AH1-542 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:08

Crissinger-Delaware Business Park 138kV

22.0 MW Capacity / 110.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Riverlake Energy, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Transmission Systems, Incorporated.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $14,553,811 $16,449,706 = 0.88 AND ( $14,553,811 - $16,449,706 ) 110.0 = $-17,235 per MW

General

The Project Developer has proposed a Solar/Storage generating facility located in the American Transmission Systems, Incorporated zone — Marion County, Ohio. The installed facilities will have a total capability of 110.0 MW with 22.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-542
Project Name:
Crissinger-Delaware Business Park 138kV
Project Developer Name:
Riverlake Energy, LLC
State:
Ohio
County:
Marion
Transmission Owner:
American Transmission Systems, Incorporated
MFO:
110.0
MWE:
110.0
MWC:
22.0
Battery Storage Specification:
330.0 MWh, 4.0-hr class
Grid Charging:
No
Fuel Type:
Solar/Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-542 will interconnect on the American Transmission Systems, Incorporated  transmission system  by tapping the Kirby - Crissinger 138 kV line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-542 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-542Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$1,496,938$0$0
Other Scope$508,527$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$11,843,200$11,843,200$11,843,200
Network Upgrades$2,710,611$2,710,611$2,710,611
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$16,559,276$14,553,811$14,553,811

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-542

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-542
Project ID: AH1-542
20% of cost allocation for Phase II Network Upgrades:(A) $2,910,762
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $1,644,971
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $1,265,791
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Cut the existing 138kV line and Loop in the new Interconnection substation.

$1,383,059$230,027$57,639$9,640$1,680,365$1,680,365
(Pending)

Install new relays and revise relay settings at Crissinger.

$396,240$42,288$16,513$854$455,895$455,895
(Pending)

Install new relays and revise relay settings at Kirby.

$414,468$42,288$17,273$854$474,883$474,883
(Pending)

Review and update relay settings at Tangy substation.

$47,744$0$1,990$0$49,734$49,734
(Pending)

Review and update relay settings at Roberts substation.

$47,744$0$1,990$0$49,734$49,734
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install 138 kV revenue metering within new Interconnection substation.

$307,063$184,931$12,797$3,736$508,527$508,527
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Construct a new 138 kV 3-breaker ring bus interconnection substation.

$6,025,394$3,111,996$251,108$66,538$9,455,036$9,455,036
(Pending)

Install/test approximately 5.01 miles of new ADSS cable from the AH1-542 substation control house to a new splice point on existing fiber cable.

$1,409,884$338,680$58,757$6,841$1,814,162$1,814,162
(Pending)

Design, installation, and testing/commissioning for MPLS equipment for SCADA transport at AH1-542 Substation.

$372,246$126,949$15,513$2,564$517,272$517,272
(Pending)

Estimated (2) in-sub fiber builds for relaying protection from AH1-542 substation control house to the Crissinger – Kirby 138kV Line with existing OPGW.

$51,928$2,586$2,164$52$56,730$56,730
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install line terminal equipment within the AH1-542 Interconnection substation. Install up to 0.1 miles of conductor from AH1-542 Interconnection Substation to the Project Developer-owned dead-end structure outside of interconnection substation fence.

$1,040,610$354,273$43,367$8,954$1,447,204$1,447,204
(Pending)

Integrate Interconnection Facilities protection and controls to the Transmission Owner system.

$47,744$0$1,990$0$49,734$49,734
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Cut the existing 138kV line and Loop in the new Interconnection substation.

$1,383,059$230,027$57,639$9,640$1,680,365$1,680,365
(Pending)

Install new relays and revise relay settings at Crissinger.

$396,240$42,288$16,513$854$455,895$455,895
(Pending)

Install new relays and revise relay settings at Kirby.

$414,468$42,288$17,273$854$474,883$474,883
(Pending)

Review and update relay settings at Tangy substation.

$47,744$0$1,990$0$49,734$49,734
(Pending)

Review and update relay settings at Roberts substation.

$47,744$0$1,990$0$49,734$49,734
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Transmission Owner oversight of developer design and construction of new interconnection substation.

$1,007,838$0$42,002$0$1,049,840$1,049,840
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install 138 kV revenue metering within new Interconnection substation.

$307,063$184,931$12,797$3,736$508,527$508,527
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Install/test approximately 5.01 miles of new ADSS cable from the AH1-542 substation control house to a new splice point on existing fiber cable.

$1,409,884$338,680$58,757$6,841$1,814,162$1,814,162
(Pending)

Install (1) security system and camera system. Install (1) indoor security AC cabinet. Install (1) network fiber termination rack.

$1,664,568$262,676$69,371$5,306$2,001,921$2,001,921
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Integrate Interconnection Facilities protection and controls to the Transmission Owner system.

$47,744$0$1,990$0$49,734$49,734
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$16,559,276$16,559,276
Developer Build Option$8,134,795$8,134,795

Based on the scope of work for the Interconnection Facilities, it is expected to take 42 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

FE performed an analysis of its underlying transmission system <100 kV system. New Service Request Project AH1-542 did not contribute to any overloads on the FE transmission <100 kV system.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-542 was evaluated as a 110.0 MW (22.0 MW Capacity) injection in the ATSI area.

AH1-542 was evaluated as part of a plant. The plant consists of AH1-542. The total Energy output of the plant was evaluated at its maximum seasonal capability of 110.0 MW (110.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC111.73 %4142.0B4627.93
14.19
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#706_05GAVIN 765_C1_SRT-A
BreakerAC107.42 %4142.0B4449.39
19.67
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC106.82 %4142.0B4424.53
14.4
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC106.7 %4142.0B4419.47
14.36
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC106.67 %4142.0B4418.17
14.35
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC104.85 %4142.0B4342.78
3.34
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC104.04 %4142.0B4309.27
4.58
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-030_SRT-A
TowerAC100.26 %4142.0B4152.93
16.17
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
ATSI_P7-1_TE-345-031_SRT-A
TowerAC100.15 %4142.0B4148.28
16.18

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.73 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4627.93
MW Contribution:
14.19
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.68 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5205.7
MW Contribution:
13.74
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
13.634
25326509SID D
50/50
1.875
253378AE2-206_GEN
Solar/Wind Harmer
4.933
957841AF2-078 GEN
Solar/Wind Harmer
7.818
942221AE2-234 GEN
Solar/Wind Harmer
4.491
24387305FR-4G C
Solar/Wind Harmer
6.468
274770LINCOLN ;1U
Adder
7.887
274771LINCOLN ;2U
Adder
7.887
274805UNIV PK N;1U
Adder
6.337
274888KELLY CRK;1U
Solar/Wind Harmer
7.437
274696ROCKY RD ;4P
Adder
14.179
274697ROCKY RD ;3P
Adder
3.763
274762LEE CO EC;3U
Adder
11.36
962101AG1-054 GEN
Solar/Wind Helper
0.804
270166AC1-044 GEN3
50/50
13.634
270485AE1-090_GEN
Solar/Wind Harmer
0.867
253398AE2-221_GEN2
Solar/Wind Harmer
5.86
940581AE2-045 GEN
Solar/Wind Harmer
13.168
971605AH1-302 GEN
Solar/Wind Harmer
11.259
964861AG1-349 GEN
Solar/Wind Harmer
10.135
958861AF2-177 GEN
Solar/Wind Harmer
14.078
965011AG1-365 GEN
Solar/Wind Harmer
12.88
270594AE1-207 GEN
Solar/Wind Harmer
17.476
270032AE2-172
Solar/Wind Harmer
5.985
945371AF1-202 GEN
Solar/Wind Harmer
8.941
24386605FR-22G C
Solar/Wind Harmer
5.476
274773LINCOLN ;4U
Adder
7.887
274774LINCOLN ;5U
Adder
7.887
970825AG2-519 GEN
Solar/Wind Harmer
2.659
270005AE1-210 C O1
Solar/Wind Harmer
6.921
274723RIVER EC ;12
Adder
22.667
274751CRETE EC ;1U
Adder
6.184
274761LEE CO EC;2U
Adder
11.36
25196808ZIMRHP
Adder
91.918
25196008MFTGT1
Adder
1.676
254303AC2-168 GEN
Solar/Wind Helper
0.2
961971AG1-040 GEN
Solar/Wind Helper
0.526
238126S14_GEN_1
Solar/Wind Helper
0.672
241955AC1-078 GEN
Solar/Wind Harmer
12.28
241973AD2-163_GEN1
Solar/Wind Harmer
3.183
241974AD2-163_GEN2
Solar/Wind Harmer
3.183
943861AF1-054 GEN
Solar/Wind Harmer
6.081
943851AF1-053 GEN
Solar/Wind Harmer
2.938
253343AC1-166 GEN
Solar/Wind Harmer
1.644
270227U2-072_GEN3
Solar/Wind Harmer
2.95
270228U2-072_GEN4
Solar/Wind Harmer
2.95
270231U2-072_GEN5
Solar/Wind Harmer
2.95
962771AG1-126 GEN
Solar/Wind Harmer
60.25
970149AG2-104 GEN
Solar/Wind Harmer
37.205
270286AF1-227 GEN2
Solar/Wind Harmer
3.521
270578AF1-285 GEN2
Solar/Wind Harmer
1.806
971917AH1-482 GEN
Solar/Wind Harmer
11.693
24791305MDL-5G
Solar/Wind Harmer
3.102
970373AG2-245 GEN
Solar/Wind Harmer
27.014
274822ROCKFORD ;11
Adder
24.117
970091AG2-072 GEN
Adder
52.601
270051AF1-062 GEN
50/50
17.906
960801AF2-371 GEN
Solar/Wind Harmer
3.703
964871AG1-351 GEN
Solar/Wind Harmer
2.557
270043AE2-236 GEN
Solar/Wind Harmer
7.15
965461AG1-414 GEN
Solar/Wind Harmer
2.931
253394AE2-221_GEN
Solar/Wind Harmer
5.86
965021AG1-366 GEN
Solar/Wind Harmer
2.995
274772LINCOLN ;3U
Adder
7.887
962031AG1-047 GEN
Solar/Wind Harmer
3.839
957741AF2-068 GEN
Solar/Wind Harmer
19.045
970825AG2-519 GEN
Solar/Wind Harmer
7.139
274724RIVER EC ;11
Adder
22.402
972259AH1-714 GEN
Adder
24.031
274729ELWOOD EC;1P
Adder
20.631
25196008MFTGT1
Adder
1.623
237048AF1-022 C
Solar/Wind Helper
0.208
237046AF1-021 C
Solar/Wind Helper
0.376
270120AB2-067 GEN2
50/50
13.634
270160DARBY CT5
50/50
0.817
270466AD2-091
50/50
8.337
270054AF2-122 C O1
Solar/Wind Harmer
5.579
938701AE1-092 GEN
Solar/Wind Harmer
29.745
270462AD2-086
Solar/Wind Harmer
9.973
253415AE1-040 GEN
Solar/Wind Harmer
1.495
253349AC2-067 GEN
Solar/Wind Harmer
2.665
970349AG2-230 GEN
Solar/Wind Harmer
19.467
960971AF2-388 GEN
Solar/Wind Harmer
14.115
24697605MDL-3G C
Solar/Wind Harmer
4.743
270181AB1-006 GEN2
Solar/Wind Harmer
0.92
270599AE1-208 GEN
Solar/Wind Harmer
10.386
966841AG1-555 GEN
Solar/Wind Harmer
3.198
24725505WLD G2 C
Solar/Wind Harmer
5.055
270247TR4_N_V136
Solar/Wind Harmer
1.078
970883AG2-550 GEN
Solar/Wind Harmer
12.676
274808UNIV PK N;4U
Adder
6.295
274674JOLIET 9 ;6U
Adder
19.323
274693ROCKY RD ;1P
Adder
13.715
274683WAUKEGAN ;8U
Adder
26.185
274683WAUKEGAN ;8U
Adder
22.073
25194408D.CRK1
Adder
9.285
972235AH1-702 GEN1
Adder
3.095
274764LEE CO EC;5U
Adder
11.387
254305AE2-115 C
Solar/Wind Helper
0.277
241967AE2-285_GEN
Solar/Wind Helper
0.8
946071AF1-272 GEN
Solar/Wind Helper
2.92
20083426SW_E13_K22
Solar/Wind Helper
0.059
20088826HIGHLAND
Solar/Wind Helper
0.947
23585401KL_K28_T16
Solar/Wind Helper
1.286
238117U2-030
Solar/Wind Helper
0.287
961921AG1-034 GEN
Solar/Wind Harmer
22.831
270287AF1-227 GEN3
Solar/Wind Harmer
3.521
942051AE2-217 GEN
Solar/Wind Harmer
28.777
942871AE2-306 GEN
Solar/Wind Harmer
1.355
270391AF1-285 GEN3
Solar/Wind Harmer
0.695
944531AF1-118 GEN
Solar/Wind Harmer
45.692
971347AH1-153 GEN
Solar/Wind Harmer
6.489
970781AG2-491 GEN
Solar/Wind Harmer
12.867
270063AE2-323 C
Solar/Wind Harmer
2.782
972231SS25-0005
Solar/Wind Harmer
12.006
274752CRETE EC ;2U
Adder
6.184
274826FISK ;BP
Adder
13.792
274730ELWOOD EC;6P
Adder
20.631
25196608WSDLE5
Adder
10.548
20092526R32
Solar/Wind Helper
1.228
202652Y1-033 WT C
Solar/Wind Helper
0.585
20398826ARMNA MT
Solar/Wind Helper
1.535
238127S14_GEN_2
Solar/Wind Helper
0.672
941421AE2-139 GEN
Solar/Wind Helper
2.297
274887GEN-1.85
Solar/Wind Harmer
0.443
270158DARBY CT3
50/50
0.818
270036AE2-216 BAT
50/50
9.171
270224U2-072_GEN2
Solar/Wind Harmer
2.95
959141AF2-205 GEN
Solar/Wind Harmer
7.803
253406AD2-031_GEN
Solar/Wind Harmer
1.637
945581AF1-223 GEN
Solar/Wind Harmer
5.812
24386405FR-21G C
Solar/Wind Harmer
5.476
274775LINCOLN ;6U
Adder
7.887
274777LINCOLN ;8U
Adder
7.887
961761AG1-017 GEN
Solar/Wind Harmer
0.543
247536S-71 GEN
Solar/Wind Harmer
5.133
965051AG1-369 GEN
Solar/Wind Harmer
6.329
970031AG2-029 GEN
Solar/Wind Harmer
31.677
971029AG2-637 GEN
Solar/Wind Harmer
18.999
972037AH1-567 GEN1
Adder
0.231
972228AH1-698 GEN2
Adder
4.668
274675JOLIET 29;7U
Adder
38.521
274675JOLIET 29;7U
Adder
37.145
274823ROCKFORD ;21
Adder
23.942
972267AH1-718 GEN
Adder
5.066
270161DARBY CT6
50/50
0.806
25326109MON D
50/50
1.882
946101AF1-275 GEN
Solar/Wind Harmer
2.638
942861AE2-305 GEN
Solar/Wind Harmer
12.319
270269AC2-059
Solar/Wind Harmer
12.923
253400AC2-068 GEN
Solar/Wind Harmer
1.072
945421AF1-207 GEN
Solar/Wind Harmer
18.162
944541AF1-119 GEN
Solar/Wind Harmer
5.407
270180AB1-006 GEN1
Solar/Wind Harmer
9.254
24697905MDL-4G C
Solar/Wind Harmer
2.953
965791AG1-447 GEN
Solar/Wind Harmer
8.187
270031AE2-169
Solar/Wind Harmer
10.386
24699105WLD G1 C
Solar/Wind Harmer
4.996
270201AC2-176 GEN
Solar/Wind Harmer
6.526
964611AG1-324 GEN
Solar/Wind Harmer
0.664
970885AG2-551 GEN
Solar/Wind Harmer
2.948
270383AD1-128 GEN
Solar/Wind Harmer
7.709
247620Y3-023
Adder
0.579
274695ROCKY RD ;2P
Adder
13.852
25194508D.CRK3
Adder
1.736
972236AH1-702 GEN2
Adder
2.691
274765LEE CO EC;6U
Adder
11.387
274763LEE CO EC;4U
Adder
11.253
254304AE2-114 C
Solar/Wind Helper
0.277
946381AF1-302 GEN
Solar/Wind Helper
0.24
203961AE2-224 GEN
Solar/Wind Helper
2.516
940863AE2-074 GEN
Solar/Wind Helper
0.487
203954AE2-126 C
Solar/Wind Helper
0.496
235054AD2-180 GEN
Solar/Wind Helper
1.697
203946AE2-131 C
Solar/Wind Helper
0.495
235531U2-073 GEN
Solar/Wind Helper
2.713
270159DARBY CT4
50/50
0.82
961821AG1-024 GEN
Solar/Wind Harmer
15.221
945631AF1-228 GEN
Solar/Wind Harmer
7.537
253338AC1-165 GEN
Solar/Wind Harmer
1.644
270223U2-072_GEN1
Solar/Wind Harmer
2.95
270578AF1-285 GEN2
Solar/Wind Harmer
0.695
270432AC2-029 GEN
Solar/Wind Harmer
10.129
241972AD1-140 GEN
Solar/Wind Harmer
6.404
270340AC2-060 GEN
Solar/Wind Harmer
3.955
270263AC1-001 GEN
Solar/Wind Harmer
1.363
959331AF2-224 GEN
Solar/Wind Harmer
12.88
946581AF1-322 GEN
Solar/Wind Harmer
13.166
960681AF2-359 GEN
Solar/Wind Harmer
4.837
274776LINCOLN ;7U
Adder
7.887
270526AF1-158 GEN
Solar/Wind Harmer
5.757
964611AG1-324 GEN
Solar/Wind Harmer
4.95
270191TR4_S_V150
Solar/Wind Harmer
3.801
965041AG1-368 GEN
Solar/Wind Harmer
12.63
963841AG1-237 GEN
Solar/Wind Harmer
13.795
274687WILL CNTY;4U
Adder
35.099
274687WILL CNTY;4U
Adder
35.099
274731ELWOOD EC;2P
Adder
20.631
274733ELWOOD EC;3P
Adder
20.631
274746AC1-111 G10
Adder
6.986
241982AE2-343 S C
Solar/Wind Helper
0.28
23750501ELLIOTTS
Solar/Wind Helper
0.704
20089126CSLMN_L13
Solar/Wind Helper
0.622
20088926STNY CRK
Solar/Wind Helper
0.862
20094526CT_V3-030
Solar/Wind Helper
0.502
20088626ARWF_N39
Solar/Wind Helper
1.259
20334926Z1-069 C
Solar/Wind Helper
1.425
238118U2-030_1
Solar/Wind Helper
0.287
970155AG2-107 GEN
Solar/Wind Harmer
26.272
253370AE2-315 SEC1
Adder
2.649
253371AE2-315 SEC2
Adder
2.506
965651AG1-433 GEN
Solar/Wind Harmer
7.057
971995AH1-542 GEN
Solar/Wind Harmer
14.188
270055AF2-134 C O1
Solar/Wind Harmer
3.893
270024AE2-089 GEN
Solar/Wind Harmer
5.963
972207SS24-0001
Solar/Wind Harmer
28.043
253316AC1-085 GEN3
Solar/Wind Harmer
10.624
946171AF1-282 GEN
Solar/Wind Harmer
12.689
274812UNIV PK N;8U
Adder
6.323
24639705ELKHART HY
Adder
0.193
274676JOLIET 29;8U
Adder
38.521
274745AC1-111 GEN9
Adder
6.986
274682WAUKEGAN ;7U
Adder
22.344
274828WAUKEGAN ;BP
Adder
13.726
24728605AND G2
Adder
4.712
25194608D.CRK4
Adder
2.018
241966AE1-183 GEN
Solar/Wind Helper
0.316
203830AF1-094 GEN
Solar/Wind Helper
0.526
203979AG1-198 GEN
Solar/Wind Helper
0.315
964201AG1-281 GEN
Solar/Wind Helper
0.505
238185AF2-356 C
Solar/Wind Helper
2.211
20091526CHSTN_FL
Solar/Wind Helper
0.61
20090526Q36
Solar/Wind Helper
1.071
203952AE2-129 C
Solar/Wind Helper
0.495
238120AE2-309 GEN
Solar/Wind Helper
0.423
23751101LEADS_P59
Solar/Wind Helper
1.861
270302AB2-170 GEN
Solar/Wind Harmer
12.005
253372AE2-315 SEC3
Adder
2.506
253372AE2-315 SEC3
Adder
2.506
25306009OHH W.
Adder
3.787
970289AG2-191 GEN
Solar/Wind Harmer
2.456
958391AF2-133 GEN
Solar/Wind Harmer
11.7
963791AG1-232 GEN
Solar/Wind Harmer
17.234
253433AC1-085 GEN1
Solar/Wind Harmer
6.743
253432AC1-085 GEN2
Solar/Wind Harmer
0.339
247521TR3_G114
Solar/Wind Harmer
4.26
972227AH1-698 GEN1
Adder
3.287
274827FISK ;RP
Adder
9.775
274800UNIV PARK;3U
Adder
7.343
274801UNIV PARK;4U
Adder
7.343
274735ELWOOD EC;4P
Adder
20.631
274744AC1-111 GEN8
Adder
6.986
241997AF1-093 GEN
Solar/Wind Helper
0.316
200917MEHOOPANY_G
Solar/Wind Helper
2.134
970153AG2-106 GEN
Solar/Wind Harmer
26.272
270284AF1-227 GEN1
Solar/Wind Harmer
9.52
276820AF1-078_GEN
Solar/Wind Harmer
2.191
960071AF2-298 GEN
Solar/Wind Harmer
2.003
253303V4-073 C
Solar/Wind Harmer
0.153
253370AE2-315 SEC1
Adder
2.649
253371AE2-315 SEC2
Adder
2.506
247642Z2-115 C
Solar/Wind Harmer
0.083
970289AG2-191 GEN
Solar/Wind Harmer
0.992
253317AC1-085 GEN4
Solar/Wind Harmer
10.624
946181AF1-283 GEN
Solar/Wind Harmer
16.496
946031AF1-268 GEN
Solar/Wind Harmer
10.518
972181SS23-001
Solar/Wind Harmer
7.504
247643Z2-116 C
Solar/Wind Harmer
0.088
276164X3-005 C
Solar/Wind Harmer
0.887
274811UNIV PK N;7U
Adder
6.323
274676JOLIET 29;8U
Adder
37.145
274734ELWOOD EC;8P
Adder
20.631
274736ELWOOD EC;9P
Adder
20.631
274682WAUKEGAN ;7U
Adder
22.344
24728505AND G1
Adder
4.712
25194608D.CRK4
Adder
2.018
274767LEE CO EC;8U
Adder
11.226
235058AG1-386 C
Solar/Wind Helper
0.581
964991AG1-363 GEN
Solar/Wind Helper
3.784
20303426NA_O38_P22
Solar/Wind Helper
1.032
203993AD2-133_GEN1
Solar/Wind Helper
1.071
23652301WDPWR_K20
Solar/Wind Helper
0.162
203846AF2-130 C
Solar/Wind Helper
0.505
203955AF1-039 C O1
Solar/Wind Helper
0.386
23750701CROSSCHOOL
Solar/Wind Helper
1.2
270349AD2-093_GEN
Solar/Wind Harmer
6.551
270471AD2-092_GEN
Solar/Wind Harmer
6.551
253383AE2-342_GEN
Solar/Wind Harmer
1.432
25322209TAIT E
Adder
12.972
25322209TAIT E
Adder
12.68
253370AE2-315 SEC1
Adder
2.649
970291AG2-192 GEN
Solar/Wind Harmer
1.681
970291AG2-192 GEN
Solar/Wind Harmer
0.541
270535AF1-215 GEN1
Solar/Wind Harmer
5.84
270536AF1-215 GEN2
Solar/Wind Harmer
5.84
24755605MDL-5G
Solar/Wind Harmer
3.102
965681AG1-436 GEN
Solar/Wind Harmer
16.003
247621Y3-024
Adder
0.306
270246TR4_N_V150
Solar/Wind Harmer
1.078
241801AE1-079 GEN
Solar/Wind Helper
0.313
203835AF1-098 GEN
Solar/Wind Helper
2.083
203818AF1-086 GEN
Solar/Wind Helper
1.799
203853AF1-134 C O1
Solar/Wind Helper
0.505
203804AE2-113_GEN
Solar/Wind Helper
1.868
270156DARBY CT1
50/50
0.834
270157DARBY CT2
50/50
0.831
270459AD2-067 GEN
Solar/Wind Harmer
14.991
270071AF1-092 GEN
Solar/Wind Harmer
19.771
24729505KEY G4
Adder
8.445
958711AF2-162 GEN
Solar/Wind Harmer
1.306
24691005MDL-2G C
Solar/Wind Harmer
4.758
24387005FR-3G C
Solar/Wind Harmer
5.037
270543AE2-219 C
Solar/Wind Harmer
12.676
971771AH1-392 GEN
Solar/Wind Harmer
11.401
274728ELWOOD EC;5P
Adder
20.631
25196408WSDLE3
Adder
10.858
25196108MFTGT2
Adder
1.847
25196108MFTGT2
Adder
1.715
241985AE1-237 GEN
Solar/Wind Helper
0.312
20089226LOOKOUT
Solar/Wind Helper
0.62
203940AF1-140 C
Solar/Wind Helper
0.417
237043AE2-125 C
Solar/Wind Helper
0.204
23751201ROTHROCK
Solar/Wind Helper
0.744
270475AD2-096_GEN
50/50
10.496
270518AE2-148 GEN
Solar/Wind Harmer
18.58
253325AC1-069 GEN
Solar/Wind Harmer
1.586
964401AG1-302 GEN
Solar/Wind Harmer
11.693
24690905MDL-1G C
Solar/Wind Harmer
10.33
24386205FR-12G C
Solar/Wind Harmer
5.457
24441505OLIV SLR
Solar/Wind Harmer
0.17
270004AE1-209 GEN
Solar/Wind Harmer
6.921
274753CRETE EC ;3U
Adder
6.184
274814UNIV PK N;0U
Adder
6.378
274807UNIV PK N;3U
Adder
6.364
274803UNIV PARK;6U
Adder
7.347
972038AH1-567 GEN2
Adder
0.46
274760LEE CO EC;1U
Adder
11.36
962511AG1-100 GEN
Solar/Wind Helper
0.525
23562501BACKB
Solar/Wind Helper
0.906
203854AF2-039 C
Solar/Wind Helper
0.332
276843GEN-1.7
Solar/Wind Harmer
0.048
962761AG1-125 GEN
Solar/Wind Harmer
60.25
270520AE2-214 GEN
Solar/Wind Harmer
10.552
253333AC1-068 GEN
Solar/Wind Harmer
1.586
270391AF1-285 GEN3
Solar/Wind Harmer
1.806
270317AD1-130_GEN
Solar/Wind Harmer
4.589
270273AD2-016 GEN
Solar/Wind Harmer
3.685
25326309TAIT D
Adder
1.458
958381AF2-132 GEN
Solar/Wind Harmer
11.693
276903AD2-071 C
Solar/Wind Harmer
12.774
24385905FR-11G C
Solar/Wind Harmer
10.583
274754CRETE EC ;4U
Adder
6.184
270216AD2-079_GEN
Solar/Wind Harmer
0.764
274802UNIV PARK;5U
Adder
7.347
274732ELWOOD EC;7P
Adder
20.631
274674JOLIET 9 ;6U
Adder
19.323
274766LEE CO EC;7U
Adder
11.226
203947AF1-006 C
Solar/Wind Helper
0.571
20084626FORWARD
Solar/Wind Helper
0.376
20089026BF_G21_K23
Solar/Wind Helper
0.492
203855AF2-088 C
Solar/Wind Helper
0.16
CPLELTFEXP_CPLE->PJM
CLTF
2.158
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.077
CBM West 1LTFEXP_CBM-W1->PJM
CBM
156.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.206
MECLTFEXP_MEC->PJM
CLTF
19.244
SIGELTFEXP_SIGE->PJM
CLTF
0.591
NYPJM->LTFIMP_NY
CLTF
5.256
LGEELTFEXP_LGEE->PJM
CLTF
7.735
WECLTFEXP_WEC->PJM
CLTF
4.687
AG2-052LTFEXP_AG2-052->PJM
LTF
0.294
AH1-155LTFEXP_AH1-155->PJM
LTF
0.441
LAGNLTFEXP_LAGN->PJM
CLTF
17.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.667
TVALTFEXP_TVA->PJM
CLTF
8.311

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#706_05GAVIN 765_C1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#706_05GAVIN 765_C1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.42 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4449.39
MW Contribution:
19.67
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
15.492
241973AD2-163_GEN1
Solar/Wind Harmer
4.025
241974AD2-163_GEN2
Solar/Wind Harmer
4.025
270227U2-072_GEN3
Solar/Wind Harmer
3.956
270228U2-072_GEN4
Solar/Wind Harmer
3.956
270231U2-072_GEN5
Solar/Wind Harmer
3.956
943861AF1-054 GEN
Solar/Wind Harmer
7.538
943851AF1-053 GEN
Solar/Wind Harmer
3.643
270302AB2-170 GEN
Solar/Wind Harmer
16.105
253343AC1-166 GEN
Solar/Wind Harmer
1.946
957201AF2-014 GEN
Solar/Wind Harmer
7.338
247521TR3_G114
Solar/Wind Harmer
5.362
970179AG2-119 GEN
Solar/Wind Harmer
12.462
963791AG1-232 GEN
Solar/Wind Harmer
20.803
944161AF1-084 GEN
Solar/Wind Harmer
3.358
958391AF2-133 GEN
Solar/Wind Harmer
13.726
970289AG2-191 GEN
Solar/Wind Harmer
2.804
274827FISK ;RP
Adder
11.436
274800UNIV PARK;3U
Adder
8.587
274801UNIV PARK;4U
Adder
8.587
972227AH1-698 GEN1
Adder
3.84
274735ELWOOD EC;4P
Adder
24.024
274744AC1-111 GEN8
Adder
8.105
253372AE2-315 SEC3
Adder
2.747
253372AE2-315 SEC3
Adder
2.747
25306009OHH W.
Adder
4.15
24721905FLATG4
50/50
3.319
24722005FLATG5
50/50
3.319
962771AG1-126 GEN
Solar/Wind Harmer
87.132
970153AG2-106 GEN
Solar/Wind Harmer
37.994
270284AF1-227 GEN1
Solar/Wind Harmer
12.766
276820AF1-078_GEN
Solar/Wind Harmer
2.693
24695305TIMB G C
Solar/Wind Harmer
5.277
247643Z2-116 C
Solar/Wind Harmer
0.107
270588AE1-091_GEN
Solar/Wind Harmer
16.602
972181SS23-001
Solar/Wind Harmer
8.839
247642Z2-115 C
Solar/Wind Harmer
0.095
276164X3-005 C
Solar/Wind Harmer
1.042
274811UNIV PK N;7U
Adder
7.423
970289AG2-191 GEN
Solar/Wind Harmer
1.133
276806AD2-047 C O1
Solar/Wind Harmer
15.763
274676JOLIET 29;8U
Adder
43.287
274734ELWOOD EC;8P
Adder
24.024
274736ELWOOD EC;9P
Adder
24.024
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
274682WAUKEGAN ;7U
Adder
25.826
274767LEE CO EC;8U
Adder
12.777
24728505AND G1
Adder
5.071
25194608D.CRK4
Adder
2.025
23906502RICHG2&3
Adder
1.439
270349AD2-093_GEN
Solar/Wind Harmer
8.784
270471AD2-092_GEN
Solar/Wind Harmer
8.784
253383AE2-342_GEN
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
1.357
965681AG1-436 GEN
Solar/Wind Harmer
19.243
270535AF1-215 GEN1
Solar/Wind Harmer
6.903
270120AB2-067 GEN2
50/50
17.244
270054AF2-122 C O1
Solar/Wind Harmer
7.347
270462AD2-086
Solar/Wind Harmer
13.378
938701AE1-092 GEN
Solar/Wind Harmer
39.554
270247TR4_N_V136
Solar/Wind Harmer
1.357
970349AG2-230 GEN
Solar/Wind Harmer
23.598
942801AE2-298 GEN
Solar/Wind Harmer
2.373
961051AF2-396 GEN
Solar/Wind Harmer
24.247
961051AF2-396 GEN
Solar/Wind Harmer
11.278
960971AF2-388 GEN
Solar/Wind Harmer
16.409
944231AF1-091 GEN
Solar/Wind Harmer
26.952
24697605MDL-3G C
Solar/Wind Harmer
5.47
270181AB1-006 GEN2
Solar/Wind Harmer
1.061
274808UNIV PK N;4U
Adder
7.391
274674JOLIET 9 ;6U
Adder
22.504
274693ROCKY RD ;1P
Adder
15.856
274683WAUKEGAN ;8U
Adder
30.253
274683WAUKEGAN ;8U
Adder
25.502
972235AH1-702 GEN1
Adder
3.539
274764LEE CO EC;5U
Adder
12.96
25194408D.CRK1
Adder
9.313
23585401KL_K28_T16
Solar/Wind Helper
1.178
238117U2-030
Solar/Wind Helper
0.267
946101AF1-275 GEN
Solar/Wind Harmer
3.388
942861AE2-305 GEN
Solar/Wind Harmer
15.272
241960AC2-195 GEN
Solar/Wind Harmer
4.323
247620Y3-023
Adder
0.71
965791AG1-447 GEN
Solar/Wind Harmer
9.845
25326109MON D
Adder
1.994
944541AF1-119 GEN
Solar/Wind Harmer
6.286
945421AF1-207 GEN
Solar/Wind Harmer
21.073
270269AC2-059
Solar/Wind Harmer
13.884
270180AB1-006 GEN1
Solar/Wind Harmer
10.673
24697905MDL-4G C
Solar/Wind Harmer
3.405
958011AF2-095 GEN
Solar/Wind Harmer
21.218
274695ROCKY RD ;2P
Adder
16.014
972236AH1-702 GEN2
Adder
3.077
274765LEE CO EC;6U
Adder
12.96
274763LEE CO EC;4U
Adder
12.808
25194508D.CRK3
Adder
1.741
972159AH1-661 GEN
Adder
1.225
235054AD2-180 GEN
Solar/Wind Helper
1.576
235531U2-073 GEN
Solar/Wind Helper
2.548
24721605FLATG1
50/50
3.319
961821AG1-024 GEN
Solar/Wind Harmer
20.11
270223U2-072_GEN1
Solar/Wind Harmer
3.956
270578AF1-285 GEN2
Solar/Wind Harmer
0.932
945631AF1-228 GEN
Solar/Wind Harmer
9.329
253338AC1-165 GEN
Solar/Wind Harmer
1.946
241972AD1-140 GEN
Solar/Wind Harmer
7.47
270432AC2-029 GEN
Solar/Wind Harmer
11.406
959331AF2-224 GEN
Solar/Wind Harmer
16.062
270191TR4_S_V150
Solar/Wind Harmer
4.784
965041AG1-368 GEN
Solar/Wind Harmer
15.857
960681AF2-359 GEN
Solar/Wind Harmer
5.817
270526AF1-158 GEN
Solar/Wind Harmer
6.973
274776LINCOLN ;7U
Adder
9.27
946581AF1-322 GEN
Solar/Wind Harmer
15.185
966831AG1-554 GEN
Solar/Wind Harmer
1.764
274687WILL CNTY;4U
Adder
40.93
274687WILL CNTY;4U
Adder
40.93
274731ELWOOD EC;2P
Adder
24.024
274733ELWOOD EC;3P
Adder
24.024
274746AC1-111 G10
Adder
8.105
23750501ELLIOTTS
Solar/Wind Helper
0.6
238118U2-030_1
Solar/Wind Helper
0.267
270119AB2-067 GEN1
50/50
17.244
253378AE2-206_GEN
Solar/Wind Harmer
6.061
25326509SID D
Adder
2.143
246937BC-WTG2
Solar/Wind Harmer
6.329
247607V1-011 GEN
Solar/Wind Harmer
6.22
270475AD2-096_GEN
50/50
14.072
270518AE2-148 GEN
Solar/Wind Harmer
22.44
253325AC1-069 GEN
Solar/Wind Harmer
1.877
270491AE1-102 GEN2
Solar/Wind Harmer
2.103
971199AH1-059 GEN
Solar/Wind Harmer
3.233
24441505OLIV SLR
Solar/Wind Harmer
0.205
964401AG1-302 GEN
Solar/Wind Harmer
13.753
274753CRETE EC ;3U
Adder
7.284
24690905MDL-1G C
Solar/Wind Harmer
11.914
274814UNIV PK N;0U
Adder
7.488
274807UNIV PK N;3U
Adder
7.472
274803UNIV PARK;6U
Adder
8.599
276843GEN-1.7
Solar/Wind Harmer
0.845
972038AH1-567 GEN2
Adder
0.538
274760LEE CO EC;1U
Adder
12.93
23562501BACKB
Solar/Wind Helper
0.847
942221AE2-234 GEN
Solar/Wind Harmer
5.285
957841AF2-078 GEN
Solar/Wind Harmer
9.072
274770LINCOLN ;1U
Adder
9.27
274771LINCOLN ;2U
Adder
9.27
274805UNIV PK N;1U
Adder
7.439
274888KELLY CRK;1U
Solar/Wind Harmer
8.695
970941AG2-585 GEN
Solar/Wind Harmer
8.104
274696ROCKY RD ;4P
Adder
16.391
274697ROCKY RD ;3P
Adder
4.35
274762LEE CO EC;3U
Adder
12.93
23751201ROTHROCK
Solar/Wind Helper
0.691
237043AE2-125 C
Solar/Wind Helper
0.16
270459AD2-067 GEN
Solar/Wind Harmer
19.807
270435AC2-044 GEN
Solar/Wind Harmer
3.236
270071AF1-092 GEN
Solar/Wind Harmer
23.849
270007AE1-245 C
Solar/Wind Harmer
8.496
971771AH1-392 GEN
Solar/Wind Harmer
13.875
24729505KEY G4
Adder
9.953
958711AF2-162 GEN
Solar/Wind Harmer
1.519
24691005MDL-2G C
Solar/Wind Harmer
5.488
274728ELWOOD EC;5P
Adder
24.024
25196408WSDLE3
Adder
10.931
25196108MFTGT2
Adder
1.832
25196108MFTGT2
Adder
1.701
270051AF1-062 GEN
50/50
23.559
960801AF2-371 GEN
Solar/Wind Harmer
4.344
964871AG1-351 GEN
Solar/Wind Harmer
2.999
246938BC-WTG3
Solar/Wind Harmer
6.438
965021AG1-366 GEN
Solar/Wind Harmer
3.735
270043AE2-236 GEN
Solar/Wind Harmer
8.753
270505AE1-170 C O1
Solar/Wind Harmer
22.99
945111AF1-176 GEN
Solar/Wind Harmer
8.665
270044AE2-322 C
Solar/Wind Harmer
1.989
274772LINCOLN ;3U
Adder
9.27
274724RIVER EC ;11
Adder
26.355
965461AG1-414 GEN
Solar/Wind Harmer
3.346
972259AH1-714 GEN
Adder
28.051
274729ELWOOD EC;1P
Adder
24.024
25196008MFTGT1
Adder
1.61
237048AF1-022 C
Solar/Wind Helper
0.174
237046AF1-021 C
Solar/Wind Helper
0.304
270166AC1-044 GEN3
50/50
17.244
270485AE1-090_GEN
Solar/Wind Harmer
1.163
246936BC-WTG1
Solar/Wind Harmer
6.329
270489AE1-102 GEN1
Solar/Wind Harmer
2.103
965011AG1-365 GEN
Solar/Wind Harmer
16.062
957891AF2-083 GEN
Solar/Wind Harmer
22.99
945111AF1-176 GEN
Solar/Wind Harmer
27.342
964861AG1-349 GEN
Solar/Wind Harmer
11.914
24441205WTRV SLR C
Solar/Wind Harmer
0.203
940581AE2-045 GEN
Solar/Wind Harmer
15.382
971605AH1-302 GEN
Solar/Wind Harmer
13.152
274773LINCOLN ;4U
Adder
9.27
274774LINCOLN ;5U
Adder
9.27
958861AF2-177 GEN
Solar/Wind Harmer
16.291
274751CRETE EC ;1U
Adder
7.284
274723RIVER EC ;12
Adder
26.668
274761LEE CO EC;2U
Adder
12.93
25196008MFTGT1
Adder
1.662
25196808ZIMRHP
Adder
90.149
238126S14_GEN_1
Solar/Wind Helper
0.635
270536AF1-215 GEN2
Solar/Wind Harmer
6.903
24755605MDL-5G
Solar/Wind Harmer
3.578
25322209TAIT E
Adder
14.396
25322209TAIT E
Adder
14.072
970291AG2-192 GEN
Solar/Wind Harmer
1.918
970291AG2-192 GEN
Solar/Wind Harmer
0.618
276776AD2-060 GEN
Solar/Wind Harmer
0.617
253370AE2-315 SEC1
Adder
2.904
247621Y3-024
Adder
0.348
23906402RICHG1
Adder
1.437
964991AG1-363 GEN
Solar/Wind Helper
3.522
235058AG1-386 C
Solar/Wind Helper
0.4
24721705FLATG2
50/50
3.319
24721805FLATG3
50/50
3.319
970155AG2-107 GEN
Solar/Wind Harmer
37.994
971995AH1-542 GEN
Solar/Wind Harmer
19.672
965421AG1-410 GEN
Solar/Wind Harmer
48.507
24639705ELKHART HY
Adder
0.237
270449AD2-020 GEN
Solar/Wind Harmer
4.272
270055AF2-134 C O1
Solar/Wind Harmer
4.602
965651AG1-433 GEN
Solar/Wind Harmer
8.204
972207SS24-0001
Solar/Wind Harmer
32.96
270024AE2-089 GEN
Solar/Wind Harmer
6.948
274812UNIV PK N;8U
Adder
7.423
274676JOLIET 29;8U
Adder
44.89
274745AC1-111 GEN9
Adder
8.105
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
274682WAUKEGAN ;7U
Adder
25.826
274828WAUKEGAN ;BP
Adder
15.858
24728605AND G2
Adder
5.071
25194608D.CRK4
Adder
2.025
23906502RICHG2&3
Adder
1.439
238185AF2-356 C
Solar/Wind Helper
2.037
23751101LEADS_P59
Solar/Wind Helper
1.839
238120AE2-309 GEN
Solar/Wind Helper
0.401
270224U2-072_GEN2
Solar/Wind Harmer
3.956
965051AG1-369 GEN
Solar/Wind Harmer
7.966
970031AG2-029 GEN
Solar/Wind Harmer
38.958
270404AC1-167 GEN
Solar/Wind Harmer
1.639
959141AF2-205 GEN
Solar/Wind Harmer
9.136
274775LINCOLN ;6U
Adder
9.27
274777LINCOLN ;8U
Adder
9.27
972037AH1-567 GEN1
Adder
0.27
960591AF2-350 GEN
Solar/Wind Harmer
14.735
972228AH1-698 GEN2
Adder
5.454
274675JOLIET 29;7U
Adder
44.89
274675JOLIET 29;7U
Adder
43.287
274823ROCKFORD ;21
Adder
27.402
972267AH1-718 GEN
Adder
5.748
23652301WDPWR_K20
Solar/Wind Helper
0.129
23750701CROSSCHOOL
Solar/Wind Helper
1.119
203955AF1-039 C O1
Solar/Wind Helper
0.331
961921AG1-034 GEN
Solar/Wind Harmer
30.165
270287AF1-227 GEN3
Solar/Wind Harmer
4.722
942871AE2-306 GEN
Solar/Wind Harmer
1.817
270391AF1-285 GEN3
Solar/Wind Harmer
0.932
942051AE2-217 GEN
Solar/Wind Harmer
35.999
958091AF2-103 GEN
Solar/Wind Harmer
0.254
971347AH1-153 GEN
Solar/Wind Harmer
7.866
270063AE2-323 C
Solar/Wind Harmer
3.423
944531AF1-118 GEN
Solar/Wind Harmer
54.114
958581AF2-149 GEN
Solar/Wind Harmer
6.587
972231SS25-0005
Solar/Wind Harmer
14.143
274752CRETE EC ;2U
Adder
7.284
970781AG2-491 GEN
Solar/Wind Harmer
14.841
274826FISK ;BP
Adder
16.137
274887GEN-1.85
Solar/Wind Harmer
7.851
276772AC2-154 GEN
Solar/Wind Harmer
4.112
274730ELWOOD EC;6P
Adder
24.024
25196608WSDLE5
Adder
10.619
238127S14_GEN_2
Solar/Wind Helper
0.635
202652Y1-033 WT C
Solar/Wind Helper
0.501
970707AG2-453 GEN
Solar/Wind Harmer
31.58
962761AG1-125 GEN
Solar/Wind Harmer
87.132
270520AE2-214 GEN
Solar/Wind Harmer
13.554
270391AF1-285 GEN3
Solar/Wind Harmer
2.423
270317AD1-130_GEN
Solar/Wind Harmer
6.157
253333AC1-068 GEN
Solar/Wind Harmer
1.877
270216AD2-079_GEN
Solar/Wind Harmer
0.934
958381AF2-132 GEN
Solar/Wind Harmer
13.753
274754CRETE EC ;4U
Adder
7.284
270273AD2-016 GEN
Solar/Wind Harmer
3.959
25326309TAIT D
Adder
1.618
274802UNIV PARK;5U
Adder
8.599
274674JOLIET 9 ;6U
Adder
22.504
274732ELWOOD EC;7P
Adder
24.024
274766LEE CO EC;7U
Adder
12.777
970149AG2-104 GEN
Solar/Wind Harmer
53.804
270286AF1-227 GEN2
Solar/Wind Harmer
4.722
270578AF1-285 GEN2
Solar/Wind Harmer
2.423
270258AD1-119 GEN
Solar/Wind Harmer
3.118
970373AG2-245 GEN
Solar/Wind Harmer
32.081
943021AE2-325 GEN
Solar/Wind Harmer
5.553
971917AH1-482 GEN
Solar/Wind Harmer
13.746
270297AD1-101 GEN
Solar/Wind Harmer
3.045
24791305MDL-5G
Solar/Wind Harmer
3.578
274822ROCKFORD ;11
Adder
27.602
970091AG2-072 GEN
Adder
55.681
CBM West 2LTFEXP_CBM-W2->PJM
CBM
124.415
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.5
MECLTFEXP_MEC->PJM
CLTF
20.741
SIGELTFEXP_SIGE->PJM
CLTF
0.579
NYPJM->LTFIMP_NY
CLTF
4.821
LGEELTFEXP_LGEE->PJM
CLTF
7.242
WECLTFEXP_WEC->PJM
CLTF
5.355
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.468
AG2-052LTFEXP_AG2-052->PJM
LTF
0.342
AH1-155LTFEXP_AH1-155->PJM
LTF
0.513
LAGNLTFEXP_LAGN->PJM
CLTF
14.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
TVALTFEXP_TVA->PJM
CLTF
6.29

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-020_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.82 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4424.53
MW Contribution:
14.4
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.3 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5024.36
MW Contribution:
13.94
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
13.704
270485AE1-090_GEN
Solar/Wind Harmer
0.878
253398AE2-221_GEN2
Solar/Wind Harmer
5.944
940581AE2-045 GEN
Solar/Wind Harmer
13.356
971605AH1-302 GEN
Solar/Wind Harmer
11.42
964861AG1-349 GEN
Solar/Wind Harmer
10.279
958861AF2-177 GEN
Solar/Wind Harmer
14.28
965011AG1-365 GEN
Solar/Wind Harmer
13.064
270594AE1-207 GEN
Solar/Wind Harmer
17.727
270032AE2-172
Solar/Wind Harmer
6.071
945371AF1-202 GEN
Solar/Wind Harmer
9.07
24386605FR-22G C
Solar/Wind Harmer
5.555
274773LINCOLN ;4U
Adder
8.001
274774LINCOLN ;5U
Adder
8.001
970825AG2-519 GEN
Solar/Wind Harmer
2.698
270005AE1-210 C O1
Solar/Wind Harmer
7.022
274723RIVER EC ;12
Adder
22.995
274751CRETE EC ;1U
Adder
6.273
274761LEE CO EC;2U
Adder
11.529
25196808ZIMRHP
Adder
93.328
25196008MFTGT1
Adder
1.701
254303AC2-168 GEN
Solar/Wind Helper
0.198
961971AG1-040 GEN
Solar/Wind Helper
0.519
238126S14_GEN_1
Solar/Wind Helper
0.664
970149AG2-104 GEN
Solar/Wind Harmer
37.579
270286AF1-227 GEN2
Solar/Wind Harmer
3.56
270578AF1-285 GEN2
Solar/Wind Harmer
1.829
971917AH1-482 GEN
Solar/Wind Harmer
11.86
24791305MDL-5G
Solar/Wind Harmer
3.146
970373AG2-245 GEN
Solar/Wind Harmer
27.399
274822ROCKFORD ;11
Adder
24.475
270051AF1-062 GEN
50/50
18.085
960801AF2-371 GEN
Solar/Wind Harmer
3.753
964871AG1-351 GEN
Solar/Wind Harmer
2.591
270043AE2-236 GEN
Solar/Wind Harmer
7.251
965461AG1-414 GEN
Solar/Wind Harmer
2.973
253394AE2-221_GEN
Solar/Wind Harmer
5.944
965021AG1-366 GEN
Solar/Wind Harmer
3.038
274772LINCOLN ;3U
Adder
8.001
962031AG1-047 GEN
Solar/Wind Harmer
3.895
957741AF2-068 GEN
Solar/Wind Harmer
19.322
970825AG2-519 GEN
Solar/Wind Harmer
7.243
274724RIVER EC ;11
Adder
22.726
270120AB2-067 GEN2
50/50
13.704
270160DARBY CT5
50/50
0.827
270466AD2-091
50/50
8.446
270054AF2-122 C O1
Solar/Wind Harmer
5.642
938701AE1-092 GEN
Solar/Wind Harmer
30.136
270462AD2-086
Solar/Wind Harmer
10.102
253415AE1-040 GEN
Solar/Wind Harmer
1.516
253349AC2-067 GEN
Solar/Wind Harmer
2.703
970349AG2-230 GEN
Solar/Wind Harmer
19.743
960971AF2-388 GEN
Solar/Wind Harmer
14.317
24697605MDL-3G C
Solar/Wind Harmer
4.811
270181AB1-006 GEN2
Solar/Wind Harmer
0.933
270599AE1-208 GEN
Solar/Wind Harmer
10.536
966841AG1-555 GEN
Solar/Wind Harmer
3.244
24725505WLD G2 C
Solar/Wind Harmer
5.129
270247TR4_N_V136
Solar/Wind Harmer
1.093
961921AG1-034 GEN
Solar/Wind Harmer
23.077
270287AF1-227 GEN3
Solar/Wind Harmer
3.56
942051AE2-217 GEN
Solar/Wind Harmer
29.118
942871AE2-306 GEN
Solar/Wind Harmer
1.372
270391AF1-285 GEN3
Solar/Wind Harmer
0.703
944531AF1-118 GEN
Solar/Wind Harmer
46.338
971347AH1-153 GEN
Solar/Wind Harmer
6.581
970781AG2-491 GEN
Solar/Wind Harmer
13.051
270063AE2-323 C
Solar/Wind Harmer
2.823
972231SS25-0005
Solar/Wind Harmer
12.18
274752CRETE EC ;2U
Adder
6.273
274826FISK ;BP
Adder
13.992
274730ELWOOD EC;6P
Adder
20.931
25196608WSDLE5
Adder
10.708
202652Y1-033 WT C
Solar/Wind Helper
0.578
20092526R32
Solar/Wind Helper
1.213
20398826ARMNA MT
Solar/Wind Helper
1.514
238127S14_GEN_2
Solar/Wind Helper
0.664
941421AE2-139 GEN
Solar/Wind Helper
2.265
270161DARBY CT6
50/50
0.815
25326109MON D
50/50
1.908
946101AF1-275 GEN
Solar/Wind Harmer
2.667
942861AE2-305 GEN
Solar/Wind Harmer
12.466
270269AC2-059
Solar/Wind Harmer
13.102
253400AC2-068 GEN
Solar/Wind Harmer
1.087
945421AF1-207 GEN
Solar/Wind Harmer
18.42
944541AF1-119 GEN
Solar/Wind Harmer
5.484
270180AB1-006 GEN1
Solar/Wind Harmer
9.386
24697905MDL-4G C
Solar/Wind Harmer
2.995
965791AG1-447 GEN
Solar/Wind Harmer
8.305
270031AE2-169
Solar/Wind Harmer
10.536
24699105WLD G1 C
Solar/Wind Harmer
5.069
270201AC2-176 GEN
Solar/Wind Harmer
6.621
964611AG1-324 GEN
Solar/Wind Harmer
0.674
970885AG2-551 GEN
Solar/Wind Harmer
2.991
270383AD1-128 GEN
Solar/Wind Harmer
7.821
247620Y3-023
Adder
0.588
274695ROCKY RD ;2P
Adder
14.055
25194508D.CRK3
Adder
1.762
972236AH1-702 GEN2
Adder
2.731
274765LEE CO EC;6U
Adder
11.556
274763LEE CO EC;4U
Adder
11.421
254304AE2-114 C
Solar/Wind Helper
0.274
946381AF1-302 GEN
Solar/Wind Helper
0.237
203961AE2-224 GEN
Solar/Wind Helper
2.485
940863AE2-074 GEN
Solar/Wind Helper
0.48
235054AD2-180 GEN
Solar/Wind Helper
1.679
203954AE2-126 C
Solar/Wind Helper
0.49
203946AE2-131 C
Solar/Wind Helper
0.489
235531U2-073 GEN
Solar/Wind Helper
2.681
270159DARBY CT4
50/50
0.83
961821AG1-024 GEN
Solar/Wind Harmer
15.385
945631AF1-228 GEN
Solar/Wind Harmer
7.626
253338AC1-165 GEN
Solar/Wind Harmer
1.665
270223U2-072_GEN1
Solar/Wind Harmer
2.986
270578AF1-285 GEN2
Solar/Wind Harmer
0.703
270432AC2-029 GEN
Solar/Wind Harmer
10.263
241972AD1-140 GEN
Solar/Wind Harmer
6.488
270340AC2-060 GEN
Solar/Wind Harmer
4.012
270263AC1-001 GEN
Solar/Wind Harmer
1.383
959331AF2-224 GEN
Solar/Wind Harmer
13.064
946581AF1-322 GEN
Solar/Wind Harmer
13.354
960681AF2-359 GEN
Solar/Wind Harmer
4.907
274776LINCOLN ;7U
Adder
8.001
270526AF1-158 GEN
Solar/Wind Harmer
5.84
964611AG1-324 GEN
Solar/Wind Harmer
5.022
270191TR4_S_V150
Solar/Wind Harmer
3.856
965041AG1-368 GEN
Solar/Wind Harmer
12.814
963841AG1-237 GEN
Solar/Wind Harmer
13.995
274687WILL CNTY;4U
Adder
35.61
274687WILL CNTY;4U
Adder
35.61
274731ELWOOD EC;2P
Adder
20.931
274733ELWOOD EC;3P
Adder
20.931
274746AC1-111 G10
Adder
7.088
241982AE2-343 S C
Solar/Wind Helper
0.277
23750501ELLIOTTS
Solar/Wind Helper
0.697
20089126CSLMN_L13
Solar/Wind Helper
0.615
20088926STNY CRK
Solar/Wind Helper
0.851
20094526CT_V3-030
Solar/Wind Helper
0.495
20088626ARWF_N39
Solar/Wind Helper
1.243
20334926Z1-069 C
Solar/Wind Helper
1.406
238118U2-030_1
Solar/Wind Helper
0.284
970155AG2-107 GEN
Solar/Wind Harmer
26.536
253370AE2-315 SEC1
Adder
2.687
253371AE2-315 SEC2
Adder
2.541
965651AG1-433 GEN
Solar/Wind Harmer
7.158
971995AH1-542 GEN
Solar/Wind Harmer
14.398
270055AF2-134 C O1
Solar/Wind Harmer
3.949
270024AE2-089 GEN
Solar/Wind Harmer
6.05
972207SS24-0001
Solar/Wind Harmer
28.446
241955AC1-078 GEN
Solar/Wind Harmer
12.422
241973AD2-163_GEN1
Solar/Wind Harmer
3.221
241974AD2-163_GEN2
Solar/Wind Harmer
3.221
943861AF1-054 GEN
Solar/Wind Harmer
6.153
943851AF1-053 GEN
Solar/Wind Harmer
2.973
253343AC1-166 GEN
Solar/Wind Harmer
1.665
270227U2-072_GEN3
Solar/Wind Harmer
2.986
270228U2-072_GEN4
Solar/Wind Harmer
2.986
270231U2-072_GEN5
Solar/Wind Harmer
2.986
270302AB2-170 GEN
Solar/Wind Harmer
12.161
253372AE2-315 SEC3
Adder
2.541
253372AE2-315 SEC3
Adder
2.541
25306009OHH W.
Adder
3.841
970289AG2-191 GEN
Solar/Wind Harmer
2.491
958391AF2-133 GEN
Solar/Wind Harmer
11.867
963791AG1-232 GEN
Solar/Wind Harmer
17.483
253433AC1-085 GEN1
Solar/Wind Harmer
6.842
253432AC1-085 GEN2
Solar/Wind Harmer
0.344
247521TR3_G114
Solar/Wind Harmer
4.322
972227AH1-698 GEN1
Adder
3.334
274827FISK ;RP
Adder
9.917
274800UNIV PARK;3U
Adder
7.45
274801UNIV PARK;4U
Adder
7.45
274735ELWOOD EC;4P
Adder
20.931
274744AC1-111 GEN8
Adder
7.088
241997AF1-093 GEN
Solar/Wind Helper
0.312
200917MEHOOPANY_G
Solar/Wind Helper
2.104
962771AG1-126 GEN
Solar/Wind Harmer
60.856
970153AG2-106 GEN
Solar/Wind Harmer
26.536
270284AF1-227 GEN1
Solar/Wind Harmer
9.626
276820AF1-078_GEN
Solar/Wind Harmer
2.221
960071AF2-298 GEN
Solar/Wind Harmer
2.031
253303V4-073 C
Solar/Wind Harmer
0.155
253370AE2-315 SEC1
Adder
2.687
253371AE2-315 SEC2
Adder
2.541
247642Z2-115 C
Solar/Wind Harmer
0.084
970289AG2-191 GEN
Solar/Wind Harmer
1.006
253317AC1-085 GEN4
Solar/Wind Harmer
10.78
946181AF1-283 GEN
Solar/Wind Harmer
16.739
946031AF1-268 GEN
Solar/Wind Harmer
10.671
972181SS23-001
Solar/Wind Harmer
7.613
247643Z2-116 C
Solar/Wind Harmer
0.089
276164X3-005 C
Solar/Wind Harmer
0.9
274811UNIV PK N;7U
Adder
6.415
274676JOLIET 29;8U
Adder
37.686
274734ELWOOD EC;8P
Adder
20.931
274736ELWOOD EC;9P
Adder
20.931
274682WAUKEGAN ;7U
Adder
22.672
24728505AND G1
Adder
4.783
25194608D.CRK4
Adder
2.049
274767LEE CO EC;8U
Adder
11.394
235058AG1-386 C
Solar/Wind Helper
0.575
964991AG1-363 GEN
Solar/Wind Helper
3.745
20303426NA_O38_P22
Solar/Wind Helper
1.019
203993AD2-133_GEN1
Solar/Wind Helper
1.057
965431AG1-411 GEN
Solar/Wind Harmer
0
270158DARBY CT3
50/50
0.828
270036AE2-216 BAT
50/50
9.29
270224U2-072_GEN2
Solar/Wind Harmer
2.986
959141AF2-205 GEN
Solar/Wind Harmer
7.914
253406AD2-031_GEN
Solar/Wind Harmer
1.661
945581AF1-223 GEN
Solar/Wind Harmer
5.896
24386405FR-21G C
Solar/Wind Harmer
5.555
274775LINCOLN ;6U
Adder
8.001
274777LINCOLN ;8U
Adder
8.001
961761AG1-017 GEN
Solar/Wind Harmer
0.551
247536S-71 GEN
Solar/Wind Harmer
5.208
965051AG1-369 GEN
Solar/Wind Harmer
6.421
970031AG2-029 GEN
Solar/Wind Harmer
32.137
971029AG2-637 GEN
Solar/Wind Harmer
19.276
972037AH1-567 GEN1
Adder
0.234
972228AH1-698 GEN2
Adder
4.735
274675JOLIET 29;7U
Adder
39.082
274675JOLIET 29;7U
Adder
37.686
274823ROCKFORD ;21
Adder
24.297
972267AH1-718 GEN
Adder
5.142
23652301WDPWR_K20
Solar/Wind Helper
0.16
203846AF2-130 C
Solar/Wind Helper
0.499
203955AF1-039 C O1
Solar/Wind Helper
0.382
23750701CROSSCHOOL
Solar/Wind Helper
1.187
970883AG2-550 GEN
Solar/Wind Harmer
12.861
274808UNIV PK N;4U
Adder
6.386
274674JOLIET 9 ;6U
Adder
19.605
274693ROCKY RD ;1P
Adder
13.917
274683WAUKEGAN ;8U
Adder
26.57
274683WAUKEGAN ;8U
Adder
22.397
25194408D.CRK1
Adder
9.426
972235AH1-702 GEN1
Adder
3.14
274764LEE CO EC;5U
Adder
11.556
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
946071AF1-272 GEN
Solar/Wind Helper
2.885
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.936
23585401KL_K28_T16
Solar/Wind Helper
1.272
238117U2-030
Solar/Wind Helper
0.284
270349AD2-093_GEN
Solar/Wind Harmer
6.619
270471AD2-092_GEN
Solar/Wind Harmer
6.619
253383AE2-342_GEN
Solar/Wind Harmer
1.448
25322209TAIT E
Adder
13.154
25322209TAIT E
Adder
12.859
253370AE2-315 SEC1
Adder
2.687
970291AG2-192 GEN
Solar/Wind Harmer
1.705
970291AG2-192 GEN
Solar/Wind Harmer
0.549
270535AF1-215 GEN1
Solar/Wind Harmer
5.924
270536AF1-215 GEN2
Solar/Wind Harmer
5.924
24755605MDL-5G
Solar/Wind Harmer
3.146
965681AG1-436 GEN
Solar/Wind Harmer
16.232
247621Y3-024
Adder
0.311
270246TR4_N_V150
Solar/Wind Harmer
1.093
241801AE1-079 GEN
Solar/Wind Helper
0.309
203835AF1-098 GEN
Solar/Wind Helper
2.054
203818AF1-086 GEN
Solar/Wind Helper
1.776
203853AF1-134 C O1
Solar/Wind Helper
0.498
203804AE2-113_GEN
Solar/Wind Helper
1.843
270156DARBY CT1
50/50
0.843
270157DARBY CT2
50/50
0.841
270459AD2-067 GEN
Solar/Wind Harmer
15.153
270071AF1-092 GEN
Solar/Wind Harmer
20.047
24729505KEY G4
Adder
8.564
958711AF2-162 GEN
Solar/Wind Harmer
1.325
24691005MDL-2G C
Solar/Wind Harmer
4.826
24387005FR-3G C
Solar/Wind Harmer
5.109
270543AE2-219 C
Solar/Wind Harmer
12.861
971771AH1-392 GEN
Solar/Wind Harmer
11.566
274728ELWOOD EC;5P
Adder
20.931
25196408WSDLE3
Adder
11.023
25196108MFTGT2
Adder
1.876
25196108MFTGT2
Adder
1.742
241985AE1-237 GEN
Solar/Wind Helper
0.309
20089226LOOKOUT
Solar/Wind Helper
0.613
203940AF1-140 C
Solar/Wind Helper
0.412
270119AB2-067 GEN1
50/50
13.704
25326509SID D
50/50
1.901
253378AE2-206_GEN
Solar/Wind Harmer
5
957841AF2-078 GEN
Solar/Wind Harmer
7.93
942221AE2-234 GEN
Solar/Wind Harmer
4.556
24387305FR-4G C
Solar/Wind Harmer
6.561
274770LINCOLN ;1U
Adder
8.001
274771LINCOLN ;2U
Adder
8.001
274805UNIV PK N;1U
Adder
6.429
274697ROCKY RD ;3P
Adder
3.818
274696ROCKY RD ;4P
Adder
14.387
274762LEE CO EC;3U
Adder
11.529
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
23751201ROTHROCK
Solar/Wind Helper
0.736
270475AD2-096_GEN
50/50
10.605
270518AE2-148 GEN
Solar/Wind Harmer
18.808
253325AC1-069 GEN
Solar/Wind Harmer
1.605
964401AG1-302 GEN
Solar/Wind Harmer
11.86
24690905MDL-1G C
Solar/Wind Harmer
10.477
24386205FR-12G C
Solar/Wind Harmer
5.536
24441505OLIV SLR
Solar/Wind Harmer
0.172
270004AE1-209 GEN
Solar/Wind Harmer
7.022
274753CRETE EC ;3U
Adder
6.273
274814UNIV PK N;0U
Adder
6.471
274807UNIV PK N;3U
Adder
6.457
274803UNIV PARK;6U
Adder
7.454
972038AH1-567 GEN2
Adder
0.466
274760LEE CO EC;1U
Adder
11.529
962511AG1-100 GEN
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
0.896
203854AF2-039 C
Solar/Wind Helper
0.328
972259AH1-714 GEN
Adder
24.38
274729ELWOOD EC;1P
Adder
20.931
25196008MFTGT1
Adder
1.648
237048AF1-022 C
Solar/Wind Helper
0.206
237046AF1-021 C
Solar/Wind Helper
0.372
253316AC1-085 GEN3
Solar/Wind Harmer
10.78
946171AF1-282 GEN
Solar/Wind Harmer
12.876
274812UNIV PK N;8U
Adder
6.415
24639705ELKHART HY
Adder
0.196
274676JOLIET 29;8U
Adder
39.082
274745AC1-111 GEN9
Adder
7.088
274682WAUKEGAN ;7U
Adder
22.672
274828WAUKEGAN ;BP
Adder
13.928
24728605AND G2
Adder
4.783
25194608D.CRK4
Adder
2.049
241966AE1-183 GEN
Solar/Wind Helper
0.312
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
238185AF2-356 C
Solar/Wind Helper
2.187
964201AG1-281 GEN
Solar/Wind Helper
0.499
20091526CHSTN_FL
Solar/Wind Helper
0.602
20090526Q36
Solar/Wind Helper
1.057
203952AE2-129 C
Solar/Wind Helper
0.489
238120AE2-309 GEN
Solar/Wind Helper
0.418
23751101LEADS_P59
Solar/Wind Helper
1.838
965421AG1-410 GEN
Solar/Wind Harmer
8.043
962761AG1-125 GEN
Solar/Wind Harmer
60.856
270520AE2-214 GEN
Solar/Wind Harmer
10.667
253333AC1-068 GEN
Solar/Wind Harmer
1.605
270391AF1-285 GEN3
Solar/Wind Harmer
1.829
270317AD1-130_GEN
Solar/Wind Harmer
4.649
270273AD2-016 GEN
Solar/Wind Harmer
3.736
25326309TAIT D
Adder
1.478
958381AF2-132 GEN
Solar/Wind Harmer
11.86
276903AD2-071 C
Solar/Wind Harmer
12.959
24385905FR-11G C
Solar/Wind Harmer
10.735
274754CRETE EC ;4U
Adder
6.273
270216AD2-079_GEN
Solar/Wind Harmer
0.776
274802UNIV PARK;5U
Adder
7.454
274732ELWOOD EC;7P
Adder
20.931
274674JOLIET 9 ;6U
Adder
19.605
274766LEE CO EC;7U
Adder
11.394
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.372
20089026BF_G21_K23
Solar/Wind Helper
0.487
203855AF2-088 C
Solar/Wind Helper
0.158
970091AG2-072 GEN
Adder
53.422
CPLELTFEXP_CPLE->PJM
CLTF
2.322
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.459
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.09
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.869
MECLTFEXP_MEC->PJM
CLTF
19.548
SIGELTFEXP_SIGE->PJM
CLTF
0.601
NYPJM->LTFIMP_NY
CLTF
5.177
LGEELTFEXP_LGEE->PJM
CLTF
7.861
WECLTFEXP_WEC->PJM
CLTF
4.757
AG2-052LTFEXP_AG2-052->PJM
LTF
0.298
AH1-155LTFEXP_AH1-155->PJM
LTF
0.447
LAGNLTFEXP_LAGN->PJM
CLTF
17.663
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.14
TVALTFEXP_TVA->PJM
CLTF
8.485

