AH1-387 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:20

Meadowbrook-Greenland Gap 500kV

22.05 MW Capacity / 150.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is CPV Springs Wind, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is The Potomac Edison Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $37,756,968 $32,396,358 = 1.17 AND ( $37,756,968 - $32,396,358 ) 150.0 = $35,737 per MW

General

The Project Developer has proposed a Wind generating facility located in the The Potomac Edison Company zone — Hampshire County, West Virginia. The installed facilities will have a total capability of 150.0 MW with 22.05 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-387
Project Name:
Meadowbrook-Greenland Gap 500kV
Project Developer Name:
CPV Springs Wind, LLC
State:
West Virginia
County:
Hampshire
Transmission Owner:
The Potomac Edison Company
MFO:
150.0
MWE:
150.0
MWC:
22.05
Fuel Type:
Wind
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-387 will interconnect on the The Potomac Edison Company transmission system by tapping the Greenland Gap - Meadow Brook 500 kV line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-387 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-387Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$3,129,272$0$0
Other Scope$987,463$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$29,407,943$29,407,943$29,407,943
Network Upgrades$8,349,025$8,349,025$8,349,025
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$41,873,703$37,756,968$37,756,968

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-387

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-387
Project ID: AH1-387
20% of cost allocation for Phase II Network Upgrades:(A) $7,551,394
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $3,239,636
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $4,311,758
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Cut the existing Meadow Brook - Greenland Gap 500 kV line and loop in the new interconnection substation.

$3,198,019$3,176,720$170,135$110,594$6,655,468$6,655,468
(Pending)

Revise relay settings at Greenland Gap substation as required.

$723,698$59,371$63,830$2,583$849,482$849,482
(Pending)

Install new backup wave traps and line tuners at Meadow Brook Substation. Include additional UPLC and PCM-350 relay panel and wiring to convert to a PR DCUB and BU DCUB.

$743,702$59,371$39,565$1,437$844,075$844,075
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Provide revenue metering panel within new AH1-387 control house. Integrate revenue metering to interconnection substation. Provide new 3-phase 500 kV free-standing CT/VT combo units.

$404,203$548,483$21,504$13,273$987,463$987,463
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install/test 96F/SM ADSS cable from the AH1-387 substation control house to the Greenland Gap-Meadow Brook 500 kV line.

$2,349,790$300,389$125,009$7,269$2,782,457$2,782,457
(Pending)

Construct a new 500 kV three (3) breaker ring bus interconnection substation.

$15,074,084$9,964,636$801,941$241,985$26,082,646$26,082,646
(Pending)

Run fiber from AH1-387 substation control house to the Point of Change in Ownership.

$48,874$2,378$2,600$58$53,910$53,910
(Pending)

Design, install, and test/commission MPLS equipment for SCADA transport at new AH1-387 substation.

$350,700$116,748$18,657$2,825$488,930$488,930
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install line terminal equipment within the AH1-387 interconnection substation. Install one (1) span from AH1-387 interconnection substation to the Project Developer-owned dead-end structure outside of TO substation fence.

$1,783,978$1,156,005$94,908$35,148$3,070,039$3,070,039
(Pending)

Integrate interconnection facilities protection and controls to the Transmission Owner system.

$56,241$0$2,992$0$59,233$59,233
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Cut the existing Meadow Brook - Greenland Gap 500 kV line and loop in the new interconnection substation.

$3,198,019$3,176,720$170,135$110,594$6,655,468$6,655,468
(Pending)

Revise relay settings at Greenland Gap substation as required.

$723,698$59,371$63,830$2,583$849,482$849,482
(Pending)

Install new backup wave traps and line tuners at Meadow Brook Substation. Include additional UPLC and PCM-350 relay panel and wiring to convert to a PR DCUB and BU DCUB.

$743,702$59,371$39,565$1,437$844,075$844,075
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Oversight of Project Developer design and construction of new interconnection substation.

$1,299,010$0$69,107$0$1,368,117$1,368,117
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Provide revenue metering panel within new AH1-387 control house. Integrate revenue metering to interconnection substation. Provide new 3-phase 500 kV free-standing CT/VT combo units.

$404,203$548,483$21,504$13,273$987,463$987,463
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install/test 96F/SM ADSS cable from the AH1-387 substation control house to the Greenland Gap-Meadow Brook 500 kV line.

$2,349,790$300,389$125,009$7,269$2,782,457$2,782,457
(Pending)

Install one (1) security system and camera system. Install one (1) indoor security AC cabinet. Install one (1) network fiber termination rack.

$1,885,311$349,062$100,299$8,447$2,343,119$2,343,119
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Integrate interconnection facilities protection and controls to the Transmission Owner system.

$56,241$0$2,992$0$59,233$59,233
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$41,873,703$41,873,703
Developer Build Option$15,889,414$15,889,414

Based on the scope of work for the Interconnection Facilities, it is expected to take 41 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

FE performed an analysis of its underlying transmission system <100 kV. New Service Request Project AH1-387 did not contribute to any overloads on the FE transmission <100 kV system.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The wind generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Wind speed (meters/second) - (Required)
  • Wind direction (decimal degrees from true north) - (Required)
  • Ambient air temperature (Fahrenheit) - (Required)
  • Air Pressure (Hectopascals) - (Required)
  • Humidity (Percent) - (Accepted, not required)
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-387 was evaluated as a 150.0 MW (22.05 MW Capacity) injection in the APS area.

AH1-387 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC132.6 %1417.0B1878.9
3.87
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC131.8 %1331.98B1755.6
1.23
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC121.4 %1417.0B1720.2
4.56
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC121.88 %1478.62B1802.21
1.23
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC106.46 %1809.0C1925.78
3.87
GD2DVP
8FRONT ROYAL-8MORRSVL 500.0 kV Ckt 1 line
AP_P1-2_PE-500-404T_SRT-A
SingleAC100.67 %3220.44B3241.91
6.62

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.6 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1878.9
MW Contribution:
3.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
Adder
0.11
3144293JTRSVLE
Adder
0.139
3144293JTRSVLE
Adder
0.139
3144293JTRSVLE
Adder
0.139
3147043LAWRENC
Solar/Wind Harmer
-0.004
3147043LAWRENC
Adder
0.529
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3147133PAMPLIN
Solar/Wind Harmer
-0.007
20390526W1-045 C
Solar/Wind Helper
0.278
20671828STAW2-080
Solar/Wind Helper
0.015
20671928W4-073
Solar/Wind Helper
0.051
20673628F1S_V4-069
Solar/Wind Helper
0.017
20673728F2S_V4-070
Solar/Wind Helper
0.017
20673828FLE_V3-070
Solar/Wind Helper
0.05
20674128FR_U2-059
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20674628WNG_W3-110
Solar/Wind Helper
0.051
20674828DL_W4-046
Solar/Wind Helper
0.005
20674928WA_W3-044
Solar/Wind Helper
0.056
20675128HRM_W1-127
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
20675528CPH_W2-050
Solar/Wind Helper
0.065
20675728RH_W2-091
Solar/Wind Helper
0.047
20675828AU_W4-064
Solar/Wind Helper
0.017
20675928HOL_W4-097
Solar/Wind Helper
0.029
20676128MHD_W3-029
Solar/Wind Helper
0.055
20676228FRD_X1-012
Solar/Wind Helper
0.052
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20676428JCR_X2-075
Solar/Wind Helper
0.039
20676728BRNX1-095
Solar/Wind Helper
0.017
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
20714928UPF_X1-085
Solar/Wind Helper
0.003
20715028HAN_X4-015
Solar/Wind Helper
0.033
20715228NPK_W1-113
Solar/Wind Helper
0.045
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
20716028EGP_W2-019
Solar/Wind Helper
0.011
20716928W4-060COL
Solar/Wind Helper
0.03
20720528MAN_W1-024
Solar/Wind Helper
0.016
20720628TIN_W1-124
Solar/Wind Helper
0.11
20720728JCB_W1-129
Solar/Wind Helper
0.033
20720828JCB_W4-025
Solar/Wind Helper
0.037
207408W3-077 C
Solar/Wind Helper
0.048
207439AE1-081 C O1
Solar/Wind Helper
0.011
214067T20SOLAR
Solar/Wind Helper
0.007
217206BARNGR HS C
Solar/Wind Helper
0.004
217208PARK ELE C
Solar/Wind Helper
0.003
217209CENTRL HS C
Solar/Wind Helper
0.005
217211CAMDEN ST C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.017
232404W1-003 C
Solar/Wind Helper
0.306
232408W1-005 C
Solar/Wind Helper
0.306
232410W1-006 C
Solar/Wind Helper
0.306
232417X3-008 C
Solar/Wind Helper
0.14
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.204
23777801MSM_W1-116
Solar/Wind Helper
0.157
23777901MDS_W4-102
Solar/Wind Helper
0.113
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3141346CRANES
Adder
0.082
3141426STAFORD
Solar/Wind Harmer
-0.002
3141843SHACKLE
Adder
0.329
3141906WESTMOR
Solar/Wind Harmer
-0.003
3142296MT RD221
Adder
0.206
3142366NRTHEST
Adder
0.211
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
0.733
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142956BIRDNECK
Solar/Wind Harmer
0.377
3143096IRON208
Adder
0.264
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.27
3143316POE
Solar/Wind Harmer
-0.028
3143336POWHATN
Solar/Wind Harmer
0.84
3143336POWHATN
Solar/Wind Harmer
0.714
3144216WINCHST
Adder
0.239
3144356SAPONY
Solar/Wind Harmer
0.241
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3146396TANGLEW
Solar/Wind Harmer
0.128
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3146776BUCKING
Solar/Wind Harmer
-0.002
3146776BUCKING
Solar/Wind Harmer
-0.003
3150071POSSM 5
Adder
32.531
3150151POSSMC1
Adder
0.712
3150151POSSMC1
Adder
0.712
3150151POSSMC1
Adder
0.712
3150181POSSMC2
Adder
0.712
3150181POSSMC2
Adder
0.712
3150181POSSMC2
Adder
0.718
3150211REMNGT1
Adder
10.853
3150221REMNGT2
Adder
10.925
3150241REMNGT4
Adder
10.998
3150281M RUN A
Adder
11.691
3150291M RUN B
Adder
11.597
3150301M RUN C
Adder
11.683
3150331BIRCHWDA
Adder
11.656
3150341NORNECKC1
Adder
0.678
3150341NORNECKC1
Adder
0.683
3150351NORNECKC2
Adder
0.661
3150351NORNECKC2
Adder
0.65
3150391LDYSMT3
Adder
9.161
3150401LDYSMT4
Adder
9.178
3150411LDYSMT5
Adder
9.207
3150671DARBY 1
Adder
4.621
3150681DARBY 2
Adder
4.627
3150691DARBY 3
Adder
4.643
3150701DARBY 4
Adder
4.632
3150921YORKTN3
Adder
1.594
209027LOR2_Q27
Solar/Wind Helper
0.551
212266LOR1
Solar/Wind Helper
0.16
217081WEATEXAS C
Solar/Wind Helper
0.007
217169METRODIV C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217202FBANKSOLAR C
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
218438BLK ROCK C
Solar/Wind Helper
0.016
218440SUMMTASSOC C
Solar/Wind Helper
0.009
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219249CENTRALDIV C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219276PARKLANDSO C
Solar/Wind Helper
0.052
219291REEVESSOUT C
Solar/Wind Helper
0.007
219348LDSOLAR C
Solar/Wind Helper
0.067
219607WPEMNERT C
Solar/Wind Helper
0.047
219612MATRIX C
Solar/Wind Helper
0.014
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
235020AA1-095 C
Solar/Wind Helper
0.031
3150981CHESPKA
Adder
0.782
3150991CHESPKB
Adder
0.641
3150991CHESPKB
Adder
0.656
3151081ELIZAR1
Adder
5.744
3151091ELIZAR2
Adder
5.644
3151101ELIZAR3
Adder
5.817
3151171GRAVELC
Adder
0.672
3151171GRAVELC
Adder
0.883
3151191GRAVEL3
Adder
4.537
3151201GRAVEL4
Adder
4.595
3151211GRAVEL5
Adder
4.537
3151221GRAVEL6
Adder
4.59
3151731LOISA B
Adder
4.646
3151751LOISA D
Adder
4.646
3151761LOISA E
Adder
9.471
3152111X4-039 GT1
50/50
1.834
3152121X4-039 GT2
50/50
1.822
3152131X4-039 ST
50/50
2.868
316075AC2-137 C
Solar/Wind Harmer
0.195
316077AC2-138 C
Solar/Wind Harmer
0.154
228728W1-130C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Harmer
-0.002
3138133OCRAN
Solar/Wind Harmer
-0.004
3138283WHITEMARSH
Solar/Wind Harmer
0.011
3141766HARMONY
Solar/Wind Harmer
0.644
3141766HARMONY
Solar/Wind Harmer
-0.001
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
3141813NORNECK
Solar/Wind Harmer
-0.007
3141913WHIT STONE
Solar/Wind Harmer
-0.007
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3143873LANEXA
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
3146456SLIGO L269
Solar/Wind Harmer
0.827
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146926FARMVIL
Solar/Wind Harmer
-0.004
3147346CASHSCORNER
Solar/Wind Harmer
0.123
3147666LOUISA
Solar/Wind Harmer
-0.032
3147666LOUISA
Solar/Wind Harmer
-0.018
232406W1-004 FULL
Solar/Wind Helper
0.306
232436AB1-176 C
Solar/Wind Helper
0.027
3141726DUNNSVL
Solar/Wind Harmer
-0.029
3145663CRESWEL
Solar/Wind Harmer
-0.019
316034AC1-036 C
Solar/Wind Harmer
0.12
316036AC1-147 C
Solar/Wind Harmer
0.189
316059AD1-063 C
Solar/Wind Harmer
0.163
316159AE1-175 C
Solar/Wind Harmer
0.192
316240AF1-291 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.141
316258AE1-075 C
Solar/Wind Harmer
0.171
316305AF2-043 C
Solar/Wind Harmer
0.21
316314AB2-024 C
Solar/Wind Harmer
0.618
316315AB2-025 C
Solar/Wind Harmer
0.186
316316AC1-027 C
Solar/Wind Harmer
0.215
316317KELFORD C
Solar/Wind Harmer
0.304
316336AC2-165 C
Solar/Wind Harmer
4.383
316382AG1-145 C
Solar/Wind Harmer
0.215
316405AF2-144 C
Solar/Wind Harmer
0.181
223402AF1-300 C
Solar/Wind Helper
0.386
230415AB2-049 C
Solar/Wind Helper
0.018
20742028HF_AC1-207
Solar/Wind Helper
0.082
207454AA2-184 E
Solar/Wind Helper
0.18
207459AE1-142 C O1
Solar/Wind Helper
0.169
207471AF2-354 C
Solar/Wind Helper
0.096
208835TUHI V3-051
Solar/Wind Helper
0.017
208835TUHI V3-051
Solar/Wind Helper
0.017
232424Y1-079 C
Solar/Wind Helper
0.07
3150371LDYSMT1
Adder
8.868
3150381LDYSMT2
Adder
8.811
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
226910AB2-157 C
Solar/Wind Helper
0.014
233901CHERRYDALE C
Solar/Wind Helper
0.14
233940AF2-379 C
Solar/Wind Helper
0.037
212507AE2-042_GEN
Solar/Wind Helper
0.818
219907AC1-030 C
Solar/Wind Helper
0.02
237025AB1-124 C
Solar/Wind Helper
0.234
237030AB1-096 C
Solar/Wind Helper
0.095
237038AE2-054 C
Solar/Wind Helper
0.191
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145336SMITFLD
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.003
3141196NOKESVL
Solar/Wind Harmer
-0.043
3141873WAN 176
Solar/Wind Harmer
0.858
3141873WAN 176
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.038
3143526WINTERP
Solar/Wind Harmer
-0.038
316411AF1-147_GEN1
Solar/Wind Harmer
1.073
316415AF1-147_GEN2
Solar/Wind Harmer
1.073
316404AE1-155 C
Solar/Wind Harmer
1.394
316017AA1-139 ULT1
Solar/Wind Harmer
0.565
316018AA1-139 ULT2
Solar/Wind Harmer
0.599
316181AB2-040 GEN
Solar/Wind Harmer
0.919
316033AB2-134 GEN
Solar/Wind Harmer
2.294
228754AB1-001 C
Solar/Wind Helper
0.015
316388AE2-253 GEN
Solar/Wind Harmer
0.471
235062AE1-101 C1
Solar/Wind Helper
1.173
205956AE1-196_GEN
Solar/Wind Helper
0.407
217204WCALDSOLAR C
Solar/Wind Helper
0.002
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
3142543TWELFTH
Solar/Wind Harmer
-0.001
3144303KENBRDG
Solar/Wind Harmer
-0.005
237080AD1-060 GEN
Solar/Wind Helper
0.243
235067AD1-061 GEN
Solar/Wind Helper
0.308
237001AB1-127_GEN
Solar/Wind Helper
0.343
237002AB1-128_GEN
Solar/Wind Helper
0.332
238221AF1-254 C O1
Solar/Wind Helper
0.198
316203AE2-005 GEN
Solar/Wind Harmer
3.049
316441AF1-014 GEN
Solar/Wind Harmer
0.488
237085AD2-009_GEN
Solar/Wind Helper
1.053
233944AB2-135 GEN
Solar/Wind Helper
0.358
233946AB2-136 GEN
Solar/Wind Helper
0.343
316426AA2-053 GEN
Solar/Wind Harmer
0.662
316190AA2-174 GEN
Solar/Wind Harmer
0.081
3156081AA2-088 GEN
Solar/Wind Harmer
2.18
233994AC2-023 GEN
Solar/Wind Helper
0.58
315614AA2-178 GEN
Solar/Wind Harmer
0.729
315816AE2-034 GEN
Solar/Wind Harmer
0.546
316312AB1-027
Solar/Wind Harmer
0.244
316011AB1-132 GEN
Solar/Wind Harmer
1.372
316369SG1_INVT
Solar/Wind Harmer
1.27
315651AD1-115 GEN
Solar/Wind Harmer
3.931
316023GEN1_S
Solar/Wind Harmer
0.45
316365GEN2_N
Solar/Wind Harmer
0.45
237006AB1-125 GEN
Solar/Wind Helper
0.175
23779801AA1-109
Solar/Wind Helper
0.262
316463AE2-346 GEN
Solar/Wind Harmer
0.107
315839AE2-212 C
Solar/Wind Harmer
0.214
233982AB2-133 GEN
Solar/Wind Helper
0.218
233915AB1-141 GEN
Solar/Wind Helper
0.305
233918AB1-142 GEN
Solar/Wind Helper
0.305
315821AE2-092 GEN
Solar/Wind Harmer
1.353
315814AE2-033 C
Solar/Wind Harmer
6.429
315671AE2-027_GEN
Solar/Wind Harmer
1.289
315747AE2-019 GEN
50/50
12.529
233930AB2-032 GEN
Solar/Wind Helper
0.231
233987AB2-037 GEN
Solar/Wind Helper
1.415
315662AE1-191 GEN
Solar/Wind Harmer
0.87
315666AE1-190 GEN
Solar/Wind Harmer
0.217
315673AE1-157 GEN
Solar/Wind Harmer
5.701
315813AE1-149 C
Solar/Wind Harmer
4.424
315683AE1-153 C
Solar/Wind Harmer
8.072
315742AE1-103 GEN
Solar/Wind Harmer
1.629
319010AE1-072 C
Solar/Wind Harmer
1.412
316065AD1-022 GEN
Solar/Wind Harmer
3.346
315697AD1-025 GEN
Solar/Wind Harmer
1.438
316185AD1-033 GEN
Solar/Wind Harmer
0.74
233933AB2-153 GEN
Solar/Wind Helper
0.141
315773AC2-141 GEN
Solar/Wind Harmer
2.954
316280AD1-041 GEN
Solar/Wind Harmer
0.544
233935AB2-179 C
Solar/Wind Helper
0.776
315732AD1-074 GEN1
Solar/Wind Harmer
1.354
315733AD1-074 GEN2
Solar/Wind Harmer
1.354
315735AD1-075 GEN1
Solar/Wind Harmer
0.677
315737AD1-076 GEN
Solar/Wind Harmer
1.273
316473AC1-191 GEN
Solar/Wind Harmer
0.787
316478AD1-087 GEN
Solar/Wind Harmer
0.565
316486AD2-202 GEN
Solar/Wind Harmer
0.166
316447AC1-158 HLD
Solar/Wind Harmer
1.872
316044AC1-158 PL1
Solar/Wind Harmer
0.851
316045AC1-158 PL2
Solar/Wind Harmer
2.723
316450AC1-158 RIC
Solar/Wind Harmer
0.227
316468AD1-105 GEN
Solar/Wind Harmer
0.85
316072AD1-144
Solar/Wind Harmer
0.142
315778AD1-151 GEN
Solar/Wind Harmer
6.347
316156AD2-030 GEN
Solar/Wind Harmer
0.193
316337AD2-073 GEN
Solar/Wind Harmer
0.198
234015AF2-250 C
Solar/Wind Helper
0.023
234036AF2-325 C
Solar/Wind Helper
0.026
207484AF2-139 C O1
Solar/Wind Helper
0.048
207510AF2-138 C
Solar/Wind Helper
0.046
207518AF1-320_GEN
Solar/Wind Helper
0.895
207442AE1-156 GEN
Solar/Wind Helper
0.188
226929AD2-058 GEN
Solar/Wind Helper
0.079
207437AD2-070 GEN
Solar/Wind Helper
0.079
209054AE2-059 GEN
Solar/Wind Helper
0.042
313526AB2-022
Solar/Wind Harmer
0.187
316313AB2-026
Solar/Wind Harmer
0.19
207445AB1-138_GEN
Solar/Wind Helper
0.061
209071AE2-133 GEN
Solar/Wind Helper
0.042
209116AE2-175 GEN
Solar/Wind Helper
0.998
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145513AHOSKIE
Solar/Wind Harmer
0.058
233923SMA
Solar/Wind Helper
0.454
230433AD2-135 GEN
Solar/Wind Helper
0.01
219680HOPEWELLV C1
Solar/Wind Helper
0.002
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219908AB1-139 C
Solar/Wind Helper
0.043
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219304NAMERICA C
Solar/Wind Helper
0.077
219921AF1-264
Solar/Wind Helper
0.03
203975AE1-071-GEN
Solar/Wind Helper
1.876
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
207530AG1-191 GEN
Solar/Wind Helper
0.038
230511AF1-262
Solar/Wind Helper
0.009
205932AD2-116_GEN
Solar/Wind Helper
0.407
205941AD2-115 GEN
Solar/Wind Helper
0.303
205943AE1-185 GEN
Solar/Wind Helper
0.41
205917AD1-020 ES
Solar/Wind Helper
0.358
205916AD1-020 GEN
Solar/Wind Helper
1.663
3147623JAMES R
Solar/Wind Harmer
0.103
209067AE2-060 GEN
Solar/Wind Helper
0.042
209137AF2-361 C
Solar/Wind Helper
0.706
3146206CASHIE
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316349AD2-085 GEN
Solar/Wind Harmer
0.622
3156021HOLLOMANSOL
Solar/Wind Harmer
0.892
315652AC1-086 GEN
Solar/Wind Harmer
7.388
313506AB2-031 GEN
Solar/Wind Harmer
0.529
316006AB2-029 C
Solar/Wind Harmer
0.548
316322AB2-045
Solar/Wind Harmer
0.225
316192AB2-158 GEN
Solar/Wind Harmer
0.957
316083AB2-161 GEN
Solar/Wind Harmer
1.144
316174AB2-169 GEN
Solar/Wind Harmer
1.007
316087AB2-174 GEN
Solar/Wind Harmer
0.941
316132AB2-190 GEN1
Solar/Wind Harmer
0.72
316458AB2-190 GEN2
Solar/Wind Harmer
0.72
316254AC1-120 GEN1
Solar/Wind Harmer
3.304
316170AC1-121 GEN2
Solar/Wind Harmer
1.101
316375AC2-012 GEN
Solar/Wind Harmer
2.434
316311AC2-079 GEN
Solar/Wind Harmer
3.535
316339AD2-160 GEN
Solar/Wind Harmer
0.471
316164AC1-076 GEN
Solar/Wind Harmer
0.727
316140AB2-099
Solar/Wind Harmer
0.045
316223AC1-118
Solar/Wind Harmer
0.2
316294AC1-161 GEN
Solar/Wind Harmer
2.283
315975AC1-164 GENB
Solar/Wind Harmer
0.049
315976AC1-164 GENA
Solar/Wind Harmer
1.643
316169AC1-164_GENC
Solar/Wind Harmer
1.419
316381AD1-082 GEN
Solar/Wind Harmer
0.645
316233AE1-074 FULL
Solar/Wind Harmer
0.196
316236AE1-162_GEN
Solar/Wind Harmer
0.213
316093AE2-104_GEN
Solar/Wind Harmer
2.03
315607AA1-063A GEN
Solar/Wind Harmer
0.667
3150851SPRUNCC
Adder
0.297
3150861SPRUNCD
Adder
0.297
230434AG1-499 GEN
Solar/Wind Helper
0.136
233964AF2-378 GEN
Solar/Wind Helper
0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.054
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
207511W3-106 GEN
Solar/Wind Helper
0.015
208972BECR K09
Solar/Wind Helper
0.176
209029WAYMART-WD
Solar/Wind Helper
0.438
223401AF1-299 GEN
Solar/Wind Helper
0.386
230407AD2-065 C
Solar/Wind Helper
0.024
232432Z2-076 GEN
Solar/Wind Helper
0.04
232434Z2-077 GEN
Solar/Wind Helper
0.076
233996TM1833_GEN
Solar/Wind Helper
0.124
233997TMININ_4.2
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138126ROCKLANDING
Solar/Wind Harmer
0.022
3138216PACIFIC
Solar/Wind Harmer
-0.003
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3142946ENON
Solar/Wind Harmer
-0.001
3142946ENON
Solar/Wind Harmer
-0.002
3144536CHRHLND
Solar/Wind Harmer
-0.001
3144873MCLAUGH
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
-0.007
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.621
3145783HORNRTN
Solar/Wind Harmer
0.194
3145783HORNRTN
Solar/Wind Harmer
0.078
3145796HORNRTN
Solar/Wind Harmer
-0.019
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3145823KELFORD
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.186
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
0.198
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.026
3146043SEABORD
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.693
315800Z1-036_GEN1
Solar/Wind Harmer
1.693
316318V4-068
Solar/Wind Harmer
0.166
316320Y1-086
Solar/Wind Harmer
0.408
316321Z2-027
Solar/Wind Harmer
0.187
942461AE2-259 GEN
Solar/Wind Harmer
0.995
944011AF1-069 GEN
Solar/Wind Harmer
4.06
944491AF1-114 GEN
Solar/Wind Harmer
2.202
944581AF1-123 GEN
Solar/Wind Harmer
32.014
944591AF1-124 GEN
Solar/Wind Harmer
32.129
944601AF1-125 GEN
Solar/Wind Harmer
31.514
944631AF1-128 GEN
Adder
30.58
944641AF1-129 GEN
Adder
30.387
946281AF1-292 GEN
Solar/Wind Harmer
0.149
946301AF1-294 GEN
Solar/Wind Harmer
1.679
946691AF1-333 GEN
Solar/Wind Helper
0.23
946731AF1-337 GEN
Solar/Wind Helper
0.23
946741AF1-338 GEN
Solar/Wind Helper
0.23
946751AF1-339 GEN
Solar/Wind Helper
0.23
959311AF2-222 GEN
Solar/Wind Harmer
6.794
959381AF2-229 GEN
Solar/Wind Helper
0.283
959421AF2-233 GEN
Solar/Wind Helper
0.23
959431AF2-234 GEN
Solar/Wind Helper
0.459
959561AF2-247 GEN
Solar/Wind Helper
0.012
960081AF2-299 GEN
Solar/Wind Harmer
0.746
961261AF2-417 GEN
Solar/Wind Helper
0.239
961301AF2-421 GEN
Solar/Wind Helper
0.239
961331AF2-424 GEN
Solar/Wind Helper
0.234
961341AF2-425 GEN
Solar/Wind Helper
0.234
961421AF2-433 GEN
Solar/Wind Helper
0.233
961431AF2-434 GEN
Solar/Wind Helper
0.233
961611AG1-000B GEN
Solar/Wind Harmer
3.506
961611AG1-000B GEN
Solar/Wind Harmer
1.496
961791AG1-021 GEN
Solar/Wind Harmer
0.819
961941AG1-037 GEN
Solar/Wind Harmer
0.05
961951AG1-038 GEN
Solar/Wind Harmer
0.96
962571AG1-106 GEN
Solar/Wind Harmer
0.944
962861AG1-135 GEN
Solar/Wind Harmer
2.737
963151AG1-164 GEN
Solar/Wind Helper
0.239
963161AG1-165 GEN
Solar/Wind Helper
0.239
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
966881AG1-559 GEN
Solar/Wind Harmer
0.227
966881AG1-559 GEN
Solar/Wind Harmer
0.078
970053AG2-049 GEN
Adder
1.473
970085AG2-068 GEN
Solar/Wind Harmer
4.162
970087AG2-069 GEN
Solar/Wind Harmer
6.243
970099AG2-077 GEN
Solar/Wind Harmer
8.303
970133AG2-095 GEN
Solar/Wind Harmer
0.806
970221AG2-151 GEN
Solar/Wind Harmer
4.15
970257AG2-171 GEN
Solar/Wind Harmer
0.153
970293AG2-193 GEN
Solar/Wind Harmer
0.906
970301AG2-198 GEN
Solar/Wind Harmer
3.329
970323AG2-213 GEN
Solar/Wind Harmer
3.251
970533AG2-339 GEN
Solar/Wind Harmer
4.647
970581AG2-369 GEN
Solar/Wind Harmer
3.579
970601AG2-382 GEN
Solar/Wind Harmer
2.923
970657AG2-426 GEN
Solar/Wind Harmer
1.423
970657AG2-426 GEN
Solar/Wind Harmer
0.444
970673AG2-436 GEN
Solar/Wind Harmer
15.054
970681AG2-440 GEN
Solar/Wind Harmer
3.06
970683AG2-441 GEN
Solar/Wind Harmer
4.61
970685AG2-442 GEN
Solar/Wind Harmer
5.722
970917AG2-570 GEN
Solar/Wind Harmer
16.739
970919AG2-571 GEN
Solar/Wind Harmer
2.119
970933AG2-581 GEN
Solar/Wind Harmer
6.362
970937AG2-583 GEN
Solar/Wind Harmer
4.944
971069AG2-661 GEN
Solar/Wind Harmer
1.128
971153AH1-033 GEN
Solar/Wind Harmer
0.81
971163AH1-040 GEN
Solar/Wind Harmer
6.349
971223AH1-071 GEN
Solar/Wind Harmer
0.911
971281AH1-106 GEN
Solar/Wind Harmer
1.182
971283AH1-107 GEN
Solar/Wind Harmer
1.182
971285AH1-108 GEN
Adder
0.486
971317AH1-138 GEN
Solar/Wind Harmer
0.894
971377AH1-170 GEN
Solar/Wind Harmer
0.83
971445AH1-216 GEN
Solar/Wind Harmer
4.378
971455AH1-223 GEN
Solar/Wind Harmer
2.258
971547AH1-271 GEN
Solar/Wind Harmer
1.67
971563AH1-280 GEN
Solar/Wind Harmer
0.819
971685AH1-345 GEN
Solar/Wind Harmer
0.836
219918AC2-009 C
Solar/Wind Helper
0.001
227287AC2-120 GEN
Solar/Wind Helper
0.31
316431W1029_GEN1
Solar/Wind Harmer
1.256
316433W1029_GEN2
Solar/Wind Harmer
1.256
316435W1029_GEN3
Solar/Wind Harmer
1.256
939411AE1-173 GEN
Solar/Wind Harmer
35.115
940641AE2-051 GEN
Solar/Wind Harmer
6.583
941031AE2-094 GEN
Solar/Wind Harmer
12.958
957481AF2-042 GEN
Solar/Wind Harmer
20.758
957601AF2-054 GEN
Solar/Wind Harmer
0.216
957831AF2-077 GEN
Solar/Wind Harmer
0.216
957871AF2-081 GEN
Solar/Wind Harmer
3.504
957921AF2-086 GEN
Solar/Wind Helper
0.231
957971AF2-091 GEN
Solar/Wind Harmer
0.749
958211AF2-115 GEN
Solar/Wind Harmer
1.024
958261AF2-120 GEN
Solar/Wind Harmer
2.829
963691AG1-221 GEN
Solar/Wind Harmer
2.258
963711AG1-223 GEN
Solar/Wind Helper
0.037
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
964211AG1-282 GEN
Solar/Wind Harmer
0.22
964851AG1-348 GEN
Solar/Wind Helper
0.036
966001AG1-469 GEN
Solar/Wind Harmer
0.153
966621AG1-532 GEN
Solar/Wind Harmer
0.135
971761AH1-387 GEN
Solar/Wind Harmer
3.866
971777AH1-397 GEN
Solar/Wind Harmer
0.844
971781AH1-399 GEN
Solar/Wind Harmer
0.458
971845AH1-439 GEN
Solar/Wind Harmer
3.565
971967AH1-528 GEN
Solar/Wind Harmer
12.837
972003AH1-546 GEN
Solar/Wind Harmer
2.743
972135AH1-637 GEN
Solar/Wind Harmer
0.749
972185AH1-677 GEN
Adder
3.415
972187AH1-678 GEN
Adder
1.725
972189AH1-679 GEN
Adder
1.102
972193AH1-681 GEN
Adder
1.345
972195AH1-682 GEN
Adder
1.204
972197AH1-683 GEN
Adder
1.433
972199AH1-684 GEN
Adder
1.667
972201AH1-685 GEN
Adder
1.885
972205AH1-687 GEN
Adder
2.57
972213AH1-691 GEN
Adder
1.49
972215AH1-692 GEN
Adder
1.49
972217AH1-693 GEN
Adder
1.45
972219AH1-694 GEN
Adder
1.032
972223AH1-696 GEN
Adder
5.622
972255AH1-712 GEN
Adder
30.111
972277AH1-723 GEN
Adder
35.088
233950AC2-186 GEN
Solar/Wind Helper
0.07
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
315835AF2-110_GEN
Solar/Wind Harmer
0.873
232422X3-066 FULL
Solar/Wind Helper
0.069
315693AD1-088 GEN
Solar/Wind Harmer
3.317
316487AF1-042 GEN
Solar/Wind Harmer
0.96
315833AF1-017_GEN
Solar/Wind Harmer
1.331
316484AD2-074 GEN
Solar/Wind Harmer
1.834
219919AE1-041 FULL
Solar/Wind Helper
0.002
219912AD2-042 GEN
Solar/Wind Helper
0.089
219914AD2-027 C
Solar/Wind Helper
0.068
235063AE1-101 C2
Solar/Wind Helper
1.173
3151721LOISA A
Adder
4.622
NYPJM->LTFIMP_NY
CLTF
2.537
LGEELTFEXP_LGEE->PJM
CLTF
1.748
WECLTFEXP_WEC->PJM
CLTF
0.938
CPLELTFEXP_CPLE->PJM
CLTF
4.221
LAGNLTFEXP_LAGN->PJM
CLTF
5.819
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.807
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.589
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.743
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.752
TVALTFEXP_TVA->PJM
CLTF
2.93
MECLTFEXP_MEC->PJM
CLTF
4.279
SIGELTFEXP_SIGE->PJM
CLTF
0.135

