmer
1.457
971675AH1-338 GEN
Solar/Wind Harmer
14.608
971171AH1-044 GEN
Solar/Wind Harmer
10.215
274656BYRON ;1U
50/50
4.815
274824ROCKFORD ;12
50/50
34.364
274857EASY ROAD;U1
Solar/Wind Harmer
7.256
274760LEE CO EC;1U
Adder
14.092
274767LEE CO EC;8U
Adder
13.926
276603SUBLETTE C
Solar/Wind Harmer
1.213
965931AG1-462 GEN
Solar/Wind Harmer
21.963
971087AG2-675 GEN
Solar/Wind Harmer
3.205
274855GSG-6 ;RU
Solar/Wind Harmer
3.013
274850MENDOTA H;RU
Solar/Wind Harmer
2.095
276602WESTBROOK C
Solar/Wind Harmer
1.734
276799AD1-013 GEN
Solar/Wind Harmer
1.781
946671AF1-331 GEN
Solar/Wind Harmer
0.337
959091AF2-200 GEN
Solar/Wind Harmer
10.215
972236AH1-702 GEN2
50/50
5.054
972235AH1-702 GEN1
50/50
5.805
274764LEE CO EC;5U
Adder
14.125
274765LEE CO EC;6U
Adder
14.125
274762LEE CO EC;3U
Adder
14.092
274763LEE CO EC;4U
Adder
13.959
938861AE1-114 GEN
Solar/Wind Harmer
12.192
276158O29GEN2
Solar/Wind Harmer
4.553
276157O29GEN1
Solar/Wind Harmer
3.462
960751AF2-366 GEN
Solar/Wind Harmer
2.156
962691AG1-118 GEN
Solar/Wind Harmer
17.965
971341AH1-150 GEN
Solar/Wind Harmer
10.215
971343AH1-151 GEN
Solar/Wind Harmer
10.215
972031AH1-564 GEN
50/50
36.821
274822ROCKFORD ;11
50/50
43.963
970819AG2-516 GEN
Solar/Wind Harmer
23.288
274858EASY ROAD;U2
Solar/Wind Harmer
7.256
274761LEE CO EC;2U
Adder
14.092
274766LEE CO EC;7U
Adder
13.926
276708O09 GEN2
Solar/Wind Harmer
3.251
962781AG1-127 GEN
Solar/Wind Harmer
7.147
274872LEEDK;1U
Solar/Wind Harmer
5.695
957471AF2-041 GEN
Solar/Wind Harmer
15.322
959081AF2-199 GEN
Solar/Wind Harmer
5.107
971067AG2-660 GEN
Solar/Wind Harmer
1.188
991777J1629 G
External Queue
9.221789360046387
990512J1326
External Queue
9.45048999786377
990117J1214
External Queue
32.50968551635742
990727J1377 G
External Queue
13.989998817443848
991092J1477
External Queue
2.8669803142547607
990407J1304
External Queue
8.001517295837402
NYPJM->LTFIMP_NY
CLTF
0.245
WECLTFEXP_WEC->PJM
CLTF
0.771
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.04
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.914
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.315
MECLTFEXP_MEC->PJM
CLTF
9.276
SIGELTFEXP_SIGE->PJM
CLTF
0.002
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.142
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.401
LAGNLTFEXP_LAGN->PJM
CLTF
2.57
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.131
TVALTFEXP_TVA->PJM
CLTF
0.658

Details for CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT5-8___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT5-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.28 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1682.12
MW Contribution:
21.36
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT5-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.23 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1681.29
MW Contribution:
21.31
Bus #Bus NameTypeMW Contribution
972236AH1-702 GEN2
50/50
5.01
972235AH1-702 GEN1
50/50
5.755
274764LEE CO EC;5U
Adder
14.088
274765LEE CO EC;6U
Adder
14.088
274762LEE CO EC;3U
Adder
14.055
274763LEE CO EC;4U
Adder
13.922
938861AE1-114 GEN
Solar/Wind Harmer
12.132
276158O29GEN2
Solar/Wind Harmer
4.571
276157O29GEN1
Solar/Wind Harmer
3.476
960751AF2-366 GEN
Solar/Wind Harmer
2.181
962691AG1-118 GEN
Solar/Wind Harmer
18.362
971341AH1-150 GEN
Solar/Wind Harmer
10.951
971343AH1-151 GEN
Solar/Wind Harmer
10.951
274657BYRON ;2U
50/50
4.638
274823ROCKFORD ;21
50/50
43.146
274856ECOGROVE ;U1
Solar/Wind Harmer
6.052
276611AD2-172 GEN
Solar/Wind Harmer
4.591
276612AE2-035 GEN
Solar/Wind Harmer
4.591
971681AH1-341 GEN
Solar/Wind Harmer
21.364
972267AH1-718 GEN
Adder
4.537
276741O09 GEN1
Solar/Wind Harmer
3.264
946321AF1-296 GEN
Solar/Wind Harmer
9.281
276861AD2-134 GEN
Solar/Wind Harmer
1.47
276863AD2-134 GEN
Solar/Wind Harmer
1.47
971675AH1-338 GEN
Solar/Wind Harmer
14.744
971171AH1-044 GEN
Solar/Wind Harmer
10.951
274656BYRON ;1U
50/50
4.773
274824ROCKFORD ;12
50/50
33.97
274857EASY ROAD;U1
Solar/Wind Harmer
7.237
274760LEE CO EC;1U
Adder
14.055
274767LEE CO EC;8U
Adder
13.889
276603SUBLETTE C
Solar/Wind Harmer
1.214
965931AG1-462 GEN
Solar/Wind Harmer
22.033
971087AG2-675 GEN
Solar/Wind Harmer
3.215
274855GSG-6 ;RU
Solar/Wind Harmer
3.041
274850MENDOTA H;RU
Solar/Wind Harmer
2.114
276602WESTBROOK C
Solar/Wind Harmer
1.75
276799AD1-013 GEN
Solar/Wind Harmer
1.798
946671AF1-331 GEN
Solar/Wind Harmer
0.341
959091AF2-200 GEN
Solar/Wind Harmer
10.951
972031AH1-564 GEN
50/50
36.4
274822ROCKFORD ;11
50/50
43.459
970819AG2-516 GEN
Solar/Wind Harmer
23.055
274858EASY ROAD;U2
Solar/Wind Harmer
7.237
274761LEE CO EC;2U
Adder
14.055
274766LEE CO EC;7U
Adder
13.889
276708O09 GEN2
Solar/Wind Harmer
3.264
962781AG1-127 GEN
Solar/Wind Harmer
7.228
274872LEEDK;1U
Solar/Wind Harmer
5.774
957471AF2-041 GEN
Solar/Wind Harmer
16.426
959081AF2-199 GEN
Solar/Wind Harmer
5.475
971067AG2-660 GEN
Solar/Wind Harmer
1.273
991777J1629 G
External Queue
9.072366714477539
990512J1326
External Queue
9.348932266235352
990117J1214
External Queue
32.16032409667969
990727J1377 G
External Queue
13.844555854797363
991092J1477
External Queue
2.8871541023254395
990407J1304
External Queue
7.912186622619629
NYPJM->LTFIMP_NY
CLTF
0.244
WECLTFEXP_WEC->PJM
CLTF
0.738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.616
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.907
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.262
MECLTFEXP_MEC->PJM
CLTF
9.249
SIGELTFEXP_SIGE->PJM
CLTF
0.002
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.141
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
2.561
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.132
TVALTFEXP_TVA->PJM
CLTF
0.655

Details for CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line l/o COMED_P4-6_006-345-BT78___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_006-345-BT78___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.77 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1658.52
MW Contribution:
21.21
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_006-345-BT78___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.72 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1657.7
MW Contribution:
21.16
Bus #Bus NameTypeMW Contribution
274824ROCKFORD ;12
50/50
35.423
274656BYRON ;1U
50/50
4.367
274857EASY ROAD;U1
Solar/Wind Harmer
6.657
274760LEE CO EC;1U
Adder
12.927
274767LEE CO EC;8U
Adder
12.775
276603SUBLETTE C
Solar/Wind Harmer
1.171
965931AG1-462 GEN
Solar/Wind Harmer
20.81
971087AG2-675 GEN
Solar/Wind Harmer
3.037
274855GSG-6 ;RU
Solar/Wind Harmer
2.98
274850MENDOTA H;RU
Solar/Wind Harmer
2.072
276602WESTBROOK C
Solar/Wind Harmer
1.716
276799AD1-013 GEN
Solar/Wind Harmer
1.763
946671AF1-331 GEN
Solar/Wind Harmer
0.334
959091AF2-200 GEN
Solar/Wind Harmer
9.412
972236AH1-702 GEN2
50/50
5.664
972235AH1-702 GEN1
50/50
5.265
938861AE1-114 GEN
Solar/Wind Harmer
12.223
274764LEE CO EC;5U
Adder
12.958
274765LEE CO EC;6U
Adder
12.958
274762LEE CO EC;3U
Adder
12.927
274763LEE CO EC;4U
Adder
12.806
276158O29GEN2
Solar/Wind Harmer
4.296
276157O29GEN1
Solar/Wind Harmer
3.266
960751AF2-366 GEN
Solar/Wind Harmer
2.183
962691AG1-118 GEN
Solar/Wind Harmer
18.157
971341AH1-150 GEN
Solar/Wind Harmer
9.412
971343AH1-151 GEN
Solar/Wind Harmer
9.412
274822ROCKFORD ;11
50/50
45.318
972031AH1-564 GEN
50/50
37.955
970819AG2-516 GEN
Solar/Wind Harmer
24.222
274858EASY ROAD;U2
Solar/Wind Harmer
6.657
274761LEE CO EC;2U
Adder
12.927
274766LEE CO EC;7U
Adder
12.775
276708O09 GEN2
Solar/Wind Harmer
3.067
962781AG1-127 GEN
Solar/Wind Harmer
7.236
274872LEEDK;1U
Solar/Wind Harmer
5.712
957471AF2-041 GEN
Solar/Wind Harmer
14.118
959081AF2-199 GEN
Solar/Wind Harmer
4.706
971067AG2-660 GEN
Solar/Wind Harmer
1.094
274657BYRON ;2U
50/50
5.244
274823ROCKFORD ;21
50/50
44.99
274856ECOGROVE ;U1
Solar/Wind Harmer
6.268
276611AD2-172 GEN
Solar/Wind Harmer
4.755
276612AE2-035 GEN
Solar/Wind Harmer
4.755
971681AH1-341 GEN
Solar/Wind Harmer
21.212
972267AH1-718 GEN
Adder
4.202
276741O09 GEN1
Solar/Wind Harmer
3.067
946321AF1-296 GEN
Solar/Wind Harmer
8.818
276861AD2-134 GEN
Solar/Wind Harmer
1.441
276863AD2-134 GEN
Solar/Wind Harmer
1.441
971675AH1-338 GEN
Solar/Wind Harmer
14.455
971171AH1-044 GEN
Solar/Wind Harmer
9.412
991777J1629 G
External Queue
9.970706939697266
990512J1326
External Queue
10.093079566955566
990117J1214
External Queue
34.720191955566406
990727J1377 G
External Queue
14.965534210205078
991092J1477
External Queue
2.653498649597168
990407J1304
External Queue
8.583191871643066
NYPJM->LTFIMP_NY
CLTF
0.242
WECLTFEXP_WEC->PJM
CLTF
0.882
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.876
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.042
MECLTFEXP_MEC->PJM
CLTF
9.175
SIGELTFEXP_SIGE->PJM
CLTF
0.002
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.011
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.141
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.4
LAGNLTFEXP_LAGN->PJM
CLTF
2.534
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.126
TVALTFEXP_TVA->PJM
CLTF
0.645

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.12 %
Rating:2112.0 MVA
Rating Type:B
MVA to Mitigate:2410.19
MW Contribution:
16.39
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.31 %
Rating:2112.0 MVA
Rating Type:B
MVA to Mitigate:2393.07
MW Contribution:
16.14
Bus #Bus NameTypeMW Contribution
274711KENDALL ;4S
50/50
0.935
274709KENDALL ;3S
50/50
0.935
276897AD1-100 C
Solar/Wind Harmer
56.385
274683WAUKEGAN ;8U
Adder
25.335
274683WAUKEGAN ;8U
Adder
21.356
274696ROCKY RD ;4P
Adder
13.612
274695ROCKY RD ;2P
Adder
13.298
274693ROCKY RD ;1P
Adder
13.167
274697ROCKY RD ;3P
Adder
3.612
276893AG1-478 C
Solar/Wind Harmer
0.519
274674JOLIET 9 ;6U
Adder
18.041
962691AG1-118 GEN
Solar/Wind Harmer
35.014
274770LINCOLN ;1U
Adder
7.209
274771LINCOLN ;2U
Adder
7.209
960751AF2-366 GEN
Solar/Wind Harmer
3.334
276901AD2-066 C O1
Solar/Wind Harmer
3.988
274888KELLY CRK;1U
Solar/Wind Harmer
6.659
276776AD2-060 GEN
Solar/Wind Harmer
0.472
958011AF2-095 GEN
Solar/Wind Harmer
16.249
970941AG2-585 GEN
Solar/Wind Harmer
6.206
971341AH1-150 GEN
Solar/Wind Harmer
22.556
971343AH1-151 GEN
Solar/Wind Harmer
22.556
972235AH1-702 GEN1
Adder
2.823
972236AH1-702 GEN2
Adder
2.455
958481AF2-142 GEN
Solar/Wind Harmer
16.744
958491AF2-143 GEN
Solar/Wind Harmer
16.706
276872AE1-163_GEN1
Solar/Wind Harmer
7.455
276876AE1-163_GEN2
Solar/Wind Harmer
7.455
938861AE1-114 GEN
Solar/Wind Harmer
8.959
274764LEE CO EC;5U
Adder
10.121
274765LEE CO EC;6U
Adder
10.121
274762LEE CO EC;3U
Adder
10.097
274763LEE CO EC;4U
Adder
10.002
276158O29GEN2
Solar/Wind Harmer
5.254
276157O29GEN1
Solar/Wind Harmer
3.994
274751CRETE EC ;1U
50/50
21.713
274754CRETE EC ;4U
50/50
21.713
960281AF2-319 GEN
50/50
3.2
274705KENDALL ;1S
50/50
1.001
274710KENDALL ;4C
50/50
1.4
274861TOP CROP ;1U
Solar/Wind Harmer
8.335
274676JOLIET 29;8U
Adder
39.435
274732ELWOOD EC;7P
Adder
21.096
274871GR RIDGE ;2U
Solar/Wind Harmer
9.534
274847GR RIDGE ;BU
Solar/Wind Harmer
6.269
941551AE2-152 GEN
Solar/Wind Harmer
5.505
274745AC1-111 GEN9
Adder
6.756
274682WAUKEGAN ;7U
Adder
21.661
274828WAUKEGAN ;BP
Adder
13.28
276882AE2-255 GEN
Solar/Wind Harmer
3.962
274674JOLIET 9 ;6U
Adder
18.041
972207SS24-0001
Solar/Wind Harmer
25.632
274773LINCOLN ;4U
Adder
7.209
274774LINCOLN ;5U
Adder
7.209
962781AG1-127 GEN
Solar/Wind Harmer
11.052
274872LEEDK;1U
Solar/Wind Harmer
9.495
971997AH1-543 GEN
Solar/Wind Harmer
17.791
957471AF2-041 GEN
Solar/Wind Harmer
33.834
959081AF2-199 GEN
Solar/Wind Harmer
11.278
971067AG2-660 GEN
Solar/Wind Harmer
2.623
274822ROCKFORD ;11
Adder
22.098
276694AA1-018 GEN2
Solar/Wind Harmer
7.044
276691AA1-018 GEN1
Solar/Wind Harmer
0.842
276805AD2-038 GEN
Solar/Wind Harmer
5.711
970819AG2-516 GEN
Solar/Wind Harmer
13.364
970569AG2-363 GEN
Solar/Wind Harmer
33.233
274858EASY ROAD;U2
Solar/Wind Harmer
5.199
274761LEE CO EC;2U
Adder
10.097
274766LEE CO EC;7U
Adder
9.978
939401AE1-172 GEN
Solar/Wind Harmer
15.078
276708O09 GEN2
Solar/Wind Harmer
3.751
276646AC1-214 GEN2
Solar/Wind Harmer
1.367
972227AH1-698 GEN1
50/50
3.693
274655BRAIDWOOD;2U
50/50
4.895
972228AH1-698 GEN2
50/50
5.229
274687WILL CNTY;4U
50/50
38.863
274687WILL CNTY;4U
50/50
38.863
274704KENDALL ;1C
50/50
1.498
274706KENDALL ;2C
50/50
1.498
274708KENDALL ;3C
50/50
1.416
274675JOLIET 29;7U
Adder
39.41
274675JOLIET 29;7U
Adder
38.003
274728ELWOOD EC;5P
Adder
21.096
274731ELWOOD EC;2P
Adder
21.05
274733ELWOOD EC;3P
Adder
21.05
274735ELWOOD EC;4P
Adder
21.05
970833AG2-524 GEN
Solar/Wind Harmer
10.754
970833AG2-524 GEN
Solar/Wind Harmer
5.002
274744AC1-111 GEN8
Adder
6.756
274746AC1-111 G10
Adder
6.756
276893AG1-478 C
Solar/Wind Harmer
0.651
274827FISK ;RP
Adder
9.026
274775LINCOLN ;6U
Adder
7.209
274776LINCOLN ;7U
Adder
7.209
274777LINCOLN ;8U
Adder
7.209
971411AH1-196 GEN
Solar/Wind Harmer
17.235
971675AH1-338 GEN
Solar/Wind Harmer
20.464
276861AD2-134 GEN
Solar/Wind Harmer
2.029
276863AD2-134 GEN
Solar/Wind Harmer
2.029
960591AF2-350 GEN
Solar/Wind Harmer
11.284
971171AH1-044 GEN
Solar/Wind Harmer
22.556
274823ROCKFORD ;21
Adder
21.938
970073AG2-061 GEN
Solar/Wind Harmer
2.59
276889AE2-281 GEN
Solar/Wind Harmer
2.13
274856ECOGROVE ;U1
Solar/Wind Harmer
3.739
276611AD2-172 GEN
Solar/Wind Harmer
2.836
276612AE2-035 GEN
Solar/Wind Harmer
2.836
971681AH1-341 GEN
Solar/Wind Harmer
16.389
926823AC1-168 GEN
Solar/Wind Harmer
4.622
972267AH1-718 GEN
Adder
4.424
276741O09 GEN1
Solar/Wind Harmer
3.751
274800UNIV PARK;3U
Adder
6.074
274801UNIV PARK;4U
Adder
6.074
274863CRW1-WTG
Solar/Wind Harmer
5.796
274864CRW2-WTG
Solar/Wind Harmer
5.796
274877BISHOP HL;1U
Solar/Wind Harmer
3.42
946321AF1-296 GEN
Solar/Wind Harmer
10.446
970169AG2-114 GEN
Solar/Wind Harmer
10.007
972037AH1-567 GEN1
Adder
0.18
276726Z2-087_GEN
Solar/Wind Harmer
6.986
959341AF2-225 GEN
Solar/Wind Harmer
13.253
274853TWINGROVE;U1
Solar/Wind Harmer
6.058
274854TWINGROVE;U2
Solar/Wind Harmer
5.931
276668AB2-070 GEN1
Solar/Wind Harmer
1.516
276848AB2-070 GEN3
Solar/Wind Harmer
1.516
276849AB2-070 GEN2
Solar/Wind Harmer
1.516
276763AC1-053 GEN1
Solar/Wind Harmer
2.667
276645AC1-214 GEN1
Solar/Wind Harmer
1.367
942111AE2-223 GEN
Solar/Wind Harmer
7.243
960611AF2-352 GEN
Solar/Wind Harmer
1.956
274805UNIV PK N;1U
Adder
3.711
274808UNIV PK N;4U
Adder
3.687
274880W4-005 GEN4
Solar/Wind Harmer
2.074
276174W4-005 GEN2
Solar/Wind Harmer
2.074
276615X2-022 GEN
Solar/Wind Harmer
1.281
276838X2-022 GEN2
Solar/Wind Harmer
0.152
276916AD2-100_GEN
Solar/Wind Harmer
11.868
276911AD2-131_GEN
Solar/Wind Harmer
2.399
274752CRETE EC ;2U
50/50
21.713
274753CRETE EC ;3U
50/50
21.713
959351AF2-226 GEN
50/50
3.2
274654BRAIDWOOD;1U
50/50
5.059
274707KENDALL ;2S
50/50
1.001
972231SS25-0005
Solar/Wind Harmer
39.731
972181SS23-001
Solar/Wind Harmer
24.832
274862TOP CROP ;2U
Solar/Wind Harmer
6.96
274676JOLIET 29;8U
Adder
38.026
972259AH1-714 GEN
Adder
24.515
274730ELWOOD EC;6P
Adder
21.096
274734ELWOOD EC;8P
Adder
21.096
274736ELWOOD EC;9P
Adder
21.096
274729ELWOOD EC;1P
Adder
21.05
970707AG2-453 GEN
Solar/Wind Harmer
34.964
939351AE1-166 GEN
Solar/Wind Harmer
7.198
274682WAUKEGAN ;7U
Adder
21.661
943121AE2-341 GEN
Solar/Wind Harmer
18.003
943591AF1-030 GEN
Solar/Wind Harmer
12.002
276868AE1-113 GEN
Solar/Wind Harmer
11.884
274879MINONK ;1U
Solar/Wind Harmer
7.923
274826FISK ;BP
Adder
12.736
274772LINCOLN ;3U
Adder
7.209
276799AD1-013 GEN
Solar/Wind Harmer
2.514
946671AF1-331 GEN
Solar/Wind Harmer
0.476
274855GSG-6 ;RU
Solar/Wind Harmer
4.195
274850MENDOTA H;RU
Solar/Wind Harmer
2.917
276602WESTBROOK C
Solar/Wind Harmer
2.415
274887GEN-1.85
Solar/Wind Harmer
6.012
276772AC2-154 GEN
Solar/Wind Harmer
3.149
276843GEN-1.7
Solar/Wind Harmer
0.647
276806AD2-047 C O1
Solar/Wind Harmer
12.071
959091AF2-200 GEN
Solar/Wind Harmer
22.556
970571AG2-364 GEN
Solar/Wind Harmer
22.155
274857EASY ROAD;U1
Solar/Wind Harmer
5.199
274760LEE CO EC;1U
Adder
10.097
274767LEE CO EC;8U
Adder
9.978
276603SUBLETTE C
Solar/Wind Harmer
1.132
972038AH1-567 GEN2
Adder
0.38
274851PROVIDENC;RU
Solar/Wind Harmer
2.907
274849CRESCENT ;1U
Solar/Wind Harmer
1.887
276782AC1-033 GEN
Solar/Wind Harmer
4.043
274878BISHOP HL;2U
Solar/Wind Harmer
3.42
965931AG1-462 GEN
Solar/Wind Harmer
25.247
971087AG2-675 GEN
Solar/Wind Harmer
3.684
274803UNIV PARK;6U
Adder
5.736
276164X3-005 C
Solar/Wind Harmer
0.638
965091AG1-374 GEN
Solar/Wind Harmer
25.226
959611AF2-252 GEN
Solar/Wind Harmer
1.956
274814UNIV PK N;0U
Adder
3.736
274807UNIV PK N;3U
Adder
3.727
274811UNIV PK N;7U
Adder
3.703
274724RIVER EC ;11
Adder
12.886
276785W4-005 GEN1
Solar/Wind Harmer
2.074
971993AH1-541 GEN
Solar/Wind Harmer
6.336
957381AF2-032 GEN
Solar/Wind Harmer
1.188
942481AE2-261 GEN
Solar/Wind Harmer
17.544
274848CAMPGROVE;RU
Solar/Wind Harmer
6.463
274802UNIV PARK;5U
Adder
5.736
276655WTG1_EQ
Solar/Wind Harmer
7.712
276656WTG2_EQ
Solar/Wind Harmer
1.021
939741AE1-205 GEN
Solar/Wind Harmer
17.671
274812UNIV PK N;8U
Adder
3.703
276686W4-005 GEN3
Solar/Wind Harmer
2.074
276621W2-048 GEN
Solar/Wind Harmer
4.078
274723RIVER EC ;12
Adder
11.513
965911AG1-460 GEN
Solar/Wind Harmer
0.819
276764AC1-053 GEN2
Solar/Wind Harmer
2.667
960681AF2-359 GEN
Solar/Wind Helper
1.356
991777J1629 G
External Queue
13.433813095092773
990512J1326
External Queue
5.908938884735107
990117J1214
External Queue
20.32674789428711
990727J1377 G
External Queue
6.859858989715576
991092J1477
External Queue
3.17045521736145
991303J1755 G
External Queue
5.078529357910156
990407J1304
External Queue
4.570870876312256
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.214
NYPJM->LTFIMP_NY
CLTF
1.018
WECLTFEXP_WEC->PJM
CLTF
4.307
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.53
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.811
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.359
MECLTFEXP_MEC->PJM
CLTF
13.306
SIGELTFEXP_SIGE->PJM
CLTF
0.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.43
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.511
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.46
LAGNLTFEXP_LAGN->PJM
CLTF
4.269
TVALTFEXP_TVA->PJM
CLTF
1.055

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.12 %
Rating:2112.0 MVA
Rating Type:B
MVA to Mitigate:2410.15
MW Contribution:
16.39
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.31 %
Rating:2112.0 MVA
Rating Type:B
MVA to Mitigate:2393.03
MW Contribution:
16.14
Bus #Bus NameTypeMW Contribution
274752CRETE EC ;2U
50/50
21.713
274753CRETE EC ;3U
50/50
21.713
959351AF2-226 GEN
50/50
3.2
274654BRAIDWOOD;1U
50/50
5.059
274707KENDALL ;2S
50/50
1.001
972231SS25-0005
Solar/Wind Harmer
39.731
972181SS23-001
Solar/Wind Harmer
24.832
274862TOP CROP ;2U
Solar/Wind Harmer
6.96
274676JOLIET 29;8U
Adder
38.026
972259AH1-714 GEN
Adder
24.514
274730ELWOOD EC;6P
Adder
21.096
274734ELWOOD EC;8P
Adder
21.096
274736ELWOOD EC;9P
Adder
21.096
274711KENDALL ;4S
50/50
0.935
274709KENDALL ;3S
50/50
0.935
276897AD1-100 C
Solar/Wind Harmer
56.386
274683WAUKEGAN ;8U
Adder
25.335
274683WAUKEGAN ;8U
Adder
21.356
274695ROCKY RD ;2P
Adder
13.298
274693ROCKY RD ;1P
Adder
13.167
274697ROCKY RD ;3P
Adder
3.612
274696ROCKY RD ;4P
Adder
13.611
276893AG1-478 C
Solar/Wind Harmer
0.519
274674JOLIET 9 ;6U
Adder
18.04
962691AG1-118 GEN
Solar/Wind Harmer
35.013
274770LINCOLN ;1U
Adder
7.21
274771LINCOLN ;2U
Adder
7.21
960751AF2-366 GEN
Solar/Wind Harmer
3.334
276901AD2-066 C O1
Solar/Wind Harmer
3.988
274888KELLY CRK;1U
Solar/Wind Harmer
6.659
276776AD2-060 GEN
Solar/Wind Harmer
0.472
958011AF2-095 GEN
Solar/Wind Harmer
16.249
970941AG2-585 GEN
Solar/Wind Harmer
6.206
971341AH1-150 GEN
Solar/Wind Harmer
22.555
971343AH1-151 GEN
Solar/Wind Harmer
22.555
972235AH1-702 GEN1
Adder
2.823
972236AH1-702 GEN2
Adder
2.455
958481AF2-142 GEN
Solar/Wind Harmer
16.744
958491AF2-143 GEN
Solar/Wind Harmer
16.706
276872AE1-163_GEN1
Solar/Wind Harmer
7.455
276876AE1-163_GEN2
Solar/Wind Harmer
7.455
938861AE1-114 GEN
Solar/Wind Harmer
8.959
274764LEE CO EC;5U
Adder
10.121
274765LEE CO EC;6U
Adder
10.121
274762LEE CO EC;3U
Adder
10.097
274763LEE CO EC;4U
Adder
10.002
276158O29GEN2
Solar/Wind Harmer
5.254
276157O29GEN1
Solar/Wind Harmer
3.994
276645AC1-214 GEN1
Solar/Wind Harmer
1.367
942111AE2-223 GEN
Solar/Wind Harmer
7.243
960611AF2-352 GEN
Solar/Wind Harmer
1.956
274805UNIV PK N;1U
Adder
3.711
274808UNIV PK N;4U
Adder
3.687
274880W4-005 GEN4
Solar/Wind Harmer
2.074
276174W4-005 GEN2
Solar/Wind Harmer
2.074
276615X2-022 GEN
Solar/Wind Harmer
1.281
276838X2-022 GEN2
Solar/Wind Harmer
0.152
276916AD2-100_GEN
Solar/Wind Harmer
11.868
276911AD2-131_GEN
Solar/Wind Harmer
2.399
274751CRETE EC ;1U
50/50
21.713
274754CRETE EC ;4U
50/50
21.713
960281AF2-319 GEN
50/50
3.2
274705KENDALL ;1S
50/50
1.001
274710KENDALL ;4C
50/50
1.4
274861TOP CROP ;1U
Solar/Wind Harmer
8.335
274676JOLIET 29;8U
Adder
39.434
274732ELWOOD EC;7P
Adder
21.096
274871GR RIDGE ;2U
Solar/Wind Harmer
9.534
274847GR RIDGE ;BU
Solar/Wind Harmer
6.269
941551AE2-152 GEN
Solar/Wind Harmer
5.505
274745AC1-111 GEN9
Adder
6.756
274682WAUKEGAN ;7U
Adder
21.661
274828WAUKEGAN ;BP
Adder
13.28
276882AE2-255 GEN
Solar/Wind Harmer
3.962
274674JOLIET 9 ;6U
Adder
18.04
972207SS24-0001
Solar/Wind Harmer
25.635
274773LINCOLN ;4U
Adder
7.21
274774LINCOLN ;5U
Adder
7.21
962781AG1-127 GEN
Solar/Wind Harmer
11.051
274872LEEDK;1U
Solar/Wind Harmer
9.494
971997AH1-543 GEN
Solar/Wind Harmer
17.791
957471AF2-041 GEN
Solar/Wind Harmer
33.833
959081AF2-199 GEN
Solar/Wind Harmer
11.278
971067AG2-660 GEN
Solar/Wind Harmer
2.623
274822ROCKFORD ;11
Adder
22.098
276694AA1-018 GEN2
Solar/Wind Harmer
7.044
276691AA1-018 GEN1
Solar/Wind Harmer
0.842
276805AD2-038 GEN
Solar/Wind Harmer
5.711
970819AG2-516 GEN
Solar/Wind Harmer
13.363
970569AG2-363 GEN
Solar/Wind Harmer
33.233
274858EASY ROAD;U2
Solar/Wind Harmer
5.199
274761LEE CO EC;2U
Adder
10.097
274766LEE CO EC;7U
Adder
9.978
939401AE1-172 GEN
Solar/Wind Harmer
15.078
276708O09 GEN2
Solar/Wind Harmer
3.751
276646AC1-214 GEN2
Solar/Wind Harmer
1.367
274848CAMPGROVE;RU
Solar/Wind Harmer
6.463
274802UNIV PARK;5U
Adder
5.736
276655WTG1_EQ
Solar/Wind Harmer
7.712
276656WTG2_EQ
Solar/Wind Harmer
1.021
939741AE1-205 GEN
Solar/Wind Harmer
17.671
274812UNIV PK N;8U
Adder
3.703
276686W4-005 GEN3
Solar/Wind Harmer
2.074
276621W2-048 GEN
Solar/Wind Harmer
4.078
274723RIVER EC ;12
Adder
11.514
965911AG1-460 GEN
Solar/Wind Harmer
0.819
972227AH1-698 GEN1
50/50
3.693
274655BRAIDWOOD;2U
50/50
4.895
972228AH1-698 GEN2
50/50
5.229
274687WILL CNTY;4U
50/50
38.862
274687WILL CNTY;4U
50/50
38.862
274704KENDALL ;1C
50/50
1.498
274706KENDALL ;2C
50/50
1.498
274708KENDALL ;3C
50/50
1.416
274675JOLIET 29;7U
Adder
39.41
274675JOLIET 29;7U
Adder
38.002
274728ELWOOD EC;5P
Adder
21.096
274731ELWOOD EC;2P
Adder
21.05
274733ELWOOD EC;3P
Adder
21.05
274735ELWOOD EC;4P
Adder
21.05
970833AG2-524 GEN
Solar/Wind Harmer
10.754
970833AG2-524 GEN
Solar/Wind Harmer
5.002
274744AC1-111 GEN8
Adder
6.756
274746AC1-111 G10
Adder
6.756
276893AG1-478 C
Solar/Wind Harmer
0.651
274827FISK ;RP
Adder
9.026
274775LINCOLN ;6U
Adder
7.21
274776LINCOLN ;7U
Adder
7.21
274777LINCOLN ;8U
Adder
7.21
971411AH1-196 GEN
Solar/Wind Harmer
17.235
971675AH1-338 GEN
Solar/Wind Harmer
20.463
276861AD2-134 GEN
Solar/Wind Harmer
2.029
276863AD2-134 GEN
Solar/Wind Harmer
2.029
960591AF2-350 GEN
Solar/Wind Harmer
11.284
971171AH1-044 GEN
Solar/Wind Harmer
22.555
274823ROCKFORD ;21
Adder
21.938
970073AG2-061 GEN
Solar/Wind Harmer
2.59
276889AE2-281 GEN
Solar/Wind Harmer
2.13
274856ECOGROVE ;U1
Solar/Wind Harmer
3.739
276611AD2-172 GEN
Solar/Wind Harmer
2.836
276612AE2-035 GEN
Solar/Wind Harmer
2.836
971681AH1-341 GEN
Solar/Wind Harmer
16.388
926823AC1-168 GEN
Solar/Wind Harmer
4.622
972267AH1-718 GEN
Adder
4.424
276741O09 GEN1
Solar/Wind Harmer
3.751
274800UNIV PARK;3U
Adder
6.074
274801UNIV PARK;4U
Adder
6.074
274863CRW1-WTG
Solar/Wind Harmer
5.796
274864CRW2-WTG
Solar/Wind Harmer
5.796
274877BISHOP HL;1U
Solar/Wind Harmer
3.42
946321AF1-296 GEN
Solar/Wind Harmer
10.446
970169AG2-114 GEN
Solar/Wind Harmer
10.007
972037AH1-567 GEN1
Adder
0.18
276726Z2-087_GEN
Solar/Wind Harmer
6.986
959341AF2-225 GEN
Solar/Wind Harmer
13.253
274853TWINGROVE;U1
Solar/Wind Harmer
6.058
274854TWINGROVE;U2
Solar/Wind Harmer
5.931
276668AB2-070 GEN1
Solar/Wind Harmer
1.516
276848AB2-070 GEN3
Solar/Wind Harmer
1.516
276849AB2-070 GEN2
Solar/Wind Harmer
1.516
276763AC1-053 GEN1
Solar/Wind Harmer
2.667
276764AC1-053 GEN2
Solar/Wind Harmer
2.667
960681AF2-359 GEN
Solar/Wind Helper
1.356
274729ELWOOD EC;1P
Adder
21.05
970707AG2-453 GEN
Solar/Wind Harmer
34.962
939351AE1-166 GEN
Solar/Wind Harmer
7.198
274682WAUKEGAN ;7U
Adder
21.661
943121AE2-341 GEN
Solar/Wind Harmer
18.002
943591AF1-030 GEN
Solar/Wind Harmer
12.001
276868AE1-113 GEN
Solar/Wind Harmer
11.884
274879MINONK ;1U
Solar/Wind Harmer
7.923
274826FISK ;BP
Adder
12.736
274772LINCOLN ;3U
Adder
7.21
276799AD1-013 GEN
Solar/Wind Harmer
2.514
946671AF1-331 GEN
Solar/Wind Harmer
0.476
274855GSG-6 ;RU
Solar/Wind Harmer
4.195
274850MENDOTA H;RU
Solar/Wind Harmer
2.917
276602WESTBROOK C
Solar/Wind Harmer
2.415
274887GEN-1.85
Solar/Wind Harmer
6.012
276772AC2-154 GEN
Solar/Wind Harmer
3.149
276843GEN-1.7
Solar/Wind Harmer
0.647
276806AD2-047 C O1
Solar/Wind Harmer
12.071
959091AF2-200 GEN
Solar/Wind Harmer
22.555
970571AG2-364 GEN
Solar/Wind Harmer
22.155
274857EASY ROAD;U1
Solar/Wind Harmer
5.199
274760LEE CO EC;1U
Adder
10.097
274767LEE CO EC;8U
Adder
9.978
276603SUBLETTE C
Solar/Wind Harmer
1.132
972038AH1-567 GEN2
Adder
0.38
274851PROVIDENC;RU
Solar/Wind Harmer
2.907
274849CRESCENT ;1U
Solar/Wind Harmer
1.887
276782AC1-033 GEN
Solar/Wind Harmer
4.043
274878BISHOP HL;2U
Solar/Wind Harmer
3.42
965931AG1-462 GEN
Solar/Wind Harmer
25.247
971087AG2-675 GEN
Solar/Wind Harmer
3.684
274803UNIV PARK;6U
Adder
5.736
276164X3-005 C
Solar/Wind Harmer
0.638
965091AG1-374 GEN
Solar/Wind Harmer
25.226
959611AF2-252 GEN
Solar/Wind Harmer
1.956
274814UNIV PK N;0U
Adder
3.736
274807UNIV PK N;3U
Adder
3.727
274811UNIV PK N;7U
Adder
3.703
274724RIVER EC ;11
Adder
12.887
276785W4-005 GEN1
Solar/Wind Harmer
2.074
971993AH1-541 GEN
Solar/Wind Harmer
6.336
957381AF2-032 GEN
Solar/Wind Harmer
1.188
942481AE2-261 GEN
Solar/Wind Harmer
17.544
991777J1629 G
External Queue
13.433511734008789
990512J1326
External Queue
5.908795356750488
990117J1214
External Queue
20.326255798339844
990727J1377 G
External Queue
6.859685897827148
991092J1477
External Queue
3.170389413833618
991303J1755 G
External Queue
5.078456878662109
990407J1304
External Queue
4.57075834274292
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.214
NYPJM->LTFIMP_NY
CLTF
1.018
WECLTFEXP_WEC->PJM
CLTF
4.307
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.528
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.811
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.359
MECLTFEXP_MEC->PJM
CLTF
13.306
SIGELTFEXP_SIGE->PJM
CLTF
0.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.43
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.511
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.46
LAGNLTFEXP_LAGN->PJM
CLTF
4.269
TVALTFEXP_TVA->PJM
CLTF
1.055

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.41 %
Rating:2112.0 MVA
Rating Type:B
MVA to Mitigate:2395.13
MW Contribution:
16.28
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.77 %
Rating:2112.0 MVA
Rating Type:B
MVA to Mitigate:2381.72
MW Contribution:
16.06
Bus #Bus NameTypeMW Contribution
274711KENDALL ;4S
50/50
0.929
274709KENDALL ;3S
50/50
0.929
276897AD1-100 C
Solar/Wind Harmer
56.056
274683WAUKEGAN ;8U
Adder
25.175
274683WAUKEGAN ;8U
Adder
21.221
274695ROCKY RD ;2P
Adder
13.213
274693ROCKY RD ;1P
Adder
13.083
274697ROCKY RD ;3P
Adder
3.589
274696ROCKY RD ;4P
Adder
13.524
276893AG1-478 C
Solar/Wind Harmer
0.515
274674JOLIET 9 ;6U
Adder
17.92
962691AG1-118 GEN
Solar/Wind Harmer
34.786
274770LINCOLN ;1U
Adder
7.171
274771LINCOLN ;2U
Adder
7.171
960751AF2-366 GEN
Solar/Wind Harmer
3.312
276901AD2-066 C O1
Solar/Wind Harmer
3.963
274888KELLY CRK;1U
Solar/Wind Harmer
6.613
276776AD2-060 GEN
Solar/Wind Harmer
0.469
958011AF2-095 GEN
Solar/Wind Harmer
16.138
970941AG2-585 GEN
Solar/Wind Harmer
6.164
971341AH1-150 GEN
Solar/Wind Harmer
22.41
971343AH1-151 GEN
Solar/Wind Harmer
22.41
972235AH1-702 GEN1
Adder
2.805
972236AH1-702 GEN2
Adder
2.439
958481AF2-142 GEN
Solar/Wind Harmer
16.634
958491AF2-143 GEN
Solar/Wind Harmer
16.598
276872AE1-163_GEN1
Solar/Wind Harmer
7.408
276876AE1-163_GEN2
Solar/Wind Harmer
7.408
938861AE1-114 GEN
Solar/Wind Harmer
8.902
274764LEE CO EC;5U
Adder
10.056
274765LEE CO EC;6U
Adder
10.056
274762LEE CO EC;3U
Adder
10.032
274763LEE CO EC;4U
Adder
9.938
276158O29GEN2
Solar/Wind Harmer
5.22
276157O29GEN1
Solar/Wind Harmer
3.969
276645AC1-214 GEN1
Solar/Wind Harmer
1.358
942111AE2-223 GEN
Solar/Wind Harmer
7.197
960611AF2-352 GEN
Solar/Wind Harmer
1.943
274805UNIV PK N;1U
Adder
3.67
274808UNIV PK N;4U
Adder
3.646
274880W4-005 GEN4
Solar/Wind Harmer
2.06
276174W4-005 GEN2
Solar/Wind Harmer
2.06
276615X2-022 GEN
Solar/Wind Harmer
1.272
276838X2-022 GEN2
Solar/Wind Harmer
0.151
276916AD2-100_GEN
Solar/Wind Harmer
11.787
276911AD2-131_GEN
Solar/Wind Harmer
2.382
274752CRETE EC ;2U
50/50
21.669
274753CRETE EC ;3U
50/50
21.669
959351AF2-226 GEN
50/50
3.183
274654BRAIDWOOD;1U
50/50
5.03
274707KENDALL ;2S
50/50
0.995
972231SS25-0005
Solar/Wind Harmer
39.651
972181SS23-001
Solar/Wind Harmer
24.782
274862TOP CROP ;2U
Solar/Wind Harmer
6.922
274676JOLIET 29;8U
Adder
37.795
972259AH1-714 GEN
Adder
24.363
274730ELWOOD EC;6P
Adder
20.969
274734ELWOOD EC;8P
Adder
20.969
274736ELWOOD EC;9P
Adder
20.969
274729ELWOOD EC;1P
Adder
20.923
970707AG2-453 GEN
Solar/Wind Harmer
34.73
939351AE1-166 GEN
Solar/Wind Harmer
7.156
274682WAUKEGAN ;7U
Adder
21.524
943121AE2-341 GEN
Solar/Wind Harmer
17.883
943591AF1-030 GEN
Solar/Wind Harmer
11.922
276868AE1-113 GEN
Solar/Wind Harmer
11.812
274879MINONK ;1U
Solar/Wind Harmer
7.875
274772LINCOLN ;3U
Adder
7.171
274826FISK ;BP
Adder
12.65
276799AD1-013 GEN
Solar/Wind Harmer
2.497
946671AF1-331 GEN
Solar/Wind Harmer
0.473
274855GSG-6 ;RU
Solar/Wind Harmer
4.168
274850MENDOTA H;RU
Solar/Wind Harmer
2.898
276602WESTBROOK C
Solar/Wind Harmer
2.399
274887GEN-1.85
Solar/Wind Harmer
5.971
276772AC2-154 GEN
Solar/Wind Harmer
3.128
276843GEN-1.7
Solar/Wind Harmer
0.642
276806AD2-047 C O1
Solar/Wind Harmer
11.989
959091AF2-200 GEN
Solar/Wind Harmer
22.41
970571AG2-364 GEN
Solar/Wind Harmer
22.019
274857EASY ROAD;U1
Solar/Wind Harmer
5.166
274760LEE CO EC;1U
Adder
10.032
274767LEE CO EC;8U
Adder
9.914
276603SUBLETTE C
Solar/Wind Harmer
1.125
972038AH1-567 GEN2
Adder
0.377
274851PROVIDENC;RU
Solar/Wind Harmer
2.888
274849CRESCENT ;1U
Solar/Wind Harmer
1.875
276782AC1-033 GEN
Solar/Wind Harmer
4.017
274878BISHOP HL;2U
Solar/Wind Harmer
3.399
965931AG1-462 GEN
Solar/Wind Harmer
25.085
971087AG2-675 GEN
Solar/Wind Harmer
3.66
274803UNIV PARK;6U
Adder
5.69
276164X3-005 C
Solar/Wind Harmer
0.633
965091AG1-374 GEN
Solar/Wind Harmer
25.065
959611AF2-252 GEN
Solar/Wind Harmer
1.943
274814UNIV PK N;0U
Adder
3.694
274807UNIV PK N;3U
Adder
3.686
274811UNIV PK N;7U
Adder
3.662
274724RIVER EC ;11
Adder
12.739
276785W4-005 GEN1
Solar/Wind Harmer
2.06
971993AH1-541 GEN
Solar/Wind Harmer
6.294
957381AF2-032 GEN
Solar/Wind Harmer
1.18
942481AE2-261 GEN
Solar/Wind Harmer
17.426
274751CRETE EC ;1U
50/50
21.669
274754CRETE EC ;4U
50/50
21.669
960281AF2-319 GEN
50/50
3.183
274705KENDALL ;1S
50/50
0.995
274710KENDALL ;4C
50/50
1.39
274861TOP CROP ;1U
Solar/Wind Harmer
8.291
274676JOLIET 29;8U
Adder
39.195
274732ELWOOD EC;7P
Adder
20.969
274871GR RIDGE ;2U
Solar/Wind Harmer
9.474
274847GR RIDGE ;BU
Solar/Wind Harmer
6.23
941551AE2-152 GEN
Solar/Wind Harmer
5.473
274745AC1-111 GEN9
Adder
6.712
274682WAUKEGAN ;7U
Adder
21.524
274828WAUKEGAN ;BP
Adder
13.196
276882AE2-255 GEN
Solar/Wind Harmer
3.937
274674JOLIET 9 ;6U
Adder
17.92
972207SS24-0001
Solar/Wind Harmer
25.497
274773LINCOLN ;4U
Adder
7.171
274774LINCOLN ;5U
Adder
7.171
962781AG1-127 GEN
Solar/Wind Harmer
10.98
274872LEEDK;1U
Solar/Wind Harmer
9.433
971997AH1-543 GEN
Solar/Wind Harmer
17.677
957471AF2-041 GEN
Solar/Wind Harmer
33.615
959081AF2-199 GEN
Solar/Wind Harmer
11.205
971067AG2-660 GEN
Solar/Wind Harmer
2.606
274822ROCKFORD ;11
Adder
21.956
276694AA1-018 GEN2
Solar/Wind Harmer
6.997
276691AA1-018 GEN1
Solar/Wind Harmer
0.836
276805AD2-038 GEN
Solar/Wind Harmer
5.674
970819AG2-516 GEN
Solar/Wind Harmer
13.278
970569AG2-363 GEN
Solar/Wind Harmer
33.029
274858EASY ROAD;U2
Solar/Wind Harmer
5.166
274761LEE CO EC;2U
Adder
10.032
274766LEE CO EC;7U
Adder
9.914
939401AE1-172 GEN
Solar/Wind Harmer
14.988
276708O09 GEN2
Solar/Wind Harmer
3.727
276646AC1-214 GEN2
Solar/Wind Harmer
1.358
274848CAMPGROVE;RU
Solar/Wind Harmer
6.422
274802UNIV PARK;5U
Adder
5.69
276655WTG1_EQ
Solar/Wind Harmer
7.663
276656WTG2_EQ
Solar/Wind Harmer
1.015
939741AE1-205 GEN
Solar/Wind Harmer
17.559
274812UNIV PK N;8U
Adder
3.662
276686W4-005 GEN3
Solar/Wind Harmer
2.06
276621W2-048 GEN
Solar/Wind Harmer
4.051
274723RIVER EC ;12
Adder
11.365
965911AG1-460 GEN
Solar/Wind Harmer
0.813
972227AH1-698 GEN1
50/50
3.672
274655BRAIDWOOD;2U
50/50
4.867
972228AH1-698 GEN2
50/50
5.199
274687WILL CNTY;4U
50/50
38.631
274687WILL CNTY;4U
50/50
38.631
274704KENDALL ;1C
50/50
1.489
274706KENDALL ;2C
50/50
1.489
274708KENDALL ;3C
50/50
1.406
274675JOLIET 29;7U
Adder
39.17
274675JOLIET 29;7U
Adder
37.771
274728ELWOOD EC;5P
Adder
20.969
274731ELWOOD EC;2P
Adder
20.923
274733ELWOOD EC;3P
Adder
20.923
274735ELWOOD EC;4P
Adder
20.923
970833AG2-524 GEN
Solar/Wind Harmer
10.686
970833AG2-524 GEN
Solar/Wind Harmer
4.97
274744AC1-111 GEN8
Adder
6.712
274746AC1-111 G10
Adder
6.712
276893AG1-478 C
Solar/Wind Harmer
0.646
274775LINCOLN ;6U
Adder
7.171
274776LINCOLN ;7U
Adder
7.171
274777LINCOLN ;8U
Adder
7.171
274827FISK ;RP
Adder
8.965
971411AH1-196 GEN
Solar/Wind Harmer
17.125
971675AH1-338 GEN
Solar/Wind Harmer
20.331
276861AD2-134 GEN
Solar/Wind Harmer
2.015
276863AD2-134 GEN
Solar/Wind Harmer
2.015
960591AF2-350 GEN
Solar/Wind Harmer
11.207
971171AH1-044 GEN
Solar/Wind Harmer
22.41
274823ROCKFORD ;21
Adder
21.797
970073AG2-061 GEN
Solar/Wind Harmer
2.573
276889AE2-281 GEN
Solar/Wind Harmer
2.117
274856ECOGROVE ;U1
Solar/Wind Harmer
3.715
276611AD2-172 GEN
Solar/Wind Harmer
2.818
276612AE2-035 GEN
Solar/Wind Harmer
2.818
971681AH1-341 GEN
Solar/Wind Harmer
16.283
926823AC1-168 GEN
Solar/Wind Harmer
4.593
972267AH1-718 GEN
Adder
4.396
276741O09 GEN1
Solar/Wind Harmer
3.727
274800UNIV PARK;3U
Adder
6.028
274801UNIV PARK;4U
Adder
6.028
274863CRW1-WTG
Solar/Wind Harmer
5.761
274864CRW2-WTG
Solar/Wind Harmer
5.761
274877BISHOP HL;1U
Solar/Wind Harmer
3.399
946321AF1-296 GEN
Solar/Wind Harmer
10.379
970169AG2-114 GEN
Solar/Wind Harmer
9.944
972037AH1-567 GEN1
Adder
0.179
276726Z2-087_GEN
Solar/Wind Harmer
6.942
959341AF2-225 GEN
Solar/Wind Harmer
13.169
274853TWINGROVE;U1
Solar/Wind Harmer
6.019
274854TWINGROVE;U2
Solar/Wind Harmer
5.893
276668AB2-070 GEN1
Solar/Wind Harmer
1.506
276848AB2-070 GEN3
Solar/Wind Harmer
1.506
276849AB2-070 GEN2
Solar/Wind Harmer
1.506
276763AC1-053 GEN1
Solar/Wind Harmer
2.649
276764AC1-053 GEN2
Solar/Wind Harmer
2.649
960681AF2-359 GEN
Solar/Wind Helper
1.374
991777J1629 G
External Queue
13.376709938049316
990512J1326
External Queue
5.883509159088135
990117J1214
External Queue
20.23927116394043
990727J1377 G
External Queue
6.829868793487549
991092J1477
External Queue
3.1583495140075684
991303J1755 G
External Queue
5.057826042175293
990407J1304
External Queue
4.550849437713623
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.211
NYPJM->LTFIMP_NY
CLTF
1.01
WECLTFEXP_WEC->PJM
CLTF
4.28
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.822
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.797
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.151
MECLTFEXP_MEC->PJM
CLTF
13.221
SIGELTFEXP_SIGE->PJM
CLTF
0.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.425
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.507
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.447
LAGNLTFEXP_LAGN->PJM
CLTF
4.243
TVALTFEXP_TVA->PJM
CLTF
1.05

Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.45 %
Rating:2112.0 MVA
Rating Type:B
MVA to Mitigate:2374.91
MW Contribution:
16.16
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE/NIPS
Facility Description:
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.24 %
Rating:2112.0 MVA
Rating Type:B
MVA to Mitigate:2391.55
MW Contribution:
16.06
Bus #Bus NameTypeMW Contribution
274711KENDALL ;4S
50/50
0.921
274709KENDALL ;3S
50/50
0.921
276897AD1-100 C
Solar/Wind Harmer
55.556
274683WAUKEGAN ;8U
Adder
24.962
274683WAUKEGAN ;8U
Adder
21.041
274695ROCKY RD ;2P
Adder
13.1
274693ROCKY RD ;1P
Adder
12.971
274697ROCKY RD ;3P
Adder
3.559
274696ROCKY RD ;4P
Adder
13.409
276893AG1-478 C
Solar/Wind Harmer
0.51
274674JOLIET 9 ;6U
Adder
17.75
962691AG1-118 GEN
Solar/Wind Harmer
34.493
274770LINCOLN ;1U
Adder
7.101
274771LINCOLN ;2U
Adder
7.101
960751AF2-366 GEN
Solar/Wind Harmer
3.285
276901AD2-066 C O1
Solar/Wind Harmer
3.93
971341AH1-150 GEN
Solar/Wind Harmer
22.228
971343AH1-151 GEN
Solar/Wind Harmer
22.228
274888KELLY CRK;1U
Solar/Wind Harmer
6.544
276776AD2-060 GEN
Solar/Wind Harmer
0.464
958011AF2-095 GEN
Solar/Wind Harmer
15.969
970941AG2-585 GEN
Solar/Wind Harmer
6.099
972235AH1-702 GEN1
Adder
2.783
972236AH1-702 GEN2
Adder
2.42
958481AF2-142 GEN
Solar/Wind Harmer
16.478
958491AF2-143 GEN
Solar/Wind Harmer
16.451
276872AE1-163_GEN1
Solar/Wind Harmer
7.348
276876AE1-163_GEN2
Solar/Wind Harmer
7.348
938861AE1-114 GEN
Solar/Wind Harmer
8.831
274764LEE CO EC;5U
Adder
9.977
274765LEE CO EC;6U
Adder
9.977
274762LEE CO EC;3U
Adder
9.954
274763LEE CO EC;4U
Adder
9.86
276158O29GEN2
Solar/Wind Harmer
5.181
276157O29GEN1
Solar/Wind Harmer
3.939
276645AC1-214 GEN1
Solar/Wind Harmer
1.349
942111AE2-223 GEN
Solar/Wind Harmer
7.154
960611AF2-352 GEN
Solar/Wind Harmer
1.932
274805UNIV PK N;1U
Adder
3.605
274808UNIV PK N;4U
Adder
3.581
274880W4-005 GEN4
Solar/Wind Harmer
2.054
276174W4-005 GEN2
Solar/Wind Harmer
2.054
276615X2-022 GEN
Solar/Wind Harmer
1.269
276838X2-022 GEN2
Solar/Wind Harmer
0.151
276916AD2-100_GEN
Solar/Wind Harmer
11.786
276911AD2-131_GEN
Solar/Wind Harmer
2.382
274751CRETE EC ;1U
50/50
21.597
274754CRETE EC ;4U
50/50
21.597
960281AF2-319 GEN
50/50
3.159
274705KENDALL ;1S
50/50
0.987
274710KENDALL ;4C
50/50
1.378
274861TOP CROP ;1U
Solar/Wind Harmer
8.228
274676JOLIET 29;8U
Adder
38.85
274732ELWOOD EC;7P
Adder
20.787
274871GR RIDGE ;2U
Solar/Wind Harmer
9.393
274847GR RIDGE ;BU
Solar/Wind Harmer
6.176
941551AE2-152 GEN
Solar/Wind Harmer
5.424
274745AC1-111 GEN9
Adder
6.654
274682WAUKEGAN ;7U
Adder
21.342
274828WAUKEGAN ;BP
Adder
13.084
276882AE2-255 GEN
Solar/Wind Harmer
3.905
274674JOLIET 9 ;6U
Adder
17.75
972207SS24-0001
Solar/Wind Harmer
25.249
274773LINCOLN ;4U
Adder
7.101
274774LINCOLN ;5U
Adder
7.101
962781AG1-127 GEN
Solar/Wind Harmer
10.888
274872LEEDK;1U
Solar/Wind Harmer
9.354
971997AH1-543 GEN
Solar/Wind Harmer
17.535
957471AF2-041 GEN
Solar/Wind Harmer
33.342
959081AF2-199 GEN
Solar/Wind Harmer
11.114
971067AG2-660 GEN
Solar/Wind Harmer
2.585
274822ROCKFORD ;11
Adder
21.779
276694AA1-018 GEN2
Solar/Wind Harmer
6.932
276691AA1-018 GEN1
Solar/Wind Harmer
0.829
970819AG2-516 GEN
Solar/Wind Harmer
13.171
276805AD2-038 GEN
Solar/Wind Harmer
5.624
970569AG2-363 GEN
Solar/Wind Harmer
32.776
274858EASY ROAD;U2
Solar/Wind Harmer
5.125
274761LEE CO EC;2U
Adder
9.954
274766LEE CO EC;7U
Adder
9.836
939401AE1-172 GEN
Solar/Wind Harmer
14.867
276708O09 GEN2
Solar/Wind Harmer
3.699
276646AC1-214 GEN2
Solar/Wind Harmer
1.349
274848CAMPGROVE;RU
Solar/Wind Harmer
6.377
274802UNIV PARK;5U
Adder
5.619
276655WTG1_EQ
Solar/Wind Harmer
7.617
276656WTG2_EQ
Solar/Wind Harmer
1.008
939741AE1-205 GEN
Solar/Wind Harmer
17.453
274812UNIV PK N;8U
Adder
3.597
276686W4-005 GEN3
Solar/Wind Harmer
2.054
276621W2-048 GEN
Solar/Wind Harmer
4.042
274723RIVER EC ;12
Adder
11.122
965911AG1-460 GEN
Solar/Wind Harmer
0.813
972227AH1-698 GEN1
50/50
3.64
274655BRAIDWOOD;2U
50/50
4.825
972228AH1-698 GEN2
50/50
5.154
274687WILL CNTY;4U
50/50
38.293
274687WILL CNTY;4U
50/50
38.293
274704KENDALL ;1C
50/50
1.476
274706KENDALL ;2C
50/50
1.476
274708KENDALL ;3C
50/50
1.394
274675JOLIET 29;7U
Adder
38.825
274675JOLIET 29;7U
Adder
37.439
274728ELWOOD EC;5P
Adder
20.787
274731ELWOOD EC;2P
Adder
20.741
274733ELWOOD EC;3P
Adder
20.741
274735ELWOOD EC;4P
Adder
20.741
970833AG2-524 GEN
Solar/Wind Harmer
10.594
970833AG2-524 GEN
Solar/Wind Harmer
4.927
274744AC1-111 GEN8
Adder
6.654
274746AC1-111 G10
Adder
6.654
276893AG1-478 C
Solar/Wind Harmer
0.64
274775LINCOLN ;6U
Adder
7.101
274776LINCOLN ;7U
Adder
7.101
274777LINCOLN ;8U
Adder
7.101
274827FISK ;RP
Adder
8.871
971411AH1-196 GEN
Solar/Wind Harmer
16.984
971675AH1-338 GEN
Solar/Wind Harmer
20.164
276861AD2-134 GEN
Solar/Wind Harmer
1.999
276863AD2-134 GEN
Solar/Wind Harmer
1.999
971171AH1-044 GEN
Solar/Wind Harmer
22.228
274823ROCKFORD ;21
Adder
21.621
960591AF2-350 GEN
Solar/Wind Harmer
11.09
970073AG2-061 GEN
Solar/Wind Harmer
2.551
276889AE2-281 GEN
Solar/Wind Harmer
2.099
274856ECOGROVE ;U1
Solar/Wind Harmer
3.685
276611AD2-172 GEN
Solar/Wind Harmer
2.795
276612AE2-035 GEN
Solar/Wind Harmer
2.795
971681AH1-341 GEN
Solar/Wind Harmer
16.155
926823AC1-168 GEN
Solar/Wind Harmer
4.558
972267AH1-718 GEN
Adder
4.362
276741O09 GEN1
Solar/Wind Harmer
3.699
274863CRW1-WTG
Solar/Wind Harmer
5.717
274864CRW2-WTG
Solar/Wind Harmer
5.717
274800UNIV PARK;3U
Adder
5.958
274801UNIV PARK;4U
Adder
5.958
274877BISHOP HL;1U
Solar/Wind Harmer
3.374
946321AF1-296 GEN
Solar/Wind Harmer
10.304
970169AG2-114 GEN
Solar/Wind Harmer
9.872
972037AH1-567 GEN1
Adder
0.176
276726Z2-087_GEN
Solar/Wind Harmer
6.9
959341AF2-225 GEN
Solar/Wind Harmer
13.09
274853TWINGROVE;U1
Solar/Wind Harmer
5.987
274854TWINGROVE;U2
Solar/Wind Harmer
5.861
276668AB2-070 GEN1
Solar/Wind Harmer
1.501
276848AB2-070 GEN3
Solar/Wind Harmer
1.501
276849AB2-070 GEN2
Solar/Wind Harmer
1.501
276763AC1-053 GEN1
Solar/Wind Harmer
2.642
276764AC1-053 GEN2
Solar/Wind Harmer
2.642
960681AF2-359 GEN
Solar/Wind Helper
1.411
270526AF1-158 GEN
Solar/Wind Helper
0.853
274752CRETE EC ;2U
50/50
21.597
274753CRETE EC ;3U
50/50
21.597
959351AF2-226 GEN
50/50
3.159
274654BRAIDWOOD;1U
50/50
4.987
274707KENDALL ;2S
50/50
0.987
972231SS25-0005
Solar/Wind Harmer
39.517
972181SS23-001
Solar/Wind Harmer
24.698
274862TOP CROP ;2U
Solar/Wind Harmer
6.87
274676JOLIET 29;8U
Adder
37.462
972259AH1-714 GEN
Adder
24.151
274730ELWOOD EC;6P
Adder
20.787
274734ELWOOD EC;8P
Adder
20.787
274736ELWOOD EC;9P
Adder
20.787
274729ELWOOD EC;1P
Adder
20.741
970707AG2-453 GEN
Solar/Wind Harmer
34.427
939351AE1-166 GEN
Solar/Wind Harmer
7.093
274682WAUKEGAN ;7U
Adder
21.342
943121AE2-341 GEN
Solar/Wind Harmer
17.728
943591AF1-030 GEN
Solar/Wind Harmer
11.819
276868AE1-113 GEN
Solar/Wind Harmer
11.716
274879MINONK ;1U
Solar/Wind Harmer
7.811
274772LINCOLN ;3U
Adder
7.101
274826FISK ;BP
Adder
12.517
276799AD1-013 GEN
Solar/Wind Harmer
2.477
946671AF1-331 GEN
Solar/Wind Harmer
0.469
274855GSG-6 ;RU
Solar/Wind Harmer
4.134
274850MENDOTA H;RU
Solar/Wind Harmer
2.874
276602WESTBROOK C
Solar/Wind Harmer
2.38
959091AF2-200 GEN
Solar/Wind Harmer
22.228
274887GEN-1.85
Solar/Wind Harmer
5.909
276772AC2-154 GEN
Solar/Wind Harmer
3.095
276843GEN-1.7
Solar/Wind Harmer
0.636
276806AD2-047 C O1
Solar/Wind Harmer
11.864
970571AG2-364 GEN
Solar/Wind Harmer
21.85
274857EASY ROAD;U1
Solar/Wind Harmer
5.125
274760LEE CO EC;1U
Adder
9.954
274767LEE CO EC;8U
Adder
9.836
276603SUBLETTE C
Solar/Wind Harmer
1.116
972038AH1-567 GEN2
Adder
0.373
274851PROVIDENC;RU
Solar/Wind Harmer
2.867
274849CRESCENT ;1U
Solar/Wind Harmer
1.861
276782AC1-033 GEN
Solar/Wind Harmer
3.988
274878BISHOP HL;2U
Solar/Wind Harmer
3.374
965931AG1-462 GEN
Solar/Wind Harmer
24.906
971087AG2-675 GEN
Solar/Wind Harmer
3.634
274803UNIV PARK;6U
Adder
5.619
276164X3-005 C
Solar/Wind Harmer
0.624
965091AG1-374 GEN
Solar/Wind Harmer
24.928
959611AF2-252 GEN
Solar/Wind Harmer
1.932
274814UNIV PK N;0U
Adder
3.628
274807UNIV PK N;3U
Adder
3.62
274811UNIV PK N;7U
Adder
3.597
274724RIVER EC ;11
Adder
12.499
276785W4-005 GEN1
Solar/Wind Harmer
2.054
971993AH1-541 GEN
Solar/Wind Harmer
6.276
957381AF2-032 GEN
Solar/Wind Harmer
1.179
942481AE2-261 GEN
Solar/Wind Harmer
17.414
24441505OLIV SLR
Solar/Wind Helper
0.05
991777J1629 G
External Queue
13.329572677612305
990512J1326
External Queue
5.862173557281494
990117J1214
External Queue
20.165876388549805
990727J1377 G
External Queue
6.803083896636963
991092J1477
External Queue
3.155707836151123
991303J1755 G
External Queue
5.045024394989014
990407J1304
External Queue
4.53252649307251
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.195
NYPJM->LTFIMP_NY
CLTF
0.998
WECLTFEXP_WEC->PJM
CLTF
4.245
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.3
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.982
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.619
MECLTFEXP_MEC->PJM
CLTF
13.15
SIGELTFEXP_SIGE->PJM
CLTF
0.013
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.399
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.442
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.253
LAGNLTFEXP_LAGN->PJM
CLTF
4.3
TVALTFEXP_TVA->PJM
CLTF
1.091

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.07 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1261.88
MW Contribution:
6.47
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1260.39
MW Contribution:
6.41
Bus #Bus NameTypeMW Contribution
274738AURORA EC;3P
50/50
1.406
274740AURORA EC;4P
50/50
1.406
274742AC1-111 GEN6
50/50
0.169
971341AH1-150 GEN
Solar/Wind Harmer
16.805
971343AH1-151 GEN
Solar/Wind Harmer
16.805
962691AG1-118 GEN
Solar/Wind Harmer
17.869
274764LEE CO EC;5U
Adder
5.562
274765LEE CO EC;6U
Adder
5.562
274762LEE CO EC;3U
Adder
5.549
274763LEE CO EC;4U
Adder
5.497
938861AE1-114 GEN
Solar/Wind Harmer
2.162
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.603
972235AH1-702 GEN1
Adder
1.246
972236AH1-702 GEN2
Adder
1.081
274695ROCKY RD ;2P
Adder
5.391
274693ROCKY RD ;1P
Adder
5.338
274697ROCKY RD ;3P
Adder
1.465
274696ROCKY RD ;4P
Adder
5.494
274741AC1-111 GEN5
50/50
0.169
959091AF2-200 GEN
Solar/Wind Harmer
16.805
943121AE2-341 GEN
Solar/Wind Harmer
9.007
943591AF1-030 GEN
Solar/Wind Harmer
5.99
946671AF1-331 GEN
Solar/Wind Harmer
0.559
274855GSG-6 ;RU
Solar/Wind Harmer
0.19
274850MENDOTA H;RU
Solar/Wind Harmer
0.061
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
5.549
274767LEE CO EC;8U
Adder
5.484
965931AG1-462 GEN
Solar/Wind Harmer
8.496
971087AG2-675 GEN
Solar/Wind Harmer
1.777
274743AC1-111 GEN7
50/50
0.169
274745AC1-111 GEN9
50/50
3.094
276890AG1-513 C
50/50
0.243
957471AF2-041 GEN
Solar/Wind Harmer
25.208
959081AF2-199 GEN
Solar/Wind Harmer
8.403
971067AG2-660 GEN
Solar/Wind Harmer
2.801
962781AG1-127 GEN
Solar/Wind Harmer
5.282
274872LEEDK;1U
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
5.549
274766LEE CO EC;7U
Adder
5.484
276708O09 GEN2
Solar/Wind Harmer
0.132
970819AG2-516 GEN
Solar/Wind Harmer
3.683
274822ROCKFORD ;11
Adder
8.628
972029AH1-563 GEN
50/50
9.1
274744AC1-111 GEN8
50/50
3.094
274746AC1-111 G10
50/50
3.094
971171AH1-044 GEN
Solar/Wind Harmer
16.805
971675AH1-338 GEN
Solar/Wind Harmer
2.039
276861AD2-134 GEN
Solar/Wind Harmer
0.093
276863AD2-134 GEN
Solar/Wind Harmer
0.093
972267AH1-718 GEN
Adder
2.763
971681AH1-341 GEN
Solar/Wind Harmer
6.474
276741O09 GEN1
Solar/Wind Harmer
0.132
946321AF1-296 GEN
Solar/Wind Harmer
1.885
274856ECOGROVE ;U1
Solar/Wind Harmer
0.078
274823ROCKFORD ;21
Adder
8.568
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.077
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.001
MECLTFEXP_MEC->PJM
CLTF
3.707
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.318
LAGNLTFEXP_LAGN->PJM
CLTF
0.938
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.213

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P4-6_111-345-R______SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_111-345-R______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.29 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1603.94
MW Contribution:
10.39
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_111-345-R______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.12 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1601.2
MW Contribution:
10.28
Bus #Bus NameTypeMW Contribution
274738AURORA EC;3P
50/50
1.627
274740AURORA EC;4P
50/50
1.627
274742AC1-111 GEN6
50/50
0.352
971341AH1-150 GEN
Solar/Wind Harmer
26.436
971343AH1-151 GEN
Solar/Wind Harmer
26.436
962691AG1-118 GEN
Solar/Wind Harmer
31.06
960751AF2-366 GEN
Solar/Wind Harmer
2.786
274764LEE CO EC;5U
Adder
6.651
274765LEE CO EC;6U
Adder
6.651
274762LEE CO EC;3U
Adder
6.636
274763LEE CO EC;4U
Adder
6.573
274695ROCKY RD ;2P
Adder
7.859
274693ROCKY RD ;1P
Adder
7.782
274697ROCKY RD ;3P
Adder
2.135
274696ROCKY RD ;4P
Adder
8.008
938861AE1-114 GEN
Solar/Wind Harmer
5.424
972235AH1-702 GEN1
Adder
1.599
972236AH1-702 GEN2
Adder
1.388
276158O29GEN2
Solar/Wind Harmer
3.092
276157O29GEN1
Solar/Wind Harmer
2.351
972029AH1-563 GEN
50/50
18.942
274744AC1-111 GEN8
50/50
6.44
274746AC1-111 G10
50/50
6.44
971171AH1-044 GEN
Solar/Wind Harmer
26.436
971675AH1-338 GEN
Solar/Wind Harmer
16.301
276861AD2-134 GEN
Solar/Wind Harmer
1.613
276863AD2-134 GEN
Solar/Wind Harmer
1.613
972267AH1-718 GEN
Adder
3.185
971681AH1-341 GEN
Solar/Wind Harmer
10.393
276741O09 GEN1
Solar/Wind Harmer
2.208
274856ECOGROVE ;U1
Solar/Wind Harmer
2.023
276611AD2-172 GEN
Solar/Wind Harmer
1.535
276612AE2-035 GEN
Solar/Wind Harmer
1.535
274823ROCKFORD ;21
Adder
11.108
946321AF1-296 GEN
Solar/Wind Harmer
5.821
971411AH1-196 GEN
Solar/Wind Harmer
7.659
274741AC1-111 GEN5
50/50
0.352
274739AURORA EC;2P
50/50
1.032
959091AF2-200 GEN
Solar/Wind Harmer
26.436
943121AE2-341 GEN
Solar/Wind Harmer
14.637
943591AF1-030 GEN
Solar/Wind Harmer
9.758
276799AD1-013 GEN
Solar/Wind Harmer
2.007
946671AF1-331 GEN
Solar/Wind Harmer
0.38
274855GSG-6 ;RU
Solar/Wind Harmer
3.335
274850MENDOTA H;RU
Solar/Wind Harmer
2.319
276602WESTBROOK C
Solar/Wind Harmer
1.92
276603SUBLETTE C
Solar/Wind Harmer
0.763
274857EASY ROAD;U1
Solar/Wind Harmer
3.417
274760LEE CO EC;1U
Adder
6.636
274767LEE CO EC;8U
Adder
6.557
970707AG2-453 GEN
Solar/Wind Harmer
15.618
965931AG1-462 GEN
Solar/Wind Harmer
14.028
971087AG2-675 GEN
Solar/Wind Harmer
2.047
274743AC1-111 GEN7
50/50
0.352
274745AC1-111 GEN9
50/50
6.44
276890AG1-513 C
50/50
0.505
274737AURORA EC;1P
50/50
1.032
957471AF2-041 GEN
Solar/Wind Harmer
39.654
959081AF2-199 GEN
Solar/Wind Harmer
13.218
971067AG2-660 GEN
Solar/Wind Harmer
3.074
962781AG1-127 GEN
Solar/Wind Harmer
9.235
274872LEEDK;1U
Solar/Wind Harmer
7.934
274858EASY ROAD;U2
Solar/Wind Harmer
3.417
274761LEE CO EC;2U
Adder
6.636
274766LEE CO EC;7U
Adder
6.557
276708O09 GEN2
Solar/Wind Harmer
2.208
274822ROCKFORD ;11
Adder
11.187
970819AG2-516 GEN
Solar/Wind Harmer
6.739
NYPJM->LTFIMP_NY
CLTF
0.193
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.08
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.059
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.508
MECLTFEXP_MEC->PJM
CLTF
4.311
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.144
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.43
LAGNLTFEXP_LAGN->PJM
CLTF
1.013
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.209

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345R__3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.11 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1585.33
MW Contribution:
8.89
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345R__3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.95 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1582.85
MW Contribution:
8.79
Bus #Bus NameTypeMW Contribution
274738AURORA EC;3P
50/50
1.485
274740AURORA EC;4P
50/50
1.485
971341AH1-150 GEN
Solar/Wind Harmer
24.555
971343AH1-151 GEN
Solar/Wind Harmer
24.555
962691AG1-118 GEN
Solar/Wind Harmer
27.548
960751AF2-366 GEN
Solar/Wind Harmer
2.454
274764LEE CO EC;5U
Adder
5.705
274765LEE CO EC;6U
Adder
5.705
274762LEE CO EC;3U
Adder
5.691
274763LEE CO EC;4U
Adder
5.638
938861AE1-114 GEN
Solar/Wind Harmer
4.593
276158O29GEN2
Solar/Wind Harmer
2.739
276157O29GEN1
Solar/Wind Harmer
2.082
274695ROCKY RD ;2P
Adder
5.972
274693ROCKY RD ;1P
Adder
5.914
274697ROCKY RD ;3P
Adder
1.622
274696ROCKY RD ;4P
Adder
6.08
972235AH1-702 GEN1
Adder
1.291
972236AH1-702 GEN2
Adder
1.119
957471AF2-041 GEN
Solar/Wind Harmer
36.832
959081AF2-199 GEN
Solar/Wind Harmer
12.277
971067AG2-660 GEN
Solar/Wind Harmer
2.855
962781AG1-127 GEN
Solar/Wind Harmer
8.135
274872LEEDK;1U
Solar/Wind Harmer
7.009
274745AC1-111 GEN9
Adder
4.499
274858EASY ROAD;U2
Solar/Wind Harmer
2.931
274761LEE CO EC;2U
Adder
5.691
274766LEE CO EC;7U
Adder
5.624
276708O09 GEN2
Solar/Wind Harmer
1.956
274822ROCKFORD ;11
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
5.36
971171AH1-044 GEN
Solar/Wind Harmer
24.555
274744AC1-111 GEN8
Adder
4.499
274746AC1-111 G10
Adder
4.499
971675AH1-338 GEN
Solar/Wind Harmer
14.368
276861AD2-134 GEN
Solar/Wind Harmer
1.422
276863AD2-134 GEN
Solar/Wind Harmer
1.422
972267AH1-718 GEN
Adder
2.82
971681AH1-341 GEN
Solar/Wind Harmer
8.895
276741O09 GEN1
Solar/Wind Harmer
1.956
274856ECOGROVE ;U1
Solar/Wind Harmer
1.648
276611AD2-172 GEN
Solar/Wind Harmer
1.25
276612AE2-035 GEN
Solar/Wind Harmer
1.25
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274823ROCKFORD ;21
Adder
8.755
959091AF2-200 GEN
Solar/Wind Harmer
24.555
943121AE2-341 GEN
Solar/Wind Harmer
13.063
943591AF1-030 GEN
Solar/Wind Harmer
8.709
276799AD1-013 GEN
Solar/Wind Harmer
1.769
946671AF1-331 GEN
Solar/Wind Harmer
0.335
274855GSG-6 ;RU
Solar/Wind Harmer
2.94
274850MENDOTA H;RU
Solar/Wind Harmer
2.044
276602WESTBROOK C
Solar/Wind Harmer
1.692
276603SUBLETTE C
Solar/Wind Harmer
0.667
274857EASY ROAD;U1
Solar/Wind Harmer
2.931
274760LEE CO EC;1U
Adder
5.691
274767LEE CO EC;8U
Adder
5.624
970707AG2-453 GEN
Solar/Wind Harmer
14.837
965931AG1-462 GEN
Solar/Wind Harmer
12.292
971087AG2-675 GEN
Solar/Wind Harmer
1.794
NYPJM->LTFIMP_NY
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.068
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.785
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.706
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.478
MECLTFEXP_MEC->PJM
CLTF
3.534
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.117
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.347
LAGNLTFEXP_LAGN->PJM
CLTF
0.871
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.19

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002__SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_120-45-L12002__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.04 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1584.26
MW Contribution:
9.52
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_120-45-L12002__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.86 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1581.53
MW Contribution:
9.42
Bus #Bus NameTypeMW Contribution
959091AF2-200 GEN
Solar/Wind Harmer
25.075
943121AE2-341 GEN
Solar/Wind Harmer
13.112
943591AF1-030 GEN
Solar/Wind Harmer
8.741
276799AD1-013 GEN
Solar/Wind Harmer
1.828
946671AF1-331 GEN
Solar/Wind Harmer
0.346
274855GSG-6 ;RU
Solar/Wind Harmer
3.04
274850MENDOTA H;RU
Solar/Wind Harmer
2.113
276602WESTBROOK C
Solar/Wind Harmer
1.75
276603SUBLETTE C
Solar/Wind Harmer
0.705
274857EASY ROAD;U1
Solar/Wind Harmer
3.137
274760LEE CO EC;1U
Adder
6.093
274767LEE CO EC;8U
Adder
6.021
970707AG2-453 GEN
Solar/Wind Harmer
14.657
965931AG1-462 GEN
Solar/Wind Harmer
13.135
971087AG2-675 GEN
Solar/Wind Harmer
1.917
274738AURORA EC;3P
50/50
1.501
274740AURORA EC;4P
50/50
1.501
971341AH1-150 GEN
Solar/Wind Harmer
25.075
971343AH1-151 GEN
Solar/Wind Harmer
25.075
962691AG1-118 GEN
Solar/Wind Harmer
28.205
960751AF2-366 GEN
Solar/Wind Harmer
2.525
274764LEE CO EC;5U
Adder
6.107
274765LEE CO EC;6U
Adder
6.107
274762LEE CO EC;3U
Adder
6.093
274763LEE CO EC;4U
Adder
6.035
938861AE1-114 GEN
Solar/Wind Harmer
4.957
274695ROCKY RD ;2P
Adder
6.651
274693ROCKY RD ;1P
Adder
6.585
274697ROCKY RD ;3P
Adder
1.807
274696ROCKY RD ;4P
Adder
6.777
276158O29GEN2
Solar/Wind Harmer
2.891
276157O29GEN1
Solar/Wind Harmer
2.198
972235AH1-702 GEN1
Adder
1.427
972236AH1-702 GEN2
Adder
1.238
971171AH1-044 GEN
Solar/Wind Harmer
25.075
971675AH1-338 GEN
Solar/Wind Harmer
14.853
276861AD2-134 GEN
Solar/Wind Harmer
1.47
276863AD2-134 GEN
Solar/Wind Harmer
1.47
274744AC1-111 GEN8
Adder
4.405
274746AC1-111 G10
Adder
4.405
972267AH1-718 GEN
Adder
2.969
971681AH1-341 GEN
Solar/Wind Harmer
9.521
276741O09 GEN1
Solar/Wind Harmer
2.064
274856ECOGROVE ;U1
Solar/Wind Harmer
1.824
276611AD2-172 GEN
Solar/Wind Harmer
1.383
276612AE2-035 GEN
Solar/Wind Harmer
1.383
946321AF1-296 GEN
Solar/Wind Harmer
5.44
274823ROCKFORD ;21
Adder
9.877
971411AH1-196 GEN
Solar/Wind Harmer
6.703
957471AF2-041 GEN
Solar/Wind Harmer
37.612
959081AF2-199 GEN
Solar/Wind Harmer
12.537
971067AG2-660 GEN
Solar/Wind Harmer
2.916
962781AG1-127 GEN
Solar/Wind Harmer
8.371
274872LEEDK;1U
Solar/Wind Harmer
7.203
274745AC1-111 GEN9
Adder
4.405
274858EASY ROAD;U2
Solar/Wind Harmer
3.137
274761LEE CO EC;2U
Adder
6.093
274766LEE CO EC;7U
Adder
6.021
276708O09 GEN2
Solar/Wind Harmer
2.064
274822ROCKFORD ;11
Adder
9.947
970819AG2-516 GEN
Solar/Wind Harmer
6.03
NYPJM->LTFIMP_NY
CLTF
0.18
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.282
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.519
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.602
MECLTFEXP_MEC->PJM
CLTF
4.065
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.361
LAGNLTFEXP_LAGN->PJM
CLTF
1.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.231

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P4_111-45-L11120__SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-L11120__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.85 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1581.28
MW Contribution:
8.89
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-L11120__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.69 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1578.78
MW Contribution:
8.79
Bus #Bus NameTypeMW Contribution
274738AURORA EC;3P
50/50
1.485
274740AURORA EC;4P
50/50
1.485
971341AH1-150 GEN
Solar/Wind Harmer
24.555
971343AH1-151 GEN
Solar/Wind Harmer
24.555
962691AG1-118 GEN
Solar/Wind Harmer
27.548
960751AF2-366 GEN
Solar/Wind Harmer
2.454
274764LEE CO EC;5U
Adder
5.705
274765LEE CO EC;6U
Adder
5.705
274762LEE CO EC;3U
Adder
5.691
274763LEE CO EC;4U
Adder
5.638
938861AE1-114 GEN
Solar/Wind Harmer
4.593
276158O29GEN2
Solar/Wind Harmer
2.739
276157O29GEN1
Solar/Wind Harmer
2.082
274695ROCKY RD ;2P
Adder
5.972
274693ROCKY RD ;1P
Adder
5.914
274697ROCKY RD ;3P
Adder
1.622
274696ROCKY RD ;4P
Adder
6.08
972235AH1-702 GEN1
Adder
1.291
972236AH1-702 GEN2
Adder
1.119
959091AF2-200 GEN
Solar/Wind Harmer
24.555
943121AE2-341 GEN
Solar/Wind Harmer
13.063
943591AF1-030 GEN
Solar/Wind Harmer
8.709
276799AD1-013 GEN
Solar/Wind Harmer
1.769
946671AF1-331 GEN
Solar/Wind Harmer
0.335
274855GSG-6 ;RU
Solar/Wind Harmer
2.94
274850MENDOTA H;RU
Solar/Wind Harmer
2.044
276602WESTBROOK C
Solar/Wind Harmer
1.692
276603SUBLETTE C
Solar/Wind Harmer
0.667
274857EASY ROAD;U1
Solar/Wind Harmer
2.931
274760LEE CO EC;1U
Adder
5.691
274767LEE CO EC;8U
Adder
5.624
970707AG2-453 GEN
Solar/Wind Harmer
14.837
965931AG1-462 GEN
Solar/Wind Harmer
12.292
971087AG2-675 GEN
Solar/Wind Harmer
1.794
957471AF2-041 GEN
Solar/Wind Harmer
36.832
959081AF2-199 GEN
Solar/Wind Harmer
12.277
971067AG2-660 GEN
Solar/Wind Harmer
2.855
962781AG1-127 GEN
Solar/Wind Harmer
8.135
274872LEEDK;1U
Solar/Wind Harmer
7.009
274745AC1-111 GEN9
Adder
4.499
274858EASY ROAD;U2
Solar/Wind Harmer
2.931
274761LEE CO EC;2U
Adder
5.691
274766LEE CO EC;7U
Adder
5.624
276708O09 GEN2
Solar/Wind Harmer
1.956
274822ROCKFORD ;11
Adder
8.816
970819AG2-516 GEN
Solar/Wind Harmer
5.36
971171AH1-044 GEN
Solar/Wind Harmer
24.555
274744AC1-111 GEN8
Adder
4.499
274746AC1-111 G10
Adder
4.499
971675AH1-338 GEN
Solar/Wind Harmer
14.368
276861AD2-134 GEN
Solar/Wind Harmer
1.422
276863AD2-134 GEN
Solar/Wind Harmer
1.422
972267AH1-718 GEN
Adder
2.82
971681AH1-341 GEN
Solar/Wind Harmer
8.895
276741O09 GEN1
Solar/Wind Harmer
1.956
274856ECOGROVE ;U1
Solar/Wind Harmer
1.648
276611AD2-172 GEN
Solar/Wind Harmer
1.25
276612AE2-035 GEN
Solar/Wind Harmer
1.25
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274823ROCKFORD ;21
Adder
8.755
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.068
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.785
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.706
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.478
MECLTFEXP_MEC->PJM
CLTF
3.534
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.117
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.347
LAGNLTFEXP_LAGN->PJM
CLTF
0.871
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.19

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L10322__SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_120-45-L10322__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.68 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1578.61
MW Contribution:
9.51
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_120-45-L10322__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1575.88
MW Contribution:
9.41
Bus #Bus NameTypeMW Contribution
274738AURORA EC;3P
50/50
1.501
274740AURORA EC;4P
50/50
1.501
971341AH1-150 GEN
Solar/Wind Harmer
25.067
971343AH1-151 GEN
Solar/Wind Harmer
25.067
962691AG1-118 GEN
Solar/Wind Harmer
28.193
960751AF2-366 GEN
Solar/Wind Harmer
2.524
274764LEE CO EC;5U
Adder
6.1
274765LEE CO EC;6U
Adder
6.1
274762LEE CO EC;3U
Adder
6.086
274763LEE CO EC;4U
Adder
6.029
938861AE1-114 GEN
Solar/Wind Harmer
4.951
274695ROCKY RD ;2P
Adder
6.639
274693ROCKY RD ;1P
Adder
6.574
274697ROCKY RD ;3P
Adder
1.804
274696ROCKY RD ;4P
Adder
6.765
276158O29GEN2
Solar/Wind Harmer
2.889
276157O29GEN1
Solar/Wind Harmer
2.196
972235AH1-702 GEN1
Adder
1.425
972236AH1-702 GEN2
Adder
1.236
971171AH1-044 GEN
Solar/Wind Harmer
25.067
971675AH1-338 GEN
Solar/Wind Harmer
14.845
276861AD2-134 GEN
Solar/Wind Harmer
1.469
957471AF2-041 GEN
Solar/Wind Harmer
37.6
959081AF2-199 GEN
Solar/Wind Harmer
12.533
971067AG2-660 GEN
Solar/Wind Harmer
2.915
962781AG1-127 GEN
Solar/Wind Harmer
8.366
274872LEEDK;1U
Solar/Wind Harmer
7.2
274745AC1-111 GEN9
Adder
4.403
274858EASY ROAD;U2
Solar/Wind Harmer
3.134
274761LEE CO EC;2U
Adder
6.086
274766LEE CO EC;7U
Adder
6.014
276708O09 GEN2
Solar/Wind Harmer
2.063
274822ROCKFORD ;11
Adder
9.928
970819AG2-516 GEN
Solar/Wind Harmer
6.018
959091AF2-200 GEN
Solar/Wind Harmer
25.067
943121AE2-341 GEN
Solar/Wind Harmer
13.11
943591AF1-030 GEN
Solar/Wind Harmer
8.74
276799AD1-013 GEN
Solar/Wind Harmer
1.827
946671AF1-331 GEN
Solar/Wind Harmer
0.346
274855GSG-6 ;RU
Solar/Wind Harmer
3.038
274850MENDOTA H;RU
Solar/Wind Harmer
2.112
276602WESTBROOK C
Solar/Wind Harmer
1.749
276603SUBLETTE C
Solar/Wind Harmer
0.704
274857EASY ROAD;U1
Solar/Wind Harmer
3.134
274760LEE CO EC;1U
Adder
6.086
274767LEE CO EC;8U
Adder
6.014
970707AG2-453 GEN
Solar/Wind Harmer
14.656
965931AG1-462 GEN
Solar/Wind Harmer
13.121
971087AG2-675 GEN
Solar/Wind Harmer
1.915
276863AD2-134 GEN
Solar/Wind Harmer
1.469
274744AC1-111 GEN8
Adder
4.403
274746AC1-111 G10
Adder
4.403
972267AH1-718 GEN
Adder
2.967
971681AH1-341 GEN
Solar/Wind Harmer
9.511
276741O09 GEN1
Solar/Wind Harmer
2.063
274856ECOGROVE ;U1
Solar/Wind Harmer
1.821
276611AD2-172 GEN
Solar/Wind Harmer
1.381
276612AE2-035 GEN
Solar/Wind Harmer
1.381
946321AF1-296 GEN
Solar/Wind Harmer
5.434
274823ROCKFORD ;21
Adder
9.858
971411AH1-196 GEN
Solar/Wind Harmer
6.686
NYPJM->LTFIMP_NY
CLTF
0.18
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.2
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.6
MECLTFEXP_MEC->PJM
CLTF
4.056
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.361
LAGNLTFEXP_LAGN->PJM
CLTF
1.025
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.231

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P2-2_120_LO-345R__2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_120_LO-345R__2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.68 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1578.61
MW Contribution:
9.51
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_120_LO-345R__2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1575.88
MW Contribution:
9.41
Bus #Bus NameTypeMW Contribution
274738AURORA EC;3P
50/50
1.501
274740AURORA EC;4P
50/50
1.501
971341AH1-150 GEN
Solar/Wind Harmer
25.067
971343AH1-151 GEN
Solar/Wind Harmer
25.067
962691AG1-118 GEN
Solar/Wind Harmer
28.193
960751AF2-366 GEN
Solar/Wind Harmer
2.524
274764LEE CO EC;5U
Adder
6.1
274765LEE CO EC;6U
Adder
6.1
274762LEE CO EC;3U
Adder
6.086
274763LEE CO EC;4U
Adder
6.029
938861AE1-114 GEN
Solar/Wind Harmer
4.951
274695ROCKY RD ;2P
Adder
6.639
274693ROCKY RD ;1P
Adder
6.574
274697ROCKY RD ;3P
Adder
1.804
274696ROCKY RD ;4P
Adder
6.765
276158O29GEN2
Solar/Wind Harmer
2.889
276157O29GEN1
Solar/Wind Harmer
2.196
972235AH1-702 GEN1
Adder
1.425
972236AH1-702 GEN2
Adder
1.236
957471AF2-041 GEN
Solar/Wind Harmer
37.6
959081AF2-199 GEN
Solar/Wind Harmer
12.533
971067AG2-660 GEN
Solar/Wind Harmer
2.915
962781AG1-127 GEN
Solar/Wind Harmer
8.366
274872LEEDK;1U
Solar/Wind Harmer
7.2
274745AC1-111 GEN9
Adder
4.403
274858EASY ROAD;U2
Solar/Wind Harmer
3.134
274761LEE CO EC;2U
Adder
6.086
274766LEE CO EC;7U
Adder
6.014
276708O09 GEN2
Solar/Wind Harmer
2.063
274822ROCKFORD ;11
Adder
9.928
970819AG2-516 GEN
Solar/Wind Harmer
6.018
959091AF2-200 GEN
Solar/Wind Harmer
25.067
943121AE2-341 GEN
Solar/Wind Harmer
13.11
943591AF1-030 GEN
Solar/Wind Harmer
8.74
276799AD1-013 GEN
Solar/Wind Harmer
1.827
946671AF1-331 GEN
Solar/Wind Harmer
0.346
274855GSG-6 ;RU
Solar/Wind Harmer
3.038
274850MENDOTA H;RU
Solar/Wind Harmer
2.112
276602WESTBROOK C
Solar/Wind Harmer
1.749
276603SUBLETTE C
Solar/Wind Harmer
0.704
274857EASY ROAD;U1
Solar/Wind Harmer
3.134
274760LEE CO EC;1U
Adder
6.086
274767LEE CO EC;8U
Adder
6.014
970707AG2-453 GEN
Solar/Wind Harmer
14.656
965931AG1-462 GEN
Solar/Wind Harmer
13.121
971087AG2-675 GEN
Solar/Wind Harmer
1.915
971171AH1-044 GEN
Solar/Wind Harmer
25.067
971675AH1-338 GEN
Solar/Wind Harmer
14.845
276861AD2-134 GEN
Solar/Wind Harmer
1.469
276863AD2-134 GEN
Solar/Wind Harmer
1.469
274744AC1-111 GEN8
Adder
4.403
274746AC1-111 G10
Adder
4.403
972267AH1-718 GEN
Adder
2.967
971681AH1-341 GEN
Solar/Wind Harmer
9.511
276741O09 GEN1
Solar/Wind Harmer
2.063
274856ECOGROVE ;U1
Solar/Wind Harmer
1.821
276611AD2-172 GEN
Solar/Wind Harmer
1.381
276612AE2-035 GEN
Solar/Wind Harmer
1.381
946321AF1-296 GEN
Solar/Wind Harmer
5.434
274823ROCKFORD ;21
Adder
9.858
971411AH1-196 GEN
Solar/Wind Harmer
6.686
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
NYPJM->LTFIMP_NY
CLTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.2
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.6
MECLTFEXP_MEC->PJM
CLTF
4.056
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.505
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.361
LAGNLTFEXP_LAGN->PJM
CLTF
1.025
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.231

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L11120__SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_120-45-L11120__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.67 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1578.44
MW Contribution:
9.51
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_120-45-L11120__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.49 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1575.72
MW Contribution:
9.41
Bus #Bus NameTypeMW Contribution
274738AURORA EC;3P
50/50
1.501
274740AURORA EC;4P
50/50
1.501
971341AH1-150 GEN
Solar/Wind Harmer
25.067
971343AH1-151 GEN
Solar/Wind Harmer
25.067
962691AG1-118 GEN
Solar/Wind Harmer
28.193
960751AF2-366 GEN
Solar/Wind Harmer
2.524
274764LEE CO EC;5U
Adder
6.1
274765LEE CO EC;6U
Adder
6.1
274762LEE CO EC;3U
Adder
6.086
274763LEE CO EC;4U
Adder
6.029
938861AE1-114 GEN
Solar/Wind Harmer
4.951
274695ROCKY RD ;2P
Adder
6.639
274693ROCKY RD ;1P
Adder
6.574
959091AF2-200 GEN
Solar/Wind Harmer
25.067
943121AE2-341 GEN
Solar/Wind Harmer
13.11
943591AF1-030 GEN
Solar/Wind Harmer
8.74
276799AD1-013 GEN
Solar/Wind Harmer
1.827
946671AF1-331 GEN
Solar/Wind Harmer
0.346
274855GSG-6 ;RU
Solar/Wind Harmer
3.038
274850MENDOTA H;RU
Solar/Wind Harmer
2.112
276602WESTBROOK C
Solar/Wind Harmer
1.749
276603SUBLETTE C
Solar/Wind Harmer
0.704
274857EASY ROAD;U1
Solar/Wind Harmer
3.134
274760LEE CO EC;1U
Adder
6.086
274767LEE CO EC;8U
Adder
6.014
970707AG2-453 GEN
Solar/Wind Harmer
14.656
965931AG1-462 GEN
Solar/Wind Harmer
13.121
971087AG2-675 GEN
Solar/Wind Harmer
1.915
274697ROCKY RD ;3P
Adder
1.804
274696ROCKY RD ;4P
Adder
6.765
276158O29GEN2
Solar/Wind Harmer
2.889
276157O29GEN1
Solar/Wind Harmer
2.196
972235AH1-702 GEN1
Adder
1.425
972236AH1-702 GEN2
Adder
1.236
957471AF2-041 GEN
Solar/Wind Harmer
37.6
959081AF2-199 GEN
Solar/Wind Harmer
12.533
971067AG2-660 GEN
Solar/Wind Harmer
2.915
962781AG1-127 GEN
Solar/Wind Harmer
8.366
274872LEEDK;1U
Solar/Wind Harmer
7.2
274745AC1-111 GEN9
Adder
4.403
274858EASY ROAD;U2
Solar/Wind Harmer
3.134
274761LEE CO EC;2U
Adder
6.086
274766LEE CO EC;7U
Adder
6.014
276708O09 GEN2
Solar/Wind Harmer
2.063
274822ROCKFORD ;11
Adder
9.928
970819AG2-516 GEN
Solar/Wind Harmer
6.018
971171AH1-044 GEN
Solar/Wind Harmer
25.067
971675AH1-338 GEN
Solar/Wind Harmer
14.845
276861AD2-134 GEN
Solar/Wind Harmer
1.469
276863AD2-134 GEN
Solar/Wind Harmer
1.469
274744AC1-111 GEN8
Adder
4.403
274746AC1-111 G10
Adder
4.403
972267AH1-718 GEN
Adder
2.967
971681AH1-341 GEN
Solar/Wind Harmer
9.511
276741O09 GEN1
Solar/Wind Harmer
2.063
274856ECOGROVE ;U1
Solar/Wind Harmer
1.821
276611AD2-172 GEN
Solar/Wind Harmer
1.381
276612AE2-035 GEN
Solar/Wind Harmer
1.381
946321AF1-296 GEN
Solar/Wind Harmer
5.434
274823ROCKFORD ;21
Adder
9.858
971411AH1-196 GEN
Solar/Wind Harmer
6.686
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
NYPJM->LTFIMP_NY
CLTF
0.18
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.2
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.6
MECLTFEXP_MEC->PJM
CLTF
4.056
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.361
LAGNLTFEXP_LAGN->PJM
CLTF
1.025
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.231

Details for STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line l/o COMED_P4-6_111-345-B______SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_111-345-B______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.37 %
Rating:455.0 MVA
Rating Type:STE
MVA to Mitigate:470.34
MW Contribution:
11.87
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_111-345-B______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.37 %
Rating:455.0 MVA
Rating Type:STE
MVA to Mitigate:470.32
MW Contribution:
11.86
Bus #Bus NameTypeMW Contribution
938861AE1-114 GEN
Solar/Wind Harmer
5.23
276158O29GEN2
Solar/Wind Harmer
2.362
276157O29GEN1
Solar/Wind Harmer
1.796
971341AH1-150 GEN
Solar/Wind Harmer
7.569
971343AH1-151 GEN
Solar/Wind Harmer
7.569
960751AF2-366 GEN
Solar/Wind Helper
1.945
276708O09 GEN2
Solar/Wind Harmer
1.686
957471AF2-041 GEN
Solar/Wind Harmer
11.353
959081AF2-199 GEN
Solar/Wind Harmer
3.784
971067AG2-660 GEN
Solar/Wind Harmer
0.88
274872LEEDK;1U
Solar/Wind Helper
11.034
276799AD1-013 GEN
Solar/Wind Harmer
11.195
946671AF1-331 GEN
Solar/Wind Harmer
2.121
274855GSG-6 ;RU
Solar/Wind Harmer
18.29
274850MENDOTA H;RU
Solar/Wind Harmer
12.717
276602WESTBROOK C
Solar/Wind Harmer
10.529
276603SUBLETTE C
Solar/Wind Harmer
1.114
959091AF2-200 GEN
Solar/Wind Harmer
7.569
971675AH1-338 GEN
Solar/Wind Harmer
90.078
276861AD2-134 GEN
Solar/Wind Harmer
8.845
276863AD2-134 GEN
Solar/Wind Harmer
8.845
971681AH1-341 GEN
Solar/Wind Harmer
11.869
276741O09 GEN1
Solar/Wind Harmer
1.686
971171AH1-044 GEN
Solar/Wind Harmer
7.569
NYPJM->LTFIMP_NY
CLTF
0.043
WECLTFEXP_WEC->PJM
CLTF
0.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.842
CPLELTFEXP_CPLE->PJM
CLTF
0.023
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.186
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.657
MECLTFEXP_MEC->PJM
CLTF
2.369
SIGELTFEXP_SIGE->PJM
CLTF
0.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
0.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.145
TVALTFEXP_TVA->PJM
CLTF
0.214

Details for STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line l/o COMED_P4_111-45-TR81____SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-TR81____SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.42 %
Rating:455.0 MVA
Rating Type:STE
MVA to Mitigate:456.9
MW Contribution:
11.98
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-TR81____SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:455.0 MVA
Rating Type:STE
MVA to Mitigate:456.86
MW Contribution:
11.97
Bus #Bus NameTypeMW Contribution
938861AE1-114 GEN
Solar/Wind Harmer
5.275
276158O29GEN2
Solar/Wind Harmer
2.376
276157O29GEN1
Solar/Wind Harmer
1.806
971341AH1-150 GEN
Solar/Wind Harmer
7.613
971343AH1-151 GEN
Solar/Wind Harmer
7.613
960751AF2-366 GEN
Solar/Wind Helper
1.878
971675AH1-338 GEN
Solar/Wind Harmer
90.824
276861AD2-134 GEN
Solar/Wind Harmer
8.918
276863AD2-134 GEN
Solar/Wind Harmer
8.918
971681AH1-341 GEN
Solar/Wind Harmer
11.982
276741O09 GEN1
Solar/Wind Harmer
1.696
971171AH1-044 GEN
Solar/Wind Harmer
7.613
276799AD1-013 GEN
Solar/Wind Harmer
11.288
946671AF1-331 GEN
Solar/Wind Harmer
2.139
274855GSG-6 ;RU
Solar/Wind Harmer
18.442
274850MENDOTA H;RU
Solar/Wind Harmer
12.822
276602WESTBROOK C
Solar/Wind Harmer
10.616
276603SUBLETTE C
Solar/Wind Harmer
1.123
959091AF2-200 GEN
Solar/Wind Harmer
7.613
276708O09 GEN2
Solar/Wind Harmer
1.696
957471AF2-041 GEN
Solar/Wind Harmer
11.419
959081AF2-199 GEN
Solar/Wind Harmer
3.806
971067AG2-660 GEN
Solar/Wind Harmer
0.885
274872LEEDK;1U
Solar/Wind Helper
10.775
NYPJM->LTFIMP_NY
CLTF
0.043
WECLTFEXP_WEC->PJM
CLTF
0.141
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.826
CPLELTFEXP_CPLE->PJM
CLTF
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.155
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.651
MECLTFEXP_MEC->PJM
CLTF
2.372
SIGELTFEXP_SIGE->PJM
CLTF
0.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
0.734
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.14
TVALTFEXP_TVA->PJM
CLTF
0.212

Details for STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line l/o COMED_P4_111-45-L11124__SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-L11124__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.42 %
Rating:455.0 MVA
Rating Type:STE
MVA to Mitigate:456.9
MW Contribution:
11.98
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-L11124__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:455.0 MVA
Rating Type:STE
MVA to Mitigate:456.86
MW Contribution:
11.97
Bus #Bus NameTypeMW Contribution
938861AE1-114 GEN
Solar/Wind Harmer
5.275
276158O29GEN2
Solar/Wind Harmer
2.376
276157O29GEN1
Solar/Wind Harmer
1.806
971341AH1-150 GEN
Solar/Wind Harmer
7.613
971343AH1-151 GEN
Solar/Wind Harmer
7.613
960751AF2-366 GEN
Solar/Wind Helper
1.878
971675AH1-338 GEN
Solar/Wind Harmer
90.824
276861AD2-134 GEN
Solar/Wind Harmer
8.918
276863AD2-134 GEN
Solar/Wind Harmer
8.918
971681AH1-341 GEN
Solar/Wind Harmer
11.982
276741O09 GEN1
Solar/Wind Harmer
1.696
971171AH1-044 GEN
Solar/Wind Harmer
7.613
276799AD1-013 GEN
Solar/Wind Harmer
11.288
946671AF1-331 GEN
Solar/Wind Harmer
2.139
274855GSG-6 ;RU
Solar/Wind Harmer
18.442
274850MENDOTA H;RU
Solar/Wind Harmer
12.822
276602WESTBROOK C
Solar/Wind Harmer
10.616
276603SUBLETTE C
Solar/Wind Harmer
1.123
959091AF2-200 GEN
Solar/Wind Harmer
7.613
276708O09 GEN2
Solar/Wind Harmer
1.696
957471AF2-041 GEN
Solar/Wind Harmer
11.419
959081AF2-199 GEN
Solar/Wind Harmer
3.806
971067AG2-660 GEN
Solar/Wind Harmer
0.885
274872LEEDK;1U
Solar/Wind Helper
10.775
NYPJM->LTFIMP_NY
CLTF
0.043
WECLTFEXP_WEC->PJM
CLTF
0.141
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.826
CPLELTFEXP_CPLE->PJM
CLTF
0.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.155
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.651
MECLTFEXP_MEC->PJM
CLTF
2.372
SIGELTFEXP_SIGE->PJM
CLTF
0.003
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
0.734
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.14
TVALTFEXP_TVA->PJM
CLTF
0.212

Details for STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345B__1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345B__1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.42 %
Rating:455.0 MVA
Rating Type:STE
MVA to Mitigate:456.9
MW Contribution:
11.98
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345B__1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:455.0 MVA
Rating Type:STE
MVA to Mitigate:456.85
MW Contribution:
11.97
Bus #Bus NameTypeMW Contribution
938861AE1-114 GEN
Solar/Wind Harmer
5.275
276158O29GEN2
Solar/Wind Harmer
2.376
276157O29GEN1
Solar/Wind Harmer
1.806
971341AH1-150 GEN
Solar/Wind Harmer
7.613
971343AH1-151 GEN
Solar/Wind Harmer
7.613
276708O09 GEN2
Solar/Wind Harmer
1.696
957471AF2-041 GEN
Solar/Wind Harmer
11.419
959081AF2-199 GEN
Solar/Wind Harmer
3.806
971067AG2-660 GEN
Solar/Wind Harmer
0.885
274872LEEDK;1U
Solar/Wind Helper
10.775
960751AF2-366 GEN
Solar/Wind Helper
1.878
971675AH1-338 GEN
Solar/Wind Harmer
90.824
276861AD2-134 GEN
Solar/Wind Harmer
8.918
276863AD2-134 GEN
Solar/Wind Harmer
8.918
971681AH1-341 GEN
Solar/Wind Harmer
11.982
276741O09 GEN1
Solar/Wind Harmer
1.696
971171AH1-044 GEN
Solar/Wind Harmer
7.613
276799AD1-013 GEN
Solar/Wind Harmer
11.288
946671AF1-331 GEN
Solar/Wind Harmer
2.139
274855GSG-6 ;RU
Solar/Wind Harmer
18.442
274850MENDOTA H;RU
Solar/Wind Harmer
12.822
276602WESTBROOK C
Solar/Wind Harmer
10.616
276603SUBLETTE C
Solar/Wind Harmer
1.123
959091AF2-200 GEN
Solar/Wind Harmer
7.613
NYPJM->LTFIMP_NY
CLTF
0.043
WECLTFEXP_WEC->PJM
CLTF
0.141
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.826
CPLELTFEXP_CPLE->PJM
CLTF
0.021
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.651
MECLTFEXP_MEC->PJM
CLTF
2.372
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.155
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.025
LAGNLTFEXP_LAGN->PJM
CLTF
0.734
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.14
TVALTFEXP_TVA->PJM
CLTF
0.212

Details for UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.02 %
Rating:2004.0 MVA
Rating Type:B
MVA to Mitigate:2224.79
MW Contribution:
15.24
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE/NIPS
Facility Description:
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.65 %
Rating:2004.0 MVA
Rating Type:B
MVA to Mitigate:2197.35
MW Contribution:
15.05
Bus #Bus NameTypeMW Contribution
274815UNIV PK N;XU
50/50
0.857
274813UNIV PK N;9U
50/50
0.855
274816UNIV PK N;YU
50/50
0.855
274809UNIV PK N;5U
50/50
0.851
274805UNIV PK N;1U
50/50
15.639
274808UNIV PK N;4U
50/50
15.536
274711KENDALL ;4S
50/50
0.926
274709KENDALL ;3S
50/50
0.926
274798UNIV PARK;1U
50/50
0.313
958481AF2-142 GEN
Solar/Wind Harmer
18.76
958491AF2-143 GEN
Solar/Wind Harmer
17.714
276893AG1-478 C
Solar/Wind Harmer
0.512
274674JOLIET 9 ;6U
Adder
17.94
276776AD2-060 GEN
Solar/Wind Harmer
0.484
274888KELLY CRK;1U
Solar/Wind Harmer
6.816
970941AG2-585 GEN
Solar/Wind Harmer
6.353
958011AF2-095 GEN
Solar/Wind Harmer
16.632
276897AD1-100 C
Solar/Wind Harmer
52.935
274683WAUKEGAN ;8U
Adder
23.403
274683WAUKEGAN ;8U
Adder
19.728
274695ROCKY RD ;2P
Adder
12.364
274693ROCKY RD ;1P
Adder
12.242
274697ROCKY RD ;3P
Adder
3.359
274696ROCKY RD ;4P
Adder
12.655
274770LINCOLN ;1U
Adder
6.783
274771LINCOLN ;2U
Adder
6.783
962691AG1-118 GEN
Solar/Wind Harmer
32.753
276901AD2-066 C O1
Solar/Wind Harmer
3.814
960751AF2-366 GEN
Solar/Wind Harmer
3.117
276872AE1-163_GEN1
Solar/Wind Harmer
7.281
276876AE1-163_GEN2
Solar/Wind Harmer
7.281
971341AH1-150 GEN
Solar/Wind Harmer
20.999
971343AH1-151 GEN
Solar/Wind Harmer
20.999
972235AH1-702 GEN1
Adder
2.623
972236AH1-702 GEN2
Adder
2.281
938861AE1-114 GEN
Solar/Wind Harmer
8.329
274764LEE CO EC;5U
Adder
9.406
274765LEE CO EC;6U
Adder
9.406
274762LEE CO EC;3U
Adder
9.384
274763LEE CO EC;4U
Adder
9.296
276158O29GEN2
Solar/Wind Harmer
4.887
276157O29GEN1
Solar/Wind Harmer
3.715
276645AC1-214 GEN1
Solar/Wind Harmer
1.277
942111AE2-223 GEN
Solar/Wind Harmer
6.793
960611AF2-352 GEN
Solar/Wind Harmer
1.833
274880W4-005 GEN4
Solar/Wind Harmer
1.937
276174W4-005 GEN2
Solar/Wind Harmer
1.937
276615X2-022 GEN
Solar/Wind Harmer
1.195
276838X2-022 GEN2
Solar/Wind Harmer
0.142
276916AD2-100_GEN
Solar/Wind Harmer
11.094
276911AD2-131_GEN
Solar/Wind Harmer
2.242
274814UNIV PK N;0U
50/50
15.741
274807UNIV PK N;3U
50/50
15.707
274811UNIV PK N;7U
50/50
15.605
274803UNIV PARK;6U
50/50
10.566
274654BRAIDWOOD;1U
50/50
4.693
972259AH1-714 GEN
50/50
24.289
972038AH1-567 GEN2
50/50
0.451
274707KENDALL ;2S
50/50
0.887
274676JOLIET 29;8U
Adder
35.164
274729ELWOOD EC;1P
Adder
19.419
274730ELWOOD EC;6P
Adder
19.39
274734ELWOOD EC;8P
Adder
19.39
274736ELWOOD EC;9P
Adder
19.39
970707AG2-453 GEN
Solar/Wind Harmer
32.699
276772AC2-154 GEN
Solar/Wind Harmer
3.224
276806AD2-047 C O1
Solar/Wind Harmer
12.358
274887GEN-1.85
Solar/Wind Harmer
6.154
276843GEN-1.7
Solar/Wind Harmer
0.662
939351AE1-166 GEN
Solar/Wind Harmer
6.758
943121AE2-341 GEN
Solar/Wind Harmer
16.939
943591AF1-030 GEN
Solar/Wind Harmer
11.293
274682WAUKEGAN ;7U
Adder
20.01
274772LINCOLN ;3U
Adder
6.783
274826FISK ;BP
Adder
11.9
276868AE1-113 GEN
Solar/Wind Harmer
10.876
274879MINONK ;1U
Solar/Wind Harmer
7.251
276799AD1-013 GEN
Solar/Wind Harmer
2.348
946671AF1-331 GEN
Solar/Wind Harmer
0.445
274855GSG-6 ;RU
Solar/Wind Harmer
3.918
274850MENDOTA H;RU
Solar/Wind Harmer
2.724
276602WESTBROOK C
Solar/Wind Harmer
2.255
959091AF2-200 GEN
Solar/Wind Harmer
20.999
274862TOP CROP ;2U
Solar/Wind Harmer
5.225
970571AG2-364 GEN
Solar/Wind Harmer
20.356
274857EASY ROAD;U1
Solar/Wind Harmer
4.832
274760LEE CO EC;1U
Adder
9.384
274767LEE CO EC;8U
Adder
9.274
276603SUBLETTE C
Solar/Wind Harmer
1.053
274851PROVIDENC;RU
Solar/Wind Harmer
2.714
274849CRESCENT ;1U
Solar/Wind Harmer
1.762
276782AC1-033 GEN
Solar/Wind Harmer
3.765
274878BISHOP HL;2U
Solar/Wind Harmer
3.185
965931AG1-462 GEN
Solar/Wind Harmer
23.443
971087AG2-675 GEN
Solar/Wind Harmer
3.421
276164X3-005 C
Solar/Wind Harmer
0.611
965091AG1-374 GEN
Solar/Wind Harmer
23.641
959611AF2-252 GEN
Solar/Wind Harmer
1.833
274724RIVER EC ;11
Adder
11.578
276785W4-005 GEN1
Solar/Wind Harmer
1.937
971993AH1-541 GEN
Solar/Wind Harmer
5.919
957381AF2-032 GEN
Solar/Wind Harmer
1.106
942481AE2-261 GEN
Solar/Wind Harmer
16.335
274806UNIV PK N;2U
50/50
0.872
274810UNIV PK N;6U
50/50
0.853
274812UNIV PK N;8U
50/50
15.605
274802UNIV PARK;5U
50/50
10.566
274710KENDALL ;4C
50/50
1.385
274705KENDALL ;1S
50/50
0.887
276694AA1-018 GEN2
Solar/Wind Harmer
7.891
276691AA1-018 GEN1
Solar/Wind Harmer
0.943
274676JOLIET 29;8U
Adder
36.467
276805AD2-038 GEN
Solar/Wind Harmer
6.055
274732ELWOOD EC;7P
Adder
19.39
274674JOLIET 9 ;6U
Adder
17.94
274871GR RIDGE ;2U
Solar/Wind Harmer
8.956
274847GR RIDGE ;BU
Solar/Wind Harmer
5.889
941551AE2-152 GEN
Solar/Wind Harmer
5.168
274745AC1-111 GEN9
Adder
6.327
274682WAUKEGAN ;7U
Adder
20.01
274828WAUKEGAN ;BP
Adder
12.268
972207SS24-0001
Solar/Wind Harmer
24.116
274773LINCOLN ;4U
Adder
6.783
274774LINCOLN ;5U
Adder
6.783
962781AG1-127 GEN
Solar/Wind Harmer
10.333
274872LEEDK;1U
Solar/Wind Harmer
8.878
276882AE2-255 GEN
Solar/Wind Harmer
3.626
971997AH1-543 GEN
Solar/Wind Harmer
16.634
957471AF2-041 GEN
Solar/Wind Harmer
31.498
959081AF2-199 GEN
Solar/Wind Harmer
10.499
971067AG2-660 GEN
Solar/Wind Harmer
2.442
274822ROCKFORD ;11
Adder
20.529
970819AG2-516 GEN
Solar/Wind Harmer
12.413
274861TOP CROP ;1U
Solar/Wind Harmer
6.257
970569AG2-363 GEN
Solar/Wind Harmer
30.535
939401AE1-172 GEN
Solar/Wind Harmer
14.156
274858EASY ROAD;U2
Solar/Wind Harmer
4.832
274761LEE CO EC;2U
Adder
9.384
274766LEE CO EC;7U
Adder
9.274
276708O09 GEN2
Solar/Wind Harmer
3.489
276646AC1-214 GEN2
Solar/Wind Harmer
1.277
274848CAMPGROVE;RU
Solar/Wind Harmer
6.014
276655WTG1_EQ
Solar/Wind Harmer
7.232
276656WTG2_EQ
Solar/Wind Harmer
0.958
939741AE1-205 GEN
Solar/Wind Harmer
16.572
274723RIVER EC ;12
Adder
11.919
276686W4-005 GEN3
Solar/Wind Harmer
1.937
276621W2-048 GEN
Solar/Wind Harmer
3.804
965911AG1-460 GEN
Solar/Wind Harmer
0.762
972037AH1-567 GEN1
50/50
0.332
274655BRAIDWOOD;2U
50/50
4.572
972228AH1-698 GEN2
50/50
4.883
972227AH1-698 GEN1
50/50
3.426
274660LASCO STA;1U
50/50
8.627
274661LASCO STA;2U
50/50
6.678
274708KENDALL ;3C
50/50
1.401
274799UNIV PARK;2U
50/50
0.323
274800UNIV PARK;3U
50/50
7.2
274801UNIV PARK;4U
50/50
7.2
274704KENDALL ;1C
50/50
1.328
274706KENDALL ;2C
50/50
1.328
274675JOLIET 29;7U
Adder
36.487
274675JOLIET 29;7U
Adder
35.184
274731ELWOOD EC;2P
Adder
19.419
274733ELWOOD EC;3P
Adder
19.419
274735ELWOOD EC;4P
Adder
19.419
970073AG2-061 GEN
Solar/Wind Harmer
2.746
274728ELWOOD EC;5P
Adder
19.39
970833AG2-524 GEN
Solar/Wind Harmer
10.188
970833AG2-524 GEN
Solar/Wind Harmer
4.739
276893AG1-478 C
Solar/Wind Harmer
0.642
960591AF2-350 GEN
Solar/Wind Harmer
11.551
274687WILL CNTY;4U
Adder
31.654
274687WILL CNTY;4U
Adder
31.654
274744AC1-111 GEN8
Adder
6.327
274746AC1-111 G10
Adder
6.327
274775LINCOLN ;6U
Adder
6.783
274776LINCOLN ;7U
Adder
6.783
274777LINCOLN ;8U
Adder
6.783
274827FISK ;RP
Adder
8.434
276889AE2-281 GEN
Solar/Wind Harmer
2.08
971411AH1-196 GEN
Solar/Wind Harmer
16.002
971675AH1-338 GEN
Solar/Wind Harmer
19.111
276861AD2-134 GEN
Solar/Wind Harmer
1.894
276863AD2-134 GEN
Solar/Wind Harmer
1.894
971171AH1-044 GEN
Solar/Wind Harmer
20.999
274823ROCKFORD ;21
Adder
20.38
274856ECOGROVE ;U1
Solar/Wind Harmer
3.474
276611AD2-172 GEN
Solar/Wind Harmer
2.635
276612AE2-035 GEN
Solar/Wind Harmer
2.635
971681AH1-341 GEN
Solar/Wind Harmer
15.242
926823AC1-168 GEN
Solar/Wind Harmer
4.328
972267AH1-718 GEN
Adder
4.112
276741O09 GEN1
Solar/Wind Harmer
3.489
274863CRW1-WTG
Solar/Wind Harmer
5.442
274864CRW2-WTG
Solar/Wind Harmer
5.442
274877BISHOP HL;1U
Solar/Wind Harmer
3.185
970169AG2-114 GEN
Solar/Wind Harmer
9.405
946321AF1-296 GEN
Solar/Wind Harmer
9.702
276726Z2-087_GEN
Solar/Wind Harmer
6.552
959341AF2-225 GEN
Solar/Wind Harmer
12.429
274853TWINGROVE;U1
Solar/Wind Harmer
5.677
274854TWINGROVE;U2
Solar/Wind Harmer
5.558
276668AB2-070 GEN1
Solar/Wind Harmer
1.416
276848AB2-070 GEN3
Solar/Wind Harmer
1.416
276849AB2-070 GEN2
Solar/Wind Harmer
1.416
276763AC1-053 GEN1
Solar/Wind Harmer
2.49
276764AC1-053 GEN2
Solar/Wind Harmer
2.49
944221AF1-090 GEN
Solar/Wind Harmer
5.097
991777J1629 G
External Queue
12.460098266601562
990512J1326
External Queue
5.492130756378174
990117J1214
External Queue
18.892929077148438
990727J1377 G
External Queue
6.381270885467529
991092J1477
External Queue
2.951280355453491
991303J1755 G
External Queue
4.770939350128174
990407J1304
External Queue
4.2490010261535645
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.215
NYPJM->LTFIMP_NY
CLTF
0.974
WECLTFEXP_WEC->PJM
CLTF
3.984
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
61.521
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.483
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.848
MECLTFEXP_MEC->PJM
CLTF
12.331
SIGELTFEXP_SIGE->PJM
CLTF
0.007
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.434
LAGNLTFEXP_LAGN->PJM
CLTF
3.906
TVALTFEXP_TVA->PJM
CLTF
0.947

Details for UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.02 %
Rating:2004.0 MVA
Rating Type:B
MVA to Mitigate:2224.77
MW Contribution:
15.24
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE/NIPS
Facility Description:
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.65 %
Rating:2004.0 MVA
Rating Type:B
MVA to Mitigate:2197.32
MW Contribution:
15.05
Bus #Bus NameTypeMW Contribution
274815UNIV PK N;XU
50/50
0.857
274813UNIV PK N;9U
50/50
0.855
274816UNIV PK N;YU
50/50
0.855
274809UNIV PK N;5U
50/50
0.851
274805UNIV PK N;1U
50/50
15.639
274808UNIV PK N;4U
50/50
15.536
274711KENDALL ;4S
50/50
0.925
274709KENDALL ;3S
50/50
0.925
274798UNIV PARK;1U
50/50
0.313
958481AF2-142 GEN
Solar/Wind Harmer
18.76
958491AF2-143 GEN
Solar/Wind Harmer
17.714
276893AG1-478 C
Solar/Wind Harmer
0.512
274674JOLIET 9 ;6U
Adder
17.94
276776AD2-060 GEN
Solar/Wind Harmer
0.484
274888KELLY CRK;1U
Solar/Wind Harmer
6.816
970941AG2-585 GEN
Solar/Wind Harmer
6.353
958011AF2-095 GEN
Solar/Wind Harmer
16.632
276897AD1-100 C
Solar/Wind Harmer
52.937
274683WAUKEGAN ;8U
Adder
23.403
274683WAUKEGAN ;8U
Adder
19.728
274696ROCKY RD ;4P
Adder
12.655
274695ROCKY RD ;2P
Adder
12.364
274693ROCKY RD ;1P
Adder
12.242
274697ROCKY RD ;3P
Adder
3.359
274770LINCOLN ;1U
Adder
6.783
274771LINCOLN ;2U
Adder
6.783
962691AG1-118 GEN
Solar/Wind Harmer
32.752
276901AD2-066 C O1
Solar/Wind Harmer
3.814
960751AF2-366 GEN
Solar/Wind Harmer
3.117
276872AE1-163_GEN1
Solar/Wind Harmer
7.281
276876AE1-163_GEN2
Solar/Wind Harmer
7.281
971341AH1-150 GEN
Solar/Wind Harmer
20.998
971343AH1-151 GEN
Solar/Wind Harmer
20.998
972235AH1-702 GEN1
Adder
2.623
972236AH1-702 GEN2
Adder
2.281
938861AE1-114 GEN
Solar/Wind Harmer
8.329
274764LEE CO EC;5U
Adder
9.406
274765LEE CO EC;6U
Adder
9.406
274762LEE CO EC;3U
Adder
9.384
274763LEE CO EC;4U
Adder
9.296
276158O29GEN2
Solar/Wind Harmer
4.887
276157O29GEN1
Solar/Wind Harmer
3.715
276645AC1-214 GEN1
Solar/Wind Harmer
1.277
942111AE2-223 GEN
Solar/Wind Harmer
6.793
960611AF2-352 GEN
Solar/Wind Harmer
1.833
274880W4-005 GEN4
Solar/Wind Harmer
1.937
276174W4-005 GEN2
Solar/Wind Harmer
1.937
276615X2-022 GEN
Solar/Wind Harmer
1.195
276838X2-022 GEN2
Solar/Wind Harmer
0.142
276916AD2-100_GEN
Solar/Wind Harmer
11.094
276911AD2-131_GEN
Solar/Wind Harmer
2.242
274806UNIV PK N;2U
50/50
0.872
274810UNIV PK N;6U
50/50
0.853
274812UNIV PK N;8U
50/50
15.605
274802UNIV PARK;5U
50/50
10.566
274710KENDALL ;4C
50/50
1.385
274705KENDALL ;1S
50/50
0.887
276694AA1-018 GEN2
Solar/Wind Harmer
7.891
276691AA1-018 GEN1
Solar/Wind Harmer
0.943
274676JOLIET 29;8U
Adder
36.466
276805AD2-038 GEN
Solar/Wind Harmer
6.055
274732ELWOOD EC;7P
Adder
19.39
274674JOLIET 9 ;6U
Adder
17.94
274871GR RIDGE ;2U
Solar/Wind Harmer
8.956
274847GR RIDGE ;BU
Solar/Wind Harmer
5.889
941551AE2-152 GEN
Solar/Wind Harmer
5.168
274745AC1-111 GEN9
Adder
6.327
274682WAUKEGAN ;7U
Adder
20.009
274828WAUKEGAN ;BP
Adder
12.267
972207SS24-0001
Solar/Wind Harmer
24.116
274773LINCOLN ;4U
Adder
6.783
274774LINCOLN ;5U
Adder
6.783
962781AG1-127 GEN
Solar/Wind Harmer
10.333
274872LEEDK;1U
Solar/Wind Harmer
8.878
276882AE2-255 GEN
Solar/Wind Harmer
3.626
971997AH1-543 GEN
Solar/Wind Harmer
16.634
957471AF2-041 GEN
Solar/Wind Harmer
31.498
959081AF2-199 GEN
Solar/Wind Harmer
10.499
971067AG2-660 GEN
Solar/Wind Harmer
2.442
274822ROCKFORD ;11
Adder
20.529
970819AG2-516 GEN
Solar/Wind Harmer
12.413
274861TOP CROP ;1U
Solar/Wind Harmer
6.257
970569AG2-363 GEN
Solar/Wind Harmer
30.534
939401AE1-172 GEN
Solar/Wind Harmer
14.157
274858EASY ROAD;U2
Solar/Wind Harmer
4.832
274761LEE CO EC;2U
Adder
9.384
274766LEE CO EC;7U
Adder
9.273
276708O09 GEN2
Solar/Wind Harmer
3.489
276646AC1-214 GEN2
Solar/Wind Harmer
1.277
274848CAMPGROVE;RU
Solar/Wind Harmer
6.013
276655WTG1_EQ
Solar/Wind Harmer
7.232
276656WTG2_EQ
Solar/Wind Harmer
0.958
939741AE1-205 GEN
Solar/Wind Harmer
16.573
274723RIVER EC ;12
Adder
11.919
276686W4-005 GEN3
Solar/Wind Harmer
1.937
276621W2-048 GEN
Solar/Wind Harmer
3.804
965911AG1-460 GEN
Solar/Wind Harmer
0.762
972037AH1-567 GEN1
50/50
0.332
274655BRAIDWOOD;2U
50/50
4.572
972228AH1-698 GEN2
50/50
4.883
972227AH1-698 GEN1
50/50
3.426
274661LASCO STA;2U
50/50
6.678
274660LASCO STA;1U
50/50
8.626
274708KENDALL ;3C
50/50
1.401
274799UNIV PARK;2U
50/50
0.323
274800UNIV PARK;3U
50/50
7.2
274801UNIV PARK;4U
50/50
7.2
274704KENDALL ;1C
50/50
1.328
274706KENDALL ;2C
50/50
1.328
274675JOLIET 29;7U
Adder
36.487
274675JOLIET 29;7U
Adder
35.183
274731ELWOOD EC;2P
Adder
19.419
274733ELWOOD EC;3P
Adder
19.419
274735ELWOOD EC;4P
Adder
19.419
970073AG2-061 GEN
Solar/Wind Harmer
2.746
274728ELWOOD EC;5P
Adder
19.39
276893AG1-478 C
Solar/Wind Harmer
0.642
970833AG2-524 GEN
Solar/Wind Harmer
10.188
970833AG2-524 GEN
Solar/Wind Harmer
4.739
960591AF2-350 GEN
Solar/Wind Harmer
11.551
274687WILL CNTY;4U
Adder
31.654
274687WILL CNTY;4U
Adder
31.654
274744AC1-111 GEN8
Adder
6.327
274746AC1-111 G10
Adder
6.327
274775LINCOLN ;6U
Adder
6.783
274776LINCOLN ;7U
Adder
6.783
274777LINCOLN ;8U
Adder
6.783
274827FISK ;RP
Adder
8.434
276889AE2-281 GEN
Solar/Wind Harmer
2.08
971411AH1-196 GEN
Solar/Wind Harmer
16.002
971675AH1-338 GEN
Solar/Wind Harmer
19.111
276861AD2-134 GEN
Solar/Wind Harmer
1.894
276863AD2-134 GEN
Solar/Wind Harmer
1.894
971171AH1-044 GEN
Solar/Wind Harmer
20.998
274823ROCKFORD ;21
Adder
20.38
274856ECOGROVE ;U1
Solar/Wind Harmer
3.474
276611AD2-172 GEN
Solar/Wind Harmer
2.635
276612AE2-035 GEN
Solar/Wind Harmer
2.635
971681AH1-341 GEN
Solar/Wind Harmer
15.241
926823AC1-168 GEN
Solar/Wind Harmer
4.328
972267AH1-718 GEN
Adder
4.112
276741O09 GEN1
Solar/Wind Harmer
3.489
274863CRW1-WTG
Solar/Wind Harmer
5.442
274864CRW2-WTG
Solar/Wind Harmer
5.442
274877BISHOP HL;1U
Solar/Wind Harmer
3.185
970169AG2-114 GEN
Solar/Wind Harmer
9.405
946321AF1-296 GEN
Solar/Wind Harmer
9.702
276726Z2-087_GEN
Solar/Wind Harmer
6.552
959341AF2-225 GEN
Solar/Wind Harmer
12.429
274853TWINGROVE;U1
Solar/Wind Harmer
5.678
274854TWINGROVE;U2
Solar/Wind Harmer
5.559
276668AB2-070 GEN1
Solar/Wind Harmer
1.416
276848AB2-070 GEN3
Solar/Wind Harmer
1.416
276849AB2-070 GEN2
Solar/Wind Harmer
1.416
276763AC1-053 GEN1
Solar/Wind Harmer
2.49
276764AC1-053 GEN2
Solar/Wind Harmer
2.49
944221AF1-090 GEN
Solar/Wind Harmer
5.097
274814UNIV PK N;0U
50/50
15.741
274807UNIV PK N;3U
50/50
15.707
274811UNIV PK N;7U
50/50
15.605
274803UNIV PARK;6U
50/50
10.566
274654BRAIDWOOD;1U
50/50
4.693
972259AH1-714 GEN
50/50
24.288
972038AH1-567 GEN2
50/50
0.451
274707KENDALL ;2S
50/50
0.887
274676JOLIET 29;8U
Adder
35.164
274729ELWOOD EC;1P
Adder
19.419
274730ELWOOD EC;6P
Adder
19.39
274734ELWOOD EC;8P
Adder
19.39
274736ELWOOD EC;9P
Adder
19.39
970707AG2-453 GEN
Solar/Wind Harmer
32.698
276772AC2-154 GEN
Solar/Wind Harmer
3.224
276806AD2-047 C O1
Solar/Wind Harmer
12.358
274887GEN-1.85
Solar/Wind Harmer
6.154
276843GEN-1.7
Solar/Wind Harmer
0.662
939351AE1-166 GEN
Solar/Wind Harmer
6.758
943121AE2-341 GEN
Solar/Wind Harmer
16.939
943591AF1-030 GEN
Solar/Wind Harmer
11.292
274682WAUKEGAN ;7U
Adder
20.009
274772LINCOLN ;3U
Adder
6.783
274826FISK ;BP
Adder
11.9
276868AE1-113 GEN
Solar/Wind Harmer
10.876
274879MINONK ;1U
Solar/Wind Harmer
7.251
276799AD1-013 GEN
Solar/Wind Harmer
2.348
946671AF1-331 GEN
Solar/Wind Harmer
0.445
274855GSG-6 ;RU
Solar/Wind Harmer
3.917
274850MENDOTA H;RU
Solar/Wind Harmer
2.724
276602WESTBROOK C
Solar/Wind Harmer
2.255
959091AF2-200 GEN
Solar/Wind Harmer
20.998
274862TOP CROP ;2U
Solar/Wind Harmer
5.225
970571AG2-364 GEN
Solar/Wind Harmer
20.356
274857EASY ROAD;U1
Solar/Wind Harmer
4.832
274760LEE CO EC;1U
Adder
9.384
274767LEE CO EC;8U
Adder
9.273
276603SUBLETTE C
Solar/Wind Harmer
1.053
274851PROVIDENC;RU
Solar/Wind Harmer
2.714
274849CRESCENT ;1U
Solar/Wind Harmer
1.762
276782AC1-033 GEN
Solar/Wind Harmer
3.765
274878BISHOP HL;2U
Solar/Wind Harmer
3.185
965931AG1-462 GEN
Solar/Wind Harmer
23.442
971087AG2-675 GEN
Solar/Wind Harmer
3.421
276164X3-005 C
Solar/Wind Harmer
0.611
965091AG1-374 GEN
Solar/Wind Harmer
23.641
959611AF2-252 GEN
Solar/Wind Harmer
1.833
274724RIVER EC ;11
Adder
11.579
276785W4-005 GEN1
Solar/Wind Harmer
1.937
971993AH1-541 GEN
Solar/Wind Harmer
5.919
957381AF2-032 GEN
Solar/Wind Harmer
1.106
942481AE2-261 GEN
Solar/Wind Harmer
16.335
991777J1629 G
External Queue
12.45987319946289
990512J1326
External Queue
5.492026329040527
990117J1214
External Queue
18.89257049560547
990727J1377 G
External Queue
6.381145477294922
991092J1477
External Queue
2.95123553276062
991303J1755 G
External Queue
4.770899295806885
990407J1304
External Queue
4.248918056488037
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.215
NYPJM->LTFIMP_NY
CLTF
0.974
WECLTFEXP_WEC->PJM
CLTF
3.984
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
61.52
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.483
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.848
MECLTFEXP_MEC->PJM
CLTF
12.331
SIGELTFEXP_SIGE->PJM
CLTF
0.007
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.5
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.434
LAGNLTFEXP_LAGN->PJM
CLTF
3.906
TVALTFEXP_TVA->PJM
CLTF
0.947

Details for UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.33 %
Rating:2004.0 MVA
Rating Type:B
MVA to Mitigate:2210.98
MW Contribution:
15.14
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE/NIPS
Facility Description:
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.13 %
Rating:2004.0 MVA
Rating Type:B
MVA to Mitigate:2186.94
MW Contribution:
14.97
Bus #Bus NameTypeMW Contribution
274814UNIV PK N;0U
50/50
15.701
274807UNIV PK N;3U
50/50
15.667
274811UNIV PK N;7U
50/50
15.564
274803UNIV PARK;6U
50/50
10.521
274654BRAIDWOOD;1U
50/50
4.666
972259AH1-714 GEN
50/50
24.138
972038AH1-567 GEN2
50/50
0.448
274707KENDALL ;2S
50/50
0.882
274676JOLIET 29;8U
Adder
34.949
274729ELWOOD EC;1P
Adder
19.301
274730ELWOOD EC;6P
Adder
19.272
274734ELWOOD EC;8P
Adder
19.272
274736ELWOOD EC;9P
Adder
19.272
970707AG2-453 GEN
Solar/Wind Harmer
32.478
276772AC2-154 GEN
Solar/Wind Harmer
3.204
276806AD2-047 C O1
Solar/Wind Harmer
12.282
274887GEN-1.85
Solar/Wind Harmer
6.116
276843GEN-1.7
Solar/Wind Harmer
0.658
939351AE1-166 GEN
Solar/Wind Harmer
6.72
943121AE2-341 GEN
Solar/Wind Harmer
16.826
943591AF1-030 GEN
Solar/Wind Harmer
11.218
274682WAUKEGAN ;7U
Adder
19.882
274772LINCOLN ;3U
Adder
6.749
274826FISK ;BP
Adder
11.82
276868AE1-113 GEN
Solar/Wind Harmer
10.809
274879MINONK ;1U
Solar/Wind Harmer
7.206
276799AD1-013 GEN
Solar/Wind Harmer
2.332
946671AF1-331 GEN
Solar/Wind Harmer
0.442
274855GSG-6 ;RU
Solar/Wind Harmer
3.892
274850MENDOTA H;RU
Solar/Wind Harmer
2.706
276602WESTBROOK C
Solar/Wind Harmer
2.24
959091AF2-200 GEN
Solar/Wind Harmer
20.862
274862TOP CROP ;2U
Solar/Wind Harmer
5.19
970571AG2-364 GEN
Solar/Wind Harmer
20.23
274857EASY ROAD;U1
Solar/Wind Harmer
4.801
274760LEE CO EC;1U
Adder
9.323
274767LEE CO EC;8U
Adder
9.214
276603SUBLETTE C
Solar/Wind Harmer
1.046
274851PROVIDENC;RU
Solar/Wind Harmer
2.697
274849CRESCENT ;1U
Solar/Wind Harmer
1.751
276782AC1-033 GEN
Solar/Wind Harmer
3.741
274878BISHOP HL;2U
Solar/Wind Harmer
3.165
965931AG1-462 GEN
Solar/Wind Harmer
23.291
971087AG2-675 GEN
Solar/Wind Harmer
3.399
276164X3-005 C
Solar/Wind Harmer
0.606
965091AG1-374 GEN
Solar/Wind Harmer
23.492
959611AF2-252 GEN
Solar/Wind Harmer
1.821
274724RIVER EC ;11
Adder
11.443
276785W4-005 GEN1
Solar/Wind Harmer
1.924
971993AH1-541 GEN
Solar/Wind Harmer
5.88
957381AF2-032 GEN
Solar/Wind Harmer
1.099
942481AE2-261 GEN
Solar/Wind Harmer
16.226
274806UNIV PK N;2U
50/50
0.87
274810UNIV PK N;6U
50/50
0.851
274812UNIV PK N;8U
50/50
15.564
274802UNIV PARK;5U
50/50
10.521
274710KENDALL ;4C
50/50
1.376
274705KENDALL ;1S
50/50
0.882
276694AA1-018 GEN2
Solar/Wind Harmer
7.848
276691AA1-018 GEN1
Solar/Wind Harmer
0.938
274676JOLIET 29;8U
Adder
36.243
276805AD2-038 GEN
Solar/Wind Harmer
6.021
274732ELWOOD EC;7P
Adder
19.272
274674JOLIET 9 ;6U
Adder
17.828
274871GR RIDGE ;2U
Solar/Wind Harmer
8.9
274847GR RIDGE ;BU
Solar/Wind Harmer
5.852
941551AE2-152 GEN
Solar/Wind Harmer
5.139
274745AC1-111 GEN9
Adder
6.286
274682WAUKEGAN ;7U
Adder
19.882
274828WAUKEGAN ;BP
Adder
12.189
972207SS24-0001
Solar/Wind Harmer
23.996
274773LINCOLN ;4U
Adder
6.749
274774LINCOLN ;5U
Adder
6.749
962781AG1-127 GEN
Solar/Wind Harmer
10.266
274872LEEDK;1U
Solar/Wind Harmer
8.82
276882AE2-255 GEN
Solar/Wind Harmer
3.603
971997AH1-543 GEN
Solar/Wind Harmer
16.528
957471AF2-041 GEN
Solar/Wind Harmer
31.294
959081AF2-199 GEN
Solar/Wind Harmer
10.431
971067AG2-660 GEN
Solar/Wind Harmer
2.426
274822ROCKFORD ;11
Adder
20.396
970819AG2-516 GEN
Solar/Wind Harmer
12.333
274861TOP CROP ;1U
Solar/Wind Harmer
6.216
970569AG2-363 GEN
Solar/Wind Harmer
30.345
939401AE1-172 GEN
Solar/Wind Harmer
14.074
274858EASY ROAD;U2
Solar/Wind Harmer
4.801
274761LEE CO EC;2U
Adder
9.323
274766LEE CO EC;7U
Adder
9.214
276708O09 GEN2
Solar/Wind Harmer
3.467
276646AC1-214 GEN2
Solar/Wind Harmer
1.268
972037AH1-567 GEN1
50/50
0.33
274655BRAIDWOOD;2U
50/50
4.546
972228AH1-698 GEN2
50/50
4.855
972227AH1-698 GEN1
50/50
3.406
274661LASCO STA;2U
50/50
6.637
274660LASCO STA;1U
50/50
8.573
274708KENDALL ;3C
50/50
1.392
274799UNIV PARK;2U
50/50
0.321
274800UNIV PARK;3U
50/50
7.155
274801UNIV PARK;4U
50/50
7.155
274815UNIV PK N;XU
50/50
0.855
274813UNIV PK N;9U
50/50
0.853
274816UNIV PK N;YU
50/50
0.853
274809UNIV PK N;5U
50/50
0.849
274805UNIV PK N;1U
50/50
15.599
274808UNIV PK N;4U
50/50
15.496
274711KENDALL ;4S
50/50
0.92
274709KENDALL ;3S
50/50
0.92
274798UNIV PARK;1U
50/50
0.311
958481AF2-142 GEN
Solar/Wind Harmer
18.657
958491AF2-143 GEN
Solar/Wind Harmer
17.613
276893AG1-478 C
Solar/Wind Harmer
0.508
274674JOLIET 9 ;6U
Adder
17.828
276776AD2-060 GEN
Solar/Wind Harmer
0.481
274888KELLY CRK;1U
Solar/Wind Harmer
6.774
970941AG2-585 GEN
Solar/Wind Harmer
6.314
958011AF2-095 GEN
Solar/Wind Harmer
16.53
276897AD1-100 C
Solar/Wind Harmer
52.635
274683WAUKEGAN ;8U
Adder
23.254
274683WAUKEGAN ;8U
Adder
19.602
274695ROCKY RD ;2P
Adder
12.284
274693ROCKY RD ;1P
Adder
12.163
274697ROCKY RD ;3P
Adder
3.337
274696ROCKY RD ;4P
Adder
12.573
274770LINCOLN ;1U
Adder
6.749
274771LINCOLN ;2U
Adder
6.749
962691AG1-118 GEN
Solar/Wind Harmer
32.538
276901AD2-066 C O1
Solar/Wind Harmer
3.79
960751AF2-366 GEN
Solar/Wind Harmer
3.097
276872AE1-163_GEN1
Solar/Wind Harmer
7.237
276876AE1-163_GEN2
Solar/Wind Harmer
7.237
971341AH1-150 GEN
Solar/Wind Harmer
20.862
971343AH1-151 GEN
Solar/Wind Harmer
20.862
972235AH1-702 GEN1
Adder
2.606
972236AH1-702 GEN2
Adder
2.266
938861AE1-114 GEN
Solar/Wind Harmer
8.275
274764LEE CO EC;5U
Adder
9.345
274765LEE CO EC;6U
Adder
9.345
274762LEE CO EC;3U
Adder
9.323
274763LEE CO EC;4U
Adder
9.236
276158O29GEN2
Solar/Wind Harmer
4.855
276157O29GEN1
Solar/Wind Harmer
3.691
276645AC1-214 GEN1
Solar/Wind Harmer
1.268
942111AE2-223 GEN
Solar/Wind Harmer
6.75
960611AF2-352 GEN
Solar/Wind Harmer
1.821
274880W4-005 GEN4
Solar/Wind Harmer
1.924
276174W4-005 GEN2
Solar/Wind Harmer
1.924
276615X2-022 GEN
Solar/Wind Harmer
1.187
276838X2-022 GEN2
Solar/Wind Harmer
0.141
276916AD2-100_GEN
Solar/Wind Harmer
11.019
276911AD2-131_GEN
Solar/Wind Harmer
2.227
274704KENDALL ;1C
50/50
1.319
274706KENDALL ;2C
50/50
1.319
274675JOLIET 29;7U
Adder
36.264
274675JOLIET 29;7U
Adder
34.969
274731ELWOOD EC;2P
Adder
19.301
274733ELWOOD EC;3P
Adder
19.301
274735ELWOOD EC;4P
Adder
19.301
970073AG2-061 GEN
Solar/Wind Harmer
2.731
274728ELWOOD EC;5P
Adder
19.272
276893AG1-478 C
Solar/Wind Harmer
0.638
970833AG2-524 GEN
Solar/Wind Harmer
10.125
970833AG2-524 GEN
Solar/Wind Harmer
4.709
960591AF2-350 GEN
Solar/Wind Harmer
11.48
274687WILL CNTY;4U
Adder
31.452
274687WILL CNTY;4U
Adder
31.452
274744AC1-111 GEN8
Adder
6.286
274746AC1-111 G10
Adder
6.286
274775LINCOLN ;6U
Adder
6.749
274776LINCOLN ;7U
Adder
6.749
274777LINCOLN ;8U
Adder
6.749
274827FISK ;RP
Adder
8.377
276889AE2-281 GEN
Solar/Wind Harmer
2.068
971411AH1-196 GEN
Solar/Wind Harmer
15.899
971675AH1-338 GEN
Solar/Wind Harmer
18.986
276861AD2-134 GEN
Solar/Wind Harmer
1.882
276863AD2-134 GEN
Solar/Wind Harmer
1.882
971171AH1-044 GEN
Solar/Wind Harmer
20.862
274823ROCKFORD ;21
Adder
20.248
274856ECOGROVE ;U1
Solar/Wind Harmer
3.452
276611AD2-172 GEN
Solar/Wind Harmer
2.618
276612AE2-035 GEN
Solar/Wind Harmer
2.618
971681AH1-341 GEN
Solar/Wind Harmer
15.143
926823AC1-168 GEN
Solar/Wind Harmer
4.301
972267AH1-718 GEN
Adder
4.086
276741O09 GEN1
Solar/Wind Harmer
3.467
274863CRW1-WTG
Solar/Wind Harmer
5.41
274864CRW2-WTG
Solar/Wind Harmer
5.41
274877BISHOP HL;1U
Solar/Wind Harmer
3.165
970169AG2-114 GEN
Solar/Wind Harmer
9.346
946321AF1-296 GEN
Solar/Wind Harmer
9.64
276726Z2-087_GEN
Solar/Wind Harmer
6.511
959341AF2-225 GEN
Solar/Wind Harmer
12.352
274853TWINGROVE;U1
Solar/Wind Harmer
5.642
274854TWINGROVE;U2
Solar/Wind Harmer
5.523
276668AB2-070 GEN1
Solar/Wind Harmer
1.406
276848AB2-070 GEN3
Solar/Wind Harmer
1.406
276849AB2-070 GEN2
Solar/Wind Harmer
1.406
276763AC1-053 GEN1
Solar/Wind Harmer
2.474
276764AC1-053 GEN2
Solar/Wind Harmer
2.474
944221AF1-090 GEN
Solar/Wind Harmer
5.062
274848CAMPGROVE;RU
Solar/Wind Harmer
5.975
276655WTG1_EQ
Solar/Wind Harmer
7.187
276656WTG2_EQ
Solar/Wind Harmer
0.952
939741AE1-205 GEN
Solar/Wind Harmer
16.469
274723RIVER EC ;12
Adder
11.782
276686W4-005 GEN3
Solar/Wind Harmer
1.924
276621W2-048 GEN
Solar/Wind Harmer
3.779
965911AG1-460 GEN
Solar/Wind Harmer
0.757
991777J1629 G
External Queue
12.406346321105957
990512J1326
External Queue
5.468172073364258
990117J1214
External Queue
18.810510635375977
990727J1377 G
External Queue
6.353004455566406
991092J1477
External Queue
2.9398884773254395
991303J1755 G
External Queue
4.751594543457031
990407J1304
External Queue
4.230135917663574
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.212
NYPJM->LTFIMP_NY
CLTF
0.966
WECLTFEXP_WEC->PJM
CLTF
3.958
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.421
CBM West 1LTFEXP_CBM-W1->PJM
CBM
60.862
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.654
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.471
MECLTFEXP_MEC->PJM
CLTF
12.252
SIGELTFEXP_SIGE->PJM
CLTF
0.007
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.496
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.422
LAGNLTFEXP_LAGN->PJM
CLTF
3.882
TVALTFEXP_TVA->PJM
CLTF
0.942

Details for UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE/NIPS
Facility Description:
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.39 %
Rating:2004.0 MVA
Rating Type:B
MVA to Mitigate:2192.13
MW Contribution:
15.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:CE/NIPS
Facility Description:
UNIV PK N;RP-17P9701-WEST 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.62 %
Rating:2004.0 MVA
Rating Type:B
MVA to Mitigate:2196.77
MW Contribution:
14.97
Bus #Bus NameTypeMW Contribution
274815UNIV PK N;XU
50/50
0.851
274813UNIV PK N;9U
50/50
0.849
274816UNIV PK N;YU
50/50
0.849
274809UNIV PK N;5U
50/50
0.846
274805UNIV PK N;1U
50/50
15.534
274808UNIV PK N;4U
50/50
15.432
274711KENDALL ;4S
50/50
0.912
274709KENDALL ;3S
50/50
0.912
274798UNIV PARK;1U
50/50
0.308
958481AF2-142 GEN
Solar/Wind Harmer
18.513
958491AF2-143 GEN
Solar/Wind Harmer
17.477
276893AG1-478 C
Solar/Wind Harmer
0.504
274674JOLIET 9 ;6U
Adder
17.67
276776AD2-060 GEN
Solar/Wind Harmer
0.476
274888KELLY CRK;1U
Solar/Wind Harmer
6.71
970941AG2-585 GEN
Solar/Wind Harmer
6.254
958011AF2-095 GEN
Solar/Wind Harmer
16.373
276897AD1-100 C
Solar/Wind Harmer
52.171
274683WAUKEGAN ;8U
Adder
23.056
274683WAUKEGAN ;8U
Adder
19.435
274695ROCKY RD ;2P
Adder
12.18
274693ROCKY RD ;1P
Adder
12.06
274697ROCKY RD ;3P
Adder
3.309
274696ROCKY RD ;4P
Adder
12.466
274770LINCOLN ;1U
Adder
6.684
274771LINCOLN ;2U
Adder
6.684
962691AG1-118 GEN
Solar/Wind Harmer
32.266
276901AD2-066 C O1
Solar/Wind Harmer
3.76
960751AF2-366 GEN
Solar/Wind Harmer
3.071
276872AE1-163_GEN1
Solar/Wind Harmer
7.181
276876AE1-163_GEN2
Solar/Wind Harmer
7.181
971341AH1-150 GEN
Solar/Wind Harmer
20.693
971343AH1-151 GEN
Solar/Wind Harmer
20.693
972235AH1-702 GEN1
Adder
2.585
972236AH1-702 GEN2
Adder
2.248
938861AE1-114 GEN
Solar/Wind Harmer
8.21
274764LEE CO EC;5U
Adder
9.272
274765LEE CO EC;6U
Adder
9.272
274762LEE CO EC;3U
Adder
9.25
274763LEE CO EC;4U
Adder
9.163
276158O29GEN2
Solar/Wind Harmer
4.819
276157O29GEN1
Solar/Wind Harmer
3.664
276645AC1-214 GEN1
Solar/Wind Harmer
1.259
942111AE2-223 GEN
Solar/Wind Harmer
6.71
960611AF2-352 GEN
Solar/Wind Harmer
1.811
274880W4-005 GEN4
Solar/Wind Harmer
1.919
276174W4-005 GEN2
Solar/Wind Harmer
1.919
276615X2-022 GEN
Solar/Wind Harmer
1.184
276838X2-022 GEN2
Solar/Wind Harmer
0.141
276916AD2-100_GEN
Solar/Wind Harmer
11.018
276911AD2-131_GEN
Solar/Wind Harmer
2.227
274814UNIV PK N;0U
50/50
15.636
274807UNIV PK N;3U
50/50
15.602
274811UNIV PK N;7U
50/50
15.5
274803UNIV PARK;6U
50/50
10.451
274654BRAIDWOOD;1U
50/50
4.626
972259AH1-714 GEN
50/50
23.93
972038AH1-567 GEN2
50/50
0.444
274707KENDALL ;2S
50/50
0.874
274676JOLIET 29;8U
Adder
34.64
274729ELWOOD EC;1P
Adder
19.132
274730ELWOOD EC;6P
Adder
19.103
274734ELWOOD EC;8P
Adder
19.103
274736ELWOOD EC;9P
Adder
19.103
970707AG2-453 GEN
Solar/Wind Harmer
32.196
276772AC2-154 GEN
Solar/Wind Harmer
3.174
276806AD2-047 C O1
Solar/Wind Harmer
12.166
274887GEN-1.85
Solar/Wind Harmer
6.058
276843GEN-1.7
Solar/Wind Harmer
0.652
939351AE1-166 GEN
Solar/Wind Harmer
6.66
943121AE2-341 GEN
Solar/Wind Harmer
16.682
943591AF1-030 GEN
Solar/Wind Harmer
11.121
274682WAUKEGAN ;7U
Adder
19.712
274772LINCOLN ;3U
Adder
6.684
274826FISK ;BP
Adder
11.697
276868AE1-113 GEN
Solar/Wind Harmer
10.72
274879MINONK ;1U
Solar/Wind Harmer
7.147
276799AD1-013 GEN
Solar/Wind Harmer
2.313
946671AF1-331 GEN
Solar/Wind Harmer
0.438
274855GSG-6 ;RU
Solar/Wind Harmer
3.86
274850MENDOTA H;RU
Solar/Wind Harmer
2.684
276602WESTBROOK C
Solar/Wind Harmer
2.222
959091AF2-200 GEN
Solar/Wind Harmer
20.693
274862TOP CROP ;2U
Solar/Wind Harmer
5.141
970571AG2-364 GEN
Solar/Wind Harmer
20.073
274857EASY ROAD;U1
Solar/Wind Harmer
4.763
274760LEE CO EC;1U
Adder
9.25
274767LEE CO EC;8U
Adder
9.141
276603SUBLETTE C
Solar/Wind Harmer
1.038
274851PROVIDENC;RU
Solar/Wind Harmer
2.678
274849CRESCENT ;1U
Solar/Wind Harmer
1.738
276782AC1-033 GEN
Solar/Wind Harmer
3.714
274878BISHOP HL;2U
Solar/Wind Harmer
3.142
965931AG1-462 GEN
Solar/Wind Harmer
23.125
971087AG2-675 GEN
Solar/Wind Harmer
3.374
276164X3-005 C
Solar/Wind Harmer
0.598
965091AG1-374 GEN
Solar/Wind Harmer
23.365
959611AF2-252 GEN
Solar/Wind Harmer
1.811
276785W4-005 GEN1
Solar/Wind Harmer
1.919
971993AH1-541 GEN
Solar/Wind Harmer
5.863
274724RIVER EC ;11
Adder
11.22
957381AF2-032 GEN
Solar/Wind Harmer
1.098
942481AE2-261 GEN
Solar/Wind Harmer
16.215
274806UNIV PK N;2U
50/50
0.866
274810UNIV PK N;6U
50/50
0.848
274812UNIV PK N;8U
50/50
15.5
274802UNIV PARK;5U
50/50
10.451
274710KENDALL ;4C
50/50
1.364
274705KENDALL ;1S
50/50
0.874
276694AA1-018 GEN2
Solar/Wind Harmer
7.787
276691AA1-018 GEN1
Solar/Wind Harmer
0.931
274676JOLIET 29;8U
Adder
35.923
276805AD2-038 GEN
Solar/Wind Harmer
5.975
274732ELWOOD EC;7P
Adder
19.103
274871GR RIDGE ;2U
Solar/Wind Harmer
8.825
274847GR RIDGE ;BU
Solar/Wind Harmer
5.803
274674JOLIET 9 ;6U
Adder
17.67
941551AE2-152 GEN
Solar/Wind Harmer
5.094
274745AC1-111 GEN9
Adder
6.232
274682WAUKEGAN ;7U
Adder
19.712
274828WAUKEGAN ;BP
Adder
12.085
972207SS24-0001
Solar/Wind Harmer
23.766
274773LINCOLN ;4U
Adder
6.684
274774LINCOLN ;5U
Adder
6.684
962781AG1-127 GEN
Solar/Wind Harmer
10.18
274872LEEDK;1U
Solar/Wind Harmer
8.747
276882AE2-255 GEN
Solar/Wind Harmer
3.573
971997AH1-543 GEN
Solar/Wind Harmer
16.395
957471AF2-041 GEN
Solar/Wind Harmer
31.04
959081AF2-199 GEN
Solar/Wind Harmer
10.347
971067AG2-660 GEN
Solar/Wind Harmer
2.406
274822ROCKFORD ;11
Adder
20.231
970819AG2-516 GEN
Solar/Wind Harmer
12.234
274861TOP CROP ;1U
Solar/Wind Harmer
6.158
970569AG2-363 GEN
Solar/Wind Harmer
30.109
939401AE1-172 GEN
Solar/Wind Harmer
13.962
274858EASY ROAD;U2
Solar/Wind Harmer
4.763
274761LEE CO EC;2U
Adder
9.25
274766LEE CO EC;7U
Adder
9.141
276708O09 GEN2
Solar/Wind Harmer
3.44
276646AC1-214 GEN2
Solar/Wind Harmer
1.259
274848CAMPGROVE;RU
Solar/Wind Harmer
5.933
276655WTG1_EQ
Solar/Wind Harmer
7.144
276656WTG2_EQ
Solar/Wind Harmer
0.946
939741AE1-205 GEN
Solar/Wind Harmer
16.371
274723RIVER EC ;12
Adder
11.557
276686W4-005 GEN3
Solar/Wind Harmer
1.919
276621W2-048 GEN
Solar/Wind Harmer
3.771
965911AG1-460 GEN
Solar/Wind Harmer
0.757
972037AH1-567 GEN1
50/50
0.328
274655BRAIDWOOD;2U
50/50
4.507
972228AH1-698 GEN2
50/50
4.814
972227AH1-698 GEN1
50/50
3.377
274661LASCO STA;2U
50/50
6.579
274660LASCO STA;1U
50/50
8.499
274708KENDALL ;3C
50/50
1.38
274799UNIV PARK;2U
50/50
0.318
274800UNIV PARK;3U
50/50
7.086
274801UNIV PARK;4U
50/50
7.086
274704KENDALL ;1C
50/50
1.308
274706KENDALL ;2C
50/50
1.308
274675JOLIET 29;7U
Adder
35.943
274675JOLIET 29;7U
Adder
34.659
970073AG2-061 GEN
Solar/Wind Harmer
2.71
274731ELWOOD EC;2P
Adder
19.132
274733ELWOOD EC;3P
Adder
19.132
274735ELWOOD EC;4P
Adder
19.132
274728ELWOOD EC;5P
Adder
19.103
970833AG2-524 GEN
Solar/Wind Harmer
10.039
970833AG2-524 GEN
Solar/Wind Harmer
4.669
276893AG1-478 C
Solar/Wind Harmer
0.632
960591AF2-350 GEN
Solar/Wind Harmer
11.371
274744AC1-111 GEN8
Adder
6.232
274746AC1-111 G10
Adder
6.232
274687WILL CNTY;4U
Adder
31.156
274687WILL CNTY;4U
Adder
31.156
274775LINCOLN ;6U
Adder
6.684
274776LINCOLN ;7U
Adder
6.684
274777LINCOLN ;8U
Adder
6.684
276889AE2-281 GEN
Solar/Wind Harmer
2.052
274827FISK ;RP
Adder
8.29
971411AH1-196 GEN
Solar/Wind Harmer
15.768
971675AH1-338 GEN
Solar/Wind Harmer
18.831
276861AD2-134 GEN
Solar/Wind Harmer
1.867
276863AD2-134 GEN
Solar/Wind Harmer
1.867
971171AH1-044 GEN
Solar/Wind Harmer
20.693
274823ROCKFORD ;21
Adder
20.084
274856ECOGROVE ;U1
Solar/Wind Harmer
3.424
276611AD2-172 GEN
Solar/Wind Harmer
2.597
276612AE2-035 GEN
Solar/Wind Harmer
2.597
971681AH1-341 GEN
Solar/Wind Harmer
15.024
926823AC1-168 GEN
Solar/Wind Harmer
4.269
972267AH1-718 GEN
Adder
4.054
276741O09 GEN1
Solar/Wind Harmer
3.44
274863CRW1-WTG
Solar/Wind Harmer
5.368
274864CRW2-WTG
Solar/Wind Harmer
5.368
274877BISHOP HL;1U
Solar/Wind Harmer
3.142
970169AG2-114 GEN
Solar/Wind Harmer
9.28
946321AF1-296 GEN
Solar/Wind Harmer
9.57
276726Z2-087_GEN
Solar/Wind Harmer
6.472
959341AF2-225 GEN
Solar/Wind Harmer
12.278
274853TWINGROVE;U1
Solar/Wind Harmer
5.611
274854TWINGROVE;U2
Solar/Wind Harmer
5.494
276668AB2-070 GEN1
Solar/Wind Harmer
1.402
276848AB2-070 GEN3
Solar/Wind Harmer
1.402
276849AB2-070 GEN2
Solar/Wind Harmer
1.402
276763AC1-053 GEN1
Solar/Wind Harmer
2.467
276764AC1-053 GEN2
Solar/Wind Harmer
2.467
944221AF1-090 GEN
Solar/Wind Harmer
5.073
960681AF2-359 GEN
Solar/Wind Helper
0.721
991777J1629 G
External Queue
12.362510681152344
990512J1326
External Queue
5.448331832885742
990117J1214
External Queue
18.742259979248047
990727J1377 G
External Queue
6.328101634979248
991092J1477
External Queue
2.9374141693115234
991303J1755 G
External Queue
4.739677429199219
990407J1304
External Queue
4.213100910186768
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.197
NYPJM->LTFIMP_NY
CLTF
0.955
WECLTFEXP_WEC->PJM
CLTF
3.926
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.397
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.449
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.643
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.088
MECLTFEXP_MEC->PJM
CLTF
12.185
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.436
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.242
LAGNLTFEXP_LAGN->PJM
CLTF
3.934
TVALTFEXP_TVA->PJM
CLTF
0.98

Details for WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.6 %
Rating:381.0 MVA
Rating Type:ALDR
MVA to Mitigate:406.13
MW Contribution:
10.24
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.55 %
Rating:381.0 MVA
Rating Type:ALDR
MVA to Mitigate:405.95
MW Contribution:
10.23
Bus #Bus NameTypeMW Contribution
276799AD1-013 GEN
Solar/Wind Harmer
5.975
946671AF1-331 GEN
Solar/Wind Harmer
1.132
274855GSG-6 ;RU
Solar/Wind Harmer
9.78
274850MENDOTA H;RU
Solar/Wind Harmer
6.8
276602WESTBROOK C
Solar/Wind Harmer
5.63
276603SUBLETTE C
Solar/Wind Harmer
0.775
959091AF2-200 GEN
Solar/Wind Harmer
7.325
274760LEE CO EC;1U
Adder
3.171
274767LEE CO EC;8U
Adder
3.133
962691AG1-118 GEN
Solar/Wind Harmer
104.958
960751AF2-366 GEN
Solar/Wind Harmer
9.559
938861AE1-114 GEN
Solar/Wind Harmer
4.684
971341AH1-150 GEN
Solar/Wind Harmer
7.325
971343AH1-151 GEN
Solar/Wind Harmer
7.325
274764LEE CO EC;5U
Adder
3.178
274765LEE CO EC;6U
Adder
3.178
274762LEE CO EC;3U
Adder
3.171
274763LEE CO EC;4U
Adder
3.141
971675AH1-338 GEN
Solar/Wind Harmer
48.126
276861AD2-134 GEN
Solar/Wind Harmer
4.729
276863AD2-134 GEN
Solar/Wind Harmer
4.729
971681AH1-341 GEN
Solar/Wind Harmer
10.245
274856ECOGROVE ;U1
Solar/Wind Harmer
1.577
276611AD2-172 GEN
Solar/Wind Harmer
1.196
276612AE2-035 GEN
Solar/Wind Harmer
1.196
971171AH1-044 GEN
Solar/Wind Harmer
7.325
274872LEEDK;1U
Solar/Wind Harmer
27.376
962781AG1-127 GEN
Solar/Wind Harmer
31.685
957471AF2-041 GEN
Solar/Wind Harmer
10.988
959081AF2-199 GEN
Solar/Wind Harmer
3.663
971067AG2-660 GEN
Solar/Wind Harmer
0.852
274761LEE CO EC;2U
Adder
3.171
274766LEE CO EC;7U
Adder
3.133
NYPJM->LTFIMP_NY
CLTF
0.073
WECLTFEXP_WEC->PJM
CLTF
0.427
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.007
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.603
MECLTFEXP_MEC->PJM
CLTF
2.739
SIGELTFEXP_SIGE->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.206
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.108
LAGNLTFEXP_LAGN->PJM
CLTF
0.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.049
TVALTFEXP_TVA->PJM
CLTF
0.205

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:125.66 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:5604.3
MW Contribution:
40.0
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:121.77 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:5431.09
MW Contribution:
38.9
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
23.785
274774LINCOLN ;5U
50/50
23.785
274710KENDALL ;4C
50/50
3.594
274705KENDALL ;1S
50/50
2.233
972207SS24-0001
Solar/Wind Harmer
79.696
941551AE2-152 GEN
Solar/Wind Harmer
13.765
274871GR RIDGE ;2U
Solar/Wind Harmer
23.136
274847GR RIDGE ;BU
Solar/Wind Harmer
15.212
274745AC1-111 GEN9
Adder
16.783
274676JOLIET 29;8U
Adder
89.061
274732ELWOOD EC;7P
Adder
47.507
962781AG1-127 GEN
Solar/Wind Harmer
27.442
274872LEEDK;1U
Solar/Wind Harmer
23.583
274674JOLIET 9 ;6U
Adder
44.223
274682WAUKEGAN ;7U
Adder
51.601
274751CRETE EC ;1U
Adder
14.031
274754CRETE EC ;4U
Adder
14.031
274828WAUKEGAN ;BP
Adder
31.644
274812UNIV PK N;8U
Adder
14.317
939401AE1-172 GEN
Solar/Wind Harmer
38.947
274802UNIV PARK;5U
Adder
16.231
957471AF2-041 GEN
Solar/Wind Harmer
82.983
959081AF2-199 GEN
Solar/Wind Harmer
27.661
971067AG2-660 GEN
Solar/Wind Harmer
6.433
971997AH1-543 GEN
Solar/Wind Harmer
43.252
274822ROCKFORD ;11
Adder
53.804
274861TOP CROP ;1U
Solar/Wind Harmer
16.513
276694AA1-018 GEN2
Solar/Wind Harmer
17.192
276691AA1-018 GEN1
Solar/Wind Harmer
2.055
970819AG2-516 GEN
Solar/Wind Harmer
32.522
276882AE2-255 GEN
Solar/Wind Harmer
9.076
276805AD2-038 GEN
Solar/Wind Harmer
13.7
274858EASY ROAD;U2
Solar/Wind Harmer
12.673
274761LEE CO EC;2U
Adder
24.611
274766LEE CO EC;7U
Adder
24.321
276708O09 GEN2
Solar/Wind Harmer
9.117
274770LINCOLN ;1U
50/50
23.785
274771LINCOLN ;2U
50/50
23.785
274711KENDALL ;4S
50/50
2.402
274709KENDALL ;3S
50/50
2.402
276897AD1-100 C
Solar/Wind Harmer
140.988
274695ROCKY RD ;2P
Adder
32.477
274693ROCKY RD ;1P
Adder
32.158
274697ROCKY RD ;3P
Adder
8.823
274696ROCKY RD ;4P
Adder
33.24
962691AG1-118 GEN
Solar/Wind Harmer
87.001
960751AF2-366 GEN
Solar/Wind Harmer
8.279
274674JOLIET 9 ;6U
Adder
44.223
274683WAUKEGAN ;8U
Adder
60.368
274683WAUKEGAN ;8U
Adder
50.887
274805UNIV PK N;1U
Adder
14.348
274808UNIV PK N;4U
Adder
14.254
276893AG1-478 C
Solar/Wind Harmer
1.242
274888KELLY CRK;1U
Solar/Wind Harmer
16.531
276776AD2-060 GEN
Solar/Wind Harmer
1.173
958011AF2-095 GEN
Solar/Wind Harmer
40.34
970941AG2-585 GEN
Solar/Wind Harmer
15.408
971341AH1-150 GEN
Solar/Wind Harmer
55.322
971343AH1-151 GEN
Solar/Wind Harmer
55.322
972235AH1-702 GEN1
Adder
6.879
972236AH1-702 GEN2
Adder
5.982
958481AF2-142 GEN
Solar/Wind Harmer
40.871
276901AD2-066 C O1
Solar/Wind Harmer
9.494
958491AF2-143 GEN
Solar/Wind Harmer
40.076
938861AE1-114 GEN
Solar/Wind Harmer
21.844
274764LEE CO EC;5U
Adder
24.669
274765LEE CO EC;6U
Adder
24.669
274762LEE CO EC;3U
Adder
24.611
274763LEE CO EC;4U
Adder
24.379
276872AE1-163_GEN1
Solar/Wind Harmer
17.448
274775LINCOLN ;6U
50/50
23.785
274776LINCOLN ;7U
50/50
23.785
274777LINCOLN ;8U
50/50
23.785
274661LASCO STA;2U
50/50
17.331
274660LASCO STA;1U
50/50
22.388
274708KENDALL ;3C
50/50
3.635
274704KENDALL ;1C
50/50
3.34
274706KENDALL ;2C
50/50
3.34
274744AC1-111 GEN8
Adder
16.783
274746AC1-111 G10
Adder
16.783
970833AG2-524 GEN
Solar/Wind Harmer
26.188
970833AG2-524 GEN
Solar/Wind Harmer
12.18
972227AH1-698 GEN1
Adder
7.774
972228AH1-698 GEN2
Adder
11.037
274675JOLIET 29;7U
Adder
89.067
274675JOLIET 29;7U
Adder
85.886
274731ELWOOD EC;2P
Adder
47.515
274733ELWOOD EC;3P
Adder
47.515
274735ELWOOD EC;4P
Adder
47.515
274728ELWOOD EC;5P
Adder
47.507
276876AE1-163_GEN2
Solar/Wind Harmer
17.448
276158O29GEN2
Solar/Wind Harmer
12.769
276157O29GEN1
Solar/Wind Harmer
9.709
276645AC1-214 GEN1
Solar/Wind Harmer
3.292
942111AE2-223 GEN
Solar/Wind Harmer
18.498
960611AF2-352 GEN
Solar/Wind Harmer
4.993
274880W4-005 GEN4
Solar/Wind Harmer
5.289
276174W4-005 GEN2
Solar/Wind Harmer
5.289
274772LINCOLN ;3U
50/50
23.785
972259AH1-714 GEN
50/50
63.035
274707KENDALL ;2S
50/50
2.233
970707AG2-453 GEN
Solar/Wind Harmer
91.639
943121AE2-341 GEN
Solar/Wind Harmer
45.899
943591AF1-030 GEN
Solar/Wind Harmer
30.599
939351AE1-166 GEN
Solar/Wind Harmer
17.999
274676JOLIET 29;8U
Adder
85.88
274729ELWOOD EC;1P
Adder
47.515
274730ELWOOD EC;6P
Adder
47.507
274734ELWOOD EC;8P
Adder
47.507
274736ELWOOD EC;9P
Adder
47.507
274682WAUKEGAN ;7U
Adder
51.601
972231SS25-0005
Solar/Wind Harmer
27.243
972181SS23-001
Solar/Wind Harmer
17.027
274752CRETE EC ;2U
Adder
14.031
274753CRETE EC ;3U
Adder
14.031
274814UNIV PK N;0U
Adder
14.442
274807UNIV PK N;3U
Adder
14.411
274811UNIV PK N;7U
Adder
14.317
276799AD1-013 GEN
Solar/Wind Harmer
6.219
946671AF1-331 GEN
Solar/Wind Harmer
1.178
274855GSG-6 ;RU
Solar/Wind Harmer
10.375
274850MENDOTA H;RU
Solar/Wind Harmer
7.214
276602WESTBROOK C
Solar/Wind Harmer
5.973
274887GEN-1.85
Solar/Wind Harmer
14.926
276772AC2-154 GEN
Solar/Wind Harmer
7.818
276843GEN-1.7
Solar/Wind Harmer
1.606
276806AD2-047 C O1
Solar/Wind Harmer
29.969
274803UNIV PARK;6U
Adder
16.231
959091AF2-200 GEN
Solar/Wind Harmer
55.322
274862TOP CROP ;2U
Solar/Wind Harmer
13.788
972038AH1-567 GEN2
Adder
0.988
274826FISK ;BP
Adder
29.553
276868AE1-113 GEN
Solar/Wind Harmer
27.226
274879MINONK ;1U
Solar/Wind Harmer
18.151
274857EASY ROAD;U1
Solar/Wind Harmer
12.673
274760LEE CO EC;1U
Adder
24.611
274767LEE CO EC;8U
Adder
24.321
276603SUBLETTE C
Solar/Wind Harmer
2.764
970571AG2-364 GEN
Solar/Wind Harmer
50.958
276164X3-005 C
Solar/Wind Harmer
1.742
274851PROVIDENC;RU
Solar/Wind Harmer
7.001
274849CRESCENT ;1U
Solar/Wind Harmer
4.545
276782AC1-033 GEN
Solar/Wind Harmer
9.734
274878BISHOP HL;2U
Solar/Wind Harmer
8.236
965931AG1-462 GEN
Solar/Wind Harmer
61.337
971087AG2-675 GEN
Solar/Wind Harmer
8.95
274724RIVER EC ;11
Adder
38.453
965091AG1-374 GEN
Solar/Wind Harmer
64.41
959611AF2-252 GEN
Solar/Wind Harmer
4.993
276785W4-005 GEN1
Solar/Wind Harmer
5.289
971993AH1-541 GEN
Solar/Wind Harmer
16.161
957381AF2-032 GEN
Solar/Wind Harmer
3.014
942481AE2-261 GEN
Solar/Wind Harmer
44.542
276615X2-022 GEN
Solar/Wind Harmer
3.254
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276916AD2-100_GEN
Solar/Wind Harmer
30.3
276911AD2-131_GEN
Solar/Wind Harmer
6.124
970569AG2-363 GEN
Solar/Wind Harmer
76.437
276646AC1-214 GEN2
Solar/Wind Harmer
3.292
274848CAMPGROVE;RU
Solar/Wind Harmer
15.542
276655WTG1_EQ
Solar/Wind Harmer
19.694
276656WTG2_EQ
Solar/Wind Harmer
2.608
939741AE1-205 GEN
Solar/Wind Harmer
45.129
274723RIVER EC ;12
Adder
38.445
276686W4-005 GEN3
Solar/Wind Harmer
5.289
276621W2-048 GEN
Solar/Wind Harmer
10.362
965911AG1-460 GEN
Solar/Wind Harmer
2.079
274687WILL CNTY;4U
Adder
79.889
274687WILL CNTY;4U
Adder
79.889
276893AG1-478 C
Solar/Wind Harmer
1.559
971675AH1-338 GEN
Solar/Wind Harmer
50.62
276861AD2-134 GEN
Solar/Wind Harmer
5.017
276863AD2-134 GEN
Solar/Wind Harmer
5.017
960591AF2-350 GEN
Solar/Wind Harmer
28.014
971411AH1-196 GEN
Solar/Wind Harmer
41.893
972037AH1-567 GEN1
Adder
0.51
971171AH1-044 GEN
Solar/Wind Harmer
55.322
274823ROCKFORD ;21
Adder
53.414
274800UNIV PARK;3U
Adder
15.784
274801UNIV PARK;4U
Adder
15.784
274856ECOGROVE ;U1
Solar/Wind Harmer
9.106
276611AD2-172 GEN
Solar/Wind Harmer
6.907
276612AE2-035 GEN
Solar/Wind Harmer
6.907
274827FISK ;RP
Adder
20.945
274863CRW1-WTG
Solar/Wind Harmer
14.917
274864CRW2-WTG
Solar/Wind Harmer
14.917
970073AG2-061 GEN
Solar/Wind Harmer
6.213
971681AH1-341 GEN
Solar/Wind Harmer
39.998
276889AE2-281 GEN
Solar/Wind Harmer
4.985
926823AC1-168 GEN
Solar/Wind Harmer
11.142
972267AH1-718 GEN
Adder
10.786
276741O09 GEN1
Solar/Wind Harmer
9.117
970169AG2-114 GEN
Solar/Wind Harmer
25.441
274877BISHOP HL;1U
Solar/Wind Harmer
8.236
946321AF1-296 GEN
Solar/Wind Harmer
25.388
276726Z2-087_GEN
Solar/Wind Harmer
17.842
959341AF2-225 GEN
Solar/Wind Harmer
33.847
274853TWINGROVE;U1
Solar/Wind Harmer
15.468
274854TWINGROVE;U2
Solar/Wind Harmer
15.144
276668AB2-070 GEN1
Solar/Wind Harmer
3.859
276848AB2-070 GEN3
Solar/Wind Harmer
3.859
276849AB2-070 GEN2
Solar/Wind Harmer
3.859
276763AC1-053 GEN1
Solar/Wind Harmer
6.787
276764AC1-053 GEN2
Solar/Wind Harmer
6.787
991777J1629 G
External Queue
30.850322723388672
990512J1326
External Queue
13.68272590637207
990117J1214
External Queue
47.068572998046875
990727J1377 G
External Queue
15.952624320983887
991092J1477
External Queue
7.281757831573486
991303J1755 G
External Queue
11.446473121643066
990407J1304
External Queue
10.605093955993652
NYPJM->LTFIMP_NY
CLTF
2.529
WECLTFEXP_WEC->PJM
CLTF
10.324
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.074
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.534
CBM West 1LTFEXP_CBM-W1->PJM
CBM
172.893
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.868
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.394
MECLTFEXP_MEC->PJM
CLTF
32.345
SIGELTFEXP_SIGE->PJM
CLTF
0.045
AG2-052LTFEXP_AG2-052->PJM
LTF
0.082
AH1-155LTFEXP_AH1-155->PJM
LTF
0.122
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.148
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.22
LAGNLTFEXP_LAGN->PJM
CLTF
10.658
TVALTFEXP_TVA->PJM
CLTF
2.709

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:123.83 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:5522.64
MW Contribution:
40.0
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.0 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:5351.81
MW Contribution:
38.9
Bus #Bus NameTypeMW Contribution
274772LINCOLN ;3U
50/50
23.785
972259AH1-714 GEN
50/50
63.035
274707KENDALL ;2S
50/50
2.233
970707AG2-453 GEN
Solar/Wind Harmer
91.639
943121AE2-341 GEN
Solar/Wind Harmer
45.899
943591AF1-030 GEN
Solar/Wind Harmer
30.599
939351AE1-166 GEN
Solar/Wind Harmer
17.999
274676JOLIET 29;8U
Adder
85.88
274729ELWOOD EC;1P
Adder
47.515
274730ELWOOD EC;6P
Adder
47.507
274734ELWOOD EC;8P
Adder
47.507
274736ELWOOD EC;9P
Adder
47.507
274682WAUKEGAN ;7U
Adder
51.601
274814UNIV PK N;0U
Adder
14.442
274807UNIV PK N;3U
Adder
14.411
274811UNIV PK N;7U
Adder
14.317
276799AD1-013 GEN
Solar/Wind Harmer
6.219
946671AF1-331 GEN
Solar/Wind Harmer
1.178
274855GSG-6 ;RU
Solar/Wind Harmer
10.375
274850MENDOTA H;RU
Solar/Wind Harmer
7.214
276602WESTBROOK C
Solar/Wind Harmer
5.973
274887GEN-1.85
Solar/Wind Harmer
14.926
276772AC2-154 GEN
Solar/Wind Harmer
7.818
276843GEN-1.7
Solar/Wind Harmer
1.606
276806AD2-047 C O1
Solar/Wind Harmer
29.969
274803UNIV PARK;6U
Adder
16.231
959091AF2-200 GEN
Solar/Wind Harmer
55.322
274862TOP CROP ;2U
Solar/Wind Harmer
13.788
972038AH1-567 GEN2
Adder
0.988
274826FISK ;BP
Adder
29.553
276868AE1-113 GEN
Solar/Wind Harmer
27.226
274879MINONK ;1U
Solar/Wind Harmer
18.151
274857EASY ROAD;U1
Solar/Wind Harmer
12.673
274760LEE CO EC;1U
Adder
24.611
274767LEE CO EC;8U
Adder
24.321
276603SUBLETTE C
Solar/Wind Harmer
2.764
970571AG2-364 GEN
Solar/Wind Harmer
50.958
276164X3-005 C
Solar/Wind Harmer
1.742
274851PROVIDENC;RU
Solar/Wind Harmer
7.001
274849CRESCENT ;1U
Solar/Wind Harmer
4.545
276782AC1-033 GEN
Solar/Wind Harmer
9.734
274878BISHOP HL;2U
Solar/Wind Harmer
8.236
965931AG1-462 GEN
Solar/Wind Harmer
61.337
971087AG2-675 GEN
Solar/Wind Harmer
8.95
274724RIVER EC ;11
Adder
38.453
965091AG1-374 GEN
Solar/Wind Harmer
64.41
959611AF2-252 GEN
Solar/Wind Harmer
4.993
276785W4-005 GEN1
Solar/Wind Harmer
5.289
971993AH1-541 GEN
Solar/Wind Harmer
16.161
957381AF2-032 GEN
Solar/Wind Harmer
3.014
942481AE2-261 GEN
Solar/Wind Harmer
44.542
274770LINCOLN ;1U
50/50
23.785
274771LINCOLN ;2U
50/50
23.785
274711KENDALL ;4S
50/50
2.402
274709KENDALL ;3S
50/50
2.402
276897AD1-100 C
Solar/Wind Harmer
140.988
274695ROCKY RD ;2P
Adder
32.477
274693ROCKY RD ;1P
Adder
32.158
274697ROCKY RD ;3P
Adder
8.823
274696ROCKY RD ;4P
Adder
33.24
962691AG1-118 GEN
Solar/Wind Harmer
87.001
960751AF2-366 GEN
Solar/Wind Harmer
8.279
274674JOLIET 9 ;6U
Adder
44.223
274683WAUKEGAN ;8U
Adder
60.368
274683WAUKEGAN ;8U
Adder
50.887
274805UNIV PK N;1U
Adder
14.348
274808UNIV PK N;4U
Adder
14.254
276893AG1-478 C
Solar/Wind Harmer
1.242
274888KELLY CRK;1U
Solar/Wind Harmer
16.531
276776AD2-060 GEN
Solar/Wind Harmer
1.173
958011AF2-095 GEN
Solar/Wind Harmer
40.34
970941AG2-585 GEN
Solar/Wind Harmer
15.408
971341AH1-150 GEN
Solar/Wind Harmer
55.322
971343AH1-151 GEN
Solar/Wind Harmer
55.322
972235AH1-702 GEN1
Adder
6.879
972236AH1-702 GEN2
Adder
5.982
958481AF2-142 GEN
Solar/Wind Harmer
40.871
276901AD2-066 C O1
Solar/Wind Harmer
9.494
958491AF2-143 GEN
Solar/Wind Harmer
40.076
938861AE1-114 GEN
Solar/Wind Harmer
21.844
274764LEE CO EC;5U
Adder
24.669
274765LEE CO EC;6U
Adder
24.669
274762LEE CO EC;3U
Adder
24.611
274763LEE CO EC;4U
Adder
24.379
276872AE1-163_GEN1
Solar/Wind Harmer
17.448
276876AE1-163_GEN2
Solar/Wind Harmer
17.448
276158O29GEN2
Solar/Wind Harmer
12.769
276157O29GEN1
Solar/Wind Harmer
9.709
276645AC1-214 GEN1
Solar/Wind Harmer
3.292
942111AE2-223 GEN
Solar/Wind Harmer
18.498
960611AF2-352 GEN
Solar/Wind Harmer
4.993
274880W4-005 GEN4
Solar/Wind Harmer
5.289
276174W4-005 GEN2
Solar/Wind Harmer
5.289
276615X2-022 GEN
Solar/Wind Harmer
3.254
276838X2-022 GEN2
Solar/Wind Harmer
0.386
276916AD2-100_GEN
Solar/Wind Harmer
30.3
276911AD2-131_GEN
Solar/Wind Harmer
6.124
274775LINCOLN ;6U
50/50
23.785
274776LINCOLN ;7U
50/50
23.785
274777LINCOLN ;8U
50/50
23.785
274661LASCO STA;2U
50/50
17.331
274660LASCO STA;1U
50/50
22.388
274708KENDALL ;3C
50/50
3.635
274704KENDALL ;1C
50/50
3.34
274706KENDALL ;2C
50/50
3.34
274744AC1-111 GEN8
Adder
16.783
274746AC1-111 G10
Adder
16.783
970833AG2-524 GEN
Solar/Wind Harmer
26.188
970833AG2-524 GEN
Solar/Wind Harmer
12.18
972227AH1-698 GEN1
Adder
7.774
972228AH1-698 GEN2
Adder
11.037
274675JOLIET 29;7U
Adder
89.067
274675JOLIET 29;7U
Adder
85.886
274731ELWOOD EC;2P
Adder
47.515
274733ELWOOD EC;3P
Adder
47.515
274735ELWOOD EC;4P
Adder
47.515
274728ELWOOD EC;5P
Adder
47.507
274687WILL CNTY;4U
Adder
79.889
274687WILL CNTY;4U
Adder
79.889
276893AG1-478 C
Solar/Wind Harmer
1.559
971675AH1-338 GEN
Solar/Wind Harmer
50.62
276861AD2-134 GEN
Solar/Wind Harmer
5.017
276863AD2-134 GEN
Solar/Wind Harmer
5.017
960591AF2-350 GEN
Solar/Wind Harmer
28.014
971411AH1-196 GEN
Solar/Wind Harmer
41.893
972037AH1-567 GEN1
Adder
0.51
971171AH1-044 GEN
Solar/Wind Harmer
55.322
274823ROCKFORD ;21
Adder
53.414
274800UNIV PARK;3U
Adder
15.784
274801UNIV PARK;4U
Adder
15.784
274856ECOGROVE ;U1
Solar/Wind Harmer
9.106
276611AD2-172 GEN
Solar/Wind Harmer
6.907
276612AE2-035 GEN
Solar/Wind Harmer
6.907
274827FISK ;RP
Adder
20.945
274863CRW1-WTG
Solar/Wind Harmer
14.917
274864CRW2-WTG
Solar/Wind Harmer
14.917
970073AG2-061 GEN
Solar/Wind Harmer
6.213
971681AH1-341 GEN
Solar/Wind Harmer
39.998
276889AE2-281 GEN
Solar/Wind Harmer
4.985
926823AC1-168 GEN
Solar/Wind Harmer
11.142
972267AH1-718 GEN
Adder
10.786
276741O09 GEN1
Solar/Wind Harmer
9.117
970169AG2-114 GEN
Solar/Wind Harmer
25.441
274877BISHOP HL;1U
Solar/Wind Harmer
8.236
946321AF1-296 GEN
Solar/Wind Harmer
25.388
276726Z2-087_GEN
Solar/Wind Harmer
17.842
959341AF2-225 GEN
Solar/Wind Harmer
33.847
274853TWINGROVE;U1
Solar/Wind Harmer
15.468
274854TWINGROVE;U2
Solar/Wind Harmer
15.144
276668AB2-070 GEN1
Solar/Wind Harmer
3.859
276848AB2-070 GEN3
Solar/Wind Harmer
3.859
276849AB2-070 GEN2
Solar/Wind Harmer
3.859
276763AC1-053 GEN1
Solar/Wind Harmer
6.787
276764AC1-053 GEN2
Solar/Wind Harmer
6.787
944221AF1-090 GEN
Solar/Wind Harmer
14.014
274773LINCOLN ;4U
50/50
23.785
274774LINCOLN ;5U
50/50
23.785
274710KENDALL ;4C
50/50
3.594
274705KENDALL ;1S
50/50
2.233
972207SS24-0001
Solar/Wind Harmer
79.696
941551AE2-152 GEN
Solar/Wind Harmer
13.765
274871GR RIDGE ;2U
Solar/Wind Harmer
23.136
274847GR RIDGE ;BU
Solar/Wind Harmer
15.212
274745AC1-111 GEN9
Adder
16.783
274676JOLIET 29;8U
Adder
89.061
274732ELWOOD EC;7P
Adder
47.507
962781AG1-127 GEN
Solar/Wind Harmer
27.442
274872LEEDK;1U
Solar/Wind Harmer
23.583
274674JOLIET 9 ;6U
Adder
44.223
274682WAUKEGAN ;7U
Adder
51.601
274828WAUKEGAN ;BP
Adder
31.644
274812UNIV PK N;8U
Adder
14.317
939401AE1-172 GEN
Solar/Wind Harmer
38.947
274802UNIV PARK;5U
Adder
16.231
957471AF2-041 GEN
Solar/Wind Harmer
82.983
959081AF2-199 GEN
Solar/Wind Harmer
27.661
971067AG2-660 GEN
Solar/Wind Harmer
6.433
971997AH1-543 GEN
Solar/Wind Harmer
43.252
274822ROCKFORD ;11
Adder
53.804
274861TOP CROP ;1U
Solar/Wind Harmer
16.513
276694AA1-018 GEN2
Solar/Wind Harmer
17.192
276691AA1-018 GEN1
Solar/Wind Harmer
2.055
970819AG2-516 GEN
Solar/Wind Harmer
32.522
276882AE2-255 GEN
Solar/Wind Harmer
9.076
276805AD2-038 GEN
Solar/Wind Harmer
13.7
274858EASY ROAD;U2
Solar/Wind Harmer
12.673
274761LEE CO EC;2U
Adder
24.611
274766LEE CO EC;7U
Adder
24.321
276708O09 GEN2
Solar/Wind Harmer
9.117
970569AG2-363 GEN
Solar/Wind Harmer
76.437
276646AC1-214 GEN2
Solar/Wind Harmer
3.292
274848CAMPGROVE;RU
Solar/Wind Harmer
15.542
276655WTG1_EQ
Solar/Wind Harmer
19.694
276656WTG2_EQ
Solar/Wind Harmer
2.608
939741AE1-205 GEN
Solar/Wind Harmer
45.129
274723RIVER EC ;12
Adder
38.445
276686W4-005 GEN3
Solar/Wind Harmer
5.289
276621W2-048 GEN
Solar/Wind Harmer
10.362
965911AG1-460 GEN
Solar/Wind Harmer
2.079
991777J1629 G
External Queue
30.850322723388672
990512J1326
External Queue
13.68272590637207
991278J1725 G
External Queue
4.494668006896973
990117J1214
External Queue
47.068572998046875
990727J1377 G
External Queue
15.952624320983887
991092J1477
External Queue
7.281757831573486
991303J1755 G
External Queue
11.600627899169922
990407J1304
External Queue
10.605093955993652
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.534
NYPJM->LTFIMP_NY
CLTF
2.529
WECLTFEXP_WEC->PJM
CLTF
10.324
CBM West 1LTFEXP_CBM-W1->PJM
CBM
172.893
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.394
MECLTFEXP_MEC->PJM
CLTF
32.345
SIGELTFEXP_SIGE->PJM
CLTF
0.045
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.074
AG2-052LTFEXP_AG2-052->PJM
LTF
0.082
AH1-155LTFEXP_AH1-155->PJM
LTF
0.122
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.868
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.148
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.22
LAGNLTFEXP_LAGN->PJM
CLTF
10.658
TVALTFEXP_TVA->PJM
CLTF
2.709

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o AEP_P4_#2973_05DUMONT 345_F1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.05 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:5086.61
MW Contribution:
36.48
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.38 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:4967.64
MW Contribution:
35.71
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
22.577
274771LINCOLN ;2U
50/50
22.577
274711KENDALL ;4S
50/50
2.197
274709KENDALL ;3S
50/50
2.197
276897AD1-100 C
Solar/Wind Harmer
129.206
274695ROCKY RD ;2P
Adder
29.605
274693ROCKY RD ;1P
Adder
29.314
274697ROCKY RD ;3P
Adder
8.042
274696ROCKY RD ;4P
Adder
30.301
962691AG1-118 GEN
Solar/Wind Harmer
79.509
960751AF2-366 GEN
Solar/Wind Harmer
7.566
274674JOLIET 9 ;6U
Adder
40.376
274683WAUKEGAN ;8U
Adder
54.833
274683WAUKEGAN ;8U
Adder
46.222
958011AF2-095 GEN
Solar/Wind Harmer
37.15
274888KELLY CRK;1U
Solar/Wind Harmer
15.224
276776AD2-060 GEN
Solar/Wind Harmer
1.08
970941AG2-585 GEN
Solar/Wind Harmer
14.189
276893AG1-478 C
Solar/Wind Harmer
1.13
971341AH1-150 GEN
Solar/Wind Harmer
50.475
971343AH1-151 GEN
Solar/Wind Harmer
50.475
274773LINCOLN ;4U
50/50
22.577
274774LINCOLN ;5U
50/50
22.577
274710KENDALL ;4C
50/50
3.286
274705KENDALL ;1S
50/50
2.01
972207SS24-0001
Solar/Wind Harmer
75.647
941551AE2-152 GEN
Solar/Wind Harmer
12.615
274745AC1-111 GEN9
Adder
15.334
274871GR RIDGE ;2U
Solar/Wind Harmer
21.001
274847GR RIDGE ;BU
Solar/Wind Harmer
13.809
962781AG1-127 GEN
Solar/Wind Harmer
25.078
274872LEEDK;1U
Solar/Wind Harmer
21.552
274674JOLIET 9 ;6U
Adder
40.376
274676JOLIET 29;8U
Adder
80.082
274682WAUKEGAN ;7U
Adder
46.867
274828WAUKEGAN ;BP
Adder
28.743
274732ELWOOD EC;7P
Adder
42.686
939401AE1-172 GEN
Solar/Wind Harmer
35.917
957471AF2-041 GEN
Solar/Wind Harmer
75.712
972235AH1-702 GEN1
Adder
6.271
972236AH1-702 GEN2
Adder
5.453
276901AD2-066 C O1
Solar/Wind Harmer
8.606
958481AF2-142 GEN
Solar/Wind Harmer
36.633
938861AE1-114 GEN
Solar/Wind Harmer
19.917
274764LEE CO EC;5U
Adder
22.493
274765LEE CO EC;6U
Adder
22.493
274762LEE CO EC;3U
Adder
22.44
274763LEE CO EC;4U
Adder
22.228
958491AF2-143 GEN
Solar/Wind Harmer
36
276872AE1-163_GEN1
Solar/Wind Harmer
15.724
276876AE1-163_GEN2
Solar/Wind Harmer
15.724
276158O29GEN2
Solar/Wind Harmer
11.64
276157O29GEN1
Solar/Wind Harmer
8.85
276645AC1-214 GEN1
Solar/Wind Harmer
2.997
274805UNIV PK N;1U
Adder
10.964
274808UNIV PK N;4U
Adder
10.892
942111AE2-223 GEN
Solar/Wind Harmer
17.05
960611AF2-352 GEN
Solar/Wind Harmer
4.604
274880W4-005 GEN4
Solar/Wind Harmer
4.888
276174W4-005 GEN2
Solar/Wind Harmer
4.888
276615X2-022 GEN
Solar/Wind Harmer
3.008
276838X2-022 GEN2
Solar/Wind Harmer
0.357
276916AD2-100_GEN
Solar/Wind Harmer
28.052
276911AD2-131_GEN
Solar/Wind Harmer
5.669
274775LINCOLN ;6U
50/50
22.577
274776LINCOLN ;7U
50/50
22.577
274777LINCOLN ;8U
50/50
22.577
274708KENDALL ;3C
50/50
3.325
274661LASCO STA;2U
50/50
15.72
274660LASCO STA;1U
50/50
20.307
274704KENDALL ;1C
50/50
3.007
274706KENDALL ;2C
50/50
3.007
274744AC1-111 GEN8
Adder
15.334
274746AC1-111 G10
Adder
15.334
970833AG2-524 GEN
Solar/Wind Harmer
23.786
970833AG2-524 GEN
Solar/Wind Harmer
11.063
972227AH1-698 GEN1
Adder
6.941
972228AH1-698 GEN2
Adder
9.854
274675JOLIET 29;7U
Adder
80.09
274675JOLIET 29;7U
Adder
77.23
274731ELWOOD EC;2P
Adder
42.699
274733ELWOOD EC;3P
Adder
42.699
274735ELWOOD EC;4P
Adder
42.699
274728ELWOOD EC;5P
Adder
42.686
960591AF2-350 GEN
Solar/Wind Harmer
25.798
274687WILL CNTY;4U
Adder
72.042
274687WILL CNTY;4U
Adder
72.042
276893AG1-478 C
Solar/Wind Harmer
1.418
971675AH1-338 GEN
Solar/Wind Harmer
46.24
276861AD2-134 GEN
Solar/Wind Harmer
4.583
276863AD2-134 GEN
Solar/Wind Harmer
4.583
971411AH1-196 GEN
Solar/Wind Harmer
38.17
971171AH1-044 GEN
Solar/Wind Harmer
50.475
274800UNIV PARK;3U
Adder
14.652
274801UNIV PARK;4U
Adder
14.652
274823ROCKFORD ;21
Adder
48.685
274827FISK ;RP
Adder
19.337
274863CRW1-WTG
Solar/Wind Harmer
13.75
274864CRW2-WTG
Solar/Wind Harmer
13.75
274856ECOGROVE ;U1
Solar/Wind Harmer
8.301
276611AD2-172 GEN
Solar/Wind Harmer
6.297
276612AE2-035 GEN
Solar/Wind Harmer
6.297
971681AH1-341 GEN
Solar/Wind Harmer
36.475
972037AH1-567 GEN1
Adder
0.445
970073AG2-061 GEN
Solar/Wind Harmer
5.581
972267AH1-718 GEN
Adder
9.836
926823AC1-168 GEN
Solar/Wind Harmer
10.131
276889AE2-281 GEN
Solar/Wind Harmer
4.492
970169AG2-114 GEN
Solar/Wind Harmer
23.392
276741O09 GEN1
Solar/Wind Harmer
8.311
274877BISHOP HL;1U
Solar/Wind Harmer
7.497
946321AF1-296 GEN
Solar/Wind Harmer
23.15
276726Z2-087_GEN
Solar/Wind Harmer
16.445
959341AF2-225 GEN
Solar/Wind Harmer
31.197
274853TWINGROVE;U1
Solar/Wind Harmer
14.263
274854TWINGROVE;U2
Solar/Wind Harmer
13.964
276668AB2-070 GEN1
Solar/Wind Harmer
3.566
276848AB2-070 GEN3
Solar/Wind Harmer
3.566
276849AB2-070 GEN2
Solar/Wind Harmer
3.566
276763AC1-053 GEN1
Solar/Wind Harmer
6.272
276764AC1-053 GEN2
Solar/Wind Harmer
6.272
274772LINCOLN ;3U
50/50
22.577
972259AH1-714 GEN
50/50
57.175
274707KENDALL ;2S
50/50
2.01
970707AG2-453 GEN
Solar/Wind Harmer
84.287
943121AE2-341 GEN
Solar/Wind Harmer
42.095
943591AF1-030 GEN
Solar/Wind Harmer
28.063
939351AE1-166 GEN
Solar/Wind Harmer
16.495
274676JOLIET 29;8U
Adder
77.222
274682WAUKEGAN ;7U
Adder
46.867
274729ELWOOD EC;1P
Adder
42.699
274730ELWOOD EC;6P
Adder
42.686
274734ELWOOD EC;8P
Adder
42.686
274736ELWOOD EC;9P
Adder
42.686
274887GEN-1.85
Solar/Wind Harmer
13.745
276772AC2-154 GEN
Solar/Wind Harmer
7.199
276843GEN-1.7
Solar/Wind Harmer
1.479
276806AD2-047 C O1
Solar/Wind Harmer
27.598
276799AD1-013 GEN
Solar/Wind Harmer
5.681
946671AF1-331 GEN
Solar/Wind Harmer
1.076
274855GSG-6 ;RU
Solar/Wind Harmer
9.477
274850MENDOTA H;RU
Solar/Wind Harmer
6.589
276602WESTBROOK C
Solar/Wind Harmer
5.456
959091AF2-200 GEN
Solar/Wind Harmer
50.475
972038AH1-567 GEN2
Adder
0.917
274826FISK ;BP
Adder
27.285
276164X3-005 C
Solar/Wind Harmer
1.713
274803UNIV PARK;6U
Adder
14.166
274862TOP CROP ;2U
Solar/Wind Harmer
12.288
276868AE1-113 GEN
Solar/Wind Harmer
24.574
274879MINONK ;1U
Solar/Wind Harmer
16.384
274857EASY ROAD;U1
Solar/Wind Harmer
11.555
274760LEE CO EC;1U
Adder
22.44
274767LEE CO EC;8U
Adder
22.175
276603SUBLETTE C
Solar/Wind Harmer
2.521
970571AG2-364 GEN
Solar/Wind Harmer
46.026
274724RIVER EC ;11
Adder
40.175
274851PROVIDENC;RU
Solar/Wind Harmer
6.372
274849CRESCENT ;1U
Solar/Wind Harmer
4.136
276782AC1-033 GEN
Solar/Wind Harmer
8.861
274878BISHOP HL;2U
Solar/Wind Harmer
7.497
965931AG1-462 GEN
Solar/Wind Harmer
55.932
971087AG2-675 GEN
Solar/Wind Harmer
8.162
274814UNIV PK N;0U
Adder
11.036
274807UNIV PK N;3U
Adder
11.012
274811UNIV PK N;7U
Adder
10.94
965091AG1-374 GEN
Solar/Wind Harmer
59.392
959611AF2-252 GEN
Solar/Wind Harmer
4.604
972231SS25-0005
Solar/Wind Harmer
18.009
972181SS23-001
Solar/Wind Harmer
11.256
274752CRETE EC ;2U
Adder
9.275
274753CRETE EC ;3U
Adder
9.275
276785W4-005 GEN1
Solar/Wind Harmer
4.888
971993AH1-541 GEN
Solar/Wind Harmer
14.937
957381AF2-032 GEN
Solar/Wind Harmer
2.788
942481AE2-261 GEN
Solar/Wind Harmer
41.21
959081AF2-199 GEN
Solar/Wind Harmer
25.237
971067AG2-660 GEN
Solar/Wind Harmer
5.869
971997AH1-543 GEN
Solar/Wind Harmer
39.391
274822ROCKFORD ;11
Adder
49.04
970819AG2-516 GEN
Solar/Wind Harmer
29.643
276694AA1-018 GEN2
Solar/Wind Harmer
15.41
276691AA1-018 GEN1
Solar/Wind Harmer
1.842
274802UNIV PARK;5U
Adder
14.166
274861TOP CROP ;1U
Solar/Wind Harmer
14.717
276882AE2-255 GEN
Solar/Wind Harmer
8.192
274858EASY ROAD;U2
Solar/Wind Harmer
11.555
274761LEE CO EC;2U
Adder
22.44
274766LEE CO EC;7U
Adder
22.175
276805AD2-038 GEN
Solar/Wind Harmer
12.307
276708O09 GEN2
Solar/Wind Harmer
8.311
970569AG2-363 GEN
Solar/Wind Harmer
69.04
274723RIVER EC ;12
Adder
40.474
276646AC1-214 GEN2
Solar/Wind Harmer
2.997
274848CAMPGROVE;RU
Solar/Wind Harmer
14.149
274812UNIV PK N;8U
Adder
10.94
276655WTG1_EQ
Solar/Wind Harmer
18.153
276656WTG2_EQ
Solar/Wind Harmer
2.404
939741AE1-205 GEN
Solar/Wind Harmer
41.597
274751CRETE EC ;1U
Adder
9.275
274754CRETE EC ;4U
Adder
9.275
276686W4-005 GEN3
Solar/Wind Harmer
4.888
276621W2-048 GEN
Solar/Wind Harmer
9.577
965911AG1-460 GEN
Solar/Wind Harmer
1.923
991777J1629 G
External Queue
27.41379737854004
990512J1326
External Queue
12.176995277404785
990117J1214
External Queue
41.88886260986328
990727J1377 G
External Queue
14.21141242980957
991092J1477
External Queue
6.454954147338867
991303J1755 G
External Queue
10.145639419555664
990407J1304
External Queue
9.444897651672363
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.477
NYPJM->LTFIMP_NY
CLTF
2.312
WECLTFEXP_WEC->PJM
CLTF
9.389
CBM West 1LTFEXP_CBM-W1->PJM
CBM
163.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.073
CBM West 2LTFEXP_CBM-W2->PJM
CBM
72.846
MECLTFEXP_MEC->PJM
CLTF
29.542
SIGELTFEXP_SIGE->PJM
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.967
AG2-052LTFEXP_AG2-052->PJM
LTF
0.249
AH1-155LTFEXP_AH1-155->PJM
LTF
0.373
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.985
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.73
LAGNLTFEXP_LAGN->PJM
CLTF
9.883
TVALTFEXP_TVA->PJM
CLTF
2.555

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o AEP_P4_#2976_05DUMONT 345_F_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2976_05DUMONT 345_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.94 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:5081.51
MW Contribution:
36.43
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2976_05DUMONT 345_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.2 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:4959.3
MW Contribution:
35.64
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
22.551
274771LINCOLN ;2U
50/50
22.551
274711KENDALL ;4S
50/50
2.194
274709KENDALL ;3S
50/50
2.194
276897AD1-100 C
Solar/Wind Harmer
129.042
274695ROCKY RD ;2P
Adder
29.567
274693ROCKY RD ;1P
Adder
29.276
274697ROCKY RD ;3P
Adder
8.032
274696ROCKY RD ;4P
Adder
30.262
962691AG1-118 GEN
Solar/Wind Harmer
79.407
960751AF2-366 GEN
Solar/Wind Harmer
7.556
274674JOLIET 9 ;6U
Adder
40.324
274683WAUKEGAN ;8U
Adder
54.762
274683WAUKEGAN ;8U
Adder
46.162
274888KELLY CRK;1U
Solar/Wind Harmer
15.204
276776AD2-060 GEN
Solar/Wind Harmer
1.079
958011AF2-095 GEN
Solar/Wind Harmer
37.101
970941AG2-585 GEN
Solar/Wind Harmer
14.171
276893AG1-478 C
Solar/Wind Harmer
1.129
971341AH1-150 GEN
Solar/Wind Harmer
50.409
971343AH1-151 GEN
Solar/Wind Harmer
50.409
972235AH1-702 GEN1
Adder
6.263
972236AH1-702 GEN2
Adder
5.446
276901AD2-066 C O1
Solar/Wind Harmer
8.595
958481AF2-142 GEN
Solar/Wind Harmer
36.584
938861AE1-114 GEN
Solar/Wind Harmer
19.891
274764LEE CO EC;5U
Adder
22.463
274765LEE CO EC;6U
Adder
22.463
274762LEE CO EC;3U
Adder
22.41
274763LEE CO EC;4U
Adder
22.199
958491AF2-143 GEN
Solar/Wind Harmer
35.952
276872AE1-163_GEN1
Solar/Wind Harmer
15.702
276876AE1-163_GEN2
Solar/Wind Harmer
15.702
276158O29GEN2
Solar/Wind Harmer
11.624
276157O29GEN1
Solar/Wind Harmer
8.838
276645AC1-214 GEN1
Solar/Wind Harmer
2.993
274805UNIV PK N;1U
Adder
10.947
274808UNIV PK N;4U
Adder
10.875
942111AE2-223 GEN
Solar/Wind Harmer
17.026
960611AF2-352 GEN
Solar/Wind Harmer
4.597
274880W4-005 GEN4
Solar/Wind Harmer
4.881
276174W4-005 GEN2
Solar/Wind Harmer
4.881
276615X2-022 GEN
Solar/Wind Harmer
3.003
276838X2-022 GEN2
Solar/Wind Harmer
0.357
276916AD2-100_GEN
Solar/Wind Harmer
28.004
276911AD2-131_GEN
Solar/Wind Harmer
5.66
274772LINCOLN ;3U
50/50
22.551
972259AH1-714 GEN
50/50
57.103
274707KENDALL ;2S
50/50
2.007
970707AG2-453 GEN
Solar/Wind Harmer
84.184
943121AE2-341 GEN
Solar/Wind Harmer
42.042
943591AF1-030 GEN
Solar/Wind Harmer
28.028
939351AE1-166 GEN
Solar/Wind Harmer
16.474
274676JOLIET 29;8U
Adder
77.12
274682WAUKEGAN ;7U
Adder
46.806
274729ELWOOD EC;1P
Adder
42.643
274730ELWOOD EC;6P
Adder
42.63
274734ELWOOD EC;8P
Adder
42.63
274736ELWOOD EC;9P
Adder
42.63
274887GEN-1.85
Solar/Wind Harmer
13.727
276772AC2-154 GEN
Solar/Wind Harmer
7.19
276843GEN-1.7
Solar/Wind Harmer
1.477
276806AD2-047 C O1
Solar/Wind Harmer
27.562
276799AD1-013 GEN
Solar/Wind Harmer
5.674
946671AF1-331 GEN
Solar/Wind Harmer
1.075
274855GSG-6 ;RU
Solar/Wind Harmer
9.465
274850MENDOTA H;RU
Solar/Wind Harmer
6.581
276602WESTBROOK C
Solar/Wind Harmer
5.449
959091AF2-200 GEN
Solar/Wind Harmer
50.409
972038AH1-567 GEN2
Adder
0.916
274826FISK ;BP
Adder
27.249
276164X3-005 C
Solar/Wind Harmer
1.71
274803UNIV PARK;6U
Adder
14.146
274862TOP CROP ;2U
Solar/Wind Harmer
12.272
276868AE1-113 GEN
Solar/Wind Harmer
24.542
274879MINONK ;1U
Solar/Wind Harmer
16.362
274857EASY ROAD;U1
Solar/Wind Harmer
11.54
274760LEE CO EC;1U
Adder
22.41
274767LEE CO EC;8U
Adder
22.146
276603SUBLETTE C
Solar/Wind Harmer
2.517
970571AG2-364 GEN
Solar/Wind Harmer
45.964
274724RIVER EC ;11
Adder
40.125
274851PROVIDENC;RU
Solar/Wind Harmer
6.363
274849CRESCENT ;1U
Solar/Wind Harmer
4.131
276782AC1-033 GEN
Solar/Wind Harmer
8.849
274878BISHOP HL;2U
Solar/Wind Harmer
7.487
965931AG1-462 GEN
Solar/Wind Harmer
55.856
971087AG2-675 GEN
Solar/Wind Harmer
8.15
274814UNIV PK N;0U
Adder
11.018
274807UNIV PK N;3U
Adder
10.994
274811UNIV PK N;7U
Adder
10.923
965091AG1-374 GEN
Solar/Wind Harmer
59.308
959611AF2-252 GEN
Solar/Wind Harmer
4.597
972231SS25-0005
Solar/Wind Harmer
17.976
972181SS23-001
Solar/Wind Harmer
11.235
274752CRETE EC ;2U
Adder
9.258
274753CRETE EC ;3U
Adder
9.258
276785W4-005 GEN1
Solar/Wind Harmer
4.881
971993AH1-541 GEN
Solar/Wind Harmer
14.914
957381AF2-032 GEN
Solar/Wind Harmer
2.783
942481AE2-261 GEN
Solar/Wind Harmer
41.142
274773LINCOLN ;4U
50/50
22.551
274774LINCOLN ;5U
50/50
22.551
274710KENDALL ;4C
50/50
3.282
274705KENDALL ;1S
50/50
2.007
972207SS24-0001
Solar/Wind Harmer
75.56
941551AE2-152 GEN
Solar/Wind Harmer
12.599
274745AC1-111 GEN9
Adder
15.314
274871GR RIDGE ;2U
Solar/Wind Harmer
20.974
274847GR RIDGE ;BU
Solar/Wind Harmer
13.791
962781AG1-127 GEN
Solar/Wind Harmer
25.046
274872LEEDK;1U
Solar/Wind Harmer
21.525
274674JOLIET 9 ;6U
Adder
40.324
274676JOLIET 29;8U
Adder
79.977
274682WAUKEGAN ;7U
Adder
46.806
274828WAUKEGAN ;BP
Adder
28.705
274732ELWOOD EC;7P
Adder
42.63
939401AE1-172 GEN
Solar/Wind Harmer
35.871
957471AF2-041 GEN
Solar/Wind Harmer
75.613
959081AF2-199 GEN
Solar/Wind Harmer
25.204
971067AG2-660 GEN
Solar/Wind Harmer
5.862
971997AH1-543 GEN
Solar/Wind Harmer
39.339
274822ROCKFORD ;11
Adder
48.976
970819AG2-516 GEN
Solar/Wind Harmer
29.604
276694AA1-018 GEN2
Solar/Wind Harmer
15.389
276691AA1-018 GEN1
Solar/Wind Harmer
1.839
274802UNIV PARK;5U
Adder
14.146
274861TOP CROP ;1U
Solar/Wind Harmer
14.697
276882AE2-255 GEN
Solar/Wind Harmer
8.181
274858EASY ROAD;U2
Solar/Wind Harmer
11.54
274761LEE CO EC;2U
Adder
22.41
274766LEE CO EC;7U
Adder
22.146
276805AD2-038 GEN
Solar/Wind Harmer
12.29
276708O09 GEN2
Solar/Wind Harmer
8.299
970569AG2-363 GEN
Solar/Wind Harmer
68.946
274723RIVER EC ;12
Adder
40.423
276646AC1-214 GEN2
Solar/Wind Harmer
2.993
274848CAMPGROVE;RU
Solar/Wind Harmer
14.13
274812UNIV PK N;8U
Adder
10.923
276655WTG1_EQ
Solar/Wind Harmer
18.127
276656WTG2_EQ
Solar/Wind Harmer
2.4
939741AE1-205 GEN
Solar/Wind Harmer
41.538
274751CRETE EC ;1U
Adder
9.258
274754CRETE EC ;4U
Adder
9.258
276686W4-005 GEN3
Solar/Wind Harmer
4.881
276621W2-048 GEN
Solar/Wind Harmer
9.562
965911AG1-460 GEN
Solar/Wind Harmer
1.92
274775LINCOLN ;6U
50/50
22.551
274776LINCOLN ;7U
50/50
22.551
274777LINCOLN ;8U
50/50
22.551
274708KENDALL ;3C
50/50
3.32
274661LASCO STA;2U
50/50
15.7
274660LASCO STA;1U
50/50
20.281
274704KENDALL ;1C
50/50
3.003
274706KENDALL ;2C
50/50
3.003
274744AC1-111 GEN8
Adder
15.314
274746AC1-111 G10
Adder
15.314
970833AG2-524 GEN
Solar/Wind Harmer
23.756
970833AG2-524 GEN
Solar/Wind Harmer
11.049
972227AH1-698 GEN1
Adder
6.932
972228AH1-698 GEN2
Adder
9.841
274675JOLIET 29;7U
Adder
79.985
274675JOLIET 29;7U
Adder
77.128
274731ELWOOD EC;2P
Adder
42.643
274733ELWOOD EC;3P
Adder
42.643
274735ELWOOD EC;4P
Adder
42.643
274728ELWOOD EC;5P
Adder
42.63
960591AF2-350 GEN
Solar/Wind Harmer
25.765
274687WILL CNTY;4U
Adder
71.947
274687WILL CNTY;4U
Adder
71.947
276893AG1-478 C
Solar/Wind Harmer
1.416
971675AH1-338 GEN
Solar/Wind Harmer
46.18
276861AD2-134 GEN
Solar/Wind Harmer
4.577
276863AD2-134 GEN
Solar/Wind Harmer
4.577
971411AH1-196 GEN
Solar/Wind Harmer
38.121
971171AH1-044 GEN
Solar/Wind Harmer
50.409
274800UNIV PARK;3U
Adder
14.633
274801UNIV PARK;4U
Adder
14.633
274823ROCKFORD ;21
Adder
48.621
274827FISK ;RP
Adder
19.312
274863CRW1-WTG
Solar/Wind Harmer
13.732
274864CRW2-WTG
Solar/Wind Harmer
13.732
274856ECOGROVE ;U1
Solar/Wind Harmer
8.29
276611AD2-172 GEN
Solar/Wind Harmer
6.288
276612AE2-035 GEN
Solar/Wind Harmer
6.288
971681AH1-341 GEN
Solar/Wind Harmer
36.427
972037AH1-567 GEN1
Adder
0.444
970073AG2-061 GEN
Solar/Wind Harmer
5.574
972267AH1-718 GEN
Adder
9.823
926823AC1-168 GEN
Solar/Wind Harmer
10.118
276889AE2-281 GEN
Solar/Wind Harmer
4.486
970169AG2-114 GEN
Solar/Wind Harmer
23.36
276741O09 GEN1
Solar/Wind Harmer
8.299
274877BISHOP HL;1U
Solar/Wind Harmer
7.487
946321AF1-296 GEN
Solar/Wind Harmer
23.119
276726Z2-087_GEN
Solar/Wind Harmer
16.422
959341AF2-225 GEN
Solar/Wind Harmer
31.154
274853TWINGROVE;U1
Solar/Wind Harmer
14.243
274854TWINGROVE;U2
Solar/Wind Harmer
13.944
276668AB2-070 GEN1
Solar/Wind Harmer
3.561
276848AB2-070 GEN3
Solar/Wind Harmer
3.561
276849AB2-070 GEN2
Solar/Wind Harmer
3.561
276763AC1-053 GEN1
Solar/Wind Harmer
6.262
276764AC1-053 GEN2
Solar/Wind Harmer
6.262
991777J1629 G
External Queue
27.345205307006836
990512J1326
External Queue
12.146886825561523
990117J1214
External Queue
41.7852897644043
990727J1377 G
External Queue
14.176959991455078
991092J1477
External Queue
6.436434268951416
991303J1755 G
External Queue
10.118729591369629
990407J1304
External Queue
9.422101974487305
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.479
NYPJM->LTFIMP_NY
CLTF
2.309
WECLTFEXP_WEC->PJM
CLTF
9.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
163.333
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
72.671
MECLTFEXP_MEC->PJM
CLTF
29.499
SIGELTFEXP_SIGE->PJM
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.969
AG2-052LTFEXP_AG2-052->PJM
LTF
0.248
AH1-155LTFEXP_AH1-155->PJM
LTF
0.372
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.989
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.744
LAGNLTFEXP_LAGN->PJM
CLTF
9.859
TVALTFEXP_TVA->PJM
CLTF
2.546

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A_SENS
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.68 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:4891.59
MW Contribution:
34.62
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
21.701
274771LINCOLN ;2U
50/50
21.701
274711KENDALL ;4S
50/50
2.089
274709KENDALL ;3S
50/50
2.089
276897AD1-100 C
Solar/Wind Harmer
122.605
274695ROCKY RD ;2P
Adder
28.105
274693ROCKY RD ;1P
Adder
27.828
274697ROCKY RD ;3P
Adder
7.635
274696ROCKY RD ;4P
Adder
28.765
962691AG1-118 GEN
Solar/Wind Harmer
75.572
960751AF2-366 GEN
Solar/Wind Harmer
7.191
274674JOLIET 9 ;6U
Adder
38.004
274683WAUKEGAN ;8U
Adder
51.946
274683WAUKEGAN ;8U
Adder
43.788
276893AG1-478 C
Solar/Wind Harmer
1.062
274888KELLY CRK;1U
Solar/Wind Harmer
14.215
958011AF2-095 GEN
Solar/Wind Harmer
34.689
970941AG2-585 GEN
Solar/Wind Harmer
13.249
276776AD2-060 GEN
Solar/Wind Harmer
1.008
971341AH1-150 GEN
Solar/Wind Harmer
47.934
971343AH1-151 GEN
Solar/Wind Harmer
47.934
972235AH1-702 GEN1
Adder
5.952
972236AH1-702 GEN2
Adder
5.175
276901AD2-066 C O1
Solar/Wind Harmer
8.136
938861AE1-114 GEN
Solar/Wind Harmer
18.905
958481AF2-142 GEN
Solar/Wind Harmer
34.463
274764LEE CO EC;5U
Adder
21.35
274765LEE CO EC;6U
Adder
21.35
274762LEE CO EC;3U
Adder
21.299
274763LEE CO EC;4U
Adder
21.099
958491AF2-143 GEN
Solar/Wind Harmer
33.911
276872AE1-163_GEN1
Solar/Wind Harmer
14.839
276876AE1-163_GEN2
Solar/Wind Harmer
14.839
276158O29GEN2
Solar/Wind Harmer
11.046
276157O29GEN1
Solar/Wind Harmer
8.398
276645AC1-214 GEN1
Solar/Wind Harmer
2.841
274805UNIV PK N;1U
Adder
10.293
274808UNIV PK N;4U
Adder
10.226
942111AE2-223 GEN
Solar/Wind Harmer
16.23
960611AF2-352 GEN
Solar/Wind Harmer
4.383
274880W4-005 GEN4
Solar/Wind Harmer
4.657
276174W4-005 GEN2
Solar/Wind Harmer
4.657
276615X2-022 GEN
Solar/Wind Harmer
2.865
276838X2-022 GEN2
Solar/Wind Harmer
0.34
276916AD2-100_GEN
Solar/Wind Harmer
26.732
276911AD2-131_GEN
Solar/Wind Harmer
5.403
274773LINCOLN ;4U
50/50
21.701
274774LINCOLN ;5U
50/50
21.701
274710KENDALL ;4C
50/50
3.125
274705KENDALL ;1S
50/50
1.896
972207SS24-0001
Solar/Wind Harmer
72.714
941551AE2-152 GEN
Solar/Wind Harmer
11.97
274745AC1-111 GEN9
Adder
14.573
274871GR RIDGE ;2U
Solar/Wind Harmer
19.954
274847GR RIDGE ;BU
Solar/Wind Harmer
13.12
962781AG1-127 GEN
Solar/Wind Harmer
23.836
274872LEEDK;1U
Solar/Wind Harmer
20.485
274682WAUKEGAN ;7U
Adder
44.398
274674JOLIET 9 ;6U
Adder
38.004
274828WAUKEGAN ;BP
Adder
27.229
274676JOLIET 29;8U
Adder
75.477
939401AE1-172 GEN
Solar/Wind Harmer
34.178
274732ELWOOD EC;7P
Adder
40.26
957471AF2-041 GEN
Solar/Wind Harmer
71.902
959081AF2-199 GEN
Solar/Wind Harmer
23.967
971067AG2-660 GEN
Solar/Wind Harmer
5.574
971997AH1-543 GEN
Solar/Wind Harmer
37.379
274822ROCKFORD ;11
Adder
46.543
970819AG2-516 GEN
Solar/Wind Harmer
28.133
276694AA1-018 GEN2
Solar/Wind Harmer
14.497
276691AA1-018 GEN1
Solar/Wind Harmer
1.733
276882AE2-255 GEN
Solar/Wind Harmer
7.739
274858EASY ROAD;U2
Solar/Wind Harmer
10.968
274761LEE CO EC;2U
Adder
21.299
274766LEE CO EC;7U
Adder
21.049
274861TOP CROP ;1U
Solar/Wind Harmer
13.847
274802UNIV PARK;5U
Adder
13.217
276805AD2-038 GEN
Solar/Wind Harmer
11.593
276708O09 GEN2
Solar/Wind Harmer
7.887
970569AG2-363 GEN
Solar/Wind Harmer
65.245
276646AC1-214 GEN2
Solar/Wind Harmer
2.841
274848CAMPGROVE;RU
Solar/Wind Harmer
13.416
274812UNIV PK N;8U
Adder
10.271
274723RIVER EC ;12
Adder
35.834
276655WTG1_EQ
Solar/Wind Harmer
17.28
276656WTG2_EQ
Solar/Wind Harmer
2.288
939741AE1-205 GEN
Solar/Wind Harmer
39.596
274751CRETE EC ;1U
Adder
8.729
274754CRETE EC ;4U
Adder
8.729
276686W4-005 GEN3
Solar/Wind Harmer
4.657
276621W2-048 GEN
Solar/Wind Harmer
9.122
965911AG1-460 GEN
Solar/Wind Harmer
1.832
274772LINCOLN ;3U
50/50
21.701
972259AH1-714 GEN
50/50
54.368
274707KENDALL ;2S
50/50
1.896
970707AG2-453 GEN
Solar/Wind Harmer
80.605
943121AE2-341 GEN
Solar/Wind Harmer
40.092
943591AF1-030 GEN
Solar/Wind Harmer
26.728
939351AE1-166 GEN
Solar/Wind Harmer
15.652
274682WAUKEGAN ;7U
Adder
44.398
274676JOLIET 29;8U
Adder
72.781
274729ELWOOD EC;1P
Adder
40.274
274730ELWOOD EC;6P
Adder
40.26
274734ELWOOD EC;8P
Adder
40.26
274736ELWOOD EC;9P
Adder
40.26
276799AD1-013 GEN
Solar/Wind Harmer
5.398
946671AF1-331 GEN
Solar/Wind Harmer
1.023
274855GSG-6 ;RU
Solar/Wind Harmer
9.005
274850MENDOTA H;RU
Solar/Wind Harmer
6.261
276602WESTBROOK C
Solar/Wind Harmer
5.184
274887GEN-1.85
Solar/Wind Harmer
12.835
276843GEN-1.7
Solar/Wind Harmer
1.381
276772AC2-154 GEN
Solar/Wind Harmer
6.723
276806AD2-047 C O1
Solar/Wind Harmer
25.77
959091AF2-200 GEN
Solar/Wind Harmer
47.934
972038AH1-567 GEN2
Adder
0.851
274826FISK ;BP
Adder
25.278
276868AE1-113 GEN
Solar/Wind Harmer
23.215
274879MINONK ;1U
Solar/Wind Harmer
15.477
274857EASY ROAD;U1
Solar/Wind Harmer
10.968
274760LEE CO EC;1U
Adder
21.299
274767LEE CO EC;8U
Adder
21.049
274862TOP CROP ;2U
Solar/Wind Harmer
11.562
276603SUBLETTE C
Solar/Wind Harmer
2.393
274803UNIV PARK;6U
Adder
13.217
276164X3-005 C
Solar/Wind Harmer
1.556
970571AG2-364 GEN
Solar/Wind Harmer
43.496
274851PROVIDENC;RU
Solar/Wind Harmer
6.042
274849CRESCENT ;1U
Solar/Wind Harmer
3.922
276782AC1-033 GEN
Solar/Wind Harmer
8.403
274878BISHOP HL;2U
Solar/Wind Harmer
7.109
965931AG1-462 GEN
Solar/Wind Harmer
53.077
971087AG2-675 GEN
Solar/Wind Harmer
7.745
274814UNIV PK N;0U
Adder
10.361
274807UNIV PK N;3U
Adder
10.338
274811UNIV PK N;7U
Adder
10.271
274724RIVER EC ;11
Adder
35.469
965091AG1-374 GEN
Solar/Wind Harmer
56.543
959611AF2-252 GEN
Solar/Wind Harmer
4.383
972231SS25-0005
Solar/Wind Harmer
16.949
972181SS23-001
Solar/Wind Harmer
10.593
274752CRETE EC ;2U
Adder
8.729
274753CRETE EC ;3U
Adder
8.729
276785W4-005 GEN1
Solar/Wind Harmer
4.657
971993AH1-541 GEN
Solar/Wind Harmer
14.23
957381AF2-032 GEN
Solar/Wind Harmer
2.656
942481AE2-261 GEN
Solar/Wind Harmer
39.265
274775LINCOLN ;6U
50/50
21.701
274776LINCOLN ;7U
50/50
21.701
274777LINCOLN ;8U
50/50
21.701
274708KENDALL ;3C
50/50
3.161
274661LASCO STA;2U
50/50
14.948
274660LASCO STA;1U
50/50
19.31
274704KENDALL ;1C
50/50
2.837
274706KENDALL ;2C
50/50
2.837
274744AC1-111 GEN8
Adder
14.573
274746AC1-111 G10
Adder
14.573
970833AG2-524 GEN
Solar/Wind Harmer
22.585
970833AG2-524 GEN
Solar/Wind Harmer
10.504
972227AH1-698 GEN1
Adder
6.559
972228AH1-698 GEN2
Adder
9.312
274675JOLIET 29;7U
Adder
75.485
274675JOLIET 29;7U
Adder
72.789
274731ELWOOD EC;2P
Adder
40.274
274733ELWOOD EC;3P
Adder
40.274
274735ELWOOD EC;4P
Adder
40.274
274728ELWOOD EC;5P
Adder
40.26
971675AH1-338 GEN
Solar/Wind Harmer
43.937
276861AD2-134 GEN
Solar/Wind Harmer
4.355
276863AD2-134 GEN
Solar/Wind Harmer
4.355
276893AG1-478 C
Solar/Wind Harmer
1.333
274687WILL CNTY;4U
Adder
67.677
274687WILL CNTY;4U
Adder
67.677
971411AH1-196 GEN
Solar/Wind Harmer
36.222
960591AF2-350 GEN
Solar/Wind Harmer
24.09
971171AH1-044 GEN
Solar/Wind Harmer
47.934
274823ROCKFORD ;21
Adder
46.206
274863CRW1-WTG
Solar/Wind Harmer
13.085
274864CRW2-WTG
Solar/Wind Harmer
13.085
274856ECOGROVE ;U1
Solar/Wind Harmer
7.878
276611AD2-172 GEN
Solar/Wind Harmer
5.976
276612AE2-035 GEN
Solar/Wind Harmer
5.976
274800UNIV PARK;3U
Adder
13.589
274801UNIV PARK;4U
Adder
13.589
274827FISK ;RP
Adder
17.915
971681AH1-341 GEN
Solar/Wind Harmer
34.624
972037AH1-567 GEN1
Adder
0.415
970073AG2-061 GEN
Solar/Wind Harmer
5.258
972267AH1-718 GEN
Adder
9.336
926823AC1-168 GEN
Solar/Wind Harmer
9.61
970169AG2-114 GEN
Solar/Wind Harmer
22.256
276889AE2-281 GEN
Solar/Wind Harmer
4.24
276741O09 GEN1
Solar/Wind Harmer
7.887
274877BISHOP HL;1U
Solar/Wind Harmer
7.109
946321AF1-296 GEN
Solar/Wind Harmer
21.969
276726Z2-087_GEN
Solar/Wind Harmer
15.655
959341AF2-225 GEN
Solar/Wind Harmer
29.697
274853TWINGROVE;U1
Solar/Wind Harmer
13.579
274854TWINGROVE;U2
Solar/Wind Harmer
13.294
276668AB2-070 GEN1
Solar/Wind Harmer
3.397
276848AB2-070 GEN3
Solar/Wind Harmer
3.397
276849AB2-070 GEN2
Solar/Wind Harmer
3.397
276763AC1-053 GEN1
Solar/Wind Harmer
5.974
276764AC1-053 GEN2
Solar/Wind Harmer
5.974
991777J1629 G
External Queue
26.092803955078125
990512J1326
External Queue
11.597373008728027
990117J1214
External Queue
39.894962310791016
990727J1377 G
External Queue
13.53684139251709
991092J1477
External Queue
6.156309127807617
991303J1755 G
External Queue
9.658561706542969
990407J1304
External Queue
8.994183540344238
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.471
NYPJM->LTFIMP_NY
CLTF
2.228
WECLTFEXP_WEC->PJM
CLTF
8.899
CBM West 1LTFEXP_CBM-W1->PJM
CBM
153.361
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.651
MECLTFEXP_MEC->PJM
CLTF
28.033
SIGELTFEXP_SIGE->PJM
CLTF
0.049
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.948
AG2-052LTFEXP_AG2-052->PJM
LTF
0.116
AH1-155LTFEXP_AH1-155->PJM
LTF
0.174
CBM West 2LTFEXP_CBM-W2->PJM
CBM
69.286
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.951
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.637
LAGNLTFEXP_LAGN->PJM
CLTF
9.359
TVALTFEXP_TVA->PJM
CLTF
2.41