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-021_SRT-SL


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4419.47
MW Contribution:
14.36
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.09 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5015.35
MW Contribution:
13.89
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
13.695
270485AE1-090_GEN
Solar/Wind Harmer
0.877
253398AE2-221_GEN2
Solar/Wind Harmer
5.932
940581AE2-045 GEN
Solar/Wind Harmer
13.329
961921AG1-034 GEN
Solar/Wind Harmer
23.036
270287AF1-227 GEN3
Solar/Wind Harmer
3.554
942051AE2-217 GEN
Solar/Wind Harmer
29.065
942871AE2-306 GEN
Solar/Wind Harmer
1.369
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
270161DARBY CT6
50/50
0.814
25326109MON D
50/50
1.904
946101AF1-275 GEN
Solar/Wind Harmer
2.662
942861AE2-305 GEN
Solar/Wind Harmer
12.443
270269AC2-059
Solar/Wind Harmer
13.072
253400AC2-068 GEN
Solar/Wind Harmer
1.085
945421AF1-207 GEN
Solar/Wind Harmer
18.384
944541AF1-119 GEN
Solar/Wind Harmer
5.473
270159DARBY CT4
50/50
0.828
961821AG1-024 GEN
Solar/Wind Harmer
15.357
945631AF1-228 GEN
Solar/Wind Harmer
7.612
253338AC1-165 GEN
Solar/Wind Harmer
1.661
270223U2-072_GEN1
Solar/Wind Harmer
2.981
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
10.241
241972AD1-140 GEN
Solar/Wind Harmer
6.475
270340AC2-060 GEN
Solar/Wind Harmer
4.004
270263AC1-001 GEN
Solar/Wind Harmer
1.38
959331AF2-224 GEN
Solar/Wind Harmer
13.038
946581AF1-322 GEN
Solar/Wind Harmer
13.327
960681AF2-359 GEN
Solar/Wind Harmer
4.897
274776LINCOLN ;7U
Adder
7.985
270526AF1-158 GEN
Solar/Wind Harmer
5.829
964611AG1-324 GEN
Solar/Wind Harmer
5.011
270191TR4_S_V150
Solar/Wind Harmer
3.848
965041AG1-368 GEN
Solar/Wind Harmer
12.788
963841AG1-237 GEN
Solar/Wind Harmer
13.967
274687WILL CNTY;4U
Adder
35.54
274687WILL CNTY;4U
Adder
35.54
274731ELWOOD EC;2P
Adder
20.89
274733ELWOOD EC;3P
Adder
20.89
274746AC1-111 G10
Adder
7.074
241982AE2-343 S C
Solar/Wind Helper
0.277
23750501ELLIOTTS
Solar/Wind Helper
0.695
20089126CSLMN_L13
Solar/Wind Helper
0.614
20088926STNY CRK
Solar/Wind Helper
0.85
20094526CT_V3-030
Solar/Wind Helper
0.495
20088626ARWF_N39
Solar/Wind Helper
1.241
20334926Z1-069 C
Solar/Wind Helper
1.404
238118U2-030_1
Solar/Wind Helper
0.283
241955AC1-078 GEN
Solar/Wind Harmer
12.399
241973AD2-163_GEN1
Solar/Wind Harmer
3.215
241974AD2-163_GEN2
Solar/Wind Harmer
3.215
943861AF1-054 GEN
Solar/Wind Harmer
6.142
943851AF1-053 GEN
Solar/Wind Harmer
2.968
253343AC1-166 GEN
Solar/Wind Harmer
1.661
270227U2-072_GEN3
Solar/Wind Harmer
2.981
270228U2-072_GEN4
Solar/Wind Harmer
2.981
270231U2-072_GEN5
Solar/Wind Harmer
2.981
270302AB2-170 GEN
Solar/Wind Harmer
12.138
253372AE2-315 SEC3
Adder
2.536
253372AE2-315 SEC3
Adder
2.536
25306009OHH W.
Adder
3.833
970289AG2-191 GEN
Solar/Wind Harmer
2.486
958391AF2-133 GEN
Solar/Wind Harmer
11.843
963791AG1-232 GEN
Solar/Wind Harmer
17.447
253433AC1-085 GEN1
Solar/Wind Harmer
6.828
253432AC1-085 GEN2
Solar/Wind Harmer
0.344
247521TR3_G114
Solar/Wind Harmer
4.313
972227AH1-698 GEN1
Adder
3.328
274827FISK ;RP
Adder
9.897
274800UNIV PARK;3U
Adder
7.435
274801UNIV PARK;4U
Adder
7.435
274735ELWOOD EC;4P
Adder
20.89
274744AC1-111 GEN8
Adder
7.074
241997AF1-093 GEN
Solar/Wind Helper
0.312
962771AG1-126 GEN
Solar/Wind Harmer
60.765
970153AG2-106 GEN
Solar/Wind Harmer
26.496
270284AF1-227 GEN1
Solar/Wind Harmer
9.61
276820AF1-078_GEN
Solar/Wind Harmer
2.217
960071AF2-298 GEN
Solar/Wind Harmer
2.027
253303V4-073 C
Solar/Wind Harmer
0.155
253370AE2-315 SEC1
Adder
2.681
253371AE2-315 SEC2
Adder
2.536
247642Z2-115 C
Solar/Wind Harmer
0.084
970289AG2-191 GEN
Solar/Wind Harmer
1.004
253317AC1-085 GEN4
Solar/Wind Harmer
10.757
946181AF1-283 GEN
Solar/Wind Harmer
16.703
946031AF1-268 GEN
Solar/Wind Harmer
10.649
972181SS23-001
Solar/Wind Harmer
7.597
247643Z2-116 C
Solar/Wind Harmer
0.089
276164X3-005 C
Solar/Wind Harmer
0.899
274811UNIV PK N;7U
Adder
6.402
274676JOLIET 29;8U
Adder
37.611
274734ELWOOD EC;8P
Adder
20.89
274736ELWOOD EC;9P
Adder
20.89
274682WAUKEGAN ;7U
Adder
22.627
24728505AND G1
Adder
4.773
25194608D.CRK4
Adder
2.045
274767LEE CO EC;8U
Adder
11.371
235058AG1-386 C
Solar/Wind Helper
0.575
964991AG1-363 GEN
Solar/Wind Helper
3.733
20303426NA_O38_P22
Solar/Wind Helper
1.018
203993AD2-133_GEN1
Solar/Wind Helper
1.056
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.272
270224U2-072_GEN2
Solar/Wind Harmer
2.981
959141AF2-205 GEN
Solar/Wind Harmer
7.898
253406AD2-031_GEN
Solar/Wind Harmer
1.657
945581AF1-223 GEN
Solar/Wind Harmer
5.884
24386405FR-21G C
Solar/Wind Harmer
5.544
274775LINCOLN ;6U
Adder
7.985
274777LINCOLN ;8U
Adder
7.985
961761AG1-017 GEN
Solar/Wind Harmer
0.55
247536S-71 GEN
Solar/Wind Harmer
5.197
965051AG1-369 GEN
Solar/Wind Harmer
6.408
270120AB2-067 GEN2
50/50
13.695
270160DARBY CT5
50/50
0.825
270466AD2-091
50/50
8.429
270054AF2-122 C O1
Solar/Wind Harmer
5.631
938701AE1-092 GEN
Solar/Wind Harmer
30.075
270462AD2-086
Solar/Wind Harmer
10.083
253415AE1-040 GEN
Solar/Wind Harmer
1.513
253349AC2-067 GEN
Solar/Wind Harmer
2.698
970349AG2-230 GEN
Solar/Wind Harmer
19.704
960971AF2-388 GEN
Solar/Wind Harmer
14.288
24697605MDL-3G C
Solar/Wind Harmer
4.801
270181AB1-006 GEN2
Solar/Wind Harmer
0.931
270599AE1-208 GEN
Solar/Wind Harmer
10.515
966841AG1-555 GEN
Solar/Wind Harmer
3.237
24725505WLD G2 C
Solar/Wind Harmer
5.118
270247TR4_N_V136
Solar/Wind Harmer
1.091
970883AG2-550 GEN
Solar/Wind Harmer
12.834
274808UNIV PK N;4U
Adder
6.374
274674JOLIET 9 ;6U
Adder
19.566
274693ROCKY RD ;1P
Adder
13.889
274683WAUKEGAN ;8U
Adder
26.517
274683WAUKEGAN ;8U
Adder
22.353
25194408D.CRK1
Adder
9.405
972235AH1-702 GEN1
Adder
3.134
274764LEE CO EC;5U
Adder
11.533
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
946071AF1-272 GEN
Solar/Wind Helper
2.881
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
23585401KL_K28_T16
Solar/Wind Helper
1.269
238117U2-030
Solar/Wind Helper
0.283
270349AD2-093_GEN
Solar/Wind Harmer
6.609
270471AD2-092_GEN
Solar/Wind Harmer
6.609
253383AE2-342_GEN
Solar/Wind Harmer
1.446
25322209TAIT E
Adder
13.127
25322209TAIT E
Adder
12.832
253370AE2-315 SEC1
Adder
2.681
970291AG2-192 GEN
Solar/Wind Harmer
1.701
970291AG2-192 GEN
Solar/Wind Harmer
0.548
270535AF1-215 GEN1
Solar/Wind Harmer
5.912
270536AF1-215 GEN2
Solar/Wind Harmer
5.912
24755605MDL-5G
Solar/Wind Harmer
3.14
965681AG1-436 GEN
Solar/Wind Harmer
16.2
247621Y3-024
Adder
0.31
270246TR4_N_V150
Solar/Wind Harmer
1.091
241801AE1-079 GEN
Solar/Wind Helper
0.309
203835AF1-098 GEN
Solar/Wind Helper
2.053
203818AF1-086 GEN
Solar/Wind Helper
1.773
203853AF1-134 C O1
Solar/Wind Helper
0.498
203804AE2-113_GEN
Solar/Wind Helper
1.841
970031AG2-029 GEN
Solar/Wind Harmer
32.072
971029AG2-637 GEN
Solar/Wind Harmer
19.236
972228AH1-698 GEN2
Adder
4.726
972037AH1-567 GEN1
Adder
0.234
274675JOLIET 29;7U
Adder
39.004
274675JOLIET 29;7U
Adder
37.611
274823ROCKFORD ;21
Adder
24.249
972267AH1-718 GEN
Adder
5.132
23652301WDPWR_K20
Solar/Wind Helper
0.16
203846AF2-130 C
Solar/Wind Helper
0.499
203955AF1-039 C O1
Solar/Wind Helper
0.381
23750701CROSSCHOOL
Solar/Wind Helper
1.183
270180AB1-006 GEN1
Solar/Wind Harmer
9.367
24697905MDL-4G C
Solar/Wind Harmer
2.989
965791AG1-447 GEN
Solar/Wind Harmer
8.288
270031AE2-169
Solar/Wind Harmer
10.515
24699105WLD G1 C
Solar/Wind Harmer
5.058
270201AC2-176 GEN
Solar/Wind Harmer
6.607
964611AG1-324 GEN
Solar/Wind Harmer
0.672
970885AG2-551 GEN
Solar/Wind Harmer
2.985
270383AD1-128 GEN
Solar/Wind Harmer
7.805
247620Y3-023
Adder
0.587
274695ROCKY RD ;2P
Adder
14.027
25194508D.CRK3
Adder
1.758
972236AH1-702 GEN2
Adder
2.725
274765LEE CO EC;6U
Adder
11.533
274763LEE CO EC;4U
Adder
11.398
254304AE2-114 C
Solar/Wind Helper
0.274
946381AF1-302 GEN
Solar/Wind Helper
0.237
203961AE2-224 GEN
Solar/Wind Helper
2.481
940863AE2-074 GEN
Solar/Wind Helper
0.48
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.674
203946AE2-131 C
Solar/Wind Helper
0.488
235531U2-073 GEN
Solar/Wind Helper
2.674
270156DARBY CT1
50/50
0.842
270157DARBY CT2
50/50
0.84
270459AD2-067 GEN
Solar/Wind Harmer
15.126
270071AF1-092 GEN
Solar/Wind Harmer
20.008
24729505KEY G4
Adder
8.547
958711AF2-162 GEN
Solar/Wind Harmer
1.322
24691005MDL-2G C
Solar/Wind Harmer
4.816
24387005FR-3G C
Solar/Wind Harmer
5.099
270543AE2-219 C
Solar/Wind Harmer
12.834
971771AH1-392 GEN
Solar/Wind Harmer
11.543
270119AB2-067 GEN1
50/50
13.695
25326509SID D
50/50
1.897
253378AE2-206_GEN
Solar/Wind Harmer
4.99
957841AF2-078 GEN
Solar/Wind Harmer
7.914
942221AE2-234 GEN
Solar/Wind Harmer
4.547
24387305FR-4G C
Solar/Wind Harmer
6.548
274770LINCOLN ;1U
Adder
7.985
274771LINCOLN ;2U
Adder
7.985
274805UNIV PK N;1U
Adder
6.416
274888KELLY CRK;1U
Solar/Wind Harmer
7.53
274697ROCKY RD ;3P
Adder
3.811
274696ROCKY RD ;4P
Adder
14.358
274762LEE CO EC;3U
Adder
11.506
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
23751201ROTHROCK
Solar/Wind Helper
0.734
270475AD2-096_GEN
50/50
10.588
270518AE2-148 GEN
Solar/Wind Harmer
18.772
253325AC1-069 GEN
Solar/Wind Harmer
1.602
964401AG1-302 GEN
Solar/Wind Harmer
11.837
24690905MDL-1G C
Solar/Wind Harmer
10.457
24386205FR-12G C
Solar/Wind Harmer
5.525
24441505OLIV SLR
Solar/Wind Harmer
0.172
270004AE1-209 GEN
Solar/Wind Harmer
7.007
274753CRETE EC ;3U
Adder
6.261
274814UNIV PK N;0U
Adder
6.458
274807UNIV PK N;3U
Adder
6.444
274803UNIV PARK;6U
Adder
7.439
972038AH1-567 GEN2
Adder
0.465
274760LEE CO EC;1U
Adder
11.506
962511AG1-100 GEN
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
0.894
203854AF2-039 C
Solar/Wind Helper
0.327
276843GEN-1.7
Solar/Wind Harmer
0.048
274728ELWOOD EC;5P
Adder
20.89
25196408WSDLE3
Adder
10.998
25196108MFTGT2
Adder
1.871
25196108MFTGT2
Adder
1.738
241985AE1-237 GEN
Solar/Wind Helper
0.309
20089226LOOKOUT
Solar/Wind Helper
0.612
203940AF1-140 C
Solar/Wind Helper
0.411
270051AF1-062 GEN
50/50
18.055
960801AF2-371 GEN
Solar/Wind Harmer
3.744
964871AG1-351 GEN
Solar/Wind Harmer
2.585
270043AE2-236 GEN
Solar/Wind Harmer
7.237
965461AG1-414 GEN
Solar/Wind Harmer
2.967
253394AE2-221_GEN
Solar/Wind Harmer
5.932
965021AG1-366 GEN
Solar/Wind Harmer
3.032
274772LINCOLN ;3U
Adder
7.985
962031AG1-047 GEN
Solar/Wind Harmer
3.887
957741AF2-068 GEN
Solar/Wind Harmer
19.282
970825AG2-519 GEN
Solar/Wind Harmer
7.228
274724RIVER EC ;11
Adder
22.681
972259AH1-714 GEN
Adder
24.332
274729ELWOOD EC;1P
Adder
20.89
25196008MFTGT1
Adder
1.644
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
971605AH1-302 GEN
Solar/Wind Harmer
11.397
964861AG1-349 GEN
Solar/Wind Harmer
10.259
958861AF2-177 GEN
Solar/Wind Harmer
14.251
965011AG1-365 GEN
Solar/Wind Harmer
13.038
270594AE1-207 GEN
Solar/Wind Harmer
17.691
270032AE2-172
Solar/Wind Harmer
6.059
945371AF1-202 GEN
Solar/Wind Harmer
9.051
24386605FR-22G C
Solar/Wind Harmer
5.544
274773LINCOLN ;4U
Adder
7.985
274774LINCOLN ;5U
Adder
7.985
970825AG2-519 GEN
Solar/Wind Harmer
2.692
270005AE1-210 C O1
Solar/Wind Harmer
7.007
274723RIVER EC ;12
Adder
22.949
274751CRETE EC ;1U
Adder
6.261
274761LEE CO EC;2U
Adder
11.506
25196808ZIMRHP
Adder
93.121
25196008MFTGT1
Adder
1.698
254303AC2-168 GEN
Solar/Wind Helper
0.198
961971AG1-040 GEN
Solar/Wind Helper
0.519
238126S14_GEN_1
Solar/Wind Helper
0.662
970155AG2-107 GEN
Solar/Wind Harmer
26.496
253370AE2-315 SEC1
Adder
2.681
253371AE2-315 SEC2
Adder
2.536
965651AG1-433 GEN
Solar/Wind Harmer
7.144
971995AH1-542 GEN
Solar/Wind Harmer
14.364
270055AF2-134 C O1
Solar/Wind Harmer
3.941
270024AE2-089 GEN
Solar/Wind Harmer
6.037
972207SS24-0001
Solar/Wind Harmer
28.39
253316AC1-085 GEN3
Solar/Wind Harmer
10.757
946171AF1-282 GEN
Solar/Wind Harmer
12.848
274812UNIV PK N;8U
Adder
6.402
24639705ELKHART HY
Adder
0.196
274676JOLIET 29;8U
Adder
39.004
274745AC1-111 GEN9
Adder
7.074
274682WAUKEGAN ;7U
Adder
22.627
274828WAUKEGAN ;BP
Adder
13.9
24728605AND G2
Adder
4.773
25194608D.CRK4
Adder
2.045
241966AE1-183 GEN
Solar/Wind Helper
0.312
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
238185AF2-356 C
Solar/Wind Helper
2.181
964201AG1-281 GEN
Solar/Wind Helper
0.498
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.056
203952AE2-129 C
Solar/Wind Helper
0.488
238120AE2-309 GEN
Solar/Wind Helper
0.417
23751101LEADS_P59
Solar/Wind Helper
1.833
944531AF1-118 GEN
Solar/Wind Harmer
46.245
971347AH1-153 GEN
Solar/Wind Harmer
6.568
970781AG2-491 GEN
Solar/Wind Harmer
13.025
270063AE2-323 C
Solar/Wind Harmer
2.817
972231SS25-0005
Solar/Wind Harmer
12.156
274752CRETE EC ;2U
Adder
6.261
274826FISK ;BP
Adder
13.965
274730ELWOOD EC;6P
Adder
20.89
25196608WSDLE5
Adder
10.684
202652Y1-033 WT C
Solar/Wind Helper
0.577
20092526R32
Solar/Wind Helper
1.211
20398826ARMNA MT
Solar/Wind Helper
1.512
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.261
274887GEN-1.85
Solar/Wind Harmer
0.448
962761AG1-125 GEN
Solar/Wind Harmer
60.765
270520AE2-214 GEN
Solar/Wind Harmer
10.649
253333AC1-068 GEN
Solar/Wind Harmer
1.602
270391AF1-285 GEN3
Solar/Wind Harmer
1.826
270317AD1-130_GEN
Solar/Wind Harmer
4.64
270273AD2-016 GEN
Solar/Wind Harmer
3.727
25326309TAIT D
Adder
1.475
958381AF2-132 GEN
Solar/Wind Harmer
11.837
276903AD2-071 C
Solar/Wind Harmer
12.933
24385905FR-11G C
Solar/Wind Harmer
10.714
274754CRETE EC ;4U
Adder
6.261
270216AD2-079_GEN
Solar/Wind Harmer
0.774
274802UNIV PARK;5U
Adder
7.439
274732ELWOOD EC;7P
Adder
20.89
274674JOLIET 9 ;6U
Adder
19.566
274766LEE CO EC;7U
Adder
11.371
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.486
203855AF2-088 C
Solar/Wind Helper
0.158
970149AG2-104 GEN
Solar/Wind Harmer
37.522
270286AF1-227 GEN2
Solar/Wind Harmer
3.554
270578AF1-285 GEN2
Solar/Wind Harmer
1.826
971917AH1-482 GEN
Solar/Wind Harmer
11.837
24791305MDL-5G
Solar/Wind Harmer
3.14
970373AG2-245 GEN
Solar/Wind Harmer
27.345
274822ROCKFORD ;11
Adder
24.426
970091AG2-072 GEN
Adder
53.308
CPLELTFEXP_CPLE->PJM
CLTF
2.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.733
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.797
MECLTFEXP_MEC->PJM
CLTF
19.508
SIGELTFEXP_SIGE->PJM
CLTF
0.599
NYPJM->LTFIMP_NY
CLTF
5.166
LGEELTFEXP_LGEE->PJM
CLTF
7.844
WECLTFEXP_WEC->PJM
CLTF
4.747
AG2-052LTFEXP_AG2-052->PJM
LTF
0.298
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446
LAGNLTFEXP_LAGN->PJM
CLTF
17.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.12
TVALTFEXP_TVA->PJM
CLTF
8.468

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.67 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4418.17
MW Contribution:
14.35
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5011.7
MW Contribution:
13.87
Bus #Bus NameTypeMW Contribution
270159DARBY CT4
50/50
0.828
961821AG1-024 GEN
Solar/Wind Harmer
15.345
945631AF1-228 GEN
Solar/Wind Harmer
7.606
253338AC1-165 GEN
Solar/Wind Harmer
1.66
270223U2-072_GEN1
Solar/Wind Harmer
2.978
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
241955AC1-078 GEN
Solar/Wind Harmer
12.389
241973AD2-163_GEN1
Solar/Wind Harmer
3.212
241974AD2-163_GEN2
Solar/Wind Harmer
3.212
943861AF1-054 GEN
Solar/Wind Harmer
6.137
943851AF1-053 GEN
Solar/Wind Harmer
2.966
253343AC1-166 GEN
Solar/Wind Harmer
1.66
270227U2-072_GEN3
Solar/Wind Harmer
2.978
270228U2-072_GEN4
Solar/Wind Harmer
2.978
270231U2-072_GEN5
Solar/Wind Harmer
2.978
270302AB2-170 GEN
Solar/Wind Harmer
12.128
253372AE2-315 SEC3
Adder
2.534
253372AE2-315 SEC3
Adder
2.534
25306009OHH W.
Adder
3.829
970289AG2-191 GEN
Solar/Wind Harmer
2.484
958391AF2-133 GEN
Solar/Wind Harmer
11.833
963791AG1-232 GEN
Solar/Wind Harmer
17.431
253433AC1-085 GEN1
Solar/Wind Harmer
6.821
253432AC1-085 GEN2
Solar/Wind Harmer
0.343
247521TR3_G114
Solar/Wind Harmer
4.309
972227AH1-698 GEN1
Adder
3.325
274827FISK ;RP
Adder
9.888
274800UNIV PARK;3U
Adder
7.429
274801UNIV PARK;4U
Adder
7.429
274735ELWOOD EC;4P
Adder
20.872
274744AC1-111 GEN8
Adder
7.068
241997AF1-093 GEN
Solar/Wind Helper
0.312
962771AG1-126 GEN
Solar/Wind Harmer
60.725
970153AG2-106 GEN
Solar/Wind Harmer
26.479
270284AF1-227 GEN1
Solar/Wind Harmer
9.603
276820AF1-078_GEN
Solar/Wind Harmer
2.215
960071AF2-298 GEN
Solar/Wind Harmer
2.025
253303V4-073 C
Solar/Wind Harmer
0.155
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
247642Z2-115 C
Solar/Wind Harmer
0.084
970289AG2-191 GEN
Solar/Wind Harmer
1.003
253317AC1-085 GEN4
Solar/Wind Harmer
10.746
946181AF1-283 GEN
Solar/Wind Harmer
16.687
946031AF1-268 GEN
Solar/Wind Harmer
10.639
972181SS23-001
Solar/Wind Harmer
7.591
247643Z2-116 C
Solar/Wind Harmer
0.089
276164X3-005 C
Solar/Wind Harmer
0.898
274811UNIV PK N;7U
Adder
6.396
274676JOLIET 29;8U
Adder
37.578
274734ELWOOD EC;8P
Adder
20.872
274736ELWOOD EC;9P
Adder
20.872
274682WAUKEGAN ;7U
Adder
22.607
24728505AND G1
Adder
4.768
25194608D.CRK4
Adder
2.043
274767LEE CO EC;8U
Adder
11.361
235058AG1-386 C
Solar/Wind Helper
0.575
964991AG1-363 GEN
Solar/Wind Helper
3.728
20303426NA_O38_P22
Solar/Wind Helper
1.017
203993AD2-133_GEN1
Solar/Wind Helper
1.055
270120AB2-067 GEN2
50/50
13.691
270160DARBY CT5
50/50
0.825
270466AD2-091
50/50
8.422
270054AF2-122 C O1
Solar/Wind Harmer
5.626
938701AE1-092 GEN
Solar/Wind Harmer
30.048
270462AD2-086
Solar/Wind Harmer
10.074
253415AE1-040 GEN
Solar/Wind Harmer
1.511
253349AC2-067 GEN
Solar/Wind Harmer
2.695
970349AG2-230 GEN
Solar/Wind Harmer
19.687
960971AF2-388 GEN
Solar/Wind Harmer
14.275
24697605MDL-3G C
Solar/Wind Harmer
4.797
270181AB1-006 GEN2
Solar/Wind Harmer
0.931
270599AE1-208 GEN
Solar/Wind Harmer
10.505
966841AG1-555 GEN
Solar/Wind Harmer
3.234
24725505WLD G2 C
Solar/Wind Harmer
5.114
270247TR4_N_V136
Solar/Wind Harmer
1.09
970883AG2-550 GEN
Solar/Wind Harmer
12.822
274808UNIV PK N;4U
Adder
6.368
274674JOLIET 9 ;6U
Adder
19.549
274693ROCKY RD ;1P
Adder
13.877
270349AD2-093_GEN
Solar/Wind Harmer
6.604
270471AD2-092_GEN
Solar/Wind Harmer
6.604
253383AE2-342_GEN
Solar/Wind Harmer
1.445
25322209TAIT E
Adder
13.115
25322209TAIT E
Adder
12.82
253370AE2-315 SEC1
Adder
2.679
970291AG2-192 GEN
Solar/Wind Harmer
1.7
970291AG2-192 GEN
Solar/Wind Harmer
0.547
270535AF1-215 GEN1
Solar/Wind Harmer
5.907
270536AF1-215 GEN2
Solar/Wind Harmer
5.907
24755605MDL-5G
Solar/Wind Harmer
3.137
965681AG1-436 GEN
Solar/Wind Harmer
16.186
247621Y3-024
Adder
0.31
270246TR4_N_V150
Solar/Wind Harmer
1.09
241801AE1-079 GEN
Solar/Wind Helper
0.309
203835AF1-098 GEN
Solar/Wind Helper
2.053
203818AF1-086 GEN
Solar/Wind Helper
1.772
203853AF1-134 C O1
Solar/Wind Helper
0.497
203804AE2-113_GEN
Solar/Wind Helper
1.84
274683WAUKEGAN ;8U
Adder
26.494
274683WAUKEGAN ;8U
Adder
22.333
25194408D.CRK1
Adder
9.396
972235AH1-702 GEN1
Adder
3.131
274764LEE CO EC;5U
Adder
11.523
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
946071AF1-272 GEN
Solar/Wind Helper
2.879
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
23585401KL_K28_T16
Solar/Wind Helper
1.267
238117U2-030
Solar/Wind Helper
0.283
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.265
270224U2-072_GEN2
Solar/Wind Harmer
2.978
959141AF2-205 GEN
Solar/Wind Harmer
7.891
270432AC2-029 GEN
Solar/Wind Harmer
10.231
241972AD1-140 GEN
Solar/Wind Harmer
6.47
270340AC2-060 GEN
Solar/Wind Harmer
4
270263AC1-001 GEN
Solar/Wind Harmer
1.378
959331AF2-224 GEN
Solar/Wind Harmer
13.026
946581AF1-322 GEN
Solar/Wind Harmer
13.316
960681AF2-359 GEN
Solar/Wind Harmer
4.892
274776LINCOLN ;7U
Adder
7.978
270526AF1-158 GEN
Solar/Wind Harmer
5.824
964611AG1-324 GEN
Solar/Wind Harmer
5.007
270191TR4_S_V150
Solar/Wind Harmer
3.845
965041AG1-368 GEN
Solar/Wind Harmer
12.776
963841AG1-237 GEN
Solar/Wind Harmer
13.955
274687WILL CNTY;4U
Adder
35.509
274687WILL CNTY;4U
Adder
35.509
274731ELWOOD EC;2P
Adder
20.872
274733ELWOOD EC;3P
Adder
20.872
274746AC1-111 G10
Adder
7.068
241982AE2-343 S C
Solar/Wind Helper
0.277
23750501ELLIOTTS
Solar/Wind Helper
0.695
20089126CSLMN_L13
Solar/Wind Helper
0.613
20088926STNY CRK
Solar/Wind Helper
0.849
20094526CT_V3-030
Solar/Wind Helper
0.494
20088626ARWF_N39
Solar/Wind Helper
1.24
20334926Z1-069 C
Solar/Wind Helper
1.403
270161DARBY CT6
50/50
0.813
25326109MON D
50/50
1.903
946101AF1-275 GEN
Solar/Wind Harmer
2.66
942861AE2-305 GEN
Solar/Wind Harmer
12.433
270269AC2-059
Solar/Wind Harmer
13.059
253400AC2-068 GEN
Solar/Wind Harmer
1.084
945421AF1-207 GEN
Solar/Wind Harmer
18.368
944541AF1-119 GEN
Solar/Wind Harmer
5.469
270180AB1-006 GEN1
Solar/Wind Harmer
9.359
24697905MDL-4G C
Solar/Wind Harmer
2.986
965791AG1-447 GEN
Solar/Wind Harmer
8.281
270031AE2-169
Solar/Wind Harmer
10.505
24699105WLD G1 C
Solar/Wind Harmer
5.054
270201AC2-176 GEN
Solar/Wind Harmer
6.601
964611AG1-324 GEN
Solar/Wind Harmer
0.672
970885AG2-551 GEN
Solar/Wind Harmer
2.982
270383AD1-128 GEN
Solar/Wind Harmer
7.798
247620Y3-023
Adder
0.586
274695ROCKY RD ;2P
Adder
14.015
25194508D.CRK3
Adder
1.757
972236AH1-702 GEN2
Adder
2.723
274765LEE CO EC;6U
Adder
11.523
274763LEE CO EC;4U
Adder
11.388
254304AE2-114 C
Solar/Wind Helper
0.274
946381AF1-302 GEN
Solar/Wind Helper
0.237
203961AE2-224 GEN
Solar/Wind Helper
2.479
940863AE2-074 GEN
Solar/Wind Helper
0.479
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.672
203946AE2-131 C
Solar/Wind Helper
0.488
235531U2-073 GEN
Solar/Wind Helper
2.67
238118U2-030_1
Solar/Wind Helper
0.283
270119AB2-067 GEN1
50/50
13.691
25326509SID D
50/50
1.895
253378AE2-206_GEN
Solar/Wind Harmer
4.985
957841AF2-078 GEN
Solar/Wind Harmer
7.907
942221AE2-234 GEN
Solar/Wind Harmer
4.543
24387305FR-4G C
Solar/Wind Harmer
6.542
274770LINCOLN ;1U
Adder
7.978
274771LINCOLN ;2U
Adder
7.978
274805UNIV PK N;1U
Adder
6.41
274888KELLY CRK;1U
Solar/Wind Harmer
7.524
274697ROCKY RD ;3P
Adder
3.807
274696ROCKY RD ;4P
Adder
14.346
274762LEE CO EC;3U
Adder
11.496
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
23751201ROTHROCK
Solar/Wind Helper
0.733
270475AD2-096_GEN
50/50
10.581
270518AE2-148 GEN
Solar/Wind Harmer
18.756
253325AC1-069 GEN
Solar/Wind Harmer
1.601
964401AG1-302 GEN
Solar/Wind Harmer
11.826
24690905MDL-1G C
Solar/Wind Harmer
10.447
24386205FR-12G C
Solar/Wind Harmer
5.52
24441505OLIV SLR
Solar/Wind Harmer
0.172
270004AE1-209 GEN
Solar/Wind Harmer
7.001
274753CRETE EC ;3U
Adder
6.255
274814UNIV PK N;0U
Adder
6.452
274807UNIV PK N;3U
Adder
6.438
274803UNIV PARK;6U
Adder
7.433
972038AH1-567 GEN2
Adder
0.465
274760LEE CO EC;1U
Adder
11.496
962511AG1-100 GEN
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
0.893
203854AF2-039 C
Solar/Wind Helper
0.327
276843GEN-1.7
Solar/Wind Harmer
0.048
270156DARBY CT1
50/50
0.841
270157DARBY CT2
50/50
0.839
270459AD2-067 GEN
Solar/Wind Harmer
15.114
270071AF1-092 GEN
Solar/Wind Harmer
19.99
24729505KEY G4
Adder
8.54
958711AF2-162 GEN
Solar/Wind Harmer
1.321
24691005MDL-2G C
Solar/Wind Harmer
4.812
24387005FR-3G C
Solar/Wind Harmer
5.095
270543AE2-219 C
Solar/Wind Harmer
12.822
971771AH1-392 GEN
Solar/Wind Harmer
11.533
274728ELWOOD EC;5P
Adder
20.872
25196408WSDLE3
Adder
10.988
25196108MFTGT2
Adder
1.87
25196108MFTGT2
Adder
1.736
241985AE1-237 GEN
Solar/Wind Helper
0.309
20089226LOOKOUT
Solar/Wind Helper
0.611
203940AF1-140 C
Solar/Wind Helper
0.411
270051AF1-062 GEN
50/50
18.043
960801AF2-371 GEN
Solar/Wind Harmer
3.74
964871AG1-351 GEN
Solar/Wind Harmer
2.583
270043AE2-236 GEN
Solar/Wind Harmer
7.23
965461AG1-414 GEN
Solar/Wind Harmer
2.965
253394AE2-221_GEN
Solar/Wind Harmer
5.926
965021AG1-366 GEN
Solar/Wind Harmer
3.029
274772LINCOLN ;3U
Adder
7.978
962031AG1-047 GEN
Solar/Wind Harmer
3.883
957741AF2-068 GEN
Solar/Wind Harmer
19.265
970825AG2-519 GEN
Solar/Wind Harmer
7.221
274724RIVER EC ;11
Adder
22.661
972259AH1-714 GEN
Adder
24.311
274729ELWOOD EC;1P
Adder
20.872
25196008MFTGT1
Adder
1.643
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
270166AC1-044 GEN3
50/50
13.691
270485AE1-090_GEN
Solar/Wind Harmer
0.876
253398AE2-221_GEN2
Solar/Wind Harmer
5.926
940581AE2-045 GEN
Solar/Wind Harmer
13.318
971605AH1-302 GEN
Solar/Wind Harmer
11.387
964861AG1-349 GEN
Solar/Wind Harmer
10.25
958861AF2-177 GEN
Solar/Wind Harmer
14.238
965011AG1-365 GEN
Solar/Wind Harmer
13.026
270594AE1-207 GEN
Solar/Wind Harmer
17.675
270032AE2-172
Solar/Wind Harmer
6.053
945371AF1-202 GEN
Solar/Wind Harmer
9.043
24386605FR-22G C
Solar/Wind Harmer
5.54
274773LINCOLN ;4U
Adder
7.978
274774LINCOLN ;5U
Adder
7.978
970825AG2-519 GEN
Solar/Wind Harmer
2.69
270005AE1-210 C O1
Solar/Wind Harmer
7.001
274723RIVER EC ;12
Adder
22.929
274751CRETE EC ;1U
Adder
6.255
274761LEE CO EC;2U
Adder
11.496
25196808ZIMRHP
Adder
93.029
25196008MFTGT1
Adder
1.696
254303AC2-168 GEN
Solar/Wind Helper
0.198
961971AG1-040 GEN
Solar/Wind Helper
0.519
238126S14_GEN_1
Solar/Wind Helper
0.662
970155AG2-107 GEN
Solar/Wind Harmer
26.479
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
965651AG1-433 GEN
Solar/Wind Harmer
7.138
971995AH1-542 GEN
Solar/Wind Harmer
14.349
270055AF2-134 C O1
Solar/Wind Harmer
3.938
270024AE2-089 GEN
Solar/Wind Harmer
6.032
972207SS24-0001
Solar/Wind Harmer
28.366
253316AC1-085 GEN3
Solar/Wind Harmer
10.746
946171AF1-282 GEN
Solar/Wind Harmer
12.836
274812UNIV PK N;8U
Adder
6.396
24639705ELKHART HY
Adder
0.196
274676JOLIET 29;8U
Adder
38.97
274745AC1-111 GEN9
Adder
7.068
274682WAUKEGAN ;7U
Adder
22.607
274828WAUKEGAN ;BP
Adder
13.888
24728605AND G2
Adder
4.768
25194608D.CRK4
Adder
2.043
241966AE1-183 GEN
Solar/Wind Helper
0.312
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
964201AG1-281 GEN
Solar/Wind Helper
0.498
238185AF2-356 C
Solar/Wind Helper
2.178
20091526CHSTN_FL
Solar/Wind Helper
0.601
20090526Q36
Solar/Wind Helper
1.055
203952AE2-129 C
Solar/Wind Helper
0.488
238120AE2-309 GEN
Solar/Wind Helper
0.416
23751101LEADS_P59
Solar/Wind Helper
1.832
253406AD2-031_GEN
Solar/Wind Harmer
1.656
945581AF1-223 GEN
Solar/Wind Harmer
5.879
24386405FR-21G C
Solar/Wind Harmer
5.54
274775LINCOLN ;6U
Adder
7.978
274777LINCOLN ;8U
Adder
7.978
961761AG1-017 GEN
Solar/Wind Harmer
0.55
247536S-71 GEN
Solar/Wind Harmer
5.193
965051AG1-369 GEN
Solar/Wind Harmer
6.402
970031AG2-029 GEN
Solar/Wind Harmer
32.043
971029AG2-637 GEN
Solar/Wind Harmer
19.218
972228AH1-698 GEN2
Adder
4.722
972037AH1-567 GEN1
Adder
0.233
274675JOLIET 29;7U
Adder
38.97
274675JOLIET 29;7U
Adder
37.578
274823ROCKFORD ;21
Adder
24.227
972267AH1-718 GEN
Adder
5.127
23652301WDPWR_K20
Solar/Wind Helper
0.16
203846AF2-130 C
Solar/Wind Helper
0.498
203955AF1-039 C O1
Solar/Wind Helper
0.38
23750701CROSSCHOOL
Solar/Wind Helper
1.182
961921AG1-034 GEN
Solar/Wind Harmer
23.018
270287AF1-227 GEN3
Solar/Wind Harmer
3.552
942051AE2-217 GEN
Solar/Wind Harmer
29.041
942871AE2-306 GEN
Solar/Wind Harmer
1.368
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
944531AF1-118 GEN
Solar/Wind Harmer
46.204
971347AH1-153 GEN
Solar/Wind Harmer
6.562
970781AG2-491 GEN
Solar/Wind Harmer
13.014
270063AE2-323 C
Solar/Wind Harmer
2.815
972231SS25-0005
Solar/Wind Harmer
12.145
274752CRETE EC ;2U
Adder
6.255
274826FISK ;BP
Adder
13.952
274730ELWOOD EC;6P
Adder
20.872
25196608WSDLE5
Adder
10.674
202652Y1-033 WT C
Solar/Wind Helper
0.576
20092526R32
Solar/Wind Helper
1.21
20398826ARMNA MT
Solar/Wind Helper
1.511
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.259
274887GEN-1.85
Solar/Wind Harmer
0.448
962761AG1-125 GEN
Solar/Wind Harmer
60.725
270520AE2-214 GEN
Solar/Wind Harmer
10.641
253333AC1-068 GEN
Solar/Wind Harmer
1.601
270391AF1-285 GEN3
Solar/Wind Harmer
1.824
270317AD1-130_GEN
Solar/Wind Harmer
4.636
270273AD2-016 GEN
Solar/Wind Harmer
3.724
25326309TAIT D
Adder
1.474
958381AF2-132 GEN
Solar/Wind Harmer
11.826
276903AD2-071 C
Solar/Wind Harmer
12.921
24385905FR-11G C
Solar/Wind Harmer
10.705
274754CRETE EC ;4U
Adder
6.255
270216AD2-079_GEN
Solar/Wind Harmer
0.773
274802UNIV PARK;5U
Adder
7.433
274732ELWOOD EC;7P
Adder
20.872
274674JOLIET 9 ;6U
Adder
19.549
274766LEE CO EC;7U
Adder
11.361
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.485
203855AF2-088 C
Solar/Wind Helper
0.158
970149AG2-104 GEN
Solar/Wind Harmer
37.498
270286AF1-227 GEN2
Solar/Wind Harmer
3.552
270578AF1-285 GEN2
Solar/Wind Harmer
1.824
971917AH1-482 GEN
Solar/Wind Harmer
11.826
24791305MDL-5G
Solar/Wind Harmer
3.137
970373AG2-245 GEN
Solar/Wind Harmer
27.321
274822ROCKFORD ;11
Adder
24.404
970091AG2-072 GEN
Adder
53.258
CPLELTFEXP_CPLE->PJM
CLTF
2.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.056
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.765
MECLTFEXP_MEC->PJM
CLTF
19.491
SIGELTFEXP_SIGE->PJM
CLTF
0.599
NYPJM->LTFIMP_NY
CLTF
5.162
LGEELTFEXP_LGEE->PJM
CLTF
7.836
WECLTFEXP_WEC->PJM
CLTF
4.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.297
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446
LAGNLTFEXP_LAGN->PJM
CLTF
17.61
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.111
TVALTFEXP_TVA->PJM
CLTF
8.46

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4342.78
MW Contribution:
3.34
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.43 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4946.71
MW Contribution:
3.23
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
10.581
270518AE2-148 GEN
Solar/Wind Harmer
0.888
253325AC1-069 GEN
Solar/Wind Harmer
0.012
970191AG2-125 GEN
Solar/Wind Harmer
2.379
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
971655AH1-328 GEN
Solar/Wind Harmer
3.602
25322209TAIT E
Adder
13.115
25322209TAIT E
Adder
12.82
253370AE2-315 SEC1
Adder
2.679
970291AG2-192 GEN
Solar/Wind Harmer
1.186
970291AG2-192 GEN
Solar/Wind Harmer
0.547
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
4.358
965681AG1-436 GEN
Solar/Wind Harmer
11.293
247621Y3-024
Adder
0.31
270246TR4_N_V150
Solar/Wind Harmer
0.057
276776AD2-060 GEN
Solar/Wind Harmer
0.949
276901AD2-066 C O1
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
17.379
971343AH1-151 GEN
Solar/Wind Harmer
17.379
971587AH1-292 GEN
Solar/Wind Harmer
6.129
276916AD2-100_GEN
Solar/Wind Harmer
17.538
241801AE1-079 GEN
Solar/Wind Helper
0.309
203835AF1-098 GEN
Solar/Wind Helper
2.053
203818AF1-086 GEN
Solar/Wind Helper
1.772
203853AF1-134 C O1
Solar/Wind Helper
0.497
203804AE2-113_GEN
Solar/Wind Helper
1.84
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
4.282
943851AF1-053 GEN
Solar/Wind Harmer
2.966
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.422
253372AE2-315 SEC3
Adder
2.534
253372AE2-315 SEC3
Adder
2.534
25306009OHH W.
Adder
3.829
970289AG2-191 GEN
Solar/Wind Harmer
1.733
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
12.161
247521TR3_G114
Solar/Wind Harmer
0.324
972227AH1-698 GEN1
Adder
3.325
274827FISK ;RP
Adder
9.888
274800UNIV PARK;3U
Adder
7.429
274801UNIV PARK;4U
Adder
7.429
957201AF2-014 GEN
Solar/Wind Harmer
0.001
274735ELWOOD EC;4P
Adder
20.872
274744AC1-111 GEN8
Adder
7.068
970169AG2-114 GEN
Solar/Wind Harmer
8.736
959341AF2-225 GEN
Solar/Wind Harmer
9.098
274877BISHOP HL;1U
Solar/Wind Harmer
0.287
276741O09 GEN1
Solar/Wind Harmer
0.303
276668AB2-070 GEN1
Solar/Wind Harmer
0.334
276848AB2-070 GEN3
Solar/Wind Harmer
0.333
276849AB2-070 GEN2
Solar/Wind Harmer
0.334
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
241997AF1-093 GEN
Solar/Wind Helper
0.312
24690905MDL-1G C
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.936
274753CRETE EC ;3U
Adder
10.545
274814UNIV PK N;0U
Adder
6.452
274807UNIV PK N;3U
Adder
6.438
276843GEN-1.7
Solar/Wind Harmer
0.288
274803UNIV PARK;6U
Adder
7.433
972038AH1-567 GEN2
Adder
0.465
24379505HDWTR1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
1.154
965091AG1-374 GEN
Solar/Wind Harmer
25.867
274760LEE CO EC;1U
Adder
11.496
274878BISHOP HL;2U
Solar/Wind Harmer
0.287
965931AG1-462 GEN
Solar/Wind Harmer
21.621
962511AG1-100 GEN
Solar/Wind Helper
0.518
23562501BACKB
Solar/Wind Helper
0.893
203854AF2-039 C
Solar/Wind Helper
0.327
270159DARBY CT4
50/50
0.828
961821AG1-024 GEN
Solar/Wind Harmer
7.494
945631AF1-228 GEN
Solar/Wind Harmer
0
270578AF1-285 GEN2
Solar/Wind Harmer
0.702
270432AC2-029 GEN
Solar/Wind Harmer
4.521
241972AD1-140 GEN
Solar/Wind Harmer
1.102
270119AB2-067 GEN1
50/50
13.691
25326509SID D
50/50
1.895
957841AF2-078 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
3.637
24387305FR-4G C
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
10.86
274771LINCOLN ;2U
Adder
10.86
274805UNIV PK N;1U
Adder
6.41
274888KELLY CRK;1U
Solar/Wind Harmer
0.519
970941AG2-585 GEN
Solar/Wind Harmer
4.892
276897AD1-100 C
Solar/Wind Harmer
22.228
246937BC-WTG2
Solar/Wind Harmer
0.358
276893AG1-478 C
Solar/Wind Harmer
0.591
970241AG2-163 GEN
Solar/Wind Harmer
5.155
274697ROCKY RD ;3P
Adder
3.807
274696ROCKY RD ;4P
Adder
14.346
962691AG1-118 GEN
Solar/Wind Harmer
26.273
247607V1-011 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
2.816
938861AE1-114 GEN
Solar/Wind Harmer
4.893
276645AC1-214 GEN1
Solar/Wind Harmer
0.338
274762LEE CO EC;3U
Adder
11.496
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.387
276838X2-022 GEN2
Solar/Wind Harmer
0.476
970623AG2-406 GEN
Solar/Wind Harmer
1.547
962581AG1-107 GEN
Solar/Wind Harmer
0.001
962101AG1-054 GEN
Solar/Wind Helper
0.794
237043AE2-125 C
Solar/Wind Helper
0.201
23751201ROTHROCK
Solar/Wind Helper
0.733
270166AC1-044 GEN3
50/50
13.691
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
11.387
964861AG1-349 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
3.938
965011AG1-365 GEN
Solar/Wind Harmer
9.088
270594AE1-207 GEN
Solar/Wind Harmer
10.169
270032AE2-172
Solar/Wind Harmer
6.053
945371AF1-202 GEN
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
10.86
274774LINCOLN ;5U
Adder
10.86
970825AG2-519 GEN
Solar/Wind Harmer
3.175
270005AE1-210 C O1
Solar/Wind Harmer
1.936
274723RIVER EC ;12
Adder
22.929
274751CRETE EC ;1U
Adder
10.545
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.358
270489AE1-102 GEN1
Solar/Wind Harmer
1.154
957891AF2-083 GEN
Solar/Wind Harmer
14.717
945111AF1-176 GEN
Solar/Wind Harmer
15.739
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
4.591
970569AG2-363 GEN
Solar/Wind Harmer
26.052
939741AE1-205 GEN
Solar/Wind Harmer
12.131
252510AF1-249 C
Solar/Wind Harmer
0.065
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
11.496
25196808ZIMRHP
Adder
93.029
25196008MFTGT1
Adder
1.696
276621W2-048 GEN
Solar/Wind Harmer
0.423
254303AC2-168 GEN
Solar/Wind Helper
0.198
961971AG1-040 GEN
Solar/Wind Helper
0.519
238126S14_GEN_1
Solar/Wind Helper
0.662
962771AG1-126 GEN
Solar/Wind Harmer
51.21
970153AG2-106 GEN
Solar/Wind Harmer
32.701
270284AF1-227 GEN1
Solar/Wind Harmer
0
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.003
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.642
946031AF1-268 GEN
Solar/Wind Harmer
8.511
274811UNIV PK N;7U
Adder
6.396
276806AD2-047 C O1
Solar/Wind Harmer
5.041
274676JOLIET 29;8U
Adder
37.578
274734ELWOOD EC;8P
Adder
20.872
274736ELWOOD EC;9P
Adder
20.872
943121AE2-341 GEN
Solar/Wind Harmer
14.798
943591AF1-030 GEN
Solar/Wind Harmer
9.841
24695305TIMB G C
Solar/Wind Harmer
0.747
274682WAUKEGAN ;7U
Adder
22.607
959091AF2-200 GEN
Solar/Wind Harmer
17.379
24728505AND G1
Adder
4.768
25194608D.CRK4
Adder
2.043
252519AF1-045_GEN
Solar/Wind Harmer
4.521
274767LEE CO EC;8U
Adder
11.361
971087AG2-675 GEN
Solar/Wind Harmer
4.522
957381AF2-032 GEN
Solar/Wind Harmer
1.898
235058AG1-386 C
Solar/Wind Helper
0.575
964991AG1-363 GEN
Solar/Wind Helper
3.728
20303426NA_O38_P22
Solar/Wind Helper
1.017
203993AD2-133_GEN1
Solar/Wind Helper
1.055
970155AG2-107 GEN
Solar/Wind Harmer
32.701
253370AE2-315 SEC1
Adder
2.679
253371AE2-315 SEC2
Adder
2.534
965651AG1-433 GEN
Solar/Wind Harmer
2.673
971995AH1-542 GEN
Solar/Wind Harmer
3.337
270055AF2-134 C O1
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.955
274812UNIV PK N;8U
Adder
6.396
24639705ELKHART HY
Adder
0.196
965421AG1-410 GEN
Solar/Wind Harmer
26.684
970613AG2-401 GEN
Solar/Wind Harmer
6.512
274676JOLIET 29;8U
Adder
38.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
7.068
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
22.607
274828WAUKEGAN ;BP
Adder
13.888
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
957471AF2-041 GEN
Solar/Wind Harmer
26.068
24728605AND G2
Adder
4.768
25194608D.CRK4
Adder
2.043
252516AE2-318_GEN
Solar/Wind Harmer
9.707
274848CAMPGROVE;RU
Solar/Wind Harmer
0
241966AE1-183 GEN
Solar/Wind Helper
0.312
203830AF1-094 GEN
Solar/Wind Helper
0.518
203979AG1-198 GEN
Solar/Wind Helper
0.311
964201AG1-281 GEN
Solar/Wind Helper
0.498
238185AF2-356 C
Solar/Wind Helper
2.178
20091526CHSTN_FL
Solar/Wind Helper
0.601
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.92
959331AF2-224 GEN
Solar/Wind Harmer
6.362
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.469
274776LINCOLN ;7U
Adder
10.86
270526AF1-158 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
3.493
965041AG1-368 GEN
Solar/Wind Harmer
8.914
963841AG1-237 GEN
Solar/Wind Harmer
3.86
274687WILL CNTY;4U
Adder
35.509
274687WILL CNTY;4U
Adder
35.509
274731ELWOOD EC;2P
Adder
20.872
274733ELWOOD EC;3P
Adder
20.872
274746AC1-111 G10
Adder
7.068
270356AE2-297 GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.477
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.277
23750501ELLIOTTS
Solar/Wind Helper
0.695
20089126CSLMN_L13
Solar/Wind Helper
0.613
20088926STNY CRK
Solar/Wind Helper
0.849
20094526CT_V3-030
Solar/Wind Helper
0.494
20088626ARWF_N39
Solar/Wind Helper
1.24
20334926Z1-069 C
Solar/Wind Helper
1.403
238118U2-030_1
Solar/Wind Helper
0.283
970149AG2-104 GEN
Solar/Wind Harmer
27.654
971917AH1-482 GEN
Solar/Wind Harmer
11.826
970373AG2-245 GEN
Solar/Wind Harmer
19.061
941551AE2-152 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
20.916
276691AA1-018 GEN1
Solar/Wind Harmer
1.43
274861TOP CROP ;1U
Solar/Wind Harmer
0
970773AG2-487 GEN
Solar/Wind Harmer
1.548
943021AE2-325 GEN
Solar/Wind Harmer
4.573
276882AE2-255 GEN
Solar/Wind Harmer
1.021
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
8.689
971067AG2-660 GEN
Solar/Wind Harmer
2.896
274822ROCKFORD ;11
Adder
24.404
276655WTG1_EQ
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
10.388
276646AC1-214 GEN2
Solar/Wind Harmer
0.338
970091AG2-072 GEN
Adder
16.07
270161DARBY CT6
50/50
0.813
25326109MON D
50/50
1.903
942861AE2-305 GEN
Solar/Wind Harmer
8.674
270269AC2-059
Solar/Wind Harmer
0
970329AG2-216 GEN
Solar/Wind Harmer
4.181
945421AF1-207 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.609
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
8.281
270031AE2-169
Solar/Wind Harmer
4.946
24699105WLD G1 C
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.672
970885AG2-551 GEN
Solar/Wind Harmer
2.982
270383AD1-128 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
12.809
247620Y3-023
Adder
0.586
274695ROCKY RD ;2P
Adder
14.015
958491AF2-143 GEN
Solar/Wind Harmer
13.148
276872AE1-163_GEN1
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.001
25194508D.CRK3
Adder
1.757
972236AH1-702 GEN2
Adder
2.723
274765LEE CO EC;6U
Adder
11.523
274763LEE CO EC;4U
Adder
11.388
252509AD1-136 GEN
Solar/Wind Harmer
0.043
962761AG1-125 GEN
Solar/Wind Harmer
51.21
270520AE2-214 GEN
Solar/Wind Harmer
0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
270273AD2-016 GEN
Solar/Wind Harmer
1.001
25326309TAIT D
Adder
1.474
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
10.066
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
10.545
274802UNIV PARK;5U
Adder
7.433
270437AC2-090 C
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
20.872
274674JOLIET 9 ;6U
Adder
19.549
939401AE1-172 GEN
Solar/Wind Harmer
6.59
962781AG1-127 GEN
Solar/Wind Harmer
8.326
274766LEE CO EC;7U
Adder
11.361
276708O09 GEN2
Solar/Wind Harmer
0.303
965911AG1-460 GEN
Solar/Wind Harmer
1.674
203947AF1-006 C
Solar/Wind Helper
0.563
20084626FORWARD
Solar/Wind Helper
0.371
20089026BF_G21_K23
Solar/Wind Helper
0.485
203855AF2-088 C
Solar/Wind Helper
0.158
270120AB2-067 GEN2
50/50
13.691
270160DARBY CT5
50/50
0.825
270466AD2-091
50/50
8.422
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
16.303
270462AD2-086
Solar/Wind Harmer
0.001
970349AG2-230 GEN
Solar/Wind Harmer
13.735
960971AF2-388 GEN
Solar/Wind Harmer
5.346
24697605MDL-3G C
Solar/Wind Harmer
0
270599AE1-208 GEN
Solar/Wind Harmer
8.243
966841AG1-555 GEN
Solar/Wind Harmer
1.019
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.057
970883AG2-550 GEN
Solar/Wind Harmer
8.946
274808UNIV PK N;4U
Adder
6.368
926881AC1-175 GEN
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
19.549
958481AF2-142 GEN
Solar/Wind Harmer
13.2
961051AF2-396 GEN
Solar/Wind Harmer
17.567
961051AF2-396 GEN
Solar/Wind Harmer
11.711
274693ROCKY RD ;1P
Adder
13.877
274683WAUKEGAN ;8U
Adder
26.494
274683WAUKEGAN ;8U
Adder
22.333
276876AE1-163_GEN2
Solar/Wind Harmer
0
270051AF1-062 GEN
50/50
18.043
270043AE2-236 GEN
Solar/Wind Harmer
5.885
253394AE2-221_GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
3.029
274772LINCOLN ;3U
Adder
10.86
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
13.441
970825AG2-519 GEN
Solar/Wind Harmer
6.737
274724RIVER EC ;11
Adder
22.661
972259AH1-714 GEN
Adder
24.311
270240V3-007_GEN2
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.319
274729ELWOOD EC;1P
Adder
20.872
270505AE1-170 C O1
Solar/Wind Harmer
9.267
945111AF1-176 GEN
Solar/Wind Harmer
7.15
946671AF1-331 GEN
Solar/Wind Harmer
0.929
274850MENDOTA H;RU
Solar/Wind Harmer
0.101
970571AG2-364 GEN
Solar/Wind Harmer
17.368
971993AH1-541 GEN
Solar/Wind Harmer
3.929
25196008MFTGT1
Adder
1.643
942481AE2-261 GEN
Solar/Wind Harmer
25.023
270367AC2-061_GEN
Solar/Wind Harmer
-0.001
237048AF1-022 C
Solar/Wind Helper
0.205
237046AF1-021 C
Solar/Wind Helper
0.372
270156DARBY CT1
50/50
0.841
270157DARBY CT2
50/50
0.839
270459AD2-067 GEN
Solar/Wind Harmer
0
270071AF1-092 GEN
Solar/Wind Harmer
17.821
24729505KEY G4
Adder
8.54
24691005MDL-2G C
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.262
971771AH1-392 GEN
Solar/Wind Harmer
8.94
270435AC2-044 GEN
Solar/Wind Harmer
1.124
274728ELWOOD EC;5P
Adder
20.872
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.922
276861AD2-134 GEN
Solar/Wind Harmer
0.155
276863AD2-134 GEN
Solar/Wind Harmer
0.155
25196408WSDLE3
Adder
10.988
270007AE1-245 C
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
0.202
971681AH1-341 GEN
Solar/Wind Harmer
13.904
25196108MFTGT2
Adder
1.87
25196108MFTGT2
Adder
1.736
241985AE1-237 GEN
Solar/Wind Helper
0.309
20089226LOOKOUT
Solar/Wind Helper
0.611
203940AF1-140 C
Solar/Wind Helper
0.411
25194408D.CRK1
Adder
9.396
972235AH1-702 GEN1
Adder
3.131
960611AF2-352 GEN
Solar/Wind Harmer
2.874
274764LEE CO EC;5U
Adder
11.523
945391AF1-204 GEN
Solar/Wind Harmer
9.138
276615X2-022 GEN
Solar/Wind Harmer
0.088
254305AE2-115 C
Solar/Wind Helper
0.274
241967AE2-285_GEN
Solar/Wind Helper
0.791
946071AF1-272 GEN
Solar/Wind Helper
2.879
20083426SW_E13_K22
Solar/Wind Helper
0.058
20088826HIGHLAND
Solar/Wind Helper
0.934
23585401KL_K28_T16
Solar/Wind Helper
1.267
238117U2-030
Solar/Wind Helper
0.283
961921AG1-034 GEN
Solar/Wind Harmer
11.241
942051AE2-217 GEN
Solar/Wind Harmer
20.261
270391AF1-285 GEN3
Solar/Wind Harmer
0.702
944531AF1-118 GEN
Solar/Wind Harmer
41.277
971347AH1-153 GEN
Solar/Wind Harmer
4.578
970781AG2-491 GEN
Solar/Wind Harmer
9.079
270063AE2-323 C
Solar/Wind Harmer
0.001
274752CRETE EC ;2U
Adder
10.545
274887GEN-1.85
Solar/Wind Harmer
0.231
970707AG2-453 GEN
Solar/Wind Harmer
29.056
274826FISK ;BP
Adder
13.952
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
20.872
274862TOP CROP ;2U
Solar/Wind Harmer
1.188
276868AE1-113 GEN
Solar/Wind Harmer
1.751
274879MINONK ;1U
Solar/Wind Harmer
0.365
274855GSG-6 ;RU
Solar/Wind Harmer
0.318
25196608WSDLE5
Adder
10.674
959611AF2-252 GEN
Solar/Wind Harmer
2.874
274857EASY ROAD;U1
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
12.901
276782AC1-033 GEN
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.384
202652Y1-033 WT C
Solar/Wind Helper
0.576
20092526R32
Solar/Wind Helper
1.21
20398826ARMNA MT
Solar/Wind Helper
1.511
238127S14_GEN_2
Solar/Wind Helper
0.662
941421AE2-139 GEN
Solar/Wind Helper
2.259
958171AF2-111 GEN
Solar/Wind Harmer
13.887
270158DARBY CT3
50/50
0.826
270036AE2-216 BAT
50/50
9.265
971611AH1-305 GEN
Solar/Wind Harmer
5.423
959141AF2-205 GEN
Solar/Wind Harmer
0.001
253406AD2-031_GEN
Solar/Wind Harmer
0.671
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
10.86
274777LINCOLN ;8U
Adder
10.86
247536S-71 GEN
Solar/Wind Harmer
0.358
965051AG1-369 GEN
Solar/Wind Harmer
4.466
970031AG2-029 GEN
Solar/Wind Harmer
4.844
971029AG2-637 GEN
Solar/Wind Harmer
13.408
960591AF2-350 GEN
Solar/Wind Harmer
8.895
972228AH1-698 GEN2
Adder
4.722
972037AH1-567 GEN1
Adder
0.233
274675JOLIET 29;7U
Adder
38.97
274675JOLIET 29;7U
Adder
37.578
970833AG2-524 GEN
Solar/Wind Harmer
9.741
970833AG2-524 GEN
Solar/Wind Harmer
6.494
971675AH1-338 GEN
Solar/Wind Harmer
3.397
971411AH1-196 GEN
Solar/Wind Harmer
13.063
971171AH1-044 GEN
Solar/Wind Harmer
17.379
274823ROCKFORD ;21
Adder
24.227
274853TWINGROVE;U1
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.127
946321AF1-296 GEN
Solar/Wind Harmer
4.758
23652301WDPWR_K20
Solar/Wind Helper
0.16
203846AF2-130 C
Solar/Wind Helper
0.498
203955AF1-039 C O1
Solar/Wind Helper
0.38
23750701CROSSCHOOL
Solar/Wind Helper
1.182
276911AD2-131_GEN
Solar/Wind Harmer
1.155
254304AE2-114 C
Solar/Wind Helper
0.274
946381AF1-302 GEN
Solar/Wind Helper
0.237
203961AE2-224 GEN
Solar/Wind Helper
2.479
940863AE2-074 GEN
Solar/Wind Helper
0.479
203954AE2-126 C
Solar/Wind Helper
0.489
235054AD2-180 GEN
Solar/Wind Helper
1.672
203946AE2-131 C
Solar/Wind Helper
0.488
235531U2-073 GEN
Solar/Wind Helper
2.67
20090526Q36
Solar/Wind Helper
1.055
203952AE2-129 C
Solar/Wind Helper
0.488
238120AE2-309 GEN
Solar/Wind Helper
0.416
23751101LEADS_P59
Solar/Wind Helper
1.832
CPLELTFEXP_CPLE->PJM
CLTF
2.319
CBM West 2LTFEXP_CBM-W2->PJM
CBM
135.056
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.575
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.765
MECLTFEXP_MEC->PJM
CLTF
19.491
SIGELTFEXP_SIGE->PJM
CLTF
0.599
NYPJM->LTFIMP_NY
CLTF
5.162
LGEELTFEXP_LGEE->PJM
CLTF
7.836
WECLTFEXP_WEC->PJM
CLTF
4.743
AG2-052LTFEXP_AG2-052->PJM
LTF
0.297
AH1-155LTFEXP_AH1-155->PJM
LTF
0.446
LAGNLTFEXP_LAGN->PJM
CLTF
17.61
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.111
TVALTFEXP_TVA->PJM
CLTF
8.46

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4309.27
MW Contribution:
4.58
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:92.06 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3813.12
MW Contribution:
3.83
Bus #Bus NameTypeMW Contribution
270349AD2-093_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Harmer
0.002
971655AH1-328 GEN
Solar/Wind Harmer
4.742
270246TR4_N_V150
Solar/Wind Harmer
0.071
965681AG1-436 GEN
Solar/Wind Harmer
13.426
270535AF1-215 GEN1
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
14.396
25322209TAIT E
Adder
14.072
970291AG2-192 GEN
Solar/Wind Harmer
1.338
970291AG2-192 GEN
Solar/Wind Harmer
0.618
276776AD2-060 GEN
Solar/Wind Harmer
1.097
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
5.259
943851AF1-053 GEN
Solar/Wind Harmer
3.643
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.888
957201AF2-014 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.403
970179AG2-119 GEN
Solar/Wind Harmer
9.709
963791AG1-232 GEN
Solar/Wind Harmer
14.514
958391AF2-133 GEN
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
1.956
274827FISK ;RP
Adder
11.436
274800UNIV PARK;3U
Adder
8.587
274801UNIV PARK;4U
Adder
8.587
972227AH1-698 GEN1
Adder
3.84
274735ELWOOD EC;4P
Adder
24.024
274744AC1-111 GEN8
Adder
8.105
253372AE2-315 SEC3
Adder
2.747
253372AE2-315 SEC3
Adder
2.747
25306009OHH W.
Adder
4.15
970169AG2-114 GEN
Solar/Wind Harmer
9.859
959341AF2-225 GEN
Solar/Wind Harmer
10.156
276741O09 GEN1
Solar/Wind Harmer
0.34
274877BISHOP HL;1U
Solar/Wind Harmer
0.321
270475AD2-096_GEN
50/50
14.072
270518AE2-148 GEN
Solar/Wind Harmer
1.063
253325AC1-069 GEN
Solar/Wind Harmer
0.014
270491AE1-102 GEN2
Solar/Wind Harmer
1.468
971199AH1-059 GEN
Solar/Wind Harmer
2.255
964401AG1-302 GEN
Solar/Wind Harmer
0.002
270119AB2-067 GEN1
50/50
17.244
25326509SID D
Adder
2.143
246937BC-WTG2
Solar/Wind Harmer
0.455
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.96
942221AE2-234 GEN
Solar/Wind Harmer
4.232
957841AF2-078 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.914
274770LINCOLN ;1U
Adder
12.619
274771LINCOLN ;2U
Adder
12.619
274805UNIV PK N;1U
Adder
7.439
274888KELLY CRK;1U
Solar/Wind Harmer
0.6
970941AG2-585 GEN
Solar/Wind Harmer
5.654
276897AD1-100 C
Solar/Wind Harmer
25.624
276893AG1-478 C
Solar/Wind Harmer
0.68
24387305FR-4G C
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
16.391
274697ROCKY RD ;3P
Adder
4.35
962691AG1-118 GEN
Solar/Wind Harmer
29.945
970241AG2-163 GEN
Solar/Wind Harmer
5.694
938861AE1-114 GEN
Solar/Wind Harmer
5.51
274762LEE CO EC;3U
Adder
12.93
942111AE2-223 GEN
Solar/Wind Harmer
3.143
276645AC1-214 GEN1
Solar/Wind Harmer
0.379
276158O29GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
1.554
276838X2-022 GEN2
Solar/Wind Harmer
0.516
23751201ROTHROCK
Solar/Wind Helper
0.691
237043AE2-125 C
Solar/Wind Helper
0.16
270166AC1-044 GEN3
50/50
17.244
246936BC-WTG1
Solar/Wind Harmer
0.455
270489AE1-102 GEN1
Solar/Wind Harmer
1.468
965011AG1-365 GEN
Solar/Wind Harmer
11.206
957891AF2-083 GEN
Solar/Wind Harmer
17.821
945111AF1-176 GEN
Solar/Wind Harmer
19.076
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
13.152
274773LINCOLN ;4U
Adder
12.619
274774LINCOLN ;5U
Adder
12.619
958861AF2-177 GEN
Solar/Wind Harmer
4.506
274751CRETE EC ;1U
Adder
12.279
274723RIVER EC ;12
Adder
26.668
945371AF1-202 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
11.433
270032AE2-172
Solar/Wind Harmer
6.805
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
5.217
970825AG2-519 GEN
Solar/Wind Harmer
3.528
270005AE1-210 C O1
Solar/Wind Harmer
2.149
970569AG2-363 GEN
Solar/Wind Harmer
29.408
274858EASY ROAD;U2
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
12.93
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
939741AE1-205 GEN
Solar/Wind Harmer
13.541
253398AE2-221_GEN2
Solar/Wind Harmer
0.001
276621W2-048 GEN
Solar/Wind Harmer
0.459
25196008MFTGT1
Adder
1.662
25196808ZIMRHP
Adder
90.149
238126S14_GEN_1
Solar/Wind Helper
0.635
276668AB2-070 GEN1
Solar/Wind Harmer
0.365
276848AB2-070 GEN3
Solar/Wind Harmer
0.363
276849AB2-070 GEN2
Solar/Wind Harmer
0.365
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
24721905FLATG4
50/50
3.319
24722005FLATG5
50/50
3.319
962771AG1-126 GEN
Solar/Wind Harmer
73.48
970153AG2-106 GEN
Solar/Wind Harmer
46.922
270284AF1-227 GEN1
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.934
270588AE1-091_GEN
Solar/Wind Harmer
8.236
247642Z2-115 C
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
7.423
970289AG2-191 GEN
Solar/Wind Harmer
1.133
276806AD2-047 C O1
Solar/Wind Harmer
5.825
274676JOLIET 29;8U
Adder
43.287
274734ELWOOD EC;8P
Adder
24.024
274736ELWOOD EC;9P
Adder
24.024
943121AE2-341 GEN
Solar/Wind Harmer
16.972
943591AF1-030 GEN
Solar/Wind Harmer
11.286
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
274682WAUKEGAN ;7U
Adder
25.826
946031AF1-268 GEN
Solar/Wind Harmer
9.47
959091AF2-200 GEN
Solar/Wind Harmer
19.677
274767LEE CO EC;8U
Adder
12.777
971087AG2-675 GEN
Solar/Wind Harmer
5.012
24728505AND G1
Adder
5.071
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
11.737
957381AF2-032 GEN
Solar/Wind Harmer
2.038
25194608D.CRK4
Adder
2.025
23906502RICHG2&3
Adder
1.439
23906402RICHG1
Adder
1.437
964991AG1-363 GEN
Solar/Wind Helper
3.522
235058AG1-386 C
Solar/Wind Helper
0.4
24721605FLATG1
50/50
3.319
961821AG1-024 GEN
Solar/Wind Harmer
9.821
270578AF1-285 GEN2
Solar/Wind Harmer
0.932
945631AF1-228 GEN
Solar/Wind Harmer
-0.001
241972AD1-140 GEN
Solar/Wind Harmer
1.272
270432AC2-029 GEN
Solar/Wind Harmer
5.04
959331AF2-224 GEN
Solar/Wind Harmer
7.844
965041AG1-368 GEN
Solar/Wind Harmer
11.063
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
12.619
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274687WILL CNTY;4U
Adder
40.93
274687WILL CNTY;4U
Adder
40.93
274731ELWOOD EC;2P
Adder
24.024
274733ELWOOD EC;3P
Adder
24.024
971609AH1-304 GEN
Solar/Wind Harmer
1.657
274746AC1-111 G10
Adder
8.105
964611AG1-324 GEN
Solar/Wind Harmer
3.923
963841AG1-237 GEN
Solar/Wind Harmer
4.303
926823AC1-168 GEN
Solar/Wind Harmer
1.667
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
970149AG2-104 GEN
Solar/Wind Harmer
39.681
970373AG2-245 GEN
Solar/Wind Harmer
22.382
943021AE2-325 GEN
Solar/Wind Harmer
5.553
971917AH1-482 GEN
Solar/Wind Harmer
13.746
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.636
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
1.162
274872LEEDK;1U
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
9.838
971067AG2-660 GEN
Solar/Wind Harmer
3.279
274822ROCKFORD ;11
Adder
27.602
970819AG2-516 GEN
Solar/Wind Harmer
11.727
963741AG1-226 GEN
Solar/Wind Harmer
23.101
276655WTG1_EQ
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.379
970773AG2-487 GEN
Solar/Wind Harmer
1.647
970091AG2-072 GEN
Adder
20.654
962761AG1-125 GEN
Solar/Wind Harmer
73.48
270520AE2-214 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Harmer
-0.001
253333AC1-068 GEN
Solar/Wind Harmer
0.014
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274754CRETE EC ;4U
Adder
12.279
270273AD2-016 GEN
Solar/Wind Harmer
1.064
25326309TAIT D
Adder
1.618
274802UNIV PARK;5U
Adder
8.599
274674JOLIET 9 ;6U
Adder
22.504
274732ELWOOD EC;7P
Adder
24.024
241813AF1-122_GEN
Solar/Wind Harmer
4.544
971201AH1-060 GEN
Solar/Wind Harmer
2.029
24385905FR-11G C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
11.216
939401AE1-172 GEN
Solar/Wind Harmer
7.51
962781AG1-127 GEN
Solar/Wind Harmer
9.482
274766LEE CO EC;7U
Adder
12.777
270437AC2-090 C
Solar/Wind Harmer
0
276708O09 GEN2
Solar/Wind Harmer
0.34
270051AF1-062 GEN
50/50
23.559
246938BC-WTG3
Solar/Wind Harmer
0.406
965021AG1-366 GEN
Solar/Wind Harmer
3.735
270043AE2-236 GEN
Solar/Wind Harmer
7.125
270505AE1-170 C O1
Solar/Wind Harmer
11.228
945111AF1-176 GEN
Solar/Wind Harmer
8.665
274772LINCOLN ;3U
Adder
12.619
274724RIVER EC ;11
Adder
26.355
972259AH1-714 GEN
Adder
28.051
274729ELWOOD EC;1P
Adder
24.024
970065AG2-057 GEN
Solar/Wind Harmer
1.014
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
15.132
970825AG2-519 GEN
Solar/Wind Harmer
7.486
946671AF1-331 GEN
Solar/Wind Harmer
1.054
274850MENDOTA H;RU
Solar/Wind Harmer
0.115
970571AG2-364 GEN
Solar/Wind Harmer
19.606
270240V3-007_GEN2
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.285
25196008MFTGT1
Adder
1.61
237048AF1-022 C
Solar/Wind Helper
0.174
237046AF1-021 C
Solar/Wind Helper
0.304
942481AE2-261 GEN
Solar/Wind Harmer
16.491
270459AD2-067 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
1.43
270071AF1-092 GEN
Solar/Wind Harmer
21.261
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
10.756
24729505KEY G4
Adder
9.953
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
24.024
270120AB2-067 GEN2
50/50
17.244
270054AF2-122 C O1
Solar/Wind Harmer
0
270462AD2-086
Solar/Wind Harmer
0.002
938701AE1-092 GEN
Solar/Wind Harmer
21.46
270247TR4_N_V136
Solar/Wind Harmer
0.071
970349AG2-230 GEN
Solar/Wind Harmer
16.464
961051AF2-396 GEN
Solar/Wind Harmer
21.315
961051AF2-396 GEN
Solar/Wind Harmer
14.21
960971AF2-388 GEN
Solar/Wind Harmer
6.145
944231AF1-091 GEN
Solar/Wind Harmer
24.097
24697605MDL-3G C
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
7.391
274674JOLIET 9 ;6U
Adder
22.504
270599AE1-208 GEN
Solar/Wind Harmer
9.3
966841AG1-555 GEN
Solar/Wind Harmer
1.147
958481AF2-142 GEN
Solar/Wind Harmer
15.103
274693ROCKY RD ;1P
Adder
15.856
274683WAUKEGAN ;8U
Adder
30.253
274683WAUKEGAN ;8U
Adder
25.502
24725505WLD G2 C
Solar/Wind Harmer
0
970883AG2-550 GEN
Solar/Wind Harmer
9.92
276876AE1-163_GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
3.539
274764LEE CO EC;5U
Adder
12.96
926881AC1-175 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
3.19
945391AF1-204 GEN
Solar/Wind Harmer
9.764
276615X2-022 GEN
Solar/Wind Harmer
0.095
25194408D.CRK1
Adder
9.313
23585401KL_K28_T16
Solar/Wind Helper
1.178
238117U2-030
Solar/Wind Helper
0.267
961921AG1-034 GEN
Solar/Wind Harmer
14.732
270391AF1-285 GEN3
Solar/Wind Harmer
0.932
942051AE2-217 GEN
Solar/Wind Harmer
25.116
971347AH1-153 GEN
Solar/Wind Harmer
5.488
270063AE2-323 C
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
48.343
274752CRETE EC ;2U
Adder
12.279
970781AG2-491 GEN
Solar/Wind Harmer
10.354
274826FISK ;BP
Adder
16.137
274887GEN-1.85
Solar/Wind Harmer
0.267
970707AG2-453 GEN
Solar/Wind Harmer
33.528
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
24.024
274862TOP CROP ;2U
Solar/Wind Harmer
1.359
276868AE1-113 GEN
Solar/Wind Harmer
1.991
274879MINONK ;1U
Solar/Wind Harmer
0.415
274855GSG-6 ;RU
Solar/Wind Harmer
0.361
274857EASY ROAD;U1
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
3.19
970193AG2-126 GEN
Solar/Wind Harmer
13.784
270541AE2-072 C
Solar/Wind Harmer
0.001
25196608WSDLE5
Adder
10.619
238127S14_GEN_2
Solar/Wind Helper
0.635
202652Y1-033 WT C
Solar/Wind Helper
0.501
965051AG1-369 GEN
Solar/Wind Harmer
5.558
970031AG2-029 GEN
Solar/Wind Harmer
5.889
959141AF2-205 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
6.264
274775LINCOLN ;6U
Adder
12.619
274777LINCOLN ;8U
Adder
12.619
972037AH1-567 GEN1
Adder
0.27
960591AF2-350 GEN
Solar/Wind Harmer
10.28
972228AH1-698 GEN2
Adder
5.454
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
44.89
274675JOLIET 29;7U
Adder
43.287
970833AG2-524 GEN
Solar/Wind Harmer
11.198
970833AG2-524 GEN
Solar/Wind Harmer
7.465
270377AD1-106 GEN
Solar/Wind Harmer
3.864
24386405FR-21G C
Solar/Wind Harmer
0
247536S-71 GEN
Solar/Wind Harmer
0.4
971675AH1-338 GEN
Solar/Wind Harmer
3.854
971411AH1-196 GEN
Solar/Wind Harmer
14.823
971171AH1-044 GEN
Solar/Wind Harmer
19.677
971029AG2-637 GEN
Solar/Wind Harmer
14.756
274823ROCKFORD ;21
Adder
27.402
972267AH1-718 GEN
Adder
5.748
274853TWINGROVE;U1
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
5.283
253406AD2-031_GEN
Solar/Wind Harmer
0.684
23652301WDPWR_K20
Solar/Wind Helper
0.129
23750701CROSSCHOOL
Solar/Wind Helper
1.119
203955AF1-039 C O1
Solar/Wind Helper
0.331
942861AE2-305 GEN
Solar/Wind Harmer
10.655
970329AG2-216 GEN
Solar/Wind Harmer
5.083
247620Y3-023
Adder
0.71
965791AG1-447 GEN
Solar/Wind Harmer
9.845
25326109MON D
Adder
1.994
944541AF1-119 GEN
Solar/Wind Harmer
0.7
945421AF1-207 GEN
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
14.803
270031AE2-169
Solar/Wind Harmer
5.58
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.754
274695ROCKY RD ;2P
Adder
16.014
958491AF2-143 GEN
Solar/Wind Harmer
14.984
24699105WLD G1 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
3.307
276872AE1-163_GEN1
Solar/Wind Harmer
0
972236AH1-702 GEN2
Adder
3.077
270383AD1-128 GEN
Solar/Wind Harmer
0
274765LEE CO EC;6U
Adder
12.96
274763LEE CO EC;4U
Adder
12.808
25194508D.CRK3
Adder
1.741
972159AH1-661 GEN
Adder
1.225
235054AD2-180 GEN
Solar/Wind Helper
1.576
235531U2-073 GEN
Solar/Wind Helper
2.548
270340AC2-060 GEN
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
270263AC1-001 GEN
Solar/Wind Harmer
0.924
23750501ELLIOTTS
Solar/Wind Helper
0.6
238118U2-030_1
Solar/Wind Helper
0.267
24721705FLATG2
50/50
3.319
24721805FLATG3
50/50
3.319
970155AG2-107 GEN
Solar/Wind Harmer
46.922
971995AH1-542 GEN
Solar/Wind Harmer
4.575
965421AG1-410 GEN
Solar/Wind Harmer
33.842
24639705ELKHART HY
Adder
0.237
270449AD2-020 GEN
Solar/Wind Harmer
-0.001
270055AF2-134 C O1
Solar/Wind Harmer
0
965651AG1-433 GEN
Solar/Wind Harmer
3.072
270024AE2-089 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.423
274676JOLIET 29;8U
Adder
44.89
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
8.105
253370AE2-315 SEC1
Adder
2.904
253371AE2-315 SEC2
Adder
2.747
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
25.826
274828WAUKEGAN ;BP
Adder
15.858
957471AF2-041 GEN
Solar/Wind Harmer
29.515
970613AG2-401 GEN
Solar/Wind Harmer
7.109
274848CAMPGROVE;RU
Solar/Wind Harmer
0
24728605AND G2
Adder
5.071
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.029
25194608D.CRK4
Adder
2.025
23906502RICHG2&3
Adder
1.439
238185AF2-356 C
Solar/Wind Helper
2.037
23751101LEADS_P59
Solar/Wind Helper
1.839
238120AE2-309 GEN
Solar/Wind Helper
0.401
971613AH1-306 GEN
Solar/Wind Harmer
4.9
253370AE2-315 SEC1
Adder
2.904
247621Y3-024
Adder
0.348
276901AD2-066 C O1
Solar/Wind Harmer
-0.001
971341AH1-150 GEN
Solar/Wind Harmer
19.677
971343AH1-151 GEN
Solar/Wind Harmer
19.677
274753CRETE EC ;3U
Adder
12.279
24690905MDL-1G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
7.488
274807UNIV PK N;3U
Adder
7.472
274803UNIV PARK;6U
Adder
8.599
971549AH1-272 GEN
Solar/Wind Harmer
20.903
970073AG2-061 GEN
Solar/Wind Harmer
3.33
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
270543AE2-219 C
Solar/Wind Harmer
6.944
276861AD2-134 GEN
Solar/Wind Harmer
0.176
276863AD2-134 GEN
Solar/Wind Harmer
0.176
274856ECOGROVE ;U1
Solar/Wind Harmer
0.228
971681AH1-341 GEN
Solar/Wind Harmer
15.659
25196408WSDLE3
Adder
10.931
25196108MFTGT2
Adder
1.832
25196108MFTGT2
Adder
1.701
276843GEN-1.7
Solar/Wind Harmer
0.332
972038AH1-567 GEN2
Adder
0.538
24386205FR-12G C
Solar/Wind Harmer
0
970191AG2-125 GEN
Solar/Wind Harmer
2.597
270004AE1-209 GEN
Solar/Wind Harmer
2.149
274760LEE CO EC;1U
Adder
12.93
24379505HDWTR1G C
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.321
965091AG1-374 GEN
Solar/Wind Harmer
28.713
965931AG1-462 GEN
Solar/Wind Harmer
23.963
23562501BACKB
Solar/Wind Helper
0.847
965911AG1-460 GEN
Solar/Wind Harmer
1.103
CBM West 2LTFEXP_CBM-W2->PJM
CBM
124.415
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.5
MECLTFEXP_MEC->PJM
CLTF
20.741
SIGELTFEXP_SIGE->PJM
CLTF
0.579
NYPJM->LTFIMP_NY
CLTF
4.821
LGEELTFEXP_LGEE->PJM
CLTF
7.242
WECLTFEXP_WEC->PJM
CLTF
5.355
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.468
AG2-052LTFEXP_AG2-052->PJM
LTF
0.342
AH1-155LTFEXP_AH1-155->PJM
LTF
0.513
LAGNLTFEXP_LAGN->PJM
CLTF
14.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.305
TVALTFEXP_TVA->PJM
CLTF
6.29

