AH1-460 Phase II System Impact Study Report

v1.00 released 2026-06-03 17:59

Hooversville - Scalp Level 115 kV

39.6 MW Capacity / 66.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Julius Energy, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Mid-Atlantic Interstate Transmission, LLC.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request meets the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposits refunded. See Readiness Deposit calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $74,614,360 $31,356,595 = 2.38 AND ( $74,614,360 - $31,356,595 ) 66.0 = $655,421 per MW

General

The Project Developer has proposed a Solar generating facility located in the Mid-Atlantic Interstate Transmission, LLC zone — Somerset County, Pennsylvania. The installed facilities will have a total capability of 66.0 MW with 39.6 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-460
Project Name:
Hooversville - Scalp Level 115 kV
Project Developer Name:
Julius Energy, LLC
State:
Pennsylvania
County:
Somerset
Transmission Owner:
Mid-Atlantic Interstate Transmission, LLC
MFO:
66.0
MWE:
66.0
MWC:
39.6
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-460 will interconnect on the Mid-Atlantic Interstate Transmission, LLC  transmission system on the Hooversville - Rachel Hill 115 kV line between Hooversville and Scalp Level.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-460 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-460Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$1,931,406$0$0
Other Scope$475,724$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$16,761,420$16,761,420$16,761,420
Network Upgrades$3,231,754$3,231,754$3,231,754
System Reliability Network Upgrades
Steady State Thermal & Voltage$54,621,186$54,621,186$54,621,186
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$77,021,490$74,614,360$74,614,360

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-460

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-460
Project ID: AH1-460
20% of cost allocation for Phase II Network Upgrades:(A) $14,922,872
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $3,135,660
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $11,787,212
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install new relays and revise relay settings at Rachel Hill Substation. Remove back-up relaying, wave trap, line tuner, and associated equipment on the Hooversville terminal.

$435,513$28,292$7,872$198$471,875$471,875
(Pending)

Install new relays and revise relay settings at Hooversville Substation. Remove back-up relaying, wave trap, line tuner, and associated equipment on the Rachel Hill terminal.

$435,513$28,292$7,872$198$471,875$471,875
(Pending)

Install new relays and revise relay settings at Scalp Level.

$474,563$16,962$8,578$119$500,222$500,222
(Pending)

Loop Hooversville-Rachel Hill 115kV HH Line into the proposed AH1-460 interconnection station, approximately 3.65 miles from the Scalp Level Tap and 3.35 miles from Hooversville 115 kV Substation.

$1,515,950$236,115$27,401$8,316$1,787,782$1,787,782
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install 115 kV revenue metering equipment within new interconnection substation.

$324,997$143,846$5,874$1,007$475,724$475,724
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Construct a new 115 kV three (3) breaker ring bus interconnection substation.

$10,908,419$3,216,464$197,170$27,376$14,349,429$14,349,429
(Pending)

Install/test approximately 3.35 miles of new 96F/SM ADSS fiber from the AH1-460 substation control house to a new splice point on the “Riser to Quemahoning” fiber cable.

$1,597,021$241,820$28,866$1,693$1,869,400$1,869,400
(Pending)

Design, install, test and commission MPLS equipment for SCADA transport at AH1-460 substation.

$360,022$120,148$6,507$841$487,518$487,518
(Pending)

Install two in-subtation fibers from the new AH1-460 substation to the Point of Change in Ownership.

$51,675$2,447$934$17$55,073$55,073
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install line terminal equipment within the AH1-460 interconnection substation. Install up to 0.1 miles of conductor from AH1-460 interconnection substation to the Project Developer-owned dead-end structure outside of TO substation fence.

$1,484,118$366,108$26,825$4,961$1,882,012$1,882,012
(Pending)

Integrate Interconnection Facilities protection and controls to the Transmission Owner system.

$48,517$0$877$0$49,394$49,394
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install new relays and revise relay settings at Rachel Hill Substation. Remove back-up relaying, wave trap, line tuner, and associated equipment on the Hooversville terminal.

$435,513$28,292$7,872$198$471,875$471,875
(Pending)

Install new relays and revise relay settings at Hooversville Substation. Remove back-up relaying, wave trap, line tuner, and associated equipment on the Rachel Hill terminal.

$435,513$28,292$7,872$198$471,875$471,875
(Pending)

Install new relays and revise relay settings at Scalp Level.

$474,563$16,962$8,578$119$500,222$500,222
(Pending)

Loop Hooversville-Rachel Hill 115kV HH Line into the proposed AH1-460 interconnection station, approximately 3.65 miles from the Scalp Level Tap and 3.35 miles from Hooversville 115 kV Substation.

$1,515,950$236,115$27,401$8,316$1,787,782$1,787,782
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Oversight of Project Developer design and construction of new interconnection substation.

$1,292,001$0$23,353$0$1,315,354$1,315,354
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install 115 kV revenue metering equipment within new interconnection substation.

$324,997$143,846$5,874$1,007$475,724$475,724
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install/test approximately 3.35 miles of new 96F/SM ADSS fiber from the AH1-460 substation control house to a new splice point on the “Riser to Quemahoning” fiber cable.

$1,597,021$241,820$28,866$1,693$1,869,400$1,869,400
(Pending)

Install one (1) security system and camera system. Install one (1) indoor security AC cabinet. Install one (1) network fiber termination rack. Program SCADA RTU.

$1,724,201$266,194$31,165$1,863$2,023,423$2,023,423
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Integrate Interconnection Facilities protection and controls to the Transmission Owner system.

$48,517$0$877$0$49,394$49,394
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$22,400,304$22,400,304
Developer Build Option$8,965,049$8,965,049

Based on the scope of work for the Interconnection Facilities, it is expected to take 42 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

FE performed an analysis of its underlying transmission system <100 kV. New Service Request Project AH1-460 did not contribute to any overloads on the FE transmission <100 kV system.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-460 was evaluated as a 66.0 MW (39.6 MW Capacity) injection in the PENELEC area.

AH1-460 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 66.0 MW (66.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0252-A_SRT-A
BreakerAC108.34 %160.0B173.34
5.87
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0252-C_SRT-A
BreakerAC108.34 %160.0B173.34
5.87
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0252-B_SRT-A
BreakerAC108.34 %160.0B173.34
5.87
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0201A-20_SRT-A
BreakerAC107.65 %160.0B172.25
5.86
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
BreakerAC106.48 %160.0B170.37
5.46
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0183-209_SRT-A
BreakerAC105.72 %160.0B169.16
6.04
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P7-1_MP-138-018_SRT-SL
TowerAC104.82 %160.0B167.71
5.23
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC104.57 %160.0B167.31
5.86
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_M_SRT-A
BreakerAC104.31 %160.0B166.9
5.36
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-2_WP-138-033T_SRT-A
BusAC102.48 %160.0B163.98
5.52
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC101.45 %160.0B162.32
5.34
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P7-1_MP-138-056_SRT-A-1
TowerAC101.25 %160.0B162.0
5.29
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_10_P42_100570_SRT-A
BreakerAC118.4 %618.0B731.74
5.1
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-500-004-DRT-008_SRT-SL
BreakerAC117.56 %618.0B726.55
5.51
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-500-DRT31_SRT-SL
BreakerAC117.56 %618.0B726.55
5.51
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_10_P42_100569_SRT-A
BreakerAC117.1 %618.0B723.67
5.13
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-115-0331-A_SRT-A
BreakerAC116.98 %618.0B722.93
5.53
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-115-0331-B_SRT-A
BreakerAC116.86 %618.0B722.22
5.54
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-2_PN-115-030_SRT-A
BusAC109.75 %618.0B678.27
5.55
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-2_PN-115-031_SRT-A
BusAC108.41 %618.0B670.0
5.41
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC105.99 %618.0B655.0
6.41
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_08_P22_102799_SRT-A
BusAC102.88 %618.0B635.79
4.95
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_10_P22_100579_SRT-A
BusAC102.35 %618.0B632.54
4.85
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_48_P71_102649_SRT-A
TowerAC102.15 %618.0B631.26
4.96
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PECO_P7-1_220-9091_SRT-A/* $ BUCKS $ PECO_P7-1_220-9091 $ DCT
TowerAC101.49 %618.0B627.23
4.96

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0252-A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0252-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.34 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:173.34
MW Contribution:
5.87
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.946
203843AF2-002_GEN
Solar/Wind Harmer
0.966
20084626FORWARD
Solar/Wind Harmer
0.755
203955AF1-039 C O1
Solar/Wind Harmer
1.865
20089126CSLMN_L13
Solar/Wind Harmer
2.459
20088926STNY CRK
Solar/Wind Harmer
1.678
203844AF2-092 C
Solar/Wind Harmer
1.089
20094526CT_V3-030
Solar/Wind Harmer
0.308
20084126DEEPCRK2
50/50
0.419
203841AF2-001_GEN
Solar/Wind Harmer
1.932
20079426CONEMAGH
Adder
0.574
970631AG2-411 GEN
Solar/Wind Harmer
4.551
202652Y1-033 WT C
Solar/Wind Harmer
3.836
971879AH1-460 GEN
Solar/Wind Harmer
5.869
20092526R32
Solar/Wind Harmer
1.179
238127S14_GEN_2
Solar/Wind Helper
0.45
20083426SW_E13_K22
Solar/Wind Harmer
0.512
203839AF1-321 GEN
Solar/Wind Harmer
1.932
20088826HIGHLAND
Solar/Wind Harmer
1.101
20089226LOOKOUT
Solar/Wind Harmer
2.452
203940AF1-140 C
Solar/Wind Harmer
0.342
20083726HOMER C1
Adder
25.87
20083926HOMER C3
Adder
22.044
20083826HOMER C2
Adder
20.823
944781AF1-143 GEN
Solar/Wind Harmer
27.898
203857AF2-221 C
Solar/Wind Harmer
1.208
20081326YOUGH
50/50
0.18
964201AG1-281 GEN
Solar/Wind Harmer
0.355
20091526CHSTN_FL
Solar/Wind Harmer
0.443
238120AE2-309 GEN
Solar/Wind Helper
0.221
20084026DEEPCRK1
50/50
0.414
238126S14_GEN_1
Solar/Wind Helper
0.45
G-007ALTFEXP_G-007A->PJM
CMTX
0.768
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.18
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.181
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.626
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.421

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0252-C_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0252-C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.34 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:173.34
MW Contribution:
5.87
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.946
203843AF2-002_GEN
Solar/Wind Harmer
0.966
20084626FORWARD
Solar/Wind Harmer
0.755
203955AF1-039 C O1
Solar/Wind Harmer
1.865
20089126CSLMN_L13
Solar/Wind Harmer
2.459
20088926STNY CRK
Solar/Wind Harmer
1.678
203844AF2-092 C
Solar/Wind Harmer
1.089
20094526CT_V3-030
Solar/Wind Harmer
0.308
20084126DEEPCRK2
50/50
0.419
203841AF2-001_GEN
Solar/Wind Harmer
1.932
20079426CONEMAGH
Adder
0.574
970631AG2-411 GEN
Solar/Wind Harmer
4.551
202652Y1-033 WT C
Solar/Wind Harmer
3.836
971879AH1-460 GEN
Solar/Wind Harmer
5.869
20083426SW_E13_K22
Solar/Wind Harmer
0.512
203839AF1-321 GEN
Solar/Wind Harmer
1.932
20088826HIGHLAND
Solar/Wind Harmer
1.101
20092526R32
Solar/Wind Harmer
1.179
238127S14_GEN_2
Solar/Wind Helper
0.45
20089226LOOKOUT
Solar/Wind Harmer
2.452
203940AF1-140 C
Solar/Wind Harmer
0.342
20083726HOMER C1
Adder
25.87
20083926HOMER C3
Adder
22.044
20083826HOMER C2
Adder
20.823
944781AF1-143 GEN
Solar/Wind Harmer
27.898
203857AF2-221 C
Solar/Wind Harmer
1.208
20081326YOUGH
50/50
0.18
964201AG1-281 GEN
Solar/Wind Harmer
0.355
20091526CHSTN_FL
Solar/Wind Harmer
0.443
238120AE2-309 GEN
Solar/Wind Helper
0.221
20084026DEEPCRK1
50/50
0.414
238126S14_GEN_1
Solar/Wind Helper
0.45
G-007ALTFEXP_G-007A->PJM
CMTX
0.768
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.18
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.181
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.626
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.421

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0252-B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0252-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.34 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:173.34
MW Contribution:
5.87
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.946
203843AF2-002_GEN
Solar/Wind Harmer
0.966
20084626FORWARD
Solar/Wind Harmer
0.755
203955AF1-039 C O1
Solar/Wind Harmer
1.865
20089126CSLMN_L13
Solar/Wind Harmer
2.459
20088926STNY CRK
Solar/Wind Harmer
1.678
203844AF2-092 C
Solar/Wind Harmer
1.089
20094526CT_V3-030
Solar/Wind Harmer
0.308
20084126DEEPCRK2
50/50
0.419
203841AF2-001_GEN
Solar/Wind Harmer
1.932
20079426CONEMAGH
Adder
0.574
970631AG2-411 GEN
Solar/Wind Harmer
4.551
20083426SW_E13_K22
Solar/Wind Harmer
0.512
203839AF1-321 GEN
Solar/Wind Harmer
1.932
20088826HIGHLAND
Solar/Wind Harmer
1.101
202652Y1-033 WT C
Solar/Wind Harmer
3.836
971879AH1-460 GEN
Solar/Wind Harmer
5.869
20092526R32
Solar/Wind Harmer
1.179
238127S14_GEN_2
Solar/Wind Helper
0.45
20089226LOOKOUT
Solar/Wind Harmer
2.452
203940AF1-140 C
Solar/Wind Harmer
0.342
20083726HOMER C1
Adder
25.87
20083926HOMER C3
Adder
22.044
20083826HOMER C2
Adder
20.823
944781AF1-143 GEN
Solar/Wind Harmer
27.898
203857AF2-221 C
Solar/Wind Harmer
1.208
20081326YOUGH
50/50
0.18
964201AG1-281 GEN
Solar/Wind Harmer
0.355
20091526CHSTN_FL
Solar/Wind Harmer
0.443
238120AE2-309 GEN
Solar/Wind Helper
0.221
20084026DEEPCRK1
50/50
0.414
238126S14_GEN_1
Solar/Wind Helper
0.45
G-007ALTFEXP_G-007A->PJM
CMTX
0.768
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.18
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.181
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.626
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.421

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0201A-20_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0201A-20_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.65 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:172.25
MW Contribution:
5.86
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.946
203843AF2-002_GEN
Solar/Wind Harmer
0.965
20084626FORWARD
Solar/Wind Harmer
0.754
203955AF1-039 C O1
Solar/Wind Harmer
1.865
20089126CSLMN_L13
Solar/Wind Harmer
2.458
20088926STNY CRK
Solar/Wind Harmer
1.677
203844AF2-092 C
Solar/Wind Harmer
1.088
20094526CT_V3-030
Solar/Wind Harmer
0.31
20084126DEEPCRK2
50/50
0.419
203841AF2-001_GEN
Solar/Wind Harmer
1.93
20079426CONEMAGH
Adder
0.575
970631AG2-411 GEN
Solar/Wind Harmer
4.545
20083426SW_E13_K22
Solar/Wind Harmer
0.512
203839AF1-321 GEN
Solar/Wind Harmer
1.93
20088826HIGHLAND
Solar/Wind Harmer
1.099
202652Y1-033 WT C
Solar/Wind Harmer
3.836
971879AH1-460 GEN
Solar/Wind Harmer
5.861
20092526R32
Solar/Wind Harmer
1.178
238127S14_GEN_2
Solar/Wind Helper
0.45
20089226LOOKOUT
Solar/Wind Harmer
2.452
203940AF1-140 C
Solar/Wind Harmer
0.342
20083726HOMER C1
Adder
25.528
20083926HOMER C3
Adder
21.79
20083826HOMER C2
Adder
20.583
944781AF1-143 GEN
Solar/Wind Harmer
27.89
203857AF2-221 C
Solar/Wind Harmer
1.207
20081326YOUGH
50/50
0.18
964201AG1-281 GEN
Solar/Wind Harmer
0.355
20091526CHSTN_FL
Solar/Wind Harmer
0.443
238120AE2-309 GEN
Solar/Wind Helper
0.221
20084026DEEPCRK1
50/50
0.414
238126S14_GEN_1
Solar/Wind Helper
0.45
G-007ALTFEXP_G-007A->PJM
CMTX
0.763
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.068
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.18
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.168
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.625
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.42

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.48 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:170.37
MW Contribution:
5.46
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.914
203843AF2-002_GEN
Solar/Wind Harmer
0.904
20084626FORWARD
Solar/Wind Harmer
0.706
203955AF1-039 C O1
Solar/Wind Harmer
1.849
20089126CSLMN_L13
Solar/Wind Harmer
2.418
20088926STNY CRK
Solar/Wind Harmer
1.609
203844AF2-092 C
Solar/Wind Harmer
1.019
20084126DEEPCRK2
50/50
0.418
203841AF2-001_GEN
Solar/Wind Harmer
1.808
970631AG2-411 GEN
Solar/Wind Harmer
4.256
20083426SW_E13_K22
Solar/Wind Harmer
0.496
203839AF1-321 GEN
Solar/Wind Harmer
1.808
20088826HIGHLAND
Solar/Wind Harmer
1.003
202652Y1-033 WT C
Solar/Wind Harmer
3.803
971879AH1-460 GEN
Solar/Wind Harmer
5.461
20092526R32
Solar/Wind Harmer
1.075
238127S14_GEN_2
Solar/Wind Helper
0.452
20089226LOOKOUT
Solar/Wind Harmer
2.412
203940AF1-140 C
Solar/Wind Harmer
0.314
20083726HOMER C1
Adder
20.074
20083926HOMER C3
Adder
19.233
20083826HOMER C2
Adder
18.168
944781AF1-143 GEN
Solar/Wind Harmer
27.435
203857AF2-221 C
Solar/Wind Harmer
1.116
20081326YOUGH
50/50
0.179
964201AG1-281 GEN
Solar/Wind Harmer
0.322
20091526CHSTN_FL
Solar/Wind Harmer
0.395
238120AE2-309 GEN
Solar/Wind Helper
0.221
20084026DEEPCRK1
50/50
0.414
238126S14_GEN_1
Solar/Wind Helper
0.452
G-007ALTFEXP_G-007A->PJM
CMTX
0.861
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.105
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.582
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.142
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.426
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.658
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.442

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0183-209_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0183-209_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.72 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:169.16
MW Contribution:
6.04
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0183-209_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.59 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:173.74
MW Contribution:
6.03
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.96
203843AF2-002_GEN
Solar/Wind Harmer
0.992
20084626FORWARD
Solar/Wind Harmer
0.776
20089126CSLMN_L13
Solar/Wind Harmer
2.476
20088926STNY CRK
Solar/Wind Harmer
1.706
203844AF2-092 C
Solar/Wind Harmer
1.115
203955AF1-039 C O1
Solar/Wind Harmer
1.872
20084126DEEPCRK2
50/50
0.419
203841AF2-001_GEN
Solar/Wind Harmer
1.985
20079426CONEMAGH
Adder
0.593
202652Y1-033 WT C
Solar/Wind Harmer
3.85
971879AH1-460 GEN
Solar/Wind Harmer
6.038
20092526R32
Solar/Wind Harmer
1.219
238127S14_GEN_2
Solar/Wind Helper
0.448
970631AG2-411 GEN
Solar/Wind Harmer
4.674
20083426SW_E13_K22
Solar/Wind Harmer
0.519
203839AF1-321 GEN
Solar/Wind Harmer
1.985
20088826HIGHLAND
Solar/Wind Harmer
1.138
20089226LOOKOUT
Solar/Wind Harmer
2.469
203940AF1-140 C
Solar/Wind Harmer
0.352
20083726HOMER C1
Adder
29.418
20083926HOMER C3
Adder
16.186
20083826HOMER C2
Adder
15.289
20081326YOUGH
50/50
0.181
964201AG1-281 GEN
Solar/Wind Harmer
0.366
20091526CHSTN_FL
Solar/Wind Harmer
0.454
238120AE2-309 GEN
Solar/Wind Helper
0.22
944781AF1-143 GEN
Solar/Wind Harmer
28.091
203857AF2-221 C
Solar/Wind Harmer
1.246
20084026DEEPCRK1
50/50
0.415
238126S14_GEN_1
Solar/Wind Helper
0.448
G-007ALTFEXP_G-007A->PJM
CMTX
0.825
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.3
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.179
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.141
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.327
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.654
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.44

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P7-1_MP-138-018_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_MP-138-018_SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.82 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:167.71
MW Contribution:
5.23
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_MP-138-018_SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.01 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:176.01
MW Contribution:
5.21
Bus #Bus NameTypeMW Contribution
203955AF1-039 C O1
Solar/Wind Harmer
1.813
20089126CSLMN_L13
Solar/Wind Harmer
2.364
20088926STNY CRK
Solar/Wind Harmer
1.558
203844AF2-092 C
Solar/Wind Harmer
0.978
238118U2-030_1
Solar/Wind Helper
0.141
20084126DEEPCRK2
50/50
0.411
203841AF2-001_GEN
Solar/Wind Harmer
1.735
202652Y1-033 WT C
Solar/Wind Harmer
3.73
971879AH1-460 GEN
Solar/Wind Harmer
5.228
20092526R32
Solar/Wind Harmer
1.021
238127S14_GEN_2
Solar/Wind Helper
0.505
20083426SW_E13_K22
Solar/Wind Harmer
0.482
203839AF1-321 GEN
Solar/Wind Harmer
1.735
20088826HIGHLAND
Solar/Wind Harmer
0.953
23585401KL_K28_T16
Solar/Wind Helper
0.616
238117U2-030
Solar/Wind Helper
0.141
20089026BF_G21_K23
Solar/Wind Harmer
1.871
203843AF2-002_GEN
Solar/Wind Harmer
0.867
20084626FORWARD
Solar/Wind Harmer
0.678
970631AG2-411 GEN
Solar/Wind Harmer
4.082
235531U2-073 GEN
Solar/Wind Helper
1.383
20089226LOOKOUT
Solar/Wind Harmer
2.358
203940AF1-140 C
Solar/Wind Harmer
0.299
20083726HOMER C1
Adder
17.585
20083926HOMER C3
Adder
15.186
20083826HOMER C2
Adder
14.345
944781AF1-143 GEN
Solar/Wind Harmer
26.824
203857AF2-221 C
Solar/Wind Harmer
1.065
20084026DEEPCRK1
50/50
0.406
238126S14_GEN_1
Solar/Wind Helper
0.505
20081326YOUGH
50/50
0.176
964201AG1-281 GEN
Solar/Wind Harmer
0.306
238120AE2-309 GEN
Solar/Wind Helper
0.254
G-007ALTFEXP_G-007A->PJM
CMTX
0.704
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.097
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.876
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.164
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.994
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.549
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.367