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.8 %
Rating:1331.98 MVA
Rating Type:B
MVA to Mitigate:1755.6
MW Contribution:
1.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
Adder
0.136
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.172
3147043LAWRENC
Solar/Wind Harmer
0.044
3147043LAWRENC
Adder
0.663
3147133PAMPLIN
Solar/Wind Harmer
0.226
3147133PAMPLIN
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
0.072
20390526W1-045 C
Solar/Wind Helper
0.253
20671828STAW2-080
Solar/Wind Helper
0.015
20671928W4-073
Solar/Wind Helper
0.052
20673628F1S_V4-069
Solar/Wind Helper
0.017
20673728F2S_V4-070
Solar/Wind Helper
0.017
20673828FLE_V3-070
Solar/Wind Helper
0.05
20674128FR_U2-059
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20674628WNG_W3-110
Solar/Wind Helper
0.051
20674828DL_W4-046
Solar/Wind Helper
0.005
20674928WA_W3-044
Solar/Wind Helper
0.057
20675128HRM_W1-127
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
20675528CPH_W2-050
Solar/Wind Helper
0.066
20675728RH_W2-091
Solar/Wind Helper
0.047
20675828AU_W4-064
Solar/Wind Helper
0.017
20675928HOL_W4-097
Solar/Wind Helper
0.029
20676128MHD_W3-029
Solar/Wind Helper
0.056
20676228FRD_X1-012
Solar/Wind Helper
0.053
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20676428JCR_X2-075
Solar/Wind Helper
0.039
20676728BRNX1-095
Solar/Wind Helper
0.017
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
20714928UPF_X1-085
Solar/Wind Helper
0.003
20715028HAN_X4-015
Solar/Wind Helper
0.034
20715228NPK_W1-113
Solar/Wind Helper
0.046
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
20716028EGP_W2-019
Solar/Wind Helper
0.011
20716928W4-060COL
Solar/Wind Helper
0.03
20720528MAN_W1-024
Solar/Wind Helper
0.017
20720628TIN_W1-124
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.034
20720828JCB_W4-025
Solar/Wind Helper
0.037
207408W3-077 C
Solar/Wind Helper
0.048
207439AE1-081 C O1
Solar/Wind Helper
0.011
214067T20SOLAR
Solar/Wind Helper
0.007
217206BARNGR HS C
Solar/Wind Helper
0.004
217208PARK ELE C
Solar/Wind Helper
0.003
217209CENTRL HS C
Solar/Wind Helper
0.005
217211CAMDEN ST C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.017
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
232410W1-006 C
Solar/Wind Helper
0.305
232417X3-008 C
Solar/Wind Helper
0.14
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.204
23777801MSM_W1-116
Solar/Wind Helper
0.131
23777901MDS_W4-102
Solar/Wind Helper
0.106
3137176SLIGO L2192
Solar/Wind Harmer
0.318
3140676OCCOQUN
50/50
0.016
3141346CRANES
50/50
0.127
3141426STAFORD
Solar/Wind Harmer
0.023
3141843SHACKLE
Adder
0.431
3141906WESTMOR
Solar/Wind Harmer
0.036
3142296MT RD221
Adder
0.27
3142366NRTHEST
Adder
0.275
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.82
3142416OLDCHRC
Solar/Wind Harmer
0.084
3142433PROV 92
Solar/Wind Harmer
0.336
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3143096IRON208
Adder
0.344
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.351
3143316POE
Solar/Wind Harmer
0.321
3143336POWHATN
Solar/Wind Harmer
1.41
3143336POWHATN
Solar/Wind Harmer
1.198
3144216WINCHST
Adder
0.309
3144356SAPONY
Solar/Wind Harmer
0.656
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.192
3145506HICKORY
Solar/Wind Harmer
0.048
3146386ELIZ CT
Solar/Wind Harmer
0.079
3146396TANGLEW
Solar/Wind Harmer
0.218
3146776BUCKING
Solar/Wind Harmer
0.293
3146776BUCKING
Solar/Wind Harmer
0.024
3146776BUCKING
Solar/Wind Harmer
0.026
3146776BUCKING
Solar/Wind Harmer
0.029
3150071POSSM 5
50/50
52.154
3150081POSSM6A
50/50
0.849
3150091POSSM6B
50/50
0.849
3150101POSSM6S
50/50
1.293
3150151POSSMC1
50/50
1.141
3150151POSSMC1
50/50
1.141
3150151POSSMC1
50/50
1.141
3150181POSSMC2
50/50
1.141
3150181POSSMC2
50/50
1.141
3150181POSSMC2
50/50
1.151
3150211REMNGT1
50/50
13.121
3150221REMNGT2
50/50
13.208
3150231REMNGT3
50/50
0.781
3150241REMNGT4
50/50
13.296
3150281M RUN A
Adder
13.337
3150291M RUN B
Adder
13.23
3150301M RUN C
Adder
13.329
3150331BIRCHWDA
Adder
16.601
3150341NORNECKC1
Adder
0.905
3150341NORNECKC1
Adder
0.912
3150351NORNECKC2
Adder
0.883
3150351NORNECKC2
Adder
0.868
3150391LDYSMT3
Adder
12.635
3150401LDYSMT4
Adder
12.659
3150411LDYSMT5
Adder
12.698
3150671DARBY 1
Adder
6.03
3150681DARBY 2
Adder
6.037
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
3150921YORKTN3
Adder
2.065
209027LOR2_Q27
Solar/Wind Helper
0.559
212266LOR1
Solar/Wind Helper
0.163
217081WEATEXAS C
Solar/Wind Helper
0.007
217169METRODIV C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217202FBANKSOLAR C
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
218438BLK ROCK C
Solar/Wind Helper
0.016
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219249CENTRALDIV C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219276PARKLANDSO C
Solar/Wind Helper
0.052
219291REEVESSOUT C
Solar/Wind Helper
0.007
219348LDSOLAR C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
219612MATRIX C
Solar/Wind Helper
0.014
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
235020AA1-095 C
Solar/Wind Helper
0.029
3150981CHESPKA
Adder
1.005
3150991CHESPKB
Adder
0.823
3150991CHESPKB
Adder
0.843
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
3151101ELIZAR3
Adder
7.476
3151171GRAVELC
Adder
0.867
3151171GRAVELC
Adder
1.14
3151191GRAVEL3
Adder
5.855
3151201GRAVEL4
Adder
5.93
3151211GRAVEL5
Adder
5.855
3151221GRAVEL6
Adder
5.923
3151731LOISA B
Adder
5.59
3151751LOISA D
Adder
5.59
3151761LOISA E
Adder
11.397
3151861LOWMORA
Adder
0.644
3151861LOWMORA
Adder
0.618
3151881LOWMORC
Adder
0.628
3151881LOWMORC
Adder
0.639
3152111X4-039 GT1
50/50
1.844
3152121X4-039 GT2
50/50
1.832
3152131X4-039 ST
50/50
2.883
316075AC2-137 C
Solar/Wind Harmer
0.022
228728W1-130C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Harmer
0.025
3138133OCRAN
Solar/Wind Harmer
0.051
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3141766HARMONY
Solar/Wind Harmer
1.127
3141766HARMONY
Solar/Wind Harmer
0.017
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3141813NORNECK
Solar/Wind Harmer
0.087
3141913WHIT STONE
Solar/Wind Harmer
0.085
3143226MDLTHAN
Solar/Wind Harmer
0.083
3143873LANEXA
Solar/Wind Harmer
0.051
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.077
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
3146456SLIGO L269
Solar/Wind Harmer
1.414
3146456SLIGO L269
Solar/Wind Harmer
0.08
3146456SLIGO L269
Solar/Wind Harmer
0.08
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.255
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
3146926FARMVIL
Solar/Wind Harmer
0.044
3146926FARMVIL
Solar/Wind Harmer
0.044
3147346CASHSCORNER
Solar/Wind Harmer
0.196
3147666LOUISA
Solar/Wind Harmer
0.355
3147666LOUISA
Solar/Wind Harmer
0.204
3147983MERCK5
Solar/Wind Harmer
0.024
232406W1-004 FULL
Solar/Wind Helper
0.305
232436AB1-176 C
Solar/Wind Helper
0.027
3141726DUNNSVL
Solar/Wind Harmer
0.347
3145663CRESWEL
Solar/Wind Harmer
0.214
316034AC1-036 C
Solar/Wind Harmer
0.005
316036AC1-147 C
Solar/Wind Harmer
0.014
316159AE1-175 C
Solar/Wind Harmer
0.071
316246AF1-032 C
Solar/Wind Harmer
0.036
316258AE1-075 C
Solar/Wind Harmer
0.059
316315AB2-025 C
Solar/Wind Harmer
0.063
316316AC1-027 C
Solar/Wind Harmer
0.077
316336AC2-165 C
Solar/Wind Harmer
3.964
223402AF1-300 C
Solar/Wind Helper
0.398
230415AB2-049 C
Solar/Wind Helper
0.018
20742028HF_AC1-207
Solar/Wind Helper
0.082
207454AA2-184 E
Solar/Wind Helper
0.181
207459AE1-142 C O1
Solar/Wind Helper
0.17
207471AF2-354 C
Solar/Wind Helper
0.097
208835TUHI V3-051
Solar/Wind Helper
0.017
208835TUHI V3-051
Solar/Wind Helper
0.017
232424Y1-079 C
Solar/Wind Helper
0.07
3150371LDYSMT1
Adder
12.232
3150381LDYSMT2
Adder
12.153
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
226910AB2-157 C
Solar/Wind Helper
0.021
233901CHERRYDALE C
Solar/Wind Helper
0.14
233940AF2-379 C
Solar/Wind Helper
0.037
212507AE2-042_GEN
Solar/Wind Helper
0.831
219907AC1-030 C
Solar/Wind Helper
0.02
237025AB1-124 C
Solar/Wind Helper
0.194
237030AB1-096 C
Solar/Wind Helper
0.079
237038AE2-054 C
Solar/Wind Helper
0.174
3130156CHOWAN
Solar/Wind Harmer
0.077
3130156CHOWAN
Solar/Wind Harmer
0.077
3130156CHOWAN
Solar/Wind Harmer
0.077
3145336SMITFLD
Solar/Wind Harmer
0.324
3145336SMITFLD
Solar/Wind Harmer
0.032
3148133STUARTS
Solar/Wind Harmer
0.039
3141196NOKESVL
Solar/Wind Harmer
0.428
3147243WELCO
Solar/Wind Harmer
0.042
3141873WAN 176
Solar/Wind Harmer
1.502
3141873WAN 176
Solar/Wind Harmer
0.017
3143526WINTERP
Solar/Wind Harmer
0.434
3143526WINTERP
Solar/Wind Harmer
0.434
316404AE1-155 C
Solar/Wind Harmer
0
316017AA1-139 ULT1
Solar/Wind Harmer
0.043
316181AB2-040 GEN
Solar/Wind Harmer
0.105
316033AB2-134 GEN
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Helper
0.015
316388AE2-253 GEN
Solar/Wind Harmer
0.249
235062AE1-101 C1
Solar/Wind Helper
1.069
205956AE1-196_GEN
Solar/Wind Helper
0.386
217204WCALDSOLAR C
Solar/Wind Helper
0.002
3148013FISHERV
Solar/Wind Harmer
0.037
3148013FISHERV
Solar/Wind Harmer
0.065
3145176PASQUOTANK
Solar/Wind Harmer
0.049
3132123MT JACKSON
Solar/Wind Harmer
0.182
3132273ORANGE
Solar/Wind Harmer
0.018
3142543TWELFTH
Solar/Wind Harmer
0.008
3144303KENBRDG
Solar/Wind Harmer
0.057
3147173SINAI
Solar/Wind Harmer
0.067
3148463FAIRFLD
Solar/Wind Harmer
0.06
237080AD1-060 GEN
Solar/Wind Helper
0.222
235067AD1-061 GEN
Solar/Wind Helper
0.282
237001AB1-127_GEN
Solar/Wind Helper
0.308
237002AB1-128_GEN
Solar/Wind Helper
0.299
238221AF1-254 C O1
Solar/Wind Helper
0.18
316203AE2-005 GEN
Solar/Wind Harmer
0
237085AD2-009_GEN
Solar/Wind Helper
0.975
316494AC1-189 GEN
Solar/Wind Harmer
0.237
316005AA1-067
Solar/Wind Harmer
0.076
233944AB2-135 GEN
Solar/Wind Helper
0.357
233946AB2-136 GEN
Solar/Wind Helper
0.343
316426AA2-053 GEN
Solar/Wind Harmer
0.245
316327AA2-057 GEN
Solar/Wind Harmer
0.104
3156081AA2-088 GEN
Solar/Wind Harmer
0
233994AC2-023 GEN
Solar/Wind Helper
0.579
315614AA2-178 GEN
Solar/Wind Harmer
0.435
315816AE2-034 GEN
Solar/Wind Harmer
0.327
316312AB1-027
Solar/Wind Harmer
0.15
316049AB1-081 GEN
Solar/Wind Harmer
0.392
316011AB1-132 GEN
Solar/Wind Harmer
1.331
315651AD1-115 GEN
Solar/Wind Harmer
0
316023GEN1_S
Solar/Wind Harmer
0.167
316365GEN2_N
Solar/Wind Harmer
0.167
237006AB1-125 GEN
Solar/Wind Helper
0.146
23779801AA1-109
Solar/Wind Helper
0.218
316463AE2-346 GEN
Solar/Wind Harmer
0.064
233982AB2-133 GEN
Solar/Wind Helper
0.218
233915AB1-141 GEN
Solar/Wind Helper
0.305
233918AB1-142 GEN
Solar/Wind Helper
0.305
315821AE2-092 GEN
Solar/Wind Harmer
0
315814AE2-033 C
Solar/Wind Harmer
6.193
315671AE2-027_GEN
Solar/Wind Harmer
0.001
315747AE2-019 GEN
50/50
13.161
233930AB2-032 GEN
Solar/Wind Helper
0.231
233987AB2-037 GEN
Solar/Wind Helper
1.413
315673AE1-157 GEN
Solar/Wind Harmer
6.386
315813AE1-149 C
Solar/Wind Harmer
4.327
315683AE1-153 C
Solar/Wind Harmer
7.208
315742AE1-103 GEN
Solar/Wind Harmer
1.163
319010AE1-072 C
Solar/Wind Harmer
0.398
316065AD1-022 GEN
Solar/Wind Harmer
3.468
315697AD1-025 GEN
Solar/Wind Harmer
0.088
233933AB2-153 GEN
Solar/Wind Helper
0.141
315773AC2-141 GEN
Solar/Wind Harmer
2.95
233935AB2-179 C
Solar/Wind Helper
0.775
315732AD1-074 GEN1
Solar/Wind Harmer
0.431
315733AD1-074 GEN2
Solar/Wind Harmer
0.431
315735AD1-075 GEN1
Solar/Wind Harmer
0.215
315737AD1-076 GEN
Solar/Wind Harmer
0.97
316473AC1-191 GEN
Solar/Wind Harmer
0.29
316478AD1-087 GEN
Solar/Wind Harmer
0.251
316486AD2-202 GEN
Solar/Wind Harmer
0.074
316447AC1-158 HLD
Solar/Wind Harmer
1.006
316044AC1-158 PL1
Solar/Wind Harmer
0.458
316045AC1-158 PL2
Solar/Wind Harmer
1.464
316450AC1-158 RIC
Solar/Wind Harmer
0.122
316072AD1-144
Solar/Wind Harmer
0.029
315778AD1-151 GEN
Solar/Wind Harmer
6.568
316156AD2-030 GEN
Solar/Wind Harmer
0.062
315785AD2-033 C
Solar/Wind Harmer
0.577
316337AD2-073 GEN
Solar/Wind Harmer
0.076
234015AF2-250 C
Solar/Wind Helper
0.023
234036AF2-325 C
Solar/Wind Helper
0.025
207484AF2-139 C O1
Solar/Wind Helper
0.048
207510AF2-138 C
Solar/Wind Helper
0.047
207518AF1-320_GEN
Solar/Wind Helper
0.902
207442AE1-156 GEN
Solar/Wind Helper
0.189
226929AD2-058 GEN
Solar/Wind Helper
0.144
207437AD2-070 GEN
Solar/Wind Helper
0.079
209054AE2-059 GEN
Solar/Wind Helper
0.043
313526AB2-022
Solar/Wind Harmer
0.042
316313AB2-026
Solar/Wind Harmer
0.049
207445AB1-138_GEN
Solar/Wind Helper
0.061
209071AE2-133 GEN
Solar/Wind Helper
0.042
209116AE2-175 GEN
Solar/Wind Helper
1.008
3145513AHOSKIE
Solar/Wind Harmer
0.074
3145513AHOSKIE
Solar/Wind Harmer
0.156
233923SMA
Solar/Wind Helper
0.453
230433AD2-135 GEN
Solar/Wind Helper
0.01
219680HOPEWELLV C1
Solar/Wind Helper
0.002
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.043
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219258KINSLEYDEP C
Solar/Wind Helper
0.046
219304NAMERICA C
Solar/Wind Helper
0.078
219921AF1-264
Solar/Wind Helper
0.03
203975AE1-071-GEN
Solar/Wind Helper
1.719
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
207530AG1-191 GEN
Solar/Wind Helper
0.038
230511AF1-262
Solar/Wind Helper
0.009
205932AD2-116_GEN
Solar/Wind Helper
0.386
205941AD2-115 GEN
Solar/Wind Helper
0.303
205943AE1-185 GEN
Solar/Wind Helper
0.388
205917AD1-020 ES
Solar/Wind Helper
0.319
205916AD1-020 GEN
Solar/Wind Helper
1.485
270494AE1-108_GEN
Solar/Wind Harmer
0.797
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3147623JAMES R
Solar/Wind Harmer
0.166
209067AE2-060 GEN
Solar/Wind Helper
0.042
209137AF2-361 C
Solar/Wind Helper
0.711
3150011OMF A
50/50
0.213
3150021OMF B
50/50
0.213
3146206CASHIE
Solar/Wind Harmer
0.075
3146206CASHIE
Solar/Wind Harmer
0.075
3146206CASHIE
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
316274AC1-208 GEN
Solar/Wind Harmer
0.369
316349AD2-085 GEN
Solar/Wind Harmer
0.053
3156021HOLLOMANSOL
Solar/Wind Harmer
0.335
315652AC1-086 GEN
Solar/Wind Harmer
8.072
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316359AB2-059 GEN
Solar/Wind Harmer
0.245
316131AB2-060 GEN
Solar/Wind Harmer
0.221
316192AB2-158 GEN
Solar/Wind Harmer
0.497
316132AB2-190 GEN1
Solar/Wind Harmer
0.439
316458AB2-190 GEN2
Solar/Wind Harmer
0.439
316263AC1-034 GEN
Solar/Wind Harmer
2.619
316129AC1-054 GEN
Solar/Wind Harmer
0.267
316123AC1-075 GEN
Solar/Wind Harmer
0.082
316210AC1-098 GEN
Solar/Wind Harmer
0.664
316212AC1-099_GEN
Solar/Wind Harmer
0.37
316118AC1-105 GEN
Solar/Wind Harmer
0.174
316254AC1-120 GEN1
Solar/Wind Harmer
3.292
316170AC1-121 GEN2
Solar/Wind Harmer
1.13
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316375AC2-012 GEN
Solar/Wind Harmer
0
316311AC2-079 GEN
Solar/Wind Harmer
2.299
316283AC2-100 C
Solar/Wind Harmer
0.124
316339AD2-160 GEN
Solar/Wind Harmer
0.128
316164AC1-076 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.026
316223AC1-118
Solar/Wind Harmer
0.064
316294AC1-161 GEN
Solar/Wind Harmer
1.396
315975AC1-164 GENB
Solar/Wind Harmer
0.026
315976AC1-164 GENA
Solar/Wind Harmer
0.883
316169AC1-164_GENC
Solar/Wind Harmer
0.763
316381AD1-082 GEN
Solar/Wind Harmer
0.082
316233AE1-074 FULL
Solar/Wind Harmer
0.067
316093AE2-104_GEN
Solar/Wind Harmer
1.34
315607AA1-063A GEN
Solar/Wind Harmer
0.149
3150851SPRUNCC
Adder
0.385
3150861SPRUNCD
Adder
0.385
230434AG1-499 GEN
Solar/Wind Helper
0.137
233964AF2-378 GEN
Solar/Wind Helper
0.025
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.055
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.148
207511W3-106 GEN
Solar/Wind Helper
0.015
208972BECR K09