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.96 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:4859.78
MW Contribution:
34.88
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.66 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:4712.39
MW Contribution:
33.97
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
21.811
274776LINCOLN ;7U
50/50
21.811
274777LINCOLN ;8U
50/50
21.811
274708KENDALL ;3C
50/50
3.17
274661LASCO STA;2U
50/50
14.978
274660LASCO STA;1U
50/50
19.348
274704KENDALL ;1C
50/50
2.84
274706KENDALL ;2C
50/50
2.84
274744AC1-111 GEN8
Adder
14.624
274746AC1-111 G10
Adder
14.624
970833AG2-524 GEN
Solar/Wind Harmer
22.67
970833AG2-524 GEN
Solar/Wind Harmer
10.544
972227AH1-698 GEN1
Adder
6.558
274772LINCOLN ;3U
50/50
21.811
972259AH1-714 GEN
50/50
54.475
274707KENDALL ;2S
50/50
1.898
970707AG2-453 GEN
Solar/Wind Harmer
80.887
943121AE2-341 GEN
Solar/Wind Harmer
40.247
943591AF1-030 GEN
Solar/Wind Harmer
26.831
939351AE1-166 GEN
Solar/Wind Harmer
15.726
274682WAUKEGAN ;7U
Adder
44.53
274676JOLIET 29;8U
Adder
72.751
276799AD1-013 GEN
Solar/Wind Harmer
5.43
946671AF1-331 GEN
Solar/Wind Harmer
1.029
274855GSG-6 ;RU
Solar/Wind Harmer
9.058
274850MENDOTA H;RU
Solar/Wind Harmer
6.298
276602WESTBROOK C
Solar/Wind Harmer
5.214
274729ELWOOD EC;1P
Adder
40.308
274730ELWOOD EC;6P
Adder
40.292
274734ELWOOD EC;8P
Adder
40.292
274736ELWOOD EC;9P
Adder
40.292
959091AF2-200 GEN
Solar/Wind Harmer
48.225
274887GEN-1.85
Solar/Wind Harmer
12.83
276772AC2-154 GEN
Solar/Wind Harmer
6.72
276843GEN-1.7
Solar/Wind Harmer
1.38
276806AD2-047 C O1
Solar/Wind Harmer
25.761
972038AH1-567 GEN2
Adder
0.849
276868AE1-113 GEN
Solar/Wind Harmer
23.365
274879MINONK ;1U
Solar/Wind Harmer
15.577
274857EASY ROAD;U1
Solar/Wind Harmer
11.05
274760LEE CO EC;1U
Adder
21.459
274767LEE CO EC;8U
Adder
21.207
274826FISK ;BP
Adder
25.205
276603SUBLETTE C
Solar/Wind Harmer
2.412
274862TOP CROP ;2U
Solar/Wind Harmer
11.586
274803UNIV PARK;6U
Adder
13.133
276164X3-005 C
Solar/Wind Harmer
1.551
970571AG2-364 GEN
Solar/Wind Harmer
43.954
274851PROVIDENC;RU
Solar/Wind Harmer
6.144
274849CRESCENT ;1U
Solar/Wind Harmer
3.988
276782AC1-033 GEN
Solar/Wind Harmer
8.541
274878BISHOP HL;2U
Solar/Wind Harmer
7.226
965931AG1-462 GEN
Solar/Wind Harmer
53.677
971087AG2-675 GEN
Solar/Wind Harmer
7.832
274814UNIV PK N;0U
Adder
10.156
274807UNIV PK N;3U
Adder
10.134
274811UNIV PK N;7U
Adder
10.068
274724RIVER EC ;11
Adder
35.292
965091AG1-374 GEN
Solar/Wind Harmer
59.107
959611AF2-252 GEN
Solar/Wind Harmer
4.582
972231SS25-0005
Solar/Wind Harmer
16.307
972181SS23-001
Solar/Wind Harmer
10.192
274752CRETE EC ;2U
Adder
8.398
274753CRETE EC ;3U
Adder
8.398
276785W4-005 GEN1
Solar/Wind Harmer
4.996
971993AH1-541 GEN
Solar/Wind Harmer
15.265
957381AF2-032 GEN
Solar/Wind Harmer
2.853
942481AE2-261 GEN
Solar/Wind Harmer
42.196
972228AH1-698 GEN2
Adder
9.309
274675JOLIET 29;7U
Adder
75.454
274675JOLIET 29;7U
Adder
72.759
971675AH1-338 GEN
Solar/Wind Harmer
44.192
276861AD2-134 GEN
Solar/Wind Harmer
4.38
276863AD2-134 GEN
Solar/Wind Harmer
4.38
274731ELWOOD EC;2P
Adder
40.308
274733ELWOOD EC;3P
Adder
40.308
274735ELWOOD EC;4P
Adder
40.308
274728ELWOOD EC;5P
Adder
40.292
971411AH1-196 GEN
Solar/Wind Harmer
36.405
274770LINCOLN ;1U
50/50
21.811
274771LINCOLN ;2U
50/50
21.811
274711KENDALL ;4S
50/50
2.095
274709KENDALL ;3S
50/50
2.095
276897AD1-100 C
Solar/Wind Harmer
123.181
274695ROCKY RD ;2P
Adder
28.21
274693ROCKY RD ;1P
Adder
27.932
274697ROCKY RD ;3P
Adder
7.663
274696ROCKY RD ;4P
Adder
28.872
962691AG1-118 GEN
Solar/Wind Harmer
75.93
960751AF2-366 GEN
Solar/Wind Harmer
7.226
274683WAUKEGAN ;8U
Adder
52.105
274683WAUKEGAN ;8U
Adder
43.922
274674JOLIET 9 ;6U
Adder
38.058
276893AG1-478 C
Solar/Wind Harmer
1.063
971341AH1-150 GEN
Solar/Wind Harmer
48.225
971343AH1-151 GEN
Solar/Wind Harmer
48.225
274888KELLY CRK;1U
Solar/Wind Harmer
14.21
276776AD2-060 GEN
Solar/Wind Harmer
1.008
958011AF2-095 GEN
Solar/Wind Harmer
34.676
970941AG2-585 GEN
Solar/Wind Harmer
13.244
972235AH1-702 GEN1
Adder
5.988
972236AH1-702 GEN2
Adder
5.207
276901AD2-066 C O1
Solar/Wind Harmer
8.205
938861AE1-114 GEN
Solar/Wind Harmer
19.044
274764LEE CO EC;5U
Adder
21.51
274765LEE CO EC;6U
Adder
21.51
274762LEE CO EC;3U
Adder
21.459
274763LEE CO EC;4U
Adder
21.257
958481AF2-142 GEN
Solar/Wind Harmer
34.545
958491AF2-143 GEN
Solar/Wind Harmer
34.072
276158O29GEN2
Solar/Wind Harmer
11.163
276157O29GEN1
Solar/Wind Harmer
8.487
276872AE1-163_GEN1
Solar/Wind Harmer
14.96
276876AE1-163_GEN2
Solar/Wind Harmer
14.96
276645AC1-214 GEN1
Solar/Wind Harmer
2.89
942111AE2-223 GEN
Solar/Wind Harmer
16.913
274805UNIV PK N;1U
Adder
10.09
274808UNIV PK N;4U
Adder
10.024
960611AF2-352 GEN
Solar/Wind Harmer
4.582
274880W4-005 GEN4
Solar/Wind Harmer
4.996
276174W4-005 GEN2
Solar/Wind Harmer
4.996
276615X2-022 GEN
Solar/Wind Harmer
3.075
276838X2-022 GEN2
Solar/Wind Harmer
0.365
276916AD2-100_GEN
Solar/Wind Harmer
28.764
276911AD2-131_GEN
Solar/Wind Harmer
5.813
274773LINCOLN ;4U
50/50
21.811
274774LINCOLN ;5U
50/50
21.811
274710KENDALL ;4C
50/50
3.134
274705KENDALL ;1S
50/50
1.898
972207SS24-0001
Solar/Wind Harmer
73.081
941551AE2-152 GEN
Solar/Wind Harmer
12.027
274745AC1-111 GEN9
Adder
14.624
274871GR RIDGE ;2U
Solar/Wind Harmer
20.031
274847GR RIDGE ;BU
Solar/Wind Harmer
13.171
962781AG1-127 GEN
Solar/Wind Harmer
23.952
274872LEEDK;1U
Solar/Wind Harmer
20.59
939401AE1-172 GEN
Solar/Wind Harmer
34.725
274682WAUKEGAN ;7U
Adder
44.53
274828WAUKEGAN ;BP
Adder
27.312
274674JOLIET 9 ;6U
Adder
38.058
274676JOLIET 29;8U
Adder
75.446
274732ELWOOD EC;7P
Adder
40.292
957471AF2-041 GEN
Solar/Wind Harmer
72.337
959081AF2-199 GEN
Solar/Wind Harmer
24.112
971067AG2-660 GEN
Solar/Wind Harmer
5.608
971997AH1-543 GEN
Solar/Wind Harmer
37.729
274822ROCKFORD ;11
Adder
46.814
970819AG2-516 GEN
Solar/Wind Harmer
28.308
276882AE2-255 GEN
Solar/Wind Harmer
7.788
274858EASY ROAD;U2
Solar/Wind Harmer
11.05
274761LEE CO EC;2U
Adder
21.459
274766LEE CO EC;7U
Adder
21.207
276694AA1-018 GEN2
Solar/Wind Harmer
14.531
276691AA1-018 GEN1
Solar/Wind Harmer
1.737
274861TOP CROP ;1U
Solar/Wind Harmer
13.876
276805AD2-038 GEN
Solar/Wind Harmer
11.648
274802UNIV PARK;5U
Adder
13.133
276708O09 GEN2
Solar/Wind Harmer
7.97
970569AG2-363 GEN
Solar/Wind Harmer
65.932
276646AC1-214 GEN2
Solar/Wind Harmer
2.89
274848CAMPGROVE;RU
Solar/Wind Harmer
13.659
276655WTG1_EQ
Solar/Wind Harmer
18.007
276656WTG2_EQ
Solar/Wind Harmer
2.384
939741AE1-205 GEN
Solar/Wind Harmer
41.263
274812UNIV PK N;8U
Adder
10.068
274723RIVER EC ;12
Adder
35.624
274751CRETE EC ;1U
Adder
8.398
274754CRETE EC ;4U
Adder
8.398
276686W4-005 GEN3
Solar/Wind Harmer
4.996
276621W2-048 GEN
Solar/Wind Harmer
9.791
965911AG1-460 GEN
Solar/Wind Harmer
1.969
276893AG1-478 C
Solar/Wind Harmer
1.334
274687WILL CNTY;4U
Adder
67.613
274687WILL CNTY;4U
Adder
67.613
971171AH1-044 GEN
Solar/Wind Harmer
48.225
960591AF2-350 GEN
Solar/Wind Harmer
24.081
274863CRW1-WTG
Solar/Wind Harmer
13.355
274864CRW2-WTG
Solar/Wind Harmer
13.355
274823ROCKFORD ;21
Adder
46.475
274856ECOGROVE ;U1
Solar/Wind Harmer
7.93
276611AD2-172 GEN
Solar/Wind Harmer
6.015
276612AE2-035 GEN
Solar/Wind Harmer
6.015
274800UNIV PARK;3U
Adder
13.568
274801UNIV PARK;4U
Adder
13.568
971681AH1-341 GEN
Solar/Wind Harmer
34.882
274827FISK ;RP
Adder
17.863
970169AG2-114 GEN
Solar/Wind Harmer
22.822
970073AG2-061 GEN
Solar/Wind Harmer
5.283
926823AC1-168 GEN
Solar/Wind Harmer
9.744
972267AH1-718 GEN
Adder
9.416
972037AH1-567 GEN1
Adder
0.412
276741O09 GEN1
Solar/Wind Harmer
7.97
276889AE2-281 GEN
Solar/Wind Harmer
4.274
274877BISHOP HL;1U
Solar/Wind Harmer
7.226
946321AF1-296 GEN
Solar/Wind Harmer
22.21
276726Z2-087_GEN
Solar/Wind Harmer
16.313
959341AF2-225 GEN
Solar/Wind Harmer
30.947
274853TWINGROVE;U1
Solar/Wind Harmer
14.195
274854TWINGROVE;U2
Solar/Wind Harmer
13.897
276668AB2-070 GEN1
Solar/Wind Harmer
3.647
276848AB2-070 GEN3
Solar/Wind Harmer
3.647
276849AB2-070 GEN2
Solar/Wind Harmer
3.647
276763AC1-053 GEN1
Solar/Wind Harmer
6.413
276764AC1-053 GEN2
Solar/Wind Harmer
6.413
991777J1629 G
External Queue
26.21718406677246
990512J1326
External Queue
11.6556978225708
990117J1214
External Queue
40.09560012817383
990727J1377 G
External Queue
13.596264839172363
991092J1477
External Queue
6.257870674133301
991303J1755 G
External Queue
9.865641593933105
990407J1304
External Queue
9.029948234558105
NYPJM->LTFIMP_NY
CLTF
2.203
WECLTFEXP_WEC->PJM
CLTF
8.944
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.911
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
154.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.041
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.924
MECLTFEXP_MEC->PJM
CLTF
28.487
SIGELTFEXP_SIGE->PJM
CLTF
0.04
AG2-052LTFEXP_AG2-052->PJM
LTF
0.117
AH1-155LTFEXP_AH1-155->PJM
LTF
0.175
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.875
LAGNLTFEXP_LAGN->PJM
CLTF
9.694
TVALTFEXP_TVA->PJM
CLTF
2.523
CONTINGENCY 'AP_P2-3_PE-765-237806-SB1_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 1           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237806-SB2_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REMOVE SWSHUNT FROM BUS 237806 BLOCK 1 STEP 2           /*01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB6_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB5_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1          /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 242508 TO BUS 237805 CKT 1 /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB3_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-237805-237806_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 237805 TO BUS 237806 CKT 1   /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-2_PE-765-242508-237805_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1   /*05AMOS       765.0 - 01WELTON_SPR 765.0
END
CONTINGENCY 'AEP_P4_#GREENTOWN-TEDDY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 243207 TO BUS 248105 CKT 1   /*05GRNTWN     765.0 - 05GREENTW_RM 765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248102 CKT 1   /*05TEDDY_RG   765.0 - 05TEDDY      765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248105 CKT 1   /*05TEDDY_RG   765.0 - 05GREENTW_RM 765.0
END
CONTINGENCY 'AEP_P4_#2979_05DUMONT 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290597 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290597 CKT 1    /*05GRNTWN     765.0 - 05DUMONT_RG  765.0
END
CONTINGENCY 'COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A'
 TRIP BRANCH FROM BUS 274750 TO BUS 255112 CKT 1   /*CRETE EC ;BP 345.0 - 17STJOHN     345.0
 TRIP BRANCH FROM BUS 274804 TO BUS 255201 CKT 1   /*UNIV PK N;RP 345.0 - 17P9701-WEST 345.0
END
CONTINGENCY 'AP_P2-3_PE-765-237805-SB4_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 242508 TO BUS 237805 CKT 1          /*05AMOS       765.0 - 01WELTON_SPR 765.0
 REDUCE BUS 237805 SHUNT BY 50 PERCENT                          /*01WELTON_SPR 765.0
 SET PRECONTRATING 6392 BRANCH FROM BUS 237805 TO BUS 237806 CKT 1 /*01WELTON_SPR 765.0 - 01ROCKYPOINT 765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P1-2_#AG1-125-ADKINS_SRT-A_SENS'
 OPEN BRANCH FROM BUS 962760 TO BUS 248125 CKT 1   /*AG1-125 TP   765.0 - 05ADKINS     765.0
END
CONTINGENCY 'AEP_P1-2_#XXXX_GREENTOWN_TEDDY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 243207 TO BUS 248105 CKT 1   /*05GRNTWN     765.0 - 05GREENTW_RM 765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248102 CKT 1   /*05TEDDY_RG   765.0 - 05TEDDY      765.0
 OPEN BRANCH FROM BUS 248104 TO BUS 248105 CKT 1   /*05TEDDY_RG   765.0 - 05GREENTW_RM 765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#TEDDY MARY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 242928 TO BUS 248102 CKT 1   /*05MARYSV     765.0 - 05TEDDY      765.0
END
CONTINGENCY 'AEP_P4_05MARYSV 765_C2_SRT-A_SENS'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2   /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 248102 CKT 1   /*05MARYSV     765.0 - 05TEDDY      765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290598 TO BUS 290599 CKT 1    /*05GREENTW_RJ 765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P7-1_#11010___SRT-A'
 OPEN BRANCH FROM BUS 242933 TO BUS 243211 CKT 1   /*05RPMONE     345.0 - 05ALLEN      345.0
 OPEN BRANCH FROM BUS 243211 TO BUS 243232 CKT 1   /*05ALLEN      345.0 - 05SORENS     345.0
END
CONTINGENCY 'AEP_P1-2_#9287_1679_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290597 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290597 CKT 1    /*05GRNTWN     765.0 - 05DUMONT_RG  765.0
END
CONTINGENCY 'AEP_P7-1_#11087___SRT-A-1'
 OPEN BRANCH FROM BUS 243218 TO BUS 288691 CKT 1   /*05DESOTO     345.0 - 05WHIPPLEDTC 345.0
 OPEN BRANCH FROM BUS 243218 TO BUS 958860 CKT 2   /*05DESOTO     345.0 - AF2-177 TP   345.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 290602 CKT 1   /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 290602 CKT 1   /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'AEP_P4_#1750_05DUMONT 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243219 CKT 3    /*05DUMONT     765.0 - 05DUMONT     345.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290602 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 270644 TO BUS 290602 CKT 1    /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290597 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290602 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290597 CKT 1    /*05GRNTWN     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 270644 TO BUS 290602 CKT 1    /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
END
CONTINGENCY 'AEP_P1-2_#695_1681_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290602 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 270644 TO BUS 290602 CKT 1    /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
END
CONTINGENCY '765-L11215__-S_SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 290602 CKT 1   /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
END
CONTINGENCY 'AEP_P4_#2973_05DUMONT 345_F1_SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 255113 CKT 1   /*05DUMONT     345.0 - 17STILLWELL  345.0
END
CONTINGENCY 'AEP_P4_#8805_05OLIVE 345_D_SRT-A-1'
 OPEN BRANCH FROM BUS 243229 TO BUS 960680 CKT 1   /*05OLIVE      345.0 - AF2-359 TP   345.0
 OPEN BRANCH FROM BUS 243229 TO BUS 970372 CKT 1   /*05OLIVE      345.0 - AG2-245 TP   345.0
END
CONTINGENCY 'AEP_P7-1_#11009___SRT-A-1'
 OPEN BRANCH FROM BUS 243229 TO BUS 255199 CKT 1   /*05OLIVE      345.0 - 17P9700-EAST 345.0
 OPEN BRANCH FROM BUS 243229 TO BUS 960680 CKT 1   /*05OLIVE      345.0 - AF2-359 TP   345.0
 OPEN BRANCH FROM BUS 255104 TO BUS 255199 CKT 1   /*17GREEN_ACRE 345.0 - 17P9700-EAST 345.0
END
CONTINGENCY 'AEP_P7-1_#11009___SRT-A-2'
 OPEN BRANCH FROM BUS 243229 TO BUS 255199 CKT 1   /*05OLIVE      345.0 - 17P9700-EAST 345.0
 OPEN BRANCH FROM BUS 255104 TO BUS 255199 CKT 1   /*17GREEN_ACRE 345.0 - 17P9700-EAST 345.0
 OPEN BRANCH FROM BUS 960680 TO BUS 255112 CKT 1   /*AF2-359 TP   345.0 - 17STJOHN     345.0
END
CONTINGENCY 'AEP_P4_#18494_05LARRISN DR 345_CB1_SRT-A_SENS'
 OPEN BRANCH FROM BUS 243918 TO BUS 289013 CKT 1   /*05ELDERBERRY 345.0 - 05LARRISN DR 345.0
END
CONTINGENCY 'AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A_SENS'
 OPEN BRANCH FROM BUS 243918 TO BUS 289013 CKT 1   /*05ELDERBERRY 345.0 - 05LARRISN DR 345.0
END
CONTINGENCY 'COMED_P4_023-65-BT3-4___SRT-A'
 TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1   /*COLLINS  ;   765.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ; R 345.0
 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;2C  33.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-022T_SRT-A_SENS'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 264594 CKT 1   /*02LEMOYN     345.0 - 19LULU       345.0
 DISCONNECT BRANCH FROM BUS 241901 TO BUS 264612 CKT 1   /*02LALLENDORF 345.0 - 19MON12      345.0
END
CONTINGENCY 'AEP_P4_#3128_05EUGENE 345_A2_SRT-A'
 OPEN BRANCH FROM BUS 243221 TO BUS 249504 CKT 1   /*05EUGENE     345.0 - 08CAYSUB     345.0
 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1   /*05EUGENE     345.0 - 7BUNSONVILLE 345.0
END
CONTINGENCY 'AEP_P2-2_#286_05EUGENE 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1   /*05EUGENE     345.0 - 7BUNSONVILLE 345.0
END
CONTINGENCY 'COMED_P4_023-65-BT2-3___SRT-A'
 TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1   /*COLLINS  ;   765.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
END
CONTINGENCY 'COMED_P4_023-65-BT4-5___SRT-A'
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ; R 345.0
 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;2C  33.0
END
CONTINGENCY 'COMED_P4_006-45-BT3-8___SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 270679 CKT Z1   /*BYRON    ; B 345.0 - BYRON    ; R 345.0
 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1    /*LEE CO EC;BP 345.0 - BYRON    ; B 345.0
END
CONTINGENCY 'COMED_P4_006-45-BT3-4___SRT-A'
 REMOVE UNIT 1 FROM BUS 274656                     /*BYRON    ;1U  25.0
 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1   /*LEE CO EC;BP 345.0 - BYRON    ; B 345.0
END
CONTINGENCY 'COMED_P4-6_006-345-BT78___SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 270679 CKT Z1   /*BYRON    ; B 345.0 - BYRON    ; R 345.0
 TRIP BRANCH FROM BUS 270678 TO BUS 270916 CKT 1    /*BYRON    ; B 345.0 - WAYNE    ; B 345.0
END
CONTINGENCY 'COMED_P4_144-45-BT5-8___SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 270916 CKT 1    /*BYRON    ; B 345.0 - WAYNE    ; B 345.0
 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT Z1   /*WAYNE    ; B 345.0 - WAYNE    ; R 345.0
END
CONTINGENCY 'COMED_P4_144-45-BT7-8___SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 270916 CKT 1   /*BYRON    ; B 345.0 - WAYNE    ; B 345.0
 TRIP BRANCH FROM BUS 270916 TO BUS 270900 CKT 1   /*WAYNE    ; B 345.0 - TOLLWAY ; B  345.0
 TRIP BRANCH FROM BUS 275228 TO BUS 270916 CKT 1   /*WAYNE    ;1M 138.0 - WAYNE    ; B 345.0
 TRIP BRANCH FROM BUS 275228 TO BUS 272740 CKT 1   /*WAYNE    ;1M 138.0 - WAYNE    ; B 138.0
 TRIP BRANCH FROM BUS 275228 TO BUS 275328 CKT 1   /*WAYNE    ;1M 138.0 - WAYNE    ;1C  34.5
END
CONTINGENCY 'COMED_P2-2_154_LV-345R__3_SRT-A'
 DISCONNECT BUS 275194                             /*LIBERTYVI;1M 138.0
 TRIP BRANCH FROM BUS 270807 TO BUS 270883 CKT 1   /*LIBERTYVI; R 345.0 - SILVER LK; R 345.0
END
CONTINGENCY 'COMED_P4_111-45-TR81____SRT-A'
 DISCONNECT BUS 270732                             /*ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 275182 TO BUS 270732 CKT 1   /*ELECT JCT;1M 138.0 - ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 275182 TO BUS 271392 CKT 1   /*ELECT JCT;1M 138.0 - ELECT JCT;1B 138.0
 TRIP BRANCH FROM BUS 275182 TO BUS 275282 CKT 1   /*ELECT JCT;1M 138.0 - ELECT JCT;1C  34.5
END
CONTINGENCY 'COMED_P4_111-45-L11124__SRT-A'
 DISCONNECT BUS 270732                             /*ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 270732 TO BUS 270814 CKT 1   /*ELECT JCT;1B 345.0 - LOMBARD  ;4B 345.0
END
CONTINGENCY 'COMED_P2-2_111_EJ-345B__1_SRT-A'
 DISCONNECT BUS 270732   /*ELECT JCT;1B 345.0
END
CONTINGENCY 'COMED_P1-2_345-L0626__B-R_SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 270916 CKT 1   /*BYRON    ; B 345.0 - WAYNE    ; B 345.0
END
CONTINGENCY 'COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A'
 TRIP BRANCH FROM BUS 270728 TO BUS 274750 CKT 1   /*E FRANKFO; B 345.0 - CRETE EC ;BP 345.0
 TRIP BRANCH FROM BUS 274804 TO BUS 255201 CKT 1   /*UNIV PK N;RP 345.0 - 17P9701-WEST 345.0
END
CONTINGENCY 'COMED_P4-6_111-345-R______SRT-A'
 DISCONNECT BUS 270731   /*ELECT JCT;4R 345.0
 DISCONNECT BUS 270733   /*ELECT JCT;3R 345.0
 DISCONNECT BUS 275183   /*ELECT JCT;3M 138.0
 DISCONNECT BUS 275184   /*ELECT JCT;4M 138.0
END
CONTINGENCY 'COMED_P2-2_111_EJ-345R__3_SRT-A'
 DISCONNECT BUS 270733   /*ELECT JCT;3R 345.0
 DISCONNECT BUS 275183   /*ELECT JCT;3M 138.0
END
CONTINGENCY 'COMED_P4_120-45-L12002__SRT-A'
 DISCONNECT BUS 270813                             /*LOMBARD  ;2R 345.0
 DISCONNECT BUS 275198                             /*LOMBARD  ;2M 138.0
 TRIP BRANCH FROM BUS 275191 TO BUS 270781 CKT 1   /*ITASCA   ;2M 138.0 - ITASCA   ; R 345.0
 TRIP BRANCH FROM BUS 275191 TO BUS 271735 CKT 1   /*ITASCA   ;2M 138.0 - ITASCA   ; R 138.0
 TRIP BRANCH FROM BUS 275191 TO BUS 275291 CKT 1   /*ITASCA   ;2M 138.0 - ITASCA   ;2C  34.5
END
CONTINGENCY 'COMED_P4_111-45-L11120__SRT-A'
 DISCONNECT BUS 270733                                 /*ELECT JCT;3R 345.0
 DISCONNECT BUS 275183                                 /*ELECT JCT;3M 138.0
 MOVE 100 PERCENT LOAD FROM BUS 270749 TO BUS 270751   /*ESS W407M; R 345.0 - ESS W407M;9T 345.0
 TRIP BRANCH FROM BUS 270733 TO BUS 270747 CKT 1       /*ELECT JCT;3R 345.0 - ESS W407K;0T 345.0
 TRIP BRANCH FROM BUS 270747 TO BUS 270753 CKT 1       /*ESS W407K;0T 345.0 - ESS W407M;0T 345.0
 TRIP BRANCH FROM BUS 270753 TO BUS 270749 CKT 1       /*ESS W407M;0T 345.0 - ESS W407M; R 345.0
 TRIP BRANCH FROM BUS 270753 TO BUS 270813 CKT 1       /*ESS W407M;0T 345.0 - LOMBARD  ;2R 345.0
END
CONTINGENCY 'COMED_P4_120-45-L10322__SRT-A'
 DISCONNECT BUS 270813   /*LOMBARD  ;2R 345.0
 DISCONNECT BUS 275198   /*LOMBARD  ;2M 138.0
END
CONTINGENCY 'COMED_P2-2_120_LO-345R__2_SRT-A'
 DISCONNECT BUS 270813   /*LOMBARD  ;2R 345.0
 DISCONNECT BUS 275198   /*LOMBARD  ;2M 138.0
END
CONTINGENCY 'COMED_P4_120-45-L11120__SRT-A'
 DISCONNECT BUS 270813                                 /*LOMBARD  ;2R 345.0
 DISCONNECT BUS 275198                                 /*LOMBARD  ;2M 138.0
 MOVE 100 PERCENT LOAD FROM BUS 270749 TO BUS 270751   /*ESS W407M; R 345.0 - ESS W407M;9T 345.0
 TRIP BRANCH FROM BUS 270733 TO BUS 270747 CKT 1       /*ELECT JCT;3R 345.0 - ESS W407K;0T 345.0
 TRIP BRANCH FROM BUS 270747 TO BUS 270753 CKT 1       /*ESS W407K;0T 345.0 - ESS W407M;0T 345.0
 TRIP BRANCH FROM BUS 270753 TO BUS 270749 CKT 1       /*ESS W407M;0T 345.0 - ESS W407M; R 345.0
END
CONTINGENCY 'COMED_P4-6_111-345-B______SRT-A'
 DISCONNECT BUS 270730                                          /*ELECT JCT;2B 345.0
 DISCONNECT BUS 270732                                          /*ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 270928 TO BUS 272794 TO BUS 275334 CKT 1  /*WOLFS    ; B 345.0 - WOLFS    ; B 138.0 - WOLFS    ;1C  34.5
END
CONTINGENCY 'COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-2'
 CLOSE LINE FROM BUS 272114 TO BUS 272115 CKT Z1       /*N AURORA ; B 138.0 - N AURORA ; R 138.0
 MOVE 100 PERCENT LOAD FROM BUS 271586 TO BUS 271587   /*ESS W541 ; B 138.0 - ESS W541 ; R 138.0
 MOVE 100 PERCENT LOAD FROM BUS 272522 TO BUS 272523   /*SUGAR GRV; B 138.0 - SUGAR GRV; R 138.0
 TRIP BRANCH FROM BUS 271390 TO BUS 271586 CKT 1       /*ELECT JCT;2B 138.0 - ESS W541 ; B 138.0
 TRIP BRANCH FROM BUS 271586 TO BUS 272114 CKT 1       /*ESS W541 ; B 138.0 - N AURORA ; B 138.0
 TRIP BRANCH FROM BUS 272114 TO BUS 272522 CKT 1       /*N AURORA ; B 138.0 - SUGAR GRV; B 138.0
 TRIP BRANCH FROM BUS 272522 TO BUS 962690 CKT 1       /*SUGAR GRV; B 138.0 - AG1-118 TP   138.0
 TRIP BRANCH FROM BUS 957470 TO BUS 270732 CKT 1       /*AF2-041 TP   345.0 - ELECT JCT;1B 345.0
END
CONTINGENCY 'AEP_P4_#2976_05DUMONT 345_F_SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 243234 CKT 1   /*05DUMONT     345.0 - 05TWIN B     345.0
 OPEN BRANCH FROM BUS 243219 TO BUS 255113 CKT 1   /*05DUMONT     345.0 - 17STILLWELL  345.0
END
290610 to 242512 ckt Z1
243206 to 290606 ckt Z1
290602 to 243206 ckt Z1
242514 to 290610 ckt 1
290623 to 242925 ckt Z1
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
255199 to 243229 ckt 1
255113 to 243219 ckt 1
255112 to 960680 ckt 1
256583 to 238530 ckt 1
346810 to 247712 ckt 1
276896 to 270926 ckt 1
957470 to 270732 ckt 1
960580 to 270883 ckt 1
960680 to 243229 ckt 1
270674 to 255111 ckt 1
270677 to 255109 ckt 1
270694 to 960580 ckt 1
274750 to 255112 ckt 1
270732 to 270814 ckt 1
272516 to 271680 ckt 1
274804 to 255201 ckt 1
272730 to 272445 ckt 1
270644 to 290602 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC113.4 %1683.0B1908.5
5.68
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC116.27 %1892.0B2199.92
4.88
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC115.8 %1892.0B2190.94
4.9
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC115.9 %1878.0B2176.69
5.0
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC115.49 %1878.0B2168.95
5.01
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC110.65 %1737.0B1922.03
7.98
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
BreakerAC107.18 %2320.0B2486.65
7.0
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC104.78 %2320.0B2430.97
5.24
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.13 %3393.4B4008.49
9.91
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC129.08 %5001.0B6455.24
28.52
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC116.27 %5001.0B5814.76
25.93
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC115.38 %5001.0B5769.93
27.82
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC115.14 %5001.0B5758.3
25.99
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P7-1_#11046___SRT-A
TowerAC112.82 %5001.0B5642.02
25.45
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#17234_05GRNTWN 765_N_SRT-A
BreakerAC110.82 %5001.0B5542.35
26.95
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P7-1_#11001___SRT-A
TowerAC110.75 %5001.0B5538.46
25.45
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P2-2_#6229_05MERIDN 345_1_SRT-A
BusAC106.21 %5001.0B5311.53
24.23
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P2-2_#702_05JEFRSO 765_2_SRT-A
BusAC104.53 %5001.0B5227.77
23.77
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC116.88 %5523.0B6455.24
28.52
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC105.28 %5523.0B5814.76
25.93
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC104.47 %5523.0B5769.93
27.82
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC104.26 %5523.0B5758.3
25.99
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P7-1_#11046___SRT-A
TowerAC102.16 %5523.0B5642.02
25.45
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#17234_05GRNTWN 765_N_SRT-A
BreakerAC100.35 %5523.0B5542.35
26.95
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P7-1_#11001___SRT-A
TowerAC100.28 %5523.0B5538.46
25.45
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC115.16 %1868.0B2151.12
9.09
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC114.59 %1868.0B2140.55
9.69
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC114.59 %1868.0B2140.55
9.69
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#671_05COOK 345_M2_SRT-A
BreakerAC104.8 %1868.0B1957.75
7.1
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#6560_05COOK 345_M_SRT-A
BreakerAC104.7 %1868.0B1955.71
7.1
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
AEP_P7-1_#10997___SRT-A
TowerAC104.69 %1868.0B1955.69
7.1
GD2AEP
05GAVIN-05MOUNTN 765.0 kV Ckt 1 line
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
BreakerAC121.81 %4571.0B5567.74
15.48
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#709_546_SRT-A
SingleAC105.58 %3039.0B3208.68
8.8
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC113.16 %2826.0B3197.84
8.8
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC111.91 %2246.0B2513.45
7.65
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC127.9 %4142.0B5297.56
13.51
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC108.0 %4142.0B4473.55
14.13
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#711_05MARYSV 765_A1_SRT-A
BreakerAC107.43 %3097.0B3327.22
7.43
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC107.32 %3097.0B3323.76
7.31
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC107.32 %3097.0B3323.61
7.31
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC107.26 %3097.0B3321.91
7.31
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC107.26 %3097.0B3321.72
7.31
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC107.23 %3097.0B3320.78
7.3
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#711_6224_SRT-A
SingleAC101.73 %3097.0B3150.57
5.56
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
SingleAC101.63 %3097.0B3147.5
5.48
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.31 %4571.0B5773.71
13.56
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
BusAC117.25 %4571.0B5359.3
15.41
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
SingleAC111.01 %4571.0B5074.41
11.54
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Base Case
SingleAC110.62 %4047.0A4476.89
11.16
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC126.34 %4571.0B5774.92
13.56
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
BusAC117.48 %4571.0B5369.79
15.41
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
SingleAC111.24 %4571.0B5084.88
11.54
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Base Case
SingleAC110.76 %4047.0A4482.29
11.16
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Base Case
SingleAC120.76 %4047.0A4887.22
18.31
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC116.4 %5523.0B6428.58
14.63
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC109.18 %4558.0A4976.63
10.12
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.76 %5523.0B5896.19
12.31
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC122.25 %1868.0B2283.58
7.74
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P1-2_#7442_200545_SRT-A
SingleAC103.01 %3097.0B3190.2
11.4
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC120.41 %5523.0B6649.99
11.09
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC110.78 %5523.0B6118.43
27.72
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC109.5 %5523.0B6047.92
27.79
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.53 %5523.0B5607.44
20.81
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-027A_SRT-A
TowerAC100.15 %5523.0B5531.21
23.36
GD2AEP
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC109.63 %6066.0B6649.99
11.09
GD2AEP
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC100.98 %6066.0B6125.38
27.72
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC112.63 %2317.0B2609.67
5.37
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC141.94 %1540.0B2185.8
5.61
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC133.27 %1540.0B2052.4
4.91
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
BusAC106.62 %1841.0B1962.84
10.49
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A
BusAC100.88 %1841.0B1857.18
10.58
GD2ATSI/ITCT
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
ATSI_P7-1_TE-345-025T_SRT-A
TowerAC122.24 %1660.0B2029.25
7.62
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P2-2_116_GG-345R__2_SRT-A
BusAC100.01 %1837.0STE1837.1
19.53
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC128.82 %1868.0B2406.35
7.74
GD2CE
COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line
COMED_P4_167-65-BT4-5___SRT-A
BreakerAC105.28 %1469.0STE1546.53
11.72
GD2CE
COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line
COMED_P4_167-65-BT3-4___SRT-A
BreakerAC105.28 %1469.0STE1546.53
11.72
GD2CE
COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_167-65-BT4-5___SRT-A
BreakerAC105.44 %1469.0STE1548.9
11.72
GD2CE
COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_167-65-BT3-4___SRT-A
BreakerAC105.44 %1469.0STE1548.9
11.72
GD2CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4-6_116-345-R______SRT-A
BreakerAC113.48 %2297.0STE2606.61
12.31
GD2CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_116-45-L11614__SRT-A
BreakerAC110.83 %2297.0STE2545.8
10.56
GD2CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_116-45-TR82____SRT-A
BreakerAC105.84 %2297.0STE2431.22
10.58
GD2CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P2-2_116_GG-345R__2_SRT-A
BusAC105.84 %2297.0STE2431.21
10.58
GD2CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_116-45-L0303___SRT-A
BreakerAC101.9 %2297.0STE2340.63
10.59
GD2CE
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC112.66 %1469.0STE1654.96
11.35
GD2CE
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT2-3___SRT-A
BreakerAC111.3 %1469.0STE1635.05
11.35
GD2CE
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT4-5___SRT-A
BreakerAC111.3 %1469.0STE1635.01
11.35
GD2CE
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC112.75 %1469.0STE1656.29
11.31
GD2CE
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT2-3___SRT-A
BreakerAC110.9 %1469.0STE1629.1
11.31
GD2CE
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT4-5___SRT-A
BreakerAC110.9 %1469.0STE1629.08
11.31
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
BusAC105.72 %4460.0B4715.14
33.66
GD2CE
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC112.89 %1469.0STE1658.32
11.35
GD2CE
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT2-3___SRT-A
BreakerAC111.43 %1469.0STE1636.94
11.35
GD2CE
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT4-5___SRT-A
BreakerAC111.43 %1469.0STE1636.9
11.35
GD2CE
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC112.93 %1469.0STE1658.94
11.31
GD2CE
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT2-3___SRT-A
BreakerAC110.99 %1469.0STE1630.47
11.31
GD2CE
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT4-5___SRT-A
BreakerAC110.99 %1469.0STE1630.44
11.31

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.4 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:1908.5
MW Contribution:
5.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
5.546
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.525
970621AG2-405 GEN
Solar/Wind Harmer
0.945
944231AF1-091 GEN
Solar/Wind Harmer
11.69
970623AG2-406 GEN
Solar/Wind Harmer
0.886
961051AF2-396 GEN
Solar/Wind Harmer
9.383
961051AF2-396 GEN
Solar/Wind Harmer
6.256
246937BC-WTG2
Solar/Wind Harmer
0.187
247607V1-011 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.296
270246TR4_N_V150
Solar/Wind Harmer
0.028
270247TR4_N_V136
Solar/Wind Harmer
0.028
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
5.151
965791AG1-447 GEN
Solar/Wind Harmer
3.777
970349AG2-230 GEN
Solar/Wind Harmer
6.147
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.728
274808UNIV PK N;4U
Adder
2.71
274888KELLY CRK;1U
Solar/Wind Harmer
0.218
276776AD2-060 GEN
Solar/Wind Harmer
0.398
958011AF2-095 GEN
Solar/Wind Harmer
5.377
970941AG2-585 GEN
Solar/Wind Harmer
2.054
274770LINCOLN ;1U
Adder
4.514
274771LINCOLN ;2U
Adder
4.514
276897AD1-100 C
Solar/Wind Harmer
9.25
276893AG1-478 C
Solar/Wind Harmer
0.247
274674JOLIET 9 ;6U
Adder
8.16
958481AF2-142 GEN
Solar/Wind Harmer
5.484
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
1.462
274696ROCKY RD ;4P
Adder
5.935
274695ROCKY RD ;2P
Adder
5.798
274693ROCKY RD ;1P
Adder
5.741
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.968
274683WAUKEGAN ;8U
Adder
9.245
958491AF2-143 GEN
Solar/Wind Harmer
5.438
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
10.839
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
7.132
971343AH1-151 GEN
Solar/Wind Harmer
7.132
972235AH1-702 GEN1
Adder
1.284
972236AH1-702 GEN2
Adder
1.116
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.397
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.564
942111AE2-223 GEN
Solar/Wind Harmer
1.128
944541AF1-119 GEN
Solar/Wind Harmer
0.23
960971AF2-388 GEN
Solar/Wind Harmer
2.023
960611AF2-352 GEN
Solar/Wind Harmer
1.144
970241AG2-163 GEN
Solar/Wind Harmer
1.971
270031AE2-169
Solar/Wind Harmer
1.849
270599AE1-208 GEN
Solar/Wind Harmer
3.081
270201AC2-176 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.434
970291AG2-192 GEN
Solar/Wind Harmer
0.2
964611AG1-324 GEN
Solar/Wind Harmer
0.25
247621Y3-024
Adder
0.115
971613AH1-306 GEN
Solar/Wind Harmer
1.591
276615X2-022 GEN
Solar/Wind Harmer
0.034
276838X2-022 GEN2
Solar/Wind Harmer
0.185
25326509SID D
Adder
0.616
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
1.397
276916AD2-100_GEN
Solar/Wind Harmer
6.713
276911AD2-131_GEN
Solar/Wind Harmer
0.442
970883AG2-550 GEN
Solar/Wind Harmer
3.196
970885AG2-551 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
3.366
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
203835AF1-098 GEN
Solar/Wind Helper
1.351
241967AE2-285_GEN
Solar/Wind Helper
0.345
241801AE1-079 GEN
Solar/Wind Helper
0.135
254304AE2-114 C
Solar/Wind Helper
0.114
254305AE2-115 C
Solar/Wind Helper
0.114
962101AG1-054 GEN
Solar/Wind Helper
0.331
203804AE2-113_GEN
Solar/Wind Helper
0.87
940863AE2-074 GEN
Solar/Wind Helper
0.226
946381AF1-302 GEN
Solar/Wind Helper
0.105
24189902OREGON_CT2
50/50
4.122
23856402BAYSG1
50/50
1.575
23888702TROY G3
50/50
1.525
972253AH1-711 GEN
50/50
46.615
23920202STRYCT
50/50
1.928
241858AF1-205_GEN
Solar/Wind Harmer
3.781
23906502RICHG2&3
Adder
1.343
960841AF2-375 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
0.187
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.25
957891AF2-083 GEN
Solar/Wind Harmer
7.68
965421AG1-410 GEN
Solar/Wind Harmer
13.812
24639705ELKHART HY
Adder
0.098
965011AG1-365 GEN
Solar/Wind Harmer
4.252
270317AD1-130_GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.303
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
4.532
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.781
274812UNIV PK N;8U
Adder
2.722
274802UNIV PARK;5U
Adder
3.135
274773LINCOLN ;4U
Adder
4.514
274774LINCOLN ;5U
Adder
4.514
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.29
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.713
274674JOLIET 9 ;6U
Adder
8.16
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.594
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.362
274828WAUKEGAN ;BP
Adder
5.749
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.702
276882AE2-255 GEN
Solar/Wind Harmer
0.421
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.886
270024AE2-089 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
10.699
959081AF2-199 GEN
Solar/Wind Harmer
3.566
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.012
970569AG2-363 GEN
Solar/Wind Harmer
10.659
970819AG2-516 GEN
Solar/Wind Harmer
4.255
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276708O09 GEN2
Solar/Wind Harmer
0.123
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.858
965651AG1-433 GEN
Solar/Wind Harmer
1.011
958861AF2-177 GEN
Solar/Wind Harmer
1.481
963741AG1-226 GEN
Solar/Wind Harmer
7.998
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
3.712
270032AE2-172
Solar/Wind Harmer
2.209
276621W2-048 GEN
Solar/Wind Harmer
0.164
276903AD2-071 C
Solar/Wind Harmer
3.645
970825AG2-519 GEN
Solar/Wind Harmer
1.151
270005AE1-210 C O1
Solar/Wind Harmer
0.699
965911AG1-460 GEN
Solar/Wind Harmer
0.643
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.285
24728605AND G2
Adder
1.661
241885AC2-103 GEN1
Solar/Wind Helper
6.847
241807AE2-176_GEN
Solar/Wind Helper
1.645
203947AF1-006 C
Solar/Wind Helper
0.391
961971AG1-040 GEN
Solar/Wind Helper
0.342
203830AF1-094 GEN
Solar/Wind Helper
0.331
203979AG1-198 GEN
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
23929302BS-PKR
50/50
2.775
958321AF2-126 GEN
Solar/Wind Harmer
1.137
23906402RICHG1
Adder
1.346
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.167
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
270505AE1-170 C O1
Solar/Wind Harmer
4.855
945111AF1-176 GEN
Solar/Wind Harmer
3.748
270588AE1-091_GEN
Solar/Wind Harmer
3.596
24695305TIMB G C
Solar/Wind Harmer
0.378
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.417
971347AH1-153 GEN
Solar/Wind Harmer
2.049
270043AE2-236 GEN
Solar/Wind Harmer
2.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
9.665
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274811UNIV PK N;7U
Adder
2.722
274803UNIV PARK;6U
Adder
3.135
274826FISK ;BP
Adder
5.877
972038AH1-567 GEN2
Adder
0.196
274887GEN-1.85
Solar/Wind Harmer
0.097
276843GEN-1.7
Solar/Wind Harmer
0.121
276806AD2-047 C O1
Solar/Wind Harmer
2.116
23888502TROY G1
50/50
1.525
23888602TROY G2
50/50
1.525
945411AF1-206 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.522
270575GUS2 35KV
Solar/Wind Harmer
4.522
270499AE1-146 GEN
Solar/Wind Harmer
0.021
971549AH1-272 GEN
Solar/Wind Harmer
11.979
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.588
270007AE1-245 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.388
971771AH1-392 GEN
Solar/Wind Harmer
4.384
965041AG1-368 GEN
Solar/Wind Harmer
4.372
247521TR3_G114
Solar/Wind Harmer
0.157
965051AG1-369 GEN
Solar/Wind Harmer
2.168
270526AF1-158 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
2.976
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.581
960681AF2-359 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.317
971567AH1-282 GEN
Solar/Wind Harmer
3.005
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
270071AF1-092 GEN
Solar/Wind Harmer
7.265
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
274800UNIV PARK;3U
Adder
3.125
274801UNIV PARK;4U
Adder
3.125
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.514
274776LINCOLN ;7U
Adder
4.514
274777LINCOLN ;8U
Adder
4.514
971611AH1-305 GEN
Solar/Wind Harmer
2.221
972228AH1-698 GEN2
Adder
1.977
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.866
274687WILL CNTY;4U
Adder
14.866
274675JOLIET 29;7U
Adder
16.29
274675JOLIET 29;7U
Adder
15.708
274728ELWOOD EC;5P
Adder
8.713
274731ELWOOD EC;2P
Adder
8.712
274733ELWOOD EC;3P
Adder
8.712
274735ELWOOD EC;4P
Adder
8.712
970833AG2-524 GEN
Solar/Wind Harmer
4.048
970833AG2-524 GEN
Solar/Wind Harmer
2.699
274744AC1-111 GEN8
Adder
2.931
274746AC1-111 G10
Adder
2.931
970073AG2-061 GEN
Solar/Wind Harmer
1.208
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
5.374
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.396
276861AD2-134 GEN
Solar/Wind Harmer
0.064
276863AD2-134 GEN
Solar/Wind Harmer
0.064
971171AH1-044 GEN
Solar/Wind Harmer
7.132
274823ROCKFORD ;21
Adder
9.94
926823AC1-168 GEN
Solar/Wind Harmer
0.603
970169AG2-114 GEN
Solar/Wind Harmer
3.545
274856ECOGROVE ;U1
Solar/Wind Harmer
0.083
24729505KEY G4
Adder
3.292
971681AH1-341 GEN
Solar/Wind Harmer
5.682
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
2.087
276741O09 GEN1
Solar/Wind Harmer
0.123
274877BISHOP HL;1U
Solar/Wind Harmer
0.116
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.643
963841AG1-237 GEN
Solar/Wind Harmer
1.491
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.921
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.549
970289AG2-191 GEN
Solar/Wind Harmer
0.635
964611AG1-324 GEN
Solar/Wind Harmer
1.3
276668AB2-070 GEN1
Solar/Wind Harmer
0.13
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.13
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
1.251
247536S-71 GEN
Solar/Wind Harmer
0.131
270543AE2-219 C
Solar/Wind Harmer
2.237
944221AF1-090 GEN
Solar/Wind Harmer
1.843
971029AG2-637 GEN
Solar/Wind Harmer
4.677
241886AC2-103 GEN2
Solar/Wind Helper
6.847
241985AE1-237 GEN
Solar/Wind Helper
0.134
241982AE2-343 S C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
20334926Z1-069 C
Solar/Wind Helper
0.646
274772LINCOLN ;3U
Adder
4.514
972259AH1-714 GEN
Adder
10.137
274676JOLIET 29;8U
Adder
15.708
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
8.712
274730ELWOOD EC;6P
Adder
8.713
274734ELWOOD EC;8P
Adder
8.713
274736ELWOOD EC;9P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.078
943121AE2-341 GEN
Solar/Wind Harmer
6.131
943591AF1-030 GEN
Solar/Wind Harmer
4.077
274862TOP CROP ;2U
Solar/Wind Harmer
0.494
274682WAUKEGAN ;7U
Adder
9.362
276868AE1-113 GEN
Solar/Wind Harmer
0.722
274879MINONK ;1U
Solar/Wind Harmer
0.151
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.598
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
944531AF1-118 GEN
Solar/Wind Harmer
16.015
959091AF2-200 GEN
Solar/Wind Harmer
7.132
970571AG2-364 GEN
Solar/Wind Harmer
7.106
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
4.638
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.116
965091AG1-374 GEN
Solar/Wind Harmer
10.297
959611AF2-252 GEN
Solar/Wind Harmer
1.144
965931AG1-462 GEN
Solar/Wind Harmer
8.718
971087AG2-675 GEN
Solar/Wind Harmer
1.823
247642Z2-115 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.032
970289AG2-191 GEN
Solar/Wind Harmer
0.367
971993AH1-541 GEN
Solar/Wind Harmer
1.533
946031AF1-268 GEN
Solar/Wind Harmer
3.094
970825AG2-519 GEN
Solar/Wind Harmer
2.443
270004AE1-209 GEN
Solar/Wind Harmer
0.699
957381AF2-032 GEN
Solar/Wind Harmer
0.73
942481AE2-261 GEN
Solar/Wind Harmer
9.607
970193AG2-126 GEN
Solar/Wind Harmer
4.752
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728705AND G3
Adder
3.474
24728505AND G1
Adder
1.661
962511AG1-100 GEN
Solar/Wind Helper
0.35
991177J1571 G
External Queue
15.794994354248047
991182J1586 G
External Queue
28.12165069580078
990527J1329
External Queue
2.0237011909484863
990142J1224
External Queue
14.793254852294922
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.945
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.857
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
CPLELTFEXP_CPLE->PJM
CLTF
0.731
MECLTFEXP_MEC->PJM
CLTF
7.632
SIGELTFEXP_SIGE->PJM
CLTF
0.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.534
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.401
TVALTFEXP_TVA->PJM
CLTF
2.775

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.27 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2199.92
MW Contribution:
4.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
15.354
24190002OREGON_ST1
50/50
3.828
24189802OREGON_CT1
50/50
2.906
23888802TROY G4
50/50
1.902
970621AG2-405 GEN
Solar/Wind Harmer
0.863
944231AF1-091 GEN
Solar/Wind Harmer
10.721
970623AG2-406 GEN
Solar/Wind Harmer
0.805
246937BC-WTG2
Solar/Wind Harmer
0.167
247607V1-011 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
8.175
961051AF2-396 GEN
Solar/Wind Harmer
5.45
247620Y3-023
Adder
0.259
270246TR4_N_V150
Solar/Wind Harmer
0.025
270247TR4_N_V136
Solar/Wind Harmer
0.025
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.465
965791AG1-447 GEN
Solar/Wind Harmer
3.274
970349AG2-230 GEN
Solar/Wind Harmer
5.33
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.355
274808UNIV PK N;4U
Adder
2.34
274888KELLY CRK;1U
Solar/Wind Harmer
0.188
276776AD2-060 GEN
Solar/Wind Harmer
0.344
958011AF2-095 GEN
Solar/Wind Harmer
4.639
970941AG2-585 GEN
Solar/Wind Harmer
1.772
274770LINCOLN ;1U
Adder
3.895
274771LINCOLN ;2U
Adder
3.895
276897AD1-100 C
Solar/Wind Harmer
7.977
276893AG1-478 C
Solar/Wind Harmer
0.213
274674JOLIET 9 ;6U
Adder
7.036
942221AE2-234 GEN
Solar/Wind Harmer
1.273
958481AF2-142 GEN
Solar/Wind Harmer
4.726
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.112
274695ROCKY RD ;2P
Adder
4.994
274693ROCKY RD ;1P
Adder
4.945
274697ROCKY RD ;3P
Adder
1.357
274683WAUKEGAN ;8U
Adder
9.446
274683WAUKEGAN ;8U
Adder
7.963
958491AF2-143 GEN
Solar/Wind Harmer
4.683
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
9.333
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.136
971343AH1-151 GEN
Solar/Wind Harmer
6.136
972235AH1-702 GEN1
Adder
1.104
972236AH1-702 GEN2
Adder
0.96
938861AE1-114 GEN
Solar/Wind Harmer
1.719
274764LEE CO EC;5U
Adder
4.043
274765LEE CO EC;6U
Adder
4.043
274762LEE CO EC;3U
Adder
4.034
274763LEE CO EC;4U
Adder
3.996
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.484
203835AF1-098 GEN
Solar/Wind Helper
1.32
23929302BS-PKR
50/50
2.128
958321AF2-126 GEN
Solar/Wind Harmer
1.129
23906402RICHG1
Adder
1.331
23906502RICHG2&3
Adder
1.328
270541AE2-072 C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.149
270491AE1-102 GEN2
Solar/Wind Harmer
0.538
270588AE1-091_GEN
Solar/Wind Harmer
3.209
945111AF1-176 GEN
Solar/Wind Harmer
3.265
270505AE1-170 C O1
Solar/Wind Harmer
4.228
24695305TIMB G C
Solar/Wind Harmer
0.337
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.249
270043AE2-236 GEN
Solar/Wind Harmer
2.282
971347AH1-153 GEN
Solar/Wind Harmer
1.777
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
274752CRETE EC ;2U
Adder
3.916
274753CRETE EC ;3U
Adder
3.916
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.348
274814UNIV PK N;0U
Adder
2.371
274807UNIV PK N;3U
Adder
2.366
274811UNIV PK N;7U
Adder
2.35
274803UNIV PARK;6U
Adder
2.705
274826FISK ;BP
Adder
5.071
972038AH1-567 GEN2
Adder
0.169
274887GEN-1.85
Solar/Wind Harmer
0.084
276843GEN-1.7
Solar/Wind Harmer
0.104
276806AD2-047 C O1
Solar/Wind Harmer
1.825
274772LINCOLN ;3U
Adder
3.895
972259AH1-714 GEN
Adder
8.742
274676JOLIET 29;8U
Adder
13.546
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
7.512
274730ELWOOD EC;6P
Adder
7.513
274734ELWOOD EC;8P
Adder
7.513
274736ELWOOD EC;9P
Adder
7.513
970707AG2-453 GEN
Solar/Wind Harmer
10.414
943121AE2-341 GEN
Solar/Wind Harmer
5.283
943591AF1-030 GEN
Solar/Wind Harmer
3.513
274862TOP CROP ;2U
Solar/Wind Harmer
0.425
274682WAUKEGAN ;7U
Adder
8.064
276868AE1-113 GEN
Solar/Wind Harmer
0.621
274879MINONK ;1U
Solar/Wind Harmer
0.13
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.1
944531AF1-118 GEN
Solar/Wind Harmer
13.889
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
0.112
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
959091AF2-200 GEN
Solar/Wind Harmer
6.136
970571AG2-364 GEN
Solar/Wind Harmer
6.112
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.034
274767LEE CO EC;8U
Adder
3.986
24386205FR-12G C
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.342
241967AE2-285_GEN
Solar/Wind Helper
0.341
241801AE1-079 GEN
Solar/Wind Helper
0.133
254304AE2-114 C
Solar/Wind Helper
0.113
254305AE2-115 C
Solar/Wind Helper
0.113
962101AG1-054 GEN
Solar/Wind Helper
0.329
203804AE2-113_GEN
Solar/Wind Helper
0.869
940863AE2-074 GEN
Solar/Wind Helper
0.225
946381AF1-302 GEN
Solar/Wind Helper
0.105
23888502TROY G1
50/50
1.902
23888602TROY G2
50/50
1.902
241886AC2-103 GEN2
Solar/Wind Harmer
0
945411AF1-206 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.061
270575GUS2 35KV
Solar/Wind Harmer
4.061
270499AE1-146 GEN
Solar/Wind Harmer
0.019
971549AH1-272 GEN
Solar/Wind Harmer
10.493
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.524
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
3.882
970031AG2-029 GEN
Solar/Wind Harmer
2.091
247521TR3_G114
Solar/Wind Harmer
0.14
965051AG1-369 GEN
Solar/Wind Harmer
1.924
971771AH1-392 GEN
Solar/Wind Harmer
3.813
959331AF2-224 GEN
Solar/Wind Harmer
2.624
270526AF1-158 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.517
960681AF2-359 GEN
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
2.667
963791AG1-232 GEN
Solar/Wind Harmer
4.667
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270071AF1-092 GEN
Solar/Wind Harmer
6.326
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.594
274800UNIV PARK;3U
Adder
2.696
274801UNIV PARK;4U
Adder
2.696
960591AF2-350 GEN
Solar/Wind Harmer
3.221
274775LINCOLN ;6U
Adder
3.895
274776LINCOLN ;7U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
971611AH1-305 GEN
Solar/Wind Harmer
1.917
972228AH1-698 GEN2
Adder
1.705
972227AH1-698 GEN1
Adder
1.201
274687WILL CNTY;4U
Adder
12.821
274687WILL CNTY;4U
Adder
12.821
274675JOLIET 29;7U
Adder
14.048
274675JOLIET 29;7U
Adder
13.546
274728ELWOOD EC;5P
Adder
7.513
274731ELWOOD EC;2P
Adder
7.512
274733ELWOOD EC;3P
Adder
7.512
274735ELWOOD EC;4P
Adder
7.512
970833AG2-524 GEN
Solar/Wind Harmer
3.49
970833AG2-524 GEN
Solar/Wind Harmer
2.326
274744AC1-111 GEN8
Adder
2.526
274746AC1-111 G10
Adder
2.526
970073AG2-061 GEN
Solar/Wind Harmer
1.041
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.625
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.201
276861AD2-134 GEN
Solar/Wind Harmer
0.055
276863AD2-134 GEN
Solar/Wind Harmer
0.055
971171AH1-044 GEN
Solar/Wind Harmer
6.136
24729505KEY G4
Adder
2.853
274823ROCKFORD ;21
Adder
8.55
926823AC1-168 GEN
Solar/Wind Harmer
0.519
970169AG2-114 GEN
Solar/Wind Harmer
3.049
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
971681AH1-341 GEN
Solar/Wind Harmer
4.884
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.793
276741O09 GEN1
Solar/Wind Harmer
0.106
241985AE1-237 GEN
Solar/Wind Helper
0.133
241982AE2-343 S C
Solar/Wind Helper
0.119
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
20334926Z1-069 C
Solar/Wind Helper
0.647
24189902OREGON_CT2
50/50
2.845
23888702TROY G3
50/50
1.902
972253AH1-711 GEN
50/50
58.161
23856402BAYSG1
50/50
1.208
23920202STRYCT
50/50
1.93
241885AC2-103 GEN1
Solar/Wind Harmer
0
241858AF1-205_GEN
Solar/Wind Harmer
3.879
23906502RICHG2&3
Adder
1.328
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.167
270489AE1-102 GEN1
Solar/Wind Harmer
0.538
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.151
965421AG1-410 GEN
Solar/Wind Harmer
12.304
945111AF1-176 GEN
Solar/Wind Harmer
7.189
957891AF2-083 GEN
Solar/Wind Harmer
6.688
24639705ELKHART HY
Adder
0.086
965011AG1-365 GEN
Solar/Wind Harmer
3.748
270317AD1-130_GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.184
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
3.916
274754CRETE EC ;4U
Adder
3.916
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.286
274723RIVER EC ;12
Adder
8.448
274812UNIV PK N;8U
Adder
2.35
274802UNIV PARK;5U
Adder
2.705
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.025
274676JOLIET 29;8U
Adder
14.047
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.513
274674JOLIET 9 ;6U
Adder
7.036
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.526
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.512
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.064
274828WAUKEGAN ;BP
Adder
4.951
276805AD2-038 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.327
276882AE2-255 GEN
Solar/Wind Harmer
0.362
962781AG1-127 GEN
Solar/Wind Harmer
2.955
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.624
957471AF2-041 GEN
Solar/Wind Harmer
9.204
959081AF2-199 GEN
Solar/Wind Harmer
3.068
971067AG2-660 GEN
Solar/Wind Harmer
1.023
274822ROCKFORD ;11
Adder
8.612
970569AG2-363 GEN
Solar/Wind Harmer
9.168
970819AG2-516 GEN
Solar/Wind Harmer
3.659
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.034
274766LEE CO EC;7U
Adder
3.986
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276708O09 GEN2
Solar/Wind Harmer
0.106
241807AE2-176_GEN
Solar/Wind Helper
2.245
203947AF1-006 C
Solar/Wind Helper
0.381
961971AG1-040 GEN
Solar/Wind Helper
0.334
203830AF1-094 GEN
Solar/Wind Helper
0.324
203979AG1-198 GEN
Solar/Wind Helper
0.195
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.077
991177J1571 G
External Queue
15.850347518920898
991182J1586 G
External Queue
26.14141845703125
990527J1329
External Queue
1.907416582107544
990142J1224
External Queue
13.943214416503906
NYPJM->LTFIMP_NY
CLTF
2.03
LGEELTFEXP_LGEE->PJM
CLTF
2.008
WECLTFEXP_WEC->PJM
CLTF
1.673
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.332
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.892
CPLELTFEXP_CPLE->PJM
CLTF
0.328
MECLTFEXP_MEC->PJM
CLTF
6.511
SIGELTFEXP_SIGE->PJM
CLTF
0.168
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.683
LAGNLTFEXP_LAGN->PJM
CLTF
4.961
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.187
TVALTFEXP_TVA->PJM
CLTF
2.246

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.8 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2190.94
MW Contribution:
4.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
15.36
24190002OREGON_ST1
50/50
3.83
24189802OREGON_CT1
50/50
2.907
23888802TROY G4
50/50
1.904
970621AG2-405 GEN
Solar/Wind Harmer
0.865
944231AF1-091 GEN
Solar/Wind Harmer
10.737
970623AG2-406 GEN
Solar/Wind Harmer
0.807
246937BC-WTG2
Solar/Wind Harmer
0.167
247607V1-011 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
8.189
961051AF2-396 GEN
Solar/Wind Harmer
5.459
247620Y3-023
Adder
0.259
270246TR4_N_V150
Solar/Wind Harmer
0.025
270247TR4_N_V136
Solar/Wind Harmer
0.025
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.474
965791AG1-447 GEN
Solar/Wind Harmer
3.281
970349AG2-230 GEN
Solar/Wind Harmer
5.34
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.36
274808UNIV PK N;4U
Adder
2.345
274888KELLY CRK;1U
Solar/Wind Harmer
0.188
276776AD2-060 GEN
Solar/Wind Harmer
0.344
958011AF2-095 GEN
Solar/Wind Harmer
4.649
970941AG2-585 GEN
Solar/Wind Harmer
1.776
274770LINCOLN ;1U
Adder
3.903
274771LINCOLN ;2U
Adder
3.903
276897AD1-100 C
Solar/Wind Harmer
7.994
24189902OREGON_CT2
50/50
2.847
23888702TROY G3
50/50
1.904
972253AH1-711 GEN
50/50
58.195
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.931
241858AF1-205_GEN
Solar/Wind Harmer
3.882
23906502RICHG2&3
Adder
1.329
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.167
270489AE1-102 GEN1
Solar/Wind Harmer
0.539
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
12.325
945111AF1-176 GEN
Solar/Wind Harmer
7.201
957891AF2-083 GEN
Solar/Wind Harmer
6.7
24639705ELKHART HY
Adder
0.086
965011AG1-365 GEN
Solar/Wind Harmer
3.755
270317AD1-130_GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.199
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
3.924
274754CRETE EC ;4U
Adder
3.924
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.296
274723RIVER EC ;12
Adder
8.466
274812UNIV PK N;8U
Adder
2.355
274802UNIV PARK;5U
Adder
2.711
940581AE2-045 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
3.903
274774LINCOLN ;5U
Adder
3.903
971605AH1-302 GEN
Solar/Wind Harmer
4.034
274676JOLIET 29;8U
Adder
14.079
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.529
274674JOLIET 9 ;6U
Adder
7.052
276893AG1-478 C
Solar/Wind Harmer
0.213
274674JOLIET 9 ;6U
Adder
7.052
942221AE2-234 GEN
Solar/Wind Harmer
1.276
958481AF2-142 GEN
Solar/Wind Harmer
4.736
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.123
274695ROCKY RD ;2P
Adder
5.005
274693ROCKY RD ;1P
Adder
4.956
274697ROCKY RD ;3P
Adder
1.36
274683WAUKEGAN ;8U
Adder
9.467
274683WAUKEGAN ;8U
Adder
7.981
958491AF2-143 GEN
Solar/Wind Harmer
4.694
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
9.354
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.15
971343AH1-151 GEN
Solar/Wind Harmer
6.15
972235AH1-702 GEN1
Adder
1.107
972236AH1-702 GEN2
Adder
0.962
938861AE1-114 GEN
Solar/Wind Harmer
1.723
274764LEE CO EC;5U
Adder
4.053
274765LEE CO EC;6U
Adder
4.053
274762LEE CO EC;3U
Adder
4.043
274763LEE CO EC;4U
Adder
4.005
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.343
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.485
203835AF1-098 GEN
Solar/Wind Helper
1.318
241967AE2-285_GEN
Solar/Wind Helper
0.34
241801AE1-079 GEN
Solar/Wind Helper
0.133
254304AE2-114 C
Solar/Wind Helper
0.113
254305AE2-115 C
Solar/Wind Helper
0.113
962101AG1-054 GEN
Solar/Wind Helper
0.328
203804AE2-113_GEN
Solar/Wind Helper
0.867
940863AE2-074 GEN
Solar/Wind Helper
0.225
946381AF1-302 GEN
Solar/Wind Helper
0.105
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.531
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.513
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.082
274828WAUKEGAN ;BP
Adder
4.963
276805AD2-038 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.332
276882AE2-255 GEN
Solar/Wind Harmer
0.363
962781AG1-127 GEN
Solar/Wind Harmer
2.962
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.628
957471AF2-041 GEN
Solar/Wind Harmer
9.225
959081AF2-199 GEN
Solar/Wind Harmer
3.075
971067AG2-660 GEN
Solar/Wind Harmer
1.025
274822ROCKFORD ;11
Adder
8.632
970569AG2-363 GEN
Solar/Wind Harmer
9.19
970819AG2-516 GEN
Solar/Wind Harmer
3.668
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.043
274766LEE CO EC;7U
Adder
3.996
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276708O09 GEN2
Solar/Wind Harmer
0.106
241885AC2-103 GEN1
Solar/Wind Helper
3.957
241807AE2-176_GEN
Solar/Wind Helper
2.243
203947AF1-006 C
Solar/Wind Helper
0.381
961971AG1-040 GEN
Solar/Wind Helper
0.334
203830AF1-094 GEN
Solar/Wind Helper
0.324
203979AG1-198 GEN
Solar/Wind Helper
0.194
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
23888502TROY G1
50/50
1.904
23888602TROY G2
50/50
1.904
945411AF1-206 GEN
Solar/Wind Harmer
0
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270361_3
Solar/Wind Harmer
4.066
270575GUS2 35KV
Solar/Wind Harmer
4.066
270499AE1-146 GEN
Solar/Wind Harmer
0.019
971549AH1-272 GEN
Solar/Wind Harmer
10.508
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.525
270007AE1-245 C
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
3.889
970031AG2-029 GEN
Solar/Wind Harmer
2.095
247521TR3_G114
Solar/Wind Harmer
0.14
965051AG1-369 GEN
Solar/Wind Harmer
1.928
971771AH1-392 GEN
Solar/Wind Harmer
3.82
959331AF2-224 GEN
Solar/Wind Harmer
2.629
270526AF1-158 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.518
960681AF2-359 GEN
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
2.672
963791AG1-232 GEN
Solar/Wind Harmer
4.677
270578AF1-285 GEN2
Solar/Wind Harmer
0.228
270071AF1-092 GEN
Solar/Wind Harmer
6.34
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
274800UNIV PARK;3U
Adder
2.702
274801UNIV PARK;4U
Adder
2.702
960591AF2-350 GEN
Solar/Wind Harmer
3.228
274775LINCOLN ;6U
Adder
3.903
274776LINCOLN ;7U
Adder
3.903
274777LINCOLN ;8U
Adder
3.903
971611AH1-305 GEN
Solar/Wind Harmer
1.921
972228AH1-698 GEN2
Adder
1.709
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.849
274687WILL CNTY;4U
Adder
12.849
274675JOLIET 29;7U
Adder
14.079
274675JOLIET 29;7U
Adder
13.576
274728ELWOOD EC;5P
Adder
7.529
274731ELWOOD EC;2P
Adder
7.529
274733ELWOOD EC;3P
Adder
7.529
274735ELWOOD EC;4P
Adder
7.529
970833AG2-524 GEN
Solar/Wind Harmer
3.497
970833AG2-524 GEN
Solar/Wind Harmer
2.332
274744AC1-111 GEN8
Adder
2.531
274746AC1-111 G10
Adder
2.531
970073AG2-061 GEN
Solar/Wind Harmer
1.043
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.636
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.204
276861AD2-134 GEN
Solar/Wind Harmer
0.055
276863AD2-134 GEN
Solar/Wind Harmer
0.055
971171AH1-044 GEN
Solar/Wind Harmer
6.15
24729505KEY G4
Adder
2.859
274823ROCKFORD ;21
Adder
8.57
926823AC1-168 GEN
Solar/Wind Harmer
0.52
970169AG2-114 GEN
Solar/Wind Harmer
3.057
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
971681AH1-341 GEN
Solar/Wind Harmer
4.896
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.797
276741O09 GEN1
Solar/Wind Harmer
0.106
241886AC2-103 GEN2
Solar/Wind Helper
3.957
241985AE1-237 GEN
Solar/Wind Helper
0.132
241982AE2-343 S C
Solar/Wind Helper
0.119
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
20334926Z1-069 C
Solar/Wind Helper
0.645
23929302BS-PKR
50/50
2.13
958321AF2-126 GEN
Solar/Wind Harmer
1.13
23906402RICHG1
Adder
1.333
23906502RICHG2&3
Adder
1.329
270541AE2-072 C
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.149
270491AE1-102 GEN2
Solar/Wind Harmer
0.539
270588AE1-091_GEN
Solar/Wind Harmer
3.215
945111AF1-176 GEN
Solar/Wind Harmer
3.271
270505AE1-170 C O1
Solar/Wind Harmer
4.235
24695305TIMB G C
Solar/Wind Harmer
0.338
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270043AE2-236 GEN
Solar/Wind Harmer
2.286
971347AH1-153 GEN
Solar/Wind Harmer
1.78
270391AF1-285 GEN3
Solar/Wind Harmer
0.228
274752CRETE EC ;2U
Adder
3.924
274753CRETE EC ;3U
Adder
3.924
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.366
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274811UNIV PK N;7U
Adder
2.355
274803UNIV PARK;6U
Adder
2.711
274826FISK ;BP
Adder
5.082
972038AH1-567 GEN2
Adder
0.169
274887GEN-1.85
Solar/Wind Harmer
0.084
276843GEN-1.7
Solar/Wind Harmer
0.104
276806AD2-047 C O1
Solar/Wind Harmer
1.829
274772LINCOLN ;3U
Adder
3.903
972259AH1-714 GEN
Adder
8.761
274676JOLIET 29;8U
Adder
13.576
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
7.529
274730ELWOOD EC;6P
Adder
7.529
274734ELWOOD EC;8P
Adder
7.529
274736ELWOOD EC;9P
Adder
7.529
970707AG2-453 GEN
Solar/Wind Harmer
10.437
943121AE2-341 GEN
Solar/Wind Harmer
5.295
943591AF1-030 GEN
Solar/Wind Harmer
3.521
274862TOP CROP ;2U
Solar/Wind Harmer
0.426
274682WAUKEGAN ;7U
Adder
8.082
276868AE1-113 GEN
Solar/Wind Harmer
0.623
274879MINONK ;1U
Solar/Wind Harmer
0.13
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.107
944531AF1-118 GEN
Solar/Wind Harmer
13.92
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
959091AF2-200 GEN
Solar/Wind Harmer
6.15
970571AG2-364 GEN
Solar/Wind Harmer
6.126
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.043
274767LEE CO EC;8U
Adder
3.996
24386205FR-12G C
Solar/Wind Harmer
0
962511AG1-100 GEN
Solar/Wind Helper
0.341
991177J1571 G
External Queue
15.850347518920898
991182J1586 G
External Queue
26.14141845703125
990527J1329
External Queue
1.907416582107544
990142J1224
External Queue
13.943214416503906
NYPJM->LTFIMP_NY
CLTF
2.024
LGEELTFEXP_LGEE->PJM
CLTF
2.015
WECLTFEXP_WEC->PJM
CLTF
1.677
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.48
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.931
CPLELTFEXP_CPLE->PJM
CLTF
0.339
MECLTFEXP_MEC->PJM
CLTF
6.528
SIGELTFEXP_SIGE->PJM
CLTF
0.169
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.82
LAGNLTFEXP_LAGN->PJM
CLTF
4.981
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.218
TVALTFEXP_TVA->PJM
CLTF
2.256

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.9 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2176.69
MW Contribution:
5.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.676
23856402BAYSG1
50/50
1.431
23888702TROY G3
50/50
1.834
972253AH1-711 GEN
50/50
56.063
23860302FRMENG 3
50/50
3.522
23920202STRYCT
50/50
2.05
241885AC2-103 GEN1
Solar/Wind Harmer
0
241807AE2-176_GEN
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
4.133
23906502RICHG2&3
Adder
1.422
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.175
270489AE1-102 GEN1
Solar/Wind Harmer
0.564
965421AG1-410 GEN
Solar/Wind Harmer
12.893
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.178
945111AF1-176 GEN
Solar/Wind Harmer
7.29
957891AF2-083 GEN
Solar/Wind Harmer
6.781
24639705ELKHART HY
Adder
0.087
270317AD1-130_GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
3.892
970373AG2-245 GEN
Solar/Wind Harmer
7.327
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
3.998
274754CRETE EC ;4U
Adder
3.998
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.378
274723RIVER EC ;12
Adder
8.627
274812UNIV PK N;8U
Adder
2.4
274802UNIV PARK;5U
Adder
2.764
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.116
274773LINCOLN ;4U
Adder
3.98
274774LINCOLN ;5U
Adder
3.98
274676JOLIET 29;8U
Adder
14.356
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.678
274674JOLIET 9 ;6U
Adder
7.191
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
2.582
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.523
23867002DVBSG1
50/50
12.651
24190002OREGON_ST1
50/50
3.601
24189802OREGON_CT1
50/50
2.733
23888802TROY G4
50/50
1.834
970621AG2-405 GEN
Solar/Wind Harmer
0.951
944231AF1-091 GEN
Solar/Wind Harmer
11.237
970623AG2-406 GEN
Solar/Wind Harmer
0.857
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.175
961051AF2-396 GEN
Solar/Wind Harmer
8.281
961051AF2-396 GEN
Solar/Wind Harmer
5.52
270246TR4_N_V150
Solar/Wind Harmer
0.026
270247TR4_N_V136
Solar/Wind Harmer
0.026
247620Y3-023
Adder
0.264
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.545
23929302BS-PKR
50/50
2.522
958321AF2-126 GEN
Solar/Wind Harmer
1.267
23906402RICHG1
Adder
1.424
23906502RICHG2&3
Adder
1.422
270541AE2-072 C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.737
246938BC-WTG3
Solar/Wind Harmer
0.156
270491AE1-102 GEN2
Solar/Wind Harmer
0.564
24695305TIMB G C
Solar/Wind Harmer
0.357
945111AF1-176 GEN
Solar/Wind Harmer
3.312
270505AE1-170 C O1
Solar/Wind Harmer
4.285
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.297
270043AE2-236 GEN
Solar/Wind Harmer
2.351
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
1.811
274752CRETE EC ;2U
Adder
3.998
274753CRETE EC ;3U
Adder
3.998
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.524
274814UNIV PK N;0U
Adder
2.421
274807UNIV PK N;3U
Adder
2.416
23888502TROY G1
50/50
1.834
23888602TROY G2
50/50
1.834
23860102FRMENG 1
50/50
1.736
23860202FRMENG 2
50/50
1.736
24191202EL_AA1-006
50/50
0.334
241886AC2-103 GEN2
Solar/Wind Harmer
0
945411AF1-206 GEN
Solar/Wind Harmer
0
270361_3
Solar/Wind Harmer
5.343
270575GUS2 35KV
Solar/Wind Harmer
5.343
270499AE1-146 GEN
Solar/Wind Harmer
0.024
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
10.511
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.55
965041AG1-368 GEN
Solar/Wind Harmer
4.077
247521TR3_G114
Solar/Wind Harmer
0.147
965051AG1-369 GEN
Solar/Wind Harmer
2.027
970031AG2-029 GEN
Solar/Wind Harmer
2.141
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.55
959331AF2-224 GEN
Solar/Wind Harmer
2.724
971771AH1-392 GEN
Solar/Wind Harmer
3.876
971567AH1-282 GEN
Solar/Wind Harmer
2.938
270526AF1-158 GEN
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
1.42
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
963791AG1-232 GEN
Solar/Wind Harmer
4.856
270071AF1-092 GEN
Solar/Wind Harmer
6.531
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.672
274800UNIV PARK;3U
Adder
2.755
274801UNIV PARK;4U
Adder
2.755
971611AH1-305 GEN
Solar/Wind Harmer
1.96
960591AF2-350 GEN
Solar/Wind Harmer
3.292
274775LINCOLN ;6U
Adder
3.98
274776LINCOLN ;7U
Adder
3.98
274777LINCOLN ;8U
Adder
3.98
972228AH1-698 GEN2
Adder
1.742
972227AH1-698 GEN1
Adder
1.227
274687WILL CNTY;4U
Adder
13.101
274687WILL CNTY;4U
Adder
13.101
274675JOLIET 29;7U
Adder
14.356
274675JOLIET 29;7U
Adder
13.843
274728ELWOOD EC;5P
Adder
7.678
274731ELWOOD EC;2P
Adder
7.678
274733ELWOOD EC;3P
Adder
7.678
274735ELWOOD EC;4P
Adder
7.678
970833AG2-524 GEN
Solar/Wind Harmer
3.567
970833AG2-524 GEN
Solar/Wind Harmer
2.378
274744AC1-111 GEN8
Adder
2.582
274746AC1-111 G10
Adder
2.582
970073AG2-061 GEN
Solar/Wind Harmer
1.064
24729505KEY G4
Adder
2.953
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.73
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.229
276861AD2-134 GEN
Solar/Wind Harmer
0.056
276863AD2-134 GEN
Solar/Wind Harmer
0.056
971171AH1-044 GEN
Solar/Wind Harmer
6.276
274823ROCKFORD ;21
Adder
8.745
970169AG2-114 GEN
Solar/Wind Harmer
3.121
926823AC1-168 GEN
Solar/Wind Harmer
0.531
274856ECOGROVE ;U1
Solar/Wind Harmer
0.073
971681AH1-341 GEN
Solar/Wind Harmer
4.997
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.835
276741O09 GEN1
Solar/Wind Harmer
0.109
274877BISHOP HL;1U
Solar/Wind Harmer
0.102
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.205
963841AG1-237 GEN
Solar/Wind Harmer
1.314
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.688
971609AH1-304 GEN
Solar/Wind Harmer
0.492
945581AF1-223 GEN
Solar/Wind Harmer
0
241985AE1-237 GEN
Solar/Wind Helper
0.141
241982AE2-343 S C
Solar/Wind Helper
0.127
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
20334926Z1-069 C
Solar/Wind Helper
0.691
274811UNIV PK N;7U
Adder
2.4
274803UNIV PARK;6U
Adder
2.764
274826FISK ;BP
Adder
5.181
972038AH1-567 GEN2
Adder
0.172
274887GEN-1.85
Solar/Wind Harmer
0.086
276843GEN-1.7
Solar/Wind Harmer
0.106
276806AD2-047 C O1
Solar/Wind Harmer
1.865
274772LINCOLN ;3U
Adder
3.98
972259AH1-714 GEN
Adder
8.934
274676JOLIET 29;8U
Adder
13.843
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
7.678
274730ELWOOD EC;6P
Adder
7.678
274734ELWOOD EC;8P
Adder
7.678
274736ELWOOD EC;9P
Adder
7.678
970707AG2-453 GEN
Solar/Wind Harmer
10.644
943121AE2-341 GEN
Solar/Wind Harmer
5.401
943591AF1-030 GEN
Solar/Wind Harmer
3.592
274862TOP CROP ;2U
Solar/Wind Harmer
0.435
944531AF1-118 GEN
Solar/Wind Harmer
14.371
274682WAUKEGAN ;7U
Adder
8.244
276868AE1-113 GEN
Solar/Wind Harmer
0.635
274879MINONK ;1U
Solar/Wind Harmer
0.133
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.174
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
959091AF2-200 GEN
Solar/Wind Harmer
6.276
965791AG1-447 GEN
Solar/Wind Harmer
3.333
970349AG2-230 GEN
Solar/Wind Harmer
5.432
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.405
274808UNIV PK N;4U
Adder
2.39
274888KELLY CRK;1U
Solar/Wind Harmer
0.192
276776AD2-060 GEN
Solar/Wind Harmer
0.351
958011AF2-095 GEN
Solar/Wind Harmer
4.74
970941AG2-585 GEN
Solar/Wind Harmer
1.81
274770LINCOLN ;1U
Adder
3.98
274771LINCOLN ;2U
Adder
3.98
942221AE2-234 GEN
Solar/Wind Harmer
1.321
276897AD1-100 C
Solar/Wind Harmer
8.153
276893AG1-478 C
Solar/Wind Harmer
0.217
274674JOLIET 9 ;6U
Adder
7.191
958481AF2-142 GEN
Solar/Wind Harmer
4.831
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.226
274695ROCKY RD ;2P
Adder
5.106
274693ROCKY RD ;1P
Adder
5.056
274697ROCKY RD ;3P
Adder
1.387
274683WAUKEGAN ;8U
Adder
9.658
274683WAUKEGAN ;8U
Adder
8.141
958491AF2-143 GEN
Solar/Wind Harmer
4.789
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
9.543
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.276
971343AH1-151 GEN
Solar/Wind Harmer
6.276
972235AH1-702 GEN1
Adder
1.129
972236AH1-702 GEN2
Adder
0.982
938861AE1-114 GEN
Solar/Wind Harmer
1.758
274764LEE CO EC;5U
Adder
4.137
274765LEE CO EC;6U
Adder
4.137
274762LEE CO EC;3U
Adder
4.127
274763LEE CO EC;4U
Adder
4.088
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.35
944541AF1-119 GEN
Solar/Wind Harmer
0.206
960971AF2-388 GEN
Solar/Wind Harmer
1.812
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.496
25326509SID D
Adder
0.577
942111AE2-223 GEN
Solar/Wind Harmer
0.992
970571AG2-364 GEN
Solar/Wind Harmer
6.253
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.127
274767LEE CO EC;8U
Adder
4.078
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.102
965091AG1-374 GEN
Solar/Wind Harmer
9.056
959611AF2-252 GEN
Solar/Wind Harmer
1.006
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.524
965931AG1-462 GEN
Solar/Wind Harmer
7.656
971087AG2-675 GEN
Solar/Wind Harmer
1.601
962511AG1-100 GEN
Solar/Wind Helper
0.367
203854AF2-039 C
Solar/Wind Helper
0.15
20398826ARMNA MT
Solar/Wind Helper
0.706
970329AG2-216 GEN
Solar/Wind Harmer
1.308
960611AF2-352 GEN
Solar/Wind Harmer
1.006
270201AC2-176 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.655
270599AE1-208 GEN
Solar/Wind Harmer
2.759
203835AF1-098 GEN
Solar/Wind Helper
1.417
241967AE2-285_GEN
Solar/Wind Helper
0.363
241801AE1-079 GEN
Solar/Wind Helper
0.142
254304AE2-114 C
Solar/Wind Helper
0.121
254305AE2-115 C
Solar/Wind Helper
0.121
962101AG1-054 GEN
Solar/Wind Helper
0.35
203804AE2-113_GEN
Solar/Wind Helper
0.929
940863AE2-074 GEN
Solar/Wind Helper
0.241
946381AF1-302 GEN
Solar/Wind Helper
0.113
203954AE2-126 C
Solar/Wind Helper
0.234
203853AF1-134 C O1
Solar/Wind Helper
0.22
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.244
274828WAUKEGAN ;BP
Adder
5.062
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.38
276882AE2-255 GEN
Solar/Wind Harmer
0.371
962781AG1-127 GEN
Solar/Wind Harmer
3.022
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.661
957471AF2-041 GEN
Solar/Wind Harmer
9.414
959081AF2-199 GEN
Solar/Wind Harmer
3.138
971067AG2-660 GEN
Solar/Wind Harmer
1.046
274822ROCKFORD ;11
Adder
8.809
970569AG2-363 GEN
Solar/Wind Harmer
9.379
970819AG2-516 GEN
Solar/Wind Harmer
3.743
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.127
274766LEE CO EC;7U
Adder
4.078
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.906
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276708O09 GEN2
Solar/Wind Harmer
0.109
958861AF2-177 GEN
Solar/Wind Harmer
1.326
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.273
945371AF1-202 GEN
Solar/Wind Harmer
0
203947AF1-006 C
Solar/Wind Helper
0.409
961971AG1-040 GEN
Solar/Wind Helper
0.359
203830AF1-094 GEN
Solar/Wind Helper
0.348
203979AG1-198 GEN
Solar/Wind Helper
0.209
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203855AF2-088 C
Solar/Wind Helper
0.072
991177J1571 G
External Queue
15.716124534606934
991182J1586 G
External Queue
25.29424285888672
990527J1329
External Queue
1.8514890670776367
990142J1224
External Queue
13.534384727478027
NYPJM->LTFIMP_NY
CLTF
2.163
LGEELTFEXP_LGEE->PJM
CLTF
2.093
WECLTFEXP_WEC->PJM
CLTF
1.711
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.219
CPLELTFEXP_CPLE->PJM
CLTF
0.333
MECLTFEXP_MEC->PJM
CLTF
6.675
SIGELTFEXP_SIGE->PJM
CLTF
0.174
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.932
LAGNLTFEXP_LAGN->PJM
CLTF
5.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.261
TVALTFEXP_TVA->PJM
CLTF
2.325

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.49 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2168.95
MW Contribution:
5.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23929302BS-PKR
50/50
2.524
958321AF2-126 GEN
Solar/Wind Harmer
1.268
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270541AE2-072 C
Solar/Wind Harmer
0
270588AE1-091_GEN
Solar/Wind Harmer
3.742
246938BC-WTG3
Solar/Wind Harmer
0.157
270491AE1-102 GEN2
Solar/Wind Harmer
0.565
24695305TIMB G C
Solar/Wind Harmer
0.357
945111AF1-176 GEN
Solar/Wind Harmer
3.317
270505AE1-170 C O1
Solar/Wind Harmer
4.292
270063AE2-323 C
Solar/Wind Harmer
0
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270043AE2-236 GEN
Solar/Wind Harmer
2.355
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
1.814
274752CRETE EC ;2U
Adder
4.006
274753CRETE EC ;3U
Adder
4.006
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.542
274814UNIV PK N;0U
Adder
2.426
274807UNIV PK N;3U
Adder
2.421
274811UNIV PK N;7U
Adder
2.405
274803UNIV PARK;6U
Adder
2.77
274826FISK ;BP
Adder
5.192
972038AH1-567 GEN2
Adder
0.173
274887GEN-1.85
Solar/Wind Harmer
0.086
276843GEN-1.7
Solar/Wind Harmer
0.107
276806AD2-047 C O1
Solar/Wind Harmer
1.869
274772LINCOLN ;3U
Adder
3.988
972259AH1-714 GEN
Adder
8.953
274676JOLIET 29;8U
Adder
13.872
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.667
274729ELWOOD EC;1P
Adder
7.694
274730ELWOOD EC;6P
Adder
7.694
274734ELWOOD EC;8P
Adder
7.694
274736ELWOOD EC;9P
Adder
7.694
943121AE2-341 GEN
Solar/Wind Harmer
5.412
943591AF1-030 GEN
Solar/Wind Harmer
3.599
274862TOP CROP ;2U
Solar/Wind Harmer
0.436
944531AF1-118 GEN
Solar/Wind Harmer
14.401
274682WAUKEGAN ;7U
Adder
8.262
276868AE1-113 GEN
Solar/Wind Harmer
0.637
274879MINONK ;1U
Solar/Wind Harmer
0.133
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.181
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
959091AF2-200 GEN
Solar/Wind Harmer
6.289
970571AG2-364 GEN
Solar/Wind Harmer
6.267
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.136
274767LEE CO EC;8U
Adder
4.087
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.102
965091AG1-374 GEN
Solar/Wind Harmer
9.076
959611AF2-252 GEN
Solar/Wind Harmer
1.008
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.534
965931AG1-462 GEN
Solar/Wind Harmer
7.674
971087AG2-675 GEN
Solar/Wind Harmer
1.605
247642Z2-115 C
Solar/Wind Harmer
0.001
23867002DVBSG1
50/50
12.657
24190002OREGON_ST1
50/50
3.603
24189802OREGON_CT1
50/50
2.734
23888802TROY G4
50/50
1.835
970621AG2-405 GEN
Solar/Wind Harmer
0.952
944231AF1-091 GEN
Solar/Wind Harmer
11.253
970623AG2-406 GEN
Solar/Wind Harmer
0.858
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.175
961051AF2-396 GEN
Solar/Wind Harmer
8.294
961051AF2-396 GEN
Solar/Wind Harmer
5.529
270246TR4_N_V150
Solar/Wind Harmer
0.026
270247TR4_N_V136
Solar/Wind Harmer
0.026
247620Y3-023
Adder
0.264
270462AD2-086
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.554
965791AG1-447 GEN
Solar/Wind Harmer
3.34
970349AG2-230 GEN
Solar/Wind Harmer
5.442
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
2.41
274808UNIV PK N;4U
Adder
2.394
274888KELLY CRK;1U
Solar/Wind Harmer
0.192
276776AD2-060 GEN
Solar/Wind Harmer
0.352
958011AF2-095 GEN
Solar/Wind Harmer
4.75
970941AG2-585 GEN
Solar/Wind Harmer
1.814
274770LINCOLN ;1U
Adder
3.988
274771LINCOLN ;2U
Adder
3.988
942221AE2-234 GEN
Solar/Wind Harmer
1.323
276897AD1-100 C
Solar/Wind Harmer
8.17
276893AG1-478 C
Solar/Wind Harmer
0.218
274674JOLIET 9 ;6U
Adder
7.206
958481AF2-142 GEN
Solar/Wind Harmer
4.841
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.066
274697ROCKY RD ;3P
Adder
1.39
274696ROCKY RD ;4P
Adder
5.238
274683WAUKEGAN ;8U
Adder
9.678
274683WAUKEGAN ;8U
Adder
8.158
958491AF2-143 GEN
Solar/Wind Harmer
4.799
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
9.563
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.289
971343AH1-151 GEN
Solar/Wind Harmer
6.289
972235AH1-702 GEN1
Adder
1.132
972236AH1-702 GEN2
Adder
0.984
938861AE1-114 GEN
Solar/Wind Harmer
1.762
274764LEE CO EC;5U
Adder
4.146
274765LEE CO EC;6U
Adder
4.146
274762LEE CO EC;3U
Adder
4.136
274763LEE CO EC;4U
Adder
4.097
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.351
944541AF1-119 GEN
Solar/Wind Harmer
0.207
960971AF2-388 GEN
Solar/Wind Harmer
1.816
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.497
25326509SID D
Adder
0.579
942111AE2-223 GEN
Solar/Wind Harmer
0.994
970329AG2-216 GEN
Solar/Wind Harmer
1.311
960611AF2-352 GEN
Solar/Wind Harmer
1.008
270201AC2-176 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.659
270599AE1-208 GEN
Solar/Wind Harmer
2.765
203835AF1-098 GEN
Solar/Wind Helper
1.415
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.142
254304AE2-114 C
Solar/Wind Helper
0.12
254305AE2-115 C
Solar/Wind Helper
0.12
962101AG1-054 GEN
Solar/Wind Helper
0.349
203804AE2-113_GEN
Solar/Wind Helper
0.927
940863AE2-074 GEN
Solar/Wind Helper
0.24
946381AF1-302 GEN
Solar/Wind Helper
0.112
203954AE2-126 C
Solar/Wind Helper
0.233
23888502TROY G1
50/50
1.835
23888602TROY G2
50/50
1.835
23860102FRMENG 1
50/50
1.737
23860202FRMENG 2
50/50
1.737
24191202EL_AA1-006
50/50
0.334
945411AF1-206 GEN
Solar/Wind Harmer
0
270361_3
Solar/Wind Harmer
5.347
270575GUS2 35KV
Solar/Wind Harmer
5.347
270499AE1-146 GEN
Solar/Wind Harmer
0.024
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
10.525
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.551
965041AG1-368 GEN
Solar/Wind Harmer
4.084
247521TR3_G114
Solar/Wind Harmer
0.147
965051AG1-369 GEN
Solar/Wind Harmer
2.03
970031AG2-029 GEN
Solar/Wind Harmer
2.145
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.551
959331AF2-224 GEN
Solar/Wind Harmer
2.729
971771AH1-392 GEN
Solar/Wind Harmer
3.882
971567AH1-282 GEN
Solar/Wind Harmer
2.943
270526AF1-158 GEN
Solar/Wind Harmer
0
270377AD1-106 GEN
Solar/Wind Harmer
1.423
960681AF2-359 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
963791AG1-232 GEN
Solar/Wind Harmer
4.865
270071AF1-092 GEN
Solar/Wind Harmer
6.544
958391AF2-133 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.679
274800UNIV PARK;3U
Adder
2.76
274801UNIV PARK;4U
Adder
2.76
971611AH1-305 GEN
Solar/Wind Harmer
1.964
960591AF2-350 GEN
Solar/Wind Harmer
3.298
274775LINCOLN ;6U
Adder
3.988
274776LINCOLN ;7U
Adder
3.988
274777LINCOLN ;8U
Adder
3.988
972228AH1-698 GEN2
Adder
1.746
972227AH1-698 GEN1
Adder
1.229
274687WILL CNTY;4U
Adder
13.128
274687WILL CNTY;4U
Adder
13.128
274675JOLIET 29;7U
Adder
14.386
274675JOLIET 29;7U
Adder
13.872
274728ELWOOD EC;5P
Adder
7.694
274731ELWOOD EC;2P
Adder
7.694
274733ELWOOD EC;3P
Adder
7.694
274735ELWOOD EC;4P
Adder
7.694
970833AG2-524 GEN
Solar/Wind Harmer
3.575
970833AG2-524 GEN
Solar/Wind Harmer
2.383
274744AC1-111 GEN8
Adder
2.587
274746AC1-111 G10
Adder
2.587
970073AG2-061 GEN
Solar/Wind Harmer
1.066
24729505KEY G4
Adder
2.959
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.74
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
1.231
276861AD2-134 GEN
Solar/Wind Harmer
0.056
276863AD2-134 GEN
Solar/Wind Harmer
0.056
971171AH1-044 GEN
Solar/Wind Harmer
6.289
274823ROCKFORD ;21
Adder
8.764
970169AG2-114 GEN
Solar/Wind Harmer
3.128
926823AC1-168 GEN
Solar/Wind Harmer
0.532
274856ECOGROVE ;U1
Solar/Wind Harmer
0.073
971681AH1-341 GEN
Solar/Wind Harmer
5.008
24386405FR-21G C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.839
276741O09 GEN1
Solar/Wind Harmer
0.109
274877BISHOP HL;1U
Solar/Wind Harmer
0.102
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.212
963841AG1-237 GEN
Solar/Wind Harmer
1.317
274854TWINGROVE;U2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.692
971609AH1-304 GEN
Solar/Wind Harmer
0.493
945581AF1-223 GEN
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
4.613
241985AE1-237 GEN
Solar/Wind Helper
0.141
241982AE2-343 S C
Solar/Wind Helper
0.127
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
20334926Z1-069 C
Solar/Wind Helper
0.69
24189902OREGON_CT2
50/50
2.678
23856402BAYSG1
50/50
1.432
23888702TROY G3
50/50
1.835
972253AH1-711 GEN
50/50
56.096
23860302FRMENG 3
50/50
3.525
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
4.136
23906502RICHG2&3
Adder
1.423
960841AF2-375 GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.175
270489AE1-102 GEN1
Solar/Wind Harmer
0.565
965421AG1-410 GEN
Solar/Wind Harmer
12.914
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.181
945111AF1-176 GEN
Solar/Wind Harmer
7.302
957891AF2-083 GEN
Solar/Wind Harmer
6.792
24639705ELKHART HY
Adder
0.088
270317AD1-130_GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
3.899
970373AG2-245 GEN
Solar/Wind Harmer
7.341
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
4.006
274754CRETE EC ;4U
Adder
4.006
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.387
274723RIVER EC ;12
Adder
8.645
274812UNIV PK N;8U
Adder
2.405
274802UNIV PARK;5U
Adder
2.77
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.124
274773LINCOLN ;4U
Adder
3.988
274774LINCOLN ;5U
Adder
3.988
274676JOLIET 29;8U
Adder
14.386
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.694
274674JOLIET 9 ;6U
Adder
7.206
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
2.587
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.524
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
8.262
274828WAUKEGAN ;BP
Adder
5.073
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.385
276882AE2-255 GEN
Solar/Wind Harmer
0.371
962781AG1-127 GEN
Solar/Wind Harmer
3.029
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.664
957471AF2-041 GEN
Solar/Wind Harmer
9.434
959081AF2-199 GEN
Solar/Wind Harmer
3.145
971067AG2-660 GEN
Solar/Wind Harmer
1.048
274822ROCKFORD ;11
Adder
8.828
970569AG2-363 GEN
Solar/Wind Harmer
9.4
970819AG2-516 GEN
Solar/Wind Harmer
3.751
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.136
274766LEE CO EC;7U
Adder
4.087
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
0.908
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276708O09 GEN2
Solar/Wind Harmer
0.109
958861AF2-177 GEN
Solar/Wind Harmer
1.329
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.283
945371AF1-202 GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
4.613
203947AF1-006 C
Solar/Wind Helper
0.409
961971AG1-040 GEN
Solar/Wind Helper
0.358
203830AF1-094 GEN
Solar/Wind Helper
0.347
203979AG1-198 GEN
Solar/Wind Helper
0.208
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203855AF2-088 C
Solar/Wind Helper
0.072
962511AG1-100 GEN
Solar/Wind Helper
0.366
203854AF2-039 C
Solar/Wind Helper
0.15
20398826ARMNA MT
Solar/Wind Helper
0.705
991177J1571 G
External Queue
15.716124534606934
991182J1586 G
External Queue
25.29424285888672
990527J1329
External Queue
1.8514890670776367
990142J1224
External Queue
13.534384727478027
NYPJM->LTFIMP_NY
CLTF
2.157
LGEELTFEXP_LGEE->PJM
CLTF
2.099
WECLTFEXP_WEC->PJM
CLTF
1.715
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.396
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.063
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.256
MECLTFEXP_MEC->PJM
CLTF
6.691
SIGELTFEXP_SIGE->PJM
CLTF
0.175
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
LAGNLTFEXP_LAGN->PJM
CLTF
5.139
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.291
TVALTFEXP_TVA->PJM
CLTF
2.335

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.65 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:1922.03
MW Contribution:
7.98
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.382
24729305KEY G2
50/50
0.375
24729205KEY G1
50/50
0.374
247620Y3-023
50/50
0.478
960851AF2-376 GEN
50/50
2.145
24643105BUCHANAN
50/50
0.011
270102X2-052 ST
50/50
1.316
270100X2-052 CT1
50/50
1.216
270101X2-052 CT2
50/50
1.216
270246TR4_N_V150
Solar/Wind Harmer
0.047
270247TR4_N_V136
Solar/Wind Harmer
0.047
942221AE2-234 GEN
Solar/Wind Harmer
2.915
944231AF1-091 GEN
Solar/Wind Harmer
16.486
944541AF1-119 GEN
Solar/Wind Harmer
0.437
960971AF2-388 GEN
Solar/Wind Harmer
3.84
970349AG2-230 GEN
Solar/Wind Harmer
9.006
961051AF2-396 GEN
Solar/Wind Harmer
11.975
961051AF2-396 GEN
Solar/Wind Harmer
7.983
270031AE2-169
Solar/Wind Harmer
3.187
270599AE1-208 GEN
Solar/Wind Harmer
5.311
965681AG1-436 GEN
Solar/Wind Harmer
7.151
965791AG1-447 GEN
Solar/Wind Harmer
5.244
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.421
247621Y3-024
Adder
0.188
274805UNIV PK N;1U
Adder
3.909
274808UNIV PK N;4U
Adder
3.883
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.547
274771LINCOLN ;2U
Adder
6.547
274888KELLY CRK;1U
Solar/Wind Harmer
0.312
276776AD2-060 GEN
Solar/Wind Harmer
0.571
958011AF2-095 GEN
Solar/Wind Harmer
7.714
970941AG2-585 GEN
Solar/Wind Harmer
2.946
276897AD1-100 C
Solar/Wind Harmer
13.263
274674JOLIET 9 ;6U
Adder
11.68
276893AG1-478 C
Solar/Wind Harmer
0.353
970291AG2-192 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.317
971613AH1-306 GEN
Solar/Wind Harmer
2.514
958481AF2-142 GEN
Solar/Wind Harmer
7.796
274696ROCKY RD ;4P
Adder
8.451
274695ROCKY RD ;2P
Adder
8.256
274693ROCKY RD ;1P
Adder
8.175
274697ROCKY RD ;3P
Adder
2.243
274683WAUKEGAN ;8U
Adder
15.599
274683WAUKEGAN ;8U
Adder
13.149
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
15.403
958491AF2-143 GEN
Solar/Wind Harmer
7.702
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
10.069
971343AH1-151 GEN
Solar/Wind Harmer
10.069
972235AH1-702 GEN1
Adder
1.809
972236AH1-702 GEN2
Adder
1.573
938861AE1-114 GEN
Solar/Wind Harmer
2.807
274764LEE CO EC;5U
Adder
6.597
274765LEE CO EC;6U
Adder
6.597
274762LEE CO EC;3U
Adder
6.581
274763LEE CO EC;4U
Adder
6.519
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.787
276645AC1-214 GEN1
Solar/Wind Harmer
0.191
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.55
942111AE2-223 GEN
Solar/Wind Harmer
1.562
960611AF2-352 GEN
Solar/Wind Harmer
1.575
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.631
970885AG2-551 GEN
Solar/Wind Harmer
1.544
970241AG2-163 GEN
Solar/Wind Harmer
2.669
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.046
276838X2-022 GEN2
Solar/Wind Harmer
0.248
276916AD2-100_GEN
Solar/Wind Harmer
8.848
276911AD2-131_GEN
Solar/Wind Harmer
0.583
960861AF2-377 GEN
50/50
2.456
970521AG2-332 GEN
50/50
11.157
24639705ELKHART HY
50/50
0.154
270143AC1-141 CT2_
50/50
2.081
24344105CKG2
50/50
6.284
24307105BERRINSP G
50/50
0.018
965011AG1-365 GEN
Solar/Wind Harmer
13.973
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.92
958861AF2-177 GEN
Solar/Wind Harmer
2.759
945111AF1-176 GEN
Solar/Wind Harmer
10.951
957891AF2-083 GEN
Solar/Wind Harmer
10.053
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.079
970373AG2-245 GEN
Solar/Wind Harmer
11.559
274751CRETE EC ;1U
Adder
6.49
274754CRETE EC ;4U
Adder
6.49
274723RIVER EC ;12
Adder
14.067
274812UNIV PK N;8U
Adder
3.9
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.547
274774LINCOLN ;5U
Adder
6.547
274802UNIV PARK;5U
Adder
4.495
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.946
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
23.324
274674JOLIET 9 ;6U
Adder
11.68
274732ELWOOD EC;7P
Adder
12.465
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.552
270594AE1-207 GEN
Solar/Wind Harmer
5.867
270032AE2-172
Solar/Wind Harmer
3.492
270005AE1-210 C O1
Solar/Wind Harmer
1.133
274745AC1-111 GEN9
Adder
4.189
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.845
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.842
274682WAUKEGAN ;7U
Adder
13.321
274828WAUKEGAN ;BP
Adder
8.177
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.874
939401AE1-172 GEN
Solar/Wind Harmer
3.83
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.596
971997AH1-543 GEN
Solar/Wind Harmer
2.669
957471AF2-041 GEN
Solar/Wind Harmer
15.103
959081AF2-199 GEN
Solar/Wind Harmer
5.034
971067AG2-660 GEN
Solar/Wind Harmer
1.678
274822ROCKFORD ;11
Adder
14.119
276903AD2-071 C
Solar/Wind Harmer
5.594
970819AG2-516 GEN
Solar/Wind Harmer
5.99
970569AG2-363 GEN
Solar/Wind Harmer
14.964
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.581
274766LEE CO EC;7U
Adder
6.504
276708O09 GEN2
Solar/Wind Harmer
0.172
276646AC1-214 GEN2
Solar/Wind Harmer
0.191
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.73
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.397
963741AG1-226 GEN
Solar/Wind Harmer
10.829
276621W2-048 GEN
Solar/Wind Harmer
0.22
965911AG1-460 GEN
Solar/Wind Harmer
0.85
24728605AND G2
Adder
2.182
970773AG2-487 GEN
Solar/Wind Harmer
0.657
246936BC-WTG1
Solar/Wind Helper
10.844
270317AD1-130_GEN
Solar/Wind Helper
4.072
270485AE1-090_GEN
Solar/Wind Helper
0.32
270391AF1-285 GEN3
Solar/Wind Helper
0.582
270578AF1-285 GEN2
Solar/Wind Helper
0.582
270286AF1-227 GEN2
Solar/Wind Helper
0.675
960841AF2-375 GEN
Solar/Wind Helper
1.143
945391AF1-204 GEN
Solar/Wind Harmer
4.379
970623AG2-406 GEN
Solar/Wind Harmer
0.684
971587AH1-292 GEN
Solar/Wind Harmer
2.578
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.844
270462AD2-086
Solar/Wind Helper
3.683
247522W1-056 GEN
Solar/Wind Helper
1.146
253378AE2-206_GEN
Solar/Wind Helper
0.688
270349AD2-093_GEN
Solar/Wind Helper
0.824
270471AD2-092_GEN
Solar/Wind Helper
0.824
241960AC2-195 GEN
Solar/Wind Helper
0.664
24729505KEY G4
50/50
6.995
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.016
270144AC1-141 ST1_
50/50
1.838
24344005CKG1
50/50
5.28
959331AF2-224 GEN
Solar/Wind Harmer
9.781
963791AG1-232 GEN
Solar/Wind Harmer
12.238
970031AG2-029 GEN
Solar/Wind Harmer
4.668
965041AG1-368 GEN
Solar/Wind Harmer
8.594
270071AF1-092 GEN
Solar/Wind Harmer
14.854
247521TR3_G114
Solar/Wind Harmer
0.267
965051AG1-369 GEN
Solar/Wind Harmer
3.677
971771AH1-392 GEN
Solar/Wind Harmer
6.058
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.946
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.189
274775LINCOLN ;6U
Adder
6.547
274776LINCOLN ;7U
Adder
6.547
274777LINCOLN ;8U
Adder
6.547
972037AH1-567 GEN1
Adder
0.141
274827FISK ;RP
Adder
5.975
274800UNIV PARK;3U
Adder
4.482
274801UNIV PARK;4U
Adder
4.482
960591AF2-350 GEN
Solar/Wind Harmer
5.357
972228AH1-698 GEN2
Adder
2.836
972227AH1-698 GEN1
Adder
1.997
274687WILL CNTY;4U
Adder
21.288
274687WILL CNTY;4U
Adder
21.288
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
23.324
274675JOLIET 29;7U
Adder
22.491
274728ELWOOD EC;5P
Adder
12.465
274731ELWOOD EC;2P
Adder
12.464
274733ELWOOD EC;3P
Adder
12.464
274735ELWOOD EC;4P
Adder
12.464
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.003
970833AG2-524 GEN
Solar/Wind Harmer
5.794
970833AG2-524 GEN
Solar/Wind Harmer
3.862
971611AH1-305 GEN
Solar/Wind Harmer
3.121
274744AC1-111 GEN8
Adder
4.189
274746AC1-111 G10
Adder
4.189
970073AG2-061 GEN
Solar/Wind Harmer
1.711
247536S-71 GEN
Solar/Wind Harmer
0.205
971411AH1-196 GEN
Solar/Wind Harmer
7.602
971675AH1-338 GEN
Solar/Wind Harmer
1.975
276861AD2-134 GEN
Solar/Wind Harmer
0.09
276863AD2-134 GEN
Solar/Wind Harmer
0.09
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
10.069
274823ROCKFORD ;21
Adder
14.017
274856ECOGROVE ;U1
Solar/Wind Harmer
0.116
926823AC1-168 GEN
Solar/Wind Harmer
0.847
970169AG2-114 GEN
Solar/Wind Harmer
4.974
971681AH1-341 GEN
Solar/Wind Harmer
7.978
971549AH1-272 GEN
Solar/Wind Harmer
10.208
972267AH1-718 GEN
Adder
2.917
276741O09 GEN1
Solar/Wind Harmer
0.172
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.162
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
5.047
946321AF1-296 GEN
Solar/Wind Harmer
2.661
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.041
270543AE2-219 C
Solar/Wind Harmer
3.242
276668AB2-070 GEN1
Solar/Wind Harmer
0.176
276848AB2-070 GEN3
Solar/Wind Harmer
0.175
276849AB2-070 GEN2
Solar/Wind Harmer
0.176
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
6.154
944221AF1-090 GEN
Solar/Wind Harmer
2.4
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.567
270223U2-072_GEN1
Solar/Wind Helper
0.859
270224U2-072_GEN2
Solar/Wind Helper
0.859
270227U2-072_GEN3
Solar/Wind Helper
0.859
270228U2-072_GEN4
Solar/Wind Helper
0.859
270231U2-072_GEN5
Solar/Wind Helper
0.859
966831AG1-554 GEN
Solar/Wind Helper
0.861
270499AE1-146 GEN
Solar/Wind Helper
1.911
945641AF1-229 GEN
Solar/Wind Helper
0.907
970583AG2-370 GEN
50/50
2.865
270142AC1-141 CT1_
50/50
2.081
24642205MAYFLWER
50/50
0.032
944961AF1-161 GEN
50/50
2.458
962601AG1-109 GEN
50/50
2.458
965021AG1-366 GEN
Solar/Wind Harmer
4.658
270043AE2-236 GEN
Solar/Wind Harmer
5.337
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
32.656
24695305TIMB G C
Solar/Wind Harmer
0.545
945111AF1-176 GEN
Solar/Wind Harmer
4.975
971347AH1-153 GEN
Solar/Wind Harmer
3.002
270505AE1-170 C O1
Solar/Wind Harmer
6.29
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.571
274752CRETE EC ;2U
Adder
6.49
274753CRETE EC ;3U
Adder
6.49
274724RIVER EC ;11
Adder
13.897
274814UNIV PK N;0U
Adder
3.935
274807UNIV PK N;3U
Adder
3.926
274811UNIV PK N;7U
Adder
3.9
274772LINCOLN ;3U
Adder
6.547
274803UNIV PARK;6U
Adder
4.495
274826FISK ;BP
Adder
8.431
972038AH1-567 GEN2
Adder
0.281
274887GEN-1.85
Solar/Wind Harmer
0.139
276843GEN-1.7
Solar/Wind Harmer
0.173
276806AD2-047 C O1
Solar/Wind Harmer
3.036
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.564
970707AG2-453 GEN
Solar/Wind Harmer
17.395
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.491
274729ELWOOD EC;1P
Adder
12.464
274730ELWOOD EC;6P
Adder
12.465
274734ELWOOD EC;8P
Adder
12.465
274736ELWOOD EC;9P
Adder
12.465
970289AG2-191 GEN
Solar/Wind Harmer
0.58
946031AF1-268 GEN
Solar/Wind Harmer
4.982
943121AE2-341 GEN
Solar/Wind Harmer
8.771
943591AF1-030 GEN
Solar/Wind Harmer
5.832
270004AE1-209 GEN
Solar/Wind Harmer
1.133
274862TOP CROP ;2U
Solar/Wind Harmer
0.701
970825AG2-519 GEN
Solar/Wind Harmer
3.908
274682WAUKEGAN ;7U
Adder
13.321
276868AE1-113 GEN
Solar/Wind Harmer
1.021
274879MINONK ;1U
Solar/Wind Harmer
0.213
946671AF1-331 GEN
Solar/Wind Harmer
0.54
274855GSG-6 ;RU
Solar/Wind Harmer
0.185
274850MENDOTA H;RU
Solar/Wind Harmer
0.059
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
5.046
959091AF2-200 GEN
Solar/Wind Harmer
10.069
970571AG2-364 GEN
Solar/Wind Harmer
9.976
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.581
274767LEE CO EC;8U
Adder
6.504
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.162
965091AG1-374 GEN
Solar/Wind Harmer
14.177
959611AF2-252 GEN
Solar/Wind Harmer
1.575
965931AG1-462 GEN
Solar/Wind Harmer
12.05
971087AG2-675 GEN
Solar/Wind Harmer
2.52
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.067
957381AF2-032 GEN
Solar/Wind Harmer
0.966
942481AE2-261 GEN
Solar/Wind Harmer
12.705
970193AG2-126 GEN
Solar/Wind Harmer
6.182
24728705AND G3
Adder
4.563
24728505AND G1
Adder
2.182
246938BC-WTG3
Solar/Wind Helper
11.03
942871AE2-306 GEN
Solar/Wind Helper
0.436
270284AF1-227 GEN1
Solar/Wind Helper
1.841
270287AF1-227 GEN3
Solar/Wind Helper
0.675
276820AF1-078_GEN
Solar/Wind Helper
0.321
270541AE2-072 C
Solar/Wind Helper
0.902
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
NYPJM->LTFIMP_NY
CLTF
1.125
LGEELTFEXP_LGEE->PJM
CLTF
1.97
WECLTFEXP_WEC->PJM
CLTF
2.738
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.411
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.755
MECLTFEXP_MEC->PJM
CLTF
10.148
SIGELTFEXP_SIGE->PJM
CLTF
0.212
AG2-052LTFEXP_AG2-052->PJM
LTF
0.177
AH1-155LTFEXP_AH1-155->PJM
LTF
0.266
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.75
LAGNLTFEXP_LAGN->PJM
CLTF
6.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.165
TVALTFEXP_TVA->PJM
CLTF
2.538

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.18 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2486.65
MW Contribution:
7.0
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24735105WLF2G1
Adder
4.907
24734705WLF1G3
Adder
4.896
24734805WLF1G4
Adder
4.896
24734905WLF1G5
Adder
4.896
966391AG1-508 GEN
Solar/Wind Harmer
2.783
971981AH1-535 GEN
Solar/Wind Harmer
7.894
971313AH1-133 GEN
Solar/Wind Harmer
4.584
970281AG2-184 GEN
Solar/Wind Harmer
14.612
962211AG1-066 GEN
Solar/Wind Harmer
1.641
270399AC1-101 GEN
Solar/Wind Harmer
2.774
270400AC1-102 GEN
Solar/Wind Harmer
2.774
957241AF2-018 GEN
Solar/Wind Harmer
2.859
270053AF1-130 C
Solar/Wind Harmer
11.424
3429211JKCT 2G
Adder
6.347
339216AC1-074 GEN
Solar/Wind Harmer
0.857
972163AH1-664 GEN
Solar/Wind Harmer
4.973
972165AH1-665 GEN
Solar/Wind Harmer
3.979
270444AC2-157 GEN1
Solar/Wind Harmer
2.733
270445AC2-157 GEN2
Solar/Wind Harmer
2.733
944221AF1-090 GEN
Solar/Wind Harmer
5.329
276763AC1-053 GEN1
Solar/Wind Harmer
1.887
276764AC1-053 GEN2
Solar/Wind Harmer
1.887
276668AB2-070 GEN1
Solar/Wind Harmer
1.055
276848AB2-070 GEN3
Solar/Wind Harmer
1.055
276849AB2-070 GEN2
Solar/Wind Harmer
1.055
946321AF1-296 GEN
Solar/Wind Harmer
4.94
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
274853TWINGROVE;U1
Solar/Wind Harmer
3.384
274854TWINGROVE;U2
Solar/Wind Harmer
3.313
274877BISHOP HL;1U
Solar/Wind Harmer
1.582
276741O09 GEN1
Solar/Wind Harmer
1.676
972267AH1-718 GEN
Adder
1.953
276726Z2-087_GEN
Solar/Wind Harmer
3.696
959341AF2-225 GEN
Solar/Wind Harmer
7.012
971681AH1-341 GEN
Solar/Wind Harmer
7
274856ECOGROVE ;U1
Solar/Wind Harmer
1.571
276611AD2-172 GEN
Solar/Wind Harmer
1.192
276612AE2-035 GEN
Solar/Wind Harmer
1.192
274823ROCKFORD ;21
Adder
9.053
926823AC1-168 GEN
Solar/Wind Harmer
1.997
963841AG1-237 GEN
Solar/Wind Harmer
5.074
971171AH1-044 GEN
Solar/Wind Harmer
9.281
970169AG2-114 GEN
Solar/Wind Harmer
4.633
276861AD2-134 GEN
Solar/Wind Harmer
0.827
276863AD2-134 GEN
Solar/Wind Harmer
0.827
971675AH1-338 GEN
Solar/Wind Harmer
8.334
971411AH1-196 GEN
Solar/Wind Harmer
6.945
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
25196508WSDLE4
Adder
3.893
274744AC1-111 GEN8
Adder
2.557
274746AC1-111 G10
Adder
2.557
274728ELWOOD EC;5P
Adder
7.484
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
274735ELWOOD EC;4P
Adder
7.484
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
315616AA1-038_C
Solar/Wind Helper
1.809
3148463FAIRFLD
Solar/Wind Helper
0.399
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316258AE1-075 C
Solar/Wind Helper
0.181
316405AF2-144 C
Solar/Wind Helper
0.151
316164AC1-076 GEN
Solar/Wind Helper
0.62
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.113
276889AE2-281 GEN
Solar/Wind Harmer
0.021
270214AC2-123 GEN
Solar/Wind Harmer
2.486
971277AH1-098 GEN
Solar/Wind Harmer
3.312
24728205BUCHG1
Adder
3.63
971225AH1-072 GEN
Solar/Wind Harmer
1.502
971227AH1-073 GEN
Solar/Wind Harmer
1.502
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
966021AG1-471 GEN
Solar/Wind Harmer
3.282
971485AH1-239 GEN
Solar/Wind Harmer
4.84
339231AF1-038_GEN
Solar/Wind Harmer
1.081
964781AG1-341 GEN
Solar/Wind Harmer
6.17
339236AF1-050_GEN
Solar/Wind Harmer
1.045
942891AE2-308 GEN
Solar/Wind Harmer
5.443
964571AG1-320 GEN
Solar/Wind Harmer
4.43
971125AH1-004 GEN
Solar/Wind Harmer
2.108
970107AG2-081 GEN
Solar/Wind Harmer
1.581
972043AH1-570 GEN
Solar/Wind Harmer
1.293
972045AH1-571 GEN
Solar/Wind Harmer
1.034
276916AD2-100_GEN
Solar/Wind Harmer
10.169
276911AD2-131_GEN
Solar/Wind Harmer
2.055
276615X2-022 GEN
Solar/Wind Harmer
0.938
24735205WLF2G2
Adder
4.907
24728305BUCHG2
Adder
3.63
971687AH1-348 GEN
Solar/Wind Harmer
0.746
971403AH1-188 GEN
Solar/Wind Harmer
9.183
944971AF1-162 GEN
Solar/Wind Harmer
4.503
24723205RIVRG3
Adder
11.612
270336AE1-100 GEN
Solar/Wind Harmer
1.01
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
8.649
339241AF1-083 GEN
Solar/Wind Harmer
0.951
24686505CER G6
Adder
4.748
339211AE2-254 GEN
Solar/Wind Harmer
0.852
970653AG2-424 GEN
Solar/Wind Harmer
2.669
3429241JKCT 3G
Adder
6.43
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.667
943111AE2-339 GEN
Solar/Wind Harmer
0.467
943811AF1-049 GEN
Solar/Wind Harmer
1.99
339221AD2-048_GEN
Solar/Wind Harmer
0.786
970091AG2-072 GEN
Adder
38.065
945681AF1-233 GEN
Solar/Wind Harmer
9.341
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
2.987
276686W4-005 GEN3
Solar/Wind Harmer
1.44
25196008MFTGT1
Adder
0.654
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
3.029
276708O09 GEN2
Solar/Wind Harmer
1.676
276646AC1-214 GEN2
Solar/Wind Harmer
0.626
25196808ZIMRHP
Adder
35.505
276655WTG1_EQ
Solar/Wind Harmer
4.08
276656WTG2_EQ
Solar/Wind Harmer
0.54
939741AE1-205 GEN
Solar/Wind Harmer
9.349
274858EASY ROAD;U2
Solar/Wind Harmer
2.239
274761LEE CO EC;2U
Adder
4.348
274766LEE CO EC;7U
Adder
4.297
963741AG1-226 GEN
Solar/Wind Harmer
21.023
970819AG2-516 GEN
Solar/Wind Harmer
5.587
274822ROCKFORD ;11
Adder
9.119
970569AG2-363 GEN
Solar/Wind Harmer
13.937
957471AF2-041 GEN
Solar/Wind Harmer
13.921
959081AF2-199 GEN
Solar/Wind Harmer
4.64
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
274745AC1-111 GEN9
Adder
2.557
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
274676JOLIET 29;8U
Adder
13.963
3148013FISHERV
Solar/Wind Helper
0.287
316499AE2-029_GEN
Solar/Wind Helper
0.937
970563AG2-360 GEN
50/50
26.903
943031AE2-326 GEN
Solar/Wind Harmer
3.912
962751AG1-124 GEN
Solar/Wind Harmer
9.059
960911AF2-382 GEN
Solar/Wind Harmer
5.846
971461AH1-227 GEN
Solar/Wind Harmer
3.852
972103AH1-617 GEN
Solar/Wind Harmer
13.916
972273AH1-721 GEN
Adder
50.356
339255AE2-071 GEN
Solar/Wind Harmer
0.685
339250AF1-203 GEN
Solar/Wind Harmer
0.353
339206AE1-143 GEN
Solar/Wind Harmer
1.218
24686405CER G5
Adder
4.71
970093AG2-073 GEN
Solar/Wind Harmer
2.932
970653AG2-424 GEN
Solar/Wind Harmer
0.386
270030AE2-140 GEN
Solar/Wind Harmer
10.987
970455AG2-298 GEN
Solar/Wind Harmer
1.905
3429391JKCT 9G
Adder
4.482
339243AC2-075 GEN1
Solar/Wind Harmer
0.232
972167AH1-666 GEN
Solar/Wind Harmer
3.959
958171AF2-111 GEN
Solar/Wind Harmer
12.218
942481AE2-261 GEN
Solar/Wind Harmer
14.451
957381AF2-032 GEN
Solar/Wind Harmer
0.966
970193AG2-126 GEN
Solar/Wind Harmer
7.158
276785W4-005 GEN1
Solar/Wind Harmer
1.44
971993AH1-541 GEN
Solar/Wind Harmer
4.402
965931AG1-462 GEN
Solar/Wind Harmer
12.097
971087AG2-675 GEN
Solar/Wind Harmer
1.765
270186AC1-089 GEN
Solar/Wind Harmer
2.883
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.771
24728505AND G1
Adder
1.803
965091AG1-374 GEN
Solar/Wind Harmer
14.092
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
1.869
274878BISHOP HL;2U
Solar/Wind Harmer
1.582
274851PROVIDENC;RU
Solar/Wind Harmer
1.332
274849CRESCENT ;1U
Solar/Wind Harmer
0.865
276603SUBLETTE C
Solar/Wind Harmer
0.49
274857EASY ROAD;U1
Solar/Wind Harmer
2.239
274760LEE CO EC;1U
Adder
4.348
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
276838X2-022 GEN2
Solar/Wind Harmer
0.111
945391AF1-204 GEN
Solar/Wind Harmer
6.651
274880W4-005 GEN4
Solar/Wind Harmer
1.44
276174W4-005 GEN2
Solar/Wind Harmer
1.44
960611AF2-352 GEN
Solar/Wind Harmer
1.092
276158O29GEN2
Solar/Wind Harmer
2.347
276157O29GEN1
Solar/Wind Harmer
1.785
276645AC1-214 GEN1
Solar/Wind Harmer
0.626
942111AE2-223 GEN
Solar/Wind Harmer
3.832
274764LEE CO EC;5U
Adder
4.358
274765LEE CO EC;6U
Adder
4.358
274762LEE CO EC;3U
Adder
4.348
274763LEE CO EC;4U
Adder
4.307
970241AG2-163 GEN
Solar/Wind Harmer
11.68
938861AE1-114 GEN
Solar/Wind Harmer
3.826
972235AH1-702 GEN1
Adder
1.172
972236AH1-702 GEN2
Adder
1.019
971341AH1-150 GEN
Solar/Wind Harmer
9.281
971343AH1-151 GEN
Solar/Wind Harmer
9.281
252509AD1-136 GEN
Solar/Wind Harmer
0.119
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
25194508D.CRK3
Adder
0.65
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.064
274697ROCKY RD ;3P
Adder
1.389
24728805RICHG1
Adder
1.729
24728905RICHG2
Adder
1.729
274674JOLIET 9 ;6U
Adder
7.01
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
237061AD1-155 GEN
Solar/Wind Helper
0.84
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238147AE2-230_GEN1
Solar/Wind Helper
0.214
238148AE2-230_GEN2
Solar/Wind Helper
0.214
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316312AB1-027
Solar/Wind Helper
0.234
316097T157 G90
Solar/Wind Helper
0.557
316045AC1-158 PL2
Solar/Wind Helper
2.117
316450AC1-158 RIC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.609
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
316487AF1-042 GEN
Solar/Wind Helper
0.113
276872AE1-163_GEN1
Solar/Wind Harmer
0.072
276876AE1-163_GEN2
Solar/Wind Harmer
0.072
315821AE2-092 GEN
Solar/Wind Helper
1.831
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
23583801GRNGAP
Solar/Wind Helper
2.128
316095T157 G97
Solar/Wind Helper
0.557
316075AC2-137 C
Solar/Wind Helper
0.18
316223AC1-118
Solar/Wind Helper
0.174
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
270367AC2-061_GEN
Solar/Wind Harmer
1.479
970571AG2-364 GEN
Solar/Wind Harmer
9.291
959091AF2-200 GEN
Solar/Wind Harmer
9.281
252507AC2-088 GEN
Solar/Wind Harmer
0.831
274855GSG-6 ;RU
Solar/Wind Harmer
1.71
274850MENDOTA H;RU
Solar/Wind Harmer
1.189
276602WESTBROOK C
Solar/Wind Harmer
0.984
276799AD1-013 GEN
Solar/Wind Harmer
1.023
946671AF1-331 GEN
Solar/Wind Harmer
0.194
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
25196608WSDLE5
Adder
3.933
274729ELWOOD EC;1P
Adder
7.484
274730ELWOOD EC;6P
Adder
7.484
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
5.57
3147983MERCK5
Solar/Wind Helper
0.108
316192AB2-158 GEN
Solar/Wind Helper
0.989
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
3146776BUCKING
Solar/Wind Helper
0.05
238152AF2-075_GEN
Solar/Wind Helper
0.306
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.173
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.959
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
WECLTFEXP_WEC->PJM
CLTF
1.782
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
TVALTFEXP_TVA->PJM
CLTF
6.216

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2430.97
MW Contribution:
5.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971277AH1-098 GEN
Solar/Wind Harmer
2.311
24728205BUCHG1
Adder
3.63
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
24723005RIVRG1
Adder
11.612
24723105RIVRG2
Adder
11.612
966021AG1-471 GEN
Solar/Wind Harmer
2.29
971485AH1-239 GEN
Solar/Wind Harmer
3.377
964781AG1-341 GEN
Solar/Wind Harmer
4.305
942891AE2-308 GEN
Solar/Wind Harmer
3.798
964571AG1-320 GEN
Solar/Wind Harmer
3.443
971125AH1-004 GEN
Solar/Wind Harmer
1.471
970107AG2-081 GEN
Solar/Wind Harmer
1.103
972043AH1-570 GEN
Solar/Wind Harmer
0.938
972045AH1-571 GEN
Solar/Wind Harmer
0.751
971587AH1-292 GEN
Solar/Wind Harmer
2.505
276916AD2-100_GEN
Solar/Wind Harmer
7.095
276911AD2-131_GEN
Solar/Wind Harmer
0.467
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.188
945391AF1-204 GEN
Solar/Wind Harmer
3.538
960611AF2-352 GEN
Solar/Wind Harmer
1.092
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.528
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274764LEE CO EC;5U
Adder
4.358
274765LEE CO EC;6U
Adder
4.358
274762LEE CO EC;3U
Adder
4.348
274763LEE CO EC;4U
Adder
4.307
970241AG2-163 GEN
Solar/Wind Harmer
1.901
938861AE1-114 GEN
Solar/Wind Harmer
1.845
972235AH1-702 GEN1
Adder
1.172
972236AH1-702 GEN2
Adder
1.019
971341AH1-150 GEN
Solar/Wind Harmer
6.475
971343AH1-151 GEN
Solar/Wind Harmer
6.475
252509AD1-136 GEN
Solar/Wind Harmer
0.016
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.364
962691AG1-118 GEN
Solar/Wind Harmer
9.643
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.815
25183208HLCRTG
Solar/Wind Harmer
0
274683WAUKEGAN ;8U
Adder
9.688
274683WAUKEGAN ;8U
Adder
8.167
25194408D.CRK1
Adder
3.476
25194508D.CRK3
Adder
0.65
274696ROCKY RD ;4P
Adder
5.236
274695ROCKY RD ;2P
Adder
5.115
274693ROCKY RD ;1P
Adder
5.064
274697ROCKY RD ;3P
Adder
1.389
958481AF2-142 GEN
Solar/Wind Harmer
4.795
24728805RICHG1
Adder
1.729
24728905RICHG2
Adder
1.729
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.01
276893AG1-478 C
Solar/Wind Harmer
0.212
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
7.927
274888KELLY CRK;1U
Solar/Wind Harmer
0.184
276776AD2-060 GEN
Solar/Wind Harmer
0.337
958011AF2-095 GEN
Solar/Wind Harmer
4.553
970941AG2-585 GEN
Solar/Wind Harmer
1.739
926881AC1-175 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.41
970291AG2-192 GEN
Solar/Wind Harmer
0.189
971613AH1-306 GEN
Solar/Wind Harmer
1.512
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
1.712
270599AE1-208 GEN
Solar/Wind Harmer
2.854
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
3.108
970885AG2-551 GEN
Solar/Wind Harmer
1.036
964611AG1-324 GEN
Solar/Wind Harmer
0.233
270201AC2-176 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.205
960971AF2-388 GEN
Solar/Wind Harmer
1.8
965681AG1-436 GEN
Solar/Wind Harmer
3.818
965791AG1-447 GEN
Solar/Wind Harmer
2.8
942221AE2-234 GEN
Solar/Wind Harmer
1.218
970349AG2-230 GEN
Solar/Wind Harmer
4.536
3132123MT JACKSON
Solar/Wind Helper
0.746
966001AG1-469 GEN
Solar/Wind Helper
0.172
237061AD1-155 GEN
Solar/Wind Helper
0.84
316313AB2-026
Solar/Wind Helper
0.201
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.168
238147AE2-230_GEN1
Solar/Wind Helper
0.214
238148AE2-230_GEN2
Solar/Wind Helper
0.214
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316006AB2-029 C
Solar/Wind Helper
0.059
316312AB1-027
Solar/Wind Helper
0.234
316097T157 G90
Solar/Wind Helper
0.557
316045AC1-158 PL2
Solar/Wind Helper
2.117
316450AC1-158 RIC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.609
315976AC1-164 GENA
Solar/Wind Helper
1.499
316169AC1-164_GENC
Solar/Wind Helper
1.295
3142946ENON
Solar/Wind Helper
0.011
24735205WLF2G2
50/50
5.207
24728305BUCHG2
Adder
3.63
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971403AH1-188 GEN
Solar/Wind Harmer
6.407
944971AF1-162 GEN
Solar/Wind Harmer
4.503
24723205RIVRG3
Adder
11.612
972203AH1-686 GEN
Adder
1.34
964901AG1-354 GEN
Solar/Wind Harmer
6.034
24686505CER G6
Adder
4.748
970653AG2-424 GEN
Solar/Wind Harmer
1.862
3429241JKCT 3G
Adder
6.43
3429421JKCT 10G
Adder
4.482
958131AF2-107 GEN
Solar/Wind Harmer
2.003
943811AF1-049 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
38.065
945681AF1-233 GEN
Solar/Wind Harmer
6.517
965911AG1-460 GEN
Solar/Wind Harmer
0.674
276621W2-048 GEN
Solar/Wind Harmer
0.167
25196008MFTGT1
Adder
0.654
24728605AND G2
Adder
1.803
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.116
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
25196808ZIMRHP
Adder
35.505
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.566
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.348
274766LEE CO EC;7U
Adder
4.297
963741AG1-226 GEN
Solar/Wind Harmer
7.714
970819AG2-516 GEN
Solar/Wind Harmer
3.898
274822ROCKFORD ;11
Adder
9.119
970569AG2-363 GEN
Solar/Wind Harmer
9.723
957471AF2-041 GEN
Solar/Wind Harmer
9.712
959081AF2-199 GEN
Solar/Wind Harmer
3.237
971067AG2-660 GEN
Solar/Wind Harmer
1.079
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.689
276882AE2-255 GEN
Solar/Wind Harmer
0.375
962781AG1-127 GEN
Solar/Wind Harmer
3.062
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
0.568
276805AD2-038 GEN
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.024
252516AE2-318_GEN
Solar/Wind Harmer
3.594
274828WAUKEGAN ;BP
Adder
5.078
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
939401AE1-172 GEN
Solar/Wind Harmer
2.397
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
274745AC1-111 GEN9
Adder
2.557
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.484
274674JOLIET 9 ;6U
Adder
7.01
274676JOLIET 29;8U
Adder
13.963
276903AD2-071 C
Solar/Wind Harmer
3.542
941551AE2-152 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.159
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.314
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
3.938
270594AE1-207 GEN
Solar/Wind Harmer
3.528
270032AE2-172
Solar/Wind Harmer
2.1
970825AG2-519 GEN
Solar/Wind Harmer
1.115
270005AE1-210 C O1
Solar/Wind Harmer
0.68
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.068
958381AF2-132 GEN
Solar/Wind Harmer
0
253398AE2-221_GEN2
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.5
958861AF2-177 GEN
Solar/Wind Harmer
1.334
965651AG1-433 GEN
Solar/Wind Harmer
0.9
270024AE2-089 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Helper
0.287
316499AE2-029_GEN
Solar/Wind Helper
0.937
315821AE2-092 GEN
Solar/Wind Helper
1.831
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
23546401DTGZ2-030
Solar/Wind Helper
0.04
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.76
23583801GRNGAP
Solar/Wind Helper
2.128
316095T157 G97
Solar/Wind Helper
0.557
316075AC2-137 C
Solar/Wind Helper
0.18
316223AC1-118
Solar/Wind Helper
0.174
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.453
316077AC2-138 C
Solar/Wind Helper
0.106
316484AD2-074 GEN
Solar/Wind Helper
0.216
24735105WLF2G1
50/50
5.207
24734705WLF1G3
50/50
5.196
24734805WLF1G4
50/50
5.196
24734905WLF1G5
50/50
5.196
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.671
971313AH1-133 GEN
Solar/Wind Harmer
2.637
970281AG2-184 GEN
Solar/Wind Harmer
10.194
270399AC1-101 GEN
Solar/Wind Harmer
1.444
270400AC1-102 GEN
Solar/Wind Harmer
1.444
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
10.049
3429211JKCT 2G
Adder
6.347
339216AC1-074 GEN
Solar/Wind Harmer
0.095
972163AH1-664 GEN
Solar/Wind Harmer
3.863
972165AH1-665 GEN
Solar/Wind Harmer
3.094
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.131
276848AB2-070 GEN3
Solar/Wind Harmer
0.13
276849AB2-070 GEN2
Solar/Wind Harmer
0.131
946321AF1-296 GEN
Solar/Wind Harmer
1.85
25196108MFTGT2
Adder
0.721
25196108MFTGT2
Adder
0.67
274854TWINGROVE;U2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.109
276741O09 GEN1
Solar/Wind Harmer
0.116
972267AH1-718 GEN
Adder
1.953
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.424
971681AH1-341 GEN
Solar/Wind Harmer
5.242
274856ECOGROVE ;U1
Solar/Wind Harmer
0.076
274823ROCKFORD ;21
Adder
9.053
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
971171AH1-044 GEN
Solar/Wind Harmer
6.475
970169AG2-114 GEN
Solar/Wind Harmer
3.232
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276863AD2-134 GEN
Solar/Wind Harmer
0.058
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
4.049
25196308WSDLE2
Adder
4.013
25196208WSDLE1
Adder
4.003
25196708WSDLE6
Adder
3.993
25196508WSDLE4
Adder
3.893
274744AC1-111 GEN8
Adder
2.557
274746AC1-111 G10
Adder
2.557
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.499
970833AG2-524 GEN
Solar/Wind Harmer
2.333
274728ELWOOD EC;5P
Adder
7.484
274731ELWOOD EC;2P
Adder
7.484
274733ELWOOD EC;3P
Adder
7.484
274735ELWOOD EC;4P
Adder
7.484
274675JOLIET 29;7U
Adder
13.963
274675JOLIET 29;7U
Adder
13.464
960591AF2-350 GEN
Solar/Wind Harmer
3.162
970289AG2-191 GEN
Solar/Wind Harmer
0.599
971611AH1-305 GEN
Solar/Wind Harmer
1.876
971985AH1-537 GEN
Solar/Wind Harmer
0.936
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
4.672
971609AH1-304 GEN
Solar/Wind Harmer
0.508
270543AE2-219 C
Solar/Wind Harmer
2.176
253406AD2-031_GEN
Solar/Wind Harmer
0.23
964611AG1-324 GEN
Solar/Wind Harmer
1.21
247536S-71 GEN
Solar/Wind Harmer
0.124
945581AF1-223 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
5.772
315616AA1-038_C
Solar/Wind Helper
1.809
3148463FAIRFLD
Solar/Wind Helper
0.399
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
315651AD1-115 GEN
Solar/Wind Helper
0.443
316258AE1-075 C
Solar/Wind Helper
0.181
316405AF2-144 C
Solar/Wind Helper
0.151
316164AC1-076 GEN
Solar/Wind Helper
0.62
316322AB2-045
Solar/Wind Helper
0.141
316468AD1-105 GEN
Solar/Wind Helper
0.59
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.113
970563AG2-360 GEN
50/50
26.903
24689505VACITY
50/50
3.164
943031AE2-326 GEN
Solar/Wind Harmer
3.912
962751AG1-124 GEN
Solar/Wind Harmer
6.205
960911AF2-382 GEN
Solar/Wind Harmer
4.078
971461AH1-227 GEN
Solar/Wind Harmer
2.687
972103AH1-617 GEN
Solar/Wind Harmer
9.709
972273AH1-721 GEN
Adder
50.356
24686405CER G5
Adder
4.71
970093AG2-073 GEN
Solar/Wind Harmer
3.273
970653AG2-424 GEN
Solar/Wind Harmer
0.386
270030AE2-140 GEN
Solar/Wind Harmer
7.666
970455AG2-298 GEN
Solar/Wind Harmer
1.477
3429391JKCT 9G
Adder
4.482
972167AH1-666 GEN
Solar/Wind Harmer
2.762
958171AF2-111 GEN
Solar/Wind Harmer
8.524
942481AE2-261 GEN
Solar/Wind Harmer
10.082
957381AF2-032 GEN
Solar/Wind Harmer
0.764
970193AG2-126 GEN
Solar/Wind Harmer
4.994
971993AH1-541 GEN
Solar/Wind Harmer
1.535
965931AG1-462 GEN
Solar/Wind Harmer
8.44
971087AG2-675 GEN
Solar/Wind Harmer
1.765
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.771
24728505AND G1
Adder
1.803
965091AG1-374 GEN
Solar/Wind Harmer
9.832
959611AF2-252 GEN
Solar/Wind Harmer
1.092
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.109
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.348
274767LEE CO EC;8U
Adder
4.297
24721905FLATG4
Adder
9.452
270367AC2-061_GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.482
959091AF2-200 GEN
Solar/Wind Harmer
6.475
252507AC2-088 GEN
Solar/Wind Harmer
0.146
274855GSG-6 ;RU
Solar/Wind Harmer
0.118
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276868AE1-113 GEN
Solar/Wind Harmer
0.643
274879MINONK ;1U
Solar/Wind Harmer
0.134
24386205FR-12G C
Solar/Wind Harmer
0
252519AF1-045_GEN
Solar/Wind Harmer
1.674
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.258
25196608WSDLE5
Adder
3.933
274862TOP CROP ;2U
Solar/Wind Harmer
0.432
943121AE2-341 GEN
Solar/Wind Harmer
5.351
943591AF1-030 GEN
Solar/Wind Harmer
3.559
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.187
274729ELWOOD EC;1P
Adder
7.484
274730ELWOOD EC;6P
Adder
7.484
274734ELWOOD EC;8P
Adder
7.484
274736ELWOOD EC;9P
Adder
7.484
274676JOLIET 29;8U
Adder
3.003
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.354
274887GEN-1.85
Solar/Wind Harmer
0.082
276843GEN-1.7
Solar/Wind Harmer
0.102
276806AD2-047 C O1
Solar/Wind Harmer
1.792
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
4.107
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970825AG2-519 GEN
Solar/Wind Harmer
2.365
270004AE1-209 GEN
Solar/Wind Harmer
0.68
946031AF1-268 GEN
Solar/Wind Harmer
2.979
964401AG1-302 GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
971191AH1-055 GEN
Solar/Wind Harmer
7.973
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.643
970191AG2-125 GEN
Solar/Wind Harmer
0.781
944531AF1-118 GEN
Solar/Wind Harmer
13.572
971347AH1-153 GEN
Solar/Wind Harmer
1.512
3147983MERCK5
Solar/Wind Helper
0.108
316192AB2-158 GEN
Solar/Wind Helper
0.989
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
3146776BUCKING
Solar/Wind Helper
0.05
238152AF2-075_GEN
Solar/Wind Helper
0.306
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316447AC1-158 HLD
Solar/Wind Helper
1.456
316044AC1-158 PL1
Solar/Wind Helper
0.662
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
315975AC1-164 GENB
Solar/Wind Helper
0.044
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.173
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.959
3142433PROV 92
Solar/Wind Helper
0.448
316487AF1-042 GEN
Solar/Wind Helper
0.113
3141766HARMONY
Solar/Wind Helper
0.022
NYPJM->LTFIMP_NY
CLTF
1.48
LGEELTFEXP_LGEE->PJM
CLTF
3.563
WECLTFEXP_WEC->PJM
CLTF
1.782
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.647
CPLELTFEXP_CPLE->PJM
CLTF
3.109
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.184
MECLTFEXP_MEC->PJM
CLTF
8.317
SIGELTFEXP_SIGE->PJM
CLTF
0.271
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
LAGNLTFEXP_LAGN->PJM
CLTF
11.701
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.097
TVALTFEXP_TVA->PJM
CLTF
6.216

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.13 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4008.49
MW Contribution:
9.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247619Y1-049
50/50
0.05
24728205BUCHG1
50/50
7.157
270583AD2-179 GEN
Solar/Wind Harmer
14.449
971277AH1-098 GEN
Solar/Wind Harmer
5.174
942671AE2-283 GEN
Solar/Wind Harmer
5.792
970913AG2-568 GEN
Solar/Wind Harmer
7.67
971225AH1-072 GEN
Solar/Wind Harmer
1.903
971227AH1-073 GEN
Solar/Wind Harmer
1.903
24723005RIVRG1
Adder
22.932
24723105RIVRG2
Adder
22.932
942751AE2-291 GEN
Solar/Wind Harmer
7.879
966021AG1-471 GEN
Solar/Wind Harmer
4.01
971485AH1-239 GEN
Solar/Wind Harmer
5.922
964781AG1-341 GEN
Solar/Wind Harmer
7.646
942891AE2-308 GEN
Solar/Wind Harmer
7.092
964571AG1-320 GEN
Solar/Wind Harmer
6.355
971125AH1-004 GEN
Solar/Wind Harmer
2.78
970107AG2-081 GEN
Solar/Wind Harmer
2.085
972043AH1-570 GEN
Solar/Wind Harmer
1.794
972045AH1-571 GEN
Solar/Wind Harmer
1.437
962581AG1-107 GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
4.796
252509AD1-136 GEN
Solar/Wind Harmer
0.032
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
6.93
25194508D.CRK3
Adder
1.296
971073AG2-665 GEN
Solar/Wind Harmer
4.688
970879AG2-548 GEN
Solar/Wind Harmer
1.065
945391AF1-204 GEN
Solar/Wind Harmer
6.759
276916AD2-100_GEN
Solar/Wind Harmer
13.351
276911AD2-131_GEN
Solar/Wind Harmer
0.879
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
3.647
24728805RICHG1
Adder
3.383
24728905RICHG2
Adder
3.383
960251AF2-316 GEN
Solar/Wind Harmer
8.571
960201AF2-311 GEN
Solar/Wind Harmer
5.7
960611AF2-352 GEN
Solar/Wind Harmer
2.071
942111AE2-223 GEN
Solar/Wind Harmer
2.011
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.996
276645AC1-214 GEN1
Solar/Wind Harmer
0.242
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.233
274765LEE CO EC;6U
Adder
8.233
274762LEE CO EC;3U
Adder
8.213
274763LEE CO EC;4U
Adder
8.136
938861AE1-114 GEN
Solar/Wind Harmer
3.487
270383AD1-128 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.217
972236AH1-702 GEN2
Adder
1.928
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
12.26
971343AH1-151 GEN
Solar/Wind Harmer
12.26
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.796
970291AG2-192 GEN
Solar/Wind Harmer
0.367
270205AE1-176
50/50
0.006
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684405SMG2
50/50
2.195
24684505SMG3
50/50
1.341
24728405LEESVG
50/50
0.292
24728405LEESVG
50/50
0.291
24728305BUCHG2
50/50
7.157
3147312GRETNA
Solar/Wind Harmer
0.047
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
5.335
24735205WLF2G2
Adder
8.017
971687AH1-348 GEN
Solar/Wind Harmer
0.947
971403AH1-188 GEN
Solar/Wind Harmer
13.142
944971AF1-162 GEN
Solar/Wind Harmer
9.06
24723205RIVRG3
Adder
22.932
24686505CER G6
Adder
9.865
972203AH1-686 GEN
Adder
2.702
964901AG1-354 GEN
Solar/Wind Harmer
10.795
960001AF2-291 GEN
Solar/Wind Harmer
0
3429241JKCT 3G
Adder
12.016
970653AG2-424 GEN
Solar/Wind Harmer
3.403
3429421JKCT 10G
Adder
8.393
945681AF1-233 GEN
Solar/Wind Harmer
12.766
970091AG2-072 GEN
Adder
73.941
316123AC1-075 GEN
Solar/Wind Harmer
0.164
25196808ZIMRHP
Adder
70.529
25196008MFTGT1
Adder
1.292
252516AE2-318_GEN
Solar/Wind Harmer
7.186
252510AF1-249 C
Solar/Wind Harmer
0.048
25194608D.CRK4
Adder
1.506
971073AG2-665 GEN
Solar/Wind Harmer
1.065
965911AG1-460 GEN
Solar/Wind Harmer
1.269
24728605AND G2
Adder
3.478
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.322
276621W2-048 GEN
Solar/Wind Harmer
0.315
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.798
253398AE2-221_GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.664
24385905FR-11G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.218
276646AC1-214 GEN2
Solar/Wind Harmer
0.242
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.518
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.213
274766LEE CO EC;7U
Adder
8.117
276903AD2-071 C
Solar/Wind Harmer
6.875
970819AG2-516 GEN
Solar/Wind Harmer
7.371
970569AG2-363 GEN
Solar/Wind Harmer
18.425
274822ROCKFORD ;11
Adder
17.258
957471AF2-041 GEN
Solar/Wind Harmer
18.391
959081AF2-199 GEN
Solar/Wind Harmer
6.13
971067AG2-660 GEN
Solar/Wind Harmer
2.043
270594AE1-207 GEN
Solar/Wind Harmer
6.854
270032AE2-172
Solar/Wind Harmer
4.08
971997AH1-543 GEN
Solar/Wind Harmer
3.207
270005AE1-210 C O1
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
2.169
276882AE2-255 GEN
Solar/Wind Harmer
0.713
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.81
939401AE1-172 GEN
Solar/Wind Harmer
4.564
276805AD2-038 GEN
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
9.645
274682WAUKEGAN ;7U
Adder
15.687
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.988
274745AC1-111 GEN9
Adder
4.865
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.589
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.264
274674JOLIET 9 ;6U
Adder
13.36
274676JOLIET 29;8U
Adder
26.611
941551AE2-152 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
7.838
945371AF1-202 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.726
315821AE2-092 GEN
Solar/Wind Helper
3.23
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
23546401DTGZ2-030
Solar/Wind Helper
0.079
23583801GRNGAP
Solar/Wind Helper
4.295
316095T157 G97
Solar/Wind Helper
1.128
966881AG1-559 GEN
Solar/Wind Helper
0.314
316473AC1-191 GEN
Solar/Wind Helper
1.388
971613AH1-306 GEN
Solar/Wind Harmer
2.938
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
18.303
958491AF2-143 GEN
Solar/Wind Harmer
9.149
274683WAUKEGAN ;8U
Adder
18.4
274683WAUKEGAN ;8U
Adder
15.511
274696ROCKY RD ;4P
Adder
9.947
274695ROCKY RD ;2P
Adder
9.717
274693ROCKY RD ;1P
Adder
9.622
274697ROCKY RD ;3P
Adder
2.64
958481AF2-142 GEN
Solar/Wind Harmer
9.122
970883AG2-550 GEN
Solar/Wind Harmer
6.074
970885AG2-551 GEN
Solar/Wind Harmer
2.025
276893AG1-478 C
Solar/Wind Harmer
0.404
274674JOLIET 9 ;6U
Adder
13.36
270031AE2-169
Solar/Wind Harmer
3.328
270599AE1-208 GEN
Solar/Wind Harmer
5.547
276897AD1-100 C
Solar/Wind Harmer
15.124
964611AG1-324 GEN
Solar/Wind Harmer
0.453
274888KELLY CRK;1U
Solar/Wind Harmer
0.352
276776AD2-060 GEN
Solar/Wind Harmer
0.644
958011AF2-095 GEN
Solar/Wind Harmer
8.691
970941AG2-585 GEN
Solar/Wind Harmer
3.319
270201AC2-176 GEN
Solar/Wind Harmer
0
3132123MT JACKSON
Solar/Wind Helper
1.39
966001AG1-469 GEN
Solar/Wind Helper
0.32
237061AD1-155 GEN
Solar/Wind Helper
1.647
316097T157 G90
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238148AE2-230_GEN2
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316006AB2-029 C
Solar/Wind Helper
0.113
316313AB2-026
Solar/Wind Helper
0.355
966871AG1-558 GEN
Solar/Wind Helper
0.306
316045AC1-158 PL2
Solar/Wind Helper
4.039
316450AC1-158 RIC
Solar/Wind Helper
0.337
970823AG2-518 GEN
50/50
8.379
24288905REUSENS
50/50
0.056
24290605CLAY-1
50/50
0.252
24290705CLAY-2
50/50
0.252
24684605SMG4
50/50
2.21
24415905BUCK
50/50
0.033
3151561HALLBR1
50/50
0.562
971881AH1-461 GEN
50/50
14.967
970563AG2-360 GEN
50/50
45.796
970417AG2-272 GEN
50/50
3.731
962751AG1-124 GEN
Solar/Wind Harmer
12.886
958121AF2-106 GEN
Solar/Wind Harmer
0.001
943031AE2-326 GEN
Solar/Wind Harmer
6.78
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.174
941801AE2-185 GEN
Solar/Wind Harmer
7.447
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.535
270030AE2-140 GEN
Solar/Wind Harmer
21.562
960911AF2-382 GEN
Solar/Wind Harmer
7.632
971461AH1-227 GEN
Solar/Wind Harmer
4.882
970223AG2-152 GEN
Solar/Wind Harmer
12.382
972103AH1-617 GEN
Solar/Wind Harmer
18.009
24686405CER G5
Adder
9.787
972273AH1-721 GEN
Adder
89.23
24721905FLATG4
Adder
21.662
970093AG2-073 GEN
Solar/Wind Harmer
6.071
970653AG2-424 GEN
Solar/Wind Harmer
0.705
3429391JKCT 9G
Adder
8.393
971191AH1-055 GEN
Solar/Wind Harmer
18.034
970455AG2-298 GEN
Solar/Wind Harmer
2.725
972167AH1-666 GEN
Solar/Wind Harmer
5.413
958171AF2-111 GEN
Solar/Wind Harmer
16.661
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.292
25196008MFTGT1
Adder
1.251
252519AF1-045_GEN
Solar/Wind Harmer
3.347
25194608D.CRK4
Adder
1.506
970879AG2-548 GEN
Solar/Wind Harmer
4.688
25196608WSDLE5
Adder
7.839
970193AG2-126 GEN
Solar/Wind Harmer
9.542
942481AE2-261 GEN
Solar/Wind Harmer
18.979
957381AF2-032 GEN
Solar/Wind Harmer
1.438
24728705AND G3
Adder
7.274
24728505AND G1
Adder
3.478
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.219
971993AH1-541 GEN
Solar/Wind Harmer
2.902
253394AE2-221_GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
15.863
971087AG2-675 GEN
Solar/Wind Harmer
3.318
965091AG1-374 GEN
Solar/Wind Harmer
18.636
959611AF2-252 GEN
Solar/Wind Harmer
2.071
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.206
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.213
274767LEE CO EC;8U
Adder
8.117
970571AG2-364 GEN
Solar/Wind Harmer
12.283
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.138
959091AF2-200 GEN
Solar/Wind Harmer
12.26
247642Z2-115 C
Solar/Wind Harmer
0.003
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970289AG2-191 GEN
Solar/Wind Harmer
0.673
946671AF1-331 GEN
Solar/Wind Harmer
0.653
270004AE1-209 GEN
Solar/Wind Harmer
1.324
970825AG2-519 GEN
Solar/Wind Harmer
4.603
276868AE1-113 GEN
Solar/Wind Harmer
1.222
274879MINONK ;1U
Solar/Wind Harmer
0.255
946031AF1-268 GEN
Solar/Wind Harmer
5.802
274682WAUKEGAN ;7U
Adder
15.687
274862TOP CROP ;2U
Solar/Wind Harmer
0.821
943121AE2-341 GEN
Solar/Wind Harmer
10.182
943591AF1-030 GEN
Solar/Wind Harmer
6.771
274729ELWOOD EC;1P
Adder
14.264
274730ELWOOD EC;6P
Adder
14.264
274734ELWOOD EC;8P
Adder
14.264
274736ELWOOD EC;9P
Adder
14.264
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.749
274887GEN-1.85
Solar/Wind Harmer
0.157
276843GEN-1.7
Solar/Wind Harmer
0.195
276806AD2-047 C O1
Solar/Wind Harmer
3.42
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.046
970191AG2-125 GEN
Solar/Wind Harmer
1.552
964401AG1-302 GEN
Solar/Wind Harmer
0.001
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.089
238152AF2-075_GEN
Solar/Wind Helper
0.605
316447AC1-158 HLD
Solar/Wind Helper
2.777
316044AC1-158 PL1
Solar/Wind Helper
1.262
971543AH1-269 GEN
50/50
12.24
24684705SMG5
50/50
0.845
24684305SMG1
50/50
0.795
24416005BYLLESBY
50/50
0.03
971331AH1-145 GEN
Solar/Wind Harmer
18.351
971329AH1-144 GEN
Solar/Wind Harmer
6.744
966391AG1-508 GEN
Solar/Wind Harmer
1.991
270197AD1-017 GEN1
Solar/Wind Harmer
1.424
270069AE2-166 C O1
Solar/Wind Harmer
10.375
971313AH1-133 GEN
Solar/Wind Harmer
5.363
24734705WLF1G3
Adder
8.187
24734805WLF1G4
Adder
8.187
24734905WLF1G5
Adder
8.187
24735105WLF2G1
Adder
8.017
270399AC1-101 GEN
Solar/Wind Harmer
2.889
270400AC1-102 GEN
Solar/Wind Harmer
2.889
941621AE2-160 GEN
Adder
4.281
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
20.219
970281AG2-184 GEN
Solar/Wind Harmer
18.909
971981AH1-535 GEN
Solar/Wind Harmer
5.838
971061AG2-657 GEN
Solar/Wind Harmer
5.362
3429211JKCT 2G
Adder
11.861
339216AC1-074 GEN
Solar/Wind Harmer
0.182
972163AH1-664 GEN
Solar/Wind Harmer
7.559
972165AH1-665 GEN
Solar/Wind Harmer
6.054
971985AH1-537 GEN
Solar/Wind Harmer
2.009
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.424
25196108MFTGT2
Adder
1.322
944221AF1-090 GEN
Solar/Wind Harmer
3.75
25196408WSDLE3
Adder
8.07
25196308WSDLE2
Adder
8
25196208WSDLE1
Adder
7.98
25196708WSDLE6
Adder
7.96
25196508WSDLE4
Adder
7.759
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.247
276848AB2-070 GEN3
Solar/Wind Harmer
0.246
276849AB2-070 GEN2
Solar/Wind Harmer
0.247
270356AE2-297 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.464
963841AG1-237 GEN
Solar/Wind Harmer
2.696
946321AF1-296 GEN
Solar/Wind Harmer
3.479
274854TWINGROVE;U2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
270340AC2-060 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.498
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.206
276741O09 GEN1
Solar/Wind Harmer
0.218
972267AH1-718 GEN
Adder
3.684
971681AH1-341 GEN
Solar/Wind Harmer
9.907
274856ECOGROVE ;U1
Solar/Wind Harmer
0.144
926823AC1-168 GEN
Solar/Wind Harmer
1.044
970169AG2-114 GEN
Solar/Wind Harmer
6.143
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.132
971171AH1-044 GEN
Solar/Wind Harmer
12.26
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
970289AG2-191 GEN
Solar/Wind Harmer
1.163
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.387
971411AH1-196 GEN
Solar/Wind Harmer
9.181
270263AC1-001 GEN
Solar/Wind Harmer
0.61
970073AG2-061 GEN
Solar/Wind Harmer
2.033
971029AG2-637 GEN
Solar/Wind Harmer
9.145
270543AE2-219 C
Solar/Wind Harmer
4.252
274744AC1-111 GEN8
Adder
4.865
274746AC1-111 G10
Adder
4.865
971611AH1-305 GEN
Solar/Wind Harmer
3.614
970833AG2-524 GEN
Solar/Wind Harmer
6.668
970833AG2-524 GEN
Solar/Wind Harmer
4.445
959141AF2-205 GEN
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.264
274731ELWOOD EC;2P
Adder
14.264
274733ELWOOD EC;3P
Adder
14.264
274735ELWOOD EC;4P
Adder
14.264
247536S-71 GEN
Solar/Wind Harmer
0.242
25306009OHH W.
Adder
2.5
971609AH1-304 GEN
Solar/Wind Harmer
0.988
274675JOLIET 29;7U
Adder
26.611
274675JOLIET 29;7U
Adder
7.635
964611AG1-324 GEN
Solar/Wind Harmer
2.357
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
6.035
945581AF1-223 GEN
Solar/Wind Harmer
0
315616AA1-038_C
Solar/Wind Helper
3.297
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
315651AD1-115 GEN
Solar/Wind Helper
0.843
316164AC1-076 GEN
Solar/Wind Helper
1.176
316258AE1-075 C
Solar/Wind Helper
0.32
316405AF2-144 C
Solar/Wind Helper
0.267
316468AD1-105 GEN
Solar/Wind Helper
1.089
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.368
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.272
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.277
CPLELTFEXP_CPLE->PJM
CLTF
6.213
MECLTFEXP_MEC->PJM
CLTF
15.399
SIGELTFEXP_SIGE->PJM
CLTF
0.508
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.985
LAGNLTFEXP_LAGN->PJM
CLTF
20.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.52
TVALTFEXP_TVA->PJM
CLTF
10.596

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.08 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:6455.24
MW Contribution:
28.52
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
14.354
274771LINCOLN ;2U
50/50
14.354
970349AG2-230 GEN
Solar/Wind Harmer
33.698
276897AD1-100 C
Solar/Wind Harmer
96.099
274888KELLY CRK;1U
Solar/Wind Harmer
12.159
276776AD2-060 GEN
Solar/Wind Harmer
0.863
958011AF2-095 GEN
Solar/Wind Harmer
29.672
970941AG2-585 GEN
Solar/Wind Harmer
11.333
965681AG1-436 GEN
Solar/Wind Harmer
25.631
965791AG1-447 GEN
Solar/Wind Harmer
13.113
274674JOLIET 9 ;6U
Adder
31.523
274805UNIV PK N;1U
Adder
10.241
274808UNIV PK N;4U
Adder
10.174
276893AG1-478 C
Solar/Wind Harmer
0.894
274695ROCKY RD ;2P
Adder
22.398
274693ROCKY RD ;1P
Adder
22.177
274697ROCKY RD ;3P
Adder
6.084
274696ROCKY RD ;4P
Adder
22.926
274683WAUKEGAN ;8U
Adder
42.139
274683WAUKEGAN ;8U
Adder
35.522
962691AG1-118 GEN
Solar/Wind Harmer
59.904
960751AF2-366 GEN
Solar/Wind Harmer
5.711
958481AF2-142 GEN
Solar/Wind Harmer
29.827
276901AD2-066 C O1
Solar/Wind Harmer
6.889
958491AF2-143 GEN
Solar/Wind Harmer
29.417
971341AH1-150 GEN
Solar/Wind Harmer
38.858
971343AH1-151 GEN
Solar/Wind Harmer
38.858
972235AH1-702 GEN1
Adder
4.859
972236AH1-702 GEN2
Adder
4.225
270535AF1-215 GEN1
Solar/Wind Harmer
8.733
270536AF1-215 GEN2
Solar/Wind Harmer
8.733
276872AE1-163_GEN1
Solar/Wind Harmer
12.914
276876AE1-163_GEN2
Solar/Wind Harmer
12.914
938861AE1-114 GEN
Solar/Wind Harmer
15.58
274764LEE CO EC;5U
Adder
17.639
274765LEE CO EC;6U
Adder
17.639
274762LEE CO EC;3U
Adder
17.597
274763LEE CO EC;4U
Adder
17.431
276158O29GEN2
Solar/Wind Harmer
9.31
276157O29GEN1
Solar/Wind Harmer
7.079
276645AC1-214 GEN1
Solar/Wind Harmer
2.476
942111AE2-223 GEN
Solar/Wind Harmer
14.834
945421AF1-207 GEN
Solar/Wind Harmer
25.334
957841AF2-078 GEN
Solar/Wind Harmer
10.906
247620Y3-023
Adder
0.633
24344105CKG2
50/50
19.954
274773LINCOLN ;4U
50/50
14.354
274774LINCOLN ;5U
50/50
14.354
972207SS24-0001
Solar/Wind Harmer
48.096
941551AE2-152 GEN
Solar/Wind Harmer
9.382
274871GR RIDGE ;2U
Solar/Wind Harmer
15.794
274847GR RIDGE ;BU
Solar/Wind Harmer
10.385
274723RIVER EC ;12
Adder
36.775
274802UNIV PARK;5U
Adder
11.953
274676JOLIET 29;8U
Adder
62.88
274674JOLIET 9 ;6U
Adder
31.523
274745AC1-111 GEN9
Adder
11.424
274732ELWOOD EC;7P
Adder
33.592
274812UNIV PK N;8U
Adder
10.219
274751CRETE EC ;1U
Adder
9.913
274754CRETE EC ;4U
Adder
9.913
274682WAUKEGAN ;7U
Adder
35.996
274828WAUKEGAN ;BP
Adder
22.089
962781AG1-127 GEN
Solar/Wind Harmer
18.93
276694AA1-018 GEN2
Solar/Wind Harmer
12.547
276691AA1-018 GEN1
Solar/Wind Harmer
1.5
274861TOP CROP ;1U
Solar/Wind Harmer
12.033
274872LEEDK;1U
Solar/Wind Harmer
16.294
939401AE1-172 GEN
Solar/Wind Harmer
27.589
276805AD2-038 GEN
Solar/Wind Harmer
10.057
971997AH1-543 GEN
Solar/Wind Harmer
30.868
970373AG2-245 GEN
Solar/Wind Harmer
41.094
276882AE2-255 GEN
Solar/Wind Harmer
6.594
957471AF2-041 GEN
Solar/Wind Harmer
58.287
959081AF2-199 GEN
Solar/Wind Harmer
19.429
971067AG2-660 GEN
Solar/Wind Harmer
4.518
274822ROCKFORD ;11
Adder
37.946
270055AF2-134 C O1
Solar/Wind Harmer
5.822
970819AG2-516 GEN
Solar/Wind Harmer
23.034
970569AG2-363 GEN
Solar/Wind Harmer
56.914
958381AF2-132 GEN
Solar/Wind Harmer
17.169
274858EASY ROAD;U2
Solar/Wind Harmer
9.062
274761LEE CO EC;2U
Adder
17.597
274766LEE CO EC;7U
Adder
17.39
964861AG1-349 GEN
Solar/Wind Harmer
14.852
971917AH1-482 GEN
Solar/Wind Harmer
17.136
276708O09 GEN2
Solar/Wind Harmer
6.648
276646AC1-214 GEN2
Solar/Wind Harmer
2.476
940581AE2-045 GEN
Solar/Wind Harmer
18.841
971605AH1-302 GEN
Solar/Wind Harmer
16.11
274848CAMPGROVE;RU
Solar/Wind Harmer
11.799
276655WTG1_EQ
Solar/Wind Harmer
15.794
276656WTG2_EQ
Solar/Wind Harmer
2.091
939741AE1-205 GEN
Solar/Wind Harmer
36.19
24441205WTRV SLR C
Solar/Wind Harmer
0.239
970091AG2-072 GEN
Adder
127.265
24639705ELKHART HY
Adder
0.232
274772LINCOLN ;3U
50/50
14.354
972259AH1-714 GEN
50/50
42.287
971347AH1-153 GEN
Solar/Wind Harmer
11.233
970707AG2-453 GEN
Solar/Wind Harmer
59.281
939351AE1-166 GEN
Solar/Wind Harmer
12.269
276164X3-005 C
Solar/Wind Harmer
1.449
274887GEN-1.85
Solar/Wind Harmer
10.978
276772AC2-154 GEN
Solar/Wind Harmer
5.75
276843GEN-1.7
Solar/Wind Harmer
1.181
276806AD2-047 C O1
Solar/Wind Harmer
22.043
274724RIVER EC ;11
Adder
36.378
972038AH1-567 GEN2
Adder
0.75
943121AE2-341 GEN
Solar/Wind Harmer
30.81
943591AF1-030 GEN
Solar/Wind Harmer
20.54
274826FISK ;BP
Adder
22.485
274803UNIV PARK;6U
Adder
11.953
274676JOLIET 29;8U
Adder
60.634
274729ELWOOD EC;1P
Adder
33.593
274730ELWOOD EC;6P
Adder
33.592
274734ELWOOD EC;8P
Adder
33.592
274736ELWOOD EC;9P
Adder
33.592
274814UNIV PK N;0U
Adder
10.308
274807UNIV PK N;3U
Adder
10.286
274811UNIV PK N;7U
Adder
10.219
972231SS25-0005
Solar/Wind Harmer
19.247
972181SS23-001
Solar/Wind Harmer
12.03
274752CRETE EC ;2U
Adder
9.913
274753CRETE EC ;3U
Adder
9.913
274682WAUKEGAN ;7U
Adder
35.996
274862TOP CROP ;2U
Solar/Wind Harmer
10.047
276799AD1-013 GEN
Solar/Wind Harmer
4.333
946671AF1-331 GEN
Solar/Wind Harmer
0.821
274855GSG-6 ;RU
Solar/Wind Harmer
7.234
274850MENDOTA H;RU
Solar/Wind Harmer
5.03
276602WESTBROOK C
Solar/Wind Harmer
4.165
276868AE1-113 GEN
Solar/Wind Harmer
19.781
274879MINONK ;1U
Solar/Wind Harmer
13.188
959091AF2-200 GEN
Solar/Wind Harmer
38.858
24441505OLIV SLR
Solar/Wind Harmer
0.26
970571AG2-364 GEN
Solar/Wind Harmer
37.943
964401AG1-302 GEN
Solar/Wind Harmer
17.169
274857EASY ROAD;U1
Solar/Wind Harmer
9.062
274760LEE CO EC;1U
Adder
17.597
274767LEE CO EC;8U
Adder
17.39
276603SUBLETTE C
Solar/Wind Harmer
1.98
274851PROVIDENC;RU
Solar/Wind Harmer
5.265
274849CRESCENT ;1U
Solar/Wind Harmer
3.418
276782AC1-033 GEN
Solar/Wind Harmer
7.324
274878BISHOP HL;2U
Solar/Wind Harmer
6.197
965931AG1-462 GEN
Solar/Wind Harmer
45.525
971087AG2-675 GEN
Solar/Wind Harmer
6.643
270505AE1-170 C O1
Solar/Wind Harmer
26.743
965091AG1-374 GEN
Solar/Wind Harmer
36.699
274775LINCOLN ;6U
50/50
14.354
274776LINCOLN ;7U
50/50
14.354
274777LINCOLN ;8U
50/50
14.354
274661LASCO STA;2U
50/50
11.601
274660LASCO STA;1U
50/50
15.017
972228AH1-698 GEN2
Adder
7.663
972227AH1-698 GEN1
Adder
5.396
960591AF2-350 GEN
Solar/Wind Harmer
20.605
970833AG2-524 GEN
Solar/Wind Harmer
17.935
970833AG2-524 GEN
Solar/Wind Harmer
8.342
274800UNIV PARK;3U
Adder
11.976
274801UNIV PARK;4U
Adder
11.976
274827FISK ;RP
Adder
15.936
960681AF2-359 GEN
Solar/Wind Harmer
7.748
972037AH1-567 GEN1
Adder
0.375
274675JOLIET 29;7U
Adder
62.882
274675JOLIET 29;7U
Adder
60.636
274687WILL CNTY;4U
Adder
57.233
274687WILL CNTY;4U
Adder
57.233
274744AC1-111 GEN8
Adder
11.424
274746AC1-111 G10
Adder
11.424
274731ELWOOD EC;2P
Adder
33.593
274733ELWOOD EC;3P
Adder
33.593
274735ELWOOD EC;4P
Adder
33.593
274728ELWOOD EC;5P
Adder
33.592
276893AG1-478 C
Solar/Wind Harmer
1.122
970073AG2-061 GEN
Solar/Wind Harmer
4.561
971675AH1-338 GEN
Solar/Wind Harmer
35.284
276861AD2-134 GEN
Solar/Wind Harmer
3.498
276863AD2-134 GEN
Solar/Wind Harmer
3.498
971411AH1-196 GEN
Solar/Wind Harmer
29.363
971171AH1-044 GEN
Solar/Wind Harmer
38.858
274863CRW1-WTG
Solar/Wind Harmer
10.833
274864CRW2-WTG
Solar/Wind Harmer
10.833
274823ROCKFORD ;21
Adder
37.671
276889AE2-281 GEN
Solar/Wind Harmer
3.69
270526AF1-158 GEN
Solar/Wind Harmer
8.708
274856ECOGROVE ;U1
Solar/Wind Harmer
6.46
276611AD2-172 GEN
Solar/Wind Harmer
4.9
276612AE2-035 GEN
Solar/Wind Harmer
4.9
926823AC1-168 GEN
Solar/Wind Harmer
8.181
971681AH1-341 GEN
Solar/Wind Harmer
28.524
970169AG2-114 GEN
Solar/Wind Harmer
19.011
958391AF2-133 GEN
Solar/Wind Harmer
17.015
972267AH1-718 GEN
Adder
7.776
959141AF2-205 GEN
Solar/Wind Harmer
11.266
276741O09 GEN1
Solar/Wind Harmer
6.648
274877BISHOP HL;1U
Solar/Wind Harmer
6.197
971771AH1-392 GEN
Solar/Wind Harmer
16.472
276726Z2-087_GEN
Solar/Wind Harmer
14.308
959341AF2-225 GEN
Solar/Wind Harmer
27.143
946321AF1-296 GEN
Solar/Wind Harmer
18.76
274853TWINGROVE;U1
Solar/Wind Harmer
12.743
274854TWINGROVE;U2
Solar/Wind Harmer
12.476
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.61
NYPJM->LTFIMP_NY
CLTF
2.971
LGEELTFEXP_LGEE->PJM
CLTF
1.539
WECLTFEXP_WEC->PJM
CLTF
7.334
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.469
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.627
MECLTFEXP_MEC->PJM
CLTF
25.788
SIGELTFEXP_SIGE->PJM
CLTF
0.335
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.262
AG2-052LTFEXP_AG2-052->PJM
LTF
0.429
AH1-155LTFEXP_AH1-155->PJM
LTF
0.643
CBM West 2LTFEXP_CBM-W2->PJM
CBM
107.682
LAGNLTFEXP_LAGN->PJM
CLTF
11.814
TVALTFEXP_TVA->PJM
CLTF
3.934

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.27 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5814.76
MW Contribution:
25.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274772LINCOLN ;3U
50/50
13.107
972259AH1-714 GEN
50/50
38.51
971347AH1-153 GEN
Solar/Wind Harmer
10.271
970707AG2-453 GEN
Solar/Wind Harmer
54.061
939351AE1-166 GEN
Solar/Wind Harmer
11.159
276164X3-005 C
Solar/Wind Harmer
1.317
274887GEN-1.85
Solar/Wind Harmer
9.982
276772AC2-154 GEN
Solar/Wind Harmer
5.229
276843GEN-1.7
Solar/Wind Harmer
1.074
276806AD2-047 C O1
Solar/Wind Harmer
20.043
943121AE2-341 GEN
Solar/Wind Harmer
28.067
943591AF1-030 GEN
Solar/Wind Harmer
18.711
972038AH1-567 GEN2
Adder
0.682
274826FISK ;BP
Adder
20.443
274724RIVER EC ;11
Adder
33.047
274676JOLIET 29;8U
Adder
55.16
274803UNIV PARK;6U
Adder
10.863
274729ELWOOD EC;1P
Adder
30.548
274730ELWOOD EC;6P
Adder
30.547
274734ELWOOD EC;8P
Adder
30.547
274736ELWOOD EC;9P
Adder
30.547
274814UNIV PK N;0U
Adder
9.359
274807UNIV PK N;3U
Adder
9.338
274811UNIV PK N;7U
Adder
9.277
972231SS25-0005
Solar/Wind Harmer
17.453
972181SS23-001
Solar/Wind Harmer
10.908
274752CRETE EC ;2U
Adder
8.989
274753CRETE EC ;3U
Adder
8.989
274682WAUKEGAN ;7U
Adder
32.756
274862TOP CROP ;2U
Solar/Wind Harmer
9.124
276799AD1-013 GEN
Solar/Wind Harmer
3.942
946671AF1-331 GEN
Solar/Wind Harmer
0.747
274855GSG-6 ;RU
Solar/Wind Harmer
6.582
274850MENDOTA H;RU
Solar/Wind Harmer
4.576
276602WESTBROOK C
Solar/Wind Harmer
3.789
276868AE1-113 GEN
Solar/Wind Harmer
17.957
274879MINONK ;1U
Solar/Wind Harmer
11.972
959091AF2-200 GEN
Solar/Wind Harmer
35.344
24441505OLIV SLR
Solar/Wind Harmer
0.234
970571AG2-364 GEN
Solar/Wind Harmer
34.394
274857EASY ROAD;U1
Solar/Wind Harmer
8.237
274760LEE CO EC;1U
Adder
15.997
274767LEE CO EC;8U
Adder
15.808
276603SUBLETTE C
Solar/Wind Harmer
1.8
274851PROVIDENC;RU
Solar/Wind Harmer
4.767
274849CRESCENT ;1U
Solar/Wind Harmer
3.095
276782AC1-033 GEN
Solar/Wind Harmer
6.634
274878BISHOP HL;2U
Solar/Wind Harmer
5.612
964401AG1-302 GEN
Solar/Wind Harmer
15.035
965931AG1-462 GEN
Solar/Wind Harmer
41.335
971087AG2-675 GEN
Solar/Wind Harmer
6.032
270505AE1-170 C O1
Solar/Wind Harmer
24.099
965091AG1-374 GEN
Solar/Wind Harmer
47.632
959611AF2-252 GEN
Solar/Wind Harmer
3.692
274770LINCOLN ;1U
50/50
13.107
274771LINCOLN ;2U
50/50
13.107
970349AG2-230 GEN
Solar/Wind Harmer
30.814
276897AD1-100 C
Solar/Wind Harmer
87.406
274888KELLY CRK;1U
Solar/Wind Harmer
11.056
276776AD2-060 GEN
Solar/Wind Harmer
0.784
958011AF2-095 GEN
Solar/Wind Harmer
26.979
970941AG2-585 GEN
Solar/Wind Harmer
10.305
274674JOLIET 9 ;6U
Adder
28.674
965681AG1-436 GEN
Solar/Wind Harmer
23.18
965791AG1-447 GEN
Solar/Wind Harmer
11.859
276893AG1-478 C
Solar/Wind Harmer
0.813
274805UNIV PK N;1U
Adder
9.298
274808UNIV PK N;4U
Adder
9.237
274695ROCKY RD ;2P
Adder
20.387
274693ROCKY RD ;1P
Adder
20.186
274697ROCKY RD ;3P
Adder
5.538
274696ROCKY RD ;4P
Adder
20.867
274683WAUKEGAN ;8U
Adder
38.346
274683WAUKEGAN ;8U
Adder
32.324
962691AG1-118 GEN
Solar/Wind Harmer
54.524
960751AF2-366 GEN
Solar/Wind Harmer
5.198
958481AF2-142 GEN
Solar/Wind Harmer
27.089
276901AD2-066 C O1
Solar/Wind Harmer
6.252
958491AF2-143 GEN
Solar/Wind Harmer
26.701
971341AH1-150 GEN
Solar/Wind Harmer
35.344
971343AH1-151 GEN
Solar/Wind Harmer
35.344
972235AH1-702 GEN1
Adder
4.419
972236AH1-702 GEN2
Adder
3.843
276872AE1-163_GEN1
Solar/Wind Harmer
11.713
276876AE1-163_GEN2
Solar/Wind Harmer
11.713
938861AE1-114 GEN
Solar/Wind Harmer
14.164
274764LEE CO EC;5U
Adder
16.035
274765LEE CO EC;6U
Adder
16.035
274762LEE CO EC;3U
Adder
15.997
274763LEE CO EC;4U
Adder
15.846
270535AF1-215 GEN1
Solar/Wind Harmer
7.7
270536AF1-215 GEN2
Solar/Wind Harmer
7.7
276158O29GEN2
Solar/Wind Harmer
8.453
276157O29GEN1
Solar/Wind Harmer
6.427
276645AC1-214 GEN1
Solar/Wind Harmer
2.242
942111AE2-223 GEN
Solar/Wind Harmer
13.339
960611AF2-352 GEN
Solar/Wind Harmer
3.692
247620Y3-023
Adder
0.558
24344105CKG2
50/50
18.459
274773LINCOLN ;4U
50/50
13.107
274774LINCOLN ;5U
50/50
13.107
972207SS24-0001
Solar/Wind Harmer
43.918
941551AE2-152 GEN
Solar/Wind Harmer
8.533
274871GR RIDGE ;2U
Solar/Wind Harmer
14.371
274847GR RIDGE ;BU
Solar/Wind Harmer
9.45
274676JOLIET 29;8U
Adder
57.203
274723RIVER EC ;12
Adder
33.403
274802UNIV PARK;5U
Adder
10.863
274674JOLIET 9 ;6U
Adder
28.674
274745AC1-111 GEN9
Adder
10.402
274732ELWOOD EC;7P
Adder
30.547
274812UNIV PK N;8U
Adder
9.277
274751CRETE EC ;1U
Adder
8.989
274754CRETE EC ;4U
Adder
8.989
274682WAUKEGAN ;7U
Adder
32.756
274828WAUKEGAN ;BP
Adder
20.1
962781AG1-127 GEN
Solar/Wind Harmer
17.229
274872LEEDK;1U
Solar/Wind Harmer
14.829
276694AA1-018 GEN2
Solar/Wind Harmer
11.395
276691AA1-018 GEN1
Solar/Wind Harmer
1.362
274861TOP CROP ;1U
Solar/Wind Harmer
10.928
939401AE1-172 GEN
Solar/Wind Harmer
25.006
971997AH1-543 GEN
Solar/Wind Harmer
28.024
276805AD2-038 GEN
Solar/Wind Harmer
9.128
276882AE2-255 GEN
Solar/Wind Harmer
5.986
957471AF2-041 GEN
Solar/Wind Harmer
53.016
959081AF2-199 GEN
Solar/Wind Harmer
17.672
971067AG2-660 GEN
Solar/Wind Harmer
4.11
274822ROCKFORD ;11
Adder
34.515
970819AG2-516 GEN
Solar/Wind Harmer
20.949
970373AG2-245 GEN
Solar/Wind Harmer
36.468
970569AG2-363 GEN
Solar/Wind Harmer
51.591
274858EASY ROAD;U2
Solar/Wind Harmer
8.237
274761LEE CO EC;2U
Adder
15.997
274766LEE CO EC;7U
Adder
15.808
270055AF2-134 C O1
Solar/Wind Harmer
5.133
276708O09 GEN2
Solar/Wind Harmer
6.036
276646AC1-214 GEN2
Solar/Wind Harmer
2.242
958381AF2-132 GEN
Solar/Wind Harmer
15.035
274848CAMPGROVE;RU
Solar/Wind Harmer
10.679
964861AG1-349 GEN
Solar/Wind Harmer
12.996
971917AH1-482 GEN
Solar/Wind Harmer
14.994
276655WTG1_EQ
Solar/Wind Harmer
14.202
276656WTG2_EQ
Solar/Wind Harmer
1.88
939741AE1-205 GEN
Solar/Wind Harmer
32.544
24441205WTRV SLR C
Solar/Wind Harmer
0.216
940581AE2-045 GEN
Solar/Wind Harmer
16.332
971605AH1-302 GEN
Solar/Wind Harmer
13.964
24639705ELKHART HY
Adder
0.206
970091AG2-072 GEN
Adder
82.471
270449AD2-020 GEN
Solar/Wind Harmer
2.744
943021AE2-325 GEN
Solar/Wind Harmer
3.566
274775LINCOLN ;6U
50/50
13.107
274776LINCOLN ;7U
50/50
13.107
274777LINCOLN ;8U
50/50
13.107
274661LASCO STA;2U
50/50
10.565
274660LASCO STA;1U
50/50
13.676
972228AH1-698 GEN2
Adder
6.97
972227AH1-698 GEN1
Adder
4.908
960591AF2-350 GEN
Solar/Wind Harmer
18.736
970833AG2-524 GEN
Solar/Wind Harmer
16.319
970833AG2-524 GEN
Solar/Wind Harmer
7.59
274800UNIV PARK;3U
Adder
10.888
274801UNIV PARK;4U
Adder
10.888
274827FISK ;RP
Adder
14.488
274675JOLIET 29;7U
Adder
57.205
274675JOLIET 29;7U
Adder
55.162
972037AH1-567 GEN1
Adder
0.341
274687WILL CNTY;4U
Adder
52.056
274687WILL CNTY;4U
Adder
52.056
274744AC1-111 GEN8
Adder
10.402
274746AC1-111 G10
Adder
10.402
274731ELWOOD EC;2P
Adder
30.548
274733ELWOOD EC;3P
Adder
30.548
274735ELWOOD EC;4P
Adder
30.548
274728ELWOOD EC;5P
Adder
30.547
960681AF2-359 GEN
Solar/Wind Harmer
7.007
276893AG1-478 C
Solar/Wind Harmer
1.02
971675AH1-338 GEN
Solar/Wind Harmer
32.101
276861AD2-134 GEN
Solar/Wind Harmer
3.183
276863AD2-134 GEN
Solar/Wind Harmer
3.183
971411AH1-196 GEN
Solar/Wind Harmer
26.713
970073AG2-061 GEN
Solar/Wind Harmer
4.14
971171AH1-044 GEN
Solar/Wind Harmer
35.344
274823ROCKFORD ;21
Adder
34.265
274863CRW1-WTG
Solar/Wind Harmer
9.803
274864CRW2-WTG
Solar/Wind Harmer
9.803
276889AE2-281 GEN
Solar/Wind Harmer
3.347
274856ECOGROVE ;U1
Solar/Wind Harmer
5.874
276611AD2-172 GEN
Solar/Wind Harmer
4.456
276612AE2-035 GEN
Solar/Wind Harmer
4.456
270526AF1-158 GEN
Solar/Wind Harmer
7.859
971681AH1-341 GEN
Solar/Wind Harmer
25.93
926823AC1-168 GEN
Solar/Wind Harmer
7.416
970169AG2-114 GEN
Solar/Wind Harmer
17.177
972267AH1-718 GEN
Adder
7.067
276741O09 GEN1
Solar/Wind Harmer
6.036
274877BISHOP HL;1U
Solar/Wind Harmer
5.612
971771AH1-392 GEN
Solar/Wind Harmer
14.838
958391AF2-133 GEN
Solar/Wind Harmer
14.844
946321AF1-296 GEN
Solar/Wind Harmer
17.035
276726Z2-087_GEN
Solar/Wind Harmer
12.866
959341AF2-225 GEN
Solar/Wind Harmer
24.408
959141AF2-205 GEN
Solar/Wind Harmer
9.801
274853TWINGROVE;U1
Solar/Wind Harmer
11.439
274854TWINGROVE;U2
Solar/Wind Harmer
11.199
944161AF1-084 GEN
Solar/Wind Harmer
3.508
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.466
NYPJM->LTFIMP_NY
CLTF
2.772
LGEELTFEXP_LGEE->PJM
CLTF
3.226
WECLTFEXP_WEC->PJM
CLTF
6.672
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.32
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.391
MECLTFEXP_MEC->PJM
CLTF
23.429
SIGELTFEXP_SIGE->PJM
CLTF
0.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.025
AG2-052LTFEXP_AG2-052->PJM
LTF
0.385
AH1-155LTFEXP_AH1-155->PJM
LTF
0.577
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.714
LAGNLTFEXP_LAGN->PJM
CLTF
11.241
TVALTFEXP_TVA->PJM
CLTF
3.967

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.38 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5769.93
MW Contribution:
27.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
14.2
274771LINCOLN ;2U
50/50
14.2
270102X2-052 ST
50/50
3.302
270100X2-052 CT1
50/50
3.05
270101X2-052 CT2
50/50
3.05
970349AG2-230 GEN
Solar/Wind Harmer
33.931
965681AG1-436 GEN
Solar/Wind Harmer
25.645
965791AG1-447 GEN
Solar/Wind Harmer
13.121
276897AD1-100 C
Solar/Wind Harmer
94.51
274888KELLY CRK;1U
Solar/Wind Harmer
11.985
276776AD2-060 GEN
Solar/Wind Harmer
0.85
958011AF2-095 GEN
Solar/Wind Harmer
29.247
970941AG2-585 GEN
Solar/Wind Harmer
11.171
274805UNIV PK N;1U
Adder
10.12
274808UNIV PK N;4U
Adder
10.053
274674JOLIET 9 ;6U
Adder
31.025
276893AG1-478 C
Solar/Wind Harmer
0.88
274695ROCKY RD ;2P
Adder
21.991
274693ROCKY RD ;1P
Adder
21.775
24344105CKG2
50/50
20.132
274773LINCOLN ;4U
50/50
14.2
274774LINCOLN ;5U
50/50
14.2
972207SS24-0001
Solar/Wind Harmer
47.58
941551AE2-152 GEN
Solar/Wind Harmer
9.227
274723RIVER EC ;12
Adder
36.384
274802UNIV PARK;5U
Adder
11.792
274871GR RIDGE ;2U
Solar/Wind Harmer
15.527
274847GR RIDGE ;BU
Solar/Wind Harmer
10.21
274676JOLIET 29;8U
Adder
61.926
274812UNIV PK N;8U
Adder
10.097
274674JOLIET 9 ;6U
Adder
31.025
274732ELWOOD EC;7P
Adder
33.049
274745AC1-111 GEN9
Adder
11.233
274751CRETE EC ;1U
Adder
9.812
274754CRETE EC ;4U
Adder
9.812
274682WAUKEGAN ;7U
Adder
35.341
274828WAUKEGAN ;BP
Adder
21.683
962781AG1-127 GEN
Solar/Wind Harmer
18.559
276694AA1-018 GEN2
Solar/Wind Harmer
12.298
970373AG2-245 GEN
Solar/Wind Harmer
40.93
276691AA1-018 GEN1
Solar/Wind Harmer
1.47
274861TOP CROP ;1U
Solar/Wind Harmer
11.794
274872LEEDK;1U
Solar/Wind Harmer
15.969
939401AE1-172 GEN
Solar/Wind Harmer
26.858
276805AD2-038 GEN
Solar/Wind Harmer
9.832
270055AF2-134 C O1
Solar/Wind Harmer
5.787
971997AH1-543 GEN
Solar/Wind Harmer
30.118
276882AE2-255 GEN
Solar/Wind Harmer
6.441
957471AF2-041 GEN
Solar/Wind Harmer
56.986
959081AF2-199 GEN
Solar/Wind Harmer
18.995
971067AG2-660 GEN
Solar/Wind Harmer
4.418
274822ROCKFORD ;11
Adder
37.094
958381AF2-132 GEN
Solar/Wind Harmer
17.03
970819AG2-516 GEN
Solar/Wind Harmer
22.498
964861AG1-349 GEN
Solar/Wind Harmer
14.729
971917AH1-482 GEN
Solar/Wind Harmer
16.993
274858EASY ROAD;U2
Solar/Wind Harmer
8.832
274761LEE CO EC;2U
Adder
17.152
274766LEE CO EC;7U
Adder
16.95
970569AG2-363 GEN
Solar/Wind Harmer
55.3
940581AE2-045 GEN
Solar/Wind Harmer
18.631
971605AH1-302 GEN
Solar/Wind Harmer
15.93
276708O09 GEN2
Solar/Wind Harmer
6.457
24441205WTRV SLR C
Solar/Wind Harmer
0.241
276646AC1-214 GEN2
Solar/Wind Harmer
2.394
270449AD2-020 GEN
Solar/Wind Harmer
4.968
943021AE2-325 GEN
Solar/Wind Harmer
6.456
957891AF2-083 GEN
Solar/Wind Harmer
26.586
274848CAMPGROVE;RU
Solar/Wind Harmer
11.386
276655WTG1_EQ
Solar/Wind Harmer
15.057
276656WTG2_EQ
Solar/Wind Harmer
1.994
939741AE1-205 GEN
Solar/Wind Harmer
34.503
24639705ELKHART HY
Adder
0.234
274772LINCOLN ;3U
50/50
14.2
972259AH1-714 GEN
50/50
41.679
971347AH1-153 GEN
Solar/Wind Harmer
11.31
970707AG2-453 GEN
Solar/Wind Harmer
58.482
276164X3-005 C
Solar/Wind Harmer
1.432
939351AE1-166 GEN
Solar/Wind Harmer
12.066
274724RIVER EC ;11
Adder
35.991
274887GEN-1.85
Solar/Wind Harmer
10.821
276772AC2-154 GEN
Solar/Wind Harmer
5.668
276843GEN-1.7
Solar/Wind Harmer
1.164
276806AD2-047 C O1
Solar/Wind Harmer
21.727
274826FISK ;BP
Adder
22.183
972038AH1-567 GEN2
Adder
0.739
274803UNIV PARK;6U
Adder
11.792
943121AE2-341 GEN
Solar/Wind Harmer
30.308
943591AF1-030 GEN
Solar/Wind Harmer
20.205
274676JOLIET 29;8U
Adder
59.714
274814UNIV PK N;0U
Adder
10.186
274807UNIV PK N;3U
Adder
10.164
274811UNIV PK N;7U
Adder
10.097
274729ELWOOD EC;1P
Adder
33.05
274730ELWOOD EC;6P
Adder
33.049
274734ELWOOD EC;8P
Adder
33.049
274736ELWOOD EC;9P
Adder
33.049
972231SS25-0005
Solar/Wind Harmer
19.052
972181SS23-001
Solar/Wind Harmer
11.907
274752CRETE EC ;2U
Adder
9.812
274753CRETE EC ;3U
Adder
9.812
274682WAUKEGAN ;7U
Adder
35.341
24441505OLIV SLR
Solar/Wind Harmer
0.26
274862TOP CROP ;2U
Solar/Wind Harmer
9.847
276799AD1-013 GEN
Solar/Wind Harmer
4.241
946671AF1-331 GEN
Solar/Wind Harmer
0.804
274855GSG-6 ;RU
Solar/Wind Harmer
7.079
274850MENDOTA H;RU
Solar/Wind Harmer
4.922
276602WESTBROOK C
Solar/Wind Harmer
4.075
276868AE1-113 GEN
Solar/Wind Harmer
19.321
274879MINONK ;1U
Solar/Wind Harmer
12.881
959091AF2-200 GEN
Solar/Wind Harmer
37.991
964401AG1-302 GEN
Solar/Wind Harmer
17.03
274857EASY ROAD;U1
Solar/Wind Harmer
8.832
274760LEE CO EC;1U
Adder
17.152
274775LINCOLN ;6U
50/50
14.2
274776LINCOLN ;7U
50/50
14.2
274777LINCOLN ;8U
50/50
14.2
274661LASCO STA;2U
50/50
11.434
274660LASCO STA;1U
50/50
14.801
960681AF2-359 GEN
Solar/Wind Harmer
7.752
972228AH1-698 GEN2
Adder
7.55
972227AH1-698 GEN1
Adder
5.316
960591AF2-350 GEN
Solar/Wind Harmer
20.31
274827FISK ;RP
Adder
15.722
274800UNIV PARK;3U
Adder
11.81
274801UNIV PARK;4U
Adder
11.81
972037AH1-567 GEN1
Adder
0.37
970833AG2-524 GEN
Solar/Wind Harmer
17.634
970833AG2-524 GEN
Solar/Wind Harmer
8.202
274675JOLIET 29;7U
Adder
61.928
274675JOLIET 29;7U
Adder
59.716
274687WILL CNTY;4U
Adder
56.379
274687WILL CNTY;4U
Adder
56.379
274728ELWOOD EC;5P
Adder
33.049
274731ELWOOD EC;2P
Adder
33.05
274733ELWOOD EC;3P
Adder
33.05
274735ELWOOD EC;4P
Adder
33.05
274744AC1-111 GEN8
Adder
11.233
274746AC1-111 G10
Adder
11.233
276893AG1-478 C
Solar/Wind Harmer
1.104
270526AF1-158 GEN
Solar/Wind Harmer
8.736
971675AH1-338 GEN
Solar/Wind Harmer
34.53
276861AD2-134 GEN
Solar/Wind Harmer
3.423
276863AD2-134 GEN
Solar/Wind Harmer
3.423
970073AG2-061 GEN
Solar/Wind Harmer
4.459
971411AH1-196 GEN
Solar/Wind Harmer
28.745
971171AH1-044 GEN
Solar/Wind Harmer
37.991
274823ROCKFORD ;21
Adder
36.825
274863CRW1-WTG
Solar/Wind Harmer
10.5
274864CRW2-WTG
Solar/Wind Harmer
10.5
276889AE2-281 GEN
Solar/Wind Harmer
3.594
274856ECOGROVE ;U1
Solar/Wind Harmer
6.307
276611AD2-172 GEN
Solar/Wind Harmer
4.784
276612AE2-035 GEN
Solar/Wind Harmer
4.784
958391AF2-133 GEN
Solar/Wind Harmer
16.858
971681AH1-341 GEN
Solar/Wind Harmer
27.815
926823AC1-168 GEN
Solar/Wind Harmer
7.944
274697ROCKY RD ;3P
Adder
5.974
274696ROCKY RD ;4P
Adder
22.509
274683WAUKEGAN ;8U
Adder
41.366
274683WAUKEGAN ;8U
Adder
34.869
962691AG1-118 GEN
Solar/Wind Harmer
58.752
960751AF2-366 GEN
Solar/Wind Harmer
5.599
958481AF2-142 GEN
Solar/Wind Harmer
29.235
276901AD2-066 C O1
Solar/Wind Harmer
6.728
958491AF2-143 GEN
Solar/Wind Harmer
28.76
270535AF1-215 GEN1
Solar/Wind Harmer
8.681
270536AF1-215 GEN2
Solar/Wind Harmer
8.681
971341AH1-150 GEN
Solar/Wind Harmer
37.991
971343AH1-151 GEN
Solar/Wind Harmer
37.991
972235AH1-702 GEN1
Adder
4.748
972236AH1-702 GEN2
Adder
4.129
276872AE1-163_GEN1
Solar/Wind Harmer
12.58
276876AE1-163_GEN2
Solar/Wind Harmer
12.58
938861AE1-114 GEN
Solar/Wind Harmer
15.194
274764LEE CO EC;5U
Adder
17.192
274765LEE CO EC;6U
Adder
17.192
274762LEE CO EC;3U
Adder
17.152
274763LEE CO EC;4U
Adder
16.99
276158O29GEN2
Solar/Wind Harmer
9.043
276157O29GEN1
Solar/Wind Harmer
6.875
276645AC1-214 GEN1
Solar/Wind Harmer
2.394
945421AF1-207 GEN
Solar/Wind Harmer
24.972
957841AF2-078 GEN
Solar/Wind Harmer
10.75
961051AF2-396 GEN
Solar/Wind Harmer
27.758
961051AF2-396 GEN
Solar/Wind Harmer
12.911
247620Y3-023
Adder
0.639
942111AE2-223 GEN
Solar/Wind Harmer
8.73
959141AF2-205 GEN
Solar/Wind Harmer
11.153
971771AH1-392 GEN
Solar/Wind Harmer
16.564
970169AG2-114 GEN
Solar/Wind Harmer
18.347
972267AH1-718 GEN
Adder
7.567
276741O09 GEN1
Solar/Wind Harmer
6.457
274877BISHOP HL;1U
Solar/Wind Harmer
5.989
944161AF1-084 GEN
Solar/Wind Harmer
3.922
946321AF1-296 GEN
Solar/Wind Harmer
18.169
276726Z2-087_GEN
Solar/Wind Harmer
8.421
959341AF2-225 GEN
Solar/Wind Harmer
15.975
274767LEE CO EC;8U
Adder
16.95
970571AG2-364 GEN
Solar/Wind Harmer
36.866
276603SUBLETTE C
Solar/Wind Harmer
1.929
270505AE1-170 C O1
Solar/Wind Harmer
26.946
274851PROVIDENC;RU
Solar/Wind Harmer
5.09
274849CRESCENT ;1U
Solar/Wind Harmer
3.305
276782AC1-033 GEN
Solar/Wind Harmer
7.079
274878BISHOP HL;2U
Solar/Wind Harmer
5.989
965931AG1-462 GEN
Solar/Wind Harmer
44.05
971087AG2-675 GEN
Solar/Wind Harmer
6.428
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.596
NYPJM->LTFIMP_NY
CLTF
2.797
LGEELTFEXP_LGEE->PJM
CLTF
1.86
WECLTFEXP_WEC->PJM
CLTF
7.169
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.48
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.637
MECLTFEXP_MEC->PJM
CLTF
24.605
SIGELTFEXP_SIGE->PJM
CLTF
0.291
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.22
AG2-052LTFEXP_AG2-052->PJM
LTF
0.42
AH1-155LTFEXP_AH1-155->PJM
LTF
0.63
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.182
LAGNLTFEXP_LAGN->PJM
CLTF
10.73
TVALTFEXP_TVA->PJM
CLTF
3.51

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.14 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5758.3
MW Contribution:
25.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
13.132
274771LINCOLN ;2U
50/50
13.132
970349AG2-230 GEN
Solar/Wind Harmer
30.869
276897AD1-100 C
Solar/Wind Harmer
87.577
274888KELLY CRK;1U
Solar/Wind Harmer
11.078
276776AD2-060 GEN
Solar/Wind Harmer
0.786
958011AF2-095 GEN
Solar/Wind Harmer
27.033
970941AG2-585 GEN
Solar/Wind Harmer
10.325
274674JOLIET 9 ;6U
Adder
28.731
965681AG1-436 GEN
Solar/Wind Harmer
23.226
965791AG1-447 GEN
Solar/Wind Harmer
11.883
276893AG1-478 C
Solar/Wind Harmer
0.815
274805UNIV PK N;1U
Adder
9.316
274808UNIV PK N;4U
Adder
9.255
274695ROCKY RD ;2P
Adder
20.428
274693ROCKY RD ;1P
Adder
20.227
274697ROCKY RD ;3P
Adder
5.549
274696ROCKY RD ;4P
Adder
20.909
274683WAUKEGAN ;8U
Adder
38.424
274683WAUKEGAN ;8U
Adder
32.389
962691AG1-118 GEN
Solar/Wind Harmer
54.635
960751AF2-366 GEN
Solar/Wind Harmer
5.208
958481AF2-142 GEN
Solar/Wind Harmer
27.144
276901AD2-066 C O1
Solar/Wind Harmer
6.265
958491AF2-143 GEN
Solar/Wind Harmer
26.757
971341AH1-150 GEN
Solar/Wind Harmer
35.418
971343AH1-151 GEN
Solar/Wind Harmer
35.418
972235AH1-702 GEN1
Adder
4.429
972236AH1-702 GEN2
Adder
3.851
276872AE1-163_GEN1
Solar/Wind Harmer
11.738
276876AE1-163_GEN2
Solar/Wind Harmer
11.738
938861AE1-114 GEN
Solar/Wind Harmer
14.195
274764LEE CO EC;5U
Adder
16.069
274765LEE CO EC;6U
Adder
16.069
274762LEE CO EC;3U
Adder
16.031
274763LEE CO EC;4U
Adder
15.88
270535AF1-215 GEN1
Solar/Wind Harmer
7.717
270536AF1-215 GEN2
Solar/Wind Harmer
7.717
276158O29GEN2
Solar/Wind Harmer
8.472
276157O29GEN1
Solar/Wind Harmer
6.441
276645AC1-214 GEN1
Solar/Wind Harmer
2.247
942111AE2-223 GEN
Solar/Wind Harmer
13.369
960611AF2-352 GEN
Solar/Wind Harmer
3.701
247620Y3-023
Adder
0.559
274772LINCOLN ;3U
50/50
13.132
972259AH1-714 GEN
50/50
38.585
971347AH1-153 GEN
Solar/Wind Harmer
10.29
970707AG2-453 GEN
Solar/Wind Harmer
54.165
939351AE1-166 GEN
Solar/Wind Harmer
11.181
276164X3-005 C
Solar/Wind Harmer
1.32
274887GEN-1.85
Solar/Wind Harmer
10.002
276772AC2-154 GEN
Solar/Wind Harmer
5.239
276843GEN-1.7
Solar/Wind Harmer
1.076
276806AD2-047 C O1
Solar/Wind Harmer
20.082
943121AE2-341 GEN
Solar/Wind Harmer
28.123
943591AF1-030 GEN
Solar/Wind Harmer
18.748
972038AH1-567 GEN2
Adder
0.683
274826FISK ;BP
Adder
20.483
274724RIVER EC ;11
Adder
33.112
274676JOLIET 29;8U
Adder
55.27
274803UNIV PARK;6U
Adder
10.885
274729ELWOOD EC;1P
Adder
30.609
274730ELWOOD EC;6P
Adder
30.608
274734ELWOOD EC;8P
Adder
30.608
274736ELWOOD EC;9P
Adder
30.608
274814UNIV PK N;0U
Adder
9.377
274807UNIV PK N;3U
Adder
9.357
274811UNIV PK N;7U
Adder
9.296
972231SS25-0005
Solar/Wind Harmer
17.488
972181SS23-001
Solar/Wind Harmer
10.93
274752CRETE EC ;2U
Adder
9.007
274753CRETE EC ;3U
Adder
9.007
274682WAUKEGAN ;7U
Adder
32.822
274862TOP CROP ;2U
Solar/Wind Harmer
9.143
276799AD1-013 GEN
Solar/Wind Harmer
3.951
946671AF1-331 GEN
Solar/Wind Harmer
0.749
274855GSG-6 ;RU
Solar/Wind Harmer
6.595
274850MENDOTA H;RU
Solar/Wind Harmer
4.586
276602WESTBROOK C
Solar/Wind Harmer
3.797
276868AE1-113 GEN
Solar/Wind Harmer
17.995
274879MINONK ;1U
Solar/Wind Harmer
11.997
959091AF2-200 GEN
Solar/Wind Harmer
35.418
24441505OLIV SLR
Solar/Wind Harmer
0.235
970571AG2-364 GEN
Solar/Wind Harmer
34.468
274857EASY ROAD;U1
Solar/Wind Harmer
8.255
274760LEE CO EC;1U
Adder
16.031
274767LEE CO EC;8U
Adder
15.842
276603SUBLETTE C
Solar/Wind Harmer
1.804
274851PROVIDENC;RU
Solar/Wind Harmer
4.778
274849CRESCENT ;1U
Solar/Wind Harmer
3.102
276782AC1-033 GEN
Solar/Wind Harmer
6.648
274878BISHOP HL;2U
Solar/Wind Harmer
5.625
964401AG1-302 GEN
Solar/Wind Harmer
15.068
965931AG1-462 GEN
Solar/Wind Harmer
41.429
971087AG2-675 GEN
Solar/Wind Harmer
6.045
270505AE1-170 C O1
Solar/Wind Harmer
24.154
965091AG1-374 GEN
Solar/Wind Harmer
47.742
959611AF2-252 GEN
Solar/Wind Harmer
3.701
274775LINCOLN ;6U
50/50
13.132
274776LINCOLN ;7U
50/50
13.132
274777LINCOLN ;8U
50/50
13.132
274661LASCO STA;2U
50/50
10.585
274660LASCO STA;1U
50/50
13.702
972228AH1-698 GEN2
Adder
6.984
972227AH1-698 GEN1
Adder
4.917
960591AF2-350 GEN
Solar/Wind Harmer
18.773
970833AG2-524 GEN
Solar/Wind Harmer
16.351
970833AG2-524 GEN
Solar/Wind Harmer
7.605
274800UNIV PARK;3U
Adder
10.91
274801UNIV PARK;4U
Adder
10.91
274827FISK ;RP
Adder
14.517
274675JOLIET 29;7U
Adder
57.318
274675JOLIET 29;7U
Adder
55.271
972037AH1-567 GEN1
Adder
0.342
274687WILL CNTY;4U
Adder
52.16
274687WILL CNTY;4U
Adder
52.16
274744AC1-111 GEN8
Adder
10.422
274746AC1-111 G10
Adder
10.422
274731ELWOOD EC;2P
Adder
30.609
274733ELWOOD EC;3P
Adder
30.609
274735ELWOOD EC;4P
Adder
30.609
274728ELWOOD EC;5P
Adder
30.608
960681AF2-359 GEN
Solar/Wind Harmer
7.021
276893AG1-478 C
Solar/Wind Harmer
1.022
971675AH1-338 GEN
Solar/Wind Harmer
32.168
276861AD2-134 GEN
Solar/Wind Harmer
3.189
276863AD2-134 GEN
Solar/Wind Harmer
3.189
971411AH1-196 GEN
Solar/Wind Harmer
26.769
970073AG2-061 GEN
Solar/Wind Harmer
4.148
971171AH1-044 GEN
Solar/Wind Harmer
35.418
274823ROCKFORD ;21
Adder
34.337
274863CRW1-WTG
Solar/Wind Harmer
9.823
274864CRW2-WTG
Solar/Wind Harmer
9.823
276889AE2-281 GEN
Solar/Wind Harmer
3.354
274856ECOGROVE ;U1
Solar/Wind Harmer
5.887
276611AD2-172 GEN
Solar/Wind Harmer
4.466
276612AE2-035 GEN
Solar/Wind Harmer
4.466
270526AF1-158 GEN
Solar/Wind Harmer
7.876
971681AH1-341 GEN
Solar/Wind Harmer
25.986
926823AC1-168 GEN
Solar/Wind Harmer
7.431
970169AG2-114 GEN
Solar/Wind Harmer
17.214
972267AH1-718 GEN
Adder
7.082
276741O09 GEN1
Solar/Wind Harmer
6.049
274877BISHOP HL;1U
Solar/Wind Harmer
5.625
971771AH1-392 GEN
Solar/Wind Harmer
14.871
958391AF2-133 GEN
Solar/Wind Harmer
14.878
946321AF1-296 GEN
Solar/Wind Harmer
17.074
276726Z2-087_GEN
Solar/Wind Harmer
12.895
959341AF2-225 GEN
Solar/Wind Harmer
24.463
959141AF2-205 GEN
Solar/Wind Harmer
9.824
274853TWINGROVE;U1
Solar/Wind Harmer
11.466
274854TWINGROVE;U2
Solar/Wind Harmer
11.225
944161AF1-084 GEN
Solar/Wind Harmer
3.516
24344105CKG2
50/50
18.486
274773LINCOLN ;4U
50/50
13.132
274774LINCOLN ;5U
50/50
13.132
972207SS24-0001
Solar/Wind Harmer
43.999
941551AE2-152 GEN
Solar/Wind Harmer
8.55
274871GR RIDGE ;2U
Solar/Wind Harmer
14.399
274847GR RIDGE ;BU
Solar/Wind Harmer
9.468
274676JOLIET 29;8U
Adder
57.317
274723RIVER EC ;12
Adder
33.469
274802UNIV PARK;5U
Adder
10.885
274674JOLIET 9 ;6U
Adder
28.731
274745AC1-111 GEN9
Adder
10.422
274732ELWOOD EC;7P
Adder
30.608
274812UNIV PK N;8U
Adder
9.296
274751CRETE EC ;1U
Adder
9.007
274754CRETE EC ;4U
Adder
9.007
274682WAUKEGAN ;7U
Adder
32.822
274828WAUKEGAN ;BP
Adder
20.141
962781AG1-127 GEN
Solar/Wind Harmer
17.264
274872LEEDK;1U
Solar/Wind Harmer
14.859
276694AA1-018 GEN2
Solar/Wind Harmer
11.418
276691AA1-018 GEN1
Solar/Wind Harmer
1.365
274861TOP CROP ;1U
Solar/Wind Harmer
10.95
939401AE1-172 GEN
Solar/Wind Harmer
25.058
971997AH1-543 GEN
Solar/Wind Harmer
28.082
276805AD2-038 GEN
Solar/Wind Harmer
9.147
276882AE2-255 GEN
Solar/Wind Harmer
5.998
957471AF2-041 GEN
Solar/Wind Harmer
53.127
959081AF2-199 GEN
Solar/Wind Harmer
17.709
971067AG2-660 GEN
Solar/Wind Harmer
4.118
274822ROCKFORD ;11
Adder
34.587
970819AG2-516 GEN
Solar/Wind Harmer
20.993
970373AG2-245 GEN
Solar/Wind Harmer
36.545
970569AG2-363 GEN
Solar/Wind Harmer
51.702
274858EASY ROAD;U2
Solar/Wind Harmer
8.255
274761LEE CO EC;2U
Adder
16.031
274766LEE CO EC;7U
Adder
15.842
270055AF2-134 C O1
Solar/Wind Harmer
5.144
276708O09 GEN2
Solar/Wind Harmer
6.049
276646AC1-214 GEN2
Solar/Wind Harmer
2.247
958381AF2-132 GEN
Solar/Wind Harmer
15.068
274848CAMPGROVE;RU
Solar/Wind Harmer
10.703
964861AG1-349 GEN
Solar/Wind Harmer
13.025
971917AH1-482 GEN
Solar/Wind Harmer
15.028
276655WTG1_EQ
Solar/Wind Harmer
14.235
276656WTG2_EQ
Solar/Wind Harmer
1.885
939741AE1-205 GEN
Solar/Wind Harmer
32.617
24441205WTRV SLR C
Solar/Wind Harmer
0.216
940581AE2-045 GEN
Solar/Wind Harmer
16.37
971605AH1-302 GEN
Solar/Wind Harmer
13.997
24639705ELKHART HY
Adder
0.207
970091AG2-072 GEN
Adder
82.754
270449AD2-020 GEN
Solar/Wind Harmer
2.75
943021AE2-325 GEN
Solar/Wind Harmer
3.574
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.451
NYPJM->LTFIMP_NY
CLTF
2.748
LGEELTFEXP_LGEE->PJM
CLTF
3.252
WECLTFEXP_WEC->PJM
CLTF
6.686
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.531
MECLTFEXP_MEC->PJM
CLTF
23.491
SIGELTFEXP_SIGE->PJM
CLTF
0.349
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.001
AG2-052LTFEXP_AG2-052->PJM
LTF
0.385
AH1-155LTFEXP_AH1-155->PJM
LTF
0.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
100.213
LAGNLTFEXP_LAGN->PJM
CLTF
11.317
TVALTFEXP_TVA->PJM
CLTF
4.004

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11046___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11046___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:112.82 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5642.02
MW Contribution:
25.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
13.013
274771LINCOLN ;2U
50/50
13.013
270102X2-052 ST
50/50
3.098
270100X2-052 CT1
50/50
2.862
270101X2-052 CT2
50/50
2.862
970349AG2-230 GEN
Solar/Wind Harmer
33.216
965681AG1-436 GEN
Solar/Wind Harmer
23.954
274775LINCOLN ;6U
50/50
13.013
274776LINCOLN ;7U
50/50
13.013
274777LINCOLN ;8U
50/50
13.013
24344005CKG1
50/50
12.253
274661LASCO STA;2U
50/50
10.475
274660LASCO STA;1U
50/50
13.559
960681AF2-359 GEN
Solar/Wind Harmer
7.241
972228AH1-698 GEN2
Adder
6.918
972227AH1-698 GEN1
Adder
4.871
960591AF2-350 GEN
Solar/Wind Harmer
18.62
274827FISK ;RP
Adder
14.422
274800UNIV PARK;3U
Adder
10.832
274801UNIV PARK;4U
Adder
10.832
972037AH1-567 GEN1
Adder
0.339
274675JOLIET 29;7U
Adder
56.754
274675JOLIET 29;7U
Adder
54.727
970833AG2-524 GEN
Solar/Wind Harmer
16.147
970833AG2-524 GEN
Solar/Wind Harmer
7.51
274687WILL CNTY;4U
Adder
51.679
274687WILL CNTY;4U
Adder
51.679
274728ELWOOD EC;5P
Adder
30.278
274731ELWOOD EC;2P
Adder
30.278
274733ELWOOD EC;3P
Adder
30.278
274735ELWOOD EC;4P
Adder
30.278
274744AC1-111 GEN8
Adder
10.289
274746AC1-111 G10
Adder
10.289
276893AG1-478 C
Solar/Wind Harmer
1.011
270526AF1-158 GEN
Solar/Wind Harmer
8.218
971675AH1-338 GEN
Solar/Wind Harmer
31.611
276861AD2-134 GEN
Solar/Wind Harmer
3.134
276863AD2-134 GEN
Solar/Wind Harmer
3.134
970073AG2-061 GEN
Solar/Wind Harmer
4.081
971411AH1-196 GEN
Solar/Wind Harmer
26.319
971771AH1-392 GEN
Solar/Wind Harmer
15.769
971171AH1-044 GEN
Solar/Wind Harmer
34.776
274823ROCKFORD ;21
Adder
33.712
274863CRW1-WTG
Solar/Wind Harmer
9.573
274864CRW2-WTG
Solar/Wind Harmer
9.573
276889AE2-281 GEN
Solar/Wind Harmer
3.287
274856ECOGROVE ;U1
Solar/Wind Harmer
5.773
276611AD2-172 GEN
Solar/Wind Harmer
4.379
276612AE2-035 GEN
Solar/Wind Harmer
4.379
971681AH1-341 GEN
Solar/Wind Harmer
25.453
926823AC1-168 GEN
Solar/Wind Harmer
7.255
970169AG2-114 GEN
Solar/Wind Harmer
16.707
24344105CKG2
50/50
18.536
274773LINCOLN ;4U
50/50
13.013
274774LINCOLN ;5U
50/50
13.013
972207SS24-0001
Solar/Wind Harmer
43.601
274723RIVER EC ;12
Adder
33.447
941551AE2-152 GEN
Solar/Wind Harmer
8.448
274802UNIV PARK;5U
Adder
10.814
274676JOLIET 29;8U
Adder
56.753
274812UNIV PK N;8U
Adder
9.261
274871GR RIDGE ;2U
Solar/Wind Harmer
14.217
274847GR RIDGE ;BU
Solar/Wind Harmer
9.348
274674JOLIET 9 ;6U
Adder
28.429
274732ELWOOD EC;7P
Adder
30.278
274751CRETE EC ;1U
Adder
9.003
274754CRETE EC ;4U
Adder
9.003
274745AC1-111 GEN9
Adder
10.289
274682WAUKEGAN ;7U
Adder
32.372
274828WAUKEGAN ;BP
Adder
19.861
962781AG1-127 GEN
Solar/Wind Harmer
16.994
276694AA1-018 GEN2
Solar/Wind Harmer
11.261
276691AA1-018 GEN1
Solar/Wind Harmer
1.346
274861TOP CROP ;1U
Solar/Wind Harmer
10.799
274872LEEDK;1U
Solar/Wind Harmer
14.622
939401AE1-172 GEN
Solar/Wind Harmer
24.517
276805AD2-038 GEN
Solar/Wind Harmer
8.998
971997AH1-543 GEN
Solar/Wind Harmer
27.538
276882AE2-255 GEN
Solar/Wind Harmer
5.892
957471AF2-041 GEN
Solar/Wind Harmer
52.164
959081AF2-199 GEN
Solar/Wind Harmer
17.388
971067AG2-660 GEN
Solar/Wind Harmer
4.044
970373AG2-245 GEN
Solar/Wind Harmer
36.471
274822ROCKFORD ;11
Adder
33.958
970819AG2-516 GEN
Solar/Wind Harmer
20.595
274858EASY ROAD;U2
Solar/Wind Harmer
8.082
274761LEE CO EC;2U
Adder
15.695
274766LEE CO EC;7U
Adder
15.51
970569AG2-363 GEN
Solar/Wind Harmer
50.539
270055AF2-134 C O1
Solar/Wind Harmer
5.067
24441205WTRV SLR C
Solar/Wind Harmer
0.225
957891AF2-083 GEN
Solar/Wind Harmer
24.975
270449AD2-020 GEN
Solar/Wind Harmer
4.655
943021AE2-325 GEN
Solar/Wind Harmer
6.05
276708O09 GEN2
Solar/Wind Harmer
5.904
276646AC1-214 GEN2
Solar/Wind Harmer
2.185
958381AF2-132 GEN
Solar/Wind Harmer
14.629
274848CAMPGROVE;RU
Solar/Wind Harmer
10.389
964861AG1-349 GEN
Solar/Wind Harmer
12.625
971917AH1-482 GEN
Solar/Wind Harmer
14.566
945111AF1-176 GEN
Solar/Wind Harmer
28.333
270216AD2-079_GEN
Solar/Wind Harmer
0.948
276655WTG1_EQ
Solar/Wind Harmer
13.659
276656WTG2_EQ
Solar/Wind Harmer
1.809
939741AE1-205 GEN
Solar/Wind Harmer
31.299
24639705ELKHART HY
Adder
0.212
940581AE2-045 GEN
Solar/Wind Harmer
2.416
971605AH1-302 GEN
Solar/Wind Harmer
2.066
965791AG1-447 GEN
Solar/Wind Harmer
12.256
276897AD1-100 C
Solar/Wind Harmer
86.531
274888KELLY CRK;1U
Solar/Wind Harmer
10.988
276776AD2-060 GEN
Solar/Wind Harmer
0.779
958011AF2-095 GEN
Solar/Wind Harmer
26.813
970941AG2-585 GEN
Solar/Wind Harmer
10.241
274805UNIV PK N;1U
Adder
9.281
274808UNIV PK N;4U
Adder
9.22
274674JOLIET 9 ;6U
Adder
28.429
276893AG1-478 C
Solar/Wind Harmer
0.806
274695ROCKY RD ;2P
Adder
20.141
274693ROCKY RD ;1P
Adder
19.943
274697ROCKY RD ;3P
Adder
5.471
274696ROCKY RD ;4P
Adder
20.616
274683WAUKEGAN ;8U
Adder
37.89
274683WAUKEGAN ;8U
Adder
31.939
962691AG1-118 GEN
Solar/Wind Harmer
53.799
960751AF2-366 GEN
Solar/Wind Harmer
5.127
958481AF2-142 GEN
Solar/Wind Harmer
26.769
958491AF2-143 GEN
Solar/Wind Harmer
26.32
276901AD2-066 C O1
Solar/Wind Harmer
6.153
971341AH1-150 GEN
Solar/Wind Harmer
34.776
971343AH1-151 GEN
Solar/Wind Harmer
34.776
972235AH1-702 GEN1
Adder
4.346
972236AH1-702 GEN2
Adder
3.779
276872AE1-163_GEN1
Solar/Wind Harmer
11.504
276876AE1-163_GEN2
Solar/Wind Harmer
11.504
938861AE1-114 GEN
Solar/Wind Harmer
13.904
274764LEE CO EC;5U
Adder
15.732
274765LEE CO EC;6U
Adder
15.732
274762LEE CO EC;3U
Adder
15.695
274763LEE CO EC;4U
Adder
15.547
270535AF1-215 GEN1
Solar/Wind Harmer
7.601
270536AF1-215 GEN2
Solar/Wind Harmer
7.601
276158O29GEN2
Solar/Wind Harmer
8.268
276157O29GEN1
Solar/Wind Harmer
6.286
961051AF2-396 GEN
Solar/Wind Harmer
25.934
961051AF2-396 GEN
Solar/Wind Harmer
12.062
276645AC1-214 GEN1
Solar/Wind Harmer
2.185
942111AE2-223 GEN
Solar/Wind Harmer
12.829
247620Y3-023
Adder
0.56
270349AD2-093_GEN
Solar/Wind Helper
1.323
270471AD2-092_GEN
Solar/Wind Helper
1.323
972267AH1-718 GEN
Adder
6.922
944161AF1-084 GEN
Solar/Wind Harmer
3.67
276741O09 GEN1
Solar/Wind Harmer
5.904
274877BISHOP HL;1U
Solar/Wind Harmer
5.467
946321AF1-296 GEN
Solar/Wind Harmer
16.614
958391AF2-133 GEN
Solar/Wind Harmer
14.33
276726Z2-087_GEN
Solar/Wind Harmer
12.374
959341AF2-225 GEN
Solar/Wind Harmer
23.475
959141AF2-205 GEN
Solar/Wind Harmer
9.405
274772LINCOLN ;3U
50/50
13.013
972259AH1-714 GEN
50/50
38.183
971347AH1-153 GEN
Solar/Wind Harmer
11.072
970707AG2-453 GEN
Solar/Wind Harmer
53.574
276164X3-005 C
Solar/Wind Harmer
1.315
274724RIVER EC ;11
Adder
33.1
939351AE1-166 GEN
Solar/Wind Harmer
11.047
274887GEN-1.85
Solar/Wind Harmer
9.921
276772AC2-154 GEN
Solar/Wind Harmer
5.196
276843GEN-1.7
Solar/Wind Harmer
1.067
276806AD2-047 C O1
Solar/Wind Harmer
19.919
274826FISK ;BP
Adder
20.35
972038AH1-567 GEN2
Adder
0.678
274803UNIV PARK;6U
Adder
10.814
943121AE2-341 GEN
Solar/Wind Harmer
27.76
943591AF1-030 GEN
Solar/Wind Harmer
18.507
274676JOLIET 29;8U
Adder
54.726
274814UNIV PK N;0U
Adder
9.342
274807UNIV PK N;3U
Adder
9.322
274811UNIV PK N;7U
Adder
9.261
274729ELWOOD EC;1P
Adder
30.278
274730ELWOOD EC;6P
Adder
30.278
274734ELWOOD EC;8P
Adder
30.278
274736ELWOOD EC;9P
Adder
30.278
972231SS25-0005
Solar/Wind Harmer
17.481
972181SS23-001
Solar/Wind Harmer
10.926
274752CRETE EC ;2U
Adder
9.003
274753CRETE EC ;3U
Adder
9.003
24441505OLIV SLR
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
32.372
274862TOP CROP ;2U
Solar/Wind Harmer
9.016
276799AD1-013 GEN
Solar/Wind Harmer
3.882
946671AF1-331 GEN
Solar/Wind Harmer
0.736
274855GSG-6 ;RU
Solar/Wind Harmer
6.481
274850MENDOTA H;RU
Solar/Wind Harmer
4.506
276602WESTBROOK C
Solar/Wind Harmer
3.731
276868AE1-113 GEN
Solar/Wind Harmer
17.676
274879MINONK ;1U
Solar/Wind Harmer
11.785
959091AF2-200 GEN
Solar/Wind Harmer
34.776
270505AE1-170 C O1
Solar/Wind Harmer
25.43
274857EASY ROAD;U1
Solar/Wind Harmer
8.082
274760LEE CO EC;1U
Adder
15.695
274767LEE CO EC;8U
Adder
15.51
970571AG2-364 GEN
Solar/Wind Harmer
33.693
276603SUBLETTE C
Solar/Wind Harmer
1.765
274851PROVIDENC;RU
Solar/Wind Harmer
4.646
274849CRESCENT ;1U
Solar/Wind Harmer
3.016
276782AC1-033 GEN
Solar/Wind Harmer
6.462
274878BISHOP HL;2U
Solar/Wind Harmer
5.467
964401AG1-302 GEN
Solar/Wind Harmer
14.629
247643Z2-116 C
Solar/Wind Harmer
0.111
945111AF1-176 GEN
Solar/Wind Harmer
8.98
965931AG1-462 GEN
Solar/Wind Harmer
40.277
971087AG2-675 GEN
Solar/Wind Harmer
5.877
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.333
NYPJM->LTFIMP_NY
CLTF
2.587
LGEELTFEXP_LGEE->PJM
CLTF
1.849
WECLTFEXP_WEC->PJM
CLTF
6.565
CBM West 1LTFEXP_CBM-W1->PJM
CBM
178.559
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.487
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.969
MECLTFEXP_MEC->PJM
CLTF
22.505
SIGELTFEXP_SIGE->PJM
CLTF
0.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.793
AG2-052LTFEXP_AG2-052->PJM
LTF
0.381
AH1-155LTFEXP_AH1-155->PJM
LTF
0.572
LAGNLTFEXP_LAGN->PJM
CLTF
10.208
TVALTFEXP_TVA->PJM
CLTF
3.465

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#17234_05GRNTWN 765_N_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#17234_05GRNTWN 765_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.82 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5542.35
MW Contribution:
26.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
13.873
274776LINCOLN ;7U
50/50
13.873
274777LINCOLN ;8U
50/50
13.873
274660LASCO STA;1U
50/50
14.426
274661LASCO STA;2U
50/50
11.144
960681AF2-359 GEN
Solar/Wind Harmer
7.592
972228AH1-698 GEN2
Adder
7.356
972227AH1-698 GEN1
Adder
5.179
960591AF2-350 GEN
Solar/Wind Harmer
19.787
274827FISK ;RP
Adder
15.32
274800UNIV PARK;3U
Adder
11.506
274801UNIV PARK;4U
Adder
11.506
972037AH1-567 GEN1
Adder
0.361
970833AG2-524 GEN
Solar/Wind Harmer
17.165
970833AG2-524 GEN
Solar/Wind Harmer
7.984
274675JOLIET 29;7U
Adder
60.312
274675JOLIET 29;7U
Adder
58.158
274687WILL CNTY;4U
Adder
54.91
274687WILL CNTY;4U
Adder
54.91
274731ELWOOD EC;2P
Adder
32.173
274733ELWOOD EC;3P
Adder
32.173
274735ELWOOD EC;4P
Adder
32.173
274728ELWOOD EC;5P
Adder
32.172
274744AC1-111 GEN8
Adder
10.934
274746AC1-111 G10
Adder
10.934
276893AG1-478 C
Solar/Wind Harmer
1.074
270526AF1-158 GEN
Solar/Wind Harmer
8.546
971675AH1-338 GEN
Solar/Wind Harmer
33.525
276861AD2-134 GEN
Solar/Wind Harmer
3.324
276863AD2-134 GEN
Solar/Wind Harmer
3.324
971411AH1-196 GEN
Solar/Wind Harmer
27.91
970073AG2-061 GEN
Solar/Wind Harmer
4.327
971171AH1-044 GEN
Solar/Wind Harmer
36.865
274823ROCKFORD ;21
Adder
35.728
274863CRW1-WTG
Solar/Wind Harmer
10.151
274864CRW2-WTG
Solar/Wind Harmer
10.151
276889AE2-281 GEN
Solar/Wind Harmer
3.482
274856ECOGROVE ;U1
Solar/Wind Harmer
6.115
276611AD2-172 GEN
Solar/Wind Harmer
4.639
276612AE2-035 GEN
Solar/Wind Harmer
4.639
958391AF2-133 GEN
Solar/Wind Harmer
16.414
971771AH1-392 GEN
Solar/Wind Harmer
16.192
971681AH1-341 GEN
Solar/Wind Harmer
26.952
959141AF2-205 GEN
Solar/Wind Harmer
10.854
926823AC1-168 GEN
Solar/Wind Harmer
7.683
970169AG2-114 GEN
Solar/Wind Harmer
17.698
972267AH1-718 GEN
Adder
7.323
276741O09 GEN1
Solar/Wind Harmer
6.244
944161AF1-084 GEN
Solar/Wind Harmer
3.836
274877BISHOP HL;1U
Solar/Wind Harmer
5.778
946321AF1-296 GEN
Solar/Wind Harmer
17.537
946581AF1-322 GEN
Solar/Wind Harmer
17.017
24691005MDL-2G C
Solar/Wind Harmer
0.114
24344105CKG2
50/50
19.895
274773LINCOLN ;4U
50/50
13.873
274774LINCOLN ;5U
50/50
13.873
972207SS24-0001
Solar/Wind Harmer
46.485
941551AE2-152 GEN
Solar/Wind Harmer
8.983
274723RIVER EC ;12
Adder
35.484
274802UNIV PARK;5U
Adder
11.49
274871GR RIDGE ;2U
Solar/Wind Harmer
15.113
274847GR RIDGE ;BU
Solar/Wind Harmer
9.938
274676JOLIET 29;8U
Adder
60.31
274812UNIV PK N;8U
Adder
9.842
274674JOLIET 9 ;6U
Adder
30.207
274732ELWOOD EC;7P
Adder
32.172
274751CRETE EC ;1U
Adder
9.568
274754CRETE EC ;4U
Adder
9.568
274745AC1-111 GEN9
Adder
10.934
274682WAUKEGAN ;7U
Adder
34.368
274828WAUKEGAN ;BP
Adder
21.084
970373AG2-245 GEN
Solar/Wind Harmer
39.972
962781AG1-127 GEN
Solar/Wind Harmer
18.037
276694AA1-018 GEN2
Solar/Wind Harmer
11.948
276691AA1-018 GEN1
Solar/Wind Harmer
1.428
274861TOP CROP ;1U
Solar/Wind Harmer
11.457
274872LEEDK;1U
Solar/Wind Harmer
15.517
939401AE1-172 GEN
Solar/Wind Harmer
26.021
270055AF2-134 C O1
Solar/Wind Harmer
5.645
276805AD2-038 GEN
Solar/Wind Harmer
9.541
971997AH1-543 GEN
Solar/Wind Harmer
29.204
276882AE2-255 GEN
Solar/Wind Harmer
6.247
957471AF2-041 GEN
Solar/Wind Harmer
55.297
959081AF2-199 GEN
Solar/Wind Harmer
18.432
971067AG2-660 GEN
Solar/Wind Harmer
4.287
274822ROCKFORD ;11
Adder
35.989
958381AF2-132 GEN
Solar/Wind Harmer
16.593
964861AG1-349 GEN
Solar/Wind Harmer
14.349
971917AH1-482 GEN
Solar/Wind Harmer
16.555
970819AG2-516 GEN
Solar/Wind Harmer
21.818
274858EASY ROAD;U2
Solar/Wind Harmer
8.556
274761LEE CO EC;2U
Adder
16.615
274766LEE CO EC;7U
Adder
16.419
970569AG2-363 GEN
Solar/Wind Harmer
53.495
940581AE2-045 GEN
Solar/Wind Harmer
18.12
971605AH1-302 GEN
Solar/Wind Harmer
15.493
24441205WTRV SLR C
Solar/Wind Harmer
0.236
276708O09 GEN2
Solar/Wind Harmer
6.244
270449AD2-020 GEN
Solar/Wind Harmer
4.857
943021AE2-325 GEN
Solar/Wind Harmer
6.312
957891AF2-083 GEN
Solar/Wind Harmer
25.981
276646AC1-214 GEN2
Solar/Wind Harmer
2.31
274848CAMPGROVE;RU
Solar/Wind Harmer
10.977
945111AF1-176 GEN
Solar/Wind Harmer
29.755
24639705ELKHART HY
Adder
0.227
274770LINCOLN ;1U
50/50
13.873
274771LINCOLN ;2U
50/50
13.873
270102X2-052 ST
50/50
3.236
270100X2-052 CT1
50/50
2.989
270101X2-052 CT2
50/50
2.989
970349AG2-230 GEN
Solar/Wind Harmer
33.375
965681AG1-436 GEN
Solar/Wind Harmer
25.114
965791AG1-447 GEN
Solar/Wind Harmer
12.849
276897AD1-100 C
Solar/Wind Harmer
92.013
274888KELLY CRK;1U
Solar/Wind Harmer
11.676
276776AD2-060 GEN
Solar/Wind Harmer
0.828
958011AF2-095 GEN
Solar/Wind Harmer
28.493
970941AG2-585 GEN
Solar/Wind Harmer
10.883
274805UNIV PK N;1U
Adder
9.864
274808UNIV PK N;4U
Adder
9.799
274674JOLIET 9 ;6U
Adder
30.207
276893AG1-478 C
Solar/Wind Harmer
0.856
274695ROCKY RD ;2P
Adder
21.388
274693ROCKY RD ;1P
Adder
21.178
274697ROCKY RD ;3P
Adder
5.81
274696ROCKY RD ;4P
Adder
21.892
274683WAUKEGAN ;8U
Adder
40.223
274683WAUKEGAN ;8U
Adder
33.906
962691AG1-118 GEN
Solar/Wind Harmer
57.111
960751AF2-366 GEN
Solar/Wind Harmer
5.442
958481AF2-142 GEN
Solar/Wind Harmer
28.403
270535AF1-215 GEN1
Solar/Wind Harmer
8.468
270536AF1-215 GEN2
Solar/Wind Harmer
8.468
276901AD2-066 C O1
Solar/Wind Harmer
6.526
958491AF2-143 GEN
Solar/Wind Harmer
27.907
971341AH1-150 GEN
Solar/Wind Harmer
36.865
971343AH1-151 GEN
Solar/Wind Harmer
36.865
972235AH1-702 GEN1
Adder
4.606
972236AH1-702 GEN2
Adder
4.005
276872AE1-163_GEN1
Solar/Wind Harmer
12.185
276876AE1-163_GEN2
Solar/Wind Harmer
12.185
938861AE1-114 GEN
Solar/Wind Harmer
14.722
274764LEE CO EC;5U
Adder
16.654
274765LEE CO EC;6U
Adder
16.654
274762LEE CO EC;3U
Adder
16.615
274763LEE CO EC;4U
Adder
16.458
276158O29GEN2
Solar/Wind Harmer
8.744
276157O29GEN1
Solar/Wind Harmer
6.649
945421AF1-207 GEN
Solar/Wind Harmer
24.244
957841AF2-078 GEN
Solar/Wind Harmer
10.437
276645AC1-214 GEN1
Solar/Wind Harmer
2.31
961051AF2-396 GEN
Solar/Wind Harmer
27.123
961051AF2-396 GEN
Solar/Wind Harmer
12.615
270180AB1-006 GEN1
Solar/Wind Harmer
11.962
247620Y3-023
Adder
0.619
24697605MDL-3G C
Solar/Wind Harmer
0.114
274772LINCOLN ;3U
50/50
13.873
972259AH1-714 GEN
50/50
40.623
971347AH1-153 GEN
Solar/Wind Harmer
11.125
970707AG2-453 GEN
Solar/Wind Harmer
57.042
276164X3-005 C
Solar/Wind Harmer
1.396
274724RIVER EC ;11
Adder
35.102
939351AE1-166 GEN
Solar/Wind Harmer
11.747
274887GEN-1.85
Solar/Wind Harmer
10.542
276772AC2-154 GEN
Solar/Wind Harmer
5.522
276843GEN-1.7
Solar/Wind Harmer
1.134
276806AD2-047 C O1
Solar/Wind Harmer
21.168
274826FISK ;BP
Adder
21.617
972038AH1-567 GEN2
Adder
0.72
274803UNIV PARK;6U
Adder
11.49
943121AE2-341 GEN
Solar/Wind Harmer
29.511
943591AF1-030 GEN
Solar/Wind Harmer
19.674
274676JOLIET 29;8U
Adder
58.156
274814UNIV PK N;0U
Adder
9.929
274807UNIV PK N;3U
Adder
9.907
274811UNIV PK N;7U
Adder
9.842
274729ELWOOD EC;1P
Adder
32.173
972231SS25-0005
Solar/Wind Harmer
18.577
274730ELWOOD EC;6P
Adder
32.172
274734ELWOOD EC;8P
Adder
32.172
274736ELWOOD EC;9P
Adder
32.172
972181SS23-001
Solar/Wind Harmer
11.611
274752CRETE EC ;2U
Adder
9.568
274753CRETE EC ;3U
Adder
9.568
274682WAUKEGAN ;7U
Adder
34.368
24441505OLIV SLR
Solar/Wind Harmer
0.255
274862TOP CROP ;2U
Solar/Wind Harmer
9.566
276799AD1-013 GEN
Solar/Wind Harmer
4.118
946671AF1-331 GEN
Solar/Wind Harmer
0.78
274855GSG-6 ;RU
Solar/Wind Harmer
6.873
274850MENDOTA H;RU
Solar/Wind Harmer
4.779
276602WESTBROOK C
Solar/Wind Harmer
3.957
276868AE1-113 GEN
Solar/Wind Harmer
18.741
274879MINONK ;1U
Solar/Wind Harmer
12.494
959091AF2-200 GEN
Solar/Wind Harmer
36.865
964401AG1-302 GEN
Solar/Wind Harmer
16.593
274857EASY ROAD;U1
Solar/Wind Harmer
8.556
274760LEE CO EC;1U
Adder
16.615
274767LEE CO EC;8U
Adder
16.419
970571AG2-364 GEN
Solar/Wind Harmer
35.663
276603SUBLETTE C
Solar/Wind Harmer
1.868
270505AE1-170 C O1
Solar/Wind Harmer
26.348
274851PROVIDENC;RU
Solar/Wind Harmer
4.912
274849CRESCENT ;1U
Solar/Wind Harmer
3.189
276782AC1-033 GEN
Solar/Wind Harmer
6.83
274878BISHOP HL;2U
Solar/Wind Harmer
5.778
945111AF1-176 GEN
Solar/Wind Harmer
9.43
965931AG1-462 GEN
Solar/Wind Harmer
42.498
971087AG2-675 GEN
Solar/Wind Harmer
6.201
24690905MDL-1G C
Solar/Wind Harmer
13.352
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.546
NYPJM->LTFIMP_NY
CLTF
2.646
LGEELTFEXP_LGEE->PJM
CLTF
0.959
WECLTFEXP_WEC->PJM
CLTF
6.954
CBM West 1LTFEXP_CBM-W1->PJM
CBM
190.051
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.426
MECLTFEXP_MEC->PJM
CLTF
23.53
SIGELTFEXP_SIGE->PJM
CLTF
0.23
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.123
AG2-052LTFEXP_AG2-052->PJM
LTF
0.406
AH1-155LTFEXP_AH1-155->PJM
LTF
0.609
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.532
LAGNLTFEXP_LAGN->PJM
CLTF
9.794
TVALTFEXP_TVA->PJM
CLTF
3.08

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11001___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11001___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.75 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5538.46
MW Contribution:
25.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
13.013
274771LINCOLN ;2U
50/50
13.013
270102X2-052 ST
50/50
3.098
270100X2-052 CT1
50/50
2.862
270101X2-052 CT2
50/50
2.862
970349AG2-230 GEN
Solar/Wind Harmer
33.216
965681AG1-436 GEN
Solar/Wind Harmer
23.954
965791AG1-447 GEN
Solar/Wind Harmer
12.256
276897AD1-100 C
Solar/Wind Harmer
86.531
274888KELLY CRK;1U
Solar/Wind Harmer
10.988
276776AD2-060 GEN
Solar/Wind Harmer
0.779
958011AF2-095 GEN
Solar/Wind Harmer
26.813
970941AG2-585 GEN
Solar/Wind Harmer
10.241
274805UNIV PK N;1U
Adder
9.281
274808UNIV PK N;4U
Adder
9.22
274674JOLIET 9 ;6U
Adder
28.429
276893AG1-478 C
Solar/Wind Harmer
0.806
274695ROCKY RD ;2P
Adder
20.141
274693ROCKY RD ;1P
Adder
19.943
274697ROCKY RD ;3P
Adder
5.471
274696ROCKY RD ;4P
Adder
20.616
274683WAUKEGAN ;8U
Adder
37.89
274683WAUKEGAN ;8U
Adder
31.939
962691AG1-118 GEN
Solar/Wind Harmer
53.799
24344105CKG2
50/50
18.536
274773LINCOLN ;4U
50/50
13.013
274774LINCOLN ;5U
50/50
13.013
972207SS24-0001
Solar/Wind Harmer
43.601
274723RIVER EC ;12
Adder
33.447
941551AE2-152 GEN
Solar/Wind Harmer
8.448
274802UNIV PARK;5U
Adder
10.814
274676JOLIET 29;8U
Adder
56.753
274812UNIV PK N;8U
Adder
9.261
274871GR RIDGE ;2U
Solar/Wind Harmer
14.217
274847GR RIDGE ;BU
Solar/Wind Harmer
9.348
274674JOLIET 9 ;6U
Adder
28.429
274732ELWOOD EC;7P
Adder
30.278
274751CRETE EC ;1U
Adder
9.003
274754CRETE EC ;4U
Adder
9.003
274745AC1-111 GEN9
Adder
10.289
274682WAUKEGAN ;7U
Adder
32.372
274828WAUKEGAN ;BP
Adder
19.861
962781AG1-127 GEN
Solar/Wind Harmer
16.994
276694AA1-018 GEN2
Solar/Wind Harmer
11.261
276691AA1-018 GEN1
Solar/Wind Harmer
1.346
274861TOP CROP ;1U
Solar/Wind Harmer
10.799
274772LINCOLN ;3U
50/50
13.013
972259AH1-714 GEN
50/50
38.183
971347AH1-153 GEN
Solar/Wind Harmer
11.072
970707AG2-453 GEN
Solar/Wind Harmer
53.574
276164X3-005 C
Solar/Wind Harmer
1.315
274724RIVER EC ;11
Adder
33.1
939351AE1-166 GEN
Solar/Wind Harmer
11.047
274887GEN-1.85
Solar/Wind Harmer
9.921
276772AC2-154 GEN
Solar/Wind Harmer
5.196
276843GEN-1.7
Solar/Wind Harmer
1.067
276806AD2-047 C O1
Solar/Wind Harmer
19.919
274826FISK ;BP
Adder
20.35
972038AH1-567 GEN2
Adder
0.678
274803UNIV PARK;6U
Adder
10.814
943121AE2-341 GEN
Solar/Wind Harmer
27.76
943591AF1-030 GEN
Solar/Wind Harmer
18.507
274676JOLIET 29;8U
Adder
54.726
274814UNIV PK N;0U
Adder
9.342
274807UNIV PK N;3U
Adder
9.322
274811UNIV PK N;7U
Adder
9.261
274729ELWOOD EC;1P
Adder
30.278
274730ELWOOD EC;6P
Adder
30.278
274734ELWOOD EC;8P
Adder
30.278
274736ELWOOD EC;9P
Adder
30.278
972231SS25-0005
Solar/Wind Harmer
17.481
972181SS23-001
Solar/Wind Harmer
10.926
274752CRETE EC ;2U
Adder
9.003
274753CRETE EC ;3U
Adder
9.003
24441505OLIV SLR
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
32.372
274862TOP CROP ;2U
Solar/Wind Harmer
9.016
276799AD1-013 GEN
Solar/Wind Harmer
3.882
946671AF1-331 GEN
Solar/Wind Harmer
0.736
274855GSG-6 ;RU
Solar/Wind Harmer
6.481
274850MENDOTA H;RU
Solar/Wind Harmer
4.506
276602WESTBROOK C
Solar/Wind Harmer
3.731
276868AE1-113 GEN
Solar/Wind Harmer
17.676
274879MINONK ;1U
Solar/Wind Harmer
11.785
959091AF2-200 GEN
Solar/Wind Harmer
34.776
270505AE1-170 C O1
Solar/Wind Harmer
25.43
274857EASY ROAD;U1
Solar/Wind Harmer
8.082
274760LEE CO EC;1U
Adder
15.695
274767LEE CO EC;8U
Adder
15.51
970571AG2-364 GEN
Solar/Wind Harmer
33.693
276603SUBLETTE C
Solar/Wind Harmer
1.765
274851PROVIDENC;RU
Solar/Wind Harmer
4.646
274849CRESCENT ;1U
Solar/Wind Harmer
3.016
276782AC1-033 GEN
Solar/Wind Harmer
6.462
274878BISHOP HL;2U
Solar/Wind Harmer
5.467
964401AG1-302 GEN
Solar/Wind Harmer
14.629
247643Z2-116 C
Solar/Wind Harmer
0.111
945111AF1-176 GEN
Solar/Wind Harmer
8.98
965931AG1-462 GEN
Solar/Wind Harmer
40.277
971087AG2-675 GEN
Solar/Wind Harmer
5.877
960751AF2-366 GEN
Solar/Wind Harmer
5.127
958481AF2-142 GEN
Solar/Wind Harmer
26.769
958491AF2-143 GEN
Solar/Wind Harmer
26.32
276901AD2-066 C O1
Solar/Wind Harmer
6.153
971341AH1-150 GEN
Solar/Wind Harmer
34.776
971343AH1-151 GEN
Solar/Wind Harmer
34.776
972235AH1-702 GEN1
Adder
4.346
972236AH1-702 GEN2
Adder
3.779
276872AE1-163_GEN1
Solar/Wind Harmer
11.504
276876AE1-163_GEN2
Solar/Wind Harmer
11.504
938861AE1-114 GEN
Solar/Wind Harmer
13.904
274764LEE CO EC;5U
Adder
15.732
274765LEE CO EC;6U
Adder
15.732
274762LEE CO EC;3U
Adder
15.695
274763LEE CO EC;4U
Adder
15.547
270535AF1-215 GEN1
Solar/Wind Harmer
7.601
270536AF1-215 GEN2
Solar/Wind Harmer
7.601
276158O29GEN2
Solar/Wind Harmer
8.268
276157O29GEN1
Solar/Wind Harmer
6.286
961051AF2-396 GEN
Solar/Wind Harmer
25.934
961051AF2-396 GEN
Solar/Wind Harmer
12.062
276645AC1-214 GEN1
Solar/Wind Harmer
2.185
942111AE2-223 GEN
Solar/Wind Harmer
12.829
247620Y3-023
Adder
0.56
270349AD2-093_GEN
Solar/Wind Helper
1.323
270471AD2-092_GEN
Solar/Wind Helper
1.323
274872LEEDK;1U
Solar/Wind Harmer
14.622
939401AE1-172 GEN
Solar/Wind Harmer
24.517
276805AD2-038 GEN
Solar/Wind Harmer
8.998
971997AH1-543 GEN
Solar/Wind Harmer
27.538
276882AE2-255 GEN
Solar/Wind Harmer
5.892
957471AF2-041 GEN
Solar/Wind Harmer
52.164
959081AF2-199 GEN
Solar/Wind Harmer
17.388
971067AG2-660 GEN
Solar/Wind Harmer
4.044
970373AG2-245 GEN
Solar/Wind Harmer
36.471
274822ROCKFORD ;11
Adder
33.958
970819AG2-516 GEN
Solar/Wind Harmer
20.595
274858EASY ROAD;U2
Solar/Wind Harmer
8.082
274761LEE CO EC;2U
Adder
15.695
274766LEE CO EC;7U
Adder
15.51
970569AG2-363 GEN
Solar/Wind Harmer
50.539
270055AF2-134 C O1
Solar/Wind Harmer
5.067
24441205WTRV SLR C
Solar/Wind Harmer
0.225
957891AF2-083 GEN
Solar/Wind Harmer
24.975
270449AD2-020 GEN
Solar/Wind Harmer
4.655
943021AE2-325 GEN
Solar/Wind Harmer
6.05
276708O09 GEN2
Solar/Wind Harmer
5.904
276646AC1-214 GEN2
Solar/Wind Harmer
2.185
958381AF2-132 GEN
Solar/Wind Harmer
14.629
274848CAMPGROVE;RU
Solar/Wind Harmer
10.389
964861AG1-349 GEN
Solar/Wind Harmer
12.625
971917AH1-482 GEN
Solar/Wind Harmer
14.566
945111AF1-176 GEN
Solar/Wind Harmer
28.333
270216AD2-079_GEN
Solar/Wind Harmer
0.948
276655WTG1_EQ
Solar/Wind Harmer
13.659
276656WTG2_EQ
Solar/Wind Harmer
1.809
939741AE1-205 GEN
Solar/Wind Harmer
31.299
24639705ELKHART HY
Adder
0.212
940581AE2-045 GEN
Solar/Wind Harmer
2.416
971605AH1-302 GEN
Solar/Wind Harmer
2.066
274775LINCOLN ;6U
50/50
13.013
274776LINCOLN ;7U
50/50
13.013
274777LINCOLN ;8U
50/50
13.013
24344005CKG1
50/50
12.253
274661LASCO STA;2U
50/50
10.475
274660LASCO STA;1U
50/50
13.559
960681AF2-359 GEN
Solar/Wind Harmer
7.241
972228AH1-698 GEN2
Adder
6.918
972227AH1-698 GEN1
Adder
4.871
960591AF2-350 GEN
Solar/Wind Harmer
18.62
274827FISK ;RP
Adder
14.422
274800UNIV PARK;3U
Adder
10.832
274801UNIV PARK;4U
Adder
10.832
972037AH1-567 GEN1
Adder
0.339
274675JOLIET 29;7U
Adder
56.754
274675JOLIET 29;7U
Adder
54.727
970833AG2-524 GEN
Solar/Wind Harmer
16.147
970833AG2-524 GEN
Solar/Wind Harmer
7.51
274687WILL CNTY;4U
Adder
51.679
274687WILL CNTY;4U
Adder
51.679
274728ELWOOD EC;5P
Adder
30.278
274731ELWOOD EC;2P
Adder
30.278
274733ELWOOD EC;3P
Adder
30.278
274735ELWOOD EC;4P
Adder
30.278
274744AC1-111 GEN8
Adder
10.289
274746AC1-111 G10
Adder
10.289
276893AG1-478 C
Solar/Wind Harmer
1.011
270526AF1-158 GEN
Solar/Wind Harmer
8.218
971675AH1-338 GEN
Solar/Wind Harmer
31.611
276861AD2-134 GEN
Solar/Wind Harmer
3.134
276863AD2-134 GEN
Solar/Wind Harmer
3.134
970073AG2-061 GEN
Solar/Wind Harmer
4.081
971411AH1-196 GEN
Solar/Wind Harmer
26.319
971771AH1-392 GEN
Solar/Wind Harmer
15.769
971171AH1-044 GEN
Solar/Wind Harmer
34.776
274823ROCKFORD ;21
Adder
33.712
274863CRW1-WTG
Solar/Wind Harmer
9.573
274864CRW2-WTG
Solar/Wind Harmer
9.573
276889AE2-281 GEN
Solar/Wind Harmer
3.287
274856ECOGROVE ;U1
Solar/Wind Harmer
5.773
276611AD2-172 GEN
Solar/Wind Harmer
4.379
276612AE2-035 GEN
Solar/Wind Harmer
4.379
971681AH1-341 GEN
Solar/Wind Harmer
25.453
926823AC1-168 GEN
Solar/Wind Harmer
7.255
970169AG2-114 GEN
Solar/Wind Harmer
16.707
972267AH1-718 GEN
Adder
6.922
944161AF1-084 GEN
Solar/Wind Harmer
3.67
276741O09 GEN1
Solar/Wind Harmer
5.904
274877BISHOP HL;1U
Solar/Wind Harmer
5.467
946321AF1-296 GEN
Solar/Wind Harmer
16.614
958391AF2-133 GEN
Solar/Wind Harmer
14.33
276726Z2-087_GEN
Solar/Wind Harmer
12.374
959341AF2-225 GEN
Solar/Wind Harmer
23.475
959141AF2-205 GEN
Solar/Wind Harmer
9.405
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.333
NYPJM->LTFIMP_NY
CLTF
2.587
LGEELTFEXP_LGEE->PJM
CLTF
1.849
WECLTFEXP_WEC->PJM
CLTF
6.565
CBM West 1LTFEXP_CBM-W1->PJM
CBM
178.559
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.487
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.969
MECLTFEXP_MEC->PJM
CLTF
22.505
SIGELTFEXP_SIGE->PJM
CLTF
0.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.793
AG2-052LTFEXP_AG2-052->PJM
LTF
0.381
AH1-155LTFEXP_AH1-155->PJM
LTF
0.572
LAGNLTFEXP_LAGN->PJM
CLTF
10.208
TVALTFEXP_TVA->PJM
CLTF
3.465