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.57 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:167.31
MW Contribution:
5.86
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.04 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:172.86
MW Contribution:
5.85
Bus #Bus NameTypeMW Contribution
203955AF1-039 C O1
Solar/Wind Harmer
1.865
20089126CSLMN_L13
Solar/Wind Harmer
2.458
20088926STNY CRK
Solar/Wind Harmer
1.677
203844AF2-092 C
Solar/Wind Harmer
1.09
20094526CT_V3-030
Solar/Wind Harmer
0.308
20084126DEEPCRK2
50/50
0.419
203841AF2-001_GEN
Solar/Wind Harmer
1.925
20079426CONEMAGH
Adder
0.592
202652Y1-033 WT C
Solar/Wind Harmer
3.836
971879AH1-460 GEN
Solar/Wind Harmer
5.86
20092526R32
Solar/Wind Harmer
1.187
238127S14_GEN_2
Solar/Wind Helper
0.448
20083426SW_E13_K22
Solar/Wind Harmer
0.511
203839AF1-321 GEN
Solar/Wind Harmer
1.925
20088826HIGHLAND
Solar/Wind Harmer
1.108
20089026BF_G21_K23
Solar/Wind Harmer
1.945
203843AF2-002_GEN
Solar/Wind Harmer
0.963
20084626FORWARD
Solar/Wind Harmer
0.752
970631AG2-411 GEN
Solar/Wind Harmer
4.534
20089226LOOKOUT
Solar/Wind Harmer
2.451
203940AF1-140 C
Solar/Wind Harmer
0.344
20083726HOMER C1
Adder
22.81
20083926HOMER C3
Adder
19.629
20083826HOMER C2
Adder
18.542
944781AF1-143 GEN
Solar/Wind Harmer
27.885
203857AF2-221 C
Solar/Wind Harmer
1.21
20084026DEEPCRK1
50/50
0.415
238126S14_GEN_1
Solar/Wind Helper
0.448
20081326YOUGH
50/50
0.18
964201AG1-281 GEN
Solar/Wind Harmer
0.357
20091526CHSTN_FL
Solar/Wind Harmer
0.446
238120AE2-309 GEN
Solar/Wind Helper
0.22
G-007ALTFEXP_G-007A->PJM
CMTX
0.657
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.101
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.58
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.172
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.122
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.878
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.568
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.381

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_M_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.31 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:166.9
MW Contribution:
5.36
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.5 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:172.01
MW Contribution:
5.35
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.906
203843AF2-002_GEN
Solar/Wind Harmer
0.889
20084626FORWARD
Solar/Wind Harmer
0.694
20089126CSLMN_L13
Solar/Wind Harmer
2.408
20088926STNY CRK
Solar/Wind Harmer
1.592
203844AF2-092 C
Solar/Wind Harmer
1.002
203955AF1-039 C O1
Solar/Wind Harmer
1.845
20084126DEEPCRK2
50/50
0.418
203841AF2-001_GEN
Solar/Wind Harmer
1.777
202652Y1-033 WT C
Solar/Wind Harmer
3.795
970631AG2-411 GEN
Solar/Wind Harmer
4.183
971879AH1-460 GEN
Solar/Wind Harmer
5.36
20092526R32
Solar/Wind Harmer
1.05
238127S14_GEN_2
Solar/Wind Helper
0.452
20083426SW_E13_K22
Solar/Wind Harmer
0.491
203839AF1-321 GEN
Solar/Wind Harmer
1.777
20088826HIGHLAND
Solar/Wind Harmer
0.98
20089226LOOKOUT
Solar/Wind Harmer
2.402
203940AF1-140 C
Solar/Wind Harmer
0.307
20083726HOMER C1
Adder
18.359
20083926HOMER C3
Adder
15.893
20083826HOMER C2
Adder
15.013
20081326YOUGH
50/50
0.179
964201AG1-281 GEN
Solar/Wind Harmer
0.315
20091526CHSTN_FL
Solar/Wind Harmer
0.386
238120AE2-309 GEN
Solar/Wind Helper
0.222
944781AF1-143 GEN
Solar/Wind Harmer
27.323
203857AF2-221 C
Solar/Wind Harmer
1.093
20084026DEEPCRK1
50/50
0.413
238126S14_GEN_1
Solar/Wind Helper
0.452
G-007ALTFEXP_G-007A->PJM
CMTX
0.702
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.103
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.174
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.127
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.006
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.592
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.396

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-2_WP-138-033T_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-033T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.48 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:163.98
MW Contribution:
5.52
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
203955AF1-039 C O1
Solar/Wind Harmer
1.851
20089126CSLMN_L13
Solar/Wind Harmer
2.423
20088926STNY CRK
Solar/Wind Harmer
1.618
203844AF2-092 C
Solar/Wind Harmer
1.029
20084126DEEPCRK2
50/50
0.418
203841AF2-001_GEN
Solar/Wind Harmer
1.824
20079426CONEMAGH
Adder
0.528
202652Y1-033 WT C
Solar/Wind Harmer
3.807
971879AH1-460 GEN
Solar/Wind Harmer
5.516
20092526R32
Solar/Wind Harmer
1.092
238127S14_GEN_2
Solar/Wind Helper
0.453
20083426SW_E13_K22
Solar/Wind Harmer
0.498
203839AF1-321 GEN
Solar/Wind Harmer
1.824
20088826HIGHLAND
Solar/Wind Harmer
1.019
20089026BF_G21_K23
Solar/Wind Harmer
1.918
203843AF2-002_GEN
Solar/Wind Harmer
0.912
20084626FORWARD
Solar/Wind Harmer
0.712
970631AG2-411 GEN
Solar/Wind Harmer
4.293
20089226LOOKOUT
Solar/Wind Harmer
2.417
203940AF1-140 C
Solar/Wind Harmer
0.318
20083726HOMER C1
Adder
19.367
20083926HOMER C3
Adder
16.646
20083826HOMER C2
Adder
15.724
944781AF1-143 GEN
Solar/Wind Harmer
27.49
203857AF2-221 C
Solar/Wind Harmer
1.129
20084026DEEPCRK1
50/50
0.414
238126S14_GEN_1
Solar/Wind Helper
0.453
20081326YOUGH
50/50
0.179
964201AG1-281 GEN
Solar/Wind Harmer
0.327
20091526CHSTN_FL
Solar/Wind Harmer
0.404
238120AE2-309 GEN
Solar/Wind Helper
0.222
G-007ALTFEXP_G-007A->PJM
CMTX
0.838
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.106
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.342
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.178
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.14
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.364
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.649
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.436

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT19_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.45 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:162.32
MW Contribution:
5.34
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:183.9
MW Contribution:
5.33
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.904
203843AF2-002_GEN
Solar/Wind Harmer
0.886
20084626FORWARD
Solar/Wind Harmer
0.692
20089126CSLMN_L13
Solar/Wind Harmer
2.406
20088926STNY CRK
Solar/Wind Harmer
1.589
203844AF2-092 C
Solar/Wind Harmer
0.999
203955AF1-039 C O1
Solar/Wind Harmer
1.844
20084126DEEPCRK2
50/50
0.418
203841AF2-001_GEN
Solar/Wind Harmer
1.771
202652Y1-033 WT C
Solar/Wind Harmer
3.793
971879AH1-460 GEN
Solar/Wind Harmer
5.341
20092526R32
Solar/Wind Harmer
1.045
238127S14_GEN_2
Solar/Wind Helper
0.454
970631AG2-411 GEN
Solar/Wind Harmer
4.169
20083426SW_E13_K22
Solar/Wind Harmer
0.491
203839AF1-321 GEN
Solar/Wind Harmer
1.771
20088826HIGHLAND
Solar/Wind Harmer
0.975
20089226LOOKOUT
Solar/Wind Harmer
2.4
203940AF1-140 C
Solar/Wind Harmer
0.306
20083726HOMER C1
Adder
18.159
20083926HOMER C3
Adder
15.719
20083826HOMER C2
Adder
14.848
20081326YOUGH
50/50
0.179
964201AG1-281 GEN
Solar/Wind Harmer
0.313
20091526CHSTN_FL
Solar/Wind Harmer
0.384
238120AE2-309 GEN
Solar/Wind Helper
0.223
944781AF1-143 GEN
Solar/Wind Harmer
27.297
203857AF2-221 C
Solar/Wind Harmer
1.089
20084026DEEPCRK1
50/50
0.413
238126S14_GEN_1
Solar/Wind Helper
0.454
G-007ALTFEXP_G-007A->PJM
CMTX
0.753
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.104
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.054
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.129
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.131
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.6
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.401

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P7-1_MP-138-056_SRT-A-1


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_MP-138-056_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.25 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:162.0
MW Contribution:
5.29
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_MP-138-056_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.47 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:168.75
MW Contribution:
5.28
Bus #Bus NameTypeMW Contribution
203955AF1-039 C O1
Solar/Wind Harmer
1.824
20089126CSLMN_L13
Solar/Wind Harmer
2.38
20088926STNY CRK
Solar/Wind Harmer
1.573
203844AF2-092 C
Solar/Wind Harmer
0.99
238118U2-030_1
Solar/Wind Helper
0.151
20084126DEEPCRK2
50/50
0.413
203841AF2-001_GEN
Solar/Wind Harmer
1.755
202652Y1-033 WT C
Solar/Wind Harmer
3.752
971879AH1-460 GEN
Solar/Wind Harmer
5.292
20092526R32
Solar/Wind Harmer
1.036
238127S14_GEN_2
Solar/Wind Helper
0.501
20083426SW_E13_K22
Solar/Wind Harmer
0.486
203839AF1-321 GEN
Solar/Wind Harmer
1.755
20088826HIGHLAND
Solar/Wind Harmer
0.967
238117U2-030
Solar/Wind Helper
0.151
23585401KL_K28_T16
Solar/Wind Helper
0.561
20089026BF_G21_K23
Solar/Wind Harmer
1.884
203843AF2-002_GEN
Solar/Wind Harmer
0.877
20084626FORWARD
Solar/Wind Harmer
0.685
970631AG2-411 GEN
Solar/Wind Harmer
4.13
235531U2-073 GEN
Solar/Wind Helper
1.445
20089226LOOKOUT
Solar/Wind Harmer
2.374
203940AF1-140 C
Solar/Wind Harmer
0.303
20083726HOMER C1
Adder
18.076
20083926HOMER C3
Adder
15.683
20083826HOMER C2
Adder
14.815
944781AF1-143 GEN
Solar/Wind Harmer
27.004
203857AF2-221 C
Solar/Wind Harmer
1.079
20084026DEEPCRK1
50/50
0.409
238126S14_GEN_1
Solar/Wind Helper
0.501
20081326YOUGH
50/50
0.177
964201AG1-281 GEN
Solar/Wind Harmer
0.311
20091526CHSTN_FL
Solar/Wind Harmer
0.381
238120AE2-309 GEN
Solar/Wind Helper
0.251
G-007ALTFEXP_G-007A->PJM
CMTX
0.738
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.106
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.031
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.179
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.126
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.092
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.589
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.394

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_10_P42_100570_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_10_P42_100570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.4 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:731.74
MW Contribution:
5.1
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_10_P42_100570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.9 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:784.25
MW Contribution:
5.06
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
28.855
20064926PENNTECH
50/50
0.39
203855AF2-088 C
Solar/Wind Harmer
0.357
20084626FORWARD
Solar/Wind Harmer
0.61
203843AF2-002_GEN
Solar/Wind Harmer
0.748
20335026MILZ1-092
Adder
1.401
970647AG2-420 GEN
Solar/Wind Harmer
0.142
20089026BF_G21_K23
Solar/Wind Harmer
0.424
203947AF1-006 C
Solar/Wind Harmer
0.304
200644SENECA#3
50/50
0.196
20088626ARWF_N39
Solar/Wind Harmer
3.015
238217AF1-153 C O1
Solar/Wind Harmer
3.025
20094526CT_V3-030
Solar/Wind Harmer
0.74
203844AF2-092 C
Solar/Wind Harmer
1.105
20088926STNY CRK
Solar/Wind Harmer
0.964
20334926Z1-069 C
Solar/Wind Harmer
1.635
20089126CSLMN_L13
Solar/Wind Harmer
0.535
20083226HNSMLK 5
Adder
3.277
203926AA2-133 GEN
Adder
1.107
965121AG1-377 GEN
Solar/Wind Harmer
3.46
203846AF2-130 C
Solar/Wind Harmer
0.371
203955AF1-039 C O1
Solar/Wind Harmer
0.221
203854AF2-039 C
Solar/Wind Harmer
0.742
203841AF2-001_GEN
Solar/Wind Harmer
1.496
20079426CONEMAGH
Adder
0.892
970663AG2-429 GEN
Solar/Wind Harmer
0.684
203856AF2-165 C
Solar/Wind Harmer
0.739
20328326MANOR_T86
Adder
0.079
962511AG1-100 GEN
Solar/Wind Harmer
0.327
238202AE2-262_GEN
Solar/Wind Harmer
19.159
20092526R32
Solar/Wind Harmer
1.589
20120126WRREN CT
Adder
5.752
971879AH1-460 GEN
Solar/Wind Harmer
5.101
941421AE2-139 GEN
Solar/Wind Harmer
1.937
20398826ARMNA MT
Solar/Wind Harmer
1.483
970647AG2-420 GEN
Solar/Wind Harmer
1.222
20083126HNSMLK 4
Adder
3.277
203962AF1-287 GEN
Solar/Wind Harmer
1.097
202652Y1-033 WT C
Solar/Wind Harmer
0.454
209137AF2-361 C
Solar/Wind Helper
2.025
203946AE2-131 C
Solar/Wind Harmer
1.046
203954AE2-126 C
Solar/Wind Harmer
0.984
203961AE2-224 GEN
Solar/Wind Harmer
4.249
946381AF1-302 GEN
Solar/Wind Harmer
2.479
940863AE2-074 GEN
Solar/Wind Harmer
1.031
970631AG2-411 GEN
Solar/Wind Harmer
3.674
970663AG2-429 GEN
Solar/Wind Harmer
2.832
20081226ALY HYDR
50/50
0.369
216419AE2-001 C
Solar/Wind Harmer
5.499
972169AH1-667 GEN
Solar/Wind Harmer
2.475
20088826HIGHLAND
Solar/Wind Harmer
1.483
203839AF1-321 GEN
Solar/Wind Harmer
1.496
20083426SW_E13_K22
Solar/Wind Harmer
0.21
946071AF1-272 GEN
Solar/Wind Harmer
2.202
203963AG1-253 GEN
Solar/Wind Harmer
0.234
238215AE2-248 C
Solar/Wind Harmer
4.521
203987AE2-118 C
Solar/Wind Harmer
4.714
20390526W1-045 C
Solar/Wind Harmer
0.397
203940AF1-140 C
Solar/Wind Harmer
0.509
20083926HOMER C3
Adder
45.963
20083826HOMER C2
Adder
43.418
20083726HOMER C1
Adder
43.391
20089226LOOKOUT
Solar/Wind Harmer
0.534
20066626SHAWVL 4
50/50
2.204
20066526SHAWVL 3
50/50
2.187
20071526SHAWVL 1
50/50
1.479
200642SENECA#1
50/50
1.532
200643SENECA#2
50/50
1.431
941231AE2-117 GEN
Solar/Wind Harmer
5.057
962411AG1-090 GEN
Solar/Wind Harmer
16.436
970305AG2-200 GEN
Solar/Wind Harmer
1.547
203857AF2-221 C
Solar/Wind Harmer
1.2
944781AF1-143 GEN
Solar/Wind Harmer
6.072
238206AE2-263_GEN
Solar/Wind Harmer
17.963
203952AE2-129 C
Solar/Wind Harmer
1.046
20090526Q36
Solar/Wind Harmer
2.606
20091526CHSTN_FL
Solar/Wind Harmer
1.218
964201AG1-281 GEN
Solar/Wind Harmer
0.809
20326126BLOSSBCT
Adder
1.647
959471AF2-238 GEN
Solar/Wind Harmer
1.317
203830AF1-094 GEN
Solar/Wind Harmer
0.355
203979AG1-198 GEN
Solar/Wind Harmer
0.213
20082826HNSMLK 1
Adder
3.277
20083026HNSMLK 3
Adder
3.277
238183AE2-316 GEN
Solar/Wind Harmer
4.951
970899AG2-561 GEN
Solar/Wind Harmer
1.674
20335126GROZ1-110
Adder
1.826
238219AF1-167 C
Solar/Wind Harmer
0.9
959381AF2-229 GEN
Solar/Wind Harmer
0.773
970555AG2-356 GEN
Solar/Wind Harmer
1.317
966771AG1-548 GEN
Solar/Wind Harmer
8.566
966771AG1-548 GEN
Solar/Wind Harmer
1.66
209067AE2-060 GEN
Solar/Wind Helper
0.121
20091326SHAW-D
50/50
1.269
957561AF2-050 GEN
Solar/Wind Harmer
7.026
970267AG2-176 GEN
Solar/Wind Harmer
8.211
203813AE2-344_GEN
Solar/Wind Harmer
6.363
961971AG1-040 GEN
Solar/Wind Harmer
0.33
965131AG1-378 GEN
Solar/Wind Harmer
3.46
203975AE1-071-GEN
Solar/Wind Harmer
4.639
203993AD2-133_GEN1
Solar/Wind Harmer
2.606
20303426NA_O38_P22
Solar/Wind Harmer
2.441
960051AF2-296 GEN
Solar/Wind Harmer
2.838
957161AF2-010 GEN
Solar/Wind Harmer
4.536
203948AG1-140 C
Solar/Wind Harmer
0.153
203860AG1-193 C
Solar/Wind Harmer
0.578
20082926HNSMLK 2
Adder
3.277
203853AF1-134 C O1
Solar/Wind Harmer
0.858
203804AE2-113_GEN
Solar/Wind Harmer
5.669
203818AF1-086 GEN
Solar/Wind Harmer
2.866
203982AD2-062_GEN
Solar/Wind Harmer
6.544
203835AF1-098 GEN
Solar/Wind Harmer
1.556
203980AG1-197 GEN
Solar/Wind Harmer
0.817
203859AF2-294 C
Solar/Wind Harmer
0.917
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.163
LGEELTFEXP_LGEE->PJM
CLTF
0.57
MECLTFEXP_MEC->PJM
CLTF
1.43
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.201
TVALTFEXP_TVA->PJM
CLTF
0.675
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.64
CPLELTFEXP_CPLE->PJM
CLTF
0.33
SIGELTFEXP_SIGE->PJM
CLTF
0.044
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.209
WECLTFEXP_WEC->PJM
CLTF
0.344
LAGNLTFEXP_LAGN->PJM
CLTF
1.388