Solar/Wind Helper
0.178
209029WAYMART-WD
Solar/Wind Helper
0.444
223401AF1-299 GEN
Solar/Wind Helper
0.398
230407AD2-065 C
Solar/Wind Helper
0.024
232432Z2-076 GEN
Solar/Wind Helper
0.04
232434Z2-077 GEN
Solar/Wind Helper
0.076
233996TM1833_GEN
Solar/Wind Helper
0.124
233997TMININ_4.2
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
3130086AYDLETT
Solar/Wind Harmer
0.319
3137643SOCKMAN
Solar/Wind Harmer
0.293
3138126ROCKLANDING
Solar/Wind Harmer
0.038
3138216PACIFIC
Solar/Wind Harmer
0.025
3138266HYDRAULIC
Solar/Wind Harmer
0.002
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138543CONSLDL
Solar/Wind Harmer
0.046
3142053HEARTS
Solar/Wind Harmer
0.121
3142946ENON
Solar/Wind Harmer
0.008
3142946ENON
Solar/Wind Harmer
0.028
3144536CHRHLND
Solar/Wind Harmer
0.012
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145453TOT5
Solar/Wind Harmer
0.097
3145493TOT1
Solar/Wind Harmer
0.309
3145493TOT1
Solar/Wind Harmer
0.161
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
3145603CNETO
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.073
3145783HORNRTN
Solar/Wind Harmer
1.297
3145783HORNRTN
Solar/Wind Harmer
1.037
3145783HORNRTN
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.218
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
3145823KELFORD
Solar/Wind Harmer
0.073
3145823KELFORD
Solar/Wind Harmer
0.073
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
0.135
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.334
3145893MURPHYS
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.203
3145933PARMELE
Solar/Wind Harmer
0.143
3145933PARMELE
Solar/Wind Harmer
0.072
3145933PARMELE
Solar/Wind Harmer
0.072
3145963POPLR C
Solar/Wind Harmer
0.073
3145963POPLR C
Solar/Wind Harmer
0.073
3146033SCOT NK
Solar/Wind Harmer
0.29
3146043SEABORD
Solar/Wind Harmer
0.074
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.277
3146233WITAKRS
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.074
3146263WOODLND
Solar/Wind Harmer
0.074
3146293MARTNCO
Solar/Wind Harmer
0.066
3146406KITTY HAWK
Solar/Wind Harmer
0.01
316321Z2-027
Solar/Wind Harmer
0.014
942461AE2-259 GEN
Solar/Wind Harmer
0
942751AE2-291 GEN
Solar/Wind Harmer
3.269
944011AF1-069 GEN
Solar/Wind Harmer
4.7
944491AF1-114 GEN
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
18.116
944591AF1-124 GEN
Solar/Wind Harmer
18.181
944601AF1-125 GEN
Solar/Wind Harmer
17.837
944631AF1-128 GEN
Adder
39.784
944641AF1-129 GEN
Adder
39.347
946301AF1-294 GEN
Solar/Wind Harmer
1.421
946691AF1-333 GEN
Solar/Wind Helper
0.234
946731AF1-337 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
946751AF1-339 GEN
Solar/Wind Helper
0.234
959311AF2-222 GEN
Solar/Wind Harmer
6.364
959381AF2-229 GEN
Solar/Wind Helper
0.257
959421AF2-233 GEN
Solar/Wind Helper
0.233
959431AF2-234 GEN
Solar/Wind Helper
0.467
959561AF2-247 GEN
Solar/Wind Helper
0.012
960081AF2-299 GEN
Solar/Wind Harmer
0.713
961261AF2-417 GEN
Solar/Wind Helper
0.241
961301AF2-421 GEN
Solar/Wind Helper
0.242
961331AF2-424 GEN
Solar/Wind Helper
0.237
961341AF2-425 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.237
961431AF2-434 GEN
Solar/Wind Helper
0.237
961601AG1-000A GEN
Solar/Wind Harmer
1.225
961601AG1-000A GEN
Solar/Wind Harmer
4.902
961611AG1-000B GEN
Solar/Wind Harmer
4.282
961611AG1-000B GEN
Solar/Wind Harmer
2.178
961671AG1-007 GEN
Solar/Wind Harmer
0.011
961791AG1-021 GEN
Solar/Wind Harmer
0.691
962561AG1-105 GEN
Solar/Wind Harmer
3.315
962571AG1-106 GEN
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
2.759
963151AG1-164 GEN
Solar/Wind Helper
0.242
963161AG1-165 GEN
Solar/Wind Helper
0.242
966871AG1-558 GEN
Solar/Wind Harmer
0.099
966881AG1-559 GEN
Solar/Wind Harmer
0.105
970053AG2-049 GEN
50/50
2.019
970085AG2-068 GEN
Solar/Wind Harmer
3.973
970087AG2-069 GEN
Solar/Wind Harmer
5.959
970099AG2-077 GEN
Solar/Wind Harmer
7.893
970117AG2-086 GEN
Solar/Wind Harmer
1.398
970117AG2-086 GEN
Solar/Wind Harmer
0.932
970133AG2-095 GEN
Solar/Wind Harmer
0.793
970189AG2-124 GEN
Solar/Wind Harmer
2.502
970221AG2-151 GEN
Solar/Wind Harmer
3.81
970257AG2-171 GEN
Solar/Wind Harmer
2.288
970293AG2-193 GEN
Solar/Wind Harmer
0.898
970301AG2-198 GEN
Solar/Wind Harmer
3.132
970323AG2-213 GEN
Solar/Wind Harmer
3.051
970401AG2-262 GEN
Solar/Wind Harmer
0.403
970533AG2-339 GEN
Solar/Wind Harmer
5.901
970581AG2-369 GEN
Solar/Wind Harmer
3.417
970601AG2-382 GEN
Solar/Wind Harmer
2.806
970657AG2-426 GEN
Solar/Wind Harmer
1.809
970657AG2-426 GEN
Solar/Wind Harmer
0.592
970673AG2-436 GEN
Solar/Wind Harmer
9.667
970681AG2-440 GEN
Solar/Wind Harmer
2.871
970683AG2-441 GEN
Solar/Wind Harmer
4.325
970685AG2-442 GEN
Solar/Wind Harmer
5.367
970831AG2-522 GEN
Solar/Wind Harmer
3.061
970917AG2-570 GEN
Solar/Wind Harmer
6.668
970919AG2-571 GEN
Solar/Wind Harmer
2.667
970933AG2-581 GEN
Solar/Wind Harmer
6.095
970937AG2-583 GEN
Solar/Wind Harmer
4.632
971065AG2-659 GEN
Solar/Wind Harmer
3.047
971069AG2-661 GEN
Solar/Wind Harmer
1.459
971153AH1-033 GEN
Solar/Wind Harmer
0.924
971163AH1-040 GEN
Solar/Wind Harmer
6.123
971223AH1-071 GEN
Solar/Wind Harmer
0.889
971281AH1-106 GEN
Solar/Wind Harmer
1.159
971283AH1-107 GEN
Solar/Wind Harmer
1.159
971285AH1-108 GEN
Adder
0.63
971317AH1-138 GEN
Solar/Wind Harmer
0.617
971377AH1-170 GEN
Solar/Wind Harmer
0.762
971445AH1-216 GEN
Solar/Wind Harmer
5.713
971455AH1-223 GEN
Solar/Wind Harmer
2.31
971547AH1-271 GEN
Solar/Wind Harmer
1.603
971563AH1-280 GEN
Solar/Wind Harmer
0.768
971623AH1-311 GEN
Solar/Wind Harmer
0.138
971683AH1-343 GEN
Solar/Wind Harmer
2.374
971685AH1-345 GEN
Solar/Wind Harmer
0.729
219918AC2-009 C
Solar/Wind Helper
0.001
227287AC2-120 GEN
Solar/Wind Helper
0.492
939411AE1-173 GEN
Solar/Wind Harmer
34.104
940641AE2-051 GEN
Solar/Wind Harmer
6.384
941031AE2-094 GEN
Solar/Wind Harmer
14.385
957481AF2-042 GEN
Solar/Wind Harmer
19.733
957861AF2-080 GEN
Solar/Wind Harmer
3.026
957871AF2-081 GEN
Solar/Wind Harmer
3.983
957921AF2-086 GEN
Solar/Wind Helper
0.234
958211AF2-115 GEN
Solar/Wind Harmer
0.864
958261AF2-120 GEN
Solar/Wind Harmer
2.855
963691AG1-221 GEN
Solar/Wind Harmer
2.31
963711AG1-223 GEN
Solar/Wind Helper
0.037
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
964241AG1-285 GEN
Solar/Wind Harmer
4.743
964791AG1-342 GEN
Solar/Wind Harmer
1.319
964851AG1-348 GEN
Solar/Wind Helper
0.036
966001AG1-469 GEN
Solar/Wind Harmer
0.051
971761AH1-387 GEN
Solar/Wind Harmer
1.229
971775AH1-396 GEN
Solar/Wind Harmer
0.114
971777AH1-397 GEN
Solar/Wind Harmer
0.223
971781AH1-399 GEN
Solar/Wind Harmer
0.117
971845AH1-439 GEN
Solar/Wind Harmer
3.318
971967AH1-528 GEN
Solar/Wind Harmer
12.296
972003AH1-546 GEN
Solar/Wind Harmer
2.538
972135AH1-637 GEN
Solar/Wind Harmer
0.78
972185AH1-677 GEN
Adder
4.323
972187AH1-678 GEN
Adder
2.18
972189AH1-679 GEN
Adder
1.465
972193AH1-681 GEN
Adder
1.64
972195AH1-682 GEN
Adder
1.66
972197AH1-683 GEN
Adder
1.977
972199AH1-684 GEN
50/50
2.016
972201AH1-685 GEN
50/50
2.279
972205AH1-687 GEN
Adder
3.128
972213AH1-691 GEN
Adder
2.056
972215AH1-692 GEN
Adder
2.056
972217AH1-693 GEN
50/50
1.753
972219AH1-694 GEN
Adder
1.423
972223AH1-696 GEN
50/50
9.014
972255AH1-712 GEN
Adder
36.701
972277AH1-723 GEN
Adder
42.768
233950AC2-186 GEN
Solar/Wind Helper
0.07
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
315722AD1-056 GEN
Solar/Wind Harmer
2.442
315724AD1-057 GEN
Solar/Wind Harmer
1.362
315835AF2-110_GEN
Solar/Wind Harmer
0.547
232422X3-066 FULL
Solar/Wind Helper
0.069
315693AD1-088 GEN
Solar/Wind Harmer
3.538
219919AE1-041 FULL
Solar/Wind Helper
0.002
219912AD2-042 GEN
Solar/Wind Helper
0.089
219914AD2-027 C
Solar/Wind Helper
0.068
235063AE1-101 C2
Solar/Wind Helper
1.069
3151721LOISA A
Adder
5.561
NYPJM->LTFIMP_NY
CLTF
2.582
LGEELTFEXP_LGEE->PJM
CLTF
1.798
WECLTFEXP_WEC->PJM
CLTF
0.958
CPLELTFEXP_CPLE->PJM
CLTF
5.053
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.329
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.822
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.552
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.532
TVALTFEXP_TVA->PJM
CLTF
3.177
MECLTFEXP_MEC->PJM
CLTF
4.431
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.4 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1720.2
MW Contribution:
4.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
Adder
0.13
3144293JTRSVLE
Adder
0.164
3144293JTRSVLE
Adder
0.164
3144293JTRSVLE
Adder
0.164
3147043LAWRENC
Solar/Wind Harmer
-0.005
3147043LAWRENC
Adder
0.625
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.006
3147133PAMPLIN
Solar/Wind Harmer
-0.008
20390526W1-045 C
Solar/Wind Helper
0.226
23544701WINZ1-113
Adder
0.24
20671828STAW2-080
Solar/Wind Helper
0.02
20671928W4-073
Solar/Wind Helper
0.066
20673628F1S_V4-069
Solar/Wind Helper
0.022
20673728F2S_V4-070
Solar/Wind Helper
0.022
20673828FLE_V3-070
Solar/Wind Helper
0.065
20674128FR_U2-059
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.017
20674628WNG_W3-110
Solar/Wind Helper
0.066
20674828DL_W4-046
Solar/Wind Helper
0.006
20674928WA_W3-044
Solar/Wind Helper
0.073
20675128HRM_W1-127
Solar/Wind Helper
0.022
20675428EAM_W2-061
Solar/Wind Helper
0.012
20675528CPH_W2-050
Solar/Wind Helper
0.085
20675728RH_W2-091
Solar/Wind Helper
0.06
20675828AU_W4-064
Solar/Wind Helper
0.022
20675928HOL_W4-097
Solar/Wind Helper
0.037
20676128MHD_W3-029
Solar/Wind Helper
0.072
20676228FRD_X1-012
Solar/Wind Helper
0.068
20676328BVR_Y1-020
Solar/Wind Helper
0.02
20676428JCR_X2-075
Solar/Wind Helper
0.051
20676728BRNX1-095
Solar/Wind Helper
0.022
20714528FRN_Y2-051
Solar/Wind Helper
0.043
20714828MDF_W3-079
Solar/Wind Helper
0.099
20714928UPF_X1-085
Solar/Wind Helper
0.004
20715028HAN_X4-015
Solar/Wind Helper
0.044
20715228NPK_W1-113
Solar/Wind Helper
0.059
20715728PEM_W1-119
Solar/Wind Helper
0.073
20715828PEM_W1-120
Solar/Wind Helper
0.073
20716028EGP_W2-019
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.039
20720528MAN_W1-024
Solar/Wind Helper
0.021
20720628TIN_W1-124
Solar/Wind Helper
0.144
20720728JCB_W1-129
Solar/Wind Helper
0.044
20720828JCB_W4-025
Solar/Wind Helper
0.048
207408W3-077 C
Solar/Wind Helper
0.062
207439AE1-081 C O1
Solar/Wind Helper
0.014
214067T20SOLAR
Solar/Wind Helper
0.009
217206BARNGR HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
217209CENTRL HS C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.022
232404W1-003 C
Solar/Wind Helper
0.401
232408W1-005 C
Solar/Wind Helper
0.401
232410W1-006 C
Solar/Wind Helper
0.401
232417X3-008 C
Solar/Wind Helper
0.184
232426Y1-080 FULL
Solar/Wind Helper
0.031
232428Y3-058 C
Solar/Wind Helper
0.267
23777801MSM_W1-116
Solar/Wind Helper
0.111
3137176SLIGO L2192
Solar/Wind Harmer
-0.033
3141346CRANES
Adder
0.097
3141426STAFORD
Solar/Wind Harmer
-0.002
3141843SHACKLE
Adder
0.389
3141906WESTMOR
Solar/Wind Harmer
-0.003
3142296MT RD221
Adder
0.244
3142366NRTHEST
Adder
0.249
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3142416OLDCHRC
Solar/Wind Harmer
0.866
3142416OLDCHRC
Solar/Wind Harmer
-0.008
3142433PROV 92
Solar/Wind Harmer
-0.034
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142956BIRDNECK
Solar/Wind Harmer
0.445
3143096IRON208
Adder
0.312
3143096IRON208
Adder
0.318
3143096IRON208
Adder
0.318
3143316POE
Solar/Wind Harmer
-0.033
3143336POWHATN
Solar/Wind Harmer
0.99
3143336POWHATN
Solar/Wind Harmer
0.841
3144216WINCHST
Adder
0.282
3144356SAPONY
Solar/Wind Harmer
0.285
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.02
3145506HICKORY
Solar/Wind Harmer
-0.005
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3146396TANGLEW
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
3146776BUCKING
Solar/Wind Harmer
-0.003
3146776BUCKING
Solar/Wind Harmer
-0.003
3150071POSSM 5
Adder
38.706
3150151POSSMC1
Adder
0.847
3150151POSSMC1
Adder
0.847
3150151POSSMC1
Adder
0.847
3150181POSSMC2
Adder
0.847
3150181POSSMC2
Adder
0.847
3150181POSSMC2
Adder
0.854
3150211REMNGT1
Adder
12.461
3150221REMNGT2
Adder
12.544
3150241REMNGT4
Adder
12.627
3150281M RUN A
Adder
13.427
3150291M RUN B
Adder
13.319
3150301M RUN C
Adder
13.419
3150331BIRCHWDA
Adder
13.822
3150341NORNECKC1
Adder
0.801
3150341NORNECKC1
Adder
0.808
3150351NORNECKC2
Adder
0.782
3150351NORNECKC2
Adder
0.769
3150391LDYSMT3
Adder
10.838
3150401LDYSMT4
Adder
10.858
3150411LDYSMT5
Adder
10.892
3150671DARBY 1
Adder
5.457
3150681DARBY 2
Adder
5.463
3150691DARBY 3
Adder
5.482
3150701DARBY 4
Adder
5.469
3150921YORKTN3
Adder
1.882
209027LOR2_Q27
Solar/Wind Helper
0.713
212266LOR1
Solar/Wind Helper
0.208
217081WEATEXAS C
Solar/Wind Helper
0.009
217169METRODIV C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.002
217202FBANKSOLAR C
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.021
218440SUMMTASSOC C
Solar/Wind Helper
0.012
218660EHAMPSOLAR C
Solar/Wind Helper
0.025
219236SOUTHERNHQ C
Solar/Wind Helper
0.004
219249CENTRALDIV C
Solar/Wind Helper
0.008
219272CLEANLIGHT C
Solar/Wind Helper
0.02
219276PARKLANDSO C
Solar/Wind Helper
0.068
219291REEVESSOUT C
Solar/Wind Helper
0.009
219348LDSOLAR C
Solar/Wind Helper
0.088
219607WPEMNERT C
Solar/Wind Helper
0.062
219612MATRIX C
Solar/Wind Helper
0.018
219615MILLCREEK C
Solar/Wind Helper
0.02
219620RIDERU C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.042
227927V4-067C
Solar/Wind Helper
0.008
3150981CHESPKA
Adder
0.923
3150991CHESPKB
Adder
0.756
3150991CHESPKB
Adder
0.775
3151081ELIZAR1
Adder
6.78
3151091ELIZAR2
Adder
6.662
3151101ELIZAR3
Adder
6.866
3151171GRAVELC
Adder
0.793
3151171GRAVELC
Adder
1.042
3151191GRAVEL3
Adder
5.356
3151201GRAVEL4
Adder
5.424
3151211GRAVEL5
Adder
5.356
3151221GRAVEL6
Adder
5.418
3151731LOISA B
Adder
5.418
3151751LOISA D
Adder
5.418
3151761LOISA E
Adder
11.045
3151861LOWMORA
Adder
0.673
3151861LOWMORA
Adder
0.647
3151881LOWMORC
Adder
0.657
3151881LOWMORC
Adder
0.668
3152111X4-039 GT1
50/50
2.013
3152121X4-039 GT2
50/50
2
3152131X4-039 ST
50/50
3.148
3152541MT STMG
Adder
0.592
316075AC2-137 C
Solar/Wind Harmer
0.23
316077AC2-138 C
Solar/Wind Harmer
0.182
228728W1-130C
Solar/Wind Helper
0.042
228729W2-030 C
Solar/Wind Helper
0.085
3138133OCRAN
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.005
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3141766HARMONY
Solar/Wind Harmer
0.761
3141766HARMONY
Solar/Wind Harmer
-0.002
3141783LANCAST
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.003
3141813NORNECK
Solar/Wind Harmer
-0.009
3141913WHIT STONE
Solar/Wind Harmer
-0.009
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3143873LANEXA
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
3146376EDENTON
Solar/Wind Harmer
0.24
3146376EDENTON
Solar/Wind Harmer
0.24
3146456SLIGO L269
Solar/Wind Harmer
0.976
3146456SLIGO L269
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.005
3146926FARMVIL
Solar/Wind Harmer
-0.005
3147346CASHSCORNER
Solar/Wind Harmer
0.143
3147666LOUISA
Solar/Wind Harmer
-0.038
3147666LOUISA
Solar/Wind Harmer
-0.022
232406W1-004 FULL
Solar/Wind Helper
0.401
232436AB1-176 C
Solar/Wind Helper
0.035
3141726DUNNSVL
Solar/Wind Harmer
-0.034
3145663CRESWEL
Solar/Wind Harmer
-0.022
316034AC1-036 C
Solar/Wind Harmer
0.142
316036AC1-147 C
Solar/Wind Harmer
0.224
316059AD1-063 C
Solar/Wind Harmer
0.193
316159AE1-175 C
Solar/Wind Harmer
0.226
316240AF1-291 C
Solar/Wind Harmer
0.254
316246AF1-032 C
Solar/Wind Harmer
0.167
316258AE1-075 C
Solar/Wind Harmer
0.202
316305AF2-043 C