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P2-2_#6229_05MERIDN 345_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#6229_05MERIDN 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.21 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5311.53
MW Contribution:
24.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
12.39
274776LINCOLN ;7U
50/50
12.39
274777LINCOLN ;8U
50/50
12.39
24344005CKG1
50/50
11.56
274661LASCO STA;2U
50/50
9.958
274660LASCO STA;1U
50/50
12.89
960681AF2-359 GEN
Solar/Wind Harmer
6.739
972228AH1-698 GEN2
Adder
6.568
972227AH1-698 GEN1
Adder
4.625
960591AF2-350 GEN
Solar/Wind Harmer
17.663
274827FISK ;RP
Adder
13.669
274800UNIV PARK;3U
Adder
10.269
274801UNIV PARK;4U
Adder
10.269
970833AG2-524 GEN
Solar/Wind Harmer
15.35
970833AG2-524 GEN
Solar/Wind Harmer
7.14
972037AH1-567 GEN1
Adder
0.322
274675JOLIET 29;7U
Adder
53.885
274675JOLIET 29;7U
Adder
51.96
274687WILL CNTY;4U
Adder
49.047
274687WILL CNTY;4U
Adder
49.047
274744AC1-111 GEN8
Adder
9.785
274746AC1-111 G10
Adder
9.785
274728ELWOOD EC;5P
Adder
28.751
274731ELWOOD EC;2P
Adder
28.752
274733ELWOOD EC;3P
Adder
28.752
274735ELWOOD EC;4P
Adder
28.752
276893AG1-478 C
Solar/Wind Harmer
0.96
270526AF1-158 GEN
Solar/Wind Harmer
7.663
971675AH1-338 GEN
Solar/Wind Harmer
30.078
276861AD2-134 GEN
Solar/Wind Harmer
2.982
276863AD2-134 GEN
Solar/Wind Harmer
2.982
971411AH1-196 GEN
Solar/Wind Harmer
25.036
970073AG2-061 GEN
Solar/Wind Harmer
3.877
971171AH1-044 GEN
Solar/Wind Harmer
33.09
274823ROCKFORD ;21
Adder
32.075
971771AH1-392 GEN
Solar/Wind Harmer
14.71
274863CRW1-WTG
Solar/Wind Harmer
9.117
274864CRW2-WTG
Solar/Wind Harmer
9.117
274856ECOGROVE ;U1
Solar/Wind Harmer
5.493
276611AD2-172 GEN
Solar/Wind Harmer
4.167
276612AE2-035 GEN
Solar/Wind Harmer
4.167
276889AE2-281 GEN
Solar/Wind Harmer
3.125
971681AH1-341 GEN
Solar/Wind Harmer
24.225
926823AC1-168 GEN
Solar/Wind Harmer
6.905
970169AG2-114 GEN
Solar/Wind Harmer
15.919
972267AH1-718 GEN
Adder
6.59
276741O09 GEN1
Solar/Wind Harmer
5.621
944161AF1-084 GEN
Solar/Wind Harmer
3.448
274877BISHOP HL;1U
Solar/Wind Harmer
5.207
946321AF1-296 GEN
Solar/Wind Harmer
15.824
958391AF2-133 GEN
Solar/Wind Harmer
13.563
276726Z2-087_GEN
Solar/Wind Harmer
11.806
959341AF2-225 GEN
Solar/Wind Harmer
22.396
959141AF2-205 GEN
Solar/Wind Harmer
8.915
274853TWINGROVE;U1
Solar/Wind Harmer
3.225
24344105CKG2
50/50
17.786
274773LINCOLN ;4U
50/50
12.39
274774LINCOLN ;5U
50/50
12.39
972207SS24-0001
Solar/Wind Harmer
41.515
941551AE2-152 GEN
Solar/Wind Harmer
8.029
274723RIVER EC ;12
Adder
31.601
274871GR RIDGE ;2U
Solar/Wind Harmer
13.517
274847GR RIDGE ;BU
Solar/Wind Harmer
8.888
274802UNIV PARK;5U
Adder
10.248
274676JOLIET 29;8U
Adder
53.883
274674JOLIET 9 ;6U
Adder
26.996
274745AC1-111 GEN9
Adder
9.785
274812UNIV PK N;8U
Adder
8.762
274732ELWOOD EC;7P
Adder
28.751
274751CRETE EC ;1U
Adder
8.501
274754CRETE EC ;4U
Adder
8.501
274682WAUKEGAN ;7U
Adder
30.774
274828WAUKEGAN ;BP
Adder
18.881
962781AG1-127 GEN
Solar/Wind Harmer
16.167
276694AA1-018 GEN2
Solar/Wind Harmer
10.693
276691AA1-018 GEN1
Solar/Wind Harmer
1.278
274872LEEDK;1U
Solar/Wind Harmer
13.911
274861TOP CROP ;1U
Solar/Wind Harmer
10.254
939401AE1-172 GEN
Solar/Wind Harmer
23.338
276805AD2-038 GEN
Solar/Wind Harmer
8.549
971997AH1-543 GEN
Solar/Wind Harmer
26.201
276882AE2-255 GEN
Solar/Wind Harmer
5.601
957471AF2-041 GEN
Solar/Wind Harmer
49.635
959081AF2-199 GEN
Solar/Wind Harmer
16.545
971067AG2-660 GEN
Solar/Wind Harmer
3.848
274822ROCKFORD ;11
Adder
32.309
970819AG2-516 GEN
Solar/Wind Harmer
19.596
970373AG2-245 GEN
Solar/Wind Harmer
34.202
274858EASY ROAD;U2
Solar/Wind Harmer
7.692
274761LEE CO EC;2U
Adder
14.939
274766LEE CO EC;7U
Adder
14.763
970569AG2-363 GEN
Solar/Wind Harmer
48.073
270055AF2-134 C O1
Solar/Wind Harmer
4.768
276708O09 GEN2
Solar/Wind Harmer
5.621
24441205WTRV SLR C
Solar/Wind Harmer
0.211
957891AF2-083 GEN
Solar/Wind Harmer
23.432
270449AD2-020 GEN
Solar/Wind Harmer
4.373
943021AE2-325 GEN
Solar/Wind Harmer
5.682
276646AC1-214 GEN2
Solar/Wind Harmer
2.081
274848CAMPGROVE;RU
Solar/Wind Harmer
9.895
958381AF2-132 GEN
Solar/Wind Harmer
13.816
964861AG1-349 GEN
Solar/Wind Harmer
11.929
971917AH1-482 GEN
Solar/Wind Harmer
13.763
945111AF1-176 GEN
Solar/Wind Harmer
26.646
276655WTG1_EQ
Solar/Wind Harmer
13.032
276656WTG2_EQ
Solar/Wind Harmer
1.725
939741AE1-205 GEN
Solar/Wind Harmer
29.861
270216AD2-079_GEN
Solar/Wind Harmer
0.888
24639705ELKHART HY
Adder
0.2
274770LINCOLN ;1U
50/50
12.39
274771LINCOLN ;2U
50/50
12.39
270102X2-052 ST
50/50
2.875
270100X2-052 CT1
50/50
2.657
270101X2-052 CT2
50/50
2.657
970349AG2-230 GEN
Solar/Wind Harmer
30.196
965681AG1-436 GEN
Solar/Wind Harmer
22.295
965791AG1-447 GEN
Solar/Wind Harmer
11.407
276897AD1-100 C
Solar/Wind Harmer
82.243
274888KELLY CRK;1U
Solar/Wind Harmer
10.423
276776AD2-060 GEN
Solar/Wind Harmer
0.739
958011AF2-095 GEN
Solar/Wind Harmer
25.435
970941AG2-585 GEN
Solar/Wind Harmer
9.715
274674JOLIET 9 ;6U
Adder
26.996
274805UNIV PK N;1U
Adder
8.781
274808UNIV PK N;4U
Adder
8.724
276893AG1-478 C
Solar/Wind Harmer
0.765
274695ROCKY RD ;2P
Adder
19.154
274693ROCKY RD ;1P
Adder
18.965
274697ROCKY RD ;3P
Adder
5.203
274696ROCKY RD ;4P
Adder
19.605
274683WAUKEGAN ;8U
Adder
36.021
274683WAUKEGAN ;8U
Adder
30.364
962691AG1-118 GEN
Solar/Wind Harmer
51.18
960751AF2-366 GEN
Solar/Wind Harmer
4.878
958481AF2-142 GEN
Solar/Wind Harmer
25.42
276901AD2-066 C O1
Solar/Wind Harmer
5.85
958491AF2-143 GEN
Solar/Wind Harmer
25.006
971341AH1-150 GEN
Solar/Wind Harmer
33.09
971343AH1-151 GEN
Solar/Wind Harmer
33.09
972235AH1-702 GEN1
Adder
4.136
972236AH1-702 GEN2
Adder
3.596
276872AE1-163_GEN1
Solar/Wind Harmer
10.937
276876AE1-163_GEN2
Solar/Wind Harmer
10.937
938861AE1-114 GEN
Solar/Wind Harmer
13.233
274764LEE CO EC;5U
Adder
14.974
274765LEE CO EC;6U
Adder
14.974
274762LEE CO EC;3U
Adder
14.939
274763LEE CO EC;4U
Adder
14.798
270535AF1-215 GEN1
Solar/Wind Harmer
7.152
270536AF1-215 GEN2
Solar/Wind Harmer
7.152
276158O29GEN2
Solar/Wind Harmer
7.872
276157O29GEN1
Solar/Wind Harmer
5.985
276645AC1-214 GEN1
Solar/Wind Harmer
2.081
961051AF2-396 GEN
Solar/Wind Harmer
24.37
961051AF2-396 GEN
Solar/Wind Harmer
11.335
942111AE2-223 GEN
Solar/Wind Harmer
12.239
247620Y3-023
Adder
0.533
274772LINCOLN ;3U
50/50
12.39
972259AH1-714 GEN
50/50
36.297
971347AH1-153 GEN
Solar/Wind Harmer
10.065
970707AG2-453 GEN
Solar/Wind Harmer
50.987
276164X3-005 C
Solar/Wind Harmer
1.244
939351AE1-166 GEN
Solar/Wind Harmer
10.5
274887GEN-1.85
Solar/Wind Harmer
9.41
276772AC2-154 GEN
Solar/Wind Harmer
4.929
276843GEN-1.7
Solar/Wind Harmer
1.013
276806AD2-047 C O1
Solar/Wind Harmer
18.895
274724RIVER EC ;11
Adder
31.27
274826FISK ;BP
Adder
19.288
972038AH1-567 GEN2
Adder
0.643
943121AE2-341 GEN
Solar/Wind Harmer
26.41
943591AF1-030 GEN
Solar/Wind Harmer
17.607
274803UNIV PARK;6U
Adder
10.248
274676JOLIET 29;8U
Adder
51.959
274814UNIV PK N;0U
Adder
8.839
274807UNIV PK N;3U
Adder
8.819
274811UNIV PK N;7U
Adder
8.762
274729ELWOOD EC;1P
Adder
28.752
274730ELWOOD EC;6P
Adder
28.751
274734ELWOOD EC;8P
Adder
28.751
274736ELWOOD EC;9P
Adder
28.751
972231SS25-0005
Solar/Wind Harmer
16.506
972181SS23-001
Solar/Wind Harmer
10.316
274752CRETE EC ;2U
Adder
8.501
274753CRETE EC ;3U
Adder
8.501
274682WAUKEGAN ;7U
Adder
30.774
24441505OLIV SLR
Solar/Wind Harmer
0.228
274862TOP CROP ;2U
Solar/Wind Harmer
8.562
276799AD1-013 GEN
Solar/Wind Harmer
3.694
946671AF1-331 GEN
Solar/Wind Harmer
0.7
274855GSG-6 ;RU
Solar/Wind Harmer
6.167
274850MENDOTA H;RU
Solar/Wind Harmer
4.288
276602WESTBROOK C
Solar/Wind Harmer
3.55
276868AE1-113 GEN
Solar/Wind Harmer
16.804
274879MINONK ;1U
Solar/Wind Harmer
11.203
959091AF2-200 GEN
Solar/Wind Harmer
33.09
274857EASY ROAD;U1
Solar/Wind Harmer
7.692
274760LEE CO EC;1U
Adder
14.939
274767LEE CO EC;8U
Adder
14.763
970571AG2-364 GEN
Solar/Wind Harmer
32.049
276603SUBLETTE C
Solar/Wind Harmer
1.68
270505AE1-170 C O1
Solar/Wind Harmer
23.849
274851PROVIDENC;RU
Solar/Wind Harmer
4.424
274849CRESCENT ;1U
Solar/Wind Harmer
2.872
276782AC1-033 GEN
Solar/Wind Harmer
6.154
274878BISHOP HL;2U
Solar/Wind Harmer
5.207
964401AG1-302 GEN
Solar/Wind Harmer
13.816
965931AG1-462 GEN
Solar/Wind Harmer
38.367
971087AG2-675 GEN
Solar/Wind Harmer
5.598
945111AF1-176 GEN
Solar/Wind Harmer
8.445
247643Z2-116 C
Solar/Wind Harmer
0.104
959611AF2-252 GEN
Solar/Wind Harmer
1.041
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.307
NYPJM->LTFIMP_NY
CLTF
2.483
LGEELTFEXP_LGEE->PJM
CLTF
1.9
WECLTFEXP_WEC->PJM
CLTF
6.245
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.996
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.295
CBM West 2LTFEXP_CBM-W2->PJM
CBM
84.376
MECLTFEXP_MEC->PJM
CLTF
21.482
SIGELTFEXP_SIGE->PJM
CLTF
0.251
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.358
AH1-155LTFEXP_AH1-155->PJM
LTF
0.537
LAGNLTFEXP_LAGN->PJM
CLTF
9.874
TVALTFEXP_TVA->PJM
CLTF
3.386

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P2-2_#702_05JEFRSO 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#702_05JEFRSO 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.53 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5227.77
MW Contribution:
23.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
12.172
274776LINCOLN ;7U
50/50
12.172
274777LINCOLN ;8U
50/50
12.172
274660LASCO STA;1U
50/50
12.646
274661LASCO STA;2U
50/50
9.77
972228AH1-698 GEN2
Adder
6.439
972227AH1-698 GEN1
Adder
4.534
960591AF2-350 GEN
Solar/Wind Harmer
17.303
970833AG2-524 GEN
Solar/Wind Harmer
15.062
970833AG2-524 GEN
Solar/Wind Harmer
7.006
274800UNIV PARK;3U
Adder
10.055
274801UNIV PARK;4U
Adder
10.055
274827FISK ;RP
Adder
13.381
274675JOLIET 29;7U
Adder
52.814
274675JOLIET 29;7U
Adder
50.928
972037AH1-567 GEN1
Adder
0.315
274687WILL CNTY;4U
Adder
48.059
274687WILL CNTY;4U
Adder
48.059
274744AC1-111 GEN8
Adder
9.601
274746AC1-111 G10
Adder
9.601
960681AF2-359 GEN
Solar/Wind Harmer
6.485
274731ELWOOD EC;2P
Adder
28.187
274733ELWOOD EC;3P
Adder
28.187
274735ELWOOD EC;4P
Adder
28.187
274728ELWOOD EC;5P
Adder
28.186
276893AG1-478 C
Solar/Wind Harmer
0.941
971675AH1-338 GEN
Solar/Wind Harmer
29.516
276861AD2-134 GEN
Solar/Wind Harmer
2.926
274770LINCOLN ;1U
50/50
12.172
274771LINCOLN ;2U
50/50
12.172
970349AG2-230 GEN
Solar/Wind Harmer
28.813
276897AD1-100 C
Solar/Wind Harmer
80.7
274888KELLY CRK;1U
Solar/Wind Harmer
10.211
276776AD2-060 GEN
Solar/Wind Harmer
0.724
958011AF2-095 GEN
Solar/Wind Harmer
24.917
970941AG2-585 GEN
Solar/Wind Harmer
9.517
274674JOLIET 9 ;6U
Adder
26.466
965681AG1-436 GEN
Solar/Wind Harmer
21.454
965791AG1-447 GEN
Solar/Wind Harmer
10.976
276893AG1-478 C
Solar/Wind Harmer
0.75
274805UNIV PK N;1U
Adder
8.583
274808UNIV PK N;4U
Adder
8.527
274695ROCKY RD ;2P
Adder
18.792
274693ROCKY RD ;1P
Adder
18.607
274697ROCKY RD ;3P
Adder
5.105
274696ROCKY RD ;4P
Adder
19.234
274683WAUKEGAN ;8U
Adder
35.329
274683WAUKEGAN ;8U
Adder
29.781
962691AG1-118 GEN
Solar/Wind Harmer
50.223
960751AF2-366 GEN
Solar/Wind Harmer
4.786
958481AF2-142 GEN
Solar/Wind Harmer
24.92
276901AD2-066 C O1
Solar/Wind Harmer
5.741
958491AF2-143 GEN
Solar/Wind Harmer
24.523
971341AH1-150 GEN
Solar/Wind Harmer
32.47
971343AH1-151 GEN
Solar/Wind Harmer
32.47
972235AH1-702 GEN1
Adder
4.058
972236AH1-702 GEN2
Adder
3.528
276872AE1-163_GEN1
Solar/Wind Harmer
10.732
276876AE1-163_GEN2
Solar/Wind Harmer
10.732
938861AE1-114 GEN
Solar/Wind Harmer
12.985
274764LEE CO EC;5U
Adder
14.693
274765LEE CO EC;6U
Adder
14.693
274762LEE CO EC;3U
Adder
14.658
274763LEE CO EC;4U
Adder
14.52
270535AF1-215 GEN1
Solar/Wind Harmer
7.015
270536AF1-215 GEN2
Solar/Wind Harmer
7.015
276158O29GEN2
Solar/Wind Harmer
7.727
276157O29GEN1
Solar/Wind Harmer
5.875
276645AC1-214 GEN1
Solar/Wind Harmer
2.044
942111AE2-223 GEN
Solar/Wind Harmer
12.064
961051AF2-396 GEN
Solar/Wind Harmer
22.741
961051AF2-396 GEN
Solar/Wind Harmer
10.577
247620Y3-023
Adder
0.498
960611AF2-352 GEN
Solar/Wind Harmer
0.35
274772LINCOLN ;3U
50/50
12.172
972259AH1-714 GEN
50/50
35.612
971347AH1-153 GEN
Solar/Wind Harmer
9.604
970707AG2-453 GEN
Solar/Wind Harmer
50.065
939351AE1-166 GEN
Solar/Wind Harmer
10.303
276164X3-005 C
Solar/Wind Harmer
1.217
274887GEN-1.85
Solar/Wind Harmer
9.219
276772AC2-154 GEN
Solar/Wind Harmer
4.829
276843GEN-1.7
Solar/Wind Harmer
0.992
276806AD2-047 C O1
Solar/Wind Harmer
18.511
943121AE2-341 GEN
Solar/Wind Harmer
25.921
943591AF1-030 GEN
Solar/Wind Harmer
17.281
972038AH1-567 GEN2
Adder
0.629
274826FISK ;BP
Adder
18.881
274724RIVER EC ;11
Adder
30.536
274676JOLIET 29;8U
Adder
50.926
274803UNIV PARK;6U
Adder
10.031
274729ELWOOD EC;1P
Adder
28.187
274730ELWOOD EC;6P
Adder
28.186
274734ELWOOD EC;8P
Adder
28.186
274736ELWOOD EC;9P
Adder
28.186
274814UNIV PK N;0U
Adder
8.64
274807UNIV PK N;3U
Adder
8.621
274811UNIV PK N;7U
Adder
8.565
972231SS25-0005
Solar/Wind Harmer
16.107
972181SS23-001
Solar/Wind Harmer
10.067
274752CRETE EC ;2U
Adder
8.296
274753CRETE EC ;3U
Adder
8.296
274682WAUKEGAN ;7U
Adder
30.183
274862TOP CROP ;2U
Solar/Wind Harmer
8.393
276799AD1-013 GEN
Solar/Wind Harmer
3.625
946671AF1-331 GEN
Solar/Wind Harmer
0.687
274855GSG-6 ;RU
Solar/Wind Harmer
6.051
274850MENDOTA H;RU
Solar/Wind Harmer
4.207
276602WESTBROOK C
Solar/Wind Harmer
3.484
276868AE1-113 GEN
Solar/Wind Harmer
16.486
274879MINONK ;1U
Solar/Wind Harmer
10.991
959091AF2-200 GEN
Solar/Wind Harmer
32.47
24441505OLIV SLR
Solar/Wind Harmer
0.216
274857EASY ROAD;U1
Solar/Wind Harmer
7.548
274760LEE CO EC;1U
Adder
14.658
274767LEE CO EC;8U
Adder
14.486
970571AG2-364 GEN
Solar/Wind Harmer
31.458
276603SUBLETTE C
Solar/Wind Harmer
1.649
274851PROVIDENC;RU
Solar/Wind Harmer
4.346
274849CRESCENT ;1U
Solar/Wind Harmer
2.821
276782AC1-033 GEN
Solar/Wind Harmer
6.045
274878BISHOP HL;2U
Solar/Wind Harmer
5.115
964401AG1-302 GEN
Solar/Wind Harmer
13.632
270505AE1-170 C O1
Solar/Wind Harmer
22.165
24344105CKG2
50/50
17.473
274773LINCOLN ;4U
50/50
12.172
274774LINCOLN ;5U
50/50
12.172
972207SS24-0001
Solar/Wind Harmer
40.784
941551AE2-152 GEN
Solar/Wind Harmer
7.879
274871GR RIDGE ;2U
Solar/Wind Harmer
13.264
274847GR RIDGE ;BU
Solar/Wind Harmer
8.722
274723RIVER EC ;12
Adder
30.862
274676JOLIET 29;8U
Adder
52.813
274802UNIV PARK;5U
Adder
10.031
274674JOLIET 9 ;6U
Adder
26.466
274745AC1-111 GEN9
Adder
9.601
274732ELWOOD EC;7P
Adder
28.186
274812UNIV PK N;8U
Adder
8.565
274751CRETE EC ;1U
Adder
8.296
274754CRETE EC ;4U
Adder
8.296
274682WAUKEGAN ;7U
Adder
30.183
274828WAUKEGAN ;BP
Adder
18.519
962781AG1-127 GEN
Solar/Wind Harmer
15.865
274872LEEDK;1U
Solar/Wind Harmer
13.651
276694AA1-018 GEN2
Solar/Wind Harmer
10.483
276691AA1-018 GEN1
Solar/Wind Harmer
1.253
274861TOP CROP ;1U
Solar/Wind Harmer
10.052
939401AE1-172 GEN
Solar/Wind Harmer
22.938
276805AD2-038 GEN
Solar/Wind Harmer
8.384
971997AH1-543 GEN
Solar/Wind Harmer
25.725
276882AE2-255 GEN
Solar/Wind Harmer
5.496
957471AF2-041 GEN
Solar/Wind Harmer
48.705
959081AF2-199 GEN
Solar/Wind Harmer
16.235
971067AG2-660 GEN
Solar/Wind Harmer
3.776
274822ROCKFORD ;11
Adder
31.699
970819AG2-516 GEN
Solar/Wind Harmer
19.227
970373AG2-245 GEN
Solar/Wind Harmer
33.361
274858EASY ROAD;U2
Solar/Wind Harmer
7.548
274761LEE CO EC;2U
Adder
14.658
274766LEE CO EC;7U
Adder
14.486
970569AG2-363 GEN
Solar/Wind Harmer
47.188
270055AF2-134 C O1
Solar/Wind Harmer
4.676
276708O09 GEN2
Solar/Wind Harmer
5.517
276646AC1-214 GEN2
Solar/Wind Harmer
2.044
274848CAMPGROVE;RU
Solar/Wind Harmer
9.722
958381AF2-132 GEN
Solar/Wind Harmer
13.632
964861AG1-349 GEN
Solar/Wind Harmer
11.778
971917AH1-482 GEN
Solar/Wind Harmer
13.589
24441205WTRV SLR C
Solar/Wind Harmer
0.199
276655WTG1_EQ
Solar/Wind Harmer
12.845
276656WTG2_EQ
Solar/Wind Harmer
1.701
939741AE1-205 GEN
Solar/Wind Harmer
29.433
270449AD2-020 GEN
Solar/Wind Harmer
4.082
943021AE2-325 GEN
Solar/Wind Harmer
5.305
957891AF2-083 GEN
Solar/Wind Harmer
21.813
940581AE2-045 GEN
Solar/Wind Harmer
14.707
971605AH1-302 GEN
Solar/Wind Harmer
12.575
24639705ELKHART HY
Adder
0.186
965931AG1-462 GEN
Solar/Wind Harmer
37.652
971087AG2-675 GEN
Solar/Wind Harmer
5.494
276863AD2-134 GEN
Solar/Wind Harmer
2.926
971411AH1-196 GEN
Solar/Wind Harmer
24.562
970073AG2-061 GEN
Solar/Wind Harmer
3.802
971171AH1-044 GEN
Solar/Wind Harmer
32.47
274823ROCKFORD ;21
Adder
31.469
274863CRW1-WTG
Solar/Wind Harmer
8.966
274864CRW2-WTG
Solar/Wind Harmer
8.966
270526AF1-158 GEN
Solar/Wind Harmer
7.249
274856ECOGROVE ;U1
Solar/Wind Harmer
5.39
276611AD2-172 GEN
Solar/Wind Harmer
4.089
276612AE2-035 GEN
Solar/Wind Harmer
4.089
276889AE2-281 GEN
Solar/Wind Harmer
3.066
971681AH1-341 GEN
Solar/Wind Harmer
23.771
926823AC1-168 GEN
Solar/Wind Harmer
6.783
970169AG2-114 GEN
Solar/Wind Harmer
15.664
972267AH1-718 GEN
Adder
6.467
276741O09 GEN1
Solar/Wind Harmer
5.517
274877BISHOP HL;1U
Solar/Wind Harmer
5.115
971771AH1-392 GEN
Solar/Wind Harmer
13.649
946321AF1-296 GEN
Solar/Wind Harmer
15.529
958391AF2-133 GEN
Solar/Wind Harmer
13.426
276726Z2-087_GEN
Solar/Wind Harmer
11.637
959341AF2-225 GEN
Solar/Wind Harmer
22.075
959141AF2-205 GEN
Solar/Wind Harmer
8.848
944161AF1-084 GEN
Solar/Wind Harmer
3.226
274853TWINGROVE;U1
Solar/Wind Harmer
10.309
274854TWINGROVE;U2
Solar/Wind Harmer
1.061
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.307
NYPJM->LTFIMP_NY
CLTF
2.412
LGEELTFEXP_LGEE->PJM
CLTF
0.79
WECLTFEXP_WEC->PJM
CLTF
6.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
164.421
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.437
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.477
MECLTFEXP_MEC->PJM
CLTF
21.057
SIGELTFEXP_SIGE->PJM
CLTF
0.218
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.731
AG2-052LTFEXP_AG2-052->PJM
LTF
0.349
AH1-155LTFEXP_AH1-155->PJM
LTF
0.523
LAGNLTFEXP_LAGN->PJM
CLTF
9.447
TVALTFEXP_TVA->PJM
CLTF
3.137

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.88 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6455.24
MW Contribution:
28.52
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
14.354
274771LINCOLN ;2U
50/50
14.354
970349AG2-230 GEN
Solar/Wind Harmer
33.698
276897AD1-100 C
Solar/Wind Harmer
96.099
274888KELLY CRK;1U
Solar/Wind Harmer
12.159
276776AD2-060 GEN
Solar/Wind Harmer
0.863
958011AF2-095 GEN
Solar/Wind Harmer
29.672
970941AG2-585 GEN
Solar/Wind Harmer
11.333
965681AG1-436 GEN
Solar/Wind Harmer
25.631
965791AG1-447 GEN
Solar/Wind Harmer
13.113
274674JOLIET 9 ;6U
Adder
31.523
274805UNIV PK N;1U
Adder
10.241
274808UNIV PK N;4U
Adder
10.174
276893AG1-478 C
Solar/Wind Harmer
0.894
274695ROCKY RD ;2P
Adder
22.398
274693ROCKY RD ;1P
Adder
22.177
274697ROCKY RD ;3P
Adder
6.084
274696ROCKY RD ;4P
Adder
22.926
274683WAUKEGAN ;8U
Adder
42.139
274683WAUKEGAN ;8U
Adder
35.522
962691AG1-118 GEN
Solar/Wind Harmer
59.904
960751AF2-366 GEN
Solar/Wind Harmer
5.711
958481AF2-142 GEN
Solar/Wind Harmer
29.827
276901AD2-066 C O1
Solar/Wind Harmer
6.889
958491AF2-143 GEN
Solar/Wind Harmer
29.417
971341AH1-150 GEN
Solar/Wind Harmer
38.858
971343AH1-151 GEN
Solar/Wind Harmer
38.858
972235AH1-702 GEN1
Adder
4.859
972236AH1-702 GEN2
Adder
4.225
270535AF1-215 GEN1
Solar/Wind Harmer
8.733
270536AF1-215 GEN2
Solar/Wind Harmer
8.733
276872AE1-163_GEN1
Solar/Wind Harmer
12.914
276876AE1-163_GEN2
Solar/Wind Harmer
12.914
938861AE1-114 GEN
Solar/Wind Harmer
15.58
274764LEE CO EC;5U
Adder
17.639
274765LEE CO EC;6U
Adder
17.639
274762LEE CO EC;3U
Adder
17.597
274763LEE CO EC;4U
Adder
17.431
276158O29GEN2
Solar/Wind Harmer
9.31
276157O29GEN1
Solar/Wind Harmer
7.079
276645AC1-214 GEN1
Solar/Wind Harmer
2.476
942111AE2-223 GEN
Solar/Wind Harmer
14.834
945421AF1-207 GEN
Solar/Wind Harmer
25.334
957841AF2-078 GEN
Solar/Wind Harmer
10.906
247620Y3-023
Adder
0.633
274772LINCOLN ;3U
50/50
14.354
972259AH1-714 GEN
50/50
42.287
971347AH1-153 GEN
Solar/Wind Harmer
11.233
970707AG2-453 GEN
Solar/Wind Harmer
59.281
939351AE1-166 GEN
Solar/Wind Harmer
12.269
276164X3-005 C
Solar/Wind Harmer
1.449
274887GEN-1.85
Solar/Wind Harmer
10.978
276772AC2-154 GEN
Solar/Wind Harmer
5.75
276843GEN-1.7
Solar/Wind Harmer
1.181
276806AD2-047 C O1
Solar/Wind Harmer
22.043
274724RIVER EC ;11
Adder
36.378
972038AH1-567 GEN2
Adder
0.75
943121AE2-341 GEN
Solar/Wind Harmer
30.81
943591AF1-030 GEN
Solar/Wind Harmer
20.54
274826FISK ;BP
Adder
22.485
274803UNIV PARK;6U
Adder
11.953
274676JOLIET 29;8U
Adder
60.634
274729ELWOOD EC;1P
Adder
33.593
274730ELWOOD EC;6P
Adder
33.592
274734ELWOOD EC;8P
Adder
33.592
274736ELWOOD EC;9P
Adder
33.592
274814UNIV PK N;0U
Adder
10.308
274807UNIV PK N;3U
Adder
10.286
274811UNIV PK N;7U
Adder
10.219
972231SS25-0005
Solar/Wind Harmer
19.247
972181SS23-001
Solar/Wind Harmer
12.03
274752CRETE EC ;2U
Adder
9.913
274753CRETE EC ;3U
Adder
9.913
274682WAUKEGAN ;7U
Adder
35.996
274862TOP CROP ;2U
Solar/Wind Harmer
10.047
276799AD1-013 GEN
Solar/Wind Harmer
4.333
946671AF1-331 GEN
Solar/Wind Harmer
0.821
274855GSG-6 ;RU
Solar/Wind Harmer
7.234
274850MENDOTA H;RU
Solar/Wind Harmer
5.03
276602WESTBROOK C
Solar/Wind Harmer
4.165
276868AE1-113 GEN
Solar/Wind Harmer
19.781
274879MINONK ;1U
Solar/Wind Harmer
13.188
959091AF2-200 GEN
Solar/Wind Harmer
38.858
24441505OLIV SLR
Solar/Wind Harmer
0.26
970571AG2-364 GEN
Solar/Wind Harmer
37.943
964401AG1-302 GEN
Solar/Wind Harmer
17.169
274857EASY ROAD;U1
Solar/Wind Harmer
9.062
274760LEE CO EC;1U
Adder
17.597
274767LEE CO EC;8U
Adder
17.39
276603SUBLETTE C
Solar/Wind Harmer
1.98
274851PROVIDENC;RU
Solar/Wind Harmer
5.265
274849CRESCENT ;1U
Solar/Wind Harmer
3.418
276782AC1-033 GEN
Solar/Wind Harmer
7.324
274878BISHOP HL;2U
Solar/Wind Harmer
6.197
965931AG1-462 GEN
Solar/Wind Harmer
45.525
971087AG2-675 GEN
Solar/Wind Harmer
6.643
270505AE1-170 C O1
Solar/Wind Harmer
26.743
965091AG1-374 GEN
Solar/Wind Harmer
36.699
24344105CKG2
50/50
19.954
274773LINCOLN ;4U
50/50
14.354
274774LINCOLN ;5U
50/50
14.354
972207SS24-0001
Solar/Wind Harmer
48.096
941551AE2-152 GEN
Solar/Wind Harmer
9.382
274871GR RIDGE ;2U
Solar/Wind Harmer
15.794
274847GR RIDGE ;BU
Solar/Wind Harmer
10.385
274723RIVER EC ;12
Adder
36.775
274802UNIV PARK;5U
Adder
11.953
274676JOLIET 29;8U
Adder
62.88
274674JOLIET 9 ;6U
Adder
31.523
274745AC1-111 GEN9
Adder
11.424
274732ELWOOD EC;7P
Adder
33.592
274812UNIV PK N;8U
Adder
10.219
274751CRETE EC ;1U
Adder
9.913
274754CRETE EC ;4U
Adder
9.913
274682WAUKEGAN ;7U
Adder
35.996
274828WAUKEGAN ;BP
Adder
22.089
962781AG1-127 GEN
Solar/Wind Harmer
18.93
276694AA1-018 GEN2
Solar/Wind Harmer
12.547
276691AA1-018 GEN1
Solar/Wind Harmer
1.5
274861TOP CROP ;1U
Solar/Wind Harmer
12.033
274872LEEDK;1U
Solar/Wind Harmer
16.294
939401AE1-172 GEN
Solar/Wind Harmer
27.589
276805AD2-038 GEN
Solar/Wind Harmer
10.057
971997AH1-543 GEN
Solar/Wind Harmer
30.868
970373AG2-245 GEN
Solar/Wind Harmer
41.094
276882AE2-255 GEN
Solar/Wind Harmer
6.594
957471AF2-041 GEN
Solar/Wind Harmer
58.287
959081AF2-199 GEN
Solar/Wind Harmer
19.429
971067AG2-660 GEN
Solar/Wind Harmer
4.518
274822ROCKFORD ;11
Adder
37.946
270055AF2-134 C O1
Solar/Wind Harmer
5.822
970819AG2-516 GEN
Solar/Wind Harmer
23.034
970569AG2-363 GEN
Solar/Wind Harmer
56.914
958381AF2-132 GEN
Solar/Wind Harmer
17.169
274858EASY ROAD;U2
Solar/Wind Harmer
9.062
274761LEE CO EC;2U
Adder
17.597
274766LEE CO EC;7U
Adder
17.39
964861AG1-349 GEN
Solar/Wind Harmer
14.852
971917AH1-482 GEN
Solar/Wind Harmer
17.136
276708O09 GEN2
Solar/Wind Harmer
6.648
276646AC1-214 GEN2
Solar/Wind Harmer
2.476
940581AE2-045 GEN
Solar/Wind Harmer
18.841
971605AH1-302 GEN
Solar/Wind Harmer
16.11
274848CAMPGROVE;RU
Solar/Wind Harmer
11.799
276655WTG1_EQ
Solar/Wind Harmer
15.794
276656WTG2_EQ
Solar/Wind Harmer
2.091
939741AE1-205 GEN
Solar/Wind Harmer
36.19
24441205WTRV SLR C
Solar/Wind Harmer
0.239
970091AG2-072 GEN
Adder
127.265
24639705ELKHART HY
Adder
0.232
274775LINCOLN ;6U
50/50
14.354
274776LINCOLN ;7U
50/50
14.354
274777LINCOLN ;8U
50/50
14.354
274661LASCO STA;2U
50/50
11.601
274660LASCO STA;1U
50/50
15.017
972228AH1-698 GEN2
Adder
7.663
972227AH1-698 GEN1
Adder
5.396
960591AF2-350 GEN
Solar/Wind Harmer
20.605
970833AG2-524 GEN
Solar/Wind Harmer
17.935
970833AG2-524 GEN
Solar/Wind Harmer
8.342
274800UNIV PARK;3U
Adder
11.976
274801UNIV PARK;4U
Adder
11.976
274827FISK ;RP
Adder
15.936
960681AF2-359 GEN
Solar/Wind Harmer
7.748
972037AH1-567 GEN1
Adder
0.375
274675JOLIET 29;7U
Adder
62.882
274675JOLIET 29;7U
Adder
60.636
274687WILL CNTY;4U
Adder
57.233
274687WILL CNTY;4U
Adder
57.233
274744AC1-111 GEN8
Adder
11.424
274746AC1-111 G10
Adder
11.424
274731ELWOOD EC;2P
Adder
33.593
274733ELWOOD EC;3P
Adder
33.593
274735ELWOOD EC;4P
Adder
33.593
274728ELWOOD EC;5P
Adder
33.592
276893AG1-478 C
Solar/Wind Harmer
1.122
970073AG2-061 GEN
Solar/Wind Harmer
4.561
971675AH1-338 GEN
Solar/Wind Harmer
35.284
276861AD2-134 GEN
Solar/Wind Harmer
3.498
276863AD2-134 GEN
Solar/Wind Harmer
3.498
971411AH1-196 GEN
Solar/Wind Harmer
29.363
971171AH1-044 GEN
Solar/Wind Harmer
38.858
274863CRW1-WTG
Solar/Wind Harmer
10.833
274864CRW2-WTG
Solar/Wind Harmer
10.833
274823ROCKFORD ;21
Adder
37.671
276889AE2-281 GEN
Solar/Wind Harmer
3.69
270526AF1-158 GEN
Solar/Wind Harmer
8.708
274856ECOGROVE ;U1
Solar/Wind Harmer
6.46
276611AD2-172 GEN
Solar/Wind Harmer
4.9
276612AE2-035 GEN
Solar/Wind Harmer
4.9
926823AC1-168 GEN
Solar/Wind Harmer
8.181
971681AH1-341 GEN
Solar/Wind Harmer
28.524
970169AG2-114 GEN
Solar/Wind Harmer
19.011
958391AF2-133 GEN
Solar/Wind Harmer
17.015
972267AH1-718 GEN
Adder
7.776
959141AF2-205 GEN
Solar/Wind Harmer
11.266
276741O09 GEN1
Solar/Wind Harmer
6.648
274877BISHOP HL;1U
Solar/Wind Harmer
6.197
971771AH1-392 GEN
Solar/Wind Harmer
16.472
276726Z2-087_GEN
Solar/Wind Harmer
14.308
959341AF2-225 GEN
Solar/Wind Harmer
27.143
946321AF1-296 GEN
Solar/Wind Harmer
18.76
274853TWINGROVE;U1
Solar/Wind Harmer
12.743
274854TWINGROVE;U2
Solar/Wind Harmer
12.476
NYPJM->LTFIMP_NY
CLTF
2.971
LGEELTFEXP_LGEE->PJM
CLTF
1.539
WECLTFEXP_WEC->PJM
CLTF
7.334
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.262
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.61
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
107.682
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.627
MECLTFEXP_MEC->PJM
CLTF
25.788
SIGELTFEXP_SIGE->PJM
CLTF
0.335
AG2-052LTFEXP_AG2-052->PJM
LTF
0.429
AH1-155LTFEXP_AH1-155->PJM
LTF
0.643
LAGNLTFEXP_LAGN->PJM
CLTF
11.814
TVALTFEXP_TVA->PJM
CLTF
3.934

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.28 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5814.76
MW Contribution:
25.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
13.107
274776LINCOLN ;7U
50/50
13.107
274777LINCOLN ;8U
50/50
13.107
274661LASCO STA;2U
50/50
10.565
274660LASCO STA;1U
50/50
13.676
972228AH1-698 GEN2
Adder
6.97
972227AH1-698 GEN1
Adder
4.908
960591AF2-350 GEN
Solar/Wind Harmer
18.736
970833AG2-524 GEN
Solar/Wind Harmer
16.319
970833AG2-524 GEN
Solar/Wind Harmer
7.59
274800UNIV PARK;3U
Adder
10.888
274801UNIV PARK;4U
Adder
10.888
274827FISK ;RP
Adder
14.488
274675JOLIET 29;7U
Adder
57.205
274675JOLIET 29;7U
Adder
55.162
972037AH1-567 GEN1
Adder
0.341
274687WILL CNTY;4U
Adder
52.056
274687WILL CNTY;4U
Adder
52.056
274744AC1-111 GEN8
Adder
10.402
274746AC1-111 G10
Adder
10.402
274731ELWOOD EC;2P
Adder
30.548
274733ELWOOD EC;3P
Adder
30.548
274735ELWOOD EC;4P
Adder
30.548
274728ELWOOD EC;5P
Adder
30.547
960681AF2-359 GEN
Solar/Wind Harmer
7.007
276893AG1-478 C
Solar/Wind Harmer
1.02
971675AH1-338 GEN
Solar/Wind Harmer
32.101
276861AD2-134 GEN
Solar/Wind Harmer
3.183
276863AD2-134 GEN
Solar/Wind Harmer
3.183
971411AH1-196 GEN
Solar/Wind Harmer
26.713
970073AG2-061 GEN
Solar/Wind Harmer
4.14
971171AH1-044 GEN
Solar/Wind Harmer
35.344
274823ROCKFORD ;21
Adder
34.265
274863CRW1-WTG
Solar/Wind Harmer
9.803
274864CRW2-WTG
Solar/Wind Harmer
9.803
276889AE2-281 GEN
Solar/Wind Harmer
3.347
274856ECOGROVE ;U1
Solar/Wind Harmer
5.874
276611AD2-172 GEN
Solar/Wind Harmer
4.456
276612AE2-035 GEN
Solar/Wind Harmer
4.456
270526AF1-158 GEN
Solar/Wind Harmer
7.859
971681AH1-341 GEN
Solar/Wind Harmer
25.93
926823AC1-168 GEN
Solar/Wind Harmer
7.416
970169AG2-114 GEN
Solar/Wind Harmer
17.177
972267AH1-718 GEN
Adder
7.067
276741O09 GEN1
Solar/Wind Harmer
6.036
274877BISHOP HL;1U
Solar/Wind Harmer
5.612
971771AH1-392 GEN
Solar/Wind Harmer
14.838
958391AF2-133 GEN
Solar/Wind Harmer
14.844
946321AF1-296 GEN
Solar/Wind Harmer
17.035
276726Z2-087_GEN
Solar/Wind Harmer
12.866
959341AF2-225 GEN
Solar/Wind Harmer
24.408
959141AF2-205 GEN
Solar/Wind Harmer
9.801
274853TWINGROVE;U1
Solar/Wind Harmer
11.439
274854TWINGROVE;U2
Solar/Wind Harmer
11.199
944161AF1-084 GEN
Solar/Wind Harmer
3.508
274770LINCOLN ;1U
50/50
13.107
274771LINCOLN ;2U
50/50
13.107
970349AG2-230 GEN
Solar/Wind Harmer
30.814
276897AD1-100 C
Solar/Wind Harmer
87.406
274888KELLY CRK;1U
Solar/Wind Harmer
11.056
276776AD2-060 GEN
Solar/Wind Harmer
0.784
958011AF2-095 GEN
Solar/Wind Harmer
26.979
970941AG2-585 GEN
Solar/Wind Harmer
10.305
274674JOLIET 9 ;6U
Adder
28.674
965681AG1-436 GEN
Solar/Wind Harmer
23.18
965791AG1-447 GEN
Solar/Wind Harmer
11.859
276893AG1-478 C
Solar/Wind Harmer
0.813
274805UNIV PK N;1U
Adder
9.298
274808UNIV PK N;4U
Adder
9.237
274695ROCKY RD ;2P
Adder
20.387
274693ROCKY RD ;1P
Adder
20.186
274697ROCKY RD ;3P
Adder
5.538
274696ROCKY RD ;4P
Adder
20.867
274683WAUKEGAN ;8U
Adder
38.346
274683WAUKEGAN ;8U
Adder
32.324
962691AG1-118 GEN
Solar/Wind Harmer
54.524
960751AF2-366 GEN
Solar/Wind Harmer
5.198
958481AF2-142 GEN
Solar/Wind Harmer
27.089
276901AD2-066 C O1
Solar/Wind Harmer
6.252
958491AF2-143 GEN
Solar/Wind Harmer
26.701
971341AH1-150 GEN
Solar/Wind Harmer
35.344
971343AH1-151 GEN
Solar/Wind Harmer
35.344
972235AH1-702 GEN1
Adder
4.419
972236AH1-702 GEN2
Adder
3.843
276872AE1-163_GEN1
Solar/Wind Harmer
11.713
276876AE1-163_GEN2
Solar/Wind Harmer
11.713
938861AE1-114 GEN
Solar/Wind Harmer
14.164
274764LEE CO EC;5U
Adder
16.035
274765LEE CO EC;6U
Adder
16.035
274762LEE CO EC;3U
Adder
15.997
274763LEE CO EC;4U
Adder
15.846
270535AF1-215 GEN1
Solar/Wind Harmer
7.7
270536AF1-215 GEN2
Solar/Wind Harmer
7.7
276158O29GEN2
Solar/Wind Harmer
8.453
276157O29GEN1
Solar/Wind Harmer
6.427
276645AC1-214 GEN1
Solar/Wind Harmer
2.242
942111AE2-223 GEN
Solar/Wind Harmer
13.339
960611AF2-352 GEN
Solar/Wind Harmer
3.692
247620Y3-023
Adder
0.558
274772LINCOLN ;3U
50/50
13.107
972259AH1-714 GEN
50/50
38.51
971347AH1-153 GEN
Solar/Wind Harmer
10.271
970707AG2-453 GEN
Solar/Wind Harmer
54.061
939351AE1-166 GEN
Solar/Wind Harmer
11.159
276164X3-005 C
Solar/Wind Harmer
1.317
274887GEN-1.85
Solar/Wind Harmer
9.982
276772AC2-154 GEN
Solar/Wind Harmer
5.229
276843GEN-1.7
Solar/Wind Harmer
1.074
276806AD2-047 C O1
Solar/Wind Harmer
20.043
943121AE2-341 GEN
Solar/Wind Harmer
28.067
943591AF1-030 GEN
Solar/Wind Harmer
18.711
972038AH1-567 GEN2
Adder
0.682
274826FISK ;BP
Adder
20.443
274724RIVER EC ;11
Adder
33.047
274676JOLIET 29;8U
Adder
55.16
274803UNIV PARK;6U
Adder
10.863
274729ELWOOD EC;1P
Adder
30.548
274730ELWOOD EC;6P
Adder
30.547
274734ELWOOD EC;8P
Adder
30.547
274736ELWOOD EC;9P
Adder
30.547
274814UNIV PK N;0U
Adder
9.359
274807UNIV PK N;3U
Adder
9.338
274811UNIV PK N;7U
Adder
9.277
972231SS25-0005
Solar/Wind Harmer
17.453
972181SS23-001
Solar/Wind Harmer
10.908
274752CRETE EC ;2U
Adder
8.989
274753CRETE EC ;3U
Adder
8.989
274682WAUKEGAN ;7U
Adder
32.756
274862TOP CROP ;2U
Solar/Wind Harmer
9.124
276799AD1-013 GEN
Solar/Wind Harmer
3.942
946671AF1-331 GEN
Solar/Wind Harmer
0.747
274855GSG-6 ;RU
Solar/Wind Harmer
6.582
274850MENDOTA H;RU
Solar/Wind Harmer
4.576
276602WESTBROOK C
Solar/Wind Harmer
3.789
276868AE1-113 GEN
Solar/Wind Harmer
17.957
274879MINONK ;1U
Solar/Wind Harmer
11.972
959091AF2-200 GEN
Solar/Wind Harmer
35.344
24441505OLIV SLR
Solar/Wind Harmer
0.234
970571AG2-364 GEN
Solar/Wind Harmer
34.394
274857EASY ROAD;U1
Solar/Wind Harmer
8.237
274760LEE CO EC;1U
Adder
15.997
274767LEE CO EC;8U
Adder
15.808
276603SUBLETTE C
Solar/Wind Harmer
1.8
274851PROVIDENC;RU
Solar/Wind Harmer
4.767
274849CRESCENT ;1U
Solar/Wind Harmer
3.095
276782AC1-033 GEN
Solar/Wind Harmer
6.634
274878BISHOP HL;2U
Solar/Wind Harmer
5.612
964401AG1-302 GEN
Solar/Wind Harmer
15.035
965931AG1-462 GEN
Solar/Wind Harmer
41.335
971087AG2-675 GEN
Solar/Wind Harmer
6.032
270505AE1-170 C O1
Solar/Wind Harmer
24.099
965091AG1-374 GEN
Solar/Wind Harmer
47.632
959611AF2-252 GEN
Solar/Wind Harmer
3.692
24344105CKG2
50/50
18.459
274773LINCOLN ;4U
50/50
13.107
274774LINCOLN ;5U
50/50
13.107
972207SS24-0001
Solar/Wind Harmer
43.918
941551AE2-152 GEN
Solar/Wind Harmer
8.533
274871GR RIDGE ;2U
Solar/Wind Harmer
14.371
274847GR RIDGE ;BU
Solar/Wind Harmer
9.45
274676JOLIET 29;8U
Adder
57.203
274723RIVER EC ;12
Adder
33.403
274802UNIV PARK;5U
Adder
10.863
274674JOLIET 9 ;6U
Adder
28.674
274745AC1-111 GEN9
Adder
10.402
274732ELWOOD EC;7P
Adder
30.547
274812UNIV PK N;8U
Adder
9.277
274751CRETE EC ;1U
Adder
8.989
274754CRETE EC ;4U
Adder
8.989
274682WAUKEGAN ;7U
Adder
32.756
274828WAUKEGAN ;BP
Adder
20.1
962781AG1-127 GEN
Solar/Wind Harmer
17.229
274872LEEDK;1U
Solar/Wind Harmer
14.829
276694AA1-018 GEN2
Solar/Wind Harmer
11.395
276691AA1-018 GEN1
Solar/Wind Harmer
1.362
274861TOP CROP ;1U
Solar/Wind Harmer
10.928
939401AE1-172 GEN
Solar/Wind Harmer
25.006
971997AH1-543 GEN
Solar/Wind Harmer
28.024
276805AD2-038 GEN
Solar/Wind Harmer
9.128
276882AE2-255 GEN
Solar/Wind Harmer
5.986
957471AF2-041 GEN
Solar/Wind Harmer
53.016
959081AF2-199 GEN
Solar/Wind Harmer
17.672
971067AG2-660 GEN
Solar/Wind Harmer
4.11
274822ROCKFORD ;11
Adder
34.515
970819AG2-516 GEN
Solar/Wind Harmer
20.949
970373AG2-245 GEN
Solar/Wind Harmer
36.468
970569AG2-363 GEN
Solar/Wind Harmer
51.591
274858EASY ROAD;U2
Solar/Wind Harmer
8.237
274761LEE CO EC;2U
Adder
15.997
274766LEE CO EC;7U
Adder
15.808
270055AF2-134 C O1
Solar/Wind Harmer
5.133
276708O09 GEN2
Solar/Wind Harmer
6.036
276646AC1-214 GEN2
Solar/Wind Harmer
2.242
958381AF2-132 GEN
Solar/Wind Harmer
15.035
274848CAMPGROVE;RU
Solar/Wind Harmer
10.679
964861AG1-349 GEN
Solar/Wind Harmer
12.996
971917AH1-482 GEN
Solar/Wind Harmer
14.994
276655WTG1_EQ
Solar/Wind Harmer
14.202
276656WTG2_EQ
Solar/Wind Harmer
1.88
939741AE1-205 GEN
Solar/Wind Harmer
32.544
24441205WTRV SLR C
Solar/Wind Harmer
0.216
940581AE2-045 GEN
Solar/Wind Harmer
16.332
971605AH1-302 GEN
Solar/Wind Harmer
13.964
24639705ELKHART HY
Adder
0.206
970091AG2-072 GEN
Adder
82.471
270449AD2-020 GEN
Solar/Wind Harmer
2.744
943021AE2-325 GEN
Solar/Wind Harmer
3.566
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.466
NYPJM->LTFIMP_NY
CLTF
2.772
LGEELTFEXP_LGEE->PJM
CLTF
3.226
WECLTFEXP_WEC->PJM
CLTF
6.672
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.32
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.391
MECLTFEXP_MEC->PJM
CLTF
23.429
SIGELTFEXP_SIGE->PJM
CLTF
0.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.025
AG2-052LTFEXP_AG2-052->PJM
LTF
0.385
AH1-155LTFEXP_AH1-155->PJM
LTF
0.577
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.714
LAGNLTFEXP_LAGN->PJM
CLTF
11.241
TVALTFEXP_TVA->PJM
CLTF
3.967

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.47 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5769.93
MW Contribution:
27.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
14.2
274776LINCOLN ;7U
50/50
14.2
274777LINCOLN ;8U
50/50
14.2
274661LASCO STA;2U
50/50
11.434
274660LASCO STA;1U
50/50
14.801
960681AF2-359 GEN
Solar/Wind Harmer
7.752
972228AH1-698 GEN2
Adder
7.55
972227AH1-698 GEN1
Adder
5.316
960591AF2-350 GEN
Solar/Wind Harmer
20.31
274827FISK ;RP
Adder
15.722
274800UNIV PARK;3U
Adder
11.81
274801UNIV PARK;4U
Adder
11.81
972037AH1-567 GEN1
Adder
0.37
970833AG2-524 GEN
Solar/Wind Harmer
17.634
970833AG2-524 GEN
Solar/Wind Harmer
8.202
274675JOLIET 29;7U
Adder
61.928
274675JOLIET 29;7U
Adder
59.716
274687WILL CNTY;4U
Adder
56.379
274687WILL CNTY;4U
Adder
56.379
274728ELWOOD EC;5P
Adder
33.049
274731ELWOOD EC;2P
Adder
33.05
274733ELWOOD EC;3P
Adder
33.05
274735ELWOOD EC;4P
Adder
33.05
274744AC1-111 GEN8
Adder
11.233
274746AC1-111 G10
Adder
11.233
276893AG1-478 C
Solar/Wind Harmer
1.104
270526AF1-158 GEN
Solar/Wind Harmer
8.736
971675AH1-338 GEN
Solar/Wind Harmer
34.53
276861AD2-134 GEN
Solar/Wind Harmer
3.423
276863AD2-134 GEN
Solar/Wind Harmer
3.423
970073AG2-061 GEN
Solar/Wind Harmer
4.459
971411AH1-196 GEN
Solar/Wind Harmer
28.745
971171AH1-044 GEN
Solar/Wind Harmer
37.991
274823ROCKFORD ;21
Adder
36.825
274863CRW1-WTG
Solar/Wind Harmer
10.5
274864CRW2-WTG
Solar/Wind Harmer
10.5
276889AE2-281 GEN
Solar/Wind Harmer
3.594
274856ECOGROVE ;U1
Solar/Wind Harmer
6.307
276611AD2-172 GEN
Solar/Wind Harmer
4.784
276612AE2-035 GEN
Solar/Wind Harmer
4.784
958391AF2-133 GEN
Solar/Wind Harmer
16.858
971681AH1-341 GEN
Solar/Wind Harmer
27.815
926823AC1-168 GEN
Solar/Wind Harmer
7.944
959141AF2-205 GEN
Solar/Wind Harmer
11.153
971771AH1-392 GEN
Solar/Wind Harmer
16.564
274770LINCOLN ;1U
50/50
14.2
274771LINCOLN ;2U
50/50
14.2
270102X2-052 ST
50/50
3.302
270100X2-052 CT1
50/50
3.05
24344105CKG2
50/50
20.132
274773LINCOLN ;4U
50/50
14.2
274774LINCOLN ;5U
50/50
14.2
972207SS24-0001
Solar/Wind Harmer
47.58
941551AE2-152 GEN
Solar/Wind Harmer
9.227
274723RIVER EC ;12
Adder
36.384
274802UNIV PARK;5U
Adder
11.792
274871GR RIDGE ;2U
Solar/Wind Harmer
15.527
274847GR RIDGE ;BU
Solar/Wind Harmer
10.21
274676JOLIET 29;8U
Adder
61.926
274812UNIV PK N;8U
Adder
10.097
274674JOLIET 9 ;6U
Adder
31.025
274732ELWOOD EC;7P
Adder
33.049
274745AC1-111 GEN9
Adder
11.233
274751CRETE EC ;1U
Adder
9.812
274754CRETE EC ;4U
Adder
9.812
274682WAUKEGAN ;7U
Adder
35.341
274828WAUKEGAN ;BP
Adder
21.683
962781AG1-127 GEN
Solar/Wind Harmer
18.559
276694AA1-018 GEN2
Solar/Wind Harmer
12.298
970373AG2-245 GEN
Solar/Wind Harmer
40.93
276691AA1-018 GEN1
Solar/Wind Harmer
1.47
274861TOP CROP ;1U
Solar/Wind Harmer
11.794
274872LEEDK;1U
Solar/Wind Harmer
15.969
274772LINCOLN ;3U
50/50
14.2
972259AH1-714 GEN
50/50
41.679
971347AH1-153 GEN
Solar/Wind Harmer
11.31
970707AG2-453 GEN
Solar/Wind Harmer
58.482
276164X3-005 C
Solar/Wind Harmer
1.432
939351AE1-166 GEN
Solar/Wind Harmer
12.066
274724RIVER EC ;11
Adder
35.991
274887GEN-1.85
Solar/Wind Harmer
10.821
276772AC2-154 GEN
Solar/Wind Harmer
5.668
276843GEN-1.7
Solar/Wind Harmer
1.164
276806AD2-047 C O1
Solar/Wind Harmer
21.727
274826FISK ;BP
Adder
22.183
972038AH1-567 GEN2
Adder
0.739
274803UNIV PARK;6U
Adder
11.792
943121AE2-341 GEN
Solar/Wind Harmer
30.308
943591AF1-030 GEN
Solar/Wind Harmer
20.205
274676JOLIET 29;8U
Adder
59.714
274814UNIV PK N;0U
Adder
10.186
274807UNIV PK N;3U
Adder
10.164
274811UNIV PK N;7U
Adder
10.097
274729ELWOOD EC;1P
Adder
33.05
274730ELWOOD EC;6P
Adder
33.049
274734ELWOOD EC;8P
Adder
33.049
274736ELWOOD EC;9P
Adder
33.049
972231SS25-0005
Solar/Wind Harmer
19.052
972181SS23-001
Solar/Wind Harmer
11.907
274752CRETE EC ;2U
Adder
9.812
274753CRETE EC ;3U
Adder
9.812
274682WAUKEGAN ;7U
Adder
35.341
24441505OLIV SLR
Solar/Wind Harmer
0.26
274862TOP CROP ;2U
Solar/Wind Harmer
9.847
276799AD1-013 GEN
Solar/Wind Harmer
4.241
946671AF1-331 GEN
Solar/Wind Harmer
0.804
274855GSG-6 ;RU
Solar/Wind Harmer
7.079
274850MENDOTA H;RU
Solar/Wind Harmer
4.922
276602WESTBROOK C
Solar/Wind Harmer
4.075
276868AE1-113 GEN
Solar/Wind Harmer
19.321
274879MINONK ;1U
Solar/Wind Harmer
12.881
959091AF2-200 GEN
Solar/Wind Harmer
37.991
964401AG1-302 GEN
Solar/Wind Harmer
17.03
274857EASY ROAD;U1
Solar/Wind Harmer
8.832
274760LEE CO EC;1U
Adder
17.152
274767LEE CO EC;8U
Adder
16.95
970571AG2-364 GEN
Solar/Wind Harmer
36.866
276603SUBLETTE C
Solar/Wind Harmer
1.929
270505AE1-170 C O1
Solar/Wind Harmer
26.946
274851PROVIDENC;RU
Solar/Wind Harmer
5.09
274849CRESCENT ;1U
Solar/Wind Harmer
3.305
276782AC1-033 GEN
Solar/Wind Harmer
7.079
274878BISHOP HL;2U
Solar/Wind Harmer
5.989
965931AG1-462 GEN
Solar/Wind Harmer
44.05
971087AG2-675 GEN
Solar/Wind Harmer
6.428
970169AG2-114 GEN
Solar/Wind Harmer
18.347
972267AH1-718 GEN
Adder
7.567
276741O09 GEN1
Solar/Wind Harmer
6.457
274877BISHOP HL;1U
Solar/Wind Harmer
5.989
944161AF1-084 GEN
Solar/Wind Harmer
3.922
946321AF1-296 GEN
Solar/Wind Harmer
18.169
276726Z2-087_GEN
Solar/Wind Harmer
8.421
959341AF2-225 GEN
Solar/Wind Harmer
15.975
270101X2-052 CT2
50/50
3.05
970349AG2-230 GEN
Solar/Wind Harmer
33.931
965681AG1-436 GEN
Solar/Wind Harmer
25.645
965791AG1-447 GEN
Solar/Wind Harmer
13.121
276897AD1-100 C
Solar/Wind Harmer
94.51
274888KELLY CRK;1U
Solar/Wind Harmer
11.985
276776AD2-060 GEN
Solar/Wind Harmer
0.85
958011AF2-095 GEN
Solar/Wind Harmer
29.247
970941AG2-585 GEN
Solar/Wind Harmer
11.171
274805UNIV PK N;1U
Adder
10.12
274808UNIV PK N;4U
Adder
10.053
274674JOLIET 9 ;6U
Adder
31.025
276893AG1-478 C
Solar/Wind Harmer
0.88
274695ROCKY RD ;2P
Adder
21.991
274693ROCKY RD ;1P
Adder
21.775
274697ROCKY RD ;3P
Adder
5.974
274696ROCKY RD ;4P
Adder
22.509
274683WAUKEGAN ;8U
Adder
41.366
274683WAUKEGAN ;8U
Adder
34.869
962691AG1-118 GEN
Solar/Wind Harmer
58.752
960751AF2-366 GEN
Solar/Wind Harmer
5.599
958481AF2-142 GEN
Solar/Wind Harmer
29.235
276901AD2-066 C O1
Solar/Wind Harmer
6.728
958491AF2-143 GEN
Solar/Wind Harmer
28.76
270535AF1-215 GEN1
Solar/Wind Harmer
8.681
270536AF1-215 GEN2
Solar/Wind Harmer
8.681
971341AH1-150 GEN
Solar/Wind Harmer
37.991
971343AH1-151 GEN
Solar/Wind Harmer
37.991
972235AH1-702 GEN1
Adder
4.748
972236AH1-702 GEN2
Adder
4.129
276872AE1-163_GEN1
Solar/Wind Harmer
12.58
276876AE1-163_GEN2
Solar/Wind Harmer
12.58
938861AE1-114 GEN
Solar/Wind Harmer
15.194
274764LEE CO EC;5U
Adder
17.192
274765LEE CO EC;6U
Adder
17.192
274762LEE CO EC;3U
Adder
17.152
274763LEE CO EC;4U
Adder
16.99
276158O29GEN2
Solar/Wind Harmer
9.043
276157O29GEN1
Solar/Wind Harmer
6.875
276645AC1-214 GEN1
Solar/Wind Harmer
2.394
945421AF1-207 GEN
Solar/Wind Harmer
24.972
957841AF2-078 GEN
Solar/Wind Harmer
10.75
961051AF2-396 GEN
Solar/Wind Harmer
27.758
961051AF2-396 GEN
Solar/Wind Harmer
12.911
247620Y3-023
Adder
0.639
942111AE2-223 GEN
Solar/Wind Harmer
8.73
939401AE1-172 GEN
Solar/Wind Harmer
26.858
276805AD2-038 GEN
Solar/Wind Harmer
9.832
270055AF2-134 C O1
Solar/Wind Harmer
5.787
971997AH1-543 GEN
Solar/Wind Harmer
30.118
276882AE2-255 GEN
Solar/Wind Harmer
6.441
957471AF2-041 GEN
Solar/Wind Harmer
56.986
959081AF2-199 GEN
Solar/Wind Harmer
18.995
971067AG2-660 GEN
Solar/Wind Harmer
4.418
274822ROCKFORD ;11
Adder
37.094
958381AF2-132 GEN
Solar/Wind Harmer
17.03
970819AG2-516 GEN
Solar/Wind Harmer
22.498
964861AG1-349 GEN
Solar/Wind Harmer
14.729
971917AH1-482 GEN
Solar/Wind Harmer
16.993
274858EASY ROAD;U2
Solar/Wind Harmer
8.832
274761LEE CO EC;2U
Adder
17.152
274766LEE CO EC;7U
Adder
16.95
970569AG2-363 GEN
Solar/Wind Harmer
55.3
940581AE2-045 GEN
Solar/Wind Harmer
18.631
971605AH1-302 GEN
Solar/Wind Harmer
15.93
276708O09 GEN2
Solar/Wind Harmer
6.457
24441205WTRV SLR C
Solar/Wind Harmer
0.241
276646AC1-214 GEN2
Solar/Wind Harmer
2.394
270449AD2-020 GEN
Solar/Wind Harmer
4.968
943021AE2-325 GEN
Solar/Wind Harmer
6.456
957891AF2-083 GEN
Solar/Wind Harmer
26.586
274848CAMPGROVE;RU
Solar/Wind Harmer
11.386
276655WTG1_EQ
Solar/Wind Harmer
15.057
276656WTG2_EQ
Solar/Wind Harmer
1.994
939741AE1-205 GEN
Solar/Wind Harmer
34.503
24639705ELKHART HY
Adder
0.234
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.596
NYPJM->LTFIMP_NY
CLTF
2.797
LGEELTFEXP_LGEE->PJM
CLTF
1.86
WECLTFEXP_WEC->PJM
CLTF
7.169
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.48
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.637
MECLTFEXP_MEC->PJM
CLTF
24.605
SIGELTFEXP_SIGE->PJM
CLTF
0.291
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.22
AG2-052LTFEXP_AG2-052->PJM
LTF
0.42
AH1-155LTFEXP_AH1-155->PJM
LTF
0.63
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.182
LAGNLTFEXP_LAGN->PJM
CLTF
10.73
TVALTFEXP_TVA->PJM
CLTF
3.51

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.26 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5758.3
MW Contribution:
25.99
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
13.132
274776LINCOLN ;7U
50/50
13.132
274777LINCOLN ;8U
50/50
13.132
274661LASCO STA;2U
50/50
10.585
274660LASCO STA;1U
50/50
13.702
972228AH1-698 GEN2
Adder
6.984
972227AH1-698 GEN1
Adder
4.917
960591AF2-350 GEN
Solar/Wind Harmer
18.773
970833AG2-524 GEN
Solar/Wind Harmer
16.351
970833AG2-524 GEN
Solar/Wind Harmer
7.605
274800UNIV PARK;3U
Adder
10.91
274801UNIV PARK;4U
Adder
10.91
274827FISK ;RP
Adder
14.517
274770LINCOLN ;1U
50/50
13.132
274771LINCOLN ;2U
50/50
13.132
970349AG2-230 GEN
Solar/Wind Harmer
30.869
276897AD1-100 C
Solar/Wind Harmer
87.577
274888KELLY CRK;1U
Solar/Wind Harmer
11.078
276776AD2-060 GEN
Solar/Wind Harmer
0.786
958011AF2-095 GEN
Solar/Wind Harmer
27.033
970941AG2-585 GEN
Solar/Wind Harmer
10.325
274674JOLIET 9 ;6U
Adder
28.731
965681AG1-436 GEN
Solar/Wind Harmer
23.226
965791AG1-447 GEN
Solar/Wind Harmer
11.883
276893AG1-478 C
Solar/Wind Harmer
0.815
274805UNIV PK N;1U
Adder
9.316
274808UNIV PK N;4U
Adder
9.255
274695ROCKY RD ;2P
Adder
20.428
274693ROCKY RD ;1P
Adder
20.227
274697ROCKY RD ;3P
Adder
5.549
274696ROCKY RD ;4P
Adder
20.909
274683WAUKEGAN ;8U
Adder
38.424
274683WAUKEGAN ;8U
Adder
32.389
962691AG1-118 GEN
Solar/Wind Harmer
54.635
960751AF2-366 GEN
Solar/Wind Harmer
5.208
958481AF2-142 GEN
Solar/Wind Harmer
27.144
276901AD2-066 C O1
Solar/Wind Harmer
6.265
958491AF2-143 GEN
Solar/Wind Harmer
26.757
971341AH1-150 GEN
Solar/Wind Harmer
35.418
971343AH1-151 GEN
Solar/Wind Harmer
35.418
972235AH1-702 GEN1
Adder
4.429
972236AH1-702 GEN2
Adder
3.851
276872AE1-163_GEN1
Solar/Wind Harmer
11.738
276876AE1-163_GEN2
Solar/Wind Harmer
11.738
938861AE1-114 GEN
Solar/Wind Harmer
14.195
274764LEE CO EC;5U
Adder
16.069
274765LEE CO EC;6U
Adder
16.069
274762LEE CO EC;3U
Adder
16.031
274763LEE CO EC;4U
Adder
15.88
270535AF1-215 GEN1
Solar/Wind Harmer
7.717
270536AF1-215 GEN2
Solar/Wind Harmer
7.717
276158O29GEN2
Solar/Wind Harmer
8.472
276157O29GEN1
Solar/Wind Harmer
6.441
276645AC1-214 GEN1
Solar/Wind Harmer
2.247
942111AE2-223 GEN
Solar/Wind Harmer
13.369
960611AF2-352 GEN
Solar/Wind Harmer
3.701
247620Y3-023
Adder
0.559
274772LINCOLN ;3U
50/50
13.132
972259AH1-714 GEN
50/50
38.585
971347AH1-153 GEN
Solar/Wind Harmer
10.29
970707AG2-453 GEN
Solar/Wind Harmer
54.165
939351AE1-166 GEN
Solar/Wind Harmer
11.181
276164X3-005 C
Solar/Wind Harmer
1.32
274887GEN-1.85
Solar/Wind Harmer
10.002
276772AC2-154 GEN
Solar/Wind Harmer
5.239
276843GEN-1.7
Solar/Wind Harmer
1.076
276806AD2-047 C O1
Solar/Wind Harmer
20.082
943121AE2-341 GEN
Solar/Wind Harmer
28.123
943591AF1-030 GEN
Solar/Wind Harmer
18.748
972038AH1-567 GEN2
Adder
0.683
274826FISK ;BP
Adder
20.483
274724RIVER EC ;11
Adder
33.112
274676JOLIET 29;8U
Adder
55.27
274803UNIV PARK;6U
Adder
10.885
274729ELWOOD EC;1P
Adder
30.609
274730ELWOOD EC;6P
Adder
30.608
274734ELWOOD EC;8P
Adder
30.608
274736ELWOOD EC;9P
Adder
30.608
274814UNIV PK N;0U
Adder
9.377
274807UNIV PK N;3U
Adder
9.357
274811UNIV PK N;7U
Adder
9.296
972231SS25-0005
Solar/Wind Harmer
17.488
972181SS23-001
Solar/Wind Harmer
10.93
274752CRETE EC ;2U
Adder
9.007
274753CRETE EC ;3U
Adder
9.007
274682WAUKEGAN ;7U
Adder
32.822
274862TOP CROP ;2U
Solar/Wind Harmer
9.143
276799AD1-013 GEN
Solar/Wind Harmer
3.951
946671AF1-331 GEN
Solar/Wind Harmer
0.749
274855GSG-6 ;RU
Solar/Wind Harmer
6.595
274850MENDOTA H;RU
Solar/Wind Harmer
4.586
276602WESTBROOK C
Solar/Wind Harmer
3.797
276868AE1-113 GEN
Solar/Wind Harmer
17.995
274879MINONK ;1U
Solar/Wind Harmer
11.997
959091AF2-200 GEN
Solar/Wind Harmer
35.418
24441505OLIV SLR
Solar/Wind Harmer
0.235
970571AG2-364 GEN
Solar/Wind Harmer
34.468
274857EASY ROAD;U1
Solar/Wind Harmer
8.255
274760LEE CO EC;1U
Adder
16.031
274767LEE CO EC;8U
Adder
15.842
276603SUBLETTE C
Solar/Wind Harmer
1.804
274851PROVIDENC;RU
Solar/Wind Harmer
4.778
274849CRESCENT ;1U
Solar/Wind Harmer
3.102
276782AC1-033 GEN
Solar/Wind Harmer
6.648
274878BISHOP HL;2U
Solar/Wind Harmer
5.625
964401AG1-302 GEN
Solar/Wind Harmer
15.068
965931AG1-462 GEN
Solar/Wind Harmer
41.429
971087AG2-675 GEN
Solar/Wind Harmer
6.045
270505AE1-170 C O1
Solar/Wind Harmer
24.154
965091AG1-374 GEN
Solar/Wind Harmer
47.742
959611AF2-252 GEN
Solar/Wind Harmer
3.701
274675JOLIET 29;7U
Adder
57.318
274675JOLIET 29;7U
Adder
55.271
972037AH1-567 GEN1
Adder
0.342
274687WILL CNTY;4U
Adder
52.16
274687WILL CNTY;4U
Adder
52.16
274744AC1-111 GEN8
Adder
10.422
274746AC1-111 G10
Adder
10.422
274731ELWOOD EC;2P
Adder
30.609
274733ELWOOD EC;3P
Adder
30.609
274735ELWOOD EC;4P
Adder
30.609
274728ELWOOD EC;5P
Adder
30.608
960681AF2-359 GEN
Solar/Wind Harmer
7.021
276893AG1-478 C
Solar/Wind Harmer
1.022
971675AH1-338 GEN
Solar/Wind Harmer
32.168
276861AD2-134 GEN
Solar/Wind Harmer
3.189
276863AD2-134 GEN
Solar/Wind Harmer
3.189
971411AH1-196 GEN
Solar/Wind Harmer
26.769
970073AG2-061 GEN
Solar/Wind Harmer
4.148
971171AH1-044 GEN
Solar/Wind Harmer
35.418
274823ROCKFORD ;21
Adder
34.337
274863CRW1-WTG
Solar/Wind Harmer
9.823
274864CRW2-WTG
Solar/Wind Harmer
9.823
276889AE2-281 GEN
Solar/Wind Harmer
3.354
274856ECOGROVE ;U1
Solar/Wind Harmer
5.887
276611AD2-172 GEN
Solar/Wind Harmer
4.466
276612AE2-035 GEN
Solar/Wind Harmer
4.466
270526AF1-158 GEN
Solar/Wind Harmer
7.876
971681AH1-341 GEN
Solar/Wind Harmer
25.986
926823AC1-168 GEN
Solar/Wind Harmer
7.431
970169AG2-114 GEN
Solar/Wind Harmer
17.214
972267AH1-718 GEN
Adder
7.082
276741O09 GEN1
Solar/Wind Harmer
6.049
274877BISHOP HL;1U
Solar/Wind Harmer
5.625
971771AH1-392 GEN
Solar/Wind Harmer
14.871
958391AF2-133 GEN
Solar/Wind Harmer
14.878
946321AF1-296 GEN
Solar/Wind Harmer
17.074
276726Z2-087_GEN
Solar/Wind Harmer
12.895
959341AF2-225 GEN
Solar/Wind Harmer
24.463
959141AF2-205 GEN
Solar/Wind Harmer
9.824
274853TWINGROVE;U1
Solar/Wind Harmer
11.466
274854TWINGROVE;U2
Solar/Wind Harmer
11.225
944161AF1-084 GEN
Solar/Wind Harmer
3.516
24344105CKG2
50/50
18.486
274773LINCOLN ;4U
50/50
13.132
274774LINCOLN ;5U
50/50
13.132
972207SS24-0001
Solar/Wind Harmer
43.999
941551AE2-152 GEN
Solar/Wind Harmer
8.55
274871GR RIDGE ;2U
Solar/Wind Harmer
14.399
274847GR RIDGE ;BU
Solar/Wind Harmer
9.468
274676JOLIET 29;8U
Adder
57.317
274723RIVER EC ;12
Adder
33.469
274802UNIV PARK;5U
Adder
10.885
274674JOLIET 9 ;6U
Adder
28.731
274745AC1-111 GEN9
Adder
10.422
274732ELWOOD EC;7P
Adder
30.608
274812UNIV PK N;8U
Adder
9.296
274751CRETE EC ;1U
Adder
9.007
274754CRETE EC ;4U
Adder
9.007
274682WAUKEGAN ;7U
Adder
32.822
274828WAUKEGAN ;BP
Adder
20.141
962781AG1-127 GEN
Solar/Wind Harmer
17.264
274872LEEDK;1U
Solar/Wind Harmer
14.859
276694AA1-018 GEN2
Solar/Wind Harmer
11.418
276691AA1-018 GEN1
Solar/Wind Harmer
1.365
274861TOP CROP ;1U
Solar/Wind Harmer
10.95
939401AE1-172 GEN
Solar/Wind Harmer
25.058
971997AH1-543 GEN
Solar/Wind Harmer
28.082
276805AD2-038 GEN
Solar/Wind Harmer
9.147
276882AE2-255 GEN
Solar/Wind Harmer
5.998
957471AF2-041 GEN
Solar/Wind Harmer
53.127
959081AF2-199 GEN
Solar/Wind Harmer
17.709
971067AG2-660 GEN
Solar/Wind Harmer
4.118
274822ROCKFORD ;11
Adder
34.587
970819AG2-516 GEN
Solar/Wind Harmer
20.993
970373AG2-245 GEN
Solar/Wind Harmer
36.545
970569AG2-363 GEN
Solar/Wind Harmer
51.702
274858EASY ROAD;U2
Solar/Wind Harmer
8.255
274761LEE CO EC;2U
Adder
16.031
274766LEE CO EC;7U
Adder
15.842
270055AF2-134 C O1
Solar/Wind Harmer
5.144
276708O09 GEN2
Solar/Wind Harmer
6.049
276646AC1-214 GEN2
Solar/Wind Harmer
2.247
958381AF2-132 GEN
Solar/Wind Harmer
15.068
274848CAMPGROVE;RU
Solar/Wind Harmer
10.703
964861AG1-349 GEN
Solar/Wind Harmer
13.025
971917AH1-482 GEN
Solar/Wind Harmer
15.028
276655WTG1_EQ
Solar/Wind Harmer
14.235
276656WTG2_EQ
Solar/Wind Harmer
1.885
939741AE1-205 GEN
Solar/Wind Harmer
32.617
24441205WTRV SLR C
Solar/Wind Harmer
0.216
940581AE2-045 GEN
Solar/Wind Harmer
16.37
971605AH1-302 GEN
Solar/Wind Harmer
13.997
24639705ELKHART HY
Adder
0.207
970091AG2-072 GEN
Adder
82.754
270449AD2-020 GEN
Solar/Wind Harmer
2.75
943021AE2-325 GEN
Solar/Wind Harmer
3.574
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.451
NYPJM->LTFIMP_NY
CLTF
2.748
LGEELTFEXP_LGEE->PJM
CLTF
3.252
WECLTFEXP_WEC->PJM
CLTF
6.686
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.531
MECLTFEXP_MEC->PJM
CLTF
23.491
SIGELTFEXP_SIGE->PJM
CLTF
0.349
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.001
AG2-052LTFEXP_AG2-052->PJM
LTF
0.385
AH1-155LTFEXP_AH1-155->PJM
LTF
0.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
100.213
LAGNLTFEXP_LAGN->PJM
CLTF
11.317
TVALTFEXP_TVA->PJM
CLTF
4.004

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P7-1_#11046___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11046___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.16 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5642.02
MW Contribution:
25.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
13.013
274776LINCOLN ;7U
50/50
13.013
274777LINCOLN ;8U
50/50
13.013
24344005CKG1
50/50
12.253
274661LASCO STA;2U
50/50
10.475
274660LASCO STA;1U
50/50
13.559
960681AF2-359 GEN
Solar/Wind Harmer
7.241
972228AH1-698 GEN2
Adder
6.918
972227AH1-698 GEN1
Adder
4.871
960591AF2-350 GEN
Solar/Wind Harmer
18.62
274827FISK ;RP
Adder
14.422
274770LINCOLN ;1U
50/50
13.013
274771LINCOLN ;2U
50/50
13.013
270102X2-052 ST
50/50
3.098
270100X2-052 CT1
50/50
2.862
270101X2-052 CT2
50/50
2.862
970349AG2-230 GEN
Solar/Wind Harmer
33.216
965681AG1-436 GEN
Solar/Wind Harmer
23.954
965791AG1-447 GEN
Solar/Wind Harmer
12.256
276897AD1-100 C
Solar/Wind Harmer
86.531
274888KELLY CRK;1U
Solar/Wind Harmer
10.988
276776AD2-060 GEN
Solar/Wind Harmer
0.779
958011AF2-095 GEN
Solar/Wind Harmer
26.813
970941AG2-585 GEN
Solar/Wind Harmer
10.241
274805UNIV PK N;1U
Adder
9.281
274808UNIV PK N;4U
Adder
9.22
274674JOLIET 9 ;6U
Adder
28.429
276893AG1-478 C
Solar/Wind Harmer
0.806
274695ROCKY RD ;2P
Adder
20.141
274693ROCKY RD ;1P
Adder
19.943
274697ROCKY RD ;3P
Adder
5.471
274696ROCKY RD ;4P
Adder
20.616
274683WAUKEGAN ;8U
Adder
37.89
274683WAUKEGAN ;8U
Adder
31.939
962691AG1-118 GEN
Solar/Wind Harmer
53.799
960751AF2-366 GEN
Solar/Wind Harmer
5.127
958481AF2-142 GEN
Solar/Wind Harmer
26.769
958491AF2-143 GEN
Solar/Wind Harmer
26.32
276901AD2-066 C O1
Solar/Wind Harmer
6.153
971341AH1-150 GEN
Solar/Wind Harmer
34.776
971343AH1-151 GEN
Solar/Wind Harmer
34.776
972235AH1-702 GEN1
Adder
4.346
972236AH1-702 GEN2
Adder
3.779
276872AE1-163_GEN1
Solar/Wind Harmer
11.504
276876AE1-163_GEN2
Solar/Wind Harmer
11.504
938861AE1-114 GEN
Solar/Wind Harmer
13.904
274764LEE CO EC;5U
Adder
15.732
274765LEE CO EC;6U
Adder
15.732
274762LEE CO EC;3U
Adder
15.695
274763LEE CO EC;4U
Adder
15.547
270535AF1-215 GEN1
Solar/Wind Harmer
7.601
270536AF1-215 GEN2
Solar/Wind Harmer
7.601
276158O29GEN2
Solar/Wind Harmer
8.268
276157O29GEN1
Solar/Wind Harmer
6.286
961051AF2-396 GEN
Solar/Wind Harmer
25.934
961051AF2-396 GEN
Solar/Wind Harmer
12.062
276645AC1-214 GEN1
Solar/Wind Harmer
2.185
942111AE2-223 GEN
Solar/Wind Harmer
12.829
247620Y3-023
Adder
0.56
270349AD2-093_GEN
Solar/Wind Helper
1.323
270471AD2-092_GEN
Solar/Wind Helper
1.323
274800UNIV PARK;3U
Adder
10.832
274801UNIV PARK;4U
Adder
10.832
972037AH1-567 GEN1
Adder
0.339
274675JOLIET 29;7U
Adder
56.754
274675JOLIET 29;7U
Adder
54.727
970833AG2-524 GEN
Solar/Wind Harmer
16.147
970833AG2-524 GEN
Solar/Wind Harmer
7.51
274687WILL CNTY;4U
Adder
51.679
274687WILL CNTY;4U
Adder
51.679
274728ELWOOD EC;5P
Adder
30.278
274731ELWOOD EC;2P
Adder
30.278
274733ELWOOD EC;3P
Adder
30.278
274735ELWOOD EC;4P
Adder
30.278
274744AC1-111 GEN8
Adder
10.289
274746AC1-111 G10
Adder
10.289
276893AG1-478 C
Solar/Wind Harmer
1.011
270526AF1-158 GEN
Solar/Wind Harmer
8.218
971675AH1-338 GEN
Solar/Wind Harmer
31.611
276861AD2-134 GEN
Solar/Wind Harmer
3.134
276863AD2-134 GEN
Solar/Wind Harmer
3.134
970073AG2-061 GEN
Solar/Wind Harmer
4.081
971411AH1-196 GEN
Solar/Wind Harmer
26.319
971771AH1-392 GEN
Solar/Wind Harmer
15.769
971171AH1-044 GEN
Solar/Wind Harmer
34.776
274823ROCKFORD ;21
Adder
33.712
274863CRW1-WTG
Solar/Wind Harmer
9.573
274864CRW2-WTG
Solar/Wind Harmer
9.573
276889AE2-281 GEN
Solar/Wind Harmer
3.287
274856ECOGROVE ;U1
Solar/Wind Harmer
5.773
276611AD2-172 GEN
Solar/Wind Harmer
4.379
276612AE2-035 GEN
Solar/Wind Harmer
4.379
971681AH1-341 GEN
Solar/Wind Harmer
25.453
926823AC1-168 GEN
Solar/Wind Harmer
7.255
970169AG2-114 GEN
Solar/Wind Harmer
16.707
972267AH1-718 GEN
Adder
6.922
944161AF1-084 GEN
Solar/Wind Harmer
3.67
276741O09 GEN1
Solar/Wind Harmer
5.904
274877BISHOP HL;1U
Solar/Wind Harmer
5.467
946321AF1-296 GEN
Solar/Wind Harmer
16.614
958391AF2-133 GEN
Solar/Wind Harmer
14.33
276726Z2-087_GEN
Solar/Wind Harmer
12.374
959341AF2-225 GEN
Solar/Wind Harmer
23.475
959141AF2-205 GEN
Solar/Wind Harmer
9.405
274772LINCOLN ;3U
50/50
13.013
972259AH1-714 GEN
50/50
38.183
971347AH1-153 GEN
Solar/Wind Harmer
11.072
970707AG2-453 GEN
Solar/Wind Harmer
53.574
276164X3-005 C
Solar/Wind Harmer
1.315
274724RIVER EC ;11
Adder
33.1
939351AE1-166 GEN
Solar/Wind Harmer
11.047
274887GEN-1.85
Solar/Wind Harmer
9.921
276772AC2-154 GEN
Solar/Wind Harmer
5.196
276843GEN-1.7
Solar/Wind Harmer
1.067
276806AD2-047 C O1
Solar/Wind Harmer
19.919
274826FISK ;BP
Adder
20.35
972038AH1-567 GEN2
Adder
0.678
274803UNIV PARK;6U
Adder
10.814
943121AE2-341 GEN
Solar/Wind Harmer
27.76
943591AF1-030 GEN
Solar/Wind Harmer
18.507
274676JOLIET 29;8U
Adder
54.726
274814UNIV PK N;0U
Adder
9.342
274807UNIV PK N;3U
Adder
9.322
274811UNIV PK N;7U
Adder
9.261
274729ELWOOD EC;1P
Adder
30.278
274730ELWOOD EC;6P
Adder
30.278
274734ELWOOD EC;8P
Adder
30.278
274736ELWOOD EC;9P
Adder
30.278
972231SS25-0005
Solar/Wind Harmer
17.481
972181SS23-001
Solar/Wind Harmer
10.926
274752CRETE EC ;2U
Adder
9.003
274753CRETE EC ;3U
Adder
9.003
24441505OLIV SLR
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
32.372
274862TOP CROP ;2U
Solar/Wind Harmer
9.016
276799AD1-013 GEN
Solar/Wind Harmer
3.882
946671AF1-331 GEN
Solar/Wind Harmer
0.736
274855GSG-6 ;RU
Solar/Wind Harmer
6.481
274850MENDOTA H;RU
Solar/Wind Harmer
4.506
276602WESTBROOK C
Solar/Wind Harmer
3.731
276868AE1-113 GEN
Solar/Wind Harmer
17.676
274879MINONK ;1U
Solar/Wind Harmer
11.785
959091AF2-200 GEN
Solar/Wind Harmer
34.776
270505AE1-170 C O1
Solar/Wind Harmer
25.43
274857EASY ROAD;U1
Solar/Wind Harmer
8.082
274760LEE CO EC;1U
Adder
15.695
274767LEE CO EC;8U
Adder
15.51
970571AG2-364 GEN
Solar/Wind Harmer
33.693
276603SUBLETTE C
Solar/Wind Harmer
1.765
274851PROVIDENC;RU
Solar/Wind Harmer
4.646
274849CRESCENT ;1U
Solar/Wind Harmer
3.016
276782AC1-033 GEN
Solar/Wind Harmer
6.462
274878BISHOP HL;2U
Solar/Wind Harmer
5.467
964401AG1-302 GEN
Solar/Wind Harmer
14.629
247643Z2-116 C
Solar/Wind Harmer
0.111
945111AF1-176 GEN
Solar/Wind Harmer
8.98
965931AG1-462 GEN
Solar/Wind Harmer
40.277
971087AG2-675 GEN
Solar/Wind Harmer
5.877
24344105CKG2
50/50
18.536
274773LINCOLN ;4U
50/50
13.013
274774LINCOLN ;5U
50/50
13.013
972207SS24-0001
Solar/Wind Harmer
43.601
274723RIVER EC ;12
Adder
33.447
941551AE2-152 GEN
Solar/Wind Harmer
8.448
274802UNIV PARK;5U
Adder
10.814
274676JOLIET 29;8U
Adder
56.753
274812UNIV PK N;8U
Adder
9.261
274871GR RIDGE ;2U
Solar/Wind Harmer
14.217
274847GR RIDGE ;BU
Solar/Wind Harmer
9.348
274674JOLIET 9 ;6U
Adder
28.429
274732ELWOOD EC;7P
Adder
30.278
274751CRETE EC ;1U
Adder
9.003
274754CRETE EC ;4U
Adder
9.003
274745AC1-111 GEN9
Adder
10.289
274682WAUKEGAN ;7U
Adder
32.372
274828WAUKEGAN ;BP
Adder
19.861
962781AG1-127 GEN
Solar/Wind Harmer
16.994
276694AA1-018 GEN2
Solar/Wind Harmer
11.261
276691AA1-018 GEN1
Solar/Wind Harmer
1.346
274861TOP CROP ;1U
Solar/Wind Harmer
10.799
274872LEEDK;1U
Solar/Wind Harmer
14.622
939401AE1-172 GEN
Solar/Wind Harmer
24.517
276805AD2-038 GEN
Solar/Wind Harmer
8.998
971997AH1-543 GEN
Solar/Wind Harmer
27.538
276882AE2-255 GEN
Solar/Wind Harmer
5.892
957471AF2-041 GEN
Solar/Wind Harmer
52.164
959081AF2-199 GEN
Solar/Wind Harmer
17.388
971067AG2-660 GEN
Solar/Wind Harmer
4.044
970373AG2-245 GEN
Solar/Wind Harmer
36.471
274822ROCKFORD ;11
Adder
33.958
970819AG2-516 GEN
Solar/Wind Harmer
20.595
274858EASY ROAD;U2
Solar/Wind Harmer
8.082
274761LEE CO EC;2U
Adder
15.695
274766LEE CO EC;7U
Adder
15.51
970569AG2-363 GEN
Solar/Wind Harmer
50.539
270055AF2-134 C O1
Solar/Wind Harmer
5.067
24441205WTRV SLR C
Solar/Wind Harmer
0.225
957891AF2-083 GEN
Solar/Wind Harmer
24.975
270449AD2-020 GEN
Solar/Wind Harmer
4.655
943021AE2-325 GEN
Solar/Wind Harmer
6.05
276708O09 GEN2
Solar/Wind Harmer
5.904
276646AC1-214 GEN2
Solar/Wind Harmer
2.185
958381AF2-132 GEN
Solar/Wind Harmer
14.629
274848CAMPGROVE;RU
Solar/Wind Harmer
10.389
964861AG1-349 GEN
Solar/Wind Harmer
12.625
971917AH1-482 GEN
Solar/Wind Harmer
14.566
945111AF1-176 GEN
Solar/Wind Harmer
28.333
270216AD2-079_GEN
Solar/Wind Harmer
0.948
276655WTG1_EQ
Solar/Wind Harmer
13.659
276656WTG2_EQ
Solar/Wind Harmer
1.809
939741AE1-205 GEN
Solar/Wind Harmer
31.299
24639705ELKHART HY
Adder
0.212
940581AE2-045 GEN
Solar/Wind Harmer
2.416
971605AH1-302 GEN
Solar/Wind Harmer
2.066
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.333
NYPJM->LTFIMP_NY
CLTF
2.587
LGEELTFEXP_LGEE->PJM
CLTF
1.849
WECLTFEXP_WEC->PJM
CLTF
6.565
CBM West 1LTFEXP_CBM-W1->PJM
CBM
178.559
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.487
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.969
MECLTFEXP_MEC->PJM
CLTF
22.505
SIGELTFEXP_SIGE->PJM
CLTF
0.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.793
AG2-052LTFEXP_AG2-052->PJM
LTF
0.381
AH1-155LTFEXP_AH1-155->PJM
LTF
0.572
LAGNLTFEXP_LAGN->PJM
CLTF
10.208
TVALTFEXP_TVA->PJM
CLTF
3.465

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#17234_05GRNTWN 765_N_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17234_05GRNTWN 765_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.35 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5542.35
MW Contribution:
26.95
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
13.873
274771LINCOLN ;2U
50/50
13.873
270102X2-052 ST
50/50
3.236
270100X2-052 CT1
50/50
2.989
270101X2-052 CT2
50/50
2.989
970349AG2-230 GEN
Solar/Wind Harmer
33.375
965681AG1-436 GEN
Solar/Wind Harmer
25.114
965791AG1-447 GEN
Solar/Wind Harmer
12.849
276897AD1-100 C
Solar/Wind Harmer
92.013
274888KELLY CRK;1U
Solar/Wind Harmer
11.676
276776AD2-060 GEN
Solar/Wind Harmer
0.828
958011AF2-095 GEN
Solar/Wind Harmer
28.493
970941AG2-585 GEN
Solar/Wind Harmer
10.883
274805UNIV PK N;1U
Adder
9.864
274808UNIV PK N;4U
Adder
9.799
274674JOLIET 9 ;6U
Adder
30.207
276893AG1-478 C
Solar/Wind Harmer
0.856
274695ROCKY RD ;2P
Adder
21.388
274693ROCKY RD ;1P
Adder
21.178
274697ROCKY RD ;3P
Adder
5.81
274696ROCKY RD ;4P
Adder
21.892
274683WAUKEGAN ;8U
Adder
40.223
274683WAUKEGAN ;8U
Adder
33.906
962691AG1-118 GEN
Solar/Wind Harmer
57.111
960751AF2-366 GEN
Solar/Wind Harmer
5.442
958481AF2-142 GEN
Solar/Wind Harmer
28.403
270535AF1-215 GEN1
Solar/Wind Harmer
8.468
270536AF1-215 GEN2
Solar/Wind Harmer
8.468
276901AD2-066 C O1
Solar/Wind Harmer
6.526
958491AF2-143 GEN
Solar/Wind Harmer
27.907
971341AH1-150 GEN
Solar/Wind Harmer
36.865
971343AH1-151 GEN
Solar/Wind Harmer
36.865
972235AH1-702 GEN1
Adder
4.606
972236AH1-702 GEN2
Adder
4.005
276872AE1-163_GEN1
Solar/Wind Harmer
12.185
276876AE1-163_GEN2
Solar/Wind Harmer
12.185
938861AE1-114 GEN
Solar/Wind Harmer
14.722
274764LEE CO EC;5U
Adder
16.654
274765LEE CO EC;6U
Adder
16.654
274762LEE CO EC;3U
Adder
16.615
274763LEE CO EC;4U
Adder
16.458
276158O29GEN2
Solar/Wind Harmer
8.744
276157O29GEN1
Solar/Wind Harmer
6.649
945421AF1-207 GEN
Solar/Wind Harmer
24.244
957841AF2-078 GEN
Solar/Wind Harmer
10.437
276645AC1-214 GEN1
Solar/Wind Harmer
2.31
961051AF2-396 GEN
Solar/Wind Harmer
27.123
961051AF2-396 GEN
Solar/Wind Harmer
12.615
270180AB1-006 GEN1
Solar/Wind Harmer
11.962
247620Y3-023
Adder
0.619
24697605MDL-3G C
Solar/Wind Harmer
0.114
274772LINCOLN ;3U
50/50
13.873
972259AH1-714 GEN
50/50
40.623
971347AH1-153 GEN
Solar/Wind Harmer
11.125
970707AG2-453 GEN
Solar/Wind Harmer
57.042
276164X3-005 C
Solar/Wind Harmer
1.396
274724RIVER EC ;11
Adder
35.102
939351AE1-166 GEN
Solar/Wind Harmer
11.747
274887GEN-1.85
Solar/Wind Harmer
10.542
276772AC2-154 GEN
Solar/Wind Harmer
5.522
276843GEN-1.7
Solar/Wind Harmer
1.134
276806AD2-047 C O1
Solar/Wind Harmer
21.168
274826FISK ;BP
Adder
21.617
972038AH1-567 GEN2
Adder
0.72
274803UNIV PARK;6U
Adder
11.49
943121AE2-341 GEN
Solar/Wind Harmer
29.511
943591AF1-030 GEN
Solar/Wind Harmer
19.674
274676JOLIET 29;8U
Adder
58.156
274814UNIV PK N;0U
Adder
9.929
274807UNIV PK N;3U
Adder
9.907
274811UNIV PK N;7U
Adder
9.842
274729ELWOOD EC;1P
Adder
32.173
972231SS25-0005
Solar/Wind Harmer
18.577
274730ELWOOD EC;6P
Adder
32.172
274734ELWOOD EC;8P
Adder
32.172
274736ELWOOD EC;9P
Adder
32.172
972181SS23-001
Solar/Wind Harmer
11.611
274752CRETE EC ;2U
Adder
9.568
274753CRETE EC ;3U
Adder
9.568
274682WAUKEGAN ;7U
Adder
34.368
24441505OLIV SLR
Solar/Wind Harmer
0.255
274862TOP CROP ;2U
Solar/Wind Harmer
9.566
276799AD1-013 GEN
Solar/Wind Harmer
4.118
946671AF1-331 GEN
Solar/Wind Harmer
0.78
274855GSG-6 ;RU
Solar/Wind Harmer
6.873
274850MENDOTA H;RU
Solar/Wind Harmer
4.779
276602WESTBROOK C
Solar/Wind Harmer
3.957
276868AE1-113 GEN
Solar/Wind Harmer
18.741
274879MINONK ;1U
Solar/Wind Harmer
12.494
959091AF2-200 GEN
Solar/Wind Harmer
36.865
964401AG1-302 GEN
Solar/Wind Harmer
16.593
274857EASY ROAD;U1
Solar/Wind Harmer
8.556
274760LEE CO EC;1U
Adder
16.615
274767LEE CO EC;8U
Adder
16.419
970571AG2-364 GEN
Solar/Wind Harmer
35.663
276603SUBLETTE C
Solar/Wind Harmer
1.868
270505AE1-170 C O1
Solar/Wind Harmer
26.348
274851PROVIDENC;RU
Solar/Wind Harmer
4.912
274849CRESCENT ;1U
Solar/Wind Harmer
3.189
276782AC1-033 GEN
Solar/Wind Harmer
6.83
274878BISHOP HL;2U
Solar/Wind Harmer
5.778
945111AF1-176 GEN
Solar/Wind Harmer
9.43
965931AG1-462 GEN
Solar/Wind Harmer
42.498
971087AG2-675 GEN
Solar/Wind Harmer
6.201
24690905MDL-1G C
Solar/Wind Harmer
13.352
274775LINCOLN ;6U
50/50
13.873
274776LINCOLN ;7U
50/50
13.873
274777LINCOLN ;8U
50/50
13.873
274660LASCO STA;1U
50/50
14.426
274661LASCO STA;2U
50/50
11.144
960681AF2-359 GEN
Solar/Wind Harmer
7.592
972228AH1-698 GEN2
Adder
7.356
972227AH1-698 GEN1
Adder
5.179
960591AF2-350 GEN
Solar/Wind Harmer
19.787
274827FISK ;RP
Adder
15.32
274800UNIV PARK;3U
Adder
11.506
274801UNIV PARK;4U
Adder
11.506
972037AH1-567 GEN1
Adder
0.361
970833AG2-524 GEN
Solar/Wind Harmer
17.165
970833AG2-524 GEN
Solar/Wind Harmer
7.984
274675JOLIET 29;7U
Adder
60.312
274675JOLIET 29;7U
Adder
58.158
274687WILL CNTY;4U
Adder
54.91
274687WILL CNTY;4U
Adder
54.91
274731ELWOOD EC;2P
Adder
32.173
274733ELWOOD EC;3P
Adder
32.173
274735ELWOOD EC;4P
Adder
32.173
274728ELWOOD EC;5P
Adder
32.172
274744AC1-111 GEN8
Adder
10.934
274746AC1-111 G10
Adder
10.934
276893AG1-478 C
Solar/Wind Harmer
1.074
270526AF1-158 GEN
Solar/Wind Harmer
8.546
971675AH1-338 GEN
Solar/Wind Harmer
33.525
276861AD2-134 GEN
Solar/Wind Harmer
3.324
276863AD2-134 GEN
Solar/Wind Harmer
3.324
971411AH1-196 GEN
Solar/Wind Harmer
27.91
970073AG2-061 GEN
Solar/Wind Harmer
4.327
971171AH1-044 GEN
Solar/Wind Harmer
36.865
274823ROCKFORD ;21
Adder
35.728
274863CRW1-WTG
Solar/Wind Harmer
10.151
274864CRW2-WTG
Solar/Wind Harmer
10.151
276889AE2-281 GEN
Solar/Wind Harmer
3.482
274856ECOGROVE ;U1
Solar/Wind Harmer
6.115
276611AD2-172 GEN
Solar/Wind Harmer
4.639
276612AE2-035 GEN
Solar/Wind Harmer
4.639
958391AF2-133 GEN
Solar/Wind Harmer
16.414
971771AH1-392 GEN
Solar/Wind Harmer
16.192
971681AH1-341 GEN
Solar/Wind Harmer
26.952
959141AF2-205 GEN
Solar/Wind Harmer
10.854
926823AC1-168 GEN
Solar/Wind Harmer
7.683
970169AG2-114 GEN
Solar/Wind Harmer
17.698
972267AH1-718 GEN
Adder
7.323
276741O09 GEN1
Solar/Wind Harmer
6.244
944161AF1-084 GEN
Solar/Wind Harmer
3.836
274877BISHOP HL;1U
Solar/Wind Harmer
5.778
946321AF1-296 GEN
Solar/Wind Harmer
17.537
946581AF1-322 GEN
Solar/Wind Harmer
17.017
24691005MDL-2G C
Solar/Wind Harmer
0.114
24344105CKG2
50/50
19.895
274773LINCOLN ;4U
50/50
13.873
274774LINCOLN ;5U
50/50
13.873
972207SS24-0001
Solar/Wind Harmer
46.485
941551AE2-152 GEN
Solar/Wind Harmer
8.983
274723RIVER EC ;12
Adder
35.484
274802UNIV PARK;5U
Adder
11.49
274871GR RIDGE ;2U
Solar/Wind Harmer
15.113
274847GR RIDGE ;BU
Solar/Wind Harmer
9.938
274676JOLIET 29;8U
Adder
60.31
274812UNIV PK N;8U
Adder
9.842
274674JOLIET 9 ;6U
Adder
30.207
274732ELWOOD EC;7P
Adder
32.172
274751CRETE EC ;1U
Adder
9.568
274754CRETE EC ;4U
Adder
9.568
274745AC1-111 GEN9
Adder
10.934
274682WAUKEGAN ;7U
Adder
34.368
274828WAUKEGAN ;BP
Adder
21.084
970373AG2-245 GEN
Solar/Wind Harmer
39.972
962781AG1-127 GEN
Solar/Wind Harmer
18.037
276694AA1-018 GEN2
Solar/Wind Harmer
11.948
276691AA1-018 GEN1
Solar/Wind Harmer
1.428
274861TOP CROP ;1U
Solar/Wind Harmer
11.457
274872LEEDK;1U
Solar/Wind Harmer
15.517
939401AE1-172 GEN
Solar/Wind Harmer
26.021
270055AF2-134 C O1
Solar/Wind Harmer
5.645
276805AD2-038 GEN
Solar/Wind Harmer
9.541
971997AH1-543 GEN
Solar/Wind Harmer
29.204
276882AE2-255 GEN
Solar/Wind Harmer
6.247
957471AF2-041 GEN
Solar/Wind Harmer
55.297
959081AF2-199 GEN
Solar/Wind Harmer
18.432
971067AG2-660 GEN
Solar/Wind Harmer
4.287
274822ROCKFORD ;11
Adder
35.989
958381AF2-132 GEN
Solar/Wind Harmer
16.593
964861AG1-349 GEN
Solar/Wind Harmer
14.349
971917AH1-482 GEN
Solar/Wind Harmer
16.555
970819AG2-516 GEN
Solar/Wind Harmer
21.818
274858EASY ROAD;U2
Solar/Wind Harmer
8.556
274761LEE CO EC;2U
Adder
16.615
274766LEE CO EC;7U
Adder
16.419
970569AG2-363 GEN
Solar/Wind Harmer
53.495
940581AE2-045 GEN
Solar/Wind Harmer
18.12
971605AH1-302 GEN
Solar/Wind Harmer
15.493
24441205WTRV SLR C
Solar/Wind Harmer
0.236
276708O09 GEN2
Solar/Wind Harmer
6.244
270449AD2-020 GEN
Solar/Wind Harmer
4.857
943021AE2-325 GEN
Solar/Wind Harmer
6.312
957891AF2-083 GEN
Solar/Wind Harmer
25.981
276646AC1-214 GEN2
Solar/Wind Harmer
2.31
274848CAMPGROVE;RU
Solar/Wind Harmer
10.977
945111AF1-176 GEN
Solar/Wind Harmer
29.755
24639705ELKHART HY
Adder
0.227
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.546
NYPJM->LTFIMP_NY
CLTF
2.646
LGEELTFEXP_LGEE->PJM
CLTF
0.959
WECLTFEXP_WEC->PJM
CLTF
6.954
CBM West 1LTFEXP_CBM-W1->PJM
CBM
190.051
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.426
MECLTFEXP_MEC->PJM
CLTF
23.53
SIGELTFEXP_SIGE->PJM
CLTF
0.23
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.123
AG2-052LTFEXP_AG2-052->PJM
LTF
0.406
AH1-155LTFEXP_AH1-155->PJM
LTF
0.609
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.532
LAGNLTFEXP_LAGN->PJM
CLTF
9.794
TVALTFEXP_TVA->PJM
CLTF
3.08

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P7-1_#11001___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11001___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.28 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5538.46
MW Contribution:
25.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274772LINCOLN ;3U
50/50
13.013
972259AH1-714 GEN
50/50
38.183
971347AH1-153 GEN
Solar/Wind Harmer
11.072
970707AG2-453 GEN
Solar/Wind Harmer
53.574
276164X3-005 C
Solar/Wind Harmer
1.315
274724RIVER EC ;11
Adder
33.1
939351AE1-166 GEN
Solar/Wind Harmer
11.047
274887GEN-1.85
Solar/Wind Harmer
9.921
276772AC2-154 GEN
Solar/Wind Harmer
5.196
276843GEN-1.7
Solar/Wind Harmer
1.067
276806AD2-047 C O1
Solar/Wind Harmer
19.919
274826FISK ;BP
Adder
20.35
972038AH1-567 GEN2
Adder
0.678
274803UNIV PARK;6U
Adder
10.814
943121AE2-341 GEN
Solar/Wind Harmer
27.76
943591AF1-030 GEN
Solar/Wind Harmer
18.507
274676JOLIET 29;8U
Adder
54.726
274814UNIV PK N;0U
Adder
9.342
274807UNIV PK N;3U
Adder
9.322
274811UNIV PK N;7U
Adder
9.261
274729ELWOOD EC;1P
Adder
30.278
274730ELWOOD EC;6P
Adder
30.278
274734ELWOOD EC;8P
Adder
30.278
274736ELWOOD EC;9P
Adder
30.278
972231SS25-0005
Solar/Wind Harmer
17.481
972181SS23-001
Solar/Wind Harmer
10.926
274752CRETE EC ;2U
Adder
9.003
274753CRETE EC ;3U
Adder
9.003
24441505OLIV SLR
Solar/Wind Harmer
0.244
274682WAUKEGAN ;7U
Adder
32.372
274862TOP CROP ;2U
Solar/Wind Harmer
9.016
276799AD1-013 GEN
Solar/Wind Harmer
3.882
946671AF1-331 GEN
Solar/Wind Harmer
0.736
274855GSG-6 ;RU
Solar/Wind Harmer
6.481
274850MENDOTA H;RU
Solar/Wind Harmer
4.506
276602WESTBROOK C
Solar/Wind Harmer
3.731
276868AE1-113 GEN
Solar/Wind Harmer
17.676
274879MINONK ;1U
Solar/Wind Harmer
11.785
959091AF2-200 GEN
Solar/Wind Harmer
34.776
270505AE1-170 C O1
Solar/Wind Harmer
25.43
274857EASY ROAD;U1
Solar/Wind Harmer
8.082
274760LEE CO EC;1U
Adder
15.695
274767LEE CO EC;8U
Adder
15.51
970571AG2-364 GEN
Solar/Wind Harmer
33.693
276603SUBLETTE C
Solar/Wind Harmer
1.765
274851PROVIDENC;RU
Solar/Wind Harmer
4.646
274849CRESCENT ;1U
Solar/Wind Harmer
3.016
276782AC1-033 GEN
Solar/Wind Harmer
6.462
274878BISHOP HL;2U
Solar/Wind Harmer
5.467
964401AG1-302 GEN
Solar/Wind Harmer
14.629
247643Z2-116 C
Solar/Wind Harmer
0.111
945111AF1-176 GEN
Solar/Wind Harmer
8.98
965931AG1-462 GEN
Solar/Wind Harmer
40.277
971087AG2-675 GEN
Solar/Wind Harmer
5.877
274770LINCOLN ;1U
50/50
13.013
274771LINCOLN ;2U
50/50
13.013
270102X2-052 ST
50/50
3.098
270100X2-052 CT1
50/50
2.862
270101X2-052 CT2
50/50
2.862
970349AG2-230 GEN
Solar/Wind Harmer
33.216
965681AG1-436 GEN
Solar/Wind Harmer
23.954
965791AG1-447 GEN
Solar/Wind Harmer
12.256
276897AD1-100 C
Solar/Wind Harmer
86.531
274888KELLY CRK;1U
Solar/Wind Harmer
10.988
276776AD2-060 GEN
Solar/Wind Harmer
0.779
958011AF2-095 GEN
Solar/Wind Harmer
26.813
970941AG2-585 GEN
Solar/Wind Harmer
10.241
274805UNIV PK N;1U
Adder
9.281
274808UNIV PK N;4U
Adder
9.22
274674JOLIET 9 ;6U
Adder
28.429
276893AG1-478 C
Solar/Wind Harmer
0.806
274695ROCKY RD ;2P
Adder
20.141
274693ROCKY RD ;1P
Adder
19.943
274697ROCKY RD ;3P
Adder
5.471
274696ROCKY RD ;4P
Adder
20.616
274683WAUKEGAN ;8U
Adder
37.89
274683WAUKEGAN ;8U
Adder
31.939
962691AG1-118 GEN
Solar/Wind Harmer
53.799
960751AF2-366 GEN
Solar/Wind Harmer
5.127
958481AF2-142 GEN
Solar/Wind Harmer
26.769
958491AF2-143 GEN
Solar/Wind Harmer
26.32
276901AD2-066 C O1
Solar/Wind Harmer
6.153
971341AH1-150 GEN
Solar/Wind Harmer
34.776
971343AH1-151 GEN
Solar/Wind Harmer
34.776
972235AH1-702 GEN1
Adder
4.346
972236AH1-702 GEN2
Adder
3.779
276872AE1-163_GEN1
Solar/Wind Harmer
11.504
276876AE1-163_GEN2
Solar/Wind Harmer
11.504
938861AE1-114 GEN
Solar/Wind Harmer
13.904
274764LEE CO EC;5U
Adder
15.732
274765LEE CO EC;6U
Adder
15.732
274762LEE CO EC;3U
Adder
15.695
274763LEE CO EC;4U
Adder
15.547
270535AF1-215 GEN1
Solar/Wind Harmer
7.601
270536AF1-215 GEN2
Solar/Wind Harmer
7.601
276158O29GEN2
Solar/Wind Harmer
8.268
276157O29GEN1
Solar/Wind Harmer
6.286
961051AF2-396 GEN
Solar/Wind Harmer
25.934
961051AF2-396 GEN
Solar/Wind Harmer
12.062
276645AC1-214 GEN1
Solar/Wind Harmer
2.185
942111AE2-223 GEN
Solar/Wind Harmer
12.829
247620Y3-023
Adder
0.56
270349AD2-093_GEN
Solar/Wind Helper
1.323
270471AD2-092_GEN
Solar/Wind Helper
1.323
24344105CKG2
50/50
18.536
274773LINCOLN ;4U
50/50
13.013
274774LINCOLN ;5U
50/50
13.013
972207SS24-0001
Solar/Wind Harmer
43.601
274723RIVER EC ;12
Adder
33.447
941551AE2-152 GEN
Solar/Wind Harmer
8.448
274802UNIV PARK;5U
Adder
10.814
274676JOLIET 29;8U
Adder
56.753
274812UNIV PK N;8U
Adder
9.261
274871GR RIDGE ;2U
Solar/Wind Harmer
14.217
274847GR RIDGE ;BU
Solar/Wind Harmer
9.348
274674JOLIET 9 ;6U
Adder
28.429
274732ELWOOD EC;7P
Adder
30.278
274751CRETE EC ;1U
Adder
9.003
274754CRETE EC ;4U
Adder
9.003
274745AC1-111 GEN9
Adder
10.289
274682WAUKEGAN ;7U
Adder
32.372
274828WAUKEGAN ;BP
Adder
19.861
962781AG1-127 GEN
Solar/Wind Harmer
16.994
276694AA1-018 GEN2
Solar/Wind Harmer
11.261
276691AA1-018 GEN1
Solar/Wind Harmer
1.346
274861TOP CROP ;1U
Solar/Wind Harmer
10.799
274872LEEDK;1U
Solar/Wind Harmer
14.622
939401AE1-172 GEN
Solar/Wind Harmer
24.517
276805AD2-038 GEN
Solar/Wind Harmer
8.998
971997AH1-543 GEN
Solar/Wind Harmer
27.538
276882AE2-255 GEN
Solar/Wind Harmer
5.892
957471AF2-041 GEN
Solar/Wind Harmer
52.164
959081AF2-199 GEN
Solar/Wind Harmer
17.388
971067AG2-660 GEN
Solar/Wind Harmer
4.044
970373AG2-245 GEN
Solar/Wind Harmer
36.471
274822ROCKFORD ;11
Adder
33.958
970819AG2-516 GEN
Solar/Wind Harmer
20.595
274858EASY ROAD;U2
Solar/Wind Harmer
8.082
274761LEE CO EC;2U
Adder
15.695
274766LEE CO EC;7U
Adder
15.51
970569AG2-363 GEN
Solar/Wind Harmer
50.539
270055AF2-134 C O1
Solar/Wind Harmer
5.067
24441205WTRV SLR C
Solar/Wind Harmer
0.225
957891AF2-083 GEN
Solar/Wind Harmer
24.975
270449AD2-020 GEN
Solar/Wind Harmer
4.655
943021AE2-325 GEN
Solar/Wind Harmer
6.05
276708O09 GEN2
Solar/Wind Harmer
5.904
276646AC1-214 GEN2
Solar/Wind Harmer
2.185
958381AF2-132 GEN
Solar/Wind Harmer
14.629
274848CAMPGROVE;RU
Solar/Wind Harmer
10.389
964861AG1-349 GEN
Solar/Wind Harmer
12.625
971917AH1-482 GEN
Solar/Wind Harmer
14.566
945111AF1-176 GEN
Solar/Wind Harmer
28.333
270216AD2-079_GEN
Solar/Wind Harmer
0.948
276655WTG1_EQ
Solar/Wind Harmer
13.659
276656WTG2_EQ
Solar/Wind Harmer
1.809
939741AE1-205 GEN
Solar/Wind Harmer
31.299
24639705ELKHART HY
Adder
0.212
940581AE2-045 GEN
Solar/Wind Harmer
2.416
971605AH1-302 GEN
Solar/Wind Harmer
2.066
274775LINCOLN ;6U
50/50
13.013
274776LINCOLN ;7U
50/50
13.013
274777LINCOLN ;8U
50/50
13.013
24344005CKG1
50/50
12.253
274661LASCO STA;2U
50/50
10.475
274660LASCO STA;1U
50/50
13.559
960681AF2-359 GEN
Solar/Wind Harmer
7.241
972228AH1-698 GEN2
Adder
6.918
972227AH1-698 GEN1
Adder
4.871
960591AF2-350 GEN
Solar/Wind Harmer
18.62
274827FISK ;RP
Adder
14.422
274800UNIV PARK;3U
Adder
10.832
274801UNIV PARK;4U
Adder
10.832
972037AH1-567 GEN1
Adder
0.339
274675JOLIET 29;7U
Adder
56.754
274675JOLIET 29;7U
Adder
54.727
970833AG2-524 GEN
Solar/Wind Harmer
16.147
970833AG2-524 GEN
Solar/Wind Harmer
7.51
274687WILL CNTY;4U
Adder
51.679
274687WILL CNTY;4U
Adder
51.679
274728ELWOOD EC;5P
Adder
30.278
274731ELWOOD EC;2P
Adder
30.278
274733ELWOOD EC;3P
Adder
30.278
274735ELWOOD EC;4P
Adder
30.278
274744AC1-111 GEN8
Adder
10.289
274746AC1-111 G10
Adder
10.289
276893AG1-478 C
Solar/Wind Harmer
1.011
270526AF1-158 GEN
Solar/Wind Harmer
8.218
971675AH1-338 GEN
Solar/Wind Harmer
31.611
276861AD2-134 GEN
Solar/Wind Harmer
3.134
276863AD2-134 GEN
Solar/Wind Harmer
3.134
970073AG2-061 GEN
Solar/Wind Harmer
4.081
971411AH1-196 GEN
Solar/Wind Harmer
26.319
971771AH1-392 GEN
Solar/Wind Harmer
15.769
971171AH1-044 GEN
Solar/Wind Harmer
34.776
274823ROCKFORD ;21
Adder
33.712
274863CRW1-WTG
Solar/Wind Harmer
9.573
274864CRW2-WTG
Solar/Wind Harmer
9.573
276889AE2-281 GEN
Solar/Wind Harmer
3.287
274856ECOGROVE ;U1
Solar/Wind Harmer
5.773
276611AD2-172 GEN
Solar/Wind Harmer
4.379
276612AE2-035 GEN
Solar/Wind Harmer
4.379
971681AH1-341 GEN
Solar/Wind Harmer
25.453
926823AC1-168 GEN
Solar/Wind Harmer
7.255
970169AG2-114 GEN
Solar/Wind Harmer
16.707
972267AH1-718 GEN
Adder
6.922
944161AF1-084 GEN
Solar/Wind Harmer
3.67
276741O09 GEN1
Solar/Wind Harmer
5.904
274877BISHOP HL;1U
Solar/Wind Harmer
5.467
946321AF1-296 GEN
Solar/Wind Harmer
16.614
958391AF2-133 GEN
Solar/Wind Harmer
14.33
276726Z2-087_GEN
Solar/Wind Harmer
12.374
959341AF2-225 GEN
Solar/Wind Harmer
23.475
959141AF2-205 GEN
Solar/Wind Harmer
9.405
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.333
NYPJM->LTFIMP_NY
CLTF
2.587
LGEELTFEXP_LGEE->PJM
CLTF
1.849
WECLTFEXP_WEC->PJM
CLTF
6.565
CBM West 1LTFEXP_CBM-W1->PJM
CBM
178.559
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.487
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.969
MECLTFEXP_MEC->PJM
CLTF
22.505
SIGELTFEXP_SIGE->PJM
CLTF
0.252
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.793
AG2-052LTFEXP_AG2-052->PJM
LTF
0.381
AH1-155LTFEXP_AH1-155->PJM
LTF
0.572
LAGNLTFEXP_LAGN->PJM
CLTF
10.208
TVALTFEXP_TVA->PJM
CLTF
3.465

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.16 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2151.12
MW Contribution:
9.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274752CRETE EC ;2U
50/50
4.789
274753CRETE EC ;3U
50/50
4.789
964401AG1-302 GEN
Solar/Wind Harmer
14.311
24441505OLIV SLR
Solar/Wind Harmer
0.179
972231SS25-0005
Solar/Wind Harmer
8.763
972181SS23-001
Solar/Wind Harmer
5.477
24690905MDL-1G C
Solar/Wind Harmer
6.802
970781AG2-491 GEN
Solar/Wind Harmer
8.473
274814UNIV PK N;0U
Adder
4.112
274807UNIV PK N;3U
Adder
4.103
274811UNIV PK N;7U
Adder
4.076
24386205FR-12G C
Solar/Wind Harmer
3.248
274803UNIV PARK;6U
Adder
4.085
972259AH1-714 GEN
Adder
12.815
274676JOLIET 29;8U
Adder
19.828
274730ELWOOD EC;6P
Adder
10.985
274734ELWOOD EC;8P
Adder
10.985
274736ELWOOD EC;9P
Adder
10.985
274729ELWOOD EC;1P
Adder
10.983
970707AG2-453 GEN
Solar/Wind Harmer
18.53
939351AE1-166 GEN
Solar/Wind Harmer
3.903
274862TOP CROP ;2U
Solar/Wind Harmer
3.322
274887GEN-1.85
Solar/Wind Harmer
3.486
276772AC2-154 GEN
Solar/Wind Harmer
1.826
276843GEN-1.7
Solar/Wind Harmer
0.375
276806AD2-047 C O1
Solar/Wind Harmer
7
274826FISK ;BP
Adder
7.128
274772LINCOLN ;3U
Adder
4.019
943121AE2-341 GEN
Solar/Wind Harmer
9.706
943591AF1-030 GEN
Solar/Wind Harmer
6.471
972038AH1-567 GEN2
Adder
0.235
274682WAUKEGAN ;7U
Adder
11.56
276868AE1-113 GEN
Solar/Wind Harmer
6.416
274879MINONK ;1U
Solar/Wind Harmer
4.278
276799AD1-013 GEN
Solar/Wind Harmer
1.377
946671AF1-331 GEN
Solar/Wind Harmer
0.261
270102X2-052 ST
50/50
4.736
270100X2-052 CT1
50/50
4.376
270101X2-052 CT2
50/50
4.376
965681AG1-436 GEN
Solar/Wind Harmer
32.209
965791AG1-447 GEN
Solar/Wind Harmer
16.479
270535AF1-215 GEN1
Solar/Wind Harmer
8.277
270536AF1-215 GEN2
Solar/Wind Harmer
8.277
945421AF1-207 GEN
Solar/Wind Harmer
12.671
957841AF2-078 GEN
Solar/Wind Harmer
5.455
270180AB1-006 GEN1
Solar/Wind Harmer
6.094
24697605MDL-3G C
Solar/Wind Harmer
3.123
24755605MDL-5G
Solar/Wind Harmer
2.043
24697905MDL-4G C
Solar/Wind Harmer
1.944
270181AB1-006 GEN2
Solar/Wind Harmer
0.606
274805UNIV PK N;1U
Adder
4.085
274808UNIV PK N;4U
Adder
4.059
24387305FR-4G C
Solar/Wind Harmer
3.85
966841AG1-555 GEN
Solar/Wind Harmer
1.903
276897AD1-100 C
Solar/Wind Harmer
30.569
276893AG1-478 C
Solar/Wind Harmer
0.288
274888KELLY CRK;1U
Solar/Wind Harmer
3.861
276776AD2-060 GEN
Solar/Wind Harmer
0.274
274674JOLIET 9 ;6U
Adder
10.074
970941AG2-585 GEN
Solar/Wind Harmer
3.599
958011AF2-095 GEN
Solar/Wind Harmer
9.422
958481AF2-142 GEN
Solar/Wind Harmer
9.8
274770LINCOLN ;1U
Adder
4.019
274771LINCOLN ;2U
Adder
4.019
274683WAUKEGAN ;8U
Adder
13.531
274683WAUKEGAN ;8U
Adder
11.406
958491AF2-143 GEN
Solar/Wind Harmer
9.625
274696ROCKY RD ;4P
Adder
7.311
274695ROCKY RD ;2P
Adder
7.143
274693ROCKY RD ;1P
Adder
7.072
274697ROCKY RD ;3P
Adder
1.94
970241AG2-163 GEN
Solar/Wind Harmer
15.875
962691AG1-118 GEN
Solar/Wind Harmer
19.011
276901AD2-066 C O1
Solar/Wind Harmer
2.221
960751AF2-366 GEN
Solar/Wind Harmer
1.813
276872AE1-163_GEN1
Solar/Wind Harmer
4.2
276876AE1-163_GEN2
Solar/Wind Harmer
4.2
971341AH1-150 GEN
Solar/Wind Harmer
12.373
971343AH1-151 GEN
Solar/Wind Harmer
12.373
972235AH1-702 GEN1
Adder
1.55
972236AH1-702 GEN2
Adder
1.348
938861AE1-114 GEN
Solar/Wind Harmer
4.968
274764LEE CO EC;5U
Adder
5.624
274765LEE CO EC;6U
Adder
5.624
274762LEE CO EC;3U
Adder
5.611
274763LEE CO EC;4U
Adder
5.558
276158O29GEN2
Solar/Wind Harmer
2.971
276157O29GEN1
Solar/Wind Harmer
2.259
276645AC1-214 GEN1
Solar/Wind Harmer
0.792
274751CRETE EC ;1U
50/50
4.789
274754CRETE EC ;4U
50/50
4.789
970373AG2-245 GEN
Solar/Wind Harmer
43.31
270055AF2-134 C O1
Solar/Wind Harmer
5.518
958381AF2-132 GEN
Solar/Wind Harmer
14.311
964861AG1-349 GEN
Solar/Wind Harmer
12.196
971917AH1-482 GEN
Solar/Wind Harmer
14.071
940581AE2-045 GEN
Solar/Wind Harmer
12.574
971605AH1-302 GEN
Solar/Wind Harmer
10.752
24791305MDL-5G
Solar/Wind Harmer
2.043
274812UNIV PK N;8U
Adder
4.076
24385905FR-11G C
Solar/Wind Harmer
6.3
24386605FR-22G C
Solar/Wind Harmer
3.26
274802UNIV PARK;5U
Adder
4.085
274676JOLIET 29;8U
Adder
20.562
274732ELWOOD EC;7P
Adder
10.985
274871GR RIDGE ;2U
Solar/Wind Harmer
5.073
274847GR RIDGE ;BU
Solar/Wind Harmer
3.336
941551AE2-152 GEN
Solar/Wind Harmer
2.985
274861TOP CROP ;1U
Solar/Wind Harmer
3.979
274674JOLIET 9 ;6U
Adder
10.074
276694AA1-018 GEN2
Solar/Wind Harmer
4.122
276691AA1-018 GEN1
Solar/Wind Harmer
0.493
274745AC1-111 GEN9
Adder
3.627
972207SS24-0001
Solar/Wind Harmer
14.289
274773LINCOLN ;4U
Adder
4.019
274855GSG-6 ;RU
Solar/Wind Harmer
2.298
274850MENDOTA H;RU
Solar/Wind Harmer
1.598
276602WESTBROOK C
Solar/Wind Harmer
1.323
959091AF2-200 GEN
Solar/Wind Harmer
12.373
970571AG2-364 GEN
Solar/Wind Harmer
12.287
276164X3-005 C
Solar/Wind Harmer
0.425
274857EASY ROAD;U1
Solar/Wind Harmer
2.889
274760LEE CO EC;1U
Adder
5.611
274767LEE CO EC;8U
Adder
5.545
276603SUBLETTE C
Solar/Wind Harmer
0.631
274851PROVIDENC;RU
Solar/Wind Harmer
1.685
274849CRESCENT ;1U
Solar/Wind Harmer
1.094
276782AC1-033 GEN
Solar/Wind Harmer
2.343
274878BISHOP HL;2U
Solar/Wind Harmer
1.982
274724RIVER EC ;11
Adder
9.961
960681AF2-359 GEN
Solar/Wind Harmer
9.736
958391AF2-133 GEN
Solar/Wind Harmer
13.144
959141AF2-205 GEN
Solar/Wind Harmer
8.182
270526AF1-158 GEN
Solar/Wind Harmer
5.12
946581AF1-322 GEN
Solar/Wind Harmer
8.669
24691005MDL-2G C
Solar/Wind Harmer
3.133
24386405FR-21G C
Solar/Wind Harmer
3.26
24387005FR-3G C
Solar/Wind Harmer
2.998
972037AH1-567 GEN1
Adder
0.128
963841AG1-237 GEN
Solar/Wind Harmer
7.585
972228AH1-698 GEN2
Adder
2.536
972227AH1-698 GEN1
Adder
1.785
274675JOLIET 29;7U
Adder
20.562
274675JOLIET 29;7U
Adder
19.827
274728ELWOOD EC;5P
Adder
10.985
274731ELWOOD EC;2P
Adder
10.983
274733ELWOOD EC;3P
Adder
10.983
274735ELWOOD EC;4P
Adder
10.983
274687WILL CNTY;4U
Adder
18.653
274687WILL CNTY;4U
Adder
18.653
970833AG2-524 GEN
Solar/Wind Harmer
5.757
970833AG2-524 GEN
Solar/Wind Harmer
2.678
276893AG1-478 C
Solar/Wind Harmer
0.361
960591AF2-350 GEN
Solar/Wind Harmer
6.543
274827FISK ;RP
Adder
5.051
274744AC1-111 GEN8
Adder
3.627
274746AC1-111 G10
Adder
3.627
274775LINCOLN ;6U
Adder
4.019
274776LINCOLN ;7U
Adder
4.019
274777LINCOLN ;8U
Adder
4.019
274800UNIV PARK;3U
Adder
3.76
274801UNIV PARK;4U
Adder
3.76
970073AG2-061 GEN
Solar/Wind Harmer
1.492
276889AE2-281 GEN
Solar/Wind Harmer
1.2
971411AH1-196 GEN
Solar/Wind Harmer
9.374
971675AH1-338 GEN
Solar/Wind Harmer
11.21
276861AD2-134 GEN
Solar/Wind Harmer
1.111
276863AD2-134 GEN
Solar/Wind Harmer
1.111
971171AH1-044 GEN
Solar/Wind Harmer
12.373
274823ROCKFORD ;21
Adder
12.019
274856ECOGROVE ;U1
Solar/Wind Harmer
2.061
276611AD2-172 GEN
Solar/Wind Harmer
1.563
276612AE2-035 GEN
Solar/Wind Harmer
1.563
274863CRW1-WTG
Solar/Wind Harmer
3.409
274864CRW2-WTG
Solar/Wind Harmer
3.409
926823AC1-168 GEN
Solar/Wind Harmer
2.622
971681AH1-341 GEN
Solar/Wind Harmer
9.093
970169AG2-114 GEN
Solar/Wind Harmer
5.997
972267AH1-718 GEN
Adder
2.479
276741O09 GEN1
Solar/Wind Harmer
2.121
274877BISHOP HL;1U
Solar/Wind Harmer
1.982
274774LINCOLN ;5U
Adder
4.019
274682WAUKEGAN ;7U
Adder
11.56
274828WAUKEGAN ;BP
Adder
7.093
276805AD2-038 GEN
Solar/Wind Harmer
3.29
963741AG1-226 GEN
Solar/Wind Harmer
28.575
276882AE2-255 GEN
Solar/Wind Harmer
2.139
962781AG1-127 GEN
Solar/Wind Harmer
6.008
274872LEEDK;1U
Solar/Wind Harmer
5.171
971997AH1-543 GEN
Solar/Wind Harmer
9.858
939401AE1-172 GEN
Solar/Wind Harmer
8.678
957471AF2-041 GEN
Solar/Wind Harmer
18.559
959081AF2-199 GEN
Solar/Wind Harmer
6.186
971067AG2-660 GEN
Solar/Wind Harmer
1.439
274822ROCKFORD ;11
Adder
12.107
970569AG2-363 GEN
Solar/Wind Harmer
18.43
970819AG2-516 GEN
Solar/Wind Harmer
7.35
274858EASY ROAD;U2
Solar/Wind Harmer
2.889
274761LEE CO EC;2U
Adder
5.611
274766LEE CO EC;7U
Adder
5.545
276708O09 GEN2
Solar/Wind Harmer
2.121
276646AC1-214 GEN2
Solar/Wind Harmer
0.792
274723RIVER EC ;12
Adder
10.284
274848CAMPGROVE;RU
Solar/Wind Harmer
1.101
991312J1772
External Queue
11.811302185058594
NYPJM->LTFIMP_NY
CLTF
0.91
LGEELTFEXP_LGEE->PJM
CLTF
0.682
WECLTFEXP_WEC->PJM
CLTF
2.35
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.165
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.045
CBM West 1LTFEXP_CBM-W1->PJM
CBM
40.98
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.162
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.08
MECLTFEXP_MEC->PJM
CLTF
8.225
SIGELTFEXP_SIGE->PJM
CLTF
0.1
LAGNLTFEXP_LAGN->PJM
CLTF
4.032
TVALTFEXP_TVA->PJM
CLTF
1.432

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.59 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2140.55
MW Contribution:
9.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
5.015
270100X2-052 CT1
50/50
4.634
270101X2-052 CT2
50/50
4.634
274815UNIV PK N;XU
50/50
0.261
274813UNIV PK N;9U
50/50
0.26
274816UNIV PK N;YU
50/50
0.26
274809UNIV PK N;5U
50/50
0.259
274805UNIV PK N;1U
50/50
4.764
274808UNIV PK N;4U
50/50
4.733
965681AG1-436 GEN
Solar/Wind Harmer
34.223
965791AG1-447 GEN
Solar/Wind Harmer
17.509
270535AF1-215 GEN1
Solar/Wind Harmer
8.19
270536AF1-215 GEN2
Solar/Wind Harmer
8.19
274888KELLY CRK;1U
Solar/Wind Harmer
4.271
276776AD2-060 GEN
Solar/Wind Harmer
0.303
958011AF2-095 GEN
Solar/Wind Harmer
10.422
970941AG2-585 GEN
Solar/Wind Harmer
3.981
276893AG1-478 C
Solar/Wind Harmer
0.316
276897AD1-100 C
Solar/Wind Harmer
33.357
274674JOLIET 9 ;6U
Adder
11.047
274770LINCOLN ;1U
Adder
4.423
274771LINCOLN ;2U
Adder
4.423
958481AF2-142 GEN
Solar/Wind Harmer
10.644
945421AF1-207 GEN
Solar/Wind Harmer
9.916
957841AF2-078 GEN
Solar/Wind Harmer
4.269
274683WAUKEGAN ;8U
Adder
14.679
274683WAUKEGAN ;8U
Adder
12.373
274696ROCKY RD ;4P
Adder
7.926
274695ROCKY RD ;2P
Adder
7.744
274693ROCKY RD ;1P
Adder
7.668
274697ROCKY RD ;3P
Adder
2.104
958491AF2-143 GEN
Solar/Wind Harmer
10.387
962691AG1-118 GEN
Solar/Wind Harmer
20.541
960751AF2-366 GEN
Solar/Wind Harmer
1.957
276901AD2-066 C O1
Solar/Wind Harmer
2.386
276872AE1-163_GEN1
Solar/Wind Harmer
4.491
276876AE1-163_GEN2
Solar/Wind Harmer
4.491
971341AH1-150 GEN
Solar/Wind Harmer
13.271
971343AH1-151 GEN
Solar/Wind Harmer
13.271
972235AH1-702 GEN1
Adder
1.66
972236AH1-702 GEN2
Adder
1.444
270180AB1-006 GEN1
Solar/Wind Harmer
4.691
24697605MDL-3G C
Solar/Wind Harmer
2.404
24755605MDL-5G
Solar/Wind Harmer
1.572
24697905MDL-4G C
Solar/Wind Harmer
1.497
270181AB1-006 GEN2
Solar/Wind Harmer
0.466
938861AE1-114 GEN
Solar/Wind Harmer
5.296
274764LEE CO EC;5U
Adder
5.988
274765LEE CO EC;6U
Adder
5.988
274762LEE CO EC;3U
Adder
5.974
274763LEE CO EC;4U
Adder
5.918
276158O29GEN2
Solar/Wind Harmer
3.138
276157O29GEN1
Solar/Wind Harmer
2.386
276645AC1-214 GEN1
Solar/Wind Harmer
0.829
942111AE2-223 GEN
Solar/Wind Harmer
4.72
24387305FR-4G C
Solar/Wind Harmer
1.772
274752CRETE EC ;2U
50/50
5.252
274753CRETE EC ;3U
50/50
5.252
274814UNIV PK N;0U
50/50
4.795
274807UNIV PK N;3U
50/50
4.785
274811UNIV PK N;7U
50/50
4.754
24441505OLIV SLR
Solar/Wind Harmer
0.203
964401AG1-302 GEN
Solar/Wind Harmer
13.706
972231SS25-0005
Solar/Wind Harmer
9.61
972181SS23-001
Solar/Wind Harmer
6.006
274803UNIV PARK;6U
Adder
4.513
274676JOLIET 29;8U
Adder
21.743
972259AH1-714 GEN
Adder
14.014
274730ELWOOD EC;6P
Adder
12.015
274734ELWOOD EC;8P
Adder
12.015
274736ELWOOD EC;9P
Adder
12.015
274729ELWOOD EC;1P
Adder
12.013
274826FISK ;BP
Adder
7.93
274887GEN-1.85
Solar/Wind Harmer
3.856
276772AC2-154 GEN
Solar/Wind Harmer
2.02
276843GEN-1.7
Solar/Wind Harmer
0.415
276806AD2-047 C O1
Solar/Wind Harmer
7.742
970707AG2-453 GEN
Solar/Wind Harmer
20.232
939351AE1-166 GEN
Solar/Wind Harmer
4.259
972038AH1-567 GEN2
Adder
0.262
274772LINCOLN ;3U
Adder
4.423
274862TOP CROP ;2U
Solar/Wind Harmer
3.607
943121AE2-341 GEN
Solar/Wind Harmer
10.551
943591AF1-030 GEN
Solar/Wind Harmer
7.034
274682WAUKEGAN ;7U
Adder
12.545
276164X3-005 C
Solar/Wind Harmer
0.482
276868AE1-113 GEN
Solar/Wind Harmer
6.898
274879MINONK ;1U
Solar/Wind Harmer
4.599
276799AD1-013 GEN
Solar/Wind Harmer
1.48
946671AF1-331 GEN
Solar/Wind Harmer
0.28
274855GSG-6 ;RU
Solar/Wind Harmer
2.47
274850MENDOTA H;RU
Solar/Wind Harmer
1.717
276602WESTBROOK C
Solar/Wind Harmer
1.422
959091AF2-200 GEN
Solar/Wind Harmer
13.271
970571AG2-364 GEN
Solar/Wind Harmer
13.048
24690905MDL-1G C
Solar/Wind Harmer
5.236
970781AG2-491 GEN
Solar/Wind Harmer
6.522
274724RIVER EC ;11
Adder
11.531
274857EASY ROAD;U1
Solar/Wind Harmer
3.076
274760LEE CO EC;1U
Adder
5.974
274767LEE CO EC;8U
Adder
5.904
276603SUBLETTE C
Solar/Wind Harmer
0.671
274851PROVIDENC;RU
Solar/Wind Harmer
1.764
274849CRESCENT ;1U
Solar/Wind Harmer
1.145
276782AC1-033 GEN
Solar/Wind Harmer
2.45
274878BISHOP HL;2U
Solar/Wind Harmer
2.072
965931AG1-462 GEN
Solar/Wind Harmer
15.179
971087AG2-675 GEN
Solar/Wind Harmer
2.215
24386205FR-12G C
Solar/Wind Harmer
1.495
274751CRETE EC ;1U
50/50
5.252
274754CRETE EC ;4U
50/50
5.252
274806UNIV PK N;2U
50/50
0.266
274810UNIV PK N;6U
50/50
0.26
274812UNIV PK N;8U
50/50
4.754
970373AG2-245 GEN
Solar/Wind Harmer
43.861
270055AF2-134 C O1
Solar/Wind Harmer
5.46
958381AF2-132 GEN
Solar/Wind Harmer
13.706
964861AG1-349 GEN
Solar/Wind Harmer
11.632
971917AH1-482 GEN
Solar/Wind Harmer
13.42
940581AE2-045 GEN
Solar/Wind Harmer
11.221
971605AH1-302 GEN
Solar/Wind Harmer
9.594
274802UNIV PARK;5U
Adder
4.513
274676JOLIET 29;8U
Adder
22.548
274732ELWOOD EC;7P
Adder
12.015
941551AE2-152 GEN
Solar/Wind Harmer
3.257
274871GR RIDGE ;2U
Solar/Wind Harmer
5.518
274847GR RIDGE ;BU
Solar/Wind Harmer
3.628
274674JOLIET 9 ;6U
Adder
11.047
972207SS24-0001
Solar/Wind Harmer
15.724
274773LINCOLN ;4U
Adder
4.423
274774LINCOLN ;5U
Adder
4.423
274861TOP CROP ;1U
Solar/Wind Harmer
4.32
276694AA1-018 GEN2
Solar/Wind Harmer
4.478
276691AA1-018 GEN1
Solar/Wind Harmer
0.535
274745AC1-111 GEN9
Adder
3.944
274682WAUKEGAN ;7U
Adder
12.545
274828WAUKEGAN ;BP
Adder
7.694
276805AD2-038 GEN
Solar/Wind Harmer
3.551
962781AG1-127 GEN
Solar/Wind Harmer
6.486
276882AE2-255 GEN
Solar/Wind Harmer
2.299
274872LEEDK;1U
Solar/Wind Harmer
5.577
971997AH1-543 GEN
Solar/Wind Harmer
10.546
957471AF2-041 GEN
Solar/Wind Harmer
19.907
959081AF2-199 GEN
Solar/Wind Harmer
6.636
971067AG2-660 GEN
Solar/Wind Harmer
1.543
939401AE1-172 GEN
Solar/Wind Harmer
9.231
274723RIVER EC ;12
Adder
11.863
274822ROCKFORD ;11
Adder
12.983
970819AG2-516 GEN
Solar/Wind Harmer
7.865
970569AG2-363 GEN
Solar/Wind Harmer
19.572
24791305MDL-5G
Solar/Wind Harmer
1.572
274858EASY ROAD;U2
Solar/Wind Harmer
3.076
274761LEE CO EC;2U
Adder
5.974
274766LEE CO EC;7U
Adder
5.904
276708O09 GEN2
Solar/Wind Harmer
2.24
276646AC1-214 GEN2
Solar/Wind Harmer
0.829
274848CAMPGROVE;RU
Solar/Wind Harmer
3.932
276655WTG1_EQ
Solar/Wind Harmer
5.026
276656WTG2_EQ
Solar/Wind Harmer
0.665
939741AE1-205 GEN
Solar/Wind Harmer
11.516
24385905FR-11G C
Solar/Wind Harmer
2.9
24386605FR-22G C
Solar/Wind Harmer
1.5
960681AF2-359 GEN
Solar/Wind Harmer
10.345
958391AF2-133 GEN
Solar/Wind Harmer
12.316
270526AF1-158 GEN
Solar/Wind Harmer
5.937
959141AF2-205 GEN
Solar/Wind Harmer
7.519
972037AH1-567 GEN1
Adder
0.142
972228AH1-698 GEN2
Adder
2.781
972227AH1-698 GEN1
Adder
1.958
274675JOLIET 29;7U
Adder
22.548
274675JOLIET 29;7U
Adder
21.743
274687WILL CNTY;4U
Adder
20.507
274687WILL CNTY;4U
Adder
20.507
274728ELWOOD EC;5P
Adder
12.015
274731ELWOOD EC;2P
Adder
12.013
274733ELWOOD EC;3P
Adder
12.013
274735ELWOOD EC;4P
Adder
12.013
274827FISK ;RP
Adder
5.62
960591AF2-350 GEN
Solar/Wind Harmer
7.237
276893AG1-478 C
Solar/Wind Harmer
0.396
970833AG2-524 GEN
Solar/Wind Harmer
6.265
970833AG2-524 GEN
Solar/Wind Harmer
2.914
274800UNIV PARK;3U
Adder
4.179
274801UNIV PARK;4U
Adder
4.179
274775LINCOLN ;6U
Adder
4.423
274776LINCOLN ;7U
Adder
4.423
274777LINCOLN ;8U
Adder
4.423
274744AC1-111 GEN8
Adder
3.944
274746AC1-111 G10
Adder
3.944
970073AG2-061 GEN
Solar/Wind Harmer
1.61
971411AH1-196 GEN
Solar/Wind Harmer
10.09
971675AH1-338 GEN
Solar/Wind Harmer
12.048
276861AD2-134 GEN
Solar/Wind Harmer
1.194
276863AD2-134 GEN
Solar/Wind Harmer
1.194
276889AE2-281 GEN
Solar/Wind Harmer
1.283
971171AH1-044 GEN
Solar/Wind Harmer
13.271
274823ROCKFORD ;21
Adder
12.889
274856ECOGROVE ;U1
Solar/Wind Harmer
2.203
276611AD2-172 GEN
Solar/Wind Harmer
1.671
276612AE2-035 GEN
Solar/Wind Harmer
1.671
946581AF1-322 GEN
Solar/Wind Harmer
6.674
24691005MDL-2G C
Solar/Wind Harmer
2.412
971681AH1-341 GEN
Solar/Wind Harmer
9.693
926823AC1-168 GEN
Solar/Wind Harmer
2.772
274863CRW1-WTG
Solar/Wind Harmer
3.589
274864CRW2-WTG
Solar/Wind Harmer
3.589
972267AH1-718 GEN
Adder
2.628
276741O09 GEN1
Solar/Wind Harmer
2.24
970169AG2-114 GEN
Solar/Wind Harmer
6.245
274877BISHOP HL;1U
Solar/Wind Harmer
2.072
946321AF1-296 GEN
Solar/Wind Harmer
6.269
276726Z2-087_GEN
Solar/Wind Harmer
4.553
959341AF2-225 GEN
Solar/Wind Harmer
8.637
24386405FR-21G C
Solar/Wind Harmer
1.5
24387005FR-3G C
Solar/Wind Harmer
1.38
990662J1358
External Queue
6.74398136138916
990762J1386
External Queue
5.902415752410889
NYPJM->LTFIMP_NY
CLTF
0.912
WECLTFEXP_WEC->PJM
CLTF
2.521
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.413
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.21
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.175
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.451
MECLTFEXP_MEC->PJM
CLTF
8.251
SIGELTFEXP_SIGE->PJM
CLTF
0.043
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.163
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.375
LAGNLTFEXP_LAGN->PJM
CLTF
3.011
TVALTFEXP_TVA->PJM
CLTF
0.829

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.59 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2140.55
MW Contribution:
9.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274751CRETE EC ;1U
50/50
5.252
274754CRETE EC ;4U
50/50
5.252
274806UNIV PK N;2U
50/50
0.266
274810UNIV PK N;6U
50/50
0.26
274812UNIV PK N;8U
50/50
4.754
970373AG2-245 GEN
Solar/Wind Harmer
43.861
270055AF2-134 C O1
Solar/Wind Harmer
5.46
958381AF2-132 GEN
Solar/Wind Harmer
13.706
964861AG1-349 GEN
Solar/Wind Harmer
11.632
971917AH1-482 GEN
Solar/Wind Harmer
13.42
940581AE2-045 GEN
Solar/Wind Harmer
11.221
971605AH1-302 GEN
Solar/Wind Harmer
9.594
270102X2-052 ST
50/50
5.015
270100X2-052 CT1
50/50
4.634
270101X2-052 CT2
50/50
4.634
274815UNIV PK N;XU
50/50
0.261
274813UNIV PK N;9U
50/50
0.26
274816UNIV PK N;YU
50/50
0.26
274809UNIV PK N;5U
50/50
0.259
274805UNIV PK N;1U
50/50
4.764
274808UNIV PK N;4U
50/50
4.733
965681AG1-436 GEN
Solar/Wind Harmer
34.223
965791AG1-447 GEN
Solar/Wind Harmer
17.509
270535AF1-215 GEN1
Solar/Wind Harmer
8.19
270536AF1-215 GEN2
Solar/Wind Harmer
8.19
274888KELLY CRK;1U
Solar/Wind Harmer
4.271
276776AD2-060 GEN
Solar/Wind Harmer
0.303
958011AF2-095 GEN
Solar/Wind Harmer
10.422
970941AG2-585 GEN
Solar/Wind Harmer
3.981
276893AG1-478 C
Solar/Wind Harmer
0.316
276897AD1-100 C
Solar/Wind Harmer
33.357
274674JOLIET 9 ;6U
Adder
11.047
274770LINCOLN ;1U
Adder
4.423
274771LINCOLN ;2U
Adder
4.423
960681AF2-359 GEN
Solar/Wind Harmer
10.345
958391AF2-133 GEN
Solar/Wind Harmer
12.316
270526AF1-158 GEN
Solar/Wind Harmer
5.937
959141AF2-205 GEN
Solar/Wind Harmer
7.519
972037AH1-567 GEN1
Adder
0.142
972228AH1-698 GEN2
Adder
2.781
972227AH1-698 GEN1
Adder
1.958
274675JOLIET 29;7U
Adder
22.548
274675JOLIET 29;7U
Adder
21.743
274687WILL CNTY;4U
Adder
20.507
274687WILL CNTY;4U
Adder
20.507
274728ELWOOD EC;5P
Adder
12.015
274731ELWOOD EC;2P
Adder
12.013
274733ELWOOD EC;3P
Adder
12.013
274735ELWOOD EC;4P
Adder
12.013
274827FISK ;RP
Adder
5.62
960591AF2-350 GEN
Solar/Wind Harmer
7.237
276893AG1-478 C
Solar/Wind Harmer
0.396
970833AG2-524 GEN
Solar/Wind Harmer
6.265
970833AG2-524 GEN
Solar/Wind Harmer
2.914
274800UNIV PARK;3U
Adder
4.179
274801UNIV PARK;4U
Adder
4.179
274775LINCOLN ;6U
Adder
4.423
274776LINCOLN ;7U
Adder
4.423
274777LINCOLN ;8U
Adder
4.423
274744AC1-111 GEN8
Adder
3.944
274746AC1-111 G10
Adder
3.944
970073AG2-061 GEN
Solar/Wind Harmer
1.61
971411AH1-196 GEN
Solar/Wind Harmer
10.09
971675AH1-338 GEN
Solar/Wind Harmer
12.048
276861AD2-134 GEN
Solar/Wind Harmer
1.194
276863AD2-134 GEN
Solar/Wind Harmer
1.194
276889AE2-281 GEN
Solar/Wind Harmer
1.283
971171AH1-044 GEN
Solar/Wind Harmer
13.271
274823ROCKFORD ;21
Adder
12.889
274856ECOGROVE ;U1
Solar/Wind Harmer
2.203
276611AD2-172 GEN
Solar/Wind Harmer
1.671
276612AE2-035 GEN
Solar/Wind Harmer
1.671
946581AF1-322 GEN
Solar/Wind Harmer
6.674
24691005MDL-2G C
Solar/Wind Harmer
2.412
971681AH1-341 GEN
Solar/Wind Harmer
9.693
926823AC1-168 GEN
Solar/Wind Harmer
2.772
274863CRW1-WTG
Solar/Wind Harmer
3.589
274864CRW2-WTG
Solar/Wind Harmer
3.589
972267AH1-718 GEN
Adder
2.628
276741O09 GEN1
Solar/Wind Harmer
2.24
970169AG2-114 GEN
Solar/Wind Harmer
6.245
274877BISHOP HL;1U
Solar/Wind Harmer
2.072
946321AF1-296 GEN
Solar/Wind Harmer
6.269
276726Z2-087_GEN
Solar/Wind Harmer
4.553
959341AF2-225 GEN
Solar/Wind Harmer
8.637
24386405FR-21G C
Solar/Wind Harmer
1.5
24387005FR-3G C
Solar/Wind Harmer
1.38
274802UNIV PARK;5U
Adder
4.513
274676JOLIET 29;8U
Adder
22.548
274732ELWOOD EC;7P
Adder
12.015
941551AE2-152 GEN
Solar/Wind Harmer
3.257
274871GR RIDGE ;2U
Solar/Wind Harmer
5.518
274847GR RIDGE ;BU
Solar/Wind Harmer
3.628
274674JOLIET 9 ;6U
Adder
11.047
972207SS24-0001
Solar/Wind Harmer
15.724
274773LINCOLN ;4U
Adder
4.423
274774LINCOLN ;5U
Adder
4.423
274861TOP CROP ;1U
Solar/Wind Harmer
4.32
276694AA1-018 GEN2
Solar/Wind Harmer
4.478
276691AA1-018 GEN1
Solar/Wind Harmer
0.535
274745AC1-111 GEN9
Adder
3.944
274682WAUKEGAN ;7U
Adder
12.545
274828WAUKEGAN ;BP
Adder
7.694
276805AD2-038 GEN
Solar/Wind Harmer
3.551
962781AG1-127 GEN
Solar/Wind Harmer
6.486
276882AE2-255 GEN
Solar/Wind Harmer
2.299
274872LEEDK;1U
Solar/Wind Harmer
5.577
971997AH1-543 GEN
Solar/Wind Harmer
10.546
957471AF2-041 GEN
Solar/Wind Harmer
19.907
959081AF2-199 GEN
Solar/Wind Harmer
6.636
971067AG2-660 GEN
Solar/Wind Harmer
1.543
939401AE1-172 GEN
Solar/Wind Harmer
9.231
274723RIVER EC ;12
Adder
11.863
274822ROCKFORD ;11
Adder
12.983
970819AG2-516 GEN
Solar/Wind Harmer
7.865
970569AG2-363 GEN
Solar/Wind Harmer
19.572
24791305MDL-5G
Solar/Wind Harmer
1.572
274858EASY ROAD;U2
Solar/Wind Harmer
3.076
274761LEE CO EC;2U
Adder
5.974
274766LEE CO EC;7U
Adder
5.904
276708O09 GEN2
Solar/Wind Harmer
2.24
276646AC1-214 GEN2
Solar/Wind Harmer
0.829
274848CAMPGROVE;RU
Solar/Wind Harmer
3.932
276655WTG1_EQ
Solar/Wind Harmer
5.026
276656WTG2_EQ
Solar/Wind Harmer
0.665
939741AE1-205 GEN
Solar/Wind Harmer
11.516
24385905FR-11G C
Solar/Wind Harmer
2.9
24386605FR-22G C
Solar/Wind Harmer
1.5
958481AF2-142 GEN
Solar/Wind Harmer
10.644
945421AF1-207 GEN
Solar/Wind Harmer
9.916
957841AF2-078 GEN
Solar/Wind Harmer
4.269
274683WAUKEGAN ;8U
Adder
14.679
274683WAUKEGAN ;8U
Adder
12.373
274696ROCKY RD ;4P
Adder
7.926
274695ROCKY RD ;2P
Adder
7.744
274693ROCKY RD ;1P
Adder
7.668
274697ROCKY RD ;3P
Adder
2.104
958491AF2-143 GEN
Solar/Wind Harmer
10.387
962691AG1-118 GEN
Solar/Wind Harmer
20.541
960751AF2-366 GEN
Solar/Wind Harmer
1.957
276901AD2-066 C O1
Solar/Wind Harmer
2.386
276872AE1-163_GEN1
Solar/Wind Harmer
4.491
276876AE1-163_GEN2
Solar/Wind Harmer
4.491
971341AH1-150 GEN
Solar/Wind Harmer
13.271
971343AH1-151 GEN
Solar/Wind Harmer
13.271
972235AH1-702 GEN1
Adder
1.66
972236AH1-702 GEN2
Adder
1.444
270180AB1-006 GEN1
Solar/Wind Harmer
4.691
24697605MDL-3G C
Solar/Wind Harmer
2.404
24755605MDL-5G
Solar/Wind Harmer
1.572
24697905MDL-4G C
Solar/Wind Harmer
1.497
270181AB1-006 GEN2
Solar/Wind Harmer
0.466
938861AE1-114 GEN
Solar/Wind Harmer
5.296
274764LEE CO EC;5U
Adder
5.988
274765LEE CO EC;6U
Adder
5.988
274762LEE CO EC;3U
Adder
5.974
274763LEE CO EC;4U
Adder
5.918
276158O29GEN2
Solar/Wind Harmer
3.138
276157O29GEN1
Solar/Wind Harmer
2.386
276645AC1-214 GEN1
Solar/Wind Harmer
0.829
942111AE2-223 GEN
Solar/Wind Harmer
4.72
24387305FR-4G C
Solar/Wind Harmer
1.772
274752CRETE EC ;2U
50/50
5.252
274753CRETE EC ;3U
50/50
5.252
274814UNIV PK N;0U
50/50
4.795
274807UNIV PK N;3U
50/50
4.785
274811UNIV PK N;7U
50/50
4.754
24441505OLIV SLR
Solar/Wind Harmer
0.203
964401AG1-302 GEN
Solar/Wind Harmer
13.706
972231SS25-0005
Solar/Wind Harmer
9.61
972181SS23-001
Solar/Wind Harmer
6.006
274803UNIV PARK;6U
Adder
4.513
274676JOLIET 29;8U
Adder
21.743
972259AH1-714 GEN
Adder
14.014
274730ELWOOD EC;6P
Adder
12.015
274734ELWOOD EC;8P
Adder
12.015
274736ELWOOD EC;9P
Adder
12.015
274729ELWOOD EC;1P
Adder
12.013
274826FISK ;BP
Adder
7.93
274887GEN-1.85
Solar/Wind Harmer
3.856
276772AC2-154 GEN
Solar/Wind Harmer
2.02
276843GEN-1.7
Solar/Wind Harmer
0.415
276806AD2-047 C O1
Solar/Wind Harmer
7.742
970707AG2-453 GEN
Solar/Wind Harmer
20.232
939351AE1-166 GEN
Solar/Wind Harmer
4.259
972038AH1-567 GEN2
Adder
0.262
274772LINCOLN ;3U
Adder
4.423
274862TOP CROP ;2U
Solar/Wind Harmer
3.607
943121AE2-341 GEN
Solar/Wind Harmer
10.551
943591AF1-030 GEN
Solar/Wind Harmer
7.034
274682WAUKEGAN ;7U
Adder
12.545
276164X3-005 C
Solar/Wind Harmer
0.482
276868AE1-113 GEN
Solar/Wind Harmer
6.898
274879MINONK ;1U
Solar/Wind Harmer
4.599
276799AD1-013 GEN
Solar/Wind Harmer
1.48
946671AF1-331 GEN
Solar/Wind Harmer
0.28
274855GSG-6 ;RU
Solar/Wind Harmer
2.47
274850MENDOTA H;RU
Solar/Wind Harmer
1.717
276602WESTBROOK C
Solar/Wind Harmer
1.422
959091AF2-200 GEN
Solar/Wind Harmer
13.271
970571AG2-364 GEN
Solar/Wind Harmer
13.048
24690905MDL-1G C
Solar/Wind Harmer
5.236
970781AG2-491 GEN
Solar/Wind Harmer
6.522
274724RIVER EC ;11
Adder
11.531
274857EASY ROAD;U1
Solar/Wind Harmer
3.076
274760LEE CO EC;1U
Adder
5.974
274767LEE CO EC;8U
Adder
5.904
276603SUBLETTE C
Solar/Wind Harmer
0.671
274851PROVIDENC;RU
Solar/Wind Harmer
1.764
274849CRESCENT ;1U
Solar/Wind Harmer
1.145
276782AC1-033 GEN
Solar/Wind Harmer
2.45
274878BISHOP HL;2U
Solar/Wind Harmer
2.072
965931AG1-462 GEN
Solar/Wind Harmer
15.179
971087AG2-675 GEN
Solar/Wind Harmer
2.215
24386205FR-12G C
Solar/Wind Harmer
1.495
990662J1358
External Queue
6.743991374969482
990762J1386
External Queue
5.902422904968262
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.21
NYPJM->LTFIMP_NY
CLTF
0.912
WECLTFEXP_WEC->PJM
CLTF
2.521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.175
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.451
MECLTFEXP_MEC->PJM
CLTF
8.251
SIGELTFEXP_SIGE->PJM
CLTF
0.043
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.413
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.334
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.163
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.375
LAGNLTFEXP_LAGN->PJM
CLTF
3.011
TVALTFEXP_TVA->PJM
CLTF
0.829

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#671_05COOK 345_M2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#671_05COOK 345_M2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.8 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1957.75
MW Contribution:
7.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960681AF2-359 GEN
Solar/Wind Harmer
13.731
958391AF2-133 GEN
Solar/Wind Harmer
16.966
959141AF2-205 GEN
Solar/Wind Harmer
10.41
270526AF1-158 GEN
Solar/Wind Harmer
7.638
946581AF1-322 GEN
Solar/Wind Harmer
9.672
24691005MDL-2G C
Solar/Wind Harmer
3.495
24386405FR-21G C
Solar/Wind Harmer
3.555
24387005FR-3G C
Solar/Wind Harmer
3.269
963841AG1-237 GEN
Solar/Wind Harmer
8.11
972037AH1-567 GEN1
Adder
0.124
274827FISK ;RP
Adder
4.686
274800UNIV PARK;3U
Adder
3.427
274801UNIV PARK;4U
Adder
3.427
972228AH1-698 GEN2
Adder
2.175
972227AH1-698 GEN1
Adder
1.531
274687WILL CNTY;4U
Adder
16.3
274687WILL CNTY;4U
Adder
16.3
960591AF2-350 GEN
Solar/Wind Harmer
5.798
274675JOLIET 29;7U
Adder
17.604
274675JOLIET 29;7U
Adder
16.975
274728ELWOOD EC;5P
Adder
9.372
274731ELWOOD EC;2P
Adder
9.365
274733ELWOOD EC;3P
Adder
9.365
274735ELWOOD EC;4P
Adder
9.365
276893AG1-478 C
Solar/Wind Harmer
0.31
970073AG2-061 GEN
Solar/Wind Harmer
1.293
971771AH1-392 GEN
Solar/Wind Harmer
4.902
276889AE2-281 GEN
Solar/Wind Harmer
1.02
970833AG2-524 GEN
Solar/Wind Harmer
4.519
970833AG2-524 GEN
Solar/Wind Harmer
2.102
274744AC1-111 GEN8
Adder
2.759
274746AC1-111 G10
Adder
2.759
926823AC1-168 GEN
Solar/Wind Harmer
2.102
971411AH1-196 GEN
Solar/Wind Harmer
7.329
274823ROCKFORD ;21
Adder
9.388
270102X2-052 ST
50/50
6.575
270100X2-052 CT1
50/50
6.075
270101X2-052 CT2
50/50
6.075
274815UNIV PK N;XU
50/50
0.256
274813UNIV PK N;9U
50/50
0.256
274816UNIV PK N;YU
50/50
0.256
274809UNIV PK N;5U
50/50
0.254
274805UNIV PK N;1U
50/50
4.675
274808UNIV PK N;4U
50/50
4.644
965681AG1-436 GEN
Solar/Wind Harmer
45.423
965791AG1-447 GEN
Solar/Wind Harmer
23.24
270535AF1-215 GEN1
Solar/Wind Harmer
11.13
270536AF1-215 GEN2
Solar/Wind Harmer
11.13
945421AF1-207 GEN
Solar/Wind Harmer
14.344
957841AF2-078 GEN
Solar/Wind Harmer
6.175
270180AB1-006 GEN1
Solar/Wind Harmer
6.798
24697605MDL-3G C
Solar/Wind Harmer
3.484
24755605MDL-5G
Solar/Wind Harmer
2.279
971171AH1-044 GEN
Solar/Wind Harmer
9.578
274856ECOGROVE ;U1
Solar/Wind Harmer
1.611
276611AD2-172 GEN
Solar/Wind Harmer
1.222
276612AE2-035 GEN
Solar/Wind Harmer
1.222
971675AH1-338 GEN
Solar/Wind Harmer
8.591
276861AD2-134 GEN
Solar/Wind Harmer
0.852
276863AD2-134 GEN
Solar/Wind Harmer
0.852
971681AH1-341 GEN
Solar/Wind Harmer
7.099
274877BISHOP HL;1U
Solar/Wind Harmer
1.593
972267AH1-718 GEN
Adder
1.94
274863CRW1-WTG
Solar/Wind Harmer
0.282
274864CRW2-WTG
Solar/Wind Harmer
0.282
274751CRETE EC ;1U
50/50
5.652
274754CRETE EC ;4U
50/50
5.652
970023AG2-014 GEN
50/50
2.198
970783AG2-492 GEN
50/50
2.198
274806UNIV PK N;2U
50/50
0.261
274810UNIV PK N;6U
50/50
0.255
274812UNIV PK N;8U
50/50
4.665
970373AG2-245 GEN
Solar/Wind Harmer
59.276
270055AF2-134 C O1
Solar/Wind Harmer
7.42
958381AF2-132 GEN
Solar/Wind Harmer
18.778
964861AG1-349 GEN
Solar/Wind Harmer
15.953
971917AH1-482 GEN
Solar/Wind Harmer
18.405
940581AE2-045 GEN
Solar/Wind Harmer
15.654
971605AH1-302 GEN
Solar/Wind Harmer
13.384
24791305MDL-5G
Solar/Wind Harmer
2.279
24385905FR-11G C
Solar/Wind Harmer
6.87
24386605FR-22G C
Solar/Wind Harmer
3.555
274802UNIV PARK;5U
Adder
3.935
963741AG1-226 GEN
Solar/Wind Harmer
29.884
274723RIVER EC ;12
Adder
10.822
274861TOP CROP ;1U
Solar/Wind Harmer
3.518
276694AA1-018 GEN2
Solar/Wind Harmer
3.621
274676JOLIET 29;8U
Adder
17.606
276691AA1-018 GEN1
Solar/Wind Harmer
0.433
274732ELWOOD EC;7P
Adder
9.372
276805AD2-038 GEN
Solar/Wind Harmer
2.852
274674JOLIET 9 ;6U
Adder
8.447
276882AE2-255 GEN
Solar/Wind Harmer
1.792
941551AE2-152 GEN
Solar/Wind Harmer
2.363
274871GR RIDGE ;2U
Solar/Wind Harmer
3.965
274847GR RIDGE ;BU
Solar/Wind Harmer
2.607
970569AG2-363 GEN
Solar/Wind Harmer
15.438
274682WAUKEGAN ;7U
Adder
9.248
274828WAUKEGAN ;BP
Adder
5.673
971997AH1-543 GEN
Solar/Wind Harmer
7.781
274745AC1-111 GEN9
Adder
2.759
274822ROCKFORD ;11
Adder
9.457
962781AG1-127 GEN
Solar/Wind Harmer
4.576
274872LEEDK;1U
Solar/Wind Harmer
3.938
970819AG2-516 GEN
Solar/Wind Harmer
5.748
957471AF2-041 GEN
Solar/Wind Harmer
14.367
959081AF2-199 GEN
Solar/Wind Harmer
4.789
971067AG2-660 GEN
Solar/Wind Harmer
1.114
939401AE1-172 GEN
Solar/Wind Harmer
6.665
276646AC1-214 GEN2
Solar/Wind Harmer
0.638
274858EASY ROAD;U2
Solar/Wind Harmer
2.259
274761LEE CO EC;2U
Adder
4.387
274766LEE CO EC;7U
Adder
4.335
24697905MDL-4G C
Solar/Wind Harmer
2.169
270181AB1-006 GEN2
Solar/Wind Harmer
0.676
24387305FR-4G C
Solar/Wind Harmer
4.199
966841AG1-555 GEN
Solar/Wind Harmer
2.075
970241AG2-163 GEN
Solar/Wind Harmer
16.602
276776AD2-060 GEN
Solar/Wind Harmer
0.243
274888KELLY CRK;1U
Solar/Wind Harmer
3.421
958011AF2-095 GEN
Solar/Wind Harmer
8.349
970941AG2-585 GEN
Solar/Wind Harmer
3.189
958481AF2-142 GEN
Solar/Wind Harmer
8.608
276893AG1-478 C
Solar/Wind Harmer
0.247
958491AF2-143 GEN
Solar/Wind Harmer
8.342
274674JOLIET 9 ;6U
Adder
8.447
276872AE1-163_GEN1
Solar/Wind Harmer
3.569
276876AE1-163_GEN2
Solar/Wind Harmer
3.569
276901AD2-066 C O1
Solar/Wind Harmer
1.837
276897AD1-100 C
Solar/Wind Harmer
24.208
274683WAUKEGAN ;8U
Adder
10.822
274683WAUKEGAN ;8U
Adder
9.122
274696ROCKY RD ;4P
Adder
5.673
274695ROCKY RD ;2P
Adder
5.541
274693ROCKY RD ;1P
Adder
5.487
274697ROCKY RD ;3P
Adder
1.505
962691AG1-118 GEN
Solar/Wind Harmer
14.467
960751AF2-366 GEN
Solar/Wind Harmer
1.381
972236AH1-702 GEN2
Adder
1.052
972235AH1-702 GEN1
Adder
1.21
971341AH1-150 GEN
Solar/Wind Harmer
9.578
971343AH1-151 GEN
Solar/Wind Harmer
9.578
276645AC1-214 GEN1
Solar/Wind Harmer
0.638
938861AE1-114 GEN
Solar/Wind Harmer
3.883
274764LEE CO EC;5U
Adder
4.398
274765LEE CO EC;6U
Adder
4.398
274762LEE CO EC;3U
Adder
4.387
274763LEE CO EC;4U
Adder
4.346
274752CRETE EC ;2U
50/50
5.652
274753CRETE EC ;3U
50/50
5.652
274814UNIV PK N;0U
50/50
4.705
274807UNIV PK N;3U
50/50
4.695
274811UNIV PK N;7U
50/50
4.665
964401AG1-302 GEN
Solar/Wind Harmer
18.778
24441505OLIV SLR
Solar/Wind Harmer
0.263
972231SS25-0005
Solar/Wind Harmer
10.342
972181SS23-001
Solar/Wind Harmer
6.464
24690905MDL-1G C
Solar/Wind Harmer
7.589
970781AG2-491 GEN
Solar/Wind Harmer
9.453
24386205FR-12G C
Solar/Wind Harmer
3.542
274803UNIV PARK;6U
Adder
3.935
274826FISK ;BP
Adder
6.611
274724RIVER EC ;11
Adder
10.454
972038AH1-567 GEN2
Adder
0.214
276164X3-005 C
Solar/Wind Harmer
0.41
274862TOP CROP ;2U
Solar/Wind Harmer
2.937
276772AC2-154 GEN
Solar/Wind Harmer
1.618
276806AD2-047 C O1
Solar/Wind Harmer
6.203
274887GEN-1.85
Solar/Wind Harmer
3.089
276843GEN-1.7
Solar/Wind Harmer
0.332
274676JOLIET 29;8U
Adder
16.977
274730ELWOOD EC;6P
Adder
9.372
274734ELWOOD EC;8P
Adder
9.372
274736ELWOOD EC;9P
Adder
9.372
274729ELWOOD EC;1P
Adder
9.365
276868AE1-113 GEN
Solar/Wind Harmer
5.376
274879MINONK ;1U
Solar/Wind Harmer
3.584
939351AE1-166 GEN
Solar/Wind Harmer
3.091
972259AH1-714 GEN
Adder
9.924
970571AG2-364 GEN
Solar/Wind Harmer
10.292
274682WAUKEGAN ;7U
Adder
9.248
959091AF2-200 GEN
Solar/Wind Harmer
9.578
276799AD1-013 GEN
Solar/Wind Harmer
1.055
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274855GSG-6 ;RU
Solar/Wind Harmer
1.762
274850MENDOTA H;RU
Solar/Wind Harmer
1.225
276602WESTBROOK C
Solar/Wind Harmer
1.014
274851PROVIDENC;RU
Solar/Wind Harmer
1.357
274849CRESCENT ;1U
Solar/Wind Harmer
0.881
943121AE2-341 GEN
Solar/Wind Harmer
7.114
943591AF1-030 GEN
Solar/Wind Harmer
4.743
276782AC1-033 GEN
Solar/Wind Harmer
1.883
274878BISHOP HL;2U
Solar/Wind Harmer
1.593
274857EASY ROAD;U1
Solar/Wind Harmer
2.259
274760LEE CO EC;1U
Adder
4.387
274767LEE CO EC;8U
Adder
4.335
990577J1339
External Queue
12.615906715393066
991247J1684 G
External Queue
10.119549751281738
990582J1340
External Queue
12.615906715393066
990662J1358
External Queue
11.089126586914062
991312J1772
External Queue
15.900864601135254
990762J1386
External Queue
8.400224685668945
991332J1785
External Queue
7.064146041870117
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.091
NYPJM->LTFIMP_NY
CLTF
0.797
LGEELTFEXP_LGEE->PJM
CLTF
0.31
WECLTFEXP_WEC->PJM
CLTF
1.87
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.391
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.459
MECLTFEXP_MEC->PJM
CLTF
6.51
SIGELTFEXP_SIGE->PJM
CLTF
0.074
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.591
LAGNLTFEXP_LAGN->PJM
CLTF
3.03
TVALTFEXP_TVA->PJM
CLTF
1.024

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#6560_05COOK 345_M_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6560_05COOK 345_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.7 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1955.71
MW Contribution:
7.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960681AF2-359 GEN
Solar/Wind Harmer
13.73
958391AF2-133 GEN
Solar/Wind Harmer
16.965
270102X2-052 ST
50/50
6.575
270100X2-052 CT1
50/50
6.075
270101X2-052 CT2
50/50
6.075
274815UNIV PK N;XU
50/50
0.256
274813UNIV PK N;9U
50/50
0.256
274816UNIV PK N;YU
50/50
0.256
274809UNIV PK N;5U
50/50
0.254
274805UNIV PK N;1U
50/50
4.674
274808UNIV PK N;4U
50/50
4.644
965681AG1-436 GEN
Solar/Wind Harmer
45.421
965791AG1-447 GEN
Solar/Wind Harmer
23.239
270535AF1-215 GEN1
Solar/Wind Harmer
11.13
270536AF1-215 GEN2
Solar/Wind Harmer
11.13
945421AF1-207 GEN
Solar/Wind Harmer
14.343
274752CRETE EC ;2U
50/50
5.652
274753CRETE EC ;3U
50/50
5.652
274814UNIV PK N;0U
50/50
4.705
274807UNIV PK N;3U
50/50
4.695
274811UNIV PK N;7U
50/50
4.664
964401AG1-302 GEN
Solar/Wind Harmer
18.777
24441505OLIV SLR
Solar/Wind Harmer
0.263
972231SS25-0005
Solar/Wind Harmer
10.341
972181SS23-001
Solar/Wind Harmer
6.463
24690905MDL-1G C
Solar/Wind Harmer
7.588
970781AG2-491 GEN
Solar/Wind Harmer
9.452
24386205FR-12G C
Solar/Wind Harmer
3.542
274803UNIV PARK;6U
Adder
3.935
274826FISK ;BP
Adder
6.611
274724RIVER EC ;11
Adder
10.453
972038AH1-567 GEN2
Adder
0.214
959141AF2-205 GEN
Solar/Wind Harmer
10.409
270526AF1-158 GEN
Solar/Wind Harmer
7.636
946581AF1-322 GEN
Solar/Wind Harmer
9.671
24691005MDL-2G C
Solar/Wind Harmer
3.495
24386405FR-21G C
Solar/Wind Harmer
3.555
24387005FR-3G C
Solar/Wind Harmer
3.269
963841AG1-237 GEN
Solar/Wind Harmer
8.109
972037AH1-567 GEN1
Adder
0.124
274827FISK ;RP
Adder
4.685
274800UNIV PARK;3U
Adder
3.426
274801UNIV PARK;4U
Adder
3.426
972228AH1-698 GEN2
Adder
2.175
972227AH1-698 GEN1
Adder
1.531
274687WILL CNTY;4U
Adder
16.298
274687WILL CNTY;4U
Adder
16.298
960591AF2-350 GEN
Solar/Wind Harmer
5.797
274675JOLIET 29;7U
Adder
17.602
274675JOLIET 29;7U
Adder
16.973
274728ELWOOD EC;5P
Adder
9.37
274731ELWOOD EC;2P
Adder
9.364
274733ELWOOD EC;3P
Adder
9.364
274735ELWOOD EC;4P
Adder
9.364
276893AG1-478 C
Solar/Wind Harmer
0.31
970073AG2-061 GEN
Solar/Wind Harmer
1.293
971771AH1-392 GEN
Solar/Wind Harmer
4.895
276889AE2-281 GEN
Solar/Wind Harmer
1.02
970833AG2-524 GEN
Solar/Wind Harmer
4.519
970833AG2-524 GEN
Solar/Wind Harmer
2.102
274744AC1-111 GEN8
Adder
2.758
274746AC1-111 G10
Adder
2.758
926823AC1-168 GEN
Solar/Wind Harmer
2.102
971411AH1-196 GEN
Solar/Wind Harmer
7.328
274823ROCKFORD ;21
Adder
9.387
971171AH1-044 GEN
Solar/Wind Harmer
9.577
274856ECOGROVE ;U1
Solar/Wind Harmer
1.611
276611AD2-172 GEN
Solar/Wind Harmer
1.222
276612AE2-035 GEN
Solar/Wind Harmer
1.222
971675AH1-338 GEN
Solar/Wind Harmer
8.59
276861AD2-134 GEN
Solar/Wind Harmer
0.852
276863AD2-134 GEN
Solar/Wind Harmer
0.852
971681AH1-341 GEN
Solar/Wind Harmer
7.098
274877BISHOP HL;1U
Solar/Wind Harmer
1.593
972267AH1-718 GEN
Adder
1.94
274863CRW1-WTG
Solar/Wind Harmer
0.282
274864CRW2-WTG
Solar/Wind Harmer
0.282
274751CRETE EC ;1U
50/50
5.652
274754CRETE EC ;4U
50/50
5.652
970023AG2-014 GEN
50/50
2.198
970783AG2-492 GEN
50/50
2.198
274806UNIV PK N;2U
50/50
0.261
274810UNIV PK N;6U
50/50
0.255
274812UNIV PK N;8U
50/50
4.664
970373AG2-245 GEN
Solar/Wind Harmer
59.273
270055AF2-134 C O1
Solar/Wind Harmer
7.42
958381AF2-132 GEN
Solar/Wind Harmer
18.777
964861AG1-349 GEN
Solar/Wind Harmer
15.952
957841AF2-078 GEN
Solar/Wind Harmer
6.174
270180AB1-006 GEN1
Solar/Wind Harmer
6.798
24697605MDL-3G C
Solar/Wind Harmer
3.484
24755605MDL-5G
Solar/Wind Harmer
2.279
24697905MDL-4G C
Solar/Wind Harmer
2.169
270181AB1-006 GEN2
Solar/Wind Harmer
0.676
24387305FR-4G C
Solar/Wind Harmer
4.198
966841AG1-555 GEN
Solar/Wind Harmer
2.075
970241AG2-163 GEN
Solar/Wind Harmer
16.601
274888KELLY CRK;1U
Solar/Wind Harmer
3.421
276776AD2-060 GEN
Solar/Wind Harmer
0.243
970941AG2-585 GEN
Solar/Wind Harmer
3.189
958011AF2-095 GEN
Solar/Wind Harmer
8.348
958481AF2-142 GEN
Solar/Wind Harmer
8.607
276893AG1-478 C
Solar/Wind Harmer
0.247
958491AF2-143 GEN
Solar/Wind Harmer
8.341
274674JOLIET 9 ;6U
Adder
8.446
276872AE1-163_GEN1
Solar/Wind Harmer
3.569
276876AE1-163_GEN2
Solar/Wind Harmer
3.569
276901AD2-066 C O1
Solar/Wind Harmer
1.837
276897AD1-100 C
Solar/Wind Harmer
24.205
274683WAUKEGAN ;8U
Adder
10.821
274683WAUKEGAN ;8U
Adder
9.121
274696ROCKY RD ;4P
Adder
5.672
274695ROCKY RD ;2P
Adder
5.541
274693ROCKY RD ;1P
Adder
5.486
274697ROCKY RD ;3P
Adder
1.505
962691AG1-118 GEN
Solar/Wind Harmer
14.465
960751AF2-366 GEN
Solar/Wind Harmer
1.38
972235AH1-702 GEN1
Adder
1.21
972236AH1-702 GEN2
Adder
1.052
971341AH1-150 GEN
Solar/Wind Harmer
9.577
971343AH1-151 GEN
Solar/Wind Harmer
9.577
276645AC1-214 GEN1
Solar/Wind Harmer
0.638
938861AE1-114 GEN
Solar/Wind Harmer
3.882
274764LEE CO EC;5U
Adder
4.397
274765LEE CO EC;6U
Adder
4.397
274762LEE CO EC;3U
Adder
4.387
274763LEE CO EC;4U
Adder
4.345
971917AH1-482 GEN
Solar/Wind Harmer
18.404
940581AE2-045 GEN
Solar/Wind Harmer
15.653
971605AH1-302 GEN
Solar/Wind Harmer
13.384
24791305MDL-5G
Solar/Wind Harmer
2.279
24385905FR-11G C
Solar/Wind Harmer
6.869
24386605FR-22G C
Solar/Wind Harmer
3.555
274802UNIV PARK;5U
Adder
3.935
963741AG1-226 GEN
Solar/Wind Harmer
29.881
274723RIVER EC ;12
Adder
10.82
274861TOP CROP ;1U
Solar/Wind Harmer
3.517
276694AA1-018 GEN2
Solar/Wind Harmer
3.621
276691AA1-018 GEN1
Solar/Wind Harmer
0.433
274676JOLIET 29;8U
Adder
17.604
274732ELWOOD EC;7P
Adder
9.37
276805AD2-038 GEN
Solar/Wind Harmer
2.851
274674JOLIET 9 ;6U
Adder
8.446
276882AE2-255 GEN
Solar/Wind Harmer
1.792
941551AE2-152 GEN
Solar/Wind Harmer
2.363
274871GR RIDGE ;2U
Solar/Wind Harmer
3.965
274847GR RIDGE ;BU
Solar/Wind Harmer
2.607
970569AG2-363 GEN
Solar/Wind Harmer
15.436
274682WAUKEGAN ;7U
Adder
9.247
274828WAUKEGAN ;BP
Adder
5.672
971997AH1-543 GEN
Solar/Wind Harmer
7.78
274745AC1-111 GEN9
Adder
2.758
274822ROCKFORD ;11
Adder
9.456
962781AG1-127 GEN
Solar/Wind Harmer
4.575
274872LEEDK;1U
Solar/Wind Harmer
3.938
970819AG2-516 GEN
Solar/Wind Harmer
5.747
957471AF2-041 GEN
Solar/Wind Harmer
14.365
959081AF2-199 GEN
Solar/Wind Harmer
4.788
971067AG2-660 GEN
Solar/Wind Harmer
1.114
939401AE1-172 GEN
Solar/Wind Harmer
6.665
276646AC1-214 GEN2
Solar/Wind Harmer
0.638
274858EASY ROAD;U2
Solar/Wind Harmer
2.259
274761LEE CO EC;2U
Adder
4.387
274766LEE CO EC;7U
Adder
4.335
276164X3-005 C
Solar/Wind Harmer
0.41
274862TOP CROP ;2U
Solar/Wind Harmer
2.937
274887GEN-1.85
Solar/Wind Harmer
3.089
276772AC2-154 GEN
Solar/Wind Harmer
1.618
276843GEN-1.7
Solar/Wind Harmer
0.332
276806AD2-047 C O1
Solar/Wind Harmer
6.202
274676JOLIET 29;8U
Adder
16.975
274730ELWOOD EC;6P
Adder
9.37
274734ELWOOD EC;8P
Adder
9.37
274736ELWOOD EC;9P
Adder
9.37
274729ELWOOD EC;1P
Adder
9.364
276868AE1-113 GEN
Solar/Wind Harmer
5.375
274879MINONK ;1U
Solar/Wind Harmer
3.584
939351AE1-166 GEN
Solar/Wind Harmer
3.09
972259AH1-714 GEN
Adder
9.923
970571AG2-364 GEN
Solar/Wind Harmer
10.291
274682WAUKEGAN ;7U
Adder
9.247
959091AF2-200 GEN
Solar/Wind Harmer
9.577
276799AD1-013 GEN
Solar/Wind Harmer
1.055
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274855GSG-6 ;RU
Solar/Wind Harmer
1.762
274850MENDOTA H;RU
Solar/Wind Harmer
1.225
276602WESTBROOK C
Solar/Wind Harmer
1.014
274851PROVIDENC;RU
Solar/Wind Harmer
1.357
274849CRESCENT ;1U
Solar/Wind Harmer
0.881
943121AE2-341 GEN
Solar/Wind Harmer
7.113
943591AF1-030 GEN
Solar/Wind Harmer
4.742
276782AC1-033 GEN
Solar/Wind Harmer
1.883
274878BISHOP HL;2U
Solar/Wind Harmer
1.593
274857EASY ROAD;U1
Solar/Wind Harmer
2.259
274760LEE CO EC;1U
Adder
4.387
274767LEE CO EC;8U
Adder
4.335
990577J1339
External Queue
12.613812446594238
991247J1684 G
External Queue
10.11737060546875
990582J1340
External Queue
12.613812446594238
990662J1358
External Queue
11.08664321899414
991312J1772
External Queue
15.89951229095459
990762J1386
External Queue
8.399128913879395
991332J1785
External Queue
7.062060356140137
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.091
NYPJM->LTFIMP_NY
CLTF
0.797
LGEELTFEXP_LGEE->PJM
CLTF
0.31
WECLTFEXP_WEC->PJM
CLTF
1.87
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.395
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.458
MECLTFEXP_MEC->PJM
CLTF
6.509
SIGELTFEXP_SIGE->PJM
CLTF
0.073
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.587
LAGNLTFEXP_LAGN->PJM
CLTF
3.029
TVALTFEXP_TVA->PJM
CLTF
1.024

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P7-1_#10997___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10997___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.69 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1955.69
MW Contribution:
7.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960681AF2-359 GEN
Solar/Wind Harmer
13.73
958391AF2-133 GEN
Solar/Wind Harmer
16.965
959141AF2-205 GEN
Solar/Wind Harmer
10.409
270526AF1-158 GEN
Solar/Wind Harmer
7.636
946581AF1-322 GEN
Solar/Wind Harmer
9.671
274751CRETE EC ;1U
50/50
5.652
274754CRETE EC ;4U
50/50
5.652
970023AG2-014 GEN
50/50
2.198
970783AG2-492 GEN
50/50
2.198
274806UNIV PK N;2U
50/50
0.261
274810UNIV PK N;6U
50/50
0.255
274812UNIV PK N;8U
50/50
4.664
970373AG2-245 GEN
Solar/Wind Harmer
59.273
270055AF2-134 C O1
Solar/Wind Harmer
7.42
24691005MDL-2G C
Solar/Wind Harmer
3.495
24386405FR-21G C
Solar/Wind Harmer
3.555
24387005FR-3G C
Solar/Wind Harmer
3.269
963841AG1-237 GEN
Solar/Wind Harmer
8.109
972037AH1-567 GEN1
Adder
0.124
274827FISK ;RP
Adder
4.685
274800UNIV PARK;3U
Adder
3.426
274801UNIV PARK;4U
Adder
3.426
972228AH1-698 GEN2
Adder
2.175
972227AH1-698 GEN1
Adder
1.531
274687WILL CNTY;4U
Adder
16.298
274687WILL CNTY;4U
Adder
16.298
960591AF2-350 GEN
Solar/Wind Harmer
5.797
274675JOLIET 29;7U
Adder
17.602
274675JOLIET 29;7U
Adder
16.973
274728ELWOOD EC;5P
Adder
9.37
274731ELWOOD EC;2P
Adder
9.364
274733ELWOOD EC;3P
Adder
9.364
274735ELWOOD EC;4P
Adder
9.364
276893AG1-478 C
Solar/Wind Harmer
0.31
970073AG2-061 GEN
Solar/Wind Harmer
1.293
971771AH1-392 GEN
Solar/Wind Harmer
4.895
276889AE2-281 GEN
Solar/Wind Harmer
1.02
970833AG2-524 GEN
Solar/Wind Harmer
4.519
970833AG2-524 GEN
Solar/Wind Harmer
2.102
274744AC1-111 GEN8
Adder
2.758
274746AC1-111 G10
Adder
2.758
926823AC1-168 GEN
Solar/Wind Harmer
2.102
971411AH1-196 GEN
Solar/Wind Harmer
7.328
274823ROCKFORD ;21
Adder
9.387
971171AH1-044 GEN
Solar/Wind Harmer
9.577
274856ECOGROVE ;U1
Solar/Wind Harmer
1.611
276611AD2-172 GEN
Solar/Wind Harmer
1.222
276612AE2-035 GEN
Solar/Wind Harmer
1.222
971675AH1-338 GEN
Solar/Wind Harmer
8.59
276861AD2-134 GEN
Solar/Wind Harmer
0.852
276863AD2-134 GEN
Solar/Wind Harmer
0.852
971681AH1-341 GEN
Solar/Wind Harmer
7.098
274877BISHOP HL;1U
Solar/Wind Harmer
1.593
972267AH1-718 GEN
Adder
1.94
274863CRW1-WTG
Solar/Wind Harmer
0.282
274864CRW2-WTG
Solar/Wind Harmer
0.282
270102X2-052 ST
50/50
6.575
270100X2-052 CT1
50/50
6.075
270101X2-052 CT2
50/50
6.075
274815UNIV PK N;XU
50/50
0.256
274813UNIV PK N;9U
50/50
0.256
274816UNIV PK N;YU
50/50
0.256
274809UNIV PK N;5U
50/50
0.254
274805UNIV PK N;1U
50/50
4.674
274808UNIV PK N;4U
50/50
4.644
965681AG1-436 GEN
Solar/Wind Harmer
45.421
965791AG1-447 GEN
Solar/Wind Harmer
23.239
270535AF1-215 GEN1
Solar/Wind Harmer
11.13
270536AF1-215 GEN2
Solar/Wind Harmer
11.13
945421AF1-207 GEN
Solar/Wind Harmer
14.343
957841AF2-078 GEN
Solar/Wind Harmer
6.174
270180AB1-006 GEN1
Solar/Wind Harmer
6.798
24697605MDL-3G C
Solar/Wind Harmer
3.484
24755605MDL-5G
Solar/Wind Harmer
2.279
24697905MDL-4G C
Solar/Wind Harmer
2.169
270181AB1-006 GEN2
Solar/Wind Harmer
0.676
24387305FR-4G C
Solar/Wind Harmer
4.198
966841AG1-555 GEN
Solar/Wind Harmer
2.075
970241AG2-163 GEN
Solar/Wind Harmer
16.601
274888KELLY CRK;1U
Solar/Wind Harmer
3.421
276776AD2-060 GEN
Solar/Wind Harmer
0.243
970941AG2-585 GEN
Solar/Wind Harmer
3.189
958011AF2-095 GEN
Solar/Wind Harmer
8.348
958481AF2-142 GEN
Solar/Wind Harmer
8.607
276893AG1-478 C
Solar/Wind Harmer
0.247
958491AF2-143 GEN
Solar/Wind Harmer
8.341
274674JOLIET 9 ;6U
Adder
8.446
276872AE1-163_GEN1
Solar/Wind Harmer
3.569
276876AE1-163_GEN2
Solar/Wind Harmer
3.569
276901AD2-066 C O1
Solar/Wind Harmer
1.837
276897AD1-100 C
Solar/Wind Harmer
24.205
274683WAUKEGAN ;8U
Adder
10.821
274683WAUKEGAN ;8U
Adder
9.121
274696ROCKY RD ;4P
Adder
5.672
274695ROCKY RD ;2P
Adder
5.541
274693ROCKY RD ;1P
Adder
5.486
274697ROCKY RD ;3P
Adder
1.505
962691AG1-118 GEN
Solar/Wind Harmer
14.465
960751AF2-366 GEN
Solar/Wind Harmer
1.38
972235AH1-702 GEN1
Adder
1.21
972236AH1-702 GEN2
Adder
1.052
971341AH1-150 GEN
Solar/Wind Harmer
9.577
971343AH1-151 GEN
Solar/Wind Harmer
9.577
276645AC1-214 GEN1
Solar/Wind Harmer
0.638
938861AE1-114 GEN
Solar/Wind Harmer
3.882
274764LEE CO EC;5U
Adder
4.397
274765LEE CO EC;6U
Adder
4.397
274762LEE CO EC;3U
Adder
4.387
274763LEE CO EC;4U
Adder
4.345
274752CRETE EC ;2U
50/50
5.652
274753CRETE EC ;3U
50/50
5.652
274814UNIV PK N;0U
50/50
4.705
274807UNIV PK N;3U
50/50
4.695
274811UNIV PK N;7U
50/50
4.664
964401AG1-302 GEN
Solar/Wind Harmer
18.777
24441505OLIV SLR
Solar/Wind Harmer
0.263
972231SS25-0005
Solar/Wind Harmer
10.341
972181SS23-001
Solar/Wind Harmer
6.463
24690905MDL-1G C
Solar/Wind Harmer
7.588
970781AG2-491 GEN
Solar/Wind Harmer
9.452
24386205FR-12G C
Solar/Wind Harmer
3.542
274803UNIV PARK;6U
Adder
3.935
274826FISK ;BP
Adder
6.611
274724RIVER EC ;11
Adder
10.453
972038AH1-567 GEN2
Adder
0.214
276164X3-005 C
Solar/Wind Harmer
0.41
274862TOP CROP ;2U
Solar/Wind Harmer
2.937
274887GEN-1.85
Solar/Wind Harmer
3.089
276772AC2-154 GEN
Solar/Wind Harmer
1.618
276843GEN-1.7
Solar/Wind Harmer
0.332
276806AD2-047 C O1
Solar/Wind Harmer
6.202
274676JOLIET 29;8U
Adder
16.975
274730ELWOOD EC;6P
Adder
9.37
274734ELWOOD EC;8P
Adder
9.37
274736ELWOOD EC;9P
Adder
9.37
274729ELWOOD EC;1P
Adder
9.364
276868AE1-113 GEN
Solar/Wind Harmer
5.375
274879MINONK ;1U
Solar/Wind Harmer
3.584
939351AE1-166 GEN
Solar/Wind Harmer
3.09
972259AH1-714 GEN
Adder
9.923
970571AG2-364 GEN
Solar/Wind Harmer
10.291
274682WAUKEGAN ;7U
Adder
9.247
959091AF2-200 GEN
Solar/Wind Harmer
9.577
276799AD1-013 GEN
Solar/Wind Harmer
1.055
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274855GSG-6 ;RU
Solar/Wind Harmer
1.762
274850MENDOTA H;RU
Solar/Wind Harmer
1.225
276602WESTBROOK C
Solar/Wind Harmer
1.014
274851PROVIDENC;RU
Solar/Wind Harmer
1.357
274849CRESCENT ;1U
Solar/Wind Harmer
0.881
943121AE2-341 GEN
Solar/Wind Harmer
7.113
943591AF1-030 GEN
Solar/Wind Harmer
4.742
276782AC1-033 GEN
Solar/Wind Harmer
1.883
274878BISHOP HL;2U
Solar/Wind Harmer
1.593
274857EASY ROAD;U1
Solar/Wind Harmer
2.259
274760LEE CO EC;1U
Adder
4.387
274767LEE CO EC;8U
Adder
4.335
958381AF2-132 GEN
Solar/Wind Harmer
18.777
964861AG1-349 GEN
Solar/Wind Harmer
15.952
971917AH1-482 GEN
Solar/Wind Harmer
18.404
940581AE2-045 GEN
Solar/Wind Harmer
15.653
971605AH1-302 GEN
Solar/Wind Harmer
13.384
24791305MDL-5G
Solar/Wind Harmer
2.279
24385905FR-11G C
Solar/Wind Harmer
6.869
24386605FR-22G C
Solar/Wind Harmer
3.555
274802UNIV PARK;5U
Adder
3.935
963741AG1-226 GEN
Solar/Wind Harmer
29.881
274723RIVER EC ;12
Adder
10.82
274861TOP CROP ;1U
Solar/Wind Harmer
3.517
276694AA1-018 GEN2
Solar/Wind Harmer
3.621
276691AA1-018 GEN1
Solar/Wind Harmer
0.433
274676JOLIET 29;8U
Adder
17.604
274732ELWOOD EC;7P
Adder
9.37
276805AD2-038 GEN
Solar/Wind Harmer
2.851
274674JOLIET 9 ;6U
Adder
8.446
276882AE2-255 GEN
Solar/Wind Harmer
1.792
941551AE2-152 GEN
Solar/Wind Harmer
2.363
274871GR RIDGE ;2U
Solar/Wind Harmer
3.965
274847GR RIDGE ;BU
Solar/Wind Harmer
2.607
970569AG2-363 GEN
Solar/Wind Harmer
15.436
274682WAUKEGAN ;7U
Adder
9.247
274828WAUKEGAN ;BP
Adder
5.672
971997AH1-543 GEN
Solar/Wind Harmer
7.78
274745AC1-111 GEN9
Adder
2.758
274822ROCKFORD ;11
Adder
9.456
962781AG1-127 GEN
Solar/Wind Harmer
4.575
274872LEEDK;1U
Solar/Wind Harmer
3.938
970819AG2-516 GEN
Solar/Wind Harmer
5.747
957471AF2-041 GEN
Solar/Wind Harmer
14.365
959081AF2-199 GEN
Solar/Wind Harmer
4.788
971067AG2-660 GEN
Solar/Wind Harmer
1.114
939401AE1-172 GEN
Solar/Wind Harmer
6.665
276646AC1-214 GEN2
Solar/Wind Harmer
0.638
274858EASY ROAD;U2
Solar/Wind Harmer
2.259
274761LEE CO EC;2U
Adder
4.387
274766LEE CO EC;7U
Adder
4.335
990577J1339
External Queue
12.613812446594238
991247J1684 G
External Queue
10.11737060546875
990582J1340
External Queue
12.613812446594238
990662J1358
External Queue
11.08664321899414
991312J1772
External Queue
15.89951229095459
990762J1386
External Queue
8.399128913879395
991332J1785
External Queue
7.062060356140137
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.091
NYPJM->LTFIMP_NY
CLTF
0.797
LGEELTFEXP_LGEE->PJM
CLTF
0.31
WECLTFEXP_WEC->PJM
CLTF
1.87
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.395
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.458
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.587
MECLTFEXP_MEC->PJM
CLTF
6.509
SIGELTFEXP_SIGE->PJM
CLTF
0.073
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.221
LAGNLTFEXP_LAGN->PJM
CLTF
3.029
TVALTFEXP_TVA->PJM
CLTF
1.024

Details for 05GAVIN-05MOUNTN 765.0 kV Ckt 1 line l/o AEP_P4_#8075_05MARYSV 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05GAVIN-05MOUNTN 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8075_05MARYSV 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.81 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5567.74
MW Contribution:
15.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
25.323
24721705FLATG2
50/50
83.72
270102X2-052 ST
50/50
1.77
270100X2-052 CT1
50/50
1.635
270101X2-052 CT2
50/50
1.635
970349AG2-230 GEN
Solar/Wind Harmer
17.451
965681AG1-436 GEN
Solar/Wind Harmer
13.797
965791AG1-447 GEN
Solar/Wind Harmer
7.059
274770LINCOLN ;1U
Adder
6.828
274771LINCOLN ;2U
Adder
6.828
274805UNIV PK N;1U
Adder
5.43
274808UNIV PK N;4U
Adder
5.395
274888KELLY CRK;1U
Solar/Wind Harmer
6.373
276776AD2-060 GEN
Solar/Wind Harmer
0.452
958011AF2-095 GEN
Solar/Wind Harmer
15.552
970941AG2-585 GEN
Solar/Wind Harmer
5.94
276897AD1-100 C
Solar/Wind Harmer
50.05
274674JOLIET 9 ;6U
Adder
16.537
276893AG1-478 C
Solar/Wind Harmer
0.47
961051AF2-396 GEN
Solar/Wind Harmer
16.977
961051AF2-396 GEN
Solar/Wind Harmer
7.896
247620Y3-023
Adder
0.491
274696ROCKY RD ;4P
Adder
12.099
274695ROCKY RD ;2P
Adder
11.82
274693ROCKY RD ;1P
Adder
11.704
274697ROCKY RD ;3P
Adder
3.211
274683WAUKEGAN ;8U
Adder
22.325
274683WAUKEGAN ;8U
Adder
18.819
958481AF2-142 GEN
Solar/Wind Harmer
15.887
962691AG1-118 GEN
Solar/Wind Harmer
31.712
270535AF1-215 GEN1
Solar/Wind Harmer
4.788
270536AF1-215 GEN2
Solar/Wind Harmer
4.788
960751AF2-366 GEN
Solar/Wind Harmer
3.028
958491AF2-143 GEN
Solar/Wind Harmer
15.765
276901AD2-066 C O1
Solar/Wind Harmer
3.683
971341AH1-150 GEN
Solar/Wind Harmer
20.86
971343AH1-151 GEN
Solar/Wind Harmer
20.86
276872AE1-163_GEN1
Solar/Wind Harmer
6.982
276876AE1-163_GEN2
Solar/Wind Harmer
6.982
972235AH1-702 GEN1
Adder
2.619
972236AH1-702 GEN2
Adder
2.278
274764LEE CO EC;5U
Adder
9.6
274765LEE CO EC;6U
Adder
9.6
274762LEE CO EC;3U
Adder
9.577
274763LEE CO EC;4U
Adder
9.487
243186AF1-051 GEN
50/50
25.323
24318705GVG2
50/50
23.473
24721805FLATG3
50/50
5.637
24344105CKG2
50/50
8.984
962761AG1-125 GEN
Solar/Wind Harmer
117.776
970149AG2-104 GEN
Solar/Wind Harmer
72.727
970155AG2-107 GEN
Solar/Wind Harmer
51.356
972207SS24-0001
Solar/Wind Harmer
24.277
274773LINCOLN ;4U
Adder
6.828
274774LINCOLN ;5U
Adder
6.828
270216AD2-079_GEN
Solar/Wind Harmer
0.659
274723RIVER EC ;12
Adder
19.477
274751CRETE EC ;1U
Adder
5.299
274754CRETE EC ;4U
Adder
5.299
274812UNIV PK N;8U
Adder
5.418
274802UNIV PARK;5U
Adder
6.296
957891AF2-083 GEN
Solar/Wind Harmer
16.172
941551AE2-152 GEN
Solar/Wind Harmer
4.886
24639705ELKHART HY
Adder
0.165
274676JOLIET 29;8U
Adder
32.988
274674JOLIET 9 ;6U
Adder
16.537
945111AF1-176 GEN
Solar/Wind Harmer
19.155
274732ELWOOD EC;7P
Adder
17.641
274871GR RIDGE ;2U
Solar/Wind Harmer
8.25
274847GR RIDGE ;BU
Solar/Wind Harmer
5.425
274745AC1-111 GEN9
Adder
5.979
970373AG2-245 GEN
Solar/Wind Harmer
22.427
270449AD2-020 GEN
Solar/Wind Harmer
2.991
943021AE2-325 GEN
Solar/Wind Harmer
3.887
274682WAUKEGAN ;7U
Adder
19.056
274828WAUKEGAN ;BP
Adder
11.703
276694AA1-018 GEN2
Solar/Wind Harmer
6.683
276691AA1-018 GEN1
Solar/Wind Harmer
0.799
274861TOP CROP ;1U
Solar/Wind Harmer
6.413
270055AF2-134 C O1
Solar/Wind Harmer
3.192
962781AG1-127 GEN
Solar/Wind Harmer
10.037
274872LEEDK;1U
Solar/Wind Harmer
8.651
939401AE1-172 GEN
Solar/Wind Harmer
14.65
276805AD2-038 GEN
Solar/Wind Harmer
5.39
276882AE2-255 GEN
Solar/Wind Harmer
3.535
971997AH1-543 GEN
Solar/Wind Harmer
16.49
24441205WTRV SLR C
Solar/Wind Harmer
0.141
958381AF2-132 GEN
Solar/Wind Harmer
9.462
957471AF2-041 GEN
Solar/Wind Harmer
31.291
959081AF2-199 GEN
Solar/Wind Harmer
10.43
971067AG2-660 GEN
Solar/Wind Harmer
2.426
964861AG1-349 GEN
Solar/Wind Harmer
8.19
971917AH1-482 GEN
Solar/Wind Harmer
9.449
274822ROCKFORD ;11
Adder
20.427
970819AG2-516 GEN
Solar/Wind Harmer
12.445
274761LEE CO EC;2U
Adder
9.577
274766LEE CO EC;7U
Adder
9.465
970569AG2-363 GEN
Solar/Wind Harmer
20.591
24721605FLATG1
50/50
5.637
960681AF2-359 GEN
Solar/Wind Harmer
4.171
274775LINCOLN ;6U
Adder
6.828
274776LINCOLN ;7U
Adder
6.828
274777LINCOLN ;8U
Adder
6.828
971771AH1-392 GEN
Solar/Wind Harmer
9.865
270526AF1-158 GEN
Solar/Wind Harmer
4.968
270071AF1-092 GEN
Solar/Wind Harmer
16.393
274827FISK ;RP
Adder
8.382
972228AH1-698 GEN2
Adder
4.001
972227AH1-698 GEN1
Adder
2.817
960591AF2-350 GEN
Solar/Wind Harmer
10.8
972037AH1-567 GEN1
Adder
0.198
274800UNIV PARK;3U
Adder
6.294
274801UNIV PARK;4U
Adder
6.294
274687WILL CNTY;4U
Adder
30.059
274687WILL CNTY;4U
Adder
30.059
274675JOLIET 29;7U
Adder
32.988
274675JOLIET 29;7U
Adder
31.81
274728ELWOOD EC;5P
Adder
17.641
274731ELWOOD EC;2P
Adder
17.641
274733ELWOOD EC;3P
Adder
17.641
274735ELWOOD EC;4P
Adder
17.641
970833AG2-524 GEN
Solar/Wind Harmer
9.369
970833AG2-524 GEN
Solar/Wind Harmer
4.358
276893AG1-478 C
Solar/Wind Harmer
0.59
274744AC1-111 GEN8
Adder
5.979
274746AC1-111 G10
Adder
5.979
944161AF1-084 GEN
Solar/Wind Harmer
2.343
970073AG2-061 GEN
Solar/Wind Harmer
2.444
971675AH1-338 GEN
Solar/Wind Harmer
18.853
971411AH1-196 GEN
Solar/Wind Harmer
15.71
276861AD2-134 GEN
Solar/Wind Harmer
1.87
276863AD2-134 GEN
Solar/Wind Harmer
1.87
971171AH1-044 GEN
Solar/Wind Harmer
20.86
970031AG2-029 GEN
Solar/Wind Harmer
26.06
274823ROCKFORD ;21
Adder
20.279
274863CRW1-WTG
Solar/Wind Harmer
5.807
274864CRW2-WTG
Solar/Wind Harmer
5.807
276889AE2-281 GEN
Solar/Wind Harmer
1.995
24729505KEY G4
Adder
6.732
958391AF2-133 GEN
Solar/Wind Harmer
9.403
274856ECOGROVE ;U1
Solar/Wind Harmer
3.494
276611AD2-172 GEN
Solar/Wind Harmer
2.65
276612AE2-035 GEN
Solar/Wind Harmer
2.65
926823AC1-168 GEN
Solar/Wind Harmer
4.437
971681AH1-341 GEN
Solar/Wind Harmer
15.482
972267AH1-718 GEN
Adder
4.26
24318705GVG2
50/50
23.473
24722005FLATG5
50/50
5.637
24721905FLATG4
50/50
102.97
962771AG1-126 GEN
Solar/Wind Harmer
117.776
970153AG2-106 GEN
Solar/Wind Harmer
51.356
971347AH1-153 GEN
Solar/Wind Harmer
5.817
270043AE2-236 GEN
Solar/Wind Harmer
6.077
274772LINCOLN ;3U
Adder
6.828
24441505OLIV SLR
Solar/Wind Harmer
0.146
247643Z2-116 C
Solar/Wind Harmer
0.076
274724RIVER EC ;11
Adder
19.254
970707AG2-453 GEN
Solar/Wind Harmer
30.421
276164X3-005 C
Solar/Wind Harmer
0.762
972231SS25-0005
Solar/Wind Harmer
10.288
972181SS23-001
Solar/Wind Harmer
6.43
274752CRETE EC ;2U
Adder
5.299
274753CRETE EC ;3U
Adder
5.299
972259AH1-714 GEN
Adder
20.646
274814UNIV PK N;0U
Adder
5.466
274807UNIV PK N;3U
Adder
5.454
274811UNIV PK N;7U
Adder
5.418
274826FISK ;BP
Adder
11.827
274887GEN-1.85
Solar/Wind Harmer
5.754
276772AC2-154 GEN
Solar/Wind Harmer
3.014
276843GEN-1.7
Solar/Wind Harmer
0.619
276806AD2-047 C O1
Solar/Wind Harmer
11.553
274803UNIV PARK;6U
Adder
6.296
972038AH1-567 GEN2
Adder
0.394
270505AE1-170 C O1
Solar/Wind Harmer
16.193
939351AE1-166 GEN
Solar/Wind Harmer
6.39
274676JOLIET 29;8U
Adder
31.81
945111AF1-176 GEN
Solar/Wind Harmer
6.071
274729ELWOOD EC;1P
Adder
17.641
274730ELWOOD EC;6P
Adder
17.641
274734ELWOOD EC;8P
Adder
17.641
274736ELWOOD EC;9P
Adder
17.641
943121AE2-341 GEN
Solar/Wind Harmer
16.071
943591AF1-030 GEN
Solar/Wind Harmer
10.714
274682WAUKEGAN ;7U
Adder
19.056
274862TOP CROP ;2U
Solar/Wind Harmer
5.355
944531AF1-118 GEN
Solar/Wind Harmer
36.997
270063AE2-323 C
Solar/Wind Harmer
2.319
276868AE1-113 GEN
Solar/Wind Harmer
10.604
274879MINONK ;1U
Solar/Wind Harmer
7.07
276799AD1-013 GEN
Solar/Wind Harmer
2.315
946671AF1-331 GEN
Solar/Wind Harmer
0.439
274855GSG-6 ;RU
Solar/Wind Harmer
3.866
274850MENDOTA H;RU
Solar/Wind Harmer
2.688
276602WESTBROOK C
Solar/Wind Harmer
2.226
964401AG1-302 GEN
Solar/Wind Harmer
9.462
959091AF2-200 GEN
Solar/Wind Harmer
20.86
274760LEE CO EC;1U
Adder
9.577
274767LEE CO EC;8U
Adder
9.465
970571AG2-364 GEN
Solar/Wind Harmer
13.727
NYPJM->LTFIMP_NY
CLTF
3.437
LGEELTFEXP_LGEE->PJM
CLTF
4.047
WECLTFEXP_WEC->PJM
CLTF
3.968
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.794
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.36
CPLELTFEXP_CPLE->PJM
CLTF
3.107
MECLTFEXP_MEC->PJM
CLTF
15.734
SIGELTFEXP_SIGE->PJM
CLTF
0.372
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
CBM West 2LTFEXP_CBM-W2->PJM
CBM
100.587
LAGNLTFEXP_LAGN->PJM
CLTF
13.978
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.324
TVALTFEXP_TVA->PJM
CLTF
6.618

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.58 %
Rating:3039.0 MVA
Rating Type:B
MVA to Mitigate:3208.68
MW Contribution:
8.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
942601AE2-276 GEN
50/50
8.364
270102X2-052 ST
50/50
1.428
270100X2-052 CT1
50/50
1.319
270101X2-052 CT2
50/50
1.319
971587AH1-292 GEN
Solar/Wind Harmer
7.361
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
970091AG2-072 GEN
50/50
218.725
270407AB1-088 ST1
50/50
2.513
970023AG2-014 GEN
50/50
2.694
970783AG2-492 GEN
50/50
2.694
24344105CKG2
50/50
6.799
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.786
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.763
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
17.105
970373AG2-245 GEN
Solar/Wind Harmer
14.697
274773LINCOLN ;4U
Adder
7.265
274774LINCOLN ;5U
Adder
7.265
274751CRETE EC ;1U
Adder
7.074
274754CRETE EC ;4U
Adder
7.074
274723RIVER EC ;12
Adder
15.309
274812UNIV PK N;8U
Adder
4.274
941551AE2-152 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
4.947
939401AE1-172 GEN
Solar/Wind Harmer
4.39
274732ELWOOD EC;7P
Adder
13.819
274674JOLIET 9 ;6U
Adder
12.932
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
25.765
274745AC1-111 GEN9
Adder
4.638
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.939
274861TOP CROP ;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.081
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3
276882AE2-255 GEN
Solar/Wind Harmer
0.666
274682WAUKEGAN ;7U
Adder
14.697
274828WAUKEGAN ;BP
Adder
9.02
962781AG1-127 GEN
Solar/Wind Harmer
5.386
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
16.84
276621W2-048 GEN
Solar/Wind Harmer
0.279
24697605MDL-3G C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.892
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.216
965681AG1-436 GEN
Solar/Wind Harmer
7.77
965791AG1-447 GEN
Solar/Wind Harmer
5.698
945391AF1-204 GEN
Solar/Wind Harmer
6.551
970349AG2-230 GEN
Solar/Wind Harmer
9.139
274770LINCOLN ;1U
Adder
7.265
274771LINCOLN ;2U
Adder
7.265
274805UNIV PK N;1U
Adder
4.283
274808UNIV PK N;4U
Adder
4.255
276897AD1-100 C
Solar/Wind Harmer
14.818
274888KELLY CRK;1U
Solar/Wind Harmer
0.345
276776AD2-060 GEN
Solar/Wind Harmer
0.632
958011AF2-095 GEN
Solar/Wind Harmer
8.526
970941AG2-585 GEN
Solar/Wind Harmer
3.257
276893AG1-478 C
Solar/Wind Harmer
0.391
274674JOLIET 9 ;6U
Adder
12.932
958481AF2-142 GEN
Solar/Wind Harmer
8.668
942111AE2-223 GEN
Solar/Wind Harmer
1.876
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
8.594
960611AF2-352 GEN
Solar/Wind Harmer
1.91
274695ROCKY RD ;2P
Adder
9.123
274693ROCKY RD ;1P
Adder
9.033
274697ROCKY RD ;3P
Adder
2.478
274696ROCKY RD ;4P
Adder
9.338
274683WAUKEGAN ;8U
Adder
17.208
274683WAUKEGAN ;8U
Adder
14.506
962691AG1-118 GEN
Solar/Wind Harmer
17.022
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.058
276838X2-022 GEN2
Solar/Wind Harmer
0.314
971341AH1-150 GEN
Solar/Wind Harmer
11.115
971343AH1-151 GEN
Solar/Wind Harmer
11.115
276645AC1-214 GEN1
Solar/Wind Harmer
0.217
972235AH1-702 GEN1
Adder
1.993
972236AH1-702 GEN2
Adder
1.733
961051AF2-396 GEN
Solar/Wind Harmer
11.03
961051AF2-396 GEN
Solar/Wind Harmer
7.353
276916AD2-100_GEN
Solar/Wind Harmer
11.472
276911AD2-131_GEN
Solar/Wind Harmer
0.756
938861AE1-114 GEN
Solar/Wind Harmer
3.095
274764LEE CO EC;5U
Adder
7.269
274765LEE CO EC;6U
Adder
7.269
274762LEE CO EC;3U
Adder
7.252
274763LEE CO EC;4U
Adder
7.183
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.873
247620Y3-023
Adder
0.342
970291AG2-192 GEN
Solar/Wind Harmer
0.495
970291AG2-192 GEN
Solar/Wind Harmer
0.229
944231AF1-091 GEN
Solar/Wind Harmer
7.025
971613AH1-306 GEN
Solar/Wind Harmer
1.445
252509AD1-136 GEN
Solar/Wind Helper
0.21
25183208HLCRTG
Solar/Wind Helper
2.03
962581AG1-107 GEN
Solar/Wind Helper
0.905
961491AF2-440 GEN
Solar/Wind Helper
0.037
253349AC2-067 GEN
Solar/Wind Helper
0.213
253400AC2-068 GEN
Solar/Wind Helper
0.086
339236AF1-050_GEN
Solar/Wind Helper
0.404
253415AE1-040 GEN
Solar/Wind Helper
0.484
339231AF1-038_GEN
Solar/Wind Helper
0.394
957891AF2-083 GEN
Solar/Wind Harmer
9.279
957471AF2-041 GEN
Solar/Wind Harmer
16.672
959081AF2-199 GEN
Solar/Wind Harmer
5.557
971067AG2-660 GEN
Solar/Wind Harmer
1.852
274822ROCKFORD ;11
Adder
15.554
276646AC1-214 GEN2
Solar/Wind Harmer
0.217
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.884
945111AF1-176 GEN
Solar/Wind Harmer
9.811
970819AG2-516 GEN
Solar/Wind Harmer
6.595
274848CAMPGROVE;RU
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.094
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.252
274766LEE CO EC;7U
Adder
7.166
276708O09 GEN2
Solar/Wind Harmer
0.191
24639705ELKHART HY
Adder
0.118
965011AG1-365 GEN
Solar/Wind Harmer
3.067
270594AE1-207 GEN
Solar/Wind Harmer
3.372
270032AE2-172
Solar/Wind Harmer
2.007
252510AF1-249 C
Solar/Wind Helper
0.376
339221AD2-048_GEN
Solar/Wind Helper
1.206
943111AE2-339 GEN
Solar/Wind Helper
0.641
339211AE2-254 GEN
Solar/Wind Helper
0.448
253398AE2-221_GEN2
Solar/Wind Helper
1.24
339241AF1-083 GEN
Solar/Wind Helper
0.404
253333AC1-068 GEN
Solar/Wind Helper
0.484
24344205RKG1
50/50
11.252
24344205RKG1
50/50
11.252
24344305RKG2
50/50
11.213
270393AB1-087 CT1
50/50
2.513
270394AB1-087 ST1
50/50
2.513
970539AG2-343 GEN
50/50
9.396
970543AG2-345 GEN
50/50
4.698
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.661
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.267
960681AF2-359 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.265
274776LINCOLN ;7U
Adder
7.265
274777LINCOLN ;8U
Adder
7.265
270526AF1-158 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.144
972227AH1-698 GEN1
Adder
2.214
960591AF2-350 GEN
Solar/Wind Harmer
5.921
972037AH1-567 GEN1
Adder
0.155
274800UNIV PARK;3U
Adder
4.938
274801UNIV PARK;4U
Adder
4.938
274827FISK ;RP
Adder
6.57
274687WILL CNTY;4U
Adder
23.495
274687WILL CNTY;4U
Adder
23.495
274731ELWOOD EC;2P
Adder
13.819
274733ELWOOD EC;3P
Adder
13.819
274735ELWOOD EC;4P
Adder
13.819
274728ELWOOD EC;5P
Adder
13.819
970833AG2-524 GEN
Solar/Wind Harmer
6.449
970833AG2-524 GEN
Solar/Wind Harmer
4.299
274675JOLIET 29;7U
Adder
25.765
274675JOLIET 29;7U
Adder
24.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
5.808
274744AC1-111 GEN8
Adder
4.638
274746AC1-111 G10
Adder
4.638
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.06
971771AH1-392 GEN
Solar/Wind Harmer
5.748
274854TWINGROVE;U2
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.91
276668AB2-070 GEN1
Solar/Wind Harmer
0.222
276848AB2-070 GEN3
Solar/Wind Harmer
0.221
276849AB2-070 GEN2
Solar/Wind Harmer
0.222
926823AC1-168 GEN
Solar/Wind Harmer
0.958
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.182
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276863AD2-134 GEN
Solar/Wind Harmer
0.1
971411AH1-196 GEN
Solar/Wind Harmer
8.382
971171AH1-044 GEN
Solar/Wind Harmer
11.115
274823ROCKFORD ;21
Adder
15.441
274856ECOGROVE ;U1
Solar/Wind Harmer
0.128
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971681AH1-341 GEN
Solar/Wind Harmer
8.802
944221AF1-090 GEN
Solar/Wind Harmer
3.186
276741O09 GEN1
Solar/Wind Harmer
0.191
972267AH1-718 GEN
Adder
3.215
946321AF1-296 GEN
Solar/Wind Harmer
2.925
971549AH1-272 GEN
Solar/Wind Harmer
10.203
270071AF1-092 GEN
Solar/Wind Harmer
8.932
970031AG2-029 GEN
Solar/Wind Harmer
2.434
970289AG2-191 GEN
Solar/Wind Harmer
0.724
959331AF2-224 GEN
Solar/Wind Harmer
2.147
339216AC1-074 GEN
Solar/Wind Helper
1.461
253406AD2-031_GEN
Solar/Wind Helper
0.712
270340AC2-060 GEN
Solar/Wind Helper
1.095
241972AD1-140 GEN
Solar/Wind Helper
2.071
253338AC1-165 GEN
Solar/Wind Helper
0.467
253343AC1-166 GEN
Solar/Wind Helper
0.467
24344305RKG2
50/50
11.018
270406AB1-088 CT1
50/50
2.513
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.082
24386205FR-12G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970193AG2-126 GEN
Solar/Wind Harmer
9.249
971347AH1-153 GEN
Solar/Wind Harmer
3.046
274772LINCOLN ;3U
Adder
7.265
274752CRETE EC ;2U
Adder
7.074
274753CRETE EC ;3U
Adder
7.074
274724RIVER EC ;11
Adder
15.124
274814UNIV PK N;0U
Adder
4.311
274807UNIV PK N;3U
Adder
4.302
274811UNIV PK N;7U
Adder
4.274
939351AE1-166 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
0.154
276843GEN-1.7
Solar/Wind Harmer
0.191
276806AD2-047 C O1
Solar/Wind Harmer
3.355
274803UNIV PARK;6U
Adder
4.947
972038AH1-567 GEN2
Adder
0.309
972259AH1-714 GEN
Adder
16.155
274826FISK ;BP
Adder
9.27
970707AG2-453 GEN
Solar/Wind Harmer
19.288
274729ELWOOD EC;1P
Adder
13.819
274730ELWOOD EC;6P
Adder
13.819
274734ELWOOD EC;8P
Adder
13.819
274736ELWOOD EC;9P
Adder
13.819
274676JOLIET 29;8U
Adder
24.844
943121AE2-341 GEN
Solar/Wind Harmer
9.707
943591AF1-030 GEN
Solar/Wind Harmer
6.455
274862TOP CROP ;2U
Solar/Wind Harmer
0.78
965091AG1-374 GEN
Solar/Wind Harmer
17.188
959611AF2-252 GEN
Solar/Wind Harmer
1.91
276868AE1-113 GEN
Solar/Wind Harmer
1.141
274879MINONK ;1U
Solar/Wind Harmer
0.238
274682WAUKEGAN ;7U
Adder
14.697
971993AH1-541 GEN
Solar/Wind Harmer
2.606
970571AG2-364 GEN
Solar/Wind Harmer
11.227
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.065
270505AE1-170 C O1
Solar/Wind Harmer
5.856
959091AF2-200 GEN
Solar/Wind Harmer
11.115
945111AF1-176 GEN
Solar/Wind Harmer
4.457
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
957381AF2-032 GEN
Solar/Wind Harmer
1.241
942481AE2-261 GEN
Solar/Wind Harmer
16.362
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
7.252
274767LEE CO EC;8U
Adder
7.166
965931AG1-462 GEN
Solar/Wind Harmer
13.235
971087AG2-675 GEN
Solar/Wind Harmer
2.768
270063AE2-323 C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.002
270043AE2-236 GEN
Solar/Wind Harmer
2.578
970289AG2-191 GEN
Solar/Wind Harmer
0.419
965021AG1-366 GEN
Solar/Wind Harmer
1.022
252507AC2-088 GEN
Solar/Wind Helper
1.471
252524AE2-267 GEN
Solar/Wind Helper
0.466
339243AC2-075 GEN1
Solar/Wind Helper
0.336
270186AC1-089 GEN
Solar/Wind Helper
0.822
270367AC2-061_GEN
Solar/Wind Helper
1.691
253394AE2-221_GEN
Solar/Wind Helper
1.24
339206AE1-143 GEN
Solar/Wind Helper
1.206
960071AF2-298 GEN
Solar/Wind Helper
0.355
339255AE2-071 GEN
Solar/Wind Helper
0.153
339250AF1-203 GEN
Solar/Wind Helper
0.118
270518AE2-148 GEN
Solar/Wind Helper
5.631
253325AC1-069 GEN
Solar/Wind Helper
0.484
991312J1772
External Queue
12.36315631866455
955142J992
External Queue
11.419598579406738
990742J1381
External Queue
17.560279846191406
950011AG9-010
External Queue
6.200752258300781
950051AG9-018
External Queue
4.865413665771484
991082J1475 G
External Queue
6.164829730987549
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.737
NYPJM->LTFIMP_NY
CLTF
1.033
WECLTFEXP_WEC->PJM
CLTF
3.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.546
MECLTFEXP_MEC->PJM
CLTF
10.638
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.212
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.591
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.962
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.555
LAGNLTFEXP_LAGN->PJM
CLTF
2.301
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.16 %
Rating:2826.0 MVA
Rating Type:B
MVA to Mitigate:3197.84
MW Contribution:
8.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
942601AE2-276 GEN
50/50
8.364
270102X2-052 ST
50/50
1.428
270100X2-052 CT1
50/50
1.319
270101X2-052 CT2
50/50
1.319
971587AH1-292 GEN
Solar/Wind Harmer
7.361
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.892
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
4.216
965681AG1-436 GEN
Solar/Wind Harmer
7.77
965791AG1-447 GEN
Solar/Wind Harmer
5.698
945391AF1-204 GEN
Solar/Wind Harmer
6.551
970349AG2-230 GEN
Solar/Wind Harmer
9.139
274770LINCOLN ;1U
Adder
7.265
274771LINCOLN ;2U
Adder
7.265
274805UNIV PK N;1U
Adder
4.283
274808UNIV PK N;4U
Adder
4.255
276897AD1-100 C
Solar/Wind Harmer
14.818
274888KELLY CRK;1U
Solar/Wind Harmer
0.345
276776AD2-060 GEN
Solar/Wind Harmer
0.632
958011AF2-095 GEN
Solar/Wind Harmer
8.526
970941AG2-585 GEN
Solar/Wind Harmer
3.257
276893AG1-478 C
Solar/Wind Harmer
0.391
274674JOLIET 9 ;6U
Adder
12.932
958481AF2-142 GEN
Solar/Wind Harmer
8.668
942111AE2-223 GEN
Solar/Wind Harmer
1.876
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
8.594
960611AF2-352 GEN
Solar/Wind Harmer
1.91
274695ROCKY RD ;2P
Adder
9.123
274693ROCKY RD ;1P
Adder
9.033
274697ROCKY RD ;3P
Adder
2.478
274696ROCKY RD ;4P
Adder
9.338
274683WAUKEGAN ;8U
Adder
17.208
274683WAUKEGAN ;8U
Adder
14.506
962691AG1-118 GEN
Solar/Wind Harmer
17.022
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.058
276838X2-022 GEN2
Solar/Wind Harmer
0.314
971341AH1-150 GEN
Solar/Wind Harmer
11.115
971343AH1-151 GEN
Solar/Wind Harmer
11.115
276645AC1-214 GEN1
Solar/Wind Harmer
0.217
972235AH1-702 GEN1
Adder
1.993
972236AH1-702 GEN2
Adder
1.733
961051AF2-396 GEN
Solar/Wind Harmer
11.03
961051AF2-396 GEN
Solar/Wind Harmer
7.353
276916AD2-100_GEN
Solar/Wind Harmer
11.472
276911AD2-131_GEN
Solar/Wind Harmer
0.756
938861AE1-114 GEN
Solar/Wind Harmer
3.095
274764LEE CO EC;5U
Adder
7.269
274765LEE CO EC;6U
Adder
7.269
274762LEE CO EC;3U
Adder
7.252
274763LEE CO EC;4U
Adder
7.183
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.873
247620Y3-023
Adder
0.342
970291AG2-192 GEN
Solar/Wind Harmer
0.495
970291AG2-192 GEN
Solar/Wind Harmer
0.229
944231AF1-091 GEN
Solar/Wind Harmer
7.025
971613AH1-306 GEN
Solar/Wind Harmer
1.445
252509AD1-136 GEN
Solar/Wind Helper
0.21
25183208HLCRTG
Solar/Wind Helper
2.03
962581AG1-107 GEN
Solar/Wind Helper
0.905
961491AF2-440 GEN
Solar/Wind Helper
0.037
253349AC2-067 GEN
Solar/Wind Helper
0.213
253400AC2-068 GEN
Solar/Wind Helper
0.086
339236AF1-050_GEN
Solar/Wind Helper
0.404
253415AE1-040 GEN
Solar/Wind Helper
0.484
24344205RKG1
50/50
11.252
24344205RKG1
50/50
11.252
24344305RKG2
50/50
11.213
270393AB1-087 CT1
50/50
2.513
270394AB1-087 ST1
50/50
2.513
970539AG2-343 GEN
50/50
9.396
970543AG2-345 GEN
50/50
4.698
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.661
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.267
960681AF2-359 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.265
274776LINCOLN ;7U
Adder
7.265
274777LINCOLN ;8U
Adder
7.265
270526AF1-158 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.144
972227AH1-698 GEN1
Adder
2.214
960591AF2-350 GEN
Solar/Wind Harmer
5.921
972037AH1-567 GEN1
Adder
0.155
274800UNIV PARK;3U
Adder
4.938
274801UNIV PARK;4U
Adder
4.938
274827FISK ;RP
Adder
6.57
274687WILL CNTY;4U
Adder
23.495
274687WILL CNTY;4U
Adder
23.495
274731ELWOOD EC;2P
Adder
13.819
274733ELWOOD EC;3P
Adder
13.819
274735ELWOOD EC;4P
Adder
13.819
274728ELWOOD EC;5P
Adder
13.819
970833AG2-524 GEN
Solar/Wind Harmer
6.449
970833AG2-524 GEN
Solar/Wind Harmer
4.299
274675JOLIET 29;7U
Adder
25.765
274675JOLIET 29;7U
Adder
24.845
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
5.808
274744AC1-111 GEN8
Adder
4.638
274746AC1-111 G10
Adder
4.638
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.06
971771AH1-392 GEN
Solar/Wind Harmer
5.748
274854TWINGROVE;U2
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.91
276668AB2-070 GEN1
Solar/Wind Harmer
0.222
276848AB2-070 GEN3
Solar/Wind Harmer
0.221
276849AB2-070 GEN2
Solar/Wind Harmer
0.222
926823AC1-168 GEN
Solar/Wind Harmer
0.958
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
2.182
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276863AD2-134 GEN
Solar/Wind Harmer
0.1
971411AH1-196 GEN
Solar/Wind Harmer
8.382
971171AH1-044 GEN
Solar/Wind Harmer
11.115
274823ROCKFORD ;21
Adder
15.441
274856ECOGROVE ;U1
Solar/Wind Harmer
0.128
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971681AH1-341 GEN
Solar/Wind Harmer
8.802
944221AF1-090 GEN
Solar/Wind Harmer
3.186
276741O09 GEN1
Solar/Wind Harmer
0.191
972267AH1-718 GEN
Adder
3.215
946321AF1-296 GEN
Solar/Wind Harmer
2.925
971549AH1-272 GEN
Solar/Wind Harmer
10.203
270071AF1-092 GEN
Solar/Wind Harmer
8.932
970031AG2-029 GEN
Solar/Wind Harmer
2.434
970289AG2-191 GEN
Solar/Wind Harmer
0.724
959331AF2-224 GEN
Solar/Wind Harmer
2.147
339216AC1-074 GEN
Solar/Wind Helper
1.461
253406AD2-031_GEN
Solar/Wind Helper
0.712
270340AC2-060 GEN
Solar/Wind Helper
1.095
241972AD1-140 GEN
Solar/Wind Helper
2.071
253338AC1-165 GEN
Solar/Wind Helper
0.467
253343AC1-166 GEN
Solar/Wind Helper
0.467
339231AF1-038_GEN
Solar/Wind Helper
0.394
970091AG2-072 GEN
50/50
218.725
270407AB1-088 ST1
50/50
2.513
970023AG2-014 GEN
50/50
2.694
970783AG2-492 GEN
50/50
2.694
24344105CKG2
50/50
6.799
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.786
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.763
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
17.105
970373AG2-245 GEN
Solar/Wind Harmer
14.697
274773LINCOLN ;4U
Adder
7.265
274774LINCOLN ;5U
Adder
7.265
274751CRETE EC ;1U
Adder
7.074
274754CRETE EC ;4U
Adder
7.074
274723RIVER EC ;12
Adder
15.309
274812UNIV PK N;8U
Adder
4.274
941551AE2-152 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
4.947
939401AE1-172 GEN
Solar/Wind Harmer
4.39
274732ELWOOD EC;7P
Adder
13.819
274674JOLIET 9 ;6U
Adder
12.932
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
25.765
274745AC1-111 GEN9
Adder
4.638
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.939
274861TOP CROP ;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.081
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3
276882AE2-255 GEN
Solar/Wind Harmer
0.666
274682WAUKEGAN ;7U
Adder
14.697
274828WAUKEGAN ;BP
Adder
9.02
962781AG1-127 GEN
Solar/Wind Harmer
5.386
274872LEEDK;1U
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
16.84
276621W2-048 GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
9.279
957471AF2-041 GEN
Solar/Wind Harmer
16.672
959081AF2-199 GEN
Solar/Wind Harmer
5.557
971067AG2-660 GEN
Solar/Wind Harmer
1.852
274822ROCKFORD ;11
Adder
15.554
276646AC1-214 GEN2
Solar/Wind Harmer
0.217
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.884
945111AF1-176 GEN
Solar/Wind Harmer
9.811
970819AG2-516 GEN
Solar/Wind Harmer
6.595
274848CAMPGROVE;RU
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.094
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
7.252
274766LEE CO EC;7U
Adder
7.166
276708O09 GEN2
Solar/Wind Harmer
0.191
24639705ELKHART HY
Adder
0.118
965011AG1-365 GEN
Solar/Wind Harmer
3.067
270594AE1-207 GEN
Solar/Wind Harmer
3.372
270032AE2-172
Solar/Wind Harmer
2.007
252510AF1-249 C
Solar/Wind Helper
0.376
339221AD2-048_GEN
Solar/Wind Helper
1.206
943111AE2-339 GEN
Solar/Wind Helper
0.641
339211AE2-254 GEN
Solar/Wind Helper
0.448
253398AE2-221_GEN2
Solar/Wind Helper
1.24
339241AF1-083 GEN
Solar/Wind Helper
0.404
253333AC1-068 GEN
Solar/Wind Helper
0.484
24344305RKG2
50/50
11.018
270406AB1-088 CT1
50/50
2.513
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.082
24386205FR-12G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970193AG2-126 GEN
Solar/Wind Harmer
9.249
971347AH1-153 GEN
Solar/Wind Harmer
3.046
274772LINCOLN ;3U
Adder
7.265
274752CRETE EC ;2U
Adder
7.074
274753CRETE EC ;3U
Adder
7.074
274724RIVER EC ;11
Adder
15.124
274814UNIV PK N;0U
Adder
4.311
274807UNIV PK N;3U
Adder
4.302
274811UNIV PK N;7U
Adder
4.274
939351AE1-166 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
0.154
276843GEN-1.7
Solar/Wind Harmer
0.191
276806AD2-047 C O1
Solar/Wind Harmer
3.355
274803UNIV PARK;6U
Adder
4.947
972038AH1-567 GEN2
Adder
0.309
972259AH1-714 GEN
Adder
16.155
274826FISK ;BP
Adder
9.27
970707AG2-453 GEN
Solar/Wind Harmer
19.288
274729ELWOOD EC;1P
Adder
13.819
274730ELWOOD EC;6P
Adder
13.819
274734ELWOOD EC;8P
Adder
13.819
274736ELWOOD EC;9P
Adder
13.819
274676JOLIET 29;8U
Adder
24.844
943121AE2-341 GEN
Solar/Wind Harmer
9.707
943591AF1-030 GEN
Solar/Wind Harmer
6.455
274862TOP CROP ;2U
Solar/Wind Harmer
0.78
965091AG1-374 GEN
Solar/Wind Harmer
17.188
959611AF2-252 GEN
Solar/Wind Harmer
1.91
276868AE1-113 GEN
Solar/Wind Harmer
1.141
274879MINONK ;1U
Solar/Wind Harmer
0.238
274682WAUKEGAN ;7U
Adder
14.697
971993AH1-541 GEN
Solar/Wind Harmer
2.606
970571AG2-364 GEN
Solar/Wind Harmer
11.227
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.065
270505AE1-170 C O1
Solar/Wind Harmer
5.856
959091AF2-200 GEN
Solar/Wind Harmer
11.115
945111AF1-176 GEN
Solar/Wind Harmer
4.457
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
957381AF2-032 GEN
Solar/Wind Harmer
1.241
942481AE2-261 GEN
Solar/Wind Harmer
16.362
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
7.252
274767LEE CO EC;8U
Adder
7.166
965931AG1-462 GEN
Solar/Wind Harmer
13.235
971087AG2-675 GEN
Solar/Wind Harmer
2.768
270063AE2-323 C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.002
270043AE2-236 GEN
Solar/Wind Harmer
2.578
970289AG2-191 GEN
Solar/Wind Harmer
0.419
965021AG1-366 GEN
Solar/Wind Harmer
1.022
252507AC2-088 GEN
Solar/Wind Helper
1.471
252524AE2-267 GEN
Solar/Wind Helper
0.466
339243AC2-075 GEN1
Solar/Wind Helper
0.336
270186AC1-089 GEN
Solar/Wind Helper
0.822
270367AC2-061_GEN
Solar/Wind Helper
1.691
253394AE2-221_GEN
Solar/Wind Helper
1.24
339206AE1-143 GEN
Solar/Wind Helper
1.206
960071AF2-298 GEN
Solar/Wind Helper
0.355
339255AE2-071 GEN
Solar/Wind Helper
0.153
339250AF1-203 GEN
Solar/Wind Helper
0.118
270518AE2-148 GEN
Solar/Wind Helper
5.631
253325AC1-069 GEN
Solar/Wind Helper
0.484
991312J1772
External Queue
12.36315631866455
955142J992
External Queue
11.419598579406738
990742J1381
External Queue
17.560279846191406
950011AG9-010
External Queue
6.200752258300781
950051AG9-018
External Queue
4.865413665771484
991082J1475 G
External Queue
6.164829730987549
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.737
NYPJM->LTFIMP_NY
CLTF
1.033
WECLTFEXP_WEC->PJM
CLTF
3.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.546
MECLTFEXP_MEC->PJM
CLTF
10.638
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.212
AG2-052LTFEXP_AG2-052->PJM
LTF
0.201
AH1-155LTFEXP_AH1-155->PJM
LTF
0.302
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.591
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.962
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.555
LAGNLTFEXP_LAGN->PJM
CLTF
2.301
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.91 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2513.45
MW Contribution:
7.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.371
24729305KEY G2
50/50
0.365
24729205KEY G1
50/50
0.363
247620Y3-023
50/50
0.463
960851AF2-376 GEN
50/50
2.077
24643105BUCHANAN
50/50
0.01
246937BC-WTG2
Solar/Wind Harmer
1.154
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.833
944231AF1-091 GEN
Solar/Wind Harmer
16.013
944541AF1-119 GEN
Solar/Wind Harmer
0.423
960971AF2-388 GEN
Solar/Wind Harmer
3.72
970349AG2-230 GEN
Solar/Wind Harmer
8.699
961051AF2-396 GEN
Solar/Wind Harmer
11.565
961051AF2-396 GEN
Solar/Wind Harmer
7.71
270031AE2-169
Solar/Wind Harmer
3.074
270599AE1-208 GEN
Solar/Wind Harmer
5.123
965681AG1-436 GEN
Solar/Wind Harmer
6.895
965791AG1-447 GEN
Solar/Wind Harmer
5.056
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.406
247621Y3-024
Adder
0.181
274805UNIV PK N;1U
Adder
3.762
274808UNIV PK N;4U
Adder
3.737
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.299
274771LINCOLN ;2U
Adder
6.299
274888KELLY CRK;1U
Solar/Wind Harmer
0.3
276776AD2-060 GEN
Solar/Wind Harmer
0.55
958011AF2-095 GEN
Solar/Wind Harmer
7.42
970941AG2-585 GEN
Solar/Wind Harmer
2.834
276897AD1-100 C
Solar/Wind Harmer
12.751
274674JOLIET 9 ;6U
Adder
11.228
276893AG1-478 C
Solar/Wind Harmer
0.339
970291AG2-192 GEN
Solar/Wind Harmer
0.659
970291AG2-192 GEN
Solar/Wind Harmer
0.304
971613AH1-306 GEN
Solar/Wind Harmer
2.416
958481AF2-142 GEN
Solar/Wind Harmer
7.489
274696ROCKY RD ;4P
Adder
8.116
274695ROCKY RD ;2P
Adder
7.929
24727005RPMNG1
50/50
3.31
960861AF2-377 GEN
50/50
2.388
970521AG2-332 GEN
50/50
10.816
24639705ELKHART HY
50/50
0.149
270143AC1-141 CT2_
50/50
2.011
246936BC-WTG1
Solar/Wind Harmer
1.154
270489AE1-102 GEN1
Solar/Wind Harmer
3.723
965421AG1-410 GEN
Solar/Wind Harmer
81.634
965011AG1-365 GEN
Solar/Wind Harmer
13.768
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.86
958861AF2-177 GEN
Solar/Wind Harmer
2.67
945111AF1-176 GEN
Solar/Wind Harmer
10.586
957891AF2-083 GEN
Solar/Wind Harmer
9.711
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.972
970373AG2-245 GEN
Solar/Wind Harmer
11.129
274751CRETE EC ;1U
Adder
6.248
274754CRETE EC ;4U
Adder
6.248
274723RIVER EC ;12
Adder
13.542
274812UNIV PK N;8U
Adder
3.753
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.299
274774LINCOLN ;5U
Adder
6.299
274802UNIV PARK;5U
Adder
4.324
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.679
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.423
274674JOLIET 9 ;6U
Adder
11.228
274732ELWOOD EC;7P
Adder
11.982
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.296
270594AE1-207 GEN
Solar/Wind Harmer
5.638
270032AE2-172
Solar/Wind Harmer
3.356
270005AE1-210 C O1
Solar/Wind Harmer
1.089
274745AC1-111 GEN9
Adder
4.025
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.811
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.769
274682WAUKEGAN ;7U
Adder
12.793
274828WAUKEGAN ;BP
Adder
7.853
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.68
939401AE1-172 GEN
Solar/Wind Harmer
3.677
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971997AH1-543 GEN
Solar/Wind Harmer
2.561
957471AF2-041 GEN
Solar/Wind Harmer
14.489
959081AF2-199 GEN
Solar/Wind Harmer
4.83
971067AG2-660 GEN
Solar/Wind Harmer
1.61
24727205RPMNG3
50/50
3.291
24729505KEY G4
50/50
6.793
24653605MOTTVILLE
50/50
0.003
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.776
957201AF2-014 GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
3.627
959331AF2-224 GEN
Solar/Wind Harmer
9.638
963791AG1-232 GEN
Solar/Wind Harmer
11.962
970031AG2-029 GEN
Solar/Wind Harmer
4.557
965041AG1-368 GEN
Solar/Wind Harmer
8.389
270071AF1-092 GEN
Solar/Wind Harmer
14.462
247521TR3_G114
Solar/Wind Harmer
0.259
965051AG1-369 GEN
Solar/Wind Harmer
3.575
971771AH1-392 GEN
Solar/Wind Harmer
5.853
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.913
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.109
274775LINCOLN ;6U
Adder
6.299
274776LINCOLN ;7U
Adder
6.299
274777LINCOLN ;8U
Adder
6.299
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.748
274800UNIV PARK;3U
Adder
4.311
274801UNIV PARK;4U
Adder
4.311
960591AF2-350 GEN
Solar/Wind Harmer
5.152
972228AH1-698 GEN2
Adder
2.728
972227AH1-698 GEN1
Adder
1.92
274687WILL CNTY;4U
Adder
20.467
274687WILL CNTY;4U
Adder
20.467
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.423
274675JOLIET 29;7U
Adder
21.622
274728ELWOOD EC;5P
Adder
11.982
274731ELWOOD EC;2P
Adder
11.982
274733ELWOOD EC;3P
Adder
11.982
274735ELWOOD EC;4P
Adder
11.982
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.964
970833AG2-524 GEN
Solar/Wind Harmer
5.568
970833AG2-524 GEN
Solar/Wind Harmer
3.712
971611AH1-305 GEN
Solar/Wind Harmer
2.999
274744AC1-111 GEN8
Adder
4.025
274746AC1-111 G10
Adder
4.025
970073AG2-061 GEN
Solar/Wind Harmer
1.643
247536S-71 GEN
Solar/Wind Harmer
0.197
971411AH1-196 GEN
Solar/Wind Harmer
7.295
971675AH1-338 GEN
Solar/Wind Harmer
1.895
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276863AD2-134 GEN
Solar/Wind Harmer
0.087
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.659
274823ROCKFORD ;21
Adder
13.445
274856ECOGROVE ;U1
Solar/Wind Harmer
0.112
926823AC1-168 GEN
Solar/Wind Harmer
0.812
970169AG2-114 GEN
Solar/Wind Harmer
4.769
971681AH1-341 GEN
Solar/Wind Harmer
7.649
274693ROCKY RD ;1P
Adder
7.851
274697ROCKY RD ;3P
Adder
2.154
274683WAUKEGAN ;8U
Adder
14.981
274683WAUKEGAN ;8U
Adder
12.628
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
7.394
962691AG1-118 GEN
Solar/Wind Harmer
14.789
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.659
971343AH1-151 GEN
Solar/Wind Harmer
9.659
972235AH1-702 GEN1
Adder
1.735
972236AH1-702 GEN2
Adder
1.509
938861AE1-114 GEN
Solar/Wind Harmer
2.691
274764LEE CO EC;5U
Adder
6.323
274765LEE CO EC;6U
Adder
6.323
274762LEE CO EC;3U
Adder
6.308
274763LEE CO EC;4U
Adder
6.249
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.754
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.527
942111AE2-223 GEN
Solar/Wind Harmer
1.496
960611AF2-352 GEN
Solar/Wind Harmer
1.507
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.427
970885AG2-551 GEN
Solar/Wind Harmer
1.476
970241AG2-163 GEN
Solar/Wind Harmer
2.55
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.043
276838X2-022 GEN2
Solar/Wind Harmer
0.236
276916AD2-100_GEN
Solar/Wind Harmer
8.418
276911AD2-131_GEN
Solar/Wind Harmer
0.555
945391AF1-204 GEN
Solar/Wind Harmer
4.161
970623AG2-406 GEN
Solar/Wind Harmer
0.646
971587AH1-292 GEN
Solar/Wind Harmer
2.428
247607V1-011 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
3.77
247522W1-056 GEN
Solar/Wind Helper
1.187
253378AE2-206_GEN
Solar/Wind Helper
0.725
270349AD2-093_GEN
Solar/Wind Helper
0.869
270471AD2-092_GEN
Solar/Wind Helper
0.869
241960AC2-195 GEN
Solar/Wind Helper
0.709
274822ROCKFORD ;11
Adder
13.543
276903AD2-071 C
Solar/Wind Harmer
5.365
970819AG2-516 GEN
Solar/Wind Harmer
5.744
970569AG2-363 GEN
Solar/Wind Harmer
14.349
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.308
274766LEE CO EC;7U
Adder
6.234
276708O09 GEN2
Solar/Wind Harmer
0.165
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.443
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.247
963741AG1-226 GEN
Solar/Wind Harmer
10.345
276621W2-048 GEN
Solar/Wind Harmer
0.21
965911AG1-460 GEN
Solar/Wind Harmer
0.809
24728605AND G2
Adder
2.069
970773AG2-487 GEN
Solar/Wind Harmer
0.62
270317AD1-130_GEN
Solar/Wind Helper
4.168
270485AE1-090_GEN
Solar/Wind Helper
0.328
270391AF1-285 GEN3
Solar/Wind Helper
0.597
270578AF1-285 GEN2
Solar/Wind Helper
0.597
270286AF1-227 GEN2
Solar/Wind Helper
0.701
960841AF2-375 GEN
Solar/Wind Helper
1.192
971549AH1-272 GEN
Solar/Wind Harmer
9.785
972267AH1-718 GEN
Adder
2.795
276741O09 GEN1
Solar/Wind Harmer
0.165
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.155
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.832
946321AF1-296 GEN
Solar/Wind Harmer
2.546
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.952
270543AE2-219 C
Solar/Wind Harmer
3.099
276668AB2-070 GEN1
Solar/Wind Harmer
0.168
276848AB2-070 GEN3
Solar/Wind Harmer
0.167
276849AB2-070 GEN2
Solar/Wind Harmer
0.168
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.847
944221AF1-090 GEN
Solar/Wind Harmer
2.28
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
0.881
270224U2-072_GEN2
Solar/Wind Helper
0.881
270227U2-072_GEN3
Solar/Wind Helper
0.881
270228U2-072_GEN4
Solar/Wind Helper
0.881
270231U2-072_GEN5
Solar/Wind Helper
0.881
966831AG1-554 GEN
Solar/Wind Helper
0.889
270499AE1-146 GEN
Solar/Wind Helper
1.989
945641AF1-229 GEN
Solar/Wind Helper
0.952
965431AG1-411 GEN
50/50
45.352
24727105RPMNG2
50/50
3.311
970583AG2-370 GEN
50/50
2.796
270142AC1-141 CT1_
50/50
2.011
24642205MAYFLWER
50/50
0.03
246938BC-WTG3
Solar/Wind Harmer
1.031
270491AE1-102 GEN2
Solar/Wind Harmer
3.723
965021AG1-366 GEN
Solar/Wind Harmer
4.589
270043AE2-236 GEN
Solar/Wind Harmer
5.206
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.738
24695305TIMB G C
Solar/Wind Harmer
0.527
945111AF1-176 GEN
Solar/Wind Harmer
4.809
971347AH1-153 GEN
Solar/Wind Harmer
2.9
270505AE1-170 C O1
Solar/Wind Harmer
6.075
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.264
274752CRETE EC ;2U
Adder
6.248
274753CRETE EC ;3U
Adder
6.248
274724RIVER EC ;11
Adder
13.377
274814UNIV PK N;0U
Adder
3.786
274807UNIV PK N;3U
Adder
3.778
274811UNIV PK N;7U
Adder
3.753
274772LINCOLN ;3U
Adder
6.299
274803UNIV PARK;6U
Adder
4.324
274826FISK ;BP
Adder
8.11
972038AH1-567 GEN2
Adder
0.27
274887GEN-1.85
Solar/Wind Harmer
0.134
276843GEN-1.7
Solar/Wind Harmer
0.167
276806AD2-047 C O1
Solar/Wind Harmer
2.92
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.004
970707AG2-453 GEN
Solar/Wind Harmer
16.726
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.622
274729ELWOOD EC;1P
Adder
11.982
274730ELWOOD EC;6P
Adder
11.982
274734ELWOOD EC;8P
Adder
11.982
274736ELWOOD EC;9P
Adder
11.982
970289AG2-191 GEN
Solar/Wind Harmer
0.558
946031AF1-268 GEN
Solar/Wind Harmer
4.787
943121AE2-341 GEN
Solar/Wind Harmer
8.427
943591AF1-030 GEN
Solar/Wind Harmer
5.604
270004AE1-209 GEN
Solar/Wind Harmer
1.089
274862TOP CROP ;2U
Solar/Wind Harmer
0.674
970825AG2-519 GEN
Solar/Wind Harmer
3.754
274682WAUKEGAN ;7U
Adder
12.793
276868AE1-113 GEN
Solar/Wind Harmer
0.98
274879MINONK ;1U
Solar/Wind Harmer
0.204
946671AF1-331 GEN
Solar/Wind Harmer
0.519
274855GSG-6 ;RU
Solar/Wind Harmer
0.177
274850MENDOTA H;RU
Solar/Wind Harmer
0.056
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.841
959091AF2-200 GEN
Solar/Wind Harmer
9.659
970571AG2-364 GEN
Solar/Wind Harmer
9.566
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.308
274767LEE CO EC;8U
Adder
6.234
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.155
965091AG1-374 GEN
Solar/Wind Harmer
13.563
965931AG1-462 GEN
Solar/Wind Harmer
11.528
971087AG2-675 GEN
Solar/Wind Harmer
2.411
959611AF2-252 GEN
Solar/Wind Harmer
1.507
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.973
957381AF2-032 GEN
Solar/Wind Harmer
0.92
942481AE2-261 GEN
Solar/Wind Harmer
12.093
970193AG2-126 GEN
Solar/Wind Harmer
5.875
24728705AND G3
Adder
4.327
24728505AND G1
Adder
2.069
942871AE2-306 GEN
Solar/Wind Helper
0.448
270284AF1-227 GEN1
Solar/Wind Helper
1.912
270287AF1-227 GEN3
Solar/Wind Helper
0.701
276820AF1-078_GEN
Solar/Wind Helper
0.338
270541AE2-072 C
Solar/Wind Helper
0.958
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
NYPJM->LTFIMP_NY
CLTF
1.314
LGEELTFEXP_LGEE->PJM
CLTF
1.767
WECLTFEXP_WEC->PJM
CLTF
2.626
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.114
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.636
MECLTFEXP_MEC->PJM
CLTF
9.653
SIGELTFEXP_SIGE->PJM
CLTF
0.197
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.094
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.784
LAGNLTFEXP_LAGN->PJM
CLTF
5.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.274
TVALTFEXP_TVA->PJM
CLTF
2.24