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-030_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.26 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4152.93
MW Contribution:
16.17
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-030_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:96.51 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3997.33
MW Contribution:
13.96
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
12.841
241973AD2-163_GEN1
Solar/Wind Harmer
3.356
241974AD2-163_GEN2
Solar/Wind Harmer
3.356
270227U2-072_GEN3
Solar/Wind Harmer
3.264
270228U2-072_GEN4
Solar/Wind Harmer
3.264
270231U2-072_GEN5
Solar/Wind Harmer
3.264
943861AF1-054 GEN
Solar/Wind Harmer
6.343
943851AF1-053 GEN
Solar/Wind Harmer
3.065
270302AB2-170 GEN
Solar/Wind Harmer
13.397
253343AC1-166 GEN
Solar/Wind Harmer
1.652
957201AF2-014 GEN
Solar/Wind Harmer
6.318
247521TR3_G114
Solar/Wind Harmer
4.624
270120AB2-067 GEN2
50/50
15.769
270160DARBY CT5
50/50
0.838
270466AD2-091
50/50
9.303
270054AF2-122 C O1
Solar/Wind Harmer
6.002
270462AD2-086
Solar/Wind Harmer
11.128
938701AE1-092 GEN
Solar/Wind Harmer
32.666
270247TR4_N_V136
Solar/Wind Harmer
1.17
942801AE2-298 GEN
Solar/Wind Harmer
2.059
970349AG2-230 GEN
Solar/Wind Harmer
20.346
961051AF2-396 GEN
Solar/Wind Harmer
21.131
961051AF2-396 GEN
Solar/Wind Harmer
9.828
944231AF1-091 GEN
Solar/Wind Harmer
23.698
960971AF2-388 GEN
Solar/Wind Harmer
14.305
24697605MDL-3G C
Solar/Wind Harmer
4.776
270181AB1-006 GEN2
Solar/Wind Harmer
0.927
274808UNIV PK N;4U
Adder
6.442
253349AC2-067 GEN
Solar/Wind Harmer
2.612
274674JOLIET 9 ;6U
Adder
19.662
274693ROCKY RD ;1P
Adder
13.893
274683WAUKEGAN ;8U
Adder
26.517
274683WAUKEGAN ;8U
Adder
22.352
972235AH1-702 GEN1
Adder
3.115
274764LEE CO EC;5U
Adder
11.43
25194408D.CRK1
Adder
8.612
254305AE2-115 C
Solar/Wind Helper
0.219
241967AE2-285_GEN
Solar/Wind Helper
0.634
946071AF1-272 GEN
Solar/Wind Helper
2.473
23585401KL_K28_T16
Solar/Wind Helper
1.134
20083426SW_E13_K22
Solar/Wind Helper
0.05
270161DARBY CT6
50/50
0.827
946101AF1-275 GEN
Solar/Wind Harmer
2.774
942861AE2-305 GEN
Solar/Wind Harmer
12.851
247620Y3-023
Adder
0.617
965791AG1-447 GEN
Solar/Wind Harmer
8.532
25326109MON D
Adder
1.754
270269AC2-059
Solar/Wind Harmer
12.313
944541AF1-119 GEN
Solar/Wind Harmer
5.48
945421AF1-207 GEN
Solar/Wind Harmer
18.355
270180AB1-006 GEN1
Solar/Wind Harmer
9.319
24697905MDL-4G C
Solar/Wind Harmer
2.973
958011AF2-095 GEN
Solar/Wind Harmer
18.512
253400AC2-068 GEN
Solar/Wind Harmer
1.051
274695ROCKY RD ;2P
Adder
14.031
972236AH1-702 GEN2
Adder
2.709
274765LEE CO EC;6U
Adder
11.43
274763LEE CO EC;4U
Adder
11.296
25194508D.CRK3
Adder
1.61
254304AE2-114 C
Solar/Wind Helper
0.219
946381AF1-302 GEN
Solar/Wind Helper
0.204
270159DARBY CT4
50/50
0.841
961821AG1-024 GEN
Solar/Wind Harmer
16.692
945631AF1-228 GEN
Solar/Wind Harmer
7.764
270223U2-072_GEN1
Solar/Wind Harmer
3.264
270578AF1-285 GEN2
Solar/Wind Harmer
0.769
253338AC1-165 GEN
Solar/Wind Harmer
1.652
241972AD1-140 GEN
Solar/Wind Harmer
6.448
270432AC2-029 GEN
Solar/Wind Harmer
9.905
959331AF2-224 GEN
Solar/Wind Harmer
13.812
270191TR4_S_V150
Solar/Wind Harmer
4.126
965041AG1-368 GEN
Solar/Wind Harmer
13.691
270526AF1-158 GEN
Solar/Wind Harmer
6.052
960681AF2-359 GEN
Solar/Wind Harmer
5.041
274776LINCOLN ;7U
Adder
8.061
946581AF1-322 GEN
Solar/Wind Harmer
13.258
274687WILL CNTY;4U
Adder
35.747
274687WILL CNTY;4U
Adder
35.747
274731ELWOOD EC;2P
Adder
20.991
274733ELWOOD EC;3P
Adder
20.991
274746AC1-111 G10
Adder
7.091
241982AE2-343 S C
Solar/Wind Helper
0.222
23750501ELLIOTTS
Solar/Wind Helper
0.602
20089126CSLMN_L13
Solar/Wind Helper
0.536
20088926STNY CRK
Solar/Wind Helper
0.738
270475AD2-096_GEN
50/50
11.209
270518AE2-148 GEN
Solar/Wind Harmer
18.916
253325AC1-069 GEN
Solar/Wind Harmer
1.593
270491AE1-102 GEN2
Solar/Wind Harmer
1.811
24441505OLIV SLR
Solar/Wind Harmer
0.178
964401AG1-302 GEN
Solar/Wind Harmer
11.955
274753CRETE EC ;3U
Adder
6.344
24690905MDL-1G C
Solar/Wind Harmer
10.402
274814UNIV PK N;0U
Adder
6.527
274807UNIV PK N;3U
Adder
6.513
274803UNIV PARK;6U
Adder
7.502
270119AB2-067 GEN1
50/50
15.769
25326509SID D
50/50
1.962
253378AE2-206_GEN
Solar/Wind Harmer
5.191
246937BC-WTG2
Solar/Wind Harmer
5.449
247607V1-011 GEN
Solar/Wind Harmer
5.389
942221AE2-234 GEN
Solar/Wind Harmer
4.606
957841AF2-078 GEN
Solar/Wind Harmer
7.901
274770LINCOLN ;1U
Adder
8.061
274771LINCOLN ;2U
Adder
8.061
274805UNIV PK N;1U
Adder
6.485
274888KELLY CRK;1U
Solar/Wind Harmer
7.586
970941AG2-585 GEN
Solar/Wind Harmer
7.071
274696ROCKY RD ;4P
Adder
14.362
274697ROCKY RD ;3P
Adder
3.812
274762LEE CO EC;3U
Adder
11.403
962101AG1-054 GEN
Solar/Wind Helper
0.64
237043AE2-125 C
Solar/Wind Helper
0.169
23751201ROTHROCK
Solar/Wind Helper
0.663
270156DARBY CT1
50/50
0.855
270157DARBY CT2
50/50
0.853
270459AD2-067 GEN
Solar/Wind Harmer
16.44
270435AC2-044 GEN
Solar/Wind Harmer
2.786
270071AF1-092 GEN
Solar/Wind Harmer
20.508
270007AE1-245 C
Solar/Wind Harmer
7.361
971771AH1-392 GEN
Solar/Wind Harmer
12.042
24729505KEY G4
Adder
8.63
958711AF2-162 GEN
Solar/Wind Harmer
1.324
24691005MDL-2G C
Solar/Wind Harmer
4.791
971549AH1-272 GEN
Solar/Wind Harmer
23.856
274728ELWOOD EC;5P
Adder
20.991
25196408WSDLE3
Adder
10.092
25196108MFTGT2
Adder
1.705
25196108MFTGT2
Adder
1.583
241985AE1-237 GEN
Solar/Wind Helper
0.248
20089226LOOKOUT
Solar/Wind Helper
0.534
270051AF1-062 GEN
50/50
19.36
960801AF2-371 GEN
Solar/Wind Harmer
3.709
964871AG1-351 GEN
Solar/Wind Harmer
2.561
246938BC-WTG3
Solar/Wind Harmer
5.543
965021AG1-366 GEN
Solar/Wind Harmer
3.212
270043AE2-236 GEN
Solar/Wind Harmer
7.533
270505AE1-170 C O1
Solar/Wind Harmer
20.011
945111AF1-176 GEN
Solar/Wind Harmer
7.543
270044AE2-322 C
Solar/Wind Harmer
1.744
274772LINCOLN ;3U
Adder
8.061
274724RIVER EC ;11
Adder
22.955
965461AG1-414 GEN
Solar/Wind Harmer
2.929
972259AH1-714 GEN
Adder
24.478
274729ELWOOD EC;1P
Adder
20.991
25196008MFTGT1
Adder
1.498
237048AF1-022 C
Solar/Wind Helper
0.176
237046AF1-021 C
Solar/Wind Helper
0.314
270166AC1-044 GEN3
50/50
15.769
270485AE1-090_GEN
Solar/Wind Harmer
0.968
246936BC-WTG1
Solar/Wind Harmer
5.449
270489AE1-102 GEN1
Solar/Wind Harmer
1.811
965011AG1-365 GEN
Solar/Wind Harmer
13.812
945111AF1-176 GEN
Solar/Wind Harmer
23.801
957891AF2-083 GEN
Solar/Wind Harmer
20.009
24441205WTRV SLR C
Solar/Wind Harmer
0.178
964861AG1-349 GEN
Solar/Wind Harmer
10.357
940581AE2-045 GEN
Solar/Wind Harmer
13.384
971605AH1-302 GEN
Solar/Wind Harmer
11.444
958861AF2-177 GEN
Solar/Wind Harmer
14.228
274773LINCOLN ;4U
Adder
8.061
274774LINCOLN ;5U
Adder
8.061
274751CRETE EC ;1U
Adder
6.344
274723RIVER EC ;12
Adder
23.228
945371AF1-202 GEN
Solar/Wind Harmer
8.988
274761LEE CO EC;2U
Adder
11.403
25196008MFTGT1
Adder
1.547
25196808ZIMRHP
Adder
84.175
254303AC2-168 GEN
Solar/Wind Helper
0.157
961971AG1-040 GEN
Solar/Wind Helper
0.445
270594AE1-207 GEN
Solar/Wind Harmer
5.091
270032AE2-172
Solar/Wind Harmer
1.743
270349AD2-093_GEN
Solar/Wind Harmer
6.996
270471AD2-092_GEN
Solar/Wind Harmer
6.996
253383AE2-342_GEN
Solar/Wind Harmer
1.515
270246TR4_N_V150
Solar/Wind Harmer
1.17
965681AG1-436 GEN
Solar/Wind Harmer
16.676
270535AF1-215 GEN1
Solar/Wind Harmer
5.996
270536AF1-215 GEN2
Solar/Wind Harmer
5.996
25322209TAIT E
Adder
12.734
25322209TAIT E
Adder
12.447
24755605MDL-5G
Solar/Wind Harmer
3.124
970291AG2-192 GEN
Solar/Wind Harmer
1.679
970291AG2-192 GEN
Solar/Wind Harmer
0.541
253370AE2-315 SEC1
Adder
2.58
276776AD2-060 GEN
Solar/Wind Harmer
0.538
247621Y3-024
Adder
0.307
241801AE1-079 GEN
Solar/Wind Helper
0.248
203835AF1-098 GEN
Solar/Wind Helper
1.767
963791AG1-232 GEN
Solar/Wind Harmer
18.061
944161AF1-084 GEN
Solar/Wind Harmer
2.932
958391AF2-133 GEN
Solar/Wind Harmer
11.935
970289AG2-191 GEN
Solar/Wind Harmer
2.454
253372AE2-315 SEC3
Adder
2.44
253372AE2-315 SEC3
Adder
2.44
274827FISK ;RP
Adder
9.977
274800UNIV PARK;3U
Adder
7.493
274801UNIV PARK;4U
Adder
7.493
972227AH1-698 GEN1
Adder
3.351
25306009OHH W.
Adder
3.692
274735ELWOOD EC;4P
Adder
20.991
274744AC1-111 GEN8
Adder
7.091
241997AF1-093 GEN
Solar/Wind Helper
0.252
962771AG1-126 GEN
Solar/Wind Harmer
61.099
970153AG2-106 GEN
Solar/Wind Harmer
26.642
270284AF1-227 GEN1
Solar/Wind Harmer
10.292
276820AF1-078_GEN
Solar/Wind Harmer
2.306
24695305TIMB G C
Solar/Wind Harmer
4.562
247643Z2-116 C
Solar/Wind Harmer
0.093
270588AE1-091_GEN
Solar/Wind Harmer
14.355
960071AF2-298 GEN
Solar/Wind Harmer
1.969
247642Z2-115 C
Solar/Wind Harmer
0.083
972181SS23-001
Solar/Wind Harmer
7.699
276164X3-005 C
Solar/Wind Harmer
0.908
274811UNIV PK N;7U
Adder
6.471
970289AG2-191 GEN
Solar/Wind Harmer
0.991
253303V4-073 C
Solar/Wind Harmer
0.149
253370AE2-315 SEC1
Adder
2.58
253371AE2-315 SEC2
Adder
2.44
276806AD2-047 C O1
Solar/Wind Harmer
13.753
274676JOLIET 29;8U
Adder
37.812
274734ELWOOD EC;8P
Adder
20.991
274736ELWOOD EC;9P
Adder
20.991
274682WAUKEGAN ;7U
Adder
22.632
274767LEE CO EC;8U
Adder
11.269
24728505AND G1
Adder
4.559
23906502RICHG2&3
Adder
1.375
23906402RICHG1
Adder
1.374
25194608D.CRK4
Adder
1.872
235058AG1-386 C
Solar/Wind Helper
0.454
964991AG1-363 GEN
Solar/Wind Helper
3.324
970155AG2-107 GEN
Solar/Wind Harmer
26.642
971995AH1-542 GEN
Solar/Wind Harmer
16.172
965421AG1-410 GEN
Solar/Wind Harmer
41.76
24639705ELKHART HY
Adder
0.206
270449AD2-020 GEN
Solar/Wind Harmer
3.725
270055AF2-134 C O1
Solar/Wind Harmer
3.997
965651AG1-433 GEN
Solar/Wind Harmer
7.153
972207SS24-0001
Solar/Wind Harmer
28.659
270024AE2-089 GEN
Solar/Wind Harmer
6.086
274812UNIV PK N;8U
Adder
6.471
253370AE2-315 SEC1
Adder
2.58
253371AE2-315 SEC2
Adder
2.44
274676JOLIET 29;8U
Adder
39.213
274745AC1-111 GEN9
Adder
7.091
274682WAUKEGAN ;7U
Adder
22.632
274828WAUKEGAN ;BP
Adder
13.9
24728605AND G2
Adder
4.559
23906502RICHG2&3
Adder
1.375
25194608D.CRK4
Adder
1.872
241966AE1-183 GEN
Solar/Wind Helper
0.252
238185AF2-356 C
Solar/Wind Helper
1.95
203830AF1-094 GEN
Solar/Wind Helper
0.445
203979AG1-198 GEN
Solar/Wind Helper
0.267
270158DARBY CT3
50/50
0.839
270036AE2-216 BAT
50/50
10.234
270224U2-072_GEN2
Solar/Wind Harmer
3.264
965051AG1-369 GEN
Solar/Wind Harmer
6.87
970031AG2-029 GEN
Solar/Wind Harmer
33.755
270404AC1-167 GEN
Solar/Wind Harmer
1.437
959141AF2-205 GEN
Solar/Wind Harmer
7.947
274775LINCOLN ;6U
Adder
8.061
274777LINCOLN ;8U
Adder
8.061
945581AF1-223 GEN
Solar/Wind Harmer
5.843
972037AH1-567 GEN1
Adder
0.235
960591AF2-350 GEN
Solar/Wind Harmer
12.856
972228AH1-698 GEN2
Adder
4.758
274675JOLIET 29;7U
Adder
39.213
274675JOLIET 29;7U
Adder
37.813
274823ROCKFORD ;21
Adder
24.111
972267AH1-718 GEN
Adder
5.076
23652301WDPWR_K20
Solar/Wind Helper
0.135
203846AF2-130 C
Solar/Wind Helper
0.426
203955AF1-039 C O1
Solar/Wind Helper
0.334
961921AG1-034 GEN
Solar/Wind Harmer
25.037
270287AF1-227 GEN3
Solar/Wind Harmer
3.807
942051AE2-217 GEN
Solar/Wind Harmer
30.068
942871AE2-306 GEN
Solar/Wind Harmer
1.499
270391AF1-285 GEN3
Solar/Wind Harmer
0.769
958091AF2-103 GEN
Solar/Wind Harmer
0.22
971347AH1-153 GEN
Solar/Wind Harmer
6.782
270063AE2-323 C
Solar/Wind Harmer
2.966
944531AF1-118 GEN
Solar/Wind Harmer
46.834
972231SS25-0005
Solar/Wind Harmer
12.318
274752CRETE EC ;2U
Adder
6.344
970781AG2-491 GEN
Solar/Wind Harmer
12.958
274826FISK ;BP
Adder
14.078
274887GEN-1.85
Solar/Wind Harmer
6.849
276772AC2-154 GEN
Solar/Wind Harmer
3.588
274730ELWOOD EC;6P
Adder
20.991
25196608WSDLE5
Adder
9.804
202652Y1-033 WT C
Solar/Wind Helper
0.507
962761AG1-125 GEN
Solar/Wind Harmer
61.099
270520AE2-214 GEN
Solar/Wind Harmer
11.097
270391AF1-285 GEN3
Solar/Wind Harmer
1.999
270317AD1-130_GEN
Solar/Wind Harmer
5.121
253333AC1-068 GEN
Solar/Wind Harmer
1.593
270216AD2-079_GEN
Solar/Wind Harmer
0.811
270273AD2-016 GEN
Solar/Wind Harmer
3.511
958381AF2-132 GEN
Solar/Wind Harmer
11.955
25326309TAIT D
Adder
1.431
274754CRETE EC ;4U
Adder
6.344
274802UNIV PARK;5U
Adder
7.502
274732ELWOOD EC;7P
Adder
20.991
274674JOLIET 9 ;6U
Adder
19.662
274766LEE CO EC;7U
Adder
11.269
20089026BF_G21_K23
Solar/Wind Helper
0.424
203947AF1-006 C
Solar/Wind Helper
0.484
20084626FORWARD
Solar/Wind Helper
0.322
276843GEN-1.7
Solar/Wind Harmer
0.737
972038AH1-567 GEN2
Adder
0.469
274760LEE CO EC;1U
Adder
11.403
23562501BACKB
Solar/Wind Helper
0.81
962511AG1-100 GEN
Solar/Wind Helper
0.445
970149AG2-104 GEN
Solar/Wind Harmer
37.729
270286AF1-227 GEN2
Solar/Wind Harmer
3.807
270578AF1-285 GEN2
Solar/Wind Harmer
1.999
270258AD1-119 GEN
Solar/Wind Harmer
2.722
943021AE2-325 GEN
Solar/Wind Harmer
4.842
970373AG2-245 GEN
Solar/Wind Harmer
27.846
270297AD1-101 GEN
Solar/Wind Harmer
2.676
971917AH1-482 GEN
Solar/Wind Harmer
11.949
24791305MDL-5G
Solar/Wind Harmer
3.124
274822ROCKFORD ;11
Adder
24.287
23920202STRYCT
Adder
1.48
970091AG2-072 GEN
Adder
42.348
CPLELTFEXP_CPLE->PJM
CLTF
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.936
CBM West 1LTFEXP_CBM-W1->PJM
CBM
168.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.689
MECLTFEXP_MEC->PJM
CLTF
18.731
SIGELTFEXP_SIGE->PJM
CLTF
0.544
NYPJM->LTFIMP_NY
CLTF
4.743
LGEELTFEXP_LGEE->PJM
CLTF
6.936
WECLTFEXP_WEC->PJM
CLTF
4.716
AG2-052LTFEXP_AG2-052->PJM
LTF
0.299
AH1-155LTFEXP_AH1-155->PJM
LTF
0.449
LAGNLTFEXP_LAGN->PJM
CLTF
14.706
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.029
TVALTFEXP_TVA->PJM
CLTF
6.774

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o ATSI_P7-1_TE-345-031_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.15 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4148.28
MW Contribution:
16.18
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
ATSI_P7-1_TE-345-031_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:96.38 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:3992.14
MW Contribution:
13.96
Bus #Bus NameTypeMW Contribution
270120AB2-067 GEN2
50/50
15.77
270160DARBY CT5
50/50
0.838
270466AD2-091
50/50
9.305
270054AF2-122 C O1
Solar/Wind Harmer
6.003
270462AD2-086
Solar/Wind Harmer
11.13
938701AE1-092 GEN
Solar/Wind Harmer
32.673
270247TR4_N_V136
Solar/Wind Harmer
1.17
942801AE2-298 GEN
Solar/Wind Harmer
2.06
970349AG2-230 GEN
Solar/Wind Harmer
20.351
961051AF2-396 GEN
Solar/Wind Harmer
21.136
961051AF2-396 GEN
Solar/Wind Harmer
9.831
944231AF1-091 GEN
Solar/Wind Harmer
23.704
960971AF2-388 GEN
Solar/Wind Harmer
14.309
24697605MDL-3G C
Solar/Wind Harmer
4.778
270181AB1-006 GEN2
Solar/Wind Harmer
0.927
274808UNIV PK N;4U
Adder
6.444
253349AC2-067 GEN
Solar/Wind Harmer
2.613
274674JOLIET 9 ;6U
Adder
19.667
274693ROCKY RD ;1P
Adder
13.896
274683WAUKEGAN ;8U
Adder
26.524
274683WAUKEGAN ;8U
Adder
22.358
972235AH1-702 GEN1
Adder
3.116
274764LEE CO EC;5U
Adder
11.433
25194408D.CRK1
Adder
8.615
254305AE2-115 C
Solar/Wind Helper
0.219
241967AE2-285_GEN
Solar/Wind Helper
0.634
946071AF1-272 GEN
Solar/Wind Helper
2.472
23585401KL_K28_T16
Solar/Wind Helper
1.134
20083426SW_E13_K22
Solar/Wind Helper
0.05
270161DARBY CT6
50/50
0.827
946101AF1-275 GEN
Solar/Wind Harmer
2.775
942861AE2-305 GEN
Solar/Wind Harmer
12.854
247620Y3-023
Adder
0.617
965791AG1-447 GEN
Solar/Wind Harmer
8.534
25326109MON D
Adder
1.754
270269AC2-059
Solar/Wind Harmer
12.316
944541AF1-119 GEN
Solar/Wind Harmer
5.481
945421AF1-207 GEN
Solar/Wind Harmer
18.359
270180AB1-006 GEN1
Solar/Wind Harmer
9.321
24697905MDL-4G C
Solar/Wind Harmer
2.974
958011AF2-095 GEN
Solar/Wind Harmer
18.517
253400AC2-068 GEN
Solar/Wind Harmer
1.051
274695ROCKY RD ;2P
Adder
14.034
972236AH1-702 GEN2
Adder
2.709
274765LEE CO EC;6U
Adder
11.433
274763LEE CO EC;4U
Adder
11.299
25194508D.CRK3
Adder
1.611
254304AE2-114 C
Solar/Wind Helper
0.219
946381AF1-302 GEN
Solar/Wind Helper
0.204
270159DARBY CT4
50/50
0.841
961821AG1-024 GEN
Solar/Wind Harmer
16.694
945631AF1-228 GEN
Solar/Wind Harmer
7.765
270223U2-072_GEN1
Solar/Wind Harmer
3.264
270578AF1-285 GEN2
Solar/Wind Harmer
0.769
253338AC1-165 GEN
Solar/Wind Harmer
1.653
241972AD1-140 GEN
Solar/Wind Harmer
6.45
270432AC2-029 GEN
Solar/Wind Harmer
9.907
959331AF2-224 GEN
Solar/Wind Harmer
13.815
270191TR4_S_V150
Solar/Wind Harmer
4.127
965041AG1-368 GEN
Solar/Wind Harmer
13.694
270526AF1-158 GEN
Solar/Wind Harmer
6.053
960681AF2-359 GEN
Solar/Wind Harmer
5.042
274776LINCOLN ;7U
Adder
8.063
946581AF1-322 GEN
Solar/Wind Harmer
13.262
274687WILL CNTY;4U
Adder
35.756
274687WILL CNTY;4U
Adder
35.756
274731ELWOOD EC;2P
Adder
20.997
274733ELWOOD EC;3P
Adder
20.997
274746AC1-111 G10
Adder
7.092
241982AE2-343 S C
Solar/Wind Helper
0.222
23750501ELLIOTTS
Solar/Wind Helper
0.601
20089126CSLMN_L13
Solar/Wind Helper
0.536
20088926STNY CRK
Solar/Wind Helper
0.738
270119AB2-067 GEN1
50/50
15.77
25326509SID D
50/50
1.962
253378AE2-206_GEN
Solar/Wind Harmer
5.193
246937BC-WTG2
Solar/Wind Harmer
5.451
247607V1-011 GEN
Solar/Wind Harmer
5.39
942221AE2-234 GEN
Solar/Wind Harmer
4.607
957841AF2-078 GEN
Solar/Wind Harmer
7.903
274770LINCOLN ;1U
Adder
8.063
274771LINCOLN ;2U
Adder
8.063
274805UNIV PK N;1U
Adder
6.486
274888KELLY CRK;1U
Solar/Wind Harmer
7.588
970941AG2-585 GEN
Solar/Wind Harmer
7.072
274696ROCKY RD ;4P
Adder
14.366
274697ROCKY RD ;3P
Adder
3.812
274762LEE CO EC;3U
Adder
11.406
962101AG1-054 GEN
Solar/Wind Helper
0.64
237043AE2-125 C
Solar/Wind Helper
0.169
23751201ROTHROCK
Solar/Wind Helper
0.662
270156DARBY CT1
50/50
0.855
270157DARBY CT2
50/50
0.853
270459AD2-067 GEN
Solar/Wind Harmer
16.443
270435AC2-044 GEN
Solar/Wind Harmer
2.787
270071AF1-092 GEN
Solar/Wind Harmer
20.513
270007AE1-245 C
Solar/Wind Harmer
7.363
971771AH1-392 GEN
Solar/Wind Harmer
12.045
24729505KEY G4
Adder
8.632
958711AF2-162 GEN
Solar/Wind Harmer
1.324
24691005MDL-2G C
Solar/Wind Harmer
4.793
971549AH1-272 GEN
Solar/Wind Harmer
23.862
274728ELWOOD EC;5P
Adder
20.997
25196408WSDLE3
Adder
10.095
25196108MFTGT2
Adder
1.705
25196108MFTGT2
Adder
1.584
241985AE1-237 GEN
Solar/Wind Helper
0.247
20089226LOOKOUT
Solar/Wind Helper
0.534
270051AF1-062 GEN
50/50
19.363
960801AF2-371 GEN
Solar/Wind Harmer
3.709
964871AG1-351 GEN
Solar/Wind Harmer
2.561
246938BC-WTG3
Solar/Wind Harmer
5.545
965021AG1-366 GEN
Solar/Wind Harmer
3.213
270043AE2-236 GEN
Solar/Wind Harmer
7.535
270505AE1-170 C O1
Solar/Wind Harmer
20.016
945111AF1-176 GEN
Solar/Wind Harmer
7.545
270044AE2-322 C
Solar/Wind Harmer
1.744
274772LINCOLN ;3U
Adder
8.063
274724RIVER EC ;11
Adder
22.961
965461AG1-414 GEN
Solar/Wind Harmer
2.93
972259AH1-714 GEN
Adder
24.485
274729ELWOOD EC;1P
Adder
20.997
25196008MFTGT1
Adder
1.498
237048AF1-022 C
Solar/Wind Helper
0.176
237046AF1-021 C
Solar/Wind Helper
0.314
270166AC1-044 GEN3
50/50
15.77
270485AE1-090_GEN
Solar/Wind Harmer
0.968
246936BC-WTG1
Solar/Wind Harmer
5.451
270489AE1-102 GEN1
Solar/Wind Harmer
1.811
965011AG1-365 GEN
Solar/Wind Harmer
13.815
945111AF1-176 GEN
Solar/Wind Harmer
23.807
957891AF2-083 GEN
Solar/Wind Harmer
20.013
24441205WTRV SLR C
Solar/Wind Harmer
0.178
964861AG1-349 GEN
Solar/Wind Harmer
10.359
940581AE2-045 GEN
Solar/Wind Harmer
13.387
971605AH1-302 GEN
Solar/Wind Harmer
11.446
958861AF2-177 GEN
Solar/Wind Harmer
14.232
274773LINCOLN ;4U
Adder
8.063
274774LINCOLN ;5U
Adder
8.063
274751CRETE EC ;1U
Adder
6.346
274723RIVER EC ;12
Adder
23.234
945371AF1-202 GEN
Solar/Wind Harmer
8.99
274761LEE CO EC;2U
Adder
11.406
25196008MFTGT1
Adder
1.547
25196808ZIMRHP
Adder
84.199
254303AC2-168 GEN
Solar/Wind Helper
0.157
961971AG1-040 GEN
Solar/Wind Helper
0.445
270594AE1-207 GEN
Solar/Wind Harmer
5.092
270032AE2-172
Solar/Wind Harmer
1.744
270349AD2-093_GEN
Solar/Wind Harmer
6.997
270471AD2-092_GEN
Solar/Wind Harmer
6.997
253383AE2-342_GEN
Solar/Wind Harmer
1.515
270246TR4_N_V150
Solar/Wind Harmer
1.17
965681AG1-436 GEN
Solar/Wind Harmer
16.68
270535AF1-215 GEN1
Solar/Wind Harmer
5.998
270536AF1-215 GEN2
Solar/Wind Harmer
5.998
25322209TAIT E
Adder
12.737
25322209TAIT E
Adder
12.451
24755605MDL-5G
Solar/Wind Harmer
3.125
970291AG2-192 GEN
Solar/Wind Harmer
1.68
970291AG2-192 GEN
Solar/Wind Harmer
0.541
253370AE2-315 SEC1
Adder
2.581
276776AD2-060 GEN
Solar/Wind Harmer
0.538
247621Y3-024
Adder
0.307
241801AE1-079 GEN
Solar/Wind Helper
0.248
203835AF1-098 GEN
Solar/Wind Helper
1.766
241955AC1-078 GEN
Solar/Wind Harmer
12.844
241973AD2-163_GEN1
Solar/Wind Harmer
3.356
241974AD2-163_GEN2
Solar/Wind Harmer
3.356
270227U2-072_GEN3
Solar/Wind Harmer
3.264
270228U2-072_GEN4
Solar/Wind Harmer
3.264
270231U2-072_GEN5
Solar/Wind Harmer
3.264
943861AF1-054 GEN
Solar/Wind Harmer
6.345
943851AF1-053 GEN
Solar/Wind Harmer
3.066
270302AB2-170 GEN
Solar/Wind Harmer
13.399
253343AC1-166 GEN
Solar/Wind Harmer
1.653
957201AF2-014 GEN
Solar/Wind Harmer
6.32
247521TR3_G114
Solar/Wind Harmer
4.625
963791AG1-232 GEN
Solar/Wind Harmer
18.065
944161AF1-084 GEN
Solar/Wind Harmer
2.932
958391AF2-133 GEN
Solar/Wind Harmer
11.938
970289AG2-191 GEN
Solar/Wind Harmer
2.455
253372AE2-315 SEC3
Adder
2.441
253372AE2-315 SEC3
Adder
2.441
274827FISK ;RP
Adder
9.979
274800UNIV PARK;3U
Adder
7.495
274801UNIV PARK;4U
Adder
7.495
972227AH1-698 GEN1
Adder
3.351
25306009OHH W.
Adder
3.693
274735ELWOOD EC;4P
Adder
20.997
274744AC1-111 GEN8
Adder
7.092
241997AF1-093 GEN
Solar/Wind Helper
0.252
962771AG1-126 GEN
Solar/Wind Harmer
61.109
970153AG2-106 GEN
Solar/Wind Harmer
26.647
270284AF1-227 GEN1
Solar/Wind Harmer
10.294
276820AF1-078_GEN
Solar/Wind Harmer
2.307
24695305TIMB G C
Solar/Wind Harmer
4.564
247643Z2-116 C
Solar/Wind Harmer
0.093
270588AE1-091_GEN
Solar/Wind Harmer
14.359
960071AF2-298 GEN
Solar/Wind Harmer
1.969
247642Z2-115 C
Solar/Wind Harmer
0.083
972181SS23-001
Solar/Wind Harmer
7.701
276164X3-005 C
Solar/Wind Harmer
0.908
274811UNIV PK N;7U
Adder
6.472
970289AG2-191 GEN
Solar/Wind Harmer
0.992
253303V4-073 C
Solar/Wind Harmer
0.149
253370AE2-315 SEC1
Adder
2.581
253371AE2-315 SEC2
Adder
2.441
276806AD2-047 C O1
Solar/Wind Harmer
13.756
274676JOLIET 29;8U
Adder
37.822
274734ELWOOD EC;8P
Adder
20.997
274736ELWOOD EC;9P
Adder
20.997
274682WAUKEGAN ;7U
Adder
22.638
274767LEE CO EC;8U
Adder
11.272
24728505AND G1
Adder
4.56
23906502RICHG2&3
Adder
1.375
23906402RICHG1
Adder
1.375
25194608D.CRK4
Adder
1.873
235058AG1-386 C
Solar/Wind Helper
0.454
964991AG1-363 GEN
Solar/Wind Helper
3.323
970155AG2-107 GEN
Solar/Wind Harmer
26.647
971995AH1-542 GEN
Solar/Wind Harmer
16.176
965421AG1-410 GEN
Solar/Wind Harmer
41.769
24639705ELKHART HY
Adder
0.206
270449AD2-020 GEN
Solar/Wind Harmer
3.726
270055AF2-134 C O1
Solar/Wind Harmer
3.998
965651AG1-433 GEN
Solar/Wind Harmer
7.154
972207SS24-0001
Solar/Wind Harmer
28.666
270024AE2-089 GEN
Solar/Wind Harmer
6.087
274812UNIV PK N;8U
Adder
6.472
253370AE2-315 SEC1
Adder
2.581
253371AE2-315 SEC2
Adder
2.441
274676JOLIET 29;8U
Adder
39.223
274745AC1-111 GEN9
Adder
7.092
274682WAUKEGAN ;7U
Adder
22.638
274828WAUKEGAN ;BP
Adder
13.903
24728605AND G2
Adder
4.56
23906502RICHG2&3
Adder
1.375
25194608D.CRK4
Adder
1.873
241966AE1-183 GEN
Solar/Wind Helper
0.252
238185AF2-356 C
Solar/Wind Helper
1.949
203830AF1-094 GEN
Solar/Wind Helper
0.445
203979AG1-198 GEN
Solar/Wind Helper
0.267
270158DARBY CT3
50/50
0.839
270036AE2-216 BAT
50/50
10.236
270224U2-072_GEN2
Solar/Wind Harmer
3.264
965051AG1-369 GEN
Solar/Wind Harmer
6.871
970031AG2-029 GEN
Solar/Wind Harmer
33.763
270404AC1-167 GEN
Solar/Wind Harmer
1.438
959141AF2-205 GEN
Solar/Wind Harmer
7.949
274775LINCOLN ;6U
Adder
8.063
274777LINCOLN ;8U
Adder
8.063
945581AF1-223 GEN
Solar/Wind Harmer
5.844
972037AH1-567 GEN1
Adder
0.236
960591AF2-350 GEN
Solar/Wind Harmer
12.859
972228AH1-698 GEN2
Adder
4.76
274675JOLIET 29;7U
Adder
39.223
274675JOLIET 29;7U
Adder
37.822
274823ROCKFORD ;21
Adder
24.117
972267AH1-718 GEN
Adder
5.077
23652301WDPWR_K20
Solar/Wind Helper
0.134
203846AF2-130 C
Solar/Wind Helper
0.426
203955AF1-039 C O1
Solar/Wind Helper
0.334
961921AG1-034 GEN
Solar/Wind Harmer
25.042
270287AF1-227 GEN3
Solar/Wind Harmer
3.807
942051AE2-217 GEN
Solar/Wind Harmer
30.074
942871AE2-306 GEN
Solar/Wind Harmer
1.499
270391AF1-285 GEN3
Solar/Wind Harmer
0.769
958091AF2-103 GEN
Solar/Wind Harmer
0.22
971347AH1-153 GEN
Solar/Wind Harmer
6.784
270063AE2-323 C
Solar/Wind Harmer
2.967
944531AF1-118 GEN
Solar/Wind Harmer
46.845
972231SS25-0005
Solar/Wind Harmer
12.321
274752CRETE EC ;2U
Adder
6.346
970781AG2-491 GEN
Solar/Wind Harmer
12.961
274826FISK ;BP
Adder
14.081
274887GEN-1.85
Solar/Wind Harmer
6.851
276772AC2-154 GEN
Solar/Wind Harmer
3.589
274730ELWOOD EC;6P
Adder
20.997
25196608WSDLE5
Adder
9.806
202652Y1-033 WT C
Solar/Wind Helper
0.506
962761AG1-125 GEN
Solar/Wind Harmer
61.109
270520AE2-214 GEN
Solar/Wind Harmer
11.099
270391AF1-285 GEN3
Solar/Wind Harmer
1.999
270317AD1-130_GEN
Solar/Wind Harmer
5.122
253333AC1-068 GEN
Solar/Wind Harmer
1.594
270216AD2-079_GEN
Solar/Wind Harmer
0.811
270273AD2-016 GEN
Solar/Wind Harmer
3.512
958381AF2-132 GEN
Solar/Wind Harmer
11.958
25326309TAIT D
Adder
1.432
274754CRETE EC ;4U
Adder
6.346
274802UNIV PARK;5U
Adder
7.503
274732ELWOOD EC;7P
Adder
20.997
274674JOLIET 9 ;6U
Adder
19.667
274766LEE CO EC;7U
Adder
11.272
20089026BF_G21_K23
Solar/Wind Helper
0.424
203947AF1-006 C
Solar/Wind Helper
0.484
20084626FORWARD
Solar/Wind Helper
0.322
270475AD2-096_GEN
50/50
11.21
270518AE2-148 GEN
Solar/Wind Harmer
18.92
253325AC1-069 GEN
Solar/Wind Harmer
1.594
270491AE1-102 GEN2
Solar/Wind Harmer
1.811
24441505OLIV SLR
Solar/Wind Harmer
0.178
964401AG1-302 GEN
Solar/Wind Harmer
11.958
274753CRETE EC ;3U
Adder
6.346
24690905MDL-1G C
Solar/Wind Harmer
10.405
274814UNIV PK N;0U
Adder
6.529
274807UNIV PK N;3U
Adder
6.515
274803UNIV PARK;6U
Adder
7.503
276843GEN-1.7
Solar/Wind Harmer
0.737
972038AH1-567 GEN2
Adder
0.469
274760LEE CO EC;1U
Adder
11.406
23562501BACKB
Solar/Wind Helper
0.809
962511AG1-100 GEN
Solar/Wind Helper
0.444
970149AG2-104 GEN
Solar/Wind Harmer
37.735
270286AF1-227 GEN2
Solar/Wind Harmer
3.807
270578AF1-285 GEN2
Solar/Wind Harmer
1.999
270258AD1-119 GEN
Solar/Wind Harmer
2.723
943021AE2-325 GEN
Solar/Wind Harmer
4.844
970373AG2-245 GEN
Solar/Wind Harmer
27.853
971917AH1-482 GEN
Solar/Wind Harmer
11.952
270297AD1-101 GEN
Solar/Wind Harmer
2.676
24791305MDL-5G
Solar/Wind Harmer
3.125
274822ROCKFORD ;11
Adder
24.293
23920202STRYCT
Adder
1.481
970091AG2-072 GEN
Adder
42.361
CPLELTFEXP_CPLE->PJM
CLTF
0.32
CBM West 2LTFEXP_CBM-W2->PJM
CBM
119.979
CBM West 1LTFEXP_CBM-W1->PJM
CBM
168.737
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.702
MECLTFEXP_MEC->PJM
CLTF
18.736
SIGELTFEXP_SIGE->PJM
CLTF
0.544
NYPJM->LTFIMP_NY
CLTF
4.741
LGEELTFEXP_LGEE->PJM
CLTF
6.938
WECLTFEXP_WEC->PJM
CLTF
4.717
AG2-052LTFEXP_AG2-052->PJM
LTF
0.299
AH1-155LTFEXP_AH1-155->PJM
LTF
0.449
LAGNLTFEXP_LAGN->PJM
CLTF
14.713
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.039
TVALTFEXP_TVA->PJM
CLTF
6.778
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AEP_P4_#706_05GAVIN 765_C1_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-030_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P7-1_TE-345-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
290623 to 242925 ckt Z1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC123.53 %3792.0B4684.3
10.36
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC123.51 %3792.0B4683.54
10.36
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC123.51 %3792.0B4683.44
10.41
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC122.65 %3792.0B4650.99
2.41
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC122.64 %3792.0B4650.57
2.41
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC139.19 %3792.0B5278.17
10.1
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC139.17 %3792.0B5277.43
10.1
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC138.98 %3792.0B5270.18
10.21
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC138.45 %3792.0B5250.02
2.35
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC138.41 %3792.0B5248.4
2.35
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.25 %3729.0B5006.21
12.46
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.4 %3729.0B4974.31
12.45
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC133.01 %3729.0B4959.97
12.46
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC133.01 %3729.0B4959.97
12.46
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.87 %3729.0B4917.49
2.89
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.69 %3729.0B4873.53
12.94
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.24 %3729.0B4632.89
2.8
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC116.82 %1409.0B1646.06
11.8
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC110.97 %1409.0B1563.59
11.77
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC110.88 %1409.0B1562.23
11.76
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC105.36 %1409.0B1484.58
11.71
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC105.35 %1409.0B1484.33
11.71
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC135.56 %3792.0B5140.38
12.46
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC134.72 %3792.0B5108.61
12.45
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC134.34 %3792.0B5094.21
12.46
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC134.34 %3792.0B5094.21
12.46
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC133.22 %3792.0B5051.83
2.89
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC132.01 %3792.0B5005.84
12.94
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.57 %3792.0B4761.71
2.8