Solar/Wind Harmer
0.248
316314AB2-024 C
Solar/Wind Harmer
0.73
316315AB2-025 C
Solar/Wind Harmer
0.22
316316AC1-027 C
Solar/Wind Harmer
0.254
316317KELFORD C
Solar/Wind Harmer
0.359
316336AC2-165 C
Solar/Wind Harmer
5.168
316382AG1-145 C
Solar/Wind Harmer
0.254
316405AF2-144 C
Solar/Wind Harmer
0.213
223402AF1-300 C
Solar/Wind Helper
0.38
230415AB2-049 C
Solar/Wind Helper
0.023
20742028HF_AC1-207
Solar/Wind Helper
0.106
207454AA2-184 E
Solar/Wind Helper
0.234
207459AE1-142 C O1
Solar/Wind Helper
0.221
207471AF2-354 C
Solar/Wind Helper
0.124
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
232424Y1-079 C
Solar/Wind Helper
0.092
3150371LDYSMT1
Adder
10.492
3150381LDYSMT2
Adder
10.424
218524CNTRALGAS1 C
Solar/Wind Helper
0.121
218526CNTRALGAS2 C
Solar/Wind Helper
0.121
226910AB2-157 C
Solar/Wind Helper
0.012
233901CHERRYDALE C
Solar/Wind Helper
0.184
233940AF2-379 C
Solar/Wind Helper
0.049
212507AE2-042_GEN
Solar/Wind Helper
1.059
219907AC1-030 C
Solar/Wind Helper
0.026
237025AB1-124 C
Solar/Wind Helper
0.169
237030AB1-096 C
Solar/Wind Helper
0.069
237038AE2-054 C
Solar/Wind Helper
0.12
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.033
3145336SMITFLD
Solar/Wind Harmer
-0.003
3141196NOKESVL
Solar/Wind Harmer
-0.049
3141873WAN 176
Solar/Wind Harmer
1.014
3141873WAN 176
Solar/Wind Harmer
-0.002
3143526WINTERP
Solar/Wind Harmer
-0.044
3143526WINTERP
Solar/Wind Harmer
-0.044
316411AF1-147_GEN1
Solar/Wind Harmer
1.196
316415AF1-147_GEN2
Solar/Wind Harmer
1.196
316404AE1-155 C
Solar/Wind Harmer
1.647
316017AA1-139 ULT1
Solar/Wind Harmer
0.667
316018AA1-139 ULT2
Solar/Wind Harmer
0.707
316181AB2-040 GEN
Solar/Wind Harmer
1.085
316033AB2-134 GEN
Solar/Wind Harmer
2.708
228754AB1-001 C
Solar/Wind Helper
0.02
316388AE2-253 GEN
Solar/Wind Harmer
0.556
235062AE1-101 C1
Solar/Wind Helper
0.75
205956AE1-196_GEN
Solar/Wind Helper
0.424
217204WCALDSOLAR C
Solar/Wind Helper
0.002
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3132273ORANGE
Solar/Wind Harmer
-0.002
3142543TWELFTH
Solar/Wind Harmer
-0.001
3144303KENBRDG
Solar/Wind Harmer
-0.006
237080AD1-060 GEN
Solar/Wind Helper
0.152
235067AD1-061 GEN
Solar/Wind Helper
0.193
237001AB1-127_GEN
Solar/Wind Helper
0.222
237002AB1-128_GEN
Solar/Wind Helper
0.213
238221AF1-254 C O1
Solar/Wind Helper
0.123
316203AE2-005 GEN
Solar/Wind Harmer
3.602
316441AF1-014 GEN
Solar/Wind Harmer
0.576
233944AB2-135 GEN
Solar/Wind Helper
0.467
233946AB2-136 GEN
Solar/Wind Helper
0.45
316426AA2-053 GEN
Solar/Wind Harmer
0.782
316190AA2-174 GEN
Solar/Wind Harmer
0.095
3156081AA2-088 GEN
Solar/Wind Harmer
2.574
233994AC2-023 GEN
Solar/Wind Helper
0.76
315614AA2-178 GEN
Solar/Wind Harmer
0.86
315816AE2-034 GEN
Solar/Wind Harmer
0.645
316312AB1-027
Solar/Wind Harmer
0.289
316011AB1-132 GEN
Solar/Wind Harmer
1.62
316369SG1_INVT
Solar/Wind Harmer
1.5
315651AD1-115 GEN
Solar/Wind Harmer
4.548
316023GEN1_S
Solar/Wind Harmer
0.531
316365GEN2_N
Solar/Wind Harmer
0.531
237006AB1-125 GEN
Solar/Wind Helper
0.127
23779801AA1-109
Solar/Wind Helper
0.182
316463AE2-346 GEN
Solar/Wind Harmer
0.126
315839AE2-212 C
Solar/Wind Harmer
0.253
233982AB2-133 GEN
Solar/Wind Helper
0.284
233915AB1-141 GEN
Solar/Wind Helper
0.398
233918AB1-142 GEN
Solar/Wind Helper
0.398
315821AE2-092 GEN
Solar/Wind Harmer
1.599
315814AE2-033 C
Solar/Wind Harmer
7.588
315671AE2-027_GEN
Solar/Wind Harmer
1.522
315747AE2-019 GEN
50/50
14.046
233930AB2-032 GEN
Solar/Wind Helper
0.302
233987AB2-037 GEN
Solar/Wind Helper
1.854
315662AE1-191 GEN
Solar/Wind Harmer
1.027
315666AE1-190 GEN
Solar/Wind Harmer
0.257
315673AE1-157 GEN
Solar/Wind Harmer
6.743
315813AE1-149 C
Solar/Wind Harmer
5.222
315683AE1-153 C
Solar/Wind Harmer
9.352
315742AE1-103 GEN
Solar/Wind Harmer
1.923
319010AE1-072 C
Solar/Wind Harmer
1.667
316065AD1-022 GEN
Solar/Wind Harmer
3.952
315697AD1-025 GEN
Solar/Wind Harmer
1.697
316185AD1-033 GEN
Solar/Wind Harmer
0.873
233933AB2-153 GEN
Solar/Wind Helper
0.184
315773AC2-141 GEN
Solar/Wind Harmer
3.486
316280AD1-041 GEN
Solar/Wind Harmer
0.642
233935AB2-179 C
Solar/Wind Helper
1.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.599
315733AD1-074 GEN2
Solar/Wind Harmer
1.599
315735AD1-075 GEN1
Solar/Wind Harmer
0.799
315737AD1-076 GEN
Solar/Wind Harmer
1.504
316473AC1-191 GEN
Solar/Wind Harmer
0.93
316478AD1-087 GEN
Solar/Wind Harmer
0.668
316486AD2-202 GEN
Solar/Wind Harmer
0.195
316447AC1-158 HLD
Solar/Wind Harmer
2.175
316044AC1-158 PL1
Solar/Wind Harmer
0.989
316045AC1-158 PL2
Solar/Wind Harmer
3.165
316450AC1-158 RIC
Solar/Wind Harmer
0.264
316468AD1-105 GEN
Solar/Wind Harmer
1.005
316072AD1-144
Solar/Wind Harmer
0.167
315778AD1-151 GEN
Solar/Wind Harmer
7.492
316156AD2-030 GEN
Solar/Wind Harmer
0.227
316337AD2-073 GEN
Solar/Wind Harmer
0.234
234015AF2-250 C
Solar/Wind Helper
0.03
234036AF2-325 C
Solar/Wind Helper
0.033
207484AF2-139 C O1
Solar/Wind Helper
0.062
207510AF2-138 C
Solar/Wind Helper
0.06
207518AF1-320_GEN
Solar/Wind Helper
1.157
207442AE1-156 GEN
Solar/Wind Helper
0.244
226929AD2-058 GEN
Solar/Wind Helper
0.066
207437AD2-070 GEN
Solar/Wind Helper
0.102
209054AE2-059 GEN
Solar/Wind Helper
0.054
313526AB2-022
Solar/Wind Harmer
0.221
316313AB2-026
Solar/Wind Harmer
0.224
207445AB1-138_GEN
Solar/Wind Helper
0.079
209071AE2-133 GEN
Solar/Wind Helper
0.054
209116AE2-175 GEN
Solar/Wind Helper
1.293
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.068
233923SMA
Solar/Wind Helper
0.594
230433AD2-135 GEN
Solar/Wind Helper
0.013
219680HOPEWELLV C1
Solar/Wind Helper
0.002
219686LUMSOLAR_N C
Solar/Wind Helper
0.031
219688LUMSOLAR_S C
Solar/Wind Helper
0.031
219908AB1-139 C
Solar/Wind Helper
0.055
219904AC1-010 C
Solar/Wind Helper
0.047
219906AC1-017 C
Solar/Wind Helper
0.032
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219258KINSLEYDEP C
Solar/Wind Helper
0.059
219304NAMERICA C
Solar/Wind Helper
0.101
219921AF1-264
Solar/Wind Helper
0.039
203975AE1-071-GEN
Solar/Wind Helper
1.568
211065PSPA IPP
Solar/Wind Helper
0.11
211065PSPA IPP
Solar/Wind Helper
0.11
207530AG1-191 GEN
Solar/Wind Helper
0.049
230511AF1-262
Solar/Wind Helper
0.011
205932AD2-116_GEN
Solar/Wind Helper
0.424
205941AD2-115 GEN
Solar/Wind Helper
0.376
205943AE1-185 GEN
Solar/Wind Helper
0.425
205917AD1-020 ES
Solar/Wind Helper
0.323
205916AD1-020 GEN
Solar/Wind Helper
1.501
3147623JAMES R
Solar/Wind Harmer
0.121
209067AE2-060 GEN
Solar/Wind Helper
0.052
209137AF2-361 C
Solar/Wind Helper
0.867
3146206CASHIE
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
316349AD2-085 GEN
Solar/Wind Harmer
0.734
3156021HOLLOMANSOL
Solar/Wind Harmer
1.054
315652AC1-086 GEN
Solar/Wind Harmer
8.728
313506AB2-031 GEN
Solar/Wind Harmer
0.625
316006AB2-029 C
Solar/Wind Harmer
0.63
316322AB2-045
Solar/Wind Harmer
0.266
316192AB2-158 GEN
Solar/Wind Harmer
1.118
316083AB2-161 GEN
Solar/Wind Harmer
1.35
316174AB2-169 GEN
Solar/Wind Harmer
1.19
316087AB2-174 GEN
Solar/Wind Harmer
1.111
316132AB2-190 GEN1
Solar/Wind Harmer
0.85
316458AB2-190 GEN2
Solar/Wind Harmer
0.85
316254AC1-120 GEN1
Solar/Wind Harmer
3.829
316170AC1-121 GEN2
Solar/Wind Harmer
1.276
316375AC2-012 GEN
Solar/Wind Harmer
2.873
316311AC2-079 GEN
Solar/Wind Harmer
4.173
316339AD2-160 GEN
Solar/Wind Harmer
0.556
316164AC1-076 GEN
Solar/Wind Harmer
0.844
316140AB2-099
Solar/Wind Harmer
0.053
316223AC1-118
Solar/Wind Harmer
0.236
316294AC1-161 GEN
Solar/Wind Harmer
2.694
315975AC1-164 GENB
Solar/Wind Harmer
0.057
315976AC1-164 GENA
Solar/Wind Harmer
1.94
316169AC1-164_GENC
Solar/Wind Harmer
1.676
316381AD1-082 GEN
Solar/Wind Harmer
0.761
316233AE1-074 FULL
Solar/Wind Harmer
0.231
316236AE1-162_GEN
Solar/Wind Harmer
0.251
316093AE2-104_GEN
Solar/Wind Harmer
2.397
315607AA1-063A GEN
Solar/Wind Harmer
0.787
3150851SPRUNCC
Adder
0.35
3150861SPRUNCD
Adder
0.35
230434AG1-499 GEN
Solar/Wind Helper
0.178
233964AF2-378 GEN
Solar/Wind Helper
0.033
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.064
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
207511W3-106 GEN
Solar/Wind Helper
0.02
208972BECR K09
Solar/Wind Helper
0.228
209029WAYMART-WD
Solar/Wind Helper
0.567
223401AF1-299 GEN
Solar/Wind Helper
0.38
230407AD2-065 C
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.053
232434Z2-077 GEN
Solar/Wind Helper
0.1
233996TM1833_GEN
Solar/Wind Helper
0.162
233997TMININ_4.2
Solar/Wind Helper
0.162
233998TM1NIN_3.36
Solar/Wind Helper
0.162
3130086AYDLETT
Solar/Wind Harmer
-0.033
3137643SOCKMAN
Solar/Wind Harmer
-0.031
3138126ROCKLANDING
Solar/Wind Harmer
0.026
3138216PACIFIC
Solar/Wind Harmer
-0.003
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3142946ENON
Solar/Wind Harmer
-0.001
3142946ENON
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3144873MCLAUGH
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
0.917
3145783HORNRTN
Solar/Wind Harmer
0.733
3145783HORNRTN
Solar/Wind Harmer
0.229
3145783HORNRTN
Solar/Wind Harmer
0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3145823KELFORD
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145963POPLR C
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
3146033SCOT NK
Solar/Wind Harmer
-0.031
3146043SEABORD
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.999
315800Z1-036_GEN1
Solar/Wind Harmer
1.999
316318V4-068
Solar/Wind Harmer
0.197
316320Y1-086
Solar/Wind Harmer
0.482
316321Z2-027
Solar/Wind Harmer
0.221
942461AE2-259 GEN
Solar/Wind Harmer
1.175
944011AF1-069 GEN
Solar/Wind Harmer
4.79
944491AF1-114 GEN
Solar/Wind Harmer
2.607
944581AF1-123 GEN
Solar/Wind Harmer
37.785
944591AF1-124 GEN
Solar/Wind Harmer
37.921
944601AF1-125 GEN
Solar/Wind Harmer
37.195
944631AF1-128 GEN
Adder
36.103
944641AF1-129 GEN
Adder
35.868
946281AF1-292 GEN
Solar/Wind Harmer
0.175
946301AF1-294 GEN
Solar/Wind Harmer
1.983
946691AF1-333 GEN
Solar/Wind Helper
0.298
946731AF1-337 GEN
Solar/Wind Helper
0.298
946741AF1-338 GEN
Solar/Wind Helper
0.298
946751AF1-339 GEN
Solar/Wind Helper
0.298
959311AF2-222 GEN
Solar/Wind Harmer
8.024
959381AF2-229 GEN
Solar/Wind Helper
0.231
959421AF2-233 GEN
Solar/Wind Helper
0.297
959431AF2-234 GEN
Solar/Wind Helper
0.595
959561AF2-247 GEN
Solar/Wind Helper
0.016
960081AF2-299 GEN
Solar/Wind Harmer
0.881
961261AF2-417 GEN
Solar/Wind Helper
0.309
961301AF2-421 GEN
Solar/Wind Helper
0.31
961331AF2-424 GEN
Solar/Wind Helper
0.303
961341AF2-425 GEN
Solar/Wind Helper
0.303
961421AF2-433 GEN
Solar/Wind Helper
0.302
961431AF2-434 GEN
Solar/Wind Helper
0.302
961611AG1-000B GEN
Solar/Wind Harmer
4.139
961611AG1-000B GEN
Solar/Wind Harmer
1.766
961791AG1-021 GEN
Solar/Wind Harmer
0.967
961941AG1-037 GEN
Solar/Wind Harmer
0.059
961951AG1-038 GEN
Solar/Wind Harmer
1.134
962571AG1-106 GEN
Solar/Wind Harmer
1.115
962861AG1-135 GEN
Solar/Wind Harmer
3.234
963151AG1-164 GEN
Solar/Wind Helper
0.31
963161AG1-165 GEN
Solar/Wind Helper
0.31
966871AG1-558 GEN
Solar/Wind Harmer
0.26
966871AG1-558 GEN
Solar/Wind Harmer
0.089
966881AG1-559 GEN
Solar/Wind Harmer
0.268
966881AG1-559 GEN
Solar/Wind Harmer
0.092
970053AG2-049 GEN
Adder
1.705
970085AG2-068 GEN
Solar/Wind Harmer
4.913
970087AG2-069 GEN
Solar/Wind Harmer
7.37
970099AG2-077 GEN
Solar/Wind Harmer
9.803
970133AG2-095 GEN
Solar/Wind Harmer
0.951
970221AG2-151 GEN
Solar/Wind Harmer
4.898
970257AG2-171 GEN
Solar/Wind Harmer
0.181
970293AG2-193 GEN
Solar/Wind Harmer
1.069
970301AG2-198 GEN
Solar/Wind Harmer
3.93
970323AG2-213 GEN
Solar/Wind Harmer
3.839
970533AG2-339 GEN
Solar/Wind Harmer
5.483
970581AG2-369 GEN
Solar/Wind Harmer
4.225
970601AG2-382 GEN
Solar/Wind Harmer
3.452
970657AG2-426 GEN
Solar/Wind Harmer
1.68
970657AG2-426 GEN
Solar/Wind Harmer
0.524
970673AG2-436 GEN
Solar/Wind Harmer
17.761
970681AG2-440 GEN
Solar/Wind Harmer
3.614
970683AG2-441 GEN
Solar/Wind Harmer
5.445
970685AG2-442 GEN
Solar/Wind Harmer
6.757
970917AG2-570 GEN
Solar/Wind Harmer
19.76
970919AG2-571 GEN
Solar/Wind Harmer
2.501
970933AG2-581 GEN
Solar/Wind Harmer
7.508
970937AG2-583 GEN
Solar/Wind Harmer
5.831
971069AG2-661 GEN
Solar/Wind Harmer
1.332
971153AH1-033 GEN
Solar/Wind Harmer
0.956
971163AH1-040 GEN
Solar/Wind Harmer
7.498
971223AH1-071 GEN
Solar/Wind Harmer
1.073
971281AH1-106 GEN
Solar/Wind Harmer
1.394
971283AH1-107 GEN
Solar/Wind Harmer
1.394
971285AH1-108 GEN
Adder
0.573
971317AH1-138 GEN
Solar/Wind Harmer
1.055
971377AH1-170 GEN
Solar/Wind Harmer
0.98
971445AH1-216 GEN
Solar/Wind Harmer
5.168
971455AH1-223 GEN
Solar/Wind Harmer
2.518
971547AH1-271 GEN
Solar/Wind Harmer
1.973
971563AH1-280 GEN
Solar/Wind Harmer
0.967
971685AH1-345 GEN
Solar/Wind Harmer
0.962
219918AC2-009 C
Solar/Wind Helper
0.001
227287AC2-120 GEN
Solar/Wind Helper
0.268
316431W1029_GEN1
Solar/Wind Harmer
1.483
316433W1029_GEN2
Solar/Wind Harmer
1.483
316435W1029_GEN3
Solar/Wind Harmer
1.483
939411AE1-173 GEN
Solar/Wind Harmer
41.429
940641AE2-051 GEN
Solar/Wind Harmer
7.765
941031AE2-094 GEN
Solar/Wind Harmer
15.288
957481AF2-042 GEN
Solar/Wind Harmer
24.507
957601AF2-054 GEN
Solar/Wind Harmer
0.256
957831AF2-077 GEN
Solar/Wind Harmer
0.255
957871AF2-081 GEN
Solar/Wind Harmer
4.136
957921AF2-086 GEN
Solar/Wind Helper
0.299
957971AF2-091 GEN
Solar/Wind Harmer
0.887
958211AF2-115 GEN
Solar/Wind Harmer
1.209
958261AF2-120 GEN
Solar/Wind Harmer
3.344
963691AG1-221 GEN
Solar/Wind Harmer
2.518
963711AG1-223 GEN
Solar/Wind Helper
0.049
964051AG1-259 GEN
Solar/Wind Helper
0.044
964061AG1-260 GEN
Solar/Wind Helper
0.044
964211AG1-282 GEN
Solar/Wind Harmer
0.26
964851AG1-348 GEN
Solar/Wind Helper
0.046
966001AG1-469 GEN
Solar/Wind Harmer
0.179
966621AG1-532 GEN
Solar/Wind Harmer
0.159
971761AH1-387 GEN
Solar/Wind Harmer
4.557
971777AH1-397 GEN
Solar/Wind Harmer
0.997
971781AH1-399 GEN
Solar/Wind Harmer
0.542
971845AH1-439 GEN
Solar/Wind Harmer
4.206
971967AH1-528 GEN
Solar/Wind Harmer
15.148
972003AH1-546 GEN
Solar/Wind Harmer
3.236
972135AH1-637 GEN
Solar/Wind Harmer
0.886
972185AH1-677 GEN
Adder
4.03
972187AH1-678 GEN
Adder
2.035
972189AH1-679 GEN
Adder
1.303
972193AH1-681 GEN
Adder
1.592
972195AH1-682 GEN
Adder
1.424
972197AH1-683 GEN
Adder
1.696
972199AH1-684 GEN
Adder
1.915
972201AH1-685 GEN
Adder
2.164
972205AH1-687 GEN
Adder
3.031
972213AH1-691 GEN
Adder
1.763
972215AH1-692 GEN
Adder
1.763
972217AH1-693 GEN
Adder
1.665
972219AH1-694 GEN
Adder
1.221
972223AH1-696 GEN
Adder
6.689
972255AH1-712 GEN
Adder
35.633
972257AH1-713 GEN
Adder
0.696
972277AH1-723 GEN
Adder
41.523
233950AC2-186 GEN
Solar/Wind Helper
0.092
233952AC2-187 GEN
Solar/Wind Helper
0.184
233954AC2-188 GEN
Solar/Wind Helper
0.184
315835AF2-110_GEN
Solar/Wind Harmer
1.03
232422X3-066 FULL
Solar/Wind Helper
0.09
315693AD1-088 GEN
Solar/Wind Harmer
3.916
316487AF1-042 GEN
Solar/Wind Harmer
1.134
315833AF1-017_GEN
Solar/Wind Harmer
1.571
316484AD2-074 GEN
Solar/Wind Harmer
2.167
219919AE1-041 FULL
Solar/Wind Helper
0.003
219912AD2-042 GEN
Solar/Wind Helper
0.116
219914AD2-027 C
Solar/Wind Helper
0.089
235063AE1-101 C2
Solar/Wind Helper
0.75
3151721LOISA A
Adder
5.39
NYPJM->LTFIMP_NY
CLTF
3.275
LGEELTFEXP_LGEE->PJM
CLTF
2.092
WECLTFEXP_WEC->PJM
CLTF
1.123
CPLELTFEXP_CPLE->PJM
CLTF
5
LAGNLTFEXP_LAGN->PJM
CLTF
6.94
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.695
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.759
TVALTFEXP_TVA->PJM
CLTF
3.494
MECLTFEXP_MEC->PJM
CLTF
5.118
SIGELTFEXP_SIGE->PJM
CLTF
0.161
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.1