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-004-DRT-008_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-008_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.56 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:726.55
MW Contribution:
5.51
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-008_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.95 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:778.36
MW Contribution:
5.46
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
30.112
20064926PENNTECH
50/50
0.408
203855AF2-088 C
Solar/Wind Harmer
0.374
20084626FORWARD
Solar/Wind Harmer
0.659
203843AF2-002_GEN
Solar/Wind Harmer
0.809
20089026BF_G21_K23
Solar/Wind Harmer
0.457
20335026MILZ1-092
Adder
1.486
970647AG2-420 GEN
Solar/Wind Harmer
0.151
203947AF1-006 C
Solar/Wind Harmer
0.322
200644SENECA#3
50/50
0.207
20088626ARWF_N39
Solar/Wind Harmer
3.177
238217AF1-153 C O1
Solar/Wind Harmer
3.165
20094526CT_V3-030
Solar/Wind Harmer
0.789
203844AF2-092 C
Solar/Wind Harmer
1.183
20088926STNY CRK
Solar/Wind Harmer
1.036
20334926Z1-069 C
Solar/Wind Harmer
1.738
20089126CSLMN_L13
Solar/Wind Harmer
0.577
20083226HNSMLK 5
Adder
3.512
203926AA2-133 GEN
Adder
1.159
965121AG1-377 GEN
Solar/Wind Harmer
3.625
203846AF2-130 C
Solar/Wind Harmer
0.395
203955AF1-039 C O1
Solar/Wind Harmer
0.238
23732901CHBRG_I12
Adder
1.16
203854AF2-039 C
Solar/Wind Harmer
0.776
203841AF2-001_GEN
Solar/Wind Harmer
1.619
20079426CONEMAGH
Adder
0.963
970663AG2-429 GEN
Solar/Wind Harmer
0.725
203856AF2-165 C
Solar/Wind Harmer
0.785
20328326MANOR_T86
Adder
0.083
962511AG1-100 GEN
Solar/Wind Harmer
0.347
238202AE2-262_GEN
Solar/Wind Harmer
19.96
20092526R32
Solar/Wind Harmer
1.703
20120126WRREN CT
Adder
6.065
971879AH1-460 GEN
Solar/Wind Harmer
5.51
20398826ARMNA MT
Solar/Wind Harmer
1.573
941421AE2-139 GEN
Solar/Wind Harmer
2.026
970647AG2-420 GEN
Solar/Wind Harmer
1.3
20083126HNSMLK 4
Adder
3.512
203962AF1-287 GEN
Solar/Wind Harmer
1.163
202652Y1-033 WT C
Solar/Wind Harmer
0.489
209137AF2-361 C
Solar/Wind Helper
1.631
203946AE2-131 C
Solar/Wind Harmer
1.096
203954AE2-126 C
Solar/Wind Harmer
1.03
203961AE2-224 GEN
Solar/Wind Harmer
4.493
946381AF1-302 GEN
Solar/Wind Harmer
2.603
940863AE2-074 GEN
Solar/Wind Harmer
1.094
970631AG2-411 GEN
Solar/Wind Harmer
3.969
970663AG2-429 GEN
Solar/Wind Harmer
3.003
20081226ALY HYDR
50/50
0.384
216419AE2-001 C
Solar/Wind Harmer
5.721
972169AH1-667 GEN
Solar/Wind Harmer
2.587
20088826HIGHLAND
Solar/Wind Harmer
1.589
203839AF1-321 GEN
Solar/Wind Harmer
1.619
20083426SW_E13_K22
Solar/Wind Harmer
0.226
946071AF1-272 GEN
Solar/Wind Harmer
2.433
203963AG1-253 GEN
Solar/Wind Harmer
0.248
238215AE2-248 C
Solar/Wind Harmer
4.703
203987AE2-118 C
Solar/Wind Harmer
4.926
20390526W1-045 C
Solar/Wind Harmer
0.421
203940AF1-140 C
Solar/Wind Harmer
0.543
20083726HOMER C1
Adder
48.284
20083926HOMER C3
Adder
50.283
20083826HOMER C2
Adder
47.498
20089226LOOKOUT
Solar/Wind Harmer
0.576
20066626SHAWVL 4
50/50
2.3
20066526SHAWVL 3
50/50
2.283
20071526SHAWVL 1
50/50
1.545
200642SENECA#1
50/50
1.614
200643SENECA#2
50/50
1.507
941231AE2-117 GEN
Solar/Wind Harmer
5.278
962411AG1-090 GEN
Solar/Wind Harmer
17.219
970305AG2-200 GEN
Solar/Wind Harmer
1.631
203857AF2-221 C
Solar/Wind Harmer
1.294
944781AF1-143 GEN
Solar/Wind Harmer
6.547
238206AE2-263_GEN
Solar/Wind Harmer
18.714
203952AE2-129 C
Solar/Wind Harmer
1.096
20090526Q36
Solar/Wind Harmer
2.735
20091526CHSTN_FL
Solar/Wind Harmer
1.286
964201AG1-281 GEN
Solar/Wind Harmer
0.855
20326126BLOSSBCT
Adder
1.742
959471AF2-238 GEN
Solar/Wind Harmer
1.391
203830AF1-094 GEN
Solar/Wind Harmer
0.377
203979AG1-198 GEN
Solar/Wind Harmer
0.226
20082826HNSMLK 1
Adder
3.512
20083026HNSMLK 3
Adder
3.512
238183AE2-316 GEN
Solar/Wind Harmer
5.197
970899AG2-561 GEN
Solar/Wind Harmer
1.799
20335126GROZ1-110
Adder
1.916
238219AF1-167 C
Solar/Wind Harmer
0.952
959381AF2-229 GEN
Solar/Wind Harmer
0.819
970555AG2-356 GEN
Solar/Wind Harmer
1.391
966771AG1-548 GEN
Solar/Wind Harmer
9.077
966771AG1-548 GEN
Solar/Wind Harmer
1.759
209067AE2-060 GEN
Solar/Wind Helper
0.097
965131AG1-378 GEN
Solar/Wind Harmer
3.625
203975AE1-071-GEN
Solar/Wind Harmer
4.863
203993AD2-133_GEN1
Solar/Wind Harmer
2.735
20303426NA_O38_P22
Solar/Wind Harmer
2.572
960051AF2-296 GEN
Solar/Wind Harmer
2.987
957161AF2-010 GEN
Solar/Wind Harmer
4.807
203948AG1-140 C
Solar/Wind Harmer
0.162
203860AG1-193 C
Solar/Wind Harmer
0.615
20082926HNSMLK 2
Adder
3.512
203853AF1-134 C O1
Solar/Wind Harmer
0.903
203804AE2-113_GEN
Solar/Wind Harmer
5.971
203818AF1-086 GEN
Solar/Wind Harmer
3.041
203982AD2-062_GEN
Solar/Wind Harmer
6.927
203835AF1-098 GEN
Solar/Wind Harmer
1.645
203980AG1-197 GEN
Solar/Wind Harmer
0.867
203859AF2-294 C
Solar/Wind Harmer
0.972
20091326SHAW-D
50/50
1.326
957561AF2-050 GEN
Solar/Wind Harmer
7.43
970267AG2-176 GEN
Solar/Wind Harmer
8.734
203813AE2-344_GEN
Solar/Wind Harmer
6.746
961971AG1-040 GEN
Solar/Wind Harmer
0.35
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.661
LGEELTFEXP_LGEE->PJM
CLTF
0.591
MECLTFEXP_MEC->PJM
CLTF
1.483
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.506
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.281
TVALTFEXP_TVA->PJM
CLTF
0.704
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.751
CPLELTFEXP_CPLE->PJM
CLTF
0.358
SIGELTFEXP_SIGE->PJM
CLTF
0.045
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.613
WECLTFEXP_WEC->PJM
CLTF
0.356
LAGNLTFEXP_LAGN->PJM
CLTF
1.447

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-DRT31_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-DRT31_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.56 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:726.55
MW Contribution:
5.51
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-DRT31_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.95 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:778.36
MW Contribution:
5.46
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
30.112
20064926PENNTECH
50/50
0.408
203855AF2-088 C
Solar/Wind Harmer
0.374
20084626FORWARD
Solar/Wind Harmer
0.659
203843AF2-002_GEN
Solar/Wind Harmer
0.809
20089026BF_G21_K23
Solar/Wind Harmer
0.457
20335026MILZ1-092
Adder
1.486
970647AG2-420 GEN
Solar/Wind Harmer
0.151
203947AF1-006 C
Solar/Wind Harmer
0.322
200644SENECA#3
50/50
0.207
20088626ARWF_N39
Solar/Wind Harmer
3.177
238217AF1-153 C O1
Solar/Wind Harmer
3.165
20094526CT_V3-030
Solar/Wind Harmer
0.789
203844AF2-092 C
Solar/Wind Harmer
1.183
20088926STNY CRK
Solar/Wind Harmer
1.036
20334926Z1-069 C
Solar/Wind Harmer
1.738
20089126CSLMN_L13
Solar/Wind Harmer
0.577
20083226HNSMLK 5
Adder
3.512
203926AA2-133 GEN
Adder
1.159
965121AG1-377 GEN
Solar/Wind Harmer
3.625
203846AF2-130 C
Solar/Wind Harmer
0.395
203955AF1-039 C O1
Solar/Wind Harmer
0.238
23732901CHBRG_I12
Adder
1.16
203854AF2-039 C
Solar/Wind Harmer
0.776
203841AF2-001_GEN
Solar/Wind Harmer
1.619
20079426CONEMAGH
Adder
0.963
970663AG2-429 GEN
Solar/Wind Harmer
0.725
203856AF2-165 C
Solar/Wind Harmer
0.785
20328326MANOR_T86
Adder
0.083
962511AG1-100 GEN
Solar/Wind Harmer
0.347
238202AE2-262_GEN
Solar/Wind Harmer
19.96
20092526R32
Solar/Wind Harmer
1.703
20120126WRREN CT
Adder
6.065
971879AH1-460 GEN
Solar/Wind Harmer
5.51
20398826ARMNA MT
Solar/Wind Harmer
1.573
941421AE2-139 GEN
Solar/Wind Harmer
2.026
970647AG2-420 GEN
Solar/Wind Harmer
1.3
20083126HNSMLK 4
Adder
3.512
203962AF1-287 GEN
Solar/Wind Harmer
1.163
202652Y1-033 WT C
Solar/Wind Harmer
0.489
209137AF2-361 C
Solar/Wind Helper
1.631
203946AE2-131 C
Solar/Wind Harmer
1.096
203954AE2-126 C
Solar/Wind Harmer
1.03
203961AE2-224 GEN
Solar/Wind Harmer
4.493
946381AF1-302 GEN
Solar/Wind Harmer
2.603
940863AE2-074 GEN
Solar/Wind Harmer
1.094
970631AG2-411 GEN
Solar/Wind Harmer
3.969
970663AG2-429 GEN
Solar/Wind Harmer
3.003
20081226ALY HYDR
50/50
0.384
216419AE2-001 C
Solar/Wind Harmer
5.721
972169AH1-667 GEN
Solar/Wind Harmer
2.587
20088826HIGHLAND
Solar/Wind Harmer
1.589
203839AF1-321 GEN
Solar/Wind Harmer
1.619
20083426SW_E13_K22
Solar/Wind Harmer
0.226
946071AF1-272 GEN
Solar/Wind Harmer
2.433
203963AG1-253 GEN
Solar/Wind Harmer
0.248
238215AE2-248 C
Solar/Wind Harmer
4.703
203987AE2-118 C
Solar/Wind Harmer
4.926
20390526W1-045 C
Solar/Wind Harmer
0.421
203940AF1-140 C
Solar/Wind Harmer
0.543
20083726HOMER C1
Adder
48.284
20083926HOMER C3
Adder
50.283
20083826HOMER C2
Adder
47.498
20089226LOOKOUT
Solar/Wind Harmer
0.576
20066626SHAWVL 4
50/50
2.3
20066526SHAWVL 3
50/50
2.283
20071526SHAWVL 1
50/50
1.545
238206AE2-263_GEN
Solar/Wind Harmer
18.714
203952AE2-129 C
Solar/Wind Harmer
1.096
20090526Q36
Solar/Wind Harmer
2.735
20091526CHSTN_FL
Solar/Wind Harmer
1.286
964201AG1-281 GEN
Solar/Wind Harmer
0.855
20326126BLOSSBCT
Adder
1.742
959471AF2-238 GEN
Solar/Wind Harmer
1.391
203830AF1-094 GEN
Solar/Wind Harmer
0.377
203979AG1-198 GEN
Solar/Wind Harmer
0.226
20082826HNSMLK 1
Adder
3.512
20083026HNSMLK 3
Adder
3.512
200642SENECA#1
50/50
1.614
200643SENECA#2
50/50
1.507
941231AE2-117 GEN
Solar/Wind Harmer
5.278
962411AG1-090 GEN
Solar/Wind Harmer
17.219
970305AG2-200 GEN
Solar/Wind Harmer
1.631
203857AF2-221 C
Solar/Wind Harmer
1.294
944781AF1-143 GEN
Solar/Wind Harmer
6.547
238183AE2-316 GEN
Solar/Wind Harmer
5.197
970899AG2-561 GEN
Solar/Wind Harmer
1.799
20335126GROZ1-110
Adder
1.916
238219AF1-167 C
Solar/Wind Harmer
0.952
959381AF2-229 GEN
Solar/Wind Harmer
0.819
970555AG2-356 GEN
Solar/Wind Harmer
1.391
966771AG1-548 GEN
Solar/Wind Harmer
9.077
966771AG1-548 GEN
Solar/Wind Harmer
1.759
209067AE2-060 GEN
Solar/Wind Helper
0.097
965131AG1-378 GEN
Solar/Wind Harmer
3.625
203975AE1-071-GEN
Solar/Wind Harmer
4.863
203993AD2-133_GEN1
Solar/Wind Harmer
2.735
20303426NA_O38_P22
Solar/Wind Harmer
2.572
960051AF2-296 GEN
Solar/Wind Harmer
2.987
957161AF2-010 GEN
Solar/Wind Harmer
4.807
203948AG1-140 C
Solar/Wind Harmer
0.162
203860AG1-193 C
Solar/Wind Harmer
0.615
20082926HNSMLK 2
Adder
3.512
203853AF1-134 C O1
Solar/Wind Harmer
0.903
203804AE2-113_GEN
Solar/Wind Harmer
5.971
203818AF1-086 GEN
Solar/Wind Harmer
3.041
203982AD2-062_GEN
Solar/Wind Harmer
6.927
203835AF1-098 GEN
Solar/Wind Harmer
1.645
203980AG1-197 GEN
Solar/Wind Harmer
0.867
203859AF2-294 C
Solar/Wind Harmer
0.972
20091326SHAW-D
50/50
1.326
957561AF2-050 GEN
Solar/Wind Harmer
7.43
970267AG2-176 GEN
Solar/Wind Harmer
8.734
203813AE2-344_GEN
Solar/Wind Harmer
6.746
961971AG1-040 GEN
Solar/Wind Harmer
0.35
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.661
LGEELTFEXP_LGEE->PJM
CLTF
0.591
MECLTFEXP_MEC->PJM
CLTF
1.483
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.506
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.281
TVALTFEXP_TVA->PJM
CLTF
0.704
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.751
CPLELTFEXP_CPLE->PJM
CLTF
0.358
SIGELTFEXP_SIGE->PJM
CLTF
0.045
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.613
WECLTFEXP_WEC->PJM
CLTF
0.356
LAGNLTFEXP_LAGN->PJM
CLTF
1.447

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_10_P42_100569_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_10_P42_100569_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.1 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:723.67
MW Contribution:
5.13
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
28.902
20064926PENNTECH
50/50
0.39
203855AF2-088 C
Solar/Wind Harmer
0.358
20084626FORWARD
Solar/Wind Harmer
0.613
203843AF2-002_GEN
Solar/Wind Harmer
0.752
20335026MILZ1-092
Adder
1.409
20089026BF_G21_K23
Solar/Wind Harmer
0.425
970647AG2-420 GEN
Solar/Wind Harmer
0.141
203947AF1-006 C
Solar/Wind Harmer
0.3
200644SENECA#3
50/50
0.196
20088626ARWF_N39
Solar/Wind Harmer
3.031
238217AF1-153 C O1
Solar/Wind Harmer
3.025
20094526CT_V3-030
Solar/Wind Harmer
0.743
203844AF2-092 C
Solar/Wind Harmer
1.111
20088926STNY CRK
Solar/Wind Harmer
0.968
20334926Z1-069 C
Solar/Wind Harmer
1.637
20089126CSLMN_L13
Solar/Wind Harmer
0.536
965121AG1-377 GEN
Solar/Wind Harmer
3.468
203846AF2-130 C
Solar/Wind Harmer
0.368
203955AF1-039 C O1
Solar/Wind Harmer
0.221
23732901CHBRG_I12
Adder
1.099
20083226HNSMLK 5
Adder
3.241
203926AA2-133 GEN
Adder
1.124
203854AF2-039 C
Solar/Wind Harmer
0.744
203841AF2-001_GEN
Solar/Wind Harmer
1.504
20079426CONEMAGH
Adder
0.9
970663AG2-429 GEN
Solar/Wind Harmer
0.676
203856AF2-165 C
Solar/Wind Harmer
0.731
20328326MANOR_T86
Adder
0.08
962511AG1-100 GEN
Solar/Wind Harmer
0.323
203946AE2-131 C
Solar/Wind Harmer
1.049
203954AE2-126 C
Solar/Wind Harmer
0.985
203961AE2-224 GEN
Solar/Wind Harmer
4.274
946381AF1-302 GEN
Solar/Wind Harmer
2.473
940863AE2-074 GEN
Solar/Wind Harmer
1.031
970631AG2-411 GEN
Solar/Wind Harmer
3.693
970663AG2-429 GEN
Solar/Wind Harmer
2.798
238202AE2-262_GEN
Solar/Wind Harmer
19.196
20092526R32
Solar/Wind Harmer
1.599
20120126WRREN CT
Adder
5.733
971879AH1-460 GEN
Solar/Wind Harmer
5.131
941421AE2-139 GEN
Solar/Wind Harmer
1.958
20398826ARMNA MT
Solar/Wind Harmer
1.491
970647AG2-420 GEN
Solar/Wind Harmer
1.21
20083126HNSMLK 4
Adder
3.241
203962AF1-287 GEN
Solar/Wind Harmer
1.084
202652Y1-033 WT C
Solar/Wind Harmer
0.454
209137AF2-361 C
Solar/Wind Helper
2
20081226ALY HYDR
50/50
0.37
216419AE2-001 C
Solar/Wind Harmer
5.511
972169AH1-667 GEN
Solar/Wind Harmer
2.479
20088826HIGHLAND
Solar/Wind Harmer
1.493
203839AF1-321 GEN
Solar/Wind Harmer
1.504
20083426SW_E13_K22
Solar/Wind Harmer
0.211
946071AF1-272 GEN
Solar/Wind Harmer
2.186
203963AG1-253 GEN
Solar/Wind Harmer
0.231
238215AE2-248 C
Solar/Wind Harmer
4.531
203987AE2-118 C
Solar/Wind Harmer
4.73
20390526W1-045 C
Solar/Wind Harmer
0.4
203940AF1-140 C
Solar/Wind Harmer
0.512
20083926HOMER C3
Adder
45.818
20083826HOMER C2
Adder
43.28
20083726HOMER C1
Adder
43.349
20089226LOOKOUT
Solar/Wind Harmer
0.535
238206AE2-263_GEN
Solar/Wind Harmer
17.997
203952AE2-129 C
Solar/Wind Harmer
1.049
20090526Q36
Solar/Wind Harmer
2.614
20091526CHSTN_FL
Solar/Wind Harmer
1.223
964201AG1-281 GEN
Solar/Wind Harmer
0.813
20326126BLOSSBCT
Adder
1.655
959471AF2-238 GEN
Solar/Wind Harmer
1.325
20066626SHAWVL 4
50/50
2.207
20066526SHAWVL 3
50/50
2.191
20071526SHAWVL 1
50/50
1.482
200642SENECA#1
50/50
1.529
200643SENECA#2
50/50
1.428
941231AE2-117 GEN
Solar/Wind Harmer
5.073
962411AG1-090 GEN
Solar/Wind Harmer
16.475
970305AG2-200 GEN
Solar/Wind Harmer
1.541
203857AF2-221 C
Solar/Wind Harmer
1.208
944781AF1-143 GEN
Solar/Wind Harmer
6.085
238183AE2-316 GEN
Solar/Wind Harmer
4.939
970899AG2-561 GEN
Solar/Wind Harmer
1.674
203830AF1-094 GEN
Solar/Wind Harmer
0.352
203979AG1-198 GEN
Solar/Wind Harmer
0.211
20082826HNSMLK 1
Adder
3.241
20083026HNSMLK 3
Adder
3.241
959381AF2-229 GEN
Solar/Wind Harmer
0.779
970555AG2-356 GEN
Solar/Wind Harmer
1.325
966771AG1-548 GEN
Solar/Wind Harmer
8.473
966771AG1-548 GEN
Solar/Wind Harmer
1.642
209067AE2-060 GEN
Solar/Wind Helper
0.119
20335126GROZ1-110
Adder
1.839
238219AF1-167 C
Solar/Wind Harmer
0.889
965131AG1-378 GEN
Solar/Wind Harmer
3.468
203975AE1-071-GEN
Solar/Wind Harmer
4.662
203993AD2-133_GEN1
Solar/Wind Harmer
2.614
20303426NA_O38_P22
Solar/Wind Harmer
2.454
960051AF2-296 GEN
Solar/Wind Harmer
2.842
957161AF2-010 GEN
Solar/Wind Harmer
4.487
203948AG1-140 C
Solar/Wind Harmer
0.152
203860AG1-193 C
Solar/Wind Harmer
0.571
20082926HNSMLK 2
Adder
3.241
203853AF1-134 C O1
Solar/Wind Harmer
0.859
203804AE2-113_GEN
Solar/Wind Harmer
5.668
203818AF1-086 GEN
Solar/Wind Harmer
2.869
203982AD2-062_GEN
Solar/Wind Harmer
6.593
203835AF1-098 GEN
Solar/Wind Harmer
1.542
203859AF2-294 C
Solar/Wind Harmer
0.924
203980AG1-197 GEN
Solar/Wind Harmer
0.807
20091326SHAW-D
50/50
1.271
957561AF2-050 GEN
Solar/Wind Harmer
7.068
970267AG2-176 GEN
Solar/Wind Harmer
8.111
203813AE2-344_GEN
Solar/Wind Harmer
6.285
961971AG1-040 GEN
Solar/Wind Harmer
0.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.061
LGEELTFEXP_LGEE->PJM
CLTF
0.522
MECLTFEXP_MEC->PJM
CLTF
1.313
CBM NorthLTFEXP_CBM-N->PJM
CBM
1.005
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.077
TVALTFEXP_TVA->PJM
CLTF
0.616
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.41
CPLELTFEXP_CPLE->PJM
CLTF
0.292
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.344
WECLTFEXP_WEC->PJM
CLTF
0.316
LAGNLTFEXP_LAGN->PJM
CLTF
1.267

