AH1-546 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:45

Bremo - Buckingham 230 kV

39.0 MW Capacity / 65.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Mountain Pine Arvonia LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $26,053,121 $34,080,024 = 0.76 AND ( $26,053,121 - $34,080,024 ) 65.0 = $-123,491 per MW

General

The Project Developer has proposed a Solar generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Buckingham County, Virginia. The installed facilities will have a total capability of 65.0 MW with 39.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-546
Project Name:
Bremo - Buckingham 230 kV
Project Developer Name:
Mountain Pine Arvonia LLC
State:
Virginia
County:
Buckingham
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
65.0
MWE:
65.0
MWC:
39.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-546 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system by tapping the Bremo - Buckingham 230 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-546 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-546Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$1,140,057$0$0
Other Scope$499,571$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$17,414,227$17,414,227$17,414,227
Network Upgrades$8,324,897$8,324,897$8,324,897
System Reliability Network Upgrades
Steady State Thermal & Voltage$313,997$313,997$313,997
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$27,692,749$26,053,121$26,053,121

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-546

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-546
Project ID: AH1-546
20% of cost allocation for Phase II Network Upgrades:(A) $5,210,624
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $3,408,002
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $1,802,622
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

This scope serves to cut in 230 kV line 298 into a new three breaker substation.

$5,628,665$1,458,246$415,706$221,103$7,723,720$7,723,720
(Pending)

Remote end network upgrades at Bremo Substation

$168,816$91,376$39,726$11,884$311,802$311,802
(Pending)

Remote end network upgrade at Farmville Substation.

$121,334$55,942$13,424$5,111$195,811$195,811
(Pending)

Remote end network upgrade at Buckingham Substation

$84,377$0$9,187$0$93,564$93,564
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

This scope includes metering accuracy coupling capacitor voltage transformers (CCVT), metering accuracy current transformers (CT) and associated equipment.

$317,977$33,491$141,737$6,366$499,571$499,571
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

The scope serves to build a 230kV three breaker ring bus to support the new solar farm built by Project Developer.

$8,597,453$5,965,501$2,360,476$490,797$17,414,227$17,414,227
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Portion of the interconnection switching station soley associated with the single feed to the generating facilities collector station including disconnect switch, conductors and connectors.

$655,281$333,331$124,824$26,621$1,140,057$1,140,057
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

This scope serves to cut in 230 kV line 298 into a new three breaker substation.

$5,628,665$1,458,246$415,706$221,103$7,723,720$7,723,720
(Pending)

Remote end network upgrades at Bremo Substation

$168,816$91,376$39,726$11,884$311,802$311,802
(Pending)

Remote end network upgrade at Farmville Substation.

$121,334$55,942$13,424$5,111$195,811$195,811
(Pending)

Remote end network upgrade at Buckingham Substation

$84,377$0$9,187$0$93,564$93,564
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Option to Build (OTB) oversite for Other scope

$31,876$0$3,557$0$35,433$35,433
(Pending)

Option to Build (OTB) oversite for Transmission Owner Interconnection Facilities scope

$104,541$0$22,939$0$127,480$127,480
(Pending)

Option to Build (OTB) oversite for Stand Alone Network Upgrade scope

$1,899,749$423,186$406,894$38,727$2,768,556$2,768,556
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$27,378,752$27,378,752
Developer Build Option$11,256,366$11,256,366

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 96 to 97 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-546 was evaluated as a 65.0 MW (39.0 MW Capacity) injection in the Dominion area.

AH1-546 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 65.0 MW (65.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A_SENS
BreakerAC119.42 %830.0C991.21
21.81
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S_SENS
BreakerAC119.42 %830.0C991.21
21.81
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
SingleAC118.66 %678.68B805.35
16.39
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC109.08 %678.68B740.31
21.7
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC102.11 %830.0C847.48
28.57
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC102.11 %830.0C847.48
28.57
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC100.31 %830.0C832.54
21.97
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S_SENS
BreakerAC118.86 %830.0C986.57
21.81
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A_SENS
BreakerAC118.86 %830.0C986.57
21.81
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
SingleAC117.79 %678.68B799.44
16.39
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC108.09 %678.68B733.57
21.7
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC101.3 %830.0C840.79
28.57
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC101.3 %830.0C840.79
28.57
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
DVP_P4-5: 556X2_SRT-S
BreakerAC135.38 %1050.6C1422.29
6.25
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
DVP_P4-5: 556X1_SRT-S
BreakerAC134.91 %1053.0C1420.61
6.24
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
SingleAC110.74 %678.68B751.6
15.29
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC105.38 %678.68B715.22
20.23
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
SingleAC110.99 %661.76B734.51
15.29
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC105.47 %661.76B697.98
20.23
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC100.19 %809.0C810.51
26.64
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC100.19 %809.0C810.51
26.64
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
SingleAC107.84 %661.76B713.66
15.29
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC102.19 %661.76B676.22
20.23
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC118.18 %3099.0B3662.4
6.5
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL_SENS
BreakerAC105.83 %3099.0B3279.67
5.48
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
PEPCO_P4_PP41_SRT-A
BreakerAC103.07 %3099.0B3194.05
5.46
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC210.5 %541.0B1138.82
5.64
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC210.16 %541.0B1136.95
5.64
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC210.16 %541.0B1136.95
5.64
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC201.89 %541.0B1092.2
5.56
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC201.87 %541.0B1092.14
5.56
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC172.45 %508.54B876.98
4.28
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC169.26 %508.54B860.77
4.28
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS
TowerAC105.47 %541.0B570.59
2.67
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC148.37 %699.0C1037.09
41.02
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC148.37 %699.0C1037.09
41.02
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC147.68 %699.0C1032.31
41.02
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC143.16 %571.52B818.17
31.16
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC141.58 %699.0C989.64
41.02
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC141.58 %699.0C989.64
41.02
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC140.31 %571.52B801.9
31.16

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.42 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:991.21
MW Contribution:
21.81
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.206
316303AF2-085
50/50
2.484
316322AB2-045
Solar/Wind Harmer
1.467
971845AH1-439 GEN
Solar/Wind Harmer
22.808
316258AE1-075 C
Solar/Wind Harmer
0.76
316405AF2-144 C
Solar/Wind Harmer
0.803
946301AF1-294 GEN
Solar/Wind Harmer
5.991
961791AG1-021 GEN
Solar/Wind Harmer
2.922
3144303KENBRDG
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
12.304
970681AG2-440 GEN
Solar/Wind Harmer
8.167
316238AB2-078_GEN
Solar/Wind Harmer
0.41
316239AB2-077_GEN
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.345
971281AH1-106 GEN
Solar/Wind Harmer
2.085
971283AH1-107 GEN
Solar/Wind Harmer
2.085
316486AD2-202 GEN
Solar/Wind Harmer
0.302
970831AG2-522 GEN
Solar/Wind Harmer
4.94
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.62
971967AH1-528 GEN
Solar/Wind Harmer
16.771
946281AF1-292 GEN
Solar/Wind Harmer
0.19
3137643SOCKMAN
Solar/Wind Harmer
-0.032
970673AG2-436 GEN
Solar/Wind Harmer
17.241
970533AG2-339 GEN
Solar/Wind Harmer
5.254
316426AA2-053 GEN
Solar/Wind Harmer
0.785
970085AG2-068 GEN
Solar/Wind Harmer
4.799
970581AG2-369 GEN
Solar/Wind Harmer
4.127
3146043SEABORD
Solar/Wind Harmer
-0.008
315814AE2-033 C
Solar/Wind Harmer
6.846
315652AC1-086 GEN
Solar/Wind Harmer
8.081
316274AC1-208 GEN
Solar/Wind Harmer
0.772
316318V4-068
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.105
3146033SCOT NK
Solar/Wind Harmer
-0.028
315839AE2-212 C
Solar/Wind Harmer
0.21
316463AE2-346 GEN
Solar/Wind Harmer
0.112
3145513AHOSKIE
Solar/Wind Harmer
0.061
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.689
970657AG2-426 GEN
Solar/Wind Harmer
0.424
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.894
315833AF1-017_GEN
Solar/Wind Harmer
1.255
316311AC2-079 GEN
Solar/Wind Harmer
3.332
315732AD1-074 GEN1
Solar/Wind Harmer
1.322
315733AD1-074 GEN2
Solar/Wind Harmer
1.322
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315697AD1-025 GEN
Solar/Wind Harmer
1.317
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.601
316174AB2-169 GEN
Solar/Wind Harmer
0.993
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
957871AF2-081 GEN
Solar/Wind Harmer
3.196
957861AF2-080 GEN
Solar/Wind Harmer
2.791
316316AC1-027 C
Solar/Wind Harmer
0.195
316236AE1-162_GEN
Solar/Wind Harmer
0.192
3151081ELIZAR1
Adder
5.199
3151091ELIZAR2
Adder
5.109
971445AH1-216 GEN
Solar/Wind Harmer
3.943
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3145746EVERETS
Solar/Wind Harmer
-0.025
3151921BEARGRDN G2
50/50
4.545
3144293JTRSVLE
50/50
0.527
972003AH1-546 GEN
Solar/Wind Harmer
21.813
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.168
942461AE2-259 GEN
Solar/Wind Harmer
4.286
3147133PAMPLIN
Solar/Wind Harmer
-0.07
970257AG2-171 GEN
Solar/Wind Harmer
7.117
971775AH1-396 GEN
Solar/Wind Harmer
1.339
959311AF2-222 GEN
Solar/Wind Harmer
17.432
964241AG1-285 GEN
Solar/Wind Harmer
11.676
970221AG2-151 GEN
Solar/Wind Harmer
9.255
316478AD1-087 GEN
Solar/Wind Harmer
1.032
270494AE1-108_GEN
Solar/Wind Harmer
2.999
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.379
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.172
316181AB2-040 GEN
Solar/Wind Harmer
1.147
971683AH1-343 GEN
Solar/Wind Harmer
3.493
944011AF1-069 GEN
Solar/Wind Harmer
4.59
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970917AG2-570 GEN
Solar/Wind Harmer
19.442
3156081AA2-088 GEN
Solar/Wind Harmer
2.348
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.5
3145893MURPHYS
Solar/Wind Harmer
0.05
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.265
3143096IRON208
Adder
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.614
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.322
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.26
3145273HOLLAND
Solar/Wind Harmer
-0.005
970657AG2-426 GEN
Solar/Wind Harmer
1.358
970133AG2-095 GEN
Solar/Wind Harmer
0.756
315722AD1-056 GEN
Solar/Wind Harmer
2.391
3146233WITAKRS
Solar/Wind Harmer
0.139
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.004
316458AB2-190 GEN2
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.62
315778AD1-151 GEN
Solar/Wind Harmer
5.844
315735AD1-075 GEN1
Solar/Wind Harmer
0.661
3146376EDENTON
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316123AC1-075 GEN
Solar/Wind Harmer
0.697
3145963POPLR C
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
1.355
316305AF2-043 C
Solar/Wind Harmer
0.193
3151931BEARGRDN S1
50/50
5.872
3151911BEARGRDN G1
50/50
4.545
3144293JTRSVLE
50/50
0.527
3144293JTRSVLE
50/50
0.416
970119AG2-088 GEN
50/50
18.628
970937AG2-583 GEN
Solar/Wind Harmer
33.126
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.727
971563AH1-280 GEN
Solar/Wind Harmer
2.922
970685AG2-442 GEN
Solar/Wind Harmer
16.459
315785AD2-033 C
Solar/Wind Harmer
4.092
316034AC1-036 C
Solar/Wind Harmer
0.304
3143226MDLTHAN
Solar/Wind Harmer
-0.016
315693AD1-088 GEN
Solar/Wind Harmer
7.448
971377AH1-170 GEN
Solar/Wind Harmer
1.851
3147623JAMES R
Solar/Wind Harmer
0.229
316131AB2-060 GEN
Solar/Wind Harmer
1.533
3143526WINTERP
Solar/Wind Harmer
-0.066
957481AF2-042 GEN
Solar/Wind Harmer
37.368
970401AG2-262 GEN
Solar/Wind Harmer
0.741
971065AG2-659 GEN
Solar/Wind Harmer
5.161
316129AC1-054 GEN
Solar/Wind Harmer
0.886
3147043LAWRENC
Adder
0.815
3150851SPRUNCC
Adder
0.379
960081AF2-299 GEN
Solar/Wind Harmer
0.953
316087AB2-174 GEN
Solar/Wind Harmer
1.183
3145783HORNRTN
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
14.649
970919AG2-571 GEN
Solar/Wind Harmer
2.461
315607AA1-063A GEN
Solar/Wind Harmer
0.776
970087AG2-069 GEN
Solar/Wind Harmer
7.198
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.501
940641AE2-051 GEN
Solar/Wind Harmer
6.871
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.212
3143096IRON208
Adder
0.265
939411AE1-173 GEN
Solar/Wind Harmer
35.461
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.242
316381AD1-082 GEN
Solar/Wind Harmer
0.616
3156021HOLLOMANSOL
Solar/Wind Harmer
0.9
316319Z2-044 C
Solar/Wind Harmer
0.368
3146233WITAKRS
Solar/Wind Harmer
-0.026
316132AB2-190 GEN1
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.654
971069AG2-661 GEN
Solar/Wind Harmer
1.039
315737AD1-076 GEN
Solar/Wind Harmer
1.244
316369SG1_INVT
Solar/Wind Harmer
1.164
316093AE2-104_GEN
Solar/Wind Harmer
1.898
315816AE2-034 GEN
Solar/Wind Harmer
0.526
3145663CRESWEL
Solar/Wind Harmer
-0.018
971163AH1-040 GEN
Solar/Wind Harmer
6.117
3130156CHOWAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.601
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.87
3142053HEARTS
Solar/Wind Harmer
0.076
3145963POPLR C
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
3.175
944631AF1-128 GEN
Adder
27.172
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
319010AE1-072 C
Solar/Wind Harmer
1.29
3146456SLIGO L269
Solar/Wind Harmer
-0.006
3146293MARTNCO
Solar/Wind Harmer
0.04
316494AC1-189 GEN
Solar/Wind Harmer
0.686
944591AF1-124 GEN
Solar/Wind Harmer
29.1
316375AC2-012 GEN
Solar/Wind Harmer
2.204
316036AC1-147 C
Solar/Wind Harmer
0.171
3150981CHESPKA
Adder
0.708
3145336SMITFLD
Solar/Wind Harmer
-0.025
3151171GRAVELC
Adder
0.603
316072AD1-144
Solar/Wind Harmer
0.128
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.765
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.122
315616AA1-038_C
Solar/Wind Helper
0.552
316246AF1-032 C
Solar/Wind Harmer
0.13
316321Z2-027
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
2.557
316320Y1-086
Solar/Wind Harmer
0.376
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.74
316420AA1-050 GEN
Solar/Wind Harmer
0.728
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
3145933PARMELE
Solar/Wind Harmer
-0.006
3142956BIRDNECK
Solar/Wind Harmer
0.342
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
28.996
944601AF1-125 GEN
Solar/Wind Harmer
28.543
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.266
3151171GRAVELC
Adder
0.794
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.511
3132273ORANGE
Solar/Wind Helper
0.026
970909AG2-566 GEN
50/50
2.48
3144293JTRSVLE
50/50
0.527
3146776BUCKING
Solar/Wind Harmer
-0.174
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.18
316313AB2-026
Solar/Wind Harmer
0.845
970301AG2-198 GEN
Solar/Wind Harmer
13.062
958211AF2-115 GEN
Solar/Wind Harmer
3.653
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
970323AG2-213 GEN
Solar/Wind Harmer
9.489
971223AH1-071 GEN
Solar/Wind Harmer
1.962
313527AB2-043 GEN
Solar/Wind Harmer
2.256
316237AB2-079_GEN
Solar/Wind Harmer
0.41
3143526WINTERP
Solar/Wind Harmer
-0.066
970099AG2-077 GEN
Solar/Wind Harmer
14.947
962561AG1-105 GEN
Solar/Wind Harmer
6.603
964791AG1-342 GEN
Solar/Wind Harmer
2.424
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.294
316118AC1-105 GEN
Solar/Wind Harmer
0.715
970933AG2-581 GEN
Solar/Wind Harmer
9.133
316248AF1-058 C
Solar/Wind Harmer
0.286
313506AB2-031 GEN
Solar/Wind Harmer
0.66
972187AH1-678 GEN
Adder
2.044
972185AH1-677 GEN
Adder
3.99
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.932
3145783HORNRTN
Solar/Wind Harmer
0.745
3145783HORNRTN
Solar/Wind Harmer
0.233
3145783HORNRTN
Solar/Wind Harmer
0.093
316365GEN2_N
Solar/Wind Harmer
0.501
3144356SAPONY
Solar/Wind Harmer
0.256
316315AB2-025 C
Solar/Wind Harmer
0.198
962571AG1-106 GEN
Solar/Wind Harmer
1.033
3145893MURPHYS
Solar/Wind Harmer
0.2
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.047
316240AF1-291 C
Solar/Wind Harmer
0.208
944641AF1-129 GEN
Adder
29.302
315742AE1-103 GEN
Solar/Wind Harmer
1.626
316083AB2-161 GEN
Solar/Wind Harmer
1.092
315724AD1-057 GEN
Solar/Wind Harmer
1.315
316349AD2-085 GEN
Solar/Wind Harmer
0.587
316065AD1-022 GEN
Solar/Wind Harmer
3.297
316033AB2-134 GEN
Solar/Wind Harmer
2.102
315835AF2-110_GEN
Solar/Wind Harmer
0.816
315614AA2-178 GEN
Solar/Wind Harmer
0.702
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316049AB1-081 GEN
Solar/Wind Harmer
0.696
316263AC1-034 GEN
Solar/Wind Harmer
3.034
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.167
316433W1029_GEN2
Solar/Wind Harmer
1.167
316435W1029_GEN3
Solar/Wind Harmer
1.167
961601AG1-000A GEN
Solar/Wind Harmer
2.525
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
0.755
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.43
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3150991CHESPKB
Adder
0.594
3150991CHESPKB
Adder
0.58
316005AA1-067
Solar/Wind Harmer
0.128
966001AG1-469 GEN
Solar/Wind Helper
0.182
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.077
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
1.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.607
CPLELTFEXP_CPLE->PJM
CLTF
3.66
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.81
MECLTFEXP_MEC->PJM
CLTF
0.061
NYPJM->LTFIMP_NY
CLTF
0.429

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.42 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:991.21
MW Contribution:
21.81
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.872
3151911BEARGRDN G1
50/50
4.545
3144293JTRSVLE
50/50
0.527
3144293JTRSVLE
50/50
0.416
970119AG2-088 GEN
50/50
18.628
970937AG2-583 GEN
Solar/Wind Harmer
33.126
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.727
971563AH1-280 GEN
Solar/Wind Harmer
2.922
972205AH1-687 GEN
50/50
22.206
316303AF2-085
50/50
2.484
316322AB2-045
Solar/Wind Harmer
1.467
971845AH1-439 GEN
Solar/Wind Harmer
22.808
316258AE1-075 C
Solar/Wind Harmer
0.76
316405AF2-144 C
Solar/Wind Harmer
0.803
946301AF1-294 GEN
Solar/Wind Harmer
5.991
961791AG1-021 GEN
Solar/Wind Harmer
2.922
3144303KENBRDG
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
12.304
970681AG2-440 GEN
Solar/Wind Harmer
8.167
316238AB2-078_GEN
Solar/Wind Harmer
0.41
316239AB2-077_GEN
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.345
971281AH1-106 GEN
Solar/Wind Harmer
2.085
971283AH1-107 GEN
Solar/Wind Harmer
2.085
316486AD2-202 GEN
Solar/Wind Harmer
0.302
970831AG2-522 GEN
Solar/Wind Harmer
4.94
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.62
971967AH1-528 GEN
Solar/Wind Harmer
16.771
946281AF1-292 GEN
Solar/Wind Harmer
0.19
3137643SOCKMAN
Solar/Wind Harmer
-0.032
970673AG2-436 GEN
Solar/Wind Harmer
17.241
970533AG2-339 GEN
Solar/Wind Harmer
5.254
316426AA2-053 GEN
Solar/Wind Harmer
0.785
970085AG2-068 GEN
Solar/Wind Harmer
4.799
970581AG2-369 GEN
Solar/Wind Harmer
4.127
3146043SEABORD
Solar/Wind Harmer
-0.008
315814AE2-033 C
Solar/Wind Harmer
6.846
315652AC1-086 GEN
Solar/Wind Harmer
8.081
316274AC1-208 GEN
Solar/Wind Harmer
0.772
316318V4-068
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.105
3146033SCOT NK
Solar/Wind Harmer
-0.028
315839AE2-212 C
Solar/Wind Harmer
0.21
316463AE2-346 GEN
Solar/Wind Harmer
0.112
3145513AHOSKIE
Solar/Wind Harmer
0.061
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.689
970657AG2-426 GEN
Solar/Wind Harmer
0.424
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.894
315833AF1-017_GEN
Solar/Wind Harmer
1.255
316311AC2-079 GEN
Solar/Wind Harmer
3.332
315732AD1-074 GEN1
Solar/Wind Harmer
1.322
315733AD1-074 GEN2
Solar/Wind Harmer
1.322
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315697AD1-025 GEN
Solar/Wind Harmer
1.317
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.601
316174AB2-169 GEN
Solar/Wind Harmer
0.993
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
957871AF2-081 GEN
Solar/Wind Harmer
3.196
957861AF2-080 GEN
Solar/Wind Harmer
2.791
316316AC1-027 C
Solar/Wind Harmer
0.195
316236AE1-162_GEN
Solar/Wind Harmer
0.192
3151081ELIZAR1
Adder
5.199
3151091ELIZAR2
Adder
5.109
971445AH1-216 GEN
Solar/Wind Harmer
3.943
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.122
315616AA1-038_C
Solar/Wind Helper
0.552
3151921BEARGRDN G2
50/50
4.545
3144293JTRSVLE
50/50
0.527
972003AH1-546 GEN
Solar/Wind Harmer
21.813
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.168
942461AE2-259 GEN
Solar/Wind Harmer
4.286
3147133PAMPLIN
Solar/Wind Harmer
-0.07
970257AG2-171 GEN
Solar/Wind Harmer
7.117
971775AH1-396 GEN
Solar/Wind Harmer
1.339
959311AF2-222 GEN
Solar/Wind Harmer
17.432
964241AG1-285 GEN
Solar/Wind Harmer
11.676
970221AG2-151 GEN
Solar/Wind Harmer
9.255
316478AD1-087 GEN
Solar/Wind Harmer
1.032
270494AE1-108_GEN
Solar/Wind Harmer
2.999
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.379
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.172
316181AB2-040 GEN
Solar/Wind Harmer
1.147
971683AH1-343 GEN
Solar/Wind Harmer
3.493
944011AF1-069 GEN
Solar/Wind Harmer
4.59
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970917AG2-570 GEN
Solar/Wind Harmer
19.442
3156081AA2-088 GEN
Solar/Wind Harmer
2.348
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.5
3145893MURPHYS
Solar/Wind Harmer
0.05
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.265
3143096IRON208
Adder
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.614
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.322
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.26
3145273HOLLAND
Solar/Wind Harmer
-0.005
970657AG2-426 GEN
Solar/Wind Harmer
1.358
970133AG2-095 GEN
Solar/Wind Harmer
0.756
315722AD1-056 GEN
Solar/Wind Harmer
2.391
3146233WITAKRS
Solar/Wind Harmer
0.139
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.004
316458AB2-190 GEN2
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.62
315778AD1-151 GEN
Solar/Wind Harmer
5.844
315735AD1-075 GEN1
Solar/Wind Harmer
0.661
3146376EDENTON
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316123AC1-075 GEN
Solar/Wind Harmer
0.697
3145963POPLR C
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
1.355
316305AF2-043 C
Solar/Wind Harmer
0.193
316246AF1-032 C
Solar/Wind Harmer
0.13
316321Z2-027
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
2.557
316320Y1-086
Solar/Wind Harmer
0.376
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.74
316420AA1-050 GEN
Solar/Wind Harmer
0.728
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
3145933PARMELE
Solar/Wind Harmer
-0.006
3142956BIRDNECK
Solar/Wind Harmer
0.342
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
28.996
944601AF1-125 GEN
Solar/Wind Harmer
28.543
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.266
3151171GRAVELC
Adder
0.794
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.511
3132273ORANGE
Solar/Wind Helper
0.026
970685AG2-442 GEN
Solar/Wind Harmer
16.459
315785AD2-033 C
Solar/Wind Harmer
4.092
316034AC1-036 C
Solar/Wind Harmer
0.304
3143226MDLTHAN
Solar/Wind Harmer
-0.016
315693AD1-088 GEN
Solar/Wind Harmer
7.448
971377AH1-170 GEN
Solar/Wind Harmer
1.851
3147623JAMES R
Solar/Wind Harmer
0.229
316131AB2-060 GEN
Solar/Wind Harmer
1.533
3143526WINTERP
Solar/Wind Harmer
-0.066
957481AF2-042 GEN
Solar/Wind Harmer
37.368
970401AG2-262 GEN
Solar/Wind Harmer
0.741
971065AG2-659 GEN
Solar/Wind Harmer
5.161
316129AC1-054 GEN
Solar/Wind Harmer
0.886
3147043LAWRENC
Adder
0.815
3150851SPRUNCC
Adder
0.379
960081AF2-299 GEN
Solar/Wind Harmer
0.953
316087AB2-174 GEN
Solar/Wind Harmer
1.183
3145783HORNRTN
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
14.649
970919AG2-571 GEN
Solar/Wind Harmer
2.461
315607AA1-063A GEN
Solar/Wind Harmer
0.776
970087AG2-069 GEN
Solar/Wind Harmer
7.198
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.501
940641AE2-051 GEN
Solar/Wind Harmer
6.871
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.212
3143096IRON208
Adder
0.265
939411AE1-173 GEN
Solar/Wind Harmer
35.461
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.242
316381AD1-082 GEN
Solar/Wind Harmer
0.616
3156021HOLLOMANSOL
Solar/Wind Harmer
0.9
316319Z2-044 C
Solar/Wind Harmer
0.368
3146233WITAKRS
Solar/Wind Harmer
-0.026
316132AB2-190 GEN1
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.654
971069AG2-661 GEN
Solar/Wind Harmer
1.039
315737AD1-076 GEN
Solar/Wind Harmer
1.244
316369SG1_INVT
Solar/Wind Harmer
1.164
316093AE2-104_GEN
Solar/Wind Harmer
1.898
315816AE2-034 GEN
Solar/Wind Harmer
0.526
3145663CRESWEL
Solar/Wind Harmer
-0.018
971163AH1-040 GEN
Solar/Wind Harmer
6.117
3130156CHOWAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.601
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.87
3142053HEARTS
Solar/Wind Harmer
0.076
3145963POPLR C
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
3.175
944631AF1-128 GEN
Adder
27.172
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
319010AE1-072 C
Solar/Wind Harmer
1.29
3146456SLIGO L269
Solar/Wind Harmer
-0.006
3146293MARTNCO
Solar/Wind Harmer
0.04
316494AC1-189 GEN
Solar/Wind Harmer
0.686
944591AF1-124 GEN
Solar/Wind Harmer
29.1
316375AC2-012 GEN
Solar/Wind Harmer
2.204
316036AC1-147 C
Solar/Wind Harmer
0.171
3150981CHESPKA
Adder
0.708
3145336SMITFLD
Solar/Wind Harmer
-0.025
3151171GRAVELC
Adder
0.603
316072AD1-144
Solar/Wind Harmer
0.128
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.765
970909AG2-566 GEN
50/50
2.48
3144293JTRSVLE
50/50
0.527
3146776BUCKING
Solar/Wind Harmer
-0.174
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.18
316313AB2-026
Solar/Wind Harmer
0.845
970301AG2-198 GEN
Solar/Wind Harmer
13.062
958211AF2-115 GEN
Solar/Wind Harmer
3.653
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
970323AG2-213 GEN
Solar/Wind Harmer
9.489
971223AH1-071 GEN
Solar/Wind Harmer
1.962
313527AB2-043 GEN
Solar/Wind Harmer
2.256
316237AB2-079_GEN
Solar/Wind Harmer
0.41
3143526WINTERP
Solar/Wind Harmer
-0.066
970099AG2-077 GEN
Solar/Wind Harmer
14.947
962561AG1-105 GEN
Solar/Wind Harmer
6.603
964791AG1-342 GEN
Solar/Wind Harmer
2.424
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.294
316118AC1-105 GEN
Solar/Wind Harmer
0.715
970933AG2-581 GEN
Solar/Wind Harmer
9.133
316248AF1-058 C
Solar/Wind Harmer
0.286
313506AB2-031 GEN
Solar/Wind Harmer
0.66
972187AH1-678 GEN
Adder
2.044
972185AH1-677 GEN
Adder
3.99
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.932
3145783HORNRTN
Solar/Wind Harmer
0.745
3145783HORNRTN
Solar/Wind Harmer
0.233
3145783HORNRTN
Solar/Wind Harmer
0.093
316365GEN2_N
Solar/Wind Harmer
0.501
3144356SAPONY
Solar/Wind Harmer
0.256
316315AB2-025 C
Solar/Wind Harmer
0.198
962571AG1-106 GEN
Solar/Wind Harmer
1.033
3145893MURPHYS
Solar/Wind Harmer
0.2
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.047
316240AF1-291 C
Solar/Wind Harmer
0.208
944641AF1-129 GEN
Adder
29.302
315742AE1-103 GEN
Solar/Wind Harmer
1.626
316083AB2-161 GEN
Solar/Wind Harmer
1.092
315724AD1-057 GEN
Solar/Wind Harmer
1.315
316349AD2-085 GEN
Solar/Wind Harmer
0.587
316065AD1-022 GEN
Solar/Wind Harmer
3.297
316033AB2-134 GEN
Solar/Wind Harmer
2.102
315835AF2-110_GEN
Solar/Wind Harmer
0.816
315614AA2-178 GEN
Solar/Wind Harmer
0.702
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316049AB1-081 GEN
Solar/Wind Harmer
0.696
316263AC1-034 GEN
Solar/Wind Harmer
3.034
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.167
316433W1029_GEN2
Solar/Wind Harmer
1.167
316435W1029_GEN3
Solar/Wind Harmer
1.167
961601AG1-000A GEN
Solar/Wind Harmer
2.525
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
0.755
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.43
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3150991CHESPKB
Adder
0.594
3150991CHESPKB
Adder
0.58
316005AA1-067
Solar/Wind Harmer
0.128
966001AG1-469 GEN
Solar/Wind Helper
0.182
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.077
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
1.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.607
CPLELTFEXP_CPLE->PJM
CLTF
3.66
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.81
MECLTFEXP_MEC->PJM
CLTF
0.061
NYPJM->LTFIMP_NY
CLTF
0.429

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.66 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:805.35
MW Contribution:
16.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.808
972205AH1-687 GEN
50/50
21.963
316303AF2-085
50/50
2.099
3151541CLOVER2
50/50
2.397
3151601KERR 3
50/50
0.215
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
963041AG1-153 GEN
50/50
2.149
315244AE2-183_ST
50/50
2.291
3151281ROARAP4
50/50
0.085
971285AH1-108 GEN
50/50
0.591
315779AE2-040
50/50
0.989
971845AH1-439 GEN
Solar/Wind Harmer
17.227
316258AE1-075 C
Solar/Wind Harmer
0.197
946301AF1-294 GEN
Solar/Wind Harmer
4.161
961791AG1-021 GEN
Solar/Wind Harmer
2.024
3144303KENBRDG
Solar/Wind Harmer
0.138
970683AG2-441 GEN
Solar/Wind Harmer
9.631
970681AG2-440 GEN
Solar/Wind Harmer
6.392
316486AD2-202 GEN
Solar/Wind Harmer
0.114
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.36
971283AH1-107 GEN
Solar/Wind Harmer
1.36
970831AG2-522 GEN
Solar/Wind Harmer
3.97
3147173SINAI
Solar/Wind Harmer
0.089
3147243WELCO
Solar/Wind Harmer
0.056
971967AH1-528 GEN
Solar/Wind Harmer
14.085
970673AG2-436 GEN
Solar/Wind Harmer
9.882
970533AG2-339 GEN
Solar/Wind Harmer
5.967
3137643SOCKMAN
Solar/Wind Harmer
0.308
970085AG2-068 GEN
Solar/Wind Harmer
4.081
970581AG2-369 GEN
Solar/Wind Harmer
3.51
316426AA2-053 GEN
Solar/Wind Harmer
0.249
3146043SEABORD
Solar/Wind Harmer
0.073
315814AE2-033 C
Solar/Wind Harmer
5.613
315652AC1-086 GEN
Solar/Wind Harmer
7.598
316274AC1-208 GEN
Solar/Wind Harmer
0.355
3145893MURPHYS
Solar/Wind Harmer
0.186
3145893MURPHYS
Solar/Wind Harmer
0.069
3145796HORNRTN
Solar/Wind Harmer
0.218
3145796HORNRTN
Solar/Wind Harmer
0.027
316210AC1-098 GEN
Solar/Wind Harmer
0.627
3146033SCOT NK
Solar/Wind Harmer
0.27
316463AE2-346 GEN
Solar/Wind Harmer
0.057
3145513AHOSKIE
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.133
3145683EARLEYS
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.067
316327AA2-057 GEN
Solar/Wind Harmer
0.097
3146206CASHIE
Solar/Wind Harmer
0.064
970601AG2-382 GEN
Solar/Wind Harmer
2.394
315732AD1-074 GEN1
Solar/Wind Harmer
0.362
315733AD1-074 GEN2
Solar/Wind Harmer
0.362
3143316POE
Solar/Wind Harmer
0.252
3130546PLYMOUTH
Solar/Wind Harmer
0.064
970657AG2-426 GEN
Solar/Wind Harmer
0.466
316311AC2-079 GEN
Solar/Wind Harmer
1.819
3130156CHOWAN
Solar/Wind Harmer
0.063
3130156CHOWAN
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.173
313526AB2-022
Solar/Wind Harmer
0.033
3146406KITTY HAWK
Solar/Wind Harmer
0.008
957871AF2-081 GEN
Solar/Wind Harmer
3.112
316316AC1-027 C
Solar/Wind Harmer
0.059
3151081ELIZAR1
Adder
5.701
3151091ELIZAR2
Adder
5.602
3145573BETHELC
Solar/Wind Harmer
0.062
3145573BETHELC
Solar/Wind Harmer
0.062
957861AF2-080 GEN
Solar/Wind Harmer
2.662
3145746EVERETS
Solar/Wind Harmer
0.245
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
971445AH1-216 GEN
Solar/Wind Harmer
4.283
315697AD1-025 GEN
Solar/Wind Harmer
0.064
3151201GRAVEL4
Adder
4.378
970909AG2-566 GEN
50/50
2.507
3144293JTRSVLE
50/50
0.534
970535AG2-341 GEN
50/50
2.068
3151581KERR 1
50/50
0.077
3152661PLYWOOD A
50/50
0.21
3151041BRUNSWICKG3
50/50
1.061
972187AH1-678 GEN
50/50
2.435
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.315
972185AH1-677 GEN
50/50
4.769
3151261ROARAP2
50/50
0.091
3146776BUCKING
Solar/Wind Harmer
1.546
3146776BUCKING
Solar/Wind Harmer
0.125
316336AC2-165 C
Solar/Wind Harmer
15.338
316313AB2-026
Solar/Wind Harmer
0.165
970301AG2-198 GEN
Solar/Wind Harmer
10.027
958211AF2-115 GEN
Solar/Wind Harmer
2.53
3147133PAMPLIN
Solar/Wind Harmer
0.204
3147133PAMPLIN
Solar/Wind Harmer
0.163
970323AG2-213 GEN
Solar/Wind Harmer
7.367
971223AH1-071 GEN
Solar/Wind Harmer
1.259
970099AG2-077 GEN
Solar/Wind Harmer
12.06
962561AG1-105 GEN
Solar/Wind Harmer
5.245
964791AG1-342 GEN
Solar/Wind Harmer
2.031
3151911BEARGRDN G1
50/50
4.495
3144293JTRSVLE
50/50
0.534
3144293JTRSVLE
50/50
0.422
970119AG2-088 GEN
50/50
15.744
3151531CLOVER1
50/50
2.414
3151591KERR 2
50/50
0.215
3151641KERR 7
50/50
0.215
3147043LAWRENC
50/50
0.914
3151051BRUNSWICKS1
50/50
2.203
3151021BRUNSWICKG1
50/50
1.061
971451AH1-221 GEN
50/50
3.223
315243AE2-183_GT3
50/50
1.321
3151281ROARAP4
50/50
0.091
3150851SPRUNCC
50/50
0.361
3151391GASTONA
50/50
0.185
3151411GASTONB
50/50
0.185
970937AG2-583 GEN
Solar/Wind Harmer
24.603
3146776BUCKING
Solar/Wind Harmer
0.155
3146926FARMVIL
Solar/Wind Harmer
0.184
3143336POWHATN
Solar/Wind Harmer
4.701
3151921BEARGRDN G2
50/50
4.495
3144293JTRSVLE
50/50
0.534
970413AG2-270 GEN
50/50
10.515
3151031BRUNSWICKG2
50/50
1.061
3151261ROARAP2
50/50
0.094
3150861SPRUNCD
50/50
0.361
3151391GASTONA
50/50
0.185
3151411GASTONB
50/50
0.185
972003AH1-546 GEN
Solar/Wind Harmer
16.394
3146776BUCKING
Solar/Wind Harmer
0.139
3146926FARMVIL
Solar/Wind Harmer
0.184
3143336POWHATN
Solar/Wind Harmer
3.996
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.64
970257AG2-171 GEN
Solar/Wind Harmer
5.525
971775AH1-396 GEN
Solar/Wind Harmer
0.276
959311AF2-222 GEN
Solar/Wind Harmer
13.645
964241AG1-285 GEN
Solar/Wind Harmer
9.212
970221AG2-151 GEN
Solar/Wind Harmer
6.773
316478AD1-087 GEN
Solar/Wind Harmer
0.389
270494AE1-108_GEN
Solar/Wind Harmer
1.182
3147043LAWRENC
Solar/Wind Harmer
0.057
944011AF1-069 GEN
Solar/Wind Harmer
4.752
316181AB2-040 GEN
Solar/Wind Harmer
0.112
970917AG2-570 GEN
Solar/Wind Harmer
6.894
971683AH1-343 GEN
Solar/Wind Harmer
2.8
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.069
316011AB1-132 GEN
Solar/Wind Harmer
1.253
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3145893MURPHYS
Solar/Wind Harmer
0.115
3145893MURPHYS
Solar/Wind Harmer
0.069
3145796HORNRTN
Solar/Wind Harmer
0.272
3145796HORNRTN
Solar/Wind Harmer
0.068
316212AC1-099_GEN
Solar/Wind Harmer
0.35
3146173TUNIS
Solar/Wind Harmer
0.068
3145823KELFORD
Solar/Wind Harmer
0.067
3145273HOLLAND
Solar/Wind Harmer
0.049
315722AD1-056 GEN
Solar/Wind Harmer
2.24
3146233WITAKRS
Solar/Wind Harmer
0.322
3146233WITAKRS
Solar/Wind Harmer
0.044
3146206CASHIE
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.042
316222AC1-221 GEN
Solar/Wind Harmer
0.263
315735AD1-075 GEN1
Solar/Wind Harmer
0.181
315813AE1-149 C
Solar/Wind Harmer
3.388
970657AG2-426 GEN
Solar/Wind Harmer
1.423
3146376EDENTON
Solar/Wind Harmer
0.063
316283AC2-100 C
Solar/Wind Harmer
0.123
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.011
3145963POPLR C
Solar/Wind Harmer
0.063
316246AF1-032 C
Solar/Wind Harmer
0.028
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.062
971153AH1-033 GEN
Solar/Wind Harmer
0.723
316017AA1-139 ULT1
Solar/Wind Harmer
0.033
971623AH1-311 GEN
Solar/Wind Harmer
0.125
944581AF1-123 GEN
Solar/Wind Harmer
14.049
944601AF1-125 GEN
Solar/Wind Harmer
13.832
3151101ELIZAR3
Adder
5.774
3144873MCLAUGH
Solar/Wind Harmer
0.002
961601AG1-000A GEN
Solar/Wind Harmer
4.415
3145933PARMELE
Solar/Wind Harmer
0.062
3146073TAR RVR
Solar/Wind Harmer
0.062
3146083TARBORO
Solar/Wind Harmer
0.062
3144536CHRHLND
Solar/Wind Harmer
0.009
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
3145336SMITFLD
Solar/Wind Harmer
0.024
316123AC1-075 GEN
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
0.581
316458AB2-190 GEN2
Solar/Wind Harmer
0.322
315778AD1-151 GEN
Solar/Wind Harmer
4.826
961611AG1-000B GEN
Solar/Wind Harmer
1.605
3151171GRAVELC
Adder
0.841
3143096IRON208
Adder
0.248
3143096IRON208
Adder
0.243
3148013FISHERV
Solar/Wind Helper
0.179
316499AE2-029_GEN
Solar/Wind Helper
0.52
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.259
3146843MT LREL
Solar/Wind Harmer
0.106
3146843MT LREL
Solar/Wind Harmer
0.106
3143526WINTERP
Solar/Wind Harmer
0.509
316118AC1-105 GEN
Solar/Wind Harmer
0.25
970933AG2-581 GEN
Solar/Wind Harmer
7.587
313506AB2-031 GEN
Solar/Wind Harmer
0.241
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.095
3145783HORNRTN
Solar/Wind Harmer
1.334
3145783HORNRTN
Solar/Wind Harmer
1.067
3145783HORNRTN
Solar/Wind Harmer
0.333
3145783HORNRTN
Solar/Wind Harmer
0.133
316365GEN2_N
Solar/Wind Harmer
0.159
3144356SAPONY
Solar/Wind Harmer
0.593
316315AB2-025 C
Solar/Wind Harmer
0.057
962571AG1-106 GEN
Solar/Wind Harmer
0.983
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.461
3145893MURPHYS
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.204
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
316140AB2-099
Solar/Wind Harmer
0.024
315742AE1-103 GEN
Solar/Wind Harmer
0.988
315724AD1-057 GEN
Solar/Wind Harmer
1.249
316065AD1-022 GEN
Solar/Wind Harmer
2.944
315614AA2-178 GEN
Solar/Wind Harmer
0.361
316349AD2-085 GEN
Solar/Wind Harmer
0.042
315835AF2-110_GEN
Solar/Wind Harmer
0.434
3146376EDENTON
Solar/Wind Harmer
0.281
3146376EDENTON
Solar/Wind Harmer
0.281
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146386ELIZ CT
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.25
3137176SLIGO L2192
Solar/Wind Harmer
0.249
3146456SLIGO L269
Solar/Wind Harmer
1.106
316049AB1-081 GEN
Solar/Wind Harmer
0.356
316339AD2-160 GEN
Solar/Wind Harmer
0.1
316388AE2-253 GEN
Solar/Wind Harmer
0.194
316263AC1-034 GEN
Solar/Wind Harmer
2.375
3145506HICKORY
Solar/Wind Harmer
0.25
3145506HICKORY
Solar/Wind Harmer
0.15
3145506HICKORY
Solar/Wind Harmer
0.037
3150991CHESPKB
Adder
0.651
3150991CHESPKB
Adder
0.636
961601AG1-000A GEN
Solar/Wind Harmer
1.104
3145933PARMELE
Solar/Wind Harmer
0.124
3145933PARMELE
Solar/Wind Harmer
0.062
3145493TOT1
Solar/Wind Harmer
0.143
3145453TOT5
Solar/Wind Harmer
0.086
3145603CNETO
Solar/Wind Harmer
0.057
316005AA1-067
Solar/Wind Harmer
0.066
316294AC1-161 GEN
Solar/Wind Harmer
1.057
944641AF1-129 GEN
Adder
29.012
316033AB2-134 GEN
Solar/Wind Harmer
0
966001AG1-469 GEN
Solar/Wind Helper
0.186
3151221GRAVEL6
Adder
4.373
3151191GRAVEL3
Adder
4.322
3151211GRAVEL5
Adder
4.322
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.107
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
315616AA1-038_C
Solar/Wind Helper
0.562
971563AH1-280 GEN
Solar/Wind Harmer
2.249
970685AG2-442 GEN
Solar/Wind Harmer
12.826
315785AD2-033 C
Solar/Wind Harmer
1.334
316034AC1-036 C
Solar/Wind Harmer
0.01
315693AD1-088 GEN
Solar/Wind Harmer
6.634
316131AB2-060 GEN
Solar/Wind Harmer
0.41
971377AH1-170 GEN
Solar/Wind Harmer
1.355
3147623JAMES R
Solar/Wind Harmer
0.294
3143226MDLTHAN
Solar/Wind Harmer
0.118
957481AF2-042 GEN
Solar/Wind Harmer
30.149
970401AG2-262 GEN
Solar/Wind Harmer
0.621
3143526WINTERP
Solar/Wind Harmer
0.509
971065AG2-659 GEN
Solar/Wind Harmer
4.138
316129AC1-054 GEN
Solar/Wind Harmer
0.356
960081AF2-299 GEN
Solar/Wind Harmer
0.774
941031AE2-094 GEN
Solar/Wind Harmer
14.545
970919AG2-571 GEN
Solar/Wind Harmer
2.758
970087AG2-069 GEN
Solar/Wind Harmer
6.122
3145783HORNRTN
Solar/Wind Harmer
0.075
940641AE2-051 GEN
Solar/Wind Harmer
5.96
315607AA1-063A GEN
Solar/Wind Harmer
0.148
316023GEN1_S
Solar/Wind Harmer
0.159
939411AE1-173 GEN
Solar/Wind Harmer
30.495
3146263WOODLND
Solar/Wind Harmer
0.069
3145893MURPHYS
Solar/Wind Harmer
0.275
3145893MURPHYS
Solar/Wind Harmer
0.306
3145796HORNRTN
Solar/Wind Harmer
0.225
3145796HORNRTN
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
3145823KELFORD
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.067
3156021HOLLOMANSOL
Solar/Wind Harmer
0.292
3146233WITAKRS
Solar/Wind Harmer
0.256
3146206CASHIE
Solar/Wind Harmer
0.064
971547AH1-271 GEN
Solar/Wind Harmer
1.368
315737AD1-076 GEN
Solar/Wind Harmer
0.816
316381AD1-082 GEN
Solar/Wind Harmer
0.064
315816AE2-034 GEN
Solar/Wind Harmer
0.27
3145663CRESWEL
Solar/Wind Harmer
0.177
971163AH1-040 GEN
Solar/Wind Harmer
5.071
316093AE2-104_GEN
Solar/Wind Harmer
1.064
3130156CHOWAN
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.204
3146516WINFALL
Solar/Wind Harmer
0.063
3145963POPLR C
Solar/Wind Harmer
0.063
3142543TWELFTH
Solar/Wind Harmer
0.006
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
319010AE1-072 C
Solar/Wind Harmer
0.311
3146456SLIGO L269
Solar/Wind Harmer
0.062
316359AB2-059 GEN
Solar/Wind Harmer
0.222
3142053HEARTS
Solar/Wind Harmer
0.11
944591AF1-124 GEN
Solar/Wind Harmer
14.099
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150981CHESPKA
Adder
0.776
3146293MARTNCO
Solar/Wind Harmer
0.057
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.062
3145493TOT1
Solar/Wind Harmer
0.275
316494AC1-189 GEN
Solar/Wind Harmer
0.209
316072AD1-144
Solar/Wind Harmer
0.022
315671AE2-027_GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
315773AC2-141 GEN
Solar/Wind Harmer
2.232
3145336SMITFLD
Solar/Wind Harmer
0.244
316132AB2-190 GEN1
Solar/Wind Harmer
0.322
971069AG2-661 GEN
Solar/Wind Harmer
1.073
961611AG1-000B GEN
Solar/Wind Harmer
3.157
3151171GRAVELC
Adder
0.64
3143096IRON208
Adder
0.248
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.785
3147666LOUISA
Solar/Wind Helper
0.45
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.062
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.167
LAGNLTFEXP_LAGN->PJM
CLTF
1.43
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.724
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.695
CPLELTFEXP_CPLE->PJM
CLTF
4.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.187
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.099
MECLTFEXP_MEC->PJM
CLTF
0.124
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.461

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.08 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:740.31
MW Contribution:
21.7
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.43 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:939.5
MW Contribution:
21.78
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
3151531CLOVER1
50/50
2.212
3151591KERR 2
50/50
0.2
3151641KERR 7
50/50
0.2
3147043LAWRENC
50/50
0.756
970937AG2-583 GEN
Solar/Wind Harmer
39.417
3146776BUCKING
Solar/Wind Harmer
0.2
3146926FARMVIL
Solar/Wind Harmer
0.23
971377AH1-170 GEN
Solar/Wind Harmer
2.854
3147623JAMES R
Solar/Wind Harmer
0.62
971563AH1-280 GEN
Solar/Wind Harmer
2.631
970685AG2-442 GEN
Solar/Wind Harmer
14.043
315785AD2-033 C
Solar/Wind Harmer
1.465
316034AC1-036 C
Solar/Wind Harmer
0.011
315693AD1-088 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.416
970401AG2-262 GEN
Solar/Wind Harmer
0.601
957481AF2-042 GEN
Solar/Wind Harmer
26.83
971065AG2-659 GEN
Solar/Wind Harmer
3.622
316129AC1-054 GEN
Solar/Wind Harmer
0.307
960081AF2-299 GEN
Solar/Wind Harmer
0.544
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
970535AG2-341 GEN
50/50
2.001
3151581KERR 1
50/50
0.071
3152661PLYWOOD A
50/50
0.197
316336AC2-165 C
Solar/Wind Harmer
32.562
3146776BUCKING
Solar/Wind Harmer
2.001
3146776BUCKING
Solar/Wind Harmer
0.162
970301AG2-198 GEN
Solar/Wind Harmer
11.924
958211AF2-115 GEN
Solar/Wind Harmer
2.96
3147133PAMPLIN
Solar/Wind Harmer
0.235
3147133PAMPLIN
Solar/Wind Harmer
0.188
970323AG2-213 GEN
Solar/Wind Harmer
8.199
962561AG1-105 GEN
Solar/Wind Harmer
5.114
964791AG1-342 GEN
Solar/Wind Harmer
1.967
3146843MT LREL
Solar/Wind Harmer
0.102
3146843MT LREL
Solar/Wind Harmer
0.102
970099AG2-077 GEN
Solar/Wind Harmer
10.732
316118AC1-105 GEN
Solar/Wind Harmer
0.237
970933AG2-581 GEN
Solar/Wind Harmer
5.491
966001AG1-469 GEN
Solar/Wind Helper
0.139
972205AH1-687 GEN
50/50
29.134
3151541CLOVER2
50/50
2.196
3151601KERR 3
50/50
0.2
3151611KERR 4
50/50
0.2
3151621KERR 5
50/50
0.2
3151631KERR 6
50/50
0.2
971845AH1-439 GEN
Solar/Wind Harmer
22.245
946301AF1-294 GEN
Solar/Wind Harmer
4.868
961791AG1-021 GEN
Solar/Wind Harmer
2.368
3144303KENBRDG
Solar/Wind Harmer
0.154
970683AG2-441 GEN
Solar/Wind Harmer
10.284
970681AG2-440 GEN
Solar/Wind Harmer
6.826
316486AD2-202 GEN
Solar/Wind Harmer
0.105
3147173SINAI
Solar/Wind Harmer
0.083
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.367
971967AH1-528 GEN
Solar/Wind Harmer
9.13
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
970413AG2-270 GEN
50/50
9.635
972003AH1-546 GEN
Solar/Wind Harmer
21.695
3146776BUCKING
Solar/Wind Harmer
0.18
3146926FARMVIL
Solar/Wind Harmer
0.23
942461AE2-259 GEN
Solar/Wind Harmer
0.001
970221AG2-151 GEN
Solar/Wind Harmer
14.27
3147133PAMPLIN
Solar/Wind Harmer
0.737
270494AE1-108_GEN
Solar/Wind Harmer
2.499
970257AG2-171 GEN
Solar/Wind Harmer
6.149
971775AH1-396 GEN
Solar/Wind Harmer
0.307
959311AF2-222 GEN
Solar/Wind Harmer
14.386
964241AG1-285 GEN
Solar/Wind Harmer
9.36
315821AE2-092 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.357
958131AF2-107 GEN
Solar/Wind Harmer
2.368
3147043LAWRENC
Solar/Wind Harmer
0.047
971683AH1-343 GEN
Solar/Wind Harmer
2.656
316123AC1-075 GEN
Solar/Wind Harmer
0.079
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.11 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:847.48
MW Contribution:
28.57
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.35 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1056.99
MW Contribution:
28.68
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
972003AH1-546 GEN
Solar/Wind Harmer
28.565
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.235
970221AG2-151 GEN
Solar/Wind Harmer
18.789
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270494AE1-108_GEN
Solar/Wind Harmer
6.111
970257AG2-171 GEN
Solar/Wind Harmer
8.096
972205AH1-687 GEN
50/50
29.134
316322AB2-045
Solar/Wind Harmer
1.888
971845AH1-439 GEN
Solar/Wind Harmer
29.289
946301AF1-294 GEN
Solar/Wind Harmer
7.102
961791AG1-021 GEN
Solar/Wind Harmer
3.465
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
13.541
970681AG2-440 GEN
Solar/Wind Harmer
8.987
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316486AD2-202 GEN
Solar/Wind Harmer
0.293
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.433
971967AH1-528 GEN
Solar/Wind Harmer
12.053
946281AF1-292 GEN
Solar/Wind Harmer
0.143
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
970937AG2-583 GEN
Solar/Wind Harmer
51.899
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.758
3147623JAMES R
Solar/Wind Harmer
0.465
971563AH1-280 GEN
Solar/Wind Harmer
3.465
970685AG2-442 GEN
Solar/Wind Harmer
18.491
315785AD2-033 C
Solar/Wind Harmer
4.603
316034AC1-036 C
Solar/Wind Harmer
0.329
315693AD1-088 GEN
Solar/Wind Harmer
7.766
316131AB2-060 GEN
Solar/Wind Harmer
1.615
970401AG2-262 GEN
Solar/Wind Harmer
0.751
957481AF2-042 GEN
Solar/Wind Harmer
35.327
971065AG2-659 GEN
Solar/Wind Harmer
4.769
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.712
960081AF2-299 GEN
Solar/Wind Harmer
0.716
971775AH1-396 GEN
Solar/Wind Harmer
1.523
959311AF2-222 GEN
Solar/Wind Harmer
18.979
964241AG1-285 GEN
Solar/Wind Harmer
12.324
315821AE2-092 GEN
Solar/Wind Harmer
2.69
316478AD1-087 GEN
Solar/Wind Harmer
0.999
958131AF2-107 GEN
Solar/Wind Harmer
3.152
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.854
971683AH1-343 GEN
Solar/Wind Harmer
3.498
316123AC1-075 GEN
Solar/Wind Harmer
0.72
966621AG1-532 GEN
Solar/Wind Harmer
0.129
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
970535AG2-341 GEN
50/50
2.001
316336AC2-165 C
Solar/Wind Harmer
45.084
3146776BUCKING
Solar/Wind Harmer
-0.224
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.7
958211AF2-115 GEN
Solar/Wind Harmer
4.331
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
970323AG2-213 GEN
Solar/Wind Harmer
10.795
313527AB2-043 GEN
Solar/Wind Harmer
2.357
316237AB2-079_GEN
Solar/Wind Harmer
0.426
962561AG1-105 GEN
Solar/Wind Harmer
6.734
964791AG1-342 GEN
Solar/Wind Harmer
2.459
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
14.131
316118AC1-105 GEN
Solar/Wind Harmer
0.714
315687AD1-152 GEN
Solar/Wind Harmer
1.245
316248AF1-058 C
Solar/Wind Harmer
0.281
970933AG2-581 GEN
Solar/Wind Harmer
7.23
966001AG1-469 GEN
Solar/Wind Helper
0.139
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.11 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:847.48
MW Contribution:
28.57
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
29.134
316322AB2-045
Solar/Wind Harmer
1.888
971845AH1-439 GEN
Solar/Wind Harmer
29.289
946301AF1-294 GEN
Solar/Wind Harmer
7.102
961791AG1-021 GEN
Solar/Wind Harmer
3.465
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
13.541
970681AG2-440 GEN
Solar/Wind Harmer
8.987
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316486AD2-202 GEN
Solar/Wind Harmer
0.293
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.433
971967AH1-528 GEN
Solar/Wind Harmer
12.053
946281AF1-292 GEN
Solar/Wind Harmer
0.143
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
972003AH1-546 GEN
Solar/Wind Harmer
28.565
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.235
970221AG2-151 GEN
Solar/Wind Harmer
18.789
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270494AE1-108_GEN
Solar/Wind Harmer
6.111
970257AG2-171 GEN
Solar/Wind Harmer
8.096
971775AH1-396 GEN
Solar/Wind Harmer
1.523
959311AF2-222 GEN
Solar/Wind Harmer
18.979
964241AG1-285 GEN
Solar/Wind Harmer
12.324
315821AE2-092 GEN
Solar/Wind Harmer
2.69
316478AD1-087 GEN
Solar/Wind Harmer
0.999
958131AF2-107 GEN
Solar/Wind Harmer
3.152
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.854
971683AH1-343 GEN
Solar/Wind Harmer
3.498
316123AC1-075 GEN
Solar/Wind Harmer
0.72
966621AG1-532 GEN
Solar/Wind Harmer
0.129
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
970937AG2-583 GEN
Solar/Wind Harmer
51.899
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.758
3147623JAMES R
Solar/Wind Harmer
0.465
971563AH1-280 GEN
Solar/Wind Harmer
3.465
970685AG2-442 GEN
Solar/Wind Harmer
18.491
315785AD2-033 C
Solar/Wind Harmer
4.603
316034AC1-036 C
Solar/Wind Harmer
0.329
315693AD1-088 GEN
Solar/Wind Harmer
7.766
316131AB2-060 GEN
Solar/Wind Harmer
1.615
970401AG2-262 GEN
Solar/Wind Harmer
0.751
957481AF2-042 GEN
Solar/Wind Harmer
35.327
971065AG2-659 GEN
Solar/Wind Harmer
4.769
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.712
960081AF2-299 GEN
Solar/Wind Harmer
0.716
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
970535AG2-341 GEN
50/50
2.001
316336AC2-165 C
Solar/Wind Harmer
45.084
3146776BUCKING
Solar/Wind Harmer
-0.224
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.7
958211AF2-115 GEN
Solar/Wind Harmer
4.331
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
970323AG2-213 GEN
Solar/Wind Harmer
10.795
313527AB2-043 GEN
Solar/Wind Harmer
2.357
316237AB2-079_GEN
Solar/Wind Harmer
0.426
962561AG1-105 GEN
Solar/Wind Harmer
6.734
964791AG1-342 GEN
Solar/Wind Harmer
2.459
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
14.131
316118AC1-105 GEN
Solar/Wind Harmer
0.714
315687AD1-152 GEN
Solar/Wind Harmer
1.245
316248AF1-058 C
Solar/Wind Harmer
0.281
970933AG2-581 GEN
Solar/Wind Harmer
7.23
966001AG1-469 GEN
Solar/Wind Helper
0.139
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:832.54
MW Contribution:
21.97
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.263
3151541CLOVER2
50/50
3.787
3151601KERR 3
50/50
0.28
3151611KERR 4
50/50
0.28
3151621KERR 5
50/50
0.28
3151631KERR 6
50/50
0.28
316322AB2-045
Solar/Wind Harmer
1.543
971845AH1-439 GEN
Solar/Wind Harmer
24.09
3151921BEARGRDN G2
50/50
4.556
3144293JTRSVLE
50/50
0.637
970413AG2-270 GEN
50/50
16.613
972003AH1-546 GEN
Solar/Wind Harmer
21.973
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.023
942461AE2-259 GEN
Solar/Wind Harmer
5.02
3147133PAMPLIN
Solar/Wind Harmer
-0.089
3143336POWHATN
Solar/Wind Harmer
2.774
970257AG2-171 GEN
Solar/Wind Harmer
9.023
971775AH1-396 GEN
Solar/Wind Harmer
1.698
959311AF2-222 GEN
Solar/Wind Harmer
24.67
964241AG1-285 GEN
Solar/Wind Harmer
16.962
316478AD1-087 GEN
Solar/Wind Harmer
1.722
970221AG2-151 GEN
Solar/Wind Harmer
9.368
316003AC1-222 GEN
Solar/Wind Harmer
1.28
971683AH1-343 GEN
Solar/Wind Harmer
5.189
270494AE1-108_GEN
Solar/Wind Harmer
3.072
3147043LAWRENC
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
1.038
316222AC1-221 GEN
Solar/Wind Harmer
0.852
316283AC2-100 C
Solar/Wind Harmer
0.78
966621AG1-532 GEN
Solar/Wind Harmer
0.163
316181AB2-040 GEN
Solar/Wind Harmer
1.095
316190AA2-174 GEN
Solar/Wind Harmer
0.089
3148013FISHERV
Solar/Wind Helper
0.17
316499AE2-029_GEN
Solar/Wind Helper
0.493
3132273ORANGE
Solar/Wind Helper
0.025
3151931BEARGRDN S1
50/50
5.887
3151911BEARGRDN G1
50/50
4.556
3144293JTRSVLE
50/50
0.637
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
3.815
3151591KERR 2
50/50
0.28
3151641KERR 7
50/50
0.28
3146776BUCKING
Solar/Wind Harmer
-0.018
970937AG2-583 GEN
Solar/Wind Harmer
32.126
3146926FARMVIL
Solar/Wind Harmer
-0.023
971563AH1-280 GEN
Solar/Wind Harmer
3.53
3143336POWHATN
Solar/Wind Harmer
3.264
970685AG2-442 GEN
Solar/Wind Harmer
22.356
316034AC1-036 C
Solar/Wind Harmer
0.432
315785AD2-033 C
Solar/Wind Harmer
5.252
315693AD1-088 GEN
Solar/Wind Harmer
11.47
957481AF2-042 GEN
Solar/Wind Harmer
66.102
316131AB2-060 GEN
Solar/Wind Harmer
2.106
970401AG2-262 GEN
Solar/Wind Harmer
1.061
971377AH1-170 GEN
Solar/Wind Harmer
1.874
3147623JAMES R
Solar/Wind Harmer
0.232
971065AG2-659 GEN
Solar/Wind Harmer
6.58
316129AC1-054 GEN
Solar/Wind Harmer
1.111
3147043LAWRENC
Adder
0.921
3143226MDLTHAN
Solar/Wind Harmer
-0.009
960081AF2-299 GEN
Solar/Wind Harmer
0.903
316087AB2-174 GEN
Solar/Wind Harmer
1.127
3145783HORNRTN
Solar/Wind Harmer
-0.007
3143526WINTERP
Solar/Wind Harmer
-0.038
315607AA1-063A GEN
Solar/Wind Harmer
0.701
3147983MERCK5
Solar/Wind Helper
0.054
946301AF1-294 GEN
Solar/Wind Harmer
7.236
961791AG1-021 GEN
Solar/Wind Harmer
3.53
316258AE1-075 C
Solar/Wind Harmer
0.666
316405AF2-144 C
Solar/Wind Harmer
0.703
970683AG2-441 GEN
Solar/Wind Harmer
17.252
970681AG2-440 GEN
Solar/Wind Harmer
11.45
3144303KENBRDG
Solar/Wind Harmer
-0.019
971967AH1-528 GEN
Solar/Wind Harmer
40.435
316486AD2-202 GEN
Solar/Wind Harmer
0.504
316238AB2-078_GEN
Solar/Wind Harmer
0.568
316239AB2-077_GEN
Solar/Wind Harmer
0.568
3147173SINAI
Solar/Wind Harmer
-0.014
3147243WELCO
Solar/Wind Harmer
-0.009
970831AG2-522 GEN
Solar/Wind Harmer
6.062
946281AF1-292 GEN
Solar/Wind Harmer
0.18
3137643SOCKMAN
Solar/Wind Harmer
-0.031
316233AE1-074 FULL
Solar/Wind Harmer
0.199
971281AH1-106 GEN
Solar/Wind Harmer
1.201
971283AH1-107 GEN
Solar/Wind Harmer
1.201
316426AA2-053 GEN
Solar/Wind Harmer
0.732
3146043SEABORD
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.695
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.102
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.524
970909AG2-566 GEN
50/50
3.024
3144293JTRSVLE
50/50
0.637
970535AG2-341 GEN
50/50
2.722
3151581KERR 1
50/50
0.1
3152661PLYWOOD A
50/50
0.29
3146776BUCKING
Solar/Wind Harmer
-0.183
3146776BUCKING
Solar/Wind Harmer
-0.015
316336AC2-165 C
Solar/Wind Harmer
20.18
970301AG2-198 GEN
Solar/Wind Harmer
15.924
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.412
316313AB2-026
Solar/Wind Harmer
0.74
970323AG2-213 GEN
Solar/Wind Harmer
12.03
970933AG2-581 GEN
Solar/Wind Harmer
20.164
970099AG2-077 GEN
Solar/Wind Harmer
26.441
313527AB2-043 GEN
Solar/Wind Harmer
3.123
316237AB2-079_GEN
Solar/Wind Harmer
0.568
315687AD1-152 GEN
Solar/Wind Harmer
2.079
962561AG1-105 GEN
Solar/Wind Harmer
9.401
964791AG1-342 GEN
Solar/Wind Harmer
3.473
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
316118AC1-105 GEN
Solar/Wind Harmer
1.04
316248AF1-058 C
Solar/Wind Harmer
0.424
971223AH1-071 GEN
Solar/Wind Harmer
1.137
942751AE2-291 GEN
Solar/Wind Harmer
5.435
313506AB2-031 GEN
Solar/Wind Harmer
0.63
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.064
3145783HORNRTN
Solar/Wind Harmer
0.888
3145783HORNRTN
Solar/Wind Harmer
0.71
3145783HORNRTN
Solar/Wind Harmer
0.222
3145783HORNRTN
Solar/Wind Harmer
0.089
3143526WINTERP
Solar/Wind Harmer
-0.038
966001AG1-469 GEN
Solar/Wind Helper
0.179
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.036
LAGNLTFEXP_LAGN->PJM
CLTF
1.317
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.766
TVALTFEXP_TVA->PJM
CLTF
0.645
CPLELTFEXP_CPLE->PJM
CLTF
3.489
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.989
MECLTFEXP_MEC->PJM
CLTF
0.188
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.388
LGEELTFEXP_LGEE->PJM
CLTF
0.003

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.86 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:986.57
MW Contribution:
21.81
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.206
316303AF2-085
50/50
2.484
316322AB2-045
Solar/Wind Harmer
1.467
971845AH1-439 GEN
Solar/Wind Harmer
22.808
316258AE1-075 C
Solar/Wind Harmer
0.76
316405AF2-144 C
Solar/Wind Harmer
0.803
946301AF1-294 GEN
Solar/Wind Harmer
5.991
961791AG1-021 GEN
Solar/Wind Harmer
2.922
3144303KENBRDG
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
12.304
970681AG2-440 GEN
Solar/Wind Harmer
8.167
316238AB2-078_GEN
Solar/Wind Harmer
0.41
316239AB2-077_GEN
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.345
971281AH1-106 GEN
Solar/Wind Harmer
2.085
971283AH1-107 GEN
Solar/Wind Harmer
2.085
316486AD2-202 GEN
Solar/Wind Harmer
0.302
970831AG2-522 GEN
Solar/Wind Harmer
4.94
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.62
971967AH1-528 GEN
Solar/Wind Harmer
16.771
946281AF1-292 GEN
Solar/Wind Harmer
0.19
3137643SOCKMAN
Solar/Wind Harmer
-0.032
970673AG2-436 GEN
Solar/Wind Harmer
17.241
970533AG2-339 GEN
Solar/Wind Harmer
5.254
316426AA2-053 GEN
Solar/Wind Harmer
0.785
970085AG2-068 GEN
Solar/Wind Harmer
4.799
970581AG2-369 GEN
Solar/Wind Harmer
4.127
3146043SEABORD
Solar/Wind Harmer
-0.008
315814AE2-033 C
Solar/Wind Harmer
6.846
315652AC1-086 GEN
Solar/Wind Harmer
8.081
316274AC1-208 GEN
Solar/Wind Harmer
0.772
316318V4-068
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.105
3146033SCOT NK
Solar/Wind Harmer
-0.028
315839AE2-212 C
Solar/Wind Harmer
0.21
316463AE2-346 GEN
Solar/Wind Harmer
0.112
3145513AHOSKIE
Solar/Wind Harmer
0.061
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.689
970657AG2-426 GEN
Solar/Wind Harmer
0.424
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.894
315833AF1-017_GEN
Solar/Wind Harmer
1.255
316311AC2-079 GEN
Solar/Wind Harmer
3.332
315732AD1-074 GEN1
Solar/Wind Harmer
1.322
315733AD1-074 GEN2
Solar/Wind Harmer
1.322
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315697AD1-025 GEN
Solar/Wind Harmer
1.317
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.601
316174AB2-169 GEN
Solar/Wind Harmer
0.993
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3151921BEARGRDN G2
50/50
4.545
3144293JTRSVLE
50/50
0.527
972003AH1-546 GEN
Solar/Wind Harmer
21.813
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.168
942461AE2-259 GEN
Solar/Wind Harmer
4.286
3147133PAMPLIN
Solar/Wind Harmer
-0.07
970257AG2-171 GEN
Solar/Wind Harmer
7.117
971775AH1-396 GEN
Solar/Wind Harmer
1.339
959311AF2-222 GEN
Solar/Wind Harmer
17.432
964241AG1-285 GEN
Solar/Wind Harmer
11.676
970221AG2-151 GEN
Solar/Wind Harmer
9.255
316478AD1-087 GEN
Solar/Wind Harmer
1.032
270494AE1-108_GEN
Solar/Wind Harmer
2.999
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.379
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.172
316181AB2-040 GEN
Solar/Wind Harmer
1.147
971683AH1-343 GEN
Solar/Wind Harmer
3.493
944011AF1-069 GEN
Solar/Wind Harmer
4.59
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970917AG2-570 GEN
Solar/Wind Harmer
19.442
3156081AA2-088 GEN
Solar/Wind Harmer
2.348
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.5
3145893MURPHYS
Solar/Wind Harmer
0.05
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.265
3143096IRON208
Adder
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.614
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.322
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.26
3145273HOLLAND
Solar/Wind Harmer
-0.005
970657AG2-426 GEN
Solar/Wind Harmer
1.358
970133AG2-095 GEN
Solar/Wind Harmer
0.756
315722AD1-056 GEN
Solar/Wind Harmer
2.391
3146233WITAKRS
Solar/Wind Harmer
0.139
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.004
316458AB2-190 GEN2
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.62
315778AD1-151 GEN
Solar/Wind Harmer
5.844
315735AD1-075 GEN1
Solar/Wind Harmer
0.661
3146376EDENTON
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316123AC1-075 GEN
Solar/Wind Harmer
0.697
3145963POPLR C
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
1.355
316305AF2-043 C
Solar/Wind Harmer
0.193
316246AF1-032 C
Solar/Wind Harmer
0.13
316321Z2-027
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
2.557
316320Y1-086
Solar/Wind Harmer
0.376
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.74
316420AA1-050 GEN
Solar/Wind Harmer
0.728
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
3145933PARMELE
Solar/Wind Harmer
-0.006
3142956BIRDNECK
Solar/Wind Harmer
0.342
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
28.996
944601AF1-125 GEN
Solar/Wind Harmer
28.543
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.266
3151171GRAVELC
Adder
0.794
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.511
3132273ORANGE
Solar/Wind Helper
0.026
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
957871AF2-081 GEN
Solar/Wind Harmer
3.196
957861AF2-080 GEN
Solar/Wind Harmer
2.791
316316AC1-027 C
Solar/Wind Harmer
0.195
316236AE1-162_GEN
Solar/Wind Harmer
0.192
3151081ELIZAR1
Adder
5.199
3151091ELIZAR2
Adder
5.109
971445AH1-216 GEN
Solar/Wind Harmer
3.943
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.122
315616AA1-038_C
Solar/Wind Helper
0.552
3151931BEARGRDN S1
50/50
5.872
3151911BEARGRDN G1
50/50
4.545
3144293JTRSVLE
50/50
0.527
3144293JTRSVLE
50/50
0.416
970119AG2-088 GEN
50/50
18.628
970937AG2-583 GEN
Solar/Wind Harmer
33.126
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.727
971563AH1-280 GEN
Solar/Wind Harmer
2.922
970685AG2-442 GEN
Solar/Wind Harmer
16.459
315785AD2-033 C
Solar/Wind Harmer
4.092
316034AC1-036 C
Solar/Wind Harmer
0.304
3143226MDLTHAN
Solar/Wind Harmer
-0.016
315693AD1-088 GEN
Solar/Wind Harmer
7.448
971377AH1-170 GEN
Solar/Wind Harmer
1.851
3147623JAMES R
Solar/Wind Harmer
0.229
316131AB2-060 GEN
Solar/Wind Harmer
1.533
3143526WINTERP
Solar/Wind Harmer
-0.066
957481AF2-042 GEN
Solar/Wind Harmer
37.368
970401AG2-262 GEN
Solar/Wind Harmer
0.741
971065AG2-659 GEN
Solar/Wind Harmer
5.161
316129AC1-054 GEN
Solar/Wind Harmer
0.886
3147043LAWRENC
Adder
0.815
3150851SPRUNCC
Adder
0.379
960081AF2-299 GEN
Solar/Wind Harmer
0.953
316087AB2-174 GEN
Solar/Wind Harmer
1.183
3145783HORNRTN
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
14.649
970919AG2-571 GEN
Solar/Wind Harmer
2.461
315607AA1-063A GEN
Solar/Wind Harmer
0.776
970087AG2-069 GEN
Solar/Wind Harmer
7.198
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.501
940641AE2-051 GEN
Solar/Wind Harmer
6.871
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.212
3143096IRON208
Adder
0.265
939411AE1-173 GEN
Solar/Wind Harmer
35.461
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.242
316381AD1-082 GEN
Solar/Wind Harmer
0.616
3156021HOLLOMANSOL
Solar/Wind Harmer
0.9
316319Z2-044 C
Solar/Wind Harmer
0.368
3146233WITAKRS
Solar/Wind Harmer
-0.026
316132AB2-190 GEN1
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.654
971069AG2-661 GEN
Solar/Wind Harmer
1.039
315737AD1-076 GEN
Solar/Wind Harmer
1.244
316369SG1_INVT
Solar/Wind Harmer
1.164
316093AE2-104_GEN
Solar/Wind Harmer
1.898
315816AE2-034 GEN
Solar/Wind Harmer
0.526
3145663CRESWEL
Solar/Wind Harmer
-0.018
971163AH1-040 GEN
Solar/Wind Harmer
6.117
3130156CHOWAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.601
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.87
3142053HEARTS
Solar/Wind Harmer
0.076
3145963POPLR C
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
3.175
944631AF1-128 GEN
Adder
27.172
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
319010AE1-072 C
Solar/Wind Harmer
1.29
3146456SLIGO L269
Solar/Wind Harmer
-0.006
3146293MARTNCO
Solar/Wind Harmer
0.04
316494AC1-189 GEN
Solar/Wind Harmer
0.686
944591AF1-124 GEN
Solar/Wind Harmer
29.1
316375AC2-012 GEN
Solar/Wind Harmer
2.204
316036AC1-147 C
Solar/Wind Harmer
0.171
3150981CHESPKA
Adder
0.708
3145336SMITFLD
Solar/Wind Harmer
-0.025
3151171GRAVELC
Adder
0.603
316072AD1-144
Solar/Wind Harmer
0.128
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.765
970909AG2-566 GEN
50/50
2.48
3144293JTRSVLE
50/50
0.527
3146776BUCKING
Solar/Wind Harmer
-0.174
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.18
316313AB2-026
Solar/Wind Harmer
0.845
970301AG2-198 GEN
Solar/Wind Harmer
13.062
958211AF2-115 GEN
Solar/Wind Harmer
3.653
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
970323AG2-213 GEN
Solar/Wind Harmer
9.489
971223AH1-071 GEN
Solar/Wind Harmer
1.962
313527AB2-043 GEN
Solar/Wind Harmer
2.256
316237AB2-079_GEN
Solar/Wind Harmer
0.41
3143526WINTERP
Solar/Wind Harmer
-0.066
970099AG2-077 GEN
Solar/Wind Harmer
14.947
962561AG1-105 GEN
Solar/Wind Harmer
6.603
964791AG1-342 GEN
Solar/Wind Harmer
2.424
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.294
316118AC1-105 GEN
Solar/Wind Harmer
0.715
970933AG2-581 GEN
Solar/Wind Harmer
9.133
316248AF1-058 C
Solar/Wind Harmer
0.286
313506AB2-031 GEN
Solar/Wind Harmer
0.66
972187AH1-678 GEN
Adder
2.044
972185AH1-677 GEN
Adder
3.99
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.932
3145783HORNRTN
Solar/Wind Harmer
0.745
3145783HORNRTN
Solar/Wind Harmer
0.233
3145783HORNRTN
Solar/Wind Harmer
0.093
316365GEN2_N
Solar/Wind Harmer
0.501
3144356SAPONY
Solar/Wind Harmer
0.256
316315AB2-025 C
Solar/Wind Harmer
0.198
962571AG1-106 GEN
Solar/Wind Harmer
1.033
3145893MURPHYS
Solar/Wind Harmer
0.2
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.047
316240AF1-291 C
Solar/Wind Harmer
0.208
944641AF1-129 GEN
Adder
29.302
315742AE1-103 GEN
Solar/Wind Harmer
1.626
316083AB2-161 GEN
Solar/Wind Harmer
1.092
315724AD1-057 GEN
Solar/Wind Harmer
1.315
316349AD2-085 GEN
Solar/Wind Harmer
0.587
316065AD1-022 GEN
Solar/Wind Harmer
3.297
316033AB2-134 GEN
Solar/Wind Harmer
2.102
315835AF2-110_GEN
Solar/Wind Harmer
0.816
315614AA2-178 GEN
Solar/Wind Harmer
0.702
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316049AB1-081 GEN
Solar/Wind Harmer
0.696
316263AC1-034 GEN
Solar/Wind Harmer
3.034
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.167
316433W1029_GEN2
Solar/Wind Harmer
1.167
316435W1029_GEN3
Solar/Wind Harmer
1.167
961601AG1-000A GEN
Solar/Wind Harmer
2.525
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
0.755
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.43
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3150991CHESPKB
Adder
0.594
3150991CHESPKB
Adder
0.58
316005AA1-067
Solar/Wind Harmer
0.128
966001AG1-469 GEN
Solar/Wind Helper
0.182
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.077
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
1.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.607
CPLELTFEXP_CPLE->PJM
CLTF
3.66
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.81
MECLTFEXP_MEC->PJM
CLTF
0.061
NYPJM->LTFIMP_NY
CLTF
0.429

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.86 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:986.57
MW Contribution:
21.81
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.48
3144293JTRSVLE
50/50
0.527
3146776BUCKING
Solar/Wind Harmer
-0.174
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.18
316313AB2-026
Solar/Wind Harmer
0.845
970301AG2-198 GEN
Solar/Wind Harmer
13.062
958211AF2-115 GEN
Solar/Wind Harmer
3.653
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
970323AG2-213 GEN
Solar/Wind Harmer
9.489
971223AH1-071 GEN
Solar/Wind Harmer
1.962
313527AB2-043 GEN
Solar/Wind Harmer
2.256
316237AB2-079_GEN
Solar/Wind Harmer
0.41
3143526WINTERP
Solar/Wind Harmer
-0.066
970099AG2-077 GEN
Solar/Wind Harmer
14.947
962561AG1-105 GEN
Solar/Wind Harmer
6.603
964791AG1-342 GEN
Solar/Wind Harmer
2.424
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.294
972205AH1-687 GEN
50/50
22.206
316303AF2-085
50/50
2.484
316322AB2-045
Solar/Wind Harmer
1.467
971845AH1-439 GEN
Solar/Wind Harmer
22.808
316258AE1-075 C
Solar/Wind Harmer
0.76
316405AF2-144 C
Solar/Wind Harmer
0.803
946301AF1-294 GEN
Solar/Wind Harmer
5.991
961791AG1-021 GEN
Solar/Wind Harmer
2.922
3144303KENBRDG
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
12.304
970681AG2-440 GEN
Solar/Wind Harmer
8.167
316238AB2-078_GEN
Solar/Wind Harmer
0.41
316239AB2-077_GEN
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.345
971281AH1-106 GEN
Solar/Wind Harmer
2.085
971283AH1-107 GEN
Solar/Wind Harmer
2.085
316486AD2-202 GEN
Solar/Wind Harmer
0.302
970831AG2-522 GEN
Solar/Wind Harmer
4.94
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.62
971967AH1-528 GEN
Solar/Wind Harmer
16.771
946281AF1-292 GEN
Solar/Wind Harmer
0.19
3137643SOCKMAN
Solar/Wind Harmer
-0.032
970673AG2-436 GEN
Solar/Wind Harmer
17.241
970533AG2-339 GEN
Solar/Wind Harmer
5.254
316426AA2-053 GEN
Solar/Wind Harmer
0.785
970085AG2-068 GEN
Solar/Wind Harmer
4.799
970581AG2-369 GEN
Solar/Wind Harmer
4.127
3146043SEABORD
Solar/Wind Harmer
-0.008
315814AE2-033 C
Solar/Wind Harmer
6.846
315652AC1-086 GEN
Solar/Wind Harmer
8.081
316274AC1-208 GEN
Solar/Wind Harmer
0.772
316318V4-068
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.105
3146033SCOT NK
Solar/Wind Harmer
-0.028
315839AE2-212 C
Solar/Wind Harmer
0.21
316463AE2-346 GEN
Solar/Wind Harmer
0.112
3145513AHOSKIE
Solar/Wind Harmer
0.061
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.689
970657AG2-426 GEN
Solar/Wind Harmer
0.424
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.894
315833AF1-017_GEN
Solar/Wind Harmer
1.255
316311AC2-079 GEN
Solar/Wind Harmer
3.332
315732AD1-074 GEN1
Solar/Wind Harmer
1.322
315733AD1-074 GEN2
Solar/Wind Harmer
1.322
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315697AD1-025 GEN
Solar/Wind Harmer
1.317
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.601
316174AB2-169 GEN
Solar/Wind Harmer
0.993
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
957871AF2-081 GEN
Solar/Wind Harmer
3.196
957861AF2-080 GEN
Solar/Wind Harmer
2.791
316316AC1-027 C
Solar/Wind Harmer
0.195
316236AE1-162_GEN
Solar/Wind Harmer
0.192
3151081ELIZAR1
Adder
5.199
3151091ELIZAR2
Adder
5.109
971445AH1-216 GEN
Solar/Wind Harmer
3.943
3151201GRAVEL4
Adder
4.129
3151221GRAVEL6
Adder
4.124
3151191GRAVEL3
Adder
4.077
3151211GRAVEL5
Adder
4.077
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.122
315616AA1-038_C
Solar/Wind Helper
0.552
3151931BEARGRDN S1
50/50
5.872
3151911BEARGRDN G1
50/50
4.545
3144293JTRSVLE
50/50
0.527
3144293JTRSVLE
50/50
0.416
970119AG2-088 GEN
50/50
18.628
970937AG2-583 GEN
Solar/Wind Harmer
33.126
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.727
971563AH1-280 GEN
Solar/Wind Harmer
2.922
970685AG2-442 GEN
Solar/Wind Harmer
16.459
315785AD2-033 C
Solar/Wind Harmer
4.092
316034AC1-036 C
Solar/Wind Harmer
0.304
3143226MDLTHAN
Solar/Wind Harmer
-0.016
315693AD1-088 GEN
Solar/Wind Harmer
7.448
971377AH1-170 GEN
Solar/Wind Harmer
1.851
3147623JAMES R
Solar/Wind Harmer
0.229
316131AB2-060 GEN
Solar/Wind Harmer
1.533
3143526WINTERP
Solar/Wind Harmer
-0.066
957481AF2-042 GEN
Solar/Wind Harmer
37.368
970401AG2-262 GEN
Solar/Wind Harmer
0.741
971065AG2-659 GEN
Solar/Wind Harmer
5.161
316129AC1-054 GEN
Solar/Wind Harmer
0.886
3147043LAWRENC
Adder
0.815
3150851SPRUNCC
Adder
0.379
960081AF2-299 GEN
Solar/Wind Harmer
0.953
316087AB2-174 GEN
Solar/Wind Harmer
1.183
3145783HORNRTN
Solar/Wind Harmer
-0.008
941031AE2-094 GEN
Solar/Wind Harmer
14.649
970919AG2-571 GEN
Solar/Wind Harmer
2.461
315607AA1-063A GEN
Solar/Wind Harmer
0.776
970087AG2-069 GEN
Solar/Wind Harmer
7.198
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.501
940641AE2-051 GEN
Solar/Wind Harmer
6.871
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.212
3143096IRON208
Adder
0.265
939411AE1-173 GEN
Solar/Wind Harmer
35.461
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.242
316381AD1-082 GEN
Solar/Wind Harmer
0.616
3156021HOLLOMANSOL
Solar/Wind Harmer
0.9
316319Z2-044 C
Solar/Wind Harmer
0.368
3146233WITAKRS
Solar/Wind Harmer
-0.026
316132AB2-190 GEN1
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.654
971069AG2-661 GEN
Solar/Wind Harmer
1.039
315737AD1-076 GEN
Solar/Wind Harmer
1.244
316369SG1_INVT
Solar/Wind Harmer
1.164
316093AE2-104_GEN
Solar/Wind Harmer
1.898
315816AE2-034 GEN
Solar/Wind Harmer
0.526
3145663CRESWEL
Solar/Wind Harmer
-0.018
971163AH1-040 GEN
Solar/Wind Harmer
6.117
3130156CHOWAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.601
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.87
3142053HEARTS
Solar/Wind Harmer
0.076
3145963POPLR C
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
3.175
944631AF1-128 GEN
Adder
27.172
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
319010AE1-072 C
Solar/Wind Harmer
1.29
3146456SLIGO L269
Solar/Wind Harmer
-0.006
3146293MARTNCO
Solar/Wind Harmer
0.04
316494AC1-189 GEN
Solar/Wind Harmer
0.686
944591AF1-124 GEN
Solar/Wind Harmer
29.1
316375AC2-012 GEN
Solar/Wind Harmer
2.204
316036AC1-147 C
Solar/Wind Harmer
0.171
3150981CHESPKA
Adder
0.708
3145336SMITFLD
Solar/Wind Harmer
-0.025
3151171GRAVELC
Adder
0.603
316072AD1-144
Solar/Wind Harmer
0.128
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.765
3151921BEARGRDN G2
50/50
4.545
3144293JTRSVLE
50/50
0.527
972003AH1-546 GEN
Solar/Wind Harmer
21.813
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.168
942461AE2-259 GEN
Solar/Wind Harmer
4.286
3147133PAMPLIN
Solar/Wind Harmer
-0.07
970257AG2-171 GEN
Solar/Wind Harmer
7.117
971775AH1-396 GEN
Solar/Wind Harmer
1.339
959311AF2-222 GEN
Solar/Wind Harmer
17.432
964241AG1-285 GEN
Solar/Wind Harmer
11.676
970221AG2-151 GEN
Solar/Wind Harmer
9.255
316478AD1-087 GEN
Solar/Wind Harmer
1.032
270494AE1-108_GEN
Solar/Wind Harmer
2.999
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.379
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.172
316181AB2-040 GEN
Solar/Wind Harmer
1.147
971683AH1-343 GEN
Solar/Wind Harmer
3.493
944011AF1-069 GEN
Solar/Wind Harmer
4.59
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970917AG2-570 GEN
Solar/Wind Harmer
19.442
3156081AA2-088 GEN
Solar/Wind Harmer
2.348
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.5
3145893MURPHYS
Solar/Wind Harmer
0.05
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.265
3143096IRON208
Adder
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.614
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.322
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.26
3145273HOLLAND
Solar/Wind Harmer
-0.005
970657AG2-426 GEN
Solar/Wind Harmer
1.358
970133AG2-095 GEN
Solar/Wind Harmer
0.756
315722AD1-056 GEN
Solar/Wind Harmer
2.391
3146233WITAKRS
Solar/Wind Harmer
0.139
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.004
316458AB2-190 GEN2
Solar/Wind Harmer
0.668
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.62
315778AD1-151 GEN
Solar/Wind Harmer
5.844
315735AD1-075 GEN1
Solar/Wind Harmer
0.661
3146376EDENTON
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316123AC1-075 GEN
Solar/Wind Harmer
0.697
3145963POPLR C
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
961611AG1-000B GEN
Solar/Wind Harmer
1.355
316305AF2-043 C
Solar/Wind Harmer
0.193
316246AF1-032 C
Solar/Wind Harmer
0.13
316321Z2-027
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
2.557
316320Y1-086
Solar/Wind Harmer
0.376
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.74
316420AA1-050 GEN
Solar/Wind Harmer
0.728
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
3145933PARMELE
Solar/Wind Harmer
-0.006
3142956BIRDNECK
Solar/Wind Harmer
0.342
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
28.996
944601AF1-125 GEN
Solar/Wind Harmer
28.543
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.266
3151171GRAVELC
Adder
0.794
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.511
3132273ORANGE
Solar/Wind Helper
0.026
316118AC1-105 GEN
Solar/Wind Harmer
0.715
970933AG2-581 GEN
Solar/Wind Harmer
9.133
316248AF1-058 C
Solar/Wind Harmer
0.286
313506AB2-031 GEN
Solar/Wind Harmer
0.66
972187AH1-678 GEN
Adder
2.044
972185AH1-677 GEN
Adder
3.99
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.932
3145783HORNRTN
Solar/Wind Harmer
0.745
3145783HORNRTN
Solar/Wind Harmer
0.233
3145783HORNRTN
Solar/Wind Harmer
0.093
316365GEN2_N
Solar/Wind Harmer
0.501
3144356SAPONY
Solar/Wind Harmer
0.256
316315AB2-025 C
Solar/Wind Harmer
0.198
962571AG1-106 GEN
Solar/Wind Harmer
1.033
3145893MURPHYS
Solar/Wind Harmer
0.2
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.047
316240AF1-291 C
Solar/Wind Harmer
0.208
944641AF1-129 GEN
Adder
29.302
315742AE1-103 GEN
Solar/Wind Harmer
1.626
316083AB2-161 GEN
Solar/Wind Harmer
1.092
315724AD1-057 GEN
Solar/Wind Harmer
1.315
316349AD2-085 GEN
Solar/Wind Harmer
0.587
316065AD1-022 GEN
Solar/Wind Harmer
3.297
316033AB2-134 GEN
Solar/Wind Harmer
2.102
315835AF2-110_GEN
Solar/Wind Harmer
0.816
315614AA2-178 GEN
Solar/Wind Harmer
0.702
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316049AB1-081 GEN
Solar/Wind Harmer
0.696
316263AC1-034 GEN
Solar/Wind Harmer
3.034
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.167
316433W1029_GEN2
Solar/Wind Harmer
1.167
316435W1029_GEN3
Solar/Wind Harmer
1.167
961601AG1-000A GEN
Solar/Wind Harmer
2.525
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
0.755
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.43
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3150991CHESPKB
Adder
0.594
3150991CHESPKB
Adder
0.58
316005AA1-067
Solar/Wind Harmer
0.128
966001AG1-469 GEN
Solar/Wind Helper
0.182
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.077
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
1.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.027
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.607
CPLELTFEXP_CPLE->PJM
CLTF
3.66
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.346
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.81
MECLTFEXP_MEC->PJM
CLTF
0.061
NYPJM->LTFIMP_NY
CLTF
0.429

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.79 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:799.44
MW Contribution:
16.39
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.495
3144293JTRSVLE
50/50
0.534
970413AG2-270 GEN
50/50
10.515
3151031BRUNSWICKG2
50/50
1.061
3151261ROARAP2
50/50
0.094
3150861SPRUNCD
50/50
0.361
3151391GASTONA
50/50
0.185
3151411GASTONB
50/50
0.185
972003AH1-546 GEN
Solar/Wind Harmer
16.394
3146776BUCKING
Solar/Wind Harmer
0.139
3146926FARMVIL
Solar/Wind Harmer
0.184
3143336POWHATN
Solar/Wind Harmer
3.996
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.64
970257AG2-171 GEN
Solar/Wind Harmer
5.525
971775AH1-396 GEN
Solar/Wind Harmer
0.276
959311AF2-222 GEN
Solar/Wind Harmer
13.645
964241AG1-285 GEN
Solar/Wind Harmer
9.212
970221AG2-151 GEN
Solar/Wind Harmer
6.773
316478AD1-087 GEN
Solar/Wind Harmer
0.389
270494AE1-108_GEN
Solar/Wind Harmer
1.182
3147043LAWRENC
Solar/Wind Harmer
0.057
944011AF1-069 GEN
Solar/Wind Harmer
4.752
316181AB2-040 GEN
Solar/Wind Harmer
0.112
970917AG2-570 GEN
Solar/Wind Harmer
6.894
971683AH1-343 GEN
Solar/Wind Harmer
2.8
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.069
316011AB1-132 GEN
Solar/Wind Harmer
1.253
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3145893MURPHYS
Solar/Wind Harmer
0.115
3145893MURPHYS
Solar/Wind Harmer
0.069
3145796HORNRTN
Solar/Wind Harmer
0.272
3145796HORNRTN
Solar/Wind Harmer
0.068
316212AC1-099_GEN
Solar/Wind Harmer
0.35
3146173TUNIS
Solar/Wind Harmer
0.068
3145823KELFORD
Solar/Wind Harmer
0.067
3145273HOLLAND
Solar/Wind Harmer
0.049
315722AD1-056 GEN
Solar/Wind Harmer
2.24
3146233WITAKRS
Solar/Wind Harmer
0.322
3146233WITAKRS
Solar/Wind Harmer
0.044
3146206CASHIE
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.042
316222AC1-221 GEN
Solar/Wind Harmer
0.263
315735AD1-075 GEN1
Solar/Wind Harmer
0.181
315813AE1-149 C
Solar/Wind Harmer
3.388
970657AG2-426 GEN
Solar/Wind Harmer
1.423
970909AG2-566 GEN
50/50
2.507
3144293JTRSVLE
50/50
0.534
970535AG2-341 GEN
50/50
2.068
3151581KERR 1
50/50
0.077
3152661PLYWOOD A
50/50
0.21
3151041BRUNSWICKG3
50/50
1.061
972187AH1-678 GEN
50/50
2.435
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.315
972185AH1-677 GEN
50/50
4.769
3151261ROARAP2
50/50
0.091
3146776BUCKING
Solar/Wind Harmer
1.546
3146776BUCKING
Solar/Wind Harmer
0.125
316336AC2-165 C
Solar/Wind Harmer
15.338
316313AB2-026
Solar/Wind Harmer
0.165
970301AG2-198 GEN
Solar/Wind Harmer
10.027
958211AF2-115 GEN
Solar/Wind Harmer
2.53
3147133PAMPLIN
Solar/Wind Harmer
0.204
3147133PAMPLIN
Solar/Wind Harmer
0.163
970323AG2-213 GEN
Solar/Wind Harmer
7.367
971223AH1-071 GEN
Solar/Wind Harmer
1.259
970099AG2-077 GEN
Solar/Wind Harmer
12.06
962561AG1-105 GEN
Solar/Wind Harmer
5.245
964791AG1-342 GEN
Solar/Wind Harmer
2.031
3146843MT LREL
Solar/Wind Harmer
0.106
3146843MT LREL
Solar/Wind Harmer
0.106
3143526WINTERP
Solar/Wind Harmer
0.509
316118AC1-105 GEN
Solar/Wind Harmer
0.25
970933AG2-581 GEN
Solar/Wind Harmer
7.587
313506AB2-031 GEN
Solar/Wind Harmer
0.241
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.095
3145783HORNRTN
Solar/Wind Harmer
1.334
3145783HORNRTN
Solar/Wind Harmer
1.067
3145783HORNRTN
Solar/Wind Harmer
0.333
3145783HORNRTN
Solar/Wind Harmer
0.133
316365GEN2_N
Solar/Wind Harmer
0.159
3144356SAPONY
Solar/Wind Harmer
0.593
316315AB2-025 C
Solar/Wind Harmer
0.057
962571AG1-106 GEN
Solar/Wind Harmer
0.983
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
972205AH1-687 GEN
50/50
21.963
316303AF2-085
50/50
2.099
3151541CLOVER2
50/50
2.397
3151601KERR 3
50/50
0.215
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
963041AG1-153 GEN
50/50
2.149
315244AE2-183_ST
50/50
2.291
3151281ROARAP4
50/50
0.085
971285AH1-108 GEN
50/50
0.591
315779AE2-040
50/50
0.989
971845AH1-439 GEN
Solar/Wind Harmer
17.227
316258AE1-075 C
Solar/Wind Harmer
0.197
946301AF1-294 GEN
Solar/Wind Harmer
4.161
961791AG1-021 GEN
Solar/Wind Harmer
2.024
3144303KENBRDG
Solar/Wind Harmer
0.138
970683AG2-441 GEN
Solar/Wind Harmer
9.631
970681AG2-440 GEN
Solar/Wind Harmer
6.392
316486AD2-202 GEN
Solar/Wind Harmer
0.114
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.36
971283AH1-107 GEN
Solar/Wind Harmer
1.36
970831AG2-522 GEN
Solar/Wind Harmer
3.97
3147173SINAI
Solar/Wind Harmer
0.089
3147243WELCO
Solar/Wind Harmer
0.056
971967AH1-528 GEN
Solar/Wind Harmer
14.085
970673AG2-436 GEN
Solar/Wind Harmer
9.882
970533AG2-339 GEN
Solar/Wind Harmer
5.967
3137643SOCKMAN
Solar/Wind Harmer
0.308
970085AG2-068 GEN
Solar/Wind Harmer
4.081
970581AG2-369 GEN
Solar/Wind Harmer
3.51
316426AA2-053 GEN
Solar/Wind Harmer
0.249
3146043SEABORD
Solar/Wind Harmer
0.073
315814AE2-033 C
Solar/Wind Harmer
5.613
315652AC1-086 GEN
Solar/Wind Harmer
7.598
316274AC1-208 GEN
Solar/Wind Harmer
0.355
3145893MURPHYS
Solar/Wind Harmer
0.186
3145893MURPHYS
Solar/Wind Harmer
0.069
3145796HORNRTN
Solar/Wind Harmer
0.218
3145796HORNRTN
Solar/Wind Harmer
0.027
316210AC1-098 GEN
Solar/Wind Harmer
0.627
3146033SCOT NK
Solar/Wind Harmer
0.27
316463AE2-346 GEN
Solar/Wind Harmer
0.057
3145513AHOSKIE
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.133
3145683EARLEYS
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.067
316327AA2-057 GEN
Solar/Wind Harmer
0.097
3146206CASHIE
Solar/Wind Harmer
0.064
970601AG2-382 GEN
Solar/Wind Harmer
2.394
315732AD1-074 GEN1
Solar/Wind Harmer
0.362
315733AD1-074 GEN2
Solar/Wind Harmer
0.362
3143316POE
Solar/Wind Harmer
0.252
3130546PLYMOUTH
Solar/Wind Harmer
0.064
970657AG2-426 GEN
Solar/Wind Harmer
0.466
316311AC2-079 GEN
Solar/Wind Harmer
1.819
3130156CHOWAN
Solar/Wind Harmer
0.063
3130156CHOWAN
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.173
313526AB2-022
Solar/Wind Harmer
0.033
3146406KITTY HAWK
Solar/Wind Harmer
0.008
957871AF2-081 GEN
Solar/Wind Harmer
3.112
316316AC1-027 C
Solar/Wind Harmer
0.059
3151081ELIZAR1
Adder
5.701
3151091ELIZAR2
Adder
5.602
3145573BETHELC
Solar/Wind Harmer
0.062
3145573BETHELC
Solar/Wind Harmer
0.062
957861AF2-080 GEN
Solar/Wind Harmer
2.662
3145746EVERETS
Solar/Wind Harmer
0.245
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
971445AH1-216 GEN
Solar/Wind Harmer
4.283
3146376EDENTON
Solar/Wind Harmer
0.063
316283AC2-100 C
Solar/Wind Harmer
0.123
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.011
3145963POPLR C
Solar/Wind Harmer
0.063
316246AF1-032 C
Solar/Wind Harmer
0.028
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.062
971153AH1-033 GEN
Solar/Wind Harmer
0.723
316017AA1-139 ULT1
Solar/Wind Harmer
0.033
971623AH1-311 GEN
Solar/Wind Harmer
0.125
944581AF1-123 GEN
Solar/Wind Harmer
14.049
944601AF1-125 GEN
Solar/Wind Harmer
13.832
3151101ELIZAR3
Adder
5.774
3144873MCLAUGH
Solar/Wind Harmer
0.002
961601AG1-000A GEN
Solar/Wind Harmer
4.415
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.461
3145893MURPHYS
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.204
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
316140AB2-099
Solar/Wind Harmer
0.024
315742AE1-103 GEN
Solar/Wind Harmer
0.988
315724AD1-057 GEN
Solar/Wind Harmer
1.249
316065AD1-022 GEN
Solar/Wind Harmer
2.944
315614AA2-178 GEN
Solar/Wind Harmer
0.361
316349AD2-085 GEN
Solar/Wind Harmer
0.042
315835AF2-110_GEN
Solar/Wind Harmer
0.434
3146376EDENTON
Solar/Wind Harmer
0.281
3146376EDENTON
Solar/Wind Harmer
0.281
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146626S HERTFORD
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.063
3146386ELIZ CT
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.25
3137176SLIGO L2192
Solar/Wind Harmer
0.249
3146456SLIGO L269
Solar/Wind Harmer
1.106
316049AB1-081 GEN
Solar/Wind Harmer
0.356
316339AD2-160 GEN
Solar/Wind Harmer
0.1
316388AE2-253 GEN
Solar/Wind Harmer
0.194
316263AC1-034 GEN
Solar/Wind Harmer
2.375
3145506HICKORY
Solar/Wind Harmer
0.25
3145506HICKORY
Solar/Wind Harmer
0.15
3145506HICKORY
Solar/Wind Harmer
0.037
3150991CHESPKB
Adder
0.651
3150991CHESPKB
Adder
0.636
961601AG1-000A GEN
Solar/Wind Harmer
1.104
3145933PARMELE
Solar/Wind Harmer
0.124
3145933PARMELE
Solar/Wind Harmer
0.062
3145493TOT1
Solar/Wind Harmer
0.143
3145453TOT5
Solar/Wind Harmer
0.086
3145603CNETO
Solar/Wind Harmer
0.057
316005AA1-067
Solar/Wind Harmer
0.066
316294AC1-161 GEN
Solar/Wind Harmer
1.057
3151931BEARGRDN S1
50/50
5.808
3151911BEARGRDN G1
50/50
4.495
3144293JTRSVLE
50/50
0.534
3144293JTRSVLE
50/50
0.422
970119AG2-088 GEN
50/50
15.744
3151531CLOVER1
50/50
2.414
3151591KERR 2
50/50
0.215
3151641KERR 7
50/50
0.215
3147043LAWRENC
50/50
0.914
3151051BRUNSWICKS1
50/50
2.203
3151021BRUNSWICKG1
50/50
1.061
971451AH1-221 GEN
50/50
3.223
315243AE2-183_GT3
50/50
1.321
3151281ROARAP4
50/50
0.091
3150851SPRUNCC
50/50
0.361
3151391GASTONA
50/50
0.185
3151411GASTONB
50/50
0.185
970937AG2-583 GEN
Solar/Wind Harmer
24.603
3146776BUCKING
Solar/Wind Harmer
0.155
3146926FARMVIL
Solar/Wind Harmer
0.184
3143336POWHATN
Solar/Wind Harmer
4.701
971563AH1-280 GEN
Solar/Wind Harmer
2.249
970685AG2-442 GEN
Solar/Wind Harmer
12.826
315785AD2-033 C
Solar/Wind Harmer
1.334
316034AC1-036 C
Solar/Wind Harmer
0.01
315693AD1-088 GEN
Solar/Wind Harmer
6.634
316131AB2-060 GEN
Solar/Wind Harmer
0.41
971377AH1-170 GEN
Solar/Wind Harmer
1.355
3147623JAMES R
Solar/Wind Harmer
0.294
3143226MDLTHAN
Solar/Wind Harmer
0.118
957481AF2-042 GEN
Solar/Wind Harmer
30.149
970401AG2-262 GEN
Solar/Wind Harmer
0.621
3143526WINTERP
Solar/Wind Harmer
0.509
971065AG2-659 GEN
Solar/Wind Harmer
4.138
316129AC1-054 GEN
Solar/Wind Harmer
0.356
960081AF2-299 GEN
Solar/Wind Harmer
0.774
941031AE2-094 GEN
Solar/Wind Harmer
14.545
970919AG2-571 GEN
Solar/Wind Harmer
2.758
970087AG2-069 GEN
Solar/Wind Harmer
6.122
3145783HORNRTN
Solar/Wind Harmer
0.075
940641AE2-051 GEN
Solar/Wind Harmer
5.96
315607AA1-063A GEN
Solar/Wind Harmer
0.148
316023GEN1_S
Solar/Wind Harmer
0.159
939411AE1-173 GEN
Solar/Wind Harmer
30.495
3146263WOODLND
Solar/Wind Harmer
0.069
3145893MURPHYS
Solar/Wind Harmer
0.275
3145893MURPHYS
Solar/Wind Harmer
0.306
3145796HORNRTN
Solar/Wind Harmer
0.225
3145796HORNRTN
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
3145823KELFORD
Solar/Wind Harmer
0.067
3145683EARLEYS
Solar/Wind Harmer
0.067
3156021HOLLOMANSOL
Solar/Wind Harmer
0.292
3146233WITAKRS
Solar/Wind Harmer
0.256
3146206CASHIE
Solar/Wind Harmer
0.064
971547AH1-271 GEN
Solar/Wind Harmer
1.368
315737AD1-076 GEN
Solar/Wind Harmer
0.816
316381AD1-082 GEN
Solar/Wind Harmer
0.064
315816AE2-034 GEN
Solar/Wind Harmer
0.27
3145663CRESWEL
Solar/Wind Harmer
0.177
971163AH1-040 GEN
Solar/Wind Harmer
5.071
316093AE2-104_GEN
Solar/Wind Harmer
1.064
3130156CHOWAN
Solar/Wind Harmer
0.063
3146516WINFALL
Solar/Wind Harmer
0.204
3146516WINFALL
Solar/Wind Harmer
0.063
3145963POPLR C
Solar/Wind Harmer
0.063
3142543TWELFTH
Solar/Wind Harmer
0.006
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
319010AE1-072 C
Solar/Wind Harmer
0.311
3146456SLIGO L269
Solar/Wind Harmer
0.062
316359AB2-059 GEN
Solar/Wind Harmer
0.222
3142053HEARTS
Solar/Wind Harmer
0.11
944591AF1-124 GEN
Solar/Wind Harmer
14.099
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150981CHESPKA
Adder
0.776
3146293MARTNCO
Solar/Wind Harmer
0.057
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.062
3145493TOT1
Solar/Wind Harmer
0.275
316494AC1-189 GEN
Solar/Wind Harmer
0.209
316072AD1-144
Solar/Wind Harmer
0.022
315671AE2-027_GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
315773AC2-141 GEN
Solar/Wind Harmer
2.232
3145336SMITFLD
Solar/Wind Harmer
0.244
3145933PARMELE
Solar/Wind Harmer
0.062
3146073TAR RVR
Solar/Wind Harmer
0.062
3146083TARBORO
Solar/Wind Harmer
0.062
3144536CHRHLND
Solar/Wind Harmer
0.009
3145746EVERETS
Solar/Wind Harmer
0.062
3145746EVERETS
Solar/Wind Harmer
0.062
3145336SMITFLD
Solar/Wind Harmer
0.024
316123AC1-075 GEN
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
0.581
316458AB2-190 GEN2
Solar/Wind Harmer
0.322
315778AD1-151 GEN
Solar/Wind Harmer
4.826
961611AG1-000B GEN
Solar/Wind Harmer
1.605
3151171GRAVELC
Adder
0.841
3143096IRON208
Adder
0.248
3143096IRON208
Adder
0.243
3148013FISHERV
Solar/Wind Helper
0.179
316499AE2-029_GEN
Solar/Wind Helper
0.52
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.259
316132AB2-190 GEN1
Solar/Wind Harmer
0.322
971069AG2-661 GEN
Solar/Wind Harmer
1.073
961611AG1-000B GEN
Solar/Wind Harmer
3.157
3151171GRAVELC
Adder
0.64
3143096IRON208
Adder
0.248
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.785
3147666LOUISA
Solar/Wind Helper
0.45
944641AF1-129 GEN
Adder
29.012
316033AB2-134 GEN
Solar/Wind Harmer
0
966001AG1-469 GEN
Solar/Wind Helper
0.186
315697AD1-025 GEN
Solar/Wind Harmer
0.064
3151201GRAVEL4
Adder
4.378
3151221GRAVEL6
Adder
4.373
3151191GRAVEL3
Adder
4.322
3151211GRAVEL5
Adder
4.322
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.107
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
315616AA1-038_C
Solar/Wind Helper
0.562
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.062
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.167
LAGNLTFEXP_LAGN->PJM
CLTF
1.43
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.724
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.695
CPLELTFEXP_CPLE->PJM
CLTF
4.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.187
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.099
MECLTFEXP_MEC->PJM
CLTF
0.124
SIGELTFEXP_SIGE->PJM
CLTF
0.001
NYPJM->LTFIMP_NY
CLTF
0.461

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.09 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:733.57
MW Contribution:
21.7
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.34 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:932.1
MW Contribution:
21.78
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
970535AG2-341 GEN
50/50
2.001
3151581KERR 1
50/50
0.071
3152661PLYWOOD A
50/50
0.197
316336AC2-165 C
Solar/Wind Harmer
32.562
972205AH1-687 GEN
50/50
29.134
3151541CLOVER2
50/50
2.196
3151601KERR 3
50/50
0.2
3151611KERR 4
50/50
0.2
3151621KERR 5
50/50
0.2
3151631KERR 6
50/50
0.2
971845AH1-439 GEN
Solar/Wind Harmer
22.245
946301AF1-294 GEN
Solar/Wind Harmer
4.868
961791AG1-021 GEN
Solar/Wind Harmer
2.368
3144303KENBRDG
Solar/Wind Harmer
0.154
970683AG2-441 GEN
Solar/Wind Harmer
10.284
970681AG2-440 GEN
Solar/Wind Harmer
6.826
316486AD2-202 GEN
Solar/Wind Harmer
0.105
3147173SINAI
Solar/Wind Harmer
0.083
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.367
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
3151531CLOVER1
50/50
2.212
3151591KERR 2
50/50
0.2
3151641KERR 7
50/50
0.2
3147043LAWRENC
50/50
0.756
970937AG2-583 GEN
Solar/Wind Harmer
39.417
3146776BUCKING
Solar/Wind Harmer
0.2
3146926FARMVIL
Solar/Wind Harmer
0.23
971377AH1-170 GEN
Solar/Wind Harmer
2.854
3147623JAMES R
Solar/Wind Harmer
0.62
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
970413AG2-270 GEN
50/50
9.635
972003AH1-546 GEN
Solar/Wind Harmer
21.695
3146776BUCKING
Solar/Wind Harmer
0.18
3146926FARMVIL
Solar/Wind Harmer
0.23
942461AE2-259 GEN
Solar/Wind Harmer
0.001
970221AG2-151 GEN
Solar/Wind Harmer
14.27
3147133PAMPLIN
Solar/Wind Harmer
0.737
270494AE1-108_GEN
Solar/Wind Harmer
2.499
970257AG2-171 GEN
Solar/Wind Harmer
6.149
971775AH1-396 GEN
Solar/Wind Harmer
0.307
959311AF2-222 GEN
Solar/Wind Harmer
14.386
964241AG1-285 GEN
Solar/Wind Harmer
9.36
315821AE2-092 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.357
958131AF2-107 GEN
Solar/Wind Harmer
2.368
3147043LAWRENC
Solar/Wind Harmer
0.047
971563AH1-280 GEN
Solar/Wind Harmer
2.631
970685AG2-442 GEN
Solar/Wind Harmer
14.043
315785AD2-033 C
Solar/Wind Harmer
1.465
316034AC1-036 C
Solar/Wind Harmer
0.011
315693AD1-088 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.416
970401AG2-262 GEN
Solar/Wind Harmer
0.601
957481AF2-042 GEN
Solar/Wind Harmer
26.83
971065AG2-659 GEN
Solar/Wind Harmer
3.622
316129AC1-054 GEN
Solar/Wind Harmer
0.307
971967AH1-528 GEN
Solar/Wind Harmer
9.13
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3146776BUCKING
Solar/Wind Harmer
2.001
3146776BUCKING
Solar/Wind Harmer
0.162
970301AG2-198 GEN
Solar/Wind Harmer
11.924
958211AF2-115 GEN
Solar/Wind Harmer
2.96
3147133PAMPLIN
Solar/Wind Harmer
0.235
3147133PAMPLIN
Solar/Wind Harmer
0.188
970323AG2-213 GEN
Solar/Wind Harmer
8.199
962561AG1-105 GEN
Solar/Wind Harmer
5.114
964791AG1-342 GEN
Solar/Wind Harmer
1.967
3146843MT LREL
Solar/Wind Harmer
0.102
3146843MT LREL
Solar/Wind Harmer
0.102
970099AG2-077 GEN
Solar/Wind Harmer
10.732
316118AC1-105 GEN
Solar/Wind Harmer
0.237
960081AF2-299 GEN
Solar/Wind Harmer
0.544
971683AH1-343 GEN
Solar/Wind Harmer
2.656
316123AC1-075 GEN
Solar/Wind Harmer
0.079
970933AG2-581 GEN
Solar/Wind Harmer
5.491
966001AG1-469 GEN
Solar/Wind Helper
0.139
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.3 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:840.79
MW Contribution:
28.57
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.46 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1049.6
MW Contribution:
28.68
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
972003AH1-546 GEN
Solar/Wind Harmer
28.565
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.235
970221AG2-151 GEN
Solar/Wind Harmer
18.789
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270494AE1-108_GEN
Solar/Wind Harmer
6.111
970257AG2-171 GEN
Solar/Wind Harmer
8.096
971775AH1-396 GEN
Solar/Wind Harmer
1.523
959311AF2-222 GEN
Solar/Wind Harmer
18.979
964241AG1-285 GEN
Solar/Wind Harmer
12.324
315821AE2-092 GEN
Solar/Wind Harmer
2.69
316478AD1-087 GEN
Solar/Wind Harmer
0.999
958131AF2-107 GEN
Solar/Wind Harmer
3.152
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.854
971683AH1-343 GEN
Solar/Wind Harmer
3.498
316123AC1-075 GEN
Solar/Wind Harmer
0.72
966621AG1-532 GEN
Solar/Wind Harmer
0.129
972205AH1-687 GEN
50/50
29.134
316322AB2-045
Solar/Wind Harmer
1.888
971845AH1-439 GEN
Solar/Wind Harmer
29.289
946301AF1-294 GEN
Solar/Wind Harmer
7.102
961791AG1-021 GEN
Solar/Wind Harmer
3.465
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
13.541
970681AG2-440 GEN
Solar/Wind Harmer
8.987
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316486AD2-202 GEN
Solar/Wind Harmer
0.293
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.433
971967AH1-528 GEN
Solar/Wind Harmer
12.053
946281AF1-292 GEN
Solar/Wind Harmer
0.143
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
970937AG2-583 GEN
Solar/Wind Harmer
51.899
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.758
3147623JAMES R
Solar/Wind Harmer
0.465
971563AH1-280 GEN
Solar/Wind Harmer
3.465
970685AG2-442 GEN
Solar/Wind Harmer
18.491
315785AD2-033 C
Solar/Wind Harmer
4.603
316034AC1-036 C
Solar/Wind Harmer
0.329
315693AD1-088 GEN
Solar/Wind Harmer
7.766
316131AB2-060 GEN
Solar/Wind Harmer
1.615
970401AG2-262 GEN
Solar/Wind Harmer
0.751
957481AF2-042 GEN
Solar/Wind Harmer
35.327
971065AG2-659 GEN
Solar/Wind Harmer
4.769
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.712
960081AF2-299 GEN
Solar/Wind Harmer
0.716
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
970535AG2-341 GEN
50/50
2.001
316336AC2-165 C
Solar/Wind Harmer
45.084
3146776BUCKING
Solar/Wind Harmer
-0.224
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.7
958211AF2-115 GEN
Solar/Wind Harmer
4.331
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
970323AG2-213 GEN
Solar/Wind Harmer
10.795
313527AB2-043 GEN
Solar/Wind Harmer
2.357
316237AB2-079_GEN
Solar/Wind Harmer
0.426
962561AG1-105 GEN
Solar/Wind Harmer
6.734
964791AG1-342 GEN
Solar/Wind Harmer
2.459
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
14.131
316118AC1-105 GEN
Solar/Wind Harmer
0.714
315687AD1-152 GEN
Solar/Wind Harmer
1.245
316248AF1-058 C
Solar/Wind Harmer
0.281
970933AG2-581 GEN
Solar/Wind Harmer
7.23
966001AG1-469 GEN
Solar/Wind Helper
0.139
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.3 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:840.79
MW Contribution:
28.57
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
29.134
316322AB2-045
Solar/Wind Harmer
1.888
971845AH1-439 GEN
Solar/Wind Harmer
29.289
946301AF1-294 GEN
Solar/Wind Harmer
7.102
961791AG1-021 GEN
Solar/Wind Harmer
3.465
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
13.541
970681AG2-440 GEN
Solar/Wind Harmer
8.987
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316486AD2-202 GEN
Solar/Wind Harmer
0.293
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.433
971967AH1-528 GEN
Solar/Wind Harmer
12.053
946281AF1-292 GEN
Solar/Wind Harmer
0.143
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151931BEARGRDN S1
50/50
7.704
3151911BEARGRDN G1
50/50
5.963
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.493
970937AG2-583 GEN
Solar/Wind Harmer
51.899
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.758
3147623JAMES R
Solar/Wind Harmer
0.465
971563AH1-280 GEN
Solar/Wind Harmer
3.465
970685AG2-442 GEN
Solar/Wind Harmer
18.491
315785AD2-033 C
Solar/Wind Harmer
4.603
316034AC1-036 C
Solar/Wind Harmer
0.329
315693AD1-088 GEN
Solar/Wind Harmer
7.766
316131AB2-060 GEN
Solar/Wind Harmer
1.615
970401AG2-262 GEN
Solar/Wind Harmer
0.751
957481AF2-042 GEN
Solar/Wind Harmer
35.327
971065AG2-659 GEN
Solar/Wind Harmer
4.769
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.712
960081AF2-299 GEN
Solar/Wind Harmer
0.716
3151921BEARGRDN G2
50/50
5.963
3144293JTRSVLE
50/50
0.625
972003AH1-546 GEN
Solar/Wind Harmer
28.565
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.235
970221AG2-151 GEN
Solar/Wind Harmer
18.789
3147133PAMPLIN
Solar/Wind Harmer
-0.082
270494AE1-108_GEN
Solar/Wind Harmer
6.111
970257AG2-171 GEN
Solar/Wind Harmer
8.096
971775AH1-396 GEN
Solar/Wind Harmer
1.523
959311AF2-222 GEN
Solar/Wind Harmer
18.979
964241AG1-285 GEN
Solar/Wind Harmer
12.324
315821AE2-092 GEN
Solar/Wind Harmer
2.69
316478AD1-087 GEN
Solar/Wind Harmer
0.999
958131AF2-107 GEN
Solar/Wind Harmer
3.152
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.854
971683AH1-343 GEN
Solar/Wind Harmer
3.498
316123AC1-075 GEN
Solar/Wind Harmer
0.72
966621AG1-532 GEN
Solar/Wind Harmer
0.129
970909AG2-566 GEN
50/50
2.981
3144293JTRSVLE
50/50
0.625
970535AG2-341 GEN
50/50
2.001
316336AC2-165 C
Solar/Wind Harmer
45.084
3146776BUCKING
Solar/Wind Harmer
-0.224
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.7
958211AF2-115 GEN
Solar/Wind Harmer
4.331
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
970323AG2-213 GEN
Solar/Wind Harmer
10.795
313527AB2-043 GEN
Solar/Wind Harmer
2.357
316237AB2-079_GEN
Solar/Wind Harmer
0.426
962561AG1-105 GEN
Solar/Wind Harmer
6.734
964791AG1-342 GEN
Solar/Wind Harmer
2.459
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
14.131
316118AC1-105 GEN
Solar/Wind Harmer
0.714
315687AD1-152 GEN
Solar/Wind Harmer
1.245
316248AF1-058 C
Solar/Wind Harmer
0.281
970933AG2-581 GEN
Solar/Wind Harmer
7.23
966001AG1-469 GEN
Solar/Wind Helper
0.139
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
1.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.638
TVALTFEXP_TVA->PJM
CLTF
0.537
CPLELTFEXP_CPLE->PJM
CLTF
2.881
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.128
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.645
MECLTFEXP_MEC->PJM
CLTF
0.131
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.397

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-5: 556X2_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-5: 556X2_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.38 %
Rating:1050.6 MVA
Rating Type:C
MVA to Mitigate:1422.29
MW Contribution:
6.25
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-5: 556X2_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.68 %
Rating:1050.6 MVA
Rating Type:C
MVA to Mitigate:1204.79
MW Contribution:
5.84
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
35.916
3144293JTRSVLE
50/50
0.894
3151921BEARGRDN G2
50/50
1.148
959311AF2-222 GEN
Solar/Wind Harmer
55.336
3151541CLOVER2
50/50
8.187
3151601KERR 3
50/50
0.581
3151611KERR 4
50/50
0.581
3151621KERR 5
50/50
0.581
3151631KERR 6
50/50
0.581
972205AH1-687 GEN
50/50
5.608
970683AG2-441 GEN
Solar/Wind Harmer
37.949
970681AG2-440 GEN
Solar/Wind Harmer
25.187
316486AD2-202 GEN
Solar/Wind Harmer
1.09
3144303KENBRDG
Solar/Wind Harmer
-0.032
316238AB2-078_GEN
Solar/Wind Harmer
1.194
316239AB2-077_GEN
Solar/Wind Harmer
1.194
946301AF1-294 GEN
Solar/Wind Harmer
10.157
961791AG1-021 GEN
Solar/Wind Harmer
4.955
3147173SINAI
Solar/Wind Harmer
-0.029
3147243WELCO
Solar/Wind Harmer
-0.018
971845AH1-439 GEN
Solar/Wind Harmer
14.44
316322AB2-045
Solar/Wind Harmer
0.883
970831AG2-522 GEN
Solar/Wind Harmer
10.919
946281AF1-292 GEN
Solar/Wind Harmer
0.186
3137643SOCKMAN
Solar/Wind Harmer
-0.032
270455AD2-022 GEN
Solar/Wind Harmer
1.341
270457AD2-023 GEN
Solar/Wind Harmer
0.68
316426AA2-053 GEN
Solar/Wind Harmer
0.697
3151531CLOVER1
50/50
8.247
3144293JTRSVLE
50/50
0.894
3144293JTRSVLE
50/50
0.706
3151591KERR 2
50/50
0.581
3151641KERR 7
50/50
0.581
3147043LAWRENC
50/50
1.545
3151931BEARGRDN S1
50/50
1.483
3151911BEARGRDN G1
50/50
1.148
315693AD1-088 GEN
Solar/Wind Harmer
30.331
316034AC1-036 C
Solar/Wind Harmer
0.975
970685AG2-442 GEN
Solar/Wind Harmer
45.649
957481AF2-042 GEN
Solar/Wind Harmer
135.112
316131AB2-060 GEN
Solar/Wind Harmer
4.353
315785AD2-033 C
Solar/Wind Harmer
9.076
971563AH1-280 GEN
Solar/Wind Harmer
4.955
3146926FARMVIL
Solar/Wind Harmer
-0.022
970401AG2-262 GEN
Solar/Wind Harmer
2.198
3146776BUCKING
Solar/Wind Harmer
-0.01
971065AG2-659 GEN
Solar/Wind Harmer
12.517
316129AC1-054 GEN
Solar/Wind Harmer
2.067
971377AH1-170 GEN
Solar/Wind Harmer
1.546
3147623JAMES R
Solar/Wind Harmer
0.191
970937AG2-583 GEN
Solar/Wind Harmer
7.416
3147123OTTER R
Solar/Wind Harmer
-0.006
960081AF2-299 GEN
Solar/Wind Harmer
0.932
316087AB2-174 GEN
Solar/Wind Harmer
1.173
3147312GRETNA
Solar/Wind Harmer
-0.006
3146802CHATHAM
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
3.046
3145783HORNRTN
Solar/Wind Harmer
-0.008
315773AC2-141 GEN
Solar/Wind Helper
2.592
970909AG2-566 GEN
50/50
4.441
3144293JTRSVLE
50/50
0.894
970535AG2-341 GEN
50/50
5.689
3151581KERR 1
50/50
0.207
3152661PLYWOOD A
50/50
0.594
3147133PAMPLIN
Solar/Wind Harmer
-0.048
3147133PAMPLIN
Solar/Wind Harmer
-0.038
970301AG2-198 GEN
Solar/Wind Harmer
23.39
970099AG2-077 GEN
Solar/Wind Harmer
54.045
313527AB2-043 GEN
Solar/Wind Harmer
6.575
970323AG2-213 GEN
Solar/Wind Harmer
20.016
316237AB2-079_GEN
Solar/Wind Harmer
1.194
958211AF2-115 GEN
Solar/Wind Harmer
6.193
315687AD1-152 GEN
Solar/Wind Harmer
4.374
962561AG1-105 GEN
Solar/Wind Harmer
19.525
964791AG1-342 GEN
Solar/Wind Harmer
7.192
3146843MT LREL
Solar/Wind Harmer
-0.034
3146843MT LREL
Solar/Wind Harmer
-0.034
316118AC1-105 GEN
Solar/Wind Harmer
2.139
316248AF1-058 C
Solar/Wind Harmer
0.865
3146776BUCKING
Solar/Wind Harmer
-0.105
3146776BUCKING
Solar/Wind Harmer
-0.009
942751AE2-291 GEN
Solar/Wind Harmer
11.08
313506AB2-031 GEN
Solar/Wind Harmer
0.658
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
942671AE2-283 GEN
Solar/Wind Harmer
2.69
3145783HORNRTN
Solar/Wind Harmer
0.907
3145783HORNRTN
Solar/Wind Harmer
0.726
3145783HORNRTN
Solar/Wind Harmer
0.227
3145783HORNRTN
Solar/Wind Harmer
0.091
316294AC1-161 GEN
Solar/Wind Helper
2.202
964241AG1-285 GEN
Solar/Wind Harmer
40.056
3147133PAMPLIN
Solar/Wind Harmer
-0.15
316478AD1-087 GEN
Solar/Wind Harmer
3.722
942461AE2-259 GEN
Solar/Wind Harmer
6.2
970257AG2-171 GEN
Solar/Wind Harmer
15.012
971775AH1-396 GEN
Solar/Wind Harmer
2.824
3146926FARMVIL
Solar/Wind Harmer
-0.022
316003AC1-222 GEN
Solar/Wind Harmer
2.609
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.578
316123AC1-075 GEN
Solar/Wind Harmer
2.117
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
6.245
316222AC1-221 GEN
Solar/Wind Harmer
1.375
316283AC2-100 C
Solar/Wind Harmer
1.245
970221AG2-151 GEN
Solar/Wind Harmer
7.732
270494AE1-108_GEN
Solar/Wind Harmer
2.638
315821AE2-092 GEN
Solar/Wind Harmer
1.834
966621AG1-532 GEN
Solar/Wind Harmer
0.168
316181AB2-040 GEN
Solar/Wind Harmer
1.144
316217AC1-145 GEN
Solar/Wind Harmer
1.317
316197AC1-042 GEN
Solar/Wind Harmer
0.999
3147312GRETNA
Solar/Wind Harmer
-0.002
316190AA2-174 GEN
Solar/Wind Harmer
0.085
LAGNLTFEXP_LAGN->PJM
CLTF
1.679
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.694
TVALTFEXP_TVA->PJM
CLTF
0.849
CPLELTFEXP_CPLE->PJM
CLTF
2.782
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.844
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.361
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.904
MECLTFEXP_MEC->PJM
CLTF
0.81
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.297
LGEELTFEXP_LGEE->PJM
CLTF
0.297
WECLTFEXP_WEC->PJM
CLTF
0.15

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: 556X1_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: 556X1_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.91 %
Rating:1053.0 MVA
Rating Type:C
MVA to Mitigate:1420.61
MW Contribution:
6.24
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: 556X1_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.29 %
Rating:1053.0 MVA
Rating Type:C
MVA to Mitigate:1203.45
MW Contribution:
5.84
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
8.177
3151601KERR 3
50/50
0.58
3151611KERR 4
50/50
0.58
3151621KERR 5
50/50
0.58
3151631KERR 6
50/50
0.58
972205AH1-687 GEN
50/50
5.601
970683AG2-441 GEN
Solar/Wind Harmer
37.904
970681AG2-440 GEN
Solar/Wind Harmer
25.158
316486AD2-202 GEN
Solar/Wind Harmer
1.089
3144303KENBRDG
Solar/Wind Harmer
-0.032
316238AB2-078_GEN
Solar/Wind Harmer
1.192
316239AB2-077_GEN
Solar/Wind Harmer
1.192
946301AF1-294 GEN
Solar/Wind Harmer
10.145
3151531CLOVER1
50/50
8.237
3144293JTRSVLE
50/50
0.893
3144293JTRSVLE
50/50
0.705
3151591KERR 2
50/50
0.58
3151641KERR 7
50/50
0.58
3147043LAWRENC
50/50
1.543
3151931BEARGRDN S1
50/50
1.481
3151911BEARGRDN G1
50/50
1.146
970909AG2-566 GEN
50/50
4.436
3144293JTRSVLE
50/50
0.893
970535AG2-341 GEN
50/50
5.682
3151581KERR 1
50/50
0.207
3152661PLYWOOD A
50/50
0.594
3147133PAMPLIN
Solar/Wind Harmer
-0.048
3147133PAMPLIN
Solar/Wind Harmer
-0.038
961791AG1-021 GEN
Solar/Wind Harmer
4.949
3147173SINAI
Solar/Wind Harmer
-0.029
3147243WELCO
Solar/Wind Harmer
-0.018
971845AH1-439 GEN
Solar/Wind Harmer
14.423
316322AB2-045
Solar/Wind Harmer
0.882
970831AG2-522 GEN
Solar/Wind Harmer
10.906
946281AF1-292 GEN
Solar/Wind Harmer
0.185
3137643SOCKMAN
Solar/Wind Harmer
-0.032
270455AD2-022 GEN
Solar/Wind Harmer
1.34
270457AD2-023 GEN
Solar/Wind Harmer
0.679
316426AA2-053 GEN
Solar/Wind Harmer
0.696
970413AG2-270 GEN
50/50
35.874
3144293JTRSVLE
50/50
0.893
3151921BEARGRDN G2
50/50
1.146
959311AF2-222 GEN
Solar/Wind Harmer
55.27
964241AG1-285 GEN
Solar/Wind Harmer
40.008
3147133PAMPLIN
Solar/Wind Harmer
-0.15
316478AD1-087 GEN
Solar/Wind Harmer
3.717
942461AE2-259 GEN
Solar/Wind Harmer
6.193
970257AG2-171 GEN
Solar/Wind Harmer
14.994
971775AH1-396 GEN
Solar/Wind Harmer
2.821
3146926FARMVIL
Solar/Wind Harmer
-0.022
316003AC1-222 GEN
Solar/Wind Harmer
2.606
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.565
316123AC1-075 GEN
Solar/Wind Harmer
2.114
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
6.237
316222AC1-221 GEN
Solar/Wind Harmer
1.374
316283AC2-100 C
Solar/Wind Harmer
1.244
970221AG2-151 GEN
Solar/Wind Harmer
7.723
270494AE1-108_GEN
Solar/Wind Harmer
2.635
315821AE2-092 GEN
Solar/Wind Harmer
1.831
966621AG1-532 GEN
Solar/Wind Harmer
0.168
316181AB2-040 GEN
Solar/Wind Harmer
1.142
316217AC1-145 GEN
Solar/Wind Harmer
1.316
316197AC1-042 GEN
Solar/Wind Harmer
0.997
3147312GRETNA
Solar/Wind Harmer
-0.002
316190AA2-174 GEN
Solar/Wind Harmer
0.085
315693AD1-088 GEN
Solar/Wind Harmer
30.295
316034AC1-036 C
Solar/Wind Harmer
0.974
970685AG2-442 GEN
Solar/Wind Harmer
45.595
957481AF2-042 GEN
Solar/Wind Harmer
134.952
316131AB2-060 GEN
Solar/Wind Harmer
4.348
315785AD2-033 C
Solar/Wind Harmer
9.066
971563AH1-280 GEN
Solar/Wind Harmer
4.949
3146926FARMVIL
Solar/Wind Harmer
-0.022
970401AG2-262 GEN
Solar/Wind Harmer
2.195
3146776BUCKING
Solar/Wind Harmer
-0.01
971065AG2-659 GEN
Solar/Wind Harmer
12.502
316129AC1-054 GEN
Solar/Wind Harmer
2.064
971377AH1-170 GEN
Solar/Wind Harmer
1.545
3147623JAMES R
Solar/Wind Harmer
0.191
970937AG2-583 GEN
Solar/Wind Harmer
7.407
3147123OTTER R
Solar/Wind Harmer
-0.006
960081AF2-299 GEN
Solar/Wind Harmer
0.931
316087AB2-174 GEN
Solar/Wind Harmer
1.171
3147312GRETNA
Solar/Wind Harmer
-0.006
3146802CHATHAM
Solar/Wind Harmer
-0.006
941801AE2-185 GEN
Solar/Wind Harmer
3.042
3145783HORNRTN
Solar/Wind Harmer
-0.008
315773AC2-141 GEN
Solar/Wind Helper
2.589
970301AG2-198 GEN
Solar/Wind Harmer
23.362
970099AG2-077 GEN
Solar/Wind Harmer
53.981
313527AB2-043 GEN
Solar/Wind Harmer
6.568
970323AG2-213 GEN
Solar/Wind Harmer
19.992
316237AB2-079_GEN
Solar/Wind Harmer
1.192
958211AF2-115 GEN
Solar/Wind Harmer
6.186
315687AD1-152 GEN
Solar/Wind Harmer
4.368
962561AG1-105 GEN
Solar/Wind Harmer
19.502
964791AG1-342 GEN
Solar/Wind Harmer
7.184
3146843MT LREL
Solar/Wind Harmer
-0.033
3146843MT LREL
Solar/Wind Harmer
-0.033
316118AC1-105 GEN
Solar/Wind Harmer
2.136
316248AF1-058 C
Solar/Wind Harmer
0.864
3146776BUCKING
Solar/Wind Harmer
-0.105
3146776BUCKING
Solar/Wind Harmer
-0.009
942751AE2-291 GEN
Solar/Wind Harmer
11.067
313506AB2-031 GEN
Solar/Wind Harmer
0.658
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.067
942671AE2-283 GEN
Solar/Wind Harmer
2.687
3145783HORNRTN
Solar/Wind Harmer
0.906
3145783HORNRTN
Solar/Wind Harmer
0.725
3145783HORNRTN
Solar/Wind Harmer
0.227
3145783HORNRTN
Solar/Wind Harmer
0.091
316294AC1-161 GEN
Solar/Wind Helper
2.199
LAGNLTFEXP_LAGN->PJM
CLTF
1.677
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.687
TVALTFEXP_TVA->PJM
CLTF
0.848
CPLELTFEXP_CPLE->PJM
CLTF
2.778
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.834
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.355
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.901
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.296
LGEELTFEXP_LGEE->PJM
CLTF
0.296
WECLTFEXP_WEC->PJM
CLTF
0.15

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.74 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:751.6
MW Contribution:
15.29
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.476
316303AF2-085
50/50
1.951
3151541CLOVER2
50/50
2.251
3151601KERR 3
50/50
0.203
3151611KERR 4
50/50
0.203
3151621KERR 5
50/50
0.203
3151631KERR 6
50/50
0.203
963041AG1-153 GEN
50/50
2.01
315244AE2-183_ST
50/50
2.141
3151281ROARAP4
50/50
0.08
971285AH1-108 GEN
50/50
0.547
315779AE2-040
50/50
0.923
971845AH1-439 GEN
Solar/Wind Harmer
16.07
316258AE1-075 C
Solar/Wind Harmer
0.184
946301AF1-294 GEN
Solar/Wind Harmer
3.892
961791AG1-021 GEN
Solar/Wind Harmer
1.893
3144303KENBRDG
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
9.017
970681AG2-440 GEN
Solar/Wind Harmer
5.985
316486AD2-202 GEN
Solar/Wind Harmer
0.107
316233AE1-074 FULL
Solar/Wind Harmer
0.073
971281AH1-106 GEN
Solar/Wind Harmer
1.262
971283AH1-107 GEN
Solar/Wind Harmer
1.262
3151921BEARGRDN G2
50/50
4.191
3144293JTRSVLE
50/50
0.5
970413AG2-270 GEN
50/50
9.876
3151031BRUNSWICKG2
50/50
0.993
3151261ROARAP2
50/50
0.088
3150861SPRUNCD
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
972003AH1-546 GEN
Solar/Wind Harmer
15.285
3151931BEARGRDN S1
50/50
5.414
3151911BEARGRDN G1
50/50
4.191
3144293JTRSVLE
50/50
0.5
3144293JTRSVLE
50/50
0.394
970119AG2-088 GEN
50/50
14.635
3151531CLOVER1
50/50
2.268
3151591KERR 2
50/50
0.203
3151641KERR 7
50/50
0.203
3147043LAWRENC
50/50
0.857
3151051BRUNSWICKS1
50/50
2.06
3151021BRUNSWICKG1
50/50
0.993
971451AH1-221 GEN
50/50
3.014
315243AE2-183_GT3
50/50
1.235
3151281ROARAP4
50/50
0.085
3150851SPRUNCC
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
971377AH1-170 GEN
Solar/Wind Harmer
4.283
3147623JAMES R
Solar/Wind Harmer
0.93
970937AG2-583 GEN
Solar/Wind Harmer
22.933
3146776BUCKING
Solar/Wind Harmer
0.144
3146926FARMVIL
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
4.379
971563AH1-280 GEN
Solar/Wind Harmer
2.104
970685AG2-442 GEN
Solar/Wind Harmer
12.003
315785AD2-033 C
Solar/Wind Harmer
1.25
316034AC1-036 C
Solar/Wind Harmer
0.009
315693AD1-088 GEN
Solar/Wind Harmer
6.214
316131AB2-060 GEN
Solar/Wind Harmer
0.385
3143226MDLTHAN
Solar/Wind Harmer
0.11
957481AF2-042 GEN
Solar/Wind Harmer
28.268
970401AG2-262 GEN
Solar/Wind Harmer
0.589
971065AG2-659 GEN
Solar/Wind Harmer
3.89
3143526WINTERP
Solar/Wind Harmer
0.473
316129AC1-054 GEN
Solar/Wind Harmer
0.334
960081AF2-299 GEN
Solar/Wind Harmer
0.725
941031AE2-094 GEN
Solar/Wind Harmer
13.584
970919AG2-571 GEN
Solar/Wind Harmer
2.582
970087AG2-069 GEN
Solar/Wind Harmer
5.736
3145783HORNRTN
Solar/Wind Harmer
0.07
940641AE2-051 GEN
Solar/Wind Harmer
5.555
315607AA1-063A GEN
Solar/Wind Harmer
0.139
316023GEN1_S
Solar/Wind Harmer
0.149
939411AE1-173 GEN
Solar/Wind Harmer
28.41
3146263WOODLND
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.258
970831AG2-522 GEN
Solar/Wind Harmer
3.731
3147173SINAI
Solar/Wind Harmer
0.086
3147243WELCO
Solar/Wind Harmer
0.054
971967AH1-528 GEN
Solar/Wind Harmer
13.172
970673AG2-436 GEN
Solar/Wind Harmer
9.233
970533AG2-339 GEN
Solar/Wind Harmer
5.573
3137643SOCKMAN
Solar/Wind Harmer
0.289
970085AG2-068 GEN
Solar/Wind Harmer
3.824
970581AG2-369 GEN
Solar/Wind Harmer
3.288
316426AA2-053 GEN
Solar/Wind Harmer
0.234
3146043SEABORD
Solar/Wind Harmer
0.069
315814AE2-033 C
Solar/Wind Harmer
5.236
315652AC1-086 GEN
Solar/Wind Harmer
7.126
316274AC1-208 GEN
Solar/Wind Harmer
0.334
3145893MURPHYS
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.204
3145796HORNRTN
Solar/Wind Harmer
0.026
316210AC1-098 GEN
Solar/Wind Harmer
0.589
3146033SCOT NK
Solar/Wind Harmer
0.253
316463AE2-346 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
0.132
3145513AHOSKIE
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.125
3145683EARLEYS
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
0.062
316327AA2-057 GEN
Solar/Wind Harmer
0.092
3146206CASHIE
Solar/Wind Harmer
0.06
970601AG2-382 GEN
Solar/Wind Harmer
2.24
315732AD1-074 GEN1
Solar/Wind Harmer
0.338
315733AD1-074 GEN2
Solar/Wind Harmer
0.338
3130546PLYMOUTH
Solar/Wind Harmer
0.059
3143316POE
Solar/Wind Harmer
0.234
970657AG2-426 GEN
Solar/Wind Harmer
0.433
316311AC2-079 GEN
Solar/Wind Harmer
1.692
3130156CHOWAN
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.059
3146486SUNBURY
Solar/Wind Harmer
0.058
3146486SUNBURY
Solar/Wind Harmer
0.058
3145176PASQUOTANK
Solar/Wind Harmer
0.036
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3146406KITTY HAWK
Solar/Wind Harmer
0.007
957871AF2-081 GEN
Solar/Wind Harmer
2.894
957861AF2-080 GEN
Solar/Wind Harmer
2.505
316316AC1-027 C
Solar/Wind Harmer
0.055
3145746EVERETS
Solar/Wind Harmer
0.23
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151081ELIZAR1
Adder
5.3
3151091ELIZAR2
Adder
5.208
971445AH1-216 GEN
Solar/Wind Harmer
3.978
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.079
3148013FISHERV
Solar/Wind Helper
0.076
3148463FAIRFLD
Solar/Wind Helper
0.12
315616AA1-038_C
Solar/Wind Helper
0.544
3145893MURPHYS
Solar/Wind Harmer
0.287
3145796HORNRTN
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.064
3146173TUNIS
Solar/Wind Harmer
0.063
3145823KELFORD
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.062
3156021HOLLOMANSOL
Solar/Wind Harmer
0.273
3146233WITAKRS
Solar/Wind Harmer
0.241
3146206CASHIE
Solar/Wind Harmer
0.06
971547AH1-271 GEN
Solar/Wind Harmer
1.28
315737AD1-076 GEN
Solar/Wind Harmer
0.763
315816AE2-034 GEN
Solar/Wind Harmer
0.253
3145663CRESWEL
Solar/Wind Harmer
0.166
971163AH1-040 GEN
Solar/Wind Harmer
4.737
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.047
316381AD1-082 GEN
Solar/Wind Harmer
0.06
316359AB2-059 GEN
Solar/Wind Harmer
0.21
3142053HEARTS
Solar/Wind Harmer
0.104
3130156CHOWAN
Solar/Wind Harmer
0.059
316093AE2-104_GEN
Solar/Wind Harmer
0.99
3145963POPLR C
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.19
3146516WINFALL
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.259
319010AE1-072 C
Solar/Wind Harmer
0.29
3146293MARTNCO
Solar/Wind Harmer
0.054
3146456SLIGO L269
Solar/Wind Harmer
0.058
316494AC1-189 GEN
Solar/Wind Harmer
0.196
944591AF1-124 GEN
Solar/Wind Harmer
13.109
3142543TWELFTH
Solar/Wind Harmer
0.006
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.01
3150981CHESPKA
Adder
0.721
316072AD1-144
Solar/Wind Harmer
0.02
315671AE2-027_GEN
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.073
3145336SMITFLD
Solar/Wind Harmer
0.226
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.844
3147666LOUISA
Solar/Wind Helper
0.484
970221AG2-151 GEN
Solar/Wind Harmer
21.415
3146776BUCKING
Solar/Wind Harmer
0.13
270494AE1-108_GEN
Solar/Wind Harmer
3.742
3146926FARMVIL
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
3.722
942461AE2-259 GEN
Solar/Wind Harmer
0
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.598
970257AG2-171 GEN
Solar/Wind Harmer
5.176
971775AH1-396 GEN
Solar/Wind Harmer
0.259
959311AF2-222 GEN
Solar/Wind Harmer
12.78
964241AG1-285 GEN
Solar/Wind Harmer
8.638
958131AF2-107 GEN
Solar/Wind Harmer
3.491
316478AD1-087 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.054
971683AH1-343 GEN
Solar/Wind Harmer
2.762
944011AF1-069 GEN
Solar/Wind Harmer
4.438
316181AB2-040 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.456
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.065
316011AB1-132 GEN
Solar/Wind Harmer
1.175
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.064
316212AC1-099_GEN
Solar/Wind Harmer
0.328
3146173TUNIS
Solar/Wind Harmer
0.063
316123AC1-075 GEN
Solar/Wind Harmer
0.084
3145823KELFORD
Solar/Wind Harmer
0.063
315722AD1-056 GEN
Solar/Wind Harmer
2.107
3145273HOLLAND
Solar/Wind Harmer
0.046
316222AC1-221 GEN
Solar/Wind Harmer
0.25
3146233WITAKRS
Solar/Wind Harmer
0.304
3146233WITAKRS
Solar/Wind Harmer
0.041
3138543CONSLDL
Solar/Wind Harmer
0.04
316283AC2-100 C
Solar/Wind Harmer
0.118
3146206CASHIE
Solar/Wind Harmer
0.06
315735AD1-075 GEN1
Solar/Wind Harmer
0.169
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.059
315813AE1-149 C
Solar/Wind Harmer
3.146
970657AG2-426 GEN
Solar/Wind Harmer
1.323
971623AH1-311 GEN
Solar/Wind Harmer
0.118
3146376EDENTON
Solar/Wind Harmer
0.059
3145963POPLR C
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
4.163
316321Z2-027
Solar/Wind Harmer
0.01
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
316246AF1-032 C
Solar/Wind Harmer
0.026
3145933PARMELE
Solar/Wind Harmer
0.058
3146456SLIGO L269
Solar/Wind Harmer
0.058
971153AH1-033 GEN
Solar/Wind Harmer
0.672
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
944581AF1-123 GEN
Solar/Wind Harmer
13.062
944601AF1-125 GEN
Solar/Wind Harmer
12.861
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151101ELIZAR3
Adder
5.368
3144873MCLAUGH
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.023
316499AE2-029_GEN
Solar/Wind Helper
0.506
3132273ORANGE
Solar/Wind Helper
0.028
3148013FISHERV
Solar/Wind Helper
0.132
3147666LOUISA
Solar/Wind Helper
0.279
970909AG2-566 GEN
50/50
2.342
3144293JTRSVLE
50/50
0.5
970535AG2-341 GEN
50/50
1.944
3151581KERR 1
50/50
0.072
3152661PLYWOOD A
50/50
0.2
3151041BRUNSWICKG3
50/50
0.993
972187AH1-678 GEN
50/50
2.277
315242AE2-183_GT2
50/50
1.235
315241AE2-183_GT1
50/50
1.23
972185AH1-677 GEN
50/50
4.459
3151261ROARAP2
50/50
0.086
3146776BUCKING
Solar/Wind Harmer
1.442
3146776BUCKING
Solar/Wind Harmer
0.117
316336AC2-165 C
Solar/Wind Harmer
14.292
316313AB2-026
Solar/Wind Harmer
0.153
970301AG2-198 GEN
Solar/Wind Harmer
9.368
958211AF2-115 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.152
970323AG2-213 GEN
Solar/Wind Harmer
6.901
971223AH1-071 GEN
Solar/Wind Harmer
1.171
970099AG2-077 GEN
Solar/Wind Harmer
11.307
962561AG1-105 GEN
Solar/Wind Harmer
4.967
964791AG1-342 GEN
Solar/Wind Harmer
1.927
3146843MT LREL
Solar/Wind Harmer
0.1
3146843MT LREL
Solar/Wind Harmer
0.1
316118AC1-105 GEN
Solar/Wind Harmer
0.238
3143526WINTERP
Solar/Wind Harmer
0.473
970933AG2-581 GEN
Solar/Wind Harmer
7.1
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.089
3145783HORNRTN
Solar/Wind Harmer
1.252
3145783HORNRTN
Solar/Wind Harmer
1.001
3145783HORNRTN
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
0.125
316365GEN2_N
Solar/Wind Harmer
0.149
3144356SAPONY
Solar/Wind Harmer
0.553
316315AB2-025 C
Solar/Wind Harmer
0.053
962571AG1-106 GEN
Solar/Wind Harmer
0.922
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.039
3145893MURPHYS
Solar/Wind Harmer
0.431
3145893MURPHYS
Solar/Wind Harmer
0.116
3145796HORNRTN
Solar/Wind Harmer
0.192
3146173TUNIS
Solar/Wind Harmer
0.063
3146173TUNIS
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.022
315742AE1-103 GEN
Solar/Wind Harmer
0.922
315724AD1-057 GEN
Solar/Wind Harmer
1.175
316065AD1-022 GEN
Solar/Wind Harmer
2.754
315614AA2-178 GEN
Solar/Wind Harmer
0.337
316049AB1-081 GEN
Solar/Wind Harmer
0.335
316263AC1-034 GEN
Solar/Wind Harmer
2.24
316349AD2-085 GEN
Solar/Wind Harmer
0.039
3146376EDENTON
Solar/Wind Harmer
0.262
3146376EDENTON
Solar/Wind Harmer
0.262
315835AF2-110_GEN
Solar/Wind Harmer
0.404
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
1.041
3146386ELIZ CT
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.135
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
3130086AYDLETT
Solar/Wind Harmer
0.233
3145933PARMELE
Solar/Wind Harmer
0.116
3145933PARMELE
Solar/Wind Harmer
0.058
3137176SLIGO L2192
Solar/Wind Harmer
0.231
3146456SLIGO L269
Solar/Wind Harmer
1.029
316339AD2-160 GEN
Solar/Wind Harmer
0.093
316388AE2-253 GEN
Solar/Wind Harmer
0.181
3145506HICKORY
Solar/Wind Harmer
0.232
3145506HICKORY
Solar/Wind Harmer
0.139
3145506HICKORY
Solar/Wind Harmer
0.035
316005AA1-067
Solar/Wind Harmer
0.062
3150991CHESPKB
Adder
0.605
3150991CHESPKB
Adder
0.591
942751AE2-291 GEN
Solar/Wind Harmer
3.112
316294AC1-161 GEN
Solar/Wind Harmer
0.982
944641AF1-129 GEN
Adder
26.869
966001AG1-469 GEN
Solar/Wind Helper
0.199
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.033
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
1.45
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.449
TVALTFEXP_TVA->PJM
CLTF
0.709
CPLELTFEXP_CPLE->PJM
CLTF
3.819
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.496
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.173
MECLTFEXP_MEC->PJM
CLTF
0.182
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.464

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.38 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:715.22
MW Contribution:
20.23
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.24 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:938.23
MW Contribution:
20.31
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.184
3151911BEARGRDN G1
50/50
5.56
3144293JTRSVLE
50/50
0.584
3144293JTRSVLE
50/50
0.461
3151531CLOVER1
50/50
2.075
3151591KERR 2
50/50
0.188
3151641KERR 7
50/50
0.188
3147043LAWRENC
50/50
0.708
970937AG2-583 GEN
Solar/Wind Harmer
36.756
971377AH1-170 GEN
Solar/Wind Harmer
5.682
3147623JAMES R
Solar/Wind Harmer
1.234
3146776BUCKING
Solar/Wind Harmer
0.187
3146926FARMVIL
Solar/Wind Harmer
0.215
971563AH1-280 GEN
Solar/Wind Harmer
2.459
970685AG2-442 GEN
Solar/Wind Harmer
13.128
315785AD2-033 C
Solar/Wind Harmer
1.371
970909AG2-566 GEN
50/50
2.783
3144293JTRSVLE
50/50
0.584
970535AG2-341 GEN
50/50
1.879
3151581KERR 1
50/50
0.067
3152661PLYWOOD A
50/50
0.188
316336AC2-165 C
Solar/Wind Harmer
30.363
3146776BUCKING
Solar/Wind Harmer
1.867
3146776BUCKING
Solar/Wind Harmer
0.151
970301AG2-198 GEN
Solar/Wind Harmer
11.132
958211AF2-115 GEN
Solar/Wind Harmer
2.766
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
970323AG2-213 GEN
Solar/Wind Harmer
7.672
962561AG1-105 GEN
Solar/Wind Harmer
4.838
964791AG1-342 GEN
Solar/Wind Harmer
1.864
3146843MT LREL
Solar/Wind Harmer
0.097
3146843MT LREL
Solar/Wind Harmer
0.097
970099AG2-077 GEN
Solar/Wind Harmer
10.049
316118AC1-105 GEN
Solar/Wind Harmer
0.226
970933AG2-581 GEN
Solar/Wind Harmer
5.128
942751AE2-291 GEN
Solar/Wind Harmer
3.108
966001AG1-469 GEN
Solar/Wind Helper
0.155
972205AH1-687 GEN
50/50
27.167
3151541CLOVER2
50/50
2.06
3151601KERR 3
50/50
0.188
3151611KERR 4
50/50
0.188
3151621KERR 5
50/50
0.188
3151631KERR 6
50/50
0.188
971845AH1-439 GEN
Solar/Wind Harmer
20.749
946301AF1-294 GEN
Solar/Wind Harmer
4.549
961791AG1-021 GEN
Solar/Wind Harmer
2.213
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
9.617
970681AG2-440 GEN
Solar/Wind Harmer
6.383
316486AD2-202 GEN
Solar/Wind Harmer
0.098
3147173SINAI
Solar/Wind Harmer
0.08
3147243WELCO
Solar/Wind Harmer
0.05
970831AG2-522 GEN
Solar/Wind Harmer
3.162
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
316034AC1-036 C
Solar/Wind Harmer
0.01
315693AD1-088 GEN
Solar/Wind Harmer
6.208
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970401AG2-262 GEN
Solar/Wind Harmer
0.57
957481AF2-042 GEN
Solar/Wind Harmer
25.123
971065AG2-659 GEN
Solar/Wind Harmer
3.402
316129AC1-054 GEN
Solar/Wind Harmer
0.289
962751AG1-124 GEN
Solar/Wind Harmer
2.837
3151921BEARGRDN G2
50/50
5.56
3144293JTRSVLE
50/50
0.584
970413AG2-270 GEN
50/50
9.039
972003AH1-546 GEN
Solar/Wind Harmer
20.231
970221AG2-151 GEN
Solar/Wind Harmer
28.409
3146776BUCKING
Solar/Wind Harmer
0.168
270494AE1-108_GEN
Solar/Wind Harmer
4.971
3146926FARMVIL
Solar/Wind Harmer
0.215
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.689
970257AG2-171 GEN
Solar/Wind Harmer
5.754
971775AH1-396 GEN
Solar/Wind Harmer
0.288
958131AF2-107 GEN
Solar/Wind Harmer
4.68
959311AF2-222 GEN
Solar/Wind Harmer
13.458
964241AG1-285 GEN
Solar/Wind Harmer
8.766
316478AD1-087 GEN
Solar/Wind Harmer
0.335
3147043LAWRENC
Solar/Wind Harmer
0.044
971683AH1-343 GEN
Solar/Wind Harmer
2.624
316123AC1-075 GEN
Solar/Wind Harmer
0.082
LAGNLTFEXP_LAGN->PJM
CLTF
1.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.485
TVALTFEXP_TVA->PJM
CLTF
0.56
CPLELTFEXP_CPLE->PJM
CLTF
2.765
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.492
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.743
MECLTFEXP_MEC->PJM
CLTF
0.187
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.403
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.99 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:734.51
MW Contribution:
15.29
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.414
3151911BEARGRDN G1
50/50
4.191
3144293JTRSVLE
50/50
0.5
3144293JTRSVLE
50/50
0.394
970119AG2-088 GEN
50/50
14.635
3151531CLOVER1
50/50
2.268
3151591KERR 2
50/50
0.203
3151641KERR 7
50/50
0.203
3147043LAWRENC
50/50
0.857
3151051BRUNSWICKS1
50/50
2.06
3151021BRUNSWICKG1
50/50
0.993
971451AH1-221 GEN
50/50
3.014
315243AE2-183_GT3
50/50
1.235
3151281ROARAP4
50/50
0.085
3150851SPRUNCC
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
971377AH1-170 GEN
Solar/Wind Harmer
4.283
3147623JAMES R
Solar/Wind Harmer
0.93
970937AG2-583 GEN
Solar/Wind Harmer
22.933
3146776BUCKING
Solar/Wind Harmer
0.144
3146926FARMVIL
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
4.379
971563AH1-280 GEN
Solar/Wind Harmer
2.104
970685AG2-442 GEN
Solar/Wind Harmer
12.003
315785AD2-033 C
Solar/Wind Harmer
1.25
316034AC1-036 C
Solar/Wind Harmer
0.009
315693AD1-088 GEN
Solar/Wind Harmer
6.214
316131AB2-060 GEN
Solar/Wind Harmer
0.385
3143226MDLTHAN
Solar/Wind Harmer
0.11
957481AF2-042 GEN
Solar/Wind Harmer
28.268
970401AG2-262 GEN
Solar/Wind Harmer
0.589
971065AG2-659 GEN
Solar/Wind Harmer
3.89
3143526WINTERP
Solar/Wind Harmer
0.473
316129AC1-054 GEN
Solar/Wind Harmer
0.334
960081AF2-299 GEN
Solar/Wind Harmer
0.725
941031AE2-094 GEN
Solar/Wind Harmer
13.584
970919AG2-571 GEN
Solar/Wind Harmer
2.582
970087AG2-069 GEN
Solar/Wind Harmer
5.736
3145783HORNRTN
Solar/Wind Harmer
0.07
940641AE2-051 GEN
Solar/Wind Harmer
5.555
315607AA1-063A GEN
Solar/Wind Harmer
0.139
316023GEN1_S
Solar/Wind Harmer
0.149
939411AE1-173 GEN
Solar/Wind Harmer
28.41
3146263WOODLND
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.258
3145893MURPHYS
Solar/Wind Harmer
0.287
3145796HORNRTN
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.064
3146173TUNIS
Solar/Wind Harmer
0.063
3145823KELFORD
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.062
3156021HOLLOMANSOL
Solar/Wind Harmer
0.273
3146233WITAKRS
Solar/Wind Harmer
0.241
3146206CASHIE
Solar/Wind Harmer
0.06
971547AH1-271 GEN
Solar/Wind Harmer
1.28
315737AD1-076 GEN
Solar/Wind Harmer
0.763
315816AE2-034 GEN
Solar/Wind Harmer
0.253
3145663CRESWEL
Solar/Wind Harmer
0.166
971163AH1-040 GEN
Solar/Wind Harmer
4.737
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.047
316381AD1-082 GEN
Solar/Wind Harmer
0.06
316359AB2-059 GEN
Solar/Wind Harmer
0.21
3142053HEARTS
Solar/Wind Harmer
0.104
972205AH1-687 GEN
50/50
20.476
316303AF2-085
50/50
1.951
3151541CLOVER2
50/50
2.251
3151601KERR 3
50/50
0.203
3151611KERR 4
50/50
0.203
3151621KERR 5
50/50
0.203
3151631KERR 6
50/50
0.203
963041AG1-153 GEN
50/50
2.01
315244AE2-183_ST
50/50
2.141
3151281ROARAP4
50/50
0.08
971285AH1-108 GEN
50/50
0.547
315779AE2-040
50/50
0.923
971845AH1-439 GEN
Solar/Wind Harmer
16.07
316258AE1-075 C
Solar/Wind Harmer
0.184
946301AF1-294 GEN
Solar/Wind Harmer
3.892
961791AG1-021 GEN
Solar/Wind Harmer
1.893
3144303KENBRDG
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
9.017
970681AG2-440 GEN
Solar/Wind Harmer
5.985
316486AD2-202 GEN
Solar/Wind Harmer
0.107
316233AE1-074 FULL
Solar/Wind Harmer
0.073
971281AH1-106 GEN
Solar/Wind Harmer
1.262
971283AH1-107 GEN
Solar/Wind Harmer
1.262
970831AG2-522 GEN
Solar/Wind Harmer
3.731
3147173SINAI
Solar/Wind Harmer
0.086
3147243WELCO
Solar/Wind Harmer
0.054
971967AH1-528 GEN
Solar/Wind Harmer
13.172
970673AG2-436 GEN
Solar/Wind Harmer
9.233
970533AG2-339 GEN
Solar/Wind Harmer
5.573
3137643SOCKMAN
Solar/Wind Harmer
0.289
970085AG2-068 GEN
Solar/Wind Harmer
3.824
970581AG2-369 GEN
Solar/Wind Harmer
3.288
316426AA2-053 GEN
Solar/Wind Harmer
0.234
3146043SEABORD
Solar/Wind Harmer
0.069
315814AE2-033 C
Solar/Wind Harmer
5.236
315652AC1-086 GEN
Solar/Wind Harmer
7.126
316274AC1-208 GEN
Solar/Wind Harmer
0.334
3145893MURPHYS
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.204
3145796HORNRTN
Solar/Wind Harmer
0.026
316210AC1-098 GEN
Solar/Wind Harmer
0.589
3146033SCOT NK
Solar/Wind Harmer
0.253
316463AE2-346 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
0.132
3145513AHOSKIE
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.125
3145683EARLEYS
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
0.062
316327AA2-057 GEN
Solar/Wind Harmer
0.092
3146206CASHIE
Solar/Wind Harmer
0.06
970601AG2-382 GEN
Solar/Wind Harmer
2.24
315732AD1-074 GEN1
Solar/Wind Harmer
0.338
315733AD1-074 GEN2
Solar/Wind Harmer
0.338
3130546PLYMOUTH
Solar/Wind Harmer
0.059
3143316POE
Solar/Wind Harmer
0.234
970657AG2-426 GEN
Solar/Wind Harmer
0.433
316311AC2-079 GEN
Solar/Wind Harmer
1.692
3130156CHOWAN
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.059
3146486SUNBURY
Solar/Wind Harmer
0.058
3146486SUNBURY
Solar/Wind Harmer
0.058
3145176PASQUOTANK
Solar/Wind Harmer
0.036
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3146406KITTY HAWK
Solar/Wind Harmer
0.007
957871AF2-081 GEN
Solar/Wind Harmer
2.894
957861AF2-080 GEN
Solar/Wind Harmer
2.505
316316AC1-027 C
Solar/Wind Harmer
0.055
3145746EVERETS
Solar/Wind Harmer
0.23
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151081ELIZAR1
Adder
5.3
3151091ELIZAR2
Adder
5.208
971445AH1-216 GEN
Solar/Wind Harmer
3.978
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.079
3148013FISHERV
Solar/Wind Helper
0.076
3148463FAIRFLD
Solar/Wind Helper
0.12
315616AA1-038_C
Solar/Wind Helper
0.544
3151921BEARGRDN G2
50/50
4.191
3144293JTRSVLE
50/50
0.5
970413AG2-270 GEN
50/50
9.876
3151031BRUNSWICKG2
50/50
0.993
3151261ROARAP2
50/50
0.088
3150861SPRUNCD
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
972003AH1-546 GEN
Solar/Wind Harmer
15.285
970221AG2-151 GEN
Solar/Wind Harmer
21.415
3146776BUCKING
Solar/Wind Harmer
0.13
270494AE1-108_GEN
Solar/Wind Harmer
3.742
3146926FARMVIL
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
3.722
942461AE2-259 GEN
Solar/Wind Harmer
0
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.598
970257AG2-171 GEN
Solar/Wind Harmer
5.176
971775AH1-396 GEN
Solar/Wind Harmer
0.259
959311AF2-222 GEN
Solar/Wind Harmer
12.78
964241AG1-285 GEN
Solar/Wind Harmer
8.638
958131AF2-107 GEN
Solar/Wind Harmer
3.491
316478AD1-087 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.054
971683AH1-343 GEN
Solar/Wind Harmer
2.762
944011AF1-069 GEN
Solar/Wind Harmer
4.438
316181AB2-040 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.456
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.065
316011AB1-132 GEN
Solar/Wind Harmer
1.175
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.064
316212AC1-099_GEN
Solar/Wind Harmer
0.328
3146173TUNIS
Solar/Wind Harmer
0.063
316123AC1-075 GEN
Solar/Wind Harmer
0.084
3145823KELFORD
Solar/Wind Harmer
0.063
315722AD1-056 GEN
Solar/Wind Harmer
2.107
3145273HOLLAND
Solar/Wind Harmer
0.046
316222AC1-221 GEN
Solar/Wind Harmer
0.25
3146233WITAKRS
Solar/Wind Harmer
0.304
3146233WITAKRS
Solar/Wind Harmer
0.041
3138543CONSLDL
Solar/Wind Harmer
0.04
316283AC2-100 C
Solar/Wind Harmer
0.118
3146206CASHIE
Solar/Wind Harmer
0.06
315735AD1-075 GEN1
Solar/Wind Harmer
0.169
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.059
315813AE1-149 C
Solar/Wind Harmer
3.146
970657AG2-426 GEN
Solar/Wind Harmer
1.323
971623AH1-311 GEN
Solar/Wind Harmer
0.118
3146376EDENTON
Solar/Wind Harmer
0.059
3145963POPLR C
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
4.163
316321Z2-027
Solar/Wind Harmer
0.01
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
316246AF1-032 C
Solar/Wind Harmer
0.026
3145933PARMELE
Solar/Wind Harmer
0.058
3146456SLIGO L269
Solar/Wind Harmer
0.058
971153AH1-033 GEN
Solar/Wind Harmer
0.672
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
944581AF1-123 GEN
Solar/Wind Harmer
13.062
944601AF1-125 GEN
Solar/Wind Harmer
12.861
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151101ELIZAR3
Adder
5.368
3144873MCLAUGH
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.023
316499AE2-029_GEN
Solar/Wind Helper
0.506
3132273ORANGE
Solar/Wind Helper
0.028
3148013FISHERV
Solar/Wind Helper
0.132
3147666LOUISA
Solar/Wind Helper
0.279
3130156CHOWAN
Solar/Wind Harmer
0.059
316093AE2-104_GEN
Solar/Wind Harmer
0.99
3145963POPLR C
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.19
3146516WINFALL
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.259
319010AE1-072 C
Solar/Wind Harmer
0.29
3146293MARTNCO
Solar/Wind Harmer
0.054
3146456SLIGO L269
Solar/Wind Harmer
0.058
316494AC1-189 GEN
Solar/Wind Harmer
0.196
944591AF1-124 GEN
Solar/Wind Harmer
13.109
3142543TWELFTH
Solar/Wind Harmer
0.006
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.01
3150981CHESPKA
Adder
0.721
316072AD1-144
Solar/Wind Harmer
0.02
315671AE2-027_GEN
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.073
3145336SMITFLD
Solar/Wind Harmer
0.226
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.844
3147666LOUISA
Solar/Wind Helper
0.484
970909AG2-566 GEN
50/50
2.342
3144293JTRSVLE
50/50
0.5
970535AG2-341 GEN
50/50
1.944
3151581KERR 1
50/50
0.072
3152661PLYWOOD A
50/50
0.2
3151041BRUNSWICKG3
50/50
0.993
972187AH1-678 GEN
50/50
2.277
315242AE2-183_GT2
50/50
1.235
315241AE2-183_GT1
50/50
1.23
972185AH1-677 GEN
50/50
4.459
3151261ROARAP2
50/50
0.086
3146776BUCKING
Solar/Wind Harmer
1.442
3146776BUCKING
Solar/Wind Harmer
0.117
316336AC2-165 C
Solar/Wind Harmer
14.292
316313AB2-026
Solar/Wind Harmer
0.153
970301AG2-198 GEN
Solar/Wind Harmer
9.368
958211AF2-115 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.152
970323AG2-213 GEN
Solar/Wind Harmer
6.901
971223AH1-071 GEN
Solar/Wind Harmer
1.171
970099AG2-077 GEN
Solar/Wind Harmer
11.307
962561AG1-105 GEN
Solar/Wind Harmer
4.967
964791AG1-342 GEN
Solar/Wind Harmer
1.927
3146843MT LREL
Solar/Wind Harmer
0.1
3146843MT LREL
Solar/Wind Harmer
0.1
316118AC1-105 GEN
Solar/Wind Harmer
0.238
3143526WINTERP
Solar/Wind Harmer
0.473
970933AG2-581 GEN
Solar/Wind Harmer
7.1
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.089
3145783HORNRTN
Solar/Wind Harmer
1.252
3145783HORNRTN
Solar/Wind Harmer
1.001
3145783HORNRTN
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
0.125
316365GEN2_N
Solar/Wind Harmer
0.149
3144356SAPONY
Solar/Wind Harmer
0.553
316315AB2-025 C
Solar/Wind Harmer
0.053
962571AG1-106 GEN
Solar/Wind Harmer
0.922
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.039
3145893MURPHYS
Solar/Wind Harmer
0.431
3145893MURPHYS
Solar/Wind Harmer
0.116
3145796HORNRTN
Solar/Wind Harmer
0.192
3146173TUNIS
Solar/Wind Harmer
0.063
3146173TUNIS
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.022
315742AE1-103 GEN
Solar/Wind Harmer
0.922
315724AD1-057 GEN
Solar/Wind Harmer
1.175
316065AD1-022 GEN
Solar/Wind Harmer
2.754
315614AA2-178 GEN
Solar/Wind Harmer
0.337
316049AB1-081 GEN
Solar/Wind Harmer
0.335
316263AC1-034 GEN
Solar/Wind Harmer
2.24
316349AD2-085 GEN
Solar/Wind Harmer
0.039
3146376EDENTON
Solar/Wind Harmer
0.262
3146376EDENTON
Solar/Wind Harmer
0.262
315835AF2-110_GEN
Solar/Wind Harmer
0.404
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
1.041
3146386ELIZ CT
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.135
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
3130086AYDLETT
Solar/Wind Harmer
0.233
3145933PARMELE
Solar/Wind Harmer
0.116
3145933PARMELE
Solar/Wind Harmer
0.058
3137176SLIGO L2192
Solar/Wind Harmer
0.231
3146456SLIGO L269
Solar/Wind Harmer
1.029
316339AD2-160 GEN
Solar/Wind Harmer
0.093
316388AE2-253 GEN
Solar/Wind Harmer
0.181
3145506HICKORY
Solar/Wind Harmer
0.232
3145506HICKORY
Solar/Wind Harmer
0.139
3145506HICKORY
Solar/Wind Harmer
0.035
316005AA1-067
Solar/Wind Harmer
0.062
3150991CHESPKB
Adder
0.605
3150991CHESPKB
Adder
0.591
942751AE2-291 GEN
Solar/Wind Harmer
3.112
316294AC1-161 GEN
Solar/Wind Harmer
0.982
944641AF1-129 GEN
Adder
26.869
966001AG1-469 GEN
Solar/Wind Helper
0.199
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.033
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
1.45
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.449
TVALTFEXP_TVA->PJM
CLTF
0.709
CPLELTFEXP_CPLE->PJM
CLTF
3.819
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.496
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.173
MECLTFEXP_MEC->PJM
CLTF
0.182
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.464