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.53 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4684.3
MW Contribution:
10.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23684101S70BUS1
50/50
0.295
970879AG2-548 GEN
Solar/Wind Harmer
1.187
962581AG1-107 GEN
Solar/Wind Harmer
4.922
961491AF2-440 GEN
Solar/Wind Harmer
2.045
253378AE2-206_GEN
Solar/Wind Harmer
3.461
25326509SID D
Adder
1.261
942221AE2-234 GEN
Solar/Wind Harmer
3.273
246937BC-WTG2
Solar/Wind Harmer
3.612
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
274805UNIV PK N;1U
Adder
4.563
274696ROCKY RD ;4P
Adder
10.261
274697ROCKY RD ;3P
Adder
2.723
23751201ROTHROCK
Solar/Wind Helper
0.855
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
316411AF1-147_GEN1
Solar/Wind Helper
0.762
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
3.759
270471AD2-092_GEN
Solar/Wind Harmer
3.759
253383AE2-342_GEN
Solar/Wind Harmer
0.888
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
247621Y3-024
Adder
0.226
970291AG2-192 GEN
Solar/Wind Harmer
1.215
970291AG2-192 GEN
Solar/Wind Harmer
0.391
270246TR4_N_V150
Solar/Wind Harmer
0.788
316097T157 G90
Solar/Wind Helper
1.331
238147AE2-230_GEN1
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.297
23684201S70BUS2
50/50
0.3
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
4.42
252510AF1-249 C
Solar/Wind Harmer
0.402
25196808ZIMRHP
Adder
72.791
270485AE1-090_GEN
Solar/Wind Harmer
0.58
25196008MFTGT1
Adder
1.323
942081AE2-220 GEN
Solar/Wind Harmer
6.014
270209AC1-174_GEN
Solar/Wind Harmer
3.827
270239V3-007_GEN1
Solar/Wind Harmer
1.618
958861AF2-177 GEN
Solar/Wind Harmer
10.268
945371AF1-202 GEN
Solar/Wind Harmer
6.551
270005AE1-210 C O1
Solar/Wind Harmer
5.125
970825AG2-519 GEN
Solar/Wind Harmer
1.966
270594AE1-207 GEN
Solar/Wind Harmer
12.702
270032AE2-172
Solar/Wind Harmer
4.35
965011AG1-365 GEN
Solar/Wind Harmer
9.303
246936BC-WTG1
Solar/Wind Harmer
3.612
927014AC1-188 GEN
Solar/Wind Harmer
1.627
946101AF1-275 GEN
Solar/Wind Harmer
1.548
971073AG2-665 GEN
Solar/Wind Harmer
8.168
270269AC2-059
Solar/Wind Harmer
9.486
942861AE2-305 GEN
Solar/Wind Harmer
7.811
25326109MON D
Adder
1.28
25183208HLCRTG
Solar/Wind Harmer
5.858
972159AH1-661 GEN
Adder
0.966
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
35.963
970153AG2-106 GEN
Solar/Wind Harmer
15.681
270284AF1-227 GEN1
Solar/Wind Harmer
5.709
253317AC1-085 GEN4
Solar/Wind Harmer
8.153
946181AF1-283 GEN
Solar/Wind Harmer
12.659
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
960071AF2-298 GEN
Solar/Wind Harmer
1.467
252519AF1-045_GEN
Solar/Wind Harmer
3.517
276820AF1-078_GEN
Solar/Wind Harmer
1.537
252524AE2-267 GEN
Solar/Wind Harmer
1.516
25194608D.CRK4
Adder
1.582
946031AF1-268 GEN
Solar/Wind Harmer
7.782
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.06
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
3.079
274811UNIV PK N;7U
Adder
4.553
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
274682WAUKEGAN ;7U
Adder
16.174
964991AG1-363 GEN
Solar/Wind Helper
4.289
238110AE1-109 GEN3
Solar/Wind Helper
0.103
235063AE1-101 C2
Solar/Wind Helper
1.447
962761AG1-125 GEN
Solar/Wind Harmer
35.963
270520AE2-214 GEN
Solar/Wind Harmer
6.192
270273AD2-016 GEN
Solar/Wind Harmer
2.704
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
1.046
270391AF1-285 GEN3
Solar/Wind Harmer
1.175
25326309TAIT D
Adder
1.064
270317AD1-130_GEN
Solar/Wind Harmer
3.069
944031AF1-071 GEN
Solar/Wind Harmer
0.956
270437AC2-090 C
Solar/Wind Harmer
5.249
276903AD2-071 C
Solar/Wind Harmer
9.334
274754CRETE EC ;4U
Adder
7.503
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274674JOLIET 9 ;6U
Adder
13.943
235067AD1-061 GEN
Solar/Wind Helper
0.388
237002AB1-128_GEN
Solar/Wind Helper
0.386
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
957541AF2-048 GEN
Solar/Wind Harmer
1.627
961921AG1-034 GEN
Solar/Wind Harmer
13.042
270287AF1-227 GEN3
Solar/Wind Harmer
2.112
942051AE2-217 GEN
Solar/Wind Harmer
18.072
942871AE2-306 GEN
Solar/Wind Harmer
0.881
270459AD2-067 GEN
Solar/Wind Harmer
8.564
940611AE2-048 GEN
Solar/Wind Harmer
22.264
941391AE2-136 GEN
Solar/Wind Harmer
11.537
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
270543AE2-219 C
Solar/Wind Harmer
9.417
24729505KEY G4
Adder
6.101
958711AF2-162 GEN
Solar/Wind Harmer
0.951
270071AF1-092 GEN
Solar/Wind Harmer
14.041
270435AC2-044 GEN
Solar/Wind Harmer
1.847
274728ELWOOD EC;5P
Adder
14.887
270512AE1-227 GEN2
Solar/Wind Harmer
2.215
971191AH1-055 GEN
Solar/Wind Harmer
19.337
970879AG2-548 GEN
Solar/Wind Harmer
8.168
960801AF2-371 GEN
Solar/Wind Harmer
2.586
964871AG1-351 GEN
Solar/Wind Harmer
1.786
270367AC2-061_GEN
Solar/Wind Harmer
3.102
253394AE2-221_GEN
Solar/Wind Harmer
4.42
270186AC1-089 GEN
Solar/Wind Harmer
5.927
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
7.557
270240V3-007_GEN2
Solar/Wind Harmer
5.818
962031AG1-047 GEN
Solar/Wind Harmer
2.835
957741AF2-068 GEN
Solar/Wind Harmer
14.065
970825AG2-519 GEN
Solar/Wind Harmer
5.279
965461AG1-414 GEN
Solar/Wind Harmer
2.119
270043AE2-236 GEN
Solar/Wind Harmer
5.125
965021AG1-366 GEN
Solar/Wind Harmer
2.164
246938BC-WTG3
Solar/Wind Harmer
3.674
274772LINCOLN ;3U
Adder
7.689
274724RIVER EC ;11
Adder
16.119
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
237048AF1-022 C
Solar/Wind Helper
0.176
238175AF1-290_GEN
Solar/Wind Helper
0.135
316415AF1-147_GEN2
Solar/Wind Helper
0.762
241955AC1-078 GEN
Solar/Wind Harmer
7.548
241973AD2-163_GEN1
Solar/Wind Harmer
1.986
241974AD2-163_GEN2
Solar/Wind Harmer
1.986
253343AC1-166 GEN
Solar/Wind Harmer
1.085
943861AF1-054 GEN
Solar/Wind Harmer
3.855
943851AF1-053 GEN
Solar/Wind Harmer
1.863
253433AC1-085 GEN1
Solar/Wind Harmer
5.175
253432AC1-085 GEN2
Solar/Wind Harmer
0.26
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270227U2-072_GEN3
Solar/Wind Harmer
1.918
270228U2-072_GEN4
Solar/Wind Harmer
1.918
270231U2-072_GEN5
Solar/Wind Harmer
1.918
25306009OHH W.
Adder
2.794
270302AB2-170 GEN
Solar/Wind Harmer
8.028
970289AG2-191 GEN
Solar/Wind Harmer
1.776
963791AG1-232 GEN
Solar/Wind Harmer
12.58
247521TR3_G114
Solar/Wind Harmer
3.113
957201AF2-014 GEN
Solar/Wind Harmer
4.187
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
274735ELWOOD EC;4P
Adder
14.887
274744AC1-111 GEN8
Adder
5.047
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
970155AG2-107 GEN
Solar/Wind Harmer
15.681
972203AH1-686 GEN
Adder
2.339
24723205RIVRG3
Adder
18.772
253316AC1-085 GEN3
Solar/Wind Harmer
8.153
946171AF1-282 GEN
Solar/Wind Harmer
9.738
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252516AE2-318_GEN
Solar/Wind Harmer
9.663
25194608D.CRK4
Adder
1.582
945681AF1-233 GEN
Solar/Wind Harmer
17.8
971995AH1-542 GEN
Solar/Wind Harmer
10.357
965651AG1-433 GEN
Solar/Wind Harmer
5.136
270024AE2-089 GEN
Solar/Wind Harmer
4.385
965421AG1-410 GEN
Solar/Wind Harmer
27.72
24728605AND G2
Adder
3.541
24639705ELKHART HY
Adder
0.141
274812UNIV PK N;8U
Adder
4.553
274676JOLIET 29;8U
Adder
27.787
274745AC1-111 GEN9
Adder
5.047
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
23777801MSM_W1-116
Solar/Wind Helper
0.1
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
252507AC2-088 GEN
Solar/Wind Harmer
1.731
25196608WSDLE5
Adder
8.25
958171AF2-111 GEN
Solar/Wind Harmer
23.611
944531AF1-118 GEN
Solar/Wind Harmer
32.926
971347AH1-153 GEN
Solar/Wind Harmer
4.626
24728705AND G3
Adder
7.406
274752CRETE EC ;2U
Adder
7.503
274826FISK ;BP
Adder
9.937
274730ELWOOD EC;6P
Adder
14.887
238127S14_GEN_2
Solar/Wind Helper
0.769
238152AF2-075_GEN
Solar/Wind Helper
0.617
23777901MDS_W4-102
Solar/Wind Helper
0.153
270054AF2-122 C O1
Solar/Wind Harmer
3.36
253415AE1-040 GEN
Solar/Wind Harmer
1.12
938701AE1-092 GEN
Solar/Wind Harmer
20.019
253349AC2-067 GEN
Solar/Wind Harmer
1.965
25194408D.CRK1
Adder
7.279
270462AD2-086
Solar/Wind Harmer
6.668
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
9.417
926881AC1-175 GEN
Solar/Wind Harmer
5.249
960971AF2-388 GEN
Solar/Wind Harmer
10.271
270599AE1-208 GEN
Solar/Wind Harmer
7.629
24725505WLD G2 C
Solar/Wind Harmer
3.711
270247TR4_N_V136
Solar/Wind Harmer
0.788
970349AG2-230 GEN
Solar/Wind Harmer
13.877
274808UNIV PK N;4U
Adder
4.533
274674JOLIET 9 ;6U
Adder
13.943
274693ROCKY RD ;1P
Adder
9.926
23585401KL_K28_T16
Solar/Wind Helper
1.451
238117U2-030
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.432
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
270489AE1-102 GEN1
Solar/Wind Harmer
1.2
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
23583801GRNGAP
Solar/Wind Helper
4.978
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.438
270291AC1-194 GEN
Solar/Wind Harmer
5.184
971985AH1-537 GEN
Solar/Wind Harmer
17.842
253406AD2-031_GEN
Solar/Wind Harmer
1.251
270224U2-072_GEN2
Solar/Wind Harmer
1.918
971029AG2-637 GEN
Solar/Wind Harmer
14.154
972165AH1-665 GEN
Solar/Wind Harmer
7.543
247536S-71 GEN
Solar/Wind Harmer
3.803
945581AF1-223 GEN
Solar/Wind Harmer
4.258
961761AG1-017 GEN
Solar/Wind Harmer
0.401
965051AG1-369 GEN
Solar/Wind Harmer
4.624
274775LINCOLN ;6U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
972228AH1-698 GEN2
Adder
3.362
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
23750701CROSSCHOOL
Solar/Wind Helper
1.372
961821AG1-024 GEN
Solar/Wind Harmer
8.695
270432AC2-029 GEN
Solar/Wind Harmer
7.128
270263AC1-001 GEN
Solar/Wind Harmer
1.061
945631AF1-228 GEN
Solar/Wind Harmer
4.727
253338AC1-165 GEN
Solar/Wind Harmer
1.085
270340AC2-060 GEN
Solar/Wind Harmer
3.013
241972AD1-140 GEN
Solar/Wind Harmer
4.405
270223U2-072_GEN1
Solar/Wind Harmer
1.918
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25196508WSDLE4
Adder
8.165
972163AH1-664 GEN
Solar/Wind Harmer
9.428
964611AG1-324 GEN
Solar/Wind Harmer
3.657
270356AE2-297 GEN
Solar/Wind Harmer
4.321
959331AF2-224 GEN
Solar/Wind Harmer
9.303
270191TR4_S_V150
Solar/Wind Harmer
2.777
965041AG1-368 GEN
Solar/Wind Harmer
9.252
274776LINCOLN ;7U
Adder
7.689
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274746AC1-111 G10
Adder
5.047
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
23779801AA1-109
Solar/Wind Helper
0.168
3138216PACIFIC
Solar/Wind Helper
0.038
252509AD1-136 GEN
Solar/Wind Harmer
0.247
253400AC2-068 GEN
Solar/Wind Harmer
0.79
25194508D.CRK3
Adder
1.361
24728805RICHG1
Adder
3.564
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
5.743
944541AF1-119 GEN
Solar/Wind Harmer
3.934
270201AC2-176 GEN
Solar/Wind Harmer
4.819
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
7.629
24699105WLD G1 C
Solar/Wind Harmer
3.668
247620Y3-023
Adder
0.422
274695ROCKY RD ;2P
Adder
10.024
235054AD2-180 GEN
Solar/Wind Helper
1.948
235531U2-073 GEN
Solar/Wind Helper
3.079
238149AF1-291A_GEN
Solar/Wind Helper
0.123
945421AF1-207 GEN
Solar/Wind Harmer
9.897
24318805MLG1
50/50
6.603
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
1.046
270518AE2-148 GEN
Solar/Wind Harmer
12.072
24379505HDWTR1G C
Solar/Wind Harmer
7.436
270004AE1-209 GEN
Solar/Wind Harmer
5.125
270491AE1-102 GEN2
Solar/Wind Harmer
1.2
274753CRETE EC ;3U
Adder
7.503
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274803UNIV PARK;6U
Adder
5.293
972038AH1-567 GEN2
Adder
0.331
23562501BACKB
Solar/Wind Helper
1.049
238108AE1-109 GEN1
Solar/Wind Helper
0.103
237001AB1-127_GEN
Solar/Wind Helper
0.384
23559101PLEAS2
50/50
11.898
23562301OGROV1
50/50
2.293
970149AG2-104 GEN
Solar/Wind Harmer
22.207
960001AF2-291 GEN
Solar/Wind Harmer
3.191
270510AE1-227 GEN1
Solar/Wind Harmer
2.61
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270286AF1-227 GEN2
Solar/Wind Harmer
2.112
270578AF1-285 GEN2
Solar/Wind Harmer
1.175
270222AC2-111 GEN
Solar/Wind Harmer
4.248
970091AG2-072 GEN
Adder
71.643
23546401DTGZ2-030
Solar/Wind Helper
0.078
237038AE2-054 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4683.54
MW Contribution:
10.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23684101S70BUS1
50/50
0.295
970879AG2-548 GEN
Solar/Wind Harmer
1.187
962581AG1-107 GEN
Solar/Wind Harmer
4.922
961491AF2-440 GEN
Solar/Wind Harmer
2.045
253378AE2-206_GEN
Solar/Wind Harmer
3.461
25326509SID D
Adder
1.261
942221AE2-234 GEN
Solar/Wind Harmer
3.273
246937BC-WTG2
Solar/Wind Harmer
3.612
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
274805UNIV PK N;1U
Adder
4.563
274696ROCKY RD ;4P
Adder
10.261
274697ROCKY RD ;3P
Adder
2.723
23751201ROTHROCK
Solar/Wind Helper
0.855
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
316411AF1-147_GEN1
Solar/Wind Helper
0.762
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
3.759
270471AD2-092_GEN
Solar/Wind Harmer
3.759
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
35.963
970153AG2-106 GEN
Solar/Wind Harmer
15.681
270284AF1-227 GEN1
Solar/Wind Harmer
5.709
253317AC1-085 GEN4
Solar/Wind Harmer
8.153
946181AF1-283 GEN
Solar/Wind Harmer
12.659
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
960071AF2-298 GEN
Solar/Wind Harmer
1.467
252519AF1-045_GEN
Solar/Wind Harmer
3.517
276820AF1-078_GEN
Solar/Wind Harmer
1.537
252524AE2-267 GEN
Solar/Wind Harmer
1.516
25194608D.CRK4
Adder
1.582
946031AF1-268 GEN
Solar/Wind Harmer
7.782
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.06
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
3.079
274811UNIV PK N;7U
Adder
4.553
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
274682WAUKEGAN ;7U
Adder
16.174
964991AG1-363 GEN
Solar/Wind Helper
4.289
238110AE1-109 GEN3
Solar/Wind Helper
0.103
235063AE1-101 C2
Solar/Wind Helper
1.447
962761AG1-125 GEN
Solar/Wind Harmer
35.963
270459AD2-067 GEN
Solar/Wind Harmer
8.564
940611AE2-048 GEN
Solar/Wind Harmer
22.264
941391AE2-136 GEN
Solar/Wind Harmer
11.537
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
270543AE2-219 C
Solar/Wind Harmer
9.417
24729505KEY G4
Adder
6.101
958711AF2-162 GEN
Solar/Wind Harmer
0.951
270071AF1-092 GEN
Solar/Wind Harmer
14.041
270435AC2-044 GEN
Solar/Wind Harmer
1.847
274728ELWOOD EC;5P
Adder
14.887
270512AE1-227 GEN2
Solar/Wind Harmer
2.215
971191AH1-055 GEN
Solar/Wind Harmer
19.337
970879AG2-548 GEN
Solar/Wind Harmer
8.168
960801AF2-371 GEN
Solar/Wind Harmer
2.586
964871AG1-351 GEN
Solar/Wind Harmer
1.786
270367AC2-061_GEN
Solar/Wind Harmer
3.102
253394AE2-221_GEN
Solar/Wind Harmer
4.42
270186AC1-089 GEN
Solar/Wind Harmer
5.927
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
7.557
270240V3-007_GEN2
Solar/Wind Harmer
5.818
962031AG1-047 GEN
Solar/Wind Harmer
2.835
957741AF2-068 GEN
Solar/Wind Harmer
14.065
970825AG2-519 GEN
Solar/Wind Harmer
5.279
965461AG1-414 GEN
Solar/Wind Harmer
2.119
270043AE2-236 GEN
Solar/Wind Harmer
5.125
965021AG1-366 GEN
Solar/Wind Harmer
2.164
246938BC-WTG3
Solar/Wind Harmer
3.674
274772LINCOLN ;3U
Adder
7.689
274724RIVER EC ;11
Adder
16.119
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
237048AF1-022 C
Solar/Wind Helper
0.176
238175AF1-290_GEN
Solar/Wind Helper
0.135
316415AF1-147_GEN2
Solar/Wind Helper
0.762
241955AC1-078 GEN
Solar/Wind Harmer
7.548
241973AD2-163_GEN1
Solar/Wind Harmer
1.986
241974AD2-163_GEN2
Solar/Wind Harmer
1.986
253343AC1-166 GEN
Solar/Wind Harmer
1.085
943861AF1-054 GEN
Solar/Wind Harmer
3.855
943851AF1-053 GEN
Solar/Wind Harmer
1.863
253433AC1-085 GEN1
Solar/Wind Harmer
5.175
253432AC1-085 GEN2
Solar/Wind Harmer
0.26
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
270227U2-072_GEN3
Solar/Wind Harmer
1.918
270228U2-072_GEN4
Solar/Wind Harmer
1.918
270231U2-072_GEN5
Solar/Wind Harmer
1.918
25306009OHH W.
Adder
2.794
270302AB2-170 GEN
Solar/Wind Harmer
8.028
970289AG2-191 GEN
Solar/Wind Harmer
1.776
963791AG1-232 GEN
Solar/Wind Harmer
12.58
247521TR3_G114
Solar/Wind Harmer
3.113
957201AF2-014 GEN
Solar/Wind Harmer
4.187
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
274735ELWOOD EC;4P
Adder
14.887
274744AC1-111 GEN8
Adder
5.047
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
970155AG2-107 GEN
Solar/Wind Harmer
15.681
972203AH1-686 GEN
Adder
2.339
24723205RIVRG3
Adder
18.772
253316AC1-085 GEN3
Solar/Wind Harmer
8.153
946171AF1-282 GEN
Solar/Wind Harmer
9.738
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252516AE2-318_GEN
Solar/Wind Harmer
9.663
25194608D.CRK4
Adder
1.582
945681AF1-233 GEN
Solar/Wind Harmer
17.8
971995AH1-542 GEN
Solar/Wind Harmer
10.357
965651AG1-433 GEN
Solar/Wind Harmer
5.136
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
957541AF2-048 GEN
Solar/Wind Harmer
1.627
961921AG1-034 GEN
Solar/Wind Harmer
13.042
270287AF1-227 GEN3
Solar/Wind Harmer
2.112
942051AE2-217 GEN
Solar/Wind Harmer
18.072
942871AE2-306 GEN
Solar/Wind Harmer
0.881
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
252507AC2-088 GEN
Solar/Wind Harmer
1.731
25196608WSDLE5
Adder
8.25
958171AF2-111 GEN
Solar/Wind Harmer
23.611
944531AF1-118 GEN
Solar/Wind Harmer
32.926
971347AH1-153 GEN
Solar/Wind Harmer
4.626
24728705AND G3
Adder
7.406
274752CRETE EC ;2U
Adder
7.503
274826FISK ;BP
Adder
9.937
274730ELWOOD EC;6P
Adder
14.887
238127S14_GEN_2
Solar/Wind Helper
0.769
238152AF2-075_GEN
Solar/Wind Helper
0.617
23777901MDS_W4-102
Solar/Wind Helper
0.153
270054AF2-122 C O1
Solar/Wind Harmer
3.36
253415AE1-040 GEN
Solar/Wind Harmer
1.12
938701AE1-092 GEN
Solar/Wind Harmer
20.019
253349AC2-067 GEN
Solar/Wind Harmer
1.965
25194408D.CRK1
Adder
7.279
270462AD2-086
Solar/Wind Harmer
6.668
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
9.417
926881AC1-175 GEN
Solar/Wind Harmer
5.249
960971AF2-388 GEN
Solar/Wind Harmer
10.271
270599AE1-208 GEN
Solar/Wind Harmer
7.629
24725505WLD G2 C
Solar/Wind Harmer
3.711
270247TR4_N_V136
Solar/Wind Harmer
0.788
970349AG2-230 GEN
Solar/Wind Harmer
13.877
274808UNIV PK N;4U
Adder
4.533
274674JOLIET 9 ;6U
Adder
13.943
274693ROCKY RD ;1P
Adder
9.926
23585401KL_K28_T16
Solar/Wind Helper
1.451
238117U2-030
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.432
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
23684201S70BUS2
50/50
0.3
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
4.42
252510AF1-249 C
Solar/Wind Harmer
0.402
25196808ZIMRHP
Adder
72.791
270485AE1-090_GEN
Solar/Wind Harmer
0.58
25196008MFTGT1
Adder
1.323
942081AE2-220 GEN
Solar/Wind Harmer
6.014
270209AC1-174_GEN
Solar/Wind Harmer
3.827
270239V3-007_GEN1
Solar/Wind Harmer
1.618
958861AF2-177 GEN
Solar/Wind Harmer
10.268
945371AF1-202 GEN
Solar/Wind Harmer
6.551
270005AE1-210 C O1
Solar/Wind Harmer
5.125
970825AG2-519 GEN
Solar/Wind Harmer
1.966
270594AE1-207 GEN
Solar/Wind Harmer
12.702
270032AE2-172
Solar/Wind Harmer
4.35
965011AG1-365 GEN
Solar/Wind Harmer
9.303
246936BC-WTG1
Solar/Wind Harmer
3.612
270489AE1-102 GEN1
Solar/Wind Harmer
1.2
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
23583801GRNGAP
Solar/Wind Helper
4.978
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.438
270291AC1-194 GEN
Solar/Wind Harmer
5.184
971985AH1-537 GEN
Solar/Wind Harmer
17.842
253406AD2-031_GEN
Solar/Wind Harmer
1.251
270224U2-072_GEN2
Solar/Wind Harmer
1.918
971029AG2-637 GEN
Solar/Wind Harmer
14.154
972165AH1-665 GEN
Solar/Wind Harmer
7.543
247536S-71 GEN
Solar/Wind Harmer
3.803
945581AF1-223 GEN
Solar/Wind Harmer
4.258
961761AG1-017 GEN
Solar/Wind Harmer
0.401
965051AG1-369 GEN
Solar/Wind Harmer
4.624
274775LINCOLN ;6U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
972228AH1-698 GEN2
Adder
3.362
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
23750701CROSSCHOOL
Solar/Wind Helper
1.372
961821AG1-024 GEN
Solar/Wind Harmer
8.695
270432AC2-029 GEN
Solar/Wind Harmer
7.128
270263AC1-001 GEN
Solar/Wind Harmer
1.061
945631AF1-228 GEN
Solar/Wind Harmer
4.727
253338AC1-165 GEN
Solar/Wind Harmer
1.085
270340AC2-060 GEN
Solar/Wind Harmer
3.013
241972AD1-140 GEN
Solar/Wind Harmer
4.405
270223U2-072_GEN1
Solar/Wind Harmer
1.918
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25196508WSDLE4
Adder
8.165
972163AH1-664 GEN
Solar/Wind Harmer
9.428
964611AG1-324 GEN
Solar/Wind Harmer
3.657
270356AE2-297 GEN
Solar/Wind Harmer
4.321
959331AF2-224 GEN
Solar/Wind Harmer
9.303
270191TR4_S_V150
Solar/Wind Harmer
2.777
965041AG1-368 GEN
Solar/Wind Harmer
9.252
274776LINCOLN ;7U
Adder
7.689
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
274746AC1-111 G10
Adder
5.047
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
23779801AA1-109
Solar/Wind Helper
0.168
3138216PACIFIC
Solar/Wind Helper
0.038
927014AC1-188 GEN
Solar/Wind Harmer
1.627
946101AF1-275 GEN
Solar/Wind Harmer
1.548
971073AG2-665 GEN
Solar/Wind Harmer
8.168
270269AC2-059
Solar/Wind Harmer
9.486
942861AE2-305 GEN
Solar/Wind Harmer
7.811
25326109MON D
Adder
1.28
25183208HLCRTG
Solar/Wind Harmer
5.858
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.247
253400AC2-068 GEN
Solar/Wind Harmer
0.79
25194508D.CRK3
Adder
1.361
24728805RICHG1
Adder
3.564
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
5.743
270024AE2-089 GEN
Solar/Wind Harmer
4.385
965421AG1-410 GEN
Solar/Wind Harmer
27.72
24728605AND G2
Adder
3.541
24639705ELKHART HY
Adder
0.141
274812UNIV PK N;8U
Adder
4.553
274676JOLIET 29;8U
Adder
27.787
274745AC1-111 GEN9
Adder
5.047
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
23777801MSM_W1-116
Solar/Wind Helper
0.1
253383AE2-342_GEN
Solar/Wind Harmer
0.888
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
247621Y3-024
Adder
0.226
970291AG2-192 GEN
Solar/Wind Harmer
1.215
970291AG2-192 GEN
Solar/Wind Harmer
0.391
270246TR4_N_V150
Solar/Wind Harmer
0.788
316097T157 G90
Solar/Wind Helper
1.331
238147AE2-230_GEN1
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.297
944541AF1-119 GEN
Solar/Wind Harmer
3.934
270201AC2-176 GEN
Solar/Wind Harmer
4.819
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
7.629
24699105WLD G1 C
Solar/Wind Harmer
3.668
247620Y3-023
Adder
0.422
274695ROCKY RD ;2P
Adder
10.024
235054AD2-180 GEN
Solar/Wind Helper
1.948
235531U2-073 GEN
Solar/Wind Helper
3.079
238149AF1-291A_GEN
Solar/Wind Helper
0.123
945421AF1-207 GEN
Solar/Wind Harmer
9.897
24318805MLG1
50/50
6.603
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
1.046
270518AE2-148 GEN
Solar/Wind Harmer
12.072
24379505HDWTR1G C
Solar/Wind Harmer
7.436
270004AE1-209 GEN
Solar/Wind Harmer
5.125
270491AE1-102 GEN2
Solar/Wind Harmer
1.2
274753CRETE EC ;3U
Adder
7.503
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274803UNIV PARK;6U
Adder
5.293
972038AH1-567 GEN2
Adder
0.331
23562501BACKB
Solar/Wind Helper
1.049
238108AE1-109 GEN1
Solar/Wind Helper
0.103
237001AB1-127_GEN
Solar/Wind Helper
0.384
270520AE2-214 GEN
Solar/Wind Harmer
6.192
270273AD2-016 GEN
Solar/Wind Harmer
2.704
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
1.046
270391AF1-285 GEN3
Solar/Wind Harmer
1.175
25326309TAIT D
Adder
1.064
270317AD1-130_GEN
Solar/Wind Harmer
3.069
944031AF1-071 GEN
Solar/Wind Harmer
0.956
270437AC2-090 C
Solar/Wind Harmer
5.249
276903AD2-071 C
Solar/Wind Harmer
9.334
274754CRETE EC ;4U
Adder
7.503
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274674JOLIET 9 ;6U
Adder
13.943
235067AD1-061 GEN
Solar/Wind Helper
0.388
237002AB1-128_GEN
Solar/Wind Helper
0.386
23559101PLEAS2
50/50
11.898
23562301OGROV1
50/50
2.293
970149AG2-104 GEN
Solar/Wind Harmer
22.207
960001AF2-291 GEN
Solar/Wind Harmer
3.191
270510AE1-227 GEN1
Solar/Wind Harmer
2.61
971073AG2-665 GEN
Solar/Wind Harmer
1.187
270286AF1-227 GEN2
Solar/Wind Harmer
2.112
270578AF1-285 GEN2
Solar/Wind Harmer
1.175
270222AC2-111 GEN
Solar/Wind Harmer
4.248
970091AG2-072 GEN
Adder
71.643
23546401DTGZ2-030
Solar/Wind Helper
0.078
237038AE2-054 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.51 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4683.44
MW Contribution:
10.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24721905FLATG4
Adder
24.155
962771AG1-126 GEN
Solar/Wind Harmer
36.099
970153AG2-106 GEN
Solar/Wind Harmer
15.741
270284AF1-227 GEN1
Solar/Wind Harmer
5.734
253317AC1-085 GEN4
Solar/Wind Harmer
8.185
946181AF1-283 GEN
Solar/Wind Harmer
12.71
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.955
253371AE2-315 SEC2
Adder
1.85
960071AF2-298 GEN
Solar/Wind Harmer
1.473
252519AF1-045_GEN
Solar/Wind Harmer
3.531
276820AF1-078_GEN
Solar/Wind Harmer
1.544
252524AE2-267 GEN
Solar/Wind Harmer
1.522
25194608D.CRK4
Adder
1.589
946031AF1-268 GEN
Solar/Wind Harmer
7.814
970289AG2-191 GEN
Solar/Wind Harmer
0.72
247642Z2-115 C
Solar/Wind Harmer
0.06
24728505AND G1
Adder
3.555
24695305TIMB G C
Solar/Wind Harmer
3.093
274811UNIV PK N;7U
Adder
4.572
274734ELWOOD EC;8P
Adder
14.948
274736ELWOOD EC;9P
Adder
14.948
274676JOLIET 29;8U
Adder
26.905
274682WAUKEGAN ;7U
Adder
16.24
964991AG1-363 GEN
Solar/Wind Helper
4.317
238110AE1-109 GEN3
Solar/Wind Helper
0.102
235063AE1-101 C2
Solar/Wind Helper
1.453
270459AD2-067 GEN
Solar/Wind Harmer
8.603
940611AE2-048 GEN
Solar/Wind Harmer
22.381
941391AE2-136 GEN
Solar/Wind Harmer
11.597
25196408WSDLE3
Adder
8.526
25196308WSDLE2
Adder
8.452
25196208WSDLE1
Adder
8.431
25196708WSDLE6
Adder
8.409
25196108MFTGT2
Adder
1.464
25196108MFTGT2
Adder
1.359
270512AE1-227 GEN2
Solar/Wind Harmer
2.229
971191AH1-055 GEN
Solar/Wind Harmer
19.41
970879AG2-548 GEN
Solar/Wind Harmer
8.201
960801AF2-371 GEN
Solar/Wind Harmer
2.597
964871AG1-351 GEN
Solar/Wind Harmer
1.793
270367AC2-061_GEN
Solar/Wind Harmer
3.114
253394AE2-221_GEN
Solar/Wind Harmer
4.438
270186AC1-089 GEN
Solar/Wind Harmer
5.95
25196008MFTGT1
Adder
1.286
972167AH1-666 GEN
Solar/Wind Harmer
7.586
270240V3-007_GEN2
Solar/Wind Harmer
5.841
962031AG1-047 GEN
Solar/Wind Harmer
2.847
957741AF2-068 GEN
Solar/Wind Harmer
14.123
241955AC1-078 GEN
Solar/Wind Harmer
7.581
241973AD2-163_GEN1
Solar/Wind Harmer
1.995
241974AD2-163_GEN2
Solar/Wind Harmer
1.995
253343AC1-166 GEN
Solar/Wind Harmer
1.089
943861AF1-054 GEN
Solar/Wind Harmer
3.872
943851AF1-053 GEN
Solar/Wind Harmer
1.871
253433AC1-085 GEN1
Solar/Wind Harmer
5.195
253432AC1-085 GEN2
Solar/Wind Harmer
0.261
253372AE2-315 SEC3
Adder
1.85
253372AE2-315 SEC3
Adder
1.85
270227U2-072_GEN3
Solar/Wind Harmer
1.927
270228U2-072_GEN4
Solar/Wind Harmer
1.927
270231U2-072_GEN5
Solar/Wind Harmer
1.927
25306009OHH W.
Adder
2.806
270302AB2-170 GEN
Solar/Wind Harmer
8.066
970289AG2-191 GEN
Solar/Wind Harmer
1.783
963791AG1-232 GEN
Solar/Wind Harmer
12.634
247521TR3_G114
Solar/Wind Harmer
3.127
957201AF2-014 GEN
Solar/Wind Harmer
4.207
972227AH1-698 GEN1
Adder
2.377
274827FISK ;RP
Adder
7.071
274800UNIV PARK;3U
Adder
5.313
274801UNIV PARK;4U
Adder
5.313
274735ELWOOD EC;4P
Adder
14.948
274744AC1-111 GEN8
Adder
5.067
238169AE2-226 GEN1
Solar/Wind Helper
0.61
238170AE2-226 GEN2
Solar/Wind Helper
0.61
237025AB1-124 C
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.059
23559001PLEAS1
50/50
11.912
23562401OGROV2
50/50
2.283
270330AC1-082 GEN2
Solar/Wind Harmer
0.495
957541AF2-048 GEN
Solar/Wind Harmer
1.634
961921AG1-034 GEN
Solar/Wind Harmer
13.102
270287AF1-227 GEN3
Solar/Wind Harmer
2.121
942051AE2-217 GEN
Solar/Wind Harmer
18.15
942871AE2-306 GEN
Solar/Wind Harmer
0.885
270391AF1-285 GEN3
Solar/Wind Harmer
0.454
252507AC2-088 GEN
Solar/Wind Harmer
1.738
25196608WSDLE5
Adder
8.282
958171AF2-111 GEN
Solar/Wind Harmer
23.702
944531AF1-118 GEN
Solar/Wind Harmer
33.064
971347AH1-153 GEN
Solar/Wind Harmer
4.646
24728705AND G3
Adder
7.436
958581AF2-149 GEN
Solar/Wind Harmer
3.962
274752CRETE EC ;2U
Adder
7.534
274826FISK ;BP
Adder
9.978
274730ELWOOD EC;6P
Adder
14.948
238127S14_GEN_2
Solar/Wind Helper
0.755
238152AF2-075_GEN
Solar/Wind Helper
0.621
23777901MDS_W4-102
Solar/Wind Helper
0.154
270054AF2-122 C O1
Solar/Wind Harmer
3.376
253415AE1-040 GEN
Solar/Wind Harmer
1.125
938701AE1-092 GEN
Solar/Wind Harmer
20.114
253349AC2-067 GEN
Solar/Wind Harmer
1.973
25194408D.CRK1
Adder
7.308
270462AD2-086
Solar/Wind Harmer
6.699
24728905RICHG2
Adder
3.578
970883AG2-550 GEN
Solar/Wind Harmer
9.456
926881AC1-175 GEN
Solar/Wind Harmer
5.27
960971AF2-388 GEN
Solar/Wind Harmer
10.314
270599AE1-208 GEN
Solar/Wind Harmer
7.66
24725505WLD G2 C
Solar/Wind Harmer
3.726
270247TR4_N_V136
Solar/Wind Harmer
0.791
970349AG2-230 GEN
Solar/Wind Harmer
13.937
274808UNIV PK N;4U
Adder
4.552
274674JOLIET 9 ;6U
Adder
14
274693ROCKY RD ;1P
Adder
9.966
23585401KL_K28_T16
Solar/Wind Helper
1.409
238117U2-030
Solar/Wind Helper
0.311
238148AE2-230_GEN2
Solar/Wind Helper
0.435
235062AE1-101 C1
Solar/Wind Helper
1.453
237006AB1-125 GEN
Solar/Wind Helper
0.108
970825AG2-519 GEN
Solar/Wind Harmer
5.3
965461AG1-414 GEN
Solar/Wind Harmer
2.128
270043AE2-236 GEN
Solar/Wind Harmer
5.148
965021AG1-366 GEN
Solar/Wind Harmer
2.173
246938BC-WTG3
Solar/Wind Harmer
3.691
274772LINCOLN ;3U
Adder
7.721
274724RIVER EC ;11
Adder
16.186
972259AH1-714 GEN
Adder
17.382
274729ELWOOD EC;1P
Adder
14.948
238175AF1-290_GEN
Solar/Wind Helper
0.135
316415AF1-147_GEN2
Solar/Wind Helper
0.768
237048AF1-022 C
Solar/Wind Helper
0.156
23684201S70BUS2
50/50
0.302
270331AC1-082 GEN3
Solar/Wind Harmer
0.497
972269AH1-719 GEN
Adder
2.301
253398AE2-221_GEN2
Solar/Wind Harmer
4.438
252510AF1-249 C
Solar/Wind Harmer
0.403
270485AE1-090_GEN
Solar/Wind Harmer
0.583
25196808ZIMRHP
Adder
73.077
25196008MFTGT1
Adder
1.328
942081AE2-220 GEN
Solar/Wind Harmer
6.039
270209AC1-174_GEN
Solar/Wind Harmer
3.843
270239V3-007_GEN1
Solar/Wind Harmer
1.625
958861AF2-177 GEN
Solar/Wind Harmer
10.311
945371AF1-202 GEN
Solar/Wind Harmer
6.578
270005AE1-210 C O1
Solar/Wind Harmer
5.146
970825AG2-519 GEN
Solar/Wind Harmer
1.974
270594AE1-207 GEN
Solar/Wind Harmer
12.754
270032AE2-172
Solar/Wind Harmer
4.368
965011AG1-365 GEN
Solar/Wind Harmer
9.345
246936BC-WTG1
Solar/Wind Harmer
3.628
270489AE1-102 GEN1
Solar/Wind Harmer
1.206
274773LINCOLN ;4U
Adder
7.721
274774LINCOLN ;5U
Adder
7.721
274751CRETE EC ;1U
Adder
7.534
274723RIVER EC ;12
Adder
16.377
23583801GRNGAP
Solar/Wind Helper
5.023
238126S14_GEN_1
Solar/Wind Helper
0.755
237085AD2-009_GEN
Solar/Wind Helper
1.443
270291AC1-194 GEN
Solar/Wind Harmer
5.205
971985AH1-537 GEN
Solar/Wind Harmer
17.911
253406AD2-031_GEN
Solar/Wind Harmer
1.256
270224U2-072_GEN2
Solar/Wind Harmer
1.927
971029AG2-637 GEN
Solar/Wind Harmer
14.212
972165AH1-665 GEN
Solar/Wind Harmer
7.571
247536S-71 GEN
Solar/Wind Harmer
3.819
945581AF1-223 GEN
Solar/Wind Harmer
4.276
961761AG1-017 GEN
Solar/Wind Harmer
0.403
965051AG1-369 GEN
Solar/Wind Harmer
4.645
274775LINCOLN ;6U
Adder
7.721
274777LINCOLN ;8U
Adder
7.721
972037AH1-567 GEN1
Adder
0.167
972228AH1-698 GEN2
Adder
3.376
274675JOLIET 29;7U
Adder
27.901
274675JOLIET 29;7U
Adder
26.905
23750701CROSSCHOOL
Solar/Wind Helper
1.353
970031AG2-029 GEN
Solar/Wind Harmer
4.035
961821AG1-024 GEN
Solar/Wind Harmer
8.735
270432AC2-029 GEN
Solar/Wind Harmer
7.158
270263AC1-001 GEN
Solar/Wind Harmer
1.066
945631AF1-228 GEN
Solar/Wind Harmer
4.748
253338AC1-165 GEN
Solar/Wind Harmer
1.089
270340AC2-060 GEN
Solar/Wind Harmer
3.025
241972AD1-140 GEN
Solar/Wind Harmer
4.424
270223U2-072_GEN1
Solar/Wind Harmer
1.927
270578AF1-285 GEN2
Solar/Wind Harmer
0.454
25196508WSDLE4
Adder
8.198
972163AH1-664 GEN
Solar/Wind Harmer
9.464
964611AG1-324 GEN
Solar/Wind Harmer
3.672
270356AE2-297 GEN
Solar/Wind Harmer
4.339
970155AG2-107 GEN
Solar/Wind Harmer
15.741
972203AH1-686 GEN
Adder
2.346
24723205RIVRG3
Adder
18.832
253316AC1-085 GEN3
Solar/Wind Harmer
8.185
946171AF1-282 GEN
Solar/Wind Harmer
9.777
253370AE2-315 SEC1
Adder
1.955
253371AE2-315 SEC2
Adder
1.85
252516AE2-318_GEN
Solar/Wind Harmer
9.702
25194608D.CRK4
Adder
1.589
945681AF1-233 GEN
Solar/Wind Harmer
17.868
971995AH1-542 GEN
Solar/Wind Harmer
10.409
965651AG1-433 GEN
Solar/Wind Harmer
5.157
270024AE2-089 GEN
Solar/Wind Harmer
4.403
965421AG1-410 GEN
Solar/Wind Harmer
27.848
24728605AND G2
Adder
3.555
24639705ELKHART HY
Adder
0.141
274812UNIV PK N;8U
Adder
4.572
274676JOLIET 29;8U
Adder
27.901
274745AC1-111 GEN9
Adder
5.067
274682WAUKEGAN ;7U
Adder
1.999
23751101LEADS_P59
Solar/Wind Helper
2.36
316095T157 G97
Solar/Wind Helper
1.343
238185AF2-356 C
Solar/Wind Helper
2.448
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238120AE2-309 GEN
Solar/Wind Helper
0.48
23777801MSM_W1-116
Solar/Wind Helper
0.1
24318905MLG2
50/50
4.853
270349AD2-093_GEN
Solar/Wind Harmer
3.775
270471AD2-092_GEN
Solar/Wind Harmer
3.775
253383AE2-342_GEN
Solar/Wind Harmer
0.892
24723005RIVRG1
Adder
18.832
24723105RIVRG2
Adder
18.832
253370AE2-315 SEC1
Adder
1.955
25322209TAIT E
Adder
9.512
25322209TAIT E
Adder
9.298
247621Y3-024
Adder
0.227
970291AG2-192 GEN
Solar/Wind Harmer
1.22
970291AG2-192 GEN
Solar/Wind Harmer
0.393
270246TR4_N_V150
Solar/Wind Harmer
0.791
316097T157 G90
Solar/Wind Helper
1.343
238147AE2-230_GEN1
Solar/Wind Helper
0.435
237080AD1-060 GEN
Solar/Wind Helper
0.298
927014AC1-188 GEN
Solar/Wind Harmer
1.634
946101AF1-275 GEN
Solar/Wind Harmer
1.555
971073AG2-665 GEN
Solar/Wind Harmer
8.201
270269AC2-059
Solar/Wind Harmer
9.525
942861AE2-305 GEN
Solar/Wind Harmer
7.845
25326109MON D
Adder
1.285
972159AH1-661 GEN
Adder
0.971
25183208HLCRTG
Solar/Wind Harmer
5.882
252509AD1-136 GEN
Solar/Wind Harmer
0.248
253400AC2-068 GEN
Solar/Wind Harmer
0.793
25194508D.CRK3
Adder
1.366
24728805RICHG1
Adder
3.578
970885AG2-551 GEN
Solar/Wind Harmer
2.199
270383AD1-128 GEN
Solar/Wind Harmer
5.766
944541AF1-119 GEN
Solar/Wind Harmer
3.951
270201AC2-176 GEN
Solar/Wind Harmer
4.839
964611AG1-324 GEN
Solar/Wind Harmer
0.493
270031AE2-169
Solar/Wind Harmer
7.66
24699105WLD G1 C
Solar/Wind Harmer
3.683
247620Y3-023
Adder
0.424
274695ROCKY RD ;2P
Adder
10.065
235054AD2-180 GEN
Solar/Wind Helper
1.901
235531U2-073 GEN
Solar/Wind Helper
3.003
238149AF1-291A_GEN
Solar/Wind Helper
0.124
24318805MLG1
50/50
6.628
270329AC1-082 GEN1
Solar/Wind Harmer
0.495
24686405CER G5
Adder
8.32
253325AC1-069 GEN
Solar/Wind Harmer
1.051
270518AE2-148 GEN
Solar/Wind Harmer
12.124
24379505HDWTR1G C
Solar/Wind Harmer
7.466
270004AE1-209 GEN
Solar/Wind Harmer
5.146
270491AE1-102 GEN2
Solar/Wind Harmer
1.206
971199AH1-059 GEN
Solar/Wind Harmer
1.944
274753CRETE EC ;3U
Adder
7.534
274814UNIV PK N;0U
Adder
4.612
274807UNIV PK N;3U
Adder
4.602
274803UNIV PARK;6U
Adder
5.315
972038AH1-567 GEN2
Adder
0.333
23562501BACKB
Solar/Wind Helper
1.016
238108AE1-109 GEN1
Solar/Wind Helper
0.102
237001AB1-127_GEN
Solar/Wind Helper
0.386
959331AF2-224 GEN
Solar/Wind Harmer
9.345
270191TR4_S_V150
Solar/Wind Harmer
2.79
965041AG1-368 GEN
Solar/Wind Harmer
9.293
274776LINCOLN ;7U
Adder
7.721
274687WILL CNTY;4U
Adder
25.419
274687WILL CNTY;4U
Adder
25.419
274731ELWOOD EC;2P
Adder
14.948
274733ELWOOD EC;3P
Adder
14.948
274746AC1-111 G10
Adder
5.067
238118U2-030_1
Solar/Wind Helper
0.311
23750501ELLIOTTS
Solar/Wind Helper
0.612
23779801AA1-109
Solar/Wind Helper
0.169
3138216PACIFIC
Solar/Wind Helper
0.038
962761AG1-125 GEN
Solar/Wind Harmer
36.099
270520AE2-214 GEN
Solar/Wind Harmer
6.219
270273AD2-016 GEN
Solar/Wind Harmer
2.715
24686505CER G6
Adder
8.386
253333AC1-068 GEN
Solar/Wind Harmer
1.051
270391AF1-285 GEN3
Solar/Wind Harmer
1.18
25326309TAIT D
Adder
1.069
270317AD1-130_GEN
Solar/Wind Harmer
3.084
944031AF1-071 GEN
Solar/Wind Harmer
0.96
270437AC2-090 C
Solar/Wind Harmer
5.27
276903AD2-071 C
Solar/Wind Harmer
9.372
274754CRETE EC ;4U
Adder
7.534
274802UNIV PARK;5U
Adder
5.315
274732ELWOOD EC;7P
Adder
14.948
274674JOLIET 9 ;6U
Adder
14
235067AD1-061 GEN
Solar/Wind Helper
0.39
237002AB1-128_GEN
Solar/Wind Helper
0.387
23684101S70BUS1
50/50
0.296
970879AG2-548 GEN
Solar/Wind Harmer
1.192
962581AG1-107 GEN
Solar/Wind Harmer
4.941
961491AF2-440 GEN
Solar/Wind Harmer
2.053
253378AE2-206_GEN
Solar/Wind Harmer
3.476
25326509SID D
Adder
1.267
942221AE2-234 GEN
Solar/Wind Harmer
3.287
246937BC-WTG2
Solar/Wind Harmer
3.628
274770LINCOLN ;1U
Adder
7.721
274771LINCOLN ;2U
Adder
7.721
274805UNIV PK N;1U
Adder
4.582
274696ROCKY RD ;4P
Adder
10.303
274697ROCKY RD ;3P
Adder
2.734
23751201ROTHROCK
Solar/Wind Helper
0.827
237061AD1-155 GEN
Solar/Wind Helper
1.542
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.239
316411AF1-147_GEN1
Solar/Wind Helper
0.768
23559101PLEAS2
50/50
11.912
23562301OGROV1
50/50
2.303
970149AG2-104 GEN
Solar/Wind Harmer
22.291
270510AE1-227 GEN1
Solar/Wind Harmer
2.626
960001AF2-291 GEN
Solar/Wind Harmer
3.203
971073AG2-665 GEN
Solar/Wind Harmer
1.192
270286AF1-227 GEN2
Solar/Wind Harmer
2.121
270578AF1-285 GEN2
Solar/Wind Harmer
1.18
270222AC2-111 GEN
Solar/Wind Harmer
4.266
970091AG2-072 GEN
Adder
71.916
23546401DTGZ2-030
Solar/Wind Helper
0.078
237038AE2-054 C
Solar/Wind Helper
0.238
270543AE2-219 C
Solar/Wind Harmer
9.456
24729505KEY G4
Adder
6.127
958711AF2-162 GEN
Solar/Wind Harmer
0.955
270071AF1-092 GEN
Solar/Wind Harmer
14.1
270435AC2-044 GEN
Solar/Wind Harmer
1.855
274728ELWOOD EC;5P
Adder
14.948
CPLELTFEXP_CPLE->PJM
CLTF
1.203
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.012
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.694
MECLTFEXP_MEC->PJM
CLTF
14.418
SIGELTFEXP_SIGE->PJM
CLTF
0.465
NYPJM->LTFIMP_NY
CLTF
4.537
LGEELTFEXP_LGEE->PJM
CLTF
6.253
WECLTFEXP_WEC->PJM
CLTF
3.425
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.32
LAGNLTFEXP_LAGN->PJM
CLTF
14.087
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.851
TVALTFEXP_TVA->PJM
CLTF
6.994

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.99
MW Contribution:
2.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25196508WSDLE4
Adder
8.165
972163AH1-664 GEN
Solar/Wind Harmer
7.323
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.067
959331AF2-224 GEN
Solar/Wind Harmer
4.543
965041AG1-368 GEN
Solar/Wind Harmer
6.455
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
970155AG2-107 GEN
Solar/Wind Harmer
19.366
972203AH1-686 GEN
Adder
2.339
24723205RIVRG3
Adder
18.772
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252516AE2-318_GEN
Solar/Wind Harmer
7.551
25194608D.CRK4
Adder
1.582
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
970613AG2-401 GEN
Solar/Wind Harmer
4.811
965651AG1-433 GEN
Solar/Wind Harmer
1.923
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965421AG1-410 GEN
Solar/Wind Harmer
19.339
24728605AND G2
Adder
3.541
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.553
274676JOLIET 29;8U
Adder
27.787
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
971655AH1-328 GEN
Solar/Wind Harmer
2.4
247621Y3-024
Adder
0.226
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
270246TR4_N_V150
Solar/Wind Harmer
0.041
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.006
971587AH1-292 GEN
Solar/Wind Harmer
4.656
276776AD2-060 GEN
Solar/Wind Harmer
0.676
971125AH1-004 GEN
Solar/Wind Harmer
2.523
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.331
238147AE2-230_GEN1
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.297
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.862
25194408D.CRK1
Adder
7.279
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.846
270599AE1-208 GEN
Solar/Wind Harmer
5.986
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
972043AH1-570 GEN
Solar/Wind Harmer
1.663
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274808UNIV PK N;4U
Adder
4.533
945391AF1-204 GEN
Solar/Wind Harmer
6.73
274674JOLIET 9 ;6U
Adder
13.943
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
274693ROCKY RD ;1P
Adder
9.926
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
23585401KL_K28_T16
Solar/Wind Helper
1.451
238117U2-030
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.432
235062AE1-101 C1
Solar/Wind Helper
1.447
237006AB1-125 GEN
Solar/Wind Helper
0.107
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274776LINCOLN ;7U
Adder
7.689
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274746AC1-111 G10
Adder
5.047
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
23779801AA1-109
Solar/Wind Helper
0.168
3138216PACIFIC
Solar/Wind Helper
0.038
971073AG2-665 GEN
Solar/Wind Harmer
5.224
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
25326109MON D
Adder
1.28
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194508D.CRK3
Adder
1.361
24728805RICHG1
Adder
3.564
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.075
253406AD2-031_GEN
Solar/Wind Harmer
0.507
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972165AH1-665 GEN
Solar/Wind Harmer
5.865
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.226
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
971675AH1-338 GEN
Solar/Wind Harmer
2.438
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
971171AH1-044 GEN
Solar/Wind Harmer
3.185
23684201S70BUS2
50/50
0.3
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.051
25196808ZIMRHP
Adder
72.791
25196008MFTGT1
Adder
1.323
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
965011AG1-365 GEN
Solar/Wind Harmer
6.491
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
274773LINCOLN ;4U
Adder
7.689
23684101S70BUS1
50/50
0.295
970879AG2-548 GEN
Solar/Wind Harmer
1.187
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.261
942221AE2-234 GEN
Solar/Wind Harmer
2.621
246937BC-WTG2
Solar/Wind Harmer
0.26
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
25306009OHH W.
Adder
2.794
270302AB2-170 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247620Y3-023
Adder
0.422
972045AH1-571 GEN
Solar/Wind Harmer
1.333
958011AF2-095 GEN
Solar/Wind Harmer
9.122
274695ROCKY RD ;2P
Adder
10.024
958491AF2-143 GEN
Solar/Wind Harmer
9.422
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.948
235531U2-073 GEN
Solar/Wind Helper
3.079
238149AF1-291A_GEN
Solar/Wind Helper
0.123
23559101PLEAS2
50/50
11.898
23562301OGROV1
50/50
2.293
970149AG2-104 GEN
Solar/Wind Harmer
16.378
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
971073AG2-665 GEN
Solar/Wind Harmer
1.187
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970091AG2-072 GEN
Adder
71.643
971917AH1-482 GEN
Solar/Wind Harmer
8.351
970373AG2-245 GEN
Solar/Wind Harmer
13.48
963741AG1-226 GEN
Solar/Wind Harmer
15.1
971653AH1-327 GEN
Solar/Wind Harmer
0.941
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
247521TR3_G114
Solar/Wind Harmer
0.234
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274735ELWOOD EC;4P
Adder
14.887
274744AC1-111 GEN8
Adder
5.047
970169AG2-114 GEN
Solar/Wind Harmer
6.285
959341AF2-225 GEN
Solar/Wind Harmer
6.578
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252519AF1-045_GEN
Solar/Wind Harmer
3.517
25194608D.CRK4
Adder
1.582
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
274811UNIV PK N;7U
Adder
4.553
276806AD2-047 C O1
Solar/Wind Harmer
3.589
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274682WAUKEGAN ;7U
Adder
16.174
270588AE1-091_GEN
Solar/Wind Harmer
4.882
964991AG1-363 GEN
Solar/Wind Helper
4.289
238110AE1-109 GEN3
Solar/Wind Helper
0.103
235063AE1-101 C2
Solar/Wind Helper
1.447
959091AF2-200 GEN
Solar/Wind Harmer
3.185
970241AG2-163 GEN
Solar/Wind Harmer
3.722
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
970941AG2-585 GEN
Solar/Wind Harmer
3.484
276897AD1-100 C
Solar/Wind Harmer
15.831
276893AG1-478 C
Solar/Wind Harmer
0.421
970107AG2-081 GEN
Solar/Wind Harmer
1.892
274696ROCKY RD ;4P
Adder
10.261
274697ROCKY RD ;3P
Adder
2.723
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
316411AF1-147_GEN1
Solar/Wind Helper
0.762
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
970825AG2-519 GEN
Solar/Wind Harmer
4.924
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
246938BC-WTG3
Solar/Wind Harmer
0.232
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274724RIVER EC ;11
Adder
16.119
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
946671AF1-331 GEN
Solar/Wind Harmer
0.667
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
237048AF1-022 C
Solar/Wind Helper
0.176
238175AF1-290_GEN
Solar/Wind Helper
0.135
316415AF1-147_GEN2
Solar/Wind Helper
0.762
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.293
939741AE1-205 GEN
Solar/Wind Harmer
8.771
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23583801GRNGAP
Solar/Wind Helper
4.978
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.438
943021AE2-325 GEN
Solar/Wind Harmer
3.32
941551AE2-152 GEN
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.303
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.732
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.078
237038AE2-054 C
Solar/Wind Helper
0.237
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
24318805MLG1
50/50
6.603
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
970191AG2-125 GEN
Solar/Wind Harmer
1.734
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
961921AG1-034 GEN
Solar/Wind Harmer
6.37
942051AE2-217 GEN
Solar/Wind Harmer
12.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
252507AC2-088 GEN
Solar/Wind Harmer
0.304
25196608WSDLE5
Adder
8.25
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
971347AH1-153 GEN
Solar/Wind Harmer
3.227
24728705AND G3
Adder
7.406
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.503
274887GEN-1.85
Solar/Wind Harmer
0.165
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
274730ELWOOD EC;6P
Adder
14.887
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
959611AF2-252 GEN
Solar/Wind Harmer
2.083
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
238127S14_GEN_2
Solar/Wind Helper
0.769
238152AF2-075_GEN
Solar/Wind Helper
0.617
23777901MDS_W4-102
Solar/Wind Helper
0.153
962761AG1-125 GEN
Solar/Wind Harmer
30.328
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.726
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.064
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.272
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.503
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274674JOLIET 9 ;6U
Adder
13.943
939401AE1-172 GEN
Solar/Wind Harmer
4.718
962781AG1-127 GEN
Solar/Wind Harmer
5.964
235067AD1-061 GEN
Solar/Wind Helper
0.388
237002AB1-128_GEN
Solar/Wind Helper
0.386
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.503
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274803UNIV PARK;6U
Adder
5.293
276843GEN-1.7
Solar/Wind Harmer
0.205
972038AH1-567 GEN2
Adder
0.331
965091AG1-374 GEN
Solar/Wind Harmer
18.751
23562501BACKB
Solar/Wind Helper
1.049
238108AE1-109 GEN1
Solar/Wind Helper
0.103
237001AB1-127_GEN
Solar/Wind Helper
0.384
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
270071AF1-092 GEN
Solar/Wind Harmer
12.517
270435AC2-044 GEN
Solar/Wind Harmer
0.816
24691005MDL-2G C
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
274728ELWOOD EC;5P
Adder
14.887
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4650.57
MW Contribution:
2.41
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970155AG2-107 GEN
Solar/Wind Harmer
19.366
972203AH1-686 GEN
Adder
2.339
24723205RIVRG3
Adder
18.772
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.794
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252516AE2-318_GEN
Solar/Wind Harmer
7.551
25194608D.CRK4
Adder
1.582
945681AF1-233 GEN
Solar/Wind Harmer
12.419
971995AH1-542 GEN
Solar/Wind Harmer
2.409
970613AG2-401 GEN
Solar/Wind Harmer
4.811
24318905MLG2
50/50
4.819
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.862
961821AG1-024 GEN
Solar/Wind Harmer
4.246
270432AC2-029 GEN
Solar/Wind Harmer
3.15
270263AC1-001 GEN
Solar/Wind Harmer
0.709
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.749
270578AF1-285 GEN2
Solar/Wind Harmer
0.452
25196508WSDLE4
Adder
8.165
25194408D.CRK1
Adder
7.279
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.564
970883AG2-550 GEN
Solar/Wind Harmer
6.57
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.846
270599AE1-208 GEN
Solar/Wind Harmer
5.986
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.041
970349AG2-230 GEN
Solar/Wind Harmer
9.682
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.726
972043AH1-570 GEN
Solar/Wind Harmer
1.663
961051AF2-396 GEN
Solar/Wind Harmer
12.733
961051AF2-396 GEN
Solar/Wind Harmer
8.489
274808UNIV PK N;4U
Adder
4.533
945391AF1-204 GEN
Solar/Wind Harmer
6.73
274674JOLIET 9 ;6U
Adder
13.943
958481AF2-142 GEN
Solar/Wind Harmer
9.443
944231AF1-091 GEN
Solar/Wind Harmer
14.516
274693ROCKY RD ;1P
Adder
9.926
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.083
23585401KL_K28_T16
Solar/Wind Helper
1.451
238117U2-030
Solar/Wind Helper
0.32
238148AE2-230_GEN2
Solar/Wind Helper
0.432
235062AE1-101 C1
Solar/Wind Helper
1.447
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.075
253406AD2-031_GEN
Solar/Wind Harmer
0.507
971029AG2-637 GEN
Solar/Wind Harmer
9.875
972165AH1-665 GEN
Solar/Wind Harmer
5.865
247536S-71 GEN
Solar/Wind Harmer
0.262
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.226
970031AG2-029 GEN
Solar/Wind Harmer
3.483
971611AH1-305 GEN
Solar/Wind Harmer
3.826
959141AF2-205 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.171
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.689
274777LINCOLN ;8U
Adder
7.689
972037AH1-567 GEN1
Adder
0.166
960591AF2-350 GEN
Solar/Wind Harmer
6.334
972228AH1-698 GEN2
Adder
3.362
274675JOLIET 29;7U
Adder
27.787
274675JOLIET 29;7U
Adder
26.795
970833AG2-524 GEN
Solar/Wind Harmer
6.949
970833AG2-524 GEN
Solar/Wind Harmer
4.633
971675AH1-338 GEN
Solar/Wind Harmer
2.438
971411AH1-196 GEN
Solar/Wind Harmer
9.373
23750701CROSSCHOOL
Solar/Wind Helper
1.372
971171AH1-044 GEN
Solar/Wind Harmer
3.185
24723005RIVRG1
Adder
18.772
24723105RIVRG2
Adder
18.772
253370AE2-315 SEC1
Adder
1.947
25322209TAIT E
Adder
9.472
25322209TAIT E
Adder
9.26
971655AH1-328 GEN
Solar/Wind Harmer
2.4
247621Y3-024
Adder
0.226
971613AH1-306 GEN
Solar/Wind Harmer
3.132
970291AG2-192 GEN
Solar/Wind Harmer
0.848
970291AG2-192 GEN
Solar/Wind Harmer
0.391
270246TR4_N_V150
Solar/Wind Harmer
0.041
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.006
971587AH1-292 GEN
Solar/Wind Harmer
4.656
276776AD2-060 GEN
Solar/Wind Harmer
0.676
971125AH1-004 GEN
Solar/Wind Harmer
2.523
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.331
238147AE2-230_GEN1
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.297
971341AH1-150 GEN
Solar/Wind Harmer
3.185
971343AH1-151 GEN
Solar/Wind Harmer
3.185
971073AG2-665 GEN
Solar/Wind Harmer
5.224
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.449
25326109MON D
Adder
1.28
25183208HLCRTG
Solar/Wind Harmer
0
972159AH1-661 GEN
Adder
0.966
252509AD1-136 GEN
Solar/Wind Harmer
0.034
970329AG2-216 GEN
Solar/Wind Harmer
2.902
25194508D.CRK3
Adder
1.361
24728805RICHG1
Adder
3.564
970885AG2-551 GEN
Solar/Wind Harmer
2.19
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.438
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.491
270031AE2-169
Solar/Wind Harmer
3.592
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.871
247620Y3-023
Adder
0.422
972045AH1-571 GEN
Solar/Wind Harmer
1.333
958011AF2-095 GEN
Solar/Wind Harmer
9.122
274695ROCKY RD ;2P
Adder
10.024
958491AF2-143 GEN
Solar/Wind Harmer
9.422
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
1.948
235531U2-073 GEN
Solar/Wind Helper
3.079
238149AF1-291A_GEN
Solar/Wind Helper
0.123
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.69
943851AF1-053 GEN
Solar/Wind Harmer
1.863
253372AE2-315 SEC3
Adder
1.842
253372AE2-315 SEC3
Adder
1.842
25306009OHH W.
Adder
2.794
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.941
970289AG2-191 GEN
Solar/Wind Harmer
1.239
963791AG1-232 GEN
Solar/Wind Harmer
8.777
247521TR3_G114
Solar/Wind Harmer
0.234
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.368
274827FISK ;RP
Adder
7.042
274800UNIV PARK;3U
Adder
5.291
274801UNIV PARK;4U
Adder
5.291
970179AG2-119 GEN
Solar/Wind Harmer
5.652
274735ELWOOD EC;4P
Adder
14.887
274744AC1-111 GEN8
Adder
5.047
970169AG2-114 GEN
Solar/Wind Harmer
6.285
959341AF2-225 GEN
Solar/Wind Harmer
6.578
238169AE2-226 GEN1
Solar/Wind Helper
0.606
238170AE2-226 GEN2
Solar/Wind Helper
0.606
237025AB1-124 C
Solar/Wind Helper
0.143
237030AB1-096 C
Solar/Wind Helper
0.058
24721905FLATG4
Adder
24.08
962771AG1-126 GEN
Solar/Wind Harmer
30.328
970153AG2-106 GEN
Solar/Wind Harmer
19.366
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.832
253370AE2-315 SEC1
Adder
1.947
253371AE2-315 SEC2
Adder
1.842
252519AF1-045_GEN
Solar/Wind Harmer
3.517
25194608D.CRK4
Adder
1.582
946031AF1-268 GEN
Solar/Wind Harmer
6.225
970289AG2-191 GEN
Solar/Wind Harmer
0.717
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.541
24695305TIMB G C
Solar/Wind Harmer
0.545
274811UNIV PK N;7U
Adder
4.553
276806AD2-047 C O1
Solar/Wind Harmer
3.589
274734ELWOOD EC;8P
Adder
14.887
274736ELWOOD EC;9P
Adder
14.887
274676JOLIET 29;8U
Adder
26.795
943121AE2-341 GEN
Solar/Wind Harmer
10.564
943591AF1-030 GEN
Solar/Wind Harmer
7.025
274682WAUKEGAN ;7U
Adder
16.174
270588AE1-091_GEN
Solar/Wind Harmer
4.882
964991AG1-363 GEN
Solar/Wind Helper
4.289
238110AE1-109 GEN3
Solar/Wind Helper
0.103
235063AE1-101 C2
Solar/Wind Helper
1.447
959091AF2-200 GEN
Solar/Wind Harmer
3.185
23684101S70BUS1
50/50
0.295
970879AG2-548 GEN
Solar/Wind Harmer
1.187
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.261
942221AE2-234 GEN
Solar/Wind Harmer
2.621
246937BC-WTG2
Solar/Wind Harmer
0.26
957841AF2-078 GEN
Solar/Wind Harmer
0
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.722
274770LINCOLN ;1U
Adder
7.689
274771LINCOLN ;2U
Adder
7.689
970623AG2-406 GEN
Solar/Wind Harmer
1.161
274805UNIV PK N;1U
Adder
4.563
274888KELLY CRK;1U
Solar/Wind Harmer
0.369
970941AG2-585 GEN
Solar/Wind Harmer
3.484
276897AD1-100 C
Solar/Wind Harmer
15.831
276893AG1-478 C
Solar/Wind Harmer
0.421
970107AG2-081 GEN
Solar/Wind Harmer
1.892
274696ROCKY RD ;4P
Adder
10.261
274697ROCKY RD ;3P
Adder
2.723
962691AG1-118 GEN
Solar/Wind Harmer
18.812
942111AE2-223 GEN
Solar/Wind Harmer
2.036
970621AG2-405 GEN
Solar/Wind Harmer
1.144
23751201ROTHROCK
Solar/Wind Helper
0.855
237061AD1-155 GEN
Solar/Wind Helper
1.53
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.238
316411AF1-147_GEN1
Solar/Wind Helper
0.762
270512AE1-227 GEN2
Solar/Wind Harmer
1.881
971191AH1-055 GEN
Solar/Wind Harmer
18.543
970879AG2-548 GEN
Solar/Wind Harmer
5.224
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.281
972167AH1-666 GEN
Solar/Wind Harmer
5.273
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.813
970825AG2-519 GEN
Solar/Wind Harmer
4.924
270043AE2-236 GEN
Solar/Wind Harmer
4.172
965021AG1-366 GEN
Solar/Wind Harmer
2.164
246938BC-WTG3
Solar/Wind Harmer
0.232
945111AF1-176 GEN
Solar/Wind Harmer
5.168
270505AE1-170 C O1
Solar/Wind Harmer
6.695
274772LINCOLN ;3U
Adder
7.689
274724RIVER EC ;11
Adder
16.119
972259AH1-714 GEN
Adder
17.31
274729ELWOOD EC;1P
Adder
14.887
946671AF1-331 GEN
Solar/Wind Harmer
0.667
274850MENDOTA H;RU
Solar/Wind Harmer
0.073
970571AG2-364 GEN
Solar/Wind Harmer
12.497
237048AF1-022 C
Solar/Wind Helper
0.176
238175AF1-290_GEN
Solar/Wind Helper
0.135
316415AF1-147_GEN2
Solar/Wind Helper
0.762
23684201S70BUS2
50/50
0.3
972269AH1-719 GEN
Adder
2.288
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.051
25196808ZIMRHP
Adder
72.791
25196008MFTGT1
Adder
1.323
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.84
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.418
970825AG2-519 GEN
Solar/Wind Harmer
2.32
270594AE1-207 GEN
Solar/Wind Harmer
7.308
270032AE2-172
Solar/Wind Harmer
4.35
965011AG1-365 GEN
Solar/Wind Harmer
6.491
246936BC-WTG1
Solar/Wind Harmer
0.26
270489AE1-102 GEN1
Solar/Wind Harmer
0.837
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
8.034
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.629
945111AF1-176 GEN
Solar/Wind Harmer
11.377
274773LINCOLN ;4U
Adder
7.689
274774LINCOLN ;5U
Adder
7.689
274751CRETE EC ;1U
Adder
7.503
274723RIVER EC ;12
Adder
16.309
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.293
939741AE1-205 GEN
Solar/Wind Harmer
8.771
970569AG2-363 GEN
Solar/Wind Harmer
18.746
23583801GRNGAP
Solar/Wind Helper
4.978
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.438
23559101PLEAS2
50/50
11.898
23562301OGROV1
50/50
2.293
970149AG2-104 GEN
Solar/Wind Harmer
16.378
960001AF2-291 GEN
Solar/Wind Harmer
0
270510AE1-227 GEN1
Solar/Wind Harmer
1.881
971073AG2-665 GEN
Solar/Wind Harmer
1.187
970773AG2-487 GEN
Solar/Wind Harmer
1.155
970091AG2-072 GEN
Adder
71.643
971917AH1-482 GEN
Solar/Wind Harmer
8.351
970373AG2-245 GEN
Solar/Wind Harmer
13.48
963741AG1-226 GEN
Solar/Wind Harmer
15.1
943021AE2-325 GEN
Solar/Wind Harmer
3.32
941551AE2-152 GEN
Solar/Wind Harmer
0
944971AF1-162 GEN
Solar/Wind Harmer
6.303
276691AA1-018 GEN1
Solar/Wind Harmer
1.023
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.732
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.078
237038AE2-054 C
Solar/Wind Helper
0.237
959081AF2-199 GEN
Solar/Wind Harmer
1.593
971067AG2-660 GEN
Solar/Wind Harmer
0.531
965651AG1-433 GEN
Solar/Wind Harmer
1.923
270024AE2-089 GEN
Solar/Wind Harmer
0.001
965421AG1-410 GEN
Solar/Wind Harmer
19.339
24728605AND G2
Adder
3.541
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.141
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.553
274676JOLIET 29;8U
Adder
27.787
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.047
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
1.991
23751101LEADS_P59
Solar/Wind Helper
2.413
316095T157 G97
Solar/Wind Helper
1.331
238185AF2-356 C
Solar/Wind Helper
2.499
238120AE2-309 GEN
Solar/Wind Helper
0.489
238109AE1-109 GEN2
Solar/Wind Helper
0.103
23777801MSM_W1-116
Solar/Wind Helper
0.1
957471AF2-041 GEN
Solar/Wind Harmer
4.778
23559001PLEAS1
50/50
11.898
23562401OGROV2
50/50
2.273
961921AG1-034 GEN
Solar/Wind Harmer
6.37
942051AE2-217 GEN
Solar/Wind Harmer
12.608
270391AF1-285 GEN3
Solar/Wind Harmer
0.452
252507AC2-088 GEN
Solar/Wind Harmer
0.304
25196608WSDLE5
Adder
8.25
958171AF2-111 GEN
Solar/Wind Harmer
16.473
944531AF1-118 GEN
Solar/Wind Harmer
29.414
971347AH1-153 GEN
Solar/Wind Harmer
3.227
24728705AND G3
Adder
7.406
970781AG2-491 GEN
Solar/Wind Harmer
6.424
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.503
274887GEN-1.85
Solar/Wind Harmer
0.165
970193AG2-126 GEN
Solar/Wind Harmer
9.501
274826FISK ;BP
Adder
9.937
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.679
274730ELWOOD EC;6P
Adder
14.887
274862TOP CROP ;2U
Solar/Wind Harmer
0.85
276868AE1-113 GEN
Solar/Wind Harmer
1.255
274879MINONK ;1U
Solar/Wind Harmer
0.262
959611AF2-252 GEN
Solar/Wind Harmer
2.083
237006AB1-125 GEN
Solar/Wind Helper
0.107
962761AG1-125 GEN
Solar/Wind Harmer
30.328
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.726
24686505CER G6
Adder
8.358
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.064
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.272
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.503
274802UNIV PARK;5U
Adder
5.293
274732ELWOOD EC;7P
Adder
14.887
274674JOLIET 9 ;6U
Adder
13.943
939401AE1-172 GEN
Solar/Wind Harmer
4.718
962781AG1-127 GEN
Solar/Wind Harmer
5.964
235067AD1-061 GEN
Solar/Wind Helper
0.388
237002AB1-128_GEN
Solar/Wind Helper
0.386
24318805MLG1
50/50
6.603
24686405CER G5
Adder
8.292
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.572
970191AG2-125 GEN
Solar/Wind Harmer
1.734
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.418
270491AE1-102 GEN2
Solar/Wind Harmer
0.837
971199AH1-059 GEN
Solar/Wind Harmer
1.349
24690905MDL-1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.503
274814UNIV PK N;0U
Adder
4.593
274807UNIV PK N;3U
Adder
4.583
274803UNIV PARK;6U
Adder
5.293
276843GEN-1.7
Solar/Wind Harmer
0.205
972038AH1-567 GEN2
Adder
0.331
965091AG1-374 GEN
Solar/Wind Harmer
18.751
23562501BACKB
Solar/Wind Helper
1.049
238108AE1-109 GEN1
Solar/Wind Helper
0.103
237001AB1-127_GEN
Solar/Wind Helper
0.384
274855GSG-6 ;RU
Solar/Wind Harmer
0.228
238127S14_GEN_2
Solar/Wind Helper
0.769
238152AF2-075_GEN
Solar/Wind Helper
0.617
23777901MDS_W4-102
Solar/Wind Helper
0.153
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
17.38
941391AE2-136 GEN
Solar/Wind Harmer
9.79
25196408WSDLE3
Adder
8.492
25196308WSDLE2
Adder
8.418
25196208WSDLE1
Adder
8.397
25196708WSDLE6
Adder
8.376
25196108MFTGT2
Adder
1.458
25196108MFTGT2
Adder
1.354
270543AE2-219 C
Solar/Wind Harmer
4.599
24729505KEY G4
Adder
6.101
270071AF1-092 GEN
Solar/Wind Harmer
12.517
270435AC2-044 GEN
Solar/Wind Harmer
0.816
24691005MDL-2G C
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0
971771AH1-392 GEN
Solar/Wind Harmer
6.4
274728ELWOOD EC;5P
Adder
14.887
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.094
276861AD2-134 GEN
Solar/Wind Harmer
0.111
276863AD2-134 GEN
Solar/Wind Harmer
0.111
972163AH1-664 GEN
Solar/Wind Harmer
7.323
964611AG1-324 GEN
Solar/Wind Harmer
2.551
270356AE2-297 GEN
Solar/Wind Harmer
0
971609AH1-304 GEN
Solar/Wind Harmer
1.067
959331AF2-224 GEN
Solar/Wind Harmer
4.543
965041AG1-368 GEN
Solar/Wind Harmer
6.455
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.771
274776LINCOLN ;7U
Adder
7.689
274687WILL CNTY;4U
Adder
25.315
274687WILL CNTY;4U
Adder
25.315
274731ELWOOD EC;2P
Adder
14.887
274733ELWOOD EC;3P
Adder
14.887
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
14.066
274746AC1-111 G10
Adder
5.047
276726Z2-087_GEN
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.063
274854TWINGROVE;U2
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.32
23750501ELLIOTTS
Solar/Wind Helper
0.64
23779801AA1-109
Solar/Wind Helper
0.168
3138216PACIFIC
Solar/Wind Helper
0.038
CPLELTFEXP_CPLE->PJM
CLTF
1.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
104.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
125.509
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.61
MECLTFEXP_MEC->PJM
CLTF
14.364
SIGELTFEXP_SIGE->PJM
CLTF
0.464
NYPJM->LTFIMP_NY
CLTF
4.529
LGEELTFEXP_LGEE->PJM
CLTF
6.23
WECLTFEXP_WEC->PJM
CLTF
3.411
AG2-052LTFEXP_AG2-052->PJM
LTF
0.213
AH1-155LTFEXP_AH1-155->PJM
LTF
0.319
LAGNLTFEXP_LAGN->PJM
CLTF
14.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.869
TVALTFEXP_TVA->PJM
CLTF
6.974