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-115-0331-A_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-0331-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.98 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:722.93
MW Contribution:
5.53
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-0331-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.44 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:775.2
MW Contribution:
5.48
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
32.887
20064926PENNTECH
50/50
0.44
203855AF2-088 C
Solar/Wind Harmer
0.406
20084626FORWARD
Solar/Wind Harmer
0.661
203843AF2-002_GEN
Solar/Wind Harmer
0.809
20335026MILZ1-092
Adder
1.62
970647AG2-420 GEN
Solar/Wind Harmer
0.152
20089026BF_G21_K23
Solar/Wind Harmer
0.452
203947AF1-006 C
Solar/Wind Harmer
0.325
200644SENECA#3
50/50
0.219
20088626ARWF_N39
Solar/Wind Harmer
3.396
238217AF1-153 C O1
Solar/Wind Harmer
3.421
20094526CT_V3-030
Solar/Wind Harmer
0.819
203844AF2-092 C
Solar/Wind Harmer
1.214
20334926Z1-069 C
Solar/Wind Harmer
1.841
20088926STNY CRK
Solar/Wind Harmer
1.048
20089126CSLMN_L13
Solar/Wind Harmer
0.571
20083226HNSMLK 5
Adder
3.481
203926AA2-133 GEN
Adder
1.362
965121AG1-377 GEN
Solar/Wind Harmer
3.923
203846AF2-130 C
Solar/Wind Harmer
0.399
203955AF1-039 C O1
Solar/Wind Harmer
0.231
20334726NME_Y1-047
Adder
1.159
203854AF2-039 C
Solar/Wind Harmer
0.844
203841AF2-001_GEN
Solar/Wind Harmer
1.618
20079426CONEMAGH
Adder
0.965
970663AG2-429 GEN
Solar/Wind Harmer
0.732
20328326MANOR_T86
Adder
0.095
203856AF2-165 C
Solar/Wind Harmer
0.791
962511AG1-100 GEN
Solar/Wind Harmer
0.349
238202AE2-262_GEN
Solar/Wind Harmer
21.899
20120126WRREN CT
Adder
6.383
20092526R32
Solar/Wind Harmer
1.744
971879AH1-460 GEN
Solar/Wind Harmer
5.532
941421AE2-139 GEN
Solar/Wind Harmer
2.323
20398826ARMNA MT
Solar/Wind Harmer
1.714
970647AG2-420 GEN
Solar/Wind Harmer
1.308
20083126HNSMLK 4
Adder
3.481
203962AF1-287 GEN
Solar/Wind Harmer
1.171
202652Y1-033 WT C
Solar/Wind Harmer
0.475
209137AF2-361 C
Solar/Wind Helper
1.365
203946AE2-131 C
Solar/Wind Harmer
1.186
203954AE2-126 C
Solar/Wind Harmer
1.116
203961AE2-224 GEN
Solar/Wind Harmer
4.761
946381AF1-302 GEN
Solar/Wind Harmer
2.772
940863AE2-074 GEN
Solar/Wind Harmer
1.154
970631AG2-411 GEN
Solar/Wind Harmer
3.983
970663AG2-429 GEN
Solar/Wind Harmer
3.031
20081226ALY HYDR
50/50
0.422
216419AE2-001 C
Solar/Wind Harmer
6.297
972169AH1-667 GEN
Solar/Wind Harmer
2.813
20088826HIGHLAND
Solar/Wind Harmer
1.627
203839AF1-321 GEN
Solar/Wind Harmer
1.618
20083426SW_E13_K22
Solar/Wind Harmer
0.226
946071AF1-272 GEN
Solar/Wind Harmer
2.34
203963AG1-253 GEN
Solar/Wind Harmer
0.252
238215AE2-248 C
Solar/Wind Harmer
5.178
203987AE2-118 C
Solar/Wind Harmer
5.378
203940AF1-140 C
Solar/Wind Harmer
0.563
20083926HOMER C3
Adder
49.307
20083826HOMER C2
Adder
46.576
20083726HOMER C1
Adder
46.082
20089226LOOKOUT
Solar/Wind Harmer
0.569
238206AE2-263_GEN
Solar/Wind Harmer
20.532
203952AE2-129 C
Solar/Wind Harmer
1.186
20090526Q36
Solar/Wind Harmer
2.948
20091526CHSTN_FL
Solar/Wind Harmer
1.366
964201AG1-281 GEN
Solar/Wind Harmer
0.905
20326126BLOSSBCT
Adder
1.899
959471AF2-238 GEN
Solar/Wind Harmer
1.532
203830AF1-094 GEN
Solar/Wind Harmer
0.381
203979AG1-198 GEN
Solar/Wind Harmer
0.229
20082826HNSMLK 1
Adder
3.481
20083026HNSMLK 3
Adder
3.481
20066626SHAWVL 4
50/50
2.511
20066526SHAWVL 3
50/50
2.493
20071526SHAWVL 1
50/50
1.684
200642SENECA#1
50/50
1.711
200643SENECA#2
50/50
1.598
941231AE2-117 GEN
Solar/Wind Harmer
5.782
962411AG1-090 GEN
Solar/Wind Harmer
18.635
970305AG2-200 GEN
Solar/Wind Harmer
1.716
203857AF2-221 C
Solar/Wind Harmer
1.305
944781AF1-143 GEN
Solar/Wind Harmer
6.474
238183AE2-316 GEN
Solar/Wind Harmer
5.536
20335126GROZ1-110
Adder
2.141
970899AG2-561 GEN
Solar/Wind Harmer
1.826
238219AF1-167 C
Solar/Wind Harmer
0.965
970555AG2-356 GEN
Solar/Wind Harmer
1.532
966771AG1-548 GEN
Solar/Wind Harmer
9.19
966771AG1-548 GEN
Solar/Wind Harmer
1.781
200917MEHOOPANY_G
Solar/Wind Harmer
1.724
209067AE2-060 GEN
Solar/Wind Helper
0.082
203975AE1-071-GEN
Solar/Wind Harmer
13.333
965131AG1-378 GEN
Solar/Wind Harmer
3.923
203993AD2-133_GEN1
Solar/Wind Harmer
2.948
20303426NA_O38_P22
Solar/Wind Harmer
2.749
960051AF2-296 GEN
Solar/Wind Harmer
3.194
957161AF2-010 GEN
Solar/Wind Harmer
4.866
203948AG1-140 C
Solar/Wind Harmer
0.165
203860AG1-193 C
Solar/Wind Harmer
0.616
20082926HNSMLK 2
Adder
3.481
203853AF1-134 C O1
Solar/Wind Harmer
0.966
203804AE2-113_GEN
Solar/Wind Harmer
6.375
203818AF1-086 GEN
Solar/Wind Harmer
3.188
203835AF1-098 GEN
Solar/Wind Harmer
1.687
203859AF2-294 C
Solar/Wind Harmer
1.076
203980AG1-197 GEN
Solar/Wind Harmer
0.869
20091326SHAW-D
50/50
1.442
957561AF2-050 GEN
Solar/Wind Harmer
7.873
203813AE2-344_GEN
Solar/Wind Harmer
6.787
970267AG2-176 GEN
Solar/Wind Harmer
8.735
961971AG1-040 GEN
Solar/Wind Harmer
0.351
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.603
LGEELTFEXP_LGEE->PJM
CLTF
0.399
MECLTFEXP_MEC->PJM
CLTF
1.018
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.439
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.507
TVALTFEXP_TVA->PJM
CLTF
0.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.722
CPLELTFEXP_CPLE->PJM
CLTF
0.084
SIGELTFEXP_SIGE->PJM
CLTF
0.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.935
WECLTFEXP_WEC->PJM
CLTF
0.25
LAGNLTFEXP_LAGN->PJM
CLTF
0.9

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-115-0331-B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-0331-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.86 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:722.22
MW Contribution:
5.54
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-0331-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.41 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:775.03
MW Contribution:
5.48
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
32.902
20064926PENNTECH
50/50
0.441
203855AF2-088 C
Solar/Wind Harmer
0.406
20084626FORWARD
Solar/Wind Harmer
0.661
203843AF2-002_GEN
Solar/Wind Harmer
0.81
20335026MILZ1-092
Adder
1.622
970647AG2-420 GEN
Solar/Wind Harmer
0.152
20089026BF_G21_K23
Solar/Wind Harmer
0.452
203947AF1-006 C
Solar/Wind Harmer
0.325
200644SENECA#3
50/50
0.22
20088626ARWF_N39
Solar/Wind Harmer
3.397
238217AF1-153 C O1
Solar/Wind Harmer
3.423
20094526CT_V3-030
Solar/Wind Harmer
0.82
203844AF2-092 C
Solar/Wind Harmer
1.215
20334926Z1-069 C
Solar/Wind Harmer
1.843
20088926STNY CRK
Solar/Wind Harmer
1.048
20089126CSLMN_L13
Solar/Wind Harmer
0.571
20083226HNSMLK 5
Adder
3.482
203926AA2-133 GEN
Adder
1.365
965121AG1-377 GEN
Solar/Wind Harmer
3.925
203846AF2-130 C
Solar/Wind Harmer
0.399
203955AF1-039 C O1
Solar/Wind Harmer
0.231
20334726NME_Y1-047
Adder
1.162
203854AF2-039 C
Solar/Wind Harmer
0.844
203841AF2-001_GEN
Solar/Wind Harmer
1.619
20079426CONEMAGH
Adder
0.965
970663AG2-429 GEN
Solar/Wind Harmer
0.733
20328326MANOR_T86
Adder
0.095
203856AF2-165 C
Solar/Wind Harmer
0.791
962511AG1-100 GEN
Solar/Wind Harmer
0.349
238202AE2-262_GEN
Solar/Wind Harmer
21.909
20120126WRREN CT
Adder
6.386
20092526R32
Solar/Wind Harmer
1.745
971879AH1-460 GEN
Solar/Wind Harmer
5.535
941421AE2-139 GEN
Solar/Wind Harmer
2.327
20398826ARMNA MT
Solar/Wind Harmer
1.717
970647AG2-420 GEN
Solar/Wind Harmer
1.309
20083126HNSMLK 4
Adder
3.482
203962AF1-287 GEN
Solar/Wind Harmer
1.171
202652Y1-033 WT C
Solar/Wind Harmer
0.475
209137AF2-361 C
Solar/Wind Helper
1.361
203946AE2-131 C
Solar/Wind Harmer
1.187
203954AE2-126 C
Solar/Wind Harmer
1.116
203961AE2-224 GEN
Solar/Wind Harmer
4.763
946381AF1-302 GEN
Solar/Wind Harmer
2.774
940863AE2-074 GEN
Solar/Wind Harmer
1.155
970631AG2-411 GEN
Solar/Wind Harmer
3.986
970663AG2-429 GEN
Solar/Wind Harmer
3.033
20081226ALY HYDR
50/50
0.422
216419AE2-001 C
Solar/Wind Harmer
6.3
972169AH1-667 GEN
Solar/Wind Harmer
2.814
20088826HIGHLAND
Solar/Wind Harmer
1.628
203839AF1-321 GEN
Solar/Wind Harmer
1.619
20083426SW_E13_K22
Solar/Wind Harmer
0.226
946071AF1-272 GEN
Solar/Wind Harmer
2.342
203963AG1-253 GEN
Solar/Wind Harmer
0.252
238215AE2-248 C
Solar/Wind Harmer
5.18
203987AE2-118 C
Solar/Wind Harmer
5.38
203940AF1-140 C
Solar/Wind Harmer
0.563
20083926HOMER C3
Adder
49.345
20083826HOMER C2
Adder
46.612
20083726HOMER C1
Adder
46.121
20089226LOOKOUT
Solar/Wind Harmer
0.569
238206AE2-263_GEN
Solar/Wind Harmer
20.541
203952AE2-129 C
Solar/Wind Harmer
1.187
20090526Q36
Solar/Wind Harmer
2.949
20091526CHSTN_FL
Solar/Wind Harmer
1.367
964201AG1-281 GEN
Solar/Wind Harmer
0.906
20326126BLOSSBCT
Adder
1.901
959471AF2-238 GEN
Solar/Wind Harmer
1.534
203830AF1-094 GEN
Solar/Wind Harmer
0.382
203979AG1-198 GEN
Solar/Wind Harmer
0.229
20082826HNSMLK 1
Adder
3.482
20083026HNSMLK 3
Adder
3.482
20066626SHAWVL 4
50/50
2.513
20066526SHAWVL 3
50/50
2.494
20071526SHAWVL 1
50/50
1.685
200642SENECA#1
50/50
1.712
200643SENECA#2
50/50
1.599
941231AE2-117 GEN
Solar/Wind Harmer
5.784
962411AG1-090 GEN
Solar/Wind Harmer
18.644
970305AG2-200 GEN
Solar/Wind Harmer
1.717
203857AF2-221 C
Solar/Wind Harmer
1.306
944781AF1-143 GEN
Solar/Wind Harmer
6.474
238183AE2-316 GEN
Solar/Wind Harmer
5.539
20335126GROZ1-110
Adder
2.144
970899AG2-561 GEN
Solar/Wind Harmer
1.827
238219AF1-167 C
Solar/Wind Harmer
0.966
970555AG2-356 GEN
Solar/Wind Harmer
1.534
966771AG1-548 GEN
Solar/Wind Harmer
9.193
966771AG1-548 GEN
Solar/Wind Harmer
1.782
200917MEHOOPANY_G
Solar/Wind Harmer
1.728
209067AE2-060 GEN
Solar/Wind Helper
0.081
203975AE1-071-GEN
Solar/Wind Harmer
13.339
965131AG1-378 GEN
Solar/Wind Harmer
3.925
203993AD2-133_GEN1
Solar/Wind Harmer
2.949
20303426NA_O38_P22
Solar/Wind Harmer
2.75
960051AF2-296 GEN
Solar/Wind Harmer
3.196
957161AF2-010 GEN
Solar/Wind Harmer
4.867
203948AG1-140 C
Solar/Wind Harmer
0.165
203860AG1-193 C
Solar/Wind Harmer
0.616
20082926HNSMLK 2
Adder
3.482
203853AF1-134 C O1
Solar/Wind Harmer
0.966
203804AE2-113_GEN
Solar/Wind Harmer
6.378
203818AF1-086 GEN
Solar/Wind Harmer
3.189
203835AF1-098 GEN
Solar/Wind Harmer
1.688
203859AF2-294 C
Solar/Wind Harmer
1.077
203980AG1-197 GEN
Solar/Wind Harmer
0.87
20091326SHAW-D
50/50
1.443
957561AF2-050 GEN
Solar/Wind Harmer
7.877
203813AE2-344_GEN
Solar/Wind Harmer
6.789
970267AG2-176 GEN
Solar/Wind Harmer
8.738
961971AG1-040 GEN
Solar/Wind Harmer
0.351
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.513
LGEELTFEXP_LGEE->PJM
CLTF
0.395
MECLTFEXP_MEC->PJM
CLTF
1.007
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.52
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.484
TVALTFEXP_TVA->PJM
CLTF
0.424
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.695
CPLELTFEXP_CPLE->PJM
CLTF
0.075
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.843
WECLTFEXP_WEC->PJM
CLTF
0.247
LAGNLTFEXP_LAGN->PJM
CLTF
0.886

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-2_PN-115-030_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-030_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.75 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:678.27
MW Contribution:
5.55
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-030_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.35 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:731.4
MW Contribution:
5.49
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
32.928
20064926PENNTECH
50/50
0.441
203855AF2-088 C
Solar/Wind Harmer
0.407
20084626FORWARD
Solar/Wind Harmer
0.663
203843AF2-002_GEN
Solar/Wind Harmer
0.811
20335026MILZ1-092
Adder
1.626
970647AG2-420 GEN
Solar/Wind Harmer
0.153
20089026BF_G21_K23
Solar/Wind Harmer
0.453
203947AF1-006 C
Solar/Wind Harmer
0.326
965121AG1-377 GEN
Solar/Wind Harmer
3.929
203846AF2-130 C
Solar/Wind Harmer
0.4
203955AF1-039 C O1
Solar/Wind Harmer
0.232
20334726NME_Y1-047
Adder
1.166
200644SENECA#3
50/50
0.22
20088626ARWF_N39
Solar/Wind Harmer
3.401
238217AF1-153 C O1
Solar/Wind Harmer
3.426
20094526CT_V3-030
Solar/Wind Harmer
0.821
203844AF2-092 C
Solar/Wind Harmer
1.217
20334926Z1-069 C
Solar/Wind Harmer
1.847
20088926STNY CRK
Solar/Wind Harmer
1.05
20089126CSLMN_L13
Solar/Wind Harmer
0.572
20083226HNSMLK 5
Adder
3.493
203926AA2-133 GEN
Adder
1.369
203854AF2-039 C
Solar/Wind Harmer
0.845
203841AF2-001_GEN
Solar/Wind Harmer
1.623
20079426CONEMAGH
Adder
0.968
970663AG2-429 GEN
Solar/Wind Harmer
0.734
20328326MANOR_T86
Adder
0.095
203856AF2-165 C
Solar/Wind Harmer
0.794
962511AG1-100 GEN
Solar/Wind Harmer
0.35
203946AE2-131 C
Solar/Wind Harmer
1.188
203954AE2-126 C
Solar/Wind Harmer
1.117
203961AE2-224 GEN
Solar/Wind Harmer
4.769
946381AF1-302 GEN
Solar/Wind Harmer
2.778
940863AE2-074 GEN
Solar/Wind Harmer
1.157
20081226ALY HYDR
50/50
0.422
216419AE2-001 C
Solar/Wind Harmer
6.303
972169AH1-667 GEN
Solar/Wind Harmer
2.816
20088826HIGHLAND
Solar/Wind Harmer
1.631
203839AF1-321 GEN
Solar/Wind Harmer
1.623
20083426SW_E13_K22
Solar/Wind Harmer
0.227
946071AF1-272 GEN
Solar/Wind Harmer
2.347
203963AG1-253 GEN
Solar/Wind Harmer
0.253
238202AE2-262_GEN
Solar/Wind Harmer
21.924
20120126WRREN CT
Adder
6.398
20092526R32
Solar/Wind Harmer
1.748
971879AH1-460 GEN
Solar/Wind Harmer
5.547
941421AE2-139 GEN
Solar/Wind Harmer
2.332
20398826ARMNA MT
Solar/Wind Harmer
1.721
970647AG2-420 GEN
Solar/Wind Harmer
1.312
20083126HNSMLK 4
Adder
3.493
203962AF1-287 GEN
Solar/Wind Harmer
1.175
202652Y1-033 WT C
Solar/Wind Harmer
0.476
209137AF2-361 C
Solar/Wind Helper
1.358
970631AG2-411 GEN
Solar/Wind Harmer
3.994
970663AG2-429 GEN
Solar/Wind Harmer
3.041
238215AE2-248 C
Solar/Wind Harmer
5.183
203987AE2-118 C
Solar/Wind Harmer
5.383
203940AF1-140 C
Solar/Wind Harmer
0.564
20083926HOMER C3
Adder
49.471
20083826HOMER C2
Adder
46.731
20083726HOMER C1
Adder
46.242
20089226LOOKOUT
Solar/Wind Harmer
0.571
20066626SHAWVL 4
50/50
2.515
20066526SHAWVL 3
50/50
2.496
20071526SHAWVL 1
50/50
1.686
200642SENECA#1
50/50
1.715
200643SENECA#2
50/50
1.601
941231AE2-117 GEN
Solar/Wind Harmer
5.787
962411AG1-090 GEN
Solar/Wind Harmer
18.66
970305AG2-200 GEN
Solar/Wind Harmer
1.72
203857AF2-221 C
Solar/Wind Harmer
1.308
944781AF1-143 GEN
Solar/Wind Harmer
6.492
238206AE2-263_GEN
Solar/Wind Harmer
20.555
970555AG2-356 GEN
Solar/Wind Harmer
1.538
966771AG1-548 GEN
Solar/Wind Harmer
9.219
966771AG1-548 GEN
Solar/Wind Harmer
1.787
200917MEHOOPANY_G
Solar/Wind Harmer
1.735
209067AE2-060 GEN
Solar/Wind Helper
0.081
238183AE2-316 GEN
Solar/Wind Harmer
5.546
20335126GROZ1-110
Adder
2.148
970899AG2-561 GEN
Solar/Wind Harmer
1.83
238219AF1-167 C
Solar/Wind Harmer
0.968
965131AG1-378 GEN
Solar/Wind Harmer
3.929
203993AD2-133_GEN1
Solar/Wind Harmer
2.952
20303426NA_O38_P22
Solar/Wind Harmer
2.753
960051AF2-296 GEN
Solar/Wind Harmer
3.199
957161AF2-010 GEN
Solar/Wind Harmer
4.881
203948AG1-140 C
Solar/Wind Harmer
0.166
203860AG1-193 C
Solar/Wind Harmer
0.618
20082926HNSMLK 2
Adder
3.493
203853AF1-134 C O1
Solar/Wind Harmer
0.967
203804AE2-113_GEN
Solar/Wind Harmer
6.387
203818AF1-086 GEN
Solar/Wind Harmer
3.194
203835AF1-098 GEN
Solar/Wind Harmer
1.692
203859AF2-294 C
Solar/Wind Harmer
1.08
203980AG1-197 GEN
Solar/Wind Harmer
0.872
20091326SHAW-D
50/50
1.444
957561AF2-050 GEN
Solar/Wind Harmer
7.886
203813AE2-344_GEN
Solar/Wind Harmer
6.81
970267AG2-176 GEN
Solar/Wind Harmer
8.764
961971AG1-040 GEN
Solar/Wind Harmer
0.352
203952AE2-129 C
Solar/Wind Harmer
1.188
20090526Q36
Solar/Wind Harmer
2.952
20091526CHSTN_FL
Solar/Wind Harmer
1.369
964201AG1-281 GEN
Solar/Wind Harmer
0.907
20326126BLOSSBCT
Adder
1.905
959471AF2-238 GEN
Solar/Wind Harmer
1.538
203830AF1-094 GEN
Solar/Wind Harmer
0.383
203979AG1-198 GEN
Solar/Wind Harmer
0.23
20082826HNSMLK 1
Adder
3.493
20083026HNSMLK 3
Adder
3.493
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.772
LGEELTFEXP_LGEE->PJM
CLTF
0.407
MECLTFEXP_MEC->PJM
CLTF
1.037
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.622
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.538
TVALTFEXP_TVA->PJM
CLTF
0.442
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.763
CPLELTFEXP_CPLE->PJM
CLTF
0.095
SIGELTFEXP_SIGE->PJM
CLTF
0.031
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.083
WECLTFEXP_WEC->PJM
CLTF
0.254
LAGNLTFEXP_LAGN->PJM
CLTF
0.922