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.47 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:697.98
MW Contribution:
20.23
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.17 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:920.95
MW Contribution:
20.31
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.184
3151911BEARGRDN G1
50/50
5.56
3144293JTRSVLE
50/50
0.584
3144293JTRSVLE
50/50
0.461
3151531CLOVER1
50/50
2.075
3151591KERR 2
50/50
0.188
3151641KERR 7
50/50
0.188
3147043LAWRENC
50/50
0.708
970937AG2-583 GEN
Solar/Wind Harmer
36.756
971377AH1-170 GEN
Solar/Wind Harmer
5.682
3147623JAMES R
Solar/Wind Harmer
1.234
3146776BUCKING
Solar/Wind Harmer
0.187
3146926FARMVIL
Solar/Wind Harmer
0.215
971563AH1-280 GEN
Solar/Wind Harmer
2.459
970685AG2-442 GEN
Solar/Wind Harmer
13.128
315785AD2-033 C
Solar/Wind Harmer
1.371
316034AC1-036 C
Solar/Wind Harmer
0.01
315693AD1-088 GEN
Solar/Wind Harmer
6.208
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970401AG2-262 GEN
Solar/Wind Harmer
0.57
957481AF2-042 GEN
Solar/Wind Harmer
25.123
971065AG2-659 GEN
Solar/Wind Harmer
3.402
316129AC1-054 GEN
Solar/Wind Harmer
0.289
962751AG1-124 GEN
Solar/Wind Harmer
2.837
970909AG2-566 GEN
50/50
2.783
3144293JTRSVLE
50/50
0.584
970535AG2-341 GEN
50/50
1.879
3151581KERR 1
50/50
0.067
3152661PLYWOOD A
50/50
0.188
316336AC2-165 C
Solar/Wind Harmer
30.363
3146776BUCKING
Solar/Wind Harmer
1.867
3146776BUCKING
Solar/Wind Harmer
0.151
970301AG2-198 GEN
Solar/Wind Harmer
11.132
958211AF2-115 GEN
Solar/Wind Harmer
2.766
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
970323AG2-213 GEN
Solar/Wind Harmer
7.672
962561AG1-105 GEN
Solar/Wind Harmer
4.838
964791AG1-342 GEN
Solar/Wind Harmer
1.864
3146843MT LREL
Solar/Wind Harmer
0.097
3146843MT LREL
Solar/Wind Harmer
0.097
970099AG2-077 GEN
Solar/Wind Harmer
10.049
316118AC1-105 GEN
Solar/Wind Harmer
0.226
970933AG2-581 GEN
Solar/Wind Harmer
5.128
942751AE2-291 GEN
Solar/Wind Harmer
3.108
966001AG1-469 GEN
Solar/Wind Helper
0.155
972205AH1-687 GEN
50/50
27.167
3151541CLOVER2
50/50
2.06
3151601KERR 3
50/50
0.188
3151611KERR 4
50/50
0.188
3151621KERR 5
50/50
0.188
3151631KERR 6
50/50
0.188
971845AH1-439 GEN
Solar/Wind Harmer
20.749
946301AF1-294 GEN
Solar/Wind Harmer
4.549
961791AG1-021 GEN
Solar/Wind Harmer
2.213
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
9.617
970681AG2-440 GEN
Solar/Wind Harmer
6.383
316486AD2-202 GEN
Solar/Wind Harmer
0.098
3147173SINAI
Solar/Wind Harmer
0.08
3147243WELCO
Solar/Wind Harmer
0.05
970831AG2-522 GEN
Solar/Wind Harmer
3.162
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151921BEARGRDN G2
50/50
5.56
3144293JTRSVLE
50/50
0.584
970413AG2-270 GEN
50/50
9.039
972003AH1-546 GEN
Solar/Wind Harmer
20.231
970221AG2-151 GEN
Solar/Wind Harmer
28.409
3146776BUCKING
Solar/Wind Harmer
0.168
270494AE1-108_GEN
Solar/Wind Harmer
4.971
3146926FARMVIL
Solar/Wind Harmer
0.215
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.689
970257AG2-171 GEN
Solar/Wind Harmer
5.754
971775AH1-396 GEN
Solar/Wind Harmer
0.288
958131AF2-107 GEN
Solar/Wind Harmer
4.68
959311AF2-222 GEN
Solar/Wind Harmer
13.458
964241AG1-285 GEN
Solar/Wind Harmer
8.766
316478AD1-087 GEN
Solar/Wind Harmer
0.335
3147043LAWRENC
Solar/Wind Harmer
0.044
971683AH1-343 GEN
Solar/Wind Harmer
2.624
316123AC1-075 GEN
Solar/Wind Harmer
0.082
LAGNLTFEXP_LAGN->PJM
CLTF
1.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.485
TVALTFEXP_TVA->PJM
CLTF
0.56
CPLELTFEXP_CPLE->PJM
CLTF
2.765
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.492
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.743
MECLTFEXP_MEC->PJM
CLTF
0.187
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.403
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.19 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:810.51
MW Contribution:
26.64
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.99 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1043.51
MW Contribution:
26.74
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.184
3151911BEARGRDN G1
50/50
5.56
3144293JTRSVLE
50/50
0.584
3144293JTRSVLE
50/50
0.461
970937AG2-583 GEN
Solar/Wind Harmer
48.395
971377AH1-170 GEN
Solar/Wind Harmer
7.481
3147623JAMES R
Solar/Wind Harmer
0.926
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
971563AH1-280 GEN
Solar/Wind Harmer
3.238
970685AG2-442 GEN
Solar/Wind Harmer
17.285
315785AD2-033 C
Solar/Wind Harmer
4.309
316034AC1-036 C
Solar/Wind Harmer
0.308
315693AD1-088 GEN
Solar/Wind Harmer
7.265
316131AB2-060 GEN
Solar/Wind Harmer
1.515
970401AG2-262 GEN
Solar/Wind Harmer
0.712
957481AF2-042 GEN
Solar/Wind Harmer
33.079
971065AG2-659 GEN
Solar/Wind Harmer
4.479
316129AC1-054 GEN
Solar/Wind Harmer
0.759
3151921BEARGRDN G2
50/50
5.56
3144293JTRSVLE
50/50
0.584
972003AH1-546 GEN
Solar/Wind Harmer
26.637
970221AG2-151 GEN
Solar/Wind Harmer
37.406
3146776BUCKING
Solar/Wind Harmer
-0.019
270494AE1-108_GEN
Solar/Wind Harmer
12.155
3146926FARMVIL
Solar/Wind Harmer
-0.024
315821AE2-092 GEN
Solar/Wind Harmer
7.738
942461AE2-259 GEN
Solar/Wind Harmer
4.887
3147133PAMPLIN
Solar/Wind Harmer
-0.077
970257AG2-171 GEN
Solar/Wind Harmer
7.576
971775AH1-396 GEN
Solar/Wind Harmer
1.425
958131AF2-107 GEN
Solar/Wind Harmer
6.23
959311AF2-222 GEN
Solar/Wind Harmer
17.755
964241AG1-285 GEN
Solar/Wind Harmer
11.542
316478AD1-087 GEN
Solar/Wind Harmer
0.938
316003AC1-222 GEN
Solar/Wind Harmer
0.829
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.455
316123AC1-075 GEN
Solar/Wind Harmer
0.746
972205AH1-687 GEN
50/50
27.167
316322AB2-045
Solar/Wind Harmer
1.761
971845AH1-439 GEN
Solar/Wind Harmer
27.32
946301AF1-294 GEN
Solar/Wind Harmer
6.637
961791AG1-021 GEN
Solar/Wind Harmer
3.238
3144303KENBRDG
Solar/Wind Harmer
-0.016
970683AG2-441 GEN
Solar/Wind Harmer
12.663
970681AG2-440 GEN
Solar/Wind Harmer
8.405
316238AB2-078_GEN
Solar/Wind Harmer
0.4
316239AB2-077_GEN
Solar/Wind Harmer
0.4
316486AD2-202 GEN
Solar/Wind Harmer
0.275
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.163
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3147043LAWRENC
Adder
0.667
962751AG1-124 GEN
Solar/Wind Harmer
4.142
970909AG2-566 GEN
50/50
2.783
3144293JTRSVLE
50/50
0.584
316336AC2-165 C
Solar/Wind Harmer
42.04
3146776BUCKING
Solar/Wind Harmer
-0.209
3146776BUCKING
Solar/Wind Harmer
-0.017
970301AG2-198 GEN
Solar/Wind Harmer
14.657
958211AF2-115 GEN
Solar/Wind Harmer
4.047
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
970323AG2-213 GEN
Solar/Wind Harmer
10.101
313527AB2-043 GEN
Solar/Wind Harmer
2.211
316237AB2-079_GEN
Solar/Wind Harmer
0.4
962561AG1-105 GEN
Solar/Wind Harmer
6.37
964791AG1-342 GEN
Solar/Wind Harmer
2.33
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.232
316118AC1-105 GEN
Solar/Wind Harmer
0.68
315687AD1-152 GEN
Solar/Wind Harmer
1.173
316248AF1-058 C
Solar/Wind Harmer
0.269
970933AG2-581 GEN
Solar/Wind Harmer
6.752
942751AE2-291 GEN
Solar/Wind Harmer
4.092
966001AG1-469 GEN
Solar/Wind Helper
0.155
LAGNLTFEXP_LAGN->PJM
CLTF
1.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.485
TVALTFEXP_TVA->PJM
CLTF
0.56
CPLELTFEXP_CPLE->PJM
CLTF
2.765
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.492
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.743
MECLTFEXP_MEC->PJM
CLTF
0.187
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.403
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.19 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:810.51
MW Contribution:
26.64
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
27.167
316322AB2-045
Solar/Wind Harmer
1.761
971845AH1-439 GEN
Solar/Wind Harmer
27.32
946301AF1-294 GEN
Solar/Wind Harmer
6.637
961791AG1-021 GEN
Solar/Wind Harmer
3.238
3144303KENBRDG
Solar/Wind Harmer
-0.016
970683AG2-441 GEN
Solar/Wind Harmer
12.663
970681AG2-440 GEN
Solar/Wind Harmer
8.405
316238AB2-078_GEN
Solar/Wind Harmer
0.4
316239AB2-077_GEN
Solar/Wind Harmer
0.4
316486AD2-202 GEN
Solar/Wind Harmer
0.275
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.163
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151931BEARGRDN S1
50/50
7.184
3151911BEARGRDN G1
50/50
5.56
3144293JTRSVLE
50/50
0.584
3144293JTRSVLE
50/50
0.461
970937AG2-583 GEN
Solar/Wind Harmer
48.395
971377AH1-170 GEN
Solar/Wind Harmer
7.481
3147623JAMES R
Solar/Wind Harmer
0.926
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
971563AH1-280 GEN
Solar/Wind Harmer
3.238
970685AG2-442 GEN
Solar/Wind Harmer
17.285
315785AD2-033 C
Solar/Wind Harmer
4.309
316034AC1-036 C
Solar/Wind Harmer
0.308
315693AD1-088 GEN
Solar/Wind Harmer
7.265
316131AB2-060 GEN
Solar/Wind Harmer
1.515
970401AG2-262 GEN
Solar/Wind Harmer
0.712
957481AF2-042 GEN
Solar/Wind Harmer
33.079
971065AG2-659 GEN
Solar/Wind Harmer
4.479
316129AC1-054 GEN
Solar/Wind Harmer
0.759
3147043LAWRENC
Adder
0.667
962751AG1-124 GEN
Solar/Wind Harmer
4.142
3151921BEARGRDN G2
50/50
5.56
3144293JTRSVLE
50/50
0.584
972003AH1-546 GEN
Solar/Wind Harmer
26.637
970221AG2-151 GEN
Solar/Wind Harmer
37.406
3146776BUCKING
Solar/Wind Harmer
-0.019
270494AE1-108_GEN
Solar/Wind Harmer
12.155
3146926FARMVIL
Solar/Wind Harmer
-0.024
315821AE2-092 GEN
Solar/Wind Harmer
7.738
942461AE2-259 GEN
Solar/Wind Harmer
4.887
3147133PAMPLIN
Solar/Wind Harmer
-0.077
970257AG2-171 GEN
Solar/Wind Harmer
7.576
971775AH1-396 GEN
Solar/Wind Harmer
1.425
958131AF2-107 GEN
Solar/Wind Harmer
6.23
959311AF2-222 GEN
Solar/Wind Harmer
17.755
964241AG1-285 GEN
Solar/Wind Harmer
11.542
316478AD1-087 GEN
Solar/Wind Harmer
0.938
316003AC1-222 GEN
Solar/Wind Harmer
0.829
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.455
316123AC1-075 GEN
Solar/Wind Harmer
0.746
970909AG2-566 GEN
50/50
2.783
3144293JTRSVLE
50/50
0.584
316336AC2-165 C
Solar/Wind Harmer
42.04
3146776BUCKING
Solar/Wind Harmer
-0.209
3146776BUCKING
Solar/Wind Harmer
-0.017
970301AG2-198 GEN
Solar/Wind Harmer
14.657
958211AF2-115 GEN
Solar/Wind Harmer
4.047
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
970323AG2-213 GEN
Solar/Wind Harmer
10.101
313527AB2-043 GEN
Solar/Wind Harmer
2.211
316237AB2-079_GEN
Solar/Wind Harmer
0.4
962561AG1-105 GEN
Solar/Wind Harmer
6.37
964791AG1-342 GEN
Solar/Wind Harmer
2.33
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.232
316118AC1-105 GEN
Solar/Wind Harmer
0.68
315687AD1-152 GEN
Solar/Wind Harmer
1.173
316248AF1-058 C
Solar/Wind Harmer
0.269
970933AG2-581 GEN
Solar/Wind Harmer
6.752
942751AE2-291 GEN
Solar/Wind Harmer
4.092
966001AG1-469 GEN
Solar/Wind Helper
0.155
LAGNLTFEXP_LAGN->PJM
CLTF
1.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.485
TVALTFEXP_TVA->PJM
CLTF
0.56
CPLELTFEXP_CPLE->PJM
CLTF
2.765
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.492
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.743
MECLTFEXP_MEC->PJM
CLTF
0.187
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.403
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.84 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:713.66
MW Contribution:
15.29
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.476
316303AF2-085
50/50
1.951
3151541CLOVER2
50/50
2.251
3151601KERR 3
50/50
0.203
3151611KERR 4
50/50
0.203
3151621KERR 5
50/50
0.203
3151631KERR 6
50/50
0.203
963041AG1-153 GEN
50/50
2.01
315244AE2-183_ST
50/50
2.141
3151281ROARAP4
50/50
0.08
971285AH1-108 GEN
50/50
0.547
315779AE2-040
50/50
0.923
971845AH1-439 GEN
Solar/Wind Harmer
16.07
316258AE1-075 C
Solar/Wind Harmer
0.184
946301AF1-294 GEN
Solar/Wind Harmer
3.892
961791AG1-021 GEN
Solar/Wind Harmer
1.893
3144303KENBRDG
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
9.017
970681AG2-440 GEN
Solar/Wind Harmer
5.985
316486AD2-202 GEN
Solar/Wind Harmer
0.107
316233AE1-074 FULL
Solar/Wind Harmer
0.073
971281AH1-106 GEN
Solar/Wind Harmer
1.262
971283AH1-107 GEN
Solar/Wind Harmer
1.262
970831AG2-522 GEN
Solar/Wind Harmer
3.731
3147173SINAI
Solar/Wind Harmer
0.086
3147243WELCO
Solar/Wind Harmer
0.054
971967AH1-528 GEN
Solar/Wind Harmer
13.172
970673AG2-436 GEN
Solar/Wind Harmer
9.233
970533AG2-339 GEN
Solar/Wind Harmer
5.573
3137643SOCKMAN
Solar/Wind Harmer
0.289
970085AG2-068 GEN
Solar/Wind Harmer
3.824
970581AG2-369 GEN
Solar/Wind Harmer
3.288
316426AA2-053 GEN
Solar/Wind Harmer
0.234
3146043SEABORD
Solar/Wind Harmer
0.069
315814AE2-033 C
Solar/Wind Harmer
5.236
315652AC1-086 GEN
Solar/Wind Harmer
7.126
316274AC1-208 GEN
Solar/Wind Harmer
0.334
3145893MURPHYS
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.204
3145796HORNRTN
Solar/Wind Harmer
0.026
316210AC1-098 GEN
Solar/Wind Harmer
0.589
3146033SCOT NK
Solar/Wind Harmer
0.253
316463AE2-346 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
0.132
3145513AHOSKIE
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.125
3145683EARLEYS
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
0.062
316327AA2-057 GEN
Solar/Wind Harmer
0.092
3146206CASHIE
Solar/Wind Harmer
0.06
970601AG2-382 GEN
Solar/Wind Harmer
2.24
315732AD1-074 GEN1
Solar/Wind Harmer
0.338
315733AD1-074 GEN2
Solar/Wind Harmer
0.338
3130546PLYMOUTH
Solar/Wind Harmer
0.059
3143316POE
Solar/Wind Harmer
0.234
970657AG2-426 GEN
Solar/Wind Harmer
0.433
316311AC2-079 GEN
Solar/Wind Harmer
1.692
3130156CHOWAN
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.059
3146486SUNBURY
Solar/Wind Harmer
0.058
3146486SUNBURY
Solar/Wind Harmer
0.058
3145176PASQUOTANK
Solar/Wind Harmer
0.036
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3145573BETHELC
Solar/Wind Harmer
0.058
3151931BEARGRDN S1
50/50
5.414
3151911BEARGRDN G1
50/50
4.191
3144293JTRSVLE
50/50
0.5
3144293JTRSVLE
50/50
0.394
970119AG2-088 GEN
50/50
14.635
3151531CLOVER1
50/50
2.268
3151591KERR 2
50/50
0.203
3151641KERR 7
50/50
0.203
3147043LAWRENC
50/50
0.857
3151051BRUNSWICKS1
50/50
2.06
3151021BRUNSWICKG1
50/50
0.993
971451AH1-221 GEN
50/50
3.014
315243AE2-183_GT3
50/50
1.235
3151281ROARAP4
50/50
0.085
3150851SPRUNCC
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
971377AH1-170 GEN
Solar/Wind Harmer
4.283
3147623JAMES R
Solar/Wind Harmer
0.93
970937AG2-583 GEN
Solar/Wind Harmer
22.933
3146776BUCKING
Solar/Wind Harmer
0.144
3146926FARMVIL
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
4.379
971563AH1-280 GEN
Solar/Wind Harmer
2.104
970685AG2-442 GEN
Solar/Wind Harmer
12.003
315785AD2-033 C
Solar/Wind Harmer
1.25
316034AC1-036 C
Solar/Wind Harmer
0.009
315693AD1-088 GEN
Solar/Wind Harmer
6.214
316131AB2-060 GEN
Solar/Wind Harmer
0.385
3143226MDLTHAN
Solar/Wind Harmer
0.11
957481AF2-042 GEN
Solar/Wind Harmer
28.268
970401AG2-262 GEN
Solar/Wind Harmer
0.589
971065AG2-659 GEN
Solar/Wind Harmer
3.89
3143526WINTERP
Solar/Wind Harmer
0.473
316129AC1-054 GEN
Solar/Wind Harmer
0.334
960081AF2-299 GEN
Solar/Wind Harmer
0.725
941031AE2-094 GEN
Solar/Wind Harmer
13.584
970919AG2-571 GEN
Solar/Wind Harmer
2.582
970087AG2-069 GEN
Solar/Wind Harmer
5.736
3145783HORNRTN
Solar/Wind Harmer
0.07
940641AE2-051 GEN
Solar/Wind Harmer
5.555
315607AA1-063A GEN
Solar/Wind Harmer
0.139
316023GEN1_S
Solar/Wind Harmer
0.149
939411AE1-173 GEN
Solar/Wind Harmer
28.41
3146263WOODLND
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.258
3145893MURPHYS
Solar/Wind Harmer
0.287
3145796HORNRTN
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.064
3146173TUNIS
Solar/Wind Harmer
0.063
3145823KELFORD
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.062
3156021HOLLOMANSOL
Solar/Wind Harmer
0.273
3146233WITAKRS
Solar/Wind Harmer
0.241
3146206CASHIE
Solar/Wind Harmer
0.06
971547AH1-271 GEN
Solar/Wind Harmer
1.28
315737AD1-076 GEN
Solar/Wind Harmer
0.763
315816AE2-034 GEN
Solar/Wind Harmer
0.253
3145663CRESWEL
Solar/Wind Harmer
0.166
971163AH1-040 GEN
Solar/Wind Harmer
4.737
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.047
316381AD1-082 GEN
Solar/Wind Harmer
0.06
316359AB2-059 GEN
Solar/Wind Harmer
0.21
3142053HEARTS
Solar/Wind Harmer
0.104
3130156CHOWAN
Solar/Wind Harmer
0.059
316093AE2-104_GEN
Solar/Wind Harmer
0.99
3145963POPLR C
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.19
3146516WINFALL
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.259
319010AE1-072 C
Solar/Wind Harmer
0.29
3146293MARTNCO
Solar/Wind Harmer
0.054
3146456SLIGO L269
Solar/Wind Harmer
0.058
316494AC1-189 GEN
Solar/Wind Harmer
0.196
944591AF1-124 GEN
Solar/Wind Harmer
13.109
3142543TWELFTH
Solar/Wind Harmer
0.006
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.01
3150981CHESPKA
Adder
0.721
316072AD1-144
Solar/Wind Harmer
0.02
315671AE2-027_GEN
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.073
3145336SMITFLD
Solar/Wind Harmer
0.226
3151921BEARGRDN G2
50/50
4.191
3144293JTRSVLE
50/50
0.5
970413AG2-270 GEN
50/50
9.876
3151031BRUNSWICKG2
50/50
0.993
3151261ROARAP2
50/50
0.088
3150861SPRUNCD
50/50
0.334
3151391GASTONA
50/50
0.173
3151411GASTONB
50/50
0.173
972003AH1-546 GEN
Solar/Wind Harmer
15.285
970221AG2-151 GEN
Solar/Wind Harmer
21.415
3146776BUCKING
Solar/Wind Harmer
0.13
270494AE1-108_GEN
Solar/Wind Harmer
3.742
3146926FARMVIL
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
3.722
942461AE2-259 GEN
Solar/Wind Harmer
0
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.598
970257AG2-171 GEN
Solar/Wind Harmer
5.176
971775AH1-396 GEN
Solar/Wind Harmer
0.259
959311AF2-222 GEN
Solar/Wind Harmer
12.78
964241AG1-285 GEN
Solar/Wind Harmer
8.638
958131AF2-107 GEN
Solar/Wind Harmer
3.491
316478AD1-087 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.054
971683AH1-343 GEN
Solar/Wind Harmer
2.762
944011AF1-069 GEN
Solar/Wind Harmer
4.438
316181AB2-040 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.456
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.065
316011AB1-132 GEN
Solar/Wind Harmer
1.175
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.064
3145796HORNRTN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.064
316212AC1-099_GEN
Solar/Wind Harmer
0.328
3146173TUNIS
Solar/Wind Harmer
0.063
316123AC1-075 GEN
Solar/Wind Harmer
0.084
3145823KELFORD
Solar/Wind Harmer
0.063
315722AD1-056 GEN
Solar/Wind Harmer
2.107
3145273HOLLAND
Solar/Wind Harmer
0.046
316222AC1-221 GEN
Solar/Wind Harmer
0.25
3146233WITAKRS
Solar/Wind Harmer
0.304
3146233WITAKRS
Solar/Wind Harmer
0.041
3138543CONSLDL
Solar/Wind Harmer
0.04
316283AC2-100 C
Solar/Wind Harmer
0.118
3146206CASHIE
Solar/Wind Harmer
0.06
315735AD1-075 GEN1
Solar/Wind Harmer
0.169
3145543BTLEBRO
Solar/Wind Harmer
0.059
3145543BTLEBRO
Solar/Wind Harmer
0.059
315813AE1-149 C
Solar/Wind Harmer
3.146
970657AG2-426 GEN
Solar/Wind Harmer
1.323
971623AH1-311 GEN
Solar/Wind Harmer
0.118
3146376EDENTON
Solar/Wind Harmer
0.059
3145963POPLR C
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
4.163
316321Z2-027
Solar/Wind Harmer
0.01
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
316246AF1-032 C
Solar/Wind Harmer
0.026
3145933PARMELE
Solar/Wind Harmer
0.058
3146456SLIGO L269
Solar/Wind Harmer
0.058
971153AH1-033 GEN
Solar/Wind Harmer
0.672
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
944581AF1-123 GEN
Solar/Wind Harmer
13.062
970909AG2-566 GEN
50/50
2.342
3144293JTRSVLE
50/50
0.5
970535AG2-341 GEN
50/50
1.944
3151581KERR 1
50/50
0.072
3152661PLYWOOD A
50/50
0.2
3145573BETHELC
Solar/Wind Harmer
0.058
3146406KITTY HAWK
Solar/Wind Harmer
0.007
957871AF2-081 GEN
Solar/Wind Harmer
2.894
957861AF2-080 GEN
Solar/Wind Harmer
2.505
316316AC1-027 C
Solar/Wind Harmer
0.055
3145746EVERETS
Solar/Wind Harmer
0.23
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151081ELIZAR1
Adder
5.3
3151091ELIZAR2
Adder
5.208
971445AH1-216 GEN
Solar/Wind Harmer
3.978
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.079
944601AF1-125 GEN
Solar/Wind Harmer
12.861
3145746EVERETS
Solar/Wind Harmer
0.058
3145746EVERETS
Solar/Wind Harmer
0.058
3151101ELIZAR3
Adder
5.368
3144873MCLAUGH
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.023
316499AE2-029_GEN
Solar/Wind Helper
0.506
3148013FISHERV
Solar/Wind Helper
0.076
3148463FAIRFLD
Solar/Wind Helper
0.12
315616AA1-038_C
Solar/Wind Helper
0.544
3132273ORANGE
Solar/Wind Helper
0.028
3148013FISHERV
Solar/Wind Helper
0.132
3147666LOUISA
Solar/Wind Helper
0.279
3151041BRUNSWICKG3
50/50
0.993
972187AH1-678 GEN
50/50
2.277
315242AE2-183_GT2
50/50
1.235
315241AE2-183_GT1
50/50
1.23
972185AH1-677 GEN
50/50
4.459
3151261ROARAP2
50/50
0.086
3146776BUCKING
Solar/Wind Harmer
1.442
3146776BUCKING
Solar/Wind Harmer
0.117
316336AC2-165 C
Solar/Wind Harmer
14.292
316313AB2-026
Solar/Wind Harmer
0.153
970301AG2-198 GEN
Solar/Wind Harmer
9.368
958211AF2-115 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.152
970323AG2-213 GEN
Solar/Wind Harmer
6.901
971223AH1-071 GEN
Solar/Wind Harmer
1.171
970099AG2-077 GEN
Solar/Wind Harmer
11.307
962561AG1-105 GEN
Solar/Wind Harmer
4.967
964791AG1-342 GEN
Solar/Wind Harmer
1.927
3146843MT LREL
Solar/Wind Harmer
0.1
3146843MT LREL
Solar/Wind Harmer
0.1
316118AC1-105 GEN
Solar/Wind Harmer
0.238
3143526WINTERP
Solar/Wind Harmer
0.473
970933AG2-581 GEN
Solar/Wind Harmer
7.1
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.071
3145593CAROLNA
Solar/Wind Harmer
0.089
3145783HORNRTN
Solar/Wind Harmer
1.252
3145783HORNRTN
Solar/Wind Harmer
1.001
3145783HORNRTN
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
0.125
316365GEN2_N
Solar/Wind Harmer
0.149
3144356SAPONY
Solar/Wind Harmer
0.553
316315AB2-025 C
Solar/Wind Harmer
0.053
962571AG1-106 GEN
Solar/Wind Harmer
0.922
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.065
3142666NORTHAMPTON
Solar/Wind Harmer
0.039
3145893MURPHYS
Solar/Wind Harmer
0.431
3145893MURPHYS
Solar/Wind Harmer
0.116
3145796HORNRTN
Solar/Wind Harmer
0.192
3146173TUNIS
Solar/Wind Harmer
0.063
3146173TUNIS
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.022
315742AE1-103 GEN
Solar/Wind Harmer
0.922
315724AD1-057 GEN
Solar/Wind Harmer
1.175
316065AD1-022 GEN
Solar/Wind Harmer
2.754
315614AA2-178 GEN
Solar/Wind Harmer
0.337
316049AB1-081 GEN
Solar/Wind Harmer
0.335
316263AC1-034 GEN
Solar/Wind Harmer
2.24
316349AD2-085 GEN
Solar/Wind Harmer
0.039
3146376EDENTON
Solar/Wind Harmer
0.262
3146376EDENTON
Solar/Wind Harmer
0.262
315835AF2-110_GEN
Solar/Wind Harmer
0.404
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
961601AG1-000A GEN
Solar/Wind Harmer
1.041
3146386ELIZ CT
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.135
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
3130086AYDLETT
Solar/Wind Harmer
0.233
3145933PARMELE
Solar/Wind Harmer
0.116
3145933PARMELE
Solar/Wind Harmer
0.058
3137176SLIGO L2192
Solar/Wind Harmer
0.231
3146456SLIGO L269
Solar/Wind Harmer
1.029
316339AD2-160 GEN
Solar/Wind Harmer
0.093
316388AE2-253 GEN
Solar/Wind Harmer
0.181
3145506HICKORY
Solar/Wind Harmer
0.232
3145506HICKORY
Solar/Wind Harmer
0.139
3145506HICKORY
Solar/Wind Harmer
0.035
316005AA1-067
Solar/Wind Harmer
0.062
3150991CHESPKB
Adder
0.605
3150991CHESPKB
Adder
0.591
942751AE2-291 GEN
Solar/Wind Harmer
3.112
316294AC1-161 GEN
Solar/Wind Harmer
0.982
944641AF1-129 GEN
Adder
26.869
966001AG1-469 GEN
Solar/Wind Helper
0.199
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.844
3147666LOUISA
Solar/Wind Helper
0.484
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.033
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
1.45
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.449
TVALTFEXP_TVA->PJM
CLTF
0.709
CPLELTFEXP_CPLE->PJM
CLTF
3.819
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.496
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.173
MECLTFEXP_MEC->PJM
CLTF
0.182
SIGELTFEXP_SIGE->PJM
CLTF
0.003
NYPJM->LTFIMP_NY
CLTF
0.464

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:676.22
MW Contribution:
20.23
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.77 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:898.46
MW Contribution:
20.31
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.184
3151911BEARGRDN G1
50/50
5.56
3144293JTRSVLE
50/50
0.584
3144293JTRSVLE
50/50
0.461
3151531CLOVER1
50/50
2.075
3151591KERR 2
50/50
0.188
3151641KERR 7
50/50
0.188
3147043LAWRENC
50/50
0.708
970937AG2-583 GEN
Solar/Wind Harmer
36.756
971377AH1-170 GEN
Solar/Wind Harmer
5.682
3147623JAMES R
Solar/Wind Harmer
1.234
3146776BUCKING
Solar/Wind Harmer
0.187
3146926FARMVIL
Solar/Wind Harmer
0.215
971563AH1-280 GEN
Solar/Wind Harmer
2.459
970685AG2-442 GEN
Solar/Wind Harmer
13.128
315785AD2-033 C
Solar/Wind Harmer
1.371
316034AC1-036 C
Solar/Wind Harmer
0.01
315693AD1-088 GEN
Solar/Wind Harmer
6.208
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970401AG2-262 GEN
Solar/Wind Harmer
0.57
957481AF2-042 GEN
Solar/Wind Harmer
25.123
971065AG2-659 GEN
Solar/Wind Harmer
3.402
316129AC1-054 GEN
Solar/Wind Harmer
0.289
962751AG1-124 GEN
Solar/Wind Harmer
2.837
972205AH1-687 GEN
50/50
27.167
3151541CLOVER2
50/50
2.06
3151601KERR 3
50/50
0.188
3151611KERR 4
50/50
0.188
3151621KERR 5
50/50
0.188
3151631KERR 6
50/50
0.188
971845AH1-439 GEN
Solar/Wind Harmer
20.749
946301AF1-294 GEN
Solar/Wind Harmer
4.549
961791AG1-021 GEN
Solar/Wind Harmer
2.213
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
9.617
970681AG2-440 GEN
Solar/Wind Harmer
6.383
316486AD2-202 GEN
Solar/Wind Harmer
0.098
3147173SINAI
Solar/Wind Harmer
0.08
3147243WELCO
Solar/Wind Harmer
0.05
970831AG2-522 GEN
Solar/Wind Harmer
3.162
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151921BEARGRDN G2
50/50
5.56
3144293JTRSVLE
50/50
0.584
970413AG2-270 GEN
50/50
9.039
972003AH1-546 GEN
Solar/Wind Harmer
20.231
970221AG2-151 GEN
Solar/Wind Harmer
28.409
3146776BUCKING
Solar/Wind Harmer
0.168
270494AE1-108_GEN
Solar/Wind Harmer
4.971
3146926FARMVIL
Solar/Wind Harmer
0.215
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.689
970257AG2-171 GEN
Solar/Wind Harmer
5.754
971775AH1-396 GEN
Solar/Wind Harmer
0.288
958131AF2-107 GEN
Solar/Wind Harmer
4.68
959311AF2-222 GEN
Solar/Wind Harmer
13.458
964241AG1-285 GEN
Solar/Wind Harmer
8.766
316478AD1-087 GEN
Solar/Wind Harmer
0.335
3147043LAWRENC
Solar/Wind Harmer
0.044
971683AH1-343 GEN
Solar/Wind Harmer
2.624
316123AC1-075 GEN
Solar/Wind Harmer
0.082
970909AG2-566 GEN
50/50
2.783
3144293JTRSVLE
50/50
0.584
970535AG2-341 GEN
50/50
1.879
3151581KERR 1
50/50
0.067
3152661PLYWOOD A
50/50
0.188
316336AC2-165 C
Solar/Wind Harmer
30.363
3146776BUCKING
Solar/Wind Harmer
1.867
3146776BUCKING
Solar/Wind Harmer
0.151
970301AG2-198 GEN
Solar/Wind Harmer
11.132
958211AF2-115 GEN
Solar/Wind Harmer
2.766
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
970323AG2-213 GEN
Solar/Wind Harmer
7.672
962561AG1-105 GEN
Solar/Wind Harmer
4.838
964791AG1-342 GEN
Solar/Wind Harmer
1.864
3146843MT LREL
Solar/Wind Harmer
0.097
3146843MT LREL
Solar/Wind Harmer
0.097
970099AG2-077 GEN
Solar/Wind Harmer
10.049
316118AC1-105 GEN
Solar/Wind Harmer
0.226
970933AG2-581 GEN
Solar/Wind Harmer
5.128
942751AE2-291 GEN
Solar/Wind Harmer
3.108
966001AG1-469 GEN
Solar/Wind Helper
0.155
LAGNLTFEXP_LAGN->PJM
CLTF
1.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.485
TVALTFEXP_TVA->PJM
CLTF
0.56
CPLELTFEXP_CPLE->PJM
CLTF
2.765
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.492
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.743
MECLTFEXP_MEC->PJM
CLTF
0.187
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.403
LGEELTFEXP_LGEE->PJM
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.18 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3662.4
MW Contribution:
6.5
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.58 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3365.01
MW Contribution:
6.37
Bus #Bus NameTypeMW Contribution
3140676OCCOQUN
50/50
0.027
970053AG2-049 GEN
50/50
3.301
3141316ARNOLDS
50/50
0.025
3150411LDYSMT5
50/50
24.76
3150381LDYSMT2
50/50
23.697
972213AH1-691 GEN
50/50
4.009
972215AH1-692 GEN
50/50
4.009
3141426STAFORD
Solar/Wind Harmer
-0.005
944491AF1-114 GEN
Solar/Wind Harmer
5.789
316468AD1-105 GEN
Solar/Wind Harmer
2.189
3141813NORNECK
Solar/Wind Harmer
-0.019
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.018
957601AF2-054 GEN
Solar/Wind Harmer
0.542
3141873WAN 176
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.409
3143873LANEXA
Solar/Wind Harmer
-0.011
3142433PROV 92
Adder
0.312
3142433PROV 92
Adder
0.312
957831AF2-077 GEN
Solar/Wind Harmer
0.537
3138283WHITEMARSH
Solar/Wind Harmer
0.028
971285AH1-108 GEN
Adder
1.194
316382AG1-145 C
Solar/Wind Harmer
0.534
316159AE1-175 C
Solar/Wind Harmer
0.475
316233AE1-074 FULL
Solar/Wind Harmer
0.476
971281AH1-106 GEN
Solar/Wind Harmer
2.874
971283AH1-107 GEN
Solar/Wind Harmer
2.874
316164AC1-076 GEN
Solar/Wind Harmer
1.478
315839AE2-212 C
Solar/Wind Harmer
0.528
315697AD1-025 GEN
Solar/Wind Harmer
3.535
3143316POE
Solar/Wind Harmer
-0.069
3151201GRAVEL4
Adder
11.305
3151221GRAVEL6
Adder
11.292
3151191GRAVEL3
Adder
11.161
3151211GRAVEL5
Adder
11.161
971445AH1-216 GEN
Solar/Wind Harmer
10.762
316236AE1-162_GEN
Solar/Wind Harmer
0.523
970657AG2-426 GEN
Solar/Wind Harmer
1.092
3151081ELIZAR1
Adder
14.098
3151091ELIZAR2
Adder
13.853
316316AC1-027 C
Solar/Wind Harmer
0.529
315651AD1-115 GEN
Solar/Wind Harmer
7.57
315833AF1-017_GEN
Solar/Wind Harmer
3.27
316311AC2-079 GEN
Solar/Wind Harmer
8.685
316018AA1-139 ULT2
Solar/Wind Harmer
1.47
957871AF2-081 GEN
Solar/Wind Harmer
8.605
3146406KITTY HAWK
Solar/Wind Harmer
0.014
313526AB2-022
Solar/Wind Harmer
0.46
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146396TANGLEW
Solar/Wind Harmer
0.314
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
316258AE1-075 C
Solar/Wind Harmer
0.41
316405AF2-144 C
Solar/Wind Harmer
0.433
315814AE2-033 C
Solar/Wind Harmer
15.759
315800Z1-036_GEN1
Solar/Wind Harmer
4.164
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970533AG2-339 GEN
Solar/Wind Harmer
11.279
3147346CASHSCORNER
Solar/Wind Harmer
0.259
970673AG2-436 GEN
Solar/Wind Harmer
36.553
971967AH1-528 GEN
Solar/Wind Harmer
31.193
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315732AD1-074 GEN1
Solar/Wind Harmer
3.333
315733AD1-074 GEN2
Solar/Wind Harmer
3.333
3146206CASHIE
Solar/Wind Harmer
-0.016
970601AG2-382 GEN
Solar/Wind Harmer
7.198
316318V4-068
Solar/Wind Harmer
0.41
3145893MURPHYS
Solar/Wind Harmer
-0.044
3145893MURPHYS
Solar/Wind Harmer
-0.016
316463AE2-346 GEN
Solar/Wind Harmer
0.264
3145513AHOSKIE
Solar/Wind Harmer
0.142
961941AG1-037 GEN
Solar/Wind Harmer
0.123
3145513AHOSKIE
Solar/Wind Harmer
-0.016
946281AF1-292 GEN
Solar/Wind Harmer
0.366
3146043SEABORD
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
970085AG2-068 GEN
Solar/Wind Harmer
10.152
970581AG2-369 GEN
Solar/Wind Harmer
8.731
3137643SOCKMAN
Solar/Wind Harmer
-0.064
316426AA2-053 GEN
Solar/Wind Harmer
1.631
315652AC1-086 GEN
Solar/Wind Harmer
18.207
972223AH1-696 GEN
50/50
17.555
3150151POSSMC1
50/50
2.222
3141346CRANES
50/50
0.243
3150011OMF A
50/50
0.364
972197AH1-683 GEN
50/50
3.854
972219AH1-694 GEN
50/50
2.775
3150351NORNECKC2
50/50
1.756
957971AF2-091 GEN
Solar/Wind Harmer
1.968
972135AH1-637 GEN
Solar/Wind Harmer
1.956
966881AG1-559 GEN
Solar/Wind Harmer
0.196
316337AD2-073 GEN
Solar/Wind Harmer
0.507
964211AG1-282 GEN
Solar/Wind Harmer
0.559
3141726DUNNSVL
Solar/Wind Harmer
-0.074
316404AE1-155 C
Solar/Wind Harmer
3.542
958261AF2-120 GEN
Solar/Wind Harmer
7.191
962861AG1-135 GEN
Solar/Wind Harmer
6.949
3138133OCRAN
Solar/Wind Harmer
-0.011
3142416OLDCHRC
Solar/Wind Harmer
-0.047
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3141766HARMONY
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
2.178
316280AD1-041 GEN
Solar/Wind Harmer
1.361
316314AB2-024 C
Solar/Wind Harmer
1.548
971777AH1-397 GEN
Solar/Wind Harmer
2.113
3142433PROV 92
Solar/Wind Harmer
-0.072
3142433PROV 92
Adder
0.312
3142433PROV 92
Adder
0.312
315975AC1-164 GENB
Solar/Wind Harmer
0.121
3143096IRON208
Adder
0.667
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
75.705
316447AC1-158 HLD
Solar/Wind Harmer
3.833
316044AC1-158 PL1
Solar/Wind Harmer
1.743
3150851SPRUNCC
Adder
0.73
971317AH1-138 GEN
Solar/Wind Harmer
2.215
3143526WINTERP
Solar/Wind Harmer
-0.092
315671AE2-027_GEN
Solar/Wind Harmer
3.182
3138126ROCKLANDING
Solar/Wind Harmer
0.054
316132AB2-190 GEN1
Solar/Wind Harmer
1.772
3147666LOUISA
Solar/Wind Harmer
-0.07
316174AB2-169 GEN
Solar/Wind Harmer
2.485
970683AG2-441 GEN
Solar/Wind Harmer
11.36
970681AG2-440 GEN
Solar/Wind Harmer
7.54
3145796HORNRTN
Solar/Wind Harmer
-0.051
3145796HORNRTN
Solar/Wind Harmer
-0.006
3146033SCOT NK
Solar/Wind Harmer
-0.064
971845AH1-439 GEN
Solar/Wind Harmer
8.52
316322AB2-045
Solar/Wind Harmer
0.538
972205AH1-687 GEN
Adder
6.087
316486AD2-202 GEN
Solar/Wind Harmer
0.405
946301AF1-294 GEN
Solar/Wind Harmer
4.098
961791AG1-021 GEN
Solar/Wind Harmer
1.999
3144303KENBRDG
Solar/Wind Harmer
-0.013
3151881LOWMORC
Adder
1.346
3151881LOWMORC
Adder
1.325
3151861LOWMORA
Adder
1.304
226929AD2-058 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.826
233940AF2-379 C
Solar/Wind Helper
0.102
233901CHERRYDALE C
Solar/Wind Helper
0.382
232432Z2-076 GEN
Solar/Wind Helper
0.11
230434AG1-499 GEN
Solar/Wind Helper
0.366
228728W1-130C
Solar/Wind Helper
0.086
230407AD2-065 C
Solar/Wind Helper
0.064
227927V4-067C
Solar/Wind Helper
0.016
219258KINSLEYDEP C
Solar/Wind Helper
0.122
219615MILLCREEK C
Solar/Wind Helper
0.042
20720728JCB_W1-129
Solar/Wind Helper
0.089
20715028HAN_X4-015
Solar/Wind Helper
0.089
207445AB1-138_GEN
Solar/Wind Helper
0.162
219620RIDERU C
Solar/Wind Helper
0.002
20720628TIN_W1-124
Solar/Wind Helper
0.292
218526CNTRALGAS2 C
Solar/Wind Helper
0.245
20675528CPH_W2-050
Solar/Wind Helper
0.173
20673828FLE_V3-070
Solar/Wind Helper
0.131
20676128MHD_W3-029
Solar/Wind Helper
0.145
20676428JCR_X2-075
Solar/Wind Helper
0.103
3150101POSSM6S
50/50
2.517
3150081POSSM6A
50/50
1.651
3150151POSSMC1
50/50
2.222
3150151POSSMC1
50/50
2.222
3150021OMF B
50/50
0.364
3150331BIRCHWDA
50/50
33.562
3150401LDYSMT4
50/50
24.683
3150371LDYSMT1
50/50
23.851
3150501FRIVERG
50/50
1.395
3150351NORNECKC2
50/50
1.785
316223AC1-118
Solar/Wind Harmer
0.516
3141906WESTMOR
Solar/Wind Harmer
-0.008
971781AH1-399 GEN
Solar/Wind Harmer
1.18
966881AG1-559 GEN
Solar/Wind Harmer
0.573
316077AC2-138 C
Solar/Wind Harmer
0.392
316484AD2-074 GEN
Solar/Wind Harmer
4.646
961951AG1-038 GEN
Solar/Wind Harmer
2.431
316473AC1-191 GEN
Solar/Wind Harmer
1.982
3142416OLDCHRC
Solar/Wind Harmer
1.832
3141873WAN 176
Solar/Wind Harmer
2.151
3141766HARMONY
Solar/Wind Harmer
1.613
316203AE2-005 GEN
Solar/Wind Harmer
7.635
3141843SHACKLE
Adder
0.823
316075AC2-137 C
Solar/Wind Harmer
0.485
970293AG2-193 GEN
Solar/Wind Harmer
2.255
3142433PROV 92
Adder
0.312
3142433PROV 92
Adder
0.312
3142946ENON
Solar/Wind Harmer
-0.006
3143096IRON208
Adder
0.667
3143096IRON208
Adder
0.654
3150861SPRUNCD
Adder
0.73
3150921YORKTN3
Adder
3.941
970133AG2-095 GEN
Solar/Wind Harmer
1.982
3144216WINCHST
Adder
0.59
316458AB2-190 GEN2
Solar/Wind Harmer
1.772
3147666LOUISA
Solar/Wind Harmer
-0.04
315778AD1-151 GEN
Solar/Wind Harmer
15.614
961611AG1-000B GEN
Solar/Wind Harmer
3.68
3151171GRAVELC
Adder
2.172
315813AE1-149 C
Solar/Wind Harmer
10.876
3145336SMITFLD
Solar/Wind Harmer
-0.007
970657AG2-426 GEN
Solar/Wind Harmer
3.498
3144536CHRHLND
Solar/Wind Harmer
-0.003
3151101ELIZAR3
Adder
14.278
3144873MCLAUGH
Solar/Wind Harmer
0
3142956BIRDNECK
Solar/Wind Harmer
0.926
944581AF1-123 GEN
Solar/Wind Harmer
78.482
944601AF1-125 GEN
Solar/Wind Harmer
77.257
316017AA1-139 ULT1
Solar/Wind Harmer
1.389
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
1.99
316305AF2-043 C
Solar/Wind Harmer
0.517
316246AF1-032 C
Solar/Wind Harmer
0.347
3132273ORANGE
Solar/Wind Harmer
-0.003
316320Y1-086
Solar/Wind Harmer
1.002
316321Z2-027
Solar/Wind Harmer
0.46
3141196NOKESVL
Solar/Wind Harmer
-0.068
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3145273HOLLAND
Solar/Wind Harmer
-0.013
3150301M RUN C
Adder
20.424
3150291M RUN B
Adder
20.272
3150241REMNGT4
Adder
19.157
972199AH1-684 GEN
Adder
2.905
972217AH1-693 GEN
Adder
2.526
3143336POWHATN
Solar/Wind Harmer
1.708
3151761LOISA E
Adder
19.927
3151721LOISA A
Adder
9.724
3146376EDENTON
Solar/Wind Harmer
-0.017
944011AF1-069 GEN
Solar/Wind Harmer
9.854
3156081AA2-088 GEN
Solar/Wind Harmer
5.364
315735AD1-075 GEN1
Solar/Wind Harmer
1.667
3146206CASHIE
Solar/Wind Harmer
-0.016
3145893MURPHYS
Solar/Wind Harmer
0.115
3145893MURPHYS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
966621AG1-532 GEN
Solar/Wind Harmer
0.331
970917AG2-570 GEN
Solar/Wind Harmer
40.801
3146263WOODLND
Solar/Wind Harmer
-0.016
316181AB2-040 GEN
Solar/Wind Harmer
2.263
3147043LAWRENC
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3145963POPLR C
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.198
3143226MDLTHAN
Solar/Wind Harmer
-0.017
971069AG2-661 GEN
Solar/Wind Harmer
2.776
316369SG1_INVT
Solar/Wind Harmer
3.125
316192AB2-158 GEN
Solar/Wind Harmer
2.077
961611AG1-000B GEN
Solar/Wind Harmer
8.626
3151171GRAVELC
Adder
1.652
3145336SMITFLD
Solar/Wind Harmer
-0.069
315773AC2-141 GEN
Solar/Wind Harmer
7.245
316381AD1-082 GEN
Solar/Wind Harmer
1.585
316254AC1-120 GEN1
Solar/Wind Harmer
6.487
316170AC1-121 GEN2
Solar/Wind Harmer
2.162
316375AC2-012 GEN
Solar/Wind Harmer
5.976
316036AC1-147 C
Solar/Wind Harmer
0.465
3150981CHESPKA
Adder
1.92
316072AD1-144
Solar/Wind Harmer
0.348
944591AF1-124 GEN
Solar/Wind Harmer
78.765
3146456SLIGO L269
Solar/Wind Harmer
-0.017
319010AE1-072 C
Solar/Wind Harmer
3.467
316093AE2-104_GEN
Solar/Wind Harmer
4.987
939411AE1-173 GEN
Solar/Wind Harmer
85.489
940641AE2-051 GEN
Solar/Wind Harmer
15.983
3146516WINFALL
Solar/Wind Harmer
-0.055
3146516WINFALL
Solar/Wind Harmer
-0.017
971685AH1-345 GEN
Solar/Wind Harmer
1.487
3150281M RUN A
Adder
20.436
3150221REMNGT2
Adder
19.031
3150211REMNGT1
Adder
18.905
972201AH1-685 GEN
Adder
3.283
3143336POWHATN
Solar/Wind Harmer
2.009
3151751LOISA D
Adder
9.775
315683AE1-153 C
Solar/Wind Harmer
15.743
315611Z1-036_GEN2
Solar/Wind Harmer
4.164
3130156CHOWAN
Solar/Wind Harmer
-0.017
941031AE2-094 GEN
Solar/Wind Harmer
31.448
315816AE2-034 GEN
Solar/Wind Harmer
1.345
3145663CRESWEL
Solar/Wind Harmer
-0.046
971163AH1-040 GEN
Solar/Wind Harmer
15.624
315737AD1-076 GEN
Solar/Wind Harmer
3.134
3146206CASHIE
Solar/Wind Harmer
-0.016
971547AH1-271 GEN
Solar/Wind Harmer
4.113
316023GEN1_S
Solar/Wind Harmer
1.106
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
0.488
3146173TUNIS
Solar/Wind Harmer
-0.016
970937AG2-583 GEN
Solar/Wind Harmer
11.757
3156021HOLLOMANSOL
Solar/Wind Harmer
2.197
960081AF2-299 GEN
Solar/Wind Harmer
1.837
970919AG2-571 GEN
Solar/Wind Harmer
5.165
3145683EARLEYS
Solar/Wind Harmer
-0.016
315607AA1-063A GEN
Solar/Wind Harmer
1.642
316087AB2-174 GEN
Solar/Wind Harmer
2.317
3146263WOODLND
Solar/Wind Harmer
-0.016
970087AG2-069 GEN
Solar/Wind Harmer
15.228
3147043LAWRENC
Adder
1.305
3145963POPLR C
Solar/Wind Harmer
-0.016
957481AF2-042 GEN
Solar/Wind Harmer
50.592
3145823KELFORD
Solar/Wind Harmer
-0.016
315693AD1-088 GEN
Solar/Wind Harmer
8.067
3145783HORNRTN
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.016
970685AG2-442 GEN
Solar/Wind Harmer
14.071
316034AC1-036 C
Solar/Wind Harmer
0.297
3146926FARMVIL
Solar/Wind Harmer
-0.01
3146776BUCKING
Solar/Wind Harmer
-0.006
972277AH1-723 GEN
Adder
85.125
971563AH1-280 GEN
Solar/Wind Harmer
1.999
3150091POSSM6B
50/50
1.651
3150071POSSM 5
50/50
101.578
3150181POSSMC2
50/50
2.241
3150181POSSMC2
50/50
2.222
3150181POSSMC2
50/50
2.222
957191AF2-013 GEN
50/50
16.161
3150391LDYSMT3
50/50
24.637
972195AH1-682 GEN
50/50
3.238
3150341NORNECKC1
50/50
1.844
3150341NORNECKC1
50/50
1.829
315673AE1-157 GEN
Solar/Wind Harmer
14.418
972189AH1-679 GEN
Adder
2.773
316487AF1-042 GEN
Solar/Wind Harmer
2.431
966871AG1-558 GEN
Solar/Wind Harmer
0.554
966871AG1-558 GEN
Solar/Wind Harmer
0.189
3142296MT RD221
Adder
0.517
316312AB1-027
Solar/Wind Harmer
0.611
316156AD2-030 GEN
Solar/Wind Harmer
0.483
315666AE1-190 GEN
Solar/Wind Harmer
0.545
316441AF1-014 GEN
Solar/Wind Harmer
1.221
3150691DARBY 3
Adder
11.553
3150701DARBY 4
Adder
11.526
3150681DARBY 2
Adder
11.513
3150671DARBY 1
Adder
11.499
3142366NRTHEST
Adder
0.525
315976AC1-164 GENA
Solar/Wind Harmer
4.091
316169AC1-164_GENC
Solar/Wind Harmer
3.536
3142946ENON
Solar/Wind Harmer
-0.002
316045AC1-158 PL2
Solar/Wind Harmer
5.578
316450AC1-158 RIC
Solar/Wind Harmer
0.465
3143526WINTERP
Solar/Wind Harmer
-0.092
944641AF1-129 GEN
Adder
75.002
316240AF1-291 C
Solar/Wind Harmer
0.531
971223AH1-071 GEN
Solar/Wind Harmer
2.193
316033AB2-134 GEN
Solar/Wind Harmer
5.643
316294AC1-161 GEN
Solar/Wind Harmer
5.601
316083AB2-161 GEN
Solar/Wind Harmer
2.811
3150991CHESPKB
Adder
1.611
3150991CHESPKB
Adder
1.572
316185AD1-033 GEN
Solar/Wind Harmer
1.816
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316349AD2-085 GEN
Solar/Wind Harmer
1.529
316339AD2-160 GEN
Solar/Wind Harmer
1.158
316388AE2-253 GEN
Solar/Wind Harmer
1.158
3137176SLIGO L2192
Solar/Wind Harmer
-0.068
3146456SLIGO L269
Solar/Wind Harmer
2.03
3130086AYDLETT
Solar/Wind Harmer
-0.068
315835AF2-110_GEN
Solar/Wind Harmer
2.144
3146386ELIZ CT
Solar/Wind Harmer
-0.017
316431W1029_GEN1
Solar/Wind Harmer
3.086
316433W1029_GEN2
Solar/Wind Harmer
3.086
316435W1029_GEN3
Solar/Wind Harmer
3.086
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
316006AB2-029 C
Solar/Wind Harmer
0.975
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3144356SAPONY
Solar/Wind Harmer
0.591
316315AB2-025 C
Solar/Wind Harmer
0.456
966001AG1-469 GEN
Solar/Wind Harmer
0.32
316313AB2-026
Solar/Wind Harmer
0.455
3151731LOISA B
Adder
9.775
315742AE1-103 GEN
Solar/Wind Harmer
4.005
3146376EDENTON
Solar/Wind Harmer
0.499
3146376EDENTON
Solar/Wind Harmer
0.499
316336AC2-165 C
Solar/Wind Harmer
10.471
315614AA2-178 GEN
Solar/Wind Harmer
1.793
972185AH1-677 GEN
Adder
8.299
972187AH1-678 GEN
Adder
4.194
970933AG2-581 GEN
Solar/Wind Harmer
15.467
316065AD1-022 GEN
Solar/Wind Harmer
8.239
316365GEN2_N
Solar/Wind Harmer
1.106
3145893MURPHYS
Solar/Wind Harmer
0.459
3145893MURPHYS
Solar/Wind Harmer
-0.03
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316140AB2-099
Solar/Wind Harmer
0.11
313506AB2-031 GEN
Solar/Wind Harmer
1.302
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
20.237
962571AG1-106 GEN
Solar/Wind Harmer
2.326
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
0.134
3145783HORNRTN
Solar/Wind Harmer
1.913
3145783HORNRTN
Solar/Wind Harmer
1.53
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
970301AG2-198 GEN
Solar/Wind Harmer
8.045
3145796HORNRTN
Solar/Wind Harmer
-0.048
3147133PAMPLIN
Solar/Wind Harmer
-0.016
3147133PAMPLIN
Solar/Wind Harmer
-0.013
3146776BUCKING
Solar/Wind Harmer
-0.064
3146776BUCKING
Solar/Wind Harmer
-0.005
972193AH1-681 GEN
Adder
3.264
958211AF2-115 GEN
Solar/Wind Harmer
2.499
3144293JTRSVLE
Adder
0.34
970323AG2-213 GEN
Solar/Wind Harmer
7.979
223401AF1-299 GEN
Solar/Wind Helper
0.732
223402AF1-300 C
Solar/Wind Helper
0.732
232424Y1-079 C
Solar/Wind Helper
0.191
233946AB2-136 GEN
Solar/Wind Helper
0.936
234036AF2-325 C
Solar/Wind Helper
0.07
232436AB1-176 C
Solar/Wind Helper
0.073
233930AB2-032 GEN
Solar/Wind Helper
0.626
233982AB2-133 GEN
Solar/Wind Helper
0.59
233994AC2-023 GEN
Solar/Wind Helper
1.581
232428Y3-058 C
Solar/Wind Helper
0.556
232410W1-006 C
Solar/Wind Helper
0.834
234015AF2-250 C
Solar/Wind Helper
0.062
233952AC2-187 GEN
Solar/Wind Helper
0.382
233954AC2-188 GEN
Solar/Wind Helper
0.382
230511AF1-262
Solar/Wind Helper
0.023
230433AD2-135 GEN
Solar/Wind Helper
0.027
228754AB1-001 C
Solar/Wind Helper
0.041
219904AC1-010 C
Solar/Wind Helper
0.096
219912AD2-042 GEN
Solar/Wind Helper
0.237
219272CLEANLIGHT C
Solar/Wind Helper
0.04
219906AC1-017 C
Solar/Wind Helper
0.066
219607WPEMNERT C
Solar/Wind Helper
0.126
219304NAMERICA C
Solar/Wind Helper
0.206
214067T20SOLAR
Solar/Wind Helper
0.018
20720828JCB_W4-025
Solar/Wind Helper
0.099
207459AE1-142 C O1
Solar/Wind Helper
0.451
20714828MDF_W3-079
Solar/Wind Helper
0.202
20742028HF_AC1-207
Solar/Wind Helper
0.217
218438BLK ROCK C
Solar/Wind Helper
0.042
20675428EAM_W2-061
Solar/Wind Helper
0.024
217081WEATEXAS C
Solar/Wind Helper
0.019
217202FBANKSOLAR C
Solar/Wind Helper
0.005
217201HACKENSOLA C
Solar/Wind Helper
0.005
217206BARNGR HS C
Solar/Wind Helper
0.01
217204WCALDSOLAR C
Solar/Wind Helper
0.005
20674328GAR_V4-001
Solar/Wind Helper
0.034
207471AF2-354 C
Solar/Wind Helper
0.25
20674828DL_W4-046
Solar/Wind Helper
0.012
20675928HOL_W4-097
Solar/Wind Helper
0.074
961431AF2-434 GEN
Solar/Wind Helper
0.6
946751AF1-339 GEN
Solar/Wind Helper
0.59
964851AG1-348 GEN
Solar/Wind Helper
0.093
207408W3-077 C
Solar/Wind Helper
0.124
20675128HRM_W1-127
Solar/Wind Helper
0.044
961261AF2-417 GEN
Solar/Wind Helper
0.617
205956AE1-196_GEN
Solar/Wind Helper
0.664
209027LOR2_Q27
Solar/Wind Helper
1.417
212266LOR1
Solar/Wind Helper
0.413
205943AE1-185 GEN
Solar/Wind Helper
0.657
209029WAYMART-WD
Solar/Wind Helper
1.131
209054AE2-059 GEN
Solar/Wind Helper
0.108
959431AF2-234 GEN
Solar/Wind Helper
1.178
964051AG1-259 GEN
Solar/Wind Helper
0.088
964061AG1-260 GEN
Solar/Wind Helper
0.088
959421AF2-233 GEN
Solar/Wind Helper
0.589
209067AE2-060 GEN
Solar/Wind Helper
0.097
205917AD1-020 ES
Solar/Wind Helper
0.355
970831AG2-522 GEN
Solar/Wind Harmer
6.103
3144293JTRSVLE
Adder
0.34
3144293JTRSVLE
Adder
0.268
315785AD2-033 C
Solar/Wind Harmer
3.609
208835TUHI V3-051
Solar/Wind Helper
0.035
233918AB1-142 GEN
Solar/Wind Helper
0.826
232426Y1-080 FULL
Solar/Wind Helper
0.064
233996TM1833_GEN
Solar/Wind Helper
0.337
233998TM1NIN_3.36
Solar/Wind Helper
0.337
232404W1-003 C
Solar/Wind Helper
0.834
232408W1-005 C
Solar/Wind Helper
0.834
233944AB2-135 GEN
Solar/Wind Helper
0.97
228729W2-030 C
Solar/Wind Helper
0.176
219766PARADISE C
Solar/Wind Helper
0.086
219686LUMSOLAR_N C
Solar/Wind Helper
0.063
219907AC1-030 C
Solar/Wind Helper
0.053
219348LDSOLAR C
Solar/Wind Helper
0.18
20716028EGP_W2-019
Solar/Wind Helper
0.029
20715828PEM_W1-120
Solar/Wind Helper
0.149
219276PARKLANDSO C
Solar/Wind Helper
0.138
963711AG1-223 GEN
Solar/Wind Helper
0.099
20714528FRN_Y2-051
Solar/Wind Helper
0.088
219680HOPEWELLV C1
Solar/Wind Helper
0.005
20715228NPK_W1-113
Solar/Wind Helper
0.12
20720528MAN_W1-024
Solar/Wind Helper
0.044
218524CNTRALGAS1 C
Solar/Wind Helper
0.245
218440SUMMTASSOC C
Solar/Wind Helper
0.025
218428ETC SOLAR C
Solar/Wind Helper
0.007
219908AB1-139 C
Solar/Wind Helper
0.112
219919AE1-041 FULL
Solar/Wind Helper
0.006
20673628F1S_V4-069
Solar/Wind Helper
0.045
20671828STAW2-080
Solar/Wind Helper
0.04
217209CENTRL HS C
Solar/Wind Helper
0.013
217208PARK ELE C
Solar/Wind Helper
0.007
20676728BRNX1-095
Solar/Wind Helper
0.045
207439AE1-081 C O1
Solar/Wind Helper
0.028
207530AG1-191 GEN
Solar/Wind Helper
0.099
20676328BVR_Y1-020
Solar/Wind Helper
0.04
20674628WNG_W3-110
Solar/Wind Helper
0.133
20676228FRD_X1-012
Solar/Wind Helper
0.136
20674928WA_W3-044
Solar/Wind Helper
0.146
20675828AU_W4-064
Solar/Wind Helper
0.044
207484AF2-139 C O1
Solar/Wind Helper
0.124
20675728RH_W2-091
Solar/Wind Helper
0.121
207518AF1-320_GEN
Solar/Wind Helper
2.321
211065PSPA IPP
Solar/Wind Helper
0.219
961301AF2-421 GEN
Solar/Wind Helper
0.617
963151AG1-164 GEN
Solar/Wind Helper
0.617
205932AD2-116_GEN
Solar/Wind Helper
0.664
961341AF2-425 GEN
Solar/Wind Helper
0.601
212507AE2-042_GEN
Solar/Wind Helper
2.099
946731AF1-337 GEN
Solar/Wind Helper
0.59
209137AF2-361 C
Solar/Wind Helper
1.618
205916AD1-020 GEN
Solar/Wind Helper
1.651
316011AB1-132 GEN
Solar/Wind Harmer
3.38
316317KELFORD C
Solar/Wind Harmer
0.749
3145823KELFORD
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.064
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147133PAMPLIN
Solar/Wind Harmer
-0.05
959311AF2-222 GEN
Solar/Wind Harmer
16.774
3146926FARMVIL
Solar/Wind Harmer
-0.01
942461AE2-259 GEN
Solar/Wind Harmer
2.414
964241AG1-285 GEN
Solar/Wind Harmer
12.529
3146776BUCKING
Solar/Wind Harmer
-0.006
972255AH1-712 GEN
Adder
73.05
972003AH1-546 GEN
Solar/Wind Harmer
6.505
316478AD1-087 GEN
Solar/Wind Harmer
1.382
3144293JTRSVLE
Adder
0.34
970257AG2-171 GEN
Solar/Wind Harmer
5.984
971775AH1-396 GEN
Solar/Wind Harmer
1.126
3151861LOWMORA
Adder
1.357
227287AC2-120 GEN
Solar/Wind Helper
1.239
226910AB2-157 C
Solar/Wind Helper
0.048
208835TUHI V3-051
Solar/Wind Helper
0.035
233987AB2-037 GEN
Solar/Wind Helper
3.859
232417X3-008 C
Solar/Wind Helper
0.383
232422X3-066 FULL
Solar/Wind Helper
0.188
233964AF2-378 GEN
Solar/Wind Helper
0.069
233933AB2-153 GEN
Solar/Wind Helper
0.383
233923SMA
Solar/Wind Helper
1.237
233997TMININ_4.2
Solar/Wind Helper
0.337
232406W1-004 FULL
Solar/Wind Helper
0.834
233935AB2-179 C
Solar/Wind Helper
2.086
232434Z2-077 GEN
Solar/Wind Helper
0.209
233950AC2-186 GEN
Solar/Wind Helper
0.191
230415AB2-049 C
Solar/Wind Helper
0.048
219623KINSLEYBEA C
Solar/Wind Helper
0.003
219921AF1-264
Solar/Wind Helper
0.081
219914AD2-027 C
Solar/Wind Helper
0.182
219291REEVESSOUT C
Solar/Wind Helper
0.018
218660EHAMPSOLAR C
Solar/Wind Helper
0.052
219688LUMSOLAR_S C
Solar/Wind Helper
0.063
219236SOUTHERNHQ C
Solar/Wind Helper
0.008
959561AF2-247 GEN
Solar/Wind Helper
0.032
20715728PEM_W1-119
Solar/Wind Helper
0.149
20714928UPF_X1-085
Solar/Wind Helper
0.008
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.478
219612MATRIX C
Solar/Wind Helper
0.037
20716928W4-060COL
Solar/Wind Helper
0.079
217213AMBOY SO C
Solar/Wind Helper
0.044
219249CENTRALDIV C
Solar/Wind Helper
0.015
207442AE1-156 GEN
Solar/Wind Helper
0.494
20673728F2S_V4-070
Solar/Wind Helper
0.045
217211CAMDEN ST C
Solar/Wind Helper
0.007
217169METRODIV C
Solar/Wind Helper
0.006
207510AF2-138 C
Solar/Wind Helper
0.121
207511W3-106 GEN
Solar/Wind Helper
0.04
205941AD2-115 GEN
Solar/Wind Helper
0.726
207437AD2-070 GEN
Solar/Wind Helper
0.204
20671928W4-073
Solar/Wind Helper
0.132
20674128FR_U2-059
Solar/Wind Helper
0.006
209116AE2-175 GEN
Solar/Wind Helper
2.589
211065PSPA IPP
Solar/Wind Helper
0.219
963161AG1-165 GEN
Solar/Wind Helper
0.617
208972BECR K09
Solar/Wind Helper
0.454
961331AF2-424 GEN
Solar/Wind Helper
0.601
961421AF2-433 GEN
Solar/Wind Helper
0.6
957921AF2-086 GEN
Solar/Wind Helper
0.593
946691AF1-333 GEN
Solar/Wind Helper
0.59
946741AF1-338 GEN
Solar/Wind Helper
0.59
209071AE2-133 GEN
Solar/Wind Helper
0.107
LAGNLTFEXP_LAGN->PJM
CLTF
14.57
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.068
TVALTFEXP_TVA->PJM
CLTF
7.359
CPLELTFEXP_CPLE->PJM
CLTF
10.55
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.109
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.469
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.93
MECLTFEXP_MEC->PJM
CLTF
10.565
SIGELTFEXP_SIGE->PJM
CLTF
0.334
NYPJM->LTFIMP_NY
CLTF
6.555
LGEELTFEXP_LGEE->PJM
CLTF
4.337
WECLTFEXP_WEC->PJM
CLTF
2.304
AG2-052LTFEXP_AG2-052->PJM
LTF
0.137
AH1-155LTFEXP_AH1-155->PJM
LTF
0.205

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.83 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3279.67
MW Contribution:
5.48
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3150101POSSM6S
50/50
2.254
3150081POSSM6A
50/50
1.478
3150151POSSMC1
50/50
1.99
3150151POSSMC1
50/50
1.99
3150021OMF B
50/50
0.319
3150331BIRCHWDA
50/50
29.538
3150401LDYSMT4
50/50
21.446
3150371LDYSMT1
50/50
20.723
3150501FRIVERG
50/50
1.208
3150351NORNECKC2
50/50
1.543
316223AC1-118
Solar/Wind Harmer
0.448
3141906WESTMOR
Solar/Wind Harmer
-0.007
971781AH1-399 GEN
Solar/Wind Harmer
1.024
966881AG1-559 GEN
Solar/Wind Harmer
0.497
316077AC2-138 C
Solar/Wind Harmer
0.339
316484AD2-074 GEN
Solar/Wind Harmer
4.009
961951AG1-038 GEN
Solar/Wind Harmer
2.098
316473AC1-191 GEN
Solar/Wind Harmer
1.708
3142416OLDCHRC
Solar/Wind Harmer
1.576
3141873WAN 176
Solar/Wind Harmer
1.85
3141766HARMONY
Solar/Wind Harmer
1.387
316203AE2-005 GEN
Solar/Wind Harmer
6.567
3141843SHACKLE
Adder
0.708
316075AC2-137 C
Solar/Wind Harmer
0.417
970293AG2-193 GEN
Solar/Wind Harmer
1.937
3142433PROV 92
Adder
0.268
3142433PROV 92
Adder
0.268
3142946ENON
Solar/Wind Harmer
-0.005
3143096IRON208
Adder
0.572
3143096IRON208
Adder
0.561
3150861SPRUNCD
Adder
0.626
3150921YORKTN3
Adder
3.376
970133AG2-095 GEN
Solar/Wind Harmer
1.697
3144216WINCHST
Adder
0.506
316458AB2-190 GEN2
Solar/Wind Harmer
1.517
315778AD1-151 GEN
Solar/Wind Harmer
13.365
961611AG1-000B GEN
Solar/Wind Harmer
3.149
3151171GRAVELC
Adder
1.858
3147666LOUISA
Solar/Wind Harmer
-0.034
315813AE1-149 C
Solar/Wind Harmer
9.3
3145336SMITFLD
Solar/Wind Harmer
-0.006
970657AG2-426 GEN
Solar/Wind Harmer
2.99
3144536CHRHLND
Solar/Wind Harmer
-0.002
3151101ELIZAR3
Adder
12.198
3144873MCLAUGH
Solar/Wind Harmer
0
3142956BIRDNECK
Solar/Wind Harmer
0.791
944581AF1-123 GEN
Solar/Wind Harmer
67.036
944601AF1-125 GEN
Solar/Wind Harmer
65.99
316017AA1-139 ULT1
Solar/Wind Harmer
1.186
3146456SLIGO L269
Solar/Wind Harmer
-0.015
971153AH1-033 GEN
Solar/Wind Harmer
1.699
316305AF2-043 C
Solar/Wind Harmer
0.441
316246AF1-032 C
Solar/Wind Harmer
0.296
316320Y1-086
Solar/Wind Harmer
0.855
316321Z2-027
Solar/Wind Harmer
0.392
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3132273ORANGE
Solar/Wind Harmer
-0.003
3145273HOLLAND
Solar/Wind Harmer
-0.011
3143336POWHATN
Solar/Wind Harmer
1.452
3146376EDENTON
Solar/Wind Harmer
-0.014
3151761LOISA E
Adder
16.826
3151721LOISA A
Adder
8.211
944011AF1-069 GEN
Solar/Wind Harmer
8.384
3141196NOKESVL
Solar/Wind Harmer
-0.056
3150301M RUN C
Adder
17.078
3150291M RUN B
Adder
16.952
3150241REMNGT4
Adder
16.017
972199AH1-684 GEN
Adder
2.428
972217AH1-693 GEN
Adder
2.112
3156081AA2-088 GEN
Solar/Wind Harmer
4.559
315735AD1-075 GEN1
Solar/Wind Harmer
1.416
3146206CASHIE
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.097
3145893MURPHYS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
966621AG1-532 GEN
Solar/Wind Harmer
0.281
970917AG2-570 GEN
Solar/Wind Harmer
34.605
3146263WOODLND
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.918
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.014
3147043LAWRENC
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.168
316011AB1-132 GEN
Solar/Wind Harmer
2.865
316317KELFORD C
Solar/Wind Harmer
0.635
3145823KELFORD
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.014
959311AF2-222 GEN
Solar/Wind Harmer
14.185
3147133PAMPLIN
Solar/Wind Harmer
-0.042
964241AG1-285 GEN
Solar/Wind Harmer
10.595
942461AE2-259 GEN
Solar/Wind Harmer
2.038
3146926FARMVIL
Solar/Wind Harmer
-0.008
316478AD1-087 GEN
Solar/Wind Harmer
1.168
3146776BUCKING
Solar/Wind Harmer
-0.005
3144293JTRSVLE
Adder
0.287
316212AC1-099_GEN
Solar/Wind Harmer
1.174
972255AH1-712 GEN
Adder
61.437
972003AH1-546 GEN
Solar/Wind Harmer
5.477
227287AC2-120 GEN
Solar/Wind Helper
1.237
226910AB2-157 C
Solar/Wind Helper
0.048
208835TUHI V3-051
Solar/Wind Helper
0.029
233987AB2-037 GEN
Solar/Wind Helper
2.911
232417X3-008 C
Solar/Wind Helper
0.289
233964AF2-378 GEN
Solar/Wind Helper
0.052
232422X3-066 FULL
Solar/Wind Helper
0.142
233933AB2-153 GEN
Solar/Wind Helper
0.289
233923SMA
Solar/Wind Helper
0.933
233997TMININ_4.2
Solar/Wind Helper
0.255
232406W1-004 FULL
Solar/Wind Helper
0.63
232434Z2-077 GEN
Solar/Wind Helper
0.157
233935AB2-179 C
Solar/Wind Helper
1.573
233950AC2-186 GEN
Solar/Wind Helper
0.144
230415AB2-049 C
Solar/Wind Helper
0.036
219623KINSLEYBEA C
Solar/Wind Helper
0.003
219921AF1-264
Solar/Wind Helper
0.061
219914AD2-027 C
Solar/Wind Helper
0.136
219291REEVESSOUT C
Solar/Wind Helper
0.014
218660EHAMPSOLAR C
Solar/Wind Helper
0.039
219688LUMSOLAR_S C
Solar/Wind Helper
0.047
219236SOUTHERNHQ C
Solar/Wind Helper
0.006
959561AF2-247 GEN
Solar/Wind Helper
0.024
20715728PEM_W1-119
Solar/Wind Helper
0.112
3140676OCCOQUN
50/50
0.024
970053AG2-049 GEN
50/50
2.882
3141316ARNOLDS
50/50
0.022
3150411LDYSMT5
50/50
21.513
3150381LDYSMT2
50/50
20.589
972213AH1-691 GEN
50/50
3.483
972215AH1-692 GEN
50/50
3.483
3141426STAFORD
Solar/Wind Harmer
-0.004
944491AF1-114 GEN
Solar/Wind Harmer
5.051
316468AD1-105 GEN
Solar/Wind Harmer
1.898
3141813NORNECK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
3138133OCRAN
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.466
3141873WAN 176
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.351
3143873LANEXA
Solar/Wind Harmer
-0.009
3142433PROV 92
Adder
0.268
3142433PROV 92
Adder
0.268
957831AF2-077 GEN
Solar/Wind Harmer
0.461
3138283WHITEMARSH
Solar/Wind Harmer
0.024
971285AH1-108 GEN
Adder
1.024
316382AG1-145 C
Solar/Wind Harmer
0.458
316159AE1-175 C
Solar/Wind Harmer
0.408
316233AE1-074 FULL
Solar/Wind Harmer
0.407
972223AH1-696 GEN
50/50
15.716
3150151POSSMC1
50/50
1.99
3141346CRANES
50/50
0.215
3150011OMF A
50/50
0.319
972197AH1-683 GEN
50/50
3.349
972219AH1-694 GEN
50/50
2.411
3150351NORNECKC2
50/50
1.517
957971AF2-091 GEN
Solar/Wind Harmer
1.717
972135AH1-637 GEN
Solar/Wind Harmer
1.704
966881AG1-559 GEN
Solar/Wind Harmer
0.17
316337AD2-073 GEN
Solar/Wind Harmer
0.439
964211AG1-282 GEN
Solar/Wind Harmer
0.483
3141726DUNNSVL
Solar/Wind Harmer
-0.064
316404AE1-155 C
Solar/Wind Harmer
3.059
958261AF2-120 GEN
Solar/Wind Harmer
6.21
962861AG1-135 GEN
Solar/Wind Harmer
6
3138133OCRAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.874
316280AD1-041 GEN
Solar/Wind Harmer
1.171
316314AB2-024 C
Solar/Wind Harmer
1.331
971777AH1-397 GEN
Solar/Wind Harmer
1.818
3142433PROV 92
Solar/Wind Harmer
-0.062
3142433PROV 92
Adder
0.268
3142433PROV 92
Adder
0.268
315975AC1-164 GENB
Solar/Wind Harmer
0.104
3143096IRON208
Adder
0.572
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
64.944
3150851SPRUNCC
Adder
0.626
971317AH1-138 GEN
Solar/Wind Harmer
1.899
3143526WINTERP
Solar/Wind Harmer
-0.078
316447AC1-158 HLD
Solar/Wind Harmer
3.258
316044AC1-158 PL1
Solar/Wind Harmer
1.481
315671AE2-027_GEN
Solar/Wind Harmer
2.725
3138126ROCKLANDING
Solar/Wind Harmer
0.046
316132AB2-190 GEN1
Solar/Wind Harmer
1.517
971069AG2-661 GEN
Solar/Wind Harmer
2.376
316369SG1_INVT
Solar/Wind Harmer
2.675
3143226MDLTHAN
Solar/Wind Harmer
-0.015
961611AG1-000B GEN
Solar/Wind Harmer
7.38
3151171GRAVELC
Adder
1.413
3147666LOUISA
Solar/Wind Harmer
-0.059
316192AB2-158 GEN
Solar/Wind Harmer
1.766
3145336SMITFLD
Solar/Wind Harmer
-0.059
315773AC2-141 GEN
Solar/Wind Harmer
6.192
316381AD1-082 GEN
Solar/Wind Harmer
1.355
316375AC2-012 GEN
Solar/Wind Harmer
5.105
316036AC1-147 C
Solar/Wind Harmer
0.397
3150981CHESPKA
Adder
1.64
316072AD1-144
Solar/Wind Harmer
0.297
944591AF1-124 GEN
Solar/Wind Harmer
67.278
3146456SLIGO L269
Solar/Wind Harmer
-0.015
319010AE1-072 C
Solar/Wind Harmer
2.96
316093AE2-104_GEN
Solar/Wind Harmer
4.257
316254AC1-120 GEN1
Solar/Wind Harmer
5.477
316170AC1-121 GEN2
Solar/Wind Harmer
1.826
939411AE1-173 GEN
Solar/Wind Harmer
72.919
940641AE2-051 GEN
Solar/Wind Harmer
13.627
3146516WINFALL
Solar/Wind Harmer
-0.047
3146516WINFALL
Solar/Wind Harmer
-0.014
3143336POWHATN
Solar/Wind Harmer
1.708
315611Z1-036_GEN2
Solar/Wind Harmer
3.547
3130156CHOWAN
Solar/Wind Harmer
-0.014
3151751LOISA D
Adder
8.253
941031AE2-094 GEN
Solar/Wind Harmer
26.758
971685AH1-345 GEN
Solar/Wind Harmer
1.246
315683AE1-153 C
Solar/Wind Harmer
13.241
315816AE2-034 GEN
Solar/Wind Harmer
1.144
3145663CRESWEL
Solar/Wind Harmer
-0.039
971163AH1-040 GEN
Solar/Wind Harmer
13.291
3150281M RUN A
Adder
17.089
3150221REMNGT2
Adder
15.911
3150211REMNGT1
Adder
15.806
972201AH1-685 GEN
Adder
2.745
315737AD1-076 GEN
Solar/Wind Harmer
2.663
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.494
316023GEN1_S
Solar/Wind Harmer
0.939
3145893MURPHYS
Solar/Wind Harmer
-0.056
3145893MURPHYS
Solar/Wind Harmer
0.414
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.865
960081AF2-299 GEN
Solar/Wind Harmer
1.558
970919AG2-571 GEN
Solar/Wind Harmer
4.38
3145683EARLEYS
Solar/Wind Harmer
-0.014
315607AA1-063A GEN
Solar/Wind Harmer
1.393
970937AG2-583 GEN
Solar/Wind Harmer
9.936
316087AB2-174 GEN
Solar/Wind Harmer
1.965
3146263WOODLND
Solar/Wind Harmer
-0.014
970087AG2-069 GEN
Solar/Wind Harmer
12.909
3145963POPLR C
Solar/Wind Harmer
-0.014
3147043LAWRENC
Adder
1.105
3145823KELFORD
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
42.844
3145783HORNRTN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.826
3145796HORNRTN
Solar/Wind Harmer
-0.045
3145796HORNRTN
Solar/Wind Harmer
-0.014
970685AG2-442 GEN
Solar/Wind Harmer
11.898
316034AC1-036 C
Solar/Wind Harmer
0.251
3146926FARMVIL
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.005
971563AH1-280 GEN
Solar/Wind Harmer
1.688
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.227
972277AH1-723 GEN
Adder
71.593
208835TUHI V3-051
Solar/Wind Helper
0.029
232426Y1-080 FULL
Solar/Wind Helper
0.048
233918AB1-142 GEN
Solar/Wind Helper
0.623
233996TM1833_GEN
Solar/Wind Helper
0.255
233998TM1NIN_3.36
Solar/Wind Helper
0.255
232404W1-003 C
Solar/Wind Helper
0.63
232408W1-005 C
Solar/Wind Helper
0.63
233944AB2-135 GEN
Solar/Wind Helper
0.732
228729W2-030 C
Solar/Wind Helper
0.132
219766PARADISE C
Solar/Wind Helper
0.065
219686LUMSOLAR_N C
Solar/Wind Helper
0.047
219907AC1-030 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.135
20716028EGP_W2-019
Solar/Wind Helper
0.022
20715828PEM_W1-120
Solar/Wind Helper
0.112
963711AG1-223 GEN
Solar/Wind Helper
0.074
219276PARKLANDSO C
Solar/Wind Helper
0.103
20714528FRN_Y2-051
Solar/Wind Helper
0.066
219680HOPEWELLV C1
Solar/Wind Helper
0.004
20715228NPK_W1-113
Solar/Wind Helper
0.09
20720528MAN_W1-024
Solar/Wind Helper
0.032
218524CNTRALGAS1 C
Solar/Wind Helper
0.182
218440SUMMTASSOC C
Solar/Wind Helper
0.019
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.084
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673628F1S_V4-069
Solar/Wind Helper
0.034
20671828STAW2-080
Solar/Wind Helper
0.03
217209CENTRL HS C
Solar/Wind Helper
0.009
217208PARK ELE C
Solar/Wind Helper
0.005
20676728BRNX1-095
Solar/Wind Helper
0.033
207439AE1-081 C O1
Solar/Wind Helper
0.021
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676328BVR_Y1-020
Solar/Wind Helper
0.03
20674628WNG_W3-110
Solar/Wind Helper
0.099
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674928WA_W3-044
Solar/Wind Helper
0.108
20675828AU_W4-064
Solar/Wind Helper
0.033
207484AF2-139 C O1
Solar/Wind Helper
0.092
3150091POSSM6B
50/50
1.478
3150071POSSM 5
50/50
90.937
3150181POSSMC2
50/50
2.006
3150181POSSMC2
50/50
1.99
3150181POSSMC2
50/50
1.99
957191AF2-013 GEN
50/50
14.169
3150391LDYSMT3
50/50
21.406
972195AH1-682 GEN
50/50
2.813
3150341NORNECKC1
50/50
1.594
3150341NORNECKC1
50/50
1.581
315673AE1-157 GEN
Solar/Wind Harmer
12.502
972189AH1-679 GEN
Adder
2.392
316487AF1-042 GEN
Solar/Wind Harmer
2.098
966871AG1-558 GEN
Solar/Wind Harmer
0.477
971281AH1-106 GEN
Solar/Wind Harmer
2.46
971283AH1-107 GEN
Solar/Wind Harmer
2.46
315839AE2-212 C
Solar/Wind Harmer
0.452
315697AD1-025 GEN
Solar/Wind Harmer
3.026
3143316POE
Solar/Wind Harmer
-0.059
3151201GRAVEL4
Adder
9.67
3151221GRAVEL6
Adder
9.659
3151191GRAVEL3
Adder
9.548
3151211GRAVEL5
Adder
9.548
316164AC1-076 GEN
Solar/Wind Harmer
1.254
971445AH1-216 GEN
Solar/Wind Harmer
9.202
316236AE1-162_GEN
Solar/Wind Harmer
0.447
970657AG2-426 GEN
Solar/Wind Harmer
0.933
3151081ELIZAR1
Adder
12.044
3151091ELIZAR2
Adder
11.835
316316AC1-027 C
Solar/Wind Harmer
0.452
315833AF1-017_GEN
Solar/Wind Harmer
2.792
316311AC2-079 GEN
Solar/Wind Harmer
7.417
316018AA1-139 ULT2
Solar/Wind Harmer
1.256
957871AF2-081 GEN
Solar/Wind Harmer
7.347
3146406KITTY HAWK
Solar/Wind Harmer
0.012
313526AB2-022
Solar/Wind Harmer
0.393
3146486SUNBURY
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.015
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
3146396TANGLEW
Solar/Wind Harmer
0.268
315651AD1-115 GEN
Solar/Wind Harmer
6.382
315814AE2-033 C
Solar/Wind Harmer
13.428
316258AE1-075 C
Solar/Wind Harmer
0.348
316405AF2-144 C
Solar/Wind Harmer
0.368
315800Z1-036_GEN1
Solar/Wind Harmer
3.547
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
970533AG2-339 GEN
Solar/Wind Harmer
9.597
970673AG2-436 GEN
Solar/Wind Harmer
31.088
3147346CASHSCORNER
Solar/Wind Harmer
0.219
971967AH1-528 GEN
Solar/Wind Harmer
26.504
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315732AD1-074 GEN1
Solar/Wind Harmer
2.832
315733AD1-074 GEN2
Solar/Wind Harmer
2.832
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.114
316318V4-068
Solar/Wind Harmer
0.348
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
316463AE2-346 GEN
Solar/Wind Harmer
0.224
3145513AHOSKIE
Solar/Wind Harmer
0.121
961941AG1-037 GEN
Solar/Wind Harmer
0.104
3145513AHOSKIE
Solar/Wind Harmer
-0.014
946281AF1-292 GEN
Solar/Wind Harmer
0.31
3146043SEABORD
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.014
970085AG2-068 GEN
Solar/Wind Harmer
8.606
970581AG2-369 GEN
Solar/Wind Harmer
7.401
3137643SOCKMAN
Solar/Wind Harmer
-0.055
316426AA2-053 GEN
Solar/Wind Harmer
1.382
315652AC1-086 GEN
Solar/Wind Harmer
15.431
316174AB2-169 GEN
Solar/Wind Harmer
2.105
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.005
970683AG2-441 GEN
Solar/Wind Harmer
9.607
970681AG2-440 GEN
Solar/Wind Harmer
6.376
3146033SCOT NK
Solar/Wind Harmer
-0.054
316486AD2-202 GEN
Solar/Wind Harmer
0.342
971845AH1-439 GEN
Solar/Wind Harmer
7.184
316322AB2-045
Solar/Wind Harmer
0.454
946301AF1-294 GEN
Solar/Wind Harmer
3.461
961791AG1-021 GEN
Solar/Wind Harmer
1.688
316210AC1-098 GEN
Solar/Wind Harmer
2.113
970831AG2-522 GEN
Solar/Wind Harmer
6.744
3144303KENBRDG
Solar/Wind Harmer
-0.011
972205AH1-687 GEN
Adder
5.125
226929AD2-058 GEN
Solar/Wind Helper
0.389
233915AB1-141 GEN
Solar/Wind Helper
0.623
233940AF2-379 C
Solar/Wind Helper
0.077
233901CHERRYDALE C
Solar/Wind Helper
0.289
232432Z2-076 GEN
Solar/Wind Helper
0.083
228728W1-130C
Solar/Wind Helper
0.064
230434AG1-499 GEN
Solar/Wind Helper
0.274
230407AD2-065 C
Solar/Wind Helper
0.048
227927V4-067C
Solar/Wind Helper
0.012
219258KINSLEYDEP C
Solar/Wind Helper
0.091
219615MILLCREEK C
Solar/Wind Helper
0.031
20720728JCB_W1-129
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.067
207445AB1-138_GEN
Solar/Wind Helper
0.121
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.218
218526CNTRALGAS2 C
Solar/Wind Helper
0.182
20675528CPH_W2-050
Solar/Wind Helper
0.128
20673828FLE_V3-070
Solar/Wind Helper
0.098
20676128MHD_W3-029
Solar/Wind Helper
0.108
20676428JCR_X2-075
Solar/Wind Helper
0.076
964851AG1-348 GEN
Solar/Wind Helper
0.069
207408W3-077 C
Solar/Wind Helper
0.092
20675128HRM_W1-127
Solar/Wind Helper
0.032
205956AE1-196_GEN
Solar/Wind Helper
0.53
205943AE1-185 GEN
Solar/Wind Helper
0.525
961261AF2-417 GEN
Solar/Wind Helper
0.456
209027LOR2_Q27
Solar/Wind Helper
1.043
212266LOR1
Solar/Wind Helper
0.304
209029WAYMART-WD
Solar/Wind Helper
0.835
20714928UPF_X1-085
Solar/Wind Helper
0.006
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.356
219612MATRIX C
Solar/Wind Helper
0.027
20716928W4-060COL
Solar/Wind Helper
0.059
217213AMBOY SO C
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
207442AE1-156 GEN
Solar/Wind Helper
0.368
20673728F2S_V4-070
Solar/Wind Helper
0.034
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
205941AD2-115 GEN
Solar/Wind Helper
0.543
207510AF2-138 C
Solar/Wind Helper
0.09
207511W3-106 GEN
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.151
20671928W4-073
Solar/Wind Helper
0.098
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.914
211065PSPA IPP
Solar/Wind Helper
0.162
963161AG1-165 GEN
Solar/Wind Helper
0.455
208972BECR K09
Solar/Wind Helper
0.335
961331AF2-424 GEN
Solar/Wind Helper
0.442
961421AF2-433 GEN
Solar/Wind Helper
0.441
957921AF2-086 GEN
Solar/Wind Helper
0.436
970257AG2-171 GEN
Solar/Wind Harmer
4.189
20675728RH_W2-091
Solar/Wind Helper
0.089
207518AF1-320_GEN
Solar/Wind Helper
1.72
205932AD2-116_GEN
Solar/Wind Helper
0.53
211065PSPA IPP
Solar/Wind Helper
0.162
961301AF2-421 GEN
Solar/Wind Helper
0.455
963151AG1-164 GEN
Solar/Wind Helper
0.455
961341AF2-425 GEN
Solar/Wind Helper
0.442
966871AG1-558 GEN
Solar/Wind Harmer
0.163
3142296MT RD221
Adder
0.445
316312AB1-027
Solar/Wind Harmer
0.525
316156AD2-030 GEN
Solar/Wind Harmer
0.415
315666AE1-190 GEN
Solar/Wind Harmer
0.468
316441AF1-014 GEN
Solar/Wind Harmer
1.05
3150691DARBY 3
Adder
9.924
3150701DARBY 4
Adder
9.901
3150681DARBY 2
Adder
9.889
3150671DARBY 1
Adder
9.878
3142366NRTHEST
Adder
0.451
315976AC1-164 GENA
Solar/Wind Harmer
3.514
316169AC1-164_GENC
Solar/Wind Harmer
3.037
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
64.259
3143526WINTERP
Solar/Wind Harmer
-0.078
316045AC1-158 PL2
Solar/Wind Harmer
4.741
316450AC1-158 RIC
Solar/Wind Harmer
0.395
316240AF1-291 C
Solar/Wind Harmer
0.455
316033AB2-134 GEN
Solar/Wind Harmer
4.829
971223AH1-071 GEN
Solar/Wind Harmer
1.875
316294AC1-161 GEN
Solar/Wind Harmer
4.787
316083AB2-161 GEN
Solar/Wind Harmer
2.402
3150991CHESPKB
Adder
1.376
3150991CHESPKB
Adder
1.343
316185AD1-033 GEN
Solar/Wind Harmer
1.551
3145506HICKORY
Solar/Wind Harmer
-0.059
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316349AD2-085 GEN
Solar/Wind Harmer
1.305
316339AD2-160 GEN
Solar/Wind Harmer
0.989
316388AE2-253 GEN
Solar/Wind Harmer
0.989
3137176SLIGO L2192
Solar/Wind Harmer
-0.058
3146456SLIGO L269
Solar/Wind Harmer
1.734
3130086AYDLETT
Solar/Wind Harmer
-0.058
315835AF2-110_GEN
Solar/Wind Harmer
1.83
3146386ELIZ CT
Solar/Wind Harmer
-0.015
316431W1029_GEN1
Solar/Wind Harmer
2.632
316433W1029_GEN2
Solar/Wind Harmer
2.632
316435W1029_GEN3
Solar/Wind Harmer
2.632
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3144356SAPONY
Solar/Wind Harmer
0.504
316315AB2-025 C
Solar/Wind Harmer
0.389
316313AB2-026
Solar/Wind Harmer
0.387
315742AE1-103 GEN
Solar/Wind Harmer
3.412
3146376EDENTON
Solar/Wind Harmer
0.425
3146376EDENTON
Solar/Wind Harmer
0.425
966001AG1-469 GEN
Solar/Wind Harmer
0.27
3151731LOISA B
Adder
8.253
316006AB2-029 C
Solar/Wind Harmer
0.817
316336AC2-165 C
Solar/Wind Harmer
8.886
315614AA2-178 GEN
Solar/Wind Harmer
1.525
972185AH1-677 GEN
Adder
7.054
972187AH1-678 GEN
Adder
3.563
970933AG2-581 GEN
Solar/Wind Harmer
13.132
316065AD1-022 GEN
Solar/Wind Harmer
7
316365GEN2_N
Solar/Wind Harmer
0.939
3145893MURPHYS
Solar/Wind Harmer
0.39
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316140AB2-099
Solar/Wind Harmer
0.093
313506AB2-031 GEN
Solar/Wind Harmer
1.104
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
962571AG1-106 GEN
Solar/Wind Harmer
1.972
970099AG2-077 GEN
Solar/Wind Harmer
17.138
3145593CAROLNA
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.62
3145783HORNRTN
Solar/Wind Harmer
1.296
3145783HORNRTN
Solar/Wind Harmer
0.405
3145783HORNRTN
Solar/Wind Harmer
0.162
3145796HORNRTN
Solar/Wind Harmer
-0.041
970301AG2-198 GEN
Solar/Wind Harmer
6.798
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
3146776BUCKING
Solar/Wind Harmer
-0.054
3146776BUCKING
Solar/Wind Harmer
-0.004
958211AF2-115 GEN
Solar/Wind Harmer
2.11
3144293JTRSVLE
Adder
0.287
972193AH1-681 GEN
Adder
2.745
970323AG2-213 GEN
Solar/Wind Harmer
6.74
223401AF1-299 GEN
Solar/Wind Helper
0.645
223402AF1-300 C
Solar/Wind Helper
0.645
232424Y1-079 C
Solar/Wind Helper
0.144
233946AB2-136 GEN
Solar/Wind Helper
0.706
234036AF2-325 C
Solar/Wind Helper
0.052
232436AB1-176 C
Solar/Wind Helper
0.055
233930AB2-032 GEN
Solar/Wind Helper
0.472
233994AC2-023 GEN
Solar/Wind Helper
1.193
232428Y3-058 C
Solar/Wind Helper
0.42
232410W1-006 C
Solar/Wind Helper
0.63
234015AF2-250 C
Solar/Wind Helper
0.047
233982AB2-133 GEN
Solar/Wind Helper
0.445
233952AC2-187 GEN
Solar/Wind Helper
0.288
233954AC2-188 GEN
Solar/Wind Helper
0.288
230511AF1-262
Solar/Wind Helper
0.017
230433AD2-135 GEN
Solar/Wind Helper
0.02
228754AB1-001 C
Solar/Wind Helper
0.031
219904AC1-010 C
Solar/Wind Helper
0.072
219912AD2-042 GEN
Solar/Wind Helper
0.177
219272CLEANLIGHT C
Solar/Wind Helper
0.03
219906AC1-017 C
Solar/Wind Helper
0.049
219607WPEMNERT C
Solar/Wind Helper
0.094
219304NAMERICA C
Solar/Wind Helper
0.154
214067T20SOLAR
Solar/Wind Helper
0.013
20720828JCB_W4-025
Solar/Wind Helper
0.074
207459AE1-142 C O1
Solar/Wind Helper
0.336
20714828MDF_W3-079
Solar/Wind Helper
0.15
20742028HF_AC1-207
Solar/Wind Helper
0.161
218438BLK ROCK C
Solar/Wind Helper
0.031
20675428EAM_W2-061
Solar/Wind Helper
0.018
217081WEATEXAS C
Solar/Wind Helper
0.014
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.025
207471AF2-354 C
Solar/Wind Helper
0.185
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
961431AF2-434 GEN
Solar/Wind Helper
0.441
LAGNLTFEXP_LAGN->PJM
CLTF
11.662
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.32
TVALTFEXP_TVA->PJM
CLTF
5.895
CPLELTFEXP_CPLE->PJM
CLTF
8.786
CBM West 2LTFEXP_CBM-W2->PJM
CBM
72.3
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.703
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.494
MECLTFEXP_MEC->PJM
CLTF
8.301
SIGELTFEXP_SIGE->PJM
CLTF
0.262
NYPJM->LTFIMP_NY
CLTF
4.872
LGEELTFEXP_LGEE->PJM
CLTF
3.396
WECLTFEXP_WEC->PJM
CLTF
1.8
AG2-052LTFEXP_AG2-052->PJM
LTF
0.107
AH1-155LTFEXP_AH1-155->PJM
LTF
0.16

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o PEPCO_P4_PP41_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
PEPCO_P4_PP41_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.07 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3194.05
MW Contribution:
5.46
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
PEPCO_P4_PP41_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:98.66 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3057.4
MW Contribution:
5.29
Bus #Bus NameTypeMW Contribution
3150101POSSM6S
50/50
2.253
3150081POSSM6A
50/50
1.477
3150151POSSMC1
50/50
1.989
3150151POSSMC1
50/50
1.989
3150021OMF B
50/50
0.319
3150331BIRCHWDA
50/50
29.509
3150401LDYSMT4
50/50
21.415
3150371LDYSMT1
50/50
20.692
3150501FRIVERG
50/50
1.206
3150351NORNECKC2
50/50
1.54
316223AC1-118
Solar/Wind Harmer
0.447
3141906WESTMOR
Solar/Wind Harmer
-0.007
971781AH1-399 GEN
Solar/Wind Harmer
1.022
966881AG1-559 GEN
Solar/Wind Harmer
0.496
316077AC2-138 C
Solar/Wind Harmer
0.339
316484AD2-074 GEN
Solar/Wind Harmer
4.002
961951AG1-038 GEN
Solar/Wind Harmer
2.094
316473AC1-191 GEN
Solar/Wind Harmer
1.705
3142416OLDCHRC
Solar/Wind Harmer
1.573
3141873WAN 176
Solar/Wind Harmer
1.847
3141766HARMONY
Solar/Wind Harmer
1.384
316203AE2-005 GEN
Solar/Wind Harmer
6.554
3141843SHACKLE
Adder
0.707
316075AC2-137 C
Solar/Wind Harmer
0.416
970293AG2-193 GEN
Solar/Wind Harmer
1.933
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
3142946ENON
Solar/Wind Harmer
-0.005
3143096IRON208
Adder
0.571
3143096IRON208
Adder
0.56
3150861SPRUNCD
Adder
0.624
3150921YORKTN3
Adder
3.369
970133AG2-095 GEN
Solar/Wind Harmer
1.694
3144216WINCHST
Adder
0.505
316458AB2-190 GEN2
Solar/Wind Harmer
1.514
315778AD1-151 GEN
Solar/Wind Harmer
13.337
961611AG1-000B GEN
Solar/Wind Harmer
3.142
3151171GRAVELC
Adder
1.854
3147666LOUISA
Solar/Wind Harmer
-0.034
315813AE1-149 C
Solar/Wind Harmer
9.28
3145336SMITFLD
Solar/Wind Harmer
-0.006
970657AG2-426 GEN
Solar/Wind Harmer
2.983
3144536CHRHLND
Solar/Wind Harmer
-0.002
3151101ELIZAR3
Adder
12.171
3144873MCLAUGH
Solar/Wind Harmer
0
3142956BIRDNECK
Solar/Wind Harmer
0.79
944581AF1-123 GEN
Solar/Wind Harmer
66.887
944601AF1-125 GEN
Solar/Wind Harmer
65.843
316017AA1-139 ULT1
Solar/Wind Harmer
1.183
3146456SLIGO L269
Solar/Wind Harmer
-0.015
971153AH1-033 GEN
Solar/Wind Harmer
1.695
316305AF2-043 C
Solar/Wind Harmer
0.44
316246AF1-032 C
Solar/Wind Harmer
0.295
316320Y1-086
Solar/Wind Harmer
0.853
316321Z2-027
Solar/Wind Harmer
0.391
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3145273HOLLAND
Solar/Wind Harmer
-0.011
3132273ORANGE
Solar/Wind Harmer
-0.003
3143336POWHATN
Solar/Wind Harmer
1.448
3146376EDENTON
Solar/Wind Harmer
-0.014
3151761LOISA E
Adder
16.784
3151721LOISA A
Adder
8.19
944011AF1-069 GEN
Solar/Wind Harmer
8.364
3141196NOKESVL
Solar/Wind Harmer
-0.056
3150301M RUN C
Adder
17.03
3150291M RUN B
Adder
16.904
3150241REMNGT4
Adder
15.972
972199AH1-684 GEN
Adder
2.422
972217AH1-693 GEN
Adder
2.106
3156081AA2-088 GEN
Solar/Wind Harmer
4.547
972223AH1-696 GEN
50/50
15.712
3150151POSSMC1
50/50
1.989
3141346CRANES
50/50
0.215
3150011OMF A
50/50
0.319
972197AH1-683 GEN
50/50
3.344
972219AH1-694 GEN
50/50
2.408
3150351NORNECKC2
50/50
1.515
957971AF2-091 GEN
Solar/Wind Harmer
1.715
972135AH1-637 GEN
Solar/Wind Harmer
1.702
966881AG1-559 GEN
Solar/Wind Harmer
0.17
316337AD2-073 GEN
Solar/Wind Harmer
0.438
964211AG1-282 GEN
Solar/Wind Harmer
0.482
3141726DUNNSVL
Solar/Wind Harmer
-0.064
316404AE1-155 C
Solar/Wind Harmer
3.053
958261AF2-120 GEN
Solar/Wind Harmer
6.199
962861AG1-135 GEN
Solar/Wind Harmer
5.989
3138133OCRAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.87
316280AD1-041 GEN
Solar/Wind Harmer
1.169
316314AB2-024 C
Solar/Wind Harmer
1.329
971777AH1-397 GEN
Solar/Wind Harmer
1.814
3142433PROV 92
Solar/Wind Harmer
-0.062
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
315975AC1-164 GENB
Solar/Wind Harmer
0.104
3143096IRON208
Adder
0.571
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
64.814
3150851SPRUNCC
Adder
0.624
971317AH1-138 GEN
Solar/Wind Harmer
1.895
3143526WINTERP
Solar/Wind Harmer
-0.078
316447AC1-158 HLD
Solar/Wind Harmer
3.25
316044AC1-158 PL1
Solar/Wind Harmer
1.478
315671AE2-027_GEN
Solar/Wind Harmer
2.72
3138126ROCKLANDING
Solar/Wind Harmer
0.046
3140676OCCOQUN
50/50
0.023
970053AG2-049 GEN
50/50
2.879
3141316ARNOLDS
50/50
0.022
3150411LDYSMT5
50/50
21.482
3150381LDYSMT2
50/50
20.559
972213AH1-691 GEN
50/50
3.478
972215AH1-692 GEN
50/50
3.478
3141426STAFORD
Solar/Wind Harmer
-0.004
944491AF1-114 GEN
Solar/Wind Harmer
5.044
316468AD1-105 GEN
Solar/Wind Harmer
1.895
3141813NORNECK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
3138133OCRAN
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.466
3141873WAN 176
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.351
3143873LANEXA
Solar/Wind Harmer
-0.009
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
957831AF2-077 GEN
Solar/Wind Harmer
0.46
3138283WHITEMARSH
Solar/Wind Harmer
0.024
971285AH1-108 GEN
Adder
1.022
316382AG1-145 C
Solar/Wind Harmer
0.457
316159AE1-175 C
Solar/Wind Harmer
0.407
316233AE1-074 FULL
Solar/Wind Harmer
0.406
971281AH1-106 GEN
Solar/Wind Harmer
2.455
971283AH1-107 GEN
Solar/Wind Harmer
2.455
315839AE2-212 C
Solar/Wind Harmer
0.451
315697AD1-025 GEN
Solar/Wind Harmer
3.019
3143316POE
Solar/Wind Harmer
-0.059
3151201GRAVEL4
Adder
9.649
3151221GRAVEL6
Adder
9.638
3151191GRAVEL3
Adder
9.527
3151211GRAVEL5
Adder
9.527
316164AC1-076 GEN
Solar/Wind Harmer
1.251
971445AH1-216 GEN
Solar/Wind Harmer
9.181
316236AE1-162_GEN
Solar/Wind Harmer
0.446
316132AB2-190 GEN1
Solar/Wind Harmer
1.514
971069AG2-661 GEN
Solar/Wind Harmer
2.371
316369SG1_INVT
Solar/Wind Harmer
2.669
3143226MDLTHAN
Solar/Wind Harmer
-0.015
961611AG1-000B GEN
Solar/Wind Harmer
7.364
3151171GRAVELC
Adder
1.41
3147666LOUISA
Solar/Wind Harmer
-0.059
316192AB2-158 GEN
Solar/Wind Harmer
1.762
3145336SMITFLD
Solar/Wind Harmer
-0.059
315773AC2-141 GEN
Solar/Wind Harmer
6.178
316381AD1-082 GEN
Solar/Wind Harmer
1.352
316375AC2-012 GEN
Solar/Wind Harmer
5.094
316036AC1-147 C
Solar/Wind Harmer
0.396
3150981CHESPKA
Adder
1.637
316072AD1-144
Solar/Wind Harmer
0.297
944591AF1-124 GEN
Solar/Wind Harmer
67.128
3146456SLIGO L269
Solar/Wind Harmer
-0.015
319010AE1-072 C
Solar/Wind Harmer
2.954
970657AG2-426 GEN
Solar/Wind Harmer
0.931
3151081ELIZAR1
Adder
12.017
3151091ELIZAR2
Adder
11.809
316316AC1-027 C
Solar/Wind Harmer
0.451
315833AF1-017_GEN
Solar/Wind Harmer
2.786
316311AC2-079 GEN
Solar/Wind Harmer
7.4
316018AA1-139 ULT2
Solar/Wind Harmer
1.253
957871AF2-081 GEN
Solar/Wind Harmer
7.331
3146406KITTY HAWK
Solar/Wind Harmer
0.012
313526AB2-022
Solar/Wind Harmer
0.392
3146486SUNBURY
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.015
3146396TANGLEW
Solar/Wind Harmer
0.267
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
315651AD1-115 GEN
Solar/Wind Harmer
6.366
315814AE2-033 C
Solar/Wind Harmer
13.396
316258AE1-075 C
Solar/Wind Harmer
0.348
316405AF2-144 C
Solar/Wind Harmer
0.367
315800Z1-036_GEN1
Solar/Wind Harmer
3.539
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
970533AG2-339 GEN
Solar/Wind Harmer
9.574
970673AG2-436 GEN
Solar/Wind Harmer
31.012
3147346CASHSCORNER
Solar/Wind Harmer
0.218
971967AH1-528 GEN
Solar/Wind Harmer
26.439
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315732AD1-074 GEN1
Solar/Wind Harmer
2.825
315733AD1-074 GEN2
Solar/Wind Harmer
2.825
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.099
316318V4-068
Solar/Wind Harmer
0.347
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
316463AE2-346 GEN
Solar/Wind Harmer
0.223
3145513AHOSKIE
Solar/Wind Harmer
0.121
961941AG1-037 GEN
Solar/Wind Harmer
0.104
3145513AHOSKIE
Solar/Wind Harmer
-0.014
946281AF1-292 GEN
Solar/Wind Harmer
0.309
3146043SEABORD
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.014
970085AG2-068 GEN
Solar/Wind Harmer
8.583
970581AG2-369 GEN
Solar/Wind Harmer
7.382
3137643SOCKMAN
Solar/Wind Harmer
-0.054
316426AA2-053 GEN
Solar/Wind Harmer
1.378
315652AC1-086 GEN
Solar/Wind Harmer
15.391
316174AB2-169 GEN
Solar/Wind Harmer
2.1
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.005
970683AG2-441 GEN
Solar/Wind Harmer
9.581
970681AG2-440 GEN
Solar/Wind Harmer
6.359
3146033SCOT NK
Solar/Wind Harmer
-0.054
316486AD2-202 GEN
Solar/Wind Harmer
0.341
971845AH1-439 GEN
Solar/Wind Harmer
7.164
316322AB2-045
Solar/Wind Harmer
0.452
946301AF1-294 GEN
Solar/Wind Harmer
3.452
961791AG1-021 GEN
Solar/Wind Harmer
1.684
316210AC1-098 GEN
Solar/Wind Harmer
2.107
970831AG2-522 GEN
Solar/Wind Harmer
6.726
3144303KENBRDG
Solar/Wind Harmer
-0.011
972205AH1-687 GEN
Adder
5.111
226929AD2-058 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.621
233940AF2-379 C
Solar/Wind Helper
0.077
233901CHERRYDALE C
Solar/Wind Helper
0.288
232432Z2-076 GEN
Solar/Wind Helper
0.083
228728W1-130C
Solar/Wind Helper
0.064
230434AG1-499 GEN
Solar/Wind Helper
0.273
230407AD2-065 C
Solar/Wind Helper
0.048
227927V4-067C
Solar/Wind Helper
0.012
219258KINSLEYDEP C
Solar/Wind Helper
0.091
219615MILLCREEK C
Solar/Wind Helper
0.031
20720728JCB_W1-129
Solar/Wind Helper
0.066
20715028HAN_X4-015
Solar/Wind Helper
0.066
207445AB1-138_GEN
Solar/Wind Helper
0.12
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.217
218526CNTRALGAS2 C
Solar/Wind Helper
0.181
20675528CPH_W2-050
Solar/Wind Helper
0.128
20673828FLE_V3-070
Solar/Wind Helper
0.097
20676128MHD_W3-029
Solar/Wind Helper
0.108
20676428JCR_X2-075
Solar/Wind Helper
0.076
964851AG1-348 GEN
Solar/Wind Helper
0.069
207408W3-077 C
Solar/Wind Helper
0.092
20675128HRM_W1-127
Solar/Wind Helper
0.032
205956AE1-196_GEN
Solar/Wind Helper
0.518
205943AE1-185 GEN
Solar/Wind Helper
0.513
961261AF2-417 GEN
Solar/Wind Helper
0.453
209027LOR2_Q27
Solar/Wind Helper
1.037
212266LOR1
Solar/Wind Helper
0.302
209029WAYMART-WD
Solar/Wind Helper
0.83
315735AD1-075 GEN1
Solar/Wind Harmer
1.413
3146206CASHIE
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.097
3145893MURPHYS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
966621AG1-532 GEN
Solar/Wind Harmer
0.28
970917AG2-570 GEN
Solar/Wind Harmer
34.516
3146263WOODLND
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.913
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.014
3147043LAWRENC
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.168
316011AB1-132 GEN
Solar/Wind Harmer
2.857
316317KELFORD C
Solar/Wind Harmer
0.633
3145823KELFORD
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.014
959311AF2-222 GEN
Solar/Wind Harmer
14.147
3147133PAMPLIN
Solar/Wind Harmer
-0.042
964241AG1-285 GEN
Solar/Wind Harmer
10.566
942461AE2-259 GEN
Solar/Wind Harmer
2.033
3146926FARMVIL
Solar/Wind Harmer
-0.008
316478AD1-087 GEN
Solar/Wind Harmer
1.165
3146776BUCKING
Solar/Wind Harmer
-0.005
3144293JTRSVLE
Adder
0.286
316212AC1-099_GEN
Solar/Wind Harmer
1.171
972255AH1-712 GEN
Adder
61.265
972003AH1-546 GEN
Solar/Wind Harmer
5.462
227287AC2-120 GEN
Solar/Wind Helper
1.23
226910AB2-157 C
Solar/Wind Helper
0.048
208835TUHI V3-051
Solar/Wind Helper
0.029
233987AB2-037 GEN
Solar/Wind Helper
2.902
232417X3-008 C
Solar/Wind Helper
0.288
233964AF2-378 GEN
Solar/Wind Helper
0.052
232422X3-066 FULL
Solar/Wind Helper
0.141
233933AB2-153 GEN
Solar/Wind Helper
0.288
233923SMA
Solar/Wind Helper
0.931
233997TMININ_4.2
Solar/Wind Helper
0.254
232406W1-004 FULL
Solar/Wind Helper
0.628
232434Z2-077 GEN
Solar/Wind Helper
0.157
233935AB2-179 C
Solar/Wind Helper
1.568
233950AC2-186 GEN
Solar/Wind Helper
0.144
230415AB2-049 C
Solar/Wind Helper
0.036
219623KINSLEYBEA C
Solar/Wind Helper
0.003
219921AF1-264
Solar/Wind Helper
0.06
219914AD2-027 C
Solar/Wind Helper
0.135
219291REEVESSOUT C
Solar/Wind Helper
0.014
218660EHAMPSOLAR C
Solar/Wind Helper
0.039
219688LUMSOLAR_S C
Solar/Wind Helper
0.047
219236SOUTHERNHQ C
Solar/Wind Helper
0.006
959561AF2-247 GEN
Solar/Wind Helper
0.024
20715728PEM_W1-119
Solar/Wind Helper
0.111
20714928UPF_X1-085
Solar/Wind Helper
0.006
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.354
219612MATRIX C
Solar/Wind Helper
0.027
20716928W4-060COL
Solar/Wind Helper
0.059
217213AMBOY SO C
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
207442AE1-156 GEN
Solar/Wind Helper
0.366
20673728F2S_V4-070
Solar/Wind Helper
0.033
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
207510AF2-138 C
Solar/Wind Helper
0.089
205941AD2-115 GEN
Solar/Wind Helper
0.538
207511W3-106 GEN
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.15
20671928W4-073
Solar/Wind Helper
0.098
20674128FR_U2-059
Solar/Wind Helper
0.004
209116AE2-175 GEN
Solar/Wind Helper
1.904
211065PSPA IPP
Solar/Wind Helper
0.161
963161AG1-165 GEN
Solar/Wind Helper
0.453
208972BECR K09
Solar/Wind Helper
0.333
970257AG2-171 GEN
Solar/Wind Harmer
4.178
316093AE2-104_GEN
Solar/Wind Harmer
4.247
316254AC1-120 GEN1
Solar/Wind Harmer
5.463
316170AC1-121 GEN2
Solar/Wind Harmer
1.821
939411AE1-173 GEN
Solar/Wind Harmer
72.752
940641AE2-051 GEN
Solar/Wind Harmer
13.596
3146516WINFALL
Solar/Wind Harmer
-0.047
3146516WINFALL
Solar/Wind Harmer
-0.014
3143336POWHATN
Solar/Wind Harmer
1.704
315611Z1-036_GEN2
Solar/Wind Harmer
3.539
3130156CHOWAN
Solar/Wind Harmer
-0.014
3151751LOISA D
Adder
8.232
941031AE2-094 GEN
Solar/Wind Harmer
26.693
971685AH1-345 GEN
Solar/Wind Harmer
1.242
315683AE1-153 C
Solar/Wind Harmer
13.206
315816AE2-034 GEN
Solar/Wind Harmer
1.141
3145663CRESWEL
Solar/Wind Harmer
-0.039
971163AH1-040 GEN
Solar/Wind Harmer
13.259
3150281M RUN A
Adder
17.041
3150221REMNGT2
Adder
15.867
3150211REMNGT1
Adder
15.761
972201AH1-685 GEN
Adder
2.737
315737AD1-076 GEN
Solar/Wind Harmer
2.657
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.485
316023GEN1_S
Solar/Wind Harmer
0.937
3145893MURPHYS
Solar/Wind Harmer
-0.055
3145893MURPHYS
Solar/Wind Harmer
0.413
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.86
960081AF2-299 GEN
Solar/Wind Harmer
1.554
970919AG2-571 GEN
Solar/Wind Harmer
4.369
3145683EARLEYS
Solar/Wind Harmer
-0.014
315607AA1-063A GEN
Solar/Wind Harmer
1.389
970937AG2-583 GEN
Solar/Wind Harmer
9.91
316087AB2-174 GEN
Solar/Wind Harmer
1.96
3146263WOODLND
Solar/Wind Harmer
-0.014
970087AG2-069 GEN
Solar/Wind Harmer
12.875
3145963POPLR C
Solar/Wind Harmer
-0.014
3147043LAWRENC
Adder
1.103
3145823KELFORD
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
42.731
3145783HORNRTN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.808
3145796HORNRTN
Solar/Wind Harmer
-0.045
3145796HORNRTN
Solar/Wind Harmer
-0.014
970685AG2-442 GEN
Solar/Wind Harmer
11.866
316034AC1-036 C
Solar/Wind Harmer
0.251
3146926FARMVIL
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.005
971563AH1-280 GEN
Solar/Wind Harmer
1.684
3144293JTRSVLE
Adder
0.286
3144293JTRSVLE
Adder
0.226
972277AH1-723 GEN
Adder
71.392
208835TUHI V3-051
Solar/Wind Helper
0.029
232426Y1-080 FULL
Solar/Wind Helper
0.048
233918AB1-142 GEN
Solar/Wind Helper
0.621
233996TM1833_GEN
Solar/Wind Helper
0.254
233998TM1NIN_3.36
Solar/Wind Helper
0.254
232404W1-003 C
Solar/Wind Helper
0.628
232408W1-005 C
Solar/Wind Helper
0.628
233944AB2-135 GEN
Solar/Wind Helper
0.729
228729W2-030 C
Solar/Wind Helper
0.131
219766PARADISE C
Solar/Wind Helper
0.064
219686LUMSOLAR_N C
Solar/Wind Helper
0.047
219907AC1-030 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.134
20716028EGP_W2-019
Solar/Wind Helper
0.022
20715828PEM_W1-120
Solar/Wind Helper
0.111
963711AG1-223 GEN
Solar/Wind Helper
0.073
219276PARKLANDSO C
Solar/Wind Helper
0.103
20714528FRN_Y2-051
Solar/Wind Helper
0.065
219680HOPEWELLV C1
Solar/Wind Helper
0.004
20715228NPK_W1-113
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.032
218524CNTRALGAS1 C
Solar/Wind Helper
0.181
218440SUMMTASSOC C
Solar/Wind Helper
0.019
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.083
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673628F1S_V4-069
Solar/Wind Helper
0.033
20671828STAW2-080
Solar/Wind Helper
0.03
217209CENTRL HS C
Solar/Wind Helper
0.009
217208PARK ELE C
Solar/Wind Helper
0.005
20676728BRNX1-095
Solar/Wind Helper
0.033
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
20676328BVR_Y1-020
Solar/Wind Helper
0.03
20674628WNG_W3-110
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.101
20674928WA_W3-044
Solar/Wind Helper
0.108
20675828AU_W4-064
Solar/Wind Helper
0.032
207484AF2-139 C O1
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.089
207518AF1-320_GEN
Solar/Wind Helper
1.711
205932AD2-116_GEN
Solar/Wind Helper
0.518
211065PSPA IPP
Solar/Wind Helper
0.161
961301AF2-421 GEN
Solar/Wind Helper
0.453
963151AG1-164 GEN
Solar/Wind Helper
0.453
3150091POSSM6B
50/50
1.477
3150071POSSM 5
50/50
90.91
3150181POSSMC2
50/50
2.006
3150181POSSMC2
50/50
1.989
3150181POSSMC2
50/50
1.989
957191AF2-013 GEN
50/50
14.153
3150391LDYSMT3
50/50
21.375
972195AH1-682 GEN
50/50
2.809
3150341NORNECKC1
50/50
1.591
3150341NORNECKC1
50/50
1.578
315673AE1-157 GEN
Solar/Wind Harmer
12.483
972189AH1-679 GEN
Adder
2.388
316487AF1-042 GEN
Solar/Wind Harmer
2.094
966871AG1-558 GEN
Solar/Wind Harmer
0.476
966871AG1-558 GEN
Solar/Wind Harmer
0.163
3142296MT RD221
Adder
0.444
316312AB1-027
Solar/Wind Harmer
0.524
316156AD2-030 GEN
Solar/Wind Harmer
0.414
315666AE1-190 GEN
Solar/Wind Harmer
0.468
316441AF1-014 GEN
Solar/Wind Harmer
1.048
3150691DARBY 3
Adder
9.905
3150701DARBY 4
Adder
9.882
3150681DARBY 2
Adder
9.87
3150671DARBY 1
Adder
9.859
3142366NRTHEST
Adder
0.45
315976AC1-164 GENA
Solar/Wind Harmer
3.507
316169AC1-164_GENC
Solar/Wind Harmer
3.031
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
64.126
3143526WINTERP
Solar/Wind Harmer
-0.078
316045AC1-158 PL2
Solar/Wind Harmer
4.73
316450AC1-158 RIC
Solar/Wind Harmer
0.394
316240AF1-291 C
Solar/Wind Harmer
0.454
316033AB2-134 GEN
Solar/Wind Harmer
4.819
971223AH1-071 GEN
Solar/Wind Harmer
1.871
316294AC1-161 GEN
Solar/Wind Harmer
4.776
316083AB2-161 GEN
Solar/Wind Harmer
2.397
3150991CHESPKB
Adder
1.373
3150991CHESPKB
Adder
1.34
316185AD1-033 GEN
Solar/Wind Harmer
1.548
3145506HICKORY
Solar/Wind Harmer
-0.058
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316349AD2-085 GEN
Solar/Wind Harmer
1.303
316339AD2-160 GEN
Solar/Wind Harmer
0.986
316388AE2-253 GEN
Solar/Wind Harmer
0.986
3137176SLIGO L2192
Solar/Wind Harmer
-0.058
3146456SLIGO L269
Solar/Wind Harmer
1.73
3130086AYDLETT
Solar/Wind Harmer
-0.058
315835AF2-110_GEN
Solar/Wind Harmer
1.826
3146386ELIZ CT
Solar/Wind Harmer
-0.015
316431W1029_GEN1
Solar/Wind Harmer
2.626
316433W1029_GEN2
Solar/Wind Harmer
2.626
316435W1029_GEN3
Solar/Wind Harmer
2.626
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3144356SAPONY
Solar/Wind Harmer
0.503
316315AB2-025 C
Solar/Wind Harmer
0.388
316313AB2-026
Solar/Wind Harmer
0.386
315742AE1-103 GEN
Solar/Wind Harmer
3.404
3146376EDENTON
Solar/Wind Harmer
0.424
3146376EDENTON
Solar/Wind Harmer
0.424
966001AG1-469 GEN
Solar/Wind Harmer
0.269
3151731LOISA B
Adder
8.232
316006AB2-029 C
Solar/Wind Harmer
0.814
316336AC2-165 C
Solar/Wind Harmer
8.865
315614AA2-178 GEN
Solar/Wind Harmer
1.522
972185AH1-677 GEN
Adder
7.036
972187AH1-678 GEN
Adder
3.554
970933AG2-581 GEN
Solar/Wind Harmer
13.099
316065AD1-022 GEN
Solar/Wind Harmer
6.982
316365GEN2_N
Solar/Wind Harmer
0.937
3145893MURPHYS
Solar/Wind Harmer
0.389
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316140AB2-099
Solar/Wind Harmer
0.093
313506AB2-031 GEN
Solar/Wind Harmer
1.101
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
962571AG1-106 GEN
Solar/Wind Harmer
1.967
970099AG2-077 GEN
Solar/Wind Harmer
17.092
3145593CAROLNA
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
0.113
3145783HORNRTN
Solar/Wind Harmer
1.616
3145783HORNRTN
Solar/Wind Harmer
1.293
3145783HORNRTN
Solar/Wind Harmer
0.404
3145783HORNRTN
Solar/Wind Harmer
0.162
3145796HORNRTN
Solar/Wind Harmer
-0.041
970301AG2-198 GEN
Solar/Wind Harmer
6.78
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
3146776BUCKING
Solar/Wind Harmer
-0.054
3146776BUCKING
Solar/Wind Harmer
-0.004
958211AF2-115 GEN
Solar/Wind Harmer
2.105
3144293JTRSVLE
Adder
0.286
972193AH1-681 GEN
Adder
2.737
970323AG2-213 GEN
Solar/Wind Harmer
6.721
223401AF1-299 GEN
Solar/Wind Helper
0.64
223402AF1-300 C
Solar/Wind Helper
0.64
232424Y1-079 C
Solar/Wind Helper
0.144
233946AB2-136 GEN
Solar/Wind Helper
0.704
234036AF2-325 C
Solar/Wind Helper
0.052
232436AB1-176 C
Solar/Wind Helper
0.055
233930AB2-032 GEN
Solar/Wind Helper
0.471
233994AC2-023 GEN
Solar/Wind Helper
1.189
232428Y3-058 C
Solar/Wind Helper
0.418
233982AB2-133 GEN
Solar/Wind Helper
0.444
232410W1-006 C
Solar/Wind Helper
0.628
234015AF2-250 C
Solar/Wind Helper
0.047
233952AC2-187 GEN
Solar/Wind Helper
0.287
233954AC2-188 GEN
Solar/Wind Helper
0.287
230511AF1-262
Solar/Wind Helper
0.017
230433AD2-135 GEN
Solar/Wind Helper
0.02
228754AB1-001 C
Solar/Wind Helper
0.031
219904AC1-010 C
Solar/Wind Helper
0.071
219912AD2-042 GEN
Solar/Wind Helper
0.177
219272CLEANLIGHT C
Solar/Wind Helper
0.03
219906AC1-017 C
Solar/Wind Helper
0.049
219607WPEMNERT C
Solar/Wind Helper
0.094
219304NAMERICA C
Solar/Wind Helper
0.153
214067T20SOLAR
Solar/Wind Helper
0.013
20720828JCB_W4-025
Solar/Wind Helper
0.073
207459AE1-142 C O1
Solar/Wind Helper
0.335
20714828MDF_W3-079
Solar/Wind Helper
0.15
20742028HF_AC1-207
Solar/Wind Helper
0.161
218438BLK ROCK C
Solar/Wind Helper
0.031
20675428EAM_W2-061
Solar/Wind Helper
0.018
217081WEATEXAS C
Solar/Wind Helper
0.014
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.025
207471AF2-354 C
Solar/Wind Helper
0.184
20674828DL_W4-046
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.055
LAGNLTFEXP_LAGN->PJM
CLTF
11.594
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.227
TVALTFEXP_TVA->PJM
CLTF
5.861
CPLELTFEXP_CPLE->PJM
CLTF
8.755
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.842
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.22
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.364
MECLTFEXP_MEC->PJM
CLTF
8.244
SIGELTFEXP_SIGE->PJM
CLTF
0.26
NYPJM->LTFIMP_NY
CLTF
4.847
LGEELTFEXP_LGEE->PJM
CLTF
3.372
WECLTFEXP_WEC->PJM
CLTF
1.787
AG2-052LTFEXP_AG2-052->PJM
LTF
0.106
AH1-155LTFEXP_AH1-155->PJM
LTF
0.159

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.5 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1138.82
MW Contribution:
5.64
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:190.98 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1033.21
MW Contribution:
5.71
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
45.568
3144293JTRSVLE
50/50
0.813
3151921BEARGRDN G2
50/50
1.052
316283AC2-100 C
Solar/Wind Harmer
9.546
316222AC1-221 GEN
Solar/Wind Harmer
10.167
316003AC1-222 GEN
Solar/Wind Harmer
5.359
316478AD1-087 GEN
Solar/Wind Harmer
4.75
971683AH1-343 GEN
Solar/Wind Harmer
21.5
964241AG1-285 GEN
Solar/Wind Harmer
34.479
959311AF2-222 GEN
Solar/Wind Harmer
46.009
3147133PAMPLIN
Solar/Wind Harmer
-0.124
316123AC1-075 GEN
Solar/Wind Harmer
4.168
970257AG2-171 GEN
Solar/Wind Harmer
14.271
971775AH1-396 GEN
Solar/Wind Harmer
2.685
942461AE2-259 GEN
Solar/Wind Harmer
5.191
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
5.636
316217AC1-145 GEN
Solar/Wind Harmer
1.976
316197AC1-042 GEN
Solar/Wind Harmer
1.498
3147312GRETNA
Solar/Wind Harmer
-0.002
970221AG2-151 GEN
Solar/Wind Harmer
7.146
270494AE1-108_GEN
Solar/Wind Harmer
2.473
966621AG1-532 GEN
Solar/Wind Harmer
0.182
315821AE2-092 GEN
Solar/Wind Harmer
1.75
316181AB2-040 GEN
Solar/Wind Harmer
1.138
3151531CLOVER1
50/50
10.463
3144293JTRSVLE
50/50
0.813
3144293JTRSVLE
50/50
0.642
3151591KERR 2
50/50
0.544
3151641KERR 7
50/50
0.544
3147043LAWRENC
50/50
1.581
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.359
3151911BEARGRDN G1
50/50
1.052
957481AF2-042 GEN
Solar/Wind Harmer
162.806
970401AG2-262 GEN
Solar/Wind Harmer
3.362
315693AD1-088 GEN
Solar/Wind Harmer
23.913
316034AC1-036 C
Solar/Wind Harmer
0.815
970685AG2-442 GEN
Solar/Wind Harmer
37.509
316131AB2-060 GEN
Solar/Wind Harmer
4.326
315785AD2-033 C
Solar/Wind Harmer
8.703
971563AH1-280 GEN
Solar/Wind Harmer
4.507
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.684
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.927
3147123OTTER R
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.569
971377AH1-170 GEN
Solar/Wind Harmer
1.429
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.4
960081AF2-299 GEN
Solar/Wind Harmer
1.007
316087AB2-174 GEN
Solar/Wind Harmer
1.198
3145783HORNRTN
Solar/Wind Harmer
-0.006
3152661PLYWOOD A
50/50
1.081
970909AG2-566 GEN
50/50
3.579
3151541CLOVER2
50/50
10.387
3151601KERR 3
50/50
0.544
3151611KERR 4
50/50
0.544
3151621KERR 5
50/50
0.544
3151631KERR 6
50/50
0.544
972205AH1-687 GEN
50/50
5.138
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316486AD2-202 GEN
Solar/Wind Harmer
1.391
971967AH1-528 GEN
Solar/Wind Harmer
96.346
970683AG2-441 GEN
Solar/Wind Harmer
31.117
970681AG2-440 GEN
Solar/Wind Harmer
20.653
316238AB2-078_GEN
Solar/Wind Harmer
1.216
316239AB2-077_GEN
Solar/Wind Harmer
1.216
3144303KENBRDG
Solar/Wind Harmer
-0.03
946301AF1-294 GEN
Solar/Wind Harmer
9.24
961791AG1-021 GEN
Solar/Wind Harmer
4.507
971845AH1-439 GEN
Solar/Wind Harmer
12.217
316322AB2-045
Solar/Wind Harmer
0.749
970831AG2-522 GEN
Solar/Wind Harmer
10.166
946281AF1-292 GEN
Solar/Wind Harmer
0.201
3137643SOCKMAN
Solar/Wind Harmer
-0.031
270455AD2-022 GEN
Solar/Wind Helper
1.388
270457AD2-023 GEN
Solar/Wind Helper
0.915
3144293JTRSVLE
50/50
0.813
970535AG2-341 GEN
50/50
5.511
3151581KERR 1
50/50
0.194
315687AD1-152 GEN
Solar/Wind Harmer
7.568
316248AF1-058 C
Solar/Wind Harmer
1.79
316118AC1-105 GEN
Solar/Wind Harmer
3.813
970099AG2-077 GEN
Solar/Wind Harmer
65.122
3146843MT LREL
Solar/Wind Harmer
-0.051
3146843MT LREL
Solar/Wind Harmer
-0.051
964791AG1-342 GEN
Solar/Wind Harmer
11.003
970933AG2-581 GEN
Solar/Wind Harmer
48.045
962561AG1-105 GEN
Solar/Wind Harmer
28.018
316237AB2-079_GEN
Solar/Wind Harmer
1.216
313527AB2-043 GEN
Solar/Wind Harmer
6.552
3147133PAMPLIN
Solar/Wind Harmer
-0.04
3147133PAMPLIN
Solar/Wind Harmer
-0.032
970323AG2-213 GEN
Solar/Wind Harmer
19.028
970301AG2-198 GEN
Solar/Wind Harmer
18.849
958211AF2-115 GEN
Solar/Wind Harmer
5.634
942751AE2-291 GEN
Solar/Wind Harmer
21.345
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
942671AE2-283 GEN
Solar/Wind Harmer
4.036
313506AB2-031 GEN
Solar/Wind Harmer
0.655
316336AC2-165 C
Solar/Wind Harmer
4.63
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.061
3145783HORNRTN
Solar/Wind Harmer
0.766
3145783HORNRTN
Solar/Wind Harmer
0.613
3145783HORNRTN
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
0.077
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.755
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.383
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.801
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.554
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.383

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.16 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1136.95
MW Contribution:
5.64
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.66 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1004.43
MW Contribution:
5.72
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.367
3151601KERR 3
50/50
0.543
3151611KERR 4
50/50
0.543
3151621KERR 5
50/50
0.543
3151631KERR 6
50/50
0.543
972205AH1-687 GEN
50/50
5.147
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316486AD2-202 GEN
Solar/Wind Harmer
1.388
971967AH1-528 GEN
Solar/Wind Harmer
96.16
970683AG2-441 GEN
Solar/Wind Harmer
31.058
970681AG2-440 GEN
Solar/Wind Harmer
20.614
316238AB2-078_GEN
Solar/Wind Harmer
1.213
316239AB2-077_GEN
Solar/Wind Harmer
1.213
3144303KENBRDG
Solar/Wind Harmer
-0.03
946301AF1-294 GEN
Solar/Wind Harmer
9.224
961791AG1-021 GEN
Solar/Wind Harmer
4.499
971845AH1-439 GEN
Solar/Wind Harmer
12.211
316322AB2-045
Solar/Wind Harmer
0.749
970831AG2-522 GEN
Solar/Wind Harmer
10.132
946281AF1-292 GEN
Solar/Wind Harmer
0.2
3137643SOCKMAN
Solar/Wind Harmer
-0.031
316258AE1-075 C
Solar/Wind Harmer
0.154
316405AF2-144 C
Solar/Wind Harmer
0.162
270455AD2-022 GEN
Solar/Wind Helper
1.407
270457AD2-023 GEN
Solar/Wind Helper
0.927
970413AG2-270 GEN
50/50
45.479
3144293JTRSVLE
50/50
0.812
3151921BEARGRDN G2
50/50
1.053
316283AC2-100 C
Solar/Wind Harmer
9.527
316222AC1-221 GEN
Solar/Wind Harmer
10.147
316478AD1-087 GEN
Solar/Wind Harmer
4.741
316003AC1-222 GEN
Solar/Wind Harmer
5.348
971683AH1-343 GEN
Solar/Wind Harmer
21.455
964241AG1-285 GEN
Solar/Wind Harmer
34.41
959311AF2-222 GEN
Solar/Wind Harmer
45.921
3147133PAMPLIN
Solar/Wind Harmer
-0.124
316123AC1-075 GEN
Solar/Wind Harmer
4.158
970257AG2-171 GEN
Solar/Wind Harmer
14.243
971775AH1-396 GEN
Solar/Wind Harmer
2.68
942461AE2-259 GEN
Solar/Wind Harmer
5.184
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
5.643
316217AC1-145 GEN
Solar/Wind Harmer
1.969
316197AC1-042 GEN
Solar/Wind Harmer
1.492
3147312GRETNA
Solar/Wind Harmer
-0.002
970221AG2-151 GEN
Solar/Wind Harmer
7.16
270494AE1-108_GEN
Solar/Wind Harmer
2.477
966621AG1-532 GEN
Solar/Wind Harmer
0.182
315821AE2-092 GEN
Solar/Wind Harmer
1.756
316181AB2-040 GEN
Solar/Wind Harmer
1.136
3143336POWHATN
Solar/Wind Harmer
0.641
3151531CLOVER1
50/50
10.443
3144293JTRSVLE
50/50
0.812
3144293JTRSVLE
50/50
0.641
3151591KERR 2
50/50
0.543
3151641KERR 7
50/50
0.543
3147043LAWRENC
50/50
1.579
3151561HALLBR1
50/50
0.344
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.053
957481AF2-042 GEN
Solar/Wind Harmer
162.491
970401AG2-262 GEN
Solar/Wind Harmer
3.355
315693AD1-088 GEN
Solar/Wind Harmer
23.868
316034AC1-036 C
Solar/Wind Harmer
0.814
970685AG2-442 GEN
Solar/Wind Harmer
37.44
316131AB2-060 GEN
Solar/Wind Harmer
4.316
315785AD2-033 C
Solar/Wind Harmer
8.686
971563AH1-280 GEN
Solar/Wind Harmer
4.499
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.646
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.921
3147123OTTER R
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.552
971377AH1-170 GEN
Solar/Wind Harmer
1.432
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.427
960081AF2-299 GEN
Solar/Wind Harmer
1.007
316087AB2-174 GEN
Solar/Wind Harmer
1.196
3145783HORNRTN
Solar/Wind Harmer
-0.006
3143336POWHATN
Solar/Wind Harmer
0.755
270018AE2-047 C O1
Solar/Wind Helper
0.399
3152661PLYWOOD A
50/50
1.079
970909AG2-566 GEN
50/50
3.573
3144293JTRSVLE
50/50
0.812
970535AG2-341 GEN
50/50
5.496
3151581KERR 1
50/50
0.194
315687AD1-152 GEN
Solar/Wind Harmer
7.553
316248AF1-058 C
Solar/Wind Harmer
1.787
316118AC1-105 GEN
Solar/Wind Harmer
3.805
970099AG2-077 GEN
Solar/Wind Harmer
64.997
3146843MT LREL
Solar/Wind Harmer
-0.051
3146843MT LREL
Solar/Wind Harmer
-0.051
964791AG1-342 GEN
Solar/Wind Harmer
10.98
970933AG2-581 GEN
Solar/Wind Harmer
47.952
962561AG1-105 GEN
Solar/Wind Harmer
27.96
316237AB2-079_GEN
Solar/Wind Harmer
1.213
313527AB2-043 GEN
Solar/Wind Harmer
6.538
3147133PAMPLIN
Solar/Wind Harmer
-0.039
3147133PAMPLIN
Solar/Wind Harmer
-0.032
970323AG2-213 GEN
Solar/Wind Harmer
18.991
970301AG2-198 GEN
Solar/Wind Harmer
18.819
958211AF2-115 GEN
Solar/Wind Harmer
5.624
942751AE2-291 GEN
Solar/Wind Harmer
21.295
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
942671AE2-283 GEN
Solar/Wind Harmer
4.021
313506AB2-031 GEN
Solar/Wind Harmer
0.654
316336AC2-165 C
Solar/Wind Harmer
4.666
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.06
3145783HORNRTN
Solar/Wind Harmer
0.762
3145783HORNRTN
Solar/Wind Harmer
0.61
3145783HORNRTN
Solar/Wind Harmer
0.19
3145783HORNRTN
Solar/Wind Harmer
0.076
316313AB2-026
Solar/Wind Harmer
0.171
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.765
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.418
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.081
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.195
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.846
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.637
NYPJM->LTFIMP_NY
CLTF
0.029
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.482

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.16 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1136.95
MW Contribution:
5.64
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.72 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1004.72
MW Contribution:
5.72
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.367
3151601KERR 3
50/50
0.543
3151611KERR 4
50/50
0.543
3151621KERR 5
50/50
0.543
3151631KERR 6
50/50
0.543
972205AH1-687 GEN
50/50
5.147
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316486AD2-202 GEN
Solar/Wind Harmer
1.388
971967AH1-528 GEN
Solar/Wind Harmer
96.16
970683AG2-441 GEN
Solar/Wind Harmer
31.058
970681AG2-440 GEN
Solar/Wind Harmer
20.614
316238AB2-078_GEN
Solar/Wind Harmer
1.213
316239AB2-077_GEN
Solar/Wind Harmer
1.213
3144303KENBRDG
Solar/Wind Harmer
-0.03
946301AF1-294 GEN
Solar/Wind Harmer
9.224
961791AG1-021 GEN
Solar/Wind Harmer
4.499
971845AH1-439 GEN
Solar/Wind Harmer
12.211
316322AB2-045
Solar/Wind Harmer
0.749
970831AG2-522 GEN
Solar/Wind Harmer
10.132
946281AF1-292 GEN
Solar/Wind Harmer
0.2
3137643SOCKMAN
Solar/Wind Harmer
-0.031
316258AE1-075 C
Solar/Wind Harmer
0.154
316405AF2-144 C
Solar/Wind Harmer
0.162
270455AD2-022 GEN
Solar/Wind Helper
1.407
270457AD2-023 GEN
Solar/Wind Helper
0.927
3151531CLOVER1
50/50
10.443
3144293JTRSVLE
50/50
0.812
3144293JTRSVLE
50/50
0.641
3151591KERR 2
50/50
0.543
3151641KERR 7
50/50
0.543
3147043LAWRENC
50/50
1.579
3151561HALLBR1
50/50
0.344
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.053
957481AF2-042 GEN
Solar/Wind Harmer
162.491
970401AG2-262 GEN
Solar/Wind Harmer
3.355
315693AD1-088 GEN
Solar/Wind Harmer
23.868
316034AC1-036 C
Solar/Wind Harmer
0.814
970685AG2-442 GEN
Solar/Wind Harmer
37.44
316131AB2-060 GEN
Solar/Wind Harmer
4.316
315785AD2-033 C
Solar/Wind Harmer
8.686
971563AH1-280 GEN
Solar/Wind Harmer
4.499
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.646
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.921
3147123OTTER R
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.552
971377AH1-170 GEN
Solar/Wind Harmer
1.432
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.427
960081AF2-299 GEN
Solar/Wind Harmer
1.007
316087AB2-174 GEN
Solar/Wind Harmer
1.196
3145783HORNRTN
Solar/Wind Harmer
-0.006
3143336POWHATN
Solar/Wind Harmer
0.755
270018AE2-047 C O1
Solar/Wind Helper
0.399
970413AG2-270 GEN
50/50
45.479
3144293JTRSVLE
50/50
0.812
3151921BEARGRDN G2
50/50
1.053
316283AC2-100 C
Solar/Wind Harmer
9.527
316222AC1-221 GEN
Solar/Wind Harmer
10.147
316478AD1-087 GEN
Solar/Wind Harmer
4.741
316003AC1-222 GEN
Solar/Wind Harmer
5.348
971683AH1-343 GEN
Solar/Wind Harmer
21.455
964241AG1-285 GEN
Solar/Wind Harmer
34.41
959311AF2-222 GEN
Solar/Wind Harmer
45.921
3147133PAMPLIN
Solar/Wind Harmer
-0.124
316123AC1-075 GEN
Solar/Wind Harmer
4.158
970257AG2-171 GEN
Solar/Wind Harmer
14.243
971775AH1-396 GEN
Solar/Wind Harmer
2.68
942461AE2-259 GEN
Solar/Wind Harmer
5.184
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
5.643
316217AC1-145 GEN
Solar/Wind Harmer
1.969
316197AC1-042 GEN
Solar/Wind Harmer
1.492
3147312GRETNA
Solar/Wind Harmer
-0.002
970221AG2-151 GEN
Solar/Wind Harmer
7.16
270494AE1-108_GEN
Solar/Wind Harmer
2.477
966621AG1-532 GEN
Solar/Wind Harmer
0.182
315821AE2-092 GEN
Solar/Wind Harmer
1.756
316181AB2-040 GEN
Solar/Wind Harmer
1.136
3143336POWHATN
Solar/Wind Harmer
0.641
3152661PLYWOOD A
50/50
1.079
970909AG2-566 GEN
50/50
3.573
3144293JTRSVLE
50/50
0.812
970535AG2-341 GEN
50/50
5.496
3151581KERR 1
50/50
0.194
315687AD1-152 GEN
Solar/Wind Harmer
7.553
316248AF1-058 C
Solar/Wind Harmer
1.787
316118AC1-105 GEN
Solar/Wind Harmer
3.805
970099AG2-077 GEN
Solar/Wind Harmer
64.997
3146843MT LREL
Solar/Wind Harmer
-0.051
3146843MT LREL
Solar/Wind Harmer
-0.051
964791AG1-342 GEN
Solar/Wind Harmer
10.98
970933AG2-581 GEN
Solar/Wind Harmer
47.952
962561AG1-105 GEN
Solar/Wind Harmer
27.96
316237AB2-079_GEN
Solar/Wind Harmer
1.213
313527AB2-043 GEN
Solar/Wind Harmer
6.538
3147133PAMPLIN
Solar/Wind Harmer
-0.039
3147133PAMPLIN
Solar/Wind Harmer
-0.032
970323AG2-213 GEN
Solar/Wind Harmer
18.991
970301AG2-198 GEN
Solar/Wind Harmer
18.819
958211AF2-115 GEN
Solar/Wind Harmer
5.624
942751AE2-291 GEN
Solar/Wind Harmer
21.295
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
942671AE2-283 GEN
Solar/Wind Harmer
4.021
313506AB2-031 GEN
Solar/Wind Harmer
0.654
316336AC2-165 C
Solar/Wind Harmer
4.666
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.06
3145783HORNRTN
Solar/Wind Harmer
0.762
3145783HORNRTN
Solar/Wind Harmer
0.61
3145783HORNRTN
Solar/Wind Harmer
0.19
3145783HORNRTN
Solar/Wind Harmer
0.076
316313AB2-026
Solar/Wind Harmer
0.171
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.765
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.418
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.081
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.195
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.846
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.637
NYPJM->LTFIMP_NY
CLTF
0.029
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.482

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.89 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1092.2
MW Contribution:
5.56
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.83 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:989.14
MW Contribution:
5.63
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.515
3151601KERR 3
50/50
0.542
3151611KERR 4
50/50
0.542
3151621KERR 5
50/50
0.542
3151631KERR 6
50/50
0.542
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316486AD2-202 GEN
Solar/Wind Harmer
1.408
970683AG2-441 GEN
Solar/Wind Harmer
30.696
970681AG2-440 GEN
Solar/Wind Harmer
20.373
316238AB2-078_GEN
Solar/Wind Harmer
1.208
316239AB2-077_GEN
Solar/Wind Harmer
1.208
3144303KENBRDG
Solar/Wind Harmer
-0.03
946301AF1-294 GEN
Solar/Wind Harmer
9.146
961791AG1-021 GEN
Solar/Wind Harmer
4.462
971845AH1-439 GEN
Solar/Wind Harmer
12.045
316322AB2-045
Solar/Wind Harmer
0.739
970831AG2-522 GEN
Solar/Wind Harmer
10.124
972205AH1-687 GEN
Adder
4.774
946281AF1-292 GEN
Solar/Wind Harmer
0.199
3137643SOCKMAN
Solar/Wind Harmer
-0.03
270455AD2-022 GEN
Solar/Wind Helper
1.378
270457AD2-023 GEN
Solar/Wind Helper
0.908
3151531CLOVER1
50/50
10.593
3144293JTRSVLE
50/50
0.805
3144293JTRSVLE
50/50
0.635
3151591KERR 2
50/50
0.542
3151641KERR 7
50/50
0.542
3147043LAWRENC
50/50
1.571
3151561HALLBR1
50/50
0.347
957481AF2-042 GEN
Solar/Wind Harmer
166.61
970401AG2-262 GEN
Solar/Wind Harmer
3.363
315693AD1-088 GEN
Solar/Wind Harmer
23.555
316034AC1-036 C
Solar/Wind Harmer
0.805
970685AG2-442 GEN
Solar/Wind Harmer
37.002
316131AB2-060 GEN
Solar/Wind Harmer
4.296
315785AD2-033 C
Solar/Wind Harmer
8.632
971563AH1-280 GEN
Solar/Wind Harmer
4.462
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.637
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.92
3147123OTTER R
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.591
971377AH1-170 GEN
Solar/Wind Harmer
1.409
3147623JAMES R
Solar/Wind Harmer
0.174
970937AG2-583 GEN
Solar/Wind Harmer
7.294
960081AF2-299 GEN
Solar/Wind Harmer
1.001
316087AB2-174 GEN
Solar/Wind Harmer
1.191
3145783HORNRTN
Solar/Wind Harmer
-0.006
970413AG2-270 GEN
50/50
46.132
3144293JTRSVLE
50/50
0.805
316283AC2-100 C
Solar/Wind Harmer
9.562
316222AC1-221 GEN
Solar/Wind Harmer
10.185
316478AD1-087 GEN
Solar/Wind Harmer
4.808
316003AC1-222 GEN
Solar/Wind Harmer
5.38
971683AH1-343 GEN
Solar/Wind Harmer
21.585
964241AG1-285 GEN
Solar/Wind Harmer
34.076
959311AF2-222 GEN
Solar/Wind Harmer
45.411
3147133PAMPLIN
Solar/Wind Harmer
-0.122
316123AC1-075 GEN
Solar/Wind Harmer
4.185
970257AG2-171 GEN
Solar/Wind Harmer
14.15
971775AH1-396 GEN
Solar/Wind Harmer
2.662
942461AE2-259 GEN
Solar/Wind Harmer
5.123
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
5.556
316217AC1-145 GEN
Solar/Wind Harmer
1.986
316197AC1-042 GEN
Solar/Wind Harmer
1.505
3147312GRETNA
Solar/Wind Harmer
-0.002
970221AG2-151 GEN
Solar/Wind Harmer
7.046
270494AE1-108_GEN
Solar/Wind Harmer
2.442
966621AG1-532 GEN
Solar/Wind Harmer
0.181
315821AE2-092 GEN
Solar/Wind Harmer
1.725
316181AB2-040 GEN
Solar/Wind Harmer
1.132
3152661PLYWOOD A
50/50
1.084
970909AG2-566 GEN
50/50
3.527
3144293JTRSVLE
50/50
0.805
970535AG2-341 GEN
50/50
5.48
3151581KERR 1
50/50
0.194
315687AD1-152 GEN
Solar/Wind Harmer
7.632
316248AF1-058 C
Solar/Wind Harmer
1.797
316118AC1-105 GEN
Solar/Wind Harmer
3.822
970099AG2-077 GEN
Solar/Wind Harmer
66.644
3146843MT LREL
Solar/Wind Harmer
-0.051
3146843MT LREL
Solar/Wind Harmer
-0.051
964791AG1-342 GEN
Solar/Wind Harmer
11.008
962561AG1-105 GEN
Solar/Wind Harmer
28.005
316237AB2-079_GEN
Solar/Wind Harmer
1.208
313527AB2-043 GEN
Solar/Wind Harmer
6.508
3147133PAMPLIN
Solar/Wind Harmer
-0.039
3147133PAMPLIN
Solar/Wind Harmer
-0.031
970323AG2-213 GEN
Solar/Wind Harmer
18.867
970301AG2-198 GEN
Solar/Wind Harmer
18.574
958211AF2-115 GEN
Solar/Wind Harmer
5.577
942751AE2-291 GEN
Solar/Wind Harmer
21.432
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
942671AE2-283 GEN
Solar/Wind Harmer
4.056
313506AB2-031 GEN
Solar/Wind Harmer
0.652
316336AC2-165 C
Solar/Wind Harmer
4.562
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.06
3145783HORNRTN
Solar/Wind Harmer
0.763
3145783HORNRTN
Solar/Wind Harmer
0.61
3145783HORNRTN
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
0.076
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.751
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.371
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.53
NYPJM->LTFIMP_NY
CLTF
0.045
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.359

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.87 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1092.14
MW Contribution:
5.56
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.515
3151601KERR 3
50/50
0.542
3151611KERR 4
50/50
0.542
3151621KERR 5
50/50
0.542
3151631KERR 6
50/50
0.542
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316486AD2-202 GEN
Solar/Wind Harmer
1.408
970683AG2-441 GEN
Solar/Wind Harmer
30.699
970681AG2-440 GEN
Solar/Wind Harmer
20.375
316238AB2-078_GEN
Solar/Wind Harmer
1.208
316239AB2-077_GEN
Solar/Wind Harmer
1.208
3144303KENBRDG
Solar/Wind Harmer
-0.03
946301AF1-294 GEN
Solar/Wind Harmer
9.147
961791AG1-021 GEN
Solar/Wind Harmer
4.462
971845AH1-439 GEN
Solar/Wind Harmer
12.046
316322AB2-045
Solar/Wind Harmer
0.739
970831AG2-522 GEN
Solar/Wind Harmer
10.125
972205AH1-687 GEN
Adder
4.774
946281AF1-292 GEN
Solar/Wind Harmer
0.199
3137643SOCKMAN
Solar/Wind Harmer
-0.03
270455AD2-022 GEN
Solar/Wind Helper
1.378
270457AD2-023 GEN
Solar/Wind Helper
0.908
3151531CLOVER1
50/50
10.592
3144293JTRSVLE
50/50
0.805
3144293JTRSVLE
50/50
0.635
3151591KERR 2
50/50
0.542
3151641KERR 7
50/50
0.542
3147043LAWRENC
50/50
1.571
3151561HALLBR1
50/50
0.347
957481AF2-042 GEN
Solar/Wind Harmer
166.581
970401AG2-262 GEN
Solar/Wind Harmer
3.363
315693AD1-088 GEN
Solar/Wind Harmer
23.558
316034AC1-036 C
Solar/Wind Harmer
0.805
970685AG2-442 GEN
Solar/Wind Harmer
37.006
316131AB2-060 GEN
Solar/Wind Harmer
4.296
315785AD2-033 C
Solar/Wind Harmer
8.633
971563AH1-280 GEN
Solar/Wind Harmer
4.462
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.637
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.92
3147123OTTER R
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.591
971377AH1-170 GEN
Solar/Wind Harmer
1.409
3147623JAMES R
Solar/Wind Harmer
0.174
970937AG2-583 GEN
Solar/Wind Harmer
7.295
960081AF2-299 GEN
Solar/Wind Harmer
1.001
316087AB2-174 GEN
Solar/Wind Harmer
1.191
970413AG2-270 GEN
50/50
46.128
3144293JTRSVLE
50/50
0.805
316283AC2-100 C
Solar/Wind Harmer
9.562
316222AC1-221 GEN
Solar/Wind Harmer
10.185
316478AD1-087 GEN
Solar/Wind Harmer
4.808
316003AC1-222 GEN
Solar/Wind Harmer
5.38
971683AH1-343 GEN
Solar/Wind Harmer
21.585
964241AG1-285 GEN
Solar/Wind Harmer
34.079
959311AF2-222 GEN
Solar/Wind Harmer
45.416
3147133PAMPLIN
Solar/Wind Harmer
-0.122
316123AC1-075 GEN
Solar/Wind Harmer
4.184
970257AG2-171 GEN
Solar/Wind Harmer
14.151
971775AH1-396 GEN
Solar/Wind Harmer
2.663
942461AE2-259 GEN
Solar/Wind Harmer
5.123
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
5.556
316217AC1-145 GEN
Solar/Wind Harmer
1.986
316197AC1-042 GEN
Solar/Wind Harmer
1.505
3147312GRETNA
Solar/Wind Harmer
-0.002
970221AG2-151 GEN
Solar/Wind Harmer
7.047
270494AE1-108_GEN
Solar/Wind Harmer
2.442
966621AG1-532 GEN
Solar/Wind Harmer
0.181
315821AE2-092 GEN
Solar/Wind Harmer
1.726
316181AB2-040 GEN
Solar/Wind Harmer
1.132
3145783HORNRTN
Solar/Wind Harmer
-0.006
3152661PLYWOOD A
50/50
1.084
970909AG2-566 GEN
50/50
3.527
3144293JTRSVLE
50/50
0.805
970535AG2-341 GEN
50/50
5.48
3151581KERR 1
50/50
0.194
315687AD1-152 GEN
Solar/Wind Harmer
7.632
316248AF1-058 C
Solar/Wind Harmer
1.797
316118AC1-105 GEN
Solar/Wind Harmer
3.822
970099AG2-077 GEN
Solar/Wind Harmer
66.633
3146843MT LREL
Solar/Wind Harmer
-0.051
3146843MT LREL
Solar/Wind Harmer
-0.051
964791AG1-342 GEN
Solar/Wind Harmer
11.008
962561AG1-105 GEN
Solar/Wind Harmer
28.005
316237AB2-079_GEN
Solar/Wind Harmer
1.208
313527AB2-043 GEN
Solar/Wind Harmer
6.508
3147133PAMPLIN
Solar/Wind Harmer
-0.039
3147133PAMPLIN
Solar/Wind Harmer
-0.031
970323AG2-213 GEN
Solar/Wind Harmer
18.868
970301AG2-198 GEN
Solar/Wind Harmer
18.576
958211AF2-115 GEN
Solar/Wind Harmer
5.578
942751AE2-291 GEN
Solar/Wind Harmer
21.432
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
942671AE2-283 GEN
Solar/Wind Harmer
4.055
313506AB2-031 GEN
Solar/Wind Harmer
0.652
316336AC2-165 C
Solar/Wind Harmer
4.563
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.06
3145783HORNRTN
Solar/Wind Harmer
0.763
3145783HORNRTN
Solar/Wind Harmer
0.61
3145783HORNRTN
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
0.076
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.751
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.371
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.53
NYPJM->LTFIMP_NY
CLTF
0.045
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.359

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.45 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:876.98
MW Contribution:
4.28
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:153.19 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:779.01
MW Contribution:
4.34
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.387
3151601KERR 3
50/50
0.544
3151611KERR 4
50/50
0.544
3151621KERR 5
50/50
0.544
3151631KERR 6
50/50
0.544
972205AH1-687 GEN
50/50
5.138
3151281ROARAP4
50/50
0.073
3147173SINAI
Solar/Wind Harmer
0.53
3147243WELCO
Solar/Wind Harmer
0.331
316486AD2-202 GEN
Solar/Wind Harmer
0.498
971967AH1-528 GEN
Solar/Wind Harmer
72.98
970683AG2-441 GEN
Solar/Wind Harmer
23.633
970681AG2-440 GEN
Solar/Wind Harmer
15.686
3144303KENBRDG
Solar/Wind Harmer
0.271
946301AF1-294 GEN
Solar/Wind Harmer
6.333
961791AG1-021 GEN
Solar/Wind Harmer
3.081
971845AH1-439 GEN
Solar/Wind Harmer
9.279
970831AG2-522 GEN
Solar/Wind Harmer
7.721
3137643SOCKMAN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Helper
1.388
270457AD2-023 GEN
Solar/Wind Helper
0.915
970413AG2-270 GEN
50/50
45.568
3144293JTRSVLE
50/50
0.813
3151921BEARGRDN G2
50/50
1.052
3151261ROARAP2
50/50
0.08
24728405LEESVG
50/50
0.073
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.765
316222AC1-221 GEN
Solar/Wind Harmer
3.693
316478AD1-087 GEN
Solar/Wind Harmer
1.696
971683AH1-343 GEN
Solar/Wind Harmer
16.329
964241AG1-285 GEN
Solar/Wind Harmer
26.187
959311AF2-222 GEN
Solar/Wind Harmer
34.874
3147133PAMPLIN
Solar/Wind Harmer
1.108
316123AC1-075 GEN
Solar/Wind Harmer
0.46
970257AG2-171 GEN
Solar/Wind Harmer
10.839
971775AH1-396 GEN
Solar/Wind Harmer
0.542
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Harmer
0.161
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.099
972003AH1-546 GEN
Solar/Wind Harmer
4.28
3147312GRETNA
Solar/Wind Harmer
0.022
970221AG2-151 GEN
Solar/Wind Harmer
5.428
270494AE1-108_GEN
Solar/Wind Harmer
1.011
315821AE2-092 GEN
Solar/Wind Harmer
0
316181AB2-040 GEN
Solar/Wind Harmer
0.103
3152661PLYWOOD A
50/50
1.081
970909AG2-566 GEN
50/50
3.579
3144293JTRSVLE
50/50
0.813
970535AG2-341 GEN
50/50
5.511
3151581KERR 1
50/50
0.194
3151261ROARAP2
50/50
0.078
316118AC1-105 GEN
Solar/Wind Harmer
1.267
970099AG2-077 GEN
Solar/Wind Harmer
49.46
3146843MT LREL
Solar/Wind Harmer
0.459
3146843MT LREL
Solar/Wind Harmer
0.459
964791AG1-342 GEN
Solar/Wind Harmer
8.802
970933AG2-581 GEN
Solar/Wind Harmer
36.49
962561AG1-105 GEN
Solar/Wind Harmer
21.279
3147133PAMPLIN
Solar/Wind Harmer
0.353
3147133PAMPLIN
Solar/Wind Harmer
0.282
970323AG2-213 GEN
Solar/Wind Harmer
14.452
970301AG2-198 GEN
Solar/Wind Harmer
14.316
958211AF2-115 GEN
Solar/Wind Harmer
3.851
942751AE2-291 GEN
Solar/Wind Harmer
16.211
3146776BUCKING
Solar/Wind Harmer
0.794
3146776BUCKING
Solar/Wind Harmer
0.064
942671AE2-283 GEN
Solar/Wind Harmer
2.699
313506AB2-031 GEN
Solar/Wind Harmer
0.223
316336AC2-165 C
Solar/Wind Harmer
3.344
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.081
3145783HORNRTN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
0.817
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
3151531CLOVER1
50/50
10.463
3144293JTRSVLE
50/50
0.813
3144293JTRSVLE
50/50
0.642
3151591KERR 2
50/50
0.544
3151641KERR 7
50/50
0.544
3147043LAWRENC
50/50
1.581
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.359
3151911BEARGRDN G1
50/50
1.052
3151281ROARAP4
50/50
0.078
957481AF2-042 GEN
Solar/Wind Harmer
123.65
970401AG2-262 GEN
Solar/Wind Harmer
2.69
315693AD1-088 GEN
Solar/Wind Harmer
20.432
316034AC1-036 C
Solar/Wind Harmer
0.026
970685AG2-442 GEN
Solar/Wind Harmer
28.488
316131AB2-060 GEN
Solar/Wind Harmer
1.113
315785AD2-033 C
Solar/Wind Harmer
2.77
971563AH1-280 GEN
Solar/Wind Harmer
3.423
3146926FARMVIL
Solar/Wind Harmer
0.161
971065AG2-659 GEN
Solar/Wind Harmer
8.874
3146776BUCKING
Solar/Wind Harmer
0.079
316129AC1-054 GEN
Solar/Wind Harmer
0.733
3147123OTTER R
Solar/Wind Harmer
0.088
3147312GRETNA
Solar/Wind Harmer
0.087
3146802CHATHAM
Solar/Wind Harmer
0.081
941801AE2-185 GEN
Solar/Wind Harmer
3.47
971377AH1-170 GEN
Solar/Wind Harmer
1.086
3147623JAMES R
Solar/Wind Harmer
0.236
970937AG2-583 GEN
Solar/Wind Harmer
5.62
960081AF2-299 GEN
Solar/Wind Harmer
0.765
3145783HORNRTN
Solar/Wind Harmer
0.057
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.755
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.383
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.801
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.554
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.383

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:169.26 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:860.77
MW Contribution:
4.28
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:149.86 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:762.12
MW Contribution:
4.34
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.387
3151601KERR 3
50/50
0.544
3151611KERR 4
50/50
0.544
3151621KERR 5
50/50
0.544
3151631KERR 6
50/50
0.544
972205AH1-687 GEN
50/50
5.138
3151281ROARAP4
50/50
0.073
3147173SINAI
Solar/Wind Harmer
0.53
3147243WELCO
Solar/Wind Harmer
0.331
316486AD2-202 GEN
Solar/Wind Harmer
0.498
3152661PLYWOOD A
50/50
1.081
970909AG2-566 GEN
50/50
3.579
3144293JTRSVLE
50/50
0.813
970535AG2-341 GEN
50/50
5.511
3151581KERR 1
50/50
0.194
3151261ROARAP2
50/50
0.078
316118AC1-105 GEN
Solar/Wind Harmer
1.267
970099AG2-077 GEN
Solar/Wind Harmer
49.46
3146843MT LREL
Solar/Wind Harmer
0.459
970413AG2-270 GEN
50/50
45.568
3144293JTRSVLE
50/50
0.813
3151921BEARGRDN G2
50/50
1.052
3151261ROARAP2
50/50
0.08
24728405LEESVG
50/50
0.073
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.765
316222AC1-221 GEN
Solar/Wind Harmer
3.693
316478AD1-087 GEN
Solar/Wind Harmer
1.696
3151531CLOVER1
50/50
10.463
3144293JTRSVLE
50/50
0.813
3144293JTRSVLE
50/50
0.642
3151591KERR 2
50/50
0.544
3151641KERR 7
50/50
0.544
3147043LAWRENC
50/50
1.581
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.359
3151911BEARGRDN G1
50/50
1.052
3151281ROARAP4
50/50
0.078
957481AF2-042 GEN
Solar/Wind Harmer
123.65
970683AG2-441 GEN
Solar/Wind Harmer
23.633
970681AG2-440 GEN
Solar/Wind Harmer
15.686
3144303KENBRDG
Solar/Wind Harmer
0.271
946301AF1-294 GEN
Solar/Wind Harmer
6.333
961791AG1-021 GEN
Solar/Wind Harmer
3.081
971845AH1-439 GEN
Solar/Wind Harmer
9.279
970831AG2-522 GEN
Solar/Wind Harmer
7.721
3137643SOCKMAN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Helper
1.388
270457AD2-023 GEN
Solar/Wind Helper
0.915
971683AH1-343 GEN
Solar/Wind Harmer
16.329
964241AG1-285 GEN
Solar/Wind Harmer
26.187
959311AF2-222 GEN
Solar/Wind Harmer
34.874
3147133PAMPLIN
Solar/Wind Harmer
1.108
316123AC1-075 GEN
Solar/Wind Harmer
0.46
970257AG2-171 GEN
Solar/Wind Harmer
10.839
971775AH1-396 GEN
Solar/Wind Harmer
0.542
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Harmer
0.161
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.099
972003AH1-546 GEN
Solar/Wind Harmer
4.28
3147312GRETNA
Solar/Wind Harmer
0.022
970221AG2-151 GEN
Solar/Wind Harmer
5.428
270494AE1-108_GEN
Solar/Wind Harmer
1.011
315821AE2-092 GEN
Solar/Wind Harmer
0
316181AB2-040 GEN
Solar/Wind Harmer
0.103
970401AG2-262 GEN
Solar/Wind Harmer
2.69
315693AD1-088 GEN
Solar/Wind Harmer
20.432
316034AC1-036 C
Solar/Wind Harmer
0.026
970685AG2-442 GEN
Solar/Wind Harmer
28.488
316131AB2-060 GEN
Solar/Wind Harmer
1.113
315785AD2-033 C
Solar/Wind Harmer
2.77
971563AH1-280 GEN
Solar/Wind Harmer
3.423
3146926FARMVIL
Solar/Wind Harmer
0.161
971065AG2-659 GEN
Solar/Wind Harmer
8.874
3146776BUCKING
Solar/Wind Harmer
0.079
316129AC1-054 GEN
Solar/Wind Harmer
0.733
3147123OTTER R
Solar/Wind Harmer
0.088
3147312GRETNA
Solar/Wind Harmer
0.087
3146802CHATHAM
Solar/Wind Harmer
0.081
941801AE2-185 GEN
Solar/Wind Harmer
3.47
971377AH1-170 GEN
Solar/Wind Harmer
1.086
3147623JAMES R
Solar/Wind Harmer
0.236
970937AG2-583 GEN
Solar/Wind Harmer
5.62
960081AF2-299 GEN
Solar/Wind Harmer
0.765
3145783HORNRTN
Solar/Wind Harmer
0.057
3146843MT LREL
Solar/Wind Harmer
0.459
964791AG1-342 GEN
Solar/Wind Harmer
8.802
962561AG1-105 GEN
Solar/Wind Harmer
21.279
3147133PAMPLIN
Solar/Wind Harmer
0.353
3147133PAMPLIN
Solar/Wind Harmer
0.282
970323AG2-213 GEN
Solar/Wind Harmer
14.452
970301AG2-198 GEN
Solar/Wind Harmer
14.316
958211AF2-115 GEN
Solar/Wind Harmer
3.851
942751AE2-291 GEN
Solar/Wind Harmer
16.211
3146776BUCKING
Solar/Wind Harmer
0.794
3146776BUCKING
Solar/Wind Harmer
0.064
942671AE2-283 GEN
Solar/Wind Harmer
2.699
313506AB2-031 GEN
Solar/Wind Harmer
0.223
316336AC2-165 C
Solar/Wind Harmer
3.344
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.081
3145783HORNRTN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
0.817
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.755
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.383
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.016
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.021
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.801
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.554
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.383