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.9 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5297.56
MW Contribution:
13.51
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.726
24344105CKG2
50/50
10.12
962761AG1-125 GEN
Solar/Wind Harmer
74.4
970149AG2-104 GEN
Solar/Wind Harmer
40.177
970155AG2-107 GEN
Solar/Wind Harmer
47.51
274773LINCOLN ;4U
Adder
10.701
274774LINCOLN ;5U
Adder
10.701
274723RIVER EC ;12
Adder
22.518
24639705ELKHART HY
Adder
0.193
274751CRETE EC ;1U
Adder
10.338
274754CRETE EC ;4U
Adder
10.338
274812UNIV PK N;8U
Adder
6.271
957891AF2-083 GEN
Solar/Wind Harmer
14.548
274802UNIV PARK;5U
Adder
7.287
945111AF1-176 GEN
Solar/Wind Harmer
15.539
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.275
274676JOLIET 29;8U
Adder
38.191
274674JOLIET 9 ;6U
Adder
19.151
274732ELWOOD EC;7P
Adder
20.437
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
24721705FLATG2
50/50
25.639
270102X2-052 ST
50/50
2.04
270100X2-052 CT1
50/50
1.885
270101X2-052 CT2
50/50
1.885
970349AG2-230 GEN
Solar/Wind Harmer
13.856
965681AG1-436 GEN
Solar/Wind Harmer
11.105
965791AG1-447 GEN
Solar/Wind Harmer
8.144
274770LINCOLN ;1U
Adder
10.701
274771LINCOLN ;2U
Adder
10.701
274805UNIV PK N;1U
Adder
6.285
274808UNIV PK N;4U
Adder
6.243
247620Y3-023
Adder
0.576
274888KELLY CRK;1U
Solar/Wind Harmer
0.509
276776AD2-060 GEN
Solar/Wind Harmer
0.93
958011AF2-095 GEN
Solar/Wind Harmer
12.557
970941AG2-585 GEN
Solar/Wind Harmer
4.796
276897AD1-100 C
Solar/Wind Harmer
21.761
274674JOLIET 9 ;6U
Adder
19.151
961051AF2-396 GEN
Solar/Wind Harmer
17.344
961051AF2-396 GEN
Solar/Wind Harmer
11.563
276893AG1-478 C
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.031
274695ROCKY RD ;2P
Adder
13.708
274693ROCKY RD ;1P
Adder
13.573
274697ROCKY RD ;3P
Adder
3.724
958481AF2-142 GEN
Solar/Wind Harmer
12.877
274683WAUKEGAN ;8U
Adder
25.9
274683WAUKEGAN ;8U
Adder
21.833
962691AG1-118 GEN
Solar/Wind Harmer
25.676
958491AF2-143 GEN
Solar/Wind Harmer
12.799
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
16.931
971343AH1-151 GEN
Solar/Wind Harmer
16.931
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.565
960971AF2-388 GEN
Solar/Wind Harmer
4.962
972235AH1-702 GEN1
Adder
3.049
972236AH1-702 GEN2
Adder
2.651
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
4.755
274764LEE CO EC;5U
Adder
11.194
274765LEE CO EC;6U
Adder
11.194
274762LEE CO EC;3U
Adder
11.167
274763LEE CO EC;4U
Adder
11.062
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.343
276645AC1-214 GEN1
Solar/Wind Harmer
0.326
942111AE2-223 GEN
Solar/Wind Harmer
2.688
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
3.3
960611AF2-352 GEN
Solar/Wind Harmer
2.733
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.927
970291AG2-192 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.479
970241AG2-163 GEN
Solar/Wind Harmer
4.651
270031AE2-169
Solar/Wind Harmer
4.369
270599AE1-208 GEN
Solar/Wind Harmer
7.282
276615X2-022 GEN
Solar/Wind Harmer
0.082
276838X2-022 GEN2
Solar/Wind Harmer
0.445
971613AH1-306 GEN
Solar/Wind Harmer
3.795
270246TR4_N_V150
Solar/Wind Harmer
0.05
270247TR4_N_V136
Solar/Wind Harmer
0.05
276916AD2-100_GEN
Solar/Wind Harmer
16.28
276911AD2-131_GEN
Solar/Wind Harmer
1.072
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
17.757
945391AF1-204 GEN
Solar/Wind Harmer
8.104
964611AG1-324 GEN
Solar/Wind Harmer
0.571
270201AC2-176 GEN
Solar/Wind Harmer
0
247621Y3-024
Adder
0.257
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.297
971587AH1-292 GEN
Solar/Wind Harmer
5.361
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.112
970885AG2-551 GEN
Solar/Wind Harmer
2.371
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.29
270462AD2-086
Solar/Wind Harmer
0
24728805RICHG1
Adder
3.474
24728905RICHG2
Adder
3.474
24723005RIVRG1
Adder
16.391
24723105RIVRG2
Adder
16.391
24722005FLATG5
50/50
1.726
24721905FLATG4
50/50
31.534
962771AG1-126 GEN
Solar/Wind Harmer
74.4
970153AG2-106 GEN
Solar/Wind Harmer
47.51
971347AH1-153 GEN
Solar/Wind Harmer
4.619
270043AE2-236 GEN
Solar/Wind Harmer
5.83
944531AF1-118 GEN
Solar/Wind Harmer
39.701
274772LINCOLN ;3U
Adder
10.701
274724RIVER EC ;11
Adder
22.258
274752CRETE EC ;2U
Adder
10.338
274753CRETE EC ;3U
Adder
10.338
970707AG2-453 GEN
Solar/Wind Harmer
28.587
274814UNIV PK N;0U
Adder
6.326
274807UNIV PK N;3U
Adder
6.312
274811UNIV PK N;7U
Adder
6.271
270063AE2-323 C
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
9.169
972259AH1-714 GEN
Adder
23.869
274826FISK ;BP
Adder
13.684
274803UNIV PARK;6U
Adder
7.287
274887GEN-1.85
Solar/Wind Harmer
0.227
276843GEN-1.7
Solar/Wind Harmer
0.282
276806AD2-047 C O1
Solar/Wind Harmer
4.941
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.059
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
36.827
274729ELWOOD EC;1P
Adder
20.436
274730ELWOOD EC;6P
Adder
20.437
274734ELWOOD EC;8P
Adder
20.437
274736ELWOOD EC;9P
Adder
20.437
943121AE2-341 GEN
Solar/Wind Harmer
14.508
943591AF1-030 GEN
Solar/Wind Harmer
9.648
965021AG1-366 GEN
Solar/Wind Harmer
2.872
274862TOP CROP ;2U
Solar/Wind Harmer
1.159
274682WAUKEGAN ;7U
Adder
22.104
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.703
274879MINONK ;1U
Solar/Wind Harmer
0.355
946671AF1-331 GEN
Solar/Wind Harmer
0.906
274855GSG-6 ;RU
Solar/Wind Harmer
0.31
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
16.931
970571AG2-364 GEN
Solar/Wind Harmer
16.823
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.167
274767LEE CO EC;8U
Adder
11.036
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.328
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
965091AG1-374 GEN
Solar/Wind Harmer
24.6
959611AF2-252 GEN
Solar/Wind Harmer
2.733
24386205FR-12G C
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
20.87
971087AG2-675 GEN
Solar/Wind Harmer
4.365
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.879
971993AH1-541 GEN
Solar/Wind Harmer
3.686
957381AF2-032 GEN
Solar/Wind Harmer
1.767
942481AE2-261 GEN
Solar/Wind Harmer
23.27
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270004AE1-209 GEN
Solar/Wind Harmer
1.678
970825AG2-519 GEN
Solar/Wind Harmer
5.778
24695305TIMB G C
Solar/Wind Harmer
0.648
946031AF1-268 GEN
Solar/Wind Harmer
7.259
970193AG2-126 GEN
Solar/Wind Harmer
11.441
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.403
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.266
270491AE1-102 GEN2
Solar/Wind Harmer
0.958
24728705AND G3
Adder
8.312
24728505AND G1
Adder
3.974
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
24721605FLATG1
50/50
1.726
270071AF1-092 GEN
Solar/Wind Harmer
17.295
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
10.701
274776LINCOLN ;7U
Adder
10.701
274777LINCOLN ;8U
Adder
10.701
971771AH1-392 GEN
Solar/Wind Harmer
8.847
270526AF1-158 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
8.138
274827FISK ;RP
Adder
9.698
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
8.72
972228AH1-698 GEN2
Adder
4.629
972227AH1-698 GEN1
Adder
3.26
274800UNIV PARK;3U
Adder
7.284
274801UNIV PARK;4U
Adder
7.284
970031AG2-029 GEN
Solar/Wind Harmer
4.711
274687WILL CNTY;4U
Adder
34.799
274687WILL CNTY;4U
Adder
34.799
274675JOLIET 29;7U
Adder
38.191
274675JOLIET 29;7U
Adder
36.827
274728ELWOOD EC;5P
Adder
20.437
274731ELWOOD EC;2P
Adder
20.436
274733ELWOOD EC;3P
Adder
20.436
274735ELWOOD EC;4P
Adder
20.436
970833AG2-524 GEN
Solar/Wind Harmer
9.54
970833AG2-524 GEN
Solar/Wind Harmer
6.36
274744AC1-111 GEN8
Adder
6.924
274746AC1-111 G10
Adder
6.924
959331AF2-224 GEN
Solar/Wind Harmer
6.031
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
2.844
959141AF2-205 GEN
Solar/Wind Harmer
0
971675AH1-338 GEN
Solar/Wind Harmer
3.313
971411AH1-196 GEN
Solar/Wind Harmer
12.74
276861AD2-134 GEN
Solar/Wind Harmer
0.151
276863AD2-134 GEN
Solar/Wind Harmer
0.151
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
5.051
971171AH1-044 GEN
Solar/Wind Harmer
16.931
274823ROCKFORD ;21
Adder
23.596
970169AG2-114 GEN
Solar/Wind Harmer
8.419
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.43
971681AH1-341 GEN
Solar/Wind Harmer
13.512
972267AH1-718 GEN
Adder
4.973
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.294
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.684
946321AF1-296 GEN
Solar/Wind Harmer
4.596
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
11.059
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.499
965041AG1-368 GEN
Solar/Wind Harmer
8.029
970289AG2-191 GEN
Solar/Wind Harmer
1.518
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.297
971549AH1-272 GEN
Solar/Wind Harmer
16.346
247521TR3_G114
Solar/Wind Harmer
0.284
965051AG1-369 GEN
Solar/Wind Harmer
3.91
944221AF1-090 GEN
Solar/Wind Harmer
4.487
964611AG1-324 GEN
Solar/Wind Harmer
2.967
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.934
247536S-71 GEN
Solar/Wind Harmer
0.293
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.979
270007AE1-245 C
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
971029AG2-637 GEN
Solar/Wind Harmer
10.316
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.938
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.515
274745AC1-111 GEN9
Adder
6.924
270055AF2-134 C O1
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.615
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.395
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.104
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
13.576
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.138
939401AE1-172 GEN
Solar/Wind Harmer
6.395
962781AG1-127 GEN
Solar/Wind Harmer
8.134
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.993
971997AH1-543 GEN
Solar/Wind Harmer
4.466
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.605
957471AF2-041 GEN
Solar/Wind Harmer
25.396
959081AF2-199 GEN
Solar/Wind Harmer
8.465
971067AG2-660 GEN
Solar/Wind Harmer
2.822
965651AG1-433 GEN
Solar/Wind Harmer
2.481
274822ROCKFORD ;11
Adder
23.769
970819AG2-516 GEN
Solar/Wind Harmer
10.109
970569AG2-363 GEN
Solar/Wind Harmer
25.234
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.167
274766LEE CO EC;7U
Adder
11.036
958861AF2-177 GEN
Solar/Wind Harmer
3.623
276708O09 GEN2
Solar/Wind Harmer
0.294
276646AC1-214 GEN2
Solar/Wind Harmer
0.326
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.579
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.871
276621W2-048 GEN
Solar/Wind Harmer
0.396
270594AE1-207 GEN
Solar/Wind Harmer
8.855
270032AE2-172
Solar/Wind Harmer
5.271
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.696
965911AG1-460 GEN
Solar/Wind Harmer
1.557
270005AE1-210 C O1
Solar/Wind Harmer
1.678
970825AG2-519 GEN
Solar/Wind Harmer
2.723
965421AG1-410 GEN
Solar/Wind Harmer
22.474
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.436
246936BC-WTG1
Solar/Wind Harmer
0.297
270489AE1-102 GEN1
Solar/Wind Harmer
0.958
24728605AND G2
Adder
3.974
970091AG2-072 GEN
Adder
78.436
970773AG2-487 GEN
Solar/Wind Harmer
1.228
270317AD1-130_GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
2.059
24723205RIVRG3
Adder
16.391
NYPJM->LTFIMP_NY
CLTF
3.901
LGEELTFEXP_LGEE->PJM
CLTF
5.998
WECLTFEXP_WEC->PJM
CLTF
4.618
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.416
CPLELTFEXP_CPLE->PJM
CLTF
3.255
MECLTFEXP_MEC->PJM
CLTF
18.61
SIGELTFEXP_SIGE->PJM
CLTF
0.498
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.551
LAGNLTFEXP_LAGN->PJM
CLTF
16.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.242
TVALTFEXP_TVA->PJM
CLTF
7.96

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4473.55
MW Contribution:
14.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
69.962
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.277
270100X2-052 CT1
50/50
2.104
270101X2-052 CT2
50/50
2.104
24643105BUCHANAN
50/50
0.018
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
970349AG2-230 GEN
Solar/Wind Harmer
15.664
961051AF2-396 GEN
Solar/Wind Harmer
19.838
961051AF2-396 GEN
Solar/Wind Harmer
13.225
965681AG1-436 GEN
Solar/Wind Harmer
12.356
965791AG1-447 GEN
Solar/Wind Harmer
9.061
270462AD2-086
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
11.612
274771LINCOLN ;2U
Adder
11.612
270246TR4_N_V150
Solar/Wind Harmer
0.061
270247TR4_N_V136
Solar/Wind Harmer
0.061
274805UNIV PK N;1U
Adder
6.81
274808UNIV PK N;4U
Adder
6.766
274888KELLY CRK;1U
Solar/Wind Harmer
0.548
276776AD2-060 GEN
Solar/Wind Harmer
1.003
958011AF2-095 GEN
Solar/Wind Harmer
13.543
970941AG2-585 GEN
Solar/Wind Harmer
5.173
246937BC-WTG2
Solar/Wind Harmer
0.378
276897AD1-100 C
Solar/Wind Harmer
23.396
944231AF1-091 GEN
Solar/Wind Harmer
21.57
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
20.564
276893AG1-478 C
Solar/Wind Harmer
0.621
944541AF1-119 GEN
Solar/Wind Harmer
0.62
960971AF2-388 GEN
Solar/Wind Harmer
5.451
958481AF2-142 GEN
Solar/Wind Harmer
13.721
274695ROCKY RD ;2P
Adder
14.592
274693ROCKY RD ;1P
Adder
14.449
274697ROCKY RD ;3P
Adder
3.964
274696ROCKY RD ;4P
Adder
14.936
942221AE2-234 GEN
Solar/Wind Harmer
3.664
274683WAUKEGAN ;8U
Adder
27.547
274683WAUKEGAN ;8U
Adder
23.221
962691AG1-118 GEN
Solar/Wind Harmer
27.25
958491AF2-143 GEN
Solar/Wind Harmer
13.572
276901AD2-066 C O1
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.823
971343AH1-151 GEN
Solar/Wind Harmer
17.823
276872AE1-163_GEN1
Solar/Wind Harmer
0
24721805FLATG3
50/50
4.711
24344105CKG2
50/50
11.483
270143AC1-141 CT2_
50/50
3.456
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.675
24307105BERRINSP G
50/50
0.03
962761AG1-125 GEN
Solar/Wind Harmer
109.537
970149AG2-104 GEN
Solar/Wind Harmer
59.152
970155AG2-107 GEN
Solar/Wind Harmer
69.947
965011AG1-365 GEN
Solar/Wind Harmer
10.32
957891AF2-083 GEN
Solar/Wind Harmer
16.606
945111AF1-176 GEN
Solar/Wind Harmer
17.763
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
5.166
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
274773LINCOLN ;4U
Adder
11.612
274774LINCOLN ;5U
Adder
11.612
274723RIVER EC ;12
Adder
24.471
274751CRETE EC ;1U
Adder
11.245
274754CRETE EC ;4U
Adder
11.245
965421AG1-410 GEN
Solar/Wind Harmer
28.412
970373AG2-245 GEN
Solar/Wind Harmer
19.884
274812UNIV PK N;8U
Adder
6.795
274802UNIV PARK;5U
Adder
7.869
246936BC-WTG1
Solar/Wind Harmer
0.378
270489AE1-102 GEN1
Solar/Wind Harmer
1.219
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
41.04
270055AF2-134 C O1
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
20.564
274732ELWOOD EC;7P
Adder
21.94
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
2.726
274745AC1-111 GEN9
Adder
7.404
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.902
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.486
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
23.522
958861AF2-177 GEN
Solar/Wind Harmer
3.956
274828WAUKEGAN ;BP
Adder
14.44
962781AG1-127 GEN
Solar/Wind Harmer
8.625
939401AE1-172 GEN
Solar/Wind Harmer
6.778
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.051
971997AH1-543 GEN
Solar/Wind Harmer
4.72
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.201
957471AF2-041 GEN
Solar/Wind Harmer
26.735
959081AF2-199 GEN
Solar/Wind Harmer
8.912
971067AG2-660 GEN
Solar/Wind Harmer
2.971
274822ROCKFORD ;11
Adder
24.99
970819AG2-516 GEN
Solar/Wind Harmer
10.604
945371AF1-202 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
26.447
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.659
274766LEE CO EC;7U
Adder
11.522
276708O09 GEN2
Solar/Wind Harmer
0.306
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
270024AE2-089 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.948
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
9.214
270032AE2-172
Solar/Wind Harmer
5.485
270005AE1-210 C O1
Solar/Wind Harmer
1.752
276903AD2-071 C
Solar/Wind Harmer
8.936
970825AG2-519 GEN
Solar/Wind Harmer
2.836
963741AG1-226 GEN
Solar/Wind Harmer
18.848
276621W2-048 GEN
Solar/Wind Harmer
0.393
965911AG1-460 GEN
Solar/Wind Harmer
1.522
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
24721605FLATG1
50/50
4.711
270144AC1-141 ST1_
50/50
3.051
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.268
24653605MOTTVILLE
50/50
0.005
959331AF2-224 GEN
Solar/Wind Harmer
7.224
270578AF1-285 GEN2
Solar/Wind Harmer
0.682
270071AF1-092 GEN
Solar/Wind Harmer
19.599
970031AG2-029 GEN
Solar/Wind Harmer
5.461
971771AH1-392 GEN
Solar/Wind Harmer
10.022
270526AF1-158 GEN
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
24729505KEY G4
Adder
9.105
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.376
965041AG1-368 GEN
Solar/Wind Harmer
9.736
274775LINCOLN ;6U
Adder
11.612
274776LINCOLN ;7U
Adder
11.612
274777LINCOLN ;8U
Adder
11.612
247521TR3_G114
Solar/Wind Harmer
0.347
965051AG1-369 GEN
Solar/Wind Harmer
4.782
963791AG1-232 GEN
Solar/Wind Harmer
12.72
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.469
960591AF2-350 GEN
Solar/Wind Harmer
9.405
274800UNIV PARK;3U
Adder
7.859
274801UNIV PARK;4U
Adder
7.859
972228AH1-698 GEN2
Adder
4.989
972227AH1-698 GEN1
Adder
3.513
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.188
274687WILL CNTY;4U
Adder
37.422
274687WILL CNTY;4U
Adder
37.422
274675JOLIET 29;7U
Adder
41.04
274675JOLIET 29;7U
Adder
39.575
274728ELWOOD EC;5P
Adder
21.94
274731ELWOOD EC;2P
Adder
21.939
274733ELWOOD EC;3P
Adder
21.939
274735ELWOOD EC;4P
Adder
21.939
970833AG2-524 GEN
Solar/Wind Harmer
10.228
970833AG2-524 GEN
Solar/Wind Harmer
6.819
971549AH1-272 GEN
Solar/Wind Harmer
19.166
274744AC1-111 GEN8
Adder
7.404
274746AC1-111 G10
Adder
7.404
958391AF2-133 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
3.016
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.448
971675AH1-338 GEN
Solar/Wind Harmer
3.496
276861AD2-134 GEN
Solar/Wind Harmer
0.16
276863AD2-134 GEN
Solar/Wind Harmer
0.16
971611AH1-305 GEN
Solar/Wind Harmer
5.334
270007AE1-245 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.823
274823ROCKFORD ;21
Adder
24.808
274856ECOGROVE ;U1
Solar/Wind Harmer
0.206
945581AF1-223 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.499
970169AG2-114 GEN
Solar/Wind Harmer
8.815
971681AH1-341 GEN
Solar/Wind Harmer
14.132
972267AH1-718 GEN
Adder
5.171
276741O09 GEN1
Solar/Wind Harmer
0.306
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.961
971609AH1-304 GEN
Solar/Wind Harmer
1.381
946321AF1-296 GEN
Solar/Wind Harmer
4.723
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24722005FLATG5
50/50
4.711
24721905FLATG4
50/50
86.05
270475AD2-096_GEN
50/50
10.483
270142AC1-141 CT1_
50/50
3.456
24642205MAYFLWER
50/50
0.053
944961AF1-161 GEN
50/50
4.124
962601AG1-109 GEN
50/50
4.124
962771AG1-126 GEN
Solar/Wind Harmer
109.537
970153AG2-106 GEN
Solar/Wind Harmer
69.947
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270043AE2-236 GEN
Solar/Wind Harmer
6.765
971347AH1-153 GEN
Solar/Wind Harmer
5.221
965021AG1-366 GEN
Solar/Wind Harmer
3.44
270391AF1-285 GEN3
Solar/Wind Harmer
0.682
270063AE2-323 C
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
10.472
944531AF1-118 GEN
Solar/Wind Harmer
44.69
945111AF1-176 GEN
Solar/Wind Harmer
8.069
274772LINCOLN ;3U
Adder
11.612
274724RIVER EC ;11
Adder
24.187
274752CRETE EC ;2U
Adder
11.245
274753CRETE EC ;3U
Adder
11.245
274814UNIV PK N;0U
Adder
6.855
274807UNIV PK N;3U
Adder
6.84
274811UNIV PK N;7U
Adder
6.795
970707AG2-453 GEN
Solar/Wind Harmer
30.807
24695305TIMB G C
Solar/Wind Harmer
0.797
274803UNIV PARK;6U
Adder
7.869
274826FISK ;BP
Adder
14.772
274887GEN-1.85
Solar/Wind Harmer
0.244
276843GEN-1.7
Solar/Wind Harmer
0.304
276806AD2-047 C O1
Solar/Wind Harmer
5.33
972038AH1-567 GEN2
Adder
0.492
972259AH1-714 GEN
Adder
25.709
246938BC-WTG3
Solar/Wind Harmer
0.338
270491AE1-102 GEN2
Solar/Wind Harmer
1.219
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
39.574
274729ELWOOD EC;1P
Adder
21.939
274730ELWOOD EC;6P
Adder
21.94
274734ELWOOD EC;8P
Adder
21.94
274736ELWOOD EC;9P
Adder
21.94
943121AE2-341 GEN
Solar/Wind Harmer
15.518
943591AF1-030 GEN
Solar/Wind Harmer
10.32
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
1.234
274682WAUKEGAN ;7U
Adder
23.522
276868AE1-113 GEN
Solar/Wind Harmer
1.802
274879MINONK ;1U
Solar/Wind Harmer
0.376
946671AF1-331 GEN
Solar/Wind Harmer
0.957
274855GSG-6 ;RU
Solar/Wind Harmer
0.327
274850MENDOTA H;RU
Solar/Wind Harmer
0.104
959091AF2-200 GEN
Solar/Wind Harmer
17.823
970571AG2-364 GEN
Solar/Wind Harmer
17.631
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.659
274767LEE CO EC;8U
Adder
11.522
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.625
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
965091AG1-374 GEN
Solar/Wind Harmer
25.202
959611AF2-252 GEN
Solar/Wind Harmer
2.8
247642Z2-115 C
Solar/Wind Harmer
0.003
965931AG1-462 GEN
Solar/Wind Harmer
21.395
971087AG2-675 GEN
Solar/Wind Harmer
4.475
24386205FR-12G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.915
270004AE1-209 GEN
Solar/Wind Harmer
1.752
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
12.121
970825AG2-519 GEN
Solar/Wind Harmer
6.019
971993AH1-541 GEN
Solar/Wind Harmer
3.688
946031AF1-268 GEN
Solar/Wind Harmer
7.583
957381AF2-032 GEN
Solar/Wind Harmer
1.73
942481AE2-261 GEN
Solar/Wind Harmer
22.758
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.995
24728705AND G3
Adder
8.012
24728505AND G1
Adder
3.831
270541AE2-072 C
Solar/Wind Harmer
0
23906402RICHG1
Adder
1.111
23906502RICHG2&3
Adder
1.11
970289AG2-191 GEN
Solar/Wind Harmer
1.58
963841AG1-237 GEN
Solar/Wind Harmer
3.532
964611AG1-324 GEN
Solar/Wind Harmer
3.142
276668AB2-070 GEN1
Solar/Wind Harmer
0.314
276848AB2-070 GEN3
Solar/Wind Harmer
0.312
276849AB2-070 GEN2
Solar/Wind Harmer
0.314
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.308
270543AE2-219 C
Solar/Wind Harmer
5.181
944221AF1-090 GEN
Solar/Wind Harmer
4.314
971029AG2-637 GEN
Solar/Wind Harmer
10.609
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.202
972236AH1-702 GEN2
Adder
2.785
970623AG2-406 GEN
Solar/Wind Harmer
1.615
938861AE1-114 GEN
Solar/Wind Harmer
4.972
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
274764LEE CO EC;5U
Adder
11.687
274765LEE CO EC;6U
Adder
11.687
274762LEE CO EC;3U
Adder
11.659
274763LEE CO EC;4U
Adder
11.55
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.395
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.774
270031AE2-169
Solar/Wind Harmer
4.65
270599AE1-208 GEN
Solar/Wind Harmer
7.749
960611AF2-352 GEN
Solar/Wind Harmer
2.8
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.946
970291AG2-192 GEN
Solar/Wind Harmer
1.081
970291AG2-192 GEN
Solar/Wind Harmer
0.499
971613AH1-306 GEN
Solar/Wind Harmer
3.949
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.604
970241AG2-163 GEN
Solar/Wind Harmer
4.646
970621AG2-405 GEN
Solar/Wind Harmer
1.449
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
247621Y3-024
Adder
0.272
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
926881AC1-175 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
15.862
276911AD2-131_GEN
Solar/Wind Harmer
1.045
970883AG2-550 GEN
Solar/Wind Harmer
7.401
970885AG2-551 GEN
Solar/Wind Harmer
2.467
270383AD1-128 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.788
971587AH1-292 GEN
Solar/Wind Harmer
4.757
24728805RICHG1
Adder
3.35
24728905RICHG2
Adder
3.35
970329AG2-216 GEN
Solar/Wind Harmer
2.663
25326509SID D
Adder
1.142
970613AG2-401 GEN
Solar/Wind Harmer
5.54
24728605AND G2
Adder
3.831
970773AG2-487 GEN
Solar/Wind Harmer
1.192
23906502RICHG2&3
Adder
1.11
NYPJM->LTFIMP_NY
CLTF
3.074
LGEELTFEXP_LGEE->PJM
CLTF
4.556
WECLTFEXP_WEC->PJM
CLTF
4.845
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.375
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.313
MECLTFEXP_MEC->PJM
CLTF
18.13
SIGELTFEXP_SIGE->PJM
CLTF
0.416
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.158
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.889
LAGNLTFEXP_LAGN->PJM
CLTF
11.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.981
TVALTFEXP_TVA->PJM
CLTF
4.815

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#711_05MARYSV 765_A1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#711_05MARYSV 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.43 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3327.22
MW Contribution:
7.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
15.792
970349AG2-230 GEN
Solar/Wind Harmer
8.806
274770LINCOLN ;1U
Adder
3.399
274771LINCOLN ;2U
Adder
3.399
965681AG1-436 GEN
Solar/Wind Harmer
6.664
965791AG1-447 GEN
Solar/Wind Harmer
3.409
274888KELLY CRK;1U
Solar/Wind Harmer
3.114
276776AD2-060 GEN
Solar/Wind Harmer
0.221
958011AF2-095 GEN
Solar/Wind Harmer
7.599
970941AG2-585 GEN
Solar/Wind Harmer
2.903
276897AD1-100 C
Solar/Wind Harmer
24.489
274805UNIV PK N;1U
Adder
2.642
274808UNIV PK N;4U
Adder
2.625
274674JOLIET 9 ;6U
Adder
8.073
276893AG1-478 C
Solar/Wind Harmer
0.229
274696ROCKY RD ;4P
Adder
5.889
274695ROCKY RD ;2P
Adder
5.753
274693ROCKY RD ;1P
Adder
5.697
274697ROCKY RD ;3P
Adder
1.563
274683WAUKEGAN ;8U
Adder
10.848
274683WAUKEGAN ;8U
Adder
9.145
962691AG1-118 GEN
Solar/Wind Harmer
15.409
958481AF2-142 GEN
Solar/Wind Harmer
7.69
960751AF2-366 GEN
Solar/Wind Harmer
1.47
958491AF2-143 GEN
Solar/Wind Harmer
7.602
24721805FLATG3
50/50
1.063
962761AG1-125 GEN
Solar/Wind Harmer
78.258
970149AG2-104 GEN
Solar/Wind Harmer
48.324
970155AG2-107 GEN
Solar/Wind Harmer
34.124
972207SS24-0001
Solar/Wind Harmer
12.083
274773LINCOLN ;4U
Adder
3.399
274774LINCOLN ;5U
Adder
3.399
274723RIVER EC ;12
Adder
9.496
941551AE2-152 GEN
Solar/Wind Harmer
2.391
274802UNIV PARK;5U
Adder
3.071
274812UNIV PK N;8U
Adder
2.636
274751CRETE EC ;1U
Adder
2.57
274754CRETE EC ;4U
Adder
2.57
274676JOLIET 29;8U
Adder
16.11
274871GR RIDGE ;2U
Solar/Wind Harmer
4.032
274847GR RIDGE ;BU
Solar/Wind Harmer
2.651
274674JOLIET 9 ;6U
Adder
8.073
274732ELWOOD EC;7P
Adder
8.606
274745AC1-111 GEN9
Adder
2.922
274682WAUKEGAN ;7U
Adder
9.263
274828WAUKEGAN ;BP
Adder
5.686
276694AA1-018 GEN2
Solar/Wind Harmer
3.235
276691AA1-018 GEN1
Solar/Wind Harmer
0.387
962781AG1-127 GEN
Solar/Wind Harmer
4.873
274861TOP CROP ;1U
Solar/Wind Harmer
3.103
274872LEEDK;1U
Solar/Wind Harmer
4.197
939401AE1-172 GEN
Solar/Wind Harmer
7.067
276805AD2-038 GEN
Solar/Wind Harmer
2.599
970373AG2-245 GEN
Solar/Wind Harmer
10.616
971997AH1-543 GEN
Solar/Wind Harmer
7.954
276882AE2-255 GEN
Solar/Wind Harmer
1.704
957471AF2-041 GEN
Solar/Wind Harmer
15.098
959081AF2-199 GEN
Solar/Wind Harmer
5.033
971067AG2-660 GEN
Solar/Wind Harmer
1.17
24722005FLATG5
50/50
1.063
24721905FLATG4
50/50
19.423
962771AG1-126 GEN
Solar/Wind Harmer
78.258
970153AG2-106 GEN
Solar/Wind Harmer
34.124
971347AH1-153 GEN
Solar/Wind Harmer
2.935
274772LINCOLN ;3U
Adder
3.399
970707AG2-453 GEN
Solar/Wind Harmer
15.013
972259AH1-714 GEN
Adder
10.14
276164X3-005 C
Solar/Wind Harmer
0.372
274724RIVER EC ;11
Adder
9.39
274887GEN-1.85
Solar/Wind Harmer
2.812
276772AC2-154 GEN
Solar/Wind Harmer
1.473
276843GEN-1.7
Solar/Wind Harmer
0.303
276806AD2-047 C O1
Solar/Wind Harmer
5.646
274826FISK ;BP
Adder
5.774
939351AE1-166 GEN
Solar/Wind Harmer
3.126
972038AH1-567 GEN2
Adder
0.192
274803UNIV PARK;6U
Adder
3.071
274814UNIV PK N;0U
Adder
2.659
274807UNIV PK N;3U
Adder
2.653
274811UNIV PK N;7U
Adder
2.636
972231SS25-0005
Solar/Wind Harmer
4.99
972181SS23-001
Solar/Wind Harmer
3.119
274752CRETE EC ;2U
Adder
2.57
274753CRETE EC ;3U
Adder
2.57
274676JOLIET 29;8U
Adder
15.535
943121AE2-341 GEN
Solar/Wind Harmer
7.867
943591AF1-030 GEN
Solar/Wind Harmer
5.245
274729ELWOOD EC;1P
Adder
8.606
274730ELWOOD EC;6P
Adder
8.606
274734ELWOOD EC;8P
Adder
8.606
274736ELWOOD EC;9P
Adder
8.606
24441505OLIV SLR
Solar/Wind Harmer
0.069
274682WAUKEGAN ;7U
Adder
9.263
274862TOP CROP ;2U
Solar/Wind Harmer
2.591
276799AD1-013 GEN
Solar/Wind Harmer
1.12
24721605FLATG1
50/50
1.063
274775LINCOLN ;6U
Adder
3.399
274776LINCOLN ;7U
Adder
3.399
274777LINCOLN ;8U
Adder
3.399
960681AF2-359 GEN
Solar/Wind Harmer
2.014
972228AH1-698 GEN2
Adder
1.958
972227AH1-698 GEN1
Adder
1.378
960591AF2-350 GEN
Solar/Wind Harmer
5.277
274827FISK ;RP
Adder
4.092
274800UNIV PARK;3U
Adder
3.073
274801UNIV PARK;4U
Adder
3.073
972037AH1-567 GEN1
Adder
0.096
274687WILL CNTY;4U
Adder
14.674
274687WILL CNTY;4U
Adder
14.674
274675JOLIET 29;7U
Adder
16.11
274675JOLIET 29;7U
Adder
15.535
970833AG2-524 GEN
Solar/Wind Harmer
4.579
970833AG2-524 GEN
Solar/Wind Harmer
2.13
274728ELWOOD EC;5P
Adder
8.606
274731ELWOOD EC;2P
Adder
8.606
274733ELWOOD EC;3P
Adder
8.606
274735ELWOOD EC;4P
Adder
8.606
276893AG1-478 C
Solar/Wind Harmer
0.288
274744AC1-111 GEN8
Adder
2.922
274746AC1-111 G10
Adder
2.922
270526AF1-158 GEN
Solar/Wind Harmer
2.34
971771AH1-392 GEN
Solar/Wind Harmer
4.588
970073AG2-061 GEN
Solar/Wind Harmer
1.179
971675AH1-338 GEN
Solar/Wind Harmer
9.118
276861AD2-134 GEN
Solar/Wind Harmer
0.904
276863AD2-134 GEN
Solar/Wind Harmer
0.904
971411AH1-196 GEN
Solar/Wind Harmer
7.595
971171AH1-044 GEN
Solar/Wind Harmer
10.065
274823ROCKFORD ;21
Adder
9.774
274863CRW1-WTG
Solar/Wind Harmer
2.783
274864CRW2-WTG
Solar/Wind Harmer
2.783
276889AE2-281 GEN
Solar/Wind Harmer
0.957
274856ECOGROVE ;U1
Solar/Wind Harmer
1.68
276611AD2-172 GEN
Solar/Wind Harmer
1.274
276612AE2-035 GEN
Solar/Wind Harmer
1.274
971681AH1-341 GEN
Solar/Wind Harmer
7.429
926823AC1-168 GEN
Solar/Wind Harmer
2.122
970169AG2-114 GEN
Solar/Wind Harmer
4.901
972267AH1-718 GEN
Adder
2.035
276741O09 GEN1
Solar/Wind Harmer
1.739
958391AF2-133 GEN
Solar/Wind Harmer
4.373
274877BISHOP HL;1U
Solar/Wind Harmer
1.621
959141AF2-205 GEN
Solar/Wind Harmer
2.893
270223U2-072_GEN1
Solar/Wind Helper
1.526
270224U2-072_GEN2
Solar/Wind Helper
1.526
270227U2-072_GEN3
Solar/Wind Helper
1.526
270228U2-072_GEN4
Solar/Wind Helper
1.526
270231U2-072_GEN5
Solar/Wind Helper
1.526
241973AD2-163_GEN1
Solar/Wind Helper
2.406
241974AD2-163_GEN2
Solar/Wind Helper
2.406
241955AC1-078 GEN
Solar/Wind Helper
2.39
945631AF1-228 GEN
Solar/Wind Helper
1.862
966831AG1-554 GEN
Solar/Wind Helper
0.86
253338AC1-165 GEN
Solar/Wind Helper
0.829
253343AC1-166 GEN
Solar/Wind Helper
0.829
241972AD1-140 GEN
Solar/Wind Helper
3.091
945641AF1-229 GEN
Solar/Wind Helper
1.095
270499AE1-146 GEN
Solar/Wind Helper
1.885
270263AC1-001 GEN
Solar/Wind Helper
0.54
270340AC2-060 GEN
Solar/Wind Helper
0.967
276901AD2-066 C O1
Solar/Wind Harmer
1.777
971341AH1-150 GEN
Solar/Wind Harmer
10.065
971343AH1-151 GEN
Solar/Wind Harmer
10.065
972235AH1-702 GEN1
Adder
1.262
972236AH1-702 GEN2
Adder
1.097
276872AE1-163_GEN1
Solar/Wind Harmer
3.349
276876AE1-163_GEN2
Solar/Wind Harmer
3.349
270535AF1-215 GEN1
Solar/Wind Harmer
2.252
270536AF1-215 GEN2
Solar/Wind Harmer
2.252
938861AE1-114 GEN
Solar/Wind Harmer
4.059
274764LEE CO EC;5U
Adder
4.601
274765LEE CO EC;6U
Adder
4.601
274762LEE CO EC;3U
Adder
4.59
274763LEE CO EC;4U
Adder
4.547
276158O29GEN2
Solar/Wind Harmer
2.436
276157O29GEN1
Solar/Wind Harmer
1.852
276645AC1-214 GEN1
Solar/Wind Harmer
0.646
247620Y3-023
Adder
0.208
270349AD2-093_GEN
Solar/Wind Helper
4.68
270471AD2-092_GEN
Solar/Wind Helper
4.68
270462AD2-086
Solar/Wind Helper
5.356
253383AE2-342_GEN
Solar/Wind Helper
1.111
946101AF1-275 GEN
Solar/Wind Helper
0.784
241960AC2-195 GEN
Solar/Wind Helper
1.835
270054AF2-122 C O1
Solar/Wind Helper
1.457
253378AE2-206_GEN
Solar/Wind Helper
1.313
247522W1-056 GEN
Solar/Wind Helper
1.156
253415AE1-040 GEN
Solar/Wind Helper
0.455
961051AF2-396 GEN
Solar/Wind Harmer
7.374
961051AF2-396 GEN
Solar/Wind Harmer
3.43
946671AF1-331 GEN
Solar/Wind Harmer
0.212
274855GSG-6 ;RU
Solar/Wind Harmer
1.87
274850MENDOTA H;RU
Solar/Wind Harmer
1.3
276602WESTBROOK C
Solar/Wind Harmer
1.076
276868AE1-113 GEN
Solar/Wind Harmer
5.111
274879MINONK ;1U
Solar/Wind Harmer
3.407
959091AF2-200 GEN
Solar/Wind Harmer
10.065
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.364
274760LEE CO EC;1U
Adder
4.59
274767LEE CO EC;8U
Adder
4.536
970571AG2-364 GEN
Solar/Wind Harmer
9.862
276603SUBLETTE C
Solar/Wind Harmer
0.517
270505AE1-170 C O1
Solar/Wind Harmer
7.344
964401AG1-302 GEN
Solar/Wind Harmer
4.417
274851PROVIDENC;RU
Solar/Wind Harmer
1.375
274849CRESCENT ;1U
Solar/Wind Harmer
0.892
276782AC1-033 GEN
Solar/Wind Harmer
1.916
274878BISHOP HL;2U
Solar/Wind Harmer
1.621
945111AF1-176 GEN
Solar/Wind Harmer
2.711
270284AF1-227 GEN1
Solar/Wind Helper
6.367
270287AF1-227 GEN3
Solar/Wind Helper
2.335
942871AE2-306 GEN
Solar/Wind Helper
0.775
276820AF1-078_GEN
Solar/Wind Helper
0.613
270518AE2-148 GEN
Solar/Wind Helper
10.61
960801AF2-371 GEN
Solar/Wind Helper
0.85
964871AG1-351 GEN
Solar/Wind Helper
0.587
253325AC1-069 GEN
Solar/Wind Helper
0.859
270541AE2-072 C
Solar/Wind Helper
1.112
960071AF2-298 GEN
Solar/Wind Helper
0.32
274822ROCKFORD ;11
Adder
9.846
970819AG2-516 GEN
Solar/Wind Harmer
5.988
270055AF2-134 C O1
Solar/Wind Harmer
1.501
274858EASY ROAD;U2
Solar/Wind Harmer
2.364
274761LEE CO EC;2U
Adder
4.59
274766LEE CO EC;7U
Adder
4.536
970569AG2-363 GEN
Solar/Wind Harmer
14.794
270216AD2-079_GEN
Solar/Wind Harmer
0.298
957891AF2-083 GEN
Solar/Wind Harmer
7.311
958381AF2-132 GEN
Solar/Wind Harmer
4.417
276708O09 GEN2
Solar/Wind Harmer
1.739
964861AG1-349 GEN
Solar/Wind Harmer
3.821
971917AH1-482 GEN
Solar/Wind Harmer
4.408
276646AC1-214 GEN2
Solar/Wind Harmer
0.646
945111AF1-176 GEN
Solar/Wind Harmer
8.554
274848CAMPGROVE;RU
Solar/Wind Harmer
3.088
24639705ELKHART HY
Adder
0.072
270286AF1-227 GEN2
Solar/Wind Helper
2.335
270391AF1-285 GEN3
Solar/Wind Helper
1.033
270578AF1-285 GEN2
Solar/Wind Helper
1.033
270317AD1-130_GEN
Solar/Wind Helper
5.921
270485AE1-090_GEN
Solar/Wind Helper
0.466
270520AE2-214 GEN
Solar/Wind Helper
3.134
253333AC1-068 GEN
Solar/Wind Helper
0.859
960841AF2-375 GEN
Solar/Wind Helper
1.147
270273AD2-016 GEN
Solar/Wind Helper
1.662
270297AD1-101 GEN
Solar/Wind Helper
0.209
958961AF2-187 GEN
Solar/Wind Helper
1.121
241840AF1-064_GEN
Solar/Wind Helper
0.476
241807AE2-176_GEN
Solar/Wind Helper
0.698
NYPJM->LTFIMP_NY
CLTF
0.933
LGEELTFEXP_LGEE->PJM
CLTF
0.885
WECLTFEXP_WEC->PJM
CLTF
1.909
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.606
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.522
CPLELTFEXP_CPLE->PJM
CLTF
1.546
MECLTFEXP_MEC->PJM
CLTF
7.183
SIGELTFEXP_SIGE->PJM
CLTF
0.119
AG2-052LTFEXP_AG2-052->PJM
LTF
0.114
AH1-155LTFEXP_AH1-155->PJM
LTF
0.17
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.631
LAGNLTFEXP_LAGN->PJM
CLTF
5.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.313
TVALTFEXP_TVA->PJM
CLTF
2.485

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.32 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3323.76
MW Contribution:
7.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
3.349
274776LINCOLN ;7U
Adder
3.349
274777LINCOLN ;8U
Adder
3.349
960681AF2-359 GEN
Solar/Wind Harmer
1.984
972228AH1-698 GEN2
Adder
1.928
972227AH1-698 GEN1
Adder
1.358
960591AF2-350 GEN
Solar/Wind Harmer
5.197
274827FISK ;RP
Adder
4.03
274800UNIV PARK;3U
Adder
3.027
274801UNIV PARK;4U
Adder
3.027
972037AH1-567 GEN1
Adder
0.095
274687WILL CNTY;4U
Adder
14.452
274687WILL CNTY;4U
Adder
14.452
274675JOLIET 29;7U
Adder
15.866
274675JOLIET 29;7U
Adder
15.3
970833AG2-524 GEN
Solar/Wind Harmer
4.51
970833AG2-524 GEN
Solar/Wind Harmer
2.098
274728ELWOOD EC;5P
Adder
8.475
274731ELWOOD EC;2P
Adder
8.475
274733ELWOOD EC;3P
Adder
8.475
274735ELWOOD EC;4P
Adder
8.475
276893AG1-478 C
Solar/Wind Harmer
0.283
274744AC1-111 GEN8
Adder
2.877
274746AC1-111 G10
Adder
2.877
270526AF1-158 GEN
Solar/Wind Harmer
2.303
971771AH1-392 GEN
Solar/Wind Harmer
4.514
970073AG2-061 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
8.977
276861AD2-134 GEN
Solar/Wind Harmer
0.89
276863AD2-134 GEN
Solar/Wind Harmer
0.89
971411AH1-196 GEN
Solar/Wind Harmer
7.478
971171AH1-044 GEN
Solar/Wind Harmer
9.909
274823ROCKFORD ;21
Adder
9.622
276889AE2-281 GEN
Solar/Wind Harmer
0.942
274863CRW1-WTG
Solar/Wind Harmer
2.739
274864CRW2-WTG
Solar/Wind Harmer
2.739
274856ECOGROVE ;U1
Solar/Wind Harmer
1.654
276611AD2-172 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
1.254
971681AH1-341 GEN
Solar/Wind Harmer
7.312
926823AC1-168 GEN
Solar/Wind Harmer
2.088
970169AG2-114 GEN
Solar/Wind Harmer
4.823
972267AH1-718 GEN
Adder
2.003
276741O09 GEN1
Solar/Wind Harmer
1.712
958391AF2-133 GEN
Solar/Wind Harmer
4.3
274877BISHOP HL;1U
Solar/Wind Harmer
1.595
959141AF2-205 GEN
Solar/Wind Harmer
2.844
270223U2-072_GEN1
Solar/Wind Helper
1.536
270224U2-072_GEN2
Solar/Wind Helper
1.536
270227U2-072_GEN3
Solar/Wind Helper
1.536
270228U2-072_GEN4
Solar/Wind Helper
1.536
270231U2-072_GEN5
Solar/Wind Helper
1.536
241973AD2-163_GEN1
Solar/Wind Helper
2.441
241974AD2-163_GEN2
Solar/Wind Helper
2.441
241955AC1-078 GEN
Solar/Wind Helper
2.436
945631AF1-228 GEN
Solar/Wind Helper
1.902
966831AG1-554 GEN
Solar/Wind Helper
0.869
253338AC1-165 GEN
Solar/Wind Helper
0.848
253343AC1-166 GEN
Solar/Wind Helper
0.848
241972AD1-140 GEN
Solar/Wind Helper
3.153
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.906
270263AC1-001 GEN
Solar/Wind Helper
0.555
270340AC2-060 GEN
Solar/Wind Helper
0.994
24721705FLATG2
50/50
15.73
970349AG2-230 GEN
Solar/Wind Harmer
8.682
274770LINCOLN ;1U
Adder
3.349
274771LINCOLN ;2U
Adder
3.349
965681AG1-436 GEN
Solar/Wind Harmer
6.562
965791AG1-447 GEN
Solar/Wind Harmer
3.357
274888KELLY CRK;1U
Solar/Wind Harmer
3.067
276776AD2-060 GEN
Solar/Wind Harmer
0.218
958011AF2-095 GEN
Solar/Wind Harmer
7.484
970941AG2-585 GEN
Solar/Wind Harmer
2.859
276897AD1-100 C
Solar/Wind Harmer
24.118
274805UNIV PK N;1U
Adder
2.602
274808UNIV PK N;4U
Adder
2.585
274674JOLIET 9 ;6U
Adder
7.951
276893AG1-478 C
Solar/Wind Harmer
0.226
274695ROCKY RD ;2P
Adder
5.665
274693ROCKY RD ;1P
Adder
5.61
274697ROCKY RD ;3P
Adder
1.539
274696ROCKY RD ;4P
Adder
5.799
274683WAUKEGAN ;8U
Adder
10.682
274683WAUKEGAN ;8U
Adder
9.005
962691AG1-118 GEN
Solar/Wind Harmer
15.173
958481AF2-142 GEN
Solar/Wind Harmer
7.571
960751AF2-366 GEN
Solar/Wind Harmer
1.448
958491AF2-143 GEN
Solar/Wind Harmer
7.484
276901AD2-066 C O1
Solar/Wind Harmer
1.749
971341AH1-150 GEN
Solar/Wind Harmer
9.909
971343AH1-151 GEN
Solar/Wind Harmer
9.909
972235AH1-702 GEN1
Adder
1.242
972236AH1-702 GEN2
Adder
1.08
276872AE1-163_GEN1
Solar/Wind Harmer
3.296
276876AE1-163_GEN2
Solar/Wind Harmer
3.296
270535AF1-215 GEN1
Solar/Wind Harmer
2.215
270536AF1-215 GEN2
Solar/Wind Harmer
2.215
938861AE1-114 GEN
Solar/Wind Harmer
3.995
274764LEE CO EC;5U
Adder
4.528
274765LEE CO EC;6U
Adder
4.528
274762LEE CO EC;3U
Adder
4.518
274763LEE CO EC;4U
Adder
4.475
276158O29GEN2
Solar/Wind Harmer
2.397
276157O29GEN1
Solar/Wind Harmer
1.823
276645AC1-214 GEN1
Solar/Wind Harmer
0.636
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.705
270471AD2-092_GEN
Solar/Wind Helper
4.705
270462AD2-086
Solar/Wind Helper
5.394
253383AE2-342_GEN
Solar/Wind Helper
1.128
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.855
270054AF2-122 C O1
Solar/Wind Helper
1.473
253378AE2-206_GEN
Solar/Wind Helper
1.329
247522W1-056 GEN
Solar/Wind Helper
1.168
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.07
961051AF2-396 GEN
Solar/Wind Harmer
7.248
961051AF2-396 GEN
Solar/Wind Harmer
3.371
24721805FLATG3
50/50
1.059
962761AG1-125 GEN
Solar/Wind Harmer
77.975
970149AG2-104 GEN
Solar/Wind Harmer
48.149
970155AG2-107 GEN
Solar/Wind Harmer
34.001
972207SS24-0001
Solar/Wind Harmer
11.906
274773LINCOLN ;4U
Adder
3.349
274774LINCOLN ;5U
Adder
3.349
274723RIVER EC ;12
Adder
9.352
941551AE2-152 GEN
Solar/Wind Harmer
2.355
274802UNIV PARK;5U
Adder
3.024
274812UNIV PK N;8U
Adder
2.596
274751CRETE EC ;1U
Adder
2.531
274754CRETE EC ;4U
Adder
2.531
274676JOLIET 29;8U
Adder
15.866
274871GR RIDGE ;2U
Solar/Wind Harmer
3.971
274847GR RIDGE ;BU
Solar/Wind Harmer
2.611
274674JOLIET 9 ;6U
Adder
7.951
274732ELWOOD EC;7P
Adder
8.475
274745AC1-111 GEN9
Adder
2.877
274682WAUKEGAN ;7U
Adder
9.121
274828WAUKEGAN ;BP
Adder
5.599
276694AA1-018 GEN2
Solar/Wind Harmer
3.185
276691AA1-018 GEN1
Solar/Wind Harmer
0.381
962781AG1-127 GEN
Solar/Wind Harmer
4.798
274861TOP CROP ;1U
Solar/Wind Harmer
3.055
274872LEEDK;1U
Solar/Wind Harmer
4.133
939401AE1-172 GEN
Solar/Wind Harmer
6.957
276805AD2-038 GEN
Solar/Wind Harmer
2.558
970373AG2-245 GEN
Solar/Wind Harmer
10.446
971997AH1-543 GEN
Solar/Wind Harmer
7.83
276882AE2-255 GEN
Solar/Wind Harmer
1.677
957471AF2-041 GEN
Solar/Wind Harmer
14.863
959081AF2-199 GEN
Solar/Wind Harmer
4.954
971067AG2-660 GEN
Solar/Wind Harmer
1.152
274822ROCKFORD ;11
Adder
9.693
970819AG2-516 GEN
Solar/Wind Harmer
5.894
270055AF2-134 C O1
Solar/Wind Harmer
1.477
274858EASY ROAD;U2
Solar/Wind Harmer
2.326
274761LEE CO EC;2U
Adder
4.518
274766LEE CO EC;7U
Adder
4.465
970569AG2-363 GEN
Solar/Wind Harmer
14.559
270216AD2-079_GEN
Solar/Wind Harmer
0.293
957891AF2-083 GEN
Solar/Wind Harmer
7.188
958381AF2-132 GEN
Solar/Wind Harmer
4.344
276708O09 GEN2
Solar/Wind Harmer
1.712
964861AG1-349 GEN
Solar/Wind Harmer
3.757
971917AH1-482 GEN
Solar/Wind Harmer
4.335
276646AC1-214 GEN2
Solar/Wind Harmer
0.636
945111AF1-176 GEN
Solar/Wind Harmer
8.408
274848CAMPGROVE;RU
Solar/Wind Harmer
3.038
24639705ELKHART HY
Adder
0.071
270286AF1-227 GEN2
Solar/Wind Helper
2.348
270391AF1-285 GEN3
Solar/Wind Helper
1.04
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.963
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.2
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.159
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.703
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.347
962771AG1-126 GEN
Solar/Wind Harmer
77.975
970153AG2-106 GEN
Solar/Wind Harmer
34.001
971347AH1-153 GEN
Solar/Wind Harmer
2.894
274772LINCOLN ;3U
Adder
3.349
970707AG2-453 GEN
Solar/Wind Harmer
14.79
972259AH1-714 GEN
Adder
9.988
276164X3-005 C
Solar/Wind Harmer
0.367
274724RIVER EC ;11
Adder
9.248
274887GEN-1.85
Solar/Wind Harmer
2.769
276772AC2-154 GEN
Solar/Wind Harmer
1.45
276843GEN-1.7
Solar/Wind Harmer
0.298
276806AD2-047 C O1
Solar/Wind Harmer
5.56
274826FISK ;BP
Adder
5.687
939351AE1-166 GEN
Solar/Wind Harmer
3.079
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.024
274814UNIV PK N;0U
Adder
2.619
274807UNIV PK N;3U
Adder
2.613
274811UNIV PK N;7U
Adder
2.596
972231SS25-0005
Solar/Wind Harmer
4.914
972181SS23-001
Solar/Wind Harmer
3.071
274752CRETE EC ;2U
Adder
2.531
274753CRETE EC ;3U
Adder
2.531
274676JOLIET 29;8U
Adder
15.299
943121AE2-341 GEN
Solar/Wind Harmer
7.748
943591AF1-030 GEN
Solar/Wind Harmer
5.165
274729ELWOOD EC;1P
Adder
8.475
274730ELWOOD EC;6P
Adder
8.475
274734ELWOOD EC;8P
Adder
8.475
274736ELWOOD EC;9P
Adder
8.475
24441505OLIV SLR
Solar/Wind Harmer
0.068
274682WAUKEGAN ;7U
Adder
9.121
274862TOP CROP ;2U
Solar/Wind Harmer
2.551
276799AD1-013 GEN
Solar/Wind Harmer
1.102
946671AF1-331 GEN
Solar/Wind Harmer
0.209
274855GSG-6 ;RU
Solar/Wind Harmer
1.841
274850MENDOTA H;RU
Solar/Wind Harmer
1.28
276602WESTBROOK C
Solar/Wind Harmer
1.06
276868AE1-113 GEN
Solar/Wind Harmer
5.031
274879MINONK ;1U
Solar/Wind Harmer
3.354
959091AF2-200 GEN
Solar/Wind Harmer
9.909
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.326
274760LEE CO EC;1U
Adder
4.518
274767LEE CO EC;8U
Adder
4.465
970571AG2-364 GEN
Solar/Wind Harmer
9.706
276603SUBLETTE C
Solar/Wind Harmer
0.508
270505AE1-170 C O1
Solar/Wind Harmer
7.222
964401AG1-302 GEN
Solar/Wind Harmer
4.344
274851PROVIDENC;RU
Solar/Wind Harmer
1.352
274849CRESCENT ;1U
Solar/Wind Harmer
0.878
276782AC1-033 GEN
Solar/Wind Harmer
1.885
274878BISHOP HL;2U
Solar/Wind Harmer
1.595
945111AF1-176 GEN
Solar/Wind Harmer
2.665
270284AF1-227 GEN1
Solar/Wind Helper
6.403
270287AF1-227 GEN3
Solar/Wind Helper
2.348
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.844
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.128
960071AF2-298 GEN
Solar/Wind Helper
0.328
NYPJM->LTFIMP_NY
CLTF
0.905
LGEELTFEXP_LGEE->PJM
CLTF
0.829
WECLTFEXP_WEC->PJM
CLTF
1.879
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.534
CPLELTFEXP_CPLE->PJM
CLTF
1.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.767
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.305
MECLTFEXP_MEC->PJM
CLTF
7.06
SIGELTFEXP_SIGE->PJM
CLTF
0.115
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
5.461
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.255
TVALTFEXP_TVA->PJM
CLTF
2.432

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.32 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3323.61
MW Contribution:
7.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
15.73
970349AG2-230 GEN
Solar/Wind Harmer
8.682
274770LINCOLN ;1U
Adder
3.349
274771LINCOLN ;2U
Adder
3.349
965681AG1-436 GEN
Solar/Wind Harmer
6.562
965791AG1-447 GEN
Solar/Wind Harmer
3.357
274888KELLY CRK;1U
Solar/Wind Harmer
3.067
276776AD2-060 GEN
Solar/Wind Harmer
0.218
958011AF2-095 GEN
Solar/Wind Harmer
7.484
970941AG2-585 GEN
Solar/Wind Harmer
2.859
276897AD1-100 C
Solar/Wind Harmer
24.118
274805UNIV PK N;1U
Adder
2.602
274808UNIV PK N;4U
Adder
2.585
274674JOLIET 9 ;6U
Adder
7.951
276893AG1-478 C
Solar/Wind Harmer
0.226
274695ROCKY RD ;2P
Adder
5.665
274693ROCKY RD ;1P
Adder
5.61
274697ROCKY RD ;3P
Adder
1.539
274696ROCKY RD ;4P
Adder
5.799
274683WAUKEGAN ;8U
Adder
10.682
274683WAUKEGAN ;8U
Adder
9.005
962691AG1-118 GEN
Solar/Wind Harmer
15.173
958481AF2-142 GEN
Solar/Wind Harmer
7.571
960751AF2-366 GEN
Solar/Wind Harmer
1.448
958491AF2-143 GEN
Solar/Wind Harmer
7.484
276901AD2-066 C O1
Solar/Wind Harmer
1.749
971341AH1-150 GEN
Solar/Wind Harmer
9.909
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.347
962771AG1-126 GEN
Solar/Wind Harmer
77.975
970153AG2-106 GEN
Solar/Wind Harmer
34.001
971347AH1-153 GEN
Solar/Wind Harmer
2.894
274772LINCOLN ;3U
Adder
3.349
970707AG2-453 GEN
Solar/Wind Harmer
14.79
972259AH1-714 GEN
Adder
9.988
276164X3-005 C
Solar/Wind Harmer
0.367
274724RIVER EC ;11
Adder
9.248
274887GEN-1.85
Solar/Wind Harmer
2.769
276772AC2-154 GEN
Solar/Wind Harmer
1.45
276843GEN-1.7
Solar/Wind Harmer
0.298
276806AD2-047 C O1
Solar/Wind Harmer
5.56
274826FISK ;BP
Adder
5.687
939351AE1-166 GEN
Solar/Wind Harmer
3.079
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.024
274814UNIV PK N;0U
Adder
2.619
274807UNIV PK N;3U
Adder
2.613
274811UNIV PK N;7U
Adder
2.596
972231SS25-0005
Solar/Wind Harmer
4.914
972181SS23-001
Solar/Wind Harmer
3.071
274752CRETE EC ;2U
Adder
2.531
274753CRETE EC ;3U
Adder
2.531
274676JOLIET 29;8U
Adder
15.299
943121AE2-341 GEN
Solar/Wind Harmer
7.748
943591AF1-030 GEN
Solar/Wind Harmer
5.165
274729ELWOOD EC;1P
Adder
8.475
274730ELWOOD EC;6P
Adder
8.475
274734ELWOOD EC;8P
Adder
8.475
274736ELWOOD EC;9P
Adder
8.475
24441505OLIV SLR
Solar/Wind Harmer
0.068
274682WAUKEGAN ;7U
Adder
9.121
274862TOP CROP ;2U
Solar/Wind Harmer
2.551
276799AD1-013 GEN
Solar/Wind Harmer
1.102
946671AF1-331 GEN
Solar/Wind Harmer
0.209
274855GSG-6 ;RU
Solar/Wind Harmer
1.841
274850MENDOTA H;RU
Solar/Wind Harmer
1.28
276602WESTBROOK C
Solar/Wind Harmer
1.06
276868AE1-113 GEN
Solar/Wind Harmer
5.031
274879MINONK ;1U
Solar/Wind Harmer
3.354
971343AH1-151 GEN
Solar/Wind Harmer
9.909
972235AH1-702 GEN1
Adder
1.242
972236AH1-702 GEN2
Adder
1.08
276872AE1-163_GEN1
Solar/Wind Harmer
3.296
276876AE1-163_GEN2
Solar/Wind Harmer
3.296
270535AF1-215 GEN1
Solar/Wind Harmer
2.215
270536AF1-215 GEN2
Solar/Wind Harmer
2.215
938861AE1-114 GEN
Solar/Wind Harmer
3.995
274764LEE CO EC;5U
Adder
4.528
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
3.349
274776LINCOLN ;7U
Adder
3.349
274777LINCOLN ;8U
Adder
3.349
960681AF2-359 GEN
Solar/Wind Harmer
1.984
972228AH1-698 GEN2
Adder
1.928
972227AH1-698 GEN1
Adder
1.358
960591AF2-350 GEN
Solar/Wind Harmer
5.197
274827FISK ;RP
Adder
4.03
274800UNIV PARK;3U
Adder
3.027
274801UNIV PARK;4U
Adder
3.027
972037AH1-567 GEN1
Adder
0.095
274687WILL CNTY;4U
Adder
14.452
274687WILL CNTY;4U
Adder
14.452
274675JOLIET 29;7U
Adder
15.866
274675JOLIET 29;7U
Adder
15.3
970833AG2-524 GEN
Solar/Wind Harmer
4.51
970833AG2-524 GEN
Solar/Wind Harmer
2.098
274728ELWOOD EC;5P
Adder
8.475
274731ELWOOD EC;2P
Adder
8.475
274733ELWOOD EC;3P
Adder
8.475
274735ELWOOD EC;4P
Adder
8.475
276893AG1-478 C
Solar/Wind Harmer
0.283
274744AC1-111 GEN8
Adder
2.877
274746AC1-111 G10
Adder
2.877
270526AF1-158 GEN
Solar/Wind Harmer
2.303
971771AH1-392 GEN
Solar/Wind Harmer
4.514
970073AG2-061 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
8.977
276861AD2-134 GEN
Solar/Wind Harmer
0.89
276863AD2-134 GEN
Solar/Wind Harmer
0.89
971411AH1-196 GEN
Solar/Wind Harmer
7.478
971171AH1-044 GEN
Solar/Wind Harmer
9.909
274823ROCKFORD ;21
Adder
9.622
276889AE2-281 GEN
Solar/Wind Harmer
0.942
274863CRW1-WTG
Solar/Wind Harmer
2.739
274864CRW2-WTG
Solar/Wind Harmer
2.739
274856ECOGROVE ;U1
Solar/Wind Harmer
1.654
276611AD2-172 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
1.254
971681AH1-341 GEN
Solar/Wind Harmer
7.312
926823AC1-168 GEN
Solar/Wind Harmer
2.088
970169AG2-114 GEN
Solar/Wind Harmer
4.823
972267AH1-718 GEN
Adder
2.003
276741O09 GEN1
Solar/Wind Harmer
1.712
958391AF2-133 GEN
Solar/Wind Harmer
4.3
274877BISHOP HL;1U
Solar/Wind Harmer
1.595
959141AF2-205 GEN
Solar/Wind Harmer
2.844
270223U2-072_GEN1
Solar/Wind Helper
1.536
270224U2-072_GEN2
Solar/Wind Helper
1.536
270227U2-072_GEN3
Solar/Wind Helper
1.536
270228U2-072_GEN4
Solar/Wind Helper
1.536
270231U2-072_GEN5
Solar/Wind Helper
1.536
241973AD2-163_GEN1
Solar/Wind Helper
2.441
241974AD2-163_GEN2
Solar/Wind Helper
2.441
241955AC1-078 GEN
Solar/Wind Helper
2.436
945631AF1-228 GEN
Solar/Wind Helper
1.902
966831AG1-554 GEN
Solar/Wind Helper
0.869
253338AC1-165 GEN
Solar/Wind Helper
0.848
253343AC1-166 GEN
Solar/Wind Helper
0.848
241972AD1-140 GEN
Solar/Wind Helper
3.153
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.906
270263AC1-001 GEN
Solar/Wind Helper
0.555
270340AC2-060 GEN
Solar/Wind Helper
0.994
24721805FLATG3
50/50
1.059
962761AG1-125 GEN
Solar/Wind Harmer
77.975
970149AG2-104 GEN
Solar/Wind Harmer
48.149
970155AG2-107 GEN
Solar/Wind Harmer
34.001
972207SS24-0001
Solar/Wind Harmer
11.906
274773LINCOLN ;4U
Adder
3.349
274774LINCOLN ;5U
Adder
3.349
274723RIVER EC ;12
Adder
9.352
941551AE2-152 GEN
Solar/Wind Harmer
2.355
274802UNIV PARK;5U
Adder
3.024
274812UNIV PK N;8U
Adder
2.596
274751CRETE EC ;1U
Adder
2.531
274754CRETE EC ;4U
Adder
2.531
274676JOLIET 29;8U
Adder
15.866
274871GR RIDGE ;2U
Solar/Wind Harmer
3.971
274847GR RIDGE ;BU
Solar/Wind Harmer
2.611
274674JOLIET 9 ;6U
Adder
7.951
274732ELWOOD EC;7P
Adder
8.475
274745AC1-111 GEN9
Adder
2.877
274682WAUKEGAN ;7U
Adder
9.121
274828WAUKEGAN ;BP
Adder
5.599
276694AA1-018 GEN2
Solar/Wind Harmer
3.185
276691AA1-018 GEN1
Solar/Wind Harmer
0.381
962781AG1-127 GEN
Solar/Wind Harmer
4.798
274861TOP CROP ;1U
Solar/Wind Harmer
3.055
274872LEEDK;1U
Solar/Wind Harmer
4.133
939401AE1-172 GEN
Solar/Wind Harmer
6.957
276805AD2-038 GEN
Solar/Wind Harmer
2.558
970373AG2-245 GEN
Solar/Wind Harmer
10.446
971997AH1-543 GEN
Solar/Wind Harmer
7.83
276882AE2-255 GEN
Solar/Wind Harmer
1.677
957471AF2-041 GEN
Solar/Wind Harmer
14.863
959081AF2-199 GEN
Solar/Wind Harmer
4.954
971067AG2-660 GEN
Solar/Wind Harmer
1.152
274822ROCKFORD ;11
Adder
9.693
970819AG2-516 GEN
Solar/Wind Harmer
5.894
270055AF2-134 C O1
Solar/Wind Harmer
1.477
274858EASY ROAD;U2
Solar/Wind Harmer
2.326
274761LEE CO EC;2U
Adder
4.518
274766LEE CO EC;7U
Adder
4.465
970569AG2-363 GEN
Solar/Wind Harmer
14.559
270216AD2-079_GEN
Solar/Wind Harmer
0.293
957891AF2-083 GEN
Solar/Wind Harmer
7.188
958381AF2-132 GEN
Solar/Wind Harmer
4.344
276708O09 GEN2
Solar/Wind Harmer
1.712
964861AG1-349 GEN
Solar/Wind Harmer
3.757
971917AH1-482 GEN
Solar/Wind Harmer
4.335
276646AC1-214 GEN2
Solar/Wind Harmer
0.636
945111AF1-176 GEN
Solar/Wind Harmer
8.408
959091AF2-200 GEN
Solar/Wind Harmer
9.909
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.326
274760LEE CO EC;1U
Adder
4.518
274767LEE CO EC;8U
Adder
4.465
970571AG2-364 GEN
Solar/Wind Harmer
9.706
276603SUBLETTE C
Solar/Wind Harmer
0.508
270505AE1-170 C O1
Solar/Wind Harmer
7.222
964401AG1-302 GEN
Solar/Wind Harmer
4.344
274851PROVIDENC;RU
Solar/Wind Harmer
1.352
274849CRESCENT ;1U
Solar/Wind Harmer
0.878
276782AC1-033 GEN
Solar/Wind Harmer
1.885
274878BISHOP HL;2U
Solar/Wind Harmer
1.595
945111AF1-176 GEN
Solar/Wind Harmer
2.665
270284AF1-227 GEN1
Solar/Wind Helper
6.403
270287AF1-227 GEN3
Solar/Wind Helper
2.348
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.844
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
274765LEE CO EC;6U
Adder
4.528
274762LEE CO EC;3U
Adder
4.518
274763LEE CO EC;4U
Adder
4.475
276158O29GEN2
Solar/Wind Harmer
2.397
276157O29GEN1
Solar/Wind Harmer
1.823
276645AC1-214 GEN1
Solar/Wind Harmer
0.636
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.705
270471AD2-092_GEN
Solar/Wind Helper
4.705
270462AD2-086
Solar/Wind Helper
5.394
253383AE2-342_GEN
Solar/Wind Helper
1.128
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.855
270054AF2-122 C O1
Solar/Wind Helper
1.473
253378AE2-206_GEN
Solar/Wind Helper
1.329
247522W1-056 GEN
Solar/Wind Helper
1.168
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.07
961051AF2-396 GEN
Solar/Wind Harmer
7.248
961051AF2-396 GEN
Solar/Wind Harmer
3.371
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.128
960071AF2-298 GEN
Solar/Wind Helper
0.328
274848CAMPGROVE;RU
Solar/Wind Harmer
3.038
24639705ELKHART HY
Adder
0.071
270286AF1-227 GEN2
Solar/Wind Helper
2.348
270391AF1-285 GEN3
Solar/Wind Helper
1.04
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.963
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.2
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.159
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.703
NYPJM->LTFIMP_NY
CLTF
0.905
LGEELTFEXP_LGEE->PJM
CLTF
0.829
WECLTFEXP_WEC->PJM
CLTF
1.879
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.534
CPLELTFEXP_CPLE->PJM
CLTF
1.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.305
MECLTFEXP_MEC->PJM
CLTF
7.06
SIGELTFEXP_SIGE->PJM
CLTF
0.115
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.767
LAGNLTFEXP_LAGN->PJM
CLTF
5.461
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.255
TVALTFEXP_TVA->PJM
CLTF
2.432

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.26 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3321.91
MW Contribution:
7.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
3.347
274776LINCOLN ;7U
Adder
3.347
274777LINCOLN ;8U
Adder
3.347
960681AF2-359 GEN
Solar/Wind Harmer
1.983
972228AH1-698 GEN2
Adder
1.927
972227AH1-698 GEN1
Adder
1.357
960591AF2-350 GEN
Solar/Wind Harmer
5.195
274827FISK ;RP
Adder
4.028
274800UNIV PARK;3U
Adder
3.025
274801UNIV PARK;4U
Adder
3.025
972037AH1-567 GEN1
Adder
0.095
274687WILL CNTY;4U
Adder
14.443
274687WILL CNTY;4U
Adder
14.443
274675JOLIET 29;7U
Adder
15.857
274675JOLIET 29;7U
Adder
15.291
970833AG2-524 GEN
Solar/Wind Harmer
4.507
970833AG2-524 GEN
Solar/Wind Harmer
2.096
274728ELWOOD EC;5P
Adder
8.47
274731ELWOOD EC;2P
Adder
8.47
274733ELWOOD EC;3P
Adder
8.47
274735ELWOOD EC;4P
Adder
8.47
276893AG1-478 C
Solar/Wind Harmer
0.283
274744AC1-111 GEN8
Adder
2.876
274746AC1-111 G10
Adder
2.876
270526AF1-158 GEN
Solar/Wind Harmer
2.302
971771AH1-392 GEN
Solar/Wind Harmer
4.511
970073AG2-061 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
8.972
276861AD2-134 GEN
Solar/Wind Harmer
0.89
276863AD2-134 GEN
Solar/Wind Harmer
0.89
971411AH1-196 GEN
Solar/Wind Harmer
7.473
971171AH1-044 GEN
Solar/Wind Harmer
9.903
274823ROCKFORD ;21
Adder
9.617
276889AE2-281 GEN
Solar/Wind Harmer
0.941
274863CRW1-WTG
Solar/Wind Harmer
2.738
274864CRW2-WTG
Solar/Wind Harmer
2.738
274856ECOGROVE ;U1
Solar/Wind Harmer
1.653
276611AD2-172 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
1.254
971681AH1-341 GEN
Solar/Wind Harmer
7.308
926823AC1-168 GEN
Solar/Wind Harmer
2.087
970169AG2-114 GEN
Solar/Wind Harmer
4.82
972267AH1-718 GEN
Adder
2.001
276741O09 GEN1
Solar/Wind Harmer
1.711
958391AF2-133 GEN
Solar/Wind Harmer
4.297
274877BISHOP HL;1U
Solar/Wind Harmer
1.594
959141AF2-205 GEN
Solar/Wind Harmer
2.842
270223U2-072_GEN1
Solar/Wind Helper
1.536
270224U2-072_GEN2
Solar/Wind Helper
1.536
270227U2-072_GEN3
Solar/Wind Helper
1.536
270228U2-072_GEN4
Solar/Wind Helper
1.536
270231U2-072_GEN5
Solar/Wind Helper
1.536
241973AD2-163_GEN1
Solar/Wind Helper
2.443
241974AD2-163_GEN2
Solar/Wind Helper
2.443
241955AC1-078 GEN
Solar/Wind Helper
2.437
945631AF1-228 GEN
Solar/Wind Helper
1.903
966831AG1-554 GEN
Solar/Wind Helper
0.87
253338AC1-165 GEN
Solar/Wind Helper
0.848
253343AC1-166 GEN
Solar/Wind Helper
0.848
241972AD1-140 GEN
Solar/Wind Helper
3.155
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.907
270263AC1-001 GEN
Solar/Wind Helper
0.555
270340AC2-060 GEN
Solar/Wind Helper
0.994
24721705FLATG2
50/50
15.728
970349AG2-230 GEN
Solar/Wind Harmer
8.677
274770LINCOLN ;1U
Adder
3.347
274771LINCOLN ;2U
Adder
3.347
965681AG1-436 GEN
Solar/Wind Harmer
6.558
965791AG1-447 GEN
Solar/Wind Harmer
3.355
274888KELLY CRK;1U
Solar/Wind Harmer
3.065
276776AD2-060 GEN
Solar/Wind Harmer
0.217
958011AF2-095 GEN
Solar/Wind Harmer
7.48
970941AG2-585 GEN
Solar/Wind Harmer
2.857
276897AD1-100 C
Solar/Wind Harmer
24.104
274805UNIV PK N;1U
Adder
2.6
274808UNIV PK N;4U
Adder
2.583
274674JOLIET 9 ;6U
Adder
7.946
276893AG1-478 C
Solar/Wind Harmer
0.226
274696ROCKY RD ;4P
Adder
5.796
274695ROCKY RD ;2P
Adder
5.662
274693ROCKY RD ;1P
Adder
5.606
274697ROCKY RD ;3P
Adder
1.538
274683WAUKEGAN ;8U
Adder
10.676
274683WAUKEGAN ;8U
Adder
8.999
962691AG1-118 GEN
Solar/Wind Harmer
15.164
958481AF2-142 GEN
Solar/Wind Harmer
7.567
960751AF2-366 GEN
Solar/Wind Harmer
1.447
958491AF2-143 GEN
Solar/Wind Harmer
7.479
276901AD2-066 C O1
Solar/Wind Harmer
1.748
971341AH1-150 GEN
Solar/Wind Harmer
9.903
971343AH1-151 GEN
Solar/Wind Harmer
9.903
972235AH1-702 GEN1
Adder
1.241
972236AH1-702 GEN2
Adder
1.079
276872AE1-163_GEN1
Solar/Wind Harmer
3.294
276876AE1-163_GEN2
Solar/Wind Harmer
3.294
270535AF1-215 GEN1
Solar/Wind Harmer
2.214
270536AF1-215 GEN2
Solar/Wind Harmer
2.214
938861AE1-114 GEN
Solar/Wind Harmer
3.993
274764LEE CO EC;5U
Adder
4.526
274765LEE CO EC;6U
Adder
4.526
274762LEE CO EC;3U
Adder
4.515
274763LEE CO EC;4U
Adder
4.473
276158O29GEN2
Solar/Wind Harmer
2.396
276157O29GEN1
Solar/Wind Harmer
1.821
276645AC1-214 GEN1
Solar/Wind Harmer
0.636
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.707
270471AD2-092_GEN
Solar/Wind Helper
4.707
270462AD2-086
Solar/Wind Helper
5.396
253383AE2-342_GEN
Solar/Wind Helper
1.129
946101AF1-275 GEN
Solar/Wind Helper
0.801
241960AC2-195 GEN
Solar/Wind Helper
1.856
270054AF2-122 C O1
Solar/Wind Helper
1.472
253378AE2-206_GEN
Solar/Wind Helper
1.33
247522W1-056 GEN
Solar/Wind Helper
1.168
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.07
961051AF2-396 GEN
Solar/Wind Harmer
7.243
961051AF2-396 GEN
Solar/Wind Harmer
3.369
24721805FLATG3
50/50
1.059
962761AG1-125 GEN
Solar/Wind Harmer
77.959
970149AG2-104 GEN
Solar/Wind Harmer
48.14
970155AG2-107 GEN
Solar/Wind Harmer
33.994
972207SS24-0001
Solar/Wind Harmer
11.9
274773LINCOLN ;4U
Adder
3.347
274774LINCOLN ;5U
Adder
3.347
274723RIVER EC ;12
Adder
9.347
941551AE2-152 GEN
Solar/Wind Harmer
2.353
274802UNIV PARK;5U
Adder
3.023
274812UNIV PK N;8U
Adder
2.595
274751CRETE EC ;1U
Adder
2.529
274754CRETE EC ;4U
Adder
2.529
274676JOLIET 29;8U
Adder
15.857
274871GR RIDGE ;2U
Solar/Wind Harmer
3.969
274847GR RIDGE ;BU
Solar/Wind Harmer
2.61
274674JOLIET 9 ;6U
Adder
7.946
274732ELWOOD EC;7P
Adder
8.47
274745AC1-111 GEN9
Adder
2.876
274682WAUKEGAN ;7U
Adder
9.116
274828WAUKEGAN ;BP
Adder
5.596
276694AA1-018 GEN2
Solar/Wind Harmer
3.183
276691AA1-018 GEN1
Solar/Wind Harmer
0.38
962781AG1-127 GEN
Solar/Wind Harmer
4.796
274861TOP CROP ;1U
Solar/Wind Harmer
3.054
274872LEEDK;1U
Solar/Wind Harmer
4.131
939401AE1-172 GEN
Solar/Wind Harmer
6.953
276805AD2-038 GEN
Solar/Wind Harmer
2.557
971997AH1-543 GEN
Solar/Wind Harmer
7.825
970373AG2-245 GEN
Solar/Wind Harmer
10.44
276882AE2-255 GEN
Solar/Wind Harmer
1.676
957471AF2-041 GEN
Solar/Wind Harmer
14.855
959081AF2-199 GEN
Solar/Wind Harmer
4.952
971067AG2-660 GEN
Solar/Wind Harmer
1.152
274822ROCKFORD ;11
Adder
9.687
970819AG2-516 GEN
Solar/Wind Harmer
5.891
270055AF2-134 C O1
Solar/Wind Harmer
1.476
274858EASY ROAD;U2
Solar/Wind Harmer
2.325
274761LEE CO EC;2U
Adder
4.515
274766LEE CO EC;7U
Adder
4.462
970569AG2-363 GEN
Solar/Wind Harmer
14.55
270216AD2-079_GEN
Solar/Wind Harmer
0.292
957891AF2-083 GEN
Solar/Wind Harmer
7.184
958381AF2-132 GEN
Solar/Wind Harmer
4.341
276708O09 GEN2
Solar/Wind Harmer
1.711
964861AG1-349 GEN
Solar/Wind Harmer
3.755
971917AH1-482 GEN
Solar/Wind Harmer
4.332
276646AC1-214 GEN2
Solar/Wind Harmer
0.636
945111AF1-176 GEN
Solar/Wind Harmer
8.403
274848CAMPGROVE;RU
Solar/Wind Harmer
3.037
24639705ELKHART HY
Adder
0.071
270286AF1-227 GEN2
Solar/Wind Helper
2.349
270391AF1-285 GEN3
Solar/Wind Helper
1.04
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.965
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.202
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.16
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.703
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.344
962771AG1-126 GEN
Solar/Wind Harmer
77.959
970153AG2-106 GEN
Solar/Wind Harmer
33.994
971347AH1-153 GEN
Solar/Wind Harmer
2.892
274772LINCOLN ;3U
Adder
3.347
970707AG2-453 GEN
Solar/Wind Harmer
14.782
972259AH1-714 GEN
Adder
9.982
276164X3-005 C
Solar/Wind Harmer
0.367
274724RIVER EC ;11
Adder
9.243
274887GEN-1.85
Solar/Wind Harmer
2.768
276772AC2-154 GEN
Solar/Wind Harmer
1.45
276843GEN-1.7
Solar/Wind Harmer
0.298
276806AD2-047 C O1
Solar/Wind Harmer
5.557
274826FISK ;BP
Adder
5.683
939351AE1-166 GEN
Solar/Wind Harmer
3.077
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.023
274814UNIV PK N;0U
Adder
2.617
274807UNIV PK N;3U
Adder
2.612
274811UNIV PK N;7U
Adder
2.595
972231SS25-0005
Solar/Wind Harmer
4.911
972181SS23-001
Solar/Wind Harmer
3.069
274752CRETE EC ;2U
Adder
2.529
274753CRETE EC ;3U
Adder
2.529
274676JOLIET 29;8U
Adder
15.29
943121AE2-341 GEN
Solar/Wind Harmer
7.744
943591AF1-030 GEN
Solar/Wind Harmer
5.163
274729ELWOOD EC;1P
Adder
8.47
274730ELWOOD EC;6P
Adder
8.47
274734ELWOOD EC;8P
Adder
8.47
274736ELWOOD EC;9P
Adder
8.47
24441505OLIV SLR
Solar/Wind Harmer
0.068
274682WAUKEGAN ;7U
Adder
9.116
274862TOP CROP ;2U
Solar/Wind Harmer
2.55
276799AD1-013 GEN
Solar/Wind Harmer
1.102
946671AF1-331 GEN
Solar/Wind Harmer
0.209
274855GSG-6 ;RU
Solar/Wind Harmer
1.84
274850MENDOTA H;RU
Solar/Wind Harmer
1.279
276602WESTBROOK C
Solar/Wind Harmer
1.059
276868AE1-113 GEN
Solar/Wind Harmer
5.028
274879MINONK ;1U
Solar/Wind Harmer
3.352
959091AF2-200 GEN
Solar/Wind Harmer
9.903
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.325
274760LEE CO EC;1U
Adder
4.515
274767LEE CO EC;8U
Adder
4.462
970571AG2-364 GEN
Solar/Wind Harmer
9.7
276603SUBLETTE C
Solar/Wind Harmer
0.508
270505AE1-170 C O1
Solar/Wind Harmer
7.217
964401AG1-302 GEN
Solar/Wind Harmer
4.341
274851PROVIDENC;RU
Solar/Wind Harmer
1.352
274849CRESCENT ;1U
Solar/Wind Harmer
0.877
276782AC1-033 GEN
Solar/Wind Harmer
1.884
274878BISHOP HL;2U
Solar/Wind Harmer
1.594
945111AF1-176 GEN
Solar/Wind Harmer
2.663
270284AF1-227 GEN1
Solar/Wind Helper
6.406
270287AF1-227 GEN3
Solar/Wind Helper
2.349
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.848
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.129
960071AF2-298 GEN
Solar/Wind Helper
0.328
NYPJM->LTFIMP_NY
CLTF
0.904
LGEELTFEXP_LGEE->PJM
CLTF
0.828
WECLTFEXP_WEC->PJM
CLTF
1.878
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.496
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.299
CPLELTFEXP_CPLE->PJM
CLTF
1.537
MECLTFEXP_MEC->PJM
CLTF
7.056
SIGELTFEXP_SIGE->PJM
CLTF
0.115
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.741
LAGNLTFEXP_LAGN->PJM
CLTF
5.458
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.254
TVALTFEXP_TVA->PJM
CLTF
2.431

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.26 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3321.72
MW Contribution:
7.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
3.347
274776LINCOLN ;7U
Adder
3.347
274777LINCOLN ;8U
Adder
3.347
960681AF2-359 GEN
Solar/Wind Harmer
1.982
972228AH1-698 GEN2
Adder
1.927
972227AH1-698 GEN1
Adder
1.357
960591AF2-350 GEN
Solar/Wind Harmer
5.194
274827FISK ;RP
Adder
4.028
274800UNIV PARK;3U
Adder
3.025
274801UNIV PARK;4U
Adder
3.025
972037AH1-567 GEN1
Adder
0.095
274687WILL CNTY;4U
Adder
14.442
274687WILL CNTY;4U
Adder
14.442
274675JOLIET 29;7U
Adder
15.856
274675JOLIET 29;7U
Adder
15.29
970833AG2-524 GEN
Solar/Wind Harmer
4.507
970833AG2-524 GEN
Solar/Wind Harmer
2.096
274728ELWOOD EC;5P
Adder
8.469
274731ELWOOD EC;2P
Adder
8.469
274733ELWOOD EC;3P
Adder
8.469
274735ELWOOD EC;4P
Adder
8.469
276893AG1-478 C
Solar/Wind Harmer
0.283
274744AC1-111 GEN8
Adder
2.876
274746AC1-111 G10
Adder
2.876
270526AF1-158 GEN
Solar/Wind Harmer
2.302
971771AH1-392 GEN
Solar/Wind Harmer
4.511
970073AG2-061 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
8.971
276861AD2-134 GEN
Solar/Wind Harmer
0.89
276863AD2-134 GEN
Solar/Wind Harmer
0.89
971411AH1-196 GEN
Solar/Wind Harmer
7.473
971171AH1-044 GEN
Solar/Wind Harmer
9.902
274823ROCKFORD ;21
Adder
9.616
276889AE2-281 GEN
Solar/Wind Harmer
0.941
274863CRW1-WTG
Solar/Wind Harmer
2.737
274864CRW2-WTG
Solar/Wind Harmer
2.737
274856ECOGROVE ;U1
Solar/Wind Harmer
1.653
276611AD2-172 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
1.254
971681AH1-341 GEN
Solar/Wind Harmer
7.307
926823AC1-168 GEN
Solar/Wind Harmer
2.087
970169AG2-114 GEN
Solar/Wind Harmer
4.819
972267AH1-718 GEN
Adder
2.001
276741O09 GEN1
Solar/Wind Harmer
1.71
958391AF2-133 GEN
Solar/Wind Harmer
4.297
274877BISHOP HL;1U
Solar/Wind Harmer
1.594
959141AF2-205 GEN
Solar/Wind Harmer
2.842
270223U2-072_GEN1
Solar/Wind Helper
1.536
270224U2-072_GEN2
Solar/Wind Helper
1.536
270227U2-072_GEN3
Solar/Wind Helper
1.536
270228U2-072_GEN4
Solar/Wind Helper
1.536
270231U2-072_GEN5
Solar/Wind Helper
1.536
241973AD2-163_GEN1
Solar/Wind Helper
2.443
241974AD2-163_GEN2
Solar/Wind Helper
2.443
241955AC1-078 GEN
Solar/Wind Helper
2.437
945631AF1-228 GEN
Solar/Wind Helper
1.903
966831AG1-554 GEN
Solar/Wind Helper
0.87
253338AC1-165 GEN
Solar/Wind Helper
0.848
253343AC1-166 GEN
Solar/Wind Helper
0.848
241972AD1-140 GEN
Solar/Wind Helper
3.156
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.907
270263AC1-001 GEN
Solar/Wind Helper
0.555
270340AC2-060 GEN
Solar/Wind Helper
0.994
24721705FLATG2
50/50
15.727
970349AG2-230 GEN
Solar/Wind Harmer
8.676
274770LINCOLN ;1U
Adder
3.347
274771LINCOLN ;2U
Adder
3.347
965681AG1-436 GEN
Solar/Wind Harmer
6.558
965791AG1-447 GEN
Solar/Wind Harmer
3.355
274888KELLY CRK;1U
Solar/Wind Harmer
3.065
276776AD2-060 GEN
Solar/Wind Harmer
0.217
958011AF2-095 GEN
Solar/Wind Harmer
7.48
970941AG2-585 GEN
Solar/Wind Harmer
2.857
276897AD1-100 C
Solar/Wind Harmer
24.103
274805UNIV PK N;1U
Adder
2.6
274808UNIV PK N;4U
Adder
2.583
274674JOLIET 9 ;6U
Adder
7.946
276893AG1-478 C
Solar/Wind Harmer
0.226
274695ROCKY RD ;2P
Adder
5.662
274693ROCKY RD ;1P
Adder
5.606
274697ROCKY RD ;3P
Adder
1.538
274696ROCKY RD ;4P
Adder
5.795
274683WAUKEGAN ;8U
Adder
10.675
274683WAUKEGAN ;8U
Adder
8.999
962691AG1-118 GEN
Solar/Wind Harmer
15.163
958481AF2-142 GEN
Solar/Wind Harmer
7.566
960751AF2-366 GEN
Solar/Wind Harmer
1.447
958491AF2-143 GEN
Solar/Wind Harmer
7.479
276901AD2-066 C O1
Solar/Wind Harmer
1.748
971341AH1-150 GEN
Solar/Wind Harmer
9.902
971343AH1-151 GEN
Solar/Wind Harmer
9.902
972235AH1-702 GEN1
Adder
1.241
972236AH1-702 GEN2
Adder
1.079
276872AE1-163_GEN1
Solar/Wind Harmer
3.294
276876AE1-163_GEN2
Solar/Wind Harmer
3.294
270535AF1-215 GEN1
Solar/Wind Harmer
2.213
270536AF1-215 GEN2
Solar/Wind Harmer
2.213
938861AE1-114 GEN
Solar/Wind Harmer
3.992
274764LEE CO EC;5U
Adder
4.526
24721805FLATG3
50/50
1.059
962761AG1-125 GEN
Solar/Wind Harmer
77.957
970149AG2-104 GEN
Solar/Wind Harmer
48.139
970155AG2-107 GEN
Solar/Wind Harmer
33.993
972207SS24-0001
Solar/Wind Harmer
11.899
274773LINCOLN ;4U
Adder
3.347
274774LINCOLN ;5U
Adder
3.347
274723RIVER EC ;12
Adder
9.346
941551AE2-152 GEN
Solar/Wind Harmer
2.353
274802UNIV PARK;5U
Adder
3.023
274812UNIV PK N;8U
Adder
2.594
274751CRETE EC ;1U
Adder
2.529
274754CRETE EC ;4U
Adder
2.529
274676JOLIET 29;8U
Adder
15.856
274871GR RIDGE ;2U
Solar/Wind Harmer
3.969
274847GR RIDGE ;BU
Solar/Wind Harmer
2.61
274674JOLIET 9 ;6U
Adder
7.946
274732ELWOOD EC;7P
Adder
8.469
274745AC1-111 GEN9
Adder
2.876
274682WAUKEGAN ;7U
Adder
9.115
274828WAUKEGAN ;BP
Adder
5.596
276694AA1-018 GEN2
Solar/Wind Harmer
3.183
276691AA1-018 GEN1
Solar/Wind Harmer
0.38
962781AG1-127 GEN
Solar/Wind Harmer
4.795
274861TOP CROP ;1U
Solar/Wind Harmer
3.053
274872LEEDK;1U
Solar/Wind Harmer
4.13
939401AE1-172 GEN
Solar/Wind Harmer
6.952
276805AD2-038 GEN
Solar/Wind Harmer
2.557
970373AG2-245 GEN
Solar/Wind Harmer
10.439
971997AH1-543 GEN
Solar/Wind Harmer
7.825
276882AE2-255 GEN
Solar/Wind Harmer
1.676
957471AF2-041 GEN
Solar/Wind Harmer
14.854
959081AF2-199 GEN
Solar/Wind Harmer
4.951
971067AG2-660 GEN
Solar/Wind Harmer
1.151
274822ROCKFORD ;11
Adder
9.686
970819AG2-516 GEN
Solar/Wind Harmer
5.891
270055AF2-134 C O1
Solar/Wind Harmer
1.476
274858EASY ROAD;U2
Solar/Wind Harmer
2.325
274761LEE CO EC;2U
Adder
4.515
274766LEE CO EC;7U
Adder
4.462
970569AG2-363 GEN
Solar/Wind Harmer
14.549
270216AD2-079_GEN
Solar/Wind Harmer
0.292
957891AF2-083 GEN
Solar/Wind Harmer
7.183
958381AF2-132 GEN
Solar/Wind Harmer
4.341
276708O09 GEN2
Solar/Wind Harmer
1.71
964861AG1-349 GEN
Solar/Wind Harmer
3.754
971917AH1-482 GEN
Solar/Wind Harmer
4.332
276646AC1-214 GEN2
Solar/Wind Harmer
0.636
945111AF1-176 GEN
Solar/Wind Harmer
8.402
274848CAMPGROVE;RU
Solar/Wind Harmer
3.036
24639705ELKHART HY
Adder
0.071
270286AF1-227 GEN2
Solar/Wind Helper
2.349
270391AF1-285 GEN3
Solar/Wind Helper
1.04
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.966
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.203
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.16
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.703
274765LEE CO EC;6U
Adder
4.526
274762LEE CO EC;3U
Adder
4.515
274763LEE CO EC;4U
Adder
4.472
276158O29GEN2
Solar/Wind Harmer
2.396
276157O29GEN1
Solar/Wind Harmer
1.821
276645AC1-214 GEN1
Solar/Wind Harmer
0.636
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.707
270471AD2-092_GEN
Solar/Wind Helper
4.707
270462AD2-086
Solar/Wind Helper
5.396
253383AE2-342_GEN
Solar/Wind Helper
1.129
946101AF1-275 GEN
Solar/Wind Helper
0.801
241960AC2-195 GEN
Solar/Wind Helper
1.856
270054AF2-122 C O1
Solar/Wind Helper
1.471
253378AE2-206_GEN
Solar/Wind Helper
1.33
247522W1-056 GEN
Solar/Wind Helper
1.168
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.07
961051AF2-396 GEN
Solar/Wind Harmer
7.242
961051AF2-396 GEN
Solar/Wind Harmer
3.368
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.344
962771AG1-126 GEN
Solar/Wind Harmer
77.957
970153AG2-106 GEN
Solar/Wind Harmer
33.993
971347AH1-153 GEN
Solar/Wind Harmer
2.892
274772LINCOLN ;3U
Adder
3.347
970707AG2-453 GEN
Solar/Wind Harmer
14.781
972259AH1-714 GEN
Adder
9.981
276164X3-005 C
Solar/Wind Harmer
0.367
274724RIVER EC ;11
Adder
9.242
274887GEN-1.85
Solar/Wind Harmer
2.767
276772AC2-154 GEN
Solar/Wind Harmer
1.45
276843GEN-1.7
Solar/Wind Harmer
0.298
276806AD2-047 C O1
Solar/Wind Harmer
5.557
274826FISK ;BP
Adder
5.683
939351AE1-166 GEN
Solar/Wind Harmer
3.077
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.023
274814UNIV PK N;0U
Adder
2.617
274807UNIV PK N;3U
Adder
2.611
274811UNIV PK N;7U
Adder
2.594
972231SS25-0005
Solar/Wind Harmer
4.91
972181SS23-001
Solar/Wind Harmer
3.069
274752CRETE EC ;2U
Adder
2.529
274753CRETE EC ;3U
Adder
2.529
274676JOLIET 29;8U
Adder
15.289
943121AE2-341 GEN
Solar/Wind Harmer
7.743
943591AF1-030 GEN
Solar/Wind Harmer
5.162
274729ELWOOD EC;1P
Adder
8.469
274730ELWOOD EC;6P
Adder
8.469
274734ELWOOD EC;8P
Adder
8.469
274736ELWOOD EC;9P
Adder
8.469
24441505OLIV SLR
Solar/Wind Harmer
0.068
274682WAUKEGAN ;7U
Adder
9.115
274862TOP CROP ;2U
Solar/Wind Harmer
2.549
276799AD1-013 GEN
Solar/Wind Harmer
1.102
946671AF1-331 GEN
Solar/Wind Harmer
0.209
274855GSG-6 ;RU
Solar/Wind Harmer
1.84
274850MENDOTA H;RU
Solar/Wind Harmer
1.279
276602WESTBROOK C
Solar/Wind Harmer
1.059
276868AE1-113 GEN
Solar/Wind Harmer
5.028
274879MINONK ;1U
Solar/Wind Harmer
3.352
959091AF2-200 GEN
Solar/Wind Harmer
9.902
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.325
274760LEE CO EC;1U
Adder
4.515
274767LEE CO EC;8U
Adder
4.462
970571AG2-364 GEN
Solar/Wind Harmer
9.7
276603SUBLETTE C
Solar/Wind Harmer
0.508
270505AE1-170 C O1
Solar/Wind Harmer
7.217
964401AG1-302 GEN
Solar/Wind Harmer
4.341
274851PROVIDENC;RU
Solar/Wind Harmer
1.352
274849CRESCENT ;1U
Solar/Wind Harmer
0.877
276782AC1-033 GEN
Solar/Wind Harmer
1.884
274878BISHOP HL;2U
Solar/Wind Harmer
1.594
945111AF1-176 GEN
Solar/Wind Harmer
2.663
270284AF1-227 GEN1
Solar/Wind Helper
6.406
270287AF1-227 GEN3
Solar/Wind Helper
2.349
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.849
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.129
960071AF2-298 GEN
Solar/Wind Helper
0.328
NYPJM->LTFIMP_NY
CLTF
0.904
LGEELTFEXP_LGEE->PJM
CLTF
0.828
WECLTFEXP_WEC->PJM
CLTF
1.878
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.492
CPLELTFEXP_CPLE->PJM
CLTF
1.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.738
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.298
MECLTFEXP_MEC->PJM
CLTF
7.055
SIGELTFEXP_SIGE->PJM
CLTF
0.115
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
5.458
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.253
TVALTFEXP_TVA->PJM
CLTF
2.431

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.23 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3320.78
MW Contribution:
7.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
3.346
274776LINCOLN ;7U
Adder
3.346
274777LINCOLN ;8U
Adder
3.346
960681AF2-359 GEN
Solar/Wind Harmer
1.982
972228AH1-698 GEN2
Adder
1.926
972227AH1-698 GEN1
Adder
1.356
960591AF2-350 GEN
Solar/Wind Harmer
5.193
274827FISK ;RP
Adder
4.026
274800UNIV PARK;3U
Adder
3.024
274801UNIV PARK;4U
Adder
3.024
972037AH1-567 GEN1
Adder
0.095
274675JOLIET 29;7U
Adder
15.851
274675JOLIET 29;7U
Adder
15.285
274687WILL CNTY;4U
Adder
14.438
274687WILL CNTY;4U
Adder
14.438
970833AG2-524 GEN
Solar/Wind Harmer
4.506
970833AG2-524 GEN
Solar/Wind Harmer
2.096
274728ELWOOD EC;5P
Adder
8.467
274731ELWOOD EC;2P
Adder
8.467
274733ELWOOD EC;3P
Adder
8.467
274735ELWOOD EC;4P
Adder
8.467
276893AG1-478 C
Solar/Wind Harmer
0.283
274744AC1-111 GEN8
Adder
2.875
274746AC1-111 G10
Adder
2.875
270526AF1-158 GEN
Solar/Wind Harmer
2.301
971771AH1-392 GEN
Solar/Wind Harmer
4.509
970073AG2-061 GEN
Solar/Wind Harmer
1.159
971675AH1-338 GEN
Solar/Wind Harmer
8.968
276861AD2-134 GEN
Solar/Wind Harmer
0.889
276863AD2-134 GEN
Solar/Wind Harmer
0.889
971411AH1-196 GEN
Solar/Wind Harmer
7.471
971171AH1-044 GEN
Solar/Wind Harmer
9.899
274823ROCKFORD ;21
Adder
9.613
276889AE2-281 GEN
Solar/Wind Harmer
0.941
274863CRW1-WTG
Solar/Wind Harmer
2.737
274864CRW2-WTG
Solar/Wind Harmer
2.737
274856ECOGROVE ;U1
Solar/Wind Harmer
1.652
276611AD2-172 GEN
Solar/Wind Harmer
1.253
276612AE2-035 GEN
Solar/Wind Harmer
1.253
971681AH1-341 GEN
Solar/Wind Harmer
7.305
926823AC1-168 GEN
Solar/Wind Harmer
2.086
970169AG2-114 GEN
Solar/Wind Harmer
4.818
972267AH1-718 GEN
Adder
2.001
276741O09 GEN1
Solar/Wind Harmer
1.71
958391AF2-133 GEN
Solar/Wind Harmer
4.295
274877BISHOP HL;1U
Solar/Wind Harmer
1.594
959141AF2-205 GEN
Solar/Wind Harmer
2.841
24721805FLATG3
50/50
1.059
962761AG1-125 GEN
Solar/Wind Harmer
77.949
970149AG2-104 GEN
Solar/Wind Harmer
48.134
970155AG2-107 GEN
Solar/Wind Harmer
33.99
972207SS24-0001
Solar/Wind Harmer
11.895
274773LINCOLN ;4U
Adder
3.346
274774LINCOLN ;5U
Adder
3.346
274723RIVER EC ;12
Adder
9.343
941551AE2-152 GEN
Solar/Wind Harmer
2.352
274802UNIV PARK;5U
Adder
3.022
274812UNIV PK N;8U
Adder
2.594
274751CRETE EC ;1U
Adder
2.528
274754CRETE EC ;4U
Adder
2.528
274676JOLIET 29;8U
Adder
15.851
274871GR RIDGE ;2U
Solar/Wind Harmer
3.967
274847GR RIDGE ;BU
Solar/Wind Harmer
2.609
274674JOLIET 9 ;6U
Adder
7.943
274732ELWOOD EC;7P
Adder
8.467
274745AC1-111 GEN9
Adder
2.875
274682WAUKEGAN ;7U
Adder
9.113
274828WAUKEGAN ;BP
Adder
5.594
276694AA1-018 GEN2
Solar/Wind Harmer
3.182
276691AA1-018 GEN1
Solar/Wind Harmer
0.38
962781AG1-127 GEN
Solar/Wind Harmer
4.794
274861TOP CROP ;1U
Solar/Wind Harmer
3.053
274872LEEDK;1U
Solar/Wind Harmer
4.129
939401AE1-172 GEN
Solar/Wind Harmer
6.95
276805AD2-038 GEN
Solar/Wind Harmer
2.556
970373AG2-245 GEN
Solar/Wind Harmer
10.436
971997AH1-543 GEN
Solar/Wind Harmer
7.823
276882AE2-255 GEN
Solar/Wind Harmer
1.676
957471AF2-041 GEN
Solar/Wind Harmer
14.849
959081AF2-199 GEN
Solar/Wind Harmer
4.95
971067AG2-660 GEN
Solar/Wind Harmer
1.151
274822ROCKFORD ;11
Adder
9.684
970819AG2-516 GEN
Solar/Wind Harmer
5.889
270055AF2-134 C O1
Solar/Wind Harmer
1.475
274858EASY ROAD;U2
Solar/Wind Harmer
2.324
24721705FLATG2
50/50
15.726
970349AG2-230 GEN
Solar/Wind Harmer
8.674
274770LINCOLN ;1U
Adder
3.346
274771LINCOLN ;2U
Adder
3.346
965681AG1-436 GEN
Solar/Wind Harmer
6.556
965791AG1-447 GEN
Solar/Wind Harmer
3.354
274888KELLY CRK;1U
Solar/Wind Harmer
3.064
276776AD2-060 GEN
Solar/Wind Harmer
0.217
958011AF2-095 GEN
Solar/Wind Harmer
7.477
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.342
962771AG1-126 GEN
Solar/Wind Harmer
77.949
970153AG2-106 GEN
Solar/Wind Harmer
33.99
971347AH1-153 GEN
Solar/Wind Harmer
2.891
274772LINCOLN ;3U
Adder
3.346
970707AG2-453 GEN
Solar/Wind Harmer
14.776
972259AH1-714 GEN
Adder
9.978
276164X3-005 C
Solar/Wind Harmer
0.367
274724RIVER EC ;11
Adder
9.24
274887GEN-1.85
Solar/Wind Harmer
2.766
276772AC2-154 GEN
Solar/Wind Harmer
1.449
270223U2-072_GEN1
Solar/Wind Helper
1.537
270224U2-072_GEN2
Solar/Wind Helper
1.537
270227U2-072_GEN3
Solar/Wind Helper
1.537
270228U2-072_GEN4
Solar/Wind Helper
1.537
270231U2-072_GEN5
Solar/Wind Helper
1.537
241973AD2-163_GEN1
Solar/Wind Helper
2.444
241974AD2-163_GEN2
Solar/Wind Helper
2.444
241955AC1-078 GEN
Solar/Wind Helper
2.438
945631AF1-228 GEN
Solar/Wind Helper
1.903
966831AG1-554 GEN
Solar/Wind Helper
0.87
253338AC1-165 GEN
Solar/Wind Helper
0.849
253343AC1-166 GEN
Solar/Wind Helper
0.849
241972AD1-140 GEN
Solar/Wind Helper
3.157
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.908
270263AC1-001 GEN
Solar/Wind Helper
0.554
270340AC2-060 GEN
Solar/Wind Helper
0.995
970941AG2-585 GEN
Solar/Wind Harmer
2.856
276897AD1-100 C
Solar/Wind Harmer
24.095
274805UNIV PK N;1U
Adder
2.599
274808UNIV PK N;4U
Adder
2.582
274674JOLIET 9 ;6U
Adder
7.943
276893AG1-478 C
Solar/Wind Harmer
0.226
274696ROCKY RD ;4P
Adder
5.794
274695ROCKY RD ;2P
Adder
5.66
274693ROCKY RD ;1P
Adder
5.604
274697ROCKY RD ;3P
Adder
1.538
274683WAUKEGAN ;8U
Adder
10.672
274683WAUKEGAN ;8U
Adder
8.996
962691AG1-118 GEN
Solar/Wind Harmer
15.159
958481AF2-142 GEN
Solar/Wind Harmer
7.564
960751AF2-366 GEN
Solar/Wind Harmer
1.446
958491AF2-143 GEN
Solar/Wind Harmer
7.477
276901AD2-066 C O1
Solar/Wind Harmer
1.747
971341AH1-150 GEN
Solar/Wind Harmer
9.899
971343AH1-151 GEN
Solar/Wind Harmer
9.899
972235AH1-702 GEN1
Adder
1.241
972236AH1-702 GEN2
Adder
1.079
276872AE1-163_GEN1
Solar/Wind Harmer
3.293
276876AE1-163_GEN2
Solar/Wind Harmer
3.293
270535AF1-215 GEN1
Solar/Wind Harmer
2.213
270536AF1-215 GEN2
Solar/Wind Harmer
2.213
938861AE1-114 GEN
Solar/Wind Harmer
3.991
274764LEE CO EC;5U
Adder
4.524
274765LEE CO EC;6U
Adder
4.524
274762LEE CO EC;3U
Adder
4.514
274763LEE CO EC;4U
Adder
4.471
276158O29GEN2
Solar/Wind Harmer
2.395
276157O29GEN1
Solar/Wind Harmer
1.821
276645AC1-214 GEN1
Solar/Wind Harmer
0.635
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.708
270471AD2-092_GEN
Solar/Wind Helper
4.708
270462AD2-086
Solar/Wind Helper
5.397
253383AE2-342_GEN
Solar/Wind Helper
1.129
946101AF1-275 GEN
Solar/Wind Helper
0.801
241960AC2-195 GEN
Solar/Wind Helper
1.856
270054AF2-122 C O1
Solar/Wind Helper
1.47
253378AE2-206_GEN
Solar/Wind Helper
1.33
247522W1-056 GEN
Solar/Wind Helper
1.169
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.071
961051AF2-396 GEN
Solar/Wind Harmer
7.24
961051AF2-396 GEN
Solar/Wind Harmer
3.367
276843GEN-1.7
Solar/Wind Harmer
0.298
276806AD2-047 C O1
Solar/Wind Harmer
5.555
274826FISK ;BP
Adder
5.681
939351AE1-166 GEN
Solar/Wind Harmer
3.076
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.022
274814UNIV PK N;0U
Adder
2.616
274807UNIV PK N;3U
Adder
2.611
274811UNIV PK N;7U
Adder
2.594
972231SS25-0005
Solar/Wind Harmer
4.909
972181SS23-001
Solar/Wind Harmer
3.068
274752CRETE EC ;2U
Adder
2.528
274753CRETE EC ;3U
Adder
2.528
274676JOLIET 29;8U
Adder
15.285
943121AE2-341 GEN
Solar/Wind Harmer
7.741
943591AF1-030 GEN
Solar/Wind Harmer
5.161
274729ELWOOD EC;1P
Adder
8.467
274730ELWOOD EC;6P
Adder
8.467
274734ELWOOD EC;8P
Adder
8.467
274736ELWOOD EC;9P
Adder
8.467
24441505OLIV SLR
Solar/Wind Harmer
0.068
274682WAUKEGAN ;7U
Adder
9.113
274862TOP CROP ;2U
Solar/Wind Harmer
2.549
276799AD1-013 GEN
Solar/Wind Harmer
1.101
946671AF1-331 GEN
Solar/Wind Harmer
0.209
274855GSG-6 ;RU
Solar/Wind Harmer
1.839
274850MENDOTA H;RU
Solar/Wind Harmer
1.279
276602WESTBROOK C
Solar/Wind Harmer
1.059
276868AE1-113 GEN
Solar/Wind Harmer
5.026
274879MINONK ;1U
Solar/Wind Harmer
3.351
959091AF2-200 GEN
Solar/Wind Harmer
9.899
247643Z2-116 C
Solar/Wind Harmer
0.034
274857EASY ROAD;U1
Solar/Wind Harmer
2.324
274760LEE CO EC;1U
Adder
4.514
274767LEE CO EC;8U
Adder
4.46
970571AG2-364 GEN
Solar/Wind Harmer
9.697
276603SUBLETTE C
Solar/Wind Harmer
0.508
270505AE1-170 C O1
Solar/Wind Harmer
7.214
964401AG1-302 GEN
Solar/Wind Harmer
4.34
274851PROVIDENC;RU
Solar/Wind Harmer
1.351
274849CRESCENT ;1U
Solar/Wind Harmer
0.877
276782AC1-033 GEN
Solar/Wind Harmer
1.884
274878BISHOP HL;2U
Solar/Wind Harmer
1.594
945111AF1-176 GEN
Solar/Wind Harmer
2.662
270284AF1-227 GEN1
Solar/Wind Helper
6.407
270287AF1-227 GEN3
Solar/Wind Helper
2.35
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.851
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.129
960071AF2-298 GEN
Solar/Wind Helper
0.328
274761LEE CO EC;2U
Adder
4.514
274766LEE CO EC;7U
Adder
4.46
970569AG2-363 GEN
Solar/Wind Harmer
14.545
270216AD2-079_GEN
Solar/Wind Harmer
0.292
957891AF2-083 GEN
Solar/Wind Harmer
7.181
958381AF2-132 GEN
Solar/Wind Harmer
4.34
276708O09 GEN2
Solar/Wind Harmer
1.71
964861AG1-349 GEN
Solar/Wind Harmer
3.753
971917AH1-482 GEN
Solar/Wind Harmer
4.33
276646AC1-214 GEN2
Solar/Wind Harmer
0.635
945111AF1-176 GEN
Solar/Wind Harmer
8.399
274848CAMPGROVE;RU
Solar/Wind Harmer
3.035
24639705ELKHART HY
Adder
0.071
270286AF1-227 GEN2
Solar/Wind Helper
2.35
270391AF1-285 GEN3
Solar/Wind Helper
1.04
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.967
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.204
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.16
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.704
NYPJM->LTFIMP_NY
CLTF
0.904
LGEELTFEXP_LGEE->PJM
CLTF
0.827
WECLTFEXP_WEC->PJM
CLTF
1.878
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.295
CPLELTFEXP_CPLE->PJM
CLTF
1.537
MECLTFEXP_MEC->PJM
CLTF
7.053
SIGELTFEXP_SIGE->PJM
CLTF
0.115
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.167
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.723
LAGNLTFEXP_LAGN->PJM
CLTF
5.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.253
TVALTFEXP_TVA->PJM
CLTF
2.43

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#711_6224_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#711_6224_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.73 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3150.57
MW Contribution:
5.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.063
24344105CKG2
50/50
4.719
243186AF1-051 GEN
50/50
3.141
24318705GVG2
50/50
2.911
962761AG1-125 GEN
Solar/Wind Harmer
65.996
970149AG2-104 GEN
Solar/Wind Harmer
35.639
970155AG2-107 GEN
Solar/Wind Harmer
42.143
274773LINCOLN ;4U
Adder
4.626
274774LINCOLN ;5U
Adder
4.626
274723RIVER EC ;12
Adder
9.496
941551AE2-152 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
3.071
274812UNIV PK N;8U
Adder
2.636
274751CRETE EC ;1U
Adder
4.332
274754CRETE EC ;4U
Adder
4.332
274676JOLIET 29;8U
Adder
16.11
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
8.073
274732ELWOOD EC;7P
Adder
8.606
274745AC1-111 GEN9
Adder
2.922
274682WAUKEGAN ;7U
Adder
9.263
274828WAUKEGAN ;BP
Adder
5.686
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.581
962781AG1-127 GEN
Solar/Wind Harmer
3.402
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.646
24721605FLATG1
50/50
1.063
274775LINCOLN ;6U
Adder
4.626
274776LINCOLN ;7U
Adder
4.626
274777LINCOLN ;8U
Adder
4.626
960681AF2-359 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
1.958
972227AH1-698 GEN1
Adder
1.378
960591AF2-350 GEN
Solar/Wind Harmer
3.682
274827FISK ;RP
Adder
4.092
274800UNIV PARK;3U
Adder
3.073
274801UNIV PARK;4U
Adder
3.073
972037AH1-567 GEN1
Adder
0.096
274687WILL CNTY;4U
Adder
14.674
274687WILL CNTY;4U
Adder
14.674
274675JOLIET 29;7U
Adder
16.11
274675JOLIET 29;7U
Adder
15.535
970833AG2-524 GEN
Solar/Wind Harmer
4.026
970833AG2-524 GEN
Solar/Wind Harmer
2.684
274728ELWOOD EC;5P
Adder
8.606
274731ELWOOD EC;2P
Adder
8.606
274733ELWOOD EC;3P
Adder
8.606
274735ELWOOD EC;4P
Adder
8.606
274744AC1-111 GEN8
Adder
2.922
274746AC1-111 G10
Adder
2.922
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.557
970073AG2-061 GEN
Solar/Wind Harmer
1.179
971675AH1-338 GEN
Solar/Wind Harmer
1.378
276861AD2-134 GEN
Solar/Wind Harmer
0.063
276863AD2-134 GEN
Solar/Wind Harmer
0.063
971411AH1-196 GEN
Solar/Wind Harmer
5.299
24721705FLATG2
50/50
15.792
243186AF1-051 GEN
50/50
3.141
970349AG2-230 GEN
Solar/Wind Harmer
6.143
274770LINCOLN ;1U
Adder
4.626
274771LINCOLN ;2U
Adder
4.626
965681AG1-436 GEN
Solar/Wind Harmer
4.649
965791AG1-447 GEN
Solar/Wind Harmer
3.409
274888KELLY CRK;1U
Solar/Wind Harmer
0.215
276776AD2-060 GEN
Solar/Wind Harmer
0.393
958011AF2-095 GEN
Solar/Wind Harmer
5.302
970941AG2-585 GEN
Solar/Wind Harmer
2.025
276897AD1-100 C
Solar/Wind Harmer
9.195
274805UNIV PK N;1U
Adder
2.642
274808UNIV PK N;4U
Adder
2.625
274674JOLIET 9 ;6U
Adder
8.073
276893AG1-478 C
Solar/Wind Harmer
0.243
274696ROCKY RD ;4P
Adder
5.889
274695ROCKY RD ;2P
Adder
5.753
274693ROCKY RD ;1P
Adder
5.697
274697ROCKY RD ;3P
Adder
1.563
274683WAUKEGAN ;8U
Adder
10.848
274683WAUKEGAN ;8U
Adder
9.145
962691AG1-118 GEN
Solar/Wind Harmer
10.751
958481AF2-142 GEN
Solar/Wind Harmer
5.365
958491AF2-143 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
7.022
971343AH1-151 GEN
Solar/Wind Harmer
7.022
972235AH1-702 GEN1
Adder
1.262
972236AH1-702 GEN2
Adder
1.097
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
1.957
274764LEE CO EC;5U
Adder
4.601
274765LEE CO EC;6U
Adder
4.601
274762LEE CO EC;3U
Adder
4.59
274763LEE CO EC;4U
Adder
4.547
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.548
276645AC1-214 GEN1
Solar/Wind Harmer
0.132
961051AF2-396 GEN
Solar/Wind Harmer
6.669
961051AF2-396 GEN
Solar/Wind Harmer
4.446
942111AE2-223 GEN
Solar/Wind Harmer
1.065
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
1.072
247620Y3-023
Adder
0.208
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
270349AD2-093_GEN
Solar/Wind Helper
4.68
270471AD2-092_GEN
Solar/Wind Helper
4.68
270462AD2-086
Solar/Wind Helper
5.356
253383AE2-342_GEN
Solar/Wind Helper
1.111
946101AF1-275 GEN
Solar/Wind Helper
0.784
241960AC2-195 GEN
Solar/Wind Helper
1.835
270054AF2-122 C O1
Solar/Wind Helper
1.457
253378AE2-206_GEN
Solar/Wind Helper
1.313
247522W1-056 GEN
Solar/Wind Helper
1.156
253415AE1-040 GEN
Solar/Wind Helper
0.455
276805AD2-038 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.407
971997AH1-543 GEN
Solar/Wind Harmer
1.85
276882AE2-255 GEN
Solar/Wind Harmer
0.411
957471AF2-041 GEN
Solar/Wind Harmer
10.533
959081AF2-199 GEN
Solar/Wind Harmer
3.511
971067AG2-660 GEN
Solar/Wind Harmer
1.17
274822ROCKFORD ;11
Adder
9.846
970819AG2-516 GEN
Solar/Wind Harmer
4.178
270055AF2-134 C O1
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.59
274766LEE CO EC;7U
Adder
4.536
970569AG2-363 GEN
Solar/Wind Harmer
10.321
957891AF2-083 GEN
Solar/Wind Harmer
5.667
958381AF2-132 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.12
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.408
276646AC1-214 GEN2
Solar/Wind Harmer
0.132
945111AF1-176 GEN
Solar/Wind Harmer
5.968
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.738
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.132
24639705ELKHART HY
Adder
0.072
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.59
24385905FR-11G C
Solar/Wind Harmer
0
24722005FLATG5
50/50
1.063
24721905FLATG4
50/50
19.423
24318705GVG2
50/50
2.911
962771AG1-126 GEN
Solar/Wind Harmer
65.996
970153AG2-106 GEN
Solar/Wind Harmer
42.143
971347AH1-153 GEN
Solar/Wind Harmer
2.048
274772LINCOLN ;3U
Adder
4.626
970707AG2-453 GEN
Solar/Wind Harmer
12.22
972259AH1-714 GEN
Adder
10.14
274724RIVER EC ;11
Adder
9.39
274887GEN-1.85
Solar/Wind Harmer
0.096
276843GEN-1.7
Solar/Wind Harmer
0.119
276806AD2-047 C O1
Solar/Wind Harmer
2.086
274826FISK ;BP
Adder
5.774
939351AE1-166 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.192
274803UNIV PARK;6U
Adder
3.071
274814UNIV PK N;0U
Adder
2.659
274807UNIV PK N;3U
Adder
2.653
274811UNIV PK N;7U
Adder
2.636
274752CRETE EC ;2U
Adder
4.332
274753CRETE EC ;3U
Adder
4.332
274676JOLIET 29;8U
Adder
15.535
943121AE2-341 GEN
Solar/Wind Harmer
6.135
943591AF1-030 GEN
Solar/Wind Harmer
4.08
274729ELWOOD EC;1P
Adder
8.606
274730ELWOOD EC;6P
Adder
8.606
274734ELWOOD EC;8P
Adder
8.606
274736ELWOOD EC;9P
Adder
8.606
274682WAUKEGAN ;7U
Adder
9.263
274862TOP CROP ;2U
Solar/Wind Harmer
0.483
946671AF1-331 GEN
Solar/Wind Harmer
0.377
274855GSG-6 ;RU
Solar/Wind Harmer
0.129
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
276868AE1-113 GEN
Solar/Wind Harmer
0.705
274879MINONK ;1U
Solar/Wind Harmer
0.147
959091AF2-200 GEN
Solar/Wind Harmer
7.022
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.59
274767LEE CO EC;8U
Adder
4.536
970571AG2-364 GEN
Solar/Wind Harmer
6.881
270505AE1-170 C O1
Solar/Wind Harmer
3.587
964401AG1-302 GEN
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.112
945111AF1-176 GEN
Solar/Wind Harmer
2.711
965931AG1-462 GEN
Solar/Wind Harmer
8.411
971087AG2-675 GEN
Solar/Wind Harmer
1.759
965091AG1-374 GEN
Solar/Wind Harmer
9.651
959611AF2-252 GEN
Solar/Wind Harmer
1.072
270043AE2-236 GEN
Solar/Wind Harmer
2.049
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.153
944531AF1-118 GEN
Solar/Wind Harmer
13.848
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.393
270284AF1-227 GEN1
Solar/Wind Helper
6.367
270287AF1-227 GEN3
Solar/Wind Helper
2.335
942871AE2-306 GEN
Solar/Wind Helper
0.775
276820AF1-078_GEN
Solar/Wind Helper
0.613
270518AE2-148 GEN
Solar/Wind Helper
10.61
960801AF2-371 GEN
Solar/Wind Helper
0.85
964871AG1-351 GEN
Solar/Wind Helper
0.587
253325AC1-069 GEN
Solar/Wind Helper
0.859
270541AE2-072 C
Solar/Wind Helper
1.112
960071AF2-298 GEN
Solar/Wind Helper
0.32
971171AH1-044 GEN
Solar/Wind Harmer
7.022
274823ROCKFORD ;21
Adder
9.774
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
971681AH1-341 GEN
Solar/Wind Harmer
5.563
926823AC1-168 GEN
Solar/Wind Harmer
0.585
970169AG2-114 GEN
Solar/Wind Harmer
3.42
972267AH1-718 GEN
Adder
2.035
276741O09 GEN1
Solar/Wind Harmer
0.12
958391AF2-133 GEN
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.112
959141AF2-205 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.857
971611AH1-305 GEN
Solar/Wind Harmer
1.968
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.442
270071AF1-092 GEN
Solar/Wind Harmer
6.245
274854TWINGROVE;U2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.118
276848AB2-070 GEN3
Solar/Wind Harmer
0.118
276849AB2-070 GEN2
Solar/Wind Harmer
0.118
270223U2-072_GEN1
Solar/Wind Helper
1.526
270224U2-072_GEN2
Solar/Wind Helper
1.526
270227U2-072_GEN3
Solar/Wind Helper
1.526
270228U2-072_GEN4
Solar/Wind Helper
1.526
270231U2-072_GEN5
Solar/Wind Helper
1.526
241973AD2-163_GEN1
Solar/Wind Helper
2.406
241974AD2-163_GEN2
Solar/Wind Helper
2.406
241955AC1-078 GEN
Solar/Wind Helper
2.39
945631AF1-228 GEN
Solar/Wind Helper
1.862
966831AG1-554 GEN
Solar/Wind Helper
0.86
253338AC1-165 GEN
Solar/Wind Helper
0.829
253343AC1-166 GEN
Solar/Wind Helper
0.829
241972AD1-140 GEN
Solar/Wind Helper
3.091
945641AF1-229 GEN
Solar/Wind Helper
1.095
270499AE1-146 GEN
Solar/Wind Helper
1.885
270263AC1-001 GEN
Solar/Wind Helper
0.54
270340AC2-060 GEN
Solar/Wind Helper
0.967
24386605FR-22G C
Solar/Wind Harmer
0
270286AF1-227 GEN2
Solar/Wind Helper
2.335
270391AF1-285 GEN3
Solar/Wind Helper
1.033
270578AF1-285 GEN2
Solar/Wind Helper
1.033
270317AD1-130_GEN
Solar/Wind Helper
5.921
270485AE1-090_GEN
Solar/Wind Helper
0.466
270520AE2-214 GEN
Solar/Wind Helper
3.134
253333AC1-068 GEN
Solar/Wind Helper
0.859
960841AF2-375 GEN
Solar/Wind Helper
1.147
270273AD2-016 GEN
Solar/Wind Helper
1.662
270297AD1-101 GEN
Solar/Wind Helper
0.209
958961AF2-187 GEN
Solar/Wind Helper
1.121
241840AF1-064_GEN
Solar/Wind Helper
0.476
241807AE2-176_GEN
Solar/Wind Helper
0.698
NYPJM->LTFIMP_NY
CLTF
0.933
LGEELTFEXP_LGEE->PJM
CLTF
0.885
WECLTFEXP_WEC->PJM
CLTF
1.909
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.606
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.522
CPLELTFEXP_CPLE->PJM
CLTF
1.546
MECLTFEXP_MEC->PJM
CLTF
7.183
SIGELTFEXP_SIGE->PJM
CLTF
0.119
AG2-052LTFEXP_AG2-052->PJM
LTF
0.114
AH1-155LTFEXP_AH1-155->PJM
LTF
0.17
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.631
LAGNLTFEXP_LAGN->PJM
CLTF
5.571
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.313
TVALTFEXP_TVA->PJM
CLTF
2.485

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-3_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.63 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3147.5
MW Contribution:
5.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
15.73
243186AF1-051 GEN
50/50
3.128
970349AG2-230 GEN
Solar/Wind Harmer
6.057
274770LINCOLN ;1U
Adder
4.558
274771LINCOLN ;2U
Adder
4.558
965681AG1-436 GEN
Solar/Wind Harmer
4.578
965791AG1-447 GEN
Solar/Wind Harmer
3.357
274888KELLY CRK;1U
Solar/Wind Harmer
0.211
276776AD2-060 GEN
Solar/Wind Harmer
0.387
958011AF2-095 GEN
Solar/Wind Harmer
5.222
970941AG2-585 GEN
Solar/Wind Harmer
1.994
276897AD1-100 C
Solar/Wind Harmer
9.056
24721805FLATG3
50/50
1.059
24344105CKG2
50/50
4.657
243186AF1-051 GEN
50/50
3.128
24318705GVG2
50/50
2.899
962761AG1-125 GEN
Solar/Wind Harmer
65.757
970149AG2-104 GEN
Solar/Wind Harmer
35.51
970155AG2-107 GEN
Solar/Wind Harmer
41.991
274773LINCOLN ;4U
Adder
4.558
274774LINCOLN ;5U
Adder
4.558
274723RIVER EC ;12
Adder
9.352
941551AE2-152 GEN
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
3.024
274812UNIV PK N;8U
Adder
2.596
274751CRETE EC ;1U
Adder
4.266
274754CRETE EC ;4U
Adder
4.266
274676JOLIET 29;8U
Adder
15.866
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.951
274732ELWOOD EC;7P
Adder
8.475
274745AC1-111 GEN9
Adder
2.877
274682WAUKEGAN ;7U
Adder
9.121
274828WAUKEGAN ;BP
Adder
5.599
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.572
962781AG1-127 GEN
Solar/Wind Harmer
3.35
274861TOP CROP ;1U
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
2.605
276805AD2-038 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.288
971997AH1-543 GEN
Solar/Wind Harmer
1.821
276882AE2-255 GEN
Solar/Wind Harmer
0.405
957471AF2-041 GEN
Solar/Wind Harmer
10.37
959081AF2-199 GEN
Solar/Wind Harmer
3.457
971067AG2-660 GEN
Solar/Wind Harmer
1.152
274822ROCKFORD ;11
Adder
9.693
970819AG2-516 GEN
Solar/Wind Harmer
4.112
270055AF2-134 C O1
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.518
274766LEE CO EC;7U
Adder
4.465
970569AG2-363 GEN
Solar/Wind Harmer
10.157
957891AF2-083 GEN
Solar/Wind Harmer
5.572
958381AF2-132 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.118
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.335
276646AC1-214 GEN2
Solar/Wind Harmer
0.13
945111AF1-176 GEN
Solar/Wind Harmer
5.866
274848CAMPGROVE;RU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.708
24721605FLATG1
50/50
1.059
274775LINCOLN ;6U
Adder
4.558
24722005FLATG5
50/50
1.059
24721905FLATG4
50/50
19.347
24318705GVG2
50/50
2.899
962771AG1-126 GEN
Solar/Wind Harmer
65.757
970153AG2-106 GEN
Solar/Wind Harmer
41.991
971347AH1-153 GEN
Solar/Wind Harmer
2.019
274772LINCOLN ;3U
Adder
4.558
970707AG2-453 GEN
Solar/Wind Harmer
12.038
972259AH1-714 GEN
Adder
9.988
274724RIVER EC ;11
Adder
9.248
274887GEN-1.85
Solar/Wind Harmer
0.094
276843GEN-1.7
Solar/Wind Harmer
0.117
276806AD2-047 C O1
Solar/Wind Harmer
2.055
274826FISK ;BP
Adder
5.687
939351AE1-166 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.189
274803UNIV PARK;6U
Adder
3.024
274814UNIV PK N;0U
Adder
2.619
274807UNIV PK N;3U
Adder
2.613
274811UNIV PK N;7U
Adder
2.596
274752CRETE EC ;2U
Adder
4.266
274753CRETE EC ;3U
Adder
4.266
274676JOLIET 29;8U
Adder
15.299
943121AE2-341 GEN
Solar/Wind Harmer
6.042
943591AF1-030 GEN
Solar/Wind Harmer
4.018
274729ELWOOD EC;1P
Adder
8.475
274730ELWOOD EC;6P
Adder
8.475
274734ELWOOD EC;8P
Adder
8.475
274736ELWOOD EC;9P
Adder
8.475
274682WAUKEGAN ;7U
Adder
9.121
274862TOP CROP ;2U
Solar/Wind Harmer
0.475
946671AF1-331 GEN
Solar/Wind Harmer
0.371
274855GSG-6 ;RU
Solar/Wind Harmer
0.127
274850MENDOTA H;RU
Solar/Wind Harmer
0.04
276868AE1-113 GEN
Solar/Wind Harmer
0.694
274879MINONK ;1U
Solar/Wind Harmer
0.145
959091AF2-200 GEN
Solar/Wind Harmer
6.913
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.518
274767LEE CO EC;8U
Adder
4.465
970571AG2-364 GEN
Solar/Wind Harmer
6.772
274805UNIV PK N;1U
Adder
2.602
274808UNIV PK N;4U
Adder
2.585
274674JOLIET 9 ;6U
Adder
7.951
276893AG1-478 C
Solar/Wind Harmer
0.24
274695ROCKY RD ;2P
Adder
5.665
274693ROCKY RD ;1P
Adder
5.61
274697ROCKY RD ;3P
Adder
1.539
274696ROCKY RD ;4P
Adder
5.799
274683WAUKEGAN ;8U
Adder
10.682
274683WAUKEGAN ;8U
Adder
9.005
962691AG1-118 GEN
Solar/Wind Harmer
10.586
958481AF2-142 GEN
Solar/Wind Harmer
5.282
958491AF2-143 GEN
Solar/Wind Harmer
5.221
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.913
971343AH1-151 GEN
Solar/Wind Harmer
6.913
972235AH1-702 GEN1
Adder
1.242
972236AH1-702 GEN2
Adder
1.08
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
1.927
274764LEE CO EC;5U
Adder
4.528
274765LEE CO EC;6U
Adder
4.528
274762LEE CO EC;3U
Adder
4.518
274763LEE CO EC;4U
Adder
4.475
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.539
276645AC1-214 GEN1
Solar/Wind Harmer
0.13
961051AF2-396 GEN
Solar/Wind Harmer
6.555
961051AF2-396 GEN
Solar/Wind Harmer
4.37
942111AE2-223 GEN
Solar/Wind Harmer
1.048
960611AF2-352 GEN
Solar/Wind Harmer
1.054
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
247620Y3-023
Adder
0.204
270349AD2-093_GEN
Solar/Wind Helper
4.705
270471AD2-092_GEN
Solar/Wind Helper
4.705
270462AD2-086
Solar/Wind Helper
5.394
253383AE2-342_GEN
Solar/Wind Helper
1.128
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.855
270054AF2-122 C O1
Solar/Wind Helper
1.473
253378AE2-206_GEN
Solar/Wind Helper
1.329
247522W1-056 GEN
Solar/Wind Helper
1.168
253415AE1-040 GEN
Solar/Wind Helper
0.468
253349AC2-067 GEN
Solar/Wind Helper
0.175
253400AC2-068 GEN
Solar/Wind Helper
0.07
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.062
24639705ELKHART HY
Adder
0.071
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.513
270286AF1-227 GEN2
Solar/Wind Helper
2.348
270391AF1-285 GEN3
Solar/Wind Helper
1.04
270578AF1-285 GEN2
Solar/Wind Helper
1.04
270317AD1-130_GEN
Solar/Wind Helper
5.963
270485AE1-090_GEN
Solar/Wind Helper
0.469
270520AE2-214 GEN
Solar/Wind Helper
3.2
253333AC1-068 GEN
Solar/Wind Helper
0.879
960841AF2-375 GEN
Solar/Wind Helper
1.159
270273AD2-016 GEN
Solar/Wind Helper
1.703
270297AD1-101 GEN
Solar/Wind Helper
0.213
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.483
241807AE2-176_GEN
Solar/Wind Helper
0.703
274776LINCOLN ;7U
Adder
4.558
274777LINCOLN ;8U
Adder
4.558
960681AF2-359 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
1.928
972227AH1-698 GEN1
Adder
1.358
960591AF2-350 GEN
Solar/Wind Harmer
3.626
274827FISK ;RP
Adder
4.03
274800UNIV PARK;3U
Adder
3.027
274801UNIV PARK;4U
Adder
3.027
972037AH1-567 GEN1
Adder
0.095
274687WILL CNTY;4U
Adder
14.452
274687WILL CNTY;4U
Adder
14.452
274675JOLIET 29;7U
Adder
15.866
274675JOLIET 29;7U
Adder
15.3
970833AG2-524 GEN
Solar/Wind Harmer
3.965
970833AG2-524 GEN
Solar/Wind Harmer
2.643
274728ELWOOD EC;5P
Adder
8.475
274731ELWOOD EC;2P
Adder
8.475
274733ELWOOD EC;3P
Adder
8.475
274735ELWOOD EC;4P
Adder
8.475
274744AC1-111 GEN8
Adder
2.877
274746AC1-111 G10
Adder
2.877
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.499
970073AG2-061 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
1.357
276861AD2-134 GEN
Solar/Wind Harmer
0.062
276863AD2-134 GEN
Solar/Wind Harmer
0.062
971411AH1-196 GEN
Solar/Wind Harmer
5.217
971171AH1-044 GEN
Solar/Wind Harmer
6.913
274823ROCKFORD ;21
Adder
9.622
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.08
971681AH1-341 GEN
Solar/Wind Harmer
5.476
926823AC1-168 GEN
Solar/Wind Harmer
0.576
970169AG2-114 GEN
Solar/Wind Harmer
3.365
972267AH1-718 GEN
Adder
2.003
276741O09 GEN1
Solar/Wind Harmer
0.118
958391AF2-133 GEN
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.11
959141AF2-205 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.827
971611AH1-305 GEN
Solar/Wind Harmer
1.935
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.385
270071AF1-092 GEN
Solar/Wind Harmer
6.128
274854TWINGROVE;U2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.536
270224U2-072_GEN2
Solar/Wind Helper
1.536
270227U2-072_GEN3
Solar/Wind Helper
1.536
270228U2-072_GEN4
Solar/Wind Helper
1.536
270231U2-072_GEN5
Solar/Wind Helper
1.536
241973AD2-163_GEN1
Solar/Wind Helper
2.441
241974AD2-163_GEN2
Solar/Wind Helper
2.441
241955AC1-078 GEN
Solar/Wind Helper
2.436
945631AF1-228 GEN
Solar/Wind Helper
1.902
966831AG1-554 GEN
Solar/Wind Helper
0.869
253338AC1-165 GEN
Solar/Wind Helper
0.848
253343AC1-166 GEN
Solar/Wind Helper
0.848
241972AD1-140 GEN
Solar/Wind Helper
3.153
945641AF1-229 GEN
Solar/Wind Helper
1.107
270499AE1-146 GEN
Solar/Wind Helper
1.906
270263AC1-001 GEN
Solar/Wind Helper
0.555
270340AC2-060 GEN
Solar/Wind Helper
0.994
270505AE1-170 C O1
Solar/Wind Harmer
3.527
964401AG1-302 GEN
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.11
945111AF1-176 GEN
Solar/Wind Harmer
2.665
965931AG1-462 GEN
Solar/Wind Harmer
8.275
971087AG2-675 GEN
Solar/Wind Harmer
1.731
965091AG1-374 GEN
Solar/Wind Harmer
9.488
959611AF2-252 GEN
Solar/Wind Harmer
1.054
270043AE2-236 GEN
Solar/Wind Harmer
2.01
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.097
944531AF1-118 GEN
Solar/Wind Harmer
13.569
270284AF1-227 GEN1
Solar/Wind Helper
6.403
270287AF1-227 GEN3
Solar/Wind Helper
2.348
942871AE2-306 GEN
Solar/Wind Helper
0.78
276820AF1-078_GEN
Solar/Wind Helper
0.621
270518AE2-148 GEN
Solar/Wind Helper
10.844
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253325AC1-069 GEN
Solar/Wind Helper
0.879
270541AE2-072 C
Solar/Wind Helper
1.128
960071AF2-298 GEN
Solar/Wind Helper
0.328
NYPJM->LTFIMP_NY
CLTF
0.905
LGEELTFEXP_LGEE->PJM
CLTF
0.829
WECLTFEXP_WEC->PJM
CLTF
1.879
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.305
CPLELTFEXP_CPLE->PJM
CLTF
1.537
MECLTFEXP_MEC->PJM
CLTF
7.06
SIGELTFEXP_SIGE->PJM
CLTF
0.115
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.767
LAGNLTFEXP_LAGN->PJM
CLTF
5.461
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.255
TVALTFEXP_TVA->PJM
CLTF
2.432

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.31 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5773.71
MW Contribution:
13.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
80.774
970149AG2-104 GEN
Solar/Wind Harmer
43.619
970155AG2-107 GEN
Solar/Wind Harmer
51.58
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
10.415
274754CRETE EC ;4U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
945111AF1-176 GEN
Solar/Wind Harmer
15.659
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
6.422
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971997AH1-543 GEN
Solar/Wind Harmer
4.485
957471AF2-041 GEN
Solar/Wind Harmer
25.504
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
970569AG2-363 GEN
Solar/Wind Harmer
25.306
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
14.053
965681AG1-436 GEN
Solar/Wind Harmer
11.209
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
276776AD2-060 GEN
Solar/Wind Harmer
0.937
958011AF2-095 GEN
Solar/Wind Harmer
12.646
970941AG2-585 GEN
Solar/Wind Harmer
4.83
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
21.908
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.582
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
25.814
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
972236AH1-702 GEN2
Adder
2.662
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.897
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
965651AG1-433 GEN
Solar/Wind Harmer
2.449
276708O09 GEN2
Solar/Wind Harmer
0.295
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
965911AG1-460 GEN
Solar/Wind Harmer
1.542
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.459
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
965421AG1-410 GEN
Solar/Wind Harmer
21.55
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.196
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
972203AH1-686 GEN
Adder
1.998
942111AE2-223 GEN
Solar/Wind Harmer
2.686
960611AF2-352 GEN
Solar/Wind Harmer
2.728
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.921
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
270031AE2-169
Solar/Wind Harmer
4.257
270599AE1-208 GEN
Solar/Wind Harmer
7.096
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
276911AD2-131_GEN
Solar/Wind Harmer
1.062
270246TR4_N_V150
Solar/Wind Harmer
0.049
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.284
270383AD1-128 GEN
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
970883AG2-550 GEN
Solar/Wind Harmer
6.689
970885AG2-551 GEN
Solar/Wind Harmer
2.23
270054AF2-122 C O1
Solar/Wind Helper
1.547
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
17.36
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274775LINCOLN ;6U
Adder
10.797
274776LINCOLN ;7U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
274731ELWOOD EC;2P
Adder
20.57
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
971347AH1-153 GEN
Solar/Wind Harmer
4.684
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274753CRETE EC ;3U
Adder
10.415
270505AE1-170 C O1
Solar/Wind Harmer
9.246
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
0.228
276843GEN-1.7
Solar/Wind Harmer
0.284
276806AD2-047 C O1
Solar/Wind Harmer
4.976
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
17.002
970571AG2-364 GEN
Solar/Wind Harmer
16.871
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
965931AG1-462 GEN
Solar/Wind Harmer
20.885
971087AG2-675 GEN
Solar/Wind Harmer
4.368
965091AG1-374 GEN
Solar/Wind Harmer
24.551
959611AF2-252 GEN
Solar/Wind Harmer
2.728
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.663
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
957381AF2-032 GEN
Solar/Wind Harmer
1.75
942481AE2-261 GEN
Solar/Wind Harmer
23.05
270004AE1-209 GEN
Solar/Wind Harmer
1.624
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24695305TIMB G C
Solar/Wind Harmer
0.627
970825AG2-519 GEN
Solar/Wind Harmer
5.579
946031AF1-268 GEN
Solar/Wind Harmer
6.994
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
5.989
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.434
970169AG2-114 GEN
Solar/Wind Harmer
8.435
971681AH1-341 GEN
Solar/Wind Harmer
13.557
972267AH1-718 GEN
Adder
4.986
276741O09 GEN1
Solar/Wind Harmer
0.295
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.677
946321AF1-296 GEN
Solar/Wind Harmer
4.601
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
10.858
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
971549AH1-272 GEN
Solar/Wind Harmer
16.367
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.859
970289AG2-191 GEN
Solar/Wind Harmer
1.486
971609AH1-304 GEN
Solar/Wind Harmer
1.264
247521TR3_G114
Solar/Wind Harmer
0.275
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.891
247536S-71 GEN
Solar/Wind Harmer
0.278
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.586
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
CPLELTFEXP_CPLE->PJM
CLTF
3.243
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P2-2_#8072_05MARYSV 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.25 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5359.3
MW Contribution:
15.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.482
24721905FLATG4
50/50
27.071
962771AG1-126 GEN
Solar/Wind Harmer
112.309
970153AG2-106 GEN
Solar/Wind Harmer
48.972
971347AH1-153 GEN
Solar/Wind Harmer
5.989
274772LINCOLN ;3U
Adder
6.931
24441505OLIV SLR
Solar/Wind Harmer
0.148
270043AE2-236 GEN
Solar/Wind Harmer
6.061
247643Z2-116 C
Solar/Wind Harmer
0.076
274724RIVER EC ;11
Adder
19.46
970707AG2-453 GEN
Solar/Wind Harmer
30.756
276164X3-005 C
Solar/Wind Harmer
0.77
972231SS25-0005
Solar/Wind Harmer
10.389
972181SS23-001
Solar/Wind Harmer
6.493
274752CRETE EC ;2U
Adder
5.351
274753CRETE EC ;3U
Adder
5.351
972259AH1-714 GEN
Adder
20.849
274814UNIV PK N;0U
Adder
5.517
274807UNIV PK N;3U
Adder
5.505
274811UNIV PK N;7U
Adder
5.469
274826FISK ;BP
Adder
11.934
274887GEN-1.85
Solar/Wind Harmer
5.806
276772AC2-154 GEN
Solar/Wind Harmer
3.041
24721605FLATG1
50/50
1.482
24721705FLATG2
50/50
22.01
270102X2-052 ST
50/50
1.799
270100X2-052 CT1
50/50
1.662
270101X2-052 CT2
50/50
1.662
970349AG2-230 GEN
Solar/Wind Harmer
17.966
965681AG1-436 GEN
Solar/Wind Harmer
14.006
965791AG1-447 GEN
Solar/Wind Harmer
7.166
274770LINCOLN ;1U
Adder
6.931
274771LINCOLN ;2U
Adder
6.931
274805UNIV PK N;1U
Adder
5.481
274808UNIV PK N;4U
Adder
5.445
274888KELLY CRK;1U
Solar/Wind Harmer
6.431
276776AD2-060 GEN
Solar/Wind Harmer
0.456
958011AF2-095 GEN
Solar/Wind Harmer
15.693
970941AG2-585 GEN
Solar/Wind Harmer
5.994
276897AD1-100 C
Solar/Wind Harmer
50.481
274674JOLIET 9 ;6U
Adder
16.661
276893AG1-478 C
Solar/Wind Harmer
0.474
961051AF2-396 GEN
Solar/Wind Harmer
17.047
961051AF2-396 GEN
Solar/Wind Harmer
7.929
274695ROCKY RD ;2P
Adder
11.868
274693ROCKY RD ;1P
Adder
11.751
274697ROCKY RD ;3P
Adder
3.224
274696ROCKY RD ;4P
Adder
12.148
274683WAUKEGAN ;8U
Adder
22.4
274683WAUKEGAN ;8U
Adder
18.882
958481AF2-142 GEN
Solar/Wind Harmer
15.94
960681AF2-359 GEN
Solar/Wind Harmer
4.234
274775LINCOLN ;6U
Adder
6.931
274776LINCOLN ;7U
Adder
6.931
274777LINCOLN ;8U
Adder
6.931
270526AF1-158 GEN
Solar/Wind Harmer
5.027
971771AH1-392 GEN
Solar/Wind Harmer
9.974
270071AF1-092 GEN
Solar/Wind Harmer
16.362
274827FISK ;RP
Adder
8.458
972228AH1-698 GEN2
Adder
4.038
972227AH1-698 GEN1
Adder
2.843
960591AF2-350 GEN
Solar/Wind Harmer
10.898
972037AH1-567 GEN1
Adder
0.199
274800UNIV PARK;3U
Adder
6.351
274801UNIV PARK;4U
Adder
6.351
274687WILL CNTY;4U
Adder
30.296
274687WILL CNTY;4U
Adder
30.296
274675JOLIET 29;7U
Adder
33.244
274675JOLIET 29;7U
Adder
32.057
970833AG2-524 GEN
Solar/Wind Harmer
9.439
970833AG2-524 GEN
Solar/Wind Harmer
4.39
274728ELWOOD EC;5P
Adder
17.77
274731ELWOOD EC;2P
Adder
17.77
274733ELWOOD EC;3P
Adder
17.77
274735ELWOOD EC;4P
Adder
17.77
276893AG1-478 C
Solar/Wind Harmer
0.594
274744AC1-111 GEN8
Adder
6.017
274746AC1-111 G10
Adder
6.017
944161AF1-084 GEN
Solar/Wind Harmer
2.35
970073AG2-061 GEN
Solar/Wind Harmer
2.447
971675AH1-338 GEN
Solar/Wind Harmer
18.851
971411AH1-196 GEN
Solar/Wind Harmer
15.708
276861AD2-134 GEN
Solar/Wind Harmer
1.869
276863AD2-134 GEN
Solar/Wind Harmer
1.869
971171AH1-044 GEN
Solar/Wind Harmer
20.831
274863CRW1-WTG
Solar/Wind Harmer
5.799
274864CRW2-WTG
Solar/Wind Harmer
5.799
274823ROCKFORD ;21
Adder
20.237
276889AE2-281 GEN
Solar/Wind Harmer
1.991
958391AF2-133 GEN
Solar/Wind Harmer
9.384
274856ECOGROVE ;U1
Solar/Wind Harmer
3.481
276611AD2-172 GEN
Solar/Wind Harmer
2.641
276612AE2-035 GEN
Solar/Wind Harmer
2.641
959141AF2-205 GEN
Solar/Wind Harmer
6.218
926823AC1-168 GEN
Solar/Wind Harmer
4.418
971681AH1-341 GEN
Solar/Wind Harmer
15.409
24729505KEY G4
Adder
6.649
972267AH1-718 GEN
Adder
4.228
241955AC1-078 GEN
Solar/Wind Helper
2.298
241973AD2-163_GEN1
Solar/Wind Helper
1.862
241974AD2-163_GEN2
Solar/Wind Helper
1.862
945631AF1-228 GEN
Solar/Wind Helper
1.837
24721805FLATG3
50/50
1.482
24344105CKG2
50/50
9.343
962761AG1-125 GEN
Solar/Wind Harmer
112.309
970149AG2-104 GEN
Solar/Wind Harmer
69.351
970155AG2-107 GEN
Solar/Wind Harmer
48.972
972207SS24-0001
Solar/Wind Harmer
24.644
274773LINCOLN ;4U
Adder
6.931
274774LINCOLN ;5U
Adder
6.931
274723RIVER EC ;12
Adder
19.685
270216AD2-079_GEN
Solar/Wind Harmer
0.663
274751CRETE EC ;1U
Adder
5.351
274754CRETE EC ;4U
Adder
5.351
274812UNIV PK N;8U
Adder
5.469
274802UNIV PARK;5U
Adder
6.353
941551AE2-152 GEN
Solar/Wind Harmer
4.928
957891AF2-083 GEN
Solar/Wind Harmer
16.274
274676JOLIET 29;8U
Adder
33.244
274674JOLIET 9 ;6U
Adder
16.661
274732ELWOOD EC;7P
Adder
17.77
274871GR RIDGE ;2U
Solar/Wind Harmer
8.31
274847GR RIDGE ;BU
Solar/Wind Harmer
5.464
945111AF1-176 GEN
Solar/Wind Harmer
19.236
24639705ELKHART HY
Adder
0.165
274745AC1-111 GEN9
Adder
6.017
970373AG2-245 GEN
Solar/Wind Harmer
22.569
270449AD2-020 GEN
Solar/Wind Harmer
3.003
943021AE2-325 GEN
Solar/Wind Harmer
3.902
274682WAUKEGAN ;7U
Adder
19.124
274828WAUKEGAN ;BP
Adder
11.742
276694AA1-018 GEN2
Solar/Wind Harmer
6.705
276691AA1-018 GEN1
Solar/Wind Harmer
0.801
274861TOP CROP ;1U
Solar/Wind Harmer
6.434
270055AF2-134 C O1
Solar/Wind Harmer
3.202
962781AG1-127 GEN
Solar/Wind Harmer
10.059
274872LEEDK;1U
Solar/Wind Harmer
8.667
939401AE1-172 GEN
Solar/Wind Harmer
14.675
276805AD2-038 GEN
Solar/Wind Harmer
5.395
276882AE2-255 GEN
Solar/Wind Harmer
3.536
971997AH1-543 GEN
Solar/Wind Harmer
16.495
24441205WTRV SLR C
Solar/Wind Harmer
0.141
958381AF2-132 GEN
Solar/Wind Harmer
9.461
957471AF2-041 GEN
Solar/Wind Harmer
31.247
959081AF2-199 GEN
Solar/Wind Harmer
10.416
971067AG2-660 GEN
Solar/Wind Harmer
2.422
964861AG1-349 GEN
Solar/Wind Harmer
8.186
971917AH1-482 GEN
Solar/Wind Harmer
9.444
274822ROCKFORD ;11
Adder
20.385
970819AG2-516 GEN
Solar/Wind Harmer
12.405
970569AG2-363 GEN
Solar/Wind Harmer
30.826
274761LEE CO EC;2U
Adder
9.525
274766LEE CO EC;7U
Adder
9.413
270520AE2-214 GEN
Solar/Wind Helper
3.207
270286AF1-227 GEN2
Solar/Wind Helper
0.87
247620Y3-023
Adder
0.489
962691AG1-118 GEN
Solar/Wind Harmer
31.798
270535AF1-215 GEN1
Solar/Wind Harmer
4.804
270536AF1-215 GEN2
Solar/Wind Harmer
4.804
960751AF2-366 GEN
Solar/Wind Harmer
3.035
958491AF2-143 GEN
Solar/Wind Harmer
15.782
276901AD2-066 C O1
Solar/Wind Harmer
3.686
971341AH1-150 GEN
Solar/Wind Harmer
20.831
971343AH1-151 GEN
Solar/Wind Harmer
20.831
276872AE1-163_GEN1
Solar/Wind Harmer
6.967
276876AE1-163_GEN2
Solar/Wind Harmer
6.967
972235AH1-702 GEN1
Adder
2.613
972236AH1-702 GEN2
Adder
2.272
274764LEE CO EC;5U
Adder
9.547
274765LEE CO EC;6U
Adder
9.547
274762LEE CO EC;3U
Adder
9.525
274763LEE CO EC;4U
Adder
9.435
270054AF2-122 C O1
Solar/Wind Helper
2.097
946101AF1-275 GEN
Solar/Wind Helper
0.802
270349AD2-093_GEN
Solar/Wind Helper
1.818
270471AD2-092_GEN
Solar/Wind Helper
1.818
253383AE2-342_GEN
Solar/Wind Helper
0.854
241960AC2-195 GEN
Solar/Wind Helper
1.419
938861AE1-114 GEN
Solar/Wind Harmer
2.265
276843GEN-1.7
Solar/Wind Harmer
0.625
276806AD2-047 C O1
Solar/Wind Harmer
11.659
274803UNIV PARK;6U
Adder
6.353
972038AH1-567 GEN2
Adder
0.398
270505AE1-170 C O1
Solar/Wind Harmer
16.306
939351AE1-166 GEN
Solar/Wind Harmer
6.445
274676JOLIET 29;8U
Adder
32.056
274729ELWOOD EC;1P
Adder
17.77
274730ELWOOD EC;6P
Adder
17.77
274734ELWOOD EC;8P
Adder
17.77
274736ELWOOD EC;9P
Adder
17.77
943121AE2-341 GEN
Solar/Wind Harmer
16.181
943591AF1-030 GEN
Solar/Wind Harmer
10.787
945111AF1-176 GEN
Solar/Wind Harmer
6.096
274682WAUKEGAN ;7U
Adder
19.124
274862TOP CROP ;2U
Solar/Wind Harmer
5.372
944531AF1-118 GEN
Solar/Wind Harmer
36.716
276868AE1-113 GEN
Solar/Wind Harmer
10.607
274879MINONK ;1U
Solar/Wind Harmer
7.072
276799AD1-013 GEN
Solar/Wind Harmer
2.315
946671AF1-331 GEN
Solar/Wind Harmer
0.439
274855GSG-6 ;RU
Solar/Wind Harmer
3.866
274850MENDOTA H;RU
Solar/Wind Harmer
2.688
276602WESTBROOK C
Solar/Wind Harmer
2.225
964401AG1-302 GEN
Solar/Wind Harmer
9.461
959091AF2-200 GEN
Solar/Wind Harmer
20.831
270063AE2-323 C
Solar/Wind Harmer
2.285
970571AG2-364 GEN
Solar/Wind Harmer
20.55
274760LEE CO EC;1U
Adder
9.525
274767LEE CO EC;8U
Adder
9.413
270284AF1-227 GEN1
Solar/Wind Helper
2.373
270287AF1-227 GEN3
Solar/Wind Helper
0.87
960801AF2-371 GEN
Solar/Wind Helper
0.964
964871AG1-351 GEN
Solar/Wind Helper
0.665
NYPJM->LTFIMP_NY
CLTF
2.454
LGEELTFEXP_LGEE->PJM
CLTF
3.221
WECLTFEXP_WEC->PJM
CLTF
3.955
CBM West 1LTFEXP_CBM-W1->PJM
CBM
114.418
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.259
MECLTFEXP_MEC->PJM
CLTF
15.133
SIGELTFEXP_SIGE->PJM
CLTF
0.321
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.92
LAGNLTFEXP_LAGN->PJM
CLTF
11.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.139
TVALTFEXP_TVA->PJM
CLTF
5.225

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-3_#8072_05MARYSV 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.01 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5074.41
MW Contribution:
11.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.482
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
9.435
274776LINCOLN ;7U
Adder
9.435
274777LINCOLN ;8U
Adder
9.435
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
7.732
270071AF1-092 GEN
Solar/Wind Harmer
14.586
274827FISK ;RP
Adder
8.458
972228AH1-698 GEN2
Adder
4.038
972227AH1-698 GEN1
Adder
2.843
960591AF2-350 GEN
Solar/Wind Harmer
7.603
972037AH1-567 GEN1
Adder
0.199
274800UNIV PARK;3U
Adder
6.351
274801UNIV PARK;4U
Adder
6.351
274687WILL CNTY;4U
Adder
30.296
274687WILL CNTY;4U
Adder
30.296
274675JOLIET 29;7U
Adder
33.244
274675JOLIET 29;7U
Adder
32.057
970833AG2-524 GEN
Solar/Wind Harmer
8.297
970833AG2-524 GEN
Solar/Wind Harmer
5.531
274728ELWOOD EC;5P
Adder
17.77
274731ELWOOD EC;2P
Adder
17.77
274733ELWOOD EC;3P
Adder
17.77
274735ELWOOD EC;4P
Adder
17.77
274744AC1-111 GEN8
Adder
6.017
274746AC1-111 G10
Adder
6.017
970073AG2-061 GEN
Solar/Wind Harmer
2.447
971675AH1-338 GEN
Solar/Wind Harmer
2.85
971411AH1-196 GEN
Solar/Wind Harmer
10.959
276861AD2-134 GEN
Solar/Wind Harmer
0.13
276863AD2-134 GEN
Solar/Wind Harmer
0.13
971171AH1-044 GEN
Solar/Wind Harmer
14.533
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
20.237
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.168
959141AF2-205 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.219
971681AH1-341 GEN
Solar/Wind Harmer
11.539
24729505KEY G4
Adder
6.649
970169AG2-114 GEN
Solar/Wind Harmer
7.15
971611AH1-305 GEN
Solar/Wind Harmer
4.239
970031AG2-029 GEN
Solar/Wind Harmer
3.854
972267AH1-718 GEN
Adder
4.228
276741O09 GEN1
Solar/Wind Harmer
0.25
274877BISHOP HL;1U
Solar/Wind Harmer
0.234
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.266
946321AF1-296 GEN
Solar/Wind Harmer
3.872
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
13.514
276668AB2-070 GEN1
Solar/Wind Harmer
0.255
276848AB2-070 GEN3
Solar/Wind Harmer
0.254
276849AB2-070 GEN2
Solar/Wind Harmer
0.255
963841AG1-237 GEN
Solar/Wind Harmer
2.803
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.399
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.148
241955AC1-078 GEN
Solar/Wind Helper
2.298
241973AD2-163_GEN1
Solar/Wind Helper
1.862
241974AD2-163_GEN2
Solar/Wind Helper
1.862
945631AF1-228 GEN
Solar/Wind Helper
1.837
24721705FLATG2
50/50
22.01
270102X2-052 ST
50/50
1.799
270100X2-052 CT1
50/50
1.662
270101X2-052 CT2
50/50
1.662
970349AG2-230 GEN
Solar/Wind Harmer
12.534
965681AG1-436 GEN
Solar/Wind Harmer
9.772
965791AG1-447 GEN
Solar/Wind Harmer
7.166
274770LINCOLN ;1U
Adder
9.435
274771LINCOLN ;2U
Adder
9.435
274805UNIV PK N;1U
Adder
5.481
274808UNIV PK N;4U
Adder
5.445
274888KELLY CRK;1U
Solar/Wind Harmer
0.443
276776AD2-060 GEN
Solar/Wind Harmer
0.811
958011AF2-095 GEN
Solar/Wind Harmer
10.949
970941AG2-585 GEN
Solar/Wind Harmer
4.182
276897AD1-100 C
Solar/Wind Harmer
18.954
274674JOLIET 9 ;6U
Adder
16.661
276893AG1-478 C
Solar/Wind Harmer
0.502
961051AF2-396 GEN
Solar/Wind Harmer
14.985
961051AF2-396 GEN
Solar/Wind Harmer
9.99
274695ROCKY RD ;2P
Adder
11.868
274693ROCKY RD ;1P
Adder
11.751
274697ROCKY RD ;3P
Adder
3.224
274696ROCKY RD ;4P
Adder
12.148
274683WAUKEGAN ;8U
Adder
22.4
274683WAUKEGAN ;8U
Adder
18.882
958481AF2-142 GEN
Solar/Wind Harmer
11.121
247620Y3-023
Adder
0.489
962691AG1-118 GEN
Solar/Wind Harmer
22.185
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.011
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.533
971343AH1-151 GEN
Solar/Wind Harmer
14.533
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.613
972236AH1-702 GEN2
Adder
2.272
938861AE1-114 GEN
Solar/Wind Harmer
4.06
274764LEE CO EC;5U
Adder
9.547
274765LEE CO EC;6U
Adder
9.547
274762LEE CO EC;3U
Adder
9.525
274763LEE CO EC;4U
Adder
9.435
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.14
276645AC1-214 GEN1
Solar/Wind Harmer
0.276
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.249
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.272
944541AF1-119 GEN
Solar/Wind Harmer
0.446
960971AF2-388 GEN
Solar/Wind Harmer
3.922
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.752
276615X2-022 GEN
Solar/Wind Harmer
0.066
276838X2-022 GEN2
Solar/Wind Harmer
0.36
970241AG2-163 GEN
Solar/Wind Harmer
3.681
276916AD2-100_GEN
Solar/Wind Harmer
12.928
276911AD2-131_GEN
Solar/Wind Harmer
0.852
942221AE2-234 GEN
Solar/Wind Harmer
2.468
970291AG2-192 GEN
Solar/Wind Harmer
0.785
970291AG2-192 GEN
Solar/Wind Harmer
0.362
270054AF2-122 C O1
Solar/Wind Helper
2.097
946101AF1-275 GEN
Solar/Wind Helper
0.802
270349AD2-093_GEN
Solar/Wind Helper
1.818
270471AD2-092_GEN
Solar/Wind Helper
1.818
253383AE2-342_GEN
Solar/Wind Helper
0.854
241960AC2-195 GEN
Solar/Wind Helper
1.419
24721805FLATG3
50/50
1.482
24344105CKG2
50/50
9.343
962761AG1-125 GEN
Solar/Wind Harmer
94.712
970149AG2-104 GEN
Solar/Wind Harmer
51.146
970155AG2-107 GEN
Solar/Wind Harmer
60.48
274773LINCOLN ;4U
Adder
9.435
274774LINCOLN ;5U
Adder
9.435
274723RIVER EC ;12
Adder
19.685
274751CRETE EC ;1U
Adder
9.02
274754CRETE EC ;4U
Adder
9.02
274812UNIV PK N;8U
Adder
5.469
274802UNIV PARK;5U
Adder
6.353
941551AE2-152 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
12.616
274676JOLIET 29;8U
Adder
33.244
274674JOLIET 9 ;6U
Adder
16.661
274732ELWOOD EC;7P
Adder
17.77
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
13.42
24639705ELKHART HY
Adder
0.165
274745AC1-111 GEN9
Adder
6.017
970373AG2-245 GEN
Solar/Wind Harmer
15.746
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.902
274682WAUKEGAN ;7U
Adder
19.124
274828WAUKEGAN ;BP
Adder
11.742
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.205
274861TOP CROP ;1U
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.023
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.495
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.854
971997AH1-543 GEN
Solar/Wind Harmer
3.836
958381AF2-132 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
21.8
959081AF2-199 GEN
Solar/Wind Harmer
7.267
971067AG2-660 GEN
Solar/Wind Harmer
2.422
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.444
274822ROCKFORD ;11
Adder
20.385
970819AG2-516 GEN
Solar/Wind Harmer
8.655
970569AG2-363 GEN
Solar/Wind Harmer
21.506
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.525
274766LEE CO EC;7U
Adder
9.413
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.899
276708O09 GEN2
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.276
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.688
965651AG1-433 GEN
Solar/Wind Harmer
1.961
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.83
276621W2-048 GEN
Solar/Wind Harmer
0.32
963741AG1-226 GEN
Solar/Wind Harmer
14.933
965011AG1-365 GEN
Solar/Wind Harmer
6.284
945371AF1-202 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.24
270520AE2-214 GEN
Solar/Wind Helper
3.207
270286AF1-227 GEN2
Solar/Wind Helper
0.87
24722005FLATG5
50/50
1.482
24721905FLATG4
50/50
27.071
962771AG1-126 GEN
Solar/Wind Harmer
94.712
970153AG2-106 GEN
Solar/Wind Harmer
60.48
971347AH1-153 GEN
Solar/Wind Harmer
4.178
274772LINCOLN ;3U
Adder
9.435
270043AE2-236 GEN
Solar/Wind Harmer
4.934
274724RIVER EC ;11
Adder
19.46
970707AG2-453 GEN
Solar/Wind Harmer
25.034
274752CRETE EC ;2U
Adder
9.02
274753CRETE EC ;3U
Adder
9.02
972259AH1-714 GEN
Adder
20.849
274814UNIV PK N;0U
Adder
5.517
274807UNIV PK N;3U
Adder
5.505
274811UNIV PK N;7U
Adder
5.469
274826FISK ;BP
Adder
11.934
274887GEN-1.85
Solar/Wind Harmer
0.198
276843GEN-1.7
Solar/Wind Harmer
0.246
276806AD2-047 C O1
Solar/Wind Harmer
4.309
274803UNIV PARK;6U
Adder
6.353
972038AH1-567 GEN2
Adder
0.398
270505AE1-170 C O1
Solar/Wind Harmer
7.964
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.056
274729ELWOOD EC;1P
Adder
17.77
274730ELWOOD EC;6P
Adder
17.77
274734ELWOOD EC;8P
Adder
17.77
274736ELWOOD EC;9P
Adder
17.77
943121AE2-341 GEN
Solar/Wind Harmer
12.618
943591AF1-030 GEN
Solar/Wind Harmer
8.391
945111AF1-176 GEN
Solar/Wind Harmer
6.096
274682WAUKEGAN ;7U
Adder
19.124
274862TOP CROP ;2U
Solar/Wind Harmer
1
944531AF1-118 GEN
Solar/Wind Harmer
32.801
276868AE1-113 GEN
Solar/Wind Harmer
1.463
274879MINONK ;1U
Solar/Wind Harmer
0.305
946671AF1-331 GEN
Solar/Wind Harmer
0.78
274855GSG-6 ;RU
Solar/Wind Harmer
0.267
274850MENDOTA H;RU
Solar/Wind Harmer
0.085
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959091AF2-200 GEN
Solar/Wind Harmer
14.533
270063AE2-323 C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
14.338
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.525
274767LEE CO EC;8U
Adder
9.413
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.234
965931AG1-462 GEN
Solar/Wind Harmer
17.553
971087AG2-675 GEN
Solar/Wind Harmer
3.671
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.861
965091AG1-374 GEN
Solar/Wind Harmer
20.448
959611AF2-252 GEN
Solar/Wind Harmer
2.272
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.994
965021AG1-366 GEN
Solar/Wind Harmer
2.095
957381AF2-032 GEN
Solar/Wind Harmer
1.409
942481AE2-261 GEN
Solar/Wind Harmer
18.543
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.665
270284AF1-227 GEN1
Solar/Wind Helper
2.373
270287AF1-227 GEN3
Solar/Wind Helper
0.87
960801AF2-371 GEN
Solar/Wind Helper
0.964
964871AG1-351 GEN
Solar/Wind Helper
0.665
NYPJM->LTFIMP_NY
CLTF
2.454
LGEELTFEXP_LGEE->PJM
CLTF
3.221
WECLTFEXP_WEC->PJM
CLTF
3.955
CBM West 1LTFEXP_CBM-W1->PJM
CBM
114.418
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.259
CPLELTFEXP_CPLE->PJM
CLTF
1.997
MECLTFEXP_MEC->PJM
CLTF
15.133
SIGELTFEXP_SIGE->PJM
CLTF
0.321
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.92
LAGNLTFEXP_LAGN->PJM
CLTF
11.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.139
TVALTFEXP_TVA->PJM
CLTF
5.225

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.62 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4476.89
MW Contribution:
11.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
8.859
270143AC1-141 CT2_
50/50
2.617
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.55
274773LINCOLN ;4U
50/50
9.616
274774LINCOLN ;5U
50/50
9.616
962761AG1-125 GEN
Solar/Wind Harmer
74.627
970149AG2-104 GEN
Solar/Wind Harmer
40.3
970155AG2-107 GEN
Solar/Wind Harmer
47.655
957891AF2-083 GEN
Solar/Wind Harmer
12.55
945111AF1-176 GEN
Solar/Wind Harmer
13.401
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.895
274723RIVER EC ;12
Adder
19.037
274751CRETE EC ;1U
Adder
8.738
274754CRETE EC ;4U
Adder
8.738
965011AG1-365 GEN
Solar/Wind Harmer
7.385
274812UNIV PK N;8U
Adder
5.291
274802UNIV PARK;5U
Adder
6.138
970373AG2-245 GEN
Solar/Wind Harmer
15.385
941551AE2-152 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
1.749
270100X2-052 CT1
50/50
1.616
270101X2-052 CT2
50/50
1.616
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.526
274770LINCOLN ;1U
50/50
9.616
274771LINCOLN ;2U
50/50
9.616
970349AG2-230 GEN
Solar/Wind Harmer
12.041
965681AG1-436 GEN
Solar/Wind Harmer
9.504
965791AG1-447 GEN
Solar/Wind Harmer
6.97
961051AF2-396 GEN
Solar/Wind Harmer
14.959
961051AF2-396 GEN
Solar/Wind Harmer
9.973
274805UNIV PK N;1U
Adder
5.303
274808UNIV PK N;4U
Adder
5.268
274888KELLY CRK;1U
Solar/Wind Harmer
0.428
276776AD2-060 GEN
Solar/Wind Harmer
0.783
958011AF2-095 GEN
Solar/Wind Harmer
10.572
970941AG2-585 GEN
Solar/Wind Harmer
4.038
276897AD1-100 C
Solar/Wind Harmer
18.287
274674JOLIET 9 ;6U
Adder
16.082
276893AG1-478 C
Solar/Wind Harmer
0.485
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
11.454
274693ROCKY RD ;1P
Adder
11.341
274697ROCKY RD ;3P
Adder
3.111
274696ROCKY RD ;4P
Adder
11.724
958481AF2-142 GEN
Solar/Wind Harmer
10.754
274683WAUKEGAN ;8U
Adder
21.627
274683WAUKEGAN ;8U
Adder
18.23
962691AG1-118 GEN
Solar/Wind Harmer
21.414
958491AF2-143 GEN
Solar/Wind Harmer
10.655
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.045
971343AH1-151 GEN
Solar/Wind Harmer
14.045
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.526
972236AH1-702 GEN2
Adder
2.196
938861AE1-114 GEN
Solar/Wind Harmer
3.928
944541AF1-119 GEN
Solar/Wind Harmer
0.462
960971AF2-388 GEN
Solar/Wind Harmer
4.056
274764LEE CO EC;5U
Adder
9.237
274765LEE CO EC;6U
Adder
9.237
274762LEE CO EC;3U
Adder
9.215
274763LEE CO EC;4U
Adder
9.128
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.104
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.191
942221AE2-234 GEN
Solar/Wind Harmer
2.684
960611AF2-352 GEN
Solar/Wind Harmer
2.217
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.745
944231AF1-091 GEN
Solar/Wind Harmer
15.08
270246TR4_N_V150
Solar/Wind Harmer
0.042
270247TR4_N_V136
Solar/Wind Harmer
0.042
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.669
970291AG2-192 GEN
Solar/Wind Harmer
0.817
970291AG2-192 GEN
Solar/Wind Harmer
0.377
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.353
270031AE2-169
Solar/Wind Harmer
3.44
270599AE1-208 GEN
Solar/Wind Harmer
5.734
971613AH1-306 GEN
Solar/Wind Harmer
2.966
276916AD2-100_GEN
Solar/Wind Harmer
12.749
276911AD2-131_GEN
Solar/Wind Harmer
0.84
246937BC-WTG2
Solar/Wind Harmer
0.244
270054AF2-122 C O1
Solar/Wind Helper
1.656
274676JOLIET 29;8U
Adder
32.088
274674JOLIET 9 ;6U
Adder
16.082
274732ELWOOD EC;7P
Adder
17.157
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.803
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.165
274682WAUKEGAN ;7U
Adder
18.463
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
11.336
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.78
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.257
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.318
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.826
971997AH1-543 GEN
Solar/Wind Harmer
3.71
957471AF2-041 GEN
Solar/Wind Harmer
21.068
959081AF2-199 GEN
Solar/Wind Harmer
7.023
971067AG2-660 GEN
Solar/Wind Harmer
2.341
274822ROCKFORD ;11
Adder
19.703
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.741
970819AG2-516 GEN
Solar/Wind Harmer
8.368
970569AG2-363 GEN
Solar/Wind Harmer
20.843
965651AG1-433 GEN
Solar/Wind Harmer
2.028
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.215
274766LEE CO EC;7U
Adder
9.107
276708O09 GEN2
Solar/Wind Harmer
0.242
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
958861AF2-177 GEN
Solar/Wind Harmer
2.941
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.439
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
14.886
276621W2-048 GEN
Solar/Wind Harmer
0.314
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
6.922
270032AE2-172
Solar/Wind Harmer
4.12
965421AG1-410 GEN
Solar/Wind Harmer
18.52
965911AG1-460 GEN
Solar/Wind Harmer
1.222
246936BC-WTG1
Solar/Wind Harmer
0.244
270489AE1-102 GEN1
Solar/Wind Harmer
0.786
276903AD2-071 C
Solar/Wind Harmer
6.725
270144AC1-141 ST1_
50/50
2.311
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.028
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.616
274776LINCOLN ;7U
50/50
9.616
274777LINCOLN ;8U
50/50
9.616
270071AF1-092 GEN
Solar/Wind Harmer
14.768
971771AH1-392 GEN
Solar/Wind Harmer
7.622
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
4.047
959331AF2-224 GEN
Solar/Wind Harmer
5.169
274827FISK ;RP
Adder
8.169
972037AH1-567 GEN1
Adder
0.193
960591AF2-350 GEN
Solar/Wind Harmer
7.341
274800UNIV PARK;3U
Adder
6.134
274801UNIV PARK;4U
Adder
6.134
972228AH1-698 GEN2
Adder
3.896
972227AH1-698 GEN1
Adder
2.744
24729505KEY G4
Adder
6.793
274687WILL CNTY;4U
Adder
29.249
274687WILL CNTY;4U
Adder
29.249
274675JOLIET 29;7U
Adder
32.088
274675JOLIET 29;7U
Adder
30.942
274728ELWOOD EC;5P
Adder
17.157
274731ELWOOD EC;2P
Adder
17.157
274733ELWOOD EC;3P
Adder
17.157
274735ELWOOD EC;4P
Adder
17.157
970833AG2-524 GEN
Solar/Wind Harmer
8.005
970833AG2-524 GEN
Solar/Wind Harmer
5.336
274744AC1-111 GEN8
Adder
5.803
274746AC1-111 G10
Adder
5.803
970073AG2-061 GEN
Solar/Wind Harmer
2.368
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.753
971411AH1-196 GEN
Solar/Wind Harmer
10.588
276861AD2-134 GEN
Solar/Wind Harmer
0.126
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
14.045
274823ROCKFORD ;21
Adder
19.56
971611AH1-305 GEN
Solar/Wind Harmer
4.163
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
926823AC1-168 GEN
Solar/Wind Harmer
1.181
970169AG2-114 GEN
Solar/Wind Harmer
6.939
971681AH1-341 GEN
Solar/Wind Harmer
11.162
972267AH1-718 GEN
Adder
4.093
276741O09 GEN1
Solar/Wind Harmer
0.242
971549AH1-272 GEN
Solar/Wind Harmer
14.066
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
9.126
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.079
965041AG1-368 GEN
Solar/Wind Harmer
6.739
946321AF1-296 GEN
Solar/Wind Harmer
3.754
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.235
965051AG1-369 GEN
Solar/Wind Harmer
3.245
963841AG1-237 GEN
Solar/Wind Harmer
2.784
276668AB2-070 GEN1
Solar/Wind Harmer
0.25
276848AB2-070 GEN3
Solar/Wind Harmer
0.249
276849AB2-070 GEN2
Solar/Wind Harmer
0.25
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.194
971609AH1-304 GEN
Solar/Wind Harmer
1.022
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.766
270142AC1-141 CT1_
50/50
2.617
24642205MAYFLWER
50/50
0.04
274772LINCOLN ;3U
50/50
9.616
944961AF1-161 GEN
50/50
3.109
962601AG1-109 GEN
50/50
3.109
962771AG1-126 GEN
Solar/Wind Harmer
74.627
970153AG2-106 GEN
Solar/Wind Harmer
47.655
971347AH1-153 GEN
Solar/Wind Harmer
4.014
270043AE2-236 GEN
Solar/Wind Harmer
5.048
270505AE1-170 C O1
Solar/Wind Harmer
7.914
270063AE2-323 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.088
944531AF1-118 GEN
Solar/Wind Harmer
33.371
274724RIVER EC ;11
Adder
18.817
274752CRETE EC ;2U
Adder
8.738
274753CRETE EC ;3U
Adder
8.738
965021AG1-366 GEN
Solar/Wind Harmer
2.462
970707AG2-453 GEN
Solar/Wind Harmer
24.09
274814UNIV PK N;0U
Adder
5.338
274807UNIV PK N;3U
Adder
5.326
274811UNIV PK N;7U
Adder
5.291
972259AH1-714 GEN
Adder
20.093
274826FISK ;BP
Adder
11.527
274803UNIV PARK;6U
Adder
6.138
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.237
276806AD2-047 C O1
Solar/Wind Harmer
4.16
972038AH1-567 GEN2
Adder
0.384
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.942
274729ELWOOD EC;1P
Adder
17.157
274730ELWOOD EC;6P
Adder
17.157
274734ELWOOD EC;8P
Adder
17.157
274736ELWOOD EC;9P
Adder
17.157
943121AE2-341 GEN
Solar/Wind Harmer
12.163
943591AF1-030 GEN
Solar/Wind Harmer
8.088
274682WAUKEGAN ;7U
Adder
18.463
274862TOP CROP ;2U
Solar/Wind Harmer
0.968
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.416
274879MINONK ;1U
Solar/Wind Harmer
0.295
946671AF1-331 GEN
Solar/Wind Harmer
0.753
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
959091AF2-200 GEN
Solar/Wind Harmer
14.045
970571AG2-364 GEN
Solar/Wind Harmer
13.895
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.215
274767LEE CO EC;8U
Adder
9.107
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
24690905MDL-1G C
Solar/Wind Harmer
0
24721905FLATG4
Adder
19.661
970781AG2-491 GEN
Solar/Wind Harmer
6.766
965931AG1-462 GEN
Solar/Wind Harmer
17.022
971087AG2-675 GEN
Solar/Wind Harmer
3.56
965091AG1-374 GEN
Solar/Wind Harmer
19.952
959611AF2-252 GEN
Solar/Wind Harmer
2.217
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
971993AH1-541 GEN
Solar/Wind Harmer
2.938
24695305TIMB G C
Solar/Wind Harmer
0.537
970289AG2-191 GEN
Solar/Wind Harmer
0.691
957381AF2-032 GEN
Solar/Wind Harmer
1.388
942481AE2-261 GEN
Solar/Wind Harmer
18.271
246938BC-WTG3
Solar/Wind Harmer
0.218
270491AE1-102 GEN2
Solar/Wind Harmer
0.786
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
NYPJM->LTFIMP_NY
CLTF
2.583
LGEELTFEXP_LGEE->PJM
CLTF
3.675
WECLTFEXP_WEC->PJM
CLTF
3.823
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.267
CPLELTFEXP_CPLE->PJM
CLTF
1.444
MECLTFEXP_MEC->PJM
CLTF
14.733
SIGELTFEXP_SIGE->PJM
CLTF
0.34
AG2-052LTFEXP_AG2-052->PJM
LTF
0.237
AH1-155LTFEXP_AH1-155->PJM
LTF
0.356
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.349
LAGNLTFEXP_LAGN->PJM
CLTF
11.281
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.712
TVALTFEXP_TVA->PJM
CLTF
5.082

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.34 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5774.92
MW Contribution:
13.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721705FLATG2
50/50
26.753
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.903
270101X2-052 CT2
50/50
1.903
970349AG2-230 GEN
Solar/Wind Harmer
14.053
965681AG1-436 GEN
Solar/Wind Harmer
11.209
965791AG1-447 GEN
Solar/Wind Harmer
8.22
274770LINCOLN ;1U
Adder
10.797
274771LINCOLN ;2U
Adder
10.797
274805UNIV PK N;1U
Adder
6.33
274808UNIV PK N;4U
Adder
6.289
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
276776AD2-060 GEN
Solar/Wind Harmer
0.937
958011AF2-095 GEN
Solar/Wind Harmer
12.646
970941AG2-585 GEN
Solar/Wind Harmer
4.83
247620Y3-023
Adder
0.579
276897AD1-100 C
Solar/Wind Harmer
21.908
961051AF2-396 GEN
Solar/Wind Harmer
17.478
961051AF2-396 GEN
Solar/Wind Harmer
11.652
274674JOLIET 9 ;6U
Adder
19.278
276893AG1-478 C
Solar/Wind Harmer
0.582
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
14.112
274695ROCKY RD ;2P
Adder
13.787
274693ROCKY RD ;1P
Adder
13.651
274697ROCKY RD ;3P
Adder
3.745
958481AF2-142 GEN
Solar/Wind Harmer
12.945
274683WAUKEGAN ;8U
Adder
26.045
274683WAUKEGAN ;8U
Adder
21.955
962691AG1-118 GEN
Solar/Wind Harmer
25.814
958491AF2-143 GEN
Solar/Wind Harmer
12.858
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.002
971343AH1-151 GEN
Solar/Wind Harmer
17.002
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.061
972236AH1-702 GEN2
Adder
2.662
938861AE1-114 GEN
Solar/Wind Harmer
4.771
274764LEE CO EC;5U
Adder
11.229
274765LEE CO EC;6U
Adder
11.229
274762LEE CO EC;3U
Adder
11.202
274763LEE CO EC;4U
Adder
11.097
24722005FLATG5
50/50
1.801
24721905FLATG4
50/50
32.904
962771AG1-126 GEN
Solar/Wind Harmer
80.774
970153AG2-106 GEN
Solar/Wind Harmer
51.58
971347AH1-153 GEN
Solar/Wind Harmer
4.684
270043AE2-236 GEN
Solar/Wind Harmer
5.865
274772LINCOLN ;3U
Adder
10.797
274724RIVER EC ;11
Adder
22.43
944531AF1-118 GEN
Solar/Wind Harmer
39.561
970707AG2-453 GEN
Solar/Wind Harmer
28.808
274752CRETE EC ;2U
Adder
10.415
274753CRETE EC ;3U
Adder
10.415
270505AE1-170 C O1
Solar/Wind Harmer
9.246
274814UNIV PK N;0U
Adder
6.372
274807UNIV PK N;3U
Adder
6.358
274811UNIV PK N;7U
Adder
6.317
972259AH1-714 GEN
Adder
24.043
274826FISK ;BP
Adder
13.782
274803UNIV PARK;6U
Adder
7.339
274887GEN-1.85
Solar/Wind Harmer
0.228
276843GEN-1.7
Solar/Wind Harmer
0.284
276806AD2-047 C O1
Solar/Wind Harmer
4.976
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.113
270063AE2-323 C
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
37.076
274729ELWOOD EC;1P
Adder
20.57
274730ELWOOD EC;6P
Adder
20.57
274734ELWOOD EC;8P
Adder
20.57
274736ELWOOD EC;9P
Adder
20.57
943121AE2-341 GEN
Solar/Wind Harmer
14.603
943591AF1-030 GEN
Solar/Wind Harmer
9.711
274682WAUKEGAN ;7U
Adder
22.229
274862TOP CROP ;2U
Solar/Wind Harmer
1.165
964401AG1-302 GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
2.852
276868AE1-113 GEN
Solar/Wind Harmer
1.71
274879MINONK ;1U
Solar/Wind Harmer
0.357
946671AF1-331 GEN
Solar/Wind Harmer
0.91
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
959091AF2-200 GEN
Solar/Wind Harmer
17.002
970571AG2-364 GEN
Solar/Wind Harmer
16.871
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
11.202
274767LEE CO EC;8U
Adder
11.07
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.277
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
8.302
965931AG1-462 GEN
Solar/Wind Harmer
20.885
24721605FLATG1
50/50
1.801
270071AF1-092 GEN
Solar/Wind Harmer
17.36
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.928
274775LINCOLN ;6U
Adder
10.797
274776LINCOLN ;7U
Adder
10.797
274777LINCOLN ;8U
Adder
10.797
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
9.767
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.782
972228AH1-698 GEN2
Adder
4.662
972227AH1-698 GEN1
Adder
3.283
274800UNIV PARK;3U
Adder
7.336
274801UNIV PARK;4U
Adder
7.336
274687WILL CNTY;4U
Adder
35.036
274687WILL CNTY;4U
Adder
35.036
274675JOLIET 29;7U
Adder
38.449
274675JOLIET 29;7U
Adder
37.076
274728ELWOOD EC;5P
Adder
20.57
274731ELWOOD EC;2P
Adder
20.57
274733ELWOOD EC;3P
Adder
20.57
274735ELWOOD EC;4P
Adder
20.57
970833AG2-524 GEN
Solar/Wind Harmer
9.602
970833AG2-524 GEN
Solar/Wind Harmer
6.401
970031AG2-029 GEN
Solar/Wind Harmer
4.721
24729505KEY G4
Adder
8.09
274744AC1-111 GEN8
Adder
6.969
274746AC1-111 G10
Adder
6.969
970073AG2-061 GEN
Solar/Wind Harmer
2.857
959331AF2-224 GEN
Solar/Wind Harmer
5.989
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
3.328
971411AH1-196 GEN
Solar/Wind Harmer
12.799
276861AD2-134 GEN
Solar/Wind Harmer
0.152
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
17.002
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274823ROCKFORD ;21
Adder
23.693
274856ECOGROVE ;U1
Solar/Wind Harmer
0.197
926823AC1-168 GEN
Solar/Wind Harmer
1.434
970169AG2-114 GEN
Solar/Wind Harmer
8.435
971681AH1-341 GEN
Solar/Wind Harmer
13.557
972267AH1-718 GEN
Adder
4.986
276741O09 GEN1
Solar/Wind Harmer
0.295
274877BISHOP HL;1U
Solar/Wind Harmer
0.277
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
24721805FLATG3
50/50
1.801
24344105CKG2
50/50
10.297
962761AG1-125 GEN
Solar/Wind Harmer
80.774
970149AG2-104 GEN
Solar/Wind Harmer
43.619
970155AG2-107 GEN
Solar/Wind Harmer
51.58
274773LINCOLN ;4U
Adder
10.797
274774LINCOLN ;5U
Adder
10.797
274723RIVER EC ;12
Adder
22.692
24639705ELKHART HY
Adder
0.194
274751CRETE EC ;1U
Adder
10.415
274754CRETE EC ;4U
Adder
10.415
957891AF2-083 GEN
Solar/Wind Harmer
14.667
274812UNIV PK N;8U
Adder
6.317
274802UNIV PARK;5U
Adder
7.339
945111AF1-176 GEN
Solar/Wind Harmer
15.659
941551AE2-152 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
18.373
274676JOLIET 29;8U
Adder
38.449
274674JOLIET 9 ;6U
Adder
19.278
274732ELWOOD EC;7P
Adder
20.57
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.55
274745AC1-111 GEN9
Adder
6.969
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.402
274682WAUKEGAN ;7U
Adder
22.229
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
13.652
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.177
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.164
939401AE1-172 GEN
Solar/Wind Harmer
6.422
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
8.556
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971997AH1-543 GEN
Solar/Wind Harmer
4.485
957471AF2-041 GEN
Solar/Wind Harmer
25.504
959081AF2-199 GEN
Solar/Wind Harmer
8.501
971067AG2-660 GEN
Solar/Wind Harmer
2.834
971087AG2-675 GEN
Solar/Wind Harmer
4.368
965091AG1-374 GEN
Solar/Wind Harmer
24.551
959611AF2-252 GEN
Solar/Wind Harmer
2.728
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.663
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.86
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.897
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.346
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.686
960611AF2-352 GEN
Solar/Wind Harmer
2.728
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.921
942221AE2-234 GEN
Solar/Wind Harmer
3.241
970241AG2-163 GEN
Solar/Wind Harmer
4.6
276615X2-022 GEN
Solar/Wind Harmer
0.081
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970291AG2-192 GEN
Solar/Wind Harmer
1.017
970291AG2-192 GEN
Solar/Wind Harmer
0.469
270031AE2-169
Solar/Wind Harmer
4.257
270599AE1-208 GEN
Solar/Wind Harmer
7.096
971613AH1-306 GEN
Solar/Wind Harmer
3.702
276916AD2-100_GEN
Solar/Wind Harmer
16.116
276911AD2-131_GEN
Solar/Wind Harmer
1.062
270246TR4_N_V150
Solar/Wind Harmer
0.049
270247TR4_N_V136
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
17.5
945391AF1-204 GEN
Solar/Wind Harmer
7.946
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270201AC2-176 GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
5.222
247621Y3-024
Adder
0.245
926881AC1-175 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.284
270383AD1-128 GEN
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.232
970883AG2-550 GEN
Solar/Wind Harmer
6.689
970885AG2-551 GEN
Solar/Wind Harmer
2.23
270054AF2-122 C O1
Solar/Wind Helper
1.547
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274822ROCKFORD ;11
Adder
23.866
970819AG2-516 GEN
Solar/Wind Harmer
10.148
970569AG2-363 GEN
Solar/Wind Harmer
25.306
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.202
274766LEE CO EC;7U
Adder
11.07
965651AG1-433 GEN
Solar/Wind Harmer
2.449
276708O09 GEN2
Solar/Wind Harmer
0.295
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
11.569
958861AF2-177 GEN
Solar/Wind Harmer
3.567
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
18.662
276621W2-048 GEN
Solar/Wind Harmer
0.393
270594AE1-207 GEN
Solar/Wind Harmer
8.639
270032AE2-172
Solar/Wind Harmer
5.142
965911AG1-460 GEN
Solar/Wind Harmer
1.542
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
8.459
270005AE1-210 C O1
Solar/Wind Harmer
1.624
970825AG2-519 GEN
Solar/Wind Harmer
2.629
965421AG1-410 GEN
Solar/Wind Harmer
21.55
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.196
246936BC-WTG1
Solar/Wind Harmer
0.284
270489AE1-102 GEN1
Solar/Wind Harmer
0.915
24728605AND G2
Adder
3.809
970091AG2-072 GEN
Adder
75.982
970773AG2-487 GEN
Solar/Wind Harmer
1.155
972203AH1-686 GEN
Adder
1.998
959341AF2-225 GEN
Solar/Wind Harmer
8.677
946321AF1-296 GEN
Solar/Wind Harmer
4.601
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
10.858
945581AF1-223 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
3.469
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
971549AH1-272 GEN
Solar/Wind Harmer
16.367
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
965041AG1-368 GEN
Solar/Wind Harmer
7.859
970289AG2-191 GEN
Solar/Wind Harmer
1.486
971609AH1-304 GEN
Solar/Wind Harmer
1.264
247521TR3_G114
Solar/Wind Harmer
0.275
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.432
964611AG1-324 GEN
Solar/Wind Harmer
2.855
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.891
247536S-71 GEN
Solar/Wind Harmer
0.278
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
4.682
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.586
270578AF1-285 GEN2
Solar/Wind Harmer
0.405
957381AF2-032 GEN
Solar/Wind Harmer
1.75
942481AE2-261 GEN
Solar/Wind Harmer
23.05
270004AE1-209 GEN
Solar/Wind Harmer
1.624
970193AG2-126 GEN
Solar/Wind Harmer
11.218
24695305TIMB G C
Solar/Wind Harmer
0.627
970825AG2-519 GEN
Solar/Wind Harmer
5.579
946031AF1-268 GEN
Solar/Wind Harmer
6.994
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.967
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.253
270491AE1-102 GEN2
Solar/Wind Harmer
0.915
24728705AND G3
Adder
7.966
24728505AND G1
Adder
3.809
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
270391AF1-285 GEN3
Solar/Wind Harmer
0.405
NYPJM->LTFIMP_NY
CLTF
3.757
LGEELTFEXP_LGEE->PJM
CLTF
5.535
WECLTFEXP_WEC->PJM
CLTF
4.636
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.983
CPLELTFEXP_CPLE->PJM
CLTF
3.243
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.462
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.207
MECLTFEXP_MEC->PJM
CLTF
18.523
SIGELTFEXP_SIGE->PJM
CLTF
0.475
AG2-052LTFEXP_AG2-052->PJM
LTF
0.286
AH1-155LTFEXP_AH1-155->PJM
LTF
0.429
LAGNLTFEXP_LAGN->PJM
CLTF
16.319
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.038
TVALTFEXP_TVA->PJM
CLTF
7.716

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P2-2_#8072_05MARYSV 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.48 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5369.79
MW Contribution:
15.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
1.482
24721805FLATG3
50/50
1.482
24344105CKG2
50/50
9.343
962761AG1-125 GEN
Solar/Wind Harmer
112.309
970149AG2-104 GEN
Solar/Wind Harmer
69.351
970155AG2-107 GEN
Solar/Wind Harmer
48.972
972207SS24-0001
Solar/Wind Harmer
24.644
274773LINCOLN ;4U
Adder
6.931
274774LINCOLN ;5U
Adder
6.931
274723RIVER EC ;12
Adder
19.685
270216AD2-079_GEN
Solar/Wind Harmer
0.663
274751CRETE EC ;1U
Adder
5.351
274754CRETE EC ;4U
Adder
5.351
274812UNIV PK N;8U
Adder
5.469
274802UNIV PARK;5U
Adder
6.353
941551AE2-152 GEN
Solar/Wind Harmer
4.928
957891AF2-083 GEN
Solar/Wind Harmer
16.274
274676JOLIET 29;8U
Adder
33.244
274674JOLIET 9 ;6U
Adder
16.661
960681AF2-359 GEN
Solar/Wind Harmer
4.234
274775LINCOLN ;6U
Adder
6.931
274776LINCOLN ;7U
Adder
6.931
274777LINCOLN ;8U
Adder
6.931
270526AF1-158 GEN
Solar/Wind Harmer
5.027
971771AH1-392 GEN
Solar/Wind Harmer
9.974
270071AF1-092 GEN
Solar/Wind Harmer
16.362
274827FISK ;RP
Adder
8.458
972228AH1-698 GEN2
Adder
4.038
972227AH1-698 GEN1
Adder
2.843
960591AF2-350 GEN
Solar/Wind Harmer
10.898
972037AH1-567 GEN1
Adder
0.199
274800UNIV PARK;3U
Adder
6.351
274801UNIV PARK;4U
Adder
6.351
274687WILL CNTY;4U
Adder
30.296
274687WILL CNTY;4U
Adder
30.296
274675JOLIET 29;7U
Adder
33.244
274675JOLIET 29;7U
Adder
32.057
970833AG2-524 GEN
Solar/Wind Harmer
9.439
970833AG2-524 GEN
Solar/Wind Harmer
4.39
274728ELWOOD EC;5P
Adder
17.77
274731ELWOOD EC;2P
Adder
17.77
274733ELWOOD EC;3P
Adder
17.77
274735ELWOOD EC;4P
Adder
17.77
276893AG1-478 C
Solar/Wind Harmer
0.594
274744AC1-111 GEN8
Adder
6.017
274746AC1-111 G10
Adder
6.017
944161AF1-084 GEN
Solar/Wind Harmer
2.35
970073AG2-061 GEN
Solar/Wind Harmer
2.447
971675AH1-338 GEN
Solar/Wind Harmer
18.851
971411AH1-196 GEN
Solar/Wind Harmer
15.708
276861AD2-134 GEN
Solar/Wind Harmer
1.869
276863AD2-134 GEN
Solar/Wind Harmer
1.869
971171AH1-044 GEN
Solar/Wind Harmer
20.831
274863CRW1-WTG
Solar/Wind Harmer
5.799
274864CRW2-WTG
Solar/Wind Harmer
5.799
274823ROCKFORD ;21
Adder
20.237
276889AE2-281 GEN
Solar/Wind Harmer
1.991
958391AF2-133 GEN
Solar/Wind Harmer
9.384
274856ECOGROVE ;U1
Solar/Wind Harmer
3.481
276611AD2-172 GEN
Solar/Wind Harmer
2.641
276612AE2-035 GEN
Solar/Wind Harmer
2.641
959141AF2-205 GEN
Solar/Wind Harmer
6.218
926823AC1-168 GEN
Solar/Wind Harmer
4.418
971681AH1-341 GEN
Solar/Wind Harmer
15.409
24729505KEY G4
Adder
6.649
972267AH1-718 GEN
Adder
4.228
241955AC1-078 GEN
Solar/Wind Helper
2.298
241973AD2-163_GEN1
Solar/Wind Helper
1.862
241974AD2-163_GEN2
Solar/Wind Helper
1.862
945631AF1-228 GEN
Solar/Wind Helper
1.837
24721705FLATG2
50/50
22.01
270102X2-052 ST
50/50
1.799
270100X2-052 CT1
50/50
1.662
270101X2-052 CT2
50/50
1.662
970349AG2-230 GEN
Solar/Wind Harmer
17.966
965681AG1-436 GEN
Solar/Wind Harmer
14.006
965791AG1-447 GEN
Solar/Wind Harmer
7.166
274770LINCOLN ;1U
Adder
6.931
274771LINCOLN ;2U
Adder
6.931
274805UNIV PK N;1U
Adder
5.481
274808UNIV PK N;4U
Adder
5.445
274888KELLY CRK;1U
Solar/Wind Harmer
6.431
276776AD2-060 GEN
Solar/Wind Harmer
0.456
958011AF2-095 GEN
Solar/Wind Harmer
15.693
970941AG2-585 GEN
Solar/Wind Harmer
5.994
276897AD1-100 C
Solar/Wind Harmer
50.481
274674JOLIET 9 ;6U
Adder
16.661
276893AG1-478 C
Solar/Wind Harmer
0.474
961051AF2-396 GEN
Solar/Wind Harmer
17.047
961051AF2-396 GEN
Solar/Wind Harmer
7.929
274695ROCKY RD ;2P
Adder
11.868
274693ROCKY RD ;1P
Adder
11.751
274697ROCKY RD ;3P
Adder
3.224
274696ROCKY RD ;4P
Adder
12.148
274683WAUKEGAN ;8U
Adder
22.4
274683WAUKEGAN ;8U
Adder
18.882
958481AF2-142 GEN
Solar/Wind Harmer
15.94
247620Y3-023
Adder
0.489
962691AG1-118 GEN
Solar/Wind Harmer
31.798
270535AF1-215 GEN1
Solar/Wind Harmer
4.804
270536AF1-215 GEN2
Solar/Wind Harmer
4.804
960751AF2-366 GEN
Solar/Wind Harmer
3.035
958491AF2-143 GEN
Solar/Wind Harmer
15.782
276901AD2-066 C O1
Solar/Wind Harmer
3.686
971341AH1-150 GEN
Solar/Wind Harmer
20.831
971343AH1-151 GEN
Solar/Wind Harmer
20.831
276872AE1-163_GEN1
Solar/Wind Harmer
6.967
276876AE1-163_GEN2
Solar/Wind Harmer
6.967
972235AH1-702 GEN1
Adder
2.613
972236AH1-702 GEN2
Adder
2.272
274764LEE CO EC;5U
Adder
9.547
274765LEE CO EC;6U
Adder
9.547
274762LEE CO EC;3U
Adder
9.525
274763LEE CO EC;4U
Adder
9.435
270054AF2-122 C O1
Solar/Wind Helper
2.097
946101AF1-275 GEN
Solar/Wind Helper
0.802
270349AD2-093_GEN
Solar/Wind Helper
1.818
270471AD2-092_GEN
Solar/Wind Helper
1.818
253383AE2-342_GEN
Solar/Wind Helper
0.854
241960AC2-195 GEN
Solar/Wind Helper
1.419
938861AE1-114 GEN
Solar/Wind Harmer
2.265
274732ELWOOD EC;7P
Adder
17.77
274871GR RIDGE ;2U
Solar/Wind Harmer
8.31
274847GR RIDGE ;BU
Solar/Wind Harmer
5.464
945111AF1-176 GEN
Solar/Wind Harmer
19.236
24639705ELKHART HY
Adder
0.165
274745AC1-111 GEN9
Adder
6.017
970373AG2-245 GEN
Solar/Wind Harmer
22.569
270449AD2-020 GEN
Solar/Wind Harmer
3.003
943021AE2-325 GEN
Solar/Wind Harmer
3.902
274682WAUKEGAN ;7U
Adder
19.124
274828WAUKEGAN ;BP
Adder
11.742
276694AA1-018 GEN2
Solar/Wind Harmer
6.705
276691AA1-018 GEN1
Solar/Wind Harmer
0.801
274861TOP CROP ;1U
Solar/Wind Harmer
6.434
270055AF2-134 C O1
Solar/Wind Harmer
3.202
962781AG1-127 GEN
Solar/Wind Harmer
10.059
274872LEEDK;1U
Solar/Wind Harmer
8.667
939401AE1-172 GEN
Solar/Wind Harmer
14.675
276805AD2-038 GEN
Solar/Wind Harmer
5.395
276882AE2-255 GEN
Solar/Wind Harmer
3.536
971997AH1-543 GEN
Solar/Wind Harmer
16.495
24441205WTRV SLR C
Solar/Wind Harmer
0.141
958381AF2-132 GEN
Solar/Wind Harmer
9.461
957471AF2-041 GEN
Solar/Wind Harmer
31.247
959081AF2-199 GEN
Solar/Wind Harmer
10.416
971067AG2-660 GEN
Solar/Wind Harmer
2.422
964861AG1-349 GEN
Solar/Wind Harmer
8.186
971917AH1-482 GEN
Solar/Wind Harmer
9.444
274822ROCKFORD ;11
Adder
20.385
970819AG2-516 GEN
Solar/Wind Harmer
12.405
970569AG2-363 GEN
Solar/Wind Harmer
30.826
274761LEE CO EC;2U
Adder
9.525
274766LEE CO EC;7U
Adder
9.413
270520AE2-214 GEN
Solar/Wind Helper
3.207
270286AF1-227 GEN2
Solar/Wind Helper
0.87
24722005FLATG5
50/50
1.482
24721905FLATG4
50/50
27.071
962771AG1-126 GEN
Solar/Wind Harmer
112.309
970153AG2-106 GEN
Solar/Wind Harmer
48.972
971347AH1-153 GEN
Solar/Wind Harmer
5.989
274772LINCOLN ;3U
Adder
6.931
24441505OLIV SLR
Solar/Wind Harmer
0.148
270043AE2-236 GEN
Solar/Wind Harmer
6.061
247643Z2-116 C
Solar/Wind Harmer
0.076
274724RIVER EC ;11
Adder
19.46
970707AG2-453 GEN
Solar/Wind Harmer
30.756
276164X3-005 C
Solar/Wind Harmer
0.77
972231SS25-0005
Solar/Wind Harmer
10.389
972181SS23-001
Solar/Wind Harmer
6.493
274752CRETE EC ;2U
Adder
5.351
274753CRETE EC ;3U
Adder
5.351
972259AH1-714 GEN
Adder
20.849
274814UNIV PK N;0U
Adder
5.517
274807UNIV PK N;3U
Adder
5.505
274811UNIV PK N;7U
Adder
5.469
274826FISK ;BP
Adder
11.934
274887GEN-1.85
Solar/Wind Harmer
5.806
276772AC2-154 GEN
Solar/Wind Harmer
3.041
276843GEN-1.7
Solar/Wind Harmer
0.625
276806AD2-047 C O1
Solar/Wind Harmer
11.659
274803UNIV PARK;6U
Adder
6.353
972038AH1-567 GEN2
Adder
0.398
270505AE1-170 C O1
Solar/Wind Harmer
16.306
939351AE1-166 GEN
Solar/Wind Harmer
6.445
274676JOLIET 29;8U
Adder
32.056
274729ELWOOD EC;1P
Adder
17.77
274730ELWOOD EC;6P
Adder
17.77
274734ELWOOD EC;8P
Adder
17.77
274736ELWOOD EC;9P
Adder
17.77
943121AE2-341 GEN
Solar/Wind Harmer
16.181
943591AF1-030 GEN
Solar/Wind Harmer
10.787
945111AF1-176 GEN
Solar/Wind Harmer
6.096
274682WAUKEGAN ;7U
Adder
19.124
274862TOP CROP ;2U
Solar/Wind Harmer
5.372
944531AF1-118 GEN
Solar/Wind Harmer
36.716
276868AE1-113 GEN
Solar/Wind Harmer
10.607
274879MINONK ;1U
Solar/Wind Harmer
7.072
276799AD1-013 GEN
Solar/Wind Harmer
2.315
946671AF1-331 GEN
Solar/Wind Harmer
0.439
274855GSG-6 ;RU
Solar/Wind Harmer
3.866
274850MENDOTA H;RU
Solar/Wind Harmer
2.688
276602WESTBROOK C
Solar/Wind Harmer
2.225
964401AG1-302 GEN
Solar/Wind Harmer
9.461
959091AF2-200 GEN
Solar/Wind Harmer
20.831
270063AE2-323 C
Solar/Wind Harmer
2.285
970571AG2-364 GEN
Solar/Wind Harmer
20.55
274760LEE CO EC;1U
Adder
9.525
274767LEE CO EC;8U
Adder
9.413
270284AF1-227 GEN1
Solar/Wind Helper
2.373
270287AF1-227 GEN3
Solar/Wind Helper
0.87
960801AF2-371 GEN
Solar/Wind Helper
0.964
964871AG1-351 GEN
Solar/Wind Helper
0.665
NYPJM->LTFIMP_NY
CLTF
2.454
LGEELTFEXP_LGEE->PJM
CLTF
3.221
WECLTFEXP_WEC->PJM
CLTF
3.955
CBM West 1LTFEXP_CBM-W1->PJM
CBM
114.418
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.259
MECLTFEXP_MEC->PJM
CLTF
15.133
SIGELTFEXP_SIGE->PJM
CLTF
0.321
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.92
LAGNLTFEXP_LAGN->PJM
CLTF
11.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.139
TVALTFEXP_TVA->PJM
CLTF
5.225

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-3_#8072_05MARYSV 765_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#8072_05MARYSV 765_2_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.24 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5084.88
MW Contribution:
11.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24722005FLATG5
50/50
1.482
24721905FLATG4
50/50
27.071
962771AG1-126 GEN
Solar/Wind Harmer
94.712
970153AG2-106 GEN
Solar/Wind Harmer
60.48
971347AH1-153 GEN
Solar/Wind Harmer
4.178
274772LINCOLN ;3U
Adder
9.435
24721805FLATG3
50/50
1.482
24344105CKG2
50/50
9.343
962761AG1-125 GEN
Solar/Wind Harmer
94.712
970149AG2-104 GEN
Solar/Wind Harmer
51.146
970155AG2-107 GEN
Solar/Wind Harmer
60.48
274773LINCOLN ;4U
Adder
9.435
274774LINCOLN ;5U
Adder
9.435
274723RIVER EC ;12
Adder
19.685
274751CRETE EC ;1U
Adder
9.02
274754CRETE EC ;4U
Adder
9.02
274812UNIV PK N;8U
Adder
5.469
274802UNIV PARK;5U
Adder
6.353
941551AE2-152 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
12.616
274676JOLIET 29;8U
Adder
33.244
274674JOLIET 9 ;6U
Adder
16.661
274732ELWOOD EC;7P
Adder
17.77
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
13.42
24639705ELKHART HY
Adder
0.165
24721705FLATG2
50/50
22.01
270102X2-052 ST
50/50
1.799
270100X2-052 CT1
50/50
1.662
270101X2-052 CT2
50/50
1.662
970349AG2-230 GEN
Solar/Wind Harmer
12.534
965681AG1-436 GEN
Solar/Wind Harmer
9.772
965791AG1-447 GEN
Solar/Wind Harmer
7.166
274770LINCOLN ;1U
Adder
9.435
274771LINCOLN ;2U
Adder
9.435
274805UNIV PK N;1U
Adder
5.481
274808UNIV PK N;4U
Adder
5.445
274888KELLY CRK;1U
Solar/Wind Harmer
0.443
276776AD2-060 GEN
Solar/Wind Harmer
0.811
958011AF2-095 GEN
Solar/Wind Harmer
10.949
970941AG2-585 GEN
Solar/Wind Harmer
4.182
276897AD1-100 C
Solar/Wind Harmer
18.954
274674JOLIET 9 ;6U
Adder
16.661
276893AG1-478 C
Solar/Wind Harmer
0.502
961051AF2-396 GEN
Solar/Wind Harmer
14.985
961051AF2-396 GEN
Solar/Wind Harmer
9.99
274695ROCKY RD ;2P
Adder
11.868
274693ROCKY RD ;1P
Adder
11.751
274697ROCKY RD ;3P
Adder
3.224
274696ROCKY RD ;4P
Adder
12.148
274683WAUKEGAN ;8U
Adder
22.4
274683WAUKEGAN ;8U
Adder
18.882
958481AF2-142 GEN
Solar/Wind Harmer
11.121
247620Y3-023
Adder
0.489
962691AG1-118 GEN
Solar/Wind Harmer
22.185
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.011
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.533
971343AH1-151 GEN
Solar/Wind Harmer
14.533
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.613
972236AH1-702 GEN2
Adder
2.272
938861AE1-114 GEN
Solar/Wind Harmer
4.06
274764LEE CO EC;5U
Adder
9.547
274765LEE CO EC;6U
Adder
9.547
274762LEE CO EC;3U
Adder
9.525
274763LEE CO EC;4U
Adder
9.435
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.14
276645AC1-214 GEN1
Solar/Wind Harmer
0.276
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.249
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.272
944541AF1-119 GEN
Solar/Wind Harmer
0.446
960971AF2-388 GEN
Solar/Wind Harmer
3.922
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.752
276615X2-022 GEN
Solar/Wind Harmer
0.066
276838X2-022 GEN2
Solar/Wind Harmer
0.36
970241AG2-163 GEN
Solar/Wind Harmer
3.681
276916AD2-100_GEN
Solar/Wind Harmer
12.928
276911AD2-131_GEN
Solar/Wind Harmer
0.852
942221AE2-234 GEN
Solar/Wind Harmer
2.468
970291AG2-192 GEN
Solar/Wind Harmer
0.785
970291AG2-192 GEN
Solar/Wind Harmer
0.362
270054AF2-122 C O1
Solar/Wind Helper
2.097
946101AF1-275 GEN
Solar/Wind Helper
0.802
270349AD2-093_GEN
Solar/Wind Helper
1.818
270471AD2-092_GEN
Solar/Wind Helper
1.818
253383AE2-342_GEN
Solar/Wind Helper
0.854
241960AC2-195 GEN
Solar/Wind Helper
1.419
274745AC1-111 GEN9
Adder
6.017
970373AG2-245 GEN
Solar/Wind Harmer
15.746
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.902
274682WAUKEGAN ;7U
Adder
19.124
274828WAUKEGAN ;BP
Adder
11.742
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.205
274861TOP CROP ;1U
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.023
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.495
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.854
971997AH1-543 GEN
Solar/Wind Harmer
3.836
958381AF2-132 GEN
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
21.8
959081AF2-199 GEN
Solar/Wind Harmer
7.267
971067AG2-660 GEN
Solar/Wind Harmer
2.422
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.444
274822ROCKFORD ;11
Adder
20.385
970819AG2-516 GEN
Solar/Wind Harmer
8.655
970569AG2-363 GEN
Solar/Wind Harmer
21.506
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.525
274766LEE CO EC;7U
Adder
9.413
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.899
276708O09 GEN2
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.276
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.688
965651AG1-433 GEN
Solar/Wind Harmer
1.961
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.83
276621W2-048 GEN
Solar/Wind Harmer
0.32
963741AG1-226 GEN
Solar/Wind Harmer
14.933
965011AG1-365 GEN
Solar/Wind Harmer
6.284
945371AF1-202 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
1.24
270520AE2-214 GEN
Solar/Wind Helper
3.207
270286AF1-227 GEN2
Solar/Wind Helper
0.87
24721605FLATG1
50/50
1.482
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
9.435
274776LINCOLN ;7U
Adder
9.435
274777LINCOLN ;8U
Adder
9.435
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
7.732
270071AF1-092 GEN
Solar/Wind Harmer
14.586
274827FISK ;RP
Adder
8.458
972228AH1-698 GEN2
Adder
4.038
972227AH1-698 GEN1
Adder
2.843
960591AF2-350 GEN
Solar/Wind Harmer
7.603
972037AH1-567 GEN1
Adder
0.199
274800UNIV PARK;3U
Adder
6.351
274801UNIV PARK;4U
Adder
6.351
274687WILL CNTY;4U
Adder
30.296
274687WILL CNTY;4U
Adder
30.296
274675JOLIET 29;7U
Adder
33.244
274675JOLIET 29;7U
Adder
32.057
970833AG2-524 GEN
Solar/Wind Harmer
8.297
970833AG2-524 GEN
Solar/Wind Harmer
5.531
274728ELWOOD EC;5P
Adder
17.77
274731ELWOOD EC;2P
Adder
17.77
274733ELWOOD EC;3P
Adder
17.77
274735ELWOOD EC;4P
Adder
17.77
274744AC1-111 GEN8
Adder
6.017
274746AC1-111 G10
Adder
6.017
970073AG2-061 GEN
Solar/Wind Harmer
2.447
971675AH1-338 GEN
Solar/Wind Harmer
2.85
971411AH1-196 GEN
Solar/Wind Harmer
10.959
276861AD2-134 GEN
Solar/Wind Harmer
0.13
276863AD2-134 GEN
Solar/Wind Harmer
0.13
971171AH1-044 GEN
Solar/Wind Harmer
14.533
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
20.237
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.168
959141AF2-205 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.219
971681AH1-341 GEN
Solar/Wind Harmer
11.539
24729505KEY G4
Adder
6.649
970169AG2-114 GEN
Solar/Wind Harmer
7.15
971611AH1-305 GEN
Solar/Wind Harmer
4.239
970031AG2-029 GEN
Solar/Wind Harmer
3.854
972267AH1-718 GEN
Adder
4.228
276741O09 GEN1
Solar/Wind Harmer
0.25
274877BISHOP HL;1U
Solar/Wind Harmer
0.234
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.266
946321AF1-296 GEN
Solar/Wind Harmer
3.872
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
13.514
276668AB2-070 GEN1
Solar/Wind Harmer
0.255
276848AB2-070 GEN3
Solar/Wind Harmer
0.254
276849AB2-070 GEN2
Solar/Wind Harmer
0.255
963841AG1-237 GEN
Solar/Wind Harmer
2.803
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
4.399
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.148
241955AC1-078 GEN
Solar/Wind Helper
2.298
241973AD2-163_GEN1
Solar/Wind Helper
1.862
241974AD2-163_GEN2
Solar/Wind Helper
1.862
945631AF1-228 GEN
Solar/Wind Helper
1.837
270043AE2-236 GEN
Solar/Wind Harmer
4.934
274724RIVER EC ;11
Adder
19.46
970707AG2-453 GEN
Solar/Wind Harmer
25.034
274752CRETE EC ;2U
Adder
9.02
274753CRETE EC ;3U
Adder
9.02
972259AH1-714 GEN
Adder
20.849
274814UNIV PK N;0U
Adder
5.517
274807UNIV PK N;3U
Adder
5.505
274811UNIV PK N;7U
Adder
5.469
274826FISK ;BP
Adder
11.934
274887GEN-1.85
Solar/Wind Harmer
0.198
276843GEN-1.7
Solar/Wind Harmer
0.246
276806AD2-047 C O1
Solar/Wind Harmer
4.309
274803UNIV PARK;6U
Adder
6.353
972038AH1-567 GEN2
Adder
0.398
270505AE1-170 C O1
Solar/Wind Harmer
7.964
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.056
274729ELWOOD EC;1P
Adder
17.77
274730ELWOOD EC;6P
Adder
17.77
274734ELWOOD EC;8P
Adder
17.77
274736ELWOOD EC;9P
Adder
17.77
943121AE2-341 GEN
Solar/Wind Harmer
12.618
943591AF1-030 GEN
Solar/Wind Harmer
8.391
945111AF1-176 GEN
Solar/Wind Harmer
6.096
274682WAUKEGAN ;7U
Adder
19.124
274862TOP CROP ;2U
Solar/Wind Harmer
1
944531AF1-118 GEN
Solar/Wind Harmer
32.801
276868AE1-113 GEN
Solar/Wind Harmer
1.463
274879MINONK ;1U
Solar/Wind Harmer
0.305
946671AF1-331 GEN
Solar/Wind Harmer
0.78
274855GSG-6 ;RU
Solar/Wind Harmer
0.267
274850MENDOTA H;RU
Solar/Wind Harmer
0.085
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959091AF2-200 GEN
Solar/Wind Harmer
14.533
270063AE2-323 C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
14.338
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.525
274767LEE CO EC;8U
Adder
9.413
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.234
965931AG1-462 GEN
Solar/Wind Harmer
17.553
971087AG2-675 GEN
Solar/Wind Harmer
3.671
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.861
965091AG1-374 GEN
Solar/Wind Harmer
20.448
959611AF2-252 GEN
Solar/Wind Harmer
2.272
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
2.994
965021AG1-366 GEN
Solar/Wind Harmer
2.095
957381AF2-032 GEN
Solar/Wind Harmer
1.409
942481AE2-261 GEN
Solar/Wind Harmer
18.543
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.665
270284AF1-227 GEN1
Solar/Wind Helper
2.373
270287AF1-227 GEN3
Solar/Wind Helper
0.87
960801AF2-371 GEN
Solar/Wind Helper
0.964
964871AG1-351 GEN
Solar/Wind Helper
0.665
NYPJM->LTFIMP_NY
CLTF
2.454
LGEELTFEXP_LGEE->PJM
CLTF
3.221
WECLTFEXP_WEC->PJM
CLTF
3.955
CBM West 1LTFEXP_CBM-W1->PJM
CBM
114.418
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.259
CPLELTFEXP_CPLE->PJM
CLTF
1.997
MECLTFEXP_MEC->PJM
CLTF
15.133
SIGELTFEXP_SIGE->PJM
CLTF
0.321
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.92
LAGNLTFEXP_LAGN->PJM
CLTF
11.631
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.139
TVALTFEXP_TVA->PJM
CLTF
5.225

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.76 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4482.29
MW Contribution:
11.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.749
270100X2-052 CT1
50/50
1.616
270101X2-052 CT2
50/50
1.616
24643105BUCHANAN
50/50
0.014
247620Y3-023
50/50
0.526
274770LINCOLN ;1U
50/50
9.616
274771LINCOLN ;2U
50/50
9.616
970349AG2-230 GEN
Solar/Wind Harmer
12.041
965681AG1-436 GEN
Solar/Wind Harmer
9.504
965791AG1-447 GEN
Solar/Wind Harmer
6.97
961051AF2-396 GEN
Solar/Wind Harmer
14.959
961051AF2-396 GEN
Solar/Wind Harmer
9.973
274805UNIV PK N;1U
Adder
5.303
274808UNIV PK N;4U
Adder
5.268
274888KELLY CRK;1U
Solar/Wind Harmer
0.428
276776AD2-060 GEN
Solar/Wind Harmer
0.783
958011AF2-095 GEN
Solar/Wind Harmer
10.572
970941AG2-585 GEN
Solar/Wind Harmer
4.038
276897AD1-100 C
Solar/Wind Harmer
18.287
274674JOLIET 9 ;6U
Adder
16.082
276893AG1-478 C
Solar/Wind Harmer
0.485
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274695ROCKY RD ;2P
Adder
11.454
274693ROCKY RD ;1P
Adder
11.341
274697ROCKY RD ;3P
Adder
3.111
274696ROCKY RD ;4P
Adder
11.724
958481AF2-142 GEN
Solar/Wind Harmer
10.754
274683WAUKEGAN ;8U
Adder
21.627
274683WAUKEGAN ;8U
Adder
18.23
962691AG1-118 GEN
Solar/Wind Harmer
21.414
958491AF2-143 GEN
Solar/Wind Harmer
10.655
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.045
971343AH1-151 GEN
Solar/Wind Harmer
14.045
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.526
972236AH1-702 GEN2
Adder
2.196
938861AE1-114 GEN
Solar/Wind Harmer
3.928
944541AF1-119 GEN
Solar/Wind Harmer
0.462
960971AF2-388 GEN
Solar/Wind Harmer
4.056
274764LEE CO EC;5U
Adder
9.237
274765LEE CO EC;6U
Adder
9.237
274762LEE CO EC;3U
Adder
9.215
274763LEE CO EC;4U
Adder
9.128
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.104
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.191
942221AE2-234 GEN
Solar/Wind Harmer
2.684
960611AF2-352 GEN
Solar/Wind Harmer
2.217
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.745
944231AF1-091 GEN
Solar/Wind Harmer
15.08
270246TR4_N_V150
Solar/Wind Harmer
0.042
270247TR4_N_V136
Solar/Wind Harmer
0.042
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.669
970291AG2-192 GEN
Solar/Wind Harmer
0.817
970291AG2-192 GEN
Solar/Wind Harmer
0.377
276615X2-022 GEN
Solar/Wind Harmer
0.065
276838X2-022 GEN2
Solar/Wind Harmer
0.353
270031AE2-169
Solar/Wind Harmer
3.44
270599AE1-208 GEN
Solar/Wind Harmer
5.734
971613AH1-306 GEN
Solar/Wind Harmer
2.966
276916AD2-100_GEN
Solar/Wind Harmer
12.749
276911AD2-131_GEN
Solar/Wind Harmer
0.84
246937BC-WTG2
Solar/Wind Harmer
0.244
270054AF2-122 C O1
Solar/Wind Helper
1.656
24344105CKG2
50/50
8.859
270143AC1-141 CT2_
50/50
2.617
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.55
274773LINCOLN ;4U
50/50
9.616
274774LINCOLN ;5U
50/50
9.616
962761AG1-125 GEN
Solar/Wind Harmer
74.627
970149AG2-104 GEN
Solar/Wind Harmer
40.3
970155AG2-107 GEN
Solar/Wind Harmer
47.655
957891AF2-083 GEN
Solar/Wind Harmer
12.55
945111AF1-176 GEN
Solar/Wind Harmer
13.401
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.895
274723RIVER EC ;12
Adder
19.037
274751CRETE EC ;1U
Adder
8.738
274754CRETE EC ;4U
Adder
8.738
965011AG1-365 GEN
Solar/Wind Harmer
7.385
274812UNIV PK N;8U
Adder
5.291
274802UNIV PARK;5U
Adder
6.138
970373AG2-245 GEN
Solar/Wind Harmer
15.385
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
32.088
274674JOLIET 9 ;6U
Adder
16.082
274732ELWOOD EC;7P
Adder
17.157
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.803
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.165
274682WAUKEGAN ;7U
Adder
18.463
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
11.336
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.78
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.257
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.318
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.826
971997AH1-543 GEN
Solar/Wind Harmer
3.71
957471AF2-041 GEN
Solar/Wind Harmer
21.068
959081AF2-199 GEN
Solar/Wind Harmer
7.023
971067AG2-660 GEN
Solar/Wind Harmer
2.341
274822ROCKFORD ;11
Adder
19.703
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.741
970819AG2-516 GEN
Solar/Wind Harmer
8.368
970569AG2-363 GEN
Solar/Wind Harmer
20.843
965651AG1-433 GEN
Solar/Wind Harmer
2.028
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.215
274766LEE CO EC;7U
Adder
9.107
276708O09 GEN2
Solar/Wind Harmer
0.242
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
958861AF2-177 GEN
Solar/Wind Harmer
2.941
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.439
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
14.886
276621W2-048 GEN
Solar/Wind Harmer
0.314
270024AE2-089 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
6.922
270032AE2-172
Solar/Wind Harmer
4.12
965421AG1-410 GEN
Solar/Wind Harmer
18.52
965911AG1-460 GEN
Solar/Wind Harmer
1.222
246936BC-WTG1
Solar/Wind Harmer
0.244
270489AE1-102 GEN1
Solar/Wind Harmer
0.786
276903AD2-071 C
Solar/Wind Harmer
6.725
270144AC1-141 ST1_
50/50
2.311
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.028
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.616
274776LINCOLN ;7U
50/50
9.616
274777LINCOLN ;8U
50/50
9.616
270071AF1-092 GEN
Solar/Wind Harmer
14.768
971771AH1-392 GEN
Solar/Wind Harmer
7.622
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
4.047
959331AF2-224 GEN
Solar/Wind Harmer
5.169
274827FISK ;RP
Adder
8.169
972037AH1-567 GEN1
Adder
0.193
960591AF2-350 GEN
Solar/Wind Harmer
7.341
274800UNIV PARK;3U
Adder
6.134
274801UNIV PARK;4U
Adder
6.134
972228AH1-698 GEN2
Adder
3.896
972227AH1-698 GEN1
Adder
2.744
24729505KEY G4
Adder
6.793
274687WILL CNTY;4U
Adder
29.249
274687WILL CNTY;4U
Adder
29.249
274675JOLIET 29;7U
Adder
32.088
274675JOLIET 29;7U
Adder
30.942
274728ELWOOD EC;5P
Adder
17.157
274731ELWOOD EC;2P
Adder
17.157
274733ELWOOD EC;3P
Adder
17.157
274735ELWOOD EC;4P
Adder
17.157
970833AG2-524 GEN
Solar/Wind Harmer
8.005
970833AG2-524 GEN
Solar/Wind Harmer
5.336
274744AC1-111 GEN8
Adder
5.803
274746AC1-111 G10
Adder
5.803
970073AG2-061 GEN
Solar/Wind Harmer
2.368
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.753
971411AH1-196 GEN
Solar/Wind Harmer
10.588
276861AD2-134 GEN
Solar/Wind Harmer
0.126
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
14.045
274823ROCKFORD ;21
Adder
19.56
971611AH1-305 GEN
Solar/Wind Harmer
4.163
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
926823AC1-168 GEN
Solar/Wind Harmer
1.181
970169AG2-114 GEN
Solar/Wind Harmer
6.939
971681AH1-341 GEN
Solar/Wind Harmer
11.162
972267AH1-718 GEN
Adder
4.093
276741O09 GEN1
Solar/Wind Harmer
0.242
971549AH1-272 GEN
Solar/Wind Harmer
14.066
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
9.126
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.079
965041AG1-368 GEN
Solar/Wind Harmer
6.739
946321AF1-296 GEN
Solar/Wind Harmer
3.754
274854TWINGROVE;U2
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.235
965051AG1-369 GEN
Solar/Wind Harmer
3.245
963841AG1-237 GEN
Solar/Wind Harmer
2.784
276668AB2-070 GEN1
Solar/Wind Harmer
0.25
276848AB2-070 GEN3
Solar/Wind Harmer
0.249
276849AB2-070 GEN2
Solar/Wind Harmer
0.25
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.194
971609AH1-304 GEN
Solar/Wind Harmer
1.022
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.766
270142AC1-141 CT1_
50/50
2.617
24642205MAYFLWER
50/50
0.04
274772LINCOLN ;3U
50/50
9.616
944961AF1-161 GEN
50/50
3.109
962601AG1-109 GEN
50/50
3.109
962771AG1-126 GEN
Solar/Wind Harmer
74.627
970153AG2-106 GEN
Solar/Wind Harmer
47.655
971347AH1-153 GEN
Solar/Wind Harmer
4.014
270043AE2-236 GEN
Solar/Wind Harmer
5.048
270505AE1-170 C O1
Solar/Wind Harmer
7.914
270063AE2-323 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.088
944531AF1-118 GEN
Solar/Wind Harmer
33.371
274724RIVER EC ;11
Adder
18.817
274752CRETE EC ;2U
Adder
8.738
274753CRETE EC ;3U
Adder
8.738
965021AG1-366 GEN
Solar/Wind Harmer
2.462
970707AG2-453 GEN
Solar/Wind Harmer
24.09
274814UNIV PK N;0U
Adder
5.338
274807UNIV PK N;3U
Adder
5.326
274811UNIV PK N;7U
Adder
5.291
972259AH1-714 GEN
Adder
20.093
274826FISK ;BP
Adder
11.527
274803UNIV PARK;6U
Adder
6.138
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.237
276806AD2-047 C O1
Solar/Wind Harmer
4.16
972038AH1-567 GEN2
Adder
0.384
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
30.942
274729ELWOOD EC;1P
Adder
17.157
274730ELWOOD EC;6P
Adder
17.157
274734ELWOOD EC;8P
Adder
17.157
274736ELWOOD EC;9P
Adder
17.157
943121AE2-341 GEN
Solar/Wind Harmer
12.163
943591AF1-030 GEN
Solar/Wind Harmer
8.088
274682WAUKEGAN ;7U
Adder
18.463
274862TOP CROP ;2U
Solar/Wind Harmer
0.968
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.416
274879MINONK ;1U
Solar/Wind Harmer
0.295
946671AF1-331 GEN
Solar/Wind Harmer
0.753
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
959091AF2-200 GEN
Solar/Wind Harmer
14.045
970571AG2-364 GEN
Solar/Wind Harmer
13.895
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.215
274767LEE CO EC;8U
Adder
9.107
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
24690905MDL-1G C
Solar/Wind Harmer
0
24721905FLATG4
Adder
19.661
970781AG2-491 GEN
Solar/Wind Harmer
6.766
965931AG1-462 GEN
Solar/Wind Harmer
17.022
971087AG2-675 GEN
Solar/Wind Harmer
3.56
965091AG1-374 GEN
Solar/Wind Harmer
19.952
959611AF2-252 GEN
Solar/Wind Harmer
2.217
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
971993AH1-541 GEN
Solar/Wind Harmer
2.938
24695305TIMB G C
Solar/Wind Harmer
0.537
970289AG2-191 GEN
Solar/Wind Harmer
0.691
957381AF2-032 GEN
Solar/Wind Harmer
1.388
942481AE2-261 GEN
Solar/Wind Harmer
18.271
246938BC-WTG3
Solar/Wind Harmer
0.218
270491AE1-102 GEN2
Solar/Wind Harmer
0.786
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
NYPJM->LTFIMP_NY
CLTF
2.583
LGEELTFEXP_LGEE->PJM
CLTF
3.675
WECLTFEXP_WEC->PJM
CLTF
3.823
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.267
CPLELTFEXP_CPLE->PJM
CLTF
1.444
MECLTFEXP_MEC->PJM
CLTF
14.733
SIGELTFEXP_SIGE->PJM
CLTF
0.34
AG2-052LTFEXP_AG2-052->PJM
LTF
0.237
AH1-155LTFEXP_AH1-155->PJM
LTF
0.356
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.349
LAGNLTFEXP_LAGN->PJM
CLTF
11.281
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.712
TVALTFEXP_TVA->PJM
CLTF
5.082

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.76 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4887.22
MW Contribution:
18.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
15.609
270143AC1-141 CT2_
50/50
4.509
24639705ELKHART HY
50/50
0.301
970521AG2-332 GEN
50/50
21.375
24307105BERRINSP G
50/50
0.039
274773LINCOLN ;4U
50/50
16.29
274774LINCOLN ;5U
50/50
16.29
957891AF2-083 GEN
Solar/Wind Harmer
21.547
945111AF1-176 GEN
Solar/Wind Harmer
22.973
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
6.687
274723RIVER EC ;12
Adder
32.136
274751CRETE EC ;1U
Adder
14.744
274754CRETE EC ;4U
Adder
14.744
274812UNIV PK N;8U
Adder
8.912
274802UNIV PARK;5U
Adder
10.322
970373AG2-245 GEN
Solar/Wind Harmer
25.838
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.799
274674JOLIET 9 ;6U
Adder
26.949
274732ELWOOD EC;7P
Adder
28.742
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
9.698
270055AF2-134 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.939
274682WAUKEGAN ;7U
Adder
30.726
274861TOP CROP ;1U
Solar/Wind Harmer
0
274828WAUKEGAN ;BP
Adder
18.858
962781AG1-127 GEN
Solar/Wind Harmer
11.253
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
8.816
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
15.316
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.367
971997AH1-543 GEN
Solar/Wind Harmer
6.138
965011AG1-365 GEN
Solar/Wind Harmer
11.662
957471AF2-041 GEN
Solar/Wind Harmer
34.756
959081AF2-199 GEN
Solar/Wind Harmer
11.585
971067AG2-660 GEN
Solar/Wind Harmer
3.862
274822ROCKFORD ;11
Adder
32.468
970819AG2-516 GEN
Solar/Wind Harmer
13.763
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
14.32
970569AG2-363 GEN
Solar/Wind Harmer
34.22
965651AG1-433 GEN
Solar/Wind Harmer
3.342
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
15.096
274766LEE CO EC;7U
Adder
14.918
276708O09 GEN2
Solar/Wind Harmer
0.394
270102X2-052 ST
50/50
3
270100X2-052 CT1
50/50
2.772
270101X2-052 CT2
50/50
2.772
24643105BUCHANAN
50/50
0.023
247620Y3-023
50/50
0.894
274770LINCOLN ;1U
50/50
16.29
274771LINCOLN ;2U
50/50
16.29
970349AG2-230 GEN
Solar/Wind Harmer
20.983
965681AG1-436 GEN
Solar/Wind Harmer
16.258
965791AG1-447 GEN
Solar/Wind Harmer
11.923
961051AF2-396 GEN
Solar/Wind Harmer
25.67
961051AF2-396 GEN
Solar/Wind Harmer
17.113
274805UNIV PK N;1U
Adder
8.931
274808UNIV PK N;4U
Adder
8.873
274888KELLY CRK;1U
Solar/Wind Harmer
0.72
276776AD2-060 GEN
Solar/Wind Harmer
1.316
958011AF2-095 GEN
Solar/Wind Harmer
17.77
970941AG2-585 GEN
Solar/Wind Harmer
6.787
276897AD1-100 C
Solar/Wind Harmer
30.687
274674JOLIET 9 ;6U
Adder
26.949
276893AG1-478 C
Solar/Wind Harmer
0.813
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274695ROCKY RD ;2P
Adder
19.071
274693ROCKY RD ;1P
Adder
18.884
274697ROCKY RD ;3P
Adder
5.181
274696ROCKY RD ;4P
Adder
19.521
958481AF2-142 GEN
Solar/Wind Harmer
17.9
274683WAUKEGAN ;8U
Adder
35.976
274683WAUKEGAN ;8U
Adder
30.326
962691AG1-118 GEN
Solar/Wind Harmer
35.572
958491AF2-143 GEN
Solar/Wind Harmer
17.663
276901AD2-066 C O1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
23.171
971343AH1-151 GEN
Solar/Wind Harmer
23.171
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
4.159
972236AH1-702 GEN2
Adder
3.616
944541AF1-119 GEN
Solar/Wind Harmer
0.761
960971AF2-388 GEN
Solar/Wind Harmer
6.685
938861AE1-114 GEN
Solar/Wind Harmer
6.442
274764LEE CO EC;5U
Adder
15.132
274765LEE CO EC;6U
Adder
15.132
274762LEE CO EC;3U
Adder
15.096
274763LEE CO EC;4U
Adder
14.954
276158O29GEN2
Solar/Wind Harmer
0
270142AC1-141 CT1_
50/50
4.509
24642205MAYFLWER
50/50
0.068
276157O29GEN1
Solar/Wind Harmer
1.801
276645AC1-214 GEN1
Solar/Wind Harmer
0.437
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
3.547
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
942221AE2-234 GEN
Solar/Wind Harmer
4.299
960611AF2-352 GEN
Solar/Wind Harmer
3.565
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.183
944231AF1-091 GEN
Solar/Wind Harmer
23.934
970291AG2-192 GEN
Solar/Wind Harmer
1.289
970291AG2-192 GEN
Solar/Wind Harmer
0.595
270031AE2-169
Solar/Wind Harmer
5.447
270599AE1-208 GEN
Solar/Wind Harmer
9.078
276615X2-022 GEN
Solar/Wind Harmer
0.102
276838X2-022 GEN2
Solar/Wind Harmer
0.552
970241AG2-163 GEN
Solar/Wind Harmer
5.716
971613AH1-306 GEN
Solar/Wind Harmer
4.661
276916AD2-100_GEN
Solar/Wind Harmer
19.57
276911AD2-131_GEN
Solar/Wind Harmer
1.289
270246TR4_N_V150
Solar/Wind Harmer
0.059
270247TR4_N_V136
Solar/Wind Harmer
0.059
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.673
270201AC2-176 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
9.289
247621Y3-024
Adder
0.295
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.411
970883AG2-550 GEN
Solar/Wind Harmer
7.657
970885AG2-551 GEN
Solar/Wind Harmer
2.552
971587AH1-292 GEN
Solar/Wind Harmer
5.454
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.29
270349AD2-093_GEN
Solar/Wind Helper
1.569
270471AD2-092_GEN
Solar/Wind Helper
1.569
944961AF1-161 GEN
50/50
5.338
962601AG1-109 GEN
50/50
5.338
274772LINCOLN ;3U
50/50
16.29
971347AH1-153 GEN
Solar/Wind Harmer
6.994
270043AE2-236 GEN
Solar/Wind Harmer
8.579
270505AE1-170 C O1
Solar/Wind Harmer
13.603
945111AF1-176 GEN
Solar/Wind Harmer
10.436
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
56.263
274724RIVER EC ;11
Adder
31.767
274752CRETE EC ;2U
Adder
14.744
274753CRETE EC ;3U
Adder
14.744
274814UNIV PK N;0U
Adder
8.99
274807UNIV PK N;3U
Adder
8.97
274811UNIV PK N;7U
Adder
8.912
970707AG2-453 GEN
Solar/Wind Harmer
40.554
972259AH1-714 GEN
Adder
33.781
274803UNIV PARK;6U
Adder
10.322
274826FISK ;BP
Adder
19.382
274887GEN-1.85
Solar/Wind Harmer
0.321
276843GEN-1.7
Solar/Wind Harmer
0.399
276806AD2-047 C O1
Solar/Wind Harmer
6.993
972038AH1-567 GEN2
Adder
0.645
939351AE1-166 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
51.877
274729ELWOOD EC;1P
Adder
28.741
274730ELWOOD EC;6P
Adder
28.742
274734ELWOOD EC;8P
Adder
28.742
274736ELWOOD EC;9P
Adder
28.742
943121AE2-341 GEN
Solar/Wind Harmer
20.341
943591AF1-030 GEN
Solar/Wind Harmer
13.527
274682WAUKEGAN ;7U
Adder
30.726
274862TOP CROP ;2U
Solar/Wind Harmer
1.61
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
2.344
274879MINONK ;1U
Solar/Wind Harmer
0.489
946671AF1-331 GEN
Solar/Wind Harmer
1.245
274855GSG-6 ;RU
Solar/Wind Harmer
0.426
274850MENDOTA H;RU
Solar/Wind Harmer
0.136
965021AG1-366 GEN
Solar/Wind Harmer
3.887
959091AF2-200 GEN
Solar/Wind Harmer
23.171
970571AG2-364 GEN
Solar/Wind Harmer
22.813
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
15.096
274767LEE CO EC;8U
Adder
14.918
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.369
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
10.899
965931AG1-462 GEN
Solar/Wind Harmer
27.452
971087AG2-675 GEN
Solar/Wind Harmer
5.742
965091AG1-374 GEN
Solar/Wind Harmer
32.089
959611AF2-252 GEN
Solar/Wind Harmer
3.565
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.004
971993AH1-541 GEN
Solar/Wind Harmer
4.623
970289AG2-191 GEN
Solar/Wind Harmer
1.091
957381AF2-032 GEN
Solar/Wind Harmer
2.142
942481AE2-261 GEN
Solar/Wind Harmer
28.148
270004AE1-209 GEN
Solar/Wind Harmer
2.023
970825AG2-519 GEN
Solar/Wind Harmer
6.871
946031AF1-268 GEN
Solar/Wind Harmer
8.578
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.45
24695305TIMB G C
Solar/Wind Harmer
0.754
970193AG2-126 GEN
Solar/Wind Harmer
13.114
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728705AND G3
Adder
8.888
24728505AND G1
Adder
4.25
246938BC-WTG3
Solar/Wind Harmer
0.259
270491AE1-102 GEN2
Solar/Wind Harmer
0.936
24344005CKG1
50/50
12.151
270144AC1-141 ST1_
50/50
3.981
24641605TWIN BRNCH
50/50
0.032
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
16.29
274776LINCOLN ;7U
50/50
16.29
274777LINCOLN ;8U
50/50
16.29
971771AH1-392 GEN
Solar/Wind Harmer
13.087
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
24.893
970031AG2-029 GEN
Solar/Wind Harmer
6.756
972037AH1-567 GEN1
Adder
0.324
274827FISK ;RP
Adder
13.736
960591AF2-350 GEN
Solar/Wind Harmer
12.34
274800UNIV PARK;3U
Adder
10.31
274801UNIV PARK;4U
Adder
10.31
972228AH1-698 GEN2
Adder
6.548
972227AH1-698 GEN1
Adder
4.611
274687WILL CNTY;4U
Adder
49.058
274687WILL CNTY;4U
Adder
49.058
24729505KEY G4
Adder
11.387
274675JOLIET 29;7U
Adder
53.8
274675JOLIET 29;7U
Adder
51.878
274728ELWOOD EC;5P
Adder
28.742
274731ELWOOD EC;2P
Adder
28.741
274733ELWOOD EC;3P
Adder
28.741
274735ELWOOD EC;4P
Adder
28.741
970833AG2-524 GEN
Solar/Wind Harmer
13.404
970833AG2-524 GEN
Solar/Wind Harmer
8.936
274744AC1-111 GEN8
Adder
9.698
274746AC1-111 G10
Adder
9.698
970073AG2-061 GEN
Solar/Wind Harmer
3.925
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
4.551
971411AH1-196 GEN
Solar/Wind Harmer
17.505
276861AD2-134 GEN
Solar/Wind Harmer
0.208
276863AD2-134 GEN
Solar/Wind Harmer
0.208
959331AF2-224 GEN
Solar/Wind Harmer
8.163
971549AH1-272 GEN
Solar/Wind Harmer
24.049
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
23.171
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
32.233
971611AH1-305 GEN
Solar/Wind Harmer
6.82
274856ECOGROVE ;U1
Solar/Wind Harmer
0.267
926823AC1-168 GEN
Solar/Wind Harmer
1.939
970169AG2-114 GEN
Solar/Wind Harmer
11.381
971681AH1-341 GEN
Solar/Wind Harmer
18.311
972267AH1-718 GEN
Adder
6.682
276741O09 GEN1
Solar/Wind Harmer
0.394
274877BISHOP HL;1U
Solar/Wind Harmer
0.369
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
11.46
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.067
274854TWINGROVE;U2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
14.314
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
4.381
965041AG1-368 GEN
Solar/Wind Harmer
10.029
276668AB2-070 GEN1
Solar/Wind Harmer
0.393
276848AB2-070 GEN3
Solar/Wind Harmer
0.392
276849AB2-070 GEN2
Solar/Wind Harmer
0.393
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.884
971609AH1-304 GEN
Solar/Wind Harmer
1.618
247521TR3_G114
Solar/Wind Harmer
0.333
965051AG1-369 GEN
Solar/Wind Harmer
4.586
944221AF1-090 GEN
Solar/Wind Harmer
5.276
964611AG1-324 GEN
Solar/Wind Harmer
3.501
247536S-71 GEN
Solar/Wind Harmer
0.329
270543AE2-219 C
Solar/Wind Harmer
5.36
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.912
270356AE2-297 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.541
276646AC1-214 GEN2
Solar/Wind Harmer
0.437
958861AF2-177 GEN
Solar/Wind Harmer
4.817
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
15.28
945371AF1-202 GEN
Solar/Wind Harmer
0
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276621W2-048 GEN
Solar/Wind Harmer
0.491
963741AG1-226 GEN
Solar/Wind Harmer
23.192
270594AE1-207 GEN
Solar/Wind Harmer
10.875
270032AE2-172
Solar/Wind Harmer
6.473
270024AE2-089 GEN
Solar/Wind Harmer
0.002
965911AG1-460 GEN
Solar/Wind Harmer
1.883
276903AD2-071 C
Solar/Wind Harmer
10.45
270005AE1-210 C O1
Solar/Wind Harmer
2.023
970825AG2-519 GEN
Solar/Wind Harmer
3.238
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.152
24728605AND G2
Adder
4.25
965421AG1-410 GEN
Solar/Wind Harmer
22.891
246936BC-WTG1
Solar/Wind Harmer
0.29
270489AE1-102 GEN1
Solar/Wind Harmer
0.936
970773AG2-487 GEN
Solar/Wind Harmer
1.245
970091AG2-072 GEN
Adder
68.038
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.285
NYPJM->LTFIMP_NY
CLTF
2.94
LGEELTFEXP_LGEE->PJM
CLTF
4.042
WECLTFEXP_WEC->PJM
CLTF
6.289
CBM West 1LTFEXP_CBM-W1->PJM
CBM
191.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.325
MECLTFEXP_MEC->PJM
CLTF
22.729
SIGELTFEXP_SIGE->PJM
CLTF
0.435
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.78
AG2-052LTFEXP_AG2-052->PJM
LTF
0.393
AH1-155LTFEXP_AH1-155->PJM
LTF
0.59
CBM West 2LTFEXP_CBM-W2->PJM
CBM
110.466
LAGNLTFEXP_LAGN->PJM
CLTF
12.231
TVALTFEXP_TVA->PJM
CLTF
4.659