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.88 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:1802.21
MW Contribution:
1.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
Adder
0.136
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.172
3147043LAWRENC
Solar/Wind Harmer
0.044
3147043LAWRENC
Adder
0.663
3147133PAMPLIN
Solar/Wind Harmer
0.226
3147133PAMPLIN
Solar/Wind Harmer
0.058
3147133PAMPLIN
Solar/Wind Harmer
0.072
20390526W1-045 C
Solar/Wind Helper
0.253
20671828STAW2-080
Solar/Wind Helper
0.015
20671928W4-073
Solar/Wind Helper
0.052
20673628F1S_V4-069
Solar/Wind Helper
0.017
20673728F2S_V4-070
Solar/Wind Helper
0.017
20673828FLE_V3-070
Solar/Wind Helper
0.05
20674128FR_U2-059
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20674628WNG_W3-110
Solar/Wind Helper
0.051
20674828DL_W4-046
Solar/Wind Helper
0.005
20674928WA_W3-044
Solar/Wind Helper
0.057
20675128HRM_W1-127
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
20675528CPH_W2-050
Solar/Wind Helper
0.066
20675728RH_W2-091
Solar/Wind Helper
0.047
20675828AU_W4-064
Solar/Wind Helper
0.017
20675928HOL_W4-097
Solar/Wind Helper
0.029
20676128MHD_W3-029
Solar/Wind Helper
0.056
20676228FRD_X1-012
Solar/Wind Helper
0.053
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20676428JCR_X2-075
Solar/Wind Helper
0.039
20676728BRNX1-095
Solar/Wind Helper
0.017
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
20714928UPF_X1-085
Solar/Wind Helper
0.003
20715028HAN_X4-015
Solar/Wind Helper
0.034
20715228NPK_W1-113
Solar/Wind Helper
0.046
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
20716028EGP_W2-019
Solar/Wind Helper
0.011
20716928W4-060COL
Solar/Wind Helper
0.03
20720528MAN_W1-024
Solar/Wind Helper
0.017
20720628TIN_W1-124
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.034
20720828JCB_W4-025
Solar/Wind Helper
0.037
207408W3-077 C
Solar/Wind Helper
0.048
207439AE1-081 C O1
Solar/Wind Helper
0.011
214067T20SOLAR
Solar/Wind Helper
0.007
217206BARNGR HS C
Solar/Wind Helper
0.004
217208PARK ELE C
Solar/Wind Helper
0.003
217209CENTRL HS C
Solar/Wind Helper
0.005
217211CAMDEN ST C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.017
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
232410W1-006 C
Solar/Wind Helper
0.305
232417X3-008 C
Solar/Wind Helper
0.14
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.204
23777801MSM_W1-116
Solar/Wind Helper
0.131
23777901MDS_W4-102
Solar/Wind Helper
0.106
3137176SLIGO L2192
Solar/Wind Harmer
0.318
3140676OCCOQUN
50/50
0.016
3141346CRANES
50/50
0.127
3141426STAFORD
Solar/Wind Harmer
0.023
3141843SHACKLE
Adder
0.431
3141906WESTMOR
Solar/Wind Harmer
0.036
3142296MT RD221
Adder
0.27
3142366NRTHEST
Adder
0.275
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.82
3142416OLDCHRC
Solar/Wind Harmer
0.084
3142433PROV 92
Solar/Wind Harmer
0.336
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3143096IRON208
Adder
0.344
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.351
3143316POE
Solar/Wind Harmer
0.321
3143336POWHATN
Solar/Wind Harmer
1.41
3143336POWHATN
Solar/Wind Harmer
1.198
3144216WINCHST
Adder
0.309
3144356SAPONY
Solar/Wind Harmer
0.656
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.192
3145506HICKORY
Solar/Wind Harmer
0.048
3146386ELIZ CT
Solar/Wind Harmer
0.079
3146396TANGLEW
Solar/Wind Harmer
0.218
3146776BUCKING
Solar/Wind Harmer
0.293
3146776BUCKING
Solar/Wind Harmer
0.024
3146776BUCKING
Solar/Wind Harmer
0.026
3146776BUCKING
Solar/Wind Harmer
0.029
3150071POSSM 5
50/50
52.154
3150081POSSM6A
50/50
0.849
3150091POSSM6B
50/50
0.849
3150101POSSM6S
50/50
1.293
3150151POSSMC1
50/50
1.141
3150151POSSMC1
50/50
1.141
3150151POSSMC1
50/50
1.141
3150181POSSMC2
50/50
1.141
3150181POSSMC2
50/50
1.141
3150181POSSMC2
50/50
1.151
3150211REMNGT1
50/50
13.121
3150221REMNGT2
50/50
13.208
3150231REMNGT3
50/50
0.781
3150241REMNGT4
50/50
13.296
3150281M RUN A
Adder
13.337
3150291M RUN B
Adder
13.23
3150301M RUN C
Adder
13.329
3150331BIRCHWDA
Adder
16.601
3150341NORNECKC1
Adder
0.905
3150341NORNECKC1
Adder
0.912
3150351NORNECKC2
Adder
0.883
3150351NORNECKC2
Adder
0.868
3150391LDYSMT3
Adder
12.635
3150401LDYSMT4
Adder
12.659
3150411LDYSMT5
Adder
12.698
3150671DARBY 1
Adder
6.03
3150681DARBY 2
Adder
6.037
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
3150921YORKTN3
Adder
2.065
209027LOR2_Q27
Solar/Wind Helper
0.559
212266LOR1
Solar/Wind Helper
0.163
217081WEATEXAS C
Solar/Wind Helper
0.007
217169METRODIV C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217202FBANKSOLAR C
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
218438BLK ROCK C
Solar/Wind Helper
0.016
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219249CENTRALDIV C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219276PARKLANDSO C
Solar/Wind Helper
0.052
219291REEVESSOUT C
Solar/Wind Helper
0.007
219348LDSOLAR C
Solar/Wind Helper
0.068
219607WPEMNERT C
Solar/Wind Helper
0.047
219612MATRIX C
Solar/Wind Helper
0.014
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
235020AA1-095 C
Solar/Wind Helper
0.029
3150981CHESPKA
Adder
1.005
3150991CHESPKB
Adder
0.823
3150991CHESPKB
Adder
0.843
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
3151101ELIZAR3
Adder
7.476
3151171GRAVELC
Adder
0.867
3151171GRAVELC
Adder
1.14
3151191GRAVEL3
Adder
5.855
3151201GRAVEL4
Adder
5.93
3151211GRAVEL5
Adder
5.855
3151221GRAVEL6
Adder
5.923
3151731LOISA B
Adder
5.59
3151751LOISA D
Adder
5.59
3151761LOISA E
Adder
11.397
3151861LOWMORA
Adder
0.644
3151861LOWMORA
Adder
0.618
3151881LOWMORC
Adder
0.628
3151881LOWMORC
Adder
0.639
3152111X4-039 GT1
50/50
1.844
3152121X4-039 GT2
50/50
1.832
3152131X4-039 ST
50/50
2.883
316075AC2-137 C
Solar/Wind Harmer
0.022
228728W1-130C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Harmer
0.025
3138133OCRAN
Solar/Wind Harmer
0.051
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3141766HARMONY
Solar/Wind Harmer
1.127
3141766HARMONY
Solar/Wind Harmer
0.017
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3141813NORNECK
Solar/Wind Harmer
0.087
3141913WHIT STONE
Solar/Wind Harmer
0.085
3143226MDLTHAN
Solar/Wind Harmer
0.083
3143873LANEXA
Solar/Wind Harmer
0.051
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.077
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
3146456SLIGO L269
Solar/Wind Harmer
1.414
3146456SLIGO L269
Solar/Wind Harmer
0.08
3146456SLIGO L269
Solar/Wind Harmer
0.08
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.255
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
3146926FARMVIL
Solar/Wind Harmer
0.044
3146926FARMVIL
Solar/Wind Harmer
0.044
3147346CASHSCORNER
Solar/Wind Harmer
0.196
3147666LOUISA
Solar/Wind Harmer
0.355
3147666LOUISA
Solar/Wind Harmer
0.204
3147983MERCK5
Solar/Wind Harmer
0.024
232406W1-004 FULL
Solar/Wind Helper
0.305
232436AB1-176 C
Solar/Wind Helper
0.027
3141726DUNNSVL
Solar/Wind Harmer
0.347
3145663CRESWEL
Solar/Wind Harmer
0.214
316034AC1-036 C
Solar/Wind Harmer
0.005
316036AC1-147 C
Solar/Wind Harmer
0.014
316159AE1-175 C
Solar/Wind Harmer
0.071
316246AF1-032 C
Solar/Wind Harmer
0.036
316258AE1-075 C
Solar/Wind Harmer
0.059
316315AB2-025 C
Solar/Wind Harmer
0.063
316316AC1-027 C
Solar/Wind Harmer
0.077
316336AC2-165 C
Solar/Wind Harmer
3.964
223402AF1-300 C
Solar/Wind Helper
0.398
230415AB2-049 C
Solar/Wind Helper
0.018
20742028HF_AC1-207
Solar/Wind Helper
0.082
207454AA2-184 E
Solar/Wind Helper
0.181
207459AE1-142 C O1
Solar/Wind Helper
0.17
207471AF2-354 C
Solar/Wind Helper
0.097
208835TUHI V3-051
Solar/Wind Helper
0.017
208835TUHI V3-051
Solar/Wind Helper
0.017
232424Y1-079 C
Solar/Wind Helper
0.07
3150371LDYSMT1
Adder
12.232
3150381LDYSMT2
Adder
12.153
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
226910AB2-157 C
Solar/Wind Helper
0.021
233901CHERRYDALE C
Solar/Wind Helper
0.14
233940AF2-379 C
Solar/Wind Helper
0.037
212507AE2-042_GEN
Solar/Wind Helper
0.831
219907AC1-030 C
Solar/Wind Helper
0.02
237025AB1-124 C
Solar/Wind Helper
0.194
237030AB1-096 C
Solar/Wind Helper
0.079
237038AE2-054 C
Solar/Wind Helper
0.174
3130156CHOWAN
Solar/Wind Harmer
0.077
3130156CHOWAN
Solar/Wind Harmer
0.077
3130156CHOWAN
Solar/Wind Harmer
0.077
3145336SMITFLD
Solar/Wind Harmer
0.324
3145336SMITFLD
Solar/Wind Harmer
0.032
3148133STUARTS
Solar/Wind Harmer
0.039
3141196NOKESVL
Solar/Wind Harmer
0.428
3147243WELCO
Solar/Wind Harmer
0.042
3141873WAN 176
Solar/Wind Harmer
1.502
3141873WAN 176
Solar/Wind Harmer
0.017
3143526WINTERP
Solar/Wind Harmer
0.434
3143526WINTERP
Solar/Wind Harmer
0.434
316404AE1-155 C
Solar/Wind Harmer
0
316017AA1-139 ULT1
Solar/Wind Harmer
0.043
316181AB2-040 GEN
Solar/Wind Harmer
0.105
316033AB2-134 GEN
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Helper
0.015
316388AE2-253 GEN
Solar/Wind Harmer
0.249
235062AE1-101 C1
Solar/Wind Helper
1.069
205956AE1-196_GEN
Solar/Wind Helper
0.386
217204WCALDSOLAR C
Solar/Wind Helper
0.002
3148013FISHERV
Solar/Wind Harmer
0.037
3148013FISHERV
Solar/Wind Harmer
0.065
3145176PASQUOTANK
Solar/Wind Harmer
0.049
3132123MT JACKSON
Solar/Wind Harmer
0.182
3132273ORANGE
Solar/Wind Harmer
0.018
3142543TWELFTH
Solar/Wind Harmer
0.008
3144303KENBRDG
Solar/Wind Harmer
0.057
3147173SINAI
Solar/Wind Harmer
0.067
3148463FAIRFLD
Solar/Wind Harmer
0.06
237080AD1-060 GEN
Solar/Wind Helper
0.222
235067AD1-061 GEN
Solar/Wind Helper
0.282
237001AB1-127_GEN
Solar/Wind Helper
0.308
237002AB1-128_GEN
Solar/Wind Helper
0.299
238221AF1-254 C O1
Solar/Wind Helper
0.18
316203AE2-005 GEN
Solar/Wind Harmer
0
237085AD2-009_GEN
Solar/Wind Helper
0.975
316494AC1-189 GEN
Solar/Wind Harmer
0.237
316005AA1-067
Solar/Wind Harmer
0.076
233944AB2-135 GEN
Solar/Wind Helper
0.357
233946AB2-136 GEN
Solar/Wind Helper
0.343
316426AA2-053 GEN
Solar/Wind Harmer
0.245
316327AA2-057 GEN
Solar/Wind Harmer
0.104
3156081AA2-088 GEN
Solar/Wind Harmer
0
233994AC2-023 GEN
Solar/Wind Helper
0.579
315614AA2-178 GEN
Solar/Wind Harmer
0.435
315816AE2-034 GEN
Solar/Wind Harmer
0.327
316312AB1-027
Solar/Wind Harmer
0.15
316049AB1-081 GEN
Solar/Wind Harmer
0.392
316011AB1-132 GEN
Solar/Wind Harmer
1.331
315651AD1-115 GEN
Solar/Wind Harmer
0
316023GEN1_S
Solar/Wind Harmer
0.167
316365GEN2_N
Solar/Wind Harmer
0.167
237006AB1-125 GEN
Solar/Wind Helper
0.146
23779801AA1-109
Solar/Wind Helper
0.218
316463AE2-346 GEN
Solar/Wind Harmer
0.064
233982AB2-133 GEN
Solar/Wind Helper
0.218
233915AB1-141 GEN
Solar/Wind Helper
0.305
233918AB1-142 GEN
Solar/Wind Helper
0.305
315821AE2-092 GEN
Solar/Wind Harmer
0
315814AE2-033 C
Solar/Wind Harmer
6.193
315671AE2-027_GEN
Solar/Wind Harmer
0.001
315747AE2-019 GEN
50/50
13.161
233930AB2-032 GEN
Solar/Wind Helper
0.231
233987AB2-037 GEN
Solar/Wind Helper
1.413
315673AE1-157 GEN
Solar/Wind Harmer
6.386
315813AE1-149 C
Solar/Wind Harmer
4.327
315683AE1-153 C
Solar/Wind Harmer
7.208
315742AE1-103 GEN
Solar/Wind Harmer
1.163
319010AE1-072 C
Solar/Wind Harmer
0.398
316065AD1-022 GEN
Solar/Wind Harmer
3.468
315697AD1-025 GEN
Solar/Wind Harmer
0.088
233933AB2-153 GEN
Solar/Wind Helper
0.141
315773AC2-141 GEN
Solar/Wind Harmer
2.95
233935AB2-179 C
Solar/Wind Helper
0.775
315732AD1-074 GEN1
Solar/Wind Harmer
0.431
315733AD1-074 GEN2
Solar/Wind Harmer
0.431
315735AD1-075 GEN1
Solar/Wind Harmer
0.215
315737AD1-076 GEN
Solar/Wind Harmer
0.97
316473AC1-191 GEN
Solar/Wind Harmer
0.29
316478AD1-087 GEN
Solar/Wind Harmer
0.251
316486AD2-202 GEN
Solar/Wind Harmer
0.074
316447AC1-158 HLD
Solar/Wind Harmer
1.006
316044AC1-158 PL1
Solar/Wind Harmer
0.458
316045AC1-158 PL2
Solar/Wind Harmer
1.464
316450AC1-158 RIC
Solar/Wind Harmer
0.122
316072AD1-144
Solar/Wind Harmer
0.029
315778AD1-151 GEN
Solar/Wind Harmer
6.568
316156AD2-030 GEN
Solar/Wind Harmer
0.062
315785AD2-033 C
Solar/Wind Harmer
0.577
316337AD2-073 GEN
Solar/Wind Harmer
0.076
234015AF2-250 C
Solar/Wind Helper
0.023
234036AF2-325 C
Solar/Wind Helper
0.025
207484AF2-139 C O1
Solar/Wind Helper
0.048
207510AF2-138 C
Solar/Wind Helper
0.047
207518AF1-320_GEN
Solar/Wind Helper
0.902
207442AE1-156 GEN
Solar/Wind Helper
0.189
226929AD2-058 GEN
Solar/Wind Helper
0.144
207437AD2-070 GEN
Solar/Wind Helper
0.079
209054AE2-059 GEN
Solar/Wind Helper
0.043
313526AB2-022
Solar/Wind Harmer
0.042
316313AB2-026
Solar/Wind Harmer
0.049
207445AB1-138_GEN
Solar/Wind Helper
0.061
209071AE2-133 GEN
Solar/Wind Helper
0.042
209116AE2-175 GEN
Solar/Wind Helper
1.008
3145513AHOSKIE
Solar/Wind Harmer
0.074
3145513AHOSKIE
Solar/Wind Harmer
0.156
233923SMA
Solar/Wind Helper
0.453
230433AD2-135 GEN
Solar/Wind Helper
0.01
219680HOPEWELLV C1
Solar/Wind Helper
0.002
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
219908AB1-139 C
Solar/Wind Helper
0.043
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219258KINSLEYDEP C
Solar/Wind Helper
0.046
219304NAMERICA C
Solar/Wind Helper
0.078
219921AF1-264
Solar/Wind Helper
0.03
203975AE1-071-GEN
Solar/Wind Helper
1.719
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
207530AG1-191 GEN
Solar/Wind Helper
0.038
230511AF1-262
Solar/Wind Helper
0.009
205932AD2-116_GEN
Solar/Wind Helper
0.386
205941AD2-115 GEN
Solar/Wind Helper
0.303
205943AE1-185 GEN
Solar/Wind Helper
0.388
205917AD1-020 ES
Solar/Wind Helper
0.319
205916AD1-020 GEN
Solar/Wind Helper
1.485
270494AE1-108_GEN
Solar/Wind Harmer
0.797
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3147623JAMES R
Solar/Wind Harmer
0.166
209067AE2-060 GEN
Solar/Wind Helper
0.042
209137AF2-361 C
Solar/Wind Helper
0.711
3150011OMF A
50/50
0.213
3150021OMF B
50/50
0.213
3146206CASHIE
Solar/Wind Harmer
0.075
3146206CASHIE
Solar/Wind Harmer
0.075
3146206CASHIE
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
316274AC1-208 GEN
Solar/Wind Harmer
0.369
316349AD2-085 GEN
Solar/Wind Harmer
0.053
3156021HOLLOMANSOL
Solar/Wind Harmer
0.335
315652AC1-086 GEN
Solar/Wind Harmer
8.072
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316359AB2-059 GEN
Solar/Wind Harmer
0.245
316131AB2-060 GEN
Solar/Wind Harmer
0.221
316192AB2-158 GEN
Solar/Wind Harmer
0.497
316132AB2-190 GEN1
Solar/Wind Harmer
0.439
316458AB2-190 GEN2
Solar/Wind Harmer
0.439
316263AC1-034 GEN
Solar/Wind Harmer
2.619
316129AC1-054 GEN
Solar/Wind Harmer
0.267
316123AC1-075 GEN
Solar/Wind Harmer
0.082
316210AC1-098 GEN
Solar/Wind Harmer
0.664
316212AC1-099_GEN
Solar/Wind Harmer
0.37
316118AC1-105 GEN
Solar/Wind Harmer
0.174
316254AC1-120 GEN1
Solar/Wind Harmer
3.292
316170AC1-121 GEN2
Solar/Wind Harmer
1.13
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316375AC2-012 GEN
Solar/Wind Harmer
0
316311AC2-079 GEN
Solar/Wind Harmer
2.299
316283AC2-100 C
Solar/Wind Harmer
0.124
316339AD2-160 GEN
Solar/Wind Harmer
0.128
316164AC1-076 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.026
316223AC1-118
Solar/Wind Harmer
0.064
316294AC1-161 GEN
Solar/Wind Harmer
1.396
315975AC1-164 GENB
Solar/Wind Harmer
0.026
315976AC1-164 GENA
Solar/Wind Harmer
0.883
316169AC1-164_GENC
Solar/Wind Harmer
0.763
316381AD1-082 GEN
Solar/Wind Harmer
0.082
316233AE1-074 FULL
Solar/Wind Harmer
0.067
316093AE2-104_GEN
Solar/Wind Harmer
1.34
315607AA1-063A GEN
Solar/Wind Harmer
0.149
3150851SPRUNCC
Adder
0.385
3150861SPRUNCD
Adder
0.385
230434AG1-499 GEN
Solar/Wind Helper
0.137
233964AF2-378 GEN
Solar/Wind Helper
0.025
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.055
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.148
207511W3-106 GEN
Solar/Wind Helper
0.015
208972BECR K09
Solar/Wind Helper
0.178
209029WAYMART-WD
Solar/Wind Helper
0.444
223401AF1-299 GEN
Solar/Wind Helper
0.398
230407AD2-065 C
Solar/Wind Helper
0.024
232432Z2-076 GEN
Solar/Wind Helper
0.04
232434Z2-077 GEN
Solar/Wind Helper
0.076
233996TM1833_GEN
Solar/Wind Helper
0.124
233997TMININ_4.2
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
3130086AYDLETT
Solar/Wind Harmer
0.319
3137643SOCKMAN
Solar/Wind Harmer
0.293
3138126ROCKLANDING
Solar/Wind Harmer
0.038
3138216PACIFIC
Solar/Wind Harmer
0.025
3138266HYDRAULIC
Solar/Wind Harmer
0.002
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138543CONSLDL
Solar/Wind Harmer
0.046
3142053HEARTS
Solar/Wind Harmer
0.121
3142946ENON
Solar/Wind Harmer
0.008
3142946ENON
Solar/Wind Harmer
0.028
3144536CHRHLND
Solar/Wind Harmer
0.012
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145453TOT5
Solar/Wind Harmer
0.097
3145493TOT1
Solar/Wind Harmer
0.309
3145493TOT1
Solar/Wind Harmer
0.161
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
3145603CNETO
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.073
3145783HORNRTN
Solar/Wind Harmer
1.297
3145783HORNRTN
Solar/Wind Harmer
1.037
3145783HORNRTN
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.218
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
3145823KELFORD
Solar/Wind Harmer
0.073
3145823KELFORD
Solar/Wind Harmer
0.073
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
0.135
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.334
3145893MURPHYS
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.203
3145933PARMELE
Solar/Wind Harmer
0.143
3145933PARMELE
Solar/Wind Harmer
0.072
3145933PARMELE
Solar/Wind Harmer
0.072
3145963POPLR C
Solar/Wind Harmer
0.073
3145963POPLR C
Solar/Wind Harmer
0.073
3146033SCOT NK
Solar/Wind Harmer
0.29
3146043SEABORD
Solar/Wind Harmer
0.074
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.277
3146233WITAKRS
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.074
3146263WOODLND
Solar/Wind Harmer
0.074
3146293MARTNCO
Solar/Wind Harmer
0.066
3146406KITTY HAWK
Solar/Wind Harmer
0.01
316321Z2-027
Solar/Wind Harmer
0.014
942461AE2-259 GEN
Solar/Wind Harmer
0
942751AE2-291 GEN
Solar/Wind Harmer
3.269
944011AF1-069 GEN
Solar/Wind Harmer
4.7
944491AF1-114 GEN
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
18.116
944591AF1-124 GEN
Solar/Wind Harmer
18.181
944601AF1-125 GEN
Solar/Wind Harmer
17.837
944631AF1-128 GEN
Adder
39.784
944641AF1-129 GEN
Adder
39.347
946301AF1-294 GEN
Solar/Wind Harmer
1.421
946691AF1-333 GEN
Solar/Wind Helper
0.234
946731AF1-337 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
946751AF1-339 GEN
Solar/Wind Helper
0.234
959311AF2-222 GEN
Solar/Wind Harmer
6.364
959381AF2-229 GEN
Solar/Wind Helper
0.257
959421AF2-233 GEN
Solar/Wind Helper
0.233
959431AF2-234 GEN
Solar/Wind Helper
0.467
959561AF2-247 GEN
Solar/Wind Helper
0.012
960081AF2-299 GEN
Solar/Wind Harmer
0.713
961261AF2-417 GEN
Solar/Wind Helper
0.241
961301AF2-421 GEN
Solar/Wind Helper
0.242
961331AF2-424 GEN
Solar/Wind Helper
0.237
961341AF2-425 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.237
961431AF2-434 GEN
Solar/Wind Helper
0.237
961601AG1-000A GEN
Solar/Wind Harmer
1.225
961601AG1-000A GEN
Solar/Wind Harmer
4.902
961611AG1-000B GEN
Solar/Wind Harmer
4.282
961611AG1-000B GEN
Solar/Wind Harmer
2.178
961671AG1-007 GEN
Solar/Wind Harmer
0.011
961791AG1-021 GEN
Solar/Wind Harmer
0.691
962561AG1-105 GEN
Solar/Wind Harmer
3.315
962571AG1-106 GEN
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
2.759
963151AG1-164 GEN
Solar/Wind Helper
0.242
963161AG1-165 GEN
Solar/Wind Helper
0.242
966871AG1-558 GEN
Solar/Wind Harmer
0.099
966881AG1-559 GEN
Solar/Wind Harmer
0.105
970053AG2-049 GEN
50/50
2.019
970085AG2-068 GEN
Solar/Wind Harmer
3.973
970087AG2-069 GEN
Solar/Wind Harmer
5.959
970099AG2-077 GEN
Solar/Wind Harmer
7.893
970117AG2-086 GEN
Solar/Wind Harmer
1.398
970117AG2-086 GEN
Solar/Wind Harmer
0.932
970133AG2-095 GEN
Solar/Wind Harmer
0.793
970189AG2-124 GEN
Solar/Wind Harmer
2.502
970221AG2-151 GEN
Solar/Wind Harmer
3.81
970257AG2-171 GEN
Solar/Wind Harmer
2.288
970293AG2-193 GEN
Solar/Wind Harmer
0.898
970301AG2-198 GEN
Solar/Wind Harmer
3.132
970323AG2-213 GEN
Solar/Wind Harmer
3.051
970401AG2-262 GEN
Solar/Wind Harmer
0.403
970533AG2-339 GEN
Solar/Wind Harmer
5.901
970581AG2-369 GEN
Solar/Wind Harmer
3.417
970601AG2-382 GEN
Solar/Wind Harmer
2.806
970657AG2-426 GEN
Solar/Wind Harmer
1.809
970657AG2-426 GEN
Solar/Wind Harmer
0.592
970673AG2-436 GEN
Solar/Wind Harmer
9.667
970681AG2-440 GEN
Solar/Wind Harmer
2.871
970683AG2-441 GEN
Solar/Wind Harmer
4.325
970685AG2-442 GEN
Solar/Wind Harmer
5.367
970831AG2-522 GEN
Solar/Wind Harmer
3.061
970917AG2-570 GEN
Solar/Wind Harmer
6.668
970919AG2-571 GEN
Solar/Wind Harmer
2.667
970933AG2-581 GEN
Solar/Wind Harmer
6.095
970937AG2-583 GEN
Solar/Wind Harmer
4.632
971065AG2-659 GEN
Solar/Wind Harmer
3.047
971069AG2-661 GEN
Solar/Wind Harmer
1.459
971153AH1-033 GEN
Solar/Wind Harmer
0.924
971163AH1-040 GEN
Solar/Wind Harmer
6.123
971223AH1-071 GEN
Solar/Wind Harmer
0.889
971281AH1-106 GEN
Solar/Wind Harmer
1.159
971283AH1-107 GEN
Solar/Wind Harmer
1.159
971285AH1-108 GEN
Adder
0.63
971317AH1-138 GEN
Solar/Wind Harmer
0.617
971377AH1-170 GEN
Solar/Wind Harmer
0.762
971445AH1-216 GEN
Solar/Wind Harmer
5.713
971455AH1-223 GEN
Solar/Wind Harmer
2.31
971547AH1-271 GEN
Solar/Wind Harmer
1.603
971563AH1-280 GEN
Solar/Wind Harmer
0.768
971623AH1-311 GEN
Solar/Wind Harmer
0.138
971683AH1-343 GEN
Solar/Wind Harmer
2.374
971685AH1-345 GEN
Solar/Wind Harmer
0.729
219918AC2-009 C
Solar/Wind Helper
0.001
227287AC2-120 GEN
Solar/Wind Helper
0.492
939411AE1-173 GEN
Solar/Wind Harmer
34.104
940641AE2-051 GEN
Solar/Wind Harmer
6.384
941031AE2-094 GEN
Solar/Wind Harmer
14.385
957481AF2-042 GEN
Solar/Wind Harmer
19.733
957861AF2-080 GEN
Solar/Wind Harmer
3.026
957871AF2-081 GEN
Solar/Wind Harmer
3.983
957921AF2-086 GEN
Solar/Wind Helper
0.234
958211AF2-115 GEN
Solar/Wind Harmer
0.864
958261AF2-120 GEN
Solar/Wind Harmer
2.855
963691AG1-221 GEN
Solar/Wind Harmer
2.31
963711AG1-223 GEN
Solar/Wind Helper
0.037
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
964241AG1-285 GEN
Solar/Wind Harmer
4.743
964791AG1-342 GEN
Solar/Wind Harmer
1.319
964851AG1-348 GEN
Solar/Wind Helper
0.036
966001AG1-469 GEN
Solar/Wind Harmer
0.051
971761AH1-387 GEN
Solar/Wind Harmer
1.229
971775AH1-396 GEN
Solar/Wind Harmer
0.114
971777AH1-397 GEN
Solar/Wind Harmer
0.223
971781AH1-399 GEN
Solar/Wind Harmer
0.117
971845AH1-439 GEN
Solar/Wind Harmer
3.318
971967AH1-528 GEN
Solar/Wind Harmer
12.296
972003AH1-546 GEN
Solar/Wind Harmer
2.538
972135AH1-637 GEN
Solar/Wind Harmer
0.78
972185AH1-677 GEN
Adder
4.323
972187AH1-678 GEN
Adder
2.18
972189AH1-679 GEN
Adder
1.465
972193AH1-681 GEN
Adder
1.64
972195AH1-682 GEN
Adder
1.66
972197AH1-683 GEN
Adder
1.977
972199AH1-684 GEN
50/50
2.016
972201AH1-685 GEN
50/50
2.279
972205AH1-687 GEN
Adder
3.128
972213AH1-691 GEN
Adder
2.056
972215AH1-692 GEN
Adder
2.056
972217AH1-693 GEN
50/50
1.753
972219AH1-694 GEN
Adder
1.423
972223AH1-696 GEN
50/50
9.014
972255AH1-712 GEN
Adder
36.701
972277AH1-723 GEN
Adder
42.768
233950AC2-186 GEN
Solar/Wind Helper
0.07
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