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.47 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:570.59
MW Contribution:
2.67
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
7.657
3151601KERR 3
50/50
0.299
3151611KERR 4
50/50
0.299
3151621KERR 5
50/50
0.299
3151631KERR 6
50/50
0.299
3147173SINAI
Solar/Wind Harmer
-0.049
3147243WELCO
Solar/Wind Harmer
-0.03
316486AD2-202 GEN
Solar/Wind Harmer
1.027
316238AB2-078_GEN
Solar/Wind Harmer
0.71
316239AB2-077_GEN
Solar/Wind Harmer
0.71
970683AG2-441 GEN
Solar/Wind Harmer
14.577
970681AG2-440 GEN
Solar/Wind Harmer
9.675
3144303KENBRDG
Solar/Wind Harmer
-0.016
946301AF1-294 GEN
Solar/Wind Harmer
4.723
961791AG1-021 GEN
Solar/Wind Harmer
2.304
970831AG2-522 GEN
Solar/Wind Harmer
5.558
971845AH1-439 GEN
Solar/Wind Harmer
5.415
316322AB2-045
Solar/Wind Harmer
0.333
270455AD2-022 GEN
Solar/Wind Helper
1.651
270457AD2-023 GEN
Solar/Wind Helper
1.088
3151531CLOVER1
50/50
7.713
3144293JTRSVLE
50/50
0.416
3144293JTRSVLE
50/50
0.328
3151591KERR 2
50/50
0.299
3151641KERR 7
50/50
0.299
957481AF2-042 GEN
Solar/Wind Harmer
126.372
970401AG2-262 GEN
Solar/Wind Harmer
2.493
316131AB2-060 GEN
Solar/Wind Harmer
2.471
316034AC1-036 C
Solar/Wind Harmer
0.392
315785AD2-033 C
Solar/Wind Harmer
4.766
970685AG2-442 GEN
Solar/Wind Harmer
17.526
315693AD1-088 GEN
Solar/Wind Harmer
9.446
971563AH1-280 GEN
Solar/Wind Harmer
2.304
3146926FARMVIL
Solar/Wind Harmer
-0.008
971065AG2-659 GEN
Solar/Wind Harmer
6.4
3147123OTTER R
Solar/Wind Harmer
-0.008
316129AC1-054 GEN
Solar/Wind Harmer
1.055
3147043LAWRENC
Adder
0.872
3146776BUCKING
Solar/Wind Harmer
-0.004
3147312GRETNA
Solar/Wind Harmer
-0.007
3146802CHATHAM
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
3.444
270018AE2-047 C O1
Solar/Wind Helper
0.483
270016AE1-250 BESS
Solar/Wind Helper
0.464
970413AG2-270 GEN
50/50
33.592
3144293JTRSVLE
50/50
0.416
316283AC2-100 C
Solar/Wind Harmer
9.12
316222AC1-221 GEN
Solar/Wind Harmer
9.696
316003AC1-222 GEN
Solar/Wind Harmer
4.406
971683AH1-343 GEN
Solar/Wind Harmer
17.635
316478AD1-087 GEN
Solar/Wind Harmer
3.509
316123AC1-075 GEN
Solar/Wind Harmer
3.393
964241AG1-285 GEN
Solar/Wind Harmer
17.201
959311AF2-222 GEN
Solar/Wind Harmer
21.962
970257AG2-171 GEN
Solar/Wind Harmer
7.732
971775AH1-396 GEN
Solar/Wind Harmer
1.455
3147133PAMPLIN
Solar/Wind Harmer
-0.057
942461AE2-259 GEN
Solar/Wind Harmer
2.37
3146926FARMVIL
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Harmer
-0.004
316217AC1-145 GEN
Solar/Wind Harmer
1.489
316197AC1-042 GEN
Solar/Wind Harmer
1.129
3147312GRETNA
Solar/Wind Harmer
-0.002
972003AH1-546 GEN
Solar/Wind Harmer
2.666
943811AF1-049 GEN
Solar/Wind Helper
0.775
3152661PLYWOOD A
50/50
0.856
970535AG2-341 GEN
50/50
3.098
3144293JTRSVLE
50/50
0.416
3151581KERR 1
50/50
0.107
970909AG2-566 GEN
50/50
1.475
315687AD1-152 GEN
Solar/Wind Harmer
6.091
316248AF1-058 C
Solar/Wind Harmer
1.474
316118AC1-105 GEN
Solar/Wind Harmer
2.998
970099AG2-077 GEN
Solar/Wind Harmer
50.549
3146843MT LREL
Solar/Wind Harmer
-0.038
3146843MT LREL
Solar/Wind Harmer
-0.038
964791AG1-342 GEN
Solar/Wind Harmer
8.159
962561AG1-105 GEN
Solar/Wind Harmer
20.194
942751AE2-291 GEN
Solar/Wind Harmer
17.287
316237AB2-079_GEN
Solar/Wind Harmer
0.71
313527AB2-043 GEN
Solar/Wind Harmer
3.756
970323AG2-213 GEN
Solar/Wind Harmer
10.31
958211AF2-115 GEN
Solar/Wind Harmer
2.88
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
970301AG2-198 GEN
Solar/Wind Harmer
7.77
3146776BUCKING
Solar/Wind Harmer
-0.039
3146776BUCKING
Solar/Wind Harmer
-0.003
942671AE2-283 GEN
Solar/Wind Harmer
3.042
970933AG2-581 GEN
Solar/Wind Harmer
6.891
270013AE1-250 PV
Solar/Wind Helper
0.464
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.844
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.667
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.55
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.546
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.447
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.021
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.094
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.707

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.37 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1037.09
MW Contribution:
41.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.39 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1225.98
MW Contribution:
41.02
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.765
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.736
946301AF1-294 GEN
Solar/Wind Harmer
13.156
961791AG1-021 GEN
Solar/Wind Harmer
6.418
970683AG2-441 GEN
Solar/Wind Harmer
31.154
970681AG2-440 GEN
Solar/Wind Harmer
20.677
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.546
316486AD2-202 GEN
Solar/Wind Harmer
0.901
316238AB2-078_GEN
Solar/Wind Harmer
1.002
316239AB2-077_GEN
Solar/Wind Harmer
1.002
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.878
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.979
270455AD2-022 GEN
Solar/Wind Harmer
1.593
270457AD2-023 GEN
Solar/Wind Harmer
0.808
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.908
316327AA2-057 GEN
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.22
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.672
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.159
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.281
316405AF2-144 C
Solar/Wind Helper
0.234
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.158
970413AG2-270 GEN
50/50
29.68
972003AH1-546 GEN
Solar/Wind Harmer
41.016
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.214
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.235
971775AH1-396 GEN
Solar/Wind Harmer
3.055
959311AF2-222 GEN
Solar/Wind Harmer
44.444
964241AG1-285 GEN
Solar/Wind Harmer
30.357
316478AD1-087 GEN
Solar/Wind Harmer
3.077
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971683AH1-343 GEN
Solar/Wind Harmer
8.941
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.755
316222AC1-221 GEN
Solar/Wind Harmer
1.409
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.499
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.678
3146233WITAKRS
Solar/Wind Harmer
0.158
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.797
315722AD1-056 GEN
Solar/Wind Harmer
2.478
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.424
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.075
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.728
270494AE1-108_GEN
Solar/Wind Helper
3.729
315821AE2-092 GEN
Solar/Wind Helper
2.535
3144293JTRSVLE
50/50
1.158
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.815
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.418
970685AG2-442 GEN
Solar/Wind Harmer
40.479
316034AC1-036 C
Solar/Wind Harmer
0.777
315785AD2-033 C
Solar/Wind Harmer
9.425
315693AD1-088 GEN
Solar/Wind Harmer
20.651
957481AF2-042 GEN
Solar/Wind Harmer
118.484
316131AB2-060 GEN
Solar/Wind Harmer
3.728
970401AG2-262 GEN
Solar/Wind Harmer
1.862
971065AG2-659 GEN
Solar/Wind Harmer
10.95
316129AC1-054 GEN
Solar/Wind Harmer
1.833
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.541
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.908
316319Z2-044 C
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.973
3142053HEARTS
Solar/Wind Harmer
0.085
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
970909AG2-566 GEN
50/50
5.54
3144293JTRSVLE
50/50
1.158
970535AG2-341 GEN
50/50
4.753
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.506
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.178
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.022
970323AG2-213 GEN
Solar/Wind Harmer
21.647
970933AG2-581 GEN
Solar/Wind Harmer
36.177
970099AG2-077 GEN
Solar/Wind Harmer
47.394
313527AB2-043 GEN
Solar/Wind Harmer
5.52
316237AB2-079_GEN
Solar/Wind Harmer
1.002
315687AD1-152 GEN
Solar/Wind Harmer
3.681
962561AG1-105 GEN
Solar/Wind Harmer
16.518
964791AG1-342 GEN
Solar/Wind Harmer
6.094
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.82
316248AF1-058 C
Solar/Wind Harmer
0.739
942751AE2-291 GEN
Solar/Wind Harmer
9.07
313506AB2-031 GEN
Solar/Wind Harmer
0.863
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.391
961601AG1-000A GEN
Solar/Wind Harmer
2.762
315724AD1-057 GEN
Solar/Wind Harmer
1.363
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.98
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.061
3145603CNETO
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.011
316313AB2-026
Solar/Wind Helper
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
2.651
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.334
TVALTFEXP_TVA->PJM
CLTF
1.312
CPLELTFEXP_CPLE->PJM
CLTF
5.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.761
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.487
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.349
MECLTFEXP_MEC->PJM
CLTF
0.998
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.313
WECLTFEXP_WEC->PJM
CLTF
0.159

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.37 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1037.09
MW Contribution:
41.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.33 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1225.59
MW Contribution:
41.02
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.765
3151601KERR 3
50/50
0.482
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.736
946301AF1-294 GEN
Solar/Wind Harmer
13.156
961791AG1-021 GEN
Solar/Wind Harmer
6.418
970683AG2-441 GEN
Solar/Wind Harmer
31.154
970681AG2-440 GEN
Solar/Wind Harmer
20.677
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.546
316486AD2-202 GEN
Solar/Wind Harmer
0.901
316238AB2-078_GEN
Solar/Wind Harmer
1.002
316239AB2-077_GEN
Solar/Wind Harmer
1.002
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.878
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.979
270455AD2-022 GEN
Solar/Wind Harmer
1.593
270457AD2-023 GEN
Solar/Wind Harmer
0.808
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.908
316327AA2-057 GEN
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.22
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.672
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.159
3145893MURPHYS
Solar/Wind Harmer
-0.017
3144293JTRSVLE
50/50
1.158
970413AG2-270 GEN
50/50
29.68
972003AH1-546 GEN
Solar/Wind Harmer
41.016
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.214
3147133PAMPLIN
Solar/Wind Harmer
-0.163
970257AG2-171 GEN
Solar/Wind Harmer
16.235
971775AH1-396 GEN
Solar/Wind Harmer
3.055
959311AF2-222 GEN
Solar/Wind Harmer
44.444
964241AG1-285 GEN
Solar/Wind Harmer
30.357
316478AD1-087 GEN
Solar/Wind Harmer
3.077
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971683AH1-343 GEN
Solar/Wind Harmer
8.941
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.755
316222AC1-221 GEN
Solar/Wind Harmer
1.409
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.499
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.678
3146233WITAKRS
Solar/Wind Harmer
0.158
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.797
315722AD1-056 GEN
Solar/Wind Harmer
2.478
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.424
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.075
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.728
270494AE1-108_GEN
Solar/Wind Helper
3.729
315821AE2-092 GEN
Solar/Wind Helper
2.535
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.281
316405AF2-144 C
Solar/Wind Helper
0.234
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.158
3144293JTRSVLE
50/50
0.914
3151531CLOVER1
50/50
6.815
3151591KERR 2
50/50
0.482
3151641KERR 7
50/50
0.482
3147043LAWRENC
50/50
1.535
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.418
970685AG2-442 GEN
Solar/Wind Harmer
40.479
316034AC1-036 C
Solar/Wind Harmer
0.777
315785AD2-033 C
Solar/Wind Harmer
9.425
315693AD1-088 GEN
Solar/Wind Harmer
20.651
957481AF2-042 GEN
Solar/Wind Harmer
118.484
316131AB2-060 GEN
Solar/Wind Harmer
3.728
970401AG2-262 GEN
Solar/Wind Harmer
1.862
971065AG2-659 GEN
Solar/Wind Harmer
10.95
316129AC1-054 GEN
Solar/Wind Harmer
1.833
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.541
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.908
316319Z2-044 C
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.973
3142053HEARTS
Solar/Wind Harmer
0.085
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
970909AG2-566 GEN
50/50
5.54
3144293JTRSVLE
50/50
1.158
970535AG2-341 GEN
50/50
4.753
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.506
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.178
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.022
970323AG2-213 GEN
Solar/Wind Harmer
21.647
970933AG2-581 GEN
Solar/Wind Harmer
36.177
970099AG2-077 GEN
Solar/Wind Harmer
47.394
313527AB2-043 GEN
Solar/Wind Harmer
5.52
316237AB2-079_GEN
Solar/Wind Harmer
1.002
315687AD1-152 GEN
Solar/Wind Harmer
3.681
962561AG1-105 GEN
Solar/Wind Harmer
16.518
964791AG1-342 GEN
Solar/Wind Harmer
6.094
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.82
316248AF1-058 C
Solar/Wind Harmer
0.739
942751AE2-291 GEN
Solar/Wind Harmer
9.07
313506AB2-031 GEN
Solar/Wind Harmer
0.863
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.213
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.391
961601AG1-000A GEN
Solar/Wind Harmer
2.762
315724AD1-057 GEN
Solar/Wind Harmer
1.363
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.98
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.101
3145453TOT5
Solar/Wind Harmer
0.061
3145603CNETO
Solar/Wind Harmer
0.041
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.011
316313AB2-026
Solar/Wind Helper
0.312
LAGNLTFEXP_LAGN->PJM
CLTF
2.651
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.334
TVALTFEXP_TVA->PJM
CLTF
1.312
CPLELTFEXP_CPLE->PJM
CLTF
5.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.761
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.487
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.349
MECLTFEXP_MEC->PJM
CLTF
0.998
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.313
WECLTFEXP_WEC->PJM
CLTF
0.159

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.68 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1032.31
MW Contribution:
41.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:171.78 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1200.74
MW Contribution:
41.02
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.732
946301AF1-294 GEN
Solar/Wind Harmer
13.145
961791AG1-021 GEN
Solar/Wind Harmer
6.412
970683AG2-441 GEN
Solar/Wind Harmer
31.113
970681AG2-440 GEN
Solar/Wind Harmer
20.65
3144303KENBRDG
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
72.416
316486AD2-202 GEN
Solar/Wind Harmer
0.899
316238AB2-078_GEN
Solar/Wind Harmer
1
316239AB2-077_GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.854
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.412
970685AG2-442 GEN
Solar/Wind Harmer
40.43
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.413
315693AD1-088 GEN
Solar/Wind Harmer
20.618
957481AF2-042 GEN
Solar/Wind Harmer
118.263
316131AB2-060 GEN
Solar/Wind Harmer
3.721
970401AG2-262 GEN
Solar/Wind Harmer
1.857
971065AG2-659 GEN
Solar/Wind Harmer
10.923
316129AC1-054 GEN
Solar/Wind Harmer
1.828
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.54
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.907
316319Z2-044 C
Solar/Wind Harmer
0.413
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.962
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
972003AH1-546 GEN
Solar/Wind Harmer
41.021
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.208
3147133PAMPLIN
Solar/Wind Harmer
-0.162
970257AG2-171 GEN
Solar/Wind Harmer
16.215
971775AH1-396 GEN
Solar/Wind Harmer
3.051
959311AF2-222 GEN
Solar/Wind Harmer
44.382
964241AG1-285 GEN
Solar/Wind Harmer
30.309
316478AD1-087 GEN
Solar/Wind Harmer
3.07
316003AC1-222 GEN
Solar/Wind Harmer
2.211
971683AH1-343 GEN
Solar/Wind Harmer
8.909
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.749
316222AC1-221 GEN
Solar/Wind Harmer
1.395
316283AC2-100 C
Solar/Wind Harmer
1.274
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.497
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.675
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.765
315722AD1-056 GEN
Solar/Wind Harmer
2.458
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.421
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.303
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.08
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.72
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
316426AA2-053 GEN
Solar/Wind Harmer
0.978
270455AD2-022 GEN
Solar/Wind Harmer
1.57
270457AD2-023 GEN
Solar/Wind Harmer
0.796
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.903
316210AC1-098 GEN
Solar/Wind Harmer
1.214
316327AA2-057 GEN
Solar/Wind Harmer
0.781
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.657
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.157
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.015
970323AG2-213 GEN
Solar/Wind Harmer
21.621
970933AG2-581 GEN
Solar/Wind Harmer
36.112
970099AG2-077 GEN
Solar/Wind Harmer
47.305
313527AB2-043 GEN
Solar/Wind Harmer
5.511
316237AB2-079_GEN
Solar/Wind Harmer
1
315687AD1-152 GEN
Solar/Wind Harmer
3.67
962561AG1-105 GEN
Solar/Wind Harmer
16.477
964791AG1-342 GEN
Solar/Wind Harmer
6.078
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.814
316248AF1-058 C
Solar/Wind Harmer
0.736
942751AE2-291 GEN
Solar/Wind Harmer
9.035
313506AB2-031 GEN
Solar/Wind Harmer
0.862
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.21
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.77
316263AC1-034 GEN
Solar/Wind Harmer
3.352
961601AG1-000A GEN
Solar/Wind Harmer
2.73
315724AD1-057 GEN
Solar/Wind Harmer
1.352
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
316313AB2-026
Solar/Wind Helper
0.311
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.16 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:818.17
MW Contribution:
31.16
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.07 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:983.41
MW Contribution:
31.16
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151281ROARAP4
50/50
0.105
971845AH1-439 GEN
Solar/Wind Harmer
33.974
946301AF1-294 GEN
Solar/Wind Harmer
9.009
961791AG1-021 GEN
Solar/Wind Harmer
4.383
970683AG2-441 GEN
Solar/Wind Harmer
23.63
970681AG2-440 GEN
Solar/Wind Harmer
15.684
3144303KENBRDG
Solar/Wind Harmer
0.308
971967AH1-528 GEN
Solar/Wind Harmer
54.853
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970831AG2-522 GEN
Solar/Wind Harmer
7.484
3137643SOCKMAN
Solar/Wind Harmer
0.378
316426AA2-053 GEN
Solar/Wind Harmer
0.289
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.385
316210AC1-098 GEN
Solar/Wind Harmer
0.638
316327AA2-057 GEN
Solar/Wind Harmer
0.102
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.219
3151371ROSEMS1
50/50
0.136
3151381ROSEMG2
50/50
0.102
3146776BUCKING
Solar/Wind Harmer
3.039
3146776BUCKING
Solar/Wind Harmer
0.246
970301AG2-198 GEN
Solar/Wind Harmer
22.145
3147133PAMPLIN
Solar/Wind Harmer
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.479
970323AG2-213 GEN
Solar/Wind Harmer
16.421
970933AG2-581 GEN
Solar/Wind Harmer
27.427
970099AG2-077 GEN
Solar/Wind Harmer
35.928
962561AG1-105 GEN
Solar/Wind Harmer
12.514
964791AG1-342 GEN
Solar/Wind Harmer
4.862
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.862
313506AB2-031 GEN
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.613
3145783HORNRTN
Solar/Wind Harmer
1.291
3145783HORNRTN
Solar/Wind Harmer
0.403
3145783HORNRTN
Solar/Wind Harmer
0.161
3146033SCOT NK
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.661
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3151261ROARAP2
50/50
0.115
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
972003AH1-546 GEN
Solar/Wind Harmer
31.155
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.379
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
1.452
970257AG2-171 GEN
Solar/Wind Harmer
12.316
971775AH1-396 GEN
Solar/Wind Harmer
0.616
959311AF2-222 GEN
Solar/Wind Harmer
33.641
964241AG1-285 GEN
Solar/Wind Harmer
23.019
316478AD1-087 GEN
Solar/Wind Harmer
1.096
971683AH1-343 GEN
Solar/Wind Harmer
6.767
3147043LAWRENC
Solar/Wind Harmer
0.096
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316222AC1-221 GEN
Solar/Wind Harmer
0.507
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
316212AC1-099_GEN
Solar/Wind Harmer
0.356
3146233WITAKRS
Solar/Wind Harmer
0.334
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.044
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
4.396
315722AD1-056 GEN
Solar/Wind Harmer
2.125
3145796HORNRTN
Solar/Wind Harmer
0.243
3145796HORNRTN
Solar/Wind Harmer
0.061
316011AB1-132 GEN
Solar/Wind Harmer
1.098
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3145823KELFORD
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3151281ROARAP4
50/50
0.112
971629AH1-314 GEN
50/50
5.731
3151561HALLBR1
50/50
0.157
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.87
970685AG2-442 GEN
Solar/Wind Harmer
30.706
316034AC1-036 C
Solar/Wind Harmer
0.025
315785AD2-033 C
Solar/Wind Harmer
2.995
315693AD1-088 GEN
Solar/Wind Harmer
17.617
957481AF2-042 GEN
Solar/Wind Harmer
89.82
316131AB2-060 GEN
Solar/Wind Harmer
0.958
970401AG2-262 GEN
Solar/Wind Harmer
1.486
971065AG2-659 GEN
Solar/Wind Harmer
8.296
316129AC1-054 GEN
Solar/Wind Harmer
0.695
960081AF2-299 GEN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.161
3146233WITAKRS
Solar/Wind Harmer
0.265
316049AB1-081 GEN
Solar/Wind Harmer
0.362
316263AC1-034 GEN
Solar/Wind Harmer
2.419
961601AG1-000A GEN
Solar/Wind Harmer
1.099
315724AD1-057 GEN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.182
962571AG1-106 GEN
Solar/Wind Harmer
0.862
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.054
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
0.103
316313AB2-026
Solar/Wind Helper
0.311
3147123OTTER R
Solar/Wind Harmer
0.04
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.2
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.253
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.58 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:989.64
MW Contribution:
41.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.87 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1159.42
MW Contribution:
41.02
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.412
970685AG2-442 GEN
Solar/Wind Harmer
40.43
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.413
315693AD1-088 GEN
Solar/Wind Harmer
20.618
957481AF2-042 GEN
Solar/Wind Harmer
118.263
316131AB2-060 GEN
Solar/Wind Harmer
3.721
970401AG2-262 GEN
Solar/Wind Harmer
1.857
971065AG2-659 GEN
Solar/Wind Harmer
10.923
316129AC1-054 GEN
Solar/Wind Harmer
1.828
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.54
3145783HORNRTN
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
0.907
316319Z2-044 C
Solar/Wind Harmer
0.413
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.962
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
972003AH1-546 GEN
Solar/Wind Harmer
41.021
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.208
3147133PAMPLIN
Solar/Wind Harmer
-0.162
970257AG2-171 GEN
Solar/Wind Harmer
16.215
971775AH1-396 GEN
Solar/Wind Harmer
3.051
959311AF2-222 GEN
Solar/Wind Harmer
44.382
964241AG1-285 GEN
Solar/Wind Harmer
30.309
316478AD1-087 GEN
Solar/Wind Harmer
3.07
316003AC1-222 GEN
Solar/Wind Harmer
2.211
971683AH1-343 GEN
Solar/Wind Harmer
8.909
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.749
316222AC1-221 GEN
Solar/Wind Harmer
1.395
316283AC2-100 C
Solar/Wind Harmer
1.274
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.497
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.675
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.765
315722AD1-056 GEN
Solar/Wind Harmer
2.458
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.421
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.303
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.08
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.72
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.732
946301AF1-294 GEN
Solar/Wind Harmer
13.145
961791AG1-021 GEN
Solar/Wind Harmer
6.412
970683AG2-441 GEN
Solar/Wind Harmer
31.113
970681AG2-440 GEN
Solar/Wind Harmer
20.65
3144303KENBRDG
Solar/Wind Harmer
-0.035
316486AD2-202 GEN
Solar/Wind Harmer
0.899
316238AB2-078_GEN
Solar/Wind Harmer
1
316239AB2-077_GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.854
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
316426AA2-053 GEN
Solar/Wind Harmer
0.978
270455AD2-022 GEN
Solar/Wind Harmer
1.57
270457AD2-023 GEN
Solar/Wind Harmer
0.796
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.903
316210AC1-098 GEN
Solar/Wind Harmer
1.214
316327AA2-057 GEN
Solar/Wind Harmer
0.781
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.657
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.157
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.015
970323AG2-213 GEN
Solar/Wind Harmer
21.621
970099AG2-077 GEN
Solar/Wind Harmer
47.305
313527AB2-043 GEN
Solar/Wind Harmer
5.511
316237AB2-079_GEN
Solar/Wind Harmer
1
315687AD1-152 GEN
Solar/Wind Harmer
3.67
962561AG1-105 GEN
Solar/Wind Harmer
16.477
964791AG1-342 GEN
Solar/Wind Harmer
6.078
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.814
316248AF1-058 C
Solar/Wind Harmer
0.736
942751AE2-291 GEN
Solar/Wind Harmer
9.035
313506AB2-031 GEN
Solar/Wind Harmer
0.862
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.21
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.77
316263AC1-034 GEN
Solar/Wind Harmer
3.352
961601AG1-000A GEN
Solar/Wind Harmer
2.73
315724AD1-057 GEN
Solar/Wind Harmer
1.352
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
316313AB2-026
Solar/Wind Helper
0.311
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.58 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:989.64
MW Contribution:
41.02
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.87 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1159.42
MW Contribution:
41.02
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
316322AB2-045
Solar/Wind Harmer
2.867
971845AH1-439 GEN
Solar/Wind Harmer
44.732
946301AF1-294 GEN
Solar/Wind Harmer
13.145
961791AG1-021 GEN
Solar/Wind Harmer
6.412
970683AG2-441 GEN
Solar/Wind Harmer
31.113
970681AG2-440 GEN
Solar/Wind Harmer
20.65
3144303KENBRDG
Solar/Wind Harmer
-0.035
316486AD2-202 GEN
Solar/Wind Harmer
0.899
316238AB2-078_GEN
Solar/Wind Harmer
1
316239AB2-077_GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970831AG2-522 GEN
Solar/Wind Harmer
9.854
946281AF1-292 GEN
Solar/Wind Harmer
0.245
3137643SOCKMAN
Solar/Wind Harmer
-0.042
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
972003AH1-546 GEN
Solar/Wind Harmer
41.021
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.208
3147133PAMPLIN
Solar/Wind Harmer
-0.162
970257AG2-171 GEN
Solar/Wind Harmer
16.215
971775AH1-396 GEN
Solar/Wind Harmer
3.051
959311AF2-222 GEN
Solar/Wind Harmer
44.382
964241AG1-285 GEN
Solar/Wind Harmer
30.309
316478AD1-087 GEN
Solar/Wind Harmer
3.07
316003AC1-222 GEN
Solar/Wind Harmer
2.211
971683AH1-343 GEN
Solar/Wind Harmer
8.909
3147043LAWRENC
Solar/Wind Harmer
-0.011
316123AC1-075 GEN
Solar/Wind Harmer
1.749
316222AC1-221 GEN
Solar/Wind Harmer
1.395
316283AC2-100 C
Solar/Wind Harmer
1.274
966621AG1-532 GEN
Solar/Wind Harmer
0.222
316181AB2-040 GEN
Solar/Wind Harmer
1.497
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
971563AH1-280 GEN
Solar/Wind Harmer
6.412
970685AG2-442 GEN
Solar/Wind Harmer
40.43
316034AC1-036 C
Solar/Wind Harmer
0.776
315785AD2-033 C
Solar/Wind Harmer
9.413
315693AD1-088 GEN
Solar/Wind Harmer
20.618
957481AF2-042 GEN
Solar/Wind Harmer
118.263
316131AB2-060 GEN
Solar/Wind Harmer
3.721
970401AG2-262 GEN
Solar/Wind Harmer
1.857
971065AG2-659 GEN
Solar/Wind Harmer
10.923
316129AC1-054 GEN
Solar/Wind Harmer
1.828
960081AF2-299 GEN
Solar/Wind Harmer
1.231
316087AB2-174 GEN
Solar/Wind Harmer
1.54
3145783HORNRTN
Solar/Wind Harmer
-0.01
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3146776BUCKING
Solar/Wind Harmer
-0.34
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.157
3147133PAMPLIN
Solar/Wind Harmer
-0.052
3147133PAMPLIN
Solar/Wind Harmer
-0.042
958211AF2-115 GEN
Solar/Wind Harmer
8.015
970323AG2-213 GEN
Solar/Wind Harmer
21.621
970099AG2-077 GEN
Solar/Wind Harmer
47.305
313527AB2-043 GEN
Solar/Wind Harmer
5.511
316237AB2-079_GEN
Solar/Wind Harmer
1
315687AD1-152 GEN
Solar/Wind Harmer
3.67
962561AG1-105 GEN
Solar/Wind Harmer
16.477
964791AG1-342 GEN
Solar/Wind Harmer
6.078
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.814
316248AF1-058 C
Solar/Wind Harmer
0.736
942751AE2-291 GEN
Solar/Wind Harmer
9.035
313506AB2-031 GEN
Solar/Wind Harmer
0.862
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.21
316426AA2-053 GEN
Solar/Wind Harmer
0.978
270455AD2-022 GEN
Solar/Wind Harmer
1.57
270457AD2-023 GEN
Solar/Wind Harmer
0.796
3146043SEABORD
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
0.903
316210AC1-098 GEN
Solar/Wind Harmer
1.214
316327AA2-057 GEN
Solar/Wind Harmer
0.781
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.657
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
315607AA1-063A GEN
Solar/Wind Harmer
0.907
316319Z2-044 C
Solar/Wind Harmer
0.413
3146233WITAKRS
Solar/Wind Harmer
-0.03
3147123OTTER R
Solar/Wind Harmer
-0.004
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146263WOODLND
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.962
3142053HEARTS
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
316190AA2-174 GEN
Solar/Wind Harmer
0.119
316212AC1-099_GEN
Solar/Wind Harmer
0.675
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.765
315722AD1-056 GEN
Solar/Wind Harmer
2.458
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.421
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.303
3145823KELFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.08
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
0.72
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.303
3145783HORNRTN
Solar/Wind Harmer
0.121
316049AB1-081 GEN
Solar/Wind Harmer
0.77
316263AC1-034 GEN
Solar/Wind Harmer
3.352
961601AG1-000A GEN
Solar/Wind Harmer
2.73
315724AD1-057 GEN
Solar/Wind Harmer
1.352
3145796HORNRTN
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
0.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
316313AB2-026
Solar/Wind Helper
0.311
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Decrease to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.31 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:801.9
MW Contribution:
31.16
Impact of Topology Modeling:
Decrease

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:169.49 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:968.67
MW Contribution:
31.16
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
5.536
3144293JTRSVLE
50/50
1.157
970535AG2-341 GEN
50/50
4.743
3151581KERR 1
50/50
0.172
3152661PLYWOOD A
50/50
0.504
3151261ROARAP2
50/50
0.113
3151361ROSEMG1
50/50
0.219
3151371ROSEMS1
50/50
0.136
3151381ROSEMG2
50/50
0.102
3146776BUCKING
Solar/Wind Harmer
3.039
3146776BUCKING
Solar/Wind Harmer
0.246
970301AG2-198 GEN
Solar/Wind Harmer
22.145
3147133PAMPLIN
Solar/Wind Harmer
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.37
958211AF2-115 GEN
Solar/Wind Harmer
5.479
970323AG2-213 GEN
Solar/Wind Harmer
16.421
3151541CLOVER2
50/50
6.751
3151601KERR 3
50/50
0.481
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151281ROARAP4
50/50
0.105
971845AH1-439 GEN
Solar/Wind Harmer
33.974
946301AF1-294 GEN
Solar/Wind Harmer
9.009
961791AG1-021 GEN
Solar/Wind Harmer
4.383
970683AG2-441 GEN
Solar/Wind Harmer
23.63
970681AG2-440 GEN
Solar/Wind Harmer
15.684
3144303KENBRDG
Solar/Wind Harmer
0.308
316486AD2-202 GEN
Solar/Wind Harmer
0.322
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970831AG2-522 GEN
Solar/Wind Harmer
7.484
3137643SOCKMAN
Solar/Wind Harmer
0.378
316426AA2-053 GEN
Solar/Wind Harmer
0.289
3146043SEABORD
Solar/Wind Harmer
0.078
316274AC1-208 GEN
Solar/Wind Harmer
0.385
316210AC1-098 GEN
Solar/Wind Harmer
0.638
316327AA2-057 GEN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.661
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
0.154
3145893MURPHYS
Solar/Wind Harmer
0.057
316258AE1-075 C
Solar/Wind Helper
0.28
316405AF2-144 C
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970099AG2-077 GEN
Solar/Wind Harmer
35.928
962561AG1-105 GEN
Solar/Wind Harmer
12.514
964791AG1-342 GEN
Solar/Wind Harmer
4.862
3146843MT LREL
Solar/Wind Harmer
0.253
3146843MT LREL
Solar/Wind Harmer
0.253
316118AC1-105 GEN
Solar/Wind Harmer
0.603
942751AE2-291 GEN
Solar/Wind Harmer
6.862
313506AB2-031 GEN
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.613
3145783HORNRTN
Solar/Wind Harmer
1.291
3145783HORNRTN
Solar/Wind Harmer
0.403
3145783HORNRTN
Solar/Wind Harmer
0.161
316049AB1-081 GEN
Solar/Wind Harmer
0.362
316263AC1-034 GEN
Solar/Wind Harmer
2.419
961601AG1-000A GEN
Solar/Wind Harmer
1.099
315724AD1-057 GEN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.182
962571AG1-106 GEN
Solar/Wind Harmer
0.862
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3142666NORTHAMPTON
Solar/Wind Harmer
0.036
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.054
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
0.103
316313AB2-026
Solar/Wind Helper
0.311
3144293JTRSVLE
50/50
1.157
970413AG2-270 GEN
50/50
29.618
3151261ROARAP2
50/50
0.115
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
972003AH1-546 GEN
Solar/Wind Harmer
31.155
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.379
942461AE2-259 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
1.452
970257AG2-171 GEN
Solar/Wind Harmer
12.316
971775AH1-396 GEN
Solar/Wind Harmer
0.616
959311AF2-222 GEN
Solar/Wind Harmer
33.641
964241AG1-285 GEN
Solar/Wind Harmer
23.019
316478AD1-087 GEN
Solar/Wind Harmer
1.096
971683AH1-343 GEN
Solar/Wind Harmer
6.767
3147043LAWRENC
Solar/Wind Harmer
0.096
316123AC1-075 GEN
Solar/Wind Harmer
0.193
316222AC1-221 GEN
Solar/Wind Harmer
0.507
316283AC2-100 C
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.136
316212AC1-099_GEN
Solar/Wind Harmer
0.356
3146233WITAKRS
Solar/Wind Harmer
0.334
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.044
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
4.396
315722AD1-056 GEN
Solar/Wind Harmer
2.125
3145796HORNRTN
Solar/Wind Harmer
0.243
3145796HORNRTN
Solar/Wind Harmer
0.061
316011AB1-132 GEN
Solar/Wind Harmer
1.098
3142666NORTHAMPTON
Solar/Wind Harmer
0.06
3145823KELFORD
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
270494AE1-108_GEN
Solar/Wind Helper
3.726
315821AE2-092 GEN
Solar/Wind Helper
2.532
3144293JTRSVLE
50/50
1.157
3144293JTRSVLE
50/50
0.913
3151531CLOVER1
50/50
6.801
3151591KERR 2
50/50
0.481
3151641KERR 7
50/50
0.481
3147043LAWRENC
50/50
1.533
3151281ROARAP4
50/50
0.112
971629AH1-314 GEN
50/50
5.731
3151561HALLBR1
50/50
0.157
3151391GASTONA
50/50
0.162
3151411GASTONB
50/50
0.162
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.379
971563AH1-280 GEN
Solar/Wind Harmer
4.87
970685AG2-442 GEN
Solar/Wind Harmer
30.706
316034AC1-036 C
Solar/Wind Harmer
0.025
315785AD2-033 C
Solar/Wind Harmer
2.995
315693AD1-088 GEN
Solar/Wind Harmer
17.617
957481AF2-042 GEN
Solar/Wind Harmer
89.82
316131AB2-060 GEN
Solar/Wind Harmer
0.958
970401AG2-262 GEN
Solar/Wind Harmer
1.486
971065AG2-659 GEN
Solar/Wind Harmer
8.296
316129AC1-054 GEN
Solar/Wind Harmer
0.695
960081AF2-299 GEN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.161
3146233WITAKRS
Solar/Wind Harmer
0.265
3147123OTTER R
Solar/Wind Harmer
0.04
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.051
3146263WOODLND
Solar/Wind Harmer
0.064
316359AB2-059 GEN
Solar/Wind Harmer
0.226
3142053HEARTS
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.2
3145796HORNRTN
Solar/Wind Harmer
0.061
3145823KELFORD
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.253
LAGNLTFEXP_LAGN->PJM
CLTF
2.581
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.085
TVALTFEXP_TVA->PJM
CLTF
1.278
CPLELTFEXP_CPLE->PJM
CLTF
4.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.419
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.234
MECLTFEXP_MEC->PJM
CLTF
0.97
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.397
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.155
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A_SENS'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 313378 CKT 1   /*8MDLTHAN     500.0 - 8VONTAY      500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S_SENS'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 313378 CKT 1                /*8MDLTHAN     500.0 - 8VONTAY      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN MIDLOTHIAN-VONTAY_SRT-A_SENS'
 OPEN BRANCH FROM BUS 314914 TO BUS 313378 CKT 1   /*8MDLTHAN     500.0 - 8VONTAY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-3'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'DVP_P4-2: 242T2027_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'DVP_P4-2: 202712_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1                /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1                /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                                /*6POWHATN     230.0
 OPEN BUS 316258                                                /*AE1-075 C    230.0
 OPEN BUS 316313                                                /*AB2-026      230.0
 OPEN BUS 316405                                                /*AF2-144 C    230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
END
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-5: 556X2_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 556X1_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019F_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1          /*BRIGHTON     500.0 - 01DOUBS      500.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 2          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 4          /*01DOUBS      500.0 - 01DOUBS      230.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 1                  /*01DOUBS      500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 237804 CKT 1 /*01DOUBS      500.0 - 01ROCKYPOINT 500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 237804 CKT 2 /*01DOUBS      500.0 - 01ROCKYPOINT 500.0
END
CONTINGENCY 'PEPCO_P4_PP41_SRT-A'
 OPEN BRANCH FROM BUS 200003 TO BUS 224058 CKT 1   /*BRIGHTON     500.0 - BRG 3T 230   230.0
 OPEN BRANCH FROM BUS 200003 TO BUS 235105 CKT 1   /*BRIGHTON     500.0 - 01DOUBS      500.0
END
CONTINGENCY 'DVP_P4-2: 55692_SRT-S'
 OPEN BRANCH FROM BUS 314936 TO BUS 971966 CKT 1                /*8RAWLINGS    500.0 - AH1-528 TP   500.0
 OPEN BUS 314920                                                /*8RAWLIN_STC1 500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 587T591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-5: 593X1_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-5: 593X2_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P7-1: LN 556_Finneyw-AG1-285_SRT-A_SENS'
 OPEN BRANCH FROM BUS 313996 TO BUS 888888 CKT 1   /*6FINNEYWOOD  230.0 - AG1-285_230  230.0
 OPEN BRANCH FROM BUS 957480 TO BUS 313995 CKT 1   /*AF2-042 TP   500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H2T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 2   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H1T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 1   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
313996 to 313995 ckt 1
313996 to 313995 ckt 2
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1
314922 to 200019 ckt 1
316281 to 304070 ckt 1
972002 to 314747 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
DVP_P1-2: LN 2193_SRT-A
SingleAC110.92 %134.42B149.09
4.2
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC175.55 %678.68B1191.4
16.57
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC173.13 %830.0C1436.99
21.78
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC173.13 %830.0C1436.97
21.78
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC160.47 %830.0C1331.88
22.06
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC160.47 %830.0C1331.88
22.06
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B3_SRT-A
BusAC109.69 %830.0C910.4
23.96
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC105.52 %800.88B845.12
10.83
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC105.13 %800.88B841.95
10.83
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC174.45 %678.68B1183.97
16.57
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC172.24 %830.0C1429.6
21.78
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC172.24 %830.0C1429.58
21.78
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC159.58 %830.0C1324.55
22.06
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC159.58 %830.0C1324.55
22.06
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B3_SRT-A
BusAC108.83 %830.0C903.29
23.96
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC107.83 %800.88B863.6
10.83
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC107.43 %800.88B860.42
10.83
GD2DVP
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC119.0 %984.18B1171.21
4.37
GD2DVP
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC106.53 %984.18B1048.43
4.6
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: H2T560_SRT-A
BreakerAC137.48 %1417.0B1948.14
3.34
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: H1T560_SRT-A
BreakerAC137.48 %1417.0B1948.07
3.34
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: 560T571_SRT-S
BreakerAC136.59 %1417.0B1935.43
3.32
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC132.6 %1417.0B1878.9
2.74
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC131.8 %1331.98B1755.6
2.54
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC121.4 %1417.0B1720.2
3.24
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC171.33 %678.68B1162.8
15.44
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC167.37 %830.0C1389.21
20.29
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC167.37 %830.0C1389.18
20.29
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC159.8 %830.0C1326.36
20.55
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC159.8 %830.0C1326.36
20.55
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC127.81 %830.0C1060.79
26.74
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC173.1 %661.76B1145.53
15.44
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC169.58 %809.0C1371.94
20.29
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC169.58 %809.0C1371.91
20.29
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC161.82 %809.0C1309.09
20.55
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC161.82 %809.0C1309.09
20.55
GD2DVP
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC111.8 %984.18B1100.34
4.37
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: 562T563_SRT-S
BreakerAC123.21 %1265.1C1558.74
6.24
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S
SingleAC121.76 %1057.5B1287.59
4.73
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC121.28 %1265.1C1534.29
6.23
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC169.7 %661.76B1122.99
15.44
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC166.8 %809.0C1349.42
20.29
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC166.8 %809.0C1349.39
20.29
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC159.03 %809.0C1286.56
20.55
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC159.03 %809.0C1286.56
20.55
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC126.21 %809.0C1021.03
26.74
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC112.29 %800.88B899.3
16.57
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.55 %800.88B893.41
10.82
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2054_SRT-A
BreakerAC103.57 %980.0C1014.95
21.83
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 233T2028_SRT-A
BreakerAC101.84 %980.0C998.06
21.82
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2193_SRT-A
BreakerAC101.81 %980.0C997.75
22.09
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: WT2193_SRT-A
BreakerAC101.79 %980.0C997.51
22.09
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC101.67 %980.0C996.36
14.24
GD2DVP
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC115.48 %984.18B1136.48
4.37
GD2DVP
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.13 %984.18B1015.01
4.6
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC121.88 %1478.62B1802.21
2.54
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: H2T560_SRT-A
BreakerAC110.27 %1809.0C1994.82
3.34
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: H1T560_SRT-A
BreakerAC110.27 %1809.0C1994.74
3.34
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: 560T571_SRT-S
BreakerAC109.57 %1809.0C1982.11
3.32
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC106.46 %1809.0C1925.78
2.74
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC103.68 %3940.0C4085.15
12.86
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 298_SRT-A-4
SingleAC103.61 %3220.44B3336.6
9.93
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC119.54 %4070.2B4865.39
5.59
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC113.04 %4070.2B4600.84
5.44
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC159.03 %4070.2B6472.73
7.3
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC141.11 %4070.2B5743.4
4.79
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Base Case
SingleAC109.7 %4070.2A4464.82
4.71
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P7-1: LN 2054-2135_SRT-A
TowerAC105.79 %5011.0C5301.17
7.88
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC116.05 %4070.2B4723.52
5.49
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC114.79 %4070.2B4672.2
5.34
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC121.15 %3220.44B3901.64
4.36
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC120.7 %3220.44B3887.02
4.34
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC159.65 %3220.44B5141.33
6.53
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-1: G202_SRT-S
BreakerAC128.61 %3118.0C4010.0
3.86
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B2_SRT-S
BusAC124.42 %3118.0C3879.34
3.87
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B1_SRT-S
BusAC124.42 %3118.0C3879.34
3.87
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC122.54 %3220.44B3946.36
5.24
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: LN 2090-256_SRT-S
TowerAC102.71 %3940.0C4046.64
1.87
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: LN 2054-2135_SRT-A
TowerAC102.49 %3940.0C4038.23
7.6
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Base Case
SingleAC101.48 %3193.18A3240.38
4.88
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57302_SRT-S
BreakerAC149.16 %3118.0C4650.9
6.75
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC132.01 %3220.44B4251.24
5.11
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC129.17 %3220.44B4159.96
5.23
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC124.53 %3940.0C4906.62
6.84
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC120.22 %3940.0C4736.51
6.78
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 515T594_SRT-S
BreakerAC119.98 %3940.0C4727.27
6.73
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: XT573_SRT-S
BreakerAC118.04 %3940.0C4650.81
6.75
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC166.92 %3940.0C6576.66
9.21
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 57502_SRT-S
BreakerAC158.88 %3118.0C4954.02
7.25
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC154.87 %3220.44B4987.58
5.88
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC154.04 %3220.44B4960.85
5.93
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC109.64 %3940.0C4319.87
7.08
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC109.38 %3940.0C4309.68
7.08
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Base Case
SingleAC108.67 %3193.18A3470.14
4.48
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC106.46 %3940.0C4194.66
5.2
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC102.14 %3099.0B3165.31
5.29
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC168.62 %3940.0C6643.56
9.13
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC161.05 %3220.44B5186.56
6.05
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC156.69 %3220.44B5046.02
5.92
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P7-1: LN 2-2199_SRT-A-1
TowerAC116.02 %3940.0C4571.15
7.05
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
SingleAC115.83 %3220.44A3730.18
4.56
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P7-1: LN 2-2199_SRT-A-2
TowerAC115.74 %3940.0C4560.31
7.05
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC112.89 %3940.0C4447.98
6.83
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC112.15 %800.88B898.18
16.58
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.87 %800.88B895.98
10.83
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2054_SRT-A
BreakerAC103.54 %980.0C1014.73
21.84
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC102.07 %980.0C1000.24
14.25
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC102.06 %980.0C1000.22
14.25
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 233T2028_SRT-A
BreakerAC101.82 %980.0C997.84
21.83
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2193_SRT-A
BreakerAC101.77 %980.0C997.37
22.1
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC109.1 %800.88B873.8
10.83
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC108.71 %800.88B870.6
10.83
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC105.44 %699.0C736.99
39.02
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC100.97 %699.0C705.81
39.13

Details for 3BREMO-3FORK UNION 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.92 %
Rating:134.42 MVA
Rating Type:B
MVA to Mitigate:149.09
MW Contribution:
4.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.151
970221AG2-151 GEN
Solar/Wind Harmer
10.888
270494AE1-108_GEN
Solar/Wind Harmer
1.906
972003AH1-546 GEN
Solar/Wind Harmer
4.195
3146776BUCKING
Solar/Wind Harmer
0.035
3146926FARMVIL
Solar/Wind Harmer
0.046
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.97
958131AF2-107 GEN
Solar/Wind Harmer
1.795
3147133PAMPLIN
Solar/Wind Harmer
0.179
315821AE2-092 GEN
Solar/Wind Helper
3.512
972205AH1-687 GEN
50/50
5.623
971845AH1-439 GEN
Solar/Wind Harmer
4.382
316258AE1-075 C
Solar/Wind Harmer
0.048
3151931BEARGRDN S1
50/50
1.487
3151911BEARGRDN G1
50/50
1.151
971377AH1-170 GEN
Solar/Wind Harmer
2.178
3147623JAMES R
Solar/Wind Harmer
0.473
970937AG2-583 GEN
Solar/Wind Harmer
6.218
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.046
3143336POWHATN
Solar/Wind Harmer
1.141
957481AF2-042 GEN
Solar/Wind Harmer
6.599
970909AG2-566 GEN
50/50
0.616
3146776BUCKING
Solar/Wind Harmer
0.394
3146776BUCKING
Solar/Wind Harmer
0.032
316336AC2-165 C
Solar/Wind Harmer
3.78
316313AB2-026
Solar/Wind Harmer
0.04
970301AG2-198 GEN
Solar/Wind Harmer
2.465
3147133PAMPLIN
Solar/Wind Harmer
0.057
3147133PAMPLIN
Solar/Wind Harmer
0.046
970099AG2-077 GEN
Solar/Wind Harmer
2.64
LAGNLTFEXP_LAGN->PJM
CLTF
0.384
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.756
TVALTFEXP_TVA->PJM
CLTF
0.189
CPLELTFEXP_CPLE->PJM
CLTF
0.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.611
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.085
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.599
MECLTFEXP_MEC->PJM
CLTF
0.086
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.111
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.006

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.55 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1191.4
MW Contribution:
16.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.181
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.485
3151601KERR 3
50/50
0.231
3151611KERR 4
50/50
0.231
3151621KERR 5
50/50
0.231
3151631KERR 6
50/50
0.231
963041AG1-153 GEN
50/50
2.3
315244AE2-183_ST
50/50
2.456
3151281ROARAP4
50/50
0.093
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.514
316258AE1-075 C
Solar/Wind Harmer
0.202
946301AF1-294 GEN
Solar/Wind Harmer
4.405
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
12.335
970681AG2-440 GEN
Solar/Wind Harmer
8.187
3144303KENBRDG
Solar/Wind Harmer
0.148
316486AD2-202 GEN
Solar/Wind Harmer
0.119
316233AE1-074 FULL
Solar/Wind Harmer
0.084
970909AG2-566 GEN
50/50
2.566
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.241
3151581KERR 1
50/50
0.082
3152661PLYWOOD A
50/50
0.224
3151041BRUNSWICKG3
50/50
1.136
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.414
315241AE2-183_GT1
50/50
1.41
972185AH1-677 GEN
50/50
5.112
3151261ROARAP2
50/50
0.1
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
316336AC2-165 C
Solar/Wind Harmer
15.638
316313AB2-026
Solar/Wind Harmer
0.168
970301AG2-198 GEN
Solar/Wind Harmer
10.263
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.679
970323AG2-213 GEN
Solar/Wind Harmer
7.893
971223AH1-071 GEN
Solar/Wind Harmer
1.335
962561AG1-105 GEN
Solar/Wind Harmer
5.682
970099AG2-077 GEN
Solar/Wind Harmer
12.508
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
316118AC1-105 GEN
Solar/Wind Harmer
0.268
970933AG2-581 GEN
Solar/Wind Harmer
7.997
313506AB2-031 GEN
Solar/Wind Harmer
0.263
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316365GEN2_N
Solar/Wind Harmer
0.174
3144356SAPONY
Solar/Wind Harmer
0.654
316315AB2-025 C
Solar/Wind Harmer
0.063
962571AG1-106 GEN
Solar/Wind Harmer
1.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
970831AG2-522 GEN
Solar/Wind Harmer
4.275
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.957
970673AG2-436 GEN
Solar/Wind Harmer
10.614
970533AG2-339 GEN
Solar/Wind Harmer
6.417
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.374
970581AG2-369 GEN
Solar/Wind Harmer
3.761
316426AA2-053 GEN
Solar/Wind Harmer
0.271
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.194
315652AC1-086 GEN
Solar/Wind Harmer
8.309
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
316274AC1-208 GEN
Solar/Wind Harmer
0.387
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
316210AC1-098 GEN
Solar/Wind Harmer
0.683
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
316463AE2-346 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
0.154
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.106
970657AG2-426 GEN
Solar/Wind Harmer
0.518
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.621
316311AC2-079 GEN
Solar/Wind Harmer
2.01
315732AD1-074 GEN1
Solar/Wind Harmer
0.397
315733AD1-074 GEN2
Solar/Wind Harmer
0.397
3130546PLYMOUTH
Solar/Wind Harmer
0.07
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
957871AF2-081 GEN
Solar/Wind Harmer
3.42
316316AC1-027 C
Solar/Wind Harmer
0.065
3151081ELIZAR1
Adder
6.27
3151091ELIZAR2
Adder
6.161
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
957861AF2-080 GEN
Solar/Wind Harmer
2.904
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
971445AH1-216 GEN
Solar/Wind Harmer
4.705
3151201GRAVEL4
Adder
4.805
3151221GRAVEL6
Adder
4.799
3151191GRAVEL3
Adder
4.744
3151211GRAVEL5
Adder
4.744
315697AD1-025 GEN
Solar/Wind Harmer
0.071
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.908
3151031BRUNSWICKG2
50/50
1.136
3151261ROARAP2
50/50
0.102
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.202
3151411GASTONB
50/50
0.202
972003AH1-546 GEN
Solar/Wind Harmer
16.566
3146776BUCKING
Solar/Wind Harmer
0.142
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
4.089
3147133PAMPLIN
Solar/Wind Harmer
0.741
959311AF2-222 GEN
Solar/Wind Harmer
16.947
970257AG2-171 GEN
Solar/Wind Harmer
5.92
971775AH1-396 GEN
Solar/Wind Harmer
0.296
964241AG1-285 GEN
Solar/Wind Harmer
10.433
970221AG2-151 GEN
Solar/Wind Harmer
7.011
316478AD1-087 GEN
Solar/Wind Harmer
0.404
3147043LAWRENC
Solar/Wind Harmer
0.063
270494AE1-108_GEN
Solar/Wind Harmer
1.23
316181AB2-040 GEN
Solar/Wind Harmer
0.122
944011AF1-069 GEN
Solar/Wind Harmer
5.111
970917AG2-570 GEN
Solar/Wind Harmer
7.385
971683AH1-343 GEN
Solar/Wind Harmer
2.995
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.37
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316140AB2-099
Solar/Wind Harmer
0.026
315742AE1-103 GEN
Solar/Wind Harmer
1.084
315724AD1-057 GEN
Solar/Wind Harmer
1.363
316349AD2-085 GEN
Solar/Wind Harmer
0.047
316065AD1-022 GEN
Solar/Wind Harmer
3.224
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315614AA2-178 GEN
Solar/Wind Harmer
0.395
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146386ELIZ CT
Solar/Wind Harmer
0.069
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.216
316339AD2-160 GEN
Solar/Wind Harmer
0.11
316388AE2-253 GEN
Solar/Wind Harmer
0.214
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.514
316049AB1-081 GEN
Solar/Wind Harmer
0.387
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
316294AC1-161 GEN
Solar/Wind Harmer
1.166
3145823KELFORD
Solar/Wind Harmer
0.073
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.785
315722AD1-056 GEN
Solar/Wind Harmer
2.443
970657AG2-426 GEN
Solar/Wind Harmer
1.583
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315735AD1-075 GEN1
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.012
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
316017AA1-139 ULT1
Solar/Wind Harmer
0.037
944581AF1-123 GEN
Solar/Wind Harmer
15.462
944601AF1-125 GEN
Solar/Wind Harmer
15.223
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.35
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
316222AC1-221 GEN
Solar/Wind Harmer
0.281
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
4.809
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.263
3151931BEARGRDN S1
50/50
5.865
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.682
3151531CLOVER1
50/50
2.505
316458AB2-190 GEN2
Solar/Wind Harmer
0.351
970133AG2-095 GEN
Solar/Wind Harmer
0.63
316123AC1-075 GEN
Solar/Wind Harmer
0.087
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.513
3132273ORANGE
Solar/Wind Helper
0.027
3147666LOUISA
Solar/Wind Helper
0.273
3151591KERR 2
50/50
0.231
3151641KERR 7
50/50
0.231
3147043LAWRENC
50/50
1.001
3151051BRUNSWICKS1
50/50
2.358
3151021BRUNSWICKG1
50/50
1.136
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.414
3151281ROARAP4
50/50
0.099
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.202
3151411GASTONB
50/50
0.202
970937AG2-583 GEN
Solar/Wind Harmer
24.929
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
3143336POWHATN
Solar/Wind Harmer
4.81
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.92
316034AC1-036 C
Solar/Wind Harmer
0.012
315785AD2-033 C
Solar/Wind Harmer
1.433
316131AB2-060 GEN
Solar/Wind Harmer
0.448
315693AD1-088 GEN
Solar/Wind Harmer
6.777
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.271
970401AG2-262 GEN
Solar/Wind Harmer
0.671
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.447
316129AC1-054 GEN
Solar/Wind Harmer
0.383
960081AF2-299 GEN
Solar/Wind Harmer
0.847
941031AE2-094 GEN
Solar/Wind Harmer
15.643
970919AG2-571 GEN
Solar/Wind Harmer
2.954
970087AG2-069 GEN
Solar/Wind Harmer
6.56
3145783HORNRTN
Solar/Wind Harmer
0.082
940641AE2-051 GEN
Solar/Wind Harmer
6.46
315607AA1-063A GEN
Solar/Wind Harmer
0.162
316023GEN1_S
Solar/Wind Harmer
0.174
939411AE1-173 GEN
Solar/Wind Harmer
33.164
3146263WOODLND
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.335
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3156021HOLLOMANSOL
Solar/Wind Harmer
0.319
316381AD1-082 GEN
Solar/Wind Harmer
0.072
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.498
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
315737AD1-076 GEN
Solar/Wind Harmer
0.894
316093AE2-104_GEN
Solar/Wind Harmer
1.171
315816AE2-034 GEN
Solar/Wind Harmer
0.297
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.559
3130156CHOWAN
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
0
319010AE1-072 C
Solar/Wind Harmer
0.343
3146456SLIGO L269
Solar/Wind Harmer
0.069
944591AF1-124 GEN
Solar/Wind Harmer
15.516
3145963POPLR C
Solar/Wind Harmer
0.069
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.012
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316159AE1-175 C
Solar/Wind Harmer
0.049
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.1
3148463FAIRFLD
Solar/Wind Helper
0.12
315616AA1-038_C
Solar/Wind Helper
0.545
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316005AA1-067
Solar/Wind Harmer
0.072
316033AB2-134 GEN
Solar/Wind Harmer
0
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.196
3150701DARBY 4
Adder
4.186
3150681DARBY 2
Adder
4.181
3150671DARBY 1
Adder
4.176
942751AE2-291 GEN
Solar/Wind Harmer
3.156
966001AG1-469 GEN
Solar/Wind Helper
0.19
316359AB2-059 GEN
Solar/Wind Harmer
0.242
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.024
3146293MARTNCO
Solar/Wind Harmer
0.063
315773AC2-141 GEN
Solar/Wind Harmer
2.463
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.228
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.458
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316132AB2-190 GEN1
Solar/Wind Harmer
0.351
944631AF1-128 GEN
Adder
29.459
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.825
3147666LOUISA
Solar/Wind Helper
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
1.785
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.539
TVALTFEXP_TVA->PJM
CLTF
0.872
CPLELTFEXP_CPLE->PJM
CLTF
4.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.299
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.732
MECLTFEXP_MEC->PJM
CLTF
0.357
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.578
LGEELTFEXP_LGEE->PJM
CLTF
0.049
WECLTFEXP_WEC->PJM
CLTF
0.019

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.13 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1436.99
MW Contribution:
21.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.147
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.483
3151601KERR 3
50/50
0.23
3151611KERR 4
50/50
0.23
3151621KERR 5
50/50
0.23
3151631KERR 6
50/50
0.23
316322AB2-045
Solar/Wind Harmer
1.48
971845AH1-439 GEN
Solar/Wind Harmer
23.026
316258AE1-075 C
Solar/Wind Harmer
0.735
316405AF2-144 C
Solar/Wind Harmer
0.776
946301AF1-294 GEN
Solar/Wind Harmer
6.418
961791AG1-021 GEN
Solar/Wind Harmer
3.131
970683AG2-441 GEN
Solar/Wind Harmer
16.22
970681AG2-440 GEN
Solar/Wind Harmer
10.765
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.466
316239AB2-077_GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.331
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
970831AG2-522 GEN
Solar/Wind Harmer
5.623
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.736
946281AF1-292 GEN
Solar/Wind Harmer
0.222
970673AG2-436 GEN
Solar/Wind Harmer
20.955
970533AG2-339 GEN
Solar/Wind Harmer
6.415
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.755
970581AG2-369 GEN
Solar/Wind Harmer
4.95
971285AH1-108 GEN
Adder
0.613
316426AA2-053 GEN
Solar/Wind Harmer
0.917
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.191
315652AC1-086 GEN
Solar/Wind Harmer
9.547
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
-0.027
970909AG2-566 GEN
50/50
2.562
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.238
3151581KERR 1
50/50
0.082
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
21.624
316313AB2-026
Solar/Wind Harmer
0.817
970301AG2-198 GEN
Solar/Wind Harmer
13.495
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
970323AG2-213 GEN
Solar/Wind Harmer
10.378
313527AB2-043 GEN
Solar/Wind Harmer
2.566
316237AB2-079_GEN
Solar/Wind Harmer
0.466
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.472
970099AG2-077 GEN
Solar/Wind Harmer
16.454
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
315687AD1-152 GEN
Solar/Wind Harmer
1.429
3143526WINTERP
Solar/Wind Harmer
-0.061
316118AC1-105 GEN
Solar/Wind Harmer
0.805
970933AG2-581 GEN
Solar/Wind Harmer
10.522
316248AF1-058 C
Solar/Wind Harmer
0.321
972187AH1-678 GEN
Adder
2.455
972185AH1-677 GEN
Adder
4.816
313506AB2-031 GEN
Solar/Wind Harmer
0.771
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.3
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
316463AE2-346 GEN
Solar/Wind Harmer
0.133
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.811
315839AE2-212 C
Solar/Wind Harmer
0.239
970657AG2-426 GEN
Solar/Wind Harmer
0.5
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.45
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316311AC2-079 GEN
Solar/Wind Harmer
3.969
315732AD1-074 GEN1
Solar/Wind Harmer
1.58
315733AD1-074 GEN2
Solar/Wind Harmer
1.58
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.922
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
313526AB2-022
Solar/Wind Harmer
0.208
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.66
957871AF2-081 GEN
Solar/Wind Harmer
3.861
316316AC1-027 C
Solar/Wind Harmer
0.236
3151081ELIZAR1
Adder
6.273
3151091ELIZAR2
Adder
6.164
316174AB2-169 GEN
Solar/Wind Harmer
1.183
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
957861AF2-080 GEN
Solar/Wind Harmer
3.309
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
316236AE1-162_GEN
Solar/Wind Harmer
0.226
971445AH1-216 GEN
Solar/Wind Harmer
4.649
3151201GRAVEL4
Adder
4.808
3151221GRAVEL6
Adder
4.802
3151191GRAVEL3
Adder
4.747
3151211GRAVEL5
Adder
4.747
315697AD1-025 GEN
Solar/Wind Harmer
1.494
316382AG1-145 C
Solar/Wind Harmer
0.195
316159AE1-175 C
Solar/Wind Harmer
0.174
957831AF2-077 GEN
Solar/Wind Harmer
0.193
3138283WHITEMARSH
Solar/Wind Harmer
0.01
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
315616AA1-038_C
Solar/Wind Helper
0.549
3151931BEARGRDN S1
50/50
5.856
3151911BEARGRDN G1
50/50
4.533
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.674
3151531CLOVER1
50/50
2.502
3151591KERR 2
50/50
0.23
3151641KERR 7
50/50
0.23
970937AG2-583 GEN
Solar/Wind Harmer
32.775
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.603
971563AH1-280 GEN
Solar/Wind Harmer
3.131
970685AG2-442 GEN
Solar/Wind Harmer
20.933
316034AC1-036 C
Solar/Wind Harmer
0.384
315785AD2-033 C
Solar/Wind Harmer
4.498
316131AB2-060 GEN
Solar/Wind Harmer
1.738
315693AD1-088 GEN
Solar/Wind Harmer
7.923
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.134
970401AG2-262 GEN
Solar/Wind Harmer
0.837
3143526WINTERP
Solar/Wind Harmer
-0.061
3151921BEARGRDN G2
50/50
4.533
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.896
972003AH1-546 GEN
Solar/Wind Harmer
21.779
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.602
3143336POWHATN
Solar/Wind Harmer
3.063
3147133PAMPLIN
Solar/Wind Harmer
-0.083
959311AF2-222 GEN
Solar/Wind Harmer
22.328
970257AG2-171 GEN
Solar/Wind Harmer
7.784
971775AH1-396 GEN
Solar/Wind Harmer
1.465
964241AG1-285 GEN
Solar/Wind Harmer
13.72
970221AG2-151 GEN
Solar/Wind Harmer
9.179
316478AD1-087 GEN
Solar/Wind Harmer
1.131
3147043LAWRENC
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Harmer
2.99
316003AC1-222 GEN
Solar/Wind Harmer
0.97
966621AG1-532 GEN
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
1.34
944011AF1-069 GEN
Solar/Wind Harmer
5.605
970917AG2-570 GEN
Solar/Wind Harmer
23.325
3150861SPRUNCD
Adder
0.375
3145783HORNRTN
Solar/Wind Harmer
0.109
316365GEN2_N
Solar/Wind Harmer
0.593
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.236
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.055
315742AE1-103 GEN
Solar/Wind Harmer
1.935
316083AB2-161 GEN
Solar/Wind Harmer
1.287
315724AD1-057 GEN
Solar/Wind Harmer
1.554
316349AD2-085 GEN
Solar/Wind Harmer
0.699
316065AD1-022 GEN
Solar/Wind Harmer
3.933
315835AF2-110_GEN
Solar/Wind Harmer
0.979
315614AA2-178 GEN
Solar/Wind Harmer
0.84
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
971683AH1-343 GEN
Solar/Wind Harmer
3.936
316190AA2-174 GEN
Solar/Wind Harmer
0.112
3156081AA2-088 GEN
Solar/Wind Harmer
2.772
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.772
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.722
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.986
315722AD1-056 GEN
Solar/Wind Harmer
2.825
970657AG2-426 GEN
Solar/Wind Harmer
1.602
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.79
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.208
316305AF2-043 C
Solar/Wind Harmer
0.233
316246AF1-032 C
Solar/Wind Harmer
0.156
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.894
316017AA1-139 ULT1
Solar/Wind Harmer
0.623
944581AF1-123 GEN
Solar/Wind Harmer
35.113
944601AF1-125 GEN
Solar/Wind Harmer
34.565
3145963POPLR C
Solar/Wind Harmer
-0.008
3142956BIRDNECK
Solar/Wind Harmer
0.413
3151101ELIZAR3
Adder
6.353
3144873MCLAUGH
Solar/Wind Harmer
0
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Harmer
0.772
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.022
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
316420AA1-050 GEN
Solar/Wind Harmer
0.862
316283AC2-100 C
Solar/Wind Harmer
0.713
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.003
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151171GRAVELC
Adder
0.924
961611AG1-000B GEN
Solar/Wind Harmer
1.561
315778AD1-151 GEN
Solar/Wind Harmer
6.583
316458AB2-190 GEN2
Solar/Wind Harmer
0.745
970133AG2-095 GEN
Solar/Wind Harmer
0.83
316123AC1-075 GEN
Solar/Wind Harmer
0.79
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.527
3142946ENON
Solar/Wind Harmer
-0.002
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316435W1029_GEN3
Solar/Wind Harmer
1.405
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316240AF1-291 C
Solar/Wind Harmer
0.233
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316388AE2-253 GEN
Solar/Wind Harmer
0.519
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.811
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.538
316049AB1-081 GEN
Solar/Wind Harmer
0.822
316263AC1-034 GEN
Solar/Wind Harmer
3.582
316294AC1-161 GEN
Solar/Wind Harmer
2.453
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
2.985
3145493TOT1
Solar/Wind Harmer
0.117
3145453TOT5
Solar/Wind Harmer
0.07
3145603CNETO
Solar/Wind Harmer
0.047
316005AA1-067
Solar/Wind Harmer
0.152
316033AB2-134 GEN
Solar/Wind Harmer
2.383
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
-0.001
3150691DARBY 3
Adder
4.202
3150701DARBY 4
Adder
4.192
3150681DARBY 2
Adder
4.188
3150671DARBY 1
Adder
4.183
942751AE2-291 GEN
Solar/Wind Harmer
4.144
966001AG1-469 GEN
Solar/Wind Helper
0.199
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.849
316129AC1-054 GEN
Solar/Wind Harmer
1.005
960081AF2-299 GEN
Solar/Wind Harmer
1.114
316087AB2-174 GEN
Solar/Wind Harmer
1.383
941031AE2-094 GEN
Solar/Wind Harmer
17.887
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
8.633
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
940641AE2-051 GEN
Solar/Wind Harmer
8.505
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316023GEN1_S
Solar/Wind Harmer
0.593
939411AE1-173 GEN
Solar/Wind Harmer
43.668
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.071
316381AD1-082 GEN
Solar/Wind Harmer
0.726
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.972
316319Z2-044 C
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.031
315737AD1-076 GEN
Solar/Wind Harmer
1.485
316093AE2-104_GEN
Solar/Wind Harmer
2.276
315816AE2-034 GEN
Solar/Wind Harmer
0.63
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.32
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.922
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.398
319010AE1-072 C
Solar/Wind Harmer
1.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
944591AF1-124 GEN
Solar/Wind Harmer
35.239
3145963POPLR C
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.657
316036AC1-147 C
Solar/Wind Harmer
0.207
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.09
316072AD1-144
Solar/Wind Harmer
0.154
315773AC2-141 GEN
Solar/Wind Harmer
3.174
3146293MARTNCO
Solar/Wind Harmer
0.047
961671AG1-007 GEN
Solar/Wind Harmer
0.096
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.225
316494AC1-189 GEN
Solar/Wind Harmer
0.814
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.03
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.703
961611AG1-000B GEN
Solar/Wind Harmer
3.659
316369SG1_INVT
Solar/Wind Harmer
1.32
971069AG2-661 GEN
Solar/Wind Harmer
1.17
316132AB2-190 GEN1
Solar/Wind Harmer
0.745
944631AF1-128 GEN
Adder
29.493
3138126ROCKLANDING
Solar/Wind Harmer
0.021
971317AH1-138 GEN
Solar/Wind Harmer
0.826
3142433PROV 92
Solar/Wind Harmer
-0.025
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.929
3147666LOUISA
Solar/Wind Helper
0.538
LAGNLTFEXP_LAGN->PJM
CLTF
1.773
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.519
TVALTFEXP_TVA->PJM
CLTF
0.866
CPLELTFEXP_CPLE->PJM
CLTF
4.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.225
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.709
MECLTFEXP_MEC->PJM
CLTF
0.349
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.017

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.13 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1436.97
MW Contribution:
21.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.147
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.483
3151601KERR 3
50/50
0.23
3151611KERR 4
50/50
0.23
3151621KERR 5
50/50
0.23
3151631KERR 6
50/50
0.23
316322AB2-045
Solar/Wind Harmer
1.48
971845AH1-439 GEN
Solar/Wind Harmer
23.025
316258AE1-075 C
Solar/Wind Harmer
0.735
316405AF2-144 C
Solar/Wind Harmer
0.776
946301AF1-294 GEN
Solar/Wind Harmer
6.418
961791AG1-021 GEN
Solar/Wind Harmer
3.131
970683AG2-441 GEN
Solar/Wind Harmer
16.219
970681AG2-440 GEN
Solar/Wind Harmer
10.765
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.466
316239AB2-077_GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.331
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
970831AG2-522 GEN
Solar/Wind Harmer
5.623
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.736
946281AF1-292 GEN
Solar/Wind Harmer
0.222
970673AG2-436 GEN
Solar/Wind Harmer
20.955
970533AG2-339 GEN
Solar/Wind Harmer
6.415
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.755
970581AG2-369 GEN
Solar/Wind Harmer
4.95
971285AH1-108 GEN
Adder
0.613
316426AA2-053 GEN
Solar/Wind Harmer
0.917
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.191
315652AC1-086 GEN
Solar/Wind Harmer
9.547
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.3
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
316463AE2-346 GEN
Solar/Wind Harmer
0.133
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.811
315839AE2-212 C
Solar/Wind Harmer
0.239
970657AG2-426 GEN
Solar/Wind Harmer
0.5
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.45
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316311AC2-079 GEN
Solar/Wind Harmer
3.969
315732AD1-074 GEN1
Solar/Wind Harmer
1.58
315733AD1-074 GEN2
Solar/Wind Harmer
1.58
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.922
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
313526AB2-022
Solar/Wind Harmer
0.208
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.66
957871AF2-081 GEN
Solar/Wind Harmer
3.861
316316AC1-027 C
Solar/Wind Harmer
0.236
3151081ELIZAR1
Adder
6.273
3151091ELIZAR2
Adder
6.164
316174AB2-169 GEN
Solar/Wind Harmer
1.183
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
957861AF2-080 GEN
Solar/Wind Harmer
3.309
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
316236AE1-162_GEN
Solar/Wind Harmer
0.226
971445AH1-216 GEN
Solar/Wind Harmer
4.649
3151201GRAVEL4
Adder
4.808
3151221GRAVEL6
Adder
4.802
3151191GRAVEL3
Adder
4.747
3151211GRAVEL5
Adder
4.747
315697AD1-025 GEN
Solar/Wind Harmer
1.494
316382AG1-145 C
Solar/Wind Harmer
0.195
316159AE1-175 C
Solar/Wind Harmer
0.174
957831AF2-077 GEN
Solar/Wind Harmer
0.193
3138283WHITEMARSH
Solar/Wind Harmer
0.01
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
315616AA1-038_C
Solar/Wind Helper
0.549
3151921BEARGRDN G2
50/50
4.532
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.896
972003AH1-546 GEN
Solar/Wind Harmer
21.778
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.602
3143336POWHATN
Solar/Wind Harmer
3.063
3147133PAMPLIN
Solar/Wind Harmer
-0.083
959311AF2-222 GEN
Solar/Wind Harmer
22.328
970257AG2-171 GEN
Solar/Wind Harmer
7.784
971775AH1-396 GEN
Solar/Wind Harmer
1.464
964241AG1-285 GEN
Solar/Wind Harmer
13.72
970221AG2-151 GEN
Solar/Wind Harmer
9.179
316478AD1-087 GEN
Solar/Wind Harmer
1.131
3147043LAWRENC
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Harmer
2.99
316003AC1-222 GEN
Solar/Wind Harmer
0.97
966621AG1-532 GEN
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
1.34
944011AF1-069 GEN
Solar/Wind Harmer
5.605
970917AG2-570 GEN
Solar/Wind Harmer
23.325
3150861SPRUNCD
Adder
0.375
971683AH1-343 GEN
Solar/Wind Harmer
3.936
316190AA2-174 GEN
Solar/Wind Harmer
0.112
3156081AA2-088 GEN
Solar/Wind Harmer
2.772
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.772
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.722
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.986
315722AD1-056 GEN
Solar/Wind Harmer
2.825
970657AG2-426 GEN
Solar/Wind Harmer
1.602
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.79
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.208
316305AF2-043 C
Solar/Wind Harmer
0.233
316246AF1-032 C
Solar/Wind Harmer
0.156
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.894
316017AA1-139 ULT1
Solar/Wind Harmer
0.623
944581AF1-123 GEN
Solar/Wind Harmer
35.113
944601AF1-125 GEN
Solar/Wind Harmer
34.565
3145963POPLR C
Solar/Wind Harmer
-0.008
3142956BIRDNECK
Solar/Wind Harmer
0.413
3151101ELIZAR3
Adder
6.353
3144873MCLAUGH
Solar/Wind Harmer
0
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Harmer
0.772
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.022
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
316420AA1-050 GEN
Solar/Wind Harmer
0.862
316283AC2-100 C
Solar/Wind Harmer
0.713
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.003
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151171GRAVELC
Adder
0.924
961611AG1-000B GEN
Solar/Wind Harmer
1.561
315778AD1-151 GEN
Solar/Wind Harmer
6.583
316458AB2-190 GEN2
Solar/Wind Harmer
0.745
970133AG2-095 GEN
Solar/Wind Harmer
0.83
316123AC1-075 GEN
Solar/Wind Harmer
0.79
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.527
3142946ENON
Solar/Wind Harmer
-0.002
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
970909AG2-566 GEN
50/50
2.562
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.238
3151581KERR 1
50/50
0.082
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
21.623
316313AB2-026
Solar/Wind Harmer
0.817
970301AG2-198 GEN
Solar/Wind Harmer
13.494
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
970323AG2-213 GEN
Solar/Wind Harmer
10.378
313527AB2-043 GEN
Solar/Wind Harmer
2.566
316237AB2-079_GEN
Solar/Wind Harmer
0.466
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.472
970099AG2-077 GEN
Solar/Wind Harmer
16.454
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
315687AD1-152 GEN
Solar/Wind Harmer
1.429
3143526WINTERP
Solar/Wind Harmer
-0.061
316118AC1-105 GEN
Solar/Wind Harmer
0.805
970933AG2-581 GEN
Solar/Wind Harmer
10.522
316248AF1-058 C
Solar/Wind Harmer
0.321
972187AH1-678 GEN
Adder
2.455
972185AH1-677 GEN
Adder
4.816
313506AB2-031 GEN
Solar/Wind Harmer
0.771
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316365GEN2_N
Solar/Wind Harmer
0.593
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.236
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.055
315742AE1-103 GEN
Solar/Wind Harmer
1.935
316083AB2-161 GEN
Solar/Wind Harmer
1.287
315724AD1-057 GEN
Solar/Wind Harmer
1.554
316349AD2-085 GEN
Solar/Wind Harmer
0.699
316065AD1-022 GEN
Solar/Wind Harmer
3.933
315835AF2-110_GEN
Solar/Wind Harmer
0.979
315614AA2-178 GEN
Solar/Wind Harmer
0.84
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316435W1029_GEN3
Solar/Wind Harmer
1.405
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316240AF1-291 C
Solar/Wind Harmer
0.233
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316388AE2-253 GEN
Solar/Wind Harmer
0.519
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.811
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.539
316049AB1-081 GEN
Solar/Wind Harmer
0.822
316263AC1-034 GEN
Solar/Wind Harmer
3.582
316294AC1-161 GEN
Solar/Wind Harmer
2.453
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
2.985
3145493TOT1
Solar/Wind Harmer
0.117
3145453TOT5
Solar/Wind Harmer
0.07
3145603CNETO
Solar/Wind Harmer
0.047
316005AA1-067
Solar/Wind Harmer
0.152
316033AB2-134 GEN
Solar/Wind Harmer
2.383
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
-0.001
3150691DARBY 3
Adder
4.202
3150701DARBY 4
Adder
4.193
3150681DARBY 2
Adder
4.188
3150671DARBY 1
Adder
4.183
942751AE2-291 GEN
Solar/Wind Harmer
4.144
966001AG1-469 GEN
Solar/Wind Helper
0.199
3151931BEARGRDN S1
50/50
5.856
3151911BEARGRDN G1
50/50
4.532
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.674
3151531CLOVER1
50/50
2.502
3151591KERR 2
50/50
0.23
3151641KERR 7
50/50
0.23
970937AG2-583 GEN
Solar/Wind Harmer
32.775
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.603
971563AH1-280 GEN
Solar/Wind Harmer
3.131
970685AG2-442 GEN
Solar/Wind Harmer
20.932
316034AC1-036 C
Solar/Wind Harmer
0.384
315785AD2-033 C
Solar/Wind Harmer
4.498
316131AB2-060 GEN
Solar/Wind Harmer
1.738
315693AD1-088 GEN
Solar/Wind Harmer
7.923
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.134
970401AG2-262 GEN
Solar/Wind Harmer
0.837
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.849
316129AC1-054 GEN
Solar/Wind Harmer
1.005
960081AF2-299 GEN
Solar/Wind Harmer
1.114
316087AB2-174 GEN
Solar/Wind Harmer
1.383
941031AE2-094 GEN
Solar/Wind Harmer
17.887
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
8.633
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
940641AE2-051 GEN
Solar/Wind Harmer
8.505
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316023GEN1_S
Solar/Wind Harmer
0.593
939411AE1-173 GEN
Solar/Wind Harmer
43.668
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.071
316381AD1-082 GEN
Solar/Wind Harmer
0.726
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.972
316319Z2-044 C
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.031
315737AD1-076 GEN
Solar/Wind Harmer
1.485
316093AE2-104_GEN
Solar/Wind Harmer
2.276
315816AE2-034 GEN
Solar/Wind Harmer
0.63
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.32
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.922
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.398
319010AE1-072 C
Solar/Wind Harmer
1.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
944591AF1-124 GEN
Solar/Wind Harmer
35.239
3145963POPLR C
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.657
316036AC1-147 C
Solar/Wind Harmer
0.207
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.09
316072AD1-144
Solar/Wind Harmer
0.154
315773AC2-141 GEN
Solar/Wind Harmer
3.174
3146293MARTNCO
Solar/Wind Harmer
0.047
961671AG1-007 GEN
Solar/Wind Harmer
0.096
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.225
316494AC1-189 GEN
Solar/Wind Harmer
0.814
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.03
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.703
961611AG1-000B GEN
Solar/Wind Harmer
3.659
316369SG1_INVT
Solar/Wind Harmer
1.32
971069AG2-661 GEN
Solar/Wind Harmer
1.17
316132AB2-190 GEN1
Solar/Wind Harmer
0.745
944631AF1-128 GEN
Adder
29.493
3138126ROCKLANDING
Solar/Wind Harmer
0.021
971317AH1-138 GEN
Solar/Wind Harmer
0.826
3142433PROV 92
Solar/Wind Harmer
-0.025
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.93
3147666LOUISA
Solar/Wind Helper
0.539
LAGNLTFEXP_LAGN->PJM
CLTF
1.773
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.519
TVALTFEXP_TVA->PJM
CLTF
0.866
CPLELTFEXP_CPLE->PJM
CLTF
4.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.709
MECLTFEXP_MEC->PJM
CLTF
0.349
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.017

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:160.47 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1331.88
MW Contribution:
22.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.443
316303AF2-085
50/50
2.628
316322AB2-045
Solar/Wind Harmer
1.492
971845AH1-439 GEN
Solar/Wind Harmer
23.204
316258AE1-075 C
Solar/Wind Harmer
0.779
316405AF2-144 C
Solar/Wind Harmer
0.823
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
16.031
970681AG2-440 GEN
Solar/Wind Harmer
10.64
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.235
971283AH1-107 GEN
Solar/Wind Harmer
2.235
316486AD2-202 GEN
Solar/Wind Harmer
0.313
970831AG2-522 GEN
Solar/Wind Harmer
5.345
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
17.883
946281AF1-292 GEN
Solar/Wind Harmer
0.209
3137643SOCKMAN
Solar/Wind Harmer
-0.035
316426AA2-053 GEN
Solar/Wind Harmer
0.86
970673AG2-436 GEN
Solar/Wind Harmer
18.644
970533AG2-339 GEN
Solar/Wind Harmer
5.691
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.171
970581AG2-369 GEN
Solar/Wind Harmer
4.447
315814AE2-033 C
Solar/Wind Harmer
7.589
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.891
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.846
315839AE2-212 C
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.212
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
0.476
316327AA2-057 GEN
Solar/Wind Harmer
0.754
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316311AC2-079 GEN
Solar/Wind Harmer
3.723
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.198
315697AD1-025 GEN
Solar/Wind Harmer
1.465
315732AD1-074 GEN1
Solar/Wind Harmer
1.463
315733AD1-074 GEN2
Solar/Wind Harmer
1.463
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.777
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3151921BEARGRDN G2
50/50
4.593
3144293JTRSVLE
50/50
0.56
972003AH1-546 GEN
Solar/Wind Harmer
22.059
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.593
3147133PAMPLIN
Solar/Wind Harmer
-0.082
959311AF2-222 GEN
Solar/Wind Harmer
22.005
970257AG2-171 GEN
Solar/Wind Harmer
7.662
971775AH1-396 GEN
Solar/Wind Harmer
1.442
964241AG1-285 GEN
Solar/Wind Harmer
13.399
970221AG2-151 GEN
Solar/Wind Harmer
9.591
316478AD1-087 GEN
Solar/Wind Harmer
1.07
270494AE1-108_GEN
Solar/Wind Harmer
3.119
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.922
966621AG1-532 GEN
Solar/Wind Harmer
0.189
316181AB2-040 GEN
Solar/Wind Harmer
1.26
971683AH1-343 GEN
Solar/Wind Harmer
3.742
316190AA2-174 GEN
Solar/Wind Harmer
0.105
944011AF1-069 GEN
Solar/Wind Harmer
4.972
970917AG2-570 GEN
Solar/Wind Harmer
20.942
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.588
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.651
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.673
315813AE1-149 C
Solar/Wind Harmer
4.802
316317KELFORD C
Solar/Wind Harmer
0.354
3145823KELFORD
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
1.525
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.838
315722AD1-056 GEN
Solar/Wind Harmer
2.623
316458AB2-190 GEN2
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.494
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.731
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
1.509
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
316321Z2-027
Solar/Wind Harmer
0.192
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
970909AG2-566 GEN
50/50
2.539
3144293JTRSVLE
50/50
0.56
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.646
316313AB2-026
Solar/Wind Harmer
0.866
970301AG2-198 GEN
Solar/Wind Harmer
13.373
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
970323AG2-213 GEN
Solar/Wind Harmer
10.216
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.492
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.197
970099AG2-077 GEN
Solar/Wind Harmer
15.506
964791AG1-342 GEN
Solar/Wind Harmer
2.635
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
315687AD1-152 GEN
Solar/Wind Harmer
1.352
316118AC1-105 GEN
Solar/Wind Harmer
0.77
970933AG2-581 GEN
Solar/Wind Harmer
9.651
316248AF1-058 C
Solar/Wind Harmer
0.305
313506AB2-031 GEN
Solar/Wind Harmer
0.725
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.303
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.552
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
313526AB2-022
Solar/Wind Harmer
0.192
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
316174AB2-169 GEN
Solar/Wind Harmer
1.095
316316AC1-027 C
Solar/Wind Harmer
0.218
3151201GRAVEL4
Adder
4.604
3151221GRAVEL6
Adder
4.599
3151191GRAVEL3
Adder
4.546
3151211GRAVEL5
Adder
4.546
316236AE1-162_GEN
Solar/Wind Harmer
0.214
971445AH1-216 GEN
Solar/Wind Harmer
4.396
3151081ELIZAR1
Adder
5.794
3151091ELIZAR2
Adder
5.693
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.064
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
316382AG1-145 C
Solar/Wind Harmer
0.19
316159AE1-175 C
Solar/Wind Harmer
0.169
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.102
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
315616AA1-038_C
Solar/Wind Helper
0.535
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
3142956BIRDNECK
Solar/Wind Harmer
0.381
3144873MCLAUGH
Solar/Wind Harmer
0
3151171GRAVELC
Adder
0.885
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.868
944581AF1-123 GEN
Solar/Wind Harmer
32.275
944601AF1-125 GEN
Solar/Wind Harmer
31.771
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.664
961601AG1-000A GEN
Solar/Wind Harmer
2.801
3145933PARMELE
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.799
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.751
3142946ENON
Solar/Wind Harmer
-0.002
970293AG2-193 GEN
Solar/Wind Harmer
0.834
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.264
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.038
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.802
316083AB2-161 GEN
Solar/Wind Harmer
1.227
316349AD2-085 GEN
Solar/Wind Harmer
0.655
315724AD1-057 GEN
Solar/Wind Harmer
1.443
316065AD1-022 GEN
Solar/Wind Harmer
3.644
315835AF2-110_GEN
Solar/Wind Harmer
0.909
316033AB2-134 GEN
Solar/Wind Harmer
2.337
3142366NRTHEST
Adder
0.21
315614AA2-178 GEN
Solar/Wind Harmer
0.777
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
316435W1029_GEN3
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
316049AB1-081 GEN
Solar/Wind Harmer
0.762
316263AC1-034 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
2.766
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3150691DARBY 3
Adder
4.503
3150701DARBY 4
Adder
4.493
3150681DARBY 2
Adder
4.488
3150671DARBY 1
Adder
4.482
3145493TOT1
Solar/Wind Harmer
0.109
3145453TOT5
Solar/Wind Harmer
0.065
3145603CNETO
Solar/Wind Harmer
0.043
316005AA1-067
Solar/Wind Harmer
0.141
316294AC1-161 GEN
Solar/Wind Harmer
2.243
3142946ENON
Solar/Wind Harmer
-0.001
966001AG1-469 GEN
Solar/Wind Helper
0.186
3151931BEARGRDN S1
50/50
5.934
3151911BEARGRDN G1
50/50
4.593
3144293JTRSVLE
50/50
0.56
3144293JTRSVLE
50/50
0.442
970119AG2-088 GEN
50/50
19.708
970937AG2-583 GEN
Solar/Wind Harmer
33.601
3146776BUCKING
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
20.721
316034AC1-036 C
Solar/Wind Harmer
0.378
315785AD2-033 C
Solar/Wind Harmer
4.42
3143226MDLTHAN
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
1.689
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.6
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.764
970401AG2-262 GEN
Solar/Wind Harmer
0.805
3147043LAWRENC
Adder
0.899
971065AG2-659 GEN
Solar/Wind Harmer
5.573
316129AC1-054 GEN
Solar/Wind Harmer
0.957
3150851SPRUNCC
Adder
0.417
960081AF2-299 GEN
Solar/Wind Harmer
1.05
316087AB2-174 GEN
Solar/Wind Harmer
1.301
3145783HORNRTN
Solar/Wind Harmer
-0.009
3142543TWELFTH
Solar/Wind Harmer
-0.001
941031AE2-094 GEN
Solar/Wind Harmer
15.869
315607AA1-063A GEN
Solar/Wind Harmer
0.851
970919AG2-571 GEN
Solar/Wind Harmer
2.651
970087AG2-069 GEN
Solar/Wind Harmer
7.756
316023GEN1_S
Solar/Wind Harmer
0.552
940641AE2-051 GEN
Solar/Wind Harmer
7.519
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.962
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.397
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316381AD1-082 GEN
Solar/Wind Harmer
0.692
3156021HOLLOMANSOL
Solar/Wind Harmer
0.994
316132AB2-190 GEN1
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
316319Z2-044 C
Solar/Wind Harmer
0.403
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.114
316369SG1_INVT
Solar/Wind Harmer
1.295
315737AD1-076 GEN
Solar/Wind Harmer
1.375
944631AF1-128 GEN
Adder
30.668
315816AE2-034 GEN
Solar/Wind Harmer
0.583
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.774
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.777
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.536
3145963POPLR C
Solar/Wind Harmer
-0.007
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.456
316036AC1-147 C
Solar/Wind Harmer
0.191
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.391
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.143
316359AB2-059 GEN
Solar/Wind Harmer
0.953
3142053HEARTS
Solar/Wind Harmer
0.083
3146293MARTNCO
Solar/Wind Harmer
0.044
961671AG1-007 GEN
Solar/Wind Harmer
0.089
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.208
316494AC1-189 GEN
Solar/Wind Harmer
0.754
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315773AC2-141 GEN
Solar/Wind Harmer
2.902
3138126ROCKLANDING
Solar/Wind Harmer
0.02
3142433PROV 92
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
971317AH1-138 GEN
Solar/Wind Harmer
0.794
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.8
3147666LOUISA
Solar/Wind Helper
0.46
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.559
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.779
TVALTFEXP_TVA->PJM
CLTF
0.76
CPLELTFEXP_CPLE->PJM
CLTF
3.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.141
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.352
MECLTFEXP_MEC->PJM
CLTF
0.255
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:160.47 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1331.88
MW Contribution:
22.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.443
316303AF2-085
50/50
2.628
316322AB2-045
Solar/Wind Harmer
1.492
971845AH1-439 GEN
Solar/Wind Harmer
23.204
316258AE1-075 C
Solar/Wind Harmer
0.779
316405AF2-144 C
Solar/Wind Harmer
0.823
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
16.031
970681AG2-440 GEN
Solar/Wind Harmer
10.64
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.235
971283AH1-107 GEN
Solar/Wind Harmer
2.235
316486AD2-202 GEN
Solar/Wind Harmer
0.313
970831AG2-522 GEN
Solar/Wind Harmer
5.345
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
17.883
946281AF1-292 GEN
Solar/Wind Harmer
0.209
3137643SOCKMAN
Solar/Wind Harmer
-0.035
316426AA2-053 GEN
Solar/Wind Harmer
0.86
970673AG2-436 GEN
Solar/Wind Harmer
18.644
970533AG2-339 GEN
Solar/Wind Harmer
5.691
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.171
970581AG2-369 GEN
Solar/Wind Harmer
4.447
315814AE2-033 C
Solar/Wind Harmer
7.589
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.891
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.846
315839AE2-212 C
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.212
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
0.476
316327AA2-057 GEN
Solar/Wind Harmer
0.754
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316311AC2-079 GEN
Solar/Wind Harmer
3.723
3151921BEARGRDN G2
50/50
4.593
3144293JTRSVLE
50/50
0.56
972003AH1-546 GEN
Solar/Wind Harmer
22.059
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.593
3147133PAMPLIN
Solar/Wind Harmer
-0.082
959311AF2-222 GEN
Solar/Wind Harmer
22.005
970257AG2-171 GEN
Solar/Wind Harmer
7.662
971775AH1-396 GEN
Solar/Wind Harmer
1.442
964241AG1-285 GEN
Solar/Wind Harmer
13.399
970221AG2-151 GEN
Solar/Wind Harmer
9.591
316478AD1-087 GEN
Solar/Wind Harmer
1.07
270494AE1-108_GEN
Solar/Wind Harmer
3.119
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.922
966621AG1-532 GEN
Solar/Wind Harmer
0.189
316181AB2-040 GEN
Solar/Wind Harmer
1.26
971683AH1-343 GEN
Solar/Wind Harmer
3.742
316190AA2-174 GEN
Solar/Wind Harmer
0.105
944011AF1-069 GEN
Solar/Wind Harmer
4.972
970917AG2-570 GEN
Solar/Wind Harmer
20.942
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.588
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.651
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.673
315813AE1-149 C
Solar/Wind Harmer
4.802
316317KELFORD C
Solar/Wind Harmer
0.354
3145823KELFORD
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
1.525
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.838
315722AD1-056 GEN
Solar/Wind Harmer
2.623
316458AB2-190 GEN2
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.494
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.731
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
1.509
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
316321Z2-027
Solar/Wind Harmer
0.192
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
3142956BIRDNECK
Solar/Wind Harmer
0.381
3144873MCLAUGH
Solar/Wind Harmer
0
3151171GRAVELC
Adder
0.885
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.868
944581AF1-123 GEN
Solar/Wind Harmer
32.275
944601AF1-125 GEN
Solar/Wind Harmer
31.771
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.198
315697AD1-025 GEN
Solar/Wind Harmer
1.465
315732AD1-074 GEN1
Solar/Wind Harmer
1.463
315733AD1-074 GEN2
Solar/Wind Harmer
1.463
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.777
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.192
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
316174AB2-169 GEN
Solar/Wind Harmer
1.095
316316AC1-027 C
Solar/Wind Harmer
0.218
3151201GRAVEL4
Adder
4.604
3151221GRAVEL6
Adder
4.599
3151191GRAVEL3
Adder
4.546
3151211GRAVEL5
Adder
4.546
316236AE1-162_GEN
Solar/Wind Harmer
0.214
971445AH1-216 GEN
Solar/Wind Harmer
4.396
3151081ELIZAR1
Adder
5.794
3151091ELIZAR2
Adder
5.693
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.064
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
316382AG1-145 C
Solar/Wind Harmer
0.19
316159AE1-175 C
Solar/Wind Harmer
0.169
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.102
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
315616AA1-038_C
Solar/Wind Helper
0.535
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.664
961601AG1-000A GEN
Solar/Wind Harmer
2.801
3145933PARMELE
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.799
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.751
3142946ENON
Solar/Wind Harmer
-0.002
970293AG2-193 GEN
Solar/Wind Harmer
0.834
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.264
970909AG2-566 GEN
50/50
2.539
3144293JTRSVLE
50/50
0.56
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.646
316313AB2-026
Solar/Wind Harmer
0.866
970301AG2-198 GEN
Solar/Wind Harmer
13.373
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
970323AG2-213 GEN
Solar/Wind Harmer
10.216
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.492
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.197
970099AG2-077 GEN
Solar/Wind Harmer
15.506
964791AG1-342 GEN
Solar/Wind Harmer
2.635
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
315687AD1-152 GEN
Solar/Wind Harmer
1.352
316118AC1-105 GEN
Solar/Wind Harmer
0.77
970933AG2-581 GEN
Solar/Wind Harmer
9.651
316248AF1-058 C
Solar/Wind Harmer
0.305
313506AB2-031 GEN
Solar/Wind Harmer
0.725
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.303
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.552
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.038
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.802
316083AB2-161 GEN
Solar/Wind Harmer
1.227
316349AD2-085 GEN
Solar/Wind Harmer
0.655
315724AD1-057 GEN
Solar/Wind Harmer
1.443
316065AD1-022 GEN
Solar/Wind Harmer
3.644
315835AF2-110_GEN
Solar/Wind Harmer
0.909
316033AB2-134 GEN
Solar/Wind Harmer
2.337
3142366NRTHEST
Adder
0.21
315614AA2-178 GEN
Solar/Wind Harmer
0.777
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
316435W1029_GEN3
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
316049AB1-081 GEN
Solar/Wind Harmer
0.762
316263AC1-034 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
2.766
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3150691DARBY 3
Adder
4.503
3150701DARBY 4
Adder
4.493
3150681DARBY 2
Adder
4.488
3150671DARBY 1
Adder
4.482
3145493TOT1
Solar/Wind Harmer
0.109
3145453TOT5
Solar/Wind Harmer
0.065
3145603CNETO
Solar/Wind Harmer
0.043
316005AA1-067
Solar/Wind Harmer
0.141
316294AC1-161 GEN
Solar/Wind Harmer
2.243
3142946ENON
Solar/Wind Harmer
-0.001
966001AG1-469 GEN
Solar/Wind Helper
0.186
3151931BEARGRDN S1
50/50
5.934
3151911BEARGRDN G1
50/50
4.593
3144293JTRSVLE
50/50
0.56
3144293JTRSVLE
50/50
0.442
970119AG2-088 GEN
50/50
19.708
970937AG2-583 GEN
Solar/Wind Harmer
33.601
3146776BUCKING
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
20.721
316034AC1-036 C
Solar/Wind Harmer
0.378
315785AD2-033 C
Solar/Wind Harmer
4.42
3143226MDLTHAN
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
1.689
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.6
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.764
970401AG2-262 GEN
Solar/Wind Harmer
0.805
3147043LAWRENC
Adder
0.899
971065AG2-659 GEN
Solar/Wind Harmer
5.573
316129AC1-054 GEN
Solar/Wind Harmer
0.957
3150851SPRUNCC
Adder
0.417
960081AF2-299 GEN
Solar/Wind Harmer
1.05
316087AB2-174 GEN
Solar/Wind Harmer
1.301
3145783HORNRTN
Solar/Wind Harmer
-0.009
3142543TWELFTH
Solar/Wind Harmer
-0.001
941031AE2-094 GEN
Solar/Wind Harmer
15.869
315607AA1-063A GEN
Solar/Wind Harmer
0.851
970919AG2-571 GEN
Solar/Wind Harmer
2.651
970087AG2-069 GEN
Solar/Wind Harmer
7.756
316023GEN1_S
Solar/Wind Harmer
0.552
940641AE2-051 GEN
Solar/Wind Harmer
7.519
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.962
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.397
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316381AD1-082 GEN
Solar/Wind Harmer
0.692
3156021HOLLOMANSOL
Solar/Wind Harmer
0.994
316132AB2-190 GEN1
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
316319Z2-044 C
Solar/Wind Harmer
0.403
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.114
316369SG1_INVT
Solar/Wind Harmer
1.295
315737AD1-076 GEN
Solar/Wind Harmer
1.375
944631AF1-128 GEN
Adder
30.668
315816AE2-034 GEN
Solar/Wind Harmer
0.583
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.774
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.777
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.536
3145963POPLR C
Solar/Wind Harmer
-0.007
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.456
316036AC1-147 C
Solar/Wind Harmer
0.191
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.391
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.143
316359AB2-059 GEN
Solar/Wind Harmer
0.953
3142053HEARTS
Solar/Wind Harmer
0.083
3146293MARTNCO
Solar/Wind Harmer
0.044
961671AG1-007 GEN
Solar/Wind Harmer
0.089
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.208
316494AC1-189 GEN
Solar/Wind Harmer
0.754
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315773AC2-141 GEN
Solar/Wind Harmer
2.902
3138126ROCKLANDING
Solar/Wind Harmer
0.02
3142433PROV 92
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
971317AH1-138 GEN
Solar/Wind Harmer
0.794
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.8
3147666LOUISA
Solar/Wind Helper
0.46
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.559
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.779
TVALTFEXP_TVA->PJM
CLTF
0.76
CPLELTFEXP_CPLE->PJM
CLTF
3.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.141
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.352
MECLTFEXP_MEC->PJM
CLTF
0.255
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B3_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.69 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:910.4
MW Contribution:
23.96
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
24.401
316322AB2-045
Solar/Wind Harmer
1.609
971845AH1-439 GEN
Solar/Wind Harmer
25.005
316258AE1-075 C
Solar/Wind Harmer
0.763
316405AF2-144 C
Solar/Wind Harmer
0.806
946301AF1-294 GEN
Solar/Wind Harmer
6.653
961791AG1-021 GEN
Solar/Wind Harmer
3.245
970683AG2-441 GEN
Solar/Wind Harmer
16.65
970681AG2-440 GEN
Solar/Wind Harmer
11.051
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.451
316239AB2-077_GEN
Solar/Wind Harmer
0.451
316486AD2-202 GEN
Solar/Wind Harmer
0.303
316233AE1-074 FULL
Solar/Wind Harmer
0.277
971281AH1-106 GEN
Solar/Wind Harmer
1.674
971283AH1-107 GEN
Solar/Wind Harmer
1.674
970831AG2-522 GEN
Solar/Wind Harmer
5.074
3151921BEARGRDN G2
50/50
4.994
3144293JTRSVLE
50/50
0.585
972003AH1-546 GEN
Solar/Wind Harmer
23.964
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.022
942461AE2-259 GEN
Solar/Wind Harmer
4.864
3143336POWHATN
Solar/Wind Harmer
3.18
3147133PAMPLIN
Solar/Wind Harmer
-0.086
959311AF2-222 GEN
Solar/Wind Harmer
22.721
970257AG2-171 GEN
Solar/Wind Harmer
7.89
971775AH1-396 GEN
Solar/Wind Harmer
1.485
964241AG1-285 GEN
Solar/Wind Harmer
13.573
316478AD1-087 GEN
Solar/Wind Harmer
1.034
3147043LAWRENC
Solar/Wind Harmer
-0.006
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.173
316181AB2-040 GEN
Solar/Wind Harmer
1.149
971683AH1-343 GEN
Solar/Wind Harmer
3.439
3150861SPRUNCD
Adder
0.323
316190AA2-174 GEN
Solar/Wind Harmer
0.095
970917AG2-570 GEN
Solar/Wind Harmer
18.451
944011AF1-069 GEN
Solar/Wind Harmer
4.319
3156081AA2-088 GEN
Solar/Wind Harmer
2.294
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.461
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
970909AG2-566 GEN
50/50
2.663
3144293JTRSVLE
50/50
0.585
970535AG2-341 GEN
50/50
2.129
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
16.127
946281AF1-292 GEN
Solar/Wind Harmer
0.191
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971285AH1-108 GEN
Adder
0.528
316426AA2-053 GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970673AG2-436 GEN
Solar/Wind Harmer
16.266
970533AG2-339 GEN
Solar/Wind Harmer
4.944
970085AG2-068 GEN
Solar/Wind Harmer
4.553
970581AG2-369 GEN
Solar/Wind Harmer
3.916
316274AC1-208 GEN
Solar/Wind Harmer
0.757
315814AE2-033 C
Solar/Wind Harmer
6.529
315652AC1-086 GEN
Solar/Wind Harmer
7.869
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.079
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.027
316463AE2-346 GEN
Solar/Wind Harmer
0.109
3145513AHOSKIE
Solar/Wind Harmer
0.059
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.67
3143316POE
Solar/Wind Harmer
-0.026
315839AE2-212 C
Solar/Wind Harmer
0.195
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.784
970657AG2-426 GEN
Solar/Wind Harmer
0.401
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
3148463FAIRFLD
Solar/Wind Helper
0.141
315616AA1-038_C
Solar/Wind Helper
0.642
3151931BEARGRDN S1
50/50
6.452
3151911BEARGRDN G1
50/50
4.994
3144293JTRSVLE
50/50
0.585
3144293JTRSVLE
50/50
0.462
970937AG2-583 GEN
Solar/Wind Harmer
35.585
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.022
3143336POWHATN
Solar/Wind Harmer
3.741
971563AH1-280 GEN
Solar/Wind Harmer
3.245
970685AG2-442 GEN
Solar/Wind Harmer
21.59
316034AC1-036 C
Solar/Wind Harmer
0.39
315785AD2-033 C
Solar/Wind Harmer
4.533
316131AB2-060 GEN
Solar/Wind Harmer
1.695
315693AD1-088 GEN
Solar/Wind Harmer
7.541
3143226MDLTHAN
Solar/Wind Harmer
-0.012
970401AG2-262 GEN
Solar/Wind Harmer
0.785
957481AF2-042 GEN
Solar/Wind Harmer
37.288
971065AG2-659 GEN
Solar/Wind Harmer
5.332
3147043LAWRENC
Adder
0.854
316129AC1-054 GEN
Solar/Wind Harmer
0.913
3143526WINTERP
Solar/Wind Harmer
-0.053
960081AF2-299 GEN
Solar/Wind Harmer
0.96
316087AB2-174 GEN
Solar/Wind Harmer
1.187
3150851SPRUNCC
Adder
0.323
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.767
970919AG2-571 GEN
Solar/Wind Harmer
2.336
941031AE2-094 GEN
Solar/Wind Harmer
13.785
970087AG2-069 GEN
Solar/Wind Harmer
6.83
316023GEN1_S
Solar/Wind Harmer
0.487
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
940641AE2-051 GEN
Solar/Wind Harmer
6.432
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3145683EARLEYS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
33.321
3156021HOLLOMANSOL
Solar/Wind Harmer
0.868
316319Z2-044 C
Solar/Wind Harmer
0.356
3146233WITAKRS
Solar/Wind Harmer
-0.026
3143096IRON208
Adder
0.238
315671AE2-027_GEN
Solar/Wind Harmer
1.15
316381AD1-082 GEN
Solar/Wind Harmer
0.583
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.591
3147983MERCK5
Solar/Wind Helper
0.064
3146776BUCKING
Solar/Wind Harmer
-0.191
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
22.829
316313AB2-026
Solar/Wind Harmer
0.848
970301AG2-198 GEN
Solar/Wind Harmer
14.027
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.022
958211AF2-115 GEN
Solar/Wind Harmer
4.057
970323AG2-213 GEN
Solar/Wind Harmer
10.52
313527AB2-043 GEN
Solar/Wind Harmer
2.494
316237AB2-079_GEN
Solar/Wind Harmer
0.451
962561AG1-105 GEN
Solar/Wind Harmer
7.051
971223AH1-071 GEN
Solar/Wind Harmer
1.533
964791AG1-342 GEN
Solar/Wind Harmer
2.569
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.915
316118AC1-105 GEN
Solar/Wind Harmer
0.741
315687AD1-152 GEN
Solar/Wind Harmer
1.294
3143526WINTERP
Solar/Wind Harmer
-0.053
316248AF1-058 C
Solar/Wind Harmer
0.289
970933AG2-581 GEN
Solar/Wind Harmer
8.888
313506AB2-031 GEN
Solar/Wind Harmer
0.662
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.093
972187AH1-678 GEN
Adder
1.941
972185AH1-677 GEN
Adder
3.779
316365GEN2_N
Solar/Wind Harmer
0.487
3144356SAPONY
Solar/Wind Harmer
0.244
316315AB2-025 C
Solar/Wind Harmer
0.188
962571AG1-106 GEN
Solar/Wind Harmer
1.005
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.046
315742AE1-103 GEN
Solar/Wind Harmer
1.569
315724AD1-057 GEN
Solar/Wind Harmer
1.272
316240AF1-291 C
Solar/Wind Harmer
0.192
316083AB2-161 GEN
Solar/Wind Harmer
1.033
944641AF1-129 GEN
Adder
27.005
316065AD1-022 GEN
Solar/Wind Harmer
3.169
966001AG1-469 GEN
Solar/Wind Helper
0.167
3132123MT JACKSON
Solar/Wind Helper
0.376
316212AC1-099_GEN
Solar/Wind Harmer
0.599
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.313
3145823KELFORD
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
2.313
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.135
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.65
3138543CONSLDL
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
4.018
3143096IRON208
Adder
0.238
3143096IRON208
Adder
0.233
3146206CASHIE
Solar/Wind Harmer
-0.006
316283AC2-100 C
Solar/Wind Harmer
0.599
970657AG2-426 GEN
Solar/Wind Harmer
1.285
315821AE2-092 GEN
Solar/Wind Helper
6.554
3148013FISHERV
Solar/Wind Helper
0.273
316499AE2-029_GEN
Solar/Wind Helper
0.588
3132273ORANGE
Solar/Wind Helper
0.023
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.18
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.537
LAGNLTFEXP_LAGN->PJM
CLTF
0.856
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.321
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.399
CPLELTFEXP_CPLE->PJM
CLTF
3.428
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.971
MDUPJM->LTFIMP_MDU
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.118
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.06
NYPJM->LTFIMP_NY
CLTF
0.337

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.52 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:845.12
MW Contribution:
10.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.13 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:841.95
MW Contribution:
10.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
971967AH1-528 GEN
Solar/Wind Harmer
17.83
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970933AG2-581 GEN
Solar/Wind Harmer
8.916
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:174.45 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1183.97
MW Contribution:
16.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.908
3151031BRUNSWICKG2
50/50
1.136
3151261ROARAP2
50/50
0.102
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.202
3151411GASTONB
50/50
0.202
972003AH1-546 GEN
Solar/Wind Harmer
16.566
3146776BUCKING
Solar/Wind Harmer
0.142
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
4.089
3147133PAMPLIN
Solar/Wind Harmer
0.741
959311AF2-222 GEN
Solar/Wind Harmer
16.947
970257AG2-171 GEN
Solar/Wind Harmer
5.92
971775AH1-396 GEN
Solar/Wind Harmer
0.296
964241AG1-285 GEN
Solar/Wind Harmer
10.433
970221AG2-151 GEN
Solar/Wind Harmer
7.011
316478AD1-087 GEN
Solar/Wind Harmer
0.404
3147043LAWRENC
Solar/Wind Harmer
0.063
270494AE1-108_GEN
Solar/Wind Harmer
1.23
316181AB2-040 GEN
Solar/Wind Harmer
0.122
944011AF1-069 GEN
Solar/Wind Harmer
5.111
970917AG2-570 GEN
Solar/Wind Harmer
7.385
971683AH1-343 GEN
Solar/Wind Harmer
2.995
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.37
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
972205AH1-687 GEN
50/50
22.181
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.485
3151601KERR 3
50/50
0.231
3151611KERR 4
50/50
0.231
3151621KERR 5
50/50
0.231
3151631KERR 6
50/50
0.231
963041AG1-153 GEN
50/50
2.3
315244AE2-183_ST
50/50
2.456
3151281ROARAP4
50/50
0.093
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.514
316258AE1-075 C
Solar/Wind Harmer
0.202
946301AF1-294 GEN
Solar/Wind Harmer
4.405
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
12.335
970681AG2-440 GEN
Solar/Wind Harmer
8.187
3144303KENBRDG
Solar/Wind Harmer
0.148
316486AD2-202 GEN
Solar/Wind Harmer
0.119
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
970831AG2-522 GEN
Solar/Wind Harmer
4.275
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.957
970673AG2-436 GEN
Solar/Wind Harmer
10.614
970533AG2-339 GEN
Solar/Wind Harmer
6.417
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.374
970581AG2-369 GEN
Solar/Wind Harmer
3.761
316426AA2-053 GEN
Solar/Wind Harmer
0.271
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.194
315652AC1-086 GEN
Solar/Wind Harmer
8.309
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
316274AC1-208 GEN
Solar/Wind Harmer
0.387
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
316210AC1-098 GEN
Solar/Wind Harmer
0.683
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
316463AE2-346 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
0.154
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.106
970657AG2-426 GEN
Solar/Wind Harmer
0.518
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.621
316311AC2-079 GEN
Solar/Wind Harmer
2.01
315732AD1-074 GEN1
Solar/Wind Harmer
0.397
315733AD1-074 GEN2
Solar/Wind Harmer
0.397
3130546PLYMOUTH
Solar/Wind Harmer
0.07
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
957871AF2-081 GEN
Solar/Wind Harmer
3.42
316316AC1-027 C
Solar/Wind Harmer
0.065
3151081ELIZAR1
Adder
6.27
3151091ELIZAR2
Adder
6.161
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
957861AF2-080 GEN
Solar/Wind Harmer
2.904
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
971445AH1-216 GEN
Solar/Wind Harmer
4.705
3151201GRAVEL4
Adder
4.805
3151221GRAVEL6
Adder
4.799
3151191GRAVEL3
Adder
4.744
3151211GRAVEL5
Adder
4.744
315697AD1-025 GEN
Solar/Wind Harmer
0.071
316159AE1-175 C
Solar/Wind Harmer
0.049
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.1
3148463FAIRFLD
Solar/Wind Helper
0.12
315616AA1-038_C
Solar/Wind Helper
0.545
970909AG2-566 GEN
50/50
2.566
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.241
3151581KERR 1
50/50
0.082
3152661PLYWOOD A
50/50
0.224
3151041BRUNSWICKG3
50/50
1.136
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.414
315241AE2-183_GT1
50/50
1.41
972185AH1-677 GEN
50/50
5.112
3151261ROARAP2
50/50
0.1
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
316336AC2-165 C
Solar/Wind Harmer
15.638
316313AB2-026
Solar/Wind Harmer
0.168
970301AG2-198 GEN
Solar/Wind Harmer
10.263
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.679
970323AG2-213 GEN
Solar/Wind Harmer
7.893
971223AH1-071 GEN
Solar/Wind Harmer
1.335
962561AG1-105 GEN
Solar/Wind Harmer
5.682
970099AG2-077 GEN
Solar/Wind Harmer
12.508
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
316118AC1-105 GEN
Solar/Wind Harmer
0.268
970933AG2-581 GEN
Solar/Wind Harmer
7.997
313506AB2-031 GEN
Solar/Wind Harmer
0.263
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316365GEN2_N
Solar/Wind Harmer
0.174
3144356SAPONY
Solar/Wind Harmer
0.654
316315AB2-025 C
Solar/Wind Harmer
0.063
962571AG1-106 GEN
Solar/Wind Harmer
1.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316140AB2-099
Solar/Wind Harmer
0.026
315742AE1-103 GEN
Solar/Wind Harmer
1.084
315724AD1-057 GEN
Solar/Wind Harmer
1.363
316349AD2-085 GEN
Solar/Wind Harmer
0.047
316065AD1-022 GEN
Solar/Wind Harmer
3.224
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315614AA2-178 GEN
Solar/Wind Harmer
0.395
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146386ELIZ CT
Solar/Wind Harmer
0.069
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.216
316339AD2-160 GEN
Solar/Wind Harmer
0.11
316388AE2-253 GEN
Solar/Wind Harmer
0.214
3145506HICKORY
Solar/Wind Harmer
0.274
3151931BEARGRDN S1
50/50
5.865
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.682
3151531CLOVER1
50/50
2.505
3151591KERR 2
50/50
0.231
3151641KERR 7
50/50
0.231
3147043LAWRENC
50/50
1.001
3151051BRUNSWICKS1
50/50
2.358
3151021BRUNSWICKG1
50/50
1.136
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.414
3151281ROARAP4
50/50
0.099
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.202
3151411GASTONB
50/50
0.202
970937AG2-583 GEN
Solar/Wind Harmer
24.929
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
3143336POWHATN
Solar/Wind Harmer
4.81
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.92
316034AC1-036 C
Solar/Wind Harmer
0.012
315785AD2-033 C
Solar/Wind Harmer
1.433
316131AB2-060 GEN
Solar/Wind Harmer
0.448
315693AD1-088 GEN
Solar/Wind Harmer
6.777
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.271
970401AG2-262 GEN
Solar/Wind Harmer
0.671
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.447
316129AC1-054 GEN
Solar/Wind Harmer
0.383
960081AF2-299 GEN
Solar/Wind Harmer
0.847
941031AE2-094 GEN
Solar/Wind Harmer
15.643
970919AG2-571 GEN
Solar/Wind Harmer
2.954
970087AG2-069 GEN
Solar/Wind Harmer
6.56
3145783HORNRTN
Solar/Wind Harmer
0.082
940641AE2-051 GEN
Solar/Wind Harmer
6.46
315607AA1-063A GEN
Solar/Wind Harmer
0.162
316023GEN1_S
Solar/Wind Harmer
0.174
939411AE1-173 GEN
Solar/Wind Harmer
33.164
3146263WOODLND
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.335
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3156021HOLLOMANSOL
Solar/Wind Harmer
0.319
316381AD1-082 GEN
Solar/Wind Harmer
0.072
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.498
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
315737AD1-076 GEN
Solar/Wind Harmer
0.894
316093AE2-104_GEN
Solar/Wind Harmer
1.171
315816AE2-034 GEN
Solar/Wind Harmer
0.297
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
0.073
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.785
315722AD1-056 GEN
Solar/Wind Harmer
2.443
970657AG2-426 GEN
Solar/Wind Harmer
1.583
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315735AD1-075 GEN1
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.012
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
316017AA1-139 ULT1
Solar/Wind Harmer
0.037
944581AF1-123 GEN
Solar/Wind Harmer
15.462
944601AF1-125 GEN
Solar/Wind Harmer
15.223
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.35
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
316222AC1-221 GEN
Solar/Wind Harmer
0.281
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.514
316049AB1-081 GEN
Solar/Wind Harmer
0.387
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
316294AC1-161 GEN
Solar/Wind Harmer
1.166
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316005AA1-067
Solar/Wind Harmer
0.072
316033AB2-134 GEN
Solar/Wind Harmer
0
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.196
3150701DARBY 4
Adder
4.186
3150681DARBY 2
Adder
4.181
3150671DARBY 1
Adder
4.176
942751AE2-291 GEN
Solar/Wind Harmer
3.156
966001AG1-469 GEN
Solar/Wind Helper
0.19
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.559
3130156CHOWAN
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
0
319010AE1-072 C
Solar/Wind Harmer
0.343
3146456SLIGO L269
Solar/Wind Harmer
0.069
944591AF1-124 GEN
Solar/Wind Harmer
15.516
3145963POPLR C
Solar/Wind Harmer
0.069
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.012
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.242
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.024
3146293MARTNCO
Solar/Wind Harmer
0.063
315773AC2-141 GEN
Solar/Wind Harmer
2.463
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.228
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.458
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316132AB2-190 GEN1
Solar/Wind Harmer
0.351
944631AF1-128 GEN
Adder
29.459
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.825
3147666LOUISA
Solar/Wind Helper
0.474
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
4.809
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.263
316458AB2-190 GEN2
Solar/Wind Harmer
0.351
970133AG2-095 GEN
Solar/Wind Harmer
0.63
316123AC1-075 GEN
Solar/Wind Harmer
0.087
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.513
3132273ORANGE
Solar/Wind Helper
0.027
3147666LOUISA
Solar/Wind Helper
0.273
LAGNLTFEXP_LAGN->PJM
CLTF
1.785
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.539
TVALTFEXP_TVA->PJM
CLTF
0.872
CPLELTFEXP_CPLE->PJM
CLTF
4.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.299
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.732
MECLTFEXP_MEC->PJM
CLTF
0.357
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.578
LGEELTFEXP_LGEE->PJM
CLTF
0.049
WECLTFEXP_WEC->PJM
CLTF
0.019

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.24 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1429.6
MW Contribution:
21.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.147
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.483
3151601KERR 3
50/50
0.23
3151611KERR 4
50/50
0.23
3151621KERR 5
50/50
0.23
3151631KERR 6
50/50
0.23
316322AB2-045
Solar/Wind Harmer
1.48
971845AH1-439 GEN
Solar/Wind Harmer
23.026
316258AE1-075 C
Solar/Wind Harmer
0.735
316405AF2-144 C
Solar/Wind Harmer
0.776
946301AF1-294 GEN
Solar/Wind Harmer
6.418
961791AG1-021 GEN
Solar/Wind Harmer
3.131
970683AG2-441 GEN
Solar/Wind Harmer
16.22
970681AG2-440 GEN
Solar/Wind Harmer
10.765
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.466
316239AB2-077_GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.331
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
970831AG2-522 GEN
Solar/Wind Harmer
5.623
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.736
946281AF1-292 GEN
Solar/Wind Harmer
0.222
970673AG2-436 GEN
Solar/Wind Harmer
20.955
970533AG2-339 GEN
Solar/Wind Harmer
6.415
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.755
970581AG2-369 GEN
Solar/Wind Harmer
4.95
971285AH1-108 GEN
Adder
0.613
316426AA2-053 GEN
Solar/Wind Harmer
0.917
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.191
315652AC1-086 GEN
Solar/Wind Harmer
9.547
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.3
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
316463AE2-346 GEN
Solar/Wind Harmer
0.133
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.811
315839AE2-212 C
Solar/Wind Harmer
0.239
970657AG2-426 GEN
Solar/Wind Harmer
0.5
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.45
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316311AC2-079 GEN
Solar/Wind Harmer
3.969
315732AD1-074 GEN1
Solar/Wind Harmer
1.58
315733AD1-074 GEN2
Solar/Wind Harmer
1.58
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.922
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
313526AB2-022
Solar/Wind Harmer
0.208
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.66
957871AF2-081 GEN
Solar/Wind Harmer
3.861
316316AC1-027 C
Solar/Wind Harmer
0.236
3151081ELIZAR1
Adder
6.273
3151091ELIZAR2
Adder
6.164
316174AB2-169 GEN
Solar/Wind Harmer
1.183
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
957861AF2-080 GEN
Solar/Wind Harmer
3.309
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
316236AE1-162_GEN
Solar/Wind Harmer
0.226
971445AH1-216 GEN
Solar/Wind Harmer
4.649
3151201GRAVEL4
Adder
4.808
3151221GRAVEL6
Adder
4.802
3151191GRAVEL3
Adder
4.747
3151211GRAVEL5
Adder
4.747
315697AD1-025 GEN
Solar/Wind Harmer
1.494
316382AG1-145 C
Solar/Wind Harmer
0.195
316159AE1-175 C
Solar/Wind Harmer
0.174
957831AF2-077 GEN
Solar/Wind Harmer
0.193
3138283WHITEMARSH
Solar/Wind Harmer
0.01
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
315616AA1-038_C
Solar/Wind Helper
0.549
3151921BEARGRDN G2
50/50
4.533
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.896
972003AH1-546 GEN
Solar/Wind Harmer
21.779
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.602
3143336POWHATN
Solar/Wind Harmer
3.063
3147133PAMPLIN
Solar/Wind Harmer
-0.083
959311AF2-222 GEN
Solar/Wind Harmer
22.328
970257AG2-171 GEN
Solar/Wind Harmer
7.784
971775AH1-396 GEN
Solar/Wind Harmer
1.465
964241AG1-285 GEN
Solar/Wind Harmer
13.72
970221AG2-151 GEN
Solar/Wind Harmer
9.179
316478AD1-087 GEN
Solar/Wind Harmer
1.131
3147043LAWRENC
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Harmer
2.99
316003AC1-222 GEN
Solar/Wind Harmer
0.97
966621AG1-532 GEN
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
1.34
944011AF1-069 GEN
Solar/Wind Harmer
5.605
970917AG2-570 GEN
Solar/Wind Harmer
23.325
3150861SPRUNCD
Adder
0.375
971683AH1-343 GEN
Solar/Wind Harmer
3.936
316190AA2-174 GEN
Solar/Wind Harmer
0.112
3156081AA2-088 GEN
Solar/Wind Harmer
2.772
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.772
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.722
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.986
315722AD1-056 GEN
Solar/Wind Harmer
2.825
970657AG2-426 GEN
Solar/Wind Harmer
1.602
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.79
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.208
316305AF2-043 C
Solar/Wind Harmer
0.233
970909AG2-566 GEN
50/50
2.562
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.238
3151581KERR 1
50/50
0.082
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
21.624
316313AB2-026
Solar/Wind Harmer
0.817
970301AG2-198 GEN
Solar/Wind Harmer
13.495
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
970323AG2-213 GEN
Solar/Wind Harmer
10.378
313527AB2-043 GEN
Solar/Wind Harmer
2.566
316237AB2-079_GEN
Solar/Wind Harmer
0.466
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.472
970099AG2-077 GEN
Solar/Wind Harmer
16.454
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
315687AD1-152 GEN
Solar/Wind Harmer
1.429
3143526WINTERP
Solar/Wind Harmer
-0.061
316118AC1-105 GEN
Solar/Wind Harmer
0.805
970933AG2-581 GEN
Solar/Wind Harmer
10.522
316248AF1-058 C
Solar/Wind Harmer
0.321
972187AH1-678 GEN
Adder
2.455
972185AH1-677 GEN
Adder
4.816
313506AB2-031 GEN
Solar/Wind Harmer
0.771
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316365GEN2_N
Solar/Wind Harmer
0.593
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.236
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.055
315742AE1-103 GEN
Solar/Wind Harmer
1.935
316083AB2-161 GEN
Solar/Wind Harmer
1.287
315724AD1-057 GEN
Solar/Wind Harmer
1.554
316349AD2-085 GEN
Solar/Wind Harmer
0.699
316065AD1-022 GEN
Solar/Wind Harmer
3.933
315835AF2-110_GEN
Solar/Wind Harmer
0.979
315614AA2-178 GEN
Solar/Wind Harmer
0.84
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316435W1029_GEN3
Solar/Wind Harmer
1.405
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316240AF1-291 C
Solar/Wind Harmer
0.233
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316388AE2-253 GEN
Solar/Wind Harmer
0.519
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.811
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.538
316049AB1-081 GEN
Solar/Wind Harmer
0.822
316263AC1-034 GEN
Solar/Wind Harmer
3.582
316294AC1-161 GEN
Solar/Wind Harmer
2.453
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
2.985
3145493TOT1
Solar/Wind Harmer
0.117
3145453TOT5
Solar/Wind Harmer
0.07
3145603CNETO
Solar/Wind Harmer
0.047
316005AA1-067
Solar/Wind Harmer
0.152
316033AB2-134 GEN
Solar/Wind Harmer
2.383
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
-0.001
3150691DARBY 3
Adder
4.202
3150701DARBY 4
Adder
4.192
3150681DARBY 2
Adder
4.188
3150671DARBY 1
Adder
4.183
942751AE2-291 GEN
Solar/Wind Harmer
4.144
966001AG1-469 GEN
Solar/Wind Helper
0.199
316246AF1-032 C
Solar/Wind Harmer
0.156
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.894
316017AA1-139 ULT1
Solar/Wind Harmer
0.623
944581AF1-123 GEN
Solar/Wind Harmer
35.113
944601AF1-125 GEN
Solar/Wind Harmer
34.565
3145963POPLR C
Solar/Wind Harmer
-0.008
3142956BIRDNECK
Solar/Wind Harmer
0.413
3151101ELIZAR3
Adder
6.353
3144873MCLAUGH
Solar/Wind Harmer
0
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Harmer
0.772
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.022
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
316420AA1-050 GEN
Solar/Wind Harmer
0.862
316283AC2-100 C
Solar/Wind Harmer
0.713
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.003
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151171GRAVELC
Adder
0.924
961611AG1-000B GEN
Solar/Wind Harmer
1.561
315778AD1-151 GEN
Solar/Wind Harmer
6.583
316458AB2-190 GEN2
Solar/Wind Harmer
0.745
970133AG2-095 GEN
Solar/Wind Harmer
0.83
316123AC1-075 GEN
Solar/Wind Harmer
0.79
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.527
3142946ENON
Solar/Wind Harmer
-0.002
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
3151931BEARGRDN S1
50/50
5.856
3151911BEARGRDN G1
50/50
4.533
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.674
3151531CLOVER1
50/50
2.502
3151591KERR 2
50/50
0.23
3151641KERR 7
50/50
0.23
970937AG2-583 GEN
Solar/Wind Harmer
32.775
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.603
971563AH1-280 GEN
Solar/Wind Harmer
3.131
970685AG2-442 GEN
Solar/Wind Harmer
20.933
316034AC1-036 C
Solar/Wind Harmer
0.384
315785AD2-033 C
Solar/Wind Harmer
4.498
316131AB2-060 GEN
Solar/Wind Harmer
1.738
315693AD1-088 GEN
Solar/Wind Harmer
7.923
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.134
970401AG2-262 GEN
Solar/Wind Harmer
0.837
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.849
316129AC1-054 GEN
Solar/Wind Harmer
1.005
960081AF2-299 GEN
Solar/Wind Harmer
1.114
316087AB2-174 GEN
Solar/Wind Harmer
1.383
941031AE2-094 GEN
Solar/Wind Harmer
17.887
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
8.633
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
940641AE2-051 GEN
Solar/Wind Harmer
8.505
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316023GEN1_S
Solar/Wind Harmer
0.593
939411AE1-173 GEN
Solar/Wind Harmer
43.668
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.071
316381AD1-082 GEN
Solar/Wind Harmer
0.726
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.972
316319Z2-044 C
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.031
315737AD1-076 GEN
Solar/Wind Harmer
1.485
316093AE2-104_GEN
Solar/Wind Harmer
2.276
315816AE2-034 GEN
Solar/Wind Harmer
0.63
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.32
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.922
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.398
319010AE1-072 C
Solar/Wind Harmer
1.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
944591AF1-124 GEN
Solar/Wind Harmer
35.239
3145963POPLR C
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.657
316036AC1-147 C
Solar/Wind Harmer
0.207
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.09
316072AD1-144
Solar/Wind Harmer
0.154
315773AC2-141 GEN
Solar/Wind Harmer
3.174
3146293MARTNCO
Solar/Wind Harmer
0.047
961671AG1-007 GEN
Solar/Wind Harmer
0.096
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.225
316494AC1-189 GEN
Solar/Wind Harmer
0.814
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.03
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.703
961611AG1-000B GEN
Solar/Wind Harmer
3.659
316369SG1_INVT
Solar/Wind Harmer
1.32
971069AG2-661 GEN
Solar/Wind Harmer
1.17
316132AB2-190 GEN1
Solar/Wind Harmer
0.745
944631AF1-128 GEN
Adder
29.493
3138126ROCKLANDING
Solar/Wind Harmer
0.021
971317AH1-138 GEN
Solar/Wind Harmer
0.826
3142433PROV 92
Solar/Wind Harmer
-0.025
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.929
3147666LOUISA
Solar/Wind Helper
0.538
LAGNLTFEXP_LAGN->PJM
CLTF
1.773
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.519
TVALTFEXP_TVA->PJM
CLTF
0.866
CPLELTFEXP_CPLE->PJM
CLTF
4.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.225
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.709
MECLTFEXP_MEC->PJM
CLTF
0.349
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.017

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.24 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1429.58
MW Contribution:
21.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.147
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.483
3151601KERR 3
50/50
0.23
3151611KERR 4
50/50
0.23
3151621KERR 5
50/50
0.23
3151631KERR 6
50/50
0.23
316322AB2-045
Solar/Wind Harmer
1.48
971845AH1-439 GEN
Solar/Wind Harmer
23.025
316258AE1-075 C
Solar/Wind Harmer
0.735
316405AF2-144 C
Solar/Wind Harmer
0.776
946301AF1-294 GEN
Solar/Wind Harmer
6.418
961791AG1-021 GEN
Solar/Wind Harmer
3.131
970683AG2-441 GEN
Solar/Wind Harmer
16.219
970681AG2-440 GEN
Solar/Wind Harmer
10.765
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.466
316239AB2-077_GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.331
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
970831AG2-522 GEN
Solar/Wind Harmer
5.623
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.736
946281AF1-292 GEN
Solar/Wind Harmer
0.222
970673AG2-436 GEN
Solar/Wind Harmer
20.955
970533AG2-339 GEN
Solar/Wind Harmer
6.415
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.755
970581AG2-369 GEN
Solar/Wind Harmer
4.95
971285AH1-108 GEN
Adder
0.613
316426AA2-053 GEN
Solar/Wind Harmer
0.917
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.191
315652AC1-086 GEN
Solar/Wind Harmer
9.547
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.3
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
316463AE2-346 GEN
Solar/Wind Harmer
0.133
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.811
315839AE2-212 C
Solar/Wind Harmer
0.239
970657AG2-426 GEN
Solar/Wind Harmer
0.5
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.45
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316311AC2-079 GEN
Solar/Wind Harmer
3.969
315732AD1-074 GEN1
Solar/Wind Harmer
1.58
315733AD1-074 GEN2
Solar/Wind Harmer
1.58
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.922
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
313526AB2-022
Solar/Wind Harmer
0.208
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.66
957871AF2-081 GEN
Solar/Wind Harmer
3.861
316316AC1-027 C
Solar/Wind Harmer
0.236
3151081ELIZAR1
Adder
6.273
3151091ELIZAR2
Adder
6.164
316174AB2-169 GEN
Solar/Wind Harmer
1.183
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
957861AF2-080 GEN
Solar/Wind Harmer
3.309
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
316236AE1-162_GEN
Solar/Wind Harmer
0.226
971445AH1-216 GEN
Solar/Wind Harmer
4.649
3151201GRAVEL4
Adder
4.808
3151221GRAVEL6
Adder
4.802
3151191GRAVEL3
Adder
4.747
3151211GRAVEL5
Adder
4.747
315697AD1-025 GEN
Solar/Wind Harmer
1.494
316382AG1-145 C
Solar/Wind Harmer
0.195
316159AE1-175 C
Solar/Wind Harmer
0.174
957831AF2-077 GEN
Solar/Wind Harmer
0.193
3138283WHITEMARSH
Solar/Wind Harmer
0.01
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
315616AA1-038_C
Solar/Wind Helper
0.549
3151921BEARGRDN G2
50/50
4.532
3144293JTRSVLE
50/50
0.565
970413AG2-270 GEN
50/50
10.896
972003AH1-546 GEN
Solar/Wind Harmer
21.778
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.602
3143336POWHATN
Solar/Wind Harmer
3.063
3147133PAMPLIN
Solar/Wind Harmer
-0.083
959311AF2-222 GEN
Solar/Wind Harmer
22.328
970257AG2-171 GEN
Solar/Wind Harmer
7.784
971775AH1-396 GEN
Solar/Wind Harmer
1.464
964241AG1-285 GEN
Solar/Wind Harmer
13.72
970221AG2-151 GEN
Solar/Wind Harmer
9.179
316478AD1-087 GEN
Solar/Wind Harmer
1.131
3147043LAWRENC
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Harmer
2.99
316003AC1-222 GEN
Solar/Wind Harmer
0.97
966621AG1-532 GEN
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
1.34
944011AF1-069 GEN
Solar/Wind Harmer
5.605
970917AG2-570 GEN
Solar/Wind Harmer
23.325
3150861SPRUNCD
Adder
0.375
971683AH1-343 GEN
Solar/Wind Harmer
3.936
316190AA2-174 GEN
Solar/Wind Harmer
0.112
3156081AA2-088 GEN
Solar/Wind Harmer
2.772
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.772
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.722
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.986
315722AD1-056 GEN
Solar/Wind Harmer
2.825
970657AG2-426 GEN
Solar/Wind Harmer
1.602
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.79
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.208
316305AF2-043 C
Solar/Wind Harmer
0.233
316246AF1-032 C
Solar/Wind Harmer
0.156
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.894
316017AA1-139 ULT1
Solar/Wind Harmer
0.623
944581AF1-123 GEN
Solar/Wind Harmer
35.113
944601AF1-125 GEN
Solar/Wind Harmer
34.565
3145963POPLR C
Solar/Wind Harmer
-0.008
3142956BIRDNECK
Solar/Wind Harmer
0.413
3151101ELIZAR3
Adder
6.353
3144873MCLAUGH
Solar/Wind Harmer
0
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Harmer
0.772
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.022
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
316420AA1-050 GEN
Solar/Wind Harmer
0.862
316283AC2-100 C
Solar/Wind Harmer
0.713
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.003
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151171GRAVELC
Adder
0.924
961611AG1-000B GEN
Solar/Wind Harmer
1.561
315778AD1-151 GEN
Solar/Wind Harmer
6.583
316458AB2-190 GEN2
Solar/Wind Harmer
0.745
970133AG2-095 GEN
Solar/Wind Harmer
0.83
316123AC1-075 GEN
Solar/Wind Harmer
0.79
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.527
3142946ENON
Solar/Wind Harmer
-0.002
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
970909AG2-566 GEN
50/50
2.562
3144293JTRSVLE
50/50
0.565
970535AG2-341 GEN
50/50
2.238
3151581KERR 1
50/50
0.082
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
21.623
316313AB2-026
Solar/Wind Harmer
0.817
970301AG2-198 GEN
Solar/Wind Harmer
13.494
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
970323AG2-213 GEN
Solar/Wind Harmer
10.378
313527AB2-043 GEN
Solar/Wind Harmer
2.566
316237AB2-079_GEN
Solar/Wind Harmer
0.466
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.472
970099AG2-077 GEN
Solar/Wind Harmer
16.454
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
315687AD1-152 GEN
Solar/Wind Harmer
1.429
3143526WINTERP
Solar/Wind Harmer
-0.061
316118AC1-105 GEN
Solar/Wind Harmer
0.805
970933AG2-581 GEN
Solar/Wind Harmer
10.522
316248AF1-058 C
Solar/Wind Harmer
0.321
972187AH1-678 GEN
Adder
2.455
972185AH1-677 GEN
Adder
4.816
313506AB2-031 GEN
Solar/Wind Harmer
0.771
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316365GEN2_N
Solar/Wind Harmer
0.593
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.236
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.055
315742AE1-103 GEN
Solar/Wind Harmer
1.935
316083AB2-161 GEN
Solar/Wind Harmer
1.287
315724AD1-057 GEN
Solar/Wind Harmer
1.554
316349AD2-085 GEN
Solar/Wind Harmer
0.699
316065AD1-022 GEN
Solar/Wind Harmer
3.933
315835AF2-110_GEN
Solar/Wind Harmer
0.979
315614AA2-178 GEN
Solar/Wind Harmer
0.84
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316435W1029_GEN3
Solar/Wind Harmer
1.405
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316240AF1-291 C
Solar/Wind Harmer
0.233
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316388AE2-253 GEN
Solar/Wind Harmer
0.519
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.811
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.539
316049AB1-081 GEN
Solar/Wind Harmer
0.822
316263AC1-034 GEN
Solar/Wind Harmer
3.582
316294AC1-161 GEN
Solar/Wind Harmer
2.453
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
2.985
3145493TOT1
Solar/Wind Harmer
0.117
3145453TOT5
Solar/Wind Harmer
0.07
3145603CNETO
Solar/Wind Harmer
0.047
316005AA1-067
Solar/Wind Harmer
0.152
316033AB2-134 GEN
Solar/Wind Harmer
2.383
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
-0.001
3150691DARBY 3
Adder
4.202
3150701DARBY 4
Adder
4.193
3150681DARBY 2
Adder
4.188
3150671DARBY 1
Adder
4.183
942751AE2-291 GEN
Solar/Wind Harmer
4.144
966001AG1-469 GEN
Solar/Wind Helper
0.199
3151931BEARGRDN S1
50/50
5.856
3151911BEARGRDN G1
50/50
4.532
3144293JTRSVLE
50/50
0.565
3144293JTRSVLE
50/50
0.446
970119AG2-088 GEN
50/50
16.674
3151531CLOVER1
50/50
2.502
3151591KERR 2
50/50
0.23
3151641KERR 7
50/50
0.23
970937AG2-583 GEN
Solar/Wind Harmer
32.775
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.603
971563AH1-280 GEN
Solar/Wind Harmer
3.131
970685AG2-442 GEN
Solar/Wind Harmer
20.932
316034AC1-036 C
Solar/Wind Harmer
0.384
315785AD2-033 C
Solar/Wind Harmer
4.498
316131AB2-060 GEN
Solar/Wind Harmer
1.738
315693AD1-088 GEN
Solar/Wind Harmer
7.923
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.134
970401AG2-262 GEN
Solar/Wind Harmer
0.837
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.849
316129AC1-054 GEN
Solar/Wind Harmer
1.005
960081AF2-299 GEN
Solar/Wind Harmer
1.114
316087AB2-174 GEN
Solar/Wind Harmer
1.383
941031AE2-094 GEN
Solar/Wind Harmer
17.887
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
8.633
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
940641AE2-051 GEN
Solar/Wind Harmer
8.505
315607AA1-063A GEN
Solar/Wind Harmer
0.909
316023GEN1_S
Solar/Wind Harmer
0.593
939411AE1-173 GEN
Solar/Wind Harmer
43.668
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.071
316381AD1-082 GEN
Solar/Wind Harmer
0.726
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.972
316319Z2-044 C
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.031
315737AD1-076 GEN
Solar/Wind Harmer
1.485
316093AE2-104_GEN
Solar/Wind Harmer
2.276
315816AE2-034 GEN
Solar/Wind Harmer
0.63
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.32
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.922
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.398
319010AE1-072 C
Solar/Wind Harmer
1.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
944591AF1-124 GEN
Solar/Wind Harmer
35.239
3145963POPLR C
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.657
316036AC1-147 C
Solar/Wind Harmer
0.207
3150981CHESPKA
Adder
0.854
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.09
316072AD1-144
Solar/Wind Harmer
0.154
315773AC2-141 GEN
Solar/Wind Harmer
3.174
3146293MARTNCO
Solar/Wind Harmer
0.047
961671AG1-007 GEN
Solar/Wind Harmer
0.096
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.225
316494AC1-189 GEN
Solar/Wind Harmer
0.814
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145336SMITFLD
Solar/Wind Harmer
-0.03
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.703
961611AG1-000B GEN
Solar/Wind Harmer
3.659
316369SG1_INVT
Solar/Wind Harmer
1.32
971069AG2-661 GEN
Solar/Wind Harmer
1.17
316132AB2-190 GEN1
Solar/Wind Harmer
0.745
944631AF1-128 GEN
Adder
29.493
3138126ROCKLANDING
Solar/Wind Harmer
0.021
971317AH1-138 GEN
Solar/Wind Harmer
0.826
3142433PROV 92
Solar/Wind Harmer
-0.025
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.93
3147666LOUISA
Solar/Wind Helper
0.539
LAGNLTFEXP_LAGN->PJM
CLTF
1.773
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.519
TVALTFEXP_TVA->PJM
CLTF
0.866
CPLELTFEXP_CPLE->PJM
CLTF
4.347
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.224
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.709
MECLTFEXP_MEC->PJM
CLTF
0.349
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.017

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.58 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1324.55
MW Contribution:
22.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.443
316303AF2-085
50/50
2.628
316322AB2-045
Solar/Wind Harmer
1.492
971845AH1-439 GEN
Solar/Wind Harmer
23.204
316258AE1-075 C
Solar/Wind Harmer
0.779
316405AF2-144 C
Solar/Wind Harmer
0.823
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
16.031
970681AG2-440 GEN
Solar/Wind Harmer
10.64
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.235
971283AH1-107 GEN
Solar/Wind Harmer
2.235
316486AD2-202 GEN
Solar/Wind Harmer
0.313
970831AG2-522 GEN
Solar/Wind Harmer
5.345
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
17.883
946281AF1-292 GEN
Solar/Wind Harmer
0.209
3137643SOCKMAN
Solar/Wind Harmer
-0.035
316426AA2-053 GEN
Solar/Wind Harmer
0.86
970673AG2-436 GEN
Solar/Wind Harmer
18.644
970533AG2-339 GEN
Solar/Wind Harmer
5.691
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.171
970581AG2-369 GEN
Solar/Wind Harmer
4.447
315814AE2-033 C
Solar/Wind Harmer
7.589
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.891
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.846
315839AE2-212 C
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.212
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
0.476
316327AA2-057 GEN
Solar/Wind Harmer
0.754
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316311AC2-079 GEN
Solar/Wind Harmer
3.723
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.198
315697AD1-025 GEN
Solar/Wind Harmer
1.465
315732AD1-074 GEN1
Solar/Wind Harmer
1.463
315733AD1-074 GEN2
Solar/Wind Harmer
1.463
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.777
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.192
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
316174AB2-169 GEN
Solar/Wind Harmer
1.095
316316AC1-027 C
Solar/Wind Harmer
0.218
3151201GRAVEL4
Adder
4.604
3151221GRAVEL6
Adder
4.599
3151191GRAVEL3
Adder
4.546
3151211GRAVEL5
Adder
4.546
316236AE1-162_GEN
Solar/Wind Harmer
0.214
971445AH1-216 GEN
Solar/Wind Harmer
4.396
3151081ELIZAR1
Adder
5.794
3151091ELIZAR2
Adder
5.693
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.064
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3151921BEARGRDN G2
50/50
4.593
3144293JTRSVLE
50/50
0.56
972003AH1-546 GEN
Solar/Wind Harmer
22.059
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.593
3147133PAMPLIN
Solar/Wind Harmer
-0.082
959311AF2-222 GEN
Solar/Wind Harmer
22.005
970257AG2-171 GEN
Solar/Wind Harmer
7.662
971775AH1-396 GEN
Solar/Wind Harmer
1.442
964241AG1-285 GEN
Solar/Wind Harmer
13.399
970221AG2-151 GEN
Solar/Wind Harmer
9.591
316478AD1-087 GEN
Solar/Wind Harmer
1.07
270494AE1-108_GEN
Solar/Wind Harmer
3.119
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.922
966621AG1-532 GEN
Solar/Wind Harmer
0.189
316181AB2-040 GEN
Solar/Wind Harmer
1.26
971683AH1-343 GEN
Solar/Wind Harmer
3.742
316190AA2-174 GEN
Solar/Wind Harmer
0.105
944011AF1-069 GEN
Solar/Wind Harmer
4.972
970917AG2-570 GEN
Solar/Wind Harmer
20.942
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.588
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.651
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.673
315813AE1-149 C
Solar/Wind Harmer
4.802
316317KELFORD C
Solar/Wind Harmer
0.354
3145823KELFORD
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
1.525
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.838
315722AD1-056 GEN
Solar/Wind Harmer
2.623
316458AB2-190 GEN2
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.494
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.731
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
1.509
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
316321Z2-027
Solar/Wind Harmer
0.192
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.007
970909AG2-566 GEN
50/50
2.539
3144293JTRSVLE
50/50
0.56
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.646
316313AB2-026
Solar/Wind Harmer
0.866
970301AG2-198 GEN
Solar/Wind Harmer
13.373
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
970323AG2-213 GEN
Solar/Wind Harmer
10.216
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.492
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.197
970099AG2-077 GEN
Solar/Wind Harmer
15.506
964791AG1-342 GEN
Solar/Wind Harmer
2.635
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
315687AD1-152 GEN
Solar/Wind Harmer
1.352
316118AC1-105 GEN
Solar/Wind Harmer
0.77
970933AG2-581 GEN
Solar/Wind Harmer
9.651
316248AF1-058 C
Solar/Wind Harmer
0.305
313506AB2-031 GEN
Solar/Wind Harmer
0.725
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.303
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.552
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.038
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.802
316083AB2-161 GEN
Solar/Wind Harmer
1.227
316349AD2-085 GEN
Solar/Wind Harmer
0.655
315724AD1-057 GEN
Solar/Wind Harmer
1.443
316065AD1-022 GEN
Solar/Wind Harmer
3.644
315835AF2-110_GEN
Solar/Wind Harmer
0.909
316033AB2-134 GEN
Solar/Wind Harmer
2.337
3142366NRTHEST
Adder
0.21
315614AA2-178 GEN
Solar/Wind Harmer
0.777
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
316435W1029_GEN3
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
316049AB1-081 GEN
Solar/Wind Harmer
0.762
316263AC1-034 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
2.766
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3150691DARBY 3
Adder
4.503
3150701DARBY 4
Adder
4.493
3150681DARBY 2
Adder
4.488
3150671DARBY 1
Adder
4.482
3145493TOT1
Solar/Wind Harmer
0.109
3145453TOT5
Solar/Wind Harmer
0.065
3145603CNETO
Solar/Wind Harmer
0.043
316005AA1-067
Solar/Wind Harmer
0.141
316294AC1-161 GEN
Solar/Wind Harmer
2.243
3142946ENON
Solar/Wind Harmer
-0.001
966001AG1-469 GEN
Solar/Wind Helper
0.186
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
3142956BIRDNECK
Solar/Wind Harmer
0.381
3144873MCLAUGH
Solar/Wind Harmer
0
3151171GRAVELC
Adder
0.885
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.868
944581AF1-123 GEN
Solar/Wind Harmer
32.275
944601AF1-125 GEN
Solar/Wind Harmer
31.771
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.664
961601AG1-000A GEN
Solar/Wind Harmer
2.801
3145933PARMELE
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.799
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.751
3142946ENON
Solar/Wind Harmer
-0.002
970293AG2-193 GEN
Solar/Wind Harmer
0.834
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.264
3145746EVERETS
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
316382AG1-145 C
Solar/Wind Harmer
0.19
316159AE1-175 C
Solar/Wind Harmer
0.169
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.102
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
315616AA1-038_C
Solar/Wind Helper
0.535
3151931BEARGRDN S1
50/50
5.934
3151911BEARGRDN G1
50/50
4.593
3144293JTRSVLE
50/50
0.56
3144293JTRSVLE
50/50
0.442
970119AG2-088 GEN
50/50
19.708
970937AG2-583 GEN
Solar/Wind Harmer
33.601
3146776BUCKING
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
20.721
316034AC1-036 C
Solar/Wind Harmer
0.378
315785AD2-033 C
Solar/Wind Harmer
4.42
3143226MDLTHAN
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
1.689
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.6
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.764
970401AG2-262 GEN
Solar/Wind Harmer
0.805
3147043LAWRENC
Adder
0.899
971065AG2-659 GEN
Solar/Wind Harmer
5.573
316129AC1-054 GEN
Solar/Wind Harmer
0.957
3150851SPRUNCC
Adder
0.417
960081AF2-299 GEN
Solar/Wind Harmer
1.05
316087AB2-174 GEN
Solar/Wind Harmer
1.301
3145783HORNRTN
Solar/Wind Harmer
-0.009
3142543TWELFTH
Solar/Wind Harmer
-0.001
941031AE2-094 GEN
Solar/Wind Harmer
15.869
315607AA1-063A GEN
Solar/Wind Harmer
0.851
970919AG2-571 GEN
Solar/Wind Harmer
2.651
970087AG2-069 GEN
Solar/Wind Harmer
7.756
316023GEN1_S
Solar/Wind Harmer
0.552
940641AE2-051 GEN
Solar/Wind Harmer
7.519
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.962
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.397
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316381AD1-082 GEN
Solar/Wind Harmer
0.692
3156021HOLLOMANSOL
Solar/Wind Harmer
0.994
316132AB2-190 GEN1
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
316319Z2-044 C
Solar/Wind Harmer
0.403
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.114
316369SG1_INVT
Solar/Wind Harmer
1.295
315737AD1-076 GEN
Solar/Wind Harmer
1.375
944631AF1-128 GEN
Adder
30.668
315816AE2-034 GEN
Solar/Wind Harmer
0.583
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.774
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.777
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.536
3145963POPLR C
Solar/Wind Harmer
-0.007
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.456
316036AC1-147 C
Solar/Wind Harmer
0.191
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.391
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.143
316359AB2-059 GEN
Solar/Wind Harmer
0.953
3142053HEARTS
Solar/Wind Harmer
0.083
3146293MARTNCO
Solar/Wind Harmer
0.044
961671AG1-007 GEN
Solar/Wind Harmer
0.089
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.208
316494AC1-189 GEN
Solar/Wind Harmer
0.754
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315773AC2-141 GEN
Solar/Wind Harmer
2.902
3138126ROCKLANDING
Solar/Wind Harmer
0.02
3142433PROV 92
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
971317AH1-138 GEN
Solar/Wind Harmer
0.794
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.8
3147666LOUISA
Solar/Wind Helper
0.46
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.559
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.779
TVALTFEXP_TVA->PJM
CLTF
0.76
CPLELTFEXP_CPLE->PJM
CLTF
3.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.141
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.352
MECLTFEXP_MEC->PJM
CLTF
0.255
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.58 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1324.55
MW Contribution:
22.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.934
3151911BEARGRDN G1
50/50
4.593
3144293JTRSVLE
50/50
0.56
3144293JTRSVLE
50/50
0.442
970119AG2-088 GEN
50/50
19.708
970937AG2-583 GEN
Solar/Wind Harmer
33.601
3146776BUCKING
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
20.721
316034AC1-036 C
Solar/Wind Harmer
0.378
315785AD2-033 C
Solar/Wind Harmer
4.42
3143226MDLTHAN
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
1.689
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.6
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.764
970401AG2-262 GEN
Solar/Wind Harmer
0.805
3147043LAWRENC
Adder
0.899
971065AG2-659 GEN
Solar/Wind Harmer
5.573
316129AC1-054 GEN
Solar/Wind Harmer
0.957
3150851SPRUNCC
Adder
0.417
960081AF2-299 GEN
Solar/Wind Harmer
1.05
316087AB2-174 GEN
Solar/Wind Harmer
1.301
3145783HORNRTN
Solar/Wind Harmer
-0.009
3142543TWELFTH
Solar/Wind Harmer
-0.001
941031AE2-094 GEN
Solar/Wind Harmer
15.869
315607AA1-063A GEN
Solar/Wind Harmer
0.851
970919AG2-571 GEN
Solar/Wind Harmer
2.651
970087AG2-069 GEN
Solar/Wind Harmer
7.756
316023GEN1_S
Solar/Wind Harmer
0.552
940641AE2-051 GEN
Solar/Wind Harmer
7.519
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
970909AG2-566 GEN
50/50
2.539
3144293JTRSVLE
50/50
0.56
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
316336AC2-165 C
Solar/Wind Harmer
22.646
316313AB2-026
Solar/Wind Harmer
0.866
970301AG2-198 GEN
Solar/Wind Harmer
13.373
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
970323AG2-213 GEN
Solar/Wind Harmer
10.216
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.492
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.197
970099AG2-077 GEN
Solar/Wind Harmer
15.506
964791AG1-342 GEN
Solar/Wind Harmer
2.635
3146843MT LREL
Solar/Wind Harmer
-0.012
972205AH1-687 GEN
50/50
22.443
316303AF2-085
50/50
2.628
316322AB2-045
Solar/Wind Harmer
1.492
971845AH1-439 GEN
Solar/Wind Harmer
23.204
316258AE1-075 C
Solar/Wind Harmer
0.779
316405AF2-144 C
Solar/Wind Harmer
0.823
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
16.031
970681AG2-440 GEN
Solar/Wind Harmer
10.64
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.235
971283AH1-107 GEN
Solar/Wind Harmer
2.235
316486AD2-202 GEN
Solar/Wind Harmer
0.313
970831AG2-522 GEN
Solar/Wind Harmer
5.345
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
17.883
946281AF1-292 GEN
Solar/Wind Harmer
0.209
3137643SOCKMAN
Solar/Wind Harmer
-0.035
316426AA2-053 GEN
Solar/Wind Harmer
0.86
970673AG2-436 GEN
Solar/Wind Harmer
18.644
970533AG2-339 GEN
Solar/Wind Harmer
5.691
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.171
970581AG2-369 GEN
Solar/Wind Harmer
4.447
315814AE2-033 C
Solar/Wind Harmer
7.589
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.891
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.846
315839AE2-212 C
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.212
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
0.476
316327AA2-057 GEN
Solar/Wind Harmer
0.754
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316311AC2-079 GEN
Solar/Wind Harmer
3.723
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.198
315697AD1-025 GEN
Solar/Wind Harmer
1.465
315732AD1-074 GEN1
Solar/Wind Harmer
1.463
315733AD1-074 GEN2
Solar/Wind Harmer
1.463
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.777
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.192
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
316174AB2-169 GEN
Solar/Wind Harmer
1.095
316316AC1-027 C
Solar/Wind Harmer
0.218
3151201GRAVEL4
Adder
4.604
3151221GRAVEL6
Adder
4.599
3151191GRAVEL3
Adder
4.546
3151211GRAVEL5
Adder
4.546
316236AE1-162_GEN
Solar/Wind Harmer
0.214
971445AH1-216 GEN
Solar/Wind Harmer
4.396
3151081ELIZAR1
Adder
5.794
3151091ELIZAR2
Adder
5.693
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.064
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
316382AG1-145 C
Solar/Wind Harmer
0.19
316159AE1-175 C
Solar/Wind Harmer
0.169
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.102
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
315616AA1-038_C
Solar/Wind Helper
0.535
3151921BEARGRDN G2
50/50
4.593
3144293JTRSVLE
50/50
0.56
972003AH1-546 GEN
Solar/Wind Harmer
22.059
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.593
3147133PAMPLIN
Solar/Wind Harmer
-0.082
959311AF2-222 GEN
Solar/Wind Harmer
22.005
970257AG2-171 GEN
Solar/Wind Harmer
7.662
971775AH1-396 GEN
Solar/Wind Harmer
1.442
964241AG1-285 GEN
Solar/Wind Harmer
13.399
970221AG2-151 GEN
Solar/Wind Harmer
9.591
316478AD1-087 GEN
Solar/Wind Harmer
1.07
270494AE1-108_GEN
Solar/Wind Harmer
3.119
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.922
966621AG1-532 GEN
Solar/Wind Harmer
0.189
316181AB2-040 GEN
Solar/Wind Harmer
1.26
971683AH1-343 GEN
Solar/Wind Harmer
3.742
316190AA2-174 GEN
Solar/Wind Harmer
0.105
944011AF1-069 GEN
Solar/Wind Harmer
4.972
970917AG2-570 GEN
Solar/Wind Harmer
20.942
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.588
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.651
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.673
315813AE1-149 C
Solar/Wind Harmer
4.802
316317KELFORD C
Solar/Wind Harmer
0.354
3145823KELFORD
Solar/Wind Harmer
-0.008
970657AG2-426 GEN
Solar/Wind Harmer
1.525
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.838
315722AD1-056 GEN
Solar/Wind Harmer
2.623
316458AB2-190 GEN2
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.494
3138543CONSLDL
Solar/Wind Harmer
-0.005
315735AD1-075 GEN1
Solar/Wind Harmer
0.731
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
1.509
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
316321Z2-027
Solar/Wind Harmer
0.192
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
3142956BIRDNECK
Solar/Wind Harmer
0.381
3144873MCLAUGH
Solar/Wind Harmer
0
3151171GRAVELC
Adder
0.885
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.868
944581AF1-123 GEN
Solar/Wind Harmer
32.275
944601AF1-125 GEN
Solar/Wind Harmer
31.771
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.664
961601AG1-000A GEN
Solar/Wind Harmer
2.801
3145933PARMELE
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.799
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.751
3142946ENON
Solar/Wind Harmer
-0.002
970293AG2-193 GEN
Solar/Wind Harmer
0.834
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
3147666LOUISA
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.962
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
1.397
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316381AD1-082 GEN
Solar/Wind Harmer
0.692
3156021HOLLOMANSOL
Solar/Wind Harmer
0.994
316132AB2-190 GEN1
Solar/Wind Harmer
0.741
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
316319Z2-044 C
Solar/Wind Harmer
0.403
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.114
316369SG1_INVT
Solar/Wind Harmer
1.295
315737AD1-076 GEN
Solar/Wind Harmer
1.375
944631AF1-128 GEN
Adder
30.668
315816AE2-034 GEN
Solar/Wind Harmer
0.583
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.774
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.777
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.536
3145963POPLR C
Solar/Wind Harmer
-0.007
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.456
316036AC1-147 C
Solar/Wind Harmer
0.191
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.391
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316072AD1-144
Solar/Wind Harmer
0.143
316359AB2-059 GEN
Solar/Wind Harmer
0.953
3142053HEARTS
Solar/Wind Harmer
0.083
3146293MARTNCO
Solar/Wind Harmer
0.044
961671AG1-007 GEN
Solar/Wind Harmer
0.089
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.208
316494AC1-189 GEN
Solar/Wind Harmer
0.754
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315773AC2-141 GEN
Solar/Wind Harmer
2.902
3138126ROCKLANDING
Solar/Wind Harmer
0.02
3142433PROV 92
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.113
3142433PROV 92
Adder
0.113
971317AH1-138 GEN
Solar/Wind Harmer
0.794
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.8
3147666LOUISA
Solar/Wind Helper
0.46
3146843MT LREL
Solar/Wind Harmer
-0.012
315687AD1-152 GEN
Solar/Wind Harmer
1.352
316118AC1-105 GEN
Solar/Wind Harmer
0.77
970933AG2-581 GEN
Solar/Wind Harmer
9.651
316248AF1-058 C
Solar/Wind Harmer
0.305
313506AB2-031 GEN
Solar/Wind Harmer
0.725
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.303
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.552
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.038
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.802
316083AB2-161 GEN
Solar/Wind Harmer
1.227
316349AD2-085 GEN
Solar/Wind Harmer
0.655
315724AD1-057 GEN
Solar/Wind Harmer
1.443
316065AD1-022 GEN
Solar/Wind Harmer
3.644
315835AF2-110_GEN
Solar/Wind Harmer
0.909
316033AB2-134 GEN
Solar/Wind Harmer
2.337
3142366NRTHEST
Adder
0.21
315614AA2-178 GEN
Solar/Wind Harmer
0.777
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
316435W1029_GEN3
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
316049AB1-081 GEN
Solar/Wind Harmer
0.762
316263AC1-034 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
2.766
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3150691DARBY 3
Adder
4.503
3150701DARBY 4
Adder
4.493
3150681DARBY 2
Adder
4.488
3150671DARBY 1
Adder
4.482
3145493TOT1
Solar/Wind Harmer
0.109
3145453TOT5
Solar/Wind Harmer
0.065
3145603CNETO
Solar/Wind Harmer
0.043
316005AA1-067
Solar/Wind Harmer
0.141
316294AC1-161 GEN
Solar/Wind Harmer
2.243
3142946ENON
Solar/Wind Harmer
-0.001
966001AG1-469 GEN
Solar/Wind Helper
0.186
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.559
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.779
TVALTFEXP_TVA->PJM
CLTF
0.76
CPLELTFEXP_CPLE->PJM
CLTF
3.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.141
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.352
MECLTFEXP_MEC->PJM
CLTF
0.255
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B3_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.83 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:903.29
MW Contribution:
23.96
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
24.401
316322AB2-045
Solar/Wind Harmer
1.609
971845AH1-439 GEN
Solar/Wind Harmer
25.005
316258AE1-075 C
Solar/Wind Harmer
0.763
316405AF2-144 C
Solar/Wind Harmer
0.806
946301AF1-294 GEN
Solar/Wind Harmer
6.653
961791AG1-021 GEN
Solar/Wind Harmer
3.245
970683AG2-441 GEN
Solar/Wind Harmer
16.65
970681AG2-440 GEN
Solar/Wind Harmer
11.051
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.451
316239AB2-077_GEN
Solar/Wind Harmer
0.451
316486AD2-202 GEN
Solar/Wind Harmer
0.303
316233AE1-074 FULL
Solar/Wind Harmer
0.277
971281AH1-106 GEN
Solar/Wind Harmer
1.674
971283AH1-107 GEN
Solar/Wind Harmer
1.674
970831AG2-522 GEN
Solar/Wind Harmer
5.074
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
16.127
946281AF1-292 GEN
Solar/Wind Harmer
0.191
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971285AH1-108 GEN
Adder
0.528
316426AA2-053 GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970673AG2-436 GEN
Solar/Wind Harmer
16.266
970533AG2-339 GEN
Solar/Wind Harmer
4.944
970085AG2-068 GEN
Solar/Wind Harmer
4.553
970581AG2-369 GEN
Solar/Wind Harmer
3.916
316274AC1-208 GEN
Solar/Wind Harmer
0.757
315814AE2-033 C
Solar/Wind Harmer
6.529
315652AC1-086 GEN
Solar/Wind Harmer
7.869
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.079
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.027
316463AE2-346 GEN
Solar/Wind Harmer
0.109
3145513AHOSKIE
Solar/Wind Harmer
0.059
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.67
3143316POE
Solar/Wind Harmer
-0.026
315839AE2-212 C
Solar/Wind Harmer
0.195
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.784
970657AG2-426 GEN
Solar/Wind Harmer
0.401
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
3148463FAIRFLD
Solar/Wind Helper
0.141
315616AA1-038_C
Solar/Wind Helper
0.642
3151931BEARGRDN S1
50/50
6.452
3151911BEARGRDN G1
50/50
4.994
3144293JTRSVLE
50/50
0.585
3144293JTRSVLE
50/50
0.462
970937AG2-583 GEN
Solar/Wind Harmer
35.585
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.022
3143336POWHATN
Solar/Wind Harmer
3.741
971563AH1-280 GEN
Solar/Wind Harmer
3.245
970685AG2-442 GEN
Solar/Wind Harmer
21.59
316034AC1-036 C
Solar/Wind Harmer
0.39
315785AD2-033 C
Solar/Wind Harmer
4.533
316131AB2-060 GEN
Solar/Wind Harmer
1.695
315693AD1-088 GEN
Solar/Wind Harmer
7.541
3143226MDLTHAN
Solar/Wind Harmer
-0.012
970909AG2-566 GEN
50/50
2.663
3144293JTRSVLE
50/50
0.585
970535AG2-341 GEN
50/50
2.129
3146776BUCKING
Solar/Wind Harmer
-0.191
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
22.829
316313AB2-026
Solar/Wind Harmer
0.848
970301AG2-198 GEN
Solar/Wind Harmer
14.027
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.022
958211AF2-115 GEN
Solar/Wind Harmer
4.057
970323AG2-213 GEN
Solar/Wind Harmer
10.52
313527AB2-043 GEN
Solar/Wind Harmer
2.494
316237AB2-079_GEN
Solar/Wind Harmer
0.451
962561AG1-105 GEN
Solar/Wind Harmer
7.051
971223AH1-071 GEN
Solar/Wind Harmer
1.533
964791AG1-342 GEN
Solar/Wind Harmer
2.569
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.915
316118AC1-105 GEN
Solar/Wind Harmer
0.741
315687AD1-152 GEN
Solar/Wind Harmer
1.294
3143526WINTERP
Solar/Wind Harmer
-0.053
316248AF1-058 C
Solar/Wind Harmer
0.289
970933AG2-581 GEN
Solar/Wind Harmer
8.888
313506AB2-031 GEN
Solar/Wind Harmer
0.662
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.925
3151921BEARGRDN G2
50/50
4.994
3144293JTRSVLE
50/50
0.585
972003AH1-546 GEN
Solar/Wind Harmer
23.964
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.022
942461AE2-259 GEN
Solar/Wind Harmer
4.864
3143336POWHATN
Solar/Wind Harmer
3.18
3147133PAMPLIN
Solar/Wind Harmer
-0.086
959311AF2-222 GEN
Solar/Wind Harmer
22.721
970257AG2-171 GEN
Solar/Wind Harmer
7.89
971775AH1-396 GEN
Solar/Wind Harmer
1.485
964241AG1-285 GEN
Solar/Wind Harmer
13.573
316478AD1-087 GEN
Solar/Wind Harmer
1.034
3147043LAWRENC
Solar/Wind Harmer
-0.006
316003AC1-222 GEN
Solar/Wind Harmer
0.862
966621AG1-532 GEN
Solar/Wind Harmer
0.173
316181AB2-040 GEN
Solar/Wind Harmer
1.149
971683AH1-343 GEN
Solar/Wind Harmer
3.439
3150861SPRUNCD
Adder
0.323
316190AA2-174 GEN
Solar/Wind Harmer
0.095
970917AG2-570 GEN
Solar/Wind Harmer
18.451
944011AF1-069 GEN
Solar/Wind Harmer
4.319
3156081AA2-088 GEN
Solar/Wind Harmer
2.294
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.461
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.599
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.313
3145823KELFORD
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
2.313
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.135
3146233WITAKRS
Solar/Wind Harmer
-0.004
316222AC1-221 GEN
Solar/Wind Harmer
0.65
3138543CONSLDL
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
4.018
3143096IRON208
Adder
0.238
3143096IRON208
Adder
0.233
3146206CASHIE
Solar/Wind Harmer
-0.006
316283AC2-100 C
Solar/Wind Harmer
0.599
970657AG2-426 GEN
Solar/Wind Harmer
1.285
315821AE2-092 GEN
Solar/Wind Helper
6.554
3148013FISHERV
Solar/Wind Helper
0.273
316499AE2-029_GEN
Solar/Wind Helper
0.588
3132273ORANGE
Solar/Wind Helper
0.023
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.093
972187AH1-678 GEN
Adder
1.941
972185AH1-677 GEN
Adder
3.779
316365GEN2_N
Solar/Wind Harmer
0.487
3144356SAPONY
Solar/Wind Harmer
0.244
316315AB2-025 C
Solar/Wind Harmer
0.188
962571AG1-106 GEN
Solar/Wind Harmer
1.005
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.046
315742AE1-103 GEN
Solar/Wind Harmer
1.569
315724AD1-057 GEN
Solar/Wind Harmer
1.272
316240AF1-291 C
Solar/Wind Harmer
0.192
316083AB2-161 GEN
Solar/Wind Harmer
1.033
944641AF1-129 GEN
Adder
27.005
316065AD1-022 GEN
Solar/Wind Harmer
3.169
966001AG1-469 GEN
Solar/Wind Helper
0.167
3132123MT JACKSON
Solar/Wind Helper
0.376
970401AG2-262 GEN
Solar/Wind Harmer
0.785
957481AF2-042 GEN
Solar/Wind Harmer
37.288
971065AG2-659 GEN
Solar/Wind Harmer
5.332
3147043LAWRENC
Adder
0.854
316129AC1-054 GEN
Solar/Wind Harmer
0.913
3143526WINTERP
Solar/Wind Harmer
-0.053
960081AF2-299 GEN
Solar/Wind Harmer
0.96
316087AB2-174 GEN
Solar/Wind Harmer
1.187
3150851SPRUNCC
Adder
0.323
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.767
970919AG2-571 GEN
Solar/Wind Harmer
2.336
941031AE2-094 GEN
Solar/Wind Harmer
13.785
970087AG2-069 GEN
Solar/Wind Harmer
6.83
316023GEN1_S
Solar/Wind Harmer
0.487
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
940641AE2-051 GEN
Solar/Wind Harmer
6.432
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3145683EARLEYS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
33.321
3156021HOLLOMANSOL
Solar/Wind Harmer
0.868
316319Z2-044 C
Solar/Wind Harmer
0.356
3146233WITAKRS
Solar/Wind Harmer
-0.026
3143096IRON208
Adder
0.238
315671AE2-027_GEN
Solar/Wind Harmer
1.15
316381AD1-082 GEN
Solar/Wind Harmer
0.583
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.591
3147983MERCK5
Solar/Wind Helper
0.064
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.18
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.537
LAGNLTFEXP_LAGN->PJM
CLTF
0.856
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.321
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.399
CPLELTFEXP_CPLE->PJM
CLTF
3.428
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.971
MDUPJM->LTFIMP_MDU
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.118
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.06
NYPJM->LTFIMP_NY
CLTF
0.337