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-2_PN-115-031_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-031_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.41 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:670.0
MW Contribution:
5.41
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-031_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.29 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:718.65
MW Contribution:
5.36
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
32.196
20064926PENNTECH
50/50
0.431
203855AF2-088 C
Solar/Wind Harmer
0.398
20084626FORWARD
Solar/Wind Harmer
0.646
203843AF2-002_GEN
Solar/Wind Harmer
0.791
20335026MILZ1-092
Adder
1.581
970647AG2-420 GEN
Solar/Wind Harmer
0.149
20089026BF_G21_K23
Solar/Wind Harmer
0.443
203947AF1-006 C
Solar/Wind Harmer
0.318
965121AG1-377 GEN
Solar/Wind Harmer
3.838
203846AF2-130 C
Solar/Wind Harmer
0.39
203955AF1-039 C O1
Solar/Wind Harmer
0.227
20334726NME_Y1-047
Adder
1.125
200644SENECA#3
50/50
0.215
20088626ARWF_N39
Solar/Wind Harmer
3.322
238217AF1-153 C O1
Solar/Wind Harmer
3.349
20094526CT_V3-030
Solar/Wind Harmer
0.801
203844AF2-092 C
Solar/Wind Harmer
1.187
20334926Z1-069 C
Solar/Wind Harmer
1.8
20088926STNY CRK
Solar/Wind Harmer
1.025
20089126CSLMN_L13
Solar/Wind Harmer
0.559
20083226HNSMLK 5
Adder
3.408
203926AA2-133 GEN
Adder
1.325
203854AF2-039 C
Solar/Wind Harmer
0.826
203841AF2-001_GEN
Solar/Wind Harmer
1.583
20079426CONEMAGH
Adder
0.943
970663AG2-429 GEN
Solar/Wind Harmer
0.717
203856AF2-165 C
Solar/Wind Harmer
0.775
20328326MANOR_T86
Adder
0.092
962511AG1-100 GEN
Solar/Wind Harmer
0.342
20081226ALY HYDR
50/50
0.412
216419AE2-001 C
Solar/Wind Harmer
6.166
972169AH1-667 GEN
Solar/Wind Harmer
2.753
20088826HIGHLAND
Solar/Wind Harmer
1.591
203839AF1-321 GEN
Solar/Wind Harmer
1.583
20083426SW_E13_K22
Solar/Wind Harmer
0.221
946071AF1-272 GEN
Solar/Wind Harmer
2.288
203963AG1-253 GEN
Solar/Wind Harmer
0.247
238202AE2-262_GEN
Solar/Wind Harmer
21.442
20120126WRREN CT
Adder
6.25
20092526R32
Solar/Wind Harmer
1.705
971879AH1-460 GEN
Solar/Wind Harmer
5.41
941421AE2-139 GEN
Solar/Wind Harmer
2.264
20398826ARMNA MT
Solar/Wind Harmer
1.673
970647AG2-420 GEN
Solar/Wind Harmer
1.281
20083126HNSMLK 4
Adder
3.408
203962AF1-287 GEN
Solar/Wind Harmer
1.148
202652Y1-033 WT C
Solar/Wind Harmer
0.467
209137AF2-361 C
Solar/Wind Helper
1.389
203946AE2-131 C
Solar/Wind Harmer
1.16
203954AE2-126 C
Solar/Wind Harmer
1.092
203961AE2-224 GEN
Solar/Wind Harmer
4.657
946381AF1-302 GEN
Solar/Wind Harmer
2.714
940863AE2-074 GEN
Solar/Wind Harmer
1.129
970631AG2-411 GEN
Solar/Wind Harmer
3.895
970663AG2-429 GEN
Solar/Wind Harmer
2.967
238215AE2-248 C
Solar/Wind Harmer
5.071
203987AE2-118 C
Solar/Wind Harmer
5.243
203940AF1-140 C
Solar/Wind Harmer
0.55
20083926HOMER C3
Adder
48.207
20083826HOMER C2
Adder
45.537
20083726HOMER C1
Adder
45.031
20089226LOOKOUT
Solar/Wind Harmer
0.558
20066626SHAWVL 4
50/50
2.459
20066526SHAWVL 3
50/50
2.44
20071526SHAWVL 1
50/50
1.648
200642SENECA#1
50/50
1.675
200643SENECA#2
50/50
1.564
941231AE2-117 GEN
Solar/Wind Harmer
5.63
962411AG1-090 GEN
Solar/Wind Harmer
18.23
970305AG2-200 GEN
Solar/Wind Harmer
1.68
203857AF2-221 C
Solar/Wind Harmer
1.276
944781AF1-143 GEN
Solar/Wind Harmer
6.345
970555AG2-356 GEN
Solar/Wind Harmer
1.495
966771AG1-548 GEN
Solar/Wind Harmer
9.004
966771AG1-548 GEN
Solar/Wind Harmer
1.745
200917MEHOOPANY_G
Solar/Wind Harmer
1.674
209067AE2-060 GEN
Solar/Wind Helper
0.083
238183AE2-316 GEN
Solar/Wind Harmer
5.419
970899AG2-561 GEN
Solar/Wind Harmer
1.786
20335126GROZ1-110
Adder
2.09
238219AF1-167 C
Solar/Wind Harmer
0.945
965131AG1-378 GEN
Solar/Wind Harmer
3.838
203993AD2-133_GEN1
Solar/Wind Harmer
2.882
20303426NA_O38_P22
Solar/Wind Harmer
2.689
960051AF2-296 GEN
Solar/Wind Harmer
3.126
957161AF2-010 GEN
Solar/Wind Harmer
4.767
203948AG1-140 C
Solar/Wind Harmer
0.162
203860AG1-193 C
Solar/Wind Harmer
0.603
20082926HNSMLK 2
Adder
3.408
203853AF1-134 C O1
Solar/Wind Harmer
0.945
203804AE2-113_GEN
Solar/Wind Harmer
6.239
203818AF1-086 GEN
Solar/Wind Harmer
3.119
203835AF1-098 GEN
Solar/Wind Harmer
1.653
203859AF2-294 C
Solar/Wind Harmer
1.048
20091326SHAW-D
50/50
1.411
957561AF2-050 GEN
Solar/Wind Harmer
7.701
203813AE2-344_GEN
Solar/Wind Harmer
6.652
970267AG2-176 GEN
Solar/Wind Harmer
8.558
961971AG1-040 GEN
Solar/Wind Harmer
0.344
203980AG1-197 GEN
Solar/Wind Harmer
0.852
238206AE2-263_GEN
Solar/Wind Harmer
20.103
203952AE2-129 C
Solar/Wind Harmer
1.16
20090526Q36
Solar/Wind Harmer
2.882
20091526CHSTN_FL
Solar/Wind Harmer
1.336
964201AG1-281 GEN
Solar/Wind Harmer
0.885
20326126BLOSSBCT
Adder
1.854
959471AF2-238 GEN
Solar/Wind Harmer
1.495
203830AF1-094 GEN
Solar/Wind Harmer
0.374
203979AG1-198 GEN
Solar/Wind Harmer
0.224
20082826HNSMLK 1
Adder
3.408
20083026HNSMLK 3
Adder
3.408
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.88
LGEELTFEXP_LGEE->PJM
CLTF
0.416
MECLTFEXP_MEC->PJM
CLTF
1.057
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.105
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.625
TVALTFEXP_TVA->PJM
CLTF
0.461
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.83
CPLELTFEXP_CPLE->PJM
CLTF
0.13
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.29
WECLTFEXP_WEC->PJM
CLTF
0.258
LAGNLTFEXP_LAGN->PJM
CLTF
0.959

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.99 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:655.0
MW Contribution:
6.41
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:111.95 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:691.83
MW Contribution:
6.37
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
31.158
20064926PENNTECH
50/50
0.425
203855AF2-088 C
Solar/Wind Harmer
0.389
20084626FORWARD
Solar/Wind Harmer
0.762
965121AG1-377 GEN
Solar/Wind Harmer
3.814
203846AF2-130 C
Solar/Wind Harmer
0.413
203955AF1-039 C O1
Solar/Wind Harmer
0.269
20334726NME_Y1-047
Adder
1.106
23732901CHBRG_I12
Adder
1.199
20088626ARWF_N39
Solar/Wind Harmer
3.469
238217AF1-153 C O1
Solar/Wind Harmer
3.279
20094526CT_V3-030
Solar/Wind Harmer
0.873
203844AF2-092 C
Solar/Wind Harmer
1.346
20088926STNY CRK
Solar/Wind Harmer
1.189
20334926Z1-069 C
Solar/Wind Harmer
1.862
20089126CSLMN_L13
Solar/Wind Harmer
0.662
20083226HNSMLK 5
Adder
3.689
203926AA2-133 GEN
Adder
1.311
203854AF2-039 C
Solar/Wind Harmer
0.808
20079426CONEMAGH
Adder
1.166
203841AF2-001_GEN
Solar/Wind Harmer
1.882
970663AG2-429 GEN
Solar/Wind Harmer
0.751
203856AF2-165 C
Solar/Wind Harmer
0.82
20328326MANOR_T86
Adder
0.092
962511AG1-100 GEN
Solar/Wind Harmer
0.358
20081226ALY HYDR
50/50
0.4
216419AE2-001 C
Solar/Wind Harmer
5.877
972169AH1-667 GEN
Solar/Wind Harmer
2.692
20088826HIGHLAND
Solar/Wind Harmer
1.831
203839AF1-321 GEN
Solar/Wind Harmer
1.882
20083426SW_E13_K22
Solar/Wind Harmer
0.261
946071AF1-272 GEN
Solar/Wind Harmer
2.581
203963AG1-253 GEN
Solar/Wind Harmer
0.256
238202AE2-262_GEN
Solar/Wind Harmer
20.574
20092526R32
Solar/Wind Harmer
1.962
20120126WRREN CT
Adder
6.316
971879AH1-460 GEN
Solar/Wind Harmer
6.413
20398826ARMNA MT
Solar/Wind Harmer
1.719
941421AE2-139 GEN
Solar/Wind Harmer
2.224
970647AG2-420 GEN
Solar/Wind Harmer
1.357
20083126HNSMLK 4
Adder
3.689
203962AF1-287 GEN
Solar/Wind Harmer
1.2
202652Y1-033 WT C
Solar/Wind Harmer
0.554
209137AF2-361 C
Solar/Wind Helper
1.498
203843AF2-002_GEN
Solar/Wind Harmer
0.941
20089026BF_G21_K23
Solar/Wind Harmer
0.524
20335026MILZ1-092
Adder
1.626
970647AG2-420 GEN
Solar/Wind Harmer
0.158
203947AF1-006 C
Solar/Wind Harmer
0.331
203946AE2-131 C
Solar/Wind Harmer
1.153
203954AE2-126 C
Solar/Wind Harmer
1.072
203961AE2-224 GEN
Solar/Wind Harmer
4.982
946381AF1-302 GEN
Solar/Wind Harmer
2.697
970631AG2-411 GEN
Solar/Wind Harmer
4.594
940863AE2-074 GEN
Solar/Wind Harmer
1.165
970663AG2-429 GEN
Solar/Wind Harmer
3.11
238215AE2-248 C
Solar/Wind Harmer
4.829
203987AE2-118 C
Solar/Wind Harmer
5.178
203940AF1-140 C
Solar/Wind Harmer
0.613
20390526W1-045 C
Solar/Wind Harmer
0.435
20083726HOMER C1
Adder
54.111
20083926HOMER C3
Adder
55.062
20083826HOMER C2
Adder
52.012
20089226LOOKOUT
Solar/Wind Harmer
0.66
20066626SHAWVL 4
50/50
2.379
20066526SHAWVL 3
50/50
2.362
20071526SHAWVL 1
50/50
1.603
941231AE2-117 GEN
Solar/Wind Harmer
5.517
20050326C.SLOPE
50/50
0.382
959381AF2-229 GEN
Solar/Wind Harmer
0.846
970555AG2-356 GEN
Solar/Wind Harmer
1.518
966771AG1-548 GEN
Solar/Wind Harmer
9.39
966771AG1-548 GEN
Solar/Wind Harmer
1.82
200917MEHOOPANY_G
Solar/Wind Harmer
1.645
209067AE2-060 GEN
Solar/Wind Helper
0.089
238183AE2-316 GEN
Solar/Wind Harmer
5.385
970899AG2-561 GEN
Solar/Wind Harmer
1.98
20335126GROZ1-110
Adder
2.068
238219AF1-167 C
Solar/Wind Harmer
0.983
962411AG1-090 GEN
Solar/Wind Harmer
18.117
203857AF2-221 C
Solar/Wind Harmer
1.508
970305AG2-200 GEN
Solar/Wind Harmer
1.698
944781AF1-143 GEN
Solar/Wind Harmer
7.505
965131AG1-378 GEN
Solar/Wind Harmer
3.814
20303426NA_O38_P22
Solar/Wind Harmer
2.808
203993AD2-133_GEN1
Solar/Wind Harmer
2.906
203975AE1-071-GEN
Solar/Wind Harmer
4.995
960051AF2-296 GEN
Solar/Wind Harmer
3.155
957161AF2-010 GEN
Solar/Wind Harmer
4.977
203860AG1-193 C
Solar/Wind Harmer
0.641
203948AG1-140 C
Solar/Wind Harmer
0.168
20082926HNSMLK 2
Adder
3.689
20091326SHAW-D
50/50
1.38
957561AF2-050 GEN
Solar/Wind Harmer
8.238
970267AG2-176 GEN
Solar/Wind Harmer
9.058
961971AG1-040 GEN
Solar/Wind Harmer
0.362
203813AE2-344_GEN
Solar/Wind Harmer
6.955
203853AF1-134 C O1
Solar/Wind Harmer
0.954
203804AE2-113_GEN
Solar/Wind Harmer
6.253
203818AF1-086 GEN
Solar/Wind Harmer
3.269
203982AD2-062_GEN
Solar/Wind Harmer
7.151
203835AF1-098 GEN
Solar/Wind Harmer
1.701
203859AF2-294 C
Solar/Wind Harmer
1.077
203980AG1-197 GEN
Solar/Wind Harmer
0.897
238206AE2-263_GEN
Solar/Wind Harmer
19.289
203952AE2-129 C
Solar/Wind Harmer
1.153
20090526Q36
Solar/Wind Harmer
2.906
20091526CHSTN_FL
Solar/Wind Harmer
1.404
964201AG1-281 GEN
Solar/Wind Harmer
0.94
20326126BLOSSBCT
Adder
1.886
959471AF2-238 GEN
Solar/Wind Harmer
1.518
203830AF1-094 GEN
Solar/Wind Harmer
0.39
203979AG1-198 GEN
Solar/Wind Harmer
0.234
20082826HNSMLK 1
Adder
3.689
20083026HNSMLK 3
Adder
3.689
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.944
LGEELTFEXP_LGEE->PJM
CLTF
0.469
MECLTFEXP_MEC->PJM
CLTF
1.186
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.819
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.927
TVALTFEXP_TVA->PJM
CLTF
0.548
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.151
CPLELTFEXP_CPLE->PJM
CLTF
0.245
SIGELTFEXP_SIGE->PJM
CLTF
0.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.383
WECLTFEXP_WEC->PJM
CLTF
0.286
LAGNLTFEXP_LAGN->PJM
CLTF
1.131

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_08_P22_102799_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_08_P22_102799_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.88 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:635.79
MW Contribution:
4.95
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_08_P22_102799_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.62 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:671.24
MW Contribution:
4.91
Bus #Bus NameTypeMW Contribution
965121AG1-377 GEN
Solar/Wind Harmer
3.542
203846AF2-130 C
Solar/Wind Harmer
0.358
203955AF1-039 C O1
Solar/Wind Harmer
0.211
23732901CHBRG_I12
Adder
1.185
200644SENECA#3
50/50
0.198
20088626ARWF_N39
Solar/Wind Harmer
3.063
238217AF1-153 C O1
Solar/Wind Harmer
3.088
20094526CT_V3-030
Solar/Wind Harmer
0.736
203844AF2-092 C
Solar/Wind Harmer
1.09
20334926Z1-069 C
Solar/Wind Harmer
1.641
20088926STNY CRK
Solar/Wind Harmer
0.941
20089126CSLMN_L13
Solar/Wind Harmer
0.516
20083226HNSMLK 5
Adder
3.12
203926AA2-133 GEN
Adder
1.173
203854AF2-039 C
Solar/Wind Harmer
0.762
203841AF2-001_GEN
Solar/Wind Harmer
1.449
20079426CONEMAGH
Adder
0.861
970663AG2-429 GEN
Solar/Wind Harmer
0.656
203856AF2-165 C
Solar/Wind Harmer
0.71
20328326MANOR_T86
Adder
0.083
962511AG1-100 GEN
Solar/Wind Harmer
0.314
20081226ALY HYDR
50/50
0.382
216419AE2-001 C
Solar/Wind Harmer
5.703
238202AE2-262_GEN
Solar/Wind Harmer
19.812
20120126WRREN CT
Adder
5.748
20092526R32
Solar/Wind Harmer
1.564
971879AH1-460 GEN
Solar/Wind Harmer
4.954
941421AE2-139 GEN
Solar/Wind Harmer
2.033
20398826ARMNA MT
Solar/Wind Harmer
1.51
970647AG2-420 GEN
Solar/Wind Harmer
1.174
20083126HNSMLK 4
Adder
3.12
203962AF1-287 GEN
Solar/Wind Harmer
1.054
202652Y1-033 WT C
Solar/Wind Harmer
0.434
209137AF2-361 C
Solar/Wind Helper
1.498
972169AH1-667 GEN
Solar/Wind Harmer
2.541
20088826HIGHLAND
Solar/Wind Harmer
1.459
203839AF1-321 GEN
Solar/Wind Harmer
1.449
20083426SW_E13_K22
Solar/Wind Harmer
0.203
946071AF1-272 GEN
Solar/Wind Harmer
2.087
203963AG1-253 GEN
Solar/Wind Harmer
0.227
20072226SHAWVL 2
50/50
29.728
20064926PENNTECH
50/50
0.397
203855AF2-088 C
Solar/Wind Harmer
0.367
20084626FORWARD
Solar/Wind Harmer
0.592
203843AF2-002_GEN
Solar/Wind Harmer
0.725
20335026MILZ1-092
Adder
1.425
970647AG2-420 GEN
Solar/Wind Harmer
0.137
20089026BF_G21_K23
Solar/Wind Harmer
0.409
203947AF1-006 C
Solar/Wind Harmer
0.292
203946AE2-131 C
Solar/Wind Harmer
1.071
203954AE2-126 C
Solar/Wind Harmer
1.007
203961AE2-224 GEN
Solar/Wind Harmer
4.288
946381AF1-302 GEN
Solar/Wind Harmer
2.499
940863AE2-074 GEN
Solar/Wind Harmer
1.032
970631AG2-411 GEN
Solar/Wind Harmer
3.569
970663AG2-429 GEN
Solar/Wind Harmer
2.718
238215AE2-248 C
Solar/Wind Harmer
4.69
203987AE2-118 C
Solar/Wind Harmer
4.856
20390526W1-045 C
Solar/Wind Harmer
0.429
203940AF1-140 C
Solar/Wind Harmer
0.506
20083926HOMER C3
Adder
43.932
20083826HOMER C2
Adder
41.499
20083726HOMER C1
Adder
40.958
20089226LOOKOUT
Solar/Wind Harmer
0.515
959381AF2-229 GEN
Solar/Wind Harmer
0.834
970555AG2-356 GEN
Solar/Wind Harmer
1.349
966771AG1-548 GEN
Solar/Wind Harmer
8.267
966771AG1-548 GEN
Solar/Wind Harmer
1.602
209067AE2-060 GEN
Solar/Wind Helper
0.089
238183AE2-316 GEN
Solar/Wind Harmer
4.99
970899AG2-561 GEN
Solar/Wind Harmer
1.636
20335126GROZ1-110
Adder
1.893
238219AF1-167 C
Solar/Wind Harmer
0.866
20066626SHAWVL 4
50/50
2.27
20066526SHAWVL 3
50/50
2.253
20071526SHAWVL 1
50/50
1.522
200642SENECA#1
50/50
1.541
200643SENECA#2
50/50
1.439
941231AE2-117 GEN
Solar/Wind Harmer
5.22
962411AG1-090 GEN
Solar/Wind Harmer
16.824
970305AG2-200 GEN
Solar/Wind Harmer
1.545
203857AF2-221 C
Solar/Wind Harmer
1.169
944781AF1-143 GEN
Solar/Wind Harmer
5.855
965131AG1-378 GEN
Solar/Wind Harmer
3.542
203975AE1-071-GEN
Solar/Wind Harmer
4.919
203993AD2-133_GEN1
Solar/Wind Harmer
2.66
20303426NA_O38_P22
Solar/Wind Harmer
2.479
960051AF2-296 GEN
Solar/Wind Harmer
2.88
957161AF2-010 GEN
Solar/Wind Harmer
4.376
203948AG1-140 C
Solar/Wind Harmer
0.148
203860AG1-193 C
Solar/Wind Harmer
0.553
20082926HNSMLK 2
Adder
3.12
20091326SHAW-D
50/50
1.303
957561AF2-050 GEN
Solar/Wind Harmer
7.091
203813AE2-344_GEN
Solar/Wind Harmer
6.108
970267AG2-176 GEN
Solar/Wind Harmer
7.851
961971AG1-040 GEN
Solar/Wind Harmer
0.316
203853AF1-134 C O1
Solar/Wind Harmer
0.871
203804AE2-113_GEN
Solar/Wind Harmer
5.738
203818AF1-086 GEN
Solar/Wind Harmer
2.868
203982AD2-062_GEN
Solar/Wind Harmer
7.051
203835AF1-098 GEN
Solar/Wind Harmer
1.519
203859AF2-294 C
Solar/Wind Harmer
0.939
203980AG1-197 GEN
Solar/Wind Harmer
0.782
238206AE2-263_GEN
Solar/Wind Harmer
18.575
203952AE2-129 C
Solar/Wind Harmer
1.071
20090526Q36
Solar/Wind Harmer
2.66
20091526CHSTN_FL
Solar/Wind Harmer
1.231
964201AG1-281 GEN
Solar/Wind Harmer
0.815
20326126BLOSSBCT
Adder
1.68
959471AF2-238 GEN
Solar/Wind Harmer
1.349
203830AF1-094 GEN
Solar/Wind Harmer
0.343
203979AG1-198 GEN
Solar/Wind Harmer
0.206
20082826HNSMLK 1
Adder
3.12
20083026HNSMLK 3
Adder
3.12
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.981
LGEELTFEXP_LGEE->PJM
CLTF
0.433
MECLTFEXP_MEC->PJM
CLTF
1.093
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.861
TVALTFEXP_TVA->PJM
CLTF
0.507
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.987
CPLELTFEXP_CPLE->PJM
CLTF
0.228
SIGELTFEXP_SIGE->PJM
CLTF
0.033
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.739
WECLTFEXP_WEC->PJM
CLTF
0.264
LAGNLTFEXP_LAGN->PJM
CLTF
1.045