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.19 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5278.17
MW Contribution:
10.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270291AC1-194 GEN
Solar/Wind Harmer
5.101
971985AH1-537 GEN
Solar/Wind Harmer
17.539
253406AD2-031_GEN
Solar/Wind Harmer
1.227
270224U2-072_GEN2
Solar/Wind Harmer
1.87
972165AH1-665 GEN
Solar/Wind Harmer
7.409
971029AG2-637 GEN
Solar/Wind Harmer
13.858
247536S-71 GEN
Solar/Wind Harmer
3.723
945581AF1-223 GEN
Solar/Wind Harmer
4.167
961761AG1-017 GEN
Solar/Wind Harmer
0.393
965051AG1-369 GEN
Solar/Wind Harmer
4.516
339216AC1-074 GEN
Solar/Wind Harmer
1.512
274775LINCOLN ;6U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
972228AH1-698 GEN2
Adder
3.29
23750701CROSSCHOOL
Solar/Wind Helper
1.155
970935AG2-582 GEN
50/50
1217.29
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
3.664
270471AD2-092_GEN
Solar/Wind Harmer
3.664
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253383AE2-342_GEN
Solar/Wind Harmer
0.868
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
247621Y3-024
Adder
0.222
970291AG2-192 GEN
Solar/Wind Harmer
1.189
970291AG2-192 GEN
Solar/Wind Harmer
0.383
270246TR4_N_V150
Solar/Wind Harmer
0.769
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
237080AD1-060 GEN
Solar/Wind Helper
0.284
927014AC1-188 GEN
Solar/Wind Harmer
1.603
971073AG2-665 GEN
Solar/Wind Harmer
8.039
946101AF1-275 GEN
Solar/Wind Harmer
1.513
270269AC2-059
Solar/Wind Harmer
9.305
942861AE2-305 GEN
Solar/Wind Harmer
7.636
972159AH1-661 GEN
Adder
0.953
241955AC1-078 GEN
Solar/Wind Harmer
7.382
253343AC1-166 GEN
Solar/Wind Harmer
1.063
241973AD2-163_GEN1
Solar/Wind Harmer
1.941
241974AD2-163_GEN2
Solar/Wind Harmer
1.941
943861AF1-054 GEN
Solar/Wind Harmer
3.769
943851AF1-053 GEN
Solar/Wind Harmer
1.821
253433AC1-085 GEN1
Solar/Wind Harmer
5.075
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270227U2-072_GEN3
Solar/Wind Harmer
1.87
270228U2-072_GEN4
Solar/Wind Harmer
1.87
270231U2-072_GEN5
Solar/Wind Harmer
1.87
270302AB2-170 GEN
Solar/Wind Harmer
7.829
970289AG2-191 GEN
Solar/Wind Harmer
1.738
963791AG1-232 GEN
Solar/Wind Harmer
12.295
247521TR3_G114
Solar/Wind Harmer
3.039
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274735ELWOOD EC;4P
Adder
14.566
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
35.004
970153AG2-106 GEN
Solar/Wind Harmer
15.264
270284AF1-227 GEN1
Solar/Wind Harmer
5.566
253317AC1-085 GEN4
Solar/Wind Harmer
7.996
946181AF1-283 GEN
Solar/Wind Harmer
12.416
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.908
23684101S70BUS1
50/50
0.309
970879AG2-548 GEN
Solar/Wind Harmer
1.168
962581AG1-107 GEN
Solar/Wind Harmer
4.832
270512AE1-227 GEN2
Solar/Wind Harmer
2.247
971191AH1-055 GEN
Solar/Wind Harmer
19.037
970879AG2-548 GEN
Solar/Wind Harmer
8.039
960801AF2-371 GEN
Solar/Wind Harmer
2.536
964871AG1-351 GEN
Solar/Wind Harmer
1.751
270367AC2-061_GEN
Solar/Wind Harmer
3.046
253394AE2-221_GEN
Solar/Wind Harmer
4.334
270186AC1-089 GEN
Solar/Wind Harmer
5.821
23684201S70BUS2
50/50
0.315
270331AC1-082 GEN3
Solar/Wind Harmer
0.491
972269AH1-719 GEN
Adder
2.27
253398AE2-221_GEN2
Solar/Wind Harmer
4.334
252510AF1-249 C
Solar/Wind Harmer
0.394
25196808ZIMRHP
Adder
71.417
270485AE1-090_GEN
Solar/Wind Harmer
0.565
25196008MFTGT1
Adder
1.297
942081AE2-220 GEN
Solar/Wind Harmer
5.889
270209AC1-174_GEN
Solar/Wind Harmer
3.747
270239V3-007_GEN1
Solar/Wind Harmer
1.584
958861AF2-177 GEN
Solar/Wind Harmer
10.045
945371AF1-202 GEN
Solar/Wind Harmer
6.41
270005AE1-210 C O1
Solar/Wind Harmer
5.017
970825AG2-519 GEN
Solar/Wind Harmer
1.925
270594AE1-207 GEN
Solar/Wind Harmer
12.433
270032AE2-172
Solar/Wind Harmer
4.258
965011AG1-365 GEN
Solar/Wind Harmer
9.086
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
23583801GRNGAP
Solar/Wind Helper
4.857
237085AD2-009_GEN
Solar/Wind Helper
1.37
238126S14_GEN_1
Solar/Wind Helper
0.641
940581AE2-045 GEN
Solar/Wind Harmer
5.47
971605AH1-302 GEN
Solar/Wind Harmer
4.677
23559101PLEAS2
50/50
11.247
23562301OGROV1
50/50
2.436
970149AG2-104 GEN
Solar/Wind Harmer
21.615
270510AE1-227 GEN1
Solar/Wind Harmer
2.647
960001AF2-291 GEN
Solar/Wind Harmer
3.156
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270286AF1-227 GEN2
Solar/Wind Harmer
2.059
270578AF1-285 GEN2
Solar/Wind Harmer
1.145
270222AC2-111 GEN
Solar/Wind Harmer
4.163
970091AG2-072 GEN
Adder
70.262
339221AD2-048_GEN
Solar/Wind Harmer
1.388
23546401DTGZ2-030
Solar/Wind Helper
0.075
237038AE2-054 C
Solar/Wind Helper
0.227
961491AF2-440 GEN
Solar/Wind Harmer
2.008
253378AE2-206_GEN
Solar/Wind Harmer
3.383
25326509SID D
Adder
1.233
942221AE2-234 GEN
Solar/Wind Harmer
3.201
957841AF2-078 GEN
Solar/Wind Harmer
5.454
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
253371AE2-315 SEC2
Adder
1.805
960071AF2-298 GEN
Solar/Wind Harmer
1.437
252519AF1-045_GEN
Solar/Wind Harmer
3.45
252524AE2-267 GEN
Solar/Wind Harmer
1.486
25194608D.CRK4
Adder
1.552
276820AF1-078_GEN
Solar/Wind Harmer
1.503
970155AG2-107 GEN
Solar/Wind Harmer
15.264
972203AH1-686 GEN
Adder
2.3
24723205RIVRG3
Adder
18.491
253316AC1-085 GEN3
Solar/Wind Harmer
7.996
946171AF1-282 GEN
Solar/Wind Harmer
9.551
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252516AE2-318_GEN
Solar/Wind Harmer
9.479
25194608D.CRK4
Adder
1.552
945681AF1-233 GEN
Solar/Wind Harmer
17.484
965651AG1-433 GEN
Solar/Wind Harmer
5.023
971995AH1-542 GEN
Solar/Wind Harmer
10.104
270024AE2-089 GEN
Solar/Wind Harmer
4.289
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
27.057
24639705ELKHART HY
Adder
0.138
274812UNIV PK N;8U
Adder
4.454
316095T157 G97
Solar/Wind Helper
1.299
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
238120AE2-309 GEN
Solar/Wind Helper
0.408
23777801MSM_W1-116
Solar/Wind Helper
0.096
270054AF2-122 C O1
Solar/Wind Harmer
3.288
253415AE1-040 GEN
Solar/Wind Harmer
1.098
253349AC2-067 GEN
Solar/Wind Harmer
1.925
938701AE1-092 GEN
Solar/Wind Harmer
19.541
25194408D.CRK1
Adder
7.139
270462AD2-086
Solar/Wind Harmer
6.502
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
9.219
926881AC1-175 GEN
Solar/Wind Harmer
5.139
960971AF2-388 GEN
Solar/Wind Harmer
10.047
270599AE1-208 GEN
Solar/Wind Harmer
7.466
24725505WLD G2 C
Solar/Wind Harmer
3.633
270247TR4_N_V136
Solar/Wind Harmer
0.769
970349AG2-230 GEN
Solar/Wind Harmer
13.564
274808UNIV PK N;4U
Adder
4.435
238148AE2-230_GEN2
Solar/Wind Helper
0.416
235062AE1-101 C1
Solar/Wind Helper
1.383
238117U2-030
Solar/Wind Helper
0.26
962761AG1-125 GEN
Solar/Wind Harmer
35.004
270520AE2-214 GEN
Solar/Wind Harmer
6.054
270273AD2-016 GEN
Solar/Wind Harmer
2.653
24686505CER G6
Adder
8.25
253333AC1-068 GEN
Solar/Wind Harmer
1.025
25326309TAIT D
Adder
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
1.145
270317AD1-130_GEN
Solar/Wind Harmer
2.993
944031AF1-071 GEN
Solar/Wind Harmer
0.937
270437AC2-090 C
Solar/Wind Harmer
5.139
276903AD2-071 C
Solar/Wind Harmer
9.138
274754CRETE EC ;4U
Adder
7.339
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
235067AD1-061 GEN
Solar/Wind Helper
0.371
237002AB1-128_GEN
Solar/Wind Helper
0.369
24318805MLG1
50/50
6.319
270329AC1-082 GEN1
Solar/Wind Harmer
0.49
24686405CER G5
Adder
8.185
253325AC1-069 GEN
Solar/Wind Harmer
1.025
270518AE2-148 GEN
Solar/Wind Harmer
11.818
24379505HDWTR1G C
Solar/Wind Harmer
7.281
270004AE1-209 GEN
Solar/Wind Harmer
5.017
339243AC2-075 GEN1
Solar/Wind Harmer
0.41
274753CRETE EC ;3U
Adder
7.339
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274803UNIV PARK;6U
Adder
5.179
972038AH1-567 GEN2
Adder
0.324
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237001AB1-127_GEN
Solar/Wind Helper
0.369
25326109MON D
Adder
1.253
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
270330AC1-082 GEN2
Solar/Wind Harmer
0.49
957541AF2-048 GEN
Solar/Wind Harmer
1.603
961921AG1-034 GEN
Solar/Wind Harmer
12.743
270287AF1-227 GEN3
Solar/Wind Harmer
2.059
942051AE2-217 GEN
Solar/Wind Harmer
17.671
252507AC2-088 GEN
Solar/Wind Harmer
1.699
942871AE2-306 GEN
Solar/Wind Harmer
0.859
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
25196608WSDLE5
Adder
8.09
958171AF2-111 GEN
Solar/Wind Harmer
23.182
944531AF1-118 GEN
Solar/Wind Harmer
32.194
24728705AND G3
Adder
7.256
971347AH1-153 GEN
Solar/Wind Harmer
4.521
274752CRETE EC ;2U
Adder
7.339
274826FISK ;BP
Adder
9.721
274730ELWOOD EC;6P
Adder
14.566
25183208HLCRTG
Solar/Wind Harmer
5.747
252509AD1-136 GEN
Solar/Wind Harmer
0.243
253400AC2-068 GEN
Solar/Wind Harmer
0.774
25194508D.CRK3
Adder
1.335
24728805RICHG1
Adder
3.492
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
5.623
944541AF1-119 GEN
Solar/Wind Harmer
3.848
270201AC2-176 GEN
Solar/Wind Harmer
4.716
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
7.466
24699105WLD G1 C
Solar/Wind Harmer
3.591
945421AF1-207 GEN
Solar/Wind Harmer
12.67
247620Y3-023
Adder
0.413
238149AF1-291A_GEN
Solar/Wind Helper
0.119
235531U2-073 GEN
Solar/Wind Helper
2.544
238152AF2-075_GEN
Solar/Wind Helper
0.595
23777901MDS_W4-102
Solar/Wind Helper
0.147
238127S14_GEN_2
Solar/Wind Helper
0.641
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
7.423
270240V3-007_GEN2
Solar/Wind Harmer
5.697
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
970825AG2-519 GEN
Solar/Wind Harmer
5.167
965461AG1-414 GEN
Solar/Wind Harmer
2.074
270043AE2-236 GEN
Solar/Wind Harmer
5.008
965021AG1-366 GEN
Solar/Wind Harmer
2.113
274772LINCOLN ;3U
Adder
7.522
274724RIVER EC ;11
Adder
15.767
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
238175AF1-290_GEN
Solar/Wind Helper
0.13
946031AF1-268 GEN
Solar/Wind Harmer
7.618
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.058
24728505AND G1
Adder
3.47
274811UNIV PK N;7U
Adder
4.454
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
964991AG1-363 GEN
Solar/Wind Helper
4.131
238110AE1-109 GEN3
Solar/Wind Helper
0.088
235063AE1-101 C2
Solar/Wind Helper
1.383
940611AE2-048 GEN
Solar/Wind Harmer
22.073
941391AE2-136 GEN
Solar/Wind Harmer
11.438
270459AD2-067 GEN
Solar/Wind Harmer
8.368
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
270543AE2-219 C
Solar/Wind Harmer
9.219
24729505KEY G4
Adder
5.966
958711AF2-162 GEN
Solar/Wind Harmer
0.93
270071AF1-092 GEN
Solar/Wind Harmer
13.725
274728ELWOOD EC;5P
Adder
14.566
961821AG1-024 GEN
Solar/Wind Harmer
8.496
270432AC2-029 GEN
Solar/Wind Harmer
6.989
270263AC1-001 GEN
Solar/Wind Harmer
1.042
945631AF1-228 GEN
Solar/Wind Harmer
4.627
253338AC1-165 GEN
Solar/Wind Harmer
1.063
270340AC2-060 GEN
Solar/Wind Harmer
2.956
241972AD1-140 GEN
Solar/Wind Harmer
4.312
270223U2-072_GEN1
Solar/Wind Harmer
1.87
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196508WSDLE4
Adder
8.008
972163AH1-664 GEN
Solar/Wind Harmer
9.262
270356AE2-297 GEN
Solar/Wind Harmer
4.233
964611AG1-324 GEN
Solar/Wind Harmer
3.579
959331AF2-224 GEN
Solar/Wind Harmer
9.086
270191TR4_S_V150
Solar/Wind Harmer
2.712
965041AG1-368 GEN
Solar/Wind Harmer
9.035
274776LINCOLN ;7U
Adder
7.522
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.17 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5277.43
MW Contribution:
10.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270291AC1-194 GEN
Solar/Wind Harmer
5.101
971985AH1-537 GEN
Solar/Wind Harmer
17.539
253406AD2-031_GEN
Solar/Wind Harmer
1.227
270224U2-072_GEN2
Solar/Wind Harmer
1.87
972165AH1-665 GEN
Solar/Wind Harmer
7.409
971029AG2-637 GEN
Solar/Wind Harmer
13.858
247536S-71 GEN
Solar/Wind Harmer
3.723
970935AG2-582 GEN
50/50
1217.29
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
3.664
270471AD2-092_GEN
Solar/Wind Harmer
3.664
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253383AE2-342_GEN
Solar/Wind Harmer
0.868
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
247621Y3-024
Adder
0.222
970291AG2-192 GEN
Solar/Wind Harmer
1.189
970291AG2-192 GEN
Solar/Wind Harmer
0.383
270246TR4_N_V150
Solar/Wind Harmer
0.769
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
237080AD1-060 GEN
Solar/Wind Helper
0.284
241955AC1-078 GEN
Solar/Wind Harmer
7.382
253343AC1-166 GEN
Solar/Wind Harmer
1.063
241973AD2-163_GEN1
Solar/Wind Harmer
1.941
241974AD2-163_GEN2
Solar/Wind Harmer
1.941
943861AF1-054 GEN
Solar/Wind Harmer
3.769
943851AF1-053 GEN
Solar/Wind Harmer
1.821
253433AC1-085 GEN1
Solar/Wind Harmer
5.075
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270227U2-072_GEN3
Solar/Wind Harmer
1.87
23684201S70BUS2
50/50
0.315
270331AC1-082 GEN3
Solar/Wind Harmer
0.491
972269AH1-719 GEN
Adder
2.27
253398AE2-221_GEN2
Solar/Wind Harmer
4.334
252510AF1-249 C
Solar/Wind Harmer
0.394
25196808ZIMRHP
Adder
71.417
270485AE1-090_GEN
Solar/Wind Harmer
0.565
25196008MFTGT1
Adder
1.297
942081AE2-220 GEN
Solar/Wind Harmer
5.889
270209AC1-174_GEN
Solar/Wind Harmer
3.747
270239V3-007_GEN1
Solar/Wind Harmer
1.584
958861AF2-177 GEN
Solar/Wind Harmer
10.045
945371AF1-202 GEN
Solar/Wind Harmer
6.41
270005AE1-210 C O1
Solar/Wind Harmer
5.017
970825AG2-519 GEN
Solar/Wind Harmer
1.925
270594AE1-207 GEN
Solar/Wind Harmer
12.433
270032AE2-172
Solar/Wind Harmer
4.258
965011AG1-365 GEN
Solar/Wind Harmer
9.086
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
23583801GRNGAP
Solar/Wind Helper
4.857
237085AD2-009_GEN
Solar/Wind Helper
1.37
238126S14_GEN_1
Solar/Wind Helper
0.641
940581AE2-045 GEN
Solar/Wind Harmer
5.47
971605AH1-302 GEN
Solar/Wind Harmer
4.677
23559101PLEAS2
50/50
11.247
23562301OGROV1
50/50
2.436
970149AG2-104 GEN
Solar/Wind Harmer
21.615
270510AE1-227 GEN1
Solar/Wind Harmer
2.647
960001AF2-291 GEN
Solar/Wind Harmer
3.156
971073AG2-665 GEN
Solar/Wind Harmer
1.168
270286AF1-227 GEN2
Solar/Wind Harmer
2.059
270578AF1-285 GEN2
Solar/Wind Harmer
1.145
270222AC2-111 GEN
Solar/Wind Harmer
4.163
970091AG2-072 GEN
Adder
70.262
339221AD2-048_GEN
Solar/Wind Harmer
1.388
23546401DTGZ2-030
Solar/Wind Helper
0.075
237038AE2-054 C
Solar/Wind Helper
0.227
23684101S70BUS1
50/50
0.309
970879AG2-548 GEN
Solar/Wind Harmer
1.168
962581AG1-107 GEN
Solar/Wind Harmer
4.832
961491AF2-440 GEN
Solar/Wind Harmer
2.008
253378AE2-206_GEN
Solar/Wind Harmer
3.383
25326509SID D
Adder
1.233
942221AE2-234 GEN
Solar/Wind Harmer
3.201
957841AF2-078 GEN
Solar/Wind Harmer
5.454
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
970155AG2-107 GEN
Solar/Wind Harmer
15.264
972203AH1-686 GEN
Adder
2.3
24723205RIVRG3
Adder
18.491
253316AC1-085 GEN3
Solar/Wind Harmer
7.996
946171AF1-282 GEN
Solar/Wind Harmer
9.551
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252516AE2-318_GEN
Solar/Wind Harmer
9.479
25194608D.CRK4
Adder
1.552
945681AF1-233 GEN
Solar/Wind Harmer
17.484
965651AG1-433 GEN
Solar/Wind Harmer
5.023
971995AH1-542 GEN
Solar/Wind Harmer
10.104
270024AE2-089 GEN
Solar/Wind Harmer
4.289
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
27.057
24639705ELKHART HY
Adder
0.138
274812UNIV PK N;8U
Adder
4.454
316095T157 G97
Solar/Wind Helper
1.299
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
238120AE2-309 GEN
Solar/Wind Helper
0.408
23777801MSM_W1-116
Solar/Wind Helper
0.096
270054AF2-122 C O1
Solar/Wind Harmer
3.288
253415AE1-040 GEN
Solar/Wind Harmer
1.098
253349AC2-067 GEN
Solar/Wind Harmer
1.925
938701AE1-092 GEN
Solar/Wind Harmer
19.541
25194408D.CRK1
Adder
7.139
270462AD2-086
Solar/Wind Harmer
6.502
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
9.219
926881AC1-175 GEN
Solar/Wind Harmer
5.139
960971AF2-388 GEN
Solar/Wind Harmer
10.047
270599AE1-208 GEN
Solar/Wind Harmer
7.466
24725505WLD G2 C
Solar/Wind Harmer
3.633
270247TR4_N_V136
Solar/Wind Harmer
0.769
970349AG2-230 GEN
Solar/Wind Harmer
13.564
274808UNIV PK N;4U
Adder
4.435
238148AE2-230_GEN2
Solar/Wind Helper
0.416
235062AE1-101 C1
Solar/Wind Helper
1.383
238117U2-030
Solar/Wind Helper
0.26
962761AG1-125 GEN
Solar/Wind Harmer
35.004
270520AE2-214 GEN
Solar/Wind Harmer
6.054
270273AD2-016 GEN
Solar/Wind Harmer
2.653
24686505CER G6
Adder
8.25
253333AC1-068 GEN
Solar/Wind Harmer
1.025
25326309TAIT D
Adder
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
1.145
270317AD1-130_GEN
Solar/Wind Harmer
2.993
944031AF1-071 GEN
Solar/Wind Harmer
0.937
270437AC2-090 C
Solar/Wind Harmer
5.139
276903AD2-071 C
Solar/Wind Harmer
9.138
274754CRETE EC ;4U
Adder
7.339
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
235067AD1-061 GEN
Solar/Wind Helper
0.371
237002AB1-128_GEN
Solar/Wind Helper
0.369
24318805MLG1
50/50
6.319
270329AC1-082 GEN1
Solar/Wind Harmer
0.49
24686405CER G5
Adder
8.185
253325AC1-069 GEN
Solar/Wind Harmer
1.025
270518AE2-148 GEN
Solar/Wind Harmer
11.818
24379505HDWTR1G C
Solar/Wind Harmer
7.281
270004AE1-209 GEN
Solar/Wind Harmer
5.017
339243AC2-075 GEN1
Solar/Wind Harmer
0.41
274753CRETE EC ;3U
Adder
7.339
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274803UNIV PARK;6U
Adder
5.179
972038AH1-567 GEN2
Adder
0.324
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237001AB1-127_GEN
Solar/Wind Helper
0.369
927014AC1-188 GEN
Solar/Wind Harmer
1.603
971073AG2-665 GEN
Solar/Wind Harmer
8.039
946101AF1-275 GEN
Solar/Wind Harmer
1.513
270269AC2-059
Solar/Wind Harmer
9.305
942861AE2-305 GEN
Solar/Wind Harmer
7.636
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
25183208HLCRTG
Solar/Wind Harmer
5.747
252509AD1-136 GEN
Solar/Wind Harmer
0.243
253400AC2-068 GEN
Solar/Wind Harmer
0.774
25194508D.CRK3
Adder
1.335
24728805RICHG1
Adder
3.492
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
5.623
944541AF1-119 GEN
Solar/Wind Harmer
3.848
270201AC2-176 GEN
Solar/Wind Harmer
4.716
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
7.466
24699105WLD G1 C
Solar/Wind Harmer
3.591
945421AF1-207 GEN
Solar/Wind Harmer
12.67
247620Y3-023
Adder
0.413
238149AF1-291A_GEN
Solar/Wind Helper
0.119
235531U2-073 GEN
Solar/Wind Helper
2.544
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
270330AC1-082 GEN2
Solar/Wind Harmer
0.49
957541AF2-048 GEN
Solar/Wind Harmer
1.603
961921AG1-034 GEN
Solar/Wind Harmer
12.743
270287AF1-227 GEN3
Solar/Wind Harmer
2.059
942051AE2-217 GEN
Solar/Wind Harmer
17.671
252507AC2-088 GEN
Solar/Wind Harmer
1.699
942871AE2-306 GEN
Solar/Wind Harmer
0.859
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
25196608WSDLE5
Adder
8.09
958171AF2-111 GEN
Solar/Wind Harmer
23.182
944531AF1-118 GEN
Solar/Wind Harmer
32.194
24728705AND G3
Adder
7.256
971347AH1-153 GEN
Solar/Wind Harmer
4.521
274752CRETE EC ;2U
Adder
7.339
274826FISK ;BP
Adder
9.721
274730ELWOOD EC;6P
Adder
14.566
238152AF2-075_GEN
Solar/Wind Helper
0.595
23777901MDS_W4-102
Solar/Wind Helper
0.147
238127S14_GEN_2
Solar/Wind Helper
0.641
270512AE1-227 GEN2
Solar/Wind Harmer
2.247
971191AH1-055 GEN
Solar/Wind Harmer
19.037
970879AG2-548 GEN
Solar/Wind Harmer
8.039
960801AF2-371 GEN
Solar/Wind Harmer
2.536
964871AG1-351 GEN
Solar/Wind Harmer
1.751
270367AC2-061_GEN
Solar/Wind Harmer
3.046
253394AE2-221_GEN
Solar/Wind Harmer
4.334
270186AC1-089 GEN
Solar/Wind Harmer
5.821
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
7.423
270240V3-007_GEN2
Solar/Wind Harmer
5.697
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
970825AG2-519 GEN
Solar/Wind Harmer
5.167
965461AG1-414 GEN
Solar/Wind Harmer
2.074
270043AE2-236 GEN
Solar/Wind Harmer
5.008
965021AG1-366 GEN
Solar/Wind Harmer
2.113
274772LINCOLN ;3U
Adder
7.522
274724RIVER EC ;11
Adder
15.767
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
238175AF1-290_GEN
Solar/Wind Helper
0.13
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
35.004
970153AG2-106 GEN
Solar/Wind Harmer
15.264
270284AF1-227 GEN1
Solar/Wind Harmer
5.566
253317AC1-085 GEN4
Solar/Wind Harmer
7.996
946181AF1-283 GEN
Solar/Wind Harmer
12.416
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
960071AF2-298 GEN
Solar/Wind Harmer
1.437
945581AF1-223 GEN
Solar/Wind Harmer
4.167
961761AG1-017 GEN
Solar/Wind Harmer
0.393
965051AG1-369 GEN
Solar/Wind Harmer
4.516
339216AC1-074 GEN
Solar/Wind Harmer
1.512
274775LINCOLN ;6U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
972228AH1-698 GEN2
Adder
3.29
23750701CROSSCHOOL
Solar/Wind Helper
1.155
252519AF1-045_GEN
Solar/Wind Harmer
3.45
252524AE2-267 GEN
Solar/Wind Harmer
1.486
25194608D.CRK4
Adder
1.552
276820AF1-078_GEN
Solar/Wind Harmer
1.503
946031AF1-268 GEN
Solar/Wind Harmer
7.618
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.058
24728505AND G1
Adder
3.47
274811UNIV PK N;7U
Adder
4.454
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
964991AG1-363 GEN
Solar/Wind Helper
4.131
238110AE1-109 GEN3
Solar/Wind Helper
0.088
235063AE1-101 C2
Solar/Wind Helper
1.383
270228U2-072_GEN4
Solar/Wind Harmer
1.87
270231U2-072_GEN5
Solar/Wind Harmer
1.87
270302AB2-170 GEN
Solar/Wind Harmer
7.829
970289AG2-191 GEN
Solar/Wind Harmer
1.738
963791AG1-232 GEN
Solar/Wind Harmer
12.295
247521TR3_G114
Solar/Wind Harmer
3.039
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274735ELWOOD EC;4P
Adder
14.566
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
940611AE2-048 GEN
Solar/Wind Harmer
22.073
941391AE2-136 GEN
Solar/Wind Harmer
11.438
270459AD2-067 GEN
Solar/Wind Harmer
8.368
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
270543AE2-219 C
Solar/Wind Harmer
9.219
24729505KEY G4
Adder
5.966
958711AF2-162 GEN
Solar/Wind Harmer
0.93
270071AF1-092 GEN
Solar/Wind Harmer
13.725
274728ELWOOD EC;5P
Adder
14.566
961821AG1-024 GEN
Solar/Wind Harmer
8.496
270432AC2-029 GEN
Solar/Wind Harmer
6.989
270263AC1-001 GEN
Solar/Wind Harmer
1.042
945631AF1-228 GEN
Solar/Wind Harmer
4.627
253338AC1-165 GEN
Solar/Wind Harmer
1.063
270340AC2-060 GEN
Solar/Wind Harmer
2.956
241972AD1-140 GEN
Solar/Wind Harmer
4.312
270223U2-072_GEN1
Solar/Wind Harmer
1.87
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196508WSDLE4
Adder
8.008
972163AH1-664 GEN
Solar/Wind Harmer
9.262
270356AE2-297 GEN
Solar/Wind Harmer
4.233
964611AG1-324 GEN
Solar/Wind Harmer
3.579
959331AF2-224 GEN
Solar/Wind Harmer
9.086
270191TR4_S_V150
Solar/Wind Harmer
2.712
965041AG1-368 GEN
Solar/Wind Harmer
9.035
274776LINCOLN ;7U
Adder
7.522
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.98 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5270.18
MW Contribution:
10.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1216.009
23534401HANNIB
50/50
0.148
24318905MLG2
50/50
4.725
23684201S70BUS2
50/50
0.318
270331AC1-082 GEN3
Solar/Wind Harmer
0.495
972269AH1-719 GEN
Adder
2.296
253398AE2-221_GEN2
Solar/Wind Harmer
4.371
252510AF1-249 C
Solar/Wind Harmer
0.397
25196808ZIMRHP
Adder
72.004
270485AE1-090_GEN
Solar/Wind Harmer
0.571
25196008MFTGT1
Adder
1.308
942081AE2-220 GEN
Solar/Wind Harmer
5.939
270209AC1-174_GEN
Solar/Wind Harmer
3.779
270239V3-007_GEN1
Solar/Wind Harmer
1.598
958861AF2-177 GEN
Solar/Wind Harmer
10.133
945371AF1-202 GEN
Solar/Wind Harmer
6.466
270005AE1-210 C O1
Solar/Wind Harmer
5.06
970825AG2-519 GEN
Solar/Wind Harmer
1.941
270594AE1-207 GEN
Solar/Wind Harmer
12.54
270032AE2-172
Solar/Wind Harmer
4.294
965011AG1-365 GEN
Solar/Wind Harmer
9.171
246936BC-WTG1
Solar/Wind Harmer
3.559
270489AE1-102 GEN1
Solar/Wind Harmer
1.183
274773LINCOLN ;4U
Adder
7.587
274774LINCOLN ;5U
Adder
7.587
274751CRETE EC ;1U
Adder
7.403
274723RIVER EC ;12
Adder
16.092
23583801GRNGAP
Solar/Wind Helper
4.95
237085AD2-009_GEN
Solar/Wind Helper
1.38
23559101PLEAS2
50/50
11.275
23562301OGROV1
50/50
2.457
970149AG2-104 GEN
Solar/Wind Harmer
21.787
270510AE1-227 GEN1
Solar/Wind Harmer
2.681
960001AF2-291 GEN
Solar/Wind Harmer
3.18
971073AG2-665 GEN
Solar/Wind Harmer
1.178
270286AF1-227 GEN2
Solar/Wind Harmer
2.078
270578AF1-285 GEN2
Solar/Wind Harmer
1.157
270222AC2-111 GEN
Solar/Wind Harmer
4.198
970091AG2-072 GEN
Adder
70.821
339221AD2-048_GEN
Solar/Wind Harmer
1.399
23546401DTGZ2-030
Solar/Wind Helper
0.076
237038AE2-054 C
Solar/Wind Helper
0.229
23684101S70BUS1
50/50
0.312
970879AG2-548 GEN
Solar/Wind Harmer
1.178
962581AG1-107 GEN
Solar/Wind Harmer
4.871
961491AF2-440 GEN
Solar/Wind Harmer
2.024
253378AE2-206_GEN
Solar/Wind Harmer
3.414
25326509SID D
Adder
1.244
942221AE2-234 GEN
Solar/Wind Harmer
3.23
246937BC-WTG2
Solar/Wind Harmer
3.559
274770LINCOLN ;1U
Adder
7.587
274771LINCOLN ;2U
Adder
7.587
274805UNIV PK N;1U
Adder
4.503
237061AD1-155 GEN
Solar/Wind Helper
1.5
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.231
316411AF1-147_GEN1
Solar/Wind Helper
0.753
270349AD2-093_GEN
Solar/Wind Harmer
3.698
270471AD2-092_GEN
Solar/Wind Harmer
3.698
253383AE2-342_GEN
Solar/Wind Harmer
0.876
24723005RIVRG1
Adder
18.614
24723105RIVRG2
Adder
18.614
253370AE2-315 SEC1
Adder
1.924
25322209TAIT E
Adder
9.36
25322209TAIT E
Adder
9.149
247621Y3-024
Adder
0.223
970291AG2-192 GEN
Solar/Wind Harmer
1.199
970291AG2-192 GEN
Solar/Wind Harmer
0.386
270246TR4_N_V150
Solar/Wind Harmer
0.776
316097T157 G90
Solar/Wind Helper
1.324
238147AE2-230_GEN1
Solar/Wind Helper
0.423
237080AD1-060 GEN
Solar/Wind Helper
0.287
970155AG2-107 GEN
Solar/Wind Harmer
15.385
972203AH1-686 GEN
Adder
2.316
24723205RIVRG3
Adder
18.614
253316AC1-085 GEN3
Solar/Wind Harmer
8.063
946171AF1-282 GEN
Solar/Wind Harmer
9.631
253370AE2-315 SEC1
Adder
1.924
253371AE2-315 SEC2
Adder
1.82
252516AE2-318_GEN
Solar/Wind Harmer
9.558
25194608D.CRK4
Adder
1.565
945681AF1-233 GEN
Solar/Wind Harmer
17.624
971995AH1-542 GEN
Solar/Wind Harmer
10.211
965651AG1-433 GEN
Solar/Wind Harmer
5.067
270024AE2-089 GEN
Solar/Wind Harmer
4.327
24728605AND G2
Adder
3.499
965421AG1-410 GEN
Solar/Wind Harmer
27.321
24639705ELKHART HY
Adder
0.139
274812UNIV PK N;8U
Adder
4.493
316095T157 G97
Solar/Wind Helper
1.324
238109AE1-109 GEN2
Solar/Wind Helper
0.087
23777801MSM_W1-116
Solar/Wind Helper
0.098
270054AF2-122 C O1
Solar/Wind Harmer
3.319
253415AE1-040 GEN
Solar/Wind Harmer
1.108
938701AE1-092 GEN
Solar/Wind Harmer
19.736
253349AC2-067 GEN
Solar/Wind Harmer
1.941
25194408D.CRK1
Adder
7.198
270462AD2-086
Solar/Wind Harmer
6.566
24728905RICHG2
Adder
3.521
970883AG2-550 GEN
Solar/Wind Harmer
9.298
926881AC1-175 GEN
Solar/Wind Harmer
5.183
960971AF2-388 GEN
Solar/Wind Harmer
10.135
270599AE1-208 GEN
Solar/Wind Harmer
7.53
24725505WLD G2 C
Solar/Wind Harmer
3.664
270247TR4_N_V136
Solar/Wind Harmer
0.776
970349AG2-230 GEN
Solar/Wind Harmer
13.685
274808UNIV PK N;4U
Adder
4.473
238148AE2-230_GEN2
Solar/Wind Helper
0.423
235062AE1-101 C1
Solar/Wind Helper
1.395
237006AB1-125 GEN
Solar/Wind Helper
0.106
962761AG1-125 GEN
Solar/Wind Harmer
35.283
270520AE2-214 GEN
Solar/Wind Harmer
6.11
270273AD2-016 GEN
Solar/Wind Harmer
2.676
24686505CER G6
Adder
8.307
253333AC1-068 GEN
Solar/Wind Harmer
1.034
25326309TAIT D
Adder
1.052
270391AF1-285 GEN3
Solar/Wind Harmer
1.157
270317AD1-130_GEN
Solar/Wind Harmer
3.023
944031AF1-071 GEN
Solar/Wind Harmer
0.945
270437AC2-090 C
Solar/Wind Harmer
5.183
276903AD2-071 C
Solar/Wind Harmer
9.216
274754CRETE EC ;4U
Adder
7.403
274802UNIV PARK;5U
Adder
5.223
274732ELWOOD EC;7P
Adder
14.692
235067AD1-061 GEN
Solar/Wind Helper
0.374
237002AB1-128_GEN
Solar/Wind Helper
0.373
24318805MLG1
50/50
6.371
270329AC1-082 GEN1
Solar/Wind Harmer
0.494
24686405CER G5
Adder
8.242
253325AC1-069 GEN
Solar/Wind Harmer
1.034
270518AE2-148 GEN
Solar/Wind Harmer
11.924
24379505HDWTR1G C
Solar/Wind Harmer
7.343
270004AE1-209 GEN
Solar/Wind Harmer
5.06
971199AH1-059 GEN
Solar/Wind Harmer
1.914
339243AC2-075 GEN1
Solar/Wind Harmer
0.413
270491AE1-102 GEN2
Solar/Wind Harmer
1.183
274753CRETE EC ;3U
Adder
7.403
274814UNIV PK N;0U
Adder
4.532
274807UNIV PK N;3U
Adder
4.522
274803UNIV PARK;6U
Adder
5.223
972038AH1-567 GEN2
Adder
0.327
238108AE1-109 GEN1
Solar/Wind Helper
0.087
237001AB1-127_GEN
Solar/Wind Helper
0.372
927014AC1-188 GEN
Solar/Wind Harmer
1.616
971073AG2-665 GEN
Solar/Wind Harmer
8.107
946101AF1-275 GEN
Solar/Wind Harmer
1.527
270269AC2-059
Solar/Wind Harmer
9.386
942861AE2-305 GEN
Solar/Wind Harmer
7.705
972159AH1-661 GEN
Adder
0.964
25326109MON D
Adder
1.264
25183208HLCRTG
Solar/Wind Harmer
5.795
252509AD1-136 GEN
Solar/Wind Harmer
0.245
253400AC2-068 GEN
Solar/Wind Harmer
0.781
25194508D.CRK3
Adder
1.346
24728805RICHG1
Adder
3.521
970885AG2-551 GEN
Solar/Wind Harmer
2.162
270383AD1-128 GEN
Solar/Wind Harmer
5.671
944541AF1-119 GEN
Solar/Wind Harmer
3.882
270201AC2-176 GEN
Solar/Wind Harmer
4.757
964611AG1-324 GEN
Solar/Wind Harmer
0.484
270031AE2-169
Solar/Wind Harmer
7.53
24699105WLD G1 C
Solar/Wind Harmer
3.622
247620Y3-023
Adder
0.416
238149AF1-291A_GEN
Solar/Wind Helper
0.121
945421AF1-207 GEN
Solar/Wind Harmer
3.67
23559001PLEAS1
50/50
11.275
23562401OGROV2
50/50
2.436
270330AC1-082 GEN2
Solar/Wind Harmer
0.494
957541AF2-048 GEN
Solar/Wind Harmer
1.616
961921AG1-034 GEN
Solar/Wind Harmer
12.865
270287AF1-227 GEN3
Solar/Wind Harmer
2.078
942051AE2-217 GEN
Solar/Wind Harmer
17.832
252507AC2-088 GEN
Solar/Wind Harmer
1.712
942871AE2-306 GEN
Solar/Wind Harmer
0.867
270391AF1-285 GEN3
Solar/Wind Harmer
0.445
25196608WSDLE5
Adder
8.158
958171AF2-111 GEN
Solar/Wind Harmer
23.368
944531AF1-118 GEN
Solar/Wind Harmer
32.478
971347AH1-153 GEN
Solar/Wind Harmer
4.562
24728705AND G3
Adder
7.317
958581AF2-149 GEN
Solar/Wind Harmer
3.901
274752CRETE EC ;2U
Adder
7.403
274826FISK ;BP
Adder
9.806
274730ELWOOD EC;6P
Adder
14.692
238152AF2-075_GEN
Solar/Wind Helper
0.604
23777901MDS_W4-102
Solar/Wind Helper
0.149
270512AE1-227 GEN2
Solar/Wind Harmer
2.276
971191AH1-055 GEN
Solar/Wind Harmer
19.185
970879AG2-548 GEN
Solar/Wind Harmer
8.107
960801AF2-371 GEN
Solar/Wind Harmer
2.559
964871AG1-351 GEN
Solar/Wind Harmer
1.767
270367AC2-061_GEN
Solar/Wind Harmer
3.071
253394AE2-221_GEN
Solar/Wind Harmer
4.371
270186AC1-089 GEN
Solar/Wind Harmer
5.868
25196008MFTGT1
Adder
1.267
972167AH1-666 GEN
Solar/Wind Harmer
7.482
270240V3-007_GEN2
Solar/Wind Harmer
5.745
962031AG1-047 GEN
Solar/Wind Harmer
2.799
957741AF2-068 GEN
Solar/Wind Harmer
13.884
970825AG2-519 GEN
Solar/Wind Harmer
5.212
965461AG1-414 GEN
Solar/Wind Harmer
2.092
270043AE2-236 GEN
Solar/Wind Harmer
5.054
965021AG1-366 GEN
Solar/Wind Harmer
2.133
246938BC-WTG3
Solar/Wind Harmer
3.621
274772LINCOLN ;3U
Adder
7.587
274724RIVER EC ;11
Adder
15.904
972259AH1-714 GEN
Adder
17.082
274729ELWOOD EC;1P
Adder
14.692
238175AF1-290_GEN
Solar/Wind Helper
0.131
316415AF1-147_GEN2
Solar/Wind Helper
0.753
270291AC1-194 GEN
Solar/Wind Harmer
5.145
971985AH1-537 GEN
Solar/Wind Harmer
17.679
253406AD2-031_GEN
Solar/Wind Harmer
1.237
270224U2-072_GEN2
Solar/Wind Harmer
1.888
972165AH1-665 GEN
Solar/Wind Harmer
7.468
971029AG2-637 GEN
Solar/Wind Harmer
13.978
247536S-71 GEN
Solar/Wind Harmer
3.755
945581AF1-223 GEN
Solar/Wind Harmer
4.203
961761AG1-017 GEN
Solar/Wind Harmer
0.396
965051AG1-369 GEN
Solar/Wind Harmer
4.559
339216AC1-074 GEN
Solar/Wind Harmer
1.524
274775LINCOLN ;6U
Adder
7.587
274777LINCOLN ;8U
Adder
7.587
972037AH1-567 GEN1
Adder
0.164
972228AH1-698 GEN2
Adder
3.318
23750701CROSSCHOOL
Solar/Wind Helper
1.115
24721905FLATG4
Adder
23.616
962771AG1-126 GEN
Solar/Wind Harmer
35.283
970153AG2-106 GEN
Solar/Wind Harmer
15.385
270284AF1-227 GEN1
Solar/Wind Harmer
5.618
253317AC1-085 GEN4
Solar/Wind Harmer
8.063
946181AF1-283 GEN
Solar/Wind Harmer
12.52
253303V4-073 C
Solar/Wind Harmer
0.111
253370AE2-315 SEC1
Adder
1.924
253371AE2-315 SEC2
Adder
1.82
960071AF2-298 GEN
Solar/Wind Harmer
1.449
252519AF1-045_GEN
Solar/Wind Harmer
3.479
252524AE2-267 GEN
Solar/Wind Harmer
1.499
25194608D.CRK4
Adder
1.565
276820AF1-078_GEN
Solar/Wind Harmer
1.517
946031AF1-268 GEN
Solar/Wind Harmer
7.684
970289AG2-191 GEN
Solar/Wind Harmer
0.708
247642Z2-115 C
Solar/Wind Harmer
0.059
24728505AND G1
Adder
3.499
274811UNIV PK N;7U
Adder
4.493
274734ELWOOD EC;8P
Adder
14.692
964991AG1-363 GEN
Solar/Wind Helper
4.19
238110AE1-109 GEN3
Solar/Wind Helper
0.087
235063AE1-101 C2
Solar/Wind Helper
1.395
241955AC1-078 GEN
Solar/Wind Harmer
7.45
253343AC1-166 GEN
Solar/Wind Harmer
1.072
241973AD2-163_GEN1
Solar/Wind Harmer
1.959
241974AD2-163_GEN2
Solar/Wind Harmer
1.959
943861AF1-054 GEN
Solar/Wind Harmer
3.803
943851AF1-053 GEN
Solar/Wind Harmer
1.838
253433AC1-085 GEN1
Solar/Wind Harmer
5.118
253432AC1-085 GEN2
Solar/Wind Harmer
0.258
253372AE2-315 SEC3
Adder
1.82
253372AE2-315 SEC3
Adder
1.82
25306009OHH W.
Adder
2.761
270227U2-072_GEN3
Solar/Wind Harmer
1.888
270228U2-072_GEN4
Solar/Wind Harmer
1.888
270231U2-072_GEN5
Solar/Wind Harmer
1.888
270302AB2-170 GEN
Solar/Wind Harmer
7.906
970289AG2-191 GEN
Solar/Wind Harmer
1.753
963791AG1-232 GEN
Solar/Wind Harmer
12.407
247521TR3_G114
Solar/Wind Harmer
3.068
957201AF2-014 GEN
Solar/Wind Harmer
4.127
972227AH1-698 GEN1
Adder
2.336
274827FISK ;RP
Adder
6.949
274800UNIV PARK;3U
Adder
5.222
274801UNIV PARK;4U
Adder
5.222
274735ELWOOD EC;4P
Adder
11.662
238169AE2-226 GEN1
Solar/Wind Helper
0.593
238170AE2-226 GEN2
Solar/Wind Helper
0.593
237030AB1-096 C
Solar/Wind Helper
0.057
237025AB1-124 C
Solar/Wind Helper
0.141
940611AE2-048 GEN
Solar/Wind Harmer
22.313
941391AE2-136 GEN
Solar/Wind Harmer
11.562
270459AD2-067 GEN
Solar/Wind Harmer
8.448
25196408WSDLE3
Adder
8.398
25196308WSDLE2
Adder
8.325
25196208WSDLE1
Adder
8.304
25196708WSDLE6
Adder
8.283
25196108MFTGT2
Adder
1.442
25196108MFTGT2
Adder
1.339
270543AE2-219 C
Solar/Wind Harmer
9.298
24729505KEY G4
Adder
6.019
958711AF2-162 GEN
Solar/Wind Harmer
0.938
270071AF1-092 GEN
Solar/Wind Harmer
13.847
270435AC2-044 GEN
Solar/Wind Harmer
1.82
274728ELWOOD EC;5P
Adder
14.692
961821AG1-024 GEN
Solar/Wind Harmer
8.577
270432AC2-029 GEN
Solar/Wind Harmer
7.05
270263AC1-001 GEN
Solar/Wind Harmer
1.051
945631AF1-228 GEN
Solar/Wind Harmer
4.669
253338AC1-165 GEN
Solar/Wind Harmer
1.072
270340AC2-060 GEN
Solar/Wind Harmer
2.981
241972AD1-140 GEN
Solar/Wind Harmer
4.35
270223U2-072_GEN1
Solar/Wind Harmer
1.888
270578AF1-285 GEN2
Solar/Wind Harmer
0.445
25196508WSDLE4
Adder
8.074
972163AH1-664 GEN
Solar/Wind Harmer
9.335
270356AE2-297 GEN
Solar/Wind Harmer
4.269
964611AG1-324 GEN
Solar/Wind Harmer
3.61
959331AF2-224 GEN
Solar/Wind Harmer
9.171
270191TR4_S_V150
Solar/Wind Harmer
2.738
965041AG1-368 GEN
Solar/Wind Harmer
9.12
274776LINCOLN ;7U
Adder
7.587
274687WILL CNTY;4U
Adder
24.982
274687WILL CNTY;4U
Adder
24.982
941621AE2-160 GEN
Adder
2.939
274731ELWOOD EC;2P
Adder
14.692
274733ELWOOD EC;3P
Adder
14.692
23779801AA1-109
Solar/Wind Helper
0.164
3138216PACIFIC
Solar/Wind Helper
0.037
CPLELTFEXP_CPLE->PJM
CLTF
1.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
103.644
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.892
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.394
MECLTFEXP_MEC->PJM
CLTF
14.194
SIGELTFEXP_SIGE->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
4.427
LGEELTFEXP_LGEE->PJM
CLTF
6.165
WECLTFEXP_WEC->PJM
CLTF
3.367
AG2-052LTFEXP_AG2-052->PJM
LTF
0.21
AH1-155LTFEXP_AH1-155->PJM
LTF
0.315
LAGNLTFEXP_LAGN->PJM
CLTF
13.935
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.915
TVALTFEXP_TVA->PJM
CLTF
6.925

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5250.02
MW Contribution:
2.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23684201S70BUS2
50/50
0.315
972269AH1-719 GEN
Adder
2.27
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.05
25196808ZIMRHP
Adder
71.417
25196008MFTGT1
Adder
1.297
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970825AG2-519 GEN
Solar/Wind Harmer
2.272
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
965011AG1-365 GEN
Solar/Wind Harmer
6.339
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
939741AE1-205 GEN
Solar/Wind Harmer
8.588
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
237085AD2-009_GEN
Solar/Wind Helper
1.37
238126S14_GEN_1
Solar/Wind Helper
0.641
970155AG2-107 GEN
Solar/Wind Harmer
18.85
972203AH1-686 GEN
Adder
2.3
24723205RIVRG3
Adder
18.491
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252516AE2-318_GEN
Solar/Wind Harmer
7.407
25194608D.CRK4
Adder
1.552
945681AF1-233 GEN
Solar/Wind Harmer
12.198
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.138
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.454
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.299
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
238120AE2-309 GEN
Solar/Wind Helper
0.408
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196508WSDLE4
Adder
8.008
972163AH1-664 GEN
Solar/Wind Harmer
7.194
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
959331AF2-224 GEN
Solar/Wind Harmer
4.437
965041AG1-368 GEN
Solar/Wind Harmer
6.303
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
270526AF1-158 GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
Adder
7.522
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971073AG2-665 GEN
Solar/Wind Harmer
5.141
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.328
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
24728805RICHG1
Adder
3.492
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
1.309
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
958011AF2-095 GEN
Solar/Wind Harmer
8.924
958491AF2-143 GEN
Solar/Wind Harmer
9.221
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.119
235531U2-073 GEN
Solar/Wind Helper
2.544
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.602
25194408D.CRK1
Adder
7.139
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.762
270599AE1-208 GEN
Solar/Wind Harmer
5.858
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
966841AG1-555 GEN
Solar/Wind Harmer
0.711
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274808UNIV PK N;4U
Adder
4.435
958481AF2-142 GEN
Solar/Wind Harmer
9.241
944231AF1-091 GEN
Solar/Wind Harmer
14.169
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
238148AE2-230_GEN2
Solar/Wind Helper
0.416
235062AE1-101 C1
Solar/Wind Helper
1.383
238117U2-030
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
961921AG1-034 GEN
Solar/Wind Harmer
6.223
942051AE2-217 GEN
Solar/Wind Harmer
12.329
252507AC2-088 GEN
Solar/Wind Harmer
0.298
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
25196608WSDLE5
Adder
8.09
958171AF2-111 GEN
Solar/Wind Harmer
16.173
944531AF1-118 GEN
Solar/Wind Harmer
28.761
24728705AND G3
Adder
7.256
971347AH1-153 GEN
Solar/Wind Harmer
3.154
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.339
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274887GEN-1.85
Solar/Wind Harmer
0.161
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
970707AG2-453 GEN
Solar/Wind Harmer
20.232
274730ELWOOD EC;6P
Adder
14.566
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
959611AF2-252 GEN
Solar/Wind Harmer
2.04
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
238152AF2-075_GEN
Solar/Wind Helper
0.595
23777901MDS_W4-102
Solar/Wind Helper
0.147
238127S14_GEN_2
Solar/Wind Helper
0.641
23684101S70BUS1
50/50
0.309
970879AG2-548 GEN
Solar/Wind Harmer
1.168
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.233
942221AE2-234 GEN
Solar/Wind Harmer
2.563
957841AF2-078 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
246938BC-WTG3
Solar/Wind Harmer
0.226
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274724RIVER EC ;11
Adder
15.767
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
238175AF1-290_GEN
Solar/Wind Helper
0.13
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252519AF1-045_GEN
Solar/Wind Harmer
3.45
25194608D.CRK4
Adder
1.552
946031AF1-268 GEN
Solar/Wind Harmer
6.094
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.47
24695305TIMB G C
Solar/Wind Harmer
0.532
274811UNIV PK N;7U
Adder
4.454
276806AD2-047 C O1
Solar/Wind Harmer
3.512
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
964991AG1-363 GEN
Solar/Wind Helper
4.131
238110AE1-109 GEN3
Solar/Wind Helper
0.088
235063AE1-101 C2
Solar/Wind Helper
1.383
959091AF2-200 GEN
Solar/Wind Harmer
2.06
970935AG2-582 GEN
50/50
1217.29
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
971655AH1-328 GEN
Solar/Wind Harmer
2.343
247621Y3-024
Adder
0.222
971613AH1-306 GEN
Solar/Wind Harmer
3.066
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
270246TR4_N_V150
Solar/Wind Harmer
0.04
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.827
971587AH1-292 GEN
Solar/Wind Harmer
4.565
971125AH1-004 GEN
Solar/Wind Harmer
2.48
276776AD2-060 GEN
Solar/Wind Harmer
0.661
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
237080AD1-060 GEN
Solar/Wind Helper
0.284
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
23559101PLEAS2
50/50
11.247
23562301OGROV1
50/50
2.436
970149AG2-104 GEN
Solar/Wind Harmer
15.941
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970091AG2-072 GEN
Adder
70.262
971917AH1-482 GEN
Solar/Wind Harmer
8.17
970373AG2-245 GEN
Solar/Wind Harmer
13.183
944971AF1-162 GEN
Solar/Wind Harmer
6.272
963741AG1-226 GEN
Solar/Wind Harmer
14.786
943021AE2-325 GEN
Solar/Wind Harmer
3.244
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
23546401DTGZ2-030
Solar/Wind Helper
0.075
237038AE2-054 C
Solar/Wind Helper
0.227
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
24318805MLG1
50/50
6.319
24686405CER G5
Adder
8.185
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
970191AG2-125 GEN
Solar/Wind Harmer
1.699
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.388
971199AH1-059 GEN
Solar/Wind Harmer
1.321
24690905MDL-1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.339
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274803UNIV PARK;6U
Adder
5.179
276843GEN-1.7
Solar/Wind Harmer
0.2
972038AH1-567 GEN2
Adder
0.324
965091AG1-374 GEN
Solar/Wind Harmer
18.362
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237001AB1-127_GEN
Solar/Wind Helper
0.369
962761AG1-125 GEN
Solar/Wind Harmer
29.52
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.043
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.119
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.339
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
939401AE1-172 GEN
Solar/Wind Harmer
4.617
962781AG1-127 GEN
Solar/Wind Harmer
5.837
235067AD1-061 GEN
Solar/Wind Helper
0.371
237002AB1-128_GEN
Solar/Wind Helper
0.369
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.039
253406AD2-031_GEN
Solar/Wind Harmer
0.497
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
247536S-71 GEN
Solar/Wind Harmer
0.257
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.151
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
959141AF2-205 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
270399AC1-101 GEN
Solar/Wind Harmer
1.959
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
971171AH1-044 GEN
Solar/Wind Harmer
2.06
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270459AD2-067 GEN
Solar/Wind Harmer
0
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
270543AE2-219 C
Solar/Wind Harmer
4.502
24729505KEY G4
Adder
5.966
270071AF1-092 GEN
Solar/Wind Harmer
12.235
24691005MDL-2G C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270007AE1-245 C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.566
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
247521TR3_G114
Solar/Wind Harmer
0.229
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274735ELWOOD EC;4P
Adder
14.566
970179AG2-119 GEN
Solar/Wind Harmer
5.512
970169AG2-114 GEN
Solar/Wind Harmer
6.152
959341AF2-225 GEN
Solar/Wind Harmer
6.441
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.41 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5248.4
MW Contribution:
2.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
23684201S70BUS2
50/50
0.315
972269AH1-719 GEN
Adder
2.27
253398AE2-221_GEN2
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.05
25196808ZIMRHP
Adder
71.417
25196008MFTGT1
Adder
1.297
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
2.778
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.388
970825AG2-519 GEN
Solar/Wind Harmer
2.272
270594AE1-207 GEN
Solar/Wind Harmer
7.153
270032AE2-172
Solar/Wind Harmer
4.258
965011AG1-365 GEN
Solar/Wind Harmer
6.339
940581AE2-045 GEN
Solar/Wind Harmer
0
971605AH1-302 GEN
Solar/Wind Harmer
7.861
246936BC-WTG1
Solar/Wind Harmer
0.253
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
964861AG1-349 GEN
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
10.385
945111AF1-176 GEN
Solar/Wind Harmer
11.117
274773LINCOLN ;4U
Adder
7.522
274774LINCOLN ;5U
Adder
7.522
274751CRETE EC ;1U
Adder
7.339
274723RIVER EC ;12
Adder
15.953
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.223
939741AE1-205 GEN
Solar/Wind Harmer
8.588
970569AG2-363 GEN
Solar/Wind Harmer
18.35
23583801GRNGAP
Solar/Wind Helper
4.857
237085AD2-009_GEN
Solar/Wind Helper
1.37
238126S14_GEN_1
Solar/Wind Helper
0.641
970155AG2-107 GEN
Solar/Wind Harmer
18.85
972203AH1-686 GEN
Adder
2.3
24723205RIVRG3
Adder
18.491
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.663
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252516AE2-318_GEN
Solar/Wind Harmer
7.407
25194608D.CRK4
Adder
1.552
945681AF1-233 GEN
Solar/Wind Harmer
12.198
970613AG2-401 GEN
Solar/Wind Harmer
4.711
965651AG1-433 GEN
Solar/Wind Harmer
1.881
971995AH1-542 GEN
Solar/Wind Harmer
2.35
270024AE2-089 GEN
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.47
965421AG1-410 GEN
Solar/Wind Harmer
18.877
270055AF2-134 C O1
Solar/Wind Harmer
0
24639705ELKHART HY
Adder
0.138
270449AD2-020 GEN
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.454
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.299
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238185AF2-356 C
Solar/Wind Helper
2.003
238120AE2-309 GEN
Solar/Wind Helper
0.408
23777801MSM_W1-116
Solar/Wind Helper
0.096
957471AF2-041 GEN
Solar/Wind Harmer
3.09
961821AG1-024 GEN
Solar/Wind Harmer
4.149
270432AC2-029 GEN
Solar/Wind Harmer
3.088
270263AC1-001 GEN
Solar/Wind Harmer
0.696
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.001
241972AD1-140 GEN
Solar/Wind Harmer
0.733
270578AF1-285 GEN2
Solar/Wind Harmer
0.441
25196508WSDLE4
Adder
8.008
972163AH1-664 GEN
Solar/Wind Harmer
7.194
270356AE2-297 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
2.497
971609AH1-304 GEN
Solar/Wind Harmer
1.044
959331AF2-224 GEN
Solar/Wind Harmer
4.437
965041AG1-368 GEN
Solar/Wind Harmer
6.303
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
957241AF2-018 GEN
Solar/Wind Harmer
0
270053AF1-130 C
Solar/Wind Harmer
13.997
960681AF2-359 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
2.713
270526AF1-158 GEN
Solar/Wind Harmer
0
274776LINCOLN ;7U
Adder
7.522
270400AC1-102 GEN
Solar/Wind Harmer
1.959
274687WILL CNTY;4U
Adder
24.769
274687WILL CNTY;4U
Adder
24.769
274731ELWOOD EC;2P
Adder
14.566
274733ELWOOD EC;3P
Adder
14.566
276726Z2-087_GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
1.04
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971073AG2-665 GEN
Solar/Wind Harmer
5.141
270269AC2-059
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
5.328
972159AH1-661 GEN
Adder
0.953
25326109MON D
Adder
1.253
25183208HLCRTG
Solar/Wind Harmer
0
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25194508D.CRK3
Adder
1.335
970329AG2-216 GEN
Solar/Wind Harmer
2.837
24728805RICHG1
Adder
3.492
970885AG2-551 GEN
Solar/Wind Harmer
2.144
270383AD1-128 GEN
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.428
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.48
270031AE2-169
Solar/Wind Harmer
3.515
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
972045AH1-571 GEN
Solar/Wind Harmer
1.309
965791AG1-447 GEN
Solar/Wind Harmer
5.74
247620Y3-023
Adder
0.413
958011AF2-095 GEN
Solar/Wind Harmer
8.924
958491AF2-143 GEN
Solar/Wind Harmer
9.221
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.119
235531U2-073 GEN
Solar/Wind Helper
2.544
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
10.602
25194408D.CRK1
Adder
7.139
270462AD2-086
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.492
970883AG2-550 GEN
Solar/Wind Harmer
6.432
926881AC1-175 GEN
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
3.762
270599AE1-208 GEN
Solar/Wind Harmer
5.858
24725505WLD G2 C
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.04
970349AG2-230 GEN
Solar/Wind Harmer
9.463
24697605MDL-3G C
Solar/Wind Harmer
0
972043AH1-570 GEN
Solar/Wind Harmer
1.634
966841AG1-555 GEN
Solar/Wind Harmer
0.711
961051AF2-396 GEN
Solar/Wind Harmer
12.441
961051AF2-396 GEN
Solar/Wind Harmer
8.294
945391AF1-204 GEN
Solar/Wind Harmer
6.594
274808UNIV PK N;4U
Adder
4.435
958481AF2-142 GEN
Solar/Wind Harmer
9.241
944231AF1-091 GEN
Solar/Wind Harmer
14.169
276876AE1-163_GEN2
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
2.04
238148AE2-230_GEN2
Solar/Wind Helper
0.416
235062AE1-101 C1
Solar/Wind Helper
1.383
238117U2-030
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.247
23562401OGROV2
50/50
2.416
961921AG1-034 GEN
Solar/Wind Harmer
6.223
942051AE2-217 GEN
Solar/Wind Harmer
12.329
252507AC2-088 GEN
Solar/Wind Harmer
0.298
270391AF1-285 GEN3
Solar/Wind Harmer
0.441
25196608WSDLE5
Adder
8.09
958171AF2-111 GEN
Solar/Wind Harmer
16.173
944531AF1-118 GEN
Solar/Wind Harmer
28.761
24728705AND G3
Adder
7.256
971347AH1-153 GEN
Solar/Wind Harmer
3.154
970781AG2-491 GEN
Solar/Wind Harmer
6.287
270063AE2-323 C
Solar/Wind Harmer
0
274752CRETE EC ;2U
Adder
7.339
970193AG2-126 GEN
Solar/Wind Harmer
9.309
274887GEN-1.85
Solar/Wind Harmer
0.161
939351AE1-166 GEN
Solar/Wind Harmer
0
274826FISK ;BP
Adder
9.721
970707AG2-453 GEN
Solar/Wind Harmer
20.232
274730ELWOOD EC;6P
Adder
14.566
274862TOP CROP ;2U
Solar/Wind Harmer
0.832
276868AE1-113 GEN
Solar/Wind Harmer
1.228
274879MINONK ;1U
Solar/Wind Harmer
0.256
959611AF2-252 GEN
Solar/Wind Harmer
2.04
274855GSG-6 ;RU
Solar/Wind Harmer
0.223
238152AF2-075_GEN
Solar/Wind Helper
0.595
23777901MDS_W4-102
Solar/Wind Helper
0.147
238127S14_GEN_2
Solar/Wind Helper
0.641
23684101S70BUS1
50/50
0.309
970879AG2-548 GEN
Solar/Wind Harmer
1.168
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
1.233
942221AE2-234 GEN
Solar/Wind Harmer
2.563
957841AF2-078 GEN
Solar/Wind Harmer
0
246937BC-WTG2
Solar/Wind Harmer
0.253
24387305FR-4G C
Solar/Wind Harmer
0
247607V1-011 GEN
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.645
274770LINCOLN ;1U
Adder
7.522
274771LINCOLN ;2U
Adder
7.522
274805UNIV PK N;1U
Adder
4.464
970107AG2-081 GEN
Solar/Wind Harmer
1.86
274888KELLY CRK;1U
Solar/Wind Harmer
0.361
970941AG2-585 GEN
Solar/Wind Harmer
3.408
276897AD1-100 C
Solar/Wind Harmer
15.489
970623AG2-406 GEN
Solar/Wind Harmer
1.134
276893AG1-478 C
Solar/Wind Harmer
0.412
962691AG1-118 GEN
Solar/Wind Harmer
18.411
942111AE2-223 GEN
Solar/Wind Harmer
1.994
237061AD1-155 GEN
Solar/Wind Helper
1.477
235020AA1-095 C
Solar/Wind Helper
0.044
238221AF1-254 C O1
Solar/Wind Helper
0.228
270512AE1-227 GEN2
Solar/Wind Harmer
1.908
971191AH1-055 GEN
Solar/Wind Harmer
18.254
970879AG2-548 GEN
Solar/Wind Harmer
5.141
270367AC2-061_GEN
Solar/Wind Harmer
0
253394AE2-221_GEN
Solar/Wind Harmer
0
270186AC1-089 GEN
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.256
972167AH1-666 GEN
Solar/Wind Harmer
5.179
270240V3-007_GEN2
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
9.603
970825AG2-519 GEN
Solar/Wind Harmer
4.82
270043AE2-236 GEN
Solar/Wind Harmer
4.076
965021AG1-366 GEN
Solar/Wind Harmer
2.113
246938BC-WTG3
Solar/Wind Harmer
0.226
945111AF1-176 GEN
Solar/Wind Harmer
5.05
270505AE1-170 C O1
Solar/Wind Harmer
6.542
274772LINCOLN ;3U
Adder
7.522
274724RIVER EC ;11
Adder
15.767
972259AH1-714 GEN
Adder
16.936
274729ELWOOD EC;1P
Adder
14.566
946671AF1-331 GEN
Solar/Wind Harmer
0.653
274850MENDOTA H;RU
Solar/Wind Harmer
0.071
970571AG2-364 GEN
Solar/Wind Harmer
12.233
238175AF1-290_GEN
Solar/Wind Helper
0.13
24721905FLATG4
Adder
23.461
962771AG1-126 GEN
Solar/Wind Harmer
29.52
970153AG2-106 GEN
Solar/Wind Harmer
18.85
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
8.662
253370AE2-315 SEC1
Adder
1.908
253371AE2-315 SEC2
Adder
1.805
252519AF1-045_GEN
Solar/Wind Harmer
3.45
25194608D.CRK4
Adder
1.552
946031AF1-268 GEN
Solar/Wind Harmer
6.094
970289AG2-191 GEN
Solar/Wind Harmer
0.702
247642Z2-115 C
Solar/Wind Harmer
0.003
24728505AND G1
Adder
3.47
24695305TIMB G C
Solar/Wind Harmer
0.532
274811UNIV PK N;7U
Adder
4.454
276806AD2-047 C O1
Solar/Wind Harmer
3.512
274734ELWOOD EC;8P
Adder
14.566
274736ELWOOD EC;9P
Adder
0.016
943121AE2-341 GEN
Solar/Wind Harmer
10.337
943591AF1-030 GEN
Solar/Wind Harmer
6.874
964991AG1-363 GEN
Solar/Wind Helper
4.131
238110AE1-109 GEN3
Solar/Wind Helper
0.088
235063AE1-101 C2
Solar/Wind Helper
1.383
959091AF2-200 GEN
Solar/Wind Harmer
2.06
970935AG2-582 GEN
50/50
1217.29
24318905MLG2
50/50
4.655
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
24723005RIVRG1
Adder
18.491
24723105RIVRG2
Adder
18.491
253370AE2-315 SEC1
Adder
1.908
25322209TAIT E
Adder
9.279
25322209TAIT E
Adder
9.07
971655AH1-328 GEN
Solar/Wind Harmer
2.343
247621Y3-024
Adder
0.222
971613AH1-306 GEN
Solar/Wind Harmer
3.066
970291AG2-192 GEN
Solar/Wind Harmer
0.83
970291AG2-192 GEN
Solar/Wind Harmer
0.383
270246TR4_N_V150
Solar/Wind Harmer
0.04
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.827
971587AH1-292 GEN
Solar/Wind Harmer
4.565
971125AH1-004 GEN
Solar/Wind Harmer
2.48
276776AD2-060 GEN
Solar/Wind Harmer
0.661
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.416
237080AD1-060 GEN
Solar/Wind Helper
0.284
23559101PLEAS2
50/50
11.247
23562301OGROV1
50/50
2.436
970149AG2-104 GEN
Solar/Wind Harmer
15.941
270510AE1-227 GEN1
Solar/Wind Harmer
1.908
960001AF2-291 GEN
Solar/Wind Harmer
0
971073AG2-665 GEN
Solar/Wind Harmer
1.168
970773AG2-487 GEN
Solar/Wind Harmer
1.132
970091AG2-072 GEN
Adder
70.262
971917AH1-482 GEN
Solar/Wind Harmer
8.17
970373AG2-245 GEN
Solar/Wind Harmer
13.183
944971AF1-162 GEN
Solar/Wind Harmer
6.272
963741AG1-226 GEN
Solar/Wind Harmer
14.786
943021AE2-325 GEN
Solar/Wind Harmer
3.244
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.001
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.717
276655WTG1_EQ
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0
971403AH1-188 GEN
Solar/Wind Harmer
8.564
23546401DTGZ2-030
Solar/Wind Helper
0.075
237038AE2-054 C
Solar/Wind Helper
0.227
959081AF2-199 GEN
Solar/Wind Harmer
1.03
971067AG2-660 GEN
Solar/Wind Harmer
0.343
24318805MLG1
50/50
6.319
24686405CER G5
Adder
8.185
253325AC1-069 GEN
Solar/Wind Harmer
0.008
270518AE2-148 GEN
Solar/Wind Harmer
0.56
970191AG2-125 GEN
Solar/Wind Harmer
1.699
24379505HDWTR1G C
Solar/Wind Harmer
0
270004AE1-209 GEN
Solar/Wind Harmer
1.388
971199AH1-059 GEN
Solar/Wind Harmer
1.321
962761AG1-125 GEN
Solar/Wind Harmer
29.52
270520AE2-214 GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.712
24686505CER G6
Adder
8.25
253333AC1-068 GEN
Solar/Wind Harmer
0.008
25326309TAIT D
Adder
1.043
270317AD1-130_GEN
Solar/Wind Harmer
0
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.119
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0
274754CRETE EC ;4U
Adder
7.339
274802UNIV PARK;5U
Adder
5.179
274732ELWOOD EC;7P
Adder
14.566
939401AE1-172 GEN
Solar/Wind Harmer
4.617
962781AG1-127 GEN
Solar/Wind Harmer
5.837
235067AD1-061 GEN
Solar/Wind Helper
0.371
237002AB1-128_GEN
Solar/Wind Helper
0.369
270291AC1-194 GEN
Solar/Wind Harmer
0
971985AH1-537 GEN
Solar/Wind Harmer
2.039
253406AD2-031_GEN
Solar/Wind Harmer
0.497
972165AH1-665 GEN
Solar/Wind Harmer
5.762
971029AG2-637 GEN
Solar/Wind Harmer
9.669
247536S-71 GEN
Solar/Wind Harmer
0.257
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.151
339216AC1-074 GEN
Solar/Wind Harmer
0.168
971611AH1-305 GEN
Solar/Wind Harmer
3.744
959141AF2-205 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.403
24386405FR-21G C
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
7.522
274777LINCOLN ;8U
Adder
7.522
972037AH1-567 GEN1
Adder
0.163
960591AF2-350 GEN
Solar/Wind Harmer
6.197
972228AH1-698 GEN2
Adder
3.29
270399AC1-101 GEN
Solar/Wind Harmer
1.959
970833AG2-524 GEN
Solar/Wind Harmer
6.799
970833AG2-524 GEN
Solar/Wind Harmer
4.533
971675AH1-338 GEN
Solar/Wind Harmer
2.386
971411AH1-196 GEN
Solar/Wind Harmer
9.174
23750701CROSSCHOOL
Solar/Wind Helper
1.155
971171AH1-044 GEN
Solar/Wind Harmer
2.06
940611AE2-048 GEN
Solar/Wind Harmer
17.232
941391AE2-136 GEN
Solar/Wind Harmer
9.707
270459AD2-067 GEN
Solar/Wind Harmer
0
25196408WSDLE3
Adder
8.328
25196308WSDLE2
Adder
8.256
971341AH1-150 GEN
Solar/Wind Harmer
2.06
971343AH1-151 GEN
Solar/Wind Harmer
2.06
24690905MDL-1G C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
7.339
274814UNIV PK N;0U
Adder
4.493
274807UNIV PK N;3U
Adder
4.483
274803UNIV PARK;6U
Adder
5.179
276843GEN-1.7
Solar/Wind Harmer
0.2
972038AH1-567 GEN2
Adder
0.324
965091AG1-374 GEN
Solar/Wind Harmer
18.362
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237001AB1-127_GEN
Solar/Wind Helper
0.369
25196208WSDLE1
Adder
8.235
25196708WSDLE6
Adder
8.215
25196108MFTGT2
Adder
1.43
25196108MFTGT2
Adder
1.328
270543AE2-219 C
Solar/Wind Harmer
4.502
24729505KEY G4
Adder
5.966
270071AF1-092 GEN
Solar/Wind Harmer
12.235
24691005MDL-2G C
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
971771AH1-392 GEN
Solar/Wind Harmer
6.254
270007AE1-245 C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
14.566
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.049
276861AD2-134 GEN
Solar/Wind Harmer
0.109
276863AD2-134 GEN
Solar/Wind Harmer
0.109
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
2.63
943851AF1-053 GEN
Solar/Wind Harmer
1.821
253372AE2-315 SEC3
Adder
1.805
253372AE2-315 SEC3
Adder
1.805
25306009OHH W.
Adder
2.738
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
0.918
970289AG2-191 GEN
Solar/Wind Harmer
1.213
963791AG1-232 GEN
Solar/Wind Harmer
8.578
247521TR3_G114
Solar/Wind Harmer
0.229
957201AF2-014 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
972227AH1-698 GEN1
Adder
2.316
274827FISK ;RP
Adder
6.89
274800UNIV PARK;3U
Adder
5.177
274801UNIV PARK;4U
Adder
5.177
274735ELWOOD EC;4P
Adder
14.566
970179AG2-119 GEN
Solar/Wind Harmer
5.512
970169AG2-114 GEN
Solar/Wind Harmer
6.152
959341AF2-225 GEN
Solar/Wind Harmer
6.441
238169AE2-226 GEN1
Solar/Wind Helper
0.584
238170AE2-226 GEN2
Solar/Wind Helper
0.584
CPLELTFEXP_CPLE->PJM
CLTF
1.296
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.919
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.746
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.223
MECLTFEXP_MEC->PJM
CLTF
14.081
SIGELTFEXP_SIGE->PJM
CLTF
0.455
NYPJM->LTFIMP_NY
CLTF
4.411
LGEELTFEXP_LGEE->PJM
CLTF
6.118
WECLTFEXP_WEC->PJM
CLTF
3.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
13.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.952
TVALTFEXP_TVA->PJM
CLTF
6.885

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.25 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:5006.21
MW Contribution:
12.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
7.027
270349AD2-093_GEN
Solar/Wind Harmer
4.455
270471AD2-092_GEN
Solar/Wind Harmer
4.455
253383AE2-342_GEN
Solar/Wind Harmer
1.04
25322209TAIT E
Adder
10.635
25322209TAIT E
Adder
10.396
253370AE2-315 SEC1
Adder
2.18
270246TR4_N_V150
Solar/Wind Harmer
0.912
247621Y3-024
Adder
0.255
316097T157 G90
Solar/Wind Helper
1.515
238147AE2-230_GEN1
Solar/Wind Helper
0.501
237080AD1-060 GEN
Solar/Wind Helper
0.346
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.028
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
962761AG1-125 GEN
Solar/Wind Harmer
41.016
270520AE2-214 GEN
Solar/Wind Harmer
7.243
270391AF1-285 GEN3
Solar/Wind Harmer
1.393
253333AC1-068 GEN
Solar/Wind Harmer
1.191
270317AD1-130_GEN
Solar/Wind Harmer
3.64
270273AD2-016 GEN
Solar/Wind Harmer
3.013
25326309TAIT D
Adder
1.195
241813AF1-122_GEN
Solar/Wind Harmer
5.897
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.062
270437AC2-090 C
Solar/Wind Harmer
5.862
270216AD2-079_GEN
Solar/Wind Harmer
0.634
274754CRETE EC ;4U
Adder
8.473
274802UNIV PARK;5U
Adder
5.968
274732ELWOOD EC;7P
Adder
16.762
274674JOLIET 9 ;6U
Adder
15.699
235067AD1-061 GEN
Solar/Wind Helper
0.451
237002AB1-128_GEN
Solar/Wind Helper
0.448
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.118
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.313
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.443
961331AF2-424 GEN
Solar/Wind Helper
0.442
270120AB2-067 GEN2
50/50
7.109
270054AF2-122 C O1
Solar/Wind Harmer
3.972
938701AE1-092 GEN
Solar/Wind Harmer
23.766
270462AD2-086
Solar/Wind Harmer
7.908
253415AE1-040 GEN
Solar/Wind Harmer
1.242
253349AC2-067 GEN
Solar/Wind Harmer
2.203
270247TR4_N_V136
Solar/Wind Harmer
0.912
942801AE2-298 GEN
Solar/Wind Harmer
1.621
960971AF2-388 GEN
Solar/Wind Harmer
11.601
25194408D.CRK1
Adder
8
970883AG2-550 GEN
Solar/Wind Harmer
10.561
970349AG2-230 GEN
Solar/Wind Harmer
15.797
270599AE1-208 GEN
Solar/Wind Harmer
8.576
926881AC1-175 GEN
Solar/Wind Harmer
5.862
944231AF1-091 GEN
Solar/Wind Harmer
18.887
24728905RICHG2
Adder
3.96
274808UNIV PK N;4U
Adder
5.115
274674JOLIET 9 ;6U
Adder
15.699
274693ROCKY RD ;1P
Adder
11.156
274683WAUKEGAN ;8U
Adder
21.305
274683WAUKEGAN ;8U
Adder
9.68
23585401KL_K28_T16
Solar/Wind Helper
1.5
238117U2-030
Solar/Wind Helper
0.345
238148AE2-230_GEN2
Solar/Wind Helper
0.501
235062AE1-101 C1
Solar/Wind Helper
1.678
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.371
232424Y1-079 C
Solar/Wind Helper
0.118
232428Y3-058 C
Solar/Wind Helper
0.342
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.293
20675428EAM_W2-061
Solar/Wind Helper
0.016
23559001PLEAS1
50/50
6.362
961921AG1-034 GEN
Solar/Wind Harmer
15.551
270287AF1-227 GEN3
Solar/Wind Harmer
2.504
942051AE2-217 GEN
Solar/Wind Harmer
20.995
942871AE2-306 GEN
Solar/Wind Harmer
1.045
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
958581AF2-149 GEN
Solar/Wind Harmer
4.712
957541AF2-048 GEN
Solar/Wind Harmer
1.717
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.358
25196608WSDLE5
Adder
9.072
252507AC2-088 GEN
Solar/Wind Harmer
1.892
270063AE2-323 C
Solar/Wind Harmer
2.32
971347AH1-153 GEN
Solar/Wind Harmer
5.266
270330AC1-082 GEN2
Solar/Wind Harmer
0.5
274752CRETE EC ;2U
Adder
8.473
24728705AND G3
Adder
8.209
274826FISK ;BP
Adder
11.201
274730ELWOOD EC;6P
Adder
16.762
238127S14_GEN_2
Solar/Wind Helper
0.836
23559101PLEAS2
50/50
6.362
970149AG2-104 GEN
Solar/Wind Harmer
25.328
270286AF1-227 GEN2
Solar/Wind Harmer
2.504
270578AF1-285 GEN2
Solar/Wind Harmer
1.393
971073AG2-665 GEN
Solar/Wind Harmer
1.275
960001AF2-291 GEN
Solar/Wind Harmer
3.25
270258AD1-119 GEN
Solar/Wind Harmer
2.156
270297AD1-101 GEN
Solar/Wind Harmer
2.147
270222AC2-111 GEN
Solar/Wind Harmer
4.718
270510AE1-227 GEN1
Solar/Wind Harmer
2.605
970091AG2-072 GEN
Adder
77.647
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.283
233987AB2-037 GEN
Solar/Wind Helper
2.369
232417X3-008 C
Solar/Wind Helper
0.235
233923SMA
Solar/Wind Helper
0.76
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.329
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
270119AB2-067 GEN1
50/50
7.109
253378AE2-206_GEN
Solar/Wind Harmer
3.997
25326509SID D
Adder
1.451
970879AG2-548 GEN
Solar/Wind Harmer
1.275
246937BC-WTG2
Solar/Wind Harmer
4.216
247607V1-011 GEN
Solar/Wind Harmer
4.231
962581AG1-107 GEN
Solar/Wind Harmer
5.356
961491AF2-440 GEN
Solar/Wind Harmer
2.226
942221AE2-234 GEN
Solar/Wind Harmer
3.71
274770LINCOLN ;1U
Adder
8.673
274771LINCOLN ;2U
Adder
8.673
274805UNIV PK N;1U
Adder
5.149
274696ROCKY RD ;4P
Adder
11.533
274697ROCKY RD ;3P
Adder
3.061
23751201ROTHROCK
Solar/Wind Helper
0.836
235020AA1-095 C
Solar/Wind Helper
0.054
237061AD1-155 GEN
Solar/Wind Helper
1.772
238221AF1-254 C O1
Solar/Wind Helper
0.278
316411AF1-147_GEN1
Solar/Wind Helper
0.898
223402AF1-300 C
Solar/Wind Helper
0.371
233930AB2-032 GEN
Solar/Wind Helper
0.385
233982AB2-133 GEN
Solar/Wind Helper
0.363
233946AB2-136 GEN
Solar/Wind Helper
0.575
232410W1-006 C
Solar/Wind Helper
0.513
233952AC2-187 GEN
Solar/Wind Helper
0.235
233954AC2-188 GEN
Solar/Wind Helper
0.235
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.051
207471AF2-354 C
Solar/Wind Helper
0.17
961431AF2-434 GEN
Solar/Wind Helper
0.441
270051AF1-062 GEN
50/50
11.798
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
970879AG2-548 GEN
Solar/Wind Harmer
8.771
970065AG2-057 GEN
Solar/Wind Harmer
0.921
253394AE2-221_GEN
Solar/Wind Harmer
4.9
246938BC-WTG3
Solar/Wind Harmer
4.289
971191AH1-055 GEN
Solar/Wind Harmer
20.077
965021AG1-366 GEN
Solar/Wind Harmer
2.494
270043AE2-236 GEN
Solar/Wind Harmer
5.865
270367AC2-061_GEN
Solar/Wind Harmer
3.367
270044AE2-322 C
Solar/Wind Harmer
1.388
962031AG1-047 GEN
Solar/Wind Harmer
3.189
957741AF2-068 GEN
Solar/Wind Harmer
15.82
270512AE1-227 GEN2
Solar/Wind Harmer
2.212
270186AC1-089 GEN
Solar/Wind Harmer
6.425
270240V3-007_GEN2
Solar/Wind Harmer
6.498
970825AG2-519 GEN
Solar/Wind Harmer
5.915
25196008MFTGT1
Adder
1.404
274772LINCOLN ;3U
Adder
8.673
274724RIVER EC ;11
Adder
18.196
972259AH1-714 GEN
Adder
19.5
274729ELWOOD EC;1P
Adder
16.762
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.186
316415AF1-147_GEN2
Solar/Wind Helper
0.898
205916AD1-020 GEN
Solar/Wind Helper
1.732
233944AB2-135 GEN
Solar/Wind Helper
0.596
232408W1-005 C
Solar/Wind Helper
0.513
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.075
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.093
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
270166AC1-044 GEN3
50/50
7.109
270485AE1-090_GEN
Solar/Wind Harmer
0.688
972269AH1-719 GEN
Adder
2.545
253398AE2-221_GEN2
Solar/Wind Harmer
4.9
246936BC-WTG1
Solar/Wind Harmer
4.216
270489AE1-102 GEN1
Solar/Wind Harmer
1.401
965011AG1-365 GEN
Solar/Wind Harmer
10.725
958861AF2-177 GEN
Solar/Wind Harmer
11.586
252510AF1-249 C
Solar/Wind Harmer
0.441
945371AF1-202 GEN
Solar/Wind Harmer
7.376
270005AE1-210 C O1
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
6.717
270209AC1-174_GEN
Solar/Wind Harmer
4.274
270239V3-007_GEN1
Solar/Wind Harmer
1.807
270331AC1-082 GEN3
Solar/Wind Harmer
0.501
25196808ZIMRHP
Adder
79.685
970825AG2-519 GEN
Solar/Wind Harmer
2.203
25196008MFTGT1
Adder
1.45
274751CRETE EC ;1U
Adder
8.473
274773LINCOLN ;4U
Adder
8.673
274774LINCOLN ;5U
Adder
8.673
274723RIVER EC ;12
Adder
18.412
23583801GRNGAP
Solar/Wind Helper
5.644
238126S14_GEN_1
Solar/Wind Helper
0.836
237085AD2-009_GEN
Solar/Wind Helper
1.667
3141196NOKESVL
Solar/Wind Helper
1.039
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.235
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.091
209116AE2-175 GEN
Solar/Wind Helper
1.799
961421AF2-433 GEN
Solar/Wind Helper
0.441
270594AE1-207 GEN
Solar/Wind Harmer
13.371
270032AE2-172
Solar/Wind Harmer
4.579
946101AF1-275 GEN
Solar/Wind Harmer
1.811
942861AE2-305 GEN
Solar/Wind Harmer
9.069
270269AC2-059
Solar/Wind Harmer
10.571
972159AH1-661 GEN
Adder
1.106
241960AC2-195 GEN
Solar/Wind Harmer
3.055
971073AG2-665 GEN
Solar/Wind Harmer
8.771
25326109MON D
Adder
1.442
927014AC1-188 GEN
Solar/Wind Harmer
1.717
253400AC2-068 GEN
Solar/Wind Harmer
0.886
25183208HLCRTG
Solar/Wind Harmer
6.427
944541AF1-119 GEN
Solar/Wind Harmer
4.444
25194508D.CRK3
Adder
1.496
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.456
270201AC2-176 GEN
Solar/Wind Harmer
5.42
964611AG1-324 GEN
Solar/Wind Harmer
0.551
270031AE2-169
Solar/Wind Harmer
8.576
270383AD1-128 GEN
Solar/Wind Harmer
6.419
247620Y3-023
Adder
0.483
24728805RICHG1
Adder
3.96
274695ROCKY RD ;2P
Adder
11.267
235054AD2-180 GEN
Solar/Wind Helper
2.054
235531U2-073 GEN
Solar/Wind Helper
3.347
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.972
316045AC1-158 PL2
Solar/Wind Helper
4.182
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
20674328GAR_V4-001
Solar/Wind Helper
0.023
970155AG2-107 GEN
Solar/Wind Harmer
17.885
971995AH1-542 GEN
Solar/Wind Harmer
12.463
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
965421AG1-410 GEN
Solar/Wind Harmer
32.318
253316AC1-085 GEN3
Solar/Wind Harmer
8.992
946171AF1-282 GEN
Solar/Wind Harmer
10.741
965651AG1-433 GEN
Solar/Wind Harmer
5.801
252516AE2-318_GEN
Solar/Wind Harmer
10.604
270024AE2-089 GEN
Solar/Wind Harmer
4.961
25194608D.CRK4
Adder
1.739
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.137
24728605AND G2
Adder
3.925
274676JOLIET 29;8U
Adder
31.291
972203AH1-686 GEN
Adder
2.344
274745AC1-111 GEN9
Adder
5.677
274682WAUKEGAN ;7U
Adder
18.178
316095T157 G97
Solar/Wind Helper
1.515
238185AF2-356 C
Solar/Wind Helper
2.686
238109AE1-109 GEN2
Solar/Wind Helper
0.115
238120AE2-309 GEN
Solar/Wind Helper
0.534
23751101LEADS_P59
Solar/Wind Helper
2.15
23777801MSM_W1-116
Solar/Wind Helper
0.116
227287AC2-120 GEN
Solar/Wind Helper
0.35
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.513
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.501
238152AF2-075_GEN
Solar/Wind Helper
0.715
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.513
316044AC1-158 PL1
Solar/Wind Helper
1.307
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.586
202652Y1-033 WT C
Solar/Wind Helper
0.504
962771AG1-126 GEN
Solar/Wind Harmer
41.016
970153AG2-106 GEN
Solar/Wind Harmer
17.885
270284AF1-227 GEN1
Solar/Wind Harmer
6.768
24721905FLATG4
Adder
24.045
276820AF1-078_GEN
Solar/Wind Harmer
1.776
960071AF2-298 GEN
Solar/Wind Harmer
1.647
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
253317AC1-085 GEN4
Solar/Wind Harmer
8.992
946181AF1-283 GEN
Solar/Wind Harmer
13.963
24695305TIMB G C
Solar/Wind Harmer
3.573
270588AE1-091_GEN
Solar/Wind Harmer
11.753
252519AF1-045_GEN
Solar/Wind Harmer
3.859
252524AE2-267 GEN
Solar/Wind Harmer
1.667
25194608D.CRK4
Adder
1.739
946031AF1-268 GEN
Solar/Wind Harmer
8.725
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.137
24728505AND G1
Adder
3.925
274676JOLIET 29;8U
Adder
30.174
274734ELWOOD EC;8P
Adder
16.762
274736ELWOOD EC;9P
Adder
16.762
274682WAUKEGAN ;7U
Adder
18.178
964991AG1-363 GEN
Solar/Wind Helper
5.171
238110AE1-109 GEN3
Solar/Wind Helper
0.115
235063AE1-101 C2
Solar/Wind Helper
1.678
205932AD2-116_GEN
Solar/Wind Helper
0.514
233996TM1833_GEN
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
316447AC1-158 HLD
Solar/Wind Helper
2.876
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.526
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
24318805MLG1
50/50
10.127
270475AD2-096_GEN
50/50
7.137
270518AE2-148 GEN
Solar/Wind Harmer
13.818
253325AC1-069 GEN
Solar/Wind Harmer
1.191
971199AH1-059 GEN
Solar/Wind Harmer
2.312
270491AE1-102 GEN2
Solar/Wind Harmer
1.401
270004AE1-209 GEN
Solar/Wind Harmer
5.743
24379505HDWTR1G C
Solar/Wind Harmer
8.305
270329AC1-082 GEN1
Solar/Wind Harmer
0.5
274753CRETE EC ;3U
Adder
8.473
274814UNIV PK N;0U
Adder
5.182
274807UNIV PK N;3U
Adder
5.171
274803UNIV PARK;6U
Adder
5.968
972038AH1-567 GEN2
Adder
0.373
238108AE1-109 GEN1
Solar/Wind Helper
0.115
23562501BACKB
Solar/Wind Helper
1.023
237001AB1-127_GEN
Solar/Wind Helper
0.446
233918AB1-142 GEN
Solar/Wind Helper
0.508
228729W2-030 C
Solar/Wind Helper
0.112
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.443
963151AG1-164 GEN
Solar/Wind Helper
0.443
961341AF2-425 GEN
Solar/Wind Helper
0.442
212507AE2-042_GEN
Solar/Wind Helper
1.561
961821AG1-024 GEN
Solar/Wind Harmer
10.368
972239AH1-704 GEN
Adder
2.66
945631AF1-228 GEN
Solar/Wind Harmer
5.449
270223U2-072_GEN1
Solar/Wind Harmer
2.274
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
8.025
253338AC1-165 GEN
Solar/Wind Harmer
1.235
270263AC1-001 GEN
Solar/Wind Harmer
1.17
241972AD1-140 GEN
Solar/Wind Harmer
5.01
270340AC2-060 GEN
Solar/Wind Harmer
3.331
270191TR4_S_V150
Solar/Wind Harmer
3.216
959331AF2-224 GEN
Solar/Wind Harmer
10.725
965041AG1-368 GEN
Solar/Wind Harmer
10.701
966831AG1-554 GEN
Solar/Wind Harmer
1.275
25196508WSDLE4
Adder
8.979
964611AG1-324 GEN
Solar/Wind Harmer
4.11
274776LINCOLN ;7U
Adder
8.673
274687WILL CNTY;4U
Adder
28.512
274687WILL CNTY;4U
Adder
28.512
274731ELWOOD EC;2P
Adder
16.762
274733ELWOOD EC;3P
Adder
16.762
274746AC1-111 G10
Adder
5.677
238118U2-030_1
Solar/Wind Helper
0.345
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.647
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.372
205956AE1-196_GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.235
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
20720628TIN_W1-124
Solar/Wind Helper
0.192
316164AC1-076 GEN
Solar/Wind Helper
1.108
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.069
20675128HRM_W1-127
Solar/Wind Helper
0.03
241955AC1-078 GEN
Solar/Wind Harmer
8.781
241973AD2-163_GEN1
Solar/Wind Harmer
2.319
241974AD2-163_GEN2
Solar/Wind Harmer
2.319
943861AF1-054 GEN
Solar/Wind Harmer
4.476
943851AF1-053 GEN
Solar/Wind Harmer
2.163
270227U2-072_GEN3
Solar/Wind Harmer
2.274
270228U2-072_GEN4
Solar/Wind Harmer
2.274
270231U2-072_GEN5
Solar/Wind Harmer
2.274
253343AC1-166 GEN
Solar/Wind Harmer
1.235
270302AB2-170 GEN
Solar/Wind Harmer
9.522
970179AG2-119 GEN
Solar/Wind Harmer
8.806
253372AE2-315 SEC3
Adder
2.062
253372AE2-315 SEC3
Adder
2.062
25306009OHH W.
Adder
3.128
957201AF2-014 GEN
Solar/Wind Harmer
4.888
253433AC1-085 GEN1
Solar/Wind Harmer
5.708
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.604
963791AG1-232 GEN
Solar/Wind Harmer
14.371
274827FISK ;RP
Adder
7.938
274800UNIV PARK;3U
Adder
5.964
274801UNIV PARK;4U
Adder
5.964
972227AH1-698 GEN1
Adder
2.668
274735ELWOOD EC;4P
Adder
16.762
274744AC1-111 GEN8
Adder
5.677
238169AE2-226 GEN1
Solar/Wind Helper
0.708
238170AE2-226 GEN2
Solar/Wind Helper
0.708
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.36
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.795
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.064
207408W3-077 C
Solar/Wind Helper
0.085
209054AE2-059 GEN
Solar/Wind Helper
0.08
270459AD2-067 GEN
Solar/Wind Harmer
10.212
940611AE2-048 GEN
Solar/Wind Harmer
24.76
941391AE2-136 GEN
Solar/Wind Harmer
12.83
270435AC2-044 GEN
Solar/Wind Harmer
2.156
270007AE1-245 C
Solar/Wind Harmer
5.779
24729505KEY G4
Adder
6.914
971567AH1-282 GEN
Solar/Wind Harmer
5.316
270071AF1-092 GEN
Solar/Wind Harmer
15.971
958711AF2-162 GEN
Solar/Wind Harmer
1.074
25196408WSDLE3
Adder
9.339
25196308WSDLE2
Adder
9.258
25196208WSDLE1
Adder
9.235
25196708WSDLE6
Adder
9.211
270543AE2-219 C
Solar/Wind Harmer
10.561
25196108MFTGT2
Adder
1.598
25196108MFTGT2
Adder
1.484
274728ELWOOD EC;5P
Adder
16.762
20390526W1-045 C
Solar/Wind Helper
0.354
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.078
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.036
957921AF2-086 GEN
Solar/Wind Helper
0.436
270224U2-072_GEN2
Solar/Wind Harmer
2.274
270291AC1-194 GEN
Solar/Wind Harmer
5.61
253406AD2-031_GEN
Solar/Wind Harmer
1.383
965051AG1-369 GEN
Solar/Wind Harmer
5.355
270377AD1-106 GEN
Solar/Wind Harmer
5.62
971985AH1-537 GEN
Solar/Wind Harmer
18.964
945581AF1-223 GEN
Solar/Wind Harmer
4.795
971029AG2-637 GEN
Solar/Wind Harmer
15.851
970031AG2-029 GEN
Solar/Wind Harmer
26.415
270404AC1-167 GEN
Solar/Wind Harmer
1.144
247536S-71 GEN
Solar/Wind Harmer
4.271
961761AG1-017 GEN
Solar/Wind Harmer
0.451
274775LINCOLN ;6U
Adder
8.673
274777LINCOLN ;8U
Adder
8.673
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.789
274675JOLIET 29;7U
Adder
31.291
274675JOLIET 29;7U
Adder
30.174
23750701CROSSCHOOL
Solar/Wind Helper
1.517
205943AE1-185 GEN
Solar/Wind Helper
0.515
233915AB1-141 GEN
Solar/Wind Helper
0.508
228728W1-130C
Solar/Wind Helper
0.055
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
203955AF1-039 C O1
Solar/Wind Helper
0.332
212266LOR1
Solar/Wind Helper
0.302
CPLELTFEXP_CPLE->PJM
CLTF
0.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.743
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.944
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.079
MECLTFEXP_MEC->PJM
CLTF
15.894
SIGELTFEXP_SIGE->PJM
CLTF
0.505
NYPJM->LTFIMP_NY
CLTF
4.85
LGEELTFEXP_LGEE->PJM
CLTF
6.747
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
LAGNLTFEXP_LAGN->PJM
CLTF
14.823
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.742
TVALTFEXP_TVA->PJM
CLTF
7.286