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.83 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:863.6
MW Contribution:
10.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
970937AG2-583 GEN
Solar/Wind Harmer
28.694
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.43 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:860.42
MW Contribution:
10.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
971967AH1-528 GEN
Solar/Wind Harmer
17.83
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
970937AG2-583 GEN
Solar/Wind Harmer
28.694
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970933AG2-581 GEN
Solar/Wind Harmer
8.916
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.0 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1171.21
MW Contribution:
4.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
5.88
3151881LOWMORC
50/50
1.12
3151881LOWMORC
50/50
1.102
3151861LOWMORA
50/50
1.085
3152031BATH 3C
50/50
2.047
3152051BATH 5E
50/50
2.046
3152011BATH 1A
50/50
2.044
3152041BATH 4D
50/50
2.043
23503501NHY_Z2-039
50/50
0.005
23503401SHY_Z2-039
50/50
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
3148463FAIRFLD
Solar/Wind Harmer
0.099
971845AH1-439 GEN
Solar/Wind Harmer
4.38
315651AD1-115 GEN
Solar/Wind Helper
0.966
316164AC1-076 GEN
Solar/Wind Helper
1.193
3151921BEARGRDN G2
50/50
1.203
3151861LOWMORA
50/50
1.129
3152191CUNINGD
50/50
1.775
972255AH1-712 GEN
50/50
53.738
315760AF1-028 GEN
50/50
15.229
3152061BATH 6F
50/50
2.05
3152021BATH 2B
50/50
2.044
3148013FISHERV
Solar/Wind Harmer
0.138
315821AE2-092 GEN
Solar/Wind Harmer
0
970221AG2-151 GEN
Solar/Wind Harmer
6.845
972003AH1-546 GEN
Solar/Wind Harmer
4.369
270494AE1-108_GEN
Solar/Wind Harmer
1.304
3146776BUCKING
Solar/Wind Harmer
0.036
3146926FARMVIL
Solar/Wind Harmer
0.044
958131AF2-107 GEN
Solar/Wind Harmer
1.933
942461AE2-259 GEN
Solar/Wind Harmer
0
3132273ORANGE
Solar/Wind Helper
0.105
3147666LOUISA
Solar/Wind Helper
1.084
3151931BEARGRDN S1
50/50
1.555
3151911BEARGRDN G1
50/50
1.203
972277AH1-723 GEN
50/50
62.621
971377AH1-170 GEN
Solar/Wind Harmer
1.369
3147623JAMES R
Solar/Wind Harmer
0.297
3146776BUCKING
Solar/Wind Harmer
0.04
970937AG2-583 GEN
Solar/Wind Harmer
6.046
3147983MERCK5
Solar/Wind Harmer
0.038
3146926FARMVIL
Solar/Wind Harmer
0.044
316192AB2-158 GEN
Solar/Wind Helper
3.269
3147666LOUISA
Solar/Wind Helper
1.885
3137383CUSHAW
50/50
0.021
3152181CUNINGC
50/50
0.816
3152171CUNINGB
50/50
0.768
3152161CUNINGA
50/50
0.763
972193AH1-681 GEN
50/50
2.401
3146776BUCKING
Solar/Wind Harmer
0.395
3146776BUCKING
Solar/Wind Harmer
0.032
3132123MT JACKSON
Solar/Wind Harmer
0.208
970117AG2-086 GEN
Solar/Wind Harmer
1.596
970117AG2-086 GEN
Solar/Wind Harmer
1.064
316336AC2-165 C
Solar/Wind Harmer
3.133
966001AG1-469 GEN
Solar/Wind Helper
0.735
316006AB2-029 C
Solar/Wind Helper
0.088
LAGNLTFEXP_LAGN->PJM
CLTF
2.708
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.552
TVALTFEXP_TVA->PJM
CLTF
1.406
CPLELTFEXP_CPLE->PJM
CLTF
0.945
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.548
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.844
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.211
MECLTFEXP_MEC->PJM
CLTF
2.087
SIGELTFEXP_SIGE->PJM
CLTF
0.068
NYPJM->LTFIMP_NY
CLTF
0.744
LGEELTFEXP_LGEE->PJM
CLTF
0.897
WECLTFEXP_WEC->PJM
CLTF
0.46

Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.53 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1048.43
MW Contribution:
4.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.26
3151861LOWMORA
50/50
0.943
315760AF1-028 GEN
50/50
12.702
3152061BATH 6F
50/50
1.638
3152021BATH 2B
50/50
1.633
3144293JTRSVLE
50/50
0.158
3152191CUNINGD
50/50
1.058
972255AH1-712 GEN
50/50
32.029
972003AH1-546 GEN
Solar/Wind Harmer
4.596
970221AG2-151 GEN
Solar/Wind Harmer
7.054
315821AE2-092 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Harmer
0.123
270494AE1-108_GEN
Solar/Wind Harmer
1.333
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.052
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
1.009
958131AF2-107 GEN
Solar/Wind Harmer
1.905
3147133PAMPLIN
Solar/Wind Harmer
0.206
3132273ORANGE
Solar/Wind Helper
0.106
3147666LOUISA
Solar/Wind Helper
1.085
972205AH1-687 GEN
50/50
6.157
3151881LOWMORC
50/50
0.936
3151881LOWMORC
50/50
0.921
3151861LOWMORA
50/50
0.906
3152031BATH 3C
50/50
1.635
3152051BATH 5E
50/50
1.635
3152011BATH 1A
50/50
1.633
3152041BATH 4D
50/50
1.632
23503501NHY_Z2-039
50/50
0.004
23503401SHY_Z2-039
50/50
0.002
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.074
3148013FISHERV
Solar/Wind Harmer
0.071
971845AH1-439 GEN
Solar/Wind Harmer
4.836
3148463FAIRFLD
Solar/Wind Harmer
0.083
316258AE1-075 C
Solar/Wind Harmer
0.05
3151931BEARGRDN S1
50/50
1.628
3151911BEARGRDN G1
50/50
1.26
3144293JTRSVLE
50/50
0.158
3144293JTRSVLE
50/50
0.125
972277AH1-723 GEN
50/50
37.324
971377AH1-170 GEN
Solar/Wind Harmer
1.411
3147623JAMES R
Solar/Wind Harmer
0.307
970937AG2-583 GEN
Solar/Wind Harmer
6.726
3146776BUCKING
Solar/Wind Harmer
0.043
3146926FARMVIL
Solar/Wind Harmer
0.052
3147983MERCK5
Solar/Wind Harmer
0.033
3143336POWHATN
Solar/Wind Harmer
1.187
971563AH1-280 GEN
Solar/Wind Harmer
0.665
970685AG2-442 GEN
Solar/Wind Harmer
4.455
316192AB2-158 GEN
Solar/Wind Helper
3.275
3147666LOUISA
Solar/Wind Helper
1.888
946301AF1-294 GEN
Solar/Wind Harmer
1.229
961791AG1-021 GEN
Solar/Wind Harmer
0.598
970683AG2-441 GEN
Solar/Wind Harmer
3.461
970681AG2-440 GEN
Solar/Wind Harmer
2.297
315651AD1-115 GEN
Solar/Wind Helper
0.973
316164AC1-076 GEN
Solar/Wind Helper
1.197
3137383CUSHAW
50/50
0.018
970909AG2-566 GEN
50/50
0.694
3144293JTRSVLE
50/50
0.158
3152181CUNINGC
50/50
0.486
3152171CUNINGB
50/50
0.458
3152161CUNINGA
50/50
0.455
972193AH1-681 GEN
50/50
1.431
3146776BUCKING
Solar/Wind Harmer
0.434
3146776BUCKING
Solar/Wind Harmer
0.035
316336AC2-165 C
Solar/Wind Harmer
3.993
316313AB2-026
Solar/Wind Harmer
0.042
3147133PAMPLIN
Solar/Wind Harmer
0.066
3147133PAMPLIN
Solar/Wind Harmer
0.053
970301AG2-198 GEN
Solar/Wind Harmer
2.775
958211AF2-115 GEN
Solar/Wind Harmer
0.748
966001AG1-469 GEN
Solar/Wind Helper
0.74
316006AB2-029 C
Solar/Wind Helper
0.089
LAGNLTFEXP_LAGN->PJM
CLTF
2.956
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.464
TVALTFEXP_TVA->PJM
CLTF
1.521
CPLELTFEXP_CPLE->PJM
CLTF
1.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.062
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.536
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.509
MECLTFEXP_MEC->PJM
CLTF
2.016
SIGELTFEXP_SIGE->PJM
CLTF
0.065
NYPJM->LTFIMP_NY
CLTF
0.852
LGEELTFEXP_LGEE->PJM
CLTF
0.84
WECLTFEXP_WEC->PJM
CLTF
0.429

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T560_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.48 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1948.14
MW Contribution:
3.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
1.844
315747AE2-019 GEN
50/50
13.164
963691AG1-221 GEN
Solar/Wind Harmer
2.31
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3150151POSSMC1
Adder
1.083
3150151POSSMC1
Adder
1.083
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150241REMNGT4
Adder
12.527
972199AH1-684 GEN
Adder
1.899
972217AH1-693 GEN
Adder
1.652
3150301M RUN C
Adder
13.326
3150291M RUN B
Adder
13.227
3150331BIRCHWDA
Adder
16.668
3150401LDYSMT4
Adder
12.673
3150371LDYSMT1
Adder
12.245
966881AG1-559 GEN
Solar/Wind Harmer
0.308
316223AC1-118
Solar/Wind Harmer
0.271
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.619
3147666LOUISA
Solar/Wind Harmer
-0.023
316077AC2-138 C
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
0.884
3151761LOISA E
Adder
11.393
3151721LOISA A
Adder
5.56
316484AD2-074 GEN
Solar/Wind Harmer
2.432
961951AG1-038 GEN
Solar/Wind Harmer
1.273
316473AC1-191 GEN
Solar/Wind Harmer
1.038
3142416OLDCHRC
Solar/Wind Harmer
0.959
3141873WAN 176
Solar/Wind Harmer
1.127
3141766HARMONY
Solar/Wind Harmer
0.845
316203AE2-005 GEN
Solar/Wind Harmer
4.002
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.182
316075AC2-137 C
Solar/Wind Harmer
0.254
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
970133AG2-095 GEN
Solar/Wind Harmer
1.044
316458AB2-190 GEN2
Solar/Wind Harmer
0.932
3150921YORKTN3
Adder
2.065
315778AD1-151 GEN
Solar/Wind Harmer
8.21
3144216WINCHST
Adder
0.309
961611AG1-000B GEN
Solar/Wind Harmer
1.932
3151171GRAVELC
Adder
1.14
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.697
3144536CHRHLND
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
1.83
3151101ELIZAR3
Adder
7.475
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.122
944601AF1-125 GEN
Solar/Wind Harmer
40.48
3142956BIRDNECK
Solar/Wind Harmer
0.485
316017AA1-139 ULT1
Solar/Wind Harmer
0.725
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.039
316305AF2-043 C
Solar/Wind Harmer
0.27
316246AF1-032 C
Solar/Wind Harmer
0.181
316320Y1-086
Solar/Wind Harmer
0.522
3143336POWHATN
Solar/Wind Harmer
0.898
316321Z2-027
Solar/Wind Harmer
0.239
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
970053AG2-049 GEN
50/50
2.025
3138216PACIFIC
Solar/Wind Harmer
-0.003
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.712
3150381LDYSMT2
Adder
12.166
972213AH1-691 GEN
Adder
2.058
972215AH1-692 GEN
Adder
2.058
315651AD1-115 GEN
Solar/Wind Harmer
4.651
316164AC1-076 GEN
Solar/Wind Harmer
0.884
944491AF1-114 GEN
Solar/Wind Harmer
3.046
316468AD1-105 GEN
Solar/Wind Harmer
1.148
3141813NORNECK
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3147346CASHSCORNER
Solar/Wind Harmer
0.147
957601AF2-054 GEN
Solar/Wind Harmer
0.284
316059AD1-063 C
Solar/Wind Harmer
0.214
3141873WAN 176
Solar/Wind Harmer
-0.002
3145273HOLLAND
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.155
3146376EDENTON
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.758
315735AD1-075 GEN1
Solar/Wind Harmer
0.857
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.069
3146173TUNIS
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.169
3146263WOODLND
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.154
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.722
316190AA2-174 GEN
Solar/Wind Harmer
0.101
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.005
972003AH1-546 GEN
Solar/Wind Harmer
3.341
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.227
316411AF1-147_GEN1
Solar/Wind Harmer
1.097
3150071POSSM 5
Adder
49.515
3150181POSSMC2
Adder
1.092
3150181POSSMC2
Adder
1.083
3150181POSSMC2
Adder
1.083
316006AB2-029 C
Solar/Wind Harmer
0.629
316045AC1-158 PL2
Solar/Wind Harmer
3.324
316450AC1-158 RIC
Solar/Wind Harmer
0.277
3150391LDYSMT3
Adder
12.649
972195AH1-682 GEN
Adder
1.662
315673AE1-157 GEN
Solar/Wind Harmer
7.788
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3151731LOISA B
Adder
5.589
316487AF1-042 GEN
Solar/Wind Harmer
1.273
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316312AB1-027
Solar/Wind Harmer
0.32
316156AD2-030 GEN
Solar/Wind Harmer
0.253
315666AE1-190 GEN
Solar/Wind Harmer
0.285
316441AF1-014 GEN
Solar/Wind Harmer
0.64
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
3150681DARBY 2
Adder
6.038
3150671DARBY 1
Adder
6.031
315976AC1-164 GENA
Solar/Wind Harmer
2.145
316169AC1-164_GENC
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.17
944641AF1-129 GEN
Adder
39.347
316240AF1-291 C
Solar/Wind Harmer
0.278
316033AB2-134 GEN
Solar/Wind Harmer
2.966
316294AC1-161 GEN
Solar/Wind Harmer
2.936
316083AB2-161 GEN
Solar/Wind Harmer
1.471
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
316185AD1-033 GEN
Solar/Wind Harmer
0.95
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316349AD2-085 GEN
Solar/Wind Harmer
0.799
316339AD2-160 GEN
Solar/Wind Harmer
0.605
316388AE2-253 GEN
Solar/Wind Harmer
0.605
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.06
3130086AYDLETT
Solar/Wind Harmer
-0.036
315835AF2-110_GEN
Solar/Wind Harmer
1.119
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316313AB2-026
Solar/Wind Harmer
0.24
316431W1029_GEN1
Solar/Wind Harmer
1.606
316433W1029_GEN2
Solar/Wind Harmer
1.606
316435W1029_GEN3
Solar/Wind Harmer
1.606
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.237
316336AC2-165 C
Solar/Wind Harmer
5.487
315742AE1-103 GEN
Solar/Wind Harmer
2.076
3146376EDENTON
Solar/Wind Harmer
0.258
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
316415AF1-147_GEN2
Solar/Wind Harmer
1.097
972223AH1-696 GEN
Adder
8.557
3150151POSSMC1
Adder
1.083
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.445
3150211REMNGT1
Adder
12.362
972201AH1-685 GEN
Adder
2.147
3150281M RUN A
Adder
13.334
971685AH1-345 GEN
Solar/Wind Harmer
0.96
316447AC1-158 HLD
Solar/Wind Harmer
2.285
316044AC1-158 PL1
Solar/Wind Harmer
1.039
972197AH1-683 GEN
Adder
1.979
972219AH1-694 GEN
Adder
1.425
316254AC1-120 GEN1
Solar/Wind Harmer
3.939
316170AC1-121 GEN2
Solar/Wind Harmer
1.313
957971AF2-091 GEN
Solar/Wind Harmer
1.036
972135AH1-637 GEN
Solar/Wind Harmer
1.029
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
9.488
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.18
316337AD2-073 GEN
Solar/Wind Harmer
0.266
3150351NORNECKC2
Adder
0.869
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
316404AE1-155 C
Solar/Wind Harmer
1.854
958261AF2-120 GEN
Solar/Wind Harmer
3.763
962861AG1-135 GEN
Solar/Wind Harmer
3.636
3151751LOISA D
Adder
5.589
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.812
3141766HARMONY
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.142
316280AD1-041 GEN
Solar/Wind Harmer
0.714
971777AH1-397 GEN
Solar/Wind Harmer
1.108
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.787
3143226MDLTHAN
Solar/Wind Harmer
-0.009
971317AH1-138 GEN
Solar/Wind Harmer
1.161
316132AB2-190 GEN1
Solar/Wind Harmer
0.932
315671AE2-027_GEN
Solar/Wind Harmer
1.668
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.46
316369SG1_INVT
Solar/Wind Harmer
1.642
961611AG1-000B GEN
Solar/Wind Harmer
4.528
3151171GRAVELC
Adder
0.867
3145336SMITFLD
Solar/Wind Harmer
-0.036
315773AC2-141 GEN
Solar/Wind Harmer
3.799
316381AD1-082 GEN
Solar/Wind Harmer
0.829
316375AC2-012 GEN
Solar/Wind Harmer
3.128
316036AC1-147 C
Solar/Wind Harmer
0.243
3150981CHESPKA
Adder
1.005
944591AF1-124 GEN
Solar/Wind Harmer
41.27
316072AD1-144
Solar/Wind Harmer
0.182
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.9
319010AE1-072 C
Solar/Wind Harmer
1.811
940641AE2-051 GEN
Solar/Wind Harmer
8.405
316093AE2-104_GEN
Solar/Wind Harmer
2.602
3143336POWHATN
Solar/Wind Harmer
1.057
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
941031AE2-094 GEN
Solar/Wind Harmer
16.452
315611Z1-036_GEN2
Solar/Wind Harmer
2.158
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.694
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.061
315737AD1-076 GEN
Solar/Wind Harmer
1.612
970937AG2-583 GEN
Solar/Wind Harmer
6.097
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.111
316023GEN1_S
Solar/Wind Harmer
0.568
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.25
970919AG2-571 GEN
Solar/Wind Harmer
2.667
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.125
970087AG2-069 GEN
Solar/Wind Harmer
7.846
960081AF2-299 GEN
Solar/Wind Harmer
0.938
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.839
957481AF2-042 GEN
Solar/Wind Harmer
25.978
3146263WOODLND
Solar/Wind Harmer
-0.008
316087AB2-174 GEN
Solar/Wind Harmer
1.182
315693AD1-088 GEN
Solar/Wind Harmer
4.141
3145963POPLR C
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.662
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
971563AH1-280 GEN
Solar/Wind Harmer
1.011
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
970685AG2-442 GEN
Solar/Wind Harmer
7.066
972277AH1-723 GEN
Adder
42.757
3146293MARTNCO
Solar/Wind Harmer
0.05
316129AC1-054 GEN
Solar/Wind Harmer
0.703
316034AC1-036 C
Solar/Wind Harmer
0.149
205916AD1-020 GEN
Solar/Wind Helper
1.485
208835TUHI V3-051
Solar/Wind Helper
0.017
237001AB1-127_GEN
Solar/Wind Helper
0.308
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
23777901MDS_W4-102
Solar/Wind Helper
0.106
203975AE1-071-GEN
Solar/Wind Helper
1.719
233918AB1-142 GEN
Solar/Wind Helper
0.305
233944AB2-135 GEN
Solar/Wind Helper
0.357
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.01
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.017
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20674928WA_W3-044
Solar/Wind Helper
0.057
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.902
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.526
971283AH1-107 GEN
Solar/Wind Harmer
1.526
971285AH1-108 GEN
Adder
0.63
957831AF2-077 GEN
Solar/Wind Harmer
0.281
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316382AG1-145 C
Solar/Wind Harmer
0.28
316159AE1-175 C
Solar/Wind Harmer
0.249
315697AD1-025 GEN
Solar/Wind Harmer
1.859
315839AE2-212 C
Solar/Wind Harmer
0.277
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151191GRAVEL3
Adder
5.855
3151211GRAVEL5
Adder
5.855
971445AH1-216 GEN
Solar/Wind Harmer
5.641
316236AE1-162_GEN
Solar/Wind Harmer
0.274
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.571
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
1.708
316311AC2-079 GEN
Solar/Wind Harmer
4.537
316018AA1-139 ULT2
Solar/Wind Harmer
0.768
957871AF2-081 GEN
Solar/Wind Harmer
4.495
3146406KITTY HAWK
Solar/Wind Harmer
0.007
313526AB2-022
Solar/Wind Harmer
0.24
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316258AE1-075 C
Solar/Wind Harmer
0.216
316405AF2-144 C
Solar/Wind Harmer
0.228
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.19
970533AG2-339 GEN
Solar/Wind Harmer
5.901
315800Z1-036_GEN1
Solar/Wind Harmer
2.158
970673AG2-436 GEN
Solar/Wind Harmer
19.089
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
971967AH1-528 GEN
Solar/Wind Harmer
16.231
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.714
315733AD1-074 GEN2
Solar/Wind Harmer
1.714
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.694
316318V4-068
Solar/Wind Harmer
0.21
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.23
970581AG2-369 GEN
Solar/Wind Harmer
4.498
316463AE2-346 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.278
316426AA2-053 GEN
Solar/Wind Harmer
0.83
972205AH1-687 GEN
Adder
3.127
316322AB2-045
Solar/Wind Harmer
0.276
971845AH1-439 GEN
Solar/Wind Harmer
4.369
316174AB2-169 GEN
Solar/Wind Harmer
1.265
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.206
3146033SCOT NK
Solar/Wind Harmer
-0.032
946301AF1-294 GEN
Solar/Wind Harmer
2.073
961791AG1-021 GEN
Solar/Wind Harmer
1.011
316210AC1-098 GEN
Solar/Wind Harmer
1.264
970683AG2-441 GEN
Solar/Wind Harmer
5.694
970681AG2-440 GEN
Solar/Wind Harmer
3.78
970831AG2-522 GEN
Solar/Wind Harmer
4.03
316274AC1-208 GEN
Solar/Wind Harmer
0.865
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205943AE1-185 GEN
Solar/Wind Helper
0.388
205956AE1-196_GEN
Solar/Wind Helper
0.386
959381AF2-229 GEN
Solar/Wind Helper
0.257
20390526W1-045 C
Solar/Wind Helper
0.253
233915AB1-141 GEN
Solar/Wind Helper
0.305
233901CHERRYDALE C
Solar/Wind Helper
0.14
233940AF2-379 C
Solar/Wind Helper
0.037
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
228728W1-130C
Solar/Wind Helper
0.032
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.034
20720728JCB_W1-129
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
20673828FLE_V3-070
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.056
20676428JCR_X2-075
Solar/Wind Helper
0.039
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.241
209027LOR2_Q27
Solar/Wind Helper
0.559
212266LOR1
Solar/Wind Helper
0.163
209029WAYMART-WD
Solar/Wind Helper
0.444
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.467
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
3146376EDENTON
Solar/Wind Harmer
0.258
972185AH1-677 GEN
Adder
4.322
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.925
970933AG2-581 GEN
Solar/Wind Harmer
8.024
316065AD1-022 GEN
Solar/Wind Harmer
4.231
316365GEN2_N
Solar/Wind Harmer
0.568
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.056
970099AG2-077 GEN
Solar/Wind Harmer
10.391
313506AB2-031 GEN
Solar/Wind Harmer
0.664
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.124
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.778
3145783HORNRTN
Solar/Wind Harmer
0.243
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.264
3144293JTRSVLE
Adder
0.172
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
972193AH1-681 GEN
Adder
1.639
970323AG2-213 GEN
Solar/Wind Harmer
4.017
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
237080AD1-060 GEN
Solar/Wind Helper
0.222
235062AE1-101 C1
Solar/Wind Helper
1.069
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.343
233994AC2-023 GEN
Solar/Wind Helper
0.579
232428Y3-058 C
Solar/Wind Helper
0.204
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
234015AF2-250 C
Solar/Wind Helper
0.023
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207459AE1-142 C O1
Solar/Wind Helper
0.17
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.237
946751AF1-339 GEN
Solar/Wind Helper
0.234
316478AD1-087 GEN
Solar/Wind Harmer
0.704
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.702
3145933PARMELE
Solar/Wind Harmer
-0.008
972255AH1-712 GEN
Adder
36.692
959311AF2-222 GEN
Solar/Wind Harmer
8.394
970257AG2-171 GEN
Solar/Wind Harmer
3.013
971775AH1-396 GEN
Solar/Wind Harmer
0.567
3151861LOWMORA
Adder
0.643
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
237038AE2-054 C
Solar/Wind Helper
0.174
235067AD1-061 GEN
Solar/Wind Helper
0.282
237085AD2-009_GEN
Solar/Wind Helper
0.975
233935AB2-179 C
Solar/Wind Helper
0.775
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
232406W1-004 FULL
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.181
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
207442AE1-156 GEN
Solar/Wind Helper
0.189
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
1.008
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.237
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
209071AE2-133 GEN
Solar/Wind Helper
0.042
970221AG2-151 GEN
Solar/Wind Harmer
1.345
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
946731AF1-337 GEN
Solar/Wind Helper
0.234
209137AF2-361 C
Solar/Wind Helper
0.711
LAGNLTFEXP_LAGN->PJM
CLTF
6.302
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.53
TVALTFEXP_TVA->PJM
CLTF
3.176
CPLELTFEXP_CPLE->PJM
CLTF
5.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.815
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.55
MECLTFEXP_MEC->PJM
CLTF
4.43
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
2.582
LGEELTFEXP_LGEE->PJM
CLTF
1.797
WECLTFEXP_WEC->PJM
CLTF
0.958

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T560_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.48 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1948.07
MW Contribution:
3.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
1.844
315747AE2-019 GEN
50/50
13.164
963691AG1-221 GEN
Solar/Wind Harmer
2.31
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3150151POSSMC1
Adder
1.084
3150151POSSMC1
Adder
1.084
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150241REMNGT4
Adder
12.527
972199AH1-684 GEN
Adder
1.899
972217AH1-693 GEN
Adder
1.652
970053AG2-049 GEN
50/50
2.025
3138216PACIFIC
Solar/Wind Harmer
-0.003
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.714
3150381LDYSMT2
Adder
12.168
972213AH1-691 GEN
Adder
2.058
972215AH1-692 GEN
Adder
2.058
315651AD1-115 GEN
Solar/Wind Harmer
4.651
316164AC1-076 GEN
Solar/Wind Harmer
0.884
944491AF1-114 GEN
Solar/Wind Harmer
3.046
316468AD1-105 GEN
Solar/Wind Harmer
1.148
3141813NORNECK
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3147346CASHSCORNER
Solar/Wind Harmer
0.147
316059AD1-063 C
Solar/Wind Harmer
0.214
957601AF2-054 GEN
Solar/Wind Harmer
0.284
3141873WAN 176
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.526
971283AH1-107 GEN
Solar/Wind Harmer
1.526
971285AH1-108 GEN
Adder
0.63
957831AF2-077 GEN
Solar/Wind Harmer
0.281
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316382AG1-145 C
Solar/Wind Harmer
0.28
316159AE1-175 C
Solar/Wind Harmer
0.249
315697AD1-025 GEN
Solar/Wind Harmer
1.859
315839AE2-212 C
Solar/Wind Harmer
0.277
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151191GRAVEL3
Adder
5.855
3151211GRAVEL5
Adder
5.855
971445AH1-216 GEN
Solar/Wind Harmer
5.641
316236AE1-162_GEN
Solar/Wind Harmer
0.274
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.571
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
1.708
316311AC2-079 GEN
Solar/Wind Harmer
4.537
316018AA1-139 ULT2
Solar/Wind Harmer
0.768
957871AF2-081 GEN
Solar/Wind Harmer
4.495
3146406KITTY HAWK
Solar/Wind Harmer
0.007
313526AB2-022
Solar/Wind Harmer
0.24
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316258AE1-075 C
Solar/Wind Harmer
0.216
316405AF2-144 C
Solar/Wind Harmer
0.228
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.19
970533AG2-339 GEN
Solar/Wind Harmer
5.901
315800Z1-036_GEN1
Solar/Wind Harmer
2.158
970673AG2-436 GEN
Solar/Wind Harmer
19.089
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
971967AH1-528 GEN
Solar/Wind Harmer
16.231
3150331BIRCHWDA
Adder
16.674
3150301M RUN C
Adder
13.326
3150291M RUN B
Adder
13.227
316411AF1-147_GEN1
Solar/Wind Harmer
1.097
3150071POSSM 5
Adder
49.547
3150181POSSMC2
Adder
1.093
3150181POSSMC2
Adder
1.084
3150181POSSMC2
Adder
1.084
316006AB2-029 C
Solar/Wind Harmer
0.629
3150391LDYSMT3
Adder
12.65
972195AH1-682 GEN
Adder
1.662
316045AC1-158 PL2
Solar/Wind Harmer
3.324
316450AC1-158 RIC
Solar/Wind Harmer
0.277
315673AE1-157 GEN
Solar/Wind Harmer
7.788
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3151731LOISA B
Adder
5.588
316487AF1-042 GEN
Solar/Wind Harmer
1.273
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316312AB1-027
Solar/Wind Harmer
0.32
316156AD2-030 GEN
Solar/Wind Harmer
0.253
315666AE1-190 GEN
Solar/Wind Harmer
0.285
316441AF1-014 GEN
Solar/Wind Harmer
0.64
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
3150681DARBY 2
Adder
6.038
3150671DARBY 1
Adder
6.031
315976AC1-164 GENA
Solar/Wind Harmer
2.145
316169AC1-164_GENC
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.17
944641AF1-129 GEN
Adder
39.347
316240AF1-291 C
Solar/Wind Harmer
0.278
316033AB2-134 GEN
Solar/Wind Harmer
2.966
316294AC1-161 GEN
Solar/Wind Harmer
2.936
316083AB2-161 GEN
Solar/Wind Harmer
1.471
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
316185AD1-033 GEN
Solar/Wind Harmer
0.95
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316349AD2-085 GEN
Solar/Wind Harmer
0.799
316339AD2-160 GEN
Solar/Wind Harmer
0.605
316388AE2-253 GEN
Solar/Wind Harmer
0.605
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.06
3130086AYDLETT
Solar/Wind Harmer
-0.036
315835AF2-110_GEN
Solar/Wind Harmer
1.119
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
316415AF1-147_GEN2
Solar/Wind Harmer
1.097
972223AH1-696 GEN
Adder
8.563
3150151POSSMC1
Adder
1.084
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.445
3150211REMNGT1
Adder
12.362
972201AH1-685 GEN
Adder
2.147
3150281M RUN A
Adder
13.334
971685AH1-345 GEN
Solar/Wind Harmer
0.96
972197AH1-683 GEN
Adder
1.979
972219AH1-694 GEN
Adder
1.425
316447AC1-158 HLD
Solar/Wind Harmer
2.285
316044AC1-158 PL1
Solar/Wind Harmer
1.039
316254AC1-120 GEN1
Solar/Wind Harmer
3.939
316170AC1-121 GEN2
Solar/Wind Harmer
1.313
957971AF2-091 GEN
Solar/Wind Harmer
1.036
972135AH1-637 GEN
Solar/Wind Harmer
1.029
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
9.487
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.18
316337AD2-073 GEN
Solar/Wind Harmer
0.266
3150351NORNECKC2
Adder
0.869
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
316404AE1-155 C
Solar/Wind Harmer
1.854
958261AF2-120 GEN
Solar/Wind Harmer
3.763
962861AG1-135 GEN
Solar/Wind Harmer
3.637
3151751LOISA D
Adder
5.588
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.812
3141766HARMONY
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.142
316280AD1-041 GEN
Solar/Wind Harmer
0.714
971777AH1-397 GEN
Solar/Wind Harmer
1.108
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.787
3143226MDLTHAN
Solar/Wind Harmer
-0.009
971317AH1-138 GEN
Solar/Wind Harmer
1.161
316132AB2-190 GEN1
Solar/Wind Harmer
0.932
315671AE2-027_GEN
Solar/Wind Harmer
1.668
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.46
316369SG1_INVT
Solar/Wind Harmer
1.642
961611AG1-000B GEN
Solar/Wind Harmer
4.528
3151171GRAVELC
Adder
0.867
3145336SMITFLD
Solar/Wind Harmer
-0.036
315773AC2-141 GEN
Solar/Wind Harmer
3.799
316381AD1-082 GEN
Solar/Wind Harmer
0.829
316375AC2-012 GEN
Solar/Wind Harmer
3.128
316036AC1-147 C
Solar/Wind Harmer
0.243
3150981CHESPKA
Adder
1.005
944591AF1-124 GEN
Solar/Wind Harmer
41.27
316072AD1-144
Solar/Wind Harmer
0.182
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.9
319010AE1-072 C
Solar/Wind Harmer
1.811
940641AE2-051 GEN
Solar/Wind Harmer
8.405
316093AE2-104_GEN
Solar/Wind Harmer
2.602
3143336POWHATN
Solar/Wind Harmer
1.057
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
941031AE2-094 GEN
Solar/Wind Harmer
16.452
315611Z1-036_GEN2
Solar/Wind Harmer
2.158
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.694
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.061
315737AD1-076 GEN
Solar/Wind Harmer
1.612
3150401LDYSMT4
Adder
12.674
3150371LDYSMT1
Adder
12.247
966881AG1-559 GEN
Solar/Wind Harmer
0.308
316223AC1-118
Solar/Wind Harmer
0.271
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.619
3147666LOUISA
Solar/Wind Harmer
-0.023
316077AC2-138 C
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
0.884
3151761LOISA E
Adder
11.393
3151721LOISA A
Adder
5.56
316484AD2-074 GEN
Solar/Wind Harmer
2.432
961951AG1-038 GEN
Solar/Wind Harmer
1.273
316473AC1-191 GEN
Solar/Wind Harmer
1.038
3142416OLDCHRC
Solar/Wind Harmer
0.959
3141766HARMONY
Solar/Wind Harmer
0.845
3141873WAN 176
Solar/Wind Harmer
1.127
316203AE2-005 GEN
Solar/Wind Harmer
4.002
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.182
316075AC2-137 C
Solar/Wind Harmer
0.254
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
970133AG2-095 GEN
Solar/Wind Harmer
1.044
316458AB2-190 GEN2
Solar/Wind Harmer
0.932
3150921YORKTN3
Adder
2.065
315778AD1-151 GEN
Solar/Wind Harmer
8.21
3144216WINCHST
Adder
0.309
961611AG1-000B GEN
Solar/Wind Harmer
1.932
3151171GRAVELC
Adder
1.14
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.697
3144536CHRHLND
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
1.83
3151101ELIZAR3
Adder
7.475
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.121
944601AF1-125 GEN
Solar/Wind Harmer
40.48
3142956BIRDNECK
Solar/Wind Harmer
0.485
316017AA1-139 ULT1
Solar/Wind Harmer
0.725
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.039
316305AF2-043 C
Solar/Wind Harmer
0.27
316246AF1-032 C
Solar/Wind Harmer
0.181
316320Y1-086
Solar/Wind Harmer
0.522
3143336POWHATN
Solar/Wind Harmer
0.898
316321Z2-027
Solar/Wind Harmer
0.239
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.155
3146376EDENTON
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.758
315735AD1-075 GEN1
Solar/Wind Harmer
0.857
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.069
3146173TUNIS
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.169
3146263WOODLND
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.154
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.722
316190AA2-174 GEN
Solar/Wind Harmer
0.101
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.005
972003AH1-546 GEN
Solar/Wind Harmer
3.341
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.227
316478AD1-087 GEN
Solar/Wind Harmer
0.704
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.702
3145933PARMELE
Solar/Wind Harmer
-0.008
972255AH1-712 GEN
Adder
36.691
959311AF2-222 GEN
Solar/Wind Harmer
8.394
970257AG2-171 GEN
Solar/Wind Harmer
3.013
971775AH1-396 GEN
Solar/Wind Harmer
0.567
3151861LOWMORA
Adder
0.643
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
237038AE2-054 C
Solar/Wind Helper
0.174
235067AD1-061 GEN
Solar/Wind Helper
0.282
237085AD2-009_GEN
Solar/Wind Helper
0.975
233935AB2-179 C
Solar/Wind Helper
0.775
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
232406W1-004 FULL
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.181
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
207442AE1-156 GEN
Solar/Wind Helper
0.189
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.714
315733AD1-074 GEN2
Solar/Wind Harmer
1.714
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.694
316318V4-068
Solar/Wind Harmer
0.21
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.23
970581AG2-369 GEN
Solar/Wind Harmer
4.498
316463AE2-346 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.278
316426AA2-053 GEN
Solar/Wind Harmer
0.83
972205AH1-687 GEN
Adder
3.127
316322AB2-045
Solar/Wind Harmer
0.276
971845AH1-439 GEN
Solar/Wind Harmer
4.369
316174AB2-169 GEN
Solar/Wind Harmer
1.265
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.206
3146033SCOT NK
Solar/Wind Harmer
-0.032
946301AF1-294 GEN
Solar/Wind Harmer
2.073
217169METRODIV C
Solar/Wind Helper
0.002
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
1.008
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.237
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
209071AE2-133 GEN
Solar/Wind Helper
0.042
970221AG2-151 GEN
Solar/Wind Harmer
1.345
961791AG1-021 GEN
Solar/Wind Harmer
1.011
316210AC1-098 GEN
Solar/Wind Harmer
1.264
970683AG2-441 GEN
Solar/Wind Harmer
5.694
970681AG2-440 GEN
Solar/Wind Harmer
3.779
970831AG2-522 GEN
Solar/Wind Harmer
4.03
316274AC1-208 GEN
Solar/Wind Harmer
0.865
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205943AE1-185 GEN
Solar/Wind Helper
0.388
205956AE1-196_GEN
Solar/Wind Helper
0.386
959381AF2-229 GEN
Solar/Wind Helper
0.257
20390526W1-045 C
Solar/Wind Helper
0.253
233915AB1-141 GEN
Solar/Wind Helper
0.305
233901CHERRYDALE C
Solar/Wind Helper
0.14
233940AF2-379 C
Solar/Wind Helper
0.037
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
228728W1-130C
Solar/Wind Helper
0.032
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.034
20720728JCB_W1-129
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
20673828FLE_V3-070
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.056
20676428JCR_X2-075
Solar/Wind Helper
0.039
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.241
209027LOR2_Q27
Solar/Wind Helper
0.559
212266LOR1
Solar/Wind Helper
0.163
209029WAYMART-WD
Solar/Wind Helper
0.444
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.467
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316313AB2-026
Solar/Wind Harmer
0.24
316431W1029_GEN1
Solar/Wind Harmer
1.606
316433W1029_GEN2
Solar/Wind Harmer
1.606
316435W1029_GEN3
Solar/Wind Harmer
1.606
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.237
316336AC2-165 C
Solar/Wind Harmer
5.487
315742AE1-103 GEN
Solar/Wind Harmer
2.076
3146376EDENTON
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.258
972185AH1-677 GEN
Adder
4.322
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.925
970933AG2-581 GEN
Solar/Wind Harmer
8.024
316065AD1-022 GEN
Solar/Wind Harmer
4.231
316365GEN2_N
Solar/Wind Harmer
0.568
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.056
970099AG2-077 GEN
Solar/Wind Harmer
10.391
313506AB2-031 GEN
Solar/Wind Harmer
0.664
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.124
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.778
3145783HORNRTN
Solar/Wind Harmer
0.243
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.264
3144293JTRSVLE
Adder
0.172
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
972193AH1-681 GEN
Adder
1.639
970323AG2-213 GEN
Solar/Wind Harmer
4.017
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
237080AD1-060 GEN
Solar/Wind Helper
0.222
235062AE1-101 C1
Solar/Wind Helper
1.069
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.343
233994AC2-023 GEN
Solar/Wind Helper
0.579
232428Y3-058 C
Solar/Wind Helper
0.204
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
234015AF2-250 C
Solar/Wind Helper
0.023
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207459AE1-142 C O1
Solar/Wind Helper
0.17
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.237
946751AF1-339 GEN
Solar/Wind Helper
0.234
970937AG2-583 GEN
Solar/Wind Harmer
6.097
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.111
316023GEN1_S
Solar/Wind Harmer
0.568
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.25
970919AG2-571 GEN
Solar/Wind Harmer
2.667
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.125
970087AG2-069 GEN
Solar/Wind Harmer
7.846
960081AF2-299 GEN
Solar/Wind Harmer
0.938
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.839
957481AF2-042 GEN
Solar/Wind Harmer
25.978
3146263WOODLND
Solar/Wind Harmer
-0.008
316087AB2-174 GEN
Solar/Wind Harmer
1.182
315693AD1-088 GEN
Solar/Wind Harmer
4.14
3145963POPLR C
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.662
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
971563AH1-280 GEN
Solar/Wind Harmer
1.011
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
970685AG2-442 GEN
Solar/Wind Harmer
7.066
972277AH1-723 GEN
Adder
42.756
3146293MARTNCO
Solar/Wind Harmer
0.05
316129AC1-054 GEN
Solar/Wind Harmer
0.703
316034AC1-036 C
Solar/Wind Harmer
0.149
205916AD1-020 GEN
Solar/Wind Helper
1.485
208835TUHI V3-051
Solar/Wind Helper
0.017
237001AB1-127_GEN
Solar/Wind Helper
0.308
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
23777901MDS_W4-102
Solar/Wind Helper
0.106
203975AE1-071-GEN
Solar/Wind Helper
1.719
233918AB1-142 GEN
Solar/Wind Helper
0.305
233944AB2-135 GEN
Solar/Wind Helper
0.357
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.01
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.017
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20674928WA_W3-044
Solar/Wind Helper
0.057
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.902
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
946731AF1-337 GEN
Solar/Wind Helper
0.234
209137AF2-361 C
Solar/Wind Helper
0.711
LAGNLTFEXP_LAGN->PJM
CLTF
6.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.53
TVALTFEXP_TVA->PJM
CLTF
3.176
CPLELTFEXP_CPLE->PJM
CLTF
5.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.815
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.321
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.549
MECLTFEXP_MEC->PJM
CLTF
4.43
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
2.582
LGEELTFEXP_LGEE->PJM
CLTF
1.797
WECLTFEXP_WEC->PJM
CLTF
0.958

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: 560T571_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 560T571_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.59 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1935.43
MW Contribution:
3.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
1.847
315747AE2-019 GEN
50/50
13.195
963691AG1-221 GEN
Solar/Wind Harmer
2.315
971455AH1-223 GEN
Solar/Wind Harmer
2.315
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150151POSSMC1
Adder
1.062
3150151POSSMC1
Adder
1.062
3150241REMNGT4
Adder
12.548
972199AH1-684 GEN
Adder
1.902
972217AH1-693 GEN
Adder
1.654
3150301M RUN C
Adder
13.348
3150291M RUN B
Adder
13.249
3150331BIRCHWDA
Adder
16.425
3150401LDYSMT4
Adder
12.537
3150371LDYSMT1
Adder
12.114
966881AG1-559 GEN
Solar/Wind Harmer
0.305
3132273ORANGE
Solar/Wind Harmer
-0.002
316223AC1-118
Solar/Wind Harmer
0.268
3141906WESTMOR
Solar/Wind Harmer
-0.004
971781AH1-399 GEN
Solar/Wind Harmer
0.613
3147666LOUISA
Solar/Wind Harmer
-0.023
316077AC2-138 C
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.875
3151761LOISA E
Adder
11.363
3151721LOISA A
Adder
5.545
316484AD2-074 GEN
Solar/Wind Harmer
2.41
961951AG1-038 GEN
Solar/Wind Harmer
1.261
316473AC1-191 GEN
Solar/Wind Harmer
1.029
3142416OLDCHRC
Solar/Wind Harmer
0.952
3141766HARMONY
Solar/Wind Harmer
0.838
3141873WAN 176
Solar/Wind Harmer
1.118
316203AE2-005 GEN
Solar/Wind Harmer
3.969
3141843SHACKLE
Adder
0.428
970293AG2-193 GEN
Solar/Wind Harmer
1.173
316075AC2-137 C
Solar/Wind Harmer
0.252
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
970053AG2-049 GEN
50/50
2.017
3138216PACIFIC
Solar/Wind Harmer
-0.003
3141426STAFORD
Solar/Wind Harmer
-0.002
315651AD1-115 GEN
Solar/Wind Harmer
4.648
3150411LDYSMT5
Adder
12.576
3150381LDYSMT2
Adder
12.036
972213AH1-691 GEN
Adder
2.036
972215AH1-692 GEN
Adder
2.036
316164AC1-076 GEN
Solar/Wind Harmer
0.882
944491AF1-114 GEN
Solar/Wind Harmer
3.009
316468AD1-105 GEN
Solar/Wind Harmer
1.136
3141813NORNECK
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316059AD1-063 C
Solar/Wind Harmer
0.212
957601AF2-054 GEN
Solar/Wind Harmer
0.282
3141873WAN 176
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
316233AE1-074 FULL
Solar/Wind Harmer
0.251
971281AH1-106 GEN
Solar/Wind Harmer
1.515
971283AH1-107 GEN
Solar/Wind Harmer
1.515
971285AH1-108 GEN
Adder
0.625
957831AF2-077 GEN
Solar/Wind Harmer
0.279
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316382AG1-145 C
Solar/Wind Harmer
0.278
316159AE1-175 C
Solar/Wind Harmer
0.247
315697AD1-025 GEN
Solar/Wind Harmer
1.845
315839AE2-212 C
Solar/Wind Harmer
0.275
3151201GRAVEL4
Adder
5.887
3151221GRAVEL6
Adder
5.88
3151191GRAVEL3
Adder
5.812
3151211GRAVEL5
Adder
5.812
971445AH1-216 GEN
Solar/Wind Harmer
5.601
316236AE1-162_GEN
Solar/Wind Harmer
0.272
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.567
3151081ELIZAR1
Adder
7.328
3151091ELIZAR2
Adder
7.201
316316AC1-027 C
Solar/Wind Harmer
0.275
315833AF1-017_GEN
Solar/Wind Harmer
1.696
316311AC2-079 GEN
Solar/Wind Harmer
4.505
316018AA1-139 ULT2
Solar/Wind Harmer
0.763
957871AF2-081 GEN
Solar/Wind Harmer
4.463
3146406KITTY HAWK
Solar/Wind Harmer
0.007
313526AB2-022
Solar/Wind Harmer
0.238
316258AE1-075 C
Solar/Wind Harmer
0.214
316405AF2-144 C
Solar/Wind Harmer
0.226
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.163
315814AE2-033 C
Solar/Wind Harmer
8.134
970533AG2-339 GEN
Solar/Wind Harmer
5.862
315800Z1-036_GEN1
Solar/Wind Harmer
2.143
970673AG2-436 GEN
Solar/Wind Harmer
18.965
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
971967AH1-528 GEN
Solar/Wind Harmer
16.126
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.703
315733AD1-074 GEN2
Solar/Wind Harmer
1.703
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.67
316318V4-068
Solar/Wind Harmer
0.209
3145893MURPHYS
Solar/Wind Harmer
-0.022
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.197
970581AG2-369 GEN
Solar/Wind Harmer
4.47
316463AE2-346 GEN
Solar/Wind Harmer
0.134
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.186
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.218
316426AA2-053 GEN
Solar/Wind Harmer
0.825
972205AH1-687 GEN
Adder
3.111
316322AB2-045
Solar/Wind Harmer
0.274
971845AH1-439 GEN
Solar/Wind Harmer
4.345
316174AB2-169 GEN
Solar/Wind Harmer
1.257
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
-0.032
946301AF1-294 GEN
Solar/Wind Harmer
2.061
961791AG1-021 GEN
Solar/Wind Harmer
1.005
316210AC1-098 GEN
Solar/Wind Harmer
1.256
970683AG2-441 GEN
Solar/Wind Harmer
5.661
970681AG2-440 GEN
Solar/Wind Harmer
3.757
970831AG2-522 GEN
Solar/Wind Harmer
4.005
316274AC1-208 GEN
Solar/Wind Harmer
0.859
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151881LOWMORC
Adder
0.636
3151881LOWMORC
Adder
0.626
3151861LOWMORA
Adder
0.616
226929AD2-058 GEN
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
20390526W1-045 C
Solar/Wind Helper
0.252
233915AB1-141 GEN
Solar/Wind Helper
0.304
233940AF2-379 C
Solar/Wind Helper
0.037
233901CHERRYDALE C
Solar/Wind Helper
0.14
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.136
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.033
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.11
20675528CPH_W2-050
Solar/Wind Helper
0.066
20673828FLE_V3-070
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.055
20676428JCR_X2-075
Solar/Wind Helper
0.039
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.241
209027LOR2_Q27
Solar/Wind Helper
0.557
212266LOR1
Solar/Wind Helper
0.162
209029WAYMART-WD
Solar/Wind Helper
0.442
209054AE2-059 GEN
Solar/Wind Helper
0.042
209067AE2-060 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.465
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
3143096IRON208
Adder
0.348
3143096IRON208
Adder
0.341
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.382
970133AG2-095 GEN
Solar/Wind Harmer
1.036
316458AB2-190 GEN2
Solar/Wind Harmer
0.926
3150921YORKTN3
Adder
2.05
315778AD1-151 GEN
Solar/Wind Harmer
8.149
3144216WINCHST
Adder
0.307
961611AG1-000B GEN
Solar/Wind Harmer
1.918
3151171GRAVELC
Adder
1.131
315813AE1-149 C
Solar/Wind Harmer
5.656
3145336SMITFLD
Solar/Wind Harmer
-0.004
3144536CHRHLND
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
1.817
3151101ELIZAR3
Adder
7.422
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
40.831
944601AF1-125 GEN
Solar/Wind Harmer
40.194
3142956BIRDNECK
Solar/Wind Harmer
0.481
316017AA1-139 ULT1
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.032
316305AF2-043 C
Solar/Wind Harmer
0.268
316246AF1-032 C
Solar/Wind Harmer
0.18
316320Y1-086
Solar/Wind Harmer
0.519
3143336POWHATN
Solar/Wind Harmer
0.893
316321Z2-027
Solar/Wind Harmer
0.238
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.121
3146376EDENTON
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.74
315735AD1-075 GEN1
Solar/Wind Harmer
0.851
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
20.934
3146173TUNIS
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.168
3146263WOODLND
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.146
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.711
316190AA2-174 GEN
Solar/Wind Harmer
0.1
316317KELFORD C
Solar/Wind Harmer
0.379
3145823KELFORD
Solar/Wind Harmer
-0.008
972003AH1-546 GEN
Solar/Wind Harmer
3.324
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.22
316478AD1-087 GEN
Solar/Wind Harmer
0.7
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3144293JTRSVLE
Adder
0.171
316212AC1-099_GEN
Solar/Wind Harmer
0.698
972255AH1-712 GEN
Adder
36.481
3145933PARMELE
Solar/Wind Harmer
-0.008
959311AF2-222 GEN
Solar/Wind Harmer
8.345
970257AG2-171 GEN
Solar/Wind Harmer
2.995
971775AH1-396 GEN
Solar/Wind Harmer
0.564
3151861LOWMORA
Adder
0.641
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
237038AE2-054 C
Solar/Wind Helper
0.174
235067AD1-061 GEN
Solar/Wind Helper
0.281
237085AD2-009_GEN
Solar/Wind Helper
0.972
233935AB2-179 C
Solar/Wind Helper
0.773
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.408
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.452
233997TMININ_4.2
Solar/Wind Helper
0.123
233950AC2-186 GEN
Solar/Wind Helper
0.07
232406W1-004 FULL
Solar/Wind Helper
0.305
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.18
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
207442AE1-156 GEN
Solar/Wind Helper
0.188
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
316411AF1-147_GEN1
Solar/Wind Harmer
1.1
3150071POSSM 5
Adder
48.541
3150181POSSMC2
Adder
1.071
3150181POSSMC2
Adder
1.062
3150181POSSMC2
Adder
1.062
316006AB2-029 C
Solar/Wind Harmer
0.63
316045AC1-158 PL2
Solar/Wind Harmer
3.317
316450AC1-158 RIC
Solar/Wind Harmer
0.276
3150391LDYSMT3
Adder
12.514
972195AH1-682 GEN
Adder
1.644
315673AE1-157 GEN
Solar/Wind Harmer
7.709
972189AH1-679 GEN
Adder
1.453
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3150341NORNECKC1
Adder
0.904
3150341NORNECKC1
Adder
0.897
3151731LOISA B
Adder
5.574
316487AF1-042 GEN
Solar/Wind Harmer
1.261
966871AG1-558 GEN
Solar/Wind Harmer
0.288
966871AG1-558 GEN
Solar/Wind Harmer
0.098
3142296MT RD221
Adder
0.268
316312AB1-027
Solar/Wind Harmer
0.317
316156AD2-030 GEN
Solar/Wind Harmer
0.251
315666AE1-190 GEN
Solar/Wind Harmer
0.283
316441AF1-014 GEN
Solar/Wind Harmer
0.635
3142366NRTHEST
Adder
0.273
3150691DARBY 3
Adder
6.012
3150701DARBY 4
Adder
5.998
3150681DARBY 2
Adder
5.991
3150671DARBY 1
Adder
5.984
315976AC1-164 GENA
Solar/Wind Harmer
2.128
316169AC1-164_GENC
Solar/Wind Harmer
1.839
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.048
971223AH1-071 GEN
Solar/Wind Harmer
1.162
944641AF1-129 GEN
Adder
39.056
316240AF1-291 C
Solar/Wind Harmer
0.276
316033AB2-134 GEN
Solar/Wind Harmer
2.944
316294AC1-161 GEN
Solar/Wind Harmer
2.915
316083AB2-161 GEN
Solar/Wind Harmer
1.46
3150991CHESPKB
Adder
0.837
3150991CHESPKB
Adder
0.817
316185AD1-033 GEN
Solar/Wind Harmer
0.943
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316349AD2-085 GEN
Solar/Wind Harmer
0.793
316339AD2-160 GEN
Solar/Wind Harmer
0.601
316388AE2-253 GEN
Solar/Wind Harmer
0.601
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3146456SLIGO L269
Solar/Wind Harmer
1.053
3130086AYDLETT
Solar/Wind Harmer
-0.035
315835AF2-110_GEN
Solar/Wind Harmer
1.111
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316313AB2-026
Solar/Wind Harmer
0.238
316431W1029_GEN1
Solar/Wind Harmer
1.595
316433W1029_GEN2
Solar/Wind Harmer
1.595
316435W1029_GEN3
Solar/Wind Harmer
1.595
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.305
316315AB2-025 C
Solar/Wind Harmer
0.235
316336AC2-165 C
Solar/Wind Harmer
5.454
315742AE1-103 GEN
Solar/Wind Harmer
2.062
3146376EDENTON
Solar/Wind Harmer
0.257
3146376EDENTON
Solar/Wind Harmer
0.257
972185AH1-677 GEN
Adder
4.294
972187AH1-678 GEN
Adder
2.166
315614AA2-178 GEN
Solar/Wind Harmer
0.919
970933AG2-581 GEN
Solar/Wind Harmer
7.973
316065AD1-022 GEN
Solar/Wind Harmer
4.203
316365GEN2_N
Solar/Wind Harmer
0.564
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.056
970099AG2-077 GEN
Solar/Wind Harmer
10.327
313506AB2-031 GEN
Solar/Wind Harmer
0.66
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.1
962571AG1-106 GEN
Solar/Wind Harmer
1.178
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3145783HORNRTN
Solar/Wind Harmer
0.966
3145783HORNRTN
Solar/Wind Harmer
0.773
3145783HORNRTN
Solar/Wind Harmer
0.242
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.257
3144293JTRSVLE
Adder
0.171
972193AH1-681 GEN
Adder
1.63
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
970323AG2-213 GEN
Solar/Wind Harmer
3.993
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.066
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.217
233930AB2-032 GEN
Solar/Wind Helper
0.23
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.342
233994AC2-023 GEN
Solar/Wind Helper
0.577
232428Y3-058 C
Solar/Wind Helper
0.203
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
234015AF2-250 C
Solar/Wind Helper
0.023
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207459AE1-142 C O1
Solar/Wind Helper
0.169
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.236
946751AF1-339 GEN
Solar/Wind Helper
0.233
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.051
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
1.005
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.241
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.233
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
970221AG2-151 GEN
Solar/Wind Harmer
1.339
3152131X4-039 ST
50/50
2.888
3152121X4-039 GT2
50/50
1.835
316415AF1-147_GEN2
Solar/Wind Harmer
1.1
972223AH1-696 GEN
Adder
8.389
3150151POSSMC1
Adder
1.062
3141346CRANES
Adder
0.118
3150221REMNGT2
Adder
12.465
3150211REMNGT1
Adder
12.382
972201AH1-685 GEN
Adder
2.151
3150281M RUN A
Adder
13.356
971685AH1-345 GEN
Solar/Wind Harmer
0.961
316447AC1-158 HLD
Solar/Wind Harmer
2.28
316044AC1-158 PL1
Solar/Wind Harmer
1.037
972197AH1-683 GEN
Adder
1.958
972219AH1-694 GEN
Adder
1.41
316254AC1-120 GEN1
Solar/Wind Harmer
3.935
316170AC1-121 GEN2
Solar/Wind Harmer
1.312
957971AF2-091 GEN
Solar/Wind Harmer
1.023
315683AE1-153 C
Solar/Wind Harmer
9.479
972135AH1-637 GEN
Solar/Wind Harmer
1.017
966881AG1-559 GEN
Solar/Wind Harmer
0.104
3147666LOUISA
Solar/Wind Harmer
-0.039
316192AB2-158 GEN
Solar/Wind Harmer
1.176
316337AD2-073 GEN
Solar/Wind Harmer
0.263
3150351NORNECKC2
Adder
0.861
964211AG1-282 GEN
Solar/Wind Harmer
0.291
3141726DUNNSVL
Solar/Wind Harmer
-0.038
3151751LOISA D
Adder
5.574
316404AE1-155 C
Solar/Wind Harmer
1.836
958261AF2-120 GEN
Solar/Wind Harmer
3.727
962861AG1-135 GEN
Solar/Wind Harmer
3.603
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.024
3142416OLDCHRC
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.805
3141766HARMONY
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.132
316280AD1-041 GEN
Solar/Wind Harmer
0.708
971777AH1-397 GEN
Solar/Wind Harmer
1.099
3142433PROV 92
Solar/Wind Harmer
-0.037
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3143096IRON208
Adder
0.348
3143526WINTERP
Solar/Wind Harmer
-0.048
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.382
944631AF1-128 GEN
Adder
39.483
3143226MDLTHAN
Solar/Wind Harmer
-0.009
971317AH1-138 GEN
Solar/Wind Harmer
1.152
316132AB2-190 GEN1
Solar/Wind Harmer
0.926
315671AE2-027_GEN
Solar/Wind Harmer
1.655
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.449
316369SG1_INVT
Solar/Wind Harmer
1.63
961611AG1-000B GEN
Solar/Wind Harmer
4.495
3151171GRAVELC
Adder
0.86
3145336SMITFLD
Solar/Wind Harmer
-0.036
315773AC2-141 GEN
Solar/Wind Harmer
3.772
316381AD1-082 GEN
Solar/Wind Harmer
0.823
316375AC2-012 GEN
Solar/Wind Harmer
3.106
316036AC1-147 C
Solar/Wind Harmer
0.242
3150981CHESPKA
Adder
0.998
944591AF1-124 GEN
Solar/Wind Harmer
40.978
316072AD1-144
Solar/Wind Harmer
0.181
939411AE1-173 GEN
Solar/Wind Harmer
44.594
3146456SLIGO L269
Solar/Wind Harmer
-0.009
319010AE1-072 C
Solar/Wind Harmer
1.799
940641AE2-051 GEN
Solar/Wind Harmer
8.349
316093AE2-104_GEN
Solar/Wind Harmer
2.584
3143336POWHATN
Solar/Wind Harmer
1.05
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
941031AE2-094 GEN
Solar/Wind Harmer
16.344
315611Z1-036_GEN2
Solar/Wind Harmer
2.143
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.689
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.006
315737AD1-076 GEN
Solar/Wind Harmer
1.601
970937AG2-583 GEN
Solar/Wind Harmer
6.064
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.097
316023GEN1_S
Solar/Wind Harmer
0.564
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.249
970919AG2-571 GEN
Solar/Wind Harmer
2.65
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.118
970087AG2-069 GEN
Solar/Wind Harmer
7.796
960081AF2-299 GEN
Solar/Wind Harmer
0.932
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.833
957481AF2-042 GEN
Solar/Wind Harmer
25.816
3146263WOODLND
Solar/Wind Harmer
-0.008
316087AB2-174 GEN
Solar/Wind Harmer
1.175
315693AD1-088 GEN
Solar/Wind Harmer
4.115
3145963POPLR C
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3147043LAWRENC
Adder
0.658
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
971563AH1-280 GEN
Solar/Wind Harmer
1.005
3144293JTRSVLE
Adder
0.171
3144293JTRSVLE
Adder
0.135
970685AG2-442 GEN
Solar/Wind Harmer
7.025
972277AH1-723 GEN
Adder
42.511
3146293MARTNCO
Solar/Wind Harmer
0.05
316129AC1-054 GEN
Solar/Wind Harmer
0.698
316034AC1-036 C
Solar/Wind Harmer
0.148
205916AD1-020 GEN
Solar/Wind Helper
1.482
208835TUHI V3-051
Solar/Wind Helper
0.017
237001AB1-127_GEN
Solar/Wind Helper
0.307
205932AD2-116_GEN
Solar/Wind Helper
0.385
235063AE1-101 C2
Solar/Wind Helper
1.066
23777901MDS_W4-102
Solar/Wind Helper
0.105
203975AE1-071-GEN
Solar/Wind Helper
1.715
233918AB1-142 GEN
Solar/Wind Helper
0.304
233944AB2-135 GEN
Solar/Wind Helper
0.356
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.123
233998TM1NIN_3.36
Solar/Wind Helper
0.123
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219348LDSOLAR C
Solar/Wind Helper
0.067
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.045
20720528MAN_W1-024
Solar/Wind Helper
0.016
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.01
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.017
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20674928WA_W3-044
Solar/Wind Helper
0.056
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.899
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.241
963151AG1-164 GEN
Solar/Wind Helper
0.241
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.828
946731AF1-337 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.709
LAGNLTFEXP_LAGN->PJM
CLTF
6.282
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.471
TVALTFEXP_TVA->PJM
CLTF
3.166
CPLELTFEXP_CPLE->PJM
CLTF
5.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.711
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.515
MECLTFEXP_MEC->PJM
CLTF
4.421
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
2.573
LGEELTFEXP_LGEE->PJM
CLTF
1.794
WECLTFEXP_WEC->PJM
CLTF
0.956

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.6 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1878.9
MW Contribution:
2.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3138216PACIFIC
Solar/Wind Harmer
-0.003
970053AG2-049 GEN
Adder
1.473
315651AD1-115 GEN
Solar/Wind Harmer
3.931
316164AC1-076 GEN
Solar/Wind Harmer
0.727
3147346CASHSCORNER
Solar/Wind Harmer
0.123
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
9.207
3150381LDYSMT2
Adder
8.811
972213AH1-691 GEN
Adder
1.49
972215AH1-692 GEN
Adder
1.49
944491AF1-114 GEN
Solar/Wind Harmer
2.202
316468AD1-105 GEN
Solar/Wind Harmer
0.85
3141813NORNECK
Solar/Wind Harmer
-0.007
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971281AH1-106 GEN
Solar/Wind Harmer
1.182
971283AH1-107 GEN
Solar/Wind Harmer
1.182
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.486
316059AD1-063 C
Solar/Wind Harmer
0.163
3143873LANEXA
Solar/Wind Harmer
-0.004
957601AF2-054 GEN
Solar/Wind Harmer
0.216
3141873WAN 176
Solar/Wind Harmer
-0.001
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
957831AF2-077 GEN
Solar/Wind Harmer
0.216
3138283WHITEMARSH
Solar/Wind Harmer
0.011
316382AG1-145 C
Solar/Wind Harmer
0.215
316159AE1-175 C
Solar/Wind Harmer
0.192
315839AE2-212 C
Solar/Wind Harmer
0.214
315697AD1-025 GEN
Solar/Wind Harmer
1.438
3151201GRAVEL4
Adder
4.595
3151221GRAVEL6
Adder
4.59
3151191GRAVEL3
Adder
4.537
3151211GRAVEL5
Adder
4.537
3143316POE
Solar/Wind Harmer
-0.028
316258AE1-075 C
Solar/Wind Harmer
0.171
316405AF2-144 C
Solar/Wind Harmer
0.181
971445AH1-216 GEN
Solar/Wind Harmer
4.378
316236AE1-162_GEN
Solar/Wind Harmer
0.213
970657AG2-426 GEN
Solar/Wind Harmer
0.444
3151081ELIZAR1
Adder
5.744
3151091ELIZAR2
Adder
5.644
316316AC1-027 C
Solar/Wind Harmer
0.215
315833AF1-017_GEN
Solar/Wind Harmer
1.331
316311AC2-079 GEN
Solar/Wind Harmer
3.535
316018AA1-139 ULT2
Solar/Wind Harmer
0.599
957871AF2-081 GEN
Solar/Wind Harmer
3.504
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316411AF1-147_GEN1
Solar/Wind Harmer
1.073
316006AB2-029 C
Solar/Wind Harmer
0.548
316045AC1-158 PL2
Solar/Wind Harmer
2.723
316450AC1-158 RIC
Solar/Wind Harmer
0.227
966001AG1-469 GEN
Solar/Wind Harmer
0.153
3151731LOISA B
Adder
4.646
3150071POSSM 5
Adder
32.531
3150181POSSMC2
Adder
0.718
3150181POSSMC2
Adder
0.712
3150181POSSMC2
Adder
0.712
3150391LDYSMT3
Adder
9.161
972195AH1-682 GEN
Adder
1.204
315673AE1-157 GEN
Solar/Wind Harmer
5.701
972189AH1-679 GEN
Adder
1.102
3150341NORNECKC1
Adder
0.683
3150341NORNECKC1
Adder
0.678
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
3142296MT RD221
Adder
0.206
316487AF1-042 GEN
Solar/Wind Harmer
0.96
971223AH1-071 GEN
Solar/Wind Harmer
0.911
3143526WINTERP
Solar/Wind Harmer
-0.038
316312AB1-027
Solar/Wind Harmer
0.244
3142366NRTHEST
Adder
0.211
3150691DARBY 3
Adder
4.643
3150701DARBY 4
Adder
4.632
3150681DARBY 2
Adder
4.627
3150671DARBY 1
Adder
4.621
316441AF1-014 GEN
Solar/Wind Harmer
0.488
315666AE1-190 GEN
Solar/Wind Harmer
0.217
316156AD2-030 GEN
Solar/Wind Harmer
0.193
315976AC1-164 GENA
Solar/Wind Harmer
1.643
316169AC1-164_GENC
Solar/Wind Harmer
1.419
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
30.387
316240AF1-291 C
Solar/Wind Harmer
0.215
316033AB2-134 GEN
Solar/Wind Harmer
2.294
316313AB2-026
Solar/Wind Harmer
0.19
316294AC1-161 GEN
Solar/Wind Harmer
2.283
316083AB2-161 GEN
Solar/Wind Harmer
1.144
3150991CHESPKB
Adder
0.656
3150991CHESPKB
Adder
0.641
316185AD1-033 GEN
Solar/Wind Harmer
0.74
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316336AC2-165 C
Solar/Wind Harmer
4.383
316339AD2-160 GEN
Solar/Wind Harmer
0.471
316388AE2-253 GEN
Solar/Wind Harmer
0.471
316349AD2-085 GEN
Solar/Wind Harmer
0.622
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.827
3130086AYDLETT
Solar/Wind Harmer
-0.028
315835AF2-110_GEN
Solar/Wind Harmer
0.873
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.256
316433W1029_GEN2
Solar/Wind Harmer
1.256
316435W1029_GEN3
Solar/Wind Harmer
1.256
971761AH1-387 GEN
Solar/Wind Harmer
3.866
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3144356SAPONY
Solar/Wind Harmer
0.241
316315AB2-025 C
Solar/Wind Harmer
0.186
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
1.629
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
972185AH1-677 GEN
Adder
3.415
972187AH1-678 GEN
Adder
1.725
970933AG2-581 GEN
Solar/Wind Harmer
6.362
315614AA2-178 GEN
Solar/Wind Harmer
0.729
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
316065AD1-022 GEN
Solar/Wind Harmer
3.346
316365GEN2_N
Solar/Wind Harmer
0.45
3145893MURPHYS
Solar/Wind Harmer
0.186
3145893MURPHYS
Solar/Wind Harmer
-0.012
970301AG2-198 GEN
Solar/Wind Harmer
3.329
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
970099AG2-077 GEN
Solar/Wind Harmer
8.303
316140AB2-099
Solar/Wind Harmer
0.045
972193AH1-681 GEN
Adder
1.345
313506AB2-031 GEN
Solar/Wind Harmer
0.529
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
962571AG1-106 GEN
Solar/Wind Harmer
0.944
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.054
958211AF2-115 GEN
Solar/Wind Harmer
1.024
3144293JTRSVLE
Adder
0.139
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.621
3145783HORNRTN
Solar/Wind Harmer
0.194
3145783HORNRTN
Solar/Wind Harmer
0.078
3145796HORNRTN
Solar/Wind Harmer
-0.019
970323AG2-213 GEN
Solar/Wind Harmer
3.251
237006AB1-125 GEN
Solar/Wind Helper
0.175
223401AF1-299 GEN
Solar/Wind Helper
0.386
223402AF1-300 C
Solar/Wind Helper
0.386
238221AF1-254 C O1
Solar/Wind Helper
0.198
237080AD1-060 GEN
Solar/Wind Helper
0.243
235062AE1-101 C1
Solar/Wind Helper
1.173
235020AA1-095 C
Solar/Wind Helper
0.031
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.026
233946AB2-136 GEN
Solar/Wind Helper
0.343
233994AC2-023 GEN
Solar/Wind Helper
0.58
232428Y3-058 C
Solar/Wind Helper
0.204
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.306
234015AF2-250 C
Solar/Wind Helper
0.023
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207459AE1-142 C O1
Solar/Wind Helper
0.169
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.096
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.233
946751AF1-339 GEN
Solar/Wind Helper
0.23
313526AB2-022
Solar/Wind Harmer
0.187
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.128
970533AG2-339 GEN
Solar/Wind Harmer
4.647
315814AE2-033 C
Solar/Wind Harmer
6.429
970673AG2-436 GEN
Solar/Wind Harmer
15.054
315800Z1-036_GEN1
Solar/Wind Harmer
1.693
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
12.837
972205AH1-687 GEN
Adder
2.57
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316322AB2-045
Solar/Wind Harmer
0.225
315732AD1-074 GEN1
Solar/Wind Harmer
1.354
315733AD1-074 GEN2
Solar/Wind Harmer
1.354
971845AH1-439 GEN
Solar/Wind Harmer
3.565
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.923
316318V4-068
Solar/Wind Harmer
0.166
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.162
970581AG2-369 GEN
Solar/Wind Harmer
3.579
946281AF1-292 GEN
Solar/Wind Harmer
0.149
316463AE2-346 GEN
Solar/Wind Harmer
0.107
3145513AHOSKIE
Solar/Wind Harmer
0.058
961941AG1-037 GEN
Solar/Wind Harmer
0.05
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3137643SOCKMAN
Solar/Wind Harmer
-0.026
316426AA2-053 GEN
Solar/Wind Harmer
0.662
315652AC1-086 GEN
Solar/Wind Harmer
7.388
946301AF1-294 GEN
Solar/Wind Harmer
1.679
961791AG1-021 GEN
Solar/Wind Harmer
0.819
316486AD2-202 GEN
Solar/Wind Harmer
0.166
316174AB2-169 GEN
Solar/Wind Harmer
1.007
970683AG2-441 GEN
Solar/Wind Harmer
4.61
970681AG2-440 GEN
Solar/Wind Harmer
3.06
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
3144303KENBRDG
Solar/Wind Harmer
-0.005
237030AB1-096 C
Solar/Wind Helper
0.095
237025AB1-124 C
Solar/Wind Helper
0.234
23779801AA1-109
Solar/Wind Helper
0.262
205917AD1-020 ES
Solar/Wind Helper
0.358
226929AD2-058 GEN
Solar/Wind Helper
0.079
959381AF2-229 GEN
Solar/Wind Helper
0.283
20390526W1-045 C
Solar/Wind Helper
0.278
205943AE1-185 GEN
Solar/Wind Helper
0.41
205956AE1-196_GEN
Solar/Wind Helper
0.407
233915AB1-141 GEN
Solar/Wind Helper
0.305
233901CHERRYDALE C
Solar/Wind Helper
0.14
233940AF2-379 C
Solar/Wind Helper
0.037
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.136
228728W1-130C
Solar/Wind Helper
0.032
219258KINSLEYDEP C
Solar/Wind Helper
0.045
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20720728JCB_W1-129
Solar/Wind Helper
0.033
20715028HAN_X4-015
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.11
20675528CPH_W2-050
Solar/Wind Helper
0.065
20673828FLE_V3-070
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.055
20676428JCR_X2-075
Solar/Wind Helper
0.039
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.239
209027LOR2_Q27
Solar/Wind Helper
0.551
212266LOR1
Solar/Wind Helper
0.16
209029WAYMART-WD
Solar/Wind Helper
0.438
209067AE2-060 GEN
Solar/Wind Helper
0.042
209054AE2-059 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.459
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.23
3152111X4-039 GT1
50/50
1.834
315747AE2-019 GEN
50/50
12.529
963691AG1-221 GEN
Solar/Wind Harmer
2.258
971455AH1-223 GEN
Solar/Wind Harmer
2.258
3141196NOKESVL
Solar/Wind Harmer
-0.043
3150241REMNGT4
Adder
10.998
972199AH1-684 GEN
Adder
1.667
972217AH1-693 GEN
Adder
1.45
3150301M RUN C
Adder
11.683
3150291M RUN B
Adder
11.597
3132273ORANGE
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Harmer
-0.018
3151761LOISA E
Adder
9.471
3151721LOISA A
Adder
4.622
3150151POSSMC1
Adder
0.712
3150151POSSMC1
Adder
0.712
3150331BIRCHWDA
Adder
11.656
3150401LDYSMT4
Adder
9.178
3150371LDYSMT1
Adder
8.868
966881AG1-559 GEN
Solar/Wind Harmer
0.227
971781AH1-399 GEN
Solar/Wind Harmer
0.458
316223AC1-118
Solar/Wind Harmer
0.2
3141906WESTMOR
Solar/Wind Harmer
-0.003
316077AC2-138 C
Solar/Wind Harmer
0.154
3150351NORNECKC2
Adder
0.661
316473AC1-191 GEN
Solar/Wind Harmer
0.787
316484AD2-074 GEN
Solar/Wind Harmer
1.834
961951AG1-038 GEN
Solar/Wind Harmer
0.96
3142416OLDCHRC
Solar/Wind Harmer
0.733
970293AG2-193 GEN
Solar/Wind Harmer
0.906
316075AC2-137 C
Solar/Wind Harmer
0.195
3150861SPRUNCD
Adder
0.297
3141766HARMONY
Solar/Wind Harmer
0.644
316203AE2-005 GEN
Solar/Wind Harmer
3.049
3141873WAN 176
Solar/Wind Harmer
0.858
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.264
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142946ENON
Solar/Wind Harmer
-0.002
970133AG2-095 GEN
Solar/Wind Harmer
0.806
316458AB2-190 GEN2
Solar/Wind Harmer
0.72
315778AD1-151 GEN
Solar/Wind Harmer
6.347
3150921YORKTN3
Adder
1.594
3144216WINCHST
Adder
0.239
961611AG1-000B GEN
Solar/Wind Harmer
1.496
3151171GRAVELC
Adder
0.883
315813AE1-149 C
Solar/Wind Harmer
4.424
3143336POWHATN
Solar/Wind Harmer
0.714
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
1.423
3151101ELIZAR3
Adder
5.817
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
32.014
944601AF1-125 GEN
Solar/Wind Harmer
31.514
3142956BIRDNECK
Solar/Wind Harmer
0.377
316017AA1-139 ULT1
Solar/Wind Harmer
0.565
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.81
316305AF2-043 C
Solar/Wind Harmer
0.21
316246AF1-032 C
Solar/Wind Harmer
0.141
316320Y1-086
Solar/Wind Harmer
0.408
316321Z2-027
Solar/Wind Harmer
0.187
3146516WINFALL
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
4.06
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
972003AH1-546 GEN
Solar/Wind Harmer
2.743
3156081AA2-088 GEN
Solar/Wind Harmer
2.18
3146776BUCKING
Solar/Wind Harmer
-0.002
315735AD1-075 GEN1
Solar/Wind Harmer
0.677
970917AG2-570 GEN
Solar/Wind Harmer
16.739
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
-0.007
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
4.15
966621AG1-532 GEN
Solar/Wind Harmer
0.135
942461AE2-259 GEN
Solar/Wind Harmer
0.995
972255AH1-712 GEN
Adder
30.111
3152131X4-039 ST
50/50
2.868
3152121X4-039 GT2
50/50
1.822
316415AF1-147_GEN2
Solar/Wind Harmer
1.073
3150221REMNGT2
Adder
10.925
3150211REMNGT1
Adder
10.853
972201AH1-685 GEN
Adder
1.885
3150281M RUN A
Adder
11.691
971685AH1-345 GEN
Solar/Wind Harmer
0.836
316254AC1-120 GEN1
Solar/Wind Harmer
3.304
316170AC1-121 GEN2
Solar/Wind Harmer
1.101
316447AC1-158 HLD
Solar/Wind Harmer
1.872
316044AC1-158 PL1
Solar/Wind Harmer
0.851
315683AE1-153 C
Solar/Wind Harmer
8.072
3147666LOUISA
Solar/Wind Harmer
-0.032
316192AB2-158 GEN
Solar/Wind Harmer
0.957
3151751LOISA D
Adder
4.646
972223AH1-696 GEN
Adder
5.622
3150151POSSMC1
Adder
0.712
3141346CRANES
Adder
0.082
972197AH1-683 GEN
Adder
1.433
972219AH1-694 GEN
Adder
1.032
966881AG1-559 GEN
Solar/Wind Harmer
0.078
957971AF2-091 GEN
Solar/Wind Harmer
0.749
972135AH1-637 GEN
Solar/Wind Harmer
0.749
316337AD2-073 GEN
Solar/Wind Harmer
0.198
3150351NORNECKC2
Adder
0.65
964211AG1-282 GEN
Solar/Wind Harmer
0.22
3141726DUNNSVL
Solar/Wind Harmer
-0.029
316404AE1-155 C
Solar/Wind Harmer
1.394
958261AF2-120 GEN
Solar/Wind Harmer
2.829
962861AG1-135 GEN
Solar/Wind Harmer
2.737
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3143526WINTERP
Solar/Wind Harmer
-0.038
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.004
3150851SPRUNCC
Adder
0.297
316314AB2-024 C
Solar/Wind Harmer
0.618
3141766HARMONY
Solar/Wind Harmer
-0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.87
316280AD1-041 GEN
Solar/Wind Harmer
0.544
971777AH1-397 GEN
Solar/Wind Harmer
0.844
3143096IRON208
Adder
0.27
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
315975AC1-164 GENB
Solar/Wind Harmer
0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
30.58
971317AH1-138 GEN
Solar/Wind Harmer
0.894
315671AE2-027_GEN
Solar/Wind Harmer
1.289
316132AB2-190 GEN1
Solar/Wind Harmer
0.72
971069AG2-661 GEN
Solar/Wind Harmer
1.128
3138126ROCKLANDING
Solar/Wind Harmer
0.022
316369SG1_INVT
Solar/Wind Harmer
1.27
961611AG1-000B GEN
Solar/Wind Harmer
3.506
3151171GRAVELC
Adder
0.672
3143336POWHATN
Solar/Wind Harmer
0.84
3145336SMITFLD
Solar/Wind Harmer
-0.028
315773AC2-141 GEN
Solar/Wind Harmer
2.954
316381AD1-082 GEN
Solar/Wind Harmer
0.645
316375AC2-012 GEN
Solar/Wind Harmer
2.434
316036AC1-147 C
Solar/Wind Harmer
0.189
3150981CHESPKA
Adder
0.782
944591AF1-124 GEN
Solar/Wind Harmer
32.129
316072AD1-144
Solar/Wind Harmer
0.142
939411AE1-173 GEN
Solar/Wind Harmer
35.115
940641AE2-051 GEN
Solar/Wind Harmer
6.583
3146456SLIGO L269
Solar/Wind Harmer
-0.007
319010AE1-072 C
Solar/Wind Harmer
1.412
316093AE2-104_GEN
Solar/Wind Harmer
2.03
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
941031AE2-094 GEN
Solar/Wind Harmer
12.958
970937AG2-583 GEN
Solar/Wind Harmer
4.944
315611Z1-036_GEN2
Solar/Wind Harmer
1.693
3130156CHOWAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.546
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.349
3146776BUCKING
Solar/Wind Harmer
-0.003
3146263WOODLND
Solar/Wind Harmer
-0.007
316181AB2-040 GEN
Solar/Wind Harmer
0.919
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3147043LAWRENC
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316190AA2-174 GEN
Solar/Wind Harmer
0.081
316011AB1-132 GEN
Solar/Wind Harmer
1.372
3145963POPLR C
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.139
316478AD1-087 GEN
Solar/Wind Harmer
0.565
315821AE2-092 GEN
Solar/Wind Harmer
1.353
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
959311AF2-222 GEN
Solar/Wind Harmer
6.794
23777801MSM_W1-116
Solar/Wind Helper
0.157
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.31
237002AB1-128_GEN
Solar/Wind Helper
0.332
208835TUHI V3-051
Solar/Wind Helper
0.017
237038AE2-054 C
Solar/Wind Helper
0.191
235067AD1-061 GEN
Solar/Wind Helper
0.308
237085AD2-009_GEN
Solar/Wind Helper
1.053
233935AB2-179 C
Solar/Wind Helper
0.776
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.415
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.454
233997TMININ_4.2
Solar/Wind Helper
0.124
232406W1-004 FULL
Solar/Wind Helper
0.306
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.18
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
207442AE1-156 GEN
Solar/Wind Helper
0.188
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.046
207511W3-106 GEN
Solar/Wind Helper
0.015
20671928W4-073
Solar/Wind Helper
0.051
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
0.998
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.239
208972BECR K09
Solar/Wind Helper
0.176
961331AF2-424 GEN
Solar/Wind Helper
0.234
961421AF2-433 GEN
Solar/Wind Helper
0.233
957921AF2-086 GEN
Solar/Wind Helper
0.231
946691AF1-333 GEN
Solar/Wind Helper
0.23
946741AF1-338 GEN
Solar/Wind Helper
0.23
209071AE2-133 GEN
Solar/Wind Helper
0.042
970257AG2-171 GEN
Solar/Wind Harmer
0.153
315737AD1-076 GEN
Solar/Wind Harmer
1.273
970919AG2-571 GEN
Solar/Wind Harmer
2.119
316023GEN1_S
Solar/Wind Harmer
0.45
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.67
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.198
3146926FARMVIL
Solar/Wind Harmer
-0.004
970087AG2-069 GEN
Solar/Wind Harmer
6.243
3146173TUNIS
Solar/Wind Harmer
-0.007
957481AF2-042 GEN
Solar/Wind Harmer
20.758
971377AH1-170 GEN
Solar/Wind Harmer
0.83
3147623JAMES R
Solar/Wind Harmer
0.103
3156021HOLLOMANSOL
Solar/Wind Harmer
0.892
315693AD1-088 GEN
Solar/Wind Harmer
3.317
960081AF2-299 GEN
Solar/Wind Harmer
0.746
3145683EARLEYS
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.667
972277AH1-723 GEN
Adder
35.088
316087AB2-174 GEN
Solar/Wind Harmer
0.941
3146263WOODLND
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.529
3145963POPLR C
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
971563AH1-280 GEN
Solar/Wind Harmer
0.819
3144293JTRSVLE
Adder
0.139
3144293JTRSVLE
Adder
0.11
3145783HORNRTN
Solar/Wind Harmer
-0.007
970685AG2-442 GEN
Solar/Wind Harmer
5.722
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.007
316034AC1-036 C
Solar/Wind Harmer
0.12
205916AD1-020 GEN
Solar/Wind Helper
1.663
237001AB1-127_GEN
Solar/Wind Helper
0.343
208835TUHI V3-051
Solar/Wind Helper
0.017
235063AE1-101 C2
Solar/Wind Helper
1.173
205932AD2-116_GEN
Solar/Wind Helper
0.407
23777901MDS_W4-102
Solar/Wind Helper
0.113
203975AE1-071-GEN
Solar/Wind Helper
1.876
233918AB1-142 GEN
Solar/Wind Helper
0.305
233944AB2-135 GEN
Solar/Wind Helper
0.358
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.306
232408W1-005 C
Solar/Wind Helper
0.306
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219348LDSOLAR C
Solar/Wind Helper
0.067
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.045
20720528MAN_W1-024
Solar/Wind Helper
0.016
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.009
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.017
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20674928WA_W3-044
Solar/Wind Helper
0.056
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.895
20676228FRD_X1-012
Solar/Wind Helper
0.052
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.239
963151AG1-164 GEN
Solar/Wind Helper
0.239
961341AF2-425 GEN
Solar/Wind Helper
0.234
209137AF2-361 C
Solar/Wind Helper
0.706
212507AE2-042_GEN
Solar/Wind Helper
0.818
946731AF1-337 GEN
Solar/Wind Helper
0.23
LAGNLTFEXP_LAGN->PJM
CLTF
5.819
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.752
TVALTFEXP_TVA->PJM
CLTF
2.93
CPLELTFEXP_CPLE->PJM
CLTF
4.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.589
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.807
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.743
MECLTFEXP_MEC->PJM
CLTF
4.279
SIGELTFEXP_SIGE->PJM
CLTF
0.135
NYPJM->LTFIMP_NY
CLTF
2.537
LGEELTFEXP_LGEE->PJM
CLTF
1.748
WECLTFEXP_WEC->PJM
CLTF
0.938

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.8 %
Rating:1331.98 MVA
Rating Type:B
MVA to Mitigate:1755.6
MW Contribution:
2.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.019
3140676OCCOQUN
50/50
0.016
3138216PACIFIC
Solar/Wind Harmer
0.025
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.698
3150381LDYSMT2
Adder
12.153
972213AH1-691 GEN
Adder
2.056
972215AH1-692 GEN
Adder
2.056
315651AD1-115 GEN
Solar/Wind Harmer
0
316164AC1-076 GEN
Solar/Wind Harmer
0.129
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.087
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
3141873WAN 176
Solar/Wind Harmer
0.017
970189AG2-124 GEN
Solar/Wind Harmer
2.502
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.159
971283AH1-107 GEN
Solar/Wind Harmer
1.159
971285AH1-108 GEN
Adder
0.63
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316159AE1-175 C
Solar/Wind Harmer
0.071
315697AD1-025 GEN
Solar/Wind Harmer
0.088
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151191GRAVEL3
Adder
5.855
3151211GRAVEL5
Adder
5.855
971445AH1-216 GEN
Solar/Wind Harmer
5.713
3143316POE
Solar/Wind Harmer
0.321
970657AG2-426 GEN
Solar/Wind Harmer
0.592
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.077
316311AC2-079 GEN
Solar/Wind Harmer
2.299
957871AF2-081 GEN
Solar/Wind Harmer
3.983
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.042
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316258AE1-075 C
Solar/Wind Harmer
0.059
3146396TANGLEW
Solar/Wind Harmer
0.218
3145176PASQUOTANK
Solar/Wind Harmer
0.049
315814AE2-033 C
Solar/Wind Harmer
6.193
970533AG2-339 GEN
Solar/Wind Harmer
5.901
970673AG2-436 GEN
Solar/Wind Harmer
9.667
3130156CHOWAN
Solar/Wind Harmer
0.077
3130156CHOWAN
Solar/Wind Harmer
0.077
971967AH1-528 GEN
Solar/Wind Harmer
12.296
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.431
315733AD1-074 GEN2
Solar/Wind Harmer
0.431
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.806
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
3.973
970581AG2-369 GEN
Solar/Wind Harmer
3.417
316463AE2-346 GEN
Solar/Wind Harmer
0.064
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.148
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
3137643SOCKMAN
Solar/Wind Harmer
0.293
315652AC1-086 GEN
Solar/Wind Harmer
8.072
316426AA2-053 GEN
Solar/Wind Harmer
0.245
972205AH1-687 GEN
Adder
3.128
971845AH1-439 GEN
Solar/Wind Harmer
3.318
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
316486AD2-202 GEN
Solar/Wind Harmer
0.074
3146033SCOT NK
Solar/Wind Harmer
0.29
946301AF1-294 GEN
Solar/Wind Harmer
1.421
961791AG1-021 GEN
Solar/Wind Harmer
0.691
316210AC1-098 GEN
Solar/Wind Harmer
0.664
970683AG2-441 GEN
Solar/Wind Harmer
4.325
970681AG2-440 GEN
Solar/Wind Harmer
2.871
970831AG2-522 GEN
Solar/Wind Harmer
3.061
316274AC1-208 GEN
Solar/Wind Harmer
0.369
3144303KENBRDG
Solar/Wind Harmer
0.057
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316327AA2-057 GEN
Solar/Wind Harmer
0.104
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.026
3145573BETHELC
Solar/Wind Harmer
0.07
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
3150011OMF A
50/50
0.213
972223AH1-696 GEN
50/50
9.014
3150151POSSMC1
50/50
1.141
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.208
3150211REMNGT1
50/50
13.121
972201AH1-685 GEN
50/50
2.279
3150281M RUN A
Adder
13.337
971685AH1-345 GEN
Solar/Wind Harmer
0.729
316447AC1-158 HLD
Solar/Wind Harmer
1.006
316044AC1-158 PL1
Solar/Wind Harmer
0.458
972197AH1-683 GEN
Adder
1.977
972219AH1-694 GEN
Adder
1.423
316254AC1-120 GEN1
Solar/Wind Harmer
3.292
316170AC1-121 GEN2
Solar/Wind Harmer
1.13
972135AH1-637 GEN
Solar/Wind Harmer
0.78
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.208
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.497
316337AD2-073 GEN
Solar/Wind Harmer
0.076
3150351NORNECKC2
Adder
0.868
3141726DUNNSVL
Solar/Wind Harmer
0.347
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
2.855
962861AG1-135 GEN
Solar/Wind Harmer
2.759
3151751LOISA D
Adder
5.59
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3142433PROV 92
Solar/Wind Harmer
0.336
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
315975AC1-164 GENB
Solar/Wind Harmer
0.026
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.434
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.784
3143226MDLTHAN
Solar/Wind Harmer
0.083
971317AH1-138 GEN
Solar/Wind Harmer
0.617
316132AB2-190 GEN1
Solar/Wind Harmer
0.439
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.459
961611AG1-000B GEN
Solar/Wind Harmer
4.282
3151171GRAVELC
Adder
0.867
3145336SMITFLD
Solar/Wind Harmer
0.324
315773AC2-141 GEN
Solar/Wind Harmer
2.95
316381AD1-082 GEN
Solar/Wind Harmer
0.082
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.014
3150981CHESPKA
Adder
1.005
944591AF1-124 GEN
Solar/Wind Harmer
18.181
316072AD1-144
Solar/Wind Harmer
0.029
939411AE1-173 GEN
Solar/Wind Harmer
34.104
3146456SLIGO L269
Solar/Wind Harmer
0.08
319010AE1-072 C
Solar/Wind Harmer
0.398
940641AE2-051 GEN
Solar/Wind Harmer
6.384
316093AE2-104_GEN
Solar/Wind Harmer
1.34
3143336POWHATN
Solar/Wind Harmer
1.41
3146516WINFALL
Solar/Wind Harmer
0.255
3146516WINFALL
Solar/Wind Harmer
0.079
941031AE2-094 GEN
Solar/Wind Harmer
14.385
3130156CHOWAN
Solar/Wind Harmer
0.077
315816AE2-034 GEN
Solar/Wind Harmer
0.327
3145663CRESWEL
Solar/Wind Harmer
0.214
971163AH1-040 GEN
Solar/Wind Harmer
6.123
315737AD1-076 GEN
Solar/Wind Harmer
0.97
970937AG2-583 GEN
Solar/Wind Harmer
4.632
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.603
316023GEN1_S
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.667
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.335
970087AG2-069 GEN
Solar/Wind Harmer
5.959
960081AF2-299 GEN
Solar/Wind Harmer
0.713
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.149
957481AF2-042 GEN
Solar/Wind Harmer
19.733
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.538
3145963POPLR C
Solar/Wind Harmer
0.073
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.663
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
971563AH1-280 GEN
Solar/Wind Harmer
0.768
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
970685AG2-442 GEN
Solar/Wind Harmer
5.367
972277AH1-723 GEN
Adder
42.768
3146293MARTNCO
Solar/Wind Harmer
0.066
316129AC1-054 GEN
Solar/Wind Harmer
0.267
316034AC1-036 C
Solar/Wind Harmer
0.005
971377AH1-170 GEN
Solar/Wind Harmer
0.762
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.047
315785AD2-033 C
Solar/Wind Harmer
0.577
316131AB2-060 GEN
Solar/Wind Harmer
0.221
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316494AC1-189 GEN
Solar/Wind Harmer
0.237
3146233WITAKRS
Solar/Wind Harmer
0.277
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3145493TOT1
Solar/Wind Harmer
0.309
3152111X4-039 GT1
50/50
1.844
315747AE2-019 GEN
50/50
13.161
3150021OMF B
50/50
0.213
3150101POSSM6S
50/50
1.293
3150081POSSM6A
50/50
0.849
3150151POSSMC1
50/50
1.141
3150151POSSMC1
50/50
1.141
3150231REMNGT3
50/50
0.781
3150241REMNGT4
50/50
13.296
972199AH1-684 GEN
50/50
2.016
972217AH1-693 GEN
50/50
1.753
963691AG1-221 GEN
Solar/Wind Harmer
2.31
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3141196NOKESVL
Solar/Wind Harmer
0.428
3150301M RUN C
Adder
13.329
3150291M RUN B
Adder
13.23
3150331BIRCHWDA
Adder
16.601
3150401LDYSMT4
Adder
12.659
3150371LDYSMT1
Adder
12.232
316223AC1-118
Solar/Wind Harmer
0.064
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.117
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.883
3151761LOISA E
Adder
11.397
3151721LOISA A
Adder
5.561
316473AC1-191 GEN
Solar/Wind Harmer
0.29
3142416OLDCHRC
Solar/Wind Harmer
0.82
3141766HARMONY
Solar/Wind Harmer
1.127
3141873WAN 176
Solar/Wind Harmer
1.502
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.431
970293AG2-193 GEN
Solar/Wind Harmer
0.898
316075AC2-137 C
Solar/Wind Harmer
0.022
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
970133AG2-095 GEN
Solar/Wind Harmer
0.793
316458AB2-190 GEN2
Solar/Wind Harmer
0.439
3150921YORKTN3
Adder
2.065
315778AD1-151 GEN
Solar/Wind Harmer
6.568
3144216WINCHST
Adder
0.309
961611AG1-000B GEN
Solar/Wind Harmer
2.178
3151171GRAVELC
Adder
1.14
315813AE1-149 C
Solar/Wind Harmer
4.327
3145336SMITFLD
Solar/Wind Harmer
0.032
3144536CHRHLND
Solar/Wind Harmer
0.012
970657AG2-426 GEN
Solar/Wind Harmer
1.809
3151101ELIZAR3
Adder
7.476
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.116
944601AF1-125 GEN
Solar/Wind Harmer
17.837
316017AA1-139 ULT1
Solar/Wind Harmer
0.043
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.924
316246AF1-032 C
Solar/Wind Harmer
0.036
3143336POWHATN
Solar/Wind Harmer
1.198
316321Z2-027
Solar/Wind Harmer
0.014
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.078
3145273HOLLAND
Solar/Wind Harmer
0.059
944011AF1-069 GEN
Solar/Wind Harmer
4.7
3146376EDENTON
Solar/Wind Harmer
0.077
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.215
3146206CASHIE
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.668
3146173TUNIS
Solar/Wind Harmer
0.075
3146263WOODLND
Solar/Wind Harmer
0.074
316181AB2-040 GEN
Solar/Wind Harmer
0.105
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3145963POPLR C
Solar/Wind Harmer
0.073
316011AB1-132 GEN
Solar/Wind Harmer
1.331
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
972003AH1-546 GEN
Solar/Wind Harmer
2.538
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.251
3147133PAMPLIN
Solar/Wind Harmer
0.226
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.37
972255AH1-712 GEN
Adder
36.701
3145933PARMELE
Solar/Wind Harmer
0.072
959311AF2-222 GEN
Solar/Wind Harmer
6.364
970257AG2-171 GEN
Solar/Wind Harmer
2.288
971775AH1-396 GEN
Solar/Wind Harmer
0.114
970221AG2-151 GEN
Solar/Wind Harmer
3.81
964241AG1-285 GEN
Solar/Wind Harmer
4.743
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
2.442
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3150091POSSM6B
50/50
0.849
3150071POSSM 5
50/50
52.154
3150181POSSMC2
50/50
1.151
3150181POSSMC2
50/50
1.141
3150181POSSMC2
50/50
1.141
316045AC1-158 PL2
Solar/Wind Harmer
1.464
316450AC1-158 RIC
Solar/Wind Harmer
0.122
3150391LDYSMT3
Adder
12.635
972195AH1-682 GEN
Adder
1.66
315673AE1-157 GEN
Solar/Wind Harmer
6.386
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.912
3150341NORNECKC1
Adder
0.905
966001AG1-469 GEN
Solar/Wind Harmer
0.051
3151731LOISA B
Adder
5.59
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316312AB1-027
Solar/Wind Harmer
0.15
316156AD2-030 GEN
Solar/Wind Harmer
0.062
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
3150681DARBY 2
Adder
6.037
3150671DARBY 1
Adder
6.03
315976AC1-164 GENA
Solar/Wind Harmer
0.883
316169AC1-164_GENC
Solar/Wind Harmer
0.763
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.434
971223AH1-071 GEN
Solar/Wind Harmer
0.889
944641AF1-129 GEN
Adder
39.347
316033AB2-134 GEN
Solar/Wind Harmer
0
316294AC1-161 GEN
Solar/Wind Harmer
1.396
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.192
3145506HICKORY
Solar/Wind Harmer
0.048
316349AD2-085 GEN
Solar/Wind Harmer
0.053
316339AD2-160 GEN
Solar/Wind Harmer
0.128
316388AE2-253 GEN
Solar/Wind Harmer
0.249
3137176SLIGO L2192
Solar/Wind Harmer
0.318
3146456SLIGO L269
Solar/Wind Harmer
1.414
3130086AYDLETT
Solar/Wind Harmer
0.319
315835AF2-110_GEN
Solar/Wind Harmer
0.547
3146386ELIZ CT
Solar/Wind Harmer
0.079
316313AB2-026
Solar/Wind Harmer
0.049
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146626S HERTFORD
Solar/Wind Harmer
0.078
3144356SAPONY
Solar/Wind Harmer
0.656
316315AB2-025 C
Solar/Wind Harmer
0.063
316336AC2-165 C
Solar/Wind Harmer
3.964
315742AE1-103 GEN
Solar/Wind Harmer
1.163
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.323
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.435
970933AG2-581 GEN
Solar/Wind Harmer
6.095
316065AD1-022 GEN
Solar/Wind Harmer
3.468
316365GEN2_N
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
316140AB2-099
Solar/Wind Harmer
0.026
970099AG2-077 GEN
Solar/Wind Harmer
7.893
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
970301AG2-198 GEN
Solar/Wind Harmer
3.132
962571AG1-106 GEN
Solar/Wind Harmer
1.044
3146776BUCKING
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.297
3145783HORNRTN
Solar/Wind Harmer
1.037
3145783HORNRTN
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.218
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.172
972193AH1-681 GEN
Adder
1.64
3145933PARMELE
Solar/Wind Harmer
0.143
3145933PARMELE
Solar/Wind Harmer
0.072
970323AG2-213 GEN
Solar/Wind Harmer
3.051
316005AA1-067
Solar/Wind Harmer
0.076
315724AD1-057 GEN
Solar/Wind Harmer
1.362
3145573BETHELC
Solar/Wind Harmer
0.07
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.639
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205943AE1-185 GEN
Solar/Wind Helper
0.388
205956AE1-196_GEN
Solar/Wind Helper
0.386
959381AF2-229 GEN
Solar/Wind Helper
0.257
20390526W1-045 C
Solar/Wind Helper
0.253
233915AB1-141 GEN
Solar/Wind Helper
0.305
233940AF2-379 C
Solar/Wind Helper
0.037
233901CHERRYDALE C
Solar/Wind Helper
0.14
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
228728W1-130C
Solar/Wind Helper
0.032
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.034
20720728JCB_W1-129
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
20673828FLE_V3-070
Solar/Wind Helper
0.05
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
315821AE2-092 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
4.902
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
971623AH1-311 GEN
Solar/Wind Harmer
0.138
270494AE1-108_GEN
Solar/Wind Harmer
0.797
3148013FISHERV
Solar/Wind Harmer
0.065
971683AH1-343 GEN
Solar/Wind Harmer
2.374
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316283AC2-100 C
Solar/Wind Harmer
0.124
316123AC1-075 GEN
Solar/Wind Harmer
0.082
3151861LOWMORA
Adder
0.644
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
237038AE2-054 C
Solar/Wind Helper
0.174
235067AD1-061 GEN
Solar/Wind Helper
0.282
237085AD2-009_GEN
Solar/Wind Helper
0.975
233935AB2-179 C
Solar/Wind Helper
0.775
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
232406W1-004 FULL
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.181
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
3145493TOT1
Solar/Wind Harmer
0.161
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
962561AG1-105 GEN
Solar/Wind Harmer
3.315
961601AG1-000A GEN
Solar/Wind Harmer
1.225
316049AB1-081 GEN
Solar/Wind Harmer
0.392
316263AC1-034 GEN
Solar/Wind Harmer
2.619
964791AG1-342 GEN
Solar/Wind Harmer
1.319
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316118AC1-105 GEN
Solar/Wind Harmer
0.174
971761AH1-387 GEN
Solar/Wind Harmer
1.229
942751AE2-291 GEN
Solar/Wind Harmer
3.269
3132123MT JACKSON
Solar/Wind Harmer
0.182
970117AG2-086 GEN
Solar/Wind Harmer
1.398
970117AG2-086 GEN
Solar/Wind Harmer
0.932
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
237080AD1-060 GEN
Solar/Wind Helper
0.222
316359AB2-059 GEN
Solar/Wind Harmer
0.245
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.121
970401AG2-262 GEN
Solar/Wind Harmer
0.403
3147983MERCK5
Solar/Wind Harmer
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.485
208835TUHI V3-051
Solar/Wind Helper
0.017
237001AB1-127_GEN
Solar/Wind Helper
0.308
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
23777901MDS_W4-102
Solar/Wind Helper
0.106
203975AE1-071-GEN
Solar/Wind Helper
1.719
233918AB1-142 GEN
Solar/Wind Helper
0.305
233944AB2-135 GEN
Solar/Wind Helper
0.357
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
235062AE1-101 C1
Solar/Wind Helper
1.069
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.343
233994AC2-023 GEN
Solar/Wind Helper
0.579
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207459AE1-142 C O1
Solar/Wind Helper
0.17
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.056
20676428JCR_X2-075
Solar/Wind Helper
0.039
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.241
209027LOR2_Q27
Solar/Wind Helper
0.559
212266LOR1
Solar/Wind Helper
0.163
209029WAYMART-WD
Solar/Wind Helper
0.444
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.467
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
207442AE1-156 GEN
Solar/Wind Helper
0.189
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
1.008
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.237
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.01
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.017
207484AF2-139 C O1
Solar/Wind Helper
0.048
207530AG1-191 GEN
Solar/Wind Helper
0.038
20674928WA_W3-044
Solar/Wind Helper
0.057
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.902
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
946731AF1-337 GEN
Solar/Wind Helper
0.234
209137AF2-361 C
Solar/Wind Helper
0.711
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.237
946751AF1-339 GEN
Solar/Wind Helper
0.234
209071AE2-133 GEN
Solar/Wind Helper
0.042
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.532
TVALTFEXP_TVA->PJM
CLTF
3.177
CPLELTFEXP_CPLE->PJM
CLTF
5.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.822
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.552
MECLTFEXP_MEC->PJM
CLTF
4.431
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
2.582
LGEELTFEXP_LGEE->PJM
CLTF
1.798
WECLTFEXP_WEC->PJM
CLTF
0.958

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.4 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1720.2
MW Contribution:
3.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3138216PACIFIC
Solar/Wind Harmer
-0.003
970053AG2-049 GEN
Adder
1.705
315651AD1-115 GEN
Solar/Wind Harmer
4.548
316164AC1-076 GEN
Solar/Wind Harmer
0.844
3141426STAFORD
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.143
3150411LDYSMT5
Adder
10.892
3150381LDYSMT2
Adder
10.424
972213AH1-691 GEN
Adder
1.763
972215AH1-692 GEN
Adder
1.763
944491AF1-114 GEN
Solar/Wind Harmer
2.607
316468AD1-105 GEN
Solar/Wind Harmer
1.005
3141813NORNECK
Solar/Wind Harmer
-0.009
316233AE1-074 FULL
Solar/Wind Harmer
0.231
971281AH1-106 GEN
Solar/Wind Harmer
1.394
971283AH1-107 GEN
Solar/Wind Harmer
1.394
3141783LANCAST
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316059AD1-063 C
Solar/Wind Harmer
0.193
957601AF2-054 GEN
Solar/Wind Harmer
0.256
3143873LANEXA
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.002
971285AH1-108 GEN
Adder
0.573
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
957831AF2-077 GEN
Solar/Wind Harmer
0.255
3138283WHITEMARSH
Solar/Wind Harmer
0.013
316382AG1-145 C
Solar/Wind Harmer
0.254
316159AE1-175 C
Solar/Wind Harmer
0.226
315839AE2-212 C
Solar/Wind Harmer
0.253
315697AD1-025 GEN
Solar/Wind Harmer
1.697
3151201GRAVEL4
Adder
5.424
3151221GRAVEL6
Adder
5.418
3151191GRAVEL3
Adder
5.356
3151211GRAVEL5
Adder
5.356
3143316POE
Solar/Wind Harmer
-0.033
971445AH1-216 GEN
Solar/Wind Harmer
5.168
316236AE1-162_GEN
Solar/Wind Harmer
0.251
316258AE1-075 C
Solar/Wind Harmer
0.202
316405AF2-144 C
Solar/Wind Harmer
0.213
970657AG2-426 GEN
Solar/Wind Harmer
0.524
3151081ELIZAR1
Adder
6.78
3151091ELIZAR2
Adder
6.662
316316AC1-027 C
Solar/Wind Harmer
0.254
315833AF1-017_GEN
Solar/Wind Harmer
1.571
316311AC2-079 GEN
Solar/Wind Harmer
4.173
316018AA1-139 ULT2
Solar/Wind Harmer
0.707
957871AF2-081 GEN
Solar/Wind Harmer
4.136
3146406KITTY HAWK
Solar/Wind Harmer
0.007
313526AB2-022
Solar/Wind Harmer
0.221
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.151
970533AG2-339 GEN
Solar/Wind Harmer
5.483
315814AE2-033 C
Solar/Wind Harmer
7.588
970673AG2-436 GEN
Solar/Wind Harmer
17.761
315800Z1-036_GEN1
Solar/Wind Harmer
1.999
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
971967AH1-528 GEN
Solar/Wind Harmer
15.148
972205AH1-687 GEN
Adder
3.031
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.599
315733AD1-074 GEN2
Solar/Wind Harmer
1.599
316322AB2-045
Solar/Wind Harmer
0.266
971845AH1-439 GEN
Solar/Wind Harmer
4.206
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.452
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.913
970581AG2-369 GEN
Solar/Wind Harmer
4.225
316463AE2-346 GEN
Solar/Wind Harmer
0.126
3145513AHOSKIE
Solar/Wind Harmer
0.068
961941AG1-037 GEN
Solar/Wind Harmer
0.059
3145513AHOSKIE
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.175
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.031
3152111X4-039 GT1
50/50
2.013
315747AE2-019 GEN
50/50
14.046
963691AG1-221 GEN
Solar/Wind Harmer
2.518
971455AH1-223 GEN
Solar/Wind Harmer
2.518
3141196NOKESVL
Solar/Wind Harmer
-0.049
3150241REMNGT4
Adder
12.627
972199AH1-684 GEN
Adder
1.915
972217AH1-693 GEN
Adder
1.665
3150301M RUN C
Adder
13.419
3150291M RUN B
Adder
13.319
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.847
3150151POSSMC1
Adder
0.847
3147666LOUISA
Solar/Wind Harmer
-0.022
3151761LOISA E
Adder
11.045
3151721LOISA A
Adder
5.39
3150331BIRCHWDA
Adder
13.822
3150401LDYSMT4
Adder
10.858
3150371LDYSMT1
Adder
10.492
966881AG1-559 GEN
Solar/Wind Harmer
0.268
971781AH1-399 GEN
Solar/Wind Harmer
0.542
316223AC1-118
Solar/Wind Harmer
0.236
3141906WESTMOR
Solar/Wind Harmer
-0.003
316077AC2-138 C
Solar/Wind Harmer
0.182
3150351NORNECKC2
Adder
0.782
316473AC1-191 GEN
Solar/Wind Harmer
0.93
316484AD2-074 GEN
Solar/Wind Harmer
2.167
961951AG1-038 GEN
Solar/Wind Harmer
1.134
3142416OLDCHRC
Solar/Wind Harmer
0.866
970293AG2-193 GEN
Solar/Wind Harmer
1.069
316075AC2-137 C
Solar/Wind Harmer
0.23
3141766HARMONY
Solar/Wind Harmer
0.761
316203AE2-005 GEN
Solar/Wind Harmer
3.602
3141873WAN 176
Solar/Wind Harmer
1.014
3141843SHACKLE
Adder
0.389
3150861SPRUNCD
Adder
0.35
3143096IRON208
Adder
0.318
3143096IRON208
Adder
0.312
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
0.951
316458AB2-190 GEN2
Solar/Wind Harmer
0.85
315778AD1-151 GEN
Solar/Wind Harmer
7.492
3150921YORKTN3
Adder
1.882
3144216WINCHST
Adder
0.282
961611AG1-000B GEN
Solar/Wind Harmer
1.766
3151171GRAVELC
Adder
1.042
315813AE1-149 C
Solar/Wind Harmer
5.222
3145336SMITFLD
Solar/Wind Harmer
-0.003
3143336POWHATN
Solar/Wind Harmer
0.841
3144536CHRHLND
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
1.68
3151101ELIZAR3
Adder
6.866
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
37.785
944601AF1-125 GEN
Solar/Wind Harmer
37.195
3142956BIRDNECK
Solar/Wind Harmer
0.445
316017AA1-139 ULT1
Solar/Wind Harmer
0.667
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.956
316305AF2-043 C
Solar/Wind Harmer
0.248
316246AF1-032 C
Solar/Wind Harmer
0.167
316320Y1-086
Solar/Wind Harmer
0.482
316321Z2-027
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
944011AF1-069 GEN
Solar/Wind Harmer
4.79
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
972003AH1-546 GEN
Solar/Wind Harmer
3.236
3156081AA2-088 GEN
Solar/Wind Harmer
2.574
315735AD1-075 GEN1
Solar/Wind Harmer
0.799
3146776BUCKING
Solar/Wind Harmer
-0.003
970917AG2-570 GEN
Solar/Wind Harmer
19.76
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.005
3146173TUNIS
Solar/Wind Harmer
-0.008
970221AG2-151 GEN
Solar/Wind Harmer
4.898
966621AG1-532 GEN
Solar/Wind Harmer
0.159
972255AH1-712 GEN
Adder
35.633
942461AE2-259 GEN
Solar/Wind Harmer
1.175
3146263WOODLND
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.085
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.005
316190AA2-174 GEN
Solar/Wind Harmer
0.095
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.62
3147133PAMPLIN
Solar/Wind Harmer
-0.024
316317KELFORD C
Solar/Wind Harmer
0.359
3145823KELFORD
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.164
316478AD1-087 GEN
Solar/Wind Harmer
0.668
315821AE2-092 GEN
Solar/Wind Harmer
1.599
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
959311AF2-222 GEN
Solar/Wind Harmer
8.024
3151861LOWMORA
Adder
0.673
3152541MT STMG
Adder
0.592
23777801MSM_W1-116
Solar/Wind Helper
0.111
226910AB2-157 C
Solar/Wind Helper
0.012
208835TUHI V3-051
Solar/Wind Helper
0.019
227287AC2-120 GEN
Solar/Wind Helper
0.268
233935AB2-179 C
Solar/Wind Helper
1.008
233933AB2-153 GEN
Solar/Wind Helper
0.184
232422X3-066 FULL
Solar/Wind Helper
0.09
233987AB2-037 GEN
Solar/Wind Helper
1.854
232417X3-008 C
Solar/Wind Helper
0.184
233964AF2-378 GEN
Solar/Wind Helper
0.033
316411AF1-147_GEN1
Solar/Wind Harmer
1.196
316006AB2-029 C
Solar/Wind Harmer
0.63
316045AC1-158 PL2
Solar/Wind Harmer
3.165
316450AC1-158 RIC
Solar/Wind Harmer
0.264
3150071POSSM 5
Adder
38.706
3150181POSSMC2
Adder
0.854
3150181POSSMC2
Adder
0.847
3150181POSSMC2
Adder
0.847
966001AG1-469 GEN
Solar/Wind Harmer
0.179
3151731LOISA B
Adder
5.418
3150391LDYSMT3
Adder
10.838
972195AH1-682 GEN
Adder
1.424
315673AE1-157 GEN
Solar/Wind Harmer
6.743
972189AH1-679 GEN
Adder
1.303
3150341NORNECKC1
Adder
0.808
3150341NORNECKC1
Adder
0.801
966871AG1-558 GEN
Solar/Wind Harmer
0.26
966871AG1-558 GEN
Solar/Wind Harmer
0.089
316487AF1-042 GEN
Solar/Wind Harmer
1.134
3142296MT RD221
Adder
0.244
971223AH1-071 GEN
Solar/Wind Harmer
1.073
316312AB1-027
Solar/Wind Harmer
0.289
3143526WINTERP
Solar/Wind Harmer
-0.044
3142366NRTHEST
Adder
0.249
3150691DARBY 3
Adder
5.482
3150701DARBY 4
Adder
5.469
3150681DARBY 2
Adder
5.463
3150671DARBY 1
Adder
5.457
316441AF1-014 GEN
Solar/Wind Harmer
0.576
315666AE1-190 GEN
Solar/Wind Harmer
0.257
316156AD2-030 GEN
Solar/Wind Harmer
0.227
315976AC1-164 GENA
Solar/Wind Harmer
1.94
316169AC1-164_GENC
Solar/Wind Harmer
1.676
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
35.868
316240AF1-291 C
Solar/Wind Harmer
0.254
316033AB2-134 GEN
Solar/Wind Harmer
2.708
316294AC1-161 GEN
Solar/Wind Harmer
2.694
316313AB2-026
Solar/Wind Harmer
0.224
316083AB2-161 GEN
Solar/Wind Harmer
1.35
3150991CHESPKB
Adder
0.775
3150991CHESPKB
Adder
0.756
316185AD1-033 GEN
Solar/Wind Harmer
0.873
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.02
3145506HICKORY
Solar/Wind Harmer
-0.005
316336AC2-165 C
Solar/Wind Harmer
5.168
316349AD2-085 GEN
Solar/Wind Harmer
0.734
316339AD2-160 GEN
Solar/Wind Harmer
0.556
316388AE2-253 GEN
Solar/Wind Harmer
0.556
3137176SLIGO L2192
Solar/Wind Harmer
-0.033
3146456SLIGO L269
Solar/Wind Harmer
0.976
3130086AYDLETT
Solar/Wind Harmer
-0.033
315835AF2-110_GEN
Solar/Wind Harmer
1.03
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.483
316433W1029_GEN2
Solar/Wind Harmer
1.483
316435W1029_GEN3
Solar/Wind Harmer
1.483
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
971761AH1-387 GEN
Solar/Wind Harmer
4.557
3144356SAPONY
Solar/Wind Harmer
0.285
316315AB2-025 C
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
1.923
3146376EDENTON
Solar/Wind Harmer
0.24
3146376EDENTON
Solar/Wind Harmer
0.24
972185AH1-677 GEN
Adder
4.03
972187AH1-678 GEN
Adder
2.035
970933AG2-581 GEN
Solar/Wind Harmer
7.508
315614AA2-178 GEN
Solar/Wind Harmer
0.86
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
316065AD1-022 GEN
Solar/Wind Harmer
3.952
316365GEN2_N
Solar/Wind Harmer
0.531
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
3.93
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
9.803
316140AB2-099
Solar/Wind Harmer
0.053
972193AH1-681 GEN
Adder
1.592
313506AB2-031 GEN
Solar/Wind Harmer
0.625
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
962571AG1-106 GEN
Solar/Wind Harmer
1.115
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.064
958211AF2-115 GEN
Solar/Wind Harmer
1.209
3144293JTRSVLE
Adder
0.164
3145783HORNRTN
Solar/Wind Harmer
0.917
3145783HORNRTN
Solar/Wind Harmer
0.733
3145783HORNRTN
Solar/Wind Harmer
0.229
3145783HORNRTN
Solar/Wind Harmer
0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
970323AG2-213 GEN
Solar/Wind Harmer
3.839
237006AB1-125 GEN
Solar/Wind Helper
0.127
223401AF1-299 GEN
Solar/Wind Helper
0.38
223402AF1-300 C
Solar/Wind Helper
0.38
233930AB2-032 GEN
Solar/Wind Helper
0.302
233982AB2-133 GEN
Solar/Wind Helper
0.284
232436AB1-176 C
Solar/Wind Helper
0.035
232424Y1-079 C
Solar/Wind Helper
0.092
234036AF2-325 C
Solar/Wind Helper
0.033
233946AB2-136 GEN
Solar/Wind Helper
0.45
233994AC2-023 GEN
Solar/Wind Helper
0.76
232428Y3-058 C
Solar/Wind Helper
0.267
232410W1-006 C
Solar/Wind Helper
0.401
234015AF2-250 C
Solar/Wind Helper
0.03
233952AC2-187 GEN
Solar/Wind Helper
0.184
233954AC2-188 GEN
Solar/Wind Helper
0.184
230511AF1-262
Solar/Wind Helper
0.011
230433AD2-135 GEN
Solar/Wind Helper
0.013
228754AB1-001 C
Solar/Wind Helper
0.02
219904AC1-010 C
Solar/Wind Helper
0.047
219912AD2-042 GEN
Solar/Wind Helper
0.116
219272CLEANLIGHT C
Solar/Wind Helper
0.02
219906AC1-017 C
Solar/Wind Helper
0.032
219607WPEMNERT C
Solar/Wind Helper
0.062
219304NAMERICA C
Solar/Wind Helper
0.101
214067T20SOLAR
Solar/Wind Helper
0.009
20720828JCB_W4-025
Solar/Wind Helper
0.048
207459AE1-142 C O1
Solar/Wind Helper
0.221
20714828MDF_W3-079
Solar/Wind Helper
0.099
20742028HF_AC1-207
Solar/Wind Helper
0.106
218438BLK ROCK C
Solar/Wind Helper
0.021
20675428EAM_W2-061
Solar/Wind Helper
0.012
217081WEATEXAS C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.005
217204WCALDSOLAR C
Solar/Wind Helper
0.002
316426AA2-053 GEN
Solar/Wind Harmer
0.782
315652AC1-086 GEN
Solar/Wind Harmer
8.728
946301AF1-294 GEN
Solar/Wind Harmer
1.983
961791AG1-021 GEN
Solar/Wind Harmer
0.967
316486AD2-202 GEN
Solar/Wind Harmer
0.195
316174AB2-169 GEN
Solar/Wind Harmer
1.19
970683AG2-441 GEN
Solar/Wind Harmer
5.445
970681AG2-440 GEN
Solar/Wind Harmer
3.614
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151881LOWMORC
Adder
0.668
3151881LOWMORC
Adder
0.657
3151861LOWMORA
Adder
0.647
972257AH1-713 GEN
Adder
0.696
23544701WINZ1-113
Adder
0.24
237030AB1-096 C
Solar/Wind Helper
0.069
237025AB1-124 C
Solar/Wind Helper
0.169
23779801AA1-109
Solar/Wind Helper
0.182
205917AD1-020 ES
Solar/Wind Helper
0.323
205943AE1-185 GEN
Solar/Wind Helper
0.425
205956AE1-196_GEN
Solar/Wind Helper
0.424
233915AB1-141 GEN
Solar/Wind Helper
0.398
233901CHERRYDALE C
Solar/Wind Helper
0.184
233940AF2-379 C
Solar/Wind Helper
0.049
232432Z2-076 GEN
Solar/Wind Helper
0.053
230434AG1-499 GEN
Solar/Wind Helper
0.178
228728W1-130C
Solar/Wind Helper
0.042
230407AD2-065 C
Solar/Wind Helper
0.031
219258KINSLEYDEP C
Solar/Wind Helper
0.059
227927V4-067C
Solar/Wind Helper
0.008
219615MILLCREEK C
Solar/Wind Helper
0.02
20720728JCB_W1-129
Solar/Wind Helper
0.044
20715028HAN_X4-015
Solar/Wind Helper
0.044
207445AB1-138_GEN
Solar/Wind Helper
0.079
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.144
20675528CPH_W2-050
Solar/Wind Helper
0.085
218526CNTRALGAS2 C
Solar/Wind Helper
0.121
20673828FLE_V3-070
Solar/Wind Helper
0.065
20676128MHD_W3-029
Solar/Wind Helper
0.072
20676428JCR_X2-075
Solar/Wind Helper
0.051
226929AD2-058 GEN
Solar/Wind Helper
0.066
964851AG1-348 GEN
Solar/Wind Helper
0.046
207408W3-077 C
Solar/Wind Helper
0.062
20675128HRM_W1-127
Solar/Wind Helper
0.022
961261AF2-417 GEN
Solar/Wind Helper
0.309
959381AF2-229 GEN
Solar/Wind Helper
0.231
20390526W1-045 C
Solar/Wind Helper
0.226
209027LOR2_Q27
Solar/Wind Helper
0.713
212266LOR1
Solar/Wind Helper
0.208
209029WAYMART-WD
Solar/Wind Helper
0.567
209054AE2-059 GEN
Solar/Wind Helper
0.054
959431AF2-234 GEN
Solar/Wind Helper
0.595
233923SMA
Solar/Wind Helper
0.594
233997TMININ_4.2
Solar/Wind Helper
0.162
232406W1-004 FULL
Solar/Wind Helper
0.401
233950AC2-186 GEN
Solar/Wind Helper
0.092
232434Z2-077 GEN
Solar/Wind Helper
0.1
230415AB2-049 C
Solar/Wind Helper
0.023
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.039
219914AD2-027 C
Solar/Wind Helper
0.089
219291REEVESSOUT C
Solar/Wind Helper
0.009
219236SOUTHERNHQ C
Solar/Wind Helper
0.004
218660EHAMPSOLAR C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.031
959561AF2-247 GEN
Solar/Wind Helper
0.016
20715728PEM_W1-119
Solar/Wind Helper
0.073
20714928UPF_X1-085
Solar/Wind Helper
0.004
205941AD2-115 GEN
Solar/Wind Helper
0.376
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.234
219612MATRIX C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.022
219249CENTRALDIV C
Solar/Wind Helper
0.008
207442AE1-156 GEN
Solar/Wind Helper
0.244
20673728F2S_V4-070
Solar/Wind Helper
0.022
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.003
207510AF2-138 C
Solar/Wind Helper
0.06
207511W3-106 GEN
Solar/Wind Helper
0.02
207437AD2-070 GEN
Solar/Wind Helper
0.102
20671928W4-073
Solar/Wind Helper
0.066
20674128FR_U2-059
Solar/Wind Helper
0.003
209116AE2-175 GEN
Solar/Wind Helper
1.293
211065PSPA IPP
Solar/Wind Helper
0.11
963161AG1-165 GEN
Solar/Wind Helper
0.31
208972BECR K09
Solar/Wind Helper
0.228
961331AF2-424 GEN
Solar/Wind Helper
0.303
961421AF2-433 GEN
Solar/Wind Helper
0.302
957921AF2-086 GEN
Solar/Wind Helper
0.299
946691AF1-333 GEN
Solar/Wind Helper
0.298
946741AF1-338 GEN
Solar/Wind Helper
0.298
209071AE2-133 GEN
Solar/Wind Helper
0.054
237002AB1-128_GEN
Solar/Wind Helper
0.213
237038AE2-054 C
Solar/Wind Helper
0.12
235067AD1-061 GEN
Solar/Wind Helper
0.193
970257AG2-171 GEN
Solar/Wind Harmer
0.181
20674328GAR_V4-001
Solar/Wind Helper
0.017
20675928HOL_W4-097
Solar/Wind Helper
0.037
207471AF2-354 C
Solar/Wind Helper
0.124
20674828DL_W4-046
Solar/Wind Helper
0.006
961431AF2-434 GEN
Solar/Wind Helper
0.302
946751AF1-339 GEN
Solar/Wind Helper
0.298
238221AF1-254 C O1
Solar/Wind Helper
0.123
235062AE1-101 C1
Solar/Wind Helper
0.75
237080AD1-060 GEN
Solar/Wind Helper
0.152
3152131X4-039 ST
50/50
3.148
3152121X4-039 GT2
50/50
2
316415AF1-147_GEN2
Solar/Wind Harmer
1.196
3150221REMNGT2
Adder
12.544
3150211REMNGT1
Adder
12.461
972201AH1-685 GEN
Adder
2.164
3150281M RUN A
Adder
13.427
971685AH1-345 GEN
Solar/Wind Harmer
0.962
316254AC1-120 GEN1
Solar/Wind Harmer
3.829
316170AC1-121 GEN2
Solar/Wind Harmer
1.276
316447AC1-158 HLD
Solar/Wind Harmer
2.175
316044AC1-158 PL1
Solar/Wind Harmer
0.989
315683AE1-153 C
Solar/Wind Harmer
9.352
972223AH1-696 GEN
Adder
6.689
3150151POSSMC1
Adder
0.847
3147666LOUISA
Solar/Wind Harmer
-0.038
316192AB2-158 GEN
Solar/Wind Harmer
1.118
3151751LOISA D
Adder
5.418
3141346CRANES
Adder
0.097
972197AH1-683 GEN
Adder
1.696
972219AH1-694 GEN
Adder
1.221
966881AG1-559 GEN
Solar/Wind Harmer
0.092
957971AF2-091 GEN
Solar/Wind Harmer
0.887
972135AH1-637 GEN
Solar/Wind Harmer
0.886
316337AD2-073 GEN
Solar/Wind Harmer
0.234
3150351NORNECKC2
Adder
0.769
964211AG1-282 GEN
Solar/Wind Harmer
0.26
3141726DUNNSVL
Solar/Wind Harmer
-0.034
316404AE1-155 C
Solar/Wind Harmer
1.647
958261AF2-120 GEN
Solar/Wind Harmer
3.344
962861AG1-135 GEN
Solar/Wind Harmer
3.234
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3142416OLDCHRC
Solar/Wind Harmer
-0.008
3143526WINTERP
Solar/Wind Harmer
-0.044
3138133OCRAN
Solar/Wind Harmer
-0.005
316314AB2-024 C
Solar/Wind Harmer
0.73
3141766HARMONY
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.027
316280AD1-041 GEN
Solar/Wind Harmer
0.642
971777AH1-397 GEN
Solar/Wind Harmer
0.997
3150851SPRUNCC
Adder
0.35
3143096IRON208
Adder
0.318
3142433PROV 92
Solar/Wind Harmer
-0.034
315975AC1-164 GENB
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
36.103
971317AH1-138 GEN
Solar/Wind Harmer
1.055
315671AE2-027_GEN
Solar/Wind Harmer
1.522
316132AB2-190 GEN1
Solar/Wind Harmer
0.85
971069AG2-661 GEN
Solar/Wind Harmer
1.332
3138126ROCKLANDING
Solar/Wind Harmer
0.026
316369SG1_INVT
Solar/Wind Harmer
1.5
961611AG1-000B GEN
Solar/Wind Harmer
4.139
3151171GRAVELC
Adder
0.793
3145336SMITFLD
Solar/Wind Harmer
-0.033
315773AC2-141 GEN
Solar/Wind Harmer
3.486
3143336POWHATN
Solar/Wind Harmer
0.99
316381AD1-082 GEN
Solar/Wind Harmer
0.761
316375AC2-012 GEN
Solar/Wind Harmer
2.873
316036AC1-147 C
Solar/Wind Harmer
0.224
3150981CHESPKA
Adder
0.923
944591AF1-124 GEN
Solar/Wind Harmer
37.921
316072AD1-144
Solar/Wind Harmer
0.167
939411AE1-173 GEN
Solar/Wind Harmer
41.429
940641AE2-051 GEN
Solar/Wind Harmer
7.765
3146456SLIGO L269
Solar/Wind Harmer
-0.008
319010AE1-072 C
Solar/Wind Harmer
1.667
316093AE2-104_GEN
Solar/Wind Harmer
2.397
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.008
964051AG1-259 GEN
Solar/Wind Helper
0.044
964061AG1-260 GEN
Solar/Wind Helper
0.044
959421AF2-233 GEN
Solar/Wind Helper
0.297
209067AE2-060 GEN
Solar/Wind Helper
0.052
941031AE2-094 GEN
Solar/Wind Harmer
15.288
970937AG2-583 GEN
Solar/Wind Harmer
5.831
315611Z1-036_GEN2
Solar/Wind Harmer
1.999
3130156CHOWAN
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.645
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.498
315737AD1-076 GEN
Solar/Wind Harmer
1.504
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.501
316023GEN1_S
Solar/Wind Harmer
0.531
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.973
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3146926FARMVIL
Solar/Wind Harmer
-0.005
970087AG2-069 GEN
Solar/Wind Harmer
7.37
3146173TUNIS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
24.507
3156021HOLLOMANSOL
Solar/Wind Harmer
1.054
971377AH1-170 GEN
Solar/Wind Harmer
0.98
3147623JAMES R
Solar/Wind Harmer
0.121
960081AF2-299 GEN
Solar/Wind Harmer
0.881
315693AD1-088 GEN
Solar/Wind Harmer
3.916
972277AH1-723 GEN
Adder
41.523
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.787
316087AB2-174 GEN
Solar/Wind Harmer
1.111
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.625
3145963POPLR C
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
971563AH1-280 GEN
Solar/Wind Harmer
0.967
3144293JTRSVLE
Adder
0.164
3144293JTRSVLE
Adder
0.13
3145783HORNRTN
Solar/Wind Harmer
-0.008
970685AG2-442 GEN
Solar/Wind Harmer
6.757
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.008
316034AC1-036 C
Solar/Wind Harmer
0.142
205916AD1-020 GEN
Solar/Wind Helper
1.501
208835TUHI V3-051
Solar/Wind Helper
0.019
205932AD2-116_GEN
Solar/Wind Helper
0.424
233918AB1-142 GEN
Solar/Wind Helper
0.398
233944AB2-135 GEN
Solar/Wind Helper
0.467
232426Y1-080 FULL
Solar/Wind Helper
0.031
233996TM1833_GEN
Solar/Wind Helper
0.162
233998TM1NIN_3.36
Solar/Wind Helper
0.162
232404W1-003 C
Solar/Wind Helper
0.401
232408W1-005 C
Solar/Wind Helper
0.401
228729W2-030 C
Solar/Wind Helper
0.085
219766PARADISE C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.026
219686LUMSOLAR_N C
Solar/Wind Helper
0.031
219348LDSOLAR C
Solar/Wind Helper
0.088
20716028EGP_W2-019
Solar/Wind Helper
0.014
20715828PEM_W1-120
Solar/Wind Helper
0.073
219276PARKLANDSO C
Solar/Wind Helper
0.068
963711AG1-223 GEN
Solar/Wind Helper
0.049
20714528FRN_Y2-051
Solar/Wind Helper
0.043
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.059
20720528MAN_W1-024
Solar/Wind Helper
0.021
218524CNTRALGAS1 C
Solar/Wind Helper
0.121
218440SUMMTASSOC C
Solar/Wind Helper
0.012
218428ETC SOLAR C
Solar/Wind Helper
0.004
219908AB1-139 C
Solar/Wind Helper
0.055
219919AE1-041 FULL
Solar/Wind Helper
0.003
20673628F1S_V4-069
Solar/Wind Helper
0.022
20671828STAW2-080
Solar/Wind Helper
0.02
217209CENTRL HS C
Solar/Wind Helper
0.006
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.022
207530AG1-191 GEN
Solar/Wind Helper
0.049
207439AE1-081 C O1
Solar/Wind Helper
0.014
20676328BVR_Y1-020
Solar/Wind Helper
0.02
20674628WNG_W3-110
Solar/Wind Helper
0.066
20674928WA_W3-044
Solar/Wind Helper
0.073
207484AF2-139 C O1
Solar/Wind Helper
0.062
20676228FRD_X1-012
Solar/Wind Helper
0.068
20675728RH_W2-091
Solar/Wind Helper
0.06
207518AF1-320_GEN
Solar/Wind Helper
1.157
20675828AU_W4-064
Solar/Wind Helper
0.022
211065PSPA IPP
Solar/Wind Helper
0.11
961301AF2-421 GEN
Solar/Wind Helper
0.31
963151AG1-164 GEN
Solar/Wind Helper
0.31
961341AF2-425 GEN
Solar/Wind Helper
0.303
212507AE2-042_GEN
Solar/Wind Helper
1.059
946731AF1-337 GEN
Solar/Wind Helper
0.298
203975AE1-071-GEN
Solar/Wind Helper
1.568
209137AF2-361 C
Solar/Wind Helper
0.867
237001AB1-127_GEN
Solar/Wind Helper
0.222
235063AE1-101 C2
Solar/Wind Helper
0.75
LAGNLTFEXP_LAGN->PJM
CLTF
6.94
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.759
TVALTFEXP_TVA->PJM
CLTF
3.494
CPLELTFEXP_CPLE->PJM
CLTF
5
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.695
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.692
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.818
MECLTFEXP_MEC->PJM
CLTF
5.118
SIGELTFEXP_SIGE->PJM
CLTF
0.161
NYPJM->LTFIMP_NY
CLTF
3.275
LGEELTFEXP_LGEE->PJM
CLTF
2.092
WECLTFEXP_WEC->PJM
CLTF
1.123
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.1

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.33 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1162.8
MW Contribution:
15.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.671
316303AF2-085
50/50
2.056
3151541CLOVER2
50/50
2.335
3151601KERR 3
50/50
0.217
3151611KERR 4
50/50
0.217
3151621KERR 5
50/50
0.217
3151631KERR 6
50/50
0.217
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.288
3151281ROARAP4
50/50
0.087
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971845AH1-439 GEN
Solar/Wind Harmer
16.331
316258AE1-075 C
Solar/Wind Harmer
0.188
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
11.554
970681AG2-440 GEN
Solar/Wind Harmer
7.669
3144303KENBRDG
Solar/Wind Harmer
0.139
316486AD2-202 GEN
Solar/Wind Harmer
0.111
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.021
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.947
970673AG2-436 GEN
Solar/Wind Harmer
9.878
970533AG2-339 GEN
Solar/Wind Harmer
5.968
3137643SOCKMAN
Solar/Wind Harmer
0.315
970085AG2-068 GEN
Solar/Wind Harmer
4.091
970581AG2-369 GEN
Solar/Wind Harmer
3.519
316426AA2-053 GEN
Solar/Wind Harmer
0.254
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.748
315652AC1-086 GEN
Solar/Wind Harmer
7.784
316274AC1-208 GEN
Solar/Wind Harmer
0.364
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
316210AC1-098 GEN
Solar/Wind Harmer
0.642
3146033SCOT NK
Solar/Wind Harmer
0.276
316463AE2-346 GEN
Solar/Wind Harmer
0.059
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316327AA2-057 GEN
Solar/Wind Harmer
0.1
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
970657AG2-426 GEN
Solar/Wind Harmer
0.477
315732AD1-074 GEN1
Solar/Wind Harmer
0.37
315733AD1-074 GEN2
Solar/Wind Harmer
0.37
3130546PLYMOUTH
Solar/Wind Harmer
0.065
316311AC2-079 GEN
Solar/Wind Harmer
1.854
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
313526AB2-022
Solar/Wind Harmer
0.034
957861AF2-080 GEN
Solar/Wind Harmer
2.738
3146406KITTY HAWK
Solar/Wind Harmer
0.008
957871AF2-081 GEN
Solar/Wind Harmer
3.154
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
316316AC1-027 C
Solar/Wind Harmer
0.06
3151081ELIZAR1
Adder
5.774
3151091ELIZAR2
Adder
5.674
971445AH1-216 GEN
Solar/Wind Harmer
4.323
3151201GRAVEL4
Adder
4.409
3151221GRAVEL6
Adder
4.404
3151191GRAVEL3
Adder
4.353
3151211GRAVEL5
Adder
4.353
315697AD1-025 GEN
Solar/Wind Harmer
0.065
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.524
970909AG2-566 GEN
50/50
2.396
3144293JTRSVLE
50/50
0.529
970535AG2-341 GEN
50/50
2.11
3151581KERR 1
50/50
0.078
3152661PLYWOOD A
50/50
0.215
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.318
315241AE2-183_GT1
50/50
1.314
972185AH1-677 GEN
50/50
4.763
3151261ROARAP2
50/50
0.093
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
316336AC2-165 C
Solar/Wind Harmer
14.549
316313AB2-026
Solar/Wind Harmer
0.157
970301AG2-198 GEN
Solar/Wind Harmer
9.584
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.177
958211AF2-115 GEN
Solar/Wind Harmer
2.507
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.398
970099AG2-077 GEN
Solar/Wind Harmer
11.72
964791AG1-342 GEN
Solar/Wind Harmer
2.09
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.466
313506AB2-031 GEN
Solar/Wind Harmer
0.246
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316365GEN2_N
Solar/Wind Harmer
0.163
3144356SAPONY
Solar/Wind Harmer
0.607
316315AB2-025 C
Solar/Wind Harmer
0.058
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
316140AB2-099
Solar/Wind Harmer
0.024
315742AE1-103 GEN
Solar/Wind Harmer
1.005
315724AD1-057 GEN
Solar/Wind Harmer
1.284
316065AD1-022 GEN
Solar/Wind Harmer
3.005
315614AA2-178 GEN
Solar/Wind Harmer
0.368
316349AD2-085 GEN
Solar/Wind Harmer
0.043
316049AB1-081 GEN
Solar/Wind Harmer
0.366
316263AC1-034 GEN
Solar/Wind Harmer
2.446
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.254
3146456SLIGO L269
Solar/Wind Harmer
1.121
3137176SLIGO L2192
Solar/Wind Harmer
0.252
316339AD2-160 GEN
Solar/Wind Harmer
0.101
316388AE2-253 GEN
Solar/Wind Harmer
0.197
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316005AA1-067
Solar/Wind Harmer
0.067
942751AE2-291 GEN
Solar/Wind Harmer
3.431
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.763
316294AC1-161 GEN
Solar/Wind Harmer
1.072
316033AB2-134 GEN
Solar/Wind Harmer
0
966001AG1-469 GEN
Solar/Wind Helper
0.206
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.529
970413AG2-270 GEN
50/50
10.247
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.096
3150861SPRUNCD
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
972003AH1-546 GEN
Solar/Wind Harmer
15.439
970221AG2-151 GEN
Solar/Wind Harmer
21.636
3146776BUCKING
Solar/Wind Harmer
0.132
270494AE1-108_GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.801
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.693
959311AF2-222 GEN
Solar/Wind Harmer
15.886
970257AG2-171 GEN
Solar/Wind Harmer
5.551
971775AH1-396 GEN
Solar/Wind Harmer
0.278
964241AG1-285 GEN
Solar/Wind Harmer
9.805
958131AF2-107 GEN
Solar/Wind Harmer
3.652
316478AD1-087 GEN
Solar/Wind Harmer
0.38
3147043LAWRENC
Solar/Wind Harmer
0.059
971683AH1-343 GEN
Solar/Wind Harmer
2.983
316181AB2-040 GEN
Solar/Wind Harmer
0.114
944011AF1-069 GEN
Solar/Wind Harmer
4.753
970917AG2-570 GEN
Solar/Wind Harmer
6.903
3156081AA2-088 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
1.284
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.358
3146173TUNIS
Solar/Wind Harmer
0.069
316123AC1-075 GEN
Solar/Wind Harmer
0.092
3145823KELFORD
Solar/Wind Harmer
0.069
315722AD1-056 GEN
Solar/Wind Harmer
2.302
3145273HOLLAND
Solar/Wind Harmer
0.05
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
316222AC1-221 GEN
Solar/Wind Harmer
0.27
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.483
316283AC2-100 C
Solar/Wind Harmer
0.127
970657AG2-426 GEN
Solar/Wind Harmer
1.458
315735AD1-075 GEN1
Solar/Wind Harmer
0.185
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.549
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.011
316246AF1-032 C
Solar/Wind Harmer
0.028
3145933PARMELE
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.733
316017AA1-139 ULT1
Solar/Wind Harmer
0.034
944581AF1-123 GEN
Solar/Wind Harmer
14.243
944601AF1-125 GEN
Solar/Wind Harmer
14.023
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.848
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.025
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.82
316458AB2-190 GEN2
Solar/Wind Harmer
0.321
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.128
3151931BEARGRDN S1
50/50
5.466
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.529
3144293JTRSVLE
50/50
0.418
970119AG2-088 GEN
50/50
15.416
3151531CLOVER1
50/50
2.353
3151591KERR 2
50/50
0.217
3151641KERR 7
50/50
0.217
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.199
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.318
3151281ROARAP4
50/50
0.093
3150851SPRUNCC
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.218
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
3143336POWHATN
Solar/Wind Harmer
4.472
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.905
316034AC1-036 C
Solar/Wind Harmer
0.012
315785AD2-033 C
Solar/Wind Harmer
1.344
316131AB2-060 GEN
Solar/Wind Harmer
0.421
315693AD1-088 GEN
Solar/Wind Harmer
6.345
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.3
970401AG2-262 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
4.185
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.36
960081AF2-299 GEN
Solar/Wind Harmer
0.793
941031AE2-094 GEN
Solar/Wind Harmer
14.548
970919AG2-571 GEN
Solar/Wind Harmer
2.761
970087AG2-069 GEN
Solar/Wind Harmer
6.137
3145783HORNRTN
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.151
940641AE2-051 GEN
Solar/Wind Harmer
5.985
316023GEN1_S
Solar/Wind Harmer
0.163
939411AE1-173 GEN
Solar/Wind Harmer
30.688
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.298
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.397
316381AD1-082 GEN
Solar/Wind Harmer
0.066
315737AD1-076 GEN
Solar/Wind Harmer
0.833
315816AE2-034 GEN
Solar/Wind Harmer
0.276
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.168
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.229
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.215
319010AE1-072 C
Solar/Wind Harmer
0.316
3146456SLIGO L269
Solar/Wind Harmer
0.063
944591AF1-124 GEN
Solar/Wind Harmer
14.293
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
0
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.022
315773AC2-141 GEN
Solar/Wind Harmer
2.266
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.171
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316132AB2-190 GEN1
Solar/Wind Harmer
0.321
944631AF1-128 GEN
Adder
26.814
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.905
3147666LOUISA
Solar/Wind Helper
0.521
LAGNLTFEXP_LAGN->PJM
CLTF
1.975
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.463
TVALTFEXP_TVA->PJM
CLTF
0.975
CPLELTFEXP_CPLE->PJM
CLTF
4.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.728
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.137
MECLTFEXP_MEC->PJM
CLTF
0.549
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.615
LGEELTFEXP_LGEE->PJM
CLTF
0.138
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.37 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1389.21
MW Contribution:
20.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.635
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.467
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.402
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.293
970221AG2-151 GEN
Solar/Wind Harmer
28.434
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.927
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.892
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.504
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
970133AG2-095 GEN
Solar/Wind Harmer
0.026
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.114
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.731
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.52
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.595
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.538
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
316192AB2-158 GEN
Solar/Wind Helper
1.015
3147666LOUISA
Solar/Wind Helper
0.588
3147983MERCK5
Solar/Wind Helper
0.055
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.649
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:167.37 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1389.18
MW Contribution:
20.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.634
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.466
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.519
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.594
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.537
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.113
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.73
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.401
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.292
970221AG2-151 GEN
Solar/Wind Harmer
28.433
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.926
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.891
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
970133AG2-095 GEN
Solar/Wind Harmer
0.026
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
316192AB2-158 GEN
Solar/Wind Helper
1.016
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.648
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.8 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1326.36
MW Contribution:
20.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
957871AF2-081 GEN
Solar/Wind Harmer
3.285
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.8 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1326.36
MW Contribution:
20.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
957871AF2-081 GEN
Solar/Wind Harmer
3.285
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.81 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1060.79
MW Contribution:
26.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.579
3144293JTRSVLE
50/50
0.618
972003AH1-546 GEN
Solar/Wind Harmer
26.738
970221AG2-151 GEN
Solar/Wind Harmer
37.543
3146776BUCKING
Solar/Wind Harmer
-0.019
270494AE1-108_GEN
Solar/Wind Harmer
12.249
3146926FARMVIL
Solar/Wind Harmer
-0.024
315821AE2-092 GEN
Solar/Wind Harmer
7.754
942461AE2-259 GEN
Solar/Wind Harmer
5.223
3147133PAMPLIN
Solar/Wind Harmer
-0.092
959311AF2-222 GEN
Solar/Wind Harmer
23.56
970257AG2-171 GEN
Solar/Wind Harmer
8.15
971775AH1-396 GEN
Solar/Wind Harmer
1.533
958131AF2-107 GEN
Solar/Wind Harmer
6.444
964241AG1-285 GEN
Solar/Wind Harmer
13.685
316478AD1-087 GEN
Solar/Wind Harmer
0.939
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971683AH1-343 GEN
Solar/Wind Harmer
3.682
316123AC1-075 GEN
Solar/Wind Harmer
0.805
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
27.258
316322AB2-045
Solar/Wind Harmer
1.775
971845AH1-439 GEN
Solar/Wind Harmer
27.551
946301AF1-294 GEN
Solar/Wind Harmer
7.02
961791AG1-021 GEN
Solar/Wind Harmer
3.424
970683AG2-441 GEN
Solar/Wind Harmer
17.408
970681AG2-440 GEN
Solar/Wind Harmer
11.554
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.445
316239AB2-077_GEN
Solar/Wind Harmer
0.445
316486AD2-202 GEN
Solar/Wind Harmer
0.275
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.429
946281AF1-292 GEN
Solar/Wind Harmer
0.145
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
970909AG2-566 GEN
50/50
2.805
3144293JTRSVLE
50/50
0.618
970535AG2-341 GEN
50/50
2.051
316336AC2-165 C
Solar/Wind Harmer
42.179
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
970301AG2-198 GEN
Solar/Wind Harmer
14.775
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.28
970323AG2-213 GEN
Solar/Wind Harmer
10.867
313527AB2-043 GEN
Solar/Wind Harmer
2.468
316237AB2-079_GEN
Solar/Wind Harmer
0.445
962561AG1-105 GEN
Solar/Wind Harmer
6.959
964791AG1-342 GEN
Solar/Wind Harmer
2.534
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.73
970099AG2-077 GEN
Solar/Wind Harmer
13.191
315687AD1-152 GEN
Solar/Wind Harmer
1.188
316248AF1-058 C
Solar/Wind Harmer
0.284
970933AG2-581 GEN
Solar/Wind Harmer
6.805
942751AE2-291 GEN
Solar/Wind Harmer
4.456
966001AG1-469 GEN
Solar/Wind Helper
0.159
3151931BEARGRDN S1
50/50
7.207
3151911BEARGRDN G1
50/50
5.579
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.488
970937AG2-583 GEN
Solar/Wind Harmer
48.556
971377AH1-170 GEN
Solar/Wind Harmer
7.509
3147623JAMES R
Solar/Wind Harmer
0.929
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
971563AH1-280 GEN
Solar/Wind Harmer
3.424
970685AG2-442 GEN
Solar/Wind Harmer
22.673
316034AC1-036 C
Solar/Wind Harmer
0.403
315785AD2-033 C
Solar/Wind Harmer
4.657
316131AB2-060 GEN
Solar/Wind Harmer
1.684
315693AD1-088 GEN
Solar/Wind Harmer
7.148
970401AG2-262 GEN
Solar/Wind Harmer
0.774
957481AF2-042 GEN
Solar/Wind Harmer
32.976
971065AG2-659 GEN
Solar/Wind Harmer
4.765
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.734
962751AG1-124 GEN
Solar/Wind Harmer
4.607
960081AF2-299 GEN
Solar/Wind Harmer
0.726
LAGNLTFEXP_LAGN->PJM
CLTF
1.582
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.17
TVALTFEXP_TVA->PJM
CLTF
0.79
CPLELTFEXP_CPLE->PJM
CLTF
2.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.391
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.289
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.592
MECLTFEXP_MEC->PJM
CLTF
0.532
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.163
WECLTFEXP_WEC->PJM
CLTF
0.076

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:173.1 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1145.53
MW Contribution:
15.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.671
316303AF2-085
50/50
2.056
3151541CLOVER2
50/50
2.335
3151601KERR 3
50/50
0.217
3151611KERR 4
50/50
0.217
3151621KERR 5
50/50
0.217
3151631KERR 6
50/50
0.217
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.288
3151281ROARAP4
50/50
0.087
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971845AH1-439 GEN
Solar/Wind Harmer
16.331
316258AE1-075 C
Solar/Wind Harmer
0.188
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
11.554
970681AG2-440 GEN
Solar/Wind Harmer
7.669
3144303KENBRDG
Solar/Wind Harmer
0.139
316486AD2-202 GEN
Solar/Wind Harmer
0.111
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.021
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.947
970673AG2-436 GEN
Solar/Wind Harmer
9.878
970533AG2-339 GEN
Solar/Wind Harmer
5.968
3137643SOCKMAN
Solar/Wind Harmer
0.315
970085AG2-068 GEN
Solar/Wind Harmer
4.091
970581AG2-369 GEN
Solar/Wind Harmer
3.519
316426AA2-053 GEN
Solar/Wind Harmer
0.254
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.748
315652AC1-086 GEN
Solar/Wind Harmer
7.784
316274AC1-208 GEN
Solar/Wind Harmer
0.364
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
316210AC1-098 GEN
Solar/Wind Harmer
0.642
3146033SCOT NK
Solar/Wind Harmer
0.276
316463AE2-346 GEN
Solar/Wind Harmer
0.059
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316327AA2-057 GEN
Solar/Wind Harmer
0.1
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
970657AG2-426 GEN
Solar/Wind Harmer
0.477
315732AD1-074 GEN1
Solar/Wind Harmer
0.37
315733AD1-074 GEN2
Solar/Wind Harmer
0.37
3130546PLYMOUTH
Solar/Wind Harmer
0.065
316311AC2-079 GEN
Solar/Wind Harmer
1.854
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
313526AB2-022
Solar/Wind Harmer
0.034
957861AF2-080 GEN
Solar/Wind Harmer
2.738
3146406KITTY HAWK
Solar/Wind Harmer
0.008
957871AF2-081 GEN
Solar/Wind Harmer
3.154
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
316316AC1-027 C
Solar/Wind Harmer
0.06
3151081ELIZAR1
Adder
5.774
3151091ELIZAR2
Adder
5.674
971445AH1-216 GEN
Solar/Wind Harmer
4.323
3151201GRAVEL4
Adder
4.409
3151221GRAVEL6
Adder
4.404
3151191GRAVEL3
Adder
4.353
3151211GRAVEL5
Adder
4.353
315697AD1-025 GEN
Solar/Wind Harmer
0.065
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.524
970909AG2-566 GEN
50/50
2.396
3144293JTRSVLE
50/50
0.529
970535AG2-341 GEN
50/50
2.11
3151581KERR 1
50/50
0.078
3152661PLYWOOD A
50/50
0.215
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.318
315241AE2-183_GT1
50/50
1.314
972185AH1-677 GEN
50/50
4.763
3151261ROARAP2
50/50
0.093
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
316336AC2-165 C
Solar/Wind Harmer
14.549
316313AB2-026
Solar/Wind Harmer
0.157
970301AG2-198 GEN
Solar/Wind Harmer
9.584
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.177
958211AF2-115 GEN
Solar/Wind Harmer
2.507
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.398
970099AG2-077 GEN
Solar/Wind Harmer
11.72
964791AG1-342 GEN
Solar/Wind Harmer
2.09
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.466
313506AB2-031 GEN
Solar/Wind Harmer
0.246
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316365GEN2_N
Solar/Wind Harmer
0.163
3144356SAPONY
Solar/Wind Harmer
0.607
316315AB2-025 C
Solar/Wind Harmer
0.058
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
316140AB2-099
Solar/Wind Harmer
0.024
315742AE1-103 GEN
Solar/Wind Harmer
1.005
315724AD1-057 GEN
Solar/Wind Harmer
1.284
316065AD1-022 GEN
Solar/Wind Harmer
3.005
315614AA2-178 GEN
Solar/Wind Harmer
0.368
316349AD2-085 GEN
Solar/Wind Harmer
0.043
316049AB1-081 GEN
Solar/Wind Harmer
0.366
316263AC1-034 GEN
Solar/Wind Harmer
2.446
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.254
3146456SLIGO L269
Solar/Wind Harmer
1.121
3137176SLIGO L2192
Solar/Wind Harmer
0.252
316339AD2-160 GEN
Solar/Wind Harmer
0.101
316388AE2-253 GEN
Solar/Wind Harmer
0.197
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316005AA1-067
Solar/Wind Harmer
0.067
942751AE2-291 GEN
Solar/Wind Harmer
3.431
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.763
316294AC1-161 GEN
Solar/Wind Harmer
1.072
316033AB2-134 GEN
Solar/Wind Harmer
0
966001AG1-469 GEN
Solar/Wind Helper
0.206
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.529
970413AG2-270 GEN
50/50
10.247
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.096
3150861SPRUNCD
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
972003AH1-546 GEN
Solar/Wind Harmer
15.439
970221AG2-151 GEN
Solar/Wind Harmer
21.636
3146776BUCKING
Solar/Wind Harmer
0.132
270494AE1-108_GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.801
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.693
959311AF2-222 GEN
Solar/Wind Harmer
15.886
970257AG2-171 GEN
Solar/Wind Harmer
5.551
971775AH1-396 GEN
Solar/Wind Harmer
0.278
964241AG1-285 GEN
Solar/Wind Harmer
9.805
958131AF2-107 GEN
Solar/Wind Harmer
3.652
316478AD1-087 GEN
Solar/Wind Harmer
0.38
3147043LAWRENC
Solar/Wind Harmer
0.059
971683AH1-343 GEN
Solar/Wind Harmer
2.983
316181AB2-040 GEN
Solar/Wind Harmer
0.114
944011AF1-069 GEN
Solar/Wind Harmer
4.753
970917AG2-570 GEN
Solar/Wind Harmer
6.903
3156081AA2-088 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
1.284
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.358
3146173TUNIS
Solar/Wind Harmer
0.069
316123AC1-075 GEN
Solar/Wind Harmer
0.092
3145823KELFORD
Solar/Wind Harmer
0.069
315722AD1-056 GEN
Solar/Wind Harmer
2.302
3145273HOLLAND
Solar/Wind Harmer
0.05
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
316222AC1-221 GEN
Solar/Wind Harmer
0.27
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.483
316283AC2-100 C
Solar/Wind Harmer
0.127
970657AG2-426 GEN
Solar/Wind Harmer
1.458
315735AD1-075 GEN1
Solar/Wind Harmer
0.185
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.549
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.011
316246AF1-032 C
Solar/Wind Harmer
0.028
3145933PARMELE
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.733
316017AA1-139 ULT1
Solar/Wind Harmer
0.034
944581AF1-123 GEN
Solar/Wind Harmer
14.243
944601AF1-125 GEN
Solar/Wind Harmer
14.023
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.848
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.025
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.82
316458AB2-190 GEN2
Solar/Wind Harmer
0.321
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.128
3151931BEARGRDN S1
50/50
5.466
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.529
3144293JTRSVLE
50/50
0.418
970119AG2-088 GEN
50/50
15.416
3151531CLOVER1
50/50
2.353
3151591KERR 2
50/50
0.217
3151641KERR 7
50/50
0.217
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.199
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.318
3151281ROARAP4
50/50
0.093
3150851SPRUNCC
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.218
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
3143336POWHATN
Solar/Wind Harmer
4.472
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.905
316034AC1-036 C
Solar/Wind Harmer
0.012
315785AD2-033 C
Solar/Wind Harmer
1.344
316131AB2-060 GEN
Solar/Wind Harmer
0.421
315693AD1-088 GEN
Solar/Wind Harmer
6.345
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.3
970401AG2-262 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
4.185
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.36
960081AF2-299 GEN
Solar/Wind Harmer
0.793
941031AE2-094 GEN
Solar/Wind Harmer
14.548
970919AG2-571 GEN
Solar/Wind Harmer
2.761
970087AG2-069 GEN
Solar/Wind Harmer
6.137
3145783HORNRTN
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.151
940641AE2-051 GEN
Solar/Wind Harmer
5.985
316023GEN1_S
Solar/Wind Harmer
0.163
939411AE1-173 GEN
Solar/Wind Harmer
30.688
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.298
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.397
316381AD1-082 GEN
Solar/Wind Harmer
0.066
315737AD1-076 GEN
Solar/Wind Harmer
0.833
315816AE2-034 GEN
Solar/Wind Harmer
0.276
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.168
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.229
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.215
319010AE1-072 C
Solar/Wind Harmer
0.316
3146456SLIGO L269
Solar/Wind Harmer
0.063
944591AF1-124 GEN
Solar/Wind Harmer
14.293
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
0
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.022
315773AC2-141 GEN
Solar/Wind Harmer
2.266
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.171
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316132AB2-190 GEN1
Solar/Wind Harmer
0.321
944631AF1-128 GEN
Adder
26.814
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.905
3147666LOUISA
Solar/Wind Helper
0.521
LAGNLTFEXP_LAGN->PJM
CLTF
1.975
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.463
TVALTFEXP_TVA->PJM
CLTF
0.975
CPLELTFEXP_CPLE->PJM
CLTF
4.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.728
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.137
MECLTFEXP_MEC->PJM
CLTF
0.549
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.615
LGEELTFEXP_LGEE->PJM
CLTF
0.138
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.58 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1371.94
MW Contribution:
20.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.635
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.52
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.595
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.538
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.467
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.402
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.293
970221AG2-151 GEN
Solar/Wind Harmer
28.434
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.927
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.892
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
316192AB2-158 GEN
Solar/Wind Helper
1.015
3147666LOUISA
Solar/Wind Helper
0.588
3147983MERCK5
Solar/Wind Helper
0.055
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.504
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
970133AG2-095 GEN
Solar/Wind Harmer
0.026
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.114
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.731
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.649
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.58 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1371.91
MW Contribution:
20.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.519
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.594
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.537
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.292
970221AG2-151 GEN
Solar/Wind Harmer
28.433
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.926
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.891
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.113
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.73
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
972205AH1-687 GEN
50/50
20.634
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.466
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.401
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
316192AB2-158 GEN
Solar/Wind Helper
1.016
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
970133AG2-095 GEN
Solar/Wind Harmer
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.648
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.82 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1309.09
MW Contribution:
20.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
957871AF2-081 GEN
Solar/Wind Harmer
3.285
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.82 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1309.09
MW Contribution:
20.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
957871AF2-081 GEN
Solar/Wind Harmer
3.285
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.8 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1100.34
MW Contribution:
4.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.203
3151861LOWMORA
50/50
1.129
3152191CUNINGD
50/50
1.775
972255AH1-712 GEN
50/50
53.738
315760AF1-028 GEN
50/50
15.229
3152061BATH 6F
50/50
2.05
3152021BATH 2B
50/50
2.044
3148013FISHERV
Solar/Wind Harmer
0.138
315821AE2-092 GEN
Solar/Wind Harmer
0
970221AG2-151 GEN
Solar/Wind Harmer
6.845
972003AH1-546 GEN
Solar/Wind Harmer
4.369
270494AE1-108_GEN
Solar/Wind Harmer
1.304
3146776BUCKING
Solar/Wind Harmer
0.036
3146926FARMVIL
Solar/Wind Harmer
0.044
958131AF2-107 GEN
Solar/Wind Harmer
1.933
942461AE2-259 GEN
Solar/Wind Harmer
0
3132273ORANGE
Solar/Wind Helper
0.105
3147666LOUISA
Solar/Wind Helper
1.084
972205AH1-687 GEN
50/50
5.88
3151881LOWMORC
50/50
1.12
3151881LOWMORC
50/50
1.102
3151861LOWMORA
50/50
1.085
3152031BATH 3C
50/50
2.047
3152051BATH 5E
50/50
2.046
3152011BATH 1A
50/50
2.044
3152041BATH 4D
50/50
2.043
23503501NHY_Z2-039
50/50
0.005
23503401SHY_Z2-039
50/50
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
3148463FAIRFLD
Solar/Wind Harmer
0.099
971845AH1-439 GEN
Solar/Wind Harmer
4.38
315651AD1-115 GEN
Solar/Wind Helper
0.966
316164AC1-076 GEN
Solar/Wind Helper
1.193
3151931BEARGRDN S1
50/50
1.555
3151911BEARGRDN G1
50/50
1.203
972277AH1-723 GEN
50/50
62.621
971377AH1-170 GEN
Solar/Wind Harmer
1.369
3147623JAMES R
Solar/Wind Harmer
0.297
3146776BUCKING
Solar/Wind Harmer
0.04
970937AG2-583 GEN
Solar/Wind Harmer
6.046
3147983MERCK5
Solar/Wind Harmer
0.038
3146926FARMVIL
Solar/Wind Harmer
0.044
316192AB2-158 GEN
Solar/Wind Helper
3.269
3147666LOUISA
Solar/Wind Helper
1.885
3137383CUSHAW
50/50
0.021
3152181CUNINGC
50/50
0.816
3152171CUNINGB
50/50
0.768
3152161CUNINGA
50/50
0.763
972193AH1-681 GEN
50/50
2.401
3146776BUCKING
Solar/Wind Harmer
0.395
3146776BUCKING
Solar/Wind Harmer
0.032
3132123MT JACKSON
Solar/Wind Harmer
0.208
970117AG2-086 GEN
Solar/Wind Harmer
1.596
970117AG2-086 GEN
Solar/Wind Harmer
1.064
316336AC2-165 C
Solar/Wind Harmer
3.133
966001AG1-469 GEN
Solar/Wind Helper
0.735
316006AB2-029 C
Solar/Wind Helper
0.088
LAGNLTFEXP_LAGN->PJM
CLTF
2.708
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.552
TVALTFEXP_TVA->PJM
CLTF
1.406
CPLELTFEXP_CPLE->PJM
CLTF
0.945
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.548
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.844
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.211
MECLTFEXP_MEC->PJM
CLTF
2.087
SIGELTFEXP_SIGE->PJM
CLTF
0.068
NYPJM->LTFIMP_NY
CLTF
0.744
LGEELTFEXP_LGEE->PJM
CLTF
0.897
WECLTFEXP_WEC->PJM
CLTF
0.46