315722AD1-056 GEN
Solar/Wind Harmer
2.442
315724AD1-057 GEN
Solar/Wind Harmer
1.362
315835AF2-110_GEN
Solar/Wind Harmer
0.547
232422X3-066 FULL
Solar/Wind Helper
0.069
315693AD1-088 GEN
Solar/Wind Harmer
3.538
219919AE1-041 FULL
Solar/Wind Helper
0.002
219912AD2-042 GEN
Solar/Wind Helper
0.089
219914AD2-027 C
Solar/Wind Helper
0.068
235063AE1-101 C2
Solar/Wind Helper
1.069
3151721LOISA A
Adder
5.561
NYPJM->LTFIMP_NY
CLTF
2.582
LGEELTFEXP_LGEE->PJM
CLTF
1.798
WECLTFEXP_WEC->PJM
CLTF
0.958
CPLELTFEXP_CPLE->PJM
CLTF
5.053
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.329
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.822
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.552
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.532
TVALTFEXP_TVA->PJM
CLTF
3.177
MECLTFEXP_MEC->PJM
CLTF
4.431
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.46 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1925.78
MW Contribution:
3.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
Adder
0.11
3144293JTRSVLE
Adder
0.139
3144293JTRSVLE
Adder
0.139
3144293JTRSVLE
Adder
0.139
3147043LAWRENC
Solar/Wind Harmer
-0.004
3147043LAWRENC
Adder
0.529
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3147133PAMPLIN
Solar/Wind Harmer
-0.007
20390526W1-045 C
Solar/Wind Helper
0.278
20671828STAW2-080
Solar/Wind Helper
0.015
20671928W4-073
Solar/Wind Helper
0.051
20673628F1S_V4-069
Solar/Wind Helper
0.017
20673728F2S_V4-070
Solar/Wind Helper
0.017
20673828FLE_V3-070
Solar/Wind Helper
0.05
20674128FR_U2-059
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20674628WNG_W3-110
Solar/Wind Helper
0.051
20674828DL_W4-046
Solar/Wind Helper
0.005
20674928WA_W3-044
Solar/Wind Helper
0.056
20675128HRM_W1-127
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
20675528CPH_W2-050
Solar/Wind Helper
0.065
20675728RH_W2-091
Solar/Wind Helper
0.047
20675828AU_W4-064
Solar/Wind Helper
0.017
20675928HOL_W4-097
Solar/Wind Helper
0.029
20676128MHD_W3-029
Solar/Wind Helper
0.055
20676228FRD_X1-012
Solar/Wind Helper
0.052
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20676428JCR_X2-075
Solar/Wind Helper
0.039
20676728BRNX1-095
Solar/Wind Helper
0.017
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20714828MDF_W3-079
Solar/Wind Helper
0.076
20714928UPF_X1-085
Solar/Wind Helper
0.003
20715028HAN_X4-015
Solar/Wind Helper
0.033
20715228NPK_W1-113
Solar/Wind Helper
0.045
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
20716028EGP_W2-019
Solar/Wind Helper
0.011
20716928W4-060COL
Solar/Wind Helper
0.03
20720528MAN_W1-024
Solar/Wind Helper
0.016
20720628TIN_W1-124
Solar/Wind Helper
0.11
20720728JCB_W1-129
Solar/Wind Helper
0.033
20720828JCB_W4-025
Solar/Wind Helper
0.037
207408W3-077 C
Solar/Wind Helper
0.048
207439AE1-081 C O1
Solar/Wind Helper
0.011
214067T20SOLAR
Solar/Wind Helper
0.007
217206BARNGR HS C
Solar/Wind Helper
0.004
217208PARK ELE C
Solar/Wind Helper
0.003
217209CENTRL HS C
Solar/Wind Helper
0.005
217211CAMDEN ST C
Solar/Wind Helper
0.003
217213AMBOY SO C
Solar/Wind Helper
0.017
232404W1-003 C
Solar/Wind Helper
0.306
232408W1-005 C
Solar/Wind Helper
0.306
232410W1-006 C
Solar/Wind Helper
0.306
232417X3-008 C
Solar/Wind Helper
0.14
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.204
23777801MSM_W1-116
Solar/Wind Helper
0.157
23777901MDS_W4-102
Solar/Wind Helper
0.113
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3141346CRANES
Adder
0.082
3141426STAFORD
Solar/Wind Harmer
-0.002
3141843SHACKLE
Adder
0.329
3141906WESTMOR
Solar/Wind Harmer
-0.003
3142296MT RD221
Adder
0.206
3142366NRTHEST
Adder
0.211
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
0.733
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142956BIRDNECK
Solar/Wind Harmer
0.377
3143096IRON208
Adder
0.264
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.27
3143316POE
Solar/Wind Harmer
-0.028
3143336POWHATN
Solar/Wind Harmer
0.84
3143336POWHATN
Solar/Wind Harmer
0.714
3144216WINCHST
Adder
0.239
3144356SAPONY
Solar/Wind Harmer
0.241
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3146396TANGLEW
Solar/Wind Harmer
0.128
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3146776BUCKING
Solar/Wind Harmer
-0.002
3146776BUCKING
Solar/Wind Harmer
-0.003
3150071POSSM 5
Adder
32.531
3150151POSSMC1
Adder
0.712
3150151POSSMC1
Adder
0.712
3150151POSSMC1
Adder
0.712
3150181POSSMC2
Adder
0.712
3150181POSSMC2
Adder
0.712
3150181POSSMC2
Adder
0.718
3150211REMNGT1
Adder
10.853
3150221REMNGT2
Adder
10.925
3150241REMNGT4
Adder
10.998
3150281M RUN A
Adder
11.691
3150291M RUN B
Adder
11.597
3150301M RUN C
Adder
11.683
3150331BIRCHWDA
Adder
11.656
3150341NORNECKC1
Adder
0.678
3150341NORNECKC1
Adder
0.683
3150351NORNECKC2
Adder
0.661
3150351NORNECKC2
Adder
0.65
3150391LDYSMT3
Adder
9.161
3150401LDYSMT4
Adder
9.178
3150411LDYSMT5
Adder
9.207
3150671DARBY 1
Adder
4.621
3150681DARBY 2
Adder
4.627
3150691DARBY 3
Adder
4.643
3150701DARBY 4
Adder
4.632
3150921YORKTN3
Adder
1.594
209027LOR2_Q27
Solar/Wind Helper
0.551
212266LOR1
Solar/Wind Helper
0.16
217081WEATEXAS C
Solar/Wind Helper
0.007
217169METRODIV C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217202FBANKSOLAR C
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
218438BLK ROCK C
Solar/Wind Helper
0.016
218440SUMMTASSOC C
Solar/Wind Helper
0.009
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219249CENTRALDIV C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219276PARKLANDSO C
Solar/Wind Helper
0.052
219291REEVESSOUT C
Solar/Wind Helper
0.007
219348LDSOLAR C
Solar/Wind Helper
0.067
219607WPEMNERT C
Solar/Wind Helper
0.047
219612MATRIX C
Solar/Wind Helper
0.014
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
235020AA1-095 C
Solar/Wind Helper
0.031
3150981CHESPKA
Adder
0.782
3150991CHESPKB
Adder
0.641
3150991CHESPKB
Adder
0.656
3151081ELIZAR1
Adder
5.744
3151091ELIZAR2
Adder
5.644
3151101ELIZAR3
Adder
5.817
3151171GRAVELC
Adder
0.672
3151171GRAVELC
Adder
0.883
3151191GRAVEL3
Adder
4.537
3151201GRAVEL4
Adder
4.595
3151211GRAVEL5
Adder
4.537
3151221GRAVEL6
Adder
4.59
3151731LOISA B
Adder
4.646
3151751LOISA D
Adder
4.646
3151761LOISA E
Adder
9.471
3152111X4-039 GT1
50/50
1.834
3152121X4-039 GT2
50/50
1.822
3152131X4-039 ST
50/50
2.868
316075AC2-137 C
Solar/Wind Harmer
0.195
316077AC2-138 C
Solar/Wind Harmer
0.154
228728W1-130C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Harmer
-0.002
3138133OCRAN
Solar/Wind Harmer
-0.004
3138283WHITEMARSH
Solar/Wind Harmer
0.011
3141766HARMONY
Solar/Wind Harmer
0.644
3141766HARMONY
Solar/Wind Harmer
-0.001
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
3141813NORNECK
Solar/Wind Harmer
-0.007
3141913WHIT STONE
Solar/Wind Harmer
-0.007
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3143873LANEXA
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
3146456SLIGO L269
Solar/Wind Harmer
0.827
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146926FARMVIL
Solar/Wind Harmer
-0.004
3147346CASHSCORNER
Solar/Wind Harmer
0.123
3147666LOUISA
Solar/Wind Harmer
-0.032
3147666LOUISA
Solar/Wind Harmer
-0.018
232406W1-004 FULL
Solar/Wind Helper
0.306
232436AB1-176 C
Solar/Wind Helper
0.027
3141726DUNNSVL
Solar/Wind Harmer
-0.029
3145663CRESWEL
Solar/Wind Harmer
-0.019
316034AC1-036 C
Solar/Wind Harmer
0.12
316036AC1-147 C
Solar/Wind Harmer
0.189
316059AD1-063 C
Solar/Wind Harmer
0.163
316159AE1-175 C
Solar/Wind Harmer
0.192
316240AF1-291 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.141
316258AE1-075 C
Solar/Wind Harmer
0.171
316305AF2-043 C
Solar/Wind Harmer
0.21
316314AB2-024 C
Solar/Wind Harmer
0.618
316315AB2-025 C
Solar/Wind Harmer
0.186
316316AC1-027 C
Solar/Wind Harmer
0.215
316317KELFORD C
Solar/Wind Harmer
0.304
316336AC2-165 C
Solar/Wind Harmer
4.383
316382AG1-145 C
Solar/Wind Harmer
0.215
316405AF2-144 C
Solar/Wind Harmer
0.181
223402AF1-300 C
Solar/Wind Helper
0.386
230415AB2-049 C
Solar/Wind Helper
0.018
20742028HF_AC1-207
Solar/Wind Helper
0.082
207454AA2-184 E
Solar/Wind Helper
0.18
207459AE1-142 C O1
Solar/Wind Helper
0.169
207471AF2-354 C
Solar/Wind Helper
0.096
208835TUHI V3-051
Solar/Wind Helper
0.017
208835TUHI V3-051
Solar/Wind Helper
0.017
232424Y1-079 C
Solar/Wind Helper
0.07
3150371LDYSMT1
Adder
8.868
3150381LDYSMT2
Adder
8.811
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
226910AB2-157 C
Solar/Wind Helper
0.014
233901CHERRYDALE C
Solar/Wind Helper
0.14
233940AF2-379 C
Solar/Wind Helper
0.037
212507AE2-042_GEN
Solar/Wind Helper
0.818
219907AC1-030 C
Solar/Wind Helper
0.02
237025AB1-124 C
Solar/Wind Helper
0.234
237030AB1-096 C
Solar/Wind Helper
0.095
237038AE2-054 C
Solar/Wind Helper
0.191
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145336SMITFLD
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.003
3141196NOKESVL
Solar/Wind Harmer
-0.043
3141873WAN 176
Solar/Wind Harmer
0.858
3141873WAN 176
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.038
3143526WINTERP
Solar/Wind Harmer
-0.038
316411AF1-147_GEN1
Solar/Wind Harmer
1.073
316415AF1-147_GEN2
Solar/Wind Harmer
1.073
316404AE1-155 C
Solar/Wind Harmer
1.394
316017AA1-139 ULT1
Solar/Wind Harmer
0.565
316018AA1-139 ULT2
Solar/Wind Harmer
0.599
316181AB2-040 GEN
Solar/Wind Harmer
0.919
316033AB2-134 GEN
Solar/Wind Harmer
2.294
228754AB1-001 C
Solar/Wind Helper
0.015
316388AE2-253 GEN
Solar/Wind Harmer
0.471
235062AE1-101 C1
Solar/Wind Helper
1.173
205956AE1-196_GEN
Solar/Wind Helper
0.407
217204WCALDSOLAR C
Solar/Wind Helper
0.002
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
3142543TWELFTH
Solar/Wind Harmer
-0.001
3144303KENBRDG
Solar/Wind Harmer
-0.005
237080AD1-060 GEN
Solar/Wind Helper
0.243
235067AD1-061 GEN
Solar/Wind Helper
0.308
237001AB1-127_GEN
Solar/Wind Helper
0.343
237002AB1-128_GEN
Solar/Wind Helper
0.332
238221AF1-254 C O1
Solar/Wind Helper
0.198
316203AE2-005 GEN
Solar/Wind Harmer
3.049
316441AF1-014 GEN
Solar/Wind Harmer
0.488
237085AD2-009_GEN
Solar/Wind Helper
1.053
233944AB2-135 GEN
Solar/Wind Helper
0.358
233946AB2-136 GEN
Solar/Wind Helper
0.343
316426AA2-053 GEN
Solar/Wind Harmer
0.662
316190AA2-174 GEN
Solar/Wind Harmer
0.081
3156081AA2-088 GEN
Solar/Wind Harmer
2.18
233994AC2-023 GEN
Solar/Wind Helper
0.58
315614AA2-178 GEN
Solar/Wind Harmer
0.729
315816AE2-034 GEN
Solar/Wind Harmer
0.546
316312AB1-027
Solar/Wind Harmer
0.244
316011AB1-132 GEN
Solar/Wind Harmer
1.372
316369SG1_INVT
Solar/Wind Harmer
1.27
315651AD1-115 GEN
Solar/Wind Harmer
3.931
316023GEN1_S
Solar/Wind Harmer
0.45
316365GEN2_N
Solar/Wind Harmer
0.45
237006AB1-125 GEN
Solar/Wind Helper
0.175
23779801AA1-109
Solar/Wind Helper
0.262
316463AE2-346 GEN
Solar/Wind Harmer
0.107
315839AE2-212 C
Solar/Wind Harmer
0.214
233982AB2-133 GEN
Solar/Wind Helper
0.218
233915AB1-141 GEN
Solar/Wind Helper
0.305
233918AB1-142 GEN
Solar/Wind Helper
0.305
315821AE2-092 GEN
Solar/Wind Harmer
1.353
315814AE2-033 C
Solar/Wind Harmer
6.429
315671AE2-027_GEN
Solar/Wind Harmer
1.289
315747AE2-019 GEN
50/50
12.529
233930AB2-032 GEN
Solar/Wind Helper
0.231
233987AB2-037 GEN
Solar/Wind Helper
1.415
315662AE1-191 GEN
Solar/Wind Harmer
0.87
315666AE1-190 GEN
Solar/Wind Harmer
0.217
315673AE1-157 GEN
Solar/Wind Harmer
5.701
315813AE1-149 C
Solar/Wind Harmer
4.424
315683AE1-153 C
Solar/Wind Harmer
8.072
315742AE1-103 GEN
Solar/Wind Harmer
1.629
319010AE1-072 C
Solar/Wind Harmer
1.412
316065AD1-022 GEN
Solar/Wind Harmer
3.346
315697AD1-025 GEN
Solar/Wind Harmer
1.438
316185AD1-033 GEN
Solar/Wind Harmer
0.74
233933AB2-153 GEN
Solar/Wind Helper
0.141
315773AC2-141 GEN
Solar/Wind Harmer
2.954
316280AD1-041 GEN
Solar/Wind Harmer
0.544
233935AB2-179 C
Solar/Wind Helper
0.776
315732AD1-074 GEN1
Solar/Wind Harmer
1.354
315733AD1-074 GEN2
Solar/Wind Harmer
1.354
315735AD1-075 GEN1
Solar/Wind Harmer
0.677
315737AD1-076 GEN
Solar/Wind Harmer
1.273
316473AC1-191 GEN
Solar/Wind Harmer
0.787
316478AD1-087 GEN
Solar/Wind Harmer
0.565
316486AD2-202 GEN
Solar/Wind Harmer
0.166
316447AC1-158 HLD
Solar/Wind Harmer
1.872
316044AC1-158 PL1
Solar/Wind Harmer
0.851
316045AC1-158 PL2
Solar/Wind Harmer
2.723
316450AC1-158 RIC
Solar/Wind Harmer
0.227
316468AD1-105 GEN
Solar/Wind Harmer
0.85
316072AD1-144
Solar/Wind Harmer
0.142
315778AD1-151 GEN
Solar/Wind Harmer
6.347
316156AD2-030 GEN
Solar/Wind Harmer
0.193
316337AD2-073 GEN
Solar/Wind Harmer
0.198
234015AF2-250 C
Solar/Wind Helper
0.023
234036AF2-325 C
Solar/Wind Helper
0.026
207484AF2-139 C O1
Solar/Wind Helper
0.048
207510AF2-138 C
Solar/Wind Helper
0.046
207518AF1-320_GEN
Solar/Wind Helper
0.895
207442AE1-156 GEN
Solar/Wind Helper
0.188
226929AD2-058 GEN
Solar/Wind Helper
0.079
207437AD2-070 GEN
Solar/Wind Helper
0.079
209054AE2-059 GEN
Solar/Wind Helper
0.042
313526AB2-022
Solar/Wind Harmer
0.187
316313AB2-026
Solar/Wind Harmer
0.19
207445AB1-138_GEN
Solar/Wind Helper
0.061
209071AE2-133 GEN
Solar/Wind Helper
0.042
209116AE2-175 GEN
Solar/Wind Helper
0.998
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145513AHOSKIE
Solar/Wind Harmer
0.058
233923SMA
Solar/Wind Helper
0.454
230433AD2-135 GEN
Solar/Wind Helper
0.01
219680HOPEWELLV C1
Solar/Wind Helper
0.002
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219908AB1-139 C
Solar/Wind Helper
0.043
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219304NAMERICA C
Solar/Wind Helper
0.077
219921AF1-264
Solar/Wind Helper
0.03
203975AE1-071-GEN
Solar/Wind Helper
1.876
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
207530AG1-191 GEN
Solar/Wind Helper
0.038
230511AF1-262
Solar/Wind Helper
0.009
205932AD2-116_GEN
Solar/Wind Helper
0.407
205941AD2-115 GEN
Solar/Wind Helper
0.303
205943AE1-185 GEN
Solar/Wind Helper
0.41
205917AD1-020 ES
Solar/Wind Helper
0.358
205916AD1-020 GEN
Solar/Wind Helper
1.663
3147623JAMES R
Solar/Wind Harmer
0.103
209067AE2-060 GEN
Solar/Wind Helper
0.042
209137AF2-361 C
Solar/Wind Helper
0.706
3146206CASHIE
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316349AD2-085 GEN
Solar/Wind Harmer
0.622
3156021HOLLOMANSOL
Solar/Wind Harmer
0.892
315652AC1-086 GEN
Solar/Wind Harmer
7.388
313506AB2-031 GEN
Solar/Wind Harmer
0.529
316006AB2-029 C
Solar/Wind Harmer
0.548
316322AB2-045
Solar/Wind Harmer
0.225
316192AB2-158 GEN
Solar/Wind Harmer
0.957
316083AB2-161 GEN
Solar/Wind Harmer
1.144
316174AB2-169 GEN
Solar/Wind Harmer
1.007
316087AB2-174 GEN
Solar/Wind Harmer
0.941
316132AB2-190 GEN1
Solar/Wind Harmer
0.72
316458AB2-190 GEN2
Solar/Wind Harmer
0.72
316254AC1-120 GEN1
Solar/Wind Harmer
3.304
316170AC1-121 GEN2
Solar/Wind Harmer
1.101
316375AC2-012 GEN
Solar/Wind Harmer
2.434
316311AC2-079 GEN
Solar/Wind Harmer
3.535
316339AD2-160 GEN
Solar/Wind Harmer
0.471
316164AC1-076 GEN
Solar/Wind Harmer
0.727
316140AB2-099
Solar/Wind Harmer
0.045
316223AC1-118
Solar/Wind Harmer
0.2
316294AC1-161 GEN
Solar/Wind Harmer
2.283
315975AC1-164 GENB
Solar/Wind Harmer
0.049
315976AC1-164 GENA
Solar/Wind Harmer
1.643
316169AC1-164_GENC
Solar/Wind Harmer
1.419
316381AD1-082 GEN
Solar/Wind Harmer
0.645
316233AE1-074 FULL
Solar/Wind Harmer
0.196
316236AE1-162_GEN
Solar/Wind Harmer
0.213
316093AE2-104_GEN
Solar/Wind Harmer
2.03
315607AA1-063A GEN
Solar/Wind Harmer
0.667
3150851SPRUNCC
Adder
0.297
3150861SPRUNCD
Adder
0.297
230434AG1-499 GEN
Solar/Wind Helper
0.136
233964AF2-378 GEN
Solar/Wind Helper
0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.054
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
207511W3-106 GEN
Solar/Wind Helper
0.015
208972BECR K09
Solar/Wind Helper
0.176
209029WAYMART-WD
Solar/Wind Helper
0.438
223401AF1-299 GEN
Solar/Wind Helper
0.386
230407AD2-065 C
Solar/Wind Helper
0.024
232432Z2-076 GEN
Solar/Wind Helper
0.04
232434Z2-077 GEN
Solar/Wind Helper
0.076
233996TM1833_GEN
Solar/Wind Helper
0.124
233997TMININ_4.2
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138126ROCKLANDING
Solar/Wind Harmer
0.022
3138216PACIFIC
Solar/Wind Harmer
-0.003
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3142946ENON
Solar/Wind Harmer
-0.001
3142946ENON
Solar/Wind Harmer
-0.002
3144536CHRHLND
Solar/Wind Harmer
-0.001
3144873MCLAUGH
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
-0.007
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.621
3145783HORNRTN
Solar/Wind Harmer
0.194
3145783HORNRTN
Solar/Wind Harmer
0.078
3145796HORNRTN
Solar/Wind Harmer
-0.019
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3145823KELFORD
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.186
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
0.198
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.026
3146043SEABORD
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.693
315800Z1-036_GEN1
Solar/Wind Harmer
1.693
316318V4-068
Solar/Wind Harmer
0.166
316320Y1-086
Solar/Wind Harmer
0.408
316321Z2-027
Solar/Wind Harmer
0.187
942461AE2-259 GEN
Solar/Wind Harmer
0.995
944011AF1-069 GEN
Solar/Wind Harmer
4.06
944491AF1-114 GEN
Solar/Wind Harmer
2.202
944581AF1-123 GEN
Solar/Wind Harmer
32.014
944591AF1-124 GEN
Solar/Wind Harmer
32.129
944601AF1-125 GEN
Solar/Wind Harmer
31.514
944631AF1-128 GEN
Adder
30.58
944641AF1-129 GEN
Adder
30.387
946281AF1-292 GEN
Solar/Wind Harmer
0.149
946301AF1-294 GEN
Solar/Wind Harmer
1.679
946691AF1-333 GEN
Solar/Wind Helper
0.23
946731AF1-337 GEN
Solar/Wind Helper
0.23
946741AF1-338 GEN
Solar/Wind Helper
0.23
946751AF1-339 GEN
Solar/Wind Helper
0.23
959311AF2-222 GEN
Solar/Wind Harmer
6.794
959381AF2-229 GEN
Solar/Wind Helper
0.283
959421AF2-233 GEN
Solar/Wind Helper
0.23
959431AF2-234 GEN
Solar/Wind Helper
0.459
959561AF2-247 GEN
Solar/Wind Helper
0.012
960081AF2-299 GEN
Solar/Wind Harmer
0.746
961261AF2-417 GEN
Solar/Wind Helper
0.239
961301AF2-421 GEN
Solar/Wind Helper
0.239
961331AF2-424 GEN
Solar/Wind Helper
0.234
961341AF2-425 GEN
Solar/Wind Helper
0.234
961421AF2-433 GEN
Solar/Wind Helper
0.233
961431AF2-434 GEN
Solar/Wind Helper
0.233
961611AG1-000B GEN
Solar/Wind Harmer
3.506
961611AG1-000B GEN
Solar/Wind Harmer
1.496
961791AG1-021 GEN
Solar/Wind Harmer
0.819
961941AG1-037 GEN
Solar/Wind Harmer
0.05
961951AG1-038 GEN
Solar/Wind Harmer
0.96
962571AG1-106 GEN
Solar/Wind Harmer
0.944
962861AG1-135 GEN
Solar/Wind Harmer
2.737
963151AG1-164 GEN
Solar/Wind Helper
0.239
963161AG1-165 GEN
Solar/Wind Helper
0.239
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
966881AG1-559 GEN
Solar/Wind Harmer
0.227
966881AG1-559 GEN
Solar/Wind Harmer
0.078
970053AG2-049 GEN
Adder
1.473
970085AG2-068 GEN
Solar/Wind Harmer
4.162
970087AG2-069 GEN
Solar/Wind Harmer
6.243
970099AG2-077 GEN
Solar/Wind Harmer
8.303
970133AG2-095 GEN
Solar/Wind Harmer
0.806
970221AG2-151 GEN
Solar/Wind Harmer
4.15
970257AG2-171 GEN
Solar/Wind Harmer
0.153
970293AG2-193 GEN
Solar/Wind Harmer
0.906
970301AG2-198 GEN
Solar/Wind Harmer
3.329
970323AG2-213 GEN
Solar/Wind Harmer
3.251
970533AG2-339 GEN
Solar/Wind Harmer
4.647
970581AG2-369 GEN
Solar/Wind Harmer
3.579
970601AG2-382 GEN
Solar/Wind Harmer
2.923
970657AG2-426 GEN
Solar/Wind Harmer
1.423
970657AG2-426 GEN
Solar/Wind Harmer
0.444
970673AG2-436 GEN
Solar/Wind Harmer
15.054
970681AG2-440 GEN
Solar/Wind Harmer
3.06
970683AG2-441 GEN
Solar/Wind Harmer
4.61
970685AG2-442 GEN
Solar/Wind Harmer
5.722
970917AG2-570 GEN
Solar/Wind Harmer
16.739
970919AG2-571 GEN
Solar/Wind Harmer
2.119
970933AG2-581 GEN
Solar/Wind Harmer
6.362
970937AG2-583 GEN
Solar/Wind Harmer
4.944
971069AG2-661 GEN
Solar/Wind Harmer
1.128
971153AH1-033 GEN
Solar/Wind Harmer
0.81
971163AH1-040 GEN
Solar/Wind Harmer
6.349
971223AH1-071 GEN
Solar/Wind Harmer
0.911
971281AH1-106 GEN
Solar/Wind Harmer
1.182
971283AH1-107 GEN
Solar/Wind Harmer
1.182
971285AH1-108 GEN
Adder
0.486
971317AH1-138 GEN
Solar/Wind Harmer
0.894
971377AH1-170 GEN
Solar/Wind Harmer
0.83
971445AH1-216 GEN
Solar/Wind Harmer
4.378
971455AH1-223 GEN
Solar/Wind Harmer
2.258
971547AH1-271 GEN
Solar/Wind Harmer
1.67
971563AH1-280 GEN
Solar/Wind Harmer
0.819
971685AH1-345 GEN
Solar/Wind Harmer
0.836
219918AC2-009 C
Solar/Wind Helper
0.001
227287AC2-120 GEN
Solar/Wind Helper
0.31
316431W1029_GEN1
Solar/Wind Harmer
1.256
316433W1029_GEN2
Solar/Wind Harmer
1.256
316435W1029_GEN3
Solar/Wind Harmer
1.256
939411AE1-173 GEN
Solar/Wind Harmer
35.115
940641AE2-051 GEN
Solar/Wind Harmer
6.583
941031AE2-094 GEN
Solar/Wind Harmer
12.958
957481AF2-042 GEN
Solar/Wind Harmer
20.758
957601AF2-054 GEN
Solar/Wind Harmer
0.216
957831AF2-077 GEN
Solar/Wind Harmer
0.216
957871AF2-081 GEN
Solar/Wind Harmer
3.504
957921AF2-086 GEN
Solar/Wind Helper
0.231
957971AF2-091 GEN
Solar/Wind Harmer
0.749
958211AF2-115 GEN
Solar/Wind Harmer
1.024
958261AF2-120 GEN
Solar/Wind Harmer
2.829
963691AG1-221 GEN
Solar/Wind Harmer
2.258
963711AG1-223 GEN
Solar/Wind Helper
0.037
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
964211AG1-282 GEN
Solar/Wind Harmer
0.22
964851AG1-348 GEN
Solar/Wind Helper
0.036
966001AG1-469 GEN
Solar/Wind Harmer
0.153
966621AG1-532 GEN
Solar/Wind Harmer
0.135
971761AH1-387 GEN
Solar/Wind Harmer
3.866
971777AH1-397 GEN
Solar/Wind Harmer
0.844
971781AH1-399 GEN
Solar/Wind Harmer
0.458
971845AH1-439 GEN
Solar/Wind Harmer
3.565
971967AH1-528 GEN
Solar/Wind Harmer
12.837
972003AH1-546 GEN
Solar/Wind Harmer
2.743
972135AH1-637 GEN
Solar/Wind Harmer
0.749
972185AH1-677 GEN
Adder
3.415
972187AH1-678 GEN
Adder
1.725
972189AH1-679 GEN
Adder
1.102
972193AH1-681 GEN
Adder
1.345
972195AH1-682 GEN
Adder
1.204
972197AH1-683 GEN
Adder
1.433
972199AH1-684 GEN
Adder
1.667
972201AH1-685 GEN
Adder
1.885
972205AH1-687 GEN
Adder
2.57
972213AH1-691 GEN
Adder
1.49
972215AH1-692 GEN
Adder
1.49
972217AH1-693 GEN
Adder
1.45
972219AH1-694 GEN
Adder
1.032
972223AH1-696 GEN
Adder
5.622
972255AH1-712 GEN
Adder
30.111
972277AH1-723 GEN
Adder
35.088
233950AC2-186 GEN
Solar/Wind Helper
0.07
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
315835AF2-110_GEN
Solar/Wind Harmer
0.873
232422X3-066 FULL
Solar/Wind Helper
0.069
315693AD1-088 GEN
Solar/Wind Harmer
3.317
316487AF1-042 GEN
Solar/Wind Harmer
0.96
315833AF1-017_GEN
Solar/Wind Harmer
1.331
316484AD2-074 GEN
Solar/Wind Harmer
1.834
219919AE1-041 FULL
Solar/Wind Helper
0.002
219912AD2-042 GEN
Solar/Wind Helper
0.089
219914AD2-027 C
Solar/Wind Helper
0.068
235063AE1-101 C2
Solar/Wind Helper
1.173
3151721LOISA A
Adder
4.622
NYPJM->LTFIMP_NY
CLTF
2.537
LGEELTFEXP_LGEE->PJM
CLTF
1.748
WECLTFEXP_WEC->PJM
CLTF
0.938
CPLELTFEXP_CPLE->PJM
CLTF
4.221
LAGNLTFEXP_LAGN->PJM
CLTF
5.819
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.807
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.589
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.743
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.752
TVALTFEXP_TVA->PJM
CLTF
2.93
MECLTFEXP_MEC->PJM
CLTF
4.279
SIGELTFEXP_SIGE->PJM
CLTF
0.135