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.4 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6428.58
MW Contribution:
14.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
12.477
24721705FLATG2
50/50
40.954
24723005RIVRG1
Adder
35.892
24723105RIVRG2
Adder
35.892
970913AG2-568 GEN
Solar/Wind Harmer
8.731
971225AH1-072 GEN
Solar/Wind Harmer
2.121
971227AH1-073 GEN
Solar/Wind Harmer
2.121
24728205BUCHG1
Adder
6.8
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971073AG2-665 GEN
Solar/Wind Harmer
7.453
970879AG2-548 GEN
Solar/Wind Harmer
1.694
252509AD1-136 GEN
Solar/Wind Harmer
0.05
972043AH1-570 GEN
Solar/Wind Harmer
2.601
972045AH1-571 GEN
Solar/Wind Harmer
2.084
25183208HLCRTG
Solar/Wind Harmer
0.001
971125AH1-004 GEN
Solar/Wind Harmer
3.97
970107AG2-081 GEN
Solar/Wind Harmer
2.978
25194408D.CRK1
Adder
10.747
25194508D.CRK3
Adder
2.009
942891AE2-308 GEN
Solar/Wind Harmer
9.908
971587AH1-292 GEN
Solar/Wind Harmer
7.164
964571AG1-320 GEN
Solar/Wind Harmer
8.813
270269AC2-059
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
5.185
24728905RICHG2
Adder
5.185
945391AF1-204 GEN
Solar/Wind Harmer
10.085
926881AC1-175 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
270383AD1-128 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
5.492
970291AG2-192 GEN
Solar/Wind Harmer
1.223
970291AG2-192 GEN
Solar/Wind Harmer
0.565
971613AH1-306 GEN
Solar/Wind Harmer
4.515
25322209TAIT E
Adder
13.112
25322209TAIT E
Adder
12.817
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.061
970883AG2-550 GEN
Solar/Wind Harmer
9.352
970885AG2-551 GEN
Solar/Wind Harmer
3.117
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971485AH1-239 GEN
Solar/Wind Harmer
7.452
964781AG1-341 GEN
Solar/Wind Harmer
9.873
966021AG1-471 GEN
Solar/Wind Harmer
5.029
270031AE2-169
Solar/Wind Harmer
5.121
270599AE1-208 GEN
Solar/Wind Harmer
8.535
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
25326109MON D
Adder
1.753
964611AG1-324 GEN
Solar/Wind Harmer
0.697
247621Y3-024
Adder
0.321
270201AC2-176 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
19.462
276911AD2-131_GEN
Solar/Wind Harmer
1.282
944541AF1-119 GEN
Solar/Wind Harmer
0.618
960971AF2-388 GEN
Solar/Wind Harmer
5.431
276615X2-022 GEN
Solar/Wind Harmer
0.096
276838X2-022 GEN2
Solar/Wind Harmer
0.521
960611AF2-352 GEN
Solar/Wind Harmer
3.067
942111AE2-223 GEN
Solar/Wind Harmer
2.987
276645AC1-214 GEN1
Solar/Wind Harmer
0.358
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
22.743
274770LINCOLN ;1U
Adder
11.001
274771LINCOLN ;2U
Adder
11.001
958491AF2-143 GEN
Solar/Wind Harmer
13.642
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.467
958481AF2-142 GEN
Solar/Wind Harmer
13.633
962691AG1-118 GEN
Solar/Wind Harmer
27.261
971341AH1-150 GEN
Solar/Wind Harmer
18.173
971343AH1-151 GEN
Solar/Wind Harmer
18.173
938861AE1-114 GEN
Solar/Wind Harmer
5.149
274696ROCKY RD ;4P
Adder
14.841
274695ROCKY RD ;2P
Adder
14.499
274693ROCKY RD ;1P
Adder
14.356
274764LEE CO EC;5U
Adder
12.144
274765LEE CO EC;6U
Adder
12.144
274762LEE CO EC;3U
Adder
12.115
274763LEE CO EC;4U
Adder
12.001
274697ROCKY RD ;3P
Adder
3.939
972235AH1-702 GEN1
Adder
3.282
972236AH1-702 GEN2
Adder
2.854
276893AG1-478 C
Solar/Wind Harmer
0.606
274674JOLIET 9 ;6U
Adder
20.046
942221AE2-234 GEN
Solar/Wind Harmer
3.648
274683WAUKEGAN ;8U
Adder
27.432
971277AH1-098 GEN
Solar/Wind Harmer
3.633
274888KELLY CRK;1U
Solar/Wind Harmer
0.529
276776AD2-060 GEN
Solar/Wind Harmer
0.968
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
23585401KL_K28_T16
Solar/Wind Helper
1.54
237043AE2-125 C
Solar/Wind Helper
0.209
23751201ROTHROCK
Solar/Wind Helper
0.884
235054AD2-180 GEN
Solar/Wind Helper
2.046
238117U2-030
Solar/Wind Helper
0.345
235531U2-073 GEN
Solar/Wind Helper
3.281
962101AG1-054 GEN
Solar/Wind Helper
0.72
254304AE2-114 C
Solar/Wind Helper
0.241
254305AE2-115 C
Solar/Wind Helper
0.241
20083426SW_E13_K22
Solar/Wind Helper
0.064
241967AE2-285_GEN
Solar/Wind Helper
0.7
241801AE1-079 GEN
Solar/Wind Helper
0.274
946071AF1-272 GEN
Solar/Wind Helper
3.071
20088826HIGHLAND
Solar/Wind Helper
1.019
203961AE2-224 GEN
Solar/Wind Helper
2.731
203818AF1-086 GEN
Solar/Wind Helper
1.901
203853AF1-134 C O1
Solar/Wind Helper
0.537
946381AF1-302 GEN
Solar/Wind Helper
0.248
203946AE2-131 C
Solar/Wind Helper
0.533
203954AE2-126 C
Solar/Wind Helper
0.526
940863AE2-074 GEN
Solar/Wind Helper
0.508
203804AE2-113_GEN
Solar/Wind Helper
1.942
946751AF1-339 GEN
Solar/Wind Helper
0.504
961431AF2-434 GEN
Solar/Wind Helper
0.502
316097T157 G90
Solar/Wind Helper
1.163
203835AF1-098 GEN
Solar/Wind Helper
1.976
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
207471AF2-354 C
Solar/Wind Helper
0.185
20674328GAR_V4-001
Solar/Wind Helper
0.025
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20675428EAM_W2-061
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.029
20742028HF_AC1-207
Solar/Wind Helper
0.152
20714828MDF_W3-079
Solar/Wind Helper
0.14
207459AE1-142 C O1
Solar/Wind Helper
0.312
20720828JCB_W4-025
Solar/Wind Helper
0.068
214067T20SOLAR
Solar/Wind Helper
0.012
219607WPEMNERT C
Solar/Wind Helper
0.085
219304NAMERICA C
Solar/Wind Helper
0.14
219906AC1-017 C
Solar/Wind Helper
0.045
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.159
219904AC1-010 C
Solar/Wind Helper
0.064
228754AB1-001 C
Solar/Wind Helper
0.028
230433AD2-135 GEN
Solar/Wind Helper
0.018
230511AF1-262
Solar/Wind Helper
0.016
233952AC2-187 GEN
Solar/Wind Helper
0.242
233954AC2-188 GEN
Solar/Wind Helper
0.242
232410W1-006 C
Solar/Wind Helper
0.528
234015AF2-250 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.592
233994AC2-023 GEN
Solar/Wind Helper
1.001
232428Y3-058 C
Solar/Wind Helper
0.352
234036AF2-325 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.121
232436AB1-176 C
Solar/Wind Helper
0.046
233982AB2-133 GEN
Solar/Wind Helper
0.374
233930AB2-032 GEN
Solar/Wind Helper
0.396
235062AE1-101 C1
Solar/Wind Helper
1.478
237080AD1-060 GEN
Solar/Wind Helper
0.299
235020AA1-095 C
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.238
237006AB1-125 GEN
Solar/Wind Helper
0.11
223401AF1-299 GEN
Solar/Wind Helper
0.341
223402AF1-300 C
Solar/Wind Helper
0.341
24289405MTG1
50/50
11.336
243186AF1-051 GEN
50/50
12.477
24318705GVG2
50/50
11.565
24721805FLATG3
50/50
2.758
972203AH1-686 GEN
Adder
4.409
24723205RIVRG3
Adder
35.892
24686505CER G6
Adder
15.551
944971AF1-162 GEN
Solar/Wind Harmer
12.126
960001AF2-291 GEN
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
16.719
962761AG1-125 GEN
Solar/Wind Harmer
46.005
970149AG2-104 GEN
Solar/Wind Harmer
24.844
970155AG2-107 GEN
Solar/Wind Harmer
29.378
971687AH1-348 GEN
Solar/Wind Harmer
1.062
24728305BUCHG2
Adder
6.8
970091AG2-072 GEN
Adder
113.084
971073AG2-665 GEN
Solar/Wind Harmer
1.694
945681AF1-233 GEN
Solar/Wind Harmer
19.107
25196808ZIMRHP
Adder
108.598
252516AE2-318_GEN
Solar/Wind Harmer
11.165
252510AF1-249 C
Solar/Wind Harmer
0.075
25196008MFTGT1
Adder
1.98
25194608D.CRK4
Adder
2.336
3429241JKCT 3G
Adder
16.815
3429421JKCT 10G
Adder
11.809
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.854
24735205WLF2G2
Adder
8.041
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
4.631
970773AG2-487 GEN
Solar/Wind Harmer
1.693
270273AD2-016 GEN
Solar/Wind Harmer
0.98
24728605AND G2
Adder
5.248
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.957
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
276903AD2-071 C
Solar/Wind Harmer
10.535
963741AG1-226 GEN
Solar/Wind Harmer
22.28
964901AG1-354 GEN
Solar/Wind Harmer
14.121
270594AE1-207 GEN
Solar/Wind Harmer
10.536
270032AE2-172
Solar/Wind Harmer
6.271
270005AE1-210 C O1
Solar/Wind Harmer
2.038
970825AG2-519 GEN
Solar/Wind Harmer
3.334
25326309TAIT D
Adder
1.473
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
4.02
965911AG1-460 GEN
Solar/Wind Harmer
1.852
965651AG1-433 GEN
Solar/Wind Harmer
2.715
276621W2-048 GEN
Solar/Wind Harmer
0.463
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.546
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
12.866
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.925
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.831
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.358
270055AF2-134 C O1
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
27.326
971997AH1-543 GEN
Solar/Wind Harmer
4.779
253333AC1-068 GEN
Solar/Wind Harmer
0.01
276882AE2-255 GEN
Solar/Wind Harmer
1.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.001
274774LINCOLN ;5U
Adder
11.001
276805AD2-038 GEN
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.321
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.477
274861TOP CROP ;1U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.28
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
27.26
959081AF2-199 GEN
Solar/Wind Harmer
9.087
962781AG1-127 GEN
Solar/Wind Harmer
8.648
971067AG2-660 GEN
Solar/Wind Harmer
3.029
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.115
274766LEE CO EC;7U
Adder
11.973
274732ELWOOD EC;7P
Adder
21.404
274822ROCKFORD ;11
Adder
25.553
274674JOLIET 9 ;6U
Adder
20.046
970819AG2-516 GEN
Solar/Wind Harmer
10.9
238185AF2-356 C
Solar/Wind Helper
2.64
20089026BF_G21_K23
Solar/Wind Helper
0.545
238120AE2-309 GEN
Solar/Wind Helper
0.514
238126S14_GEN_1
Solar/Wind Helper
0.816
254303AC2-168 GEN
Solar/Wind Helper
0.175
241966AE1-183 GEN
Solar/Wind Helper
0.282
23751101LEADS_P59
Solar/Wind Helper
2.242
20084626FORWARD
Solar/Wind Helper
0.405
964201AG1-281 GEN
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.659
238109AE1-109 GEN2
Solar/Wind Helper
0.103
20090526Q36
Solar/Wind Helper
1.157
203952AE2-129 C
Solar/Wind Helper
0.533
203855AF2-088 C
Solar/Wind Helper
0.172
209071AE2-133 GEN
Solar/Wind Helper
0.092
946691AF1-333 GEN
Solar/Wind Helper
0.504
946741AF1-338 GEN
Solar/Wind Helper
0.504
961421AF2-433 GEN
Solar/Wind Helper
0.502
957921AF2-086 GEN
Solar/Wind Helper
0.497
961331AF2-424 GEN
Solar/Wind Helper
0.502
208972BECR K09
Solar/Wind Helper
0.375
963161AG1-165 GEN
Solar/Wind Helper
0.5
316095T157 G97
Solar/Wind Helper
1.163
203830AF1-094 GEN
Solar/Wind Helper
0.499
203979AG1-198 GEN
Solar/Wind Helper
0.3
23583801GRNGAP
Solar/Wind Helper
4.315
211065PSPA IPP
Solar/Wind Helper
0.169
209116AE2-175 GEN
Solar/Wind Helper
1.985
961971AG1-040 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.004
207437AD2-070 GEN
Solar/Wind Helper
0.152
207511W3-106 GEN
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.089
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
207442AE1-156 GEN
Solar/Wind Helper
0.354
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
217213AMBOY SO C
Solar/Wind Helper
0.031
205941AD2-115 GEN
Solar/Wind Helper
0.536
20716928W4-060COL
Solar/Wind Helper
0.056
219612MATRIX C
Solar/Wind Helper
0.026
207454AA2-184 E
Solar/Wind Helper
0.335
219918AC2-009 C
Solar/Wind Helper
0.001
20714928UPF_X1-085
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.103
959561AF2-247 GEN
Solar/Wind Helper
0.022
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219291REEVESSOUT C
Solar/Wind Helper
0.012
219914AD2-027 C
Solar/Wind Helper
0.122
203947AF1-006 C
Solar/Wind Helper
0.532
219921AF1-264
Solar/Wind Helper
0.054
219623KINSLEYBEA C
Solar/Wind Helper
0.002
230415AB2-049 C
Solar/Wind Helper
0.032
233923SMA
Solar/Wind Helper
0.783
233997TMININ_4.2
Solar/Wind Helper
0.214
232406W1-004 FULL
Solar/Wind Helper
0.528
233950AC2-186 GEN
Solar/Wind Helper
0.121
232434Z2-077 GEN
Solar/Wind Helper
0.132
233964AF2-378 GEN
Solar/Wind Helper
0.043
237085AD2-009_GEN
Solar/Wind Helper
1.463
232417X3-008 C
Solar/Wind Helper
0.242
233987AB2-037 GEN
Solar/Wind Helper
2.439
232422X3-066 FULL
Solar/Wind Helper
0.119
233933AB2-153 GEN
Solar/Wind Helper
0.242
233935AB2-179 C
Solar/Wind Helper
1.32
235067AD1-061 GEN
Solar/Wind Helper
0.394
237038AE2-054 C
Solar/Wind Helper
0.24
237002AB1-128_GEN
Solar/Wind Helper
0.392
208835TUHI V3-051
Solar/Wind Helper
0.022
23777801MSM_W1-116
Solar/Wind Helper
0.101
970373AG2-245 GEN
Solar/Wind Harmer
16.807
24289405MTG1
50/50
11.336
24318705GVG2
50/50
11.565
24722005FLATG5
50/50
2.758
24721905FLATG4
50/50
50.371
24686405CER G5
Adder
15.429
962771AG1-126 GEN
Solar/Wind Harmer
46.005
970153AG2-106 GEN
Solar/Wind Harmer
29.378
971191AH1-055 GEN
Solar/Wind Harmer
29.882
972103AH1-617 GEN
Solar/Wind Harmer
21.74
960911AF2-382 GEN
Solar/Wind Harmer
7.999
971461AH1-227 GEN
Solar/Wind Harmer
5.44
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
970879AG2-548 GEN
Solar/Wind Harmer
7.453
972167AH1-666 GEN
Solar/Wind Harmer
8.106
252507AC2-088 GEN
Solar/Wind Harmer
0.453
958171AF2-111 GEN
Solar/Wind Harmer
25.009
252519AF1-045_GEN
Solar/Wind Harmer
5.2
25196008MFTGT1
Adder
1.918
25194608D.CRK4
Adder
2.336
25196608WSDLE5
Adder
12.162
3429391JKCT 9G
Adder
11.809
970093AG2-073 GEN
Solar/Wind Harmer
8.38
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
12.81
253394AE2-221_GEN
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.77
970653AG2-424 GEN
Solar/Wind Harmer
0.96
972273AH1-721 GEN
Adder
114.179
24728705AND G3
Adder
10.976
24728505AND G1
Adder
5.248
970193AG2-126 GEN
Solar/Wind Harmer
14.237
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.718
253371AE2-315 SEC2
Adder
2.57
270346AE1-212 GEN
Solar/Wind Harmer
8.358
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.035
270004AE1-209 GEN
Solar/Wind Harmer
2.038
970191AG2-125 GEN
Solar/Wind Harmer
2.419
970825AG2-519 GEN
Solar/Wind Harmer
7.074
946031AF1-268 GEN
Solar/Wind Harmer
8.922
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
9.325
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.91
942481AE2-261 GEN
Solar/Wind Harmer
27.692
957381AF2-032 GEN
Solar/Wind Harmer
2.099
971993AH1-541 GEN
Solar/Wind Harmer
4.271
943031AE2-326 GEN
Solar/Wind Harmer
4.803
965091AG1-374 GEN
Solar/Wind Harmer
27.602
959611AF2-252 GEN
Solar/Wind Harmer
3.067
944531AF1-118 GEN
Solar/Wind Harmer
41.107
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.304
970571AG2-364 GEN
Solar/Wind Harmer
18.217
253325AC1-069 GEN
Solar/Wind Harmer
0.01
276868AE1-113 GEN
Solar/Wind Harmer
1.82
274879MINONK ;1U
Solar/Wind Harmer
0.38
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.001
970707AG2-453 GEN
Solar/Wind Harmer
29.702
943121AE2-341 GEN
Solar/Wind Harmer
15.239
943591AF1-030 GEN
Solar/Wind Harmer
10.134
274862TOP CROP ;2U
Solar/Wind Harmer
1.227
972259AH1-714 GEN
Adder
24.853
274855GSG-6 ;RU
Solar/Wind Harmer
0.332
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
946671AF1-331 GEN
Solar/Wind Harmer
0.969
959091AF2-200 GEN
Solar/Wind Harmer
18.173
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
12.115
274767LEE CO EC;8U
Adder
11.973
965931AG1-462 GEN
Solar/Wind Harmer
23.167
274729ELWOOD EC;1P
Adder
21.404
274730ELWOOD EC;6P
Adder
21.404
274734ELWOOD EC;8P
Adder
21.404
274736ELWOOD EC;9P
Adder
21.404
971087AG2-675 GEN
Solar/Wind Harmer
4.845
274682WAUKEGAN ;7U
Adder
7.239
274887GEN-1.85
Solar/Wind Harmer
0.236
276843GEN-1.7
Solar/Wind Harmer
0.294
276806AD2-047 C O1
Solar/Wind Harmer
5.144
237048AF1-022 C
Solar/Wind Helper
0.231
237046AF1-021 C
Solar/Wind Helper
0.4
235058AG1-386 C
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
1.078
964991AG1-363 GEN
Solar/Wind Helper
4.441
202652Y1-033 WT C
Solar/Wind Helper
0.66
238127S14_GEN_2
Solar/Wind Helper
0.816
20092526R32
Solar/Wind Helper
1.32
238108AE1-109 GEN1
Solar/Wind Helper
0.103
238110AE1-109 GEN3
Solar/Wind Helper
0.103
20303426NA_O38_P22
Solar/Wind Helper
1.125
203993AD2-133_GEN1
Solar/Wind Helper
1.157
203854AF2-039 C
Solar/Wind Helper
0.357
20398826ARMNA MT
Solar/Wind Helper
1.668
941421AE2-139 GEN
Solar/Wind Helper
2.591
209137AF2-361 C
Solar/Wind Helper
1.545
946731AF1-337 GEN
Solar/Wind Helper
0.504
212507AE2-042_GEN
Solar/Wind Helper
1.784
961341AF2-425 GEN
Solar/Wind Helper
0.502
961301AF2-421 GEN
Solar/Wind Helper
0.5
963151AG1-164 GEN
Solar/Wind Helper
0.5
211065PSPA IPP
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.73
20675728RH_W2-091
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.033
203975AE1-071-GEN
Solar/Wind Helper
2.698
207484AF2-139 C O1
Solar/Wind Helper
0.093
20674928WA_W3-044
Solar/Wind Helper
0.108
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676328BVR_Y1-020
Solar/Wind Helper
0.03
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676728BRNX1-095
Solar/Wind Helper
0.032
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20671828STAW2-080
Solar/Wind Helper
0.029
20673628F1S_V4-069
Solar/Wind Helper
0.032
962511AG1-100 GEN
Solar/Wind Helper
0.492
219908AB1-139 C
Solar/Wind Helper
0.08
219919AE1-041 FULL
Solar/Wind Helper
0.004
218428ETC SOLAR C
Solar/Wind Helper
0.005
218524CNTRALGAS1 C
Solar/Wind Helper
0.174
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20715228NPK_W1-113
Solar/Wind Helper
0.084
20720528MAN_W1-024
Solar/Wind Helper
0.031
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.069
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.103
20716028EGP_W2-019
Solar/Wind Helper
0.02
219348LDSOLAR C
Solar/Wind Helper
0.122
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
219766PARADISE C
Solar/Wind Helper
0.058
228729W2-030 C
Solar/Wind Helper
0.117
233996TM1833_GEN
Solar/Wind Helper
0.214
233998TM1NIN_3.36
Solar/Wind Helper
0.214
232404W1-003 C
Solar/Wind Helper
0.528
232408W1-005 C
Solar/Wind Helper
0.528
232426Y1-080 FULL
Solar/Wind Helper
0.04
205932AD2-116_GEN
Solar/Wind Helper
0.528
233944AB2-135 GEN
Solar/Wind Helper
0.614
233918AB1-142 GEN
Solar/Wind Helper
0.523
235063AE1-101 C2
Solar/Wind Helper
1.478
205916AD1-020 GEN
Solar/Wind Helper
1.727
237001AB1-127_GEN
Solar/Wind Helper
0.391
23777901MDS_W4-102
Solar/Wind Helper
0.152
208835TUHI V3-051
Solar/Wind Helper
0.022
238175AF1-290_GEN
Solar/Wind Helper
0.127
24721605FLATG1
50/50
2.758
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
27.062
270399AC1-101 GEN
Solar/Wind Harmer
3.79
270400AC1-102 GEN
Solar/Wind Harmer
3.79
970281AG2-184 GEN
Solar/Wind Harmer
22.827
971985AH1-537 GEN
Solar/Wind Harmer
3.231
941621AE2-160 GEN
Adder
5.034
971313AH1-133 GEN
Solar/Wind Harmer
5.062
972163AH1-664 GEN
Solar/Wind Harmer
11.291
972165AH1-665 GEN
Solar/Wind Harmer
9.043
339216AC1-074 GEN
Solar/Wind Harmer
0.266
25196108MFTGT2
Adder
2.183
25196108MFTGT2
Adder
2.027
3429211JKCT 2G
Adder
16.597
25196408WSDLE3
Adder
12.519
25196308WSDLE2
Adder
12.41
25196208WSDLE1
Adder
12.379
25196708WSDLE6
Adder
12.348
25196508WSDLE4
Adder
12.037
24734705WLF1G3
Adder
8.159
24734805WLF1G4
Adder
8.159
24734905WLF1G5
Adder
8.159
270340AC2-060 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.728
270263AC1-001 GEN
Solar/Wind Harmer
0.978
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270291AC1-194 GEN
Solar/Wind Harmer
0
24735105WLF2G1
Adder
8.041
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971061AG2-657 GEN
Solar/Wind Harmer
6.001
253372AE2-315 SEC3
Adder
2.57
253372AE2-315 SEC3
Adder
2.57
25306009OHH W.
Adder
3.905
970289AG2-191 GEN
Solar/Wind Harmer
1.788
963841AG1-237 GEN
Solar/Wind Harmer
4.07
971029AG2-637 GEN
Solar/Wind Harmer
14.087
24386405FR-21G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.546
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.372
971609AH1-304 GEN
Solar/Wind Harmer
1.521
964611AG1-324 GEN
Solar/Wind Harmer
3.625
270432AC2-029 GEN
Solar/Wind Harmer
4.119
944221AF1-090 GEN
Solar/Wind Harmer
5.449
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.362
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
971611AH1-305 GEN
Solar/Wind Harmer
5.499
959141AF2-205 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0
24729505KEY G4
Adder
8.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.649
966391AG1-508 GEN
Solar/Wind Harmer
1.42
970169AG2-114 GEN
Solar/Wind Harmer
9.156
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Harmer
0.996
274877BISHOP HL;1U
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
1.55
274775LINCOLN ;6U
Adder
11.001
274776LINCOLN ;7U
Adder
11.001
274777LINCOLN ;8U
Adder
11.001
970073AG2-061 GEN
Solar/Wind Harmer
3.032
276741O09 GEN1
Solar/Wind Harmer
0.321
970833AG2-524 GEN
Solar/Wind Harmer
10.003
970833AG2-524 GEN
Solar/Wind Harmer
6.669
274744AC1-111 GEN8
Adder
7.28
274746AC1-111 G10
Adder
7.28
276861AD2-134 GEN
Solar/Wind Harmer
0.162
276863AD2-134 GEN
Solar/Wind Harmer
0.162
971675AH1-338 GEN
Solar/Wind Harmer
3.544
971171AH1-044 GEN
Solar/Wind Harmer
18.173
971681AH1-341 GEN
Solar/Wind Harmer
14.63
972267AH1-718 GEN
Adder
5.423
946321AF1-296 GEN
Solar/Wind Harmer
5.088
274728ELWOOD EC;5P
Adder
21.404
274731ELWOOD EC;2P
Adder
21.404
274733ELWOOD EC;3P
Adder
21.404
274735ELWOOD EC;4P
Adder
21.404
274856ECOGROVE ;U1
Solar/Wind Harmer
0.212
274823ROCKFORD ;21
Adder
25.367
971411AH1-196 GEN
Solar/Wind Harmer
13.626
972228AH1-698 GEN2
Adder
4.822
972227AH1-698 GEN1
Adder
3.396
960591AF2-350 GEN
Solar/Wind Harmer
9.078
23750501ELLIOTTS
Solar/Wind Helper
0.793
23652301WDPWR_K20
Solar/Wind Helper
0.169
23750701CROSSCHOOL
Solar/Wind Helper
1.437
238118U2-030_1
Solar/Wind Helper
0.345
203955AF1-039 C O1
Solar/Wind Helper
0.435
20089126CSLMN_L13
Solar/Wind Helper
0.688
20089226LOOKOUT
Solar/Wind Helper
0.686
241997AF1-093 GEN
Solar/Wind Helper
0.282
241985AE1-237 GEN
Solar/Wind Helper
0.274
241982AE2-343 S C
Solar/Wind Helper
0.246
20088926STNY CRK
Solar/Wind Helper
0.934
203940AF1-140 C
Solar/Wind Helper
0.45
20094526CT_V3-030
Solar/Wind Helper
0.534
20088626ARWF_N39
Solar/Wind Helper
1.372
203846AF2-130 C
Solar/Wind Helper
0.501
20334926Z1-069 C
Solar/Wind Helper
1.501
200917MEHOOPANY_G
Solar/Wind Helper
2.447
209067AE2-060 GEN
Solar/Wind Helper
0.092
959431AF2-234 GEN
Solar/Wind Helper
1.007
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.504
209054AE2-059 GEN
Solar/Wind Helper
0.091
209027LOR2_Q27
Solar/Wind Helper
1.174
212266LOR1
Solar/Wind Helper
0.342
209029WAYMART-WD
Solar/Wind Helper
0.944
961261AF2-417 GEN
Solar/Wind Helper
0.499
20675128HRM_W1-127
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.093
964851AG1-348 GEN
Solar/Wind Helper
0.069
20676428JCR_X2-075
Solar/Wind Helper
0.074
20676128MHD_W3-029
Solar/Wind Helper
0.104
20673828FLE_V3-070
Solar/Wind Helper
0.094
218526CNTRALGAS2 C
Solar/Wind Helper
0.174
20675528CPH_W2-050
Solar/Wind Helper
0.123
20720628TIN_W1-124
Solar/Wind Helper
0.205
219620RIDERU C
Solar/Wind Helper
0.001
207445AB1-138_GEN
Solar/Wind Helper
0.112
20715028HAN_X4-015
Solar/Wind Helper
0.061
20720728JCB_W1-129
Solar/Wind Helper
0.061
959381AF2-229 GEN
Solar/Wind Helper
0.367
20390526W1-045 C
Solar/Wind Helper
0.36
219615MILLCREEK C
Solar/Wind Helper
0.028
219258KINSLEYDEP C
Solar/Wind Helper
0.081
227927V4-067C
Solar/Wind Helper
0.011
230407AD2-065 C
Solar/Wind Helper
0.043
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.244
233901CHERRYDALE C
Solar/Wind Helper
0.242
233940AF2-379 C
Solar/Wind Helper
0.065
232432Z2-076 GEN
Solar/Wind Helper
0.07
205956AE1-196_GEN
Solar/Wind Helper
0.528
205943AE1-185 GEN
Solar/Wind Helper
0.528
233915AB1-141 GEN
Solar/Wind Helper
0.523
205917AD1-020 ES
Solar/Wind Helper
0.371
237025AB1-124 C
Solar/Wind Helper
0.147
237030AB1-096 C
Solar/Wind Helper
0.06
23779801AA1-109
Solar/Wind Helper
0.169
238169AE2-226 GEN1
Solar/Wind Helper
0.559
238170AE2-226 GEN2
Solar/Wind Helper
0.559
NYPJM->LTFIMP_NY
CLTF
6.32
LGEELTFEXP_LGEE->PJM
CLTF
9.798
WECLTFEXP_WEC->PJM
CLTF
4.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.306
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.33
CPLELTFEXP_CPLE->PJM
CLTF
6.482
MECLTFEXP_MEC->PJM
CLTF
21.831
SIGELTFEXP_SIGE->PJM
CLTF
0.725
AG2-052LTFEXP_AG2-052->PJM
LTF
0.304
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 2LTFEXP_CBM-W2->PJM
CBM
172.282
LAGNLTFEXP_LAGN->PJM
CLTF
24.73
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.035
TVALTFEXP_TVA->PJM
CLTF
12.563

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4976.63
MW Contribution:
10.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
243186AF1-051 GEN
50/50
11.683
24721705FLATG2
50/50
36.759
24723005RIVRG1
Adder
32.69
24723105RIVRG2
Adder
32.69
970913AG2-568 GEN
Solar/Wind Harmer
8.105
24728205BUCHG1
Adder
6.196
971225AH1-072 GEN
Solar/Wind Harmer
1.885
971227AH1-073 GEN
Solar/Wind Harmer
1.885
971277AH1-098 GEN
Solar/Wind Harmer
3.388
971073AG2-665 GEN
Solar/Wind Harmer
5.846
970879AG2-548 GEN
Solar/Wind Harmer
1.329
270583AD2-179 GEN
Solar/Wind Harmer
7.872
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942891AE2-308 GEN
Solar/Wind Harmer
7.677
972043AH1-570 GEN
Solar/Wind Harmer
1.99
972045AH1-571 GEN
Solar/Wind Harmer
1.594
971125AH1-004 GEN
Solar/Wind Harmer
3.042
970107AG2-081 GEN
Solar/Wind Harmer
2.281
966021AG1-471 GEN
Solar/Wind Harmer
4.034
252509AD1-136 GEN
Solar/Wind Harmer
0.037
971485AH1-239 GEN
Solar/Wind Harmer
5.968
964571AG1-320 GEN
Solar/Wind Harmer
6.787
964781AG1-341 GEN
Solar/Wind Harmer
7.81
25183208HLCRTG
Solar/Wind Harmer
0
971587AH1-292 GEN
Solar/Wind Harmer
5.311
25194408D.CRK1
Adder
7.827
25194508D.CRK3
Adder
1.463
945391AF1-204 GEN
Solar/Wind Harmer
7.253
24728805RICHG1
Adder
3.656
24728905RICHG2
Adder
3.656
970241AG2-163 GEN
Solar/Wind Harmer
3.886
276916AD2-100_GEN
Solar/Wind Harmer
13.944
276911AD2-131_GEN
Solar/Wind Harmer
0.919
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.068
276838X2-022 GEN2
Solar/Wind Harmer
0.37
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.743
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.844
970291AG2-192 GEN
Solar/Wind Harmer
0.389
971613AH1-306 GEN
Solar/Wind Harmer
3.113
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
970883AG2-550 GEN
Solar/Wind Harmer
6.406
970885AG2-551 GEN
Solar/Wind Harmer
2.135
942111AE2-223 GEN
Solar/Wind Harmer
2.08
270031AE2-169
Solar/Wind Harmer
3.483
270599AE1-208 GEN
Solar/Wind Harmer
5.804
276645AC1-214 GEN1
Solar/Wind Harmer
0.248
964611AG1-324 GEN
Solar/Wind Harmer
0.475
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.019
247621Y3-024
Adder
0.218
270201AC2-176 GEN
Solar/Wind Harmer
0
25322209TAIT E
Adder
8.794
25322209TAIT E
Adder
8.596
274764LEE CO EC;5U
Adder
8.405
274765LEE CO EC;6U
Adder
8.405
274762LEE CO EC;3U
Adder
8.386
274763LEE CO EC;4U
Adder
8.307
938861AE1-114 GEN
Solar/Wind Harmer
3.56
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.263
972236AH1-702 GEN2
Adder
1.968
971341AH1-150 GEN
Solar/Wind Harmer
12.516
971343AH1-151 GEN
Solar/Wind Harmer
12.516
276901AD2-066 C O1
Solar/Wind Harmer
0
24289405MTG1
50/50
10.896
243186AF1-051 GEN
50/50
11.683
24318705GVG2
50/50
10.829
24721805FLATG3
50/50
2.475
24723205RIVRG3
Adder
32.69
972203AH1-686 GEN
Adder
3.965
24686505CER G6
Adder
14.074
944971AF1-162 GEN
Solar/Wind Harmer
10.992
971403AH1-188 GEN
Solar/Wind Harmer
15.251
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
6.196
971687AH1-348 GEN
Solar/Wind Harmer
0.943
24735205WLF2G2
Adder
7.131
971073AG2-665 GEN
Solar/Wind Harmer
1.329
970091AG2-072 GEN
Adder
86.562
945681AF1-233 GEN
Solar/Wind Harmer
14.491
3429241JKCT 3G
Adder
13.004
3429421JKCT 10G
Adder
9.095
970653AG2-424 GEN
Solar/Wind Harmer
3.596
964901AG1-354 GEN
Solar/Wind Harmer
11.126
25196808ZIMRHP
Adder
79.991
25196008MFTGT1
Adder
1.457
252516AE2-318_GEN
Solar/Wind Harmer
8.161
252510AF1-249 C
Solar/Wind Harmer
0.055
25194608D.CRK4
Adder
1.702
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.045
962761AG1-125 GEN
Solar/Wind Harmer
27.311
970149AG2-104 GEN
Solar/Wind Harmer
14.748
970155AG2-107 GEN
Solar/Wind Harmer
17.44
253398AE2-221_GEN2
Solar/Wind Harmer
0
24728605AND G2
Adder
3.745
970773AG2-487 GEN
Solar/Wind Harmer
1.199
963741AG1-226 GEN
Solar/Wind Harmer
15.765
965911AG1-460 GEN
Solar/Wind Harmer
1.325
943811AF1-049 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.832
276621W2-048 GEN
Solar/Wind Harmer
0.329
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.31
270594AE1-207 GEN
Solar/Wind Harmer
7.264
270032AE2-172
Solar/Wind Harmer
4.324
270273AD2-016 GEN
Solar/Wind Harmer
0.662
270005AE1-210 C O1
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
2.292
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
8.961
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.933
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.248
276708O09 GEN2
Solar/Wind Harmer
0.223
970569AG2-363 GEN
Solar/Wind Harmer
18.869
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
8.386
274766LEE CO EC;7U
Adder
8.287
25326309TAIT D
Adder
0.988
945371AF1-202 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
7.523
939401AE1-172 GEN
Solar/Wind Harmer
4.684
274822ROCKFORD ;11
Adder
17.613
957471AF2-041 GEN
Solar/Wind Harmer
18.774
959081AF2-199 GEN
Solar/Wind Harmer
6.258
971067AG2-660 GEN
Solar/Wind Harmer
2.086
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.135
971997AH1-543 GEN
Solar/Wind Harmer
3.283
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.729
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
5.929
274828WAUKEGAN ;BP
Adder
9.84
274682WAUKEGAN ;7U
Adder
16.004
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.692
276691AA1-018 GEN1
Solar/Wind Harmer
1.009
274745AC1-111 GEN9
Adder
4.965
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
14.558
274674JOLIET 9 ;6U
Adder
13.632
24721605FLATG1
50/50
2.475
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
24.531
270399AC1-101 GEN
Solar/Wind Harmer
3.431
270400AC1-102 GEN
Solar/Wind Harmer
3.431
941621AE2-160 GEN
Adder
4.685
970281AG2-184 GEN
Solar/Wind Harmer
20.069
971313AH1-133 GEN
Solar/Wind Harmer
4.633
971061AG2-657 GEN
Solar/Wind Harmer
5.63
24734705WLF1G3
Adder
7.275
24734805WLF1G4
Adder
7.275
24734905WLF1G5
Adder
7.275
971985AH1-537 GEN
Solar/Wind Harmer
2.606
24735105WLF2G1
Adder
7.131
966391AG1-508 GEN
Solar/Wind Harmer
1.323
971331AH1-145 GEN
Solar/Wind Harmer
10.902
971329AH1-144 GEN
Solar/Wind Harmer
4.007
971981AH1-535 GEN
Solar/Wind Harmer
5.247
972163AH1-664 GEN
Solar/Wind Harmer
8.578
972165AH1-665 GEN
Solar/Wind Harmer
6.87
3429211JKCT 2G
Adder
12.836
339216AC1-074 GEN
Solar/Wind Harmer
0.202
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.606
25196108MFTGT2
Adder
1.492
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
9.098
25196308WSDLE2
Adder
9.019
25196208WSDLE1
Adder
8.997
25196708WSDLE6
Adder
8.974
25196508WSDLE4
Adder
8.748
253406AD2-031_GEN
Solar/Wind Harmer
0.516
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.692
270069AE2-166 C O1
Solar/Wind Harmer
6.22
270356AE2-297 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.926
963841AG1-237 GEN
Solar/Wind Harmer
2.866
24386405FR-21G C
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.257
276848AB2-070 GEN3
Solar/Wind Harmer
0.256
276849AB2-070 GEN2
Solar/Wind Harmer
0.257
970289AG2-191 GEN
Solar/Wind Harmer
1.233
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.69
274854TWINGROVE;U2
Solar/Wind Harmer
0
25306009OHH W.
Adder
2.654
253372AE2-315 SEC3
Adder
1.743
253372AE2-315 SEC3
Adder
1.743
270543AE2-219 C
Solar/Wind Harmer
4.484
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.721
247536S-71 GEN
Solar/Wind Harmer
0.254
971611AH1-305 GEN
Solar/Wind Harmer
3.778
946321AF1-296 GEN
Solar/Wind Harmer
3.554
274877BISHOP HL;1U
Solar/Wind Harmer
0.211
971609AH1-304 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
2.468
970169AG2-114 GEN
Solar/Wind Harmer
6.325
276741O09 GEN1
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.763
926823AC1-168 GEN
Solar/Wind Harmer
1.07
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.116
274856ECOGROVE ;U1
Solar/Wind Harmer
0.147
274823ROCKFORD ;21
Adder
17.485
971171AH1-044 GEN
Solar/Wind Harmer
12.516
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
971675AH1-338 GEN
Solar/Wind Harmer
2.437
971411AH1-196 GEN
Solar/Wind Harmer
9.369
970073AG2-061 GEN
Solar/Wind Harmer
2.078
274744AC1-111 GEN8
Adder
4.965
274746AC1-111 G10
Adder
4.965
970833AG2-524 GEN
Solar/Wind Harmer
6.809
970833AG2-524 GEN
Solar/Wind Harmer
4.54
274728ELWOOD EC;5P
Adder
14.558
274731ELWOOD EC;2P
Adder
14.558
274733ELWOOD EC;3P
Adder
14.558
274735ELWOOD EC;4P
Adder
14.558
958491AF2-143 GEN
Solar/Wind Harmer
9.353
962691AG1-118 GEN
Solar/Wind Harmer
18.68
274683WAUKEGAN ;8U
Adder
18.772
274683WAUKEGAN ;8U
Adder
15.824
274696ROCKY RD ;4P
Adder
10.15
274695ROCKY RD ;2P
Adder
9.916
274693ROCKY RD ;1P
Adder
9.818
274697ROCKY RD ;3P
Adder
2.694
958481AF2-142 GEN
Solar/Wind Harmer
9.318
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
15.453
276893AG1-478 C
Solar/Wind Harmer
0.412
274674JOLIET 9 ;6U
Adder
13.632
944541AF1-119 GEN
Solar/Wind Harmer
0.412
960971AF2-388 GEN
Solar/Wind Harmer
3.621
274888KELLY CRK;1U
Solar/Wind Harmer
0.359
276776AD2-060 GEN
Solar/Wind Harmer
0.657
958011AF2-095 GEN
Solar/Wind Harmer
8.864
970941AG2-585 GEN
Solar/Wind Harmer
3.385
23585401KL_K28_T16
Solar/Wind Helper
1.157
237043AE2-125 C
Solar/Wind Helper
0.157
23751201ROTHROCK
Solar/Wind Helper
0.666
235054AD2-180 GEN
Solar/Wind Helper
1.531
965651AG1-433 GEN
Solar/Wind Harmer
1.811
274676JOLIET 29;8U
Adder
9.572
238185AF2-356 C
Solar/Wind Helper
1.975
970373AG2-245 GEN
Solar/Wind Harmer
5.443
274675JOLIET 29;7U
Adder
27.142
960591AF2-350 GEN
Solar/Wind Harmer
6.155
23750501ELLIOTTS
Solar/Wind Helper
0.598
23652301WDPWR_K20
Solar/Wind Helper
0.127
24289405MTG1
50/50
10.896
24318705GVG2
50/50
10.829
24722005FLATG5
50/50
2.475
24721905FLATG4
50/50
45.211
24686405CER G5
Adder
13.963
971191AH1-055 GEN
Solar/Wind Harmer
25.524
960911AF2-382 GEN
Solar/Wind Harmer
7.256
972103AH1-617 GEN
Solar/Wind Harmer
19.113
971461AH1-227 GEN
Solar/Wind Harmer
4.836
270346AE1-212 GEN
Solar/Wind Harmer
7.826
943031AE2-326 GEN
Solar/Wind Harmer
4.478
970879AG2-548 GEN
Solar/Wind Harmer
5.846
958121AF2-106 GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
6.527
972167AH1-666 GEN
Solar/Wind Harmer
6.143
972273AH1-721 GEN
Adder
91.222
3429391JKCT 9G
Adder
9.095
970455AG2-298 GEN
Solar/Wind Harmer
2.913
958171AF2-111 GEN
Solar/Wind Harmer
18.695
252507AC2-088 GEN
Solar/Wind Harmer
0.336
970653AG2-424 GEN
Solar/Wind Harmer
0.745
25196008MFTGT1
Adder
1.411
252519AF1-045_GEN
Solar/Wind Harmer
3.801
25194608D.CRK4
Adder
1.702
25196608WSDLE5
Adder
8.838
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.158
962771AG1-126 GEN
Solar/Wind Harmer
27.311
970153AG2-106 GEN
Solar/Wind Harmer
17.44
253394AE2-221_GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
10.239
24728705AND G3
Adder
7.833
24728505AND G1
Adder
3.745
270030AE2-140 GEN
Solar/Wind Harmer
13.518
942481AE2-261 GEN
Solar/Wind Harmer
19.808
957381AF2-032 GEN
Solar/Wind Harmer
1.5
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.022
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.714
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
6.48
270004AE1-209 GEN
Solar/Wind Harmer
1.4
970825AG2-519 GEN
Solar/Wind Harmer
4.865
965091AG1-374 GEN
Solar/Wind Harmer
19.301
946031AF1-268 GEN
Solar/Wind Harmer
6.123
959611AF2-252 GEN
Solar/Wind Harmer
2.145
253370AE2-315 SEC1
Adder
1.843
253371AE2-315 SEC2
Adder
1.743
970191AG2-125 GEN
Solar/Wind Harmer
1.638
965931AG1-462 GEN
Solar/Wind Harmer
16.203
971087AG2-675 GEN
Solar/Wind Harmer
3.389
274878BISHOP HL;2U
Solar/Wind Harmer
0.211
276782AC1-033 GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.45
970571AG2-364 GEN
Solar/Wind Harmer
12.579
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
8.386
274767LEE CO EC;8U
Adder
8.287
959091AF2-200 GEN
Solar/Wind Harmer
12.516
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
946671AF1-331 GEN
Solar/Wind Harmer
0.666
276868AE1-113 GEN
Solar/Wind Harmer
1.25
274879MINONK ;1U
Solar/Wind Harmer
0.261
274682WAUKEGAN ;7U
Adder
16.004
274862TOP CROP ;2U
Solar/Wind Harmer
0.839
943121AE2-341 GEN
Solar/Wind Harmer
10.39
943591AF1-030 GEN
Solar/Wind Harmer
6.91
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
14.558
274730ELWOOD EC;6P
Adder
14.558
274734ELWOOD EC;8P
Adder
14.558
274736ELWOOD EC;9P
Adder
14.558
970707AG2-453 GEN
Solar/Wind Harmer
20.15
274887GEN-1.85
Solar/Wind Harmer
0.16
276843GEN-1.7
Solar/Wind Harmer
0.199
276806AD2-047 C O1
Solar/Wind Harmer
3.488
237048AF1-022 C
Solar/Wind Helper
0.175
237046AF1-021 C
Solar/Wind Helper
0.301
235058AG1-386 C
Solar/Wind Helper
0.387
23562501BACKB
Solar/Wind Helper
0.811
NYPJM->LTFIMP_NY
CLTF
4.626
LGEELTFEXP_LGEE->PJM
CLTF
7.468
WECLTFEXP_WEC->PJM
CLTF
3.435
CBM West 1LTFEXP_CBM-W1->PJM
CBM
115.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.783
CPLELTFEXP_CPLE->PJM
CLTF
6.32
MECLTFEXP_MEC->PJM
CLTF
15.666
SIGELTFEXP_SIGE->PJM
CLTF
0.545
AG2-052LTFEXP_AG2-052->PJM
LTF
0.207
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.098
LAGNLTFEXP_LAGN->PJM
CLTF
19.698
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23
TVALTFEXP_TVA->PJM
CLTF
10.208

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.76 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5896.19
MW Contribution:
12.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.717
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
270053AF1-130 C
Solar/Wind Harmer
28.948
270399AC1-101 GEN
Solar/Wind Harmer
4.065
270400AC1-102 GEN
Solar/Wind Harmer
4.065
971313AH1-133 GEN
Solar/Wind Harmer
5.869
941621AE2-160 GEN
Adder
5.641
966391AG1-508 GEN
Solar/Wind Harmer
1.796
970281AG2-184 GEN
Solar/Wind Harmer
24.292
971331AH1-145 GEN
Solar/Wind Harmer
15.307
971329AH1-144 GEN
Solar/Wind Harmer
5.625
24734705WLF1G3
Adder
9.154
24734805WLF1G4
Adder
9.154
24734905WLF1G5
Adder
9.154
24735105WLF2G1
Adder
8.97
971061AG2-657 GEN
Solar/Wind Harmer
6.84
971985AH1-537 GEN
Solar/Wind Harmer
3.035
971981AH1-535 GEN
Solar/Wind Harmer
6.584
270069AE2-166 C O1
Solar/Wind Harmer
8.709
3429211JKCT 2G
Adder
15.456
972163AH1-664 GEN
Solar/Wind Harmer
10.231
972165AH1-665 GEN
Solar/Wind Harmer
8.194
339216AC1-074 GEN
Solar/Wind Harmer
0.242
270291AC1-194 GEN
Solar/Wind Harmer
0
25196108MFTGT2
Adder
1.918
25196108MFTGT2
Adder
1.781
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
25196408WSDLE3
Adder
10.861
25196308WSDLE2
Adder
10.766
25196208WSDLE1
Adder
10.739
25196708WSDLE6
Adder
10.712
25196508WSDLE4
Adder
10.442
253406AD2-031_GEN
Solar/Wind Harmer
0.618
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.825
270197AD1-017 GEN1
Solar/Wind Harmer
1.008
270356AE2-297 GEN
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.756
963841AG1-237 GEN
Solar/Wind Harmer
3.459
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.312
276848AB2-070 GEN3
Solar/Wind Harmer
0.31
276849AB2-070 GEN2
Solar/Wind Harmer
0.312
24386405FR-21G C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.489
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
243186AF1-051 GEN
50/50
12.754
24721705FLATG2
50/50
40.355
24723005RIVRG1
Adder
37.533
24723105RIVRG2
Adder
37.533
970913AG2-568 GEN
Solar/Wind Harmer
9.827
24728205BUCHG1
Adder
7.739
971225AH1-072 GEN
Solar/Wind Harmer
2.315
971227AH1-073 GEN
Solar/Wind Harmer
2.315
971277AH1-098 GEN
Solar/Wind Harmer
4.618
270583AD2-179 GEN
Solar/Wind Harmer
11.364
971073AG2-665 GEN
Solar/Wind Harmer
6.854
970879AG2-548 GEN
Solar/Wind Harmer
1.558
942891AE2-308 GEN
Solar/Wind Harmer
9.244
972043AH1-570 GEN
Solar/Wind Harmer
2.384
972045AH1-571 GEN
Solar/Wind Harmer
1.91
971125AH1-004 GEN
Solar/Wind Harmer
3.655
970107AG2-081 GEN
Solar/Wind Harmer
2.741
966021AG1-471 GEN
Solar/Wind Harmer
4.933
971485AH1-239 GEN
Solar/Wind Harmer
7.296
962581AG1-107 GEN
Solar/Wind Harmer
0.002
964781AG1-341 GEN
Solar/Wind Harmer
9.518
964571AG1-320 GEN
Solar/Wind Harmer
8.194
252509AD1-136 GEN
Solar/Wind Harmer
0.044
25183208HLCRTG
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
6.363
25194408D.CRK1
Adder
9.34
25194508D.CRK3
Adder
1.746
945391AF1-204 GEN
Solar/Wind Harmer
8.741
942671AE2-283 GEN
Solar/Wind Harmer
3.812
24728805RICHG1
Adder
4.399
24728905RICHG2
Adder
4.399
276916AD2-100_GEN
Solar/Wind Harmer
16.897
276911AD2-131_GEN
Solar/Wind Harmer
1.113
970241AG2-163 GEN
Solar/Wind Harmer
4.689
276615X2-022 GEN
Solar/Wind Harmer
0.083
276838X2-022 GEN2
Solar/Wind Harmer
0.448
926881AC1-175 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.897
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
1.019
970291AG2-192 GEN
Solar/Wind Harmer
0.47
971613AH1-306 GEN
Solar/Wind Harmer
3.76
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.602
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
2.525
253370AE2-315 SEC1
Adder
2.225
970883AG2-550 GEN
Solar/Wind Harmer
7.744
970885AG2-551 GEN
Solar/Wind Harmer
2.581
276645AC1-214 GEN1
Solar/Wind Harmer
0.302
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.239
270031AE2-169
Solar/Wind Harmer
4.216
270599AE1-208 GEN
Solar/Wind Harmer
7.027
964611AG1-324 GEN
Solar/Wind Harmer
0.575
24289405MTG1
50/50
11.78
243186AF1-051 GEN
50/50
12.754
24318705GVG2
50/50
11.822
24721805FLATG3
50/50
2.717
24723205RIVRG3
Adder
37.533
972203AH1-686 GEN
Adder
4.531
24686505CER G6
Adder
16.156
944971AF1-162 GEN
Solar/Wind Harmer
12.972
971403AH1-188 GEN
Solar/Wind Harmer
18.148
960001AF2-291 GEN
Solar/Wind Harmer
0
24728305BUCHG2
Adder
7.739
971687AH1-348 GEN
Solar/Wind Harmer
1.157
24735205WLF2G2
Adder
8.97
971073AG2-665 GEN
Solar/Wind Harmer
1.558
970091AG2-072 GEN
Adder
102.646
3429241JKCT 3G
Adder
15.659
3429421JKCT 10G
Adder
10.948
945681AF1-233 GEN
Solar/Wind Harmer
17.283
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
964901AG1-354 GEN
Solar/Wind Harmer
13.534
970653AG2-424 GEN
Solar/Wind Harmer
4.351
25196808ZIMRHP
Adder
95.39
25196008MFTGT1
Adder
1.739
252516AE2-318_GEN
Solar/Wind Harmer
9.728
252510AF1-249 C
Solar/Wind Harmer
0.065
25194608D.CRK4
Adder
2.03
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.427
24728605AND G2
Adder
4.51
253398AE2-221_GEN2
Solar/Wind Harmer
0
962761AG1-125 GEN
Solar/Wind Harmer
32.057
970149AG2-104 GEN
Solar/Wind Harmer
17.311
970155AG2-107 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.031
970773AG2-487 GEN
Solar/Wind Harmer
1.442
963741AG1-226 GEN
Solar/Wind Harmer
19.023
965911AG1-460 GEN
Solar/Wind Harmer
1.606
276621W2-048 GEN
Solar/Wind Harmer
0.398
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.825
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.823
270594AE1-207 GEN
Solar/Wind Harmer
8.772
270032AE2-172
Solar/Wind Harmer
5.222
270005AE1-210 C O1
Solar/Wind Harmer
1.692
970825AG2-519 GEN
Solar/Wind Harmer
2.77
270273AD2-016 GEN
Solar/Wind Harmer
0.795
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
10.877
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.302
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.607
276708O09 GEN2
Solar/Wind Harmer
0.271
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
10.206
274766LEE CO EC;7U
Adder
10.085
970569AG2-363 GEN
Solar/Wind Harmer
22.948
970819AG2-516 GEN
Solar/Wind Harmer
9.157
274822ROCKFORD ;11
Adder
21.436
957471AF2-041 GEN
Solar/Wind Harmer
22.848
959081AF2-199 GEN
Solar/Wind Harmer
7.616
971067AG2-660 GEN
Solar/Wind Harmer
2.539
945371AF1-202 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.694
971997AH1-543 GEN
Solar/Wind Harmer
3.993
25326309TAIT D
Adder
1.195
276882AE2-255 GEN
Solar/Wind Harmer
0.887
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.865
274872LEEDK;1U
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
7.216
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
11.976
274682WAUKEGAN ;7U
Adder
19.478
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.228
274745AC1-111 GEN9
Adder
6.042
274871GR RIDGE ;2U
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.702
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.158
25306009OHH W.
Adder
3.203
253372AE2-315 SEC3
Adder
2.104
253372AE2-315 SEC3
Adder
2.104
270543AE2-219 C
Solar/Wind Harmer
5.421
946321AF1-296 GEN
Solar/Wind Harmer
4.325
274877BISHOP HL;1U
Solar/Wind Harmer
0.257
247536S-71 GEN
Solar/Wind Harmer
0.307
971611AH1-305 GEN
Solar/Wind Harmer
4.575
970169AG2-114 GEN
Solar/Wind Harmer
7.684
24289405MTG1
50/50
11.78
24318705GVG2
50/50
11.822
24722005FLATG5
50/50
2.717
24721905FLATG4
50/50
49.634
24686405CER G5
Adder
16.028
960911AF2-382 GEN
Solar/Wind Harmer
8.992
943031AE2-326 GEN
Solar/Wind Harmer
6.089
971461AH1-227 GEN
Solar/Wind Harmer
5.939
972103AH1-617 GEN
Solar/Wind Harmer
23.135
971191AH1-055 GEN
Solar/Wind Harmer
29.317
270346AE1-212 GEN
Solar/Wind Harmer
10.045
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
6.854
972273AH1-721 GEN
Adder
111.17
270030AE2-140 GEN
Solar/Wind Harmer
18.672
970093AG2-073 GEN
Solar/Wind Harmer
7.87
270186AC1-089 GEN
Solar/Wind Harmer
0
270367AC2-061_GEN
Solar/Wind Harmer
0
3429391JKCT 9G
Adder
10.948
972167AH1-666 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
8.058
970455AG2-298 GEN
Solar/Wind Harmer
3.516
970653AG2-424 GEN
Solar/Wind Harmer
0.902
958171AF2-111 GEN
Solar/Wind Harmer
22.344
252507AC2-088 GEN
Solar/Wind Harmer
0.399
25196008MFTGT1
Adder
1.685
252519AF1-045_GEN
Solar/Wind Harmer
4.531
25194608D.CRK4
Adder
2.03
25196608WSDLE5
Adder
10.55
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
10.955
970193AG2-126 GEN
Solar/Wind Harmer
12.34
24728705AND G3
Adder
9.433
24728505AND G1
Adder
4.51
253394AE2-221_GEN
Solar/Wind Harmer
0
962771AG1-126 GEN
Solar/Wind Harmer
32.057
970153AG2-106 GEN
Solar/Wind Harmer
20.471
3147312GRETNA
Solar/Wind Harmer
0.122
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.901
942481AE2-261 GEN
Solar/Wind Harmer
24.006
957381AF2-032 GEN
Solar/Wind Harmer
1.818
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
3.664
24386205FR-12G C
Solar/Wind Harmer
0
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.862
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.832
270004AE1-209 GEN
Solar/Wind Harmer
1.692
965091AG1-374 GEN
Solar/Wind Harmer
23.422
959611AF2-252 GEN
Solar/Wind Harmer
2.602
970825AG2-519 GEN
Solar/Wind Harmer
5.878
946031AF1-268 GEN
Solar/Wind Harmer
7.4
253370AE2-315 SEC1
Adder
2.225
253371AE2-315 SEC2
Adder
2.104
965931AG1-462 GEN
Solar/Wind Harmer
19.72
971087AG2-675 GEN
Solar/Wind Harmer
4.124
3147123OTTER R
Solar/Wind Harmer
0.087
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.257
970191AG2-125 GEN
Solar/Wind Harmer
1.979
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
10.206
274767LEE CO EC;8U
Adder
10.085
970571AG2-364 GEN
Solar/Wind Harmer
15.299
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
11.443
959091AF2-200 GEN
Solar/Wind Harmer
15.232
274855GSG-6 ;RU
Solar/Wind Harmer
0.277
274850MENDOTA H;RU
Solar/Wind Harmer
0.088
946671AF1-331 GEN
Solar/Wind Harmer
0.811
276868AE1-113 GEN
Solar/Wind Harmer
1.52
274879MINONK ;1U
Solar/Wind Harmer
0.317
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
19.478
274862TOP CROP ;2U
Solar/Wind Harmer
1.021
943121AE2-341 GEN
Solar/Wind Harmer
12.644
943591AF1-030 GEN
Solar/Wind Harmer
8.409
939351AE1-166 GEN
Solar/Wind Harmer
0
274729ELWOOD EC;1P
Adder
17.715
274730ELWOOD EC;6P
Adder
17.715
274734ELWOOD EC;8P
Adder
17.715
274736ELWOOD EC;9P
Adder
17.715
970707AG2-453 GEN
Solar/Wind Harmer
24.521
274887GEN-1.85
Solar/Wind Harmer
0.195
276843GEN-1.7
Solar/Wind Harmer
0.242
276806AD2-047 C O1
Solar/Wind Harmer
4.245
237048AF1-022 C
Solar/Wind Helper
0.185
237046AF1-021 C
Solar/Wind Helper
0.318
964991AG1-363 GEN
Solar/Wind Helper
3.731
238127S14_GEN_2
Solar/Wind Helper
0.692
23562501BACKB
Solar/Wind Helper
0.87
202652Y1-033 WT C
Solar/Wind Helper
0.538
238108AE1-109 GEN1
Solar/Wind Helper
0.089
238110AE1-109 GEN3
Solar/Wind Helper
0.089
20092526R32
Solar/Wind Helper
1.061
235058AG1-386 C
Solar/Wind Helper
0.381
276741O09 GEN1
Solar/Wind Harmer
0.271
972267AH1-718 GEN
Adder
4.579
971609AH1-304 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
2.987
926823AC1-168 GEN
Solar/Wind Harmer
1.302
959141AF2-205 GEN
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
12.311
274856ECOGROVE ;U1
Solar/Wind Harmer
0.178
274823ROCKFORD ;21
Adder
21.28
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.232
945581AF1-223 GEN
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.136
276863AD2-134 GEN
Solar/Wind Harmer
0.136
971675AH1-338 GEN
Solar/Wind Harmer
2.966
971411AH1-196 GEN
Solar/Wind Harmer
11.402
970073AG2-061 GEN
Solar/Wind Harmer
2.528
274744AC1-111 GEN8
Adder
6.042
274746AC1-111 G10
Adder
6.042
970833AG2-524 GEN
Solar/Wind Harmer
8.285
970833AG2-524 GEN
Solar/Wind Harmer
5.523
274728ELWOOD EC;5P
Adder
17.715
274731ELWOOD EC;2P
Adder
17.715
274733ELWOOD EC;3P
Adder
17.715
274735ELWOOD EC;4P
Adder
17.715
274675JOLIET 29;7U
Adder
33.032
960591AF2-350 GEN
Solar/Wind Harmer
7.491
23750501ELLIOTTS
Solar/Wind Helper
0.639
23750701CROSSCHOOL
Solar/Wind Helper
1.205
238118U2-030_1
Solar/Wind Helper
0.29
23652301WDPWR_K20
Solar/Wind Helper
0.134
203955AF1-039 C O1
Solar/Wind Helper
0.355
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089226LOOKOUT
Solar/Wind Helper
0.556
20088926STNY CRK
Solar/Wind Helper
0.752
203940AF1-140 C
Solar/Wind Helper
0.362
274764LEE CO EC;5U
Adder
10.23
274765LEE CO EC;6U
Adder
10.23
274762LEE CO EC;3U
Adder
10.206
274763LEE CO EC;4U
Adder
10.109
938861AE1-114 GEN
Solar/Wind Harmer
4.333
247621Y3-024
Adder
0.264
270201AC2-176 GEN
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
2.754
972236AH1-702 GEN2
Adder
2.395
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
15.232
971343AH1-151 GEN
Solar/Wind Harmer
15.232
25322209TAIT E
Adder
10.639
25322209TAIT E
Adder
10.4
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
11.378
962691AG1-118 GEN
Solar/Wind Harmer
22.733
274683WAUKEGAN ;8U
Adder
22.847
274683WAUKEGAN ;8U
Adder
19.259
274696ROCKY RD ;4P
Adder
12.353
274695ROCKY RD ;2P
Adder
12.068
274693ROCKY RD ;1P
Adder
11.949
274697ROCKY RD ;3P
Adder
3.278
958481AF2-142 GEN
Solar/Wind Harmer
11.337
276897AD1-100 C
Solar/Wind Harmer
18.8
276893AG1-478 C
Solar/Wind Harmer
0.501
274674JOLIET 9 ;6U
Adder
16.589
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.437
276776AD2-060 GEN
Solar/Wind Harmer
0.799
958011AF2-095 GEN
Solar/Wind Harmer
10.787
23585401KL_K28_T16
Solar/Wind Helper
1.275
235054AD2-180 GEN
Solar/Wind Helper
1.707
238117U2-030
Solar/Wind Helper
0.29
235531U2-073 GEN
Solar/Wind Helper
2.776
23751201ROTHROCK
Solar/Wind Helper
0.715
237043AE2-125 C
Solar/Wind Helper
0.165
316097T157 G90
Solar/Wind Helper
1.102
20083426SW_E13_K22
Solar/Wind Helper
0.052
20088826HIGHLAND
Solar/Wind Helper
0.818
946071AF1-272 GEN
Solar/Wind Helper
2.445
203961AE2-224 GEN
Solar/Wind Helper
2.204
970941AG2-585 GEN
Solar/Wind Harmer
2.017
274847GR RIDGE ;BU
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
3.264
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
17.715
274674JOLIET 9 ;6U
Adder
16.589
274676JOLIET 29;8U
Adder
11.649
270055AF2-134 C O1
Solar/Wind Harmer
0
238185AF2-356 C
Solar/Wind Helper
2.199
238120AE2-309 GEN
Solar/Wind Helper
0.436
238126S14_GEN_1
Solar/Wind Helper
0.692
23583801GRNGAP
Solar/Wind Helper
4.116
316095T157 G97
Solar/Wind Helper
1.102
238109AE1-109 GEN2
Solar/Wind Helper
0.089
20089026BF_G21_K23
Solar/Wind Helper
0.441
20084626FORWARD
Solar/Wind Helper
0.325
964201AG1-281 GEN
Solar/Wind Helper
0.442
NYPJM->LTFIMP_NY
CLTF
5.307
LGEELTFEXP_LGEE->PJM
CLTF
8.953
WECLTFEXP_WEC->PJM
CLTF
4.181
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.616
CPLELTFEXP_CPLE->PJM
CLTF
7.73
MECLTFEXP_MEC->PJM
CLTF
19.089
SIGELTFEXP_SIGE->PJM
CLTF
0.657
AG2-052LTFEXP_AG2-052->PJM
LTF
0.252
AH1-155LTFEXP_AH1-155->PJM
LTF
0.378
CBM West 2LTFEXP_CBM-W2->PJM
CBM
161.379
LAGNLTFEXP_LAGN->PJM
CLTF
24.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.864
TVALTFEXP_TVA->PJM
CLTF
12.601

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.25 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2283.58
MW Contribution:
7.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.374
24729305KEY G2
50/50
0.367
24729205KEY G1
50/50
0.366
247620Y3-023
50/50
0.467
960851AF2-376 GEN
50/50
2.095
24643105BUCHANAN
50/50
0.01
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.855
944231AF1-091 GEN
Solar/Wind Harmer
16.139
944541AF1-119 GEN
Solar/Wind Harmer
0.427
960971AF2-388 GEN
Solar/Wind Harmer
3.752
970349AG2-230 GEN
Solar/Wind Harmer
8.78
961051AF2-396 GEN
Solar/Wind Harmer
11.674
961051AF2-396 GEN
Solar/Wind Harmer
7.782
270031AE2-169
Solar/Wind Harmer
3.104
270599AE1-208 GEN
Solar/Wind Harmer
5.173
965681AG1-436 GEN
Solar/Wind Harmer
6.963
965791AG1-447 GEN
Solar/Wind Harmer
5.106
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.41
247621Y3-024
Adder
0.183
274805UNIV PK N;1U
Adder
3.801
274808UNIV PK N;4U
Adder
3.776
24727005RPMNG1
50/50
3.317
960861AF2-377 GEN
50/50
2.406
970521AG2-332 GEN
50/50
10.906
24639705ELKHART HY
50/50
0.151
270143AC1-141 CT2_
50/50
2.029
965011AG1-365 GEN
Solar/Wind Harmer
13.822
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.876
958861AF2-177 GEN
Solar/Wind Harmer
2.694
945111AF1-176 GEN
Solar/Wind Harmer
10.683
957891AF2-083 GEN
Solar/Wind Harmer
9.802
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3
970373AG2-245 GEN
Solar/Wind Harmer
11.243
274751CRETE EC ;1U
Adder
6.312
274754CRETE EC ;4U
Adder
6.312
274723RIVER EC ;12
Adder
13.681
274812UNIV PK N;8U
Adder
3.792
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.365
274774LINCOLN ;5U
Adder
6.365
274802UNIV PARK;5U
Adder
4.369
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.75
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.662
274674JOLIET 9 ;6U
Adder
11.348
274732ELWOOD EC;7P
Adder
12.11
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.364
270594AE1-207 GEN
Solar/Wind Harmer
5.699
270032AE2-172
Solar/Wind Harmer
3.392
270005AE1-210 C O1
Solar/Wind Harmer
1.101
274745AC1-111 GEN9
Adder
4.068
24727105RPMNG2
50/50
3.318
970583AG2-370 GEN
50/50
2.814
270142AC1-141 CT1_
50/50
2.029
24642205MAYFLWER
50/50
0.031
944961AF1-161 GEN
50/50
2.395
962601AG1-109 GEN
50/50
2.395
965021AG1-366 GEN
Solar/Wind Harmer
4.607
270043AE2-236 GEN
Solar/Wind Harmer
5.241
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.981
24695305TIMB G C
Solar/Wind Harmer
0.532
945111AF1-176 GEN
Solar/Wind Harmer
4.853
971347AH1-153 GEN
Solar/Wind Harmer
2.927
270505AE1-170 C O1
Solar/Wind Harmer
6.132
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.345
274752CRETE EC ;2U
Adder
6.312
274753CRETE EC ;3U
Adder
6.312
274724RIVER EC ;11
Adder
13.515
274814UNIV PK N;0U
Adder
3.826
274807UNIV PK N;3U
Adder
3.817
274811UNIV PK N;7U
Adder
3.792
274772LINCOLN ;3U
Adder
6.365
274803UNIV PARK;6U
Adder
4.369
274826FISK ;BP
Adder
8.195
972038AH1-567 GEN2
Adder
0.273
274887GEN-1.85
Solar/Wind Harmer
0.135
276843GEN-1.7
Solar/Wind Harmer
0.168
276806AD2-047 C O1
Solar/Wind Harmer
2.951
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.153
970707AG2-453 GEN
Solar/Wind Harmer
16.903
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.852
274729ELWOOD EC;1P
Adder
12.11
274730ELWOOD EC;6P
Adder
12.11
274734ELWOOD EC;8P
Adder
12.11
274736ELWOOD EC;9P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.564
946031AF1-268 GEN
Solar/Wind Harmer
4.838
24727205RPMNG3
50/50
3.298
24729505KEY G4
50/50
6.847
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.792
959331AF2-224 GEN
Solar/Wind Harmer
9.676
963791AG1-232 GEN
Solar/Wind Harmer
12.035
970031AG2-029 GEN
Solar/Wind Harmer
4.587
965041AG1-368 GEN
Solar/Wind Harmer
8.443
270071AF1-092 GEN
Solar/Wind Harmer
14.566
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.602
971771AH1-392 GEN
Solar/Wind Harmer
5.907
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.922
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.13
274775LINCOLN ;6U
Adder
6.365
274776LINCOLN ;7U
Adder
6.365
274777LINCOLN ;8U
Adder
6.365
972037AH1-567 GEN1
Adder
0.137
274827FISK ;RP
Adder
5.808
274800UNIV PARK;3U
Adder
4.357
274801UNIV PARK;4U
Adder
4.357
960591AF2-350 GEN
Solar/Wind Harmer
5.207
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.365
274771LINCOLN ;2U
Adder
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
0.304
276776AD2-060 GEN
Solar/Wind Harmer
0.555
958011AF2-095 GEN
Solar/Wind Harmer
7.498
970941AG2-585 GEN
Solar/Wind Harmer
2.864
276897AD1-100 C
Solar/Wind Harmer
12.887
274674JOLIET 9 ;6U
Adder
11.348
276893AG1-478 C
Solar/Wind Harmer
0.343
970291AG2-192 GEN
Solar/Wind Harmer
0.666
970291AG2-192 GEN
Solar/Wind Harmer
0.308
971613AH1-306 GEN
Solar/Wind Harmer
2.442
958481AF2-142 GEN
Solar/Wind Harmer
7.57
274695ROCKY RD ;2P
Adder
8.016
274693ROCKY RD ;1P
Adder
7.937
274697ROCKY RD ;3P
Adder
2.178
274696ROCKY RD ;4P
Adder
8.205
274683WAUKEGAN ;8U
Adder
15.145
274683WAUKEGAN ;8U
Adder
12.766
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
14.951
958491AF2-143 GEN
Solar/Wind Harmer
7.476
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.768
971343AH1-151 GEN
Solar/Wind Harmer
9.768
972235AH1-702 GEN1
Adder
1.755
972236AH1-702 GEN2
Adder
1.526
938861AE1-114 GEN
Solar/Wind Harmer
2.722
274764LEE CO EC;5U
Adder
6.396
274765LEE CO EC;6U
Adder
6.396
274762LEE CO EC;3U
Adder
6.381
274763LEE CO EC;4U
Adder
6.321
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.763
276645AC1-214 GEN1
Solar/Wind Harmer
0.185
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.533
942111AE2-223 GEN
Solar/Wind Harmer
1.513
960611AF2-352 GEN
Solar/Wind Harmer
1.525
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.481
970885AG2-551 GEN
Solar/Wind Harmer
1.494
970241AG2-163 GEN
Solar/Wind Harmer
2.581
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.044
276838X2-022 GEN2
Solar/Wind Harmer
0.239
276916AD2-100_GEN
Solar/Wind Harmer
8.532
276911AD2-131_GEN
Solar/Wind Harmer
0.562
945391AF1-204 GEN
Solar/Wind Harmer
4.219
970623AG2-406 GEN
Solar/Wind Harmer
0.656
971587AH1-292 GEN
Solar/Wind Harmer
2.468
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.897
270462AD2-086
Solar/Wind Helper
3.747
247522W1-056 GEN
Solar/Wind Helper
1.177
253378AE2-206_GEN
Solar/Wind Helper
0.715
270349AD2-093_GEN
Solar/Wind Helper
0.857
270471AD2-092_GEN
Solar/Wind Helper
0.857
241960AC2-195 GEN
Solar/Wind Helper
0.697
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.82
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.788
274682WAUKEGAN ;7U
Adder
12.933
274828WAUKEGAN ;BP
Adder
7.939
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.731
939401AE1-172 GEN
Solar/Wind Harmer
3.718
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.578
971997AH1-543 GEN
Solar/Wind Harmer
2.59
957471AF2-041 GEN
Solar/Wind Harmer
14.651
959081AF2-199 GEN
Solar/Wind Harmer
4.884
971067AG2-660 GEN
Solar/Wind Harmer
1.628
274822ROCKFORD ;11
Adder
13.696
276903AD2-071 C
Solar/Wind Harmer
5.426
970819AG2-516 GEN
Solar/Wind Harmer
5.809
970569AG2-363 GEN
Solar/Wind Harmer
14.512
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.381
274766LEE CO EC;7U
Adder
6.306
276708O09 GEN2
Solar/Wind Harmer
0.167
276646AC1-214 GEN2
Solar/Wind Harmer
0.185
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.519
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.287
963741AG1-226 GEN
Solar/Wind Harmer
10.473
276621W2-048 GEN
Solar/Wind Harmer
0.213
965911AG1-460 GEN
Solar/Wind Harmer
0.82
24728605AND G2
Adder
2.099
970773AG2-487 GEN
Solar/Wind Harmer
0.63
246936BC-WTG1
Solar/Wind Helper
10.897
270317AD1-130_GEN
Solar/Wind Helper
4.143
270485AE1-090_GEN
Solar/Wind Helper
0.326
270391AF1-285 GEN3
Solar/Wind Helper
0.593
270578AF1-285 GEN2
Solar/Wind Helper
0.593
270286AF1-227 GEN2
Solar/Wind Helper
0.694
960841AF2-375 GEN
Solar/Wind Helper
1.179
943121AE2-341 GEN
Solar/Wind Harmer
8.518
943591AF1-030 GEN
Solar/Wind Harmer
5.665
270004AE1-209 GEN
Solar/Wind Harmer
1.101
274862TOP CROP ;2U
Solar/Wind Harmer
0.681
970825AG2-519 GEN
Solar/Wind Harmer
3.795
274682WAUKEGAN ;7U
Adder
12.933
276868AE1-113 GEN
Solar/Wind Harmer
0.991
274879MINONK ;1U
Solar/Wind Harmer
0.207
946671AF1-331 GEN
Solar/Wind Harmer
0.524
274855GSG-6 ;RU
Solar/Wind Harmer
0.179
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.895
959091AF2-200 GEN
Solar/Wind Harmer
9.768
970571AG2-364 GEN
Solar/Wind Harmer
9.675
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.381
274767LEE CO EC;8U
Adder
6.306
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.157
965091AG1-374 GEN
Solar/Wind Harmer
13.726
965931AG1-462 GEN
Solar/Wind Harmer
11.666
971087AG2-675 GEN
Solar/Wind Harmer
2.44
959611AF2-252 GEN
Solar/Wind Harmer
1.525
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.998
957381AF2-032 GEN
Solar/Wind Harmer
0.932
942481AE2-261 GEN
Solar/Wind Harmer
12.255
970193AG2-126 GEN
Solar/Wind Harmer
5.956
24728705AND G3
Adder
4.39
24728505AND G1
Adder
2.099
246938BC-WTG3
Solar/Wind Helper
11.083
942871AE2-306 GEN
Solar/Wind Helper
0.445
270284AF1-227 GEN1
Solar/Wind Helper
1.893
270287AF1-227 GEN3
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.334
270541AE2-072 C
Solar/Wind Helper
0.943
972228AH1-698 GEN2
Adder
2.756
972227AH1-698 GEN1
Adder
1.941
274687WILL CNTY;4U
Adder
20.685
274687WILL CNTY;4U
Adder
20.685
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.662
274675JOLIET 29;7U
Adder
21.853
274728ELWOOD EC;5P
Adder
12.11
274731ELWOOD EC;2P
Adder
12.11
274733ELWOOD EC;3P
Adder
12.11
274735ELWOOD EC;4P
Adder
12.11
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.974
970833AG2-524 GEN
Solar/Wind Harmer
5.628
970833AG2-524 GEN
Solar/Wind Harmer
3.752
971611AH1-305 GEN
Solar/Wind Harmer
3.031
274744AC1-111 GEN8
Adder
4.068
274746AC1-111 G10
Adder
4.068
970073AG2-061 GEN
Solar/Wind Harmer
1.661
247536S-71 GEN
Solar/Wind Harmer
0.199
971411AH1-196 GEN
Solar/Wind Harmer
7.376
971675AH1-338 GEN
Solar/Wind Harmer
1.916
276861AD2-134 GEN
Solar/Wind Harmer
0.088
276863AD2-134 GEN
Solar/Wind Harmer
0.088
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.768
274823ROCKFORD ;21
Adder
13.596
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
926823AC1-168 GEN
Solar/Wind Harmer
0.821
970169AG2-114 GEN
Solar/Wind Harmer
4.823
971681AH1-341 GEN
Solar/Wind Harmer
7.736
971549AH1-272 GEN
Solar/Wind Harmer
9.898
972267AH1-718 GEN
Adder
2.828
276741O09 GEN1
Solar/Wind Harmer
0.167
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.157
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.889
946321AF1-296 GEN
Solar/Wind Harmer
2.577
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.976
270543AE2-219 C
Solar/Wind Harmer
3.137
276668AB2-070 GEN1
Solar/Wind Harmer
0.17
276848AB2-070 GEN3
Solar/Wind Harmer
0.169
276849AB2-070 GEN2
Solar/Wind Harmer
0.17
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.928
944221AF1-090 GEN
Solar/Wind Harmer
2.312
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.609
270223U2-072_GEN1
Solar/Wind Helper
0.876
270224U2-072_GEN2
Solar/Wind Helper
0.876
270227U2-072_GEN3
Solar/Wind Helper
0.876
270228U2-072_GEN4
Solar/Wind Helper
0.876
270231U2-072_GEN5
Solar/Wind Helper
0.876
966831AG1-554 GEN
Solar/Wind Helper
0.882
270499AE1-146 GEN
Solar/Wind Helper
1.968
945641AF1-229 GEN
Solar/Wind Helper
0.94
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
NYPJM->LTFIMP_NY
CLTF
1.264
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.656
CBM West 1LTFEXP_CBM-W1->PJM
CBM
70.253
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.933
MECLTFEXP_MEC->PJM
CLTF
9.784
SIGELTFEXP_SIGE->PJM
CLTF
0.201
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042
AG2-052LTFEXP_AG2-052->PJM
LTF
0.172
AH1-155LTFEXP_AH1-155->PJM
LTF
0.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.835
LAGNLTFEXP_LAGN->PJM
CLTF
5.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.51
TVALTFEXP_TVA->PJM
CLTF
2.319

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P1-2_#7442_200545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P1-2_#7442_200545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.01 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3190.2
MW Contribution:
11.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
3.653
24727105RPMNG2
50/50
1.309
270142AC1-141 CT1_
50/50
3.096
24642205MAYFLWER
50/50
0.047
944961AF1-161 GEN
50/50
3.701
962601AG1-109 GEN
50/50
3.701
944531AF1-118 GEN
Solar/Wind Harmer
62.885
270043AE2-236 GEN
Solar/Wind Harmer
8.814
965021AG1-366 GEN
Solar/Wind Harmer
4.247
270063AE2-323 C
Solar/Wind Harmer
0.001
24695305TIMB G C
Solar/Wind Harmer
0.832
270004AE1-209 GEN
Solar/Wind Harmer
2.117
970825AG2-519 GEN
Solar/Wind Harmer
7.011
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.926
946031AF1-268 GEN
Solar/Wind Harmer
8.826
945111AF1-176 GEN
Solar/Wind Harmer
7.395
270505AE1-170 C O1
Solar/Wind Harmer
9.418
970289AG2-191 GEN
Solar/Wind Harmer
0.975
971347AH1-153 GEN
Solar/Wind Harmer
4.396
247642Z2-115 C
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.299
270491AE1-102 GEN2
Solar/Wind Harmer
1.078
274752CRETE EC ;2U
Adder
9.326
274753CRETE EC ;3U
Adder
9.326
274724RIVER EC ;11
Adder
19.931
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.641
274807UNIV PK N;3U
Adder
5.629
274811UNIV PK N;7U
Adder
5.593
274803UNIV PARK;6U
Adder
6.433
274826FISK ;BP
Adder
12.06
274772LINCOLN ;3U
Adder
9.292
972038AH1-567 GEN2
Adder
0.401
274887GEN-1.85
Solar/Wind Harmer
0.199
276843GEN-1.7
Solar/Wind Harmer
0.248
276806AD2-047 C O1
Solar/Wind Harmer
4.34
972259AH1-714 GEN
Adder
20.761
274676JOLIET 29;8U
Adder
32.122
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
24.739
274730ELWOOD EC;6P
Adder
17.809
274734ELWOOD EC;8P
Adder
17.809
274736ELWOOD EC;9P
Adder
17.809
274729ELWOOD EC;1P
Adder
17.808
24729505KEY G4
50/50
13.443
24727205RPMNG3
50/50
1.301
24653605MOTTVILLE
50/50
0.005
24641605TWIN BRNCH
50/50
0.023
270144AC1-141 ST1_
50/50
2.734
270071AF1-092 GEN
Solar/Wind Harmer
25.488
959331AF2-224 GEN
Solar/Wind Harmer
8.919
970031AG2-029 GEN
Solar/Wind Harmer
6.248
24729405KEY G3
50/50
0.734
24729305KEY G2
50/50
0.721
24729205KEY G1
50/50
0.718
247620Y3-023
50/50
0.69
960851AF2-376 GEN
50/50
3.277
24643105BUCHANAN
50/50
0.016
247621Y3-024
50/50
0.324
944541AF1-119 GEN
Solar/Wind Harmer
0.834
960971AF2-388 GEN
Solar/Wind Harmer
7.331
942221AE2-234 GEN
Solar/Wind Harmer
4.522
944231AF1-091 GEN
Solar/Wind Harmer
24.786
270031AE2-169
Solar/Wind Harmer
5.613
270599AE1-208 GEN
Solar/Wind Harmer
9.355
270246TR4_N_V150
Solar/Wind Harmer
0.065
270247TR4_N_V136
Solar/Wind Harmer
0.065
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.696
961051AF2-396 GEN
Solar/Wind Harmer
17.945
961051AF2-396 GEN
Solar/Wind Harmer
11.963
971613AH1-306 GEN
Solar/Wind Harmer
4.3
970291AG2-192 GEN
Solar/Wind Harmer
1.152
970291AG2-192 GEN
Solar/Wind Harmer
0.532
970349AG2-230 GEN
Solar/Wind Harmer
13.187
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.54
965681AG1-436 GEN
Solar/Wind Harmer
10.47
965791AG1-447 GEN
Solar/Wind Harmer
7.678
246937BC-WTG2
Solar/Wind Harmer
0.334
247607V1-011 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
7.947
970885AG2-551 GEN
Solar/Wind Harmer
2.649
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.605
274808UNIV PK N;4U
Adder
5.568
274770LINCOLN ;1U
Adder
9.292
274771LINCOLN ;2U
Adder
9.292
274888KELLY CRK;1U
Solar/Wind Harmer
0.447
276776AD2-060 GEN
Solar/Wind Harmer
0.817
958011AF2-095 GEN
Solar/Wind Harmer
11.028
970941AG2-585 GEN
Solar/Wind Harmer
4.212
276897AD1-100 C
Solar/Wind Harmer
18.934
276893AG1-478 C
Solar/Wind Harmer
0.504
274674JOLIET 9 ;6U
Adder
16.683
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
11.155
274696ROCKY RD ;4P
Adder
12.055
274695ROCKY RD ;2P
Adder
11.777
274693ROCKY RD ;1P
Adder
11.662
274697ROCKY RD ;3P
Adder
3.199
274683WAUKEGAN ;8U
Adder
22.263
274683WAUKEGAN ;8U
Adder
18.767
958491AF2-143 GEN
Solar/Wind Harmer
11.026
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
21.97
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
14.375
971343AH1-151 GEN
Solar/Wind Harmer
14.375
972235AH1-702 GEN1
Adder
2.583
972236AH1-702 GEN2
Adder
2.246
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.805
938861AE1-114 GEN
Solar/Wind Harmer
4.01
274764LEE CO EC;5U
Adder
9.425
274765LEE CO EC;6U
Adder
9.425
274762LEE CO EC;3U
Adder
9.403
274763LEE CO EC;4U
Adder
9.314
276645AC1-214 GEN1
Solar/Wind Harmer
0.274
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.126
942111AE2-223 GEN
Solar/Wind Harmer
2.254
960611AF2-352 GEN
Solar/Wind Harmer
2.276
970241AG2-163 GEN
Solar/Wind Harmer
3.954
276615X2-022 GEN
Solar/Wind Harmer
0.066
276838X2-022 GEN2
Solar/Wind Harmer
0.361
945391AF1-204 GEN
Solar/Wind Harmer
6.631
276916AD2-100_GEN
Solar/Wind Harmer
12.922
276911AD2-131_GEN
Solar/Wind Harmer
0.851
24728805RICHG1
Adder
3.1
24728905RICHG2
Adder
3.1
970621AG2-405 GEN
Solar/Wind Harmer
1.034
971587AH1-292 GEN
Solar/Wind Harmer
3.867
964571AG1-320 GEN
Solar/Wind Harmer
2.864
270349AD2-093_GEN
Solar/Wind Helper
1.081
270471AD2-092_GEN
Solar/Wind Helper
1.081
270054AF2-122 C O1
Solar/Wind Helper
0.78
946101AF1-275 GEN
Solar/Wind Helper
0.301
960861AF2-377 GEN
50/50
3.382
970521AG2-332 GEN
50/50
16.165
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.308
270143AC1-141 CT2_
50/50
3.096
965011AG1-365 GEN
Solar/Wind Harmer
12.741
965651AG1-433 GEN
Solar/Wind Harmer
3.666
958861AF2-177 GEN
Solar/Wind Harmer
5.255
945371AF1-202 GEN
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.002
270005AE1-210 C O1
Solar/Wind Harmer
2.117
970825AG2-519 GEN
Solar/Wind Harmer
3.304
945111AF1-176 GEN
Solar/Wind Harmer
16.279
957891AF2-083 GEN
Solar/Wind Harmer
15.012
270594AE1-207 GEN
Solar/Wind Harmer
10.034
270032AE2-172
Solar/Wind Harmer
5.973
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
4.637
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
6.415
965421AG1-410 GEN
Solar/Wind Harmer
26.149
276903AD2-071 C
Solar/Wind Harmer
9.536
246936BC-WTG1
Solar/Wind Harmer
0.334
270489AE1-102 GEN1
Solar/Wind Harmer
1.078
970373AG2-245 GEN
Solar/Wind Harmer
16.897
270055AF2-134 C O1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
9.326
274754CRETE EC ;4U
Adder
9.326
274723RIVER EC ;12
Adder
20.174
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
5.593
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
10.122
274802UNIV PARK;5U
Adder
6.433
274773LINCOLN ;4U
Adder
9.292
274774LINCOLN ;5U
Adder
9.292
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.53
274676JOLIET 29;8U
Adder
33.312
941551AE2-152 GEN
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
16.683
274732ELWOOD EC;7P
Adder
17.809
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.972
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.208
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
19.011
274828WAUKEGAN ;BP
Adder
11.67
276805AD2-038 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
5.485
962781AG1-127 GEN
Solar/Wind Harmer
6.953
276882AE2-255 GEN
Solar/Wind Harmer
0.852
274872LEEDK;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.817
957471AF2-041 GEN
Solar/Wind Harmer
21.562
959081AF2-199 GEN
Solar/Wind Harmer
7.187
971067AG2-660 GEN
Solar/Wind Harmer
2.396
274822ROCKFORD ;11
Adder
20.159
970569AG2-363 GEN
Solar/Wind Harmer
21.445
970819AG2-516 GEN
Solar/Wind Harmer
8.554
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
9.403
274766LEE CO EC;7U
Adder
9.292
276646AC1-214 GEN2
Solar/Wind Harmer
0.274
276708O09 GEN2
Solar/Wind Harmer
0.247
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
9.71
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24728605AND G2
Adder
3.747
970773AG2-487 GEN
Solar/Wind Harmer
1.202
963741AG1-226 GEN
Solar/Wind Harmer
16.041
276621W2-048 GEN
Solar/Wind Harmer
0.32
965911AG1-460 GEN
Solar/Wind Harmer
1.24
23906502RICHG2&3
Adder
0.869
970091AG2-072 GEN
Adder
47.294
23920202STRYCT
Adder
0.781
241858AF1-205_GEN
Solar/Wind Harmer
1.344
270286AF1-227 GEN2
Solar/Wind Helper
0.431
270520AE2-214 GEN
Solar/Wind Helper
1.202
943121AE2-341 GEN
Solar/Wind Harmer
12.495
943591AF1-030 GEN
Solar/Wind Harmer
8.309
274862TOP CROP ;2U
Solar/Wind Harmer
1.004
274682WAUKEGAN ;7U
Adder
19.011
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
7.342
276868AE1-113 GEN
Solar/Wind Harmer
1.461
274879MINONK ;1U
Solar/Wind Harmer
0.305
946671AF1-331 GEN
Solar/Wind Harmer
0.771
274855GSG-6 ;RU
Solar/Wind Harmer
0.264
274850MENDOTA H;RU
Solar/Wind Harmer
0.084
959091AF2-200 GEN
Solar/Wind Harmer
14.375
970571AG2-364 GEN
Solar/Wind Harmer
14.297
24386205FR-12G C
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
9.403
274767LEE CO EC;8U
Adder
9.292
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.232
965091AG1-374 GEN
Solar/Wind Harmer
20.486
959611AF2-252 GEN
Solar/Wind Harmer
2.276
24728705AND G3
Adder
7.836
24728505AND G1
Adder
3.747
965931AG1-462 GEN
Solar/Wind Harmer
17.242
971087AG2-675 GEN
Solar/Wind Harmer
3.606
971993AH1-541 GEN
Solar/Wind Harmer
3.006
970193AG2-126 GEN
Solar/Wind Harmer
9.362
957381AF2-032 GEN
Solar/Wind Harmer
1.409
942481AE2-261 GEN
Solar/Wind Harmer
18.539
23906402RICHG1
Adder
0.876
23906502RICHG2&3
Adder
0.869
270541AE2-072 C
Solar/Wind Harmer
0
958321AF2-126 GEN
Solar/Wind Harmer
0.443
270284AF1-227 GEN1
Solar/Wind Helper
1.175
270287AF1-227 GEN3
Solar/Wind Helper
0.431
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
15.281
965041AG1-368 GEN
Solar/Wind Harmer
10.96
971609AH1-304 GEN
Solar/Wind Harmer
1.667
247521TR3_G114
Solar/Wind Harmer
0.367
965051AG1-369 GEN
Solar/Wind Harmer
5.063
964611AG1-324 GEN
Solar/Wind Harmer
3.62
971771AH1-392 GEN
Solar/Wind Harmer
8.998
970289AG2-191 GEN
Solar/Wind Harmer
1.684
270526AF1-158 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.341
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.05
971549AH1-272 GEN
Solar/Wind Harmer
17.043
270007AE1-245 C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
5.563
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.202
274827FISK ;RP
Adder
8.547
959141AF2-205 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
9.292
274776LINCOLN ;7U
Adder
9.292
274777LINCOLN ;8U
Adder
9.292
274800UNIV PARK;3U
Adder
6.411
274801UNIV PARK;4U
Adder
6.411
960591AF2-350 GEN
Solar/Wind Harmer
7.658
972228AH1-698 GEN2
Adder
4.051
972227AH1-698 GEN1
Adder
2.852
971611AH1-305 GEN
Solar/Wind Harmer
4.539
274687WILL CNTY;4U
Adder
30.416
274687WILL CNTY;4U
Adder
30.416
274675JOLIET 29;7U
Adder
33.312
274675JOLIET 29;7U
Adder
32.122
274728ELWOOD EC;5P
Adder
17.809
274731ELWOOD EC;2P
Adder
17.808
274733ELWOOD EC;3P
Adder
17.808
274735ELWOOD EC;4P
Adder
17.808
970833AG2-524 GEN
Solar/Wind Harmer
8.267
970833AG2-524 GEN
Solar/Wind Harmer
5.511
274744AC1-111 GEN8
Adder
5.972
274746AC1-111 G10
Adder
5.972
970073AG2-061 GEN
Solar/Wind Harmer
2.45
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.958
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
10.852
971675AH1-338 GEN
Solar/Wind Harmer
2.819
276861AD2-134 GEN
Solar/Wind Harmer
0.129
276863AD2-134 GEN
Solar/Wind Harmer
0.129
971171AH1-044 GEN
Solar/Wind Harmer
14.375
274823ROCKFORD ;21
Adder
20.012
970169AG2-114 GEN
Solar/Wind Harmer
7.144
926823AC1-168 GEN
Solar/Wind Harmer
1.213
274856ECOGROVE ;U1
Solar/Wind Harmer
0.166
24386405FR-21G C
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
11.398
972267AH1-718 GEN
Adder
4.17
276741O09 GEN1
Solar/Wind Harmer
0.247
274877BISHOP HL;1U
Solar/Wind Harmer
0.232
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.282
963841AG1-237 GEN
Solar/Wind Harmer
3.005
274854TWINGROVE;U2
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
3.807
276668AB2-070 GEN1
Solar/Wind Harmer
0.256
276848AB2-070 GEN3
Solar/Wind Harmer
0.255
276849AB2-070 GEN2
Solar/Wind Harmer
0.256
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
3.516
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
945411AF1-206 GEN
Solar/Wind Harmer
0
990792J1392
External Queue
6.545727729797363
990497J1323
External Queue
1.9028279781341553
991297J1743
External Queue
13.235071182250977
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
NYPJM->LTFIMP_NY
CLTF
1.989
LGEELTFEXP_LGEE->PJM
CLTF
3.263
WECLTFEXP_WEC->PJM
CLTF
3.91
CBM West 1LTFEXP_CBM-W1->PJM
CBM
127.333
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.471
MECLTFEXP_MEC->PJM
CLTF
14.518
SIGELTFEXP_SIGE->PJM
CLTF
0.335
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.507
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.388
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.688
LAGNLTFEXP_LAGN->PJM
CLTF
8.402
TVALTFEXP_TVA->PJM
CLTF
3.331

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.41 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6649.99
MW Contribution:
11.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.629
270100X2-052 CT1
50/50
3.353
270101X2-052 CT2
50/50
3.353
24643105BUCHANAN
50/50
0.028
274770LINCOLN ;1U
50/50
14.526
274771LINCOLN ;2U
50/50
14.526
970349AG2-230 GEN
Solar/Wind Harmer
35.834
965681AG1-436 GEN
Solar/Wind Harmer
28.223
965791AG1-447 GEN
Solar/Wind Harmer
14.44
961051AF2-396 GEN
Solar/Wind Harmer
34.84
961051AF2-396 GEN
Solar/Wind Harmer
16.205
270535AF1-215 GEN1
Solar/Wind Harmer
9.874
270536AF1-215 GEN2
Solar/Wind Harmer
9.874
247620Y3-023
Adder
1
274805UNIV PK N;1U
Adder
10.873
274808UNIV PK N;4U
Adder
10.802
274888KELLY CRK;1U
Solar/Wind Harmer
12.718
276776AD2-060 GEN
Solar/Wind Harmer
0.902
958011AF2-095 GEN
Solar/Wind Harmer
31.035
970941AG2-585 GEN
Solar/Wind Harmer
11.854
276897AD1-100 C
Solar/Wind Harmer
99.744
274674JOLIET 9 ;6U
Adder
32.864
276893AG1-478 C
Solar/Wind Harmer
0.935
958481AF2-142 GEN
Solar/Wind Harmer
31.384
945421AF1-207 GEN
Solar/Wind Harmer
29.389
957841AF2-078 GEN
Solar/Wind Harmer
12.652
274695ROCKY RD ;2P
Adder
23.281
274693ROCKY RD ;1P
Adder
23.052
274697ROCKY RD ;3P
Adder
6.324
274696ROCKY RD ;4P
Adder
23.83
274683WAUKEGAN ;8U
Adder
43.924
274683WAUKEGAN ;8U
Adder
37.026
962691AG1-118 GEN
Solar/Wind Harmer
62.281
960751AF2-366 GEN
Solar/Wind Harmer
5.941
958491AF2-143 GEN
Solar/Wind Harmer
31.025
276901AD2-066 C O1
Solar/Wind Harmer
7.247
270180AB1-006 GEN1
Solar/Wind Harmer
14.816
24697605MDL-3G C
Solar/Wind Harmer
7.593
24755605MDL-5G
Solar/Wind Harmer
4.966
24697905MDL-4G C
Solar/Wind Harmer
4.727
270181AB1-006 GEN2
Solar/Wind Harmer
1.473
276872AE1-163_GEN1
Solar/Wind Harmer
13.665
276876AE1-163_GEN2
Solar/Wind Harmer
13.665
971341AH1-150 GEN
Solar/Wind Harmer
40.651
971343AH1-151 GEN
Solar/Wind Harmer
40.651
972235AH1-702 GEN1
Adder
5.092
972236AH1-702 GEN2
Adder
4.428
274764LEE CO EC;5U
Adder
18.556
274765LEE CO EC;6U
Adder
18.556
274762LEE CO EC;3U
Adder
18.513
274763LEE CO EC;4U
Adder
18.338
247621Y3-024
Adder
0.34
24728805RICHG1
Adder
3.514
24728905RICHG2
Adder
3.514
270349AD2-093_GEN
Solar/Wind Helper
1.579
270471AD2-092_GEN
Solar/Wind Helper
1.579
270054AF2-122 C O1
Solar/Wind Helper
1.201
24344105CKG2
50/50
18.546
270143AC1-141 CT2_
50/50
5.373
274773LINCOLN ;4U
50/50
14.526
274774LINCOLN ;5U
50/50
14.526
24639705ELKHART HY
50/50
0.358
970521AG2-332 GEN
50/50
25.426
24307105BERRINSP G
50/50
0.047
270216AD2-079_GEN
Solar/Wind Harmer
1.347
957891AF2-083 GEN
Solar/Wind Harmer
33.169
972207SS24-0001
Solar/Wind Harmer
48.671
945111AF1-176 GEN
Solar/Wind Harmer
39.263
970373AG2-245 GEN
Solar/Wind Harmer
46.177
270449AD2-020 GEN
Solar/Wind Harmer
6.142
943021AE2-325 GEN
Solar/Wind Harmer
7.982
274723RIVER EC ;12
Adder
39.065
270055AF2-134 C O1
Solar/Wind Harmer
6.582
274751CRETE EC ;1U
Adder
10.642
274754CRETE EC ;4U
Adder
10.642
274812UNIV PK N;8U
Adder
10.85
274802UNIV PARK;5U
Adder
12.572
958381AF2-132 GEN
Solar/Wind Harmer
19.541
24441205WTRV SLR C
Solar/Wind Harmer
0.29
964861AG1-349 GEN
Solar/Wind Harmer
16.917
971917AH1-482 GEN
Solar/Wind Harmer
19.518
941551AE2-152 GEN
Solar/Wind Harmer
9.738
274676JOLIET 29;8U
Adder
65.574
274674JOLIET 9 ;6U
Adder
32.864
274732ELWOOD EC;7P
Adder
35.063
274871GR RIDGE ;2U
Solar/Wind Harmer
16.38
274847GR RIDGE ;BU
Solar/Wind Harmer
10.771
940581AE2-045 GEN
Solar/Wind Harmer
21.65
971605AH1-302 GEN
Solar/Wind Harmer
18.512
274745AC1-111 GEN9
Adder
11.828
276694AA1-018 GEN2
Solar/Wind Harmer
13.202
276691AA1-018 GEN1
Solar/Wind Harmer
1.578
274861TOP CROP ;1U
Solar/Wind Harmer
12.668
274682WAUKEGAN ;7U
Adder
37.511
274828WAUKEGAN ;BP
Adder
23.024
939401AE1-172 GEN
Solar/Wind Harmer
28.97
962781AG1-127 GEN
Solar/Wind Harmer
19.693
276805AD2-038 GEN
Solar/Wind Harmer
10.606
274872LEEDK;1U
Solar/Wind Harmer
16.96
24791305MDL-5G
Solar/Wind Harmer
4.966
276882AE2-255 GEN
Solar/Wind Harmer
6.943
971997AH1-543 GEN
Solar/Wind Harmer
32.39
957471AF2-041 GEN
Solar/Wind Harmer
60.976
959081AF2-199 GEN
Solar/Wind Harmer
20.325
971067AG2-660 GEN
Solar/Wind Harmer
4.727
274822ROCKFORD ;11
Adder
39.741
970819AG2-516 GEN
Solar/Wind Harmer
24.158
970569AG2-363 GEN
Solar/Wind Harmer
60.367
274761LEE CO EC;2U
Adder
18.513
274766LEE CO EC;7U
Adder
18.295
970091AG2-072 GEN
Adder
144.176
24728605AND G2
Adder
5.21
270142AC1-141 CT1_
50/50
5.373
24642205MAYFLWER
50/50
0.082
274772LINCOLN ;3U
50/50
14.526
944961AF1-161 GEN
50/50
6.371
962601AG1-109 GEN
50/50
6.371
971347AH1-153 GEN
Solar/Wind Harmer
11.945
24441505OLIV SLR
Solar/Wind Harmer
0.3
247643Z2-116 C
Solar/Wind Harmer
0.155
270505AE1-170 C O1
Solar/Wind Harmer
33.23
270043AE2-236 GEN
Solar/Wind Harmer
12.16
945111AF1-176 GEN
Solar/Wind Harmer
12.444
274724RIVER EC ;11
Adder
38.613
972231SS25-0005
Solar/Wind Harmer
20.663
972181SS23-001
Solar/Wind Harmer
12.914
274752CRETE EC ;2U
Adder
10.642
274753CRETE EC ;3U
Adder
10.642
276164X3-005 C
Solar/Wind Harmer
1.526
274814UNIV PK N;0U
Adder
10.945
274807UNIV PK N;3U
Adder
10.921
274811UNIV PK N;7U
Adder
10.85
970707AG2-453 GEN
Solar/Wind Harmer
60.612
274803UNIV PARK;6U
Adder
12.572
972259AH1-714 GEN
Adder
41.143
274826FISK ;BP
Adder
23.601
274887GEN-1.85
Solar/Wind Harmer
11.482
276772AC2-154 GEN
Solar/Wind Harmer
6.015
276843GEN-1.7
Solar/Wind Harmer
1.235
276806AD2-047 C O1
Solar/Wind Harmer
23.056
964401AG1-302 GEN
Solar/Wind Harmer
19.541
972038AH1-567 GEN2
Adder
0.786
939351AE1-166 GEN
Solar/Wind Harmer
12.734
274676JOLIET 29;8U
Adder
63.232
274729ELWOOD EC;1P
Adder
35.063
274730ELWOOD EC;6P
Adder
35.063
274734ELWOOD EC;8P
Adder
35.063
274736ELWOOD EC;9P
Adder
35.063
270063AE2-323 C
Solar/Wind Harmer
4.688
943121AE2-341 GEN
Solar/Wind Harmer
31.796
943591AF1-030 GEN
Solar/Wind Harmer
21.197
274862TOP CROP ;2U
Solar/Wind Harmer
10.577
274682WAUKEGAN ;7U
Adder
37.511
24690905MDL-1G C
Solar/Wind Harmer
16.538
970781AG2-491 GEN
Solar/Wind Harmer
20.6
276868AE1-113 GEN
Solar/Wind Harmer
20.83
274879MINONK ;1U
Solar/Wind Harmer
13.887
276799AD1-013 GEN
Solar/Wind Harmer
4.522
946671AF1-331 GEN
Solar/Wind Harmer
0.857
274855GSG-6 ;RU
Solar/Wind Harmer
7.552
274850MENDOTA H;RU
Solar/Wind Harmer
5.251
276602WESTBROOK C
Solar/Wind Harmer
4.348
944531AF1-118 GEN
Solar/Wind Harmer
71.22
959091AF2-200 GEN
Solar/Wind Harmer
40.651
970571AG2-364 GEN
Solar/Wind Harmer
40.244
274760LEE CO EC;1U
Adder
18.513
274767LEE CO EC;8U
Adder
18.295
24728705AND G3
Adder
10.897
24728505AND G1
Adder
5.21
24344005CKG1
50/50
14.512
270144AC1-141 ST1_
50/50
4.745
24641605TWIN BRNCH
50/50
0.038
274775LINCOLN ;6U
50/50
14.526
274776LINCOLN ;7U
50/50
14.526
274777LINCOLN ;8U
50/50
14.526
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
8.531
971771AH1-392 GEN
Solar/Wind Harmer
20.2
270526AF1-158 GEN
Solar/Wind Harmer
10.168
270071AF1-092 GEN
Solar/Wind Harmer
32.913
944161AF1-084 GEN
Solar/Wind Harmer
4.816
972037AH1-567 GEN1
Adder
0.395
274827FISK ;RP
Adder
16.726
960591AF2-350 GEN
Solar/Wind Harmer
21.552
972228AH1-698 GEN2
Adder
7.981
972227AH1-698 GEN1
Adder
5.619
274800UNIV PARK;3U
Adder
12.558
274801UNIV PARK;4U
Adder
12.558
958391AF2-133 GEN
Solar/Wind Harmer
19.434
274687WILL CNTY;4U
Adder
59.789
274687WILL CNTY;4U
Adder
59.789
274675JOLIET 29;7U
Adder
65.575
274675JOLIET 29;7U
Adder
63.233
959141AF2-205 GEN
Solar/Wind Harmer
12.902
274728ELWOOD EC;5P
Adder
35.063
274731ELWOOD EC;2P
Adder
35.063
274733ELWOOD EC;3P
Adder
35.063
274735ELWOOD EC;4P
Adder
35.063
276893AG1-478 C
Solar/Wind Harmer
1.173
970833AG2-524 GEN
Solar/Wind Harmer
18.607
970833AG2-524 GEN
Solar/Wind Harmer
8.654
274744AC1-111 GEN8
Adder
11.828
274746AC1-111 G10
Adder
11.828
970031AG2-029 GEN
Solar/Wind Harmer
52.483
970073AG2-061 GEN
Solar/Wind Harmer
4.81
946581AF1-322 GEN
Solar/Wind Harmer
21.078
24691005MDL-2G C
Solar/Wind Harmer
7.617
274863CRW1-WTG
Solar/Wind Harmer
11.445
274864CRW2-WTG
Solar/Wind Harmer
11.445
971675AH1-338 GEN
Solar/Wind Harmer
36.83
971411AH1-196 GEN
Solar/Wind Harmer
30.684
276861AD2-134 GEN
Solar/Wind Harmer
3.652
276863AD2-134 GEN
Solar/Wind Harmer
3.652
276889AE2-281 GEN
Solar/Wind Harmer
3.904
971171AH1-044 GEN
Solar/Wind Harmer
40.651
274823ROCKFORD ;21
Adder
39.453
970169AG2-114 GEN
Solar/Wind Harmer
20.21
926823AC1-168 GEN
Solar/Wind Harmer
8.655
274856ECOGROVE ;U1
Solar/Wind Harmer
6.778
276611AD2-172 GEN
Solar/Wind Harmer
5.142
276612AE2-035 GEN
Solar/Wind Harmer
5.142
24729505KEY G4
Adder
12.892
972267AH1-718 GEN
Adder
8.203
971681AH1-341 GEN
Solar/Wind Harmer
11.089
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.637
NYPJM->LTFIMP_NY
CLTF
3.564
LGEELTFEXP_LGEE->PJM
CLTF
4.159
WECLTFEXP_WEC->PJM
CLTF
7.696
CBM West 1LTFEXP_CBM-W1->PJM
CBM
233.845
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.749
MECLTFEXP_MEC->PJM
CLTF
28.15
SIGELTFEXP_SIGE->PJM
CLTF
0.543
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.39
AG2-052LTFEXP_AG2-052->PJM
LTF
0.487
AH1-155LTFEXP_AH1-155->PJM
LTF
0.73
CBM West 2LTFEXP_CBM-W2->PJM
CBM
138.616
LAGNLTFEXP_LAGN->PJM
CLTF
14.71
TVALTFEXP_TVA->PJM
CLTF
5.409

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.78 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6118.43
MW Contribution:
27.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
17.244
270143AC1-141 CT2_
50/50
5.002
24639705ELKHART HY
50/50
0.334
274773LINCOLN ;4U
50/50
13.44
274774LINCOLN ;5U
50/50
13.44
24344005CKG1
50/50
13.488
270144AC1-141 ST1_
50/50
4.417
24641605TWIN BRNCH
50/50
0.036
274775LINCOLN ;6U
50/50
13.44
274776LINCOLN ;7U
50/50
13.44
274777LINCOLN ;8U
50/50
13.44
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
7.886
971771AH1-392 GEN
Solar/Wind Harmer
18.775
270526AF1-158 GEN
Solar/Wind Harmer
9.429
270071AF1-092 GEN
Solar/Wind Harmer
30.976
944161AF1-084 GEN
Solar/Wind Harmer
4.48
972037AH1-567 GEN1
Adder
0.365
274827FISK ;RP
Adder
15.465
960591AF2-350 GEN
Solar/Wind Harmer
19.923
972228AH1-698 GEN2
Adder
7.377
972227AH1-698 GEN1
Adder
5.194
274800UNIV PARK;3U
Adder
11.611
274801UNIV PARK;4U
Adder
11.611
274687WILL CNTY;4U
Adder
55.279
274687WILL CNTY;4U
Adder
55.279
274675JOLIET 29;7U
Adder
60.629
274675JOLIET 29;7U
Adder
58.463
970031AG2-029 GEN
Solar/Wind Harmer
49.365
274728ELWOOD EC;5P
Adder
32.411
274731ELWOOD EC;2P
Adder
32.41
274733ELWOOD EC;3P
Adder
32.41
274735ELWOOD EC;4P
Adder
32.41
276893AG1-478 C
Solar/Wind Harmer
1.084
970833AG2-524 GEN
Solar/Wind Harmer
17.199
970833AG2-524 GEN
Solar/Wind Harmer
7.999
274744AC1-111 GEN8
Adder
10.938
274746AC1-111 G10
Adder
10.938
958391AF2-133 GEN
Solar/Wind Harmer
17.547
24729505KEY G4
Adder
12.548
959141AF2-205 GEN
Solar/Wind Harmer
11.629
970073AG2-061 GEN
Solar/Wind Harmer
4.443
971675AH1-338 GEN
Solar/Wind Harmer
34.055
971411AH1-196 GEN
Solar/Wind Harmer
28.375
276861AD2-134 GEN
Solar/Wind Harmer
3.377
276863AD2-134 GEN
Solar/Wind Harmer
3.377
274863CRW1-WTG
Solar/Wind Harmer
10.548
274864CRW2-WTG
Solar/Wind Harmer
10.548
971171AH1-044 GEN
Solar/Wind Harmer
37.588
270102X2-052 ST
50/50
3.355
270100X2-052 CT1
50/50
3.1
270101X2-052 CT2
50/50
3.1
24643105BUCHANAN
50/50
0.026
274770LINCOLN ;1U
50/50
13.44
274771LINCOLN ;2U
50/50
13.44
247620Y3-023
50/50
0.991
970349AG2-230 GEN
Solar/Wind Harmer
33.323
965681AG1-436 GEN
Solar/Wind Harmer
26.089
965791AG1-447 GEN
Solar/Wind Harmer
13.348
961051AF2-396 GEN
Solar/Wind Harmer
32.427
961051AF2-396 GEN
Solar/Wind Harmer
15.082
274805UNIV PK N;1U
Adder
10.052
274808UNIV PK N;4U
Adder
9.986
276889AE2-281 GEN
Solar/Wind Harmer
3.605
274823ROCKFORD ;21
Adder
36.484
970169AG2-114 GEN
Solar/Wind Harmer
18.611
274856ECOGROVE ;U1
Solar/Wind Harmer
6.268
276611AD2-172 GEN
Solar/Wind Harmer
4.755
276612AE2-035 GEN
Solar/Wind Harmer
4.755
926823AC1-168 GEN
Solar/Wind Harmer
7.988
971549AH1-272 GEN
Solar/Wind Harmer
34.293
971681AH1-341 GEN
Solar/Wind Harmer
27.72
972267AH1-718 GEN
Adder
7.584
274888KELLY CRK;1U
Solar/Wind Harmer
11.757
276776AD2-060 GEN
Solar/Wind Harmer
0.834
958011AF2-095 GEN
Solar/Wind Harmer
28.69
970941AG2-585 GEN
Solar/Wind Harmer
10.958
276897AD1-100 C
Solar/Wind Harmer
92.171
270535AF1-215 GEN1
Solar/Wind Harmer
8.976
270536AF1-215 GEN2
Solar/Wind Harmer
8.976
274674JOLIET 9 ;6U
Adder
30.381
276893AG1-478 C
Solar/Wind Harmer
0.864
274695ROCKY RD ;2P
Adder
21.528
274693ROCKY RD ;1P
Adder
21.316
274697ROCKY RD ;3P
Adder
5.848
274696ROCKY RD ;4P
Adder
22.036
958481AF2-142 GEN
Solar/Wind Harmer
28.999
274683WAUKEGAN ;8U
Adder
40.618
274683WAUKEGAN ;8U
Adder
34.239
962691AG1-118 GEN
Solar/Wind Harmer
57.593
960751AF2-366 GEN
Solar/Wind Harmer
5.494
958491AF2-143 GEN
Solar/Wind Harmer
28.659
276901AD2-066 C O1
Solar/Wind Harmer
6.693
971341AH1-150 GEN
Solar/Wind Harmer
37.588
971343AH1-151 GEN
Solar/Wind Harmer
37.588
276872AE1-163_GEN1
Solar/Wind Harmer
12.619
276876AE1-163_GEN2
Solar/Wind Harmer
12.619
945421AF1-207 GEN
Solar/Wind Harmer
26.261
957841AF2-078 GEN
Solar/Wind Harmer
11.305
972235AH1-702 GEN1
Adder
4.708
972236AH1-702 GEN2
Adder
4.094
938861AE1-114 GEN
Solar/Wind Harmer
15.142
274764LEE CO EC;5U
Adder
17.158
274765LEE CO EC;6U
Adder
17.158
274762LEE CO EC;3U
Adder
17.118
274763LEE CO EC;4U
Adder
16.956
247621Y3-024
Adder
0.337
24728805RICHG1
Adder
3.728
24728905RICHG2
Adder
3.728
270349AD2-093_GEN
Solar/Wind Helper
1.56
270471AD2-092_GEN
Solar/Wind Helper
1.56
970521AG2-332 GEN
50/50
23.718
24307105BERRINSP G
50/50
0.044
270216AD2-079_GEN
Solar/Wind Harmer
1.255
957891AF2-083 GEN
Solar/Wind Harmer
30.868
945111AF1-176 GEN
Solar/Wind Harmer
36.559
972207SS24-0001
Solar/Wind Harmer
45.031
270449AD2-020 GEN
Solar/Wind Harmer
5.715
943021AE2-325 GEN
Solar/Wind Harmer
7.427
274723RIVER EC ;12
Adder
36.127
274751CRETE EC ;1U
Adder
9.837
274754CRETE EC ;4U
Adder
9.837
970373AG2-245 GEN
Solar/Wind Harmer
42.152
274812UNIV PK N;8U
Adder
10.03
24441205WTRV SLR C
Solar/Wind Harmer
0.27
274802UNIV PARK;5U
Adder
11.623
941551AE2-152 GEN
Solar/Wind Harmer
8.999
270055AF2-134 C O1
Solar/Wind Harmer
5.984
274676JOLIET 29;8U
Adder
60.628
274674JOLIET 9 ;6U
Adder
30.381
274732ELWOOD EC;7P
Adder
32.411
274871GR RIDGE ;2U
Solar/Wind Harmer
15.14
274847GR RIDGE ;BU
Solar/Wind Harmer
9.956
274745AC1-111 GEN9
Adder
10.938
958381AF2-132 GEN
Solar/Wind Harmer
17.685
964861AG1-349 GEN
Solar/Wind Harmer
15.303
971917AH1-482 GEN
Solar/Wind Harmer
17.655
276694AA1-018 GEN2
Solar/Wind Harmer
12.198
276691AA1-018 GEN1
Solar/Wind Harmer
1.458
274861TOP CROP ;1U
Solar/Wind Harmer
11.705
274682WAUKEGAN ;7U
Adder
34.688
274828WAUKEGAN ;BP
Adder
21.291
939401AE1-172 GEN
Solar/Wind Harmer
26.719
962781AG1-127 GEN
Solar/Wind Harmer
18.21
274872LEEDK;1U
Solar/Wind Harmer
15.683
276805AD2-038 GEN
Solar/Wind Harmer
9.797
940581AE2-045 GEN
Solar/Wind Harmer
19.469
971605AH1-302 GEN
Solar/Wind Harmer
16.647
276882AE2-255 GEN
Solar/Wind Harmer
6.414
971997AH1-543 GEN
Solar/Wind Harmer
29.912
957471AF2-041 GEN
Solar/Wind Harmer
56.382
959081AF2-199 GEN
Solar/Wind Harmer
18.794
971067AG2-660 GEN
Solar/Wind Harmer
4.371
274822ROCKFORD ;11
Adder
36.75
970819AG2-516 GEN
Solar/Wind Harmer
22.34
970569AG2-363 GEN
Solar/Wind Harmer
55.727
274858EASY ROAD;U2
Solar/Wind Harmer
8.815
274761LEE CO EC;2U
Adder
17.118
274766LEE CO EC;7U
Adder
16.916
970091AG2-072 GEN
Adder
105.385
24728605AND G2
Adder
5.1
270142AC1-141 CT1_
50/50
5.002
24642205MAYFLWER
50/50
0.076
274772LINCOLN ;3U
50/50
13.44
944961AF1-161 GEN
50/50
5.928
962601AG1-109 GEN
50/50
5.928
971347AH1-153 GEN
Solar/Wind Harmer
11.108
270043AE2-236 GEN
Solar/Wind Harmer
11.544
247643Z2-116 C
Solar/Wind Harmer
0.145
24441505OLIV SLR
Solar/Wind Harmer
0.278
270505AE1-170 C O1
Solar/Wind Harmer
30.925
945111AF1-176 GEN
Solar/Wind Harmer
11.586
274724RIVER EC ;11
Adder
35.711
972231SS25-0005
Solar/Wind Harmer
19.1
972181SS23-001
Solar/Wind Harmer
11.937
274752CRETE EC ;2U
Adder
9.837
274753CRETE EC ;3U
Adder
9.837
276164X3-005 C
Solar/Wind Harmer
1.411
270063AE2-323 C
Solar/Wind Harmer
4.403
274814UNIV PK N;0U
Adder
10.117
274807UNIV PK N;3U
Adder
10.095
274811UNIV PK N;7U
Adder
10.03
970707AG2-453 GEN
Solar/Wind Harmer
56.064
972259AH1-714 GEN
Adder
38.042
274803UNIV PARK;6U
Adder
11.623
274826FISK ;BP
Adder
21.822
274887GEN-1.85
Solar/Wind Harmer
10.615
276772AC2-154 GEN
Solar/Wind Harmer
5.56
276843GEN-1.7
Solar/Wind Harmer
1.142
276806AD2-047 C O1
Solar/Wind Harmer
21.313
972038AH1-567 GEN2
Adder
0.727
939351AE1-166 GEN
Solar/Wind Harmer
11.767
944531AF1-118 GEN
Solar/Wind Harmer
69.202
274676JOLIET 29;8U
Adder
58.463
274729ELWOOD EC;1P
Adder
32.41
274730ELWOOD EC;6P
Adder
32.411
274734ELWOOD EC;8P
Adder
32.411
274736ELWOOD EC;9P
Adder
32.411
943121AE2-341 GEN
Solar/Wind Harmer
29.406
943591AF1-030 GEN
Solar/Wind Harmer
19.604
964401AG1-302 GEN
Solar/Wind Harmer
17.685
274862TOP CROP ;2U
Solar/Wind Harmer
9.773
274682WAUKEGAN ;7U
Adder
34.688
276868AE1-113 GEN
Solar/Wind Harmer
19.24
274879MINONK ;1U
Solar/Wind Harmer
12.827
276799AD1-013 GEN
Solar/Wind Harmer
4.182
946671AF1-331 GEN
Solar/Wind Harmer
0.792
274855GSG-6 ;RU
Solar/Wind Harmer
6.983
274850MENDOTA H;RU
Solar/Wind Harmer
4.855
276602WESTBROOK C
Solar/Wind Harmer
4.02
959091AF2-200 GEN
Solar/Wind Harmer
37.588
970571AG2-364 GEN
Solar/Wind Harmer
37.151
274857EASY ROAD;U1
Solar/Wind Harmer
8.815
274760LEE CO EC;1U
Adder
17.118
274767LEE CO EC;8U
Adder
16.916
24728705AND G3
Adder
10.665
24728505AND G1
Adder
5.1
24690905MDL-1G C
Solar/Wind Harmer
9.079
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.518
NYPJM->LTFIMP_NY
CLTF
3.401
LGEELTFEXP_LGEE->PJM
CLTF
5.607
WECLTFEXP_WEC->PJM
CLTF
7.118
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.218
MECLTFEXP_MEC->PJM
CLTF
26.088
SIGELTFEXP_SIGE->PJM
CLTF
0.553
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.195
AG2-052LTFEXP_AG2-052->PJM
LTF
0.448
AH1-155LTFEXP_AH1-155->PJM
LTF
0.672
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.543
LAGNLTFEXP_LAGN->PJM
CLTF
14.187
TVALTFEXP_TVA->PJM
CLTF
5.423

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.5 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6047.92
MW Contribution:
27.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
13.518
270144AC1-141 ST1_
50/50
4.427
24641605TWIN BRNCH
50/50
0.036
274775LINCOLN ;6U
50/50
13.47
274776LINCOLN ;7U
50/50
13.47
274777LINCOLN ;8U
50/50
13.47
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
7.904
971771AH1-392 GEN
Solar/Wind Harmer
18.817
270526AF1-158 GEN
Solar/Wind Harmer
9.45
270071AF1-092 GEN
Solar/Wind Harmer
31.045
944161AF1-084 GEN
Solar/Wind Harmer
4.491
972037AH1-567 GEN1
Adder
0.366
274827FISK ;RP
Adder
15.501
960591AF2-350 GEN
Solar/Wind Harmer
19.969
972228AH1-698 GEN2
Adder
7.394
972227AH1-698 GEN1
Adder
5.206
274800UNIV PARK;3U
Adder
11.637
274801UNIV PARK;4U
Adder
11.637
274687WILL CNTY;4U
Adder
55.408
274687WILL CNTY;4U
Adder
55.408
274675JOLIET 29;7U
Adder
60.77
24344105CKG2
50/50
17.278
270143AC1-141 CT2_
50/50
5.013
24639705ELKHART HY
50/50
0.334
274773LINCOLN ;4U
50/50
13.47
274774LINCOLN ;5U
50/50
13.47
970521AG2-332 GEN
50/50
23.772
24307105BERRINSP G
50/50
0.044
270216AD2-079_GEN
Solar/Wind Harmer
1.258
270102X2-052 ST
50/50
3.362
270100X2-052 CT1
50/50
3.107
270101X2-052 CT2
50/50
3.107
24643105BUCHANAN
50/50
0.026
274770LINCOLN ;1U
50/50
13.47
274771LINCOLN ;2U
50/50
13.47
247620Y3-023
50/50
0.993
970349AG2-230 GEN
Solar/Wind Harmer
33.392
965681AG1-436 GEN
Solar/Wind Harmer
26.146
965791AG1-447 GEN
Solar/Wind Harmer
13.377
961051AF2-396 GEN
Solar/Wind Harmer
32.5
961051AF2-396 GEN
Solar/Wind Harmer
15.116
274805UNIV PK N;1U
Adder
10.075
274808UNIV PK N;4U
Adder
10.009
274888KELLY CRK;1U
Solar/Wind Harmer
11.784
276776AD2-060 GEN
Solar/Wind Harmer
0.836
958011AF2-095 GEN
Solar/Wind Harmer
28.756
970941AG2-585 GEN
Solar/Wind Harmer
10.983
276897AD1-100 C
Solar/Wind Harmer
92.385
270535AF1-215 GEN1
Solar/Wind Harmer
8.997
270536AF1-215 GEN2
Solar/Wind Harmer
8.997
274674JOLIET 9 ;6U
Adder
30.452
276893AG1-478 C
Solar/Wind Harmer
0.866
274695ROCKY RD ;2P
Adder
21.58
274693ROCKY RD ;1P
Adder
21.367
274697ROCKY RD ;3P
Adder
5.862
274696ROCKY RD ;4P
Adder
22.088
958481AF2-142 GEN
Solar/Wind Harmer
29.068
274683WAUKEGAN ;8U
Adder
40.715
274683WAUKEGAN ;8U
Adder
34.321
962691AG1-118 GEN
Solar/Wind Harmer
57.731
960751AF2-366 GEN
Solar/Wind Harmer
5.507
958491AF2-143 GEN
Solar/Wind Harmer
28.728
276901AD2-066 C O1
Solar/Wind Harmer
6.709
971341AH1-150 GEN
Solar/Wind Harmer
37.68
971343AH1-151 GEN
Solar/Wind Harmer
37.68
276872AE1-163_GEN1
Solar/Wind Harmer
12.65
276876AE1-163_GEN2
Solar/Wind Harmer
12.65
945421AF1-207 GEN
Solar/Wind Harmer
26.326
957841AF2-078 GEN
Solar/Wind Harmer
11.333
972235AH1-702 GEN1
Adder
4.72
972236AH1-702 GEN2
Adder
4.104
938861AE1-114 GEN
Solar/Wind Harmer
15.18
274764LEE CO EC;5U
Adder
17.201
274765LEE CO EC;6U
Adder
17.201
274762LEE CO EC;3U
Adder
17.161
274763LEE CO EC;4U
Adder
16.999
247621Y3-024
Adder
0.338
24728805RICHG1
Adder
3.746
24728905RICHG2
Adder
3.746
270349AD2-093_GEN
Solar/Wind Helper
1.553
270471AD2-092_GEN
Solar/Wind Helper
1.553
957891AF2-083 GEN
Solar/Wind Harmer
30.937
945111AF1-176 GEN
Solar/Wind Harmer
36.641
972207SS24-0001
Solar/Wind Harmer
45.133
270449AD2-020 GEN
Solar/Wind Harmer
5.728
943021AE2-325 GEN
Solar/Wind Harmer
7.444
274723RIVER EC ;12
Adder
36.21
274751CRETE EC ;1U
Adder
9.86
274754CRETE EC ;4U
Adder
9.86
970373AG2-245 GEN
Solar/Wind Harmer
42.249
274812UNIV PK N;8U
Adder
10.053
24441205WTRV SLR C
Solar/Wind Harmer
0.27
274802UNIV PARK;5U
Adder
11.65
941551AE2-152 GEN
Solar/Wind Harmer
9.02
270055AF2-134 C O1
Solar/Wind Harmer
5.998
274676JOLIET 29;8U
Adder
60.769
274674JOLIET 9 ;6U
Adder
30.452
274732ELWOOD EC;7P
Adder
32.486
274871GR RIDGE ;2U
Solar/Wind Harmer
15.176
274847GR RIDGE ;BU
Solar/Wind Harmer
9.979
274745AC1-111 GEN9
Adder
10.963
958381AF2-132 GEN
Solar/Wind Harmer
17.727
964861AG1-349 GEN
Solar/Wind Harmer
15.339
971917AH1-482 GEN
Solar/Wind Harmer
17.697
276694AA1-018 GEN2
Solar/Wind Harmer
12.227
276691AA1-018 GEN1
Solar/Wind Harmer
1.461
274861TOP CROP ;1U
Solar/Wind Harmer
11.733
274682WAUKEGAN ;7U
Adder
34.771
274828WAUKEGAN ;BP
Adder
21.342
939401AE1-172 GEN
Solar/Wind Harmer
26.783
962781AG1-127 GEN
Solar/Wind Harmer
18.254
276805AD2-038 GEN
Solar/Wind Harmer
9.821
274872LEEDK;1U
Solar/Wind Harmer
15.721
940581AE2-045 GEN
Solar/Wind Harmer
19.516
971605AH1-302 GEN
Solar/Wind Harmer
16.687
276882AE2-255 GEN
Solar/Wind Harmer
6.429
971997AH1-543 GEN
Solar/Wind Harmer
29.984
957471AF2-041 GEN
Solar/Wind Harmer
56.52
959081AF2-199 GEN
Solar/Wind Harmer
18.84
971067AG2-660 GEN
Solar/Wind Harmer
4.381
274822ROCKFORD ;11
Adder
36.841
970819AG2-516 GEN
Solar/Wind Harmer
22.395
970569AG2-363 GEN
Solar/Wind Harmer
55.866
274858EASY ROAD;U2
Solar/Wind Harmer
8.837
274761LEE CO EC;2U
Adder
17.161
274766LEE CO EC;7U
Adder
16.958
970091AG2-072 GEN
Adder
105.739
24728605AND G2
Adder
5.117
270142AC1-141 CT1_
50/50
5.013
24642205MAYFLWER
50/50
0.076
274772LINCOLN ;3U
50/50
13.47
944961AF1-161 GEN
50/50
5.942
962601AG1-109 GEN
50/50
5.942
971347AH1-153 GEN
Solar/Wind Harmer
11.131
270043AE2-236 GEN
Solar/Wind Harmer
11.57
247643Z2-116 C
Solar/Wind Harmer
0.145
24441505OLIV SLR
Solar/Wind Harmer
0.278
270505AE1-170 C O1
Solar/Wind Harmer
30.994
945111AF1-176 GEN
Solar/Wind Harmer
11.613
274724RIVER EC ;11
Adder
35.793
972231SS25-0005
Solar/Wind Harmer
19.144
972181SS23-001
Solar/Wind Harmer
11.965
274752CRETE EC ;2U
Adder
9.86
274753CRETE EC ;3U
Adder
9.86
276164X3-005 C
Solar/Wind Harmer
1.414
270063AE2-323 C
Solar/Wind Harmer
4.413
274814UNIV PK N;0U
Adder
10.141
274807UNIV PK N;3U
Adder
10.119
274811UNIV PK N;7U
Adder
10.053
970707AG2-453 GEN
Solar/Wind Harmer
56.193
972259AH1-714 GEN
Adder
38.13
274803UNIV PARK;6U
Adder
11.65
274826FISK ;BP
Adder
21.872
274887GEN-1.85
Solar/Wind Harmer
10.639
276772AC2-154 GEN
Solar/Wind Harmer
5.573
276843GEN-1.7
Solar/Wind Harmer
1.145
276806AD2-047 C O1
Solar/Wind Harmer
21.363
972038AH1-567 GEN2
Adder
0.728
939351AE1-166 GEN
Solar/Wind Harmer
11.795
944531AF1-118 GEN
Solar/Wind Harmer
69.364
274676JOLIET 29;8U
Adder
58.599
274729ELWOOD EC;1P
Adder
32.486
274730ELWOOD EC;6P
Adder
32.486
274734ELWOOD EC;8P
Adder
32.486
274736ELWOOD EC;9P
Adder
32.486
943121AE2-341 GEN
Solar/Wind Harmer
29.475
943591AF1-030 GEN
Solar/Wind Harmer
19.65
964401AG1-302 GEN
Solar/Wind Harmer
17.727
274862TOP CROP ;2U
Solar/Wind Harmer
9.796
274682WAUKEGAN ;7U
Adder
34.771
276868AE1-113 GEN
Solar/Wind Harmer
19.287
274879MINONK ;1U
Solar/Wind Harmer
12.858
276799AD1-013 GEN
Solar/Wind Harmer
4.192
946671AF1-331 GEN
Solar/Wind Harmer
0.794
274855GSG-6 ;RU
Solar/Wind Harmer
7
274850MENDOTA H;RU
Solar/Wind Harmer
4.867
276602WESTBROOK C
Solar/Wind Harmer
4.03
959091AF2-200 GEN
Solar/Wind Harmer
37.68
970571AG2-364 GEN
Solar/Wind Harmer
37.244
274857EASY ROAD;U1
Solar/Wind Harmer
8.837
274760LEE CO EC;1U
Adder
17.161
274767LEE CO EC;8U
Adder
16.958
24728705AND G3
Adder
10.702
24728505AND G1
Adder
5.117
24690905MDL-1G C
Solar/Wind Harmer
9.102
274675JOLIET 29;7U
Adder
58.6
970031AG2-029 GEN
Solar/Wind Harmer
49.481
274728ELWOOD EC;5P
Adder
32.486
274731ELWOOD EC;2P
Adder
32.486
274733ELWOOD EC;3P
Adder
32.486
274735ELWOOD EC;4P
Adder
32.486
276893AG1-478 C
Solar/Wind Harmer
1.086
970833AG2-524 GEN
Solar/Wind Harmer
17.239
970833AG2-524 GEN
Solar/Wind Harmer
8.018
274744AC1-111 GEN8
Adder
10.963
274746AC1-111 G10
Adder
10.963
958391AF2-133 GEN
Solar/Wind Harmer
17.588
24729505KEY G4
Adder
12.577
959141AF2-205 GEN
Solar/Wind Harmer
11.657
970073AG2-061 GEN
Solar/Wind Harmer
4.454
971675AH1-338 GEN
Solar/Wind Harmer
34.138
971411AH1-196 GEN
Solar/Wind Harmer
28.444
276861AD2-134 GEN
Solar/Wind Harmer
3.385
276863AD2-134 GEN
Solar/Wind Harmer
3.385
274863CRW1-WTG
Solar/Wind Harmer
10.573
274864CRW2-WTG
Solar/Wind Harmer
10.573
971171AH1-044 GEN
Solar/Wind Harmer
37.68
276889AE2-281 GEN
Solar/Wind Harmer
3.614
274823ROCKFORD ;21
Adder
36.573
970169AG2-114 GEN
Solar/Wind Harmer
18.658
274856ECOGROVE ;U1
Solar/Wind Harmer
6.284
276611AD2-172 GEN
Solar/Wind Harmer
4.767
276612AE2-035 GEN
Solar/Wind Harmer
4.767
926823AC1-168 GEN
Solar/Wind Harmer
8.008
971549AH1-272 GEN
Solar/Wind Harmer
34.378
971681AH1-341 GEN
Solar/Wind Harmer
27.789
972267AH1-718 GEN
Adder
7.604
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5
NYPJM->LTFIMP_NY
CLTF
3.371
LGEELTFEXP_LGEE->PJM
CLTF
5.638
WECLTFEXP_WEC->PJM
CLTF
7.136
CBM West 1LTFEXP_CBM-W1->PJM
CBM
218.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.394
MECLTFEXP_MEC->PJM
CLTF
26.166
SIGELTFEXP_SIGE->PJM
CLTF
0.556
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.164
AG2-052LTFEXP_AG2-052->PJM
LTF
0.449
AH1-155LTFEXP_AH1-155->PJM
LTF
0.674
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.166
LAGNLTFEXP_LAGN->PJM
CLTF
14.281
TVALTFEXP_TVA->PJM
CLTF
5.469

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.53 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5607.44
MW Contribution:
20.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.362
270100X2-052 CT1
50/50
3.107
270101X2-052 CT2
50/50
3.107
24643105BUCHANAN
50/50
0.026
274770LINCOLN ;1U
50/50
18.336
274771LINCOLN ;2U
50/50
18.336
247620Y3-023
50/50
0.993
970349AG2-230 GEN
Solar/Wind Harmer
23.297
965681AG1-436 GEN
Solar/Wind Harmer
18.242
965791AG1-447 GEN
Solar/Wind Harmer
13.377
961051AF2-396 GEN
Solar/Wind Harmer
28.57
961051AF2-396 GEN
Solar/Wind Harmer
19.046
274805UNIV PK N;1U
Adder
10.075
274808UNIV PK N;4U
Adder
10.009
274888KELLY CRK;1U
Solar/Wind Harmer
0.813
276776AD2-060 GEN
Solar/Wind Harmer
1.486
958011AF2-095 GEN
Solar/Wind Harmer
20.062
970941AG2-585 GEN
Solar/Wind Harmer
7.663
276897AD1-100 C
Solar/Wind Harmer
34.688
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
30.452
276893AG1-478 C
Solar/Wind Harmer
0.919
274695ROCKY RD ;2P
Adder
21.58
274693ROCKY RD ;1P
Adder
21.367
274697ROCKY RD ;3P
Adder
5.862
274696ROCKY RD ;4P
Adder
22.088
958481AF2-142 GEN
Solar/Wind Harmer
20.28
274683WAUKEGAN ;8U
Adder
40.715
274683WAUKEGAN ;8U
Adder
34.321
962691AG1-118 GEN
Solar/Wind Harmer
40.277
958491AF2-143 GEN
Solar/Wind Harmer
20.043
276901AD2-066 C O1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
26.289
971343AH1-151 GEN
Solar/Wind Harmer
26.289
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
4.72
972236AH1-702 GEN2
Adder
4.104
938861AE1-114 GEN
Solar/Wind Harmer
7.321
274764LEE CO EC;5U
Adder
17.201
274765LEE CO EC;6U
Adder
17.201
274762LEE CO EC;3U
Adder
17.161
274763LEE CO EC;4U
Adder
16.999
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
2.052
276645AC1-214 GEN1
Solar/Wind Harmer
0.499
944541AF1-119 GEN
Solar/Wind Harmer
0.848
960971AF2-388 GEN
Solar/Wind Harmer
7.448
942111AE2-223 GEN
Solar/Wind Harmer
4.087
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
1.408
960611AF2-352 GEN
Solar/Wind Harmer
4.121
942221AE2-234 GEN
Solar/Wind Harmer
4.822
970241AG2-163 GEN
Solar/Wind Harmer
6.864
970291AG2-192 GEN
Solar/Wind Harmer
1.502
970291AG2-192 GEN
Solar/Wind Harmer
0.693
276615X2-022 GEN
Solar/Wind Harmer
0.119
276838X2-022 GEN2
Solar/Wind Harmer
0.647
944231AF1-091 GEN
Solar/Wind Harmer
26.413
971613AH1-306 GEN
Solar/Wind Harmer
5.417
270031AE2-169
Solar/Wind Harmer
6.202
270599AE1-208 GEN
Solar/Wind Harmer
10.337
276916AD2-100_GEN
Solar/Wind Harmer
23.132
276911AD2-131_GEN
Solar/Wind Harmer
1.524
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
11.354
964611AG1-324 GEN
Solar/Wind Harmer
0.771
270201AC2-176 GEN
Solar/Wind Harmer
0
270246TR4_N_V150
Solar/Wind Harmer
0.065
270247TR4_N_V136
Solar/Wind Harmer
0.065
971587AH1-292 GEN
Solar/Wind Harmer
7.235
247621Y3-024
Adder
0.338
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
8.884
970885AG2-551 GEN
Solar/Wind Harmer
2.961
970623AG2-406 GEN
Solar/Wind Harmer
1.577
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.325
24728805RICHG1
Adder
3.746
24728905RICHG2
Adder
3.746
270349AD2-093_GEN
Solar/Wind Helper
1.553
270471AD2-092_GEN
Solar/Wind Helper
1.553
24344105CKG2
50/50
17.278
270143AC1-141 CT2_
50/50
5.013
24639705ELKHART HY
50/50
0.334
274773LINCOLN ;4U
50/50
18.336
274774LINCOLN ;5U
50/50
18.336
970521AG2-332 GEN
50/50
23.772
24307105BERRINSP G
50/50
0.044
957891AF2-083 GEN
Solar/Wind Harmer
23.982
945111AF1-176 GEN
Solar/Wind Harmer
25.563
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
7.444
274723RIVER EC ;12
Adder
36.21
274751CRETE EC ;1U
Adder
16.621
274754CRETE EC ;4U
Adder
16.621
970373AG2-245 GEN
Solar/Wind Harmer
29.476
274812UNIV PK N;8U
Adder
10.053
274802UNIV PARK;5U
Adder
11.65
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
60.769
274674JOLIET 9 ;6U
Adder
30.452
274732ELWOOD EC;7P
Adder
32.486
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
10.963
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
17.697
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
2.197
274861TOP CROP ;1U
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
34.771
274828WAUKEGAN ;BP
Adder
21.342
939401AE1-172 GEN
Solar/Wind Harmer
10.03
962781AG1-127 GEN
Solar/Wind Harmer
12.744
276805AD2-038 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
-0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
16.687
276882AE2-255 GEN
Solar/Wind Harmer
1.552
971997AH1-543 GEN
Solar/Wind Harmer
6.973
957471AF2-041 GEN
Solar/Wind Harmer
39.433
959081AF2-199 GEN
Solar/Wind Harmer
13.144
971067AG2-660 GEN
Solar/Wind Harmer
4.381
274822ROCKFORD ;11
Adder
36.841
970819AG2-516 GEN
Solar/Wind Harmer
15.625
970569AG2-363 GEN
Solar/Wind Harmer
38.976
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
17.161
274766LEE CO EC;7U
Adder
16.958
965011AG1-365 GEN
Solar/Wind Harmer
12.784
276708O09 GEN2
Solar/Wind Harmer
0.449
276646AC1-214 GEN2
Solar/Wind Harmer
0.499
965651AG1-433 GEN
Solar/Wind Harmer
3.724
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
17.604
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
5.383
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
27.848
276621W2-048 GEN
Solar/Wind Harmer
0.575
270594AE1-207 GEN
Solar/Wind Harmer
12.64
270032AE2-172
Solar/Wind Harmer
7.524
965911AG1-460 GEN
Solar/Wind Harmer
2.221
276903AD2-071 C
Solar/Wind Harmer
12.218
270024AE2-089 GEN
Solar/Wind Harmer
0.002
270005AE1-210 C O1
Solar/Wind Harmer
2.315
970825AG2-519 GEN
Solar/Wind Harmer
3.725
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.127
970091AG2-072 GEN
Adder
105.739
24728605AND G2
Adder
5.117
965421AG1-410 GEN
Solar/Wind Harmer
25.535
970773AG2-487 GEN
Solar/Wind Harmer
1.491
246936BC-WTG1
Solar/Wind Harmer
0.325
270489AE1-102 GEN1
Solar/Wind Harmer
1.048
24344005CKG1
50/50
13.518
270144AC1-141 ST1_
50/50
4.427
24641605TWIN BRNCH
50/50
0.036
274775LINCOLN ;6U
50/50
18.336
274776LINCOLN ;7U
50/50
18.336
274777LINCOLN ;8U
50/50
18.336
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
14.587
270526AF1-158 GEN
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
27.676
972037AH1-567 GEN1
Adder
0.366
274827FISK ;RP
Adder
15.501
960591AF2-350 GEN
Solar/Wind Harmer
13.932
972228AH1-698 GEN2
Adder
7.394
972227AH1-698 GEN1
Adder
5.206
274800UNIV PARK;3U
Adder
11.637
274801UNIV PARK;4U
Adder
11.637
274687WILL CNTY;4U
Adder
55.408
274687WILL CNTY;4U
Adder
55.408
274675JOLIET 29;7U
Adder
60.77
274675JOLIET 29;7U
Adder
58.6
970031AG2-029 GEN
Solar/Wind Harmer
7.48
274728ELWOOD EC;5P
Adder
32.486
274731ELWOOD EC;2P
Adder
32.486
274733ELWOOD EC;3P
Adder
32.486
274735ELWOOD EC;4P
Adder
32.486
970833AG2-524 GEN
Solar/Wind Harmer
15.154
970833AG2-524 GEN
Solar/Wind Harmer
10.103
274744AC1-111 GEN8
Adder
10.963
274746AC1-111 G10
Adder
10.963
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.577
959141AF2-205 GEN
Solar/Wind Harmer
0.001
970073AG2-061 GEN
Solar/Wind Harmer
4.454
971611AH1-305 GEN
Solar/Wind Harmer
7.947
971675AH1-338 GEN
Solar/Wind Harmer
5.16
971411AH1-196 GEN
Solar/Wind Harmer
19.845
276861AD2-134 GEN
Solar/Wind Harmer
0.236
276863AD2-134 GEN
Solar/Wind Harmer
0.236
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
26.289
274823ROCKFORD ;21
Adder
36.573
970169AG2-114 GEN
Solar/Wind Harmer
13.017
274856ECOGROVE ;U1
Solar/Wind Harmer
0.304
926823AC1-168 GEN
Solar/Wind Harmer
2.21
971549AH1-272 GEN
Solar/Wind Harmer
26.772
971681AH1-341 GEN
Solar/Wind Harmer
20.809
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
24691005MDL-2G C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
8.949
972267AH1-718 GEN
Adder
7.604
276741O09 GEN1
Solar/Wind Harmer
0.449
274877BISHOP HL;1U
Solar/Wind Harmer
0.422
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
13.203
24386405FR-21G C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.924
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
5.236
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
15.924
276668AB2-070 GEN1
Solar/Wind Harmer
0.46
276848AB2-070 GEN3
Solar/Wind Harmer
0.458
276849AB2-070 GEN2
Solar/Wind Harmer
0.46
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
2.196
971609AH1-304 GEN
Solar/Wind Harmer
1.842
965041AG1-368 GEN
Solar/Wind Harmer
11.074
944221AF1-090 GEN
Solar/Wind Harmer
6.279
964611AG1-324 GEN
Solar/Wind Harmer
4.011
247521TR3_G114
Solar/Wind Harmer
0.369
965051AG1-369 GEN
Solar/Wind Harmer
5.084
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.379
270543AE2-219 C
Solar/Wind Harmer
6.219
270356AE2-297 GEN
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
12.334
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.021
270142AC1-141 CT1_
50/50
5.013
24642205MAYFLWER
50/50
0.076
274772LINCOLN ;3U
50/50
18.336
944961AF1-161 GEN
50/50
5.942
962601AG1-109 GEN
50/50
5.942
971347AH1-153 GEN
Solar/Wind Harmer
7.766
270043AE2-236 GEN
Solar/Wind Harmer
9.417
270505AE1-170 C O1
Solar/Wind Harmer
15.137
945111AF1-176 GEN
Solar/Wind Harmer
11.613
274724RIVER EC ;11
Adder
35.793
274752CRETE EC ;2U
Adder
16.621
274753CRETE EC ;3U
Adder
16.621
270063AE2-323 C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
10.141
274807UNIV PK N;3U
Adder
10.119
274811UNIV PK N;7U
Adder
10.053
970707AG2-453 GEN
Solar/Wind Harmer
45.738
972259AH1-714 GEN
Adder
38.13
274803UNIV PARK;6U
Adder
11.65
274826FISK ;BP
Adder
21.872
274887GEN-1.85
Solar/Wind Harmer
0.362
276843GEN-1.7
Solar/Wind Harmer
0.45
276806AD2-047 C O1
Solar/Wind Harmer
7.895
972038AH1-567 GEN2
Adder
0.728
939351AE1-166 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
61.966
274676JOLIET 29;8U
Adder
58.599
274729ELWOOD EC;1P
Adder
32.486
274730ELWOOD EC;6P
Adder
32.486
274734ELWOOD EC;8P
Adder
32.486
274736ELWOOD EC;9P
Adder
32.486
943121AE2-341 GEN
Solar/Wind Harmer
22.986
943591AF1-030 GEN
Solar/Wind Harmer
15.286
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.824
274682WAUKEGAN ;7U
Adder
34.771
276868AE1-113 GEN
Solar/Wind Harmer
2.661
274879MINONK ;1U
Solar/Wind Harmer
0.555
946671AF1-331 GEN
Solar/Wind Harmer
1.412
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.154
959091AF2-200 GEN
Solar/Wind Harmer
26.289
970571AG2-364 GEN
Solar/Wind Harmer
25.984
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
17.161
274767LEE CO EC;8U
Adder
16.958
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
12.865
965021AG1-366 GEN
Solar/Wind Harmer
4.261
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.422
24386205FR-12G C
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
37.086
959611AF2-252 GEN
Solar/Wind Harmer
4.121
965931AG1-462 GEN
Solar/Wind Harmer
31.345
971087AG2-675 GEN
Solar/Wind Harmer
6.556
247642Z2-115 C
Solar/Wind Harmer
0.005
971993AH1-541 GEN
Solar/Wind Harmer
5.405
970289AG2-191 GEN
Solar/Wind Harmer
1.271
957381AF2-032 GEN
Solar/Wind Harmer
2.525
942481AE2-261 GEN
Solar/Wind Harmer
33.208
270004AE1-209 GEN
Solar/Wind Harmer
2.315
970193AG2-126 GEN
Solar/Wind Harmer
16.03
970825AG2-519 GEN
Solar/Wind Harmer
7.905
946031AF1-268 GEN
Solar/Wind Harmer
9.859
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.395
24695305TIMB G C
Solar/Wind Harmer
0.837
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
24728705AND G3
Adder
10.702
24728505AND G1
Adder
5.117
246938BC-WTG3
Solar/Wind Harmer
0.29
270491AE1-102 GEN2
Solar/Wind Harmer
1.048
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.5
NYPJM->LTFIMP_NY
CLTF
3.371
LGEELTFEXP_LGEE->PJM
CLTF
5.638
WECLTFEXP_WEC->PJM
CLTF
7.136
CBM West 1LTFEXP_CBM-W1->PJM
CBM
218.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.394
MECLTFEXP_MEC->PJM
CLTF
26.166
SIGELTFEXP_SIGE->PJM
CLTF
0.556
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.164
AG2-052LTFEXP_AG2-052->PJM
LTF
0.449
AH1-155LTFEXP_AH1-155->PJM
LTF
0.674
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.166
LAGNLTFEXP_LAGN->PJM
CLTF
14.281
TVALTFEXP_TVA->PJM
CLTF
5.469

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-027A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-027A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.15 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5531.21
MW Contribution:
23.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
16.055
270143AC1-141 CT2_
50/50
4.67
24639705ELKHART HY
50/50
0.312
970521AG2-332 GEN
50/50
22.149
24307105BERRINSP G
50/50
0.041
274773LINCOLN ;4U
50/50
12.327
274774LINCOLN ;5U
50/50
12.327
247604X1-042
50/50
0.045
270216AD2-079_GEN
Solar/Wind Harmer
1.171
957891AF2-083 GEN
Solar/Wind Harmer
28.816
945111AF1-176 GEN
Solar/Wind Harmer
34.147
270449AD2-020 GEN
Solar/Wind Harmer
5.342
943021AE2-325 GEN
Solar/Wind Harmer
6.942
24441205WTRV SLR C
Solar/Wind Harmer
0.253
972207SS24-0001
Solar/Wind Harmer
41.303
274723RIVER EC ;12
Adder
33.136
274751CRETE EC ;1U
Adder
9.021
274754CRETE EC ;4U
Adder
9.021
274812UNIV PK N;8U
Adder
9.19
274802UNIV PARK;5U
Adder
10.642
970373AG2-245 GEN
Solar/Wind Harmer
38.254
941551AE2-152 GEN
Solar/Wind Harmer
8.225
274676JOLIET 29;8U
Adder
55.463
274674JOLIET 9 ;6U
Adder
27.783
274732ELWOOD EC;7P
Adder
29.632
274871GR RIDGE ;2U
Solar/Wind Harmer
13.837
274847GR RIDGE ;BU
Solar/Wind Harmer
9.098
274745AC1-111 GEN9
Adder
9.998
270055AF2-134 C O1
Solar/Wind Harmer
5.4
276694AA1-018 GEN2
Solar/Wind Harmer
11.13
276691AA1-018 GEN1
Solar/Wind Harmer
1.33
274682WAUKEGAN ;7U
Adder
31.682
274861TOP CROP ;1U
Solar/Wind Harmer
10.679
274828WAUKEGAN ;BP
Adder
19.445
958381AF2-132 GEN
Solar/Wind Harmer
15.861
962781AG1-127 GEN
Solar/Wind Harmer
16.62
964861AG1-349 GEN
Solar/Wind Harmer
13.715
971917AH1-482 GEN
Solar/Wind Harmer
15.824
274872LEEDK;1U
Solar/Wind Harmer
14.311
939401AE1-172 GEN
Solar/Wind Harmer
24.28
276805AD2-038 GEN
Solar/Wind Harmer
8.927
965011AG1-365 GEN
Solar/Wind Harmer
17.353
276882AE2-255 GEN
Solar/Wind Harmer
5.841
971997AH1-543 GEN
Solar/Wind Harmer
27.222
957471AF2-041 GEN
Solar/Wind Harmer
51.381
959081AF2-199 GEN
Solar/Wind Harmer
17.127
971067AG2-660 GEN
Solar/Wind Harmer
3.983
274822ROCKFORD ;11
Adder
33.489
940581AE2-045 GEN
Solar/Wind Harmer
17.306
971605AH1-302 GEN
Solar/Wind Harmer
14.797
970819AG2-516 GEN
Solar/Wind Harmer
20.348
970569AG2-363 GEN
Solar/Wind Harmer
50.606
965651AG1-433 GEN
Solar/Wind Harmer
9.203
274761LEE CO EC;2U
Adder
15.574
274766LEE CO EC;7U
Adder
15.391
24728605AND G2
Adder
4.418
970091AG2-072 GEN
Adder
71.024
270102X2-052 ST
50/50
3.097
270100X2-052 CT1
50/50
2.862
270101X2-052 CT2
50/50
2.862
24643105BUCHANAN
50/50
0.024
247620Y3-023
50/50
0.926
274770LINCOLN ;1U
50/50
12.327
274771LINCOLN ;2U
50/50
12.327
970349AG2-230 GEN
Solar/Wind Harmer
30.98
965681AG1-436 GEN
Solar/Wind Harmer
24.061
965791AG1-447 GEN
Solar/Wind Harmer
12.31
961051AF2-396 GEN
Solar/Wind Harmer
30.301
961051AF2-396 GEN
Solar/Wind Harmer
14.093
274805UNIV PK N;1U
Adder
9.21
274808UNIV PK N;4U
Adder
9.15
274888KELLY CRK;1U
Solar/Wind Harmer
10.76
276776AD2-060 GEN
Solar/Wind Harmer
0.763
958011AF2-095 GEN
Solar/Wind Harmer
26.257
970941AG2-585 GEN
Solar/Wind Harmer
10.029
276897AD1-100 C
Solar/Wind Harmer
84.246
274674JOLIET 9 ;6U
Adder
27.783
276893AG1-478 C
Solar/Wind Harmer
0.79
270535AF1-215 GEN1
Solar/Wind Harmer
8.1
270536AF1-215 GEN2
Solar/Wind Harmer
8.1
274695ROCKY RD ;2P
Adder
19.663
274693ROCKY RD ;1P
Adder
19.47
274697ROCKY RD ;3P
Adder
5.342
274696ROCKY RD ;4P
Adder
20.127
958481AF2-142 GEN
Solar/Wind Harmer
26.459
274683WAUKEGAN ;8U
Adder
37.095
274683WAUKEGAN ;8U
Adder
31.27
962691AG1-118 GEN
Solar/Wind Harmer
52.572
960751AF2-366 GEN
Solar/Wind Harmer
5.014
958491AF2-143 GEN
Solar/Wind Harmer
26.112
276901AD2-066 C O1
Solar/Wind Harmer
6.094
971341AH1-150 GEN
Solar/Wind Harmer
34.254
971343AH1-151 GEN
Solar/Wind Harmer
34.254
276872AE1-163_GEN1
Solar/Wind Harmer
11.475
276876AE1-163_GEN2
Solar/Wind Harmer
11.475
972235AH1-702 GEN1
Adder
4.29
972236AH1-702 GEN2
Adder
3.73
944541AF1-119 GEN
Solar/Wind Harmer
7.05
960971AF2-388 GEN
Solar/Wind Harmer
18.406
274764LEE CO EC;5U
Adder
15.611
274765LEE CO EC;6U
Adder
15.611
274762LEE CO EC;3U
Adder
15.574
274763LEE CO EC;4U
Adder
15.428
247621Y3-024
Adder
0.306
270349AD2-093_GEN
Solar/Wind Helper
1.516
270471AD2-092_GEN
Solar/Wind Helper
1.516
24344005CKG1
50/50
12.591
270144AC1-141 ST1_
50/50
4.123
24641605TWIN BRNCH
50/50
0.033
24653605MOTTVILLE
50/50
0.007
274775LINCOLN ;6U
50/50
12.327
274776LINCOLN ;7U
50/50
12.327
274777LINCOLN ;8U
50/50
12.327
971771AH1-392 GEN
Solar/Wind Harmer
17.465
270526AF1-158 GEN
Solar/Wind Harmer
8.74
960681AF2-359 GEN
Solar/Wind Harmer
7.273
270071AF1-092 GEN
Solar/Wind Harmer
28.765
944161AF1-084 GEN
Solar/Wind Harmer
4.19
970031AG2-029 GEN
Solar/Wind Harmer
46.329
972037AH1-567 GEN1
Adder
0.334
274827FISK ;RP
Adder
14.162
960591AF2-350 GEN
Solar/Wind Harmer
18.234
274800UNIV PARK;3U
Adder
10.629
274801UNIV PARK;4U
Adder
10.629
972228AH1-698 GEN2
Adder
6.75
972227AH1-698 GEN1
Adder
4.753
274687WILL CNTY;4U
Adder
50.577
274687WILL CNTY;4U
Adder
50.577
274675JOLIET 29;7U
Adder
55.464
274675JOLIET 29;7U
Adder
53.483
24729505KEY G4
Adder
11.726
274728ELWOOD EC;5P
Adder
29.632
274731ELWOOD EC;2P
Adder
29.632
274733ELWOOD EC;3P
Adder
29.632
274735ELWOOD EC;4P
Adder
29.632
276893AG1-478 C
Solar/Wind Harmer
0.991
970833AG2-524 GEN
Solar/Wind Harmer
15.718
970833AG2-524 GEN
Solar/Wind Harmer
7.311
274744AC1-111 GEN8
Adder
9.998
274746AC1-111 G10
Adder
9.998
971549AH1-272 GEN
Solar/Wind Harmer
32.471
970073AG2-061 GEN
Solar/Wind Harmer
4.048
959331AF2-224 GEN
Solar/Wind Harmer
17.353
958391AF2-133 GEN
Solar/Wind Harmer
15.686
971675AH1-338 GEN
Solar/Wind Harmer
31.05
971411AH1-196 GEN
Solar/Wind Harmer
25.876
276861AD2-134 GEN
Solar/Wind Harmer
3.079
276863AD2-134 GEN
Solar/Wind Harmer
3.079
959141AF2-205 GEN
Solar/Wind Harmer
10.37
274863CRW1-WTG
Solar/Wind Harmer
9.562
274864CRW2-WTG
Solar/Wind Harmer
9.562
971171AH1-044 GEN
Solar/Wind Harmer
34.254
276889AE2-281 GEN
Solar/Wind Harmer
3.279
274823ROCKFORD ;21
Adder
33.246
274856ECOGROVE ;U1
Solar/Wind Harmer
5.708
276611AD2-172 GEN
Solar/Wind Harmer
4.33
276612AE2-035 GEN
Solar/Wind Harmer
4.33
926823AC1-168 GEN
Solar/Wind Harmer
7.251
958711AF2-162 GEN
Solar/Wind Harmer
1.704
970169AG2-114 GEN
Solar/Wind Harmer
16.831
972267AH1-718 GEN
Adder
6.894
971681AH1-341 GEN
Solar/Wind Harmer
23.358
270142AC1-141 CT1_
50/50
4.67
24642205MAYFLWER
50/50
0.071
944961AF1-161 GEN
50/50
5.541
962601AG1-109 GEN
50/50
5.541
274772LINCOLN ;3U
50/50
12.327
971347AH1-153 GEN
Solar/Wind Harmer
10.327
270043AE2-236 GEN
Solar/Wind Harmer
10.872
247643Z2-116 C
Solar/Wind Harmer
0.135
270505AE1-170 C O1
Solar/Wind Harmer
28.878
24441505OLIV SLR
Solar/Wind Harmer
0.257
945111AF1-176 GEN
Solar/Wind Harmer
10.822
270063AE2-323 C
Solar/Wind Harmer
4.132
944531AF1-118 GEN
Solar/Wind Harmer
64.825
274724RIVER EC ;11
Adder
32.755
972231SS25-0005
Solar/Wind Harmer
17.516
972181SS23-001
Solar/Wind Harmer
10.947
274752CRETE EC ;2U
Adder
9.021
274753CRETE EC ;3U
Adder
9.021
276164X3-005 C
Solar/Wind Harmer
1.293
274814UNIV PK N;0U
Adder
9.271
274807UNIV PK N;3U
Adder
9.251
274811UNIV PK N;7U
Adder
9.19
970707AG2-453 GEN
Solar/Wind Harmer
51.34
274803UNIV PARK;6U
Adder
10.642
274826FISK ;BP
Adder
19.982
972259AH1-714 GEN
Adder
34.817
274887GEN-1.85
Solar/Wind Harmer
9.715
276772AC2-154 GEN
Solar/Wind Harmer
5.089
276843GEN-1.7
Solar/Wind Harmer
1.045
276806AD2-047 C O1
Solar/Wind Harmer
19.506
972038AH1-567 GEN2
Adder
0.665
939351AE1-166 GEN
Solar/Wind Harmer
10.755
274676JOLIET 29;8U
Adder
53.482
274730ELWOOD EC;6P
Adder
29.632
274734ELWOOD EC;8P
Adder
29.632
274736ELWOOD EC;9P
Adder
29.632
274729ELWOOD EC;1P
Adder
29.632
943121AE2-341 GEN
Solar/Wind Harmer
26.886
943591AF1-030 GEN
Solar/Wind Harmer
17.924
274682WAUKEGAN ;7U
Adder
31.682
274862TOP CROP ;2U
Solar/Wind Harmer
8.916
964401AG1-302 GEN
Solar/Wind Harmer
15.861
965021AG1-366 GEN
Solar/Wind Harmer
4.036
276868AE1-113 GEN
Solar/Wind Harmer
17.522
274879MINONK ;1U
Solar/Wind Harmer
11.682
276799AD1-013 GEN
Solar/Wind Harmer
3.813
946671AF1-331 GEN
Solar/Wind Harmer
0.722
274855GSG-6 ;RU
Solar/Wind Harmer
6.367
274850MENDOTA H;RU
Solar/Wind Harmer
4.427
276602WESTBROOK C
Solar/Wind Harmer
3.665
959091AF2-200 GEN
Solar/Wind Harmer
34.254
970571AG2-364 GEN
Solar/Wind Harmer
33.737
274760LEE CO EC;1U
Adder
15.574
274767LEE CO EC;8U
Adder
15.391
24728705AND G3
Adder
9.241
24728505AND G1
Adder
4.418
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.248
NYPJM->LTFIMP_NY
CLTF
3.18
LGEELTFEXP_LGEE->PJM
CLTF
4.281
WECLTFEXP_WEC->PJM
CLTF
6.487
CBM West 1LTFEXP_CBM-W1->PJM
CBM
202.901
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.384
CBM West 2LTFEXP_CBM-W2->PJM
CBM
115.182
MECLTFEXP_MEC->PJM
CLTF
23.501
SIGELTFEXP_SIGE->PJM
CLTF
0.455
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.741
AG2-052LTFEXP_AG2-052->PJM
LTF
0.406
AH1-155LTFEXP_AH1-155->PJM
LTF
0.609
LAGNLTFEXP_LAGN->PJM
CLTF
12.821
TVALTFEXP_TVA->PJM
CLTF
4.926

Details for 05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.63 %
Rating:6066.0 MVA
Rating Type:B
MVA to Mitigate:6649.99
MW Contribution:
11.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
14.512
270144AC1-141 ST1_
50/50
4.745
24641605TWIN BRNCH
50/50
0.038
274775LINCOLN ;6U
50/50
14.526
274776LINCOLN ;7U
50/50
14.526
274777LINCOLN ;8U
50/50
14.526
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
8.531
971771AH1-392 GEN
Solar/Wind Harmer
20.2
270526AF1-158 GEN
Solar/Wind Harmer
10.168
270071AF1-092 GEN
Solar/Wind Harmer
32.913
944161AF1-084 GEN
Solar/Wind Harmer
4.816
972037AH1-567 GEN1
Adder
0.395
274827FISK ;RP
Adder
16.726
960591AF2-350 GEN
Solar/Wind Harmer
21.552
972228AH1-698 GEN2
Adder
7.981
972227AH1-698 GEN1
Adder
5.619
274800UNIV PARK;3U
Adder
12.558
274801UNIV PARK;4U
Adder
12.558
958391AF2-133 GEN
Solar/Wind Harmer
19.434
274687WILL CNTY;4U
Adder
59.789
274687WILL CNTY;4U
Adder
59.789
274675JOLIET 29;7U
Adder
65.575
274675JOLIET 29;7U
Adder
63.233
959141AF2-205 GEN
Solar/Wind Harmer
12.902
274728ELWOOD EC;5P
Adder
35.063
274731ELWOOD EC;2P
Adder
35.063
274733ELWOOD EC;3P
Adder
35.063
274735ELWOOD EC;4P
Adder
35.063
276893AG1-478 C
Solar/Wind Harmer
1.173
970833AG2-524 GEN
Solar/Wind Harmer
18.607
970833AG2-524 GEN
Solar/Wind Harmer
8.654
274744AC1-111 GEN8
Adder
11.828
274746AC1-111 G10
Adder
11.828
970031AG2-029 GEN
Solar/Wind Harmer
52.483
970073AG2-061 GEN
Solar/Wind Harmer
4.81
946581AF1-322 GEN
Solar/Wind Harmer
21.078
24691005MDL-2G C
Solar/Wind Harmer
7.617
274863CRW1-WTG
Solar/Wind Harmer
11.445
274864CRW2-WTG
Solar/Wind Harmer
11.445
971675AH1-338 GEN
Solar/Wind Harmer
36.83
971411AH1-196 GEN
Solar/Wind Harmer
30.684
276861AD2-134 GEN
Solar/Wind Harmer
3.652
276863AD2-134 GEN
Solar/Wind Harmer
3.652
276889AE2-281 GEN
Solar/Wind Harmer
3.904
971171AH1-044 GEN
Solar/Wind Harmer
40.651
274823ROCKFORD ;21
Adder
39.453
970169AG2-114 GEN
Solar/Wind Harmer
20.21
926823AC1-168 GEN
Solar/Wind Harmer
8.655
274856ECOGROVE ;U1
Solar/Wind Harmer
6.778
276611AD2-172 GEN
Solar/Wind Harmer
5.142
276612AE2-035 GEN
Solar/Wind Harmer
5.142
24729505KEY G4
Adder
12.892
972267AH1-718 GEN
Adder
8.203
971681AH1-341 GEN
Solar/Wind Harmer
11.089
270102X2-052 ST
50/50
3.629
270100X2-052 CT1
50/50
3.353
270101X2-052 CT2
50/50
3.353
24643105BUCHANAN
50/50
0.028
274770LINCOLN ;1U
50/50
14.526
274771LINCOLN ;2U
50/50
14.526
970349AG2-230 GEN
Solar/Wind Harmer
35.834
965681AG1-436 GEN
Solar/Wind Harmer
28.223
965791AG1-447 GEN
Solar/Wind Harmer
14.44
961051AF2-396 GEN
Solar/Wind Harmer
34.84
961051AF2-396 GEN
Solar/Wind Harmer
16.205
270535AF1-215 GEN1
Solar/Wind Harmer
9.874
270536AF1-215 GEN2
Solar/Wind Harmer
9.874
247620Y3-023
Adder
1
274805UNIV PK N;1U
Adder
10.873
274808UNIV PK N;4U
Adder
10.802
274888KELLY CRK;1U
Solar/Wind Harmer
12.718
276776AD2-060 GEN
Solar/Wind Harmer
0.902
958011AF2-095 GEN
Solar/Wind Harmer
31.035
970941AG2-585 GEN
Solar/Wind Harmer
11.854
276897AD1-100 C
Solar/Wind Harmer
99.744
274674JOLIET 9 ;6U
Adder
32.864
276893AG1-478 C
Solar/Wind Harmer
0.935
958481AF2-142 GEN
Solar/Wind Harmer
31.384
945421AF1-207 GEN
Solar/Wind Harmer
29.389
957841AF2-078 GEN
Solar/Wind Harmer
12.652
274695ROCKY RD ;2P
Adder
23.281
274693ROCKY RD ;1P
Adder
23.052
274697ROCKY RD ;3P
Adder
6.324
274696ROCKY RD ;4P
Adder
23.83
274683WAUKEGAN ;8U
Adder
43.924
274683WAUKEGAN ;8U
Adder
37.026
962691AG1-118 GEN
Solar/Wind Harmer
62.281
960751AF2-366 GEN
Solar/Wind Harmer
5.941
958491AF2-143 GEN
Solar/Wind Harmer
31.025
276901AD2-066 C O1
Solar/Wind Harmer
7.247
270180AB1-006 GEN1
Solar/Wind Harmer
14.816
24697605MDL-3G C
Solar/Wind Harmer
7.593
24755605MDL-5G
Solar/Wind Harmer
4.966
24697905MDL-4G C
Solar/Wind Harmer
4.727
270181AB1-006 GEN2
Solar/Wind Harmer
1.473
276872AE1-163_GEN1
Solar/Wind Harmer
13.665
276876AE1-163_GEN2
Solar/Wind Harmer
13.665
971341AH1-150 GEN
Solar/Wind Harmer
40.651
971343AH1-151 GEN
Solar/Wind Harmer
40.651
972235AH1-702 GEN1
Adder
5.092
972236AH1-702 GEN2
Adder
4.428
274764LEE CO EC;5U
Adder
18.556
274765LEE CO EC;6U
Adder
18.556
274762LEE CO EC;3U
Adder
18.513
274763LEE CO EC;4U
Adder
18.338
247621Y3-024
Adder
0.34
24728805RICHG1
Adder
3.514
24728905RICHG2
Adder
3.514
270349AD2-093_GEN
Solar/Wind Helper
1.579
270471AD2-092_GEN
Solar/Wind Helper
1.579
270054AF2-122 C O1
Solar/Wind Helper
1.201
24344105CKG2
50/50
18.546
270143AC1-141 CT2_
50/50
5.373
274773LINCOLN ;4U
50/50
14.526
274774LINCOLN ;5U
50/50
14.526
24639705ELKHART HY
50/50
0.358
970521AG2-332 GEN
50/50
25.426
24307105BERRINSP G
50/50
0.047
270216AD2-079_GEN
Solar/Wind Harmer
1.347
957891AF2-083 GEN
Solar/Wind Harmer
33.169
972207SS24-0001
Solar/Wind Harmer
48.671
945111AF1-176 GEN
Solar/Wind Harmer
39.263
970373AG2-245 GEN
Solar/Wind Harmer
46.177
270449AD2-020 GEN
Solar/Wind Harmer
6.142
943021AE2-325 GEN
Solar/Wind Harmer
7.982
274723RIVER EC ;12
Adder
39.065
270055AF2-134 C O1
Solar/Wind Harmer
6.582
274751CRETE EC ;1U
Adder
10.642
274754CRETE EC ;4U
Adder
10.642
274812UNIV PK N;8U
Adder
10.85
274802UNIV PARK;5U
Adder
12.572
958381AF2-132 GEN
Solar/Wind Harmer
19.541
24441205WTRV SLR C
Solar/Wind Harmer
0.29
964861AG1-349 GEN
Solar/Wind Harmer
16.917
971917AH1-482 GEN
Solar/Wind Harmer
19.518
941551AE2-152 GEN
Solar/Wind Harmer
9.738
274676JOLIET 29;8U
Adder
65.574
274674JOLIET 9 ;6U
Adder
32.864
274732ELWOOD EC;7P
Adder
35.063
274871GR RIDGE ;2U
Solar/Wind Harmer
16.38
274847GR RIDGE ;BU
Solar/Wind Harmer
10.771
940581AE2-045 GEN
Solar/Wind Harmer
21.65
971605AH1-302 GEN
Solar/Wind Harmer
18.512
274745AC1-111 GEN9
Adder
11.828
276694AA1-018 GEN2
Solar/Wind Harmer
13.202
276691AA1-018 GEN1
Solar/Wind Harmer
1.578
274861TOP CROP ;1U
Solar/Wind Harmer
12.668
274682WAUKEGAN ;7U
Adder
37.511
274828WAUKEGAN ;BP
Adder
23.024
939401AE1-172 GEN
Solar/Wind Harmer
28.97
962781AG1-127 GEN
Solar/Wind Harmer
19.693
276805AD2-038 GEN
Solar/Wind Harmer
10.606
274872LEEDK;1U
Solar/Wind Harmer
16.96
24791305MDL-5G
Solar/Wind Harmer
4.966
276882AE2-255 GEN
Solar/Wind Harmer
6.943
971997AH1-543 GEN
Solar/Wind Harmer
32.39
957471AF2-041 GEN
Solar/Wind Harmer
60.976
959081AF2-199 GEN
Solar/Wind Harmer
20.325
971067AG2-660 GEN
Solar/Wind Harmer
4.727
274822ROCKFORD ;11
Adder
39.741
970819AG2-516 GEN
Solar/Wind Harmer
24.158
970569AG2-363 GEN
Solar/Wind Harmer
60.367
274761LEE CO EC;2U
Adder
18.513
274766LEE CO EC;7U
Adder
18.295
970091AG2-072 GEN
Adder
144.176
24728605AND G2
Adder
5.21
270142AC1-141 CT1_
50/50
5.373
24642205MAYFLWER
50/50
0.082
274772LINCOLN ;3U
50/50
14.526
944961AF1-161 GEN
50/50
6.371
962601AG1-109 GEN
50/50
6.371
971347AH1-153 GEN
Solar/Wind Harmer
11.945
24441505OLIV SLR
Solar/Wind Harmer
0.3
247643Z2-116 C
Solar/Wind Harmer
0.155
270505AE1-170 C O1
Solar/Wind Harmer
33.23
270043AE2-236 GEN
Solar/Wind Harmer
12.16
945111AF1-176 GEN
Solar/Wind Harmer
12.444
274724RIVER EC ;11
Adder
38.613
972231SS25-0005
Solar/Wind Harmer
20.663
972181SS23-001
Solar/Wind Harmer
12.914
274752CRETE EC ;2U
Adder
10.642
274753CRETE EC ;3U
Adder
10.642
276164X3-005 C
Solar/Wind Harmer
1.526
274814UNIV PK N;0U
Adder
10.945
274807UNIV PK N;3U
Adder
10.921
274811UNIV PK N;7U
Adder
10.85
970707AG2-453 GEN
Solar/Wind Harmer
60.612
274803UNIV PARK;6U
Adder
12.572
972259AH1-714 GEN
Adder
41.143
274826FISK ;BP
Adder
23.601
274887GEN-1.85
Solar/Wind Harmer
11.482
276772AC2-154 GEN
Solar/Wind Harmer
6.015
276843GEN-1.7
Solar/Wind Harmer
1.235
276806AD2-047 C O1
Solar/Wind Harmer
23.056
964401AG1-302 GEN
Solar/Wind Harmer
19.541
972038AH1-567 GEN2
Adder
0.786
939351AE1-166 GEN
Solar/Wind Harmer
12.734
274676JOLIET 29;8U
Adder
63.232
274729ELWOOD EC;1P
Adder
35.063
274730ELWOOD EC;6P
Adder
35.063
274734ELWOOD EC;8P
Adder
35.063
274736ELWOOD EC;9P
Adder
35.063
270063AE2-323 C
Solar/Wind Harmer
4.688
943121AE2-341 GEN
Solar/Wind Harmer
31.796
943591AF1-030 GEN
Solar/Wind Harmer
21.197
274862TOP CROP ;2U
Solar/Wind Harmer
10.577
274682WAUKEGAN ;7U
Adder
37.511
24690905MDL-1G C
Solar/Wind Harmer
16.538
970781AG2-491 GEN
Solar/Wind Harmer
20.6
276868AE1-113 GEN
Solar/Wind Harmer
20.83
274879MINONK ;1U
Solar/Wind Harmer
13.887
276799AD1-013 GEN
Solar/Wind Harmer
4.522
946671AF1-331 GEN
Solar/Wind Harmer
0.857
274855GSG-6 ;RU
Solar/Wind Harmer
7.552
274850MENDOTA H;RU
Solar/Wind Harmer
5.251
276602WESTBROOK C
Solar/Wind Harmer
4.348
944531AF1-118 GEN
Solar/Wind Harmer
71.22
959091AF2-200 GEN
Solar/Wind Harmer
40.651
970571AG2-364 GEN
Solar/Wind Harmer
40.244
274760LEE CO EC;1U
Adder
18.513
274767LEE CO EC;8U
Adder
18.295
24728705AND G3
Adder
10.897
24728505AND G1
Adder
5.21
NYPJM->LTFIMP_NY
CLTF
3.564
LGEELTFEXP_LGEE->PJM
CLTF
4.159
WECLTFEXP_WEC->PJM
CLTF
7.696
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.39
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
233.845
CBM West 2LTFEXP_CBM-W2->PJM
CBM
138.616
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.749
MECLTFEXP_MEC->PJM
CLTF
28.15
SIGELTFEXP_SIGE->PJM
CLTF
0.543
AG2-052LTFEXP_AG2-052->PJM
LTF
0.487
AH1-155LTFEXP_AH1-155->PJM
LTF
0.73
LAGNLTFEXP_LAGN->PJM
CLTF
14.71
TVALTFEXP_TVA->PJM
CLTF
5.409

Details for 05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.98 %
Rating:6066.0 MVA
Rating Type:B
MVA to Mitigate:6125.38
MW Contribution:
27.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344005CKG1
50/50
13.488
270144AC1-141 ST1_
50/50
4.417
24641605TWIN BRNCH
50/50
0.036
274775LINCOLN ;6U
50/50
13.44
274776LINCOLN ;7U
50/50
13.44
274777LINCOLN ;8U
50/50
13.44
24653605MOTTVILLE
50/50
0.008
960681AF2-359 GEN
Solar/Wind Harmer
7.886
971771AH1-392 GEN
Solar/Wind Harmer
18.775
270526AF1-158 GEN
Solar/Wind Harmer
9.429
270071AF1-092 GEN
Solar/Wind Harmer
30.976
944161AF1-084 GEN
Solar/Wind Harmer
4.48
972037AH1-567 GEN1
Adder
0.365
274827FISK ;RP
Adder
15.465
960591AF2-350 GEN
Solar/Wind Harmer
19.923
972228AH1-698 GEN2
Adder
7.377
972227AH1-698 GEN1
Adder
5.194
274800UNIV PARK;3U
Adder
11.611
274801UNIV PARK;4U
Adder
11.611
274687WILL CNTY;4U
Adder
55.279
274687WILL CNTY;4U
Adder
55.279
274675JOLIET 29;7U
Adder
60.629
274675JOLIET 29;7U
Adder
58.463
970031AG2-029 GEN
Solar/Wind Harmer
49.365
274728ELWOOD EC;5P
Adder
32.411
274731ELWOOD EC;2P
Adder
32.41
274733ELWOOD EC;3P
Adder
32.41
274735ELWOOD EC;4P
Adder
32.41
276893AG1-478 C
Solar/Wind Harmer
1.084
970833AG2-524 GEN
Solar/Wind Harmer
17.199
970833AG2-524 GEN
Solar/Wind Harmer
7.999
274744AC1-111 GEN8
Adder
10.938
274746AC1-111 G10
Adder
10.938
958391AF2-133 GEN
Solar/Wind Harmer
17.547
24729505KEY G4
Adder
12.548
959141AF2-205 GEN
Solar/Wind Harmer
11.629
970073AG2-061 GEN
Solar/Wind Harmer
4.443
971675AH1-338 GEN
Solar/Wind Harmer
34.055
971411AH1-196 GEN
Solar/Wind Harmer
28.375
276861AD2-134 GEN
Solar/Wind Harmer
3.377
276863AD2-134 GEN
Solar/Wind Harmer
3.377
274863CRW1-WTG
Solar/Wind Harmer
10.548
274864CRW2-WTG
Solar/Wind Harmer
10.548
971171AH1-044 GEN
Solar/Wind Harmer
37.588
276889AE2-281 GEN
Solar/Wind Harmer
3.605
274823ROCKFORD ;21
Adder
36.484
970169AG2-114 GEN
Solar/Wind Harmer
18.611
274856ECOGROVE ;U1
Solar/Wind Harmer
6.268
276611AD2-172 GEN
Solar/Wind Harmer
4.755
276612AE2-035 GEN
Solar/Wind Harmer
4.755
926823AC1-168 GEN
Solar/Wind Harmer
7.988
971549AH1-272 GEN
Solar/Wind Harmer
34.293
971681AH1-341 GEN
Solar/Wind Harmer
27.72
972267AH1-718 GEN
Adder
7.584
24344105CKG2
50/50
17.244
270143AC1-141 CT2_
50/50
5.002
24639705ELKHART HY
50/50
0.334
274773LINCOLN ;4U
50/50
13.44
274774LINCOLN ;5U
50/50
13.44
970521AG2-332 GEN
50/50
23.718
24307105BERRINSP G
50/50
0.044
270216AD2-079_GEN
Solar/Wind Harmer
1.255
957891AF2-083 GEN
Solar/Wind Harmer
30.868
945111AF1-176 GEN
Solar/Wind Harmer
36.559
972207SS24-0001
Solar/Wind Harmer
45.031
270449AD2-020 GEN
Solar/Wind Harmer
5.715
943021AE2-325 GEN
Solar/Wind Harmer
7.427
274723RIVER EC ;12
Adder
36.127
274751CRETE EC ;1U
Adder
9.837
274754CRETE EC ;4U
Adder
9.837
970373AG2-245 GEN
Solar/Wind Harmer
42.152
274812UNIV PK N;8U
Adder
10.03
24441205WTRV SLR C
Solar/Wind Harmer
0.27
274802UNIV PARK;5U
Adder
11.623
941551AE2-152 GEN
Solar/Wind Harmer
8.999
270055AF2-134 C O1
Solar/Wind Harmer
5.984
274676JOLIET 29;8U
Adder
60.628
274674JOLIET 9 ;6U
Adder
30.381
274732ELWOOD EC;7P
Adder
32.411
274871GR RIDGE ;2U
Solar/Wind Harmer
15.14
270102X2-052 ST
50/50
3.355
270100X2-052 CT1
50/50
3.1
270101X2-052 CT2
50/50
3.1
24643105BUCHANAN
50/50
0.026
274770LINCOLN ;1U
50/50
13.44
274771LINCOLN ;2U
50/50
13.44
247620Y3-023
50/50
0.991
970349AG2-230 GEN
Solar/Wind Harmer
33.323
965681AG1-436 GEN
Solar/Wind Harmer
26.089
965791AG1-447 GEN
Solar/Wind Harmer
13.348
961051AF2-396 GEN
Solar/Wind Harmer
32.427
961051AF2-396 GEN
Solar/Wind Harmer
15.082
274805UNIV PK N;1U
Adder
10.052
274808UNIV PK N;4U
Adder
9.986
274888KELLY CRK;1U
Solar/Wind Harmer
11.757
276776AD2-060 GEN
Solar/Wind Harmer
0.834
958011AF2-095 GEN
Solar/Wind Harmer
28.69
970941AG2-585 GEN
Solar/Wind Harmer
10.958
276897AD1-100 C
Solar/Wind Harmer
92.171
270535AF1-215 GEN1
Solar/Wind Harmer
8.976
270536AF1-215 GEN2
Solar/Wind Harmer
8.976
274674JOLIET 9 ;6U
Adder
30.381
276893AG1-478 C
Solar/Wind Harmer
0.864
274695ROCKY RD ;2P
Adder
21.528
274693ROCKY RD ;1P
Adder
21.316
274697ROCKY RD ;3P
Adder
5.848
274696ROCKY RD ;4P
Adder
22.036
958481AF2-142 GEN
Solar/Wind Harmer
28.999
274683WAUKEGAN ;8U
Adder
40.618
274683WAUKEGAN ;8U
Adder
34.239
962691AG1-118 GEN
Solar/Wind Harmer
57.593
274847GR RIDGE ;BU
Solar/Wind Harmer
9.956
274745AC1-111 GEN9
Adder
10.938
958381AF2-132 GEN
Solar/Wind Harmer
17.685
964861AG1-349 GEN
Solar/Wind Harmer
15.303
971917AH1-482 GEN
Solar/Wind Harmer
17.655
276694AA1-018 GEN2
Solar/Wind Harmer
12.198
276691AA1-018 GEN1
Solar/Wind Harmer
1.458
274861TOP CROP ;1U
Solar/Wind Harmer
11.705
274682WAUKEGAN ;7U
Adder
34.688
274828WAUKEGAN ;BP
Adder
21.291
939401AE1-172 GEN
Solar/Wind Harmer
26.719
962781AG1-127 GEN
Solar/Wind Harmer
18.21
274872LEEDK;1U
Solar/Wind Harmer
15.683
276805AD2-038 GEN
Solar/Wind Harmer
9.797
940581AE2-045 GEN
Solar/Wind Harmer
19.469
971605AH1-302 GEN
Solar/Wind Harmer
16.647
276882AE2-255 GEN
Solar/Wind Harmer
6.414
971997AH1-543 GEN
Solar/Wind Harmer
29.912
957471AF2-041 GEN
Solar/Wind Harmer
56.382
959081AF2-199 GEN
Solar/Wind Harmer
18.794
971067AG2-660 GEN
Solar/Wind Harmer
4.371
274822ROCKFORD ;11
Adder
36.75
970819AG2-516 GEN
Solar/Wind Harmer
22.34
970569AG2-363 GEN
Solar/Wind Harmer
55.727
274858EASY ROAD;U2
Solar/Wind Harmer
8.815
274761LEE CO EC;2U
Adder
17.118
274766LEE CO EC;7U
Adder
16.916
970091AG2-072 GEN
Adder
105.385
24728605AND G2
Adder
5.1
270142AC1-141 CT1_
50/50
5.002
24642205MAYFLWER
50/50
0.076
274772LINCOLN ;3U
50/50
13.44
944961AF1-161 GEN
50/50
5.928
962601AG1-109 GEN
50/50
5.928
971347AH1-153 GEN
Solar/Wind Harmer
11.108
270043AE2-236 GEN
Solar/Wind Harmer
11.544
247643Z2-116 C
Solar/Wind Harmer
0.145
24441505OLIV SLR
Solar/Wind Harmer
0.278
270505AE1-170 C O1
Solar/Wind Harmer
30.925
945111AF1-176 GEN
Solar/Wind Harmer
11.586
274724RIVER EC ;11
Adder
35.711
972231SS25-0005
Solar/Wind Harmer
19.1
972181SS23-001
Solar/Wind Harmer
11.937
274752CRETE EC ;2U
Adder
9.837
274753CRETE EC ;3U
Adder
9.837
276164X3-005 C
Solar/Wind Harmer
1.411
270063AE2-323 C
Solar/Wind Harmer
4.403
274814UNIV PK N;0U
Adder
10.117
274807UNIV PK N;3U
Adder
10.095
274811UNIV PK N;7U
Adder
10.03
970707AG2-453 GEN
Solar/Wind Harmer
56.064
972259AH1-714 GEN
Adder
38.042
274803UNIV PARK;6U
Adder
11.623
274826FISK ;BP
Adder
21.822
274887GEN-1.85
Solar/Wind Harmer
10.615
276772AC2-154 GEN
Solar/Wind Harmer
5.56
276843GEN-1.7
Solar/Wind Harmer
1.142
276806AD2-047 C O1
Solar/Wind Harmer
21.313
972038AH1-567 GEN2
Adder
0.727
939351AE1-166 GEN
Solar/Wind Harmer
11.767
944531AF1-118 GEN
Solar/Wind Harmer
69.202
274676JOLIET 29;8U
Adder
58.463
274729ELWOOD EC;1P
Adder
32.41
274730ELWOOD EC;6P
Adder
32.411
274734ELWOOD EC;8P
Adder
32.411
274736ELWOOD EC;9P
Adder
32.411
943121AE2-341 GEN
Solar/Wind Harmer
29.406
943591AF1-030 GEN
Solar/Wind Harmer
19.604
964401AG1-302 GEN
Solar/Wind Harmer
17.685
274862TOP CROP ;2U
Solar/Wind Harmer
9.773
274682WAUKEGAN ;7U
Adder
34.688
276868AE1-113 GEN
Solar/Wind Harmer
19.24
274879MINONK ;1U
Solar/Wind Harmer
12.827
276799AD1-013 GEN
Solar/Wind Harmer
4.182
946671AF1-331 GEN
Solar/Wind Harmer
0.792
274855GSG-6 ;RU
Solar/Wind Harmer
6.983
274850MENDOTA H;RU
Solar/Wind Harmer
4.855
276602WESTBROOK C
Solar/Wind Harmer
4.02
959091AF2-200 GEN
Solar/Wind Harmer
37.588
970571AG2-364 GEN
Solar/Wind Harmer
37.151
960751AF2-366 GEN
Solar/Wind Harmer
5.494
958491AF2-143 GEN
Solar/Wind Harmer
28.659
276901AD2-066 C O1
Solar/Wind Harmer
6.693
971341AH1-150 GEN
Solar/Wind Harmer
37.588
971343AH1-151 GEN
Solar/Wind Harmer
37.588
276872AE1-163_GEN1
Solar/Wind Harmer
12.619
276876AE1-163_GEN2
Solar/Wind Harmer
12.619
945421AF1-207 GEN
Solar/Wind Harmer
26.261
957841AF2-078 GEN
Solar/Wind Harmer
11.305
972235AH1-702 GEN1
Adder
4.708
972236AH1-702 GEN2
Adder
4.094
938861AE1-114 GEN
Solar/Wind Harmer
15.142
274764LEE CO EC;5U
Adder
17.158
274765LEE CO EC;6U
Adder
17.158
274762LEE CO EC;3U
Adder
17.118
274763LEE CO EC;4U
Adder
16.956
247621Y3-024
Adder
0.337
24728805RICHG1
Adder
3.728
24728905RICHG2
Adder
3.728
270349AD2-093_GEN
Solar/Wind Helper
1.56
270471AD2-092_GEN
Solar/Wind Helper
1.56
274857EASY ROAD;U1
Solar/Wind Harmer
8.815
274760LEE CO EC;1U
Adder
17.118
274767LEE CO EC;8U
Adder
16.916
24728705AND G3
Adder
10.665
24728505AND G1
Adder
5.1
24690905MDL-1G C
Solar/Wind Harmer
9.079
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.518
NYPJM->LTFIMP_NY
CLTF
3.401
LGEELTFEXP_LGEE->PJM
CLTF
5.607
WECLTFEXP_WEC->PJM
CLTF
7.118
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.218
MECLTFEXP_MEC->PJM
CLTF
26.088
SIGELTFEXP_SIGE->PJM
CLTF
0.553
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.195
AG2-052LTFEXP_AG2-052->PJM
LTF
0.448
AH1-155LTFEXP_AH1-155->PJM
LTF
0.672
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.543
LAGNLTFEXP_LAGN->PJM
CLTF
14.187
TVALTFEXP_TVA->PJM
CLTF
5.423

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.63 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2609.67
MW Contribution:
5.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
5.175
24726605LAWG1S
50/50
5.173
24726705LAWG2A
50/50
3.469
24726505LAWG1B
50/50
3.445
24726805LAWG2B
50/50
3.43
24729505KEY G4
50/50
6.226
270356AE2-297 GEN
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.089
964611AG1-324 GEN
Solar/Wind Harmer
2.474
970289AG2-191 GEN
Solar/Wind Harmer
1.136
247536S-71 GEN
Solar/Wind Harmer
0.216
270543AE2-219 C
Solar/Wind Harmer
3.467
971029AG2-637 GEN
Solar/Wind Harmer
6.645
270071AF1-092 GEN
Solar/Wind Harmer
8.015
963791AG1-232 GEN
Solar/Wind Harmer
5.573
963841AG1-237 GEN
Solar/Wind Harmer
1.664
24386405FR-21G C
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.16
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.138
276848AB2-070 GEN3
Solar/Wind Harmer
0.137
276849AB2-070 GEN2
Solar/Wind Harmer
0.138
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.675
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
3.478
274775LINCOLN ;6U
Adder
4.193
274776LINCOLN ;7U
Adder
4.193
274777LINCOLN ;8U
Adder
4.193
960681AF2-359 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
1.832
972227AH1-698 GEN1
Adder
1.29
960591AF2-350 GEN
Solar/Wind Harmer
3.45
944221AF1-090 GEN
Solar/Wind Harmer
2.022
972037AH1-567 GEN1
Adder
0.09
274800UNIV PARK;3U
Adder
2.879
274801UNIV PARK;4U
Adder
2.879
274827FISK ;RP
Adder
3.829
970833AG2-524 GEN
Solar/Wind Harmer
3.784
970833AG2-524 GEN
Solar/Wind Harmer
2.522
274728ELWOOD EC;5P
Adder
8.1
274731ELWOOD EC;2P
Adder
8.1
274733ELWOOD EC;3P
Adder
8.1
274735ELWOOD EC;4P
Adder
8.1
274687WILL CNTY;4U
Adder
13.754
274687WILL CNTY;4U
Adder
13.754
274675JOLIET 29;7U
Adder
15.095
274675JOLIET 29;7U
Adder
14.556
274744AC1-111 GEN8
Adder
2.736
274746AC1-111 G10
Adder
2.736
970073AG2-061 GEN
Solar/Wind Harmer
1.138
270526AF1-158 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.579
971771AH1-392 GEN
Solar/Wind Harmer
3.397
970031AG2-029 GEN
Solar/Wind Harmer
1.836
276861AD2-134 GEN
Solar/Wind Harmer
0.06
276863AD2-134 GEN
Solar/Wind Harmer
0.06
971675AH1-338 GEN
Solar/Wind Harmer
1.313
961161AF2-407 GEN
50/50
36.206
24728705AND G3
50/50
7.209
24728505AND G1
50/50
3.447
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.847
970825AG2-519 GEN
Solar/Wind Harmer
5.553
946031AF1-268 GEN
Solar/Wind Harmer
6.921
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.138
944531AF1-118 GEN
Solar/Wind Harmer
27.23
970289AG2-191 GEN
Solar/Wind Harmer
0.658
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
6.211
270043AE2-236 GEN
Solar/Wind Harmer
2.461
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.696
964401AG1-302 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.619
971347AH1-153 GEN
Solar/Wind Harmer
1.751
965091AG1-374 GEN
Solar/Wind Harmer
10.482
959611AF2-252 GEN
Solar/Wind Harmer
1.165
274772LINCOLN ;3U
Adder
4.193
939351AE1-166 GEN
Solar/Wind Harmer
0
957381AF2-032 GEN
Solar/Wind Harmer
0.783
942481AE2-261 GEN
Solar/Wind Harmer
10.33
274724RIVER EC ;11
Adder
8.762
274752CRETE EC ;2U
Adder
4.076
274753CRETE EC ;3U
Adder
4.076
274887GEN-1.85
Solar/Wind Harmer
0.09
276843GEN-1.7
Solar/Wind Harmer
0.112
276806AD2-047 C O1
Solar/Wind Harmer
1.955
274814UNIV PK N;0U
Adder
2.497
274807UNIV PK N;3U
Adder
2.491
274811UNIV PK N;7U
Adder
2.475
972259AH1-714 GEN
Adder
9.423
274803UNIV PARK;6U
Adder
2.879
972038AH1-567 GEN2
Adder
0.18
274826FISK ;BP
Adder
5.402
970707AG2-453 GEN
Solar/Wind Harmer
11.245
274729ELWOOD EC;1P
Adder
8.1
274730ELWOOD EC;6P
Adder
8.1
274734ELWOOD EC;8P
Adder
8.1
274736ELWOOD EC;9P
Adder
8.1
274676JOLIET 29;8U
Adder
14.556
274862TOP CROP ;2U
Solar/Wind Harmer
0.462
943121AE2-341 GEN
Solar/Wind Harmer
5.725
943591AF1-030 GEN
Solar/Wind Harmer
3.807
276868AE1-113 GEN
Solar/Wind Harmer
0.682
274879MINONK ;1U
Solar/Wind Harmer
0.142
970571AG2-364 GEN
Solar/Wind Harmer
6.786
274682WAUKEGAN ;7U
Adder
8.741
946671AF1-331 GEN
Solar/Wind Harmer
0.359
274855GSG-6 ;RU
Solar/Wind Harmer
0.123
274850MENDOTA H;RU
Solar/Wind Harmer
0.039
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.112
959091AF2-200 GEN
Solar/Wind Harmer
6.717
270063AE2-323 C
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
4.439
274767LEE CO EC;8U
Adder
4.387
270505AE1-170 C O1
Solar/Wind Harmer
3.482
945111AF1-176 GEN
Solar/Wind Harmer
2.686
965931AG1-462 GEN
Solar/Wind Harmer
8.333
971087AG2-675 GEN
Solar/Wind Harmer
1.743
965021AG1-366 GEN
Solar/Wind Harmer
1.012
252524AE2-267 GEN
Solar/Wind Helper
1.058
960071AF2-298 GEN
Solar/Wind Helper
0.562
253394AE2-221_GEN
Solar/Wind Helper
1.605
252507AC2-088 GEN
Solar/Wind Helper
1.361
276820AF1-078_GEN
Solar/Wind Helper
0.471
270367AC2-061_GEN
Solar/Wind Helper
1.959
270186AC1-089 GEN
Solar/Wind Helper
0.816
270518AE2-148 GEN
Solar/Wind Helper
8.492
253325AC1-069 GEN
Solar/Wind Helper
0.605
25194708EBND2
50/50
6.282
24729405KEY G3
50/50
0.34
24729305KEY G2
50/50
0.334
24729205KEY G1
50/50
0.332
247621Y3-024
50/50
0.2
926881AC1-175 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.465
960971AF2-388 GEN
Solar/Wind Harmer
4.082
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
3.665
270599AE1-208 GEN
Solar/Wind Harmer
6.109
270383AD1-128 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
3.047
964611AG1-324 GEN
Solar/Wind Harmer
0.476
270201AC2-176 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.777
970291AG2-192 GEN
Solar/Wind Harmer
0.359
942221AE2-234 GEN
Solar/Wind Harmer
2.113
970883AG2-550 GEN
Solar/Wind Harmer
4.953
970885AG2-551 GEN
Solar/Wind Harmer
1.651
945391AF1-204 GEN
Solar/Wind Harmer
4.4
970241AG2-163 GEN
Solar/Wind Harmer
2.28
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.427
971587AH1-292 GEN
Solar/Wind Harmer
2.74
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
24728805RICHG1
Adder
1.91
24728905RICHG2
Adder
1.91
970349AG2-230 GEN
Solar/Wind Harmer
5.254
942111AE2-223 GEN
Solar/Wind Harmer
1.137
960611AF2-352 GEN
Solar/Wind Harmer
1.165
276615X2-022 GEN
Solar/Wind Harmer
0.036
276838X2-022 GEN2
Solar/Wind Harmer
0.196
274770LINCOLN ;1U
Adder
4.193
274771LINCOLN ;2U
Adder
4.193
276897AD1-100 C
Solar/Wind Harmer
8.649
965681AG1-436 GEN
Solar/Wind Harmer
4.321
965791AG1-447 GEN
Solar/Wind Harmer
3.169
276916AD2-100_GEN
Solar/Wind Harmer
7.252
276911AD2-131_GEN
Solar/Wind Harmer
0.478
274888KELLY CRK;1U
Solar/Wind Harmer
0.201
276776AD2-060 GEN
Solar/Wind Harmer
0.368
958011AF2-095 GEN
Solar/Wind Harmer
4.968
970941AG2-585 GEN
Solar/Wind Harmer
1.898
274805UNIV PK N;1U
Adder
2.48
274808UNIV PK N;4U
Adder
2.464
276893AG1-478 C
Solar/Wind Harmer
0.229
274674JOLIET 9 ;6U
Adder
7.581
276901AD2-066 C O1
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
5.132
958491AF2-143 GEN
Solar/Wind Harmer
5.119
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.549
274695ROCKY RD ;2P
Adder
5.421
274693ROCKY RD ;1P
Adder
5.368
274697ROCKY RD ;3P
Adder
1.473
274683WAUKEGAN ;8U
Adder
10.242
274683WAUKEGAN ;8U
Adder
8.634
962691AG1-118 GEN
Solar/Wind Harmer
10.16
276645AC1-214 GEN1
Solar/Wind Harmer
0.133
971341AH1-150 GEN
Solar/Wind Harmer
6.717
24726405LAWG1A
50/50
3.345
961171AF2-408 GEN
50/50
9.629
24728605AND G2
50/50
3.447
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
7.823
970773AG2-487 GEN
Solar/Wind Harmer
1.792
270005AE1-210 C O1
Solar/Wind Harmer
1.847
945371AF1-202 GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.617
958861AF2-177 GEN
Solar/Wind Harmer
3.107
965651AG1-433 GEN
Solar/Wind Harmer
2.041
276903AD2-071 C
Solar/Wind Harmer
7.229
270594AE1-207 GEN
Solar/Wind Harmer
7.11
270032AE2-172
Solar/Wind Harmer
4.232
270024AE2-089 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
9.25
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.534
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.671
958381AF2-132 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.43
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.9
276621W2-048 GEN
Solar/Wind Harmer
0.174
939401AE1-172 GEN
Solar/Wind Harmer
2.598
274773LINCOLN ;4U
Adder
4.193
274774LINCOLN ;5U
Adder
4.193
941551AE2-152 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.691
274723RIVER EC ;12
Adder
8.866
274751CRETE EC ;1U
Adder
4.076
274754CRETE EC ;4U
Adder
4.076
274812UNIV PK N;8U
Adder
2.475
274802UNIV PARK;5U
Adder
2.879
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.1
274674JOLIET 9 ;6U
Adder
7.581
274676JOLIET 29;8U
Adder
15.095
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.556
274861TOP CROP ;1U
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.792
274745AC1-111 GEN9
Adder
2.736
276805AD2-038 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.398
970569AG2-363 GEN
Solar/Wind Harmer
10.179
274682WAUKEGAN ;7U
Adder
8.741
274828WAUKEGAN ;BP
Adder
5.369
962781AG1-127 GEN
Solar/Wind Harmer
3.219
274872LEEDK;1U
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.133
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.074
957471AF2-041 GEN
Solar/Wind Harmer
10.076
959081AF2-199 GEN
Solar/Wind Harmer
3.359
971067AG2-660 GEN
Solar/Wind Harmer
1.12
970091AG2-072 GEN
Adder
36.89
274822ROCKFORD ;11
Adder
9.422
970819AG2-516 GEN
Solar/Wind Harmer
4.01
276708O09 GEN2
Solar/Wind Harmer
0.118
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.439
274766LEE CO EC;7U
Adder
4.387
957891AF2-083 GEN
Solar/Wind Harmer
5.533
945111AF1-176 GEN
Solar/Wind Harmer
5.913
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.71
965011AG1-365 GEN
Solar/Wind Harmer
3.036
252510AF1-249 C
Solar/Wind Helper
0.649
253398AE2-221_GEN2
Solar/Wind Helper
1.605
253333AC1-068 GEN
Solar/Wind Helper
0.605
971343AH1-151 GEN
Solar/Wind Harmer
6.717
972235AH1-702 GEN1
Adder
1.209
972236AH1-702 GEN2
Adder
1.051
247620Y3-023
Adder
0.221
938861AE1-114 GEN
Solar/Wind Harmer
1.89
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.537
274764LEE CO EC;5U
Adder
4.449
274765LEE CO EC;6U
Adder
4.449
274762LEE CO EC;3U
Adder
4.439
274763LEE CO EC;4U
Adder
4.397
961051AF2-396 GEN
Solar/Wind Harmer
6.579
961051AF2-396 GEN
Solar/Wind Harmer
4.386
25183208HLCRTG
Solar/Wind Helper
2.475
252509AD1-136 GEN
Solar/Wind Helper
0.194
253378AE2-206_GEN
Solar/Wind Helper
1.008
962581AG1-107 GEN
Solar/Wind Helper
1.008
961491AF2-440 GEN
Solar/Wind Helper
0.041
253349AC2-067 GEN
Solar/Wind Helper
0.267
253400AC2-068 GEN
Solar/Wind Helper
0.107
253415AE1-040 GEN
Solar/Wind Helper
0.551
253383AE2-342_GEN
Solar/Wind Helper
0.473
274877BISHOP HL;1U
Solar/Wind Harmer
0.112
971411AH1-196 GEN
Solar/Wind Harmer
5.046
971171AH1-044 GEN
Solar/Wind Harmer
6.717
274823ROCKFORD ;21
Adder
9.354
274856ECOGROVE ;U1
Solar/Wind Harmer
0.078
971681AH1-341 GEN
Solar/Wind Harmer
5.372
276741O09 GEN1
Solar/Wind Harmer
0.118
972267AH1-718 GEN
Adder
1.98
946321AF1-296 GEN
Solar/Wind Harmer
1.835
959331AF2-224 GEN
Solar/Wind Harmer
2.126
241972AD1-140 GEN
Solar/Wind Helper
3.462
253406AD2-031_GEN
Solar/Wind Helper
0.908
270340AC2-060 GEN
Solar/Wind Helper
1.186
253338AC1-165 GEN
Solar/Wind Helper
0.584
253343AC1-166 GEN
Solar/Wind Helper
0.584
241973AD2-163_GEN1
Solar/Wind Helper
1.034
241974AD2-163_GEN2
Solar/Wind Helper
1.034
945631AF1-228 GEN
Solar/Wind Helper
1.084
241955AC1-078 GEN
Solar/Wind Helper
0.981
NYPJM->LTFIMP_NY
CLTF
0.654
LGEELTFEXP_LGEE->PJM
CLTF
1.45
WECLTFEXP_WEC->PJM
CLTF
1.827
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.493
MECLTFEXP_MEC->PJM
CLTF
7.337
SIGELTFEXP_SIGE->PJM
CLTF
0.239
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.525
LAGNLTFEXP_LAGN->PJM
CLTF
4.89
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.583
TVALTFEXP_TVA->PJM
CLTF
1.97

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.94 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2185.8
MW Contribution:
5.61
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.127
24802806KYGER 2HP
50/50
4.111
24802906KYGER 2LP
50/50
2.413
25183008BIOENL
50/50
0.03
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
7.768
25194508D.CRK3
Adder
1.452
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.516
972045AH1-571 GEN
Solar/Wind Harmer
1.214
270269AC2-059
Solar/Wind Harmer
0
971125AH1-004 GEN
Solar/Wind Harmer
2.245
970107AG2-081 GEN
Solar/Wind Harmer
1.684
253370AE2-315 SEC1
Adder
1.601
24728805RICHG1
Adder
2.955
24728905RICHG2
Adder
2.955
25322209TAIT E
Adder
7.522
25322209TAIT E
Adder
7.353
25326109MON D
Adder
0.984
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.111
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.905
970885AG2-551 GEN
Solar/Wind Harmer
1.635
247621Y3-024
Adder
0.162
964611AG1-324 GEN
Solar/Wind Harmer
0.348
270201AC2-176 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
2.485
270599AE1-208 GEN
Solar/Wind Harmer
4.141
971613AH1-306 GEN
Solar/Wind Harmer
2.151
964571AG1-320 GEN
Solar/Wind Harmer
4.079
970291AG2-192 GEN
Solar/Wind Harmer
0.57
970291AG2-192 GEN
Solar/Wind Harmer
0.263
944541AF1-119 GEN
Solar/Wind Harmer
0.292
960971AF2-388 GEN
Solar/Wind Harmer
2.564
942221AE2-234 GEN
Solar/Wind Harmer
1.655
971587AH1-292 GEN
Solar/Wind Harmer
2.993
945391AF1-204 GEN
Solar/Wind Harmer
4.316
970241AG2-163 GEN
Solar/Wind Harmer
2.286
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.434
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
7.7
276911AD2-131_GEN
Solar/Wind Harmer
0.507
276615X2-022 GEN
Solar/Wind Harmer
0.038
276838X2-022 GEN2
Solar/Wind Harmer
0.206
25326509SID D
Adder
0.689
960611AF2-352 GEN
Solar/Wind Harmer
1.21
942111AE2-223 GEN
Solar/Wind Harmer
1.178
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
8.857
274770LINCOLN ;1U
Adder
4.277
274771LINCOLN ;2U
Adder
4.277
276901AD2-066 C O1
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.206
276776AD2-060 GEN
Solar/Wind Harmer
0.377
958011AF2-095 GEN
Solar/Wind Harmer
5.084
970941AG2-585 GEN
Solar/Wind Harmer
1.942
276893AG1-478 C
Solar/Wind Harmer
0.235
274674JOLIET 9 ;6U
Adder
7.779
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
5.287
958491AF2-143 GEN
Solar/Wind Harmer
5.287
276645AC1-214 GEN1
Solar/Wind Harmer
0.138
274805UNIV PK N;1U
Adder
2.533
274808UNIV PK N;4U
Adder
2.517
274696ROCKY RD ;4P
Adder
5.728
274695ROCKY RD ;2P
Adder
5.596
274693ROCKY RD ;1P
Adder
5.541
274697ROCKY RD ;3P
Adder
1.52
962691AG1-118 GEN
Solar/Wind Harmer
10.508
964781AG1-341 GEN
Solar/Wind Harmer
3.705
971341AH1-150 GEN
Solar/Wind Harmer
6.982
971343AH1-151 GEN
Solar/Wind Harmer
6.982
970349AG2-230 GEN
Solar/Wind Harmer
5.234
965681AG1-436 GEN
Solar/Wind Harmer
4.361
965791AG1-447 GEN
Solar/Wind Harmer
3.198
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.562
938861AE1-114 GEN
Solar/Wind Harmer
1.972
970329AG2-216 GEN
Solar/Wind Harmer
1.444
961051AF2-396 GEN
Solar/Wind Harmer
6.65
961051AF2-396 GEN
Solar/Wind Harmer
4.433
971485AH1-239 GEN
Solar/Wind Harmer
2.603
966021AG1-471 GEN
Solar/Wind Harmer
1.739
270246TR4_N_V150
Solar/Wind Harmer
0.019
270247TR4_N_V136
Solar/Wind Harmer
0.019
237033AB1-150 GEN
Solar/Wind Helper
0.401
24803406KYGER 5HP
50/50
4.083
24803206KYGER 4HP
50/50
4.079
252516AE2-318_GEN
Solar/Wind Harmer
8.283
25196808ZIMRHP
Adder
79.38
25194608D.CRK4
Adder
1.689
252510AF1-249 C
Solar/Wind Harmer
0.054
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.986
25196008MFTGT1
Adder
1.369
253398AE2-221_GEN2
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.031
270273AD2-016 GEN
Solar/Wind Harmer
0.594
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
25326309TAIT D
Adder
0.844
3429421JKCT 10G
Adder
6.396
970773AG2-487 GEN
Solar/Wind Harmer
0.939
3429241JKCT 3G
Adder
8.835
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.76
270005AE1-210 C O1
Solar/Wind Harmer
1.04
24728605AND G2
Adder
2.628
970825AG2-519 GEN
Solar/Wind Harmer
1.683
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
5.07
270594AE1-207 GEN
Solar/Wind Harmer
5.019
270032AE2-172
Solar/Wind Harmer
2.988
958861AF2-177 GEN
Solar/Wind Harmer
1.919
965651AG1-433 GEN
Solar/Wind Harmer
1.282
270024AE2-089 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.063
970091AG2-072 GEN
Adder
45.503
253333AC1-068 GEN
Solar/Wind Harmer
0.005
963741AG1-226 GEN
Solar/Wind Harmer
9.274
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
964901AG1-354 GEN
Solar/Wind Harmer
5.594
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.628
276621W2-048 GEN
Solar/Wind Harmer
0.183
965911AG1-460 GEN
Solar/Wind Harmer
0.732
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.756
958381AF2-132 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
5.074
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.536
939401AE1-172 GEN
Solar/Wind Harmer
2.672
941551AE2-152 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
4.277
274774LINCOLN ;5U
Adder
4.277
971997AH1-543 GEN
Solar/Wind Harmer
1.853
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.311
274674JOLIET 9 ;6U
Adder
7.779
276694AA1-018 GEN2
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
970569AG2-363 GEN
Solar/Wind Harmer
10.575
274802UNIV PARK;5U
Adder
2.945
276691AA1-018 GEN1
Solar/Wind Harmer
0.573
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.411
276646AC1-214 GEN2
Solar/Wind Harmer
0.138
274848CAMPGROVE;RU
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.488
274812UNIV PK N;8U
Adder
2.528
274723RIVER EC ;12
Adder
9.04
274751CRETE EC ;1U
Adder
4.155
274754CRETE EC ;4U
Adder
4.155
274745AC1-111 GEN9
Adder
2.817
962781AG1-127 GEN
Solar/Wind Harmer
3.332
274872LEEDK;1U
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
10.473
959081AF2-199 GEN
Solar/Wind Harmer
3.491
971067AG2-660 GEN
Solar/Wind Harmer
1.164
276708O09 GEN2
Solar/Wind Harmer
0.123
970819AG2-516 GEN
Solar/Wind Harmer
4.177
274858EASY ROAD;U2
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
5.58
945111AF1-176 GEN
Solar/Wind Harmer
5.962
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.73
965011AG1-365 GEN
Solar/Wind Harmer
3.232
960001AF2-291 GEN
Solar/Wind Helper
1.722
270331AC1-082 GEN3
Solar/Wind Helper
0.193
235780M24_1
Solar/Wind Helper
0.496
24803106KYGER 3LP
50/50
2.43
24803306KYGER 4LP
50/50
2.38
971191AH1-055 GEN
Solar/Wind Harmer
68.684
252507AC2-088 GEN
Solar/Wind Harmer
0.357
252519AF1-045_GEN
Solar/Wind Harmer
3.858
25194608D.CRK4
Adder
1.689
25196608WSDLE5
Adder
8.798
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.081
25196008MFTGT1
Adder
1.326
958171AF2-111 GEN
Solar/Wind Harmer
17.024
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.127
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.601
253371AE2-315 SEC2
Adder
1.514
970191AG2-125 GEN
Solar/Wind Harmer
1.385
3429391JKCT 9G
Adder
6.396
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.143
270004AE1-209 GEN
Solar/Wind Harmer
1.04
24728705AND G3
Adder
5.496
24728505AND G1
Adder
2.628
946031AF1-268 GEN
Solar/Wind Harmer
4.524
970825AG2-519 GEN
Solar/Wind Harmer
3.571
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.92
970455AG2-298 GEN
Solar/Wind Harmer
1.776
970289AG2-191 GEN
Solar/Wind Harmer
0.483
247642Z2-115 C
Solar/Wind Harmer
0.002
970653AG2-424 GEN
Solar/Wind Harmer
0.428
944531AF1-118 GEN
Solar/Wind Harmer
18.504
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970193AG2-126 GEN
Solar/Wind Harmer
6.094
24386205FR-12G C
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.775
270518AE2-148 GEN
Solar/Wind Harmer
0.304
971993AH1-541 GEN
Solar/Wind Harmer
1.694
942481AE2-261 GEN
Solar/Wind Harmer
10.95
957381AF2-032 GEN
Solar/Wind Harmer
0.83
964401AG1-302 GEN
Solar/Wind Harmer
0
972273AH1-721 GEN
Adder
43.369
965091AG1-374 GEN
Solar/Wind Harmer
10.891
959611AF2-252 GEN
Solar/Wind Harmer
1.21
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
4.277
274887GEN-1.85
Solar/Wind Harmer
0.092
276843GEN-1.7
Solar/Wind Harmer
0.114
276806AD2-047 C O1
Solar/Wind Harmer
2.001
972259AH1-714 GEN
Adder
9.653
274729ELWOOD EC;1P
Adder
8.311
274730ELWOOD EC;6P
Adder
8.311
274734ELWOOD EC;8P
Adder
8.311
274736ELWOOD EC;9P
Adder
8.311
970707AG2-453 GEN
Solar/Wind Harmer
11.521
270043AE2-236 GEN
Solar/Wind Harmer
2.263
972038AH1-567 GEN2
Adder
0.184
970571AG2-364 GEN
Solar/Wind Harmer
7.05
274803UNIV PARK;6U
Adder
2.945
276868AE1-113 GEN
Solar/Wind Harmer
0.705
274879MINONK ;1U
Solar/Wind Harmer
0.147
274862TOP CROP ;2U
Solar/Wind Harmer
0.476
274826FISK ;BP
Adder
5.528
274676JOLIET 29;8U
Adder
14.935
274814UNIV PK N;0U
Adder
2.55
274807UNIV PK N;3U
Adder
2.544
274811UNIV PK N;7U
Adder
2.528
274724RIVER EC ;11
Adder
8.935
274752CRETE EC ;2U
Adder
4.155
274753CRETE EC ;3U
Adder
4.155
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
943121AE2-341 GEN
Solar/Wind Harmer
5.893
943591AF1-030 GEN
Solar/Wind Harmer
3.919
274682WAUKEGAN ;7U
Adder
5.301
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
959091AF2-200 GEN
Solar/Wind Harmer
6.982
971347AH1-153 GEN
Solar/Wind Harmer
1.745
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
8.801
971087AG2-675 GEN
Solar/Wind Harmer
1.841
270063AE2-323 C
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
3.511
945111AF1-176 GEN
Solar/Wind Harmer
2.708
965021AG1-366 GEN
Solar/Wind Harmer
1.077
270330AC1-082 GEN2
Solar/Wind Helper
0.194
270329AC1-082 GEN1
Solar/Wind Helper
0.194
24802606KYGER 1HP
50/50
4.156
24802706KYGER 1LP
50/50
2.437
24803506KYGER 5LP
50/50
2.38
971985AH1-537 GEN
Solar/Wind Harmer
5.763
25196408WSDLE3
Adder
9.057
25196308WSDLE2
Adder
8.978
25196208WSDLE1
Adder
8.956
25196708WSDLE6
Adder
8.933
25196508WSDLE4
Adder
8.708
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.401
972163AH1-664 GEN
Solar/Wind Harmer
7.027
972165AH1-665 GEN
Solar/Wind Harmer
5.628
253406AD2-031_GEN
Solar/Wind Harmer
0.458
339216AC1-074 GEN
Solar/Wind Harmer
0.162
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.58
253372AE2-315 SEC3
Adder
1.514
253372AE2-315 SEC3
Adder
1.514
25306009OHH W.
Adder
2.27
270356AE2-297 GEN
Solar/Wind Harmer
0
3429211JKCT 2G
Adder
8.721
971029AG2-637 GEN
Solar/Wind Harmer
7.57
270543AE2-219 C
Solar/Wind Harmer
3.433
247536S-71 GEN
Solar/Wind Harmer
0.191
964611AG1-324 GEN
Solar/Wind Harmer
1.811
945581AF1-223 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.738
270432AC2-029 GEN
Solar/Wind Harmer
2.001
241972AD1-140 GEN
Solar/Wind Harmer
0.484
970289AG2-191 GEN
Solar/Wind Harmer
0.834
24729505KEY G4
Adder
3.899
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.68
24386405FR-21G C
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.053
270071AF1-092 GEN
Solar/Wind Harmer
7.11
971611AH1-305 GEN
Solar/Wind Harmer
2.204
959141AF2-205 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.16
958391AF2-133 GEN
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.144
276848AB2-070 GEN3
Solar/Wind Harmer
0.143
276849AB2-070 GEN2
Solar/Wind Harmer
0.144
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.806
970169AG2-114 GEN
Solar/Wind Harmer
3.591
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
4.277
274776LINCOLN ;7U
Adder
4.277
274777LINCOLN ;8U
Adder
4.277
926823AC1-168 GEN
Solar/Wind Harmer
0.6
972228AH1-698 GEN2
Adder
1.875
972227AH1-698 GEN1
Adder
1.321
970833AG2-524 GEN
Solar/Wind Harmer
3.884
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.53
274728ELWOOD EC;5P
Adder
8.311
274731ELWOOD EC;2P
Adder
8.311
274733ELWOOD EC;3P
Adder
8.311
274735ELWOOD EC;4P
Adder
8.311
274800UNIV PARK;3U
Adder
2.946
274801UNIV PARK;4U
Adder
2.946
970073AG2-061 GEN
Solar/Wind Harmer
1.175
972037AH1-567 GEN1
Adder
0.092
274827FISK ;RP
Adder
3.918
274675JOLIET 29;7U
Adder
15.488
274675JOLIET 29;7U
Adder
14.935
274687WILL CNTY;4U
Adder
14.106
274687WILL CNTY;4U
Adder
14.106
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
274744AC1-111 GEN8
Adder
2.817
274746AC1-111 G10
Adder
2.817
276861AD2-134 GEN
Solar/Wind Harmer
0.062
276863AD2-134 GEN
Solar/Wind Harmer
0.062
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971411AH1-196 GEN
Solar/Wind Harmer
5.237
971171AH1-044 GEN
Solar/Wind Harmer
6.982
960681AF2-359 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.123
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
971681AH1-341 GEN
Solar/Wind Harmer
5.605
946321AF1-296 GEN
Solar/Wind Harmer
1.935
270526AF1-158 GEN
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
3.411
970031AG2-029 GEN
Solar/Wind Harmer
1.822
959331AF2-224 GEN
Solar/Wind Harmer
2.262
965041AG1-368 GEN
Solar/Wind Harmer
3.099
247521TR3_G114
Solar/Wind Harmer
0.11
965051AG1-369 GEN
Solar/Wind Harmer
1.514
945631AF1-228 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
6.245
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
1.666
LGEELTFEXP_LGEE->PJM
CLTF
5.14
WECLTFEXP_WEC->PJM
CLTF
1.904
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.317
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.627
MECLTFEXP_MEC->PJM
CLTF
8.009
SIGELTFEXP_SIGE->PJM
CLTF
0.331
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.289
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.393
LAGNLTFEXP_LAGN->PJM
CLTF
6.552
TVALTFEXP_TVA->PJM
CLTF
3.106

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.27 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2052.4
MW Contribution:
4.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.179
24802806KYGER 2HP
50/50
4.162
24802906KYGER 2LP
50/50
2.443
25183008BIOENL
50/50
0.032
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0
25194408D.CRK1
Adder
8.168
25194508D.CRK3
Adder
1.527
270269AC2-059
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972043AH1-570 GEN
Solar/Wind Harmer
1.575
972045AH1-571 GEN
Solar/Wind Harmer
1.262
253370AE2-315 SEC1
Adder
1.716
971125AH1-004 GEN
Solar/Wind Harmer
2.323
970107AG2-081 GEN
Solar/Wind Harmer
1.743
25322209TAIT E
Adder
8.074
25322209TAIT E
Adder
7.893
25326109MON D
Adder
1.062
24728805RICHG1
Adder
2.987
24728905RICHG2
Adder
2.987
942891AE2-308 GEN
Solar/Wind Harmer
5.239
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.803
970885AG2-551 GEN
Solar/Wind Harmer
1.601
247621Y3-024
Adder
0.156
964571AG1-320 GEN
Solar/Wind Harmer
4.114
964611AG1-324 GEN
Solar/Wind Harmer
0.333
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
2.045
270031AE2-169
Solar/Wind Harmer
2.337
270599AE1-208 GEN
Solar/Wind Harmer
3.895
970291AG2-192 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.25
971587AH1-292 GEN
Solar/Wind Harmer
3.03
25326509SID D
Adder
0.755
944541AF1-119 GEN
Solar/Wind Harmer
0.265
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.175
942221AE2-234 GEN
Solar/Wind Harmer
1.514
970329AG2-216 GEN
Solar/Wind Harmer
1.606
970241AG2-163 GEN
Solar/Wind Harmer
2.168
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.406
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
7.149
276911AD2-131_GEN
Solar/Wind Harmer
0.471
964781AG1-341 GEN
Solar/Wind Harmer
3.596
276615X2-022 GEN
Solar/Wind Harmer
0.035
276838X2-022 GEN2
Solar/Wind Harmer
0.19
942861AE2-305 GEN
Solar/Wind Harmer
2.579
960611AF2-352 GEN
Solar/Wind Harmer
1.092
942111AE2-223 GEN
Solar/Wind Harmer
1.058
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.122
971485AH1-239 GEN
Solar/Wind Harmer
2.492
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
276901AD2-066 C O1
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
4.619
966021AG1-471 GEN
Solar/Wind Harmer
1.662
276897AD1-100 C
Solar/Wind Harmer
7.68
958481AF2-142 GEN
Solar/Wind Harmer
4.605
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.494
276893AG1-478 C
Solar/Wind Harmer
0.204
274888KELLY CRK;1U
Solar/Wind Harmer
0.178
276776AD2-060 GEN
Solar/Wind Harmer
0.326
958011AF2-095 GEN
Solar/Wind Harmer
4.397
274674JOLIET 9 ;6U
Adder
6.739
970941AG2-585 GEN
Solar/Wind Harmer
1.679
971341AH1-150 GEN
Solar/Wind Harmer
6.093
971343AH1-151 GEN
Solar/Wind Harmer
6.093
938861AE1-114 GEN
Solar/Wind Harmer
1.726
962691AG1-118 GEN
Solar/Wind Harmer
9.136
274764LEE CO EC;5U
Adder
4.07
274765LEE CO EC;6U
Adder
4.07
274762LEE CO EC;3U
Adder
4.061
274763LEE CO EC;4U
Adder
4.023
274696ROCKY RD ;4P
Adder
4.974
274695ROCKY RD ;2P
Adder
4.859
274693ROCKY RD ;1P
Adder
4.811
274697ROCKY RD ;3P
Adder
1.32
274683WAUKEGAN ;8U
Adder
9.19
274683WAUKEGAN ;8U
Adder
7.747
972235AH1-702 GEN1
Adder
1.099
972236AH1-702 GEN2
Adder
0.956
237033AB1-150 GEN
Solar/Wind Helper
0.404
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252516AE2-318_GEN
Solar/Wind Harmer
8.746
25196808ZIMRHP
Adder
83.622
25194608D.CRK4
Adder
1.776
252510AF1-249 C
Solar/Wind Harmer
0.057
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.475
25196008MFTGT1
Adder
1.43
253398AE2-221_GEN2
Solar/Wind Harmer
0
945681AF1-233 GEN
Solar/Wind Harmer
12.627
270273AD2-016 GEN
Solar/Wind Harmer
0.667
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
25326309TAIT D
Adder
0.906
3429421JKCT 10G
Adder
6.589
3429241JKCT 3G
Adder
9.074
970773AG2-487 GEN
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.658
24728605AND G2
Adder
2.584
253333AC1-068 GEN
Solar/Wind Harmer
0.005
270005AE1-210 C O1
Solar/Wind Harmer
0.992
970825AG2-519 GEN
Solar/Wind Harmer
1.611
970091AG2-072 GEN
Adder
49.338
276903AD2-071 C
Solar/Wind Harmer
4.853
970653AG2-424 GEN
Solar/Wind Harmer
2.069
270594AE1-207 GEN
Solar/Wind Harmer
4.771
270032AE2-172
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.758
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.166
963741AG1-226 GEN
Solar/Wind Harmer
8.794
972203AH1-686 GEN
Adder
1.223
964901AG1-354 GEN
Solar/Wind Harmer
5.49
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276621W2-048 GEN
Solar/Wind Harmer
0.169
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
4.21
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.274
958381AF2-132 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
4.558
270055AF2-134 C O1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.636
939401AE1-172 GEN
Solar/Wind Harmer
2.347
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.122
970569AG2-363 GEN
Solar/Wind Harmer
9.303
971997AH1-543 GEN
Solar/Wind Harmer
1.622
276882AE2-255 GEN
Solar/Wind Harmer
0.36
276805AD2-038 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.499
276708O09 GEN2
Solar/Wind Harmer
0.108
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.204
274674JOLIET 9 ;6U
Adder
6.739
274676JOLIET 29;8U
Adder
13.407
274802UNIV PARK;5U
Adder
2.546
274745AC1-111 GEN9
Adder
2.441
957471AF2-041 GEN
Solar/Wind Harmer
9.139
959081AF2-199 GEN
Solar/Wind Harmer
3.046
971067AG2-660 GEN
Solar/Wind Harmer
1.015
274872LEEDK;1U
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
4.061
274766LEE CO EC;7U
Adder
4.013
962781AG1-127 GEN
Solar/Wind Harmer
2.898
274682WAUKEGAN ;7U
Adder
7.839
274828WAUKEGAN ;BP
Adder
4.817
274822ROCKFORD ;11
Adder
2.437
970819AG2-516 GEN
Solar/Wind Harmer
3.649
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.186
235780M24_1
Solar/Wind Helper
0.501
24803106KYGER 3LP
50/50
2.46
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
70.432
252507AC2-088 GEN
Solar/Wind Harmer
0.376
252519AF1-045_GEN
Solar/Wind Harmer
4.074
25194608D.CRK4
Adder
1.776
25196608WSDLE5
Adder
9.253
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.717
958171AF2-111 GEN
Solar/Wind Harmer
17.947
25196008MFTGT1
Adder
1.385
253394AE2-221_GEN
Solar/Wind Harmer
0
972167AH1-666 GEN
Solar/Wind Harmer
5.382
270367AC2-061_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
970191AG2-125 GEN
Solar/Wind Harmer
1.47
3429391JKCT 9G
Adder
6.589
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
4.224
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253325AC1-069 GEN
Solar/Wind Harmer
0.005
970455AG2-298 GEN
Solar/Wind Harmer
1.797
270004AE1-209 GEN
Solar/Wind Harmer
0.992
946031AF1-268 GEN
Solar/Wind Harmer
4.337
970825AG2-519 GEN
Solar/Wind Harmer
3.419
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.615
970653AG2-424 GEN
Solar/Wind Harmer
0.429
270518AE2-148 GEN
Solar/Wind Harmer
0.348
970289AG2-191 GEN
Solar/Wind Harmer
0.457
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
5.894
944531AF1-118 GEN
Solar/Wind Harmer
16.286
24386205FR-12G C
Solar/Wind Harmer
0
972273AH1-721 GEN
Adder
42.335
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.495
942481AE2-261 GEN
Solar/Wind Harmer
10.146
957381AF2-032 GEN
Solar/Wind Harmer
0.768
971993AH1-541 GEN
Solar/Wind Harmer
1.554
964401AG1-302 GEN
Solar/Wind Harmer
0
965091AG1-374 GEN
Solar/Wind Harmer
9.828
959611AF2-252 GEN
Solar/Wind Harmer
1.092
274878BISHOP HL;2U
Solar/Wind Harmer
0.104
276782AC1-033 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.202
942051AE2-217 GEN
Solar/Wind Harmer
5.57
276868AE1-113 GEN
Solar/Wind Harmer
0.616
274879MINONK ;1U
Solar/Wind Harmer
0.129
939351AE1-166 GEN
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.415
274729ELWOOD EC;1P
Adder
7.204
274730ELWOOD EC;6P
Adder
7.204
274734ELWOOD EC;8P
Adder
7.204
274736ELWOOD EC;9P
Adder
7.204
274887GEN-1.85
Solar/Wind Harmer
0.079
276843GEN-1.7
Solar/Wind Harmer
0.099
276806AD2-047 C O1
Solar/Wind Harmer
1.73
972259AH1-714 GEN
Adder
8.342
274676JOLIET 29;8U
Adder
12.928
972038AH1-567 GEN2
Adder
0.159
274803UNIV PARK;6U
Adder
2.546
274855GSG-6 ;RU
Solar/Wind Harmer
0.111
274850MENDOTA H;RU
Solar/Wind Harmer
0.035
946671AF1-331 GEN
Solar/Wind Harmer
0.325
959091AF2-200 GEN
Solar/Wind Harmer
6.093
274857EASY ROAD;U1
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
7.765
274760LEE CO EC;1U
Adder
4.061
274767LEE CO EC;8U
Adder
4.013
971087AG2-675 GEN
Solar/Wind Harmer
1.624
274826FISK ;BP
Adder
4.777
943121AE2-341 GEN
Solar/Wind Harmer
5.104
943591AF1-030 GEN
Solar/Wind Harmer
3.394
274682WAUKEGAN ;7U
Adder
7.839
970707AG2-453 GEN
Solar/Wind Harmer
9.937
270330AC1-082 GEN2
Solar/Wind Helper
0.188
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24802606KYGER 1HP
50/50
4.207
24802706KYGER 1LP
50/50
2.467
24803506KYGER 5LP
50/50
2.41
971985AH1-537 GEN
Solar/Wind Harmer
5.9
25196408WSDLE3
Adder
9.526
25196308WSDLE2
Adder
9.443
25196208WSDLE1
Adder
9.419
25196708WSDLE6
Adder
9.395
25196508WSDLE4
Adder
9.159
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
253406AD2-031_GEN
Solar/Wind Harmer
0.493
972163AH1-664 GEN
Solar/Wind Harmer
7.368
972165AH1-665 GEN
Solar/Wind Harmer
5.901
270263AC1-001 GEN
Solar/Wind Harmer
0.65
270340AC2-060 GEN
Solar/Wind Harmer
0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.169
253372AE2-315 SEC3
Adder
1.623
253372AE2-315 SEC3
Adder
1.623
25306009OHH W.
Adder
2.424
3429211JKCT 2G
Adder
8.956
270356AE2-297 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.299
971029AG2-637 GEN
Solar/Wind Harmer
7.492
241972AD1-140 GEN
Solar/Wind Harmer
0.535
270543AE2-219 C
Solar/Wind Harmer
3.362
247536S-71 GEN
Solar/Wind Harmer
0.185
964611AG1-324 GEN
Solar/Wind Harmer
1.732
971609AH1-304 GEN
Solar/Wind Harmer
0.694
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.79
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.463
963841AG1-237 GEN
Solar/Wind Harmer
1.583
945631AF1-228 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.02
963791AG1-232 GEN
Solar/Wind Harmer
4.554
971611AH1-305 GEN
Solar/Wind Harmer
2.005
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.132
276848AB2-070 GEN3
Solar/Wind Harmer
0.132
276849AB2-070 GEN2
Solar/Wind Harmer
0.132
959141AF2-205 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.273
943851AF1-053 GEN
Solar/Wind Harmer
0.882
274854TWINGROVE;U2
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.418
270071AF1-092 GEN
Solar/Wind Harmer
6.13
970169AG2-114 GEN
Solar/Wind Harmer
3.185
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.104
926823AC1-168 GEN
Solar/Wind Harmer
0.529
970073AG2-061 GEN
Solar/Wind Harmer
1.026
276741O09 GEN1
Solar/Wind Harmer
0.108
970833AG2-524 GEN
Solar/Wind Harmer
3.368
970833AG2-524 GEN
Solar/Wind Harmer
2.246
274728ELWOOD EC;5P
Adder
7.204
274731ELWOOD EC;2P
Adder
7.204
274733ELWOOD EC;3P
Adder
7.204
274735ELWOOD EC;4P
Adder
7.204
972227AH1-698 GEN1
Adder
1.143
972228AH1-698 GEN2
Adder
1.623
960591AF2-350 GEN
Solar/Wind Harmer
3.054
274675JOLIET 29;7U
Adder
13.407
274675JOLIET 29;7U
Adder
12.928
274687WILL CNTY;4U
Adder
12.208
274687WILL CNTY;4U
Adder
12.208
274800UNIV PARK;3U
Adder
2.547
274801UNIV PARK;4U
Adder
2.547
971681AH1-341 GEN
Solar/Wind Harmer
4.906
274744AC1-111 GEN8
Adder
2.441
274746AC1-111 G10
Adder
2.441
972267AH1-718 GEN
Adder
1.819
972037AH1-567 GEN1
Adder
0.08
276861AD2-134 GEN
Solar/Wind Harmer
0.054
276863AD2-134 GEN
Solar/Wind Harmer
0.054
971171AH1-044 GEN
Solar/Wind Harmer
6.093
971675AH1-338 GEN
Solar/Wind Harmer
1.188
946321AF1-296 GEN
Solar/Wind Harmer
1.706
274827FISK ;RP
Adder
3.386
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
971411AH1-196 GEN
Solar/Wind Harmer
4.564
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.274
NYPJM->LTFIMP_NY
CLTF
1.597
LGEELTFEXP_LGEE->PJM
CLTF
5.305
WECLTFEXP_WEC->PJM
CLTF
1.662
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.431
MECLTFEXP_MEC->PJM
CLTF
7.137
SIGELTFEXP_SIGE->PJM
CLTF
0.33
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.628
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.865
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
TVALTFEXP_TVA->PJM
CLTF
2.665

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.62 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:1962.84
MW Contribution:
10.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274805UNIV PK N;1U
Adder
4.872
274808UNIV PK N;4U
Adder
4.84
958011AF2-095 GEN
Solar/Wind Harmer
13.642
274888KELLY CRK;1U
Solar/Wind Harmer
5.591
276776AD2-060 GEN
Solar/Wind Harmer
0.397
970941AG2-585 GEN
Solar/Wind Harmer
5.211
276893AG1-478 C
Solar/Wind Harmer
0.384
274674JOLIET 9 ;6U
Adder
13.257
958481AF2-142 GEN
Solar/Wind Harmer
12.637
958491AF2-143 GEN
Solar/Wind Harmer
12.166
276897AD1-100 C
Solar/Wind Harmer
37.435
274683WAUKEGAN ;8U
Adder
16.307
274683WAUKEGAN ;8U
Adder
13.746
276901AD2-066 C O1
Solar/Wind Harmer
2.703
276872AE1-163_GEN1
Solar/Wind Harmer
5.154
276876AE1-163_GEN2
Solar/Wind Harmer
5.154
274696ROCKY RD ;4P
Adder
8.606
274695ROCKY RD ;2P
Adder
8.408
274693ROCKY RD ;1P
Adder
8.325
274697ROCKY RD ;3P
Adder
2.284
962691AG1-118 GEN
Solar/Wind Harmer
21.967
960751AF2-366 GEN
Solar/Wind Harmer
2.093
971341AH1-150 GEN
Solar/Wind Harmer
14.311
971343AH1-151 GEN
Solar/Wind Harmer
14.311
972235AH1-702 GEN1
Adder
1.802
972236AH1-702 GEN2
Adder
1.567
274770LINCOLN ;1U
Adder
4.395
274771LINCOLN ;2U
Adder
4.395
938861AE1-114 GEN
Solar/Wind Harmer
5.737
274764LEE CO EC;5U
Adder
6.485
274765LEE CO EC;6U
Adder
6.485
274762LEE CO EC;3U
Adder
6.47
274763LEE CO EC;4U
Adder
6.409
276158O29GEN2
Solar/Wind Harmer
3.399
276157O29GEN1
Solar/Wind Harmer
2.584
276645AC1-214 GEN1
Solar/Wind Harmer
0.904
942111AE2-223 GEN
Solar/Wind Harmer
4.923
960611AF2-352 GEN
Solar/Wind Harmer
1.34
274724RIVER EC ;11
50/50
24.846
957371AF2-031 GEN
50/50
1.23
274826FISK ;BP
50/50
11.717
274752CRETE EC ;2U
50/50
5.22
274753CRETE EC ;3U
50/50
5.22
276164X3-005 C
Solar/Wind Harmer
0.81
972231SS25-0005
Solar/Wind Harmer
9.552
972181SS23-001
Solar/Wind Harmer
5.97
972038AH1-567 GEN2
Adder
0.363
274814UNIV PK N;0U
Adder
4.904
274807UNIV PK N;3U
Adder
4.893
274811UNIV PK N;7U
Adder
4.861
274803UNIV PARK;6U
Adder
5.65
274887GEN-1.85
Solar/Wind Harmer
5.047
276772AC2-154 GEN
Solar/Wind Harmer
2.644
276843GEN-1.7
Solar/Wind Harmer
0.543
276806AD2-047 C O1
Solar/Wind Harmer
10.135
274676JOLIET 29;8U
Adder
25.446
274730ELWOOD EC;6P
Adder
13.955
274734ELWOOD EC;8P
Adder
13.955
274736ELWOOD EC;9P
Adder
13.955
274729ELWOOD EC;1P
Adder
13.947
274862TOP CROP ;2U
Solar/Wind Harmer
4.257
939351AE1-166 GEN
Solar/Wind Harmer
4.779
972259AH1-714 GEN
Adder
14.936
276868AE1-113 GEN
Solar/Wind Harmer
7.858
274879MINONK ;1U
Solar/Wind Harmer
5.239
274682WAUKEGAN ;7U
Adder
13.943
970571AG2-364 GEN
Solar/Wind Harmer
14.754
961501AF2-441 GEN
50/50
11.4
274827FISK ;RP
50/50
8.304
274800UNIV PARK;3U
Adder
5.803
274801UNIV PARK;4U
Adder
5.803
972037AH1-567 GEN1
Adder
0.177
960591AF2-350 GEN
Solar/Wind Harmer
9.474
274687WILL CNTY;4U
Adder
24.871
274687WILL CNTY;4U
Adder
24.871
276893AG1-478 C
Solar/Wind Harmer
0.481
274675JOLIET 29;7U
Adder
26.387
274675JOLIET 29;7U
Adder
25.445
972228AH1-698 GEN2
Adder
3.17
972227AH1-698 GEN1
Adder
2.231
274728ELWOOD EC;5P
Adder
13.955
274731ELWOOD EC;2P
Adder
13.947
274733ELWOOD EC;3P
Adder
13.947
274735ELWOOD EC;4P
Adder
13.947
970073AG2-061 GEN
Solar/Wind Harmer
1.886
970833AG2-524 GEN
Solar/Wind Harmer
6.794
970833AG2-524 GEN
Solar/Wind Harmer
3.16
276889AE2-281 GEN
Solar/Wind Harmer
1.473
274744AC1-111 GEN8
Adder
4.23
274746AC1-111 G10
Adder
4.23
971411AH1-196 GEN
Solar/Wind Harmer
10.984
274823ROCKFORD ;21
Adder
13.999
971675AH1-338 GEN
Solar/Wind Harmer
12.915
276861AD2-134 GEN
Solar/Wind Harmer
1.281
276863AD2-134 GEN
Solar/Wind Harmer
1.281
971171AH1-044 GEN
Solar/Wind Harmer
14.311
274775LINCOLN ;6U
Adder
4.395
274776LINCOLN ;7U
Adder
4.395
274777LINCOLN ;8U
Adder
4.395
274856ECOGROVE ;U1
Solar/Wind Harmer
2.39
276611AD2-172 GEN
Solar/Wind Harmer
1.813
276612AE2-035 GEN
Solar/Wind Harmer
1.813
926823AC1-168 GEN
Solar/Wind Harmer
3.016
971681AH1-341 GEN
Solar/Wind Harmer
10.489
274863CRW1-WTG
Solar/Wind Harmer
3.844
274864CRW2-WTG
Solar/Wind Harmer
3.844
972267AH1-718 GEN
Adder
2.843
276741O09 GEN1
Solar/Wind Harmer
2.427
274877BISHOP HL;1U
Solar/Wind Harmer
2.256
970169AG2-114 GEN
Solar/Wind Harmer
6.608
946321AF1-296 GEN
Solar/Wind Harmer
6.781
276726Z2-087_GEN
Solar/Wind Harmer
4.749
959341AF2-225 GEN
Solar/Wind Harmer
9.009
274853TWINGROVE;U1
Solar/Wind Harmer
4.15
274854TWINGROVE;U2
Solar/Wind Harmer
4.063
276668AB2-070 GEN1
Solar/Wind Harmer
0.846
276848AB2-070 GEN3
Solar/Wind Harmer
0.846
276849AB2-070 GEN2
Solar/Wind Harmer
0.846
274723RIVER EC ;12
50/50
24.791
972179AH1-673 GEN
50/50
12.785
274751CRETE EC ;1U
50/50
5.22
274754CRETE EC ;4U
50/50
5.22
274812UNIV PK N;8U
Adder
4.861
274802UNIV PARK;5U
Adder
5.65
274674JOLIET 9 ;6U
Adder
13.257
274676JOLIET 29;8U
Adder
26.389
274732ELWOOD EC;7P
Adder
13.955
276694AA1-018 GEN2
Solar/Wind Harmer
5.316
276691AA1-018 GEN1
Solar/Wind Harmer
0.635
274861TOP CROP ;1U
Solar/Wind Harmer
5.098
276805AD2-038 GEN
Solar/Wind Harmer
4.159
941551AE2-152 GEN
Solar/Wind Harmer
3.655
276882AE2-255 GEN
Solar/Wind Harmer
2.619
274682WAUKEGAN ;7U
Adder
13.943
274828WAUKEGAN ;BP
Adder
8.548
274871GR RIDGE ;2U
Solar/Wind Harmer
5.934
274847GR RIDGE ;BU
Solar/Wind Harmer
3.902
274745AC1-111 GEN9
Adder
4.23
970569AG2-363 GEN
Solar/Wind Harmer
22.132
962781AG1-127 GEN
Solar/Wind Harmer
6.938
971997AH1-543 GEN
Solar/Wind Harmer
11.467
274872LEEDK;1U
Solar/Wind Harmer
5.963
274822ROCKFORD ;11
Adder
14.102
957471AF2-041 GEN
Solar/Wind Harmer
21.467
959081AF2-199 GEN
Solar/Wind Harmer
7.156
971067AG2-660 GEN
Solar/Wind Harmer
1.664
939401AE1-172 GEN
Solar/Wind Harmer
9.96
970819AG2-516 GEN
Solar/Wind Harmer
8.542
972207SS24-0001
Solar/Wind Harmer
15.627
274773LINCOLN ;4U
Adder
4.395
274774LINCOLN ;5U
Adder
4.395
274858EASY ROAD;U2
Solar/Wind Harmer
3.331
274761LEE CO EC;2U
Adder
6.47
274766LEE CO EC;7U
Adder
6.393
276708O09 GEN2
Solar/Wind Harmer
2.427
276646AC1-214 GEN2
Solar/Wind Harmer
0.904
274848CAMPGROVE;RU
Solar/Wind Harmer
4.278
276655WTG1_EQ
Solar/Wind Harmer
5.242
276656WTG2_EQ
Solar/Wind Harmer
0.694
939741AE1-205 GEN
Solar/Wind Harmer
12.012
943121AE2-341 GEN
Solar/Wind Harmer
11.018
943591AF1-030 GEN
Solar/Wind Harmer
7.346
276799AD1-013 GEN
Solar/Wind Harmer
1.586
946671AF1-331 GEN
Solar/Wind Harmer
0.301
274855GSG-6 ;RU
Solar/Wind Harmer
2.648
274850MENDOTA H;RU
Solar/Wind Harmer
1.841
276602WESTBROOK C
Solar/Wind Harmer
1.524
959091AF2-200 GEN
Solar/Wind Harmer
14.311
970707AG2-453 GEN
Solar/Wind Harmer
19.955
274772LINCOLN ;3U
Adder
4.395
274857EASY ROAD;U1
Solar/Wind Harmer
3.331
274760LEE CO EC;1U
Adder
6.47
274767LEE CO EC;8U
Adder
6.393
276603SUBLETTE C
Solar/Wind Harmer
0.725
274851PROVIDENC;RU
Solar/Wind Harmer
1.922
274849CRESCENT ;1U
Solar/Wind Harmer
1.247
276782AC1-033 GEN
Solar/Wind Harmer
2.666
274878BISHOP HL;2U
Solar/Wind Harmer
2.256
965931AG1-462 GEN
Solar/Wind Harmer
16.415
971087AG2-675 GEN
Solar/Wind Harmer
2.395
965091AG1-374 GEN
Solar/Wind Harmer
17.28
959611AF2-252 GEN
Solar/Wind Harmer
1.34
990577J1339
External Queue
22.734174728393555
990647J1355
External Queue
44.96687698364258
991247J1684 G
External Queue
28.59419822692871
990582J1340
External Queue
22.734174728393555
990662J1358
External Queue
17.028202056884766
991337J1802
External Queue
10.868167877197266
990552J1334 G
External Queue
34.31124496459961
990562J1336 G
External Queue
34.31124496459961
990762J1386
External Queue
10.402408599853516
991332J1785
External Queue
14.41087818145752
990547J1333 G
External Queue
34.31124496459961
990557J1335 G
External Queue
34.31124496459961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.126
NYPJM->LTFIMP_NY
CLTF
0.758
WECLTFEXP_WEC->PJM
CLTF
2.779
CBM West 1LTFEXP_CBM-W1->PJM
CBM
57.6
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.993
MECLTFEXP_MEC->PJM
CLTF
8.862
SIGELTFEXP_SIGE->PJM
CLTF
0.033
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.269
AG2-052LTFEXP_AG2-052->PJM
LTF
0.533
AH1-155LTFEXP_AH1-155->PJM
LTF
0.799
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.154
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.367
LAGNLTFEXP_LAGN->PJM
CLTF
3.237
TVALTFEXP_TVA->PJM
CLTF
0.916