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.21 %
Rating:1265.1 MVA
Rating Type:C
MVA to Mitigate:1558.74
MW Contribution:
6.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
7.053
971285AH1-108 GEN
50/50
1.706
972205AH1-687 GEN
50/50
6.274
316233AE1-074 FULL
Solar/Wind Harmer
0.96
971281AH1-106 GEN
Solar/Wind Harmer
5.802
971283AH1-107 GEN
Solar/Wind Harmer
5.802
316258AE1-075 C
Solar/Wind Harmer
0.798
316405AF2-144 C
Solar/Wind Harmer
0.843
316322AB2-045
Solar/Wind Harmer
0.471
971845AH1-439 GEN
Solar/Wind Harmer
7.401
315839AE2-212 C
Solar/Wind Harmer
0.418
3143316POE
Solar/Wind Harmer
-0.05
315697AD1-025 GEN
Solar/Wind Harmer
2.493
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
970657AG2-426 GEN
Solar/Wind Harmer
0.737
946301AF1-294 GEN
Solar/Wind Harmer
2.87
961791AG1-021 GEN
Solar/Wind Harmer
1.4
3151201GRAVEL4
Adder
7.241
3151221GRAVEL6
Adder
7.233
3151191GRAVEL3
Adder
7.149
3151211GRAVEL5
Adder
7.149
315814AE2-033 C
Solar/Wind Harmer
10.322
3143873LANEXA
Solar/Wind Harmer
-0.007
970683AG2-441 GEN
Solar/Wind Harmer
7.679
970681AG2-440 GEN
Solar/Wind Harmer
5.097
315833AF1-017_GEN
Solar/Wind Harmer
2.036
971445AH1-216 GEN
Solar/Wind Harmer
6.631
316311AC2-079 GEN
Solar/Wind Harmer
5.401
316236AE1-162_GEN
Solar/Wind Harmer
0.321
3144303KENBRDG
Solar/Wind Harmer
-0.008
316382AG1-145 C
Solar/Wind Harmer
0.311
316159AE1-175 C
Solar/Wind Harmer
0.277
316059AD1-063 C
Solar/Wind Harmer
0.231
957601AF2-054 GEN
Solar/Wind Harmer
0.301
3141873WAN 176
Solar/Wind Harmer
-0.002
970533AG2-339 GEN
Solar/Wind Harmer
6.745
957831AF2-077 GEN
Solar/Wind Harmer
0.301
3138283WHITEMARSH
Solar/Wind Harmer
0.015
970673AG2-436 GEN
Solar/Wind Harmer
21.79
971967AH1-528 GEN
Solar/Wind Harmer
18.701
946281AF1-292 GEN
Solar/Wind Harmer
0.222
3151081ELIZAR1
Adder
8.021
3151091ELIZAR2
Adder
7.882
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316316AC1-027 C
Solar/Wind Harmer
0.3
3138133OCRAN
Solar/Wind Harmer
-0.003
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
316018AA1-139 ULT2
Solar/Wind Harmer
0.83
957871AF2-081 GEN
Solar/Wind Harmer
4.858
3146406KITTY HAWK
Solar/Wind Harmer
0.008
316238AB2-078_GEN
Solar/Wind Harmer
0.291
316239AB2-077_GEN
Solar/Wind Harmer
0.291
313526AB2-022
Solar/Wind Harmer
0.26
3146396TANGLEW
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316486AD2-202 GEN
Solar/Wind Harmer
0.242
315800Z1-036_GEN1
Solar/Wind Harmer
2.352
3137643SOCKMAN
Solar/Wind Harmer
-0.038
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3146043SEABORD
Solar/Wind Harmer
-0.009
316318V4-068
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.009
315652AC1-086 GEN
Solar/Wind Harmer
10.615
316426AA2-053 GEN
Solar/Wind Harmer
0.944
970085AG2-068 GEN
Solar/Wind Harmer
5.847
970581AG2-369 GEN
Solar/Wind Harmer
5.028
970831AG2-522 GEN
Solar/Wind Harmer
4.66
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.15
3145513AHOSKIE
Solar/Wind Harmer
0.081
961941AG1-037 GEN
Solar/Wind Harmer
0.07
3145513AHOSKIE
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.873
315733AD1-074 GEN2
Solar/Wind Harmer
1.873
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
4.051
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
316468AD1-105 GEN
Solar/Wind Harmer
1.039
3146033SCOT NK
Solar/Wind Harmer
-0.036
316210AC1-098 GEN
Solar/Wind Harmer
1.397
316274AC1-208 GEN
Solar/Wind Harmer
0.959
316174AB2-169 GEN
Solar/Wind Harmer
1.37
316327AA2-057 GEN
Solar/Wind Harmer
0.869
3145746EVERETS
Solar/Wind Harmer
-0.034
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
957861AF2-080 GEN
Solar/Wind Harmer
0.148
3150861SPRUNCD
50/50
1.043
3143096IRON208
50/50
0.685
3143096IRON208
50/50
0.671
3151921BEARGRDN G2
50/50
1.284
3143336POWHATN
Solar/Wind Harmer
3.327
972003AH1-546 GEN
Solar/Wind Harmer
6.244
3146776BUCKING
Solar/Wind Harmer
-0.005
970221AG2-151 GEN
Solar/Wind Harmer
8.71
970133AG2-095 GEN
Solar/Wind Harmer
1.552
970293AG2-193 GEN
Solar/Wind Harmer
1.708
3142946ENON
Solar/Wind Harmer
-0.004
316458AB2-190 GEN2
Solar/Wind Harmer
1.317
3146926FARMVIL
Solar/Wind Harmer
-0.008
315778AD1-151 GEN
Solar/Wind Harmer
11.251
315813AE1-149 C
Solar/Wind Harmer
7.808
316075AC2-137 C
Solar/Wind Harmer
0.332
316473AC1-191 GEN
Solar/Wind Harmer
1.314
3142416OLDCHRC
Solar/Wind Harmer
1.229
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
942461AE2-259 GEN
Solar/Wind Harmer
1.815
970657AG2-426 GEN
Solar/Wind Harmer
2.361
961611AG1-000B GEN
Solar/Wind Harmer
2.45
270494AE1-108_GEN
Solar/Wind Harmer
3.008
3147133PAMPLIN
Solar/Wind Harmer
-0.036
3144293JTRSVLE
Adder
0.238
3151171GRAVELC
Adder
1.392
3145336SMITFLD
Solar/Wind Harmer
-0.004
959311AF2-222 GEN
Solar/Wind Harmer
11.091
970257AG2-171 GEN
Solar/Wind Harmer
3.947
971775AH1-396 GEN
Solar/Wind Harmer
0.743
3141843SHACKLE
Adder
0.475
316203AE2-005 GEN
Solar/Wind Harmer
4.406
315821AE2-092 GEN
Solar/Wind Harmer
2.137
3141766HARMONY
Solar/Wind Harmer
0.912
3144216WINCHST
Adder
0.339
3144536CHRHLND
Solar/Wind Harmer
-0.002
3141873WAN 176
Solar/Wind Harmer
1.194
944011AF1-069 GEN
Solar/Wind Harmer
5.893
964241AG1-285 GEN
Solar/Wind Harmer
7.833
3150921YORKTN3
Adder
2.227
3145273HOLLAND
Solar/Wind Harmer
-0.007
966621AG1-532 GEN
Solar/Wind Harmer
0.201
3144873MCLAUGH
Solar/Wind Harmer
0
3147043LAWRENC
Solar/Wind Harmer
-0.006
3151101ELIZAR3
Adder
8.124
316305AF2-043 C
Solar/Wind Harmer
0.295
316246AF1-032 C
Solar/Wind Harmer
0.198
3142956BIRDNECK
Solar/Wind Harmer
0.526
316017AA1-139 ULT1
Solar/Wind Harmer
0.784
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.124
316320Y1-086
Solar/Wind Harmer
0.567
316321Z2-027
Solar/Wind Harmer
0.26
316181AB2-040 GEN
Solar/Wind Harmer
1.345
944581AF1-123 GEN
Solar/Wind Harmer
43.917
944601AF1-125 GEN
Solar/Wind Harmer
43.232
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3156081AA2-088 GEN
Solar/Wind Harmer
3.11
316478AD1-087 GEN
Solar/Wind Harmer
0.827
3146376EDENTON
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
-0.009
970917AG2-570 GEN
Solar/Wind Harmer
23.659
316011AB1-132 GEN
Solar/Wind Harmer
1.971
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.009
3146263WOODLND
Solar/Wind Harmer
-0.009
315735AD1-075 GEN1
Solar/Wind Harmer
0.936
3145796HORNRTN
Solar/Wind Harmer
-0.037
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
316484AD2-074 GEN
Solar/Wind Harmer
2.308
961951AG1-038 GEN
Solar/Wind Harmer
1.207
316317KELFORD C
Solar/Wind Harmer
0.422
3145823KELFORD
Solar/Wind Harmer
-0.009
971781AH1-399 GEN
Solar/Wind Harmer
0.56
3145963POPLR C
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
0.776
315722AD1-056 GEN
Solar/Wind Harmer
3.11
3145933PARMELE
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.177
3146233WITAKRS
Solar/Wind Harmer
-0.006
3150351NORNECKC2
Adder
0.76
3147666LOUISA
Solar/Wind Helper
0.27
3142366NRTHEST
50/50
0.481
3150691DARBY 3
50/50
10.123
3150701DARBY 4
50/50
10.1
3150681DARBY 2
50/50
10.088
3150671DARBY 1
50/50
10.076
944641AF1-129 GEN
50/50
66.472
971223AH1-071 GEN
Solar/Wind Harmer
5.572
3143526WINTERP
Solar/Wind Harmer
-0.185
316313AB2-026
Solar/Wind Harmer
0.887
316336AC2-165 C
Solar/Wind Harmer
18.698
316240AF1-291 C
Solar/Wind Harmer
0.437
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.005
3142946ENON
Solar/Wind Harmer
-0.001
3142296MT RD221
Adder
0.379
316033AB2-134 GEN
Solar/Wind Harmer
3.978
966871AG1-558 GEN
Solar/Wind Harmer
0.367
966871AG1-558 GEN
Solar/Wind Harmer
0.126
316312AB1-027
Solar/Wind Harmer
0.41
316083AB2-161 GEN
Solar/Wind Harmer
1.915
970301AG2-198 GEN
Solar/Wind Harmer
5.837
315976AC1-164 GENA
Solar/Wind Harmer
2.6
316169AC1-164_GENC
Solar/Wind Harmer
2.246
3147133PAMPLIN
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.009
958211AF2-115 GEN
Solar/Wind Harmer
1.75
3144293JTRSVLE
Adder
0.238
3144356SAPONY
Solar/Wind Harmer
0.389
316315AB2-025 C
Solar/Wind Harmer
0.3
316349AD2-085 GEN
Solar/Wind Harmer
0.952
970323AG2-213 GEN
Solar/Wind Harmer
5.263
316441AF1-014 GEN
Solar/Wind Harmer
0.704
315666AE1-190 GEN
Solar/Wind Harmer
0.309
316156AD2-030 GEN
Solar/Wind Harmer
0.268
316365GEN2_N
Solar/Wind Harmer
0.676
315835AF2-110_GEN
Solar/Wind Harmer
1.255
970933AG2-581 GEN
Solar/Wind Harmer
9.314
3150991CHESPKB
Adder
0.919
3150991CHESPKB
Adder
0.897
972185AH1-677 GEN
Adder
4.923
315742AE1-103 GEN
Solar/Wind Harmer
2.334
970099AG2-077 GEN
Solar/Wind Harmer
12.285
972187AH1-678 GEN
Adder
2.479
313527AB2-043 GEN
Solar/Wind Harmer
1.583
316185AD1-033 GEN
Solar/Wind Harmer
1.025
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.023
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.654
316388AE2-253 GEN
Solar/Wind Harmer
0.654
3137176SLIGO L2192
Solar/Wind Harmer
-0.038
3146456SLIGO L269
Solar/Wind Harmer
1.147
3130086AYDLETT
Solar/Wind Harmer
-0.039
316237AB2-079_GEN
Solar/Wind Harmer
0.291
3146386ELIZ CT
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
0.775
316431W1029_GEN1
Solar/Wind Harmer
1.749
316433W1029_GEN2
Solar/Wind Harmer
1.749
316435W1029_GEN3
Solar/Wind Harmer
1.749
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3146376EDENTON
Solar/Wind Harmer
0.282
3146376EDENTON
Solar/Wind Harmer
0.282
3145893MURPHYS
Solar/Wind Harmer
0.264
3145893MURPHYS
Solar/Wind Harmer
-0.017
962571AG1-106 GEN
Solar/Wind Harmer
1.356
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.078
315614AA2-178 GEN
Solar/Wind Harmer
1.01
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145783HORNRTN
Solar/Wind Harmer
1.106
3145783HORNRTN
Solar/Wind Harmer
0.885
3145783HORNRTN
Solar/Wind Harmer
0.277
3145783HORNRTN
Solar/Wind Harmer
0.111
316140AB2-099
Solar/Wind Harmer
0.063
3145796HORNRTN
Solar/Wind Harmer
-0.028
316065AD1-022 GEN
Solar/Wind Harmer
4.634
316294AC1-161 GEN
Solar/Wind Harmer
2.964
316487AF1-042 GEN
Solar/Wind Harmer
1.207
962561AG1-105 GEN
Solar/Wind Harmer
5.071
315687AD1-152 GEN
Solar/Wind Harmer
1.083
964791AG1-342 GEN
Solar/Wind Harmer
1.897
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
972189AH1-679 GEN
Adder
1.32
315724AD1-057 GEN
Solar/Wind Harmer
1.711
3145933PARMELE
Solar/Wind Harmer
-0.017
3145933PARMELE
Solar/Wind Harmer
-0.009
316118AC1-105 GEN
Solar/Wind Harmer
0.587
316005AA1-067
Solar/Wind Harmer
0.172
3150341NORNECKC1
Adder
0.785
3150341NORNECKC1
Adder
0.779
316045AC1-158 PL2
Solar/Wind Helper
2.737
316450AC1-158 RIC
Solar/Wind Helper
0.228
970119AG2-088 GEN
50/50
52.897
3150851SPRUNCC
50/50
1.043
3143096IRON208
50/50
0.685
3151931BEARGRDN S1
50/50
1.659
3151911BEARGRDN G1
50/50
1.284
3143226MDLTHAN
Solar/Wind Harmer
-0.044
3143526WINTERP
Solar/Wind Harmer
-0.185
3143336POWHATN
Solar/Wind Harmer
3.914
970937AG2-583 GEN
Solar/Wind Harmer
15.921
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
60.947
315671AE2-027_GEN
Solar/Wind Harmer
2.537
3146776BUCKING
Solar/Wind Harmer
-0.006
971377AH1-170 GEN
Solar/Wind Harmer
1.742
3147623JAMES R
Solar/Wind Harmer
0.216
316132AB2-190 GEN1
Solar/Wind Harmer
1.317
3146926FARMVIL
Solar/Wind Harmer
-0.008
971069AG2-661 GEN
Solar/Wind Harmer
2
316369SG1_INVT
Solar/Wind Harmer
2.203
3142416OLDCHRC
Solar/Wind Harmer
-0.032
3142416OLDCHRC
Solar/Wind Harmer
-0.012
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
316381AD1-082 GEN
Solar/Wind Harmer
1.08
961611AG1-000B GEN
Solar/Wind Harmer
5.741
315975AC1-164 GENB
Solar/Wind Harmer
0.077
971563AH1-280 GEN
Solar/Wind Harmer
1.4
3144293JTRSVLE
Adder
0.238
3144293JTRSVLE
Adder
0.188
3151171GRAVELC
Adder
1.058
970685AG2-442 GEN
Solar/Wind Harmer
9.645
3145336SMITFLD
Solar/Wind Harmer
-0.042
316034AC1-036 C
Solar/Wind Harmer
0.195
971777AH1-397 GEN
Solar/Wind Harmer
1.22
315785AD2-033 C
Solar/Wind Harmer
2.351
316314AB2-024 C
Solar/Wind Harmer
0.886
315662AE1-191 GEN
Solar/Wind Harmer
1.237
316280AD1-041 GEN
Solar/Wind Harmer
0.773
3141766HARMONY
Solar/Wind Harmer
-0.002
315693AD1-088 GEN
Solar/Wind Harmer
5.08
316023GEN1_S
Solar/Wind Harmer
0.676
3138126ROCKLANDING
Solar/Wind Harmer
0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.919
316072AD1-144
Solar/Wind Harmer
0.202
941031AE2-094 GEN
Solar/Wind Harmer
18.806
939411AE1-173 GEN
Solar/Wind Harmer
49.994
971317AH1-138 GEN
Solar/Wind Harmer
1.241
960081AF2-299 GEN
Solar/Wind Harmer
1.114
316375AC2-012 GEN
Solar/Wind Harmer
3.409
316036AC1-147 C
Solar/Wind Harmer
0.265
3150981CHESPKA
Adder
1.095
3147043LAWRENC
Adder
0.793
957481AF2-042 GEN
Solar/Wind Harmer
30.712
316131AB2-060 GEN
Solar/Wind Harmer
1.055
3138133OCRAN
Solar/Wind Harmer
-0.006
316087AB2-174 GEN
Solar/Wind Harmer
1.386
3146456SLIGO L269
Solar/Wind Harmer
-0.01
319010AE1-072 C
Solar/Wind Harmer
1.959
944591AF1-124 GEN
Solar/Wind Harmer
44.075
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.01
315611Z1-036_GEN2
Solar/Wind Harmer
2.352
3130156CHOWAN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.953
3145893MURPHYS
Solar/Wind Harmer
-0.038
970919AG2-571 GEN
Solar/Wind Harmer
2.995
3145893MURPHYS
Solar/Wind Harmer
0.281
315816AE2-034 GEN
Solar/Wind Harmer
0.757
3145663CRESWEL
Solar/Wind Harmer
-0.026
971163AH1-040 GEN
Solar/Wind Harmer
8.797
3146173TUNIS
Solar/Wind Harmer
-0.009
970087AG2-069 GEN
Solar/Wind Harmer
8.77
3145783HORNRTN
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
0.814
971065AG2-659 GEN
Solar/Wind Harmer
4.651
3146263WOODLND
Solar/Wind Harmer
-0.009
315737AD1-076 GEN
Solar/Wind Harmer
1.761
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.315
3145683EARLEYS
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.24
940641AE2-051 GEN
Solar/Wind Harmer
8.612
315773AC2-141 GEN
Solar/Wind Harmer
3.836
3145823KELFORD
Solar/Wind Harmer
-0.009
962861AG1-135 GEN
Solar/Wind Harmer
3.364
3145963POPLR C
Solar/Wind Harmer
-0.009
316404AE1-155 C
Solar/Wind Harmer
1.699
958261AF2-120 GEN
Solar/Wind Harmer
3.449
970401AG2-262 GEN
Solar/Wind Harmer
0.58
964211AG1-282 GEN
Solar/Wind Harmer
0.261
3141726DUNNSVL
Solar/Wind Harmer
-0.035
3146293MARTNCO
Solar/Wind Harmer
0.054
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
316319Z2-044 C
Solar/Wind Harmer
0.468
3146233WITAKRS
Solar/Wind Harmer
-0.034
3150351NORNECKC2
Adder
0.747
316447AC1-158 HLD
Solar/Wind Helper
1.882
316044AC1-158 PL1
Solar/Wind Helper
0.855
3147666LOUISA
Solar/Wind Helper
0.47
316192AB2-158 GEN
Solar/Wind Helper
0.77
316494AC1-189 GEN
Solar/Wind Harmer
0.036
LAGNLTFEXP_LAGN->PJM
CLTF
3.54
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.498
TVALTFEXP_TVA->PJM
CLTF
1.785
CPLELTFEXP_CPLE->PJM
CLTF
4.775
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.885
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.475
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.143
MECLTFEXP_MEC->PJM
CLTF
1.76
SIGELTFEXP_SIGE->PJM
CLTF
0.054
NYPJM->LTFIMP_NY
CLTF
1.097
LGEELTFEXP_LGEE->PJM
CLTF
0.657
WECLTFEXP_WEC->PJM
CLTF
0.331

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.76 %
Rating:1057.5 MVA
Rating Type:B
MVA to Mitigate:1287.59
MW Contribution:
4.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
7.058
971285AH1-108 GEN
50/50
1.708
972205AH1-687 GEN
50/50
6.264
316233AE1-074 FULL
Solar/Wind Harmer
0.254
971281AH1-106 GEN
Solar/Wind Harmer
4.411
971283AH1-107 GEN
Solar/Wind Harmer
4.411
316258AE1-075 C
Solar/Wind Harmer
0.219
971845AH1-439 GEN
Solar/Wind Harmer
5.594
3143316POE
Solar/Wind Harmer
0.447
315697AD1-025 GEN
Solar/Wind Harmer
0.119
3142433PROV 92
Adder
0.211
970119AG2-088 GEN
50/50
52.932
3150851SPRUNCC
50/50
1.044
3143096IRON208
50/50
0.687
3151931BEARGRDN S1
50/50
1.656
3151911BEARGRDN G1
50/50
1.282
3143226MDLTHAN
Solar/Wind Harmer
0.397
3143526WINTERP
Solar/Wind Harmer
1.653
3143336POWHATN
Solar/Wind Harmer
5.22
970937AG2-583 GEN
Solar/Wind Harmer
12.085
3142543TWELFTH
Solar/Wind Harmer
0.016
944631AF1-128 GEN
Adder
61.175
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.05
971377AH1-170 GEN
Solar/Wind Harmer
1.321
3147623JAMES R
Solar/Wind Harmer
0.287
316132AB2-190 GEN1
Solar/Wind Harmer
0.622
971069AG2-661 GEN
Solar/Wind Harmer
2.01
3146926FARMVIL
Solar/Wind Harmer
0.068
3142416OLDCHRC
Solar/Wind Harmer
0.283
3142416OLDCHRC
Solar/Wind Harmer
0.108
3142433PROV 92
Solar/Wind Harmer
0.434
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
316381AD1-082 GEN
Solar/Wind Harmer
0.106
3142366NRTHEST
50/50
0.482
3150691DARBY 3
50/50
10.157
3150701DARBY 4
50/50
10.134
3150681DARBY 2
50/50
10.122
3150671DARBY 1
50/50
10.11
944641AF1-129 GEN
50/50
66.397
971223AH1-071 GEN
Solar/Wind Harmer
4.235
3143526WINTERP
Solar/Wind Harmer
1.653
316313AB2-026
Solar/Wind Harmer
0.183
316336AC2-165 C
Solar/Wind Harmer
13.505
3146776BUCKING
Solar/Wind Harmer
0.497
3146776BUCKING
Solar/Wind Harmer
0.04
3142946ENON
Solar/Wind Harmer
0.012
3142296MT RD221
Adder
0.38
316033AB2-134 GEN
Solar/Wind Harmer
0
966871AG1-558 GEN
Solar/Wind Harmer
0.126
316312AB1-027
Solar/Wind Harmer
0.194
970301AG2-198 GEN
Solar/Wind Harmer
4.383
315976AC1-164 GENA
Solar/Wind Harmer
1.079
316169AC1-164_GENC
Solar/Wind Harmer
0.932
3147133PAMPLIN
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.08
958211AF2-115 GEN
Solar/Wind Harmer
1.184
3144293JTRSVLE
Adder
0.236
3144356SAPONY
Solar/Wind Harmer
0.819
316315AB2-025 C
Solar/Wind Harmer
0.078
316349AD2-085 GEN
Solar/Wind Harmer
0.064
970323AG2-213 GEN
Solar/Wind Harmer
3.952
316156AD2-030 GEN
Solar/Wind Harmer
0.066
315835AF2-110_GEN
Solar/Wind Harmer
0.618
3150991CHESPKB
Adder
0.932
3150991CHESPKB
Adder
0.91
316365GEN2_N
Solar/Wind Harmer
0.197
315742AE1-103 GEN
Solar/Wind Harmer
1.313
3145506HICKORY
Solar/Wind Harmer
0.351
3145506HICKORY
Solar/Wind Harmer
0.211
3145506HICKORY
Solar/Wind Harmer
0.053
316339AD2-160 GEN
Solar/Wind Harmer
0.14
316388AE2-253 GEN
Solar/Wind Harmer
0.273
3137176SLIGO L2192
Solar/Wind Harmer
0.348
3146456SLIGO L269
Solar/Wind Harmer
1.549
3142433PROV 92
Adder
0.211
970657AG2-426 GEN
Solar/Wind Harmer
0.764
3151201GRAVEL4
Adder
7.309
3151221GRAVEL6
Adder
7.3
3151191GRAVEL3
Adder
7.216
3151211GRAVEL5
Adder
7.216
3143873LANEXA
Solar/Wind Harmer
0.059
946301AF1-294 GEN
Solar/Wind Harmer
1.947
961791AG1-021 GEN
Solar/Wind Harmer
0.947
315814AE2-033 C
Solar/Wind Harmer
7.704
971445AH1-216 GEN
Solar/Wind Harmer
6.789
316311AC2-079 GEN
Solar/Wind Harmer
2.749
970683AG2-441 GEN
Solar/Wind Harmer
5.77
970681AG2-440 GEN
Solar/Wind Harmer
3.83
970189AG2-124 GEN
Solar/Wind Harmer
2.784
316159AE1-175 C
Solar/Wind Harmer
0.08
3144303KENBRDG
Solar/Wind Harmer
0.074
3141873WAN 176
Solar/Wind Harmer
0.018
3138283WHITEMARSH
Solar/Wind Harmer
0.021
3151081ELIZAR1
Adder
8.141
3151091ELIZAR2
Adder
7.999
316316AC1-027 C
Solar/Wind Harmer
0.084
3141913WHIT STONE
Solar/Wind Harmer
0.088
3138133OCRAN
Solar/Wind Harmer
0.026
957871AF2-081 GEN
Solar/Wind Harmer
4.364
3146406KITTY HAWK
Solar/Wind Harmer
0.011
3146486SUNBURY
Solar/Wind Harmer
0.087
3146486SUNBURY
Solar/Wind Harmer
0.087
313526AB2-022
Solar/Wind Harmer
0.046
970533AG2-339 GEN
Solar/Wind Harmer
6.573
3146396TANGLEW
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
0.054
3141783LANCAST
Solar/Wind Harmer
0.052
3141783LANCAST
Solar/Wind Harmer
0.035
970673AG2-436 GEN
Solar/Wind Harmer
10.754
971967AH1-528 GEN
Solar/Wind Harmer
13.826
3130156CHOWAN
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
0.085
3145893MURPHYS
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
0.084
3137643SOCKMAN
Solar/Wind Harmer
0.336
3146043SEABORD
Solar/Wind Harmer
0.084
316486AD2-202 GEN
Solar/Wind Harmer
0.085
315652AC1-086 GEN
Solar/Wind Harmer
9.161
3130546PLYMOUTH
Solar/Wind Harmer
0.083
315732AD1-074 GEN1
Solar/Wind Harmer
0.472
315733AD1-074 GEN2
Solar/Wind Harmer
0.472
316426AA2-053 GEN
Solar/Wind Harmer
0.277
316463AE2-346 GEN
Solar/Wind Harmer
0.07
3145513AHOSKIE
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
0.083
3146206CASHIE
Solar/Wind Harmer
0.082
970601AG2-382 GEN
Solar/Wind Harmer
3.081
3145683EARLEYS
Solar/Wind Harmer
0.164
3145683EARLEYS
Solar/Wind Harmer
0.082
3145683EARLEYS
Solar/Wind Harmer
0.082
970831AG2-522 GEN
Solar/Wind Harmer
3.5
3145796HORNRTN
Solar/Wind Harmer
0.262
3145796HORNRTN
Solar/Wind Harmer
0.033
970085AG2-068 GEN
Solar/Wind Harmer
4.336
970581AG2-369 GEN
Solar/Wind Harmer
3.729
3146033SCOT NK
Solar/Wind Harmer
0.319
316210AC1-098 GEN
Solar/Wind Harmer
0.729
316274AC1-208 GEN
Solar/Wind Harmer
0.406
316327AA2-057 GEN
Solar/Wind Harmer
0.113
3141813NORNECK
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.301
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
957861AF2-080 GEN
Solar/Wind Harmer
3.225
3145573BETHELC
Solar/Wind Harmer
0.074
3145573BETHELC
Solar/Wind Harmer
0.074
3147173SINAI
Solar/Wind Harmer
0.072
3147243WELCO
Solar/Wind Harmer
0.045
3150861SPRUNCD
50/50
1.044
3143096IRON208
50/50
0.687
3143096IRON208
50/50
0.673
3151921BEARGRDN G2
50/50
1.282
3143336POWHATN
Solar/Wind Harmer
4.437
972003AH1-546 GEN
Solar/Wind Harmer
4.733
3146776BUCKING
Solar/Wind Harmer
0.045
970221AG2-151 GEN
Solar/Wind Harmer
6.605
970133AG2-095 GEN
Solar/Wind Harmer
1.182
970293AG2-193 GEN
Solar/Wind Harmer
1.303
3142946ENON
Solar/Wind Harmer
0.04
316458AB2-190 GEN2
Solar/Wind Harmer
0.622
315778AD1-151 GEN
Solar/Wind Harmer
9.046
3146926FARMVIL
Solar/Wind Harmer
0.068
315813AE1-149 C
Solar/Wind Harmer
5.916
316075AC2-137 C
Solar/Wind Harmer
0.029
316473AC1-191 GEN
Solar/Wind Harmer
0.369
3142416OLDCHRC
Solar/Wind Harmer
1.056
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
942461AE2-259 GEN
Solar/Wind Harmer
0
961611AG1-000B GEN
Solar/Wind Harmer
2.783
970657AG2-426 GEN
Solar/Wind Harmer
2.335
270494AE1-108_GEN
Solar/Wind Harmer
1.228
3147133PAMPLIN
Solar/Wind Harmer
0.316
3151171GRAVELC
Adder
1.405
3144293JTRSVLE
Adder
0.236
3145336SMITFLD
Solar/Wind Harmer
0.038
3141843SHACKLE
Adder
0.48
316203AE2-005 GEN
Solar/Wind Harmer
0
959311AF2-222 GEN
Solar/Wind Harmer
8.314
970257AG2-171 GEN
Solar/Wind Harmer
2.964
971775AH1-396 GEN
Solar/Wind Harmer
0.148
3141766HARMONY
Solar/Wind Harmer
1.229
315821AE2-092 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.345
3144536CHRHLND
Solar/Wind Harmer
0.014
3141873WAN 176
Solar/Wind Harmer
1.61
3150921YORKTN3
Adder
2.264
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.245
3145273HOLLAND
Solar/Wind Harmer
0.066
316246AF1-032 C
Solar/Wind Harmer
0.039
964241AG1-285 GEN
Solar/Wind Harmer
5.876
316017AA1-139 ULT1
Solar/Wind Harmer
0.047
3146456SLIGO L269
Solar/Wind Harmer
0.088
971153AH1-033 GEN
Solar/Wind Harmer
1.012
944581AF1-123 GEN
Solar/Wind Harmer
19.659
944601AF1-125 GEN
Solar/Wind Harmer
19.356
944011AF1-069 GEN
Solar/Wind Harmer
5.235
316321Z2-027
Solar/Wind Harmer
0.015
3147043LAWRENC
Solar/Wind Harmer
0.052
3146516WINFALL
Solar/Wind Harmer
0.087
3146626S HERTFORD
Solar/Wind Harmer
0.086
3156081AA2-088 GEN
Solar/Wind Harmer
0
316181AB2-040 GEN
Solar/Wind Harmer
0.121
3146376EDENTON
Solar/Wind Harmer
0.085
3145893MURPHYS
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
0.084
316478AD1-087 GEN
Solar/Wind Harmer
0.29
316011AB1-132 GEN
Solar/Wind Harmer
1.511
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
315735AD1-075 GEN1
Solar/Wind Harmer
0.236
3146206CASHIE
Solar/Wind Harmer
0.082
3146263WOODLND
Solar/Wind Harmer
0.082
970917AG2-570 GEN
Solar/Wind Harmer
7.308
3145796HORNRTN
Solar/Wind Harmer
0.327
3145796HORNRTN
Solar/Wind Harmer
0.082
971781AH1-399 GEN
Solar/Wind Harmer
0.107
3145823KELFORD
Solar/Wind Harmer
0.081
3145963POPLR C
Solar/Wind Harmer
0.08
316212AC1-099_GEN
Solar/Wind Harmer
0.407
315722AD1-056 GEN
Solar/Wind Harmer
2.665
3145933PARMELE
Solar/Wind Harmer
0.077
3150351NORNECKC2
Adder
0.769
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
3146073TAR RVR
Solar/Wind Harmer
0.074
3146083TARBORO
Solar/Wind Harmer
0.074
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
961601AG1-000A GEN
Solar/Wind Harmer
5.208
971623AH1-311 GEN
Solar/Wind Harmer
0.146
971683AH1-343 GEN
Solar/Wind Harmer
2.428
316222AC1-221 GEN
Solar/Wind Harmer
0.259
316283AC2-100 C
Solar/Wind Harmer
0.122
316223AC1-118
Solar/Wind Harmer
0.043
3141906WESTMOR
Solar/Wind Harmer
0.024
316123AC1-075 GEN
Solar/Wind Harmer
0.078
958131AF2-107 GEN
Solar/Wind Harmer
1.631
3147666LOUISA
Solar/Wind Helper
0.269
961611AG1-000B GEN
Solar/Wind Harmer
5.472
315975AC1-164 GENB
Solar/Wind Harmer
0.032
3151171GRAVELC
Adder
1.068
971563AH1-280 GEN
Solar/Wind Harmer
1.052
3144293JTRSVLE
Adder
0.236
3144293JTRSVLE
Adder
0.186
970685AG2-442 GEN
Solar/Wind Harmer
7.25
3145336SMITFLD
Solar/Wind Harmer
0.384
971777AH1-397 GEN
Solar/Wind Harmer
0.248
316034AC1-036 C
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
0.018
315785AD2-033 C
Solar/Wind Harmer
0.739
3138126ROCKLANDING
Solar/Wind Harmer
0.042
316072AD1-144
Solar/Wind Harmer
0.032
316093AE2-104_GEN
Solar/Wind Harmer
1.515
971317AH1-138 GEN
Solar/Wind Harmer
0.671
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.016
3150981CHESPKA
Adder
1.111
315693AD1-088 GEN
Solar/Wind Harmer
4.263
316023GEN1_S
Solar/Wind Harmer
0.197
940641AE2-051 GEN
Solar/Wind Harmer
7.05
939411AE1-173 GEN
Solar/Wind Harmer
37.549
3138133OCRAN
Solar/Wind Harmer
0.053
3146456SLIGO L269
Solar/Wind Harmer
0.088
319010AE1-072 C
Solar/Wind Harmer
0.437
944591AF1-124 GEN
Solar/Wind Harmer
19.729
960081AF2-299 GEN
Solar/Wind Harmer
0.837
941031AE2-094 GEN
Solar/Wind Harmer
16.022
3147043LAWRENC
Adder
0.785
3146516WINFALL
Solar/Wind Harmer
0.281
3146516WINFALL
Solar/Wind Harmer
0.087
316131AB2-060 GEN
Solar/Wind Harmer
0.268
957481AF2-042 GEN
Solar/Wind Harmer
22.86
3130156CHOWAN
Solar/Wind Harmer
0.085
315773AC2-141 GEN
Solar/Wind Harmer
3.083
3145893MURPHYS
Solar/Wind Harmer
0.336
3145893MURPHYS
Solar/Wind Harmer
0.374
315816AE2-034 GEN
Solar/Wind Harmer
0.358
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.715
315607AA1-063A GEN
Solar/Wind Harmer
0.169
3146173TUNIS
Solar/Wind Harmer
0.083
315737AD1-076 GEN
Solar/Wind Harmer
1.063
3146206CASHIE
Solar/Wind Harmer
0.082
971547AH1-271 GEN
Solar/Wind Harmer
1.761
3146263WOODLND
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.082
970919AG2-571 GEN
Solar/Wind Harmer
2.923
3145683EARLEYS
Solar/Wind Harmer
0.082
3156021HOLLOMANSOL
Solar/Wind Harmer
0.369
316129AC1-054 GEN
Solar/Wind Harmer
0.306
3145796HORNRTN
Solar/Wind Harmer
0.27
3145796HORNRTN
Solar/Wind Harmer
0.082
971065AG2-659 GEN
Solar/Wind Harmer
3.49
970087AG2-069 GEN
Solar/Wind Harmer
6.503
3145823KELFORD
Solar/Wind Harmer
0.081
962861AG1-135 GEN
Solar/Wind Harmer
2.584
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
2.649
3145963POPLR C
Solar/Wind Harmer
0.08
3141726DUNNSVL
Solar/Wind Harmer
0.313
970401AG2-262 GEN
Solar/Wind Harmer
0.457
3146293MARTNCO
Solar/Wind Harmer
0.071
3150351NORNECKC2
Adder
0.756
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
316494AC1-189 GEN
Solar/Wind Harmer
0.253
3146233WITAKRS
Solar/Wind Harmer
0.297
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.074
3145493TOT1
Solar/Wind Harmer
0.329
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
316359AB2-059 GEN
Solar/Wind Harmer
0.26
3142053HEARTS
Solar/Wind Harmer
0.129
316337AD2-073 GEN
Solar/Wind Harmer
0.059
316447AC1-158 HLD
Solar/Wind Helper
1.874
316044AC1-158 PL1
Solar/Wind Helper
0.852
3147666LOUISA
Solar/Wind Helper
0.468
316192AB2-158 GEN
Solar/Wind Helper
0.767
3130086AYDLETT
Solar/Wind Harmer
0.35
3146386ELIZ CT
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
970933AG2-581 GEN
Solar/Wind Harmer
6.912
3146626S HERTFORD
Solar/Wind Harmer
0.086
3146626S HERTFORD
Solar/Wind Harmer
0.086
970099AG2-077 GEN
Solar/Wind Harmer
9.144
972185AH1-677 GEN
Adder
4.801
313506AB2-031 GEN
Solar/Wind Harmer
0.261
3146376EDENTON
Solar/Wind Harmer
0.378
3146376EDENTON
Solar/Wind Harmer
0.378
972187AH1-678 GEN
Adder
2.418
316294AC1-161 GEN
Solar/Wind Harmer
1.459
3145893MURPHYS
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
0.151
315614AA2-178 GEN
Solar/Wind Harmer
0.478
962571AG1-106 GEN
Solar/Wind Harmer
1.185
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
3146173TUNIS
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.103
316065AD1-022 GEN
Solar/Wind Harmer
3.806
316140AB2-099
Solar/Wind Harmer
0.029
3145783HORNRTN
Solar/Wind Harmer
1.464
3145783HORNRTN
Solar/Wind Harmer
1.171
3145783HORNRTN
Solar/Wind Harmer
0.366
3145783HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.245
972189AH1-679 GEN
Adder
1.328
962561AG1-105 GEN
Solar/Wind Harmer
3.796
964791AG1-342 GEN
Solar/Wind Harmer
1.496
3146843MT LREL
Solar/Wind Harmer
0.078
3146843MT LREL
Solar/Wind Harmer
0.078
315724AD1-057 GEN
Solar/Wind Harmer
1.486
3145933PARMELE
Solar/Wind Harmer
0.154
3145933PARMELE
Solar/Wind Harmer
0.077
3150341NORNECKC1
Adder
0.794
3150341NORNECKC1
Adder
0.788
316005AA1-067
Solar/Wind Harmer
0.081
316118AC1-105 GEN
Solar/Wind Harmer
0.192
3145493TOT1
Solar/Wind Harmer
0.172
3145453TOT5
Solar/Wind Harmer
0.103
3145603CNETO
Solar/Wind Harmer
0.069
316049AB1-081 GEN
Solar/Wind Harmer
0.417
961601AG1-000A GEN
Solar/Wind Harmer
1.302
316263AC1-034 GEN
Solar/Wind Harmer
2.783
316045AC1-158 PL2
Solar/Wind Helper
2.725
316450AC1-158 RIC
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
3.484
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.332
TVALTFEXP_TVA->PJM
CLTF
1.758
CPLELTFEXP_CPLE->PJM
CLTF
4.7
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.588
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.283
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.048
MECLTFEXP_MEC->PJM
CLTF
1.732
SIGELTFEXP_SIGE->PJM
CLTF
0.053
NYPJM->LTFIMP_NY
CLTF
1.089
LGEELTFEXP_LGEE->PJM
CLTF
0.647
WECLTFEXP_WEC->PJM
CLTF
0.325

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.28 %
Rating:1265.1 MVA
Rating Type:C
MVA to Mitigate:1534.29
MW Contribution:
6.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150861SPRUNCD
50/50
1.05
3143096IRON208
50/50
0.691
3143096IRON208
50/50
0.677
3151921BEARGRDN G2
50/50
1.282
3143336POWHATN
Solar/Wind Harmer
3.332
972003AH1-546 GEN
Solar/Wind Harmer
6.229
970133AG2-095 GEN
Solar/Wind Harmer
1.573
3146776BUCKING
Solar/Wind Harmer
-0.005
970221AG2-151 GEN
Solar/Wind Harmer
8.694
970293AG2-193 GEN
Solar/Wind Harmer
1.727
3142946ENON
Solar/Wind Harmer
-0.004
316458AB2-190 GEN2
Solar/Wind Harmer
1.333
315778AD1-151 GEN
Solar/Wind Harmer
11.388
315813AE1-149 C
Solar/Wind Harmer
7.962
3146926FARMVIL
Solar/Wind Harmer
-0.007
316075AC2-137 C
Solar/Wind Harmer
0.335
316473AC1-191 GEN
Solar/Wind Harmer
1.329
3142416OLDCHRC
Solar/Wind Harmer
1.242
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
942461AE2-259 GEN
Solar/Wind Harmer
1.79
970657AG2-426 GEN
Solar/Wind Harmer
2.398
961611AG1-000B GEN
Solar/Wind Harmer
2.476
270494AE1-108_GEN
Solar/Wind Harmer
2.999
3151171GRAVELC
Adder
1.406
3147133PAMPLIN
Solar/Wind Harmer
-0.035
3144293JTRSVLE
Adder
0.234
3145336SMITFLD
Solar/Wind Harmer
-0.004
3141843SHACKLE
Adder
0.482
316203AE2-005 GEN
Solar/Wind Harmer
4.465
959311AF2-222 GEN
Solar/Wind Harmer
10.913
3141766HARMONY
Solar/Wind Harmer
0.924
970257AG2-171 GEN
Solar/Wind Harmer
3.883
971775AH1-396 GEN
Solar/Wind Harmer
0.731
315821AE2-092 GEN
Solar/Wind Harmer
2.135
3144216WINCHST
Adder
0.344
3141873WAN 176
Solar/Wind Harmer
1.21
3144536CHRHLND
Solar/Wind Harmer
-0.002
3150921YORKTN3
Adder
2.256
966621AG1-532 GEN
Solar/Wind Harmer
0.203
3145273HOLLAND
Solar/Wind Harmer
-0.007
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
8.176
3147043LAWRENC
Solar/Wind Harmer
-0.006
3142366NRTHEST
50/50
0.486
3150691DARBY 3
50/50
10.226
3150701DARBY 4
50/50
10.202
3150681DARBY 2
50/50
10.19
3150671DARBY 1
50/50
10.178
944641AF1-129 GEN
50/50
67.529
971223AH1-071 GEN
Solar/Wind Harmer
5.585
3143526WINTERP
Solar/Wind Harmer
-0.185
316313AB2-026
Solar/Wind Harmer
0.889
316336AC2-165 C
Solar/Wind Harmer
18.722
316240AF1-291 C
Solar/Wind Harmer
0.445
3146776BUCKING
Solar/Wind Harmer
-0.055
3146776BUCKING
Solar/Wind Harmer
-0.005
3142946ENON
Solar/Wind Harmer
-0.001
3142296MT RD221
Adder
0.383
316033AB2-134 GEN
Solar/Wind Harmer
4.025
966871AG1-558 GEN
Solar/Wind Harmer
0.371
966871AG1-558 GEN
Solar/Wind Harmer
0.127
316312AB1-027
Solar/Wind Harmer
0.414
316083AB2-161 GEN
Solar/Wind Harmer
1.946
315976AC1-164 GENA
Solar/Wind Harmer
2.632
316169AC1-164_GENC
Solar/Wind Harmer
2.274
3144356SAPONY
Solar/Wind Harmer
0.4
316315AB2-025 C
Solar/Wind Harmer
0.309
970301AG2-198 GEN
Solar/Wind Harmer
5.72
3147133PAMPLIN
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.009
958211AF2-115 GEN
Solar/Wind Harmer
1.723
3144293JTRSVLE
Adder
0.234
316349AD2-085 GEN
Solar/Wind Harmer
0.961
316441AF1-014 GEN
Solar/Wind Harmer
0.714
315666AE1-190 GEN
Solar/Wind Harmer
0.313
970323AG2-213 GEN
Solar/Wind Harmer
5.178
316365GEN2_N
Solar/Wind Harmer
0.686
316156AD2-030 GEN
Solar/Wind Harmer
0.271
315835AF2-110_GEN
Solar/Wind Harmer
1.262
3150991CHESPKB
Adder
0.925
3150991CHESPKB
Adder
0.903
315742AE1-103 GEN
Solar/Wind Harmer
2.343
316185AD1-033 GEN
Solar/Wind Harmer
1.031
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.023
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.657
316388AE2-253 GEN
Solar/Wind Harmer
0.657
3137176SLIGO L2192
Solar/Wind Harmer
-0.039
3146456SLIGO L269
Solar/Wind Harmer
1.153
3130086AYDLETT
Solar/Wind Harmer
-0.039
3146386ELIZ CT
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
0.778
316431W1029_GEN1
Solar/Wind Harmer
1.756
316433W1029_GEN2
Solar/Wind Harmer
1.756
316435W1029_GEN3
Solar/Wind Harmer
1.756
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
316303AF2-085
50/50
7.07
971285AH1-108 GEN
50/50
1.717
972205AH1-687 GEN
50/50
6.262
316233AE1-074 FULL
Solar/Wind Harmer
0.964
971281AH1-106 GEN
Solar/Wind Harmer
5.821
971283AH1-107 GEN
Solar/Wind Harmer
5.821
316258AE1-075 C
Solar/Wind Harmer
0.8
316405AF2-144 C
Solar/Wind Harmer
0.844
315839AE2-212 C
Solar/Wind Harmer
0.426
316322AB2-045
Solar/Wind Harmer
0.468
971845AH1-439 GEN
Solar/Wind Harmer
7.344
3143316POE
Solar/Wind Harmer
-0.052
315697AD1-025 GEN
Solar/Wind Harmer
2.523
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
970657AG2-426 GEN
Solar/Wind Harmer
0.748
315814AE2-033 C
Solar/Wind Harmer
10.632
3151201GRAVEL4
Adder
7.314
3151221GRAVEL6
Adder
7.306
3151191GRAVEL3
Adder
7.222
3151211GRAVEL5
Adder
7.222
3143873LANEXA
Solar/Wind Harmer
-0.007
946301AF1-294 GEN
Solar/Wind Harmer
2.826
961791AG1-021 GEN
Solar/Wind Harmer
1.379
315833AF1-017_GEN
Solar/Wind Harmer
2.056
971445AH1-216 GEN
Solar/Wind Harmer
6.69
316311AC2-079 GEN
Solar/Wind Harmer
5.453
316236AE1-162_GEN
Solar/Wind Harmer
0.324
970683AG2-441 GEN
Solar/Wind Harmer
7.559
970681AG2-440 GEN
Solar/Wind Harmer
5.017
316382AG1-145 C
Solar/Wind Harmer
0.315
316159AE1-175 C
Solar/Wind Harmer
0.281
316059AD1-063 C
Solar/Wind Harmer
0.234
3144303KENBRDG
Solar/Wind Harmer
-0.008
957601AF2-054 GEN
Solar/Wind Harmer
0.305
3141873WAN 176
Solar/Wind Harmer
-0.002
957831AF2-077 GEN
Solar/Wind Harmer
0.305
3138283WHITEMARSH
Solar/Wind Harmer
0.016
946281AF1-292 GEN
Solar/Wind Harmer
0.224
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3151081ELIZAR1
Adder
8.072
3151091ELIZAR2
Adder
7.932
3138133OCRAN
Solar/Wind Harmer
-0.003
316316AC1-027 C
Solar/Wind Harmer
0.302
316018AA1-139 ULT2
Solar/Wind Harmer
0.835
957871AF2-081 GEN
Solar/Wind Harmer
4.884
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146406KITTY HAWK
Solar/Wind Harmer
0.008
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
313526AB2-022
Solar/Wind Harmer
0.262
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.179
315800Z1-036_GEN1
Solar/Wind Harmer
2.359
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970533AG2-339 GEN
Solar/Wind Harmer
6.414
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
316238AB2-078_GEN
Solar/Wind Harmer
0.286
316239AB2-077_GEN
Solar/Wind Harmer
0.286
315652AC1-086 GEN
Solar/Wind Harmer
10.683
971967AH1-528 GEN
Solar/Wind Harmer
17.847
3146043SEABORD
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
20.735
316318V4-068
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.009
316426AA2-053 GEN
Solar/Wind Harmer
0.944
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.004
3142956BIRDNECK
Solar/Wind Harmer
0.529
316305AF2-043 C
Solar/Wind Harmer
0.296
316246AF1-032 C
Solar/Wind Harmer
0.199
964241AG1-285 GEN
Solar/Wind Harmer
7.698
316017AA1-139 ULT1
Solar/Wind Harmer
0.788
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.129
316320Y1-086
Solar/Wind Harmer
0.569
944581AF1-123 GEN
Solar/Wind Harmer
44.182
944601AF1-125 GEN
Solar/Wind Harmer
43.493
316181AB2-040 GEN
Solar/Wind Harmer
1.352
316321Z2-027
Solar/Wind Harmer
0.261
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3156081AA2-088 GEN
Solar/Wind Harmer
3.117
944011AF1-069 GEN
Solar/Wind Harmer
5.604
3146376EDENTON
Solar/Wind Harmer
-0.009
316011AB1-132 GEN
Solar/Wind Harmer
1.983
3145893MURPHYS
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.037
3145796HORNRTN
Solar/Wind Harmer
-0.009
316484AD2-074 GEN
Solar/Wind Harmer
2.341
961951AG1-038 GEN
Solar/Wind Harmer
1.225
315735AD1-075 GEN1
Solar/Wind Harmer
0.937
3146263WOODLND
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
316478AD1-087 GEN
Solar/Wind Harmer
0.798
971781AH1-399 GEN
Solar/Wind Harmer
0.568
316317KELFORD C
Solar/Wind Harmer
0.422
3145823KELFORD
Solar/Wind Harmer
-0.009
970917AG2-570 GEN
Solar/Wind Harmer
22.587
3145963POPLR C
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
0.774
315722AD1-056 GEN
Solar/Wind Harmer
3.105
3145933PARMELE
Solar/Wind Harmer
-0.009
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.15
3145513AHOSKIE
Solar/Wind Harmer
0.081
961941AG1-037 GEN
Solar/Wind Harmer
0.07
3145513AHOSKIE
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.876
315733AD1-074 GEN2
Solar/Wind Harmer
1.876
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
4.056
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
316486AD2-202 GEN
Solar/Wind Harmer
0.234
970831AG2-522 GEN
Solar/Wind Harmer
4.609
316468AD1-105 GEN
Solar/Wind Harmer
1.053
3146033SCOT NK
Solar/Wind Harmer
-0.036
970085AG2-068 GEN
Solar/Wind Harmer
5.585
970581AG2-369 GEN
Solar/Wind Harmer
4.803
316210AC1-098 GEN
Solar/Wind Harmer
1.394
316274AC1-208 GEN
Solar/Wind Harmer
0.957
316174AB2-169 GEN
Solar/Wind Harmer
1.367
316327AA2-057 GEN
Solar/Wind Harmer
0.865
3141813NORNECK
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.034
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
957861AF2-080 GEN
Solar/Wind Harmer
0.475
3146626S HERTFORD
Solar/Wind Harmer
-0.01
313527AB2-043 GEN
Solar/Wind Harmer
1.555
3146376EDENTON
Solar/Wind Harmer
0.283
3146376EDENTON
Solar/Wind Harmer
0.283
316237AB2-079_GEN
Solar/Wind Harmer
0.286
970933AG2-581 GEN
Solar/Wind Harmer
8.91
962571AG1-106 GEN
Solar/Wind Harmer
1.365
3145893MURPHYS
Solar/Wind Harmer
0.264
3145893MURPHYS
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
11.833
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
315614AA2-178 GEN
Solar/Wind Harmer
1.012
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.078
972185AH1-677 GEN
Adder
4.69
316294AC1-161 GEN
Solar/Wind Harmer
3.029
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.363
3145783HORNRTN
Solar/Wind Harmer
1.106
3145783HORNRTN
Solar/Wind Harmer
0.885
3145783HORNRTN
Solar/Wind Harmer
0.276
3145783HORNRTN
Solar/Wind Harmer
0.111
3145796HORNRTN
Solar/Wind Harmer
-0.028
316140AB2-099
Solar/Wind Harmer
0.063
316487AF1-042 GEN
Solar/Wind Harmer
1.225
316065AD1-022 GEN
Solar/Wind Harmer
4.64
972189AH1-679 GEN
Adder
1.338
962561AG1-105 GEN
Solar/Wind Harmer
4.959
315724AD1-057 GEN
Solar/Wind Harmer
1.708
315687AD1-152 GEN
Solar/Wind Harmer
1.047
964791AG1-342 GEN
Solar/Wind Harmer
1.854
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
3145933PARMELE
Solar/Wind Harmer
-0.017
3145933PARMELE
Solar/Wind Harmer
-0.009
3150341NORNECKC1
Adder
0.797
3150341NORNECKC1
Adder
0.791
316005AA1-067
Solar/Wind Harmer
0.171
316045AC1-158 PL2
Solar/Wind Helper
2.715
316450AC1-158 RIC
Solar/Wind Helper
0.226
970119AG2-088 GEN
50/50
53.023
3150851SPRUNCC
50/50
1.05
3143096IRON208
50/50
0.691
3151931BEARGRDN S1
50/50
1.656
3151911BEARGRDN G1
50/50
1.282
3143226MDLTHAN
Solar/Wind Harmer
-0.045
3143526WINTERP
Solar/Wind Harmer
-0.185
3143336POWHATN
Solar/Wind Harmer
3.92
970937AG2-583 GEN
Solar/Wind Harmer
15.923
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
61.632
315671AE2-027_GEN
Solar/Wind Harmer
2.584
3146776BUCKING
Solar/Wind Harmer
-0.006
971377AH1-170 GEN
Solar/Wind Harmer
1.739
3147623JAMES R
Solar/Wind Harmer
0.215
316132AB2-190 GEN1
Solar/Wind Harmer
1.333
971069AG2-661 GEN
Solar/Wind Harmer
2.024
3146926FARMVIL
Solar/Wind Harmer
-0.007
316369SG1_INVT
Solar/Wind Harmer
2.229
3142416OLDCHRC
Solar/Wind Harmer
-0.032
3142416OLDCHRC
Solar/Wind Harmer
-0.012
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
316381AD1-082 GEN
Solar/Wind Harmer
1.097
961611AG1-000B GEN
Solar/Wind Harmer
5.803
315975AC1-164 GENB
Solar/Wind Harmer
0.078
3151171GRAVELC
Adder
1.069
971563AH1-280 GEN
Solar/Wind Harmer
1.379
3144293JTRSVLE
Adder
0.234
3144293JTRSVLE
Adder
0.185
970685AG2-442 GEN
Solar/Wind Harmer
9.497
3145336SMITFLD
Solar/Wind Harmer
-0.043
971777AH1-397 GEN
Solar/Wind Harmer
1.236
316314AB2-024 C
Solar/Wind Harmer
0.897
315662AE1-191 GEN
Solar/Wind Harmer
1.254
316280AD1-041 GEN
Solar/Wind Harmer
0.783
3141766HARMONY
Solar/Wind Harmer
-0.002
316034AC1-036 C
Solar/Wind Harmer
0.192
315785AD2-033 C
Solar/Wind Harmer
2.312
316023GEN1_S
Solar/Wind Harmer
0.686
3138126ROCKLANDING
Solar/Wind Harmer
0.031
316077AC2-138 C
Solar/Wind Harmer
0.18
3150351NORNECKC2
Adder
0.771
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.176
3146233WITAKRS
Solar/Wind Harmer
-0.006
3147666LOUISA
Solar/Wind Helper
0.268
316093AE2-104_GEN
Solar/Wind Harmer
2.934
316072AD1-144
Solar/Wind Harmer
0.204
971317AH1-138 GEN
Solar/Wind Harmer
1.258
960081AF2-299 GEN
Solar/Wind Harmer
1.123
316375AC2-012 GEN
Solar/Wind Harmer
3.43
316036AC1-147 C
Solar/Wind Harmer
0.267
3150981CHESPKA
Adder
1.102
3138133OCRAN
Solar/Wind Harmer
-0.006
3147043LAWRENC
Adder
0.794
315693AD1-088 GEN
Solar/Wind Harmer
4.916
316087AB2-174 GEN
Solar/Wind Harmer
1.394
3146456SLIGO L269
Solar/Wind Harmer
-0.01
319010AE1-072 C
Solar/Wind Harmer
1.969
944591AF1-124 GEN
Solar/Wind Harmer
44.341
939411AE1-173 GEN
Solar/Wind Harmer
48.473
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.01
940641AE2-051 GEN
Solar/Wind Harmer
9.068
316131AB2-060 GEN
Solar/Wind Harmer
1.036
315611Z1-036_GEN2
Solar/Wind Harmer
2.359
941031AE2-094 GEN
Solar/Wind Harmer
17.884
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.038
3145893MURPHYS
Solar/Wind Harmer
0.281
315607AA1-063A GEN
Solar/Wind Harmer
0.954
957481AF2-042 GEN
Solar/Wind Harmer
29.582
315816AE2-034 GEN
Solar/Wind Harmer
0.759
3145663CRESWEL
Solar/Wind Harmer
-0.026
971163AH1-040 GEN
Solar/Wind Harmer
8.815
315773AC2-141 GEN
Solar/Wind Harmer
3.92
3146173TUNIS
Solar/Wind Harmer
-0.009
3145783HORNRTN
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.009
315737AD1-076 GEN
Solar/Wind Harmer
1.763
3146263WOODLND
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.318
3145683EARLEYS
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.241
316129AC1-054 GEN
Solar/Wind Harmer
0.804
971065AG2-659 GEN
Solar/Wind Harmer
4.588
3145823KELFORD
Solar/Wind Harmer
-0.009
962861AG1-135 GEN
Solar/Wind Harmer
3.413
970919AG2-571 GEN
Solar/Wind Harmer
2.859
316404AE1-155 C
Solar/Wind Harmer
1.724
958261AF2-120 GEN
Solar/Wind Harmer
3.499
3145963POPLR C
Solar/Wind Harmer
-0.009
970087AG2-069 GEN
Solar/Wind Harmer
8.378
964211AG1-282 GEN
Solar/Wind Harmer
0.265
3141726DUNNSVL
Solar/Wind Harmer
-0.035
970401AG2-262 GEN
Solar/Wind Harmer
0.566
3146293MARTNCO
Solar/Wind Harmer
0.053
3150351NORNECKC2
Adder
0.759
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.465
3146233WITAKRS
Solar/Wind Harmer
-0.033
316447AC1-158 HLD
Solar/Wind Helper
1.867
316044AC1-158 PL1
Solar/Wind Helper
0.849
3147666LOUISA
Solar/Wind Helper
0.466
316192AB2-158 GEN
Solar/Wind Helper
0.763
316494AC1-189 GEN
Solar/Wind Harmer
0.117
LAGNLTFEXP_LAGN->PJM
CLTF
3.447
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.221
TVALTFEXP_TVA->PJM
CLTF
1.739
CPLELTFEXP_CPLE->PJM
CLTF
4.652
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.391
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.159
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.985
MECLTFEXP_MEC->PJM
CLTF
1.714
SIGELTFEXP_SIGE->PJM
CLTF
0.052
NYPJM->LTFIMP_NY
CLTF
1.083
LGEELTFEXP_LGEE->PJM
CLTF
0.64
WECLTFEXP_WEC->PJM
CLTF
0.322

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:169.7 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1122.99
MW Contribution:
15.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.671
316303AF2-085
50/50
2.056
3151541CLOVER2
50/50
2.335
3151601KERR 3
50/50
0.217
3151611KERR 4
50/50
0.217
3151621KERR 5
50/50
0.217
3151631KERR 6
50/50
0.217
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.288
3151281ROARAP4
50/50
0.087
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971845AH1-439 GEN
Solar/Wind Harmer
16.331
316258AE1-075 C
Solar/Wind Harmer
0.188
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
11.554
970681AG2-440 GEN
Solar/Wind Harmer
7.669
3144303KENBRDG
Solar/Wind Harmer
0.139
316486AD2-202 GEN
Solar/Wind Harmer
0.111
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.021
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.947
970673AG2-436 GEN
Solar/Wind Harmer
9.878
970533AG2-339 GEN
Solar/Wind Harmer
5.968
3137643SOCKMAN
Solar/Wind Harmer
0.315
970085AG2-068 GEN
Solar/Wind Harmer
4.091
970581AG2-369 GEN
Solar/Wind Harmer
3.519
316426AA2-053 GEN
Solar/Wind Harmer
0.254
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.748
315652AC1-086 GEN
Solar/Wind Harmer
7.784
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.529
970413AG2-270 GEN
50/50
10.247
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.096
3150861SPRUNCD
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
972003AH1-546 GEN
Solar/Wind Harmer
15.439
970221AG2-151 GEN
Solar/Wind Harmer
21.636
3146776BUCKING
Solar/Wind Harmer
0.132
270494AE1-108_GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.801
315821AE2-092 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.693
959311AF2-222 GEN
Solar/Wind Harmer
15.886
970257AG2-171 GEN
Solar/Wind Harmer
5.551
971775AH1-396 GEN
Solar/Wind Harmer
0.278
964241AG1-285 GEN
Solar/Wind Harmer
9.805
958131AF2-107 GEN
Solar/Wind Harmer
3.652
316478AD1-087 GEN
Solar/Wind Harmer
0.38
3147043LAWRENC
Solar/Wind Harmer
0.059
971683AH1-343 GEN
Solar/Wind Harmer
2.983
316181AB2-040 GEN
Solar/Wind Harmer
0.114
944011AF1-069 GEN
Solar/Wind Harmer
4.753
970917AG2-570 GEN
Solar/Wind Harmer
6.903
3156081AA2-088 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
1.284
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.358
3146173TUNIS
Solar/Wind Harmer
0.069
316123AC1-075 GEN
Solar/Wind Harmer
0.092
3145823KELFORD
Solar/Wind Harmer
0.069
315722AD1-056 GEN
Solar/Wind Harmer
2.302
3145273HOLLAND
Solar/Wind Harmer
0.05
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
316222AC1-221 GEN
Solar/Wind Harmer
0.27
3146206CASHIE
Solar/Wind Harmer
0.065
3151931BEARGRDN S1
50/50
5.466
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.529
3144293JTRSVLE
50/50
0.418
970119AG2-088 GEN
50/50
15.416
3151531CLOVER1
50/50
2.353
3151591KERR 2
50/50
0.217
3151641KERR 7
50/50
0.217
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.199
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.318
3151281ROARAP4
50/50
0.093
3150851SPRUNCC
50/50
0.364
3151391GASTONA
50/50
0.189
3151411GASTONB
50/50
0.189
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.218
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
3143336POWHATN
Solar/Wind Harmer
4.472
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.905
316034AC1-036 C
Solar/Wind Harmer
0.012
315785AD2-033 C
Solar/Wind Harmer
1.344
316131AB2-060 GEN
Solar/Wind Harmer
0.421
315693AD1-088 GEN
Solar/Wind Harmer
6.345
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.3
970401AG2-262 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
4.185
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.36
960081AF2-299 GEN
Solar/Wind Harmer
0.793
941031AE2-094 GEN
Solar/Wind Harmer
14.548
970919AG2-571 GEN
Solar/Wind Harmer
2.761
970087AG2-069 GEN
Solar/Wind Harmer
6.137
3145783HORNRTN
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.151
940641AE2-051 GEN
Solar/Wind Harmer
5.985
316023GEN1_S
Solar/Wind Harmer
0.163
939411AE1-173 GEN
Solar/Wind Harmer
30.688
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.298
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.397
316381AD1-082 GEN
Solar/Wind Harmer
0.066
315737AD1-076 GEN
Solar/Wind Harmer
0.833
315816AE2-034 GEN
Solar/Wind Harmer
0.276
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.168
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.229
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.215
319010AE1-072 C
Solar/Wind Harmer
0.316
3146456SLIGO L269
Solar/Wind Harmer
0.063
944591AF1-124 GEN
Solar/Wind Harmer
14.293
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
0
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.011
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.022
315773AC2-141 GEN
Solar/Wind Harmer
2.266
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.171
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316132AB2-190 GEN1
Solar/Wind Harmer
0.321
944631AF1-128 GEN
Adder
26.814
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.905
3147666LOUISA
Solar/Wind Helper
0.521
316274AC1-208 GEN
Solar/Wind Harmer
0.364
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
316210AC1-098 GEN
Solar/Wind Harmer
0.642
3146033SCOT NK
Solar/Wind Harmer
0.276
316463AE2-346 GEN
Solar/Wind Harmer
0.059
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316327AA2-057 GEN
Solar/Wind Harmer
0.1
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
970657AG2-426 GEN
Solar/Wind Harmer
0.477
315732AD1-074 GEN1
Solar/Wind Harmer
0.37
315733AD1-074 GEN2
Solar/Wind Harmer
0.37
3130546PLYMOUTH
Solar/Wind Harmer
0.065
316311AC2-079 GEN
Solar/Wind Harmer
1.854
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
313526AB2-022
Solar/Wind Harmer
0.034
957861AF2-080 GEN
Solar/Wind Harmer
2.738
3146406KITTY HAWK
Solar/Wind Harmer
0.008
957871AF2-081 GEN
Solar/Wind Harmer
3.154
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
316316AC1-027 C
Solar/Wind Harmer
0.06
3151081ELIZAR1
Adder
5.774
3151091ELIZAR2
Adder
5.674
971445AH1-216 GEN
Solar/Wind Harmer
4.323
3151201GRAVEL4
Adder
4.409
3151221GRAVEL6
Adder
4.404
3151191GRAVEL3
Adder
4.353
3151211GRAVEL5
Adder
4.353
315697AD1-025 GEN
Solar/Wind Harmer
0.065
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.524
315813AE1-149 C
Solar/Wind Harmer
3.483
316283AC2-100 C
Solar/Wind Harmer
0.127
970657AG2-426 GEN
Solar/Wind Harmer
1.458
315735AD1-075 GEN1
Solar/Wind Harmer
0.185
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.549
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.011
316246AF1-032 C
Solar/Wind Harmer
0.028
3145933PARMELE
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.733
316017AA1-139 ULT1
Solar/Wind Harmer
0.034
944581AF1-123 GEN
Solar/Wind Harmer
14.243
944601AF1-125 GEN
Solar/Wind Harmer
14.023
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.848
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
3145336SMITFLD
Solar/Wind Harmer
0.025
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.82
316458AB2-190 GEN2
Solar/Wind Harmer
0.321
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.128
970909AG2-566 GEN
50/50
2.396
3144293JTRSVLE
50/50
0.529
970535AG2-341 GEN
50/50
2.11
3151581KERR 1
50/50
0.078
3152661PLYWOOD A
50/50
0.215
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.318
315241AE2-183_GT1
50/50
1.314
972185AH1-677 GEN
50/50
4.763
3151261ROARAP2
50/50
0.093
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
316336AC2-165 C
Solar/Wind Harmer
14.549
316313AB2-026
Solar/Wind Harmer
0.157
970301AG2-198 GEN
Solar/Wind Harmer
9.584
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.177
958211AF2-115 GEN
Solar/Wind Harmer
2.507
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.398
970099AG2-077 GEN
Solar/Wind Harmer
11.72
964791AG1-342 GEN
Solar/Wind Harmer
2.09
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.466
313506AB2-031 GEN
Solar/Wind Harmer
0.246
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316365GEN2_N
Solar/Wind Harmer
0.163
3144356SAPONY
Solar/Wind Harmer
0.607
316315AB2-025 C
Solar/Wind Harmer
0.058
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
316140AB2-099
Solar/Wind Harmer
0.024
315742AE1-103 GEN
Solar/Wind Harmer
1.005
315724AD1-057 GEN
Solar/Wind Harmer
1.284
316065AD1-022 GEN
Solar/Wind Harmer
3.005
315614AA2-178 GEN
Solar/Wind Harmer
0.368
316349AD2-085 GEN
Solar/Wind Harmer
0.043
316049AB1-081 GEN
Solar/Wind Harmer
0.366
316263AC1-034 GEN
Solar/Wind Harmer
2.446
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.254
3146456SLIGO L269
Solar/Wind Harmer
1.121
3137176SLIGO L2192
Solar/Wind Harmer
0.252
316339AD2-160 GEN
Solar/Wind Harmer
0.101
316388AE2-253 GEN
Solar/Wind Harmer
0.197
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316005AA1-067
Solar/Wind Harmer
0.067
942751AE2-291 GEN
Solar/Wind Harmer
3.431
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.763
316294AC1-161 GEN
Solar/Wind Harmer
1.072
316033AB2-134 GEN
Solar/Wind Harmer
0
966001AG1-469 GEN
Solar/Wind Helper
0.206
LAGNLTFEXP_LAGN->PJM
CLTF
1.975
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.463
TVALTFEXP_TVA->PJM
CLTF
0.975
CPLELTFEXP_CPLE->PJM
CLTF
4.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.728
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.137
MECLTFEXP_MEC->PJM
CLTF
0.549
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.615
LGEELTFEXP_LGEE->PJM
CLTF
0.138
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.8 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1349.42
MW Contribution:
20.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.635
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.467
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.402
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.114
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.731
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.293
970221AG2-151 GEN
Solar/Wind Harmer
28.434
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.927
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.892
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.504
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
970133AG2-095 GEN
Solar/Wind Harmer
0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.52
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.595
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.538
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
316192AB2-158 GEN
Solar/Wind Helper
1.015
3147666LOUISA
Solar/Wind Helper
0.588
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
3147983MERCK5
Solar/Wind Helper
0.055
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.649
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.8 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1349.39
MW Contribution:
20.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.634
316303AF2-085
50/50
2.054
316322AB2-045
Solar/Wind Harmer
1.38
971845AH1-439 GEN
Solar/Wind Harmer
21.466
316258AE1-075 C
Solar/Wind Harmer
0.683
316405AF2-144 C
Solar/Wind Harmer
0.721
946301AF1-294 GEN
Solar/Wind Harmer
6.005
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
15.189
970681AG2-440 GEN
Solar/Wind Harmer
10.081
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.438
316239AB2-077_GEN
Solar/Wind Harmer
0.438
316486AD2-202 GEN
Solar/Wind Harmer
0.311
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.77
971283AH1-107 GEN
Solar/Wind Harmer
1.77
970831AG2-522 GEN
Solar/Wind Harmer
5.288
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.401
946281AF1-292 GEN
Solar/Wind Harmer
0.208
970673AG2-436 GEN
Solar/Wind Harmer
19.501
970533AG2-339 GEN
Solar/Wind Harmer
5.966
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970085AG2-068 GEN
Solar/Wind Harmer
5.384
970581AG2-369 GEN
Solar/Wind Harmer
4.63
316426AA2-053 GEN
Solar/Wind Harmer
0.86
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.602
315652AC1-086 GEN
Solar/Wind Harmer
8.943
316274AC1-208 GEN
Solar/Wind Harmer
0.853
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.222
3146033SCOT NK
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.124
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
0.764
3151921BEARGRDN G2
50/50
4.223
3144293JTRSVLE
50/50
0.528
972003AH1-546 GEN
Solar/Wind Harmer
20.292
970221AG2-151 GEN
Solar/Wind Harmer
28.433
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.269
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.298
3143336POWHATN
Solar/Wind Harmer
2.847
315821AE2-092 GEN
Solar/Wind Harmer
5.533
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.926
970257AG2-171 GEN
Solar/Wind Harmer
7.298
971775AH1-396 GEN
Solar/Wind Harmer
1.373
964241AG1-285 GEN
Solar/Wind Harmer
12.891
958131AF2-107 GEN
Solar/Wind Harmer
4.848
316478AD1-087 GEN
Solar/Wind Harmer
1.062
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.948
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.921
316181AB2-040 GEN
Solar/Wind Harmer
1.255
944011AF1-069 GEN
Solar/Wind Harmer
5.212
970917AG2-570 GEN
Solar/Wind Harmer
21.8
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3150861SPRUNCD
Adder
0.344
3156081AA2-088 GEN
Solar/Wind Harmer
2.584
316011AB1-132 GEN
Solar/Wind Harmer
1.66
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.679
3146173TUNIS
Solar/Wind Harmer
-0.008
316123AC1-075 GEN
Solar/Wind Harmer
0.83
316317KELFORD C
Solar/Wind Harmer
0.356
3145823KELFORD
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
2.661
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.588
970657AG2-426 GEN
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.736
316283AC2-100 C
Solar/Wind Harmer
0.686
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.859
3146516WINFALL
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.192
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.418
316420AA1-050 GEN
Solar/Wind Harmer
0.814
316305AF2-043 C
Solar/Wind Harmer
0.215
316246AF1-032 C
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.824
316017AA1-139 ULT1
Solar/Wind Harmer
0.575
944581AF1-123 GEN
Solar/Wind Harmer
32.347
944601AF1-125 GEN
Solar/Wind Harmer
31.842
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142956BIRDNECK
Solar/Wind Harmer
0.381
3151101ELIZAR3
Adder
5.851
3144873MCLAUGH
Solar/Wind Harmer
0
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.432
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
315778AD1-151 GEN
Solar/Wind Harmer
6.03
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
970133AG2-095 GEN
Solar/Wind Harmer
0.026
970909AG2-566 GEN
50/50
2.392
3144293JTRSVLE
50/50
0.528
970535AG2-341 GEN
50/50
2.107
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
20.113
316313AB2-026
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
12.6
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
970323AG2-213 GEN
Solar/Wind Harmer
9.73
313527AB2-043 GEN
Solar/Wind Harmer
2.415
316237AB2-079_GEN
Solar/Wind Harmer
0.438
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.097
970099AG2-077 GEN
Solar/Wind Harmer
15.415
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.771
315687AD1-152 GEN
Solar/Wind Harmer
1.35
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.823
316248AF1-058 C
Solar/Wind Harmer
0.309
972187AH1-678 GEN
Adder
2.289
313506AB2-031 GEN
Solar/Wind Harmer
0.723
972185AH1-677 GEN
Adder
4.487
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316365GEN2_N
Solar/Wind Harmer
0.554
3144356SAPONY
Solar/Wind Harmer
0.284
316315AB2-025 C
Solar/Wind Harmer
0.219
962571AG1-106 GEN
Solar/Wind Harmer
1.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.795
315724AD1-057 GEN
Solar/Wind Harmer
1.464
316065AD1-022 GEN
Solar/Wind Harmer
3.666
316083AB2-161 GEN
Solar/Wind Harmer
1.185
315614AA2-178 GEN
Solar/Wind Harmer
0.781
316349AD2-085 GEN
Solar/Wind Harmer
0.644
316049AB1-081 GEN
Solar/Wind Harmer
0.778
316263AC1-034 GEN
Solar/Wind Harmer
3.388
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.823
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
316435W1029_GEN3
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3151931BEARGRDN S1
50/50
5.456
3151911BEARGRDN G1
50/50
4.223
3144293JTRSVLE
50/50
0.528
3144293JTRSVLE
50/50
0.417
970119AG2-088 GEN
50/50
15.408
971377AH1-170 GEN
Solar/Wind Harmer
5.687
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.519
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.349
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
19.594
316034AC1-036 C
Solar/Wind Harmer
0.36
315785AD2-033 C
Solar/Wind Harmer
4.22
316131AB2-060 GEN
Solar/Wind Harmer
1.635
315693AD1-088 GEN
Solar/Wind Harmer
7.417
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.537
970401AG2-262 GEN
Solar/Wind Harmer
0.797
971065AG2-659 GEN
Solar/Wind Harmer
5.504
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.946
960081AF2-299 GEN
Solar/Wind Harmer
1.043
316087AB2-174 GEN
Solar/Wind Harmer
1.295
941031AE2-094 GEN
Solar/Wind Harmer
16.634
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
8.076
3145783HORNRTN
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.85
940641AE2-051 GEN
Solar/Wind Harmer
7.88
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.554
939411AE1-173 GEN
Solar/Wind Harmer
40.408
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1
316319Z2-044 C
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.839
316381AD1-082 GEN
Solar/Wind Harmer
0.668
315737AD1-076 GEN
Solar/Wind Harmer
1.384
315816AE2-034 GEN
Solar/Wind Harmer
0.586
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.805
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.972
316093AE2-104_GEN
Solar/Wind Harmer
2.101
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.781
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
319010AE1-072 C
Solar/Wind Harmer
1.438
3146456SLIGO L269
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.463
315671AE2-027_GEN
Solar/Wind Harmer
1.282
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.447
316036AC1-147 C
Solar/Wind Harmer
0.19
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.142
315773AC2-141 GEN
Solar/Wind Harmer
2.919
3145336SMITFLD
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.356
316369SG1_INVT
Solar/Wind Harmer
1.209
3143096IRON208
Adder
0.253
971069AG2-661 GEN
Solar/Wind Harmer
1.072
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
944631AF1-128 GEN
Adder
26.85
316192AB2-158 GEN
Solar/Wind Helper
1.016
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.218
315839AE2-212 C
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
0.46
315732AD1-074 GEN1
Solar/Wind Harmer
1.472
315733AD1-074 GEN2
Solar/Wind Harmer
1.472
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316311AC2-079 GEN
Solar/Wind Harmer
3.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.781
316174AB2-169 GEN
Solar/Wind Harmer
1.108
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316018AA1-139 ULT2
Solar/Wind Harmer
0.609
957871AF2-081 GEN
Solar/Wind Harmer
3.561
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.217
3151081ELIZAR1
Adder
5.777
3151091ELIZAR2
Adder
5.677
316236AE1-162_GEN
Solar/Wind Harmer
0.208
971445AH1-216 GEN
Solar/Wind Harmer
4.272
3151201GRAVEL4
Adder
4.413
3151221GRAVEL6
Adder
4.407
3151191GRAVEL3
Adder
4.357
3151211GRAVEL5
Adder
4.357
315697AD1-025 GEN
Solar/Wind Harmer
1.369
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
315616AA1-038_C
Solar/Wind Helper
0.528
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316339AD2-160 GEN
Solar/Wind Harmer
0.479
316388AE2-253 GEN
Solar/Wind Harmer
0.479
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.748
316005AA1-067
Solar/Wind Harmer
0.143
316240AF1-291 C
Solar/Wind Harmer
0.213
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
942751AE2-291 GEN
Solar/Wind Harmer
4.506
944641AF1-129 GEN
Adder
29.789
316294AC1-161 GEN
Solar/Wind Harmer
2.256
316033AB2-134 GEN
Solar/Wind Harmer
2.184
966001AG1-469 GEN
Solar/Wind Helper
0.216
LAGNLTFEXP_LAGN->PJM
CLTF
1.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.441
TVALTFEXP_TVA->PJM
CLTF
0.968
CPLELTFEXP_CPLE->PJM
CLTF
4.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.648
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.595
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.113
MECLTFEXP_MEC->PJM
CLTF
0.54
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.611
LGEELTFEXP_LGEE->PJM
CLTF
0.134
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.03 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1286.56
MW Contribution:
20.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
957871AF2-081 GEN
Solar/Wind Harmer
3.285
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.03 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1286.56
MW Contribution:
20.55
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.529
3151911BEARGRDN G1
50/50
4.28
3144293JTRSVLE
50/50
0.524
3144293JTRSVLE
50/50
0.414
970119AG2-088 GEN
50/50
18.193
971377AH1-170 GEN
Solar/Wind Harmer
5.764
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.284
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
19.404
316034AC1-036 C
Solar/Wind Harmer
0.355
315785AD2-033 C
Solar/Wind Harmer
4.148
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.591
315693AD1-088 GEN
Solar/Wind Harmer
7.121
3143526WINTERP
Solar/Wind Harmer
-0.066
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.369
971065AG2-659 GEN
Solar/Wind Harmer
5.252
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.902
3150851SPRUNCC
Adder
0.382
960081AF2-299 GEN
Solar/Wind Harmer
0.984
316087AB2-174 GEN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.798
941031AE2-094 GEN
Solar/Wind Harmer
14.784
970919AG2-571 GEN
Solar/Wind Harmer
2.483
3142543TWELFTH
Solar/Wind Harmer
-0.001
970087AG2-069 GEN
Solar/Wind Harmer
7.272
316023GEN1_S
Solar/Wind Harmer
0.516
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.091
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
1.28
316381AD1-082 GEN
Solar/Wind Harmer
0.638
3156021HOLLOMANSOL
Solar/Wind Harmer
0.929
316319Z2-044 C
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
315737AD1-076 GEN
Solar/Wind Harmer
1.283
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316132AB2-190 GEN1
Solar/Wind Harmer
0.679
315816AE2-034 GEN
Solar/Wind Harmer
0.543
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.304
316359AB2-059 GEN
Solar/Wind Harmer
0.903
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.952
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
315611Z1-036_GEN2
Solar/Wind Harmer
1.649
316369SG1_INVT
Solar/Wind Harmer
1.186
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
972205AH1-687 GEN
50/50
20.911
316303AF2-085
50/50
2.426
316322AB2-045
Solar/Wind Harmer
1.391
971845AH1-439 GEN
Solar/Wind Harmer
21.635
316258AE1-075 C
Solar/Wind Harmer
0.724
316405AF2-144 C
Solar/Wind Harmer
0.764
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
15.019
970681AG2-440 GEN
Solar/Wind Harmer
9.969
3144303KENBRDG
Solar/Wind Harmer
-0.015
316238AB2-078_GEN
Solar/Wind Harmer
0.426
316239AB2-077_GEN
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316486AD2-202 GEN
Solar/Wind Harmer
0.295
970831AG2-522 GEN
Solar/Wind Harmer
5.034
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
971967AH1-528 GEN
Solar/Wind Harmer
16.704
946281AF1-292 GEN
Solar/Wind Harmer
0.196
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316426AA2-053 GEN
Solar/Wind Harmer
0.807
970673AG2-436 GEN
Solar/Wind Harmer
17.382
970533AG2-339 GEN
Solar/Wind Harmer
5.302
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.848
970581AG2-369 GEN
Solar/Wind Harmer
4.169
315814AE2-033 C
Solar/Wind Harmer
7.05
315652AC1-086 GEN
Solar/Wind Harmer
8.342
316274AC1-208 GEN
Solar/Wind Harmer
0.797
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
316210AC1-098 GEN
Solar/Wind Harmer
1.141
3146033SCOT NK
Solar/Wind Harmer
-0.029
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3151921BEARGRDN G2
50/50
4.28
3144293JTRSVLE
50/50
0.524
972003AH1-546 GEN
Solar/Wind Harmer
20.554
970221AG2-151 GEN
Solar/Wind Harmer
28.819
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.39
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.29
315821AE2-092 GEN
Solar/Wind Harmer
5.636
3147133PAMPLIN
Solar/Wind Harmer
-0.077
959311AF2-222 GEN
Solar/Wind Harmer
20.635
970257AG2-171 GEN
Solar/Wind Harmer
7.187
971775AH1-396 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
12.6
958131AF2-107 GEN
Solar/Wind Harmer
4.894
316478AD1-087 GEN
Solar/Wind Harmer
1.007
3147043LAWRENC
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.904
966621AG1-532 GEN
Solar/Wind Harmer
0.177
971683AH1-343 GEN
Solar/Wind Harmer
3.744
316181AB2-040 GEN
Solar/Wind Harmer
1.182
316327AA2-057 GEN
Solar/Wind Harmer
0.713
970657AG2-426 GEN
Solar/Wind Harmer
0.438
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.986
315833AF1-017_GEN
Solar/Wind Harmer
1.294
316311AC2-079 GEN
Solar/Wind Harmer
3.435
315732AD1-074 GEN1
Solar/Wind Harmer
1.365
315733AD1-074 GEN2
Solar/Wind Harmer
1.365
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.649
316174AB2-169 GEN
Solar/Wind Harmer
1.027
315697AD1-025 GEN
Solar/Wind Harmer
1.342
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.896
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
313526AB2-022
Solar/Wind Harmer
0.178
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
957871AF2-081 GEN
Solar/Wind Harmer
3.285
316316AC1-027 C
Solar/Wind Harmer
0.201
3151081ELIZAR1
Adder
5.337
3151091ELIZAR2
Adder
5.245
316236AE1-162_GEN
Solar/Wind Harmer
0.196
971445AH1-216 GEN
Solar/Wind Harmer
4.04
3151201GRAVEL4
Adder
4.225
3151221GRAVEL6
Adder
4.22
3151191GRAVEL3
Adder
4.172
3151211GRAVEL5
Adder
4.172
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315616AA1-038_C
Solar/Wind Helper
0.514
316190AA2-174 GEN
Solar/Wind Harmer
0.098
944011AF1-069 GEN
Solar/Wind Harmer
4.632
970917AG2-570 GEN
Solar/Wind Harmer
19.616
3156081AA2-088 GEN
Solar/Wind Harmer
2.416
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.795
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316212AC1-099_GEN
Solar/Wind Harmer
0.634
3146173TUNIS
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.332
3145823KELFORD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.419
315722AD1-056 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
1.405
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.696
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315735AD1-075 GEN1
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316458AB2-190 GEN2
Solar/Wind Harmer
0.679
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.947
961601AG1-000A GEN
Solar/Wind Harmer
2.656
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.756
3146516WINFALL
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.178
316305AF2-043 C
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.133
316320Y1-086
Solar/Wind Harmer
0.386
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.761
961611AG1-000B GEN
Solar/Wind Harmer
1.384
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.351
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.406
944581AF1-123 GEN
Solar/Wind Harmer
29.741
944601AF1-125 GEN
Solar/Wind Harmer
29.277
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
970909AG2-566 GEN
50/50
2.372
3144293JTRSVLE
50/50
0.524
970535AG2-341 GEN
50/50
2.034
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
316336AC2-165 C
Solar/Wind Harmer
21.056
316313AB2-026
Solar/Wind Harmer
0.804
970301AG2-198 GEN
Solar/Wind Harmer
12.491
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.632
970323AG2-213 GEN
Solar/Wind Harmer
9.583
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.426
3143526WINTERP
Solar/Wind Harmer
-0.066
962561AG1-105 GEN
Solar/Wind Harmer
6.846
964791AG1-342 GEN
Solar/Wind Harmer
2.512
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.548
316118AC1-105 GEN
Solar/Wind Harmer
0.739
315687AD1-152 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.295
970933AG2-581 GEN
Solar/Wind Harmer
9.025
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.056
3145783HORNRTN
Solar/Wind Harmer
0.959
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.017
316365GEN2_N
Solar/Wind Harmer
0.516
3144356SAPONY
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.203
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316140AB2-099
Solar/Wind Harmer
0.048
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.244
315742AE1-103 GEN
Solar/Wind Harmer
1.673
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
1.362
316349AD2-085 GEN
Solar/Wind Harmer
0.605
316065AD1-022 GEN
Solar/Wind Harmer
3.401
942751AE2-291 GEN
Solar/Wind Harmer
4.317
315614AA2-178 GEN
Solar/Wind Harmer
0.724
316049AB1-081 GEN
Solar/Wind Harmer
0.723
316263AC1-034 GEN
Solar/Wind Harmer
3.149
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.623
316033AB2-134 GEN
Solar/Wind Harmer
2.141
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.201
316433W1029_GEN2
Solar/Wind Harmer
1.201
316435W1029_GEN3
Solar/Wind Harmer
1.201
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316005AA1-067
Solar/Wind Harmer
0.133
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.69
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.083
3150701DARBY 4
Adder
4.074
3150681DARBY 2
Adder
4.069
3150671DARBY 1
Adder
4.064
966001AG1-469 GEN
Solar/Wind Helper
0.202
316294AC1-161 GEN
Solar/Wind Harmer
1.368
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.922
319010AE1-072 C
Solar/Wind Harmer
1.327
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.243
316375AC2-012 GEN
Solar/Wind Harmer
2.263
316036AC1-147 C
Solar/Wind Harmer
0.176
3150981CHESPKA
Adder
0.727
944591AF1-124 GEN
Solar/Wind Harmer
29.848
316072AD1-144
Solar/Wind Harmer
0.132
3145336SMITFLD
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
0.617
315773AC2-141 GEN
Solar/Wind Harmer
2.67
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.882
3147666LOUISA
Solar/Wind Helper
0.508
LAGNLTFEXP_LAGN->PJM
CLTF
1.767
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.765
TVALTFEXP_TVA->PJM
CLTF
0.872
CPLELTFEXP_CPLE->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.665
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.788
MECLTFEXP_MEC->PJM
CLTF
0.455
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.576
LGEELTFEXP_LGEE->PJM
CLTF
0.105
WECLTFEXP_WEC->PJM
CLTF
0.047

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.21 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1021.03
MW Contribution:
26.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
27.258
316322AB2-045
Solar/Wind Harmer
1.775
971845AH1-439 GEN
Solar/Wind Harmer
27.551
946301AF1-294 GEN
Solar/Wind Harmer
7.02
970909AG2-566 GEN
50/50
2.805
3144293JTRSVLE
50/50
0.618
970535AG2-341 GEN
50/50
2.051
316336AC2-165 C
Solar/Wind Harmer
42.179
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
970301AG2-198 GEN
Solar/Wind Harmer
14.775
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.28
970323AG2-213 GEN
Solar/Wind Harmer
10.867
313527AB2-043 GEN
Solar/Wind Harmer
2.468
316237AB2-079_GEN
Solar/Wind Harmer
0.445
962561AG1-105 GEN
Solar/Wind Harmer
6.959
964791AG1-342 GEN
Solar/Wind Harmer
2.534
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
316118AC1-105 GEN
Solar/Wind Harmer
0.73
970099AG2-077 GEN
Solar/Wind Harmer
13.191
315687AD1-152 GEN
Solar/Wind Harmer
1.188
316248AF1-058 C
Solar/Wind Harmer
0.284
970933AG2-581 GEN
Solar/Wind Harmer
6.805
942751AE2-291 GEN
Solar/Wind Harmer
4.456
966001AG1-469 GEN
Solar/Wind Helper
0.159
961791AG1-021 GEN
Solar/Wind Harmer
3.424
970683AG2-441 GEN
Solar/Wind Harmer
17.408
970681AG2-440 GEN
Solar/Wind Harmer
11.554
3144303KENBRDG
Solar/Wind Harmer
-0.017
316238AB2-078_GEN
Solar/Wind Harmer
0.445
316239AB2-077_GEN
Solar/Wind Harmer
0.445
316486AD2-202 GEN
Solar/Wind Harmer
0.275
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.429
946281AF1-292 GEN
Solar/Wind Harmer
0.145
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151921BEARGRDN G2
50/50
5.579
3144293JTRSVLE
50/50
0.618
972003AH1-546 GEN
Solar/Wind Harmer
26.738
970221AG2-151 GEN
Solar/Wind Harmer
37.543
3146776BUCKING
Solar/Wind Harmer
-0.019
270494AE1-108_GEN
Solar/Wind Harmer
12.249
3146926FARMVIL
Solar/Wind Harmer
-0.024
315821AE2-092 GEN
Solar/Wind Harmer
7.754
942461AE2-259 GEN
Solar/Wind Harmer
5.223
3147133PAMPLIN
Solar/Wind Harmer
-0.092
959311AF2-222 GEN
Solar/Wind Harmer
23.56
970257AG2-171 GEN
Solar/Wind Harmer
8.15
971775AH1-396 GEN
Solar/Wind Harmer
1.533
958131AF2-107 GEN
Solar/Wind Harmer
6.444
964241AG1-285 GEN
Solar/Wind Harmer
13.685
316478AD1-087 GEN
Solar/Wind Harmer
0.939
3147043LAWRENC
Solar/Wind Harmer
-0.005
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971683AH1-343 GEN
Solar/Wind Harmer
3.682
316123AC1-075 GEN
Solar/Wind Harmer
0.805
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
3151931BEARGRDN S1
50/50
7.207
3151911BEARGRDN G1
50/50
5.579
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.488
970937AG2-583 GEN
Solar/Wind Harmer
48.556
971377AH1-170 GEN
Solar/Wind Harmer
7.509
3147623JAMES R
Solar/Wind Harmer
0.929
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
971563AH1-280 GEN
Solar/Wind Harmer
3.424
970685AG2-442 GEN
Solar/Wind Harmer
22.673
316034AC1-036 C
Solar/Wind Harmer
0.403
315785AD2-033 C
Solar/Wind Harmer
4.657
316131AB2-060 GEN
Solar/Wind Harmer
1.684
315693AD1-088 GEN
Solar/Wind Harmer
7.148
970401AG2-262 GEN
Solar/Wind Harmer
0.774
957481AF2-042 GEN
Solar/Wind Harmer
32.976
971065AG2-659 GEN
Solar/Wind Harmer
4.765
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.734
962751AG1-124 GEN
Solar/Wind Harmer
4.607
960081AF2-299 GEN
Solar/Wind Harmer
0.726
LAGNLTFEXP_LAGN->PJM
CLTF
1.582
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.17
TVALTFEXP_TVA->PJM
CLTF
0.79
CPLELTFEXP_CPLE->PJM
CLTF
2.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.391
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.289
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.592
MECLTFEXP_MEC->PJM
CLTF
0.532
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.163
WECLTFEXP_WEC->PJM
CLTF
0.076

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.29 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:899.3
MW Contribution:
16.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.275
3151601KERR 3
50/50
0.117
3151611KERR 4
50/50
0.117
3151621KERR 5
50/50
0.117
3151631KERR 6
50/50
0.117
316258AE1-075 C
Solar/Wind Harmer
0.602
971845AH1-439 GEN
Solar/Wind Harmer
16.779
946301AF1-294 GEN
Solar/Wind Harmer
3.605
961791AG1-021 GEN
Solar/Wind Harmer
1.754
970683AG2-441 GEN
Solar/Wind Harmer
9.75
970681AG2-440 GEN
Solar/Wind Harmer
6.472
3144303KENBRDG
Solar/Wind Harmer
0.112
316233AE1-074 FULL
Solar/Wind Helper
0.266
3151921BEARGRDN G2
50/50
4.559
3144293JTRSVLE
50/50
0.463
3143336POWHATN
Solar/Wind Harmer
12.19
972003AH1-546 GEN
Solar/Wind Harmer
16.568
970221AG2-151 GEN
Solar/Wind Harmer
23.292
3146776BUCKING
Solar/Wind Harmer
0.136
270494AE1-108_GEN
Solar/Wind Harmer
4.117
315821AE2-092 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.619
959311AF2-222 GEN
Solar/Wind Harmer
12.976
958131AF2-107 GEN
Solar/Wind Harmer
4.136
970257AG2-171 GEN
Solar/Wind Harmer
4.467
971775AH1-396 GEN
Solar/Wind Harmer
0.223
964241AG1-285 GEN
Solar/Wind Harmer
7.167
3151931BEARGRDN S1
50/50
5.89
3151911BEARGRDN G1
50/50
4.559
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.365
3151591KERR 2
50/50
0.117
3151641KERR 7
50/50
0.117
3143336POWHATN
Solar/Wind Harmer
14.341
970937AG2-583 GEN
Solar/Wind Harmer
37.462
971377AH1-170 GEN
Solar/Wind Harmer
4.658
3147623JAMES R
Solar/Wind Harmer
1.012
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
971563AH1-280 GEN
Solar/Wind Harmer
1.949
970685AG2-442 GEN
Solar/Wind Harmer
12.798
316034AC1-036 C
Solar/Wind Harmer
0.009
315785AD2-033 C
Solar/Wind Harmer
1.058
316131AB2-060 GEN
Solar/Wind Harmer
0.29
315693AD1-088 GEN
Solar/Wind Harmer
3.806
970401AG2-262 GEN
Solar/Wind Harmer
0.394
962751AG1-124 GEN
Solar/Wind Harmer
2.968
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.907
970909AG2-566 GEN
50/50
2.107
3144293JTRSVLE
50/50
0.463
970535AG2-341 GEN
50/50
1.292
3151581KERR 1
50/50
0.042
316313AB2-026
Solar/Wind Harmer
0.502
316336AC2-165 C
Solar/Wind Harmer
38.092
3146776BUCKING
Solar/Wind Harmer
1.511
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
8.428
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.192
970323AG2-213 GEN
Solar/Wind Harmer
5.957
962561AG1-105 GEN
Solar/Wind Harmer
3.393
964791AG1-342 GEN
Solar/Wind Harmer
1.291
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
316118AC1-105 GEN
Solar/Wind Harmer
0.151
3143526WINTERP
Solar/Wind Helper
0.907
LAGNLTFEXP_LAGN->PJM
CLTF
1.316
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.108
TVALTFEXP_TVA->PJM
CLTF
0.676
CPLELTFEXP_CPLE->PJM
CLTF
1.266
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.537
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.502
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.387
MECLTFEXP_MEC->PJM
CLTF
0.774
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.419
LGEELTFEXP_LGEE->PJM
CLTF
0.312
WECLTFEXP_WEC->PJM
CLTF
0.156

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.55 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:893.41
MW Contribution:
10.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.454
3151541CLOVER2
50/50
2.169
3151601KERR 3
50/50
0.132
3151611KERR 4
50/50
0.132
3151621KERR 5
50/50
0.132
3151631KERR 6
50/50
0.132
316258AE1-075 C
Solar/Wind Harmer
0.531
971845AH1-439 GEN
Solar/Wind Harmer
11.703
946301AF1-294 GEN
Solar/Wind Harmer
2.93
961791AG1-021 GEN
Solar/Wind Harmer
1.426
970683AG2-441 GEN
Solar/Wind Harmer
8.125
970681AG2-440 GEN
Solar/Wind Harmer
5.392
3144303KENBRDG
Solar/Wind Harmer
0.096
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.103
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
316233AE1-074 FULL
Solar/Wind Helper
0.381
315839AE2-212 C
Solar/Wind Helper
0.156
3151931BEARGRDN S1
50/50
3.822
3151911BEARGRDN G1
50/50
2.958
3144293JTRSVLE
50/50
0.376
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.186
3151591KERR 2
50/50
0.132
3151641KERR 7
50/50
0.132
3143336POWHATN
Solar/Wind Harmer
12.652
970937AG2-583 GEN
Solar/Wind Harmer
28.68
971377AH1-170 GEN
Solar/Wind Harmer
3.024
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.584
970685AG2-442 GEN
Solar/Wind Harmer
10.536
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.762
315785AD2-033 C
Solar/Wind Harmer
0.926
957481AF2-042 GEN
Solar/Wind Harmer
29.081
316131AB2-060 GEN
Solar/Wind Harmer
0.28
970401AG2-262 GEN
Solar/Wind Harmer
0.449
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.297
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.954
3142416OLDCHRC
Solar/Wind Helper
0.298
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.644
3142433PROV 92
Solar/Wind Helper
0.446
970909AG2-566 GEN
50/50
1.866
3144293JTRSVLE
50/50
0.376
970535AG2-341 GEN
50/50
1.343
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
316313AB2-026
Solar/Wind Harmer
0.443
316336AC2-165 C
Solar/Wind Harmer
32.594
3146776BUCKING
Solar/Wind Harmer
1.048
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.463
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.782
970323AG2-213 GEN
Solar/Wind Harmer
5.132
970099AG2-077 GEN
Solar/Wind Harmer
11.633
962561AG1-105 GEN
Solar/Wind Harmer
3.754
964791AG1-342 GEN
Solar/Wind Harmer
1.469
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
316118AC1-105 GEN
Solar/Wind Harmer
0.185
3143526WINTERP
Solar/Wind Helper
1.297
316240AF1-291 C
Solar/Wind Helper
0.164
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.219
3151921BEARGRDN G2
50/50
2.958
3144293JTRSVLE
50/50
0.376
970413AG2-270 GEN
50/50
9.518
3143336POWHATN
Solar/Wind Harmer
10.755
972003AH1-546 GEN
Solar/Wind Harmer
10.819
970221AG2-151 GEN
Solar/Wind Harmer
15.119
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.707
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.496
959311AF2-222 GEN
Solar/Wind Harmer
11.062
970257AG2-171 GEN
Solar/Wind Harmer
3.849
971775AH1-396 GEN
Solar/Wind Harmer
0.192
958131AF2-107 GEN
Solar/Wind Harmer
2.946
316478AD1-087 GEN
Solar/Wind Harmer
0.352
964241AG1-285 GEN
Solar/Wind Harmer
6.616
3148013FISHERV
Solar/Wind Harmer
0.07
971683AH1-343 GEN
Solar/Wind Harmer
2.311
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.713
316075AC2-137 C
Solar/Wind Helper
0.174
316458AB2-190 GEN2
Solar/Wind Helper
0.644
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.969
TVALTFEXP_TVA->PJM
CLTF
0.708
CPLELTFEXP_CPLE->PJM
CLTF
0.585
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.743
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.245
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.615
MECLTFEXP_MEC->PJM
CLTF
1.03
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.346
LGEELTFEXP_LGEE->PJM
CLTF
0.443
WECLTFEXP_WEC->PJM
CLTF
0.226

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2054_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.57 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1014.95
MW Contribution:
21.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.288
316258AE1-075 C
Solar/Wind Harmer
2.194
316405AF2-144 C
Solar/Wind Harmer
2.316
316322AB2-045
Solar/Wind Harmer
1.426
971845AH1-439 GEN
Solar/Wind Harmer
22.103
946301AF1-294 GEN
Solar/Wind Harmer
5.26
961791AG1-021 GEN
Solar/Wind Harmer
2.566
970683AG2-441 GEN
Solar/Wind Harmer
12.84
970681AG2-440 GEN
Solar/Wind Harmer
8.522
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316233AE1-074 FULL
Solar/Wind Helper
0.268
3151931BEARGRDN S1
50/50
5.893
3151911BEARGRDN G1
50/50
4.561
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.365
3143336POWHATN
Solar/Wind Harmer
10.754
970937AG2-583 GEN
Solar/Wind Harmer
49.334
971377AH1-170 GEN
Solar/Wind Harmer
6.142
3147623JAMES R
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.566
970685AG2-442 GEN
Solar/Wind Harmer
16.853
316034AC1-036 C
Solar/Wind Harmer
0.291
315785AD2-033 C
Solar/Wind Harmer
3.326
316131AB2-060 GEN
Solar/Wind Harmer
1.128
315693AD1-088 GEN
Solar/Wind Harmer
4.447
970401AG2-262 GEN
Solar/Wind Harmer
0.493
962751AG1-124 GEN
Solar/Wind Harmer
4.402
3143226MDLTHAN
Solar/Wind Helper
0.216
3143526WINTERP
Solar/Wind Helper
0.912
3151921BEARGRDN G2
50/50
4.561
3144293JTRSVLE
50/50
0.463
3143336POWHATN
Solar/Wind Harmer
9.141
972003AH1-546 GEN
Solar/Wind Harmer
21.827
970221AG2-151 GEN
Solar/Wind Harmer
30.71
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
10.084
315821AE2-092 GEN
Solar/Wind Harmer
6.906
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.031
3147133PAMPLIN
Solar/Wind Harmer
-0.069
959311AF2-222 GEN
Solar/Wind Harmer
17.121
958131AF2-107 GEN
Solar/Wind Harmer
5.54
970257AG2-171 GEN
Solar/Wind Harmer
5.883
971775AH1-396 GEN
Solar/Wind Harmer
1.107
964241AG1-285 GEN
Solar/Wind Harmer
9.436
970909AG2-566 GEN
50/50
2.107
3144293JTRSVLE
50/50
0.463
316313AB2-026
Solar/Wind Harmer
2.438
316336AC2-165 C
Solar/Wind Harmer
52.734
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.096
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.208
970323AG2-213 GEN
Solar/Wind Harmer
7.843
313527AB2-043 GEN
Solar/Wind Harmer
1.639
316237AB2-079_GEN
Solar/Wind Harmer
0.294
962561AG1-105 GEN
Solar/Wind Harmer
4.47
964791AG1-342 GEN
Solar/Wind Harmer
1.615
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.455
3143526WINTERP
Solar/Wind Helper
0.912
LAGNLTFEXP_LAGN->PJM
CLTF
1.382
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.181
TVALTFEXP_TVA->PJM
CLTF
0.71
CPLELTFEXP_CPLE->PJM
CLTF
1.281
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.974
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.938
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.516
MECLTFEXP_MEC->PJM
CLTF
0.827
SIGELTFEXP_SIGE->PJM
CLTF
0.026
NYPJM->LTFIMP_NY
CLTF
0.436
LGEELTFEXP_LGEE->PJM
CLTF
0.335
WECLTFEXP_WEC->PJM
CLTF
0.168

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 233T2028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.84 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:998.06
MW Contribution:
21.82
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.277
316258AE1-075 C
Solar/Wind Harmer
2.194
316405AF2-144 C
Solar/Wind Harmer
2.316
316322AB2-045
Solar/Wind Harmer
1.426
971845AH1-439 GEN
Solar/Wind Harmer
22.094
946301AF1-294 GEN
Solar/Wind Harmer
5.26
961791AG1-021 GEN
Solar/Wind Harmer
2.566
970683AG2-441 GEN
Solar/Wind Harmer
12.838
970681AG2-440 GEN
Solar/Wind Harmer
8.521
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316233AE1-074 FULL
Solar/Wind Helper
0.267
970909AG2-566 GEN
50/50
2.107
3144293JTRSVLE
50/50
0.463
316313AB2-026
Solar/Wind Harmer
2.438
316336AC2-165 C
Solar/Wind Harmer
52.74
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.096
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.207
970323AG2-213 GEN
Solar/Wind Harmer
7.843
313527AB2-043 GEN
Solar/Wind Harmer
1.64
316237AB2-079_GEN
Solar/Wind Harmer
0.294
962561AG1-105 GEN
Solar/Wind Harmer
4.468
964791AG1-342 GEN
Solar/Wind Harmer
1.614
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3143526WINTERP
Solar/Wind Helper
0.908
3151921BEARGRDN G2
50/50
4.559
3144293JTRSVLE
50/50
0.463
3143336POWHATN
Solar/Wind Harmer
9.142
972003AH1-546 GEN
Solar/Wind Harmer
21.816
970221AG2-151 GEN
Solar/Wind Harmer
30.673
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
10.067
315821AE2-092 GEN
Solar/Wind Harmer
6.866
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.031
3147133PAMPLIN
Solar/Wind Harmer
-0.069
959311AF2-222 GEN
Solar/Wind Harmer
17.12
958131AF2-107 GEN
Solar/Wind Harmer
5.51
970257AG2-171 GEN
Solar/Wind Harmer
5.882
971775AH1-396 GEN
Solar/Wind Harmer
1.107
964241AG1-285 GEN
Solar/Wind Harmer
9.437
3151931BEARGRDN S1
50/50
5.89
3151911BEARGRDN G1
50/50
4.559
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.365
3143336POWHATN
Solar/Wind Harmer
10.756
970937AG2-583 GEN
Solar/Wind Harmer
49.326
971377AH1-170 GEN
Solar/Wind Harmer
6.135
3147623JAMES R
Solar/Wind Harmer
0.759
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.566
970685AG2-442 GEN
Solar/Wind Harmer
16.851
316034AC1-036 C
Solar/Wind Harmer
0.291
315785AD2-033 C
Solar/Wind Harmer
3.326
316131AB2-060 GEN
Solar/Wind Harmer
1.128
315693AD1-088 GEN
Solar/Wind Harmer
4.453
970401AG2-262 GEN
Solar/Wind Harmer
0.493
962751AG1-124 GEN
Solar/Wind Harmer
4.343
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.908
LAGNLTFEXP_LAGN->PJM
CLTF
1.324
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.118
TVALTFEXP_TVA->PJM
CLTF
0.68
CPLELTFEXP_CPLE->PJM
CLTF
1.268
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.593
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.558
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.404
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.421
LGEELTFEXP_LGEE->PJM
CLTF
0.315
WECLTFEXP_WEC->PJM
CLTF
0.157

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.81 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:997.75
MW Contribution:
22.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.554
316258AE1-075 C
Solar/Wind Harmer
2.203
316405AF2-144 C
Solar/Wind Harmer
2.326
316322AB2-045
Solar/Wind Harmer
1.444
971845AH1-439 GEN
Solar/Wind Harmer
22.379
946301AF1-294 GEN
Solar/Wind Harmer
5.335
961791AG1-021 GEN
Solar/Wind Harmer
2.602
970683AG2-441 GEN
Solar/Wind Harmer
13.026
970681AG2-440 GEN
Solar/Wind Harmer
8.645
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.299
316239AB2-077_GEN
Solar/Wind Harmer
0.299
316233AE1-074 FULL
Solar/Wind Helper
0.263
3151921BEARGRDN G2
50/50
4.616
3144293JTRSVLE
50/50
0.469
3143336POWHATN
Solar/Wind Harmer
9.18
972003AH1-546 GEN
Solar/Wind Harmer
22.089
970221AG2-151 GEN
Solar/Wind Harmer
29.401
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.651
3146926FARMVIL
Solar/Wind Harmer
-0.019
315821AE2-092 GEN
Solar/Wind Harmer
6.501
942461AE2-259 GEN
Solar/Wind Harmer
4.086
3147133PAMPLIN
Solar/Wind Harmer
-0.07
959311AF2-222 GEN
Solar/Wind Harmer
17.375
970257AG2-171 GEN
Solar/Wind Harmer
5.971
971775AH1-396 GEN
Solar/Wind Harmer
1.123
958131AF2-107 GEN
Solar/Wind Harmer
5.288
964241AG1-285 GEN
Solar/Wind Harmer
9.588
3151931BEARGRDN S1
50/50
5.964
3151911BEARGRDN G1
50/50
4.616
3144293JTRSVLE
50/50
0.469
3144293JTRSVLE
50/50
0.371
3143336POWHATN
Solar/Wind Harmer
10.8
970937AG2-583 GEN
Solar/Wind Harmer
49.734
971377AH1-170 GEN
Solar/Wind Harmer
5.88
3147623JAMES R
Solar/Wind Harmer
0.728
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.602
970685AG2-442 GEN
Solar/Wind Harmer
17.094
316034AC1-036 C
Solar/Wind Harmer
0.295
315785AD2-033 C
Solar/Wind Harmer
3.377
316131AB2-060 GEN
Solar/Wind Harmer
1.147
315693AD1-088 GEN
Solar/Wind Harmer
4.54
970401AG2-262 GEN
Solar/Wind Harmer
0.501
962751AG1-124 GEN
Solar/Wind Harmer
4.175
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.895
970909AG2-566 GEN
50/50
2.137
3144293JTRSVLE
50/50
0.469
316313AB2-026
Solar/Wind Harmer
2.448
316336AC2-165 C
Solar/Wind Harmer
53.006
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.257
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.253
970323AG2-213 GEN
Solar/Wind Harmer
7.961
313527AB2-043 GEN
Solar/Wind Harmer
1.667
316237AB2-079_GEN
Solar/Wind Harmer
0.299
962561AG1-105 GEN
Solar/Wind Harmer
4.541
964791AG1-342 GEN
Solar/Wind Harmer
1.64
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3143526WINTERP
Solar/Wind Helper
0.895
LAGNLTFEXP_LAGN->PJM
CLTF
1.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.153
TVALTFEXP_TVA->PJM
CLTF
0.671
CPLELTFEXP_CPLE->PJM
CLTF
1.298
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.365
MECLTFEXP_MEC->PJM
CLTF
0.759
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.419
LGEELTFEXP_LGEE->PJM
CLTF
0.305
WECLTFEXP_WEC->PJM
CLTF
0.152

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: WT2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.79 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:997.51
MW Contribution:
22.09
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.554
316258AE1-075 C
Solar/Wind Harmer
2.203
316405AF2-144 C
Solar/Wind Harmer
2.326
316322AB2-045
Solar/Wind Harmer
1.444
971845AH1-439 GEN
Solar/Wind Harmer
22.379
946301AF1-294 GEN
Solar/Wind Harmer
5.335
961791AG1-021 GEN
Solar/Wind Harmer
2.602
970683AG2-441 GEN
Solar/Wind Harmer
13.026
970681AG2-440 GEN
Solar/Wind Harmer
8.645
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.299
316239AB2-077_GEN
Solar/Wind Harmer
0.299
316233AE1-074 FULL
Solar/Wind Helper
0.263
3151921BEARGRDN G2
50/50
4.616
3144293JTRSVLE
50/50
0.469
3143336POWHATN
Solar/Wind Harmer
9.18
972003AH1-546 GEN
Solar/Wind Harmer
22.089
970221AG2-151 GEN
Solar/Wind Harmer
29.401
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.651
3146926FARMVIL
Solar/Wind Harmer
-0.019
315821AE2-092 GEN
Solar/Wind Harmer
6.501
942461AE2-259 GEN
Solar/Wind Harmer
4.086
3147133PAMPLIN
Solar/Wind Harmer
-0.07
959311AF2-222 GEN
Solar/Wind Harmer
17.375
970257AG2-171 GEN
Solar/Wind Harmer
5.971
971775AH1-396 GEN
Solar/Wind Harmer
1.123
958131AF2-107 GEN
Solar/Wind Harmer
5.288
964241AG1-285 GEN
Solar/Wind Harmer
9.588
3151931BEARGRDN S1
50/50
5.964
3151911BEARGRDN G1
50/50
4.616
3144293JTRSVLE
50/50
0.469
3144293JTRSVLE
50/50
0.371
3143336POWHATN
Solar/Wind Harmer
10.8
970937AG2-583 GEN
Solar/Wind Harmer
49.734
971377AH1-170 GEN
Solar/Wind Harmer
5.88
3147623JAMES R
Solar/Wind Harmer
0.728
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.602
970685AG2-442 GEN
Solar/Wind Harmer
17.094
316034AC1-036 C
Solar/Wind Harmer
0.295
315785AD2-033 C
Solar/Wind Harmer
3.377
316131AB2-060 GEN
Solar/Wind Harmer
1.147
315693AD1-088 GEN
Solar/Wind Harmer
4.54
970401AG2-262 GEN
Solar/Wind Harmer
0.501
962751AG1-124 GEN
Solar/Wind Harmer
4.175
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.895
970909AG2-566 GEN
50/50
2.137
3144293JTRSVLE
50/50
0.469
316313AB2-026
Solar/Wind Harmer
2.448
316336AC2-165 C
Solar/Wind Harmer
53.006
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.257
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.253
970323AG2-213 GEN
Solar/Wind Harmer
7.961
313527AB2-043 GEN
Solar/Wind Harmer
1.667
316237AB2-079_GEN
Solar/Wind Harmer
0.299
962561AG1-105 GEN
Solar/Wind Harmer
4.541
964791AG1-342 GEN
Solar/Wind Harmer
1.64
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3143526WINTERP
Solar/Wind Helper
0.895
LAGNLTFEXP_LAGN->PJM
CLTF
1.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.153
TVALTFEXP_TVA->PJM
CLTF
0.671
CPLELTFEXP_CPLE->PJM
CLTF
1.298
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.365
MECLTFEXP_MEC->PJM
CLTF
0.759
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.419
LGEELTFEXP_LGEE->PJM
CLTF
0.305
WECLTFEXP_WEC->PJM
CLTF
0.152

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.67 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:996.36
MW Contribution:
14.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.444
316258AE1-075 C
Solar/Wind Harmer
1.934
316405AF2-144 C
Solar/Wind Harmer
2.042
316322AB2-045
Solar/Wind Harmer
0.988
971845AH1-439 GEN
Solar/Wind Harmer
15.409
946301AF1-294 GEN
Solar/Wind Harmer
4.285
961791AG1-021 GEN
Solar/Wind Harmer
2.09
970683AG2-441 GEN
Solar/Wind Harmer
10.725
970681AG2-440 GEN
Solar/Wind Harmer
7.118
3144303KENBRDG
Solar/Wind Harmer
-0.011
971967AH1-528 GEN
Solar/Wind Harmer
23.617
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
316486AD2-202 GEN
Solar/Wind Harmer
0.291
316238AB2-078_GEN
Solar/Wind Harmer
0.292
316239AB2-077_GEN
Solar/Wind Harmer
0.292
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.004
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Helper
0.383
315839AE2-212 C
Solar/Wind Helper
0.159
970909AG2-566 GEN
50/50
1.869
3144293JTRSVLE
50/50
0.377
316313AB2-026
Solar/Wind Harmer
2.149
316336AC2-165 C
Solar/Wind Harmer
45.095
3146776BUCKING
Solar/Wind Harmer
-0.117
3146776BUCKING
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
9.845
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.613
970323AG2-213 GEN
Solar/Wind Harmer
6.778
970933AG2-581 GEN
Solar/Wind Harmer
11.778
970099AG2-077 GEN
Solar/Wind Harmer
15.401
313527AB2-043 GEN
Solar/Wind Harmer
1.608
315687AD1-152 GEN
Solar/Wind Harmer
1.169
316237AB2-079_GEN
Solar/Wind Harmer
0.292
962561AG1-105 GEN
Solar/Wind Harmer
4.98
964791AG1-342 GEN
Solar/Wind Harmer
1.851
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
316118AC1-105 GEN
Solar/Wind Harmer
0.563
316248AF1-058 C
Solar/Wind Harmer
0.234
3143526WINTERP
Solar/Wind Helper
1.305
316240AF1-291 C
Solar/Wind Helper
0.166
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.159
316312AB1-027
Solar/Wind Helper
0.221
3151921BEARGRDN G2
50/50
2.956
3144293JTRSVLE
50/50
0.377
3143336POWHATN
Solar/Wind Harmer
8.06
972003AH1-546 GEN
Solar/Wind Harmer
14.237
970221AG2-151 GEN
Solar/Wind Harmer
19.894
3146776BUCKING
Solar/Wind Harmer
-0.01
270494AE1-108_GEN
Solar/Wind Harmer
6.615
3146926FARMVIL
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
4.818
942461AE2-259 GEN
Solar/Wind Harmer
3.131
3147133PAMPLIN
Solar/Wind Harmer
-0.056
959311AF2-222 GEN
Solar/Wind Harmer
14.638
970257AG2-171 GEN
Solar/Wind Harmer
5.084
971775AH1-396 GEN
Solar/Wind Harmer
0.956
958131AF2-107 GEN
Solar/Wind Harmer
3.928
316478AD1-087 GEN
Solar/Wind Harmer
0.993
964241AG1-285 GEN
Solar/Wind Harmer
8.748
3148013FISHERV
Solar/Wind Harmer
-0.008
316003AC1-222 GEN
Solar/Wind Harmer
0.728
971683AH1-343 GEN
Solar/Wind Harmer
3.075
316123AC1-075 GEN
Solar/Wind Harmer
0.688
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.721
316075AC2-137 C
Solar/Wind Helper
0.176
316458AB2-190 GEN2
Solar/Wind Helper
0.654
3151931BEARGRDN S1
50/50
3.819
3151911BEARGRDN G1
50/50
2.956
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.298
3143336POWHATN
Solar/Wind Harmer
9.482
970937AG2-583 GEN
Solar/Wind Harmer
37.736
971377AH1-170 GEN
Solar/Wind Harmer
3.979
3147623JAMES R
Solar/Wind Harmer
0.492
3146776BUCKING
Solar/Wind Harmer
-0.012
3146926FARMVIL
Solar/Wind Harmer
-0.014
971563AH1-280 GEN
Solar/Wind Harmer
2.09
970685AG2-442 GEN
Solar/Wind Harmer
13.906
316034AC1-036 C
Solar/Wind Harmer
0.251
315693AD1-088 GEN
Solar/Wind Harmer
6.775
315785AD2-033 C
Solar/Wind Harmer
2.921
957481AF2-042 GEN
Solar/Wind Harmer
38.503
316131AB2-060 GEN
Solar/Wind Harmer
1.093
970401AG2-262 GEN
Solar/Wind Harmer
0.565
3143226MDLTHAN
Solar/Wind Helper
0.302
3143526WINTERP
Solar/Wind Helper
1.305
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.968
3142416OLDCHRC
Solar/Wind Helper
0.301
3142416OLDCHRC
Solar/Wind Helper
0.115
316132AB2-190 GEN1
Solar/Wind Helper
0.654
3142433PROV 92
Solar/Wind Helper
0.453
LAGNLTFEXP_LAGN->PJM
CLTF
1.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.22
TVALTFEXP_TVA->PJM
CLTF
0.749
CPLELTFEXP_CPLE->PJM
CLTF
0.697
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.517
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.755
MECLTFEXP_MEC->PJM
CLTF
1.071
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.358
LGEELTFEXP_LGEE->PJM
CLTF
0.457
WECLTFEXP_WEC->PJM
CLTF
0.233

Details for 6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.48 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1136.48
MW Contribution:
4.37
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
5.88
3151881LOWMORC
50/50
1.12
3151881LOWMORC
50/50
1.102
3151861LOWMORA
50/50
1.085
3152031BATH 3C
50/50
2.047
3152051BATH 5E
50/50
2.046
3152011BATH 1A
50/50
2.044
3152041BATH 4D
50/50
2.043
23503501NHY_Z2-039
50/50
0.005
23503401SHY_Z2-039
50/50
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
3148463FAIRFLD
Solar/Wind Harmer
0.099
971845AH1-439 GEN
Solar/Wind Harmer
4.38
315651AD1-115 GEN
Solar/Wind Helper
0.966
316164AC1-076 GEN
Solar/Wind Helper
1.193
3151921BEARGRDN G2
50/50
1.203
3151861LOWMORA
50/50
1.129
3152191CUNINGD
50/50
1.775
972255AH1-712 GEN
50/50
53.738
315760AF1-028 GEN
50/50
15.229
3152061BATH 6F
50/50
2.05
3152021BATH 2B
50/50
2.044
3148013FISHERV
Solar/Wind Harmer
0.138
315821AE2-092 GEN
Solar/Wind Harmer
0
970221AG2-151 GEN
Solar/Wind Harmer
6.845
972003AH1-546 GEN
Solar/Wind Harmer
4.369
270494AE1-108_GEN
Solar/Wind Harmer
1.304
3146776BUCKING
Solar/Wind Harmer
0.036
3146926FARMVIL
Solar/Wind Harmer
0.044
958131AF2-107 GEN
Solar/Wind Harmer
1.933
942461AE2-259 GEN
Solar/Wind Harmer
0
3132273ORANGE
Solar/Wind Helper
0.105
3147666LOUISA
Solar/Wind Helper
1.084
3151931BEARGRDN S1
50/50
1.555
3151911BEARGRDN G1
50/50
1.203
972277AH1-723 GEN
50/50
62.621
971377AH1-170 GEN
Solar/Wind Harmer
1.369
3147623JAMES R
Solar/Wind Harmer
0.297
3146776BUCKING
Solar/Wind Harmer
0.04
970937AG2-583 GEN
Solar/Wind Harmer
6.046
3147983MERCK5
Solar/Wind Harmer
0.038
3146926FARMVIL
Solar/Wind Harmer
0.044
316192AB2-158 GEN
Solar/Wind Helper
3.269
3147666LOUISA
Solar/Wind Helper
1.885
3137383CUSHAW
50/50
0.021
3152181CUNINGC
50/50
0.816
3152171CUNINGB
50/50
0.768
3152161CUNINGA
50/50
0.763
972193AH1-681 GEN
50/50
2.401
3146776BUCKING
Solar/Wind Harmer
0.395
3146776BUCKING
Solar/Wind Harmer
0.032
3132123MT JACKSON
Solar/Wind Harmer
0.208
970117AG2-086 GEN
Solar/Wind Harmer
1.596
970117AG2-086 GEN
Solar/Wind Harmer
1.064
316336AC2-165 C
Solar/Wind Harmer
3.133
966001AG1-469 GEN
Solar/Wind Helper
0.735
316006AB2-029 C
Solar/Wind Helper
0.088
LAGNLTFEXP_LAGN->PJM
CLTF
2.708
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.552
TVALTFEXP_TVA->PJM
CLTF
1.406
CPLELTFEXP_CPLE->PJM
CLTF
0.945
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.548
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.844
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.211
MECLTFEXP_MEC->PJM
CLTF
2.087
SIGELTFEXP_SIGE->PJM
CLTF
0.068
NYPJM->LTFIMP_NY
CLTF
0.744
LGEELTFEXP_LGEE->PJM
CLTF
0.897
WECLTFEXP_WEC->PJM
CLTF
0.46

Details for 6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.13 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1015.01
MW Contribution:
4.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
6.157
3151881LOWMORC
50/50
0.936
3151881LOWMORC
50/50
0.921
3151861LOWMORA
50/50
0.906
3152031BATH 3C
50/50
1.635
3152051BATH 5E
50/50
1.635
3152011BATH 1A
50/50
1.633
3152041BATH 4D
50/50
1.632
23503501NHY_Z2-039
50/50
0.004
23503401SHY_Z2-039
50/50
0.002
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.074
3148013FISHERV
Solar/Wind Harmer
0.071
971845AH1-439 GEN
Solar/Wind Harmer
4.836
3148463FAIRFLD
Solar/Wind Harmer
0.083
316258AE1-075 C
Solar/Wind Harmer
0.05
946301AF1-294 GEN
Solar/Wind Harmer
1.229
961791AG1-021 GEN
Solar/Wind Harmer
0.598
970683AG2-441 GEN
Solar/Wind Harmer
3.461
970681AG2-440 GEN
Solar/Wind Harmer
2.297
315651AD1-115 GEN
Solar/Wind Helper
0.973
316164AC1-076 GEN
Solar/Wind Helper
1.197
3151921BEARGRDN G2
50/50
1.26
3151861LOWMORA
50/50
0.943
315760AF1-028 GEN
50/50
12.702
3152061BATH 6F
50/50
1.638
3152021BATH 2B
50/50
1.633
3144293JTRSVLE
50/50
0.158
3152191CUNINGD
50/50
1.058
972255AH1-712 GEN
50/50
32.029
972003AH1-546 GEN
Solar/Wind Harmer
4.596
970221AG2-151 GEN
Solar/Wind Harmer
7.054
315821AE2-092 GEN
Solar/Wind Harmer
0
3148013FISHERV
Solar/Wind Harmer
0.123
270494AE1-108_GEN
Solar/Wind Harmer
1.333
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.052
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
1.009
958131AF2-107 GEN
Solar/Wind Harmer
1.905
3147133PAMPLIN
Solar/Wind Harmer
0.206
3132273ORANGE
Solar/Wind Helper
0.106
3147666LOUISA
Solar/Wind Helper
1.085
3137383CUSHAW
50/50
0.018
970909AG2-566 GEN
50/50
0.694
3144293JTRSVLE
50/50
0.158
3152181CUNINGC
50/50
0.486
3152171CUNINGB
50/50
0.458
3152161CUNINGA
50/50
0.455
972193AH1-681 GEN
50/50
1.431
3146776BUCKING
Solar/Wind Harmer
0.434
3146776BUCKING
Solar/Wind Harmer
0.035
316336AC2-165 C
Solar/Wind Harmer
3.993
316313AB2-026
Solar/Wind Harmer
0.042
3147133PAMPLIN
Solar/Wind Harmer
0.066
3147133PAMPLIN
Solar/Wind Harmer
0.053
970301AG2-198 GEN
Solar/Wind Harmer
2.775
958211AF2-115 GEN
Solar/Wind Harmer
0.748
966001AG1-469 GEN
Solar/Wind Helper
0.74
316006AB2-029 C
Solar/Wind Helper
0.089
3151931BEARGRDN S1
50/50
1.628
3151911BEARGRDN G1
50/50
1.26
3144293JTRSVLE
50/50
0.158
3144293JTRSVLE
50/50
0.125
972277AH1-723 GEN
50/50
37.324
971377AH1-170 GEN
Solar/Wind Harmer
1.411
3147623JAMES R
Solar/Wind Harmer
0.307
970937AG2-583 GEN
Solar/Wind Harmer
6.726
3146776BUCKING
Solar/Wind Harmer
0.043
3146926FARMVIL
Solar/Wind Harmer
0.052
3147983MERCK5
Solar/Wind Harmer
0.033
3143336POWHATN
Solar/Wind Harmer
1.187
971563AH1-280 GEN
Solar/Wind Harmer
0.665
970685AG2-442 GEN
Solar/Wind Harmer
4.455
316192AB2-158 GEN
Solar/Wind Helper
3.275
3147666LOUISA
Solar/Wind Helper
1.888
LAGNLTFEXP_LAGN->PJM
CLTF
2.956
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.464
TVALTFEXP_TVA->PJM
CLTF
1.521
CPLELTFEXP_CPLE->PJM
CLTF
1.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.062
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.536
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.509
MECLTFEXP_MEC->PJM
CLTF
2.016
SIGELTFEXP_SIGE->PJM
CLTF
0.065
NYPJM->LTFIMP_NY
CLTF
0.852
LGEELTFEXP_LGEE->PJM
CLTF
0.84
WECLTFEXP_WEC->PJM
CLTF
0.429

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.88 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:1802.21
MW Contribution:
2.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
3150011OMF A
50/50
0.213
972223AH1-696 GEN
50/50
9.014
3150151POSSMC1
50/50
1.141
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.208
3150211REMNGT1
50/50
13.121
972201AH1-685 GEN
50/50
2.279
3150281M RUN A
Adder
13.337
971685AH1-345 GEN
Solar/Wind Harmer
0.729
316447AC1-158 HLD
Solar/Wind Harmer
1.006
316044AC1-158 PL1
Solar/Wind Harmer
0.458
972197AH1-683 GEN
Adder
1.977
972219AH1-694 GEN
Adder
1.423
316254AC1-120 GEN1
Solar/Wind Harmer
3.292
316170AC1-121 GEN2
Solar/Wind Harmer
1.13
972135AH1-637 GEN
Solar/Wind Harmer
0.78
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.208
970053AG2-049 GEN
50/50
2.019
3140676OCCOQUN
50/50
0.016
3138216PACIFIC
Solar/Wind Harmer
0.025
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.698
3150381LDYSMT2
Adder
12.153
972213AH1-691 GEN
Adder
2.056
972215AH1-692 GEN
Adder
2.056
315651AD1-115 GEN
Solar/Wind Harmer
0
316164AC1-076 GEN
Solar/Wind Harmer
0.129
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.087
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
3152111X4-039 GT1
50/50
1.844
315747AE2-019 GEN
50/50
13.161
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.497
316337AD2-073 GEN
Solar/Wind Harmer
0.076
3150091POSSM6B
50/50
0.849
3150071POSSM 5
50/50
52.154
3150181POSSMC2
50/50
1.151
3150181POSSMC2
50/50
1.141
3150181POSSMC2
50/50
1.141
316045AC1-158 PL2
Solar/Wind Harmer
1.464
316450AC1-158 RIC
Solar/Wind Harmer
0.122
3150391LDYSMT3
Adder
12.635
972195AH1-682 GEN
Adder
1.66
315673AE1-157 GEN
Solar/Wind Harmer
6.386
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.912
3150341NORNECKC1
Adder
0.905
966001AG1-469 GEN
Solar/Wind Harmer
0.051
3151731LOISA B
Adder
5.59
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316312AB1-027
Solar/Wind Harmer
0.15
316156AD2-030 GEN
Solar/Wind Harmer
0.062
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
3150681DARBY 2
Adder
6.037
3150671DARBY 1
Adder
6.03
315976AC1-164 GENA
Solar/Wind Harmer
0.883
316169AC1-164_GENC
Solar/Wind Harmer
0.763
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.434
971223AH1-071 GEN
Solar/Wind Harmer
0.889
944641AF1-129 GEN
Adder
39.347
316033AB2-134 GEN
Solar/Wind Harmer
0
316294AC1-161 GEN
Solar/Wind Harmer
1.396
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.192
3145506HICKORY
Solar/Wind Harmer
0.048
316349AD2-085 GEN
Solar/Wind Harmer
0.053
316339AD2-160 GEN
Solar/Wind Harmer
0.128
316388AE2-253 GEN
Solar/Wind Harmer
0.249
3137176SLIGO L2192
Solar/Wind Harmer
0.318
3146456SLIGO L269
Solar/Wind Harmer
1.414
3130086AYDLETT
Solar/Wind Harmer
0.319
315835AF2-110_GEN
Solar/Wind Harmer
0.547
3146386ELIZ CT
Solar/Wind Harmer
0.079
316313AB2-026
Solar/Wind Harmer
0.049
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146626S HERTFORD
Solar/Wind Harmer
0.078
3144356SAPONY
Solar/Wind Harmer
0.656
316315AB2-025 C
Solar/Wind Harmer
0.063
316336AC2-165 C
Solar/Wind Harmer
3.964
315742AE1-103 GEN
Solar/Wind Harmer
1.163
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.323
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.435
970933AG2-581 GEN
Solar/Wind Harmer
6.095
316065AD1-022 GEN
Solar/Wind Harmer
3.468
316365GEN2_N
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
316140AB2-099
Solar/Wind Harmer
0.026
970099AG2-077 GEN
Solar/Wind Harmer
7.893
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
970301AG2-198 GEN
Solar/Wind Harmer
3.132
962571AG1-106 GEN
Solar/Wind Harmer
1.044
3146776BUCKING
Solar/Wind Harmer
0.293
3141873WAN 176
Solar/Wind Harmer
0.017
970189AG2-124 GEN
Solar/Wind Harmer
2.502
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.159
971283AH1-107 GEN
Solar/Wind Harmer
1.159
971285AH1-108 GEN
Adder
0.63
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316159AE1-175 C
Solar/Wind Harmer
0.071
315697AD1-025 GEN
Solar/Wind Harmer
0.088
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151191GRAVEL3
Adder
5.855
3151211GRAVEL5
Adder
5.855
971445AH1-216 GEN
Solar/Wind Harmer
5.713
3143316POE
Solar/Wind Harmer
0.321
970657AG2-426 GEN
Solar/Wind Harmer
0.592
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.077
316311AC2-079 GEN
Solar/Wind Harmer
2.299
957871AF2-081 GEN
Solar/Wind Harmer
3.983
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.042
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316258AE1-075 C
Solar/Wind Harmer
0.059
3146396TANGLEW
Solar/Wind Harmer
0.218
3145176PASQUOTANK
Solar/Wind Harmer
0.049
315814AE2-033 C
Solar/Wind Harmer
6.193
970533AG2-339 GEN
Solar/Wind Harmer
5.901
970673AG2-436 GEN
Solar/Wind Harmer
9.667
3130156CHOWAN
Solar/Wind Harmer
0.077
3130156CHOWAN
Solar/Wind Harmer
0.077
971967AH1-528 GEN
Solar/Wind Harmer
12.296
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.431
315733AD1-074 GEN2
Solar/Wind Harmer
0.431
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.806
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
3.973
970581AG2-369 GEN
Solar/Wind Harmer
3.417
316463AE2-346 GEN
Solar/Wind Harmer
0.064
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.148
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
3137643SOCKMAN
Solar/Wind Harmer
0.293
315652AC1-086 GEN
Solar/Wind Harmer
8.072
316426AA2-053 GEN
Solar/Wind Harmer
0.245
972205AH1-687 GEN
Adder
3.128
971845AH1-439 GEN
Solar/Wind Harmer
3.318
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
316486AD2-202 GEN
Solar/Wind Harmer
0.074
3146033SCOT NK
Solar/Wind Harmer
0.29
946301AF1-294 GEN
Solar/Wind Harmer
1.421
961791AG1-021 GEN
Solar/Wind Harmer
0.691
316210AC1-098 GEN
Solar/Wind Harmer
0.664
970683AG2-441 GEN
Solar/Wind Harmer
4.325
970681AG2-440 GEN
Solar/Wind Harmer
2.871
970831AG2-522 GEN
Solar/Wind Harmer
3.061
316274AC1-208 GEN
Solar/Wind Harmer
0.369
3144303KENBRDG
Solar/Wind Harmer
0.057
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316327AA2-057 GEN
Solar/Wind Harmer
0.104
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.026
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.639
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205943AE1-185 GEN
Solar/Wind Helper
0.388
205956AE1-196_GEN
Solar/Wind Helper
0.386
959381AF2-229 GEN
Solar/Wind Helper
0.257
20390526W1-045 C
Solar/Wind Helper
0.253
233915AB1-141 GEN
Solar/Wind Helper
0.305
233940AF2-379 C
Solar/Wind Helper
0.037
233901CHERRYDALE C
Solar/Wind Helper
0.14
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
228728W1-130C
Solar/Wind Helper
0.032
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.034
20720728JCB_W1-129
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
20673828FLE_V3-070
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.056
20676428JCR_X2-075
Solar/Wind Helper
0.039
3150351NORNECKC2
Adder
0.868
3141726DUNNSVL
Solar/Wind Harmer
0.347
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
2.855
962861AG1-135 GEN
Solar/Wind Harmer
2.759
3151751LOISA D
Adder
5.59
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3142433PROV 92
Solar/Wind Harmer
0.336
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
315975AC1-164 GENB
Solar/Wind Harmer
0.026
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.434
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.784
3143226MDLTHAN
Solar/Wind Harmer
0.083
971317AH1-138 GEN
Solar/Wind Harmer
0.617
316132AB2-190 GEN1
Solar/Wind Harmer
0.439
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.459
961611AG1-000B GEN
Solar/Wind Harmer
4.282
3151171GRAVELC
Adder
0.867
3145336SMITFLD
Solar/Wind Harmer
0.324
315773AC2-141 GEN
Solar/Wind Harmer
2.95
316381AD1-082 GEN
Solar/Wind Harmer
0.082
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.014
3150981CHESPKA
Adder
1.005
944591AF1-124 GEN
Solar/Wind Harmer
18.181
316072AD1-144
Solar/Wind Harmer
0.029
939411AE1-173 GEN
Solar/Wind Harmer
34.104
3146456SLIGO L269
Solar/Wind Harmer
0.08
319010AE1-072 C
Solar/Wind Harmer
0.398
940641AE2-051 GEN
Solar/Wind Harmer
6.384
316093AE2-104_GEN
Solar/Wind Harmer
1.34
3143336POWHATN
Solar/Wind Harmer
1.41
3146516WINFALL
Solar/Wind Harmer
0.255
3146516WINFALL
Solar/Wind Harmer
0.079
941031AE2-094 GEN
Solar/Wind Harmer
14.385
3130156CHOWAN
Solar/Wind Harmer
0.077
315816AE2-034 GEN
Solar/Wind Harmer
0.327
3145663CRESWEL
Solar/Wind Harmer
0.214
971163AH1-040 GEN
Solar/Wind Harmer
6.123
315737AD1-076 GEN
Solar/Wind Harmer
0.97
970937AG2-583 GEN
Solar/Wind Harmer
4.632
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.603
316023GEN1_S
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.667
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.335
970087AG2-069 GEN
Solar/Wind Harmer
5.959
960081AF2-299 GEN
Solar/Wind Harmer
0.713
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.149
957481AF2-042 GEN
Solar/Wind Harmer
19.733
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.538
3145963POPLR C
Solar/Wind Harmer
0.073
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.663
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
971563AH1-280 GEN
Solar/Wind Harmer
0.768
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
970685AG2-442 GEN
Solar/Wind Harmer
5.367
972277AH1-723 GEN
Adder
42.768
3146293MARTNCO
Solar/Wind Harmer
0.066
316129AC1-054 GEN
Solar/Wind Harmer
0.267
316034AC1-036 C
Solar/Wind Harmer
0.005
971377AH1-170 GEN
Solar/Wind Harmer
0.762
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.047
315785AD2-033 C
Solar/Wind Harmer
0.577
316131AB2-060 GEN
Solar/Wind Harmer
0.221
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316494AC1-189 GEN
Solar/Wind Harmer
0.237
3146233WITAKRS
Solar/Wind Harmer
0.277
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3145493TOT1
Solar/Wind Harmer
0.309
316359AB2-059 GEN
Solar/Wind Harmer
0.245
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.121
970401AG2-262 GEN
Solar/Wind Harmer
0.403
3147983MERCK5
Solar/Wind Harmer
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.485
208835TUHI V3-051
Solar/Wind Helper
0.017
237001AB1-127_GEN
Solar/Wind Helper
0.308
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
23777901MDS_W4-102
Solar/Wind Helper
0.106
203975AE1-071-GEN
Solar/Wind Helper
1.719
233918AB1-142 GEN
Solar/Wind Helper
0.305
233944AB2-135 GEN
Solar/Wind Helper
0.357
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.01
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
3150021OMF B
50/50
0.213
3150101POSSM6S
50/50
1.293
3150081POSSM6A
50/50
0.849
3150151POSSMC1
50/50
1.141
3150151POSSMC1
50/50
1.141
3150231REMNGT3
50/50
0.781
3150241REMNGT4
50/50
13.296
972199AH1-684 GEN
50/50
2.016
972217AH1-693 GEN
50/50
1.753
963691AG1-221 GEN
Solar/Wind Harmer
2.31
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3141196NOKESVL
Solar/Wind Harmer
0.428
3150301M RUN C
Adder
13.329
3150291M RUN B
Adder
13.23
3150331BIRCHWDA
Adder
16.601
3150401LDYSMT4
Adder
12.659
3150371LDYSMT1
Adder
12.232
316223AC1-118
Solar/Wind Harmer
0.064
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.117
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.883
3151761LOISA E
Adder
11.397
3151721LOISA A
Adder
5.561
316473AC1-191 GEN
Solar/Wind Harmer
0.29
3142416OLDCHRC
Solar/Wind Harmer
0.82
3141766HARMONY
Solar/Wind Harmer
1.127
3141873WAN 176
Solar/Wind Harmer
1.502
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.431
970293AG2-193 GEN
Solar/Wind Harmer
0.898
316075AC2-137 C
Solar/Wind Harmer
0.022
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
970133AG2-095 GEN
Solar/Wind Harmer
0.793
316458AB2-190 GEN2
Solar/Wind Harmer
0.439
3150921YORKTN3
Adder
2.065
315778AD1-151 GEN
Solar/Wind Harmer
6.568
3144216WINCHST
Adder
0.309
961611AG1-000B GEN
Solar/Wind Harmer
2.178
3151171GRAVELC
Adder
1.14
315813AE1-149 C
Solar/Wind Harmer
4.327
3145336SMITFLD
Solar/Wind Harmer
0.032
3144536CHRHLND
Solar/Wind Harmer
0.012
970657AG2-426 GEN
Solar/Wind Harmer
1.809
3151101ELIZAR3
Adder
7.476
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.116
944601AF1-125 GEN
Solar/Wind Harmer
17.837
316017AA1-139 ULT1
Solar/Wind Harmer
0.043
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.924
316246AF1-032 C
Solar/Wind Harmer
0.036
3143336POWHATN
Solar/Wind Harmer
1.198
316321Z2-027
Solar/Wind Harmer
0.014
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.078
3145273HOLLAND
Solar/Wind Harmer
0.059
944011AF1-069 GEN
Solar/Wind Harmer
4.7
3146376EDENTON
Solar/Wind Harmer
0.077
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.215
3146206CASHIE
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.668
3146173TUNIS
Solar/Wind Harmer
0.075
3146263WOODLND
Solar/Wind Harmer
0.074
316181AB2-040 GEN
Solar/Wind Harmer
0.105
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3145963POPLR C
Solar/Wind Harmer
0.073
316011AB1-132 GEN
Solar/Wind Harmer
1.331
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
972003AH1-546 GEN
Solar/Wind Harmer
2.538
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.251
3147133PAMPLIN
Solar/Wind Harmer
0.226
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.37
972255AH1-712 GEN
Adder
36.701
3145933PARMELE
Solar/Wind Harmer
0.072
959311AF2-222 GEN
Solar/Wind Harmer
6.364
970257AG2-171 GEN
Solar/Wind Harmer
2.288
971775AH1-396 GEN
Solar/Wind Harmer
0.114
970221AG2-151 GEN
Solar/Wind Harmer
3.81
964241AG1-285 GEN
Solar/Wind Harmer
4.743
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
2.442
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
315821AE2-092 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
4.902
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
971623AH1-311 GEN
Solar/Wind Harmer
0.138
270494AE1-108_GEN
Solar/Wind Harmer
0.797
3148013FISHERV
Solar/Wind Harmer
0.065
971683AH1-343 GEN
Solar/Wind Harmer
2.374
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316283AC2-100 C
Solar/Wind Harmer
0.124
316123AC1-075 GEN
Solar/Wind Harmer
0.082
3151861LOWMORA
Adder
0.644
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
237038AE2-054 C
Solar/Wind Helper
0.174
235067AD1-061 GEN
Solar/Wind Helper
0.282
237085AD2-009_GEN
Solar/Wind Helper
0.975
233935AB2-179 C
Solar/Wind Helper
0.775
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
232406W1-004 FULL
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.181
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
207442AE1-156 GEN
Solar/Wind Helper
0.189
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.297
3145783HORNRTN
Solar/Wind Harmer
1.037
3145783HORNRTN
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.218
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.172
972193AH1-681 GEN
Adder
1.64
3145933PARMELE
Solar/Wind Harmer
0.143
3145933PARMELE
Solar/Wind Harmer
0.072
970323AG2-213 GEN
Solar/Wind Harmer
3.051
316005AA1-067
Solar/Wind Harmer
0.076
315724AD1-057 GEN
Solar/Wind Harmer
1.362
3145493TOT1
Solar/Wind Harmer
0.161
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
962561AG1-105 GEN
Solar/Wind Harmer
3.315
961601AG1-000A GEN
Solar/Wind Harmer
1.225
316049AB1-081 GEN
Solar/Wind Harmer
0.392
316263AC1-034 GEN
Solar/Wind Harmer
2.619
964791AG1-342 GEN
Solar/Wind Harmer
1.319
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316118AC1-105 GEN
Solar/Wind Harmer
0.174
971761AH1-387 GEN
Solar/Wind Harmer
1.229
942751AE2-291 GEN
Solar/Wind Harmer
3.269
3132123MT JACKSON
Solar/Wind Harmer
0.182
970117AG2-086 GEN
Solar/Wind Harmer
1.398
970117AG2-086 GEN
Solar/Wind Harmer
0.932
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
237080AD1-060 GEN
Solar/Wind Helper
0.222
235062AE1-101 C1
Solar/Wind Helper
1.069
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.343
233994AC2-023 GEN
Solar/Wind Helper
0.579
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207459AE1-142 C O1
Solar/Wind Helper
0.17
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.241
209027LOR2_Q27
Solar/Wind Helper
0.559
212266LOR1
Solar/Wind Helper
0.163
209029WAYMART-WD
Solar/Wind Helper
0.444
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.467
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
20676728BRNX1-095
Solar/Wind Helper
0.017
207484AF2-139 C O1
Solar/Wind Helper
0.048
207530AG1-191 GEN
Solar/Wind Helper
0.038
20674928WA_W3-044
Solar/Wind Helper
0.057
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.902
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
946731AF1-337 GEN
Solar/Wind Helper
0.234
209137AF2-361 C
Solar/Wind Helper
0.711
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
1.008
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.237
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
209071AE2-133 GEN
Solar/Wind Helper
0.042
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.237
946751AF1-339 GEN
Solar/Wind Helper
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.532
TVALTFEXP_TVA->PJM
CLTF
3.177
CPLELTFEXP_CPLE->PJM
CLTF
5.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.822
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.552
MECLTFEXP_MEC->PJM
CLTF
4.431
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
2.582
LGEELTFEXP_LGEE->PJM
CLTF
1.798
WECLTFEXP_WEC->PJM
CLTF
0.958

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T560_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.27 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1994.82
MW Contribution:
3.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.025
3138216PACIFIC
Solar/Wind Harmer
-0.003
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.712
3150381LDYSMT2
Adder
12.166
972213AH1-691 GEN
Adder
2.058
972215AH1-692 GEN
Adder
2.058
315651AD1-115 GEN
Solar/Wind Harmer
4.651
316164AC1-076 GEN
Solar/Wind Harmer
0.884
944491AF1-114 GEN
Solar/Wind Harmer
3.046
316468AD1-105 GEN
Solar/Wind Harmer
1.148
3141813NORNECK
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3147346CASHSCORNER
Solar/Wind Harmer
0.147
957601AF2-054 GEN
Solar/Wind Harmer
0.284
316059AD1-063 C
Solar/Wind Harmer
0.214
3141873WAN 176
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.526
971283AH1-107 GEN
Solar/Wind Harmer
1.526
971285AH1-108 GEN
Adder
0.63
957831AF2-077 GEN
Solar/Wind Harmer
0.281
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316382AG1-145 C
Solar/Wind Harmer
0.28
316159AE1-175 C
Solar/Wind Harmer
0.249
315697AD1-025 GEN
Solar/Wind Harmer
1.859
315839AE2-212 C
Solar/Wind Harmer
0.277
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151191GRAVEL3
Adder
5.855
3151211GRAVEL5
Adder
5.855
971445AH1-216 GEN
Solar/Wind Harmer
5.641
316236AE1-162_GEN
Solar/Wind Harmer
0.274
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.571
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
1.708
316311AC2-079 GEN
Solar/Wind Harmer
4.537
316018AA1-139 ULT2
Solar/Wind Harmer
0.768
957871AF2-081 GEN
Solar/Wind Harmer
4.495
3146406KITTY HAWK
Solar/Wind Harmer
0.007
313526AB2-022
Solar/Wind Harmer
0.24
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316258AE1-075 C
Solar/Wind Harmer
0.216
316405AF2-144 C
Solar/Wind Harmer
0.228
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.19
970533AG2-339 GEN
Solar/Wind Harmer
5.901
315800Z1-036_GEN1
Solar/Wind Harmer
2.158
970673AG2-436 GEN
Solar/Wind Harmer
19.089
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
971967AH1-528 GEN
Solar/Wind Harmer
16.231
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.714
315733AD1-074 GEN2
Solar/Wind Harmer
1.714
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.694
316318V4-068
Solar/Wind Harmer
0.21
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.23
970581AG2-369 GEN
Solar/Wind Harmer
4.498
316463AE2-346 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.278
316426AA2-053 GEN
Solar/Wind Harmer
0.83
972205AH1-687 GEN
Adder
3.127
316322AB2-045
Solar/Wind Harmer
0.276
971845AH1-439 GEN
Solar/Wind Harmer
4.369
316174AB2-169 GEN
Solar/Wind Harmer
1.265
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.206
3146033SCOT NK
Solar/Wind Harmer
-0.032
946301AF1-294 GEN
Solar/Wind Harmer
2.073
961791AG1-021 GEN
Solar/Wind Harmer
1.011
316210AC1-098 GEN
Solar/Wind Harmer
1.264
970683AG2-441 GEN
Solar/Wind Harmer
5.694
970681AG2-440 GEN
Solar/Wind Harmer
3.78
970831AG2-522 GEN
Solar/Wind Harmer
4.03
316274AC1-208 GEN
Solar/Wind Harmer
0.865
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
3152111X4-039 GT1
50/50
1.844
315747AE2-019 GEN
50/50
13.164
963691AG1-221 GEN
Solar/Wind Harmer
2.31
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3150151POSSMC1
Adder
1.083
3150151POSSMC1
Adder
1.083
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150241REMNGT4
Adder
12.527
972199AH1-684 GEN
Adder
1.899
972217AH1-693 GEN
Adder
1.652
3150301M RUN C
Adder
13.326
3150291M RUN B
Adder
13.227
3150331BIRCHWDA
Adder
16.668
3150401LDYSMT4
Adder
12.673
3150371LDYSMT1
Adder
12.245
966881AG1-559 GEN
Solar/Wind Harmer
0.308
316223AC1-118
Solar/Wind Harmer
0.271
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.619
3147666LOUISA
Solar/Wind Harmer
-0.023
316077AC2-138 C
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
0.884
3151761LOISA E
Adder
11.393
3151721LOISA A
Adder
5.56
316484AD2-074 GEN
Solar/Wind Harmer
2.432
961951AG1-038 GEN
Solar/Wind Harmer
1.273
316473AC1-191 GEN
Solar/Wind Harmer
1.038
3142416OLDCHRC
Solar/Wind Harmer
0.959
3141873WAN 176
Solar/Wind Harmer
1.127
3141766HARMONY
Solar/Wind Harmer
0.845
316203AE2-005 GEN
Solar/Wind Harmer
4.002
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.182
316075AC2-137 C
Solar/Wind Harmer
0.254
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
970133AG2-095 GEN
Solar/Wind Harmer
1.044
316458AB2-190 GEN2
Solar/Wind Harmer
0.932
3150921YORKTN3
Adder
2.065
315778AD1-151 GEN
Solar/Wind Harmer
8.21
3144216WINCHST
Adder
0.309
961611AG1-000B GEN
Solar/Wind Harmer
1.932
3151171GRAVELC
Adder
1.14
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.697
3144536CHRHLND
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
1.83
3151101ELIZAR3
Adder
7.475
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.122
944601AF1-125 GEN
Solar/Wind Harmer
40.48
3142956BIRDNECK
Solar/Wind Harmer
0.485
316017AA1-139 ULT1
Solar/Wind Harmer
0.725
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.039
316305AF2-043 C
Solar/Wind Harmer
0.27
316246AF1-032 C
Solar/Wind Harmer
0.181
316320Y1-086
Solar/Wind Harmer
0.522
3143336POWHATN
Solar/Wind Harmer
0.898
316321Z2-027
Solar/Wind Harmer
0.239
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.155
3146376EDENTON
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.758
315735AD1-075 GEN1
Solar/Wind Harmer
0.857
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.069
3146173TUNIS
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.169
3146263WOODLND
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.154
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.722
316190AA2-174 GEN
Solar/Wind Harmer
0.101
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.005
972003AH1-546 GEN
Solar/Wind Harmer
3.341
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.227
316478AD1-087 GEN
Solar/Wind Harmer
0.704
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.702
3145933PARMELE
Solar/Wind Harmer
-0.008
972255AH1-712 GEN
Adder
36.692
959311AF2-222 GEN
Solar/Wind Harmer
8.394
970257AG2-171 GEN
Solar/Wind Harmer
3.013
971775AH1-396 GEN
Solar/Wind Harmer
0.567
3151861LOWMORA
Adder
0.643
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
237038AE2-054 C
Solar/Wind Helper
0.174
316411AF1-147_GEN1
Solar/Wind Harmer
1.097
3150071POSSM 5
Adder
49.515
3150181POSSMC2
Adder
1.092
3150181POSSMC2
Adder
1.083
3150181POSSMC2
Adder
1.083
316006AB2-029 C
Solar/Wind Harmer
0.629
316045AC1-158 PL2
Solar/Wind Harmer
3.324
316450AC1-158 RIC
Solar/Wind Harmer
0.277
3150391LDYSMT3
Adder
12.649
972195AH1-682 GEN
Adder
1.662
315673AE1-157 GEN
Solar/Wind Harmer
7.788
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3151731LOISA B
Adder
5.589
316487AF1-042 GEN
Solar/Wind Harmer
1.273
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316312AB1-027
Solar/Wind Harmer
0.32
316156AD2-030 GEN
Solar/Wind Harmer
0.253
315666AE1-190 GEN
Solar/Wind Harmer
0.285
316441AF1-014 GEN
Solar/Wind Harmer
0.64
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
3150681DARBY 2
Adder
6.038
3150671DARBY 1
Adder
6.031
315976AC1-164 GENA
Solar/Wind Harmer
2.145
316169AC1-164_GENC
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.17
944641AF1-129 GEN
Adder
39.347
316240AF1-291 C
Solar/Wind Harmer
0.278
316033AB2-134 GEN
Solar/Wind Harmer
2.966
316294AC1-161 GEN
Solar/Wind Harmer
2.936
316083AB2-161 GEN
Solar/Wind Harmer
1.471
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
316185AD1-033 GEN
Solar/Wind Harmer
0.95
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316349AD2-085 GEN
Solar/Wind Harmer
0.799
316339AD2-160 GEN
Solar/Wind Harmer
0.605
316388AE2-253 GEN
Solar/Wind Harmer
0.605
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.06
3130086AYDLETT
Solar/Wind Harmer
-0.036
315835AF2-110_GEN
Solar/Wind Harmer
1.119
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316313AB2-026
Solar/Wind Harmer
0.24
316431W1029_GEN1
Solar/Wind Harmer
1.606
316433W1029_GEN2
Solar/Wind Harmer
1.606
316435W1029_GEN3
Solar/Wind Harmer
1.606
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.237
316336AC2-165 C
Solar/Wind Harmer
5.487
315742AE1-103 GEN
Solar/Wind Harmer
2.076
3146376EDENTON
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.258
972185AH1-677 GEN
Adder
4.322
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.925
970933AG2-581 GEN
Solar/Wind Harmer
8.024
316065AD1-022 GEN
Solar/Wind Harmer
4.231
316365GEN2_N
Solar/Wind Harmer
0.568
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.056
970099AG2-077 GEN
Solar/Wind Harmer
10.391
313506AB2-031 GEN
Solar/Wind Harmer
0.664
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.124
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.778
3145783HORNRTN
Solar/Wind Harmer
0.243
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.264
3144293JTRSVLE
Adder
0.172
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
972193AH1-681 GEN
Adder
1.639
970323AG2-213 GEN
Solar/Wind Harmer
4.017
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
223402AF1-300 C
Solar/Wind Helper
0.398
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
316415AF1-147_GEN2
Solar/Wind Harmer
1.097
972223AH1-696 GEN
Adder
8.557
3150151POSSMC1
Adder
1.083
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.445
3150211REMNGT1
Adder
12.362
972201AH1-685 GEN
Adder
2.147
3150281M RUN A
Adder
13.334
971685AH1-345 GEN
Solar/Wind Harmer
0.96
316447AC1-158 HLD
Solar/Wind Harmer
2.285
316044AC1-158 PL1
Solar/Wind Harmer
1.039
972197AH1-683 GEN
Adder
1.979
972219AH1-694 GEN
Adder
1.425
316254AC1-120 GEN1
Solar/Wind Harmer
3.939
316170AC1-121 GEN2
Solar/Wind Harmer
1.313
957971AF2-091 GEN
Solar/Wind Harmer
1.036
972135AH1-637 GEN
Solar/Wind Harmer
1.029
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
9.488
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.18
316337AD2-073 GEN
Solar/Wind Harmer
0.266
3150351NORNECKC2
Adder
0.869
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
316404AE1-155 C
Solar/Wind Harmer
1.854
958261AF2-120 GEN
Solar/Wind Harmer
3.763
962861AG1-135 GEN
Solar/Wind Harmer
3.636
3151751LOISA D
Adder
5.589
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.812
3141766HARMONY
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.142
316280AD1-041 GEN
Solar/Wind Harmer
0.714
971777AH1-397 GEN
Solar/Wind Harmer
1.108
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.787
3143226MDLTHAN
Solar/Wind Harmer
-0.009
971317AH1-138 GEN
Solar/Wind Harmer
1.161
316132AB2-190 GEN1
Solar/Wind Harmer
0.932
315671AE2-027_GEN
Solar/Wind Harmer
1.668
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.46
316369SG1_INVT
Solar/Wind Harmer
1.642
961611AG1-000B GEN
Solar/Wind Harmer
4.528
3151171GRAVELC
Adder
0.867
3145336SMITFLD
Solar/Wind Harmer
-0.036
315773AC2-141 GEN
Solar/Wind Harmer
3.799
316381AD1-082 GEN
Solar/Wind Harmer
0.829
316375AC2-012 GEN
Solar/Wind Harmer
3.128
316036AC1-147 C
Solar/Wind Harmer
0.243
3150981CHESPKA
Adder
1.005
944591AF1-124 GEN
Solar/Wind Harmer
41.27
316072AD1-144
Solar/Wind Harmer
0.182
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.9
319010AE1-072 C
Solar/Wind Harmer
1.811
940641AE2-051 GEN
Solar/Wind Harmer
8.405
316093AE2-104_GEN
Solar/Wind Harmer
2.602
3143336POWHATN
Solar/Wind Harmer
1.057
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
941031AE2-094 GEN
Solar/Wind Harmer
16.452
315611Z1-036_GEN2
Solar/Wind Harmer
2.158
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.694
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.061
315737AD1-076 GEN
Solar/Wind Harmer
1.612
970937AG2-583 GEN
Solar/Wind Harmer
6.097
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.111
316023GEN1_S
Solar/Wind Harmer
0.568
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.25
970919AG2-571 GEN
Solar/Wind Harmer
2.667
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.125
970087AG2-069 GEN
Solar/Wind Harmer
7.846
960081AF2-299 GEN
Solar/Wind Harmer
0.938
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.839
957481AF2-042 GEN
Solar/Wind Harmer
25.978
3146263WOODLND
Solar/Wind Harmer
-0.008
316087AB2-174 GEN
Solar/Wind Harmer
1.182
315693AD1-088 GEN
Solar/Wind Harmer
4.141
3145963POPLR C
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.662
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
971563AH1-280 GEN
Solar/Wind Harmer
1.011
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
970685AG2-442 GEN
Solar/Wind Harmer
7.066
972277AH1-723 GEN
Adder
42.757
3146293MARTNCO
Solar/Wind Harmer
0.05
316129AC1-054 GEN
Solar/Wind Harmer
0.703
316034AC1-036 C
Solar/Wind Harmer
0.149
205916AD1-020 GEN
Solar/Wind Helper
1.485
208835TUHI V3-051
Solar/Wind Helper
0.017
237001AB1-127_GEN
Solar/Wind Helper
0.308
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
23777901MDS_W4-102
Solar/Wind Helper
0.106
203975AE1-071-GEN
Solar/Wind Helper
1.719
233918AB1-142 GEN
Solar/Wind Helper
0.305
233944AB2-135 GEN
Solar/Wind Helper
0.357
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.01
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.017
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20674928WA_W3-044
Solar/Wind Helper
0.057
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.902
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
946731AF1-337 GEN
Solar/Wind Helper
0.234
209137AF2-361 C
Solar/Wind Helper
0.711
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205943AE1-185 GEN
Solar/Wind Helper
0.388
205956AE1-196_GEN
Solar/Wind Helper
0.386
959381AF2-229 GEN
Solar/Wind Helper
0.257
20390526W1-045 C
Solar/Wind Helper
0.253
233915AB1-141 GEN
Solar/Wind Helper
0.305
233901CHERRYDALE C
Solar/Wind Helper
0.14
233940AF2-379 C
Solar/Wind Helper
0.037
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
228728W1-130C
Solar/Wind Helper
0.032
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.034
20720728JCB_W1-129
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
20673828FLE_V3-070
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.056
20676428JCR_X2-075
Solar/Wind Helper
0.039
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.241
209027LOR2_Q27
Solar/Wind Helper
0.559
212266LOR1
Solar/Wind Helper
0.163
209029WAYMART-WD
Solar/Wind Helper
0.444
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.467
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
235067AD1-061 GEN
Solar/Wind Helper
0.282
237085AD2-009_GEN
Solar/Wind Helper
0.975
233935AB2-179 C
Solar/Wind Helper
0.775
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
232406W1-004 FULL
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.181
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
207442AE1-156 GEN
Solar/Wind Helper
0.189
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
1.008
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.237
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
209071AE2-133 GEN
Solar/Wind Helper
0.042
970221AG2-151 GEN
Solar/Wind Harmer
1.345
238221AF1-254 C O1
Solar/Wind Helper
0.18
237080AD1-060 GEN
Solar/Wind Helper
0.222
235062AE1-101 C1
Solar/Wind Helper
1.069
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.343
233994AC2-023 GEN
Solar/Wind Helper
0.579
232428Y3-058 C
Solar/Wind Helper
0.204
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
234015AF2-250 C
Solar/Wind Helper
0.023
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207459AE1-142 C O1
Solar/Wind Helper
0.17
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.237
946751AF1-339 GEN
Solar/Wind Helper
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
6.302
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.53
TVALTFEXP_TVA->PJM
CLTF
3.176
CPLELTFEXP_CPLE->PJM
CLTF
5.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.815
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.55
MECLTFEXP_MEC->PJM
CLTF
4.43
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
2.582
LGEELTFEXP_LGEE->PJM
CLTF
1.797
WECLTFEXP_WEC->PJM
CLTF
0.958

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T560_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.27 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1994.74
MW Contribution:
3.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.025
3138216PACIFIC
Solar/Wind Harmer
-0.003
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.714
3150381LDYSMT2
Adder
12.168
972213AH1-691 GEN
Adder
2.058
972215AH1-692 GEN
Adder
2.058
315651AD1-115 GEN
Solar/Wind Harmer
4.651
316164AC1-076 GEN
Solar/Wind Harmer
0.884
944491AF1-114 GEN
Solar/Wind Harmer
3.046
316468AD1-105 GEN
Solar/Wind Harmer
1.148
3141813NORNECK
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3147346CASHSCORNER
Solar/Wind Harmer
0.147
316059AD1-063 C
Solar/Wind Harmer
0.214
957601AF2-054 GEN
Solar/Wind Harmer
0.284
3141873WAN 176
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.526
971283AH1-107 GEN
Solar/Wind Harmer
1.526
971285AH1-108 GEN
Adder
0.63
957831AF2-077 GEN
Solar/Wind Harmer
0.281
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316382AG1-145 C
Solar/Wind Harmer
0.28
316159AE1-175 C
Solar/Wind Harmer
0.249
315697AD1-025 GEN
Solar/Wind Harmer
1.859
315839AE2-212 C
Solar/Wind Harmer
0.277
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151191GRAVEL3
Adder
5.855
3151211GRAVEL5
Adder
5.855
971445AH1-216 GEN
Solar/Wind Harmer
5.641
316236AE1-162_GEN
Solar/Wind Harmer
0.274
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.571
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
1.708
316311AC2-079 GEN
Solar/Wind Harmer
4.537
316018AA1-139 ULT2
Solar/Wind Harmer
0.768
957871AF2-081 GEN
Solar/Wind Harmer
4.495
3146406KITTY HAWK
Solar/Wind Harmer
0.007
313526AB2-022
Solar/Wind Harmer
0.24
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316258AE1-075 C
Solar/Wind Harmer
0.216
316405AF2-144 C
Solar/Wind Harmer
0.228
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.19
970533AG2-339 GEN
Solar/Wind Harmer
5.901
315800Z1-036_GEN1
Solar/Wind Harmer
2.158
970673AG2-436 GEN
Solar/Wind Harmer
19.089
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
971967AH1-528 GEN
Solar/Wind Harmer
16.231
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.714
315733AD1-074 GEN2
Solar/Wind Harmer
1.714
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.694
316318V4-068
Solar/Wind Harmer
0.21
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.23
970581AG2-369 GEN
Solar/Wind Harmer
4.498
316463AE2-346 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.278
316426AA2-053 GEN
Solar/Wind Harmer
0.83
972205AH1-687 GEN
Adder
3.127
316322AB2-045
Solar/Wind Harmer
0.276
971845AH1-439 GEN
Solar/Wind Harmer
4.369
316174AB2-169 GEN
Solar/Wind Harmer
1.265
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.206
3146033SCOT NK
Solar/Wind Harmer
-0.032
946301AF1-294 GEN
Solar/Wind Harmer
2.073
961791AG1-021 GEN
Solar/Wind Harmer
1.011
316210AC1-098 GEN
Solar/Wind Harmer
1.264
970683AG2-441 GEN
Solar/Wind Harmer
5.694
970681AG2-440 GEN
Solar/Wind Harmer
3.779
970831AG2-522 GEN
Solar/Wind Harmer
4.03
316274AC1-208 GEN
Solar/Wind Harmer
0.865
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205943AE1-185 GEN
Solar/Wind Helper
0.388
205956AE1-196_GEN
Solar/Wind Helper
0.386
959381AF2-229 GEN
Solar/Wind Helper
0.257
20390526W1-045 C
Solar/Wind Helper
0.253
233915AB1-141 GEN
Solar/Wind Helper
0.305
233901CHERRYDALE C
Solar/Wind Helper
0.14
233940AF2-379 C
Solar/Wind Helper
0.037
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
228728W1-130C
Solar/Wind Helper
0.032
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.034
20720728JCB_W1-129
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
20673828FLE_V3-070
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.056
20676428JCR_X2-075
Solar/Wind Helper
0.039
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.241
209027LOR2_Q27
Solar/Wind Helper
0.559
212266LOR1
Solar/Wind Helper
0.163
209029WAYMART-WD
Solar/Wind Helper
0.444
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.467
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
3152111X4-039 GT1
50/50
1.844
315747AE2-019 GEN
50/50
13.164
963691AG1-221 GEN
Solar/Wind Harmer
2.31
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3150151POSSMC1
Adder
1.084
3150151POSSMC1
Adder
1.084
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150241REMNGT4
Adder
12.527
972199AH1-684 GEN
Adder
1.899
972217AH1-693 GEN
Adder
1.652
3150331BIRCHWDA
Adder
16.674
3150301M RUN C
Adder
13.326
3150291M RUN B
Adder
13.227
3150401LDYSMT4
Adder
12.674
3150371LDYSMT1
Adder
12.247
966881AG1-559 GEN
Solar/Wind Harmer
0.308
316223AC1-118
Solar/Wind Harmer
0.271
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.619
3147666LOUISA
Solar/Wind Harmer
-0.023
316077AC2-138 C
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
0.884
3151761LOISA E
Adder
11.393
3151721LOISA A
Adder
5.56
316484AD2-074 GEN
Solar/Wind Harmer
2.432
961951AG1-038 GEN
Solar/Wind Harmer
1.273
316473AC1-191 GEN
Solar/Wind Harmer
1.038
3142416OLDCHRC
Solar/Wind Harmer
0.959
3141766HARMONY
Solar/Wind Harmer
0.845
3141873WAN 176
Solar/Wind Harmer
1.127
316203AE2-005 GEN
Solar/Wind Harmer
4.002
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.182
316075AC2-137 C
Solar/Wind Harmer
0.254
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
970133AG2-095 GEN
Solar/Wind Harmer
1.044
316458AB2-190 GEN2
Solar/Wind Harmer
0.932
3150921YORKTN3
Adder
2.065
315778AD1-151 GEN
Solar/Wind Harmer
8.21
3144216WINCHST
Adder
0.309
961611AG1-000B GEN
Solar/Wind Harmer
1.932
3151171GRAVELC
Adder
1.14
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.697
3144536CHRHLND
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
1.83
3151101ELIZAR3
Adder
7.475
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.121
944601AF1-125 GEN
Solar/Wind Harmer
40.48
3142956BIRDNECK
Solar/Wind Harmer
0.485
316017AA1-139 ULT1
Solar/Wind Harmer
0.725
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.039
316305AF2-043 C
Solar/Wind Harmer
0.27
316246AF1-032 C
Solar/Wind Harmer
0.181
316320Y1-086
Solar/Wind Harmer
0.522
3143336POWHATN
Solar/Wind Harmer
0.898
316321Z2-027
Solar/Wind Harmer
0.239
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.155
3146376EDENTON
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.758
315735AD1-075 GEN1
Solar/Wind Harmer
0.857
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.069
3146173TUNIS
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.169
3146263WOODLND
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.154
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.722
316190AA2-174 GEN
Solar/Wind Harmer
0.101
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.005
972003AH1-546 GEN
Solar/Wind Harmer
3.341
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.227
316478AD1-087 GEN
Solar/Wind Harmer
0.704
316411AF1-147_GEN1
Solar/Wind Harmer
1.097
3150071POSSM 5
Adder
49.547
3150181POSSMC2
Adder
1.093
3150181POSSMC2
Adder
1.084
3150181POSSMC2
Adder
1.084
316006AB2-029 C
Solar/Wind Harmer
0.629
3150391LDYSMT3
Adder
12.65
972195AH1-682 GEN
Adder
1.662
316045AC1-158 PL2
Solar/Wind Harmer
3.324
316450AC1-158 RIC
Solar/Wind Harmer
0.277
315673AE1-157 GEN
Solar/Wind Harmer
7.788
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3151731LOISA B
Adder
5.588
316487AF1-042 GEN
Solar/Wind Harmer
1.273
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316312AB1-027
Solar/Wind Harmer
0.32
316156AD2-030 GEN
Solar/Wind Harmer
0.253
315666AE1-190 GEN
Solar/Wind Harmer
0.285
316441AF1-014 GEN
Solar/Wind Harmer
0.64
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
3150681DARBY 2
Adder
6.038
3150671DARBY 1
Adder
6.031
315976AC1-164 GENA
Solar/Wind Harmer
2.145
316169AC1-164_GENC
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.17
944641AF1-129 GEN
Adder
39.347
316240AF1-291 C
Solar/Wind Harmer
0.278
316033AB2-134 GEN
Solar/Wind Harmer
2.966
316294AC1-161 GEN
Solar/Wind Harmer
2.936
316083AB2-161 GEN
Solar/Wind Harmer
1.471
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
316185AD1-033 GEN
Solar/Wind Harmer
0.95
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316349AD2-085 GEN
Solar/Wind Harmer
0.799
316339AD2-160 GEN
Solar/Wind Harmer
0.605
316388AE2-253 GEN
Solar/Wind Harmer
0.605
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.06
3130086AYDLETT
Solar/Wind Harmer
-0.036
315835AF2-110_GEN
Solar/Wind Harmer
1.119
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316313AB2-026
Solar/Wind Harmer
0.24
316431W1029_GEN1
Solar/Wind Harmer
1.606
316433W1029_GEN2
Solar/Wind Harmer
1.606
316435W1029_GEN3
Solar/Wind Harmer
1.606
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.237
316336AC2-165 C
Solar/Wind Harmer
5.487
315742AE1-103 GEN
Solar/Wind Harmer
2.076
3146376EDENTON
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.258
972185AH1-677 GEN
Adder
4.322
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.925
970933AG2-581 GEN
Solar/Wind Harmer
8.024
316065AD1-022 GEN
Solar/Wind Harmer
4.231
316365GEN2_N
Solar/Wind Harmer
0.568
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.056
970099AG2-077 GEN
Solar/Wind Harmer
10.391
313506AB2-031 GEN
Solar/Wind Harmer
0.664
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.124
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.778
3145783HORNRTN
Solar/Wind Harmer
0.243
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.264
3144293JTRSVLE
Adder
0.172
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
972193AH1-681 GEN
Adder
1.639
970323AG2-213 GEN
Solar/Wind Harmer
4.017
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
237080AD1-060 GEN
Solar/Wind Helper
0.222
235062AE1-101 C1
Solar/Wind Helper
1.069
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.343
233994AC2-023 GEN
Solar/Wind Helper
0.579
232428Y3-058 C
Solar/Wind Helper
0.204
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
234015AF2-250 C
Solar/Wind Helper
0.023
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207459AE1-142 C O1
Solar/Wind Helper
0.17
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.237
946751AF1-339 GEN
Solar/Wind Helper
0.234
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.702
3145933PARMELE
Solar/Wind Harmer
-0.008
972255AH1-712 GEN
Adder
36.691
959311AF2-222 GEN
Solar/Wind Harmer
8.394
970257AG2-171 GEN
Solar/Wind Harmer
3.013
971775AH1-396 GEN
Solar/Wind Harmer
0.567
3151861LOWMORA
Adder
0.643
226910AB2-157 C
Solar/Wind Helper
0.021
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
237038AE2-054 C
Solar/Wind Helper
0.174
235067AD1-061 GEN
Solar/Wind Helper
0.282
237085AD2-009_GEN
Solar/Wind Helper
0.975
233935AB2-179 C
Solar/Wind Helper
0.775
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
232406W1-004 FULL
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.181
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
207442AE1-156 GEN
Solar/Wind Helper
0.189
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
1.008
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.237
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
209071AE2-133 GEN
Solar/Wind Helper
0.042
970221AG2-151 GEN
Solar/Wind Harmer
1.345
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
316415AF1-147_GEN2
Solar/Wind Harmer
1.097
972223AH1-696 GEN
Adder
8.563
3150151POSSMC1
Adder
1.084
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.445
3150211REMNGT1
Adder
12.362
972201AH1-685 GEN
Adder
2.147
3150281M RUN A
Adder
13.334
971685AH1-345 GEN
Solar/Wind Harmer
0.96
972197AH1-683 GEN
Adder
1.979
972219AH1-694 GEN
Adder
1.425
316447AC1-158 HLD
Solar/Wind Harmer
2.285
316044AC1-158 PL1
Solar/Wind Harmer
1.039
316254AC1-120 GEN1
Solar/Wind Harmer
3.939
316170AC1-121 GEN2
Solar/Wind Harmer
1.313
957971AF2-091 GEN
Solar/Wind Harmer
1.036
972135AH1-637 GEN
Solar/Wind Harmer
1.029
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
9.487
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.18
316337AD2-073 GEN
Solar/Wind Harmer
0.266
3150351NORNECKC2
Adder
0.869
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
316404AE1-155 C
Solar/Wind Harmer
1.854
958261AF2-120 GEN
Solar/Wind Harmer
3.763
962861AG1-135 GEN
Solar/Wind Harmer
3.637
3151751LOISA D
Adder
5.588
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.812
3141766HARMONY
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.142
316280AD1-041 GEN
Solar/Wind Harmer
0.714
971777AH1-397 GEN
Solar/Wind Harmer
1.108
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.787
3143226MDLTHAN
Solar/Wind Harmer
-0.009
971317AH1-138 GEN
Solar/Wind Harmer
1.161
316132AB2-190 GEN1
Solar/Wind Harmer
0.932
315671AE2-027_GEN
Solar/Wind Harmer
1.668
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.46
316369SG1_INVT
Solar/Wind Harmer
1.642
961611AG1-000B GEN
Solar/Wind Harmer
4.528
3151171GRAVELC
Adder
0.867
3145336SMITFLD
Solar/Wind Harmer
-0.036
315773AC2-141 GEN
Solar/Wind Harmer
3.799
316381AD1-082 GEN
Solar/Wind Harmer
0.829
316375AC2-012 GEN
Solar/Wind Harmer
3.128
316036AC1-147 C
Solar/Wind Harmer
0.243
3150981CHESPKA
Adder
1.005
944591AF1-124 GEN
Solar/Wind Harmer
41.27
316072AD1-144
Solar/Wind Harmer
0.182
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.9
319010AE1-072 C
Solar/Wind Harmer
1.811
940641AE2-051 GEN
Solar/Wind Harmer
8.405
316093AE2-104_GEN
Solar/Wind Harmer
2.602
3143336POWHATN
Solar/Wind Harmer
1.057
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
941031AE2-094 GEN
Solar/Wind Harmer
16.452
315611Z1-036_GEN2
Solar/Wind Harmer
2.158
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.694
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.061
315737AD1-076 GEN
Solar/Wind Harmer
1.612
970937AG2-583 GEN
Solar/Wind Harmer
6.097
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.111
316023GEN1_S
Solar/Wind Harmer
0.568
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.25
970919AG2-571 GEN
Solar/Wind Harmer
2.667
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.125
970087AG2-069 GEN
Solar/Wind Harmer
7.846
960081AF2-299 GEN
Solar/Wind Harmer
0.938
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.839
957481AF2-042 GEN
Solar/Wind Harmer
25.978
3146263WOODLND
Solar/Wind Harmer
-0.008
316087AB2-174 GEN
Solar/Wind Harmer
1.182
315693AD1-088 GEN
Solar/Wind Harmer
4.14
3145963POPLR C
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.662
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
971563AH1-280 GEN
Solar/Wind Harmer
1.011
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
970685AG2-442 GEN
Solar/Wind Harmer
7.066
972277AH1-723 GEN
Adder
42.756
3146293MARTNCO
Solar/Wind Harmer
0.05
316129AC1-054 GEN
Solar/Wind Harmer
0.703
316034AC1-036 C
Solar/Wind Harmer
0.149
205916AD1-020 GEN
Solar/Wind Helper
1.485
208835TUHI V3-051
Solar/Wind Helper
0.017
237001AB1-127_GEN
Solar/Wind Helper
0.308
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
23777901MDS_W4-102
Solar/Wind Helper
0.106
203975AE1-071-GEN
Solar/Wind Helper
1.719
233918AB1-142 GEN
Solar/Wind Helper
0.305
233944AB2-135 GEN
Solar/Wind Helper
0.357
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.01
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.017
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20674928WA_W3-044
Solar/Wind Helper
0.057
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.902
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
946731AF1-337 GEN
Solar/Wind Helper
0.234
209137AF2-361 C
Solar/Wind Helper
0.711
LAGNLTFEXP_LAGN->PJM
CLTF
6.301
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.53
TVALTFEXP_TVA->PJM
CLTF
3.176
CPLELTFEXP_CPLE->PJM
CLTF
5.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.815
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.321
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.549
MECLTFEXP_MEC->PJM
CLTF
4.43
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
2.582
LGEELTFEXP_LGEE->PJM
CLTF
1.797
WECLTFEXP_WEC->PJM
CLTF
0.958