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_10_P22_100579_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_10_P22_100579_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.35 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:632.54
MW Contribution:
4.85
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_10_P22_100579_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.33 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:669.47
MW Contribution:
4.81
Bus #Bus NameTypeMW Contribution
965121AG1-377 GEN
Solar/Wind Harmer
3.434
203846AF2-130 C
Solar/Wind Harmer
0.35
203955AF1-039 C O1
Solar/Wind Harmer
0.207
23732901CHBRG_I12
Adder
1.115
200644SENECA#3
50/50
0.192
20088626ARWF_N39
Solar/Wind Harmer
2.973
238217AF1-153 C O1
Solar/Wind Harmer
2.996
20094526CT_V3-030
Solar/Wind Harmer
0.717
203844AF2-092 C
Solar/Wind Harmer
1.064
20334926Z1-069 C
Solar/Wind Harmer
1.605
20088926STNY CRK
Solar/Wind Harmer
0.92
20089126CSLMN_L13
Solar/Wind Harmer
0.505
20083226HNSMLK 5
Adder
3.063
203926AA2-133 GEN
Adder
1.16
203854AF2-039 C
Solar/Wind Harmer
0.739
203841AF2-001_GEN
Solar/Wind Harmer
1.419
20079426CONEMAGH
Adder
0.845
970663AG2-429 GEN
Solar/Wind Harmer
0.643
203856AF2-165 C
Solar/Wind Harmer
0.696
20328326MANOR_T86
Adder
0.081
962511AG1-100 GEN
Solar/Wind Harmer
0.308
238202AE2-262_GEN
Solar/Wind Harmer
19.175
20120126WRREN CT
Adder
5.599
20092526R32
Solar/Wind Harmer
1.527
971879AH1-460 GEN
Solar/Wind Harmer
4.85
941421AE2-139 GEN
Solar/Wind Harmer
1.996
20398826ARMNA MT
Solar/Wind Harmer
1.483
970647AG2-420 GEN
Solar/Wind Harmer
1.151
20083126HNSMLK 4
Adder
3.063
203962AF1-287 GEN
Solar/Wind Harmer
1.033
202652Y1-033 WT C
Solar/Wind Harmer
0.426
209137AF2-361 C
Solar/Wind Helper
1.912
20081226ALY HYDR
50/50
0.369
216419AE2-001 C
Solar/Wind Harmer
5.515
972169AH1-667 GEN
Solar/Wind Harmer
2.463
20088826HIGHLAND
Solar/Wind Harmer
1.425
203839AF1-321 GEN
Solar/Wind Harmer
1.419
20083426SW_E13_K22
Solar/Wind Harmer
0.199
946071AF1-272 GEN
Solar/Wind Harmer
2.05
203963AG1-253 GEN
Solar/Wind Harmer
0.222
20072226SHAWVL 2
50/50
28.794
20064926PENNTECH
50/50
0.386
203855AF2-088 C
Solar/Wind Harmer
0.356
20084626FORWARD
Solar/Wind Harmer
0.58
203843AF2-002_GEN
Solar/Wind Harmer
0.71
20335026MILZ1-092
Adder
1.4
970647AG2-420 GEN
Solar/Wind Harmer
0.134
20089026BF_G21_K23
Solar/Wind Harmer
0.4
203947AF1-006 C
Solar/Wind Harmer
0.286
203946AE2-131 C
Solar/Wind Harmer
1.038
203954AE2-126 C
Solar/Wind Harmer
0.977
203961AE2-224 GEN
Solar/Wind Harmer
4.167
946381AF1-302 GEN
Solar/Wind Harmer
2.43
940863AE2-074 GEN
Solar/Wind Harmer
1.008
970631AG2-411 GEN
Solar/Wind Harmer
3.493
970663AG2-429 GEN
Solar/Wind Harmer
2.663
238215AE2-248 C
Solar/Wind Harmer
4.535
203987AE2-118 C
Solar/Wind Harmer
4.701
20390526W1-045 C
Solar/Wind Harmer
0.406
203940AF1-140 C
Solar/Wind Harmer
0.493
20083926HOMER C3
Adder
43.161
20083826HOMER C2
Adder
40.77
20083726HOMER C1
Adder
40.311
20089226LOOKOUT
Solar/Wind Harmer
0.504
959381AF2-229 GEN
Solar/Wind Harmer
0.789
970555AG2-356 GEN
Solar/Wind Harmer
1.324
966771AG1-548 GEN
Solar/Wind Harmer
8.097
966771AG1-548 GEN
Solar/Wind Harmer
1.569
209067AE2-060 GEN
Solar/Wind Helper
0.114
238183AE2-316 GEN
Solar/Wind Harmer
4.851
970899AG2-561 GEN
Solar/Wind Harmer
1.6
20335126GROZ1-110
Adder
1.852
238219AF1-167 C
Solar/Wind Harmer
0.848
20066626SHAWVL 4
50/50
2.199
20066526SHAWVL 3
50/50
2.183
20071526SHAWVL 1
50/50
1.474
200642SENECA#1
50/50
1.5
200643SENECA#2
50/50
1.401
941231AE2-117 GEN
Solar/Wind Harmer
5.051
962411AG1-090 GEN
Solar/Wind Harmer
16.313
970305AG2-200 GEN
Solar/Wind Harmer
1.505
203857AF2-221 C
Solar/Wind Harmer
1.144
944781AF1-143 GEN
Solar/Wind Harmer
5.735
965131AG1-378 GEN
Solar/Wind Harmer
3.434
203975AE1-071-GEN
Solar/Wind Harmer
4.703
203993AD2-133_GEN1
Solar/Wind Harmer
2.58
20303426NA_O38_P22
Solar/Wind Harmer
2.407
960051AF2-296 GEN
Solar/Wind Harmer
2.797
957161AF2-010 GEN
Solar/Wind Harmer
4.286
203948AG1-140 C
Solar/Wind Harmer
0.145
203860AG1-193 C
Solar/Wind Harmer
0.543
20082926HNSMLK 2
Adder
3.063
20091326SHAW-D
50/50
1.262
957561AF2-050 GEN
Solar/Wind Harmer
6.892
203813AE2-344_GEN
Solar/Wind Harmer
5.987
970267AG2-176 GEN
Solar/Wind Harmer
7.7
961971AG1-040 GEN
Solar/Wind Harmer
0.31
203853AF1-134 C O1
Solar/Wind Harmer
0.846
203804AE2-113_GEN
Solar/Wind Harmer
5.58
203818AF1-086 GEN
Solar/Wind Harmer
2.792
203982AD2-062_GEN
Solar/Wind Harmer
6.679
203835AF1-098 GEN
Solar/Wind Harmer
1.485
203859AF2-294 C
Solar/Wind Harmer
0.926
203980AG1-197 GEN
Solar/Wind Harmer
0.767
238206AE2-263_GEN
Solar/Wind Harmer
17.977
203952AE2-129 C
Solar/Wind Harmer
1.038
20090526Q36
Solar/Wind Harmer
2.58
20091526CHSTN_FL
Solar/Wind Harmer
1.196
964201AG1-281 GEN
Solar/Wind Harmer
0.793
20326126BLOSSBCT
Adder
1.646
959471AF2-238 GEN
Solar/Wind Harmer
1.324
203830AF1-094 GEN
Solar/Wind Harmer
0.336
203979AG1-198 GEN
Solar/Wind Harmer
0.202
20082826HNSMLK 1
Adder
3.063
20083026HNSMLK 3
Adder
3.063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.988
LGEELTFEXP_LGEE->PJM
CLTF
0.433
MECLTFEXP_MEC->PJM
CLTF
1.093
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.844
TVALTFEXP_TVA->PJM
CLTF
0.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.982
CPLELTFEXP_CPLE->PJM
CLTF
0.22
SIGELTFEXP_SIGE->PJM
CLTF
0.033
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.727
WECLTFEXP_WEC->PJM
CLTF
0.264
LAGNLTFEXP_LAGN->PJM
CLTF
1.041

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_48_P71_102649_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_48_P71_102649_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.15 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:631.26
MW Contribution:
4.96
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_48_P71_102649_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.97 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:667.24
MW Contribution:
4.91
Bus #Bus NameTypeMW Contribution
965121AG1-377 GEN
Solar/Wind Harmer
3.542
203846AF2-130 C
Solar/Wind Harmer
0.358
203955AF1-039 C O1
Solar/Wind Harmer
0.211
23732901CHBRG_I12
Adder
1.185
200644SENECA#3
50/50
0.198
20088626ARWF_N39
Solar/Wind Harmer
3.063
238217AF1-153 C O1
Solar/Wind Harmer
3.089
20094526CT_V3-030
Solar/Wind Harmer
0.736
203844AF2-092 C
Solar/Wind Harmer
1.091
20334926Z1-069 C
Solar/Wind Harmer
1.642
20088926STNY CRK
Solar/Wind Harmer
0.941
20089126CSLMN_L13
Solar/Wind Harmer
0.516
20083226HNSMLK 5
Adder
3.121
203926AA2-133 GEN
Adder
1.174
203854AF2-039 C
Solar/Wind Harmer
0.762
203841AF2-001_GEN
Solar/Wind Harmer
1.45
20079426CONEMAGH
Adder
0.862
970663AG2-429 GEN
Solar/Wind Harmer
0.657
203856AF2-165 C
Solar/Wind Harmer
0.71
20328326MANOR_T86
Adder
0.083
962511AG1-100 GEN
Solar/Wind Harmer
0.314
238202AE2-262_GEN
Solar/Wind Harmer
19.814
20120126WRREN CT
Adder
5.749
20092526R32
Solar/Wind Harmer
1.564
971879AH1-460 GEN
Solar/Wind Harmer
4.956
941421AE2-139 GEN
Solar/Wind Harmer
2.034
20398826ARMNA MT
Solar/Wind Harmer
1.511
970647AG2-420 GEN
Solar/Wind Harmer
1.175
20083126HNSMLK 4
Adder
3.121
203962AF1-287 GEN
Solar/Wind Harmer
1.054
202652Y1-033 WT C
Solar/Wind Harmer
0.435
209137AF2-361 C
Solar/Wind Helper
1.498
20081226ALY HYDR
50/50
0.382
216419AE2-001 C
Solar/Wind Harmer
5.703
972169AH1-667 GEN
Solar/Wind Harmer
2.541
20088826HIGHLAND
Solar/Wind Harmer
1.46
203839AF1-321 GEN
Solar/Wind Harmer
1.45
20083426SW_E13_K22
Solar/Wind Harmer
0.203
946071AF1-272 GEN
Solar/Wind Harmer
2.087
203963AG1-253 GEN
Solar/Wind Harmer
0.227
20072226SHAWVL 2
50/50
29.731
20064926PENNTECH
50/50
0.397
203855AF2-088 C
Solar/Wind Harmer
0.367
20084626FORWARD
Solar/Wind Harmer
0.592
203843AF2-002_GEN
Solar/Wind Harmer
0.725
20335026MILZ1-092
Adder
1.426
970647AG2-420 GEN
Solar/Wind Harmer
0.137
20089026BF_G21_K23
Solar/Wind Harmer
0.409
203947AF1-006 C
Solar/Wind Harmer
0.293
203946AE2-131 C
Solar/Wind Harmer
1.071
203954AE2-126 C
Solar/Wind Harmer
1.008
203961AE2-224 GEN
Solar/Wind Harmer
4.288
946381AF1-302 GEN
Solar/Wind Harmer
2.5
940863AE2-074 GEN
Solar/Wind Harmer
1.033
970631AG2-411 GEN
Solar/Wind Harmer
3.57
970663AG2-429 GEN
Solar/Wind Harmer
2.719
238215AE2-248 C
Solar/Wind Harmer
4.691
203987AE2-118 C
Solar/Wind Harmer
4.857
20390526W1-045 C
Solar/Wind Harmer
0.429
203940AF1-140 C
Solar/Wind Harmer
0.506
20083926HOMER C3
Adder
43.949
20083826HOMER C2
Adder
41.515
20083726HOMER C1
Adder
40.974
20089226LOOKOUT
Solar/Wind Harmer
0.515
959381AF2-229 GEN
Solar/Wind Harmer
0.834
970555AG2-356 GEN
Solar/Wind Harmer
1.35
966771AG1-548 GEN
Solar/Wind Harmer
8.271
966771AG1-548 GEN
Solar/Wind Harmer
1.603
209067AE2-060 GEN
Solar/Wind Helper
0.089
238183AE2-316 GEN
Solar/Wind Harmer
4.991
970899AG2-561 GEN
Solar/Wind Harmer
1.637
20335126GROZ1-110
Adder
1.894
238219AF1-167 C
Solar/Wind Harmer
0.866
20066626SHAWVL 4
50/50
2.27
20066526SHAWVL 3
50/50
2.254
20071526SHAWVL 1
50/50
1.522
200642SENECA#1
50/50
1.541
200643SENECA#2
50/50
1.439
941231AE2-117 GEN
Solar/Wind Harmer
5.221
962411AG1-090 GEN
Solar/Wind Harmer
16.827
970305AG2-200 GEN
Solar/Wind Harmer
1.546
203857AF2-221 C
Solar/Wind Harmer
1.169
944781AF1-143 GEN
Solar/Wind Harmer
5.858
965131AG1-378 GEN
Solar/Wind Harmer
3.542
203975AE1-071-GEN
Solar/Wind Harmer
4.919
203993AD2-133_GEN1
Solar/Wind Harmer
2.66
20303426NA_O38_P22
Solar/Wind Harmer
2.48
960051AF2-296 GEN
Solar/Wind Harmer
2.88
957161AF2-010 GEN
Solar/Wind Harmer
4.378
203948AG1-140 C
Solar/Wind Harmer
0.148
203860AG1-193 C
Solar/Wind Harmer
0.553
20082926HNSMLK 2
Adder
3.121
20091326SHAW-D
50/50
1.303
957561AF2-050 GEN
Solar/Wind Harmer
7.092
203813AE2-344_GEN
Solar/Wind Harmer
6.111
970267AG2-176 GEN
Solar/Wind Harmer
7.854
961971AG1-040 GEN
Solar/Wind Harmer
0.316
203853AF1-134 C O1
Solar/Wind Harmer
0.871
203804AE2-113_GEN
Solar/Wind Harmer
5.739
203818AF1-086 GEN
Solar/Wind Harmer
2.868
203982AD2-062_GEN
Solar/Wind Harmer
7.053
203835AF1-098 GEN
Solar/Wind Harmer
1.519
203859AF2-294 C
Solar/Wind Harmer
0.94
203980AG1-197 GEN
Solar/Wind Harmer
0.782
238206AE2-263_GEN
Solar/Wind Harmer
18.577
203952AE2-129 C
Solar/Wind Harmer
1.071
20090526Q36
Solar/Wind Harmer
2.66
20091526CHSTN_FL
Solar/Wind Harmer
1.231
964201AG1-281 GEN
Solar/Wind Harmer
0.816
20326126BLOSSBCT
Adder
1.681
959471AF2-238 GEN
Solar/Wind Harmer
1.35
203830AF1-094 GEN
Solar/Wind Harmer
0.343
203979AG1-198 GEN
Solar/Wind Harmer
0.206
20082826HNSMLK 1
Adder
3.121
20083026HNSMLK 3
Adder
3.121
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.017
LGEELTFEXP_LGEE->PJM
CLTF
0.435
MECLTFEXP_MEC->PJM
CLTF
1.097
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.289
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.868
TVALTFEXP_TVA->PJM
CLTF
0.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.997
CPLELTFEXP_CPLE->PJM
CLTF
0.23
SIGELTFEXP_SIGE->PJM
CLTF
0.033
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.772
WECLTFEXP_WEC->PJM
CLTF
0.265
LAGNLTFEXP_LAGN->PJM
CLTF
1.05

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PECO_P7-1_220-9091_SRT-A/* $ BUCKS $ PECO_P7-1_220-9091 $ DCT


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PECO_P7-1_220-9091_SRT-A/* $ BUCKS $ PECO_P7-1_220-9091 $ DCT
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.49 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:627.23
MW Contribution:
4.96
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PECO_P7-1_220-9091_SRT-A/* $ BUCKS $ PECO_P7-1_220-9091 $ DCT
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.53 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:664.55
MW Contribution:
4.91
Bus #Bus NameTypeMW Contribution
965121AG1-377 GEN
Solar/Wind Harmer
3.543
203846AF2-130 C
Solar/Wind Harmer
0.358
203955AF1-039 C O1
Solar/Wind Harmer
0.211
23732901CHBRG_I12
Adder
1.186
200644SENECA#3
50/50
0.198
20088626ARWF_N39
Solar/Wind Harmer
3.064
238217AF1-153 C O1
Solar/Wind Harmer
3.089
20094526CT_V3-030
Solar/Wind Harmer
0.736
203844AF2-092 C
Solar/Wind Harmer
1.091
20334926Z1-069 C
Solar/Wind Harmer
1.642
20088926STNY CRK
Solar/Wind Harmer
0.942
20089126CSLMN_L13
Solar/Wind Harmer
0.517
20083226HNSMLK 5
Adder
3.123
203926AA2-133 GEN
Adder
1.175
203854AF2-039 C
Solar/Wind Harmer
0.763
203841AF2-001_GEN
Solar/Wind Harmer
1.45
20079426CONEMAGH
Adder
0.862
970663AG2-429 GEN
Solar/Wind Harmer
0.657
203856AF2-165 C
Solar/Wind Harmer
0.711
20328326MANOR_T86
Adder
0.083
962511AG1-100 GEN
Solar/Wind Harmer
0.314
238202AE2-262_GEN
Solar/Wind Harmer
19.817
20120126WRREN CT
Adder
5.751
20092526R32
Solar/Wind Harmer
1.565
971879AH1-460 GEN
Solar/Wind Harmer
4.958
941421AE2-139 GEN
Solar/Wind Harmer
2.035
20398826ARMNA MT
Solar/Wind Harmer
1.511
970647AG2-420 GEN
Solar/Wind Harmer
1.175
20083126HNSMLK 4
Adder
3.123
203962AF1-287 GEN
Solar/Wind Harmer
1.055
202652Y1-033 WT C
Solar/Wind Harmer
0.435
209137AF2-361 C
Solar/Wind Helper
1.497
20081226ALY HYDR
50/50
0.382
216419AE2-001 C
Solar/Wind Harmer
5.704
972169AH1-667 GEN
Solar/Wind Harmer
2.542
20088826HIGHLAND
Solar/Wind Harmer
1.46
203839AF1-321 GEN
Solar/Wind Harmer
1.45
20083426SW_E13_K22
Solar/Wind Harmer
0.203
946071AF1-272 GEN
Solar/Wind Harmer
2.089
203963AG1-253 GEN
Solar/Wind Harmer
0.227
20072226SHAWVL 2
50/50
29.736
20064926PENNTECH
50/50
0.398
203855AF2-088 C
Solar/Wind Harmer
0.367
20084626FORWARD
Solar/Wind Harmer
0.593
203843AF2-002_GEN
Solar/Wind Harmer
0.725
20335026MILZ1-092
Adder
1.427
970647AG2-420 GEN
Solar/Wind Harmer
0.137
20089026BF_G21_K23
Solar/Wind Harmer
0.409
203947AF1-006 C
Solar/Wind Harmer
0.293
203946AE2-131 C
Solar/Wind Harmer
1.071
203954AE2-126 C
Solar/Wind Harmer
1.008
203961AE2-224 GEN
Solar/Wind Harmer
4.29
946381AF1-302 GEN
Solar/Wind Harmer
2.5
940863AE2-074 GEN
Solar/Wind Harmer
1.033
970631AG2-411 GEN
Solar/Wind Harmer
3.571
970663AG2-429 GEN
Solar/Wind Harmer
2.72
238215AE2-248 C
Solar/Wind Harmer
4.691
203987AE2-118 C
Solar/Wind Harmer
4.857
20390526W1-045 C
Solar/Wind Harmer
0.429
203940AF1-140 C
Solar/Wind Harmer
0.506
20083926HOMER C3
Adder
43.973
20083826HOMER C2
Adder
41.538
20083726HOMER C1
Adder
40.998
20089226LOOKOUT
Solar/Wind Harmer
0.515
959381AF2-229 GEN
Solar/Wind Harmer
0.835
970555AG2-356 GEN
Solar/Wind Harmer
1.351
238183AE2-316 GEN
Solar/Wind Harmer
4.992
970899AG2-561 GEN
Solar/Wind Harmer
1.637
20335126GROZ1-110
Adder
1.894
238219AF1-167 C
Solar/Wind Harmer
0.866
20066626SHAWVL 4
50/50
2.271
20066526SHAWVL 3
50/50
2.254
20071526SHAWVL 1
50/50
1.522
200642SENECA#1
50/50
1.542
200643SENECA#2
50/50
1.44
941231AE2-117 GEN
Solar/Wind Harmer
5.221
962411AG1-090 GEN
Solar/Wind Harmer
16.83
970305AG2-200 GEN
Solar/Wind Harmer
1.546
203857AF2-221 C
Solar/Wind Harmer
1.169
944781AF1-143 GEN
Solar/Wind Harmer
5.861
966771AG1-548 GEN
Solar/Wind Harmer
8.276
966771AG1-548 GEN
Solar/Wind Harmer
1.604
209067AE2-060 GEN
Solar/Wind Helper
0.089
965131AG1-378 GEN
Solar/Wind Harmer
3.543
203975AE1-071-GEN
Solar/Wind Harmer
4.92
203993AD2-133_GEN1
Solar/Wind Harmer
2.661
20303426NA_O38_P22
Solar/Wind Harmer
2.48
960051AF2-296 GEN
Solar/Wind Harmer
2.881
957161AF2-010 GEN
Solar/Wind Harmer
4.381
203948AG1-140 C
Solar/Wind Harmer
0.149
203860AG1-193 C
Solar/Wind Harmer
0.554
20082926HNSMLK 2
Adder
3.123
20091326SHAW-D
50/50
1.303
957561AF2-050 GEN
Solar/Wind Harmer
7.094
203813AE2-344_GEN
Solar/Wind Harmer
6.115
970267AG2-176 GEN
Solar/Wind Harmer
7.859
961971AG1-040 GEN
Solar/Wind Harmer
0.316
203853AF1-134 C O1
Solar/Wind Harmer
0.871
203804AE2-113_GEN
Solar/Wind Harmer
5.741
203818AF1-086 GEN
Solar/Wind Harmer
2.869
203982AD2-062_GEN
Solar/Wind Harmer
7.055
203835AF1-098 GEN
Solar/Wind Harmer
1.52
203859AF2-294 C
Solar/Wind Harmer
0.94
203980AG1-197 GEN
Solar/Wind Harmer
0.783
238206AE2-263_GEN
Solar/Wind Harmer
18.579
203952AE2-129 C
Solar/Wind Harmer
1.071
20090526Q36
Solar/Wind Harmer
2.661
20091526CHSTN_FL
Solar/Wind Harmer
1.231
964201AG1-281 GEN
Solar/Wind Harmer
0.816
20326126BLOSSBCT
Adder
1.682
959471AF2-238 GEN
Solar/Wind Harmer
1.351
203830AF1-094 GEN
Solar/Wind Harmer
0.343
203979AG1-198 GEN
Solar/Wind Harmer
0.206
20082826HNSMLK 1
Adder
3.123
20083026HNSMLK 3
Adder
3.123
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.066
LGEELTFEXP_LGEE->PJM
CLTF
0.437
MECLTFEXP_MEC->PJM
CLTF
1.103
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.304
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.878
TVALTFEXP_TVA->PJM
CLTF
0.513
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.01
CPLELTFEXP_CPLE->PJM
CLTF
0.234
SIGELTFEXP_SIGE->PJM
CLTF
0.034
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.818
WECLTFEXP_WEC->PJM
CLTF
0.266
LAGNLTFEXP_LAGN->PJM
CLTF
1.057
CONTINGENCY 'PN_P2-3_PN-230-0252-A_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200739 CKT 2   /*26SHELOCTA   230.0 - 26SHELOCTA   115.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200810 CKT 1   /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0252-C_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200739 CKT 2   /*26SHELOCTA   230.0 - 26SHELOCTA   115.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200767 CKT 1   /*26SHELOCTA   230.0 - 26HOMER CT   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0252-B_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200767 CKT 1   /*26SHELOCTA   230.0 - 26HOMER CT   230.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200810 CKT 1   /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0201A-20_SRT-A'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 DISCONNECT BRANCH FROM BUS 200795 TO BUS 200810 CKT 1          /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-345-0183-301F-DRT-009_SRT-A'
 DISCONNECT BRANCH FROM BUS 200769 TO BUS 235129 CKT 1          /*26HOMER CY   345.0 - 01ARMSTRONG  345.0
 SET POSTCONTRATING 1434 BRANCH FROM BUS 200769 TO BUS 200942 CKT 1 /*26HOMER CY   345.0 - 26PIERCEBRK  345.0
END
CONTINGENCY 'PN_P2-3_PN-230-0183-209_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200769 TO BUS 202641 CKT S /*26HOMER CT   230.0 - 26HOMER CY   345.0 - 26HOMERCITYS  23.0
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200795 CKT 1          /*26HOMER CT   230.0 - 26SHELOCTA   230.0
END
CONTINGENCY 'AP_P7-1_MP-138-018_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235338 TO BUS 235391 CKT 1          /*01GRAFTN     138.0 - 01PRNTY      138.0
 DISCONNECT BRANCH FROM BUS 235356 TO BUS 235391 CKT 1          /*01KINGWD     138.0 - 01PRNTY      138.0
 SET POSTCONTRATING 459 BRANCH FROM BUS 235112 TO BUS 235391 CKT 3 /*01PRNTY      500.0 - 01PRNTY      138.0
 SET POSTCONTRATING 459 BRANCH FROM BUS 235112 TO BUS 235391 CKT 4 /*01PRNTY      500.0 - 01PRNTY      138.0
 SET PRECONTRATING 421 BRANCH FROM BUS 235112 TO BUS 235391 CKT 4 /*01PRNTY      500.0 - 01PRNTY      138.0
 SET PRECONTRATING 459 BRANCH FROM BUS 235112 TO BUS 235391 CKT 3 /*01PRNTY      500.0 - 01PRNTY      138.0
END
CONTINGENCY 'PN_P2-2_PN-500-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3   /*CONEM-GH     500.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PJM_500_BG_P4_5_CNSTN_M_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200026 CKT 1    /*CNASTONE     500.0 - HUNTERTN     500.0
 OPEN BRANCH FROM BUS 200004 TO BUS 200100 CKT ZC   /*CNASTONE     500.0 - CNASTCAP     500.0
END
CONTINGENCY 'AP_P2-2_WP-138-033T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 200763 CKT 1   /*01SOCIAL     138.0 - 26BLAIRSVL   138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235241 CKT 1   /*01SOCIAL     138.0 - 01SALTSB     138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235596 CKT 1   /*01SOCIAL     138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235973 CKT 2   /*01SOCIAL     138.0 - 01SOCIAL H    25.0
 DISCONNECT BUS 235253                                   /*01SOCIAL     138.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT19_SRT-SL'
 OPEN BRANCH FROM BUS 235108 TO BUS 964990 CKT 1                /*01HATFLD     500.0 - AG1-363 TP   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P7-1_MP-138-056_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 235122 TO BUS 235802 CKT 1   /*01LKLYNN     138.0 - 01CHEATL     138.0
 DISCONNECT BRANCH FROM BUS 235122 TO BUS 238189 CKT 1   /*01LKLYNN     138.0 - AE1-106 TAP  138.0
 DISCONNECT BRANCH FROM BUS 235802 TO BUS 237299 CKT 4   /*01CHEATL     138.0 - 01CHEAT LK    66.0
 REMOVE LOAD 2 FROM BUS 235802                           /*01CHEATL     138.0
END
CONTINGENCY 'PL_10_P42_100570_SRT-A'
 DISCONNECT BRANCH FROM BUS 200009 TO BUS 200011 CKT 1   /*JUNI         500.0 - KEYSTONE     500.0
 DISCONNECT BRANCH FROM BUS 200009 TO BUS 208004 CKT 2   /*JUNI         500.0 - JUNI         230.0
END
CONTINGENCY 'PN_P2-3_PN-500-004-DRT-008_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200009 CKT 1          /*KEYSTONE     500.0 - JUNI         500.0
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 200005 TO BUS 200011 CKT 1 /*CONEM-GH     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT31_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 OPEN BRANCH FROM BUS 200011 TO BUS 200009 CKT 1                /*KEYSTONE     500.0 - JUNI         500.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
END
CONTINGENCY 'PL_10_P42_100569_SRT-A'
 DISCONNECT BRANCH FROM BUS 200005 TO BUS 200009 CKT 1   /*CONEM-GH     500.0 - JUNI         500.0
 DISCONNECT BRANCH FROM BUS 200009 TO BUS 208004 CKT 2   /*JUNI         500.0 - JUNI         230.0
END
CONTINGENCY 'PN_P2-3_PN-115-0331-A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200520 TO BUS 203971 CKT 1   /*26ROXBURY    115.0 - AE1-071-POI  115.0
 OPEN BRANCH FROM BUS 200520 TO BUS 200532 CKT 2         /*26ROXBURY    115.0 - 26ROXBURY    138.0
END
CONTINGENCY 'PN_P2-3_PN-115-0331-B_SRT-A'
 DISCONNECT BRANCH FROM BUS 200520 TO BUS 203971 CKT 1   /*26ROXBURY    115.0 - AE1-071-POI  115.0
 OPEN BRANCH FROM BUS 200520 TO BUS 200860 CKT 3         /*26ROXBURY    115.0 - 26ROXB SB2    23.0
END
CONTINGENCY 'PN_P2-2_PN-115-030_SRT-A'
 DISCONNECT BUS 200522   /*26SHADE GP   115.0
END
CONTINGENCY 'PN_P2-2_PN-115-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 200512 TO BUS 200519 CKT 1   /*26LEWISTWN   115.0 - 26REED TAP   115.0
 DISCONNECT BRANCH FROM BUS 200513 TO BUS 200512 CKT 3   /*26LEWISTWN   230.0 - 26LEWISTWN   115.0
END
CONTINGENCY 'PL_08_P22_102799_SRT-A'
 DISCONNECT BUS 200080   /*HUST         500.0
END
CONTINGENCY 'PL_10_P22_100579_SRT-A'
 DISCONNECT BRANCH FROM BUS 200009 TO BUS 208004 CKT 1   /*JUNI         500.0 - JUNI         230.0
 REMOVE SWSHUNT FROM BUS 200009                          /*JUNI         500.0
END
CONTINGENCY 'PL_48_P71_102649_SRT-A'
 DISCONNECT BRANCH FROM BUS 207915 TO BUS 208113 CKT 1   /*GLBR         230.0 - SUSQ         230.0
 DISCONNECT BUS 208114                                   /*SUSQ G1      230.0
 DISCONNECT BUS 208124                                   /*SUSQ G1 TP   230.0
END
CONTINGENCY 'PECO_P7-1_220-9091_SRT-A
 DISCONNECT BUS 213616   /*FORDACT1      18.0
 DISCONNECT BUS 213617   /*FORDACT2      18.0
 DISCONNECT BUS 213618   /*FORDAST1      18.0
 DISCONNECT BUS 213619   /*FORDBCT1      18.0
 DISCONNECT BUS 213620   /*FORDBCT2      18.0
 DISCONNECT BUS 213621   /*FORDBST1      18.0
 DISCONNECT BUS 213622   /*FORDML90     230.0
 DISCONNECT BUS 213623   /*FORDML91     230.0
END
200762 to 235470 ckt 1
200513 to 208004 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
AP_P2-3_PE-500-014_SRT-SL
BreakerAC103.91 %179.0B186.01
5.33
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC102.78 %179.0B183.98
5.33
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC116.26 %160.0B186.02
5.33
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-3_MP-138-150_SRT-A
BreakerAC109.43 %160.0B175.08
4.04
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_10_P12_000085_SRT-A
SingleAC105.09 %618.0B649.44
3.62
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Base Case
SingleAC104.91 %493.0A517.19
3.43
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P1-2_PN-115-094_A_SRT-A
SingleAC103.04 %618.0B636.77
3.82