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.4 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4974.31
MW Contribution:
12.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
7.035
270349AD2-093_GEN
Solar/Wind Harmer
4.445
270471AD2-092_GEN
Solar/Wind Harmer
4.445
962761AG1-125 GEN
Solar/Wind Harmer
40.857
270520AE2-214 GEN
Solar/Wind Harmer
7.233
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.008
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.894
971201AH1-060 GEN
Solar/Wind Harmer
1.842
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.845
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.448
274802UNIV PARK;5U
Adder
5.949
274732ELWOOD EC;7P
Adder
16.71
274674JOLIET 9 ;6U
Adder
15.65
235067AD1-061 GEN
Solar/Wind Helper
0.45
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
270120AB2-067 GEN2
50/50
7.082
270054AF2-122 C O1
Solar/Wind Harmer
3.971
938701AE1-092 GEN
Solar/Wind Harmer
23.731
270462AD2-086
Solar/Wind Harmer
7.892
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
960971AF2-388 GEN
Solar/Wind Harmer
11.568
25194408D.CRK1
Adder
7.978
970883AG2-550 GEN
Solar/Wind Harmer
10.531
970349AG2-230 GEN
Solar/Wind Harmer
15.75
270599AE1-208 GEN
Solar/Wind Harmer
8.551
926881AC1-175 GEN
Solar/Wind Harmer
5.845
944231AF1-091 GEN
Solar/Wind Harmer
18.84
24728905RICHG2
Adder
3.949
274808UNIV PK N;4U
Adder
5.099
274674JOLIET 9 ;6U
Adder
15.65
274693ROCKY RD ;1P
Adder
11.121
274683WAUKEGAN ;8U
Adder
21.239
274683WAUKEGAN ;8U
Adder
9.65
23585401KL_K28_T16
Solar/Wind Helper
1.493
238117U2-030
Solar/Wind Helper
0.344
238148AE2-230_GEN2
Solar/Wind Helper
0.5
235062AE1-101 C1
Solar/Wind Helper
1.674
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
270119AB2-067 GEN1
50/50
7.082
253378AE2-206_GEN
Solar/Wind Harmer
3.988
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.273
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.646
274771LINCOLN ;2U
Adder
8.646
274805UNIV PK N;1U
Adder
5.133
274696ROCKY RD ;4P
Adder
11.497
274697ROCKY RD ;3P
Adder
3.051
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.83
237061AD1-155 GEN
Solar/Wind Helper
1.768
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233930AB2-032 GEN
Solar/Wind Helper
0.384
233982AB2-133 GEN
Solar/Wind Helper
0.362
233946AB2-136 GEN
Solar/Wind Helper
0.574
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
270051AF1-062 GEN
50/50
11.783
960801AF2-371 GEN
Solar/Wind Harmer
2.935
964871AG1-351 GEN
Solar/Wind Harmer
2.026
970879AG2-548 GEN
Solar/Wind Harmer
8.757
970065AG2-057 GEN
Solar/Wind Harmer
0.921
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.279
971191AH1-055 GEN
Solar/Wind Harmer
20.022
965021AG1-366 GEN
Solar/Wind Harmer
2.488
270043AE2-236 GEN
Solar/Wind Harmer
5.848
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
270166AC1-044 GEN3
50/50
7.082
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.564
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.696
958861AF2-177 GEN
Solar/Wind Harmer
11.552
252510AF1-249 C
Solar/Wind Harmer
0.44
945371AF1-202 GEN
Solar/Wind Harmer
7.355
270005AE1-210 C O1
Solar/Wind Harmer
5.726
25196808ZIMRHP
Adder
79.465
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
942081AE2-220 GEN
Solar/Wind Harmer
6.698
270209AC1-174_GEN
Solar/Wind Harmer
4.262
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.448
274773LINCOLN ;4U
Adder
8.646
274774LINCOLN ;5U
Adder
8.646
274723RIVER EC ;12
Adder
18.356
946101AF1-275 GEN
Solar/Wind Harmer
1.808
942861AE2-305 GEN
Solar/Wind Harmer
9.053
270269AC2-059
Solar/Wind Harmer
10.554
972159AH1-661 GEN
Adder
1.111
241960AC2-195 GEN
Solar/Wind Harmer
3.053
971073AG2-665 GEN
Solar/Wind Harmer
8.757
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.713
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.41
944541AF1-119 GEN
Solar/Wind Harmer
4.431
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.405
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.551
270383AD1-128 GEN
Solar/Wind Harmer
6.401
247620Y3-023
Adder
0.482
24728805RICHG1
Adder
3.949
274695ROCKY RD ;2P
Adder
11.232
235054AD2-180 GEN
Solar/Wind Helper
2.044
235531U2-073 GEN
Solar/Wind Helper
3.333
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
970155AG2-107 GEN
Solar/Wind Harmer
17.815
971995AH1-542 GEN
Solar/Wind Harmer
12.451
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.241
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.784
252516AE2-318_GEN
Solar/Wind Harmer
10.575
23559001PLEAS1
50/50
6.18
961921AG1-034 GEN
Solar/Wind Harmer
15.539
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.96
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.716
957541AF2-048 GEN
Solar/Wind Harmer
1.713
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.25
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.25
962771AG1-126 GEN
Solar/Wind Harmer
40.857
970153AG2-106 GEN
Solar/Wind Harmer
17.815
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.892
276820AF1-078_GEN
Solar/Wind Harmer
1.772
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
24695305TIMB G C
Solar/Wind Harmer
3.564
270588AE1-091_GEN
Solar/Wind Harmer
11.739
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.7
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.122
24728505AND G1
Adder
3.913
274676JOLIET 29;8U
Adder
30.081
23583801GRNGAP
Solar/Wind Helper
5.632
238126S14_GEN_1
Solar/Wind Helper
0.833
237085AD2-009_GEN
Solar/Wind Helper
1.663
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.235
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.331
270032AE2-172
Solar/Wind Harmer
4.566
24318805MLG1
50/50
10.084
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.795
253325AC1-069 GEN
Solar/Wind Harmer
1.189
972239AH1-704 GEN
Adder
2.673
961821AG1-024 GEN
Solar/Wind Harmer
10.359
945631AF1-228 GEN
Solar/Wind Harmer
5.44
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.013
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.168
241972AD1-140 GEN
Solar/Wind Harmer
4.999
270340AC2-060 GEN
Solar/Wind Harmer
3.323
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.696
965041AG1-368 GEN
Solar/Wind Harmer
10.674
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.955
964611AG1-324 GEN
Solar/Wind Harmer
4.099
274776LINCOLN ;7U
Adder
8.646
274687WILL CNTY;4U
Adder
28.425
274687WILL CNTY;4U
Adder
28.425
274731ELWOOD EC;2P
Adder
16.71
274733ELWOOD EC;3P
Adder
16.71
274746AC1-111 G10
Adder
5.66
238118U2-030_1
Solar/Wind Helper
0.344
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.644
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
241955AC1-078 GEN
Solar/Wind Harmer
8.768
241973AD2-163_GEN1
Solar/Wind Harmer
2.315
241974AD2-163_GEN2
Solar/Wind Harmer
2.315
943861AF1-054 GEN
Solar/Wind Harmer
4.468
943851AF1-053 GEN
Solar/Wind Harmer
2.159
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.8
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.877
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.332
274827FISK ;RP
Adder
7.914
274800UNIV PARK;3U
Adder
5.946
274801UNIV PARK;4U
Adder
5.946
972227AH1-698 GEN1
Adder
2.66
274735ELWOOD EC;4P
Adder
16.71
274744AC1-111 GEN8
Adder
5.66
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
274734ELWOOD EC;8P
Adder
16.71
274736ELWOOD EC;9P
Adder
16.71
274682WAUKEGAN ;7U
Adder
18.122
964991AG1-363 GEN
Solar/Wind Helper
5.16
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.674
205932AD2-116_GEN
Solar/Wind Helper
0.513
233996TM1833_GEN
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.519
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
270459AD2-067 GEN
Solar/Wind Harmer
10.203
940611AE2-048 GEN
Solar/Wind Harmer
24.928
941391AE2-136 GEN
Solar/Wind Harmer
12.917
270435AC2-044 GEN
Solar/Wind Harmer
2.151
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.319
24729505KEY G4
Adder
6.894
270071AF1-092 GEN
Solar/Wind Harmer
15.924
958711AF2-162 GEN
Solar/Wind Harmer
1.071
25196408WSDLE3
Adder
9.314
25196308WSDLE2
Adder
9.233
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.531
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.48
274728ELWOOD EC;5P
Adder
16.71
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
962031AG1-047 GEN
Solar/Wind Harmer
3.18
957741AF2-068 GEN
Solar/Wind Harmer
15.775
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.479
970825AG2-519 GEN
Solar/Wind Harmer
5.897
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.646
274724RIVER EC ;11
Adder
18.141
972259AH1-714 GEN
Adder
19.441
274729ELWOOD EC;1P
Adder
16.71
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.185
316415AF1-147_GEN2
Solar/Wind Helper
0.896
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
270024AE2-089 GEN
Solar/Wind Harmer
4.947
25194608D.CRK4
Adder
1.734
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.122
24728605AND G2
Adder
3.913
274676JOLIET 29;8U
Adder
31.195
972203AH1-686 GEN
Adder
2.333
274745AC1-111 GEN9
Adder
5.66
274682WAUKEGAN ;7U
Adder
18.122
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.674
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.532
23751101LEADS_P59
Solar/Wind Helper
2.129
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
23559101PLEAS2
50/50
6.18
970149AG2-104 GEN
Solar/Wind Harmer
25.229
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
971073AG2-665 GEN
Solar/Wind Harmer
1.273
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
960001AF2-291 GEN
Solar/Wind Harmer
3.242
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.376
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.363
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.448
24728705AND G3
Adder
8.184
274826FISK ;BP
Adder
11.167
274730ELWOOD EC;6P
Adder
16.71
238127S14_GEN_2
Solar/Wind Helper
0.833
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.582
202652Y1-033 WT C
Solar/Wind Helper
0.501
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.603
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.62
965051AG1-369 GEN
Solar/Wind Harmer
5.342
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.781
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.807
970031AG2-029 GEN
Solar/Wind Harmer
26.342
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.646
274777LINCOLN ;8U
Adder
8.646
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.777
274675JOLIET 29;7U
Adder
31.195
274675JOLIET 29;7U
Adder
30.081
23750701CROSSCHOOL
Solar/Wind Helper
1.512
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.507
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
203955AF1-039 C O1
Solar/Wind Helper
0.331
971199AH1-059 GEN
Solar/Wind Harmer
2.315
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270004AE1-209 GEN
Solar/Wind Harmer
5.726
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
24379505HDWTR1G C
Solar/Wind Harmer
8.281
274753CRETE EC ;3U
Adder
8.448
274814UNIV PK N;0U
Adder
5.166
274807UNIV PK N;3U
Adder
5.155
274803UNIV PARK;6U
Adder
5.949
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.015
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.507
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.441
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.371
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.5
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.441
CPLELTFEXP_CPLE->PJM
CLTF
0.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.337
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.966
MECLTFEXP_MEC->PJM
CLTF
15.842
SIGELTFEXP_SIGE->PJM
CLTF
0.503
NYPJM->LTFIMP_NY
CLTF
4.834
LGEELTFEXP_LGEE->PJM
CLTF
6.725
WECLTFEXP_WEC->PJM
CLTF
3.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.682
TVALTFEXP_TVA->PJM
CLTF
7.257

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.01 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4959.97
MW Contribution:
12.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.073
23684101S70BUS1
50/50
0.165
253378AE2-206_GEN
Solar/Wind Harmer
3.989
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.274
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274696ROCKY RD ;4P
Adder
11.494
274697ROCKY RD ;3P
Adder
3.05
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
946101AF1-275 GEN
Solar/Wind Harmer
1.809
942861AE2-305 GEN
Solar/Wind Harmer
9.054
270269AC2-059
Solar/Wind Harmer
10.558
270166AC1-044 GEN3
50/50
7.073
23684201S70BUS2
50/50
0.168
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.576
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.694
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
23583801GRNGAP
Solar/Wind Helper
5.632
238126S14_GEN_1
Solar/Wind Helper
0.83
237085AD2-009_GEN
Solar/Wind Helper
1.662
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
972239AH1-704 GEN
Adder
2.68
961821AG1-024 GEN
Solar/Wind Harmer
10.365
945631AF1-228 GEN
Solar/Wind Harmer
5.442
270223U2-072_GEN1
Solar/Wind Harmer
2.27
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.852
276820AF1-078_GEN
Solar/Wind Harmer
1.772
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.698
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.12
24728505AND G1
Adder
3.912
274676JOLIET 29;8U
Adder
30.072
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.673
205932AD2-116_GEN
Solar/Wind Helper
0.513
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.518
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
270459AD2-067 GEN
Solar/Wind Harmer
10.209
940611AE2-048 GEN
Solar/Wind Harmer
25.038
270051AF1-062 GEN
50/50
11.788
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
970065AG2-057 GEN
Solar/Wind Harmer
0.922
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
971191AH1-055 GEN
Solar/Wind Harmer
20.024
965021AG1-366 GEN
Solar/Wind Harmer
2.487
270043AE2-236 GEN
Solar/Wind Harmer
5.847
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
972259AH1-714 GEN
Adder
19.435
274729ELWOOD EC;1P
Adder
16.705
238175AF1-290_GEN
Solar/Wind Helper
0.158
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
970155AG2-107 GEN
Solar/Wind Harmer
17.802
971995AH1-542 GEN
Solar/Wind Harmer
12.457
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.239
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
24639705ELKHART HY
Adder
0.16
274812UNIV PK N;8U
Adder
5.12
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270340AC2-060 GEN
Solar/Wind Harmer
3.324
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.694
965041AG1-368 GEN
Solar/Wind Harmer
10.672
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.954
964611AG1-324 GEN
Solar/Wind Harmer
4.098
274776LINCOLN ;7U
Adder
8.644
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274746AC1-111 G10
Adder
5.658
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
23559101PLEAS2
50/50
6.109
23559001PLEAS1
50/50
6.109
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.967
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.723
957541AF2-048 GEN
Solar/Wind Harmer
1.714
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.241
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.445
24728705AND G3
Adder
8.182
274826FISK ;BP
Adder
11.164
274730ELWOOD EC;6P
Adder
16.705
238127S14_GEN_2
Solar/Wind Helper
0.83
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.581
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.607
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.625
965051AG1-369 GEN
Solar/Wind Harmer
5.341
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.776
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
23750701CROSSCHOOL
Solar/Wind Helper
1.507
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
970149AG2-104 GEN
Solar/Wind Harmer
25.209
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
960001AF2-291 GEN
Solar/Wind Harmer
3.243
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.346
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
24318805MLG1
50/50
10.069
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
274753CRETE EC ;3U
Adder
8.445
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274803UNIV PARK;6U
Adder
5.948
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.006
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
24318905MLG2
50/50
7.043
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
270120AB2-067 GEN2
50/50
7.073
270054AF2-122 C O1
Solar/Wind Harmer
3.974
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
960971AF2-388 GEN
Solar/Wind Harmer
11.565
25194408D.CRK1
Adder
7.977
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270599AE1-208 GEN
Solar/Wind Harmer
8.55
926881AC1-175 GEN
Solar/Wind Harmer
5.844
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728905RICHG2
Adder
3.948
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274693ROCKY RD ;1P
Adder
11.118
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
23585401KL_K28_T16
Solar/Wind Helper
1.485
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.673
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
962761AG1-125 GEN
Solar/Wind Harmer
40.825
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.01
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.844
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.445
274802UNIV PARK;5U
Adder
5.948
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
972159AH1-661 GEN
Adder
1.114
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
247620Y3-023
Adder
0.482
24728805RICHG1
Adder
3.948
274695ROCKY RD ;2P
Adder
11.229
235054AD2-180 GEN
Solar/Wind Helper
2.035
235531U2-073 GEN
Solar/Wind Helper
3.323
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.805
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.876
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.329
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972227AH1-698 GEN1
Adder
2.659
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.325
24729505KEY G4
Adder
6.892
270071AF1-092 GEN
Solar/Wind Harmer
15.92
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.53
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274728ELWOOD EC;5P
Adder
16.705
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.01 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4959.97
MW Contribution:
12.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.852
276820AF1-078_GEN
Solar/Wind Harmer
1.772
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.698
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.12
24728505AND G1
Adder
3.912
274676JOLIET 29;8U
Adder
30.072
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.673
205932AD2-116_GEN
Solar/Wind Helper
0.513
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.518
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
270051AF1-062 GEN
50/50
11.788
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
970065AG2-057 GEN
Solar/Wind Harmer
0.922
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
971191AH1-055 GEN
Solar/Wind Harmer
20.024
965021AG1-366 GEN
Solar/Wind Harmer
2.487
270043AE2-236 GEN
Solar/Wind Harmer
5.847
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
972259AH1-714 GEN
Adder
19.435
274729ELWOOD EC;1P
Adder
16.705
238175AF1-290_GEN
Solar/Wind Helper
0.158
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
970155AG2-107 GEN
Solar/Wind Harmer
17.802
971995AH1-542 GEN
Solar/Wind Harmer
12.457
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.239
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
24639705ELKHART HY
Adder
0.16
274812UNIV PK N;8U
Adder
5.12
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
972239AH1-704 GEN
Adder
2.68
961821AG1-024 GEN
Solar/Wind Harmer
10.365
945631AF1-228 GEN
Solar/Wind Harmer
5.442
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270340AC2-060 GEN
Solar/Wind Harmer
3.324
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.694
965041AG1-368 GEN
Solar/Wind Harmer
10.672
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.954
964611AG1-324 GEN
Solar/Wind Harmer
4.098
274776LINCOLN ;7U
Adder
8.644
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274746AC1-111 G10
Adder
5.658
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
23559001PLEAS1
50/50
6.109
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.967
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.723
957541AF2-048 GEN
Solar/Wind Harmer
1.714
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.241
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.445
24728705AND G3
Adder
8.182
274826FISK ;BP
Adder
11.164
274730ELWOOD EC;6P
Adder
16.705
238127S14_GEN_2
Solar/Wind Helper
0.83
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.581
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.607
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.625
965051AG1-369 GEN
Solar/Wind Harmer
5.341
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.776
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
23750701CROSSCHOOL
Solar/Wind Helper
1.507
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
23559101PLEAS2
50/50
6.109
970149AG2-104 GEN
Solar/Wind Harmer
25.209
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
960001AF2-291 GEN
Solar/Wind Harmer
3.243
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.346
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
24318805MLG1
50/50
10.069
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
274753CRETE EC ;3U
Adder
8.445
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274803UNIV PARK;6U
Adder
5.948
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.006
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
24318905MLG2
50/50
7.043
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
270120AB2-067 GEN2
50/50
7.073
270054AF2-122 C O1
Solar/Wind Harmer
3.974
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
960971AF2-388 GEN
Solar/Wind Harmer
11.565
25194408D.CRK1
Adder
7.977
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270599AE1-208 GEN
Solar/Wind Harmer
8.55
926881AC1-175 GEN
Solar/Wind Harmer
5.844
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728905RICHG2
Adder
3.948
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274693ROCKY RD ;1P
Adder
11.118
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
23585401KL_K28_T16
Solar/Wind Helper
1.485
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.673
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
270119AB2-067 GEN1
50/50
7.073
23684101S70BUS1
50/50
0.165
253378AE2-206_GEN
Solar/Wind Harmer
3.989
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.274
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274696ROCKY RD ;4P
Adder
11.494
274697ROCKY RD ;3P
Adder
3.05
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
270166AC1-044 GEN3
50/50
7.073
23684201S70BUS2
50/50
0.168
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.576
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.694
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
23583801GRNGAP
Solar/Wind Helper
5.632
238126S14_GEN_1
Solar/Wind Helper
0.83
237085AD2-009_GEN
Solar/Wind Helper
1.662
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
962761AG1-125 GEN
Solar/Wind Harmer
40.825
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.01
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.844
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.445
274802UNIV PARK;5U
Adder
5.948
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
946101AF1-275 GEN
Solar/Wind Harmer
1.809
942861AE2-305 GEN
Solar/Wind Harmer
9.054
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
247620Y3-023
Adder
0.482
24728805RICHG1
Adder
3.948
274695ROCKY RD ;2P
Adder
11.229
235054AD2-180 GEN
Solar/Wind Helper
2.035
235531U2-073 GEN
Solar/Wind Helper
3.323
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.805
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.876
270459AD2-067 GEN
Solar/Wind Harmer
10.209
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.325
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.329
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972227AH1-698 GEN1
Adder
2.659
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
24729505KEY G4
Adder
6.892
270071AF1-092 GEN
Solar/Wind Harmer
15.92
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.53
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274728ELWOOD EC;5P
Adder
16.705
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.87 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4917.49
MW Contribution:
2.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970155AG2-107 GEN
Solar/Wind Harmer
21.963
971995AH1-542 GEN
Solar/Wind Harmer
2.894
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
965421AG1-410 GEN
Solar/Wind Harmer
22.47
972239AH1-704 GEN
Adder
2.678
961821AG1-024 GEN
Solar/Wind Harmer
5.057
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.217
965041AG1-368 GEN
Solar/Wind Harmer
7.438
25196508WSDLE4
Adder
8.944
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.634
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274746AC1-111 G10
Adder
5.652
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.343
270120AB2-067 GEN2
50/50
7.069
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.867
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.048
960971AF2-388 GEN
Solar/Wind Harmer
4.326
25194408D.CRK1
Adder
7.968
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270599AE1-208 GEN
Solar/Wind Harmer
6.701
926881AC1-175 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728905RICHG2
Adder
3.944
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274808UNIV PK N;4U
Adder
5.092
274674JOLIET 9 ;6U
Adder
15.628
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274693ROCKY RD ;1P
Adder
11.106
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
23585401KL_K28_T16
Solar/Wind Helper
1.489
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.672
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
270166AC1-044 GEN3
50/50
7.069
972269AH1-719 GEN
Adder
2.573
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965011AG1-365 GEN
Solar/Wind Harmer
7.453
958861AF2-177 GEN
Solar/Wind Harmer
3.191
252510AF1-249 C
Solar/Wind Harmer
0.056
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.589
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
270119AB2-067 GEN1
50/50
7.069
25326509SID D
Adder
1.446
970879AG2-548 GEN
Solar/Wind Harmer
1.272
246937BC-WTG2
Solar/Wind Harmer
0.302
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970623AG2-406 GEN
Solar/Wind Harmer
1.351
942221AE2-234 GEN
Solar/Wind Harmer
2.958
970621AG2-405 GEN
Solar/Wind Harmer
1.345
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.126
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
274696ROCKY RD ;4P
Adder
11.481
274697ROCKY RD ;3P
Adder
3.047
962691AG1-118 GEN
Solar/Wind Harmer
21.036
942111AE2-223 GEN
Solar/Wind Harmer
2.266
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.895
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.732
970613AG2-401 GEN
Solar/Wind Harmer
5.351
24639705ELKHART HY
Adder
0.16
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
274676JOLIET 29;8U
Adder
31.151
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
18.096
316095T157 G97
Solar/Wind Helper
1.51
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
252519AF1-045_GEN
Solar/Wind Harmer
3.844
25194608D.CRK4
Adder
1.732
946031AF1-268 GEN
Solar/Wind Harmer
6.95
970289AG2-191 GEN
Solar/Wind Harmer
0.8
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
5.114
24728505AND G1
Adder
3.908
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274676JOLIET 29;8U
Adder
30.039
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
274682WAUKEGAN ;7U
Adder
18.096
964991AG1-363 GEN
Solar/Wind Helper
5.155
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.672
205932AD2-116_GEN
Solar/Wind Helper
0.512
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.868
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.516
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
959091AF2-200 GEN
Solar/Wind Harmer
9.057
942861AE2-305 GEN
Solar/Wind Harmer
6.31
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
971073AG2-665 GEN
Solar/Wind Harmer
5.597
25326109MON D
Adder
1.437
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.492
25194508D.CRK3
Adder
1.49
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970885AG2-551 GEN
Solar/Wind Harmer
2.446
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270031AE2-169
Solar/Wind Harmer
4.021
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
24728805RICHG1
Adder
3.944
24699105WLD G1 C
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.638
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
10.234
274695ROCKY RD ;2P
Adder
11.216
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
2.04
235531U2-073 GEN
Solar/Wind Helper
3.327
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.118
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
316045AC1-158 PL2
Solar/Wind Helper
4.17
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
23559101PLEAS2
50/50
6.097
970149AG2-104 GEN
Solar/Wind Harmer
18.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
971917AH1-482 GEN
Solar/Wind Harmer
9.365
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
276882AE2-255 GEN
Solar/Wind Harmer
0.818
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.274
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
23559001PLEAS1
50/50
6.097
961921AG1-034 GEN
Solar/Wind Harmer
7.586
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
944531AF1-118 GEN
Solar/Wind Harmer
33.233
25196608WSDLE5
Adder
9.036
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
3.658
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
24728705AND G3
Adder
8.173
274887GEN-1.85
Solar/Wind Harmer
0.185
274826FISK ;BP
Adder
11.151
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
274730ELWOOD EC;6P
Adder
16.687
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
970193AG2-126 GEN
Solar/Wind Harmer
10.468
238127S14_GEN_2
Solar/Wind Helper
0.831
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.303
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
962761AG1-125 GEN
Solar/Wind Harmer
34.394
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.807
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.095
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.436
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.941
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
939401AE1-172 GEN
Solar/Wind Harmer
5.275
962781AG1-127 GEN
Solar/Wind Harmer
6.668
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.441
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.559
270377AD1-106 GEN
Solar/Wind Harmer
2.842
965051AG1-369 GEN
Solar/Wind Harmer
3.723
971985AH1-537 GEN
Solar/Wind Harmer
2.196
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
247536S-71 GEN
Solar/Wind Harmer
0.293
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
274775LINCOLN ;6U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
972228AH1-698 GEN2
Adder
3.772
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
971411AH1-196 GEN
Solar/Wind Harmer
10.47
23750701CROSSCHOOL
Solar/Wind Helper
1.509
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
270051AF1-062 GEN
50/50
11.777
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
971191AH1-055 GEN
Solar/Wind Harmer
19.175
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270043AE2-236 GEN
Solar/Wind Harmer
4.754
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
945111AF1-176 GEN
Solar/Wind Harmer
5.891
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
972167AH1-666 GEN
Solar/Wind Harmer
5.69
972259AH1-714 GEN
Adder
19.413
274729ELWOOD EC;1P
Adder
16.687
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970571AG2-364 GEN
Solar/Wind Harmer
13.944
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
233944AB2-135 GEN
Solar/Wind Helper
0.594
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.843
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
270246TR4_N_V150
Solar/Wind Harmer
0.048
247621Y3-024
Adder
0.253
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
965681AG1-436 GEN
Solar/Wind Harmer
9.052
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.758
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.51
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.344
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
24318805MLG1
50/50
10.065
270475AD2-096_GEN
50/50
7.114
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
970191AG2-125 GEN
Solar/Wind Harmer
1.937
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.436
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274803UNIV PARK;6U
Adder
5.941
276843GEN-1.7
Solar/Wind Harmer
0.23
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.012
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.512
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270007AE1-245 C
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
270071AF1-092 GEN
Solar/Wind Harmer
14.177
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
270543AE2-219 C
Solar/Wind Harmer
5.137
971771AH1-392 GEN
Solar/Wind Harmer
7.271
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
971549AH1-272 GEN
Solar/Wind Harmer
14.794
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.687
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.062
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
209027LOR2_Q27
Solar/Wind Helper
1.031
25196008MFTGT1
Adder
1.443
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.68
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
23583801GRNGAP
Solar/Wind Helper
5.626
238126S14_GEN_1
Solar/Wind Helper
0.831
237085AD2-009_GEN
Solar/Wind Helper
1.661
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.792
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
970179AG2-119 GEN
Solar/Wind Harmer
6.854
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.27
963791AG1-232 GEN
Solar/Wind Harmer
9.987
970289AG2-191 GEN
Solar/Wind Harmer
1.382
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972227AH1-698 GEN1
Adder
2.656
274735ELWOOD EC;4P
Adder
16.687
274744AC1-111 GEN8
Adder
5.652
970169AG2-114 GEN
Solar/Wind Harmer
7.011
959341AF2-225 GEN
Solar/Wind Harmer
7.32
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.057
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
957471AF2-041 GEN
Solar/Wind Harmer
13.586
20675428EAM_W2-061
Solar/Wind Helper
0.016
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.58
202652Y1-033 WT C
Solar/Wind Helper
0.5
20675828AU_W4-064
Solar/Wind Helper
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.69 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4873.53
MW Contribution:
12.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
23559001PLEAS1
50/50
5.445
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
970149AG2-104 GEN
Solar/Wind Harmer
25.235
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
971073AG2-665 GEN
Solar/Wind Harmer
1.284
270297AD1-101 GEN
Solar/Wind Harmer
2.226
270258AD1-119 GEN
Solar/Wind Harmer
2.219
960001AF2-291 GEN
Solar/Wind Harmer
3.236
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
23920202STRYCT
Adder
1.44
23546401DTGZ2-030
Solar/Wind Helper
0.1
237038AE2-054 C
Solar/Wind Helper
0.294
3132273ORANGE
Solar/Wind Helper
0.049
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
232417X3-008 C
Solar/Wind Helper
0.238
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
970155AG2-107 GEN
Solar/Wind Harmer
17.82
971995AH1-542 GEN
Solar/Wind Harmer
12.942
965421AG1-410 GEN
Solar/Wind Harmer
33.164
253370AE2-315 SEC1
Adder
2.2
270119AB2-067 GEN1
50/50
7.05
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
246937BC-WTG2
Solar/Wind Harmer
4.329
970879AG2-548 GEN
Solar/Wind Harmer
1.284
247607V1-011 GEN
Solar/Wind Harmer
4.348
247522W1-056 GEN
Solar/Wind Harmer
2.469
942221AE2-234 GEN
Solar/Wind Harmer
3.759
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
237061AD1-155 GEN
Solar/Wind Helper
1.974
235020AA1-095 C
Solar/Wind Helper
0.058
238221AF1-254 C O1
Solar/Wind Helper
0.297
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
223402AF1-300 C
Solar/Wind Helper
0.389
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
233946AB2-136 GEN
Solar/Wind Helper
0.581
232410W1-006 C
Solar/Wind Helper
0.518
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
270120AB2-067 GEN2
50/50
7.05
270054AF2-122 C O1
Solar/Wind Harmer
4.054
938701AE1-092 GEN
Solar/Wind Harmer
24.428
270462AD2-086
Solar/Wind Harmer
8.12
253415AE1-040 GEN
Solar/Wind Harmer
1.252
942801AE2-298 GEN
Solar/Wind Harmer
1.666
270247TR4_N_V136
Solar/Wind Harmer
0.933
253349AC2-067 GEN
Solar/Wind Harmer
2.225
944231AF1-091 GEN
Solar/Wind Harmer
19.433
960971AF2-388 GEN
Solar/Wind Harmer
11.731
970349AG2-230 GEN
Solar/Wind Harmer
16.027
970883AG2-550 GEN
Solar/Wind Harmer
10.668
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
24728905RICHG2
Adder
3.989
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
238148AE2-230_GEN2
Solar/Wind Helper
0.556
23585401KL_K28_T16
Solar/Wind Helper
1.534
238117U2-030
Solar/Wind Helper
0.357
235062AE1-101 C1
Solar/Wind Helper
1.786
237006AB1-125 GEN
Solar/Wind Helper
0.132
223401AF1-299 GEN
Solar/Wind Helper
0.389
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
24318805MLG1
50/50
10
270518AE2-148 GEN
Solar/Wind Harmer
13.997
971199AH1-059 GEN
Solar/Wind Harmer
2.432
253325AC1-069 GEN
Solar/Wind Harmer
1.205
961961AG1-039 GEN
Solar/Wind Harmer
3.18
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
274753CRETE EC ;3U
Adder
8.571
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274803UNIV PARK;6U
Adder
6.031
972038AH1-567 GEN2
Adder
0.377
238108AE1-109 GEN1
Solar/Wind Helper
0.122
237001AB1-127_GEN
Solar/Wind Helper
0.476
23562501BACKB
Solar/Wind Helper
1
233918AB1-142 GEN
Solar/Wind Helper
0.514
228729W2-030 C
Solar/Wind Helper
0.112
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
24318905MLG2
50/50
7.451
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
253383AE2-342_GEN
Solar/Wind Harmer
1.057
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
247621Y3-024
Adder
0.257
970935AG2-582 GEN
Adder
238.716
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
237080AD1-060 GEN
Solar/Wind Helper
0.369
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
270166AC1-044 GEN3
50/50
7.05
972269AH1-719 GEN
Adder
2.693
270485AE1-090_GEN
Solar/Wind Harmer
0.706
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965011AG1-365 GEN
Solar/Wind Harmer
10.939
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
958861AF2-177 GEN
Solar/Wind Harmer
11.712
945371AF1-202 GEN
Solar/Wind Harmer
7.453
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25196808ZIMRHP
Adder
79.955
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
23583801GRNGAP
Solar/Wind Helper
6.383
238126S14_GEN_1
Solar/Wind Helper
0.87
237085AD2-009_GEN
Solar/Wind Helper
1.776
3141196NOKESVL
Solar/Wind Helper
1.144
226910AB2-157 C
Solar/Wind Helper
0.016
233933AB2-153 GEN
Solar/Wind Helper
0.238
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.777
960841AF2-375 GEN
Solar/Wind Harmer
0.624
946101AF1-275 GEN
Solar/Wind Harmer
1.838
942861AE2-305 GEN
Solar/Wind Harmer
9.201
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
25326109MON D
Adder
1.457
971073AG2-665 GEN
Solar/Wind Harmer
8.835
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944541AF1-119 GEN
Solar/Wind Harmer
4.494
247620Y3-023
Adder
0.492
25183208HLCRTG
Solar/Wind Harmer
6.454
970885AG2-551 GEN
Solar/Wind Harmer
2.481
270201AC2-176 GEN
Solar/Wind Harmer
5.48
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
238149AF1-291A_GEN
Solar/Wind Helper
0.159
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
316006AB2-029 C
Solar/Wind Helper
0.131
316045AC1-158 PL2
Solar/Wind Helper
4.643
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
219912AD2-042 GEN
Solar/Wind Helper
0.152
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
20674328GAR_V4-001
Solar/Wind Helper
0.023
972239AH1-704 GEN
50/50
3.095
961821AG1-024 GEN
Solar/Wind Harmer
10.588
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270432AC2-029 GEN
Solar/Wind Harmer
8.117
253338AC1-165 GEN
Solar/Wind Harmer
1.249
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270340AC2-060 GEN
Solar/Wind Harmer
3.354
270191TR4_S_V150
Solar/Wind Harmer
3.29
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
270499AE1-146 GEN
Solar/Wind Harmer
2.679
964611AG1-324 GEN
Solar/Wind Harmer
4.154
25196508WSDLE4
Adder
9.023
274776LINCOLN ;7U
Adder
8.764
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
23779801AA1-109
Solar/Wind Helper
0.208
226929AD2-058 GEN
Solar/Wind Helper
0.108
316164AC1-076 GEN
Solar/Wind Helper
1.232
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
270302AB2-170 GEN
Solar/Wind Harmer
9.776
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253343AC1-166 GEN
Solar/Wind Harmer
1.249
957201AF2-014 GEN
Solar/Wind Harmer
5.019
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
25306009OHH W.
Adder
3.158
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
944161AF1-084 GEN
Solar/Wind Harmer
2.352
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972227AH1-698 GEN1
Adder
2.695
274735ELWOOD EC;4P
Adder
16.929
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
315651AD1-115 GEN
Solar/Wind Helper
0.883
959381AF2-229 GEN
Solar/Wind Helper
0.368
232432Z2-076 GEN
Solar/Wind Helper
0.068
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
24721905FLATG4
Adder
23.444
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
24695305TIMB G C
Solar/Wind Harmer
3.661
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
247643Z2-116 C
Solar/Wind Harmer
0.074
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25194608D.CRK4
Adder
1.747
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
274811UNIV PK N;7U
Adder
5.194
274676JOLIET 29;8U
Adder
30.477
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238110AE1-109 GEN3
Solar/Wind Helper
0.122
235063AE1-101 C2
Solar/Wind Helper
1.786
316447AC1-158 HLD
Solar/Wind Helper
3.193
205932AD2-116_GEN
Solar/Wind Helper
0.521
232426Y1-080 FULL
Solar/Wind Helper
0.04
233996TM1833_GEN
Solar/Wind Helper
0.21
316192AB2-158 GEN
Solar/Wind Helper
1.618
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
962761AG1-125 GEN
Solar/Wind Harmer
40.867
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270317AD1-130_GEN
Solar/Wind Harmer
3.738
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
25326309TAIT D
Adder
1.207
270216AD2-079_GEN
Solar/Wind Harmer
0.645
944031AF1-071 GEN
Solar/Wind Harmer
1.069
274754CRETE EC ;4U
Adder
8.571
274802UNIV PARK;5U
Adder
6.031
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
235067AD1-061 GEN
Solar/Wind Helper
0.481
237002AB1-128_GEN
Solar/Wind Helper
0.477
208835TUHI V3-051
Solar/Wind Helper
0.022
3147666LOUISA
Solar/Wind Helper
0.553
233950AC2-186 GEN
Solar/Wind Helper
0.119
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.313
217169METRODIV C
Solar/Wind Helper
0.004
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
958581AF2-149 GEN
Solar/Wind Harmer
4.955
958091AF2-103 GEN
Solar/Wind Harmer
0.178
957541AF2-048 GEN
Solar/Wind Harmer
1.72
944531AF1-118 GEN
Solar/Wind Harmer
37.819
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971347AH1-153 GEN
Solar/Wind Harmer
5.342
25196608WSDLE5
Adder
9.116
274752CRETE EC ;2U
Adder
8.571
274826FISK ;BP
Adder
11.319
274730ELWOOD EC;6P
Adder
16.929
238152AF2-075_GEN
Solar/Wind Helper
0.794
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
316044AC1-158 PL1
Solar/Wind Helper
1.451
208835TUHI V3-051
Solar/Wind Helper
0.022
3147666LOUISA
Solar/Wind Helper
0.962
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.573
270459AD2-067 GEN
Solar/Wind Harmer
10.428
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
971567AH1-282 GEN
Solar/Wind Harmer
5.635
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
958711AF2-162 GEN
Solar/Wind Harmer
1.086
270543AE2-219 C
Solar/Wind Harmer
10.668
971771AH1-392 GEN
Solar/Wind Harmer
9.58
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274728ELWOOD EC;5P
Adder
16.929
3141426STAFORD
Solar/Wind Helper
0.058
20390526W1-045 C
Solar/Wind Helper
0.361
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.234
219258KINSLEYDEP C
Solar/Wind Helper
0.078
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
270051AF1-062 GEN
50/50
11.971
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
970065AG2-057 GEN
Solar/Wind Harmer
0.972
246938BC-WTG3
Solar/Wind Harmer
4.404
970879AG2-548 GEN
Solar/Wind Harmer
8.835
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
270043AE2-236 GEN
Solar/Wind Harmer
5.961
971191AH1-055 GEN
Solar/Wind Harmer
20.005
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
270367AC2-061_GEN
Solar/Wind Harmer
3.375
25196008MFTGT1
Adder
1.409
274724RIVER EC ;11
Adder
18.401
274772LINCOLN ;3U
Adder
8.764
972259AH1-714 GEN
Adder
19.698
274729ELWOOD EC;1P
Adder
16.929
238175AF1-290_GEN
Solar/Wind Helper
0.173
316415AF1-147_GEN2
Solar/Wind Helper
0.984
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
233944AB2-135 GEN
Solar/Wind Helper
0.603
232408W1-005 C
Solar/Wind Helper
0.518
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.084
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
253371AE2-315 SEC2
Adder
2.081
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
24639705ELKHART HY
Adder
0.164
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
25194608D.CRK4
Adder
1.747
23906502RICHG2&3
Adder
1.268
274812UNIV PK N;8U
Adder
5.194
274676JOLIET 29;8U
Adder
31.606
316095T157 G97
Solar/Wind Helper
1.71
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
238120AE2-309 GEN
Solar/Wind Helper
0.557
23777801MSM_W1-116
Solar/Wind Helper
0.123
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
232422X3-066 FULL
Solar/Wind Helper
0.117
233964AF2-378 GEN
Solar/Wind Helper
0.043
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
966881AG1-559 GEN
Solar/Wind Helper
0.313
205941AD2-115 GEN
Solar/Wind Helper
0.499
232424Y1-079 C
Solar/Wind Helper
0.119
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
966001AG1-469 GEN
Solar/Wind Helper
0.256
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.293
20675428EAM_W2-061
Solar/Wind Helper
0.016
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270377AD1-106 GEN
Solar/Wind Harmer
5.917
270291AC1-194 GEN
Solar/Wind Harmer
5.669
965051AG1-369 GEN
Solar/Wind Harmer
5.479
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
274775LINCOLN ;6U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
972228AH1-698 GEN2
Adder
3.828
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
23750701CROSSCHOOL
Solar/Wind Helper
1.591
205943AE1-185 GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
228728W1-130C
Solar/Wind Helper
0.055
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
205956AE1-196_GEN
Solar/Wind Helper
0.521
233901CHERRYDALE C
Solar/Wind Helper
0.238
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
211065PSPA IPP
Solar/Wind Helper
0.151
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
MECLTFEXP_MEC->PJM
CLTF
15.924
SIGELTFEXP_SIGE->PJM
CLTF
0.504
NYPJM->LTFIMP_NY
CLTF
4.574
LGEELTFEXP_LGEE->PJM
CLTF
6.731
WECLTFEXP_WEC->PJM
CLTF
3.853
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4632.89
MW Contribution:
2.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962761AG1-125 GEN
Solar/Wind Harmer
33.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.78
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.818
958381AF2-132 GEN
Solar/Wind Harmer
0.001
24318805MLG1
50/50
9.823
270518AE2-148 GEN
Solar/Wind Harmer
0.631
972239AH1-704 GEN
50/50
2.774
961821AG1-024 GEN
Solar/Wind Harmer
4.899
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.044
965041AG1-368 GEN
Solar/Wind Harmer
7.193
25196508WSDLE4
Adder
8.634
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.341
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
23750501ELLIOTTS
Solar/Wind Helper
0.573
205956AE1-196_GEN
Solar/Wind Helper
0.494
233901CHERRYDALE C
Solar/Wind Helper
0.226
20715028HAN_X4-015
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
20720628TIN_W1-124
Solar/Wind Helper
0.184
270166AC1-044 GEN3
50/50
6.887
972269AH1-719 GEN
Adder
2.495
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965011AG1-365 GEN
Solar/Wind Harmer
7.206
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252510AF1-249 C
Solar/Wind Harmer
0.054
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
25196008MFTGT1
Adder
1.393
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.554
970569AG2-363 GEN
Solar/Wind Harmer
20.202
939741AE1-205 GEN
Solar/Wind Harmer
9.427
23583801GRNGAP
Solar/Wind Helper
5.433
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.596
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.226
219623KINSLEYBEA C
Solar/Wind Helper
0.002
970155AG2-107 GEN
Solar/Wind Harmer
21.201
971995AH1-542 GEN
Solar/Wind Harmer
2.804
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965651AG1-433 GEN
Solar/Wind Harmer
2.09
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.672
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.941
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
274676JOLIET 29;8U
Adder
30.093
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.459
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.111
227287AC2-120 GEN
Solar/Wind Helper
0.337
232422X3-066 FULL
Solar/Wind Helper
0.111
233964AF2-378 GEN
Solar/Wind Helper
0.041
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.481
957471AF2-041 GEN
Solar/Wind Harmer
13.123
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.753
970935AG2-582 GEN
Adder
241.832
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.046
247621Y3-024
Adder
0.245
971613AH1-306 GEN
Solar/Wind Harmer
3.374
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
965681AG1-436 GEN
Solar/Wind Harmer
8.747
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.732
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
237080AD1-060 GEN
Solar/Wind Helper
0.332
219904AC1-010 C
Solar/Wind Helper
0.059
219906AC1-017 C
Solar/Wind Helper
0.041
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
270120AB2-067 GEN2
50/50
6.887
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.459
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.046
960971AF2-388 GEN
Solar/Wind Harmer
4.179
25194408D.CRK1
Adder
7.692
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270599AE1-208 GEN
Solar/Wind Harmer
6.473
944231AF1-091 GEN
Solar/Wind Harmer
16.273
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.809
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.919
966841AG1-555 GEN
Solar/Wind Harmer
0.78
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238117U2-030
Solar/Wind Helper
0.315
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
232424Y1-079 C
Solar/Wind Helper
0.113
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
316450AC1-158 RIC
Solar/Wind Helper
0.336
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.282
942861AE2-305 GEN
Solar/Wind Harmer
6.105
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
25194508D.CRK3
Adder
1.438
970885AG2-551 GEN
Solar/Wind Harmer
2.363
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
270031AE2-169
Solar/Wind Harmer
3.884
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.465
24728805RICHG1
Adder
3.809
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
9.886
958491AF2-143 GEN
Solar/Wind Harmer
10.177
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
316006AB2-029 C
Solar/Wind Helper
0.114
232436AB1-176 C
Solar/Wind Helper
0.043
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
316045AC1-158 PL2
Solar/Wind Helper
4.03
219912AD2-042 GEN
Solar/Wind Helper
0.146
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971985AH1-537 GEN
Solar/Wind Harmer
2.117
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
247536S-71 GEN
Solar/Wind Harmer
0.283
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
274775LINCOLN ;6U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
972228AH1-698 GEN2
Adder
3.644
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.63
971411AH1-196 GEN
Solar/Wind Harmer
10.113
23750701CROSSCHOOL
Solar/Wind Helper
1.401
205943AE1-185 GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
228728W1-130C
Solar/Wind Helper
0.052
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.026
219620RIDERU C
Solar/Wind Helper
0.001
971171AH1-044 GEN
Solar/Wind Harmer
8.748
23559001PLEAS1
50/50
5.39
961921AG1-034 GEN
Solar/Wind Harmer
7.349
942051AE2-217 GEN
Solar/Wind Harmer
14.139
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
944531AF1-118 GEN
Solar/Wind Harmer
32.112
25196608WSDLE5
Adder
8.723
219612MATRIX C
Solar/Wind Helper
0.023
20716928W4-060COL
Solar/Wind Helper
0.05
270119AB2-067 GEN1
50/50
6.887
25326509SID D
Adder
1.398
970879AG2-548 GEN
Solar/Wind Harmer
1.228
246937BC-WTG2
Solar/Wind Harmer
0.292
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
24387305FR-4G C
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
962691AG1-118 GEN
Solar/Wind Harmer
20.32
942111AE2-223 GEN
Solar/Wind Harmer
2.188
235020AA1-095 C
Solar/Wind Helper
0.051
237061AD1-155 GEN
Solar/Wind Helper
1.703
238221AF1-254 C O1
Solar/Wind Helper
0.267
316411AF1-147_GEN1
Solar/Wind Helper
0.865
223402AF1-300 C
Solar/Wind Helper
0.357
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
233946AB2-136 GEN
Solar/Wind Helper
0.553
232410W1-006 C
Solar/Wind Helper
0.493
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
970179AG2-119 GEN
Solar/Wind Harmer
6.643
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.261
963791AG1-232 GEN
Solar/Wind Harmer
9.652
970289AG2-191 GEN
Solar/Wind Harmer
1.334
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972227AH1-698 GEN1
Adder
2.566
274735ELWOOD EC;4P
Adder
16.119
970169AG2-114 GEN
Solar/Wind Harmer
6.772
959341AF2-225 GEN
Solar/Wind Harmer
7.07
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
959381AF2-229 GEN
Solar/Wind Helper
0.346
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230407AD2-065 C
Solar/Wind Helper
0.039
20720728JCB_W1-129
Solar/Wind Helper
0.055
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
970149AG2-104 GEN
Solar/Wind Harmer
17.929
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
971917AH1-482 GEN
Solar/Wind Harmer
9.046
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.086
237038AE2-054 C
Solar/Wind Helper
0.264
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
232417X3-008 C
Solar/Wind Helper
0.226
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
22.814
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
24695305TIMB G C
Solar/Wind Harmer
0.609
252519AF1-045_GEN
Solar/Wind Harmer
3.711
25194608D.CRK4
Adder
1.672
946031AF1-268 GEN
Solar/Wind Harmer
6.713
970289AG2-191 GEN
Solar/Wind Harmer
0.773
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
4.941
276806AD2-047 C O1
Solar/Wind Harmer
3.89
24728505AND G1
Adder
3.773
274676JOLIET 29;8U
Adder
29.018
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
964991AG1-363 GEN
Solar/Wind Helper
4.979
238110AE1-109 GEN3
Solar/Wind Helper
0.107
235063AE1-101 C2
Solar/Wind Helper
1.608
205932AD2-116_GEN
Solar/Wind Helper
0.494
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
316447AC1-158 HLD
Solar/Wind Helper
2.771
219766PARADISE C
Solar/Wind Helper
0.053
203975AE1-071-GEN
Solar/Wind Helper
2.421
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
959091AF2-200 GEN
Solar/Wind Harmer
8.748
270051AF1-062 GEN
50/50
11.411
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
270043AE2-236 GEN
Solar/Wind Harmer
4.595
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
270505AE1-170 C O1
Solar/Wind Harmer
7.374
25196008MFTGT1
Adder
1.349
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
972167AH1-666 GEN
Solar/Wind Harmer
5.491
972259AH1-714 GEN
Adder
18.754
274729ELWOOD EC;1P
Adder
16.119
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970571AG2-364 GEN
Solar/Wind Harmer
13.468
238175AF1-290_GEN
Solar/Wind Helper
0.152
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
205916AD1-020 GEN
Solar/Wind Helper
1.664
233944AB2-135 GEN
Solar/Wind Helper
0.573
232408W1-005 C
Solar/Wind Helper
0.493
219907AC1-030 C
Solar/Wind Helper
0.033
20716028EGP_W2-019
Solar/Wind Helper
0.018
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
970191AG2-125 GEN
Solar/Wind Harmer
1.872
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.15
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
276843GEN-1.7
Solar/Wind Harmer
0.222
972038AH1-567 GEN2
Adder
0.359
238108AE1-109 GEN1
Solar/Wind Helper
0.107
237001AB1-127_GEN
Solar/Wind Helper
0.428
23562501BACKB
Solar/Wind Helper
0.845
233918AB1-142 GEN
Solar/Wind Helper
0.488
228729W2-030 C
Solar/Wind Helper
0.107
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
971347AH1-153 GEN
Solar/Wind Harmer
3.535
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274887GEN-1.85
Solar/Wind Harmer
0.178
274826FISK ;BP
Adder
10.773
24728705AND G3
Adder
7.891
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274730ELWOOD EC;6P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
970193AG2-126 GEN
Solar/Wind Harmer
10.106
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
208835TUHI V3-051
Solar/Wind Helper
0.021
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
316044AC1-158 PL1
Solar/Wind Helper
1.259
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
274754CRETE EC ;4U
Adder
8.15
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
939401AE1-172 GEN
Solar/Wind Harmer
5.095
962781AG1-127 GEN
Solar/Wind Harmer
6.441
235067AD1-061 GEN
Solar/Wind Helper
0.432
237002AB1-128_GEN
Solar/Wind Helper
0.43
208835TUHI V3-051
Solar/Wind Helper
0.021
233950AC2-186 GEN
Solar/Wind Helper
0.113
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
207454AA2-184 E
Solar/Wind Helper
0.301
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270435AC2-044 GEN
Solar/Wind Harmer
0.918
971567AH1-282 GEN
Solar/Wind Harmer
5.517
270007AE1-245 C
Solar/Wind Harmer
0
24729505KEY G4
Adder
6.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
270543AE2-219 C
Solar/Wind Harmer
4.962
971771AH1-392 GEN
Solar/Wind Harmer
7.027
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
971549AH1-272 GEN
Solar/Wind Harmer
14.305
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.119
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
20390526W1-045 C
Solar/Wind Helper
0.339
3141426STAFORD
Solar/Wind Helper
0.051
233940AF2-379 C
Solar/Wind Helper
0.06
230434AG1-499 GEN
Solar/Wind Helper
0.223
219258KINSLEYDEP C
Solar/Wind Helper
0.075
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.82 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1646.06
MW Contribution:
11.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270284AF1-227 GEN1
Solar/Wind Harmer
6.84
276820AF1-078_GEN
Solar/Wind Harmer
1.068
962771AG1-126 GEN
Solar/Wind Harmer
20.895
970153AG2-106 GEN
Solar/Wind Harmer
9.111
24695305TIMB G C
Solar/Wind Harmer
1.831
270588AE1-091_GEN
Solar/Wind Harmer
5.505
960071AF2-298 GEN
Solar/Wind Harmer
0.73
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
247643Z2-116 C
Solar/Wind Harmer
0.032
946031AF1-268 GEN
Solar/Wind Harmer
3.655
972181SS23-001
Solar/Wind Harmer
2.592
276164X3-005 C
Solar/Wind Harmer
0.306
274811UNIV PK N;7U
Adder
2.178
970289AG2-191 GEN
Solar/Wind Harmer
0.333
247642Z2-115 C
Solar/Wind Harmer
0.028
276806AD2-047 C O1
Solar/Wind Harmer
4.627
270227U2-072_GEN3
Solar/Wind Harmer
1.974
270228U2-072_GEN4
Solar/Wind Harmer
1.974
270231U2-072_GEN5
Solar/Wind Harmer
1.974
241973AD2-163_GEN1
Solar/Wind Harmer
1.951
241974AD2-163_GEN2
Solar/Wind Harmer
1.951
270302AB2-170 GEN
Solar/Wind Harmer
7.816
970179AG2-119 GEN
Solar/Wind Harmer
6.791
241955AC1-078 GEN
Solar/Wind Harmer
4.994
957201AF2-014 GEN
Solar/Wind Harmer
2.726
247521TR3_G114
Solar/Wind Harmer
1.861
943861AF1-054 GEN
Solar/Wind Harmer
1.939
943851AF1-053 GEN
Solar/Wind Harmer
0.937
963791AG1-232 GEN
Solar/Wind Harmer
6.712
253343AC1-166 GEN
Solar/Wind Harmer
0.524
25306009OHH W.
Adder
1.341
253372AE2-315 SEC3
Adder
0.879
253372AE2-315 SEC3
Adder
0.879
944161AF1-084 GEN
Solar/Wind Harmer
0.999
970289AG2-191 GEN
Solar/Wind Harmer
0.824
274827FISK ;RP
Adder
3.358
274800UNIV PARK;3U
Adder
2.522
274801UNIV PARK;4U
Adder
2.522
972227AH1-698 GEN1
Adder
1.127
270287AF1-227 GEN3
Solar/Wind Harmer
2.53
942871AE2-306 GEN
Solar/Wind Harmer
0.907
270391AF1-285 GEN3
Solar/Wind Harmer
0.465
942051AE2-217 GEN
Solar/Wind Harmer
13.98
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270063AE2-323 C
Solar/Wind Harmer
1.052
944531AF1-118 GEN
Solar/Wind Harmer
16.732
270541AE2-072 C
Solar/Wind Harmer
2.158
971347AH1-153 GEN
Solar/Wind Harmer
2.305
972231SS25-0005
Solar/Wind Harmer
4.147
274752CRETE EC ;2U
Adder
2.136
274826FISK ;BP
Adder
4.738
274887GEN-1.85
Solar/Wind Harmer
2.304
276772AC2-154 GEN
Solar/Wind Harmer
1.207
970707AG2-453 GEN
Solar/Wind Harmer
11.087
270466AD2-091
50/50
5.428
938701AE1-092 GEN
Solar/Wind Harmer
21.99
270462AD2-086
Solar/Wind Harmer
6.492
942801AE2-298 GEN
Solar/Wind Harmer
0.86
270247TR4_N_V136
Solar/Wind Harmer
0.471
944231AF1-091 GEN
Solar/Wind Harmer
8.795
253349AC2-067 GEN
Solar/Wind Harmer
0.96
960971AF2-388 GEN
Solar/Wind Harmer
5.068
970349AG2-230 GEN
Solar/Wind Harmer
6.915
961051AF2-396 GEN
Solar/Wind Harmer
7.218
961051AF2-396 GEN
Solar/Wind Harmer
3.357
270599AE1-208 GEN
Solar/Wind Harmer
3.645
970883AG2-550 GEN
Solar/Wind Harmer
4.458
274808UNIV PK N;4U
Adder
2.168
270054AF2-122 C O1
Solar/Wind Helper
0.827
970065AG2-057 GEN
Solar/Wind Harmer
0.651
246938BC-WTG3
Solar/Wind Harmer
2.392
965021AG1-366 GEN
Solar/Wind Harmer
1.232
270044AE2-322 C
Solar/Wind Harmer
0.692
270043AE2-236 GEN
Solar/Wind Harmer
2.704
945111AF1-176 GEN
Solar/Wind Harmer
2.583
270505AE1-170 C O1
Solar/Wind Harmer
6.831
962031AG1-047 GEN
Solar/Wind Harmer
1.364
957741AF2-068 GEN
Solar/Wind Harmer
6.767
970825AG2-519 GEN
Solar/Wind Harmer
2.467
274772LINCOLN ;3U
Adder
2.707
274724RIVER EC ;11
Adder
7.731
270485AE1-090_GEN
Solar/Wind Harmer
0.565
246936BC-WTG1
Solar/Wind Harmer
2.351
270489AE1-102 GEN1
Solar/Wind Harmer
0.781
965011AG1-365 GEN
Solar/Wind Harmer
5.3
958861AF2-177 GEN
Solar/Wind Harmer
5.03
945111AF1-176 GEN
Solar/Wind Harmer
8.149
957891AF2-083 GEN
Solar/Wind Harmer
6.834
945371AF1-202 GEN
Solar/Wind Harmer
3.165
24441205WTRV SLR C
Solar/Wind Harmer
0.06
270005AE1-210 C O1
Solar/Wind Harmer
2.395
970825AG2-519 GEN
Solar/Wind Harmer
0.919
274751CRETE EC ;1U
Adder
2.136
274773LINCOLN ;4U
Adder
2.707
274774LINCOLN ;5U
Adder
2.707
274723RIVER EC ;12
Adder
7.823
270594AE1-207 GEN
Solar/Wind Harmer
5.904
270032AE2-172
Solar/Wind Harmer
2.022
270036AE2-216 BAT
50/50
5.971
270224U2-072_GEN2
Solar/Wind Harmer
1.974
965051AG1-369 GEN
Solar/Wind Harmer
2.764
270404AC1-167 GEN
Solar/Wind Harmer
0.571
970031AG2-029 GEN
Solar/Wind Harmer
12.056
945581AF1-223 GEN
Solar/Wind Harmer
2.057
961761AG1-017 GEN
Solar/Wind Harmer
0.193
247536S-71 GEN
Solar/Wind Harmer
1.815
971029AG2-637 GEN
Solar/Wind Harmer
6.646
274775LINCOLN ;6U
Adder
2.707
274777LINCOLN ;8U
Adder
2.707
972037AH1-567 GEN1
Adder
0.079
960591AF2-350 GEN
Solar/Wind Harmer
4.325
972228AH1-698 GEN2
Adder
1.601
971995AH1-542 GEN
Solar/Wind Harmer
11.797
970155AG2-107 GEN
Solar/Wind Harmer
9.111
965421AG1-410 GEN
Solar/Wind Harmer
17.827
270024AE2-089 GEN
Solar/Wind Harmer
2.197
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
965651AG1-433 GEN
Solar/Wind Harmer
2.534
24639705ELKHART HY
Adder
0.071
270449AD2-020 GEN
Solar/Wind Harmer
1.271
972207SS24-0001
Solar/Wind Harmer
9.624
270055AF2-134 C O1
Solar/Wind Harmer
1.317
274812UNIV PK N;8U
Adder
2.178
274676JOLIET 29;8U
Adder
13.196
270349AD2-093_GEN
Solar/Wind Harmer
4.875
270471AD2-092_GEN
Solar/Wind Harmer
4.875
270246TR4_N_V150
Solar/Wind Harmer
0.471
25322209TAIT E
Adder
4.684
25322209TAIT E
Adder
4.578
253370AE2-315 SEC1
Adder
0.929
247621Y3-024
Adder
0.109
253383AE2-342_GEN
Solar/Wind Harmer
0.398
965681AG1-436 GEN
Solar/Wind Harmer
5.605
270535AF1-215 GEN1
Solar/Wind Harmer
1.976
270536AF1-215 GEN2
Solar/Wind Harmer
1.976
970291AG2-192 GEN
Solar/Wind Harmer
0.564
946101AF1-275 GEN
Solar/Wind Harmer
1.347
241960AC2-195 GEN
Solar/Wind Harmer
2.356
942861AE2-305 GEN
Solar/Wind Harmer
3.928
25326109MON D
Adder
0.654
253400AC2-068 GEN
Solar/Wind Harmer
0.386
247620Y3-023
Adder
0.214
944541AF1-119 GEN
Solar/Wind Harmer
1.941
270201AC2-176 GEN
Solar/Wind Harmer
2.319
964611AG1-324 GEN
Solar/Wind Harmer
0.235
965791AG1-447 GEN
Solar/Wind Harmer
2.868
270031AE2-169
Solar/Wind Harmer
3.645
970885AG2-551 GEN
Solar/Wind Harmer
1.037
270383AD1-128 GEN
Solar/Wind Harmer
2.644
958011AF2-095 GEN
Solar/Wind Harmer
6.228
270475AD2-096_GEN
50/50
7.81
270491AE1-102 GEN2
Solar/Wind Harmer
0.781
270518AE2-148 GEN
Solar/Wind Harmer
6.261
253325AC1-069 GEN
Solar/Wind Harmer
0.505
24441505OLIV SLR
Solar/Wind Harmer
0.06
270004AE1-209 GEN
Solar/Wind Harmer
2.395
274753CRETE EC ;3U
Adder
2.136
274814UNIV PK N;0U
Adder
2.197
274807UNIV PK N;3U
Adder
2.192
274803UNIV PARK;6U
Adder
2.524
276843GEN-1.7
Solar/Wind Harmer
0.248
972038AH1-567 GEN2
Adder
0.158
964401AG1-302 GEN
Solar/Wind Harmer
3.921
970291AG2-192 GEN
Solar/Wind Harmer
0.182
276776AD2-060 GEN
Solar/Wind Harmer
0.181
270223U2-072_GEN1
Solar/Wind Harmer
1.974
270578AF1-285 GEN2
Solar/Wind Harmer
0.465
241972AD1-140 GEN
Solar/Wind Harmer
2.573
270191TR4_S_V150
Solar/Wind Harmer
1.66
965041AG1-368 GEN
Solar/Wind Harmer
5.371
945631AF1-228 GEN
Solar/Wind Harmer
2.514
959331AF2-224 GEN
Solar/Wind Harmer
5.3
253338AC1-165 GEN
Solar/Wind Harmer
0.524
270526AF1-158 GEN
Solar/Wind Harmer
2.05
964611AG1-324 GEN
Solar/Wind Harmer
1.75
960681AF2-359 GEN
Solar/Wind Harmer
1.694
274776LINCOLN ;7U
Adder
2.707
274687WILL CNTY;4U
Adder
12.029
274687WILL CNTY;4U
Adder
12.029
274675JOLIET 29;7U
Adder
13.196
274675JOLIET 29;7U
Adder
12.725
270391AF1-285 GEN3
Solar/Wind Harmer
1.209
270317AD1-130_GEN
Solar/Wind Harmer
2.988
270520AE2-214 GEN
Solar/Wind Harmer
5.389
241813AF1-122_GEN
Solar/Wind Harmer
4.164
971201AH1-060 GEN
Solar/Wind Harmer
1.301
962761AG1-125 GEN
Solar/Wind Harmer
20.895
253333AC1-068 GEN
Solar/Wind Harmer
0.505
25326309TAIT D
Adder
0.527
270216AD2-079_GEN
Solar/Wind Harmer
0.279
274754CRETE EC ;4U
Adder
2.136
274802UNIV PARK;5U
Adder
2.524
958381AF2-132 GEN
Solar/Wind Harmer
3.921
253378AE2-206_GEN
Solar/Wind Harmer
2.404
25326509SID D
Adder
0.839
246937BC-WTG2
Solar/Wind Harmer
2.351
247607V1-011 GEN
Solar/Wind Harmer
2.234
942221AE2-234 GEN
Solar/Wind Harmer
1.652
274770LINCOLN ;1U
Adder
2.707
274771LINCOLN ;2U
Adder
2.707
274805UNIV PK N;1U
Adder
2.183
274888KELLY CRK;1U
Solar/Wind Harmer
2.552
970941AG2-585 GEN
Solar/Wind Harmer
2.379
274676JOLIET 29;8U
Adder
12.724
270286AF1-227 GEN2
Solar/Wind Harmer
2.53
270578AF1-285 GEN2
Solar/Wind Harmer
1.209
970149AG2-104 GEN
Solar/Wind Harmer
12.903
270297AD1-101 GEN
Solar/Wind Harmer
1.129
270258AD1-119 GEN
Solar/Wind Harmer
1.095
943021AE2-325 GEN
Solar/Wind Harmer
1.652
970373AG2-245 GEN
Solar/Wind Harmer
9.221
965461AG1-414 GEN
Solar/Wind Harmer
0.984
972259AH1-714 GEN
Adder
8.237
270435AC2-044 GEN
Solar/Wind Harmer
1.202
270007AE1-245 C
Solar/Wind Harmer
3.051
270071AF1-092 GEN
Solar/Wind Harmer
7.206
24729505KEY G4
Adder
3.077
958711AF2-162 GEN
Solar/Wind Harmer
0.469
971771AH1-392 GEN
Solar/Wind Harmer
4.103
270543AE2-219 C
Solar/Wind Harmer
4.458
971549AH1-272 GEN
Solar/Wind Harmer
8.101
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.726
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.311
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.538
MECLTFEXP_MEC->PJM
CLTF
6.315
SIGELTFEXP_SIGE->PJM
CLTF
0.181
NYPJM->LTFIMP_NY
CLTF
1.312
LGEELTFEXP_LGEE->PJM
CLTF
2.29
WECLTFEXP_WEC->PJM
CLTF
1.588
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
LAGNLTFEXP_LAGN->PJM
CLTF
5.1
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.32
TVALTFEXP_TVA->PJM
CLTF
2.365