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: 560T571_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 560T571_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.57 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1982.11
MW Contribution:
3.32
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152131X4-039 ST
50/50
2.888
3152121X4-039 GT2
50/50
1.835
316415AF1-147_GEN2
Solar/Wind Harmer
1.1
972223AH1-696 GEN
Adder
8.389
3150151POSSMC1
Adder
1.062
3141346CRANES
Adder
0.118
3150221REMNGT2
Adder
12.465
3150211REMNGT1
Adder
12.382
972201AH1-685 GEN
Adder
2.151
3150281M RUN A
Adder
13.356
971685AH1-345 GEN
Solar/Wind Harmer
0.961
316447AC1-158 HLD
Solar/Wind Harmer
2.28
316044AC1-158 PL1
Solar/Wind Harmer
1.037
972197AH1-683 GEN
Adder
1.958
972219AH1-694 GEN
Adder
1.41
316254AC1-120 GEN1
Solar/Wind Harmer
3.935
316170AC1-121 GEN2
Solar/Wind Harmer
1.312
957971AF2-091 GEN
Solar/Wind Harmer
1.023
315683AE1-153 C
Solar/Wind Harmer
9.479
972135AH1-637 GEN
Solar/Wind Harmer
1.017
966881AG1-559 GEN
Solar/Wind Harmer
0.104
3147666LOUISA
Solar/Wind Harmer
-0.039
316192AB2-158 GEN
Solar/Wind Harmer
1.176
316337AD2-073 GEN
Solar/Wind Harmer
0.263
3150351NORNECKC2
Adder
0.861
964211AG1-282 GEN
Solar/Wind Harmer
0.291
3141726DUNNSVL
Solar/Wind Harmer
-0.038
3151751LOISA D
Adder
5.574
316404AE1-155 C
Solar/Wind Harmer
1.836
958261AF2-120 GEN
Solar/Wind Harmer
3.727
962861AG1-135 GEN
Solar/Wind Harmer
3.603
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.024
3142416OLDCHRC
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.805
3141766HARMONY
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.132
316280AD1-041 GEN
Solar/Wind Harmer
0.708
971777AH1-397 GEN
Solar/Wind Harmer
1.099
3142433PROV 92
Solar/Wind Harmer
-0.037
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3143096IRON208
Adder
0.348
3143526WINTERP
Solar/Wind Harmer
-0.048
3142543TWELFTH
Solar/Wind Harmer
-0.001
970053AG2-049 GEN
50/50
2.017
3138216PACIFIC
Solar/Wind Harmer
-0.003
3141426STAFORD
Solar/Wind Harmer
-0.002
315651AD1-115 GEN
Solar/Wind Harmer
4.648
3150411LDYSMT5
Adder
12.576
3150381LDYSMT2
Adder
12.036
972213AH1-691 GEN
Adder
2.036
972215AH1-692 GEN
Adder
2.036
316164AC1-076 GEN
Solar/Wind Harmer
0.882
944491AF1-114 GEN
Solar/Wind Harmer
3.009
316468AD1-105 GEN
Solar/Wind Harmer
1.136
3141813NORNECK
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316059AD1-063 C
Solar/Wind Harmer
0.212
957601AF2-054 GEN
Solar/Wind Harmer
0.282
3141873WAN 176
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
316233AE1-074 FULL
Solar/Wind Harmer
0.251
971281AH1-106 GEN
Solar/Wind Harmer
1.515
971283AH1-107 GEN
Solar/Wind Harmer
1.515
971285AH1-108 GEN
Adder
0.625
957831AF2-077 GEN
Solar/Wind Harmer
0.279
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316382AG1-145 C
Solar/Wind Harmer
0.278
316159AE1-175 C
Solar/Wind Harmer
0.247
315697AD1-025 GEN
Solar/Wind Harmer
1.845
315839AE2-212 C
Solar/Wind Harmer
0.275
3151201GRAVEL4
Adder
5.887
3151221GRAVEL6
Adder
5.88
3151191GRAVEL3
Adder
5.812
3151211GRAVEL5
Adder
5.812
971445AH1-216 GEN
Solar/Wind Harmer
5.601
316236AE1-162_GEN
Solar/Wind Harmer
0.272
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.567
3151081ELIZAR1
Adder
7.328
3151091ELIZAR2
Adder
7.201
316316AC1-027 C
Solar/Wind Harmer
0.275
315833AF1-017_GEN
Solar/Wind Harmer
1.696
316311AC2-079 GEN
Solar/Wind Harmer
4.505
316018AA1-139 ULT2
Solar/Wind Harmer
0.763
957871AF2-081 GEN
Solar/Wind Harmer
4.463
3146406KITTY HAWK
Solar/Wind Harmer
0.007
313526AB2-022
Solar/Wind Harmer
0.238
316258AE1-075 C
Solar/Wind Harmer
0.214
316405AF2-144 C
Solar/Wind Harmer
0.226
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.163
315814AE2-033 C
Solar/Wind Harmer
8.134
970533AG2-339 GEN
Solar/Wind Harmer
5.862
315800Z1-036_GEN1
Solar/Wind Harmer
2.143
970673AG2-436 GEN
Solar/Wind Harmer
18.965
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
971967AH1-528 GEN
Solar/Wind Harmer
16.126
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.703
315733AD1-074 GEN2
Solar/Wind Harmer
1.703
3146206CASHIE
Solar/Wind Harmer
-0.008
3152111X4-039 GT1
50/50
1.847
315747AE2-019 GEN
50/50
13.195
963691AG1-221 GEN
Solar/Wind Harmer
2.315
971455AH1-223 GEN
Solar/Wind Harmer
2.315
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150151POSSMC1
Adder
1.062
3150151POSSMC1
Adder
1.062
3150241REMNGT4
Adder
12.548
972199AH1-684 GEN
Adder
1.902
972217AH1-693 GEN
Adder
1.654
3150301M RUN C
Adder
13.348
3150291M RUN B
Adder
13.249
3150331BIRCHWDA
Adder
16.425
3150401LDYSMT4
Adder
12.537
3150371LDYSMT1
Adder
12.114
966881AG1-559 GEN
Solar/Wind Harmer
0.305
3132273ORANGE
Solar/Wind Harmer
-0.002
316223AC1-118
Solar/Wind Harmer
0.268
3141906WESTMOR
Solar/Wind Harmer
-0.004
971781AH1-399 GEN
Solar/Wind Harmer
0.613
3147666LOUISA
Solar/Wind Harmer
-0.023
316077AC2-138 C
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.875
3151761LOISA E
Adder
11.363
3151721LOISA A
Adder
5.545
316484AD2-074 GEN
Solar/Wind Harmer
2.41
961951AG1-038 GEN
Solar/Wind Harmer
1.261
316473AC1-191 GEN
Solar/Wind Harmer
1.029
3142416OLDCHRC
Solar/Wind Harmer
0.952
3141766HARMONY
Solar/Wind Harmer
0.838
3141873WAN 176
Solar/Wind Harmer
1.118
316203AE2-005 GEN
Solar/Wind Harmer
3.969
3141843SHACKLE
Adder
0.428
970293AG2-193 GEN
Solar/Wind Harmer
1.173
316075AC2-137 C
Solar/Wind Harmer
0.252
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3143096IRON208
Adder
0.348
3143096IRON208
Adder
0.341
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.382
970133AG2-095 GEN
Solar/Wind Harmer
1.036
316458AB2-190 GEN2
Solar/Wind Harmer
0.926
3150921YORKTN3
Adder
2.05
315778AD1-151 GEN
Solar/Wind Harmer
8.149
3144216WINCHST
Adder
0.307
961611AG1-000B GEN
Solar/Wind Harmer
1.918
3151171GRAVELC
Adder
1.131
315813AE1-149 C
Solar/Wind Harmer
5.656
3145336SMITFLD
Solar/Wind Harmer
-0.004
3144536CHRHLND
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
1.817
3151101ELIZAR3
Adder
7.422
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
40.831
944601AF1-125 GEN
Solar/Wind Harmer
40.194
3142956BIRDNECK
Solar/Wind Harmer
0.481
316411AF1-147_GEN1
Solar/Wind Harmer
1.1
3150071POSSM 5
Adder
48.541
3150181POSSMC2
Adder
1.071
3150181POSSMC2
Adder
1.062
3150181POSSMC2
Adder
1.062
316006AB2-029 C
Solar/Wind Harmer
0.63
316045AC1-158 PL2
Solar/Wind Harmer
3.317
316450AC1-158 RIC
Solar/Wind Harmer
0.276
3150391LDYSMT3
Adder
12.514
972195AH1-682 GEN
Adder
1.644
315673AE1-157 GEN
Solar/Wind Harmer
7.709
972189AH1-679 GEN
Adder
1.453
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3150341NORNECKC1
Adder
0.904
3150341NORNECKC1
Adder
0.897
3151731LOISA B
Adder
5.574
316487AF1-042 GEN
Solar/Wind Harmer
1.261
966871AG1-558 GEN
Solar/Wind Harmer
0.288
966871AG1-558 GEN
Solar/Wind Harmer
0.098
3142296MT RD221
Adder
0.268
316312AB1-027
Solar/Wind Harmer
0.317
316156AD2-030 GEN
Solar/Wind Harmer
0.251
315666AE1-190 GEN
Solar/Wind Harmer
0.283
316441AF1-014 GEN
Solar/Wind Harmer
0.635
3142366NRTHEST
Adder
0.273
3150691DARBY 3
Adder
6.012
3150701DARBY 4
Adder
5.998
3150681DARBY 2
Adder
5.991
3150671DARBY 1
Adder
5.984
315976AC1-164 GENA
Solar/Wind Harmer
2.128
316169AC1-164_GENC
Solar/Wind Harmer
1.839
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.048
971223AH1-071 GEN
Solar/Wind Harmer
1.162
944641AF1-129 GEN
Adder
39.056
316240AF1-291 C
Solar/Wind Harmer
0.276
316033AB2-134 GEN
Solar/Wind Harmer
2.944
316294AC1-161 GEN
Solar/Wind Harmer
2.915
316083AB2-161 GEN
Solar/Wind Harmer
1.46
3150991CHESPKB
Adder
0.837
3150991CHESPKB
Adder
0.817
316185AD1-033 GEN
Solar/Wind Harmer
0.943
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316349AD2-085 GEN
Solar/Wind Harmer
0.793
316339AD2-160 GEN
Solar/Wind Harmer
0.601
316388AE2-253 GEN
Solar/Wind Harmer
0.601
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3146456SLIGO L269
Solar/Wind Harmer
1.053
3130086AYDLETT
Solar/Wind Harmer
-0.035
315835AF2-110_GEN
Solar/Wind Harmer
1.111
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316313AB2-026
Solar/Wind Harmer
0.238
316431W1029_GEN1
Solar/Wind Harmer
1.595
316433W1029_GEN2
Solar/Wind Harmer
1.595
316435W1029_GEN3
Solar/Wind Harmer
1.595
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.305
970601AG2-382 GEN
Solar/Wind Harmer
3.67
316318V4-068
Solar/Wind Harmer
0.209
3145893MURPHYS
Solar/Wind Harmer
-0.022
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.197
970581AG2-369 GEN
Solar/Wind Harmer
4.47
316463AE2-346 GEN
Solar/Wind Harmer
0.134
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.186
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.218
316426AA2-053 GEN
Solar/Wind Harmer
0.825
972205AH1-687 GEN
Adder
3.111
316322AB2-045
Solar/Wind Harmer
0.274
971845AH1-439 GEN
Solar/Wind Harmer
4.345
316174AB2-169 GEN
Solar/Wind Harmer
1.257
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
-0.032
946301AF1-294 GEN
Solar/Wind Harmer
2.061
961791AG1-021 GEN
Solar/Wind Harmer
1.005
316210AC1-098 GEN
Solar/Wind Harmer
1.256
970683AG2-441 GEN
Solar/Wind Harmer
5.661
970681AG2-440 GEN
Solar/Wind Harmer
3.757
970831AG2-522 GEN
Solar/Wind Harmer
4.005
316274AC1-208 GEN
Solar/Wind Harmer
0.859
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151881LOWMORC
Adder
0.636
3151881LOWMORC
Adder
0.626
3151861LOWMORA
Adder
0.616
226929AD2-058 GEN
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
20390526W1-045 C
Solar/Wind Helper
0.252
233915AB1-141 GEN
Solar/Wind Helper
0.304
233940AF2-379 C
Solar/Wind Helper
0.037
233901CHERRYDALE C
Solar/Wind Helper
0.14
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.136
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20715028HAN_X4-015
Solar/Wind Helper
0.033
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.11
20675528CPH_W2-050
Solar/Wind Helper
0.066
20673828FLE_V3-070
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.055
20676428JCR_X2-075
Solar/Wind Helper
0.039
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.241
209027LOR2_Q27
Solar/Wind Helper
0.557
212266LOR1
Solar/Wind Helper
0.162
209029WAYMART-WD
Solar/Wind Helper
0.442
209054AE2-059 GEN
Solar/Wind Helper
0.042
209067AE2-060 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.465
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
316017AA1-139 ULT1
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.032
316305AF2-043 C
Solar/Wind Harmer
0.268
316246AF1-032 C
Solar/Wind Harmer
0.18
316320Y1-086
Solar/Wind Harmer
0.519
3143336POWHATN
Solar/Wind Harmer
0.893
316321Z2-027
Solar/Wind Harmer
0.238
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
5.121
3146376EDENTON
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.74
315735AD1-075 GEN1
Solar/Wind Harmer
0.851
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
20.934
3146173TUNIS
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.168
3146263WOODLND
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.146
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.711
316190AA2-174 GEN
Solar/Wind Harmer
0.1
316317KELFORD C
Solar/Wind Harmer
0.379
3145823KELFORD
Solar/Wind Harmer
-0.008
972003AH1-546 GEN
Solar/Wind Harmer
3.324
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.22
316478AD1-087 GEN
Solar/Wind Harmer
0.7
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3144293JTRSVLE
Adder
0.171
316212AC1-099_GEN
Solar/Wind Harmer
0.698
972255AH1-712 GEN
Adder
36.481
3145933PARMELE
Solar/Wind Harmer
-0.008
959311AF2-222 GEN
Solar/Wind Harmer
8.345
970257AG2-171 GEN
Solar/Wind Harmer
2.995
971775AH1-396 GEN
Solar/Wind Harmer
0.564
3151861LOWMORA
Adder
0.641
226910AB2-157 C
Solar/Wind Helper
0.021
3150851SPRUNCC
Adder
0.382
944631AF1-128 GEN
Adder
39.483
3143226MDLTHAN
Solar/Wind Harmer
-0.009
971317AH1-138 GEN
Solar/Wind Harmer
1.152
316132AB2-190 GEN1
Solar/Wind Harmer
0.926
315671AE2-027_GEN
Solar/Wind Harmer
1.655
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.449
316369SG1_INVT
Solar/Wind Harmer
1.63
961611AG1-000B GEN
Solar/Wind Harmer
4.495
3151171GRAVELC
Adder
0.86
3145336SMITFLD
Solar/Wind Harmer
-0.036
315773AC2-141 GEN
Solar/Wind Harmer
3.772
316381AD1-082 GEN
Solar/Wind Harmer
0.823
316375AC2-012 GEN
Solar/Wind Harmer
3.106
316036AC1-147 C
Solar/Wind Harmer
0.242
3150981CHESPKA
Adder
0.998
944591AF1-124 GEN
Solar/Wind Harmer
40.978
316072AD1-144
Solar/Wind Harmer
0.181
939411AE1-173 GEN
Solar/Wind Harmer
44.594
3146456SLIGO L269
Solar/Wind Harmer
-0.009
319010AE1-072 C
Solar/Wind Harmer
1.799
940641AE2-051 GEN
Solar/Wind Harmer
8.349
316093AE2-104_GEN
Solar/Wind Harmer
2.584
3143336POWHATN
Solar/Wind Harmer
1.05
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
941031AE2-094 GEN
Solar/Wind Harmer
16.344
315611Z1-036_GEN2
Solar/Wind Harmer
2.143
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.689
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.006
315737AD1-076 GEN
Solar/Wind Harmer
1.601
970937AG2-583 GEN
Solar/Wind Harmer
6.064
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.097
316023GEN1_S
Solar/Wind Harmer
0.564
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.249
970919AG2-571 GEN
Solar/Wind Harmer
2.65
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.118
970087AG2-069 GEN
Solar/Wind Harmer
7.796
960081AF2-299 GEN
Solar/Wind Harmer
0.932
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.833
957481AF2-042 GEN
Solar/Wind Harmer
25.816
3146263WOODLND
Solar/Wind Harmer
-0.008
227287AC2-120 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.131
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
237038AE2-054 C
Solar/Wind Helper
0.174
235067AD1-061 GEN
Solar/Wind Helper
0.281
237085AD2-009_GEN
Solar/Wind Helper
0.972
233935AB2-179 C
Solar/Wind Helper
0.773
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.408
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.452
233997TMININ_4.2
Solar/Wind Helper
0.123
233950AC2-186 GEN
Solar/Wind Helper
0.07
232406W1-004 FULL
Solar/Wind Helper
0.305
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
207454AA2-184 E
Solar/Wind Helper
0.18
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
316087AB2-174 GEN
Solar/Wind Harmer
1.175
315693AD1-088 GEN
Solar/Wind Harmer
4.115
3145963POPLR C
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.005
3147043LAWRENC
Adder
0.658
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
971563AH1-280 GEN
Solar/Wind Harmer
1.005
3144293JTRSVLE
Adder
0.171
3144293JTRSVLE
Adder
0.135
970685AG2-442 GEN
Solar/Wind Harmer
7.025
972277AH1-723 GEN
Adder
42.511
3146293MARTNCO
Solar/Wind Harmer
0.05
316129AC1-054 GEN
Solar/Wind Harmer
0.698
316034AC1-036 C
Solar/Wind Harmer
0.148
205916AD1-020 GEN
Solar/Wind Helper
1.482
208835TUHI V3-051
Solar/Wind Helper
0.017
237001AB1-127_GEN
Solar/Wind Helper
0.307
205932AD2-116_GEN
Solar/Wind Helper
0.385
235063AE1-101 C2
Solar/Wind Helper
1.066
23777901MDS_W4-102
Solar/Wind Helper
0.105
203975AE1-071-GEN
Solar/Wind Helper
1.715
233918AB1-142 GEN
Solar/Wind Helper
0.304
233944AB2-135 GEN
Solar/Wind Helper
0.356
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.123
233998TM1NIN_3.36
Solar/Wind Helper
0.123
232404W1-003 C
Solar/Wind Helper
0.305
232408W1-005 C
Solar/Wind Helper
0.305
207442AE1-156 GEN
Solar/Wind Helper
0.188
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.051
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
1.005
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.241
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.233
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
970221AG2-151 GEN
Solar/Wind Harmer
1.339
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219348LDSOLAR C
Solar/Wind Helper
0.067
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.045
20720528MAN_W1-024
Solar/Wind Helper
0.016
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.01
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.017
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20674928WA_W3-044
Solar/Wind Helper
0.056
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.899
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.241
963151AG1-164 GEN
Solar/Wind Helper
0.241
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.828
946731AF1-337 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.709
316315AB2-025 C
Solar/Wind Harmer
0.235
316336AC2-165 C
Solar/Wind Harmer
5.454
315742AE1-103 GEN
Solar/Wind Harmer
2.062
3146376EDENTON
Solar/Wind Harmer
0.257
3146376EDENTON
Solar/Wind Harmer
0.257
972185AH1-677 GEN
Adder
4.294
972187AH1-678 GEN
Adder
2.166
315614AA2-178 GEN
Solar/Wind Harmer
0.919
970933AG2-581 GEN
Solar/Wind Harmer
7.973
316065AD1-022 GEN
Solar/Wind Harmer
4.203
316365GEN2_N
Solar/Wind Harmer
0.564
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316140AB2-099
Solar/Wind Harmer
0.056
970099AG2-077 GEN
Solar/Wind Harmer
10.327
313506AB2-031 GEN
Solar/Wind Harmer
0.66
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.1
962571AG1-106 GEN
Solar/Wind Harmer
1.178
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3145783HORNRTN
Solar/Wind Harmer
0.966
3145783HORNRTN
Solar/Wind Harmer
0.773
3145783HORNRTN
Solar/Wind Harmer
0.242
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.257
3144293JTRSVLE
Adder
0.171
972193AH1-681 GEN
Adder
1.63
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
970323AG2-213 GEN
Solar/Wind Harmer
3.993
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.066
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.217
233930AB2-032 GEN
Solar/Wind Helper
0.23
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.342
233994AC2-023 GEN
Solar/Wind Helper
0.577
232428Y3-058 C
Solar/Wind Helper
0.203
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
234015AF2-250 C
Solar/Wind Helper
0.023
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207459AE1-142 C O1
Solar/Wind Helper
0.169
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.236
946751AF1-339 GEN
Solar/Wind Helper
0.233
LAGNLTFEXP_LAGN->PJM
CLTF
6.282
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.471
TVALTFEXP_TVA->PJM
CLTF
3.166
CPLELTFEXP_CPLE->PJM
CLTF
5.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.711
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.515
MECLTFEXP_MEC->PJM
CLTF
4.421
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
2.573
LGEELTFEXP_LGEE->PJM
CLTF
1.794
WECLTFEXP_WEC->PJM
CLTF
0.956

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.46 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1925.78
MW Contribution:
2.74
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3138216PACIFIC
Solar/Wind Harmer
-0.003
970053AG2-049 GEN
Adder
1.473
315651AD1-115 GEN
Solar/Wind Harmer
3.931
316164AC1-076 GEN
Solar/Wind Harmer
0.727
3147346CASHSCORNER
Solar/Wind Harmer
0.123
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
9.207
3150381LDYSMT2
Adder
8.811
972213AH1-691 GEN
Adder
1.49
972215AH1-692 GEN
Adder
1.49
944491AF1-114 GEN
Solar/Wind Harmer
2.202
316468AD1-105 GEN
Solar/Wind Harmer
0.85
3141813NORNECK
Solar/Wind Harmer
-0.007
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971281AH1-106 GEN
Solar/Wind Harmer
1.182
971283AH1-107 GEN
Solar/Wind Harmer
1.182
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.486
316059AD1-063 C
Solar/Wind Harmer
0.163
3143873LANEXA
Solar/Wind Harmer
-0.004
957601AF2-054 GEN
Solar/Wind Harmer
0.216
3141873WAN 176
Solar/Wind Harmer
-0.001
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
957831AF2-077 GEN
Solar/Wind Harmer
0.216
3138283WHITEMARSH
Solar/Wind Harmer
0.011
316382AG1-145 C
Solar/Wind Harmer
0.215
316159AE1-175 C
Solar/Wind Harmer
0.192
315839AE2-212 C
Solar/Wind Harmer
0.214
315697AD1-025 GEN
Solar/Wind Harmer
1.438
3151201GRAVEL4
Adder
4.595
3151221GRAVEL6
Adder
4.59
3151191GRAVEL3
Adder
4.537
3151211GRAVEL5
Adder
4.537
3143316POE
Solar/Wind Harmer
-0.028
316258AE1-075 C
Solar/Wind Harmer
0.171
316405AF2-144 C
Solar/Wind Harmer
0.181
971445AH1-216 GEN
Solar/Wind Harmer
4.378
316236AE1-162_GEN
Solar/Wind Harmer
0.213
970657AG2-426 GEN
Solar/Wind Harmer
0.444
3151081ELIZAR1
Adder
5.744
3151091ELIZAR2
Adder
5.644
316316AC1-027 C
Solar/Wind Harmer
0.215
315833AF1-017_GEN
Solar/Wind Harmer
1.331
316311AC2-079 GEN
Solar/Wind Harmer
3.535
316018AA1-139 ULT2
Solar/Wind Harmer
0.599
957871AF2-081 GEN
Solar/Wind Harmer
3.504
3146406KITTY HAWK
Solar/Wind Harmer
0.006
313526AB2-022
Solar/Wind Harmer
0.187
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.128
970533AG2-339 GEN
Solar/Wind Harmer
4.647
315814AE2-033 C
Solar/Wind Harmer
6.429
970673AG2-436 GEN
Solar/Wind Harmer
15.054
315800Z1-036_GEN1
Solar/Wind Harmer
1.693
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
12.837
972205AH1-687 GEN
Adder
2.57
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316322AB2-045
Solar/Wind Harmer
0.225
315732AD1-074 GEN1
Solar/Wind Harmer
1.354
315733AD1-074 GEN2
Solar/Wind Harmer
1.354
971845AH1-439 GEN
Solar/Wind Harmer
3.565
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.923
316318V4-068
Solar/Wind Harmer
0.166
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.162
970581AG2-369 GEN
Solar/Wind Harmer
3.579
946281AF1-292 GEN
Solar/Wind Harmer
0.149
316463AE2-346 GEN
Solar/Wind Harmer
0.107
3145513AHOSKIE
Solar/Wind Harmer
0.058
961941AG1-037 GEN
Solar/Wind Harmer
0.05
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3137643SOCKMAN
Solar/Wind Harmer
-0.026
316426AA2-053 GEN
Solar/Wind Harmer
0.662
315652AC1-086 GEN
Solar/Wind Harmer
7.388
946301AF1-294 GEN
Solar/Wind Harmer
1.679
961791AG1-021 GEN
Solar/Wind Harmer
0.819
316486AD2-202 GEN
Solar/Wind Harmer
0.166
316174AB2-169 GEN
Solar/Wind Harmer
1.007
970683AG2-441 GEN
Solar/Wind Harmer
4.61
970681AG2-440 GEN
Solar/Wind Harmer
3.06
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
3144303KENBRDG
Solar/Wind Harmer
-0.005
237030AB1-096 C
Solar/Wind Helper
0.095
237025AB1-124 C
Solar/Wind Helper
0.234
23779801AA1-109
Solar/Wind Helper
0.262
205917AD1-020 ES
Solar/Wind Helper
0.358
226929AD2-058 GEN
Solar/Wind Helper
0.079
959381AF2-229 GEN
Solar/Wind Helper
0.283
20390526W1-045 C
Solar/Wind Helper
0.278
205943AE1-185 GEN
Solar/Wind Helper
0.41
205956AE1-196_GEN
Solar/Wind Helper
0.407
233915AB1-141 GEN
Solar/Wind Helper
0.305
233901CHERRYDALE C
Solar/Wind Helper
0.14
233940AF2-379 C
Solar/Wind Helper
0.037
232432Z2-076 GEN
Solar/Wind Helper
0.04
230434AG1-499 GEN
Solar/Wind Helper
0.136
228728W1-130C
Solar/Wind Helper
0.032
219258KINSLEYDEP C
Solar/Wind Helper
0.045
230407AD2-065 C
Solar/Wind Helper
0.024
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
20720728JCB_W1-129
Solar/Wind Helper
0.033
20715028HAN_X4-015
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
219620RIDERU C
Solar/Wind Helper
0.001
20720628TIN_W1-124
Solar/Wind Helper
0.11
20675528CPH_W2-050
Solar/Wind Helper
0.065
20673828FLE_V3-070
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
20676128MHD_W3-029
Solar/Wind Helper
0.055
20676428JCR_X2-075
Solar/Wind Helper
0.039
207408W3-077 C
Solar/Wind Helper
0.048
3152111X4-039 GT1
50/50
1.834
315747AE2-019 GEN
50/50
12.529
963691AG1-221 GEN
Solar/Wind Harmer
2.258
971455AH1-223 GEN
Solar/Wind Harmer
2.258
3141196NOKESVL
Solar/Wind Harmer
-0.043
3150241REMNGT4
Adder
10.998
972199AH1-684 GEN
Adder
1.667
972217AH1-693 GEN
Adder
1.45
3150301M RUN C
Adder
11.683
3150291M RUN B
Adder
11.597
3132273ORANGE
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Harmer
-0.018
3151761LOISA E
Adder
9.471
3151721LOISA A
Adder
4.622
3150151POSSMC1
Adder
0.712
3150151POSSMC1
Adder
0.712
3150331BIRCHWDA
Adder
11.656
3150401LDYSMT4
Adder
9.178
3150371LDYSMT1
Adder
8.868
966881AG1-559 GEN
Solar/Wind Harmer
0.227
971781AH1-399 GEN
Solar/Wind Harmer
0.458
316223AC1-118
Solar/Wind Harmer
0.2
3141906WESTMOR
Solar/Wind Harmer
-0.003
316077AC2-138 C
Solar/Wind Harmer
0.154
3150351NORNECKC2
Adder
0.661
316473AC1-191 GEN
Solar/Wind Harmer
0.787
316484AD2-074 GEN
Solar/Wind Harmer
1.834
961951AG1-038 GEN
Solar/Wind Harmer
0.96
3142416OLDCHRC
Solar/Wind Harmer
0.733
970293AG2-193 GEN
Solar/Wind Harmer
0.906
316075AC2-137 C
Solar/Wind Harmer
0.195
3150861SPRUNCD
Adder
0.297
3141766HARMONY
Solar/Wind Harmer
0.644
316203AE2-005 GEN
Solar/Wind Harmer
3.049
3141873WAN 176
Solar/Wind Harmer
0.858
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.264
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142946ENON
Solar/Wind Harmer
-0.002
970133AG2-095 GEN
Solar/Wind Harmer
0.806
316458AB2-190 GEN2
Solar/Wind Harmer
0.72
315778AD1-151 GEN
Solar/Wind Harmer
6.347
3150921YORKTN3
Adder
1.594
3144216WINCHST
Adder
0.239
961611AG1-000B GEN
Solar/Wind Harmer
1.496
3151171GRAVELC
Adder
0.883
315813AE1-149 C
Solar/Wind Harmer
4.424
3143336POWHATN
Solar/Wind Harmer
0.714
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
970657AG2-426 GEN
Solar/Wind Harmer
1.423
3151101ELIZAR3
Adder
5.817
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
32.014
944601AF1-125 GEN
Solar/Wind Harmer
31.514
3142956BIRDNECK
Solar/Wind Harmer
0.377
316017AA1-139 ULT1
Solar/Wind Harmer
0.565
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.81
316305AF2-043 C
Solar/Wind Harmer
0.21
3152131X4-039 ST
50/50
2.868
3152121X4-039 GT2
50/50
1.822
316415AF1-147_GEN2
Solar/Wind Harmer
1.073
3150221REMNGT2
Adder
10.925
3150211REMNGT1
Adder
10.853
972201AH1-685 GEN
Adder
1.885
3150281M RUN A
Adder
11.691
971685AH1-345 GEN
Solar/Wind Harmer
0.836
316254AC1-120 GEN1
Solar/Wind Harmer
3.304
316170AC1-121 GEN2
Solar/Wind Harmer
1.101
316447AC1-158 HLD
Solar/Wind Harmer
1.872
316044AC1-158 PL1
Solar/Wind Harmer
0.851
315683AE1-153 C
Solar/Wind Harmer
8.072
3147666LOUISA
Solar/Wind Harmer
-0.032
316192AB2-158 GEN
Solar/Wind Harmer
0.957
3151751LOISA D
Adder
4.646
972223AH1-696 GEN
Adder
5.622
3150151POSSMC1
Adder
0.712
3141346CRANES
Adder
0.082
972197AH1-683 GEN
Adder
1.433
972219AH1-694 GEN
Adder
1.032
966881AG1-559 GEN
Solar/Wind Harmer
0.078
957971AF2-091 GEN
Solar/Wind Harmer
0.749
972135AH1-637 GEN
Solar/Wind Harmer
0.749
316337AD2-073 GEN
Solar/Wind Harmer
0.198
3150351NORNECKC2
Adder
0.65
964211AG1-282 GEN
Solar/Wind Harmer
0.22
3141726DUNNSVL
Solar/Wind Harmer
-0.029
316404AE1-155 C
Solar/Wind Harmer
1.394
958261AF2-120 GEN
Solar/Wind Harmer
2.829
962861AG1-135 GEN
Solar/Wind Harmer
2.737
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3143526WINTERP
Solar/Wind Harmer
-0.038
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.004
3150851SPRUNCC
Adder
0.297
316314AB2-024 C
Solar/Wind Harmer
0.618
3141766HARMONY
Solar/Wind Harmer
-0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.87
316280AD1-041 GEN
Solar/Wind Harmer
0.544
971777AH1-397 GEN
Solar/Wind Harmer
0.844
3143096IRON208
Adder
0.27
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
315975AC1-164 GENB
Solar/Wind Harmer
0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
30.58
971317AH1-138 GEN
Solar/Wind Harmer
0.894
315671AE2-027_GEN
Solar/Wind Harmer
1.289
316132AB2-190 GEN1
Solar/Wind Harmer
0.72
971069AG2-661 GEN
Solar/Wind Harmer
1.128
3138126ROCKLANDING
Solar/Wind Harmer
0.022
316369SG1_INVT
Solar/Wind Harmer
1.27
961611AG1-000B GEN
Solar/Wind Harmer
3.506
3151171GRAVELC
Adder
0.672
3143336POWHATN
Solar/Wind Harmer
0.84
316246AF1-032 C
Solar/Wind Harmer
0.141
316320Y1-086
Solar/Wind Harmer
0.408
316321Z2-027
Solar/Wind Harmer
0.187
3146516WINFALL
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
4.06
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
972003AH1-546 GEN
Solar/Wind Harmer
2.743
3156081AA2-088 GEN
Solar/Wind Harmer
2.18
3146776BUCKING
Solar/Wind Harmer
-0.002
315735AD1-075 GEN1
Solar/Wind Harmer
0.677
970917AG2-570 GEN
Solar/Wind Harmer
16.739
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
-0.007
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
4.15
966621AG1-532 GEN
Solar/Wind Harmer
0.135
942461AE2-259 GEN
Solar/Wind Harmer
0.995
972255AH1-712 GEN
Adder
30.111
3146263WOODLND
Solar/Wind Harmer
-0.007
316181AB2-040 GEN
Solar/Wind Harmer
0.919
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3147043LAWRENC
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316190AA2-174 GEN
Solar/Wind Harmer
0.081
316011AB1-132 GEN
Solar/Wind Harmer
1.372
3145963POPLR C
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.139
316478AD1-087 GEN
Solar/Wind Harmer
0.565
315821AE2-092 GEN
Solar/Wind Harmer
1.353
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
959311AF2-222 GEN
Solar/Wind Harmer
6.794
23777801MSM_W1-116
Solar/Wind Helper
0.157
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.31
237002AB1-128_GEN
Solar/Wind Helper
0.332
208835TUHI V3-051
Solar/Wind Helper
0.017
237038AE2-054 C
Solar/Wind Helper
0.191
235067AD1-061 GEN
Solar/Wind Helper
0.308
237085AD2-009_GEN
Solar/Wind Helper
1.053
233935AB2-179 C
Solar/Wind Helper
0.776
233933AB2-153 GEN
Solar/Wind Helper
0.141
232422X3-066 FULL
Solar/Wind Helper
0.069
233987AB2-037 GEN
Solar/Wind Helper
1.415
232417X3-008 C
Solar/Wind Helper
0.14
233964AF2-378 GEN
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.454
233997TMININ_4.2
Solar/Wind Helper
0.124
232406W1-004 FULL
Solar/Wind Helper
0.306
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
3145336SMITFLD
Solar/Wind Harmer
-0.028
315773AC2-141 GEN
Solar/Wind Harmer
2.954
316381AD1-082 GEN
Solar/Wind Harmer
0.645
316375AC2-012 GEN
Solar/Wind Harmer
2.434
316036AC1-147 C
Solar/Wind Harmer
0.189
3150981CHESPKA
Adder
0.782
944591AF1-124 GEN
Solar/Wind Harmer
32.129
316072AD1-144
Solar/Wind Harmer
0.142
939411AE1-173 GEN
Solar/Wind Harmer
35.115
940641AE2-051 GEN
Solar/Wind Harmer
6.583
3146456SLIGO L269
Solar/Wind Harmer
-0.007
319010AE1-072 C
Solar/Wind Harmer
1.412
316093AE2-104_GEN
Solar/Wind Harmer
2.03
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
941031AE2-094 GEN
Solar/Wind Harmer
12.958
970937AG2-583 GEN
Solar/Wind Harmer
4.944
315611Z1-036_GEN2
Solar/Wind Harmer
1.693
3130156CHOWAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.546
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.349
3146776BUCKING
Solar/Wind Harmer
-0.003
315737AD1-076 GEN
Solar/Wind Harmer
1.273
970919AG2-571 GEN
Solar/Wind Harmer
2.119
316023GEN1_S
Solar/Wind Harmer
0.45
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.67
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.198
3146926FARMVIL
Solar/Wind Harmer
-0.004
970087AG2-069 GEN
Solar/Wind Harmer
6.243
3146173TUNIS
Solar/Wind Harmer
-0.007
957481AF2-042 GEN
Solar/Wind Harmer
20.758
971377AH1-170 GEN
Solar/Wind Harmer
0.83
3147623JAMES R
Solar/Wind Harmer
0.103
3156021HOLLOMANSOL
Solar/Wind Harmer
0.892
315693AD1-088 GEN
Solar/Wind Harmer
3.317
960081AF2-299 GEN
Solar/Wind Harmer
0.746
3145683EARLEYS
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.667
972277AH1-723 GEN
Adder
35.088
316087AB2-174 GEN
Solar/Wind Harmer
0.941
3146263WOODLND
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.529
3145963POPLR C
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
971563AH1-280 GEN
Solar/Wind Harmer
0.819
3144293JTRSVLE
Adder
0.139
3144293JTRSVLE
Adder
0.11
3145783HORNRTN
Solar/Wind Harmer
-0.007
970685AG2-442 GEN
Solar/Wind Harmer
5.722
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.007
316034AC1-036 C
Solar/Wind Harmer
0.12
205916AD1-020 GEN
Solar/Wind Helper
1.663
237001AB1-127_GEN
Solar/Wind Helper
0.343
208835TUHI V3-051
Solar/Wind Helper
0.017
235063AE1-101 C2
Solar/Wind Helper
1.173
205932AD2-116_GEN
Solar/Wind Helper
0.407
23777901MDS_W4-102
Solar/Wind Helper
0.113
203975AE1-071-GEN
Solar/Wind Helper
1.876
233918AB1-142 GEN
Solar/Wind Helper
0.305
233944AB2-135 GEN
Solar/Wind Helper
0.358
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.306
232408W1-005 C
Solar/Wind Helper
0.306
219766PARADISE C
Solar/Wind Helper
0.032
228729W2-030 C
Solar/Wind Helper
0.065
219907AC1-030 C
Solar/Wind Helper
0.02
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
316411AF1-147_GEN1
Solar/Wind Harmer
1.073
316006AB2-029 C
Solar/Wind Harmer
0.548
316045AC1-158 PL2
Solar/Wind Harmer
2.723
316450AC1-158 RIC
Solar/Wind Harmer
0.227
966001AG1-469 GEN
Solar/Wind Harmer
0.153
3151731LOISA B
Adder
4.646
3150071POSSM 5
Adder
32.531
3150181POSSMC2
Adder
0.718
3150181POSSMC2
Adder
0.712
3150181POSSMC2
Adder
0.712
3150391LDYSMT3
Adder
9.161
972195AH1-682 GEN
Adder
1.204
315673AE1-157 GEN
Solar/Wind Harmer
5.701
972189AH1-679 GEN
Adder
1.102
3150341NORNECKC1
Adder
0.683
3150341NORNECKC1
Adder
0.678
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
3142296MT RD221
Adder
0.206
316487AF1-042 GEN
Solar/Wind Harmer
0.96
971223AH1-071 GEN
Solar/Wind Harmer
0.911
3143526WINTERP
Solar/Wind Harmer
-0.038
316312AB1-027
Solar/Wind Harmer
0.244
3142366NRTHEST
Adder
0.211
3150691DARBY 3
Adder
4.643
3150701DARBY 4
Adder
4.632
3150681DARBY 2
Adder
4.627
3150671DARBY 1
Adder
4.621
316441AF1-014 GEN
Solar/Wind Harmer
0.488
315666AE1-190 GEN
Solar/Wind Harmer
0.217
316156AD2-030 GEN
Solar/Wind Harmer
0.193
315976AC1-164 GENA
Solar/Wind Harmer
1.643
316169AC1-164_GENC
Solar/Wind Harmer
1.419
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
30.387
316240AF1-291 C
Solar/Wind Harmer
0.215
316033AB2-134 GEN
Solar/Wind Harmer
2.294
316313AB2-026
Solar/Wind Harmer
0.19
316294AC1-161 GEN
Solar/Wind Harmer
2.283
316083AB2-161 GEN
Solar/Wind Harmer
1.144
3150991CHESPKB
Adder
0.656
3150991CHESPKB
Adder
0.641
316185AD1-033 GEN
Solar/Wind Harmer
0.74
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316336AC2-165 C
Solar/Wind Harmer
4.383
316339AD2-160 GEN
Solar/Wind Harmer
0.471
316388AE2-253 GEN
Solar/Wind Harmer
0.471
316349AD2-085 GEN
Solar/Wind Harmer
0.622
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.827
3130086AYDLETT
Solar/Wind Harmer
-0.028
315835AF2-110_GEN
Solar/Wind Harmer
0.873
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.256
316433W1029_GEN2
Solar/Wind Harmer
1.256
316435W1029_GEN3
Solar/Wind Harmer
1.256
971761AH1-387 GEN
Solar/Wind Harmer
3.866
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3144356SAPONY
Solar/Wind Harmer
0.241
316315AB2-025 C
Solar/Wind Harmer
0.186
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
1.629
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
972185AH1-677 GEN
Adder
3.415
972187AH1-678 GEN
Adder
1.725
970933AG2-581 GEN
Solar/Wind Harmer
6.362
315614AA2-178 GEN
Solar/Wind Harmer
0.729
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
316065AD1-022 GEN
Solar/Wind Harmer
3.346
316365GEN2_N
Solar/Wind Harmer
0.45
3145893MURPHYS
Solar/Wind Harmer
0.186
3145893MURPHYS
Solar/Wind Harmer
-0.012
970301AG2-198 GEN
Solar/Wind Harmer
3.329
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
970099AG2-077 GEN
Solar/Wind Harmer
8.303
316140AB2-099
Solar/Wind Harmer
0.045
972193AH1-681 GEN
Adder
1.345
313506AB2-031 GEN
Solar/Wind Harmer
0.529
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
962571AG1-106 GEN
Solar/Wind Harmer
0.944
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.054
958211AF2-115 GEN
Solar/Wind Harmer
1.024
3144293JTRSVLE
Adder
0.139
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.621
3145783HORNRTN
Solar/Wind Harmer
0.194
3145783HORNRTN
Solar/Wind Harmer
0.078
3145796HORNRTN
Solar/Wind Harmer
-0.019
970323AG2-213 GEN
Solar/Wind Harmer
3.251
237006AB1-125 GEN
Solar/Wind Helper
0.175
223401AF1-299 GEN
Solar/Wind Helper
0.386
223402AF1-300 C
Solar/Wind Helper
0.386
238221AF1-254 C O1
Solar/Wind Helper
0.198
237080AD1-060 GEN
Solar/Wind Helper
0.243
235062AE1-101 C1
Solar/Wind Helper
1.173
235020AA1-095 C
Solar/Wind Helper
0.031
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
232436AB1-176 C
Solar/Wind Helper
0.027
232424Y1-079 C
Solar/Wind Helper
0.07
234036AF2-325 C
Solar/Wind Helper
0.026
233946AB2-136 GEN
Solar/Wind Helper
0.343
233994AC2-023 GEN
Solar/Wind Helper
0.58
232428Y3-058 C
Solar/Wind Helper
0.204
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.306
234015AF2-250 C
Solar/Wind Helper
0.023
230511AF1-262
Solar/Wind Helper
0.009
230433AD2-135 GEN
Solar/Wind Helper
0.01
219904AC1-010 C
Solar/Wind Helper
0.036
219912AD2-042 GEN
Solar/Wind Helper
0.089
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219906AC1-017 C
Solar/Wind Helper
0.025
219607WPEMNERT C
Solar/Wind Helper
0.047
964851AG1-348 GEN
Solar/Wind Helper
0.036
20675128HRM_W1-127
Solar/Wind Helper
0.017
961261AF2-417 GEN
Solar/Wind Helper
0.239
209027LOR2_Q27
Solar/Wind Helper
0.551
212266LOR1
Solar/Wind Helper
0.16
209029WAYMART-WD
Solar/Wind Helper
0.438
209067AE2-060 GEN
Solar/Wind Helper
0.042
209054AE2-059 GEN
Solar/Wind Helper
0.042
959431AF2-234 GEN
Solar/Wind Helper
0.459
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.23
219348LDSOLAR C
Solar/Wind Helper
0.067
20716028EGP_W2-019
Solar/Wind Helper
0.011
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
20715228NPK_W1-113
Solar/Wind Helper
0.045
20720528MAN_W1-024
Solar/Wind Helper
0.016
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
218440SUMMTASSOC C
Solar/Wind Helper
0.009
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
218428ETC SOLAR C
Solar/Wind Helper
0.003
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.017
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20674928WA_W3-044
Solar/Wind Helper
0.056
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20675728RH_W2-091
Solar/Wind Helper
0.047
20674628WNG_W3-110
Solar/Wind Helper
0.051
207518AF1-320_GEN
Solar/Wind Helper
0.895
20676228FRD_X1-012
Solar/Wind Helper
0.052
20675828AU_W4-064
Solar/Wind Helper
0.017
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.239
963151AG1-164 GEN
Solar/Wind Helper
0.239
961341AF2-425 GEN
Solar/Wind Helper
0.234
209137AF2-361 C
Solar/Wind Helper
0.706
212507AE2-042_GEN
Solar/Wind Helper
0.818
946731AF1-337 GEN
Solar/Wind Helper
0.23
219304NAMERICA C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.007
20720828JCB_W4-025
Solar/Wind Helper
0.037
207454AA2-184 E
Solar/Wind Helper
0.18
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
207442AE1-156 GEN
Solar/Wind Helper
0.188
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.046
207511W3-106 GEN
Solar/Wind Helper
0.015
20671928W4-073
Solar/Wind Helper
0.051
20674128FR_U2-059
Solar/Wind Helper
0.002
209116AE2-175 GEN
Solar/Wind Helper
0.998
211065PSPA IPP
Solar/Wind Helper
0.085
963161AG1-165 GEN
Solar/Wind Helper
0.239
208972BECR K09
Solar/Wind Helper
0.176
961331AF2-424 GEN
Solar/Wind Helper
0.234
961421AF2-433 GEN
Solar/Wind Helper
0.233
957921AF2-086 GEN
Solar/Wind Helper
0.231
946691AF1-333 GEN
Solar/Wind Helper
0.23
946741AF1-338 GEN
Solar/Wind Helper
0.23
209071AE2-133 GEN
Solar/Wind Helper
0.042
970257AG2-171 GEN
Solar/Wind Harmer
0.153
207459AE1-142 C O1
Solar/Wind Helper
0.169
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.009
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.096
20674828DL_W4-046
Solar/Wind Helper
0.005
961431AF2-434 GEN
Solar/Wind Helper
0.233
946751AF1-339 GEN
Solar/Wind Helper
0.23
LAGNLTFEXP_LAGN->PJM
CLTF
5.819
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.752
TVALTFEXP_TVA->PJM
CLTF
2.93
CPLELTFEXP_CPLE->PJM
CLTF
4.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.589
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.807
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.743
MECLTFEXP_MEC->PJM
CLTF
4.279
SIGELTFEXP_SIGE->PJM
CLTF
0.135
NYPJM->LTFIMP_NY
CLTF
2.537
LGEELTFEXP_LGEE->PJM
CLTF
1.748
WECLTFEXP_WEC->PJM
CLTF
0.938

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.68 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4085.15
MW Contribution:
12.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
5.363
315241AE2-183_GT1
50/50
5.349
972185AH1-677 GEN
50/50
19.387
3151041BRUNSWICKG3
50/50
4.229
972187AH1-678 GEN
50/50
9.703
970909AG2-566 GEN
50/50
3.042
3144293JTRSVLE
50/50
0.671
970535AG2-341 GEN
50/50
4.397
3151581KERR 1
50/50
0.179
3151261ROARAP2
50/50
0.275
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.808
3151371ROSEMS1
50/50
0.501
3151381ROSEMG2
50/50
0.379
970933AG2-581 GEN
Solar/Wind Harmer
33.318
970099AG2-077 GEN
Solar/Wind Harmer
41.272
970301AG2-198 GEN
Solar/Wind Harmer
16.023
3146776BUCKING
Solar/Wind Harmer
-0.126
3146776BUCKING
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
958211AF2-115 GEN
Solar/Wind Harmer
4.651
315687AD1-152 GEN
Solar/Wind Harmer
3.504
970323AG2-213 GEN
Solar/Wind Harmer
14.484
313527AB2-043 GEN
Solar/Wind Harmer
4.554
3144356SAPONY
Solar/Wind Harmer
0.978
316315AB2-025 C
Solar/Wind Harmer
0.754
316237AB2-079_GEN
Solar/Wind Harmer
0.84
962561AG1-105 GEN
Solar/Wind Harmer
14.998
316365GEN2_N
Solar/Wind Harmer
1.781
964791AG1-342 GEN
Solar/Wind Harmer
5.642
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
313506AB2-031 GEN
Solar/Wind Harmer
2.1
316294AC1-161 GEN
Solar/Wind Harmer
8.423
316118AC1-105 GEN
Solar/Wind Harmer
1.771
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
0.214
3145783HORNRTN
Solar/Wind Harmer
3.038
3145783HORNRTN
Solar/Wind Harmer
2.43
3145783HORNRTN
Solar/Wind Harmer
0.759
3145783HORNRTN
Solar/Wind Harmer
0.304
962571AG1-106 GEN
Solar/Wind Harmer
3.662
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.101
3145506HICKORY
Solar/Wind Harmer
-0.061
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.666
316339AD2-160 GEN
Solar/Wind Harmer
1.702
316388AE2-253 GEN
Solar/Wind Harmer
1.702
3137176SLIGO L2192
Solar/Wind Harmer
-0.1
3146456SLIGO L269
Solar/Wind Harmer
2.985
3130086AYDLETT
Solar/Wind Harmer
-0.101
316248AF1-058 C
Solar/Wind Harmer
0.759
3145796HORNRTN
Solar/Wind Harmer
-0.075
3146386ELIZ CT
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.7
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.538
316433W1029_GEN2
Solar/Wind Harmer
4.538
316435W1029_GEN3
Solar/Wind Harmer
4.538
315244AE2-183_ST
50/50
9.313
963041AG1-153 GEN
50/50
8.562
3151541CLOVER2
50/50
5.968
315779AE2-040
50/50
3.484
3151601KERR 3
50/50
0.501
3151611KERR 4
50/50
0.501
3151621KERR 5
50/50
0.501
3151631KERR 6
50/50
0.501
3151281ROARAP4
50/50
0.256
970533AG2-339 GEN
Solar/Wind Harmer
25.362
970673AG2-436 GEN
Solar/Wind Harmer
81.518
971967AH1-528 GEN
Solar/Wind Harmer
68.252
970085AG2-068 GEN
Solar/Wind Harmer
21.238
970581AG2-369 GEN
Solar/Wind Harmer
18.265
316322AB2-045
Solar/Wind Harmer
1.062
971845AH1-439 GEN
Solar/Wind Harmer
16.816
316486AD2-202 GEN
Solar/Wind Harmer
0.796
946301AF1-294 GEN
Solar/Wind Harmer
7.628
961791AG1-021 GEN
Solar/Wind Harmer
3.721
970683AG2-441 GEN
Solar/Wind Harmer
20.75
970681AG2-440 GEN
Solar/Wind Harmer
13.772
3144303KENBRDG
Solar/Wind Harmer
-0.023
315814AE2-033 C
Solar/Wind Harmer
26.043
316238AB2-078_GEN
Solar/Wind Harmer
0.84
316239AB2-077_GEN
Solar/Wind Harmer
0.84
970831AG2-522 GEN
Solar/Wind Harmer
13.396
946281AF1-292 GEN
Solar/Wind Harmer
0.596
3137643SOCKMAN
Solar/Wind Harmer
-0.103
316426AA2-053 GEN
Solar/Wind Harmer
2.579
3146043SEABORD
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.662
316018AA1-139 ULT2
Solar/Wind Harmer
2.162
957871AF2-081 GEN
Solar/Wind Harmer
12.65
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
313526AB2-022
Solar/Wind Harmer
0.677
3146396TANGLEW
Solar/Wind Harmer
0.462
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
316316AC1-027 C
Solar/Wind Harmer
0.769
316318V4-068
Solar/Wind Harmer
0.625
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3151081ELIZAR1
Adder
20.406
3151091ELIZAR2
Adder
20.051
315800Z1-036_GEN1
Solar/Wind Harmer
6.164
316463AE2-346 GEN
Solar/Wind Harmer
0.402
3145513AHOSKIE
Solar/Wind Harmer
0.217
961941AG1-037 GEN
Solar/Wind Harmer
0.187
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
316274AC1-208 GEN
Solar/Wind Harmer
2.665
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.827
3146033SCOT NK
Solar/Wind Harmer
-0.098
315732AD1-074 GEN1
Solar/Wind Harmer
4.993
315733AD1-074 GEN2
Solar/Wind Harmer
4.993
316210AC1-098 GEN
Solar/Wind Harmer
3.867
316327AA2-057 GEN
Solar/Wind Harmer
2.445
316174AB2-169 GEN
Solar/Wind Harmer
3.736
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
957861AF2-080 GEN
Solar/Wind Harmer
10.406
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
316311AC2-079 GEN
Solar/Wind Harmer
11.782
315833AF1-017_GEN
Solar/Wind Harmer
4.431
3143316POE
Solar/Wind Harmer
-0.086
970657AG2-426 GEN
Solar/Wind Harmer
1.359
316236AE1-162_GEN
Solar/Wind Harmer
0.645
971445AH1-216 GEN
Solar/Wind Harmer
13.157
3151201GRAVEL4
Adder
12.508
3151221GRAVEL6
Adder
12.494
3151191GRAVEL3
Adder
12.35
3151211GRAVEL5
Adder
12.35
270455AD2-022 GEN
Solar/Wind Harmer
3.349
270457AD2-023 GEN
Solar/Wind Harmer
1.698
315839AE2-212 C
Solar/Wind Harmer
0.492
315697AD1-025 GEN
Solar/Wind Harmer
3.238
957831AF2-077 GEN
Solar/Wind Harmer
0.437
3138283WHITEMARSH
Solar/Wind Harmer
0.022
316382AG1-145 C
Solar/Wind Harmer
0.436
316159AE1-175 C
Solar/Wind Harmer
0.388
316258AE1-075 C
Solar/Wind Helper
0.481
316405AF2-144 C
Solar/Wind Helper
0.401
316233AE1-074 FULL
Solar/Wind Helper
0.35
3151031BRUNSWICKG2
50/50
4.229
970413AG2-270 GEN
50/50
26.189
3144293JTRSVLE
50/50
0.671
3151261ROARAP2
50/50
0.282
3151391GASTONA
50/50
0.606
3151411GASTONB
50/50
0.606
944011AF1-069 GEN
Solar/Wind Harmer
22.157
970917AG2-570 GEN
Solar/Wind Harmer
86.288
3146926FARMVIL
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.011
972003AH1-546 GEN
Solar/Wind Harmer
12.856
316478AD1-087 GEN
Solar/Wind Harmer
2.718
942461AE2-259 GEN
Solar/Wind Harmer
4.631
3147133PAMPLIN
Solar/Wind Harmer
-0.094
959311AF2-222 GEN
Solar/Wind Harmer
30.36
970257AG2-171 GEN
Solar/Wind Harmer
10.863
971775AH1-396 GEN
Solar/Wind Harmer
2.044
964241AG1-285 GEN
Solar/Wind Harmer
22.168
3147043LAWRENC
Solar/Wind Harmer
-0.016
966621AG1-532 GEN
Solar/Wind Harmer
0.54
316181AB2-040 GEN
Solar/Wind Harmer
3.647
944581AF1-123 GEN
Solar/Wind Harmer
117.24
944601AF1-125 GEN
Solar/Wind Harmer
115.41
316190AA2-174 GEN
Solar/Wind Harmer
0.314
316011AB1-132 GEN
Solar/Wind Harmer
5.321
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
316017AA1-139 ULT1
Solar/Wind Harmer
2.042
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
2.925
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
316320Y1-086
Solar/Wind Harmer
1.474
3156081AA2-088 GEN
Solar/Wind Harmer
8.16
3142956BIRDNECK
Solar/Wind Harmer
1.349
316321Z2-027
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316305AF2-043 C
Solar/Wind Harmer
0.752
316246AF1-032 C
Solar/Wind Harmer
0.505
3151101ELIZAR3
Adder
20.667
3146173TUNIS
Solar/Wind Harmer
-0.025
3146376EDENTON
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316317KELFORD C
Solar/Wind Harmer
1.148
3145823KELFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.025
315735AD1-075 GEN1
Solar/Wind Harmer
2.495
316212AC1-099_GEN
Solar/Wind Harmer
2.148
315722AD1-056 GEN
Solar/Wind Harmer
8.68
3145963POPLR C
Solar/Wind Harmer
-0.024
3146233WITAKRS
Solar/Wind Harmer
0.502
3146233WITAKRS
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.024
3138543CONSLDL
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316003AC1-222 GEN
Solar/Wind Harmer
2.319
316420AA1-050 GEN
Solar/Wind Harmer
2.708
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.437
316222AC1-221 GEN
Solar/Wind Harmer
2.254
316283AC2-100 C
Solar/Wind Harmer
2.091
971683AH1-343 GEN
Solar/Wind Harmer
9.57
970657AG2-426 GEN
Solar/Wind Harmer
4.354
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.544
3151171GRAVELC
Adder
2.404
316123AC1-075 GEN
Solar/Wind Harmer
2.012
3144216WINCHST
Adder
0.613
3150921YORKTN3
Adder
4.042
961611AG1-000B GEN
Solar/Wind Harmer
3.8
315778AD1-151 GEN
Solar/Wind Harmer
13.575
316458AB2-190 GEN2
Solar/Wind Harmer
1.423
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
316140AB2-099
Solar/Wind Harmer
0.168
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
3150991CHESPKB
Adder
2.321
3150991CHESPKB
Adder
2.265
315742AE1-103 GEN
Solar/Wind Harmer
5.898
315614AA2-178 GEN
Solar/Wind Harmer
2.672
316065AD1-022 GEN
Solar/Wind Harmer
12.372
315835AF2-110_GEN
Solar/Wind Harmer
3.074
315724AD1-057 GEN
Solar/Wind Harmer
4.774
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
316005AA1-067
Solar/Wind Harmer
0.481
3145493TOT1
Solar/Wind Harmer
0.367
3145453TOT5
Solar/Wind Harmer
0.22
3145603CNETO
Solar/Wind Harmer
0.147
316049AB1-081 GEN
Solar/Wind Harmer
2.554
316263AC1-034 GEN
Solar/Wind Harmer
11.125
961601AG1-000A GEN
Solar/Wind Harmer
9.319
316349AD2-085 GEN
Solar/Wind Harmer
2.072
316083AB2-161 GEN
Solar/Wind Harmer
3.461
942751AE2-291 GEN
Solar/Wind Harmer
10.866
316033AB2-134 GEN
Solar/Wind Harmer
5.167
270013AE1-250 PV
Solar/Wind Harmer
2.007
316240AF1-291 C
Solar/Wind Harmer
0.388
316313AB2-026
Solar/Wind Helper
0.534
316045AC1-158 PL2
Solar/Wind Helper
4.257
316450AC1-158 RIC
Solar/Wind Helper
0.355
3143526WINTERP
Solar/Wind Helper
1.193
315243AE2-183_GT3
50/50
5.363
3151051BRUNSWICKS1
50/50
8.78
3151021BRUNSWICKG1
50/50
4.229
971451AH1-221 GEN
50/50
12.843
3151531CLOVER1
50/50
6.014
3144293JTRSVLE
50/50
0.671
3144293JTRSVLE
50/50
0.53
3151591KERR 2
50/50
0.501
3151641KERR 7
50/50
0.501
3147043LAWRENC
50/50
2.31
3151281ROARAP4
50/50
0.274
3151391GASTONA
50/50
0.606
3151411GASTONB
50/50
0.606
941031AE2-094 GEN
Solar/Wind Harmer
70.715
940641AE2-051 GEN
Solar/Wind Harmer
34.508
970919AG2-571 GEN
Solar/Wind Harmer
10.922
970087AG2-069 GEN
Solar/Wind Harmer
31.857
939411AE1-173 GEN
Solar/Wind Harmer
169.831
957481AF2-042 GEN
Solar/Wind Harmer
103.181
315693AD1-088 GEN
Solar/Wind Harmer
16.286
3146926FARMVIL
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.013
971563AH1-280 GEN
Solar/Wind Harmer
3.721
970685AG2-442 GEN
Solar/Wind Harmer
25.864
316034AC1-036 C
Solar/Wind Harmer
0.536
315785AD2-033 C
Solar/Wind Harmer
6.517
316131AB2-060 GEN
Solar/Wind Harmer
3.025
971065AG2-659 GEN
Solar/Wind Harmer
13.518
316129AC1-054 GEN
Solar/Wind Harmer
2.354
960081AF2-299 GEN
Solar/Wind Harmer
2.991
316023GEN1_S
Solar/Wind Harmer
1.781
970401AG2-262 GEN
Solar/Wind Harmer
1.724
316087AB2-174 GEN
Solar/Wind Harmer
3.747
315773AC2-141 GEN
Solar/Wind Harmer
10.899
944591AF1-124 GEN
Solar/Wind Harmer
117.662
3145783HORNRTN
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.572
3146456SLIGO L269
Solar/Wind Harmer
-0.025
319010AE1-072 C
Solar/Wind Harmer
5.101
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.744
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
315611Z1-036_GEN2
Solar/Wind Harmer
6.164
3130156CHOWAN
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.609
316036AC1-147 C
Solar/Wind Harmer
0.67
3150981CHESPKA
Adder
2.766
3145683EARLEYS
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.004
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.279
3145823KELFORD
Solar/Wind Harmer
-0.025
3156021HOLLOMANSOL
Solar/Wind Harmer
3.327
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.187
315737AD1-076 GEN
Solar/Wind Harmer
4.693
316093AE2-104_GEN
Solar/Wind Harmer
7.15
3145963POPLR C
Solar/Wind Harmer
-0.024
316319Z2-044 C
Solar/Wind Harmer
1.326
3146233WITAKRS
Solar/Wind Harmer
-0.095
3146293MARTNCO
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316494AC1-189 GEN
Solar/Wind Harmer
2.559
961671AG1-007 GEN
Solar/Wind Harmer
0.3
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.705
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.192
3142053HEARTS
Solar/Wind Harmer
0.279
316072AD1-144
Solar/Wind Harmer
0.476
3145336SMITFLD
Solar/Wind Harmer
-0.085
316381AD1-082 GEN
Solar/Wind Harmer
1.951
3151171GRAVELC
Adder
1.828
3138126ROCKLANDING
Solar/Wind Harmer
0.056
961611AG1-000B GEN
Solar/Wind Harmer
8.906
971317AH1-138 GEN
Solar/Wind Harmer
2.061
316369SG1_INVT
Solar/Wind Harmer
2.862
971069AG2-661 GEN
Solar/Wind Harmer
2.413
315671AE2-027_GEN
Solar/Wind Harmer
2.578
316132AB2-190 GEN1
Solar/Wind Harmer
1.423
970223AG2-152 GEN
Solar/Wind Harmer
12.166
270016AE1-250 BESS
Solar/Wind Harmer
2.007
3143226MDLTHAN
Solar/Wind Helper
0.35
316447AC1-158 HLD
Solar/Wind Helper
2.927
316044AC1-158 PL1
Solar/Wind Helper
1.33
3143526WINTERP
Solar/Wind Helper
1.193
LAGNLTFEXP_LAGN->PJM
CLTF
9.773
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.451
TVALTFEXP_TVA->PJM
CLTF
4.879
CPLELTFEXP_CPLE->PJM
CLTF
14.696
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.799
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.044
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.621
MECLTFEXP_MEC->PJM
CLTF
4.569
SIGELTFEXP_SIGE->PJM
CLTF
0.136
NYPJM->LTFIMP_NY
CLTF
2.278
LGEELTFEXP_LGEE->PJM
CLTF
1.626
WECLTFEXP_WEC->PJM
CLTF
0.836

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 298_SRT-A-4


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 298_SRT-A-4
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.61 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3336.6
MW Contribution:
9.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
9.474
963041AG1-153 GEN
50/50
8.709
3151541CLOVER2
50/50
6.065
315779AE2-040
50/50
3.569
3151601KERR 3
50/50
0.509
3151611KERR 4
50/50
0.509
3151621KERR 5
50/50
0.509
3151631KERR 6
50/50
0.509
3151281ROARAP4
50/50
0.262
970533AG2-339 GEN
Solar/Wind Harmer
25.805
970673AG2-436 GEN
Solar/Wind Harmer
41.993
971967AH1-528 GEN
Solar/Wind Harmer
52.591
970085AG2-068 GEN
Solar/Wind Harmer
16.403
970581AG2-369 GEN
Solar/Wind Harmer
14.107
971845AH1-439 GEN
Solar/Wind Harmer
12.985
316486AD2-202 GEN
Solar/Wind Harmer
0.29
946301AF1-294 GEN
Solar/Wind Harmer
5.315
961791AG1-021 GEN
Solar/Wind Harmer
2.586
970683AG2-441 GEN
Solar/Wind Harmer
16.022
970681AG2-440 GEN
Solar/Wind Harmer
10.634
3144303KENBRDG
Solar/Wind Harmer
0.209
315814AE2-033 C
Solar/Wind Harmer
20.173
970831AG2-522 GEN
Solar/Wind Harmer
10.363
3137643SOCKMAN
Solar/Wind Harmer
0.942
316426AA2-053 GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
0.232
315652AC1-086 GEN
Solar/Wind Harmer
25.468
957871AF2-081 GEN
Solar/Wind Harmer
11.5
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.123
3146396TANGLEW
Solar/Wind Harmer
0.632
316316AC1-027 C
Solar/Wind Harmer
0.219
3145176PASQUOTANK
Solar/Wind Harmer
0.142
3145796HORNRTN
Solar/Wind Harmer
0.733
3145796HORNRTN
Solar/Wind Harmer
0.092
3146486SUNBURY
Solar/Wind Harmer
0.228
3146486SUNBURY
Solar/Wind Harmer
0.228
3151081ELIZAR1
Adder
20.952
3151091ELIZAR2
Adder
20.588
3145893MURPHYS
Solar/Wind Harmer
0.616
3145893MURPHYS
Solar/Wind Harmer
0.228
3147173SINAI
Solar/Wind Harmer
0.227
3147243WELCO
Solar/Wind Harmer
0.142
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
316463AE2-346 GEN
Solar/Wind Harmer
0.194
3145513AHOSKIE
Solar/Wind Harmer
0.474
3145513AHOSKIE
Solar/Wind Harmer
0.227
3145683EARLEYS
Solar/Wind Harmer
0.453
3145683EARLEYS
Solar/Wind Harmer
0.226
3145683EARLEYS
Solar/Wind Harmer
0.226
3130546PLYMOUTH
Solar/Wind Harmer
0.225
3146206CASHIE
Solar/Wind Harmer
0.225
970601AG2-382 GEN
Solar/Wind Harmer
8.412
315732AD1-074 GEN1
Solar/Wind Harmer
1.284
315733AD1-074 GEN2
Solar/Wind Harmer
1.284
316274AC1-208 GEN
Solar/Wind Harmer
1.159
3146033SCOT NK
Solar/Wind Harmer
0.899
316210AC1-098 GEN
Solar/Wind Harmer
2.073
316327AA2-057 GEN
Solar/Wind Harmer
0.325
3145746EVERETS
Solar/Wind Harmer
0.861
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
957861AF2-080 GEN
Solar/Wind Harmer
9.306
3145573BETHELC
Solar/Wind Harmer
0.215
3145573BETHELC
Solar/Wind Harmer
0.215
316311AC2-079 GEN
Solar/Wind Harmer
6.146
3143316POE
Solar/Wind Harmer
0.802
970657AG2-426 GEN
Solar/Wind Harmer
1.456
971445AH1-216 GEN
Solar/Wind Harmer
13.765
3151201GRAVEL4
Adder
12.976
3151221GRAVEL6
Adder
12.961
3151191GRAVEL3
Adder
12.811
3151211GRAVEL5
Adder
12.811
315697AD1-025 GEN
Solar/Wind Harmer
0.161
3138283WHITEMARSH
Solar/Wind Harmer
0.031
316159AE1-175 C
Solar/Wind Harmer
0.116
316258AE1-075 C
Solar/Wind Helper
0.347
316405AF2-144 C
Solar/Wind Helper
0.289
3151031BRUNSWICKG2
50/50
4.302
970413AG2-270 GEN
50/50
26.618
3144293JTRSVLE
50/50
0.682
3151261ROARAP2
50/50
0.288
3151391GASTONA
50/50
0.619
3151411GASTONB
50/50
0.619
944011AF1-069 GEN
Solar/Wind Harmer
20.553
970917AG2-570 GEN
Solar/Wind Harmer
27.771
3146926FARMVIL
Solar/Wind Harmer
0.172
3146776BUCKING
Solar/Wind Harmer
0.103
972003AH1-546 GEN
Solar/Wind Harmer
9.927
316478AD1-087 GEN
Solar/Wind Harmer
0.986
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.853
959311AF2-222 GEN
Solar/Wind Harmer
23.396
970257AG2-171 GEN
Solar/Wind Harmer
8.388
971775AH1-396 GEN
Solar/Wind Harmer
0.419
964241AG1-285 GEN
Solar/Wind Harmer
17.117
3147043LAWRENC
Solar/Wind Harmer
0.147
316181AB2-040 GEN
Solar/Wind Harmer
0.339
944581AF1-123 GEN
Solar/Wind Harmer
52.976
944601AF1-125 GEN
Solar/Wind Harmer
52.16
316011AB1-132 GEN
Solar/Wind Harmer
4.2
316017AA1-139 ULT1
Solar/Wind Harmer
0.123
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
315243AE2-183_GT3
50/50
5.456
3151051BRUNSWICKS1
50/50
8.931
3151021BRUNSWICKG1
50/50
4.302
971451AH1-221 GEN
50/50
13.064
3151531CLOVER1
50/50
6.112
3144293JTRSVLE
50/50
0.682
3144293JTRSVLE
50/50
0.539
3151591KERR 2
50/50
0.509
3151641KERR 7
50/50
0.509
3147043LAWRENC
50/50
2.356
3151281ROARAP4
50/50
0.28
3151391GASTONA
50/50
0.619
3151411GASTONB
50/50
0.619
941031AE2-094 GEN
Solar/Wind Harmer
62.902
940641AE2-051 GEN
Solar/Wind Harmer
26.697
970919AG2-571 GEN
Solar/Wind Harmer
11.108
939411AE1-173 GEN
Solar/Wind Harmer
131.566
970087AG2-069 GEN
Solar/Wind Harmer
24.605
957481AF2-042 GEN
Solar/Wind Harmer
79.674
315693AD1-088 GEN
Solar/Wind Harmer
14.148
3146926FARMVIL
Solar/Wind Harmer
0.172
3146776BUCKING
Solar/Wind Harmer
0.115
971563AH1-280 GEN
Solar/Wind Harmer
2.873
970685AG2-442 GEN
Solar/Wind Harmer
19.971
316034AC1-036 C
Solar/Wind Harmer
0.017
315785AD2-033 C
Solar/Wind Harmer
2.108
316131AB2-060 GEN
Solar/Wind Harmer
0.791
971065AG2-659 GEN
Solar/Wind Harmer
10.452
316129AC1-054 GEN
Solar/Wind Harmer
0.911
960081AF2-299 GEN
Solar/Wind Harmer
2.32
316023GEN1_S
Solar/Wind Harmer
0.535
970401AG2-262 GEN
Solar/Wind Harmer
1.4
315773AC2-141 GEN
Solar/Wind Harmer
8.676
944591AF1-124 GEN
Solar/Wind Harmer
53.164
3145783HORNRTN
Solar/Wind Harmer
0.232
315607AA1-063A GEN
Solar/Wind Harmer
0.467
3146456SLIGO L269
Solar/Wind Harmer
0.231
319010AE1-072 C
Solar/Wind Harmer
1.151
3145796HORNRTN
Solar/Wind Harmer
0.756
3145796HORNRTN
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.741
3146516WINFALL
Solar/Wind Harmer
0.229
3146263WOODLND
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.913
3145893MURPHYS
Solar/Wind Harmer
1.015
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.04
3150981CHESPKA
Adder
2.841
3146173TUNIS
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
3145683EARLEYS
Solar/Wind Harmer
0.226
315816AE2-034 GEN
Solar/Wind Harmer
0.965
3145663CRESWEL
Solar/Wind Harmer
0.633
971163AH1-040 GEN
Solar/Wind Harmer
18.103
3145823KELFORD
Solar/Wind Harmer
0.225
3156021HOLLOMANSOL
Solar/Wind Harmer
1.014
3146206CASHIE
Solar/Wind Harmer
0.225
971547AH1-271 GEN
Solar/Wind Harmer
4.807
315737AD1-076 GEN
Solar/Wind Harmer
2.89
316093AE2-104_GEN
Solar/Wind Harmer
3.78
3145963POPLR C
Solar/Wind Harmer
0.221
3146293MARTNCO
Solar/Wind Harmer
0.202
3146233WITAKRS
Solar/Wind Harmer
0.866
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
316494AC1-189 GEN
Solar/Wind Harmer
0.729
316072AD1-144
Solar/Wind Harmer
0.077
961671AG1-007 GEN
Solar/Wind Harmer
0.033
3146083TARBORO
Solar/Wind Harmer
0.215
3145493TOT1
Solar/Wind Harmer
0.958
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.765
3142053HEARTS
Solar/Wind Harmer
0.379
3145336SMITFLD
Solar/Wind Harmer
0.789
316381AD1-082 GEN
Solar/Wind Harmer
0.199
3151171GRAVELC
Adder
1.896
3138126ROCKLANDING
Solar/Wind Harmer
0.077
961611AG1-000B GEN
Solar/Wind Harmer
8.768
971317AH1-138 GEN
Solar/Wind Harmer
1.141
971069AG2-661 GEN
Solar/Wind Harmer
2.537
315671AE2-027_GEN
Solar/Wind Harmer
0.001
316132AB2-190 GEN1
Solar/Wind Harmer
0.707
970223AG2-152 GEN
Solar/Wind Harmer
8.528
3143226MDLTHAN
Solar/Wind Helper
0.314
316447AC1-158 HLD
Solar/Wind Helper
2.869
316044AC1-158 PL1
Solar/Wind Helper
1.304
3147666LOUISA
Solar/Wind Helper
0.907
316192AB2-158 GEN
Solar/Wind Helper
1.512
3146456SLIGO L269
Solar/Wind Harmer
0.231
971153AH1-033 GEN
Solar/Wind Harmer
2.668
316321Z2-027
Solar/Wind Harmer
0.041
3145796HORNRTN
Solar/Wind Harmer
0.916
3145796HORNRTN
Solar/Wind Harmer
0.229
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.229
3151101ELIZAR3
Adder
21.22
316246AF1-032 C
Solar/Wind Harmer
0.102
3146263WOODLND
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.382
3145893MURPHYS
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.228
3144873MCLAUGH
Solar/Wind Harmer
0.006
3146173TUNIS
Solar/Wind Harmer
0.227
3146376EDENTON
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.169
3145823KELFORD
Solar/Wind Harmer
0.225
3146206CASHIE
Solar/Wind Harmer
0.225
315735AD1-075 GEN1
Solar/Wind Harmer
0.641
316212AC1-099_GEN
Solar/Wind Harmer
1.156
3145963POPLR C
Solar/Wind Harmer
0.221
315722AD1-056 GEN
Solar/Wind Harmer
7.652
3144536CHRHLND
Solar/Wind Harmer
0.033
3145933PARMELE
Solar/Wind Harmer
0.218
3146233WITAKRS
Solar/Wind Harmer
1.093
3146233WITAKRS
Solar/Wind Harmer
0.148
3138543CONSLDL
Solar/Wind Harmer
0.143
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
3146073TAR RVR
Solar/Wind Harmer
0.215
3146083TARBORO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
971623AH1-311 GEN
Solar/Wind Harmer
0.43
961601AG1-000A GEN
Solar/Wind Harmer
15.286
316222AC1-221 GEN
Solar/Wind Harmer
0.83
316283AC2-100 C
Solar/Wind Harmer
0.392
971683AH1-343 GEN
Solar/Wind Harmer
7.339
970657AG2-426 GEN
Solar/Wind Harmer
4.45
3145336SMITFLD
Solar/Wind Harmer
0.079
315813AE1-149 C
Solar/Wind Harmer
9.892
3151171GRAVELC
Adder
2.494
3144216WINCHST
Adder
0.635
961611AG1-000B GEN
Solar/Wind Harmer
4.458
316123AC1-075 GEN
Solar/Wind Harmer
0.223
3150921YORKTN3
Adder
4.193
315778AD1-151 GEN
Solar/Wind Harmer
11.415
316458AB2-190 GEN2
Solar/Wind Harmer
0.707
970133AG2-095 GEN
Solar/Wind Harmer
1.1
3147666LOUISA
Solar/Wind Helper
0.521
315242AE2-183_GT2
50/50
5.456
315241AE2-183_GT1
50/50
5.441
972185AH1-677 GEN
50/50
19.722
3151041BRUNSWICKG3
50/50
4.302
972187AH1-678 GEN
50/50
9.87
970909AG2-566 GEN
50/50
3.093
3144293JTRSVLE
50/50
0.682
970535AG2-341 GEN
50/50
4.471
3151581KERR 1
50/50
0.182
3151261ROARAP2
50/50
0.281
3152661PLYWOOD A
50/50
0.515
3151361ROSEMG1
50/50
0.826
3151371ROSEMS1
50/50
0.511
3151381ROSEMG2
50/50
0.386
970933AG2-581 GEN
Solar/Wind Harmer
25.738
970099AG2-077 GEN
Solar/Wind Harmer
31.87
970301AG2-198 GEN
Solar/Wind Harmer
12.373
3146776BUCKING
Solar/Wind Harmer
1.145
3146776BUCKING
Solar/Wind Harmer
0.093
3147133PAMPLIN
Solar/Wind Harmer
0.272
3147133PAMPLIN
Solar/Wind Harmer
0.217
958211AF2-115 GEN
Solar/Wind Harmer
3.232
970323AG2-213 GEN
Solar/Wind Harmer
11.184
3144356SAPONY
Solar/Wind Harmer
2.139
316315AB2-025 C
Solar/Wind Harmer
0.205
316365GEN2_N
Solar/Wind Harmer
0.535
962561AG1-105 GEN
Solar/Wind Harmer
11.564
964791AG1-342 GEN
Solar/Wind Harmer
4.581
3146843MT LREL
Solar/Wind Harmer
0.238
3146843MT LREL
Solar/Wind Harmer
0.238
316294AC1-161 GEN
Solar/Wind Harmer
4.107
313506AB2-031 GEN
Solar/Wind Harmer
0.73
3145593CAROLNA
Solar/Wind Harmer
0.234
3145593CAROLNA
Solar/Wind Harmer
0.234
3145593CAROLNA
Solar/Wind Harmer
0.291
316118AC1-105 GEN
Solar/Wind Harmer
0.597
3145783HORNRTN
Solar/Wind Harmer
4.134
3145783HORNRTN
Solar/Wind Harmer
3.307
3145783HORNRTN
Solar/Wind Harmer
1.033
3145783HORNRTN
Solar/Wind Harmer
0.413
962571AG1-106 GEN
Solar/Wind Harmer
3.294
3145506HICKORY
Solar/Wind Harmer
0.925
3145506HICKORY
Solar/Wind Harmer
0.555
3145506HICKORY
Solar/Wind Harmer
0.139
316339AD2-160 GEN
Solar/Wind Harmer
0.37
316388AE2-253 GEN
Solar/Wind Harmer
0.719
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
3142666NORTHAMPTON
Solar/Wind Harmer
0.139
3137176SLIGO L2192
Solar/Wind Harmer
0.918
3146456SLIGO L269
Solar/Wind Harmer
4.084
3130086AYDLETT
Solar/Wind Harmer
0.922
3146386ELIZ CT
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.687
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3145893MURPHYS
Solar/Wind Harmer
1.528
3145893MURPHYS
Solar/Wind Harmer
0.411
3146626S HERTFORD
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.228
3150991CHESPKB
Adder
2.383
3150991CHESPKB
Adder
2.326
3146173TUNIS
Solar/Wind Harmer
0.227
3146173TUNIS
Solar/Wind Harmer
0.227
3146376EDENTON
Solar/Wind Harmer
1.01
3146376EDENTON
Solar/Wind Harmer
1.01
316140AB2-099
Solar/Wind Harmer
0.081
315742AE1-103 GEN
Solar/Wind Harmer
3.386
315614AA2-178 GEN
Solar/Wind Harmer
1.287
316065AD1-022 GEN
Solar/Wind Harmer
10.374
315835AF2-110_GEN
Solar/Wind Harmer
1.542
315724AD1-057 GEN
Solar/Wind Harmer
4.269
3145933PARMELE
Solar/Wind Harmer
0.436
3145933PARMELE
Solar/Wind Harmer
0.218
316005AA1-067
Solar/Wind Harmer
0.231
3145493TOT1
Solar/Wind Harmer
0.499
3145453TOT5
Solar/Wind Harmer
0.3
3145603CNETO
Solar/Wind Harmer
0.2
316049AB1-081 GEN
Solar/Wind Harmer
1.224
316263AC1-034 GEN
Solar/Wind Harmer
8.177
961601AG1-000A GEN
Solar/Wind Harmer
3.821
316349AD2-085 GEN
Solar/Wind Harmer
0.143
942751AE2-291 GEN
Solar/Wind Harmer
8.254
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316313AB2-026
Solar/Wind Helper
0.386
316045AC1-158 PL2
Solar/Wind Helper
4.173
316450AC1-158 RIC
Solar/Wind Helper
0.348
LAGNLTFEXP_LAGN->PJM
CLTF
9.765
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.758
TVALTFEXP_TVA->PJM
CLTF
4.87
CPLELTFEXP_CPLE->PJM
CLTF
14.89
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.544
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.5
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.568
MECLTFEXP_MEC->PJM
CLTF
4.516
SIGELTFEXP_SIGE->PJM
CLTF
0.134
NYPJM->LTFIMP_NY
CLTF
2.256
LGEELTFEXP_LGEE->PJM
CLTF
1.597
WECLTFEXP_WEC->PJM
CLTF
0.821

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.54 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4865.39
MW Contribution:
5.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971507AH1-251 GEN
50/50
17.357
3152251N ANNA1
50/50
14.386
972197AH1-683 GEN
50/50
5.811
972219AH1-694 GEN
50/50
4.184
315052AA1-145 CT2
50/50
2.037
316447AC1-158 HLD
Solar/Wind Harmer
3.325
316044AC1-158 PL1
Solar/Wind Harmer
1.512
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.647
3142416OLDCHRC
Solar/Wind Harmer
0.248
3143526WINTERP
Solar/Wind Harmer
1.272
3143096IRON208
Adder
1.024
3150851SPRUNCC
Adder
1.126
3143226MDLTHAN
Solar/Wind Harmer
0.244
3142543TWELFTH
Solar/Wind Harmer
0.023
315975AC1-164 GENB
Solar/Wind Harmer
0.076
944631AF1-128 GEN
Adder
115.543
316132AB2-190 GEN1
Solar/Wind Harmer
1.272
315671AE2-027_GEN
Solar/Wind Harmer
0.002
971069AG2-661 GEN
Solar/Wind Harmer
4.226
971317AH1-138 GEN
Solar/Wind Harmer
1.763
3138126ROCKLANDING
Solar/Wind Harmer
0.108
3142433PROV 92
Solar/Wind Harmer
0.943
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
12.373
315773AC2-141 GEN
Solar/Wind Harmer
8.57
3151171GRAVELC
Adder
2.502
3145336SMITFLD
Solar/Wind Harmer
0.936
944591AF1-124 GEN
Solar/Wind Harmer
52.511
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.041
3150981CHESPKA
Adder
2.901
316381AD1-082 GEN
Solar/Wind Harmer
0.236
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.611
316072AD1-144
Solar/Wind Harmer
0.082
939411AE1-173 GEN
Solar/Wind Harmer
98.409
940641AE2-051 GEN
Solar/Wind Harmer
18.429
3146456SLIGO L269
Solar/Wind Harmer
0.229
319010AE1-072 C
Solar/Wind Harmer
1.144
316093AE2-104_GEN
Solar/Wind Harmer
3.834
3138133OCRAN
Solar/Wind Harmer
0.136
3146516WINFALL
Solar/Wind Harmer
0.726
3146516WINFALL
Solar/Wind Harmer
0.224
941031AE2-094 GEN
Solar/Wind Harmer
40.872
3130156CHOWAN
Solar/Wind Harmer
0.218
962861AG1-135 GEN
Solar/Wind Harmer
6.968
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.175
3141726DUNNSVL
Solar/Wind Harmer
0.858
315816AE2-034 GEN
Solar/Wind Harmer
0.909
3145663CRESWEL
Solar/Wind Harmer
0.596
971163AH1-040 GEN
Solar/Wind Harmer
17.043
3150351NORNECKC2
Adder
2.111
3143336POWHATN
Solar/Wind Harmer
3.743
315737AD1-076 GEN
Solar/Wind Harmer
2.675
970919AG2-571 GEN
Solar/Wind Harmer
7.345
3146206CASHIE
Solar/Wind Harmer
0.206
971547AH1-271 GEN
Solar/Wind Harmer
4.402
316023GEN1_S
Solar/Wind Harmer
0.458
3145893MURPHYS
Solar/Wind Harmer
0.822
3145893MURPHYS
Solar/Wind Harmer
0.913
970087AG2-069 GEN
Solar/Wind Harmer
16.324
971531AH1-263 GEN
50/50
86.339
3150411LDYSMT5
50/50
37.33
3150381LDYSMT2
50/50
35.726
972213AH1-691 GEN
50/50
6.043
972215AH1-692 GEN
50/50
6.043
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971281AH1-106 GEN
Solar/Wind Harmer
3.394
971283AH1-107 GEN
Solar/Wind Harmer
3.394
971285AH1-108 GEN
Adder
1.842
316164AC1-076 GEN
Solar/Wind Harmer
0.334
316159AE1-175 C
Solar/Wind Harmer
0.204
315697AD1-025 GEN
Solar/Wind Harmer
0.255
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3151201GRAVEL4
Adder
17.117
3151221GRAVEL6
Adder
17.097
3152261N ANNA2
50/50
14.393
3150401LDYSMT4
50/50
37.213
3150371LDYSMT1
50/50
35.958
315051AA1-145 CT1
50/50
2.024
3142416OLDCHRC
Solar/Wind Harmer
2.412
970293AG2-193 GEN
Solar/Wind Harmer
2.622
316075AC2-137 C
Solar/Wind Harmer
0.065
3143096IRON208
Adder
1.024
3143096IRON208
Adder
1.003
3150861SPRUNCD
Adder
1.126
316473AC1-191 GEN
Solar/Wind Harmer
0.821
3142946ENON
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
2.301
316458AB2-190 GEN2
Solar/Wind Harmer
1.272
315778AD1-151 GEN
Solar/Wind Harmer
19.016
3150921YORKTN3
Adder
5.932
3144216WINCHST
Adder
0.89
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
6.292
3151171GRAVELC
Adder
3.289
3145336SMITFLD
Solar/Wind Harmer
0.094
315813AE1-149 C
Solar/Wind Harmer
12.487
3144536CHRHLND
Solar/Wind Harmer
0.035
944581AF1-123 GEN
Solar/Wind Harmer
52.325
944601AF1-125 GEN
Solar/Wind Harmer
51.52
3151101ELIZAR3
Adder
21.578
3144873MCLAUGH
Solar/Wind Harmer
0.006
970657AG2-426 GEN
Solar/Wind Harmer
5.208
3141766HARMONY
Solar/Wind Harmer
3.088
3141843SHACKLE
Adder
1.183
316203AE2-005 GEN
Solar/Wind Harmer
0
316017AA1-139 ULT1
Solar/Wind Harmer
0.123
3141873WAN 176
Solar/Wind Harmer
4.085
3146456SLIGO L269
Solar/Wind Harmer
0.229
971153AH1-033 GEN
Solar/Wind Harmer
2.653
316246AF1-032 C
Solar/Wind Harmer
0.102
316321Z2-027
Solar/Wind Harmer
0.04
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.222
3145273HOLLAND
Solar/Wind Harmer
0.166
944011AF1-069 GEN
Solar/Wind Harmer
13.354
3146376EDENTON
Solar/Wind Harmer
0.218
3150351NORNECKC2
Adder
2.146
971781AH1-399 GEN
Solar/Wind Harmer
0.278
3143336POWHATN
Solar/Wind Harmer
3.181
315735AD1-075 GEN1
Solar/Wind Harmer
0.593
3156081AA2-088 GEN
Solar/Wind Harmer
0
970917AG2-570 GEN
Solar/Wind Harmer
18.362
3146206CASHIE
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
0.344
3145893MURPHYS
Solar/Wind Harmer
0.205
3146173TUNIS
Solar/Wind Harmer
0.203
3147666LOUISA
Solar/Wind Harmer
0.462
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.198
3151191GRAVEL3
Adder
16.9
3151211GRAVEL5
Adder
16.9
971445AH1-216 GEN
Solar/Wind Harmer
16.491
3143316POE
Solar/Wind Harmer
0.926
3143873LANEXA
Solar/Wind Harmer
0.14
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3151081ELIZAR1
Adder
21.305
3151091ELIZAR2
Adder
20.935
970657AG2-426 GEN
Solar/Wind Harmer
1.704
316316AC1-027 C
Solar/Wind Harmer
0.221
970189AG2-124 GEN
Solar/Wind Harmer
6.859
957871AF2-081 GEN
Solar/Wind Harmer
11.449
3141873WAN 176
Solar/Wind Harmer
0.046
316311AC2-079 GEN
Solar/Wind Harmer
6.594
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.121
3141913WHIT STONE
Solar/Wind Harmer
0.227
3146486SUNBURY
Solar/Wind Harmer
0.226
3146486SUNBURY
Solar/Wind Harmer
0.226
3138133OCRAN
Solar/Wind Harmer
0.068
3146396TANGLEW
Solar/Wind Harmer
0.623
3145176PASQUOTANK
Solar/Wind Harmer
0.14
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
970533AG2-339 GEN
Solar/Wind Harmer
16.767
315814AE2-033 C
Solar/Wind Harmer
17.519
970673AG2-436 GEN
Solar/Wind Harmer
27.344
3130156CHOWAN
Solar/Wind Harmer
0.218
3130156CHOWAN
Solar/Wind Harmer
0.218
971967AH1-528 GEN
Solar/Wind Harmer
34.357
3141813NORNECK
Solar/Wind Harmer
0.212
316258AE1-075 C
Solar/Wind Harmer
0.157
3130546PLYMOUTH
Solar/Wind Harmer
0.209
315732AD1-074 GEN1
Solar/Wind Harmer
1.188
315733AD1-074 GEN2
Solar/Wind Harmer
1.188
3146206CASHIE
Solar/Wind Harmer
0.206
970601AG2-382 GEN
Solar/Wind Harmer
7.704
3145893MURPHYS
Solar/Wind Harmer
0.555
3145893MURPHYS
Solar/Wind Harmer
0.205
970085AG2-068 GEN
Solar/Wind Harmer
10.883
970581AG2-369 GEN
Solar/Wind Harmer
9.359
316463AE2-346 GEN
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
0.423
3145513AHOSKIE
Solar/Wind Harmer
0.202
3145683EARLEYS
Solar/Wind Harmer
0.403
3145683EARLEYS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.201
3146043SEABORD
Solar/Wind Harmer
0.201
315652AC1-086 GEN
Solar/Wind Harmer
21.728
3137643SOCKMAN
Solar/Wind Harmer
0.787
316426AA2-053 GEN
Solar/Wind Harmer
0.658
3145796HORNRTN
Solar/Wind Harmer
0.622
3145796HORNRTN
Solar/Wind Harmer
0.078
3146033SCOT NK
Solar/Wind Harmer
0.773
316486AD2-202 GEN
Solar/Wind Harmer
0.194
316210AC1-098 GEN
Solar/Wind Harmer
1.756
316274AC1-208 GEN
Solar/Wind Harmer
0.972
970831AG2-522 GEN
Solar/Wind Harmer
7.993
3145746EVERETS
Solar/Wind Harmer
0.739
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
316327AA2-057 GEN
Solar/Wind Harmer
0.27
957861AF2-080 GEN
Solar/Wind Harmer
7.87
3145573BETHELC
Solar/Wind Harmer
0.18
3145573BETHELC
Solar/Wind Harmer
0.18
3144303KENBRDG
Solar/Wind Harmer
0.143
970683AG2-441 GEN
Solar/Wind Harmer
10.744
970681AG2-440 GEN
Solar/Wind Harmer
7.131
946301AF1-294 GEN
Solar/Wind Harmer
3.51
961791AG1-021 GEN
Solar/Wind Harmer
1.708
944491AF1-114 GEN
Solar/Wind Harmer
0
971845AH1-439 GEN
Solar/Wind Harmer
7.683
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.102
972205AH1-687 GEN
Adder
6.848
3147346CASHSCORNER
Solar/Wind Harmer
0.277
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138216PACIFIC
Solar/Wind Helper
0.039
316181AB2-040 GEN
Solar/Wind Harmer
0.282
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
316011AB1-132 GEN
Solar/Wind Harmer
3.583
3145823KELFORD
Solar/Wind Harmer
0.197
3145796HORNRTN
Solar/Wind Harmer
0.778
3145796HORNRTN
Solar/Wind Harmer
0.194
3147043LAWRENC
Solar/Wind Harmer
0.117
316223AC1-118
Solar/Wind Harmer
0.137
3141906WESTMOR
Solar/Wind Harmer
0.077
316478AD1-087 GEN
Solar/Wind Harmer
0.661
316212AC1-099_GEN
Solar/Wind Harmer
0.98
3145933PARMELE
Solar/Wind Harmer
0.19
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
315722AD1-056 GEN
Solar/Wind Harmer
6.378
3146073TAR RVR
Solar/Wind Harmer
0.18
3146083TARBORO
Solar/Wind Harmer
0.18
3146233WITAKRS
Solar/Wind Harmer
0.902
3146233WITAKRS
Solar/Wind Harmer
0.122
3138543CONSLDL
Solar/Wind Harmer
0.118
964241AG1-285 GEN
Solar/Wind Harmer
11.954
970257AG2-171 GEN
Solar/Wind Harmer
5.718
971775AH1-396 GEN
Solar/Wind Harmer
0.286
959311AF2-222 GEN
Solar/Wind Harmer
15.874
3144293JTRSVLE
Adder
0.425
3147133PAMPLIN
Solar/Wind Harmer
0.557
942461AE2-259 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
12.548
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.176
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3146926FARMVIL
Solar/Wind Harmer
0.106
3146776BUCKING
Solar/Wind Harmer
0.061
972255AH1-712 GEN
Adder
84.292
972003AH1-546 GEN
Solar/Wind Harmer
5.592
970221AG2-151 GEN
Solar/Wind Harmer
8.049
971683AH1-343 GEN
Solar/Wind Harmer
5.518
316222AC1-221 GEN
Solar/Wind Harmer
0.612
316283AC2-100 C
Solar/Wind Harmer
0.289
3132273ORANGE
Solar/Wind Harmer
0.028
316123AC1-075 GEN
Solar/Wind Harmer
0.179
270494AE1-108_GEN
Solar/Wind Harmer
1.598
315821AE2-092 GEN
Solar/Wind Harmer
0
3150331BIRCHWDA
Adder
21.248
3151761LOISA E
Adder
16.344
3151721LOISA A
Adder
7.975
3141196NOKESVL
Solar/Wind Helper
1.254
3146173TUNIS
Solar/Wind Harmer
0.203
3156021HOLLOMANSOL
Solar/Wind Harmer
0.914
316337AD2-073 GEN
Solar/Wind Harmer
0.175
3145683EARLEYS
Solar/Wind Harmer
0.201
3147666LOUISA
Solar/Wind Harmer
0.803
960081AF2-299 GEN
Solar/Wind Harmer
1.925
315607AA1-063A GEN
Solar/Wind Harmer
0.403
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.198
957481AF2-042 GEN
Solar/Wind Harmer
52.774
3145823KELFORD
Solar/Wind Harmer
0.197
316192AB2-158 GEN
Solar/Wind Harmer
1.103
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.641
3145796HORNRTN
Solar/Wind Harmer
0.194
315693AD1-088 GEN
Solar/Wind Harmer
9.325
3147043LAWRENC
Adder
1.757
3146293MARTNCO
Solar/Wind Harmer
0.176
316129AC1-054 GEN
Solar/Wind Harmer
0.695
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
971065AG2-659 GEN
Solar/Wind Harmer
7.908
316494AC1-189 GEN
Solar/Wind Harmer
0.617
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.18
3145493TOT1
Solar/Wind Harmer
0.799
3146233WITAKRS
Solar/Wind Harmer
0.715
316131AB2-060 GEN
Solar/Wind Harmer
0.559
970937AG2-583 GEN
Solar/Wind Harmer
10.998
315785AD2-033 C
Solar/Wind Harmer
1.446
316034AC1-036 C
Solar/Wind Harmer
0.012
970685AG2-442 GEN
Solar/Wind Harmer
13.298
972135AH1-637 GEN
Solar/Wind Harmer
1.52
971563AH1-280 GEN
Solar/Wind Harmer
1.897
3144293JTRSVLE
Adder
0.425
3144293JTRSVLE
Adder
0.335
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.141
316359AB2-059 GEN
Solar/Wind Harmer
0.627
3142053HEARTS
Solar/Wind Harmer
0.311
3146926FARMVIL
Solar/Wind Harmer
0.106
970401AG2-262 GEN
Solar/Wind Harmer
0.999
3146776BUCKING
Solar/Wind Harmer
0.068
972277AH1-723 GEN
Adder
98.225
971377AH1-170 GEN
Solar/Wind Harmer
1.61
3147623JAMES R
Solar/Wind Harmer
0.35
3151751LOISA D
Adder
8.017
316254AC1-120 GEN1
Solar/Wind Harmer
4.309
316170AC1-121 GEN2
Solar/Wind Harmer
1.48
316415AF1-147_GEN2
Solar/Wind Helper
0.811
3150391LDYSMT3
50/50
37.144
972195AH1-682 GEN
50/50
4.881
972189AH1-679 GEN
50/50
4.546
3142296MT RD221
50/50
0.852
3142366NRTHEST
50/50
0.857
316045AC1-158 PL2
Solar/Wind Harmer
4.839
316450AC1-158 RIC
Solar/Wind Harmer
0.403
315673AE1-157 GEN
Solar/Wind Harmer
17.965
316312AB1-027
Solar/Wind Harmer
0.443
3150691DARBY 3
Adder
17.755
3150701DARBY 4
Adder
17.714
3150681DARBY 2
Adder
17.693
3150671DARBY 1
Adder
17.672
3143526WINTERP
Solar/Wind Harmer
1.272
971223AH1-071 GEN
Solar/Wind Harmer
2.602
966871AG1-558 GEN
Solar/Wind Harmer
0.281
315976AC1-164 GENA
Solar/Wind Harmer
2.554
316169AC1-164_GENC
Solar/Wind Harmer
2.207
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
114.524
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
4.056
3150991CHESPKB
Adder
2.434
3150991CHESPKB
Adder
2.375
3145506HICKORY
Solar/Wind Harmer
0.924
3145506HICKORY
Solar/Wind Harmer
0.554
3145506HICKORY
Solar/Wind Harmer
0.139
316339AD2-160 GEN
Solar/Wind Harmer
0.368
316388AE2-253 GEN
Solar/Wind Harmer
0.716
316156AD2-030 GEN
Solar/Wind Harmer
0.168
316349AD2-085 GEN
Solar/Wind Harmer
0.153
3137176SLIGO L2192
Solar/Wind Harmer
0.913
3146456SLIGO L269
Solar/Wind Harmer
4.061
3130086AYDLETT
Solar/Wind Harmer
0.916
315835AF2-110_GEN
Solar/Wind Harmer
1.564
3146386ELIZ CT
Solar/Wind Harmer
0.227
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.222
3146626S HERTFORD
Solar/Wind Harmer
0.222
3144356SAPONY
Solar/Wind Harmer
1.859
316315AB2-025 C
Solar/Wind Harmer
0.178
315742AE1-103 GEN
Solar/Wind Harmer
3.271
3146376EDENTON
Solar/Wind Harmer
0.969
3146376EDENTON
Solar/Wind Harmer
0.969
972185AH1-677 GEN
Adder
12.144
972187AH1-678 GEN
Adder
6.093
315614AA2-178 GEN
Solar/Wind Harmer
1.212
3150341NORNECKC1
Adder
2.217
3150341NORNECKC1
Adder
2.199
970933AG2-581 GEN
Solar/Wind Harmer
16.86
316313AB2-026
Solar/Wind Harmer
0.131
316065AD1-022 GEN
Solar/Wind Harmer
9.539
316365GEN2_N
Solar/Wind Harmer
0.458
3145893MURPHYS
Solar/Wind Harmer
1.375
3145893MURPHYS
Solar/Wind Harmer
0.37
3146173TUNIS
Solar/Wind Harmer
0.203
3146173TUNIS
Solar/Wind Harmer
0.203
316140AB2-099
Solar/Wind Harmer
0.072
316336AC2-165 C
Solar/Wind Harmer
10.224
313506AB2-031 GEN
Solar/Wind Harmer
0.608
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970099AG2-077 GEN
Solar/Wind Harmer
21.11
962571AG1-106 GEN
Solar/Wind Harmer
2.81
3145593CAROLNA
Solar/Wind Harmer
0.196
3145593CAROLNA
Solar/Wind Harmer
0.196
3145593CAROLNA
Solar/Wind Harmer
0.244
3145783HORNRTN
Solar/Wind Harmer
3.462
3145783HORNRTN
Solar/Wind Harmer
2.769
3145783HORNRTN
Solar/Wind Harmer
0.865
3145783HORNRTN
Solar/Wind Harmer
0.346
3145796HORNRTN
Solar/Wind Harmer
0.583
3145933PARMELE
Solar/Wind Harmer
0.379
3145933PARMELE
Solar/Wind Harmer
0.19
316005AA1-067
Solar/Wind Harmer
0.198
315724AD1-057 GEN
Solar/Wind Harmer
3.558
970301AG2-198 GEN
Solar/Wind Harmer
7.839
3145493TOT1
Solar/Wind Harmer
0.417
3145453TOT5
Solar/Wind Harmer
0.25
3145603CNETO
Solar/Wind Harmer
0.167
970323AG2-213 GEN
Solar/Wind Harmer
7.624
958211AF2-115 GEN
Solar/Wind Harmer
2.135
3144293JTRSVLE
Adder
0.425
3147133PAMPLIN
Solar/Wind Harmer
0.177
3147133PAMPLIN
Solar/Wind Harmer
0.142
961601AG1-000A GEN
Solar/Wind Harmer
3.137
316049AB1-081 GEN
Solar/Wind Harmer
1.003
316263AC1-034 GEN
Solar/Wind Harmer
6.702
962561AG1-105 GEN
Solar/Wind Harmer
8.245
964791AG1-342 GEN
Solar/Wind Harmer
3.271
3146843MT LREL
Solar/Wind Harmer
0.17
3146843MT LREL
Solar/Wind Harmer
0.17
3146776BUCKING
Solar/Wind Harmer
0.675
3146776BUCKING
Solar/Wind Harmer
0.055
316118AC1-105 GEN
Solar/Wind Harmer
0.427
972193AH1-681 GEN
Adder
3.766
942751AE2-291 GEN
Solar/Wind Harmer
6.895
966001AG1-469 GEN
Solar/Wind Harmer
0.072
3151731LOISA B
Adder
8.017
316411AF1-147_GEN1
Solar/Wind Helper
0.811
LAGNLTFEXP_LAGN->PJM
CLTF
7.995
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.949
TVALTFEXP_TVA->PJM
CLTF
4.055
CPLELTFEXP_CPLE->PJM
CLTF
11.373
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.232
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.187
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.788
MECLTFEXP_MEC->PJM
CLTF
3.599
SIGELTFEXP_SIGE->PJM
CLTF
0.11
NYPJM->LTFIMP_NY
CLTF
3.271
LGEELTFEXP_LGEE->PJM
CLTF
1.325
WECLTFEXP_WEC->PJM
CLTF
0.638

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.04 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4600.84
MW Contribution:
5.44
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
73.133
3150411LDYSMT5
50/50
36.944
3150381LDYSMT2
50/50
35.357
972213AH1-691 GEN
50/50
5.981
972215AH1-692 GEN
50/50
5.981
316233AE1-074 FULL
Solar/Wind Harmer
0.193
971281AH1-106 GEN
Solar/Wind Harmer
3.346
971283AH1-107 GEN
Solar/Wind Harmer
3.346
971285AH1-108 GEN
Adder
1.817
316159AE1-175 C
Solar/Wind Harmer
0.201
315697AD1-025 GEN
Solar/Wind Harmer
0.252
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
3151201GRAVEL4
Adder
16.892
3151221GRAVEL6
Adder
16.873
3151191GRAVEL3
Adder
16.678
3151211GRAVEL5
Adder
16.678
971445AH1-216 GEN
Solar/Wind Harmer
16.274
3143316POE
Solar/Wind Harmer
0.914
3143873LANEXA
Solar/Wind Harmer
0.139
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3151081ELIZAR1
Adder
21.023
3152261N ANNA2
50/50
14.183
3150401LDYSMT4
50/50
36.829
3150371LDYSMT1
50/50
35.587
315051AA1-145 CT1
50/50
2
3142416OLDCHRC
Solar/Wind Harmer
2.382
970293AG2-193 GEN
Solar/Wind Harmer
2.588
316075AC2-137 C
Solar/Wind Harmer
0.064
3143096IRON208
Adder
1.01
3143096IRON208
Adder
0.99
3150861SPRUNCD
Adder
1.11
316473AC1-191 GEN
Solar/Wind Harmer
0.811
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.271
316458AB2-190 GEN2
Solar/Wind Harmer
1.255
315778AD1-151 GEN
Solar/Wind Harmer
18.767
3150921YORKTN3
Adder
5.855
3144216WINCHST
Adder
0.878
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
6.209
3151171GRAVELC
Adder
3.246
3145336SMITFLD
Solar/Wind Harmer
0.092
315813AE1-149 C
Solar/Wind Harmer
12.322
3144536CHRHLND
Solar/Wind Harmer
0.034
944581AF1-123 GEN
Solar/Wind Harmer
51.631
944601AF1-125 GEN
Solar/Wind Harmer
50.836
3151101ELIZAR3
Adder
21.292
3144873MCLAUGH
Solar/Wind Harmer
0.006
970657AG2-426 GEN
Solar/Wind Harmer
5.139
3141766HARMONY
Solar/Wind Harmer
3.05
3141843SHACKLE
Adder
1.168
316203AE2-005 GEN
Solar/Wind Harmer
0
316017AA1-139 ULT1
Solar/Wind Harmer
0.121
3141873WAN 176
Solar/Wind Harmer
4.033
3146456SLIGO L269
Solar/Wind Harmer
0.226
971153AH1-033 GEN
Solar/Wind Harmer
2.618
316246AF1-032 C
Solar/Wind Harmer
0.101
316321Z2-027
Solar/Wind Harmer
0.04
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.219
3145273HOLLAND
Solar/Wind Harmer
0.164
944011AF1-069 GEN
Solar/Wind Harmer
13.17
3146376EDENTON
Solar/Wind Harmer
0.215
3150351NORNECKC2
Adder
2.121
971781AH1-399 GEN
Solar/Wind Harmer
0.275
3143336POWHATN
Solar/Wind Harmer
3.122
315735AD1-075 GEN1
Solar/Wind Harmer
0.585
3156081AA2-088 GEN
Solar/Wind Harmer
0
970917AG2-570 GEN
Solar/Wind Harmer
18.109
3146206CASHIE
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.339
3145893MURPHYS
Solar/Wind Harmer
0.203
3146173TUNIS
Solar/Wind Harmer
0.201
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
316181AB2-040 GEN
Solar/Wind Harmer
0.278
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
316011AB1-132 GEN
Solar/Wind Harmer
3.535
3145823KELFORD
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.767
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Solar/Wind Harmer
0.115
316223AC1-118
Solar/Wind Harmer
0.136
3141906WESTMOR
Solar/Wind Harmer
0.076
3147666LOUISA
Solar/Wind Harmer
0.435
316478AD1-087 GEN
Solar/Wind Harmer
0.651
316212AC1-099_GEN
Solar/Wind Harmer
0.966
3145933PARMELE
Solar/Wind Harmer
0.187
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
315722AD1-056 GEN
Solar/Wind Harmer
6.293
3146073TAR RVR
Solar/Wind Harmer
0.177
3146083TARBORO
Solar/Wind Harmer
0.177
3146233WITAKRS
Solar/Wind Harmer
0.89
3146233WITAKRS
Solar/Wind Harmer
0.121
3138543CONSLDL
Solar/Wind Harmer
0.117
964241AG1-285 GEN
Solar/Wind Harmer
11.761
970257AG2-171 GEN
Solar/Wind Harmer
5.621
971775AH1-396 GEN
Solar/Wind Harmer
0.281
959311AF2-222 GEN
Solar/Wind Harmer
15.601
3144293JTRSVLE
Adder
0.417
3147133PAMPLIN
Solar/Wind Harmer
0.547
961601AG1-000A GEN
Solar/Wind Harmer
12.382
3145543BTLEBRO
Solar/Wind Harmer
0.174
3152251N ANNA1
50/50
14.176
972197AH1-683 GEN
50/50
5.751
972219AH1-694 GEN
50/50
4.141
315052AA1-145 CT2
50/50
2.012
966881AG1-559 GEN
Solar/Wind Harmer
0.296
3142416OLDCHRC
Solar/Wind Harmer
0.639
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143526WINTERP
Solar/Wind Harmer
1.254
3143096IRON208
Adder
1.01
3150851SPRUNCC
Adder
1.11
3142543TWELFTH
Solar/Wind Harmer
0.023
3143226MDLTHAN
Solar/Wind Harmer
0.24
315975AC1-164 GENB
Solar/Wind Harmer
0.075
944631AF1-128 GEN
Adder
114.046
316132AB2-190 GEN1
Solar/Wind Harmer
1.255
315671AE2-027_GEN
Solar/Wind Harmer
0.002
971069AG2-661 GEN
Solar/Wind Harmer
4.17
971317AH1-138 GEN
Solar/Wind Harmer
1.74
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3142433PROV 92
Solar/Wind Harmer
0.931
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
12.211
315773AC2-141 GEN
Solar/Wind Harmer
8.457
3151171GRAVELC
Adder
2.469
3145336SMITFLD
Solar/Wind Harmer
0.924
944591AF1-124 GEN
Solar/Wind Harmer
51.815
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.041
3150981CHESPKA
Adder
2.863
316381AD1-082 GEN
Solar/Wind Harmer
0.232
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.603
316072AD1-144
Solar/Wind Harmer
0.081
939411AE1-173 GEN
Solar/Wind Harmer
97.075
940641AE2-051 GEN
Solar/Wind Harmer
18.178
3146456SLIGO L269
Solar/Wind Harmer
0.226
319010AE1-072 C
Solar/Wind Harmer
1.128
316093AE2-104_GEN
Solar/Wind Harmer
3.783
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.716
3146516WINFALL
Solar/Wind Harmer
0.221
941031AE2-094 GEN
Solar/Wind Harmer
40.308
962861AG1-135 GEN
Solar/Wind Harmer
6.884
3130156CHOWAN
Solar/Wind Harmer
0.215
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.088
3141726DUNNSVL
Solar/Wind Harmer
0.847
315816AE2-034 GEN
Solar/Wind Harmer
0.897
3145663CRESWEL
Solar/Wind Harmer
0.588
971163AH1-040 GEN
Solar/Wind Harmer
16.816
3150351NORNECKC2
Adder
2.086
3143336POWHATN
Solar/Wind Harmer
3.673
315737AD1-076 GEN
Solar/Wind Harmer
2.64
970919AG2-571 GEN
Solar/Wind Harmer
7.244
3146206CASHIE
Solar/Wind Harmer
0.203
971547AH1-271 GEN
Solar/Wind Harmer
4.344
316023GEN1_S
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
0.81
3145893MURPHYS
Solar/Wind Harmer
0.901
970087AG2-069 GEN
Solar/Wind Harmer
16.1
3146173TUNIS
Solar/Wind Harmer
0.201
3156021HOLLOMANSOL
Solar/Wind Harmer
0.902
316337AD2-073 GEN
Solar/Wind Harmer
0.173
3145683EARLEYS
Solar/Wind Harmer
0.199
960081AF2-299 GEN
Solar/Wind Harmer
1.899
315607AA1-063A GEN
Solar/Wind Harmer
0.397
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
957481AF2-042 GEN
Solar/Wind Harmer
51.995
3145823KELFORD
Solar/Wind Harmer
0.195
3145783HORNRTN
Solar/Wind Harmer
0.192
3145796HORNRTN
Solar/Wind Harmer
0.633
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Adder
1.732
315693AD1-088 GEN
Solar/Wind Harmer
9.181
3147666LOUISA
Solar/Wind Harmer
0.756
3146293MARTNCO
Solar/Wind Harmer
0.174
316192AB2-158 GEN
Solar/Wind Harmer
1.035
316129AC1-054 GEN
Solar/Wind Harmer
0.685
3151091ELIZAR2
Adder
20.658
970657AG2-426 GEN
Solar/Wind Harmer
1.682
316316AC1-027 C
Solar/Wind Harmer
0.218
970189AG2-124 GEN
Solar/Wind Harmer
6.773
957871AF2-081 GEN
Solar/Wind Harmer
11.297
3141873WAN 176
Solar/Wind Harmer
0.045
316311AC2-079 GEN
Solar/Wind Harmer
6.506
3146406KITTY HAWK
Solar/Wind Harmer
0.028
3141913WHIT STONE
Solar/Wind Harmer
0.224
313526AB2-022
Solar/Wind Harmer
0.12
3138133OCRAN
Solar/Wind Harmer
0.067
3146486SUNBURY
Solar/Wind Harmer
0.223
3146486SUNBURY
Solar/Wind Harmer
0.223
3146396TANGLEW
Solar/Wind Harmer
0.615
3145176PASQUOTANK
Solar/Wind Harmer
0.138
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
970533AG2-339 GEN
Solar/Wind Harmer
16.536
315814AE2-033 C
Solar/Wind Harmer
17.282
970673AG2-436 GEN
Solar/Wind Harmer
26.967
3130156CHOWAN
Solar/Wind Harmer
0.215
3130156CHOWAN
Solar/Wind Harmer
0.215
971967AH1-528 GEN
Solar/Wind Harmer
33.875
3141813NORNECK
Solar/Wind Harmer
0.209
316258AE1-075 C
Solar/Wind Harmer
0.154
3130546PLYMOUTH
Solar/Wind Harmer
0.206
315732AD1-074 GEN1
Solar/Wind Harmer
1.172
315733AD1-074 GEN2
Solar/Wind Harmer
1.172
3146206CASHIE
Solar/Wind Harmer
0.203
970601AG2-382 GEN
Solar/Wind Harmer
7.602
3145893MURPHYS
Solar/Wind Harmer
0.547
3145893MURPHYS
Solar/Wind Harmer
0.203
970085AG2-068 GEN
Solar/Wind Harmer
10.733
970581AG2-369 GEN
Solar/Wind Harmer
9.231
316463AE2-346 GEN
Solar/Wind Harmer
0.171
3145513AHOSKIE
Solar/Wind Harmer
0.418
3145513AHOSKIE
Solar/Wind Harmer
0.2
3145683EARLEYS
Solar/Wind Harmer
0.398
3145683EARLEYS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.199
3146043SEABORD
Solar/Wind Harmer
0.198
315652AC1-086 GEN
Solar/Wind Harmer
21.435
3137643SOCKMAN
Solar/Wind Harmer
0.776
316426AA2-053 GEN
Solar/Wind Harmer
0.649
3145796HORNRTN
Solar/Wind Harmer
0.614
3145796HORNRTN
Solar/Wind Harmer
0.077
3146033SCOT NK
Solar/Wind Harmer
0.763
316486AD2-202 GEN
Solar/Wind Harmer
0.191
316210AC1-098 GEN
Solar/Wind Harmer
1.733
316274AC1-208 GEN
Solar/Wind Harmer
0.959
970831AG2-522 GEN
Solar/Wind Harmer
7.879
3145746EVERETS
Solar/Wind Harmer
0.729
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
316327AA2-057 GEN
Solar/Wind Harmer
0.267
957861AF2-080 GEN
Solar/Wind Harmer
7.766
3145573BETHELC
Solar/Wind Harmer
0.177
3145573BETHELC
Solar/Wind Harmer
0.177
3144303KENBRDG
Solar/Wind Harmer
0.14
970683AG2-441 GEN
Solar/Wind Harmer
10.555
3145543BTLEBRO
Solar/Wind Harmer
0.174
971623AH1-311 GEN
Solar/Wind Harmer
0.348
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.103
3146776BUCKING
Solar/Wind Harmer
0.059
972255AH1-712 GEN
Adder
83.058
972003AH1-546 GEN
Solar/Wind Harmer
5.44
971683AH1-343 GEN
Solar/Wind Harmer
5.439
970221AG2-151 GEN
Solar/Wind Harmer
7.825
316222AC1-221 GEN
Solar/Wind Harmer
0.604
316283AC2-100 C
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.176
270494AE1-108_GEN
Solar/Wind Harmer
1.557
315821AE2-092 GEN
Solar/Wind Harmer
0
3150331BIRCHWDA
Adder
21.106
3141196NOKESVL
Solar/Wind Helper
1.228
970681AG2-440 GEN
Solar/Wind Harmer
7.006
946301AF1-294 GEN
Solar/Wind Harmer
3.446
961791AG1-021 GEN
Solar/Wind Harmer
1.677
944491AF1-114 GEN
Solar/Wind Harmer
0
971845AH1-439 GEN
Solar/Wind Harmer
7.501
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.101
972205AH1-687 GEN
Adder
6.658
3138216PACIFIC
Solar/Wind Helper
0.038
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
971065AG2-659 GEN
Solar/Wind Harmer
7.794
316494AC1-189 GEN
Solar/Wind Harmer
0.608
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.177
3145493TOT1
Solar/Wind Harmer
0.789
3146233WITAKRS
Solar/Wind Harmer
0.706
316131AB2-060 GEN
Solar/Wind Harmer
0.55
972135AH1-637 GEN
Solar/Wind Harmer
1.504
315785AD2-033 C
Solar/Wind Harmer
1.422
316034AC1-036 C
Solar/Wind Harmer
0.012
970937AG2-583 GEN
Solar/Wind Harmer
10.738
970685AG2-442 GEN
Solar/Wind Harmer
13.06
971563AH1-280 GEN
Solar/Wind Harmer
1.863
3144293JTRSVLE
Adder
0.417
3144293JTRSVLE
Adder
0.329
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.139
316359AB2-059 GEN
Solar/Wind Harmer
0.618
3142053HEARTS
Solar/Wind Harmer
0.306
3146926FARMVIL
Solar/Wind Harmer
0.103
970401AG2-262 GEN
Solar/Wind Harmer
0.984
3146776BUCKING
Solar/Wind Harmer
0.066
972277AH1-723 GEN
Adder
96.787
971377AH1-170 GEN
Solar/Wind Harmer
1.565
3147623JAMES R
Solar/Wind Harmer
0.34
316447AC1-158 HLD
Solar/Wind Helper
4.178
316044AC1-158 PL1
Solar/Wind Helper
1.899
316415AF1-147_GEN2
Solar/Wind Helper
0.788
3150391LDYSMT3
50/50
36.76
972195AH1-682 GEN
50/50
4.831
972189AH1-679 GEN
50/50
4.491
3142296MT RD221
50/50
0.841
3142366NRTHEST
50/50
0.846
315673AE1-157 GEN
Solar/Wind Harmer
17.771
316312AB1-027
Solar/Wind Harmer
0.437
3150691DARBY 3
Adder
17.527
3150701DARBY 4
Adder
17.486
3150681DARBY 2
Adder
17.466
3150671DARBY 1
Adder
17.445
3143526WINTERP
Solar/Wind Harmer
1.254
971223AH1-071 GEN
Solar/Wind Harmer
2.564
966871AG1-558 GEN
Solar/Wind Harmer
0.277
315976AC1-164 GENA
Solar/Wind Harmer
2.522
316169AC1-164_GENC
Solar/Wind Harmer
2.179
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
113.017
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
4.003
3150991CHESPKB
Adder
2.401
3150991CHESPKB
Adder
2.344
3145506HICKORY
Solar/Wind Harmer
0.911
3145506HICKORY
Solar/Wind Harmer
0.547
3145506HICKORY
Solar/Wind Harmer
0.137
316339AD2-160 GEN
Solar/Wind Harmer
0.363
316388AE2-253 GEN
Solar/Wind Harmer
0.707
316156AD2-030 GEN
Solar/Wind Harmer
0.166
316349AD2-085 GEN
Solar/Wind Harmer
0.151
3137176SLIGO L2192
Solar/Wind Harmer
0.901
3146456SLIGO L269
Solar/Wind Harmer
4.007
3130086AYDLETT
Solar/Wind Harmer
0.904
315835AF2-110_GEN
Solar/Wind Harmer
1.544
3146386ELIZ CT
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.219
3144356SAPONY
Solar/Wind Harmer
1.834
316315AB2-025 C
Solar/Wind Harmer
0.175
315742AE1-103 GEN
Solar/Wind Harmer
3.228
3146376EDENTON
Solar/Wind Harmer
0.956
3146376EDENTON
Solar/Wind Harmer
0.956
972185AH1-677 GEN
Adder
11.976
972187AH1-678 GEN
Adder
6.009
315614AA2-178 GEN
Solar/Wind Harmer
1.196
3150341NORNECKC1
Adder
2.191
3150341NORNECKC1
Adder
2.173
970933AG2-581 GEN
Solar/Wind Harmer
16.621
316313AB2-026
Solar/Wind Harmer
0.129
316065AD1-022 GEN
Solar/Wind Harmer
9.412
316365GEN2_N
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
1.356
3145893MURPHYS
Solar/Wind Harmer
0.365
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
316140AB2-099
Solar/Wind Harmer
0.071
316336AC2-165 C
Solar/Wind Harmer
10.02
313506AB2-031 GEN
Solar/Wind Harmer
0.6
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
3142666NORTHAMPTON
Solar/Wind Harmer
0.195
3142666NORTHAMPTON
Solar/Wind Harmer
0.117
970099AG2-077 GEN
Solar/Wind Harmer
20.798
962571AG1-106 GEN
Solar/Wind Harmer
2.772
3145593CAROLNA
Solar/Wind Harmer
0.193
3145593CAROLNA
Solar/Wind Harmer
0.193
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.414
3145783HORNRTN
Solar/Wind Harmer
2.731
3145783HORNRTN
Solar/Wind Harmer
0.854
3145783HORNRTN
Solar/Wind Harmer
0.341
3145796HORNRTN
Solar/Wind Harmer
0.575
3145933PARMELE
Solar/Wind Harmer
0.374
3145933PARMELE
Solar/Wind Harmer
0.187
316005AA1-067
Solar/Wind Harmer
0.195
315724AD1-057 GEN
Solar/Wind Harmer
3.51
970301AG2-198 GEN
Solar/Wind Harmer
7.694
3145493TOT1
Solar/Wind Harmer
0.411
3145453TOT5
Solar/Wind Harmer
0.247
3145603CNETO
Solar/Wind Harmer
0.164
970323AG2-213 GEN
Solar/Wind Harmer
7.495
958211AF2-115 GEN
Solar/Wind Harmer
2.096
3144293JTRSVLE
Adder
0.417
3147133PAMPLIN
Solar/Wind Harmer
0.174
3147133PAMPLIN
Solar/Wind Harmer
0.139
961601AG1-000A GEN
Solar/Wind Harmer
3.095
316049AB1-081 GEN
Solar/Wind Harmer
0.99
316263AC1-034 GEN
Solar/Wind Harmer
6.613
962561AG1-105 GEN
Solar/Wind Harmer
8.121
964791AG1-342 GEN
Solar/Wind Harmer
3.222
3146843MT LREL
Solar/Wind Harmer
0.168
3146843MT LREL
Solar/Wind Harmer
0.168
3146776BUCKING
Solar/Wind Harmer
0.659
3146776BUCKING
Solar/Wind Harmer
0.053
316118AC1-105 GEN
Solar/Wind Harmer
0.421
972193AH1-681 GEN
Adder
3.711
942751AE2-291 GEN
Solar/Wind Harmer
6.798
316045AC1-158 PL2
Solar/Wind Helper
6.076
316450AC1-158 RIC
Solar/Wind Helper
0.506
316411AF1-147_GEN1
Solar/Wind Helper
0.788
316006AB2-029 C
Solar/Wind Helper
0.111
LAGNLTFEXP_LAGN->PJM
CLTF
7.97
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.669
TVALTFEXP_TVA->PJM
CLTF
4.04
CPLELTFEXP_CPLE->PJM
CLTF
11.231
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.295
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.728
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.762
MECLTFEXP_MEC->PJM
CLTF
3.637
SIGELTFEXP_SIGE->PJM
CLTF
0.111
NYPJM->LTFIMP_NY
CLTF
3.156
LGEELTFEXP_LGEE->PJM
CLTF
1.343
WECLTFEXP_WEC->PJM
CLTF
0.65

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:159.03 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:6472.73
MW Contribution:
7.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
220.273
3150631CHESTG8
50/50
2.35
316159AE1-175 C
Solar/Wind Harmer
0.323
315697AD1-025 GEN
Solar/Wind Harmer
0.395
3151201GRAVEL4
Adder
26.62
3151221GRAVEL6
Adder
26.59
3151191GRAVEL3
Adder
26.283
3151211GRAVEL5
Adder
26.283
971445AH1-216 GEN
Solar/Wind Harmer
25.675
971285AH1-108 GEN
Adder
2.749
3151081ELIZAR1
Adder
33.238
3151091ELIZAR2
Adder
32.66
316316AC1-027 C
Solar/Wind Harmer
0.345
957871AF2-081 GEN
Solar/Wind Harmer
17.845
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3138283WHITEMARSH
Solar/Wind Harmer
0.083
3146406KITTY HAWK
Solar/Wind Harmer
0.044
970657AG2-426 GEN
Solar/Wind Harmer
2.609
316311AC2-079 GEN
Solar/Wind Harmer
10.174
3143873LANEXA
Solar/Wind Harmer
0.212
316233AE1-074 FULL
Solar/Wind Harmer
0.283
971281AH1-106 GEN
Solar/Wind Harmer
4.907
971283AH1-107 GEN
Solar/Wind Harmer
4.907
313526AB2-022
Solar/Wind Harmer
0.189
3146486SUNBURY
Solar/Wind Harmer
0.352
3146486SUNBURY
Solar/Wind Harmer
0.352
3143316POE
Solar/Wind Harmer
1.394
3146396TANGLEW
Solar/Wind Harmer
0.969
3145176PASQUOTANK
Solar/Wind Harmer
0.218
970189AG2-124 GEN
Solar/Wind Harmer
10.294
3141873WAN 176
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.338
3130156CHOWAN
Solar/Wind Harmer
0.338
3141913WHIT STONE
Solar/Wind Harmer
0.332
315814AE2-033 C
Solar/Wind Harmer
26.224
3138133OCRAN
Solar/Wind Harmer
0.099
970533AG2-339 GEN
Solar/Wind Harmer
24.659
3141783LANCAST
Solar/Wind Harmer
0.195
3141783LANCAST
Solar/Wind Harmer
0.13
3130546PLYMOUTH
Solar/Wind Harmer
0.323
970673AG2-436 GEN
Solar/Wind Harmer
40.239
315732AD1-074 GEN1
Solar/Wind Harmer
1.836
315733AD1-074 GEN2
Solar/Wind Harmer
1.836
3146206CASHIE
Solar/Wind Harmer
0.318
970601AG2-382 GEN
Solar/Wind Harmer
11.886
971967AH1-528 GEN
Solar/Wind Harmer
50.538
3145893MURPHYS
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.315
316463AE2-346 GEN
Solar/Wind Harmer
0.265
3145513AHOSKIE
Solar/Wind Harmer
0.65
3145513AHOSKIE
Solar/Wind Harmer
0.311
3145683EARLEYS
Solar/Wind Harmer
0.619
3145683EARLEYS
Solar/Wind Harmer
0.309
3145683EARLEYS
Solar/Wind Harmer
0.309
3146043SEABORD
Solar/Wind Harmer
0.307
970085AG2-068 GEN
Solar/Wind Harmer
16.114
970581AG2-369 GEN
Solar/Wind Harmer
13.858
315652AC1-086 GEN
Solar/Wind Harmer
33.038
316426AA2-053 GEN
Solar/Wind Harmer
1.002
3137643SOCKMAN
Solar/Wind Harmer
1.193
3145796HORNRTN
Solar/Wind Harmer
0.947
3145796HORNRTN
Solar/Wind Harmer
0.118
3146033SCOT NK
Solar/Wind Harmer
1.183
316210AC1-098 GEN
Solar/Wind Harmer
2.685
316258AE1-075 C
Solar/Wind Harmer
0.216
316274AC1-208 GEN
Solar/Wind Harmer
1.484
3145746EVERETS
Solar/Wind Harmer
1.136
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
970831AG2-522 GEN
Solar/Wind Harmer
12.02
316486AD2-202 GEN
Solar/Wind Harmer
0.286
957861AF2-080 GEN
Solar/Wind Harmer
12.085
316327AA2-057 GEN
Solar/Wind Harmer
0.413
3141813NORNECK
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.275
3145573BETHELC
Solar/Wind Harmer
0.275
3144303KENBRDG
Solar/Wind Harmer
0.208
970683AG2-441 GEN
Solar/Wind Harmer
15.53
970681AG2-440 GEN
Solar/Wind Harmer
10.308
946301AF1-294 GEN
Solar/Wind Harmer
5.041
961791AG1-021 GEN
Solar/Wind Harmer
2.452
3147173SINAI
Solar/Wind Harmer
0.246
3147243WELCO
Solar/Wind Harmer
0.154
971845AH1-439 GEN
Solar/Wind Harmer
10.407
972205AH1-687 GEN
Adder
8.897
270197AD1-017 GEN1
Solar/Wind Harmer
1.05
3148133STUARTS
Solar/Wind Harmer
0.092
3148013FISHERV
Solar/Wind Harmer
0.088
3148463FAIRFLD
Solar/Wind Harmer
0.149
3142296MT RD221
50/50
1.309
3150691DARBY 3
50/50
29.078
3150701DARBY 4
50/50
29.01
3150681DARBY 2
50/50
28.977
3150671DARBY 1
50/50
28.943
3142366NRTHEST
50/50
1.316
3150621CHESTS7
50/50
1.097
316312AB1-027
Solar/Wind Harmer
0.691
315976AC1-164 GENA
Solar/Wind Harmer
4.068
316169AC1-164_GENC
Solar/Wind Harmer
3.515
3142946ENON
Solar/Wind Harmer
0.038
316294AC1-161 GEN
Solar/Wind Harmer
6.385
316033AB2-134 GEN
Solar/Wind Harmer
0.002
944641AF1-129 GEN
Adder
173.96
3150991CHESPKB
Adder
3.796
3150991CHESPKB
Adder
3.705
3145506HICKORY
Solar/Wind Harmer
1.441
3145506HICKORY
Solar/Wind Harmer
0.864
3145506HICKORY
Solar/Wind Harmer
0.216
316339AD2-160 GEN
Solar/Wind Harmer
0.574
316388AE2-253 GEN
Solar/Wind Harmer
1.117
3137176SLIGO L2192
Solar/Wind Harmer
1.423
3146456SLIGO L269
Solar/Wind Harmer
6.328
966871AG1-558 GEN
Solar/Wind Harmer
0.413
3130086AYDLETT
Solar/Wind Harmer
1.428
316349AD2-085 GEN
Solar/Wind Harmer
0.236
3143526WINTERP
Solar/Wind Harmer
1.839
315835AF2-110_GEN
Solar/Wind Harmer
2.427
3146386ELIZ CT
Solar/Wind Harmer
0.353
3146516WINFALL
Solar/Wind Harmer
0.348
3146516WINFALL
Solar/Wind Harmer
0.348
3146516WINFALL
Solar/Wind Harmer
0.348
3146626S HERTFORD
Solar/Wind Harmer
0.346
3146626S HERTFORD
Solar/Wind Harmer
0.346
971223AH1-071 GEN
Solar/Wind Harmer
3.659
316156AD2-030 GEN
Solar/Wind Harmer
0.251
315742AE1-103 GEN
Solar/Wind Harmer
5.052
3146376EDENTON
Solar/Wind Harmer
1.502
3146376EDENTON
Solar/Wind Harmer
1.502
3144356SAPONY
Solar/Wind Harmer
2.782
316315AB2-025 C
Solar/Wind Harmer
0.266
315614AA2-178 GEN
Solar/Wind Harmer
1.876
972193AH1-681 GEN
Adder
7.349
316065AD1-022 GEN
Solar/Wind Harmer
14.725
3150611CHESTG7
50/50
2.388
3151161SURRY 1
50/50
14.898
3142416OLDCHRC
Solar/Wind Harmer
3.766
316075AC2-137 C
Solar/Wind Harmer
0.103
970293AG2-193 GEN
Solar/Wind Harmer
4.088
3142946ENON
Solar/Wind Harmer
0.127
3143096IRON208
Adder
1.568
3143096IRON208
Adder
1.537
3150921YORKTN3
Adder
9.345
3144216WINCHST
Adder
1.4
970133AG2-095 GEN
Solar/Wind Harmer
3.539
316458AB2-190 GEN2
Solar/Wind Harmer
1.962
315778AD1-151 GEN
Solar/Wind Harmer
29.389
961611AG1-000B GEN
Solar/Wind Harmer
9.766
3151171GRAVELC
Adder
5.116
3150861SPRUNCD
Adder
1.68
3145336SMITFLD
Solar/Wind Harmer
0.146
3144536CHRHLND
Solar/Wind Harmer
0.054
944581AF1-123 GEN
Solar/Wind Harmer
81.688
944601AF1-125 GEN
Solar/Wind Harmer
80.429
3151101ELIZAR3
Adder
33.663
3144873MCLAUGH
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.191
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.357
971153AH1-033 GEN
Solar/Wind Harmer
4.134
316473AC1-191 GEN
Solar/Wind Harmer
1.208
316246AF1-032 C
Solar/Wind Harmer
0.158
315813AE1-149 C
Solar/Wind Harmer
18.999
970657AG2-426 GEN
Solar/Wind Harmer
7.973
316321Z2-027
Solar/Wind Harmer
0.063
3141766HARMONY
Solar/Wind Harmer
4.65
3146516WINFALL
Solar/Wind Harmer
0.348
3141843SHACKLE
Adder
1.775
316203AE2-005 GEN
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
0.346
3145273HOLLAND
Solar/Wind Harmer
0.257
3141873WAN 176
Solar/Wind Harmer
6.09
3146376EDENTON
Solar/Wind Harmer
0.338
944011AF1-069 GEN
Solar/Wind Harmer
19.64
315735AD1-075 GEN1
Solar/Wind Harmer
0.917
972255AH1-712 GEN
Adder
164.477
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.318
3145893MURPHYS
Solar/Wind Harmer
0.528
3145893MURPHYS
Solar/Wind Harmer
0.315
3146173TUNIS
Solar/Wind Harmer
0.312
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
970917AG2-570 GEN
Solar/Wind Harmer
27.157
3145823KELFORD
Solar/Wind Harmer
0.303
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
316011AB1-132 GEN
Solar/Wind Harmer
5.448
316181AB2-040 GEN
Solar/Wind Harmer
0.427
3145796HORNRTN
Solar/Wind Harmer
1.183
3145796HORNRTN
Solar/Wind Harmer
0.296
3145933PARMELE
Solar/Wind Harmer
0.292
3147043LAWRENC
Solar/Wind Harmer
0.175
316212AC1-099_GEN
Solar/Wind Harmer
1.498
3143336POWHATN
Solar/Wind Harmer
4.37
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
315722AD1-056 GEN
Solar/Wind Harmer
9.736
316478AD1-087 GEN
Solar/Wind Harmer
0.974
3150351NORNECKC2
Adder
2.799
3146073TAR RVR
Solar/Wind Harmer
0.275
3146083TARBORO
Solar/Wind Harmer
0.275
3146233WITAKRS
Solar/Wind Harmer
1.38
3146233WITAKRS
Solar/Wind Harmer
0.187
3138543CONSLDL
Solar/Wind Harmer
0.181
961601AG1-000A GEN
Solar/Wind Harmer
19.208
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.27
971623AH1-311 GEN
Solar/Wind Harmer
0.54
964241AG1-285 GEN
Solar/Wind Harmer
17.565
970257AG2-171 GEN
Solar/Wind Harmer
8.322
971775AH1-396 GEN
Solar/Wind Harmer
0.416
959311AF2-222 GEN
Solar/Wind Harmer
23.056
3144293JTRSVLE
Adder
0.61
3147133PAMPLIN
Solar/Wind Harmer
0.797
971781AH1-399 GEN
Solar/Wind Harmer
0.329
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.147
3146776BUCKING
Solar/Wind Harmer
0.082
971683AH1-343 GEN
Solar/Wind Harmer
8.387
316222AC1-221 GEN
Solar/Wind Harmer
0.936
316283AC2-100 C
Solar/Wind Harmer
0.443
972003AH1-546 GEN
Solar/Wind Harmer
7.301
316223AC1-118
Solar/Wind Harmer
0.148
3141906WESTMOR
Solar/Wind Harmer
0.083
3151881LOWMORC
Adder
1.59
3151881LOWMORC
Adder
1.565
3151861LOWMORA
Adder
1.54
270069AE2-166 C O1
Solar/Wind Harmer
6.438
944491AF1-114 GEN
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.855
315651AD1-115 GEN
Solar/Wind Helper
1.155
226929AD2-058 GEN
Solar/Wind Helper
0.127
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
23779801AA1-109
Solar/Wind Helper
0.186
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.161
205917AD1-020 ES
Solar/Wind Helper
0.356
233915AB1-141 GEN
Solar/Wind Helper
0.489
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219615MILLCREEK C
Solar/Wind Helper
0.026
316123AC1-075 GEN
Solar/Wind Harmer
0.276
970221AG2-151 GEN
Solar/Wind Harmer
10.604
270494AE1-108_GEN
Solar/Wind Harmer
2.19
315821AE2-092 GEN
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.032
3148013FISHERV
Solar/Wind Harmer
0.153
3151861LOWMORA
Adder
1.602
958131AF2-107 GEN
Solar/Wind Harmer
4.284
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3141196NOKESVL
Solar/Wind Helper
1.392
3147666LOUISA
Solar/Wind Helper
0.739
227287AC2-120 GEN
Solar/Wind Helper
0.434
226910AB2-157 C
Solar/Wind Helper
0.018
3132273ORANGE
Solar/Wind Helper
0.053
23777801MSM_W1-116
Solar/Wind Helper
0.111
208835TUHI V3-051
Solar/Wind Helper
0.021
237002AB1-128_GEN
Solar/Wind Helper
0.386
237038AE2-054 C
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.384
237085AD2-009_GEN
Solar/Wind Helper
1.397
233935AB2-179 C
Solar/Wind Helper
1.236
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
233987AB2-037 GEN
Solar/Wind Helper
2.28
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.732
233997TMININ_4.2
Solar/Wind Helper
0.2
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
233950AC2-186 GEN
Solar/Wind Helper
0.113
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.049
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
972185AH1-677 GEN
Adder
17.888
3145893MURPHYS
Solar/Wind Harmer
2.11
3145893MURPHYS
Solar/Wind Harmer
0.567
972187AH1-678 GEN
Adder
8.982
3146173TUNIS
Solar/Wind Harmer
0.312
3146173TUNIS
Solar/Wind Harmer
0.312
316365GEN2_N
Solar/Wind Harmer
0.691
316140AB2-099
Solar/Wind Harmer
0.111
970933AG2-581 GEN
Solar/Wind Harmer
24.793
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.181
962571AG1-106 GEN
Solar/Wind Harmer
4.273
313506AB2-031 GEN
Solar/Wind Harmer
0.92
3145593CAROLNA
Solar/Wind Harmer
0.297
3145593CAROLNA
Solar/Wind Harmer
0.297
3145593CAROLNA
Solar/Wind Harmer
0.37
3145796HORNRTN
Solar/Wind Harmer
0.888
3145783HORNRTN
Solar/Wind Harmer
5.262
3145783HORNRTN
Solar/Wind Harmer
4.209
3145783HORNRTN
Solar/Wind Harmer
1.315
3145783HORNRTN
Solar/Wind Harmer
0.526
3145933PARMELE
Solar/Wind Harmer
0.584
3145933PARMELE
Solar/Wind Harmer
0.292
970099AG2-077 GEN
Solar/Wind Harmer
31.038
316313AB2-026
Solar/Wind Harmer
0.18
316005AA1-067
Solar/Wind Harmer
0.305
315724AD1-057 GEN
Solar/Wind Harmer
5.431
3150341NORNECKC1
Adder
2.892
3150341NORNECKC1
Adder
2.869
3145493TOT1
Solar/Wind Harmer
0.639
3145453TOT5
Solar/Wind Harmer
0.383
3145603CNETO
Solar/Wind Harmer
0.256
316336AC2-165 C
Solar/Wind Harmer
13.939
961601AG1-000A GEN
Solar/Wind Harmer
4.802
316049AB1-081 GEN
Solar/Wind Harmer
1.536
316263AC1-034 GEN
Solar/Wind Harmer
10.258
970301AG2-198 GEN
Solar/Wind Harmer
11.151
970323AG2-213 GEN
Solar/Wind Harmer
11.095
972189AH1-679 GEN
Adder
4.352
962561AG1-105 GEN
Solar/Wind Harmer
12.278
958211AF2-115 GEN
Solar/Wind Harmer
3.066
3144293JTRSVLE
Adder
0.61
964791AG1-342 GEN
Solar/Wind Harmer
4.878
3146843MT LREL
Solar/Wind Harmer
0.254
3146843MT LREL
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.203
316118AC1-105 GEN
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.912
3146776BUCKING
Solar/Wind Harmer
0.074
942751AE2-291 GEN
Solar/Wind Harmer
10.74
942671AE2-283 GEN
Solar/Wind Harmer
3.934
316045AC1-158 PL2
Solar/Wind Helper
8.047
316450AC1-158 RIC
Solar/Wind Helper
0.671
316006AB2-029 C
Solar/Wind Helper
0.166
316411AF1-147_GEN1
Solar/Wind Helper
1.085
223401AF1-299 GEN
Solar/Wind Helper
0.395
223402AF1-300 C
Solar/Wind Helper
0.395
237006AB1-125 GEN
Solar/Wind Helper
0.121
238221AF1-254 C O1
Solar/Wind Helper
0.239
235020AA1-095 C
Solar/Wind Helper
0.045
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.432
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232436AB1-176 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.113
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.935
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.016
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.058
219912AD2-042 GEN
Solar/Wind Helper
0.145
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.077
219304NAMERICA C
Solar/Wind Helper
0.126
3152331SURRY 2
50/50
15.655
3150641CHESTS8
50/50
1.21
3142416OLDCHRC
Solar/Wind Harmer
1.01
3142416OLDCHRC
Solar/Wind Harmer
0.387
315975AC1-164 GENB
Solar/Wind Harmer
0.12
944631AF1-128 GEN
Adder
179.295
3143096IRON208
Adder
1.568
3138126ROCKLANDING
Solar/Wind Harmer
0.17
971317AH1-138 GEN
Solar/Wind Harmer
2.77
315773AC2-141 GEN
Solar/Wind Harmer
13.491
3142543TWELFTH
Solar/Wind Harmer
0.035
316132AB2-190 GEN1
Solar/Wind Harmer
1.962
971069AG2-661 GEN
Solar/Wind Harmer
6.531
961611AG1-000B GEN
Solar/Wind Harmer
19.206
3151171GRAVELC
Adder
3.89
3150851SPRUNCC
Adder
1.68
3145336SMITFLD
Solar/Wind Harmer
1.457
944591AF1-124 GEN
Solar/Wind Harmer
81.978
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.064
3150981CHESPKA
Adder
4.525
315671AE2-027_GEN
Solar/Wind Harmer
0.002
316072AD1-144
Solar/Wind Harmer
0.128
3142433PROV 92
Solar/Wind Harmer
1.431
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.357
319010AE1-072 C
Solar/Wind Harmer
1.782
316381AD1-082 GEN
Solar/Wind Harmer
0.36
3143526WINTERP
Solar/Wind Harmer
1.839
316093AE2-104_GEN
Solar/Wind Harmer
5.948
3141766HARMONY
Solar/Wind Harmer
0.07
3146516WINFALL
Solar/Wind Harmer
1.128
3146516WINFALL
Solar/Wind Harmer
0.348
971777AH1-397 GEN
Solar/Wind Harmer
0.917
939411AE1-173 GEN
Solar/Wind Harmer
148.2
3143226MDLTHAN
Solar/Wind Harmer
0.343
940641AE2-051 GEN
Solar/Wind Harmer
27.419
3130156CHOWAN
Solar/Wind Harmer
0.338
3138133OCRAN
Solar/Wind Harmer
0.198
315816AE2-034 GEN
Solar/Wind Harmer
1.407
3145663CRESWEL
Solar/Wind Harmer
0.923
971163AH1-040 GEN
Solar/Wind Harmer
26.382
941031AE2-094 GEN
Solar/Wind Harmer
60.109
315737AD1-076 GEN
Solar/Wind Harmer
4.134
972277AH1-723 GEN
Adder
191.666
3146206CASHIE
Solar/Wind Harmer
0.318
971547AH1-271 GEN
Solar/Wind Harmer
6.792
3145893MURPHYS
Solar/Wind Harmer
1.261
3145893MURPHYS
Solar/Wind Harmer
1.402
3156021HOLLOMANSOL
Solar/Wind Harmer
1.407
3146173TUNIS
Solar/Wind Harmer
0.312
316023GEN1_S
Solar/Wind Harmer
0.691
3145683EARLEYS
Solar/Wind Harmer
0.309
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
315607AA1-063A GEN
Solar/Wind Harmer
0.615
970919AG2-571 GEN
Solar/Wind Harmer
10.863
3145823KELFORD
Solar/Wind Harmer
0.303
960081AF2-299 GEN
Solar/Wind Harmer
2.903
970087AG2-069 GEN
Solar/Wind Harmer
24.172
962861AG1-135 GEN
Solar/Wind Harmer
9.549
3145796HORNRTN
Solar/Wind Harmer
0.976
3145796HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.296
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
9.772
3146293MARTNCO
Solar/Wind Harmer
0.271
3147043LAWRENC
Adder
2.634
957481AF2-042 GEN
Solar/Wind Harmer
77.596
3143336POWHATN
Solar/Wind Harmer
5.141
3141726DUNNSVL
Solar/Wind Harmer
1.144
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
315693AD1-088 GEN
Solar/Wind Harmer
13.636
316494AC1-189 GEN
Solar/Wind Harmer
0.947
316129AC1-054 GEN
Solar/Wind Harmer
1.044
971065AG2-659 GEN
Solar/Wind Harmer
11.863
3150351NORNECKC2
Adder
2.753
961671AG1-007 GEN
Solar/Wind Harmer
0.042
3146083TARBORO
Solar/Wind Harmer
0.275
3145493TOT1
Solar/Wind Harmer
1.225
3146233WITAKRS
Solar/Wind Harmer
1.094
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.216
316359AB2-059 GEN
Solar/Wind Harmer
0.959
3142053HEARTS
Solar/Wind Harmer
0.475
316131AB2-060 GEN
Solar/Wind Harmer
0.824
315785AD2-033 C
Solar/Wind Harmer
2.11
316034AC1-036 C
Solar/Wind Harmer
0.017
970685AG2-442 GEN
Solar/Wind Harmer
19.165
971563AH1-280 GEN
Solar/Wind Harmer
2.725
3144293JTRSVLE
Adder
0.61
3144293JTRSVLE
Adder
0.481
970401AG2-262 GEN
Solar/Wind Harmer
1.491
3146926FARMVIL
Solar/Wind Harmer
0.147
316337AD2-073 GEN
Solar/Wind Harmer
0.21
970937AG2-583 GEN
Solar/Wind Harmer
14.653
3146776BUCKING
Solar/Wind Harmer
0.091
971377AH1-170 GEN
Solar/Wind Harmer
2.121
3147623JAMES R
Solar/Wind Harmer
0.461
970223AG2-152 GEN
Solar/Wind Harmer
12.092
3147123OTTER R
Solar/Wind Harmer
0.099
3147312GRETNA
Solar/Wind Harmer
0.126
3146802CHATHAM
Solar/Wind Harmer
0.118
941801AE2-185 GEN
Solar/Wind Harmer
5.057
972135AH1-637 GEN
Solar/Wind Harmer
1.313
270030AE2-140 GEN
Solar/Wind Harmer
15.083
962751AG1-124 GEN
Solar/Wind Harmer
6.345
316447AC1-158 HLD
Solar/Wind Helper
5.534
316044AC1-158 PL1
Solar/Wind Helper
2.515
316415AF1-147_GEN2
Solar/Wind Helper
1.085
3147666LOUISA
Solar/Wind Helper
1.286
316192AB2-158 GEN
Solar/Wind Helper
2.116
23777901MDS_W4-102
Solar/Wind Helper
0.153
237001AB1-127_GEN
Solar/Wind Helper
0.387
208835TUHI V3-051
Solar/Wind Helper
0.021
235063AE1-101 C2
Solar/Wind Helper
1.432
205916AD1-020 GEN
Solar/Wind Helper
1.655
233918AB1-142 GEN
Solar/Wind Helper
0.489
233944AB2-135 GEN
Solar/Wind Helper
0.574
205932AD2-116_GEN
Solar/Wind Helper
0.494
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.2
233998TM1NIN_3.36
Solar/Wind Helper
0.2
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
238175AF1-290_GEN
Solar/Wind Helper
0.121
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219348LDSOLAR C
Solar/Wind Helper
0.11
LAGNLTFEXP_LAGN->PJM
CLTF
14.557
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.893
TVALTFEXP_TVA->PJM
CLTF
7.369
CPLELTFEXP_CPLE->PJM
CLTF
17.675
CBM West 2LTFEXP_CBM-W2->PJM
CBM
79.931
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.074
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.634
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.24
NYPJM->LTFIMP_NY
CLTF
4.657
LGEELTFEXP_LGEE->PJM
CLTF
2.991
WECLTFEXP_WEC->PJM
CLTF
1.512
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.11 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5743.4
MW Contribution:
4.79
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150921YORKTN3
50/50
8.613
3144216WINCHST
50/50
1.287
3151101ELIZAR3
50/50
30.933
3151161SURRY 1
50/50
12.681
3142416OLDCHRC
Solar/Wind Harmer
3.204
316075AC2-137 C
Solar/Wind Harmer
0.087
970293AG2-193 GEN
Solar/Wind Harmer
3.393
944581AF1-123 GEN
Solar/Wind Harmer
70.914
972263AH1-716 GEN
50/50
193.959
3151081ELIZAR1
50/50
30.542
3151091ELIZAR2
50/50
30.012
941591AE2-156 GEN
50/50
27.909
3151201GRAVEL4
50/50
24.044
316159AE1-175 C
Solar/Wind Harmer
0.28
316316AC1-027 C
Solar/Wind Harmer
0.299
971445AH1-216 GEN
Solar/Wind Harmer
21.985
3151221GRAVEL6
Adder
22.633
3151191GRAVEL3
Adder
22.373
3151211GRAVEL5
Adder
22.373
957871AF2-081 GEN
Solar/Wind Harmer
15.456
3146406KITTY HAWK
Solar/Wind Harmer
0.038
3138283WHITEMARSH
Solar/Wind Harmer
0.072
315697AD1-025 GEN
Solar/Wind Harmer
0.33
313526AB2-022
Solar/Wind Harmer
0.163
3146486SUNBURY
Solar/Wind Harmer
0.304
3146486SUNBURY
Solar/Wind Harmer
0.304
3146396TANGLEW
Solar/Wind Harmer
0.838
3145176PASQUOTANK
Solar/Wind Harmer
0.188
316311AC2-079 GEN
Solar/Wind Harmer
8.676
3143873LANEXA
Solar/Wind Harmer
0.181
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
970657AG2-426 GEN
Solar/Wind Harmer
2.194
970189AG2-124 GEN
Solar/Wind Harmer
8.799
3141873WAN 176
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.291
3130156CHOWAN
Solar/Wind Harmer
0.291
3143316POE
Solar/Wind Harmer
1.152
3141913WHIT STONE
Solar/Wind Harmer
0.285
3138133OCRAN
Solar/Wind Harmer
0.085
315814AE2-033 C
Solar/Wind Harmer
22.007
970533AG2-339 GEN
Solar/Wind Harmer
21.004
3130546PLYMOUTH
Solar/Wind Harmer
0.278
3141783LANCAST
Solar/Wind Harmer
0.167
3141783LANCAST
Solar/Wind Harmer
0.111
315732AD1-074 GEN1
Solar/Wind Harmer
1.577
315733AD1-074 GEN2
Solar/Wind Harmer
1.577
970673AG2-436 GEN
Solar/Wind Harmer
34.262
3146206CASHIE
Solar/Wind Harmer
0.273
970601AG2-382 GEN
Solar/Wind Harmer
10.197
3145893MURPHYS
Solar/Wind Harmer
0.727
3145893MURPHYS
Solar/Wind Harmer
0.269
971967AH1-528 GEN
Solar/Wind Harmer
42.871
316463AE2-346 GEN
Solar/Wind Harmer
0.227
3145513AHOSKIE
Solar/Wind Harmer
0.556
3145513AHOSKIE
Solar/Wind Harmer
0.265
3145683EARLEYS
Solar/Wind Harmer
0.529
3145683EARLEYS
Solar/Wind Harmer
0.264
3145683EARLEYS
Solar/Wind Harmer
0.264
3146043SEABORD
Solar/Wind Harmer
0.261
970085AG2-068 GEN
Solar/Wind Harmer
13.709
970581AG2-369 GEN
Solar/Wind Harmer
11.79
315652AC1-086 GEN
Solar/Wind Harmer
28.018
316426AA2-053 GEN
Solar/Wind Harmer
0.85
3137643SOCKMAN
Solar/Wind Harmer
1.009
3146033SCOT NK
Solar/Wind Harmer
1.008
971285AH1-108 GEN
Adder
1.896
3145796HORNRTN
Solar/Wind Harmer
0.803
3145796HORNRTN
Solar/Wind Harmer
0.1
316210AC1-098 GEN
Solar/Wind Harmer
2.286
316274AC1-208 GEN
Solar/Wind Harmer
1.261
3145746EVERETS
Solar/Wind Harmer
0.971
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
957861AF2-080 GEN
Solar/Wind Harmer
10.316
316327AA2-057 GEN
Solar/Wind Harmer
0.352
970831AG2-522 GEN
Solar/Wind Harmer
10.103
3141813NORNECK
Solar/Wind Harmer
0.235
316486AD2-202 GEN
Solar/Wind Harmer
0.239
3145573BETHELC
Solar/Wind Harmer
0.235
3145573BETHELC
Solar/Wind Harmer
0.235
3144303KENBRDG
Solar/Wind Harmer
0.168
3147173SINAI
Solar/Wind Harmer
0.206
3147243WELCO
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
12.403
970681AG2-440 GEN
Solar/Wind Harmer
8.232
946301AF1-294 GEN
Solar/Wind Harmer
3.988
961791AG1-021 GEN
Solar/Wind Harmer
1.94
944601AF1-125 GEN
Solar/Wind Harmer
69.822
3142946ENON
Solar/Wind Harmer
0.105
3144873MCLAUGH
Solar/Wind Harmer
0.008
3144536CHRHLND
Solar/Wind Harmer
0.047
3145336SMITFLD
Solar/Wind Harmer
0.125
3151171GRAVELC
Adder
4.355
316017AA1-139 ULT1
Solar/Wind Harmer
0.166
3146456SLIGO L269
Solar/Wind Harmer
0.31
971153AH1-033 GEN
Solar/Wind Harmer
3.58
961611AG1-000B GEN
Solar/Wind Harmer
8.261
316246AF1-032 C
Solar/Wind Harmer
0.137
972255AH1-712 GEN
Adder
157.324
315778AD1-151 GEN
Solar/Wind Harmer
24.517
316458AB2-190 GEN2
Solar/Wind Harmer
1.627
316321Z2-027
Solar/Wind Harmer
0.054
970133AG2-095 GEN
Solar/Wind Harmer
2.906
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
316473AC1-191 GEN
Solar/Wind Harmer
1.012
3141766HARMONY
Solar/Wind Harmer
3.989
970657AG2-426 GEN
Solar/Wind Harmer
6.706
3146626S HERTFORD
Solar/Wind Harmer
0.298
3141843SHACKLE
Adder
1.517
316203AE2-005 GEN
Solar/Wind Harmer
0
315813AE1-149 C
Solar/Wind Harmer
15.797
3145273HOLLAND
Solar/Wind Harmer
0.221
3141873WAN 176
Solar/Wind Harmer
5.225
3143096IRON208
Adder
1.224
3143096IRON208
Adder
1.2
3146376EDENTON
Solar/Wind Harmer
0.291
944011AF1-069 GEN
Solar/Wind Harmer
16.729
315735AD1-075 GEN1
Solar/Wind Harmer
0.788
3146206CASHIE
Solar/Wind Harmer
0.273
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
0.269
3146173TUNIS
Solar/Wind Harmer
0.267
3145963POPLR C
Solar/Wind Harmer
0.262
3146263WOODLND
Solar/Wind Harmer
0.261
970917AG2-570 GEN
Solar/Wind Harmer
23.102
3145823KELFORD
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
316011AB1-132 GEN
Solar/Wind Harmer
4.62
316181AB2-040 GEN
Solar/Wind Harmer
0.36
3150861SPRUNCD
Adder
1.159
3145796HORNRTN
Solar/Wind Harmer
1.004
3145796HORNRTN
Solar/Wind Harmer
0.251
3145933PARMELE
Solar/Wind Harmer
0.25
316212AC1-099_GEN
Solar/Wind Harmer
1.275
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3147043LAWRENC
Solar/Wind Harmer
0.146
315722AD1-056 GEN
Solar/Wind Harmer
8.274
3150351NORNECKC2
Adder
2.387
316478AD1-087 GEN
Solar/Wind Harmer
0.815
3146073TAR RVR
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
0.235
3146233WITAKRS
Solar/Wind Harmer
1.174
3146233WITAKRS
Solar/Wind Harmer
0.159
3138543CONSLDL
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
16.35
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.23
971623AH1-311 GEN
Solar/Wind Harmer
0.459
964241AG1-285 GEN
Solar/Wind Harmer
14.365
970257AG2-171 GEN
Solar/Wind Harmer
6.712
971775AH1-396 GEN
Solar/Wind Harmer
0.336
959311AF2-222 GEN
Solar/Wind Harmer
18.544
971781AH1-399 GEN
Solar/Wind Harmer
0.272
3144293JTRSVLE
Adder
0.482
3147133PAMPLIN
Solar/Wind Harmer
0.626
316222AC1-221 GEN
Solar/Wind Harmer
0.794
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.376
3142296MT RD221
50/50
1.095
3150991CHESPKB
50/50
3.487
3150991CHESPKB
50/50
3.403
315976AC1-164 GENA
Solar/Wind Harmer
3.491
316169AC1-164_GENC
Solar/Wind Harmer
3.016
316312AB1-027
Solar/Wind Harmer
0.588
316294AC1-161 GEN
Solar/Wind Harmer
5.584
3142946ENON
Solar/Wind Harmer
0.031
3145506HICKORY
Solar/Wind Harmer
1.248
3145506HICKORY
Solar/Wind Harmer
0.749
3145506HICKORY
Solar/Wind Harmer
0.187
316339AD2-160 GEN
Solar/Wind Harmer
0.497
316388AE2-253 GEN
Solar/Wind Harmer
0.967
3150691DARBY 3
Adder
22.312
3150701DARBY 4
Adder
22.26
3150681DARBY 2
Adder
22.234
3150671DARBY 1
Adder
22.208
3137176SLIGO L2192
Solar/Wind Harmer
1.233
3146456SLIGO L269
Solar/Wind Harmer
5.48
3130086AYDLETT
Solar/Wind Harmer
1.236
316033AB2-134 GEN
Solar/Wind Harmer
0.001
972193AH1-681 GEN
Adder
7.029
3146386ELIZ CT
Solar/Wind Harmer
0.306
3142366NRTHEST
Adder
0.998
315835AF2-110_GEN
Solar/Wind Harmer
2.089
316349AD2-085 GEN
Solar/Wind Harmer
0.201
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
966871AG1-558 GEN
Solar/Wind Harmer
0.346
3146626S HERTFORD
Solar/Wind Harmer
0.298
3146626S HERTFORD
Solar/Wind Harmer
0.298
944641AF1-129 GEN
Adder
140.43
316156AD2-030 GEN
Solar/Wind Harmer
0.215
3146376EDENTON
Solar/Wind Harmer
1.295
3146376EDENTON
Solar/Wind Harmer
1.295
315742AE1-103 GEN
Solar/Wind Harmer
4.334
315614AA2-178 GEN
Solar/Wind Harmer
1.614
3144356SAPONY
Solar/Wind Harmer
2.334
316315AB2-025 C
Solar/Wind Harmer
0.223
316065AD1-022 GEN
Solar/Wind Harmer
12.64
972185AH1-677 GEN
Adder
15.221
3145893MURPHYS
Solar/Wind Harmer
1.802
3145893MURPHYS
Solar/Wind Harmer
0.484
972187AH1-678 GEN
Adder
7.639
3146173TUNIS
Solar/Wind Harmer
0.267
3146173TUNIS
Solar/Wind Harmer
0.267
316140AB2-099
Solar/Wind Harmer
0.094
316365GEN2_N
Solar/Wind Harmer
0.583
970933AG2-581 GEN
Solar/Wind Harmer
20.966
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
962571AG1-106 GEN
Solar/Wind Harmer
3.624
313506AB2-031 GEN
Solar/Wind Harmer
0.777
3145593CAROLNA
Solar/Wind Harmer
0.252
3152331SURRY 2
50/50
13.811
3150981CHESPKA
50/50
4.157
315975AC1-164 GENB
Solar/Wind Harmer
0.103
3142416OLDCHRC
Solar/Wind Harmer
0.859
3142416OLDCHRC
Solar/Wind Harmer
0.329
315773AC2-141 GEN
Solar/Wind Harmer
11.798
971317AH1-138 GEN
Solar/Wind Harmer
2.407
3138126ROCKLANDING
Solar/Wind Harmer
0.148
944591AF1-124 GEN
Solar/Wind Harmer
71.166
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.056
3145336SMITFLD
Solar/Wind Harmer
1.249
3151171GRAVELC
Adder
3.312
316072AD1-144
Solar/Wind Harmer
0.11
3146456SLIGO L269
Solar/Wind Harmer
0.31
961611AG1-000B GEN
Solar/Wind Harmer
16.246
319010AE1-072 C
Solar/Wind Harmer
1.543
944631AF1-128 GEN
Adder
146.631
972277AH1-723 GEN
Adder
183.33
971069AG2-661 GEN
Solar/Wind Harmer
5.448
316132AB2-190 GEN1
Solar/Wind Harmer
1.627
316093AE2-104_GEN
Solar/Wind Harmer
5.119
3146516WINFALL
Solar/Wind Harmer
0.975
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Solar/Wind Harmer
1.198
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
3141766HARMONY
Solar/Wind Harmer
0.06
939411AE1-173 GEN
Solar/Wind Harmer
127.42
316381AD1-082 GEN
Solar/Wind Harmer
0.302
971777AH1-397 GEN
Solar/Wind Harmer
0.784
315671AE2-027_GEN
Solar/Wind Harmer
0.002
940641AE2-051 GEN
Solar/Wind Harmer
23.504
3143096IRON208
Adder
1.224
3130156CHOWAN
Solar/Wind Harmer
0.291
315816AE2-034 GEN
Solar/Wind Harmer
1.211
3145663CRESWEL
Solar/Wind Harmer
0.794
971163AH1-040 GEN
Solar/Wind Harmer
22.704
3138133OCRAN
Solar/Wind Harmer
0.17
3142543TWELFTH
Solar/Wind Harmer
0.027
941031AE2-094 GEN
Solar/Wind Harmer
51.201
315737AD1-076 GEN
Solar/Wind Harmer
3.552
3146206CASHIE
Solar/Wind Harmer
0.273
971547AH1-271 GEN
Solar/Wind Harmer
5.827
3145893MURPHYS
Solar/Wind Harmer
1.077
3145893MURPHYS
Solar/Wind Harmer
1.197
3156021HOLLOMANSOL
Solar/Wind Harmer
1.205
3146173TUNIS
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.264
3145963POPLR C
Solar/Wind Harmer
0.262
316023GEN1_S
Solar/Wind Harmer
0.583
3146263WOODLND
Solar/Wind Harmer
0.261
970919AG2-571 GEN
Solar/Wind Harmer
9.241
315607AA1-063A GEN
Solar/Wind Harmer
0.522
3145823KELFORD
Solar/Wind Harmer
0.258
970087AG2-069 GEN
Solar/Wind Harmer
20.564
962861AG1-135 GEN
Solar/Wind Harmer
8.162
960081AF2-299 GEN
Solar/Wind Harmer
2.444
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
8.351
3150851SPRUNCC
Adder
1.159
3145796HORNRTN
Solar/Wind Harmer
0.828
3145796HORNRTN
Solar/Wind Harmer
0.251
3145783HORNRTN
Solar/Wind Harmer
0.251
3146293MARTNCO
Solar/Wind Harmer
0.232
3141726DUNNSVL
Solar/Wind Harmer
0.977
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
957481AF2-042 GEN
Solar/Wind Harmer
65.003
3147043LAWRENC
Adder
2.204
316494AC1-189 GEN
Solar/Wind Harmer
0.808
3150351NORNECKC2
Adder
2.348
315693AD1-088 GEN
Solar/Wind Harmer
11.298
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.235
3145493TOT1
Solar/Wind Harmer
1.045
316129AC1-054 GEN
Solar/Wind Harmer
0.877
3146233WITAKRS
Solar/Wind Harmer
0.931
971065AG2-659 GEN
Solar/Wind Harmer
9.952
316359AB2-059 GEN
Solar/Wind Harmer
0.816
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.184
3142053HEARTS
Solar/Wind Harmer
0.405
316131AB2-060 GEN
Solar/Wind Harmer
0.678
970401AG2-262 GEN
Solar/Wind Harmer
1.241
315785AD2-033 C
Solar/Wind Harmer
1.709
316034AC1-036 C
Solar/Wind Harmer
0.014
316337AD2-073 GEN
Solar/Wind Harmer
0.178
970685AG2-442 GEN
Solar/Wind Harmer
15.239
971563AH1-280 GEN
Solar/Wind Harmer
2.155
3144293JTRSVLE
Adder
0.482
3144293JTRSVLE
Adder
0.381
316233AE1-074 FULL
Solar/Wind Harmer
0.149
971281AH1-106 GEN
Solar/Wind Harmer
2.577
971283AH1-107 GEN
Solar/Wind Harmer
2.577
971845AH1-439 GEN
Solar/Wind Harmer
7.42
270197AD1-017 GEN1
Solar/Wind Harmer
0.905
3148463FAIRFLD
Solar/Wind Harmer
0.137
3151881LOWMORC
Adder
1.462
3151881LOWMORC
Adder
1.439
3151861LOWMORA
Adder
1.416
3148133STUARTS
Solar/Wind Harmer
0.081
3148013FISHERV
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.767
316258AE1-075 C
Solar/Wind Harmer
0.1
270069AE2-166 C O1
Solar/Wind Harmer
5.596
316164AC1-076 GEN
Solar/Wind Helper
1.581
315651AD1-115 GEN
Solar/Wind Helper
0.988
226929AD2-058 GEN
Solar/Wind Helper
0.113
3138216PACIFIC
Solar/Wind Helper
0.046
3141426STAFORD
Solar/Wind Helper
0.056
23779801AA1-109
Solar/Wind Helper
0.162
237030AB1-096 C
Solar/Wind Helper
0.057
237025AB1-124 C
Solar/Wind Helper
0.141
971683AH1-343 GEN
Solar/Wind Harmer
7.057
3146926FARMVIL
Solar/Wind Harmer
0.11
316223AC1-118
Solar/Wind Harmer
0.125
3141906WESTMOR
Solar/Wind Harmer
0.07
316123AC1-075 GEN
Solar/Wind Harmer
0.233
3146776BUCKING
Solar/Wind Harmer
0.058
972003AH1-546 GEN
Solar/Wind Harmer
4.79
3151861LOWMORA
Adder
1.473
3147312GRETNA
Solar/Wind Harmer
0.027
3148013FISHERV
Solar/Wind Harmer
0.135
3143336POWHATN
Solar/Wind Harmer
2.027
315821AE2-092 GEN
Solar/Wind Harmer
0
970221AG2-151 GEN
Solar/Wind Harmer
7.102
270494AE1-108_GEN
Solar/Wind Harmer
1.538
943811AF1-049 GEN
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
3.412
3141196NOKESVL
Solar/Wind Helper
1.219
227287AC2-120 GEN
Solar/Wind Helper
0.385
226910AB2-157 C
Solar/Wind Helper
0.016
3147666LOUISA
Solar/Wind Helper
0.593
23777801MSM_W1-116
Solar/Wind Helper
0.097
3132273ORANGE
Solar/Wind Helper
0.045
3143526WINTERP
Solar/Wind Harmer
0.966
3146926FARMVIL
Solar/Wind Harmer
0.11
3146776BUCKING
Solar/Wind Harmer
0.065
970223AG2-152 GEN
Solar/Wind Harmer
10.386
3147123OTTER R
Solar/Wind Harmer
0.085
3147312GRETNA
Solar/Wind Harmer
0.108
3146802CHATHAM
Solar/Wind Harmer
0.102
941801AE2-185 GEN
Solar/Wind Harmer
4.336
970937AG2-583 GEN
Solar/Wind Harmer
8.26
3143336POWHATN
Solar/Wind Harmer
2.385
3143226MDLTHAN
Solar/Wind Harmer
0.133
971377AH1-170 GEN
Solar/Wind Harmer
1.42
3147623JAMES R
Solar/Wind Harmer
0.309
972135AH1-637 GEN
Solar/Wind Harmer
1.094
270030AE2-140 GEN
Solar/Wind Harmer
13.071
962751AG1-124 GEN
Solar/Wind Harmer
5.382
316447AC1-158 HLD
Solar/Wind Helper
4.521
316044AC1-158 PL1
Solar/Wind Helper
2.054
316415AF1-147_GEN2
Solar/Wind Helper
0.951
3147666LOUISA
Solar/Wind Helper
1.032
316192AB2-158 GEN
Solar/Wind Helper
1.7
3145593CAROLNA
Solar/Wind Harmer
0.252
3145593CAROLNA
Solar/Wind Harmer
0.314
3145796HORNRTN
Solar/Wind Harmer
0.753
3145783HORNRTN
Solar/Wind Harmer
4.46
3145783HORNRTN
Solar/Wind Harmer
3.568
3145783HORNRTN
Solar/Wind Harmer
1.115
3145783HORNRTN
Solar/Wind Harmer
0.446
3145933PARMELE
Solar/Wind Harmer
0.5
3145933PARMELE
Solar/Wind Harmer
0.25
316005AA1-067
Solar/Wind Harmer
0.26
970099AG2-077 GEN
Solar/Wind Harmer
26.001
315724AD1-057 GEN
Solar/Wind Harmer
4.616
3150341NORNECKC1
Adder
2.466
3150341NORNECKC1
Adder
2.447
3145493TOT1
Solar/Wind Harmer
0.545
3145453TOT5
Solar/Wind Harmer
0.327
3145603CNETO
Solar/Wind Harmer
0.218
961601AG1-000A GEN
Solar/Wind Harmer
4.087
316049AB1-081 GEN
Solar/Wind Harmer
1.307
316263AC1-034 GEN
Solar/Wind Harmer
8.73
972189AH1-679 GEN
Adder
3.65
962561AG1-105 GEN
Solar/Wind Harmer
10.202
964791AG1-342 GEN
Solar/Wind Harmer
4.06
3146843MT LREL
Solar/Wind Harmer
0.211
3146843MT LREL
Solar/Wind Harmer
0.211
970323AG2-213 GEN
Solar/Wind Harmer
8.949
316118AC1-105 GEN
Solar/Wind Harmer
0.535
970301AG2-198 GEN
Solar/Wind Harmer
8.779
958211AF2-115 GEN
Solar/Wind Harmer
2.425
3144293JTRSVLE
Adder
0.482
3147133PAMPLIN
Solar/Wind Harmer
0.199
3147133PAMPLIN
Solar/Wind Harmer
0.159
3143526WINTERP
Solar/Wind Harmer
0.966
942751AE2-291 GEN
Solar/Wind Harmer
9.096
3146776BUCKING
Solar/Wind Harmer
0.647
3146776BUCKING
Solar/Wind Harmer
0.052
942671AE2-283 GEN
Solar/Wind Harmer
3.372
316336AC2-165 C
Solar/Wind Harmer
6.804
316313AB2-026
Solar/Wind Harmer
0.083
971223AH1-071 GEN
Solar/Wind Harmer
1.425
316045AC1-158 PL2
Solar/Wind Helper
6.574
316450AC1-158 RIC
Solar/Wind Helper
0.548
316006AB2-029 C
Solar/Wind Helper
0.143
316411AF1-147_GEN1
Solar/Wind Helper
0.951
223401AF1-299 GEN
Solar/Wind Helper
0.348
223402AF1-300 C
Solar/Wind Helper
0.348
237006AB1-125 GEN
Solar/Wind Helper
0.105
LAGNLTFEXP_LAGN->PJM
CLTF
12.647
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.213
TVALTFEXP_TVA->PJM
CLTF
6.406
CPLELTFEXP_CPLE->PJM
CLTF
15.088
CBM West 2LTFEXP_CBM-W2->PJM
CBM
69.748
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.903
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.32
MECLTFEXP_MEC->PJM
CLTF
6.832
SIGELTFEXP_SIGE->PJM
CLTF
0.211
NYPJM->LTFIMP_NY
CLTF
4.065
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.334
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.11