Details for 8FRONT ROYAL-8MORRSVL 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-404T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8FRONT ROYAL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-404T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.67 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3241.91
MW Contribution:
6.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23503301WHY_Z2-039
50/50
0.009
23503901LHY_Z2-039
50/50
0.005
23544701WINZ1-113
50/50
1.004
23503401SHY_Z2-039
50/50
0.005
23503501NHY_Z2-039
50/50
0.007
3141426STAFORD
Solar/Wind Helper
0.056
3152511MT STM1
50/50
2.142
3152511MT STM1
50/50
2.159
3152521MT STM2
50/50
2.2
3152521MT STM2
50/50
2.21
3152531MT STM3
50/50
4.175
3152541MT STMG
50/50
1.739
3152701WARREN G1
50/50
6.32
3152711WARREN G2
50/50
6.32
3152721WARREN G3
50/50
6.32
3152731WARREN S1
50/50
11.831
3147666LOUISA
Solar/Wind Helper
0.959
3147666LOUISA
Solar/Wind Helper
0.551
3141196NOKESVL
Solar/Wind Helper
1.175
316411AF1-147_GEN1
Solar/Wind Helper
0.812
316415AF1-147_GEN2
Solar/Wind Helper
0.812
3132123MT JACKSON
Solar/Wind Harmer
0.416
3132273ORANGE
Solar/Wind Helper
0.05
238223AG1-045 C
Solar/Wind Harmer
4.626
315651AD1-115 GEN
Solar/Wind Helper
1.013
23583801GRNGAP
Solar/Wind Harmer
0
316447AC1-158 HLD
Solar/Wind Helper
3.972
316044AC1-158 PL1
Solar/Wind Helper
1.805
316045AC1-158 PL2
Solar/Wind Helper
5.776
316450AC1-158 RIC
Solar/Wind Helper
0.481
316006AB2-029 C
Solar/Wind Helper
0.16
316192AB2-158 GEN
Solar/Wind Helper
1.604
316164AC1-076 GEN
Solar/Wind Helper
1.414
3138216PACIFIC
Solar/Wind Helper
0.038
966881AG1-559 GEN
Solar/Wind Helper
0.31
970117AG2-086 GEN
Solar/Wind Harmer
3.188
970117AG2-086 GEN
Solar/Wind Harmer
2.126
970459AG2-300 GEN
50/50
18.964
971513AH1-254 GEN
Solar/Wind Harmer
5.736
971569AH1-283 GEN
Solar/Wind Harmer
15.971
964441AG1-307 GEN
Solar/Wind Harmer
5.813
964441AG1-307 GEN
Solar/Wind Harmer
0.969
965471AG1-415 GEN
Solar/Wind Harmer
4.218
971761AH1-387 GEN
Solar/Wind Harmer
6.622
972257AH1-713 GEN
50/50
2.046
NYPJM->LTFIMP_NY
CLTF
1.24
LGEELTFEXP_LGEE->PJM
CLTF
1.482
WECLTFEXP_WEC->PJM
CLTF
0.842
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.195
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.335
LAGNLTFEXP_LAGN->PJM
CLTF
2.295
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.928
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.031
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.984
TVALTFEXP_TVA->PJM
CLTF
1.145
MECLTFEXP_MEC->PJM
CLTF
3.343
SIGELTFEXP_SIGE->PJM
CLTF
0.108
CONTINGENCY 'AP_P2-3_PE-500-019F_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1          /*BRIGHTON     500.0 - 01DOUBS      500.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 2          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 4          /*01DOUBS      500.0 - 01DOUBS      230.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 1                  /*01DOUBS      500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
END
CONTINGENCY 'PEPCO_P1_5070_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P1-2_PE-500-404T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235110 TO BUS 313440 CKT 1   /*01MDWBRK     500.0 - 8VINTHIL     500.0
END
314290 to 223938 ckt 1
313911 to 314290 ckt 1
314929 to 314916 ckt 1