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_PE-500-014_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.91 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:186.01
MW Contribution:
5.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.901
203843AF2-002_GEN
Solar/Wind Harmer
0.884
20084626FORWARD
Solar/Wind Harmer
0.691
20089126CSLMN_L13
Solar/Wind Harmer
2.402
20088926STNY CRK
Solar/Wind Harmer
1.586
203844AF2-092 C
Solar/Wind Harmer
0.997
203955AF1-039 C O1
Solar/Wind Harmer
1.841
20084126DEEPCRK2
50/50
0.417
203841AF2-001_GEN
Solar/Wind Harmer
1.768
202652Y1-033 WT C
Solar/Wind Harmer
3.787
971879AH1-460 GEN
Solar/Wind Harmer
5.332
20092526R32
Solar/Wind Harmer
1.043
238127S14_GEN_2
Solar/Wind Helper
0.468
970631AG2-411 GEN
Solar/Wind Harmer
4.162
20083426SW_E13_K22
Solar/Wind Harmer
0.49
203839AF1-321 GEN
Solar/Wind Harmer
1.768
20088826HIGHLAND
Solar/Wind Harmer
0.974
20089226LOOKOUT
Solar/Wind Harmer
2.396
203940AF1-140 C
Solar/Wind Harmer
0.305
20083726HOMER C1
Adder
18.135
20083926HOMER C3
Adder
15.702
20083826HOMER C2
Adder
14.833
944781AF1-143 GEN
Solar/Wind Harmer
27.254
203857AF2-221 C
Solar/Wind Harmer
1.087
20081326YOUGH
50/50
0.179
964201AG1-281 GEN
Solar/Wind Harmer
0.312
20091526CHSTN_FL
Solar/Wind Harmer
0.383
238120AE2-309 GEN
Solar/Wind Helper
0.232
20084026DEEPCRK1
50/50
0.413
238126S14_GEN_1
Solar/Wind Helper
0.468
G-007ALTFEXP_G-007A->PJM
CMTX
0.749
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.187
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.118
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.581
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.383

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_WP-500-DRT19_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.78 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:183.98
MW Contribution:
5.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.902
203843AF2-002_GEN
Solar/Wind Harmer
0.884
20084626FORWARD
Solar/Wind Harmer
0.691
20089126CSLMN_L13
Solar/Wind Harmer
2.402
20088926STNY CRK
Solar/Wind Harmer
1.586
203844AF2-092 C
Solar/Wind Harmer
0.997
203955AF1-039 C O1
Solar/Wind Harmer
1.841
20084126DEEPCRK2
50/50
0.417
203841AF2-001_GEN
Solar/Wind Harmer
1.769
202652Y1-033 WT C
Solar/Wind Harmer
3.787
971879AH1-460 GEN
Solar/Wind Harmer
5.333
20092526R32
Solar/Wind Harmer
1.044
238127S14_GEN_2
Solar/Wind Helper
0.468
970631AG2-411 GEN
Solar/Wind Harmer
4.163
20083426SW_E13_K22
Solar/Wind Harmer
0.49
203839AF1-321 GEN
Solar/Wind Harmer
1.769
20088826HIGHLAND
Solar/Wind Harmer
0.974
20089226LOOKOUT
Solar/Wind Harmer
2.396
203940AF1-140 C
Solar/Wind Harmer
0.305
20083726HOMER C1
Adder
18.143
20083926HOMER C3
Adder
15.71
20083826HOMER C2
Adder
14.84
944781AF1-143 GEN
Solar/Wind Harmer
27.255
203857AF2-221 C
Solar/Wind Harmer
1.087
20081326YOUGH
50/50
0.179
964201AG1-281 GEN
Solar/Wind Harmer
0.313
20091526CHSTN_FL
Solar/Wind Harmer
0.383
238120AE2-309 GEN
Solar/Wind Helper
0.232
20084026DEEPCRK1
50/50
0.413
238126S14_GEN_1
Solar/Wind Helper
0.468
G-007ALTFEXP_G-007A->PJM
CMTX
0.752
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.048
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.186
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.122
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.126
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.578
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.381

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.26 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:186.02
MW Contribution:
5.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.901
203843AF2-002_GEN
Solar/Wind Harmer
0.884
20084626FORWARD
Solar/Wind Harmer
0.691
20089126CSLMN_L13
Solar/Wind Harmer
2.402
20088926STNY CRK
Solar/Wind Harmer
1.586
203844AF2-092 C
Solar/Wind Harmer
0.997
203955AF1-039 C O1
Solar/Wind Harmer
1.841
20084126DEEPCRK2
50/50
0.417
203841AF2-001_GEN
Solar/Wind Harmer
1.768
202652Y1-033 WT C
Solar/Wind Harmer
3.787
971879AH1-460 GEN
Solar/Wind Harmer
5.332
20092526R32
Solar/Wind Harmer
1.043
238127S14_GEN_2
Solar/Wind Helper
0.468
970631AG2-411 GEN
Solar/Wind Harmer
4.162
20083426SW_E13_K22
Solar/Wind Harmer
0.49
203839AF1-321 GEN
Solar/Wind Harmer
1.768
20088826HIGHLAND
Solar/Wind Harmer
0.974
20089226LOOKOUT
Solar/Wind Harmer
2.396
203940AF1-140 C
Solar/Wind Harmer
0.305
20083726HOMER C1
Adder
18.135
20083926HOMER C3
Adder
15.702
20083826HOMER C2
Adder
14.833
944781AF1-143 GEN
Solar/Wind Harmer
27.254
203857AF2-221 C
Solar/Wind Harmer
1.087
20081326YOUGH
50/50
0.179
964201AG1-281 GEN
Solar/Wind Harmer
0.312
20091526CHSTN_FL
Solar/Wind Harmer
0.383
238120AE2-309 GEN
Solar/Wind Helper
0.232
20084026DEEPCRK1
50/50
0.413
238126S14_GEN_1
Solar/Wind Helper
0.468
G-007ALTFEXP_G-007A->PJM
CMTX
0.749
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.187
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.118
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.581
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.383

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-3_MP-138-150_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-138-150_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.43 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:175.08
MW Contribution:
4.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20089026BF_G21_K23
Solar/Wind Harmer
1.436
203843AF2-002_GEN
Solar/Wind Harmer
0.67
20084626FORWARD
Solar/Wind Harmer
0.523
20089126CSLMN_L13
Solar/Wind Harmer
1.814
20088926STNY CRK
Solar/Wind Harmer
1.2
203844AF2-092 C
Solar/Wind Harmer
0.755
238118U2-030_1
Solar/Wind Helper
0.284
203955AF1-039 C O1
Solar/Wind Harmer
1.39
20084126DEEPCRK2
50/50
0.315
203841AF2-001_GEN
Solar/Wind Harmer
1.34
202652Y1-033 WT C
Solar/Wind Harmer
2.859
971879AH1-460 GEN
Solar/Wind Harmer
4.042
20092526R32
Solar/Wind Harmer
0.792
238127S14_GEN_2
Solar/Wind Helper
1.008
970631AG2-411 GEN
Solar/Wind Harmer
3.154
235531U2-073 GEN
Solar/Wind Helper
2.742
20083426SW_E13_K22
Solar/Wind Harmer
0.37
203839AF1-321 GEN
Solar/Wind Harmer
1.34
20088826HIGHLAND
Solar/Wind Harmer
0.739
238117U2-030
Solar/Wind Helper
0.284
20089226LOOKOUT
Solar/Wind Harmer
1.809
203940AF1-140 C
Solar/Wind Harmer
0.232
20083726HOMER C1
Adder
13.903
20083926HOMER C3
Adder
12.132
20083826HOMER C2
Adder
11.46
944781AF1-143 GEN
Solar/Wind Harmer
20.582
203857AF2-221 C
Solar/Wind Harmer
0.824
20081326YOUGH
50/50
0.135
238120AE2-309 GEN
Solar/Wind Helper
0.464
20084026DEEPCRK1
50/50
0.311
238126S14_GEN_1
Solar/Wind Helper
1.008
G-007ALTFEXP_G-007A->PJM
CMTX
0.345
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.078
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.793
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.145
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.046
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.246
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.146

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_10_P12_000085_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_10_P12_000085_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.09 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:649.44
MW Contribution:
3.62
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
29.593
20064926PENNTECH
50/50
0.399
203843AF2-002_GEN
Solar/Wind Harmer
0.531
970647AG2-420 GEN
Solar/Wind Harmer
0.146
20089026BF_G21_K23
Solar/Wind Harmer
0.029
20335026MILZ1-092
Adder
1.393
203947AF1-006 C
Solar/Wind Harmer
0.026
209071AE2-133 GEN
Solar/Wind Helper
0.041
200644SENECA#3
50/50
0.201
238217AF1-153 C O1
Solar/Wind Harmer
2.164
20094526CT_V3-030
Solar/Wind Harmer
0.126
203844AF2-092 C
Solar/Wind Harmer
0.787
20088926STNY CRK
Solar/Wind Harmer
0.108
20334926Z1-069 C
Solar/Wind Harmer
0.414
20089126CSLMN_L13
Solar/Wind Harmer
0.028
20083226HNSMLK 5
Adder
3.367
203926AA2-133 GEN
Adder
1.063
959421AF2-233 GEN
Solar/Wind Helper
0.225
965121AG1-377 GEN
Solar/Wind Harmer
1.237
23732901CHBRG_I12
Adder
1.108
959431AF2-234 GEN
Solar/Wind Helper
0.45
238202AE2-262_GEN
Solar/Wind Harmer
13.672
20120126WRREN CT
Adder
5.903
20092526R32
Solar/Wind Harmer
0.194
971879AH1-460 GEN
Solar/Wind Harmer
3.623
972323AH1-746 GEN
Solar/Wind Harmer
2.667
203841AF2-001_GEN
Solar/Wind Harmer
1.062
20079426CONEMAGH
Adder
0.907
970663AG2-429 GEN
Solar/Wind Harmer
0.748
20328326MANOR_T86
Adder
0.077
212507AE2-042_GEN
Solar/Wind Helper
0.784
20398826ARMNA MT
Solar/Wind Harmer
0.024
970647AG2-420 GEN
Solar/Wind Harmer
0.877
941421AE2-139 GEN
Solar/Wind Harmer
0
20083126HNSMLK 4
Adder
3.367
203962AF1-287 GEN
Solar/Wind Harmer
0.791
209137AF2-361 C
Solar/Wind Helper
1.69
203961AE2-224 GEN
Solar/Wind Harmer
0
970631AG2-411 GEN
Solar/Wind Harmer
3.718
970663AG2-429 GEN
Solar/Wind Harmer
2.854
946751AF1-339 GEN
Solar/Wind Helper
0.224
20081226ALY HYDR
50/50
0.379
216419AE2-001 C
Solar/Wind Harmer
3.94
972169AH1-667 GEN
Solar/Wind Harmer
2.342
203839AF1-321 GEN
Solar/Wind Harmer
1.062
946071AF1-272 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.189
238215AE2-248 C
Solar/Wind Harmer
3.24
203987AE2-118 C
Solar/Wind Harmer
3.376
20390526W1-045 C
Solar/Wind Harmer
0.08
20083926HOMER C3
Adder
46.738
20083826HOMER C2
Adder
44.149
20083726HOMER C1
Adder
44.015
20089226LOOKOUT
Solar/Wind Harmer
0.073
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
20066626SHAWVL 4
50/50
2.256
20066526SHAWVL 3
50/50
2.239
20071526SHAWVL 1
50/50
1.518
200642SENECA#1
50/50
1.571
200643SENECA#2
50/50
1.467
941231AE2-117 GEN
Solar/Wind Harmer
3.623
962411AG1-090 GEN
Solar/Wind Harmer
6.186
970305AG2-200 GEN
Solar/Wind Harmer
1.107
203857AF2-221 C
Solar/Wind Harmer
0.597
944781AF1-143 GEN
Solar/Wind Harmer
4.325
238206AE2-263_GEN
Solar/Wind Harmer
12.852
20090526Q36
Solar/Wind Harmer
0.626
20091526CHSTN_FL
Solar/Wind Harmer
0.177
20326126BLOSSBCT
Adder
1.649
959471AF2-238 GEN
Solar/Wind Harmer
0.914
20082826HNSMLK 1
Adder
3.367
20083026HNSMLK 3
Adder
3.367
970899AG2-561 GEN
Solar/Wind Harmer
1.192
20335126GROZ1-110
Adder
1.822
238219AF1-167 C
Solar/Wind Harmer
0.643
946731AF1-337 GEN
Solar/Wind Helper
0.224
970555AG2-356 GEN
Solar/Wind Harmer
0.914
966771AG1-548 GEN
Solar/Wind Harmer
1.406
966771AG1-548 GEN
Solar/Wind Harmer
1.758
209067AE2-060 GEN
Solar/Wind Helper
0.101
209054AE2-059 GEN
Solar/Wind Helper
0.04
20091326SHAW-D
50/50
1.301
957561AF2-050 GEN
Solar/Wind Harmer
5.014
970267AG2-176 GEN
Solar/Wind Harmer
5.91
203813AE2-344_GEN
Solar/Wind Harmer
4.588
946691AF1-333 GEN
Solar/Wind Helper
0.224
946741AF1-338 GEN
Solar/Wind Helper
0.224
965131AG1-378 GEN
Solar/Wind Harmer
1.237
203975AE1-071-GEN
Solar/Wind Harmer
0.007
203993AD2-133_GEN1
Solar/Wind Harmer
0.62
960051AF2-296 GEN
Solar/Wind Harmer
2.028
957161AF2-010 GEN
Solar/Wind Harmer
3.249
203948AG1-140 C
Solar/Wind Harmer
0.119
203860AG1-193 C
Solar/Wind Harmer
0.415
20082926HNSMLK 2
Adder
3.367
203804AE2-113_GEN
Solar/Wind Harmer
0
203818AF1-086 GEN
Solar/Wind Harmer
0.687
203982AD2-062_GEN
Solar/Wind Harmer
5.215
203980AG1-197 GEN
Solar/Wind Harmer
0.588
203859AF2-294 C
Solar/Wind Harmer
0.63
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.623
LGEELTFEXP_LGEE->PJM
CLTF
0.808
MECLTFEXP_MEC->PJM
CLTF
1.978
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.775
NYPJM->LTFIMP_NY
CLTF
0.22
TVALTFEXP_TVA->PJM
CLTF
1.008
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.011
CPLELTFEXP_CPLE->PJM
CLTF
0.572
SIGELTFEXP_SIGE->PJM
CLTF
0.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.9
WECLTFEXP_WEC->PJM
CLTF
0.467
LAGNLTFEXP_LAGN->PJM
CLTF
2.043