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.7 %
Rating:4070.2 MVA
Rating Type:A
MVA to Mitigate:4464.82
MW Contribution:
4.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152191CUNINGD
50/50
5.572
972255AH1-712 GEN
50/50
168.651
3142416OLDCHRC
Solar/Wind Harmer
3.111
316075AC2-137 C
Solar/Wind Harmer
0.083
970293AG2-193 GEN
Solar/Wind Harmer
3.249
316473AC1-191 GEN
Solar/Wind Harmer
1.005
3142946ENON
Solar/Wind Harmer
0.098
3143096IRON208
Adder
1.179
3143096IRON208
Adder
1.155
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3150921YORKTN3
Adder
6.848
3144216WINCHST
Adder
1.021
3141766HARMONY
Solar/Wind Harmer
3.609
3141843SHACKLE
Adder
1.37
970133AG2-095 GEN
Solar/Wind Harmer
2.573
316203AE2-005 GEN
Solar/Wind Harmer
0
316458AB2-190 GEN2
Solar/Wind Harmer
1.413
3141873WAN 176
Solar/Wind Harmer
4.682
315778AD1-151 GEN
Solar/Wind Harmer
21.066
961611AG1-000B GEN
Solar/Wind Harmer
6.913
3151171GRAVELC
Adder
3.601
3150861SPRUNCD
Adder
1.166
3145336SMITFLD
Solar/Wind Harmer
0.101
3144536CHRHLND
Solar/Wind Harmer
0.037
3151101ELIZAR3
Adder
22.737
3144873MCLAUGH
Solar/Wind Harmer
0.006
944581AF1-123 GEN
Solar/Wind Harmer
54.896
944601AF1-125 GEN
Solar/Wind Harmer
54.051
316017AA1-139 ULT1
Solar/Wind Harmer
0.128
315813AE1-149 C
Solar/Wind Harmer
12.81
3146456SLIGO L269
Solar/Wind Harmer
0.24
971153AH1-033 GEN
Solar/Wind Harmer
2.775
316246AF1-032 C
Solar/Wind Harmer
0.106
970657AG2-426 GEN
Solar/Wind Harmer
5.364
316321Z2-027
Solar/Wind Harmer
0.042
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
3145273HOLLAND
Solar/Wind Harmer
0.17
3146376EDENTON
Solar/Wind Harmer
0.223
3150351NORNECKC2
Adder
2.179
315735AD1-075 GEN1
Solar/Wind Harmer
0.597
971781AH1-399 GEN
Solar/Wind Harmer
0.275
3146206CASHIE
Solar/Wind Harmer
0.206
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.339
3145893MURPHYS
Solar/Wind Harmer
0.202
3146173TUNIS
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.197
972277AH1-723 GEN
50/50
196.529
3142416OLDCHRC
Solar/Wind Harmer
0.834
3142416OLDCHRC
Solar/Wind Harmer
0.32
315975AC1-164 GENB
Solar/Wind Harmer
0.096
944631AF1-128 GEN
Adder
136.219
3143096IRON208
Adder
1.179
971317AH1-138 GEN
Solar/Wind Harmer
2.061
3142433PROV 92
Solar/Wind Harmer
1.097
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3138126ROCKLANDING
Solar/Wind Harmer
0.125
3141766HARMONY
Solar/Wind Harmer
0.054
3142543TWELFTH
Solar/Wind Harmer
0.026
971777AH1-397 GEN
Solar/Wind Harmer
0.708
316132AB2-190 GEN1
Solar/Wind Harmer
1.413
971069AG2-661 GEN
Solar/Wind Harmer
4.681
961611AG1-000B GEN
Solar/Wind Harmer
13.596
3151171GRAVELC
Adder
2.738
3138133OCRAN
Solar/Wind Harmer
0.153
315671AE2-027_GEN
Solar/Wind Harmer
0.002
3150851SPRUNCC
Adder
1.166
3145336SMITFLD
Solar/Wind Harmer
1.01
315773AC2-141 GEN
Solar/Wind Harmer
9.17
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.044
3150981CHESPKA
Adder
3.059
316072AD1-144
Solar/Wind Harmer
0.087
944591AF1-124 GEN
Solar/Wind Harmer
55.091
3142296MT RD221
50/50
1.09
3152181CUNINGC
50/50
2.56
3152171CUNINGB
50/50
2.409
3152161CUNINGA
50/50
2.396
972193AH1-681 GEN
50/50
7.535
3150691DARBY 3
50/50
22.92
3150701DARBY 4
50/50
22.867
3150681DARBY 2
50/50
22.84
3150671DARBY 1
50/50
22.813
3142366NRTHEST
50/50
1.032
316312AB1-027
Solar/Wind Harmer
0.571
315976AC1-164 GENA
Solar/Wind Harmer
3.257
316169AC1-164_GENC
Solar/Wind Harmer
2.815
966871AG1-558 GEN
Solar/Wind Harmer
0.344
3142946ENON
Solar/Wind Harmer
0.029
316156AD2-030 GEN
Solar/Wind Harmer
0.193
316033AB2-134 GEN
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
124.25
316294AC1-161 GEN
Solar/Wind Harmer
4.34
3150991CHESPKB
Adder
2.566
3150991CHESPKB
Adder
2.504
3145506HICKORY
Solar/Wind Harmer
0.969
3145506HICKORY
Solar/Wind Harmer
0.581
3145506HICKORY
Solar/Wind Harmer
0.145
316339AD2-160 GEN
Solar/Wind Harmer
0.386
316388AE2-253 GEN
Solar/Wind Harmer
0.75
3137176SLIGO L2192
Solar/Wind Harmer
0.956
3146456SLIGO L269
Solar/Wind Harmer
4.248
3130086AYDLETT
Solar/Wind Harmer
0.958
316349AD2-085 GEN
Solar/Wind Harmer
0.159
315835AF2-110_GEN
Solar/Wind Harmer
1.625
3146386ELIZ CT
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
3146626S HERTFORD
Solar/Wind Harmer
0.23
3146376EDENTON
Solar/Wind Harmer
0.993
3146376EDENTON
Solar/Wind Harmer
0.993
315742AE1-103 GEN
Solar/Wind Harmer
3.329
972189AH1-679 GEN
Adder
3.724
315614AA2-178 GEN
Solar/Wind Harmer
1.231
3143526WINTERP
Solar/Wind Harmer
1.123
3150341NORNECKC1
Adder
2.251
3150341NORNECKC1
Adder
2.233
316065AD1-022 GEN
Solar/Wind Harmer
9.567
3145893MURPHYS
Solar/Wind Harmer
1.355
3145893MURPHYS
Solar/Wind Harmer
0.364
3144356SAPONY
Solar/Wind Harmer
1.694
316315AB2-025 C
Solar/Wind Harmer
0.162
3146173TUNIS
Solar/Wind Harmer
0.2
3146173TUNIS
Solar/Wind Harmer
0.2
316140AB2-099
Solar/Wind Harmer
0.071
316365GEN2_N
Solar/Wind Harmer
0.427
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.113
962571AG1-106 GEN
Solar/Wind Harmer
2.664
3145933PARMELE
Solar/Wind Harmer
0.372
3145933PARMELE
Solar/Wind Harmer
0.186
313506AB2-031 GEN
Solar/Wind Harmer
0.569
3145593CAROLNA
Solar/Wind Harmer
0.185
3145593CAROLNA
Solar/Wind Harmer
0.185
3145593CAROLNA
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
3.28
3145783HORNRTN
Solar/Wind Harmer
2.624
3145783HORNRTN
Solar/Wind Harmer
0.82
3145783HORNRTN
Solar/Wind Harmer
0.328
3145796HORNRTN
Solar/Wind Harmer
0.553
971223AH1-071 GEN
Solar/Wind Harmer
1.934
316005AA1-067
Solar/Wind Harmer
0.193
315724AD1-057 GEN
Solar/Wind Harmer
3.373
972185AH1-677 GEN
Adder
9.672
3145493TOT1
Solar/Wind Harmer
0.399
3145453TOT5
Solar/Wind Harmer
0.239
3145603CNETO
Solar/Wind Harmer
0.16
972187AH1-678 GEN
Adder
4.872
970933AG2-581 GEN
Solar/Wind Harmer
13.555
961601AG1-000A GEN
Solar/Wind Harmer
2.976
316049AB1-081 GEN
Solar/Wind Harmer
0.951
316263AC1-034 GEN
Solar/Wind Harmer
6.355
316313AB2-026
Solar/Wind Harmer
0.101
970099AG2-077 GEN
Solar/Wind Harmer
17.361
316336AC2-165 C
Solar/Wind Harmer
8.008
970323AG2-213 GEN
Solar/Wind Harmer
6.629
970301AG2-198 GEN
Solar/Wind Harmer
6.539
958211AF2-115 GEN
Solar/Wind Harmer
1.837
3144293JTRSVLE
Adder
0.366
3147133PAMPLIN
Solar/Wind Harmer
0.152
3147133PAMPLIN
Solar/Wind Harmer
0.122
962561AG1-105 GEN
Solar/Wind Harmer
7.294
964791AG1-342 GEN
Solar/Wind Harmer
2.897
3146843MT LREL
Solar/Wind Harmer
0.151
3146843MT LREL
Solar/Wind Harmer
0.151
316118AC1-105 GEN
Solar/Wind Harmer
0.38
3146776BUCKING
Solar/Wind Harmer
0.568
3146776BUCKING
Solar/Wind Harmer
0.046
942751AE2-291 GEN
Solar/Wind Harmer
6.832
316045AC1-158 PL2
Solar/Wind Helper
5.278
316450AC1-158 RIC
Solar/Wind Helper
0.44
316006AB2-029 C
Solar/Wind Helper
0.118
316411AF1-147_GEN1
Solar/Wind Helper
0.803
316159AE1-175 C
Solar/Wind Harmer
0.245
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3143873LANEXA
Solar/Wind Harmer
0.165
3138283WHITEMARSH
Solar/Wind Harmer
0.062
970189AG2-124 GEN
Solar/Wind Harmer
7.942
3141873WAN 176
Solar/Wind Harmer
0.053
315697AD1-025 GEN
Solar/Wind Harmer
0.282
3151201GRAVEL4
Adder
18.738
3151221GRAVEL6
Adder
18.716
3151191GRAVEL3
Adder
18.501
3151211GRAVEL5
Adder
18.501
3141913WHIT STONE
Solar/Wind Harmer
0.256
3138133OCRAN
Solar/Wind Harmer
0.076
971445AH1-216 GEN
Solar/Wind Harmer
17.824
971285AH1-108 GEN
Adder
1.908
3141783LANCAST
Solar/Wind Harmer
0.15
3141783LANCAST
Solar/Wind Harmer
0.1
3151081ELIZAR1
Adder
22.45
3151091ELIZAR2
Adder
22.06
316316AC1-027 C
Solar/Wind Harmer
0.232
957871AF2-081 GEN
Solar/Wind Harmer
11.986
3146406KITTY HAWK
Solar/Wind Harmer
0.03
970657AG2-426 GEN
Solar/Wind Harmer
1.755
316311AC2-079 GEN
Solar/Wind Harmer
6.826
313526AB2-022
Solar/Wind Harmer
0.126
3146486SUNBURY
Solar/Wind Harmer
0.235
3146486SUNBURY
Solar/Wind Harmer
0.235
3146396TANGLEW
Solar/Wind Harmer
0.648
3145176PASQUOTANK
Solar/Wind Harmer
0.146
3143316POE
Solar/Wind Harmer
0.909
3130156CHOWAN
Solar/Wind Harmer
0.223
3130156CHOWAN
Solar/Wind Harmer
0.223
316233AE1-074 FULL
Solar/Wind Harmer
0.173
971281AH1-106 GEN
Solar/Wind Harmer
2.998
971283AH1-107 GEN
Solar/Wind Harmer
2.998
3141813NORNECK
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
0.211
315732AD1-074 GEN1
Solar/Wind Harmer
1.197
315733AD1-074 GEN2
Solar/Wind Harmer
1.197
3146206CASHIE
Solar/Wind Harmer
0.206
970601AG2-382 GEN
Solar/Wind Harmer
7.709
3145893MURPHYS
Solar/Wind Harmer
0.547
3145893MURPHYS
Solar/Wind Harmer
0.202
315814AE2-033 C
Solar/Wind Harmer
15.978
316463AE2-346 GEN
Solar/Wind Harmer
0.17
3145513AHOSKIE
Solar/Wind Harmer
0.417
3145513AHOSKIE
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.396
3145683EARLEYS
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.198
3146043SEABORD
Solar/Wind Harmer
0.194
316426AA2-053 GEN
Solar/Wind Harmer
0.628
315652AC1-086 GEN
Solar/Wind Harmer
20.595
3146033SCOT NK
Solar/Wind Harmer
0.747
3137643SOCKMAN
Solar/Wind Harmer
0.741
3145796HORNRTN
Solar/Wind Harmer
0.59
3145796HORNRTN
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
1.685
3145746EVERETS
Solar/Wind Harmer
0.719
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
316274AC1-208 GEN
Solar/Wind Harmer
0.927
957861AF2-080 GEN
Solar/Wind Harmer
7.595
970533AG2-339 GEN
Solar/Wind Harmer
13.243
316327AA2-057 GEN
Solar/Wind Harmer
0.257
970673AG2-436 GEN
Solar/Wind Harmer
21.668
3145573BETHELC
Solar/Wind Harmer
0.172
3145573BETHELC
Solar/Wind Harmer
0.172
971967AH1-528 GEN
Solar/Wind Harmer
27.442
970831AG2-522 GEN
Solar/Wind Harmer
7.302
970085AG2-068 GEN
Solar/Wind Harmer
8.84
970581AG2-369 GEN
Solar/Wind Harmer
7.602
316258AE1-075 C
Solar/Wind Harmer
0.122
316486AD2-202 GEN
Solar/Wind Harmer
0.162
3144303KENBRDG
Solar/Wind Harmer
0.124
970683AG2-441 GEN
Solar/Wind Harmer
9.293
970681AG2-440 GEN
Solar/Wind Harmer
6.168
946301AF1-294 GEN
Solar/Wind Harmer
3.021
961791AG1-021 GEN
Solar/Wind Harmer
1.47
3147173SINAI
Solar/Wind Harmer
0.146
3147243WELCO
Solar/Wind Harmer
0.091
971845AH1-439 GEN
Solar/Wind Harmer
6.462
3148133STUARTS
Solar/Wind Harmer
0.084
3148013FISHERV
Solar/Wind Harmer
0.08
3148463FAIRFLD
Solar/Wind Harmer
0.139
3151881LOWMORC
Adder
1.48
3151881LOWMORC
Adder
1.457
3151861LOWMORA
Adder
1.433
972205AH1-687 GEN
Adder
5.773
316164AC1-076 GEN
Solar/Wind Helper
1.298
226929AD2-058 GEN
Solar/Wind Helper
0.097
315651AD1-115 GEN
Solar/Wind Helper
0.804
3138216PACIFIC
Solar/Wind Helper
0.039
3146263WOODLND
Solar/Wind Harmer
0.195
3145823KELFORD
Solar/Wind Harmer
0.192
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
316011AB1-132 GEN
Solar/Wind Harmer
3.396
3145933PARMELE
Solar/Wind Harmer
0.186
316181AB2-040 GEN
Solar/Wind Harmer
0.264
3145796HORNRTN
Solar/Wind Harmer
0.737
3145796HORNRTN
Solar/Wind Harmer
0.184
316212AC1-099_GEN
Solar/Wind Harmer
0.94
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3147043LAWRENC
Solar/Wind Harmer
0.107
944011AF1-069 GEN
Solar/Wind Harmer
10.548
315722AD1-056 GEN
Solar/Wind Harmer
6.047
3146073TAR RVR
Solar/Wind Harmer
0.172
3146083TARBORO
Solar/Wind Harmer
0.172
3146233WITAKRS
Solar/Wind Harmer
0.857
3146233WITAKRS
Solar/Wind Harmer
0.116
3138543CONSLDL
Solar/Wind Harmer
0.112
961601AG1-000A GEN
Solar/Wind Harmer
11.904
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.167
971623AH1-311 GEN
Solar/Wind Harmer
0.334
970917AG2-570 GEN
Solar/Wind Harmer
14.853
3143336POWHATN
Solar/Wind Harmer
2.461
316223AC1-118
Solar/Wind Harmer
0.115
3141906WESTMOR
Solar/Wind Harmer
0.065
316478AD1-087 GEN
Solar/Wind Harmer
0.551
964241AG1-285 GEN
Solar/Wind Harmer
10.47
970257AG2-171 GEN
Solar/Wind Harmer
4.971
971775AH1-396 GEN
Solar/Wind Harmer
0.249
959311AF2-222 GEN
Solar/Wind Harmer
13.78
3144293JTRSVLE
Adder
0.366
3147133PAMPLIN
Solar/Wind Harmer
0.478
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.089
3146776BUCKING
Solar/Wind Harmer
0.051
3148013FISHERV
Solar/Wind Harmer
0.139
3151861LOWMORA
Adder
1.492
971683AH1-343 GEN
Solar/Wind Harmer
5.088
316222AC1-221 GEN
Solar/Wind Harmer
0.561
972003AH1-546 GEN
Solar/Wind Harmer
4.713
316283AC2-100 C
Solar/Wind Harmer
0.265
315821AE2-092 GEN
Solar/Wind Harmer
0
970221AG2-151 GEN
Solar/Wind Harmer
7.092
316123AC1-075 GEN
Solar/Wind Harmer
0.173
270494AE1-108_GEN
Solar/Wind Harmer
1.495
3141196NOKESVL
Solar/Wind Helper
1.032
227287AC2-120 GEN
Solar/Wind Helper
0.329
226910AB2-157 C
Solar/Wind Helper
0.013
3146456SLIGO L269
Solar/Wind Harmer
0.24
319010AE1-072 C
Solar/Wind Harmer
1.196
316381AD1-082 GEN
Solar/Wind Harmer
0.242
316093AE2-104_GEN
Solar/Wind Harmer
3.983
3146516WINFALL
Solar/Wind Harmer
0.752
3146516WINFALL
Solar/Wind Harmer
0.232
962861AG1-135 GEN
Solar/Wind Harmer
7.397
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.574
3141726DUNNSVL
Solar/Wind Harmer
0.893
3130156CHOWAN
Solar/Wind Harmer
0.223
315816AE2-034 GEN
Solar/Wind Harmer
0.923
3145663CRESWEL
Solar/Wind Harmer
0.606
971163AH1-040 GEN
Solar/Wind Harmer
17.314
3143526WINTERP
Solar/Wind Harmer
1.123
3150351NORNECKC2
Adder
2.143
315737AD1-076 GEN
Solar/Wind Harmer
2.694
3146206CASHIE
Solar/Wind Harmer
0.206
971547AH1-271 GEN
Solar/Wind Harmer
4.405
939411AE1-173 GEN
Solar/Wind Harmer
87.534
3145893MURPHYS
Solar/Wind Harmer
0.81
3145893MURPHYS
Solar/Wind Harmer
0.901
3156021HOLLOMANSOL
Solar/Wind Harmer
0.906
3146173TUNIS
Solar/Wind Harmer
0.2
3145683EARLEYS
Solar/Wind Harmer
0.198
3145963POPLR C
Solar/Wind Harmer
0.197
3146263WOODLND
Solar/Wind Harmer
0.195
315607AA1-063A GEN
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
0.192
940641AE2-051 GEN
Solar/Wind Harmer
15.404
316023GEN1_S
Solar/Wind Harmer
0.427
316337AD2-073 GEN
Solar/Wind Harmer
0.164
960081AF2-299 GEN
Solar/Wind Harmer
1.787
3146293MARTNCO
Solar/Wind Harmer
0.172
3145783HORNRTN
Solar/Wind Harmer
0.184
3145796HORNRTN
Solar/Wind Harmer
0.608
3145796HORNRTN
Solar/Wind Harmer
0.184
3143226MDLTHAN
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3147043LAWRENC
Adder
1.606
316494AC1-189 GEN
Solar/Wind Harmer
0.595
941031AE2-094 GEN
Solar/Wind Harmer
32.283
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.172
3145493TOT1
Solar/Wind Harmer
0.765
3146233WITAKRS
Solar/Wind Harmer
0.679
316129AC1-054 GEN
Solar/Wind Harmer
0.632
971065AG2-659 GEN
Solar/Wind Harmer
7.161
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.134
316359AB2-059 GEN
Solar/Wind Harmer
0.594
3142053HEARTS
Solar/Wind Harmer
0.294
970919AG2-571 GEN
Solar/Wind Harmer
5.941
970087AG2-069 GEN
Solar/Wind Harmer
13.26
3143336POWHATN
Solar/Wind Harmer
2.896
957481AF2-042 GEN
Solar/Wind Harmer
43.403
315693AD1-088 GEN
Solar/Wind Harmer
7.714
316131AB2-060 GEN
Solar/Wind Harmer
0.491
315785AD2-033 C
Solar/Wind Harmer
1.26
316034AC1-036 C
Solar/Wind Harmer
0.01
970685AG2-442 GEN
Solar/Wind Harmer
11.476
971563AH1-280 GEN
Solar/Wind Harmer
1.633
3144293JTRSVLE
Adder
0.366
3144293JTRSVLE
Adder
0.289
970401AG2-262 GEN
Solar/Wind Harmer
0.885
3146926FARMVIL
Solar/Wind Harmer
0.089
970937AG2-583 GEN
Solar/Wind Harmer
8.933
3146776BUCKING
Solar/Wind Harmer
0.057
971377AH1-170 GEN
Solar/Wind Harmer
1.418
3147623JAMES R
Solar/Wind Harmer
0.308
972135AH1-637 GEN
Solar/Wind Harmer
1.023
970223AG2-152 GEN
Solar/Wind Harmer
7.914
316447AC1-158 HLD
Solar/Wind Helper
3.629
316044AC1-158 PL1
Solar/Wind Helper
1.649
316415AF1-147_GEN2
Solar/Wind Helper
0.803
LAGNLTFEXP_LAGN->PJM
CLTF
9.763
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.968
TVALTFEXP_TVA->PJM
CLTF
4.966
CPLELTFEXP_CPLE->PJM
CLTF
10.775
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.743
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.302
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.412
MECLTFEXP_MEC->PJM
CLTF
5.481
SIGELTFEXP_SIGE->PJM
CLTF
0.171
NYPJM->LTFIMP_NY
CLTF
3.384
LGEELTFEXP_LGEE->PJM
CLTF
2.155
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2054-2135_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2054-2135_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.79 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5301.17
MW Contribution:
7.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316382AG1-145 C
Solar/Wind Harmer
0.967
316159AE1-175 C
Solar/Wind Harmer
0.861
3142433PROV 92
Adder
0.532
3152191CUNINGD
50/50
5.774
972255AH1-712 GEN
50/50
174.744
3142416OLDCHRC
Solar/Wind Harmer
3.629
316075AC2-137 C
Solar/Wind Harmer
0.933
970293AG2-193 GEN
Solar/Wind Harmer
4.27
316473AC1-191 GEN
Solar/Wind Harmer
3.582
3142946ENON
Solar/Wind Harmer
-0.011
3143096IRON208
Adder
1.178
3143096IRON208
Adder
1.155
3142433PROV 92
Adder
0.532
3142433PROV 92
Adder
0.532
3150921YORKTN3
Adder
6.839
3144216WINCHST
Adder
1.02
3141766HARMONY
Solar/Wind Harmer
2.697
970133AG2-095 GEN
Solar/Wind Harmer
3.385
3141843SHACKLE
Adder
1.364
316203AE2-005 GEN
Solar/Wind Harmer
12.648
316458AB2-190 GEN2
Solar/Wind Harmer
3.002
315778AD1-151 GEN
Solar/Wind Harmer
26.321
3142433PROV 92
Adder
0.532
3143873LANEXA
Solar/Wind Harmer
-0.018
316059AD1-063 C
Solar/Wind Harmer
0.683
957831AF2-077 GEN
Solar/Wind Harmer
0.903
3138283WHITEMARSH
Solar/Wind Harmer
0.047
957601AF2-054 GEN
Solar/Wind Harmer
0.882
3141873WAN 176
Solar/Wind Harmer
-0.006
315697AD1-025 GEN
Solar/Wind Harmer
5.942
3151201GRAVEL4
Adder
18.734
3151221GRAVEL6
Adder
18.712
3151191GRAVEL3
Adder
18.497
3151211GRAVEL5
Adder
18.497
3141913WHIT STONE
Solar/Wind Harmer
-0.029
971285AH1-108 GEN
Adder
1.912
971445AH1-216 GEN
Solar/Wind Harmer
17.601
3138133OCRAN
Solar/Wind Harmer
-0.009
316236AE1-162_GEN
Solar/Wind Harmer
0.854
3141783LANCAST
Solar/Wind Harmer
-0.017
3141783LANCAST
Solar/Wind Harmer
-0.011
315839AE2-212 C
Solar/Wind Harmer
0.832
3151081ELIZAR1
Adder
22.457
3151091ELIZAR2
Adder
22.067
316316AC1-027 C
Solar/Wind Harmer
0.84
316018AA1-139 ULT2
Solar/Wind Harmer
2.314
957871AF2-081 GEN
Solar/Wind Harmer
13.54
3146406KITTY HAWK
Solar/Wind Harmer
0.022
970657AG2-426 GEN
Solar/Wind Harmer
1.695
315833AF1-017_GEN
Solar/Wind Harmer
5.079
316311AC2-079 GEN
Solar/Wind Harmer
13.491
313526AB2-022
Solar/Wind Harmer
0.716
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146396TANGLEW
Solar/Wind Harmer
0.487
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3143316POE
Solar/Wind Harmer
-0.102
315800Z1-036_GEN1
Solar/Wind Harmer
6.27
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316233AE1-074 FULL
Solar/Wind Harmer
0.658
971281AH1-106 GEN
Solar/Wind Harmer
3.977
971283AH1-107 GEN
Solar/Wind Harmer
3.977
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.797
315733AD1-074 GEN2
Solar/Wind Harmer
4.797
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.231
316468AD1-105 GEN
Solar/Wind Harmer
2.652
316318V4-068
Solar/Wind Harmer
0.573
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
315814AE2-033 C
Solar/Wind Harmer
21.237
316463AE2-346 GEN
Solar/Wind Harmer
0.365
3145513AHOSKIE
Solar/Wind Harmer
0.197
961941AG1-037 GEN
Solar/Wind Harmer
0.17
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.022
3145683EARLEYS
Solar/Wind Harmer
-0.022
316174AB2-169 GEN
Solar/Wind Harmer
3.407
3146043SEABORD
Solar/Wind Harmer
-0.022
316426AA2-053 GEN
Solar/Wind Harmer
2.158
315652AC1-086 GEN
Solar/Wind Harmer
23.989
3146033SCOT NK
Solar/Wind Harmer
-0.085
946281AF1-292 GEN
Solar/Wind Harmer
0.477
3137643SOCKMAN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.067
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
3.26
3145746EVERETS
Solar/Wind Harmer
-0.082
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
316274AC1-208 GEN
Solar/Wind Harmer
2.21
316258AE1-075 C
Solar/Wind Harmer
0.488
316405AF2-144 C
Solar/Wind Harmer
0.515
957861AF2-080 GEN
Solar/Wind Harmer
8.799
316327AA2-057 GEN
Solar/Wind Harmer
2.008
970831AG2-522 GEN
Solar/Wind Harmer
9.901
3141873WAN 176
Solar/Wind Harmer
3.497
961611AG1-000B GEN
Solar/Wind Harmer
6.132
3151171GRAVELC
Adder
3.6
3150861SPRUNCD
Adder
1.168
3145336SMITFLD
Solar/Wind Harmer
-0.011
3144536CHRHLND
Solar/Wind Harmer
-0.004
3151101ELIZAR3
Adder
22.745
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142956BIRDNECK
Solar/Wind Harmer
1.471
944581AF1-123 GEN
Solar/Wind Harmer
124.654
944601AF1-125 GEN
Solar/Wind Harmer
122.709
316017AA1-139 ULT1
Solar/Wind Harmer
2.185
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.125
315813AE1-149 C
Solar/Wind Harmer
16.878
316305AF2-043 C
Solar/Wind Harmer
0.81
316246AF1-032 C
Solar/Wind Harmer
0.543
970657AG2-426 GEN
Solar/Wind Harmer
5.431
316320Y1-086
Solar/Wind Harmer
1.559
316321Z2-027
Solar/Wind Harmer
0.712
316484AD2-074 GEN
Solar/Wind Harmer
6.657
961951AG1-038 GEN
Solar/Wind Harmer
3.483
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
3146376EDENTON
Solar/Wind Harmer
-0.025
316077AC2-138 C
Solar/Wind Harmer
0.503
3150351NORNECKC2
Adder
2.158
315735AD1-075 GEN1
Solar/Wind Harmer
2.397
3156081AA2-088 GEN
Solar/Wind Harmer
7.586
3146206CASHIE
Solar/Wind Harmer
-0.023
971781AH1-399 GEN
Solar/Wind Harmer
1.43
3145893MURPHYS
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.022
3146263WOODLND
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.014
3145823KELFORD
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
316190AA2-174 GEN
Solar/Wind Harmer
0.263
316011AB1-132 GEN
Solar/Wind Harmer
4.454
966621AG1-532 GEN
Solar/Wind Harmer
0.432
316181AB2-040 GEN
Solar/Wind Harmer
2.957
3145933PARMELE
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.021
316212AC1-099_GEN
Solar/Wind Harmer
1.811
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3147043LAWRENC
Solar/Wind Harmer
-0.012
3143336POWHATN
Solar/Wind Harmer
2.034
315722AD1-056 GEN
Solar/Wind Harmer
7.113
316420AA1-050 GEN
Solar/Wind Harmer
2.264
944011AF1-069 GEN
Solar/Wind Harmer
11.629
3146073TAR RVR
Solar/Wind Harmer
-0.02
3146083TARBORO
Solar/Wind Harmer
-0.02
3146233WITAKRS
Solar/Wind Harmer
0.409
3146233WITAKRS
Solar/Wind Harmer
-0.013
3138543CONSLDL
Solar/Wind Harmer
-0.013
3148013FISHERV
Solar/Wind Harmer
-0.019
972003AH1-546 GEN
Solar/Wind Harmer
7.883
3146776BUCKING
Solar/Wind Harmer
-0.007
315821AE2-092 GEN
Solar/Wind Harmer
3.99
961601AG1-000A GEN
Solar/Wind Harmer
7.63
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.011
970221AG2-151 GEN
Solar/Wind Harmer
11.916
942461AE2-259 GEN
Solar/Wind Harmer
2.864
970917AG2-570 GEN
Solar/Wind Harmer
47.464
3147133PAMPLIN
Solar/Wind Harmer
-0.059
3144293JTRSVLE
Adder
0.402
959311AF2-222 GEN
Solar/Wind Harmer
19.687
970257AG2-171 GEN
Solar/Wind Harmer
7.068
971775AH1-396 GEN
Solar/Wind Harmer
1.33
3151861LOWMORA
Adder
1.726
3142296MT RD221
50/50
1.087
3152181CUNINGC
50/50
2.652
3152171CUNINGB
50/50
2.496
3152161CUNINGA
50/50
2.483
972193AH1-681 GEN
50/50
7.808
3150691DARBY 3
50/50
22.88
3150701DARBY 4
50/50
22.827
3150681DARBY 2
50/50
22.8
3150671DARBY 1
50/50
22.774
3142366NRTHEST
50/50
1.03
316312AB1-027
Solar/Wind Harmer
1.21
315976AC1-164 GENA
Solar/Wind Harmer
7.891
316169AC1-164_GENC
Solar/Wind Harmer
6.818
966871AG1-558 GEN
Solar/Wind Harmer
1.001
966871AG1-558 GEN
Solar/Wind Harmer
0.342
3142946ENON
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
2.022
315666AE1-190 GEN
Solar/Wind Harmer
0.895
316156AD2-030 GEN
Solar/Wind Harmer
0.785
316033AB2-134 GEN
Solar/Wind Harmer
9.481
944641AF1-129 GEN
Adder
124.218
316240AF1-291 C
Solar/Wind Harmer
0.869
316294AC1-161 GEN
Solar/Wind Harmer
9.123
3150991CHESPKB
Adder
2.567
3150991CHESPKB
Adder
2.505
316185AD1-033 GEN
Solar/Wind Harmer
2.876
3145506HICKORY
Solar/Wind Harmer
-0.108
3145506HICKORY
Solar/Wind Harmer
-0.065
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.823
316388AE2-253 GEN
Solar/Wind Harmer
1.823
3137176SLIGO L2192
Solar/Wind Harmer
-0.107
3146456SLIGO L269
Solar/Wind Harmer
3.189
3130086AYDLETT
Solar/Wind Harmer
-0.107
316083AB2-161 GEN
Solar/Wind Harmer
4.364
316349AD2-085 GEN
Solar/Wind Harmer
2.375
315835AF2-110_GEN
Solar/Wind Harmer
3.332
3146386ELIZ CT
Solar/Wind Harmer
-0.027
316487AF1-042 GEN
Solar/Wind Harmer
3.483
316431W1029_GEN1
Solar/Wind Harmer
4.755
316433W1029_GEN2
Solar/Wind Harmer
4.755
316435W1029_GEN3
Solar/Wind Harmer
4.755
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146376EDENTON
Solar/Wind Harmer
0.748
3146376EDENTON
Solar/Wind Harmer
0.748
315742AE1-103 GEN
Solar/Wind Harmer
5.975
972189AH1-679 GEN
Adder
3.68
3143526WINTERP
Solar/Wind Harmer
-0.127
315614AA2-178 GEN
Solar/Wind Harmer
2.631
3150341NORNECKC1
Adder
2.229
3150341NORNECKC1
Adder
2.212
316065AD1-022 GEN
Solar/Wind Harmer
11.763
3145893MURPHYS
Solar/Wind Harmer
0.642
3145893MURPHYS
Solar/Wind Harmer
-0.041
3144356SAPONY
Solar/Wind Harmer
0.797
316315AB2-025 C
Solar/Wind Harmer
0.615
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316140AB2-099
Solar/Wind Harmer
0.152
316365GEN2_N
Solar/Wind Harmer
1.466
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
962571AG1-106 GEN
Solar/Wind Harmer
3.065
313506AB2-031 GEN
Solar/Wind Harmer
1.702
3145593CAROLNA
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
0.176
3145933PARMELE
Solar/Wind Harmer
-0.042
3145933PARMELE
Solar/Wind Harmer
-0.021
3145783HORNRTN
Solar/Wind Harmer
2.502
3145783HORNRTN
Solar/Wind Harmer
2.002
3145783HORNRTN
Solar/Wind Harmer
0.626
3145783HORNRTN
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
-0.063
971223AH1-071 GEN
Solar/Wind Harmer
2.582
316005AA1-067
Solar/Wind Harmer
0.416
316313AB2-026
Solar/Wind Harmer
0.542
316336AC2-165 C
Solar/Wind Harmer
12.509
315724AD1-057 GEN
Solar/Wind Harmer
3.912
3145493TOT1
Solar/Wind Harmer
0.305
3145453TOT5
Solar/Wind Harmer
0.183
3145603CNETO
Solar/Wind Harmer
0.122
972185AH1-677 GEN
Adder
9.75
972187AH1-678 GEN
Adder
4.917
970933AG2-581 GEN
Solar/Wind Harmer
18.16
3146776BUCKING
Solar/Wind Harmer
-0.077
3146776BUCKING
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
7.535
316049AB1-081 GEN
Solar/Wind Harmer
2.061
316263AC1-034 GEN
Solar/Wind Harmer
8.979
970301AG2-198 GEN
Solar/Wind Harmer
9.522
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3147133PAMPLIN
Solar/Wind Harmer
-0.015
958211AF2-115 GEN
Solar/Wind Harmer
2.959
3144293JTRSVLE
Adder
0.402
970099AG2-077 GEN
Solar/Wind Harmer
23.615
970323AG2-213 GEN
Solar/Wind Harmer
9.424
316045AC1-158 PL2
Solar/Wind Helper
5.713
316450AC1-158 RIC
Solar/Wind Helper
0.476
966001AG1-469 GEN
Solar/Wind Helper
0.344
316006AB2-029 C
Solar/Wind Helper
0.143
972277AH1-723 GEN
50/50
203.63
3142416OLDCHRC
Solar/Wind Harmer
-0.093
3142416OLDCHRC
Solar/Wind Harmer
-0.036
315975AC1-164 GENB
Solar/Wind Harmer
0.233
944631AF1-128 GEN
Adder
136.056
3143096IRON208
Adder
1.178
971317AH1-138 GEN
Solar/Wind Harmer
3.87
316314AB2-024 C
Solar/Wind Harmer
2.632
3142433PROV 92
Solar/Wind Harmer
-0.122
3142433PROV 92
Adder
0.532
3142433PROV 92
Adder
0.532
3138126ROCKLANDING
Solar/Wind Harmer
0.093
3142543TWELFTH
Solar/Wind Harmer
-0.003
3141766HARMONY
Solar/Wind Harmer
-0.006
971777AH1-397 GEN
Solar/Wind Harmer
3.502
315662AE1-191 GEN
Solar/Wind Harmer
3.581
316280AD1-041 GEN
Solar/Wind Harmer
2.238
316132AB2-190 GEN1
Solar/Wind Harmer
3.002
971069AG2-661 GEN
Solar/Wind Harmer
4.679
316369SG1_INVT
Solar/Wind Harmer
5.251
961611AG1-000B GEN
Solar/Wind Harmer
14.371
3151171GRAVELC
Adder
2.738
3150851SPRUNCC
Adder
1.168
315671AE2-027_GEN
Solar/Wind Harmer
5.133
3138133OCRAN
Solar/Wind Harmer
-0.017
3145336SMITFLD
Solar/Wind Harmer
-0.113
315773AC2-141 GEN
Solar/Wind Harmer
11.805
316375AC2-012 GEN
Solar/Wind Harmer
9.522
316036AC1-147 C
Solar/Wind Harmer
0.741
3150981CHESPKA
Adder
3.06
316072AD1-144
Solar/Wind Harmer
0.556
944591AF1-124 GEN
Solar/Wind Harmer
125.103
3146456SLIGO L269
Solar/Wind Harmer
-0.027
319010AE1-072 C
Solar/Wind Harmer
5.445
316381AD1-082 GEN
Solar/Wind Harmer
2.461
316093AE2-104_GEN
Solar/Wind Harmer
7.75
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
962861AG1-135 GEN
Solar/Wind Harmer
9.667
316404AE1-155 C
Solar/Wind Harmer
4.875
958261AF2-120 GEN
Solar/Wind Harmer
9.897
315611Z1-036_GEN2
Solar/Wind Harmer
6.27
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.749
3141726DUNNSVL
Solar/Wind Harmer
-0.099
3143526WINTERP
Solar/Wind Harmer
-0.127
315816AE2-034 GEN
Solar/Wind Harmer
1.974
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.928
3150351NORNECKC2
Adder
2.122
315737AD1-076 GEN
Solar/Wind Harmer
4.509
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.847
939411AE1-173 GEN
Solar/Wind Harmer
115.349
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.682
3156021HOLLOMANSOL
Solar/Wind Harmer
3.069
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
3146263WOODLND
Solar/Wind Harmer
-0.022
315607AA1-063A GEN
Solar/Wind Harmer
2.216
3145823KELFORD
Solar/Wind Harmer
-0.022
316023GEN1_S
Solar/Wind Harmer
1.466
940641AE2-051 GEN
Solar/Wind Harmer
20.301
960081AF2-299 GEN
Solar/Wind Harmer
2.394
316087AB2-174 GEN
Solar/Wind Harmer
3.026
3146293MARTNCO
Solar/Wind Harmer
0.131
3145783HORNRTN
Solar/Wind Harmer
-0.021
316337AD2-073 GEN
Solar/Wind Harmer
0.564
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.021
3143226MDLTHAN
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3147043LAWRENC
Adder
1.651
3143336POWHATN
Solar/Wind Harmer
2.393
316494AC1-189 GEN
Solar/Wind Harmer
2.164
941031AE2-094 GEN
Solar/Wind Harmer
37.113
970937AG2-583 GEN
Solar/Wind Harmer
14.162
961671AG1-007 GEN
Solar/Wind Harmer
0.249
3146083TARBORO
Solar/Wind Harmer
-0.02
3145493TOT1
Solar/Wind Harmer
0.584
316129AC1-054 GEN
Solar/Wind Harmer
1.715
316319Z2-044 C
Solar/Wind Harmer
1.08
3146233WITAKRS
Solar/Wind Harmer
-0.077
971065AG2-659 GEN
Solar/Wind Harmer
9.74
3146776BUCKING
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3145543BTLEBRO
Solar/Wind Harmer
-0.015
316359AB2-059 GEN
Solar/Wind Harmer
2.576
3142053HEARTS
Solar/Wind Harmer
0.225
3146926FARMVIL
Solar/Wind Harmer
-0.011
971377AH1-170 GEN
Solar/Wind Harmer
2.383
3147623JAMES R
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
6.008
971563AH1-280 GEN
Solar/Wind Harmer
2.367
3144293JTRSVLE
Adder
0.402
3144293JTRSVLE
Adder
0.318
970685AG2-442 GEN
Solar/Wind Harmer
16.549
315693AD1-088 GEN
Solar/Wind Harmer
9.453
957481AF2-042 GEN
Solar/Wind Harmer
59.037
316034AC1-036 C
Solar/Wind Harmer
0.349
970087AG2-069 GEN
Solar/Wind Harmer
17.667
315785AD2-033 C
Solar/Wind Harmer
4.26
3147666LOUISA
Solar/Wind Helper
1.315
316192AB2-158 GEN
Solar/Wind Helper
2.211
316447AC1-158 HLD
Solar/Wind Helper
3.928
316044AC1-158 PL1
Solar/Wind Helper
1.785
316415AF1-147_GEN2
Solar/Wind Helper
0.859
316411AF1-147_GEN1
Solar/Wind Helper
0.859
970533AG2-339 GEN
Solar/Wind Harmer
13.311
3145573BETHELC
Solar/Wind Harmer
-0.02
3145573BETHELC
Solar/Wind Harmer
-0.02
970673AG2-436 GEN
Solar/Wind Harmer
43.061
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
971967AH1-528 GEN
Solar/Wind Harmer
36.679
3148133STUARTS
Solar/Wind Harmer
-0.012
3148013FISHERV
Solar/Wind Harmer
-0.011
972205AH1-687 GEN
Adder
7.385
316322AB2-045
Solar/Wind Harmer
0.647
971845AH1-439 GEN
Solar/Wind Harmer
10.232
946301AF1-294 GEN
Solar/Wind Harmer
4.852
961791AG1-021 GEN
Solar/Wind Harmer
2.367
970683AG2-441 GEN
Solar/Wind Harmer
13.344
970681AG2-440 GEN
Solar/Wind Harmer
8.856
3144303KENBRDG
Solar/Wind Harmer
-0.015
970085AG2-068 GEN
Solar/Wind Harmer
11.778
970581AG2-369 GEN
Solar/Wind Harmer
10.129
3151881LOWMORC
Adder
1.713
3151881LOWMORC
Adder
1.686
3151861LOWMORA
Adder
1.659
316164AC1-076 GEN
Solar/Wind Helper
1.629
315651AD1-115 GEN
Solar/Wind Helper
1.077
226929AD2-058 GEN
Solar/Wind Helper
0.103
3138216PACIFIC
Solar/Wind Helper
0.042
3141426STAFORD
Solar/Wind Helper
0.051
3147666LOUISA
Solar/Wind Helper
0.756
3132273ORANGE
Solar/Wind Helper
0.065
3141196NOKESVL
Solar/Wind Helper
1.112
227287AC2-120 GEN
Solar/Wind Helper
0.349
226910AB2-157 C
Solar/Wind Helper
0.014
964241AG1-285 GEN
Solar/Wind Harmer
5.297
LAGNLTFEXP_LAGN->PJM
CLTF
10.444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.085
TVALTFEXP_TVA->PJM
CLTF
5.318
CPLELTFEXP_CPLE->PJM
CLTF
11.149
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.15
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.698
MECLTFEXP_MEC->PJM
CLTF
5.97
SIGELTFEXP_SIGE->PJM
CLTF
0.187
NYPJM->LTFIMP_NY
CLTF
3.569
LGEELTFEXP_LGEE->PJM
CLTF
2.362
WECLTFEXP_WEC->PJM
CLTF
1.192
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.1

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.05 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4723.52
MW Contribution:
5.49
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
38.362
3150381LDYSMT2
50/50
36.714
972213AH1-691 GEN
50/50
6.211
972215AH1-692 GEN
50/50
6.211
316233AE1-074 FULL
Solar/Wind Harmer
0.199
3152251N ANNA1
50/50
14.627
972197AH1-683 GEN
50/50
5.972
972219AH1-694 GEN
50/50
4.3
315052AA1-145 CT2
50/50
2.083
966881AG1-559 GEN
Solar/Wind Harmer
0.307
3142416OLDCHRC
Solar/Wind Harmer
0.66
971281AH1-106 GEN
Solar/Wind Harmer
3.452
971283AH1-107 GEN
Solar/Wind Harmer
3.452
971285AH1-108 GEN
Adder
1.876
316159AE1-175 C
Solar/Wind Harmer
0.208
315697AD1-025 GEN
Solar/Wind Harmer
0.26
3142433PROV 92
Adder
0.468
3142433PROV 92
Adder
0.468
3151201GRAVEL4
Adder
17.442
3151221GRAVEL6
Adder
17.422
3151191GRAVEL3
Adder
17.222
3151211GRAVEL5
Adder
17.222
971445AH1-216 GEN
Solar/Wind Harmer
16.803
3143873LANEXA
Solar/Wind Harmer
0.143
3143316POE
Solar/Wind Harmer
0.943
3138283WHITEMARSH
Solar/Wind Harmer
0.055
3151081ELIZAR1
Adder
21.702
3151091ELIZAR2
Adder
21.325
970657AG2-426 GEN
Solar/Wind Harmer
1.736
970189AG2-124 GEN
Solar/Wind Harmer
7.002
316316AC1-027 C
Solar/Wind Harmer
0.225
3141873WAN 176
Solar/Wind Harmer
0.047
957871AF2-081 GEN
Solar/Wind Harmer
11.661
316311AC2-079 GEN
Solar/Wind Harmer
6.716
3146406KITTY HAWK
Solar/Wind Harmer
0.029
3141913WHIT STONE
Solar/Wind Harmer
0.232
313526AB2-022
Solar/Wind Harmer
0.123
3138133OCRAN
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.23
3146486SUNBURY
Solar/Wind Harmer
0.23
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
3141783LANCAST
Solar/Wind Harmer
0.138
3141783LANCAST
Solar/Wind Harmer
0.092
970533AG2-339 GEN
Solar/Wind Harmer
17.052
315814AE2-033 C
Solar/Wind Harmer
17.827
970673AG2-436 GEN
Solar/Wind Harmer
27.806
3130156CHOWAN
Solar/Wind Harmer
0.222
3130156CHOWAN
Solar/Wind Harmer
0.222
971967AH1-528 GEN
Solar/Wind Harmer
34.913
3141813NORNECK
Solar/Wind Harmer
0.216
3130546PLYMOUTH
Solar/Wind Harmer
0.213
315732AD1-074 GEN1
Solar/Wind Harmer
1.209
315733AD1-074 GEN2
Solar/Wind Harmer
1.209
316258AE1-075 C
Solar/Wind Harmer
0.158
3146206CASHIE
Solar/Wind Harmer
0.21
970601AG2-382 GEN
Solar/Wind Harmer
7.841
3145893MURPHYS
Solar/Wind Harmer
0.564
3145893MURPHYS
Solar/Wind Harmer
0.209
970085AG2-068 GEN
Solar/Wind Harmer
11.063
970581AG2-369 GEN
Solar/Wind Harmer
9.514
316463AE2-346 GEN
Solar/Wind Harmer
0.176
3145513AHOSKIE
Solar/Wind Harmer
0.431
3145513AHOSKIE
Solar/Wind Harmer
0.206
3145683EARLEYS
Solar/Wind Harmer
0.41
3145683EARLEYS
Solar/Wind Harmer
0.205
3145683EARLEYS
Solar/Wind Harmer
0.205
3146043SEABORD
Solar/Wind Harmer
0.204
315652AC1-086 GEN
Solar/Wind Harmer
22.096
3137643SOCKMAN
Solar/Wind Harmer
0.799
316426AA2-053 GEN
Solar/Wind Harmer
0.669
3145796HORNRTN
Solar/Wind Harmer
0.633
3145796HORNRTN
Solar/Wind Harmer
0.079
3146033SCOT NK
Solar/Wind Harmer
0.786
316486AD2-202 GEN
Solar/Wind Harmer
0.197
316210AC1-098 GEN
Solar/Wind Harmer
1.786
316274AC1-208 GEN
Solar/Wind Harmer
0.988
970831AG2-522 GEN
Solar/Wind Harmer
8.11
3145746EVERETS
Solar/Wind Harmer
0.751
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
316327AA2-057 GEN
Solar/Wind Harmer
0.275
957861AF2-080 GEN
Solar/Wind Harmer
8.003
3145573BETHELC
Solar/Wind Harmer
0.183
3145573BETHELC
Solar/Wind Harmer
0.183
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
10.809
3152261N ANNA2
50/50
14.634
3150401LDYSMT4
50/50
38.243
3150371LDYSMT1
50/50
36.953
315051AA1-145 CT1
50/50
2.07
3142416OLDCHRC
Solar/Wind Harmer
2.462
970293AG2-193 GEN
Solar/Wind Harmer
2.675
316075AC2-137 C
Solar/Wind Harmer
0.067
3143096IRON208
Adder
1.043
3143096IRON208
Adder
1.023
3150861SPRUNCD
Adder
1.146
316473AC1-191 GEN
Solar/Wind Harmer
0.838
3142946ENON
Solar/Wind Harmer
0.083
970133AG2-095 GEN
Solar/Wind Harmer
2.346
316458AB2-190 GEN2
Solar/Wind Harmer
1.296
315778AD1-151 GEN
Solar/Wind Harmer
19.38
3142433PROV 92
Adder
0.468
3142433PROV 92
Adder
0.468
3150921YORKTN3
Adder
6.048
3144216WINCHST
Adder
0.907
961611AG1-000B GEN
Solar/Wind Harmer
6.412
3151171GRAVELC
Adder
3.352
3145336SMITFLD
Solar/Wind Harmer
0.095
315813AE1-149 C
Solar/Wind Harmer
12.72
3144536CHRHLND
Solar/Wind Harmer
0.035
944581AF1-123 GEN
Solar/Wind Harmer
53.298
944601AF1-125 GEN
Solar/Wind Harmer
52.477
3151101ELIZAR3
Adder
21.98
3142416OLDCHRC
Solar/Wind Harmer
0.253
3143096IRON208
Adder
1.043
3143526WINTERP
Solar/Wind Harmer
1.293
3150851SPRUNCC
Adder
1.146
3142543TWELFTH
Solar/Wind Harmer
0.024
315975AC1-164 GENB
Solar/Wind Harmer
0.077
3143226MDLTHAN
Solar/Wind Harmer
0.247
944631AF1-128 GEN
Adder
117.82
316132AB2-190 GEN1
Solar/Wind Harmer
1.296
315671AE2-027_GEN
Solar/Wind Harmer
0.002
971069AG2-661 GEN
Solar/Wind Harmer
4.307
971317AH1-138 GEN
Solar/Wind Harmer
1.798
3142433PROV 92
Solar/Wind Harmer
0.962
3142433PROV 92
Adder
0.468
3142433PROV 92
Adder
0.468
3138126ROCKLANDING
Solar/Wind Harmer
0.11
961611AG1-000B GEN
Solar/Wind Harmer
12.609
3151171GRAVELC
Adder
2.549
315773AC2-141 GEN
Solar/Wind Harmer
8.73
3145336SMITFLD
Solar/Wind Harmer
0.954
944591AF1-124 GEN
Solar/Wind Harmer
53.488
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.042
3150981CHESPKA
Adder
2.955
316381AD1-082 GEN
Solar/Wind Harmer
0.24
3141766HARMONY
Solar/Wind Harmer
0.047
971777AH1-397 GEN
Solar/Wind Harmer
0.624
316072AD1-144
Solar/Wind Harmer
0.084
939411AE1-173 GEN
Solar/Wind Harmer
100.161
970681AG2-440 GEN
Solar/Wind Harmer
7.174
946301AF1-294 GEN
Solar/Wind Harmer
3.526
961791AG1-021 GEN
Solar/Wind Harmer
1.715
944491AF1-114 GEN
Solar/Wind Harmer
0
971845AH1-439 GEN
Solar/Wind Harmer
7.612
3147173SINAI
Solar/Wind Harmer
0.166
3147243WELCO
Solar/Wind Harmer
0.104
972205AH1-687 GEN
Adder
6.712
316164AC1-076 GEN
Solar/Wind Helper
1.956
315651AD1-115 GEN
Solar/Wind Helper
0.968
3138216PACIFIC
Solar/Wind Helper
0.039
940641AE2-051 GEN
Solar/Wind Harmer
18.753
3146456SLIGO L269
Solar/Wind Harmer
0.234
319010AE1-072 C
Solar/Wind Harmer
1.165
316093AE2-104_GEN
Solar/Wind Harmer
3.905
3138133OCRAN
Solar/Wind Harmer
0.139
3146516WINFALL
Solar/Wind Harmer
0.739
3146516WINFALL
Solar/Wind Harmer
0.228
941031AE2-094 GEN
Solar/Wind Harmer
41.566
962861AG1-135 GEN
Solar/Wind Harmer
7.123
3130156CHOWAN
Solar/Wind Harmer
0.222
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.335
3141726DUNNSVL
Solar/Wind Harmer
0.877
315816AE2-034 GEN
Solar/Wind Harmer
0.925
3145663CRESWEL
Solar/Wind Harmer
0.607
971163AH1-040 GEN
Solar/Wind Harmer
17.349
3150351NORNECKC2
Adder
2.159
315737AD1-076 GEN
Solar/Wind Harmer
2.723
3143336POWHATN
Solar/Wind Harmer
3.761
3146206CASHIE
Solar/Wind Harmer
0.21
971547AH1-271 GEN
Solar/Wind Harmer
4.48
970919AG2-571 GEN
Solar/Wind Harmer
7.467
316023GEN1_S
Solar/Wind Harmer
0.465
3145893MURPHYS
Solar/Wind Harmer
0.836
3145893MURPHYS
Solar/Wind Harmer
0.929
316337AD2-073 GEN
Solar/Wind Harmer
0.179
970087AG2-069 GEN
Solar/Wind Harmer
16.594
3146173TUNIS
Solar/Wind Harmer
0.207
3156021HOLLOMANSOL
Solar/Wind Harmer
0.93
3145683EARLEYS
Solar/Wind Harmer
0.205
960081AF2-299 GEN
Solar/Wind Harmer
1.957
315607AA1-063A GEN
Solar/Wind Harmer
0.41
3146263WOODLND
Solar/Wind Harmer
0.203
3145963POPLR C
Solar/Wind Harmer
0.202
3145823KELFORD
Solar/Wind Harmer
0.201
957481AF2-042 GEN
Solar/Wind Harmer
53.504
3145783HORNRTN
Solar/Wind Harmer
0.198
3145796HORNRTN
Solar/Wind Harmer
0.652
3145796HORNRTN
Solar/Wind Harmer
0.198
3147043LAWRENC
Adder
1.783
315693AD1-088 GEN
Solar/Wind Harmer
9.436
3146293MARTNCO
Solar/Wind Harmer
0.179
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
316129AC1-054 GEN
Solar/Wind Harmer
0.705
971065AG2-659 GEN
Solar/Wind Harmer
8.02
316494AC1-189 GEN
Solar/Wind Harmer
0.627
972135AH1-637 GEN
Solar/Wind Harmer
1.561
961671AG1-007 GEN
Solar/Wind Harmer
0.028
3146083TARBORO
Solar/Wind Harmer
0.183
3145493TOT1
Solar/Wind Harmer
0.813
3146233WITAKRS
Solar/Wind Harmer
0.727
3147666LOUISA
Solar/Wind Harmer
0.728
316131AB2-060 GEN
Solar/Wind Harmer
0.565
315785AD2-033 C
Solar/Wind Harmer
1.458
316034AC1-036 C
Solar/Wind Harmer
0.012
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.143
316359AB2-059 GEN
Solar/Wind Harmer
0.637
3142053HEARTS
Solar/Wind Harmer
0.316
970685AG2-442 GEN
Solar/Wind Harmer
13.369
971563AH1-280 GEN
Solar/Wind Harmer
1.906
3144293JTRSVLE
Adder
0.427
3144293JTRSVLE
Adder
0.337
970937AG2-583 GEN
Solar/Wind Harmer
10.9
316192AB2-158 GEN
Solar/Wind Harmer
0.993
3146926FARMVIL
Solar/Wind Harmer
0.105
970401AG2-262 GEN
Solar/Wind Harmer
1.011
3146776BUCKING
Solar/Wind Harmer
0.067
972277AH1-723 GEN
Adder
99.398
971377AH1-170 GEN
Solar/Wind Harmer
1.577
3147623JAMES R
Solar/Wind Harmer
0.343
316447AC1-158 HLD
Solar/Wind Helper
4.878
316044AC1-158 PL1
Solar/Wind Helper
2.217
316415AF1-147_GEN2
Solar/Wind Helper
0.804
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.153
970657AG2-426 GEN
Solar/Wind Harmer
5.304
3141843SHACKLE
Adder
1.207
316203AE2-005 GEN
Solar/Wind Harmer
0
3141873WAN 176
Solar/Wind Harmer
4.17
316017AA1-139 ULT1
Solar/Wind Harmer
0.125
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.702
316246AF1-032 C
Solar/Wind Harmer
0.104
316321Z2-027
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.169
944011AF1-069 GEN
Solar/Wind Harmer
13.581
3146376EDENTON
Solar/Wind Harmer
0.222
3150351NORNECKC2
Adder
2.195
971781AH1-399 GEN
Solar/Wind Harmer
0.285
315735AD1-075 GEN1
Solar/Wind Harmer
0.604
3156081AA2-088 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.196
3146206CASHIE
Solar/Wind Harmer
0.21
970917AG2-570 GEN
Solar/Wind Harmer
18.667
3145893MURPHYS
Solar/Wind Harmer
0.35
3145893MURPHYS
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.207
3146263WOODLND
Solar/Wind Harmer
0.203
3145963POPLR C
Solar/Wind Harmer
0.202
316181AB2-040 GEN
Solar/Wind Harmer
0.287
3142666NORTHAMPTON
Solar/Wind Harmer
0.201
316011AB1-132 GEN
Solar/Wind Harmer
3.644
3145823KELFORD
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.791
3145796HORNRTN
Solar/Wind Harmer
0.198
316223AC1-118
Solar/Wind Harmer
0.141
3141906WESTMOR
Solar/Wind Harmer
0.079
3147043LAWRENC
Solar/Wind Harmer
0.118
316478AD1-087 GEN
Solar/Wind Harmer
0.67
316212AC1-099_GEN
Solar/Wind Harmer
0.996
3145933PARMELE
Solar/Wind Harmer
0.193
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
315722AD1-056 GEN
Solar/Wind Harmer
6.485
3146073TAR RVR
Solar/Wind Harmer
0.183
3146083TARBORO
Solar/Wind Harmer
0.183
3146233WITAKRS
Solar/Wind Harmer
0.917
3146233WITAKRS
Solar/Wind Harmer
0.124
3138543CONSLDL
Solar/Wind Harmer
0.12
3147666LOUISA
Solar/Wind Harmer
0.419
964241AG1-285 GEN
Solar/Wind Harmer
12.07
970257AG2-171 GEN
Solar/Wind Harmer
5.761
971775AH1-396 GEN
Solar/Wind Harmer
0.288
959311AF2-222 GEN
Solar/Wind Harmer
15.987
961601AG1-000A GEN
Solar/Wind Harmer
12.757
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
971623AH1-311 GEN
Solar/Wind Harmer
0.359
3144293JTRSVLE
Adder
0.427
3147133PAMPLIN
Solar/Wind Harmer
0.559
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.105
3146776BUCKING
Solar/Wind Harmer
0.06
972255AH1-712 GEN
Adder
85.298
972003AH1-546 GEN
Solar/Wind Harmer
5.488
971683AH1-343 GEN
Solar/Wind Harmer
5.586
316222AC1-221 GEN
Solar/Wind Harmer
0.621
316283AC2-100 C
Solar/Wind Harmer
0.294
970221AG2-151 GEN
Solar/Wind Harmer
7.883
316123AC1-075 GEN
Solar/Wind Harmer
0.181
270494AE1-108_GEN
Solar/Wind Harmer
1.571
3150331BIRCHWDA
Adder
22.077
315821AE2-092 GEN
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.252
3150391LDYSMT3
50/50
38.171
972195AH1-682 GEN
50/50
5.016
972189AH1-679 GEN
50/50
4.649
3142296MT RD221
50/50
0.869
3142366NRTHEST
50/50
0.874
3150691DARBY 3
50/50
19.218
315673AE1-157 GEN
Solar/Wind Harmer
18.436
316312AB1-027
Solar/Wind Harmer
0.452
3150701DARBY 4
Adder
18.069
3150681DARBY 2
Adder
18.048
3150671DARBY 1
Adder
18.027
3143526WINTERP
Solar/Wind Harmer
1.293
966871AG1-558 GEN
Solar/Wind Harmer
0.287
315976AC1-164 GENA
Solar/Wind Harmer
2.606
316169AC1-164_GENC
Solar/Wind Harmer
2.252
971223AH1-071 GEN
Solar/Wind Harmer
2.642
3142946ENON
Solar/Wind Harmer
0.025
944641AF1-129 GEN
Adder
116.711
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
4.132
3150991CHESPKB
Adder
2.479
3150991CHESPKB
Adder
2.42
3145506HICKORY
Solar/Wind Harmer
0.941
3145506HICKORY
Solar/Wind Harmer
0.564
3145506HICKORY
Solar/Wind Harmer
0.141
316156AD2-030 GEN
Solar/Wind Harmer
0.172
316339AD2-160 GEN
Solar/Wind Harmer
0.375
316388AE2-253 GEN
Solar/Wind Harmer
0.73
316349AD2-085 GEN
Solar/Wind Harmer
0.156
3137176SLIGO L2192
Solar/Wind Harmer
0.93
3146456SLIGO L269
Solar/Wind Harmer
4.136
3130086AYDLETT
Solar/Wind Harmer
0.933
315835AF2-110_GEN
Solar/Wind Harmer
1.593
3146386ELIZ CT
Solar/Wind Harmer
0.231
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
3144356SAPONY
Solar/Wind Harmer
1.892
316315AB2-025 C
Solar/Wind Harmer
0.181
315742AE1-103 GEN
Solar/Wind Harmer
3.33
3146376EDENTON
Solar/Wind Harmer
0.986
3146376EDENTON
Solar/Wind Harmer
0.986
972185AH1-677 GEN
Adder
12.347
972187AH1-678 GEN
Adder
6.195
315614AA2-178 GEN
Solar/Wind Harmer
1.234
3150341NORNECKC1
Adder
2.268
3150341NORNECKC1
Adder
2.25
970933AG2-581 GEN
Solar/Wind Harmer
17.123
316313AB2-026
Solar/Wind Harmer
0.132
316065AD1-022 GEN
Solar/Wind Harmer
9.708
316365GEN2_N
Solar/Wind Harmer
0.465
3145893MURPHYS
Solar/Wind Harmer
1.399
3145893MURPHYS
Solar/Wind Harmer
0.376
3146173TUNIS
Solar/Wind Harmer
0.207
3146173TUNIS
Solar/Wind Harmer
0.207
316140AB2-099
Solar/Wind Harmer
0.073
316336AC2-165 C
Solar/Wind Harmer
10.238
313506AB2-031 GEN
Solar/Wind Harmer
0.618
3142666NORTHAMPTON
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.121
962571AG1-106 GEN
Solar/Wind Harmer
2.858
970099AG2-077 GEN
Solar/Wind Harmer
21.401
3145593CAROLNA
Solar/Wind Harmer
0.199
3145593CAROLNA
Solar/Wind Harmer
0.199
3145593CAROLNA
Solar/Wind Harmer
0.248
3145783HORNRTN
Solar/Wind Harmer
3.518
3145783HORNRTN
Solar/Wind Harmer
2.815
3145783HORNRTN
Solar/Wind Harmer
0.88
3145783HORNRTN
Solar/Wind Harmer
0.352
3145796HORNRTN
Solar/Wind Harmer
0.593
3145933PARMELE
Solar/Wind Harmer
0.386
3145933PARMELE
Solar/Wind Harmer
0.193
316005AA1-067
Solar/Wind Harmer
0.202
315724AD1-057 GEN
Solar/Wind Harmer
3.617
970301AG2-198 GEN
Solar/Wind Harmer
7.87
3145493TOT1
Solar/Wind Harmer
0.424
3145453TOT5
Solar/Wind Harmer
0.254
3145603CNETO
Solar/Wind Harmer
0.17
970323AG2-213 GEN
Solar/Wind Harmer
7.682
961601AG1-000A GEN
Solar/Wind Harmer
3.189
316049AB1-081 GEN
Solar/Wind Harmer
1.02
316263AC1-034 GEN
Solar/Wind Harmer
6.813
958211AF2-115 GEN
Solar/Wind Harmer
2.144
3144293JTRSVLE
Adder
0.427
3147133PAMPLIN
Solar/Wind Harmer
0.178
3147133PAMPLIN
Solar/Wind Harmer
0.142
962561AG1-105 GEN
Solar/Wind Harmer
8.343
964791AG1-342 GEN
Solar/Wind Harmer
3.31
3146843MT LREL
Solar/Wind Harmer
0.172
3146843MT LREL
Solar/Wind Harmer
0.172
316118AC1-105 GEN
Solar/Wind Harmer
0.433
3146776BUCKING
Solar/Wind Harmer
0.668
3146776BUCKING
Solar/Wind Harmer
0.054
972193AH1-681 GEN
Adder
3.811
942751AE2-291 GEN
Solar/Wind Harmer
6.973
316045AC1-158 PL2
Solar/Wind Helper
7.094
316450AC1-158 RIC
Solar/Wind Helper
0.591
316006AB2-029 C
Solar/Wind Helper
0.146
316411AF1-147_GEN1
Solar/Wind Helper
0.804
LAGNLTFEXP_LAGN->PJM
CLTF
8.17
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.357
TVALTFEXP_TVA->PJM
CLTF
4.141
CPLELTFEXP_CPLE->PJM
CLTF
11.555
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.284
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.156
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.099
MECLTFEXP_MEC->PJM
CLTF
3.718
SIGELTFEXP_SIGE->PJM
CLTF
0.113
NYPJM->LTFIMP_NY
CLTF
3.219
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.664

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.79 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4672.2
MW Contribution:
5.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
37.466
3150381LDYSMT2
50/50
35.856
972213AH1-691 GEN
50/50
6.065
972215AH1-692 GEN
50/50
6.065
971285AH1-108 GEN
Adder
1.81
316233AE1-074 FULL
Solar/Wind Harmer
0.192
971281AH1-106 GEN
Solar/Wind Harmer
3.322
971283AH1-107 GEN
Solar/Wind Harmer
3.322
316159AE1-175 C
Solar/Wind Harmer
0.201
315697AD1-025 GEN
Solar/Wind Harmer
0.251
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3151201GRAVEL4
Adder
16.824
3151221GRAVEL6
Adder
16.805
3151191GRAVEL3
Adder
16.611
3151211GRAVEL5
Adder
16.611
3143873LANEXA
Solar/Wind Harmer
0.138
971445AH1-216 GEN
Solar/Wind Harmer
16.201
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143316POE
Solar/Wind Harmer
0.909
970189AG2-124 GEN
Solar/Wind Harmer
6.771
3151081ELIZAR1
Adder
20.909
3151091ELIZAR2
Adder
20.546
970657AG2-426 GEN
Solar/Wind Harmer
1.673
316316AC1-027 C
Solar/Wind Harmer
0.217
3141873WAN 176
Solar/Wind Harmer
0.045
957871AF2-081 GEN
Solar/Wind Harmer
11.233
316311AC2-079 GEN
Solar/Wind Harmer
6.47
3146406KITTY HAWK
Solar/Wind Harmer
0.028
3141913WHIT STONE
Solar/Wind Harmer
0.224
3138133OCRAN
Solar/Wind Harmer
0.067
313526AB2-022
Solar/Wind Harmer
0.119
3146486SUNBURY
Solar/Wind Harmer
0.222
3146486SUNBURY
Solar/Wind Harmer
0.222
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
3146396TANGLEW
Solar/Wind Harmer
0.611
3145176PASQUOTANK
Solar/Wind Harmer
0.137
315814AE2-033 C
Solar/Wind Harmer
17.143
970533AG2-339 GEN
Solar/Wind Harmer
16.359
970673AG2-436 GEN
Solar/Wind Harmer
26.678
3130156CHOWAN
Solar/Wind Harmer
0.214
3130156CHOWAN
Solar/Wind Harmer
0.214
3141813NORNECK
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
33.507
3130546PLYMOUTH
Solar/Wind Harmer
0.205
315732AD1-074 GEN1
Solar/Wind Harmer
1.164
315733AD1-074 GEN2
Solar/Wind Harmer
1.164
316258AE1-075 C
Solar/Wind Harmer
0.152
3146206CASHIE
Solar/Wind Harmer
0.202
970601AG2-382 GEN
Solar/Wind Harmer
7.547
3145893MURPHYS
Solar/Wind Harmer
0.543
3145893MURPHYS
Solar/Wind Harmer
0.201
970085AG2-068 GEN
Solar/Wind Harmer
10.616
970581AG2-369 GEN
Solar/Wind Harmer
9.13
316463AE2-346 GEN
Solar/Wind Harmer
0.169
3145513AHOSKIE
Solar/Wind Harmer
0.415
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.395
3145683EARLEYS
Solar/Wind Harmer
0.197
3145683EARLEYS
Solar/Wind Harmer
0.197
3146043SEABORD
Solar/Wind Harmer
0.197
315652AC1-086 GEN
Solar/Wind Harmer
21.254
3137643SOCKMAN
Solar/Wind Harmer
0.769
316426AA2-053 GEN
Solar/Wind Harmer
0.644
3145796HORNRTN
Solar/Wind Harmer
0.608
3145796HORNRTN
Solar/Wind Harmer
0.076
3146033SCOT NK
Solar/Wind Harmer
0.756
316210AC1-098 GEN
Solar/Wind Harmer
1.718
316486AD2-202 GEN
Solar/Wind Harmer
0.189
316274AC1-208 GEN
Solar/Wind Harmer
0.951
970831AG2-522 GEN
Solar/Wind Harmer
7.801
3145746EVERETS
Solar/Wind Harmer
0.723
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
3152251N ANNA1
50/50
13.705
972197AH1-683 GEN
50/50
5.832
972219AH1-694 GEN
50/50
4.199
315052AA1-145 CT2
50/50
2.024
316447AC1-158 HLD
Solar/Wind Harmer
2.991
316044AC1-158 PL1
Solar/Wind Harmer
1.36
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.64
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143096IRON208
Adder
1.009
3150851SPRUNCC
Adder
1.106
3142543TWELFTH
Solar/Wind Harmer
0.023
315975AC1-164 GENB
Solar/Wind Harmer
0.075
3143526WINTERP
Solar/Wind Harmer
1.245
944631AF1-128 GEN
Adder
113.89
3143226MDLTHAN
Solar/Wind Harmer
0.238
316132AB2-190 GEN1
Solar/Wind Harmer
1.251
315671AE2-027_GEN
Solar/Wind Harmer
0.002
971069AG2-661 GEN
Solar/Wind Harmer
4.156
3142433PROV 92
Solar/Wind Harmer
0.931
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
971317AH1-138 GEN
Solar/Wind Harmer
1.737
3138126ROCKLANDING
Solar/Wind Harmer
0.107
961611AG1-000B GEN
Solar/Wind Harmer
12.165
3151171GRAVELC
Adder
2.459
315773AC2-141 GEN
Solar/Wind Harmer
8.412
3145336SMITFLD
Solar/Wind Harmer
0.919
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.603
944591AF1-124 GEN
Solar/Wind Harmer
51.527
316381AD1-082 GEN
Solar/Wind Harmer
0.231
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.041
3150981CHESPKA
Adder
2.847
316072AD1-144
Solar/Wind Harmer
0.081
939411AE1-173 GEN
Solar/Wind Harmer
96.242
3146456SLIGO L269
Solar/Wind Harmer
0.225
319010AE1-072 C
Solar/Wind Harmer
1.122
940641AE2-051 GEN
Solar/Wind Harmer
18.003
316093AE2-104_GEN
Solar/Wind Harmer
3.762
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.712
3146516WINFALL
Solar/Wind Harmer
0.22
941031AE2-094 GEN
Solar/Wind Harmer
39.877
962861AG1-135 GEN
Solar/Wind Harmer
6.891
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.096
3130156CHOWAN
Solar/Wind Harmer
0.214
3141726DUNNSVL
Solar/Wind Harmer
0.849
3150351NORNECKC2
Adder
2.089
315816AE2-034 GEN
Solar/Wind Harmer
0.891
3145663CRESWEL
Solar/Wind Harmer
0.584
971163AH1-040 GEN
Solar/Wind Harmer
16.704
315737AD1-076 GEN
Solar/Wind Harmer
2.621
3143336POWHATN
Solar/Wind Harmer
3.626
3146206CASHIE
Solar/Wind Harmer
0.202
971547AH1-271 GEN
Solar/Wind Harmer
4.313
970919AG2-571 GEN
Solar/Wind Harmer
7.165
316023GEN1_S
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
0.804
3145893MURPHYS
Solar/Wind Harmer
0.894
316337AD2-073 GEN
Solar/Wind Harmer
0.173
3146173TUNIS
Solar/Wind Harmer
0.199
970087AG2-069 GEN
Solar/Wind Harmer
15.924
3156021HOLLOMANSOL
Solar/Wind Harmer
0.896
3145683EARLEYS
Solar/Wind Harmer
0.197
315607AA1-063A GEN
Solar/Wind Harmer
0.394
960081AF2-299 GEN
Solar/Wind Harmer
1.882
3146263WOODLND
Solar/Wind Harmer
0.196
3145963POPLR C
Solar/Wind Harmer
0.194
3145823KELFORD
Solar/Wind Harmer
0.193
957481AF2-042 GEN
Solar/Wind Harmer
51.403
3145783HORNRTN
Solar/Wind Harmer
0.19
3145796HORNRTN
Solar/Wind Harmer
0.627
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Adder
1.715
315693AD1-088 GEN
Solar/Wind Harmer
9.073
3146293MARTNCO
Solar/Wind Harmer
0.172
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.678
971065AG2-659 GEN
Solar/Wind Harmer
7.714
3147666LOUISA
Solar/Wind Harmer
0.715
316327AA2-057 GEN
Solar/Wind Harmer
0.264
957861AF2-080 GEN
Solar/Wind Harmer
7.697
3145573BETHELC
Solar/Wind Harmer
0.176
3145573BETHELC
Solar/Wind Harmer
0.176
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
10.422
970681AG2-440 GEN
Solar/Wind Harmer
6.917
946301AF1-294 GEN
Solar/Wind Harmer
3.402
961791AG1-021 GEN
Solar/Wind Harmer
1.655
944491AF1-114 GEN
Solar/Wind Harmer
0
971845AH1-439 GEN
Solar/Wind Harmer
7.381
3147173SINAI
Solar/Wind Harmer
0.159
3147243WELCO
Solar/Wind Harmer
0.1
972205AH1-687 GEN
Adder
6.536
3138216PACIFIC
Solar/Wind Helper
0.038
3152261N ANNA2
50/50
13.712
3150401LDYSMT4
50/50
37.349
3150371LDYSMT1
50/50
36.089
315051AA1-145 CT1
50/50
2.012
3142416OLDCHRC
Solar/Wind Harmer
2.386
970293AG2-193 GEN
Solar/Wind Harmer
2.589
316075AC2-137 C
Solar/Wind Harmer
0.064
3143096IRON208
Adder
1.009
3143096IRON208
Adder
0.988
316473AC1-191 GEN
Solar/Wind Harmer
0.813
3150861SPRUNCD
Adder
1.106
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.265
316458AB2-190 GEN2
Solar/Wind Harmer
1.251
315778AD1-151 GEN
Solar/Wind Harmer
18.704
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3150921YORKTN3
Adder
5.839
3144216WINCHST
Adder
0.876
961611AG1-000B GEN
Solar/Wind Harmer
6.185
3151171GRAVELC
Adder
3.233
3145336SMITFLD
Solar/Wind Harmer
0.092
315813AE1-149 C
Solar/Wind Harmer
12.259
3144536CHRHLND
Solar/Wind Harmer
0.034
3141766HARMONY
Solar/Wind Harmer
3.049
3141843SHACKLE
Adder
1.168
316203AE2-005 GEN
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
21.177
944581AF1-123 GEN
Solar/Wind Harmer
51.344
944601AF1-125 GEN
Solar/Wind Harmer
50.553
3144873MCLAUGH
Solar/Wind Harmer
0.006
970657AG2-426 GEN
Solar/Wind Harmer
5.111
3141873WAN 176
Solar/Wind Harmer
4.032
316017AA1-139 ULT1
Solar/Wind Harmer
0.12
3146456SLIGO L269
Solar/Wind Harmer
0.225
971153AH1-033 GEN
Solar/Wind Harmer
2.603
316246AF1-032 C
Solar/Wind Harmer
0.1
316321Z2-027
Solar/Wind Harmer
0.039
3146516WINFALL
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.218
3145273HOLLAND
Solar/Wind Harmer
0.163
944011AF1-069 GEN
Solar/Wind Harmer
13.029
3146376EDENTON
Solar/Wind Harmer
0.213
971781AH1-399 GEN
Solar/Wind Harmer
0.276
3150351NORNECKC2
Adder
2.124
315735AD1-075 GEN1
Solar/Wind Harmer
0.581
3156081AA2-088 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.082
3146206CASHIE
Solar/Wind Harmer
0.202
970917AG2-570 GEN
Solar/Wind Harmer
17.912
3145893MURPHYS
Solar/Wind Harmer
0.337
3145893MURPHYS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.199
3146263WOODLND
Solar/Wind Harmer
0.196
3145963POPLR C
Solar/Wind Harmer
0.194
316181AB2-040 GEN
Solar/Wind Harmer
0.276
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
316011AB1-132 GEN
Solar/Wind Harmer
3.505
3145823KELFORD
Solar/Wind Harmer
0.193
316223AC1-118
Solar/Wind Harmer
0.136
3141906WESTMOR
Solar/Wind Harmer
0.077
3145796HORNRTN
Solar/Wind Harmer
0.761
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Solar/Wind Harmer
0.114
316212AC1-099_GEN
Solar/Wind Harmer
0.958
316478AD1-087 GEN
Solar/Wind Harmer
0.643
3145933PARMELE
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
315722AD1-056 GEN
Solar/Wind Harmer
6.236
3147666LOUISA
Solar/Wind Harmer
0.411
3146073TAR RVR
Solar/Wind Harmer
0.176
3146083TARBORO
Solar/Wind Harmer
0.176
3146233WITAKRS
Solar/Wind Harmer
0.882
3146233WITAKRS
Solar/Wind Harmer
0.12
3138543CONSLDL
Solar/Wind Harmer
0.116
964241AG1-285 GEN
Solar/Wind Harmer
11.623
970257AG2-171 GEN
Solar/Wind Harmer
5.552
971775AH1-396 GEN
Solar/Wind Harmer
0.278
959311AF2-222 GEN
Solar/Wind Harmer
15.408
961601AG1-000A GEN
Solar/Wind Harmer
12.265
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.172
3144293JTRSVLE
Adder
0.412
971623AH1-311 GEN
Solar/Wind Harmer
0.345
3147133PAMPLIN
Solar/Wind Harmer
0.54
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.102
972255AH1-712 GEN
Adder
83.218
3146776BUCKING
Solar/Wind Harmer
0.058
972003AH1-546 GEN
Solar/Wind Harmer
5.342
971683AH1-343 GEN
Solar/Wind Harmer
5.372
316222AC1-221 GEN
Solar/Wind Harmer
0.597
316283AC2-100 C
Solar/Wind Harmer
0.282
970221AG2-151 GEN
Solar/Wind Harmer
7.681
316123AC1-075 GEN
Solar/Wind Harmer
0.174
270494AE1-108_GEN
Solar/Wind Harmer
1.529
3150331BIRCHWDA
Adder
21.423
315821AE2-092 GEN
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.226
316494AC1-189 GEN
Solar/Wind Harmer
0.603
972135AH1-637 GEN
Solar/Wind Harmer
1.512
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.176
3145493TOT1
Solar/Wind Harmer
0.781
3146233WITAKRS
Solar/Wind Harmer
0.699
316131AB2-060 GEN
Solar/Wind Harmer
0.544
316192AB2-158 GEN
Solar/Wind Harmer
0.979
315785AD2-033 C
Solar/Wind Harmer
1.405
316034AC1-036 C
Solar/Wind Harmer
0.012
970685AG2-442 GEN
Solar/Wind Harmer
12.893
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.138
316359AB2-059 GEN
Solar/Wind Harmer
0.613
971563AH1-280 GEN
Solar/Wind Harmer
1.839
3144293JTRSVLE
Adder
0.412
3144293JTRSVLE
Adder
0.325
3142053HEARTS
Solar/Wind Harmer
0.304
970937AG2-583 GEN
Solar/Wind Harmer
10.568
3146926FARMVIL
Solar/Wind Harmer
0.102
970401AG2-262 GEN
Solar/Wind Harmer
0.973
972277AH1-723 GEN
Adder
96.974
3146776BUCKING
Solar/Wind Harmer
0.065
971377AH1-170 GEN
Solar/Wind Harmer
1.536
3147623JAMES R
Solar/Wind Harmer
0.334
316415AF1-147_GEN2
Solar/Wind Helper
0.789
3150391LDYSMT3
50/50
37.279
972195AH1-682 GEN
50/50
4.899
972189AH1-679 GEN
50/50
4.517
3142296MT RD221
50/50
0.843
3142366NRTHEST
50/50
0.846
3150691DARBY 3
50/50
18.598
316045AC1-158 PL2
Solar/Wind Harmer
4.352
316450AC1-158 RIC
Solar/Wind Harmer
0.363
315673AE1-157 GEN
Solar/Wind Harmer
17.979
316312AB1-027
Solar/Wind Harmer
0.438
3150701DARBY 4
Adder
17.486
3150681DARBY 2
Adder
17.466
3150671DARBY 1
Adder
17.445
966871AG1-558 GEN
Solar/Wind Harmer
0.278
315976AC1-164 GENA
Solar/Wind Harmer
2.522
316169AC1-164_GENC
Solar/Wind Harmer
2.18
3143526WINTERP
Solar/Wind Harmer
1.245
3142946ENON
Solar/Wind Harmer
0.024
971223AH1-071 GEN
Solar/Wind Harmer
2.538
944641AF1-129 GEN
Adder
112.654
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
3.982
3150991CHESPKB
Adder
2.389
3150991CHESPKB
Adder
2.331
316156AD2-030 GEN
Solar/Wind Harmer
0.166
3145506HICKORY
Solar/Wind Harmer
0.906
3145506HICKORY
Solar/Wind Harmer
0.544
3145506HICKORY
Solar/Wind Harmer
0.136
316339AD2-160 GEN
Solar/Wind Harmer
0.361
316388AE2-253 GEN
Solar/Wind Harmer
0.703
316349AD2-085 GEN
Solar/Wind Harmer
0.15
3137176SLIGO L2192
Solar/Wind Harmer
0.896
3146456SLIGO L269
Solar/Wind Harmer
3.984
3130086AYDLETT
Solar/Wind Harmer
0.899
315835AF2-110_GEN
Solar/Wind Harmer
1.535
3146386ELIZ CT
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
3144356SAPONY
Solar/Wind Harmer
1.819
316315AB2-025 C
Solar/Wind Harmer
0.174
315742AE1-103 GEN
Solar/Wind Harmer
3.207
3146376EDENTON
Solar/Wind Harmer
0.95
3146376EDENTON
Solar/Wind Harmer
0.95
972185AH1-677 GEN
Adder
11.847
3150341NORNECKC1
Adder
2.194
3150341NORNECKC1
Adder
2.177
315614AA2-178 GEN
Solar/Wind Harmer
1.188
972187AH1-678 GEN
Adder
5.944
970933AG2-581 GEN
Solar/Wind Harmer
16.438
316313AB2-026
Solar/Wind Harmer
0.127
316065AD1-022 GEN
Solar/Wind Harmer
9.345
316365GEN2_N
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
1.346
3145893MURPHYS
Solar/Wind Harmer
0.362
3146173TUNIS
Solar/Wind Harmer
0.199
3146173TUNIS
Solar/Wind Harmer
0.199
316140AB2-099
Solar/Wind Harmer
0.07
316336AC2-165 C
Solar/Wind Harmer
9.886
313506AB2-031 GEN
Solar/Wind Harmer
0.594
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.116
962571AG1-106 GEN
Solar/Wind Harmer
2.749
970099AG2-077 GEN
Solar/Wind Harmer
20.561
3145593CAROLNA
Solar/Wind Harmer
0.191
3145593CAROLNA
Solar/Wind Harmer
0.191
3145593CAROLNA
Solar/Wind Harmer
0.238
3145783HORNRTN
Solar/Wind Harmer
3.385
3145783HORNRTN
Solar/Wind Harmer
2.708
3145783HORNRTN
Solar/Wind Harmer
0.846
3145783HORNRTN
Solar/Wind Harmer
0.338
3145796HORNRTN
Solar/Wind Harmer
0.57
3145933PARMELE
Solar/Wind Harmer
0.371
3145933PARMELE
Solar/Wind Harmer
0.186
316005AA1-067
Solar/Wind Harmer
0.194
315724AD1-057 GEN
Solar/Wind Harmer
3.479
970301AG2-198 GEN
Solar/Wind Harmer
7.591
3145493TOT1
Solar/Wind Harmer
0.407
3145453TOT5
Solar/Wind Harmer
0.244
3145603CNETO
Solar/Wind Harmer
0.163
970323AG2-213 GEN
Solar/Wind Harmer
7.402
961601AG1-000A GEN
Solar/Wind Harmer
3.066
316049AB1-081 GEN
Solar/Wind Harmer
0.981
316263AC1-034 GEN
Solar/Wind Harmer
6.551
958211AF2-115 GEN
Solar/Wind Harmer
2.069
3144293JTRSVLE
Adder
0.412
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.137
962561AG1-105 GEN
Solar/Wind Harmer
8.026
964791AG1-342 GEN
Solar/Wind Harmer
3.184
3146843MT LREL
Solar/Wind Harmer
0.166
3146843MT LREL
Solar/Wind Harmer
0.166
972193AH1-681 GEN
Adder
3.718
316118AC1-105 GEN
Solar/Wind Harmer
0.416
3146776BUCKING
Solar/Wind Harmer
0.648
3146776BUCKING
Solar/Wind Harmer
0.052
942751AE2-291 GEN
Solar/Wind Harmer
6.709
316006AB2-029 C
Solar/Wind Helper
0.121
316411AF1-147_GEN1
Solar/Wind Helper
0.789
LAGNLTFEXP_LAGN->PJM
CLTF
7.792
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.331
TVALTFEXP_TVA->PJM
CLTF
3.951
CPLELTFEXP_CPLE->PJM
CLTF
11.096
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.435
MECLTFEXP_MEC->PJM
CLTF
3.506
SIGELTFEXP_SIGE->PJM
CLTF
0.107
NYPJM->LTFIMP_NY
CLTF
3.17
LGEELTFEXP_LGEE->PJM
CLTF
1.29
WECLTFEXP_WEC->PJM
CLTF
0.621

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.15 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3901.64
MW Contribution:
4.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150401LDYSMT4
50/50
28.489
3150371LDYSMT1
50/50
27.528
315051AA1-145 CT1
50/50
1.568
3142416OLDCHRC
Solar/Wind Harmer
1.859
970293AG2-193 GEN
Solar/Wind Harmer
2.002
316075AC2-137 C
Solar/Wind Harmer
0.05
3143096IRON208
Adder
0.775
3143096IRON208
Adder
0.759
316473AC1-191 GEN
Solar/Wind Harmer
0.624
3142946ENON
Solar/Wind Harmer
0.062
3150861SPRUNCD
Adder
0.843
970133AG2-095 GEN
Solar/Wind Harmer
1.734
316458AB2-190 GEN2
Solar/Wind Harmer
0.957
315778AD1-151 GEN
Solar/Wind Harmer
14.303
3150921YORKTN3
Adder
4.461
3144216WINCHST
Adder
0.669
961611AG1-000B GEN
Solar/Wind Harmer
4.724
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151171GRAVELC
Adder
2.468
3145336SMITFLD
Solar/Wind Harmer
0.07
972197AH1-683 GEN
50/50
4.449
972219AH1-694 GEN
50/50
3.203
315052AA1-145 CT2
50/50
1.577
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
0.498
3142416OLDCHRC
Solar/Wind Harmer
0.191
315975AC1-164 GENB
Solar/Wind Harmer
0.058
3143096IRON208
Adder
0.775
3142543TWELFTH
Solar/Wind Harmer
0.018
944631AF1-128 GEN
Adder
87.526
3150851SPRUNCC
Adder
0.843
3143526WINTERP
Solar/Wind Harmer
0.936
316132AB2-190 GEN1
Solar/Wind Harmer
0.957
971069AG2-661 GEN
Solar/Wind Harmer
3.178
315671AE2-027_GEN
Solar/Wind Harmer
0.001
971317AH1-138 GEN
Solar/Wind Harmer
1.326
3138126ROCKLANDING
Solar/Wind Harmer
0.081
961611AG1-000B GEN
Solar/Wind Harmer
9.291
3142433PROV 92
Solar/Wind Harmer
0.707
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3143226MDLTHAN
Solar/Wind Harmer
0.176
3151171GRAVELC
Adder
1.877
315773AC2-141 GEN
Solar/Wind Harmer
6.405
3145336SMITFLD
Solar/Wind Harmer
0.701
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.031
3150981CHESPKA
Adder
2.167
316381AD1-082 GEN
Solar/Wind Harmer
0.176
944591AF1-124 GEN
Solar/Wind Harmer
39.202
316072AD1-144
Solar/Wind Harmer
0.061
3141766HARMONY
Solar/Wind Harmer
0.034
971777AH1-397 GEN
Solar/Wind Harmer
0.454
3146456SLIGO L269
Solar/Wind Harmer
0.171
319010AE1-072 C
Solar/Wind Harmer
0.854
316093AE2-104_GEN
Solar/Wind Harmer
2.865
939411AE1-173 GEN
Solar/Wind Harmer
72.216
940641AE2-051 GEN
Solar/Wind Harmer
13.444
3146516WINFALL
Solar/Wind Harmer
0.543
971531AH1-263 GEN
50/50
38.564
3150411LDYSMT5
50/50
28.578
3150381LDYSMT2
50/50
27.35
972213AH1-691 GEN
50/50
4.627
972215AH1-692 GEN
50/50
4.627
971285AH1-108 GEN
Adder
1.379
316159AE1-175 C
Solar/Wind Harmer
0.154
316233AE1-074 FULL
Solar/Wind Harmer
0.144
971281AH1-106 GEN
Solar/Wind Harmer
2.497
971283AH1-107 GEN
Solar/Wind Harmer
2.497
315697AD1-025 GEN
Solar/Wind Harmer
0.192
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151201GRAVEL4
Adder
12.843
3151221GRAVEL6
Adder
12.828
3151191GRAVEL3
Adder
12.68
3151211GRAVEL5
Adder
12.68
971445AH1-216 GEN
Solar/Wind Harmer
12.355
3143873LANEXA
Solar/Wind Harmer
0.105
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143316POE
Solar/Wind Harmer
0.689
3151081ELIZAR1
Adder
15.915
3151091ELIZAR2
Adder
15.638
970657AG2-426 GEN
Solar/Wind Harmer
1.273
316316AC1-027 C
Solar/Wind Harmer
0.165
970189AG2-124 GEN
Solar/Wind Harmer
5.099
957871AF2-081 GEN
Solar/Wind Harmer
8.553
316311AC2-079 GEN
Solar/Wind Harmer
4.926
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3141873WAN 176
Solar/Wind Harmer
0.034
313526AB2-022
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.169
3146486SUNBURY
Solar/Wind Harmer
0.169
3146396TANGLEW
Solar/Wind Harmer
0.466
3145176PASQUOTANK
Solar/Wind Harmer
0.105
3141913WHIT STONE
Solar/Wind Harmer
0.167
3138133OCRAN
Solar/Wind Harmer
0.05
3141783LANCAST
Solar/Wind Harmer
0.099
3141783LANCAST
Solar/Wind Harmer
0.066
315814AE2-033 C
Solar/Wind Harmer
12.96
3130156CHOWAN
Solar/Wind Harmer
0.163
3130156CHOWAN
Solar/Wind Harmer
0.163
970533AG2-339 GEN
Solar/Wind Harmer
12.209
970673AG2-436 GEN
Solar/Wind Harmer
19.934
971967AH1-528 GEN
Solar/Wind Harmer
25.131
3130546PLYMOUTH
Solar/Wind Harmer
0.157
315732AD1-074 GEN1
Solar/Wind Harmer
0.891
315733AD1-074 GEN2
Solar/Wind Harmer
0.891
316258AE1-075 C
Solar/Wind Harmer
0.117
315813AE1-149 C
Solar/Wind Harmer
9.324
3144536CHRHLND
Solar/Wind Harmer
0.026
3151101ELIZAR3
Adder
16.118
3144873MCLAUGH
Solar/Wind Harmer
0.004
944581AF1-123 GEN
Solar/Wind Harmer
39.063
944601AF1-125 GEN
Solar/Wind Harmer
38.461
970657AG2-426 GEN
Solar/Wind Harmer
3.889
3141766HARMONY
Solar/Wind Harmer
2.298
3141843SHACKLE
Adder
0.879
316203AE2-005 GEN
Solar/Wind Harmer
0
316017AA1-139 ULT1
Solar/Wind Harmer
0.092
3146456SLIGO L269
Solar/Wind Harmer
0.171
971153AH1-033 GEN
Solar/Wind Harmer
1.982
316246AF1-032 C
Solar/Wind Harmer
0.076
3141873WAN 176
Solar/Wind Harmer
3.026
316321Z2-027
Solar/Wind Harmer
0.03
3146516WINFALL
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.166
3145273HOLLAND
Solar/Wind Harmer
0.124
3146376EDENTON
Solar/Wind Harmer
0.163
944011AF1-069 GEN
Solar/Wind Harmer
9.724
315735AD1-075 GEN1
Solar/Wind Harmer
0.445
3156081AA2-088 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
2.358
3146206CASHIE
Solar/Wind Harmer
0.155
3145893MURPHYS
Solar/Wind Harmer
0.258
3145893MURPHYS
Solar/Wind Harmer
0.154
3146173TUNIS
Solar/Wind Harmer
0.153
970917AG2-570 GEN
Solar/Wind Harmer
13.485
3146263WOODLND
Solar/Wind Harmer
0.15
3150351NORNECKC2
Adder
1.518
3145963POPLR C
Solar/Wind Harmer
0.149
971781AH1-399 GEN
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316181AB2-040 GEN
Solar/Wind Harmer
0.211
3145823KELFORD
Solar/Wind Harmer
0.148
316011AB1-132 GEN
Solar/Wind Harmer
2.686
3145796HORNRTN
Solar/Wind Harmer
0.584
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Solar/Wind Harmer
0.087
3145933PARMELE
Solar/Wind Harmer
0.143
316212AC1-099_GEN
Solar/Wind Harmer
0.738
316478AD1-087 GEN
Solar/Wind Harmer
0.492
972255AH1-712 GEN
Adder
72.54
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
315722AD1-056 GEN
Solar/Wind Harmer
4.811
3146073TAR RVR
Solar/Wind Harmer
0.136
3146083TARBORO
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
0.682
3146233WITAKRS
Solar/Wind Harmer
0.092
3138543CONSLDL
Solar/Wind Harmer
0.089
964241AG1-285 GEN
Solar/Wind Harmer
9.026
970257AG2-171 GEN
Solar/Wind Harmer
4.324
971775AH1-396 GEN
Solar/Wind Harmer
0.216
959311AF2-222 GEN
Solar/Wind Harmer
12.009
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
0.423
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.08
961601AG1-000A GEN
Solar/Wind Harmer
9.505
3145543BTLEBRO
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.133
971623AH1-311 GEN
Solar/Wind Harmer
0.267
3147666LOUISA
Solar/Wind Harmer
0.307
3146776BUCKING
Solar/Wind Harmer
0.047
316223AC1-118
Solar/Wind Harmer
0.091
3141906WESTMOR
Solar/Wind Harmer
0.051
972003AH1-546 GEN
Solar/Wind Harmer
4.363
970221AG2-151 GEN
Solar/Wind Harmer
6.373
3146516WINFALL
Solar/Wind Harmer
0.167
3138133OCRAN
Solar/Wind Harmer
0.1
3130156CHOWAN
Solar/Wind Harmer
0.163
941031AE2-094 GEN
Solar/Wind Harmer
29.76
315816AE2-034 GEN
Solar/Wind Harmer
0.681
3145663CRESWEL
Solar/Wind Harmer
0.447
971163AH1-040 GEN
Solar/Wind Harmer
12.772
962861AG1-135 GEN
Solar/Wind Harmer
5.01
315737AD1-076 GEN
Solar/Wind Harmer
2.007
3143336POWHATN
Solar/Wind Harmer
2.775
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
5.148
3146206CASHIE
Solar/Wind Harmer
0.155
971547AH1-271 GEN
Solar/Wind Harmer
3.304
3145893MURPHYS
Solar/Wind Harmer
0.616
3145893MURPHYS
Solar/Wind Harmer
0.685
316023GEN1_S
Solar/Wind Harmer
0.341
3141726DUNNSVL
Solar/Wind Harmer
0.611
3146173TUNIS
Solar/Wind Harmer
0.153
3156021HOLLOMANSOL
Solar/Wind Harmer
0.686
970919AG2-571 GEN
Solar/Wind Harmer
5.394
3145683EARLEYS
Solar/Wind Harmer
0.151
315607AA1-063A GEN
Solar/Wind Harmer
0.302
3146263WOODLND
Solar/Wind Harmer
0.15
970087AG2-069 GEN
Solar/Wind Harmer
12.006
960081AF2-299 GEN
Solar/Wind Harmer
1.44
3150351NORNECKC2
Adder
1.493
3145963POPLR C
Solar/Wind Harmer
0.149
3145823KELFORD
Solar/Wind Harmer
0.148
957481AF2-042 GEN
Solar/Wind Harmer
39.076
3145783HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.482
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Adder
1.317
315693AD1-088 GEN
Solar/Wind Harmer
6.932
3146293MARTNCO
Solar/Wind Harmer
0.133
972277AH1-723 GEN
Adder
84.53
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.523
316337AD2-073 GEN
Solar/Wind Harmer
0.12
971065AG2-659 GEN
Solar/Wind Harmer
5.948
316494AC1-189 GEN
Solar/Wind Harmer
0.466
970937AG2-583 GEN
Solar/Wind Harmer
8.399
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.136
3145493TOT1
Solar/Wind Harmer
0.605
3146233WITAKRS
Solar/Wind Harmer
0.541
316131AB2-060 GEN
Solar/Wind Harmer
0.422
315785AD2-033 C
Solar/Wind Harmer
1.093
316034AC1-036 C
Solar/Wind Harmer
0.009
970685AG2-442 GEN
Solar/Wind Harmer
10.073
971563AH1-280 GEN
Solar/Wind Harmer
1.438
3144293JTRSVLE
Adder
0.322
3144293JTRSVLE
Adder
0.254
3146926FARMVIL
Solar/Wind Harmer
0.08
3145543BTLEBRO
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.475
3142053HEARTS
Solar/Wind Harmer
0.235
3147666LOUISA
Solar/Wind Harmer
0.533
316192AB2-158 GEN
Solar/Wind Harmer
0.738
3146776BUCKING
Solar/Wind Harmer
0.052
970401AG2-262 GEN
Solar/Wind Harmer
0.758
971377AH1-170 GEN
Solar/Wind Harmer
1.275
3147623JAMES R
Solar/Wind Harmer
0.277
3146206CASHIE
Solar/Wind Harmer
0.155
970601AG2-382 GEN
Solar/Wind Harmer
5.781
3145893MURPHYS
Solar/Wind Harmer
0.416
3145893MURPHYS
Solar/Wind Harmer
0.154
316463AE2-346 GEN
Solar/Wind Harmer
0.13
3145513AHOSKIE
Solar/Wind Harmer
0.318
3145513AHOSKIE
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.303
3145683EARLEYS
Solar/Wind Harmer
0.151
3145683EARLEYS
Solar/Wind Harmer
0.151
3146043SEABORD
Solar/Wind Harmer
0.151
970085AG2-068 GEN
Solar/Wind Harmer
8.004
970581AG2-369 GEN
Solar/Wind Harmer
6.884
3141813NORNECK
Solar/Wind Harmer
0.15
315652AC1-086 GEN
Solar/Wind Harmer
16.288
316426AA2-053 GEN
Solar/Wind Harmer
0.494
3137643SOCKMAN
Solar/Wind Harmer
0.59
3145796HORNRTN
Solar/Wind Harmer
0.467
3145796HORNRTN
Solar/Wind Harmer
0.058
3146033SCOT NK
Solar/Wind Harmer
0.582
316210AC1-098 GEN
Solar/Wind Harmer
1.323
316274AC1-208 GEN
Solar/Wind Harmer
0.732
316486AD2-202 GEN
Solar/Wind Harmer
0.144
970831AG2-522 GEN
Solar/Wind Harmer
6.009
3145746EVERETS
Solar/Wind Harmer
0.558
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
316327AA2-057 GEN
Solar/Wind Harmer
0.204
957861AF2-080 GEN
Solar/Wind Harmer
5.951
3145573BETHELC
Solar/Wind Harmer
0.136
3145573BETHELC
Solar/Wind Harmer
0.136
3144303KENBRDG
Solar/Wind Harmer
0.108
970683AG2-441 GEN
Solar/Wind Harmer
8.135
970681AG2-440 GEN
Solar/Wind Harmer
5.399
946301AF1-294 GEN
Solar/Wind Harmer
2.66
961791AG1-021 GEN
Solar/Wind Harmer
1.294
971845AH1-439 GEN
Solar/Wind Harmer
5.912
972205AH1-687 GEN
Adder
5.352
3147173SINAI
Solar/Wind Harmer
0.124
3147243WELCO
Solar/Wind Harmer
0.078
226929AD2-058 GEN
Solar/Wind Helper
0.118
971683AH1-343 GEN
Solar/Wind Harmer
4.262
316222AC1-221 GEN
Solar/Wind Harmer
0.471
316283AC2-100 C
Solar/Wind Harmer
0.223
227287AC2-120 GEN
Solar/Wind Helper
0.389
226910AB2-157 C
Solar/Wind Helper
0.016
3150391LDYSMT3
50/50
28.436
972195AH1-682 GEN
50/50
3.737
972189AH1-679 GEN
50/50
3.521
3142296MT RD221
50/50
0.659
3142366NRTHEST
50/50
0.655
315673AE1-157 GEN
Solar/Wind Harmer
13.8
316312AB1-027
Solar/Wind Harmer
0.341
3150691DARBY 3
Adder
13.558
3150701DARBY 4
Adder
13.527
3150681DARBY 2
Adder
13.511
3150671DARBY 1
Adder
13.495
315976AC1-164 GENA
Solar/Wind Harmer
1.947
316169AC1-164_GENC
Solar/Wind Harmer
1.682
966871AG1-558 GEN
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
0.018
944641AF1-129 GEN
Adder
86.186
3143526WINTERP
Solar/Wind Harmer
0.936
316033AB2-134 GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.883
316294AC1-161 GEN
Solar/Wind Harmer
3.032
3150991CHESPKB
Adder
1.818
3150991CHESPKB
Adder
1.775
3145506HICKORY
Solar/Wind Harmer
0.69
3145506HICKORY
Solar/Wind Harmer
0.414
3145506HICKORY
Solar/Wind Harmer
0.104
316339AD2-160 GEN
Solar/Wind Harmer
0.275
316388AE2-253 GEN
Solar/Wind Harmer
0.535
316349AD2-085 GEN
Solar/Wind Harmer
0.114
3137176SLIGO L2192
Solar/Wind Harmer
0.682
3146456SLIGO L269
Solar/Wind Harmer
3.034
3130086AYDLETT
Solar/Wind Harmer
0.685
315835AF2-110_GEN
Solar/Wind Harmer
1.169
316156AD2-030 GEN
Solar/Wind Harmer
0.125
3146386ELIZ CT
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.167
3146516WINFALL
Solar/Wind Harmer
0.167
3146516WINFALL
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.166
3146626S HERTFORD
Solar/Wind Harmer
0.166
3144356SAPONY
Solar/Wind Harmer
1.375
316315AB2-025 C
Solar/Wind Harmer
0.132
315742AE1-103 GEN
Solar/Wind Harmer
2.447
3146376EDENTON
Solar/Wind Harmer
0.725
3146376EDENTON
Solar/Wind Harmer
0.725
315614AA2-178 GEN
Solar/Wind Harmer
0.908
972185AH1-677 GEN
Adder
8.87
972187AH1-678 GEN
Adder
4.457
316313AB2-026
Solar/Wind Harmer
0.097
316065AD1-022 GEN
Solar/Wind Harmer
7.157
970933AG2-581 GEN
Solar/Wind Harmer
12.367
3145893MURPHYS
Solar/Wind Harmer
1.031
3145893MURPHYS
Solar/Wind Harmer
0.277
316365GEN2_N
Solar/Wind Harmer
0.341
3146173TUNIS
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.153
316140AB2-099
Solar/Wind Harmer
0.054
316336AC2-165 C
Solar/Wind Harmer
7.636
3150341NORNECKC1
Adder
1.568
3150341NORNECKC1
Adder
1.555
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
3142666NORTHAMPTON
Solar/Wind Harmer
0.089
313506AB2-031 GEN
Solar/Wind Harmer
0.455
962571AG1-106 GEN
Solar/Wind Harmer
2.107
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.183
970099AG2-077 GEN
Solar/Wind Harmer
15.63
3145783HORNRTN
Solar/Wind Harmer
2.599
3145783HORNRTN
Solar/Wind Harmer
2.079
3145783HORNRTN
Solar/Wind Harmer
0.65
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
0.438
3145933PARMELE
Solar/Wind Harmer
0.286
3145933PARMELE
Solar/Wind Harmer
0.143
972193AH1-681 GEN
Adder
3.241
316005AA1-067
Solar/Wind Harmer
0.15
315724AD1-057 GEN
Solar/Wind Harmer
2.684
970301AG2-198 GEN
Solar/Wind Harmer
5.907
3145493TOT1
Solar/Wind Harmer
0.315
3145453TOT5
Solar/Wind Harmer
0.189
3145603CNETO
Solar/Wind Harmer
0.126
970323AG2-213 GEN
Solar/Wind Harmer
5.766
958211AF2-115 GEN
Solar/Wind Harmer
1.618
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
961601AG1-000A GEN
Solar/Wind Harmer
2.376
316049AB1-081 GEN
Solar/Wind Harmer
0.76
316263AC1-034 GEN
Solar/Wind Harmer
5.077
962561AG1-105 GEN
Solar/Wind Harmer
6.247
3146776BUCKING
Solar/Wind Harmer
0.52
3146776BUCKING
Solar/Wind Harmer
0.042
964791AG1-342 GEN
Solar/Wind Harmer
2.48
3146843MT LREL
Solar/Wind Harmer
0.129
3146843MT LREL
Solar/Wind Harmer
0.129
316118AC1-105 GEN
Solar/Wind Harmer
0.325
LAGNLTFEXP_LAGN->PJM
CLTF
7.542
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.159
TVALTFEXP_TVA->PJM
CLTF
3.819
CPLELTFEXP_CPLE->PJM
CLTF
8.867
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.841
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.651
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.334
MECLTFEXP_MEC->PJM
CLTF
4.136
SIGELTFEXP_SIGE->PJM
CLTF
0.128
NYPJM->LTFIMP_NY
CLTF
2.859
LGEELTFEXP_LGEE->PJM
CLTF
1.602
WECLTFEXP_WEC->PJM
CLTF
0.813

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.7 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3887.02
MW Contribution:
4.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
28.823
3150381LDYSMT2
50/50
27.584
972213AH1-691 GEN
50/50
4.666
972215AH1-692 GEN
50/50
4.666
971285AH1-108 GEN
Adder
1.384
316159AE1-175 C
Solar/Wind Harmer
0.155
316233AE1-074 FULL
Solar/Wind Harmer
0.144
971281AH1-106 GEN
Solar/Wind Harmer
2.505
971283AH1-107 GEN
Solar/Wind Harmer
2.505
315697AD1-025 GEN
Solar/Wind Harmer
0.192
3142433PROV 92
Adder
0.345
3142433PROV 92
Adder
0.345
3151201GRAVEL4
Adder
12.891
3151221GRAVEL6
Adder
12.876
3151191GRAVEL3
Adder
12.728
3151211GRAVEL5
Adder
12.728
971445AH1-216 GEN
Solar/Wind Harmer
12.4
3143873LANEXA
Solar/Wind Harmer
0.105
3138283WHITEMARSH
Solar/Wind Harmer
0.041
3143316POE
Solar/Wind Harmer
0.691
3151081ELIZAR1
Adder
15.97
3151091ELIZAR2
Adder
15.693
970657AG2-426 GEN
Solar/Wind Harmer
1.277
316316AC1-027 C
Solar/Wind Harmer
0.166
970189AG2-124 GEN
Solar/Wind Harmer
5.123
957871AF2-081 GEN
Solar/Wind Harmer
8.582
316311AC2-079 GEN
Solar/Wind Harmer
4.942
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3141873WAN 176
Solar/Wind Harmer
0.034
313526AB2-022
Solar/Wind Harmer
0.091
3150401LDYSMT4
50/50
28.733
3150371LDYSMT1
50/50
27.764
315051AA1-145 CT1
50/50
1.577
3142416OLDCHRC
Solar/Wind Harmer
1.868
970293AG2-193 GEN
Solar/Wind Harmer
2.012
316075AC2-137 C
Solar/Wind Harmer
0.05
3143096IRON208
Adder
0.778
3143096IRON208
Adder
0.763
316473AC1-191 GEN
Solar/Wind Harmer
0.628
3142946ENON
Solar/Wind Harmer
0.062
3150861SPRUNCD
Adder
0.846
970133AG2-095 GEN
Solar/Wind Harmer
1.741
316458AB2-190 GEN2
Solar/Wind Harmer
0.961
315778AD1-151 GEN
Solar/Wind Harmer
14.359
3150921YORKTN3
Adder
4.479
3144216WINCHST
Adder
0.672
961611AG1-000B GEN
Solar/Wind Harmer
4.742
3142433PROV 92
Adder
0.345
3142433PROV 92
Adder
0.345
3151171GRAVELC
Adder
2.477
3145336SMITFLD
Solar/Wind Harmer
0.07
315813AE1-149 C
Solar/Wind Harmer
9.357
3144536CHRHLND
Solar/Wind Harmer
0.026
3151101ELIZAR3
Adder
16.174
3144873MCLAUGH
Solar/Wind Harmer
0.004
944581AF1-123 GEN
Solar/Wind Harmer
39.197
944601AF1-125 GEN
Solar/Wind Harmer
38.593
3146486SUNBURY
Solar/Wind Harmer
0.17
3146486SUNBURY
Solar/Wind Harmer
0.17
3146396TANGLEW
Solar/Wind Harmer
0.467
3145176PASQUOTANK
Solar/Wind Harmer
0.105
970657AG2-426 GEN
Solar/Wind Harmer
3.903
3141766HARMONY
Solar/Wind Harmer
2.309
3141843SHACKLE
Adder
0.884
316203AE2-005 GEN
Solar/Wind Harmer
0
316017AA1-139 ULT1
Solar/Wind Harmer
0.092
3146456SLIGO L269
Solar/Wind Harmer
0.172
971153AH1-033 GEN
Solar/Wind Harmer
1.989
316246AF1-032 C
Solar/Wind Harmer
0.076
3141873WAN 176
Solar/Wind Harmer
3.041
316321Z2-027
Solar/Wind Harmer
0.03
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3145273HOLLAND
Solar/Wind Harmer
0.125
3146376EDENTON
Solar/Wind Harmer
0.164
944011AF1-069 GEN
Solar/Wind Harmer
9.745
315735AD1-075 GEN1
Solar/Wind Harmer
0.446
3156081AA2-088 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
2.358
3146206CASHIE
Solar/Wind Harmer
0.155
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.154
3146173TUNIS
Solar/Wind Harmer
0.153
970917AG2-570 GEN
Solar/Wind Harmer
13.514
3150351NORNECKC2
Adder
1.526
3146263WOODLND
Solar/Wind Harmer
0.15
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.15
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
316181AB2-040 GEN
Solar/Wind Harmer
0.212
3145823KELFORD
Solar/Wind Harmer
0.149
316011AB1-132 GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
0.585
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Solar/Wind Harmer
0.088
3145933PARMELE
Solar/Wind Harmer
0.143
972197AH1-683 GEN
50/50
4.487
972219AH1-694 GEN
50/50
3.23
315052AA1-145 CT2
50/50
1.587
966881AG1-559 GEN
Solar/Wind Harmer
0.232
3142416OLDCHRC
Solar/Wind Harmer
0.501
3142416OLDCHRC
Solar/Wind Harmer
0.192
315975AC1-164 GENB
Solar/Wind Harmer
0.058
3143096IRON208
Adder
0.778
3142543TWELFTH
Solar/Wind Harmer
0.018
944631AF1-128 GEN
Adder
87.909
3150851SPRUNCC
Adder
0.846
3143526WINTERP
Solar/Wind Harmer
0.939
316132AB2-190 GEN1
Solar/Wind Harmer
0.961
971069AG2-661 GEN
Solar/Wind Harmer
3.191
315671AE2-027_GEN
Solar/Wind Harmer
0.001
971317AH1-138 GEN
Solar/Wind Harmer
1.331
3138126ROCKLANDING
Solar/Wind Harmer
0.082
961611AG1-000B GEN
Solar/Wind Harmer
9.327
3142433PROV 92
Solar/Wind Harmer
0.71
3142433PROV 92
Adder
0.345
3142433PROV 92
Adder
0.345
3151171GRAVELC
Adder
1.884
3143226MDLTHAN
Solar/Wind Harmer
0.177
315773AC2-141 GEN
Solar/Wind Harmer
6.428
3145336SMITFLD
Solar/Wind Harmer
0.704
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.031
3150981CHESPKA
Adder
2.175
316381AD1-082 GEN
Solar/Wind Harmer
0.176
944591AF1-124 GEN
Solar/Wind Harmer
39.336
3141766HARMONY
Solar/Wind Harmer
0.035
316072AD1-144
Solar/Wind Harmer
0.062
971777AH1-397 GEN
Solar/Wind Harmer
0.456
3146456SLIGO L269
Solar/Wind Harmer
0.172
319010AE1-072 C
Solar/Wind Harmer
0.857
316093AE2-104_GEN
Solar/Wind Harmer
2.874
939411AE1-173 GEN
Solar/Wind Harmer
72.415
940641AE2-051 GEN
Solar/Wind Harmer
13.478
3146516WINFALL
Solar/Wind Harmer
0.545
3146516WINFALL
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.1
3130156CHOWAN
Solar/Wind Harmer
0.164
941031AE2-094 GEN
Solar/Wind Harmer
29.826
315816AE2-034 GEN
Solar/Wind Harmer
0.683
3145663CRESWEL
Solar/Wind Harmer
0.448
971163AH1-040 GEN
Solar/Wind Harmer
12.812
962861AG1-135 GEN
Solar/Wind Harmer
5.038
315737AD1-076 GEN
Solar/Wind Harmer
2.013
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
5.177
3143336POWHATN
Solar/Wind Harmer
2.774
3146206CASHIE
Solar/Wind Harmer
0.155
971547AH1-271 GEN
Solar/Wind Harmer
3.313
3145893MURPHYS
Solar/Wind Harmer
0.618
3145893MURPHYS
Solar/Wind Harmer
0.687
316023GEN1_S
Solar/Wind Harmer
0.342
3141726DUNNSVL
Solar/Wind Harmer
0.615
3146173TUNIS
Solar/Wind Harmer
0.153
3156021HOLLOMANSOL
Solar/Wind Harmer
0.688
970919AG2-571 GEN
Solar/Wind Harmer
5.406
3145683EARLEYS
Solar/Wind Harmer
0.152
315607AA1-063A GEN
Solar/Wind Harmer
0.303
3150351NORNECKC2
Adder
1.501
3146263WOODLND
Solar/Wind Harmer
0.15
970087AG2-069 GEN
Solar/Wind Harmer
12.031
960081AF2-299 GEN
Solar/Wind Harmer
1.443
3145963POPLR C
Solar/Wind Harmer
0.15
3145823KELFORD
Solar/Wind Harmer
0.149
957481AF2-042 GEN
Solar/Wind Harmer
39.136
3145783HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.483
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Adder
1.32
315693AD1-088 GEN
Solar/Wind Harmer
6.94
3146293MARTNCO
Solar/Wind Harmer
0.133
972277AH1-723 GEN
Adder
84.817
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
316337AD2-073 GEN
Solar/Wind Harmer
0.121
316129AC1-054 GEN
Solar/Wind Harmer
0.524
971065AG2-659 GEN
Solar/Wind Harmer
5.958
316494AC1-189 GEN
Solar/Wind Harmer
0.467
970937AG2-583 GEN
Solar/Wind Harmer
8.375
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.136
3145493TOT1
Solar/Wind Harmer
0.606
3146233WITAKRS
Solar/Wind Harmer
0.542
316131AB2-060 GEN
Solar/Wind Harmer
0.422
315785AD2-033 C
Solar/Wind Harmer
1.094
316034AC1-036 C
Solar/Wind Harmer
0.009
970685AG2-442 GEN
Solar/Wind Harmer
10.072
971563AH1-280 GEN
Solar/Wind Harmer
1.438
3144293JTRSVLE
Adder
0.322
3144293JTRSVLE
Adder
0.254
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.476
3142053HEARTS
Solar/Wind Harmer
0.236
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.519
3146776BUCKING
Solar/Wind Harmer
0.052
970401AG2-262 GEN
Solar/Wind Harmer
0.759
316192AB2-158 GEN
Solar/Wind Harmer
0.717
971377AH1-170 GEN
Solar/Wind Harmer
1.268
3147623JAMES R
Solar/Wind Harmer
0.276
3141913WHIT STONE
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.05
3141783LANCAST
Solar/Wind Harmer
0.099
3141783LANCAST
Solar/Wind Harmer
0.066
315814AE2-033 C
Solar/Wind Harmer
12.997
3130156CHOWAN
Solar/Wind Harmer
0.164
3130156CHOWAN
Solar/Wind Harmer
0.164
970533AG2-339 GEN
Solar/Wind Harmer
12.236
970673AG2-436 GEN
Solar/Wind Harmer
19.978
3130546PLYMOUTH
Solar/Wind Harmer
0.157
971967AH1-528 GEN
Solar/Wind Harmer
25.182
315732AD1-074 GEN1
Solar/Wind Harmer
0.894
315733AD1-074 GEN2
Solar/Wind Harmer
0.894
316258AE1-075 C
Solar/Wind Harmer
0.117
3146206CASHIE
Solar/Wind Harmer
0.155
970601AG2-382 GEN
Solar/Wind Harmer
5.798
3145893MURPHYS
Solar/Wind Harmer
0.417
3145893MURPHYS
Solar/Wind Harmer
0.154
316463AE2-346 GEN
Solar/Wind Harmer
0.13
3145513AHOSKIE
Solar/Wind Harmer
0.319
3145513AHOSKIE
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.303
3145683EARLEYS
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.152
3146043SEABORD
Solar/Wind Harmer
0.151
3141813NORNECK
Solar/Wind Harmer
0.15
970085AG2-068 GEN
Solar/Wind Harmer
8.021
970581AG2-369 GEN
Solar/Wind Harmer
6.898
315652AC1-086 GEN
Solar/Wind Harmer
16.33
316426AA2-053 GEN
Solar/Wind Harmer
0.495
3137643SOCKMAN
Solar/Wind Harmer
0.591
3145796HORNRTN
Solar/Wind Harmer
0.468
3145796HORNRTN
Solar/Wind Harmer
0.059
3146033SCOT NK
Solar/Wind Harmer
0.583
316210AC1-098 GEN
Solar/Wind Harmer
1.326
316274AC1-208 GEN
Solar/Wind Harmer
0.734
316486AD2-202 GEN
Solar/Wind Harmer
0.145
970831AG2-522 GEN
Solar/Wind Harmer
6.021
3145746EVERETS
Solar/Wind Harmer
0.56
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
316327AA2-057 GEN
Solar/Wind Harmer
0.205
957861AF2-080 GEN
Solar/Wind Harmer
5.966
3145573BETHELC
Solar/Wind Harmer
0.136
3145573BETHELC
Solar/Wind Harmer
0.136
3144303KENBRDG
Solar/Wind Harmer
0.108
970683AG2-441 GEN
Solar/Wind Harmer
8.135
970681AG2-440 GEN
Solar/Wind Harmer
5.399
946301AF1-294 GEN
Solar/Wind Harmer
2.66
961791AG1-021 GEN
Solar/Wind Harmer
1.294
971845AH1-439 GEN
Solar/Wind Harmer
5.895
3147173SINAI
Solar/Wind Harmer
0.125
3147243WELCO
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.326
226929AD2-058 GEN
Solar/Wind Helper
0.118
316212AC1-099_GEN
Solar/Wind Harmer
0.74
972255AH1-712 GEN
Adder
72.785
316478AD1-087 GEN
Solar/Wind Harmer
0.492
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
315722AD1-056 GEN
Solar/Wind Harmer
4.822
3146073TAR RVR
Solar/Wind Harmer
0.136
3146083TARBORO
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
0.684
3146233WITAKRS
Solar/Wind Harmer
0.093
3138543CONSLDL
Solar/Wind Harmer
0.09
964241AG1-285 GEN
Solar/Wind Harmer
9.033
970257AG2-171 GEN
Solar/Wind Harmer
4.326
971775AH1-396 GEN
Solar/Wind Harmer
0.216
959311AF2-222 GEN
Solar/Wind Harmer
12.012
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
0.422
942461AE2-259 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
9.528
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.268
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.299
3146776BUCKING
Solar/Wind Harmer
0.047
316223AC1-118
Solar/Wind Harmer
0.092
3141906WESTMOR
Solar/Wind Harmer
0.052
972003AH1-546 GEN
Solar/Wind Harmer
4.342
970221AG2-151 GEN
Solar/Wind Harmer
6.341
971683AH1-343 GEN
Solar/Wind Harmer
4.267
316222AC1-221 GEN
Solar/Wind Harmer
0.472
316283AC2-100 C
Solar/Wind Harmer
0.223
227287AC2-120 GEN
Solar/Wind Helper
0.388
226910AB2-157 C
Solar/Wind Helper
0.015
3150391LDYSMT3
50/50
28.679
972195AH1-682 GEN
50/50
3.769
972189AH1-679 GEN
50/50
3.542
3142296MT RD221
50/50
0.662
3142366NRTHEST
50/50
0.658
3150691DARBY 3
50/50
14.454
315673AE1-157 GEN
Solar/Wind Harmer
13.908
316312AB1-027
Solar/Wind Harmer
0.343
3150701DARBY 4
Adder
13.59
3150681DARBY 2
Adder
13.574
3150671DARBY 1
Adder
13.558
315976AC1-164 GENA
Solar/Wind Harmer
1.956
316169AC1-164_GENC
Solar/Wind Harmer
1.69
966871AG1-558 GEN
Solar/Wind Harmer
0.215
3142946ENON
Solar/Wind Harmer
0.018
944641AF1-129 GEN
Adder
86.526
3143526WINTERP
Solar/Wind Harmer
0.939
316033AB2-134 GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.887
316294AC1-161 GEN
Solar/Wind Harmer
3.042
3150991CHESPKB
Adder
1.824
3150991CHESPKB
Adder
1.781
3145506HICKORY
Solar/Wind Harmer
0.692
3145506HICKORY
Solar/Wind Harmer
0.415
3145506HICKORY
Solar/Wind Harmer
0.104
316339AD2-160 GEN
Solar/Wind Harmer
0.276
316388AE2-253 GEN
Solar/Wind Harmer
0.537
316349AD2-085 GEN
Solar/Wind Harmer
0.115
3137176SLIGO L2192
Solar/Wind Harmer
0.685
3146456SLIGO L269
Solar/Wind Harmer
3.044
3130086AYDLETT
Solar/Wind Harmer
0.687
316156AD2-030 GEN
Solar/Wind Harmer
0.125
315835AF2-110_GEN
Solar/Wind Harmer
1.173
3146386ELIZ CT
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.167
3144356SAPONY
Solar/Wind Harmer
1.379
316315AB2-025 C
Solar/Wind Harmer
0.132
315742AE1-103 GEN
Solar/Wind Harmer
2.455
3146376EDENTON
Solar/Wind Harmer
0.728
3146376EDENTON
Solar/Wind Harmer
0.728
315614AA2-178 GEN
Solar/Wind Harmer
0.911
972185AH1-677 GEN
Adder
8.889
972187AH1-678 GEN
Adder
4.466
316313AB2-026
Solar/Wind Harmer
0.097
316065AD1-022 GEN
Solar/Wind Harmer
7.178
970933AG2-581 GEN
Solar/Wind Harmer
12.39
3145893MURPHYS
Solar/Wind Harmer
1.034
3145893MURPHYS
Solar/Wind Harmer
0.278
316365GEN2_N
Solar/Wind Harmer
0.342
3146173TUNIS
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.153
316140AB2-099
Solar/Wind Harmer
0.054
3150341NORNECKC1
Adder
1.577
3150341NORNECKC1
Adder
1.564
316336AC2-165 C
Solar/Wind Harmer
7.629
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.089
313506AB2-031 GEN
Solar/Wind Harmer
0.456
962571AG1-106 GEN
Solar/Wind Harmer
2.112
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.183
970099AG2-077 GEN
Solar/Wind Harmer
15.655
3145783HORNRTN
Solar/Wind Harmer
2.606
3145783HORNRTN
Solar/Wind Harmer
2.084
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.439
3145933PARMELE
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.143
972193AH1-681 GEN
Adder
3.252
316005AA1-067
Solar/Wind Harmer
0.15
315724AD1-057 GEN
Solar/Wind Harmer
2.69
970301AG2-198 GEN
Solar/Wind Harmer
5.905
3145493TOT1
Solar/Wind Harmer
0.316
3145453TOT5
Solar/Wind Harmer
0.19
3145603CNETO
Solar/Wind Harmer
0.126
970323AG2-213 GEN
Solar/Wind Harmer
5.768
958211AF2-115 GEN
Solar/Wind Harmer
1.617
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
961601AG1-000A GEN
Solar/Wind Harmer
2.382
316049AB1-081 GEN
Solar/Wind Harmer
0.762
316263AC1-034 GEN
Solar/Wind Harmer
5.089
962561AG1-105 GEN
Solar/Wind Harmer
6.254
3146776BUCKING
Solar/Wind Harmer
0.518
3146776BUCKING
Solar/Wind Harmer
0.042
964791AG1-342 GEN
Solar/Wind Harmer
2.483
3146843MT LREL
Solar/Wind Harmer
0.129
3146843MT LREL
Solar/Wind Harmer
0.129
316118AC1-105 GEN
Solar/Wind Harmer
0.325
LAGNLTFEXP_LAGN->PJM
CLTF
7.548
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.189
TVALTFEXP_TVA->PJM
CLTF
3.822
CPLELTFEXP_CPLE->PJM
CLTF
8.882
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.864
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.649
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.343
MECLTFEXP_MEC->PJM
CLTF
4.137
SIGELTFEXP_SIGE->PJM
CLTF
0.128
NYPJM->LTFIMP_NY
CLTF
2.857
LGEELTFEXP_LGEE->PJM
CLTF
1.602
WECLTFEXP_WEC->PJM
CLTF
0.813

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:159.65 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5141.33
MW Contribution:
6.53
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
49.095
315243AE2-183_GT3
50/50
5.538
3151051BRUNSWICKS1
50/50
9.073
3151021BRUNSWICKG1
50/50
4.37
971451AH1-221 GEN
50/50
13.272
3150981CHESPKA
50/50
4.067
3150851SPRUNCC
50/50
1.46
3152331SURRY 2
50/50
12.176
3143226MDLTHAN
Solar/Wind Harmer
0.368
940641AE2-051 GEN
Solar/Wind Harmer
28.032
941031AE2-094 GEN
Solar/Wind Harmer
63.736
939411AE1-173 GEN
Solar/Wind Harmer
144.938
3143526WINTERP
Solar/Wind Harmer
1.741
970919AG2-571 GEN
Solar/Wind Harmer
11.354
970087AG2-069 GEN
Solar/Wind Harmer
25.203
315773AC2-141 GEN
Solar/Wind Harmer
11.346
944591AF1-124 GEN
Solar/Wind Harmer
69.917
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.055
3146456SLIGO L269
Solar/Wind Harmer
0.305
319010AE1-072 C
Solar/Wind Harmer
1.522
316093AE2-104_GEN
Solar/Wind Harmer
5.094
316381AD1-082 GEN
Solar/Wind Harmer
0.307
316072AD1-144
Solar/Wind Harmer
0.107
3146516WINFALL
Solar/Wind Harmer
0.971
316303AF2-085
50/50
6.546
315244AE2-183_ST
50/50
9.618
963041AG1-153 GEN
50/50
8.848
315779AE2-040
50/50
4.41
3151081ELIZAR1
50/50
29.895
3151091ELIZAR2
50/50
29.376
941591AE2-156 GEN
50/50
27.307
971285AH1-108 GEN
50/50
2.389
972263AH1-716 GEN
50/50
170.5
970533AG2-339 GEN
Solar/Wind Harmer
26.147
970673AG2-436 GEN
Solar/Wind Harmer
42.579
316233AE1-074 FULL
Solar/Wind Harmer
0.268
971281AH1-106 GEN
Solar/Wind Harmer
4.646
971283AH1-107 GEN
Solar/Wind Harmer
4.646
971967AH1-528 GEN
Solar/Wind Harmer
53.128
970085AG2-068 GEN
Solar/Wind Harmer
16.802
970581AG2-369 GEN
Solar/Wind Harmer
14.45
315814AE2-033 C
Solar/Wind Harmer
24.896
3143316POE
Solar/Wind Harmer
1.231
316316AC1-027 C
Solar/Wind Harmer
0.293
957871AF2-081 GEN
Solar/Wind Harmer
15.23
3146406KITTY HAWK
Solar/Wind Harmer
0.038
313526AB2-022
Solar/Wind Harmer
0.162
316311AC2-079 GEN
Solar/Wind Harmer
8.694
970657AG2-426 GEN
Solar/Wind Harmer
2.222
3146486SUNBURY
Solar/Wind Harmer
0.302
3146486SUNBURY
Solar/Wind Harmer
0.302
3146396TANGLEW
Solar/Wind Harmer
0.832
3145176PASQUOTANK
Solar/Wind Harmer
0.187
971445AH1-216 GEN
Solar/Wind Harmer
21.022
316258AE1-075 C
Solar/Wind Harmer
0.22
3130156CHOWAN
Solar/Wind Harmer
0.294
3130156CHOWAN
Solar/Wind Harmer
0.294
3151201GRAVEL4
Adder
21.4
3151221GRAVEL6
Adder
21.375
3151191GRAVEL3
Adder
21.129
3151211GRAVEL5
Adder
21.129
315697AD1-025 GEN
Solar/Wind Harmer
0.311
316486AD2-202 GEN
Solar/Wind Harmer
0.291
3130546PLYMOUTH
Solar/Wind Harmer
0.285
315732AD1-074 GEN1
Solar/Wind Harmer
1.623
315733AD1-074 GEN2
Solar/Wind Harmer
1.623
3145893MURPHYS
Solar/Wind Harmer
0.765
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.566
3146043SEABORD
Solar/Wind Harmer
0.28
316463AE2-346 GEN
Solar/Wind Harmer
0.239
3145513AHOSKIE
Solar/Wind Harmer
0.586
3145513AHOSKIE
Solar/Wind Harmer
0.28
3145683EARLEYS
Solar/Wind Harmer
0.558
3145683EARLEYS
Solar/Wind Harmer
0.279
3145683EARLEYS
Solar/Wind Harmer
0.279
315652AC1-086 GEN
Solar/Wind Harmer
30.648
3137643SOCKMAN
Solar/Wind Harmer
1.11
316426AA2-053 GEN
Solar/Wind Harmer
0.925
3145796HORNRTN
Solar/Wind Harmer
0.879
3145796HORNRTN
Solar/Wind Harmer
0.11
316159AE1-175 C
Solar/Wind Harmer
0.233
3146033SCOT NK
Solar/Wind Harmer
1.083
970831AG2-522 GEN
Solar/Wind Harmer
11.444
316210AC1-098 GEN
Solar/Wind Harmer
2.473
316274AC1-208 GEN
Solar/Wind Harmer
1.374
3138283WHITEMARSH
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
1.038
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316327AA2-057 GEN
Solar/Wind Harmer
0.384
957861AF2-080 GEN
Solar/Wind Harmer
11.117
3145573BETHELC
Solar/Wind Harmer
0.255
3145573BETHELC
Solar/Wind Harmer
0.255
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
3144303KENBRDG
Solar/Wind Harmer
0.201
970683AG2-441 GEN
Solar/Wind Harmer
15.004
970681AG2-440 GEN
Solar/Wind Harmer
9.958
946301AF1-294 GEN
Solar/Wind Harmer
4.863
961791AG1-021 GEN
Solar/Wind Harmer
2.366
3143873LANEXA
Solar/Wind Harmer
0.147
970189AG2-124 GEN
Solar/Wind Harmer
7.205
3141873WAN 176
Solar/Wind Harmer
0.048
3147173SINAI
Solar/Wind Harmer
0.24
3147243WELCO
Solar/Wind Harmer
0.15
3141913WHIT STONE
Solar/Wind Harmer
0.233
3138133OCRAN
Solar/Wind Harmer
0.069
3141783LANCAST
Solar/Wind Harmer
0.136
3141783LANCAST
Solar/Wind Harmer
0.091
971845AH1-439 GEN
Solar/Wind Harmer
9.695
3141813NORNECK
Solar/Wind Harmer
0.19
972205AH1-687 GEN
Adder
7.904
270197AD1-017 GEN1
Solar/Wind Harmer
0.884
316164AC1-076 GEN
Solar/Wind Helper
1.502
315651AD1-115 GEN
Solar/Wind Helper
0.943
3138216PACIFIC
Solar/Wind Helper
0.039
226929AD2-058 GEN
Solar/Wind Helper
0.091
3151031BRUNSWICKG2
50/50
4.37
3151101ELIZAR3
50/50
30.278
3150861SPRUNCD
50/50
1.46
3151161SURRY 1
50/50
11.976
944011AF1-069 GEN
Solar/Wind Harmer
20.825
970917AG2-570 GEN
Solar/Wind Harmer
28.384
944581AF1-123 GEN
Solar/Wind Harmer
69.669
944601AF1-125 GEN
Solar/Wind Harmer
68.596
3144873MCLAUGH
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.163
3146456SLIGO L269
Solar/Wind Harmer
0.305
971153AH1-033 GEN
Solar/Wind Harmer
3.53
3144536CHRHLND
Solar/Wind Harmer
0.046
316246AF1-032 C
Solar/Wind Harmer
0.135
970657AG2-426 GEN
Solar/Wind Harmer
6.791
315813AE1-149 C
Solar/Wind Harmer
16.138
316321Z2-027
Solar/Wind Harmer
0.054
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
0.12
3146626S HERTFORD
Solar/Wind Harmer
0.298
3145273HOLLAND
Solar/Wind Harmer
0.223
3143336POWHATN
Solar/Wind Harmer
4.458
3146376EDENTON
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
4.113
961611AG1-000B GEN
Solar/Wind Harmer
7.79
315778AD1-151 GEN
Solar/Wind Harmer
23.043
316458AB2-190 GEN2
Solar/Wind Harmer
1.527
3156081AA2-088 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.99
315735AD1-075 GEN1
Solar/Wind Harmer
0.81
3144216WINCHST
Adder
1.071
970133AG2-095 GEN
Solar/Wind Harmer
2.72
3145893MURPHYS
Solar/Wind Harmer
0.474
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
3150921YORKTN3
Adder
7.096
3146173TUNIS
Solar/Wind Harmer
0.281
316181AB2-040 GEN
Solar/Wind Harmer
0.399
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
316011AB1-132 GEN
Solar/Wind Harmer
5.054
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Solar/Wind Harmer
0.166
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
1.099
3145796HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.146
3143096IRON208
Adder
1.123
316212AC1-099_GEN
Solar/Wind Harmer
1.379
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
1.196
957481AF2-042 GEN
Solar/Wind Harmer
79.621
3143336POWHATN
Solar/Wind Harmer
5.245
3130156CHOWAN
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
3.127
961611AG1-000B GEN
Solar/Wind Harmer
15.32
315671AE2-027_GEN
Solar/Wind Harmer
0.002
316023GEN1_S
Solar/Wind Harmer
0.648
315816AE2-034 GEN
Solar/Wind Harmer
1.234
3145663CRESWEL
Solar/Wind Harmer
0.809
971163AH1-040 GEN
Solar/Wind Harmer
23.139
315693AD1-088 GEN
Solar/Wind Harmer
13.86
971069AG2-661 GEN
Solar/Wind Harmer
5.121
316132AB2-190 GEN1
Solar/Wind Harmer
1.527
315737AD1-076 GEN
Solar/Wind Harmer
3.655
960081AF2-299 GEN
Solar/Wind Harmer
2.727
3138126ROCKLANDING
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
1.132
3145893MURPHYS
Solar/Wind Harmer
1.259
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.038
3146173TUNIS
Solar/Wind Harmer
0.281
3142543TWELFTH
Solar/Wind Harmer
0.027
3156021HOLLOMANSOL
Solar/Wind Harmer
1.261
315607AA1-063A GEN
Solar/Wind Harmer
0.562
3145683EARLEYS
Solar/Wind Harmer
0.279
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Adder
2.497
971317AH1-138 GEN
Solar/Wind Harmer
2.055
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
0.906
3145796HORNRTN
Solar/Wind Harmer
0.275
3145783HORNRTN
Solar/Wind Harmer
0.274
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.146
944631AF1-128 GEN
Adder
128.737
316129AC1-054 GEN
Solar/Wind Harmer
0.998
971065AG2-659 GEN
Solar/Wind Harmer
11.366
3146293MARTNCO
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316494AC1-189 GEN
Solar/Wind Harmer
0.871
316131AB2-060 GEN
Solar/Wind Harmer
0.8
3146233WITAKRS
Solar/Wind Harmer
1.018
961671AG1-007 GEN
Solar/Wind Harmer
0.039
3146083TARBORO
Solar/Wind Harmer
0.255
3145493TOT1
Solar/Wind Harmer
1.135
315975AC1-164 GENB
Solar/Wind Harmer
0.079
3142433PROV 92
Solar/Wind Harmer
1.011
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
315785AD2-033 C
Solar/Wind Harmer
2.043
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.201
316359AB2-059 GEN
Solar/Wind Harmer
0.895
3142053HEARTS
Solar/Wind Harmer
0.444
316034AC1-036 C
Solar/Wind Harmer
0.017
970685AG2-442 GEN
Solar/Wind Harmer
18.502
970401AG2-262 GEN
Solar/Wind Harmer
1.45
971563AH1-280 GEN
Solar/Wind Harmer
2.629
3144293JTRSVLE
Adder
0.588
3144293JTRSVLE
Adder
0.464
971777AH1-397 GEN
Solar/Wind Harmer
0.642
3141766HARMONY
Solar/Wind Harmer
0.048
3142416OLDCHRC
Solar/Wind Harmer
0.622
3142416OLDCHRC
Solar/Wind Harmer
0.238
3146926FARMVIL
Solar/Wind Harmer
0.14
3138133OCRAN
Solar/Wind Harmer
0.139
970937AG2-583 GEN
Solar/Wind Harmer
13.903
3146776BUCKING
Solar/Wind Harmer
0.085
962861AG1-135 GEN
Solar/Wind Harmer
6.638
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.787
3141726DUNNSVL
Solar/Wind Harmer
0.785
3150351NORNECKC2
Adder
1.898
971377AH1-170 GEN
Solar/Wind Harmer
1.82
3147623JAMES R
Solar/Wind Harmer
0.395
316337AD2-073 GEN
Solar/Wind Harmer
0.144
970223AG2-152 GEN
Solar/Wind Harmer
10.638
3147123OTTER R
Solar/Wind Harmer
0.084
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.167
972277AH1-723 GEN
Adder
76.754
270030AE2-140 GEN
Solar/Wind Harmer
12.682
316447AC1-158 HLD
Solar/Wind Helper
4.857
316044AC1-158 PL1
Solar/Wind Helper
2.207
3147666LOUISA
Solar/Wind Helper
1.246
316192AB2-158 GEN
Solar/Wind Helper
2.054
316415AF1-147_GEN2
Solar/Wind Helper
0.811
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.089
315722AD1-056 GEN
Solar/Wind Harmer
9.066
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3146233WITAKRS
Solar/Wind Harmer
1.285
3146233WITAKRS
Solar/Wind Harmer
0.174
3138543CONSLDL
Solar/Wind Harmer
0.169
964241AG1-285 GEN
Solar/Wind Harmer
17.033
3146073TAR RVR
Solar/Wind Harmer
0.255
3146083TARBORO
Solar/Wind Harmer
0.255
970293AG2-193 GEN
Solar/Wind Harmer
2.714
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
961601AG1-000A GEN
Solar/Wind Harmer
17.927
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.252
971623AH1-311 GEN
Solar/Wind Harmer
0.504
316075AC2-137 C
Solar/Wind Harmer
0.067
970257AG2-171 GEN
Solar/Wind Harmer
8.052
971775AH1-396 GEN
Solar/Wind Harmer
0.403
959311AF2-222 GEN
Solar/Wind Harmer
22.299
3144293JTRSVLE
Adder
0.588
3147133PAMPLIN
Solar/Wind Harmer
0.768
3141843SHACKLE
Adder
1.242
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
3.22
3141873WAN 176
Solar/Wind Harmer
4.288
942461AE2-259 GEN
Solar/Wind Harmer
0
3142416OLDCHRC
Solar/Wind Harmer
2.32
3146926FARMVIL
Solar/Wind Harmer
0.14
316222AC1-221 GEN
Solar/Wind Harmer
0.904
316283AC2-100 C
Solar/Wind Harmer
0.427
971683AH1-343 GEN
Solar/Wind Harmer
7.996
316473AC1-191 GEN
Solar/Wind Harmer
0.733
3146776BUCKING
Solar/Wind Harmer
0.076
316123AC1-075 GEN
Solar/Wind Harmer
0.255
3150351NORNECKC2
Adder
1.93
972003AH1-546 GEN
Solar/Wind Harmer
6.525
970221AG2-151 GEN
Solar/Wind Harmer
9.098
270494AE1-108_GEN
Solar/Wind Harmer
1.833
971781AH1-399 GEN
Solar/Wind Harmer
0.197
316223AC1-118
Solar/Wind Harmer
0.101
3141906WESTMOR
Solar/Wind Harmer
0.057
315821AE2-092 GEN
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.026
972255AH1-712 GEN
Adder
65.866
943811AF1-049 GEN
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
3.325
3147666LOUISA
Solar/Wind Helper
0.716
3141196NOKESVL
Solar/Wind Helper
1.04
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.313
226910AB2-157 C
Solar/Wind Helper
0.013
315242AE2-183_GT2
50/50
5.538
315241AE2-183_GT1
50/50
5.524
972185AH1-677 GEN
50/50
20.02
3151041BRUNSWICKG3
50/50
4.37
972187AH1-678 GEN
50/50
10.028
3150991CHESPKB
50/50
3.412
3150991CHESPKB
50/50
3.33
971223AH1-071 GEN
Solar/Wind Harmer
3.928
3143526WINTERP
Solar/Wind Harmer
1.741
970933AG2-581 GEN
Solar/Wind Harmer
25.921
3144356SAPONY
Solar/Wind Harmer
2.643
316315AB2-025 C
Solar/Wind Harmer
0.253
316294AC1-161 GEN
Solar/Wind Harmer
5.37
3145506HICKORY
Solar/Wind Harmer
1.227
3145506HICKORY
Solar/Wind Harmer
0.736
3145506HICKORY
Solar/Wind Harmer
0.184
316339AD2-160 GEN
Solar/Wind Harmer
0.49
316388AE2-253 GEN
Solar/Wind Harmer
0.953
3137176SLIGO L2192
Solar/Wind Harmer
1.215
3146456SLIGO L269
Solar/Wind Harmer
5.404
3130086AYDLETT
Solar/Wind Harmer
1.22
3146386ELIZ CT
Solar/Wind Harmer
0.303
315835AF2-110_GEN
Solar/Wind Harmer
2.079
316349AD2-085 GEN
Solar/Wind Harmer
0.202
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
970099AG2-077 GEN
Solar/Wind Harmer
31.848
3146626S HERTFORD
Solar/Wind Harmer
0.298
3146626S HERTFORD
Solar/Wind Harmer
0.298
315742AE1-103 GEN
Solar/Wind Harmer
4.41
316313AB2-026
Solar/Wind Harmer
0.184
3146376EDENTON
Solar/Wind Harmer
1.307
3146376EDENTON
Solar/Wind Harmer
1.307
316365GEN2_N
Solar/Wind Harmer
0.648
315614AA2-178 GEN
Solar/Wind Harmer
1.645
316033AB2-134 GEN
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
137.077
316065AD1-022 GEN
Solar/Wind Harmer
13.063
3145893MURPHYS
Solar/Wind Harmer
1.895
3145893MURPHYS
Solar/Wind Harmer
0.509
3146173TUNIS
Solar/Wind Harmer
0.281
3146173TUNIS
Solar/Wind Harmer
0.281
313506AB2-031 GEN
Solar/Wind Harmer
0.859
316140AB2-099
Solar/Wind Harmer
0.1
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.167
962571AG1-106 GEN
Solar/Wind Harmer
3.964
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.344
316336AC2-165 C
Solar/Wind Harmer
13.978
3145796HORNRTN
Solar/Wind Harmer
0.824
3145783HORNRTN
Solar/Wind Harmer
4.881
3145783HORNRTN
Solar/Wind Harmer
3.905
3145783HORNRTN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
0.488
3145933PARMELE
Solar/Wind Harmer
0.53
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.026
315724AD1-057 GEN
Solar/Wind Harmer
5.057
316005AA1-067
Solar/Wind Harmer
0.278
3142366NRTHEST
Adder
0.843
970301AG2-198 GEN
Solar/Wind Harmer
10.98
3150691DARBY 3
Adder
18.476
3150701DARBY 4
Adder
18.433
3150681DARBY 2
Adder
18.412
3150671DARBY 1
Adder
18.39
3145493TOT1
Solar/Wind Harmer
0.592
3145453TOT5
Solar/Wind Harmer
0.355
3145603CNETO
Solar/Wind Harmer
0.237
315976AC1-164 GENA
Solar/Wind Harmer
2.665
316169AC1-164_GENC
Solar/Wind Harmer
2.302
961601AG1-000A GEN
Solar/Wind Harmer
4.482
316049AB1-081 GEN
Solar/Wind Harmer
1.434
316263AC1-034 GEN
Solar/Wind Harmer
9.576
970323AG2-213 GEN
Solar/Wind Harmer
10.736
962561AG1-105 GEN
Solar/Wind Harmer
11.943
964791AG1-342 GEN
Solar/Wind Harmer
4.747
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
958211AF2-115 GEN
Solar/Wind Harmer
2.957
3144293JTRSVLE
Adder
0.588
3147133PAMPLIN
Solar/Wind Harmer
0.244
3147133PAMPLIN
Solar/Wind Harmer
0.196
316118AC1-105 GEN
Solar/Wind Harmer
0.623
316156AD2-030 GEN
Solar/Wind Harmer
0.177
316312AB1-027
Solar/Wind Harmer
0.426
3142296MT RD221
Adder
0.747
966871AG1-558 GEN
Solar/Wind Harmer
0.251
3146776BUCKING
Solar/Wind Harmer
0.847
3146776BUCKING
Solar/Wind Harmer
0.069
3150341NORNECKC1
Adder
1.994
3150341NORNECKC1
Adder
1.978
942751AE2-291 GEN
Solar/Wind Harmer
9.753
972189AH1-679 GEN
Adder
2.484
942671AE2-283 GEN
Solar/Wind Harmer
3.241
972193AH1-681 GEN
Adder
2.943
316045AC1-158 PL2
Solar/Wind Helper
7.063
316450AC1-158 RIC
Solar/Wind Helper
0.589
316006AB2-029 C
Solar/Wind Helper
0.131
316411AF1-147_GEN1
Solar/Wind Helper
0.811
LAGNLTFEXP_LAGN->PJM
CLTF
12.446
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.855
TVALTFEXP_TVA->PJM
CLTF
6.264
CPLELTFEXP_CPLE->PJM
CLTF
16.77
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.592
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.214
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.577
MECLTFEXP_MEC->PJM
CLTF
6.248
SIGELTFEXP_SIGE->PJM
CLTF
0.19
NYPJM->LTFIMP_NY
CLTF
3.58
LGEELTFEXP_LGEE->PJM
CLTF
2.327
WECLTFEXP_WEC->PJM
CLTF
1.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-1: G202_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-1: G202_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.61 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4010.0
MW Contribution:
3.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
4.529
315241AE2-183_GT1
50/50
4.517
972185AH1-677 GEN
50/50
16.37
3151041BRUNSWICKG3
50/50
3.569
316303AF2-085
50/50
5.401
972187AH1-678 GEN
50/50
8.19
971223AH1-071 GEN
Solar/Wind Harmer
4.267
970933AG2-581 GEN
Solar/Wind Harmer
27.786
3143526WINTERP
Solar/Wind Harmer
-0.15
315244AE2-183_ST
50/50
7.864
963041AG1-153 GEN
50/50
7.226
315779AE2-040
50/50
3.408
3151541CLOVER2
50/50
4.885
970533AG2-339 GEN
Solar/Wind Harmer
21.437
970673AG2-436 GEN
Solar/Wind Harmer
68.876
971967AH1-528 GEN
Solar/Wind Harmer
57.259
316233AE1-074 FULL
Solar/Wind Harmer
0.781
971281AH1-106 GEN
Solar/Wind Harmer
4.718
971283AH1-107 GEN
Solar/Wind Harmer
4.718
970085AG2-068 GEN
Solar/Wind Harmer
17.983
970581AG2-369 GEN
Solar/Wind Harmer
15.465
315814AE2-033 C
Solar/Wind Harmer
25.433
316258AE1-075 C
Solar/Wind Harmer
0.646
316405AF2-144 C
Solar/Wind Harmer
0.682
3143316POE
Solar/Wind Harmer
-0.101
316486AD2-202 GEN
Solar/Wind Harmer
0.652
316316AC1-027 C
Solar/Wind Harmer
0.76
316018AA1-139 ULT2
Solar/Wind Harmer
2.12
957871AF2-081 GEN
Solar/Wind Harmer
12.403
3151081ELIZAR1
Adder
20.233
3151091ELIZAR2
Adder
19.882
3146406KITTY HAWK
Solar/Wind Harmer
0.021
313526AB2-022
Solar/Wind Harmer
0.663
3146396TANGLEW
Solar/Wind Harmer
0.452
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.393
315833AF1-017_GEN
Solar/Wind Harmer
4.666
946281AF1-292 GEN
Solar/Wind Harmer
0.549
970657AG2-426 GEN
Solar/Wind Harmer
1.545
315800Z1-036_GEN1
Solar/Wind Harmer
5.978
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
315652AC1-086 GEN
Solar/Wind Harmer
26.833
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.592
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.713
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.773
315733AD1-074 GEN2
Solar/Wind Harmer
4.773
316426AA2-053 GEN
Solar/Wind Harmer
2.378
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.315
316236AE1-162_GEN
Solar/Wind Harmer
0.708
316463AE2-346 GEN
Solar/Wind Harmer
0.38
3145513AHOSKIE
Solar/Wind Harmer
0.205
961941AG1-037 GEN
Solar/Wind Harmer
0.177
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.577
971445AH1-216 GEN
Solar/Wind Harmer
14.537
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
970831AG2-522 GEN
Solar/Wind Harmer
11.657
3146033SCOT NK
Solar/Wind Harmer
-0.091
316174AB2-169 GEN
Solar/Wind Harmer
3.518
3151201GRAVEL4
Adder
14.777
3151221GRAVEL6
Adder
14.76
3151191GRAVEL3
Adder
14.59
3151211GRAVEL5
Adder
14.59
316210AC1-098 GEN
Solar/Wind Harmer
3.571
316274AC1-208 GEN
Solar/Wind Harmer
2.45
316238AB2-078_GEN
Solar/Wind Harmer
0.68
316239AB2-077_GEN
Solar/Wind Harmer
0.68
316327AA2-057 GEN
Solar/Wind Harmer
2.241
3145746EVERETS
Solar/Wind Harmer
-0.087
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3144303KENBRDG
Solar/Wind Harmer
-0.018
315697AD1-025 GEN
Solar/Wind Harmer
4.457
957861AF2-080 GEN
Solar/Wind Harmer
9.602
3151031BRUNSWICKG2
50/50
3.569
970683AG2-441 GEN
Solar/Wind Harmer
15.425
970681AG2-440 GEN
Solar/Wind Harmer
10.238
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
946301AF1-294 GEN
Solar/Wind Harmer
5.536
961791AG1-021 GEN
Solar/Wind Harmer
2.701
3147173SINAI
Solar/Wind Harmer
-0.021
3147243WELCO
Solar/Wind Harmer
-0.013
316382AG1-145 C
Solar/Wind Harmer
0.578
316159AE1-175 C
Solar/Wind Harmer
0.515
957831AF2-077 GEN
Solar/Wind Harmer
0.567
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971845AH1-439 GEN
Solar/Wind Harmer
9.775
316322AB2-045
Solar/Wind Harmer
0.611
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
3143873LANEXA
Solar/Wind Harmer
-0.01
957601AF2-054 GEN
Solar/Wind Harmer
0.498
3141873WAN 176
Solar/Wind Harmer
-0.003
270455AD2-022 GEN
Solar/Wind Harmer
2.939
270457AD2-023 GEN
Solar/Wind Harmer
1.49
316059AD1-063 C
Solar/Wind Harmer
0.37
3141913WHIT STONE
Solar/Wind Harmer
-0.016
3138133OCRAN
Solar/Wind Harmer
-0.005
972205AH1-687 GEN
Adder
5.885
970413AG2-270 GEN
50/50
21.437
3151101ELIZAR3
50/50
21.744
944011AF1-069 GEN
Solar/Wind Harmer
18.729
970917AG2-570 GEN
Solar/Wind Harmer
72.999
3143336POWHATN
Solar/Wind Harmer
2.691
316478AD1-087 GEN
Solar/Wind Harmer
2.225
944581AF1-123 GEN
Solar/Wind Harmer
114.073
944601AF1-125 GEN
Solar/Wind Harmer
112.293
3142956BIRDNECK
Solar/Wind Harmer
1.332
316017AA1-139 ULT1
Solar/Wind Harmer
2.002
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
2.867
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316305AF2-043 C
Solar/Wind Harmer
0.743
316246AF1-032 C
Solar/Wind Harmer
0.498
316320Y1-086
Solar/Wind Harmer
1.443
316321Z2-027
Solar/Wind Harmer
0.661
966621AG1-532 GEN
Solar/Wind Harmer
0.497
970657AG2-426 GEN
Solar/Wind Harmer
4.95
3146516WINFALL
Solar/Wind Harmer
-0.024
315813AE1-149 C
Solar/Wind Harmer
15.281
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
316181AB2-040 GEN
Solar/Wind Harmer
3.355
3156081AA2-088 GEN
Solar/Wind Harmer
7.766
3147043LAWRENC
Solar/Wind Harmer
-0.014
316011AB1-132 GEN
Solar/Wind Harmer
4.982
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.166
3145893MURPHYS
Solar/Wind Harmer
-0.024
315735AD1-075 GEN1
Solar/Wind Harmer
2.386
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.289
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
3150861SPRUNCD
Adder
0.964
316317KELFORD C
Solar/Wind Harmer
1.075
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3151171GRAVELC
Adder
2.84
316212AC1-099_GEN
Solar/Wind Harmer
1.984
961611AG1-000B GEN
Solar/Wind Harmer
4.744
315722AD1-056 GEN
Solar/Wind Harmer
8.004
964241AG1-285 GEN
Solar/Wind Harmer
17.54
3145933PARMELE
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.283
971775AH1-396 GEN
Solar/Wind Harmer
1.559
3144356SAPONY
Solar/Wind Harmer
0.957
316315AB2-025 C
Solar/Wind Harmer
0.738
970099AG2-077 GEN
Solar/Wind Harmer
33.814
316313AB2-026
Solar/Wind Harmer
0.718
316365GEN2_N
Solar/Wind Harmer
1.688
316294AC1-161 GEN
Solar/Wind Harmer
8.066
316185AD1-033 GEN
Solar/Wind Harmer
2.619
3145506HICKORY
Solar/Wind Harmer
-0.099
3145506HICKORY
Solar/Wind Harmer
-0.059
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.669
316388AE2-253 GEN
Solar/Wind Harmer
1.669
3137176SLIGO L2192
Solar/Wind Harmer
-0.098
3146456SLIGO L269
Solar/Wind Harmer
2.926
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.308
3150991CHESPKB
Adder
2.252
316336AC2-165 C
Solar/Wind Harmer
15.441
3146386ELIZ CT
Solar/Wind Harmer
-0.025
315835AF2-110_GEN
Solar/Wind Harmer
3.077
316349AD2-085 GEN
Solar/Wind Harmer
2.181
316431W1029_GEN1
Solar/Wind Harmer
4.437
316433W1029_GEN2
Solar/Wind Harmer
4.437
316435W1029_GEN3
Solar/Wind Harmer
4.437
316083AB2-161 GEN
Solar/Wind Harmer
3.973
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
5.77
3146376EDENTON
Solar/Wind Harmer
0.716
3146376EDENTON
Solar/Wind Harmer
0.716
313506AB2-031 GEN
Solar/Wind Harmer
1.931
315687AD1-152 GEN
Solar/Wind Harmer
2.894
315614AA2-178 GEN
Solar/Wind Harmer
2.57
962571AG1-106 GEN
Solar/Wind Harmer
3.429
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.663
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
0.196
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316065AD1-022 GEN
Solar/Wind Harmer
11.802
316140AB2-099
Solar/Wind Harmer
0.158
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145783HORNRTN
Solar/Wind Harmer
2.788
3145783HORNRTN
Solar/Wind Harmer
2.231
3145783HORNRTN
Solar/Wind Harmer
0.697
3145783HORNRTN
Solar/Wind Harmer
0.279
970301AG2-198 GEN
Solar/Wind Harmer
11.413
313527AB2-043 GEN
Solar/Wind Harmer
3.677
316237AB2-079_GEN
Solar/Wind Harmer
0.68
315724AD1-057 GEN
Solar/Wind Harmer
4.402
316240AF1-291 C
Solar/Wind Harmer
0.673
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
316005AA1-067
Solar/Wind Harmer
0.446
970323AG2-213 GEN
Solar/Wind Harmer
11.044
316033AB2-134 GEN
Solar/Wind Harmer
7.111
944641AF1-129 GEN
Adder
93.169
962561AG1-105 GEN
Solar/Wind Harmer
12.316
3145493TOT1
Solar/Wind Harmer
0.337
3145453TOT5
Solar/Wind Harmer
0.202
3145603CNETO
Solar/Wind Harmer
0.135
964791AG1-342 GEN
Solar/Wind Harmer
4.648
3146843MT LREL
Solar/Wind Harmer
-0.022
3146843MT LREL
Solar/Wind Harmer
-0.022
961601AG1-000A GEN
Solar/Wind Harmer
8.508
316049AB1-081 GEN
Solar/Wind Harmer
2.328
316263AC1-034 GEN
Solar/Wind Harmer
10.143
958211AF2-115 GEN
Solar/Wind Harmer
3.376
3144293JTRSVLE
Adder
0.459
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3147133PAMPLIN
Solar/Wind Harmer
-0.017
316118AC1-105 GEN
Solar/Wind Harmer
1.47
316248AF1-058 C
Solar/Wind Harmer
0.635
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
3142946ENON
Solar/Wind Harmer
-0.002
3142366NRTHEST
Adder
0.5
3150691DARBY 3
Adder
10.856
3150701DARBY 4
Adder
10.831
3150681DARBY 2
Adder
10.818
3150671DARBY 1
Adder
10.806
316441AF1-014 GEN
Solar/Wind Harmer
1.124
315666AE1-190 GEN
Solar/Wind Harmer
0.501
316156AD2-030 GEN
Solar/Wind Harmer
0.443
315976AC1-164 GENA
Solar/Wind Harmer
3.681
316169AC1-164_GENC
Solar/Wind Harmer
3.18
3142296MT RD221
Adder
0.385
3150341NORNECKC1
Adder
1.196
3150341NORNECKC1
Adder
1.187
316045AC1-158 PL2
Solar/Wind Helper
5.276
316450AC1-158 RIC
Solar/Wind Helper
0.44
970119AG2-088 GEN
50/50
40.505
315243AE2-183_GT3
50/50
4.529
3151051BRUNSWICKS1
50/50
7.41
3151021BRUNSWICKG1
50/50
3.569
971451AH1-221 GEN
50/50
10.839
3151531CLOVER1
50/50
4.922
3143226MDLTHAN
Solar/Wind Harmer
-0.034
941031AE2-094 GEN
Solar/Wind Harmer
59.772
940641AE2-051 GEN
Solar/Wind Harmer
29.706
939411AE1-173 GEN
Solar/Wind Harmer
149.955
970919AG2-571 GEN
Solar/Wind Harmer
9.24
3143526WINTERP
Solar/Wind Harmer
-0.15
970087AG2-069 GEN
Solar/Wind Harmer
26.974
957481AF2-042 GEN
Solar/Wind Harmer
84.535
3143336POWHATN
Solar/Wind Harmer
3.166
315693AD1-088 GEN
Solar/Wind Harmer
13.017
316023GEN1_S
Solar/Wind Harmer
1.688
944591AF1-124 GEN
Solar/Wind Harmer
114.484
315773AC2-141 GEN
Solar/Wind Harmer
10.436
3146456SLIGO L269
Solar/Wind Harmer
-0.025
319010AE1-072 C
Solar/Wind Harmer
4.999
316375AC2-012 GEN
Solar/Wind Harmer
8.56
316036AC1-147 C
Solar/Wind Harmer
0.666
3150981CHESPKA
Adder
2.751
316093AE2-104_GEN
Solar/Wind Harmer
7.158
960081AF2-299 GEN
Solar/Wind Harmer
2.757
316381AD1-082 GEN
Solar/Wind Harmer
2.24
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.024
316087AB2-174 GEN
Solar/Wind Harmer
3.449
315611Z1-036_GEN2
Solar/Wind Harmer
5.978
3130156CHOWAN
Solar/Wind Harmer
-0.024
316072AD1-144
Solar/Wind Harmer
0.486
3147043LAWRENC
Adder
1.928
315816AE2-034 GEN
Solar/Wind Harmer
1.928
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.393
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.705
315607AA1-063A GEN
Solar/Wind Harmer
2.392
315737AD1-076 GEN
Solar/Wind Harmer
4.487
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
959311AF2-222 GEN
Solar/Wind Harmer
22.982
3146233WITAKRS
Solar/Wind Harmer
0.459
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.014
315778AD1-151 GEN
Solar/Wind Harmer
19.499
316420AA1-050 GEN
Solar/Wind Harmer
2.492
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
316458AB2-190 GEN2
Solar/Wind Harmer
2.184
961601AG1-000A GEN
Solar/Wind Harmer
8.615
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3144293JTRSVLE
Adder
0.459
3147133PAMPLIN
Solar/Wind Harmer
-0.067
970133AG2-095 GEN
Solar/Wind Harmer
2.385
3144216WINCHST
Adder
0.71
942461AE2-259 GEN
Solar/Wind Harmer
3.153
3150921YORKTN3
Adder
4.678
3146926FARMVIL
Solar/Wind Harmer
-0.012
316003AC1-222 GEN
Solar/Wind Harmer
1.956
3143096IRON208
Adder
0.729
3143096IRON208
Adder
0.715
316222AC1-221 GEN
Solar/Wind Harmer
1.937
316283AC2-100 C
Solar/Wind Harmer
1.799
971683AH1-343 GEN
Solar/Wind Harmer
8.146
3146776BUCKING
Solar/Wind Harmer
-0.006
3142946ENON
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
316203AE2-005 GEN
Solar/Wind Harmer
7.033
3141843SHACKLE
Adder
0.759
3141873WAN 176
Solar/Wind Harmer
1.975
970293AG2-193 GEN
Solar/Wind Harmer
2.064
3141766HARMONY
Solar/Wind Harmer
1.459
316123AC1-075 GEN
Solar/Wind Harmer
1.757
316075AC2-137 C
Solar/Wind Harmer
0.431
3150351NORNECKC2
Adder
1.158
3147666LOUISA
Solar/Wind Helper
0.519
972003AH1-546 GEN
Solar/Wind Harmer
3.861
971547AH1-271 GEN
Solar/Wind Harmer
5.895
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
3150851SPRUNCC
Adder
0.964
3145783HORNRTN
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.154
3145683EARLEYS
Solar/Wind Harmer
-0.023
316129AC1-054 GEN
Solar/Wind Harmer
2.034
971065AG2-659 GEN
Solar/Wind Harmer
11.619
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3151171GRAVELC
Adder
2.16
315671AE2-027_GEN
Solar/Wind Harmer
4.096
316131AB2-060 GEN
Solar/Wind Harmer
2.433
961611AG1-000B GEN
Solar/Wind Harmer
11.118
3146293MARTNCO
Solar/Wind Harmer
0.139
315785AD2-033 C
Solar/Wind Harmer
5.02
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316034AC1-036 C
Solar/Wind Harmer
0.408
316369SG1_INVT
Solar/Wind Harmer
3.938
316494AC1-189 GEN
Solar/Wind Harmer
2.361
316319Z2-044 C
Solar/Wind Harmer
1.212
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.467
961671AG1-007 GEN
Solar/Wind Harmer
0.276
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.647
970401AG2-262 GEN
Solar/Wind Harmer
1.42
970685AG2-442 GEN
Solar/Wind Harmer
19.016
316132AB2-190 GEN1
Solar/Wind Harmer
2.184
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316359AB2-059 GEN
Solar/Wind Harmer
2.91
3142053HEARTS
Solar/Wind Harmer
0.254
971563AH1-280 GEN
Solar/Wind Harmer
2.701
3144293JTRSVLE
Adder
0.459
3144293JTRSVLE
Adder
0.362
3138126ROCKLANDING
Solar/Wind Harmer
0.065
3142543TWELFTH
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
-0.012
971317AH1-138 GEN
Solar/Wind Harmer
2.496
970937AG2-583 GEN
Solar/Wind Harmer
14.174
3143096IRON208
Adder
0.729
944631AF1-128 GEN
Adder
80.655
3146776BUCKING
Solar/Wind Harmer
-0.007
3142433PROV 92
Solar/Wind Harmer
-0.07
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
971777AH1-397 GEN
Solar/Wind Harmer
1.947
315662AE1-191 GEN
Solar/Wind Harmer
2.004
316280AD1-041 GEN
Solar/Wind Harmer
1.253
3141766HARMONY
Solar/Wind Harmer
-0.003
316314AB2-024 C
Solar/Wind Harmer
1.387
315975AC1-164 GENB
Solar/Wind Harmer
0.109
3138133OCRAN
Solar/Wind Harmer
-0.009
3150351NORNECKC2
Adder
1.139
316447AC1-158 HLD
Solar/Wind Helper
3.628
316044AC1-158 PL1
Solar/Wind Helper
1.649
3147666LOUISA
Solar/Wind Helper
0.903
LAGNLTFEXP_LAGN->PJM
CLTF
8.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.923
TVALTFEXP_TVA->PJM
CLTF
4.46
CPLELTFEXP_CPLE->PJM
CLTF
12.928
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.548
CBM West 1LTFEXP_CBM-W1->PJM
CBM
26.825
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.236
MECLTFEXP_MEC->PJM
CLTF
4.218
SIGELTFEXP_SIGE->PJM
CLTF
0.127
NYPJM->LTFIMP_NY
CLTF
2.451
LGEELTFEXP_LGEE->PJM
CLTF
1.527
WECLTFEXP_WEC->PJM
CLTF
0.775