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.97 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1563.59
MW Contribution:
11.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270227U2-072_GEN3
Solar/Wind Harmer
1.969
270228U2-072_GEN4
Solar/Wind Harmer
1.969
270231U2-072_GEN5
Solar/Wind Harmer
1.969
241973AD2-163_GEN1
Solar/Wind Harmer
1.945
241974AD2-163_GEN2
Solar/Wind Harmer
1.945
270302AB2-170 GEN
Solar/Wind Harmer
7.798
970179AG2-119 GEN
Solar/Wind Harmer
6.776
241955AC1-078 GEN
Solar/Wind Harmer
4.984
957201AF2-014 GEN
Solar/Wind Harmer
2.72
247521TR3_G114
Solar/Wind Harmer
1.857
943861AF1-054 GEN
Solar/Wind Harmer
1.926
943851AF1-053 GEN
Solar/Wind Harmer
0.931
963791AG1-232 GEN
Solar/Wind Harmer
6.697
253343AC1-166 GEN
Solar/Wind Harmer
0.523
25306009OHH W.
Adder
1.338
253372AE2-315 SEC3
Adder
0.877
253372AE2-315 SEC3
Adder
0.877
944161AF1-084 GEN
Solar/Wind Harmer
0.997
970289AG2-191 GEN
Solar/Wind Harmer
0.823
274827FISK ;RP
Adder
3.351
270287AF1-227 GEN3
Solar/Wind Harmer
2.524
942871AE2-306 GEN
Solar/Wind Harmer
0.905
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
942051AE2-217 GEN
Solar/Wind Harmer
13.942
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270063AE2-323 C
Solar/Wind Harmer
1.049
944531AF1-118 GEN
Solar/Wind Harmer
16.696
270541AE2-072 C
Solar/Wind Harmer
2.153
971347AH1-153 GEN
Solar/Wind Harmer
2.3
972231SS25-0005
Solar/Wind Harmer
4.138
274752CRETE EC ;2U
Adder
2.131
274826FISK ;BP
Adder
4.728
274887GEN-1.85
Solar/Wind Harmer
2.299
276772AC2-154 GEN
Solar/Wind Harmer
1.204
970707AG2-453 GEN
Solar/Wind Harmer
11.064
270466AD2-091
50/50
5.415
938701AE1-092 GEN
Solar/Wind Harmer
21.934
270462AD2-086
Solar/Wind Harmer
6.477
942801AE2-298 GEN
Solar/Wind Harmer
0.858
270247TR4_N_V136
Solar/Wind Harmer
0.47
944231AF1-091 GEN
Solar/Wind Harmer
8.776
253349AC2-067 GEN
Solar/Wind Harmer
0.958
960971AF2-388 GEN
Solar/Wind Harmer
5.057
970349AG2-230 GEN
Solar/Wind Harmer
6.9
961051AF2-396 GEN
Solar/Wind Harmer
7.203
961051AF2-396 GEN
Solar/Wind Harmer
3.35
270599AE1-208 GEN
Solar/Wind Harmer
3.637
970883AG2-550 GEN
Solar/Wind Harmer
4.448
274808UNIV PK N;4U
Adder
2.164
270054AF2-122 C O1
Solar/Wind Helper
0.821
270485AE1-090_GEN
Solar/Wind Harmer
0.563
246936BC-WTG1
Solar/Wind Harmer
2.346
270489AE1-102 GEN1
Solar/Wind Harmer
0.78
965011AG1-365 GEN
Solar/Wind Harmer
5.288
971995AH1-542 GEN
Solar/Wind Harmer
11.77
970155AG2-107 GEN
Solar/Wind Harmer
9.09
965421AG1-410 GEN
Solar/Wind Harmer
17.787
270024AE2-089 GEN
Solar/Wind Harmer
2.192
965651AG1-433 GEN
Solar/Wind Harmer
2.529
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
24639705ELKHART HY
Adder
0.071
270449AD2-020 GEN
Solar/Wind Harmer
1.268
972207SS24-0001
Solar/Wind Harmer
9.604
270055AF2-134 C O1
Solar/Wind Harmer
1.315
274812UNIV PK N;8U
Adder
2.173
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.35
942861AE2-305 GEN
Solar/Wind Harmer
3.903
25326109MON D
Adder
0.652
253400AC2-068 GEN
Solar/Wind Harmer
0.385
247620Y3-023
Adder
0.214
944541AF1-119 GEN
Solar/Wind Harmer
1.937
270201AC2-176 GEN
Solar/Wind Harmer
2.314
964611AG1-324 GEN
Solar/Wind Harmer
0.234
965791AG1-447 GEN
Solar/Wind Harmer
2.861
270031AE2-169
Solar/Wind Harmer
3.637
970885AG2-551 GEN
Solar/Wind Harmer
1.034
270383AD1-128 GEN
Solar/Wind Harmer
2.638
958011AF2-095 GEN
Solar/Wind Harmer
6.215
270475AD2-096_GEN
50/50
7.792
270491AE1-102 GEN2
Solar/Wind Harmer
0.78
270518AE2-148 GEN
Solar/Wind Harmer
6.249
253325AC1-069 GEN
Solar/Wind Harmer
0.504
24441505OLIV SLR
Solar/Wind Harmer
0.06
270004AE1-209 GEN
Solar/Wind Harmer
2.39
274753CRETE EC ;3U
Adder
2.131
274814UNIV PK N;0U
Adder
2.192
274807UNIV PK N;3U
Adder
2.187
274803UNIV PARK;6U
Adder
2.519
276843GEN-1.7
Solar/Wind Harmer
0.247
972038AH1-567 GEN2
Adder
0.157
964401AG1-302 GEN
Solar/Wind Harmer
3.912
270349AD2-093_GEN
Solar/Wind Harmer
4.863
270471AD2-092_GEN
Solar/Wind Harmer
4.863
270246TR4_N_V150
Solar/Wind Harmer
0.47
25322209TAIT E
Adder
4.673
25322209TAIT E
Adder
4.568
253370AE2-315 SEC1
Adder
0.927
247621Y3-024
Adder
0.109
965681AG1-436 GEN
Solar/Wind Harmer
5.593
253383AE2-342_GEN
Solar/Wind Harmer
0.395
270535AF1-215 GEN1
Solar/Wind Harmer
1.972
270536AF1-215 GEN2
Solar/Wind Harmer
1.972
970291AG2-192 GEN
Solar/Wind Harmer
0.563
970291AG2-192 GEN
Solar/Wind Harmer
0.181
276776AD2-060 GEN
Solar/Wind Harmer
0.181
274800UNIV PARK;3U
Adder
2.516
274801UNIV PARK;4U
Adder
2.516
972227AH1-698 GEN1
Adder
1.125
270223U2-072_GEN1
Solar/Wind Harmer
1.969
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241972AD1-140 GEN
Solar/Wind Harmer
2.566
270191TR4_S_V150
Solar/Wind Harmer
1.657
965041AG1-368 GEN
Solar/Wind Harmer
5.359
945631AF1-228 GEN
Solar/Wind Harmer
2.509
959331AF2-224 GEN
Solar/Wind Harmer
5.288
253338AC1-165 GEN
Solar/Wind Harmer
0.523
270526AF1-158 GEN
Solar/Wind Harmer
2.045
964611AG1-324 GEN
Solar/Wind Harmer
1.747
960681AF2-359 GEN
Solar/Wind Harmer
1.691
274776LINCOLN ;7U
Adder
2.701
270036AE2-216 BAT
50/50
5.957
270224U2-072_GEN2
Solar/Wind Harmer
1.969
965051AG1-369 GEN
Solar/Wind Harmer
2.758
270404AC1-167 GEN
Solar/Wind Harmer
0.569
970031AG2-029 GEN
Solar/Wind Harmer
12.029
945581AF1-223 GEN
Solar/Wind Harmer
2.053
961761AG1-017 GEN
Solar/Wind Harmer
0.193
247536S-71 GEN
Solar/Wind Harmer
1.811
971029AG2-637 GEN
Solar/Wind Harmer
6.632
274775LINCOLN ;6U
Adder
2.701
274777LINCOLN ;8U
Adder
2.701
972037AH1-567 GEN1
Adder
0.079
960591AF2-350 GEN
Solar/Wind Harmer
4.316
972228AH1-698 GEN2
Adder
1.597
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270317AD1-130_GEN
Solar/Wind Harmer
2.981
270520AE2-214 GEN
Solar/Wind Harmer
5.374
241813AF1-122_GEN
Solar/Wind Harmer
4.155
971201AH1-060 GEN
Solar/Wind Harmer
1.298
962761AG1-125 GEN
Solar/Wind Harmer
20.847
253333AC1-068 GEN
Solar/Wind Harmer
0.504
25326309TAIT D
Adder
0.526
270216AD2-079_GEN
Solar/Wind Harmer
0.278
274754CRETE EC ;4U
Adder
2.131
274802UNIV PARK;5U
Adder
2.519
958381AF2-132 GEN
Solar/Wind Harmer
3.912
958861AF2-177 GEN
Solar/Wind Harmer
5.02
945111AF1-176 GEN
Solar/Wind Harmer
8.131
957891AF2-083 GEN
Solar/Wind Harmer
6.82
945371AF1-202 GEN
Solar/Wind Harmer
3.158
24441205WTRV SLR C
Solar/Wind Harmer
0.06
270005AE1-210 C O1
Solar/Wind Harmer
2.39
970825AG2-519 GEN
Solar/Wind Harmer
0.917
274751CRETE EC ;1U
Adder
2.131
274773LINCOLN ;4U
Adder
2.701
274774LINCOLN ;5U
Adder
2.701
274723RIVER EC ;12
Adder
7.806
270594AE1-207 GEN
Solar/Wind Harmer
5.891
270032AE2-172
Solar/Wind Harmer
2.018
253378AE2-206_GEN
Solar/Wind Harmer
2.398
25326509SID D
Adder
0.837
246937BC-WTG2
Solar/Wind Harmer
2.346
247607V1-011 GEN
Solar/Wind Harmer
2.229
942221AE2-234 GEN
Solar/Wind Harmer
1.648
274770LINCOLN ;1U
Adder
2.701
274771LINCOLN ;2U
Adder
2.701
274805UNIV PK N;1U
Adder
2.178
274888KELLY CRK;1U
Solar/Wind Harmer
2.547
970941AG2-585 GEN
Solar/Wind Harmer
2.374
270284AF1-227 GEN1
Solar/Wind Harmer
6.824
276820AF1-078_GEN
Solar/Wind Harmer
1.065
962771AG1-126 GEN
Solar/Wind Harmer
20.847
970153AG2-106 GEN
Solar/Wind Harmer
9.09
24695305TIMB G C
Solar/Wind Harmer
1.827
270588AE1-091_GEN
Solar/Wind Harmer
5.494
960071AF2-298 GEN
Solar/Wind Harmer
0.728
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
247643Z2-116 C
Solar/Wind Harmer
0.032
946031AF1-268 GEN
Solar/Wind Harmer
3.647
972181SS23-001
Solar/Wind Harmer
2.586
276164X3-005 C
Solar/Wind Harmer
0.305
274811UNIV PK N;7U
Adder
2.173
970289AG2-191 GEN
Solar/Wind Harmer
0.332
247642Z2-115 C
Solar/Wind Harmer
0.028
276806AD2-047 C O1
Solar/Wind Harmer
4.617
270286AF1-227 GEN2
Solar/Wind Harmer
2.524
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
970149AG2-104 GEN
Solar/Wind Harmer
12.873
270297AD1-101 GEN
Solar/Wind Harmer
1.127
270258AD1-119 GEN
Solar/Wind Harmer
1.093
943021AE2-325 GEN
Solar/Wind Harmer
1.648
970373AG2-245 GEN
Solar/Wind Harmer
9.201
970065AG2-057 GEN
Solar/Wind Harmer
0.649
246938BC-WTG3
Solar/Wind Harmer
2.386
965021AG1-366 GEN
Solar/Wind Harmer
1.23
270044AE2-322 C
Solar/Wind Harmer
0.691
270043AE2-236 GEN
Solar/Wind Harmer
2.698
945111AF1-176 GEN
Solar/Wind Harmer
2.577
270505AE1-170 C O1
Solar/Wind Harmer
6.816
962031AG1-047 GEN
Solar/Wind Harmer
1.361
957741AF2-068 GEN
Solar/Wind Harmer
6.753
970825AG2-519 GEN
Solar/Wind Harmer
2.462
274772LINCOLN ;3U
Adder
2.701
274724RIVER EC ;11
Adder
7.714
965461AG1-414 GEN
Solar/Wind Harmer
0.982
972259AH1-714 GEN
Adder
8.22
270435AC2-044 GEN
Solar/Wind Harmer
1.199
270007AE1-245 C
Solar/Wind Harmer
3.044
270071AF1-092 GEN
Solar/Wind Harmer
7.19
24729505KEY G4
Adder
3.07
958711AF2-162 GEN
Solar/Wind Harmer
0.468
971771AH1-392 GEN
Solar/Wind Harmer
4.095
270543AE2-219 C
Solar/Wind Harmer
4.448
971549AH1-272 GEN
Solar/Wind Harmer
8.084
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.643
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.519
MECLTFEXP_MEC->PJM
CLTF
6.302
SIGELTFEXP_SIGE->PJM
CLTF
0.181
NYPJM->LTFIMP_NY
CLTF
1.31
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.584
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
LAGNLTFEXP_LAGN->PJM
CLTF
5.09
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.316
TVALTFEXP_TVA->PJM
CLTF
2.361

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.88 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1562.23
MW Contribution:
11.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270287AF1-227 GEN3
Solar/Wind Harmer
2.523
942871AE2-306 GEN
Solar/Wind Harmer
0.904
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
942051AE2-217 GEN
Solar/Wind Harmer
13.933
270466AD2-091
50/50
5.413
938701AE1-092 GEN
Solar/Wind Harmer
21.921
270462AD2-086
Solar/Wind Harmer
6.473
942801AE2-298 GEN
Solar/Wind Harmer
0.858
270247TR4_N_V136
Solar/Wind Harmer
0.469
944231AF1-091 GEN
Solar/Wind Harmer
8.771
253349AC2-067 GEN
Solar/Wind Harmer
0.957
960971AF2-388 GEN
Solar/Wind Harmer
5.055
970349AG2-230 GEN
Solar/Wind Harmer
6.897
961051AF2-396 GEN
Solar/Wind Harmer
7.199
961051AF2-396 GEN
Solar/Wind Harmer
3.348
270599AE1-208 GEN
Solar/Wind Harmer
3.636
970883AG2-550 GEN
Solar/Wind Harmer
4.446
274808UNIV PK N;4U
Adder
2.163
270054AF2-122 C O1
Solar/Wind Helper
0.82
971995AH1-542 GEN
Solar/Wind Harmer
11.763
970155AG2-107 GEN
Solar/Wind Harmer
9.086
965421AG1-410 GEN
Solar/Wind Harmer
17.778
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.349
942861AE2-305 GEN
Solar/Wind Harmer
3.897
25326109MON D
Adder
0.652
253400AC2-068 GEN
Solar/Wind Harmer
0.385
247620Y3-023
Adder
0.214
944541AF1-119 GEN
Solar/Wind Harmer
1.936
270201AC2-176 GEN
Solar/Wind Harmer
2.313
964611AG1-324 GEN
Solar/Wind Harmer
0.234
965791AG1-447 GEN
Solar/Wind Harmer
2.86
270031AE2-169
Solar/Wind Harmer
3.636
970885AG2-551 GEN
Solar/Wind Harmer
1.034
270383AD1-128 GEN
Solar/Wind Harmer
2.637
958011AF2-095 GEN
Solar/Wind Harmer
6.212
270475AD2-096_GEN
50/50
7.787
270491AE1-102 GEN2
Solar/Wind Harmer
0.779
270518AE2-148 GEN
Solar/Wind Harmer
6.247
253325AC1-069 GEN
Solar/Wind Harmer
0.504
24441505OLIV SLR
Solar/Wind Harmer
0.06
270004AE1-209 GEN
Solar/Wind Harmer
2.388
274753CRETE EC ;3U
Adder
2.13
274814UNIV PK N;0U
Adder
2.191
274807UNIV PK N;3U
Adder
2.186
274803UNIV PARK;6U
Adder
2.518
972038AH1-567 GEN2
Adder
0.157
276843GEN-1.7
Solar/Wind Harmer
0.247
964401AG1-302 GEN
Solar/Wind Harmer
3.91
270349AD2-093_GEN
Solar/Wind Harmer
4.86
270471AD2-092_GEN
Solar/Wind Harmer
4.86
270246TR4_N_V150
Solar/Wind Harmer
0.469
25322209TAIT E
Adder
4.67
25322209TAIT E
Adder
4.565
253370AE2-315 SEC1
Adder
0.926
247621Y3-024
Adder
0.109
965681AG1-436 GEN
Solar/Wind Harmer
5.59
253383AE2-342_GEN
Solar/Wind Harmer
0.394
270535AF1-215 GEN1
Solar/Wind Harmer
1.971
270536AF1-215 GEN2
Solar/Wind Harmer
1.971
970291AG2-192 GEN
Solar/Wind Harmer
0.562
970291AG2-192 GEN
Solar/Wind Harmer
0.181
276776AD2-060 GEN
Solar/Wind Harmer
0.181
270227U2-072_GEN3
Solar/Wind Harmer
1.968
270228U2-072_GEN4
Solar/Wind Harmer
1.968
270231U2-072_GEN5
Solar/Wind Harmer
1.968
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
270302AB2-170 GEN
Solar/Wind Harmer
7.794
970179AG2-119 GEN
Solar/Wind Harmer
6.772
241955AC1-078 GEN
Solar/Wind Harmer
4.982
957201AF2-014 GEN
Solar/Wind Harmer
2.718
247521TR3_G114
Solar/Wind Harmer
1.856
943861AF1-054 GEN
Solar/Wind Harmer
1.923
943851AF1-053 GEN
Solar/Wind Harmer
0.929
963791AG1-232 GEN
Solar/Wind Harmer
6.694
253343AC1-166 GEN
Solar/Wind Harmer
0.523
25306009OHH W.
Adder
1.337
253372AE2-315 SEC3
Adder
0.876
253372AE2-315 SEC3
Adder
0.876
944161AF1-084 GEN
Solar/Wind Harmer
0.996
970289AG2-191 GEN
Solar/Wind Harmer
0.822
274827FISK ;RP
Adder
3.349
274800UNIV PARK;3U
Adder
2.515
274801UNIV PARK;4U
Adder
2.515
972227AH1-698 GEN1
Adder
1.124
270223U2-072_GEN1
Solar/Wind Harmer
1.968
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241972AD1-140 GEN
Solar/Wind Harmer
2.564
270191TR4_S_V150
Solar/Wind Harmer
1.656
965041AG1-368 GEN
Solar/Wind Harmer
5.357
945631AF1-228 GEN
Solar/Wind Harmer
2.508
959331AF2-224 GEN
Solar/Wind Harmer
5.285
253338AC1-165 GEN
Solar/Wind Harmer
0.523
270526AF1-158 GEN
Solar/Wind Harmer
2.044
964611AG1-324 GEN
Solar/Wind Harmer
1.746
960681AF2-359 GEN
Solar/Wind Harmer
1.69
274776LINCOLN ;7U
Adder
2.7
270036AE2-216 BAT
50/50
5.954
270224U2-072_GEN2
Solar/Wind Harmer
1.968
965051AG1-369 GEN
Solar/Wind Harmer
2.757
270404AC1-167 GEN
Solar/Wind Harmer
0.569
970031AG2-029 GEN
Solar/Wind Harmer
12.023
945581AF1-223 GEN
Solar/Wind Harmer
2.052
961761AG1-017 GEN
Solar/Wind Harmer
0.193
247536S-71 GEN
Solar/Wind Harmer
1.81
971029AG2-637 GEN
Solar/Wind Harmer
6.628
274775LINCOLN ;6U
Adder
2.7
274777LINCOLN ;8U
Adder
2.7
972037AH1-567 GEN1
Adder
0.079
960591AF2-350 GEN
Solar/Wind Harmer
4.314
972228AH1-698 GEN2
Adder
1.596
270391AF1-285 GEN3
Solar/Wind Harmer
1.205
270317AD1-130_GEN
Solar/Wind Harmer
2.98
270520AE2-214 GEN
Solar/Wind Harmer
5.371
241813AF1-122_GEN
Solar/Wind Harmer
4.152
971201AH1-060 GEN
Solar/Wind Harmer
1.298
962761AG1-125 GEN
Solar/Wind Harmer
20.836
253333AC1-068 GEN
Solar/Wind Harmer
0.504
25326309TAIT D
Adder
0.525
270216AD2-079_GEN
Solar/Wind Harmer
0.278
274754CRETE EC ;4U
Adder
2.13
274802UNIV PARK;5U
Adder
2.518
958381AF2-132 GEN
Solar/Wind Harmer
3.91
270485AE1-090_GEN
Solar/Wind Harmer
0.563
246936BC-WTG1
Solar/Wind Harmer
2.344
270489AE1-102 GEN1
Solar/Wind Harmer
0.779
965011AG1-365 GEN
Solar/Wind Harmer
5.285
958861AF2-177 GEN
Solar/Wind Harmer
5.017
945111AF1-176 GEN
Solar/Wind Harmer
8.127
957891AF2-083 GEN
Solar/Wind Harmer
6.816
945371AF1-202 GEN
Solar/Wind Harmer
3.157
24441205WTRV SLR C
Solar/Wind Harmer
0.06
270005AE1-210 C O1
Solar/Wind Harmer
2.388
970825AG2-519 GEN
Solar/Wind Harmer
0.916
274751CRETE EC ;1U
Adder
2.13
274773LINCOLN ;4U
Adder
2.7
274774LINCOLN ;5U
Adder
2.7
274723RIVER EC ;12
Adder
7.802
270594AE1-207 GEN
Solar/Wind Harmer
5.888
270032AE2-172
Solar/Wind Harmer
2.017
253378AE2-206_GEN
Solar/Wind Harmer
2.397
25326509SID D
Adder
0.837
246937BC-WTG2
Solar/Wind Harmer
2.344
247607V1-011 GEN
Solar/Wind Harmer
2.227
942221AE2-234 GEN
Solar/Wind Harmer
1.648
274770LINCOLN ;1U
Adder
2.7
274771LINCOLN ;2U
Adder
2.7
274805UNIV PK N;1U
Adder
2.177
274888KELLY CRK;1U
Solar/Wind Harmer
2.545
970941AG2-585 GEN
Solar/Wind Harmer
2.372
270284AF1-227 GEN1
Solar/Wind Harmer
6.82
276820AF1-078_GEN
Solar/Wind Harmer
1.065
962771AG1-126 GEN
Solar/Wind Harmer
20.836
970153AG2-106 GEN
Solar/Wind Harmer
9.086
24695305TIMB G C
Solar/Wind Harmer
1.826
270588AE1-091_GEN
Solar/Wind Harmer
5.492
960071AF2-298 GEN
Solar/Wind Harmer
0.728
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
247643Z2-116 C
Solar/Wind Harmer
0.032
946031AF1-268 GEN
Solar/Wind Harmer
3.645
972181SS23-001
Solar/Wind Harmer
2.585
276164X3-005 C
Solar/Wind Harmer
0.305
274811UNIV PK N;7U
Adder
2.172
970289AG2-191 GEN
Solar/Wind Harmer
0.332
247642Z2-115 C
Solar/Wind Harmer
0.028
276806AD2-047 C O1
Solar/Wind Harmer
4.615
270024AE2-089 GEN
Solar/Wind Harmer
2.191
965651AG1-433 GEN
Solar/Wind Harmer
2.527
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
24639705ELKHART HY
Adder
0.071
270449AD2-020 GEN
Solar/Wind Harmer
1.268
972207SS24-0001
Solar/Wind Harmer
9.599
270055AF2-134 C O1
Solar/Wind Harmer
1.314
274812UNIV PK N;8U
Adder
2.172
270286AF1-227 GEN2
Solar/Wind Harmer
2.523
270578AF1-285 GEN2
Solar/Wind Harmer
1.205
970149AG2-104 GEN
Solar/Wind Harmer
12.866
270297AD1-101 GEN
Solar/Wind Harmer
1.126
270258AD1-119 GEN
Solar/Wind Harmer
1.092
943021AE2-325 GEN
Solar/Wind Harmer
1.648
970373AG2-245 GEN
Solar/Wind Harmer
9.197
970065AG2-057 GEN
Solar/Wind Harmer
0.649
246938BC-WTG3
Solar/Wind Harmer
2.385
965021AG1-366 GEN
Solar/Wind Harmer
1.229
270044AE2-322 C
Solar/Wind Harmer
0.691
270043AE2-236 GEN
Solar/Wind Harmer
2.697
945111AF1-176 GEN
Solar/Wind Harmer
2.576
270505AE1-170 C O1
Solar/Wind Harmer
6.813
962031AG1-047 GEN
Solar/Wind Harmer
1.36
957741AF2-068 GEN
Solar/Wind Harmer
6.749
970825AG2-519 GEN
Solar/Wind Harmer
2.461
274772LINCOLN ;3U
Adder
2.7
274724RIVER EC ;11
Adder
7.711
965461AG1-414 GEN
Solar/Wind Harmer
0.981
972259AH1-714 GEN
Adder
8.216
270435AC2-044 GEN
Solar/Wind Harmer
1.199
270007AE1-245 C
Solar/Wind Harmer
3.043
270071AF1-092 GEN
Solar/Wind Harmer
7.187
24729505KEY G4
Adder
3.068
958711AF2-162 GEN
Solar/Wind Harmer
0.468
971771AH1-392 GEN
Solar/Wind Harmer
4.093
270543AE2-219 C
Solar/Wind Harmer
4.446
971549AH1-272 GEN
Solar/Wind Harmer
8.08
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270063AE2-323 C
Solar/Wind Harmer
1.049
944531AF1-118 GEN
Solar/Wind Harmer
16.688
270541AE2-072 C
Solar/Wind Harmer
2.152
971347AH1-153 GEN
Solar/Wind Harmer
2.299
972231SS25-0005
Solar/Wind Harmer
4.136
274752CRETE EC ;2U
Adder
2.13
274826FISK ;BP
Adder
4.726
274887GEN-1.85
Solar/Wind Harmer
2.298
276772AC2-154 GEN
Solar/Wind Harmer
1.204
970707AG2-453 GEN
Solar/Wind Harmer
11.058
CPLELTFEXP_CPLE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.624
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.165
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.515
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181
NYPJM->LTFIMP_NY
CLTF
1.309
LGEELTFEXP_LGEE->PJM
CLTF
2.284
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
LAGNLTFEXP_LAGN->PJM
CLTF
5.087
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.315
TVALTFEXP_TVA->PJM
CLTF
2.36

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1484.58
MW Contribution:
11.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
5.389
938701AE1-092 GEN
Solar/Wind Harmer
21.815
270462AD2-086
Solar/Wind Harmer
6.445
942801AE2-298 GEN
Solar/Wind Harmer
0.854
270247TR4_N_V136
Solar/Wind Harmer
0.468
944231AF1-091 GEN
Solar/Wind Harmer
8.735
253349AC2-067 GEN
Solar/Wind Harmer
0.953
960971AF2-388 GEN
Solar/Wind Harmer
5.034
970349AG2-230 GEN
Solar/Wind Harmer
6.869
961051AF2-396 GEN
Solar/Wind Harmer
7.17
961051AF2-396 GEN
Solar/Wind Harmer
3.335
270599AE1-208 GEN
Solar/Wind Harmer
3.621
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.649
253400AC2-068 GEN
Solar/Wind Harmer
0.383
247620Y3-023
Adder
0.213
944541AF1-119 GEN
Solar/Wind Harmer
1.928
270201AC2-176 GEN
Solar/Wind Harmer
2.303
964611AG1-324 GEN
Solar/Wind Harmer
0.233
965791AG1-447 GEN
Solar/Wind Harmer
2.848
270031AE2-169
Solar/Wind Harmer
3.621
970885AG2-551 GEN
Solar/Wind Harmer
1.03
270383AD1-128 GEN
Solar/Wind Harmer
2.627
270475AD2-096_GEN
50/50
7.753
270491AE1-102 GEN2
Solar/Wind Harmer
0.776
270518AE2-148 GEN
Solar/Wind Harmer
6.224
253325AC1-069 GEN
Solar/Wind Harmer
0.503
24441505OLIV SLR
Solar/Wind Harmer
0.06
270004AE1-209 GEN
Solar/Wind Harmer
2.379
274753CRETE EC ;3U
Adder
2.121
274814UNIV PK N;0U
Adder
2.182
274807UNIV PK N;3U
Adder
2.178
274803UNIV PARK;6U
Adder
2.508
270349AD2-093_GEN
Solar/Wind Harmer
4.839
270471AD2-092_GEN
Solar/Wind Harmer
4.839
270246TR4_N_V150
Solar/Wind Harmer
0.468
25322209TAIT E
Adder
4.65
25322209TAIT E
Adder
4.546
253370AE2-315 SEC1
Adder
0.922
247621Y3-024
Adder
0.108
965681AG1-436 GEN
Solar/Wind Harmer
5.567
253383AE2-342_GEN
Solar/Wind Harmer
0.387
270535AF1-215 GEN1
Solar/Wind Harmer
1.963
270536AF1-215 GEN2
Solar/Wind Harmer
1.963
970291AG2-192 GEN
Solar/Wind Harmer
0.56
970291AG2-192 GEN
Solar/Wind Harmer
0.18
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
241973AD2-163_GEN1
Solar/Wind Harmer
1.933
241974AD2-163_GEN2
Solar/Wind Harmer
1.933
270302AB2-170 GEN
Solar/Wind Harmer
7.76
970179AG2-119 GEN
Solar/Wind Harmer
6.743
241955AC1-078 GEN
Solar/Wind Harmer
4.963
957201AF2-014 GEN
Solar/Wind Harmer
2.707
247521TR3_G114
Solar/Wind Harmer
1.848
963791AG1-232 GEN
Solar/Wind Harmer
6.667
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
253343AC1-166 GEN
Solar/Wind Harmer
0.521
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
944161AF1-084 GEN
Solar/Wind Harmer
0.992
970289AG2-191 GEN
Solar/Wind Harmer
0.819
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241972AD1-140 GEN
Solar/Wind Harmer
2.551
270191TR4_S_V150
Solar/Wind Harmer
1.649
965041AG1-368 GEN
Solar/Wind Harmer
5.334
945631AF1-228 GEN
Solar/Wind Harmer
2.5
959331AF2-224 GEN
Solar/Wind Harmer
5.263
253338AC1-165 GEN
Solar/Wind Harmer
0.521
270526AF1-158 GEN
Solar/Wind Harmer
2.036
964611AG1-324 GEN
Solar/Wind Harmer
1.739
960681AF2-359 GEN
Solar/Wind Harmer
1.683
274776LINCOLN ;7U
Adder
2.689
270036AE2-216 BAT
50/50
5.928
270224U2-072_GEN2
Solar/Wind Harmer
1.959
965051AG1-369 GEN
Solar/Wind Harmer
2.745
270404AC1-167 GEN
Solar/Wind Harmer
0.567
970031AG2-029 GEN
Solar/Wind Harmer
11.974
945581AF1-223 GEN
Solar/Wind Harmer
2.044
961761AG1-017 GEN
Solar/Wind Harmer
0.192
247536S-71 GEN
Solar/Wind Harmer
1.803
270485AE1-090_GEN
Solar/Wind Harmer
0.56
246936BC-WTG1
Solar/Wind Harmer
2.335
270489AE1-102 GEN1
Solar/Wind Harmer
0.776
965011AG1-365 GEN
Solar/Wind Harmer
5.263
958861AF2-177 GEN
Solar/Wind Harmer
4.997
945111AF1-176 GEN
Solar/Wind Harmer
8.094
957891AF2-083 GEN
Solar/Wind Harmer
6.788
945371AF1-202 GEN
Solar/Wind Harmer
3.144
24441205WTRV SLR C
Solar/Wind Harmer
0.06
270005AE1-210 C O1
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
0.913
274751CRETE EC ;1U
Adder
2.121
274773LINCOLN ;4U
Adder
2.689
274774LINCOLN ;5U
Adder
2.689
274723RIVER EC ;12
Adder
7.77
270594AE1-207 GEN
Solar/Wind Harmer
5.865
270032AE2-172
Solar/Wind Harmer
2.008
253378AE2-206_GEN
Solar/Wind Harmer
2.385
25326509SID D
Adder
0.833
246937BC-WTG2
Solar/Wind Harmer
2.335
247607V1-011 GEN
Solar/Wind Harmer
2.218
942221AE2-234 GEN
Solar/Wind Harmer
1.641
274770LINCOLN ;1U
Adder
2.689
274771LINCOLN ;2U
Adder
2.689
274805UNIV PK N;1U
Adder
2.168
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
276820AF1-078_GEN
Solar/Wind Harmer
1.059
962771AG1-126 GEN
Solar/Wind Harmer
20.746
970153AG2-106 GEN
Solar/Wind Harmer
9.046
24695305TIMB G C
Solar/Wind Harmer
1.818
270588AE1-091_GEN
Solar/Wind Harmer
5.471
960071AF2-298 GEN
Solar/Wind Harmer
0.725
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
247643Z2-116 C
Solar/Wind Harmer
0.032
946031AF1-268 GEN
Solar/Wind Harmer
3.631
972181SS23-001
Solar/Wind Harmer
2.574
276164X3-005 C
Solar/Wind Harmer
0.304
274811UNIV PK N;7U
Adder
2.163
970289AG2-191 GEN
Solar/Wind Harmer
0.331
247642Z2-115 C
Solar/Wind Harmer
0.028
971995AH1-542 GEN
Solar/Wind Harmer
11.711
970155AG2-107 GEN
Solar/Wind Harmer
9.046
965421AG1-410 GEN
Solar/Wind Harmer
17.703
270024AE2-089 GEN
Solar/Wind Harmer
2.182
965651AG1-433 GEN
Solar/Wind Harmer
2.517
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
24639705ELKHART HY
Adder
0.071
270449AD2-020 GEN
Solar/Wind Harmer
1.263
972207SS24-0001
Solar/Wind Harmer
9.56
270055AF2-134 C O1
Solar/Wind Harmer
1.309
274812UNIV PK N;8U
Adder
2.163
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
970149AG2-104 GEN
Solar/Wind Harmer
12.811
270297AD1-101 GEN
Solar/Wind Harmer
1.121
270258AD1-119 GEN
Solar/Wind Harmer
1.088
943021AE2-325 GEN
Solar/Wind Harmer
1.641
970373AG2-245 GEN
Solar/Wind Harmer
9.16
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270317AD1-130_GEN
Solar/Wind Harmer
2.967
270520AE2-214 GEN
Solar/Wind Harmer
5.342
241813AF1-122_GEN
Solar/Wind Harmer
4.135
971201AH1-060 GEN
Solar/Wind Harmer
1.292
962761AG1-125 GEN
Solar/Wind Harmer
20.746
253333AC1-068 GEN
Solar/Wind Harmer
0.503
25326309TAIT D
Adder
0.523
270216AD2-079_GEN
Solar/Wind Harmer
0.277
274754CRETE EC ;4U
Adder
2.121
274802UNIV PARK;5U
Adder
2.508
970883AG2-550 GEN
Solar/Wind Harmer
4.428
274808UNIV PK N;4U
Adder
2.154
270054AF2-122 C O1
Solar/Wind Helper
0.81
970065AG2-057 GEN
Solar/Wind Harmer
0.646
246938BC-WTG3
Solar/Wind Harmer
2.375
965021AG1-366 GEN
Solar/Wind Harmer
1.224
270044AE2-322 C
Solar/Wind Harmer
0.688
270043AE2-236 GEN
Solar/Wind Harmer
2.686
945111AF1-176 GEN
Solar/Wind Harmer
2.565
270505AE1-170 C O1
Solar/Wind Harmer
6.785
962031AG1-047 GEN
Solar/Wind Harmer
1.355
957741AF2-068 GEN
Solar/Wind Harmer
6.722
970825AG2-519 GEN
Solar/Wind Harmer
2.451
274772LINCOLN ;3U
Adder
2.689
274724RIVER EC ;11
Adder
7.679
965461AG1-414 GEN
Solar/Wind Harmer
0.977
270435AC2-044 GEN
Solar/Wind Harmer
1.194
270007AE1-245 C
Solar/Wind Harmer
3.03
270071AF1-092 GEN
Solar/Wind Harmer
7.157
24729505KEY G4
Adder
3.056
958711AF2-162 GEN
Solar/Wind Harmer
0.466
971771AH1-392 GEN
Solar/Wind Harmer
4.076
270543AE2-219 C
Solar/Wind Harmer
4.428
971549AH1-272 GEN
Solar/Wind Harmer
8.047
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
942051AE2-217 GEN
Solar/Wind Harmer
13.86
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270063AE2-323 C
Solar/Wind Harmer
1.045
944531AF1-118 GEN
Solar/Wind Harmer
16.62
270541AE2-072 C
Solar/Wind Harmer
2.143
971347AH1-153 GEN
Solar/Wind Harmer
2.29
972231SS25-0005
Solar/Wind Harmer
4.119
274752CRETE EC ;2U
Adder
2.121
971029AG2-637 GEN
Solar/Wind Harmer
6.602
274775LINCOLN ;6U
Adder
2.689
274777LINCOLN ;8U
Adder
2.689
972037AH1-567 GEN1
Adder
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.337
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.48
MECLTFEXP_MEC->PJM
CLTF
6.274
SIGELTFEXP_SIGE->PJM
CLTF
0.18
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.276
WECLTFEXP_WEC->PJM
CLTF
1.577
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.149
LAGNLTFEXP_LAGN->PJM
CLTF
5.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.308
TVALTFEXP_TVA->PJM
CLTF
2.351

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.35 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1484.33
MW Contribution:
11.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.649
253400AC2-068 GEN
Solar/Wind Harmer
0.383
247620Y3-023
Adder
0.213
944541AF1-119 GEN
Solar/Wind Harmer
1.928
270201AC2-176 GEN
Solar/Wind Harmer
2.303
964611AG1-324 GEN
Solar/Wind Harmer
0.233
965791AG1-447 GEN
Solar/Wind Harmer
2.848
270031AE2-169
Solar/Wind Harmer
3.621
270475AD2-096_GEN
50/50
7.753
270491AE1-102 GEN2
Solar/Wind Harmer
0.776
270518AE2-148 GEN
Solar/Wind Harmer
6.224
253325AC1-069 GEN
Solar/Wind Harmer
0.503
24441505OLIV SLR
Solar/Wind Harmer
0.06
270004AE1-209 GEN
Solar/Wind Harmer
2.379
274753CRETE EC ;3U
Adder
2.121
274814UNIV PK N;0U
Adder
2.182
274807UNIV PK N;3U
Adder
2.178
274803UNIV PARK;6U
Adder
2.508
270349AD2-093_GEN
Solar/Wind Harmer
4.839
270471AD2-092_GEN
Solar/Wind Harmer
4.839
270246TR4_N_V150
Solar/Wind Harmer
0.468
25322209TAIT E
Adder
4.65
25322209TAIT E
Adder
4.546
253370AE2-315 SEC1
Adder
0.922
247621Y3-024
Adder
0.108
965681AG1-436 GEN
Solar/Wind Harmer
5.567
253383AE2-342_GEN
Solar/Wind Harmer
0.387
270535AF1-215 GEN1
Solar/Wind Harmer
1.963
270536AF1-215 GEN2
Solar/Wind Harmer
1.963
970291AG2-192 GEN
Solar/Wind Harmer
0.56
970291AG2-192 GEN
Solar/Wind Harmer
0.18
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
241973AD2-163_GEN1
Solar/Wind Harmer
1.933
241974AD2-163_GEN2
Solar/Wind Harmer
1.933
270302AB2-170 GEN
Solar/Wind Harmer
7.76
970179AG2-119 GEN
Solar/Wind Harmer
6.743
241955AC1-078 GEN
Solar/Wind Harmer
4.963
957201AF2-014 GEN
Solar/Wind Harmer
2.707
247521TR3_G114
Solar/Wind Harmer
1.848
963791AG1-232 GEN
Solar/Wind Harmer
6.667
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
253343AC1-166 GEN
Solar/Wind Harmer
0.521
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
944161AF1-084 GEN
Solar/Wind Harmer
0.992
970289AG2-191 GEN
Solar/Wind Harmer
0.819
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241972AD1-140 GEN
Solar/Wind Harmer
2.551
270191TR4_S_V150
Solar/Wind Harmer
1.649
965041AG1-368 GEN
Solar/Wind Harmer
5.334
945631AF1-228 GEN
Solar/Wind Harmer
2.5
959331AF2-224 GEN
Solar/Wind Harmer
5.263
253338AC1-165 GEN
Solar/Wind Harmer
0.521
270526AF1-158 GEN
Solar/Wind Harmer
2.036
964611AG1-324 GEN
Solar/Wind Harmer
1.739
960681AF2-359 GEN
Solar/Wind Harmer
1.683
274776LINCOLN ;7U
Adder
2.689
270485AE1-090_GEN
Solar/Wind Harmer
0.56
246936BC-WTG1
Solar/Wind Harmer
2.335
270489AE1-102 GEN1
Solar/Wind Harmer
0.776
965011AG1-365 GEN
Solar/Wind Harmer
5.263
253378AE2-206_GEN
Solar/Wind Harmer
2.385
25326509SID D
Adder
0.833
246937BC-WTG2
Solar/Wind Harmer
2.335
247607V1-011 GEN
Solar/Wind Harmer
2.218
942221AE2-234 GEN
Solar/Wind Harmer
1.641
274770LINCOLN ;1U
Adder
2.689
274771LINCOLN ;2U
Adder
2.689
274805UNIV PK N;1U
Adder
2.168
958861AF2-177 GEN
Solar/Wind Harmer
4.997
945111AF1-176 GEN
Solar/Wind Harmer
8.094
957891AF2-083 GEN
Solar/Wind Harmer
6.788
945371AF1-202 GEN
Solar/Wind Harmer
3.144
24441205WTRV SLR C
Solar/Wind Harmer
0.06
270005AE1-210 C O1
Solar/Wind Harmer
2.379
970825AG2-519 GEN
Solar/Wind Harmer
0.913
274751CRETE EC ;1U
Adder
2.121
274773LINCOLN ;4U
Adder
2.689
274774LINCOLN ;5U
Adder
2.689
274723RIVER EC ;12
Adder
7.77
270594AE1-207 GEN
Solar/Wind Harmer
5.865
270032AE2-172
Solar/Wind Harmer
2.008
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
276820AF1-078_GEN
Solar/Wind Harmer
1.059
962771AG1-126 GEN
Solar/Wind Harmer
20.746
970153AG2-106 GEN
Solar/Wind Harmer
9.046
24695305TIMB G C
Solar/Wind Harmer
1.818
270588AE1-091_GEN
Solar/Wind Harmer
5.471
960071AF2-298 GEN
Solar/Wind Harmer
0.725
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
247643Z2-116 C
Solar/Wind Harmer
0.032
946031AF1-268 GEN
Solar/Wind Harmer
3.631
972181SS23-001
Solar/Wind Harmer
2.574
276164X3-005 C
Solar/Wind Harmer
0.304
274811UNIV PK N;7U
Adder
2.163
970289AG2-191 GEN
Solar/Wind Harmer
0.331
247642Z2-115 C
Solar/Wind Harmer
0.028
971995AH1-542 GEN
Solar/Wind Harmer
11.711
970155AG2-107 GEN
Solar/Wind Harmer
9.046
965421AG1-410 GEN
Solar/Wind Harmer
17.703
270024AE2-089 GEN
Solar/Wind Harmer
2.182
965651AG1-433 GEN
Solar/Wind Harmer
2.517
253370AE2-315 SEC1
Adder
0.922
253371AE2-315 SEC2
Adder
0.873
24639705ELKHART HY
Adder
0.071
270449AD2-020 GEN
Solar/Wind Harmer
1.263
972207SS24-0001
Solar/Wind Harmer
9.56
270055AF2-134 C O1
Solar/Wind Harmer
1.309
274812UNIV PK N;8U
Adder
2.163
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
970149AG2-104 GEN
Solar/Wind Harmer
12.811
270297AD1-101 GEN
Solar/Wind Harmer
1.121
270258AD1-119 GEN
Solar/Wind Harmer
1.088
943021AE2-325 GEN
Solar/Wind Harmer
1.641
970373AG2-245 GEN
Solar/Wind Harmer
9.16
970885AG2-551 GEN
Solar/Wind Harmer
1.03
270383AD1-128 GEN
Solar/Wind Harmer
2.627
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270317AD1-130_GEN
Solar/Wind Harmer
2.967
270520AE2-214 GEN
Solar/Wind Harmer
5.342
241813AF1-122_GEN
Solar/Wind Harmer
4.135
971201AH1-060 GEN
Solar/Wind Harmer
1.292
962761AG1-125 GEN
Solar/Wind Harmer
20.746
253333AC1-068 GEN
Solar/Wind Harmer
0.503
25326309TAIT D
Adder
0.523
270216AD2-079_GEN
Solar/Wind Harmer
0.277
274754CRETE EC ;4U
Adder
2.121
274802UNIV PARK;5U
Adder
2.508
270466AD2-091
50/50
5.389
938701AE1-092 GEN
Solar/Wind Harmer
21.815
270462AD2-086
Solar/Wind Harmer
6.445
942801AE2-298 GEN
Solar/Wind Harmer
0.854
270247TR4_N_V136
Solar/Wind Harmer
0.468
944231AF1-091 GEN
Solar/Wind Harmer
8.735
253349AC2-067 GEN
Solar/Wind Harmer
0.953
960971AF2-388 GEN
Solar/Wind Harmer
5.034
970349AG2-230 GEN
Solar/Wind Harmer
6.869
961051AF2-396 GEN
Solar/Wind Harmer
7.17
961051AF2-396 GEN
Solar/Wind Harmer
3.335
270599AE1-208 GEN
Solar/Wind Harmer
3.621
970883AG2-550 GEN
Solar/Wind Harmer
4.428
274808UNIV PK N;4U
Adder
2.154
270054AF2-122 C O1
Solar/Wind Helper
0.81
970065AG2-057 GEN
Solar/Wind Harmer
0.646
246938BC-WTG3
Solar/Wind Harmer
2.375
965021AG1-366 GEN
Solar/Wind Harmer
1.224
270044AE2-322 C
Solar/Wind Harmer
0.688
270043AE2-236 GEN
Solar/Wind Harmer
2.686
945111AF1-176 GEN
Solar/Wind Harmer
2.565
270505AE1-170 C O1
Solar/Wind Harmer
6.785
962031AG1-047 GEN
Solar/Wind Harmer
1.355
957741AF2-068 GEN
Solar/Wind Harmer
6.722
970825AG2-519 GEN
Solar/Wind Harmer
2.451
274772LINCOLN ;3U
Adder
2.689
274724RIVER EC ;11
Adder
7.679
965461AG1-414 GEN
Solar/Wind Harmer
0.977
270435AC2-044 GEN
Solar/Wind Harmer
1.194
270007AE1-245 C
Solar/Wind Harmer
3.03
270071AF1-092 GEN
Solar/Wind Harmer
7.157
24729505KEY G4
Adder
3.056
958711AF2-162 GEN
Solar/Wind Harmer
0.466
971771AH1-392 GEN
Solar/Wind Harmer
4.076
270543AE2-219 C
Solar/Wind Harmer
4.428
971549AH1-272 GEN
Solar/Wind Harmer
8.047
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
942051AE2-217 GEN
Solar/Wind Harmer
13.86
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270063AE2-323 C
Solar/Wind Harmer
1.045
944531AF1-118 GEN
Solar/Wind Harmer
16.62
270541AE2-072 C
Solar/Wind Harmer
2.143
971347AH1-153 GEN
Solar/Wind Harmer
2.29
972231SS25-0005
Solar/Wind Harmer
4.119
274752CRETE EC ;2U
Adder
2.121
270036AE2-216 BAT
50/50
5.928
270224U2-072_GEN2
Solar/Wind Harmer
1.959
965051AG1-369 GEN
Solar/Wind Harmer
2.745
270404AC1-167 GEN
Solar/Wind Harmer
0.567
970031AG2-029 GEN
Solar/Wind Harmer
11.974
945581AF1-223 GEN
Solar/Wind Harmer
2.044
961761AG1-017 GEN
Solar/Wind Harmer
0.192
247536S-71 GEN
Solar/Wind Harmer
1.803
971029AG2-637 GEN
Solar/Wind Harmer
6.602
274775LINCOLN ;6U
Adder
2.689
274777LINCOLN ;8U
Adder
2.689
972037AH1-567 GEN1
Adder
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.337
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.942
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.48
MECLTFEXP_MEC->PJM
CLTF
6.274
SIGELTFEXP_SIGE->PJM
CLTF
0.18
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.276
WECLTFEXP_WEC->PJM
CLTF
1.577
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.149
LAGNLTFEXP_LAGN->PJM
CLTF
5.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.308
TVALTFEXP_TVA->PJM
CLTF
2.351

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.56 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5140.38
MW Contribution:
12.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.109
270485AE1-090_GEN
Solar/Wind Harmer
0.688
972269AH1-719 GEN
Adder
2.545
253398AE2-221_GEN2
Solar/Wind Harmer
4.9
246936BC-WTG1
Solar/Wind Harmer
4.216
270489AE1-102 GEN1
Solar/Wind Harmer
1.401
965011AG1-365 GEN
Solar/Wind Harmer
10.725
958861AF2-177 GEN
Solar/Wind Harmer
11.586
252510AF1-249 C
Solar/Wind Harmer
0.441
945371AF1-202 GEN
Solar/Wind Harmer
7.376
23559101PLEAS2
50/50
6.362
970149AG2-104 GEN
Solar/Wind Harmer
25.328
270119AB2-067 GEN1
50/50
7.109
253378AE2-206_GEN
Solar/Wind Harmer
3.997
25326509SID D
Adder
1.451
970879AG2-548 GEN
Solar/Wind Harmer
1.275
246937BC-WTG2
Solar/Wind Harmer
4.216
247607V1-011 GEN
Solar/Wind Harmer
4.231
962581AG1-107 GEN
Solar/Wind Harmer
5.356
961491AF2-440 GEN
Solar/Wind Harmer
2.226
942221AE2-234 GEN
Solar/Wind Harmer
3.71
274770LINCOLN ;1U
Adder
8.673
274771LINCOLN ;2U
Adder
8.673
274805UNIV PK N;1U
Adder
5.149
274696ROCKY RD ;4P
Adder
11.533
274697ROCKY RD ;3P
Adder
3.061
23751201ROTHROCK
Solar/Wind Helper
0.836
235020AA1-095 C
Solar/Wind Helper
0.054
237061AD1-155 GEN
Solar/Wind Helper
1.772
238221AF1-254 C O1
Solar/Wind Helper
0.278
316411AF1-147_GEN1
Solar/Wind Helper
0.898
223402AF1-300 C
Solar/Wind Helper
0.371
233930AB2-032 GEN
Solar/Wind Helper
0.385
233982AB2-133 GEN
Solar/Wind Helper
0.363
233946AB2-136 GEN
Solar/Wind Helper
0.575
232410W1-006 C
Solar/Wind Helper
0.513
233952AC2-187 GEN
Solar/Wind Helper
0.235
233954AC2-188 GEN
Solar/Wind Helper
0.235
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.051
207471AF2-354 C
Solar/Wind Helper
0.17
961431AF2-434 GEN
Solar/Wind Helper
0.441
270005AE1-210 C O1
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
6.717
270209AC1-174_GEN
Solar/Wind Harmer
4.274
270239V3-007_GEN1
Solar/Wind Harmer
1.807
270331AC1-082 GEN3
Solar/Wind Harmer
0.501
25196808ZIMRHP
Adder
79.685
970825AG2-519 GEN
Solar/Wind Harmer
2.203
25196008MFTGT1
Adder
1.45
274751CRETE EC ;1U
Adder
8.473
274773LINCOLN ;4U
Adder
8.673
274774LINCOLN ;5U
Adder
8.673
274723RIVER EC ;12
Adder
18.412
23583801GRNGAP
Solar/Wind Helper
5.644
238126S14_GEN_1
Solar/Wind Helper
0.836
237085AD2-009_GEN
Solar/Wind Helper
1.667
3141196NOKESVL
Solar/Wind Helper
1.039
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.235
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.091
209116AE2-175 GEN
Solar/Wind Helper
1.799
961421AF2-433 GEN
Solar/Wind Helper
0.441
270594AE1-207 GEN
Solar/Wind Harmer
13.371
270032AE2-172
Solar/Wind Harmer
4.579
24318905MLG2
50/50
7.027
270349AD2-093_GEN
Solar/Wind Harmer
4.455
270471AD2-092_GEN
Solar/Wind Harmer
4.455
253383AE2-342_GEN
Solar/Wind Harmer
1.04
25322209TAIT E
Adder
10.635
25322209TAIT E
Adder
10.396
253370AE2-315 SEC1
Adder
2.18
270246TR4_N_V150
Solar/Wind Harmer
0.912
247621Y3-024
Adder
0.255
316097T157 G90
Solar/Wind Helper
1.515
238147AE2-230_GEN1
Solar/Wind Helper
0.501
237080AD1-060 GEN
Solar/Wind Helper
0.346
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.028
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
970155AG2-107 GEN
Solar/Wind Harmer
17.885
971995AH1-542 GEN
Solar/Wind Harmer
12.463
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
965421AG1-410 GEN
Solar/Wind Harmer
32.318
253316AC1-085 GEN3
Solar/Wind Harmer
8.992
946171AF1-282 GEN
Solar/Wind Harmer
10.741
965651AG1-433 GEN
Solar/Wind Harmer
5.801
252516AE2-318_GEN
Solar/Wind Harmer
10.604
270024AE2-089 GEN
Solar/Wind Harmer
4.961
25194608D.CRK4
Adder
1.739
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.137
24728605AND G2
Adder
3.925
274676JOLIET 29;8U
Adder
31.291
972203AH1-686 GEN
Adder
2.344
274745AC1-111 GEN9
Adder
5.677
274682WAUKEGAN ;7U
Adder
18.178
316095T157 G97
Solar/Wind Helper
1.515
238185AF2-356 C
Solar/Wind Helper
2.686
238109AE1-109 GEN2
Solar/Wind Helper
0.115
238120AE2-309 GEN
Solar/Wind Helper
0.534
23751101LEADS_P59
Solar/Wind Helper
2.15
23777801MSM_W1-116
Solar/Wind Helper
0.116
227287AC2-120 GEN
Solar/Wind Helper
0.35
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.513
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.501
270120AB2-067 GEN2
50/50
7.109
270054AF2-122 C O1
Solar/Wind Harmer
3.972
938701AE1-092 GEN
Solar/Wind Harmer
23.766
270462AD2-086
Solar/Wind Harmer
7.908
253415AE1-040 GEN
Solar/Wind Harmer
1.242
253349AC2-067 GEN
Solar/Wind Harmer
2.203
270247TR4_N_V136
Solar/Wind Harmer
0.912
942801AE2-298 GEN
Solar/Wind Harmer
1.621
960971AF2-388 GEN
Solar/Wind Harmer
11.601
25194408D.CRK1
Adder
8
970883AG2-550 GEN
Solar/Wind Harmer
10.561
970349AG2-230 GEN
Solar/Wind Harmer
15.797
270599AE1-208 GEN
Solar/Wind Harmer
8.576
926881AC1-175 GEN
Solar/Wind Harmer
5.862
944231AF1-091 GEN
Solar/Wind Harmer
18.887
24728905RICHG2
Adder
3.96
274808UNIV PK N;4U
Adder
5.115
274674JOLIET 9 ;6U
Adder
15.699
274693ROCKY RD ;1P
Adder
11.156
274683WAUKEGAN ;8U
Adder
21.305
274683WAUKEGAN ;8U
Adder
9.68
23585401KL_K28_T16
Solar/Wind Helper
1.5
238117U2-030
Solar/Wind Helper
0.345
238148AE2-230_GEN2
Solar/Wind Helper
0.501
235062AE1-101 C1
Solar/Wind Helper
1.678
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.371
232424Y1-079 C
Solar/Wind Helper
0.118
232428Y3-058 C
Solar/Wind Helper
0.342
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.293
20675428EAM_W2-061
Solar/Wind Helper
0.016
962761AG1-125 GEN
Solar/Wind Harmer
41.016
270520AE2-214 GEN
Solar/Wind Harmer
7.243
270391AF1-285 GEN3
Solar/Wind Harmer
1.393
253333AC1-068 GEN
Solar/Wind Harmer
1.191
270317AD1-130_GEN
Solar/Wind Harmer
3.64
270273AD2-016 GEN
Solar/Wind Harmer
3.013
25326309TAIT D
Adder
1.195
241813AF1-122_GEN
Solar/Wind Harmer
5.897
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.062
270437AC2-090 C
Solar/Wind Harmer
5.862
270216AD2-079_GEN
Solar/Wind Harmer
0.634
274754CRETE EC ;4U
Adder
8.473
274802UNIV PARK;5U
Adder
5.968
274732ELWOOD EC;7P
Adder
16.762
274674JOLIET 9 ;6U
Adder
15.699
235067AD1-061 GEN
Solar/Wind Helper
0.451
237002AB1-128_GEN
Solar/Wind Helper
0.448
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.118
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.313
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.443
961331AF2-424 GEN
Solar/Wind Helper
0.442
24318805MLG1
50/50
10.127
270475AD2-096_GEN
50/50
7.137
270518AE2-148 GEN
Solar/Wind Harmer
13.818
253325AC1-069 GEN
Solar/Wind Harmer
1.191
971199AH1-059 GEN
Solar/Wind Harmer
2.312
270491AE1-102 GEN2
Solar/Wind Harmer
1.401
270004AE1-209 GEN
Solar/Wind Harmer
5.743
24379505HDWTR1G C
Solar/Wind Harmer
8.305
270329AC1-082 GEN1
Solar/Wind Harmer
0.5
274753CRETE EC ;3U
Adder
8.473
274814UNIV PK N;0U
Adder
5.182
274807UNIV PK N;3U
Adder
5.171
274803UNIV PARK;6U
Adder
5.968
972038AH1-567 GEN2
Adder
0.373
238108AE1-109 GEN1
Solar/Wind Helper
0.115
23562501BACKB
Solar/Wind Helper
1.023
237001AB1-127_GEN
Solar/Wind Helper
0.446
233918AB1-142 GEN
Solar/Wind Helper
0.508
228729W2-030 C
Solar/Wind Helper
0.112
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
946101AF1-275 GEN
Solar/Wind Harmer
1.811
942861AE2-305 GEN
Solar/Wind Harmer
9.069
270269AC2-059
Solar/Wind Harmer
10.571
972159AH1-661 GEN
Adder
1.106
241960AC2-195 GEN
Solar/Wind Harmer
3.055
971073AG2-665 GEN
Solar/Wind Harmer
8.771
25326109MON D
Adder
1.442
927014AC1-188 GEN
Solar/Wind Harmer
1.717
253400AC2-068 GEN
Solar/Wind Harmer
0.886
25183208HLCRTG
Solar/Wind Harmer
6.427
944541AF1-119 GEN
Solar/Wind Harmer
4.444
25194508D.CRK3
Adder
1.496
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.456
270201AC2-176 GEN
Solar/Wind Harmer
5.42
964611AG1-324 GEN
Solar/Wind Harmer
0.551
270031AE2-169
Solar/Wind Harmer
8.576
270383AD1-128 GEN
Solar/Wind Harmer
6.419
247620Y3-023
Adder
0.483
24728805RICHG1
Adder
3.96
274695ROCKY RD ;2P
Adder
11.267
235054AD2-180 GEN
Solar/Wind Helper
2.054
235531U2-073 GEN
Solar/Wind Helper
3.347
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.972
316045AC1-158 PL2
Solar/Wind Helper
4.182
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
20674328GAR_V4-001
Solar/Wind Helper
0.023
23559001PLEAS1
50/50
6.362
961921AG1-034 GEN
Solar/Wind Harmer
15.551
270287AF1-227 GEN3
Solar/Wind Harmer
2.504
942051AE2-217 GEN
Solar/Wind Harmer
20.995
942871AE2-306 GEN
Solar/Wind Harmer
1.045
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
958581AF2-149 GEN
Solar/Wind Harmer
4.712
957541AF2-048 GEN
Solar/Wind Harmer
1.717
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.358
25196608WSDLE5
Adder
9.072
252507AC2-088 GEN
Solar/Wind Harmer
1.892
270063AE2-323 C
Solar/Wind Harmer
2.32
971347AH1-153 GEN
Solar/Wind Harmer
5.266
270330AC1-082 GEN2
Solar/Wind Harmer
0.5
274752CRETE EC ;2U
Adder
8.473
24728705AND G3
Adder
8.209
274826FISK ;BP
Adder
11.201
274730ELWOOD EC;6P
Adder
16.762
238127S14_GEN_2
Solar/Wind Helper
0.836
238152AF2-075_GEN
Solar/Wind Helper
0.715
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.513
316044AC1-158 PL1
Solar/Wind Helper
1.307
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.586
202652Y1-033 WT C
Solar/Wind Helper
0.504
270286AF1-227 GEN2
Solar/Wind Harmer
2.504
270578AF1-285 GEN2
Solar/Wind Harmer
1.393
971073AG2-665 GEN
Solar/Wind Harmer
1.275
960001AF2-291 GEN
Solar/Wind Harmer
3.25
270258AD1-119 GEN
Solar/Wind Harmer
2.156
270297AD1-101 GEN
Solar/Wind Harmer
2.147
270222AC2-111 GEN
Solar/Wind Harmer
4.718
270510AE1-227 GEN1
Solar/Wind Harmer
2.605
970091AG2-072 GEN
Adder
77.647
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.283
233987AB2-037 GEN
Solar/Wind Helper
2.369
232417X3-008 C
Solar/Wind Helper
0.235
233923SMA
Solar/Wind Helper
0.76
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.329
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
957921AF2-086 GEN
Solar/Wind Helper
0.436
270051AF1-062 GEN
50/50
11.798
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
970879AG2-548 GEN
Solar/Wind Harmer
8.771
970065AG2-057 GEN
Solar/Wind Harmer
0.921
253394AE2-221_GEN
Solar/Wind Harmer
4.9
246938BC-WTG3
Solar/Wind Harmer
4.289
971191AH1-055 GEN
Solar/Wind Harmer
20.077
965021AG1-366 GEN
Solar/Wind Harmer
2.494
270043AE2-236 GEN
Solar/Wind Harmer
5.865
270367AC2-061_GEN
Solar/Wind Harmer
3.367
270044AE2-322 C
Solar/Wind Harmer
1.388
962031AG1-047 GEN
Solar/Wind Harmer
3.189
957741AF2-068 GEN
Solar/Wind Harmer
15.82
270512AE1-227 GEN2
Solar/Wind Harmer
2.212
270186AC1-089 GEN
Solar/Wind Harmer
6.425
270240V3-007_GEN2
Solar/Wind Harmer
6.498
970825AG2-519 GEN
Solar/Wind Harmer
5.915
25196008MFTGT1
Adder
1.404
274772LINCOLN ;3U
Adder
8.673
274724RIVER EC ;11
Adder
18.196
972259AH1-714 GEN
Adder
19.5
274729ELWOOD EC;1P
Adder
16.762
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.186
316415AF1-147_GEN2
Solar/Wind Helper
0.898
205916AD1-020 GEN
Solar/Wind Helper
1.732
233944AB2-135 GEN
Solar/Wind Helper
0.596
232408W1-005 C
Solar/Wind Helper
0.513
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.075
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.093
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.443
963151AG1-164 GEN
Solar/Wind Helper
0.443
961341AF2-425 GEN
Solar/Wind Helper
0.442
212507AE2-042_GEN
Solar/Wind Helper
1.561
270224U2-072_GEN2
Solar/Wind Harmer
2.274
270291AC1-194 GEN
Solar/Wind Harmer
5.61
253406AD2-031_GEN
Solar/Wind Harmer
1.383
965051AG1-369 GEN
Solar/Wind Harmer
5.355
270377AD1-106 GEN
Solar/Wind Harmer
5.62
971985AH1-537 GEN
Solar/Wind Harmer
18.964
945581AF1-223 GEN
Solar/Wind Harmer
4.795
971029AG2-637 GEN
Solar/Wind Harmer
15.851
970031AG2-029 GEN
Solar/Wind Harmer
26.415
270404AC1-167 GEN
Solar/Wind Harmer
1.144
247536S-71 GEN
Solar/Wind Harmer
4.271
961761AG1-017 GEN
Solar/Wind Harmer
0.451
274775LINCOLN ;6U
Adder
8.673
274777LINCOLN ;8U
Adder
8.673
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.789
274675JOLIET 29;7U
Adder
31.291
274675JOLIET 29;7U
Adder
30.174
23750701CROSSCHOOL
Solar/Wind Helper
1.517
205943AE1-185 GEN
Solar/Wind Helper
0.515
233915AB1-141 GEN
Solar/Wind Helper
0.508
228728W1-130C
Solar/Wind Helper
0.055
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
203955AF1-039 C O1
Solar/Wind Helper
0.332
212266LOR1
Solar/Wind Helper
0.302
962771AG1-126 GEN
Solar/Wind Harmer
41.016
970153AG2-106 GEN
Solar/Wind Harmer
17.885
270284AF1-227 GEN1
Solar/Wind Harmer
6.768
24721905FLATG4
Adder
24.045
276820AF1-078_GEN
Solar/Wind Harmer
1.776
960071AF2-298 GEN
Solar/Wind Harmer
1.647
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
253317AC1-085 GEN4
Solar/Wind Harmer
8.992
946181AF1-283 GEN
Solar/Wind Harmer
13.963
24695305TIMB G C
Solar/Wind Harmer
3.573
270588AE1-091_GEN
Solar/Wind Harmer
11.753
252519AF1-045_GEN
Solar/Wind Harmer
3.859
252524AE2-267 GEN
Solar/Wind Harmer
1.667
25194608D.CRK4
Adder
1.739
946031AF1-268 GEN
Solar/Wind Harmer
8.725
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.137
24728505AND G1
Adder
3.925
274676JOLIET 29;8U
Adder
30.174
274734ELWOOD EC;8P
Adder
16.762
274736ELWOOD EC;9P
Adder
16.762
274682WAUKEGAN ;7U
Adder
18.178
964991AG1-363 GEN
Solar/Wind Helper
5.171
238110AE1-109 GEN3
Solar/Wind Helper
0.115
235063AE1-101 C2
Solar/Wind Helper
1.678
205932AD2-116_GEN
Solar/Wind Helper
0.514
233996TM1833_GEN
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
316447AC1-158 HLD
Solar/Wind Helper
2.876
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.526
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
241955AC1-078 GEN
Solar/Wind Harmer
8.781
241973AD2-163_GEN1
Solar/Wind Harmer
2.319
241974AD2-163_GEN2
Solar/Wind Harmer
2.319
943861AF1-054 GEN
Solar/Wind Harmer
4.476
943851AF1-053 GEN
Solar/Wind Harmer
2.163
270227U2-072_GEN3
Solar/Wind Harmer
2.274
270228U2-072_GEN4
Solar/Wind Harmer
2.274
270231U2-072_GEN5
Solar/Wind Harmer
2.274
253343AC1-166 GEN
Solar/Wind Harmer
1.235
270302AB2-170 GEN
Solar/Wind Harmer
9.522
970179AG2-119 GEN
Solar/Wind Harmer
8.806
253372AE2-315 SEC3
Adder
2.062
253372AE2-315 SEC3
Adder
2.062
25306009OHH W.
Adder
3.128
957201AF2-014 GEN
Solar/Wind Harmer
4.888
253433AC1-085 GEN1
Solar/Wind Harmer
5.708
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.604
963791AG1-232 GEN
Solar/Wind Harmer
14.371
274827FISK ;RP
Adder
7.938
274800UNIV PARK;3U
Adder
5.964
274801UNIV PARK;4U
Adder
5.964
972227AH1-698 GEN1
Adder
2.668
274735ELWOOD EC;4P
Adder
16.762
274744AC1-111 GEN8
Adder
5.677
238169AE2-226 GEN1
Solar/Wind Helper
0.708
238170AE2-226 GEN2
Solar/Wind Helper
0.708
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.36
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.795
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.064
207408W3-077 C
Solar/Wind Helper
0.085
209054AE2-059 GEN
Solar/Wind Helper
0.08
270459AD2-067 GEN
Solar/Wind Harmer
10.212
940611AE2-048 GEN
Solar/Wind Harmer
24.76
941391AE2-136 GEN
Solar/Wind Harmer
12.83
270435AC2-044 GEN
Solar/Wind Harmer
2.156
270007AE1-245 C
Solar/Wind Harmer
5.779
24729505KEY G4
Adder
6.914
971567AH1-282 GEN
Solar/Wind Harmer
5.316
270071AF1-092 GEN
Solar/Wind Harmer
15.971
958711AF2-162 GEN
Solar/Wind Harmer
1.074
25196408WSDLE3
Adder
9.339
25196308WSDLE2
Adder
9.258
25196208WSDLE1
Adder
9.235
25196708WSDLE6
Adder
9.211
270543AE2-219 C
Solar/Wind Harmer
10.561
25196108MFTGT2
Adder
1.598
25196108MFTGT2
Adder
1.484
274728ELWOOD EC;5P
Adder
16.762
20390526W1-045 C
Solar/Wind Helper
0.354
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.078
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.036
961821AG1-024 GEN
Solar/Wind Harmer
10.368
972239AH1-704 GEN
Adder
2.66
945631AF1-228 GEN
Solar/Wind Harmer
5.449
270223U2-072_GEN1
Solar/Wind Harmer
2.274
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
8.025
253338AC1-165 GEN
Solar/Wind Harmer
1.235
270263AC1-001 GEN
Solar/Wind Harmer
1.17
241972AD1-140 GEN
Solar/Wind Harmer
5.01
270340AC2-060 GEN
Solar/Wind Harmer
3.331
270191TR4_S_V150
Solar/Wind Harmer
3.216
959331AF2-224 GEN
Solar/Wind Harmer
10.725
965041AG1-368 GEN
Solar/Wind Harmer
10.701
966831AG1-554 GEN
Solar/Wind Harmer
1.275
25196508WSDLE4
Adder
8.979
964611AG1-324 GEN
Solar/Wind Harmer
4.11
274776LINCOLN ;7U
Adder
8.673
274687WILL CNTY;4U
Adder
28.512
274687WILL CNTY;4U
Adder
28.512
274731ELWOOD EC;2P
Adder
16.762
274733ELWOOD EC;3P
Adder
16.762
274746AC1-111 G10
Adder
5.677
238118U2-030_1
Solar/Wind Helper
0.345
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.647
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.372
205956AE1-196_GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.235
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
20720628TIN_W1-124
Solar/Wind Helper
0.192
316164AC1-076 GEN
Solar/Wind Helper
1.108
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.069
20675128HRM_W1-127
Solar/Wind Helper
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.743
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.944
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.079
MECLTFEXP_MEC->PJM
CLTF
15.894
SIGELTFEXP_SIGE->PJM
CLTF
0.505
NYPJM->LTFIMP_NY
CLTF
4.85
LGEELTFEXP_LGEE->PJM
CLTF
6.747
WECLTFEXP_WEC->PJM
CLTF
3.823
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
LAGNLTFEXP_LAGN->PJM
CLTF
14.823
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.742
TVALTFEXP_TVA->PJM
CLTF
7.286