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.91 %
Rating:493.0 MVA
Rating Type:A
MVA to Mitigate:517.19
MW Contribution:
3.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
29.604
20064926PENNTECH
50/50
0.396
203843AF2-002_GEN
Solar/Wind Harmer
0.502
20335026MILZ1-092
Adder
1.402
970647AG2-420 GEN
Solar/Wind Harmer
0.137
20089026BF_G21_K23
Solar/Wind Harmer
0.027
203947AF1-006 C
Solar/Wind Harmer
0.025
200644SENECA#3
50/50
0.197
238217AF1-153 C O1
Solar/Wind Harmer
2.146
20094526CT_V3-030
Solar/Wind Harmer
0.122
203844AF2-092 C
Solar/Wind Harmer
0.756
20334926Z1-069 C
Solar/Wind Harmer
0.407
20088926STNY CRK
Solar/Wind Harmer
0.102
20089126CSLMN_L13
Solar/Wind Harmer
0.027
20083226HNSMLK 5
Adder
3.125
203926AA2-133 GEN
Adder
1.137
965121AG1-377 GEN
Solar/Wind Harmer
1.23
23732901CHBRG_I12
Adder
1.154
972323AH1-746 GEN
Solar/Wind Harmer
2.597
203841AF2-001_GEN
Solar/Wind Harmer
1.004
20079426CONEMAGH
Adder
0.855
970663AG2-429 GEN
Solar/Wind Harmer
0.7
20328326MANOR_T86
Adder
0.081
238202AE2-262_GEN
Solar/Wind Harmer
13.722
20120126WRREN CT
Adder
5.738
20092526R32
Solar/Wind Harmer
0.186
971879AH1-460 GEN
Solar/Wind Harmer
3.434
941421AE2-139 GEN
Solar/Wind Harmer
0
20398826ARMNA MT
Solar/Wind Harmer
0.024
970647AG2-420 GEN
Solar/Wind Harmer
0.82
20083126HNSMLK 4
Adder
3.125
203962AF1-287 GEN
Solar/Wind Harmer
0.739
209137AF2-361 C
Solar/Wind Helper
1.532
203961AE2-224 GEN
Solar/Wind Harmer
0
970631AG2-411 GEN
Solar/Wind Harmer
3.524
970663AG2-429 GEN
Solar/Wind Harmer
2.669
20081226ALY HYDR
50/50
0.38
216419AE2-001 C
Solar/Wind Harmer
3.964
972169AH1-667 GEN
Solar/Wind Harmer
2.335
203839AF1-321 GEN
Solar/Wind Harmer
1.004
946071AF1-272 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.179
238215AE2-248 C
Solar/Wind Harmer
3.26
203987AE2-118 C
Solar/Wind Harmer
3.374
20390526W1-045 C
Solar/Wind Harmer
0.082
20083926HOMER C3
Adder
43.658
20083826HOMER C2
Adder
41.24
20083726HOMER C1
Adder
40.627
20089226LOOKOUT
Solar/Wind Harmer
0.068
20066626SHAWVL 4
50/50
2.256
20066526SHAWVL 3
50/50
2.24
20071526SHAWVL 1
50/50
1.516
200642SENECA#1
50/50
1.537
200643SENECA#2
50/50
1.436
941231AE2-117 GEN
Solar/Wind Harmer
3.627
962411AG1-090 GEN
Solar/Wind Harmer
6.151
970305AG2-200 GEN
Solar/Wind Harmer
1.076
203857AF2-221 C
Solar/Wind Harmer
0.567
944781AF1-143 GEN
Solar/Wind Harmer
4.066
238206AE2-263_GEN
Solar/Wind Harmer
12.898
20090526Q36
Solar/Wind Harmer
0.62
20091526CHSTN_FL
Solar/Wind Harmer
0.174
20326126BLOSSBCT
Adder
1.657
959471AF2-238 GEN
Solar/Wind Harmer
0.926
20082826HNSMLK 1
Adder
3.125
20083026HNSMLK 3
Adder
3.125
970899AG2-561 GEN
Solar/Wind Harmer
1.136
20335126GROZ1-110
Adder
1.863
238219AF1-167 C
Solar/Wind Harmer
0.602
970555AG2-356 GEN
Solar/Wind Harmer
0.926
966771AG1-548 GEN
Solar/Wind Harmer
1.321
966771AG1-548 GEN
Solar/Wind Harmer
1.651
209067AE2-060 GEN
Solar/Wind Helper
0.091
20091326SHAW-D
50/50
1.297
957561AF2-050 GEN
Solar/Wind Harmer
4.921
203813AE2-344_GEN
Solar/Wind Harmer
4.286
970267AG2-176 GEN
Solar/Wind Harmer
5.502
965131AG1-378 GEN
Solar/Wind Harmer
1.23
203975AE1-071-GEN
Solar/Wind Harmer
0.007
203993AD2-133_GEN1
Solar/Wind Harmer
0.614
960051AF2-296 GEN
Solar/Wind Harmer
2
957161AF2-010 GEN
Solar/Wind Harmer
3.051
203948AG1-140 C
Solar/Wind Harmer
0.112
203860AG1-193 C
Solar/Wind Harmer
0.387
20082926HNSMLK 2
Adder
3.125
203804AE2-113_GEN
Solar/Wind Harmer
0
203818AF1-086 GEN
Solar/Wind Harmer
0.669
203982AD2-062_GEN
Solar/Wind Harmer
5.376
203859AF2-294 C
Solar/Wind Harmer
0.642
203980AG1-197 GEN
Solar/Wind Harmer
0.548
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.271
LGEELTFEXP_LGEE->PJM
CLTF
0.606
MECLTFEXP_MEC->PJM
CLTF
1.488
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.997
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.452
TVALTFEXP_TVA->PJM
CLTF
0.749
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.904
CPLELTFEXP_CPLE->PJM
CLTF
0.404
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.938
WECLTFEXP_WEC->PJM
CLTF
0.353
LAGNLTFEXP_LAGN->PJM
CLTF
1.521

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P1-2_PN-115-094_A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-115-094_A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.04 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:636.77
MW Contribution:
3.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
32.734
20064926PENNTECH
50/50
0.438
203843AF2-002_GEN
Solar/Wind Harmer
0.559
20335026MILZ1-092
Adder
1.592
970647AG2-420 GEN
Solar/Wind Harmer
0.152
20089026BF_G21_K23
Solar/Wind Harmer
0.03
203947AF1-006 C
Solar/Wind Harmer
0.027
200644SENECA#3
50/50
0.218
238217AF1-153 C O1
Solar/Wind Harmer
2.376
20094526CT_V3-030
Solar/Wind Harmer
0.135
203844AF2-092 C
Solar/Wind Harmer
0.84
20334926Z1-069 C
Solar/Wind Harmer
0.456
20088926STNY CRK
Solar/Wind Harmer
0.114
20089126CSLMN_L13
Solar/Wind Harmer
0.029
20083226HNSMLK 5
Adder
3.473
203926AA2-133 GEN
Adder
1.322
965121AG1-377 GEN
Solar/Wind Harmer
1.362
20334726NME_Y1-047
Adder
1.116
972323AH1-746 GEN
Solar/Wind Harmer
2.883
203841AF2-001_GEN
Solar/Wind Harmer
1.118
20079426CONEMAGH
Adder
0.955
970663AG2-429 GEN
Solar/Wind Harmer
0.778
20328326MANOR_T86
Adder
0.093
238202AE2-262_GEN
Solar/Wind Harmer
15.162
20120126WRREN CT
Adder
6.361
20092526R32
Solar/Wind Harmer
0.208
971879AH1-460 GEN
Solar/Wind Harmer
3.824
941421AE2-139 GEN
Solar/Wind Harmer
0
20398826ARMNA MT
Solar/Wind Harmer
0.028
970647AG2-420 GEN
Solar/Wind Harmer
0.91
20083126HNSMLK 4
Adder
3.473
203962AF1-287 GEN
Solar/Wind Harmer
0.818
209137AF2-361 C
Solar/Wind Helper
1.401
203961AE2-224 GEN
Solar/Wind Harmer
0
970631AG2-411 GEN
Solar/Wind Harmer
3.923
970663AG2-429 GEN
Solar/Wind Harmer
2.968
20081226ALY HYDR
50/50
0.42
216419AE2-001 C
Solar/Wind Harmer
4.375
972169AH1-667 GEN
Solar/Wind Harmer
2.584
203839AF1-321 GEN
Solar/Wind Harmer
1.118
946071AF1-272 GEN
Solar/Wind Harmer
0
203963AG1-253 GEN
Solar/Wind Harmer
0.198
238215AE2-248 C
Solar/Wind Harmer
3.598
203987AE2-118 C
Solar/Wind Harmer
3.735
20083926HOMER C3
Adder
48.861
20083826HOMER C2
Adder
46.155
20083726HOMER C1
Adder
45.578
20089226LOOKOUT
Solar/Wind Harmer
0.075
20066626SHAWVL 4
50/50
2.495
20066526SHAWVL 3
50/50
2.477
20071526SHAWVL 1
50/50
1.677
200642SENECA#1
50/50
1.705
200643SENECA#2
50/50
1.592
941231AE2-117 GEN
Solar/Wind Harmer
4.016
962411AG1-090 GEN
Solar/Wind Harmer
6.808
970305AG2-200 GEN
Solar/Wind Harmer
1.193
203857AF2-221 C
Solar/Wind Harmer
0.631
944781AF1-143 GEN
Solar/Wind Harmer
4.472
238206AE2-263_GEN
Solar/Wind Harmer
14.253
20090526Q36
Solar/Wind Harmer
0.687
20091526CHSTN_FL
Solar/Wind Harmer
0.193
20326126BLOSSBCT
Adder
1.871
959471AF2-238 GEN
Solar/Wind Harmer
1.05
20082826HNSMLK 1
Adder
3.473
20083026HNSMLK 3
Adder
3.473
970899AG2-561 GEN
Solar/Wind Harmer
1.264
20335126GROZ1-110
Adder
2.107
238219AF1-167 C
Solar/Wind Harmer
0.669
970555AG2-356 GEN
Solar/Wind Harmer
1.05
966771AG1-548 GEN
Solar/Wind Harmer
1.463
966771AG1-548 GEN
Solar/Wind Harmer
1.829
200917MEHOOPANY_G
Solar/Wind Harmer
0.166
209067AE2-060 GEN
Solar/Wind Helper
0.084
20091326SHAW-D
50/50
1.435
957561AF2-050 GEN
Solar/Wind Harmer
5.458
203813AE2-344_GEN
Solar/Wind Harmer
4.744
970267AG2-176 GEN
Solar/Wind Harmer
6.097
203975AE1-071-GEN
Solar/Wind Harmer
0.02
965131AG1-378 GEN
Solar/Wind Harmer
1.362
203993AD2-133_GEN1
Solar/Wind Harmer
0.68
960051AF2-296 GEN
Solar/Wind Harmer
2.216
957161AF2-010 GEN
Solar/Wind Harmer
3.38
203948AG1-140 C
Solar/Wind Harmer
0.125
203860AG1-193 C
Solar/Wind Harmer
0.429
20082926HNSMLK 2
Adder
3.473
203804AE2-113_GEN
Solar/Wind Harmer
0
203818AF1-086 GEN
Solar/Wind Harmer
0.743
203859AF2-294 C
Solar/Wind Harmer
0.734
203980AG1-197 GEN
Solar/Wind Harmer
0.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.841
LGEELTFEXP_LGEE->PJM
CLTF
0.573
MECLTFEXP_MEC->PJM
CLTF
1.408
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.071
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.041
TVALTFEXP_TVA->PJM
CLTF
0.669
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.623
CPLELTFEXP_CPLE->PJM
CLTF
0.229
SIGELTFEXP_SIGE->PJM
CLTF
0.044
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.083
WECLTFEXP_WEC->PJM
CLTF
0.338
LAGNLTFEXP_LAGN->PJM
CLTF
1.364
CONTINGENCY 'AP_P2-3_PE-500-014_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235103 TO BUS 964990 CKT 1          /*01BLACKO     500.0 - AG1-363 TP   500.0
 REDUCE BUS 235103 SHUNT BY 50 PERCENT                          /*01BLACKO     500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 235101 TO BUS 235103 CKT 1 /*01BEDNGT     500.0 - 01BLACKO     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235101 TO BUS 235103 CKT 1 /*01BEDNGT     500.0 - 01BLACKO     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT19_SRT-SL'
 OPEN BRANCH FROM BUS 235108 TO BUS 964990 CKT 1                /*01HATFLD     500.0 - AG1-363 TP   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P2-3_MP-138-150_SRT-A'
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235305 CKT 1   /*01ALBRIG     138.0 - 01 106 J     138.0
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235320 CKT 1   /*01ALBRIG     138.0 - 01DENVER     138.0
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235402 CKT 1   /*01ALBRIG     138.0 - 01SNOW T     138.0
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235469 CKT 1   /*01ALBRIG     138.0 - 01GARRET     138.0
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 238184 CKT 1   /*01ALBRIG     138.0 - AF2-356 TAP  138.0
 DISCONNECT BRANCH FROM BUS 235297 TO BUS 235305 CKT 1   /*01HAZELT     138.0 - 01 106 J     138.0
 DISCONNECT BRANCH FROM BUS 238189 TO BUS 235305 CKT 1   /*AE1-106 TAP  138.0 - 01 106 J     138.0
END
CONTINGENCY 'PL_10_P12_000085_SRT-A'
 DISCONNECT BRANCH FROM BUS 200009 TO BUS 200011 CKT 1   /*JUNI         500.0 - KEYSTONE     500.0
END
CONTINGENCY 'PN_P1-2_PN-115-094_A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200520 TO BUS 203971 CKT 1   /*26ROXBURY    115.0 - AE1-071-POI  115.0
END
235470 to 235469 ckt 1
200762 to 235470 ckt 1
200513 to 208004 ckt 1

Winter Peak Analysis

The New Service Request AH1-460 was evaluated as a 66.0 MW (39.6 MW Capacity) injection in the PENELEC area.

AH1-460 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 66.0 MW (66.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-460 was evaluated as a 66.0 MW injection

AH1-460 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 66.0 MW (66.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 2, Cluster 82 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 82 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 82 projects will meet the dynamics requirements of the NERC, FE, and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2028 summer peak load case, modified to include applicable projects. Cluster 82 projects have been dispatched online at maximum power output, with approximately unity power factor at the high side of the GSUs, 1.00 pu voltage at the generator terminals, and 1.02 pu voltage at the POI buses.

Cluster 82 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 134 contingencies were studied, each with a 20 second simulation time period (with 1.0 second initial run prior to any events). Studied faults included:

  1. Steady state operation (Category P0);
  2. Three phase faults with normal clearing time on the intact network (Category P1);
  3. Single phase to ground faults with delayed clearing due to a stuck breaker (Category P4);
  4. Single phase to ground faults with delayed clearing as a result of protection failure (Category P5);
  5. Single phase to ground faults with normal clearing for common structure (Category P7).

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 82 projects.

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2028 peak load case:

  1. Cluster 82 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 82 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

AF2-001, AF2-002, and AF1-321 were tripped during the fault application closed to their POIs as a result of fictitious frequency spikes at the frequency relay monitored bus, i.e., inverter terminal bus. Therefore, frequency protection in the model was disabled for faults close to the POI of the projects due to the deficiency of PSSE frequency calculation for inverter-based generation facilities. No more tripping issue of the AF2-001, AF2-002, and AF1-321 were observed.

No mitigations were found to be required for TC2 Cluster 82.

Table 1: TC2 Cluster 82 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO (MW)

MWE

(MW)

MWC

(MW)

Point of Interconnection

82

AG2-411

Solar

FirstEnergy (FE) transmission system, Pennsylvania Electric Co (PENELEC) zone

63

63

40.7

Statler Hill 115 kV

AH1-460

Solar

FirstEnergy (FE) transmission system, Pennsylvania Electric Co (PENELEC) zone

66

66

39.6

Hooversville - Scalp Level 115 kV

AG2-176

Solar

FirstEnergy (FE) transmission system, Pennsylvania Electric Co (PENELEC) zone

150

150

90

Geneva 115 kV

 

Reactive Power Analysis

AH1-460 meets the 0.95 leading and lagging PF requirement at the high side of the main transformer.

 

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA2-133Wyalusing 34.5kVIn Service
AD2-062Roxbury-Greene 138 kVWithdrawn
AD2-133Eagle Valley 115kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE2-001Nittany-Zion 46 kVSuspended
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-118ABW Tap-Williamsburg 46 kVEngineering & Procurement
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-248Fillmore-Thompson Farm 46 kVSuspended
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-316Brookville-Squab Hollow 138 kVUnder Construction
AE2-344Edinboro South-Venango Junction 115 kVWithdrawn
AF1-006Fairview East 34.5 kVIn Service
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-086Madera-Westover South 115 kVPartially in Service - Under Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVUnder Construction
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-167West Freedom-C&K Coal 25 kVSuspended
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-287Edinboro South 34.5 kV IIWithdrawn
AF1-302Brookville-Squab Hollow 138 kVUnder Construction
AF1-321Hooversville 115 kV ISuspended
AF2-001Hooversville 115 kV IISuspended
AF2-002Hooversville 115 kV IIISuspended
AF2-010Union City-Titusville 115 kVWithdrawn
AF2-039Shawville-Clearfield 34.5 kVUnder Construction
AF2-050Bear Rock-Johnstown 230 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIUnder Construction
AF2-092Snake Spring-Bedford Area 23 kVWithdrawn
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-165Clark Summit-Emlenton 34.5 kVIn Service
AF2-221Scalp Level 22.9 kVSuspended
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-294Thompson 34.5 kVSuspended
AF2-296Madera 34.5 kVEngineering & Procurement
AF2-361Mifflintown Tap 69 kVUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-090Philipsburg 115 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-140Union City 34.5 kVSuspended
AG1-193Utica Junction 34.5 kVWithdrawn
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVIn Service
AG1-253Erie East-Union City 34.5 kVSuspended
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-377Philipsburg 115 kVEngineering & Procurement
AG1-378Philipsburg 115 kVEngineering & Procurement
AG1-548Erie South-Union City 115 kVEngineering & Procurement
AG2-176Geneva 115 kVActive
AG2-200North Warren - Russell 34.5 kVActive
AG2-356South Troy - Canton 34.5 kVActive
AG2-411Statler Hill 115 kVActive
AG2-420Eclipse #2 34.5 kVActive
AG2-429Burma - Armstrong 138 kVActive
AG2-561Glory - Glen Campbell 34.5 kVActive
AH1-667Philipsburg-Shawville 34.5 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AH1-460 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
PENELECn6817.1Rebuild 24.59 miles of the Lewistown-Juniata 230kV transmission line and upgrade terminal endsCost Allocated$53,787,987N/A
PPLn6818Rebuild PPL's ~0.9 miles LEWI-JUNI 230kV Line with a summer normal rating of at least 3000 Amps.Cost Allocated$833,199N/A
APSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Contingent$0N/A
AEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationContingent$0N/A
APSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Contingent$0N/A
APSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Contingent$0N/A
APSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Contingent$0N/A
APSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardContingent$0N/A
APSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Contingent$0N/A
APSb4002.1Garrett-Garrett Tap 115 kV Line Upgrade: Rebuild approximately 1.9 miles of 115 kV line with larger conductorContingent$0N/A
APSb4002.2Adjust the relay settings at Penn Mar, Garrett, and Deep Creek 115kV substationsContingent$0N/A
Grand Total:$54,621,186

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n6817.1
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n6817.1
Title
Rebuild 24.59 miles of the Lewistown-Juniata 230kV transmission line and upgrade terminal ends
Description
Rebuild 24.59 miles of the Lewistown-Juniata 230kV transmission line and upgrade terminal ends. Expected FE facility ratings: 835/961/1051 MVA SN/SE/SLD. FE upgade n6817.1 required in addition to n6818 (Rebuild of PPL section of line). PPL ratings after n6818 are only 815/928 MVA SN/SE. Expected line ratings after n6818 & n6817.1 will be 815/928 MVA SN/SE.
Total Cost ($USD)
$122,656,404
Discounted Total Cost ($USD)
$122,656,404
Allocated Cost ($USD)
$53,787,987
Time Estimate
81 Months

Contributor

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A815.0 MVA
(All)B928.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-1768.2 MW56.1%$68,868,417
AH1-4606.4 MW43.9%$53,787,987

System Reinforcement: n6818
Type
Load Flow
TO
PPL
RTEP ID / TO ID
n6818
Title
Rebuild PPL's ~0.9 miles LEWI-JUNI 230kV Line with a summer normal rating of at least 3000 Amps.
Description
The FE portion of the line is rated at 546/666 MVA SN/SE. The PPL portion is limiting, which requires n6818. Reinforcement scope no longer includes any substation scope as Juniata 230kV substation is being rebuilt under S0945.1. Actual PPL facility ratings after upgrade: 815/928 MVA SN/SE
Total Cost ($USD)
$1,900,000
Discounted Total Cost ($USD)
$1,900,000
Allocated Cost ($USD)
$833,199
Time Estimate
24 to 36 Months

Contributor

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A546.0 MVA
(All)B666.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-1768.2 MW56.1%$1,066,801
AH1-4606.4 MW43.9%$833,199

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4002.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4002.1
Title
Garrett-Garrett Tap 115 kV Line Upgrade: Rebuild approximately 1.9 miles of 115 kV line with larger conductor
Description
Rebuild approximately 1.9 miles of 115 kV line with larger conductor. Install OPGW for the static & install one new SCADA controlled 2000 A disconnect with whips. Also requires b4002.2 to achieve new line ratings.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
26GARRETT-01GARRET 115.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A133.0 MVA
(All)B160.0 MVA
WINA150.0 MVA
WINB190.0 MVA

System Reinforcement: b4002.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4002.2
Title
Adjust the relay settings at Penn Mar, Garrett, and Deep Creek 115kV substations
Description
Adjust the relay settings at Penn Mar, Garrett, and Deep Creek substations to accommodate the new ratings and impedance changes associates with the Garrett- Garrett Tap 115 kV Line rebuild.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-460 may not presently have cost responsibility for this upgrade, AH1-460 may need this upgrade in-service to be deliverable to the PJM system. If AH1-460 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
26GARRETT-01GARRET 115.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A417.0 MVA
(All)B480.0 MVA
WINA417.0 MVA
WINB506.0 MVA

System Reinforcement: s0945.1
Type
Load Flow
TO
PPL
RTEP ID / TO ID
s0945.1
Title
Rebuild the Juniata 230/69 kV Substation
Description
None
Cost Information
Time Estimate
Dec 18 2025

Not Contingent

Note: AH1-460 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AH1-460 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A493.0 MVA
(All)B624.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-460


AH1-460 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowAPSb4000.11Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAEPb4000.1Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.2Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.3Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.4Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.5Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substationTopology-0.0%Contingent$0
Load FlowAPSb4000.6Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)Topology-0.0%Contingent$0
Load FlowAPSb4000.7Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Load FlowAPSb4000.8Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)Topology-0.0%Contingent$0
Load FlowAPSb4000.10Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yardTopology-0.0%Contingent$0
Load FlowAPSb4000.9Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-460 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-460 One Line Diagram

AH1-460 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.