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.88 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:1857.18
MW Contribution:
10.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
961501AF2-441 GEN
50/50
11.456
274827FISK ;RP
50/50
8.353
274800UNIV PARK;3U
Adder
5.837
274801UNIV PARK;4U
Adder
5.837
972037AH1-567 GEN1
Adder
0.178
960591AF2-350 GEN
Solar/Wind Harmer
9.533
274687WILL CNTY;4U
Adder
25.038
274687WILL CNTY;4U
Adder
25.038
276893AG1-478 C
Solar/Wind Harmer
0.485
274675JOLIET 29;7U
Adder
26.57
274675JOLIET 29;7U
Adder
25.621
972228AH1-698 GEN2
Adder
3.192
972227AH1-698 GEN1
Adder
2.246
274728ELWOOD EC;5P
Adder
14.052
274731ELWOOD EC;2P
Adder
14.045
274733ELWOOD EC;3P
Adder
14.045
274735ELWOOD EC;4P
Adder
14.045
970073AG2-061 GEN
Solar/Wind Harmer
1.9
970833AG2-524 GEN
Solar/Wind Harmer
6.846
970833AG2-524 GEN
Solar/Wind Harmer
3.184
276889AE2-281 GEN
Solar/Wind Harmer
1.484
274744AC1-111 GEN8
Adder
4.263
274746AC1-111 G10
Adder
4.263
971411AH1-196 GEN
Solar/Wind Harmer
11.073
274823ROCKFORD ;21
Adder
14.115
971675AH1-338 GEN
Solar/Wind Harmer
13.022
276861AD2-134 GEN
Solar/Wind Harmer
1.291
276863AD2-134 GEN
Solar/Wind Harmer
1.291
971171AH1-044 GEN
Solar/Wind Harmer
14.43
274775LINCOLN ;6U
Adder
4.432
274776LINCOLN ;7U
Adder
4.432
274777LINCOLN ;8U
Adder
4.432
274856ECOGROVE ;U1
Solar/Wind Harmer
2.411
276611AD2-172 GEN
Solar/Wind Harmer
1.829
276612AE2-035 GEN
Solar/Wind Harmer
1.829
926823AC1-168 GEN
Solar/Wind Harmer
3.041
971681AH1-341 GEN
Solar/Wind Harmer
10.578
274863CRW1-WTG
Solar/Wind Harmer
3.877
274864CRW2-WTG
Solar/Wind Harmer
3.877
972267AH1-718 GEN
Adder
2.867
276741O09 GEN1
Solar/Wind Harmer
2.448
274877BISHOP HL;1U
Solar/Wind Harmer
2.276
970169AG2-114 GEN
Solar/Wind Harmer
6.668
946321AF1-296 GEN
Solar/Wind Harmer
6.844
276726Z2-087_GEN
Solar/Wind Harmer
4.796
959341AF2-225 GEN
Solar/Wind Harmer
9.098
274853TWINGROVE;U1
Solar/Wind Harmer
4.193
274854TWINGROVE;U2
Solar/Wind Harmer
4.105
276668AB2-070 GEN1
Solar/Wind Harmer
0.856
276848AB2-070 GEN3
Solar/Wind Harmer
0.856
274723RIVER EC ;12
50/50
24.904
972179AH1-673 GEN
50/50
12.844
274751CRETE EC ;1U
50/50
5.251
274754CRETE EC ;4U
50/50
5.251
274812UNIV PK N;8U
Adder
4.891
274802UNIV PARK;5U
Adder
5.685
274674JOLIET 9 ;6U
Adder
13.349
274676JOLIET 29;8U
Adder
26.572
274732ELWOOD EC;7P
Adder
14.052
276694AA1-018 GEN2
Solar/Wind Harmer
5.353
276691AA1-018 GEN1
Solar/Wind Harmer
0.64
274861TOP CROP ;1U
Solar/Wind Harmer
5.134
276805AD2-038 GEN
Solar/Wind Harmer
4.19
941551AE2-152 GEN
Solar/Wind Harmer
3.682
276882AE2-255 GEN
Solar/Wind Harmer
2.639
274682WAUKEGAN ;7U
Adder
14.05
274828WAUKEGAN ;BP
Adder
8.614
274871GR RIDGE ;2U
Solar/Wind Harmer
5.979
274847GR RIDGE ;BU
Solar/Wind Harmer
3.932
274745AC1-111 GEN9
Adder
4.263
970569AG2-363 GEN
Solar/Wind Harmer
22.31
962781AG1-127 GEN
Solar/Wind Harmer
6.994
971997AH1-543 GEN
Solar/Wind Harmer
11.561
274872LEEDK;1U
Solar/Wind Harmer
6.011
274822ROCKFORD ;11
Adder
14.219
957471AF2-041 GEN
Solar/Wind Harmer
21.645
959081AF2-199 GEN
Solar/Wind Harmer
7.215
971067AG2-660 GEN
Solar/Wind Harmer
1.678
939401AE1-172 GEN
Solar/Wind Harmer
10.043
970819AG2-516 GEN
Solar/Wind Harmer
8.614
972207SS24-0001
Solar/Wind Harmer
15.758
274773LINCOLN ;4U
Adder
4.432
274774LINCOLN ;5U
Adder
4.432
274858EASY ROAD;U2
Solar/Wind Harmer
3.36
274761LEE CO EC;2U
Adder
6.525
274766LEE CO EC;7U
Adder
6.448
276708O09 GEN2
Solar/Wind Harmer
2.448
276646AC1-214 GEN2
Solar/Wind Harmer
0.912
274848CAMPGROVE;RU
Solar/Wind Harmer
4.316
276655WTG1_EQ
Solar/Wind Harmer
5.294
276656WTG2_EQ
Solar/Wind Harmer
0.701
939741AE1-205 GEN
Solar/Wind Harmer
12.131
274805UNIV PK N;1U
Adder
4.902
274808UNIV PK N;4U
Adder
4.87
274888KELLY CRK;1U
Solar/Wind Harmer
5.626
276776AD2-060 GEN
Solar/Wind Harmer
0.399
958011AF2-095 GEN
Solar/Wind Harmer
13.728
970941AG2-585 GEN
Solar/Wind Harmer
5.243
276893AG1-478 C
Solar/Wind Harmer
0.386
274674JOLIET 9 ;6U
Adder
13.349
958481AF2-142 GEN
Solar/Wind Harmer
12.726
958491AF2-143 GEN
Solar/Wind Harmer
12.255
276897AD1-100 C
Solar/Wind Harmer
37.712
274683WAUKEGAN ;8U
Adder
16.433
274683WAUKEGAN ;8U
Adder
13.852
276901AD2-066 C O1
Solar/Wind Harmer
2.724
276872AE1-163_GEN1
Solar/Wind Harmer
5.194
276876AE1-163_GEN2
Solar/Wind Harmer
5.194
274696ROCKY RD ;4P
Adder
8.674
274695ROCKY RD ;2P
Adder
8.474
274693ROCKY RD ;1P
Adder
8.391
274697ROCKY RD ;3P
Adder
2.302
962691AG1-118 GEN
Solar/Wind Harmer
22.146
960751AF2-366 GEN
Solar/Wind Harmer
2.11
971341AH1-150 GEN
Solar/Wind Harmer
14.43
971343AH1-151 GEN
Solar/Wind Harmer
14.43
972236AH1-702 GEN2
Adder
1.58
972235AH1-702 GEN1
Adder
1.817
274770LINCOLN ;1U
Adder
4.432
274771LINCOLN ;2U
Adder
4.432
938861AE1-114 GEN
Solar/Wind Harmer
5.786
274764LEE CO EC;5U
Adder
6.54
274765LEE CO EC;6U
Adder
6.54
274762LEE CO EC;3U
Adder
6.525
274763LEE CO EC;4U
Adder
6.464
276158O29GEN2
Solar/Wind Harmer
3.429
276157O29GEN1
Solar/Wind Harmer
2.607
276645AC1-214 GEN1
Solar/Wind Harmer
0.912
942111AE2-223 GEN
Solar/Wind Harmer
4.972
960611AF2-352 GEN
Solar/Wind Harmer
1.353
274724RIVER EC ;11
50/50
24.958
957371AF2-031 GEN
50/50
1.236
274826FISK ;BP
50/50
11.787
274752CRETE EC ;2U
50/50
5.251
274753CRETE EC ;3U
50/50
5.251
276164X3-005 C
Solar/Wind Harmer
0.814
972231SS25-0005
Solar/Wind Harmer
9.609
972181SS23-001
Solar/Wind Harmer
6.006
972038AH1-567 GEN2
Adder
0.365
274814UNIV PK N;0U
Adder
4.934
274807UNIV PK N;3U
Adder
4.923
274811UNIV PK N;7U
Adder
4.891
274803UNIV PARK;6U
Adder
5.685
274887GEN-1.85
Solar/Wind Harmer
5.079
276772AC2-154 GEN
Solar/Wind Harmer
2.66
276843GEN-1.7
Solar/Wind Harmer
0.547
276806AD2-047 C O1
Solar/Wind Harmer
10.198
274676JOLIET 29;8U
Adder
25.623
274730ELWOOD EC;6P
Adder
14.052
274734ELWOOD EC;8P
Adder
14.052
274736ELWOOD EC;9P
Adder
14.052
274729ELWOOD EC;1P
Adder
14.045
274862TOP CROP ;2U
Solar/Wind Harmer
4.287
939351AE1-166 GEN
Solar/Wind Harmer
4.815
972259AH1-714 GEN
Adder
15.049
276868AE1-113 GEN
Solar/Wind Harmer
7.918
274879MINONK ;1U
Solar/Wind Harmer
5.279
274682WAUKEGAN ;7U
Adder
14.05
970571AG2-364 GEN
Solar/Wind Harmer
14.873
943121AE2-341 GEN
Solar/Wind Harmer
11.108
943591AF1-030 GEN
Solar/Wind Harmer
7.405
276799AD1-013 GEN
Solar/Wind Harmer
1.599
946671AF1-331 GEN
Solar/Wind Harmer
0.303
274855GSG-6 ;RU
Solar/Wind Harmer
2.67
274850MENDOTA H;RU
Solar/Wind Harmer
1.856
276602WESTBROOK C
Solar/Wind Harmer
1.537
959091AF2-200 GEN
Solar/Wind Harmer
14.43
970707AG2-453 GEN
Solar/Wind Harmer
20.121
274772LINCOLN ;3U
Adder
4.432
274857EASY ROAD;U1
Solar/Wind Harmer
3.36
274760LEE CO EC;1U
Adder
6.525
274767LEE CO EC;8U
Adder
6.448
276603SUBLETTE C
Solar/Wind Harmer
0.732
274851PROVIDENC;RU
Solar/Wind Harmer
1.939
274849CRESCENT ;1U
Solar/Wind Harmer
1.259
276782AC1-033 GEN
Solar/Wind Harmer
2.69
274878BISHOP HL;2U
Solar/Wind Harmer
2.276
965931AG1-462 GEN
Solar/Wind Harmer
16.567
971087AG2-675 GEN
Solar/Wind Harmer
2.417
965091AG1-374 GEN
Solar/Wind Harmer
17.459
959611AF2-252 GEN
Solar/Wind Harmer
1.353
276849AB2-070 GEN2
Solar/Wind Harmer
0.856
990577J1339
External Queue
22.734174728393555
990647J1355
External Queue
44.96687698364258
991247J1684 G
External Queue
28.59419822692871
990582J1340
External Queue
22.734174728393555
990662J1358
External Queue
17.028202056884766
991337J1802
External Queue
10.868167877197266
990552J1334 G
External Queue
34.31124496459961
990562J1336 G
External Queue
34.31124496459961
990762J1386
External Queue
10.402408599853516
991332J1785
External Queue
14.41087818145752
990547J1333 G
External Queue
34.31124496459961
990557J1335 G
External Queue
34.31124496459961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.102
NYPJM->LTFIMP_NY
CLTF
0.72
WECLTFEXP_WEC->PJM
CLTF
2.802
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.953
MECLTFEXP_MEC->PJM
CLTF
8.963
SIGELTFEXP_SIGE->PJM
CLTF
0.036
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.229
AG2-052LTFEXP_AG2-052->PJM
LTF
0.534
AH1-155LTFEXP_AH1-155->PJM
LTF
0.801
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.798
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.115
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.247
LAGNLTFEXP_LAGN->PJM
CLTF
3.359
TVALTFEXP_TVA->PJM
CLTF
0.976

Details for 19MON12-02LALLENDORF 345.0 kV Ckt 1 line l/o ATSI_P7-1_TE-345-025T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:ATSI/ITCT
Facility Description:
19MON12-02LALLENDORF 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_TE-345-025T_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:122.24 %
Rating:1660.0 MVA
Rating Type:B
MVA to Mitigate:2029.25
MW Contribution:
7.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
247604X1-042
50/50
0.024
24441205WTRV SLR C
Solar/Wind Harmer
0.125
270449AD2-020 GEN
Solar/Wind Harmer
2.349
943021AE2-325 GEN
Solar/Wind Harmer
3.052
957891AF2-083 GEN
Solar/Wind Harmer
11.862
945111AF1-176 GEN
Solar/Wind Harmer
14.073
270216AD2-079_GEN
Solar/Wind Harmer
0.431
24639705ELKHART HY
Adder
0.108
970373AG2-245 GEN
Solar/Wind Harmer
12.759
270055AF2-134 C O1
Solar/Wind Harmer
1.782
274751CRETE EC ;1U
Adder
2.82
274754CRETE EC ;4U
Adder
2.82
958381AF2-132 GEN
Solar/Wind Harmer
5.173
274723RIVER EC ;12
Adder
10.198
964861AG1-349 GEN
Solar/Wind Harmer
4.467
971917AH1-482 GEN
Solar/Wind Harmer
5.154
274812UNIV PK N;8U
Adder
2.834
274802UNIV PARK;5U
Adder
3.243
972207SS24-0001
Solar/Wind Harmer
12.118
274773LINCOLN ;4U
Adder
3.408
274774LINCOLN ;5U
Adder
3.408
274676JOLIET 29;8U
Adder
16.733
940581AE2-045 GEN
Solar/Wind Harmer
5.547
971605AH1-302 GEN
Solar/Wind Harmer
4.743
274732ELWOOD EC;7P
Adder
8.938
274674JOLIET 9 ;6U
Adder
8.372
941551AE2-152 GEN
Solar/Wind Harmer
2.464
274871GR RIDGE ;2U
Solar/Wind Harmer
4.144
274847GR RIDGE ;BU
Solar/Wind Harmer
2.725
274745AC1-111 GEN9
Adder
2.992
276694AA1-018 GEN2
Solar/Wind Harmer
3.375
276691AA1-018 GEN1
Solar/Wind Harmer
0.403
274861TOP CROP ;1U
Solar/Wind Harmer
3.24
274682WAUKEGAN ;7U
Adder
9.536
274828WAUKEGAN ;BP
Adder
5.853
276805AD2-038 GEN
Solar/Wind Harmer
2.707
962781AG1-127 GEN
Solar/Wind Harmer
4.989
276882AE2-255 GEN
Solar/Wind Harmer
1.767
274872LEEDK;1U
Solar/Wind Harmer
4.297
939401AE1-172 GEN
Solar/Wind Harmer
7.285
971997AH1-543 GEN
Solar/Wind Harmer
8.198
957471AF2-041 GEN
Solar/Wind Harmer
15.483
959081AF2-199 GEN
Solar/Wind Harmer
5.161
971067AG2-660 GEN
Solar/Wind Harmer
1.2
274822ROCKFORD ;11
Adder
10.104
970819AG2-516 GEN
Solar/Wind Harmer
6.145
970569AG2-363 GEN
Solar/Wind Harmer
15.36
274761LEE CO EC;2U
Adder
4.711
274766LEE CO EC;7U
Adder
4.656
241885AC2-103 GEN1
Solar/Wind Helper
2.234
241807AE2-176_GEN
Solar/Wind Helper
1.462
960841AF2-375 GEN
Solar/Wind Helper
1.14
241840AF1-064_GEN
Solar/Wind Helper
0.697
961051AF2-396 GEN
Solar/Wind Harmer
13.012
961051AF2-396 GEN
Solar/Wind Harmer
6.052
247620Y3-023
Adder
0.313
965681AG1-436 GEN
Solar/Wind Harmer
8.192
965791AG1-447 GEN
Solar/Wind Harmer
4.191
970349AG2-230 GEN
Solar/Wind Harmer
9.573
270535AF1-215 GEN1
Solar/Wind Harmer
2.673
270536AF1-215 GEN2
Solar/Wind Harmer
2.673
274805UNIV PK N;1U
Adder
2.84
274808UNIV PK N;4U
Adder
2.821
274888KELLY CRK;1U
Solar/Wind Harmer
3.255
276776AD2-060 GEN
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
7.943
970941AG2-585 GEN
Solar/Wind Harmer
3.034
274770LINCOLN ;1U
Adder
3.408
274771LINCOLN ;2U
Adder
3.408
276893AG1-478 C
Solar/Wind Harmer
0.238
274674JOLIET 9 ;6U
Adder
8.372
276897AD1-100 C
Solar/Wind Harmer
25.237
958481AF2-142 GEN
Solar/Wind Harmer
8.022
274696ROCKY RD ;4P
Adder
6.042
274695ROCKY RD ;2P
Adder
5.902
274693ROCKY RD ;1P
Adder
5.844
274697ROCKY RD ;3P
Adder
1.603
274683WAUKEGAN ;8U
Adder
11.167
274683WAUKEGAN ;8U
Adder
9.413
958491AF2-143 GEN
Solar/Wind Harmer
7.92
962691AG1-118 GEN
Solar/Wind Harmer
15.774
276901AD2-066 C O1
Solar/Wind Harmer
1.841
960751AF2-366 GEN
Solar/Wind Harmer
1.505
276872AE1-163_GEN1
Solar/Wind Harmer
3.482
276876AE1-163_GEN2
Solar/Wind Harmer
3.482
945421AF1-207 GEN
Solar/Wind Harmer
7.282
957841AF2-078 GEN
Solar/Wind Harmer
3.135
971341AH1-150 GEN
Solar/Wind Harmer
10.322
971343AH1-151 GEN
Solar/Wind Harmer
10.322
972235AH1-702 GEN1
Adder
1.295
972236AH1-702 GEN2
Adder
1.126
274764LEE CO EC;5U
Adder
4.722
274765LEE CO EC;6U
Adder
4.722
274762LEE CO EC;3U
Adder
4.711
274763LEE CO EC;4U
Adder
4.667
241996AE2-282_GEN
Solar/Wind Helper
0.855
241808AF1-120 C
Solar/Wind Helper
0.478
938861AE1-114 GEN
Solar/Wind Harmer
0.668
270505AE1-170 C O1
Solar/Wind Harmer
11.986
945111AF1-176 GEN
Solar/Wind Harmer
4.46
247643Z2-116 C
Solar/Wind Harmer
0.05
24441505OLIV SLR
Solar/Wind Harmer
0.093
971347AH1-153 GEN
Solar/Wind Harmer
3.191
270063AE2-323 C
Solar/Wind Harmer
1.278
972231SS25-0005
Solar/Wind Harmer
5.475
972181SS23-001
Solar/Wind Harmer
3.422
274752CRETE EC ;2U
Adder
2.82
274753CRETE EC ;3U
Adder
2.82
964401AG1-302 GEN
Solar/Wind Harmer
5.173
274724RIVER EC ;11
Adder
10.076
274814UNIV PK N;0U
Adder
2.859
274807UNIV PK N;3U
Adder
2.852
274811UNIV PK N;7U
Adder
2.834
276164X3-005 C
Solar/Wind Harmer
0.395
274803UNIV PARK;6U
Adder
3.243
274826FISK ;BP
Adder
6.072
972038AH1-567 GEN2
Adder
0.202
274887GEN-1.85
Solar/Wind Harmer
2.939
276772AC2-154 GEN
Solar/Wind Harmer
1.539
276843GEN-1.7
Solar/Wind Harmer
0.316
276806AD2-047 C O1
Solar/Wind Harmer
5.901
274772LINCOLN ;3U
Adder
3.408
274676JOLIET 29;8U
Adder
16.135
972259AH1-714 GEN
Adder
10.402
274729ELWOOD EC;1P
Adder
8.938
274730ELWOOD EC;6P
Adder
8.938
274734ELWOOD EC;8P
Adder
8.938
274736ELWOOD EC;9P
Adder
8.938
939351AE1-166 GEN
Solar/Wind Harmer
3.222
970707AG2-453 GEN
Solar/Wind Harmer
15.201
943121AE2-341 GEN
Solar/Wind Harmer
8.021
943591AF1-030 GEN
Solar/Wind Harmer
5.348
274862TOP CROP ;2U
Solar/Wind Harmer
2.705
274682WAUKEGAN ;7U
Adder
9.536
276868AE1-113 GEN
Solar/Wind Harmer
5.302
274879MINONK ;1U
Solar/Wind Harmer
3.535
276799AD1-013 GEN
Solar/Wind Harmer
1.147
946671AF1-331 GEN
Solar/Wind Harmer
0.217
274855GSG-6 ;RU
Solar/Wind Harmer
1.915
274850MENDOTA H;RU
Solar/Wind Harmer
1.332
276602WESTBROOK C
Solar/Wind Harmer
1.103
959091AF2-200 GEN
Solar/Wind Harmer
10.322
970571AG2-364 GEN
Solar/Wind Harmer
10.24
274760LEE CO EC;1U
Adder
4.711
274767LEE CO EC;8U
Adder
4.656
241832AE2-181_GEN
Solar/Wind Helper
0.386
971549AH1-272 GEN
Solar/Wind Harmer
22.651
944161AF1-084 GEN
Solar/Wind Harmer
1.91
971771AH1-392 GEN
Solar/Wind Harmer
6.457
270526AF1-158 GEN
Solar/Wind Harmer
3.184
960681AF2-359 GEN
Solar/Wind Harmer
2.476
970031AG2-029 GEN
Solar/Wind Harmer
14.816
958391AF2-133 GEN
Solar/Wind Harmer
5.083
972037AH1-567 GEN1
Adder
0.102
274827FISK ;RP
Adder
4.303
274800UNIV PARK;3U
Adder
3.225
274801UNIV PARK;4U
Adder
3.225
959141AF2-205 GEN
Solar/Wind Harmer
3.344
960591AF2-350 GEN
Solar/Wind Harmer
5.516
274775LINCOLN ;6U
Adder
3.408
274776LINCOLN ;7U
Adder
3.408
274777LINCOLN ;8U
Adder
3.408
972228AH1-698 GEN2
Adder
2.034
972227AH1-698 GEN1
Adder
1.432
274687WILL CNTY;4U
Adder
15.287
274687WILL CNTY;4U
Adder
15.287
274675JOLIET 29;7U
Adder
16.733
274675JOLIET 29;7U
Adder
16.135
276893AG1-478 C
Solar/Wind Harmer
0.299
274728ELWOOD EC;5P
Adder
8.938
274731ELWOOD EC;2P
Adder
8.938
274733ELWOOD EC;3P
Adder
8.938
274735ELWOOD EC;4P
Adder
8.938
970833AG2-524 GEN
Solar/Wind Harmer
4.709
970833AG2-524 GEN
Solar/Wind Harmer
2.19
274744AC1-111 GEN8
Adder
2.992
274746AC1-111 G10
Adder
2.992
970073AG2-061 GEN
Solar/Wind Harmer
1.228
971411AH1-196 GEN
Solar/Wind Harmer
7.796
971675AH1-338 GEN
Solar/Wind Harmer
9.341
276861AD2-134 GEN
Solar/Wind Harmer
0.926
276863AD2-134 GEN
Solar/Wind Harmer
0.926
276889AE2-281 GEN
Solar/Wind Harmer
0.995
971171AH1-044 GEN
Solar/Wind Harmer
10.322
274863CRW1-WTG
Solar/Wind Harmer
2.875
274864CRW2-WTG
Solar/Wind Harmer
2.875
274823ROCKFORD ;21
Adder
10.031
274856ECOGROVE ;U1
Solar/Wind Harmer
1.724
276611AD2-172 GEN
Solar/Wind Harmer
1.308
276612AE2-035 GEN
Solar/Wind Harmer
1.308
926823AC1-168 GEN
Solar/Wind Harmer
2.192
971681AH1-341 GEN
Solar/Wind Harmer
7.625
972267AH1-718 GEN
Adder
2.089
241886AC2-103 GEN2
Solar/Wind Helper
2.234
945641AF1-229 GEN
Solar/Wind Helper
1.133
270499AE1-146 GEN
Solar/Wind Helper
1.718
945411AF1-206 GEN
Solar/Wind Helper
1.615
991182J1586 G
External Queue
63.8489990234375
991227J1663 G
External Queue
13.66822624206543
990527J1329
External Queue
5.053378105163574
990142J1224
External Queue
36.94019317626953
NYPJM->LTFIMP_NY
CLTF
1.052
LGEELTFEXP_LGEE->PJM
CLTF
1.561
WECLTFEXP_WEC->PJM
CLTF
1.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
176.866
CPLELTFEXP_CPLE->PJM
CLTF
0.409
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.998
MECLTFEXP_MEC->PJM
CLTF
7.323
SIGELTFEXP_SIGE->PJM
CLTF
0.15
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.191
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.541
LAGNLTFEXP_LAGN->PJM
CLTF
4.922
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.087
TVALTFEXP_TVA->PJM
CLTF
2.098

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_116_GG-345R__2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.01 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:1837.1
MW Contribution:
19.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972267AH1-718 GEN
50/50
9.139
274701CORDOVA ;1S
50/50
1.71
274700CORDOVA ;2C
50/50
1.525
971171AH1-044 GEN
Solar/Wind Harmer
92.51
276741O09 GEN1
Solar/Wind Harmer
5.582
946321AF1-296 GEN
Solar/Wind Harmer
15.347
971681AH1-341 GEN
Solar/Wind Harmer
19.531
274856ECOGROVE ;U1
Solar/Wind Harmer
3.131
276611AD2-172 GEN
Solar/Wind Harmer
2.375
276612AE2-035 GEN
Solar/Wind Harmer
2.375
274877BISHOP HL;1U
Solar/Wind Harmer
2.5
274823ROCKFORD ;21
Adder
12.826
276861AD2-134 GEN
Solar/Wind Harmer
1.16
276863AD2-134 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
11.486
274717NELSON EC;2C
50/50
2.312
274718NELSON EC;2S
50/50
1.69
274764LEE CO EC;5U
50/50
15.562
274765LEE CO EC;6U
50/50
15.562
274762LEE CO EC;3U
50/50
15.525
274763LEE CO EC;4U
50/50
15.379
971341AH1-150 GEN
Solar/Wind Harmer
92.51
971343AH1-151 GEN
Solar/Wind Harmer
92.51
276158O29GEN2
Solar/Wind Harmer
7.818
276157O29GEN1
Solar/Wind Harmer
5.944
938861AE1-114 GEN
Solar/Wind Harmer
10.268
972235AH1-702 GEN1
Adder
2.061
972236AH1-702 GEN2
Adder
1.788
276645AC1-214 GEN1
Solar/Wind Harmer
0.808
274761LEE CO EC;2U
50/50
15.525
274766LEE CO EC;7U
50/50
15.342
274663QUAD CITI;2U
50/50
8.679
957471AF2-041 GEN
Solar/Wind Harmer
138.765
959081AF2-199 GEN
Solar/Wind Harmer
46.255
971067AG2-660 GEN
Solar/Wind Harmer
10.757
274858EASY ROAD;U2
Solar/Wind Harmer
7.534
276708O09 GEN2
Solar/Wind Harmer
5.582
970819AG2-516 GEN
Solar/Wind Harmer
9.402
274848CAMPGROVE;RU
Solar/Wind Harmer
4.269
274822ROCKFORD ;11
Adder
12.917
276646AC1-214 GEN2
Solar/Wind Harmer
0.808
274715NELSON EC;1C
50/50
2.312
274716NELSON EC;1S
50/50
1.69
274760LEE CO EC;1U
50/50
15.525
274767LEE CO EC;8U
50/50
15.342
274699CORDOVA ;1C
50/50
1.525
274662QUAD CITI;1U
50/50
8.633
959091AF2-200 GEN
Solar/Wind Harmer
92.51
274857EASY ROAD;U1
Solar/Wind Harmer
7.534
276603SUBLETTE C
Solar/Wind Harmer
1.614
965931AG1-462 GEN
Solar/Wind Harmer
38.274
971087AG2-675 GEN
Solar/Wind Harmer
5.585
276782AC1-033 GEN
Solar/Wind Harmer
2.956
274878BISHOP HL;2U
Solar/Wind Harmer
2.5
274855GSG-6 ;RU
Solar/Wind Harmer
2.399
274850MENDOTA H;RU
Solar/Wind Harmer
1.668
276602WESTBROOK C
Solar/Wind Harmer
1.381
276799AD1-013 GEN
Solar/Wind Harmer
1.378
946671AF1-331 GEN
Solar/Wind Harmer
0.261
274851PROVIDENC;RU
Solar/Wind Harmer
1.719
274849CRESCENT ;1U
Solar/Wind Harmer
1.116
991092J1477
External Queue
5.438872814178467
NYPJM->LTFIMP_NY
CLTF
0.198
WECLTFEXP_WEC->PJM
CLTF
0.814
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.843
CPLELTFEXP_CPLE->PJM
CLTF
0.164
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.459
MECLTFEXP_MEC->PJM
CLTF
12.479
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.545
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.115
LAGNLTFEXP_LAGN->PJM
CLTF
3.872
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.861
TVALTFEXP_TVA->PJM
CLTF
1.125

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.82 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2406.35
MW Contribution:
7.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.374
24729305KEY G2
50/50
0.367
24729205KEY G1
50/50
0.366
247620Y3-023
50/50
0.467
960851AF2-376 GEN
50/50
2.095
24643105BUCHANAN
50/50
0.01
270246TR4_N_V150
Solar/Wind Harmer
0.046
270247TR4_N_V136
Solar/Wind Harmer
0.046
942221AE2-234 GEN
Solar/Wind Harmer
2.855
944231AF1-091 GEN
Solar/Wind Harmer
16.139
944541AF1-119 GEN
Solar/Wind Harmer
0.427
960971AF2-388 GEN
Solar/Wind Harmer
3.752
970349AG2-230 GEN
Solar/Wind Harmer
8.78
961051AF2-396 GEN
Solar/Wind Harmer
11.674
961051AF2-396 GEN
Solar/Wind Harmer
7.782
270031AE2-169
Solar/Wind Harmer
3.104
270599AE1-208 GEN
Solar/Wind Harmer
5.173
965681AG1-436 GEN
Solar/Wind Harmer
6.963
965791AG1-447 GEN
Solar/Wind Harmer
5.106
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.41
247621Y3-024
Adder
0.183
274805UNIV PK N;1U
Adder
3.801
274808UNIV PK N;4U
Adder
3.776
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
6.365
274771LINCOLN ;2U
Adder
6.365
274888KELLY CRK;1U
Solar/Wind Harmer
0.304
276776AD2-060 GEN
Solar/Wind Harmer
0.555
958011AF2-095 GEN
Solar/Wind Harmer
7.498
970941AG2-585 GEN
Solar/Wind Harmer
2.864
276897AD1-100 C
Solar/Wind Harmer
12.887
274674JOLIET 9 ;6U
Adder
11.348
276893AG1-478 C
Solar/Wind Harmer
0.343
970291AG2-192 GEN
Solar/Wind Harmer
0.666
970291AG2-192 GEN
Solar/Wind Harmer
0.308
971613AH1-306 GEN
Solar/Wind Harmer
2.442
958481AF2-142 GEN
Solar/Wind Harmer
7.57
274695ROCKY RD ;2P
Adder
8.016
274693ROCKY RD ;1P
Adder
7.937
274697ROCKY RD ;3P
Adder
2.178
274696ROCKY RD ;4P
Adder
8.205
274683WAUKEGAN ;8U
Adder
15.145
274683WAUKEGAN ;8U
Adder
12.766
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
14.951
958491AF2-143 GEN
Solar/Wind Harmer
7.476
276901AD2-066 C O1
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
9.768
971343AH1-151 GEN
Solar/Wind Harmer
9.768
972235AH1-702 GEN1
Adder
1.755
972236AH1-702 GEN2
Adder
1.526
938861AE1-114 GEN
Solar/Wind Harmer
2.722
274764LEE CO EC;5U
Adder
6.396
274765LEE CO EC;6U
Adder
6.396
274762LEE CO EC;3U
Adder
6.381
274763LEE CO EC;4U
Adder
6.321
24725505WLD G2 C
Solar/Wind Harmer
0
24699105WLD G1 C
Solar/Wind Harmer
0
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.763
276645AC1-214 GEN1
Solar/Wind Harmer
0.185
24387305FR-4G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.533
942111AE2-223 GEN
Solar/Wind Harmer
1.513
960611AF2-352 GEN
Solar/Wind Harmer
1.525
926881AC1-175 GEN
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
4.481
970885AG2-551 GEN
Solar/Wind Harmer
1.494
970241AG2-163 GEN
Solar/Wind Harmer
2.581
270383AD1-128 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
0.044
276838X2-022 GEN2
Solar/Wind Harmer
0.239
276916AD2-100_GEN
Solar/Wind Harmer
8.532
276911AD2-131_GEN
Solar/Wind Harmer
0.562
945391AF1-204 GEN
Solar/Wind Harmer
4.219
970623AG2-406 GEN
Solar/Wind Harmer
0.656
971587AH1-292 GEN
Solar/Wind Harmer
2.468
247607V1-011 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Helper
10.897
270462AD2-086
Solar/Wind Helper
3.747
247522W1-056 GEN
Solar/Wind Helper
1.177
253378AE2-206_GEN
Solar/Wind Helper
0.715
270349AD2-093_GEN
Solar/Wind Helper
0.857
270471AD2-092_GEN
Solar/Wind Helper
0.857
241960AC2-195 GEN
Solar/Wind Helper
0.697
24727005RPMNG1
50/50
3.317
960861AF2-377 GEN
50/50
2.406
970521AG2-332 GEN
50/50
10.906
24639705ELKHART HY
50/50
0.151
270143AC1-141 CT2_
50/50
2.029
965421AG1-410 GEN
Solar/Wind Harmer
81.797
965011AG1-365 GEN
Solar/Wind Harmer
13.822
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.876
958861AF2-177 GEN
Solar/Wind Harmer
2.694
945111AF1-176 GEN
Solar/Wind Harmer
10.683
957891AF2-083 GEN
Solar/Wind Harmer
9.802
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3
970373AG2-245 GEN
Solar/Wind Harmer
11.243
274751CRETE EC ;1U
Adder
6.312
274754CRETE EC ;4U
Adder
6.312
274723RIVER EC ;12
Adder
13.681
274812UNIV PK N;8U
Adder
3.792
270055AF2-134 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
6.365
274774LINCOLN ;5U
Adder
6.365
274802UNIV PARK;5U
Adder
4.369
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.75
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.662
274674JOLIET 9 ;6U
Adder
11.348
274732ELWOOD EC;7P
Adder
12.11
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
6.364
270594AE1-207 GEN
Solar/Wind Harmer
5.699
270032AE2-172
Solar/Wind Harmer
3.392
270005AE1-210 C O1
Solar/Wind Harmer
1.101
274745AC1-111 GEN9
Adder
4.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.82
274861TOP CROP ;1U
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
1.788
274682WAUKEGAN ;7U
Adder
12.933
274828WAUKEGAN ;BP
Adder
7.939
276805AD2-038 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
4.731
939401AE1-172 GEN
Solar/Wind Harmer
3.718
274872LEEDK;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.578
971997AH1-543 GEN
Solar/Wind Harmer
2.59
957471AF2-041 GEN
Solar/Wind Harmer
14.651
959081AF2-199 GEN
Solar/Wind Harmer
4.884
971067AG2-660 GEN
Solar/Wind Harmer
1.628
274822ROCKFORD ;11
Adder
13.696
276903AD2-071 C
Solar/Wind Harmer
5.426
970819AG2-516 GEN
Solar/Wind Harmer
5.809
970569AG2-363 GEN
Solar/Wind Harmer
14.512
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
6.381
274766LEE CO EC;7U
Adder
6.306
276708O09 GEN2
Solar/Wind Harmer
0.167
276646AC1-214 GEN2
Solar/Wind Harmer
0.185
24385905FR-11G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
6.519
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.287
963741AG1-226 GEN
Solar/Wind Harmer
10.473
276621W2-048 GEN
Solar/Wind Harmer
0.213
965911AG1-460 GEN
Solar/Wind Harmer
0.82
24728605AND G2
Adder
2.099
970773AG2-487 GEN
Solar/Wind Harmer
0.63
246936BC-WTG1
Solar/Wind Helper
10.897
270317AD1-130_GEN
Solar/Wind Helper
4.143
270485AE1-090_GEN
Solar/Wind Helper
0.326
270391AF1-285 GEN3
Solar/Wind Helper
0.593
270578AF1-285 GEN2
Solar/Wind Helper
0.593
270286AF1-227 GEN2
Solar/Wind Helper
0.694
960841AF2-375 GEN
Solar/Wind Helper
1.179
965431AG1-411 GEN
50/50
45.443
24727105RPMNG2
50/50
3.318
970583AG2-370 GEN
50/50
2.814
270142AC1-141 CT1_
50/50
2.029
24642205MAYFLWER
50/50
0.031
965021AG1-366 GEN
Solar/Wind Harmer
4.607
270043AE2-236 GEN
Solar/Wind Harmer
5.241
270063AE2-323 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
31.981
24695305TIMB G C
Solar/Wind Harmer
0.532
945111AF1-176 GEN
Solar/Wind Harmer
4.853
971347AH1-153 GEN
Solar/Wind Harmer
2.927
270505AE1-170 C O1
Solar/Wind Harmer
6.132
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
8.345
274752CRETE EC ;2U
Adder
6.312
274753CRETE EC ;3U
Adder
6.312
274724RIVER EC ;11
Adder
13.515
274814UNIV PK N;0U
Adder
3.826
274807UNIV PK N;3U
Adder
3.817
274811UNIV PK N;7U
Adder
3.792
274772LINCOLN ;3U
Adder
6.365
274803UNIV PARK;6U
Adder
4.369
274826FISK ;BP
Adder
8.195
972038AH1-567 GEN2
Adder
0.273
274887GEN-1.85
Solar/Wind Harmer
0.135
276843GEN-1.7
Solar/Wind Harmer
0.168
276806AD2-047 C O1
Solar/Wind Harmer
2.951
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
14.153
970707AG2-453 GEN
Solar/Wind Harmer
16.903
247642Z2-115 C
Solar/Wind Harmer
0.002
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.852
274729ELWOOD EC;1P
Adder
12.11
274730ELWOOD EC;6P
Adder
12.11
274734ELWOOD EC;8P
Adder
12.11
274736ELWOOD EC;9P
Adder
12.11
970289AG2-191 GEN
Solar/Wind Harmer
0.564
946031AF1-268 GEN
Solar/Wind Harmer
4.838
943121AE2-341 GEN
Solar/Wind Harmer
8.518
943591AF1-030 GEN
Solar/Wind Harmer
5.665
270004AE1-209 GEN
Solar/Wind Harmer
1.101
274862TOP CROP ;2U
Solar/Wind Harmer
0.681
970825AG2-519 GEN
Solar/Wind Harmer
3.795
274682WAUKEGAN ;7U
Adder
12.933
276868AE1-113 GEN
Solar/Wind Harmer
0.991
274879MINONK ;1U
Solar/Wind Harmer
0.207
946671AF1-331 GEN
Solar/Wind Harmer
0.524
274855GSG-6 ;RU
Solar/Wind Harmer
0.179
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
24690905MDL-1G C
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
4.895
959091AF2-200 GEN
Solar/Wind Harmer
9.768
970571AG2-364 GEN
Solar/Wind Harmer
9.675
274857EASY ROAD;U1
Solar/Wind Harmer
0
274760LEE CO EC;1U
Adder
6.381
274767LEE CO EC;8U
Adder
6.306
24386205FR-12G C
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.157
965091AG1-374 GEN
Solar/Wind Harmer
13.726
965931AG1-462 GEN
Solar/Wind Harmer
11.666
971087AG2-675 GEN
Solar/Wind Harmer
2.44
959611AF2-252 GEN
Solar/Wind Harmer
1.525
24379505HDWTR1G C
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.998
957381AF2-032 GEN
Solar/Wind Harmer
0.932
942481AE2-261 GEN
Solar/Wind Harmer
12.255
970193AG2-126 GEN
Solar/Wind Harmer
5.956
24728705AND G3
Adder
4.39
24728505AND G1
Adder
2.099
246938BC-WTG3
Solar/Wind Helper
11.083
942871AE2-306 GEN
Solar/Wind Helper
0.445
270284AF1-227 GEN1
Solar/Wind Helper
1.893
270287AF1-227 GEN3
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.334
270541AE2-072 C
Solar/Wind Helper
0.943
24727205RPMNG3
50/50
3.298
24729505KEY G4
50/50
6.847
24653605MOTTVILLE
50/50
0.004
24641605TWIN BRNCH
50/50
0.015
270144AC1-141 ST1_
50/50
1.792
959331AF2-224 GEN
Solar/Wind Harmer
9.676
963791AG1-232 GEN
Solar/Wind Harmer
12.035
970031AG2-029 GEN
Solar/Wind Harmer
4.587
965041AG1-368 GEN
Solar/Wind Harmer
8.443
270071AF1-092 GEN
Solar/Wind Harmer
14.566
247521TR3_G114
Solar/Wind Harmer
0.261
965051AG1-369 GEN
Solar/Wind Harmer
3.602
971771AH1-392 GEN
Solar/Wind Harmer
5.907
945581AF1-223 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
0.922
960681AF2-359 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.13
274775LINCOLN ;6U
Adder
6.365
274776LINCOLN ;7U
Adder
6.365
274777LINCOLN ;8U
Adder
6.365
972037AH1-567 GEN1
Adder
0.137
274827FISK ;RP
Adder
5.808
274800UNIV PARK;3U
Adder
4.357
274801UNIV PARK;4U
Adder
4.357
960591AF2-350 GEN
Solar/Wind Harmer
5.207
972228AH1-698 GEN2
Adder
2.756
972227AH1-698 GEN1
Adder
1.941
274687WILL CNTY;4U
Adder
20.685
274687WILL CNTY;4U
Adder
20.685
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.662
274675JOLIET 29;7U
Adder
21.853
274728ELWOOD EC;5P
Adder
12.11
274731ELWOOD EC;2P
Adder
12.11
274733ELWOOD EC;3P
Adder
12.11
274735ELWOOD EC;4P
Adder
12.11
959141AF2-205 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.974
970833AG2-524 GEN
Solar/Wind Harmer
5.628
970833AG2-524 GEN
Solar/Wind Harmer
3.752
971611AH1-305 GEN
Solar/Wind Harmer
3.031
274744AC1-111 GEN8
Adder
4.068
274746AC1-111 G10
Adder
4.068
970073AG2-061 GEN
Solar/Wind Harmer
1.661
247536S-71 GEN
Solar/Wind Harmer
0.199
971411AH1-196 GEN
Solar/Wind Harmer
7.376
971675AH1-338 GEN
Solar/Wind Harmer
1.916
276861AD2-134 GEN
Solar/Wind Harmer
0.088
276863AD2-134 GEN
Solar/Wind Harmer
0.088
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.768
274823ROCKFORD ;21
Adder
13.596
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
926823AC1-168 GEN
Solar/Wind Harmer
0.821
970169AG2-114 GEN
Solar/Wind Harmer
4.823
971681AH1-341 GEN
Solar/Wind Harmer
7.736
971549AH1-272 GEN
Solar/Wind Harmer
9.898
972267AH1-718 GEN
Adder
2.828
276741O09 GEN1
Solar/Wind Harmer
0.167
24386405FR-21G C
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.157
276726Z2-087_GEN
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.889
946321AF1-296 GEN
Solar/Wind Harmer
2.577
274854TWINGROVE;U2
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.976
270543AE2-219 C
Solar/Wind Harmer
3.137
276668AB2-070 GEN1
Solar/Wind Harmer
0.17
276848AB2-070 GEN3
Solar/Wind Harmer
0.169
276849AB2-070 GEN2
Solar/Wind Harmer
0.17
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
5.928
944221AF1-090 GEN
Solar/Wind Harmer
2.312
270356AE2-297 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
957201AF2-014 GEN
Solar/Wind Helper
8.609
270223U2-072_GEN1
Solar/Wind Helper
0.876
270224U2-072_GEN2
Solar/Wind Helper
0.876
270227U2-072_GEN3
Solar/Wind Helper
0.876
270228U2-072_GEN4
Solar/Wind Helper
0.876
270231U2-072_GEN5
Solar/Wind Helper
0.876
966831AG1-554 GEN
Solar/Wind Helper
0.882
270499AE1-146 GEN
Solar/Wind Helper
1.968
945641AF1-229 GEN
Solar/Wind Helper
0.94
990792J1392
External Queue
5.487830638885498
990497J1323
External Queue
1.5952997207641602
NYPJM->LTFIMP_NY
CLTF
1.264
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.656
CBM West 1LTFEXP_CBM-W1->PJM
CBM
70.253
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.933
MECLTFEXP_MEC->PJM
CLTF
9.784
SIGELTFEXP_SIGE->PJM
CLTF
0.201
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042
AG2-052LTFEXP_AG2-052->PJM
LTF
0.172
AH1-155LTFEXP_AH1-155->PJM
LTF
0.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.835
LAGNLTFEXP_LAGN->PJM
CLTF
5.801
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.51
TVALTFEXP_TVA->PJM
CLTF
2.319

Details for COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line l/o COMED_P4_167-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_167-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.28 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1546.53
MW Contribution:
11.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
276658THREERVRS;U1
50/50
5.687
274729ELWOOD EC;1P
Adder
15.511
274730ELWOOD EC;6P
Adder
15.451
274734ELWOOD EC;8P
Adder
15.451
274736ELWOOD EC;9P
Adder
15.451
274676JOLIET 29;8U
Adder
26.473
274682WAUKEGAN ;7U
Adder
15.332
943121AE2-341 GEN
Solar/Wind Harmer
12.432
943591AF1-030 GEN
Solar/Wind Harmer
8.288
276868AE1-113 GEN
Solar/Wind Harmer
8.364
274879MINONK ;1U
Solar/Wind Harmer
5.576
276799AD1-013 GEN
Solar/Wind Harmer
1.78
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
2.971
274850MENDOTA H;RU
Solar/Wind Harmer
2.066
276602WESTBROOK C
Solar/Wind Harmer
1.71
959091AF2-200 GEN
Solar/Wind Harmer
15.979
970571AG2-364 GEN
Solar/Wind Harmer
15.828
274857EASY ROAD;U1
Solar/Wind Harmer
3.728
274760LEE CO EC;1U
Adder
7.239
274767LEE CO EC;8U
Adder
7.154
276603SUBLETTE C
Solar/Wind Harmer
0.809
970707AG2-453 GEN
Solar/Wind Harmer
20.548
276782AC1-033 GEN
Solar/Wind Harmer
2.892
274878BISHOP HL;2U
Solar/Wind Harmer
2.447
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.337
274862TOP CROP ;2U
Solar/Wind Harmer
3.646
965931AG1-462 GEN
Solar/Wind Harmer
18.187
971087AG2-675 GEN
Solar/Wind Harmer
2.654
972259AH1-714 GEN
Adder
12.178
274826FISK ;BP
Adder
6.908
274710KENDALL ;4C
50/50
2.074
971997AH1-543 GEN
Solar/Wind Harmer
18.304
274732ELWOOD EC;7P
Adder
15.451
274745AC1-111 GEN9
Adder
5.024
274711KENDALL ;4S
50/50
1.389
274709KENDALL ;3S
50/50
1.389
274659DRESDEN ;3U
50/50
8.259
274658DRESDEN ;2U
50/50
5.008
276660THREERVRS;U2
50/50
3.443
274695ROCKY RD ;2P
Adder
9.602
274693ROCKY RD ;1P
Adder
9.508
274697ROCKY RD ;3P
Adder
2.609
274696ROCKY RD ;4P
Adder
9.828
274674JOLIET 9 ;6U
Adder
13.176
274683WAUKEGAN ;8U
Adder
17.937
274683WAUKEGAN ;8U
Adder
15.12
962691AG1-118 GEN
Solar/Wind Harmer
24.714
960751AF2-366 GEN
Solar/Wind Harmer
2.354
972235AH1-702 GEN1
Adder
2.028
972236AH1-702 GEN2
Adder
1.763
971341AH1-150 GEN
Solar/Wind Harmer
15.979
971343AH1-151 GEN
Solar/Wind Harmer
15.979
276901AD2-066 C O1
Solar/Wind Harmer
2.789
938861AE1-114 GEN
Solar/Wind Harmer
6.414
274764LEE CO EC;5U
Adder
7.256
274765LEE CO EC;6U
Adder
7.256
274762LEE CO EC;3U
Adder
7.239
274763LEE CO EC;4U
Adder
7.171
276872AE1-163_GEN1
Solar/Wind Harmer
5.22
276876AE1-163_GEN2
Solar/Wind Harmer
5.22
958491AF2-143 GEN
Solar/Wind Harmer
11.356
276158O29GEN2
Solar/Wind Harmer
3.761
276157O29GEN1
Solar/Wind Harmer
2.859
958481AF2-142 GEN
Solar/Wind Harmer
11.135
276893AG1-478 C
Solar/Wind Harmer
0.321
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
942111AE2-223 GEN
Solar/Wind Harmer
5.104
960611AF2-352 GEN
Solar/Wind Harmer
1.378
274805UNIV PK N;1U
Adder
2.705
274808UNIV PK N;4U
Adder
2.687
274888KELLY CRK;1U
Solar/Wind Harmer
3.105
276776AD2-060 GEN
Solar/Wind Harmer
0.22
970941AG2-585 GEN
Solar/Wind Harmer
2.894
958011AF2-095 GEN
Solar/Wind Harmer
7.578
274880W4-005 GEN4
Solar/Wind Harmer
1.489
276174W4-005 GEN2
Solar/Wind Harmer
1.489
276615X2-022 GEN
Solar/Wind Harmer
0.926
276838X2-022 GEN2
Solar/Wind Harmer
0.11
972038AH1-567 GEN2
Adder
0.227
274803UNIV PARK;6U
Adder
3.537
965091AG1-374 GEN
Solar/Wind Harmer
17.777
959611AF2-252 GEN
Solar/Wind Harmer
1.378
274814UNIV PK N;0U
Adder
2.722
274807UNIV PK N;3U
Adder
2.716
274811UNIV PK N;7U
Adder
2.699
274887GEN-1.85
Solar/Wind Harmer
2.804
276772AC2-154 GEN
Solar/Wind Harmer
1.469
276843GEN-1.7
Solar/Wind Harmer
0.302
276806AD2-047 C O1
Solar/Wind Harmer
5.63
276785W4-005 GEN1
Solar/Wind Harmer
1.489
971993AH1-541 GEN
Solar/Wind Harmer
4.549
276164X3-005 C
Solar/Wind Harmer
0.322
957381AF2-032 GEN
Solar/Wind Harmer
0.865
972231SS25-0005
Solar/Wind Harmer
4.093
972181SS23-001
Solar/Wind Harmer
2.558
274752CRETE EC ;2U
Adder
2.108
274753CRETE EC ;3U
Adder
2.108
274708KENDALL ;3C
50/50
2.099
274837EQUISTAR ; B
50/50
0.346
274837EQUISTAR ; B
50/50
0.346
276640AD2-194 GEN1
50/50
3.71
276642AD2-194 GEN2
50/50
3.696
274731ELWOOD EC;2P
Adder
15.511
274733ELWOOD EC;3P
Adder
15.511
274735ELWOOD EC;4P
Adder
15.511
274728ELWOOD EC;5P
Adder
15.451
274744AC1-111 GEN8
Adder
5.024
274746AC1-111 G10
Adder
5.024
274675JOLIET 29;7U
Adder
27.482
274675JOLIET 29;7U
Adder
26.501
971411AH1-196 GEN
Solar/Wind Harmer
12.37
970833AG2-524 GEN
Solar/Wind Harmer
7.073
970833AG2-524 GEN
Solar/Wind Harmer
3.29
970169AG2-114 GEN
Solar/Wind Harmer
8.081
274823ROCKFORD ;21
Adder
15.733
971675AH1-338 GEN
Solar/Wind Harmer
14.49
276861AD2-134 GEN
Solar/Wind Harmer
1.437
276863AD2-134 GEN
Solar/Wind Harmer
1.437
971171AH1-044 GEN
Solar/Wind Harmer
15.979
274856ECOGROVE ;U1
Solar/Wind Harmer
2.679
276611AD2-172 GEN
Solar/Wind Harmer
2.032
276612AE2-035 GEN
Solar/Wind Harmer
2.032
971681AH1-341 GEN
Solar/Wind Harmer
11.725
276889AE2-281 GEN
Solar/Wind Harmer
1.492
274687WILL CNTY;4U
Adder
21.463
274687WILL CNTY;4U
Adder
21.463
972267AH1-718 GEN
Adder
3.168
970073AG2-061 GEN
Solar/Wind Harmer
1.761
276741O09 GEN1
Solar/Wind Harmer
2.685
276893AG1-478 C
Solar/Wind Harmer
0.402
274877BISHOP HL;1U
Solar/Wind Harmer
2.447
926823AC1-168 GEN
Solar/Wind Harmer
3.102
946321AF1-296 GEN
Solar/Wind Harmer
7.512
274827FISK ;RP
Adder
4.896
274800UNIV PARK;3U
Adder
3.634
274801UNIV PARK;4U
Adder
3.634
276726Z2-087_GEN
Solar/Wind Harmer
4.924
959341AF2-225 GEN
Solar/Wind Harmer
9.34
972037AH1-567 GEN1
Adder
0.111
274853TWINGROVE;U1
Solar/Wind Harmer
4.269
274854TWINGROVE;U2
Solar/Wind Harmer
4.18
274863CRW1-WTG
Solar/Wind Harmer
3.096
274864CRW2-WTG
Solar/Wind Harmer
3.096
960591AF2-350 GEN
Solar/Wind Harmer
5.262
972228AH1-698 GEN2
Adder
1.93
972227AH1-698 GEN1
Adder
1.356
276668AB2-070 GEN1
Solar/Wind Harmer
1.092
276848AB2-070 GEN3
Solar/Wind Harmer
1.092
276849AB2-070 GEN2
Solar/Wind Harmer
1.092
276763AC1-053 GEN1
Solar/Wind Harmer
1.923
276764AC1-053 GEN2
Solar/Wind Harmer
1.923
274676JOLIET 29;8U
Adder
27.453
274674JOLIET 9 ;6U
Adder
13.176
274682WAUKEGAN ;7U
Adder
15.332
274828WAUKEGAN ;BP
Adder
9.402
276882AE2-255 GEN
Solar/Wind Harmer
2.788
962781AG1-127 GEN
Solar/Wind Harmer
7.804
274872LEEDK;1U
Solar/Wind Harmer
6.702
274822ROCKFORD ;11
Adder
15.848
957471AF2-041 GEN
Solar/Wind Harmer
23.968
959081AF2-199 GEN
Solar/Wind Harmer
7.989
971067AG2-660 GEN
Solar/Wind Harmer
1.858
970819AG2-516 GEN
Solar/Wind Harmer
9.581
970569AG2-363 GEN
Solar/Wind Harmer
23.743
274858EASY ROAD;U2
Solar/Wind Harmer
3.728
274761LEE CO EC;2U
Adder
7.239
274766LEE CO EC;7U
Adder
7.154
276805AD2-038 GEN
Solar/Wind Harmer
3.882
276708O09 GEN2
Solar/Wind Harmer
2.685
276694AA1-018 GEN2
Solar/Wind Harmer
4.684
276691AA1-018 GEN1
Solar/Wind Harmer
0.56
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
274848CAMPGROVE;RU
Solar/Wind Harmer
4.652
274861TOP CROP ;1U
Solar/Wind Harmer
4.367
274871GR RIDGE ;2U
Solar/Wind Harmer
5.498
274847GR RIDGE ;BU
Solar/Wind Harmer
3.615
276655WTG1_EQ
Solar/Wind Harmer
5.435
276656WTG2_EQ
Solar/Wind Harmer
0.72
939741AE1-205 GEN
Solar/Wind Harmer
12.453
274802UNIV PARK;5U
Adder
3.537
274812UNIV PK N;8U
Adder
2.699
276686W4-005 GEN3
Solar/Wind Harmer
1.489
939401AE1-172 GEN
Solar/Wind Harmer
6.812
276621W2-048 GEN
Solar/Wind Harmer
2.95
274751CRETE EC ;1U
Adder
2.108
274754CRETE EC ;4U
Adder
2.108
991777J1629 G
External Queue
9.17172908782959
990512J1326
External Queue
4.053486347198486
990117J1214
External Queue
13.943992614746094
990727J1377 G
External Queue
4.71599817276001
990407J1304
External Queue
3.138070583343506
NYPJM->LTFIMP_NY
CLTF
0.757
WECLTFEXP_WEC->PJM
CLTF
3.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.319
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.159
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.114
MECLTFEXP_MEC->PJM
CLTF
9.627
SIGELTFEXP_SIGE->PJM
CLTF
0.011
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.369
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.041
LAGNLTFEXP_LAGN->PJM
CLTF
3.136
TVALTFEXP_TVA->PJM
CLTF
0.787

Details for COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line l/o COMED_P4_167-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_167-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.28 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1546.53
MW Contribution:
11.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274711KENDALL ;4S
50/50
1.389
274709KENDALL ;3S
50/50
1.389
276658THREERVRS;U1
50/50
5.687
274729ELWOOD EC;1P
Adder
15.511
274730ELWOOD EC;6P
Adder
15.451
274734ELWOOD EC;8P
Adder
15.451
274736ELWOOD EC;9P
Adder
15.451
274676JOLIET 29;8U
Adder
26.473
274682WAUKEGAN ;7U
Adder
15.332
943121AE2-341 GEN
Solar/Wind Harmer
12.432
943591AF1-030 GEN
Solar/Wind Harmer
8.288
276868AE1-113 GEN
Solar/Wind Harmer
8.364
274879MINONK ;1U
Solar/Wind Harmer
5.576
276799AD1-013 GEN
Solar/Wind Harmer
1.78
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
2.971
274850MENDOTA H;RU
Solar/Wind Harmer
2.066
276602WESTBROOK C
Solar/Wind Harmer
1.71
959091AF2-200 GEN
Solar/Wind Harmer
15.979
970571AG2-364 GEN
Solar/Wind Harmer
15.828
274857EASY ROAD;U1
Solar/Wind Harmer
3.728
274760LEE CO EC;1U
Adder
7.239
274767LEE CO EC;8U
Adder
7.154
276603SUBLETTE C
Solar/Wind Harmer
0.809
970707AG2-453 GEN
Solar/Wind Harmer
20.548
276782AC1-033 GEN
Solar/Wind Harmer
2.892
274878BISHOP HL;2U
Solar/Wind Harmer
2.447
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.337
274862TOP CROP ;2U
Solar/Wind Harmer
3.646
965931AG1-462 GEN
Solar/Wind Harmer
18.187
971087AG2-675 GEN
Solar/Wind Harmer
2.654
972259AH1-714 GEN
Adder
12.178
274826FISK ;BP
Adder
6.908
972038AH1-567 GEN2
Adder
0.227
274803UNIV PARK;6U
Adder
3.537
965091AG1-374 GEN
Solar/Wind Harmer
17.777
959611AF2-252 GEN
Solar/Wind Harmer
1.378
274710KENDALL ;4C
50/50
2.074
971997AH1-543 GEN
Solar/Wind Harmer
18.304
274732ELWOOD EC;7P
Adder
15.451
274745AC1-111 GEN9
Adder
5.024
274676JOLIET 29;8U
Adder
27.453
274674JOLIET 9 ;6U
Adder
13.176
274682WAUKEGAN ;7U
Adder
15.332
274828WAUKEGAN ;BP
Adder
9.402
276882AE2-255 GEN
Solar/Wind Harmer
2.788
962781AG1-127 GEN
Solar/Wind Harmer
7.804
274872LEEDK;1U
Solar/Wind Harmer
6.702
274822ROCKFORD ;11
Adder
15.848
957471AF2-041 GEN
Solar/Wind Harmer
23.968
959081AF2-199 GEN
Solar/Wind Harmer
7.989
971067AG2-660 GEN
Solar/Wind Harmer
1.858
970819AG2-516 GEN
Solar/Wind Harmer
9.581
970569AG2-363 GEN
Solar/Wind Harmer
23.743
274858EASY ROAD;U2
Solar/Wind Harmer
3.728
274761LEE CO EC;2U
Adder
7.239
274766LEE CO EC;7U
Adder
7.154
276805AD2-038 GEN
Solar/Wind Harmer
3.882
276708O09 GEN2
Solar/Wind Harmer
2.685
276694AA1-018 GEN2
Solar/Wind Harmer
4.684
276691AA1-018 GEN1
Solar/Wind Harmer
0.56
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
274848CAMPGROVE;RU
Solar/Wind Harmer
4.652
274861TOP CROP ;1U
Solar/Wind Harmer
4.367
274871GR RIDGE ;2U
Solar/Wind Harmer
5.498
274847GR RIDGE ;BU
Solar/Wind Harmer
3.615
276655WTG1_EQ
Solar/Wind Harmer
5.435
276656WTG2_EQ
Solar/Wind Harmer
0.72
939741AE1-205 GEN
Solar/Wind Harmer
12.453
274802UNIV PARK;5U
Adder
3.537
274812UNIV PK N;8U
Adder
2.699
276686W4-005 GEN3
Solar/Wind Harmer
1.489
939401AE1-172 GEN
Solar/Wind Harmer
6.812
276621W2-048 GEN
Solar/Wind Harmer
2.95
274751CRETE EC ;1U
Adder
2.108
274754CRETE EC ;4U
Adder
2.108
274708KENDALL ;3C
50/50
2.099
274837EQUISTAR ; B
50/50
0.346
274837EQUISTAR ; B
50/50
0.346
276640AD2-194 GEN1
50/50
3.71
276642AD2-194 GEN2
50/50
3.696
274731ELWOOD EC;2P
Adder
15.511
274733ELWOOD EC;3P
Adder
15.511
274735ELWOOD EC;4P
Adder
15.511
274728ELWOOD EC;5P
Adder
15.451
274744AC1-111 GEN8
Adder
5.024
274746AC1-111 G10
Adder
5.024
274675JOLIET 29;7U
Adder
27.482
274675JOLIET 29;7U
Adder
26.501
971411AH1-196 GEN
Solar/Wind Harmer
12.37
970833AG2-524 GEN
Solar/Wind Harmer
7.073
970833AG2-524 GEN
Solar/Wind Harmer
3.29
970169AG2-114 GEN
Solar/Wind Harmer
8.081
274823ROCKFORD ;21
Adder
15.733
971675AH1-338 GEN
Solar/Wind Harmer
14.49
276861AD2-134 GEN
Solar/Wind Harmer
1.437
276863AD2-134 GEN
Solar/Wind Harmer
1.437
971171AH1-044 GEN
Solar/Wind Harmer
15.979
274856ECOGROVE ;U1
Solar/Wind Harmer
2.679
276611AD2-172 GEN
Solar/Wind Harmer
2.032
276612AE2-035 GEN
Solar/Wind Harmer
2.032
971681AH1-341 GEN
Solar/Wind Harmer
11.725
276889AE2-281 GEN
Solar/Wind Harmer
1.492
274687WILL CNTY;4U
Adder
21.463
274687WILL CNTY;4U
Adder
21.463
972267AH1-718 GEN
Adder
3.168
970073AG2-061 GEN
Solar/Wind Harmer
1.761
276741O09 GEN1
Solar/Wind Harmer
2.685
276893AG1-478 C
Solar/Wind Harmer
0.402
274877BISHOP HL;1U
Solar/Wind Harmer
2.447
926823AC1-168 GEN
Solar/Wind Harmer
3.102
946321AF1-296 GEN
Solar/Wind Harmer
7.512
274827FISK ;RP
Adder
4.896
274800UNIV PARK;3U
Adder
3.634
274801UNIV PARK;4U
Adder
3.634
276726Z2-087_GEN
Solar/Wind Harmer
4.924
959341AF2-225 GEN
Solar/Wind Harmer
9.34
972037AH1-567 GEN1
Adder
0.111
274853TWINGROVE;U1
Solar/Wind Harmer
4.269
274854TWINGROVE;U2
Solar/Wind Harmer
4.18
274863CRW1-WTG
Solar/Wind Harmer
3.096
274864CRW2-WTG
Solar/Wind Harmer
3.096
960591AF2-350 GEN
Solar/Wind Harmer
5.262
972228AH1-698 GEN2
Adder
1.93
972227AH1-698 GEN1
Adder
1.356
276668AB2-070 GEN1
Solar/Wind Harmer
1.092
276848AB2-070 GEN3
Solar/Wind Harmer
1.092
276849AB2-070 GEN2
Solar/Wind Harmer
1.092
276763AC1-053 GEN1
Solar/Wind Harmer
1.923
276764AC1-053 GEN2
Solar/Wind Harmer
1.923
274659DRESDEN ;3U
50/50
8.259
274658DRESDEN ;2U
50/50
5.008
276660THREERVRS;U2
50/50
3.443
274695ROCKY RD ;2P
Adder
9.602
274693ROCKY RD ;1P
Adder
9.508
274697ROCKY RD ;3P
Adder
2.609
274696ROCKY RD ;4P
Adder
9.828
274674JOLIET 9 ;6U
Adder
13.176
274683WAUKEGAN ;8U
Adder
17.937
274683WAUKEGAN ;8U
Adder
15.12
962691AG1-118 GEN
Solar/Wind Harmer
24.714
960751AF2-366 GEN
Solar/Wind Harmer
2.354
972235AH1-702 GEN1
Adder
2.028
972236AH1-702 GEN2
Adder
1.763
971341AH1-150 GEN
Solar/Wind Harmer
15.979
971343AH1-151 GEN
Solar/Wind Harmer
15.979
276901AD2-066 C O1
Solar/Wind Harmer
2.789
938861AE1-114 GEN
Solar/Wind Harmer
6.414
274764LEE CO EC;5U
Adder
7.256
274765LEE CO EC;6U
Adder
7.256
274762LEE CO EC;3U
Adder
7.239
274763LEE CO EC;4U
Adder
7.171
276872AE1-163_GEN1
Solar/Wind Harmer
5.22
276876AE1-163_GEN2
Solar/Wind Harmer
5.22
958491AF2-143 GEN
Solar/Wind Harmer
11.356
276158O29GEN2
Solar/Wind Harmer
3.761
276157O29GEN1
Solar/Wind Harmer
2.859
958481AF2-142 GEN
Solar/Wind Harmer
11.135
276893AG1-478 C
Solar/Wind Harmer
0.321
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
942111AE2-223 GEN
Solar/Wind Harmer
5.104
960611AF2-352 GEN
Solar/Wind Harmer
1.378
274805UNIV PK N;1U
Adder
2.705
274808UNIV PK N;4U
Adder
2.687
274888KELLY CRK;1U
Solar/Wind Harmer
3.105
276776AD2-060 GEN
Solar/Wind Harmer
0.22
970941AG2-585 GEN
Solar/Wind Harmer
2.894
958011AF2-095 GEN
Solar/Wind Harmer
7.578
274880W4-005 GEN4
Solar/Wind Harmer
1.489
276174W4-005 GEN2
Solar/Wind Harmer
1.489
276615X2-022 GEN
Solar/Wind Harmer
0.926
276838X2-022 GEN2
Solar/Wind Harmer
0.11
274814UNIV PK N;0U
Adder
2.722
274807UNIV PK N;3U
Adder
2.716
274811UNIV PK N;7U
Adder
2.699
274887GEN-1.85
Solar/Wind Harmer
2.804
276772AC2-154 GEN
Solar/Wind Harmer
1.469
276843GEN-1.7
Solar/Wind Harmer
0.302
276806AD2-047 C O1
Solar/Wind Harmer
5.63
276785W4-005 GEN1
Solar/Wind Harmer
1.489
971993AH1-541 GEN
Solar/Wind Harmer
4.549
276164X3-005 C
Solar/Wind Harmer
0.322
957381AF2-032 GEN
Solar/Wind Harmer
0.865
972231SS25-0005
Solar/Wind Harmer
4.093
972181SS23-001
Solar/Wind Harmer
2.558
274752CRETE EC ;2U
Adder
2.108
274753CRETE EC ;3U
Adder
2.108
991777J1629 G
External Queue
9.17172908782959
990512J1326
External Queue
4.053486347198486
990117J1214
External Queue
13.943992614746094
990727J1377 G
External Queue
4.71599817276001
990407J1304
External Queue
3.138070583343506
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.159
NYPJM->LTFIMP_NY
CLTF
0.757
WECLTFEXP_WEC->PJM
CLTF
3.064
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.114
MECLTFEXP_MEC->PJM
CLTF
9.627
SIGELTFEXP_SIGE->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.746
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.369
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.041
LAGNLTFEXP_LAGN->PJM
CLTF
3.136
TVALTFEXP_TVA->PJM
CLTF
0.787

Details for COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_167-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.44 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1548.9
MW Contribution:
11.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274711KENDALL ;4S
50/50
1.389
274709KENDALL ;3S
50/50
1.389
274659DRESDEN ;3U
50/50
8.259
274658DRESDEN ;2U
50/50
5.008
276660THREERVRS;U2
50/50
3.443
274695ROCKY RD ;2P
Adder
9.602
274693ROCKY RD ;1P
Adder
9.508
274697ROCKY RD ;3P
Adder
2.609
274696ROCKY RD ;4P
Adder
9.828
274674JOLIET 9 ;6U
Adder
13.176
274683WAUKEGAN ;8U
Adder
17.937
274683WAUKEGAN ;8U
Adder
15.12
962691AG1-118 GEN
Solar/Wind Harmer
24.714
960751AF2-366 GEN
Solar/Wind Harmer
2.354
972235AH1-702 GEN1
Adder
2.028
972236AH1-702 GEN2
Adder
1.763
971341AH1-150 GEN
Solar/Wind Harmer
15.979
971343AH1-151 GEN
Solar/Wind Harmer
15.979
276901AD2-066 C O1
Solar/Wind Harmer
2.789
938861AE1-114 GEN
Solar/Wind Harmer
6.414
274764LEE CO EC;5U
Adder
7.256
274765LEE CO EC;6U
Adder
7.256
274762LEE CO EC;3U
Adder
7.239
274763LEE CO EC;4U
Adder
7.171
276872AE1-163_GEN1
Solar/Wind Harmer
5.22
276876AE1-163_GEN2
Solar/Wind Harmer
5.22
958491AF2-143 GEN
Solar/Wind Harmer
11.356
276158O29GEN2
Solar/Wind Harmer
3.761
276157O29GEN1
Solar/Wind Harmer
2.859
958481AF2-142 GEN
Solar/Wind Harmer
11.135
276893AG1-478 C
Solar/Wind Harmer
0.321
276658THREERVRS;U1
50/50
5.687
274729ELWOOD EC;1P
Adder
15.511
274730ELWOOD EC;6P
Adder
15.451
274734ELWOOD EC;8P
Adder
15.451
274736ELWOOD EC;9P
Adder
15.451
274676JOLIET 29;8U
Adder
26.473
274682WAUKEGAN ;7U
Adder
15.332
943121AE2-341 GEN
Solar/Wind Harmer
12.432
943591AF1-030 GEN
Solar/Wind Harmer
8.288
276868AE1-113 GEN
Solar/Wind Harmer
8.364
274879MINONK ;1U
Solar/Wind Harmer
5.576
276799AD1-013 GEN
Solar/Wind Harmer
1.78
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
2.971
274850MENDOTA H;RU
Solar/Wind Harmer
2.066
276602WESTBROOK C
Solar/Wind Harmer
1.71
959091AF2-200 GEN
Solar/Wind Harmer
15.979
970571AG2-364 GEN
Solar/Wind Harmer
15.828
274857EASY ROAD;U1
Solar/Wind Harmer
3.728
274760LEE CO EC;1U
Adder
7.239
274767LEE CO EC;8U
Adder
7.154
276603SUBLETTE C
Solar/Wind Harmer
0.809
970707AG2-453 GEN
Solar/Wind Harmer
20.548
276782AC1-033 GEN
Solar/Wind Harmer
2.892
274878BISHOP HL;2U
Solar/Wind Harmer
2.447
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.337
274862TOP CROP ;2U
Solar/Wind Harmer
3.646
965931AG1-462 GEN
Solar/Wind Harmer
18.187
971087AG2-675 GEN
Solar/Wind Harmer
2.654
972259AH1-714 GEN
Adder
12.178
274826FISK ;BP
Adder
6.908
972038AH1-567 GEN2
Adder
0.227
274803UNIV PARK;6U
Adder
3.537
965091AG1-374 GEN
Solar/Wind Harmer
17.777
959611AF2-252 GEN
Solar/Wind Harmer
1.378
274814UNIV PK N;0U
Adder
2.722
274807UNIV PK N;3U
Adder
2.716
274811UNIV PK N;7U
Adder
2.699
274887GEN-1.85
Solar/Wind Harmer
2.804
276772AC2-154 GEN
Solar/Wind Harmer
1.469
276843GEN-1.7
Solar/Wind Harmer
0.302
276806AD2-047 C O1
Solar/Wind Harmer
5.63
276785W4-005 GEN1
Solar/Wind Harmer
1.489
971993AH1-541 GEN
Solar/Wind Harmer
4.549
276164X3-005 C
Solar/Wind Harmer
0.322
957381AF2-032 GEN
Solar/Wind Harmer
0.865
972231SS25-0005
Solar/Wind Harmer
4.093
972181SS23-001
Solar/Wind Harmer
2.558
274752CRETE EC ;2U
Adder
2.108
274753CRETE EC ;3U
Adder
2.108
274708KENDALL ;3C
50/50
2.099
274837EQUISTAR ; B
50/50
0.346
274837EQUISTAR ; B
50/50
0.346
276640AD2-194 GEN1
50/50
3.71
276642AD2-194 GEN2
50/50
3.696
274731ELWOOD EC;2P
Adder
15.511
274733ELWOOD EC;3P
Adder
15.511
274735ELWOOD EC;4P
Adder
15.511
274728ELWOOD EC;5P
Adder
15.451
274744AC1-111 GEN8
Adder
5.024
274746AC1-111 G10
Adder
5.024
274675JOLIET 29;7U
Adder
27.482
274675JOLIET 29;7U
Adder
26.501
971411AH1-196 GEN
Solar/Wind Harmer
12.37
970833AG2-524 GEN
Solar/Wind Harmer
7.073
970833AG2-524 GEN
Solar/Wind Harmer
3.29
970169AG2-114 GEN
Solar/Wind Harmer
8.081
274823ROCKFORD ;21
Adder
15.733
971675AH1-338 GEN
Solar/Wind Harmer
14.49
276861AD2-134 GEN
Solar/Wind Harmer
1.437
276863AD2-134 GEN
Solar/Wind Harmer
1.437
971171AH1-044 GEN
Solar/Wind Harmer
15.979
274856ECOGROVE ;U1
Solar/Wind Harmer
2.679
276611AD2-172 GEN
Solar/Wind Harmer
2.032
276612AE2-035 GEN
Solar/Wind Harmer
2.032
971681AH1-341 GEN
Solar/Wind Harmer
11.725
276889AE2-281 GEN
Solar/Wind Harmer
1.492
274687WILL CNTY;4U
Adder
21.463
274687WILL CNTY;4U
Adder
21.463
972267AH1-718 GEN
Adder
3.168
970073AG2-061 GEN
Solar/Wind Harmer
1.761
276741O09 GEN1
Solar/Wind Harmer
2.685
276893AG1-478 C
Solar/Wind Harmer
0.402
274877BISHOP HL;1U
Solar/Wind Harmer
2.447
926823AC1-168 GEN
Solar/Wind Harmer
3.102
946321AF1-296 GEN
Solar/Wind Harmer
7.512
274827FISK ;RP
Adder
4.896
274800UNIV PARK;3U
Adder
3.634
274801UNIV PARK;4U
Adder
3.634
276726Z2-087_GEN
Solar/Wind Harmer
4.924
959341AF2-225 GEN
Solar/Wind Harmer
9.34
972037AH1-567 GEN1
Adder
0.111
274853TWINGROVE;U1
Solar/Wind Harmer
4.269
274854TWINGROVE;U2
Solar/Wind Harmer
4.18
274863CRW1-WTG
Solar/Wind Harmer
3.096
274864CRW2-WTG
Solar/Wind Harmer
3.096
960591AF2-350 GEN
Solar/Wind Harmer
5.262
972228AH1-698 GEN2
Adder
1.93
972227AH1-698 GEN1
Adder
1.356
276668AB2-070 GEN1
Solar/Wind Harmer
1.092
276848AB2-070 GEN3
Solar/Wind Harmer
1.092
276849AB2-070 GEN2
Solar/Wind Harmer
1.092
276763AC1-053 GEN1
Solar/Wind Harmer
1.923
276764AC1-053 GEN2
Solar/Wind Harmer
1.923
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
942111AE2-223 GEN
Solar/Wind Harmer
5.104
960611AF2-352 GEN
Solar/Wind Harmer
1.378
274805UNIV PK N;1U
Adder
2.705
274808UNIV PK N;4U
Adder
2.687
274888KELLY CRK;1U
Solar/Wind Harmer
3.105
276776AD2-060 GEN
Solar/Wind Harmer
0.22
970941AG2-585 GEN
Solar/Wind Harmer
2.894
958011AF2-095 GEN
Solar/Wind Harmer
7.578
274880W4-005 GEN4
Solar/Wind Harmer
1.489
276174W4-005 GEN2
Solar/Wind Harmer
1.489
276615X2-022 GEN
Solar/Wind Harmer
0.926
276838X2-022 GEN2
Solar/Wind Harmer
0.11
274710KENDALL ;4C
50/50
2.074
971997AH1-543 GEN
Solar/Wind Harmer
18.304
274732ELWOOD EC;7P
Adder
15.451
274745AC1-111 GEN9
Adder
5.024
274676JOLIET 29;8U
Adder
27.453
274674JOLIET 9 ;6U
Adder
13.176
274682WAUKEGAN ;7U
Adder
15.332
274828WAUKEGAN ;BP
Adder
9.402
276882AE2-255 GEN
Solar/Wind Harmer
2.788
962781AG1-127 GEN
Solar/Wind Harmer
7.804
274872LEEDK;1U
Solar/Wind Harmer
6.702
274822ROCKFORD ;11
Adder
15.848
957471AF2-041 GEN
Solar/Wind Harmer
23.968
959081AF2-199 GEN
Solar/Wind Harmer
7.989
971067AG2-660 GEN
Solar/Wind Harmer
1.858
970819AG2-516 GEN
Solar/Wind Harmer
9.581
970569AG2-363 GEN
Solar/Wind Harmer
23.743
274858EASY ROAD;U2
Solar/Wind Harmer
3.728
274761LEE CO EC;2U
Adder
7.239
274766LEE CO EC;7U
Adder
7.154
276805AD2-038 GEN
Solar/Wind Harmer
3.882
276708O09 GEN2
Solar/Wind Harmer
2.685
276694AA1-018 GEN2
Solar/Wind Harmer
4.684
276691AA1-018 GEN1
Solar/Wind Harmer
0.56
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
274848CAMPGROVE;RU
Solar/Wind Harmer
4.652
274861TOP CROP ;1U
Solar/Wind Harmer
4.367
274871GR RIDGE ;2U
Solar/Wind Harmer
5.498
274847GR RIDGE ;BU
Solar/Wind Harmer
3.615
276655WTG1_EQ
Solar/Wind Harmer
5.435
276656WTG2_EQ
Solar/Wind Harmer
0.72
939741AE1-205 GEN
Solar/Wind Harmer
12.453
274802UNIV PARK;5U
Adder
3.537
274812UNIV PK N;8U
Adder
2.699
276686W4-005 GEN3
Solar/Wind Harmer
1.489
939401AE1-172 GEN
Solar/Wind Harmer
6.812
276621W2-048 GEN
Solar/Wind Harmer
2.95
274751CRETE EC ;1U
Adder
2.108
274754CRETE EC ;4U
Adder
2.108
991777J1629 G
External Queue
9.17172908782959
990512J1326
External Queue
4.053486347198486
990117J1214
External Queue
13.943992614746094
990727J1377 G
External Queue
4.71599817276001
990407J1304
External Queue
3.138070583343506
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.159
NYPJM->LTFIMP_NY
CLTF
0.757
WECLTFEXP_WEC->PJM
CLTF
3.064
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.114
MECLTFEXP_MEC->PJM
CLTF
9.627
SIGELTFEXP_SIGE->PJM
CLTF
0.011
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.746
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.369
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.041
LAGNLTFEXP_LAGN->PJM
CLTF
3.136
TVALTFEXP_TVA->PJM
CLTF
0.787

Details for COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_167-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.44 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1548.9
MW Contribution:
11.72
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
276658THREERVRS;U1
50/50
5.687
274729ELWOOD EC;1P
Adder
15.511
274730ELWOOD EC;6P
Adder
15.451
274734ELWOOD EC;8P
Adder
15.451
274736ELWOOD EC;9P
Adder
15.451
274676JOLIET 29;8U
Adder
26.473
274682WAUKEGAN ;7U
Adder
15.332
943121AE2-341 GEN
Solar/Wind Harmer
12.432
943591AF1-030 GEN
Solar/Wind Harmer
8.288
276868AE1-113 GEN
Solar/Wind Harmer
8.364
274879MINONK ;1U
Solar/Wind Harmer
5.576
276799AD1-013 GEN
Solar/Wind Harmer
1.78
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
2.971
274850MENDOTA H;RU
Solar/Wind Harmer
2.066
276602WESTBROOK C
Solar/Wind Harmer
1.71
959091AF2-200 GEN
Solar/Wind Harmer
15.979
970571AG2-364 GEN
Solar/Wind Harmer
15.828
274857EASY ROAD;U1
Solar/Wind Harmer
3.728
274760LEE CO EC;1U
Adder
7.239
274767LEE CO EC;8U
Adder
7.154
276603SUBLETTE C
Solar/Wind Harmer
0.809
970707AG2-453 GEN
Solar/Wind Harmer
20.548
276782AC1-033 GEN
Solar/Wind Harmer
2.892
274708KENDALL ;3C
50/50
2.099
274837EQUISTAR ; B
50/50
0.346
274837EQUISTAR ; B
50/50
0.346
276640AD2-194 GEN1
50/50
3.71
276642AD2-194 GEN2
50/50
3.696
274731ELWOOD EC;2P
Adder
15.511
274733ELWOOD EC;3P
Adder
15.511
274735ELWOOD EC;4P
Adder
15.511
274728ELWOOD EC;5P
Adder
15.451
274744AC1-111 GEN8
Adder
5.024
274746AC1-111 G10
Adder
5.024
274675JOLIET 29;7U
Adder
27.482
274675JOLIET 29;7U
Adder
26.501
971411AH1-196 GEN
Solar/Wind Harmer
12.37
970833AG2-524 GEN
Solar/Wind Harmer
7.073
970833AG2-524 GEN
Solar/Wind Harmer
3.29
970169AG2-114 GEN
Solar/Wind Harmer
8.081
274823ROCKFORD ;21
Adder
15.733
971675AH1-338 GEN
Solar/Wind Harmer
14.49
276861AD2-134 GEN
Solar/Wind Harmer
1.437
276863AD2-134 GEN
Solar/Wind Harmer
1.437
971171AH1-044 GEN
Solar/Wind Harmer
15.979
274856ECOGROVE ;U1
Solar/Wind Harmer
2.679
276611AD2-172 GEN
Solar/Wind Harmer
2.032
276612AE2-035 GEN
Solar/Wind Harmer
2.032
971681AH1-341 GEN
Solar/Wind Harmer
11.725
276889AE2-281 GEN
Solar/Wind Harmer
1.492
274687WILL CNTY;4U
Adder
21.463
274687WILL CNTY;4U
Adder
21.463
972267AH1-718 GEN
Adder
3.168
970073AG2-061 GEN
Solar/Wind Harmer
1.761
276741O09 GEN1
Solar/Wind Harmer
2.685
276893AG1-478 C
Solar/Wind Harmer
0.402
274877BISHOP HL;1U
Solar/Wind Harmer
2.447
926823AC1-168 GEN
Solar/Wind Harmer
3.102
946321AF1-296 GEN
Solar/Wind Harmer
7.512
274827FISK ;RP
Adder
4.896
274800UNIV PARK;3U
Adder
3.634
274801UNIV PARK;4U
Adder
3.634
276726Z2-087_GEN
Solar/Wind Harmer
4.924
959341AF2-225 GEN
Solar/Wind Harmer
9.34
972037AH1-567 GEN1
Adder
0.111
274853TWINGROVE;U1
Solar/Wind Harmer
4.269
274854TWINGROVE;U2
Solar/Wind Harmer
4.18
274863CRW1-WTG
Solar/Wind Harmer
3.096
274864CRW2-WTG
Solar/Wind Harmer
3.096
960591AF2-350 GEN
Solar/Wind Harmer
5.262
972228AH1-698 GEN2
Adder
1.93
972227AH1-698 GEN1
Adder
1.356
276668AB2-070 GEN1
Solar/Wind Harmer
1.092
276848AB2-070 GEN3
Solar/Wind Harmer
1.092
276849AB2-070 GEN2
Solar/Wind Harmer
1.092
276763AC1-053 GEN1
Solar/Wind Harmer
1.923
276764AC1-053 GEN2
Solar/Wind Harmer
1.923
274711KENDALL ;4S
50/50
1.389
274709KENDALL ;3S
50/50
1.389
274659DRESDEN ;3U
50/50
8.259
274658DRESDEN ;2U
50/50
5.008
276660THREERVRS;U2
50/50
3.443
274695ROCKY RD ;2P
Adder
9.602
274693ROCKY RD ;1P
Adder
9.508
274697ROCKY RD ;3P
Adder
2.609
274696ROCKY RD ;4P
Adder
9.828
274674JOLIET 9 ;6U
Adder
13.176
274683WAUKEGAN ;8U
Adder
17.937
274683WAUKEGAN ;8U
Adder
15.12
962691AG1-118 GEN
Solar/Wind Harmer
24.714
960751AF2-366 GEN
Solar/Wind Harmer
2.354
972235AH1-702 GEN1
Adder
2.028
972236AH1-702 GEN2
Adder
1.763
971341AH1-150 GEN
Solar/Wind Harmer
15.979
971343AH1-151 GEN
Solar/Wind Harmer
15.979
276901AD2-066 C O1
Solar/Wind Harmer
2.789
938861AE1-114 GEN
Solar/Wind Harmer
6.414
274764LEE CO EC;5U
Adder
7.256
274765LEE CO EC;6U
Adder
7.256
274762LEE CO EC;3U
Adder
7.239
274763LEE CO EC;4U
Adder
7.171
276872AE1-163_GEN1
Solar/Wind Harmer
5.22
276876AE1-163_GEN2
Solar/Wind Harmer
5.22
958491AF2-143 GEN
Solar/Wind Harmer
11.356
276158O29GEN2
Solar/Wind Harmer
3.761
276157O29GEN1
Solar/Wind Harmer
2.859
958481AF2-142 GEN
Solar/Wind Harmer
11.135
276893AG1-478 C
Solar/Wind Harmer
0.321
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
942111AE2-223 GEN
Solar/Wind Harmer
5.104
960611AF2-352 GEN
Solar/Wind Harmer
1.378
274805UNIV PK N;1U
Adder
2.705
274808UNIV PK N;4U
Adder
2.687
274888KELLY CRK;1U
Solar/Wind Harmer
3.105
276776AD2-060 GEN
Solar/Wind Harmer
0.22
970941AG2-585 GEN
Solar/Wind Harmer
2.894
958011AF2-095 GEN
Solar/Wind Harmer
7.578
274880W4-005 GEN4
Solar/Wind Harmer
1.489
276174W4-005 GEN2
Solar/Wind Harmer
1.489
276615X2-022 GEN
Solar/Wind Harmer
0.926
276838X2-022 GEN2
Solar/Wind Harmer
0.11
274710KENDALL ;4C
50/50
2.074
971997AH1-543 GEN
Solar/Wind Harmer
18.304
274732ELWOOD EC;7P
Adder
15.451
274745AC1-111 GEN9
Adder
5.024
274676JOLIET 29;8U
Adder
27.453
274674JOLIET 9 ;6U
Adder
13.176
274682WAUKEGAN ;7U
Adder
15.332
274828WAUKEGAN ;BP
Adder
9.402
276882AE2-255 GEN
Solar/Wind Harmer
2.788
962781AG1-127 GEN
Solar/Wind Harmer
7.804
274872LEEDK;1U
Solar/Wind Harmer
6.702
274822ROCKFORD ;11
Adder
15.848
957471AF2-041 GEN
Solar/Wind Harmer
23.968
959081AF2-199 GEN
Solar/Wind Harmer
7.989
971067AG2-660 GEN
Solar/Wind Harmer
1.858
970819AG2-516 GEN
Solar/Wind Harmer
9.581
970569AG2-363 GEN
Solar/Wind Harmer
23.743
274858EASY ROAD;U2
Solar/Wind Harmer
3.728
274761LEE CO EC;2U
Adder
7.239
274766LEE CO EC;7U
Adder
7.154
276805AD2-038 GEN
Solar/Wind Harmer
3.882
276708O09 GEN2
Solar/Wind Harmer
2.685
276694AA1-018 GEN2
Solar/Wind Harmer
4.684
276691AA1-018 GEN1
Solar/Wind Harmer
0.56
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
274848CAMPGROVE;RU
Solar/Wind Harmer
4.652
274861TOP CROP ;1U
Solar/Wind Harmer
4.367
274871GR RIDGE ;2U
Solar/Wind Harmer
5.498
274847GR RIDGE ;BU
Solar/Wind Harmer
3.615
276655WTG1_EQ
Solar/Wind Harmer
5.435
276656WTG2_EQ
Solar/Wind Harmer
0.72
939741AE1-205 GEN
Solar/Wind Harmer
12.453
274802UNIV PARK;5U
Adder
3.537
274812UNIV PK N;8U
Adder
2.699
276686W4-005 GEN3
Solar/Wind Harmer
1.489
939401AE1-172 GEN
Solar/Wind Harmer
6.812
276621W2-048 GEN
Solar/Wind Harmer
2.95
274751CRETE EC ;1U
Adder
2.108
274754CRETE EC ;4U
Adder
2.108
274878BISHOP HL;2U
Solar/Wind Harmer
2.447
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.337
274862TOP CROP ;2U
Solar/Wind Harmer
3.646
965931AG1-462 GEN
Solar/Wind Harmer
18.187
971087AG2-675 GEN
Solar/Wind Harmer
2.654
972259AH1-714 GEN
Adder
12.178
274826FISK ;BP
Adder
6.908
972038AH1-567 GEN2
Adder
0.227
274803UNIV PARK;6U
Adder
3.537
965091AG1-374 GEN
Solar/Wind Harmer
17.777
959611AF2-252 GEN
Solar/Wind Harmer
1.378
274814UNIV PK N;0U
Adder
2.722
274807UNIV PK N;3U
Adder
2.716
274811UNIV PK N;7U
Adder
2.699
274887GEN-1.85
Solar/Wind Harmer
2.804
276772AC2-154 GEN
Solar/Wind Harmer
1.469
276843GEN-1.7
Solar/Wind Harmer
0.302
276806AD2-047 C O1
Solar/Wind Harmer
5.63
276785W4-005 GEN1
Solar/Wind Harmer
1.489
971993AH1-541 GEN
Solar/Wind Harmer
4.549
276164X3-005 C
Solar/Wind Harmer
0.322
957381AF2-032 GEN
Solar/Wind Harmer
0.865
972231SS25-0005
Solar/Wind Harmer
4.093
972181SS23-001
Solar/Wind Harmer
2.558
274752CRETE EC ;2U
Adder
2.108
274753CRETE EC ;3U
Adder
2.108
991777J1629 G
External Queue
9.17172908782959
990512J1326
External Queue
4.053486347198486
990117J1214
External Queue
13.943992614746094
990727J1377 G
External Queue
4.71599817276001
990407J1304
External Queue
3.138070583343506
NYPJM->LTFIMP_NY
CLTF
0.757
WECLTFEXP_WEC->PJM
CLTF
3.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.319
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.159
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.114
MECLTFEXP_MEC->PJM
CLTF
9.627
SIGELTFEXP_SIGE->PJM
CLTF
0.011
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.369
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.041
LAGNLTFEXP_LAGN->PJM
CLTF
3.136
TVALTFEXP_TVA->PJM
CLTF
0.787

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4-6_116-345-R______SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_116-345-R______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.48 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2606.61
MW Contribution:
12.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
959351AF2-226 GEN
50/50
5.867
276872AE1-163_GEN1
Solar/Wind Harmer
9.059
276876AE1-163_GEN2
Solar/Wind Harmer
9.059
958491AF2-143 GEN
Solar/Wind Harmer
19.905
958481AF2-142 GEN
Solar/Wind Harmer
19.666
274683WAUKEGAN ;8U
Adder
19.931
274683WAUKEGAN ;8U
Adder
16.801
276901AD2-066 C O1
Solar/Wind Harmer
3.143
274696ROCKY RD ;4P
Adder
9.924
274695ROCKY RD ;2P
Adder
9.693
274693ROCKY RD ;1P
Adder
9.597
274697ROCKY RD ;3P
Adder
2.633
972235AH1-702 GEN1
Adder
2.12
972236AH1-702 GEN2
Adder
1.843
971341AH1-150 GEN
Solar/Wind Harmer
16.545
971343AH1-151 GEN
Solar/Wind Harmer
16.545
274764LEE CO EC;5U
Adder
7.693
274765LEE CO EC;6U
Adder
7.693
274762LEE CO EC;3U
Adder
7.675
274763LEE CO EC;4U
Adder
7.603
938861AE1-114 GEN
Solar/Wind Harmer
6.756
276158O29GEN2
Solar/Wind Harmer
4.082
276157O29GEN1
Solar/Wind Harmer
3.103
276645AC1-214 GEN1
Solar/Wind Harmer
1.06
960751AF2-366 GEN
Solar/Wind Harmer
2.215
962691AG1-118 GEN
Solar/Wind Harmer
23.124
276893AG1-478 C
Solar/Wind Harmer
0.277
960281AF2-319 GEN
50/50
5.867
274732ELWOOD EC;7P
50/50
33.881
274861TOP CROP ;1U
Solar/Wind Harmer
15.285
276882AE2-255 GEN
Solar/Wind Harmer
4.827
970569AG2-363 GEN
Solar/Wind Harmer
40.928
276805AD2-038 GEN
Solar/Wind Harmer
6.805
274676JOLIET 29;8U
Adder
40.519
276694AA1-018 GEN2
Solar/Wind Harmer
8.272
276691AA1-018 GEN1
Solar/Wind Harmer
0.989
971997AH1-543 GEN
Solar/Wind Harmer
18.453
274682WAUKEGAN ;7U
Adder
17.038
274828WAUKEGAN ;BP
Adder
10.448
274822ROCKFORD ;11
Adder
16.556
274848CAMPGROVE;RU
Solar/Wind Harmer
5.423
970819AG2-516 GEN
Solar/Wind Harmer
10.067
957471AF2-041 GEN
Solar/Wind Harmer
24.818
959081AF2-199 GEN
Solar/Wind Harmer
8.273
971067AG2-660 GEN
Solar/Wind Harmer
1.924
274858EASY ROAD;U2
Solar/Wind Harmer
3.952
274761LEE CO EC;2U
Adder
7.675
274766LEE CO EC;7U
Adder
7.585
276708O09 GEN2
Solar/Wind Harmer
2.915
274745AC1-111 GEN9
Adder
4.517
276646AC1-214 GEN2
Solar/Wind Harmer
1.06
962781AG1-127 GEN
Solar/Wind Harmer
7.34
274872LEEDK;1U
Solar/Wind Harmer
6.311
274730ELWOOD EC;6P
50/50
33.881
274734ELWOOD EC;8P
50/50
33.881
274736ELWOOD EC;9P
50/50
33.881
274729ELWOOD EC;1P
50/50
33.705
274862TOP CROP ;2U
Solar/Wind Harmer
12.762
276868AE1-113 GEN
Solar/Wind Harmer
14.481
274879MINONK ;1U
Solar/Wind Harmer
9.654
970571AG2-364 GEN
Solar/Wind Harmer
27.285
274676JOLIET 29;8U
Adder
39.072
274682WAUKEGAN ;7U
Adder
17.038
959091AF2-200 GEN
Solar/Wind Harmer
16.545
274857EASY ROAD;U1
Solar/Wind Harmer
3.952
274760LEE CO EC;1U
Adder
7.675
274767LEE CO EC;8U
Adder
7.585
274878BISHOP HL;2U
Solar/Wind Harmer
2.776
276782AC1-033 GEN
Solar/Wind Harmer
3.281
276603SUBLETTE C
Solar/Wind Harmer
0.853
965931AG1-462 GEN
Solar/Wind Harmer
20.225
971087AG2-675 GEN
Solar/Wind Harmer
2.951
274851PROVIDENC;RU
Solar/Wind Harmer
2.254
274849CRESCENT ;1U
Solar/Wind Harmer
1.463
274855GSG-6 ;RU
Solar/Wind Harmer
2.881
274850MENDOTA H;RU
Solar/Wind Harmer
2.003
276602WESTBROOK C
Solar/Wind Harmer
1.659
276799AD1-013 GEN
Solar/Wind Harmer
1.722
946671AF1-331 GEN
Solar/Wind Harmer
0.326
943121AE2-341 GEN
Solar/Wind Harmer
9.885
943591AF1-030 GEN
Solar/Wind Harmer
6.59
276642AD2-194 GEN2
50/50
7.638
274728ELWOOD EC;5P
50/50
33.881
276640AD2-194 GEN1
50/50
7.598
274731ELWOOD EC;2P
50/50
33.705
274733ELWOOD EC;3P
50/50
33.705
274735ELWOOD EC;4P
50/50
33.705
276889AE2-281 GEN
Solar/Wind Harmer
2.588
970073AG2-061 GEN
Solar/Wind Harmer
3.086
274675JOLIET 29;7U
Adder
40.372
274675JOLIET 29;7U
Adder
38.931
971411AH1-196 GEN
Solar/Wind Harmer
12.928
274823ROCKFORD ;21
Adder
16.436
274856ECOGROVE ;U1
Solar/Wind Harmer
2.814
276611AD2-172 GEN
Solar/Wind Harmer
2.135
276612AE2-035 GEN
Solar/Wind Harmer
2.135
971171AH1-044 GEN
Solar/Wind Harmer
16.545
274877BISHOP HL;1U
Solar/Wind Harmer
2.776
971681AH1-341 GEN
Solar/Wind Harmer
12.308
276741O09 GEN1
Solar/Wind Harmer
2.915
972267AH1-718 GEN
Adder
3.392
274744AC1-111 GEN8
Adder
4.517
274746AC1-111 G10
Adder
4.517
946321AF1-296 GEN
Solar/Wind Harmer
8.283
276861AD2-134 GEN
Solar/Wind Harmer
1.393
276863AD2-134 GEN
Solar/Wind Harmer
1.393
971675AH1-338 GEN
Solar/Wind Harmer
14.039
276893AG1-478 C
Solar/Wind Harmer
0.348
926823AC1-168 GEN
Solar/Wind Harmer
2.669
970169AG2-114 GEN
Solar/Wind Harmer
5.586
960681AF2-359 GEN
Solar/Wind Helper
1.073
991777J1629 G
External Queue
10.490361213684082
990512J1326
External Queue
4.515235424041748
991278J1725 G
External Queue
2.4822452068328857
990752J1383
External Queue
7.158536434173584
990117J1214
External Queue
15.532408714294434
990727J1377 G
External Queue
5.1639275550842285
991092J1477
External Queue
2.687804698944092
991303J1755 G
External Queue
3.789165735244751
990407J1304
External Queue
3.459912061691284
NYPJM->LTFIMP_NY
CLTF
0.619
WECLTFEXP_WEC->PJM
CLTF
3.38
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.167
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.067
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.549
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.759
MECLTFEXP_MEC->PJM
CLTF
10.835
SIGELTFEXP_SIGE->PJM
CLTF
0.009
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.307
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.865
LAGNLTFEXP_LAGN->PJM
CLTF
3.651
TVALTFEXP_TVA->PJM
CLTF
0.977

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614__SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_116-45-L11614__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.83 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2545.8
MW Contribution:
10.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
276872AE1-163_GEN1
Solar/Wind Harmer
8.815
276876AE1-163_GEN2
Solar/Wind Harmer
8.815
958491AF2-143 GEN
Solar/Wind Harmer
19.393
958481AF2-142 GEN
Solar/Wind Harmer
19.179
276901AD2-066 C O1
Solar/Wind Harmer
2.895
274683WAUKEGAN ;8U
Adder
16.194
274683WAUKEGAN ;8U
Adder
13.651
276645AC1-214 GEN1
Solar/Wind Harmer
0.979
274696ROCKY RD ;4P
Adder
8.249
274695ROCKY RD ;2P
Adder
8.057
274693ROCKY RD ;1P
Adder
7.977
274697ROCKY RD ;3P
Adder
2.189
276158O29GEN2
Solar/Wind Harmer
3.595
276157O29GEN1
Solar/Wind Harmer
2.733
972236AH1-702 GEN2
Adder
1.559
972235AH1-702 GEN1
Adder
1.793
274764LEE CO EC;5U
Adder
6.595
274765LEE CO EC;6U
Adder
6.595
274762LEE CO EC;3U
Adder
6.579
274763LEE CO EC;4U
Adder
6.517
971341AH1-150 GEN
Solar/Wind Harmer
14.117
959351AF2-226 GEN
50/50
5.952
274730ELWOOD EC;6P
50/50
33.34
274734ELWOOD EC;8P
50/50
33.34
274736ELWOOD EC;9P
50/50
33.34
274729ELWOOD EC;1P
50/50
33.153
274862TOP CROP ;2U
Solar/Wind Harmer
12.946
276868AE1-113 GEN
Solar/Wind Harmer
13.894
274879MINONK ;1U
Solar/Wind Harmer
9.263
970571AG2-364 GEN
Solar/Wind Harmer
26.525
274676JOLIET 29;8U
Adder
28.492
274682WAUKEGAN ;7U
Adder
13.828
274878BISHOP HL;2U
Solar/Wind Harmer
2.56
276782AC1-033 GEN
Solar/Wind Harmer
3.025
274851PROVIDENC;RU
Solar/Wind Harmer
2.083
274849CRESCENT ;1U
Solar/Wind Harmer
1.352
274857EASY ROAD;U1
Solar/Wind Harmer
3.388
274760LEE CO EC;1U
Adder
6.579
274767LEE CO EC;8U
Adder
6.502
959091AF2-200 GEN
Solar/Wind Harmer
14.117
276603SUBLETTE C
Solar/Wind Harmer
0.736
965931AG1-462 GEN
Solar/Wind Harmer
17.788
971087AG2-675 GEN
Solar/Wind Harmer
2.596
274855GSG-6 ;RU
Solar/Wind Harmer
2.458
274850MENDOTA H;RU
Solar/Wind Harmer
1.709
276602WESTBROOK C
Solar/Wind Harmer
1.415
276799AD1-013 GEN
Solar/Wind Harmer
1.469
946671AF1-331 GEN
Solar/Wind Harmer
0.278
943121AE2-341 GEN
Solar/Wind Harmer
8.382
943591AF1-030 GEN
Solar/Wind Harmer
5.588
274772LINCOLN ;3U
Adder
3.308
960281AF2-319 GEN
50/50
5.952
274732ELWOOD EC;7P
50/50
33.34
274861TOP CROP ;1U
Solar/Wind Harmer
15.506
276882AE2-255 GEN
Solar/Wind Harmer
4.632
970569AG2-363 GEN
Solar/Wind Harmer
39.788
276805AD2-038 GEN
Solar/Wind Harmer
6.63
276694AA1-018 GEN2
Solar/Wind Harmer
8.068
276691AA1-018 GEN1
Solar/Wind Harmer
0.964
971997AH1-543 GEN
Solar/Wind Harmer
17.337
274676JOLIET 29;8U
Adder
29.547
274848CAMPGROVE;RU
Solar/Wind Harmer
5.036
274682WAUKEGAN ;7U
Adder
13.828
274828WAUKEGAN ;BP
Adder
8.488
276646AC1-214 GEN2
Solar/Wind Harmer
0.979
276708O09 GEN2
Solar/Wind Harmer
2.567
274822ROCKFORD ;11
Adder
13.963
970819AG2-516 GEN
Solar/Wind Harmer
8.517
274858EASY ROAD;U2
Solar/Wind Harmer
3.388
274761LEE CO EC;2U
Adder
6.579
274766LEE CO EC;7U
Adder
6.502
957471AF2-041 GEN
Solar/Wind Harmer
21.176
959081AF2-199 GEN
Solar/Wind Harmer
7.059
971067AG2-660 GEN
Solar/Wind Harmer
1.642
274745AC1-111 GEN9
Adder
3.798
962781AG1-127 GEN
Solar/Wind Harmer
6.22
274872LEEDK;1U
Solar/Wind Harmer
5.36
972207SS24-0001
Solar/Wind Harmer
11.761
274773LINCOLN ;4U
Adder
3.308
274774LINCOLN ;5U
Adder
3.308
276642AD2-194 GEN2
50/50
7.516
274728ELWOOD EC;5P
50/50
33.34
276640AD2-194 GEN1
50/50
7.474
274731ELWOOD EC;2P
50/50
33.153
274733ELWOOD EC;3P
50/50
33.153
274735ELWOOD EC;4P
50/50
33.153
276889AE2-281 GEN
Solar/Wind Harmer
2.518
970073AG2-061 GEN
Solar/Wind Harmer
3.007
274675JOLIET 29;7U
Adder
29.322
274675JOLIET 29;7U
Adder
28.275
274877BISHOP HL;1U
Solar/Wind Harmer
2.56
971411AH1-196 GEN
Solar/Wind Harmer
10.825
276741O09 GEN1
Solar/Wind Harmer
2.567
274823ROCKFORD ;21
Adder
13.862
971343AH1-151 GEN
Solar/Wind Harmer
14.117
938861AE1-114 GEN
Solar/Wind Harmer
5.784
960751AF2-366 GEN
Solar/Wind Harmer
1.877
962691AG1-118 GEN
Solar/Wind Harmer
19.589
276893AG1-478 C
Solar/Wind Harmer
0.247
274770LINCOLN ;1U
Adder
3.308
274771LINCOLN ;2U
Adder
3.308
274856ECOGROVE ;U1
Solar/Wind Harmer
2.389
276611AD2-172 GEN
Solar/Wind Harmer
1.813
276612AE2-035 GEN
Solar/Wind Harmer
1.813
971171AH1-044 GEN
Solar/Wind Harmer
14.117
972267AH1-718 GEN
Adder
2.933
971681AH1-341 GEN
Solar/Wind Harmer
10.557
946321AF1-296 GEN
Solar/Wind Harmer
7.269
274744AC1-111 GEN8
Adder
3.798
274746AC1-111 G10
Adder
3.798
276861AD2-134 GEN
Solar/Wind Harmer
1.189
276863AD2-134 GEN
Solar/Wind Harmer
1.189
971675AH1-338 GEN
Solar/Wind Harmer
11.975
926823AC1-168 GEN
Solar/Wind Harmer
2.474
276893AG1-478 C
Solar/Wind Harmer
0.31
970169AG2-114 GEN
Solar/Wind Harmer
5.43
274775LINCOLN ;6U
Adder
3.308
274776LINCOLN ;7U
Adder
3.308
274777LINCOLN ;8U
Adder
3.308
960681AF2-359 GEN
Solar/Wind Helper
1.028
991777J1629 G
External Queue
8.684741973876953
990512J1326
External Queue
3.774540424346924
991278J1725 G
External Queue
2.536900758743286
990752J1383
External Queue
7.192905426025391
990117J1214
External Queue
12.984417915344238
990727J1377 G
External Queue
4.313335418701172
991303J1755 G
External Queue
3.670567035675049
990407J1304
External Queue
2.8755862712860107
NYPJM->LTFIMP_NY
CLTF
0.56
WECLTFEXP_WEC->PJM
CLTF
2.794
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.145
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.013
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.831
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.567
MECLTFEXP_MEC->PJM
CLTF
9.574
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.747
LAGNLTFEXP_LAGN->PJM
CLTF
3.317
TVALTFEXP_TVA->PJM
CLTF
0.903

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82____SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_116-45-TR82____SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.84 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2431.22
MW Contribution:
10.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
276872AE1-163_GEN1
Solar/Wind Harmer
8.826
276876AE1-163_GEN2
Solar/Wind Harmer
8.826
958491AF2-143 GEN
Solar/Wind Harmer
19.423
958481AF2-142 GEN
Solar/Wind Harmer
19.212
276901AD2-066 C O1
Solar/Wind Harmer
2.912
274683WAUKEGAN ;8U
Adder
16.328
274683WAUKEGAN ;8U
Adder
13.764
276645AC1-214 GEN1
Solar/Wind Harmer
0.977
274696ROCKY RD ;4P
Adder
8.284
274695ROCKY RD ;2P
Adder
8.091
274693ROCKY RD ;1P
Adder
8.011
274697ROCKY RD ;3P
Adder
2.198
276158O29GEN2
Solar/Wind Harmer
3.597
276157O29GEN1
Solar/Wind Harmer
2.735
972235AH1-702 GEN1
Adder
1.799
972236AH1-702 GEN2
Adder
1.564
274764LEE CO EC;5U
Adder
6.609
274765LEE CO EC;6U
Adder
6.609
274762LEE CO EC;3U
Adder
6.594
274763LEE CO EC;4U
Adder
6.532
971341AH1-150 GEN
Solar/Wind Harmer
14.146
971343AH1-151 GEN
Solar/Wind Harmer
14.146
938861AE1-114 GEN
Solar/Wind Harmer
5.797
960751AF2-366 GEN
Solar/Wind Harmer
1.88
962691AG1-118 GEN
Solar/Wind Harmer
19.624
276893AG1-478 C
Solar/Wind Harmer
0.255
960281AF2-319 GEN
50/50
5.972
274732ELWOOD EC;7P
50/50
33.436
274861TOP CROP ;1U
Solar/Wind Harmer
15.558
276882AE2-255 GEN
Solar/Wind Harmer
4.645
970569AG2-363 GEN
Solar/Wind Harmer
39.832
276805AD2-038 GEN
Solar/Wind Harmer
6.64
276694AA1-018 GEN2
Solar/Wind Harmer
8.082
276691AA1-018 GEN1
Solar/Wind Harmer
0.966
971997AH1-543 GEN
Solar/Wind Harmer
17.296
274676JOLIET 29;8U
Adder
30.007
274848CAMPGROVE;RU
Solar/Wind Harmer
5.024
274682WAUKEGAN ;7U
Adder
13.945
274828WAUKEGAN ;BP
Adder
8.559
276646AC1-214 GEN2
Solar/Wind Harmer
0.977
276708O09 GEN2
Solar/Wind Harmer
2.568
274822ROCKFORD ;11
Adder
14.012
970819AG2-516 GEN
Solar/Wind Harmer
8.544
274858EASY ROAD;U2
Solar/Wind Harmer
3.395
274761LEE CO EC;2U
Adder
6.594
274766LEE CO EC;7U
Adder
6.516
957471AF2-041 GEN
Solar/Wind Harmer
21.219
959081AF2-199 GEN
Solar/Wind Harmer
7.073
971067AG2-660 GEN
Solar/Wind Harmer
1.645
274745AC1-111 GEN9
Adder
3.807
962781AG1-127 GEN
Solar/Wind Harmer
6.231
274872LEEDK;1U
Solar/Wind Harmer
5.368
959351AF2-226 GEN
50/50
5.972
274730ELWOOD EC;6P
50/50
33.436
274734ELWOOD EC;8P
50/50
33.436
274736ELWOOD EC;9P
50/50
33.436
274729ELWOOD EC;1P
50/50
33.247
274862TOP CROP ;2U
Solar/Wind Harmer
12.99
276868AE1-113 GEN
Solar/Wind Harmer
13.935
274879MINONK ;1U
Solar/Wind Harmer
9.29
970571AG2-364 GEN
Solar/Wind Harmer
26.554
274676JOLIET 29;8U
Adder
28.935
274682WAUKEGAN ;7U
Adder
13.945
274878BISHOP HL;2U
Solar/Wind Harmer
2.555
276782AC1-033 GEN
Solar/Wind Harmer
3.019
274851PROVIDENC;RU
Solar/Wind Harmer
2.078
274849CRESCENT ;1U
Solar/Wind Harmer
1.349
274857EASY ROAD;U1
Solar/Wind Harmer
3.395
274760LEE CO EC;1U
Adder
6.594
274767LEE CO EC;8U
Adder
6.516
959091AF2-200 GEN
Solar/Wind Harmer
14.146
276603SUBLETTE C
Solar/Wind Harmer
0.737
965931AG1-462 GEN
Solar/Wind Harmer
17.801
971087AG2-675 GEN
Solar/Wind Harmer
2.597
274855GSG-6 ;RU
Solar/Wind Harmer
2.462
274850MENDOTA H;RU
Solar/Wind Harmer
1.712
276602WESTBROOK C
Solar/Wind Harmer
1.417
276799AD1-013 GEN
Solar/Wind Harmer
1.471
946671AF1-331 GEN
Solar/Wind Harmer
0.279
943121AE2-341 GEN
Solar/Wind Harmer
8.365
943591AF1-030 GEN
Solar/Wind Harmer
5.576
276642AD2-194 GEN2
50/50
7.538
274728ELWOOD EC;5P
50/50
33.436
276640AD2-194 GEN1
50/50
7.495
274731ELWOOD EC;2P
50/50
33.247
274733ELWOOD EC;3P
50/50
33.247
274735ELWOOD EC;4P
50/50
33.247
276889AE2-281 GEN
Solar/Wind Harmer
2.522
970073AG2-061 GEN
Solar/Wind Harmer
3.011
274675JOLIET 29;7U
Adder
29.782
274675JOLIET 29;7U
Adder
28.718
274877BISHOP HL;1U
Solar/Wind Harmer
2.555
971411AH1-196 GEN
Solar/Wind Harmer
10.869
276741O09 GEN1
Solar/Wind Harmer
2.568
274823ROCKFORD ;21
Adder
13.91
274856ECOGROVE ;U1
Solar/Wind Harmer
2.397
276611AD2-172 GEN
Solar/Wind Harmer
1.818
276612AE2-035 GEN
Solar/Wind Harmer
1.818
971171AH1-044 GEN
Solar/Wind Harmer
14.146
972267AH1-718 GEN
Adder
2.938
971681AH1-341 GEN
Solar/Wind Harmer
10.58
946321AF1-296 GEN
Solar/Wind Harmer
7.274
274744AC1-111 GEN8
Adder
3.807
274746AC1-111 G10
Adder
3.807
276861AD2-134 GEN
Solar/Wind Harmer
1.191
276863AD2-134 GEN
Solar/Wind Harmer
1.191
971675AH1-338 GEN
Solar/Wind Harmer
11.994
276893AG1-478 C
Solar/Wind Harmer
0.32
926823AC1-168 GEN
Solar/Wind Harmer
2.462
970169AG2-114 GEN
Solar/Wind Harmer
5.196
960681AF2-359 GEN
Solar/Wind Helper
1.001
991777J1629 G
External Queue
8.716798782348633
990512J1326
External Queue
3.783268690109253
991278J1725 G
External Queue
2.4970204830169678
990752J1383
External Queue
7.115962982177734
990117J1214
External Queue
13.014443397521973
990727J1377 G
External Queue
4.322702884674072
991303J1755 G
External Queue
3.6442923545837402
990407J1304
External Queue
2.883732318878174
NYPJM->LTFIMP_NY
CLTF
0.561
WECLTFEXP_WEC->PJM
CLTF
2.812
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.061
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.569
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.515
MECLTFEXP_MEC->PJM
CLTF
9.569
SIGELTFEXP_SIGE->PJM
CLTF
0.009
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.272
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.764
LAGNLTFEXP_LAGN->PJM
CLTF
3.286
TVALTFEXP_TVA->PJM
CLTF
0.888

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_116_GG-345R__2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.84 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2431.21
MW Contribution:
10.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
276642AD2-194 GEN2
50/50
7.538
274728ELWOOD EC;5P
50/50
33.436
276640AD2-194 GEN1
50/50
7.495
274731ELWOOD EC;2P
50/50
33.247
274733ELWOOD EC;3P
50/50
33.247
274735ELWOOD EC;4P
50/50
33.247
276889AE2-281 GEN
Solar/Wind Harmer
2.522
970073AG2-061 GEN
Solar/Wind Harmer
3.011
274675JOLIET 29;7U
Adder
29.782
274675JOLIET 29;7U
Adder
28.718
274877BISHOP HL;1U
Solar/Wind Harmer
2.555
971411AH1-196 GEN
Solar/Wind Harmer
10.869
276741O09 GEN1
Solar/Wind Harmer
2.568
274823ROCKFORD ;21
Adder
13.91
274856ECOGROVE ;U1
Solar/Wind Harmer
2.397
276611AD2-172 GEN
Solar/Wind Harmer
1.818
276612AE2-035 GEN
Solar/Wind Harmer
1.818
971171AH1-044 GEN
Solar/Wind Harmer
14.146
972267AH1-718 GEN
Adder
2.938
971681AH1-341 GEN
Solar/Wind Harmer
10.58
946321AF1-296 GEN
Solar/Wind Harmer
7.274
274744AC1-111 GEN8
Adder
3.807
274746AC1-111 G10
Adder
3.807
276861AD2-134 GEN
Solar/Wind Harmer
1.191
276863AD2-134 GEN
Solar/Wind Harmer
1.191
971675AH1-338 GEN
Solar/Wind Harmer
11.994
276893AG1-478 C
Solar/Wind Harmer
0.32
926823AC1-168 GEN
Solar/Wind Harmer
2.462
970169AG2-114 GEN
Solar/Wind Harmer
5.196
960681AF2-359 GEN
Solar/Wind Helper
1.001
276872AE1-163_GEN1
Solar/Wind Harmer
8.826
276876AE1-163_GEN2
Solar/Wind Harmer
8.826
958491AF2-143 GEN
Solar/Wind Harmer
19.423
958481AF2-142 GEN
Solar/Wind Harmer
19.212
276901AD2-066 C O1
Solar/Wind Harmer
2.912
274683WAUKEGAN ;8U
Adder
16.328
274683WAUKEGAN ;8U
Adder
13.764
276645AC1-214 GEN1
Solar/Wind Harmer
0.977
960281AF2-319 GEN
50/50
5.972
274732ELWOOD EC;7P
50/50
33.436
274861TOP CROP ;1U
Solar/Wind Harmer
15.558
276882AE2-255 GEN
Solar/Wind Harmer
4.645
970569AG2-363 GEN
Solar/Wind Harmer
39.832
276805AD2-038 GEN
Solar/Wind Harmer
6.64
276694AA1-018 GEN2
Solar/Wind Harmer
8.082
276691AA1-018 GEN1
Solar/Wind Harmer
0.966
971997AH1-543 GEN
Solar/Wind Harmer
17.296
274676JOLIET 29;8U
Adder
30.007
274848CAMPGROVE;RU
Solar/Wind Harmer
5.024
274682WAUKEGAN ;7U
Adder
13.945
274828WAUKEGAN ;BP
Adder
8.559
276646AC1-214 GEN2
Solar/Wind Harmer
0.977
276708O09 GEN2
Solar/Wind Harmer
2.568
274822ROCKFORD ;11
Adder
14.012
970819AG2-516 GEN
Solar/Wind Harmer
8.544
274858EASY ROAD;U2
Solar/Wind Harmer
3.395
274761LEE CO EC;2U
Adder
6.594
274766LEE CO EC;7U
Adder
6.516
957471AF2-041 GEN
Solar/Wind Harmer
21.219
959081AF2-199 GEN
Solar/Wind Harmer
7.073
971067AG2-660 GEN
Solar/Wind Harmer
1.645
274745AC1-111 GEN9
Adder
3.807
962781AG1-127 GEN
Solar/Wind Harmer
6.231
274872LEEDK;1U
Solar/Wind Harmer
5.368
274696ROCKY RD ;4P
Adder
8.284
274695ROCKY RD ;2P
Adder
8.091
274693ROCKY RD ;1P
Adder
8.011
274697ROCKY RD ;3P
Adder
2.198
276158O29GEN2
Solar/Wind Harmer
3.597
276157O29GEN1
Solar/Wind Harmer
2.735
972235AH1-702 GEN1
Adder
1.799
972236AH1-702 GEN2
Adder
1.564
274764LEE CO EC;5U
Adder
6.609
274765LEE CO EC;6U
Adder
6.609
274762LEE CO EC;3U
Adder
6.594
274763LEE CO EC;4U
Adder
6.532
971341AH1-150 GEN
Solar/Wind Harmer
14.146
971343AH1-151 GEN
Solar/Wind Harmer
14.146
938861AE1-114 GEN
Solar/Wind Harmer
5.797
960751AF2-366 GEN
Solar/Wind Harmer
1.88
962691AG1-118 GEN
Solar/Wind Harmer
19.624
276893AG1-478 C
Solar/Wind Harmer
0.255
959351AF2-226 GEN
50/50
5.972
274730ELWOOD EC;6P
50/50
33.436
274734ELWOOD EC;8P
50/50
33.436
274736ELWOOD EC;9P
50/50
33.436
274729ELWOOD EC;1P
50/50
33.247
274862TOP CROP ;2U
Solar/Wind Harmer
12.99
276868AE1-113 GEN
Solar/Wind Harmer
13.935
274879MINONK ;1U
Solar/Wind Harmer
9.29
970571AG2-364 GEN
Solar/Wind Harmer
26.554
274676JOLIET 29;8U
Adder
28.935
274682WAUKEGAN ;7U
Adder
13.945
274878BISHOP HL;2U
Solar/Wind Harmer
2.555
276782AC1-033 GEN
Solar/Wind Harmer
3.019
274851PROVIDENC;RU
Solar/Wind Harmer
2.078
274849CRESCENT ;1U
Solar/Wind Harmer
1.349
274857EASY ROAD;U1
Solar/Wind Harmer
3.395
274760LEE CO EC;1U
Adder
6.594
274767LEE CO EC;8U
Adder
6.516
959091AF2-200 GEN
Solar/Wind Harmer
14.146
276603SUBLETTE C
Solar/Wind Harmer
0.737
965931AG1-462 GEN
Solar/Wind Harmer
17.801
971087AG2-675 GEN
Solar/Wind Harmer
2.597
274855GSG-6 ;RU
Solar/Wind Harmer
2.462
274850MENDOTA H;RU
Solar/Wind Harmer
1.712
276602WESTBROOK C
Solar/Wind Harmer
1.417
276799AD1-013 GEN
Solar/Wind Harmer
1.471
946671AF1-331 GEN
Solar/Wind Harmer
0.279
943121AE2-341 GEN
Solar/Wind Harmer
8.365
943591AF1-030 GEN
Solar/Wind Harmer
5.576
991777J1629 G
External Queue
8.716798782348633
990512J1326
External Queue
3.783268690109253
991278J1725 G
External Queue
2.4970204830169678
990752J1383
External Queue
7.115962982177734
990117J1214
External Queue
13.014443397521973
990727J1377 G
External Queue
4.322702884674072
991303J1755 G
External Queue
3.6442923545837402
990407J1304
External Queue
2.883732318878174
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.061
NYPJM->LTFIMP_NY
CLTF
0.561
WECLTFEXP_WEC->PJM
CLTF
2.812
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.515
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.534
MECLTFEXP_MEC->PJM
CLTF
9.569
SIGELTFEXP_SIGE->PJM
CLTF
0.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.272
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.764
LAGNLTFEXP_LAGN->PJM
CLTF
3.286
TVALTFEXP_TVA->PJM
CLTF
0.888

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_116-45-L0303___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.9 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2340.63
MW Contribution:
10.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
959351AF2-226 GEN
50/50
5.974
274730ELWOOD EC;6P
50/50
33.449
274734ELWOOD EC;8P
50/50
33.449
274736ELWOOD EC;9P
50/50
33.449
274729ELWOOD EC;1P
50/50
33.26
274862TOP CROP ;2U
Solar/Wind Harmer
12.994
276868AE1-113 GEN
Solar/Wind Harmer
13.942
274879MINONK ;1U
Solar/Wind Harmer
9.295
970571AG2-364 GEN
Solar/Wind Harmer
26.569
274676JOLIET 29;8U
Adder
28.956
274682WAUKEGAN ;7U
Adder
13.958
274878BISHOP HL;2U
Solar/Wind Harmer
2.557
276782AC1-033 GEN
Solar/Wind Harmer
3.022
274851PROVIDENC;RU
Solar/Wind Harmer
2.08
274849CRESCENT ;1U
Solar/Wind Harmer
1.35
274857EASY ROAD;U1
Solar/Wind Harmer
3.399
274760LEE CO EC;1U
Adder
6.6
274767LEE CO EC;8U
Adder
6.523
959091AF2-200 GEN
Solar/Wind Harmer
14.16
276603SUBLETTE C
Solar/Wind Harmer
0.738
965931AG1-462 GEN
Solar/Wind Harmer
17.819
971087AG2-675 GEN
Solar/Wind Harmer
2.6
274855GSG-6 ;RU
Solar/Wind Harmer
2.465
274850MENDOTA H;RU
Solar/Wind Harmer
1.714
276602WESTBROOK C
Solar/Wind Harmer
1.419
276799AD1-013 GEN
Solar/Wind Harmer
1.472
946671AF1-331 GEN
Solar/Wind Harmer
0.279
943121AE2-341 GEN
Solar/Wind Harmer
8.375
943591AF1-030 GEN
Solar/Wind Harmer
5.584
276642AD2-194 GEN2
50/50
7.54
274728ELWOOD EC;5P
50/50
33.449
276640AD2-194 GEN1
50/50
7.498
274731ELWOOD EC;2P
50/50
33.26
274733ELWOOD EC;3P
50/50
33.26
274735ELWOOD EC;4P
50/50
33.26
274675JOLIET 29;7U
Adder
29.804
274675JOLIET 29;7U
Adder
28.74
274877BISHOP HL;1U
Solar/Wind Harmer
2.557
971411AH1-196 GEN
Solar/Wind Harmer
10.88
276741O09 GEN1
Solar/Wind Harmer
2.571
274823ROCKFORD ;21
Adder
13.924
274856ECOGROVE ;U1
Solar/Wind Harmer
2.399
276611AD2-172 GEN
Solar/Wind Harmer
1.82
276612AE2-035 GEN
Solar/Wind Harmer
1.82
971171AH1-044 GEN
Solar/Wind Harmer
14.16
972267AH1-718 GEN
Adder
2.941
971681AH1-341 GEN
Solar/Wind Harmer
10.591
946321AF1-296 GEN
Solar/Wind Harmer
7.282
274744AC1-111 GEN8
Adder
3.811
274746AC1-111 G10
Adder
3.811
276861AD2-134 GEN
Solar/Wind Harmer
1.192
276863AD2-134 GEN
Solar/Wind Harmer
1.192
971675AH1-338 GEN
Solar/Wind Harmer
12.007
276893AG1-478 C
Solar/Wind Harmer
0.32
926823AC1-168 GEN
Solar/Wind Harmer
2.465
970169AG2-114 GEN
Solar/Wind Harmer
5.204
960681AF2-359 GEN
Solar/Wind Helper
1
276901AD2-066 C O1
Solar/Wind Harmer
2.915
274683WAUKEGAN ;8U
Adder
16.344
274683WAUKEGAN ;8U
Adder
13.777
276645AC1-214 GEN1
Solar/Wind Harmer
0.978
274696ROCKY RD ;4P
Adder
8.292
274695ROCKY RD ;2P
Adder
8.099
274693ROCKY RD ;1P
Adder
8.019
274697ROCKY RD ;3P
Adder
2.2
276158O29GEN2
Solar/Wind Harmer
3.601
276157O29GEN1
Solar/Wind Harmer
2.738
972235AH1-702 GEN1
Adder
1.801
972236AH1-702 GEN2
Adder
1.566
274764LEE CO EC;5U
Adder
6.616
274765LEE CO EC;6U
Adder
6.616
274762LEE CO EC;3U
Adder
6.6
274763LEE CO EC;4U
Adder
6.538
971341AH1-150 GEN
Solar/Wind Harmer
14.16
971343AH1-151 GEN
Solar/Wind Harmer
14.16
938861AE1-114 GEN
Solar/Wind Harmer
5.803
960751AF2-366 GEN
Solar/Wind Harmer
1.882
962691AG1-118 GEN
Solar/Wind Harmer
19.645
276893AG1-478 C
Solar/Wind Harmer
0.255
960281AF2-319 GEN
50/50
5.974
274732ELWOOD EC;7P
50/50
33.449
274861TOP CROP ;1U
Solar/Wind Harmer
15.563
276882AE2-255 GEN
Solar/Wind Harmer
4.648
970569AG2-363 GEN
Solar/Wind Harmer
39.853
971997AH1-543 GEN
Solar/Wind Harmer
17.308
274676JOLIET 29;8U
Adder
30.029
274848CAMPGROVE;RU
Solar/Wind Harmer
5.029
274682WAUKEGAN ;7U
Adder
13.958
274828WAUKEGAN ;BP
Adder
8.567
276646AC1-214 GEN2
Solar/Wind Harmer
0.978
276708O09 GEN2
Solar/Wind Harmer
2.571
274822ROCKFORD ;11
Adder
14.026
970819AG2-516 GEN
Solar/Wind Harmer
8.553
274858EASY ROAD;U2
Solar/Wind Harmer
3.399
274761LEE CO EC;2U
Adder
6.6
274766LEE CO EC;7U
Adder
6.523
957471AF2-041 GEN
Solar/Wind Harmer
21.24
959081AF2-199 GEN
Solar/Wind Harmer
7.08
971067AG2-660 GEN
Solar/Wind Harmer
1.647
274745AC1-111 GEN9
Adder
3.811
962781AG1-127 GEN
Solar/Wind Harmer
6.238
274872LEEDK;1U
Solar/Wind Harmer
5.374
991777J1629 G
External Queue
8.716798782348633
990512J1326
External Queue
3.783268690109253
991278J1725 G
External Queue
2.4970204830169678
990752J1383
External Queue
7.115962982177734
990117J1214
External Queue
13.014443397521973
990727J1377 G
External Queue
4.322702884674072
991303J1755 G
External Queue
3.6442923545837402
990407J1304
External Queue
2.883732318878174
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
NYPJM->LTFIMP_NY
CLTF
0.556
WECLTFEXP_WEC->PJM
CLTF
2.815
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.675
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.543
MECLTFEXP_MEC->PJM
CLTF
9.581
SIGELTFEXP_SIGE->PJM
CLTF
0.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.145
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.632
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.267
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.75
LAGNLTFEXP_LAGN->PJM
CLTF
3.301
TVALTFEXP_TVA->PJM
CLTF
0.895

Details for WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.66 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1654.96
MW Contribution:
11.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.145
274771LINCOLN ;2U
50/50
10.145
276897AD1-100 C
Solar/Wind Harmer
49.591
274888KELLY CRK;1U
Solar/Wind Harmer
5.384
276776AD2-060 GEN
Solar/Wind Harmer
0.382
958011AF2-095 GEN
Solar/Wind Harmer
13.138
970941AG2-585 GEN
Solar/Wind Harmer
5.018
276893AG1-478 C
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
13.127
958481AF2-142 GEN
Solar/Wind Harmer
12.416
274696ROCKY RD ;4P
Adder
9.344
274695ROCKY RD ;2P
Adder
9.129
274693ROCKY RD ;1P
Adder
9.039
274697ROCKY RD ;3P
Adder
2.48
274683WAUKEGAN ;8U
Adder
17.241
274683WAUKEGAN ;8U
Adder
14.534
962691AG1-118 GEN
Solar/Wind Harmer
24.235
958491AF2-143 GEN
Solar/Wind Harmer
12.104
960751AF2-366 GEN
Solar/Wind Harmer
2.308
276901AD2-066 C O1
Solar/Wind Harmer
2.81
971341AH1-150 GEN
Solar/Wind Harmer
15.583
971343AH1-151 GEN
Solar/Wind Harmer
15.583
276872AE1-163_GEN1
Solar/Wind Harmer
5.224
276876AE1-163_GEN2
Solar/Wind Harmer
5.224
972235AH1-702 GEN1
Adder
1.947
972236AH1-702 GEN2
Adder
1.693
938861AE1-114 GEN
Solar/Wind Harmer
6.199
274764LEE CO EC;5U
Adder
7.004
274765LEE CO EC;6U
Adder
7.004
274762LEE CO EC;3U
Adder
6.987
274763LEE CO EC;4U
Adder
6.922
274773LINCOLN ;4U
50/50
10.145
274774LINCOLN ;5U
50/50
10.145
972207SS24-0001
Solar/Wind Harmer
33.993
941551AE2-152 GEN
Solar/Wind Harmer
4.842
939401AE1-172 GEN
Solar/Wind Harmer
13.647
274871GR RIDGE ;2U
Solar/Wind Harmer
6.711
274847GR RIDGE ;BU
Solar/Wind Harmer
4.413
274676JOLIET 29;8U
Adder
26.339
274732ELWOOD EC;7P
Adder
14.098
274674JOLIET 9 ;6U
Adder
13.127
274745AC1-111 GEN9
Adder
4.669
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
276691AA1-018 GEN1
Solar/Wind Harmer
0.624
274861TOP CROP ;1U
Solar/Wind Harmer
5.001
274682WAUKEGAN ;7U
Adder
14.738
274828WAUKEGAN ;BP
Adder
9.038
276805AD2-038 GEN
Solar/Wind Harmer
4.138
962781AG1-127 GEN
Solar/Wind Harmer
7.649
274872LEEDK;1U
Solar/Wind Harmer
6.576
276882AE2-255 GEN
Solar/Wind Harmer
2.684
971997AH1-543 GEN
Solar/Wind Harmer
12.45
957471AF2-041 GEN
Solar/Wind Harmer
23.374
959081AF2-199 GEN
Solar/Wind Harmer
7.791
971067AG2-660 GEN
Solar/Wind Harmer
1.812
274723RIVER EC ;12
Adder
13.918
274822ROCKFORD ;11
Adder
15.229
970819AG2-516 GEN
Solar/Wind Harmer
9.217
970569AG2-363 GEN
Solar/Wind Harmer
22.744
274858EASY ROAD;U2
Solar/Wind Harmer
3.598
274761LEE CO EC;2U
Adder
6.987
274766LEE CO EC;7U
Adder
6.905
274812UNIV PK N;8U
Adder
3.747
276655WTG1_EQ
Solar/Wind Harmer
6.415
276656WTG2_EQ
Solar/Wind Harmer
0.849
939741AE1-205 GEN
Solar/Wind Harmer
14.7
276708O09 GEN2
Solar/Wind Harmer
2.615
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
274751CRETE EC ;1U
Adder
3.162
274754CRETE EC ;4U
Adder
3.162
276686W4-005 GEN3
Solar/Wind Harmer
1.697
276621W2-048 GEN
Solar/Wind Harmer
3.297
965911AG1-460 GEN
Solar/Wind Harmer
0.657
274775LINCOLN ;6U
50/50
10.145
274776LINCOLN ;7U
50/50
10.145
274777LINCOLN ;8U
50/50
10.145
972227AH1-698 GEN1
50/50
2.59
274655BRAIDWOOD;2U
50/50
3.439
972228AH1-698 GEN2
50/50
3.673
274661LASCO STA;2U
50/50
5.008
274660LASCO STA;1U
50/50
6.482
274687WILL CNTY;4U
50/50
25.536
274687WILL CNTY;4U
50/50
25.536
274863CRW1-WTG
Solar/Wind Harmer
5.113
274864CRW2-WTG
Solar/Wind Harmer
5.113
960591AF2-350 GEN
Solar/Wind Harmer
9.124
970833AG2-524 GEN
Solar/Wind Harmer
7.586
970833AG2-524 GEN
Solar/Wind Harmer
3.528
276893AG1-478 C
Solar/Wind Harmer
0.478
274827FISK ;RP
Adder
6.663
274800UNIV PARK;3U
Adder
5.005
274801UNIV PARK;4U
Adder
5.005
274675JOLIET 29;7U
Adder
26.339
274675JOLIET 29;7U
Adder
25.399
274728ELWOOD EC;5P
Adder
14.098
274731ELWOOD EC;2P
Adder
14.098
274733ELWOOD EC;3P
Adder
14.098
274735ELWOOD EC;4P
Adder
14.098
274744AC1-111 GEN8
Adder
4.669
274746AC1-111 G10
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.093
970073AG2-061 GEN
Solar/Wind Harmer
1.877
971411AH1-196 GEN
Solar/Wind Harmer
11.85
971675AH1-338 GEN
Solar/Wind Harmer
14.177
276861AD2-134 GEN
Solar/Wind Harmer
1.405
276863AD2-134 GEN
Solar/Wind Harmer
1.405
971171AH1-044 GEN
Solar/Wind Harmer
15.583
276889AE2-281 GEN
Solar/Wind Harmer
1.493
274823ROCKFORD ;21
Adder
15.118
274856ECOGROVE ;U1
Solar/Wind Harmer
2.581
276611AD2-172 GEN
Solar/Wind Harmer
1.958
276612AE2-035 GEN
Solar/Wind Harmer
1.958
926823AC1-168 GEN
Solar/Wind Harmer
3.274
971681AH1-341 GEN
Solar/Wind Harmer
11.347
972267AH1-718 GEN
Adder
3.069
276726Z2-087_GEN
Solar/Wind Harmer
5.812
959341AF2-225 GEN
Solar/Wind Harmer
11.025
276741O09 GEN1
Solar/Wind Harmer
2.615
274877BISHOP HL;1U
Solar/Wind Harmer
2.414
274853TWINGROVE;U1
Solar/Wind Harmer
5.029
274854TWINGROVE;U2
Solar/Wind Harmer
4.924
946321AF1-296 GEN
Solar/Wind Harmer
7.28
276668AB2-070 GEN1
Solar/Wind Harmer
1.234
276848AB2-070 GEN3
Solar/Wind Harmer
1.234
276849AB2-070 GEN2
Solar/Wind Harmer
1.234
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
274805UNIV PK N;1U
Adder
3.755
274808UNIV PK N;4U
Adder
3.73
942111AE2-223 GEN
Solar/Wind Harmer
6.025
276158O29GEN2
Solar/Wind Harmer
3.662
276157O29GEN1
Solar/Wind Harmer
2.784
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
960611AF2-352 GEN
Solar/Wind Harmer
1.623
274880W4-005 GEN4
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276615X2-022 GEN
Solar/Wind Harmer
1.035
276838X2-022 GEN2
Solar/Wind Harmer
0.123
276916AD2-100_GEN
Solar/Wind Harmer
9.568
276911AD2-131_GEN
Solar/Wind Harmer
1.934
274772LINCOLN ;3U
50/50
10.145
274654BRAIDWOOD;1U
50/50
3.551
972259AH1-714 GEN
50/50
18.253
939351AE1-166 GEN
Solar/Wind Harmer
6.331
274887GEN-1.85
Solar/Wind Harmer
4.861
276772AC2-154 GEN
Solar/Wind Harmer
2.546
276843GEN-1.7
Solar/Wind Harmer
0.523
276806AD2-047 C O1
Solar/Wind Harmer
9.76
970707AG2-453 GEN
Solar/Wind Harmer
24.508
276164X3-005 C
Solar/Wind Harmer
0.608
274826FISK ;BP
Adder
9.402
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.398
274730ELWOOD EC;6P
Adder
14.098
274734ELWOOD EC;8P
Adder
14.098
274736ELWOOD EC;9P
Adder
14.098
274729ELWOOD EC;1P
Adder
14.098
943121AE2-341 GEN
Solar/Wind Harmer
12.523
943591AF1-030 GEN
Solar/Wind Harmer
8.349
274803UNIV PARK;6U
Adder
4.863
274862TOP CROP ;2U
Solar/Wind Harmer
4.176
274682WAUKEGAN ;7U
Adder
14.738
276868AE1-113 GEN
Solar/Wind Harmer
8.052
274879MINONK ;1U
Solar/Wind Harmer
5.368
276799AD1-013 GEN
Solar/Wind Harmer
1.741
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.906
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
274724RIVER EC ;11
Adder
13.811
959091AF2-200 GEN
Solar/Wind Harmer
15.583
970571AG2-364 GEN
Solar/Wind Harmer
15.163
274857EASY ROAD;U1
Solar/Wind Harmer
3.598
274760LEE CO EC;1U
Adder
6.987
274767LEE CO EC;8U
Adder
6.905
276603SUBLETTE C
Solar/Wind Harmer
0.785
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274811UNIV PK N;7U
Adder
3.747
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.336
276782AC1-033 GEN
Solar/Wind Harmer
2.854
274878BISHOP HL;2U
Solar/Wind Harmer
2.414
965091AG1-374 GEN
Solar/Wind Harmer
20.941
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.603
971087AG2-675 GEN
Solar/Wind Harmer
2.569
972231SS25-0005
Solar/Wind Harmer
6.139
972181SS23-001
Solar/Wind Harmer
3.837
274752CRETE EC ;2U
Adder
3.162
274753CRETE EC ;3U
Adder
3.162
276785W4-005 GEN1
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.186
957381AF2-032 GEN
Solar/Wind Harmer
0.952
942481AE2-261 GEN
Solar/Wind Harmer
14.068
990512J1326
External Queue
3.794844388961792
990117J1214
External Queue
13.054264068603516
990727J1377 G
External Queue
4.411266803741455
990407J1304
External Queue
2.936152935028076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.95
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.255
MECLTFEXP_MEC->PJM
CLTF
9.382
SIGELTFEXP_SIGE->PJM
CLTF
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.729
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
TVALTFEXP_TVA->PJM
CLTF
0.823

Details for WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.3 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1635.05
MW Contribution:
11.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
10.145
274776LINCOLN ;7U
50/50
10.145
274777LINCOLN ;8U
50/50
10.145
972227AH1-698 GEN1
50/50
2.59
274655BRAIDWOOD;2U
50/50
3.439
972228AH1-698 GEN2
50/50
3.673
274661LASCO STA;2U
50/50
5.008
274660LASCO STA;1U
50/50
6.482
274687WILL CNTY;4U
50/50
25.536
274687WILL CNTY;4U
50/50
25.536
274863CRW1-WTG
Solar/Wind Harmer
5.113
274864CRW2-WTG
Solar/Wind Harmer
5.113
960591AF2-350 GEN
Solar/Wind Harmer
9.124
970833AG2-524 GEN
Solar/Wind Harmer
7.586
970833AG2-524 GEN
Solar/Wind Harmer
3.528
276893AG1-478 C
Solar/Wind Harmer
0.478
274827FISK ;RP
Adder
6.663
274800UNIV PARK;3U
Adder
5.005
274801UNIV PARK;4U
Adder
5.005
274675JOLIET 29;7U
Adder
26.339
274675JOLIET 29;7U
Adder
25.399
274728ELWOOD EC;5P
Adder
14.098
274731ELWOOD EC;2P
Adder
14.098
274733ELWOOD EC;3P
Adder
14.098
274735ELWOOD EC;4P
Adder
14.098
274744AC1-111 GEN8
Adder
4.669
274746AC1-111 G10
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.093
970073AG2-061 GEN
Solar/Wind Harmer
1.877
971411AH1-196 GEN
Solar/Wind Harmer
11.85
971675AH1-338 GEN
Solar/Wind Harmer
14.177
276861AD2-134 GEN
Solar/Wind Harmer
1.405
276863AD2-134 GEN
Solar/Wind Harmer
1.405
971171AH1-044 GEN
Solar/Wind Harmer
15.583
276889AE2-281 GEN
Solar/Wind Harmer
1.493
274823ROCKFORD ;21
Adder
15.118
274856ECOGROVE ;U1
Solar/Wind Harmer
2.581
276611AD2-172 GEN
Solar/Wind Harmer
1.958
276612AE2-035 GEN
Solar/Wind Harmer
1.958
926823AC1-168 GEN
Solar/Wind Harmer
3.274
971681AH1-341 GEN
Solar/Wind Harmer
11.347
972267AH1-718 GEN
Adder
3.069
276726Z2-087_GEN
Solar/Wind Harmer
5.812
959341AF2-225 GEN
Solar/Wind Harmer
11.025
276741O09 GEN1
Solar/Wind Harmer
2.615
274877BISHOP HL;1U
Solar/Wind Harmer
2.414
274853TWINGROVE;U1
Solar/Wind Harmer
5.029
274854TWINGROVE;U2
Solar/Wind Harmer
4.924
946321AF1-296 GEN
Solar/Wind Harmer
7.28
276668AB2-070 GEN1
Solar/Wind Harmer
1.234
276848AB2-070 GEN3
Solar/Wind Harmer
1.234
276849AB2-070 GEN2
Solar/Wind Harmer
1.234
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
274770LINCOLN ;1U
50/50
10.145
274771LINCOLN ;2U
50/50
10.145
276897AD1-100 C
Solar/Wind Harmer
49.591
274888KELLY CRK;1U
Solar/Wind Harmer
5.384
276776AD2-060 GEN
Solar/Wind Harmer
0.382
958011AF2-095 GEN
Solar/Wind Harmer
13.138
970941AG2-585 GEN
Solar/Wind Harmer
5.018
276893AG1-478 C
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
13.127
958481AF2-142 GEN
Solar/Wind Harmer
12.416
274696ROCKY RD ;4P
Adder
9.344
274695ROCKY RD ;2P
Adder
9.129
274693ROCKY RD ;1P
Adder
9.039
274697ROCKY RD ;3P
Adder
2.48
274683WAUKEGAN ;8U
Adder
17.241
274683WAUKEGAN ;8U
Adder
14.534
274772LINCOLN ;3U
50/50
10.145
274654BRAIDWOOD;1U
50/50
3.551
972259AH1-714 GEN
50/50
18.253
939351AE1-166 GEN
Solar/Wind Harmer
6.331
274887GEN-1.85
Solar/Wind Harmer
4.861
276772AC2-154 GEN
Solar/Wind Harmer
2.546
276843GEN-1.7
Solar/Wind Harmer
0.523
276806AD2-047 C O1
Solar/Wind Harmer
9.76
970707AG2-453 GEN
Solar/Wind Harmer
24.508
276164X3-005 C
Solar/Wind Harmer
0.608
962691AG1-118 GEN
Solar/Wind Harmer
24.235
958491AF2-143 GEN
Solar/Wind Harmer
12.104
960751AF2-366 GEN
Solar/Wind Harmer
2.308
276901AD2-066 C O1
Solar/Wind Harmer
2.81
971341AH1-150 GEN
Solar/Wind Harmer
15.583
971343AH1-151 GEN
Solar/Wind Harmer
15.583
276872AE1-163_GEN1
Solar/Wind Harmer
5.224
276876AE1-163_GEN2
Solar/Wind Harmer
5.224
972235AH1-702 GEN1
Adder
1.947
972236AH1-702 GEN2
Adder
1.693
938861AE1-114 GEN
Solar/Wind Harmer
6.199
274764LEE CO EC;5U
Adder
7.004
274765LEE CO EC;6U
Adder
7.004
274762LEE CO EC;3U
Adder
6.987
274763LEE CO EC;4U
Adder
6.922
274805UNIV PK N;1U
Adder
3.755
274808UNIV PK N;4U
Adder
3.73
942111AE2-223 GEN
Solar/Wind Harmer
6.025
276158O29GEN2
Solar/Wind Harmer
3.662
276157O29GEN1
Solar/Wind Harmer
2.784
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
960611AF2-352 GEN
Solar/Wind Harmer
1.623
274880W4-005 GEN4
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276615X2-022 GEN
Solar/Wind Harmer
1.035
276838X2-022 GEN2
Solar/Wind Harmer
0.123
276916AD2-100_GEN
Solar/Wind Harmer
9.568
276911AD2-131_GEN
Solar/Wind Harmer
1.934
274826FISK ;BP
Adder
9.402
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.398
274730ELWOOD EC;6P
Adder
14.098
274734ELWOOD EC;8P
Adder
14.098
274736ELWOOD EC;9P
Adder
14.098
274729ELWOOD EC;1P
Adder
14.098
943121AE2-341 GEN
Solar/Wind Harmer
12.523
943591AF1-030 GEN
Solar/Wind Harmer
8.349
274803UNIV PARK;6U
Adder
4.863
274862TOP CROP ;2U
Solar/Wind Harmer
4.176
274682WAUKEGAN ;7U
Adder
14.738
276868AE1-113 GEN
Solar/Wind Harmer
8.052
274879MINONK ;1U
Solar/Wind Harmer
5.368
276799AD1-013 GEN
Solar/Wind Harmer
1.741
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.906
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
274724RIVER EC ;11
Adder
13.811
959091AF2-200 GEN
Solar/Wind Harmer
15.583
970571AG2-364 GEN
Solar/Wind Harmer
15.163
274857EASY ROAD;U1
Solar/Wind Harmer
3.598
274760LEE CO EC;1U
Adder
6.987
274767LEE CO EC;8U
Adder
6.905
276603SUBLETTE C
Solar/Wind Harmer
0.785
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274811UNIV PK N;7U
Adder
3.747
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.336
276782AC1-033 GEN
Solar/Wind Harmer
2.854
274878BISHOP HL;2U
Solar/Wind Harmer
2.414
965091AG1-374 GEN
Solar/Wind Harmer
20.941
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.603
971087AG2-675 GEN
Solar/Wind Harmer
2.569
972231SS25-0005
Solar/Wind Harmer
6.139
972181SS23-001
Solar/Wind Harmer
3.837
274752CRETE EC ;2U
Adder
3.162
274753CRETE EC ;3U
Adder
3.162
276785W4-005 GEN1
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.186
957381AF2-032 GEN
Solar/Wind Harmer
0.952
942481AE2-261 GEN
Solar/Wind Harmer
14.068
274773LINCOLN ;4U
50/50
10.145
274774LINCOLN ;5U
50/50
10.145
972207SS24-0001
Solar/Wind Harmer
33.993
941551AE2-152 GEN
Solar/Wind Harmer
4.842
939401AE1-172 GEN
Solar/Wind Harmer
13.647
274871GR RIDGE ;2U
Solar/Wind Harmer
6.711
274847GR RIDGE ;BU
Solar/Wind Harmer
4.413
274676JOLIET 29;8U
Adder
26.339
274732ELWOOD EC;7P
Adder
14.098
274674JOLIET 9 ;6U
Adder
13.127
274745AC1-111 GEN9
Adder
4.669
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
276691AA1-018 GEN1
Solar/Wind Harmer
0.624
274861TOP CROP ;1U
Solar/Wind Harmer
5.001
274682WAUKEGAN ;7U
Adder
14.738
274828WAUKEGAN ;BP
Adder
9.038
276805AD2-038 GEN
Solar/Wind Harmer
4.138
962781AG1-127 GEN
Solar/Wind Harmer
7.649
274872LEEDK;1U
Solar/Wind Harmer
6.576
276882AE2-255 GEN
Solar/Wind Harmer
2.684
971997AH1-543 GEN
Solar/Wind Harmer
12.45
957471AF2-041 GEN
Solar/Wind Harmer
23.374
959081AF2-199 GEN
Solar/Wind Harmer
7.791
971067AG2-660 GEN
Solar/Wind Harmer
1.812
274723RIVER EC ;12
Adder
13.918
274822ROCKFORD ;11
Adder
15.229
970819AG2-516 GEN
Solar/Wind Harmer
9.217
970569AG2-363 GEN
Solar/Wind Harmer
22.744
274858EASY ROAD;U2
Solar/Wind Harmer
3.598
274761LEE CO EC;2U
Adder
6.987
274766LEE CO EC;7U
Adder
6.905
274812UNIV PK N;8U
Adder
3.747
276655WTG1_EQ
Solar/Wind Harmer
6.415
276656WTG2_EQ
Solar/Wind Harmer
0.849
939741AE1-205 GEN
Solar/Wind Harmer
14.7
276708O09 GEN2
Solar/Wind Harmer
2.615
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
274751CRETE EC ;1U
Adder
3.162
274754CRETE EC ;4U
Adder
3.162
276686W4-005 GEN3
Solar/Wind Harmer
1.697
276621W2-048 GEN
Solar/Wind Harmer
3.297
965911AG1-460 GEN
Solar/Wind Harmer
0.657
990512J1326
External Queue
3.794844388961792
990117J1214
External Queue
13.054264068603516
990727J1377 G
External Queue
4.411265850067139
990407J1304
External Queue
2.936152935028076
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.95
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.729
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.255
MECLTFEXP_MEC->PJM
CLTF
9.382
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
TVALTFEXP_TVA->PJM
CLTF
0.823

Details for WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.3 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1635.01
MW Contribution:
11.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
10.145
274776LINCOLN ;7U
50/50
10.145
274777LINCOLN ;8U
50/50
10.145
972227AH1-698 GEN1
50/50
2.59
274655BRAIDWOOD;2U
50/50
3.439
972228AH1-698 GEN2
50/50
3.673
274661LASCO STA;2U
50/50
5.008
274660LASCO STA;1U
50/50
6.482
274687WILL CNTY;4U
50/50
25.536
274687WILL CNTY;4U
50/50
25.536
274863CRW1-WTG
Solar/Wind Harmer
5.113
274864CRW2-WTG
Solar/Wind Harmer
5.113
960591AF2-350 GEN
Solar/Wind Harmer
9.124
970833AG2-524 GEN
Solar/Wind Harmer
7.586
970833AG2-524 GEN
Solar/Wind Harmer
3.528
274770LINCOLN ;1U
50/50
10.145
274771LINCOLN ;2U
50/50
10.145
276897AD1-100 C
Solar/Wind Harmer
49.591
274888KELLY CRK;1U
Solar/Wind Harmer
5.384
276776AD2-060 GEN
Solar/Wind Harmer
0.382
958011AF2-095 GEN
Solar/Wind Harmer
13.138
970941AG2-585 GEN
Solar/Wind Harmer
5.018
276893AG1-478 C
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
13.127
958481AF2-142 GEN
Solar/Wind Harmer
12.416
274696ROCKY RD ;4P
Adder
9.344
274695ROCKY RD ;2P
Adder
9.129
274693ROCKY RD ;1P
Adder
9.039
274697ROCKY RD ;3P
Adder
2.48
274683WAUKEGAN ;8U
Adder
17.241
274683WAUKEGAN ;8U
Adder
14.534
962691AG1-118 GEN
Solar/Wind Harmer
24.235
958491AF2-143 GEN
Solar/Wind Harmer
12.104
960751AF2-366 GEN
Solar/Wind Harmer
2.308
276901AD2-066 C O1
Solar/Wind Harmer
2.81
971341AH1-150 GEN
Solar/Wind Harmer
15.583
971343AH1-151 GEN
Solar/Wind Harmer
15.583
276872AE1-163_GEN1
Solar/Wind Harmer
5.224
276876AE1-163_GEN2
Solar/Wind Harmer
5.224
972235AH1-702 GEN1
Adder
1.947
972236AH1-702 GEN2
Adder
1.693
938861AE1-114 GEN
Solar/Wind Harmer
6.199
274764LEE CO EC;5U
Adder
7.004
274765LEE CO EC;6U
Adder
7.004
274762LEE CO EC;3U
Adder
6.987
274763LEE CO EC;4U
Adder
6.922
274805UNIV PK N;1U
Adder
3.755
274808UNIV PK N;4U
Adder
3.73
942111AE2-223 GEN
Solar/Wind Harmer
6.025
276158O29GEN2
Solar/Wind Harmer
3.662
276157O29GEN1
Solar/Wind Harmer
2.784
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
960611AF2-352 GEN
Solar/Wind Harmer
1.623
274880W4-005 GEN4
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276615X2-022 GEN
Solar/Wind Harmer
1.035
276838X2-022 GEN2
Solar/Wind Harmer
0.123
276916AD2-100_GEN
Solar/Wind Harmer
9.568
276911AD2-131_GEN
Solar/Wind Harmer
1.934
274772LINCOLN ;3U
50/50
10.145
274654BRAIDWOOD;1U
50/50
3.551
972259AH1-714 GEN
50/50
18.253
939351AE1-166 GEN
Solar/Wind Harmer
6.331
274887GEN-1.85
Solar/Wind Harmer
4.861
276772AC2-154 GEN
Solar/Wind Harmer
2.546
276843GEN-1.7
Solar/Wind Harmer
0.523
276806AD2-047 C O1
Solar/Wind Harmer
9.76
970707AG2-453 GEN
Solar/Wind Harmer
24.508
276164X3-005 C
Solar/Wind Harmer
0.608
274826FISK ;BP
Adder
9.402
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.398
274730ELWOOD EC;6P
Adder
14.098
274734ELWOOD EC;8P
Adder
14.098
274736ELWOOD EC;9P
Adder
14.098
274729ELWOOD EC;1P
Adder
14.098
943121AE2-341 GEN
Solar/Wind Harmer
12.523
943591AF1-030 GEN
Solar/Wind Harmer
8.349
274803UNIV PARK;6U
Adder
4.863
274862TOP CROP ;2U
Solar/Wind Harmer
4.176
274682WAUKEGAN ;7U
Adder
14.738
276868AE1-113 GEN
Solar/Wind Harmer
8.052
274879MINONK ;1U
Solar/Wind Harmer
5.368
276799AD1-013 GEN
Solar/Wind Harmer
1.741
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.906
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
274724RIVER EC ;11
Adder
13.811
959091AF2-200 GEN
Solar/Wind Harmer
15.583
970571AG2-364 GEN
Solar/Wind Harmer
15.163
274857EASY ROAD;U1
Solar/Wind Harmer
3.598
274760LEE CO EC;1U
Adder
6.987
274767LEE CO EC;8U
Adder
6.905
276603SUBLETTE C
Solar/Wind Harmer
0.785
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274811UNIV PK N;7U
Adder
3.747
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.336
276782AC1-033 GEN
Solar/Wind Harmer
2.854
274878BISHOP HL;2U
Solar/Wind Harmer
2.414
965091AG1-374 GEN
Solar/Wind Harmer
20.941
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.603
971087AG2-675 GEN
Solar/Wind Harmer
2.569
972231SS25-0005
Solar/Wind Harmer
6.139
972181SS23-001
Solar/Wind Harmer
3.837
274752CRETE EC ;2U
Adder
3.162
274753CRETE EC ;3U
Adder
3.162
276785W4-005 GEN1
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.186
957381AF2-032 GEN
Solar/Wind Harmer
0.952
942481AE2-261 GEN
Solar/Wind Harmer
14.068
274773LINCOLN ;4U
50/50
10.145
274774LINCOLN ;5U
50/50
10.145
972207SS24-0001
Solar/Wind Harmer
33.993
941551AE2-152 GEN
Solar/Wind Harmer
4.842
939401AE1-172 GEN
Solar/Wind Harmer
13.647
274871GR RIDGE ;2U
Solar/Wind Harmer
6.711
274847GR RIDGE ;BU
Solar/Wind Harmer
4.413
274676JOLIET 29;8U
Adder
26.339
274732ELWOOD EC;7P
Adder
14.098
274674JOLIET 9 ;6U
Adder
13.127
274745AC1-111 GEN9
Adder
4.669
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
276691AA1-018 GEN1
Solar/Wind Harmer
0.624
274861TOP CROP ;1U
Solar/Wind Harmer
5.001
274682WAUKEGAN ;7U
Adder
14.738
274828WAUKEGAN ;BP
Adder
9.038
276805AD2-038 GEN
Solar/Wind Harmer
4.138
962781AG1-127 GEN
Solar/Wind Harmer
7.649
274872LEEDK;1U
Solar/Wind Harmer
6.576
276882AE2-255 GEN
Solar/Wind Harmer
2.684
971997AH1-543 GEN
Solar/Wind Harmer
12.45
957471AF2-041 GEN
Solar/Wind Harmer
23.374
959081AF2-199 GEN
Solar/Wind Harmer
7.791
971067AG2-660 GEN
Solar/Wind Harmer
1.812
274723RIVER EC ;12
Adder
13.918
274822ROCKFORD ;11
Adder
15.229
970819AG2-516 GEN
Solar/Wind Harmer
9.217
970569AG2-363 GEN
Solar/Wind Harmer
22.744
274858EASY ROAD;U2
Solar/Wind Harmer
3.598
274761LEE CO EC;2U
Adder
6.987
274766LEE CO EC;7U
Adder
6.905
274812UNIV PK N;8U
Adder
3.747
276655WTG1_EQ
Solar/Wind Harmer
6.415
276656WTG2_EQ
Solar/Wind Harmer
0.849
939741AE1-205 GEN
Solar/Wind Harmer
14.7
276708O09 GEN2
Solar/Wind Harmer
2.615
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
274751CRETE EC ;1U
Adder
3.162
274754CRETE EC ;4U
Adder
3.162
276686W4-005 GEN3
Solar/Wind Harmer
1.697
276621W2-048 GEN
Solar/Wind Harmer
3.297
965911AG1-460 GEN
Solar/Wind Harmer
0.657
276893AG1-478 C
Solar/Wind Harmer
0.478
274827FISK ;RP
Adder
6.663
274800UNIV PARK;3U
Adder
5.005
274801UNIV PARK;4U
Adder
5.005
274675JOLIET 29;7U
Adder
26.339
274675JOLIET 29;7U
Adder
25.399
274728ELWOOD EC;5P
Adder
14.098
274731ELWOOD EC;2P
Adder
14.098
274733ELWOOD EC;3P
Adder
14.098
274735ELWOOD EC;4P
Adder
14.098
274744AC1-111 GEN8
Adder
4.669
274746AC1-111 G10
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.093
970073AG2-061 GEN
Solar/Wind Harmer
1.877
971411AH1-196 GEN
Solar/Wind Harmer
11.85
971675AH1-338 GEN
Solar/Wind Harmer
14.177
276861AD2-134 GEN
Solar/Wind Harmer
1.405
276863AD2-134 GEN
Solar/Wind Harmer
1.405
971171AH1-044 GEN
Solar/Wind Harmer
15.583
276889AE2-281 GEN
Solar/Wind Harmer
1.493
274823ROCKFORD ;21
Adder
15.118
274856ECOGROVE ;U1
Solar/Wind Harmer
2.581
276611AD2-172 GEN
Solar/Wind Harmer
1.958
276612AE2-035 GEN
Solar/Wind Harmer
1.958
926823AC1-168 GEN
Solar/Wind Harmer
3.274
971681AH1-341 GEN
Solar/Wind Harmer
11.347
972267AH1-718 GEN
Adder
3.069
276726Z2-087_GEN
Solar/Wind Harmer
5.812
959341AF2-225 GEN
Solar/Wind Harmer
11.025
276741O09 GEN1
Solar/Wind Harmer
2.615
274877BISHOP HL;1U
Solar/Wind Harmer
2.414
274853TWINGROVE;U1
Solar/Wind Harmer
5.029
274854TWINGROVE;U2
Solar/Wind Harmer
4.924
946321AF1-296 GEN
Solar/Wind Harmer
7.28
276668AB2-070 GEN1
Solar/Wind Harmer
1.234
276848AB2-070 GEN3
Solar/Wind Harmer
1.234
276849AB2-070 GEN2
Solar/Wind Harmer
1.234
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
990512J1326
External Queue
3.794844388961792
990117J1214
External Queue
13.054264068603516
990727J1377 G
External Queue
4.411266803741455
990407J1304
External Queue
2.936152935028076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.95
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.255
MECLTFEXP_MEC->PJM
CLTF
9.382
SIGELTFEXP_SIGE->PJM
CLTF
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.729
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
TVALTFEXP_TVA->PJM
CLTF
0.823

Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.75 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1656.29
MW Contribution:
11.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.318
274771LINCOLN ;2U
50/50
10.318
276897AD1-100 C
Solar/Wind Harmer
49.166
274888KELLY CRK;1U
Solar/Wind Harmer
5.357
276776AD2-060 GEN
Solar/Wind Harmer
0.38
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
276893AG1-478 C
Solar/Wind Harmer
0.379
274674JOLIET 9 ;6U
Adder
13.082
958481AF2-142 GEN
Solar/Wind Harmer
12.398
274696ROCKY RD ;4P
Adder
9.313
274695ROCKY RD ;2P
Adder
9.099
274693ROCKY RD ;1P
Adder
9.009
274697ROCKY RD ;3P
Adder
2.472
274683WAUKEGAN ;8U
Adder
17.186
274683WAUKEGAN ;8U
Adder
14.487
958491AF2-143 GEN
Solar/Wind Harmer
12.08
962691AG1-118 GEN
Solar/Wind Harmer
24.15
960751AF2-366 GEN
Solar/Wind Harmer
2.3
276901AD2-066 C O1
Solar/Wind Harmer
2.799
971341AH1-150 GEN
Solar/Wind Harmer
15.529
971343AH1-151 GEN
Solar/Wind Harmer
15.529
276872AE1-163_GEN1
Solar/Wind Harmer
5.21
276876AE1-163_GEN2
Solar/Wind Harmer
5.21
972235AH1-702 GEN1
Adder
1.94
972236AH1-702 GEN2
Adder
1.687
938861AE1-114 GEN
Solar/Wind Harmer
6.178
274764LEE CO EC;5U
Adder
6.979
274765LEE CO EC;6U
Adder
6.979
274762LEE CO EC;3U
Adder
6.963
274763LEE CO EC;4U
Adder
6.897
274805UNIV PK N;1U
Adder
3.748
274808UNIV PK N;4U
Adder
3.723
942111AE2-223 GEN
Solar/Wind Harmer
5.984
276158O29GEN2
Solar/Wind Harmer
3.648
276157O29GEN1
Solar/Wind Harmer
2.774
276645AC1-214 GEN1
Solar/Wind Harmer
0.964
960611AF2-352 GEN
Solar/Wind Harmer
1.612
274880W4-005 GEN4
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276615X2-022 GEN
Solar/Wind Harmer
1.029
276838X2-022 GEN2
Solar/Wind Harmer
0.122
276916AD2-100_GEN
Solar/Wind Harmer
9.512
276911AD2-131_GEN
Solar/Wind Harmer
1.922
274772LINCOLN ;3U
50/50
10.318
274654BRAIDWOOD;1U
50/50
3.53
972259AH1-714 GEN
50/50
18.156
939351AE1-166 GEN
Solar/Wind Harmer
6.277
274887GEN-1.85
Solar/Wind Harmer
4.837
276772AC2-154 GEN
Solar/Wind Harmer
2.533
276843GEN-1.7
Solar/Wind Harmer
0.52
276806AD2-047 C O1
Solar/Wind Harmer
9.712
970707AG2-453 GEN
Solar/Wind Harmer
24.395
276164X3-005 C
Solar/Wind Harmer
0.607
274826FISK ;BP
Adder
9.382
274676JOLIET 29;8U
Adder
25.333
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.059
274730ELWOOD EC;6P
Adder
14.059
274734ELWOOD EC;8P
Adder
14.059
274736ELWOOD EC;9P
Adder
14.059
274803UNIV PARK;6U
Adder
4.85
943121AE2-341 GEN
Solar/Wind Harmer
12.478
943591AF1-030 GEN
Solar/Wind Harmer
8.319
274862TOP CROP ;2U
Solar/Wind Harmer
4.16
274682WAUKEGAN ;7U
Adder
14.691
276868AE1-113 GEN
Solar/Wind Harmer
8.026
274879MINONK ;1U
Solar/Wind Harmer
5.351
276799AD1-013 GEN
Solar/Wind Harmer
1.735
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.896
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
274724RIVER EC ;11
Adder
13.76
959091AF2-200 GEN
Solar/Wind Harmer
15.529
970571AG2-364 GEN
Solar/Wind Harmer
15.113
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.963
274767LEE CO EC;8U
Adder
6.881
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274811UNIV PK N;7U
Adder
3.74
276603SUBLETTE C
Solar/Wind Harmer
0.782
274851PROVIDENC;RU
Solar/Wind Harmer
2.05
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276782AC1-033 GEN
Solar/Wind Harmer
2.842
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
965091AG1-374 GEN
Solar/Wind Harmer
20.799
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.54
971087AG2-675 GEN
Solar/Wind Harmer
2.559
972231SS25-0005
Solar/Wind Harmer
6.115
972181SS23-001
Solar/Wind Harmer
3.822
274752CRETE EC ;2U
Adder
3.15
274753CRETE EC ;3U
Adder
3.15
276785W4-005 GEN1
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.153
957381AF2-032 GEN
Solar/Wind Harmer
0.946
942481AE2-261 GEN
Solar/Wind Harmer
13.986
274775LINCOLN ;6U
50/50
10.318
274776LINCOLN ;7U
50/50
10.318
274777LINCOLN ;8U
50/50
10.318
972227AH1-698 GEN1
50/50
2.574
274655BRAIDWOOD;2U
50/50
3.418
972228AH1-698 GEN2
50/50
3.651
274660LASCO STA;1U
50/50
6.448
274661LASCO STA;2U
50/50
4.981
274863CRW1-WTG
Solar/Wind Harmer
5.072
274864CRW2-WTG
Solar/Wind Harmer
5.072
960591AF2-350 GEN
Solar/Wind Harmer
9.078
276893AG1-478 C
Solar/Wind Harmer
0.476
970833AG2-524 GEN
Solar/Wind Harmer
7.55
970833AG2-524 GEN
Solar/Wind Harmer
3.512
274687WILL CNTY;4U
Adder
23.991
274687WILL CNTY;4U
Adder
23.991
274827FISK ;RP
Adder
6.649
274675JOLIET 29;7U
Adder
26.271
274675JOLIET 29;7U
Adder
25.333
274800UNIV PARK;3U
Adder
4.988
274801UNIV PARK;4U
Adder
4.988
274728ELWOOD EC;5P
Adder
14.059
274731ELWOOD EC;2P
Adder
14.059
274733ELWOOD EC;3P
Adder
14.059
274735ELWOOD EC;4P
Adder
14.059
274744AC1-111 GEN8
Adder
4.653
274746AC1-111 G10
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970073AG2-061 GEN
Solar/Wind Harmer
1.873
970169AG2-114 GEN
Solar/Wind Harmer
8.041
971411AH1-196 GEN
Solar/Wind Harmer
11.81
274773LINCOLN ;4U
50/50
10.318
274774LINCOLN ;5U
50/50
10.318
972207SS24-0001
Solar/Wind Harmer
34.57
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.53
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
274847GR RIDGE ;BU
Solar/Wind Harmer
4.391
274676JOLIET 29;8U
Adder
26.271
274732ELWOOD EC;7P
Adder
14.059
274674JOLIET 9 ;6U
Adder
13.082
274745AC1-111 GEN9
Adder
4.653
274802UNIV PARK;5U
Adder
4.85
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
276691AA1-018 GEN1
Solar/Wind Harmer
0.623
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274682WAUKEGAN ;7U
Adder
14.691
274828WAUKEGAN ;BP
Adder
9.009
276805AD2-038 GEN
Solar/Wind Harmer
4.13
962781AG1-127 GEN
Solar/Wind Harmer
7.623
274872LEEDK;1U
Solar/Wind Harmer
6.553
276882AE2-255 GEN
Solar/Wind Harmer
2.675
971997AH1-543 GEN
Solar/Wind Harmer
12.406
957471AF2-041 GEN
Solar/Wind Harmer
23.293
959081AF2-199 GEN
Solar/Wind Harmer
7.764
971067AG2-660 GEN
Solar/Wind Harmer
1.806
274723RIVER EC ;12
Adder
13.908
274822ROCKFORD ;11
Adder
15.177
970819AG2-516 GEN
Solar/Wind Harmer
9.185
970569AG2-363 GEN
Solar/Wind Harmer
22.669
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.963
274766LEE CO EC;7U
Adder
6.881
274812UNIV PK N;8U
Adder
3.74
276655WTG1_EQ
Solar/Wind Harmer
6.371
276656WTG2_EQ
Solar/Wind Harmer
0.844
939741AE1-205 GEN
Solar/Wind Harmer
14.599
276708O09 GEN2
Solar/Wind Harmer
2.605
276646AC1-214 GEN2
Solar/Wind Harmer
0.964
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
274751CRETE EC ;1U
Adder
3.15
274754CRETE EC ;4U
Adder
3.15
276686W4-005 GEN3
Solar/Wind Harmer
1.686
276621W2-048 GEN
Solar/Wind Harmer
3.277
965911AG1-460 GEN
Solar/Wind Harmer
0.653
971675AH1-338 GEN
Solar/Wind Harmer
14.127
276861AD2-134 GEN
Solar/Wind Harmer
1.4
276863AD2-134 GEN
Solar/Wind Harmer
1.4
971171AH1-044 GEN
Solar/Wind Harmer
15.529
276889AE2-281 GEN
Solar/Wind Harmer
1.489
274823ROCKFORD ;21
Adder
15.067
274856ECOGROVE ;U1
Solar/Wind Harmer
2.572
276611AD2-172 GEN
Solar/Wind Harmer
1.951
276612AE2-035 GEN
Solar/Wind Harmer
1.951
926823AC1-168 GEN
Solar/Wind Harmer
3.26
971681AH1-341 GEN
Solar/Wind Harmer
11.307
972267AH1-718 GEN
Adder
3.058
276726Z2-087_GEN
Solar/Wind Harmer
5.772
959341AF2-225 GEN
Solar/Wind Harmer
10.949
276741O09 GEN1
Solar/Wind Harmer
2.605
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
946321AF1-296 GEN
Solar/Wind Harmer
7.254
274853TWINGROVE;U1
Solar/Wind Harmer
4.995
274854TWINGROVE;U2
Solar/Wind Harmer
4.89
276668AB2-070 GEN1
Solar/Wind Harmer
1.227
276848AB2-070 GEN3
Solar/Wind Harmer
1.227
276849AB2-070 GEN2
Solar/Wind Harmer
1.227
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
990512J1326
External Queue
3.782691478729248
990117J1214
External Queue
13.012457847595215
990727J1377 G
External Queue
4.397138595581055
990407J1304
External Queue
2.92684268951416
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.94
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.316
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.611
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.243
MECLTFEXP_MEC->PJM
CLTF
9.347
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.954
LAGNLTFEXP_LAGN->PJM
CLTF
3.163
TVALTFEXP_TVA->PJM
CLTF
0.818

Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.9 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1629.1
MW Contribution:
11.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
10.318
274774LINCOLN ;5U
50/50
10.318
972207SS24-0001
Solar/Wind Harmer
34.57
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.53
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
274847GR RIDGE ;BU
Solar/Wind Harmer
4.391
274676JOLIET 29;8U
Adder
26.271
274732ELWOOD EC;7P
Adder
14.059
274674JOLIET 9 ;6U
Adder
13.082
274745AC1-111 GEN9
Adder
4.653
274802UNIV PARK;5U
Adder
4.85
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
276691AA1-018 GEN1
Solar/Wind Harmer
0.623
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274682WAUKEGAN ;7U
Adder
14.691
274828WAUKEGAN ;BP
Adder
9.009
276805AD2-038 GEN
Solar/Wind Harmer
4.13
962781AG1-127 GEN
Solar/Wind Harmer
7.623
274872LEEDK;1U
Solar/Wind Harmer
6.553
276882AE2-255 GEN
Solar/Wind Harmer
2.675
971997AH1-543 GEN
Solar/Wind Harmer
12.406
957471AF2-041 GEN
Solar/Wind Harmer
23.293
959081AF2-199 GEN
Solar/Wind Harmer
7.764
971067AG2-660 GEN
Solar/Wind Harmer
1.806
274723RIVER EC ;12
Adder
13.908
274822ROCKFORD ;11
Adder
15.177
970819AG2-516 GEN
Solar/Wind Harmer
9.185
970569AG2-363 GEN
Solar/Wind Harmer
22.669
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.963
274766LEE CO EC;7U
Adder
6.881
274772LINCOLN ;3U
50/50
10.318
274654BRAIDWOOD;1U
50/50
3.53
972259AH1-714 GEN
50/50
18.156
939351AE1-166 GEN
Solar/Wind Harmer
6.277
274887GEN-1.85
Solar/Wind Harmer
4.837
276772AC2-154 GEN
Solar/Wind Harmer
2.533
276843GEN-1.7
Solar/Wind Harmer
0.52
276806AD2-047 C O1
Solar/Wind Harmer
9.712
970707AG2-453 GEN
Solar/Wind Harmer
24.395
276164X3-005 C
Solar/Wind Harmer
0.607
274826FISK ;BP
Adder
9.382
274676JOLIET 29;8U
Adder
25.333
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.059
274730ELWOOD EC;6P
Adder
14.059
274734ELWOOD EC;8P
Adder
14.059
274736ELWOOD EC;9P
Adder
14.059
274803UNIV PARK;6U
Adder
4.85
943121AE2-341 GEN
Solar/Wind Harmer
12.478
943591AF1-030 GEN
Solar/Wind Harmer
8.319
274862TOP CROP ;2U
Solar/Wind Harmer
4.16
274682WAUKEGAN ;7U
Adder
14.691
276868AE1-113 GEN
Solar/Wind Harmer
8.026
274879MINONK ;1U
Solar/Wind Harmer
5.351
276799AD1-013 GEN
Solar/Wind Harmer
1.735
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.896
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
274724RIVER EC ;11
Adder
13.76
959091AF2-200 GEN
Solar/Wind Harmer
15.529
970571AG2-364 GEN
Solar/Wind Harmer
15.113
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.963
274767LEE CO EC;8U
Adder
6.881
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274811UNIV PK N;7U
Adder
3.74
276603SUBLETTE C
Solar/Wind Harmer
0.782
274851PROVIDENC;RU
Solar/Wind Harmer
2.05
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276782AC1-033 GEN
Solar/Wind Harmer
2.842
274770LINCOLN ;1U
50/50
10.318
274771LINCOLN ;2U
50/50
10.318
276897AD1-100 C
Solar/Wind Harmer
49.166
274888KELLY CRK;1U
Solar/Wind Harmer
5.357
276776AD2-060 GEN
Solar/Wind Harmer
0.38
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
276893AG1-478 C
Solar/Wind Harmer
0.379
274674JOLIET 9 ;6U
Adder
13.082
958481AF2-142 GEN
Solar/Wind Harmer
12.398
274696ROCKY RD ;4P
Adder
9.313
274695ROCKY RD ;2P
Adder
9.099
274693ROCKY RD ;1P
Adder
9.009
274697ROCKY RD ;3P
Adder
2.472
274683WAUKEGAN ;8U
Adder
17.186
274683WAUKEGAN ;8U
Adder
14.487
958491AF2-143 GEN
Solar/Wind Harmer
12.08
962691AG1-118 GEN
Solar/Wind Harmer
24.15
960751AF2-366 GEN
Solar/Wind Harmer
2.3
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
965091AG1-374 GEN
Solar/Wind Harmer
20.799
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.54
971087AG2-675 GEN
Solar/Wind Harmer
2.559
972231SS25-0005
Solar/Wind Harmer
6.115
972181SS23-001
Solar/Wind Harmer
3.822
274752CRETE EC ;2U
Adder
3.15
274753CRETE EC ;3U
Adder
3.15
276785W4-005 GEN1
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.153
957381AF2-032 GEN
Solar/Wind Harmer
0.946
942481AE2-261 GEN
Solar/Wind Harmer
13.986
274775LINCOLN ;6U
50/50
10.318
274776LINCOLN ;7U
50/50
10.318
274777LINCOLN ;8U
50/50
10.318
972227AH1-698 GEN1
50/50
2.574
274655BRAIDWOOD;2U
50/50
3.418
972228AH1-698 GEN2
50/50
3.651
274660LASCO STA;1U
50/50
6.448
274661LASCO STA;2U
50/50
4.981
274863CRW1-WTG
Solar/Wind Harmer
5.072
274864CRW2-WTG
Solar/Wind Harmer
5.072
276901AD2-066 C O1
Solar/Wind Harmer
2.799
971341AH1-150 GEN
Solar/Wind Harmer
15.529
971343AH1-151 GEN
Solar/Wind Harmer
15.529
276872AE1-163_GEN1
Solar/Wind Harmer
5.21
276876AE1-163_GEN2
Solar/Wind Harmer
5.21
972235AH1-702 GEN1
Adder
1.94
972236AH1-702 GEN2
Adder
1.687
938861AE1-114 GEN
Solar/Wind Harmer
6.178
274764LEE CO EC;5U
Adder
6.979
274765LEE CO EC;6U
Adder
6.979
274762LEE CO EC;3U
Adder
6.963
274763LEE CO EC;4U
Adder
6.897
274805UNIV PK N;1U
Adder
3.748
274808UNIV PK N;4U
Adder
3.723
942111AE2-223 GEN
Solar/Wind Harmer
5.984
276158O29GEN2
Solar/Wind Harmer
3.648
276157O29GEN1
Solar/Wind Harmer
2.774
276645AC1-214 GEN1
Solar/Wind Harmer
0.964
960611AF2-352 GEN
Solar/Wind Harmer
1.612
274880W4-005 GEN4
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276615X2-022 GEN
Solar/Wind Harmer
1.029
276838X2-022 GEN2
Solar/Wind Harmer
0.122
276916AD2-100_GEN
Solar/Wind Harmer
9.512
276911AD2-131_GEN
Solar/Wind Harmer
1.922
274812UNIV PK N;8U
Adder
3.74
276655WTG1_EQ
Solar/Wind Harmer
6.371
276656WTG2_EQ
Solar/Wind Harmer
0.844
939741AE1-205 GEN
Solar/Wind Harmer
14.599
276708O09 GEN2
Solar/Wind Harmer
2.605
276646AC1-214 GEN2
Solar/Wind Harmer
0.964
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
274751CRETE EC ;1U
Adder
3.15
274754CRETE EC ;4U
Adder
3.15
276686W4-005 GEN3
Solar/Wind Harmer
1.686
276621W2-048 GEN
Solar/Wind Harmer
3.277
965911AG1-460 GEN
Solar/Wind Harmer
0.653
960591AF2-350 GEN
Solar/Wind Harmer
9.078
276893AG1-478 C
Solar/Wind Harmer
0.476
970833AG2-524 GEN
Solar/Wind Harmer
7.55
970833AG2-524 GEN
Solar/Wind Harmer
3.512
274687WILL CNTY;4U
Adder
23.991
274687WILL CNTY;4U
Adder
23.991
274827FISK ;RP
Adder
6.649
274675JOLIET 29;7U
Adder
26.271
274675JOLIET 29;7U
Adder
25.333
274800UNIV PARK;3U
Adder
4.988
274801UNIV PARK;4U
Adder
4.988
274728ELWOOD EC;5P
Adder
14.059
274731ELWOOD EC;2P
Adder
14.059
274733ELWOOD EC;3P
Adder
14.059
274735ELWOOD EC;4P
Adder
14.059
274744AC1-111 GEN8
Adder
4.653
274746AC1-111 G10
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970073AG2-061 GEN
Solar/Wind Harmer
1.873
970169AG2-114 GEN
Solar/Wind Harmer
8.041
971411AH1-196 GEN
Solar/Wind Harmer
11.81
971675AH1-338 GEN
Solar/Wind Harmer
14.127
276861AD2-134 GEN
Solar/Wind Harmer
1.4
276863AD2-134 GEN
Solar/Wind Harmer
1.4
971171AH1-044 GEN
Solar/Wind Harmer
15.529
276889AE2-281 GEN
Solar/Wind Harmer
1.489
274823ROCKFORD ;21
Adder
15.067
274856ECOGROVE ;U1
Solar/Wind Harmer
2.572
276611AD2-172 GEN
Solar/Wind Harmer
1.951
276612AE2-035 GEN
Solar/Wind Harmer
1.951
926823AC1-168 GEN
Solar/Wind Harmer
3.26
971681AH1-341 GEN
Solar/Wind Harmer
11.307
972267AH1-718 GEN
Adder
3.058
276726Z2-087_GEN
Solar/Wind Harmer
5.772
959341AF2-225 GEN
Solar/Wind Harmer
10.949
276741O09 GEN1
Solar/Wind Harmer
2.605
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
946321AF1-296 GEN
Solar/Wind Harmer
7.254
274853TWINGROVE;U1
Solar/Wind Harmer
4.995
274854TWINGROVE;U2
Solar/Wind Harmer
4.89
276668AB2-070 GEN1
Solar/Wind Harmer
1.227
276848AB2-070 GEN3
Solar/Wind Harmer
1.227
276849AB2-070 GEN2
Solar/Wind Harmer
1.227
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
990512J1326
External Queue
3.782691478729248
990117J1214
External Queue
13.012457847595215
990727J1377 G
External Queue
4.397138595581055
990407J1304
External Queue
2.92684268951416
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.94
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.316
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.611
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.243
MECLTFEXP_MEC->PJM
CLTF
9.347
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.954
LAGNLTFEXP_LAGN->PJM
CLTF
3.163
TVALTFEXP_TVA->PJM
CLTF
0.818

Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.9 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1629.08
MW Contribution:
11.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274772LINCOLN ;3U
50/50
10.318
274654BRAIDWOOD;1U
50/50
3.53
972259AH1-714 GEN
50/50
18.156
939351AE1-166 GEN
Solar/Wind Harmer
6.277
274887GEN-1.85
Solar/Wind Harmer
4.837
276772AC2-154 GEN
Solar/Wind Harmer
2.533
276843GEN-1.7
Solar/Wind Harmer
0.52
276806AD2-047 C O1
Solar/Wind Harmer
9.712
970707AG2-453 GEN
Solar/Wind Harmer
24.395
276164X3-005 C
Solar/Wind Harmer
0.607
274826FISK ;BP
Adder
9.382
274676JOLIET 29;8U
Adder
25.333
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.059
274730ELWOOD EC;6P
Adder
14.059
274734ELWOOD EC;8P
Adder
14.059
274736ELWOOD EC;9P
Adder
14.059
274803UNIV PARK;6U
Adder
4.85
943121AE2-341 GEN
Solar/Wind Harmer
12.478
943591AF1-030 GEN
Solar/Wind Harmer
8.319
274862TOP CROP ;2U
Solar/Wind Harmer
4.16
274682WAUKEGAN ;7U
Adder
14.691
276868AE1-113 GEN
Solar/Wind Harmer
8.026
274879MINONK ;1U
Solar/Wind Harmer
5.351
276799AD1-013 GEN
Solar/Wind Harmer
1.735
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.896
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
274724RIVER EC ;11
Adder
13.76
959091AF2-200 GEN
Solar/Wind Harmer
15.529
970571AG2-364 GEN
Solar/Wind Harmer
15.113
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.963
274767LEE CO EC;8U
Adder
6.881
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274811UNIV PK N;7U
Adder
3.74
276603SUBLETTE C
Solar/Wind Harmer
0.782
274851PROVIDENC;RU
Solar/Wind Harmer
2.05
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276782AC1-033 GEN
Solar/Wind Harmer
2.842
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
965091AG1-374 GEN
Solar/Wind Harmer
20.799
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.54
971087AG2-675 GEN
Solar/Wind Harmer
2.559
972231SS25-0005
Solar/Wind Harmer
6.115
972181SS23-001
Solar/Wind Harmer
3.822
274752CRETE EC ;2U
Adder
3.15
274753CRETE EC ;3U
Adder
3.15
276785W4-005 GEN1
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.153
957381AF2-032 GEN
Solar/Wind Harmer
0.946
942481AE2-261 GEN
Solar/Wind Harmer
13.986
274770LINCOLN ;1U
50/50
10.318
274771LINCOLN ;2U
50/50
10.318
276897AD1-100 C
Solar/Wind Harmer
49.166
274888KELLY CRK;1U
Solar/Wind Harmer
5.357
276776AD2-060 GEN
Solar/Wind Harmer
0.38
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
276893AG1-478 C
Solar/Wind Harmer
0.379
274674JOLIET 9 ;6U
Adder
13.082
958481AF2-142 GEN
Solar/Wind Harmer
12.398
274696ROCKY RD ;4P
Adder
9.313
274695ROCKY RD ;2P
Adder
9.099
274693ROCKY RD ;1P
Adder
9.009
274697ROCKY RD ;3P
Adder
2.472
274683WAUKEGAN ;8U
Adder
17.186
274683WAUKEGAN ;8U
Adder
14.487
958491AF2-143 GEN
Solar/Wind Harmer
12.08
962691AG1-118 GEN
Solar/Wind Harmer
24.15
960751AF2-366 GEN
Solar/Wind Harmer
2.3
276901AD2-066 C O1
Solar/Wind Harmer
2.799
971341AH1-150 GEN
Solar/Wind Harmer
15.529
971343AH1-151 GEN
Solar/Wind Harmer
15.529
276872AE1-163_GEN1
Solar/Wind Harmer
5.21
276876AE1-163_GEN2
Solar/Wind Harmer
5.21
972235AH1-702 GEN1
Adder
1.94
972236AH1-702 GEN2
Adder
1.687
938861AE1-114 GEN
Solar/Wind Harmer
6.178
274764LEE CO EC;5U
Adder
6.979
274765LEE CO EC;6U
Adder
6.979
274762LEE CO EC;3U
Adder
6.963
274763LEE CO EC;4U
Adder
6.897
274805UNIV PK N;1U
Adder
3.748
274808UNIV PK N;4U
Adder
3.723
942111AE2-223 GEN
Solar/Wind Harmer
5.984
276158O29GEN2
Solar/Wind Harmer
3.648
276157O29GEN1
Solar/Wind Harmer
2.774
276645AC1-214 GEN1
Solar/Wind Harmer
0.964
960611AF2-352 GEN
Solar/Wind Harmer
1.612
274880W4-005 GEN4
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276615X2-022 GEN
Solar/Wind Harmer
1.029
276838X2-022 GEN2
Solar/Wind Harmer
0.122
276916AD2-100_GEN
Solar/Wind Harmer
9.512
276911AD2-131_GEN
Solar/Wind Harmer
1.922
274773LINCOLN ;4U
50/50
10.318
274774LINCOLN ;5U
50/50
10.318
972207SS24-0001
Solar/Wind Harmer
34.57
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.53
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
274847GR RIDGE ;BU
Solar/Wind Harmer
4.391
274676JOLIET 29;8U
Adder
26.271
274732ELWOOD EC;7P
Adder
14.059
274674JOLIET 9 ;6U
Adder
13.082
274745AC1-111 GEN9
Adder
4.653
274802UNIV PARK;5U
Adder
4.85
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
276691AA1-018 GEN1
Solar/Wind Harmer
0.623
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274682WAUKEGAN ;7U
Adder
14.691
274828WAUKEGAN ;BP
Adder
9.009
276805AD2-038 GEN
Solar/Wind Harmer
4.13
962781AG1-127 GEN
Solar/Wind Harmer
7.623
274872LEEDK;1U
Solar/Wind Harmer
6.553
276882AE2-255 GEN
Solar/Wind Harmer
2.675
971997AH1-543 GEN
Solar/Wind Harmer
12.406
957471AF2-041 GEN
Solar/Wind Harmer
23.293
959081AF2-199 GEN
Solar/Wind Harmer
7.764
971067AG2-660 GEN
Solar/Wind Harmer
1.806
274723RIVER EC ;12
Adder
13.908
274822ROCKFORD ;11
Adder
15.177
970819AG2-516 GEN
Solar/Wind Harmer
9.185
970569AG2-363 GEN
Solar/Wind Harmer
22.669
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.963
274766LEE CO EC;7U
Adder
6.881
274812UNIV PK N;8U
Adder
3.74
276655WTG1_EQ
Solar/Wind Harmer
6.371
276656WTG2_EQ
Solar/Wind Harmer
0.844
939741AE1-205 GEN
Solar/Wind Harmer
14.599
276708O09 GEN2
Solar/Wind Harmer
2.605
276646AC1-214 GEN2
Solar/Wind Harmer
0.964
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
274751CRETE EC ;1U
Adder
3.15
274754CRETE EC ;4U
Adder
3.15
276686W4-005 GEN3
Solar/Wind Harmer
1.686
276621W2-048 GEN
Solar/Wind Harmer
3.277
965911AG1-460 GEN
Solar/Wind Harmer
0.653
274775LINCOLN ;6U
50/50
10.318
274776LINCOLN ;7U
50/50
10.318
274777LINCOLN ;8U
50/50
10.318
972227AH1-698 GEN1
50/50
2.574
274655BRAIDWOOD;2U
50/50
3.418
972228AH1-698 GEN2
50/50
3.651
274660LASCO STA;1U
50/50
6.448
274661LASCO STA;2U
50/50
4.981
274863CRW1-WTG
Solar/Wind Harmer
5.072
274864CRW2-WTG
Solar/Wind Harmer
5.072
960591AF2-350 GEN
Solar/Wind Harmer
9.078
276893AG1-478 C
Solar/Wind Harmer
0.476
970833AG2-524 GEN
Solar/Wind Harmer
7.55
970833AG2-524 GEN
Solar/Wind Harmer
3.512
274687WILL CNTY;4U
Adder
23.991
274687WILL CNTY;4U
Adder
23.991
274827FISK ;RP
Adder
6.649
274675JOLIET 29;7U
Adder
26.271
274675JOLIET 29;7U
Adder
25.333
274800UNIV PARK;3U
Adder
4.988
274801UNIV PARK;4U
Adder
4.988
274728ELWOOD EC;5P
Adder
14.059
274731ELWOOD EC;2P
Adder
14.059
274733ELWOOD EC;3P
Adder
14.059
274735ELWOOD EC;4P
Adder
14.059
274744AC1-111 GEN8
Adder
4.653
274746AC1-111 G10
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970073AG2-061 GEN
Solar/Wind Harmer
1.873
970169AG2-114 GEN
Solar/Wind Harmer
8.041
971411AH1-196 GEN
Solar/Wind Harmer
11.81
971675AH1-338 GEN
Solar/Wind Harmer
14.127
276861AD2-134 GEN
Solar/Wind Harmer
1.4
276863AD2-134 GEN
Solar/Wind Harmer
1.4
971171AH1-044 GEN
Solar/Wind Harmer
15.529
276889AE2-281 GEN
Solar/Wind Harmer
1.489
274823ROCKFORD ;21
Adder
15.067
274856ECOGROVE ;U1
Solar/Wind Harmer
2.572
276611AD2-172 GEN
Solar/Wind Harmer
1.951
276612AE2-035 GEN
Solar/Wind Harmer
1.951
926823AC1-168 GEN
Solar/Wind Harmer
3.26
971681AH1-341 GEN
Solar/Wind Harmer
11.307
972267AH1-718 GEN
Adder
3.058
276726Z2-087_GEN
Solar/Wind Harmer
5.772
959341AF2-225 GEN
Solar/Wind Harmer
10.949
276741O09 GEN1
Solar/Wind Harmer
2.605
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
946321AF1-296 GEN
Solar/Wind Harmer
7.254
274853TWINGROVE;U1
Solar/Wind Harmer
4.995
274854TWINGROVE;U2
Solar/Wind Harmer
4.89
276668AB2-070 GEN1
Solar/Wind Harmer
1.227
276848AB2-070 GEN3
Solar/Wind Harmer
1.227
276849AB2-070 GEN2
Solar/Wind Harmer
1.227
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
990512J1326
External Queue
3.782691478729248
990117J1214
External Queue
13.012457847595215
990727J1377 G
External Queue
4.397138595581055
990407J1304
External Queue
2.92684268951416
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.94
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.408
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.243
MECLTFEXP_MEC->PJM
CLTF
9.347
SIGELTFEXP_SIGE->PJM
CLTF
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.316
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.611
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.954
LAGNLTFEXP_LAGN->PJM
CLTF
3.163
TVALTFEXP_TVA->PJM
CLTF
0.818

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.72 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:4715.14
MW Contribution:
33.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
20.172
274776LINCOLN ;7U
50/50
20.172
274777LINCOLN ;8U
50/50
20.172
274708KENDALL ;3C
50/50
3.087
274661LASCO STA;2U
50/50
14.479
274660LASCO STA;1U
50/50
18.742
274704KENDALL ;1C
50/50
2.74
274706KENDALL ;2C
50/50
2.74
274744AC1-111 GEN8
Adder
14.216
274746AC1-111 G10
Adder
14.216
970833AG2-524 GEN
Solar/Wind Harmer
21.914
970833AG2-524 GEN
Solar/Wind Harmer
10.193
972227AH1-698 GEN1
Adder
6.285
972228AH1-698 GEN2
Adder
8.922
971675AH1-338 GEN
Solar/Wind Harmer
42.809
276861AD2-134 GEN
Solar/Wind Harmer
4.243
276863AD2-134 GEN
Solar/Wind Harmer
4.243
274675JOLIET 29;7U
Adder
72.862
274675JOLIET 29;7U
Adder
70.26
274731ELWOOD EC;2P
Adder
38.876
274733ELWOOD EC;3P
Adder
38.876
274735ELWOOD EC;4P
Adder
38.876
274728ELWOOD EC;5P
Adder
38.861
971411AH1-196 GEN
Solar/Wind Harmer
35.234
971171AH1-044 GEN
Solar/Wind Harmer
46.659
274687WILL CNTY;4U
Adder
65.155
274687WILL CNTY;4U
Adder
65.155
276893AG1-478 C
Solar/Wind Harmer
1.282
274823ROCKFORD ;21
Adder
44.94
960591AF2-350 GEN
Solar/Wind Harmer
23.019
274856ECOGROVE ;U1
Solar/Wind Harmer
7.66
276611AD2-172 GEN
Solar/Wind Harmer
5.811
276612AE2-035 GEN
Solar/Wind Harmer
5.811
971681AH1-341 GEN
Solar/Wind Harmer
33.664
274800UNIV PARK;3U
Adder
13.022
274801UNIV PARK;4U
Adder
13.022
274863CRW1-WTG
Solar/Wind Harmer
12.463
274864CRW2-WTG
Solar/Wind Harmer
12.463
274827FISK ;RP
Adder
17.136
972267AH1-718 GEN
Adder
9.072
970073AG2-061 GEN
Solar/Wind Harmer
5.059
972037AH1-567 GEN1
Adder
0.397
926823AC1-168 GEN
Solar/Wind Harmer
9.299
276741O09 GEN1
Solar/Wind Harmer
7.655
970169AG2-114 GEN
Solar/Wind Harmer
21.374
276889AE2-281 GEN
Solar/Wind Harmer
4.086
946321AF1-296 GEN
Solar/Wind Harmer
21.319
274877BISHOP HL;1U
Solar/Wind Harmer
6.878
276726Z2-087_GEN
Solar/Wind Harmer
14.976
959341AF2-225 GEN
Solar/Wind Harmer
28.41
274853TWINGROVE;U1
Solar/Wind Harmer
12.987
274854TWINGROVE;U2
Solar/Wind Harmer
12.714
276668AB2-070 GEN1
Solar/Wind Harmer
3.247
276848AB2-070 GEN3
Solar/Wind Harmer
3.247
276849AB2-070 GEN2
Solar/Wind Harmer
3.247
276763AC1-053 GEN1
Solar/Wind Harmer
5.71
276764AC1-053 GEN2
Solar/Wind Harmer
5.71
944221AF1-090 GEN
Solar/Wind Harmer
2.83
274770LINCOLN ;1U
50/50
20.172
274771LINCOLN ;2U
50/50
20.172
274711KENDALL ;4S
50/50
2.042
274709KENDALL ;3S
50/50
2.042
276897AD1-100 C
Solar/Wind Harmer
116.375
274695ROCKY RD ;2P
Adder
27.368
274693ROCKY RD ;1P
Adder
27.098
274697ROCKY RD ;3P
Adder
7.435
274696ROCKY RD ;4P
Adder
28.01
962691AG1-118 GEN
Solar/Wind Harmer
73.698
960751AF2-366 GEN
Solar/Wind Harmer
7.012
274683WAUKEGAN ;8U
Adder
50.45
274683WAUKEGAN ;8U
Adder
42.527
274674JOLIET 9 ;6U
Adder
36.731
971341AH1-150 GEN
Solar/Wind Harmer
46.659
971343AH1-151 GEN
Solar/Wind Harmer
46.659
276893AG1-478 C
Solar/Wind Harmer
1.022
274888KELLY CRK;1U
Solar/Wind Harmer
13.583
276776AD2-060 GEN
Solar/Wind Harmer
0.964
958011AF2-095 GEN
Solar/Wind Harmer
33.147
970941AG2-585 GEN
Solar/Wind Harmer
12.66
972235AH1-702 GEN1
Adder
5.789
972236AH1-702 GEN2
Adder
5.034
276901AD2-066 C O1
Solar/Wind Harmer
7.863
938861AE1-114 GEN
Solar/Wind Harmer
18.379
274764LEE CO EC;5U
Adder
20.754
274765LEE CO EC;6U
Adder
20.754
274762LEE CO EC;3U
Adder
20.705
274763LEE CO EC;4U
Adder
20.51
958481AF2-142 GEN
Solar/Wind Harmer
33.126
958491AF2-143 GEN
Solar/Wind Harmer
32.631
276158O29GEN2
Solar/Wind Harmer
10.721
276157O29GEN1
Solar/Wind Harmer
8.151
276872AE1-163_GEN1
Solar/Wind Harmer
14.301
276876AE1-163_GEN2
Solar/Wind Harmer
14.301
276645AC1-214 GEN1
Solar/Wind Harmer
2.748
274805UNIV PK N;1U
Adder
9.834
274808UNIV PK N;4U
Adder
9.769
942111AE2-223 GEN
Solar/Wind Harmer
15.526
960611AF2-352 GEN
Solar/Wind Harmer
4.192
274880W4-005 GEN4
Solar/Wind Harmer
4.449
276174W4-005 GEN2
Solar/Wind Harmer
4.449
276615X2-022 GEN
Solar/Wind Harmer
2.738
276838X2-022 GEN2
Solar/Wind Harmer
0.325
276916AD2-100_GEN
Solar/Wind Harmer
25.522
276911AD2-131_GEN
Solar/Wind Harmer
5.158
274772LINCOLN ;3U
50/50
20.172
972259AH1-714 GEN
50/50
52.777
274707KENDALL ;2S
50/50
1.834
970707AG2-453 GEN
Solar/Wind Harmer
79.137
943121AE2-341 GEN
Solar/Wind Harmer
39.226
943591AF1-030 GEN
Solar/Wind Harmer
26.151
939351AE1-166 GEN
Solar/Wind Harmer
14.857
274682WAUKEGAN ;7U
Adder
43.119
276799AD1-013 GEN
Solar/Wind Harmer
5.26
946671AF1-331 GEN
Solar/Wind Harmer
0.997
274855GSG-6 ;RU
Solar/Wind Harmer
8.774
274850MENDOTA H;RU
Solar/Wind Harmer
6.1
276602WESTBROOK C
Solar/Wind Harmer
5.051
274676JOLIET 29;8U
Adder
70.252
274729ELWOOD EC;1P
Adder
38.876
274730ELWOOD EC;6P
Adder
38.861
274734ELWOOD EC;8P
Adder
38.861
274736ELWOOD EC;9P
Adder
38.861
959091AF2-200 GEN
Solar/Wind Harmer
46.659
274887GEN-1.85
Solar/Wind Harmer
12.264
276772AC2-154 GEN
Solar/Wind Harmer
6.424
276843GEN-1.7
Solar/Wind Harmer
1.32
276806AD2-047 C O1
Solar/Wind Harmer
24.624
972038AH1-567 GEN2
Adder
0.815
274857EASY ROAD;U1
Solar/Wind Harmer
10.662
274760LEE CO EC;1U
Adder
20.705
274767LEE CO EC;8U
Adder
20.461
276603SUBLETTE C
Solar/Wind Harmer
2.326
276868AE1-113 GEN
Solar/Wind Harmer
22.42
274879MINONK ;1U
Solar/Wind Harmer
14.948
274826FISK ;BP
Adder
24.18
274862TOP CROP ;2U
Solar/Wind Harmer
11.115
274803UNIV PARK;6U
Adder
12.652
276164X3-005 C
Solar/Wind Harmer
1.479
970571AG2-364 GEN
Solar/Wind Harmer
41.965
274851PROVIDENC;RU
Solar/Wind Harmer
5.843
274849CRESCENT ;1U
Solar/Wind Harmer
3.793
276782AC1-033 GEN
Solar/Wind Harmer
8.13
274878BISHOP HL;2U
Solar/Wind Harmer
6.878
965931AG1-462 GEN
Solar/Wind Harmer
51.496
971087AG2-675 GEN
Solar/Wind Harmer
7.514
274814UNIV PK N;0U
Adder
9.898
274807UNIV PK N;3U
Adder
9.877
274811UNIV PK N;7U
Adder
9.812
274724RIVER EC ;11
Adder
33.677
965091AG1-374 GEN
Solar/Wind Harmer
54.077
959611AF2-252 GEN
Solar/Wind Harmer
4.192
972231SS25-0005
Solar/Wind Harmer
16.134
972181SS23-001
Solar/Wind Harmer
10.084
274752CRETE EC ;2U
Adder
8.31
274753CRETE EC ;3U
Adder
8.31
276785W4-005 GEN1
Solar/Wind Harmer
4.449
971993AH1-541 GEN
Solar/Wind Harmer
13.596
957381AF2-032 GEN
Solar/Wind Harmer
2.537
942481AE2-261 GEN
Solar/Wind Harmer
37.502
274773LINCOLN ;4U
50/50
20.172
274774LINCOLN ;5U
50/50
20.172
274710KENDALL ;4C
50/50
3.051
274705KENDALL ;1S
50/50
1.834
972207SS24-0001
Solar/Wind Harmer
67.589
274745AC1-111 GEN9
Adder
14.216
274871GR RIDGE ;2U
Solar/Wind Harmer
19.36
274847GR RIDGE ;BU
Solar/Wind Harmer
12.73
941551AE2-152 GEN
Solar/Wind Harmer
11.362
962781AG1-127 GEN
Solar/Wind Harmer
23.242
274872LEEDK;1U
Solar/Wind Harmer
19.974
274682WAUKEGAN ;7U
Adder
43.119
274828WAUKEGAN ;BP
Adder
26.445
274674JOLIET 9 ;6U
Adder
36.731
274676JOLIET 29;8U
Adder
72.853
274732ELWOOD EC;7P
Adder
38.861
957471AF2-041 GEN
Solar/Wind Harmer
69.989
959081AF2-199 GEN
Solar/Wind Harmer
23.33
971067AG2-660 GEN
Solar/Wind Harmer
5.425
939401AE1-172 GEN
Solar/Wind Harmer
32.481
274822ROCKFORD ;11
Adder
45.268
971997AH1-543 GEN
Solar/Wind Harmer
36.278
970819AG2-516 GEN
Solar/Wind Harmer
27.356
274858EASY ROAD;U2
Solar/Wind Harmer
10.662
274761LEE CO EC;2U
Adder
20.705
274766LEE CO EC;7U
Adder
20.461
276882AE2-255 GEN
Solar/Wind Harmer
7.474
276694AA1-018 GEN2
Solar/Wind Harmer
13.935
276691AA1-018 GEN1
Solar/Wind Harmer
1.666
274861TOP CROP ;1U
Solar/Wind Harmer
13.312
276805AD2-038 GEN
Solar/Wind Harmer
11.156
274802UNIV PARK;5U
Adder
12.652
276708O09 GEN2
Solar/Wind Harmer
7.655
970569AG2-363 GEN
Solar/Wind Harmer
62.948
276646AC1-214 GEN2
Solar/Wind Harmer
2.748
274848CAMPGROVE;RU
Solar/Wind Harmer
12.973
274812UNIV PK N;8U
Adder
9.812
274723RIVER EC ;12
Adder
34.02
276655WTG1_EQ
Solar/Wind Harmer
16.531
276656WTG2_EQ
Solar/Wind Harmer
2.189
939741AE1-205 GEN
Solar/Wind Harmer
37.88
274751CRETE EC ;1U
Adder
8.31
274754CRETE EC ;4U
Adder
8.31
276686W4-005 GEN3
Solar/Wind Harmer
4.449
276621W2-048 GEN
Solar/Wind Harmer
8.718
965911AG1-460 GEN
Solar/Wind Harmer
1.75
991777J1629 G
External Queue
25.562633514404297
990512J1326
External Queue
11.37018871307373
990117J1214
External Queue
39.11344528198242
990727J1377 G
External Queue
13.277053833007812
991092J1477
External Queue
6.0236663818359375
991303J1755 G
External Queue
9.531838417053223
990407J1304
External Queue
8.819650650024414
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.465
NYPJM->LTFIMP_NY
CLTF
2.189
WECLTFEXP_WEC->PJM
CLTF
8.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
147.602
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
65.645
MECLTFEXP_MEC->PJM
CLTF
27.125
SIGELTFEXP_SIGE->PJM
CLTF
0.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.93
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.01
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.829
LAGNLTFEXP_LAGN->PJM
CLTF
8.925
TVALTFEXP_TVA->PJM
CLTF
2.261

Details for WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.89 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1658.32
MW Contribution:
11.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274772LINCOLN ;3U
50/50
10.145
274654BRAIDWOOD;1U
50/50
3.551
972259AH1-714 GEN
50/50
18.253
939351AE1-166 GEN
Solar/Wind Harmer
6.331
274887GEN-1.85
Solar/Wind Harmer
4.861
276772AC2-154 GEN
Solar/Wind Harmer
2.546
276843GEN-1.7
Solar/Wind Harmer
0.523
276806AD2-047 C O1
Solar/Wind Harmer
9.76
970707AG2-453 GEN
Solar/Wind Harmer
24.508
276164X3-005 C
Solar/Wind Harmer
0.608
274826FISK ;BP
Adder
9.402
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.398
274730ELWOOD EC;6P
Adder
14.098
274734ELWOOD EC;8P
Adder
14.098
274736ELWOOD EC;9P
Adder
14.098
274729ELWOOD EC;1P
Adder
14.098
943121AE2-341 GEN
Solar/Wind Harmer
12.523
943591AF1-030 GEN
Solar/Wind Harmer
8.349
274803UNIV PARK;6U
Adder
4.863
274862TOP CROP ;2U
Solar/Wind Harmer
4.176
274682WAUKEGAN ;7U
Adder
14.738
276868AE1-113 GEN
Solar/Wind Harmer
8.052
274879MINONK ;1U
Solar/Wind Harmer
5.368
276799AD1-013 GEN
Solar/Wind Harmer
1.741
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.906
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
274724RIVER EC ;11
Adder
13.811
274775LINCOLN ;6U
50/50
10.145
274776LINCOLN ;7U
50/50
10.145
274777LINCOLN ;8U
50/50
10.145
972227AH1-698 GEN1
50/50
2.59
274655BRAIDWOOD;2U
50/50
3.439
972228AH1-698 GEN2
50/50
3.673
274661LASCO STA;2U
50/50
5.008
274660LASCO STA;1U
50/50
6.482
274687WILL CNTY;4U
50/50
25.536
274687WILL CNTY;4U
50/50
25.536
274863CRW1-WTG
Solar/Wind Harmer
5.113
274864CRW2-WTG
Solar/Wind Harmer
5.113
960591AF2-350 GEN
Solar/Wind Harmer
9.124
970833AG2-524 GEN
Solar/Wind Harmer
7.586
970833AG2-524 GEN
Solar/Wind Harmer
3.528
276893AG1-478 C
Solar/Wind Harmer
0.478
274827FISK ;RP
Adder
6.663
274800UNIV PARK;3U
Adder
5.005
274801UNIV PARK;4U
Adder
5.005
274675JOLIET 29;7U
Adder
26.339
274675JOLIET 29;7U
Adder
25.399
274728ELWOOD EC;5P
Adder
14.098
274731ELWOOD EC;2P
Adder
14.098
274733ELWOOD EC;3P
Adder
14.098
274735ELWOOD EC;4P
Adder
14.098
274744AC1-111 GEN8
Adder
4.669
274746AC1-111 G10
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.093
970073AG2-061 GEN
Solar/Wind Harmer
1.877
971411AH1-196 GEN
Solar/Wind Harmer
11.85
971675AH1-338 GEN
Solar/Wind Harmer
14.177
276861AD2-134 GEN
Solar/Wind Harmer
1.405
276863AD2-134 GEN
Solar/Wind Harmer
1.405
971171AH1-044 GEN
Solar/Wind Harmer
15.583
276889AE2-281 GEN
Solar/Wind Harmer
1.493
274823ROCKFORD ;21
Adder
15.118
274856ECOGROVE ;U1
Solar/Wind Harmer
2.581
276611AD2-172 GEN
Solar/Wind Harmer
1.958
276612AE2-035 GEN
Solar/Wind Harmer
1.958
926823AC1-168 GEN
Solar/Wind Harmer
3.274
971681AH1-341 GEN
Solar/Wind Harmer
11.347
972267AH1-718 GEN
Adder
3.069
276726Z2-087_GEN
Solar/Wind Harmer
5.812
959341AF2-225 GEN
Solar/Wind Harmer
11.025
276741O09 GEN1
Solar/Wind Harmer
2.615
274877BISHOP HL;1U
Solar/Wind Harmer
2.414
274853TWINGROVE;U1
Solar/Wind Harmer
5.029
274854TWINGROVE;U2
Solar/Wind Harmer
4.924
946321AF1-296 GEN
Solar/Wind Harmer
7.28
276668AB2-070 GEN1
Solar/Wind Harmer
1.234
276848AB2-070 GEN3
Solar/Wind Harmer
1.234
276849AB2-070 GEN2
Solar/Wind Harmer
1.234
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
274770LINCOLN ;1U
50/50
10.145
274771LINCOLN ;2U
50/50
10.145
276897AD1-100 C
Solar/Wind Harmer
49.591
274888KELLY CRK;1U
Solar/Wind Harmer
5.384
276776AD2-060 GEN
Solar/Wind Harmer
0.382
958011AF2-095 GEN
Solar/Wind Harmer
13.138
970941AG2-585 GEN
Solar/Wind Harmer
5.018
276893AG1-478 C
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
13.127
958481AF2-142 GEN
Solar/Wind Harmer
12.416
274696ROCKY RD ;4P
Adder
9.344
274695ROCKY RD ;2P
Adder
9.129
274693ROCKY RD ;1P
Adder
9.039
274697ROCKY RD ;3P
Adder
2.48
274683WAUKEGAN ;8U
Adder
17.241
274683WAUKEGAN ;8U
Adder
14.534
962691AG1-118 GEN
Solar/Wind Harmer
24.235
958491AF2-143 GEN
Solar/Wind Harmer
12.104
960751AF2-366 GEN
Solar/Wind Harmer
2.308
276901AD2-066 C O1
Solar/Wind Harmer
2.81
971341AH1-150 GEN
Solar/Wind Harmer
15.583
971343AH1-151 GEN
Solar/Wind Harmer
15.583
276872AE1-163_GEN1
Solar/Wind Harmer
5.224
276876AE1-163_GEN2
Solar/Wind Harmer
5.224
972235AH1-702 GEN1
Adder
1.947
972236AH1-702 GEN2
Adder
1.693
938861AE1-114 GEN
Solar/Wind Harmer
6.199
274764LEE CO EC;5U
Adder
7.004
274765LEE CO EC;6U
Adder
7.004
274762LEE CO EC;3U
Adder
6.987
274763LEE CO EC;4U
Adder
6.922
274805UNIV PK N;1U
Adder
3.755
274808UNIV PK N;4U
Adder
3.73
942111AE2-223 GEN
Solar/Wind Harmer
6.025
276158O29GEN2
Solar/Wind Harmer
3.662
276157O29GEN1
Solar/Wind Harmer
2.784
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
960611AF2-352 GEN
Solar/Wind Harmer
1.623
274880W4-005 GEN4
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276615X2-022 GEN
Solar/Wind Harmer
1.035
276838X2-022 GEN2
Solar/Wind Harmer
0.123
276916AD2-100_GEN
Solar/Wind Harmer
9.568
276911AD2-131_GEN
Solar/Wind Harmer
1.934
959091AF2-200 GEN
Solar/Wind Harmer
15.583
970571AG2-364 GEN
Solar/Wind Harmer
15.163
274857EASY ROAD;U1
Solar/Wind Harmer
3.598
274760LEE CO EC;1U
Adder
6.987
274767LEE CO EC;8U
Adder
6.905
276603SUBLETTE C
Solar/Wind Harmer
0.785
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274811UNIV PK N;7U
Adder
3.747
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.336
276782AC1-033 GEN
Solar/Wind Harmer
2.854
274878BISHOP HL;2U
Solar/Wind Harmer
2.414
965091AG1-374 GEN
Solar/Wind Harmer
20.941
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.603
971087AG2-675 GEN
Solar/Wind Harmer
2.569
972231SS25-0005
Solar/Wind Harmer
6.139
972181SS23-001
Solar/Wind Harmer
3.837
274752CRETE EC ;2U
Adder
3.162
274753CRETE EC ;3U
Adder
3.162
276785W4-005 GEN1
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.186
957381AF2-032 GEN
Solar/Wind Harmer
0.952
942481AE2-261 GEN
Solar/Wind Harmer
14.068
274773LINCOLN ;4U
50/50
10.145
274774LINCOLN ;5U
50/50
10.145
972207SS24-0001
Solar/Wind Harmer
33.993
941551AE2-152 GEN
Solar/Wind Harmer
4.842
939401AE1-172 GEN
Solar/Wind Harmer
13.647
274871GR RIDGE ;2U
Solar/Wind Harmer
6.711
274847GR RIDGE ;BU
Solar/Wind Harmer
4.413
274676JOLIET 29;8U
Adder
26.339
274732ELWOOD EC;7P
Adder
14.098
274674JOLIET 9 ;6U
Adder
13.127
274745AC1-111 GEN9
Adder
4.669
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
276691AA1-018 GEN1
Solar/Wind Harmer
0.624
274861TOP CROP ;1U
Solar/Wind Harmer
5.001
274682WAUKEGAN ;7U
Adder
14.738
274828WAUKEGAN ;BP
Adder
9.038
276805AD2-038 GEN
Solar/Wind Harmer
4.138
962781AG1-127 GEN
Solar/Wind Harmer
7.649
274872LEEDK;1U
Solar/Wind Harmer
6.576
276882AE2-255 GEN
Solar/Wind Harmer
2.684
971997AH1-543 GEN
Solar/Wind Harmer
12.45
957471AF2-041 GEN
Solar/Wind Harmer
23.374
959081AF2-199 GEN
Solar/Wind Harmer
7.791
971067AG2-660 GEN
Solar/Wind Harmer
1.812
274723RIVER EC ;12
Adder
13.918
274822ROCKFORD ;11
Adder
15.229
970819AG2-516 GEN
Solar/Wind Harmer
9.217
970569AG2-363 GEN
Solar/Wind Harmer
22.744
274858EASY ROAD;U2
Solar/Wind Harmer
3.598
274761LEE CO EC;2U
Adder
6.987
274766LEE CO EC;7U
Adder
6.905
274812UNIV PK N;8U
Adder
3.747
276655WTG1_EQ
Solar/Wind Harmer
6.415
276656WTG2_EQ
Solar/Wind Harmer
0.849
939741AE1-205 GEN
Solar/Wind Harmer
14.7
276708O09 GEN2
Solar/Wind Harmer
2.615
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
274751CRETE EC ;1U
Adder
3.162
274754CRETE EC ;4U
Adder
3.162
276686W4-005 GEN3
Solar/Wind Harmer
1.697
276621W2-048 GEN
Solar/Wind Harmer
3.297
965911AG1-460 GEN
Solar/Wind Harmer
0.657
990512J1326
External Queue
3.794844388961792
990117J1214
External Queue
13.054264068603516
990727J1377 G
External Queue
4.411266803741455
990407J1304
External Queue
2.936152935028076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.95
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.255
MECLTFEXP_MEC->PJM
CLTF
9.382
SIGELTFEXP_SIGE->PJM
CLTF
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.729
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
TVALTFEXP_TVA->PJM
CLTF
0.823

Details for WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT2-3___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.43 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1636.94
MW Contribution:
11.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
10.145
274776LINCOLN ;7U
50/50
10.145
274777LINCOLN ;8U
50/50
10.145
972227AH1-698 GEN1
50/50
2.59
274655BRAIDWOOD;2U
50/50
3.439
972228AH1-698 GEN2
50/50
3.673
274661LASCO STA;2U
50/50
5.008
274660LASCO STA;1U
50/50
6.482
274687WILL CNTY;4U
50/50
25.536
274687WILL CNTY;4U
50/50
25.536
274863CRW1-WTG
Solar/Wind Harmer
5.113
274864CRW2-WTG
Solar/Wind Harmer
5.113
960591AF2-350 GEN
Solar/Wind Harmer
9.124
970833AG2-524 GEN
Solar/Wind Harmer
7.586
970833AG2-524 GEN
Solar/Wind Harmer
3.528
276893AG1-478 C
Solar/Wind Harmer
0.478
274827FISK ;RP
Adder
6.663
274800UNIV PARK;3U
Adder
5.005
274801UNIV PARK;4U
Adder
5.005
274675JOLIET 29;7U
Adder
26.339
274675JOLIET 29;7U
Adder
25.399
274728ELWOOD EC;5P
Adder
14.098
274731ELWOOD EC;2P
Adder
14.098
274733ELWOOD EC;3P
Adder
14.098
274735ELWOOD EC;4P
Adder
14.098
274744AC1-111 GEN8
Adder
4.669
274746AC1-111 G10
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.093
970073AG2-061 GEN
Solar/Wind Harmer
1.877
971411AH1-196 GEN
Solar/Wind Harmer
11.85
971675AH1-338 GEN
Solar/Wind Harmer
14.177
276861AD2-134 GEN
Solar/Wind Harmer
1.405
276863AD2-134 GEN
Solar/Wind Harmer
1.405
971171AH1-044 GEN
Solar/Wind Harmer
15.583
276889AE2-281 GEN
Solar/Wind Harmer
1.493
274823ROCKFORD ;21
Adder
15.118
274856ECOGROVE ;U1
Solar/Wind Harmer
2.581
276611AD2-172 GEN
Solar/Wind Harmer
1.958
276612AE2-035 GEN
Solar/Wind Harmer
1.958
926823AC1-168 GEN
Solar/Wind Harmer
3.274
971681AH1-341 GEN
Solar/Wind Harmer
11.347
972267AH1-718 GEN
Adder
3.069
276726Z2-087_GEN
Solar/Wind Harmer
5.812
959341AF2-225 GEN
Solar/Wind Harmer
11.025
274770LINCOLN ;1U
50/50
10.145
274771LINCOLN ;2U
50/50
10.145
276897AD1-100 C
Solar/Wind Harmer
49.591
274888KELLY CRK;1U
Solar/Wind Harmer
5.384
276776AD2-060 GEN
Solar/Wind Harmer
0.382
958011AF2-095 GEN
Solar/Wind Harmer
13.138
970941AG2-585 GEN
Solar/Wind Harmer
5.018
276893AG1-478 C
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
13.127
958481AF2-142 GEN
Solar/Wind Harmer
12.416
274696ROCKY RD ;4P
Adder
9.344
274695ROCKY RD ;2P
Adder
9.129
274693ROCKY RD ;1P
Adder
9.039
274697ROCKY RD ;3P
Adder
2.48
274683WAUKEGAN ;8U
Adder
17.241
274683WAUKEGAN ;8U
Adder
14.534
962691AG1-118 GEN
Solar/Wind Harmer
24.235
958491AF2-143 GEN
Solar/Wind Harmer
12.104
960751AF2-366 GEN
Solar/Wind Harmer
2.308
276901AD2-066 C O1
Solar/Wind Harmer
2.81
971341AH1-150 GEN
Solar/Wind Harmer
15.583
971343AH1-151 GEN
Solar/Wind Harmer
15.583
276872AE1-163_GEN1
Solar/Wind Harmer
5.224
276876AE1-163_GEN2
Solar/Wind Harmer
5.224
972235AH1-702 GEN1
Adder
1.947
972236AH1-702 GEN2
Adder
1.693
938861AE1-114 GEN
Solar/Wind Harmer
6.199
274764LEE CO EC;5U
Adder
7.004
274765LEE CO EC;6U
Adder
7.004
274762LEE CO EC;3U
Adder
6.987
274763LEE CO EC;4U
Adder
6.922
274805UNIV PK N;1U
Adder
3.755
274808UNIV PK N;4U
Adder
3.73
942111AE2-223 GEN
Solar/Wind Harmer
6.025
276158O29GEN2
Solar/Wind Harmer
3.662
276157O29GEN1
Solar/Wind Harmer
2.784
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
960611AF2-352 GEN
Solar/Wind Harmer
1.623
274880W4-005 GEN4
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276615X2-022 GEN
Solar/Wind Harmer
1.035
276838X2-022 GEN2
Solar/Wind Harmer
0.123
276916AD2-100_GEN
Solar/Wind Harmer
9.568
276911AD2-131_GEN
Solar/Wind Harmer
1.934
274772LINCOLN ;3U
50/50
10.145
274654BRAIDWOOD;1U
50/50
3.551
972259AH1-714 GEN
50/50
18.253
939351AE1-166 GEN
Solar/Wind Harmer
6.331
274887GEN-1.85
Solar/Wind Harmer
4.861
276772AC2-154 GEN
Solar/Wind Harmer
2.546
276843GEN-1.7
Solar/Wind Harmer
0.523
276806AD2-047 C O1
Solar/Wind Harmer
9.76
970707AG2-453 GEN
Solar/Wind Harmer
24.508
276164X3-005 C
Solar/Wind Harmer
0.608
274826FISK ;BP
Adder
9.402
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.398
274730ELWOOD EC;6P
Adder
14.098
274734ELWOOD EC;8P
Adder
14.098
274736ELWOOD EC;9P
Adder
14.098
274729ELWOOD EC;1P
Adder
14.098
943121AE2-341 GEN
Solar/Wind Harmer
12.523
943591AF1-030 GEN
Solar/Wind Harmer
8.349
274803UNIV PARK;6U
Adder
4.863
274862TOP CROP ;2U
Solar/Wind Harmer
4.176
274682WAUKEGAN ;7U
Adder
14.738
276868AE1-113 GEN
Solar/Wind Harmer
8.052
274879MINONK ;1U
Solar/Wind Harmer
5.368
276799AD1-013 GEN
Solar/Wind Harmer
1.741
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.906
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
274724RIVER EC ;11
Adder
13.811
959091AF2-200 GEN
Solar/Wind Harmer
15.583
970571AG2-364 GEN
Solar/Wind Harmer
15.163
274857EASY ROAD;U1
Solar/Wind Harmer
3.598
274760LEE CO EC;1U
Adder
6.987
274767LEE CO EC;8U
Adder
6.905
276603SUBLETTE C
Solar/Wind Harmer
0.785
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274811UNIV PK N;7U
Adder
3.747
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.336
276782AC1-033 GEN
Solar/Wind Harmer
2.854
274878BISHOP HL;2U
Solar/Wind Harmer
2.414
965091AG1-374 GEN
Solar/Wind Harmer
20.941
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.603
971087AG2-675 GEN
Solar/Wind Harmer
2.569
972231SS25-0005
Solar/Wind Harmer
6.139
972181SS23-001
Solar/Wind Harmer
3.837
274752CRETE EC ;2U
Adder
3.162
274753CRETE EC ;3U
Adder
3.162
276785W4-005 GEN1
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.186
957381AF2-032 GEN
Solar/Wind Harmer
0.952
942481AE2-261 GEN
Solar/Wind Harmer
14.068
274773LINCOLN ;4U
50/50
10.145
274774LINCOLN ;5U
50/50
10.145
972207SS24-0001
Solar/Wind Harmer
33.993
941551AE2-152 GEN
Solar/Wind Harmer
4.842
939401AE1-172 GEN
Solar/Wind Harmer
13.647
274871GR RIDGE ;2U
Solar/Wind Harmer
6.711
274847GR RIDGE ;BU
Solar/Wind Harmer
4.413
274676JOLIET 29;8U
Adder
26.339
274732ELWOOD EC;7P
Adder
14.098
274674JOLIET 9 ;6U
Adder
13.127
274745AC1-111 GEN9
Adder
4.669
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
276691AA1-018 GEN1
Solar/Wind Harmer
0.624
274861TOP CROP ;1U
Solar/Wind Harmer
5.001
274682WAUKEGAN ;7U
Adder
14.738
274828WAUKEGAN ;BP
Adder
9.038
276805AD2-038 GEN
Solar/Wind Harmer
4.138
962781AG1-127 GEN
Solar/Wind Harmer
7.649
274872LEEDK;1U
Solar/Wind Harmer
6.576
276882AE2-255 GEN
Solar/Wind Harmer
2.684
971997AH1-543 GEN
Solar/Wind Harmer
12.45
957471AF2-041 GEN
Solar/Wind Harmer
23.374
959081AF2-199 GEN
Solar/Wind Harmer
7.791
971067AG2-660 GEN
Solar/Wind Harmer
1.812
274723RIVER EC ;12
Adder
13.918
274822ROCKFORD ;11
Adder
15.229
970819AG2-516 GEN
Solar/Wind Harmer
9.217
970569AG2-363 GEN
Solar/Wind Harmer
22.744
274858EASY ROAD;U2
Solar/Wind Harmer
3.598
274761LEE CO EC;2U
Adder
6.987
274766LEE CO EC;7U
Adder
6.905
274812UNIV PK N;8U
Adder
3.747
276655WTG1_EQ
Solar/Wind Harmer
6.415
276656WTG2_EQ
Solar/Wind Harmer
0.849
939741AE1-205 GEN
Solar/Wind Harmer
14.7
276708O09 GEN2
Solar/Wind Harmer
2.615
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
274751CRETE EC ;1U
Adder
3.162
274754CRETE EC ;4U
Adder
3.162
276686W4-005 GEN3
Solar/Wind Harmer
1.697
276621W2-048 GEN
Solar/Wind Harmer
3.297
965911AG1-460 GEN
Solar/Wind Harmer
0.657
276741O09 GEN1
Solar/Wind Harmer
2.615
274877BISHOP HL;1U
Solar/Wind Harmer
2.414
274853TWINGROVE;U1
Solar/Wind Harmer
5.029
274854TWINGROVE;U2
Solar/Wind Harmer
4.924
946321AF1-296 GEN
Solar/Wind Harmer
7.28
276668AB2-070 GEN1
Solar/Wind Harmer
1.234
276848AB2-070 GEN3
Solar/Wind Harmer
1.234
276849AB2-070 GEN2
Solar/Wind Harmer
1.234
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
990512J1326
External Queue
3.794844388961792
990117J1214
External Queue
13.054264068603516
990727J1377 G
External Queue
4.411265850067139
990407J1304
External Queue
2.936152935028076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.95
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.255
MECLTFEXP_MEC->PJM
CLTF
9.382
SIGELTFEXP_SIGE->PJM
CLTF
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.729
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
TVALTFEXP_TVA->PJM
CLTF
0.823

Details for WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.43 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1636.9
MW Contribution:
11.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
10.145
274774LINCOLN ;5U
50/50
10.145
972207SS24-0001
Solar/Wind Harmer
33.993
941551AE2-152 GEN
Solar/Wind Harmer
4.842
939401AE1-172 GEN
Solar/Wind Harmer
13.647
274871GR RIDGE ;2U
Solar/Wind Harmer
6.711
274847GR RIDGE ;BU
Solar/Wind Harmer
4.413
274676JOLIET 29;8U
Adder
26.339
274732ELWOOD EC;7P
Adder
14.098
274674JOLIET 9 ;6U
Adder
13.127
274745AC1-111 GEN9
Adder
4.669
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
276691AA1-018 GEN1
Solar/Wind Harmer
0.624
274861TOP CROP ;1U
Solar/Wind Harmer
5.001
274682WAUKEGAN ;7U
Adder
14.738
274828WAUKEGAN ;BP
Adder
9.038
276805AD2-038 GEN
Solar/Wind Harmer
4.138
962781AG1-127 GEN
Solar/Wind Harmer
7.649
274775LINCOLN ;6U
50/50
10.145
274776LINCOLN ;7U
50/50
10.145
274777LINCOLN ;8U
50/50
10.145
972227AH1-698 GEN1
50/50
2.59
274655BRAIDWOOD;2U
50/50
3.439
972228AH1-698 GEN2
50/50
3.673
274661LASCO STA;2U
50/50
5.008
274660LASCO STA;1U
50/50
6.482
274687WILL CNTY;4U
50/50
25.536
274687WILL CNTY;4U
50/50
25.536
274863CRW1-WTG
Solar/Wind Harmer
5.113
274864CRW2-WTG
Solar/Wind Harmer
5.113
960591AF2-350 GEN
Solar/Wind Harmer
9.124
970833AG2-524 GEN
Solar/Wind Harmer
7.586
970833AG2-524 GEN
Solar/Wind Harmer
3.528
276893AG1-478 C
Solar/Wind Harmer
0.478
274827FISK ;RP
Adder
6.663
274800UNIV PARK;3U
Adder
5.005
274801UNIV PARK;4U
Adder
5.005
274675JOLIET 29;7U
Adder
26.339
274675JOLIET 29;7U
Adder
25.399
274728ELWOOD EC;5P
Adder
14.098
274731ELWOOD EC;2P
Adder
14.098
274733ELWOOD EC;3P
Adder
14.098
274735ELWOOD EC;4P
Adder
14.098
274744AC1-111 GEN8
Adder
4.669
274746AC1-111 G10
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.093
970073AG2-061 GEN
Solar/Wind Harmer
1.877
971411AH1-196 GEN
Solar/Wind Harmer
11.85
971675AH1-338 GEN
Solar/Wind Harmer
14.177
276861AD2-134 GEN
Solar/Wind Harmer
1.405
276863AD2-134 GEN
Solar/Wind Harmer
1.405
971171AH1-044 GEN
Solar/Wind Harmer
15.583
276889AE2-281 GEN
Solar/Wind Harmer
1.493
274823ROCKFORD ;21
Adder
15.118
274856ECOGROVE ;U1
Solar/Wind Harmer
2.581
276611AD2-172 GEN
Solar/Wind Harmer
1.958
276612AE2-035 GEN
Solar/Wind Harmer
1.958
926823AC1-168 GEN
Solar/Wind Harmer
3.274
971681AH1-341 GEN
Solar/Wind Harmer
11.347
972267AH1-718 GEN
Adder
3.069
276726Z2-087_GEN
Solar/Wind Harmer
5.812
959341AF2-225 GEN
Solar/Wind Harmer
11.025
276741O09 GEN1
Solar/Wind Harmer
2.615
274877BISHOP HL;1U
Solar/Wind Harmer
2.414
274853TWINGROVE;U1
Solar/Wind Harmer
5.029
274854TWINGROVE;U2
Solar/Wind Harmer
4.924
946321AF1-296 GEN
Solar/Wind Harmer
7.28
276668AB2-070 GEN1
Solar/Wind Harmer
1.234
276848AB2-070 GEN3
Solar/Wind Harmer
1.234
276849AB2-070 GEN2
Solar/Wind Harmer
1.234
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
274872LEEDK;1U
Solar/Wind Harmer
6.576
276882AE2-255 GEN
Solar/Wind Harmer
2.684
971997AH1-543 GEN
Solar/Wind Harmer
12.45
957471AF2-041 GEN
Solar/Wind Harmer
23.374
959081AF2-199 GEN
Solar/Wind Harmer
7.791
971067AG2-660 GEN
Solar/Wind Harmer
1.812
274723RIVER EC ;12
Adder
13.918
274822ROCKFORD ;11
Adder
15.229
970819AG2-516 GEN
Solar/Wind Harmer
9.217
970569AG2-363 GEN
Solar/Wind Harmer
22.744
274858EASY ROAD;U2
Solar/Wind Harmer
3.598
274761LEE CO EC;2U
Adder
6.987
274766LEE CO EC;7U
Adder
6.905
274812UNIV PK N;8U
Adder
3.747
276655WTG1_EQ
Solar/Wind Harmer
6.415
276656WTG2_EQ
Solar/Wind Harmer
0.849
939741AE1-205 GEN
Solar/Wind Harmer
14.7
276708O09 GEN2
Solar/Wind Harmer
2.615
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
274770LINCOLN ;1U
50/50
10.145
274771LINCOLN ;2U
50/50
10.145
276897AD1-100 C
Solar/Wind Harmer
49.591
274888KELLY CRK;1U
Solar/Wind Harmer
5.384
276776AD2-060 GEN
Solar/Wind Harmer
0.382
958011AF2-095 GEN
Solar/Wind Harmer
13.138
970941AG2-585 GEN
Solar/Wind Harmer
5.018
276893AG1-478 C
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
13.127
958481AF2-142 GEN
Solar/Wind Harmer
12.416
274696ROCKY RD ;4P
Adder
9.344
274695ROCKY RD ;2P
Adder
9.129
274693ROCKY RD ;1P
Adder
9.039
274697ROCKY RD ;3P
Adder
2.48
274683WAUKEGAN ;8U
Adder
17.241
274683WAUKEGAN ;8U
Adder
14.534
962691AG1-118 GEN
Solar/Wind Harmer
24.235
958491AF2-143 GEN
Solar/Wind Harmer
12.104
960751AF2-366 GEN
Solar/Wind Harmer
2.308
276901AD2-066 C O1
Solar/Wind Harmer
2.81
971341AH1-150 GEN
Solar/Wind Harmer
15.583
971343AH1-151 GEN
Solar/Wind Harmer
15.583
276872AE1-163_GEN1
Solar/Wind Harmer
5.224
276876AE1-163_GEN2
Solar/Wind Harmer
5.224
972235AH1-702 GEN1
Adder
1.947
972236AH1-702 GEN2
Adder
1.693
938861AE1-114 GEN
Solar/Wind Harmer
6.199
274764LEE CO EC;5U
Adder
7.004
274765LEE CO EC;6U
Adder
7.004
274762LEE CO EC;3U
Adder
6.987
274763LEE CO EC;4U
Adder
6.922
274805UNIV PK N;1U
Adder
3.755
274808UNIV PK N;4U
Adder
3.73
942111AE2-223 GEN
Solar/Wind Harmer
6.025
276158O29GEN2
Solar/Wind Harmer
3.662
276157O29GEN1
Solar/Wind Harmer
2.784
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
960611AF2-352 GEN
Solar/Wind Harmer
1.623
274880W4-005 GEN4
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276615X2-022 GEN
Solar/Wind Harmer
1.035
276838X2-022 GEN2
Solar/Wind Harmer
0.123
276916AD2-100_GEN
Solar/Wind Harmer
9.568
276911AD2-131_GEN
Solar/Wind Harmer
1.934
274772LINCOLN ;3U
50/50
10.145
274654BRAIDWOOD;1U
50/50
3.551
972259AH1-714 GEN
50/50
18.253
939351AE1-166 GEN
Solar/Wind Harmer
6.331
274887GEN-1.85
Solar/Wind Harmer
4.861
276772AC2-154 GEN
Solar/Wind Harmer
2.546
276843GEN-1.7
Solar/Wind Harmer
0.523
276806AD2-047 C O1
Solar/Wind Harmer
9.76
970707AG2-453 GEN
Solar/Wind Harmer
24.508
276164X3-005 C
Solar/Wind Harmer
0.608
274826FISK ;BP
Adder
9.402
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.398
274730ELWOOD EC;6P
Adder
14.098
274734ELWOOD EC;8P
Adder
14.098
274736ELWOOD EC;9P
Adder
14.098
274729ELWOOD EC;1P
Adder
14.098
943121AE2-341 GEN
Solar/Wind Harmer
12.523
943591AF1-030 GEN
Solar/Wind Harmer
8.349
274803UNIV PARK;6U
Adder
4.863
274862TOP CROP ;2U
Solar/Wind Harmer
4.176
274682WAUKEGAN ;7U
Adder
14.738
276868AE1-113 GEN
Solar/Wind Harmer
8.052
274879MINONK ;1U
Solar/Wind Harmer
5.368
276799AD1-013 GEN
Solar/Wind Harmer
1.741
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.906
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
274724RIVER EC ;11
Adder
13.811
959091AF2-200 GEN
Solar/Wind Harmer
15.583
970571AG2-364 GEN
Solar/Wind Harmer
15.163
274857EASY ROAD;U1
Solar/Wind Harmer
3.598
274760LEE CO EC;1U
Adder
6.987
274767LEE CO EC;8U
Adder
6.905
276603SUBLETTE C
Solar/Wind Harmer
0.785
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274811UNIV PK N;7U
Adder
3.747
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.336
276782AC1-033 GEN
Solar/Wind Harmer
2.854
274878BISHOP HL;2U
Solar/Wind Harmer
2.414
965091AG1-374 GEN
Solar/Wind Harmer
20.941
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.603
971087AG2-675 GEN
Solar/Wind Harmer
2.569
972231SS25-0005
Solar/Wind Harmer
6.139
972181SS23-001
Solar/Wind Harmer
3.837
274752CRETE EC ;2U
Adder
3.162
274753CRETE EC ;3U
Adder
3.162
276785W4-005 GEN1
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.186
957381AF2-032 GEN
Solar/Wind Harmer
0.952
942481AE2-261 GEN
Solar/Wind Harmer
14.068
274751CRETE EC ;1U
Adder
3.162
274754CRETE EC ;4U
Adder
3.162
276686W4-005 GEN3
Solar/Wind Harmer
1.697
276621W2-048 GEN
Solar/Wind Harmer
3.297
965911AG1-460 GEN
Solar/Wind Harmer
0.657
990512J1326
External Queue
3.794844388961792
990117J1214
External Queue
13.054264068603516
990727J1377 G
External Queue
4.411266803741455
990407J1304
External Queue
2.936152935028076
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.95
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.255
MECLTFEXP_MEC->PJM
CLTF
9.382
SIGELTFEXP_SIGE->PJM
CLTF
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.729
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.178
TVALTFEXP_TVA->PJM
CLTF
0.823

Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.93 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1658.94
MW Contribution:
11.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.318
274771LINCOLN ;2U
50/50
10.318
276897AD1-100 C
Solar/Wind Harmer
49.166
274888KELLY CRK;1U
Solar/Wind Harmer
5.357
276776AD2-060 GEN
Solar/Wind Harmer
0.38
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
276893AG1-478 C
Solar/Wind Harmer
0.379
274674JOLIET 9 ;6U
Adder
13.082
958481AF2-142 GEN
Solar/Wind Harmer
12.398
274696ROCKY RD ;4P
Adder
9.313
274695ROCKY RD ;2P
Adder
9.099
274693ROCKY RD ;1P
Adder
9.009
274697ROCKY RD ;3P
Adder
2.472
274683WAUKEGAN ;8U
Adder
17.186
274683WAUKEGAN ;8U
Adder
14.487
958491AF2-143 GEN
Solar/Wind Harmer
12.08
962691AG1-118 GEN
Solar/Wind Harmer
24.15
960751AF2-366 GEN
Solar/Wind Harmer
2.3
276901AD2-066 C O1
Solar/Wind Harmer
2.799
971341AH1-150 GEN
Solar/Wind Harmer
15.529
971343AH1-151 GEN
Solar/Wind Harmer
15.529
276872AE1-163_GEN1
Solar/Wind Harmer
5.21
276876AE1-163_GEN2
Solar/Wind Harmer
5.21
972235AH1-702 GEN1
Adder
1.94
972236AH1-702 GEN2
Adder
1.687
938861AE1-114 GEN
Solar/Wind Harmer
6.178
274764LEE CO EC;5U
Adder
6.979
274765LEE CO EC;6U
Adder
6.979
274773LINCOLN ;4U
50/50
10.318
274774LINCOLN ;5U
50/50
10.318
972207SS24-0001
Solar/Wind Harmer
34.57
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.53
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
274847GR RIDGE ;BU
Solar/Wind Harmer
4.391
274676JOLIET 29;8U
Adder
26.271
274732ELWOOD EC;7P
Adder
14.059
274674JOLIET 9 ;6U
Adder
13.082
274745AC1-111 GEN9
Adder
4.653
274802UNIV PARK;5U
Adder
4.85
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
276691AA1-018 GEN1
Solar/Wind Harmer
0.623
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274682WAUKEGAN ;7U
Adder
14.691
274828WAUKEGAN ;BP
Adder
9.009
276805AD2-038 GEN
Solar/Wind Harmer
4.13
962781AG1-127 GEN
Solar/Wind Harmer
7.623
274872LEEDK;1U
Solar/Wind Harmer
6.553
276882AE2-255 GEN
Solar/Wind Harmer
2.675
971997AH1-543 GEN
Solar/Wind Harmer
12.406
957471AF2-041 GEN
Solar/Wind Harmer
23.293
959081AF2-199 GEN
Solar/Wind Harmer
7.764
971067AG2-660 GEN
Solar/Wind Harmer
1.806
274723RIVER EC ;12
Adder
13.908
274822ROCKFORD ;11
Adder
15.177
970819AG2-516 GEN
Solar/Wind Harmer
9.185
970569AG2-363 GEN
Solar/Wind Harmer
22.669
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.963
274766LEE CO EC;7U
Adder
6.881
274812UNIV PK N;8U
Adder
3.74
276655WTG1_EQ
Solar/Wind Harmer
6.371
276656WTG2_EQ
Solar/Wind Harmer
0.844
939741AE1-205 GEN
Solar/Wind Harmer
14.599
276708O09 GEN2
Solar/Wind Harmer
2.605
276646AC1-214 GEN2
Solar/Wind Harmer
0.964
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
274751CRETE EC ;1U
Adder
3.15
274754CRETE EC ;4U
Adder
3.15
276686W4-005 GEN3
Solar/Wind Harmer
1.686
276621W2-048 GEN
Solar/Wind Harmer
3.277
965911AG1-460 GEN
Solar/Wind Harmer
0.653
274772LINCOLN ;3U
50/50
10.318
274654BRAIDWOOD;1U
50/50
3.53
972259AH1-714 GEN
50/50
18.156
939351AE1-166 GEN
Solar/Wind Harmer
6.277
274887GEN-1.85
Solar/Wind Harmer
4.837
276772AC2-154 GEN
Solar/Wind Harmer
2.533
276843GEN-1.7
Solar/Wind Harmer
0.52
276806AD2-047 C O1
Solar/Wind Harmer
9.712
970707AG2-453 GEN
Solar/Wind Harmer
24.395
276164X3-005 C
Solar/Wind Harmer
0.607
274826FISK ;BP
Adder
9.382
274676JOLIET 29;8U
Adder
25.333
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.059
274730ELWOOD EC;6P
Adder
14.059
274734ELWOOD EC;8P
Adder
14.059
274736ELWOOD EC;9P
Adder
14.059
274803UNIV PARK;6U
Adder
4.85
943121AE2-341 GEN
Solar/Wind Harmer
12.478
943591AF1-030 GEN
Solar/Wind Harmer
8.319
274862TOP CROP ;2U
Solar/Wind Harmer
4.16
274682WAUKEGAN ;7U
Adder
14.691
276868AE1-113 GEN
Solar/Wind Harmer
8.026
274879MINONK ;1U
Solar/Wind Harmer
5.351
276799AD1-013 GEN
Solar/Wind Harmer
1.735
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.896
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
274724RIVER EC ;11
Adder
13.76
959091AF2-200 GEN
Solar/Wind Harmer
15.529
970571AG2-364 GEN
Solar/Wind Harmer
15.113
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.963
274767LEE CO EC;8U
Adder
6.881
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274811UNIV PK N;7U
Adder
3.74
276603SUBLETTE C
Solar/Wind Harmer
0.782
274851PROVIDENC;RU
Solar/Wind Harmer
2.05
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276782AC1-033 GEN
Solar/Wind Harmer
2.842
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
965091AG1-374 GEN
Solar/Wind Harmer
20.799
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.54
971087AG2-675 GEN
Solar/Wind Harmer
2.559
972231SS25-0005
Solar/Wind Harmer
6.115
972181SS23-001
Solar/Wind Harmer
3.822
274752CRETE EC ;2U
Adder
3.15
274753CRETE EC ;3U
Adder
3.15
276785W4-005 GEN1
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.153
957381AF2-032 GEN
Solar/Wind Harmer
0.946
942481AE2-261 GEN
Solar/Wind Harmer
13.986
274762LEE CO EC;3U
Adder
6.963
274763LEE CO EC;4U
Adder
6.897
274805UNIV PK N;1U
Adder
3.748
274808UNIV PK N;4U
Adder
3.723
942111AE2-223 GEN
Solar/Wind Harmer
5.984
276158O29GEN2
Solar/Wind Harmer
3.648
276157O29GEN1
Solar/Wind Harmer
2.774
276645AC1-214 GEN1
Solar/Wind Harmer
0.964
960611AF2-352 GEN
Solar/Wind Harmer
1.612
274880W4-005 GEN4
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276615X2-022 GEN
Solar/Wind Harmer
1.029
276838X2-022 GEN2
Solar/Wind Harmer
0.122
276916AD2-100_GEN
Solar/Wind Harmer
9.512
276911AD2-131_GEN
Solar/Wind Harmer
1.922
274775LINCOLN ;6U
50/50
10.318
274776LINCOLN ;7U
50/50
10.318
274777LINCOLN ;8U
50/50
10.318
972227AH1-698 GEN1
50/50
2.574
274655BRAIDWOOD;2U
50/50
3.418
972228AH1-698 GEN2
50/50
3.651
274660LASCO STA;1U
50/50
6.448
274661LASCO STA;2U
50/50
4.981
274863CRW1-WTG
Solar/Wind Harmer
5.072
274864CRW2-WTG
Solar/Wind Harmer
5.072
960591AF2-350 GEN
Solar/Wind Harmer
9.078
276893AG1-478 C
Solar/Wind Harmer
0.476
970833AG2-524 GEN
Solar/Wind Harmer
7.55
970833AG2-524 GEN
Solar/Wind Harmer
3.512
274687WILL CNTY;4U
Adder
23.991
274687WILL CNTY;4U
Adder
23.991
274827FISK ;RP
Adder
6.649
274675JOLIET 29;7U
Adder
26.271
274675JOLIET 29;7U
Adder
25.333
274800UNIV PARK;3U
Adder
4.988
274801UNIV PARK;4U
Adder
4.988
274728ELWOOD EC;5P
Adder
14.059
274731ELWOOD EC;2P
Adder
14.059
274733ELWOOD EC;3P
Adder
14.059
274735ELWOOD EC;4P
Adder
14.059
274744AC1-111 GEN8
Adder
4.653
274746AC1-111 G10
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970073AG2-061 GEN
Solar/Wind Harmer
1.873
970169AG2-114 GEN
Solar/Wind Harmer
8.041
971411AH1-196 GEN
Solar/Wind Harmer
11.81
971675AH1-338 GEN
Solar/Wind Harmer
14.127
276861AD2-134 GEN
Solar/Wind Harmer
1.4
276863AD2-134 GEN
Solar/Wind Harmer
1.4
971171AH1-044 GEN
Solar/Wind Harmer
15.529
276889AE2-281 GEN
Solar/Wind Harmer
1.489
274823ROCKFORD ;21
Adder
15.067
274856ECOGROVE ;U1
Solar/Wind Harmer
2.572
276611AD2-172 GEN
Solar/Wind Harmer
1.951
276612AE2-035 GEN
Solar/Wind Harmer
1.951
926823AC1-168 GEN
Solar/Wind Harmer
3.26
971681AH1-341 GEN
Solar/Wind Harmer
11.307
972267AH1-718 GEN
Adder
3.058
276726Z2-087_GEN
Solar/Wind Harmer
5.772
959341AF2-225 GEN
Solar/Wind Harmer
10.949
276741O09 GEN1
Solar/Wind Harmer
2.605
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
946321AF1-296 GEN
Solar/Wind Harmer
7.254
274853TWINGROVE;U1
Solar/Wind Harmer
4.995
274854TWINGROVE;U2
Solar/Wind Harmer
4.89
276668AB2-070 GEN1
Solar/Wind Harmer
1.227
276848AB2-070 GEN3
Solar/Wind Harmer
1.227
276849AB2-070 GEN2
Solar/Wind Harmer
1.227
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
990512J1326
External Queue
3.782691478729248
990117J1214
External Queue
13.012457847595215
990727J1377 G
External Queue
4.397138595581055
990407J1304
External Queue
2.92684268951416
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.94
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.408
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.243
MECLTFEXP_MEC->PJM
CLTF
9.347
SIGELTFEXP_SIGE->PJM
CLTF
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.316
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.611
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.954
LAGNLTFEXP_LAGN->PJM
CLTF
3.163
TVALTFEXP_TVA->PJM
CLTF
0.818

Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT2-3___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.99 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1630.47
MW Contribution:
11.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.318
274771LINCOLN ;2U
50/50
10.318
276897AD1-100 C
Solar/Wind Harmer
49.166
274888KELLY CRK;1U
Solar/Wind Harmer
5.357
276776AD2-060 GEN
Solar/Wind Harmer
0.38
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
276893AG1-478 C
Solar/Wind Harmer
0.379
274674JOLIET 9 ;6U
Adder
13.082
958481AF2-142 GEN
Solar/Wind Harmer
12.398
274696ROCKY RD ;4P
Adder
9.313
274695ROCKY RD ;2P
Adder
9.099
274693ROCKY RD ;1P
Adder
9.009
274697ROCKY RD ;3P
Adder
2.472
274683WAUKEGAN ;8U
Adder
17.186
274683WAUKEGAN ;8U
Adder
14.487
958491AF2-143 GEN
Solar/Wind Harmer
12.08
962691AG1-118 GEN
Solar/Wind Harmer
24.15
960751AF2-366 GEN
Solar/Wind Harmer
2.3
276901AD2-066 C O1
Solar/Wind Harmer
2.799
971341AH1-150 GEN
Solar/Wind Harmer
15.529
971343AH1-151 GEN
Solar/Wind Harmer
15.529
276872AE1-163_GEN1
Solar/Wind Harmer
5.21
276876AE1-163_GEN2
Solar/Wind Harmer
5.21
972235AH1-702 GEN1
Adder
1.94
972236AH1-702 GEN2
Adder
1.687
938861AE1-114 GEN
Solar/Wind Harmer
6.178
274764LEE CO EC;5U
Adder
6.979
274765LEE CO EC;6U
Adder
6.979
274762LEE CO EC;3U
Adder
6.963
274763LEE CO EC;4U
Adder
6.897
274805UNIV PK N;1U
Adder
3.748
274808UNIV PK N;4U
Adder
3.723
942111AE2-223 GEN
Solar/Wind Harmer
5.984
276158O29GEN2
Solar/Wind Harmer
3.648
276157O29GEN1
Solar/Wind Harmer
2.774
276645AC1-214 GEN1
Solar/Wind Harmer
0.964
960611AF2-352 GEN
Solar/Wind Harmer
1.612
274880W4-005 GEN4
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276615X2-022 GEN
Solar/Wind Harmer
1.029
276838X2-022 GEN2
Solar/Wind Harmer
0.122
276916AD2-100_GEN
Solar/Wind Harmer
9.512
276911AD2-131_GEN
Solar/Wind Harmer
1.922
274772LINCOLN ;3U
50/50
10.318
274654BRAIDWOOD;1U
50/50
3.53
972259AH1-714 GEN
50/50
18.156
939351AE1-166 GEN
Solar/Wind Harmer
6.277
274887GEN-1.85
Solar/Wind Harmer
4.837
276772AC2-154 GEN
Solar/Wind Harmer
2.533
276843GEN-1.7
Solar/Wind Harmer
0.52
276806AD2-047 C O1
Solar/Wind Harmer
9.712
970707AG2-453 GEN
Solar/Wind Harmer
24.395
276164X3-005 C
Solar/Wind Harmer
0.607
274826FISK ;BP
Adder
9.382
274676JOLIET 29;8U
Adder
25.333
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.059
274730ELWOOD EC;6P
Adder
14.059
274734ELWOOD EC;8P
Adder
14.059
274736ELWOOD EC;9P
Adder
14.059
274803UNIV PARK;6U
Adder
4.85
943121AE2-341 GEN
Solar/Wind Harmer
12.478
943591AF1-030 GEN
Solar/Wind Harmer
8.319
274862TOP CROP ;2U
Solar/Wind Harmer
4.16
274682WAUKEGAN ;7U
Adder
14.691
276868AE1-113 GEN
Solar/Wind Harmer
8.026
274879MINONK ;1U
Solar/Wind Harmer
5.351
276799AD1-013 GEN
Solar/Wind Harmer
1.735
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.896
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
274724RIVER EC ;11
Adder
13.76
959091AF2-200 GEN
Solar/Wind Harmer
15.529
970571AG2-364 GEN
Solar/Wind Harmer
15.113
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.963
274767LEE CO EC;8U
Adder
6.881
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274811UNIV PK N;7U
Adder
3.74
276603SUBLETTE C
Solar/Wind Harmer
0.782
274851PROVIDENC;RU
Solar/Wind Harmer
2.05
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276782AC1-033 GEN
Solar/Wind Harmer
2.842
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
965091AG1-374 GEN
Solar/Wind Harmer
20.799
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.54
971087AG2-675 GEN
Solar/Wind Harmer
2.559
972231SS25-0005
Solar/Wind Harmer
6.115
972181SS23-001
Solar/Wind Harmer
3.822
274752CRETE EC ;2U
Adder
3.15
274753CRETE EC ;3U
Adder
3.15
276785W4-005 GEN1
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.153
957381AF2-032 GEN
Solar/Wind Harmer
0.946
942481AE2-261 GEN
Solar/Wind Harmer
13.986
274773LINCOLN ;4U
50/50
10.318
274774LINCOLN ;5U
50/50
10.318
972207SS24-0001
Solar/Wind Harmer
34.57
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.53
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
274847GR RIDGE ;BU
Solar/Wind Harmer
4.391
274676JOLIET 29;8U
Adder
26.271
274732ELWOOD EC;7P
Adder
14.059
274674JOLIET 9 ;6U
Adder
13.082
274745AC1-111 GEN9
Adder
4.653
274802UNIV PARK;5U
Adder
4.85
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
276691AA1-018 GEN1
Solar/Wind Harmer
0.623
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274682WAUKEGAN ;7U
Adder
14.691
274828WAUKEGAN ;BP
Adder
9.009
276805AD2-038 GEN
Solar/Wind Harmer
4.13
962781AG1-127 GEN
Solar/Wind Harmer
7.623
274872LEEDK;1U
Solar/Wind Harmer
6.553
276882AE2-255 GEN
Solar/Wind Harmer
2.675
971997AH1-543 GEN
Solar/Wind Harmer
12.406
957471AF2-041 GEN
Solar/Wind Harmer
23.293
959081AF2-199 GEN
Solar/Wind Harmer
7.764
971067AG2-660 GEN
Solar/Wind Harmer
1.806
274723RIVER EC ;12
Adder
13.908
274822ROCKFORD ;11
Adder
15.177
970819AG2-516 GEN
Solar/Wind Harmer
9.185
970569AG2-363 GEN
Solar/Wind Harmer
22.669
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.963
274766LEE CO EC;7U
Adder
6.881
274812UNIV PK N;8U
Adder
3.74
276655WTG1_EQ
Solar/Wind Harmer
6.371
276656WTG2_EQ
Solar/Wind Harmer
0.844
939741AE1-205 GEN
Solar/Wind Harmer
14.599
276708O09 GEN2
Solar/Wind Harmer
2.605
276646AC1-214 GEN2
Solar/Wind Harmer
0.964
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
274751CRETE EC ;1U
Adder
3.15
274754CRETE EC ;4U
Adder
3.15
276686W4-005 GEN3
Solar/Wind Harmer
1.686
276621W2-048 GEN
Solar/Wind Harmer
3.277
965911AG1-460 GEN
Solar/Wind Harmer
0.653
274775LINCOLN ;6U
50/50
10.318
274776LINCOLN ;7U
50/50
10.318
274777LINCOLN ;8U
50/50
10.318
972227AH1-698 GEN1
50/50
2.574
274655BRAIDWOOD;2U
50/50
3.418
972228AH1-698 GEN2
50/50
3.651
274660LASCO STA;1U
50/50
6.448
274661LASCO STA;2U
50/50
4.981
274863CRW1-WTG
Solar/Wind Harmer
5.072
274864CRW2-WTG
Solar/Wind Harmer
5.072
960591AF2-350 GEN
Solar/Wind Harmer
9.078
276893AG1-478 C
Solar/Wind Harmer
0.476
970833AG2-524 GEN
Solar/Wind Harmer
7.55
970833AG2-524 GEN
Solar/Wind Harmer
3.512
274687WILL CNTY;4U
Adder
23.991
274687WILL CNTY;4U
Adder
23.991
274827FISK ;RP
Adder
6.649
274675JOLIET 29;7U
Adder
26.271
274675JOLIET 29;7U
Adder
25.333
274800UNIV PARK;3U
Adder
4.988
274801UNIV PARK;4U
Adder
4.988
274728ELWOOD EC;5P
Adder
14.059
274731ELWOOD EC;2P
Adder
14.059
274733ELWOOD EC;3P
Adder
14.059
274735ELWOOD EC;4P
Adder
14.059
274744AC1-111 GEN8
Adder
4.653
274746AC1-111 G10
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970073AG2-061 GEN
Solar/Wind Harmer
1.873
970169AG2-114 GEN
Solar/Wind Harmer
8.041
971411AH1-196 GEN
Solar/Wind Harmer
11.81
971675AH1-338 GEN
Solar/Wind Harmer
14.127
276861AD2-134 GEN
Solar/Wind Harmer
1.4
276863AD2-134 GEN
Solar/Wind Harmer
1.4
971171AH1-044 GEN
Solar/Wind Harmer
15.529
276889AE2-281 GEN
Solar/Wind Harmer
1.489
274823ROCKFORD ;21
Adder
15.067
274856ECOGROVE ;U1
Solar/Wind Harmer
2.572
276611AD2-172 GEN
Solar/Wind Harmer
1.951
276612AE2-035 GEN
Solar/Wind Harmer
1.951
926823AC1-168 GEN
Solar/Wind Harmer
3.26
971681AH1-341 GEN
Solar/Wind Harmer
11.307
972267AH1-718 GEN
Adder
3.058
276726Z2-087_GEN
Solar/Wind Harmer
5.772
959341AF2-225 GEN
Solar/Wind Harmer
10.949
276741O09 GEN1
Solar/Wind Harmer
2.605
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
946321AF1-296 GEN
Solar/Wind Harmer
7.254
274853TWINGROVE;U1
Solar/Wind Harmer
4.995
274854TWINGROVE;U2
Solar/Wind Harmer
4.89
276668AB2-070 GEN1
Solar/Wind Harmer
1.227
276848AB2-070 GEN3
Solar/Wind Harmer
1.227
276849AB2-070 GEN2
Solar/Wind Harmer
1.227
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
990512J1326
External Queue
3.782691478729248
990117J1214
External Queue
13.012457847595215
990727J1377 G
External Queue
4.397138595581055
990407J1304
External Queue
2.92684268951416
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.94
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.316
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.611
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.243
MECLTFEXP_MEC->PJM
CLTF
9.347
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.954
LAGNLTFEXP_LAGN->PJM
CLTF
3.163
TVALTFEXP_TVA->PJM
CLTF
0.818

Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT4-5___SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:CE
Facility Description:
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.99 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1630.44
MW Contribution:
11.31
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.318
274771LINCOLN ;2U
50/50
10.318
276897AD1-100 C
Solar/Wind Harmer
49.166
274888KELLY CRK;1U
Solar/Wind Harmer
5.357
274772LINCOLN ;3U
50/50
10.318
274654BRAIDWOOD;1U
50/50
3.53
972259AH1-714 GEN
50/50
18.156
939351AE1-166 GEN
Solar/Wind Harmer
6.277
274887GEN-1.85
Solar/Wind Harmer
4.837
276772AC2-154 GEN
Solar/Wind Harmer
2.533
276843GEN-1.7
Solar/Wind Harmer
0.52
276806AD2-047 C O1
Solar/Wind Harmer
9.712
970707AG2-453 GEN
Solar/Wind Harmer
24.395
276164X3-005 C
Solar/Wind Harmer
0.607
274826FISK ;BP
Adder
9.382
274676JOLIET 29;8U
Adder
25.333
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.059
274730ELWOOD EC;6P
Adder
14.059
274734ELWOOD EC;8P
Adder
14.059
274736ELWOOD EC;9P
Adder
14.059
274803UNIV PARK;6U
Adder
4.85
943121AE2-341 GEN
Solar/Wind Harmer
12.478
943591AF1-030 GEN
Solar/Wind Harmer
8.319
274862TOP CROP ;2U
Solar/Wind Harmer
4.16
274682WAUKEGAN ;7U
Adder
14.691
276868AE1-113 GEN
Solar/Wind Harmer
8.026
274879MINONK ;1U
Solar/Wind Harmer
5.351
276799AD1-013 GEN
Solar/Wind Harmer
1.735
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.896
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
274724RIVER EC ;11
Adder
13.76
959091AF2-200 GEN
Solar/Wind Harmer
15.529
970571AG2-364 GEN
Solar/Wind Harmer
15.113
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.963
274767LEE CO EC;8U
Adder
6.881
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274811UNIV PK N;7U
Adder
3.74
276603SUBLETTE C
Solar/Wind Harmer
0.782
274851PROVIDENC;RU
Solar/Wind Harmer
2.05
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276782AC1-033 GEN
Solar/Wind Harmer
2.842
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
965091AG1-374 GEN
Solar/Wind Harmer
20.799
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.54
971087AG2-675 GEN
Solar/Wind Harmer
2.559
972231SS25-0005
Solar/Wind Harmer
6.115
972181SS23-001
Solar/Wind Harmer
3.822
274752CRETE EC ;2U
Adder
3.15
274753CRETE EC ;3U
Adder
3.15
276785W4-005 GEN1
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.153
957381AF2-032 GEN
Solar/Wind Harmer
0.946
942481AE2-261 GEN
Solar/Wind Harmer
13.986
276776AD2-060 GEN
Solar/Wind Harmer
0.38
958011AF2-095 GEN
Solar/Wind Harmer
13.073
970941AG2-585 GEN
Solar/Wind Harmer
4.993
276893AG1-478 C
Solar/Wind Harmer
0.379
274674JOLIET 9 ;6U
Adder
13.082
958481AF2-142 GEN
Solar/Wind Harmer
12.398
274696ROCKY RD ;4P
Adder
9.313
274695ROCKY RD ;2P
Adder
9.099
274693ROCKY RD ;1P
Adder
9.009
274697ROCKY RD ;3P
Adder
2.472
274683WAUKEGAN ;8U
Adder
17.186
274683WAUKEGAN ;8U
Adder
14.487
958491AF2-143 GEN
Solar/Wind Harmer
12.08
962691AG1-118 GEN
Solar/Wind Harmer
24.15
960751AF2-366 GEN
Solar/Wind Harmer
2.3
276901AD2-066 C O1
Solar/Wind Harmer
2.799
971341AH1-150 GEN
Solar/Wind Harmer
15.529
971343AH1-151 GEN
Solar/Wind Harmer
15.529
276872AE1-163_GEN1
Solar/Wind Harmer
5.21
276876AE1-163_GEN2
Solar/Wind Harmer
5.21
972235AH1-702 GEN1
Adder
1.94
972236AH1-702 GEN2
Adder
1.687
938861AE1-114 GEN
Solar/Wind Harmer
6.178
274764LEE CO EC;5U
Adder
6.979
274765LEE CO EC;6U
Adder
6.979
274762LEE CO EC;3U
Adder
6.963
274763LEE CO EC;4U
Adder
6.897
274805UNIV PK N;1U
Adder
3.748
274808UNIV PK N;4U
Adder
3.723
942111AE2-223 GEN
Solar/Wind Harmer
5.984
276158O29GEN2
Solar/Wind Harmer
3.648
276157O29GEN1
Solar/Wind Harmer
2.774
276645AC1-214 GEN1
Solar/Wind Harmer
0.964
960611AF2-352 GEN
Solar/Wind Harmer
1.612
274880W4-005 GEN4
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276615X2-022 GEN
Solar/Wind Harmer
1.029
276838X2-022 GEN2
Solar/Wind Harmer
0.122
276916AD2-100_GEN
Solar/Wind Harmer
9.512
276911AD2-131_GEN
Solar/Wind Harmer
1.922
274773LINCOLN ;4U
50/50
10.318
274774LINCOLN ;5U
50/50
10.318
972207SS24-0001
Solar/Wind Harmer
34.57
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.53
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
274847GR RIDGE ;BU
Solar/Wind Harmer
4.391
274676JOLIET 29;8U
Adder
26.271
274732ELWOOD EC;7P
Adder
14.059
274674JOLIET 9 ;6U
Adder
13.082
274745AC1-111 GEN9
Adder
4.653
274802UNIV PARK;5U
Adder
4.85
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
276691AA1-018 GEN1
Solar/Wind Harmer
0.623
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274682WAUKEGAN ;7U
Adder
14.691
274828WAUKEGAN ;BP
Adder
9.009
276805AD2-038 GEN
Solar/Wind Harmer
4.13
962781AG1-127 GEN
Solar/Wind Harmer
7.623
274872LEEDK;1U
Solar/Wind Harmer
6.553
276882AE2-255 GEN
Solar/Wind Harmer
2.675
971997AH1-543 GEN
Solar/Wind Harmer
12.406
957471AF2-041 GEN
Solar/Wind Harmer
23.293
959081AF2-199 GEN
Solar/Wind Harmer
7.764
971067AG2-660 GEN
Solar/Wind Harmer
1.806
274723RIVER EC ;12
Adder
13.908
274822ROCKFORD ;11
Adder
15.177
970819AG2-516 GEN
Solar/Wind Harmer
9.185
970569AG2-363 GEN
Solar/Wind Harmer
22.669
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.963
274766LEE CO EC;7U
Adder
6.881
274812UNIV PK N;8U
Adder
3.74
276655WTG1_EQ
Solar/Wind Harmer
6.371
276656WTG2_EQ
Solar/Wind Harmer
0.844
939741AE1-205 GEN
Solar/Wind Harmer
14.599
276708O09 GEN2
Solar/Wind Harmer
2.605
276646AC1-214 GEN2
Solar/Wind Harmer
0.964
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
274751CRETE EC ;1U
Adder
3.15
274754CRETE EC ;4U
Adder
3.15
276686W4-005 GEN3
Solar/Wind Harmer
1.686
276621W2-048 GEN
Solar/Wind Harmer
3.277
965911AG1-460 GEN
Solar/Wind Harmer
0.653
274775LINCOLN ;6U
50/50
10.318
274776LINCOLN ;7U
50/50
10.318
274777LINCOLN ;8U
50/50
10.318
972227AH1-698 GEN1
50/50
2.574
274655BRAIDWOOD;2U
50/50
3.418
972228AH1-698 GEN2
50/50
3.651
274660LASCO STA;1U
50/50
6.448
274661LASCO STA;2U
50/50
4.981
274863CRW1-WTG
Solar/Wind Harmer
5.072
274864CRW2-WTG
Solar/Wind Harmer
5.072
960591AF2-350 GEN
Solar/Wind Harmer
9.078
276893AG1-478 C
Solar/Wind Harmer
0.476
970833AG2-524 GEN
Solar/Wind Harmer
7.55
970833AG2-524 GEN
Solar/Wind Harmer
3.512
274687WILL CNTY;4U
Adder
23.991
274687WILL CNTY;4U
Adder
23.991
274827FISK ;RP
Adder
6.649
274675JOLIET 29;7U
Adder
26.271
274675JOLIET 29;7U
Adder
25.333
274800UNIV PARK;3U
Adder
4.988
274801UNIV PARK;4U
Adder
4.988
274728ELWOOD EC;5P
Adder
14.059
274731ELWOOD EC;2P
Adder
14.059
274733ELWOOD EC;3P
Adder
14.059
274735ELWOOD EC;4P
Adder
14.059
274744AC1-111 GEN8
Adder
4.653
274746AC1-111 G10
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970073AG2-061 GEN
Solar/Wind Harmer
1.873
970169AG2-114 GEN
Solar/Wind Harmer
8.041
971411AH1-196 GEN
Solar/Wind Harmer
11.81
971675AH1-338 GEN
Solar/Wind Harmer
14.127
276861AD2-134 GEN
Solar/Wind Harmer
1.4
276863AD2-134 GEN
Solar/Wind Harmer
1.4
971171AH1-044 GEN
Solar/Wind Harmer
15.529
276889AE2-281 GEN
Solar/Wind Harmer
1.489
274823ROCKFORD ;21
Adder
15.067
274856ECOGROVE ;U1
Solar/Wind Harmer
2.572
276611AD2-172 GEN
Solar/Wind Harmer
1.951
276612AE2-035 GEN
Solar/Wind Harmer
1.951
926823AC1-168 GEN
Solar/Wind Harmer
3.26
971681AH1-341 GEN
Solar/Wind Harmer
11.307
972267AH1-718 GEN
Adder
3.058
276726Z2-087_GEN
Solar/Wind Harmer
5.772
959341AF2-225 GEN
Solar/Wind Harmer
10.949
276741O09 GEN1
Solar/Wind Harmer
2.605
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
946321AF1-296 GEN
Solar/Wind Harmer
7.254
274853TWINGROVE;U1
Solar/Wind Harmer
4.995
274854TWINGROVE;U2
Solar/Wind Harmer
4.89
276668AB2-070 GEN1
Solar/Wind Harmer
1.227
276848AB2-070 GEN3
Solar/Wind Harmer
1.227
276849AB2-070 GEN2
Solar/Wind Harmer
1.227
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
990512J1326
External Queue
3.782691478729248
990117J1214
External Queue
13.012457847595215
990727J1377 G
External Queue
4.397138595581055
990407J1304
External Queue
2.92684268951416
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.94
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.408
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.243
MECLTFEXP_MEC->PJM
CLTF
9.347
SIGELTFEXP_SIGE->PJM
CLTF
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.316
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.611
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.954
LAGNLTFEXP_LAGN->PJM
CLTF
3.163
TVALTFEXP_TVA->PJM
CLTF
0.818
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-825_SRT-A'
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-824_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290598 TO BUS 290599 CKT 1    /*05GREENTW_RJ 765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P7-1_#11046___SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 246955 CKT 1   /*05DUMONT     345.0 - 05OLIVE_BP   345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243234 CKT 1   /*05MERIDN     345.0 - 05TWIN B     345.0
 OPEN BRANCH FROM BUS 243232 TO BUS 246955 CKT 1   /*05SORENS     345.0 - 05OLIVE_BP   345.0
END
CONTINGENCY 'AEP_P4_#17234_05GRNTWN 765_N_SRT-A'
 OPEN BRANCH FROM BUS 243207 TO BUS 290222 CKT 3    /*05GRNTWN     765.0 - 05GRNTWN 3EQ   1.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 244658 TO BUS 290221 CKT 3    /*05GRNTWN     138.0 - 05GRNTW3_XFL 138.0
 OPEN BRANCH FROM BUS 290221 TO BUS 290222 CKT 3    /*05GRNTW3_XFL 138.0 - 05GRNTWN 3EQ   1.0
 OPEN BRANCH FROM BUS 290222 TO BUS 290223 CKT 3    /*05GRNTWN 3EQ   1.0 - 05GRNTWN T3   13.8
 OPEN BRANCH FROM BUS 290598 TO BUS 290599 CKT 1    /*05GREENTW_RJ 765.0 - 05JEFFRSN_RG 765.0
END
CONTINGENCY 'AEP_P7-1_#11001___SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 246955 CKT 1   /*05DUMONT     345.0 - 05OLIVE_BP   345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243232 CKT 1   /*05MERIDN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 243232 TO BUS 246955 CKT 1   /*05SORENS     345.0 - 05OLIVE_BP   345.0
END
CONTINGENCY 'AEP_P2-2_#6229_05MERIDN 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243228 TO BUS 243232 CKT 1   /*05MERIDN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243234 CKT 1   /*05MERIDN     345.0 - 05TWIN B     345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243783 CKT 1   /*05MERIDN     345.0 - 05EWHTLY     345.0
END
CONTINGENCY 'AEP_P2-2_#702_05JEFRSO 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2   /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1   /*05JEFRSO     345.0 - 06CLIFTY     345.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290597 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290602 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290597 CKT 1    /*05GRNTWN     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 270644 TO BUS 290602 CKT 1    /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 290602 CKT 1   /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 290602 CKT 1   /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'AEP_P4_#671_05COOK 345_M2_SRT-A'
 OPEN BRANCH FROM BUS 243215 TO BUS 243229 CKT 1   /*05COOK       345.0 - 05OLIVE      345.0
END
CONTINGENCY 'AEP_P4_#6560_05COOK 345_M_SRT-A'
 OPEN BRANCH FROM BUS 243215 TO BUS 243223 CKT 1   /*05COOK       345.0 - 05JACKSON RD 345.0
 OPEN BRANCH FROM BUS 243215 TO BUS 243229 CKT 1   /*05COOK       345.0 - 05OLIVE      345.0
END
CONTINGENCY 'AEP_P7-1_#10997___SRT-A'
 OPEN BRANCH FROM BUS 243215 TO BUS 243223 CKT 1   /*05COOK       345.0 - 05JACKSON RD 345.0
 OPEN BRANCH FROM BUS 243215 TO BUS 243229 CKT 1   /*05COOK       345.0 - 05OLIVE      345.0
END
CONTINGENCY 'AEP_P4_#8075_05MARYSV 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P4_#711_05MARYSV 765_A1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#711_6224_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P1-3_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#8072_05MARYSV 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2   /*05MARYSV     765.0 - 05MARYSV     345.0
END
CONTINGENCY 'AEP_P1-3_#8072_05MARYSV 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2   /*05MARYSV     765.0 - 05MARYSV     345.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7442_200545_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-027A_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 239289 CKT 1   /*02DAV-BE     345.0 - 02HAYES      345.0
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 243918 CKT 1   /*05DUMONT     345.0 - 05ELDERBERRY 345.0
END
CONTINGENCY 'AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243229 TO BUS 243918 CKT 1   /*05OLIVE      345.0 - 05ELDERBERRY 345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-025T_SRT-A'
 DISCONNECT BRANCH FROM BUS 238889 TO BUS 265709 CKT 1   /*02LEMOYN     345.0 - 19MAPLE      345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 256583 CKT 1   /*19LULU       345.0 - 18MOROCCO    345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264613 CKT 1   /*19LULU       345.0 - 19MON34      345.0
 DISCONNECT BRANCH FROM BUS 264594 TO BUS 264839 CKT 1   /*19LULU       345.0 - 19MILAN      345.0
END
CONTINGENCY 'COMED_P2-2_116_GG-345R__2_SRT-A'
 DISCONNECT BUS 270769   /*GOODINGS ;2R 345.0
END
CONTINGENCY 'COMED_P4_167-65-BT4-5___SRT-A'
 TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1   /*COLLINS  ;   765.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1   /*PLANO    ;4M 345.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1   /*PLANO    ;4M 345.0 - PLANO    ; R 345.0
 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1   /*PLANO    ;4M 345.0 - PLANO    ;4C  33.0
END
CONTINGENCY 'COMED_P4_167-65-BT3-4___SRT-A'
 TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1   /*COLLINS  ;   765.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1   /*PLANO    ;3M 345.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1   /*PLANO    ;3M 345.0 - PLANO    ; B 345.0
 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1   /*PLANO    ;3M 345.0 - PLANO    ;3C  33.0
END
CONTINGENCY 'COMED_P4-6_116-345-R______SRT-A'
 DISCONNECT BUS 270767                                          /*GOODINGS ;1R 345.0
 DISCONNECT BUS 270769                                          /*GOODINGS ;2R 345.0
 DISCONNECT BUS 275240                                          /*GOODINGS ;1M 138.0
 TRIP BRANCH FROM BUS 270729 TO BUS 271385 TO BUS 275351 CKT 1  /*E FRANKFO; R 345.0 - E FRANKFO; R 138.0 - E FRANKFO;3C  34.5
END
CONTINGENCY 'COMED_P4_116-45-L11614__SRT-A'
 DISCONNECT BUS 270769                             /*GOODINGS ;2R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270665 CKT 1   /*BLUE ISL ;RT 345.0 - BLUE ISL ; R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270927 CKT 1   /*BLUE ISL ;RT 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 270769 TO BUS 270667 CKT 1   /*GOODINGS ;2R 345.0 - BLUE ISL ;RT 345.0
END
CONTINGENCY 'COMED_P4_116-45-TR82____SRT-A'
 DISCONNECT BUS 270769                                          /*GOODINGS ;2R 345.0
 TRIP BRANCH FROM BUS 270769 TO BUS 271565 TO BUS 275324 CKT 1  /*GOODINGS ;2R 345.0 - GOODINGS ; R 138.0 - GOODINGS ;2C  34.5
END
CONTINGENCY 'COMED_P4_116-45-L0303___SRT-A'
 DISCONNECT BUS 270769                             /*GOODINGS ;2R 345.0
 REMOVE SWSHUNT FROM BUS 270827                    /*NEVADA   ; R 345.0
 TRIP BRANCH FROM BUS 270854 TO BUS 276883 CKT 1   /*POWERTON ; B 345.0 - AE2-281 TAP  345.0
END
CONTINGENCY 'COMED_P4_023-65-BT3-4___SRT-A'
 TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1   /*COLLINS  ;   765.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ; R 345.0
 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;2C  33.0
END
CONTINGENCY 'COMED_P4_023-65-BT2-3___SRT-A'
 TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1   /*COLLINS  ;   765.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
END
CONTINGENCY 'COMED_P4_023-65-BT4-5___SRT-A'
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ; R 345.0
 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;2C  33.0
END
238563 to 238654 ckt 1
238654 to 239289 ckt 1
239289 to 238569 ckt 1
243211 to 242933 ckt 1
247977 to 242524 ckt 17
242519 to 314912 ckt 1
243206 to 290606 ckt Z1
290606 to 246999 ckt 1
243918 to 243219 ckt 1
242923 to 242516 ckt 1
243208 to 242865 ckt 2
242865 to 248000 ckt 1
246929 to 242935 ckt 1
242926 to 246751 ckt 1
242928 to 242939 ckt 2
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
242516 to 242920 ckt 1
242933 to 965420 ckt 1
243232 to 246999 ckt 3
246999 to 290607 ckt Z1
290607 to 290608 ckt 1
243233 to 249567 ckt 1
248005 to 242528 ckt 1
255113 to 243219 ckt 1
264612 to 241901 ckt 1
957470 to 270732 ckt 1
965420 to 246929 ckt 1
270697 to 275168 ckt 1
275168 to 270607 ckt 1
270770 to 270766 ckt 1
270926 to 275232 ckt 1
270927 to 275233 ckt 1
270644 to 290602 ckt 1
275232 to 270644 ckt 1
275233 to 270644 ckt 1

Winter Peak Analysis

The New Service Request AH1-341 was evaluated as a 150.0 MW (96.6 MW Capacity) injection in the ComEd area.

AH1-341 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P4_006-45-BT3-8___SRT-A
BreakerAC100.35 %1912.0STE1918.71
1.31
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P4_006-45-BT3-4___SRT-A
BreakerAC100.08 %1912.0STE1913.55
1.3

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.35 %
Rating:1912.0 MVA
Rating Type:STE
MVA to Mitigate:1918.71
MW Contribution:
1.31
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.12 %
Rating:1912.0 MVA
Rating Type:STE
MVA to Mitigate:1914.23
MW Contribution:
1.3
Bus #Bus NameTypeMW Contribution
274764LEE CO EC;5U
50/50
28.632
274766LEE CO EC;7U
50/50
28.201
274857EASY ROAD;U1
Solar/Wind Harmer
15.509
972267AH1-718 GEN
50/50
3.646
971675AH1-338 GEN
Solar/Wind Harmer
0.766
274717NELSON EC;2C
50/50
3.156
965931AG1-462 GEN
Solar/Wind Harmer
2.977
274878BISHOP HL;2U
Solar/Wind Harmer
4.486
276646AC1-214 GEN2
Solar/Wind Harmer
1.461
274760LEE CO EC;1U
50/50
28.665
274763LEE CO EC;4U
50/50
28.433
276741O09 GEN1
Solar/Wind Harmer
10.137
276676AA2-030 GEN
50/50
3.443
274699CORDOVA ;1C
50/50
2.674
274700CORDOVA ;2C
50/50
2.61
276158O29GEN2
Solar/Wind Harmer
10.795
276708O09 GEN2
Solar/Wind Harmer
10.137
274761LEE CO EC;2U
50/50
28.565
274762LEE CO EC;3U
50/50
28.565
274858EASY ROAD;U2
Solar/Wind Harmer
15.509
971681AH1-341 GEN
Solar/Wind Harmer
1.308
938861AE1-114 GEN
Solar/Wind Harmer
18.663
274850MENDOTA H;RU
Solar/Wind Harmer
2.584
276863AD2-134 GEN
Solar/Wind Harmer
1.797
276861AD2-134 GEN
Solar/Wind Harmer
1.797
274856ECOGROVE ;U1
Solar/Wind Harmer
3.202
274716NELSON EC;1S
50/50
2.341
971171AH1-044 GEN
Solar/Wind Harmer
5.857
946321AF1-296 GEN
Solar/Wind Harmer
33.895
274662QUAD CITI;1U
50/50
12.143
276782AC1-033 GEN
Solar/Wind Harmer
4.524
274855GSG-6 ;RU
Solar/Wind Harmer
3.716
276677AA1-146_GEN
50/50
3.443
276157O29GEN1
Solar/Wind Harmer
10.795
276645AC1-214 GEN1
Solar/Wind Harmer
1.461
276603SUBLETTE C
Solar/Wind Harmer
2.338
276602WESTBROOK C
Solar/Wind Harmer
1.833
957471AF2-041 GEN
Solar/Wind Harmer
8.785
274848CAMPGROVE;RU
Solar/Wind Harmer
5.97
971343AH1-151 GEN
Solar/Wind Harmer
5.857
971087AG2-675 GEN
Solar/Wind Harmer
7.473
274767LEE CO EC;8U
50/50
28.201
971341AH1-150 GEN
Solar/Wind Harmer
5.857
274877BISHOP HL;1U
Solar/Wind Harmer
4.486
959091AF2-200 GEN
Solar/Wind Harmer
5.857
274849CRESCENT ;1U
Solar/Wind Harmer
2.004
274715NELSON EC;1C
50/50
3.197
274765LEE CO EC;6U
50/50
28.764
274701CORDOVA ;1S
50/50
2.434
971067AG2-660 GEN
Solar/Wind Harmer
11.713
274718NELSON EC;2S
50/50
2.341
274663QUAD CITI;2U
50/50
12.172
959081AF2-199 GEN
Solar/Wind Harmer
2.928
274851PROVIDENC;RU
Solar/Wind Harmer
2.723
991092J1477
External Queue
0
991303J1755 G
External Queue
5.969897747039795
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.093
CPLELTFEXP_CPLE->PJM
CLTF
0.137
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.895
TVALTFEXP_TVA->PJM
CLTF
1.342
LAGNLTFEXP_LAGN->PJM
CLTF
4.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.653
WECLTFEXP_WEC->PJM
CLTF
0.103
MECLTFEXP_MEC->PJM
CLTF
14.653
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
131.473
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.641
NYPJM->LTFIMP_NY
CLTF
0.275
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.079
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-4___SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.08 %
Rating:1912.0 MVA
Rating Type:STE
MVA to Mitigate:1913.55
MW Contribution:
1.3
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_006-45-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:99.87 %
Rating:1912.0 MVA
Rating Type:STE
MVA to Mitigate:1909.48
MW Contribution:
1.29
Bus #Bus NameTypeMW Contribution
274764LEE CO EC;5U
50/50
28.57
274766LEE CO EC;7U
50/50
28.14
274857EASY ROAD;U1
Solar/Wind Harmer
15.475
972267AH1-718 GEN
50/50
3.638
971675AH1-338 GEN
Solar/Wind Harmer
0.76
274717NELSON EC;2C
50/50
3.149
965931AG1-462 GEN
Solar/Wind Harmer
2.966
274878BISHOP HL;2U
Solar/Wind Harmer
4.471
276646AC1-214 GEN2
Solar/Wind Harmer
1.456
274760LEE CO EC;1U
50/50
28.603
274763LEE CO EC;4U
50/50
28.371
276741O09 GEN1
Solar/Wind Harmer
10.107
276676AA2-030 GEN
50/50
3.436
274699CORDOVA ;1C
50/50
2.664
274700CORDOVA ;2C
50/50
2.601
276158O29GEN2
Solar/Wind Harmer
10.763
276708O09 GEN2
Solar/Wind Harmer
10.107
274761LEE CO EC;2U
50/50
28.504
274762LEE CO EC;3U
50/50
28.504
274858EASY ROAD;U2
Solar/Wind Harmer
15.475
971681AH1-341 GEN
Solar/Wind Harmer
1.297
938861AE1-114 GEN
Solar/Wind Harmer
18.401
274850MENDOTA H;RU
Solar/Wind Harmer
2.561
276863AD2-134 GEN
Solar/Wind Harmer
1.781
276861AD2-134 GEN
Solar/Wind Harmer
1.781
274856ECOGROVE ;U1
Solar/Wind Harmer
3.071
274716NELSON EC;1S
50/50
2.336
971171AH1-044 GEN
Solar/Wind Harmer
5.855
946321AF1-296 GEN
Solar/Wind Harmer
33.753
274662QUAD CITI;1U
50/50
12.096
276782AC1-033 GEN
Solar/Wind Harmer
4.509
274855GSG-6 ;RU
Solar/Wind Harmer
3.684
276677AA1-146_GEN
50/50
3.436
276157O29GEN1
Solar/Wind Harmer
10.763
276645AC1-214 GEN1
Solar/Wind Harmer
1.456
276603SUBLETTE C
Solar/Wind Harmer
2.327
276602WESTBROOK C
Solar/Wind Harmer
1.817
957471AF2-041 GEN
Solar/Wind Harmer
8.782
274848CAMPGROVE;RU
Solar/Wind Harmer
5.951
971343AH1-151 GEN
Solar/Wind Harmer
5.855
971087AG2-675 GEN
Solar/Wind Harmer
7.444
274767LEE CO EC;8U
50/50
28.14
971341AH1-150 GEN
Solar/Wind Harmer
5.855
274877BISHOP HL;1U
Solar/Wind Harmer
4.471
959091AF2-200 GEN
Solar/Wind Harmer
5.855
274849CRESCENT ;1U
Solar/Wind Harmer
1.998
274715NELSON EC;1C
50/50
3.191
274765LEE CO EC;6U
50/50
28.702
274701CORDOVA ;1S
50/50
2.425
971067AG2-660 GEN
Solar/Wind Harmer
11.71
274718NELSON EC;2S
50/50
2.336
274663QUAD CITI;2U
50/50
12.125
959081AF2-199 GEN
Solar/Wind Harmer
2.927
274851PROVIDENC;RU
Solar/Wind Harmer
2.715
991092J1477
External Queue
0
991303J1755 G
External Queue
6.020914077758789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.403
WECLTFEXP_WEC->PJM
CLTF
0.06
MECLTFEXP_MEC->PJM
CLTF
14.496
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
130.456
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.412
NYPJM->LTFIMP_NY
CLTF
0.274
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.079
SIGELTFEXP_SIGE->PJM
CLTF
0.019
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.881
TVALTFEXP_TVA->PJM
CLTF
1.328
LAGNLTFEXP_LAGN->PJM
CLTF
4.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.049
CPLELTFEXP_CPLE->PJM
CLTF
0.134
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.175
CONTINGENCY 'COMED_P4_006-45-BT3-8___SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 270679 CKT Z1   /*BYRON    ; B 345.0 - BYRON    ; R 345.0
 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1    /*LEE CO EC;BP 345.0 - BYRON    ; B 345.0
END
CONTINGENCY 'COMED_P4_006-45-BT3-4___SRT-A'
 REMOVE UNIT 1 FROM BUS 274656                     /*BYRON    ;1U  25.0
 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1   /*LEE CO EC;BP 345.0 - BYRON    ; B 345.0
END
957470 to 270732 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC120.49 %1737.0B2092.95
0.59
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC118.4 %1737.0B2056.53
0.6
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC116.41 %1737.0B2022.06
0.6
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC115.97 %1737.0B2014.34
0.58
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC108.18 %5133.0B5552.88
1.63
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC103.35 %3276.0B3385.78
0.66
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#709_546_SRT-A
SingleAC101.76 %3276.0B3333.77
0.67
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC101.76 %3276.0B3333.74
0.67
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC111.9 %2991.0B3346.96
0.66
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC110.0 %2991.0B3290.17
0.67
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC110.0 %2991.0B3290.12
0.67
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC113.19 %4961.0B5615.13
1.73
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC103.69 %4961.0B5144.06
1.6
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC103.1 %4961.0B5114.58
1.69
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC102.1 %4961.0B5065.25
1.6
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC102.1 %4961.0B5065.17
1.6
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC103.66 %2219.0B2300.12
0.59
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC101.06 %2219.0B2242.58
0.6
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC100.53 %2219.0B2230.82
0.6
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC100.04 %2219.0B2219.82
0.58
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC108.89 %2317.0B2523.04
0.4
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC107.9 %2317.0B2499.98
0.41
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC107.01 %2317.0B2479.49
0.41
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC107.01 %2317.0B2479.4
0.4
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
BusAC106.64 %2317.0B2470.96
0.39
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
BreakerAC106.64 %2317.0B2470.93
0.39
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC106.03 %2219.0B2352.88
0.59
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC103.21 %2219.0B2290.26
0.6
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC102.89 %2219.0B2283.06
0.6
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC102.36 %2219.0B2271.47
0.58

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.49 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2092.95
MW Contribution:
0.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270246TR4_N_V150
Solar/Wind Harmer
1.152
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.556
970291AG2-192 GEN
Solar/Wind Harmer
0.303
274871GR RIDGE ;2U
Solar/Wind Harmer
5.335
970583AG2-370 GEN
50/50
2.758
965051AG1-369 GEN
Solar/Wind Harmer
0.293
970349AG2-230 GEN
Solar/Wind Harmer
0.721
943121AE2-341 GEN
Solar/Wind Harmer
0.627
957471AF2-041 GEN
Solar/Wind Harmer
1.206
274848CAMPGROVE;RU
Solar/Wind Harmer
4.509
276785W4-005 GEN1
Solar/Wind Harmer
2.126
276849AB2-070 GEN2
Solar/Wind Harmer
1.825
957201AF2-014 GEN
Solar/Wind Helper
3.942
270284AF1-227 GEN1
Solar/Wind Helper
0.948
270428AC2-015 C
Solar/Wind Helper
0.374
253383AE2-342_GEN
Solar/Wind Helper
0.103
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.152
944531AF1-118 GEN
Solar/Wind Harmer
2.052
970707AG2-453 GEN
Solar/Wind Harmer
1.192
970833AG2-524 GEN
Solar/Wind Harmer
3.705
958481AF2-142 GEN
Solar/Wind Harmer
0.623
274862TOP CROP ;2U
Solar/Wind Harmer
4.856
274879MINONK ;1U
Solar/Wind Harmer
6.36
971675AH1-338 GEN
Solar/Wind Harmer
0.728
970781AG2-491 GEN
Solar/Wind Harmer
0.403
276903AD2-071 C
Solar/Wind Harmer
0.399
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.811
945391AF1-204 GEN
Solar/Wind Harmer
13.018
270391AF1-285 GEN3
Solar/Wind Helper
0.285
241847AF2-150_GEN
Solar/Wind Helper
0.265
960851AF2-376 GEN
50/50
2.033
965021AG1-366 GEN
Solar/Wind Harmer
4.557
942221AE2-234 GEN
Solar/Wind Harmer
0.204
958861AF2-177 GEN
Solar/Wind Harmer
15.92
945371AF1-202 GEN
Solar/Wind Harmer
7.521
270505AE1-170 C O1
Solar/Wind Harmer
0.718
270032AE2-172
Solar/Wind Harmer
3.34
970825AG2-519 GEN
Solar/Wind Harmer
1.758
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.231
971997AH1-543 GEN
Solar/Wind Harmer
0.639
276889AE2-281 GEN
Solar/Wind Harmer
1.572
24691005MDL-2G C
Solar/Wind Harmer
3.143
971549AH1-272 GEN
Solar/Wind Harmer
0.722
276158O29GEN2
Solar/Wind Harmer
3.427
276708O09 GEN2
Solar/Wind Harmer
3.218
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.241
270543AE2-219 C
Solar/Wind Harmer
0.365
971993AH1-541 GEN
Solar/Wind Harmer
0.329
276621W2-048 GEN
Solar/Wind Harmer
5.054
942481AE2-261 GEN
Solar/Wind Harmer
1.011
270485AE1-090_GEN
Solar/Wind Helper
0.155
965011AG1-365 GEN
Solar/Wind Harmer
1.139
945111AF1-176 GEN
Solar/Wind Harmer
0.876
945111AF1-176 GEN
Solar/Wind Harmer
4.774
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.668
943021AE2-325 GEN
Solar/Wind Harmer
2.95
964611AG1-324 GEN
Solar/Wind Harmer
0.402
276843GEN-1.7
Solar/Wind Harmer
0.568
958011AF2-095 GEN
Solar/Wind Harmer
0.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.447
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.615
24697905MDL-4G C
Solar/Wind Harmer
2.096
970819AG2-516 GEN
Solar/Wind Harmer
0.478
276646AC1-214 GEN2
Solar/Wind Harmer
1.204
274878BISHOP HL;2U
Solar/Wind Harmer
3.016
274854TWINGROVE;U2
Solar/Wind Harmer
5.82
270191TR4_S_V150
Solar/Wind Harmer
3.471
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.032
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.18
270180AB1-006 GEN1
Solar/Wind Harmer
5.658
24791305MDL-5G
Solar/Wind Harmer
2.096
276741O09 GEN1
Solar/Wind Harmer
3.218
276726Z2-087_GEN
Solar/Wind Harmer
5.982
944221AF1-090 GEN
Solar/Wind Harmer
10.146
966831AG1-554 GEN
Solar/Wind Helper
0.281
961051AF2-396 GEN
Solar/Wind Harmer
0.957
961051AF2-396 GEN
Solar/Wind Harmer
7.653
270599AE1-208 GEN
Solar/Wind Harmer
0.377
972231SS25-0005
Solar/Wind Harmer
0.703
971411AH1-196 GEN
Solar/Wind Harmer
0.607
274855GSG-6 ;RU
Solar/Wind Harmer
3.454
276876AE1-163_GEN2
Solar/Wind Harmer
5.502
24386405FR-21G C
Solar/Wind Harmer
3.021
276782AC1-033 GEN
Solar/Wind Harmer
3.04
276763AC1-053 GEN1
Solar/Wind Harmer
2.764
971029AG2-637 GEN
Solar/Wind Harmer
0.481
270224U2-072_GEN2
Solar/Wind Helper
1.995
942871AE2-306 GEN
Solar/Wind Helper
0.214
945641AF1-229 GEN
Solar/Wind Helper
0.454
270541AE2-072 C
Solar/Wind Helper
0.459
24729205KEY G1
50/50
6.727
270201AC2-176 GEN
Solar/Wind Harmer
4.618
970373AG2-245 GEN
Solar/Wind Harmer
0.924
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.493
274872LEEDK;1U
Solar/Wind Harmer
7.643
276872AE1-163_GEN1
Solar/Wind Harmer
5.502
959081AF2-199 GEN
Solar/Wind Harmer
0.402
274851PROVIDENC;RU
Solar/Wind Harmer
2.244
24386205FR-12G C
Solar/Wind Harmer
3.154
24379505HDWTR1G C
Solar/Wind Harmer
5.718
970885AG2-551 GEN
Solar/Wind Harmer
1.46
963741AG1-226 GEN
Solar/Wind Harmer
1.64
276686W4-005 GEN3
Solar/Wind Harmer
2.126
276764AC1-053 GEN2
Solar/Wind Harmer
2.764
276911AD2-131_GEN
Solar/Wind Harmer
0.168
970031AG2-029 GEN
Solar/Wind Harmer
1.74
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.381
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.278
970833AG2-524 GEN
Solar/Wind Harmer
0.463
962781AG1-127 GEN
Solar/Wind Harmer
0.389
276868AE1-113 GEN
Solar/Wind Harmer
9.54
24697605MDL-3G C
Solar/Wind Harmer
3.143
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.804
24385905FR-11G C
Solar/Wind Harmer
5.939
946321AF1-296 GEN
Solar/Wind Harmer
11.289
274853TWINGROVE;U1
Solar/Wind Harmer
5.82
959611AF2-252 GEN
Solar/Wind Harmer
1.507
960611AF2-352 GEN
Solar/Wind Harmer
1.507
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.365
970193AG2-126 GEN
Solar/Wind Harmer
0.491
958581AF2-149 GEN
Solar/Wind Helper
0.222
965651AG1-433 GEN
Solar/Wind Harmer
8.19
972181SS23-001
Solar/Wind Harmer
0.439
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.299
970289AG2-191 GEN
Solar/Wind Harmer
0.08
274847GR RIDGE ;BU
Solar/Wind Harmer
4.836
946031AF1-268 GEN
Solar/Wind Harmer
0.346
959091AF2-200 GEN
Solar/Wind Harmer
0.804
274849CRESCENT ;1U
Solar/Wind Harmer
1.651
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.704
270227U2-072_GEN3
Solar/Wind Helper
1.995
270228U2-072_GEN4
Solar/Wind Helper
1.995
270231U2-072_GEN5
Solar/Wind Helper
1.995
270349AD2-093_GEN
Solar/Wind Helper
0.454
970521AG2-332 GEN
50/50
10.74
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.192
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.804
274877BISHOP HL;1U
Solar/Wind Harmer
3.016
276848AB2-070 GEN3
Solar/Wind Harmer
1.825
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.166
270471AD2-092_GEN
Solar/Wind Helper
0.454
276820AF1-078_GEN
Solar/Wind Helper
0.159
971347AH1-153 GEN
Solar/Wind Harmer
0.24
961761AG1-017 GEN
Solar/Wind Harmer
0.449
960591AF2-350 GEN
Solar/Wind Harmer
0.428
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
16.272
247536S-71 GEN
Solar/Wind Harmer
3.798
926823AC1-168 GEN
Solar/Wind Harmer
4.874
274857EASY ROAD;U1
Solar/Wind Harmer
3.688
24725505WLD G2 C
Solar/Wind Harmer
3.052
276656WTG2_EQ
Solar/Wind Harmer
0.874
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.587
270462AD2-086
Solar/Wind Helper
1.788
270317AD1-130_GEN
Solar/Wind Helper
1.166
270287AF1-227 GEN3
Solar/Wind Helper
0.35
960861AF2-377 GEN
50/50
2.345
24729305KEY G2
50/50
6.841
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.937
957891AF2-083 GEN
Solar/Wind Harmer
0.723
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.683
274888KELLY CRK;1U
Solar/Wind Harmer
5.846
276893AG1-478 C
Solar/Wind Harmer
0.338
270005AE1-210 C O1
Solar/Wind Harmer
6.493
276602WESTBROOK C
Solar/Wind Harmer
1.703
274863CRW1-WTG
Solar/Wind Harmer
4.717
274864CRW2-WTG
Solar/Wind Harmer
4.717
276603SUBLETTE C
Solar/Wind Harmer
0.798
24387305FR-4G C
Solar/Wind Harmer
4.532
24386605FR-22G C
Solar/Wind Harmer
3.021
24387005FR-3G C
Solar/Wind Harmer
2.991
274880W4-005 GEN4
Solar/Wind Harmer
2.126
246936BC-WTG1
Solar/Wind Helper
17.073
246937BC-WTG2
Solar/Wind Helper
17.073
960841AF2-375 GEN
Solar/Wind Helper
0.563
965091AG1-374 GEN
Solar/Wind Harmer
1.13
965931AG1-462 GEN
Solar/Wind Harmer
0.961
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.995
270499AE1-146 GEN
Solar/Wind Helper
0.544
247620Y3-023
50/50
0.46
959331AF2-224 GEN
Solar/Wind Harmer
1.139
965041AG1-368 GEN
Solar/Wind Harmer
0.69
270031AE2-169
Solar/Wind Harmer
0.377
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.661
274861TOP CROP ;1U
Solar/Wind Harmer
4.856
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.349
971067AG2-660 GEN
Solar/Wind Harmer
1.608
24699105WLD G1 C
Solar/Wind Harmer
3.052
276655WTG1_EQ
Solar/Wind Harmer
6.603
963841AG1-237 GEN
Solar/Wind Harmer
11.714
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.285
247522W1-056 GEN
Solar/Wind Helper
1.919
270286AF1-227 GEN2
Solar/Wind Helper
0.35
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.296
24639705ELKHART HY
50/50
0.148
963791AG1-232 GEN
Solar/Wind Harmer
0.988
247521TR3_G114
Solar/Wind Harmer
4.555
24695305TIMB G C
Solar/Wind Harmer
3.924
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.418
276694AA1-018 GEN2
Solar/Wind Harmer
4.411
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.096
971343AH1-151 GEN
Solar/Wind Harmer
0.804
970169AG2-114 GEN
Solar/Wind Harmer
0.397
959341AF2-225 GEN
Solar/Wind Harmer
0.575
971087AG2-675 GEN
Solar/Wind Harmer
2.412
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729405KEY G3
50/50
6.841
24729505KEY G4
50/50
6.727
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.436
970941AG2-585 GEN
Solar/Wind Harmer
0.236
276897AD1-100 C
Solar/Wind Harmer
56.232
971605AH1-302 GEN
Solar/Wind Harmer
6.283
970825AG2-519 GEN
Solar/Wind Harmer
0.274
276805AD2-038 GEN
Solar/Wind Harmer
4.799
970569AG2-363 GEN
Solar/Wind Harmer
1.195
276157O29GEN1
Solar/Wind Harmer
3.427
276645AC1-214 GEN1
Solar/Wind Harmer
1.204
939741AE1-205 GEN
Solar/Wind Harmer
0.767
942111AE2-223 GEN
Solar/Wind Harmer
8.972
970241AG2-163 GEN
Solar/Wind Harmer
0.911
276174W4-005 GEN2
Solar/Wind Harmer
2.126
276668AB2-070 GEN1
Solar/Wind Harmer
1.825
276838X2-022 GEN2
Solar/Wind Harmer
0.188
246938BC-WTG3
Solar/Wind Helper
17.366
970073AG2-061 GEN
Solar/Wind Harmer
1.641
274850MENDOTA H;RU
Solar/Wind Harmer
2.401
276863AD2-134 GEN
Solar/Wind Harmer
1.67
276861AD2-134 GEN
Solar/Wind Harmer
1.67
970571AG2-364 GEN
Solar/Wind Harmer
0.796
274856ECOGROVE ;U1
Solar/Wind Harmer
3.104
971681AH1-341 GEN
Solar/Wind Harmer
0.593
938861AE1-114 GEN
Solar/Wind Harmer
9.255
274858EASY ROAD;U2
Solar/Wind Harmer
3.688
270240V3-007_GEN2
Solar/Wind Harmer
4.477
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.353
990792J1392
External Queue
0.3027859032154083
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.204
NYPJM->LTFIMP_NY
CLTF
1.303
MECLTFEXP_MEC->PJM
CLTF
9.641
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.255
LGEELTFEXP_LGEE->PJM
CLTF
1.795
LAGNLTFEXP_LAGN->PJM
CLTF
5.817
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.873
TVALTFEXP_TVA->PJM
CLTF
2.36
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.443
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.032
WECLTFEXP_WEC->PJM
CLTF
2.627
SIGELTFEXP_SIGE->PJM
CLTF
0.199

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.4 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2056.53
MW Contribution:
0.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.018
270143AC1-141 CT2_
50/50
2.018
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
270102X2-052 ST
50/50
1.276
970901AG2-562 GEN
50/50
4.835
24344005CKG1
50/50
5.553
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
960851AF2-376 GEN
50/50
2.087
24307105BERRINSP G
50/50
0.017
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
270100X2-052 CT1
50/50
1.179
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
24344105CKG2
50/50
6.328
270101X2-052 CT2
50/50
1.179
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
24643105BUCHANAN
50/50
0.01
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.787
24642205MAYFLWER
50/50
0.618
962601AG1-109 GEN
50/50
2.385
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
944961AF1-161 GEN
50/50
2.385
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
990792J1392
External Queue
0.30737584829330444
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.41 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2022.06
MW Contribution:
0.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
247620Y3-023
50/50
0.466
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
270541AE2-072 C
Solar/Wind Helper
0.432
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
990792J1392
External Queue
0.30737584829330444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.97 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2014.34
MW Contribution:
0.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270246TR4_N_V150
Solar/Wind Harmer
1.123
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.295
965021AG1-366 GEN
Solar/Wind Harmer
4.503
942221AE2-234 GEN
Solar/Wind Harmer
0.2
958861AF2-177 GEN
Solar/Wind Harmer
15.573
945371AF1-202 GEN
Solar/Wind Harmer
7.349
270505AE1-170 C O1
Solar/Wind Harmer
0.702
270032AE2-172
Solar/Wind Harmer
3.253
970825AG2-519 GEN
Solar/Wind Harmer
1.712
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.198
971997AH1-543 GEN
Solar/Wind Harmer
0.622
276889AE2-281 GEN
Solar/Wind Harmer
1.53
24691005MDL-2G C
Solar/Wind Harmer
3.058
971549AH1-272 GEN
Solar/Wind Harmer
0.702
276158O29GEN2
Solar/Wind Harmer
3.332
276708O09 GEN2
Solar/Wind Harmer
3.129
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.205
270543AE2-219 C
Solar/Wind Harmer
0.354
971993AH1-541 GEN
Solar/Wind Harmer
0.319
276621W2-048 GEN
Solar/Wind Harmer
4.9
942481AE2-261 GEN
Solar/Wind Harmer
0.979
270485AE1-090_GEN
Solar/Wind Helper
0.162
270191TR4_S_V150
Solar/Wind Harmer
3.383
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.91
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.095
270180AB1-006 GEN1
Solar/Wind Harmer
5.504
24791305MDL-5G
Solar/Wind Harmer
2.038
970031AG2-029 GEN
Solar/Wind Harmer
1.71
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.032
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.144
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
276868AE1-113 GEN
Solar/Wind Harmer
9.286
24697605MDL-3G C
Solar/Wind Harmer
3.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.782
24385905FR-11G C
Solar/Wind Harmer
5.772
946321AF1-296 GEN
Solar/Wind Harmer
10.97
274853TWINGROVE;U1
Solar/Wind Harmer
5.654
959611AF2-252 GEN
Solar/Wind Harmer
1.464
960611AF2-352 GEN
Solar/Wind Harmer
1.464
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.354
970193AG2-126 GEN
Solar/Wind Harmer
0.475
958581AF2-149 GEN
Solar/Wind Helper
0.216
970521AG2-332 GEN
50/50
10.514
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
12.855
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.782
274877BISHOP HL;1U
Solar/Wind Harmer
2.932
276848AB2-070 GEN3
Solar/Wind Harmer
1.771
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.216
270471AD2-092_GEN
Solar/Wind Helper
0.517
276820AF1-078_GEN
Solar/Wind Helper
0.166
970583AG2-370 GEN
50/50
2.702
965051AG1-369 GEN
Solar/Wind Harmer
0.285
970349AG2-230 GEN
Solar/Wind Harmer
0.704
971347AH1-153 GEN
Solar/Wind Harmer
0.235
961761AG1-017 GEN
Solar/Wind Harmer
0.438
960591AF2-350 GEN
Solar/Wind Harmer
0.417
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
15.839
247536S-71 GEN
Solar/Wind Harmer
3.697
926823AC1-168 GEN
Solar/Wind Harmer
4.742
274857EASY ROAD;U1
Solar/Wind Harmer
3.587
24725505WLD G2 C
Solar/Wind Harmer
2.968
276656WTG2_EQ
Solar/Wind Harmer
0.85
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.539
270462AD2-086
Solar/Wind Helper
1.865
270317AD1-130_GEN
Solar/Wind Helper
1.216
270287AF1-227 GEN3
Solar/Wind Helper
0.382
960861AF2-377 GEN
50/50
2.286
24729305KEY G2
50/50
6.704
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.92
957891AF2-083 GEN
Solar/Wind Harmer
0.707
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.667
274888KELLY CRK;1U
Solar/Wind Harmer
5.697
276893AG1-478 C
Solar/Wind Harmer
0.33
270005AE1-210 C O1
Solar/Wind Harmer
6.326
276602WESTBROOK C
Solar/Wind Harmer
1.658
274863CRW1-WTG
Solar/Wind Harmer
4.59
274864CRW2-WTG
Solar/Wind Harmer
4.59
276603SUBLETTE C
Solar/Wind Harmer
0.776
24387305FR-4G C
Solar/Wind Harmer
4.404
24386605FR-22G C
Solar/Wind Harmer
2.936
24387005FR-3G C
Solar/Wind Harmer
2.906
274880W4-005 GEN4
Solar/Wind Harmer
2.063
246936BC-WTG1
Solar/Wind Helper
17.184
246937BC-WTG2
Solar/Wind Helper
17.184
960841AF2-375 GEN
Solar/Wind Helper
0.576
943021AE2-325 GEN
Solar/Wind Harmer
2.881
964611AG1-324 GEN
Solar/Wind Harmer
0.393
276843GEN-1.7
Solar/Wind Harmer
0.553
958011AF2-095 GEN
Solar/Wind Harmer
0.601
276691AA1-018 GEN1
Solar/Wind Harmer
0.435
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
24697905MDL-4G C
Solar/Wind Harmer
2.038
970819AG2-516 GEN
Solar/Wind Harmer
0.465
276646AC1-214 GEN2
Solar/Wind Harmer
1.17
274878BISHOP HL;2U
Solar/Wind Harmer
2.932
965931AG1-462 GEN
Solar/Wind Harmer
0.934
274854TWINGROVE;U2
Solar/Wind Harmer
5.654
965091AG1-374 GEN
Solar/Wind Harmer
1.098
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
2.097
270499AE1-146 GEN
Solar/Wind Helper
0.556
24729205KEY G1
50/50
6.593
270201AC2-176 GEN
Solar/Wind Harmer
4.506
970373AG2-245 GEN
Solar/Wind Harmer
0.901
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.326
274872LEEDK;1U
Solar/Wind Harmer
7.44
276872AE1-163_GEN1
Solar/Wind Harmer
5.354
959081AF2-199 GEN
Solar/Wind Harmer
0.391
274851PROVIDENC;RU
Solar/Wind Harmer
2.181
24386205FR-12G C
Solar/Wind Harmer
3.065
24379505HDWTR1G C
Solar/Wind Harmer
5.555
970885AG2-551 GEN
Solar/Wind Harmer
1.417
963741AG1-226 GEN
Solar/Wind Harmer
1.592
276686W4-005 GEN3
Solar/Wind Harmer
2.063
276764AC1-053 GEN2
Solar/Wind Harmer
2.681
276911AD2-131_GEN
Solar/Wind Harmer
0.162
247620Y3-023
50/50
0.45
959331AF2-224 GEN
Solar/Wind Harmer
1.126
965041AG1-368 GEN
Solar/Wind Harmer
0.675
270031AE2-169
Solar/Wind Harmer
0.368
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.489
274861TOP CROP ;1U
Solar/Wind Harmer
4.729
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.176
971067AG2-660 GEN
Solar/Wind Harmer
1.565
24699105WLD G1 C
Solar/Wind Harmer
2.968
276655WTG1_EQ
Solar/Wind Harmer
6.417
963841AG1-237 GEN
Solar/Wind Harmer
11.375
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.3
270286AF1-227 GEN2
Solar/Wind Helper
0.382
247522W1-056 GEN
Solar/Wind Helper
1.958
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.299
274871GR RIDGE ;2U
Solar/Wind Harmer
5.196
943121AE2-341 GEN
Solar/Wind Harmer
0.611
957471AF2-041 GEN
Solar/Wind Harmer
1.174
274848CAMPGROVE;RU
Solar/Wind Harmer
4.383
276785W4-005 GEN1
Solar/Wind Harmer
2.063
276849AB2-070 GEN2
Solar/Wind Harmer
1.771
957201AF2-014 GEN
Solar/Wind Helper
3.968
270284AF1-227 GEN1
Solar/Wind Helper
1.035
270428AC2-015 C
Solar/Wind Helper
0.376
253383AE2-342_GEN
Solar/Wind Helper
0.105
944531AF1-118 GEN
Solar/Wind Harmer
2.012
270247TR4_N_V136
Solar/Wind Harmer
1.123
970707AG2-453 GEN
Solar/Wind Harmer
1.161
970833AG2-524 GEN
Solar/Wind Harmer
3.609
958481AF2-142 GEN
Solar/Wind Harmer
0.607
274862TOP CROP ;2U
Solar/Wind Harmer
4.729
274879MINONK ;1U
Solar/Wind Harmer
6.19
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
276903AD2-071 C
Solar/Wind Harmer
0.388
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.786
945391AF1-204 GEN
Solar/Wind Harmer
12.593
270391AF1-285 GEN3
Solar/Wind Helper
0.3
241847AF2-150_GEN
Solar/Wind Helper
0.265
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.971
247521TR3_G114
Solar/Wind Harmer
4.44
24695305TIMB G C
Solar/Wind Harmer
3.811
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.053
943591AF1-030 GEN
Solar/Wind Harmer
0.407
276694AA1-018 GEN2
Solar/Wind Harmer
4.296
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.038
971343AH1-151 GEN
Solar/Wind Harmer
0.782
970169AG2-114 GEN
Solar/Wind Harmer
0.386
959341AF2-225 GEN
Solar/Wind Harmer
0.559
971087AG2-675 GEN
Solar/Wind Harmer
2.343
270445AC2-157 GEN2
Solar/Wind Harmer
0
24729405KEY G3
50/50
6.704
24729505KEY G4
50/50
6.593
270043AE2-236 GEN
Solar/Wind Harmer
0.363
971771AH1-392 GEN
Solar/Wind Harmer
0.426
970941AG2-585 GEN
Solar/Wind Harmer
0.23
276897AD1-100 C
Solar/Wind Harmer
54.783
971605AH1-302 GEN
Solar/Wind Harmer
6.118
970825AG2-519 GEN
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
4.671
970569AG2-363 GEN
Solar/Wind Harmer
1.162
276157O29GEN1
Solar/Wind Harmer
3.332
276645AC1-214 GEN1
Solar/Wind Harmer
1.17
939741AE1-205 GEN
Solar/Wind Harmer
0.745
942111AE2-223 GEN
Solar/Wind Harmer
8.72
970241AG2-163 GEN
Solar/Wind Harmer
0.884
276174W4-005 GEN2
Solar/Wind Harmer
2.063
276668AB2-070 GEN1
Solar/Wind Harmer
1.771
276838X2-022 GEN2
Solar/Wind Harmer
0.183
246938BC-WTG3
Solar/Wind Helper
17.48
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.856
945111AF1-176 GEN
Solar/Wind Harmer
4.667
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.651
970073AG2-061 GEN
Solar/Wind Harmer
1.597
274850MENDOTA H;RU
Solar/Wind Harmer
2.337
276863AD2-134 GEN
Solar/Wind Harmer
1.625
276861AD2-134 GEN
Solar/Wind Harmer
1.625
970571AG2-364 GEN
Solar/Wind Harmer
0.775
274856ECOGROVE ;U1
Solar/Wind Harmer
3.02
971681AH1-341 GEN
Solar/Wind Harmer
0.577
938861AE1-114 GEN
Solar/Wind Harmer
9.003
274858EASY ROAD;U2
Solar/Wind Harmer
3.587
270240V3-007_GEN2
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.369
961051AF2-396 GEN
Solar/Wind Harmer
0.935
961051AF2-396 GEN
Solar/Wind Harmer
7.477
270599AE1-208 GEN
Solar/Wind Harmer
0.368
972231SS25-0005
Solar/Wind Harmer
0.685
971411AH1-196 GEN
Solar/Wind Harmer
0.591
274855GSG-6 ;RU
Solar/Wind Harmer
3.361
276876AE1-163_GEN2
Solar/Wind Harmer
5.354
24386405FR-21G C
Solar/Wind Harmer
2.936
276782AC1-033 GEN
Solar/Wind Harmer
2.956
276763AC1-053 GEN1
Solar/Wind Harmer
2.681
971029AG2-637 GEN
Solar/Wind Harmer
0.465
270224U2-072_GEN2
Solar/Wind Helper
2.097
942871AE2-306 GEN
Solar/Wind Helper
0.225
945641AF1-229 GEN
Solar/Wind Helper
0.46
270541AE2-072 C
Solar/Wind Helper
0.478
276741O09 GEN1
Solar/Wind Harmer
3.129
276726Z2-087_GEN
Solar/Wind Harmer
5.813
944221AF1-090 GEN
Solar/Wind Harmer
9.816
966831AG1-554 GEN
Solar/Wind Helper
0.286
965651AG1-433 GEN
Solar/Wind Harmer
8.016
972181SS23-001
Solar/Wind Harmer
0.428
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.266
970289AG2-191 GEN
Solar/Wind Harmer
0.078
274847GR RIDGE ;BU
Solar/Wind Harmer
4.711
946031AF1-268 GEN
Solar/Wind Harmer
0.337
959091AF2-200 GEN
Solar/Wind Harmer
0.782
274849CRESCENT ;1U
Solar/Wind Harmer
1.605
957381AF2-032 GEN
Solar/Wind Harmer
0.066
276916AD2-100_GEN
Solar/Wind Harmer
0.681
270227U2-072_GEN3
Solar/Wind Helper
2.097
270228U2-072_GEN4
Solar/Wind Helper
2.097
270231U2-072_GEN5
Solar/Wind Helper
2.097
270349AD2-093_GEN
Solar/Wind Helper
0.517
990792J1392
External Queue
0.3014104962348938
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.512
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
SIGELTFEXP_SIGE->PJM
CLTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.67
NYPJM->LTFIMP_NY
CLTF
1.235
TVALTFEXP_TVA->PJM
CLTF
2.193
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.304
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.406
WECLTFEXP_WEC->PJM
CLTF
2.556
LAGNLTFEXP_LAGN->PJM
CLTF
5.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.955
LGEELTFEXP_LGEE->PJM
CLTF
1.68
MECLTFEXP_MEC->PJM
CLTF
9.337
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.18 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5552.88
MW Contribution:
1.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
19.245
970349AG2-230 GEN
Solar/Wind Harmer
1.931
971347AH1-153 GEN
Solar/Wind Harmer
0.644
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.179
939401AE1-172 GEN
Solar/Wind Harmer
45.023
926823AC1-168 GEN
Solar/Wind Harmer
13.325
958381AF2-132 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
10.112
959141AF2-205 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
2.355
276615X2-022 GEN
Solar/Wind Harmer
4.125
276843GEN-1.7
Solar/Wind Harmer
1.563
958011AF2-095 GEN
Solar/Wind Harmer
1.698
276691AA1-018 GEN1
Solar/Wind Harmer
1.224
958491AF2-143 GEN
Solar/Wind Harmer
1.681
970819AG2-516 GEN
Solar/Wind Harmer
1.316
276646AC1-214 GEN2
Solar/Wind Harmer
3.266
274878BISHOP HL;2U
Solar/Wind Harmer
8.175
945421AF1-207 GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
2.596
274854TWINGROVE;U2
Solar/Wind Harmer
15.584
965091AG1-374 GEN
Solar/Wind Harmer
3.027
24697905MDL-4G C
Solar/Wind Harmer
5.234
943021AE2-325 GEN
Solar/Wind Harmer
6.288
274776LINCOLN ;7U
50/50
19.245
274872LEEDK;1U
Solar/Wind Harmer
21.244
970373AG2-245 GEN
Solar/Wind Harmer
2.349
959081AF2-199 GEN
Solar/Wind Harmer
1.11
276872AE1-163_GEN1
Solar/Wind Harmer
14.997
964401AG1-302 GEN
Solar/Wind Harmer
0
274851PROVIDENC;RU
Solar/Wind Harmer
6.088
24386205FR-12G C
Solar/Wind Harmer
7.802
276686W4-005 GEN3
Solar/Wind Harmer
5.559
276764AC1-053 GEN2
Solar/Wind Harmer
7.21
963741AG1-226 GEN
Solar/Wind Harmer
3.953
276911AD2-131_GEN
Solar/Wind Harmer
0.429
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
13.286
971067AG2-660 GEN
Solar/Wind Harmer
4.441
971917AH1-482 GEN
Solar/Wind Harmer
16.838
276655WTG1_EQ
Solar/Wind Harmer
17.784
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
15.858
963841AG1-237 GEN
Solar/Wind Harmer
28.603
274887GEN-1.85
Solar/Wind Harmer
14.528
970833AG2-524 GEN
Solar/Wind Harmer
1.293
962781AG1-127 GEN
Solar/Wind Harmer
1.082
276868AE1-113 GEN
Solar/Wind Harmer
26.15
971171AH1-044 GEN
Solar/Wind Harmer
2.221
946321AF1-296 GEN
Solar/Wind Harmer
30.561
274853TWINGROVE;U1
Solar/Wind Harmer
15.584
959611AF2-252 GEN
Solar/Wind Harmer
4.036
960611AF2-352 GEN
Solar/Wind Harmer
4.036
24697605MDL-3G C
Solar/Wind Harmer
7.851
270181AB1-006 GEN2
Solar/Wind Harmer
1.57
24385905FR-11G C
Solar/Wind Harmer
14.693
970193AG2-126 GEN
Solar/Wind Harmer
1.123
270063AE2-323 C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
1.763
274871GR RIDGE ;2U
Solar/Wind Harmer
14.901
957471AF2-041 GEN
Solar/Wind Harmer
3.331
274848CAMPGROVE;RU
Solar/Wind Harmer
12.201
270449AD2-020 GEN
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
5.559
276849AB2-070 GEN2
Solar/Wind Harmer
4.769
276806AD2-047 C O1
Solar/Wind Harmer
36.31
971341AH1-150 GEN
Solar/Wind Harmer
2.221
958391AF2-133 GEN
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
8.175
276848AB2-070 GEN3
Solar/Wind Harmer
4.769
270444AC2-157 GEN1
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
3.393
970833AG2-524 GEN
Solar/Wind Harmer
10.343
958481AF2-142 GEN
Solar/Wind Harmer
1.705
274862TOP CROP ;2U
Solar/Wind Harmer
13.286
971675AH1-338 GEN
Solar/Wind Harmer
2.017
274879MINONK ;1U
Solar/Wind Harmer
17.434
970781AG2-491 GEN
Solar/Wind Harmer
1.006
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.085
943591AF1-030 GEN
Solar/Wind Harmer
1.175
965681AG1-436 GEN
Solar/Wind Harmer
1.466
276694AA1-018 GEN2
Solar/Wind Harmer
12.077
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.221
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
1.086
959341AF2-225 GEN
Solar/Wind Harmer
1.549
971087AG2-675 GEN
Solar/Wind Harmer
6.516
24755605MDL-5G
Solar/Wind Harmer
5.234
270445AC2-157 GEN2
Solar/Wind Harmer
0
274773LINCOLN ;4U
50/50
19.245
972259AH1-714 GEN
50/50
40.401
962691AG1-118 GEN
Solar/Wind Harmer
3.425
971997AH1-543 GEN
Solar/Wind Harmer
1.764
276889AE2-281 GEN
Solar/Wind Harmer
4.285
276158O29GEN2
Solar/Wind Harmer
9.347
276708O09 GEN2
Solar/Wind Harmer
8.778
957841AF2-078 GEN
Solar/Wind Harmer
0
270505AE1-170 C O1
Solar/Wind Harmer
1.526
24691005MDL-2G C
Solar/Wind Harmer
7.851
971993AH1-541 GEN
Solar/Wind Harmer
0.861
276621W2-048 GEN
Solar/Wind Harmer
13.134
971549AH1-272 GEN
Solar/Wind Harmer
1.613
942481AE2-261 GEN
Solar/Wind Harmer
2.597
274772LINCOLN ;3U
50/50
19.245
274774LINCOLN ;5U
50/50
19.245
274660LASCO STA;1U
50/50
15.532
276897AD1-100 C
Solar/Wind Harmer
156.947
970941AG2-585 GEN
Solar/Wind Harmer
0.648
276805AD2-038 GEN
Solar/Wind Harmer
13.114
970569AG2-363 GEN
Solar/Wind Harmer
3.25
276157O29GEN1
Solar/Wind Harmer
9.347
971605AH1-302 GEN
Solar/Wind Harmer
15.823
276645AC1-214 GEN1
Solar/Wind Harmer
3.266
971771AH1-392 GEN
Solar/Wind Harmer
0.941
939741AE1-205 GEN
Solar/Wind Harmer
2.066
942111AE2-223 GEN
Solar/Wind Harmer
24.167
276174W4-005 GEN2
Solar/Wind Harmer
5.559
276668AB2-070 GEN1
Solar/Wind Harmer
4.769
276838X2-022 GEN2
Solar/Wind Harmer
0.49
970241AG2-163 GEN
Solar/Wind Harmer
2.196
274770LINCOLN ;1U
50/50
19.245
274771LINCOLN ;2U
50/50
19.245
970073AG2-061 GEN
Solar/Wind Harmer
4.483
274850MENDOTA H;RU
Solar/Wind Harmer
6.65
276863AD2-134 GEN
Solar/Wind Harmer
4.625
276861AD2-134 GEN
Solar/Wind Harmer
4.625
274856ECOGROVE ;U1
Solar/Wind Harmer
8.538
971681AH1-341 GEN
Solar/Wind Harmer
1.629
938861AE1-114 GEN
Solar/Wind Harmer
25.406
970571AG2-364 GEN
Solar/Wind Harmer
2.167
274858EASY ROAD;U2
Solar/Wind Harmer
10.112
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
1.724
945111AF1-176 GEN
Solar/Wind Harmer
9.399
945391AF1-204 GEN
Solar/Wind Harmer
29.773
274777LINCOLN ;8U
50/50
19.245
972231SS25-0005
Solar/Wind Harmer
1.856
274855GSG-6 ;RU
Solar/Wind Harmer
9.565
971411AH1-196 GEN
Solar/Wind Harmer
1.679
276876AE1-163_GEN2
Solar/Wind Harmer
14.997
276782AC1-033 GEN
Solar/Wind Harmer
8.241
961051AF2-396 GEN
Solar/Wind Harmer
1.98
961051AF2-396 GEN
Solar/Wind Harmer
15.837
24386405FR-21G C
Solar/Wind Harmer
7.474
276763AC1-053 GEN1
Solar/Wind Harmer
7.21
274888KELLY CRK;1U
Solar/Wind Harmer
16.092
276893AG1-478 C
Solar/Wind Harmer
0.934
276602WESTBROOK C
Solar/Wind Harmer
4.717
274863CRW1-WTG
Solar/Wind Harmer
12.978
274864CRW2-WTG
Solar/Wind Harmer
12.978
276603SUBLETTE C
Solar/Wind Harmer
2.187
957891AF2-083 GEN
Solar/Wind Harmer
1.506
24387305FR-4G C
Solar/Wind Harmer
11.211
24386605FR-22G C
Solar/Wind Harmer
7.474
24387005FR-3G C
Solar/Wind Harmer
7.399
274880W4-005 GEN4
Solar/Wind Harmer
5.559
24344105CKG2
50/50
20.456
274661LASCO STA;2U
50/50
15.572
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
12.903
276882AE2-255 GEN
Solar/Wind Harmer
8.717
270526AF1-158 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
8.778
276726Z2-087_GEN
Solar/Wind Harmer
16.111
270180AB1-006 GEN1
Solar/Wind Harmer
14.131
24791305MDL-5G
Solar/Wind Harmer
5.234
944221AF1-090 GEN
Solar/Wind Harmer
25.717
972207SS24-0001
Solar/Wind Harmer
3.749
274847GR RIDGE ;BU
Solar/Wind Harmer
13.509
972181SS23-001
Solar/Wind Harmer
1.16
959091AF2-200 GEN
Solar/Wind Harmer
2.221
270055AF2-134 C O1
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
4.479
957381AF2-032 GEN
Solar/Wind Harmer
0.174
276916AD2-100_GEN
Solar/Wind Harmer
1.803
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.121
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.48
LAGNLTFEXP_LAGN->PJM
CLTF
10.935
AH1-155LTFEXP_AH1-155->PJM
LTF
0.619
NYPJM->LTFIMP_NY
CLTF
3.181
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.742
SIGELTFEXP_SIGE->PJM
CLTF
0.318
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.429
WECLTFEXP_WEC->PJM
CLTF
7.219
MECLTFEXP_MEC->PJM
CLTF
25.034
AG2-052LTFEXP_AG2-052->PJM
LTF
0.413
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.453
LGEELTFEXP_LGEE->PJM
CLTF
1.229
TVALTFEXP_TVA->PJM
CLTF
3.54
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
80.046

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.35 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3385.78
MW Contribution:
0.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270393AB1-087 CT1
50/50
2.588
270406AB1-088 CT1
50/50
2.588
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.742
971347AH1-153 GEN
Solar/Wind Harmer
0.247
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.48
939401AE1-172 GEN
Solar/Wind Harmer
18.931
276656WTG2_EQ
Solar/Wind Harmer
1.066
926823AC1-168 GEN
Solar/Wind Harmer
5.594
276615X2-022 GEN
Solar/Wind Harmer
2.045
274857EASY ROAD;U1
Solar/Wind Harmer
4.117
252507AC2-088 GEN
Solar/Wind Helper
0.377
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.434
276843GEN-1.7
Solar/Wind Harmer
0.637
958011AF2-095 GEN
Solar/Wind Harmer
0.692
276691AA1-018 GEN1
Solar/Wind Harmer
0.504
274854TWINGROVE;U2
Solar/Wind Harmer
7.169
965091AG1-374 GEN
Solar/Wind Harmer
1.392
958491AF2-143 GEN
Solar/Wind Harmer
0.696
943021AE2-325 GEN
Solar/Wind Harmer
2.802
276646AC1-214 GEN2
Solar/Wind Harmer
1.384
970819AG2-516 GEN
Solar/Wind Harmer
0.534
274878BISHOP HL;2U
Solar/Wind Harmer
3.456
965931AG1-462 GEN
Solar/Wind Harmer
1.068
339206AE1-143 GEN
Solar/Wind Helper
0.35
241972AD1-140 GEN
Solar/Wind Helper
0.541
970091AG2-072 GEN
50/50
216.879
270394AB1-087 ST1
50/50
2.588
970783AG2-492 GEN
50/50
2.641
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.404
963841AG1-237 GEN
Solar/Wind Harmer
19.192
971917AH1-482 GEN
Solar/Wind Harmer
9.558
960681AF2-359 GEN
Solar/Wind Harmer
0
24344205RKG1
50/50
11.484
24697605MDL-3G C
Solar/Wind Harmer
5.151
270181AB1-006 GEN2
Solar/Wind Harmer
1.03
24385905FR-11G C
Solar/Wind Harmer
9.864
970193AG2-126 GEN
Solar/Wind Harmer
0.751
274887GEN-1.85
Solar/Wind Harmer
5.918
970833AG2-524 GEN
Solar/Wind Harmer
0.523
274853TWINGROVE;U1
Solar/Wind Harmer
7.169
959611AF2-252 GEN
Solar/Wind Harmer
1.857
960611AF2-352 GEN
Solar/Wind Harmer
1.857
276868AE1-113 GEN
Solar/Wind Harmer
10.815
962781AG1-127 GEN
Solar/Wind Harmer
0.436
971171AH1-044 GEN
Solar/Wind Harmer
0.9
946321AF1-296 GEN
Solar/Wind Harmer
12.566
270063AE2-323 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
0.903
339216AC1-074 GEN
Solar/Wind Helper
0.395
253415AE1-040 GEN
Solar/Wind Helper
0.15
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.792
276848AB2-070 GEN3
Solar/Wind Harmer
2.337
971341AH1-150 GEN
Solar/Wind Harmer
0.9
274877BISHOP HL;1U
Solar/Wind Harmer
3.456
253316AC1-085 GEN3
Solar/Wind Helper
0.596
253433AC1-085 GEN1
Solar/Wind Helper
0.378
253349AC2-067 GEN
Solar/Wind Helper
0.161
253343AC1-166 GEN
Solar/Wind Helper
0.134
970543AG2-345 GEN
50/50
4.595
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.434
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.151
971997AH1-543 GEN
Solar/Wind Harmer
0.729
962691AG1-118 GEN
Solar/Wind Harmer
1.379
276889AE2-281 GEN
Solar/Wind Harmer
1.788
971993AH1-541 GEN
Solar/Wind Harmer
0.422
270505AE1-170 C O1
Solar/Wind Harmer
0.677
276621W2-048 GEN
Solar/Wind Harmer
6.511
942481AE2-261 GEN
Solar/Wind Harmer
1.324
276158O29GEN2
Solar/Wind Harmer
3.853
276708O09 GEN2
Solar/Wind Harmer
3.619
971549AH1-272 GEN
Solar/Wind Harmer
0.737
270367AC2-061_GEN
Solar/Wind Helper
0.469
962581AG1-107 GEN
Solar/Wind Helper
0.576
270100X2-052 CT1
50/50
1.285
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.856
970571AG2-364 GEN
Solar/Wind Harmer
0.909
274850MENDOTA H;RU
Solar/Wind Harmer
2.689
276863AD2-134 GEN
Solar/Wind Harmer
1.87
276861AD2-134 GEN
Solar/Wind Harmer
1.87
945111AF1-176 GEN
Solar/Wind Harmer
0.794
945111AF1-176 GEN
Solar/Wind Harmer
4.329
274856ECOGROVE ;U1
Solar/Wind Harmer
3.466
971681AH1-341 GEN
Solar/Wind Harmer
0.663
938861AE1-114 GEN
Solar/Wind Harmer
10.341
274858EASY ROAD;U2
Solar/Wind Harmer
4.117
24387305FR-4G C
Solar/Wind Harmer
7.526
24386605FR-22G C
Solar/Wind Harmer
5.018
24387005FR-3G C
Solar/Wind Harmer
4.967
274888KELLY CRK;1U
Solar/Wind Harmer
6.555
276893AG1-478 C
Solar/Wind Harmer
0.38
274863CRW1-WTG
Solar/Wind Harmer
5.543
274864CRW2-WTG
Solar/Wind Harmer
5.543
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276602WESTBROOK C
Solar/Wind Harmer
1.907
957891AF2-083 GEN
Solar/Wind Harmer
0.676
276603SUBLETTE C
Solar/Wind Harmer
0.892
270071AF1-092 GEN
Solar/Wind Harmer
0.563
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.583
253398AE2-221_GEN2
Solar/Wind Helper
0.583
339236AF1-050_GEN
Solar/Wind Helper
0.191
274861TOP CROP ;1U
Solar/Wind Harmer
5.476
276655WTG1_EQ
Solar/Wind Harmer
8.054
971067AG2-660 GEN
Solar/Wind Harmer
1.799
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.099
270186AC1-089 GEN
Solar/Wind Helper
0.607
339231AF1-038_GEN
Solar/Wind Helper
0.187
270222AC2-111 GEN
Solar/Wind Helper
0.234
339250AF1-203 GEN
Solar/Wind Helper
0.056
942601AE2-276 GEN
50/50
8.233
971605AH1-302 GEN
Solar/Wind Harmer
9.589
970241AG2-163 GEN
Solar/Wind Harmer
1.473
276897AD1-100 C
Solar/Wind Harmer
63.744
970941AG2-585 GEN
Solar/Wind Harmer
0.264
939741AE1-205 GEN
Solar/Wind Harmer
0.935
942111AE2-223 GEN
Solar/Wind Harmer
10.945
971771AH1-392 GEN
Solar/Wind Harmer
0.419
276805AD2-038 GEN
Solar/Wind Harmer
5.43
276174W4-005 GEN2
Solar/Wind Harmer
2.725
276668AB2-070 GEN1
Solar/Wind Harmer
2.337
970569AG2-363 GEN
Solar/Wind Harmer
1.363
276838X2-022 GEN2
Solar/Wind Harmer
0.243
276645AC1-214 GEN1
Solar/Wind Harmer
1.384
276157O29GEN1
Solar/Wind Harmer
3.853
270043AE2-236 GEN
Solar/Wind Harmer
0.177
961491AF2-440 GEN
Solar/Wind Helper
0.192
965681AG1-436 GEN
Solar/Wind Harmer
0.631
970169AG2-114 GEN
Solar/Wind Harmer
0.471
943591AF1-030 GEN
Solar/Wind Harmer
0.469
24344305RKG2
50/50
11.11
24344305RKG2
50/50
11.015
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.462
972181SS23-001
Solar/Wind Harmer
0.486
274847GR RIDGE ;BU
Solar/Wind Harmer
5.462
959091AF2-200 GEN
Solar/Wind Harmer
0.9
274849CRESCENT ;1U
Solar/Wind Harmer
1.898
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.928
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.183
339241AF1-083 GEN
Solar/Wind Helper
0.191
253333AC1-068 GEN
Solar/Wind Helper
0.134
962211AG1-066 GEN
Solar/Wind Helper
0.209
24344205RKG1
50/50
11.484
270102X2-052 ST
50/50
1.391
970901AG2-562 GEN
50/50
5.27
24386405FR-21G C
Solar/Wind Harmer
5.018
972231SS25-0005
Solar/Wind Harmer
0.777
276876AE1-163_GEN2
Solar/Wind Harmer
6.257
276763AC1-053 GEN1
Solar/Wind Harmer
3.546
274855GSG-6 ;RU
Solar/Wind Harmer
3.867
971411AH1-196 GEN
Solar/Wind Harmer
0.679
961051AF2-396 GEN
Solar/Wind Harmer
0.893
961051AF2-396 GEN
Solar/Wind Harmer
7.143
276782AC1-033 GEN
Solar/Wind Harmer
3.483
944031AF1-071 GEN
Solar/Wind Helper
0.053
970781AG2-491 GEN
Solar/Wind Harmer
0.66
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.916
970707AG2-453 GEN
Solar/Wind Harmer
1.341
970833AG2-524 GEN
Solar/Wind Harmer
4.183
958481AF2-142 GEN
Solar/Wind Harmer
0.702
274862TOP CROP ;2U
Solar/Wind Harmer
5.476
274879MINONK ;1U
Solar/Wind Harmer
7.21
971675AH1-338 GEN
Solar/Wind Harmer
0.815
965911AG1-460 GEN
Solar/Wind Harmer
1.062
339211AE2-254 GEN
Solar/Wind Helper
0.21
253406AD2-031_GEN
Solar/Wind Helper
0.185
276694AA1-018 GEN2
Solar/Wind Harmer
4.975
959341AF2-225 GEN
Solar/Wind Harmer
0.702
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.9
971087AG2-675 GEN
Solar/Wind Harmer
2.681
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.169
253338AC1-165 GEN
Solar/Wind Helper
0.134
970539AG2-343 GEN
50/50
9.19
274871GR RIDGE ;2U
Solar/Wind Harmer
6.025
943121AE2-341 GEN
Solar/Wind Harmer
0.704
276785W4-005 GEN1
Solar/Wind Harmer
2.725
276849AB2-070 GEN2
Solar/Wind Harmer
2.337
957471AF2-041 GEN
Solar/Wind Harmer
1.349
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
5.191
970289AG2-191 GEN
Solar/Wind Harmer
0.402
970291AG2-192 GEN
Solar/Wind Harmer
0.219
252524AE2-267 GEN
Solar/Wind Helper
0.255
253317AC1-085 GEN4
Solar/Wind Helper
0.596
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.065
24386205FR-12G C
Solar/Wind Harmer
5.238
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.651
970373AG2-245 GEN
Solar/Wind Harmer
1.197
276872AE1-163_GEN1
Solar/Wind Harmer
6.257
274872LEEDK;1U
Solar/Wind Harmer
8.563
276686W4-005 GEN3
Solar/Wind Harmer
2.725
276764AC1-053 GEN2
Solar/Wind Harmer
3.546
959081AF2-199 GEN
Solar/Wind Harmer
0.45
274851PROVIDENC;RU
Solar/Wind Harmer
2.579
276911AD2-131_GEN
Solar/Wind Harmer
0.221
25183208HLCRTG
Solar/Wind Helper
0.95
253325AC1-069 GEN
Solar/Wind Helper
0.134
270407AB1-088 ST1
50/50
2.588
970023AG2-014 GEN
50/50
2.641
24344105CKG2
50/50
6.882
270101X2-052 CT2
50/50
1.285
270180AB1-006 GEN1
Solar/Wind Harmer
9.271
24791305MDL-5G
Solar/Wind Harmer
3.434
965791AG1-447 GEN
Solar/Wind Harmer
5.553
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.297
276882AE2-255 GEN
Solar/Wind Harmer
3.605
944221AF1-090 GEN
Solar/Wind Harmer
13.705
276741O09 GEN1
Solar/Wind Harmer
3.619
339221AD2-048_GEN
Solar/Wind Helper
0.342
270340AC2-060 GEN
Solar/Wind Helper
0.373
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.557
950051AG9-018
External Queue
0.31534820795059204
955142J992
External Queue
0.6478373408317566
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
990742J1381
External Queue
1.0048468112945557
991112J1481
External Queue
1.0048468112945557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.557
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.828
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.205
NYPJM->LTFIMP_NY
CLTF
1.178
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
29.011
AH1-155LTFEXP_AH1-155->PJM
LTF
0.307
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.815
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.362
MECLTFEXP_MEC->PJM
CLTF
10.182
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67
WECLTFEXP_WEC->PJM
CLTF
2.921
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.728

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.76 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3333.77
MW Contribution:
0.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270393AB1-087 CT1
50/50
2.594
270406AB1-088 CT1
50/50
2.594
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.745
971347AH1-153 GEN
Solar/Wind Harmer
0.248
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.482
939401AE1-172 GEN
Solar/Wind Harmer
19.009
276656WTG2_EQ
Solar/Wind Harmer
1.071
926823AC1-168 GEN
Solar/Wind Harmer
5.618
276615X2-022 GEN
Solar/Wind Harmer
2.054
970539AG2-343 GEN
50/50
9.221
274871GR RIDGE ;2U
Solar/Wind Harmer
6.05
943121AE2-341 GEN
Solar/Wind Harmer
0.707
276785W4-005 GEN1
Solar/Wind Harmer
2.737
276849AB2-070 GEN2
Solar/Wind Harmer
2.347
957471AF2-041 GEN
Solar/Wind Harmer
1.355
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
5.214
970289AG2-191 GEN
Solar/Wind Harmer
0.404
970291AG2-192 GEN
Solar/Wind Harmer
0.22
252524AE2-267 GEN
Solar/Wind Helper
0.254
253317AC1-085 GEN4
Solar/Wind Helper
0.593
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.064
274857EASY ROAD;U1
Solar/Wind Harmer
4.136
252507AC2-088 GEN
Solar/Wind Helper
0.376
970781AG2-491 GEN
Solar/Wind Harmer
0.662
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.994
970707AG2-453 GEN
Solar/Wind Harmer
1.346
970833AG2-524 GEN
Solar/Wind Harmer
4.2
958481AF2-142 GEN
Solar/Wind Harmer
0.705
274862TOP CROP ;2U
Solar/Wind Harmer
5.499
274879MINONK ;1U
Solar/Wind Harmer
7.24
971675AH1-338 GEN
Solar/Wind Harmer
0.819
965911AG1-460 GEN
Solar/Wind Harmer
1.067
339211AE2-254 GEN
Solar/Wind Helper
0.209
253406AD2-031_GEN
Solar/Wind Helper
0.184
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.166
971997AH1-543 GEN
Solar/Wind Harmer
0.732
962691AG1-118 GEN
Solar/Wind Harmer
1.385
276889AE2-281 GEN
Solar/Wind Harmer
1.795
971993AH1-541 GEN
Solar/Wind Harmer
0.424
270505AE1-170 C O1
Solar/Wind Harmer
0.68
276621W2-048 GEN
Solar/Wind Harmer
6.539
942481AE2-261 GEN
Solar/Wind Harmer
1.329
276158O29GEN2
Solar/Wind Harmer
3.871
276708O09 GEN2
Solar/Wind Harmer
3.635
971549AH1-272 GEN
Solar/Wind Harmer
0.741
270367AC2-061_GEN
Solar/Wind Helper
0.466
962581AG1-107 GEN
Solar/Wind Helper
0.573
270100X2-052 CT1
50/50
1.29
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.864
970571AG2-364 GEN
Solar/Wind Harmer
0.913
274850MENDOTA H;RU
Solar/Wind Harmer
2.7
276863AD2-134 GEN
Solar/Wind Harmer
1.878
276861AD2-134 GEN
Solar/Wind Harmer
1.878
945111AF1-176 GEN
Solar/Wind Harmer
0.798
945111AF1-176 GEN
Solar/Wind Harmer
4.348
274856ECOGROVE ;U1
Solar/Wind Harmer
3.482
971681AH1-341 GEN
Solar/Wind Harmer
0.666
938861AE1-114 GEN
Solar/Wind Harmer
10.387
274858EASY ROAD;U2
Solar/Wind Harmer
4.136
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.444
276843GEN-1.7
Solar/Wind Harmer
0.639
958011AF2-095 GEN
Solar/Wind Harmer
0.694
276691AA1-018 GEN1
Solar/Wind Harmer
0.506
274854TWINGROVE;U2
Solar/Wind Harmer
7.199
965091AG1-374 GEN
Solar/Wind Harmer
1.398
958491AF2-143 GEN
Solar/Wind Harmer
0.699
943021AE2-325 GEN
Solar/Wind Harmer
2.814
276646AC1-214 GEN2
Solar/Wind Harmer
1.39
970819AG2-516 GEN
Solar/Wind Harmer
0.536
274878BISHOP HL;2U
Solar/Wind Harmer
3.471
965931AG1-462 GEN
Solar/Wind Harmer
1.073
339206AE1-143 GEN
Solar/Wind Helper
0.348
241972AD1-140 GEN
Solar/Wind Helper
0.537
270407AB1-088 ST1
50/50
2.594
970023AG2-014 GEN
50/50
2.649
24344105CKG2
50/50
6.908
270101X2-052 CT2
50/50
1.29
270180AB1-006 GEN1
Solar/Wind Harmer
9.298
24791305MDL-5G
Solar/Wind Harmer
3.444
965791AG1-447 GEN
Solar/Wind Harmer
5.575
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.327
276882AE2-255 GEN
Solar/Wind Harmer
3.62
944221AF1-090 GEN
Solar/Wind Harmer
13.766
276741O09 GEN1
Solar/Wind Harmer
3.635
339221AD2-048_GEN
Solar/Wind Helper
0.34
270340AC2-060 GEN
Solar/Wind Helper
0.37
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.545
24344205RKG1
50/50
11.499
270102X2-052 ST
50/50
1.396
970901AG2-562 GEN
50/50
5.29
24386405FR-21G C
Solar/Wind Harmer
5.033
972231SS25-0005
Solar/Wind Harmer
0.781
276876AE1-163_GEN2
Solar/Wind Harmer
6.283
276763AC1-053 GEN1
Solar/Wind Harmer
3.562
274855GSG-6 ;RU
Solar/Wind Harmer
3.884
971411AH1-196 GEN
Solar/Wind Harmer
0.682
961051AF2-396 GEN
Solar/Wind Harmer
0.897
961051AF2-396 GEN
Solar/Wind Harmer
7.174
276782AC1-033 GEN
Solar/Wind Harmer
3.499
944031AF1-071 GEN
Solar/Wind Helper
0.052
24344205RKG1
50/50
11.499
24697605MDL-3G C
Solar/Wind Harmer
5.166
270181AB1-006 GEN2
Solar/Wind Harmer
1.033
24385905FR-11G C
Solar/Wind Harmer
9.894
970193AG2-126 GEN
Solar/Wind Harmer
0.754
274887GEN-1.85
Solar/Wind Harmer
5.943
970833AG2-524 GEN
Solar/Wind Harmer
0.525
274853TWINGROVE;U1
Solar/Wind Harmer
7.199
959611AF2-252 GEN
Solar/Wind Harmer
1.864
960611AF2-352 GEN
Solar/Wind Harmer
1.864
276868AE1-113 GEN
Solar/Wind Harmer
10.861
962781AG1-127 GEN
Solar/Wind Harmer
0.438
971171AH1-044 GEN
Solar/Wind Harmer
0.904
946321AF1-296 GEN
Solar/Wind Harmer
12.624
270063AE2-323 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
0.908
339216AC1-074 GEN
Solar/Wind Helper
0.394
253415AE1-040 GEN
Solar/Wind Helper
0.149
24386205FR-12G C
Solar/Wind Harmer
5.254
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.66
970373AG2-245 GEN
Solar/Wind Harmer
1.201
276872AE1-163_GEN1
Solar/Wind Harmer
6.283
274872LEEDK;1U
Solar/Wind Harmer
8.599
276686W4-005 GEN3
Solar/Wind Harmer
2.737
276764AC1-053 GEN2
Solar/Wind Harmer
3.562
959081AF2-199 GEN
Solar/Wind Harmer
0.452
274851PROVIDENC;RU
Solar/Wind Harmer
2.59
276911AD2-131_GEN
Solar/Wind Harmer
0.222
25183208HLCRTG
Solar/Wind Helper
0.946
253325AC1-069 GEN
Solar/Wind Helper
0.133
970543AG2-345 GEN
50/50
4.61
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.444
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.633
970169AG2-114 GEN
Solar/Wind Harmer
0.473
943591AF1-030 GEN
Solar/Wind Harmer
0.471
276694AA1-018 GEN2
Solar/Wind Harmer
4.996
959341AF2-225 GEN
Solar/Wind Harmer
0.705
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.904
971087AG2-675 GEN
Solar/Wind Harmer
2.693
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.168
253338AC1-165 GEN
Solar/Wind Helper
0.133
24344305RKG2
50/50
11.124
24344305RKG2
50/50
11.029
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.468
972181SS23-001
Solar/Wind Harmer
0.488
274847GR RIDGE ;BU
Solar/Wind Harmer
5.484
959091AF2-200 GEN
Solar/Wind Harmer
0.904
274849CRESCENT ;1U
Solar/Wind Harmer
1.906
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.932
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.182
339241AF1-083 GEN
Solar/Wind Helper
0.19
253333AC1-068 GEN
Solar/Wind Helper
0.133
962211AG1-066 GEN
Solar/Wind Helper
0.207
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.852
276848AB2-070 GEN3
Solar/Wind Harmer
2.347
971341AH1-150 GEN
Solar/Wind Harmer
0.904
274877BISHOP HL;1U
Solar/Wind Harmer
3.471
253316AC1-085 GEN3
Solar/Wind Helper
0.593
253433AC1-085 GEN1
Solar/Wind Helper
0.376
253349AC2-067 GEN
Solar/Wind Helper
0.16
253343AC1-166 GEN
Solar/Wind Helper
0.133
24387305FR-4G C
Solar/Wind Harmer
7.549
24386605FR-22G C
Solar/Wind Harmer
5.033
24387005FR-3G C
Solar/Wind Harmer
4.983
274888KELLY CRK;1U
Solar/Wind Harmer
6.582
276893AG1-478 C
Solar/Wind Harmer
0.382
274863CRW1-WTG
Solar/Wind Harmer
5.566
274864CRW2-WTG
Solar/Wind Harmer
5.566
274880W4-005 GEN4
Solar/Wind Harmer
2.737
276602WESTBROOK C
Solar/Wind Harmer
1.915
957891AF2-083 GEN
Solar/Wind Harmer
0.679
276603SUBLETTE C
Solar/Wind Harmer
0.896
270071AF1-092 GEN
Solar/Wind Harmer
0.566
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.581
253398AE2-221_GEN2
Solar/Wind Helper
0.581
339236AF1-050_GEN
Solar/Wind Helper
0.19
942601AE2-276 GEN
50/50
8.252
971605AH1-302 GEN
Solar/Wind Harmer
9.618
970241AG2-163 GEN
Solar/Wind Harmer
1.478
276897AD1-100 C
Solar/Wind Harmer
64.004
970941AG2-585 GEN
Solar/Wind Harmer
0.265
939741AE1-205 GEN
Solar/Wind Harmer
0.939
942111AE2-223 GEN
Solar/Wind Harmer
10.99
971771AH1-392 GEN
Solar/Wind Harmer
0.421
276805AD2-038 GEN
Solar/Wind Harmer
5.453
276174W4-005 GEN2
Solar/Wind Harmer
2.737
276668AB2-070 GEN1
Solar/Wind Harmer
2.347
970569AG2-363 GEN
Solar/Wind Harmer
1.369
276838X2-022 GEN2
Solar/Wind Harmer
0.244
276645AC1-214 GEN1
Solar/Wind Harmer
1.39
276157O29GEN1
Solar/Wind Harmer
3.871
270043AE2-236 GEN
Solar/Wind Harmer
0.178
961491AF2-440 GEN
Solar/Wind Helper
0.191
970091AG2-072 GEN
50/50
217.153
270394AB1-087 ST1
50/50
2.594
970783AG2-492 GEN
50/50
2.649
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.435
963841AG1-237 GEN
Solar/Wind Harmer
19.253
971917AH1-482 GEN
Solar/Wind Harmer
9.588
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.499
276655WTG1_EQ
Solar/Wind Harmer
8.088
971067AG2-660 GEN
Solar/Wind Harmer
1.807
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.098
270186AC1-089 GEN
Solar/Wind Helper
0.604
339231AF1-038_GEN
Solar/Wind Helper
0.186
270222AC2-111 GEN
Solar/Wind Helper
0.233
339250AF1-203 GEN
Solar/Wind Helper
0.056
950051AG9-018
External Queue
0.31534820795059204
955142J992
External Queue
0.6478373408317566
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
990742J1381
External Queue
1.0048468112945557
991112J1481
External Queue
1.0048468112945557
NYPJM->LTFIMP_NY
CLTF
1.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.087
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.943
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
WECLTFEXP_WEC->PJM
CLTF
2.934
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.797
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.012
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.814
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.308
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.34
MECLTFEXP_MEC->PJM
CLTF
10.238
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.76 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3333.74
MW Contribution:
0.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24387305FR-4G C
Solar/Wind Harmer
7.549
24386605FR-22G C
Solar/Wind Harmer
5.033
24387005FR-3G C
Solar/Wind Harmer
4.983
274888KELLY CRK;1U
Solar/Wind Harmer
6.582
276893AG1-478 C
Solar/Wind Harmer
0.382
274863CRW1-WTG
Solar/Wind Harmer
5.566
274864CRW2-WTG
Solar/Wind Harmer
5.566
274880W4-005 GEN4
Solar/Wind Harmer
2.737
276602WESTBROOK C
Solar/Wind Harmer
1.915
957891AF2-083 GEN
Solar/Wind Harmer
0.679
276603SUBLETTE C
Solar/Wind Harmer
0.896
270071AF1-092 GEN
Solar/Wind Harmer
0.566
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.581
253398AE2-221_GEN2
Solar/Wind Helper
0.581
339236AF1-050_GEN
Solar/Wind Helper
0.19
24344205RKG1
50/50
11.499
270102X2-052 ST
50/50
1.396
970901AG2-562 GEN
50/50
5.29
24386405FR-21G C
Solar/Wind Harmer
5.033
972231SS25-0005
Solar/Wind Harmer
0.781
276876AE1-163_GEN2
Solar/Wind Harmer
6.283
276763AC1-053 GEN1
Solar/Wind Harmer
3.562
274855GSG-6 ;RU
Solar/Wind Harmer
3.884
971411AH1-196 GEN
Solar/Wind Harmer
0.682
961051AF2-396 GEN
Solar/Wind Harmer
0.897
961051AF2-396 GEN
Solar/Wind Harmer
7.174
276782AC1-033 GEN
Solar/Wind Harmer
3.499
944031AF1-071 GEN
Solar/Wind Helper
0.052
24344305RKG2
50/50
11.124
24344305RKG2
50/50
11.029
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.468
972181SS23-001
Solar/Wind Harmer
0.488
274847GR RIDGE ;BU
Solar/Wind Harmer
5.484
959091AF2-200 GEN
Solar/Wind Harmer
0.904
274849CRESCENT ;1U
Solar/Wind Harmer
1.906
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.932
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.182
339241AF1-083 GEN
Solar/Wind Helper
0.19
253333AC1-068 GEN
Solar/Wind Helper
0.133
962211AG1-066 GEN
Solar/Wind Helper
0.207
970781AG2-491 GEN
Solar/Wind Harmer
0.662
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.994
970707AG2-453 GEN
Solar/Wind Harmer
1.346
970833AG2-524 GEN
Solar/Wind Harmer
4.2
958481AF2-142 GEN
Solar/Wind Harmer
0.705
274862TOP CROP ;2U
Solar/Wind Harmer
5.499
274879MINONK ;1U
Solar/Wind Harmer
7.24
971675AH1-338 GEN
Solar/Wind Harmer
0.819
965911AG1-460 GEN
Solar/Wind Harmer
1.067
339211AE2-254 GEN
Solar/Wind Helper
0.209
253406AD2-031_GEN
Solar/Wind Helper
0.184
270393AB1-087 CT1
50/50
2.594
270406AB1-088 CT1
50/50
2.594
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.745
971347AH1-153 GEN
Solar/Wind Harmer
0.248
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.482
939401AE1-172 GEN
Solar/Wind Harmer
19.009
970543AG2-345 GEN
50/50
4.61
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.444
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.633
970169AG2-114 GEN
Solar/Wind Harmer
0.473
943591AF1-030 GEN
Solar/Wind Harmer
0.471
276694AA1-018 GEN2
Solar/Wind Harmer
4.996
959341AF2-225 GEN
Solar/Wind Harmer
0.705
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.904
971087AG2-675 GEN
Solar/Wind Harmer
2.693
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.168
253338AC1-165 GEN
Solar/Wind Helper
0.133
970539AG2-343 GEN
50/50
9.221
274871GR RIDGE ;2U
Solar/Wind Harmer
6.05
943121AE2-341 GEN
Solar/Wind Harmer
0.707
276785W4-005 GEN1
Solar/Wind Harmer
2.737
276849AB2-070 GEN2
Solar/Wind Harmer
2.347
957471AF2-041 GEN
Solar/Wind Harmer
1.355
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
5.214
970289AG2-191 GEN
Solar/Wind Harmer
0.404
970291AG2-192 GEN
Solar/Wind Harmer
0.22
252524AE2-267 GEN
Solar/Wind Helper
0.254
253317AC1-085 GEN4
Solar/Wind Helper
0.593
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.064
276656WTG2_EQ
Solar/Wind Harmer
1.071
926823AC1-168 GEN
Solar/Wind Harmer
5.618
276615X2-022 GEN
Solar/Wind Harmer
2.054
274857EASY ROAD;U1
Solar/Wind Harmer
4.136
252507AC2-088 GEN
Solar/Wind Helper
0.376
270407AB1-088 ST1
50/50
2.594
970023AG2-014 GEN
50/50
2.649
24344105CKG2
50/50
6.908
270101X2-052 CT2
50/50
1.29
270180AB1-006 GEN1
Solar/Wind Harmer
9.298
24791305MDL-5G
Solar/Wind Harmer
3.444
965791AG1-447 GEN
Solar/Wind Harmer
5.575
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.327
276882AE2-255 GEN
Solar/Wind Harmer
3.62
944221AF1-090 GEN
Solar/Wind Harmer
13.766
276741O09 GEN1
Solar/Wind Harmer
3.635
339221AD2-048_GEN
Solar/Wind Helper
0.34
270340AC2-060 GEN
Solar/Wind Helper
0.37
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.545
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.444
276843GEN-1.7
Solar/Wind Harmer
0.639
958011AF2-095 GEN
Solar/Wind Harmer
0.694
276691AA1-018 GEN1
Solar/Wind Harmer
0.506
274854TWINGROVE;U2
Solar/Wind Harmer
7.199
965091AG1-374 GEN
Solar/Wind Harmer
1.398
958491AF2-143 GEN
Solar/Wind Harmer
0.699
943021AE2-325 GEN
Solar/Wind Harmer
2.814
276646AC1-214 GEN2
Solar/Wind Harmer
1.39
970819AG2-516 GEN
Solar/Wind Harmer
0.536
274878BISHOP HL;2U
Solar/Wind Harmer
3.471
965931AG1-462 GEN
Solar/Wind Harmer
1.073
339206AE1-143 GEN
Solar/Wind Helper
0.348
241972AD1-140 GEN
Solar/Wind Helper
0.537
24344205RKG1
50/50
11.499
24697605MDL-3G C
Solar/Wind Harmer
5.166
270181AB1-006 GEN2
Solar/Wind Harmer
1.033
24385905FR-11G C
Solar/Wind Harmer
9.894
970193AG2-126 GEN
Solar/Wind Harmer
0.754
274887GEN-1.85
Solar/Wind Harmer
5.943
970833AG2-524 GEN
Solar/Wind Harmer
0.525
274853TWINGROVE;U1
Solar/Wind Harmer
7.199
959611AF2-252 GEN
Solar/Wind Harmer
1.864
960611AF2-352 GEN
Solar/Wind Harmer
1.864
276868AE1-113 GEN
Solar/Wind Harmer
10.861
962781AG1-127 GEN
Solar/Wind Harmer
0.438
971171AH1-044 GEN
Solar/Wind Harmer
0.904
946321AF1-296 GEN
Solar/Wind Harmer
12.624
270063AE2-323 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
0.908
339216AC1-074 GEN
Solar/Wind Helper
0.394
253415AE1-040 GEN
Solar/Wind Helper
0.149
970091AG2-072 GEN
50/50
217.153
270394AB1-087 ST1
50/50
2.594
970783AG2-492 GEN
50/50
2.649
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.435
963841AG1-237 GEN
Solar/Wind Harmer
19.253
971917AH1-482 GEN
Solar/Wind Harmer
9.588
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.499
276655WTG1_EQ
Solar/Wind Harmer
8.088
971067AG2-660 GEN
Solar/Wind Harmer
1.807
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.098
270186AC1-089 GEN
Solar/Wind Helper
0.604
942601AE2-276 GEN
50/50
8.252
971605AH1-302 GEN
Solar/Wind Harmer
9.618
970241AG2-163 GEN
Solar/Wind Harmer
1.478
276897AD1-100 C
Solar/Wind Harmer
64.004
970941AG2-585 GEN
Solar/Wind Harmer
0.265
939741AE1-205 GEN
Solar/Wind Harmer
0.939
942111AE2-223 GEN
Solar/Wind Harmer
10.99
971771AH1-392 GEN
Solar/Wind Harmer
0.421
276805AD2-038 GEN
Solar/Wind Harmer
5.453
276174W4-005 GEN2
Solar/Wind Harmer
2.737
276668AB2-070 GEN1
Solar/Wind Harmer
2.347
970569AG2-363 GEN
Solar/Wind Harmer
1.369
276838X2-022 GEN2
Solar/Wind Harmer
0.244
276645AC1-214 GEN1
Solar/Wind Harmer
1.39
276157O29GEN1
Solar/Wind Harmer
3.871
270043AE2-236 GEN
Solar/Wind Harmer
0.178
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.166
971997AH1-543 GEN
Solar/Wind Harmer
0.732
962691AG1-118 GEN
Solar/Wind Harmer
1.385
276889AE2-281 GEN
Solar/Wind Harmer
1.795
971993AH1-541 GEN
Solar/Wind Harmer
0.424
270505AE1-170 C O1
Solar/Wind Harmer
0.68
276621W2-048 GEN
Solar/Wind Harmer
6.539
942481AE2-261 GEN
Solar/Wind Harmer
1.329
276158O29GEN2
Solar/Wind Harmer
3.871
276708O09 GEN2
Solar/Wind Harmer
3.635
971549AH1-272 GEN
Solar/Wind Harmer
0.741
270367AC2-061_GEN
Solar/Wind Helper
0.466
962581AG1-107 GEN
Solar/Wind Helper
0.573
270100X2-052 CT1
50/50
1.29
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.864
970571AG2-364 GEN
Solar/Wind Harmer
0.913
274850MENDOTA H;RU
Solar/Wind Harmer
2.7
276863AD2-134 GEN
Solar/Wind Harmer
1.878
276861AD2-134 GEN
Solar/Wind Harmer
1.878
945111AF1-176 GEN
Solar/Wind Harmer
0.798
945111AF1-176 GEN
Solar/Wind Harmer
4.348
274856ECOGROVE ;U1
Solar/Wind Harmer
3.482
971681AH1-341 GEN
Solar/Wind Harmer
0.666
938861AE1-114 GEN
Solar/Wind Harmer
10.387
274858EASY ROAD;U2
Solar/Wind Harmer
4.136
961491AF2-440 GEN
Solar/Wind Helper
0.191
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.852
276848AB2-070 GEN3
Solar/Wind Harmer
2.347
971341AH1-150 GEN
Solar/Wind Harmer
0.904
274877BISHOP HL;1U
Solar/Wind Harmer
3.471
253316AC1-085 GEN3
Solar/Wind Helper
0.593
253433AC1-085 GEN1
Solar/Wind Helper
0.376
253349AC2-067 GEN
Solar/Wind Helper
0.16
253343AC1-166 GEN
Solar/Wind Helper
0.133
339231AF1-038_GEN
Solar/Wind Helper
0.186
270222AC2-111 GEN
Solar/Wind Helper
0.233
339250AF1-203 GEN
Solar/Wind Helper
0.056
24386205FR-12G C
Solar/Wind Harmer
5.254
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.66
970373AG2-245 GEN
Solar/Wind Harmer
1.201
276872AE1-163_GEN1
Solar/Wind Harmer
6.283
274872LEEDK;1U
Solar/Wind Harmer
8.599
276686W4-005 GEN3
Solar/Wind Harmer
2.737
276764AC1-053 GEN2
Solar/Wind Harmer
3.562
959081AF2-199 GEN
Solar/Wind Harmer
0.452
274851PROVIDENC;RU
Solar/Wind Harmer
2.59
276911AD2-131_GEN
Solar/Wind Harmer
0.222
25183208HLCRTG
Solar/Wind Helper
0.946
253325AC1-069 GEN
Solar/Wind Helper
0.133
950051AG9-018
External Queue
0.31534820795059204
955142J992
External Queue
0.6478373408317566
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
990742J1381
External Queue
1.0048468112945557
991112J1481
External Queue
1.0048468112945557
NYPJM->LTFIMP_NY
CLTF
1.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.087
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.943
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
WECLTFEXP_WEC->PJM
CLTF
2.934
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.797
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.012
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.814
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.308
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.34
MECLTFEXP_MEC->PJM
CLTF
10.238
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.9 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3346.96
MW Contribution:
0.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.151
971997AH1-543 GEN
Solar/Wind Harmer
0.729
962691AG1-118 GEN
Solar/Wind Harmer
1.379
276889AE2-281 GEN
Solar/Wind Harmer
1.788
971993AH1-541 GEN
Solar/Wind Harmer
0.422
270505AE1-170 C O1
Solar/Wind Harmer
0.677
276621W2-048 GEN
Solar/Wind Harmer
6.511
942481AE2-261 GEN
Solar/Wind Harmer
1.324
276158O29GEN2
Solar/Wind Harmer
3.853
276708O09 GEN2
Solar/Wind Harmer
3.619
971549AH1-272 GEN
Solar/Wind Harmer
0.737
270367AC2-061_GEN
Solar/Wind Helper
0.469
962581AG1-107 GEN
Solar/Wind Helper
0.576
24344205RKG1
50/50
11.484
24697605MDL-3G C
Solar/Wind Harmer
5.151
270181AB1-006 GEN2
Solar/Wind Harmer
1.03
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.792
276848AB2-070 GEN3
Solar/Wind Harmer
2.337
971341AH1-150 GEN
Solar/Wind Harmer
0.9
274877BISHOP HL;1U
Solar/Wind Harmer
3.456
253316AC1-085 GEN3
Solar/Wind Helper
0.596
253433AC1-085 GEN1
Solar/Wind Helper
0.378
253349AC2-067 GEN
Solar/Wind Helper
0.161
24385905FR-11G C
Solar/Wind Harmer
9.864
970193AG2-126 GEN
Solar/Wind Harmer
0.751
274887GEN-1.85
Solar/Wind Harmer
5.918
970833AG2-524 GEN
Solar/Wind Harmer
0.523
274853TWINGROVE;U1
Solar/Wind Harmer
7.169
959611AF2-252 GEN
Solar/Wind Harmer
1.857
960611AF2-352 GEN
Solar/Wind Harmer
1.857
276868AE1-113 GEN
Solar/Wind Harmer
10.815
962781AG1-127 GEN
Solar/Wind Harmer
0.436
971171AH1-044 GEN
Solar/Wind Harmer
0.9
946321AF1-296 GEN
Solar/Wind Harmer
12.566
270063AE2-323 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
0.903
339216AC1-074 GEN
Solar/Wind Helper
0.395
253415AE1-040 GEN
Solar/Wind Helper
0.15
270393AB1-087 CT1
50/50
2.588
270406AB1-088 CT1
50/50
2.588
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.742
971347AH1-153 GEN
Solar/Wind Harmer
0.247
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.48
939401AE1-172 GEN
Solar/Wind Harmer
18.931
276656WTG2_EQ
Solar/Wind Harmer
1.066
926823AC1-168 GEN
Solar/Wind Harmer
5.594
276615X2-022 GEN
Solar/Wind Harmer
2.045
274857EASY ROAD;U1
Solar/Wind Harmer
4.117
252507AC2-088 GEN
Solar/Wind Helper
0.377
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.434
276843GEN-1.7
Solar/Wind Harmer
0.637
958011AF2-095 GEN
Solar/Wind Harmer
0.692
276691AA1-018 GEN1
Solar/Wind Harmer
0.504
274854TWINGROVE;U2
Solar/Wind Harmer
7.169
965091AG1-374 GEN
Solar/Wind Harmer
1.392
958491AF2-143 GEN
Solar/Wind Harmer
0.696
943021AE2-325 GEN
Solar/Wind Harmer
2.802
276646AC1-214 GEN2
Solar/Wind Harmer
1.384
970819AG2-516 GEN
Solar/Wind Harmer
0.534
274878BISHOP HL;2U
Solar/Wind Harmer
3.456
965931AG1-462 GEN
Solar/Wind Harmer
1.068
339206AE1-143 GEN
Solar/Wind Helper
0.35
241972AD1-140 GEN
Solar/Wind Helper
0.541
24386205FR-12G C
Solar/Wind Harmer
5.238
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.651
970373AG2-245 GEN
Solar/Wind Harmer
1.197
276872AE1-163_GEN1
Solar/Wind Harmer
6.257
274872LEEDK;1U
Solar/Wind Harmer
8.563
276686W4-005 GEN3
Solar/Wind Harmer
2.725
276764AC1-053 GEN2
Solar/Wind Harmer
3.546
959081AF2-199 GEN
Solar/Wind Harmer
0.45
274851PROVIDENC;RU
Solar/Wind Harmer
2.579
276911AD2-131_GEN
Solar/Wind Harmer
0.221
25183208HLCRTG
Solar/Wind Helper
0.95
253325AC1-069 GEN
Solar/Wind Helper
0.134
970091AG2-072 GEN
50/50
216.879
270394AB1-087 ST1
50/50
2.588
970783AG2-492 GEN
50/50
2.641
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.404
963841AG1-237 GEN
Solar/Wind Harmer
19.192
971917AH1-482 GEN
Solar/Wind Harmer
9.558
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.476
276655WTG1_EQ
Solar/Wind Harmer
8.054
971067AG2-660 GEN
Solar/Wind Harmer
1.799
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.099
270186AC1-089 GEN
Solar/Wind Helper
0.607
339231AF1-038_GEN
Solar/Wind Helper
0.187
270222AC2-111 GEN
Solar/Wind Helper
0.234
339250AF1-203 GEN
Solar/Wind Helper
0.056
253343AC1-166 GEN
Solar/Wind Helper
0.134
970539AG2-343 GEN
50/50
9.19
274871GR RIDGE ;2U
Solar/Wind Harmer
6.025
943121AE2-341 GEN
Solar/Wind Harmer
0.704
276785W4-005 GEN1
Solar/Wind Harmer
2.725
276849AB2-070 GEN2
Solar/Wind Harmer
2.337
957471AF2-041 GEN
Solar/Wind Harmer
1.349
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
5.191
970289AG2-191 GEN
Solar/Wind Harmer
0.402
970291AG2-192 GEN
Solar/Wind Harmer
0.219
252524AE2-267 GEN
Solar/Wind Helper
0.255
253317AC1-085 GEN4
Solar/Wind Helper
0.596
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.065
970781AG2-491 GEN
Solar/Wind Harmer
0.66
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.916
970707AG2-453 GEN
Solar/Wind Harmer
1.341
970833AG2-524 GEN
Solar/Wind Harmer
4.183
958481AF2-142 GEN
Solar/Wind Harmer
0.702
274862TOP CROP ;2U
Solar/Wind Harmer
5.476
274879MINONK ;1U
Solar/Wind Harmer
7.21
971675AH1-338 GEN
Solar/Wind Harmer
0.815
965911AG1-460 GEN
Solar/Wind Harmer
1.062
339211AE2-254 GEN
Solar/Wind Helper
0.21
253406AD2-031_GEN
Solar/Wind Helper
0.185
970543AG2-345 GEN
50/50
4.595
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.434
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.631
970169AG2-114 GEN
Solar/Wind Harmer
0.471
943591AF1-030 GEN
Solar/Wind Harmer
0.469
276694AA1-018 GEN2
Solar/Wind Harmer
4.975
959341AF2-225 GEN
Solar/Wind Harmer
0.702
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.9
971087AG2-675 GEN
Solar/Wind Harmer
2.681
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.169
253338AC1-165 GEN
Solar/Wind Helper
0.134
24387305FR-4G C
Solar/Wind Harmer
7.526
24386605FR-22G C
Solar/Wind Harmer
5.018
24387005FR-3G C
Solar/Wind Harmer
4.967
274888KELLY CRK;1U
Solar/Wind Harmer
6.555
276893AG1-478 C
Solar/Wind Harmer
0.38
274863CRW1-WTG
Solar/Wind Harmer
5.543
274864CRW2-WTG
Solar/Wind Harmer
5.543
274880W4-005 GEN4
Solar/Wind Harmer
2.725
276602WESTBROOK C
Solar/Wind Harmer
1.907
957891AF2-083 GEN
Solar/Wind Harmer
0.676
276603SUBLETTE C
Solar/Wind Harmer
0.892
270071AF1-092 GEN
Solar/Wind Harmer
0.563
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.583
253398AE2-221_GEN2
Solar/Wind Helper
0.583
339236AF1-050_GEN
Solar/Wind Helper
0.191
942601AE2-276 GEN
50/50
8.233
971605AH1-302 GEN
Solar/Wind Harmer
9.589
970241AG2-163 GEN
Solar/Wind Harmer
1.473
276897AD1-100 C
Solar/Wind Harmer
63.744
970941AG2-585 GEN
Solar/Wind Harmer
0.264
939741AE1-205 GEN
Solar/Wind Harmer
0.935
942111AE2-223 GEN
Solar/Wind Harmer
10.945
971771AH1-392 GEN
Solar/Wind Harmer
0.419
276805AD2-038 GEN
Solar/Wind Harmer
5.43
276174W4-005 GEN2
Solar/Wind Harmer
2.725
276668AB2-070 GEN1
Solar/Wind Harmer
2.337
970569AG2-363 GEN
Solar/Wind Harmer
1.363
276838X2-022 GEN2
Solar/Wind Harmer
0.243
276645AC1-214 GEN1
Solar/Wind Harmer
1.384
276157O29GEN1
Solar/Wind Harmer
3.853
270043AE2-236 GEN
Solar/Wind Harmer
0.177
961491AF2-440 GEN
Solar/Wind Helper
0.192
270100X2-052 CT1
50/50
1.285
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.856
970571AG2-364 GEN
Solar/Wind Harmer
0.909
274850MENDOTA H;RU
Solar/Wind Harmer
2.689
276863AD2-134 GEN
Solar/Wind Harmer
1.87
276861AD2-134 GEN
Solar/Wind Harmer
1.87
945111AF1-176 GEN
Solar/Wind Harmer
0.794
945111AF1-176 GEN
Solar/Wind Harmer
4.329
274856ECOGROVE ;U1
Solar/Wind Harmer
3.466
971681AH1-341 GEN
Solar/Wind Harmer
0.663
938861AE1-114 GEN
Solar/Wind Harmer
10.341
274858EASY ROAD;U2
Solar/Wind Harmer
4.117
24344205RKG1
50/50
11.484
270102X2-052 ST
50/50
1.391
970901AG2-562 GEN
50/50
5.27
24386405FR-21G C
Solar/Wind Harmer
5.018
972231SS25-0005
Solar/Wind Harmer
0.777
276876AE1-163_GEN2
Solar/Wind Harmer
6.257
276763AC1-053 GEN1
Solar/Wind Harmer
3.546
274855GSG-6 ;RU
Solar/Wind Harmer
3.867
971411AH1-196 GEN
Solar/Wind Harmer
0.679
961051AF2-396 GEN
Solar/Wind Harmer
0.893
961051AF2-396 GEN
Solar/Wind Harmer
7.143
276782AC1-033 GEN
Solar/Wind Harmer
3.483
944031AF1-071 GEN
Solar/Wind Helper
0.053
270407AB1-088 ST1
50/50
2.588
970023AG2-014 GEN
50/50
2.641
24344105CKG2
50/50
6.882
270101X2-052 CT2
50/50
1.285
270180AB1-006 GEN1
Solar/Wind Harmer
9.271
24791305MDL-5G
Solar/Wind Harmer
3.434
965791AG1-447 GEN
Solar/Wind Harmer
5.553
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.297
276882AE2-255 GEN
Solar/Wind Harmer
3.605
944221AF1-090 GEN
Solar/Wind Harmer
13.705
276741O09 GEN1
Solar/Wind Harmer
3.619
339221AD2-048_GEN
Solar/Wind Helper
0.342
270340AC2-060 GEN
Solar/Wind Helper
0.373
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.557
24344305RKG2
50/50
11.11
24344305RKG2
50/50
11.015
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.462
972181SS23-001
Solar/Wind Harmer
0.486
274847GR RIDGE ;BU
Solar/Wind Harmer
5.462
959091AF2-200 GEN
Solar/Wind Harmer
0.9
274849CRESCENT ;1U
Solar/Wind Harmer
1.898
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.928
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.183
339241AF1-083 GEN
Solar/Wind Helper
0.191
253333AC1-068 GEN
Solar/Wind Helper
0.134
962211AG1-066 GEN
Solar/Wind Helper
0.209
950051AG9-018
External Queue
0.31534820795059204
955142J992
External Queue
0.6478373408317566
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
990742J1381
External Queue
1.0048468112945557
991112J1481
External Queue
1.0048468112945557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.557
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.828
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.205
NYPJM->LTFIMP_NY
CLTF
1.178
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
29.011
AH1-155LTFEXP_AH1-155->PJM
LTF
0.307
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.815
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.362
MECLTFEXP_MEC->PJM
CLTF
10.182
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67
WECLTFEXP_WEC->PJM
CLTF
2.921
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.728

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.0 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3290.17
MW Contribution:
0.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270393AB1-087 CT1
50/50
2.594
270406AB1-088 CT1
50/50
2.594
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.745
971347AH1-153 GEN
Solar/Wind Harmer
0.248
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.482
939401AE1-172 GEN
Solar/Wind Harmer
19.009
276656WTG2_EQ
Solar/Wind Harmer
1.071
926823AC1-168 GEN
Solar/Wind Harmer
5.618
276615X2-022 GEN
Solar/Wind Harmer
2.054
274857EASY ROAD;U1
Solar/Wind Harmer
4.136
252507AC2-088 GEN
Solar/Wind Helper
0.376
970539AG2-343 GEN
50/50
9.221
274871GR RIDGE ;2U
Solar/Wind Harmer
6.05
943121AE2-341 GEN
Solar/Wind Harmer
0.707
276785W4-005 GEN1
Solar/Wind Harmer
2.737
276849AB2-070 GEN2
Solar/Wind Harmer
2.347
957471AF2-041 GEN
Solar/Wind Harmer
1.355
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
5.214
970289AG2-191 GEN
Solar/Wind Harmer
0.404
970291AG2-192 GEN
Solar/Wind Harmer
0.22
252524AE2-267 GEN
Solar/Wind Helper
0.254
253317AC1-085 GEN4
Solar/Wind Helper
0.593
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.064
970781AG2-491 GEN
Solar/Wind Harmer
0.662
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.994
970707AG2-453 GEN
Solar/Wind Harmer
1.346
970833AG2-524 GEN
Solar/Wind Harmer
4.2
958481AF2-142 GEN
Solar/Wind Harmer
0.705
274862TOP CROP ;2U
Solar/Wind Harmer
5.499
274879MINONK ;1U
Solar/Wind Harmer
7.24
971675AH1-338 GEN
Solar/Wind Harmer
0.819
965911AG1-460 GEN
Solar/Wind Harmer
1.067
339211AE2-254 GEN
Solar/Wind Helper
0.209
253406AD2-031_GEN
Solar/Wind Helper
0.184
970543AG2-345 GEN
50/50
4.61
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.444
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.633
970169AG2-114 GEN
Solar/Wind Harmer
0.473
943591AF1-030 GEN
Solar/Wind Harmer
0.471
276694AA1-018 GEN2
Solar/Wind Harmer
4.996
959341AF2-225 GEN
Solar/Wind Harmer
0.705
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.904
971087AG2-675 GEN
Solar/Wind Harmer
2.693
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.168
253338AC1-165 GEN
Solar/Wind Helper
0.133
24344205RKG1
50/50
11.499
270102X2-052 ST
50/50
1.396
970901AG2-562 GEN
50/50
5.29
24386405FR-21G C
Solar/Wind Harmer
5.033
972231SS25-0005
Solar/Wind Harmer
0.781
276876AE1-163_GEN2
Solar/Wind Harmer
6.283
276763AC1-053 GEN1
Solar/Wind Harmer
3.562
274855GSG-6 ;RU
Solar/Wind Harmer
3.884
971411AH1-196 GEN
Solar/Wind Harmer
0.682
961051AF2-396 GEN
Solar/Wind Harmer
0.897
961051AF2-396 GEN
Solar/Wind Harmer
7.174
276782AC1-033 GEN
Solar/Wind Harmer
3.499
944031AF1-071 GEN
Solar/Wind Helper
0.052
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.166
971997AH1-543 GEN
Solar/Wind Harmer
0.732
962691AG1-118 GEN
Solar/Wind Harmer
1.385
276889AE2-281 GEN
Solar/Wind Harmer
1.795
971993AH1-541 GEN
Solar/Wind Harmer
0.424
270505AE1-170 C O1
Solar/Wind Harmer
0.68
276621W2-048 GEN
Solar/Wind Harmer
6.539
942481AE2-261 GEN
Solar/Wind Harmer
1.329
276158O29GEN2
Solar/Wind Harmer
3.871
276708O09 GEN2
Solar/Wind Harmer
3.635
971549AH1-272 GEN
Solar/Wind Harmer
0.741
270367AC2-061_GEN
Solar/Wind Helper
0.466
962581AG1-107 GEN
Solar/Wind Helper
0.573
270100X2-052 CT1
50/50
1.29
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.864
970571AG2-364 GEN
Solar/Wind Harmer
0.913
274850MENDOTA H;RU
Solar/Wind Harmer
2.7
276863AD2-134 GEN
Solar/Wind Harmer
1.878
276861AD2-134 GEN
Solar/Wind Harmer
1.878
945111AF1-176 GEN
Solar/Wind Harmer
0.798
945111AF1-176 GEN
Solar/Wind Harmer
4.348
274856ECOGROVE ;U1
Solar/Wind Harmer
3.482
971681AH1-341 GEN
Solar/Wind Harmer
0.666
938861AE1-114 GEN
Solar/Wind Harmer
10.387
274858EASY ROAD;U2
Solar/Wind Harmer
4.136
24387305FR-4G C
Solar/Wind Harmer
7.549
24386605FR-22G C
Solar/Wind Harmer
5.033
24387005FR-3G C
Solar/Wind Harmer
4.983
274888KELLY CRK;1U
Solar/Wind Harmer
6.582
276893AG1-478 C
Solar/Wind Harmer
0.382
274863CRW1-WTG
Solar/Wind Harmer
5.566
274864CRW2-WTG
Solar/Wind Harmer
5.566
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.444
276843GEN-1.7
Solar/Wind Harmer
0.639
958011AF2-095 GEN
Solar/Wind Harmer
0.694
276691AA1-018 GEN1
Solar/Wind Harmer
0.506
274854TWINGROVE;U2
Solar/Wind Harmer
7.199
965091AG1-374 GEN
Solar/Wind Harmer
1.398
958491AF2-143 GEN
Solar/Wind Harmer
0.699
943021AE2-325 GEN
Solar/Wind Harmer
2.814
276646AC1-214 GEN2
Solar/Wind Harmer
1.39
970819AG2-516 GEN
Solar/Wind Harmer
0.536
274878BISHOP HL;2U
Solar/Wind Harmer
3.471
965931AG1-462 GEN
Solar/Wind Harmer
1.073
339206AE1-143 GEN
Solar/Wind Helper
0.348
241972AD1-140 GEN
Solar/Wind Helper
0.537
270407AB1-088 ST1
50/50
2.594
970023AG2-014 GEN
50/50
2.649
24344105CKG2
50/50
6.908
270101X2-052 CT2
50/50
1.29
270180AB1-006 GEN1
Solar/Wind Harmer
9.298
24791305MDL-5G
Solar/Wind Harmer
3.444
965791AG1-447 GEN
Solar/Wind Harmer
5.575
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.327
276882AE2-255 GEN
Solar/Wind Harmer
3.62
944221AF1-090 GEN
Solar/Wind Harmer
13.766
276741O09 GEN1
Solar/Wind Harmer
3.635
339221AD2-048_GEN
Solar/Wind Helper
0.34
270340AC2-060 GEN
Solar/Wind Helper
0.37
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.545
24386205FR-12G C
Solar/Wind Harmer
5.254
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.66
970373AG2-245 GEN
Solar/Wind Harmer
1.201
276872AE1-163_GEN1
Solar/Wind Harmer
6.283
274872LEEDK;1U
Solar/Wind Harmer
8.599
276686W4-005 GEN3
Solar/Wind Harmer
2.737
276764AC1-053 GEN2
Solar/Wind Harmer
3.562
959081AF2-199 GEN
Solar/Wind Harmer
0.452
274851PROVIDENC;RU
Solar/Wind Harmer
2.59
276911AD2-131_GEN
Solar/Wind Harmer
0.222
25183208HLCRTG
Solar/Wind Helper
0.946
253325AC1-069 GEN
Solar/Wind Helper
0.133
24344205RKG1
50/50
11.499
24697605MDL-3G C
Solar/Wind Harmer
5.166
270181AB1-006 GEN2
Solar/Wind Harmer
1.033
24385905FR-11G C
Solar/Wind Harmer
9.894
970193AG2-126 GEN
Solar/Wind Harmer
0.754
274887GEN-1.85
Solar/Wind Harmer
5.943
970833AG2-524 GEN
Solar/Wind Harmer
0.525
274853TWINGROVE;U1
Solar/Wind Harmer
7.199
959611AF2-252 GEN
Solar/Wind Harmer
1.864
960611AF2-352 GEN
Solar/Wind Harmer
1.864
276868AE1-113 GEN
Solar/Wind Harmer
10.861
962781AG1-127 GEN
Solar/Wind Harmer
0.438
971171AH1-044 GEN
Solar/Wind Harmer
0.904
946321AF1-296 GEN
Solar/Wind Harmer
12.624
270063AE2-323 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
0.908
339216AC1-074 GEN
Solar/Wind Helper
0.394
253415AE1-040 GEN
Solar/Wind Helper
0.149
970091AG2-072 GEN
50/50
217.153
270394AB1-087 ST1
50/50
2.594
970783AG2-492 GEN
50/50
2.649
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.435
963841AG1-237 GEN
Solar/Wind Harmer
19.253
971917AH1-482 GEN
Solar/Wind Harmer
9.588
960681AF2-359 GEN
Solar/Wind Harmer
0
24344305RKG2
50/50
11.124
24344305RKG2
50/50
11.029
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.468
972181SS23-001
Solar/Wind Harmer
0.488
274847GR RIDGE ;BU
Solar/Wind Harmer
5.484
959091AF2-200 GEN
Solar/Wind Harmer
0.904
274849CRESCENT ;1U
Solar/Wind Harmer
1.906
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.932
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.182
339241AF1-083 GEN
Solar/Wind Helper
0.19
253333AC1-068 GEN
Solar/Wind Helper
0.133
962211AG1-066 GEN
Solar/Wind Helper
0.207
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.852
276848AB2-070 GEN3
Solar/Wind Harmer
2.347
971341AH1-150 GEN
Solar/Wind Harmer
0.904
274877BISHOP HL;1U
Solar/Wind Harmer
3.471
253316AC1-085 GEN3
Solar/Wind Helper
0.593
253433AC1-085 GEN1
Solar/Wind Helper
0.376
253349AC2-067 GEN
Solar/Wind Helper
0.16
253343AC1-166 GEN
Solar/Wind Helper
0.133
274880W4-005 GEN4
Solar/Wind Harmer
2.737
276602WESTBROOK C
Solar/Wind Harmer
1.915
957891AF2-083 GEN
Solar/Wind Harmer
0.679
276603SUBLETTE C
Solar/Wind Harmer
0.896
270071AF1-092 GEN
Solar/Wind Harmer
0.566
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.581
253398AE2-221_GEN2
Solar/Wind Helper
0.581
339236AF1-050_GEN
Solar/Wind Helper
0.19
942601AE2-276 GEN
50/50
8.252
971605AH1-302 GEN
Solar/Wind Harmer
9.618
970241AG2-163 GEN
Solar/Wind Harmer
1.478
276897AD1-100 C
Solar/Wind Harmer
64.004
970941AG2-585 GEN
Solar/Wind Harmer
0.265
939741AE1-205 GEN
Solar/Wind Harmer
0.939
942111AE2-223 GEN
Solar/Wind Harmer
10.99
971771AH1-392 GEN
Solar/Wind Harmer
0.421
276805AD2-038 GEN
Solar/Wind Harmer
5.453
276174W4-005 GEN2
Solar/Wind Harmer
2.737
276668AB2-070 GEN1
Solar/Wind Harmer
2.347
970569AG2-363 GEN
Solar/Wind Harmer
1.369
276838X2-022 GEN2
Solar/Wind Harmer
0.244
276645AC1-214 GEN1
Solar/Wind Harmer
1.39
276157O29GEN1
Solar/Wind Harmer
3.871
270043AE2-236 GEN
Solar/Wind Harmer
0.178
961491AF2-440 GEN
Solar/Wind Helper
0.191
274861TOP CROP ;1U
Solar/Wind Harmer
5.499
276655WTG1_EQ
Solar/Wind Harmer
8.088
971067AG2-660 GEN
Solar/Wind Harmer
1.807
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.098
270186AC1-089 GEN
Solar/Wind Helper
0.604
339231AF1-038_GEN
Solar/Wind Helper
0.186
270222AC2-111 GEN
Solar/Wind Helper
0.233
339250AF1-203 GEN
Solar/Wind Helper
0.056
950051AG9-018
External Queue
0.31534820795059204
955142J992
External Queue
0.6478373408317566
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
990742J1381
External Queue
1.0048468112945557
991112J1481
External Queue
1.0048468112945557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.012
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.814
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
NYPJM->LTFIMP_NY
CLTF
1.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.087
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.943
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.308
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.34
MECLTFEXP_MEC->PJM
CLTF
10.238
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67
WECLTFEXP_WEC->PJM
CLTF
2.934
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.797

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.0 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3290.12
MW Contribution:
0.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24344205RKG1
50/50
11.499
24697605MDL-3G C
Solar/Wind Harmer
5.166
270181AB1-006 GEN2
Solar/Wind Harmer
1.033
24385905FR-11G C
Solar/Wind Harmer
9.894
970193AG2-126 GEN
Solar/Wind Harmer
0.754
274887GEN-1.85
Solar/Wind Harmer
5.943
970833AG2-524 GEN
Solar/Wind Harmer
0.525
274853TWINGROVE;U1
Solar/Wind Harmer
7.199
959611AF2-252 GEN
Solar/Wind Harmer
1.864
270393AB1-087 CT1
50/50
2.594
270406AB1-088 CT1
50/50
2.594
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.745
971347AH1-153 GEN
Solar/Wind Harmer
0.248
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.482
939401AE1-172 GEN
Solar/Wind Harmer
19.009
276656WTG2_EQ
Solar/Wind Harmer
1.071
926823AC1-168 GEN
Solar/Wind Harmer
5.618
276615X2-022 GEN
Solar/Wind Harmer
2.054
274857EASY ROAD;U1
Solar/Wind Harmer
4.136
252507AC2-088 GEN
Solar/Wind Helper
0.376
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
3.444
276843GEN-1.7
Solar/Wind Harmer
0.639
958011AF2-095 GEN
Solar/Wind Harmer
0.694
276691AA1-018 GEN1
Solar/Wind Harmer
0.506
274854TWINGROVE;U2
Solar/Wind Harmer
7.199
965091AG1-374 GEN
Solar/Wind Harmer
1.398
958491AF2-143 GEN
Solar/Wind Harmer
0.699
943021AE2-325 GEN
Solar/Wind Harmer
2.814
276646AC1-214 GEN2
Solar/Wind Harmer
1.39
970819AG2-516 GEN
Solar/Wind Harmer
0.536
274878BISHOP HL;2U
Solar/Wind Harmer
3.471
965931AG1-462 GEN
Solar/Wind Harmer
1.073
339206AE1-143 GEN
Solar/Wind Helper
0.348
241972AD1-140 GEN
Solar/Wind Helper
0.537
24386205FR-12G C
Solar/Wind Harmer
5.254
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.66
970373AG2-245 GEN
Solar/Wind Harmer
1.201
276872AE1-163_GEN1
Solar/Wind Harmer
6.283
274872LEEDK;1U
Solar/Wind Harmer
8.599
276686W4-005 GEN3
Solar/Wind Harmer
2.737
276764AC1-053 GEN2
Solar/Wind Harmer
3.562
959081AF2-199 GEN
Solar/Wind Harmer
0.452
274851PROVIDENC;RU
Solar/Wind Harmer
2.59
276911AD2-131_GEN
Solar/Wind Harmer
0.222
25183208HLCRTG
Solar/Wind Helper
0.946
253325AC1-069 GEN
Solar/Wind Helper
0.133
960611AF2-352 GEN
Solar/Wind Harmer
1.864
276868AE1-113 GEN
Solar/Wind Harmer
10.861
962781AG1-127 GEN
Solar/Wind Harmer
0.438
971171AH1-044 GEN
Solar/Wind Harmer
0.904
946321AF1-296 GEN
Solar/Wind Harmer
12.624
270063AE2-323 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
0.908
339216AC1-074 GEN
Solar/Wind Helper
0.394
253415AE1-040 GEN
Solar/Wind Helper
0.149
970091AG2-072 GEN
50/50
217.153
270394AB1-087 ST1
50/50
2.594
970783AG2-492 GEN
50/50
2.649
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.435
963841AG1-237 GEN
Solar/Wind Harmer
19.253
971917AH1-482 GEN
Solar/Wind Harmer
9.588
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
5.499
276655WTG1_EQ
Solar/Wind Harmer
8.088
971067AG2-660 GEN
Solar/Wind Harmer
1.807
252509AD1-136 GEN
Solar/Wind Helper
0.054
339243AC2-075 GEN1
Solar/Wind Helper
0.098
270186AC1-089 GEN
Solar/Wind Helper
0.604
339231AF1-038_GEN
Solar/Wind Helper
0.186
270222AC2-111 GEN
Solar/Wind Helper
0.233
339250AF1-203 GEN
Solar/Wind Helper
0.056
270444AC2-157 GEN1
Solar/Wind Harmer
0
970539AG2-343 GEN
50/50
9.221
274871GR RIDGE ;2U
Solar/Wind Harmer
6.05
943121AE2-341 GEN
Solar/Wind Harmer
0.707
276785W4-005 GEN1
Solar/Wind Harmer
2.737
276849AB2-070 GEN2
Solar/Wind Harmer
2.347
957471AF2-041 GEN
Solar/Wind Harmer
1.355
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
5.214
970289AG2-191 GEN
Solar/Wind Harmer
0.404
970291AG2-192 GEN
Solar/Wind Harmer
0.22
252524AE2-267 GEN
Solar/Wind Helper
0.254
253317AC1-085 GEN4
Solar/Wind Helper
0.593
253432AC1-085 GEN2
Solar/Wind Helper
0.02
253400AC2-068 GEN
Solar/Wind Helper
0.064
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
14.852
276848AB2-070 GEN3
Solar/Wind Harmer
2.347
971341AH1-150 GEN
Solar/Wind Harmer
0.904
274877BISHOP HL;1U
Solar/Wind Harmer
3.471
253316AC1-085 GEN3
Solar/Wind Helper
0.593
253433AC1-085 GEN1
Solar/Wind Helper
0.376
253349AC2-067 GEN
Solar/Wind Helper
0.16
253343AC1-166 GEN
Solar/Wind Helper
0.133
970781AG2-491 GEN
Solar/Wind Harmer
0.662
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
19.994
970707AG2-453 GEN
Solar/Wind Harmer
1.346
970833AG2-524 GEN
Solar/Wind Harmer
4.2
958481AF2-142 GEN
Solar/Wind Harmer
0.705
274862TOP CROP ;2U
Solar/Wind Harmer
5.499
274879MINONK ;1U
Solar/Wind Harmer
7.24
971675AH1-338 GEN
Solar/Wind Harmer
0.819
965911AG1-460 GEN
Solar/Wind Harmer
1.067
339211AE2-254 GEN
Solar/Wind Helper
0.209
253406AD2-031_GEN
Solar/Wind Helper
0.184
970543AG2-345 GEN
50/50
4.61
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
3.444
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.633
970169AG2-114 GEN
Solar/Wind Harmer
0.473
943591AF1-030 GEN
Solar/Wind Harmer
0.471
276694AA1-018 GEN2
Solar/Wind Harmer
4.996
959341AF2-225 GEN
Solar/Wind Harmer
0.705
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.904
971087AG2-675 GEN
Solar/Wind Harmer
2.693
970291AG2-192 GEN
Solar/Wind Harmer
0.04
253303V4-073 C
Solar/Wind Helper
0.007
960071AF2-298 GEN
Solar/Wind Helper
0.168
253338AC1-165 GEN
Solar/Wind Helper
0.133
24387305FR-4G C
Solar/Wind Harmer
7.549
24386605FR-22G C
Solar/Wind Harmer
5.033
24387005FR-3G C
Solar/Wind Harmer
4.983
274888KELLY CRK;1U
Solar/Wind Harmer
6.582
276893AG1-478 C
Solar/Wind Harmer
0.382
274863CRW1-WTG
Solar/Wind Harmer
5.566
274864CRW2-WTG
Solar/Wind Harmer
5.566
274880W4-005 GEN4
Solar/Wind Harmer
2.737
276602WESTBROOK C
Solar/Wind Harmer
1.915
957891AF2-083 GEN
Solar/Wind Harmer
0.679
276603SUBLETTE C
Solar/Wind Harmer
0.896
270071AF1-092 GEN
Solar/Wind Harmer
0.566
252510AF1-249 C
Solar/Wind Helper
0.101
253394AE2-221_GEN
Solar/Wind Helper
0.581
253398AE2-221_GEN2
Solar/Wind Helper
0.581
339236AF1-050_GEN
Solar/Wind Helper
0.19
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
5.166
971997AH1-543 GEN
Solar/Wind Harmer
0.732
962691AG1-118 GEN
Solar/Wind Harmer
1.385
276889AE2-281 GEN
Solar/Wind Harmer
1.795
971993AH1-541 GEN
Solar/Wind Harmer
0.424
270505AE1-170 C O1
Solar/Wind Harmer
0.68
276621W2-048 GEN
Solar/Wind Harmer
6.539
942481AE2-261 GEN
Solar/Wind Harmer
1.329
276158O29GEN2
Solar/Wind Harmer
3.871
276708O09 GEN2
Solar/Wind Harmer
3.635
971549AH1-272 GEN
Solar/Wind Harmer
0.741
270367AC2-061_GEN
Solar/Wind Helper
0.466
962581AG1-107 GEN
Solar/Wind Helper
0.573
942601AE2-276 GEN
50/50
8.252
971605AH1-302 GEN
Solar/Wind Harmer
9.618
970241AG2-163 GEN
Solar/Wind Harmer
1.478
276897AD1-100 C
Solar/Wind Harmer
64.004
970941AG2-585 GEN
Solar/Wind Harmer
0.265
939741AE1-205 GEN
Solar/Wind Harmer
0.939
942111AE2-223 GEN
Solar/Wind Harmer
10.99
971771AH1-392 GEN
Solar/Wind Harmer
0.421
276805AD2-038 GEN
Solar/Wind Harmer
5.453
276174W4-005 GEN2
Solar/Wind Harmer
2.737
276668AB2-070 GEN1
Solar/Wind Harmer
2.347
970569AG2-363 GEN
Solar/Wind Harmer
1.369
276838X2-022 GEN2
Solar/Wind Harmer
0.244
276645AC1-214 GEN1
Solar/Wind Harmer
1.39
276157O29GEN1
Solar/Wind Harmer
3.871
270043AE2-236 GEN
Solar/Wind Harmer
0.178
961491AF2-440 GEN
Solar/Wind Helper
0.191
270100X2-052 CT1
50/50
1.29
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.864
970571AG2-364 GEN
Solar/Wind Harmer
0.913
274850MENDOTA H;RU
Solar/Wind Harmer
2.7
276863AD2-134 GEN
Solar/Wind Harmer
1.878
276861AD2-134 GEN
Solar/Wind Harmer
1.878
945111AF1-176 GEN
Solar/Wind Harmer
0.798
945111AF1-176 GEN
Solar/Wind Harmer
4.348
274856ECOGROVE ;U1
Solar/Wind Harmer
3.482
971681AH1-341 GEN
Solar/Wind Harmer
0.666
938861AE1-114 GEN
Solar/Wind Harmer
10.387
274858EASY ROAD;U2
Solar/Wind Harmer
4.136
24344205RKG1
50/50
11.499
270102X2-052 ST
50/50
1.396
970901AG2-562 GEN
50/50
5.29
24386405FR-21G C
Solar/Wind Harmer
5.033
972231SS25-0005
Solar/Wind Harmer
0.781
276876AE1-163_GEN2
Solar/Wind Harmer
6.283
276763AC1-053 GEN1
Solar/Wind Harmer
3.562
274855GSG-6 ;RU
Solar/Wind Harmer
3.884
971411AH1-196 GEN
Solar/Wind Harmer
0.682
961051AF2-396 GEN
Solar/Wind Harmer
0.897
961051AF2-396 GEN
Solar/Wind Harmer
7.174
276782AC1-033 GEN
Solar/Wind Harmer
3.499
944031AF1-071 GEN
Solar/Wind Helper
0.052
270407AB1-088 ST1
50/50
2.594
970023AG2-014 GEN
50/50
2.649
24344105CKG2
50/50
6.908
270101X2-052 CT2
50/50
1.29
270180AB1-006 GEN1
Solar/Wind Harmer
9.298
24791305MDL-5G
Solar/Wind Harmer
3.444
965791AG1-447 GEN
Solar/Wind Harmer
5.575
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
7.327
276882AE2-255 GEN
Solar/Wind Harmer
3.62
944221AF1-090 GEN
Solar/Wind Harmer
13.766
276741O09 GEN1
Solar/Wind Harmer
3.635
339221AD2-048_GEN
Solar/Wind Helper
0.34
270340AC2-060 GEN
Solar/Wind Helper
0.37
339255AE2-071 GEN
Solar/Wind Helper
0.098
270518AE2-148 GEN
Solar/Wind Helper
1.545
24344305RKG2
50/50
11.124
24344305RKG2
50/50
11.029
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.468
972181SS23-001
Solar/Wind Harmer
0.488
274847GR RIDGE ;BU
Solar/Wind Harmer
5.484
959091AF2-200 GEN
Solar/Wind Harmer
0.904
274849CRESCENT ;1U
Solar/Wind Harmer
1.906
957381AF2-032 GEN
Solar/Wind Harmer
0.089
276916AD2-100_GEN
Solar/Wind Harmer
0.932
970289AG2-191 GEN
Solar/Wind Harmer
0.058
943111AE2-339 GEN
Solar/Wind Helper
0.182
339241AF1-083 GEN
Solar/Wind Helper
0.19
253333AC1-068 GEN
Solar/Wind Helper
0.133
962211AG1-066 GEN
Solar/Wind Helper
0.207
950051AG9-018
External Queue
0.31534820795059204
955142J992
External Queue
0.6478373408317566
950031AG9-013
External Queue
6.458323955535889
950011AG9-010
External Queue
0.3960358500480652
950041AG9-017
External Queue
0.25647246837615967
991082J1475 G
External Queue
0.3523593246936798
991312J1772
External Queue
0.7026745080947876
990742J1381
External Queue
1.0048468112945557
991112J1481
External Queue
1.0048468112945557
NYPJM->LTFIMP_NY
CLTF
1.156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.087
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.943
AH1-155LTFEXP_AH1-155->PJM
LTF
0.308
WECLTFEXP_WEC->PJM
CLTF
2.934
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.797
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.012
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.814
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
AG2-052LTFEXP_AG2-052->PJM
LTF
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.308
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.34
MECLTFEXP_MEC->PJM
CLTF
10.238
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.67

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.19 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5615.13
MW Contribution:
1.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
19.594
24307105BERRINSP G
50/50
0.047
270505AE1-170 C O1
Solar/Wind Harmer
1.915
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.586
24691005MDL-2G C
Solar/Wind Harmer
9.252
971997AH1-543 GEN
Solar/Wind Harmer
1.864
276889AE2-281 GEN
Solar/Wind Harmer
4.568
971549AH1-272 GEN
Solar/Wind Harmer
2.119
276158O29GEN2
Solar/Wind Harmer
9.962
276708O09 GEN2
Solar/Wind Harmer
9.356
965021AG1-366 GEN
Solar/Wind Harmer
4.406
971993AH1-541 GEN
Solar/Wind Harmer
0.971
958861AF2-177 GEN
Solar/Wind Harmer
32.514
276621W2-048 GEN
Solar/Wind Harmer
14.904
942221AE2-234 GEN
Solar/Wind Harmer
0.357
942481AE2-261 GEN
Solar/Wind Harmer
2.986
945371AF1-202 GEN
Solar/Wind Harmer
15.509
270032AE2-172
Solar/Wind Harmer
7.806
970825AG2-519 GEN
Solar/Wind Harmer
3.715
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.656
270543AE2-219 C
Solar/Wind Harmer
0.721
247607V1-011 GEN
Solar/Wind Harmer
5.418
270435AC2-044 GEN
Solar/Wind Harmer
0.138
24643105BUCHANAN
50/50
0.028
274887GEN-1.85
Solar/Wind Harmer
15.299
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.35
970031AG2-029 GEN
Solar/Wind Harmer
3.022
962781AG1-127 GEN
Solar/Wind Harmer
1.134
24697605MDL-3G C
Solar/Wind Harmer
9.252
270181AB1-006 GEN2
Solar/Wind Harmer
1.85
276868AE1-113 GEN
Solar/Wind Harmer
27.735
971171AH1-044 GEN
Solar/Wind Harmer
2.34
24385905FR-11G C
Solar/Wind Harmer
17.58
274853TWINGROVE;U1
Solar/Wind Harmer
17.103
959611AF2-252 GEN
Solar/Wind Harmer
4.43
960611AF2-352 GEN
Solar/Wind Harmer
4.43
946321AF1-296 GEN
Solar/Wind Harmer
32.747
960971AF2-388 GEN
Solar/Wind Harmer
33.297
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.462
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.721
970521AG2-332 GEN
50/50
25.194
276806AD2-047 C O1
Solar/Wind Harmer
38.236
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.34
274877BISHOP HL;1U
Solar/Wind Harmer
8.781
276848AB2-070 GEN3
Solar/Wind Harmer
5.38
270444AC2-157 GEN1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.732
274775LINCOLN ;6U
50/50
19.594
970349AG2-230 GEN
Solar/Wind Harmer
2.066
971347AH1-153 GEN
Solar/Wind Harmer
0.689
960591AF2-350 GEN
Solar/Wind Harmer
1.241
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
47.612
926823AC1-168 GEN
Solar/Wind Harmer
14.207
274857EASY ROAD;U1
Solar/Wind Harmer
10.718
276656WTG2_EQ
Solar/Wind Harmer
2.567
276615X2-022 GEN
Solar/Wind Harmer
4.681
24725505WLD G2 C
Solar/Wind Harmer
7.118
965051AG1-369 GEN
Solar/Wind Harmer
0.436
961761AG1-017 GEN
Solar/Wind Harmer
0.84
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.286
958091AF2-103 GEN
Solar/Wind Harmer
0
24653605MOTTVILLE
50/50
0.008
957891AF2-083 GEN
Solar/Wind Harmer
1.911
270071AF1-092 GEN
Solar/Wind Harmer
1.896
274888KELLY CRK;1U
Solar/Wind Harmer
16.946
276893AG1-478 C
Solar/Wind Harmer
0.983
274863CRW1-WTG
Solar/Wind Harmer
13.812
274864CRW2-WTG
Solar/Wind Harmer
13.812
276602WESTBROOK C
Solar/Wind Harmer
4.959
24387305FR-4G C
Solar/Wind Harmer
13.414
24386605FR-22G C
Solar/Wind Harmer
8.942
24387005FR-3G C
Solar/Wind Harmer
8.853
276603SUBLETTE C
Solar/Wind Harmer
2.319
274880W4-005 GEN4
Solar/Wind Harmer
6.269
270005AE1-210 C O1
Solar/Wind Harmer
13.761
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.279
246936BC-WTG1
Solar/Wind Harmer
6.236
943021AE2-325 GEN
Solar/Wind Harmer
7.909
276843GEN-1.7
Solar/Wind Harmer
1.646
958011AF2-095 GEN
Solar/Wind Harmer
1.788
945421AF1-207 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.297
958491AF2-143 GEN
Solar/Wind Harmer
1.786
24697905MDL-4G C
Solar/Wind Harmer
6.168
970819AG2-516 GEN
Solar/Wind Harmer
1.391
276646AC1-214 GEN2
Solar/Wind Harmer
3.506
274878BISHOP HL;2U
Solar/Wind Harmer
8.781
274854TWINGROVE;U2
Solar/Wind Harmer
17.103
965091AG1-374 GEN
Solar/Wind Harmer
3.322
965931AG1-462 GEN
Solar/Wind Harmer
2.786
964611AG1-324 GEN
Solar/Wind Harmer
0.768
270491AE1-102 GEN2
Solar/Wind Harmer
0.09
270356AE2-297 GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
50/50
19.594
970373AG2-245 GEN
Solar/Wind Harmer
2.66
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
22.268
276872AE1-163_GEN1
Solar/Wind Harmer
15.988
959081AF2-199 GEN
Solar/Wind Harmer
1.17
24386205FR-12G C
Solar/Wind Harmer
9.336
274851PROVIDENC;RU
Solar/Wind Harmer
6.535
963741AG1-226 GEN
Solar/Wind Harmer
4.866
276686W4-005 GEN3
Solar/Wind Harmer
6.269
276764AC1-053 GEN2
Solar/Wind Harmer
8.149
276911AD2-131_GEN
Solar/Wind Harmer
0.495
270004AE1-209 GEN
Solar/Wind Harmer
13.761
270201AC2-176 GEN
Solar/Wind Harmer
8.644
24379505HDWTR1G C
Solar/Wind Harmer
12.238
970885AG2-551 GEN
Solar/Wind Harmer
2.885
270144AC1-141 ST1_
50/50
4.707
24642205MAYFLWER
50/50
1.638
962601AG1-109 GEN
50/50
6.313
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.337
274861TOP CROP ;1U
Solar/Wind Harmer
14.086
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
18.688
971067AG2-660 GEN
Solar/Wind Harmer
4.679
276655WTG1_EQ
Solar/Wind Harmer
19.386
963841AG1-237 GEN
Solar/Wind Harmer
34.712
959331AF2-224 GEN
Solar/Wind Harmer
1.101
965041AG1-368 GEN
Solar/Wind Harmer
0.951
270031AE2-169
Solar/Wind Harmer
0.772
24699105WLD G1 C
Solar/Wind Harmer
7.118
270383AD1-128 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
15.559
943121AE2-341 GEN
Solar/Wind Harmer
1.831
957471AF2-041 GEN
Solar/Wind Harmer
3.51
274848CAMPGROVE;RU
Solar/Wind Harmer
13.133
276785W4-005 GEN1
Solar/Wind Harmer
6.269
276849AB2-070 GEN2
Solar/Wind Harmer
5.38
970289AG2-191 GEN
Solar/Wind Harmer
1.334
970291AG2-192 GEN
Solar/Wind Harmer
0.728
270246TR4_N_V150
Solar/Wind Harmer
1.716
957201AF2-014 GEN
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.038
970707AG2-453 GEN
Solar/Wind Harmer
3.491
970833AG2-524 GEN
Solar/Wind Harmer
10.802
958481AF2-142 GEN
Solar/Wind Harmer
1.807
274862TOP CROP ;2U
Solar/Wind Harmer
14.086
970781AG2-491 GEN
Solar/Wind Harmer
1.186
274879MINONK ;1U
Solar/Wind Harmer
18.49
971675AH1-338 GEN
Solar/Wind Harmer
2.12
944531AF1-118 GEN
Solar/Wind Harmer
4.1
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.397
945391AF1-204 GEN
Solar/Wind Harmer
38.775
276903AD2-071 C
Solar/Wind Harmer
0.942
270247TR4_N_V136
Solar/Wind Harmer
1.716
270142AC1-141 CT1_
50/50
5.318
270143AC1-141 CT2_
50/50
5.318
24639705ELKHART HY
50/50
0.355
965681AG1-436 GEN
Solar/Wind Harmer
1.626
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.221
276694AA1-018 GEN2
Solar/Wind Harmer
12.798
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
6.168
971343AH1-151 GEN
Solar/Wind Harmer
2.34
970169AG2-114 GEN
Solar/Wind Harmer
1.163
959341AF2-225 GEN
Solar/Wind Harmer
1.689
971087AG2-675 GEN
Solar/Wind Harmer
6.993
970291AG2-192 GEN
Solar/Wind Harmer
0.131
963791AG1-232 GEN
Solar/Wind Harmer
1.357
270445AC2-157 GEN2
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
6.782
24695305TIMB G C
Solar/Wind Harmer
6.541
246937BC-WTG2
Solar/Wind Harmer
6.236
270459AD2-067 GEN
Solar/Wind Helper
0.77
274772LINCOLN ;3U
50/50
19.594
274774LINCOLN ;5U
50/50
19.594
944961AF1-161 GEN
50/50
6.313
971771AH1-392 GEN
Solar/Wind Harmer
1.164
270043AE2-236 GEN
Solar/Wind Harmer
0.701
970941AG2-585 GEN
Solar/Wind Harmer
0.683
276897AD1-100 C
Solar/Wind Harmer
163.988
971605AH1-302 GEN
Solar/Wind Harmer
18.338
276805AD2-038 GEN
Solar/Wind Harmer
13.931
970569AG2-363 GEN
Solar/Wind Harmer
3.474
276645AC1-214 GEN1
Solar/Wind Harmer
3.506
276157O29GEN1
Solar/Wind Harmer
9.962
939741AE1-205 GEN
Solar/Wind Harmer
2.252
942111AE2-223 GEN
Solar/Wind Harmer
26.343
970241AG2-163 GEN
Solar/Wind Harmer
2.703
276174W4-005 GEN2
Solar/Wind Harmer
6.269
276668AB2-070 GEN1
Solar/Wind Harmer
5.38
276838X2-022 GEN2
Solar/Wind Harmer
0.556
970825AG2-519 GEN
Solar/Wind Harmer
0.58
270007AE1-245 C
Solar/Wind Harmer
7.597
246938BC-WTG3
Solar/Wind Harmer
6.344
270100X2-052 CT1
50/50
3.322
274770LINCOLN ;1U
50/50
19.594
274771LINCOLN ;2U
50/50
19.594
945111AF1-176 GEN
Solar/Wind Harmer
2.262
945111AF1-176 GEN
Solar/Wind Harmer
12.331
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.763
274850MENDOTA H;RU
Solar/Wind Harmer
6.991
276863AD2-134 GEN
Solar/Wind Harmer
4.863
276861AD2-134 GEN
Solar/Wind Harmer
4.863
970571AG2-364 GEN
Solar/Wind Harmer
2.316
274856ECOGROVE ;U1
Solar/Wind Harmer
9.025
971681AH1-341 GEN
Solar/Wind Harmer
1.725
938861AE1-114 GEN
Solar/Wind Harmer
26.903
274858EASY ROAD;U2
Solar/Wind Harmer
10.718
965011AG1-365 GEN
Solar/Wind Harmer
1.101
270594AE1-207 GEN
Solar/Wind Harmer
1.561
270240V3-007_GEN2
Solar/Wind Harmer
9.582
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.09
270102X2-052 ST
50/50
3.595
970901AG2-562 GEN
50/50
13.622
24344005CKG1
50/50
15.603
274777LINCOLN ;8U
50/50
19.594
961051AF2-396 GEN
Solar/Wind Harmer
2.529
961051AF2-396 GEN
Solar/Wind Harmer
20.232
972231SS25-0005
Solar/Wind Harmer
2.007
971411AH1-196 GEN
Solar/Wind Harmer
1.767
274855GSG-6 ;RU
Solar/Wind Harmer
10.056
276876AE1-163_GEN2
Solar/Wind Harmer
15.988
24386405FR-21G C
Solar/Wind Harmer
8.942
276782AC1-033 GEN
Solar/Wind Harmer
8.851
276763AC1-053 GEN1
Solar/Wind Harmer
8.149
270599AE1-208 GEN
Solar/Wind Harmer
0.772
971029AG2-637 GEN
Solar/Wind Harmer
0.988
270054AF2-122 C O1
Solar/Wind Helper
0.559
24344105CKG2
50/50
19.094
270101X2-052 CT2
50/50
3.322
965791AG1-447 GEN
Solar/Wind Harmer
14.312
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
16.653
24791305MDL-5G
Solar/Wind Harmer
6.168
276882AE2-255 GEN
Solar/Wind Harmer
9.245
276741O09 GEN1
Solar/Wind Harmer
9.356
276726Z2-087_GEN
Solar/Wind Harmer
17.562
944541AF1-119 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
30.092
270191TR4_S_V150
Solar/Wind Harmer
5.168
972207SS24-0001
Solar/Wind Harmer
3.817
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
1.254
274847GR RIDGE ;BU
Solar/Wind Harmer
14.105
959091AF2-200 GEN
Solar/Wind Harmer
2.34
274849CRESCENT ;1U
Solar/Wind Harmer
4.808
965651AG1-433 GEN
Solar/Wind Harmer
16.648
970289AG2-191 GEN
Solar/Wind Harmer
0.192
957381AF2-032 GEN
Solar/Wind Harmer
0.2
276916AD2-100_GEN
Solar/Wind Harmer
2.081
946031AF1-268 GEN
Solar/Wind Harmer
0.712
965421AG1-410 GEN
Solar/Wind Harmer
2.186
270349AD2-093_GEN
Solar/Wind Helper
0.732
CBM West 1LTFEXP_CBM-W1->PJM
CBM
234.012
LGEELTFEXP_LGEE->PJM
CLTF
3.98
TVALTFEXP_TVA->PJM
CLTF
5.131
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
50.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
137.069
WECLTFEXP_WEC->PJM
CLTF
7.629
MECLTFEXP_MEC->PJM
CLTF
27.64
AG2-052LTFEXP_AG2-052->PJM
LTF
0.475
NYPJM->LTFIMP_NY
CLTF
3.691
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.716
SIGELTFEXP_SIGE->PJM
CLTF
0.533
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.712
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.521
LAGNLTFEXP_LAGN->PJM
CLTF
14.07
AH1-155LTFEXP_AH1-155->PJM
LTF
0.713

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.69 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5144.06
MW Contribution:
1.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
18.14
970349AG2-230 GEN
Solar/Wind Harmer
1.922
971347AH1-153 GEN
Solar/Wind Harmer
0.641
960591AF2-350 GEN
Solar/Wind Harmer
1.148
939351AE1-166 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
43.942
926823AC1-168 GEN
Solar/Wind Harmer
13.12
274857EASY ROAD;U1
Solar/Wind Harmer
9.917
276656WTG2_EQ
Solar/Wind Harmer
2.36
276615X2-022 GEN
Solar/Wind Harmer
4.283
24725505WLD G2 C
Solar/Wind Harmer
6.849
961761AG1-017 GEN
Solar/Wind Harmer
0.831
965051AG1-369 GEN
Solar/Wind Harmer
0.417
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.279
958091AF2-103 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
7.365
276843GEN-1.7
Solar/Wind Harmer
1.523
958011AF2-095 GEN
Solar/Wind Harmer
1.654
276691AA1-018 GEN1
Solar/Wind Harmer
1.199
958491AF2-143 GEN
Solar/Wind Harmer
1.651
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.287
24697905MDL-4G C
Solar/Wind Harmer
5.509
276646AC1-214 GEN2
Solar/Wind Harmer
3.237
274878BISHOP HL;2U
Solar/Wind Harmer
8.109
274854TWINGROVE;U2
Solar/Wind Harmer
15.712
965091AG1-374 GEN
Solar/Wind Harmer
3.052
965931AG1-462 GEN
Solar/Wind Harmer
2.578
964611AG1-324 GEN
Solar/Wind Harmer
0.76
270356AE2-297 GEN
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.086
270144AC1-141 ST1_
50/50
4.385
24642205MAYFLWER
50/50
1.524
962601AG1-109 GEN
50/50
5.878
247620Y3-023
50/50
0.982
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.5
274861TOP CROP ;1U
Solar/Wind Harmer
13.024
971067AG2-660 GEN
Solar/Wind Harmer
4.33
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
16.693
959331AF2-224 GEN
Solar/Wind Harmer
1.053
276655WTG1_EQ
Solar/Wind Harmer
17.823
963841AG1-237 GEN
Solar/Wind Harmer
31.024
270031AE2-169
Solar/Wind Harmer
0.756
965041AG1-368 GEN
Solar/Wind Harmer
0.91
24699105WLD G1 C
Solar/Wind Harmer
6.849
270383AD1-128 GEN
Solar/Wind Harmer
0
24643105BUCHANAN
50/50
0.026
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
14.152
970031AG2-029 GEN
Solar/Wind Harmer
2.845
970833AG2-524 GEN
Solar/Wind Harmer
1.249
962781AG1-127 GEN
Solar/Wind Harmer
1.049
276868AE1-113 GEN
Solar/Wind Harmer
25.637
971171AH1-044 GEN
Solar/Wind Harmer
2.165
24697605MDL-3G C
Solar/Wind Harmer
8.264
270181AB1-006 GEN2
Solar/Wind Harmer
1.653
960971AF2-388 GEN
Solar/Wind Harmer
32.614
24385905FR-11G C
Solar/Wind Harmer
15.687
946321AF1-296 GEN
Solar/Wind Harmer
30.3
274853TWINGROVE;U1
Solar/Wind Harmer
15.712
959611AF2-252 GEN
Solar/Wind Harmer
4.069
960611AF2-352 GEN
Solar/Wind Harmer
4.069
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.317
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.728
970521AG2-332 GEN
50/50
23.519
276806AD2-047 C O1
Solar/Wind Harmer
35.37
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.165
274877BISHOP HL;1U
Solar/Wind Harmer
8.109
276848AB2-070 GEN3
Solar/Wind Harmer
4.926
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.722
270142AC1-141 CT1_
50/50
4.953
270143AC1-141 CT2_
50/50
4.953
24639705ELKHART HY
50/50
0.331
965681AG1-436 GEN
Solar/Wind Harmer
1.504
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.13
276694AA1-018 GEN2
Solar/Wind Harmer
11.833
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.165
970169AG2-114 GEN
Solar/Wind Harmer
1.072
24755605MDL-5G
Solar/Wind Harmer
5.509
959341AF2-225 GEN
Solar/Wind Harmer
1.553
971087AG2-675 GEN
Solar/Wind Harmer
6.471
963791AG1-232 GEN
Solar/Wind Harmer
1.31
970291AG2-192 GEN
Solar/Wind Harmer
0.124
247521TR3_G114
Solar/Wind Harmer
6.497
24695305TIMB G C
Solar/Wind Harmer
6.263
270445AC2-157 GEN2
Solar/Wind Harmer
0
274773LINCOLN ;4U
50/50
18.14
24307105BERRINSP G
50/50
0.043
270505AE1-170 C O1
Solar/Wind Harmer
1.783
962691AG1-118 GEN
Solar/Wind Harmer
3.318
971997AH1-543 GEN
Solar/Wind Harmer
1.723
276889AE2-281 GEN
Solar/Wind Harmer
4.221
957841AF2-078 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
1.975
24691005MDL-2G C
Solar/Wind Harmer
8.264
965021AG1-366 GEN
Solar/Wind Harmer
4.211
276158O29GEN2
Solar/Wind Harmer
9.213
276708O09 GEN2
Solar/Wind Harmer
8.652
958861AF2-177 GEN
Solar/Wind Harmer
31.906
942221AE2-234 GEN
Solar/Wind Harmer
0.346
945371AF1-202 GEN
Solar/Wind Harmer
15.277
971993AH1-541 GEN
Solar/Wind Harmer
0.889
276621W2-048 GEN
Solar/Wind Harmer
13.64
270032AE2-172
Solar/Wind Harmer
7.423
942481AE2-261 GEN
Solar/Wind Harmer
2.729
970825AG2-519 GEN
Solar/Wind Harmer
3.672
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.699
270543AE2-219 C
Solar/Wind Harmer
0.728
247607V1-011 GEN
Solar/Wind Harmer
5.196
270435AC2-044 GEN
Solar/Wind Harmer
0.132
274772LINCOLN ;3U
50/50
18.14
274774LINCOLN ;5U
50/50
18.14
944961AF1-161 GEN
50/50
5.878
270043AE2-236 GEN
Solar/Wind Harmer
0.666
971771AH1-392 GEN
Solar/Wind Harmer
1.083
970941AG2-585 GEN
Solar/Wind Harmer
0.632
276897AD1-100 C
Solar/Wind Harmer
151.637
276805AD2-038 GEN
Solar/Wind Harmer
12.877
971605AH1-302 GEN
Solar/Wind Harmer
16.497
970569AG2-363 GEN
Solar/Wind Harmer
3.209
276157O29GEN1
Solar/Wind Harmer
9.213
276645AC1-214 GEN1
Solar/Wind Harmer
3.237
939741AE1-205 GEN
Solar/Wind Harmer
2.07
942111AE2-223 GEN
Solar/Wind Harmer
24.22
970241AG2-163 GEN
Solar/Wind Harmer
2.42
276174W4-005 GEN2
Solar/Wind Harmer
5.74
276668AB2-070 GEN1
Solar/Wind Harmer
4.926
276838X2-022 GEN2
Solar/Wind Harmer
0.509
970825AG2-519 GEN
Solar/Wind Harmer
0.573
270007AE1-245 C
Solar/Wind Harmer
7.285
246938BC-WTG3
Solar/Wind Harmer
6.065
270102X2-052 ST
50/50
3.326
970901AG2-562 GEN
50/50
12.603
24344005CKG1
50/50
14.512
274777LINCOLN ;8U
50/50
18.14
961051AF2-396 GEN
Solar/Wind Harmer
2.356
961051AF2-396 GEN
Solar/Wind Harmer
18.844
972231SS25-0005
Solar/Wind Harmer
1.856
971411AH1-196 GEN
Solar/Wind Harmer
1.635
274855GSG-6 ;RU
Solar/Wind Harmer
9.305
276876AE1-163_GEN2
Solar/Wind Harmer
14.773
276782AC1-033 GEN
Solar/Wind Harmer
8.174
24386405FR-21G C
Solar/Wind Harmer
7.979
276763AC1-053 GEN1
Solar/Wind Harmer
7.46
270599AE1-208 GEN
Solar/Wind Harmer
0.756
971029AG2-637 GEN
Solar/Wind Harmer
1.009
270100X2-052 CT1
50/50
3.074
274770LINCOLN ;1U
50/50
18.14
274771LINCOLN ;2U
50/50
18.14
945111AF1-176 GEN
Solar/Wind Harmer
2.108
945111AF1-176 GEN
Solar/Wind Harmer
11.49
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.402
940581AE2-045 GEN
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
6.469
276863AD2-134 GEN
Solar/Wind Harmer
4.499
276861AD2-134 GEN
Solar/Wind Harmer
4.499
274856ECOGROVE ;U1
Solar/Wind Harmer
8.351
970571AG2-364 GEN
Solar/Wind Harmer
2.139
971681AH1-341 GEN
Solar/Wind Harmer
1.596
938861AE1-114 GEN
Solar/Wind Harmer
24.893
274858EASY ROAD;U2
Solar/Wind Harmer
9.917
965011AG1-365 GEN
Solar/Wind Harmer
1.053
270594AE1-207 GEN
Solar/Wind Harmer
1.485
270240V3-007_GEN2
Solar/Wind Harmer
9.739
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.086
24653605MOTTVILLE
50/50
0.008
270071AF1-092 GEN
Solar/Wind Harmer
1.786
957891AF2-083 GEN
Solar/Wind Harmer
1.78
274888KELLY CRK;1U
Solar/Wind Harmer
15.676
276893AG1-478 C
Solar/Wind Harmer
0.909
276602WESTBROOK C
Solar/Wind Harmer
4.589
274863CRW1-WTG
Solar/Wind Harmer
12.737
274864CRW2-WTG
Solar/Wind Harmer
12.737
276603SUBLETTE C
Solar/Wind Harmer
2.146
24387305FR-4G C
Solar/Wind Harmer
11.969
24386605FR-22G C
Solar/Wind Harmer
7.979
24387005FR-3G C
Solar/Wind Harmer
7.9
274880W4-005 GEN4
Solar/Wind Harmer
5.74
270005AE1-210 C O1
Solar/Wind Harmer
13.697
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.264
246936BC-WTG1
Solar/Wind Harmer
5.962
246937BC-WTG2
Solar/Wind Harmer
5.962
24344105CKG2
50/50
17.764
270101X2-052 CT2
50/50
3.074
965791AG1-447 GEN
Solar/Wind Harmer
13.238
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
8.546
270180AB1-006 GEN1
Solar/Wind Harmer
14.875
274776LINCOLN ;7U
50/50
18.14
970373AG2-245 GEN
Solar/Wind Harmer
2.43
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
20.606
959081AF2-199 GEN
Solar/Wind Harmer
1.082
276872AE1-163_GEN1
Solar/Wind Harmer
14.773
274851PROVIDENC;RU
Solar/Wind Harmer
6.034
24386205FR-12G C
Solar/Wind Harmer
8.33
963741AG1-226 GEN
Solar/Wind Harmer
4.356
276686W4-005 GEN3
Solar/Wind Harmer
5.74
276764AC1-053 GEN2
Solar/Wind Harmer
7.46
276911AD2-131_GEN
Solar/Wind Harmer
0.453
270004AE1-209 GEN
Solar/Wind Harmer
13.697
270201AC2-176 GEN
Solar/Wind Harmer
8.545
24379505HDWTR1G C
Solar/Wind Harmer
12.438
970885AG2-551 GEN
Solar/Wind Harmer
2.911
972207SS24-0001
Solar/Wind Harmer
3.534
972181SS23-001
Solar/Wind Harmer
1.16
270055AF2-134 C O1
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
13.046
959091AF2-200 GEN
Solar/Wind Harmer
2.165
274849CRESCENT ;1U
Solar/Wind Harmer
4.44
965651AG1-433 GEN
Solar/Wind Harmer
16.307
970289AG2-191 GEN
Solar/Wind Harmer
0.181
957381AF2-032 GEN
Solar/Wind Harmer
0.183
276916AD2-100_GEN
Solar/Wind Harmer
1.901
946031AF1-268 GEN
Solar/Wind Harmer
0.706
965421AG1-410 GEN
Solar/Wind Harmer
2.09
270349AD2-093_GEN
Solar/Wind Helper
0.722
24641605TWIN BRNCH
50/50
0.035
970707AG2-453 GEN
Solar/Wind Harmer
3.232
944531AF1-118 GEN
Solar/Wind Harmer
3.989
970833AG2-524 GEN
Solar/Wind Harmer
9.992
958481AF2-142 GEN
Solar/Wind Harmer
1.671
274862TOP CROP ;2U
Solar/Wind Harmer
13.024
274879MINONK ;1U
Solar/Wind Harmer
17.091
971675AH1-338 GEN
Solar/Wind Harmer
1.962
970781AG2-491 GEN
Solar/Wind Harmer
1.059
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.19
276903AD2-071 C
Solar/Wind Harmer
0.899
945391AF1-204 GEN
Solar/Wind Harmer
34.921
270247TR4_N_V136
Solar/Wind Harmer
1.644
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
14.391
943121AE2-341 GEN
Solar/Wind Harmer
1.695
957471AF2-041 GEN
Solar/Wind Harmer
3.247
274848CAMPGROVE;RU
Solar/Wind Harmer
12.124
276785W4-005 GEN1
Solar/Wind Harmer
5.74
276849AB2-070 GEN2
Solar/Wind Harmer
4.926
970289AG2-191 GEN
Solar/Wind Harmer
1.255
970291AG2-192 GEN
Solar/Wind Harmer
0.684
270246TR4_N_V150
Solar/Wind Harmer
1.644
957201AF2-014 GEN
Solar/Wind Harmer
0
24791305MDL-5G
Solar/Wind Harmer
5.509
276741O09 GEN1
Solar/Wind Harmer
8.652
944541AF1-119 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
16.147
944221AF1-090 GEN
Solar/Wind Harmer
27.427
270191TR4_S_V150
Solar/Wind Harmer
4.951
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.347
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.307
LAGNLTFEXP_LAGN->PJM
CLTF
13.625
AH1-155LTFEXP_AH1-155->PJM
LTF
0.653
NYPJM->LTFIMP_NY
CLTF
3.51
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.586
SIGELTFEXP_SIGE->PJM
CLTF
0.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.183
WECLTFEXP_WEC->PJM
CLTF
7.061
MECLTFEXP_MEC->PJM
CLTF
25.64
AG2-052LTFEXP_AG2-052->PJM
LTF
0.436
CBM West 1LTFEXP_CBM-W1->PJM
CBM
218.246
LGEELTFEXP_LGEE->PJM
CLTF
5.512
TVALTFEXP_TVA->PJM
CLTF
5.176
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.752

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.1 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5114.58
MW Contribution:
1.69
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
19.36
970349AG2-230 GEN
Solar/Wind Harmer
2.07
971347AH1-153 GEN
Solar/Wind Harmer
0.69
943021AE2-325 GEN
Solar/Wind Harmer
7.925
276843GEN-1.7
Solar/Wind Harmer
1.622
958011AF2-095 GEN
Solar/Wind Harmer
1.762
945421AF1-207 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.273
958491AF2-143 GEN
Solar/Wind Harmer
1.749
24697905MDL-4G C
Solar/Wind Harmer
6.03
970819AG2-516 GEN
Solar/Wind Harmer
1.361
276646AC1-214 GEN2
Solar/Wind Harmer
3.406
274878BISHOP HL;2U
Solar/Wind Harmer
8.527
965931AG1-462 GEN
Solar/Wind Harmer
2.709
274854TWINGROVE;U2
Solar/Wind Harmer
16.378
965091AG1-374 GEN
Solar/Wind Harmer
3.181
964611AG1-324 GEN
Solar/Wind Harmer
0.776
270491AE1-102 GEN2
Solar/Wind Harmer
0.091
270356AE2-297 GEN
Solar/Wind Harmer
0
24643105BUCHANAN
50/50
0.028
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
15.078
970031AG2-029 GEN
Solar/Wind Harmer
3.032
970833AG2-524 GEN
Solar/Wind Harmer
1.328
962781AG1-127 GEN
Solar/Wind Harmer
1.113
276868AE1-113 GEN
Solar/Wind Harmer
27.147
24697605MDL-3G C
Solar/Wind Harmer
9.046
270181AB1-006 GEN2
Solar/Wind Harmer
1.809
971171AH1-044 GEN
Solar/Wind Harmer
2.292
24385905FR-11G C
Solar/Wind Harmer
16.916
960971AF2-388 GEN
Solar/Wind Harmer
33.501
946321AF1-296 GEN
Solar/Wind Harmer
31.858
274853TWINGROVE;U1
Solar/Wind Harmer
16.378
959611AF2-252 GEN
Solar/Wind Harmer
4.242
960611AF2-352 GEN
Solar/Wind Harmer
4.242
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.333
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.734
970521AG2-332 GEN
50/50
25.247
276806AD2-047 C O1
Solar/Wind Harmer
37.684
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.292
274877BISHOP HL;1U
Solar/Wind Harmer
8.527
276848AB2-070 GEN3
Solar/Wind Harmer
5.081
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.709
24307105BERRINSP G
50/50
0.047
274773LINCOLN ;4U
50/50
19.36
270505AE1-170 C O1
Solar/Wind Harmer
1.918
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.521
24691005MDL-2G C
Solar/Wind Harmer
9.046
971997AH1-543 GEN
Solar/Wind Harmer
1.823
971549AH1-272 GEN
Solar/Wind Harmer
2.128
276889AE2-281 GEN
Solar/Wind Harmer
4.462
965021AG1-366 GEN
Solar/Wind Harmer
4.438
276158O29GEN2
Solar/Wind Harmer
9.711
276708O09 GEN2
Solar/Wind Harmer
9.119
958861AF2-177 GEN
Solar/Wind Harmer
32.716
942221AE2-234 GEN
Solar/Wind Harmer
0.36
945371AF1-202 GEN
Solar/Wind Harmer
15.608
971993AH1-541 GEN
Solar/Wind Harmer
0.917
270032AE2-172
Solar/Wind Harmer
7.876
276621W2-048 GEN
Solar/Wind Harmer
14.021
942481AE2-261 GEN
Solar/Wind Harmer
2.785
970825AG2-519 GEN
Solar/Wind Harmer
3.741
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.694
270543AE2-219 C
Solar/Wind Harmer
0.734
247607V1-011 GEN
Solar/Wind Harmer
5.511
270435AC2-044 GEN
Solar/Wind Harmer
0.14
24653605MOTTVILLE
50/50
0.008
957891AF2-083 GEN
Solar/Wind Harmer
1.915
270071AF1-092 GEN
Solar/Wind Harmer
1.91
274888KELLY CRK;1U
Solar/Wind Harmer
16.701
276893AG1-478 C
Solar/Wind Harmer
0.967
276602WESTBROOK C
Solar/Wind Harmer
4.861
274863CRW1-WTG
Solar/Wind Harmer
13.439
274864CRW2-WTG
Solar/Wind Harmer
13.439
276603SUBLETTE C
Solar/Wind Harmer
2.266
24387305FR-4G C
Solar/Wind Harmer
12.907
24386605FR-22G C
Solar/Wind Harmer
8.604
24387005FR-3G C
Solar/Wind Harmer
8.518
274880W4-005 GEN4
Solar/Wind Harmer
5.919
270005AE1-210 C O1
Solar/Wind Harmer
13.854
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.292
246936BC-WTG1
Solar/Wind Harmer
6.341
246937BC-WTG2
Solar/Wind Harmer
6.341
270144AC1-141 ST1_
50/50
4.718
24642205MAYFLWER
50/50
1.639
962601AG1-109 GEN
50/50
6.326
247620Y3-023
50/50
1.053
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.13
274861TOP CROP ;1U
Solar/Wind Harmer
13.823
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
18.272
944961AF1-161 GEN
50/50
6.326
274772LINCOLN ;3U
50/50
19.36
274774LINCOLN ;5U
50/50
19.36
971771AH1-392 GEN
Solar/Wind Harmer
1.165
270043AE2-236 GEN
Solar/Wind Harmer
0.704
970941AG2-585 GEN
Solar/Wind Harmer
0.673
276897AD1-100 C
Solar/Wind Harmer
161.319
971605AH1-302 GEN
Solar/Wind Harmer
18.099
276805AD2-038 GEN
Solar/Wind Harmer
13.646
970569AG2-363 GEN
Solar/Wind Harmer
3.387
276157O29GEN1
Solar/Wind Harmer
9.711
276645AC1-214 GEN1
Solar/Wind Harmer
3.406
939741AE1-205 GEN
Solar/Wind Harmer
2.165
942111AE2-223 GEN
Solar/Wind Harmer
25.328
970241AG2-163 GEN
Solar/Wind Harmer
2.554
276174W4-005 GEN2
Solar/Wind Harmer
5.919
276668AB2-070 GEN1
Solar/Wind Harmer
5.081
276838X2-022 GEN2
Solar/Wind Harmer
0.523
970825AG2-519 GEN
Solar/Wind Harmer
0.584
270007AE1-245 C
Solar/Wind Harmer
7.728
246938BC-WTG3
Solar/Wind Harmer
6.451
972207SS24-0001
Solar/Wind Harmer
3.771
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
1.24
274847GR RIDGE ;BU
Solar/Wind Harmer
13.871
959091AF2-200 GEN
Solar/Wind Harmer
2.292
274849CRESCENT ;1U
Solar/Wind Harmer
4.671
965651AG1-433 GEN
Solar/Wind Harmer
16.751
970289AG2-191 GEN
Solar/Wind Harmer
0.194
957381AF2-032 GEN
Solar/Wind Harmer
0.187
276916AD2-100_GEN
Solar/Wind Harmer
1.936
946031AF1-268 GEN
Solar/Wind Harmer
0.718
965421AG1-410 GEN
Solar/Wind Harmer
2.22
270349AD2-093_GEN
Solar/Wind Helper
0.709
270102X2-052 ST
50/50
3.588
970901AG2-562 GEN
50/50
13.596
24344005CKG1
50/50
15.641
274777LINCOLN ;8U
50/50
19.36
961051AF2-396 GEN
Solar/Wind Harmer
2.534
961051AF2-396 GEN
Solar/Wind Harmer
20.273
972231SS25-0005
Solar/Wind Harmer
1.984
971411AH1-196 GEN
Solar/Wind Harmer
1.732
274855GSG-6 ;RU
Solar/Wind Harmer
9.856
276876AE1-163_GEN2
Solar/Wind Harmer
15.618
24386405FR-21G C
Solar/Wind Harmer
8.604
276782AC1-033 GEN
Solar/Wind Harmer
8.596
276763AC1-053 GEN1
Solar/Wind Harmer
7.686
270599AE1-208 GEN
Solar/Wind Harmer
0.777
971029AG2-637 GEN
Solar/Wind Harmer
1.009
24641605TWIN BRNCH
50/50
0.038
970707AG2-453 GEN
Solar/Wind Harmer
3.442
970833AG2-524 GEN
Solar/Wind Harmer
10.625
958481AF2-142 GEN
Solar/Wind Harmer
1.773
274862TOP CROP ;2U
Solar/Wind Harmer
13.823
944531AF1-118 GEN
Solar/Wind Harmer
4.124
274879MINONK ;1U
Solar/Wind Harmer
18.098
970781AG2-491 GEN
Solar/Wind Harmer
1.16
971675AH1-338 GEN
Solar/Wind Harmer
2.078
966841AG1-555 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.948
965911AG1-460 GEN
Solar/Wind Harmer
2.235
945391AF1-204 GEN
Solar/Wind Harmer
35.346
270247TR4_N_V136
Solar/Wind Harmer
1.736
270142AC1-141 CT1_
50/50
5.33
270143AC1-141 CT2_
50/50
5.33
24639705ELKHART HY
50/50
0.355
965681AG1-436 GEN
Solar/Wind Harmer
1.621
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.201
276694AA1-018 GEN2
Solar/Wind Harmer
12.56
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
6.03
971343AH1-151 GEN
Solar/Wind Harmer
2.292
970169AG2-114 GEN
Solar/Wind Harmer
1.128
959341AF2-225 GEN
Solar/Wind Harmer
1.624
971087AG2-675 GEN
Solar/Wind Harmer
6.799
970291AG2-192 GEN
Solar/Wind Harmer
0.133
963791AG1-232 GEN
Solar/Wind Harmer
1.369
247521TR3_G114
Solar/Wind Harmer
6.863
24695305TIMB G C
Solar/Wind Harmer
6.622
270445AC2-157 GEN2
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.224
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
46.474
926823AC1-168 GEN
Solar/Wind Harmer
13.842
274857EASY ROAD;U1
Solar/Wind Harmer
10.475
276656WTG2_EQ
Solar/Wind Harmer
2.468
276615X2-022 GEN
Solar/Wind Harmer
4.403
24725505WLD G2 C
Solar/Wind Harmer
7.152
965051AG1-369 GEN
Solar/Wind Harmer
0.441
961761AG1-017 GEN
Solar/Wind Harmer
0.849
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.391
958091AF2-103 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
15.301
943121AE2-341 GEN
Solar/Wind Harmer
1.802
957471AF2-041 GEN
Solar/Wind Harmer
3.438
274848CAMPGROVE;RU
Solar/Wind Harmer
12.74
970289AG2-191 GEN
Solar/Wind Harmer
1.347
970291AG2-192 GEN
Solar/Wind Harmer
0.735
276785W4-005 GEN1
Solar/Wind Harmer
5.919
276849AB2-070 GEN2
Solar/Wind Harmer
5.081
270246TR4_N_V150
Solar/Wind Harmer
1.736
957201AF2-014 GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
50/50
19.36
970373AG2-245 GEN
Solar/Wind Harmer
2.641
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
21.85
959081AF2-199 GEN
Solar/Wind Harmer
1.146
276872AE1-163_GEN1
Solar/Wind Harmer
15.618
24386205FR-12G C
Solar/Wind Harmer
8.983
274851PROVIDENC;RU
Solar/Wind Harmer
6.348
963741AG1-226 GEN
Solar/Wind Harmer
4.597
276686W4-005 GEN3
Solar/Wind Harmer
5.919
276764AC1-053 GEN2
Solar/Wind Harmer
7.686
276911AD2-131_GEN
Solar/Wind Harmer
0.461
270004AE1-209 GEN
Solar/Wind Harmer
13.854
270201AC2-176 GEN
Solar/Wind Harmer
8.734
24379505HDWTR1G C
Solar/Wind Harmer
12.413
970885AG2-551 GEN
Solar/Wind Harmer
2.937
24344105CKG2
50/50
19.181
270101X2-052 CT2
50/50
3.316
965791AG1-447 GEN
Solar/Wind Harmer
14.269
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
9.049
270180AB1-006 GEN1
Solar/Wind Harmer
16.282
24791305MDL-5G
Solar/Wind Harmer
6.03
276741O09 GEN1
Solar/Wind Harmer
9.119
276726Z2-087_GEN
Solar/Wind Harmer
16.885
944541AF1-119 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
27.731
270191TR4_S_V150
Solar/Wind Harmer
5.23
971067AG2-660 GEN
Solar/Wind Harmer
4.584
959331AF2-224 GEN
Solar/Wind Harmer
1.11
276655WTG1_EQ
Solar/Wind Harmer
18.638
963841AG1-237 GEN
Solar/Wind Harmer
33.096
965041AG1-368 GEN
Solar/Wind Harmer
0.961
270031AE2-169
Solar/Wind Harmer
0.777
24699105WLD G1 C
Solar/Wind Harmer
7.152
270383AD1-128 GEN
Solar/Wind Harmer
0
270100X2-052 CT1
50/50
3.316
274770LINCOLN ;1U
50/50
19.36
274771LINCOLN ;2U
50/50
19.36
945111AF1-176 GEN
Solar/Wind Harmer
2.267
945111AF1-176 GEN
Solar/Wind Harmer
12.356
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.665
274850MENDOTA H;RU
Solar/Wind Harmer
6.853
276863AD2-134 GEN
Solar/Wind Harmer
4.766
276861AD2-134 GEN
Solar/Wind Harmer
4.766
274856ECOGROVE ;U1
Solar/Wind Harmer
8.831
970571AG2-364 GEN
Solar/Wind Harmer
2.258
971681AH1-341 GEN
Solar/Wind Harmer
1.687
938861AE1-114 GEN
Solar/Wind Harmer
26.302
274858EASY ROAD;U2
Solar/Wind Harmer
10.475
965011AG1-365 GEN
Solar/Wind Harmer
1.11
270594AE1-207 GEN
Solar/Wind Harmer
1.575
270240V3-007_GEN2
Solar/Wind Harmer
9.719
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.218
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.445
LAGNLTFEXP_LAGN->PJM
CLTF
13.263
AH1-155LTFEXP_AH1-155->PJM
LTF
0.698
NYPJM->LTFIMP_NY
CLTF
3.513
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.679
SIGELTFEXP_SIGE->PJM
CLTF
0.501
CBM West 2LTFEXP_CBM-W2->PJM
CBM
127.984
WECLTFEXP_WEC->PJM
CLTF
7.473
MECLTFEXP_MEC->PJM
CLTF
26.605
AG2-052LTFEXP_AG2-052->PJM
LTF
0.465
CBM West 1LTFEXP_CBM-W1->PJM
CBM
229.695
LGEELTFEXP_LGEE->PJM
CLTF
4.399
TVALTFEXP_TVA->PJM
CLTF
4.838
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
52.01

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5065.25
MW Contribution:
1.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
18.189
970349AG2-230 GEN
Solar/Wind Harmer
1.927
971347AH1-153 GEN
Solar/Wind Harmer
0.642
960591AF2-350 GEN
Solar/Wind Harmer
1.152
939351AE1-166 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
44.067
926823AC1-168 GEN
Solar/Wind Harmer
13.159
274857EASY ROAD;U1
Solar/Wind Harmer
9.947
276656WTG2_EQ
Solar/Wind Harmer
2.367
276615X2-022 GEN
Solar/Wind Harmer
4.298
24725505WLD G2 C
Solar/Wind Harmer
6.873
961761AG1-017 GEN
Solar/Wind Harmer
0.834
965051AG1-369 GEN
Solar/Wind Harmer
0.419
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.309
958091AF2-103 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
14.431
943121AE2-341 GEN
Solar/Wind Harmer
1.699
957471AF2-041 GEN
Solar/Wind Harmer
3.257
274848CAMPGROVE;RU
Solar/Wind Harmer
12.161
276785W4-005 GEN1
Solar/Wind Harmer
5.759
276849AB2-070 GEN2
Solar/Wind Harmer
4.942
970289AG2-191 GEN
Solar/Wind Harmer
1.259
970291AG2-192 GEN
Solar/Wind Harmer
0.687
270246TR4_N_V150
Solar/Wind Harmer
1.65
957201AF2-014 GEN
Solar/Wind Harmer
0
24641605TWIN BRNCH
50/50
0.036
970707AG2-453 GEN
Solar/Wind Harmer
3.24
944531AF1-118 GEN
Solar/Wind Harmer
4
970833AG2-524 GEN
Solar/Wind Harmer
10.019
958481AF2-142 GEN
Solar/Wind Harmer
1.675
274862TOP CROP ;2U
Solar/Wind Harmer
13.061
274879MINONK ;1U
Solar/Wind Harmer
17.14
971675AH1-338 GEN
Solar/Wind Harmer
1.967
970781AG2-491 GEN
Solar/Wind Harmer
1.063
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.198
276903AD2-071 C
Solar/Wind Harmer
0.902
945391AF1-204 GEN
Solar/Wind Harmer
35.046
270247TR4_N_V136
Solar/Wind Harmer
1.65
270142AC1-141 CT1_
50/50
4.966
274773LINCOLN ;4U
50/50
18.189
24307105BERRINSP G
50/50
0.044
270505AE1-170 C O1
Solar/Wind Harmer
1.788
962691AG1-118 GEN
Solar/Wind Harmer
3.328
971997AH1-543 GEN
Solar/Wind Harmer
1.728
276889AE2-281 GEN
Solar/Wind Harmer
4.233
957841AF2-078 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
1.981
24691005MDL-2G C
Solar/Wind Harmer
8.288
965021AG1-366 GEN
Solar/Wind Harmer
4.223
276158O29GEN2
Solar/Wind Harmer
9.24
276708O09 GEN2
Solar/Wind Harmer
8.678
958861AF2-177 GEN
Solar/Wind Harmer
32.004
942221AE2-234 GEN
Solar/Wind Harmer
0.347
945371AF1-202 GEN
Solar/Wind Harmer
15.326
971993AH1-541 GEN
Solar/Wind Harmer
0.892
276621W2-048 GEN
Solar/Wind Harmer
13.685
270032AE2-172
Solar/Wind Harmer
7.448
942481AE2-261 GEN
Solar/Wind Harmer
2.738
970825AG2-519 GEN
Solar/Wind Harmer
3.685
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.71
270543AE2-219 C
Solar/Wind Harmer
0.731
247607V1-011 GEN
Solar/Wind Harmer
5.22
270435AC2-044 GEN
Solar/Wind Harmer
0.132
270100X2-052 CT1
50/50
3.082
274770LINCOLN ;1U
50/50
18.189
274771LINCOLN ;2U
50/50
18.189
945111AF1-176 GEN
Solar/Wind Harmer
2.113
945111AF1-176 GEN
Solar/Wind Harmer
11.52
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.415
940581AE2-045 GEN
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
6.488
276863AD2-134 GEN
Solar/Wind Harmer
4.512
276861AD2-134 GEN
Solar/Wind Harmer
4.512
274856ECOGROVE ;U1
Solar/Wind Harmer
8.375
970571AG2-364 GEN
Solar/Wind Harmer
2.146
971681AH1-341 GEN
Solar/Wind Harmer
1.601
938861AE1-114 GEN
Solar/Wind Harmer
24.967
274858EASY ROAD;U2
Solar/Wind Harmer
9.947
965011AG1-365 GEN
Solar/Wind Harmer
1.056
270594AE1-207 GEN
Solar/Wind Harmer
1.49
270240V3-007_GEN2
Solar/Wind Harmer
9.777
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.086
943021AE2-325 GEN
Solar/Wind Harmer
7.384
276843GEN-1.7
Solar/Wind Harmer
1.527
958011AF2-095 GEN
Solar/Wind Harmer
1.658
276691AA1-018 GEN1
Solar/Wind Harmer
1.202
958491AF2-143 GEN
Solar/Wind Harmer
1.656
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.291
24697905MDL-4G C
Solar/Wind Harmer
5.525
276646AC1-214 GEN2
Solar/Wind Harmer
3.247
274878BISHOP HL;2U
Solar/Wind Harmer
8.133
274854TWINGROVE;U2
Solar/Wind Harmer
15.76
965091AG1-374 GEN
Solar/Wind Harmer
3.061
965931AG1-462 GEN
Solar/Wind Harmer
2.586
964611AG1-324 GEN
Solar/Wind Harmer
0.763
270356AE2-297 GEN
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.086
24344105CKG2
50/50
17.806
270101X2-052 CT2
50/50
3.082
965791AG1-447 GEN
Solar/Wind Harmer
13.273
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
8.57
270180AB1-006 GEN1
Solar/Wind Harmer
14.919
24791305MDL-5G
Solar/Wind Harmer
5.525
276741O09 GEN1
Solar/Wind Harmer
8.678
944541AF1-119 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
16.196
944221AF1-090 GEN
Solar/Wind Harmer
27.525
270191TR4_S_V150
Solar/Wind Harmer
4.97
270102X2-052 ST
50/50
3.334
970901AG2-562 GEN
50/50
12.636
24344005CKG1
50/50
14.55
274777LINCOLN ;8U
50/50
18.189
961051AF2-396 GEN
Solar/Wind Harmer
2.362
961051AF2-396 GEN
Solar/Wind Harmer
18.894
972231SS25-0005
Solar/Wind Harmer
1.861
971411AH1-196 GEN
Solar/Wind Harmer
1.64
274855GSG-6 ;RU
Solar/Wind Harmer
9.332
276876AE1-163_GEN2
Solar/Wind Harmer
14.816
276782AC1-033 GEN
Solar/Wind Harmer
8.199
24386405FR-21G C
Solar/Wind Harmer
8.004
276763AC1-053 GEN1
Solar/Wind Harmer
7.485
270599AE1-208 GEN
Solar/Wind Harmer
0.758
971029AG2-637 GEN
Solar/Wind Harmer
1.014
24643105BUCHANAN
50/50
0.026
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
14.191
970031AG2-029 GEN
Solar/Wind Harmer
2.853
970833AG2-524 GEN
Solar/Wind Harmer
1.252
962781AG1-127 GEN
Solar/Wind Harmer
1.052
276868AE1-113 GEN
Solar/Wind Harmer
25.71
971171AH1-044 GEN
Solar/Wind Harmer
2.171
24697605MDL-3G C
Solar/Wind Harmer
8.288
270181AB1-006 GEN2
Solar/Wind Harmer
1.658
960971AF2-388 GEN
Solar/Wind Harmer
32.712
24385905FR-11G C
Solar/Wind Harmer
15.735
946321AF1-296 GEN
Solar/Wind Harmer
30.393
274853TWINGROVE;U1
Solar/Wind Harmer
15.76
959611AF2-252 GEN
Solar/Wind Harmer
4.082
960611AF2-352 GEN
Solar/Wind Harmer
4.082
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.322
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.731
274776LINCOLN ;7U
50/50
18.189
970373AG2-245 GEN
Solar/Wind Harmer
2.436
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
20.665
959081AF2-199 GEN
Solar/Wind Harmer
1.086
276872AE1-163_GEN1
Solar/Wind Harmer
14.816
274851PROVIDENC;RU
Solar/Wind Harmer
6.052
24386205FR-12G C
Solar/Wind Harmer
8.356
963741AG1-226 GEN
Solar/Wind Harmer
4.37
276686W4-005 GEN3
Solar/Wind Harmer
5.759
276764AC1-053 GEN2
Solar/Wind Harmer
7.485
276911AD2-131_GEN
Solar/Wind Harmer
0.454
270004AE1-209 GEN
Solar/Wind Harmer
13.746
270201AC2-176 GEN
Solar/Wind Harmer
8.576
24379505HDWTR1G C
Solar/Wind Harmer
12.487
970885AG2-551 GEN
Solar/Wind Harmer
2.924
270143AC1-141 CT2_
50/50
4.966
24639705ELKHART HY
50/50
0.332
965681AG1-436 GEN
Solar/Wind Harmer
1.508
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.133
276694AA1-018 GEN2
Solar/Wind Harmer
11.866
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.171
970169AG2-114 GEN
Solar/Wind Harmer
1.075
24755605MDL-5G
Solar/Wind Harmer
5.525
959341AF2-225 GEN
Solar/Wind Harmer
1.557
971087AG2-675 GEN
Solar/Wind Harmer
6.491
963791AG1-232 GEN
Solar/Wind Harmer
1.314
970291AG2-192 GEN
Solar/Wind Harmer
0.124
247521TR3_G114
Solar/Wind Harmer
6.522
24695305TIMB G C
Solar/Wind Harmer
6.288
270445AC2-157 GEN2
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
3.543
972181SS23-001
Solar/Wind Harmer
1.163
270055AF2-134 C O1
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
13.082
959091AF2-200 GEN
Solar/Wind Harmer
2.171
274849CRESCENT ;1U
Solar/Wind Harmer
4.453
965651AG1-433 GEN
Solar/Wind Harmer
16.356
970289AG2-191 GEN
Solar/Wind Harmer
0.181
957381AF2-032 GEN
Solar/Wind Harmer
0.184
276916AD2-100_GEN
Solar/Wind Harmer
1.907
946031AF1-268 GEN
Solar/Wind Harmer
0.709
965421AG1-410 GEN
Solar/Wind Harmer
2.099
270349AD2-093_GEN
Solar/Wind Helper
0.718
970521AG2-332 GEN
50/50
23.582
276806AD2-047 C O1
Solar/Wind Harmer
35.467
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.171
274877BISHOP HL;1U
Solar/Wind Harmer
8.133
276848AB2-070 GEN3
Solar/Wind Harmer
4.942
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.718
24653605MOTTVILLE
50/50
0.008
270071AF1-092 GEN
Solar/Wind Harmer
1.791
957891AF2-083 GEN
Solar/Wind Harmer
1.784
274888KELLY CRK;1U
Solar/Wind Harmer
15.718
276893AG1-478 C
Solar/Wind Harmer
0.911
276602WESTBROOK C
Solar/Wind Harmer
4.602
274863CRW1-WTG
Solar/Wind Harmer
12.774
274864CRW2-WTG
Solar/Wind Harmer
12.774
276603SUBLETTE C
Solar/Wind Harmer
2.152
24387305FR-4G C
Solar/Wind Harmer
12.006
24386605FR-22G C
Solar/Wind Harmer
8.004
24387005FR-3G C
Solar/Wind Harmer
7.924
274880W4-005 GEN4
Solar/Wind Harmer
5.759
270005AE1-210 C O1
Solar/Wind Harmer
13.746
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.269
246936BC-WTG1
Solar/Wind Harmer
5.99
246937BC-WTG2
Solar/Wind Harmer
5.99
274772LINCOLN ;3U
50/50
18.189
274774LINCOLN ;5U
50/50
18.189
944961AF1-161 GEN
50/50
5.894
270043AE2-236 GEN
Solar/Wind Harmer
0.667
971771AH1-392 GEN
Solar/Wind Harmer
1.085
970941AG2-585 GEN
Solar/Wind Harmer
0.633
276897AD1-100 C
Solar/Wind Harmer
152.054
276805AD2-038 GEN
Solar/Wind Harmer
12.914
971605AH1-302 GEN
Solar/Wind Harmer
16.544
970569AG2-363 GEN
Solar/Wind Harmer
3.218
276157O29GEN1
Solar/Wind Harmer
9.24
276645AC1-214 GEN1
Solar/Wind Harmer
3.247
939741AE1-205 GEN
Solar/Wind Harmer
2.076
942111AE2-223 GEN
Solar/Wind Harmer
24.294
970241AG2-163 GEN
Solar/Wind Harmer
2.428
276174W4-005 GEN2
Solar/Wind Harmer
5.759
276668AB2-070 GEN1
Solar/Wind Harmer
4.942
276838X2-022 GEN2
Solar/Wind Harmer
0.51
970825AG2-519 GEN
Solar/Wind Harmer
0.575
270007AE1-245 C
Solar/Wind Harmer
7.32
246938BC-WTG3
Solar/Wind Harmer
6.094
270144AC1-141 ST1_
50/50
4.396
24642205MAYFLWER
50/50
1.528
962601AG1-109 GEN
50/50
5.894
247620Y3-023
50/50
0.985
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.549
274861TOP CROP ;1U
Solar/Wind Harmer
13.061
971067AG2-660 GEN
Solar/Wind Harmer
4.343
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
16.742
959331AF2-224 GEN
Solar/Wind Harmer
1.056
276655WTG1_EQ
Solar/Wind Harmer
17.878
963841AG1-237 GEN
Solar/Wind Harmer
31.122
270031AE2-169
Solar/Wind Harmer
0.758
965041AG1-368 GEN
Solar/Wind Harmer
0.913
24699105WLD G1 C
Solar/Wind Harmer
6.873
270383AD1-128 GEN
Solar/Wind Harmer
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.913
WECLTFEXP_WEC->PJM
CLTF
7.082
MECLTFEXP_MEC->PJM
CLTF
25.731
AG2-052LTFEXP_AG2-052->PJM
LTF
0.437
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.553
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.271
LAGNLTFEXP_LAGN->PJM
CLTF
13.735
AH1-155LTFEXP_AH1-155->PJM
LTF
0.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
219.037
LGEELTFEXP_LGEE->PJM
CLTF
5.55
TVALTFEXP_TVA->PJM
CLTF
5.231
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.752
NYPJM->LTFIMP_NY
CLTF
3.476
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.564
SIGELTFEXP_SIGE->PJM
CLTF
0.547

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.1 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5065.17
MW Contribution:
1.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24653605MOTTVILLE
50/50
0.008
270071AF1-092 GEN
Solar/Wind Harmer
1.791
957891AF2-083 GEN
Solar/Wind Harmer
1.784
274888KELLY CRK;1U
Solar/Wind Harmer
15.718
276893AG1-478 C
Solar/Wind Harmer
0.911
276602WESTBROOK C
Solar/Wind Harmer
4.602
274863CRW1-WTG
Solar/Wind Harmer
12.774
274864CRW2-WTG
Solar/Wind Harmer
12.774
276603SUBLETTE C
Solar/Wind Harmer
2.152
24387305FR-4G C
Solar/Wind Harmer
12.006
24386605FR-22G C
Solar/Wind Harmer
8.004
24387005FR-3G C
Solar/Wind Harmer
7.924
274880W4-005 GEN4
Solar/Wind Harmer
5.759
270005AE1-210 C O1
Solar/Wind Harmer
13.746
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.269
246936BC-WTG1
Solar/Wind Harmer
5.99
246937BC-WTG2
Solar/Wind Harmer
5.99
270102X2-052 ST
50/50
3.334
970901AG2-562 GEN
50/50
12.636
24344005CKG1
50/50
14.55
274777LINCOLN ;8U
50/50
18.189
961051AF2-396 GEN
Solar/Wind Harmer
2.362
961051AF2-396 GEN
Solar/Wind Harmer
18.894
972231SS25-0005
Solar/Wind Harmer
1.861
971411AH1-196 GEN
Solar/Wind Harmer
1.64
274855GSG-6 ;RU
Solar/Wind Harmer
9.332
276876AE1-163_GEN2
Solar/Wind Harmer
14.816
276782AC1-033 GEN
Solar/Wind Harmer
8.199
24386405FR-21G C
Solar/Wind Harmer
8.004
276763AC1-053 GEN1
Solar/Wind Harmer
7.485
270599AE1-208 GEN
Solar/Wind Harmer
0.758
971029AG2-637 GEN
Solar/Wind Harmer
1.014
24641605TWIN BRNCH
50/50
0.036
970707AG2-453 GEN
Solar/Wind Harmer
3.24
944531AF1-118 GEN
Solar/Wind Harmer
4
970833AG2-524 GEN
Solar/Wind Harmer
10.019
958481AF2-142 GEN
Solar/Wind Harmer
1.675
274862TOP CROP ;2U
Solar/Wind Harmer
13.061
274879MINONK ;1U
Solar/Wind Harmer
17.14
971675AH1-338 GEN
Solar/Wind Harmer
1.967
972207SS24-0001
Solar/Wind Harmer
3.543
972181SS23-001
Solar/Wind Harmer
1.163
270055AF2-134 C O1
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
13.082
959091AF2-200 GEN
Solar/Wind Harmer
2.171
274849CRESCENT ;1U
Solar/Wind Harmer
4.453
965651AG1-433 GEN
Solar/Wind Harmer
16.356
970289AG2-191 GEN
Solar/Wind Harmer
0.181
957381AF2-032 GEN
Solar/Wind Harmer
0.184
276916AD2-100_GEN
Solar/Wind Harmer
1.907
946031AF1-268 GEN
Solar/Wind Harmer
0.709
965421AG1-410 GEN
Solar/Wind Harmer
2.099
270349AD2-093_GEN
Solar/Wind Helper
0.718
970781AG2-491 GEN
Solar/Wind Harmer
1.063
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
2.198
276903AD2-071 C
Solar/Wind Harmer
0.902
945391AF1-204 GEN
Solar/Wind Harmer
35.046
270247TR4_N_V136
Solar/Wind Harmer
1.65
274775LINCOLN ;6U
50/50
18.189
970349AG2-230 GEN
Solar/Wind Harmer
1.927
971347AH1-153 GEN
Solar/Wind Harmer
0.642
960591AF2-350 GEN
Solar/Wind Harmer
1.152
939351AE1-166 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
44.067
926823AC1-168 GEN
Solar/Wind Harmer
13.159
274857EASY ROAD;U1
Solar/Wind Harmer
9.947
276656WTG2_EQ
Solar/Wind Harmer
2.367
276615X2-022 GEN
Solar/Wind Harmer
4.298
24725505WLD G2 C
Solar/Wind Harmer
6.873
961761AG1-017 GEN
Solar/Wind Harmer
0.834
965051AG1-369 GEN
Solar/Wind Harmer
0.419
926881AC1-175 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
7.309
958091AF2-103 GEN
Solar/Wind Harmer
0
270142AC1-141 CT1_
50/50
4.966
270143AC1-141 CT2_
50/50
4.966
24639705ELKHART HY
50/50
0.332
965681AG1-436 GEN
Solar/Wind Harmer
1.508
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.133
276694AA1-018 GEN2
Solar/Wind Harmer
11.866
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.171
970169AG2-114 GEN
Solar/Wind Harmer
1.075
24755605MDL-5G
Solar/Wind Harmer
5.525
959341AF2-225 GEN
Solar/Wind Harmer
1.557
971087AG2-675 GEN
Solar/Wind Harmer
6.491
963791AG1-232 GEN
Solar/Wind Harmer
1.314
970291AG2-192 GEN
Solar/Wind Harmer
0.124
247521TR3_G114
Solar/Wind Harmer
6.522
24695305TIMB G C
Solar/Wind Harmer
6.288
270445AC2-157 GEN2
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
14.431
943121AE2-341 GEN
Solar/Wind Harmer
1.699
957471AF2-041 GEN
Solar/Wind Harmer
3.257
274848CAMPGROVE;RU
Solar/Wind Harmer
12.161
276785W4-005 GEN1
Solar/Wind Harmer
5.759
276849AB2-070 GEN2
Solar/Wind Harmer
4.942
970289AG2-191 GEN
Solar/Wind Harmer
1.259
970291AG2-192 GEN
Solar/Wind Harmer
0.687
270246TR4_N_V150
Solar/Wind Harmer
1.65
957201AF2-014 GEN
Solar/Wind Harmer
0
24344105CKG2
50/50
17.806
270101X2-052 CT2
50/50
3.082
965791AG1-447 GEN
Solar/Wind Harmer
13.273
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
8.57
270180AB1-006 GEN1
Solar/Wind Harmer
14.919
24791305MDL-5G
Solar/Wind Harmer
5.525
276741O09 GEN1
Solar/Wind Harmer
8.678
944541AF1-119 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
16.196
944221AF1-090 GEN
Solar/Wind Harmer
27.525
270191TR4_S_V150
Solar/Wind Harmer
4.97
943021AE2-325 GEN
Solar/Wind Harmer
7.384
276843GEN-1.7
Solar/Wind Harmer
1.527
958011AF2-095 GEN
Solar/Wind Harmer
1.658
276691AA1-018 GEN1
Solar/Wind Harmer
1.202
958491AF2-143 GEN
Solar/Wind Harmer
1.656
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.291
24697905MDL-4G C
Solar/Wind Harmer
5.525
276646AC1-214 GEN2
Solar/Wind Harmer
3.247
274878BISHOP HL;2U
Solar/Wind Harmer
8.133
274854TWINGROVE;U2
Solar/Wind Harmer
15.76
965091AG1-374 GEN
Solar/Wind Harmer
3.061
965931AG1-462 GEN
Solar/Wind Harmer
2.586
964611AG1-324 GEN
Solar/Wind Harmer
0.763
270356AE2-297 GEN
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.086
24643105BUCHANAN
50/50
0.026
270063AE2-323 C
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
14.191
970031AG2-029 GEN
Solar/Wind Harmer
2.853
970833AG2-524 GEN
Solar/Wind Harmer
1.252
962781AG1-127 GEN
Solar/Wind Harmer
1.052
276868AE1-113 GEN
Solar/Wind Harmer
25.71
971171AH1-044 GEN
Solar/Wind Harmer
2.171
24697605MDL-3G C
Solar/Wind Harmer
8.288
270181AB1-006 GEN2
Solar/Wind Harmer
1.658
960971AF2-388 GEN
Solar/Wind Harmer
32.712
24385905FR-11G C
Solar/Wind Harmer
15.735
946321AF1-296 GEN
Solar/Wind Harmer
30.393
274853TWINGROVE;U1
Solar/Wind Harmer
15.76
959611AF2-252 GEN
Solar/Wind Harmer
4.082
960611AF2-352 GEN
Solar/Wind Harmer
4.082
945581AF1-223 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
1.322
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.731
270144AC1-141 ST1_
50/50
4.396
24642205MAYFLWER
50/50
1.528
962601AG1-109 GEN
50/50
5.894
247620Y3-023
50/50
0.985
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.549
274861TOP CROP ;1U
Solar/Wind Harmer
13.061
971067AG2-660 GEN
Solar/Wind Harmer
4.343
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
16.742
959331AF2-224 GEN
Solar/Wind Harmer
1.056
276655WTG1_EQ
Solar/Wind Harmer
17.878
963841AG1-237 GEN
Solar/Wind Harmer
31.122
270031AE2-169
Solar/Wind Harmer
0.758
965041AG1-368 GEN
Solar/Wind Harmer
0.913
24699105WLD G1 C
Solar/Wind Harmer
6.873
270383AD1-128 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
50/50
18.189
274774LINCOLN ;5U
50/50
18.189
944961AF1-161 GEN
50/50
5.894
270043AE2-236 GEN
Solar/Wind Harmer
0.667
971771AH1-392 GEN
Solar/Wind Harmer
1.085
970941AG2-585 GEN
Solar/Wind Harmer
0.633
276897AD1-100 C
Solar/Wind Harmer
152.054
276805AD2-038 GEN
Solar/Wind Harmer
12.914
971605AH1-302 GEN
Solar/Wind Harmer
16.544
970569AG2-363 GEN
Solar/Wind Harmer
3.218
276157O29GEN1
Solar/Wind Harmer
9.24
276645AC1-214 GEN1
Solar/Wind Harmer
3.247
939741AE1-205 GEN
Solar/Wind Harmer
2.076
942111AE2-223 GEN
Solar/Wind Harmer
24.294
970241AG2-163 GEN
Solar/Wind Harmer
2.428
276174W4-005 GEN2
Solar/Wind Harmer
5.759
276668AB2-070 GEN1
Solar/Wind Harmer
4.942
276838X2-022 GEN2
Solar/Wind Harmer
0.51
970825AG2-519 GEN
Solar/Wind Harmer
0.575
270007AE1-245 C
Solar/Wind Harmer
7.32
246938BC-WTG3
Solar/Wind Harmer
6.094
274773LINCOLN ;4U
50/50
18.189
24307105BERRINSP G
50/50
0.044
270505AE1-170 C O1
Solar/Wind Harmer
1.788
962691AG1-118 GEN
Solar/Wind Harmer
3.328
971997AH1-543 GEN
Solar/Wind Harmer
1.728
276889AE2-281 GEN
Solar/Wind Harmer
4.233
957841AF2-078 GEN
Solar/Wind Harmer
0
971549AH1-272 GEN
Solar/Wind Harmer
1.981
24691005MDL-2G C
Solar/Wind Harmer
8.288
965021AG1-366 GEN
Solar/Wind Harmer
4.223
276158O29GEN2
Solar/Wind Harmer
9.24
276708O09 GEN2
Solar/Wind Harmer
8.678
958861AF2-177 GEN
Solar/Wind Harmer
32.004
942221AE2-234 GEN
Solar/Wind Harmer
0.347
945371AF1-202 GEN
Solar/Wind Harmer
15.326
971993AH1-541 GEN
Solar/Wind Harmer
0.892
276621W2-048 GEN
Solar/Wind Harmer
13.685
270032AE2-172
Solar/Wind Harmer
7.448
942481AE2-261 GEN
Solar/Wind Harmer
2.738
970825AG2-519 GEN
Solar/Wind Harmer
3.685
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.71
270543AE2-219 C
Solar/Wind Harmer
0.731
247607V1-011 GEN
Solar/Wind Harmer
5.22
270435AC2-044 GEN
Solar/Wind Harmer
0.132
270100X2-052 CT1
50/50
3.082
274770LINCOLN ;1U
50/50
18.189
274771LINCOLN ;2U
50/50
18.189
945111AF1-176 GEN
Solar/Wind Harmer
2.113
945111AF1-176 GEN
Solar/Wind Harmer
11.52
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
4.415
940581AE2-045 GEN
Solar/Wind Harmer
0
274850MENDOTA H;RU
Solar/Wind Harmer
6.488
276863AD2-134 GEN
Solar/Wind Harmer
4.512
276861AD2-134 GEN
Solar/Wind Harmer
4.512
274856ECOGROVE ;U1
Solar/Wind Harmer
8.375
970571AG2-364 GEN
Solar/Wind Harmer
2.146
971681AH1-341 GEN
Solar/Wind Harmer
1.601
938861AE1-114 GEN
Solar/Wind Harmer
24.967
274858EASY ROAD;U2
Solar/Wind Harmer
9.947
965011AG1-365 GEN
Solar/Wind Harmer
1.056
270594AE1-207 GEN
Solar/Wind Harmer
1.49
270240V3-007_GEN2
Solar/Wind Harmer
9.777
270209AC1-174_GEN
Solar/Wind Harmer
0
270489AE1-102 GEN1
Solar/Wind Harmer
0.086
970521AG2-332 GEN
50/50
23.582
276806AD2-047 C O1
Solar/Wind Harmer
35.467
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.171
274877BISHOP HL;1U
Solar/Wind Harmer
8.133
276848AB2-070 GEN3
Solar/Wind Harmer
4.942
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270471AD2-092_GEN
Solar/Wind Helper
0.718
274776LINCOLN ;7U
50/50
18.189
970373AG2-245 GEN
Solar/Wind Harmer
2.436
964401AG1-302 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
20.665
959081AF2-199 GEN
Solar/Wind Harmer
1.086
276872AE1-163_GEN1
Solar/Wind Harmer
14.816
274851PROVIDENC;RU
Solar/Wind Harmer
6.052
24386205FR-12G C
Solar/Wind Harmer
8.356
963741AG1-226 GEN
Solar/Wind Harmer
4.37
276686W4-005 GEN3
Solar/Wind Harmer
5.759
276764AC1-053 GEN2
Solar/Wind Harmer
7.485
276911AD2-131_GEN
Solar/Wind Harmer
0.454
270004AE1-209 GEN
Solar/Wind Harmer
13.746
270201AC2-176 GEN
Solar/Wind Harmer
8.576
24379505HDWTR1G C
Solar/Wind Harmer
12.487
970885AG2-551 GEN
Solar/Wind Harmer
2.924
CBM West 2LTFEXP_CBM-W2->PJM
CBM
130.913
WECLTFEXP_WEC->PJM
CLTF
7.082
MECLTFEXP_MEC->PJM
CLTF
25.731
AG2-052LTFEXP_AG2-052->PJM
LTF
0.437
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.553
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.271
LAGNLTFEXP_LAGN->PJM
CLTF
13.735
AH1-155LTFEXP_AH1-155->PJM
LTF
0.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
219.037
LGEELTFEXP_LGEE->PJM
CLTF
5.55
TVALTFEXP_TVA->PJM
CLTF
5.231
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.752
NYPJM->LTFIMP_NY
CLTF
3.476
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.564
SIGELTFEXP_SIGE->PJM
CLTF
0.547