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.72 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5108.61
MW Contribution:
12.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.082
253378AE2-206_GEN
Solar/Wind Harmer
3.988
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.273
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.646
274771LINCOLN ;2U
Adder
8.646
274805UNIV PK N;1U
Adder
5.133
274696ROCKY RD ;4P
Adder
11.497
274697ROCKY RD ;3P
Adder
3.051
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.83
237061AD1-155 GEN
Solar/Wind Helper
1.768
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233930AB2-032 GEN
Solar/Wind Helper
0.384
233982AB2-133 GEN
Solar/Wind Helper
0.362
233946AB2-136 GEN
Solar/Wind Helper
0.574
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
270166AC1-044 GEN3
50/50
7.082
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.564
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.696
958861AF2-177 GEN
Solar/Wind Harmer
11.552
252510AF1-249 C
Solar/Wind Harmer
0.44
945371AF1-202 GEN
Solar/Wind Harmer
7.355
270005AE1-210 C O1
Solar/Wind Harmer
5.726
25196808ZIMRHP
Adder
79.465
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
942081AE2-220 GEN
Solar/Wind Harmer
6.698
270209AC1-174_GEN
Solar/Wind Harmer
4.262
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.448
274773LINCOLN ;4U
Adder
8.646
274774LINCOLN ;5U
Adder
8.646
274723RIVER EC ;12
Adder
18.356
23583801GRNGAP
Solar/Wind Helper
5.632
238126S14_GEN_1
Solar/Wind Helper
0.833
237085AD2-009_GEN
Solar/Wind Helper
1.663
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.235
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.331
270032AE2-172
Solar/Wind Harmer
4.566
24318905MLG2
50/50
7.035
270349AD2-093_GEN
Solar/Wind Harmer
4.445
270471AD2-092_GEN
Solar/Wind Harmer
4.445
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.371
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.5
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
970155AG2-107 GEN
Solar/Wind Harmer
17.815
971995AH1-542 GEN
Solar/Wind Harmer
12.451
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.241
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.784
252516AE2-318_GEN
Solar/Wind Harmer
10.575
270024AE2-089 GEN
Solar/Wind Harmer
4.947
25194608D.CRK4
Adder
1.734
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.122
24728605AND G2
Adder
3.913
274676JOLIET 29;8U
Adder
31.195
972203AH1-686 GEN
Adder
2.333
274745AC1-111 GEN9
Adder
5.66
274682WAUKEGAN ;7U
Adder
18.122
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.674
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.532
23751101LEADS_P59
Solar/Wind Helper
2.129
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
270120AB2-067 GEN2
50/50
7.082
270054AF2-122 C O1
Solar/Wind Harmer
3.971
938701AE1-092 GEN
Solar/Wind Harmer
23.731
270462AD2-086
Solar/Wind Harmer
7.892
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
960971AF2-388 GEN
Solar/Wind Harmer
11.568
25194408D.CRK1
Adder
7.978
970883AG2-550 GEN
Solar/Wind Harmer
10.531
970349AG2-230 GEN
Solar/Wind Harmer
15.75
270599AE1-208 GEN
Solar/Wind Harmer
8.551
926881AC1-175 GEN
Solar/Wind Harmer
5.845
944231AF1-091 GEN
Solar/Wind Harmer
18.84
24728905RICHG2
Adder
3.949
274808UNIV PK N;4U
Adder
5.099
274674JOLIET 9 ;6U
Adder
15.65
274693ROCKY RD ;1P
Adder
11.121
274683WAUKEGAN ;8U
Adder
21.239
274683WAUKEGAN ;8U
Adder
9.65
23585401KL_K28_T16
Solar/Wind Helper
1.493
238117U2-030
Solar/Wind Helper
0.344
238148AE2-230_GEN2
Solar/Wind Helper
0.5
235062AE1-101 C1
Solar/Wind Helper
1.674
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
962761AG1-125 GEN
Solar/Wind Harmer
40.857
270520AE2-214 GEN
Solar/Wind Harmer
7.233
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.008
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.894
971201AH1-060 GEN
Solar/Wind Harmer
1.842
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.845
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.448
274802UNIV PARK;5U
Adder
5.949
274732ELWOOD EC;7P
Adder
16.71
274674JOLIET 9 ;6U
Adder
15.65
235067AD1-061 GEN
Solar/Wind Helper
0.45
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.441
946101AF1-275 GEN
Solar/Wind Harmer
1.808
942861AE2-305 GEN
Solar/Wind Harmer
9.053
270269AC2-059
Solar/Wind Harmer
10.554
972159AH1-661 GEN
Adder
1.111
241960AC2-195 GEN
Solar/Wind Harmer
3.053
971073AG2-665 GEN
Solar/Wind Harmer
8.757
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.713
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.41
944541AF1-119 GEN
Solar/Wind Harmer
4.431
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
23559001PLEAS1
50/50
6.18
961921AG1-034 GEN
Solar/Wind Harmer
15.539
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.96
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.716
957541AF2-048 GEN
Solar/Wind Harmer
1.713
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.25
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.25
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.448
24728705AND G3
Adder
8.184
274826FISK ;BP
Adder
11.167
274730ELWOOD EC;6P
Adder
16.71
238127S14_GEN_2
Solar/Wind Helper
0.833
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.405
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.551
270383AD1-128 GEN
Solar/Wind Harmer
6.401
247620Y3-023
Adder
0.482
24728805RICHG1
Adder
3.949
274695ROCKY RD ;2P
Adder
11.232
235054AD2-180 GEN
Solar/Wind Helper
2.044
235531U2-073 GEN
Solar/Wind Helper
3.333
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
23559101PLEAS2
50/50
6.18
970149AG2-104 GEN
Solar/Wind Harmer
25.229
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
971073AG2-665 GEN
Solar/Wind Harmer
1.273
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
960001AF2-291 GEN
Solar/Wind Harmer
3.242
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.376
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.363
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.582
202652Y1-033 WT C
Solar/Wind Helper
0.501
270051AF1-062 GEN
50/50
11.783
960801AF2-371 GEN
Solar/Wind Harmer
2.935
964871AG1-351 GEN
Solar/Wind Harmer
2.026
970879AG2-548 GEN
Solar/Wind Harmer
8.757
970065AG2-057 GEN
Solar/Wind Harmer
0.921
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.279
971191AH1-055 GEN
Solar/Wind Harmer
20.022
965021AG1-366 GEN
Solar/Wind Harmer
2.488
270043AE2-236 GEN
Solar/Wind Harmer
5.848
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
962031AG1-047 GEN
Solar/Wind Harmer
3.18
957741AF2-068 GEN
Solar/Wind Harmer
15.775
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.479
970825AG2-519 GEN
Solar/Wind Harmer
5.897
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.646
274724RIVER EC ;11
Adder
18.141
972259AH1-714 GEN
Adder
19.441
274729ELWOOD EC;1P
Adder
16.71
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.185
316415AF1-147_GEN2
Solar/Wind Helper
0.896
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
24318805MLG1
50/50
10.084
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.795
253325AC1-069 GEN
Solar/Wind Harmer
1.189
971199AH1-059 GEN
Solar/Wind Harmer
2.315
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270004AE1-209 GEN
Solar/Wind Harmer
5.726
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
24379505HDWTR1G C
Solar/Wind Harmer
8.281
274753CRETE EC ;3U
Adder
8.448
274814UNIV PK N;0U
Adder
5.166
274807UNIV PK N;3U
Adder
5.155
274803UNIV PARK;6U
Adder
5.949
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.015
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.507
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.603
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.62
965051AG1-369 GEN
Solar/Wind Harmer
5.342
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.781
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.807
970031AG2-029 GEN
Solar/Wind Harmer
26.342
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.646
274777LINCOLN ;8U
Adder
8.646
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.777
274675JOLIET 29;7U
Adder
31.195
274675JOLIET 29;7U
Adder
30.081
23750701CROSSCHOOL
Solar/Wind Helper
1.512
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.507
962771AG1-126 GEN
Solar/Wind Harmer
40.857
970153AG2-106 GEN
Solar/Wind Harmer
17.815
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.892
276820AF1-078_GEN
Solar/Wind Harmer
1.772
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
24695305TIMB G C
Solar/Wind Harmer
3.564
270588AE1-091_GEN
Solar/Wind Harmer
11.739
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.7
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.122
24728505AND G1
Adder
3.913
274676JOLIET 29;8U
Adder
30.081
274734ELWOOD EC;8P
Adder
16.71
274736ELWOOD EC;9P
Adder
16.71
274682WAUKEGAN ;7U
Adder
18.122
964991AG1-363 GEN
Solar/Wind Helper
5.16
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.674
205932AD2-116_GEN
Solar/Wind Helper
0.513
233996TM1833_GEN
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.519
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
241955AC1-078 GEN
Solar/Wind Harmer
8.768
241973AD2-163_GEN1
Solar/Wind Harmer
2.315
241974AD2-163_GEN2
Solar/Wind Harmer
2.315
943861AF1-054 GEN
Solar/Wind Harmer
4.468
943851AF1-053 GEN
Solar/Wind Harmer
2.159
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.8
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.877
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.332
274827FISK ;RP
Adder
7.914
274800UNIV PARK;3U
Adder
5.946
274801UNIV PARK;4U
Adder
5.946
972227AH1-698 GEN1
Adder
2.66
274735ELWOOD EC;4P
Adder
16.71
274744AC1-111 GEN8
Adder
5.66
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
270459AD2-067 GEN
Solar/Wind Harmer
10.203
940611AE2-048 GEN
Solar/Wind Harmer
24.928
941391AE2-136 GEN
Solar/Wind Harmer
12.917
270435AC2-044 GEN
Solar/Wind Harmer
2.151
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.319
24729505KEY G4
Adder
6.894
270071AF1-092 GEN
Solar/Wind Harmer
15.924
958711AF2-162 GEN
Solar/Wind Harmer
1.071
25196408WSDLE3
Adder
9.314
25196308WSDLE2
Adder
9.233
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.531
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.48
274728ELWOOD EC;5P
Adder
16.71
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.441
972239AH1-704 GEN
Adder
2.673
961821AG1-024 GEN
Solar/Wind Harmer
10.359
945631AF1-228 GEN
Solar/Wind Harmer
5.44
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.013
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.168
241972AD1-140 GEN
Solar/Wind Harmer
4.999
270340AC2-060 GEN
Solar/Wind Harmer
3.323
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.696
965041AG1-368 GEN
Solar/Wind Harmer
10.674
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.955
964611AG1-324 GEN
Solar/Wind Harmer
4.099
274776LINCOLN ;7U
Adder
8.646
274687WILL CNTY;4U
Adder
28.425
274687WILL CNTY;4U
Adder
28.425
274731ELWOOD EC;2P
Adder
16.71
274733ELWOOD EC;3P
Adder
16.71
274746AC1-111 G10
Adder
5.66
238118U2-030_1
Solar/Wind Helper
0.344
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.644
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
203955AF1-039 C O1
Solar/Wind Helper
0.331
CPLELTFEXP_CPLE->PJM
CLTF
0.578
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.337
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.545
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.966
MECLTFEXP_MEC->PJM
CLTF
15.842
SIGELTFEXP_SIGE->PJM
CLTF
0.503
NYPJM->LTFIMP_NY
CLTF
4.834
LGEELTFEXP_LGEE->PJM
CLTF
6.725
WECLTFEXP_WEC->PJM
CLTF
3.811
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.682
TVALTFEXP_TVA->PJM
CLTF
7.257

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.34 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5094.21
MW Contribution:
12.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.073
23684101S70BUS1
50/50
0.165
253378AE2-206_GEN
Solar/Wind Harmer
3.989
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.274
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274696ROCKY RD ;4P
Adder
11.494
274697ROCKY RD ;3P
Adder
3.05
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
270166AC1-044 GEN3
50/50
7.073
23684201S70BUS2
50/50
0.168
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.576
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.694
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
24318905MLG2
50/50
7.043
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
970155AG2-107 GEN
Solar/Wind Harmer
17.802
971995AH1-542 GEN
Solar/Wind Harmer
12.457
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.239
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
24639705ELKHART HY
Adder
0.16
274812UNIV PK N;8U
Adder
5.12
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
270120AB2-067 GEN2
50/50
7.073
270054AF2-122 C O1
Solar/Wind Harmer
3.974
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
962761AG1-125 GEN
Solar/Wind Harmer
40.825
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.01
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.844
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.445
274802UNIV PARK;5U
Adder
5.948
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
942801AE2-298 GEN
Solar/Wind Harmer
1.617
960971AF2-388 GEN
Solar/Wind Harmer
11.565
25194408D.CRK1
Adder
7.977
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270599AE1-208 GEN
Solar/Wind Harmer
8.55
926881AC1-175 GEN
Solar/Wind Harmer
5.844
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728905RICHG2
Adder
3.948
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274693ROCKY RD ;1P
Adder
11.118
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
23585401KL_K28_T16
Solar/Wind Helper
1.485
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.673
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
946101AF1-275 GEN
Solar/Wind Harmer
1.809
942861AE2-305 GEN
Solar/Wind Harmer
9.054
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
23559101PLEAS2
50/50
6.109
970149AG2-104 GEN
Solar/Wind Harmer
25.209
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
960001AF2-291 GEN
Solar/Wind Harmer
3.243
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.346
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
23559001PLEAS1
50/50
6.109
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.967
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.723
957541AF2-048 GEN
Solar/Wind Harmer
1.714
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.241
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.445
24728705AND G3
Adder
8.182
274826FISK ;BP
Adder
11.164
274730ELWOOD EC;6P
Adder
16.705
238127S14_GEN_2
Solar/Wind Helper
0.83
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.581
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
247620Y3-023
Adder
0.482
24728805RICHG1
Adder
3.948
274695ROCKY RD ;2P
Adder
11.229
235054AD2-180 GEN
Solar/Wind Helper
2.035
235531U2-073 GEN
Solar/Wind Helper
3.323
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
23583801GRNGAP
Solar/Wind Helper
5.632
238126S14_GEN_1
Solar/Wind Helper
0.83
237085AD2-009_GEN
Solar/Wind Helper
1.662
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
270051AF1-062 GEN
50/50
11.788
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
970065AG2-057 GEN
Solar/Wind Harmer
0.922
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
971191AH1-055 GEN
Solar/Wind Harmer
20.024
965021AG1-366 GEN
Solar/Wind Harmer
2.487
270043AE2-236 GEN
Solar/Wind Harmer
5.847
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
972259AH1-714 GEN
Adder
19.435
274729ELWOOD EC;1P
Adder
16.705
238175AF1-290_GEN
Solar/Wind Helper
0.158
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.852
276820AF1-078_GEN
Solar/Wind Harmer
1.772
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.698
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.12
24728505AND G1
Adder
3.912
274676JOLIET 29;8U
Adder
30.072
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.673
205932AD2-116_GEN
Solar/Wind Helper
0.513
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.518
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.805
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.876
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.329
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972227AH1-698 GEN1
Adder
2.659
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
24318805MLG1
50/50
10.069
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
274753CRETE EC ;3U
Adder
8.445
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274803UNIV PARK;6U
Adder
5.948
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.006
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
972239AH1-704 GEN
Adder
2.68
961821AG1-024 GEN
Solar/Wind Harmer
10.365
945631AF1-228 GEN
Solar/Wind Harmer
5.442
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270340AC2-060 GEN
Solar/Wind Harmer
3.324
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.694
965041AG1-368 GEN
Solar/Wind Harmer
10.672
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.954
964611AG1-324 GEN
Solar/Wind Harmer
4.098
274776LINCOLN ;7U
Adder
8.644
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274746AC1-111 G10
Adder
5.658
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
270459AD2-067 GEN
Solar/Wind Harmer
10.209
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.325
24729505KEY G4
Adder
6.892
270071AF1-092 GEN
Solar/Wind Harmer
15.92
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.53
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274728ELWOOD EC;5P
Adder
16.705
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.607
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.625
965051AG1-369 GEN
Solar/Wind Harmer
5.341
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.776
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
23750701CROSSCHOOL
Solar/Wind Helper
1.507
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.34 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5094.21
MW Contribution:
12.46
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
7.043
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
962761AG1-125 GEN
Solar/Wind Harmer
40.825
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.01
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.844
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.445
274802UNIV PARK;5U
Adder
5.948
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270120AB2-067 GEN2
50/50
7.073
270054AF2-122 C O1
Solar/Wind Harmer
3.974
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
960971AF2-388 GEN
Solar/Wind Harmer
11.565
25194408D.CRK1
Adder
7.977
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270599AE1-208 GEN
Solar/Wind Harmer
8.55
926881AC1-175 GEN
Solar/Wind Harmer
5.844
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728905RICHG2
Adder
3.948
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274693ROCKY RD ;1P
Adder
11.118
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
23585401KL_K28_T16
Solar/Wind Helper
1.485
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.673
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
23559101PLEAS2
50/50
6.109
970149AG2-104 GEN
Solar/Wind Harmer
25.209
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
23559001PLEAS1
50/50
6.109
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.967
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.723
957541AF2-048 GEN
Solar/Wind Harmer
1.714
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.241
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.445
24728705AND G3
Adder
8.182
274826FISK ;BP
Adder
11.164
274730ELWOOD EC;6P
Adder
16.705
238127S14_GEN_2
Solar/Wind Helper
0.83
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.581
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
960001AF2-291 GEN
Solar/Wind Harmer
3.243
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.346
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
946101AF1-275 GEN
Solar/Wind Harmer
1.809
942861AE2-305 GEN
Solar/Wind Harmer
9.054
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
247620Y3-023
Adder
0.482
24728805RICHG1
Adder
3.948
274695ROCKY RD ;2P
Adder
11.229
235054AD2-180 GEN
Solar/Wind Helper
2.035
235531U2-073 GEN
Solar/Wind Helper
3.323
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
270166AC1-044 GEN3
50/50
7.073
23684201S70BUS2
50/50
0.168
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.576
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.694
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
23583801GRNGAP
Solar/Wind Helper
5.632
270119AB2-067 GEN1
50/50
7.073
23684101S70BUS1
50/50
0.165
253378AE2-206_GEN
Solar/Wind Harmer
3.989
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.274
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274696ROCKY RD ;4P
Adder
11.494
274697ROCKY RD ;3P
Adder
3.05
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
270051AF1-062 GEN
50/50
11.788
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
970065AG2-057 GEN
Solar/Wind Harmer
0.922
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
971191AH1-055 GEN
Solar/Wind Harmer
20.024
965021AG1-366 GEN
Solar/Wind Harmer
2.487
270043AE2-236 GEN
Solar/Wind Harmer
5.847
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
972259AH1-714 GEN
Adder
19.435
274729ELWOOD EC;1P
Adder
16.705
238175AF1-290_GEN
Solar/Wind Helper
0.158
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
238126S14_GEN_1
Solar/Wind Helper
0.83
237085AD2-009_GEN
Solar/Wind Helper
1.662
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
970155AG2-107 GEN
Solar/Wind Harmer
17.802
971995AH1-542 GEN
Solar/Wind Harmer
12.457
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.239
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
24639705ELKHART HY
Adder
0.16
274812UNIV PK N;8U
Adder
5.12
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.852
276820AF1-078_GEN
Solar/Wind Harmer
1.772
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.698
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.12
24728505AND G1
Adder
3.912
274676JOLIET 29;8U
Adder
30.072
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.673
205932AD2-116_GEN
Solar/Wind Helper
0.513
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.518
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.805
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.876
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.329
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972227AH1-698 GEN1
Adder
2.659
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
24318805MLG1
50/50
10.069
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
274753CRETE EC ;3U
Adder
8.445
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274803UNIV PARK;6U
Adder
5.948
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.006
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
972239AH1-704 GEN
Adder
2.68
961821AG1-024 GEN
Solar/Wind Harmer
10.365
945631AF1-228 GEN
Solar/Wind Harmer
5.442
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270340AC2-060 GEN
Solar/Wind Harmer
3.324
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.694
965041AG1-368 GEN
Solar/Wind Harmer
10.672
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.954
964611AG1-324 GEN
Solar/Wind Harmer
4.098
274776LINCOLN ;7U
Adder
8.644
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274746AC1-111 G10
Adder
5.658
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
270459AD2-067 GEN
Solar/Wind Harmer
10.209
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.325
24729505KEY G4
Adder
6.892
270071AF1-092 GEN
Solar/Wind Harmer
15.92
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.53
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274728ELWOOD EC;5P
Adder
16.705
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.607
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.625
965051AG1-369 GEN
Solar/Wind Harmer
5.341
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.776
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
23750701CROSSCHOOL
Solar/Wind Helper
1.507
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
CPLELTFEXP_CPLE->PJM
CLTF
0.575
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
MECLTFEXP_MEC->PJM
CLTF
15.837
SIGELTFEXP_SIGE->PJM
CLTF
0.503
NYPJM->LTFIMP_NY
CLTF
4.833
LGEELTFEXP_LGEE->PJM
CLTF
6.723
WECLTFEXP_WEC->PJM
CLTF
3.81
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
TVALTFEXP_TVA->PJM
CLTF
7.253

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.83
MW Contribution:
2.89
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.069
972269AH1-719 GEN
Adder
2.573
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965011AG1-365 GEN
Solar/Wind Harmer
7.453
958861AF2-177 GEN
Solar/Wind Harmer
3.191
252510AF1-249 C
Solar/Wind Harmer
0.056
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.589
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
25196008MFTGT1
Adder
1.443
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.68
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
23583801GRNGAP
Solar/Wind Helper
5.626
238126S14_GEN_1
Solar/Wind Helper
0.831
237085AD2-009_GEN
Solar/Wind Helper
1.661
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
970155AG2-107 GEN
Solar/Wind Harmer
21.963
971995AH1-542 GEN
Solar/Wind Harmer
2.894
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
965421AG1-410 GEN
Solar/Wind Harmer
22.47
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.732
970613AG2-401 GEN
Solar/Wind Harmer
5.351
24639705ELKHART HY
Adder
0.16
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
274676JOLIET 29;8U
Adder
31.151
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
18.096
316095T157 G97
Solar/Wind Helper
1.51
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
957471AF2-041 GEN
Solar/Wind Harmer
13.586
972239AH1-704 GEN
Adder
2.678
961821AG1-024 GEN
Solar/Wind Harmer
5.057
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.217
965041AG1-368 GEN
Solar/Wind Harmer
7.438
25196508WSDLE4
Adder
8.944
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.634
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274746AC1-111 G10
Adder
5.652
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.512
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
942861AE2-305 GEN
Solar/Wind Harmer
6.31
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
971073AG2-665 GEN
Solar/Wind Harmer
5.597
25326109MON D
Adder
1.437
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.492
25194508D.CRK3
Adder
1.49
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970885AG2-551 GEN
Solar/Wind Harmer
2.446
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270031AE2-169
Solar/Wind Harmer
4.021
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
24728805RICHG1
Adder
3.944
24699105WLD G1 C
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.638
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
10.234
274695ROCKY RD ;2P
Adder
11.216
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276872AE1-163_GEN1
Solar/Wind Harmer
0
270120AB2-067 GEN2
50/50
7.069
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.867
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.048
960971AF2-388 GEN
Solar/Wind Harmer
4.326
25194408D.CRK1
Adder
7.968
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270599AE1-208 GEN
Solar/Wind Harmer
6.701
926881AC1-175 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728905RICHG2
Adder
3.944
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274808UNIV PK N;4U
Adder
5.092
274674JOLIET 9 ;6U
Adder
15.628
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274693ROCKY RD ;1P
Adder
11.106
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
23585401KL_K28_T16
Solar/Wind Helper
1.489
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.672
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
23559001PLEAS1
50/50
6.097
961921AG1-034 GEN
Solar/Wind Harmer
7.586
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
944531AF1-118 GEN
Solar/Wind Harmer
33.233
25196608WSDLE5
Adder
9.036
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
3.658
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
24728705AND G3
Adder
8.173
274887GEN-1.85
Solar/Wind Harmer
0.185
274826FISK ;BP
Adder
11.151
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
274730ELWOOD EC;6P
Adder
16.687
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
970193AG2-126 GEN
Solar/Wind Harmer
10.468
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.792
270119AB2-067 GEN1
50/50
7.069
25326509SID D
Adder
1.446
970879AG2-548 GEN
Solar/Wind Harmer
1.272
246937BC-WTG2
Solar/Wind Harmer
0.302
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970623AG2-406 GEN
Solar/Wind Harmer
1.351
942221AE2-234 GEN
Solar/Wind Harmer
2.958
970621AG2-405 GEN
Solar/Wind Harmer
1.345
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.126
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
274696ROCKY RD ;4P
Adder
11.481
274697ROCKY RD ;3P
Adder
3.047
962691AG1-118 GEN
Solar/Wind Harmer
21.036
942111AE2-223 GEN
Solar/Wind Harmer
2.266
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.895
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
270051AF1-062 GEN
50/50
11.777
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
252519AF1-045_GEN
Solar/Wind Harmer
3.844
25194608D.CRK4
Adder
1.732
946031AF1-268 GEN
Solar/Wind Harmer
6.95
970289AG2-191 GEN
Solar/Wind Harmer
0.8
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
5.114
24728505AND G1
Adder
3.908
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274676JOLIET 29;8U
Adder
30.039
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
274682WAUKEGAN ;7U
Adder
18.096
964991AG1-363 GEN
Solar/Wind Helper
5.155
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.672
205932AD2-116_GEN
Solar/Wind Helper
0.512
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.868
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.516
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
959091AF2-200 GEN
Solar/Wind Harmer
9.057
235054AD2-180 GEN
Solar/Wind Helper
2.04
235531U2-073 GEN
Solar/Wind Helper
3.327
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.118
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
316045AC1-158 PL2
Solar/Wind Helper
4.17
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
23559101PLEAS2
50/50
6.097
970149AG2-104 GEN
Solar/Wind Harmer
18.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
971917AH1-482 GEN
Solar/Wind Harmer
9.365
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
276882AE2-255 GEN
Solar/Wind Harmer
0.818
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.274
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
238127S14_GEN_2
Solar/Wind Helper
0.831
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.303
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.58
202652Y1-033 WT C
Solar/Wind Helper
0.5
962761AG1-125 GEN
Solar/Wind Harmer
34.394
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.807
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.095
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.436
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.941
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
939401AE1-172 GEN
Solar/Wind Harmer
5.275
962781AG1-127 GEN
Solar/Wind Harmer
6.668
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.441
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.559
270377AD1-106 GEN
Solar/Wind Harmer
2.842
965051AG1-369 GEN
Solar/Wind Harmer
3.723
971985AH1-537 GEN
Solar/Wind Harmer
2.196
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
247536S-71 GEN
Solar/Wind Harmer
0.293
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
274775LINCOLN ;6U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
972228AH1-698 GEN2
Adder
3.772
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
971411AH1-196 GEN
Solar/Wind Harmer
10.47
23750701CROSSCHOOL
Solar/Wind Helper
1.509
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
971191AH1-055 GEN
Solar/Wind Harmer
19.175
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270043AE2-236 GEN
Solar/Wind Harmer
4.754
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
945111AF1-176 GEN
Solar/Wind Harmer
5.891
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
972167AH1-666 GEN
Solar/Wind Harmer
5.69
972259AH1-714 GEN
Adder
19.413
274729ELWOOD EC;1P
Adder
16.687
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970571AG2-364 GEN
Solar/Wind Harmer
13.944
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
233944AB2-135 GEN
Solar/Wind Helper
0.594
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.843
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
270246TR4_N_V150
Solar/Wind Harmer
0.048
247621Y3-024
Adder
0.253
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
965681AG1-436 GEN
Solar/Wind Harmer
9.052
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.758
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.51
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.344
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
24318805MLG1
50/50
10.065
270475AD2-096_GEN
50/50
7.114
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
970191AG2-125 GEN
Solar/Wind Harmer
1.937
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.436
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274803UNIV PARK;6U
Adder
5.941
276843GEN-1.7
Solar/Wind Harmer
0.23
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.012
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270007AE1-245 C
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
270071AF1-092 GEN
Solar/Wind Harmer
14.177
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
270543AE2-219 C
Solar/Wind Harmer
5.137
971771AH1-392 GEN
Solar/Wind Harmer
7.271
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
971549AH1-272 GEN
Solar/Wind Harmer
14.794
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.687
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.062
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
209027LOR2_Q27
Solar/Wind Helper
1.031
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
970179AG2-119 GEN
Solar/Wind Harmer
6.854
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.27
963791AG1-232 GEN
Solar/Wind Harmer
9.987
970289AG2-191 GEN
Solar/Wind Harmer
1.382
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972227AH1-698 GEN1
Adder
2.656
274735ELWOOD EC;4P
Adder
16.687
274744AC1-111 GEN8
Adder
5.652
970169AG2-114 GEN
Solar/Wind Harmer
7.011
959341AF2-225 GEN
Solar/Wind Harmer
7.32
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.057
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
CPLELTFEXP_CPLE->PJM
CLTF
0.571
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
MECLTFEXP_MEC->PJM
CLTF
15.818
SIGELTFEXP_SIGE->PJM
CLTF
0.502
NYPJM->LTFIMP_NY
CLTF
4.827
LGEELTFEXP_LGEE->PJM
CLTF
6.715
WECLTFEXP_WEC->PJM
CLTF
3.806
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
TVALTFEXP_TVA->PJM
CLTF
7.243

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5005.84
MW Contribution:
12.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
24721905FLATG4
Adder
23.444
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
24695305TIMB G C
Solar/Wind Harmer
3.661
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
247643Z2-116 C
Solar/Wind Harmer
0.074
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25194608D.CRK4
Adder
1.747
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
274811UNIV PK N;7U
Adder
5.194
274676JOLIET 29;8U
Adder
30.477
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238110AE1-109 GEN3
Solar/Wind Helper
0.122
235063AE1-101 C2
Solar/Wind Helper
1.786
316447AC1-158 HLD
Solar/Wind Helper
3.193
205932AD2-116_GEN
Solar/Wind Helper
0.521
232426Y1-080 FULL
Solar/Wind Helper
0.04
233996TM1833_GEN
Solar/Wind Helper
0.21
316192AB2-158 GEN
Solar/Wind Helper
1.618
270051AF1-062 GEN
50/50
11.971
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
970065AG2-057 GEN
Solar/Wind Harmer
0.972
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
970155AG2-107 GEN
Solar/Wind Harmer
17.82
972239AH1-704 GEN
50/50
3.095
961821AG1-024 GEN
Solar/Wind Harmer
10.588
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270432AC2-029 GEN
Solar/Wind Harmer
8.117
253338AC1-165 GEN
Solar/Wind Harmer
1.249
23559001PLEAS1
50/50
5.445
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
958581AF2-149 GEN
Solar/Wind Harmer
4.955
958091AF2-103 GEN
Solar/Wind Harmer
0.178
957541AF2-048 GEN
Solar/Wind Harmer
1.72
944531AF1-118 GEN
Solar/Wind Harmer
37.819
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971347AH1-153 GEN
Solar/Wind Harmer
5.342
25196608WSDLE5
Adder
9.116
274752CRETE EC ;2U
Adder
8.571
274826FISK ;BP
Adder
11.319
274730ELWOOD EC;6P
Adder
16.929
238152AF2-075_GEN
Solar/Wind Helper
0.794
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
316044AC1-158 PL1
Solar/Wind Helper
1.451
208835TUHI V3-051
Solar/Wind Helper
0.022
3147666LOUISA
Solar/Wind Helper
0.962
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.573
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270377AD1-106 GEN
Solar/Wind Harmer
5.917
270291AC1-194 GEN
Solar/Wind Harmer
5.669
965051AG1-369 GEN
Solar/Wind Harmer
5.479
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
970149AG2-104 GEN
Solar/Wind Harmer
25.235
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
971073AG2-665 GEN
Solar/Wind Harmer
1.284
270297AD1-101 GEN
Solar/Wind Harmer
2.226
270258AD1-119 GEN
Solar/Wind Harmer
2.219
960001AF2-291 GEN
Solar/Wind Harmer
3.236
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
23920202STRYCT
Adder
1.44
23546401DTGZ2-030
Solar/Wind Helper
0.1
237038AE2-054 C
Solar/Wind Helper
0.294
3132273ORANGE
Solar/Wind Helper
0.049
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
232417X3-008 C
Solar/Wind Helper
0.238
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.151
24318805MLG1
50/50
10
270518AE2-148 GEN
Solar/Wind Harmer
13.997
971199AH1-059 GEN
Solar/Wind Harmer
2.432
253325AC1-069 GEN
Solar/Wind Harmer
1.205
961961AG1-039 GEN
Solar/Wind Harmer
3.18
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
274753CRETE EC ;3U
Adder
8.571
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274803UNIV PARK;6U
Adder
6.031
972038AH1-567 GEN2
Adder
0.377
238108AE1-109 GEN1
Solar/Wind Helper
0.122
237001AB1-127_GEN
Solar/Wind Helper
0.476
23562501BACKB
Solar/Wind Helper
1
233918AB1-142 GEN
Solar/Wind Helper
0.514
228729W2-030 C
Solar/Wind Helper
0.112
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
971995AH1-542 GEN
Solar/Wind Harmer
12.942
965421AG1-410 GEN
Solar/Wind Harmer
33.164
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
24639705ELKHART HY
Adder
0.164
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
25194608D.CRK4
Adder
1.747
23906502RICHG2&3
Adder
1.268
274812UNIV PK N;8U
Adder
5.194
274676JOLIET 29;8U
Adder
31.606
316095T157 G97
Solar/Wind Helper
1.71
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
238120AE2-309 GEN
Solar/Wind Helper
0.557
23777801MSM_W1-116
Solar/Wind Helper
0.123
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
232422X3-066 FULL
Solar/Wind Helper
0.117
233964AF2-378 GEN
Solar/Wind Helper
0.043
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
966881AG1-559 GEN
Solar/Wind Helper
0.313
205941AD2-115 GEN
Solar/Wind Helper
0.499
24318905MLG2
50/50
7.451
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
274775LINCOLN ;6U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
972228AH1-698 GEN2
Adder
3.828
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
23750701CROSSCHOOL
Solar/Wind Helper
1.591
205943AE1-185 GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
270120AB2-067 GEN2
50/50
7.05
270054AF2-122 C O1
Solar/Wind Harmer
4.054
938701AE1-092 GEN
Solar/Wind Harmer
24.428
270462AD2-086
Solar/Wind Harmer
8.12
253415AE1-040 GEN
Solar/Wind Harmer
1.252
942801AE2-298 GEN
Solar/Wind Harmer
1.666
270247TR4_N_V136
Solar/Wind Harmer
0.933
253349AC2-067 GEN
Solar/Wind Harmer
2.225
944231AF1-091 GEN
Solar/Wind Harmer
19.433
960971AF2-388 GEN
Solar/Wind Harmer
11.731
970349AG2-230 GEN
Solar/Wind Harmer
16.027
970883AG2-550 GEN
Solar/Wind Harmer
10.668
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
24728905RICHG2
Adder
3.989
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
238148AE2-230_GEN2
Solar/Wind Helper
0.556
23585401KL_K28_T16
Solar/Wind Helper
1.534
238117U2-030
Solar/Wind Helper
0.357
235062AE1-101 C1
Solar/Wind Helper
1.786
237006AB1-125 GEN
Solar/Wind Helper
0.132
223401AF1-299 GEN
Solar/Wind Helper
0.389
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
246938BC-WTG3
Solar/Wind Harmer
4.404
970879AG2-548 GEN
Solar/Wind Harmer
8.835
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
270043AE2-236 GEN
Solar/Wind Harmer
5.961
971191AH1-055 GEN
Solar/Wind Harmer
20.005
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
270367AC2-061_GEN
Solar/Wind Harmer
3.375
25196008MFTGT1
Adder
1.409
274724RIVER EC ;11
Adder
18.401
274772LINCOLN ;3U
Adder
8.764
972259AH1-714 GEN
Adder
19.698
274729ELWOOD EC;1P
Adder
16.929
238175AF1-290_GEN
Solar/Wind Helper
0.173
316415AF1-147_GEN2
Solar/Wind Helper
0.984
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
233944AB2-135 GEN
Solar/Wind Helper
0.603
232408W1-005 C
Solar/Wind Helper
0.518
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
270119AB2-067 GEN1
50/50
7.05
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
246937BC-WTG2
Solar/Wind Harmer
4.329
970879AG2-548 GEN
Solar/Wind Harmer
1.284
247607V1-011 GEN
Solar/Wind Harmer
4.348
247522W1-056 GEN
Solar/Wind Harmer
2.469
942221AE2-234 GEN
Solar/Wind Harmer
3.759
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
237061AD1-155 GEN
Solar/Wind Helper
1.974
235020AA1-095 C
Solar/Wind Helper
0.058
238221AF1-254 C O1
Solar/Wind Helper
0.297
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
223402AF1-300 C
Solar/Wind Helper
0.389
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
233946AB2-136 GEN
Solar/Wind Helper
0.581
232410W1-006 C
Solar/Wind Helper
0.518
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
270166AC1-044 GEN3
50/50
7.05
972269AH1-719 GEN
Adder
2.693
270485AE1-090_GEN
Solar/Wind Harmer
0.706
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965011AG1-365 GEN
Solar/Wind Harmer
10.939
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
958861AF2-177 GEN
Solar/Wind Harmer
11.712
945371AF1-202 GEN
Solar/Wind Harmer
7.453
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
232424Y1-079 C
Solar/Wind Helper
0.119
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
966001AG1-469 GEN
Solar/Wind Helper
0.256
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.293
20675428EAM_W2-061
Solar/Wind Helper
0.016
962761AG1-125 GEN
Solar/Wind Harmer
40.867
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270317AD1-130_GEN
Solar/Wind Harmer
3.738
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
211065PSPA IPP
Solar/Wind Helper
0.151
946101AF1-275 GEN
Solar/Wind Harmer
1.838
942861AE2-305 GEN
Solar/Wind Harmer
9.201
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
25326109MON D
Adder
1.457
971073AG2-665 GEN
Solar/Wind Harmer
8.835
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944541AF1-119 GEN
Solar/Wind Harmer
4.494
247620Y3-023
Adder
0.492
25183208HLCRTG
Solar/Wind Harmer
6.454
970885AG2-551 GEN
Solar/Wind Harmer
2.481
270201AC2-176 GEN
Solar/Wind Harmer
5.48
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
238149AF1-291A_GEN
Solar/Wind Helper
0.159
253383AE2-342_GEN
Solar/Wind Harmer
1.057
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
247621Y3-024
Adder
0.257
970935AG2-582 GEN
Adder
238.716
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
237080AD1-060 GEN
Solar/Wind Helper
0.369
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25196808ZIMRHP
Adder
79.955
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
23583801GRNGAP
Solar/Wind Helper
6.383
238126S14_GEN_1
Solar/Wind Helper
0.87
237085AD2-009_GEN
Solar/Wind Helper
1.776
3141196NOKESVL
Solar/Wind Helper
1.144
226910AB2-157 C
Solar/Wind Helper
0.016
233933AB2-153 GEN
Solar/Wind Helper
0.238
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.777
960841AF2-375 GEN
Solar/Wind Harmer
0.624
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
316006AB2-029 C
Solar/Wind Helper
0.131
316045AC1-158 PL2
Solar/Wind Helper
4.643
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
219912AD2-042 GEN
Solar/Wind Helper
0.152
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
20674328GAR_V4-001
Solar/Wind Helper
0.023
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270340AC2-060 GEN
Solar/Wind Harmer
3.354
270191TR4_S_V150
Solar/Wind Harmer
3.29
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
270499AE1-146 GEN
Solar/Wind Harmer
2.679
964611AG1-324 GEN
Solar/Wind Harmer
4.154
25196508WSDLE4
Adder
9.023
274776LINCOLN ;7U
Adder
8.764
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
23779801AA1-109
Solar/Wind Helper
0.208
226929AD2-058 GEN
Solar/Wind Helper
0.108
316164AC1-076 GEN
Solar/Wind Helper
1.232
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
205956AE1-196_GEN
Solar/Wind Helper
0.521
233901CHERRYDALE C
Solar/Wind Helper
0.238
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
270302AB2-170 GEN
Solar/Wind Harmer
9.776
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253343AC1-166 GEN
Solar/Wind Harmer
1.249
957201AF2-014 GEN
Solar/Wind Harmer
5.019
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
25306009OHH W.
Adder
3.158
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
944161AF1-084 GEN
Solar/Wind Harmer
2.352
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972227AH1-698 GEN1
Adder
2.695
274735ELWOOD EC;4P
Adder
16.929
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
315651AD1-115 GEN
Solar/Wind Helper
0.883
959381AF2-229 GEN
Solar/Wind Helper
0.368
232432Z2-076 GEN
Solar/Wind Helper
0.068
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
25326309TAIT D
Adder
1.207
270216AD2-079_GEN
Solar/Wind Harmer
0.645
944031AF1-071 GEN
Solar/Wind Harmer
1.069
274754CRETE EC ;4U
Adder
8.571
274802UNIV PARK;5U
Adder
6.031
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
235067AD1-061 GEN
Solar/Wind Helper
0.481
237002AB1-128_GEN
Solar/Wind Helper
0.477
208835TUHI V3-051
Solar/Wind Helper
0.022
3147666LOUISA
Solar/Wind Helper
0.553
233950AC2-186 GEN
Solar/Wind Helper
0.119
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.313
217169METRODIV C
Solar/Wind Helper
0.004
270459AD2-067 GEN
Solar/Wind Harmer
10.428
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
971567AH1-282 GEN
Solar/Wind Harmer
5.635
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
958711AF2-162 GEN
Solar/Wind Harmer
1.086
270543AE2-219 C
Solar/Wind Harmer
10.668
971771AH1-392 GEN
Solar/Wind Harmer
9.58
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274728ELWOOD EC;5P
Adder
16.929
3141426STAFORD
Solar/Wind Helper
0.058
20390526W1-045 C
Solar/Wind Helper
0.361
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.234
219258KINSLEYDEP C
Solar/Wind Helper
0.078
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.084
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
228728W1-130C
Solar/Wind Helper
0.055
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
MECLTFEXP_MEC->PJM
CLTF
15.924
SIGELTFEXP_SIGE->PJM
CLTF
0.504
NYPJM->LTFIMP_NY
CLTF
4.574
LGEELTFEXP_LGEE->PJM
CLTF
6.731
WECLTFEXP_WEC->PJM
CLTF
3.853
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4761.71
MW Contribution:
2.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.887
25326509SID D
Adder
1.398
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
22.814
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
942861AE2-305 GEN
Solar/Wind Harmer
6.105
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
970149AG2-104 GEN
Solar/Wind Harmer
17.929
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
971917AH1-482 GEN
Solar/Wind Harmer
9.046
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
962761AG1-125 GEN
Solar/Wind Harmer
33.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.78
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.818
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.15
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
939401AE1-172 GEN
Solar/Wind Harmer
5.095
962781AG1-127 GEN
Solar/Wind Harmer
6.441
235067AD1-061 GEN
Solar/Wind Helper
0.432
237002AB1-128_GEN
Solar/Wind Helper
0.43
208835TUHI V3-051
Solar/Wind Helper
0.021
233950AC2-186 GEN
Solar/Wind Helper
0.113
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
207454AA2-184 E
Solar/Wind Helper
0.301
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971985AH1-537 GEN
Solar/Wind Harmer
2.117
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.753
970935AG2-582 GEN
Adder
241.832
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.046
247621Y3-024
Adder
0.245
971613AH1-306 GEN
Solar/Wind Harmer
3.374
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
24318805MLG1
50/50
9.823
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
970191AG2-125 GEN
Solar/Wind Harmer
1.872
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.15
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
276843GEN-1.7
Solar/Wind Harmer
0.222
972038AH1-567 GEN2
Adder
0.359
238108AE1-109 GEN1
Solar/Wind Helper
0.107
237001AB1-127_GEN
Solar/Wind Helper
0.428
23562501BACKB
Solar/Wind Helper
0.845
233918AB1-142 GEN
Solar/Wind Helper
0.488
228729W2-030 C
Solar/Wind Helper
0.107
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
972239AH1-704 GEN
50/50
2.774
961821AG1-024 GEN
Solar/Wind Harmer
4.899
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.044
965041AG1-368 GEN
Solar/Wind Harmer
7.193
25196508WSDLE4
Adder
8.634
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.341
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
23750501ELLIOTTS
Solar/Wind Helper
0.573
205956AE1-196_GEN
Solar/Wind Helper
0.494
233901CHERRYDALE C
Solar/Wind Helper
0.226
20715028HAN_X4-015
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
20720628TIN_W1-124
Solar/Wind Helper
0.184
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270435AC2-044 GEN
Solar/Wind Harmer
0.918
971567AH1-282 GEN
Solar/Wind Harmer
5.517
270007AE1-245 C
Solar/Wind Harmer
0
24729505KEY G4
Adder
6.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
270543AE2-219 C
Solar/Wind Harmer
4.962
971771AH1-392 GEN
Solar/Wind Harmer
7.027
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
971549AH1-272 GEN
Solar/Wind Harmer
14.305
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.119
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
20390526W1-045 C
Solar/Wind Helper
0.339
3141426STAFORD
Solar/Wind Helper
0.051
270166AC1-044 GEN3
50/50
6.887
972269AH1-719 GEN
Adder
2.495
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965011AG1-365 GEN
Solar/Wind Harmer
7.206
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252510AF1-249 C
Solar/Wind Harmer
0.054
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
25196008MFTGT1
Adder
1.393
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.554
970569AG2-363 GEN
Solar/Wind Harmer
20.202
939741AE1-205 GEN
Solar/Wind Harmer
9.427
23583801GRNGAP
Solar/Wind Helper
5.433
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.596
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.226
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.023
20716928W4-060COL
Solar/Wind Helper
0.05
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
970179AG2-119 GEN
Solar/Wind Harmer
6.643
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.261
963791AG1-232 GEN
Solar/Wind Harmer
9.652
970289AG2-191 GEN
Solar/Wind Harmer
1.334
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972227AH1-698 GEN1
Adder
2.566
274735ELWOOD EC;4P
Adder
16.119
970155AG2-107 GEN
Solar/Wind Harmer
21.201
971995AH1-542 GEN
Solar/Wind Harmer
2.804
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965651AG1-433 GEN
Solar/Wind Harmer
2.09
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.672
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.941
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
274676JOLIET 29;8U
Adder
30.093
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.459
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.111
227287AC2-120 GEN
Solar/Wind Helper
0.337
232422X3-066 FULL
Solar/Wind Helper
0.111
233964AF2-378 GEN
Solar/Wind Helper
0.041
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.481
957471AF2-041 GEN
Solar/Wind Harmer
13.123
965681AG1-436 GEN
Solar/Wind Harmer
8.747
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.732
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
237080AD1-060 GEN
Solar/Wind Helper
0.332
219904AC1-010 C
Solar/Wind Helper
0.059
219906AC1-017 C
Solar/Wind Helper
0.041
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
971029AG2-637 GEN
Solar/Wind Harmer
10.639
247536S-71 GEN
Solar/Wind Harmer
0.283
270120AB2-067 GEN2
50/50
6.887
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.459
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.046
960971AF2-388 GEN
Solar/Wind Harmer
4.179
25194408D.CRK1
Adder
7.692
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270599AE1-208 GEN
Solar/Wind Harmer
6.473
944231AF1-091 GEN
Solar/Wind Harmer
16.273
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.809
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.919
966841AG1-555 GEN
Solar/Wind Harmer
0.78
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238117U2-030
Solar/Wind Helper
0.315
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
232424Y1-079 C
Solar/Wind Helper
0.113
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
316450AC1-158 RIC
Solar/Wind Helper
0.336
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.282
970329AG2-216 GEN
Solar/Wind Harmer
3.232
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
25194508D.CRK3
Adder
1.438
970885AG2-551 GEN
Solar/Wind Harmer
2.363
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
270031AE2-169
Solar/Wind Harmer
3.884
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.465
24728805RICHG1
Adder
3.809
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
9.886
958491AF2-143 GEN
Solar/Wind Harmer
10.177
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
316006AB2-029 C
Solar/Wind Helper
0.114
232436AB1-176 C
Solar/Wind Helper
0.043
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
316045AC1-158 PL2
Solar/Wind Helper
4.03
219912AD2-042 GEN
Solar/Wind Helper
0.146
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
274775LINCOLN ;6U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
972228AH1-698 GEN2
Adder
3.644
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.63
971411AH1-196 GEN
Solar/Wind Harmer
10.113
23750701CROSSCHOOL
Solar/Wind Helper
1.401
205943AE1-185 GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
228728W1-130C
Solar/Wind Helper
0.052
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.026
219620RIDERU C
Solar/Wind Helper
0.001
971171AH1-044 GEN
Solar/Wind Harmer
8.748
23559001PLEAS1
50/50
5.39
961921AG1-034 GEN
Solar/Wind Harmer
7.349
942051AE2-217 GEN
Solar/Wind Harmer
14.139
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
944531AF1-118 GEN
Solar/Wind Harmer
32.112
25196608WSDLE5
Adder
8.723
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
971347AH1-153 GEN
Solar/Wind Harmer
3.535
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274887GEN-1.85
Solar/Wind Harmer
0.178
274826FISK ;BP
Adder
10.773
24728705AND G3
Adder
7.891
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274730ELWOOD EC;6P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
970193AG2-126 GEN
Solar/Wind Harmer
10.106
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
208835TUHI V3-051
Solar/Wind Helper
0.021
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
316044AC1-158 PL1
Solar/Wind Helper
1.259
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
970879AG2-548 GEN
Solar/Wind Harmer
1.228
246937BC-WTG2
Solar/Wind Harmer
0.292
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
24387305FR-4G C
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
962691AG1-118 GEN
Solar/Wind Harmer
20.32
942111AE2-223 GEN
Solar/Wind Harmer
2.188
235020AA1-095 C
Solar/Wind Helper
0.051
237061AD1-155 GEN
Solar/Wind Helper
1.703
238221AF1-254 C O1
Solar/Wind Helper
0.267
316411AF1-147_GEN1
Solar/Wind Helper
0.865
223402AF1-300 C
Solar/Wind Helper
0.357
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
233946AB2-136 GEN
Solar/Wind Helper
0.553
232410W1-006 C
Solar/Wind Helper
0.493
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
970169AG2-114 GEN
Solar/Wind Harmer
6.772
959341AF2-225 GEN
Solar/Wind Harmer
7.07
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
959381AF2-229 GEN
Solar/Wind Helper
0.346
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230407AD2-065 C
Solar/Wind Helper
0.039
20720728JCB_W1-129
Solar/Wind Helper
0.055
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.086
237038AE2-054 C
Solar/Wind Helper
0.264
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
232417X3-008 C
Solar/Wind Helper
0.226
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
24695305TIMB G C
Solar/Wind Harmer
0.609
252519AF1-045_GEN
Solar/Wind Harmer
3.711
25194608D.CRK4
Adder
1.672
946031AF1-268 GEN
Solar/Wind Harmer
6.713
970289AG2-191 GEN
Solar/Wind Harmer
0.773
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
4.941
276806AD2-047 C O1
Solar/Wind Harmer
3.89
24728505AND G1
Adder
3.773
274676JOLIET 29;8U
Adder
29.018
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
964991AG1-363 GEN
Solar/Wind Helper
4.979
238110AE1-109 GEN3
Solar/Wind Helper
0.107
235063AE1-101 C2
Solar/Wind Helper
1.608
205932AD2-116_GEN
Solar/Wind Helper
0.494
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
316447AC1-158 HLD
Solar/Wind Helper
2.771
219766PARADISE C
Solar/Wind Helper
0.053
203975AE1-071-GEN
Solar/Wind Helper
2.421
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
959091AF2-200 GEN
Solar/Wind Harmer
8.748
270051AF1-062 GEN
50/50
11.411
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
270043AE2-236 GEN
Solar/Wind Harmer
4.595
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
270505AE1-170 C O1
Solar/Wind Harmer
7.374
25196008MFTGT1
Adder
1.349
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
972167AH1-666 GEN
Solar/Wind Harmer
5.491
972259AH1-714 GEN
Adder
18.754
274729ELWOOD EC;1P
Adder
16.119
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970571AG2-364 GEN
Solar/Wind Harmer
13.468
238175AF1-290_GEN
Solar/Wind Helper
0.152
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
205916AD1-020 GEN
Solar/Wind Helper
1.664
233944AB2-135 GEN
Solar/Wind Helper
0.573
232408W1-005 C
Solar/Wind Helper
0.493
219907AC1-030 C
Solar/Wind Helper
0.033
20716028EGP_W2-019
Solar/Wind Helper
0.018
233940AF2-379 C
Solar/Wind Helper
0.06
230434AG1-499 GEN
Solar/Wind Helper
0.223
219258KINSLEYDEP C
Solar/Wind Helper
0.075
CPLELTFEXP_CPLE->PJM
CLTF
0.539
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
MECLTFEXP_MEC->PJM
CLTF
15.273
SIGELTFEXP_SIGE->PJM
CLTF
0.485
NYPJM->LTFIMP_NY
CLTF
4.644
LGEELTFEXP_LGEE->PJM
CLTF
6.478
WECLTFEXP_WEC->PJM
CLTF
3.676
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
TVALTFEXP_TVA->PJM
CLTF
6.984
CONTINGENCY 'AEP_P4_#8975_05KAMMER 765_MM2_SRT-A'
 OPEN BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT7A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT10A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
243458 to 246752 ckt 1
242925 to 235117 ckt 1

Winter Peak Analysis

The New Service Request AH1-542 was evaluated as a 110.0 MW (22.0 MW Capacity) injection in the ATSI area.

AH1-542 was evaluated as part of a plant. The plant consists of AH1-542. The total Energy output of the plant was evaluated at its maximum seasonal capability of 110.0 MW (110.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-542 was evaluated as a 110.0 MW injection

AH1-542 was evaluated as part of a plant. The plant consists of AH1-542. The total Energy output of the plant was evaluated at its maximum seasonal capability of 110.0 MW (148.08 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC101.22 %1409.0B1426.24
13.2
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC100.94 %1409.0B1422.27
13.16
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC100.89 %1409.0B1421.52
13.16
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC100.44 %1409.0B1415.24
13.1
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC100.44 %1409.0B1415.21
13.1

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.22 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1426.24
MW Contribution:
13.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
2.809
270471AD2-092_GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
2.169
270466AD2-091
50/50
5.194
270036AE2-216 BAT
50/50
5.713
270475AD2-096_GEN
50/50
7.576
270051AF1-062 GEN
50/50
Charging
37.736
270578AF1-285 GEN2
Solar/Wind Harmer
1.116
270391AF1-285 GEN3
Solar/Wind Harmer
1.116
270462AD2-086
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
13.517
962761AG1-125 GEN
Solar/Wind Harmer
9.839
962771AG1-126 GEN
Solar/Wind Harmer
9.839
970065AG2-057 GEN
Solar/Wind Harmer
0.439
970149AG2-104 GEN
Solar/Wind Harmer
7.737
970153AG2-106 GEN
Solar/Wind Harmer
6.708
970155AG2-107 GEN
Solar/Wind Harmer
6.708
970179AG2-119 GEN
Solar/Wind Harmer
4.135
971201AH1-060 GEN
Solar/Wind Harmer
0.878
971995AH1-542 GEN
Solar/Wind Harmer
5.582
971995AH1-542 GEN
Solar/Wind Harmer
7.612
270223U2-072_GEN1
Solar/Wind Harmer
2.396
270224U2-072_GEN2
Solar/Wind Harmer
2.396
270227U2-072_GEN3
Solar/Wind Harmer
2.396
270228U2-072_GEN4
Solar/Wind Harmer
2.396
270231U2-072_GEN5
Solar/Wind Harmer
2.396
942051AE2-217 GEN
Solar/Wind Harmer
8.477
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.719
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.423
NYPJM->LTFIMP_NY
CLTF
1.572
LGEELTFEXP_LGEE->PJM
CLTF
2.031
WECLTFEXP_WEC->PJM
CLTF
1.43
CPLELTFEXP_CPLE->PJM
CLTF
0.006
TVALTFEXP_TVA->PJM
CLTF
1.907
MECLTFEXP_MEC->PJM
CLTF
5.61
LAGNLTFEXP_LAGN->PJM
CLTF
4.28
SIGELTFEXP_SIGE->PJM
CLTF
0.16
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
12.34
AG2-052LTFEXP_AG2-052->PJM
LTF
0.089
AH1-155LTFEXP_AH1-155->PJM
LTF
0.133

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.94 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1422.27
MW Contribution:
13.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
2.803
270471AD2-092_GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
2.156
270466AD2-091
50/50
5.182
270036AE2-216 BAT
50/50
5.7
270475AD2-096_GEN
50/50
7.558
270051AF1-062 GEN
50/50
Charging
37.614
270578AF1-285 GEN2
Solar/Wind Harmer
1.113
270391AF1-285 GEN3
Solar/Wind Harmer
1.113
270462AD2-086
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
13.482
962761AG1-125 GEN
Solar/Wind Harmer
9.816
962771AG1-126 GEN
Solar/Wind Harmer
9.816
970065AG2-057 GEN
Solar/Wind Harmer
0.438
970149AG2-104 GEN
Solar/Wind Harmer
7.719
970153AG2-106 GEN
Solar/Wind Harmer
6.693
970155AG2-107 GEN
Solar/Wind Harmer
6.693
970179AG2-119 GEN
Solar/Wind Harmer
4.126
971201AH1-060 GEN
Solar/Wind Harmer
0.876
971995AH1-542 GEN
Solar/Wind Harmer
5.569
971995AH1-542 GEN
Solar/Wind Harmer
7.594
270223U2-072_GEN1
Solar/Wind Harmer
2.391
270224U2-072_GEN2
Solar/Wind Harmer
2.391
270227U2-072_GEN3
Solar/Wind Harmer
2.391
270228U2-072_GEN4
Solar/Wind Harmer
2.391
270231U2-072_GEN5
Solar/Wind Harmer
2.391
942051AE2-217 GEN
Solar/Wind Harmer
8.454
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.613
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.991
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.835
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.421
NYPJM->LTFIMP_NY
CLTF
1.568
LGEELTFEXP_LGEE->PJM
CLTF
2.027
WECLTFEXP_WEC->PJM
CLTF
1.427
CPLELTFEXP_CPLE->PJM
CLTF
0.007
TVALTFEXP_TVA->PJM
CLTF
1.904
MECLTFEXP_MEC->PJM
CLTF
5.598
LAGNLTFEXP_LAGN->PJM
CLTF
4.272
SIGELTFEXP_SIGE->PJM
CLTF
0.159
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
12.308
AG2-052LTFEXP_AG2-052->PJM
LTF
0.089
AH1-155LTFEXP_AH1-155->PJM
LTF
0.133

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.89 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1421.52
MW Contribution:
13.16
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
2.802
270471AD2-092_GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
2.152
270466AD2-091
50/50
5.179
270036AE2-216 BAT
50/50
5.697
270475AD2-096_GEN
50/50
7.554
270051AF1-062 GEN
50/50
Charging
37.586
270578AF1-285 GEN2
Solar/Wind Harmer
1.112
270391AF1-285 GEN3
Solar/Wind Harmer
1.112
270462AD2-086
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
13.474
962761AG1-125 GEN
Solar/Wind Harmer
9.811
962771AG1-126 GEN
Solar/Wind Harmer
9.811
970065AG2-057 GEN
Solar/Wind Harmer
0.438
970149AG2-104 GEN
Solar/Wind Harmer
7.715
970153AG2-106 GEN
Solar/Wind Harmer
6.689
970155AG2-107 GEN
Solar/Wind Harmer
6.689
970179AG2-119 GEN
Solar/Wind Harmer
4.123
971201AH1-060 GEN
Solar/Wind Harmer
0.876
971995AH1-542 GEN
Solar/Wind Harmer
5.566
971995AH1-542 GEN
Solar/Wind Harmer
7.59
270223U2-072_GEN1
Solar/Wind Harmer
2.39
270224U2-072_GEN2
Solar/Wind Harmer
2.39
270227U2-072_GEN3
Solar/Wind Harmer
2.39
270228U2-072_GEN4
Solar/Wind Harmer
2.39
270231U2-072_GEN5
Solar/Wind Harmer
2.39
942051AE2-217 GEN
Solar/Wind Harmer
8.448
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.588
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.975
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.831
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.421
NYPJM->LTFIMP_NY
CLTF
1.568
LGEELTFEXP_LGEE->PJM
CLTF
2.026
WECLTFEXP_WEC->PJM
CLTF
1.426
CPLELTFEXP_CPLE->PJM
CLTF
0.007
TVALTFEXP_TVA->PJM
CLTF
1.903
MECLTFEXP_MEC->PJM
CLTF
5.595
LAGNLTFEXP_LAGN->PJM
CLTF
4.27
SIGELTFEXP_SIGE->PJM
CLTF
0.159
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
12.3
AG2-052LTFEXP_AG2-052->PJM
LTF
0.089
AH1-155LTFEXP_AH1-155->PJM
LTF
0.133

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.44 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1415.24
MW Contribution:
13.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
2.79
270471AD2-092_GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
2.127
270466AD2-091
50/50
5.156
270036AE2-216 BAT
50/50
5.672
270475AD2-096_GEN
50/50
7.52
270051AF1-062 GEN
50/50
Charging
37.356
270578AF1-285 GEN2
Solar/Wind Harmer
1.107
270391AF1-285 GEN3
Solar/Wind Harmer
1.107
270462AD2-086
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
13.409
962761AG1-125 GEN
Solar/Wind Harmer
9.768
962771AG1-126 GEN
Solar/Wind Harmer
9.768
970065AG2-057 GEN
Solar/Wind Harmer
0.436
970149AG2-104 GEN
Solar/Wind Harmer
7.682
970153AG2-106 GEN
Solar/Wind Harmer
6.66
970155AG2-107 GEN
Solar/Wind Harmer
6.66
970179AG2-119 GEN
Solar/Wind Harmer
4.106
971201AH1-060 GEN
Solar/Wind Harmer
0.872
971995AH1-542 GEN
Solar/Wind Harmer
5.541
971995AH1-542 GEN
Solar/Wind Harmer
7.556
270223U2-072_GEN1
Solar/Wind Harmer
2.379
270224U2-072_GEN2
Solar/Wind Harmer
2.379
270227U2-072_GEN3
Solar/Wind Harmer
2.379
270228U2-072_GEN4
Solar/Wind Harmer
2.379
270231U2-072_GEN5
Solar/Wind Harmer
2.379
942051AE2-217 GEN
Solar/Wind Harmer
8.404
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.386
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.843
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.418
NYPJM->LTFIMP_NY
CLTF
1.562
LGEELTFEXP_LGEE->PJM
CLTF
2.018
WECLTFEXP_WEC->PJM
CLTF
1.421
CPLELTFEXP_CPLE->PJM
CLTF
0.007
TVALTFEXP_TVA->PJM
CLTF
1.896
MECLTFEXP_MEC->PJM
CLTF
5.573
LAGNLTFEXP_LAGN->PJM
CLTF
4.254
SIGELTFEXP_SIGE->PJM
CLTF
0.159
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
12.239
AG2-052LTFEXP_AG2-052->PJM
LTF
0.088
AH1-155LTFEXP_AH1-155->PJM
LTF
0.132

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.44 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1415.21
MW Contribution:
13.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0
270317AD1-130_GEN
Solar/Wind Harmer
0
241813AF1-122_GEN
Solar/Wind Harmer
2.79
270471AD2-092_GEN
Solar/Wind Harmer
0
270349AD2-093_GEN
Solar/Wind Harmer
0
270520AE2-214 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
2.127
270466AD2-091
50/50
5.156
270036AE2-216 BAT
50/50
5.672
270475AD2-096_GEN
50/50
7.52
270051AF1-062 GEN
50/50
Charging
37.356
270578AF1-285 GEN2
Solar/Wind Harmer
1.107
270391AF1-285 GEN3
Solar/Wind Harmer
1.107
270462AD2-086
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
13.409
962761AG1-125 GEN
Solar/Wind Harmer
9.768
962771AG1-126 GEN
Solar/Wind Harmer
9.768
970065AG2-057 GEN
Solar/Wind Harmer
0.436
970149AG2-104 GEN
Solar/Wind Harmer
7.682
970153AG2-106 GEN
Solar/Wind Harmer
6.66
970155AG2-107 GEN
Solar/Wind Harmer
6.66
970179AG2-119 GEN
Solar/Wind Harmer
4.106
971201AH1-060 GEN
Solar/Wind Harmer
0.872
971995AH1-542 GEN
Solar/Wind Harmer
5.541
971995AH1-542 GEN
Solar/Wind Harmer
7.556
270223U2-072_GEN1
Solar/Wind Harmer
2.379
270224U2-072_GEN2
Solar/Wind Harmer
2.379
270227U2-072_GEN3
Solar/Wind Harmer
2.379
270228U2-072_GEN4
Solar/Wind Harmer
2.379
270231U2-072_GEN5
Solar/Wind Harmer
2.379
942051AE2-217 GEN
Solar/Wind Harmer
8.404
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.386
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.843
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.418
NYPJM->LTFIMP_NY
CLTF
1.562
LGEELTFEXP_LGEE->PJM
CLTF
2.018
WECLTFEXP_WEC->PJM
CLTF
1.421
CPLELTFEXP_CPLE->PJM
CLTF
0.007
TVALTFEXP_TVA->PJM
CLTF
1.896
MECLTFEXP_MEC->PJM
CLTF
5.573
LAGNLTFEXP_LAGN->PJM
CLTF
4.254
SIGELTFEXP_SIGE->PJM
CLTF
0.159
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
12.239
AG2-052LTFEXP_AG2-052->PJM
LTF
0.088
AH1-155LTFEXP_AH1-155->PJM
LTF
0.132
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
243458 to 246752 ckt 1

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 2, Cluster 45 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 45 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 45 projects will meet the dynamics requirements of the NERC, FE-ATSI, and PJM reliability standards.

The load flow scenario for the analysis was based on the RTEP 2028 summer peak load case, modified to include applicable projects. Cluster 45 projects have been dispatched online at maximum power output, with approximately unity power factor at the high side of the GSUs, 1.00 pu voltage at the generator terminals, and 1.01 pu voltage at the POI buses.

Cluster 45 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 153 contingencies were studied, each with a 20 second simulation time period (with 1.0 second initial run prior to any events). Studied faults included:

  1. Steady-state operation (Category P0);
  2. Three-phase faults with normal clearing time (Category P1);
  3. Single-phase bus faults with normal clearing time (Category P2);
  4. Single-phase faults with stuck breaker (Category P4);
  5. Single phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5).;
  6. Single-phase faults with normal clearing on common structure (Category P7).

No High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 45 projects.

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2028 peak load case:

  1. Cluster 45 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 45 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

No mitigations were found to be required for TC2 Cluster 45.

Table 1: TC2 Cluster 45 Projects

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

45

AG2-119

Solar

First Energy Transmission System, ATSI zone

80 MW

80 MW

53.6 MW

Galion to Roberts South 138 kV

AH1-542

Solar & Storage

First Energy Transmission System, ATSI zone

110 MW

110 MW

22 MW

Kirby to Crissinger 138 kV

 

Reactive Power Analysis

 The reactive power capability of AH1-542 meets the 0.95 lagging and leading PF requirement at the high side of the main transformer.

 

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AB1-006Meadow Lake 345kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-170East Lima-Marysville 345kVIn Service
AC1-001Delano 138kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-078Beatty-London 138kVIn Service
AC1-085Stuart-Clinton 345kVIn Service
AC1-111Aurora 138kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Platter Creek 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-214Crescent RidgeIn Service
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVPartially in Service - Under Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-195Galion-Roberts South 138 kVPartially in Service - Under Construction
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVWithdrawn
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVIn Service
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVUnder Construction
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVWithdrawn
AD2-093Marysville 345kVPartially in Service - Under Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVEngineering & Procurement
AE1-102Maddox Creek 345 kVSuspended
AE1-113Mole Creek 345 kVUnder Construction
AE1-114Maryland-Lancaster 138 kVEngineering & Procurement
AE1-163Powerton-Nevada 345 kVUnder Construction
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterWithdrawn
AE1-183Maysville-McDowell 69 kVUnder Construction
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVPartially in Service - Under Construction
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-089Pennville-Adams 138 kVSuspended
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVUnder Construction
AE2-216Hardin Switch 345 kVSuspended
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVEngineering & Procurement
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVUnder Construction
AE2-261Kincaid-Pana 345 kVEngineering & Procurement
AE2-285Maysville 69 kVUnder Construction
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVWithdrawn
AE2-305Givens-Mechanicsburg 138 kVWithdrawn
AE2-306Gunn Road 345 kVUnder Construction
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-322Platter Creek 69kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVPartially in Service - Under Construction
AE2-325Valley 138 kVWithdrawn
AE2-341Sandwich-Plano 138 kVEngineering & Procurement
AE2-342Woodstock 69 kVSuspended
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-053Givens-Mechanicsburg 138 kVWithdrawn
AF1-054Givens-Mechanicsburg 138 kVWithdrawn
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-084Hartford-Almena 69 kVUnder Construction
AF1-086Madera-Westover South 115 kVPartially in Service - Under Construction
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVWithdrawn
AF1-093Henderson-Stoneboro 69 kVUnder Construction
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVSuspended
AF1-118Sorenson-Desoto 345 kVWithdrawn
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVUnder Construction
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-176Corey 138 kVEngineering & Procurement
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-204Eugene 345 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVUnder Construction
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVUnder Construction
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-296Garden Plain 138 kVEngineering & Procurement
AF1-302Brookville-Squab Hollow 138 kVUnder Construction
AF1-322Meadow Lake 345 kVUnder Construction
AF1-331Twombley RoadEngineering & Procurement
AF2-014Maddox Creek 345 kVUnder Construction
AF2-032Kincaid 345 kVWithdrawn
AF2-039Shawville-Clearfield 34.5 kVUnder Construction
AF2-041Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-068Jay 138 kVEngineering & Procurement
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIUnder Construction
AF2-095Davis Creek 138 kVEngineering & Procurement
AF2-103Haviland 138 kVIn Service
AF2-111North Clark-Spurlock 345 kVEngineering & Procurement
AF2-122Kirk 138 kVPartially in Service - Under Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVEngineering & Procurement
AF2-143Powerton-Nevada 345 kVEngineering & Procurement
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-177Sorenson-DeSoto #2 345 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-200Nelson-Electric Junction 345 kVEngineering & Procurement
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-350Kensington 138 kVEngineering & Procurement
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVPartially in Service - Under Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVEngineering & Procurement
AF2-396Stinger 138 kVEngineering & Procurement
AG1-017Jay 138 kVIn Service
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVUnder Construction
AG1-118Sugar Grove-Waterman 138kVEngineering & Procurement
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVEngineering & Procurement
AG1-198Union City 34.5 kVIn Service
AG1-226Dequine-Eugene 345 kVEngineering & Procurement
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVEngineering & Procurement
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-410Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-411Maddox Creek-RP Mone 345 kVEngineering & Procurement
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVEngineering & Procurement
AG1-436Olive-University Park 345 kVEngineering & Procurement
AG1-447Olive-University Park 345 kVEngineering & Procurement
AG1-460Kincaid-Pana 345 kVEngineering & Procurement
AG1-462Cordova 345 kVEngineering & Procurement
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG2-029Forest G. Hipple-Dunton Lake 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-061Dana 345 kVActive
AG2-072Rockport 765 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-585Kensignton 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-675Cordova 345 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Silver Lake - Cherry Valley 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-338New Sub S2354 138kVActive
AH1-341ESS-H445 3B 138kvActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry - Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-073Yankee 12.5kVIn Service
W2-048Brokaw-LanesvilleIn Service
X2-022Brokaw-LanesvilleIn Service
X3-005Wildwood 12kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-542 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-542 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-542 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-542 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-542 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-542 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-542 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-542 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-542 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-542 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-542 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-542 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-542 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-542 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-542 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-542 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-542 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-542 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-542 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-542 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-542 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-542 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9767.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9767.0 / AEP-TC2-19068
Title
05KAMMER_RG 765.0 kV to 05KAMMER 765.0 kV ckt Z1 - Replace Wavetraps
Description
Replace the existing 3000A wave trap at Kammer 765 station towards Guernsey with a 5000A wave trap. Additionally, replace the 3000A circuit breaker QQ1 with a 5000A circuit breaker. Disconnect switches and a relays will be upgraded as well.
Total Cost ($USD)
$4,500,000
Discounted Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-542 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-542 could receive cost allocation. Although AH1-542 may not presently have cost responsibility for this upgrade, AH1-542 is a potential Aggregate Pool Contributor.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
Rating SetRating TypeRating Value
(All)A5523.0 MVA
(All)B5523.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-542


AH1-542 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-542 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-542 One Line Diagram

AH1-542 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.