Winter Peak Analysis

The New Service Request AH1-387 was evaluated as a 150.0 MW (22.05 MW Capacity) injection in the APS area.

AH1-387 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-387 was evaluated as a 150.0 MW injection

AH1-387 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

The new Service Requests (projects) in PJM Transition Cycle 2, Cluster 66 are listed in Table 1 below. This report will cover the dynamic analysis of the Cluster 66 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 66 projects will meet the dynamics requirements of the NERC, FirstEnergy (FE), and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2028 summer peak load case, modified to include applicable projects. The Cluster 66 projects are set at maximum power output, with approximately unity power factor at the high side of the station transformers. The voltage magnitudes at the projects’ generator terminals and POI buses are given in Table 2.

The Cluster 66 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 196 contingencies were studied, each with a 20 second simulation time period (with 1.0 second initial run prior to any events). Studied faults included:

  1. Steady-state operation (Category P0);
  2. Three-phase faults with normal clearing time (Category P1);
  3. Single-phase faults with stuck breaker (Category P4);
  4. Single phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);
  5. Single phase to ground faults with normal clearing for common structure (Category P7).

High Speed Reclosing (HSR) facilities were found in the vicinity of the TC2 Cluster 66 projects. For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2028 peak load case:

  1. The Cluster 66 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with the Cluster 66 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

In the initial simulations, the AG2-300 generator tripped on high terminal voltage for contingencies P5.01, P5.08, P5.09, P5.10, P5.18, and P5.22. The plant is modeled with REECC1/REPCA1 controls and VTGTPAT voltage protection, with REECC1 Vup = 1.10 pu and three VTGTPAT overvoltage protection instances set at 1.11 pu / 10.0 s, 1.21 pu / 0.16 s, and 1.30 pu / 0.05 s. Based on documentation for the inverter type, the parameter Vup was adjusted to 1.20 pu, and no further trips were observed after this adjustment.

No other mitigation was required for TC2 Cluster 66. 

 

Table 1: TC2 Cluster 66 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO (MW)

MWE (MW)

MWC (MW)

Point of Interconnection

66

AG2-300

Storage

FirstEnergy (FE) transmission system, Allegheny Power Systems (APS) zone

100

100

70

Meadow Brook 138 kV

66

AH1-254

Wind

FirstEnergy (FE) transmission system, Allegheny Power Systems (APS) zone

171.4

171.4

36.538

Greenland Gap 500 kV II

66

AH1-283

Solar

FirstEnergy (FE) transmission system, Allegheny Power Systems (APS) zone

200

200

120

Mount Storm-Pruntytown 500kV

66

AH1-387

Wind

FirstEnergy (FE) transmission system, Allegheny Power Systems (APS) zone

150

150

22.05

Meadowbrook-Greenland Gap 500kV

 

Reactive Power Analysis

The reactive power capability of AH1-387 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

(No dependencies were identified)

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

Not ContingentTopology Changing

Note 1: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8MORRSVL-8FRONT ROYAL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.11
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.11
Title
Replace Bells Mill T3 XF with new PEPCO standard 260 MVA 230/138 kV transformer.
Description
Replace Bells Mill T3 XF with new PEPCO standard 260 MVA 230/138 kV transformer. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.10
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.10
Title
Replace one stranded bus conductor, three thermal relays, two disconnect switches at Quince Orchard 230 kV substation.
Description
Replace one stranded bus conductor, three thermal relays, two disconnect switches at Quince Orchard 230 kV substation. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.9
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.9
Title
Replace two breakers, one bushing CT, one stranded bus conductor, four disconnect switches at Brighton 500 kV substation.
Description
Replace two breakers, one bushing CT, one stranded bus conductor, four disconnect switches at Brighton 500 kV substation.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.8
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.8
Title
Relocate Dickerson "D"-Quince Orchard 23035 to terminate at Dickerson "H" at Dickerson No. 2 tie location.
Description
Relocate Dickerson "D"-Quince Orchard 23035 to terminate at Dickerson "H" at Dickerson No. 2 tie location. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.7
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.7
Title
Install 3.2% 230 kV series reactor at Dickerson "H" terminal side of the Edwards Ferry-Dickerson circuit.
Description
Install 3.2% 230 kV series reactor at Dickerson "H" terminal side of the Edwards Ferry-Dickerson circuit. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.6
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4052.6
Title
Aspen 500 kV remote work for Dickerson (new 500 kV) - Aspen line
Description
Aspen 500 kV remote work for Dickerson (new 500 kV) - Aspen line (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4052.5
Title
Rocky Point 500 kV remote work for Dickerson (new 500 kV)-Rocky Point line
Description
Rocky Point 500 kV remote work for Dickerson (new 500 kV)-Rocky Point line. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.1
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.1
Title
New 500/230 kV substation (Dickerson) by cutting into the Aspen-Rocky Point 500 kV line
Description
New 500/230 kV substation (Dickerson) by cutting into the Aspen-Rocky Point 500 kV line. (2025-W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.4
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.4
Title
Aspen-Dickerson (new 500 kV) termination work at Dickerson 500 kV
Description
Aspen-Dickerson (new 500 kV) termination work at Dickerson 500 kV (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.3
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.3
Title
Rocky Point-Dickerson (new 500 kV) termination work at Dickerson 500 kV
Description
Rocky Point-Dickerson (new 500 kV) termination work at Dickerson 500 kV (2025 W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.2
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.2
Title
Install two 500/230 kV transformers connecting a new 500 kV Dickerson station and DIckeson "H" 230 kV station including 230 kV substation work.
Description
Install two 500/230 kV transformers connecting a new 500 kV Dickerson station and DIckeson "H" 230 kV station including 230 kV substation work. (2025 W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-387 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-387 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-387


AH1-387 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-387 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-387 One Line Diagram

AH1-387 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.