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.66 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2300.12
MW Contribution:
0.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
2.758
965051AG1-369 GEN
Solar/Wind Harmer
0.293
970349AG2-230 GEN
Solar/Wind Harmer
0.721
971347AH1-153 GEN
Solar/Wind Harmer
0.24
961761AG1-017 GEN
Solar/Wind Harmer
0.449
960591AF2-350 GEN
Solar/Wind Harmer
0.428
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
16.272
247536S-71 GEN
Solar/Wind Harmer
3.798
926823AC1-168 GEN
Solar/Wind Harmer
4.874
274857EASY ROAD;U1
Solar/Wind Harmer
3.688
24725505WLD G2 C
Solar/Wind Harmer
3.052
276656WTG2_EQ
Solar/Wind Harmer
0.874
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.587
270462AD2-086
Solar/Wind Helper
1.788
270317AD1-130_GEN
Solar/Wind Helper
1.166
270287AF1-227 GEN3
Solar/Wind Helper
0.35
943021AE2-325 GEN
Solar/Wind Harmer
2.95
964611AG1-324 GEN
Solar/Wind Harmer
0.402
276843GEN-1.7
Solar/Wind Harmer
0.568
958011AF2-095 GEN
Solar/Wind Harmer
0.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.447
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.615
24697905MDL-4G C
Solar/Wind Harmer
2.096
970819AG2-516 GEN
Solar/Wind Harmer
0.478
276646AC1-214 GEN2
Solar/Wind Harmer
1.204
274878BISHOP HL;2U
Solar/Wind Harmer
3.016
274854TWINGROVE;U2
Solar/Wind Harmer
5.82
965091AG1-374 GEN
Solar/Wind Harmer
1.13
965931AG1-462 GEN
Solar/Wind Harmer
0.961
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.995
270499AE1-146 GEN
Solar/Wind Helper
0.544
24727005RPMNG1
50/50
68.356
247620Y3-023
50/50
0.46
959331AF2-224 GEN
Solar/Wind Harmer
1.139
965041AG1-368 GEN
Solar/Wind Harmer
0.69
270031AE2-169
Solar/Wind Harmer
0.377
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.661
274861TOP CROP ;1U
Solar/Wind Harmer
4.856
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.349
971067AG2-660 GEN
Solar/Wind Harmer
1.608
24699105WLD G1 C
Solar/Wind Harmer
3.052
276655WTG1_EQ
Solar/Wind Harmer
6.603
963841AG1-237 GEN
Solar/Wind Harmer
11.714
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.285
247522W1-056 GEN
Solar/Wind Helper
1.919
270286AF1-227 GEN2
Solar/Wind Helper
0.35
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.296
970031AG2-029 GEN
Solar/Wind Harmer
1.74
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.381
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.278
970833AG2-524 GEN
Solar/Wind Harmer
0.463
962781AG1-127 GEN
Solar/Wind Harmer
0.389
276868AE1-113 GEN
Solar/Wind Harmer
9.54
24697605MDL-3G C
Solar/Wind Harmer
3.143
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.804
24385905FR-11G C
Solar/Wind Harmer
5.939
946321AF1-296 GEN
Solar/Wind Harmer
11.289
274853TWINGROVE;U1
Solar/Wind Harmer
5.82
959611AF2-252 GEN
Solar/Wind Harmer
1.507
960611AF2-352 GEN
Solar/Wind Harmer
1.507
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.365
970193AG2-126 GEN
Solar/Wind Harmer
0.491
958581AF2-149 GEN
Solar/Wind Helper
0.222
970521AG2-332 GEN
50/50
10.74
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.192
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.804
274877BISHOP HL;1U
Solar/Wind Harmer
3.016
276848AB2-070 GEN3
Solar/Wind Harmer
1.825
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.166
270471AD2-092_GEN
Solar/Wind Helper
0.454
276820AF1-078_GEN
Solar/Wind Helper
0.159
24727205RPMNG3
50/50
68.356
24639705ELKHART HY
50/50
0.148
963791AG1-232 GEN
Solar/Wind Harmer
0.988
247521TR3_G114
Solar/Wind Harmer
4.555
24695305TIMB G C
Solar/Wind Harmer
3.924
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.418
276694AA1-018 GEN2
Solar/Wind Harmer
4.411
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.096
971343AH1-151 GEN
Solar/Wind Harmer
0.804
970169AG2-114 GEN
Solar/Wind Harmer
0.397
959341AF2-225 GEN
Solar/Wind Harmer
0.575
971087AG2-675 GEN
Solar/Wind Harmer
2.412
270445AC2-157 GEN2
Solar/Wind Harmer
0
960851AF2-376 GEN
50/50
2.033
965021AG1-366 GEN
Solar/Wind Harmer
4.557
942221AE2-234 GEN
Solar/Wind Harmer
0.204
958861AF2-177 GEN
Solar/Wind Harmer
15.92
945371AF1-202 GEN
Solar/Wind Harmer
7.521
270505AE1-170 C O1
Solar/Wind Harmer
0.718
270032AE2-172
Solar/Wind Harmer
3.34
970825AG2-519 GEN
Solar/Wind Harmer
1.758
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.231
971997AH1-543 GEN
Solar/Wind Harmer
0.639
276889AE2-281 GEN
Solar/Wind Harmer
1.572
24691005MDL-2G C
Solar/Wind Harmer
3.143
971549AH1-272 GEN
Solar/Wind Harmer
0.722
276158O29GEN2
Solar/Wind Harmer
3.427
276708O09 GEN2
Solar/Wind Harmer
3.218
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.241
270543AE2-219 C
Solar/Wind Harmer
0.365
971993AH1-541 GEN
Solar/Wind Harmer
0.329
276621W2-048 GEN
Solar/Wind Harmer
5.054
942481AE2-261 GEN
Solar/Wind Harmer
1.011
270485AE1-090_GEN
Solar/Wind Helper
0.155
24729405KEY G3
50/50
6.841
24729505KEY G4
50/50
6.727
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.436
961051AF2-396 GEN
Solar/Wind Harmer
0.957
961051AF2-396 GEN
Solar/Wind Harmer
7.653
270599AE1-208 GEN
Solar/Wind Harmer
0.377
972231SS25-0005
Solar/Wind Harmer
0.703
971411AH1-196 GEN
Solar/Wind Harmer
0.607
274855GSG-6 ;RU
Solar/Wind Harmer
3.454
276876AE1-163_GEN2
Solar/Wind Harmer
5.502
24386405FR-21G C
Solar/Wind Harmer
3.021
276782AC1-033 GEN
Solar/Wind Harmer
3.04
276763AC1-053 GEN1
Solar/Wind Harmer
2.764
971029AG2-637 GEN
Solar/Wind Harmer
0.481
270224U2-072_GEN2
Solar/Wind Helper
1.995
942871AE2-306 GEN
Solar/Wind Helper
0.214
945641AF1-229 GEN
Solar/Wind Helper
0.454
270541AE2-072 C
Solar/Wind Helper
0.459
965011AG1-365 GEN
Solar/Wind Harmer
1.139
945111AF1-176 GEN
Solar/Wind Harmer
0.876
945111AF1-176 GEN
Solar/Wind Harmer
4.774
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.668
970073AG2-061 GEN
Solar/Wind Harmer
1.641
274850MENDOTA H;RU
Solar/Wind Harmer
2.401
276863AD2-134 GEN
Solar/Wind Harmer
1.67
276861AD2-134 GEN
Solar/Wind Harmer
1.67
970571AG2-364 GEN
Solar/Wind Harmer
0.796
274856ECOGROVE ;U1
Solar/Wind Harmer
3.104
971681AH1-341 GEN
Solar/Wind Harmer
0.593
938861AE1-114 GEN
Solar/Wind Harmer
9.255
274858EASY ROAD;U2
Solar/Wind Harmer
3.688
270240V3-007_GEN2
Solar/Wind Harmer
4.477
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.353
960861AF2-377 GEN
50/50
2.345
24729305KEY G2
50/50
6.841
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.937
957891AF2-083 GEN
Solar/Wind Harmer
0.723
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.683
274888KELLY CRK;1U
Solar/Wind Harmer
5.846
276893AG1-478 C
Solar/Wind Harmer
0.338
270005AE1-210 C O1
Solar/Wind Harmer
6.493
276602WESTBROOK C
Solar/Wind Harmer
1.703
274863CRW1-WTG
Solar/Wind Harmer
4.717
274864CRW2-WTG
Solar/Wind Harmer
4.717
276603SUBLETTE C
Solar/Wind Harmer
0.798
24387305FR-4G C
Solar/Wind Harmer
4.532
24386605FR-22G C
Solar/Wind Harmer
3.021
24387005FR-3G C
Solar/Wind Harmer
2.991
274880W4-005 GEN4
Solar/Wind Harmer
2.126
246936BC-WTG1
Solar/Wind Helper
17.073
246937BC-WTG2
Solar/Wind Helper
17.073
960841AF2-375 GEN
Solar/Wind Helper
0.563
24729205KEY G1
50/50
6.727
270201AC2-176 GEN
Solar/Wind Harmer
4.618
970941AG2-585 GEN
Solar/Wind Harmer
0.236
276897AD1-100 C
Solar/Wind Harmer
56.232
971605AH1-302 GEN
Solar/Wind Harmer
6.283
970825AG2-519 GEN
Solar/Wind Harmer
0.274
276805AD2-038 GEN
Solar/Wind Harmer
4.799
970569AG2-363 GEN
Solar/Wind Harmer
1.195
276157O29GEN1
Solar/Wind Harmer
3.427
276645AC1-214 GEN1
Solar/Wind Harmer
1.204
939741AE1-205 GEN
Solar/Wind Harmer
0.767
942111AE2-223 GEN
Solar/Wind Harmer
8.972
970241AG2-163 GEN
Solar/Wind Harmer
0.911
276174W4-005 GEN2
Solar/Wind Harmer
2.126
276668AB2-070 GEN1
Solar/Wind Harmer
1.825
276838X2-022 GEN2
Solar/Wind Harmer
0.188
246938BC-WTG3
Solar/Wind Helper
17.366
965651AG1-433 GEN
Solar/Wind Harmer
8.19
972181SS23-001
Solar/Wind Harmer
0.439
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.299
970289AG2-191 GEN
Solar/Wind Harmer
0.08
274847GR RIDGE ;BU
Solar/Wind Harmer
4.836
946031AF1-268 GEN
Solar/Wind Harmer
0.346
959091AF2-200 GEN
Solar/Wind Harmer
0.804
274849CRESCENT ;1U
Solar/Wind Harmer
1.651
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.704
270227U2-072_GEN3
Solar/Wind Helper
1.995
270228U2-072_GEN4
Solar/Wind Helper
1.995
270231U2-072_GEN5
Solar/Wind Helper
1.995
270349AD2-093_GEN
Solar/Wind Helper
0.454
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.152
944531AF1-118 GEN
Solar/Wind Harmer
2.052
970707AG2-453 GEN
Solar/Wind Harmer
1.192
970833AG2-524 GEN
Solar/Wind Harmer
3.705
958481AF2-142 GEN
Solar/Wind Harmer
0.623
274862TOP CROP ;2U
Solar/Wind Harmer
4.856
274879MINONK ;1U
Solar/Wind Harmer
6.36
971675AH1-338 GEN
Solar/Wind Harmer
0.728
970781AG2-491 GEN
Solar/Wind Harmer
0.403
276903AD2-071 C
Solar/Wind Harmer
0.399
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.811
945391AF1-204 GEN
Solar/Wind Harmer
13.018
270391AF1-285 GEN3
Solar/Wind Helper
0.285
241847AF2-150_GEN
Solar/Wind Helper
0.265
24727105RPMNG2
50/50
68.356
270246TR4_N_V150
Solar/Wind Harmer
1.152
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.556
970291AG2-192 GEN
Solar/Wind Harmer
0.303
274871GR RIDGE ;2U
Solar/Wind Harmer
5.335
943121AE2-341 GEN
Solar/Wind Harmer
0.627
957471AF2-041 GEN
Solar/Wind Harmer
1.206
274848CAMPGROVE;RU
Solar/Wind Harmer
4.509
276785W4-005 GEN1
Solar/Wind Harmer
2.126
276849AB2-070 GEN2
Solar/Wind Harmer
1.825
957201AF2-014 GEN
Solar/Wind Helper
3.942
270284AF1-227 GEN1
Solar/Wind Helper
0.948
270428AC2-015 C
Solar/Wind Helper
0.374
253383AE2-342_GEN
Solar/Wind Helper
0.103
970373AG2-245 GEN
Solar/Wind Harmer
0.924
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.493
274872LEEDK;1U
Solar/Wind Harmer
7.643
276872AE1-163_GEN1
Solar/Wind Harmer
5.502
959081AF2-199 GEN
Solar/Wind Harmer
0.402
274851PROVIDENC;RU
Solar/Wind Harmer
2.244
24386205FR-12G C
Solar/Wind Harmer
3.154
24379505HDWTR1G C
Solar/Wind Harmer
5.718
970885AG2-551 GEN
Solar/Wind Harmer
1.46
963741AG1-226 GEN
Solar/Wind Harmer
1.64
276686W4-005 GEN3
Solar/Wind Harmer
2.126
276764AC1-053 GEN2
Solar/Wind Harmer
2.764
276911AD2-131_GEN
Solar/Wind Harmer
0.168
270191TR4_S_V150
Solar/Wind Harmer
3.471
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.032
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.18
270180AB1-006 GEN1
Solar/Wind Harmer
5.658
24791305MDL-5G
Solar/Wind Harmer
2.096
276741O09 GEN1
Solar/Wind Harmer
3.218
276726Z2-087_GEN
Solar/Wind Harmer
5.982
944221AF1-090 GEN
Solar/Wind Harmer
10.146
966831AG1-554 GEN
Solar/Wind Helper
0.281
990792J1392
External Queue
0.3027859032154083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.873
TVALTFEXP_TVA->PJM
CLTF
2.36
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.443
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.204
NYPJM->LTFIMP_NY
CLTF
1.303
MECLTFEXP_MEC->PJM
CLTF
9.641
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.032
WECLTFEXP_WEC->PJM
CLTF
2.627
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.255
LGEELTFEXP_LGEE->PJM
CLTF
1.795
LAGNLTFEXP_LAGN->PJM
CLTF
5.817
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.06 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2242.58
MW Contribution:
0.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
24643105BUCHANAN
50/50
0.01
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.018
270143AC1-141 CT2_
50/50
2.018
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
944961AF1-161 GEN
50/50
2.385
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.787
24642205MAYFLWER
50/50
0.618
962601AG1-109 GEN
50/50
2.385
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
990792J1392
External Queue
0.30737584829330444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.53 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2230.82
MW Contribution:
0.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
990792J1392
External Queue
0.30737584829330444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.04 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2219.82
MW Contribution:
0.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
67.807
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.971
247521TR3_G114
Solar/Wind Harmer
4.44
24695305TIMB G C
Solar/Wind Harmer
3.811
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.053
943591AF1-030 GEN
Solar/Wind Harmer
0.407
970583AG2-370 GEN
50/50
2.702
965051AG1-369 GEN
Solar/Wind Harmer
0.285
970349AG2-230 GEN
Solar/Wind Harmer
0.704
971347AH1-153 GEN
Solar/Wind Harmer
0.235
961761AG1-017 GEN
Solar/Wind Harmer
0.438
960591AF2-350 GEN
Solar/Wind Harmer
0.417
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
15.839
247536S-71 GEN
Solar/Wind Harmer
3.697
926823AC1-168 GEN
Solar/Wind Harmer
4.742
274857EASY ROAD;U1
Solar/Wind Harmer
3.587
24725505WLD G2 C
Solar/Wind Harmer
2.968
276656WTG2_EQ
Solar/Wind Harmer
0.85
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.539
270462AD2-086
Solar/Wind Helper
1.865
270317AD1-130_GEN
Solar/Wind Helper
1.216
270287AF1-227 GEN3
Solar/Wind Helper
0.382
944531AF1-118 GEN
Solar/Wind Harmer
2.012
270247TR4_N_V136
Solar/Wind Harmer
1.123
970707AG2-453 GEN
Solar/Wind Harmer
1.161
970833AG2-524 GEN
Solar/Wind Harmer
3.609
958481AF2-142 GEN
Solar/Wind Harmer
0.607
274862TOP CROP ;2U
Solar/Wind Harmer
4.729
274879MINONK ;1U
Solar/Wind Harmer
6.19
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
276903AD2-071 C
Solar/Wind Harmer
0.388
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.786
945391AF1-204 GEN
Solar/Wind Harmer
12.593
270391AF1-285 GEN3
Solar/Wind Helper
0.3
241847AF2-150_GEN
Solar/Wind Helper
0.265
270191TR4_S_V150
Solar/Wind Harmer
3.383
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.91
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.095
270180AB1-006 GEN1
Solar/Wind Harmer
5.504
24791305MDL-5G
Solar/Wind Harmer
2.038
276741O09 GEN1
Solar/Wind Harmer
3.129
276726Z2-087_GEN
Solar/Wind Harmer
5.813
944221AF1-090 GEN
Solar/Wind Harmer
9.816
966831AG1-554 GEN
Solar/Wind Helper
0.286
943021AE2-325 GEN
Solar/Wind Harmer
2.881
964611AG1-324 GEN
Solar/Wind Harmer
0.393
276843GEN-1.7
Solar/Wind Harmer
0.553
958011AF2-095 GEN
Solar/Wind Harmer
0.601
276691AA1-018 GEN1
Solar/Wind Harmer
0.435
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
24697905MDL-4G C
Solar/Wind Harmer
2.038
970819AG2-516 GEN
Solar/Wind Harmer
0.465
276646AC1-214 GEN2
Solar/Wind Harmer
1.17
274878BISHOP HL;2U
Solar/Wind Harmer
2.932
965931AG1-462 GEN
Solar/Wind Harmer
0.934
274854TWINGROVE;U2
Solar/Wind Harmer
5.654
965091AG1-374 GEN
Solar/Wind Harmer
1.098
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
2.097
270499AE1-146 GEN
Solar/Wind Helper
0.556
970031AG2-029 GEN
Solar/Wind Harmer
1.71
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.032
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.144
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
276868AE1-113 GEN
Solar/Wind Harmer
9.286
24697605MDL-3G C
Solar/Wind Harmer
3.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.782
24385905FR-11G C
Solar/Wind Harmer
5.772
946321AF1-296 GEN
Solar/Wind Harmer
10.97
274853TWINGROVE;U1
Solar/Wind Harmer
5.654
959611AF2-252 GEN
Solar/Wind Harmer
1.464
960611AF2-352 GEN
Solar/Wind Harmer
1.464
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.354
970193AG2-126 GEN
Solar/Wind Harmer
0.475
958581AF2-149 GEN
Solar/Wind Helper
0.216
965021AG1-366 GEN
Solar/Wind Harmer
4.503
942221AE2-234 GEN
Solar/Wind Harmer
0.2
958861AF2-177 GEN
Solar/Wind Harmer
15.573
945371AF1-202 GEN
Solar/Wind Harmer
7.349
270505AE1-170 C O1
Solar/Wind Harmer
0.702
270032AE2-172
Solar/Wind Harmer
3.253
970825AG2-519 GEN
Solar/Wind Harmer
1.712
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.198
971997AH1-543 GEN
Solar/Wind Harmer
0.622
276889AE2-281 GEN
Solar/Wind Harmer
1.53
24691005MDL-2G C
Solar/Wind Harmer
3.058
971549AH1-272 GEN
Solar/Wind Harmer
0.702
276158O29GEN2
Solar/Wind Harmer
3.332
276708O09 GEN2
Solar/Wind Harmer
3.129
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.205
270543AE2-219 C
Solar/Wind Harmer
0.354
971993AH1-541 GEN
Solar/Wind Harmer
0.319
276621W2-048 GEN
Solar/Wind Harmer
4.9
942481AE2-261 GEN
Solar/Wind Harmer
0.979
270485AE1-090_GEN
Solar/Wind Helper
0.162
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.856
945111AF1-176 GEN
Solar/Wind Harmer
4.667
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.651
970073AG2-061 GEN
Solar/Wind Harmer
1.597
274850MENDOTA H;RU
Solar/Wind Harmer
2.337
276863AD2-134 GEN
Solar/Wind Harmer
1.625
276861AD2-134 GEN
Solar/Wind Harmer
1.625
970571AG2-364 GEN
Solar/Wind Harmer
0.775
274856ECOGROVE ;U1
Solar/Wind Harmer
3.02
971681AH1-341 GEN
Solar/Wind Harmer
0.577
938861AE1-114 GEN
Solar/Wind Harmer
9.003
274858EASY ROAD;U2
Solar/Wind Harmer
3.587
270240V3-007_GEN2
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.369
24729405KEY G3
50/50
6.704
24729505KEY G4
50/50
6.593
270043AE2-236 GEN
Solar/Wind Harmer
0.363
971771AH1-392 GEN
Solar/Wind Harmer
0.426
970941AG2-585 GEN
Solar/Wind Harmer
0.23
276897AD1-100 C
Solar/Wind Harmer
54.783
971605AH1-302 GEN
Solar/Wind Harmer
6.118
970825AG2-519 GEN
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
4.671
970569AG2-363 GEN
Solar/Wind Harmer
1.162
276157O29GEN1
Solar/Wind Harmer
3.332
276645AC1-214 GEN1
Solar/Wind Harmer
1.17
939741AE1-205 GEN
Solar/Wind Harmer
0.745
942111AE2-223 GEN
Solar/Wind Harmer
8.72
970241AG2-163 GEN
Solar/Wind Harmer
0.884
276174W4-005 GEN2
Solar/Wind Harmer
2.063
276668AB2-070 GEN1
Solar/Wind Harmer
1.771
276838X2-022 GEN2
Solar/Wind Harmer
0.183
246938BC-WTG3
Solar/Wind Helper
17.48
961051AF2-396 GEN
Solar/Wind Harmer
0.935
961051AF2-396 GEN
Solar/Wind Harmer
7.477
270599AE1-208 GEN
Solar/Wind Harmer
0.368
972231SS25-0005
Solar/Wind Harmer
0.685
971411AH1-196 GEN
Solar/Wind Harmer
0.591
274855GSG-6 ;RU
Solar/Wind Harmer
3.361
276876AE1-163_GEN2
Solar/Wind Harmer
5.354
24386405FR-21G C
Solar/Wind Harmer
2.936
276782AC1-033 GEN
Solar/Wind Harmer
2.956
276763AC1-053 GEN1
Solar/Wind Harmer
2.681
971029AG2-637 GEN
Solar/Wind Harmer
0.465
270224U2-072_GEN2
Solar/Wind Helper
2.097
942871AE2-306 GEN
Solar/Wind Helper
0.225
945641AF1-229 GEN
Solar/Wind Helper
0.46
270541AE2-072 C
Solar/Wind Helper
0.478
960861AF2-377 GEN
50/50
2.286
24729305KEY G2
50/50
6.704
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.92
957891AF2-083 GEN
Solar/Wind Harmer
0.707
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.667
274888KELLY CRK;1U
Solar/Wind Harmer
5.697
276893AG1-478 C
Solar/Wind Harmer
0.33
270005AE1-210 C O1
Solar/Wind Harmer
6.326
276602WESTBROOK C
Solar/Wind Harmer
1.658
274863CRW1-WTG
Solar/Wind Harmer
4.59
274864CRW2-WTG
Solar/Wind Harmer
4.59
276603SUBLETTE C
Solar/Wind Harmer
0.776
24387305FR-4G C
Solar/Wind Harmer
4.404
24386605FR-22G C
Solar/Wind Harmer
2.936
24387005FR-3G C
Solar/Wind Harmer
2.906
274880W4-005 GEN4
Solar/Wind Harmer
2.063
246936BC-WTG1
Solar/Wind Helper
17.184
246937BC-WTG2
Solar/Wind Helper
17.184
960841AF2-375 GEN
Solar/Wind Helper
0.576
24727105RPMNG2
50/50
67.807
270246TR4_N_V150
Solar/Wind Harmer
1.123
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.295
274871GR RIDGE ;2U
Solar/Wind Harmer
5.196
943121AE2-341 GEN
Solar/Wind Harmer
0.611
957471AF2-041 GEN
Solar/Wind Harmer
1.174
274848CAMPGROVE;RU
Solar/Wind Harmer
4.383
276785W4-005 GEN1
Solar/Wind Harmer
2.063
276849AB2-070 GEN2
Solar/Wind Harmer
1.771
957201AF2-014 GEN
Solar/Wind Helper
3.968
270284AF1-227 GEN1
Solar/Wind Helper
1.035
270428AC2-015 C
Solar/Wind Helper
0.376
253383AE2-342_GEN
Solar/Wind Helper
0.105
276694AA1-018 GEN2
Solar/Wind Harmer
4.296
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.038
971343AH1-151 GEN
Solar/Wind Harmer
0.782
970169AG2-114 GEN
Solar/Wind Harmer
0.386
959341AF2-225 GEN
Solar/Wind Harmer
0.559
971087AG2-675 GEN
Solar/Wind Harmer
2.343
270445AC2-157 GEN2
Solar/Wind Harmer
0
970521AG2-332 GEN
50/50
10.514
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
12.855
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.782
274877BISHOP HL;1U
Solar/Wind Harmer
2.932
276848AB2-070 GEN3
Solar/Wind Harmer
1.771
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.216
270471AD2-092_GEN
Solar/Wind Helper
0.517
276820AF1-078_GEN
Solar/Wind Helper
0.166
965651AG1-433 GEN
Solar/Wind Harmer
8.016
972181SS23-001
Solar/Wind Harmer
0.428
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.266
970289AG2-191 GEN
Solar/Wind Harmer
0.078
274847GR RIDGE ;BU
Solar/Wind Harmer
4.711
946031AF1-268 GEN
Solar/Wind Harmer
0.337
959091AF2-200 GEN
Solar/Wind Harmer
0.782
274849CRESCENT ;1U
Solar/Wind Harmer
1.605
957381AF2-032 GEN
Solar/Wind Harmer
0.066
276916AD2-100_GEN
Solar/Wind Harmer
0.681
270227U2-072_GEN3
Solar/Wind Helper
2.097
270228U2-072_GEN4
Solar/Wind Helper
2.097
270231U2-072_GEN5
Solar/Wind Helper
2.097
270349AD2-093_GEN
Solar/Wind Helper
0.517
24727005RPMNG1
50/50
67.807
247620Y3-023
50/50
0.45
959331AF2-224 GEN
Solar/Wind Harmer
1.126
965041AG1-368 GEN
Solar/Wind Harmer
0.675
270031AE2-169
Solar/Wind Harmer
0.368
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.489
274861TOP CROP ;1U
Solar/Wind Harmer
4.729
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.176
971067AG2-660 GEN
Solar/Wind Harmer
1.565
24699105WLD G1 C
Solar/Wind Harmer
2.968
276655WTG1_EQ
Solar/Wind Harmer
6.417
963841AG1-237 GEN
Solar/Wind Harmer
11.375
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.3
270286AF1-227 GEN2
Solar/Wind Helper
0.382
247522W1-056 GEN
Solar/Wind Helper
1.958
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.299
24729205KEY G1
50/50
6.593
270201AC2-176 GEN
Solar/Wind Harmer
4.506
970373AG2-245 GEN
Solar/Wind Harmer
0.901
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.326
274872LEEDK;1U
Solar/Wind Harmer
7.44
276872AE1-163_GEN1
Solar/Wind Harmer
5.354
959081AF2-199 GEN
Solar/Wind Harmer
0.391
274851PROVIDENC;RU
Solar/Wind Harmer
2.181
24386205FR-12G C
Solar/Wind Harmer
3.065
24379505HDWTR1G C
Solar/Wind Harmer
5.555
970885AG2-551 GEN
Solar/Wind Harmer
1.417
963741AG1-226 GEN
Solar/Wind Harmer
1.592
276686W4-005 GEN3
Solar/Wind Harmer
2.063
276764AC1-053 GEN2
Solar/Wind Harmer
2.681
276911AD2-131_GEN
Solar/Wind Harmer
0.162
990792J1392
External Queue
0.3014104962348938
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.67
NYPJM->LTFIMP_NY
CLTF
1.235
TVALTFEXP_TVA->PJM
CLTF
2.193
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.955
LGEELTFEXP_LGEE->PJM
CLTF
1.68
MECLTFEXP_MEC->PJM
CLTF
9.337
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.512
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
SIGELTFEXP_SIGE->PJM
CLTF
0.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.406
WECLTFEXP_WEC->PJM
CLTF
2.556
LAGNLTFEXP_LAGN->PJM
CLTF
5.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.89 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2523.04
MW Contribution:
0.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
4.292
961761AG1-017 GEN
Solar/Wind Harmer
0.49
247536S-71 GEN
Solar/Wind Harmer
4.111
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0.646
276615X2-022 GEN
Solar/Wind Harmer
1.279
970349AG2-230 GEN
Solar/Wind Harmer
0.423
971347AH1-153 GEN
Solar/Wind Harmer
0.141
939401AE1-172 GEN
Solar/Wind Harmer
11.164
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.278
926823AC1-168 GEN
Solar/Wind Harmer
3.373
274857EASY ROAD;U1
Solar/Wind Harmer
2.516
252507AC2-088 GEN
Solar/Wind Helper
0.343
24726805LAWG2B
50/50
3.437
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.466
24697905MDL-4G C
Solar/Wind Harmer
1.557
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.367
965091AG1-374 GEN
Solar/Wind Harmer
0.848
276843GEN-1.7
Solar/Wind Harmer
0.369
958011AF2-095 GEN
Solar/Wind Harmer
0.401
276691AA1-018 GEN1
Solar/Wind Harmer
0.297
958491AF2-143 GEN
Solar/Wind Harmer
0.413
276646AC1-214 GEN2
Solar/Wind Harmer
0.845
274878BISHOP HL;2U
Solar/Wind Harmer
2.121
970819AG2-516 GEN
Solar/Wind Harmer
0.324
965931AG1-462 GEN
Solar/Wind Harmer
0.673
943021AE2-325 GEN
Solar/Wind Harmer
1.645
241972AD1-140 GEN
Solar/Wind Helper
0.895
945631AF1-228 GEN
Solar/Wind Helper
0.524
24729205KEY G1
50/50
6.08
24379505HDWTR1G C
Solar/Wind Harmer
13.709
270004AE1-209 GEN
Solar/Wind Harmer
10.924
270201AC2-176 GEN
Solar/Wind Harmer
5.039
970885AG2-551 GEN
Solar/Wind Harmer
1.607
963741AG1-226 GEN
Solar/Wind Harmer
1.428
24386205FR-12G C
Solar/Wind Harmer
2.486
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.6
276686W4-005 GEN3
Solar/Wind Harmer
1.694
276764AC1-053 GEN2
Solar/Wind Harmer
2.21
276911AD2-131_GEN
Solar/Wind Harmer
0.14
24726905LAWG2S
50/50
5.634
24726705LAWG2A
50/50
3.657
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
17.765
970883AG2-550 GEN
Solar/Wind Harmer
0.402
970193AG2-126 GEN
Solar/Wind Harmer
0.506
24385905FR-11G C
Solar/Wind Harmer
4.682
24697605MDL-3G C
Solar/Wind Harmer
2.335
270181AB1-006 GEN2
Solar/Wind Harmer
0.467
274853TWINGROVE;U1
Solar/Wind Harmer
4.367
959611AF2-252 GEN
Solar/Wind Harmer
1.131
960611AF2-352 GEN
Solar/Wind Harmer
1.131
274887GEN-1.85
Solar/Wind Harmer
3.432
970833AG2-524 GEN
Solar/Wind Harmer
0.305
276868AE1-113 GEN
Solar/Wind Harmer
6.441
962781AG1-127 GEN
Solar/Wind Harmer
0.26
970031AG2-029 GEN
Solar/Wind Harmer
0.678
971171AH1-044 GEN
Solar/Wind Harmer
0.542
270063AE2-323 C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
3.749
274851PROVIDENC;RU
Solar/Wind Harmer
1.576
274872LEEDK;1U
Solar/Wind Harmer
5.11
959081AF2-199 GEN
Solar/Wind Harmer
0.271
25183208HLCRTG
Solar/Wind Helper
1.145
253325AC1-069 GEN
Solar/Wind Helper
0.168
25194708EBND2
50/50
6.217
24699105WLD G1 C
Solar/Wind Harmer
4.292
270031AE2-169
Solar/Wind Harmer
0.444
270383AD1-128 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
9.721
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.717
971917AH1-482 GEN
Solar/Wind Harmer
4.53
276655WTG1_EQ
Solar/Wind Harmer
4.876
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.231
971067AG2-660 GEN
Solar/Wind Harmer
1.085
252509AD1-136 GEN
Solar/Wind Helper
0.049
270186AC1-089 GEN
Solar/Wind Helper
0.595
946101AF1-275 GEN
Solar/Wind Helper
0.126
946321AF1-296 GEN
Solar/Wind Harmer
7.882
253415AE1-040 GEN
Solar/Wind Helper
0.17
961171AF2-408 GEN
50/50
9.476
970289AG2-191 GEN
Solar/Wind Harmer
0.645
970291AG2-192 GEN
Solar/Wind Harmer
0.352
276785W4-005 GEN1
Solar/Wind Harmer
1.694
276849AB2-070 GEN2
Solar/Wind Harmer
1.453
274871GR RIDGE ;2U
Solar/Wind Harmer
3.521
943121AE2-341 GEN
Solar/Wind Harmer
0.414
274848CAMPGROVE;RU
Solar/Wind Harmer
3.187
957471AF2-041 GEN
Solar/Wind Harmer
0.814
270449AD2-020 GEN
Solar/Wind Harmer
0
252524AE2-267 GEN
Solar/Wind Helper
0.57
253317AC1-085 GEN4
Solar/Wind Helper
0.701
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253400AC2-068 GEN
Solar/Wind Helper
0.08
253383AE2-342_GEN
Solar/Wind Helper
0.141
241973AD2-163_GEN1
Solar/Wind Helper
0.307
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.453
276806AD2-047 C O1
Solar/Wind Harmer
8.577
274877BISHOP HL;1U
Solar/Wind Harmer
2.121
971341AH1-150 GEN
Solar/Wind Harmer
0.542
276820AF1-078_GEN
Solar/Wind Helper
0.217
253316AC1-085 GEN3
Solar/Wind Helper
0.701
253433AC1-085 GEN1
Solar/Wind Helper
0.444
253349AC2-067 GEN
Solar/Wind Helper
0.2
253343AC1-166 GEN
Solar/Wind Helper
0.168
276903AD2-071 C
Solar/Wind Harmer
0.53
944531AF1-118 GEN
Solar/Wind Harmer
1.735
945391AF1-204 GEN
Solar/Wind Harmer
13.406
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.299
965911AG1-460 GEN
Solar/Wind Harmer
0.672
970707AG2-453 GEN
Solar/Wind Harmer
0.778
970833AG2-524 GEN
Solar/Wind Harmer
2.444
958481AF2-142 GEN
Solar/Wind Harmer
0.414
274862TOP CROP ;2U
Solar/Wind Harmer
3.231
274879MINONK ;1U
Solar/Wind Harmer
4.294
971675AH1-338 GEN
Solar/Wind Harmer
0.49
253406AD2-031_GEN
Solar/Wind Helper
0.233
942051AE2-217 GEN
Solar/Wind Helper
0.623
270520AE2-214 GEN
Solar/Wind Helper
0.504
970291AG2-192 GEN
Solar/Wind Harmer
0.064
963791AG1-232 GEN
Solar/Wind Harmer
0.448
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
1.557
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.425
970169AG2-114 GEN
Solar/Wind Harmer
0.281
965681AG1-436 GEN
Solar/Wind Harmer
0.348
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.934
943591AF1-030 GEN
Solar/Wind Harmer
0.276
971343AH1-151 GEN
Solar/Wind Harmer
0.542
971087AG2-675 GEN
Solar/Wind Harmer
1.689
960071AF2-298 GEN
Solar/Wind Helper
0.264
253303V4-073 C
Solar/Wind Helper
0.011
241974AD2-163_GEN2
Solar/Wind Helper
0.307
253338AC1-165 GEN
Solar/Wind Helper
0.168
241955AC1-078 GEN
Solar/Wind Helper
0.57
24729305KEY G2
50/50
6.183
270005AE1-210 C O1
Solar/Wind Harmer
10.924
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.745
270071AF1-092 GEN
Solar/Wind Harmer
0.507
24387305FR-4G C
Solar/Wind Harmer
3.572
24386605FR-22G C
Solar/Wind Harmer
2.381
24387005FR-3G C
Solar/Wind Harmer
2.358
274880W4-005 GEN4
Solar/Wind Harmer
1.694
274863CRW1-WTG
Solar/Wind Harmer
3.289
274864CRW2-WTG
Solar/Wind Harmer
3.289
274888KELLY CRK;1U
Solar/Wind Harmer
3.801
24726505LAWG1B
50/50
3.657
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.975
945371AF1-202 GEN
Solar/Wind Harmer
9.688
970825AG2-519 GEN
Solar/Wind Harmer
2.573
958861AF2-177 GEN
Solar/Wind Harmer
18.319
270032AE2-172
Solar/Wind Harmer
4.154
942221AE2-234 GEN
Solar/Wind Harmer
0.15
270543AE2-219 C
Solar/Wind Harmer
0.402
24691005MDL-2G C
Solar/Wind Harmer
2.335
957841AF2-078 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
0.262
276621W2-048 GEN
Solar/Wind Harmer
4.073
942481AE2-261 GEN
Solar/Wind Harmer
0.837
971997AH1-543 GEN
Solar/Wind Harmer
0.434
276889AE2-281 GEN
Solar/Wind Harmer
1.071
962691AG1-118 GEN
Solar/Wind Harmer
0.82
276158O29GEN2
Solar/Wind Harmer
2.368
276708O09 GEN2
Solar/Wind Harmer
2.224
270505AE1-170 C O1
Solar/Wind Harmer
0.399
270367AC2-061_GEN
Solar/Wind Helper
0.535
962581AG1-107 GEN
Solar/Wind Helper
0.634
24726605LAWG1S
50/50
5.634
24729405KEY G3
50/50
6.183
24729505KEY G4
50/50
6.08
970825AG2-519 GEN
Solar/Wind Harmer
0.402
970241AG2-163 GEN
Solar/Wind Harmer
0.793
270043AE2-236 GEN
Solar/Wind Harmer
0.17
971605AH1-302 GEN
Solar/Wind Harmer
4.401
276174W4-005 GEN2
Solar/Wind Harmer
1.694
276668AB2-070 GEN1
Solar/Wind Harmer
1.453
939741AE1-205 GEN
Solar/Wind Harmer
0.566
942111AE2-223 GEN
Solar/Wind Harmer
6.625
276838X2-022 GEN2
Solar/Wind Harmer
0.152
276897AD1-100 C
Solar/Wind Harmer
37.041
970941AG2-585 GEN
Solar/Wind Harmer
0.153
276805AD2-038 GEN
Solar/Wind Harmer
3.224
970569AG2-363 GEN
Solar/Wind Harmer
0.822
276645AC1-214 GEN1
Solar/Wind Harmer
0.845
971771AH1-392 GEN
Solar/Wind Harmer
0.246
276157O29GEN1
Solar/Wind Harmer
2.368
961491AF2-440 GEN
Solar/Wind Helper
0.211
24726405LAWG1A
50/50
3.657
270240V3-007_GEN2
Solar/Wind Harmer
10.734
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.831
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.102
970571AG2-364 GEN
Solar/Wind Harmer
0.548
274850MENDOTA H;RU
Solar/Wind Harmer
1.615
276863AD2-134 GEN
Solar/Wind Harmer
1.123
276861AD2-134 GEN
Solar/Wind Harmer
1.123
274856ECOGROVE ;U1
Solar/Wind Harmer
2.105
971681AH1-341 GEN
Solar/Wind Harmer
0.404
938861AE1-114 GEN
Solar/Wind Harmer
6.303
274858EASY ROAD;U2
Solar/Wind Harmer
2.516
945111AF1-176 GEN
Solar/Wind Harmer
0.474
945111AF1-176 GEN
Solar/Wind Harmer
2.586
253378AE2-206_GEN
Solar/Wind Helper
0.483
961161AF2-407 GEN
50/50
35.642
270599AE1-208 GEN
Solar/Wind Harmer
0.444
971029AG2-637 GEN
Solar/Wind Harmer
0.537
24386405FR-21G C
Solar/Wind Harmer
2.381
276763AC1-053 GEN1
Solar/Wind Harmer
2.21
972231SS25-0005
Solar/Wind Harmer
0.445
276876AE1-163_GEN2
Solar/Wind Harmer
3.749
274855GSG-6 ;RU
Solar/Wind Harmer
2.322
276782AC1-033 GEN
Solar/Wind Harmer
2.137
971411AH1-196 GEN
Solar/Wind Harmer
0.408
961051AF2-396 GEN
Solar/Wind Harmer
0.528
961051AF2-396 GEN
Solar/Wind Harmer
4.221
276893AG1-478 C
Solar/Wind Harmer
0.222
276602WESTBROOK C
Solar/Wind Harmer
1.145
276603SUBLETTE C
Solar/Wind Harmer
0.546
957891AF2-083 GEN
Solar/Wind Harmer
0.4
252510AF1-249 C
Solar/Wind Helper
0.173
253394AE2-221_GEN
Solar/Wind Helper
0.748
253398AE2-221_GEN2
Solar/Wind Helper
0.748
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.203
24791305MDL-5G
Solar/Wind Harmer
1.557
276726Z2-087_GEN
Solar/Wind Harmer
4.417
944221AF1-090 GEN
Solar/Wind Harmer
8.719
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.063
276882AE2-255 GEN
Solar/Wind Harmer
2.147
270526AF1-158 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
2.224
270518AE2-148 GEN
Solar/Wind Helper
2.34
270340AC2-060 GEN
Solar/Wind Helper
0.401
946031AF1-268 GEN
Solar/Wind Harmer
0.494
965651AG1-433 GEN
Solar/Wind Harmer
8.883
970289AG2-191 GEN
Solar/Wind Harmer
0.093
270055AF2-134 C O1
Solar/Wind Harmer
0
957381AF2-032 GEN
Solar/Wind Harmer
0.056
276916AD2-100_GEN
Solar/Wind Harmer
0.588
972207SS24-0001
Solar/Wind Harmer
0.839
972181SS23-001
Solar/Wind Harmer
0.278
274847GR RIDGE ;BU
Solar/Wind Harmer
3.192
274849CRESCENT ;1U
Solar/Wind Harmer
1.159
959091AF2-200 GEN
Solar/Wind Harmer
0.542
253333AC1-068 GEN
Solar/Wind Helper
0.168
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.474
TVALTFEXP_TVA->PJM
CLTF
1.881
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.797
NYPJM->LTFIMP_NY
CLTF
0.737
MECLTFEXP_MEC->PJM
CLTF
7.099
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.163
WECLTFEXP_WEC->PJM
CLTF
1.772
SIGELTFEXP_SIGE->PJM
CLTF
0.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.45
LGEELTFEXP_LGEE->PJM
CLTF
1.395
LAGNLTFEXP_LAGN->PJM
CLTF
4.67

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.9 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2499.98
MW Contribution:
0.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728705AND G3
50/50
8.972
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
4.31
961761AG1-017 GEN
Solar/Wind Harmer
0.493
247536S-71 GEN
Solar/Wind Harmer
4.144
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.427
971347AH1-153 GEN
Solar/Wind Harmer
0.142
276656WTG2_EQ
Solar/Wind Harmer
0.649
276615X2-022 GEN
Solar/Wind Harmer
1.283
939401AE1-172 GEN
Solar/Wind Harmer
11.231
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.28
926823AC1-168 GEN
Solar/Wind Harmer
3.391
274857EASY ROAD;U1
Solar/Wind Harmer
2.53
252507AC2-088 GEN
Solar/Wind Helper
0.342
961171AF2-408 GEN
50/50
9.509
24728605AND G2
50/50
4.239
970289AG2-191 GEN
Solar/Wind Harmer
0.648
970291AG2-192 GEN
Solar/Wind Harmer
0.353
276785W4-005 GEN1
Solar/Wind Harmer
1.7
276849AB2-070 GEN2
Solar/Wind Harmer
1.459
274871GR RIDGE ;2U
Solar/Wind Harmer
3.544
943121AE2-341 GEN
Solar/Wind Harmer
0.416
274848CAMPGROVE;RU
Solar/Wind Harmer
3.202
957471AF2-041 GEN
Solar/Wind Harmer
0.818
270449AD2-020 GEN
Solar/Wind Harmer
0
252524AE2-267 GEN
Solar/Wind Helper
0.568
253317AC1-085 GEN4
Solar/Wind Helper
0.695
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253400AC2-068 GEN
Solar/Wind Helper
0.079
253383AE2-342_GEN
Solar/Wind Helper
0.134
241973AD2-163_GEN1
Solar/Wind Helper
0.292
276903AD2-071 C
Solar/Wind Harmer
0.532
944531AF1-118 GEN
Solar/Wind Harmer
1.747
945391AF1-204 GEN
Solar/Wind Harmer
13.441
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.301
965911AG1-460 GEN
Solar/Wind Harmer
0.674
970707AG2-453 GEN
Solar/Wind Harmer
0.783
970833AG2-524 GEN
Solar/Wind Harmer
2.46
958481AF2-142 GEN
Solar/Wind Harmer
0.417
274862TOP CROP ;2U
Solar/Wind Harmer
3.251
274879MINONK ;1U
Solar/Wind Harmer
4.319
971675AH1-338 GEN
Solar/Wind Harmer
0.492
253406AD2-031_GEN
Solar/Wind Helper
0.23
942051AE2-217 GEN
Solar/Wind Helper
0.597
970291AG2-192 GEN
Solar/Wind Harmer
0.064
963791AG1-232 GEN
Solar/Wind Harmer
0.455
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
1.565
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.427
970169AG2-114 GEN
Solar/Wind Harmer
0.283
965681AG1-436 GEN
Solar/Wind Harmer
0.351
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.953
943591AF1-030 GEN
Solar/Wind Harmer
0.277
971343AH1-151 GEN
Solar/Wind Harmer
0.545
971087AG2-675 GEN
Solar/Wind Harmer
1.697
960071AF2-298 GEN
Solar/Wind Helper
0.261
253303V4-073 C
Solar/Wind Helper
0.01
253338AC1-165 GEN
Solar/Wind Helper
0.163
241974AD2-163_GEN2
Solar/Wind Helper
0.292
241955AC1-078 GEN
Solar/Wind Helper
0.54
961161AF2-407 GEN
50/50
35.759
270599AE1-208 GEN
Solar/Wind Harmer
0.447
971029AG2-637 GEN
Solar/Wind Harmer
0.542
24386405FR-21G C
Solar/Wind Harmer
2.392
276763AC1-053 GEN1
Solar/Wind Harmer
2.217
972231SS25-0005
Solar/Wind Harmer
0.449
276876AE1-163_GEN2
Solar/Wind Harmer
3.771
274855GSG-6 ;RU
Solar/Wind Harmer
2.336
971411AH1-196 GEN
Solar/Wind Harmer
0.41
276782AC1-033 GEN
Solar/Wind Harmer
2.148
961051AF2-396 GEN
Solar/Wind Harmer
0.534
961051AF2-396 GEN
Solar/Wind Harmer
4.273
24726505LAWG1B
50/50
3.661
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.984
945371AF1-202 GEN
Solar/Wind Harmer
9.734
970825AG2-519 GEN
Solar/Wind Harmer
2.585
958861AF2-177 GEN
Solar/Wind Harmer
18.415
270032AE2-172
Solar/Wind Harmer
4.174
942221AE2-234 GEN
Solar/Wind Harmer
0.151
270543AE2-219 C
Solar/Wind Harmer
0.405
24691005MDL-2G C
Solar/Wind Harmer
2.347
957841AF2-078 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
0.263
276621W2-048 GEN
Solar/Wind Harmer
4.087
942481AE2-261 GEN
Solar/Wind Harmer
0.839
971997AH1-543 GEN
Solar/Wind Harmer
0.437
276889AE2-281 GEN
Solar/Wind Harmer
1.077
962691AG1-118 GEN
Solar/Wind Harmer
0.825
276158O29GEN2
Solar/Wind Harmer
2.38
276708O09 GEN2
Solar/Wind Harmer
2.235
270505AE1-170 C O1
Solar/Wind Harmer
0.404
270367AC2-061_GEN
Solar/Wind Helper
0.533
962581AG1-107 GEN
Solar/Wind Helper
0.631
24726405LAWG1A
50/50
3.661
270240V3-007_GEN2
Solar/Wind Harmer
10.766
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.835
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.109
970571AG2-364 GEN
Solar/Wind Harmer
0.551
274850MENDOTA H;RU
Solar/Wind Harmer
1.624
276863AD2-134 GEN
Solar/Wind Harmer
1.129
276861AD2-134 GEN
Solar/Wind Harmer
1.129
274856ECOGROVE ;U1
Solar/Wind Harmer
2.116
971681AH1-341 GEN
Solar/Wind Harmer
0.406
938861AE1-114 GEN
Solar/Wind Harmer
6.337
274858EASY ROAD;U2
Solar/Wind Harmer
2.53
945111AF1-176 GEN
Solar/Wind Harmer
0.48
945111AF1-176 GEN
Solar/Wind Harmer
2.617
253378AE2-206_GEN
Solar/Wind Helper
0.471
24726805LAWG2B
50/50
3.441
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.469
24697905MDL-4G C
Solar/Wind Harmer
1.565
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.386
965091AG1-374 GEN
Solar/Wind Harmer
0.852
276843GEN-1.7
Solar/Wind Harmer
0.372
958011AF2-095 GEN
Solar/Wind Harmer
0.404
276691AA1-018 GEN1
Solar/Wind Harmer
0.299
958491AF2-143 GEN
Solar/Wind Harmer
0.416
276646AC1-214 GEN2
Solar/Wind Harmer
0.85
274878BISHOP HL;2U
Solar/Wind Harmer
2.131
970819AG2-516 GEN
Solar/Wind Harmer
0.326
943021AE2-325 GEN
Solar/Wind Harmer
1.665
965931AG1-462 GEN
Solar/Wind Harmer
0.676
241972AD1-140 GEN
Solar/Wind Helper
0.878
945631AF1-228 GEN
Solar/Wind Helper
0.503
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.225
24791305MDL-5G
Solar/Wind Harmer
1.565
276726Z2-087_GEN
Solar/Wind Harmer
4.438
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.091
944221AF1-090 GEN
Solar/Wind Harmer
8.739
270526AF1-158 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
2.16
276741O09 GEN1
Solar/Wind Harmer
2.235
270518AE2-148 GEN
Solar/Wind Helper
2.274
270340AC2-060 GEN
Solar/Wind Helper
0.395
24729205KEY G1
50/50
6.119
24379505HDWTR1G C
Solar/Wind Harmer
13.75
270004AE1-209 GEN
Solar/Wind Harmer
10.966
270201AC2-176 GEN
Solar/Wind Harmer
5.072
970885AG2-551 GEN
Solar/Wind Harmer
1.621
963741AG1-226 GEN
Solar/Wind Harmer
1.434
24386205FR-12G C
Solar/Wind Harmer
2.498
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.604
276686W4-005 GEN3
Solar/Wind Harmer
1.7
276764AC1-053 GEN2
Solar/Wind Harmer
2.217
276911AD2-131_GEN
Solar/Wind Harmer
0.14
276872AE1-163_GEN1
Solar/Wind Harmer
3.771
274872LEEDK;1U
Solar/Wind Harmer
5.14
274851PROVIDENC;RU
Solar/Wind Harmer
1.584
959081AF2-199 GEN
Solar/Wind Harmer
0.273
25183208HLCRTG
Solar/Wind Helper
1.139
253325AC1-069 GEN
Solar/Wind Helper
0.163
24726905LAWG2S
50/50
5.641
24726705LAWG2A
50/50
3.661
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
17.863
970883AG2-550 GEN
Solar/Wind Harmer
0.405
970193AG2-126 GEN
Solar/Wind Harmer
0.507
24385905FR-11G C
Solar/Wind Harmer
4.703
24697605MDL-3G C
Solar/Wind Harmer
2.347
270181AB1-006 GEN2
Solar/Wind Harmer
0.469
274853TWINGROVE;U1
Solar/Wind Harmer
4.386
959611AF2-252 GEN
Solar/Wind Harmer
1.136
960611AF2-352 GEN
Solar/Wind Harmer
1.136
274887GEN-1.85
Solar/Wind Harmer
3.456
970833AG2-524 GEN
Solar/Wind Harmer
0.307
276868AE1-113 GEN
Solar/Wind Harmer
6.479
970031AG2-029 GEN
Solar/Wind Harmer
0.688
962781AG1-127 GEN
Solar/Wind Harmer
0.261
971171AH1-044 GEN
Solar/Wind Harmer
0.545
270063AE2-323 C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
7.918
253415AE1-040 GEN
Solar/Wind Helper
0.167
946031AF1-268 GEN
Solar/Wind Harmer
0.497
965651AG1-433 GEN
Solar/Wind Harmer
8.932
970289AG2-191 GEN
Solar/Wind Harmer
0.093
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
0.845
957381AF2-032 GEN
Solar/Wind Harmer
0.056
276916AD2-100_GEN
Solar/Wind Harmer
0.589
972181SS23-001
Solar/Wind Harmer
0.28
274847GR RIDGE ;BU
Solar/Wind Harmer
3.213
274849CRESCENT ;1U
Solar/Wind Harmer
1.165
959091AF2-200 GEN
Solar/Wind Harmer
0.545
253333AC1-068 GEN
Solar/Wind Helper
0.163
24728505AND G1
50/50
4.239
247621Y3-024
50/50
0.287
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.459
276806AD2-047 C O1
Solar/Wind Harmer
8.636
274877BISHOP HL;1U
Solar/Wind Harmer
2.131
971341AH1-150 GEN
Solar/Wind Harmer
0.545
276820AF1-078_GEN
Solar/Wind Helper
0.212
253316AC1-085 GEN3
Solar/Wind Helper
0.695
253433AC1-085 GEN1
Solar/Wind Helper
0.44
253349AC2-067 GEN
Solar/Wind Helper
0.197
253343AC1-166 GEN
Solar/Wind Helper
0.163
24729305KEY G2
50/50
6.222
270005AE1-210 C O1
Solar/Wind Harmer
10.966
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.75
270071AF1-092 GEN
Solar/Wind Harmer
0.512
24387305FR-4G C
Solar/Wind Harmer
3.589
24386605FR-22G C
Solar/Wind Harmer
2.392
24387005FR-3G C
Solar/Wind Harmer
2.368
274880W4-005 GEN4
Solar/Wind Harmer
1.7
274863CRW1-WTG
Solar/Wind Harmer
3.307
274864CRW2-WTG
Solar/Wind Harmer
3.307
274888KELLY CRK;1U
Solar/Wind Harmer
3.828
276893AG1-478 C
Solar/Wind Harmer
0.224
276602WESTBROOK C
Solar/Wind Harmer
1.152
276603SUBLETTE C
Solar/Wind Harmer
0.548
957891AF2-083 GEN
Solar/Wind Harmer
0.404
252510AF1-249 C
Solar/Wind Helper
0.172
253394AE2-221_GEN
Solar/Wind Helper
0.74
253398AE2-221_GEN2
Solar/Wind Helper
0.74
24726605LAWG1S
50/50
5.641
24729405KEY G3
50/50
6.222
24729505KEY G4
50/50
6.119
970825AG2-519 GEN
Solar/Wind Harmer
0.404
970241AG2-163 GEN
Solar/Wind Harmer
0.796
270043AE2-236 GEN
Solar/Wind Harmer
0.172
971605AH1-302 GEN
Solar/Wind Harmer
4.428
276174W4-005 GEN2
Solar/Wind Harmer
1.7
276668AB2-070 GEN1
Solar/Wind Harmer
1.459
939741AE1-205 GEN
Solar/Wind Harmer
0.569
942111AE2-223 GEN
Solar/Wind Harmer
6.657
276838X2-022 GEN2
Solar/Wind Harmer
0.152
276897AD1-100 C
Solar/Wind Harmer
37.287
970941AG2-585 GEN
Solar/Wind Harmer
0.154
276805AD2-038 GEN
Solar/Wind Harmer
3.244
971771AH1-392 GEN
Solar/Wind Harmer
0.248
970569AG2-363 GEN
Solar/Wind Harmer
0.827
276645AC1-214 GEN1
Solar/Wind Harmer
0.85
276157O29GEN1
Solar/Wind Harmer
2.38
961491AF2-440 GEN
Solar/Wind Helper
0.21
25194708EBND2
50/50
6.232
24699105WLD G1 C
Solar/Wind Harmer
4.31
270031AE2-169
Solar/Wind Harmer
0.447
270383AD1-128 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
9.762
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.741
971917AH1-482 GEN
Solar/Wind Harmer
4.561
276655WTG1_EQ
Solar/Wind Harmer
4.899
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.251
971067AG2-660 GEN
Solar/Wind Harmer
1.091
252509AD1-136 GEN
Solar/Wind Helper
0.049
270186AC1-089 GEN
Solar/Wind Helper
0.593
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.002
WECLTFEXP_WEC->PJM
CLTF
1.782
LAGNLTFEXP_LAGN->PJM
CLTF
4.587
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.213
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053
SIGELTFEXP_SIGE->PJM
CLTF
0.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.192
LGEELTFEXP_LGEE->PJM
CLTF
1.394
MECLTFEXP_MEC->PJM
CLTF
7.114
AH1-155LTFEXP_AH1-155->PJM
LTF
0.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.33
NYPJM->LTFIMP_NY
CLTF
0.729
TVALTFEXP_TVA->PJM
CLTF
1.829
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.01 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2479.49
MW Contribution:
0.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
4.31
961761AG1-017 GEN
Solar/Wind Harmer
0.493
247536S-71 GEN
Solar/Wind Harmer
4.144
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
970349AG2-230 GEN
Solar/Wind Harmer
0.427
971347AH1-153 GEN
Solar/Wind Harmer
0.142
276656WTG2_EQ
Solar/Wind Harmer
0.649
276615X2-022 GEN
Solar/Wind Harmer
1.283
939401AE1-172 GEN
Solar/Wind Harmer
11.231
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.28
926823AC1-168 GEN
Solar/Wind Harmer
3.391
274857EASY ROAD;U1
Solar/Wind Harmer
2.53
252507AC2-088 GEN
Solar/Wind Helper
0.342
24726805LAWG2B
50/50
3.441
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.469
24697905MDL-4G C
Solar/Wind Harmer
1.565
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.386
965091AG1-374 GEN
Solar/Wind Harmer
0.852
276843GEN-1.7
Solar/Wind Harmer
0.372
958011AF2-095 GEN
Solar/Wind Harmer
0.404
276691AA1-018 GEN1
Solar/Wind Harmer
0.299
958491AF2-143 GEN
Solar/Wind Harmer
0.416
24729205KEY G1
50/50
6.119
24379505HDWTR1G C
Solar/Wind Harmer
13.75
270004AE1-209 GEN
Solar/Wind Harmer
10.966
270201AC2-176 GEN
Solar/Wind Harmer
5.072
970885AG2-551 GEN
Solar/Wind Harmer
1.621
963741AG1-226 GEN
Solar/Wind Harmer
1.434
24386205FR-12G C
Solar/Wind Harmer
2.498
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.604
276686W4-005 GEN3
Solar/Wind Harmer
1.7
276764AC1-053 GEN2
Solar/Wind Harmer
2.217
276911AD2-131_GEN
Solar/Wind Harmer
0.14
276872AE1-163_GEN1
Solar/Wind Harmer
3.771
274872LEEDK;1U
Solar/Wind Harmer
5.14
274851PROVIDENC;RU
Solar/Wind Harmer
1.584
959081AF2-199 GEN
Solar/Wind Harmer
0.273
25183208HLCRTG
Solar/Wind Helper
1.139
253325AC1-069 GEN
Solar/Wind Helper
0.163
276646AC1-214 GEN2
Solar/Wind Harmer
0.85
274878BISHOP HL;2U
Solar/Wind Harmer
2.131
970819AG2-516 GEN
Solar/Wind Harmer
0.326
943021AE2-325 GEN
Solar/Wind Harmer
1.665
965931AG1-462 GEN
Solar/Wind Harmer
0.676
241972AD1-140 GEN
Solar/Wind Helper
0.878
945631AF1-228 GEN
Solar/Wind Helper
0.503
25194708EBND2
50/50
6.232
24699105WLD G1 C
Solar/Wind Harmer
4.31
270031AE2-169
Solar/Wind Harmer
0.447
270383AD1-128 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
9.762
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.741
971917AH1-482 GEN
Solar/Wind Harmer
4.561
276655WTG1_EQ
Solar/Wind Harmer
4.899
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.251
971067AG2-660 GEN
Solar/Wind Harmer
1.091
252509AD1-136 GEN
Solar/Wind Helper
0.049
270186AC1-089 GEN
Solar/Wind Helper
0.593
24726905LAWG2S
50/50
5.641
24726705LAWG2A
50/50
3.661
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
17.863
970883AG2-550 GEN
Solar/Wind Harmer
0.405
970193AG2-126 GEN
Solar/Wind Harmer
0.507
24385905FR-11G C
Solar/Wind Harmer
4.703
24697605MDL-3G C
Solar/Wind Harmer
2.347
270181AB1-006 GEN2
Solar/Wind Harmer
0.469
274853TWINGROVE;U1
Solar/Wind Harmer
4.386
959611AF2-252 GEN
Solar/Wind Harmer
1.136
960611AF2-352 GEN
Solar/Wind Harmer
1.136
274887GEN-1.85
Solar/Wind Harmer
3.456
970833AG2-524 GEN
Solar/Wind Harmer
0.307
276868AE1-113 GEN
Solar/Wind Harmer
6.479
970031AG2-029 GEN
Solar/Wind Harmer
0.688
962781AG1-127 GEN
Solar/Wind Harmer
0.261
971171AH1-044 GEN
Solar/Wind Harmer
0.545
270063AE2-323 C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
7.918
253415AE1-040 GEN
Solar/Wind Helper
0.167
961171AF2-408 GEN
50/50
9.509
970289AG2-191 GEN
Solar/Wind Harmer
0.648
970291AG2-192 GEN
Solar/Wind Harmer
0.353
276785W4-005 GEN1
Solar/Wind Harmer
1.7
276849AB2-070 GEN2
Solar/Wind Harmer
1.459
274871GR RIDGE ;2U
Solar/Wind Harmer
3.544
943121AE2-341 GEN
Solar/Wind Harmer
0.416
274848CAMPGROVE;RU
Solar/Wind Harmer
3.202
957471AF2-041 GEN
Solar/Wind Harmer
0.818
270449AD2-020 GEN
Solar/Wind Harmer
0
252524AE2-267 GEN
Solar/Wind Helper
0.568
253317AC1-085 GEN4
Solar/Wind Helper
0.695
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253400AC2-068 GEN
Solar/Wind Helper
0.079
253383AE2-342_GEN
Solar/Wind Helper
0.134
241973AD2-163_GEN1
Solar/Wind Helper
0.292
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.459
276806AD2-047 C O1
Solar/Wind Harmer
8.636
274877BISHOP HL;1U
Solar/Wind Harmer
2.131
971341AH1-150 GEN
Solar/Wind Harmer
0.545
276820AF1-078_GEN
Solar/Wind Helper
0.212
253316AC1-085 GEN3
Solar/Wind Helper
0.695
253433AC1-085 GEN1
Solar/Wind Helper
0.44
253349AC2-067 GEN
Solar/Wind Helper
0.197
253343AC1-166 GEN
Solar/Wind Helper
0.163
970291AG2-192 GEN
Solar/Wind Harmer
0.064
963791AG1-232 GEN
Solar/Wind Harmer
0.455
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
1.565
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.427
970169AG2-114 GEN
Solar/Wind Harmer
0.283
965681AG1-436 GEN
Solar/Wind Harmer
0.351
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.953
943591AF1-030 GEN
Solar/Wind Harmer
0.277
971343AH1-151 GEN
Solar/Wind Harmer
0.545
971087AG2-675 GEN
Solar/Wind Harmer
1.697
960071AF2-298 GEN
Solar/Wind Helper
0.261
253303V4-073 C
Solar/Wind Helper
0.01
253338AC1-165 GEN
Solar/Wind Helper
0.163
241974AD2-163_GEN2
Solar/Wind Helper
0.292
241955AC1-078 GEN
Solar/Wind Helper
0.54
24726505LAWG1B
50/50
3.661
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.984
945371AF1-202 GEN
Solar/Wind Harmer
9.734
970825AG2-519 GEN
Solar/Wind Harmer
2.585
958861AF2-177 GEN
Solar/Wind Harmer
18.415
270032AE2-172
Solar/Wind Harmer
4.174
942221AE2-234 GEN
Solar/Wind Harmer
0.151
270543AE2-219 C
Solar/Wind Harmer
0.405
24691005MDL-2G C
Solar/Wind Harmer
2.347
957841AF2-078 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
0.263
276621W2-048 GEN
Solar/Wind Harmer
4.087
942481AE2-261 GEN
Solar/Wind Harmer
0.839
971997AH1-543 GEN
Solar/Wind Harmer
0.437
276889AE2-281 GEN
Solar/Wind Harmer
1.077
962691AG1-118 GEN
Solar/Wind Harmer
0.825
276158O29GEN2
Solar/Wind Harmer
2.38
276708O09 GEN2
Solar/Wind Harmer
2.235
270505AE1-170 C O1
Solar/Wind Harmer
0.404
270367AC2-061_GEN
Solar/Wind Helper
0.533
962581AG1-107 GEN
Solar/Wind Helper
0.631
24726605LAWG1S
50/50
5.641
24729405KEY G3
50/50
6.222
24729505KEY G4
50/50
6.119
970825AG2-519 GEN
Solar/Wind Harmer
0.404
970241AG2-163 GEN
Solar/Wind Harmer
0.796
270043AE2-236 GEN
Solar/Wind Harmer
0.172
971605AH1-302 GEN
Solar/Wind Harmer
4.428
276174W4-005 GEN2
Solar/Wind Harmer
1.7
276668AB2-070 GEN1
Solar/Wind Harmer
1.459
939741AE1-205 GEN
Solar/Wind Harmer
0.569
942111AE2-223 GEN
Solar/Wind Harmer
6.657
276838X2-022 GEN2
Solar/Wind Harmer
0.152
276897AD1-100 C
Solar/Wind Harmer
37.287
970941AG2-585 GEN
Solar/Wind Harmer
0.154
276805AD2-038 GEN
Solar/Wind Harmer
3.244
971771AH1-392 GEN
Solar/Wind Harmer
0.248
970569AG2-363 GEN
Solar/Wind Harmer
0.827
276645AC1-214 GEN1
Solar/Wind Harmer
0.85
276157O29GEN1
Solar/Wind Harmer
2.38
961491AF2-440 GEN
Solar/Wind Helper
0.21
24726405LAWG1A
50/50
3.661
270240V3-007_GEN2
Solar/Wind Harmer
10.766
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.835
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.109
970571AG2-364 GEN
Solar/Wind Harmer
0.551
274850MENDOTA H;RU
Solar/Wind Harmer
1.624
276863AD2-134 GEN
Solar/Wind Harmer
1.129
276861AD2-134 GEN
Solar/Wind Harmer
1.129
274856ECOGROVE ;U1
Solar/Wind Harmer
2.116
971681AH1-341 GEN
Solar/Wind Harmer
0.406
938861AE1-114 GEN
Solar/Wind Harmer
6.337
274858EASY ROAD;U2
Solar/Wind Harmer
2.53
945111AF1-176 GEN
Solar/Wind Harmer
0.48
945111AF1-176 GEN
Solar/Wind Harmer
2.617
253378AE2-206_GEN
Solar/Wind Helper
0.471
276903AD2-071 C
Solar/Wind Harmer
0.532
944531AF1-118 GEN
Solar/Wind Harmer
1.747
945391AF1-204 GEN
Solar/Wind Harmer
13.441
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.301
965911AG1-460 GEN
Solar/Wind Harmer
0.674
970707AG2-453 GEN
Solar/Wind Harmer
0.783
970833AG2-524 GEN
Solar/Wind Harmer
2.46
958481AF2-142 GEN
Solar/Wind Harmer
0.417
274862TOP CROP ;2U
Solar/Wind Harmer
3.251
274879MINONK ;1U
Solar/Wind Harmer
4.319
971675AH1-338 GEN
Solar/Wind Harmer
0.492
253406AD2-031_GEN
Solar/Wind Helper
0.23
942051AE2-217 GEN
Solar/Wind Helper
0.597
961161AF2-407 GEN
50/50
35.759
270599AE1-208 GEN
Solar/Wind Harmer
0.447
971029AG2-637 GEN
Solar/Wind Harmer
0.542
24386405FR-21G C
Solar/Wind Harmer
2.392
276763AC1-053 GEN1
Solar/Wind Harmer
2.217
972231SS25-0005
Solar/Wind Harmer
0.449
276876AE1-163_GEN2
Solar/Wind Harmer
3.771
274855GSG-6 ;RU
Solar/Wind Harmer
2.336
971411AH1-196 GEN
Solar/Wind Harmer
0.41
276782AC1-033 GEN
Solar/Wind Harmer
2.148
961051AF2-396 GEN
Solar/Wind Harmer
0.534
961051AF2-396 GEN
Solar/Wind Harmer
4.273
24729305KEY G2
50/50
6.222
270005AE1-210 C O1
Solar/Wind Harmer
10.966
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.75
270071AF1-092 GEN
Solar/Wind Harmer
0.512
24387305FR-4G C
Solar/Wind Harmer
3.589
24386605FR-22G C
Solar/Wind Harmer
2.392
24387005FR-3G C
Solar/Wind Harmer
2.368
274880W4-005 GEN4
Solar/Wind Harmer
1.7
274863CRW1-WTG
Solar/Wind Harmer
3.307
274864CRW2-WTG
Solar/Wind Harmer
3.307
274888KELLY CRK;1U
Solar/Wind Harmer
3.828
276893AG1-478 C
Solar/Wind Harmer
0.224
276602WESTBROOK C
Solar/Wind Harmer
1.152
276603SUBLETTE C
Solar/Wind Harmer
0.548
957891AF2-083 GEN
Solar/Wind Harmer
0.404
252510AF1-249 C
Solar/Wind Helper
0.172
253394AE2-221_GEN
Solar/Wind Helper
0.74
253398AE2-221_GEN2
Solar/Wind Helper
0.74
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.225
24791305MDL-5G
Solar/Wind Harmer
1.565
276726Z2-087_GEN
Solar/Wind Harmer
4.438
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.091
944221AF1-090 GEN
Solar/Wind Harmer
8.739
270526AF1-158 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
2.16
276741O09 GEN1
Solar/Wind Harmer
2.235
270518AE2-148 GEN
Solar/Wind Helper
2.274
270340AC2-060 GEN
Solar/Wind Helper
0.395
946031AF1-268 GEN
Solar/Wind Harmer
0.497
965651AG1-433 GEN
Solar/Wind Harmer
8.932
970289AG2-191 GEN
Solar/Wind Harmer
0.093
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
0.845
957381AF2-032 GEN
Solar/Wind Harmer
0.056
276916AD2-100_GEN
Solar/Wind Harmer
0.589
972181SS23-001
Solar/Wind Harmer
0.28
274847GR RIDGE ;BU
Solar/Wind Harmer
3.213
274849CRESCENT ;1U
Solar/Wind Harmer
1.165
959091AF2-200 GEN
Solar/Wind Harmer
0.545
253333AC1-068 GEN
Solar/Wind Helper
0.163
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.213
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053
SIGELTFEXP_SIGE->PJM
CLTF
0.233
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.33
NYPJM->LTFIMP_NY
CLTF
0.729
TVALTFEXP_TVA->PJM
CLTF
1.829
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.002
WECLTFEXP_WEC->PJM
CLTF
1.782
LAGNLTFEXP_LAGN->PJM
CLTF
4.587
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.192
LGEELTFEXP_LGEE->PJM
CLTF
1.394
MECLTFEXP_MEC->PJM
CLTF
7.114
AH1-155LTFEXP_AH1-155->PJM
LTF
0.179

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.01 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2479.4
MW Contribution:
0.4
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
4.279
961761AG1-017 GEN
Solar/Wind Harmer
0.489
247536S-71 GEN
Solar/Wind Harmer
4.101
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0.641
970349AG2-230 GEN
Solar/Wind Harmer
0.421
971347AH1-153 GEN
Solar/Wind Harmer
0.14
276615X2-022 GEN
Solar/Wind Harmer
1.269
939401AE1-172 GEN
Solar/Wind Harmer
11.084
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.277
926823AC1-168 GEN
Solar/Wind Harmer
3.347
274857EASY ROAD;U1
Solar/Wind Harmer
2.497
252507AC2-088 GEN
Solar/Wind Helper
0.344
24729205KEY G1
50/50
6.064
24379505HDWTR1G C
Solar/Wind Harmer
13.687
270004AE1-209 GEN
Solar/Wind Harmer
10.901
270201AC2-176 GEN
Solar/Wind Harmer
5.026
970885AG2-551 GEN
Solar/Wind Harmer
1.603
963741AG1-226 GEN
Solar/Wind Harmer
1.418
24386205FR-12G C
Solar/Wind Harmer
2.469
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.596
276686W4-005 GEN3
Solar/Wind Harmer
1.68
24726805LAWG2B
50/50
3.434
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.465
24697905MDL-4G C
Solar/Wind Harmer
1.546
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.333
965091AG1-374 GEN
Solar/Wind Harmer
0.842
276843GEN-1.7
Solar/Wind Harmer
0.367
958011AF2-095 GEN
Solar/Wind Harmer
0.398
276691AA1-018 GEN1
Solar/Wind Harmer
0.295
958491AF2-143 GEN
Solar/Wind Harmer
0.41
276646AC1-214 GEN2
Solar/Wind Harmer
0.839
274878BISHOP HL;2U
Solar/Wind Harmer
2.104
970819AG2-516 GEN
Solar/Wind Harmer
0.321
965931AG1-462 GEN
Solar/Wind Harmer
0.667
943021AE2-325 GEN
Solar/Wind Harmer
1.637
241972AD1-140 GEN
Solar/Wind Helper
0.889
945631AF1-228 GEN
Solar/Wind Helper
0.511
25194708EBND2
50/50
6.209
24699105WLD G1 C
Solar/Wind Harmer
4.279
270031AE2-169
Solar/Wind Harmer
0.443
270383AD1-128 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
9.652
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.684
971917AH1-482 GEN
Solar/Wind Harmer
4.5
276655WTG1_EQ
Solar/Wind Harmer
4.839
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.208
971067AG2-660 GEN
Solar/Wind Harmer
1.077
252509AD1-136 GEN
Solar/Wind Helper
0.049
270186AC1-089 GEN
Solar/Wind Helper
0.597
24726905LAWG2S
50/50
5.63
24726705LAWG2A
50/50
3.654
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
17.723
970883AG2-550 GEN
Solar/Wind Harmer
0.401
970193AG2-126 GEN
Solar/Wind Harmer
0.502
24385905FR-11G C
Solar/Wind Harmer
4.649
24697605MDL-3G C
Solar/Wind Harmer
2.319
270181AB1-006 GEN2
Solar/Wind Harmer
0.464
274853TWINGROVE;U1
Solar/Wind Harmer
4.333
959611AF2-252 GEN
Solar/Wind Harmer
1.122
960611AF2-352 GEN
Solar/Wind Harmer
1.122
274887GEN-1.85
Solar/Wind Harmer
3.408
970833AG2-524 GEN
Solar/Wind Harmer
0.303
276868AE1-113 GEN
Solar/Wind Harmer
6.393
962781AG1-127 GEN
Solar/Wind Harmer
0.258
970031AG2-029 GEN
Solar/Wind Harmer
0.675
971171AH1-044 GEN
Solar/Wind Harmer
0.538
270063AE2-323 C
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
7.816
253415AE1-040 GEN
Solar/Wind Helper
0.168
961171AF2-408 GEN
50/50
9.449
970289AG2-191 GEN
Solar/Wind Harmer
0.643
970291AG2-192 GEN
Solar/Wind Harmer
0.351
276785W4-005 GEN1
Solar/Wind Harmer
1.68
276849AB2-070 GEN2
Solar/Wind Harmer
1.442
274871GR RIDGE ;2U
Solar/Wind Harmer
3.497
943121AE2-341 GEN
Solar/Wind Harmer
0.411
274848CAMPGROVE;RU
Solar/Wind Harmer
3.162
957471AF2-041 GEN
Solar/Wind Harmer
0.807
270449AD2-020 GEN
Solar/Wind Harmer
0
252524AE2-267 GEN
Solar/Wind Helper
0.57
253317AC1-085 GEN4
Solar/Wind Helper
0.7
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253400AC2-068 GEN
Solar/Wind Helper
0.08
253383AE2-342_GEN
Solar/Wind Helper
0.138
241973AD2-163_GEN1
Solar/Wind Helper
0.3
270024AE2-089 GEN
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.442
276806AD2-047 C O1
Solar/Wind Harmer
8.519
274877BISHOP HL;1U
Solar/Wind Harmer
2.104
971341AH1-150 GEN
Solar/Wind Harmer
0.538
276820AF1-078_GEN
Solar/Wind Helper
0.216
253316AC1-085 GEN3
Solar/Wind Helper
0.7
253433AC1-085 GEN1
Solar/Wind Helper
0.443
253349AC2-067 GEN
Solar/Wind Helper
0.2
253343AC1-166 GEN
Solar/Wind Helper
0.165
970291AG2-192 GEN
Solar/Wind Harmer
0.063
963791AG1-232 GEN
Solar/Wind Harmer
0.447
270445AC2-157 GEN2
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
1.546
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.421
970169AG2-114 GEN
Solar/Wind Harmer
0.279
965681AG1-436 GEN
Solar/Wind Harmer
0.346
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.913
943591AF1-030 GEN
Solar/Wind Harmer
0.274
971343AH1-151 GEN
Solar/Wind Harmer
0.538
971087AG2-675 GEN
Solar/Wind Harmer
1.675
960071AF2-298 GEN
Solar/Wind Helper
0.263
253303V4-073 C
Solar/Wind Helper
0.011
241974AD2-163_GEN2
Solar/Wind Helper
0.3
253338AC1-165 GEN
Solar/Wind Helper
0.165
241955AC1-078 GEN
Solar/Wind Helper
0.553
24726505LAWG1B
50/50
3.654
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
2.97
945371AF1-202 GEN
Solar/Wind Harmer
9.666
970825AG2-519 GEN
Solar/Wind Harmer
2.567
958861AF2-177 GEN
Solar/Wind Harmer
18.276
270032AE2-172
Solar/Wind Harmer
4.141
942221AE2-234 GEN
Solar/Wind Harmer
0.149
270543AE2-219 C
Solar/Wind Harmer
0.401
24691005MDL-2G C
Solar/Wind Harmer
2.319
957841AF2-078 GEN
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
0.26
276621W2-048 GEN
Solar/Wind Harmer
4.04
942481AE2-261 GEN
Solar/Wind Harmer
0.83
971997AH1-543 GEN
Solar/Wind Harmer
0.431
276889AE2-281 GEN
Solar/Wind Harmer
1.063
962691AG1-118 GEN
Solar/Wind Harmer
0.814
276158O29GEN2
Solar/Wind Harmer
2.349
276708O09 GEN2
Solar/Wind Harmer
2.206
270505AE1-170 C O1
Solar/Wind Harmer
0.397
270367AC2-061_GEN
Solar/Wind Helper
0.537
962581AG1-107 GEN
Solar/Wind Helper
0.635
24726605LAWG1S
50/50
5.63
24729405KEY G3
50/50
6.167
24729505KEY G4
50/50
6.064
970825AG2-519 GEN
Solar/Wind Harmer
0.401
970241AG2-163 GEN
Solar/Wind Harmer
0.788
270043AE2-236 GEN
Solar/Wind Harmer
0.169
971605AH1-302 GEN
Solar/Wind Harmer
4.371
276174W4-005 GEN2
Solar/Wind Harmer
1.68
276668AB2-070 GEN1
Solar/Wind Harmer
1.442
939741AE1-205 GEN
Solar/Wind Harmer
0.562
942111AE2-223 GEN
Solar/Wind Harmer
6.575
276838X2-022 GEN2
Solar/Wind Harmer
0.151
276897AD1-100 C
Solar/Wind Harmer
36.785
970941AG2-585 GEN
Solar/Wind Harmer
0.152
276805AD2-038 GEN
Solar/Wind Harmer
3.201
970569AG2-363 GEN
Solar/Wind Harmer
0.816
971771AH1-392 GEN
Solar/Wind Harmer
0.244
276645AC1-214 GEN1
Solar/Wind Harmer
0.839
276157O29GEN1
Solar/Wind Harmer
2.349
961491AF2-440 GEN
Solar/Wind Helper
0.212
24726405LAWG1A
50/50
3.654
270240V3-007_GEN2
Solar/Wind Harmer
10.716
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.828
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
1.094
970571AG2-364 GEN
Solar/Wind Harmer
0.544
274850MENDOTA H;RU
Solar/Wind Harmer
1.602
276863AD2-134 GEN
Solar/Wind Harmer
1.115
276861AD2-134 GEN
Solar/Wind Harmer
1.115
274856ECOGROVE ;U1
Solar/Wind Harmer
2.088
971681AH1-341 GEN
Solar/Wind Harmer
0.401
276903AD2-071 C
Solar/Wind Harmer
0.528
944531AF1-118 GEN
Solar/Wind Harmer
1.73
945391AF1-204 GEN
Solar/Wind Harmer
13.313
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.297
965911AG1-460 GEN
Solar/Wind Harmer
0.666
970707AG2-453 GEN
Solar/Wind Harmer
0.773
970833AG2-524 GEN
Solar/Wind Harmer
2.427
958481AF2-142 GEN
Solar/Wind Harmer
0.411
274862TOP CROP ;2U
Solar/Wind Harmer
3.208
274879MINONK ;1U
Solar/Wind Harmer
4.262
971675AH1-338 GEN
Solar/Wind Harmer
0.486
253406AD2-031_GEN
Solar/Wind Helper
0.232
942051AE2-217 GEN
Solar/Wind Helper
0.61
961161AF2-407 GEN
50/50
35.536
270599AE1-208 GEN
Solar/Wind Harmer
0.443
971029AG2-637 GEN
Solar/Wind Harmer
0.536
24386405FR-21G C
Solar/Wind Harmer
2.365
276763AC1-053 GEN1
Solar/Wind Harmer
2.192
972231SS25-0005
Solar/Wind Harmer
0.442
276876AE1-163_GEN2
Solar/Wind Harmer
3.721
274855GSG-6 ;RU
Solar/Wind Harmer
2.305
276782AC1-033 GEN
Solar/Wind Harmer
2.121
971411AH1-196 GEN
Solar/Wind Harmer
0.404
961051AF2-396 GEN
Solar/Wind Harmer
0.525
961051AF2-396 GEN
Solar/Wind Harmer
4.201
938861AE1-114 GEN
Solar/Wind Harmer
6.254
274858EASY ROAD;U2
Solar/Wind Harmer
2.497
945111AF1-176 GEN
Solar/Wind Harmer
0.472
945111AF1-176 GEN
Solar/Wind Harmer
2.573
253378AE2-206_GEN
Solar/Wind Helper
0.481
24729305KEY G2
50/50
6.167
270005AE1-210 C O1
Solar/Wind Harmer
10.901
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.744
270071AF1-092 GEN
Solar/Wind Harmer
0.505
24387305FR-4G C
Solar/Wind Harmer
3.547
24386605FR-22G C
Solar/Wind Harmer
2.365
24387005FR-3G C
Solar/Wind Harmer
2.341
274880W4-005 GEN4
Solar/Wind Harmer
1.68
274863CRW1-WTG
Solar/Wind Harmer
3.265
274864CRW2-WTG
Solar/Wind Harmer
3.265
274888KELLY CRK;1U
Solar/Wind Harmer
3.775
276893AG1-478 C
Solar/Wind Harmer
0.22
276602WESTBROOK C
Solar/Wind Harmer
1.137
276603SUBLETTE C
Solar/Wind Harmer
0.541
957891AF2-083 GEN
Solar/Wind Harmer
0.398
252510AF1-249 C
Solar/Wind Helper
0.173
253394AE2-221_GEN
Solar/Wind Helper
0.746
253398AE2-221_GEN2
Solar/Wind Helper
0.746
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.174
24791305MDL-5G
Solar/Wind Harmer
1.546
276726Z2-087_GEN
Solar/Wind Harmer
4.384
941551AE2-152 GEN
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
8.642
965791AG1-447 GEN
Solar/Wind Harmer
3.045
276882AE2-255 GEN
Solar/Wind Harmer
2.131
270526AF1-158 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
2.206
270518AE2-148 GEN
Solar/Wind Helper
2.304
270340AC2-060 GEN
Solar/Wind Helper
0.399
276764AC1-053 GEN2
Solar/Wind Harmer
2.192
276911AD2-131_GEN
Solar/Wind Harmer
0.139
276872AE1-163_GEN1
Solar/Wind Harmer
3.721
274872LEEDK;1U
Solar/Wind Harmer
5.072
274851PROVIDENC;RU
Solar/Wind Harmer
1.563
959081AF2-199 GEN
Solar/Wind Harmer
0.269
25183208HLCRTG
Solar/Wind Helper
1.146
253325AC1-069 GEN
Solar/Wind Helper
0.165
946031AF1-268 GEN
Solar/Wind Harmer
0.493
965651AG1-433 GEN
Solar/Wind Harmer
8.861
970289AG2-191 GEN
Solar/Wind Harmer
0.093
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
0.834
957381AF2-032 GEN
Solar/Wind Harmer
0.056
276916AD2-100_GEN
Solar/Wind Harmer
0.583
972181SS23-001
Solar/Wind Harmer
0.277
274847GR RIDGE ;BU
Solar/Wind Harmer
3.17
274849CRESCENT ;1U
Solar/Wind Harmer
1.15
959091AF2-200 GEN
Solar/Wind Harmer
0.538
253333AC1-068 GEN
Solar/Wind Helper
0.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.716
LGEELTFEXP_LGEE->PJM
CLTF
1.364
MECLTFEXP_MEC->PJM
CLTF
7.026
AH1-155LTFEXP_AH1-155->PJM
LTF
0.176
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.917
WECLTFEXP_WEC->PJM
CLTF
1.758
LAGNLTFEXP_LAGN->PJM
CLTF
4.541
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.401
NYPJM->LTFIMP_NY
CLTF
0.715
TVALTFEXP_TVA->PJM
CLTF
1.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.247
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
SIGELTFEXP_SIGE->PJM
CLTF
0.23

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.64 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2470.96
MW Contribution:
0.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728705AND G3
50/50
13.997
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
6.608
961761AG1-017 GEN
Solar/Wind Harmer
0.815
247536S-71 GEN
Solar/Wind Harmer
7.289
276615X2-022 GEN
Solar/Wind Harmer
1.304
276656WTG2_EQ
Solar/Wind Harmer
0.645
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
10.902
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.268
926823AC1-168 GEN
Solar/Wind Harmer
3.292
970349AG2-230 GEN
Solar/Wind Harmer
0.402
971347AH1-153 GEN
Solar/Wind Harmer
0.134
274857EASY ROAD;U1
Solar/Wind Harmer
2.433
252507AC2-088 GEN
Solar/Wind Helper
0.43
276903AD2-071 C
Solar/Wind Harmer
0.802
944531AF1-118 GEN
Solar/Wind Harmer
2.515
945391AF1-204 GEN
Solar/Wind Harmer
15.38
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.293
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.119
24791305MDL-5G
Solar/Wind Harmer
1.526
24726805LAWG2B
50/50
5.929
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.772
24697905MDL-4G C
Solar/Wind Harmer
1.526
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.378
965091AG1-374 GEN
Solar/Wind Harmer
0.85
276843GEN-1.7
Solar/Wind Harmer
0.356
958011AF2-095 GEN
Solar/Wind Harmer
0.387
276691AA1-018 GEN1
Solar/Wind Harmer
0.288
958491AF2-143 GEN
Solar/Wind Harmer
0.401
276646AC1-214 GEN2
Solar/Wind Harmer
0.827
274878BISHOP HL;2U
Solar/Wind Harmer
2.074
943021AE2-325 GEN
Solar/Wind Harmer
1.651
970819AG2-516 GEN
Solar/Wind Harmer
0.313
965931AG1-462 GEN
Solar/Wind Harmer
0.653
965911AG1-460 GEN
Solar/Wind Harmer
0.686
970833AG2-524 GEN
Solar/Wind Harmer
2.354
274862TOP CROP ;2U
Solar/Wind Harmer
3.128
958481AF2-142 GEN
Solar/Wind Harmer
0.401
274879MINONK ;1U
Solar/Wind Harmer
4.165
970707AG2-453 GEN
Solar/Wind Harmer
0.744
971675AH1-338 GEN
Solar/Wind Harmer
0.472
253406AD2-031_GEN
Solar/Wind Helper
0.219
942051AE2-217 GEN
Solar/Wind Helper
0.479
24726905LAWG2S
50/50
9.719
24726705LAWG2A
50/50
6.308
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
26.967
970883AG2-550 GEN
Solar/Wind Harmer
0.753
970193AG2-126 GEN
Solar/Wind Harmer
0.58
970031AG2-029 GEN
Solar/Wind Harmer
0.774
241972AD1-140 GEN
Solar/Wind Helper
0.725
945631AF1-228 GEN
Solar/Wind Helper
0.439
944221AF1-090 GEN
Solar/Wind Harmer
8.946
276726Z2-087_GEN
Solar/Wind Harmer
4.415
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
2.958
276882AE2-255 GEN
Solar/Wind Harmer
2.083
276741O09 GEN1
Solar/Wind Harmer
2.159
270518AE2-148 GEN
Solar/Wind Helper
1.988
270340AC2-060 GEN
Solar/Wind Helper
0.398
339221AD2-048_GEN
Solar/Wind Helper
0.219
24726505LAWG1B
50/50
6.308
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
4.892
970825AG2-519 GEN
Solar/Wind Harmer
4.152
945371AF1-202 GEN
Solar/Wind Harmer
15.077
958861AF2-177 GEN
Solar/Wind Harmer
28.062
270032AE2-172
Solar/Wind Harmer
6.246
270543AE2-219 C
Solar/Wind Harmer
0.753
942221AE2-234 GEN
Solar/Wind Harmer
0.226
965021AG1-366 GEN
Solar/Wind Harmer
1.243
24691005MDL-2G C
Solar/Wind Harmer
2.288
971993AH1-541 GEN
Solar/Wind Harmer
0.267
276621W2-048 GEN
Solar/Wind Harmer
4.151
957841AF2-078 GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
0.855
971997AH1-543 GEN
Solar/Wind Harmer
0.422
276889AE2-281 GEN
Solar/Wind Harmer
1.042
270505AE1-170 C O1
Solar/Wind Harmer
0.399
962691AG1-118 GEN
Solar/Wind Harmer
0.79
276158O29GEN2
Solar/Wind Harmer
2.299
276708O09 GEN2
Solar/Wind Harmer
2.159
270367AC2-061_GEN
Solar/Wind Helper
0.514
962581AG1-107 GEN
Solar/Wind Helper
0.591
24726405LAWG1A
50/50
6.308
270240V3-007_GEN2
Solar/Wind Harmer
17.65
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
1.249
965011AG1-365 GEN
Solar/Wind Harmer
0.311
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.48
945111AF1-176 GEN
Solar/Wind Harmer
2.617
970073AG2-061 GEN
Solar/Wind Harmer
1.069
970571AG2-364 GEN
Solar/Wind Harmer
0.534
274850MENDOTA H;RU
Solar/Wind Harmer
1.557
276863AD2-134 GEN
Solar/Wind Harmer
1.083
276861AD2-134 GEN
Solar/Wind Harmer
1.083
274856ECOGROVE ;U1
Solar/Wind Harmer
2.033
971681AH1-341 GEN
Solar/Wind Harmer
0.391
938861AE1-114 GEN
Solar/Wind Harmer
6.093
274858EASY ROAD;U2
Solar/Wind Harmer
2.433
253378AE2-206_GEN
Solar/Wind Helper
0.327
24726605LAWG1S
50/50
9.719
24729405KEY G3
50/50
9.086
24729505KEY G4
50/50
8.934
970825AG2-519 GEN
Solar/Wind Harmer
0.648
270043AE2-236 GEN
Solar/Wind Harmer
0.203
970241AG2-163 GEN
Solar/Wind Harmer
0.844
276174W4-005 GEN2
Solar/Wind Harmer
1.725
24385905FR-11G C
Solar/Wind Harmer
4.713
270063AE2-323 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
2.288
270181AB1-006 GEN2
Solar/Wind Harmer
0.458
274853TWINGROVE;U1
Solar/Wind Harmer
4.378
959611AF2-252 GEN
Solar/Wind Harmer
1.134
960611AF2-352 GEN
Solar/Wind Harmer
1.134
944231AF1-091 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
3.308
970833AG2-524 GEN
Solar/Wind Harmer
0.294
276868AE1-113 GEN
Solar/Wind Harmer
6.248
962781AG1-127 GEN
Solar/Wind Harmer
0.25
971171AH1-044 GEN
Solar/Wind Harmer
0.523
946321AF1-296 GEN
Solar/Wind Harmer
7.649
253415AE1-040 GEN
Solar/Wind Helper
0.164
339216AC1-074 GEN
Solar/Wind Helper
0.256
961161AF2-407 GEN
50/50
56.057
24728905RICHG2
50/50
5.791
270599AE1-208 GEN
Solar/Wind Harmer
0.695
971029AG2-637 GEN
Solar/Wind Harmer
1.08
24386405FR-21G C
Solar/Wind Harmer
2.397
276763AC1-053 GEN1
Solar/Wind Harmer
2.251
972231SS25-0005
Solar/Wind Harmer
0.431
276876AE1-163_GEN2
Solar/Wind Harmer
3.647
276782AC1-033 GEN
Solar/Wind Harmer
2.091
961051AF2-396 GEN
Solar/Wind Harmer
0.531
961051AF2-396 GEN
Solar/Wind Harmer
4.249
274855GSG-6 ;RU
Solar/Wind Harmer
2.239
971411AH1-196 GEN
Solar/Wind Harmer
0.393
276668AB2-070 GEN1
Solar/Wind Harmer
1.48
276838X2-022 GEN2
Solar/Wind Harmer
0.155
971605AH1-302 GEN
Solar/Wind Harmer
4.256
939741AE1-205 GEN
Solar/Wind Harmer
0.566
942111AE2-223 GEN
Solar/Wind Harmer
6.622
971771AH1-392 GEN
Solar/Wind Harmer
0.245
276897AD1-100 C
Solar/Wind Harmer
35.724
970941AG2-585 GEN
Solar/Wind Harmer
0.148
276805AD2-038 GEN
Solar/Wind Harmer
3.128
276645AC1-214 GEN1
Solar/Wind Harmer
0.827
970569AG2-363 GEN
Solar/Wind Harmer
0.801
276157O29GEN1
Solar/Wind Harmer
2.299
961491AF2-440 GEN
Solar/Wind Helper
0.197
24729305KEY G2
50/50
9.086
270005AE1-210 C O1
Solar/Wind Harmer
17.522
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.239
270071AF1-092 GEN
Solar/Wind Harmer
0.615
24387305FR-4G C
Solar/Wind Harmer
3.596
24386605FR-22G C
Solar/Wind Harmer
2.397
24387005FR-3G C
Solar/Wind Harmer
2.373
274880W4-005 GEN4
Solar/Wind Harmer
1.725
274863CRW1-WTG
Solar/Wind Harmer
3.228
274864CRW2-WTG
Solar/Wind Harmer
3.228
274888KELLY CRK;1U
Solar/Wind Harmer
3.664
276893AG1-478 C
Solar/Wind Harmer
0.214
957891AF2-083 GEN
Solar/Wind Harmer
0.401
276602WESTBROOK C
Solar/Wind Harmer
1.104
276603SUBLETTE C
Solar/Wind Harmer
0.528
252510AF1-249 C
Solar/Wind Helper
0.15
253394AE2-221_GEN
Solar/Wind Helper
0.719
253398AE2-221_GEN2
Solar/Wind Helper
0.719
961171AF2-408 GEN
50/50
15.137
24728605AND G2
50/50
6.613
970289AG2-191 GEN
Solar/Wind Harmer
0.94
970291AG2-192 GEN
Solar/Wind Harmer
0.513
276785W4-005 GEN1
Solar/Wind Harmer
1.725
276849AB2-070 GEN2
Solar/Wind Harmer
1.48
274871GR RIDGE ;2U
Solar/Wind Harmer
3.392
274848CAMPGROVE;RU
Solar/Wind Harmer
3.123
943121AE2-341 GEN
Solar/Wind Harmer
0.397
270449AD2-020 GEN
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
0.785
252524AE2-267 GEN
Solar/Wind Helper
0.451
253317AC1-085 GEN4
Solar/Wind Helper
0.707
253432AC1-085 GEN2
Solar/Wind Helper
0.024
241973AD2-163_GEN1
Solar/Wind Helper
0.227
970291AG2-192 GEN
Solar/Wind Harmer
0.093
963791AG1-232 GEN
Solar/Wind Harmer
0.671
24755605MDL-5G
Solar/Wind Harmer
1.526
270445AC2-157 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.424
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
0.277
965681AG1-436 GEN
Solar/Wind Harmer
0.336
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.841
943591AF1-030 GEN
Solar/Wind Harmer
0.265
971343AH1-151 GEN
Solar/Wind Harmer
0.523
971087AG2-675 GEN
Solar/Wind Harmer
1.64
253303V4-073 C
Solar/Wind Helper
0.008
960071AF2-298 GEN
Solar/Wind Helper
0.181
253338AC1-165 GEN
Solar/Wind Helper
0.154
241974AD2-163_GEN2
Solar/Wind Helper
0.227
247621Y3-024
50/50
0.493
24728505AND G1
50/50
6.613
270024AE2-089 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.48
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
8.268
274877BISHOP HL;1U
Solar/Wind Harmer
2.074
971341AH1-150 GEN
Solar/Wind Harmer
0.523
253316AC1-085 GEN3
Solar/Wind Helper
0.707
253433AC1-085 GEN1
Solar/Wind Helper
0.448
276820AF1-078_GEN
Solar/Wind Helper
0.147
253343AC1-166 GEN
Solar/Wind Helper
0.154
946031AF1-268 GEN
Solar/Wind Harmer
0.807
965651AG1-433 GEN
Solar/Wind Harmer
13.484
970289AG2-191 GEN
Solar/Wind Harmer
0.135
276916AD2-100_GEN
Solar/Wind Harmer
0.601
957381AF2-032 GEN
Solar/Wind Harmer
0.057
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
0.269
274847GR RIDGE ;BU
Solar/Wind Harmer
3.075
274849CRESCENT ;1U
Solar/Wind Harmer
1.135
972207SS24-0001
Solar/Wind Harmer
0.8
959091AF2-200 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Helper
0.154
943111AE2-339 GEN
Solar/Wind Helper
0.102
24728805RICHG1
50/50
5.791
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.695
24699105WLD G1 C
Solar/Wind Harmer
6.608
963841AG1-237 GEN
Solar/Wind Harmer
10.078
959331AF2-224 GEN
Solar/Wind Harmer
0.311
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.622
276655WTG1_EQ
Solar/Wind Harmer
4.873
971917AH1-482 GEN
Solar/Wind Harmer
4.379
965041AG1-368 GEN
Solar/Wind Harmer
0.27
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.128
971067AG2-660 GEN
Solar/Wind Harmer
1.047
252509AD1-136 GEN
Solar/Wind Helper
0.061
270186AC1-089 GEN
Solar/Wind Helper
0.6
339243AC2-075 GEN1
Solar/Wind Helper
0.064
24729205KEY G1
50/50
8.934
24379505HDWTR1G C
Solar/Wind Harmer
22.542
270004AE1-209 GEN
Solar/Wind Harmer
17.522
270201AC2-176 GEN
Solar/Wind Harmer
8.378
970885AG2-551 GEN
Solar/Wind Harmer
3.01
963741AG1-226 GEN
Solar/Wind Harmer
1.519
24386205FR-12G C
Solar/Wind Harmer
2.503
276686W4-005 GEN3
Solar/Wind Harmer
1.725
276764AC1-053 GEN2
Solar/Wind Harmer
2.251
276911AD2-131_GEN
Solar/Wind Harmer
0.143
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.579
276872AE1-163_GEN1
Solar/Wind Harmer
3.647
274851PROVIDENC;RU
Solar/Wind Harmer
1.542
274872LEEDK;1U
Solar/Wind Harmer
4.922
959081AF2-199 GEN
Solar/Wind Harmer
0.262
25183208HLCRTG
Solar/Wind Helper
1.201
253325AC1-069 GEN
Solar/Wind Helper
0.154
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.447
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.381
MECLTFEXP_MEC->PJM
CLTF
6.886
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.069
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.195
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.031
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.851
WECLTFEXP_WEC->PJM
CLTF
1.709
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.203
SIGELTFEXP_SIGE->PJM
CLTF
0.245
NYPJM->LTFIMP_NY
CLTF
0.75
TVALTFEXP_TVA->PJM
CLTF
1.407
LAGNLTFEXP_LAGN->PJM
CLTF
3.93

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.64 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2470.93
MW Contribution:
0.39
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24728705AND G3
50/50
13.997
926881AC1-175 GEN
Solar/Wind Harmer
0
24725505WLD G2 C
Solar/Wind Harmer
6.608
961761AG1-017 GEN
Solar/Wind Harmer
0.815
247536S-71 GEN
Solar/Wind Harmer
7.289
276615X2-022 GEN
Solar/Wind Harmer
1.304
276656WTG2_EQ
Solar/Wind Harmer
0.645
959141AF2-205 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
10.902
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.268
926823AC1-168 GEN
Solar/Wind Harmer
3.292
970349AG2-230 GEN
Solar/Wind Harmer
0.402
971347AH1-153 GEN
Solar/Wind Harmer
0.134
274857EASY ROAD;U1
Solar/Wind Harmer
2.433
252507AC2-088 GEN
Solar/Wind Helper
0.43
24726805LAWG2B
50/50
5.929
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.772
24697905MDL-4G C
Solar/Wind Harmer
1.526
945421AF1-207 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
4.378
965091AG1-374 GEN
Solar/Wind Harmer
0.85
276843GEN-1.7
Solar/Wind Harmer
0.356
958011AF2-095 GEN
Solar/Wind Harmer
0.387
276691AA1-018 GEN1
Solar/Wind Harmer
0.288
958491AF2-143 GEN
Solar/Wind Harmer
0.401
276646AC1-214 GEN2
Solar/Wind Harmer
0.827
274878BISHOP HL;2U
Solar/Wind Harmer
2.074
943021AE2-325 GEN
Solar/Wind Harmer
1.651
970819AG2-516 GEN
Solar/Wind Harmer
0.313
965931AG1-462 GEN
Solar/Wind Harmer
0.653
241972AD1-140 GEN
Solar/Wind Helper
0.725
945631AF1-228 GEN
Solar/Wind Helper
0.439
24728805RICHG1
50/50
5.791
270383AD1-128 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.695
24699105WLD G1 C
Solar/Wind Harmer
6.608
963841AG1-237 GEN
Solar/Wind Harmer
10.078
959331AF2-224 GEN
Solar/Wind Harmer
0.311
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
4.622
276655WTG1_EQ
Solar/Wind Harmer
4.873
971917AH1-482 GEN
Solar/Wind Harmer
4.379
965041AG1-368 GEN
Solar/Wind Harmer
0.27
960681AF2-359 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
3.128
971067AG2-660 GEN
Solar/Wind Harmer
1.047
252509AD1-136 GEN
Solar/Wind Helper
0.061
270186AC1-089 GEN
Solar/Wind Helper
0.6
339243AC2-075 GEN1
Solar/Wind Helper
0.064
24726905LAWG2S
50/50
9.719
24726705LAWG2A
50/50
6.308
270437AC2-090 C
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
26.967
970883AG2-550 GEN
Solar/Wind Harmer
0.753
970193AG2-126 GEN
Solar/Wind Harmer
0.58
970031AG2-029 GEN
Solar/Wind Harmer
0.774
24385905FR-11G C
Solar/Wind Harmer
4.713
270063AE2-323 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
2.288
270181AB1-006 GEN2
Solar/Wind Harmer
0.458
274853TWINGROVE;U1
Solar/Wind Harmer
4.378
959611AF2-252 GEN
Solar/Wind Harmer
1.134
960611AF2-352 GEN
Solar/Wind Harmer
1.134
944231AF1-091 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
3.308
970833AG2-524 GEN
Solar/Wind Harmer
0.294
276868AE1-113 GEN
Solar/Wind Harmer
6.248
962781AG1-127 GEN
Solar/Wind Harmer
0.25
971171AH1-044 GEN
Solar/Wind Harmer
0.523
946321AF1-296 GEN
Solar/Wind Harmer
7.649
253415AE1-040 GEN
Solar/Wind Helper
0.164
339216AC1-074 GEN
Solar/Wind Helper
0.256
961171AF2-408 GEN
50/50
15.137
24728605AND G2
50/50
6.613
970289AG2-191 GEN
Solar/Wind Harmer
0.94
970291AG2-192 GEN
Solar/Wind Harmer
0.513
276785W4-005 GEN1
Solar/Wind Harmer
1.725
276849AB2-070 GEN2
Solar/Wind Harmer
1.48
274871GR RIDGE ;2U
Solar/Wind Harmer
3.392
274848CAMPGROVE;RU
Solar/Wind Harmer
3.123
943121AE2-341 GEN
Solar/Wind Harmer
0.397
270449AD2-020 GEN
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
0.785
252524AE2-267 GEN
Solar/Wind Helper
0.451
253317AC1-085 GEN4
Solar/Wind Helper
0.707
253432AC1-085 GEN2
Solar/Wind Helper
0.024
241973AD2-163_GEN1
Solar/Wind Helper
0.227
247621Y3-024
50/50
0.493
24728505AND G1
50/50
6.613
270024AE2-089 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
1.48
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
8.268
274877BISHOP HL;1U
Solar/Wind Harmer
2.074
971341AH1-150 GEN
Solar/Wind Harmer
0.523
253316AC1-085 GEN3
Solar/Wind Helper
0.707
253433AC1-085 GEN1
Solar/Wind Helper
0.448
276820AF1-078_GEN
Solar/Wind Helper
0.147
253343AC1-166 GEN
Solar/Wind Helper
0.154
970291AG2-192 GEN
Solar/Wind Harmer
0.093
963791AG1-232 GEN
Solar/Wind Harmer
0.671
24755605MDL-5G
Solar/Wind Harmer
1.526
270445AC2-157 GEN2
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
0.424
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
0.277
965681AG1-436 GEN
Solar/Wind Harmer
0.336
276901AD2-066 C O1
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
2.841
943591AF1-030 GEN
Solar/Wind Harmer
0.265
971343AH1-151 GEN
Solar/Wind Harmer
0.523
971087AG2-675 GEN
Solar/Wind Harmer
1.64
253303V4-073 C
Solar/Wind Helper
0.008
960071AF2-298 GEN
Solar/Wind Helper
0.181
253338AC1-165 GEN
Solar/Wind Helper
0.154
241974AD2-163_GEN2
Solar/Wind Helper
0.227
24726505LAWG1B
50/50
6.308
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
4.892
970825AG2-519 GEN
Solar/Wind Harmer
4.152
945371AF1-202 GEN
Solar/Wind Harmer
15.077
958861AF2-177 GEN
Solar/Wind Harmer
28.062
270032AE2-172
Solar/Wind Harmer
6.246
270543AE2-219 C
Solar/Wind Harmer
0.753
942221AE2-234 GEN
Solar/Wind Harmer
0.226
965021AG1-366 GEN
Solar/Wind Harmer
1.243
24691005MDL-2G C
Solar/Wind Harmer
2.288
971993AH1-541 GEN
Solar/Wind Harmer
0.267
276621W2-048 GEN
Solar/Wind Harmer
4.151
957841AF2-078 GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
0.855
971997AH1-543 GEN
Solar/Wind Harmer
0.422
276889AE2-281 GEN
Solar/Wind Harmer
1.042
270505AE1-170 C O1
Solar/Wind Harmer
0.399
962691AG1-118 GEN
Solar/Wind Harmer
0.79
276158O29GEN2
Solar/Wind Harmer
2.299
276708O09 GEN2
Solar/Wind Harmer
2.159
270367AC2-061_GEN
Solar/Wind Helper
0.514
962581AG1-107 GEN
Solar/Wind Helper
0.591
24726605LAWG1S
50/50
9.719
24729405KEY G3
50/50
9.086
24729505KEY G4
50/50
8.934
970825AG2-519 GEN
Solar/Wind Harmer
0.648
270043AE2-236 GEN
Solar/Wind Harmer
0.203
970241AG2-163 GEN
Solar/Wind Harmer
0.844
276174W4-005 GEN2
Solar/Wind Harmer
1.725
276668AB2-070 GEN1
Solar/Wind Harmer
1.48
276838X2-022 GEN2
Solar/Wind Harmer
0.155
971605AH1-302 GEN
Solar/Wind Harmer
4.256
939741AE1-205 GEN
Solar/Wind Harmer
0.566
942111AE2-223 GEN
Solar/Wind Harmer
6.622
971771AH1-392 GEN
Solar/Wind Harmer
0.245
276897AD1-100 C
Solar/Wind Harmer
35.724
970941AG2-585 GEN
Solar/Wind Harmer
0.148
276805AD2-038 GEN
Solar/Wind Harmer
3.128
276645AC1-214 GEN1
Solar/Wind Harmer
0.827
970569AG2-363 GEN
Solar/Wind Harmer
0.801
276157O29GEN1
Solar/Wind Harmer
2.299
961491AF2-440 GEN
Solar/Wind Helper
0.197
276903AD2-071 C
Solar/Wind Harmer
0.802
944531AF1-118 GEN
Solar/Wind Harmer
2.515
945391AF1-204 GEN
Solar/Wind Harmer
15.38
966841AG1-555 GEN
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
0.293
965911AG1-460 GEN
Solar/Wind Harmer
0.686
970833AG2-524 GEN
Solar/Wind Harmer
2.354
274862TOP CROP ;2U
Solar/Wind Harmer
3.128
958481AF2-142 GEN
Solar/Wind Harmer
0.401
274879MINONK ;1U
Solar/Wind Harmer
4.165
970707AG2-453 GEN
Solar/Wind Harmer
0.744
971675AH1-338 GEN
Solar/Wind Harmer
0.472
253406AD2-031_GEN
Solar/Wind Helper
0.219
942051AE2-217 GEN
Solar/Wind Helper
0.479
961161AF2-407 GEN
50/50
56.057
24728905RICHG2
50/50
5.791
270599AE1-208 GEN
Solar/Wind Harmer
0.695
971029AG2-637 GEN
Solar/Wind Harmer
1.08
24386405FR-21G C
Solar/Wind Harmer
2.397
276763AC1-053 GEN1
Solar/Wind Harmer
2.251
972231SS25-0005
Solar/Wind Harmer
0.431
276876AE1-163_GEN2
Solar/Wind Harmer
3.647
276782AC1-033 GEN
Solar/Wind Harmer
2.091
961051AF2-396 GEN
Solar/Wind Harmer
0.531
961051AF2-396 GEN
Solar/Wind Harmer
4.249
274855GSG-6 ;RU
Solar/Wind Harmer
2.239
971411AH1-196 GEN
Solar/Wind Harmer
0.393
24726405LAWG1A
50/50
6.308
270240V3-007_GEN2
Solar/Wind Harmer
17.65
270209AC1-174_GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
1.249
965011AG1-365 GEN
Solar/Wind Harmer
0.311
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.48
945111AF1-176 GEN
Solar/Wind Harmer
2.617
970073AG2-061 GEN
Solar/Wind Harmer
1.069
970571AG2-364 GEN
Solar/Wind Harmer
0.534
274850MENDOTA H;RU
Solar/Wind Harmer
1.557
276863AD2-134 GEN
Solar/Wind Harmer
1.083
276861AD2-134 GEN
Solar/Wind Harmer
1.083
274856ECOGROVE ;U1
Solar/Wind Harmer
2.033
971681AH1-341 GEN
Solar/Wind Harmer
0.391
938861AE1-114 GEN
Solar/Wind Harmer
6.093
274858EASY ROAD;U2
Solar/Wind Harmer
2.433
253378AE2-206_GEN
Solar/Wind Helper
0.327
24729305KEY G2
50/50
9.086
270005AE1-210 C O1
Solar/Wind Harmer
17.522
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
1.239
270071AF1-092 GEN
Solar/Wind Harmer
0.615
24387305FR-4G C
Solar/Wind Harmer
3.596
24386605FR-22G C
Solar/Wind Harmer
2.397
24387005FR-3G C
Solar/Wind Harmer
2.373
274880W4-005 GEN4
Solar/Wind Harmer
1.725
274863CRW1-WTG
Solar/Wind Harmer
3.228
274864CRW2-WTG
Solar/Wind Harmer
3.228
274888KELLY CRK;1U
Solar/Wind Harmer
3.664
276893AG1-478 C
Solar/Wind Harmer
0.214
957891AF2-083 GEN
Solar/Wind Harmer
0.401
276602WESTBROOK C
Solar/Wind Harmer
1.104
276603SUBLETTE C
Solar/Wind Harmer
0.528
252510AF1-249 C
Solar/Wind Helper
0.15
253394AE2-221_GEN
Solar/Wind Helper
0.719
253398AE2-221_GEN2
Solar/Wind Helper
0.719
944541AF1-119 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
4.119
24791305MDL-5G
Solar/Wind Harmer
1.526
944221AF1-090 GEN
Solar/Wind Harmer
8.946
276726Z2-087_GEN
Solar/Wind Harmer
4.415
270526AF1-158 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
2.958
276882AE2-255 GEN
Solar/Wind Harmer
2.083
276741O09 GEN1
Solar/Wind Harmer
2.159
270518AE2-148 GEN
Solar/Wind Helper
1.988
270340AC2-060 GEN
Solar/Wind Helper
0.398
339221AD2-048_GEN
Solar/Wind Helper
0.219
24729205KEY G1
50/50
8.934
24379505HDWTR1G C
Solar/Wind Harmer
22.542
270004AE1-209 GEN
Solar/Wind Harmer
17.522
270201AC2-176 GEN
Solar/Wind Harmer
8.378
970885AG2-551 GEN
Solar/Wind Harmer
3.01
963741AG1-226 GEN
Solar/Wind Harmer
1.519
24386205FR-12G C
Solar/Wind Harmer
2.503
276686W4-005 GEN3
Solar/Wind Harmer
1.725
276764AC1-053 GEN2
Solar/Wind Harmer
2.251
276911AD2-131_GEN
Solar/Wind Harmer
0.143
964401AG1-302 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.579
276872AE1-163_GEN1
Solar/Wind Harmer
3.647
274851PROVIDENC;RU
Solar/Wind Harmer
1.542
274872LEEDK;1U
Solar/Wind Harmer
4.922
959081AF2-199 GEN
Solar/Wind Harmer
0.262
25183208HLCRTG
Solar/Wind Helper
1.201
253325AC1-069 GEN
Solar/Wind Helper
0.154
946031AF1-268 GEN
Solar/Wind Harmer
0.807
965651AG1-433 GEN
Solar/Wind Harmer
13.484
970289AG2-191 GEN
Solar/Wind Harmer
0.135
276916AD2-100_GEN
Solar/Wind Harmer
0.601
957381AF2-032 GEN
Solar/Wind Harmer
0.057
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
0.269
274847GR RIDGE ;BU
Solar/Wind Harmer
3.075
274849CRESCENT ;1U
Solar/Wind Harmer
1.135
972207SS24-0001
Solar/Wind Harmer
0.8
959091AF2-200 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Helper
0.154
943111AE2-339 GEN
Solar/Wind Helper
0.102
NYPJM->LTFIMP_NY
CLTF
0.75
TVALTFEXP_TVA->PJM
CLTF
1.407
LAGNLTFEXP_LAGN->PJM
CLTF
3.93
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.851
WECLTFEXP_WEC->PJM
CLTF
1.709
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.203
SIGELTFEXP_SIGE->PJM
CLTF
0.245
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.069
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.195
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.031
AH1-155LTFEXP_AH1-155->PJM
LTF
0.181
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.447
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.381
MECLTFEXP_MEC->PJM
CLTF
6.886
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.03 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2352.88
MW Contribution:
0.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
2.758
965051AG1-369 GEN
Solar/Wind Harmer
0.293
970349AG2-230 GEN
Solar/Wind Harmer
0.721
971347AH1-153 GEN
Solar/Wind Harmer
0.24
961761AG1-017 GEN
Solar/Wind Harmer
0.449
960591AF2-350 GEN
Solar/Wind Harmer
0.428
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
16.272
247536S-71 GEN
Solar/Wind Harmer
3.798
926823AC1-168 GEN
Solar/Wind Harmer
4.874
274857EASY ROAD;U1
Solar/Wind Harmer
3.688
24725505WLD G2 C
Solar/Wind Harmer
3.052
276656WTG2_EQ
Solar/Wind Harmer
0.874
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.587
270462AD2-086
Solar/Wind Helper
1.788
270317AD1-130_GEN
Solar/Wind Helper
1.166
270287AF1-227 GEN3
Solar/Wind Helper
0.35
943021AE2-325 GEN
Solar/Wind Harmer
2.95
964611AG1-324 GEN
Solar/Wind Harmer
0.402
276843GEN-1.7
Solar/Wind Harmer
0.568
958011AF2-095 GEN
Solar/Wind Harmer
0.617
276691AA1-018 GEN1
Solar/Wind Harmer
0.447
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.615
24697905MDL-4G C
Solar/Wind Harmer
2.096
970819AG2-516 GEN
Solar/Wind Harmer
0.478
276646AC1-214 GEN2
Solar/Wind Harmer
1.204
274878BISHOP HL;2U
Solar/Wind Harmer
3.016
274854TWINGROVE;U2
Solar/Wind Harmer
5.82
965091AG1-374 GEN
Solar/Wind Harmer
1.13
965931AG1-462 GEN
Solar/Wind Harmer
0.961
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.995
270499AE1-146 GEN
Solar/Wind Helper
0.544
24727005RPMNG1
50/50
68.356
247620Y3-023
50/50
0.46
959331AF2-224 GEN
Solar/Wind Harmer
1.139
965041AG1-368 GEN
Solar/Wind Harmer
0.69
270031AE2-169
Solar/Wind Harmer
0.377
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.661
274861TOP CROP ;1U
Solar/Wind Harmer
4.856
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.349
971067AG2-660 GEN
Solar/Wind Harmer
1.608
24699105WLD G1 C
Solar/Wind Harmer
3.052
276655WTG1_EQ
Solar/Wind Harmer
6.603
963841AG1-237 GEN
Solar/Wind Harmer
11.714
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.285
247522W1-056 GEN
Solar/Wind Helper
1.919
270286AF1-227 GEN2
Solar/Wind Helper
0.35
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.296
970031AG2-029 GEN
Solar/Wind Harmer
1.74
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.381
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.278
970833AG2-524 GEN
Solar/Wind Harmer
0.463
962781AG1-127 GEN
Solar/Wind Harmer
0.389
276868AE1-113 GEN
Solar/Wind Harmer
9.54
24697605MDL-3G C
Solar/Wind Harmer
3.143
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.804
24385905FR-11G C
Solar/Wind Harmer
5.939
946321AF1-296 GEN
Solar/Wind Harmer
11.289
274853TWINGROVE;U1
Solar/Wind Harmer
5.82
959611AF2-252 GEN
Solar/Wind Harmer
1.507
960611AF2-352 GEN
Solar/Wind Harmer
1.507
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.365
970193AG2-126 GEN
Solar/Wind Harmer
0.491
958581AF2-149 GEN
Solar/Wind Helper
0.222
24727105RPMNG2
50/50
68.356
270246TR4_N_V150
Solar/Wind Harmer
1.152
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.556
970291AG2-192 GEN
Solar/Wind Harmer
0.303
274871GR RIDGE ;2U
Solar/Wind Harmer
5.335
943121AE2-341 GEN
Solar/Wind Harmer
0.627
957471AF2-041 GEN
Solar/Wind Harmer
1.206
274848CAMPGROVE;RU
Solar/Wind Harmer
4.509
970521AG2-332 GEN
50/50
10.74
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.192
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.804
274877BISHOP HL;1U
Solar/Wind Harmer
3.016
276848AB2-070 GEN3
Solar/Wind Harmer
1.825
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.166
270471AD2-092_GEN
Solar/Wind Helper
0.454
276820AF1-078_GEN
Solar/Wind Helper
0.159
965431AG1-411 GEN
50/50
45.078
24727205RPMNG3
50/50
68.356
24639705ELKHART HY
50/50
0.148
963791AG1-232 GEN
Solar/Wind Harmer
0.988
247521TR3_G114
Solar/Wind Harmer
4.555
24695305TIMB G C
Solar/Wind Harmer
3.924
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.418
276694AA1-018 GEN2
Solar/Wind Harmer
4.411
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.096
971343AH1-151 GEN
Solar/Wind Harmer
0.804
970169AG2-114 GEN
Solar/Wind Harmer
0.397
959341AF2-225 GEN
Solar/Wind Harmer
0.575
971087AG2-675 GEN
Solar/Wind Harmer
2.412
270445AC2-157 GEN2
Solar/Wind Harmer
0
960851AF2-376 GEN
50/50
2.033
965021AG1-366 GEN
Solar/Wind Harmer
4.557
942221AE2-234 GEN
Solar/Wind Harmer
0.204
958861AF2-177 GEN
Solar/Wind Harmer
15.92
945371AF1-202 GEN
Solar/Wind Harmer
7.521
270505AE1-170 C O1
Solar/Wind Harmer
0.718
270032AE2-172
Solar/Wind Harmer
3.34
970825AG2-519 GEN
Solar/Wind Harmer
1.758
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.231
971997AH1-543 GEN
Solar/Wind Harmer
0.639
276889AE2-281 GEN
Solar/Wind Harmer
1.572
24691005MDL-2G C
Solar/Wind Harmer
3.143
971549AH1-272 GEN
Solar/Wind Harmer
0.722
276158O29GEN2
Solar/Wind Harmer
3.427
276708O09 GEN2
Solar/Wind Harmer
3.218
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.241
270543AE2-219 C
Solar/Wind Harmer
0.365
971993AH1-541 GEN
Solar/Wind Harmer
0.329
276621W2-048 GEN
Solar/Wind Harmer
5.054
942481AE2-261 GEN
Solar/Wind Harmer
1.011
270485AE1-090_GEN
Solar/Wind Helper
0.155
24729405KEY G3
50/50
6.841
24729505KEY G4
50/50
6.727
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.436
970941AG2-585 GEN
Solar/Wind Harmer
0.236
276897AD1-100 C
Solar/Wind Harmer
56.232
971605AH1-302 GEN
Solar/Wind Harmer
6.283
970825AG2-519 GEN
Solar/Wind Harmer
0.274
276805AD2-038 GEN
Solar/Wind Harmer
4.799
970569AG2-363 GEN
Solar/Wind Harmer
1.195
276157O29GEN1
Solar/Wind Harmer
3.427
276645AC1-214 GEN1
Solar/Wind Harmer
1.204
939741AE1-205 GEN
Solar/Wind Harmer
0.767
942111AE2-223 GEN
Solar/Wind Harmer
8.972
970241AG2-163 GEN
Solar/Wind Harmer
0.911
276174W4-005 GEN2
Solar/Wind Harmer
2.126
276668AB2-070 GEN1
Solar/Wind Harmer
1.825
276838X2-022 GEN2
Solar/Wind Harmer
0.188
246938BC-WTG3
Solar/Wind Helper
17.366
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.152
944531AF1-118 GEN
Solar/Wind Harmer
2.052
961051AF2-396 GEN
Solar/Wind Harmer
0.957
961051AF2-396 GEN
Solar/Wind Harmer
7.653
270599AE1-208 GEN
Solar/Wind Harmer
0.377
972231SS25-0005
Solar/Wind Harmer
0.703
971411AH1-196 GEN
Solar/Wind Harmer
0.607
274855GSG-6 ;RU
Solar/Wind Harmer
3.454
276876AE1-163_GEN2
Solar/Wind Harmer
5.502
24386405FR-21G C
Solar/Wind Harmer
3.021
276782AC1-033 GEN
Solar/Wind Harmer
3.04
276763AC1-053 GEN1
Solar/Wind Harmer
2.764
971029AG2-637 GEN
Solar/Wind Harmer
0.481
270224U2-072_GEN2
Solar/Wind Helper
1.995
942871AE2-306 GEN
Solar/Wind Helper
0.214
945641AF1-229 GEN
Solar/Wind Helper
0.454
270541AE2-072 C
Solar/Wind Helper
0.459
965011AG1-365 GEN
Solar/Wind Harmer
1.139
945111AF1-176 GEN
Solar/Wind Harmer
0.876
945111AF1-176 GEN
Solar/Wind Harmer
4.774
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.668
970073AG2-061 GEN
Solar/Wind Harmer
1.641
274850MENDOTA H;RU
Solar/Wind Harmer
2.401
276863AD2-134 GEN
Solar/Wind Harmer
1.67
276861AD2-134 GEN
Solar/Wind Harmer
1.67
970571AG2-364 GEN
Solar/Wind Harmer
0.796
274856ECOGROVE ;U1
Solar/Wind Harmer
3.104
971681AH1-341 GEN
Solar/Wind Harmer
0.593
938861AE1-114 GEN
Solar/Wind Harmer
9.255
274858EASY ROAD;U2
Solar/Wind Harmer
3.688
270240V3-007_GEN2
Solar/Wind Harmer
4.477
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.353
960861AF2-377 GEN
50/50
2.345
24729305KEY G2
50/50
6.841
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.937
957891AF2-083 GEN
Solar/Wind Harmer
0.723
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.683
274888KELLY CRK;1U
Solar/Wind Harmer
5.846
276893AG1-478 C
Solar/Wind Harmer
0.338
270005AE1-210 C O1
Solar/Wind Harmer
6.493
276602WESTBROOK C
Solar/Wind Harmer
1.703
274863CRW1-WTG
Solar/Wind Harmer
4.717
274864CRW2-WTG
Solar/Wind Harmer
4.717
276603SUBLETTE C
Solar/Wind Harmer
0.798
24387305FR-4G C
Solar/Wind Harmer
4.532
24386605FR-22G C
Solar/Wind Harmer
3.021
24387005FR-3G C
Solar/Wind Harmer
2.991
274880W4-005 GEN4
Solar/Wind Harmer
2.126
246936BC-WTG1
Solar/Wind Helper
17.073
246937BC-WTG2
Solar/Wind Helper
17.073
960841AF2-375 GEN
Solar/Wind Helper
0.563
270191TR4_S_V150
Solar/Wind Harmer
3.471
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.032
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.18
270180AB1-006 GEN1
Solar/Wind Harmer
5.658
24791305MDL-5G
Solar/Wind Harmer
2.096
276741O09 GEN1
Solar/Wind Harmer
3.218
276726Z2-087_GEN
Solar/Wind Harmer
5.982
944221AF1-090 GEN
Solar/Wind Harmer
10.146
966831AG1-554 GEN
Solar/Wind Helper
0.281
24729205KEY G1
50/50
6.727
270201AC2-176 GEN
Solar/Wind Harmer
4.618
970373AG2-245 GEN
Solar/Wind Harmer
0.924
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.493
274872LEEDK;1U
Solar/Wind Harmer
7.643
276872AE1-163_GEN1
Solar/Wind Harmer
5.502
959081AF2-199 GEN
Solar/Wind Harmer
0.402
274851PROVIDENC;RU
Solar/Wind Harmer
2.244
24386205FR-12G C
Solar/Wind Harmer
3.154
24379505HDWTR1G C
Solar/Wind Harmer
5.718
970885AG2-551 GEN
Solar/Wind Harmer
1.46
963741AG1-226 GEN
Solar/Wind Harmer
1.64
276686W4-005 GEN3
Solar/Wind Harmer
2.126
276764AC1-053 GEN2
Solar/Wind Harmer
2.764
276911AD2-131_GEN
Solar/Wind Harmer
0.168
965421AG1-410 GEN
Solar/Wind Harmer
6.762
965651AG1-433 GEN
Solar/Wind Harmer
8.19
972181SS23-001
Solar/Wind Harmer
0.439
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.299
970289AG2-191 GEN
Solar/Wind Harmer
0.08
274847GR RIDGE ;BU
Solar/Wind Harmer
4.836
946031AF1-268 GEN
Solar/Wind Harmer
0.346
959091AF2-200 GEN
Solar/Wind Harmer
0.804
274849CRESCENT ;1U
Solar/Wind Harmer
1.651
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.704
270227U2-072_GEN3
Solar/Wind Helper
1.995
270228U2-072_GEN4
Solar/Wind Helper
1.995
270231U2-072_GEN5
Solar/Wind Helper
1.995
270349AD2-093_GEN
Solar/Wind Helper
0.454
970707AG2-453 GEN
Solar/Wind Harmer
1.192
970833AG2-524 GEN
Solar/Wind Harmer
3.705
958481AF2-142 GEN
Solar/Wind Harmer
0.623
274862TOP CROP ;2U
Solar/Wind Harmer
4.856
274879MINONK ;1U
Solar/Wind Harmer
6.36
971675AH1-338 GEN
Solar/Wind Harmer
0.728
970781AG2-491 GEN
Solar/Wind Harmer
0.403
276903AD2-071 C
Solar/Wind Harmer
0.399
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.811
945391AF1-204 GEN
Solar/Wind Harmer
13.018
270391AF1-285 GEN3
Solar/Wind Helper
0.285
241847AF2-150_GEN
Solar/Wind Helper
0.265
276785W4-005 GEN1
Solar/Wind Harmer
2.126
276849AB2-070 GEN2
Solar/Wind Harmer
1.825
957201AF2-014 GEN
Solar/Wind Helper
3.942
270284AF1-227 GEN1
Solar/Wind Helper
0.948
270428AC2-015 C
Solar/Wind Helper
0.374
253383AE2-342_GEN
Solar/Wind Helper
0.103
990792J1392
External Queue
0.3027859032154083
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.204
NYPJM->LTFIMP_NY
CLTF
1.303
MECLTFEXP_MEC->PJM
CLTF
9.641
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.255
LGEELTFEXP_LGEE->PJM
CLTF
1.795
LAGNLTFEXP_LAGN->PJM
CLTF
5.817
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.873
TVALTFEXP_TVA->PJM
CLTF
2.36
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.443
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.032
WECLTFEXP_WEC->PJM
CLTF
2.627
SIGELTFEXP_SIGE->PJM
CLTF
0.199

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.21 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2290.26
MW Contribution:
0.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
965431AG1-411 GEN
50/50
45.403
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.018
270143AC1-141 CT2_
50/50
2.018
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
24643105BUCHANAN
50/50
0.01
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
965421AG1-410 GEN
Solar/Wind Harmer
6.81
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.787
24642205MAYFLWER
50/50
0.618
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
990792J1392
External Queue
0.30737584829330444
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.89 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2283.06
MW Contribution:
0.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
943021AE2-325 GEN
Solar/Wind Harmer
2.988
964611AG1-324 GEN
Solar/Wind Harmer
0.408
276843GEN-1.7
Solar/Wind Harmer
0.573
970031AG2-029 GEN
Solar/Wind Harmer
1.759
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.565
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.323
970833AG2-524 GEN
Solar/Wind Harmer
0.467
962781AG1-127 GEN
Solar/Wind Harmer
0.392
276868AE1-113 GEN
Solar/Wind Harmer
9.612
24697605MDL-3G C
Solar/Wind Harmer
3.167
270181AB1-006 GEN2
Solar/Wind Harmer
0.633
971171AH1-044 GEN
Solar/Wind Harmer
0.81
24385905FR-11G C
Solar/Wind Harmer
5.98
946321AF1-296 GEN
Solar/Wind Harmer
11.357
274853TWINGROVE;U1
Solar/Wind Harmer
5.857
959611AF2-252 GEN
Solar/Wind Harmer
1.517
960611AF2-352 GEN
Solar/Wind Harmer
1.517
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.371
970193AG2-126 GEN
Solar/Wind Harmer
0.493
958581AF2-149 GEN
Solar/Wind Helper
0.203
970521AG2-332 GEN
50/50
10.867
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
13.303
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.81
274877BISHOP HL;1U
Solar/Wind Harmer
3.036
276848AB2-070 GEN3
Solar/Wind Harmer
1.835
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.114
276820AF1-078_GEN
Solar/Wind Helper
0.149
270471AD2-092_GEN
Solar/Wind Helper
0.392
960851AF2-376 GEN
50/50
2.087
965021AG1-366 GEN
Solar/Wind Harmer
4.6
942221AE2-234 GEN
Solar/Wind Harmer
0.207
958861AF2-177 GEN
Solar/Wind Harmer
16.102
945371AF1-202 GEN
Solar/Wind Harmer
7.608
270505AE1-170 C O1
Solar/Wind Harmer
0.727
270032AE2-172
Solar/Wind Harmer
3.376
970825AG2-519 GEN
Solar/Wind Harmer
1.78
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.24
971997AH1-543 GEN
Solar/Wind Harmer
0.644
276889AE2-281 GEN
Solar/Wind Harmer
1.583
24691005MDL-2G C
Solar/Wind Harmer
3.167
971549AH1-272 GEN
Solar/Wind Harmer
0.735
276158O29GEN2
Solar/Wind Harmer
3.45
276708O09 GEN2
Solar/Wind Harmer
3.24
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.258
270543AE2-219 C
Solar/Wind Harmer
0.371
971993AH1-541 GEN
Solar/Wind Harmer
0.331
276621W2-048 GEN
Solar/Wind Harmer
5.079
942481AE2-261 GEN
Solar/Wind Harmer
1.015
247607V1-011 GEN
Solar/Wind Harmer
2.016
270485AE1-090_GEN
Solar/Wind Helper
0.148
960861AF2-377 GEN
50/50
2.398
24729305KEY G2
50/50
6.916
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.947
957891AF2-083 GEN
Solar/Wind Harmer
0.732
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.693
274888KELLY CRK;1U
Solar/Wind Harmer
5.896
276893AG1-478 C
Solar/Wind Harmer
0.341
270005AE1-210 C O1
Solar/Wind Harmer
6.573
276602WESTBROOK C
Solar/Wind Harmer
1.716
274863CRW1-WTG
Solar/Wind Harmer
4.752
274864CRW2-WTG
Solar/Wind Harmer
4.752
276603SUBLETTE C
Solar/Wind Harmer
0.803
24387305FR-4G C
Solar/Wind Harmer
4.563
24386605FR-22G C
Solar/Wind Harmer
3.042
24387005FR-3G C
Solar/Wind Harmer
3.012
274880W4-005 GEN4
Solar/Wind Harmer
2.138
246936BC-WTG1
Solar/Wind Helper
16.963
246937BC-WTG2
Solar/Wind Helper
16.963
960841AF2-375 GEN
Solar/Wind Helper
0.538
24729405KEY G3
50/50
6.916
24729505KEY G4
50/50
6.801
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.441
970941AG2-585 GEN
Solar/Wind Harmer
0.238
276897AD1-100 C
Solar/Wind Harmer
56.698
971605AH1-302 GEN
Solar/Wind Harmer
6.335
970825AG2-519 GEN
Solar/Wind Harmer
0.278
276805AD2-038 GEN
Solar/Wind Harmer
4.835
970569AG2-363 GEN
Solar/Wind Harmer
1.203
965421AG1-410 GEN
Solar/Wind Harmer
6.81
965651AG1-433 GEN
Solar/Wind Harmer
8.283
972181SS23-001
Solar/Wind Harmer
0.443
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.31
970289AG2-191 GEN
Solar/Wind Harmer
0.081
274847GR RIDGE ;BU
Solar/Wind Harmer
4.875
946031AF1-268 GEN
Solar/Wind Harmer
0.35
959091AF2-200 GEN
Solar/Wind Harmer
0.81
274849CRESCENT ;1U
Solar/Wind Harmer
1.662
957381AF2-032 GEN
Solar/Wind Harmer
0.068
276916AD2-100_GEN
Solar/Wind Harmer
0.707
961051AF2-396 GEN
Solar/Wind Harmer
0.969
961051AF2-396 GEN
Solar/Wind Harmer
7.751
270599AE1-208 GEN
Solar/Wind Harmer
0.382
972231SS25-0005
Solar/Wind Harmer
0.709
971411AH1-196 GEN
Solar/Wind Harmer
0.612
274855GSG-6 ;RU
Solar/Wind Harmer
3.479
276876AE1-163_GEN2
Solar/Wind Harmer
5.542
24386405FR-21G C
Solar/Wind Harmer
3.042
276782AC1-033 GEN
Solar/Wind Harmer
3.06
276763AC1-053 GEN1
Solar/Wind Harmer
2.779
971029AG2-637 GEN
Solar/Wind Harmer
0.491
270224U2-072_GEN2
Solar/Wind Helper
1.89
942871AE2-306 GEN
Solar/Wind Helper
0.203
945641AF1-229 GEN
Solar/Wind Helper
0.43
270541AE2-072 C
Solar/Wind Helper
0.432
24641605TWIN BRNCH
50/50
0.015
270247TR4_N_V136
Solar/Wind Harmer
1.179
944531AF1-118 GEN
Solar/Wind Harmer
2.074
970707AG2-453 GEN
Solar/Wind Harmer
1.202
970833AG2-524 GEN
Solar/Wind Harmer
3.735
958481AF2-142 GEN
Solar/Wind Harmer
0.628
274862TOP CROP ;2U
Solar/Wind Harmer
4.894
274879MINONK ;1U
Solar/Wind Harmer
6.408
971675AH1-338 GEN
Solar/Wind Harmer
0.733
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.403
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.815
945391AF1-204 GEN
Solar/Wind Harmer
13.084
270391AF1-285 GEN3
Solar/Wind Helper
0.27
241847AF2-150_GEN
Solar/Wind Helper
0.245
270227U2-072_GEN3
Solar/Wind Helper
1.89
270228U2-072_GEN4
Solar/Wind Helper
1.89
270231U2-072_GEN5
Solar/Wind Helper
1.89
270349AD2-093_GEN
Solar/Wind Helper
0.392
965431AG1-411 GEN
50/50
45.403
24727205RPMNG3
50/50
68.866
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
1
247521TR3_G114
Solar/Wind Harmer
4.658
24695305TIMB G C
Solar/Wind Harmer
4.029
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.055
943591AF1-030 GEN
Solar/Wind Harmer
0.421
276694AA1-018 GEN2
Solar/Wind Harmer
4.446
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.111
971343AH1-151 GEN
Solar/Wind Harmer
0.81
970169AG2-114 GEN
Solar/Wind Harmer
0.4
959341AF2-225 GEN
Solar/Wind Harmer
0.579
971087AG2-675 GEN
Solar/Wind Harmer
2.426
270445AC2-157 GEN2
Solar/Wind Harmer
0
970583AG2-370 GEN
50/50
2.807
965051AG1-369 GEN
Solar/Wind Harmer
0.299
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.243
961761AG1-017 GEN
Solar/Wind Harmer
0.455
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
3.859
939401AE1-172 GEN
Solar/Wind Harmer
16.397
926823AC1-168 GEN
Solar/Wind Harmer
4.909
274857EASY ROAD;U1
Solar/Wind Harmer
3.713
24725505WLD G2 C
Solar/Wind Harmer
3.086
276656WTG2_EQ
Solar/Wind Harmer
0.88
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.595
958091AF2-103 GEN
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Helper
1.708
270317AD1-130_GEN
Solar/Wind Helper
1.114
270287AF1-227 GEN3
Solar/Wind Helper
0.318
24727105RPMNG2
50/50
68.866
270246TR4_N_V150
Solar/Wind Harmer
1.179
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.561
970291AG2-192 GEN
Solar/Wind Harmer
0.306
274871GR RIDGE ;2U
Solar/Wind Harmer
5.378
943121AE2-341 GEN
Solar/Wind Harmer
0.632
957471AF2-041 GEN
Solar/Wind Harmer
1.215
274848CAMPGROVE;RU
Solar/Wind Harmer
4.539
276785W4-005 GEN1
Solar/Wind Harmer
2.138
276849AB2-070 GEN2
Solar/Wind Harmer
1.835
957201AF2-014 GEN
Solar/Wind Helper
3.917
270284AF1-227 GEN1
Solar/Wind Helper
0.862
270428AC2-015 C
Solar/Wind Helper
0.352
24729205KEY G1
50/50
6.801
270201AC2-176 GEN
Solar/Wind Harmer
4.681
970373AG2-245 GEN
Solar/Wind Harmer
0.933
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.573
274872LEEDK;1U
Solar/Wind Harmer
7.701
276872AE1-163_GEN1
Solar/Wind Harmer
5.542
959081AF2-199 GEN
Solar/Wind Harmer
0.405
274851PROVIDENC;RU
Solar/Wind Harmer
2.259
24386205FR-12G C
Solar/Wind Harmer
3.176
24379505HDWTR1G C
Solar/Wind Harmer
5.796
970885AG2-551 GEN
Solar/Wind Harmer
1.486
963741AG1-226 GEN
Solar/Wind Harmer
1.651
276686W4-005 GEN3
Solar/Wind Harmer
2.138
276764AC1-053 GEN2
Solar/Wind Harmer
2.779
276911AD2-131_GEN
Solar/Wind Harmer
0.168
270191TR4_S_V150
Solar/Wind Harmer
3.55
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.084
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.204
270180AB1-006 GEN1
Solar/Wind Harmer
5.7
24791305MDL-5G
Solar/Wind Harmer
2.111
276741O09 GEN1
Solar/Wind Harmer
3.24
276726Z2-087_GEN
Solar/Wind Harmer
6.022
944221AF1-090 GEN
Solar/Wind Harmer
10.182
966831AG1-554 GEN
Solar/Wind Helper
0.27
958011AF2-095 GEN
Solar/Wind Harmer
0.622
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.62
24697905MDL-4G C
Solar/Wind Harmer
2.111
970819AG2-516 GEN
Solar/Wind Harmer
0.482
276646AC1-214 GEN2
Solar/Wind Harmer
1.212
274878BISHOP HL;2U
Solar/Wind Harmer
3.036
274854TWINGROVE;U2
Solar/Wind Harmer
5.857
965091AG1-374 GEN
Solar/Wind Harmer
1.138
965931AG1-462 GEN
Solar/Wind Harmer
0.967
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
1.89
270499AE1-146 GEN
Solar/Wind Helper
0.52
24727005RPMNG1
50/50
68.866
247620Y3-023
50/50
0.466
959331AF2-224 GEN
Solar/Wind Harmer
1.15
965041AG1-368 GEN
Solar/Wind Harmer
0.702
270031AE2-169
Solar/Wind Harmer
0.382
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.719
274861TOP CROP ;1U
Solar/Wind Harmer
4.894
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.396
971067AG2-660 GEN
Solar/Wind Harmer
1.62
24699105WLD G1 C
Solar/Wind Harmer
3.086
276655WTG1_EQ
Solar/Wind Harmer
6.647
963841AG1-237 GEN
Solar/Wind Harmer
11.792
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.27
247522W1-056 GEN
Solar/Wind Helper
1.839
270286AF1-227 GEN2
Solar/Wind Helper
0.318
961961AG1-039 GEN
Solar/Wind Helper
0.156
241960AC2-195 GEN
Solar/Wind Helper
0.268
276157O29GEN1
Solar/Wind Harmer
3.45
276645AC1-214 GEN1
Solar/Wind Harmer
1.212
939741AE1-205 GEN
Solar/Wind Harmer
0.772
942111AE2-223 GEN
Solar/Wind Harmer
9.032
970241AG2-163 GEN
Solar/Wind Harmer
0.917
276174W4-005 GEN2
Solar/Wind Harmer
2.138
276668AB2-070 GEN1
Solar/Wind Harmer
1.835
276838X2-022 GEN2
Solar/Wind Harmer
0.189
270007AE1-245 C
Solar/Wind Harmer
2.82
246938BC-WTG3
Solar/Wind Helper
17.255
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.887
945111AF1-176 GEN
Solar/Wind Harmer
4.834
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.675
970073AG2-061 GEN
Solar/Wind Harmer
1.653
274850MENDOTA H;RU
Solar/Wind Harmer
2.419
276863AD2-134 GEN
Solar/Wind Harmer
1.682
276861AD2-134 GEN
Solar/Wind Harmer
1.682
970571AG2-364 GEN
Solar/Wind Harmer
0.802
274856ECOGROVE ;U1
Solar/Wind Harmer
3.126
971681AH1-341 GEN
Solar/Wind Harmer
0.598
938861AE1-114 GEN
Solar/Wind Harmer
9.319
274858EASY ROAD;U2
Solar/Wind Harmer
3.713
270240V3-007_GEN2
Solar/Wind Harmer
4.538
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.331
990792J1392
External Queue
0.30737584829330444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.064
SIGELTFEXP_SIGE->PJM
CLTF
0.199
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.211
NYPJM->LTFIMP_NY
CLTF
1.286
TVALTFEXP_TVA->PJM
CLTF
2.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.728
WECLTFEXP_WEC->PJM
CLTF
2.646
LAGNLTFEXP_LAGN->PJM
CLTF
5.66
AH1-155LTFEXP_AH1-155->PJM
LTF
0.25
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.768
LGEELTFEXP_LGEE->PJM
CLTF
1.793
MECLTFEXP_MEC->PJM
CLTF
9.669
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.36 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2271.47
MW Contribution:
0.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970031AG2-029 GEN
Solar/Wind Harmer
1.71
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
16.032
945581AF1-223 GEN
Solar/Wind Harmer
0
274887GEN-1.85
Solar/Wind Harmer
5.144
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
276868AE1-113 GEN
Solar/Wind Harmer
9.286
24697605MDL-3G C
Solar/Wind Harmer
3.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.782
24385905FR-11G C
Solar/Wind Harmer
5.772
946321AF1-296 GEN
Solar/Wind Harmer
10.97
274853TWINGROVE;U1
Solar/Wind Harmer
5.654
959611AF2-252 GEN
Solar/Wind Harmer
1.464
960611AF2-352 GEN
Solar/Wind Harmer
1.464
270437AC2-090 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
0.354
970193AG2-126 GEN
Solar/Wind Harmer
0.475
970521AG2-332 GEN
50/50
10.514
270024AE2-089 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
12.855
965021AG1-366 GEN
Solar/Wind Harmer
4.503
942221AE2-234 GEN
Solar/Wind Harmer
0.2
958861AF2-177 GEN
Solar/Wind Harmer
15.573
945371AF1-202 GEN
Solar/Wind Harmer
7.349
270505AE1-170 C O1
Solar/Wind Harmer
0.702
960861AF2-377 GEN
50/50
2.286
24729305KEY G2
50/50
6.704
24653605MOTTVILLE
50/50
0.003
270071AF1-092 GEN
Solar/Wind Harmer
0.92
957891AF2-083 GEN
Solar/Wind Harmer
0.707
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.667
274888KELLY CRK;1U
Solar/Wind Harmer
5.697
276893AG1-478 C
Solar/Wind Harmer
0.33
270005AE1-210 C O1
Solar/Wind Harmer
6.326
276602WESTBROOK C
Solar/Wind Harmer
1.658
274863CRW1-WTG
Solar/Wind Harmer
4.59
274864CRW2-WTG
Solar/Wind Harmer
4.59
276603SUBLETTE C
Solar/Wind Harmer
0.776
24387305FR-4G C
Solar/Wind Harmer
4.404
24386605FR-22G C
Solar/Wind Harmer
2.936
24387005FR-3G C
Solar/Wind Harmer
2.906
274880W4-005 GEN4
Solar/Wind Harmer
2.063
246936BC-WTG1
Solar/Wind Helper
17.184
246937BC-WTG2
Solar/Wind Helper
17.184
960841AF2-375 GEN
Solar/Wind Helper
0.576
961051AF2-396 GEN
Solar/Wind Harmer
0.935
961051AF2-396 GEN
Solar/Wind Harmer
7.477
270599AE1-208 GEN
Solar/Wind Harmer
0.368
972231SS25-0005
Solar/Wind Harmer
0.685
971411AH1-196 GEN
Solar/Wind Harmer
0.591
274855GSG-6 ;RU
Solar/Wind Harmer
3.361
276876AE1-163_GEN2
Solar/Wind Harmer
5.354
24386405FR-21G C
Solar/Wind Harmer
2.936
276782AC1-033 GEN
Solar/Wind Harmer
2.956
276763AC1-053 GEN1
Solar/Wind Harmer
2.681
971029AG2-637 GEN
Solar/Wind Harmer
0.465
270224U2-072_GEN2
Solar/Wind Helper
2.097
942871AE2-306 GEN
Solar/Wind Helper
0.225
945641AF1-229 GEN
Solar/Wind Helper
0.46
270541AE2-072 C
Solar/Wind Helper
0.478
944531AF1-118 GEN
Solar/Wind Harmer
2.012
270247TR4_N_V136
Solar/Wind Harmer
1.123
970707AG2-453 GEN
Solar/Wind Harmer
1.161
970833AG2-524 GEN
Solar/Wind Harmer
3.609
958481AF2-142 GEN
Solar/Wind Harmer
0.607
274862TOP CROP ;2U
Solar/Wind Harmer
4.729
274879MINONK ;1U
Solar/Wind Harmer
6.19
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
276903AD2-071 C
Solar/Wind Harmer
0.388
966841AG1-555 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.786
945391AF1-204 GEN
Solar/Wind Harmer
12.593
270391AF1-285 GEN3
Solar/Wind Helper
0.3
241847AF2-150_GEN
Solar/Wind Helper
0.265
965421AG1-410 GEN
Solar/Wind Harmer
6.711
965651AG1-433 GEN
Solar/Wind Harmer
8.016
972181SS23-001
Solar/Wind Harmer
0.428
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.266
970289AG2-191 GEN
Solar/Wind Harmer
0.078
274847GR RIDGE ;BU
Solar/Wind Harmer
4.711
946031AF1-268 GEN
Solar/Wind Harmer
0.337
959091AF2-200 GEN
Solar/Wind Harmer
0.782
274849CRESCENT ;1U
Solar/Wind Harmer
1.605
957381AF2-032 GEN
Solar/Wind Harmer
0.066
276916AD2-100_GEN
Solar/Wind Harmer
0.681
270227U2-072_GEN3
Solar/Wind Helper
2.097
270228U2-072_GEN4
Solar/Wind Helper
2.097
270231U2-072_GEN5
Solar/Wind Helper
2.097
270349AD2-093_GEN
Solar/Wind Helper
0.517
965431AG1-411 GEN
50/50
44.74
24727205RPMNG3
50/50
67.807
24639705ELKHART HY
50/50
0.145
970583AG2-370 GEN
50/50
2.702
965051AG1-369 GEN
Solar/Wind Harmer
0.285
970349AG2-230 GEN
Solar/Wind Harmer
0.704
971347AH1-153 GEN
Solar/Wind Harmer
0.235
961761AG1-017 GEN
Solar/Wind Harmer
0.438
960591AF2-350 GEN
Solar/Wind Harmer
0.417
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
939401AE1-172 GEN
Solar/Wind Harmer
15.839
247536S-71 GEN
Solar/Wind Harmer
3.697
926823AC1-168 GEN
Solar/Wind Harmer
4.742
274857EASY ROAD;U1
Solar/Wind Harmer
3.587
24725505WLD G2 C
Solar/Wind Harmer
2.968
276656WTG2_EQ
Solar/Wind Harmer
0.85
926881AC1-175 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
1.539
270462AD2-086
Solar/Wind Helper
1.865
270317AD1-130_GEN
Solar/Wind Helper
1.216
270287AF1-227 GEN3
Solar/Wind Helper
0.382
963791AG1-232 GEN
Solar/Wind Harmer
0.971
247521TR3_G114
Solar/Wind Harmer
4.44
24695305TIMB G C
Solar/Wind Harmer
3.811
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.053
943591AF1-030 GEN
Solar/Wind Harmer
0.407
276694AA1-018 GEN2
Solar/Wind Harmer
4.296
276901AD2-066 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
2.038
971343AH1-151 GEN
Solar/Wind Harmer
0.782
970169AG2-114 GEN
Solar/Wind Harmer
0.386
959341AF2-225 GEN
Solar/Wind Harmer
0.559
971087AG2-675 GEN
Solar/Wind Harmer
2.343
270445AC2-157 GEN2
Solar/Wind Harmer
0
24727105RPMNG2
50/50
67.807
270246TR4_N_V150
Solar/Wind Harmer
1.123
270449AD2-020 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.541
970291AG2-192 GEN
Solar/Wind Harmer
0.295
274871GR RIDGE ;2U
Solar/Wind Harmer
5.196
943121AE2-341 GEN
Solar/Wind Harmer
0.611
957471AF2-041 GEN
Solar/Wind Harmer
1.174
274848CAMPGROVE;RU
Solar/Wind Harmer
4.383
276785W4-005 GEN1
Solar/Wind Harmer
2.063
276849AB2-070 GEN2
Solar/Wind Harmer
1.771
957201AF2-014 GEN
Solar/Wind Helper
3.968
270284AF1-227 GEN1
Solar/Wind Helper
1.035
270428AC2-015 C
Solar/Wind Helper
0.376
253383AE2-342_GEN
Solar/Wind Helper
0.105
24729205KEY G1
50/50
6.593
270201AC2-176 GEN
Solar/Wind Harmer
4.506
970373AG2-245 GEN
Solar/Wind Harmer
0.901
964401AG1-302 GEN
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
6.326
274872LEEDK;1U
Solar/Wind Harmer
7.44
276872AE1-163_GEN1
Solar/Wind Harmer
5.354
959081AF2-199 GEN
Solar/Wind Harmer
0.391
274851PROVIDENC;RU
Solar/Wind Harmer
2.181
270191TR4_S_V150
Solar/Wind Harmer
3.383
944541AF1-119 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.91
941551AE2-152 GEN
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
3.095
270180AB1-006 GEN1
Solar/Wind Harmer
5.504
24791305MDL-5G
Solar/Wind Harmer
2.038
276741O09 GEN1
Solar/Wind Harmer
3.129
276726Z2-087_GEN
Solar/Wind Harmer
5.813
944221AF1-090 GEN
Solar/Wind Harmer
9.816
966831AG1-554 GEN
Solar/Wind Helper
0.286
943021AE2-325 GEN
Solar/Wind Harmer
2.881
964611AG1-324 GEN
Solar/Wind Harmer
0.393
276843GEN-1.7
Solar/Wind Harmer
0.553
958011AF2-095 GEN
Solar/Wind Harmer
0.601
276691AA1-018 GEN1
Solar/Wind Harmer
0.435
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
24697905MDL-4G C
Solar/Wind Harmer
2.038
970819AG2-516 GEN
Solar/Wind Harmer
0.465
276646AC1-214 GEN2
Solar/Wind Harmer
1.17
274878BISHOP HL;2U
Solar/Wind Harmer
2.932
965931AG1-462 GEN
Solar/Wind Harmer
0.934
274854TWINGROVE;U2
Solar/Wind Harmer
5.654
965091AG1-374 GEN
Solar/Wind Harmer
1.098
270356AE2-297 GEN
Solar/Wind Harmer
0
270223U2-072_GEN1
Solar/Wind Helper
2.097
270499AE1-146 GEN
Solar/Wind Helper
0.556
958581AF2-149 GEN
Solar/Wind Helper
0.216
24727005RPMNG1
50/50
67.807
247620Y3-023
50/50
0.45
959331AF2-224 GEN
Solar/Wind Harmer
1.126
965041AG1-368 GEN
Solar/Wind Harmer
0.675
270031AE2-169
Solar/Wind Harmer
0.368
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
6.489
274861TOP CROP ;1U
Solar/Wind Harmer
4.729
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
6.176
971067AG2-660 GEN
Solar/Wind Harmer
1.565
24699105WLD G1 C
Solar/Wind Harmer
2.968
276655WTG1_EQ
Solar/Wind Harmer
6.417
963841AG1-237 GEN
Solar/Wind Harmer
11.375
270383AD1-128 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Helper
0.3
270286AF1-227 GEN2
Solar/Wind Helper
0.382
247522W1-056 GEN
Solar/Wind Helper
1.958
961961AG1-039 GEN
Solar/Wind Helper
0.169
241960AC2-195 GEN
Solar/Wind Helper
0.299
24729405KEY G3
50/50
6.704
24729505KEY G4
50/50
6.593
270043AE2-236 GEN
Solar/Wind Harmer
0.363
971771AH1-392 GEN
Solar/Wind Harmer
0.426
970941AG2-585 GEN
Solar/Wind Harmer
0.23
276897AD1-100 C
Solar/Wind Harmer
54.783
971605AH1-302 GEN
Solar/Wind Harmer
6.118
970825AG2-519 GEN
Solar/Wind Harmer
0.267
276805AD2-038 GEN
Solar/Wind Harmer
4.671
970569AG2-363 GEN
Solar/Wind Harmer
1.162
276157O29GEN1
Solar/Wind Harmer
3.332
276645AC1-214 GEN1
Solar/Wind Harmer
1.17
939741AE1-205 GEN
Solar/Wind Harmer
0.745
942111AE2-223 GEN
Solar/Wind Harmer
8.72
970241AG2-163 GEN
Solar/Wind Harmer
0.884
276174W4-005 GEN2
Solar/Wind Harmer
2.063
276668AB2-070 GEN1
Solar/Wind Harmer
1.771
276838X2-022 GEN2
Solar/Wind Harmer
0.183
246938BC-WTG3
Solar/Wind Helper
17.48
270032AE2-172
Solar/Wind Harmer
3.253
970825AG2-519 GEN
Solar/Wind Harmer
1.712
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.198
971997AH1-543 GEN
Solar/Wind Harmer
0.622
276889AE2-281 GEN
Solar/Wind Harmer
1.53
24691005MDL-2G C
Solar/Wind Harmer
3.058
971549AH1-272 GEN
Solar/Wind Harmer
0.702
276158O29GEN2
Solar/Wind Harmer
3.332
276708O09 GEN2
Solar/Wind Harmer
3.129
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
1.205
270543AE2-219 C
Solar/Wind Harmer
0.354
971993AH1-541 GEN
Solar/Wind Harmer
0.319
276621W2-048 GEN
Solar/Wind Harmer
4.9
942481AE2-261 GEN
Solar/Wind Harmer
0.979
270485AE1-090_GEN
Solar/Wind Helper
0.162
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.856
945111AF1-176 GEN
Solar/Wind Harmer
4.667
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.651
970073AG2-061 GEN
Solar/Wind Harmer
1.597
274850MENDOTA H;RU
Solar/Wind Harmer
2.337
276863AD2-134 GEN
Solar/Wind Harmer
1.625
276861AD2-134 GEN
Solar/Wind Harmer
1.625
970571AG2-364 GEN
Solar/Wind Harmer
0.775
274856ECOGROVE ;U1
Solar/Wind Harmer
3.02
971681AH1-341 GEN
Solar/Wind Harmer
0.577
938861AE1-114 GEN
Solar/Wind Harmer
9.003
274858EASY ROAD;U2
Solar/Wind Harmer
3.587
270240V3-007_GEN2
Solar/Wind Harmer
4.35
270209AC1-174_GEN
Solar/Wind Harmer
0
253378AE2-206_GEN
Solar/Wind Helper
0.369
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
0.782
274877BISHOP HL;1U
Solar/Wind Harmer
2.932
276848AB2-070 GEN3
Solar/Wind Harmer
1.771
270444AC2-157 GEN1
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Helper
1.216
270471AD2-092_GEN
Solar/Wind Helper
0.517
276820AF1-078_GEN
Solar/Wind Helper
0.166
24386205FR-12G C
Solar/Wind Harmer
3.065
24379505HDWTR1G C
Solar/Wind Harmer
5.555
970885AG2-551 GEN
Solar/Wind Harmer
1.417
963741AG1-226 GEN
Solar/Wind Harmer
1.592
276686W4-005 GEN3
Solar/Wind Harmer
2.063
276764AC1-053 GEN2
Solar/Wind Harmer
2.681
276911AD2-131_GEN
Solar/Wind Harmer
0.162
990792J1392
External Queue
0.3014104962348938
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.67
NYPJM->LTFIMP_NY
CLTF
1.235
TVALTFEXP_TVA->PJM
CLTF
2.193
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.304
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.955
LGEELTFEXP_LGEE->PJM
CLTF
1.68
MECLTFEXP_MEC->PJM
CLTF
9.337
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.512
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
SIGELTFEXP_SIGE->PJM
CLTF
0.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.406
WECLTFEXP_WEC->PJM
CLTF
2.556
LAGNLTFEXP_LAGN->PJM
CLTF
5.484
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290598 TO BUS 290599 CKT 1    /*05GREENTW_RJ 765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P2-2_#9456_06DEARB1 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
CONTINGENCY 'AEP_P4_#9456_06DEARB1 345_DC_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
243211 to 242933 ckt 1
243206 to 290606 ckt Z1
243208 to 242865 ckt 2
242865 to 248000 ckt 1
290608 to 242928 ckt Z1
242933 to 965420 ckt 1
243233 to 249567 ckt 1
965420 to 246929 ckt 1

Light Load Analysis

The New Service Request AH1-341 was evaluated as a 150.0 MW injection

AH1-341 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CE
AE2-341 TP-W PLANO ; R 138.0 kV Ckt 1 line
COMED_P1-2_138-L11106_B-R_SRT-A-1
SingleAC100.05 %503.0STE503.23
5.8
GD2CE
HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line
COMED_P1-2_138-L9407_R-R_SRT-A
SingleAC102.92 %542.0STE557.8
6.63
GD2CE
HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line
COMED_P1-2_138-L11305_B-R_SRT-A
SingleAC102.01 %542.0STE552.9
6.63
GD2CE
MCGIRR RD;-ESS H447 ;RT 138.0 kV Ckt 1 line
COMED_P1-2_345-L15502_B-R_SRT-A-2
SingleAC105.43 %503.0STE530.29
7.63
GD2CE
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Base Case
SingleAC100.15 %1553.0A1555.33
12.21
GD2CE
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
COMED_P4-6_111-345-B______SRT-A
BreakerAC117.06 %472.0STE552.54
7.51
GD2CE
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
COMED_P1-2_345-L15502_B-R_SRT-A-2
SingleAC115.86 %472.0STE546.86
7.63
GD2CE
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
COMED_P4_111-45-TR81____SRT-A
BreakerAC115.07 %472.0STE543.11
7.59
GD2CE
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
COMED_P4_111-45-L11124__SRT-A
BreakerAC115.07 %472.0STE543.11
7.59
GD2CE
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
COMED_P2-2_111_EJ-345B__1_SRT-A
BusAC115.07 %472.0STE543.11
7.59
GD2CE
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
COMED_P1-2_345-L15502_B-R_SRT-A-1
SingleAC111.72 %472.0STE527.32
7.63
GD2CE
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Base Case
SingleAC108.09 %408.0A441.0
6.96
GD2CE
W DEKALB ;3T-WATERMAN ; R 138.0 kV Ckt 1 line
COMED_P1-2_138-L9407_R-R_SRT-A
SingleAC100.62 %542.0STE545.34
6.63
GD2CE
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
COMED_P1-2_138-L11106_B-R_SRT-A-1
SingleAC118.77 %347.0STE412.15
5.8
GD2CE
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-2
TowerAC117.62 %423.0ALDR497.51
6.44
GD2CE
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-1
TowerAC104.03 %423.0ALDR440.05
6.45
GD2CE
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Base Case
SingleAC101.75 %285.0A289.98
4.27
GD2CE
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
COMED_P1-2_345-L15502_B-R_SRT-A-2
SingleAC100.51 %347.0STE348.78
4.68

Details for AE2-341 TP-W PLANO ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11106_B-R_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
AE2-341 TP-W PLANO ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_138-L11106_B-R_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.05 %
Rating:503.0 MVA
Rating Type:STE
MVA to Mitigate:503.23
MW Contribution:
5.8
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
AE2-341 TP-W PLANO ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_138-L11106_B-R_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:99.85 %
Rating:503.0 MVA
Rating Type:STE
MVA to Mitigate:502.24
MW Contribution:
5.79
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
9.875
276603SUBLETTE C
Solar/Wind Harmer
0.842
971681AH1-341 GEN
Solar/Wind Harmer
5.799
938861AE1-114 GEN
Solar/Wind Harmer
6.488
943591AF1-030 GEN
Solar/Wind Harmer
45.057
943121AE2-341 GEN
Solar/Wind Harmer
67.586
962691AG1-118 GEN
Solar/Wind Harmer
66.412
276799AD1-013 GEN
Solar/Wind Harmer
6.782
276602WESTBROOK C
Solar/Wind Harmer
7.005
276863AD2-134 GEN
Solar/Wind Harmer
6.868
946671AF1-331 GEN
Solar/Wind Harmer
3.391
276861AD2-134 GEN
Solar/Wind Harmer
6.868
971675AH1-338 GEN
Solar/Wind Harmer
30.157
274855GSG-6 ;RU
Solar/Wind Harmer
14.204
962781AG1-127 GEN
Solar/Wind Harmer
20.036
274872LEEDK;1U
Solar/Wind Harmer
39.522
274872LEEDK;1U
Solar/Wind Harmer
7.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.384
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.043
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.782
WECLTFEXP_WEC->PJM
CLTF
0.33
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.102
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.307
NYPJM->LTFIMP_NY
CLTF
0.128
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
MECLTFEXP_MEC->PJM
CLTF
1.894
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
76.538
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.035
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.076
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.377

Details for HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L9407_R-R_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_138-L9407_R-R_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.92 %
Rating:542.0 MVA
Rating Type:STE
MVA to Mitigate:557.8
MW Contribution:
6.63
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_138-L9407_R-R_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.79 %
Rating:542.0 MVA
Rating Type:STE
MVA to Mitigate:557.14
MW Contribution:
6.62
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
18.154
276603SUBLETTE C
Solar/Wind Harmer
1.222
971681AH1-341 GEN
Solar/Wind Harmer
6.628
938861AE1-114 GEN
Solar/Wind Harmer
7.113
276799AD1-013 GEN
Solar/Wind Harmer
12.487
276602WESTBROOK C
Solar/Wind Harmer
12.877
276863AD2-134 GEN
Solar/Wind Harmer
12.627
960751AF2-366 GEN
Solar/Wind Helper
4.461
946671AF1-331 GEN
Solar/Wind Harmer
6.244
276861AD2-134 GEN
Solar/Wind Harmer
12.627
971675AH1-338 GEN
Solar/Wind Harmer
55.479
274855GSG-6 ;RU
Solar/Wind Harmer
26.112
274872LEEDK;1U
Solar/Wind Harmer
73.74
274872LEEDK;1U
Solar/Wind Harmer
14.291
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.191
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.074
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.248
NYPJM->LTFIMP_NY
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.041
MECLTFEXP_MEC->PJM
CLTF
1.428
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
64.098
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.666
WECLTFEXP_WEC->PJM
CLTF
0.041
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.093
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.282
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.014
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11305_B-R_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_138-L11305_B-R_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.01 %
Rating:542.0 MVA
Rating Type:STE
MVA to Mitigate:552.9
MW Contribution:
6.63
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_138-L11305_B-R_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.89 %
Rating:542.0 MVA
Rating Type:STE
MVA to Mitigate:552.23
MW Contribution:
6.62
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
18.154
276603SUBLETTE C
Solar/Wind Harmer
1.222
971681AH1-341 GEN
Solar/Wind Harmer
6.628
938861AE1-114 GEN
Solar/Wind Harmer
7.113
960751AF2-366 GEN
Solar/Wind Helper
4.461
276799AD1-013 GEN
Solar/Wind Harmer
12.487
276602WESTBROOK C
Solar/Wind Harmer
12.877
276863AD2-134 GEN
Solar/Wind Harmer
12.627
946671AF1-331 GEN
Solar/Wind Harmer
6.244
276861AD2-134 GEN
Solar/Wind Harmer
12.627
971675AH1-338 GEN
Solar/Wind Harmer
55.479
274855GSG-6 ;RU
Solar/Wind Harmer
26.112
274872LEEDK;1U
Solar/Wind Harmer
73.74
274872LEEDK;1U
Solar/Wind Harmer
14.291
NYPJM->LTFIMP_NY
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.041
MECLTFEXP_MEC->PJM
CLTF
1.428
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
64.098
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.014
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.191
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.074
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.248
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.666
WECLTFEXP_WEC->PJM
CLTF
0.041
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.093
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.282

Details for MCGIRR RD;-ESS H447 ;RT 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
MCGIRR RD;-ESS H447 ;RT 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:503.0 MVA
Rating Type:STE
MVA to Mitigate:530.29
MW Contribution:
7.63
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
MCGIRR RD;-ESS H447 ;RT 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.23 %
Rating:503.0 MVA
Rating Type:STE
MVA to Mitigate:529.32
MW Contribution:
7.62
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
19.033
276603SUBLETTE C
Solar/Wind Harmer
1.388
971681AH1-341 GEN
Solar/Wind Harmer
7.633
938861AE1-114 GEN
Solar/Wind Harmer
8.37
957471AF2-041 GEN
Solar/Wind Harmer
5.896
276741O09 GEN1
Solar/Wind Harmer
2.49
960751AF2-366 GEN
Solar/Wind Helper
4.583
959091AF2-200 GEN
Solar/Wind Harmer
3.931
971341AH1-150 GEN
Solar/Wind Harmer
3.931
971343AH1-151 GEN
Solar/Wind Harmer
3.931
276602WESTBROOK C
Solar/Wind Harmer
13.5
276863AD2-134 GEN
Solar/Wind Harmer
13.238
276157O29GEN1
Solar/Wind Harmer
2.651
276861AD2-134 GEN
Solar/Wind Harmer
13.238
276158O29GEN2
Solar/Wind Harmer
2.651
276708O09 GEN2
Solar/Wind Harmer
2.49
971171AH1-044 GEN
Solar/Wind Harmer
3.931
274855GSG-6 ;RU
Solar/Wind Harmer
27.376
971067AG2-660 GEN
Solar/Wind Harmer
1.787
274872LEEDK;1U
50/50
Charging
5.086
274872LEEDK;1U
Solar/Wind Helper
16.479
959081AF2-199 GEN
Solar/Wind Harmer
1.965
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.182
WECLTFEXP_WEC->PJM
CLTF
0.11
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.064
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
92.542
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.349
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.033
MECLTFEXP_MEC->PJM
CLTF
2.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.528
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.132
LAGNLTFEXP_LAGN->PJM
CLTF
0.583
NYPJM->LTFIMP_NY
CLTF
0.095
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187

Details for NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.15 %
Rating:1553.0 MVA
Rating Type:A
MVA to Mitigate:1555.33
MW Contribution:
12.21
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:99.81 %
Rating:1553.0 MVA
Rating Type:A
MVA to Mitigate:1550.0
MW Contribution:
12.16
Bus #Bus NameTypeMW Contribution
274858EASY ROAD;U2
Solar/Wind Harmer
9.262
276603SUBLETTE C
Solar/Wind Harmer
1.962
971681AH1-341 GEN
Solar/Wind Harmer
12.213
938861AE1-114 GEN
Solar/Wind Harmer
16.009
276741O09 GEN1
Solar/Wind Harmer
8.101
971087AG2-675 GEN
Solar/Wind Harmer
13.659
274877BISHOP HL;1U
Solar/Wind Harmer
3.499
276157O29GEN1
Solar/Wind Harmer
8.626
274856ECOGROVE ;U1
Solar/Wind Harmer
4.503
972031AH1-564 GEN
Solar/Wind Harmer
1.766
276158O29GEN2
Solar/Wind Harmer
8.626
274857EASY ROAD;U1
Solar/Wind Harmer
9.262
276708O09 GEN2
Solar/Wind Harmer
8.101
946321AF1-296 GEN
Solar/Wind Harmer
23.955
276782AC1-033 GEN
Solar/Wind Harmer
3.529
971067AG2-660 GEN
50/50
Charging
23.266
965931AG1-462 GEN
Solar/Wind Harmer
23.946
970819AG2-516 GEN
Solar/Wind Harmer
5.803
274878BISHOP HL;2U
Solar/Wind Harmer
3.499
991092J1477
External Queue
5.358128070831299
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.585
NYPJM->LTFIMP_NY
CLTF
0.399
TVALTFEXP_TVA->PJM
CLTF
0.794
LAGNLTFEXP_LAGN->PJM
CLTF
3.234
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.565
WECLTFEXP_WEC->PJM
CLTF
0.714
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.246
SIGELTFEXP_SIGE->PJM
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.032
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.024
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.708
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.239
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
MECLTFEXP_MEC->PJM
CLTF
11.903
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
470.612

Details for STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line l/o COMED_P4-6_111-345-B______SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_111-345-B______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.06 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:552.54
MW Contribution:
7.51
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_111-345-B______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.87 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:551.63
MW Contribution:
7.5
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
18.825
276603SUBLETTE C
Solar/Wind Harmer
1.37
971681AH1-341 GEN
Solar/Wind Harmer
7.514
938861AE1-114 GEN
Solar/Wind Harmer
8.241
276799AD1-013 GEN
Solar/Wind Harmer
12.942
276602WESTBROOK C
Solar/Wind Harmer
13.353
276863AD2-134 GEN
Solar/Wind Harmer
13.093
276157O29GEN1
Solar/Wind Harmer
2.618
957471AF2-041 GEN
Solar/Wind Harmer
4.491
276741O09 GEN1
Solar/Wind Harmer
2.459
960751AF2-366 GEN
Solar/Wind Helper
4.798
959091AF2-200 GEN
Solar/Wind Harmer
2.994
971341AH1-150 GEN
Solar/Wind Harmer
2.994
971343AH1-151 GEN
Solar/Wind Harmer
2.994
946671AF1-331 GEN
Solar/Wind Harmer
6.471
276861AD2-134 GEN
Solar/Wind Harmer
13.093
276158O29GEN2
Solar/Wind Harmer
2.618
971675AH1-338 GEN
Solar/Wind Harmer
57.515
276708O09 GEN2
Solar/Wind Harmer
2.459
971171AH1-044 GEN
Solar/Wind Harmer
2.994
274855GSG-6 ;RU
Solar/Wind Harmer
27.076
971067AG2-660 GEN
Solar/Wind Harmer
1.361
274872LEEDK;1U
50/50
Charging
5.248
274872LEEDK;1U
Solar/Wind Helper
17.003
959081AF2-199 GEN
Solar/Wind Harmer
1.497
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.178
WECLTFEXP_WEC->PJM
CLTF
0.115
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.062
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
91.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.351
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.032
MECLTFEXP_MEC->PJM
CLTF
2.238
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.466
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.132
LAGNLTFEXP_LAGN->PJM
CLTF
0.581
NYPJM->LTFIMP_NY
CLTF
0.094
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.183

Details for STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.86 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:546.86
MW Contribution:
7.63
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.64 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:545.83
MW Contribution:
7.62
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
19.033
276603SUBLETTE C
Solar/Wind Harmer
1.388
971681AH1-341 GEN
Solar/Wind Harmer
7.633
938861AE1-114 GEN
Solar/Wind Harmer
8.37
276799AD1-013 GEN
Solar/Wind Harmer
13.085
276602WESTBROOK C
Solar/Wind Harmer
13.5
276863AD2-134 GEN
Solar/Wind Harmer
13.238
276157O29GEN1
Solar/Wind Harmer
2.651
957471AF2-041 GEN
Solar/Wind Harmer
4.555
276741O09 GEN1
Solar/Wind Harmer
2.49
960751AF2-366 GEN
Solar/Wind Helper
4.583
959091AF2-200 GEN
Solar/Wind Harmer
3.037
971341AH1-150 GEN
Solar/Wind Harmer
3.037
971343AH1-151 GEN
Solar/Wind Harmer
3.037
946671AF1-331 GEN
Solar/Wind Harmer
6.543
276861AD2-134 GEN
Solar/Wind Harmer
13.238
276158O29GEN2
Solar/Wind Harmer
2.651
971675AH1-338 GEN
Solar/Wind Harmer
58.152
276708O09 GEN2
Solar/Wind Harmer
2.49
971171AH1-044 GEN
Solar/Wind Harmer
3.037
274855GSG-6 ;RU
Solar/Wind Harmer
27.376
971067AG2-660 GEN
Solar/Wind Harmer
1.38
274872LEEDK;1U
50/50
Charging
5.086
274872LEEDK;1U
Solar/Wind Helper
16.479
959081AF2-199 GEN
Solar/Wind Harmer
1.518
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.182
WECLTFEXP_WEC->PJM
CLTF
0.11
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.064
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
92.542
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.349
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.033
MECLTFEXP_MEC->PJM
CLTF
2.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.528
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.132
LAGNLTFEXP_LAGN->PJM
CLTF
0.583
NYPJM->LTFIMP_NY
CLTF
0.095
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187

Details for STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line l/o COMED_P4_111-45-TR81____SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-TR81____SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.07 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:543.11
MW Contribution:
7.59
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-TR81____SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.85 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:542.1
MW Contribution:
7.58
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
18.981
276603SUBLETTE C
Solar/Wind Harmer
1.381
971681AH1-341 GEN
Solar/Wind Harmer
7.588
938861AE1-114 GEN
Solar/Wind Harmer
8.316
276799AD1-013 GEN
Solar/Wind Harmer
13.05
276602WESTBROOK C
Solar/Wind Harmer
13.464
276863AD2-134 GEN
Solar/Wind Harmer
13.202
276157O29GEN1
Solar/Wind Harmer
2.635
957471AF2-041 GEN
Solar/Wind Harmer
4.519
276741O09 GEN1
Solar/Wind Harmer
2.475
960751AF2-366 GEN
Solar/Wind Helper
4.634
959091AF2-200 GEN
Solar/Wind Harmer
3.013
971341AH1-150 GEN
Solar/Wind Harmer
3.013
971343AH1-151 GEN
Solar/Wind Harmer
3.013
946671AF1-331 GEN
Solar/Wind Harmer
6.525
276861AD2-134 GEN
Solar/Wind Harmer
13.202
276158O29GEN2
Solar/Wind Harmer
2.635
971675AH1-338 GEN
Solar/Wind Harmer
57.994
276708O09 GEN2
Solar/Wind Harmer
2.475
971171AH1-044 GEN
Solar/Wind Harmer
3.013
274855GSG-6 ;RU
Solar/Wind Harmer
27.302
971067AG2-660 GEN
Solar/Wind Harmer
1.37
274872LEEDK;1U
50/50
Charging
5.125
274872LEEDK;1U
Solar/Wind Helper
16.605
959081AF2-199 GEN
Solar/Wind Harmer
1.506
NYPJM->LTFIMP_NY
CLTF
0.094
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.482
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.132
LAGNLTFEXP_LAGN->PJM
CLTF
0.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.351
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.032
MECLTFEXP_MEC->PJM
CLTF
2.244
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.172
WECLTFEXP_WEC->PJM
CLTF
0.113
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.062
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
91.664

Details for STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line l/o COMED_P4_111-45-L11124__SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-L11124__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.07 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:543.11
MW Contribution:
7.59
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-L11124__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.85 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:542.1
MW Contribution:
7.58
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
18.981
276603SUBLETTE C
Solar/Wind Harmer
1.381
971681AH1-341 GEN
Solar/Wind Harmer
7.588
938861AE1-114 GEN
Solar/Wind Harmer
8.316
957471AF2-041 GEN
Solar/Wind Harmer
4.519
276741O09 GEN1
Solar/Wind Harmer
2.475
960751AF2-366 GEN
Solar/Wind Helper
4.634
959091AF2-200 GEN
Solar/Wind Harmer
3.013
971341AH1-150 GEN
Solar/Wind Harmer
3.013
971343AH1-151 GEN
Solar/Wind Harmer
3.013
276799AD1-013 GEN
Solar/Wind Harmer
13.05
276602WESTBROOK C
Solar/Wind Harmer
13.464
276863AD2-134 GEN
Solar/Wind Harmer
13.202
276157O29GEN1
Solar/Wind Harmer
2.635
946671AF1-331 GEN
Solar/Wind Harmer
6.525
276861AD2-134 GEN
Solar/Wind Harmer
13.202
276158O29GEN2
Solar/Wind Harmer
2.635
971675AH1-338 GEN
Solar/Wind Harmer
57.994
276708O09 GEN2
Solar/Wind Harmer
2.475
971171AH1-044 GEN
Solar/Wind Harmer
3.013
274855GSG-6 ;RU
Solar/Wind Harmer
27.302
971067AG2-660 GEN
Solar/Wind Harmer
1.37
274872LEEDK;1U
50/50
Charging
5.125
274872LEEDK;1U
Solar/Wind Helper
16.605
959081AF2-199 GEN
Solar/Wind Harmer
1.506
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.172
WECLTFEXP_WEC->PJM
CLTF
0.113
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.062
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
91.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.351
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.032
MECLTFEXP_MEC->PJM
CLTF
2.244
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.482
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.132
LAGNLTFEXP_LAGN->PJM
CLTF
0.581
NYPJM->LTFIMP_NY
CLTF
0.094
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.182

Details for STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345B__1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345B__1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.07 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:543.11
MW Contribution:
7.59
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345B__1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.85 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:542.11
MW Contribution:
7.58
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
18.981
276603SUBLETTE C
Solar/Wind Harmer
1.381
971681AH1-341 GEN
Solar/Wind Harmer
7.588
938861AE1-114 GEN
Solar/Wind Harmer
8.316
276799AD1-013 GEN
Solar/Wind Harmer
13.05
276602WESTBROOK C
Solar/Wind Harmer
13.464
276863AD2-134 GEN
Solar/Wind Harmer
13.202
276157O29GEN1
Solar/Wind Harmer
2.635
957471AF2-041 GEN
Solar/Wind Harmer
4.519
276741O09 GEN1
Solar/Wind Harmer
2.475
960751AF2-366 GEN
Solar/Wind Helper
4.634
959091AF2-200 GEN
Solar/Wind Harmer
3.013
971341AH1-150 GEN
Solar/Wind Harmer
3.013
971343AH1-151 GEN
Solar/Wind Harmer
3.013
946671AF1-331 GEN
Solar/Wind Harmer
6.525
276861AD2-134 GEN
Solar/Wind Harmer
13.202
276158O29GEN2
Solar/Wind Harmer
2.635
971675AH1-338 GEN
Solar/Wind Harmer
57.994
276708O09 GEN2
Solar/Wind Harmer
2.475
971171AH1-044 GEN
Solar/Wind Harmer
3.013
274855GSG-6 ;RU
Solar/Wind Harmer
27.302
971067AG2-660 GEN
Solar/Wind Harmer
1.37
274872LEEDK;1U
50/50
Charging
5.125
274872LEEDK;1U
Solar/Wind Helper
16.605
959081AF2-199 GEN
Solar/Wind Harmer
1.506
NYPJM->LTFIMP_NY
CLTF
0.094
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.482
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.132
LAGNLTFEXP_LAGN->PJM
CLTF
0.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.351
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.032
MECLTFEXP_MEC->PJM
CLTF
2.244
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.172
WECLTFEXP_WEC->PJM
CLTF
0.113
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.062
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
91.664

Details for STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.72 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:527.32
MW Contribution:
7.63
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.51 %
Rating:472.0 MVA
Rating Type:STE
MVA to Mitigate:526.33
MW Contribution:
7.62
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
19.033
276603SUBLETTE C
Solar/Wind Harmer
1.388
971681AH1-341 GEN
Solar/Wind Harmer
7.633
938861AE1-114 GEN
Solar/Wind Harmer
8.37
276741O09 GEN1
Solar/Wind Harmer
2.49
960751AF2-366 GEN
Solar/Wind Helper
4.583
276799AD1-013 GEN
Solar/Wind Harmer
13.085
276602WESTBROOK C
Solar/Wind Harmer
13.5
276863AD2-134 GEN
Solar/Wind Harmer
13.238
276157O29GEN1
Solar/Wind Harmer
2.651
946671AF1-331 GEN
Solar/Wind Harmer
6.543
276861AD2-134 GEN
Solar/Wind Harmer
13.238
276158O29GEN2
Solar/Wind Harmer
2.651
971675AH1-338 GEN
Solar/Wind Harmer
58.152
276708O09 GEN2
Solar/Wind Harmer
2.49
274855GSG-6 ;RU
Solar/Wind Harmer
27.376
274872LEEDK;1U
50/50
Charging
5.086
274872LEEDK;1U
Solar/Wind Helper
16.479
NYPJM->LTFIMP_NY
CLTF
0.095
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.015
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.528
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.132
LAGNLTFEXP_LAGN->PJM
CLTF
0.583
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.349
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.033
MECLTFEXP_MEC->PJM
CLTF
2.261
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.182
WECLTFEXP_WEC->PJM
CLTF
0.11
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.064
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
92.542

Details for STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.09 %
Rating:408.0 MVA
Rating Type:A
MVA to Mitigate:441.0
MW Contribution:
6.96
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
STEWARD ; B-HAUMESSER; B 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.9 %
Rating:408.0 MVA
Rating Type:A
MVA to Mitigate:440.25
MW Contribution:
6.95
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
18.902
276603SUBLETTE C
Solar/Wind Harmer
1.28
971681AH1-341 GEN
Solar/Wind Harmer
6.961
938861AE1-114 GEN
Solar/Wind Harmer
7.489
960751AF2-366 GEN
Solar/Wind Helper
4.617
276799AD1-013 GEN
Solar/Wind Harmer
13.001
276602WESTBROOK C
Solar/Wind Harmer
13.408
276863AD2-134 GEN
Solar/Wind Harmer
13.147
946671AF1-331 GEN
Solar/Wind Harmer
6.501
276861AD2-134 GEN
Solar/Wind Harmer
13.147
971675AH1-338 GEN
Solar/Wind Harmer
57.764
274855GSG-6 ;RU
Solar/Wind Harmer
27.188
274872LEEDK;1U
50/50
Charging
5.125
274872LEEDK;1U
Solar/Wind Helper
16.605
NYPJM->LTFIMP_NY
CLTF
0.073
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.909
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.088
LAGNLTFEXP_LAGN->PJM
CLTF
0.405
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.226
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
MECLTFEXP_MEC->PJM
CLTF
1.606
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.215
WECLTFEXP_WEC->PJM
CLTF
0.071
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.05
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
66.64

Details for W DEKALB ;3T-WATERMAN ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L9407_R-R_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
W DEKALB ;3T-WATERMAN ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_138-L9407_R-R_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.62 %
Rating:542.0 MVA
Rating Type:STE
MVA to Mitigate:545.34
MW Contribution:
6.63
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
W DEKALB ;3T-WATERMAN ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_138-L9407_R-R_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.49 %
Rating:542.0 MVA
Rating Type:STE
MVA to Mitigate:544.67
MW Contribution:
6.62
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
18.154
276603SUBLETTE C
Solar/Wind Harmer
1.222
971681AH1-341 GEN
Solar/Wind Harmer
6.628
938861AE1-114 GEN
Solar/Wind Harmer
7.113
276799AD1-013 GEN
Solar/Wind Harmer
12.487
276602WESTBROOK C
Solar/Wind Harmer
12.877
276863AD2-134 GEN
Solar/Wind Harmer
12.627
960751AF2-366 GEN
Solar/Wind Helper
4.461
946671AF1-331 GEN
Solar/Wind Harmer
6.244
276861AD2-134 GEN
Solar/Wind Harmer
12.627
971675AH1-338 GEN
Solar/Wind Harmer
55.479
274855GSG-6 ;RU
Solar/Wind Harmer
26.112
274872LEEDK;1U
Solar/Wind Harmer
73.74
274872LEEDK;1U
Solar/Wind Harmer
14.291
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.014
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.666
WECLTFEXP_WEC->PJM
CLTF
0.041
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.093
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.282
NYPJM->LTFIMP_NY
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.041
MECLTFEXP_MEC->PJM
CLTF
1.428
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
64.098
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.191
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.074
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.248

Details for WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_138-L11106_B-R_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_138-L11106_B-R_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.77 %
Rating:347.0 MVA
Rating Type:STE
MVA to Mitigate:412.15
MW Contribution:
5.8
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_138-L11106_B-R_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.51 %
Rating:347.0 MVA
Rating Type:STE
MVA to Mitigate:411.22
MW Contribution:
5.79
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
9.875
276603SUBLETTE C
Solar/Wind Harmer
0.842
971681AH1-341 GEN
Solar/Wind Harmer
5.799
938861AE1-114 GEN
Solar/Wind Harmer
6.488
962691AG1-118 GEN
Solar/Wind Harmer
66.412
276799AD1-013 GEN
Solar/Wind Harmer
6.782
276602WESTBROOK C
Solar/Wind Harmer
7.005
276863AD2-134 GEN
Solar/Wind Harmer
6.868
946671AF1-331 GEN
Solar/Wind Harmer
3.391
276861AD2-134 GEN
Solar/Wind Harmer
6.868
971675AH1-338 GEN
Solar/Wind Harmer
30.157
274855GSG-6 ;RU
Solar/Wind Harmer
14.204
962781AG1-127 GEN
Solar/Wind Harmer
20.036
274872LEEDK;1U
Solar/Wind Harmer
39.522
274872LEEDK;1U
Solar/Wind Harmer
7.659
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.782
WECLTFEXP_WEC->PJM
CLTF
0.33
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.102
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.307
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.035
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.076
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.377
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.384
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.043
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.128
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
MECLTFEXP_MEC->PJM
CLTF
1.894
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
76.538

Details for WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.62 %
Rating:423.0 MVA
Rating Type:ALDR
MVA to Mitigate:497.51
MW Contribution:
6.44
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.33 %
Rating:423.0 MVA
Rating Type:ALDR
MVA to Mitigate:496.32
MW Contribution:
6.43
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
10.039
276603SUBLETTE C
Solar/Wind Harmer
0.946
971681AH1-341 GEN
Solar/Wind Harmer
6.443
938861AE1-114 GEN
Solar/Wind Harmer
7.327
957471AF2-041 GEN
Solar/Wind Harmer
2.428
959091AF2-200 GEN
Solar/Wind Harmer
1.619
971341AH1-150 GEN
Solar/Wind Harmer
1.619
971343AH1-151 GEN
Solar/Wind Harmer
1.619
962691AG1-118 GEN
Solar/Wind Harmer
66.905
276799AD1-013 GEN
Solar/Wind Harmer
6.89
276602WESTBROOK C
Solar/Wind Harmer
7.121
276863AD2-134 GEN
Solar/Wind Harmer
6.982
274856ECOGROVE ;U1
Solar/Wind Harmer
2.282
946671AF1-331 GEN
Solar/Wind Harmer
3.445
276861AD2-134 GEN
Solar/Wind Harmer
6.982
971675AH1-338 GEN
Solar/Wind Harmer
30.647
971171AH1-044 GEN
Solar/Wind Harmer
1.619
274855GSG-6 ;RU
Solar/Wind Harmer
14.439
962781AG1-127 GEN
Solar/Wind Harmer
20.194
971067AG2-660 GEN
Solar/Wind Harmer
0.736
274872LEEDK;1U
Solar/Wind Harmer
39.881
274872LEEDK;1U
Solar/Wind Harmer
7.729
959081AF2-199 GEN
Solar/Wind Harmer
0.809
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.679
WECLTFEXP_WEC->PJM
CLTF
0.367
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.115
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.345
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.149
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.08
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.542
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.83
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.084
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.149
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.043
MECLTFEXP_MEC->PJM
CLTF
2.504
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
100.713

Details for WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line l/o COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.03 %
Rating:423.0 MVA
Rating Type:ALDR
MVA to Mitigate:440.05
MW Contribution:
6.45
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.75 %
Rating:423.0 MVA
Rating Type:ALDR
MVA to Mitigate:438.86
MW Contribution:
6.43
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
10.227
276603SUBLETTE C
Solar/Wind Harmer
0.953
971681AH1-341 GEN
Solar/Wind Harmer
6.445
938861AE1-114 GEN
Solar/Wind Harmer
7.321
276799AD1-013 GEN
Solar/Wind Harmer
7.019
276602WESTBROOK C
Solar/Wind Harmer
7.254
276863AD2-134 GEN
Solar/Wind Harmer
7.113
274856ECOGROVE ;U1
Solar/Wind Harmer
2.256
957471AF2-041 GEN
Solar/Wind Harmer
3.998
959091AF2-200 GEN
Solar/Wind Harmer
2.666
971341AH1-150 GEN
Solar/Wind Harmer
2.666
971343AH1-151 GEN
Solar/Wind Harmer
2.666
946671AF1-331 GEN
Solar/Wind Harmer
3.51
276861AD2-134 GEN
Solar/Wind Harmer
7.113
971675AH1-338 GEN
Solar/Wind Harmer
31.222
971171AH1-044 GEN
Solar/Wind Harmer
2.666
274855GSG-6 ;RU
Solar/Wind Harmer
14.71
962781AG1-127 GEN
Solar/Wind Harmer
19.333
971067AG2-660 GEN
Solar/Wind Harmer
1.212
274872LEEDK;1U
Solar/Wind Harmer
40.663
274872LEEDK;1U
Solar/Wind Harmer
7.881
959081AF2-199 GEN
Solar/Wind Harmer
1.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.657
WECLTFEXP_WEC->PJM
CLTF
0.359
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.114
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.343
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.147
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.08
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.537
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.676
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.083
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.148
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.043
MECLTFEXP_MEC->PJM
CLTF
2.485
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
100.104

Details for WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.75 %
Rating:285.0 MVA
Rating Type:A
MVA to Mitigate:289.98
MW Contribution:
4.27
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.5 %
Rating:285.0 MVA
Rating Type:A
MVA to Mitigate:289.29
MW Contribution:
4.26
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
7.121
276603SUBLETTE C
Solar/Wind Harmer
0.62
971681AH1-341 GEN
Solar/Wind Harmer
4.268
962691AG1-118 GEN
Solar/Wind Harmer
43.181
276799AD1-013 GEN
Solar/Wind Harmer
4.89
276602WESTBROOK C
Solar/Wind Harmer
5.051
276863AD2-134 GEN
Solar/Wind Harmer
4.953
946671AF1-331 GEN
Solar/Wind Harmer
2.445
276861AD2-134 GEN
Solar/Wind Harmer
4.953
971675AH1-338 GEN
Solar/Wind Harmer
21.746
274855GSG-6 ;RU
Solar/Wind Harmer
10.243
962781AG1-127 GEN
Solar/Wind Harmer
14.068
274872LEEDK;1U
Solar/Wind Harmer
28.459
274872LEEDK;1U
Solar/Wind Harmer
5.515
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.514
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.041
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.495
WECLTFEXP_WEC->PJM
CLTF
0.282
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.075
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.226
NYPJM->LTFIMP_NY
CLTF
0.096
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
MECLTFEXP_MEC->PJM
CLTF
1.485
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
59.089
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.309

Details for WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line l/o COMED_P1-2_345-L15502_B-R_SRT-A-2


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.51 %
Rating:347.0 MVA
Rating Type:STE
MVA to Mitigate:348.78
MW Contribution:
4.68
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CE
Facility Description:
WATERMAN ; R-SANDWICH ; R 138.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L15502_B-R_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.27 %
Rating:347.0 MVA
Rating Type:STE
MVA to Mitigate:347.92
MW Contribution:
4.67
Bus #Bus NameTypeMW Contribution
274850MENDOTA H;RU
Solar/Wind Harmer
7.201
276603SUBLETTE C
Solar/Wind Harmer
0.686
971681AH1-341 GEN
Solar/Wind Harmer
4.678
957471AF2-041 GEN
Solar/Wind Harmer
2.892
959091AF2-200 GEN
Solar/Wind Harmer
1.928
971341AH1-150 GEN
Solar/Wind Harmer
1.928
971343AH1-151 GEN
Solar/Wind Harmer
1.928
962691AG1-118 GEN
Solar/Wind Harmer
43.266
276799AD1-013 GEN
Solar/Wind Harmer
4.941
276602WESTBROOK C
Solar/Wind Harmer
5.108
276863AD2-134 GEN
Solar/Wind Harmer
5.008
946671AF1-331 GEN
Solar/Wind Harmer
2.471
276861AD2-134 GEN
Solar/Wind Harmer
5.008
971675AH1-338 GEN
Solar/Wind Harmer
21.982
971171AH1-044 GEN
Solar/Wind Harmer
1.928
274855GSG-6 ;RU
Solar/Wind Harmer
10.358
962781AG1-127 GEN
Solar/Wind Harmer
14.111
971067AG2-660 GEN
Solar/Wind Harmer
0.877
274872LEEDK;1U
Solar/Wind Harmer
28.582
274872LEEDK;1U
Solar/Wind Harmer
5.539
959081AF2-199 GEN
Solar/Wind Harmer
0.964
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.11
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.068
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.085
WECLTFEXP_WEC->PJM
CLTF
0.306
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.083
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.249
NYPJM->LTFIMP_NY
CLTF
0.109
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
MECLTFEXP_MEC->PJM
CLTF
1.885
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
74.882
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.13
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.057
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.417
CONTINGENCY 'COMED_P1-2_138-L11106_B-R_SRT-A-1'
 CLOSE LINE FROM BUS 272114 TO BUS 272115 CKT Z1       /*N AURORA ; B 138.0 - N AURORA ; R 138.0
 MOVE 100 PERCENT LOAD FROM BUS 271586 TO BUS 271587   /*ESS W541 ; B 138.0 - ESS W541 ; R 138.0
 MOVE 100 PERCENT LOAD FROM BUS 272522 TO BUS 272523   /*SUGAR GRV; B 138.0 - SUGAR GRV; R 138.0
 TRIP BRANCH FROM BUS 271390 TO BUS 271586 CKT 1       /*ELECT JCT;2B 138.0 - ESS W541 ; B 138.0
 TRIP BRANCH FROM BUS 271586 TO BUS 272114 CKT 1       /*ESS W541 ; B 138.0 - N AURORA ; B 138.0
 TRIP BRANCH FROM BUS 272114 TO BUS 272522 CKT 1       /*N AURORA ; B 138.0 - SUGAR GRV; B 138.0
 TRIP BRANCH FROM BUS 272522 TO BUS 962690 CKT 1       /*SUGAR GRV; B 138.0 - AG1-118 TP   138.0
END
CONTINGENCY 'COMED_P1-2_138-L9407_R-R_SRT-A'
 TRIP BRANCH FROM BUS 271680 TO BUS 271430 CKT 1   /*HAUMESSER; B 138.0 - ESS H452 ; B 138.0
END
CONTINGENCY 'COMED_P1-2_138-L11305_B-R_SRT-A'
 TRIP BRANCH FROM BUS 272728 TO BUS 271430 CKT 1   /*WATERMAN ; B 138.0 - ESS H452 ; B 138.0
END
CONTINGENCY 'COMED_P1-2_345-L15502_B-R_SRT-A-2'
 TRIP BRANCH FROM BUS 957470 TO BUS 270732 CKT 1   /*AF2-041 TP   345.0 - ELECT JCT;1B 345.0
END
CONTINGENCY 'COMED_P4-6_111-345-B______SRT-A'
 DISCONNECT BUS 270730                                          /*ELECT JCT;2B 345.0
 DISCONNECT BUS 270732                                          /*ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 270928 TO BUS 272794 TO BUS 275334 CKT 1  /*WOLFS    ; B 345.0 - WOLFS    ; B 138.0 - WOLFS    ;1C  34.5
END
CONTINGENCY 'COMED_P4_111-45-TR81____SRT-A'
 DISCONNECT BUS 270732                             /*ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 275182 TO BUS 270732 CKT 1   /*ELECT JCT;1M 138.0 - ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 275182 TO BUS 271392 CKT 1   /*ELECT JCT;1M 138.0 - ELECT JCT;1B 138.0
 TRIP BRANCH FROM BUS 275182 TO BUS 275282 CKT 1   /*ELECT JCT;1M 138.0 - ELECT JCT;1C  34.5
END
CONTINGENCY 'COMED_P4_111-45-L11124__SRT-A'
 DISCONNECT BUS 270732                             /*ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 270732 TO BUS 270814 CKT 1   /*ELECT JCT;1B 345.0 - LOMBARD  ;4B 345.0
END
CONTINGENCY 'COMED_P2-2_111_EJ-345B__1_SRT-A'
 DISCONNECT BUS 270732   /*ELECT JCT;1B 345.0
END
CONTINGENCY 'COMED_P1-2_345-L15502_B-R_SRT-A-1'
 TRIP BRANCH FROM BUS 270828 TO BUS 957470 CKT 1   /*NELSON   ; B 345.0 - AF2-041 TP   345.0
END
CONTINGENCY 'COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-2'
 CLOSE LINE FROM BUS 272114 TO BUS 272115 CKT Z1       /*N AURORA ; B 138.0 - N AURORA ; R 138.0
 MOVE 100 PERCENT LOAD FROM BUS 271586 TO BUS 271587   /*ESS W541 ; B 138.0 - ESS W541 ; R 138.0
 MOVE 100 PERCENT LOAD FROM BUS 272522 TO BUS 272523   /*SUGAR GRV; B 138.0 - SUGAR GRV; R 138.0
 TRIP BRANCH FROM BUS 271390 TO BUS 271586 CKT 1       /*ELECT JCT;2B 138.0 - ESS W541 ; B 138.0
 TRIP BRANCH FROM BUS 271586 TO BUS 272114 CKT 1       /*ESS W541 ; B 138.0 - N AURORA ; B 138.0
 TRIP BRANCH FROM BUS 272114 TO BUS 272522 CKT 1       /*N AURORA ; B 138.0 - SUGAR GRV; B 138.0
 TRIP BRANCH FROM BUS 272522 TO BUS 962690 CKT 1       /*SUGAR GRV; B 138.0 - AG1-118 TP   138.0
 TRIP BRANCH FROM BUS 957470 TO BUS 270732 CKT 1       /*AF2-041 TP   345.0 - ELECT JCT;1B 345.0
END
CONTINGENCY 'COMED_P7-1_138-L11106_B-R_+_345-L93407_B-R_SRT-A-1'
 CLOSE LINE FROM BUS 272114 TO BUS 272115 CKT Z1       /*N AURORA ; B 138.0 - N AURORA ; R 138.0
 MOVE 100 PERCENT LOAD FROM BUS 271586 TO BUS 271587   /*ESS W541 ; B 138.0 - ESS W541 ; R 138.0
 MOVE 100 PERCENT LOAD FROM BUS 272522 TO BUS 272523   /*SUGAR GRV; B 138.0 - SUGAR GRV; R 138.0
 TRIP BRANCH FROM BUS 271560 TO BUS 271432 CKT 1       /*CREGO RD ;BT 138.0 - CREGO RD ; B 138.0
 TRIP BRANCH FROM BUS 271560 TO BUS 272728 CKT 1       /*CREGO RD ;BT 138.0 - WATERMAN ; B 138.0
 TRIP BRANCH FROM BUS 957470 TO BUS 270732 CKT 1       /*AF2-041 TP   345.0 - ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 962690 TO BUS 271560 CKT 1       /*AG1-118 TP   138.0 - CREGO RD ;BT 138.0
END
943120 to 272803 ckt 1
271680 to 272756 ckt 1
272002 to 272365 ckt 1
270828 to 957470 ckt 1
272516 to 271680 ckt 1
272756 to 272730 ckt 1
272730 to 272445 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary:

New Service Requests (projects) in PJM Transition Cycle 2, Cluster 60 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 60 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 60 projects will meet the dynamics requirements of the NERC, ComEd and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2028 summer peak case, modified to include applicable projects. Cluster 60 projects have been dispatched online at maximum power output and the voltage schedule set to achieve near unity power factor at the high side of the main transformer.

Cluster 60 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 310 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

  1. Three-phase faults with normal clearing time;
  2. Three-phase bus faults with normal clearing time;
  3. Three-phase to ground faults with three-phase delayed clearing due to a stuck breaker (GO breakers);
  4. Three-phase to ground faults with single-phase delayed clearing due to a stuck breaker (IPO breakers)
  5. Three-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure;
  6. Three-phase faults with loss of multiple-circuit tower line.
  7. Three-phase faults with normal clearing time and a failed high speed reclose attempt.

For all simulations, the Cluster 60 projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2028 summer peak case:

  1. Cluster 60 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 60 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

AG2-516, AH1-341, and AH1-564 meet the 0.95 leading and lagging PF requirements.

No mitigations were found to be required.

Table 1: TC2 Cluster 60 Projects

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

AG2-516

Solar

COMED

120

120

72

Pecatonica 138 kV

AH1-341

Solar

COMED

150

150

96.6

Stillman – Dixon 138 kV

AH1-564

Storage

COMED

330

150

150

Rockford II 138 kV

 

Reactive Power Analysis

Analysis Complete - No Issues

The reactive power capability of AH1-341 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-146NelsonIn Service
AA2-030NelsonIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVPartially in Service - Under Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV IEngineering & Procurement
AC1-102Johns Creek-Excel 138kV IIEngineering & Procurement
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVEngineering & Procurement
AC1-214Crescent RidgeIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-106North Waldo-Wild Creek 138 kVWithdrawn
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-128Modoc-Delaware 138 kVIn Service
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVWithdrawn
AD2-093Marysville 345kVPartially in Service - Under Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-172Lena 138kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVEngineering & Procurement
AE1-100Axton 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-143Marion County 161 kVUnder Construction
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-175Light Foot 34.5 kVIn Service
AE1-183Maysville-McDowell 69 kVUnder Construction
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVPartially in Service - Under Construction
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-089Pennville-Adams 138 kVSuspended
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVIn Service
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-214Cole 345 kVUnder Construction
AE2-216Hardin Switch 345 kVSuspended
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVUnder Construction
AE2-282East Fayette 138 kVIn Service
AE2-285Maysville 69 kVUnder Construction
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-308Three Forks-Dale 138 kVEngineering & Procurement
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-325Valley 138 kVWithdrawn
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVUnder Construction
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-038Sewellton Jct-Webbs Crossroads 69 kVUnder Construction
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-071College Corner 138 kVEngineering & Procurement
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-084Hartford-Almena 69 kVUnder Construction
AF1-086Madera-Westover South 115 kVPartially in Service - Under Construction
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-093Henderson-Stoneboro 69 kVUnder Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVSuspended
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVUnder Construction
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVPartially in Service - Under Construction
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVEngineering & Procurement
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVEngineering & Procurement
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-229Galion-South Berwick 345 kVUnder Construction
AF1-233Flemingsburg – Spurlock 138kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVUnder Construction
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-302Brookville-Squab Hollow 138 kVUnder Construction
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-014Maddox Creek 345 kVUnder Construction
AF2-018Inez 138 kVEngineering & Procurement
AF2-031CalumetEngineering & Procurement
AF2-032Kincaid 345 kVWithdrawn
AF2-039Shawville-Clearfield 34.5 kVUnder Construction
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-068Jay 138 kVEngineering & Procurement
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-122Kirk 138 kVPartially in Service - Under Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-144Powhatan 34.5 kVIn Service
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-187Brookside-Cloverdale 138 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-226Katydid Road 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-319Katydid Road 345 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVPartially in Service - Under Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-396Stinger 138 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVUnder Construction
AF2-441Burnham 138kVEngineering & Procurement
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-109Valley 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-198Union City 34.5 kVIn Service
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Hodgenville-Stephensburg 69 kVEngineering & Procurement
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-410Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-471Up Church-Wayne County 69 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-508Point Lookout 69 kVWithdrawn
AG1-513Aurora 138 kVSuspended
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-014Meadow Lake 345 kVActive
AG2-029Forest G. Hipple-Dunton Lake 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Avon - Renaker 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-332East Elkhart - Elcona Tap 138 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-424Summersville - Magnolia 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-492Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-562Elderberry 345 kVActive
AG2-568Stink Run - Sundial 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-348Pound 34.5 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Delaware Business Park 138kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-563Aurora E.C. 138kVActive
AH1-564Rockford II 138 kVActive
AH1-567University Park 138 kVActive
AH1-570Millersburg 69 kVActive
AH1-571Millersburg 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-673State Line - River Energy Center 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
W1-056Ada-Dunkirk 69kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
X3-005Wildwood 12kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-081Streator 34.5kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts
AH1-341 System Reinforcements:
TOTrans Owner IDTitleAllocated Cost ($USD)
NIPSNIPS_TC1_12093Upgrade 2000A wave trap and line switch at Green Acres substation.$60,305
NIPSNIPS_TC2_18520Existing NIPS rating: SN/SE: 1538/1877 MVA$0
Grand Total:$60,305

System Reinforcement
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
(Pending) / NIPS_TC1_12093
Title
Upgrade 2000A wave trap and line switch at Green Acres substation.
Description
Upgrade wave trap and M.O. at GreenAcres substation. Current MISO end ratings are Rate A = 1195 and Rate B = 1195 MVA
Total Cost ($USD)
$1,000,000
Allocated Cost ($USD)
$60,305
Time Estimate
12 Months

Contributor

FacilityContingency
05OLIVE-17P9700-EAST 345.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-363
23.7 MW12.1%$120,609
AG2-364
15.8 MW8.0%$80,406
AG2-453
25.3 MW12.8%$128,395
AG2-524
11.5 MW5.8%$58,172
AG2-660
1.9 MW1.0%$9,655
AH1-044
16.3 MW8.3%$83,022
AH1-150
16.3 MW8.3%$83,022
AH1-151
16.3 MW8.3%$83,022
AH1-196
12.5 MW6.3%$63,286
AH1-338
14.9 MW7.6%$75,531
AH1-341
11.9 MW6.0%$60,305
AH1-543
12.9 MW6.6%$65,607
AH1-714
17.5 MW8.9%$88,969

System Reinforcement
Type
Load Flow
TO
ITCT
RTEP ID / TO ID
(Pending) / ITCT_TC1_13866
Title
MTEP #25223/#25224 - Lulu Sub. Construct the Lulu switching station. Cut in the Lemoyne-Maple and Milan-Monroe-Morocco lines into the new station (Projected ISD 6/11/2027)
Description
Construct the Lulu switching station. Cut in the Lemoyne-Maple and Milan-Monroe-Morocco lines into the new station. This project is a DPP 2020 Network Upgrade associated with the J1516, J1525, J1526, J1527, J1550, J1553, J1557, J1571, J1586, J1587, J1603, J1614, J1635, J1658, J1659, J1663, and J1664 projects. Projected In-Service 6/1/2027
Total Cost ($USD)
$29,916,928
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
METC
RTEP ID / TO ID
(Pending) / METC_TC2_19125
Title
Reconductor Allen Junction - Morocco to 2-1431 ACSS and replace 13 trainers
Description
Reconductor Allen Junction - Morocco to 2-1431 ACSS and replace 13 trainers. New ratings for METC/MISO facilities will be 2094/2390 MVA SN/SE.
Total Cost ($USD)
$17,019,725
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
(Pending) / NIPS_TC2_18494
Title
Reconductor 2.9 miles of overhead line to 2-795 ACSS@ 250°C.
Description
Reconductor 2.9 miles of overhead line to 2-795 ACSS@ 250°C.
Total Cost ($USD)
$6,000,000
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AMIL
RTEP ID / TO ID
(Pending)
Title
Rebuild Snyder to Sullivan to 4000 A
Description
Rebuild Snyder to Sullivan to 4000 A
Total Cost ($USD)
$2,568,800
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
05SULLIVAN-7SNYDER 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
(Pending) / NIPS_TC1_15152
Title
NIPS SN/SE ratings of 2133/2577 MVA achieved by change out of 2156 ACSR line conductor with 2-1590 ACSR conductor.
Description
NIPS SN/SE ratings of 2133/2577 MVA achieved by change out of 2156 ACSR line conductor with 2-1590 ACSR conductor.
Total Cost ($USD)
$1,800,000
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
17MUNSTER-BURNHAM ;0R 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
(Pending) / NIPS_TC1_15151
Title
NIPS SN/SE ratings of 1538/1877 MVA achieved by change out of 2156 ACSR line conductor with 2-1590 ACSR conductor and change out of 2156 ACSR conductor drop with 3000 AL conductor
Description
NIPS SN/SE ratings of 1538/1877 MVA achieved by change out of 2156 ACSR line conductor with 2-1590 ACSR conductor and change out of 2156 ACSR conductor drop with 3000 AL conductor
Total Cost ($USD)
$6,200,000
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
17SHEFFIELD-BURNHAM ; B 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
(Pending) / NIPS_TC2_18520
Title
Existing NIPS rating: SN/SE: 1538/1877 MVA
Description
Existing NIPS rating: SN/SE: 1538/1877 MVA
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
(Pending) / NIPS_TC1_15499
Title
NIPS SN/SE ratings of 1961/2390 MVA (TC2 and beyond)
Description
NIPS SN/SE ratings of 1206/1508 MVA (pre-TC1)
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
(Pending) / NIPS_TC2_Reactor
Title
Addition of 2 ohm reactor on the St. John to Crete 345kV line
Description
Addition of 2 ohm reactor on the St. John to Crete 345kV line
Total Cost ($USD)
$20,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)

New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact
          Powerton ;B 345 kV  (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-363, AG2-364
        
          Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-660, AH1-044, AH1-150, AH1-151
        

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Impacted FacilityTransmission OwnerReinforcementCostCost Allocated to AH1-341Scenarios
  • 17REYNOLDS 765.0 - 05GRNTWN 765.0 CKT 1
NIPS Reynolds-Greentown 765 kV
NIPSCO: No mitigation required. Rating Of NIPS-
Owned
Line Portion: SN/SE=9015 MVA/9015 MVA.

AEP: No mitigation required. 8348 MVA SN/SE
$0$0
  • NIPSCO
  • Contingent
  • Wvrich 69.0 - Rochester TP 69.0 CKT 1
NIPS Wvrich - Rochester TP 69 kV
DEI: Rebuild 1 mile of 69kV with 477ACSR/VR2 @
100/120C the ratings assume that NIPSCO terminal
upgrades would not limit our T-Line rating. $1.5M

NIPSCO: DEI mitigations acceptable to remove
constraint. $0
$1,500,000$34,098
  • NIPSCO
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AH1-341 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
ComEdn5318.1Garden Prarie - Silver Lake R 345 kV: Line rebuild, station bus work & Silver Lake 345kV Breaker ReplacementCost Allocated$19,850,112N/A
ComEdn3515.1Cherry Valley - Garden Prarie 345 kV: Line rebuild, station bus work, & Cherry Valley 345kV breaker replacementCost Allocated$16,021,714N/A
AEPn9785.0Olive - 17P9700-East: Rebuild LineCost Allocated$12,983,607N/A
AEPn9182.0Rebuild Olive - AF2-359 345kVCost Allocated$2,110,047N/A
ComEdn5792Rebuild Haumesser - West Dekalb 138 kV line (L11323)Cost Allocated$1,118,399N/A
ComEdn6779Plano 138 KV re-conductor a portion of the lineCost Allocated$903,171N/A
ComEdn9172.0Haumesser - Steward 138 kV Line ReconductorCost Allocated$800,591N/A
ComEdn9166.0Reconductor the McGirr Road to ESS H447 RT 138 KV lineCost Allocated$605,422N/A
ComEdn6639.2Reconductor the Electric Junction 345 kV line 93407, perform sag mitigation on 345 kV line 93407, upgrade one 345 kV circuit breaker and associated motor operated disconnect switches.Contingent$0N/A
ComEdb3811.1Expand Haumesser Road 138 kV substation as a 4 circuit breaker ring bus.Contingent$0N/A
ComEdb3811.2Additional Circuit Breaker at ESS H452Contingent$0N/A
ComEdb3811.3Rebuild 3 miles of 138 kV line 11323 from Haumesser Road to the H-452 tapContingent$0N/A
ComEdn6611The upgrades will be to reconductor the line, station conductor upgrades.Contingent$0N/A
ComEds3011Replace 345kV straight bus at TSS 116 Goodings Grove with a gas insulated switchgear ("GIS") breaker and a half configuration.Contingent$0N/A
Grand Total:$54,393,063

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n5318.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n5318.1 / ce-012a
Title
Garden Prarie - Silver Lake R 345 kV: Line rebuild, station bus work & Silver Lake 345kV Breaker Replacement
Description
• Rebuild entire 345kV transmission line L.97104 from TSS 971 Prairie to TSS 138 Silver Lake (approximately 24.7 miles). • Replace static wire with OPGW that contains single-mode 48 count fiber. Install 48-ct FDP at TSS 138 Silver Lake and TSS 971 Prairie to account for new OPGW. • Upgrade the existing substation TSS138 Silver Lake by replacing existing circuit breaker 345kV BT 3-4 & associated disconnect switches and replacing the line disconnect switch for 345kV line 97104. • Upgrade relay & protection at 345kV substation TSS 138 Silver Lake to support upgrade of 345kV transmission line, 97104.
Total Cost ($USD)
$163,968,683
Discounted Total Cost ($USD)
$163,968,683
Allocated Cost ($USD)
$19,850,112
Time Estimate
60 Months

Contributor

FacilityContingency
SILVER LK; R-AF2-349 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1448.0 MVA
(All)B1863.0 MVA
(All)C2232.0 MVA
(All)STE1975.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-51623.3 MW13.1%$21,556,046
AG2-660 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
1.2 MW0.7%$1,099,647
AH1-044 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
10.2 MW5.8%$9,455,299
AH1-150 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
10.2 MW5.8%$9,455,299
AH1-151 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
10.2 MW5.8%$9,455,299
AH1-19663.8 MW36.0%$59,014,397
AH1-34121.4 MW12.1%$19,850,112
AH1-56436.8 MW20.8%$34,082,582

System Reinforcement: n3515.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n3515.1 / ce-017
Title
Cherry Valley - Garden Prarie 345 kV: Line rebuild, station bus work, & Cherry Valley 345kV breaker replacement
Description
• Rebuild entire 345kV transmission line L.15616 from TSS 156 Cherry Valley to TSS 971 Prairie (approximately 15.4 miles). • Replace static wire with dual OPGW that each contain single-mode 48 count fiber. Install two (2) 48-ct FDPs at TSS 156 Cherry Valley and TSS 971 Prairie to account for new OPGW. • Upgrade the existing substation TSS 156 Cherry Valley by upgrading existing 345kV BT 4-7 circuit breaker and associated disconnect switches. • Upgrade SCADA, relay & protection at 345kV substation TSS 156 Cherry Valley to support upgrade of 345kV L.15616.
Total Cost ($USD)
$84,712,245
Discounted Total Cost ($USD)
$84,712,245
Allocated Cost ($USD)
$16,021,714
Time Estimate
50 Months

Contributor

FacilityContingency
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1448.0 MVA
(All)B1865.0 MVA
(All)STE1975.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-51623.3 MW20.5%$17,398,633
AG2-660 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
1.2 MW1.0%$887,563
AH1-044 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
10.2 MW9.0%$7,631,700
AH1-150 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
10.2 MW9.0%$7,631,700
AH1-151 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
10.2 MW9.0%$7,631,700
AH1-34121.4 MW18.9%$16,021,714
AH1-56436.8 MW32.5%$27,509,235

System Reinforcement: n9785.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9785.0 / AEP-TC2-19160
Title
Olive - 17P9700-East: Rebuild Line
Description
Rebuild Transmission line (~41 mi)
Total Cost ($USD)
$215,300,000
Discounted Total Cost ($USD)
$215,300,000
Allocated Cost ($USD)
$12,983,607
Time Estimate
60 to 72 Months

Contributor

FacilityContingency
05OLIVE-17P9700-EAST 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B2788.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-363 ⧉ Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
23.7 MW12.1%$25,967,214
AG2-364 ⧉ Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
15.8 MW8.0%$17,311,476
AG2-45325.3 MW12.8%$27,643,470
AG2-52411.5 MW5.8%$12,524,359
AG2-660 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
1.9 MW1.0%$2,078,646
AH1-044 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
16.3 MW8.3%$17,874,602
AH1-150 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
16.3 MW8.3%$17,874,602
AH1-151 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
16.3 MW8.3%$17,874,602
AH1-19612.5 MW6.3%$13,625,461
AH1-33814.9 MW7.6%$16,261,765
AH1-34111.9 MW6.0%$12,983,607
AH1-54312.9 MW6.6%$14,125,167
AH1-71417.5 MW8.9%$19,155,030

System Reinforcement: n9182.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9182.0 / AEPIMJMS01
Title
Rebuild Olive - AF2-359 345kV
Description
Rebuild the ~7.3 mile 345 kV line section between Olive and AF2-359 POI. The standard conductor for 345kV lines is 2-bundle 954 ACSR 45/7 RAIL.
Total Cost ($USD)
$35,000,000
Discounted Total Cost ($USD)
$35,000,000
Allocated Cost ($USD)
$2,110,047
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
05OLIVE-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1410.0 MVA
(All)B1718.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-363 ⧉ Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
23.2 MW12.1%$4,240,898
AG2-364 ⧉ Powerton ;B 345 kV (ComEd): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-363, AG2-364
15.5 MW8.1%$2,827,387
AG2-45324.6 MW12.8%$4,487,432
AG2-52411.1 MW5.8%$2,023,186
AG2-660 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
1.9 MW1.0%$337,775
AH1-044 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
15.9 MW8.3%$2,904,212
AH1-150 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
15.9 MW8.3%$2,904,212
AH1-151 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
15.9 MW8.3%$2,904,212
AH1-19612.1 MW6.3%$2,216,435
AH1-33814.5 MW7.5%$2,639,247
AH1-34111.6 MW6.0%$2,110,047
AH1-54312.6 MW6.5%$2,291,435
AH1-71417.1 MW8.9%$3,113,520

System Reinforcement: n5792
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n5792 / CE_NUN_L11323
Title
Rebuild Haumesser - West Dekalb 138 kV line (L11323)
Description
Transmission line L11323 (Haumesser to W Dekalb) will be rebuilt as double-circuit from TSS 94 Haumesser Rd. to Structure 3001. The rebuild of this portion of L11323 will require the removal of seventeen (17) structures. This study assumes existing Structure 302 (with switch 2311) will remain. Based on preliminary analysis of this portion of L11323, fourteen (14) double-circuit structures and one (1) single-circuit structure are required for the L11323 rebuild. All double-circuit and single-circuit structures will be weathering steel on a drilled pier foundation. Because of uncertainty in the transmission and substation layouts pending detailed engineering, this study assumes that two additional double-circuit structures and two additional single-circuit structures may be required, bringing the total to sixteen (16) double-circuit structures and two (2) single-circuit structures. This study assumes one additional structure may need to be removed, bringing the total to eighteen (18) structure removals. Proposed conductor and shield wire include T-2 556.5 KCMIL (24/7) “Parakeet” ACSR and 7#6 Alumoweld, respectively.
Total Cost ($USD)
$10,479,841
Discounted Total Cost ($USD)
$10,479,841
Allocated Cost ($USD)
$1,118,399
Time Estimate
30 Months

Contributor

FacilityContingency
HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA519.0 MVA
LLB564.0 MVA
LLC759.0 MVA
LLSTE644.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-33855.5 MW89.3%$9,361,442
AH1-3416.6 MW10.7%$1,118,399

System Reinforcement: n6779
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n6779 / CE_NUN_L14609
Title
Plano 138 KV re-conductor a portion of the line
Description
The upgrade will be to re-conductor a portion of the line. Potential transmission tower replacement required with line reconductor. The estimate for this work will not be known until the Phase 3 system upgrade Facility Study is completed per the PJM process.B ased on the conductor upgrade the scope of work might include multiple tower upgrades. This cost is not included in the preliminary estimate. A more thorough engineering study will be performed during the Facility Study Phase. It is at this time any tower upgrades/replacements will be determined.
Total Cost ($USD)
$5,600,000
Discounted Total Cost ($USD)
$5,600,000
Allocated Cost ($USD)
$903,171
Time Estimate
30 Months

Contributor

FacilityContingency
W PLANO ; R-AE2-341 TP 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A376.0 MVA
(All)ALDR619.0 MVA
(All)B483.0 MVA
(All)C538.0 MVA
(All)STE505.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-33830.2 MW83.9%$4,696,829
AH1-3415.8 MW16.1%$903,171

System Reinforcement: n9172.0
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n9172.0 / CE_NUN_L18623.2
Title
Haumesser - Steward 138 kV Line Reconductor
Description
Reconductor line between the two terminal points. Transmission tower replacement might be required. This will be determined during the network upgrade Facility Study per the PJM process. The estimate provided here does not include the tower work. Substation conductor upgrades at TSS 186 Steward & TSS 94 Haumesser Rd.
Total Cost ($USD)
$8,500,000
Discounted Total Cost ($USD)
$8,500,000
Allocated Cost ($USD)
$800,591
Time Estimate
18 to 24 Months

Contributor

FacilityContingency
HAUMESSER; B-STEWARD ; B 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLALDR722.0 MVA
LLSTE644.0 MVA
SUMA487.0 MVA
SUMALDR722.0 MVA
SUMB534.0 MVA
SUMSTE612.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-660 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
1.4 MW1.1%$91,803
AH1-044 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
7.6 MW6.0%$510,546
AH1-150 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
7.6 MW6.0%$510,546
AH1-151 ⧉ Nelson-Electric Junction 345kV - ComEd: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-660, AH1-044, AH1-150, AH1-151
7.6 MW6.0%$510,546
AH1-33890.1 MW71.5%$6,075,967
AH1-34111.9 MW9.4%$800,591

System Reinforcement: n9166.0
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n9166.0 / CE_NUN_L16914.1
Title
Reconductor the McGirr Road to ESS H447 RT 138 KV line
Description
• Reconductor 0.2 miles of 138kV transmission line 16914 from TSS 169 McGirr Road to Structure 216. • Substation conductor and equipment confirmed to meet or exceed minimum capability required below.
Total Cost ($USD)
$605,422
Discounted Total Cost ($USD)
$605,422
Allocated Cost ($USD)
$605,422
Time Estimate
24 Months

Contributor

FacilityContingency
MCGIRR RD;-ESS H447 ;RT 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A533.0 MVA
(All)B690.0 MVA
(All)C834.0 MVA
(All)STE735.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AH1-3417.6 MW100.0%$605,422

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02LALLENDORF-19MON12 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / ATSI-2025-005 (Supplemental)
Title
Lallendorf & Allen Jct Substation Upgrades (Projected ISD 6/1/2032) - s3845.1
Description
1) At Lallendorf Substation: Substation: Replace line relaying. Install new seven-mile ADSS fiber line from Lallendorf Substation to Toledo Edison regional services territory boundary. 2) At Allen Junction Substation: replace disconnect switches, breaker leads, metering, and transmission line drops. Cost Est: $7.21 mil Allen Junction – Morocco 345 kV Line ratings: - Before Proposed Solution: 1517 / 1793 / 1759 / 1793 MVA (SN/SE/WN/WE) - After Proposed Solution: 1868 / 2249 / 2340 / 2535 MVA (SN/SE/WN/WE) Laplaissance Creek 345kV sub involves tapping the Lemoyne-Maple (J1062 POI) 345kV line & Lallendorf-Monroe 345kV line https://www.pjm.com/-/media/DotCom/committees-groups/committees/teac/2025/20251208/20251208-item-04---atsi-supplemental-projects.pdf
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1868.0 MVA
(All)B2249.0 MVA
WINA2340.0 MVA
WINB2535.0 MVA

System Reinforcement: b4068.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4068.1 / AEP-TC2-18693
Title
b4068: Greentown 765 kV - Teddy 765kV - Marysville 765 kV - Greenfield Line - AEP Proposal 570
Description
b4068.1 through b4068.49: Affected Transmission Owners: AEP / Dayton / ATSI The objective of this project is to construct multiple transmission lines to address Ohio area violations. The total distance covered by the lines is approximately 359.54 miles. The first transmission line ranges from the existing Greentown Substation in Howard County, Indiana to the new Teddy Substation in Clark County, Ohio, the line then branches north towards the existing Marysville Substation in Union County, Ohio, and east to the existing Beatty Substation in Franklin County, Ohio, and then extends to the existing Cole Substation in Franklin County, Ohio. The second transmission line extends from the existing Adkins Substation in Pickaway County, Ohio, to the new West Millersport Substation in Fairfield County, Ohio, then continues to the existing Conesville Substation in Coshocton County, Ohio before finally extending to the existing Guernsey Substation in Guernsey County, Ohio. There is a total of five transmission lines that extend between unnamed substations (Hayden - Cole 345 kV, Hyatt - Maliszewski 345 kV [double circuit], Roberts - Kenny 138 kV, Wilson - 5th Avenue 138 kV, West Millersport-Kirk 345 kV). This project will traverse 4 counties (Howard, Grant, Blackford, Jay) in Indiana, and 13 counties (Darke, Shelby, Champaign, Clark, Madison, Franklin, Delaware, Pickaway, Fairfield, Licking, Muskingum, Coshocton, Guernsey) in Ohio. This proposal has a total of 38 components, including 16 substation upgrade components, two greenfield substation components, eight greenfield transmission line components covering approximately 336.2 miles, and 12 transmission line upgrade components covering approximately 23.34 miles. b4068.28/b4068.49 is dependent on b3919.1 Baseline completion.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05GAVIN 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5395.0 MVA
(All)B5523.0 MVA
05SORENS-05DUMONT_RS 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b3919.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3919.1
Title
Reconfigure Maliszewski 765 kV station and establish 345 kV breaker yard
Description
Reconfigure Maliszewski 765 kV station from 2 breakers to a 6 breaker ring bus. Install a new 765/345 kV transformer. Establish new 345 kV breaker yard with 3 string breaker and a half to include a line exit to Hyatt and a line exit to Corridor. Loop the existing Hyatt - West Millersport 345 kV line into the new established 345 kV yard at the Maliszewski station.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
02ALLEN-18MOROCCO 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer(Any)
No new ratings for this Flowgate.
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SORENSN_RM-05MARYSVL_RS 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MOUNTN-05GAVIN 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05DUMONT_RS 765.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9769.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9769.0 / AEP-TC2-19070
Title
05CLOVRD_RJA 765.0 kV to 05CLOVRD 765.0 kV ckt Z1 - Upgrade/replace CBs
Description
Upgrade/replace Cloverdale 765 kV, 4000 A CBs "CC" and "CC2" to 5000 A
Total Cost ($USD)
$25,000,000
Discounted Total Cost ($USD)
$25,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
05CLOVRD-05CLOVRD_RJA 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: s3588.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s3588.1 / (Pending)
Title
Construct new Larrison Drive 345 kV substation
Description
Construct a new station in a breaker and a half configuration consisting of sixteen (16) 345kV 5000A 63kA breakers, six (6) 345kV meters, and station fiber cable. Construct six (6) 345kV bus ties from AEP’s Larrison Drive 345kV station to the customer station. Cut in the Elderberry-Dumont and Dumont-Olive Bypass 345 kV line into the new station.
Cost Information
Time Estimate
Dec 15 2026

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-341 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05DUMONT-05ELDERBERRY 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: s3588.2
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s3588.2 / (Pending)
Title
Construct new New Prairie 345 kV substation
Description
New station to be constructed in a breaker and a half configuration consisting of sixteen (16) 345kV 5000A 63kA breakers, six (6) 345kV meters, and station fiber cable. Construct six (6) bus ties from AEP’s New Prairie 345kV station to the customer station. Cut in the Elderberry-Dumont and Dumont-Olive Bypass 345 kV line into the new station.
Cost Information
Time Estimate
Dec 15 2026

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-341 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05DUMONT-05ELDERBERRY 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9749.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9749.0 / AEP-TC2-18677
Title
05DUMONT_RW 765.0 kV to 05DUMONT 765.0 kV ckt Z1 - Replace Breaker
Description
Replace 765kV CB B at Dumont
Total Cost ($USD)
$4,000,000
Discounted Total Cost ($USD)
$4,000,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-05DUMONT_RW 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5395.0 MVA
(All)B6095.0 MVA

System Reinforcement: s3442.26
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s3442.26
Title
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont
Description
Dumont 765 kV: Replace 3000 A circuit breaker at Dumont to address a generation deliverability violation on the Dumont – Sorenson 765 kV branch related to the new customer interconnections in the area. Projected in service date 3/5/2027
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-341 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5395.0 MVA
(All)B5523.0 MVA
(All)C5523.0 MVA

System Reinforcement: n9748.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9748.0 / AEP-TC2-18670
Title
17STILLWELL 345.0 kV to 05DUMONT 345.0 kV ckt 1 - Reconductor and Replace Equipment
Description
Rebuild ~8.62 miles of AEP owned 345kV line from Dumont to Stillwell utilizing 3-954 CARDINAL ACSR 54/7. At Dumont, replace the 2-1700 KCM AAC 61 str station conductor, the wavetrap facing Stillwell, the switches for CBs F and F1, and increase the CT thermal limit above 2739.336 MVA. NIPSCO will have to address their elements below 2739.336 SE MVA.
Total Cost ($USD)
$26,060,000
Discounted Total Cost ($USD)
$26,060,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2103.0 MVA
(All)B2921.0 MVA

System Reinforcement: n9678.0
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n9678.0 / CE_NUN_L11215_1
Title
Mitigate the sag on L11215
Description
Mitigate the sag on L11215. A preliminary estimate for this work is $9M with an estimated construction timeline of 30 months. Upon completion of this work the new line ratings will be 4142/4460/5331/6368/7323 MVA (SN/SLTE/SSTE/SLD/ALDR).
Total Cost ($USD)
$9,000,000
Discounted Total Cost ($USD)
$9,000,000
Allocated Cost ($USD)
$0
Time Estimate
30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4142.0 MVA
(All)ALDR7323.0 MVA
(All)B4460.0 MVA
(All)C6368.0 MVA
(All)STE5331.0 MVA

System Reinforcement: n9763.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9763.0 / AEP-TC2-19060
Title
05J.FERR 765.0 kV to 05CLOVRD_RJA 765.0 kV ckt 1 - Replace Wavetraps
Description
Replace wave trap on 765 kV Cloverdale line. Replace/upgrade CB's B and B2 with 5000A CBs.
Total Cost ($USD)
$3,300,000
Discounted Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
05J.FERR-05CLOVRD_RJA 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A6077.0 MVA
(All)B6667.0 MVA

System Reinforcement: n9767.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9767.0 / AEP-TC2-19068
Title
05KAMMER_RG 765.0 kV to 05KAMMER 765.0 kV ckt Z1 - Replace Wavetraps
Description
Replace the existing 3000A wave trap at Kammer 765 station towards Guernsey with a 5000A wave trap. Additionally, replace the 3000A circuit breaker QQ1 with a 5000A circuit breaker. Disconnect switches and a relays will be upgraded as well.
Total Cost ($USD)
$4,500,000
Discounted Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3851.2
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.2
Title
Rebuild R.P. Mone – Maddox Creek 345kV line (9.4 miles).
Description
Rebuild R.P. Mone – Maddox Creek 345kV line (9.4 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA
(All)C3774.0 MVA
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA
(All)C3774.0 MVA

System Reinforcement: n9786.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9786.0 / AEP-TC2-19161
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Wave Traps
Description
Replace wave tap at Maliszewski towards Marysville
Total Cost ($USD)
$3,000,000
Discounted Total Cost ($USD)
$3,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B5523.0 MVA

System Reinforcement: n9766.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9766.0 / AEP-TC2_19067
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Wavetrap
Description
Replace 4000A Wavetrap towards Maliszewski with 5000A equivalent
Total Cost ($USD)
$1,100,000
Discounted Total Cost ($USD)
$1,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

System Reinforcement: b3878.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3878.1
Title
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
Description
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
Cost Information
Time Estimate
Nov 12 2027

Not Contingent

Note: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B6667.0 MVA
(All)C6868.0 MVA

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18516
Title
17P9700-EAST 345.0 kV to 05OLIVE 345.0 kV ckt 1 - AEP End Ratings
Description
AEP end rating is 1413 MVA Rate B.
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
05OLIVE-17P9700-EAST 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A972.0 MVA
(All)B1413.0 MVA

System Reinforcement: b3851.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.1 / B3851.1
Title
Rebuild Allen-RP Mone 345kV
Description
Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3137.0 MVA
(All)B3664.0 MVA

System Reinforcement: n7925.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n7925.1 / AEPI0010a
Title
Reconductor ~0.41 miles of the Sullivan – West Casey (Ameren) line
Description
•Remove ~0.41 miles of 1024.5 ACAR 30/7 conductor on the Sullivan – West Casey (Ameren) 345 kV line. •Rebuild line with ACSS Cardinal 974 KCM (54/7) •Evaluate line settings
Total Cost ($USD)
$1,216,000
Discounted Total Cost ($USD)
$1,216,000
Allocated Cost ($USD)
$0
Time Estimate
11 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
05SULLIVAN-7SNYDER 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1754.0 MVA
(All)B1942.0 MVA

System Reinforcement: b2831.2
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
b2831.2
Title
Rebuild the Tanner Creek – Miami Fort 345kV line (DEOK portion), Actual In-service date 5/14/2021
Description
Rebuild the Tanner Creek – Miami Fort 345kV line (DEOK portion) Actual In-service date 5/14/2021
Cost Information
Time Estimate
May 14 2021

Not Contingent

Note: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2390.0 MVA
(All)B2390.0 MVA
(All)C2390.0 MVA

System Reinforcement: s2019
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
s2019 / AEP Project Resolves Overload
Title
AEP Project s2019 Resolves DEOK Overload
Description
Install two (2) new 345 kV breakers and move the existing M2 breaker into the new N string at Tanners Creek station. Terminate the Dearborn line and the transformer into the new N string. Install a new 345 kV breaker “T” to complete the T string. Projected in-service date 5/23/2023.
Cost Information
Time Estimate
May 26 2021

Not Contingent

Note: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-341 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A2403.0 MVA
(All)B2403.0 MVA

System Reinforcement: b2968
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b2968
Title
Upgrade existing 345kV terminal equipment at Tanners Creek station on Tanners Creek - Miami Fort 345kV line, Actual In-Service Date 12/22/2020
Description
Upgrade existing 345kV terminal equipment at Tanners Creek station on Tanners Creek - Miami Fort 345kV line, Actual In-Service Date 12/22/2020
Cost Information
Time Estimate
Dec 22 2020

Not Contingent

Note: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1409.0 MVA
(All)B2542.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
(Pending)
Title
ComEd SSTE Rating 2295 MVA.
Description
None
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
17P9701-WEST-UNIV PK N;RP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement
Type
Load Flow
TO
NextEra
RTEP ID / TO ID
(Pending)
Title
NextEra Rating is 2495 MVA.
Description
None
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
17P9701-WEST-UNIV PK N;RP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9755.0
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n9755.0 / CE_NUN_L17705_1
Title
Reconductor Sheffield - Burnham and upgrade station conductor at Burnham
Description
This upgrade will be to reconductor the line and upgrade station conductor at Burnham Potential transmission tower replacement required with line reconductor. The estimate for this work will not be known until the Phase 3 system upgrade Facility Study is complete per the PJM process.
Total Cost ($USD)
$14,000,000
Discounted Total Cost ($USD)
$14,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
17SHEFFIELD-BURNHAM ; B 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1334.0 MVA
(All)B1528.0 MVA
(All)C1912.0 MVA
(All)STE1837.0 MVA

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending)
Title
AEP end ratings are 1413 MVA
Description
AEP end ratings are 1413 MVA
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)B1413.0 MVA

System Reinforcement
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
(Pending)
Title
ComEd SSTE Rating of 2499 MVA
Description
None
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)STE2499.0 MVA

System Reinforcement
Type
Load Flow
TO
NextEra
RTEP ID / TO ID
(Pending)
Title
NextEra STE Rating of 2495 MVA
Description
None
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
17STJOHN-CRETE EC ;BP 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4006.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b4006.1
Title
Install 765/345 kV TR 91 and associated 765 kV and 345 kV circuit breakers at Wilton Center.
Description
Install 765/345 kV TR 91 and associated 765 kV and 345 kV circuit breakers at Wilton Center.
Cost Information
Time Estimate
Dec 01 2030

Not ContingentTopology Changing

Note 1: AH1-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
COLLINS ;-COLLINS ;2M 765.0/345.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
WILTON ;-WILTON ;3M 765.0/345.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
WILTON ;-WILTON ;4M 765.0/345.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
WILTON ; B-AD1-100 TAP1 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9719.0
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n9719.0 / CE_NUN_COLLINS_TR
Title
Collins Station 23 New Transformer-reduces contingency events.
Description
Installation of 2nd transformer at Station 23 Collins. Installation to include station work, new breakers, switches and supporting facilities at both 345KV & 765KV level. Possible station civil, grading and yard expansion work required. The estimate given will not include this price and time. Facility Study at Phase III will provide further information.
Total Cost ($USD)
$15,600,000
Discounted Total Cost ($USD)
$15,600,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
COLLINS ;-COLLINS ;2M 765.0/345.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 lineCOMED_P4_023-65-BT3-4___SRT-A
No new ratings for this Flowgate.
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 lineCOMED_P4_023-65-BT4-5___SRT-A
No new ratings for this Flowgate.
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 lineCOMED_P4_023-65-BT3-4___SRT-A
No new ratings for this Flowgate.
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 lineCOMED_P4_023-65-BT4-5___SRT-A
No new ratings for this Flowgate.
WILTON ; B-AD1-100 TAP1 345.0 kV Ckt 1 lineCOMED_P4_023-65-BT3-4___SRT-A
No new ratings for this Flowgate.
WILTON ; B-AD1-100 TAP1 345.0 kV Ckt 1 lineCOMED_P4_023-65-BT4-5___SRT-A
No new ratings for this Flowgate.

System Reinforcement: n7023.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n7023.1 / CE_NUN_L11124.1
Title
Reconductor the Electric Junction - Lombard line L11124 345 kV Line and perform associated station relay and protection upgrades.
Description
• Upgrade 13.5 Miles of 345kV transmission line 11124 from TSS 111 Electric Junction to TSS 120 Lombard • Upgrade relay & protection at 345kV substation TSS 111 Electric Junction & TSS 120 Lombard to support upgrade of 345kV transmission line, L1124
Total Cost ($USD)
$38,797,273
Discounted Total Cost ($USD)
$38,797,273
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA1334.0 MVA
SUMB1726.0 MVA
SUMC2084.0 MVA
SUMSTE1837.0 MVA

System Reinforcement: n6639.2
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n6639.2 / CE_NUN_L15502_4
Title
Reconductor the Electric Junction 345 kV line 93407, perform sag mitigation on 345 kV line 93407, upgrade one 345 kV circuit breaker and associated motor operated disconnect switches.
Description
• Reconductor 27.2 Miles of 345kV transmission line 93407 from structure 339 to structure 454 • Perform sag mitigation on 13.5 miles of 345kV transmission line 93407 from structure 454 to TSS 111 Electric Junction • Upgrade the existing substation TSS 111 Electric Junction by replacing L.93407 CB motor-operated disconnect switches on both sides of the breaker.
Total Cost ($USD)
$146,197,759
Discounted Total Cost ($USD)
$146,197,759
Allocated Cost ($USD)
$0
Time Estimate
Sep 30 2029

Contingent

Note: Based on PJM cost allocation criteria, AH1-341 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AH1-341 may not have cost responsibility for this upgrade, AH1-341 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AH1-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
ELECT JCT;1B-AF2-041 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1872.0 MVA
(All)B2112.0 MVA
(All)C2485.0 MVA
(All)STE2336.0 MVA

System Reinforcement: b3811.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3811.1 / CE_PJM B3811_L11323
Title
Expand Haumesser Road 138 kV substation as a 4 circuit breaker ring bus.
Description
Expand Haumesser Road 138 kV substation as a 4 circuit breaker ring bus.
Cost Information
Time Estimate
Dec 01 2028

Contingent

Note: Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 may need this upgrade in-service to be deliverable to the PJM system. If AH1-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA438.0 MVA
LLALDR677.0 MVA
LLB528.0 MVA
LLC589.0 MVA
LLSTE542.0 MVA
SUMA376.0 MVA
SUMALDR618.0 MVA
SUMB483.0 MVA
SUMC538.0 MVA
SUMSTE495.0 MVA
WINA452.0 MVA
WINALDR691.0 MVA
WINB538.0 MVA
WINC601.0 MVA
WINSTE553.0 MVA
WATERMAN ; R-W DEKALB ;3T 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA438.0 MVA
LLALDR677.0 MVA
LLB528.0 MVA
LLC589.0 MVA
LLSTE542.0 MVA
SUMA376.0 MVA
SUMALDR618.0 MVA
SUMB483.0 MVA
SUMC538.0 MVA
SUMSTE495.0 MVA
WINA452.0 MVA
WINALDR691.0 MVA
WINB538.0 MVA
WINC601.0 MVA
WINSTE553.0 MVA

System Reinforcement: b3811.2
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3811.2 / CE_PJM B3811_L11323
Title
Additional Circuit Breaker at ESS H452
Description
Add one 138 kV circuit breaker at H-452 to complete a three circuit breaker ring bus.
Cost Information
Time Estimate
Dec 01 2028

Contingent

Note: Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 may need this upgrade in-service to be deliverable to the PJM system. If AH1-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA438.0 MVA
LLALDR677.0 MVA
LLB528.0 MVA
LLC589.0 MVA
LLSTE542.0 MVA
SUMA376.0 MVA
SUMALDR618.0 MVA
SUMB483.0 MVA
SUMC538.0 MVA
SUMSTE495.0 MVA
WINA452.0 MVA
WINALDR691.0 MVA
WINB538.0 MVA
WINC601.0 MVA
WINSTE553.0 MVA
WATERMAN ; R-W DEKALB ;3T 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA438.0 MVA
LLALDR677.0 MVA
LLB528.0 MVA
LLC589.0 MVA
LLSTE542.0 MVA
SUMA376.0 MVA
SUMALDR618.0 MVA
SUMB483.0 MVA
SUMC538.0 MVA
SUMSTE495.0 MVA
WINA452.0 MVA
WINALDR691.0 MVA
WINB538.0 MVA
WINC601.0 MVA
WINSTE553.0 MVA

System Reinforcement: b3811.3
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3811.3 / CE_PJM B3811_L11323
Title
Rebuild 3 miles of 138 kV line 11323 from Haumesser Road to the H-452 tap
Description
Rebuild 3 miles of 138 kV line 11323 from Haumesser Road to the H-452 tap with double circuit towers. Cut the H-452 tap over to the 2nd circuit from Haumesser Road. Both circuits to use twisted pair 556 ACSR Parakeet conductor.
Cost Information
Time Estimate
Dec 01 2028

Contingent

Note: Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 may need this upgrade in-service to be deliverable to the PJM system. If AH1-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
HAUMESSER; B-W DEKALB ;3T 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA438.0 MVA
LLALDR677.0 MVA
LLB528.0 MVA
LLC589.0 MVA
LLSTE542.0 MVA
SUMA376.0 MVA
SUMALDR618.0 MVA
SUMB483.0 MVA
SUMC538.0 MVA
SUMSTE495.0 MVA
WINA452.0 MVA
WINALDR691.0 MVA
WINB538.0 MVA
WINC601.0 MVA
WINSTE553.0 MVA
WATERMAN ; R-W DEKALB ;3T 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA438.0 MVA
LLALDR677.0 MVA
LLB528.0 MVA
LLC589.0 MVA
LLSTE542.0 MVA
SUMA376.0 MVA
SUMALDR618.0 MVA
SUMB483.0 MVA
SUMC538.0 MVA
SUMSTE495.0 MVA
WINA452.0 MVA
WINALDR691.0 MVA
WINB538.0 MVA
WINC601.0 MVA
WINSTE553.0 MVA

System Reinforcement: n9165.0
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n9165.0 / CE_NUN_L15502.1
Title
Perform TSS 155 Nelson Substation conductor upgrades.
Description
• Update relay settings at 345kV substation TSS 155 Nelson to support upgrade of 345kV L.15502. • Replace the cables between the 345kV BT2-3 circuit breaker and the adjacent 345kV MODs on Bus 2 and Bus 3 with cables that have a minimum rating of 1966 MVA SSTE. • Upgrade TSS 155 Nelson by upgrading existing 345kV L.15502 disconnect switch and 345kV Bus 4 disconnect switches.
Total Cost ($USD)
$1,220,445
Discounted Total Cost ($USD)
$1,220,445
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
NELSON ; B-AF2-041 TP 345.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1679.0 MVA
LLALDR2622.0 MVA
LLSTE2107.0 MVA
SUMA1679.0 MVA
SUMALDR2622.0 MVA
SUMB2058.0 MVA
SUMC2280.0 MVA
SUMSTE2107.0 MVA

System Reinforcement: n6611
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n6611 / ce-007
Title
The upgrades will be to reconductor the line, station conductor upgrades.
Description
L11301 SLD = 331 MVA& ALDR = 381 MVA. The post contingency flow for this event exceeds the rating therefore upgrades are required. The upgrades will be to reconductor the line, station conductor upgrades. Potential transmission tower replacement required with line reconductor. The estimate for this work will not be known until the Phase 3 system upgrade Facility Study is completed per the PJM process.A preliminary estimate is $ 13.1 M with a estimated construction time of 30 months. Upon completion the ratings will be 292/321/367/433/498 MVA SN/SLTE/SSTE/SLD/ALDR).
Total Cost ($USD)
$13,100,000
Discounted Total Cost ($USD)
$13,100,000
Allocated Cost ($USD)
$0
Time Estimate
30 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 may need this upgrade in-service to be deliverable to the PJM system. If AH1-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
SANDWICH ; R-WATERMAN ; R 138.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A311.0 MVA
(All)ALDR572.0 MVA
(All)B338.0 MVA
(All)C485.0 MVA
(All)STE503.0 MVA
LLALDR625.0 MVA
LLSTE503.0 MVA
SUMALDR572.0 MVA

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / (Pending)
Title
WILTON ; 765.0 kV to 05DUMONT_RW 765.0 kV ckt 1 - AEP End Ratings
Description
Limited by non-AEP equipment, AEP End ratings: 5496.0, 6143.0, 6328.0
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 12 Months

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A5496.0 MVA
(All)B6143.0 MVA

System Reinforcement: s3011
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
s3011 / CE_S3011
Title
Replace 345kV straight bus at TSS 116 Goodings Grove with a gas insulated switchgear ("GIS") breaker and a half configuration.
Description
Replace 345 kV open air straight bus with GIS in a breaker and half configuration (34 Circuit Breakers) at Goodings Grove with 80kA capability.
Cost Information
Time Estimate
Dec 31 2029

ContingentTopology Changing

Note 1: Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 may need this upgrade in-service to be deliverable to the PJM system. If AH1-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
(Any)COMED_P4_116-45-TR82____SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4_116-45-L11614__SRT-A
No new ratings for this Flowgate.
(Any)COMED_P4-6_116-345-R______SRT-A
No new ratings for this Flowgate.
(Any)COMED_P2-2_116_GG-345R__2_SRT-A
No new ratings for this Flowgate.

System Reinforcement: n9718.0
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n9718.0 / CE_NUN_COLLINS_NEW CB
Title
New Collins New 765KV Circuit Breaker
Description
At Station 23 Collins, install 2-765kV circuit breakers and relocation of 765kV L2315 termination from Bus 3 to proposed Bus 6.
Total Cost ($USD)
$15,500,000
Discounted Total Cost ($USD)
$15,500,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-341 could receive cost allocation. Although AH1-341 may not presently have cost responsibility for this upgrade, AH1-341 is a potential Aggregate Pool Contributor.

FacilityContingency
(Any)COMED_P4_023-65-BT2-3___SRT-A
No new ratings for this Flowgate.
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-341


AH1-341 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowComEds3011 / CE_S3011Replace 345kV straight bus at TSS 116 Goodings Grove with a gas insulated switchgear ("GIS") breaker and a half configuration.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-341 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-341 One Line Diagram

AH1-341 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.