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B2_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B2_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:124.42 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3879.34
MW Contribution:
3.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.422
315244AE2-183_ST
50/50
7.898
963041AG1-153 GEN
50/50
7.258
315779AE2-040
50/50
3.424
3151541CLOVER2
50/50
4.907
970533AG2-339 GEN
Solar/Wind Harmer
21.529
970673AG2-436 GEN
Solar/Wind Harmer
69.173
971967AH1-528 GEN
Solar/Wind Harmer
57.507
316233AE1-074 FULL
Solar/Wind Harmer
0.785
971281AH1-106 GEN
Solar/Wind Harmer
4.74
971283AH1-107 GEN
Solar/Wind Harmer
4.74
970085AG2-068 GEN
Solar/Wind Harmer
18.064
970581AG2-369 GEN
Solar/Wind Harmer
15.535
315814AE2-033 C
Solar/Wind Harmer
25.558
316258AE1-075 C
Solar/Wind Harmer
0.648
316405AF2-144 C
Solar/Wind Harmer
0.684
3143316POE
Solar/Wind Harmer
-0.102
316486AD2-202 GEN
Solar/Wind Harmer
0.655
316316AC1-027 C
Solar/Wind Harmer
0.765
316018AA1-139 ULT2
Solar/Wind Harmer
2.131
3151081ELIZAR1
Adder
20.345
3151091ELIZAR2
Adder
19.992
957871AF2-081 GEN
Solar/Wind Harmer
12.472
3146406KITTY HAWK
Solar/Wind Harmer
0.021
313526AB2-022
Solar/Wind Harmer
0.667
3146396TANGLEW
Solar/Wind Harmer
0.455
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.462
315833AF1-017_GEN
Solar/Wind Harmer
4.692
970657AG2-426 GEN
Solar/Wind Harmer
1.554
946281AF1-292 GEN
Solar/Wind Harmer
0.552
315800Z1-036_GEN1
Solar/Wind Harmer
6.011
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
315652AC1-086 GEN
Solar/Wind Harmer
26.977
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.595
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.718
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.8
315733AD1-074 GEN2
Solar/Wind Harmer
4.8
316426AA2-053 GEN
Solar/Wind Harmer
2.39
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.373
316236AE1-162_GEN
Solar/Wind Harmer
0.713
316463AE2-346 GEN
Solar/Wind Harmer
0.382
3145513AHOSKIE
Solar/Wind Harmer
0.206
961941AG1-037 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.586
971445AH1-216 GEN
Solar/Wind Harmer
14.622
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.716
3146033SCOT NK
Solar/Wind Harmer
-0.092
316174AB2-169 GEN
Solar/Wind Harmer
3.538
3151201GRAVEL4
Adder
14.866
3151221GRAVEL6
Adder
14.849
3151191GRAVEL3
Adder
14.678
3151211GRAVEL5
Adder
14.678
316210AC1-098 GEN
Solar/Wind Harmer
3.59
316274AC1-208 GEN
Solar/Wind Harmer
2.463
316238AB2-078_GEN
Solar/Wind Harmer
0.683
316239AB2-077_GEN
Solar/Wind Harmer
0.683
316327AA2-057 GEN
Solar/Wind Harmer
2.253
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3151031BRUNSWICKG2
50/50
3.585
970413AG2-270 GEN
50/50
21.534
3151101ELIZAR3
50/50
21.865
944011AF1-069 GEN
Solar/Wind Harmer
18.809
970917AG2-570 GEN
Solar/Wind Harmer
73.327
3143336POWHATN
Solar/Wind Harmer
2.7
316478AD1-087 GEN
Solar/Wind Harmer
2.235
944581AF1-123 GEN
Solar/Wind Harmer
114.701
944601AF1-125 GEN
Solar/Wind Harmer
112.911
3142956BIRDNECK
Solar/Wind Harmer
1.339
316017AA1-139 ULT1
Solar/Wind Harmer
2.013
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
2.883
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316305AF2-043 C
Solar/Wind Harmer
0.747
316246AF1-032 C
Solar/Wind Harmer
0.501
316320Y1-086
Solar/Wind Harmer
1.451
316321Z2-027
Solar/Wind Harmer
0.665
970657AG2-426 GEN
Solar/Wind Harmer
4.977
966621AG1-532 GEN
Solar/Wind Harmer
0.5
3146516WINFALL
Solar/Wind Harmer
-0.025
315813AE1-149 C
Solar/Wind Harmer
15.367
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
316181AB2-040 GEN
Solar/Wind Harmer
3.372
3156081AA2-088 GEN
Solar/Wind Harmer
7.808
3147043LAWRENC
Solar/Wind Harmer
-0.014
316011AB1-132 GEN
Solar/Wind Harmer
5.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.024
315735AD1-075 GEN1
Solar/Wind Harmer
2.399
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.291
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150861SPRUNCD
Adder
0.969
970119AG2-088 GEN
50/50
40.664
315243AE2-183_GT3
50/50
4.548
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.585
971451AH1-221 GEN
50/50
10.887
3151531CLOVER1
50/50
4.945
3143226MDLTHAN
Solar/Wind Harmer
-0.034
941031AE2-094 GEN
Solar/Wind Harmer
60.028
940641AE2-051 GEN
Solar/Wind Harmer
29.837
3145746EVERETS
Solar/Wind Harmer
-0.022
315697AD1-025 GEN
Solar/Wind Harmer
4.485
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.657
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
15.489
970681AG2-440 GEN
Solar/Wind Harmer
10.28
946301AF1-294 GEN
Solar/Wind Harmer
5.558
961791AG1-021 GEN
Solar/Wind Harmer
2.711
3147173SINAI
Solar/Wind Harmer
-0.021
3147243WELCO
Solar/Wind Harmer
-0.013
316382AG1-145 C
Solar/Wind Harmer
0.582
316159AE1-175 C
Solar/Wind Harmer
0.518
3146263WOODLND
Solar/Wind Harmer
-0.024
316317KELFORD C
Solar/Wind Harmer
1.081
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3151171GRAVELC
Adder
2.857
316212AC1-099_GEN
Solar/Wind Harmer
1.995
961611AG1-000B GEN
Solar/Wind Harmer
4.773
315722AD1-056 GEN
Solar/Wind Harmer
8.048
964241AG1-285 GEN
Solar/Wind Harmer
17.62
3145933PARMELE
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.319
971775AH1-396 GEN
Solar/Wind Harmer
1.565
315242AE2-183_GT2
50/50
4.548
315241AE2-183_GT1
50/50
4.536
972185AH1-677 GEN
50/50
16.441
3151041BRUNSWICKG3
50/50
3.585
972187AH1-678 GEN
50/50
8.226
971223AH1-071 GEN
Solar/Wind Harmer
4.283
970933AG2-581 GEN
Solar/Wind Harmer
27.907
3143526WINTERP
Solar/Wind Harmer
-0.151
3144356SAPONY
Solar/Wind Harmer
0.961
316315AB2-025 C
Solar/Wind Harmer
0.742
970099AG2-077 GEN
Solar/Wind Harmer
33.963
316313AB2-026
Solar/Wind Harmer
0.72
316365GEN2_N
Solar/Wind Harmer
1.697
316294AC1-161 GEN
Solar/Wind Harmer
8.111
316185AD1-033 GEN
Solar/Wind Harmer
2.633
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.678
316388AE2-253 GEN
Solar/Wind Harmer
1.678
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.942
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.32
3150991CHESPKB
Adder
2.265
316336AC2-165 C
Solar/Wind Harmer
15.488
3146386ELIZ CT
Solar/Wind Harmer
-0.025
315835AF2-110_GEN
Solar/Wind Harmer
3.094
316349AD2-085 GEN
Solar/Wind Harmer
2.193
316083AB2-161 GEN
Solar/Wind Harmer
3.995
316431W1029_GEN1
Solar/Wind Harmer
4.461
316433W1029_GEN2
Solar/Wind Harmer
4.461
316435W1029_GEN3
Solar/Wind Harmer
4.461
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
5.802
3146376EDENTON
Solar/Wind Harmer
0.72
3146376EDENTON
Solar/Wind Harmer
0.72
313506AB2-031 GEN
Solar/Wind Harmer
1.941
315687AD1-152 GEN
Solar/Wind Harmer
2.907
315614AA2-178 GEN
Solar/Wind Harmer
2.584
962571AG1-106 GEN
Solar/Wind Harmer
3.447
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.667
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
0.197
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316065AD1-022 GEN
Solar/Wind Harmer
11.868
316140AB2-099
Solar/Wind Harmer
0.159
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145783HORNRTN
Solar/Wind Harmer
2.803
3145783HORNRTN
Solar/Wind Harmer
2.243
939411AE1-173 GEN
Solar/Wind Harmer
150.649
970919AG2-571 GEN
Solar/Wind Harmer
9.282
3143526WINTERP
Solar/Wind Harmer
-0.151
970087AG2-069 GEN
Solar/Wind Harmer
27.097
957481AF2-042 GEN
Solar/Wind Harmer
84.909
3143336POWHATN
Solar/Wind Harmer
3.177
315693AD1-088 GEN
Solar/Wind Harmer
13.073
316023GEN1_S
Solar/Wind Harmer
1.697
944591AF1-124 GEN
Solar/Wind Harmer
115.114
315773AC2-141 GEN
Solar/Wind Harmer
10.494
3146456SLIGO L269
Solar/Wind Harmer
-0.025
319010AE1-072 C
Solar/Wind Harmer
5.027
316375AC2-012 GEN
Solar/Wind Harmer
8.608
316036AC1-147 C
Solar/Wind Harmer
0.67
3150981CHESPKA
Adder
2.766
316093AE2-104_GEN
Solar/Wind Harmer
7.197
316381AD1-082 GEN
Solar/Wind Harmer
2.253
957831AF2-077 GEN
Solar/Wind Harmer
0.572
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971845AH1-439 GEN
Solar/Wind Harmer
9.798
316322AB2-045
Solar/Wind Harmer
0.613
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3143873LANEXA
Solar/Wind Harmer
-0.01
957601AF2-054 GEN
Solar/Wind Harmer
0.502
3141873WAN 176
Solar/Wind Harmer
-0.003
270455AD2-022 GEN
Solar/Wind Harmer
2.959
270457AD2-023 GEN
Solar/Wind Harmer
1.501
316059AD1-063 C
Solar/Wind Harmer
0.373
3141913WHIT STONE
Solar/Wind Harmer
-0.016
3138133OCRAN
Solar/Wind Harmer
-0.005
972205AH1-687 GEN
Adder
5.891
960081AF2-299 GEN
Solar/Wind Harmer
2.771
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.467
315611Z1-036_GEN2
Solar/Wind Harmer
6.011
3130156CHOWAN
Solar/Wind Harmer
-0.024
316072AD1-144
Solar/Wind Harmer
0.489
3147043LAWRENC
Adder
1.937
315816AE2-034 GEN
Solar/Wind Harmer
1.938
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.517
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.709
315607AA1-063A GEN
Solar/Wind Harmer
2.405
315737AD1-076 GEN
Solar/Wind Harmer
4.512
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.927
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150851SPRUNCC
Adder
0.969
3146263WOODLND
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.171
3145683EARLEYS
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.045
971065AG2-659 GEN
Solar/Wind Harmer
11.678
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3151171GRAVELC
Adder
2.173
315671AE2-027_GEN
Solar/Wind Harmer
4.121
316131AB2-060 GEN
Solar/Wind Harmer
2.444
961611AG1-000B GEN
Solar/Wind Harmer
11.186
3146293MARTNCO
Solar/Wind Harmer
0.139
315785AD2-033 C
Solar/Wind Harmer
5.042
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316369SG1_INVT
Solar/Wind Harmer
3.963
316034AC1-036 C
Solar/Wind Harmer
0.41
316494AC1-189 GEN
Solar/Wind Harmer
2.375
316319Z2-044 C
Solar/Wind Harmer
1.219
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.488
961671AG1-007 GEN
Solar/Wind Harmer
0.277
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.651
970401AG2-262 GEN
Solar/Wind Harmer
1.427
970685AG2-442 GEN
Solar/Wind Harmer
19.093
316132AB2-190 GEN1
Solar/Wind Harmer
2.198
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316359AB2-059 GEN
Solar/Wind Harmer
2.926
3142053HEARTS
Solar/Wind Harmer
0.256
971563AH1-280 GEN
Solar/Wind Harmer
2.711
3144293JTRSVLE
Adder
0.461
3144293JTRSVLE
Adder
0.364
3138126ROCKLANDING
Solar/Wind Harmer
0.065
3142543TWELFTH
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
-0.012
971317AH1-138 GEN
Solar/Wind Harmer
2.513
970937AG2-583 GEN
Solar/Wind Harmer
14.205
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.242
3146776BUCKING
Solar/Wind Harmer
-0.007
3142433PROV 92
Solar/Wind Harmer
-0.07
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
971777AH1-397 GEN
Solar/Wind Harmer
1.963
315662AE1-191 GEN
Solar/Wind Harmer
2.021
316280AD1-041 GEN
Solar/Wind Harmer
1.263
3141766HARMONY
Solar/Wind Harmer
-0.003
316314AB2-024 C
Solar/Wind Harmer
1.399
315975AC1-164 GENB
Solar/Wind Harmer
0.11
3138133OCRAN
Solar/Wind Harmer
-0.01
3150351NORNECKC2
Adder
1.151
316447AC1-158 HLD
Solar/Wind Helper
3.591
316044AC1-158 PL1
Solar/Wind Helper
1.632
3147666LOUISA
Solar/Wind Helper
0.979
316192AB2-158 GEN
Solar/Wind Helper
1.615
3145783HORNRTN
Solar/Wind Harmer
0.701
3145783HORNRTN
Solar/Wind Harmer
0.28
970301AG2-198 GEN
Solar/Wind Harmer
11.455
313527AB2-043 GEN
Solar/Wind Harmer
3.694
316237AB2-079_GEN
Solar/Wind Harmer
0.683
315724AD1-057 GEN
Solar/Wind Harmer
4.427
316240AF1-291 C
Solar/Wind Harmer
0.677
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.022
316005AA1-067
Solar/Wind Harmer
0.449
316033AB2-134 GEN
Solar/Wind Harmer
7.156
970323AG2-213 GEN
Solar/Wind Harmer
11.092
944641AF1-129 GEN
Adder
93.755
962561AG1-105 GEN
Solar/Wind Harmer
12.377
3145493TOT1
Solar/Wind Harmer
0.339
3145453TOT5
Solar/Wind Harmer
0.204
3145603CNETO
Solar/Wind Harmer
0.136
964791AG1-342 GEN
Solar/Wind Harmer
4.671
3146843MT LREL
Solar/Wind Harmer
-0.022
3146843MT LREL
Solar/Wind Harmer
-0.022
961601AG1-000A GEN
Solar/Wind Harmer
8.556
316049AB1-081 GEN
Solar/Wind Harmer
2.341
316263AC1-034 GEN
Solar/Wind Harmer
10.201
958211AF2-115 GEN
Solar/Wind Harmer
3.389
3144293JTRSVLE
Adder
0.461
316118AC1-105 GEN
Solar/Wind Harmer
1.478
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3147133PAMPLIN
Solar/Wind Harmer
-0.017
316248AF1-058 C
Solar/Wind Harmer
0.638
3142946ENON
Solar/Wind Harmer
-0.002
3146776BUCKING
Solar/Wind Harmer
-0.073
3146776BUCKING
Solar/Wind Harmer
-0.006
3142366NRTHEST
Adder
0.504
3150691DARBY 3
Adder
10.945
3150701DARBY 4
Adder
10.92
3150681DARBY 2
Adder
10.907
3150671DARBY 1
Adder
10.894
316441AF1-014 GEN
Solar/Wind Harmer
1.134
315666AE1-190 GEN
Solar/Wind Harmer
0.505
316156AD2-030 GEN
Solar/Wind Harmer
0.447
315976AC1-164 GENA
Solar/Wind Harmer
3.713
316169AC1-164_GENC
Solar/Wind Harmer
3.208
3142296MT RD221
Adder
0.389
3150341NORNECKC1
Adder
1.209
3150341NORNECKC1
Adder
1.2
316045AC1-158 PL2
Solar/Wind Helper
5.223
316450AC1-158 RIC
Solar/Wind Helper
0.435
959311AF2-222 GEN
Solar/Wind Harmer
23.08
3146233WITAKRS
Solar/Wind Harmer
0.462
3146233WITAKRS
Solar/Wind Harmer
-0.015
315778AD1-151 GEN
Solar/Wind Harmer
19.622
3138543CONSLDL
Solar/Wind Harmer
-0.014
316420AA1-050 GEN
Solar/Wind Harmer
2.506
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
316458AB2-190 GEN2
Solar/Wind Harmer
2.198
961601AG1-000A GEN
Solar/Wind Harmer
8.664
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3144293JTRSVLE
Adder
0.461
3147133PAMPLIN
Solar/Wind Harmer
-0.067
970133AG2-095 GEN
Solar/Wind Harmer
2.4
3144216WINCHST
Adder
0.715
3150921YORKTN3
Adder
4.709
942461AE2-259 GEN
Solar/Wind Harmer
3.164
3146926FARMVIL
Solar/Wind Harmer
-0.012
316003AC1-222 GEN
Solar/Wind Harmer
1.966
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
316222AC1-221 GEN
Solar/Wind Harmer
1.949
316283AC2-100 C
Solar/Wind Harmer
1.809
971683AH1-343 GEN
Solar/Wind Harmer
8.192
3142946ENON
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.765
316203AE2-005 GEN
Solar/Wind Harmer
7.092
3141873WAN 176
Solar/Wind Harmer
1.992
970293AG2-193 GEN
Solar/Wind Harmer
2.081
3141766HARMONY
Solar/Wind Harmer
1.471
316123AC1-075 GEN
Solar/Wind Harmer
1.768
316075AC2-137 C
Solar/Wind Harmer
0.435
3150351NORNECKC2
Adder
1.171
3147666LOUISA
Solar/Wind Helper
0.563
972003AH1-546 GEN
Solar/Wind Harmer
3.866
LAGNLTFEXP_LAGN->PJM
CLTF
9.042
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.15
TVALTFEXP_TVA->PJM
CLTF
4.533
CPLELTFEXP_CPLE->PJM
CLTF
13.013
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.505
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.506
MECLTFEXP_MEC->PJM
CLTF
4.337
SIGELTFEXP_SIGE->PJM
CLTF
0.13
NYPJM->LTFIMP_NY
CLTF
2.4
LGEELTFEXP_LGEE->PJM
CLTF
1.575
WECLTFEXP_WEC->PJM
CLTF
0.802

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B1_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:124.42 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3879.34
MW Contribution:
3.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.422
315244AE2-183_ST
50/50
7.898
963041AG1-153 GEN
50/50
7.258
315779AE2-040
50/50
3.424
3151541CLOVER2
50/50
4.907
970533AG2-339 GEN
Solar/Wind Harmer
21.529
970673AG2-436 GEN
Solar/Wind Harmer
69.173
971967AH1-528 GEN
Solar/Wind Harmer
57.507
316233AE1-074 FULL
Solar/Wind Harmer
0.785
971281AH1-106 GEN
Solar/Wind Harmer
4.74
971283AH1-107 GEN
Solar/Wind Harmer
4.74
970085AG2-068 GEN
Solar/Wind Harmer
18.064
970581AG2-369 GEN
Solar/Wind Harmer
15.535
315814AE2-033 C
Solar/Wind Harmer
25.558
316258AE1-075 C
Solar/Wind Harmer
0.648
316405AF2-144 C
Solar/Wind Harmer
0.684
3143316POE
Solar/Wind Harmer
-0.102
316486AD2-202 GEN
Solar/Wind Harmer
0.655
316316AC1-027 C
Solar/Wind Harmer
0.765
316018AA1-139 ULT2
Solar/Wind Harmer
2.131
3151081ELIZAR1
Adder
20.345
3151091ELIZAR2
Adder
19.992
957871AF2-081 GEN
Solar/Wind Harmer
12.472
3146406KITTY HAWK
Solar/Wind Harmer
0.021
313526AB2-022
Solar/Wind Harmer
0.667
3146396TANGLEW
Solar/Wind Harmer
0.455
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.462
315833AF1-017_GEN
Solar/Wind Harmer
4.692
970657AG2-426 GEN
Solar/Wind Harmer
1.554
946281AF1-292 GEN
Solar/Wind Harmer
0.552
315800Z1-036_GEN1
Solar/Wind Harmer
6.011
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
315652AC1-086 GEN
Solar/Wind Harmer
26.977
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.595
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.718
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.8
315733AD1-074 GEN2
Solar/Wind Harmer
4.8
316426AA2-053 GEN
Solar/Wind Harmer
2.39
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.373
316236AE1-162_GEN
Solar/Wind Harmer
0.713
316463AE2-346 GEN
Solar/Wind Harmer
0.382
3145513AHOSKIE
Solar/Wind Harmer
0.206
961941AG1-037 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.586
971445AH1-216 GEN
Solar/Wind Harmer
14.622
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.716
3146033SCOT NK
Solar/Wind Harmer
-0.092
316174AB2-169 GEN
Solar/Wind Harmer
3.538
3151201GRAVEL4
Adder
14.866
3151221GRAVEL6
Adder
14.849
3151191GRAVEL3
Adder
14.678
3151211GRAVEL5
Adder
14.678
316210AC1-098 GEN
Solar/Wind Harmer
3.59
316274AC1-208 GEN
Solar/Wind Harmer
2.463
316238AB2-078_GEN
Solar/Wind Harmer
0.683
316239AB2-077_GEN
Solar/Wind Harmer
0.683
316327AA2-057 GEN
Solar/Wind Harmer
2.253
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
315697AD1-025 GEN
Solar/Wind Harmer
4.485
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.657
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
15.489
970681AG2-440 GEN
Solar/Wind Harmer
10.28
946301AF1-294 GEN
Solar/Wind Harmer
5.558
961791AG1-021 GEN
Solar/Wind Harmer
2.711
3147173SINAI
Solar/Wind Harmer
-0.021
3147243WELCO
Solar/Wind Harmer
-0.013
316382AG1-145 C
Solar/Wind Harmer
0.582
316159AE1-175 C
Solar/Wind Harmer
0.518
957831AF2-077 GEN
Solar/Wind Harmer
0.572
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971845AH1-439 GEN
Solar/Wind Harmer
9.798
316322AB2-045
Solar/Wind Harmer
0.613
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3143873LANEXA
Solar/Wind Harmer
-0.01
957601AF2-054 GEN
Solar/Wind Harmer
0.502
3141873WAN 176
Solar/Wind Harmer
-0.003
270455AD2-022 GEN
Solar/Wind Harmer
2.959
270457AD2-023 GEN
Solar/Wind Harmer
1.501
316059AD1-063 C
Solar/Wind Harmer
0.373
3141913WHIT STONE
Solar/Wind Harmer
-0.016
3138133OCRAN
Solar/Wind Harmer
-0.005
972205AH1-687 GEN
Adder
5.891
315242AE2-183_GT2
50/50
4.548
315241AE2-183_GT1
50/50
4.536
972185AH1-677 GEN
50/50
16.441
3151041BRUNSWICKG3
50/50
3.585
972187AH1-678 GEN
50/50
8.226
971223AH1-071 GEN
Solar/Wind Harmer
4.283
970933AG2-581 GEN
Solar/Wind Harmer
27.907
3143526WINTERP
Solar/Wind Harmer
-0.151
3144356SAPONY
Solar/Wind Harmer
0.961
316315AB2-025 C
Solar/Wind Harmer
0.742
970099AG2-077 GEN
Solar/Wind Harmer
33.963
316313AB2-026
Solar/Wind Harmer
0.72
316365GEN2_N
Solar/Wind Harmer
1.697
316294AC1-161 GEN
Solar/Wind Harmer
8.111
316185AD1-033 GEN
Solar/Wind Harmer
2.633
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.678
316388AE2-253 GEN
Solar/Wind Harmer
1.678
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.942
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.32
3150991CHESPKB
Adder
2.265
316336AC2-165 C
Solar/Wind Harmer
15.488
3146386ELIZ CT
Solar/Wind Harmer
-0.025
315835AF2-110_GEN
Solar/Wind Harmer
3.094
316349AD2-085 GEN
Solar/Wind Harmer
2.193
316083AB2-161 GEN
Solar/Wind Harmer
3.995
316431W1029_GEN1
Solar/Wind Harmer
4.461
316433W1029_GEN2
Solar/Wind Harmer
4.461
316435W1029_GEN3
Solar/Wind Harmer
4.461
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
5.802
3146376EDENTON
Solar/Wind Harmer
0.72
3146376EDENTON
Solar/Wind Harmer
0.72
313506AB2-031 GEN
Solar/Wind Harmer
1.941
315687AD1-152 GEN
Solar/Wind Harmer
2.907
315614AA2-178 GEN
Solar/Wind Harmer
2.584
962571AG1-106 GEN
Solar/Wind Harmer
3.447
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.667
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
0.197
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316065AD1-022 GEN
Solar/Wind Harmer
11.868
316140AB2-099
Solar/Wind Harmer
0.159
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145783HORNRTN
Solar/Wind Harmer
2.803
3145783HORNRTN
Solar/Wind Harmer
2.243
3145783HORNRTN
Solar/Wind Harmer
0.701
3145783HORNRTN
Solar/Wind Harmer
0.28
970301AG2-198 GEN
Solar/Wind Harmer
11.455
313527AB2-043 GEN
Solar/Wind Harmer
3.694
316237AB2-079_GEN
Solar/Wind Harmer
0.683
315724AD1-057 GEN
Solar/Wind Harmer
4.427
316240AF1-291 C
Solar/Wind Harmer
0.677
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.022
316005AA1-067
Solar/Wind Harmer
0.449
316033AB2-134 GEN
Solar/Wind Harmer
7.156
970323AG2-213 GEN
Solar/Wind Harmer
11.092
944641AF1-129 GEN
Adder
93.755
962561AG1-105 GEN
Solar/Wind Harmer
12.377
3145493TOT1
Solar/Wind Harmer
0.339
3145453TOT5
Solar/Wind Harmer
0.204
3145603CNETO
Solar/Wind Harmer
0.136
964791AG1-342 GEN
Solar/Wind Harmer
4.671
3146843MT LREL
Solar/Wind Harmer
-0.022
3146843MT LREL
Solar/Wind Harmer
-0.022
961601AG1-000A GEN
Solar/Wind Harmer
8.556
316049AB1-081 GEN
Solar/Wind Harmer
2.341
316263AC1-034 GEN
Solar/Wind Harmer
10.201
958211AF2-115 GEN
Solar/Wind Harmer
3.389
3144293JTRSVLE
Adder
0.461
316118AC1-105 GEN
Solar/Wind Harmer
1.478
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3147133PAMPLIN
Solar/Wind Harmer
-0.017
316248AF1-058 C
Solar/Wind Harmer
0.638
3142946ENON
Solar/Wind Harmer
-0.002
3146776BUCKING
Solar/Wind Harmer
-0.073
3146776BUCKING
Solar/Wind Harmer
-0.006
3142366NRTHEST
Adder
0.504
3150691DARBY 3
Adder
10.945
3150701DARBY 4
Adder
10.92
3150681DARBY 2
Adder
10.907
3150671DARBY 1
Adder
10.894
316441AF1-014 GEN
Solar/Wind Harmer
1.134
315666AE1-190 GEN
Solar/Wind Harmer
0.505
316156AD2-030 GEN
Solar/Wind Harmer
0.447
315976AC1-164 GENA
Solar/Wind Harmer
3.713
316169AC1-164_GENC
Solar/Wind Harmer
3.208
3142296MT RD221
Adder
0.389
3150341NORNECKC1
Adder
1.209
3150341NORNECKC1
Adder
1.2
316045AC1-158 PL2
Solar/Wind Helper
5.223
316450AC1-158 RIC
Solar/Wind Helper
0.435
3151031BRUNSWICKG2
50/50
3.585
970413AG2-270 GEN
50/50
21.534
3151101ELIZAR3
50/50
21.865
944011AF1-069 GEN
Solar/Wind Harmer
18.809
970917AG2-570 GEN
Solar/Wind Harmer
73.327
3143336POWHATN
Solar/Wind Harmer
2.7
316478AD1-087 GEN
Solar/Wind Harmer
2.235
944581AF1-123 GEN
Solar/Wind Harmer
114.701
944601AF1-125 GEN
Solar/Wind Harmer
112.911
3142956BIRDNECK
Solar/Wind Harmer
1.339
316017AA1-139 ULT1
Solar/Wind Harmer
2.013
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
2.883
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316305AF2-043 C
Solar/Wind Harmer
0.747
316246AF1-032 C
Solar/Wind Harmer
0.501
316320Y1-086
Solar/Wind Harmer
1.451
316321Z2-027
Solar/Wind Harmer
0.665
970657AG2-426 GEN
Solar/Wind Harmer
4.977
966621AG1-532 GEN
Solar/Wind Harmer
0.5
3146516WINFALL
Solar/Wind Harmer
-0.025
315813AE1-149 C
Solar/Wind Harmer
15.367
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
316181AB2-040 GEN
Solar/Wind Harmer
3.372
3156081AA2-088 GEN
Solar/Wind Harmer
7.808
3147043LAWRENC
Solar/Wind Harmer
-0.014
316011AB1-132 GEN
Solar/Wind Harmer
5.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.024
315735AD1-075 GEN1
Solar/Wind Harmer
2.399
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.291
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150861SPRUNCD
Adder
0.969
3146263WOODLND
Solar/Wind Harmer
-0.024
316317KELFORD C
Solar/Wind Harmer
1.081
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3151171GRAVELC
Adder
2.857
316212AC1-099_GEN
Solar/Wind Harmer
1.995
961611AG1-000B GEN
Solar/Wind Harmer
4.773
315722AD1-056 GEN
Solar/Wind Harmer
8.048
964241AG1-285 GEN
Solar/Wind Harmer
17.62
3145933PARMELE
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.319
971775AH1-396 GEN
Solar/Wind Harmer
1.565
959311AF2-222 GEN
Solar/Wind Harmer
23.08
3146233WITAKRS
Solar/Wind Harmer
0.462
3146233WITAKRS
Solar/Wind Harmer
-0.015
315778AD1-151 GEN
Solar/Wind Harmer
19.622
3138543CONSLDL
Solar/Wind Harmer
-0.014
316420AA1-050 GEN
Solar/Wind Harmer
2.506
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
316458AB2-190 GEN2
Solar/Wind Harmer
2.198
961601AG1-000A GEN
Solar/Wind Harmer
8.664
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3144293JTRSVLE
Adder
0.461
3147133PAMPLIN
Solar/Wind Harmer
-0.067
970133AG2-095 GEN
Solar/Wind Harmer
2.4
3144216WINCHST
Adder
0.715
3150921YORKTN3
Adder
4.709
942461AE2-259 GEN
Solar/Wind Harmer
3.164
3146926FARMVIL
Solar/Wind Harmer
-0.012
316003AC1-222 GEN
Solar/Wind Harmer
1.966
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
316222AC1-221 GEN
Solar/Wind Harmer
1.949
316283AC2-100 C
Solar/Wind Harmer
1.809
971683AH1-343 GEN
Solar/Wind Harmer
8.192
3142946ENON
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.765
316203AE2-005 GEN
Solar/Wind Harmer
7.092
3141873WAN 176
Solar/Wind Harmer
1.992
970293AG2-193 GEN
Solar/Wind Harmer
2.081
3141766HARMONY
Solar/Wind Harmer
1.471
316123AC1-075 GEN
Solar/Wind Harmer
1.768
316075AC2-137 C
Solar/Wind Harmer
0.435
3150351NORNECKC2
Adder
1.171
3147666LOUISA
Solar/Wind Helper
0.563
972003AH1-546 GEN
Solar/Wind Harmer
3.866
970119AG2-088 GEN
50/50
40.664
315243AE2-183_GT3
50/50
4.548
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.585
971451AH1-221 GEN
50/50
10.887
3151531CLOVER1
50/50
4.945
3143226MDLTHAN
Solar/Wind Harmer
-0.034
941031AE2-094 GEN
Solar/Wind Harmer
60.028
940641AE2-051 GEN
Solar/Wind Harmer
29.837
939411AE1-173 GEN
Solar/Wind Harmer
150.649
970919AG2-571 GEN
Solar/Wind Harmer
9.282
3143526WINTERP
Solar/Wind Harmer
-0.151
970087AG2-069 GEN
Solar/Wind Harmer
27.097
957481AF2-042 GEN
Solar/Wind Harmer
84.909
3143336POWHATN
Solar/Wind Harmer
3.177
315693AD1-088 GEN
Solar/Wind Harmer
13.073
316023GEN1_S
Solar/Wind Harmer
1.697
944591AF1-124 GEN
Solar/Wind Harmer
115.114
315773AC2-141 GEN
Solar/Wind Harmer
10.494
3146456SLIGO L269
Solar/Wind Harmer
-0.025
319010AE1-072 C
Solar/Wind Harmer
5.027
316375AC2-012 GEN
Solar/Wind Harmer
8.608
316036AC1-147 C
Solar/Wind Harmer
0.67
3150981CHESPKA
Adder
2.766
316093AE2-104_GEN
Solar/Wind Harmer
7.197
316381AD1-082 GEN
Solar/Wind Harmer
2.253
960081AF2-299 GEN
Solar/Wind Harmer
2.771
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.467
315611Z1-036_GEN2
Solar/Wind Harmer
6.011
3130156CHOWAN
Solar/Wind Harmer
-0.024
316072AD1-144
Solar/Wind Harmer
0.489
3147043LAWRENC
Adder
1.937
315816AE2-034 GEN
Solar/Wind Harmer
1.938
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.517
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.709
315607AA1-063A GEN
Solar/Wind Harmer
2.405
315737AD1-076 GEN
Solar/Wind Harmer
4.512
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.927
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150851SPRUNCC
Adder
0.969
3146263WOODLND
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.171
3145683EARLEYS
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.045
971065AG2-659 GEN
Solar/Wind Harmer
11.678
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3151171GRAVELC
Adder
2.173
315671AE2-027_GEN
Solar/Wind Harmer
4.121
316131AB2-060 GEN
Solar/Wind Harmer
2.444
961611AG1-000B GEN
Solar/Wind Harmer
11.186
3146293MARTNCO
Solar/Wind Harmer
0.139
315785AD2-033 C
Solar/Wind Harmer
5.042
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316369SG1_INVT
Solar/Wind Harmer
3.963
316034AC1-036 C
Solar/Wind Harmer
0.41
316494AC1-189 GEN
Solar/Wind Harmer
2.375
316319Z2-044 C
Solar/Wind Harmer
1.219
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.488
961671AG1-007 GEN
Solar/Wind Harmer
0.277
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.651
970401AG2-262 GEN
Solar/Wind Harmer
1.427
970685AG2-442 GEN
Solar/Wind Harmer
19.093
316132AB2-190 GEN1
Solar/Wind Harmer
2.198
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316359AB2-059 GEN
Solar/Wind Harmer
2.926
3142053HEARTS
Solar/Wind Harmer
0.256
971563AH1-280 GEN
Solar/Wind Harmer
2.711
3144293JTRSVLE
Adder
0.461
3144293JTRSVLE
Adder
0.364
3138126ROCKLANDING
Solar/Wind Harmer
0.065
3142543TWELFTH
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
-0.012
971317AH1-138 GEN
Solar/Wind Harmer
2.513
970937AG2-583 GEN
Solar/Wind Harmer
14.205
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.242
3146776BUCKING
Solar/Wind Harmer
-0.007
3142433PROV 92
Solar/Wind Harmer
-0.07
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
971777AH1-397 GEN
Solar/Wind Harmer
1.963
315662AE1-191 GEN
Solar/Wind Harmer
2.021
316280AD1-041 GEN
Solar/Wind Harmer
1.263
3141766HARMONY
Solar/Wind Harmer
-0.003
316314AB2-024 C
Solar/Wind Harmer
1.399
315975AC1-164 GENB
Solar/Wind Harmer
0.11
3138133OCRAN
Solar/Wind Harmer
-0.01
3150351NORNECKC2
Adder
1.151
316447AC1-158 HLD
Solar/Wind Helper
3.591
316044AC1-158 PL1
Solar/Wind Helper
1.632
3147666LOUISA
Solar/Wind Helper
0.979
316192AB2-158 GEN
Solar/Wind Helper
1.615
LAGNLTFEXP_LAGN->PJM
CLTF
9.042
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.15
TVALTFEXP_TVA->PJM
CLTF
4.533
CPLELTFEXP_CPLE->PJM
CLTF
13.013
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.505
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.506
MECLTFEXP_MEC->PJM
CLTF
4.337
SIGELTFEXP_SIGE->PJM
CLTF
0.13
NYPJM->LTFIMP_NY
CLTF
2.4
LGEELTFEXP_LGEE->PJM
CLTF
1.575
WECLTFEXP_WEC->PJM
CLTF
0.802

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.54 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3946.36
MW Contribution:
5.24
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
43.358
315243AE2-183_GT3
50/50
5.288
3151051BRUNSWICKS1
50/50
8.652
3151021BRUNSWICKG1
50/50
4.168
971451AH1-221 GEN
50/50
12.657
3150981CHESPKA
50/50
3.859
3152331SURRY 2
50/50
11.829
940641AE2-051 GEN
Solar/Wind Harmer
26.953
941031AE2-094 GEN
Solar/Wind Harmer
61.021
939411AE1-173 GEN
Solar/Wind Harmer
139.056
3143226MDLTHAN
Solar/Wind Harmer
0.325
970919AG2-571 GEN
Solar/Wind Harmer
10.793
315773AC2-141 GEN
Solar/Wind Harmer
10.96
970087AG2-069 GEN
Solar/Wind Harmer
23.933
944591AF1-124 GEN
Solar/Wind Harmer
66.754
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.052
3146456SLIGO L269
Solar/Wind Harmer
0.29
319010AE1-072 C
Solar/Wind Harmer
1.446
316093AE2-104_GEN
Solar/Wind Harmer
4.79
3146516WINFALL
Solar/Wind Harmer
0.919
3146516WINFALL
Solar/Wind Harmer
0.284
316072AD1-144
Solar/Wind Harmer
0.101
3143526WINTERP
Solar/Wind Harmer
1.468
957481AF2-042 GEN
Solar/Wind Harmer
74.732
3130156CHOWAN
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
1.107
316381AD1-082 GEN
Solar/Wind Harmer
0.276
315816AE2-034 GEN
Solar/Wind Harmer
1.16
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.754
315693AD1-088 GEN
Solar/Wind Harmer
12.912
316023GEN1_S
Solar/Wind Harmer
0.597
3151171GRAVELC
Adder
2.851
315737AD1-076 GEN
Solar/Wind Harmer
3.427
3146206CASHIE
Solar/Wind Harmer
0.265
971547AH1-271 GEN
Solar/Wind Harmer
5.651
3138126ROCKLANDING
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
1.055
3145893MURPHYS
Solar/Wind Harmer
1.173
961611AG1-000B GEN
Solar/Wind Harmer
13.781
3146173TUNIS
Solar/Wind Harmer
0.262
960081AF2-299 GEN
Solar/Wind Harmer
2.512
3156021HOLLOMANSOL
Solar/Wind Harmer
1.177
3145683EARLEYS
Solar/Wind Harmer
0.26
315607AA1-063A GEN
Solar/Wind Harmer
0.522
3146263WOODLND
Solar/Wind Harmer
0.259
3145963POPLR C
Solar/Wind Harmer
0.256
971317AH1-138 GEN
Solar/Wind Harmer
1.911
3145823KELFORD
Solar/Wind Harmer
0.255
3143336POWHATN
Solar/Wind Harmer
4.519
3145783HORNRTN
Solar/Wind Harmer
0.254
3145796HORNRTN
Solar/Wind Harmer
0.837
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Adder
2.295
971069AG2-661 GEN
Solar/Wind Harmer
4.468
3151031BRUNSWICKG2
50/50
4.168
3151101ELIZAR3
50/50
28.753
3151161SURRY 1
50/50
10.916
944011AF1-069 GEN
Solar/Wind Harmer
19.938
970917AG2-570 GEN
Solar/Wind Harmer
26.983
944581AF1-123 GEN
Solar/Wind Harmer
66.518
944601AF1-125 GEN
Solar/Wind Harmer
65.493
3144873MCLAUGH
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.155
3146456SLIGO L269
Solar/Wind Harmer
0.29
971153AH1-033 GEN
Solar/Wind Harmer
3.354
316246AF1-032 C
Solar/Wind Harmer
0.128
3144536CHRHLND
Solar/Wind Harmer
0.043
316321Z2-027
Solar/Wind Harmer
0.051
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3145273HOLLAND
Solar/Wind Harmer
0.209
3146376EDENTON
Solar/Wind Harmer
0.277
316303AF2-085
50/50
5.781
315244AE2-183_ST
50/50
9.183
963041AG1-153 GEN
50/50
8.438
3151081ELIZAR1
50/50
28.39
3151091ELIZAR2
50/50
27.897
941591AE2-156 GEN
50/50
25.918
315779AE2-040
50/50
4.045
972263AH1-716 GEN
50/50
164.827
970533AG2-339 GEN
Solar/Wind Harmer
25.033
970673AG2-436 GEN
Solar/Wind Harmer
40.723
971967AH1-528 GEN
Solar/Wind Harmer
50.609
970085AG2-068 GEN
Solar/Wind Harmer
15.955
970581AG2-369 GEN
Solar/Wind Harmer
13.722
316316AC1-027 C
Solar/Wind Harmer
0.278
957871AF2-081 GEN
Solar/Wind Harmer
14.474
3146406KITTY HAWK
Solar/Wind Harmer
0.036
315814AE2-033 C
Solar/Wind Harmer
22.84
313526AB2-022
Solar/Wind Harmer
0.153
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
3146486SUNBURY
Solar/Wind Harmer
0.286
3146486SUNBURY
Solar/Wind Harmer
0.286
316233AE1-074 FULL
Solar/Wind Harmer
0.226
971281AH1-106 GEN
Solar/Wind Harmer
3.918
971283AH1-107 GEN
Solar/Wind Harmer
3.918
316311AC2-079 GEN
Solar/Wind Harmer
8.039
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
19.444
3145336SMITFLD
Solar/Wind Harmer
0.111
970657AG2-426 GEN
Solar/Wind Harmer
6.123
3151171GRAVELC
Adder
3.748
315735AD1-075 GEN1
Solar/Wind Harmer
0.76
315813AE1-149 C
Solar/Wind Harmer
14.247
316478AD1-087 GEN
Solar/Wind Harmer
0.925
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.265
3144216WINCHST
Adder
0.998
3145893MURPHYS
Solar/Wind Harmer
0.442
3145893MURPHYS
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
6.632
961611AG1-000B GEN
Solar/Wind Harmer
7.007
3146173TUNIS
Solar/Wind Harmer
0.262
3146263WOODLND
Solar/Wind Harmer
0.259
316181AB2-040 GEN
Solar/Wind Harmer
0.368
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
316011AB1-132 GEN
Solar/Wind Harmer
4.67
3145963POPLR C
Solar/Wind Harmer
0.256
3145823KELFORD
Solar/Wind Harmer
0.255
3143336POWHATN
Solar/Wind Harmer
3.841
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Solar/Wind Harmer
0.152
315778AD1-151 GEN
Solar/Wind Harmer
20.108
316212AC1-099_GEN
Solar/Wind Harmer
1.277
316458AB2-190 GEN2
Solar/Wind Harmer
1.316
3145933PARMELE
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
8.364
3150861SPRUNCD
Adder
1.1
970133AG2-095 GEN
Solar/Wind Harmer
2.287
3146233WITAKRS
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.161
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
3138543CONSLDL
Solar/Wind Harmer
0.155
964241AG1-285 GEN
Solar/Wind Harmer
15.514
961601AG1-000A GEN
Solar/Wind Harmer
16.523
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.232
971623AH1-311 GEN
Solar/Wind Harmer
0.465
970257AG2-171 GEN
Solar/Wind Harmer
7.288
971775AH1-396 GEN
Solar/Wind Harmer
0.364
959311AF2-222 GEN
Solar/Wind Harmer
20.157
3142946ENON
Solar/Wind Harmer
0.074
3144293JTRSVLE
Adder
0.528
3147133PAMPLIN
Solar/Wind Harmer
0.687
3141873WAN 176
Solar/Wind Harmer
3.844
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
1.101
3143096IRON208
Adder
0.901
3143096IRON208
Adder
0.883
3141766HARMONY
Solar/Wind Harmer
2.864
3142433PROV 92
Adder
0.417
3142433PROV 92
Adder
0.417
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.123
3143316POE
Solar/Wind Harmer
1.084
970657AG2-426 GEN
Solar/Wind Harmer
2.004
3151201GRAVEL4
Adder
19.505
3151221GRAVEL6
Adder
19.482
3151191GRAVEL3
Adder
19.258
3151211GRAVEL5
Adder
19.258
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.522
315733AD1-074 GEN2
Solar/Wind Harmer
1.522
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3146206CASHIE
Solar/Wind Harmer
0.265
970601AG2-382 GEN
Solar/Wind Harmer
9.889
3145893MURPHYS
Solar/Wind Harmer
0.712
3145893MURPHYS
Solar/Wind Harmer
0.264
316463AE2-346 GEN
Solar/Wind Harmer
0.223
3145513AHOSKIE
Solar/Wind Harmer
0.546
3145513AHOSKIE
Solar/Wind Harmer
0.261
3146043SEABORD
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.52
3145683EARLEYS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.26
315652AC1-086 GEN
Solar/Wind Harmer
28.319
3137643SOCKMAN
Solar/Wind Harmer
1.026
316426AA2-053 GEN
Solar/Wind Harmer
0.857
315697AD1-025 GEN
Solar/Wind Harmer
0.274
316258AE1-075 C
Solar/Wind Harmer
0.19
3145796HORNRTN
Solar/Wind Harmer
0.812
3145796HORNRTN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
1.005
316159AE1-175 C
Solar/Wind Harmer
0.213
316210AC1-098 GEN
Solar/Wind Harmer
2.291
970831AG2-522 GEN
Solar/Wind Harmer
10.561
316274AC1-208 GEN
Solar/Wind Harmer
1.27
3145746EVERETS
Solar/Wind Harmer
0.963
316075AC2-137 C
Solar/Wind Harmer
0.054
316222AC1-221 GEN
Solar/Wind Harmer
0.822
316283AC2-100 C
Solar/Wind Harmer
0.389
971683AH1-343 GEN
Solar/Wind Harmer
7.173
970293AG2-193 GEN
Solar/Wind Harmer
2.062
316132AB2-190 GEN1
Solar/Wind Harmer
1.316
3146293MARTNCO
Solar/Wind Harmer
0.229
316129AC1-054 GEN
Solar/Wind Harmer
0.92
971065AG2-659 GEN
Solar/Wind Harmer
10.482
315671AE2-027_GEN
Solar/Wind Harmer
0.002
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3150851SPRUNCC
Adder
1.1
316494AC1-189 GEN
Solar/Wind Harmer
0.806
3146233WITAKRS
Solar/Wind Harmer
0.94
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.048
316131AB2-060 GEN
Solar/Wind Harmer
0.731
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.186
316359AB2-059 GEN
Solar/Wind Harmer
0.825
3142053HEARTS
Solar/Wind Harmer
0.409
315785AD2-033 C
Solar/Wind Harmer
1.852
316034AC1-036 C
Solar/Wind Harmer
0.015
970401AG2-262 GEN
Solar/Wind Harmer
1.325
970685AG2-442 GEN
Solar/Wind Harmer
16.639
944631AF1-128 GEN
Adder
106.053
971563AH1-280 GEN
Solar/Wind Harmer
2.358
3144293JTRSVLE
Adder
0.528
3144293JTRSVLE
Adder
0.417
3142543TWELFTH
Solar/Wind Harmer
0.021
315975AC1-164 GENB
Solar/Wind Harmer
0.068
971777AH1-397 GEN
Solar/Wind Harmer
0.569
3143096IRON208
Adder
0.901
3141766HARMONY
Solar/Wind Harmer
0.043
3142433PROV 92
Solar/Wind Harmer
0.859
3142433PROV 92
Adder
0.417
3142433PROV 92
Adder
0.417
3138133OCRAN
Solar/Wind Harmer
0.125
3146926FARMVIL
Solar/Wind Harmer
0.123
970937AG2-583 GEN
Solar/Wind Harmer
11.523
962861AG1-135 GEN
Solar/Wind Harmer
5.976
315242AE2-183_GT2
50/50
5.288
315241AE2-183_GT1
50/50
5.274
972185AH1-677 GEN
50/50
19.115
3151041BRUNSWICKG3
50/50
4.168
972187AH1-678 GEN
50/50
9.563
3150991CHESPKB
50/50
3.237
3150991CHESPKB
50/50
3.159
971223AH1-071 GEN
Solar/Wind Harmer
3.469
970933AG2-581 GEN
Solar/Wind Harmer
24.61
316294AC1-161 GEN
Solar/Wind Harmer
5.188
3145506HICKORY
Solar/Wind Harmer
1.167
3145506HICKORY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
0.175
316339AD2-160 GEN
Solar/Wind Harmer
0.466
316388AE2-253 GEN
Solar/Wind Harmer
0.906
3137176SLIGO L2192
Solar/Wind Harmer
1.155
3146456SLIGO L269
Solar/Wind Harmer
5.134
3130086AYDLETT
Solar/Wind Harmer
1.159
3144356SAPONY
Solar/Wind Harmer
2.424
316315AB2-025 C
Solar/Wind Harmer
0.232
3146386ELIZ CT
Solar/Wind Harmer
0.287
315835AF2-110_GEN
Solar/Wind Harmer
1.954
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3143526WINTERP
Solar/Wind Harmer
1.468
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
970099AG2-077 GEN
Solar/Wind Harmer
29.893
316349AD2-085 GEN
Solar/Wind Harmer
0.187
3146376EDENTON
Solar/Wind Harmer
1.232
3146376EDENTON
Solar/Wind Harmer
1.232
315742AE1-103 GEN
Solar/Wind Harmer
4.13
315614AA2-178 GEN
Solar/Wind Harmer
1.547
316365GEN2_N
Solar/Wind Harmer
0.597
316065AD1-022 GEN
Solar/Wind Harmer
12.234
3145893MURPHYS
Solar/Wind Harmer
1.766
3145893MURPHYS
Solar/Wind Harmer
0.475
3146173TUNIS
Solar/Wind Harmer
0.262
3146173TUNIS
Solar/Wind Harmer
0.262
316140AB2-099
Solar/Wind Harmer
0.093
313506AB2-031 GEN
Solar/Wind Harmer
0.793
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
962571AG1-106 GEN
Solar/Wind Harmer
3.663
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.318
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316313AB2-026
Solar/Wind Harmer
0.158
3145783HORNRTN
Solar/Wind Harmer
4.516
3145783HORNRTN
Solar/Wind Harmer
3.613
3145783HORNRTN
Solar/Wind Harmer
1.129
3145783HORNRTN
Solar/Wind Harmer
0.452
3145796HORNRTN
Solar/Wind Harmer
0.761
3145933PARMELE
Solar/Wind Harmer
0.493
3145933PARMELE
Solar/Wind Harmer
0.246
316005AA1-067
Solar/Wind Harmer
0.258
315724AD1-057 GEN
Solar/Wind Harmer
4.666
3145493TOT1
Solar/Wind Harmer
0.547
3145453TOT5
Solar/Wind Harmer
0.328
3145603CNETO
Solar/Wind Harmer
0.219
316336AC2-165 C
Solar/Wind Harmer
11.937
944641AF1-129 GEN
Adder
111.423
970301AG2-198 GEN
Solar/Wind Harmer
9.914
961601AG1-000A GEN
Solar/Wind Harmer
4.131
316049AB1-081 GEN
Solar/Wind Harmer
1.321
316263AC1-034 GEN
Solar/Wind Harmer
8.826
970323AG2-213 GEN
Solar/Wind Harmer
9.717
962561AG1-105 GEN
Solar/Wind Harmer
10.908
964791AG1-342 GEN
Solar/Wind Harmer
4.335
3146843MT LREL
Solar/Wind Harmer
0.226
3146843MT LREL
Solar/Wind Harmer
0.226
316118AC1-105 GEN
Solar/Wind Harmer
0.569
3142946ENON
Solar/Wind Harmer
0.022
958211AF2-115 GEN
Solar/Wind Harmer
2.653
3144293JTRSVLE
Adder
0.528
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
315976AC1-164 GENA
Solar/Wind Harmer
2.291
316169AC1-164_GENC
Solar/Wind Harmer
1.979
316156AD2-030 GEN
Solar/Wind Harmer
0.158
3150691DARBY 3
Adder
13.39
3150701DARBY 4
Adder
13.359
3150681DARBY 2
Adder
13.343
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3138283WHITEMARSH
Solar/Wind Harmer
0.056
316327AA2-057 GEN
Solar/Wind Harmer
0.355
971285AH1-108 GEN
Adder
1.8
957861AF2-080 GEN
Solar/Wind Harmer
10.29
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
3144303KENBRDG
Solar/Wind Harmer
0.182
970683AG2-441 GEN
Solar/Wind Harmer
13.519
970681AG2-440 GEN
Solar/Wind Harmer
8.973
946301AF1-294 GEN
Solar/Wind Harmer
4.363
961791AG1-021 GEN
Solar/Wind Harmer
2.122
3147173SINAI
Solar/Wind Harmer
0.219
3147243WELCO
Solar/Wind Harmer
0.137
3141873WAN 176
Solar/Wind Harmer
0.043
970189AG2-124 GEN
Solar/Wind Harmer
6.385
3142433PROV 92
Adder
0.417
3142433PROV 92
Adder
0.417
3143873LANEXA
Solar/Wind Harmer
0.129
3141913WHIT STONE
Solar/Wind Harmer
0.209
3138133OCRAN
Solar/Wind Harmer
0.062
3141783LANCAST
Solar/Wind Harmer
0.122
3141783LANCAST
Solar/Wind Harmer
0.082
971845AH1-439 GEN
Solar/Wind Harmer
8.224
3141813NORNECK
Solar/Wind Harmer
0.172
972205AH1-687 GEN
Adder
6.299
316164AC1-076 GEN
Solar/Wind Helper
1.144
3146776BUCKING
Solar/Wind Harmer
0.065
3150351NORNECKC2
Adder
1.742
316123AC1-075 GEN
Solar/Wind Harmer
0.223
3142416OLDCHRC
Solar/Wind Harmer
1.548
972003AH1-546 GEN
Solar/Wind Harmer
5.242
316223AC1-118
Solar/Wind Harmer
0.094
3141906WESTMOR
Solar/Wind Harmer
0.053
970221AG2-151 GEN
Solar/Wind Harmer
7.035
316473AC1-191 GEN
Solar/Wind Harmer
0.411
270494AE1-108_GEN
Solar/Wind Harmer
1.393
3147666LOUISA
Solar/Wind Helper
0.597
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.112
3146776BUCKING
Solar/Wind Harmer
0.072
3141726DUNNSVL
Solar/Wind Harmer
0.705
3150351NORNECKC2
Adder
1.714
3142416OLDCHRC
Solar/Wind Harmer
0.415
3142416OLDCHRC
Solar/Wind Harmer
0.159
316337AD2-073 GEN
Solar/Wind Harmer
0.131
971377AH1-170 GEN
Solar/Wind Harmer
1.407
3147623JAMES R
Solar/Wind Harmer
0.306
970223AG2-152 GEN
Solar/Wind Harmer
8.971
316447AC1-158 HLD
Solar/Wind Helper
3.807
316044AC1-158 PL1
Solar/Wind Helper
1.73
3147666LOUISA
Solar/Wind Helper
1.038
316192AB2-158 GEN
Solar/Wind Helper
1.716
3150671DARBY 1
Adder
13.328
3142366NRTHEST
Adder
0.595
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
3150341NORNECKC1
Adder
1.8
3150341NORNECKC1
Adder
1.786
316312AB1-027
Solar/Wind Harmer
0.284
942751AE2-291 GEN
Solar/Wind Harmer
8.407
3142296MT RD221
Adder
0.414
966871AG1-558 GEN
Solar/Wind Harmer
0.141
316045AC1-158 PL2
Solar/Wind Helper
5.537
316450AC1-158 RIC
Solar/Wind Helper
0.461
LAGNLTFEXP_LAGN->PJM
CLTF
10.159
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.539
TVALTFEXP_TVA->PJM
CLTF
5.085
CPLELTFEXP_CPLE->PJM
CLTF
15.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.739
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.619
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.321
MECLTFEXP_MEC->PJM
CLTF
4.72
SIGELTFEXP_SIGE->PJM
CLTF
0.141
NYPJM->LTFIMP_NY
CLTF
2.76
LGEELTFEXP_LGEE->PJM
CLTF
1.69
WECLTFEXP_WEC->PJM
CLTF
0.859

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2090-256_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2090-256_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.71 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4046.64
MW Contribution:
1.87
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.621
315244AE2-183_ST
50/50
8.091
963041AG1-153 GEN
50/50
7.436
315779AE2-040
50/50
3.549
3151541CLOVER2
50/50
5.035
970533AG2-339 GEN
Solar/Wind Harmer
22.05
970673AG2-436 GEN
Solar/Wind Harmer
70.852
971967AH1-528 GEN
Solar/Wind Harmer
58.92
316233AE1-074 FULL
Solar/Wind Harmer
0.825
971281AH1-106 GEN
Solar/Wind Harmer
4.982
971283AH1-107 GEN
Solar/Wind Harmer
4.982
970085AG2-068 GEN
Solar/Wind Harmer
18.512
970581AG2-369 GEN
Solar/Wind Harmer
15.92
315814AE2-033 C
Solar/Wind Harmer
26.491
316258AE1-075 C
Solar/Wind Harmer
0.672
316405AF2-144 C
Solar/Wind Harmer
0.709
3143316POE
Solar/Wind Harmer
-0.107
316486AD2-202 GEN
Solar/Wind Harmer
0.672
316316AC1-027 C
Solar/Wind Harmer
0.794
3151081ELIZAR1
Adder
21.14
3151091ELIZAR2
Adder
20.773
316018AA1-139 ULT2
Solar/Wind Harmer
2.213
957871AF2-081 GEN
Solar/Wind Harmer
12.948
3146406KITTY HAWK
Solar/Wind Harmer
0.021
970657AG2-426 GEN
Solar/Wind Harmer
1.628
315833AF1-017_GEN
Solar/Wind Harmer
4.893
316311AC2-079 GEN
Solar/Wind Harmer
12.997
313526AB2-022
Solar/Wind Harmer
0.692
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146396TANGLEW
Solar/Wind Harmer
0.472
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
946281AF1-292 GEN
Solar/Wind Harmer
0.57
971285AH1-108 GEN
Adder
1.699
315839AE2-212 C
Solar/Wind Harmer
0.761
315800Z1-036_GEN1
Solar/Wind Harmer
6.235
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
27.901
316236AE1-162_GEN
Solar/Wind Harmer
0.746
3137643SOCKMAN
Solar/Wind Harmer
-0.099
316318V4-068
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
-0.066
3145893MURPHYS
Solar/Wind Harmer
-0.025
971445AH1-216 GEN
Solar/Wind Harmer
15.306
3146043SEABORD
Solar/Wind Harmer
-0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
4.973
315733AD1-074 GEN2
Solar/Wind Harmer
4.973
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.744
316426AA2-053 GEN
Solar/Wind Harmer
2.471
316463AE2-346 GEN
Solar/Wind Harmer
0.395
3145513AHOSKIE
Solar/Wind Harmer
0.214
961941AG1-037 GEN
Solar/Wind Harmer
0.184
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.048
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
12.079
3151201GRAVEL4
Adder
15.627
3151221GRAVEL6
Adder
15.609
3151191GRAVEL3
Adder
15.429
3151211GRAVEL5
Adder
15.429
3146033SCOT NK
Solar/Wind Harmer
-0.095
316174AB2-169 GEN
Solar/Wind Harmer
3.661
316210AC1-098 GEN
Solar/Wind Harmer
3.71
316274AC1-208 GEN
Solar/Wind Harmer
2.545
315697AD1-025 GEN
Solar/Wind Harmer
4.751
316238AB2-078_GEN
Solar/Wind Harmer
0.703
316239AB2-077_GEN
Solar/Wind Harmer
0.703
316327AA2-057 GEN
Solar/Wind Harmer
2.327
3145746EVERETS
Solar/Wind Harmer
-0.091
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.975
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
970683AG2-441 GEN
Solar/Wind Harmer
15.945
970681AG2-440 GEN
Solar/Wind Harmer
10.583
946301AF1-294 GEN
Solar/Wind Harmer
5.723
961791AG1-021 GEN
Solar/Wind Harmer
2.792
3147173SINAI
Solar/Wind Harmer
-0.022
3147243WELCO
Solar/Wind Harmer
-0.014
316382AG1-145 C
Solar/Wind Harmer
0.619
316159AE1-175 C
Solar/Wind Harmer
0.551
957831AF2-077 GEN
Solar/Wind Harmer
0.607
3138283WHITEMARSH
Solar/Wind Harmer
0.031
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
971845AH1-439 GEN
Solar/Wind Harmer
10.113
316322AB2-045
Solar/Wind Harmer
0.632
3143873LANEXA
Solar/Wind Harmer
-0.011
957601AF2-054 GEN
Solar/Wind Harmer
0.54
3141873WAN 176
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.402
3141913WHIT STONE
Solar/Wind Harmer
-0.017
3138133OCRAN
Solar/Wind Harmer
-0.005
270455AD2-022 GEN
Solar/Wind Harmer
3.041
270457AD2-023 GEN
Solar/Wind Harmer
1.542
3141783LANCAST
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
Adder
6.102
316164AC1-076 GEN
Solar/Wind Helper
1.091
3151031BRUNSWICKG2
50/50
3.673
970413AG2-270 GEN
50/50
22.094
3151101ELIZAR3
50/50
22.719
944011AF1-069 GEN
Solar/Wind Harmer
19.264
970917AG2-570 GEN
Solar/Wind Harmer
75.138
3143336POWHATN
Solar/Wind Harmer
2.799
316478AD1-087 GEN
Solar/Wind Harmer
2.294
944581AF1-123 GEN
Solar/Wind Harmer
119.016
944601AF1-125 GEN
Solar/Wind Harmer
117.158
3142956BIRDNECK
Solar/Wind Harmer
1.391
316017AA1-139 ULT1
Solar/Wind Harmer
2.09
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
2.993
315813AE1-149 C
Solar/Wind Harmer
16.161
970657AG2-426 GEN
Solar/Wind Harmer
5.215
316305AF2-043 C
Solar/Wind Harmer
0.776
316246AF1-032 C
Solar/Wind Harmer
0.52
316320Y1-086
Solar/Wind Harmer
1.506
316321Z2-027
Solar/Wind Harmer
0.69
3144536CHRHLND
Solar/Wind Harmer
-0.004
3146516WINFALL
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
966621AG1-532 GEN
Solar/Wind Harmer
0.517
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3150861SPRUNCD
Adder
1.039
3146376EDENTON
Solar/Wind Harmer
-0.025
316181AB2-040 GEN
Solar/Wind Harmer
3.487
3156081AA2-088 GEN
Solar/Wind Harmer
8.089
3147043LAWRENC
Solar/Wind Harmer
-0.015
316011AB1-132 GEN
Solar/Wind Harmer
5.18
3145336SMITFLD
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.173
3145893MURPHYS
Solar/Wind Harmer
-0.025
315735AD1-075 GEN1
Solar/Wind Harmer
2.485
3146173TUNIS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.301
3145796HORNRTN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
316317KELFORD C
Solar/Wind Harmer
1.118
3145823KELFORD
Solar/Wind Harmer
-0.024
3151171GRAVELC
Adder
3.003
3145963POPLR C
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
5.032
316212AC1-099_GEN
Solar/Wind Harmer
2.061
315778AD1-151 GEN
Solar/Wind Harmer
20.827
315722AD1-056 GEN
Solar/Wind Harmer
8.313
3145933PARMELE
Solar/Wind Harmer
-0.023
964241AG1-285 GEN
Solar/Wind Harmer
18.135
316458AB2-190 GEN2
Solar/Wind Harmer
2.34
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
970257AG2-171 GEN
Solar/Wind Harmer
8.564
971775AH1-396 GEN
Solar/Wind Harmer
1.611
970133AG2-095 GEN
Solar/Wind Harmer
2.569
3146233WITAKRS
Solar/Wind Harmer
0.477
3146233WITAKRS
Solar/Wind Harmer
-0.015
959311AF2-222 GEN
Solar/Wind Harmer
23.758
3138543CONSLDL
Solar/Wind Harmer
-0.015
316420AA1-050 GEN
Solar/Wind Harmer
2.588
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
961601AG1-000A GEN
Solar/Wind Harmer
8.941
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3144216WINCHST
Adder
0.753
3144293JTRSVLE
Adder
0.475
3147133PAMPLIN
Solar/Wind Harmer
-0.069
3150921YORKTN3
Adder
4.957
942461AE2-259 GEN
Solar/Wind Harmer
3.259
3143096IRON208
Adder
0.799
3143096IRON208
Adder
0.783
3146926FARMVIL
Solar/Wind Harmer
-0.013
316003AC1-222 GEN
Solar/Wind Harmer
2.02
3142946ENON
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
2.002
316283AC2-100 C
Solar/Wind Harmer
1.859
971683AH1-343 GEN
Solar/Wind Harmer
8.419
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3146776BUCKING
Solar/Wind Harmer
-0.007
970293AG2-193 GEN
Solar/Wind Harmer
2.311
316203AE2-005 GEN
Solar/Wind Harmer
7.639
315242AE2-183_GT2
50/50
4.659
315241AE2-183_GT1
50/50
4.647
972185AH1-677 GEN
50/50
16.842
3151041BRUNSWICKG3
50/50
3.673
972187AH1-678 GEN
50/50
8.427
971223AH1-071 GEN
Solar/Wind Harmer
4.44
3143526WINTERP
Solar/Wind Harmer
-0.159
970933AG2-581 GEN
Solar/Wind Harmer
28.6
3144356SAPONY
Solar/Wind Harmer
0.997
316315AB2-025 C
Solar/Wind Harmer
0.769
970099AG2-077 GEN
Solar/Wind Harmer
34.835
316313AB2-026
Solar/Wind Harmer
0.746
316365GEN2_N
Solar/Wind Harmer
1.756
316294AC1-161 GEN
Solar/Wind Harmer
8.408
316185AD1-033 GEN
Solar/Wind Harmer
2.734
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.742
316388AE2-253 GEN
Solar/Wind Harmer
1.742
3150991CHESPKB
Adder
2.412
3150991CHESPKB
Adder
2.354
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.055
3130086AYDLETT
Solar/Wind Harmer
-0.103
316083AB2-161 GEN
Solar/Wind Harmer
4.188
316349AD2-085 GEN
Solar/Wind Harmer
2.288
315835AF2-110_GEN
Solar/Wind Harmer
3.217
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316336AC2-165 C
Solar/Wind Harmer
16.052
316431W1029_GEN1
Solar/Wind Harmer
4.63
316433W1029_GEN2
Solar/Wind Harmer
4.63
316435W1029_GEN3
Solar/Wind Harmer
4.63
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
6.023
3146376EDENTON
Solar/Wind Harmer
0.747
3146376EDENTON
Solar/Wind Harmer
0.747
313506AB2-031 GEN
Solar/Wind Harmer
2.007
315614AA2-178 GEN
Solar/Wind Harmer
2.679
315687AD1-152 GEN
Solar/Wind Harmer
2.984
962571AG1-106 GEN
Solar/Wind Harmer
3.565
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145893MURPHYS
Solar/Wind Harmer
0.69
3145893MURPHYS
Solar/Wind Harmer
-0.044
316065AD1-022 GEN
Solar/Wind Harmer
12.294
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
0.204
316140AB2-099
Solar/Wind Harmer
0.165
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145783HORNRTN
Solar/Wind Harmer
2.897
3145783HORNRTN
Solar/Wind Harmer
2.318
3145783HORNRTN
Solar/Wind Harmer
0.724
3145783HORNRTN
Solar/Wind Harmer
0.29
316240AF1-291 C
Solar/Wind Harmer
0.725
944641AF1-129 GEN
Adder
100.579
970301AG2-198 GEN
Solar/Wind Harmer
11.779
316033AB2-134 GEN
Solar/Wind Harmer
7.58
313527AB2-043 GEN
Solar/Wind Harmer
3.802
316237AB2-079_GEN
Solar/Wind Harmer
0.703
315724AD1-057 GEN
Solar/Wind Harmer
4.572
3145933PARMELE
Solar/Wind Harmer
-0.046
3145933PARMELE
Solar/Wind Harmer
-0.023
316005AA1-067
Solar/Wind Harmer
0.464
970323AG2-213 GEN
Solar/Wind Harmer
11.418
3145493TOT1
Solar/Wind Harmer
0.35
3145453TOT5
Solar/Wind Harmer
0.21
3145603CNETO
Solar/Wind Harmer
0.14
962561AG1-105 GEN
Solar/Wind Harmer
12.727
964791AG1-342 GEN
Solar/Wind Harmer
4.803
3146843MT LREL
Solar/Wind Harmer
-0.022
3146843MT LREL
Solar/Wind Harmer
-0.022
961601AG1-000A GEN
Solar/Wind Harmer
8.829
316049AB1-081 GEN
Solar/Wind Harmer
2.416
316263AC1-034 GEN
Solar/Wind Harmer
10.527
958211AF2-115 GEN
Solar/Wind Harmer
3.49
3144293JTRSVLE
Adder
0.475
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
316118AC1-105 GEN
Solar/Wind Harmer
1.519
316248AF1-058 C
Solar/Wind Harmer
0.656
3142946ENON
Solar/Wind Harmer
-0.002
3142366NRTHEST
Adder
0.564
3150691DARBY 3
Adder
12.208
3150701DARBY 4
Adder
12.179
3150681DARBY 2
Adder
12.165
3150671DARBY 1
Adder
12.151
3146776BUCKING
Solar/Wind Harmer
-0.075
3146776BUCKING
Solar/Wind Harmer
-0.006
316441AF1-014 GEN
Solar/Wind Harmer
1.221
315666AE1-190 GEN
Solar/Wind Harmer
0.544
316156AD2-030 GEN
Solar/Wind Harmer
0.48
315976AC1-164 GENA
Solar/Wind Harmer
4.047
316169AC1-164_GENC
Solar/Wind Harmer
3.497
316312AB1-027
Solar/Wind Harmer
0.554
3142296MT RD221
Adder
0.461
972189AH1-679 GEN
Adder
2.24
3150341NORNECKC1
Adder
1.317
3150341NORNECKC1
Adder
1.306
316045AC1-158 PL2
Solar/Wind Helper
5.384
316450AC1-158 RIC
Solar/Wind Helper
0.449
3141843SHACKLE
Adder
0.824
3141873WAN 176
Solar/Wind Harmer
2.141
316075AC2-137 C
Solar/Wind Harmer
0.481
3141766HARMONY
Solar/Wind Harmer
1.586
316123AC1-075 GEN
Solar/Wind Harmer
1.818
3142416OLDCHRC
Solar/Wind Harmer
1.663
3150351NORNECKC2
Adder
1.274
3147666LOUISA
Solar/Wind Helper
0.577
972003AH1-546 GEN
Solar/Wind Harmer
1.874
970119AG2-088 GEN
50/50
42.156
315243AE2-183_GT3
50/50
4.659
3151051BRUNSWICKS1
50/50
7.625
3151021BRUNSWICKG1
50/50
3.673
971451AH1-221 GEN
50/50
11.153
3151531CLOVER1
50/50
5.073
3143226MDLTHAN
Solar/Wind Harmer
-0.035
941031AE2-094 GEN
Solar/Wind Harmer
61.481
940641AE2-051 GEN
Solar/Wind Harmer
30.607
939411AE1-173 GEN
Solar/Wind Harmer
154.923
3143526WINTERP
Solar/Wind Harmer
-0.159
970919AG2-571 GEN
Solar/Wind Harmer
9.511
970087AG2-069 GEN
Solar/Wind Harmer
27.768
957481AF2-042 GEN
Solar/Wind Harmer
87.087
3143336POWHATN
Solar/Wind Harmer
3.293
315693AD1-088 GEN
Solar/Wind Harmer
13.416
944591AF1-124 GEN
Solar/Wind Harmer
119.444
316023GEN1_S
Solar/Wind Harmer
1.756
315773AC2-141 GEN
Solar/Wind Harmer
10.879
316375AC2-012 GEN
Solar/Wind Harmer
8.946
316036AC1-147 C
Solar/Wind Harmer
0.696
3150981CHESPKA
Adder
2.875
3146456SLIGO L269
Solar/Wind Harmer
-0.026
319010AE1-072 C
Solar/Wind Harmer
5.218
316381AD1-082 GEN
Solar/Wind Harmer
2.362
316093AE2-104_GEN
Solar/Wind Harmer
7.483
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
960081AF2-299 GEN
Solar/Wind Harmer
2.865
3150851SPRUNCC
Adder
1.039
315611Z1-036_GEN2
Solar/Wind Harmer
6.235
316072AD1-144
Solar/Wind Harmer
0.509
3130156CHOWAN
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.584
315816AE2-034 GEN
Solar/Wind Harmer
2.009
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.341
3147043LAWRENC
Adder
2.001
3145336SMITFLD
Solar/Wind Harmer
-0.099
3145893MURPHYS
Solar/Wind Harmer
-0.098
3145893MURPHYS
Solar/Wind Harmer
0.734
315607AA1-063A GEN
Solar/Wind Harmer
2.488
315737AD1-076 GEN
Solar/Wind Harmer
4.675
3146173TUNIS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.139
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.284
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
315671AE2-027_GEN
Solar/Wind Harmer
4.391
3145823KELFORD
Solar/Wind Harmer
-0.024
3151171GRAVELC
Adder
2.284
316129AC1-054 GEN
Solar/Wind Harmer
2.107
971065AG2-659 GEN
Solar/Wind Harmer
12.033
3145963POPLR C
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
11.793
316369SG1_INVT
Solar/Wind Harmer
4.198
971069AG2-661 GEN
Solar/Wind Harmer
3.703
316131AB2-060 GEN
Solar/Wind Harmer
2.515
3146293MARTNCO
Solar/Wind Harmer
0.144
316132AB2-190 GEN1
Solar/Wind Harmer
2.34
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
315785AD2-033 C
Solar/Wind Harmer
5.19
316034AC1-036 C
Solar/Wind Harmer
0.422
316494AC1-189 GEN
Solar/Wind Harmer
2.453
316319Z2-044 C
Solar/Wind Harmer
1.258
3146233WITAKRS
Solar/Wind Harmer
-0.09
3142543TWELFTH
Solar/Wind Harmer
-0.002
961671AG1-007 GEN
Solar/Wind Harmer
0.286
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.672
970401AG2-262 GEN
Solar/Wind Harmer
1.468
970685AG2-442 GEN
Solar/Wind Harmer
19.657
316359AB2-059 GEN
Solar/Wind Harmer
3.02
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3142053HEARTS
Solar/Wind Harmer
0.264
971563AH1-280 GEN
Solar/Wind Harmer
2.792
3144293JTRSVLE
Adder
0.475
3144293JTRSVLE
Adder
0.375
3138126ROCKLANDING
Solar/Wind Harmer
0.068
3143096IRON208
Adder
0.799
971317AH1-138 GEN
Solar/Wind Harmer
2.656
3146926FARMVIL
Solar/Wind Harmer
-0.013
944631AF1-128 GEN
Adder
87.974
970937AG2-583 GEN
Solar/Wind Harmer
14.719
3142433PROV 92
Solar/Wind Harmer
-0.076
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3146776BUCKING
Solar/Wind Harmer
-0.007
971777AH1-397 GEN
Solar/Wind Harmer
2.115
315662AE1-191 GEN
Solar/Wind Harmer
2.175
316280AD1-041 GEN
Solar/Wind Harmer
1.359
3141766HARMONY
Solar/Wind Harmer
-0.004
315975AC1-164 GENB
Solar/Wind Harmer
0.12
316314AB2-024 C
Solar/Wind Harmer
1.511
3138133OCRAN
Solar/Wind Harmer
-0.01
3142416OLDCHRC
Solar/Wind Harmer
-0.043
3142416OLDCHRC
Solar/Wind Harmer
-0.016
3150351NORNECKC2
Adder
1.253
316447AC1-158 HLD
Solar/Wind Helper
3.702
316044AC1-158 PL1
Solar/Wind Helper
1.682
3147666LOUISA
Solar/Wind Helper
1.004
316192AB2-158 GEN
Solar/Wind Helper
1.657
LAGNLTFEXP_LAGN->PJM
CLTF
9.27
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.925
TVALTFEXP_TVA->PJM
CLTF
4.648
CPLELTFEXP_CPLE->PJM
CLTF
13.377
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.631
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.332
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.892
MECLTFEXP_MEC->PJM
CLTF
4.428
SIGELTFEXP_SIGE->PJM
CLTF
0.133
NYPJM->LTFIMP_NY
CLTF
2.517
LGEELTFEXP_LGEE->PJM
CLTF
1.607
WECLTFEXP_WEC->PJM
CLTF
0.817

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2054-2135_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2054-2135_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.49 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4038.23
MW Contribution:
7.6
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
40.898
315243AE2-183_GT3
50/50
4.564
3151051BRUNSWICKS1
50/50
7.473
3151021BRUNSWICKG1
50/50
3.6
971451AH1-221 GEN
50/50
10.931
3151531CLOVER1
50/50
5.033
3143226MDLTHAN
Solar/Wind Harmer
-0.034
941031AE2-094 GEN
Solar/Wind Harmer
60.159
940641AE2-051 GEN
Solar/Wind Harmer
29.85
939411AE1-173 GEN
Solar/Wind Harmer
150.717
970919AG2-571 GEN
Solar/Wind Harmer
9.329
3143526WINTERP
Solar/Wind Harmer
-0.152
970087AG2-069 GEN
Solar/Wind Harmer
27.242
3143336POWHATN
Solar/Wind Harmer
3.331
957481AF2-042 GEN
Solar/Wind Harmer
86.229
315693AD1-088 GEN
Solar/Wind Harmer
13.37
316023GEN1_S
Solar/Wind Harmer
1.708
944591AF1-124 GEN
Solar/Wind Harmer
115.141
315773AC2-141 GEN
Solar/Wind Harmer
10.491
3146456SLIGO L269
Solar/Wind Harmer
-0.025
319010AE1-072 C
Solar/Wind Harmer
5.031
316375AC2-012 GEN
Solar/Wind Harmer
8.61
316036AC1-147 C
Solar/Wind Harmer
0.67
3150981CHESPKA
Adder
2.767
960081AF2-299 GEN
Solar/Wind Harmer
2.8
316093AE2-104_GEN
Solar/Wind Harmer
7.207
316381AD1-082 GEN
Solar/Wind Harmer
2.255
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.503
3147043LAWRENC
Adder
1.969
315611Z1-036_GEN2
Solar/Wind Harmer
6.028
3130156CHOWAN
Solar/Wind Harmer
-0.024
316072AD1-144
Solar/Wind Harmer
0.489
315816AE2-034 GEN
Solar/Wind Harmer
1.946
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.609
315607AA1-063A GEN
Solar/Wind Harmer
2.426
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.714
3146173TUNIS
Solar/Wind Harmer
-0.024
315737AD1-076 GEN
Solar/Wind Harmer
4.534
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.96
3146263WOODLND
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.081
971065AG2-659 GEN
Solar/Wind Harmer
11.895
3145683EARLEYS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.191
3145336SMITFLD
Solar/Wind Harmer
-0.094
3150851SPRUNCC
Adder
0.971
3145823KELFORD
Solar/Wind Harmer
-0.023
316131AB2-060 GEN
Solar/Wind Harmer
2.521
3145963POPLR C
Solar/Wind Harmer
-0.023
315785AD2-033 C
Solar/Wind Harmer
5.251
316034AC1-036 C
Solar/Wind Harmer
0.428
970685AG2-442 GEN
Solar/Wind Harmer
20.099
3151171GRAVELC
Adder
2.172
971563AH1-280 GEN
Solar/Wind Harmer
2.863
3144293JTRSVLE
Adder
0.487
3144293JTRSVLE
Adder
0.384
315671AE2-027_GEN
Solar/Wind Harmer
4.121
3146293MARTNCO
Solar/Wind Harmer
0.14
961611AG1-000B GEN
Solar/Wind Harmer
11.183
970401AG2-262 GEN
Solar/Wind Harmer
1.466
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316319Z2-044 C
Solar/Wind Harmer
1.233
3146233WITAKRS
Solar/Wind Harmer
-0.088
3146926FARMVIL
Solar/Wind Harmer
-0.013
316494AC1-189 GEN
Solar/Wind Harmer
2.399
316303AF2-085
50/50
5.453
315244AE2-183_ST
50/50
7.926
963041AG1-153 GEN
50/50
7.288
315779AE2-040
50/50
3.433
3151541CLOVER2
50/50
4.995
970533AG2-339 GEN
Solar/Wind Harmer
21.576
970673AG2-436 GEN
Solar/Wind Harmer
69.359
971967AH1-528 GEN
Solar/Wind Harmer
57.822
316233AE1-074 FULL
Solar/Wind Harmer
0.788
971281AH1-106 GEN
Solar/Wind Harmer
4.761
971283AH1-107 GEN
Solar/Wind Harmer
4.761
970085AG2-068 GEN
Solar/Wind Harmer
18.161
970581AG2-369 GEN
Solar/Wind Harmer
15.619
316258AE1-075 C
Solar/Wind Harmer
0.68
316405AF2-144 C
Solar/Wind Harmer
0.717
315814AE2-033 C
Solar/Wind Harmer
25.632
316486AD2-202 GEN
Solar/Wind Harmer
0.666
3143316POE
Solar/Wind Harmer
-0.102
316316AC1-027 C
Solar/Wind Harmer
0.765
316018AA1-139 ULT2
Solar/Wind Harmer
2.133
957871AF2-081 GEN
Solar/Wind Harmer
12.481
3151081ELIZAR1
Adder
20.351
3151091ELIZAR2
Adder
19.997
3146406KITTY HAWK
Solar/Wind Harmer
0.021
946281AF1-292 GEN
Solar/Wind Harmer
0.557
313526AB2-022
Solar/Wind Harmer
0.667
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146396TANGLEW
Solar/Wind Harmer
0.455
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.476
315833AF1-017_GEN
Solar/Wind Harmer
4.697
970657AG2-426 GEN
Solar/Wind Harmer
1.555
315800Z1-036_GEN1
Solar/Wind Harmer
6.028
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
3137643SOCKMAN
Solar/Wind Harmer
-0.096
315652AC1-086 GEN
Solar/Wind Harmer
27.196
3146043SEABORD
Solar/Wind Harmer
-0.024
316318V4-068
Solar/Wind Harmer
0.599
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
316426AA2-053 GEN
Solar/Wind Harmer
2.414
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.823
315733AD1-074 GEN2
Solar/Wind Harmer
4.823
315839AE2-212 C
Solar/Wind Harmer
0.718
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.43
970831AG2-522 GEN
Solar/Wind Harmer
11.916
316463AE2-346 GEN
Solar/Wind Harmer
0.385
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
316236AE1-162_GEN
Solar/Wind Harmer
0.713
971285AH1-108 GEN
Adder
1.589
971445AH1-216 GEN
Solar/Wind Harmer
14.621
316238AB2-078_GEN
Solar/Wind Harmer
0.704
316239AB2-077_GEN
Solar/Wind Harmer
0.704
3146033SCOT NK
Solar/Wind Harmer
-0.093
3144303KENBRDG
Solar/Wind Harmer
-0.019
316210AC1-098 GEN
Solar/Wind Harmer
3.626
316174AB2-169 GEN
Solar/Wind Harmer
3.563
316274AC1-208 GEN
Solar/Wind Harmer
2.489
970683AG2-441 GEN
Solar/Wind Harmer
16.263
970681AG2-440 GEN
Solar/Wind Harmer
10.794
3151201GRAVEL4
Adder
14.863
3151221GRAVEL6
Adder
14.846
3151191GRAVEL3
Adder
14.675
3151211GRAVEL5
Adder
14.675
946301AF1-294 GEN
Solar/Wind Harmer
5.869
961791AG1-021 GEN
Solar/Wind Harmer
2.863
316327AA2-057 GEN
Solar/Wind Harmer
2.278
3145746EVERETS
Solar/Wind Harmer
-0.089
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
957861AF2-080 GEN
Solar/Wind Harmer
9.754
315697AD1-025 GEN
Solar/Wind Harmer
4.483
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
3147173SINAI
Solar/Wind Harmer
-0.022
3147243WELCO
Solar/Wind Harmer
-0.013
971845AH1-439 GEN
Solar/Wind Harmer
11.003
316322AB2-045
Solar/Wind Harmer
0.69
316382AG1-145 C
Solar/Wind Harmer
0.581
316159AE1-175 C
Solar/Wind Harmer
0.517
957831AF2-077 GEN
Solar/Wind Harmer
0.57
3138283WHITEMARSH
Solar/Wind Harmer
0.029
972205AH1-687 GEN
Adder
7.017
315242AE2-183_GT2
50/50
4.564
315241AE2-183_GT1
50/50
4.552
972185AH1-677 GEN
50/50
16.499
3151041BRUNSWICKG3
50/50
3.6
972187AH1-678 GEN
50/50
8.259
971223AH1-071 GEN
Solar/Wind Harmer
4.308
970933AG2-581 GEN
Solar/Wind Harmer
28.126
3143526WINTERP
Solar/Wind Harmer
-0.152
316313AB2-026
Solar/Wind Harmer
0.755
3144356SAPONY
Solar/Wind Harmer
0.964
316315AB2-025 C
Solar/Wind Harmer
0.744
970099AG2-077 GEN
Solar/Wind Harmer
34.492
316336AC2-165 C
Solar/Wind Harmer
16.481
316365GEN2_N
Solar/Wind Harmer
1.708
316294AC1-161 GEN
Solar/Wind Harmer
8.108
316185AD1-033 GEN
Solar/Wind Harmer
2.634
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.679
316388AE2-253 GEN
Solar/Wind Harmer
1.679
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.945
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.321
3150991CHESPKB
Adder
2.265
3146386ELIZ CT
Solar/Wind Harmer
-0.025
315835AF2-110_GEN
Solar/Wind Harmer
3.098
316349AD2-085 GEN
Solar/Wind Harmer
2.196
316431W1029_GEN1
Solar/Wind Harmer
4.469
316433W1029_GEN2
Solar/Wind Harmer
4.469
316435W1029_GEN3
Solar/Wind Harmer
4.469
316083AB2-161 GEN
Solar/Wind Harmer
3.998
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
315687AD1-152 GEN
Solar/Wind Harmer
2.963
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
5.823
313506AB2-031 GEN
Solar/Wind Harmer
1.962
3146376EDENTON
Solar/Wind Harmer
0.722
3146376EDENTON
Solar/Wind Harmer
0.722
970301AG2-198 GEN
Solar/Wind Harmer
12.093
962571AG1-106 GEN
Solar/Wind Harmer
3.475
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.595
3145893MURPHYS
Solar/Wind Harmer
0.671
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
0.199
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
2.833
3145783HORNRTN
Solar/Wind Harmer
2.266
3145783HORNRTN
Solar/Wind Harmer
0.708
3145783HORNRTN
Solar/Wind Harmer
0.283
3145796HORNRTN
Solar/Wind Harmer
-0.071
316065AD1-022 GEN
Solar/Wind Harmer
11.931
316140AB2-099
Solar/Wind Harmer
0.16
313527AB2-043 GEN
Solar/Wind Harmer
3.807
316237AB2-079_GEN
Solar/Wind Harmer
0.704
970323AG2-213 GEN
Solar/Wind Harmer
11.579
958211AF2-115 GEN
Solar/Wind Harmer
3.579
3144293JTRSVLE
Adder
0.487
315724AD1-057 GEN
Solar/Wind Harmer
4.472
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.023
962561AG1-105 GEN
Solar/Wind Harmer
12.722
316240AF1-291 C
Solar/Wind Harmer
0.677
964791AG1-342 GEN
Solar/Wind Harmer
4.799
3146843MT LREL
Solar/Wind Harmer
-0.022
3146843MT LREL
Solar/Wind Harmer
-0.022
316005AA1-067
Solar/Wind Harmer
0.453
316033AB2-134 GEN
Solar/Wind Harmer
7.153
3145493TOT1
Solar/Wind Harmer
0.343
3145453TOT5
Solar/Wind Harmer
0.206
3145603CNETO
Solar/Wind Harmer
0.137
316118AC1-105 GEN
Solar/Wind Harmer
1.516
944641AF1-129 GEN
Adder
93.733
961601AG1-000A GEN
Solar/Wind Harmer
8.655
316049AB1-081 GEN
Solar/Wind Harmer
2.369
316263AC1-034 GEN
Solar/Wind Harmer
10.321
316248AF1-058 C
Solar/Wind Harmer
0.654
3146776BUCKING
Solar/Wind Harmer
-0.082
3146776BUCKING
Solar/Wind Harmer
-0.007
3142946ENON
Solar/Wind Harmer
-0.002
3151031BRUNSWICKG2
50/50
3.6
970413AG2-270 GEN
50/50
21.919
3151101ELIZAR3
50/50
21.871
944011AF1-069 GEN
Solar/Wind Harmer
18.85
970917AG2-570 GEN
Solar/Wind Harmer
73.696
3143336POWHATN
Solar/Wind Harmer
2.831
316478AD1-087 GEN
Solar/Wind Harmer
2.275
944581AF1-123 GEN
Solar/Wind Harmer
114.728
944601AF1-125 GEN
Solar/Wind Harmer
112.937
3142956BIRDNECK
Solar/Wind Harmer
1.34
316017AA1-139 ULT1
Solar/Wind Harmer
2.014
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
2.885
3144873MCLAUGH
Solar/Wind Harmer
-0.001
966621AG1-532 GEN
Solar/Wind Harmer
0.505
316305AF2-043 C
Solar/Wind Harmer
0.747
316246AF1-032 C
Solar/Wind Harmer
0.502
316320Y1-086
Solar/Wind Harmer
1.453
316321Z2-027
Solar/Wind Harmer
0.666
970657AG2-426 GEN
Solar/Wind Harmer
4.981
3146516WINFALL
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.018
315813AE1-149 C
Solar/Wind Harmer
15.374
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144536CHRHLND
Solar/Wind Harmer
-0.004
316181AB2-040 GEN
Solar/Wind Harmer
3.408
3147043LAWRENC
Solar/Wind Harmer
-0.015
3146376EDENTON
Solar/Wind Harmer
-0.024
3156081AA2-088 GEN
Solar/Wind Harmer
7.858
316011AB1-132 GEN
Solar/Wind Harmer
5.049
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.294
3146173TUNIS
Solar/Wind Harmer
-0.024
315735AD1-075 GEN1
Solar/Wind Harmer
2.411
3145796HORNRTN
Solar/Wind Harmer
-0.095
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
3150861SPRUNCD
Adder
0.971
316317KELFORD C
Solar/Wind Harmer
1.089
3145823KELFORD
Solar/Wind Harmer
-0.023
964241AG1-285 GEN
Solar/Wind Harmer
18.24
3145963POPLR C
Solar/Wind Harmer
-0.023
970257AG2-171 GEN
Solar/Wind Harmer
8.684
971775AH1-396 GEN
Solar/Wind Harmer
1.634
316212AC1-099_GEN
Solar/Wind Harmer
2.014
959311AF2-222 GEN
Solar/Wind Harmer
24.132
3151171GRAVELC
Adder
2.856
3144293JTRSVLE
Adder
0.487
315722AD1-056 GEN
Solar/Wind Harmer
8.131
3147133PAMPLIN
Solar/Wind Harmer
-0.071
3145933PARMELE
Solar/Wind Harmer
-0.023
961611AG1-000B GEN
Solar/Wind Harmer
4.772
942461AE2-259 GEN
Solar/Wind Harmer
3.393
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3146233WITAKRS
Solar/Wind Harmer
0.467
3146233WITAKRS
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.013
3138543CONSLDL
Solar/Wind Harmer
-0.015
316420AA1-050 GEN
Solar/Wind Harmer
2.532
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
315778AD1-151 GEN
Solar/Wind Harmer
19.614
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
961601AG1-000A GEN
Solar/Wind Harmer
8.765
316458AB2-190 GEN2
Solar/Wind Harmer
2.197
970133AG2-095 GEN
Solar/Wind Harmer
2.399
3144216WINCHST
Adder
0.714
3150921YORKTN3
Adder
4.702
316003AC1-222 GEN
Solar/Wind Harmer
2.02
3146776BUCKING
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
1.99
3143096IRON208
Adder
0.734
3143096IRON208
Adder
0.719
316283AC2-100 C
Solar/Wind Harmer
1.848
971683AH1-343 GEN
Solar/Wind Harmer
8.439
972003AH1-546 GEN
Solar/Wind Harmer
7.599
3142946ENON
Solar/Wind Harmer
-0.006
316369SG1_INVT
Solar/Wind Harmer
3.962
961671AG1-007 GEN
Solar/Wind Harmer
0.28
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.658
970937AG2-583 GEN
Solar/Wind Harmer
15.881
971069AG2-661 GEN
Solar/Wind Harmer
3.487
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.018
316359AB2-059 GEN
Solar/Wind Harmer
2.961
3142053HEARTS
Solar/Wind Harmer
0.259
316132AB2-190 GEN1
Solar/Wind Harmer
2.197
3138126ROCKLANDING
Solar/Wind Harmer
0.065
3142543TWELFTH
Solar/Wind Harmer
-0.002
3146776BUCKING
Solar/Wind Harmer
-0.008
971317AH1-138 GEN
Solar/Wind Harmer
2.508
3143096IRON208
Adder
0.734
944631AF1-128 GEN
Adder
81.128
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
270455AD2-022 GEN
Solar/Wind Harmer
3.035
270457AD2-023 GEN
Solar/Wind Harmer
1.539
3143873LANEXA
Solar/Wind Harmer
-0.01
316164AC1-076 GEN
Solar/Wind Helper
1.28
315651AD1-115 GEN
Solar/Wind Helper
0.854
957601AF2-054 GEN
Solar/Wind Harmer
0.415
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
3142433PROV 92
Solar/Wind Harmer
-0.07
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
971377AH1-170 GEN
Solar/Wind Harmer
2.105
3147623JAMES R
Solar/Wind Harmer
0.26
971777AH1-397 GEN
Solar/Wind Harmer
1.954
315662AE1-191 GEN
Solar/Wind Harmer
2.011
316280AD1-041 GEN
Solar/Wind Harmer
1.257
3150351NORNECKC2
Adder
1.137
3147666LOUISA
Solar/Wind Helper
1.361
316192AB2-158 GEN
Solar/Wind Helper
2.279
316447AC1-158 HLD
Solar/Wind Helper
3.8
316044AC1-158 PL1
Solar/Wind Helper
1.727
316123AC1-075 GEN
Solar/Wind Harmer
1.835
970221AG2-151 GEN
Solar/Wind Harmer
10.524
316203AE2-005 GEN
Solar/Wind Harmer
7.059
3141843SHACKLE
Adder
0.761
3150351NORNECKC2
Adder
1.156
3147666LOUISA
Solar/Wind Helper
0.782
3132273ORANGE
Solar/Wind Helper
0.057
3142366NRTHEST
Adder
0.503
3150691DARBY 3
Adder
10.919
3150701DARBY 4
Adder
10.893
3150681DARBY 2
Adder
10.881
3150671DARBY 1
Adder
10.868
316441AF1-014 GEN
Solar/Wind Harmer
1.128
315666AE1-190 GEN
Solar/Wind Harmer
0.503
3142296MT RD221
Adder
0.387
3150341NORNECKC1
Adder
1.194
3150341NORNECKC1
Adder
1.185
316045AC1-158 PL2
Solar/Wind Helper
5.527
316450AC1-158 RIC
Solar/Wind Helper
0.461
966001AG1-469 GEN
Solar/Wind Helper
0.322
LAGNLTFEXP_LAGN->PJM
CLTF
9.518
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.931
TVALTFEXP_TVA->PJM
CLTF
4.778
CPLELTFEXP_CPLE->PJM
CLTF
13.274
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.483
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.547
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.405
MECLTFEXP_MEC->PJM
CLTF
4.678
SIGELTFEXP_SIGE->PJM
CLTF
0.141
NYPJM->LTFIMP_NY
CLTF
2.529
LGEELTFEXP_LGEE->PJM
CLTF
1.72
WECLTFEXP_WEC->PJM
CLTF
0.876

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.48 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3240.38
MW Contribution:
4.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.422
315244AE2-183_ST
50/50
7.898
963041AG1-153 GEN
50/50
7.258
315779AE2-040
50/50
3.424
3151541CLOVER2
50/50
4.907
970533AG2-339 GEN
Solar/Wind Harmer
21.529
970673AG2-436 GEN
Solar/Wind Harmer
35.024
971967AH1-528 GEN
Solar/Wind Harmer
43.56
316233AE1-074 FULL
Solar/Wind Harmer
0.208
971281AH1-106 GEN
Solar/Wind Harmer
3.6
971283AH1-107 GEN
Solar/Wind Harmer
3.6
970085AG2-068 GEN
Solar/Wind Harmer
13.72
970581AG2-369 GEN
Solar/Wind Harmer
11.799
315814AE2-033 C
Solar/Wind Harmer
19.325
316258AE1-075 C
Solar/Wind Harmer
0.178
3143316POE
Solar/Wind Harmer
0.914
316486AD2-202 GEN
Solar/Wind Harmer
0.234
316316AC1-027 C
Solar/Wind Harmer
0.212
3151081ELIZAR1
Adder
20.345
3151091ELIZAR2
Adder
19.992
957871AF2-081 GEN
Solar/Wind Harmer
11.051
3146406KITTY HAWK
Solar/Wind Harmer
0.028
313526AB2-022
Solar/Wind Harmer
0.118
3146396TANGLEW
Solar/Wind Harmer
0.606
3145176PASQUOTANK
Solar/Wind Harmer
0.136
3146486SUNBURY
Solar/Wind Harmer
0.22
3146486SUNBURY
Solar/Wind Harmer
0.22
316311AC2-079 GEN
Solar/Wind Harmer
6.314
970657AG2-426 GEN
Solar/Wind Harmer
1.61
3130156CHOWAN
Solar/Wind Harmer
0.216
3130156CHOWAN
Solar/Wind Harmer
0.216
315652AC1-086 GEN
Solar/Wind Harmer
23.467
3137643SOCKMAN
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.574
3145893MURPHYS
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.212
3130546PLYMOUTH
Solar/Wind Harmer
0.212
315732AD1-074 GEN1
Solar/Wind Harmer
1.206
315733AD1-074 GEN2
Solar/Wind Harmer
1.206
316426AA2-053 GEN
Solar/Wind Harmer
0.706
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.878
316463AE2-346 GEN
Solar/Wind Harmer
0.18
3145513AHOSKIE
Solar/Wind Harmer
0.44
3145513AHOSKIE
Solar/Wind Harmer
0.21
3145796HORNRTN
Solar/Wind Harmer
0.673
3145796HORNRTN
Solar/Wind Harmer
0.084
971285AH1-108 GEN
Adder
1.586
971445AH1-216 GEN
Solar/Wind Harmer
14.807
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.898
3146033SCOT NK
Solar/Wind Harmer
0.822
3151201GRAVEL4
Adder
14.866
3151221GRAVEL6
Adder
14.849
3151191GRAVEL3
Adder
14.678
3151211GRAVEL5
Adder
14.678
316210AC1-098 GEN
Solar/Wind Harmer
1.886
316274AC1-208 GEN
Solar/Wind Harmer
1.05
316327AA2-057 GEN
Solar/Wind Harmer
0.294
3145746EVERETS
Solar/Wind Harmer
0.787
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
315697AD1-025 GEN
Solar/Wind Harmer
0.213
3144303KENBRDG
Solar/Wind Harmer
0.158
957861AF2-080 GEN
Solar/Wind Harmer
8.469
3145573BETHELC
Solar/Wind Harmer
0.195
3145573BETHELC
Solar/Wind Harmer
0.195
970683AG2-441 GEN
Solar/Wind Harmer
11.764
970681AG2-440 GEN
Solar/Wind Harmer
7.808
946301AF1-294 GEN
Solar/Wind Harmer
3.81
961791AG1-021 GEN
Solar/Wind Harmer
1.853
3147173SINAI
Solar/Wind Harmer
0.189
3147243WELCO
Solar/Wind Harmer
0.118
316159AE1-175 C
Solar/Wind Harmer
0.147
3138283WHITEMARSH
Solar/Wind Harmer
0.039
3151031BRUNSWICKG2
50/50
3.585
970413AG2-270 GEN
50/50
21.534
3151101ELIZAR3
50/50
21.865
944011AF1-069 GEN
Solar/Wind Harmer
17.147
970917AG2-570 GEN
Solar/Wind Harmer
23.205
3143336POWHATN
Solar/Wind Harmer
3.6
316478AD1-087 GEN
Solar/Wind Harmer
0.798
944581AF1-123 GEN
Solar/Wind Harmer
50.528
944601AF1-125 GEN
Solar/Wind Harmer
49.75
316017AA1-139 ULT1
Solar/Wind Harmer
0.118
3146456SLIGO L269
Solar/Wind Harmer
0.222
971153AH1-033 GEN
Solar/Wind Harmer
2.563
3144873MCLAUGH
Solar/Wind Harmer
0.006
316246AF1-032 C
Solar/Wind Harmer
0.098
316321Z2-027
Solar/Wind Harmer
0.039
970657AG2-426 GEN
Solar/Wind Harmer
4.921
3146516WINFALL
Solar/Wind Harmer
0.219
315813AE1-149 C
Solar/Wind Harmer
11.671
3144536CHRHLND
Solar/Wind Harmer
0.033
3145273HOLLAND
Solar/Wind Harmer
0.164
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146376EDENTON
Solar/Wind Harmer
0.216
316181AB2-040 GEN
Solar/Wind Harmer
0.307
3156081AA2-088 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Solar/Wind Harmer
0.128
316011AB1-132 GEN
Solar/Wind Harmer
3.87
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
0.356
3145893MURPHYS
Solar/Wind Harmer
0.212
315735AD1-075 GEN1
Solar/Wind Harmer
0.602
3146173TUNIS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
3145336SMITFLD
Solar/Wind Harmer
0.084
3145796HORNRTN
Solar/Wind Harmer
0.842
3145796HORNRTN
Solar/Wind Harmer
0.21
3150861SPRUNCD
Adder
0.969
3146263WOODLND
Solar/Wind Harmer
0.21
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.205
3151171GRAVELC
Adder
2.857
316212AC1-099_GEN
Solar/Wind Harmer
1.052
961611AG1-000B GEN
Solar/Wind Harmer
5.38
315722AD1-056 GEN
Solar/Wind Harmer
6.957
964241AG1-285 GEN
Solar/Wind Harmer
13.382
3145933PARMELE
Solar/Wind Harmer
0.2
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970257AG2-171 GEN
Solar/Wind Harmer
6.318
971775AH1-396 GEN
Solar/Wind Harmer
0.316
959311AF2-222 GEN
Solar/Wind Harmer
17.494
3146233WITAKRS
Solar/Wind Harmer
0.986
3146233WITAKRS
Solar/Wind Harmer
0.134
315778AD1-151 GEN
Solar/Wind Harmer
15.698
3138543CONSLDL
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.195
3146083TARBORO
Solar/Wind Harmer
0.195
316458AB2-190 GEN2
Solar/Wind Harmer
1.034
961601AG1-000A GEN
Solar/Wind Harmer
13.776
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.194
971623AH1-311 GEN
Solar/Wind Harmer
0.387
3144293JTRSVLE
Adder
0.461
3147133PAMPLIN
Solar/Wind Harmer
0.601
970133AG2-095 GEN
Solar/Wind Harmer
1.823
3144216WINCHST
Adder
0.715
3150921YORKTN3
Adder
4.709
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.11
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
316222AC1-221 GEN
Solar/Wind Harmer
0.708
316283AC2-100 C
Solar/Wind Harmer
0.334
971683AH1-343 GEN
Solar/Wind Harmer
6.222
3142946ENON
Solar/Wind Harmer
0.054
3146776BUCKING
Solar/Wind Harmer
0.058
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.765
316203AE2-005 GEN
Solar/Wind Harmer
0
3141873WAN 176
Solar/Wind Harmer
2.656
970293AG2-193 GEN
Solar/Wind Harmer
1.581
3141766HARMONY
Solar/Wind Harmer
1.962
316123AC1-075 GEN
Solar/Wind Harmer
0.195
316075AC2-137 C
Solar/Wind Harmer
0.038
972003AH1-546 GEN
Solar/Wind Harmer
4.881
3142416OLDCHRC
Solar/Wind Harmer
1.236
970221AG2-151 GEN
Solar/Wind Harmer
6.625
3150351NORNECKC2
Adder
1.171
316473AC1-191 GEN
Solar/Wind Harmer
0.382
3147666LOUISA
Solar/Wind Helper
0.563
970119AG2-088 GEN
50/50
40.664
315243AE2-183_GT3
50/50
4.548
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.585
971451AH1-221 GEN
50/50
10.887
3151531CLOVER1
50/50
4.945
3143226MDLTHAN
Solar/Wind Harmer
0.305
941031AE2-094 GEN
Solar/Wind Harmer
52.48
940641AE2-051 GEN
Solar/Wind Harmer
22.661
939411AE1-173 GEN
Solar/Wind Harmer
114.417
970919AG2-571 GEN
Solar/Wind Harmer
9.282
3143526WINTERP
Solar/Wind Harmer
1.349
970087AG2-069 GEN
Solar/Wind Harmer
20.58
957481AF2-042 GEN
Solar/Wind Harmer
64.487
3143336POWHATN
Solar/Wind Harmer
4.235
315693AD1-088 GEN
Solar/Wind Harmer
11.17
316023GEN1_S
Solar/Wind Harmer
0.499
944591AF1-124 GEN
Solar/Wind Harmer
50.708
315773AC2-141 GEN
Solar/Wind Harmer
8.149
3146456SLIGO L269
Solar/Wind Harmer
0.222
319010AE1-072 C
Solar/Wind Harmer
1.105
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.039
3150981CHESPKA
Adder
2.766
316093AE2-104_GEN
Solar/Wind Harmer
3.705
316381AD1-082 GEN
Solar/Wind Harmer
0.222
960081AF2-299 GEN
Solar/Wind Harmer
2.104
3146516WINFALL
Solar/Wind Harmer
0.709
3146516WINFALL
Solar/Wind Harmer
0.219
3130156CHOWAN
Solar/Wind Harmer
0.216
316072AD1-144
Solar/Wind Harmer
0.077
3147043LAWRENC
Adder
1.937
315816AE2-034 GEN
Solar/Wind Harmer
0.912
3145663CRESWEL
Solar/Wind Harmer
0.598
971163AH1-040 GEN
Solar/Wind Harmer
17.102
3145893MURPHYS
Solar/Wind Harmer
0.85
3145893MURPHYS
Solar/Wind Harmer
0.945
315607AA1-063A GEN
Solar/Wind Harmer
0.427
315737AD1-076 GEN
Solar/Wind Harmer
2.715
3146173TUNIS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.502
3145336SMITFLD
Solar/Wind Harmer
0.843
3145796HORNRTN
Solar/Wind Harmer
0.694
3145796HORNRTN
Solar/Wind Harmer
0.21
3150851SPRUNCC
Adder
0.969
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.945
3145683EARLEYS
Solar/Wind Harmer
0.21
316129AC1-054 GEN
Solar/Wind Harmer
0.777
971065AG2-659 GEN
Solar/Wind Harmer
8.869
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.205
3151171GRAVELC
Adder
2.173
315671AE2-027_GEN
Solar/Wind Harmer
0.001
316131AB2-060 GEN
Solar/Wind Harmer
0.629
961611AG1-000B GEN
Solar/Wind Harmer
10.58
3146293MARTNCO
Solar/Wind Harmer
0.186
315785AD2-033 C
Solar/Wind Harmer
1.604
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316034AC1-036 C
Solar/Wind Harmer
0.013
316494AC1-189 GEN
Solar/Wind Harmer
0.664
3146233WITAKRS
Solar/Wind Harmer
0.781
971069AG2-661 GEN
Solar/Wind Harmer
3.488
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.195
3145493TOT1
Solar/Wind Harmer
0.868
970401AG2-262 GEN
Solar/Wind Harmer
1.142
970685AG2-442 GEN
Solar/Wind Harmer
14.501
316132AB2-190 GEN1
Solar/Wind Harmer
1.034
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.155
316359AB2-059 GEN
Solar/Wind Harmer
0.688
3142053HEARTS
Solar/Wind Harmer
0.341
971563AH1-280 GEN
Solar/Wind Harmer
2.059
3144293JTRSVLE
Adder
0.461
3144293JTRSVLE
Adder
0.364
3138126ROCKLANDING
Solar/Wind Harmer
0.087
3142543TWELFTH
Solar/Wind Harmer
0.018
3146926FARMVIL
Solar/Wind Harmer
0.11
971317AH1-138 GEN
Solar/Wind Harmer
1.336
970937AG2-583 GEN
Solar/Wind Harmer
10.788
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.242
3146776BUCKING
Solar/Wind Harmer
0.065
3142433PROV 92
Solar/Wind Harmer
0.629
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
971777AH1-397 GEN
Solar/Wind Harmer
0.395
3141766HARMONY
Solar/Wind Harmer
0.029
315975AC1-164 GENB
Solar/Wind Harmer
0.045
3138133OCRAN
Solar/Wind Harmer
0.086
3142416OLDCHRC
Solar/Wind Harmer
0.331
3142416OLDCHRC
Solar/Wind Harmer
0.127
962861AG1-135 GEN
Solar/Wind Harmer
4.059
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.146
971377AH1-170 GEN
Solar/Wind Harmer
1.325
3147623JAMES R
Solar/Wind Harmer
0.288
3141726DUNNSVL
Solar/Wind Harmer
0.473
3150351NORNECKC2
Adder
1.151
316447AC1-158 HLD
Solar/Wind Helper
3.591
316044AC1-158 PL1
Solar/Wind Helper
1.632
3147666LOUISA
Solar/Wind Helper
0.979
316192AB2-158 GEN
Solar/Wind Helper
1.615
971845AH1-439 GEN
Solar/Wind Harmer
7.442
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3143873LANEXA
Solar/Wind Harmer
0.09
970189AG2-124 GEN
Solar/Wind Harmer
4.436
3141873WAN 176
Solar/Wind Harmer
0.03
3141913WHIT STONE
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.043
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
972205AH1-687 GEN
Adder
5.891
3141813NORNECK
Solar/Wind Harmer
0.115
315242AE2-183_GT2
50/50
4.548
315241AE2-183_GT1
50/50
4.536
972185AH1-677 GEN
50/50
16.441
3151041BRUNSWICKG3
50/50
3.585
972187AH1-678 GEN
50/50
8.226
971223AH1-071 GEN
Solar/Wind Harmer
3.253
970933AG2-581 GEN
Solar/Wind Harmer
21.195
3143526WINTERP
Solar/Wind Harmer
1.349
3144356SAPONY
Solar/Wind Harmer
2.052
316315AB2-025 C
Solar/Wind Harmer
0.196
970099AG2-077 GEN
Solar/Wind Harmer
25.795
316313AB2-026
Solar/Wind Harmer
0.148
316365GEN2_N
Solar/Wind Harmer
0.499
316294AC1-161 GEN
Solar/Wind Harmer
3.857
3145506HICKORY
Solar/Wind Harmer
0.89
3145506HICKORY
Solar/Wind Harmer
0.534
3145506HICKORY
Solar/Wind Harmer
0.134
316339AD2-160 GEN
Solar/Wind Harmer
0.355
316388AE2-253 GEN
Solar/Wind Harmer
0.691
3137176SLIGO L2192
Solar/Wind Harmer
0.882
3146456SLIGO L269
Solar/Wind Harmer
3.923
3130086AYDLETT
Solar/Wind Harmer
0.886
3150991CHESPKB
Adder
2.32
3150991CHESPKB
Adder
2.265
316336AC2-165 C
Solar/Wind Harmer
11.186
3146386ELIZ CT
Solar/Wind Harmer
0.22
315835AF2-110_GEN
Solar/Wind Harmer
1.512
316349AD2-085 GEN
Solar/Wind Harmer
0.147
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
315742AE1-103 GEN
Solar/Wind Harmer
3.249
3146376EDENTON
Solar/Wind Harmer
0.96
3146376EDENTON
Solar/Wind Harmer
0.96
313506AB2-031 GEN
Solar/Wind Harmer
0.661
315614AA2-178 GEN
Solar/Wind Harmer
1.216
962571AG1-106 GEN
Solar/Wind Harmer
3.035
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
1.423
3145893MURPHYS
Solar/Wind Harmer
0.382
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.263
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
316065AD1-022 GEN
Solar/Wind Harmer
9.727
316140AB2-099
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.631
3145783HORNRTN
Solar/Wind Harmer
3.738
3145783HORNRTN
Solar/Wind Harmer
2.99
3145783HORNRTN
Solar/Wind Harmer
0.934
3145783HORNRTN
Solar/Wind Harmer
0.374
970301AG2-198 GEN
Solar/Wind Harmer
8.7
315724AD1-057 GEN
Solar/Wind Harmer
3.881
3145933PARMELE
Solar/Wind Harmer
0.401
3145933PARMELE
Solar/Wind Harmer
0.2
316005AA1-067
Solar/Wind Harmer
0.211
316033AB2-134 GEN
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
8.424
944641AF1-129 GEN
Adder
93.755
962561AG1-105 GEN
Solar/Wind Harmer
9.4
3145493TOT1
Solar/Wind Harmer
0.452
3145453TOT5
Solar/Wind Harmer
0.271
3145603CNETO
Solar/Wind Harmer
0.181
964791AG1-342 GEN
Solar/Wind Harmer
3.737
3146843MT LREL
Solar/Wind Harmer
0.194
3146843MT LREL
Solar/Wind Harmer
0.194
961601AG1-000A GEN
Solar/Wind Harmer
3.444
316049AB1-081 GEN
Solar/Wind Harmer
1.102
316263AC1-034 GEN
Solar/Wind Harmer
7.36
958211AF2-115 GEN
Solar/Wind Harmer
2.317
3144293JTRSVLE
Adder
0.461
316118AC1-105 GEN
Solar/Wind Harmer
0.491
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.153
3142946ENON
Solar/Wind Harmer
0.016
3146776BUCKING
Solar/Wind Harmer
0.649
3146776BUCKING
Solar/Wind Harmer
0.053
3142366NRTHEST
Adder
0.504
3150691DARBY 3
Adder
10.945
3150701DARBY 4
Adder
10.92
3150681DARBY 2
Adder
10.907
3150671DARBY 1
Adder
10.894
316156AD2-030 GEN
Solar/Wind Harmer
0.109
315976AC1-164 GENA
Solar/Wind Harmer
1.529
316169AC1-164_GENC
Solar/Wind Harmer
1.321
942751AE2-291 GEN
Solar/Wind Harmer
7.371
316312AB1-027
Solar/Wind Harmer
0.227
3142296MT RD221
Adder
0.389
3150341NORNECKC1
Adder
1.209
3150341NORNECKC1
Adder
1.2
966871AG1-558 GEN
Solar/Wind Harmer
0.131
316045AC1-158 PL2
Solar/Wind Helper
5.223
316450AC1-158 RIC
Solar/Wind Helper
0.435
LAGNLTFEXP_LAGN->PJM
CLTF
9.042
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.15
TVALTFEXP_TVA->PJM
CLTF
4.533
CPLELTFEXP_CPLE->PJM
CLTF
13.013
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.505
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.506
MECLTFEXP_MEC->PJM
CLTF
4.337
SIGELTFEXP_SIGE->PJM
CLTF
0.13
NYPJM->LTFIMP_NY
CLTF
2.4
LGEELTFEXP_LGEE->PJM
CLTF
1.575
WECLTFEXP_WEC->PJM
CLTF
0.802

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57302_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57302_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.16 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4650.9
MW Contribution:
6.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.152
315244AE2-183_ST
50/50
5.998
963041AG1-153 GEN
50/50
5.514
315779AE2-040
50/50
2.502
3147346CASHSCORNER
Solar/Wind Harmer
0.402
970533AG2-339 GEN
Solar/Wind Harmer
16.336
970673AG2-436 GEN
Solar/Wind Harmer
52.504
971967AH1-528 GEN
Solar/Wind Harmer
43.839
316258AE1-075 C
Solar/Wind Harmer
0.541
316405AF2-144 C
Solar/Wind Harmer
0.571
970085AG2-068 GEN
Solar/Wind Harmer
13.704
970581AG2-369 GEN
Solar/Wind Harmer
11.785
316233AE1-074 FULL
Solar/Wind Harmer
0.573
971281AH1-106 GEN
Solar/Wind Harmer
3.463
971283AH1-107 GEN
Solar/Wind Harmer
3.463
316486AD2-202 GEN
Solar/Wind Harmer
0.507
315814AE2-033 C
Solar/Wind Harmer
18.675
3143316POE
Solar/Wind Harmer
-0.072
946281AF1-292 GEN
Solar/Wind Harmer
0.408
946301AF1-294 GEN
Solar/Wind Harmer
4.626
961791AG1-021 GEN
Solar/Wind Harmer
2.256
970683AG2-441 GEN
Solar/Wind Harmer
12.72
970681AG2-440 GEN
Solar/Wind Harmer
8.442
3144303KENBRDG
Solar/Wind Harmer
-0.014
316238AB2-078_GEN
Solar/Wind Harmer
0.536
316239AB2-077_GEN
Solar/Wind Harmer
0.536
970831AG2-522 GEN
Solar/Wind Harmer
8.846
3137643SOCKMAN
Solar/Wind Harmer
-0.07
315652AC1-086 GEN
Solar/Wind Harmer
19.738
971845AH1-439 GEN
Solar/Wind Harmer
9.311
316322AB2-045
Solar/Wind Harmer
0.586
3146043SEABORD
Solar/Wind Harmer
-0.017
316426AA2-053 GEN
Solar/Wind Harmer
1.755
316018AA1-139 ULT2
Solar/Wind Harmer
1.488
957871AF2-081 GEN
Solar/Wind Harmer
8.708
3146406KITTY HAWK
Solar/Wind Harmer
0.014
316316AC1-027 C
Solar/Wind Harmer
0.532
313526AB2-022
Solar/Wind Harmer
0.467
3151081ELIZAR1
Adder
14.144
3151091ELIZAR2
Adder
13.898
3145796HORNRTN
Solar/Wind Harmer
-0.055
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3146396TANGLEW
Solar/Wind Harmer
0.319
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
316318V4-068
Solar/Wind Harmer
0.43
3145893MURPHYS
Solar/Wind Harmer
-0.046
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.686
315833AF1-017_GEN
Solar/Wind Harmer
3.27
315800Z1-036_GEN1
Solar/Wind Harmer
4.243
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970657AG2-426 GEN
Solar/Wind Harmer
1.078
316463AE2-346 GEN
Solar/Wind Harmer
0.276
3145513AHOSKIE
Solar/Wind Harmer
0.149
961941AG1-037 GEN
Solar/Wind Harmer
0.128
3145513AHOSKIE
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.427
315732AD1-074 GEN1
Solar/Wind Harmer
3.426
315733AD1-074 GEN2
Solar/Wind Harmer
3.426
3146033SCOT NK
Solar/Wind Harmer
-0.067
316274AC1-208 GEN
Solar/Wind Harmer
1.808
316210AC1-098 GEN
Solar/Wind Harmer
2.628
316174AB2-169 GEN
Solar/Wind Harmer
2.549
972205AH1-687 GEN
Adder
6.27
316327AA2-057 GEN
Solar/Wind Harmer
1.656
3147173SINAI
Solar/Wind Harmer
-0.016
3147243WELCO
Solar/Wind Harmer
-0.01
3152261N ANNA2
50/50
36.308
3151771S ANNAG1
50/50
0.934
3151801S ANNAS2
50/50
0.48
3151761LOISA E
50/50
35.481
3151721LOISA A
50/50
17.314
3151031BRUNSWICKG2
50/50
2.723
3147666LOUISA
Solar/Wind Harmer
-0.113
944011AF1-069 GEN
Solar/Wind Harmer
14.272
3143336POWHATN
Solar/Wind Harmer
2.254
970917AG2-570 GEN
Solar/Wind Harmer
55.648
316478AD1-087 GEN
Solar/Wind Harmer
1.732
3146926FARMVIL
Solar/Wind Harmer
-0.011
966621AG1-532 GEN
Solar/Wind Harmer
0.37
942461AE2-259 GEN
Solar/Wind Harmer
2.73
3147043LAWRENC
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.057
3144293JTRSVLE
Adder
0.384
959311AF2-222 GEN
Solar/Wind Harmer
18.765
970257AG2-171 GEN
Solar/Wind Harmer
6.737
971775AH1-396 GEN
Solar/Wind Harmer
1.268
964241AG1-285 GEN
Solar/Wind Harmer
13.986
316181AB2-040 GEN
Solar/Wind Harmer
2.491
944581AF1-123 GEN
Solar/Wind Harmer
80.039
944601AF1-125 GEN
Solar/Wind Harmer
78.79
316011AB1-132 GEN
Solar/Wind Harmer
3.664
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
316190AA2-174 GEN
Solar/Wind Harmer
0.214
316017AA1-139 ULT1
Solar/Wind Harmer
1.405
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.014
3142956BIRDNECK
Solar/Wind Harmer
0.932
316320Y1-086
Solar/Wind Harmer
1.016
316305AF2-043 C
Solar/Wind Harmer
0.521
316246AF1-032 C
Solar/Wind Harmer
0.35
3151101ELIZAR3
Adder
14.325
3156081AA2-088 GEN
Solar/Wind Harmer
5.622
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.017
316321Z2-027
Solar/Wind Harmer
0.466
3145273HOLLAND
Solar/Wind Harmer
-0.013
3144873MCLAUGH
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.12
3145893MURPHYS
Solar/Wind Harmer
-0.017
3146263WOODLND
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
970657AG2-426 GEN
Solar/Wind Harmer
3.452
315813AE1-149 C
Solar/Wind Harmer
10.616
3146206CASHIE
Solar/Wind Harmer
-0.017
315735AD1-075 GEN1
Solar/Wind Harmer
1.712
3144536CHRHLND
Solar/Wind Harmer
-0.003
316317KELFORD C
Solar/Wind Harmer
0.784
3145823KELFORD
Solar/Wind Harmer
-0.017
316212AC1-099_GEN
Solar/Wind Harmer
1.46
3145963POPLR C
Solar/Wind Harmer
-0.017
972003AH1-546 GEN
Solar/Wind Harmer
6.746
315722AD1-056 GEN
Solar/Wind Harmer
5.91
3145933PARMELE
Solar/Wind Harmer
-0.016
3146233WITAKRS
Solar/Wind Harmer
0.34
3146233WITAKRS
Solar/Wind Harmer
-0.011
3138543CONSLDL
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
3145336SMITFLD
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
1.834
3146073TAR RVR
Solar/Wind Harmer
-0.016
3146083TARBORO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.016
961601AG1-000A GEN
Solar/Wind Harmer
6.377
3150861SPRUNCD
Adder
0.655
316003AC1-222 GEN
Solar/Wind Harmer
1.518
3151171GRAVELC
Adder
1.917
3132273ORANGE
Solar/Wind Harmer
-0.003
961611AG1-000B GEN
Solar/Wind Harmer
3.183
970221AG2-151 GEN
Solar/Wind Harmer
9.416
971683AH1-343 GEN
Solar/Wind Harmer
6.324
316222AC1-221 GEN
Solar/Wind Harmer
1.476
316283AC2-100 C
Solar/Wind Harmer
1.369
315778AD1-151 GEN
Solar/Wind Harmer
12.903
316458AB2-190 GEN2
Solar/Wind Harmer
1.437
3144216WINCHST
Adder
0.463
970133AG2-095 GEN
Solar/Wind Harmer
1.551
3150921YORKTN3
Adder
3.032
270494AE1-108_GEN
Solar/Wind Harmer
3.338
316123AC1-075 GEN
Solar/Wind Harmer
1.31
3151731LOISA B
50/50
17.404
315242AE2-183_GT2
50/50
3.454
315241AE2-183_GT1
50/50
3.445
972185AH1-677 GEN
50/50
12.485
3151041BRUNSWICKG3
50/50
2.723
972187AH1-678 GEN
50/50
6.249
971223AH1-071 GEN
Solar/Wind Harmer
3.28
966001AG1-469 GEN
Solar/Wind Harmer
0.464
970933AG2-581 GEN
Solar/Wind Harmer
21.352
316313AB2-026
Solar/Wind Harmer
0.601
316336AC2-165 C
Solar/Wind Harmer
13.316
3143526WINTERP
Solar/Wind Harmer
-0.11
970099AG2-077 GEN
Solar/Wind Harmer
26.279
3144356SAPONY
Solar/Wind Harmer
0.702
316315AB2-025 C
Solar/Wind Harmer
0.542
970301AG2-198 GEN
Solar/Wind Harmer
9.608
315687AD1-152 GEN
Solar/Wind Harmer
2.245
316365GEN2_N
Solar/Wind Harmer
1.243
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.82
3144293JTRSVLE
Adder
0.384
970323AG2-213 GEN
Solar/Wind Harmer
8.983
313506AB2-031 GEN
Solar/Wind Harmer
1.434
313527AB2-043 GEN
Solar/Wind Harmer
2.901
316237AB2-079_GEN
Solar/Wind Harmer
0.536
962571AG1-106 GEN
Solar/Wind Harmer
2.522
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3146776BUCKING
Solar/Wind Harmer
-0.069
3146776BUCKING
Solar/Wind Harmer
-0.006
316185AD1-033 GEN
Solar/Wind Harmer
1.835
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.042
3145506HICKORY
Solar/Wind Harmer
-0.01
316294AC1-161 GEN
Solar/Wind Harmer
5.626
316339AD2-160 GEN
Solar/Wind Harmer
1.171
316388AE2-253 GEN
Solar/Wind Harmer
1.171
3137176SLIGO L2192
Solar/Wind Harmer
-0.069
3146456SLIGO L269
Solar/Wind Harmer
2.055
3130086AYDLETT
Solar/Wind Harmer
-0.069
3145783HORNRTN
Solar/Wind Harmer
2.064
3145783HORNRTN
Solar/Wind Harmer
1.651
3145783HORNRTN
Solar/Wind Harmer
0.516
3145783HORNRTN
Solar/Wind Harmer
0.206
3146386ELIZ CT
Solar/Wind Harmer
-0.017
315839AE2-212 C
Solar/Wind Harmer
0.488
3145746EVERETS
Solar/Wind Harmer
-0.064
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
316236AE1-162_GEN
Solar/Wind Harmer
0.485
957861AF2-080 GEN
Solar/Wind Harmer
7.053
3145573BETHELC
Solar/Wind Harmer
-0.016
3145573BETHELC
Solar/Wind Harmer
-0.016
971445AH1-216 GEN
Solar/Wind Harmer
9.939
971285AH1-108 GEN
Adder
1.071
3151201GRAVEL4
Adder
9.976
3151221GRAVEL6
Adder
9.964
3151191GRAVEL3
Adder
9.849
3151211GRAVEL5
Adder
9.849
315697AD1-025 GEN
Solar/Wind Harmer
2.961
3145796HORNRTN
Solar/Wind Harmer
-0.052
315742AE1-103 GEN
Solar/Wind Harmer
4.111
315835AF2-110_GEN
Solar/Wind Harmer
2.164
3150991CHESPKB
Adder
1.612
3150991CHESPKB
Adder
1.574
316431W1029_GEN1
Solar/Wind Harmer
3.13
316433W1029_GEN2
Solar/Wind Harmer
3.13
316435W1029_GEN3
Solar/Wind Harmer
3.13
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.481
3145893MURPHYS
Solar/Wind Harmer
-0.031
316349AD2-085 GEN
Solar/Wind Harmer
1.529
3146376EDENTON
Solar/Wind Harmer
0.509
3146376EDENTON
Solar/Wind Harmer
0.509
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
962561AG1-105 GEN
Solar/Wind Harmer
9.639
316140AB2-099
Solar/Wind Harmer
0.115
316083AB2-161 GEN
Solar/Wind Harmer
2.77
315614AA2-178 GEN
Solar/Wind Harmer
1.836
964791AG1-342 GEN
Solar/Wind Harmer
3.632
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
316065AD1-022 GEN
Solar/Wind Harmer
8.488
316118AC1-105 GEN
Solar/Wind Harmer
1.145
315724AD1-057 GEN
Solar/Wind Harmer
3.251
316248AF1-058 C
Solar/Wind Harmer
0.493
3145933PARMELE
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.016
316005AA1-067
Solar/Wind Harmer
0.326
3145493TOT1
Solar/Wind Harmer
0.249
3145453TOT5
Solar/Wind Harmer
0.149
3145603CNETO
Solar/Wind Harmer
0.099
316049AB1-081 GEN
Solar/Wind Harmer
1.724
316263AC1-034 GEN
Solar/Wind Harmer
7.512
961601AG1-000A GEN
Solar/Wind Harmer
6.297
316240AF1-291 C
Solar/Wind Harmer
0.449
316033AB2-134 GEN
Solar/Wind Harmer
4.725
944641AF1-129 GEN
Adder
61.535
3152251N ANNA1
50/50
36.289
3151791S ANNAG2
50/50
0.934
3151781S ANNAS1
50/50
0.48
3151741LOISA C
50/50
0.952
3151751LOISA D
50/50
17.404
970119AG2-088 GEN
50/50
31.142
315243AE2-183_GT3
50/50
3.454
3151051BRUNSWICKS1
50/50
5.654
3151021BRUNSWICKG1
50/50
2.723
971451AH1-221 GEN
50/50
8.27
3147666LOUISA
Solar/Wind Harmer
-0.196
316192AB2-158 GEN
Solar/Wind Harmer
5.699
3143226MDLTHAN
Solar/Wind Harmer
-0.026
941031AE2-094 GEN
Solar/Wind Harmer
45.548
940641AE2-051 GEN
Solar/Wind Harmer
22.337
3143336POWHATN
Solar/Wind Harmer
2.652
970919AG2-571 GEN
Solar/Wind Harmer
7.044
939411AE1-173 GEN
Solar/Wind Harmer
111.176
970087AG2-069 GEN
Solar/Wind Harmer
20.556
3143526WINTERP
Solar/Wind Harmer
-0.11
957481AF2-042 GEN
Solar/Wind Harmer
65.698
315693AD1-088 GEN
Solar/Wind Harmer
10.259
970937AG2-583 GEN
Solar/Wind Harmer
13.447
316023GEN1_S
Solar/Wind Harmer
1.243
3146926FARMVIL
Solar/Wind Harmer
-0.011
960081AF2-299 GEN
Solar/Wind Harmer
2.051
3147043LAWRENC
Adder
1.459
971563AH1-280 GEN
Solar/Wind Harmer
2.256
3144293JTRSVLE
Adder
0.384
3144293JTRSVLE
Adder
0.303
970685AG2-442 GEN
Solar/Wind Harmer
15.775
316087AB2-174 GEN
Solar/Wind Harmer
2.562
316034AC1-036 C
Solar/Wind Harmer
0.332
315785AD2-033 C
Solar/Wind Harmer
4.061
316131AB2-060 GEN
Solar/Wind Harmer
1.923
971065AG2-659 GEN
Solar/Wind Harmer
8.868
316129AC1-054 GEN
Solar/Wind Harmer
1.549
944591AF1-124 GEN
Solar/Wind Harmer
80.328
3146776BUCKING
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
1.756
315773AC2-141 GEN
Solar/Wind Harmer
7.279
3146456SLIGO L269
Solar/Wind Harmer
-0.017
319010AE1-072 C
Solar/Wind Harmer
3.512
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.017
316093AE2-104_GEN
Solar/Wind Harmer
5.033
316375AC2-012 GEN
Solar/Wind Harmer
5.981
316036AC1-147 C
Solar/Wind Harmer
0.465
3150981CHESPKA
Adder
1.922
3146516WINFALL
Solar/Wind Harmer
-0.056
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.511
315611Z1-036_GEN2
Solar/Wind Harmer
4.243
3146263WOODLND
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
316381AD1-082 GEN
Solar/Wind Harmer
1.562
315816AE2-034 GEN
Solar/Wind Harmer
1.377
3145663CRESWEL
Solar/Wind Harmer
-0.048
971163AH1-040 GEN
Solar/Wind Harmer
15.995
3145683EARLEYS
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.11
3156021HOLLOMANSOL
Solar/Wind Harmer
2.281
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.244
315737AD1-076 GEN
Solar/Wind Harmer
3.22
3145823KELFORD
Solar/Wind Harmer
-0.017
316072AD1-144
Solar/Wind Harmer
0.338
3145963POPLR C
Solar/Wind Harmer
-0.017
3146293MARTNCO
Solar/Wind Harmer
0.101
316319Z2-044 C
Solar/Wind Harmer
0.897
3146233WITAKRS
Solar/Wind Harmer
-0.064
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
3145336SMITFLD
Solar/Wind Harmer
-0.064
316494AC1-189 GEN
Solar/Wind Harmer
1.735
961671AG1-007 GEN
Solar/Wind Harmer
0.203
3146083TARBORO
Solar/Wind Harmer
-0.016
3145493TOT1
Solar/Wind Harmer
0.477
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.013
316359AB2-059 GEN
Solar/Wind Harmer
2.155
3142053HEARTS
Solar/Wind Harmer
0.188
3150851SPRUNCC
Adder
0.655
3151171GRAVELC
Adder
1.458
315671AE2-027_GEN
Solar/Wind Harmer
2.75
961611AG1-000B GEN
Solar/Wind Harmer
7.461
971377AH1-170 GEN
Solar/Wind Harmer
1.883
3147623JAMES R
Solar/Wind Harmer
0.233
315683AE1-153 C
Solar/Wind Harmer
14.012
316369SG1_INVT
Solar/Wind Harmer
2.617
971069AG2-661 GEN
Solar/Wind Harmer
2.294
316132AB2-190 GEN1
Solar/Wind Harmer
1.437
3138126ROCKLANDING
Solar/Wind Harmer
0.042
3142543TWELFTH
Solar/Wind Harmer
-0.001
LAGNLTFEXP_LAGN->PJM
CLTF
6.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.773
TVALTFEXP_TVA->PJM
CLTF
3.101
CPLELTFEXP_CPLE->PJM
CLTF
9.698
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.906
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.435
MECLTFEXP_MEC->PJM
CLTF
2.575
SIGELTFEXP_SIGE->PJM
CLTF
0.077
NYPJM->LTFIMP_NY
CLTF
2.605
LGEELTFEXP_LGEE->PJM
CLTF
0.901
WECLTFEXP_WEC->PJM
CLTF
0.437

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.01 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4251.24
MW Contribution:
5.11
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.921
315244AE2-183_ST
50/50
5.655
963041AG1-153 GEN
50/50
5.199
316164AC1-076 GEN
Solar/Wind Harmer
0.431
3147346CASHSCORNER
Solar/Wind Harmer
0.636
970533AG2-339 GEN
Solar/Wind Harmer
15.398
970673AG2-436 GEN
Solar/Wind Harmer
25.06
971967AH1-528 GEN
Solar/Wind Harmer
31.332
316258AE1-075 C
Solar/Wind Harmer
0.143
970085AG2-068 GEN
Solar/Wind Harmer
9.811
970581AG2-369 GEN
Solar/Wind Harmer
8.437
315651AD1-115 GEN
Solar/Wind Harmer
0
316233AE1-074 FULL
Solar/Wind Harmer
0.142
971281AH1-106 GEN
Solar/Wind Harmer
2.458
971283AH1-107 GEN
Solar/Wind Harmer
2.458
316486AD2-202 GEN
Solar/Wind Harmer
0.172
315814AE2-033 C
Solar/Wind Harmer
13.198
946301AF1-294 GEN
Solar/Wind Harmer
3.044
961791AG1-021 GEN
Solar/Wind Harmer
1.481
970683AG2-441 GEN
Solar/Wind Harmer
9.252
970681AG2-440 GEN
Solar/Wind Harmer
6.141
971845AH1-439 GEN
Solar/Wind Harmer
6.949
3144303KENBRDG
Solar/Wind Harmer
0.122
3143316POE
Solar/Wind Harmer
0.596
970831AG2-522 GEN
Solar/Wind Harmer
6.326
3137643SOCKMAN
Solar/Wind Harmer
0.588
972205AH1-687 GEN
Adder
6.268
315652AC1-086 GEN
Solar/Wind Harmer
16.055
316426AA2-053 GEN
Solar/Wind Harmer
0.485
3146043SEABORD
Solar/Wind Harmer
0.145
3145796HORNRTN
Solar/Wind Harmer
0.461
3145796HORNRTN
Solar/Wind Harmer
0.058
957871AF2-081 GEN
Solar/Wind Harmer
7.135
3146406KITTY HAWK
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.386
3145893MURPHYS
Solar/Wind Harmer
0.143
316316AC1-027 C
Solar/Wind Harmer
0.136
313526AB2-022
Solar/Wind Harmer
0.076
3145176PASQUOTANK
Solar/Wind Harmer
0.088
3146396TANGLEW
Solar/Wind Harmer
0.393
3151081ELIZAR1
Adder
13.066
3151091ELIZAR2
Adder
12.839
3146486SUNBURY
Solar/Wind Harmer
0.142
3146486SUNBURY
Solar/Wind Harmer
0.142
316463AE2-346 GEN
Solar/Wind Harmer
0.121
3145513AHOSKIE
Solar/Wind Harmer
0.296
3145513AHOSKIE
Solar/Wind Harmer
0.142
316311AC2-079 GEN
Solar/Wind Harmer
4.068
3130156CHOWAN
Solar/Wind Harmer
0.141
3130156CHOWAN
Solar/Wind Harmer
0.141
3145683EARLEYS
Solar/Wind Harmer
0.283
3145683EARLEYS
Solar/Wind Harmer
0.141
3145683EARLEYS
Solar/Wind Harmer
0.141
3146206CASHIE
Solar/Wind Harmer
0.14
970601AG2-382 GEN
Solar/Wind Harmer
5.249
3130546PLYMOUTH
Solar/Wind Harmer
0.14
315732AD1-074 GEN1
Solar/Wind Harmer
0.8
315733AD1-074 GEN2
Solar/Wind Harmer
0.8
970657AG2-426 GEN
Solar/Wind Harmer
1.031
3146033SCOT NK
Solar/Wind Harmer
0.56
316274AC1-208 GEN
Solar/Wind Harmer
0.722
316210AC1-098 GEN
Solar/Wind Harmer
1.291
3147173SINAI
Solar/Wind Harmer
0.138
3147243WELCO
Solar/Wind Harmer
0.086
316327AA2-057 GEN
Solar/Wind Harmer
0.202
3145746EVERETS
Solar/Wind Harmer
0.535
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
957861AF2-080 GEN
Solar/Wind Harmer
5.782
3145573BETHELC
Solar/Wind Harmer
0.134
3145573BETHELC
Solar/Wind Harmer
0.134
971445AH1-216 GEN
Solar/Wind Harmer
9.247
971285AH1-108 GEN
Adder
0.982
3151201GRAVEL4
Adder
9.135
3151221GRAVEL6
Adder
9.124
3151191GRAVEL3
Adder
9.019
3151211GRAVEL5
Adder
9.019
315697AD1-025 GEN
Solar/Wind Harmer
0.128
3152251N ANNA1
50/50
34.934
3151791S ANNAG2
50/50
1.097
3151781S ANNAS1
50/50
0.564
3151741LOISA C
50/50
1.126
3151751LOISA D
50/50
20.59
970119AG2-088 GEN
50/50
29.407
971507AH1-251 GEN
50/50
9.041
315243AE2-183_GT3
50/50
3.256
3151051BRUNSWICKS1
50/50
5.331
3151021BRUNSWICKG1
50/50
2.568
971451AH1-221 GEN
50/50
7.798
316447AC1-158 HLD
Solar/Wind Harmer
7.854
316044AC1-158 PL1
Solar/Wind Harmer
3.572
3147666LOUISA
Solar/Wind Harmer
1.947
316192AB2-158 GEN
Solar/Wind Harmer
2.675
316254AC1-120 GEN1
Solar/Wind Harmer
7.775
316170AC1-121 GEN2
Solar/Wind Harmer
2.67
3143226MDLTHAN
Solar/Wind Harmer
0.22
941031AE2-094 GEN
Solar/Wind Harmer
37.535
940641AE2-051 GEN
Solar/Wind Harmer
15.943
3143336POWHATN
Solar/Wind Harmer
3.397
970919AG2-571 GEN
Solar/Wind Harmer
6.64
939411AE1-173 GEN
Solar/Wind Harmer
79.099
970087AG2-069 GEN
Solar/Wind Harmer
14.716
3143526WINTERP
Solar/Wind Harmer
0.921
957481AF2-042 GEN
Solar/Wind Harmer
47.227
315693AD1-088 GEN
Solar/Wind Harmer
8.321
315683AE1-153 C
Solar/Wind Harmer
13.362
970937AG2-583 GEN
Solar/Wind Harmer
10.029
3146926FARMVIL
Solar/Wind Harmer
0.095
971563AH1-280 GEN
Solar/Wind Harmer
1.645
3144293JTRSVLE
Adder
0.368
3144293JTRSVLE
Adder
0.291
316023GEN1_S
Solar/Wind Harmer
0.342
970685AG2-442 GEN
Solar/Wind Harmer
11.489
3146776BUCKING
Solar/Wind Harmer
0.061
316034AC1-036 C
Solar/Wind Harmer
0.01
315785AD2-033 C
Solar/Wind Harmer
1.232
960081AF2-299 GEN
Solar/Wind Harmer
1.46
3147043LAWRENC
Adder
1.373
316131AB2-060 GEN
Solar/Wind Harmer
0.47
971065AG2-659 GEN
Solar/Wind Harmer
6.35
316129AC1-054 GEN
Solar/Wind Harmer
0.555
315607AA1-063A GEN
Solar/Wind Harmer
0.292
3145783HORNRTN
Solar/Wind Harmer
0.145
944591AF1-124 GEN
Solar/Wind Harmer
32.717
3145796HORNRTN
Solar/Wind Harmer
0.476
3145796HORNRTN
Solar/Wind Harmer
0.144
970401AG2-262 GEN
Solar/Wind Harmer
0.841
3146456SLIGO L269
Solar/Wind Harmer
0.143
319010AE1-072 C
Solar/Wind Harmer
0.714
315773AC2-141 GEN
Solar/Wind Harmer
5.219
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.636
3146263WOODLND
Solar/Wind Harmer
0.142
316093AE2-104_GEN
Solar/Wind Harmer
2.397
3146516WINFALL
Solar/Wind Harmer
0.461
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.025
3150981CHESPKA
Adder
1.775
3130156CHOWAN
Solar/Wind Harmer
0.141
3145683EARLEYS
Solar/Wind Harmer
0.141
315816AE2-034 GEN
Solar/Wind Harmer
0.602
3145663CRESWEL
Solar/Wind Harmer
0.395
971163AH1-040 GEN
Solar/Wind Harmer
11.281
3156021HOLLOMANSOL
Solar/Wind Harmer
0.633
3145823KELFORD
Solar/Wind Harmer
0.141
3146206CASHIE
Solar/Wind Harmer
0.14
971547AH1-271 GEN
Solar/Wind Harmer
2.999
315737AD1-076 GEN
Solar/Wind Harmer
1.802
316381AD1-082 GEN
Solar/Wind Harmer
0.142
3145963POPLR C
Solar/Wind Harmer
0.138
316072AD1-144
Solar/Wind Harmer
0.049
3146293MARTNCO
Solar/Wind Harmer
0.126
3146233WITAKRS
Solar/Wind Harmer
0.538
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
971377AH1-170 GEN
Solar/Wind Harmer
1.433
3147623JAMES R
Solar/Wind Harmer
0.311
316494AC1-189 GEN
Solar/Wind Harmer
0.453
961671AG1-007 GEN
Solar/Wind Harmer
0.02
3146083TARBORO
Solar/Wind Harmer
0.134
3145493TOT1
Solar/Wind Harmer
0.595
3145543BTLEBRO
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.475
3142053HEARTS
Solar/Wind Harmer
0.235
3145336SMITFLD
Solar/Wind Harmer
0.527
3150851SPRUNCC
Adder
0.6
3151171GRAVELC
Adder
1.335
315671AE2-027_GEN
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
6.451
971069AG2-661 GEN
Solar/Wind Harmer
2.09
316132AB2-190 GEN1
Solar/Wind Harmer
0.615
3152261N ANNA2
50/50
34.952
3151771S ANNAG1
50/50
1.097
3151801S ANNAS2
50/50
0.564
3151761LOISA E
50/50
41.976
3151721LOISA A
50/50
20.483
3151031BRUNSWICKG2
50/50
2.568
3147666LOUISA
Solar/Wind Harmer
1.119
3132273ORANGE
Solar/Wind Harmer
0.054
944011AF1-069 GEN
Solar/Wind Harmer
12.264
3143336POWHATN
Solar/Wind Harmer
2.887
970917AG2-570 GEN
Solar/Wind Harmer
16.601
316478AD1-087 GEN
Solar/Wind Harmer
0.585
3146926FARMVIL
Solar/Wind Harmer
0.095
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.486
3144293JTRSVLE
Adder
0.368
959311AF2-222 GEN
Solar/Wind Harmer
13.597
3146776BUCKING
Solar/Wind Harmer
0.055
970257AG2-171 GEN
Solar/Wind Harmer
4.887
971775AH1-396 GEN
Solar/Wind Harmer
0.244
3147043LAWRENC
Solar/Wind Harmer
0.091
964241AG1-285 GEN
Solar/Wind Harmer
10.106
316181AB2-040 GEN
Solar/Wind Harmer
0.212
972003AH1-546 GEN
Solar/Wind Harmer
5.112
316011AB1-132 GEN
Solar/Wind Harmer
2.648
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
944581AF1-123 GEN
Solar/Wind Harmer
32.601
944601AF1-125 GEN
Solar/Wind Harmer
32.099
3145796HORNRTN
Solar/Wind Harmer
0.576
3145796HORNRTN
Solar/Wind Harmer
0.144
3156081AA2-088 GEN
Solar/Wind Harmer
0
316017AA1-139 ULT1
Solar/Wind Harmer
0.076
3146456SLIGO L269
Solar/Wind Harmer
0.143
971153AH1-033 GEN
Solar/Wind Harmer
1.656
3145893MURPHYS
Solar/Wind Harmer
0.239
3145893MURPHYS
Solar/Wind Harmer
0.143
3145273HOLLAND
Solar/Wind Harmer
0.107
316246AF1-032 C
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.025
3146263WOODLND
Solar/Wind Harmer
0.142
3151101ELIZAR3
Adder
13.233
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
3144873MCLAUGH
Solar/Wind Harmer
0.004
3146626S HERTFORD
Solar/Wind Harmer
0.142
3146376EDENTON
Solar/Wind Harmer
0.141
3145823KELFORD
Solar/Wind Harmer
0.141
3146206CASHIE
Solar/Wind Harmer
0.14
315735AD1-075 GEN1
Solar/Wind Harmer
0.4
970657AG2-426 GEN
Solar/Wind Harmer
3.151
316212AC1-099_GEN
Solar/Wind Harmer
0.72
315813AE1-149 C
Solar/Wind Harmer
7.437
3144536CHRHLND
Solar/Wind Harmer
0.021
315722AD1-056 GEN
Solar/Wind Harmer
4.782
3145963POPLR C
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.135
3146233WITAKRS
Solar/Wind Harmer
0.679
3146233WITAKRS
Solar/Wind Harmer
0.092
3138543CONSLDL
Solar/Wind Harmer
0.089
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
970221AG2-151 GEN
Solar/Wind Harmer
7.164
3146073TAR RVR
Solar/Wind Harmer
0.134
3146083TARBORO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.133
971623AH1-311 GEN
Solar/Wind Harmer
0.267
961601AG1-000A GEN
Solar/Wind Harmer
9.496
3145336SMITFLD
Solar/Wind Harmer
0.053
3150861SPRUNCD
Adder
0.6
3151171GRAVELC
Adder
1.755
971683AH1-343 GEN
Solar/Wind Harmer
4.545
961611AG1-000B GEN
Solar/Wind Harmer
3.28
316222AC1-221 GEN
Solar/Wind Harmer
0.505
316283AC2-100 C
Solar/Wind Harmer
0.239
315778AD1-151 GEN
Solar/Wind Harmer
9.403
316458AB2-190 GEN2
Solar/Wind Harmer
0.615
270494AE1-108_GEN
Solar/Wind Harmer
1.361
3151731LOISA B
50/50
20.59
315242AE2-183_GT2
50/50
3.256
315241AE2-183_GT1
50/50
3.248
972185AH1-677 GEN
50/50
11.771
3151041BRUNSWICKG3
50/50
2.568
972187AH1-678 GEN
50/50
5.892
316045AC1-158 PL2
Solar/Wind Harmer
11.43
316450AC1-158 RIC
Solar/Wind Harmer
0.953
966001AG1-469 GEN
Solar/Wind Harmer
0.166
971223AH1-071 GEN
Solar/Wind Harmer
2.353
970933AG2-581 GEN
Solar/Wind Harmer
15.313
316313AB2-026
Solar/Wind Harmer
0.119
316336AC2-165 C
Solar/Wind Harmer
9.289
3143526WINTERP
Solar/Wind Harmer
0.921
970099AG2-077 GEN
Solar/Wind Harmer
18.891
3144356SAPONY
Solar/Wind Harmer
1.401
316315AB2-025 C
Solar/Wind Harmer
0.134
970301AG2-198 GEN
Solar/Wind Harmer
7.017
3147133PAMPLIN
Solar/Wind Harmer
0.155
3147133PAMPLIN
Solar/Wind Harmer
0.124
958211AF2-115 GEN
Solar/Wind Harmer
1.851
3144293JTRSVLE
Adder
0.368
316365GEN2_N
Solar/Wind Harmer
0.342
3146776BUCKING
Solar/Wind Harmer
0.611
3146776BUCKING
Solar/Wind Harmer
0.049
970323AG2-213 GEN
Solar/Wind Harmer
6.516
313506AB2-031 GEN
Solar/Wind Harmer
0.457
962571AG1-106 GEN
Solar/Wind Harmer
2.077
3145593CAROLNA
Solar/Wind Harmer
0.146
3145593CAROLNA
Solar/Wind Harmer
0.146
3145593CAROLNA
Solar/Wind Harmer
0.182
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
2.576
3145783HORNRTN
Solar/Wind Harmer
2.061
3145783HORNRTN
Solar/Wind Harmer
0.644
3145783HORNRTN
Solar/Wind Harmer
0.258
962561AG1-105 GEN
Solar/Wind Harmer
6.939
3145796HORNRTN
Solar/Wind Harmer
0.432
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.344
3145506HICKORY
Solar/Wind Harmer
0.086
964791AG1-342 GEN
Solar/Wind Harmer
2.753
316339AD2-160 GEN
Solar/Wind Harmer
0.229
316388AE2-253 GEN
Solar/Wind Harmer
0.446
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
3137176SLIGO L2192
Solar/Wind Harmer
0.57
3146456SLIGO L269
Solar/Wind Harmer
2.534
3130086AYDLETT
Solar/Wind Harmer
0.572
316294AC1-161 GEN
Solar/Wind Harmer
2.47
315742AE1-103 GEN
Solar/Wind Harmer
2.136
3145893MURPHYS
Solar/Wind Harmer
0.957
3145893MURPHYS
Solar/Wind Harmer
0.257
3146386ELIZ CT
Solar/Wind Harmer
0.143
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3146516WINFALL
Solar/Wind Harmer
0.142
3146516WINFALL
Solar/Wind Harmer
0.142
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
3150991CHESPKB
Adder
1.489
3150991CHESPKB
Adder
1.454
3146626S HERTFORD
Solar/Wind Harmer
0.142
3146626S HERTFORD
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.05
316349AD2-085 GEN
Solar/Wind Harmer
0.094
3146376EDENTON
Solar/Wind Harmer
0.629
3146376EDENTON
Solar/Wind Harmer
0.629
315614AA2-178 GEN
Solar/Wind Harmer
0.802
316118AC1-105 GEN
Solar/Wind Harmer
0.36
316065AD1-022 GEN
Solar/Wind Harmer
6.471
315724AD1-057 GEN
Solar/Wind Harmer
2.667
3145933PARMELE
Solar/Wind Harmer
0.271
3145933PARMELE
Solar/Wind Harmer
0.135
316005AA1-067
Solar/Wind Harmer
0.143
3145493TOT1
Solar/Wind Harmer
0.31
3145453TOT5
Solar/Wind Harmer
0.186
3145603CNETO
Solar/Wind Harmer
0.124
316049AB1-081 GEN
Solar/Wind Harmer
0.76
316263AC1-034 GEN
Solar/Wind Harmer
5.076
961601AG1-000A GEN
Solar/Wind Harmer
2.374
316033AB2-134 GEN
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
56.025
LAGNLTFEXP_LAGN->PJM
CLTF
5.697
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.483
TVALTFEXP_TVA->PJM
CLTF
2.867
CPLELTFEXP_CPLE->PJM
CLTF
9.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.276
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.616
MECLTFEXP_MEC->PJM
CLTF
2.307
SIGELTFEXP_SIGE->PJM
CLTF
0.069
NYPJM->LTFIMP_NY
CLTF
2.593
LGEELTFEXP_LGEE->PJM
CLTF
0.8
WECLTFEXP_WEC->PJM
CLTF
0.383

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.17 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4159.96
MW Contribution:
5.23
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.112
315244AE2-183_ST
50/50
5.937
963041AG1-153 GEN
50/50
5.459
3147346CASHSCORNER
Solar/Wind Harmer
0.596
970533AG2-339 GEN
Solar/Wind Harmer
16.166
970673AG2-436 GEN
Solar/Wind Harmer
26.311
971967AH1-528 GEN
Solar/Wind Harmer
32.887
316258AE1-075 C
Solar/Wind Harmer
0.148
970085AG2-068 GEN
Solar/Wind Harmer
10.306
970581AG2-369 GEN
Solar/Wind Harmer
8.863
316233AE1-074 FULL
Solar/Wind Harmer
0.15
971281AH1-106 GEN
Solar/Wind Harmer
2.599
971283AH1-107 GEN
Solar/Wind Harmer
2.599
316486AD2-202 GEN
Solar/Wind Harmer
0.18
315814AE2-033 C
Solar/Wind Harmer
13.952
946301AF1-294 GEN
Solar/Wind Harmer
3.173
961791AG1-021 GEN
Solar/Wind Harmer
1.544
3143316POE
Solar/Wind Harmer
0.634
970683AG2-441 GEN
Solar/Wind Harmer
9.656
970681AG2-440 GEN
Solar/Wind Harmer
6.409
3144303KENBRDG
Solar/Wind Harmer
0.128
971845AH1-439 GEN
Solar/Wind Harmer
7.159
970831AG2-522 GEN
Solar/Wind Harmer
6.664
3137643SOCKMAN
Solar/Wind Harmer
0.622
315652AC1-086 GEN
Solar/Wind Harmer
16.984
316426AA2-053 GEN
Solar/Wind Harmer
0.513
3146043SEABORD
Solar/Wind Harmer
0.153
957871AF2-081 GEN
Solar/Wind Harmer
7.605
3146406KITTY HAWK
Solar/Wind Harmer
0.019
3145796HORNRTN
Solar/Wind Harmer
0.488
3145796HORNRTN
Solar/Wind Harmer
0.061
316316AC1-027 C
Solar/Wind Harmer
0.145
313526AB2-022
Solar/Wind Harmer
0.081
3151081ELIZAR1
Adder
13.938
3151091ELIZAR2
Adder
13.695
3146396TANGLEW
Solar/Wind Harmer
0.419
3145176PASQUOTANK
Solar/Wind Harmer
0.094
3146486SUNBURY
Solar/Wind Harmer
0.152
3146486SUNBURY
Solar/Wind Harmer
0.152
3145893MURPHYS
Solar/Wind Harmer
0.409
3145893MURPHYS
Solar/Wind Harmer
0.152
316311AC2-079 GEN
Solar/Wind Harmer
4.338
3130156CHOWAN
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
316463AE2-346 GEN
Solar/Wind Harmer
0.128
3145513AHOSKIE
Solar/Wind Harmer
0.314
3145513AHOSKIE
Solar/Wind Harmer
0.15
972205AH1-687 GEN
Adder
6.406
3145683EARLEYS
Solar/Wind Harmer
0.3
3145683EARLEYS
Solar/Wind Harmer
0.15
3145683EARLEYS
Solar/Wind Harmer
0.15
970657AG2-426 GEN
Solar/Wind Harmer
1.101
3130546PLYMOUTH
Solar/Wind Harmer
0.149
3146206CASHIE
Solar/Wind Harmer
0.149
970601AG2-382 GEN
Solar/Wind Harmer
5.572
315732AD1-074 GEN1
Solar/Wind Harmer
0.85
315733AD1-074 GEN2
Solar/Wind Harmer
0.85
3146033SCOT NK
Solar/Wind Harmer
0.593
316274AC1-208 GEN
Solar/Wind Harmer
0.763
316210AC1-098 GEN
Solar/Wind Harmer
1.366
3147173SINAI
Solar/Wind Harmer
0.145
3147243WELCO
Solar/Wind Harmer
0.091
316327AA2-057 GEN
Solar/Wind Harmer
0.214
3145746EVERETS
Solar/Wind Harmer
0.566
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
957861AF2-080 GEN
Solar/Wind Harmer
6.121
3145573BETHELC
Solar/Wind Harmer
0.142
3152261N ANNA2
50/50
36.017
3151771S ANNAG1
50/50
1.039
3151801S ANNAS2
50/50
0.534
3151761LOISA E
50/50
39.48
3151721LOISA A
50/50
19.265
3151031BRUNSWICKG2
50/50
2.696
3147666LOUISA
Solar/Wind Harmer
1.117
944011AF1-069 GEN
Solar/Wind Harmer
12.876
3143336POWHATN
Solar/Wind Harmer
3.004
970917AG2-570 GEN
Solar/Wind Harmer
17.437
316478AD1-087 GEN
Solar/Wind Harmer
0.614
3146926FARMVIL
Solar/Wind Harmer
0.098
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.506
3144293JTRSVLE
Adder
0.384
3147043LAWRENC
Solar/Wind Harmer
0.096
959311AF2-222 GEN
Solar/Wind Harmer
14.204
970257AG2-171 GEN
Solar/Wind Harmer
5.108
971775AH1-396 GEN
Solar/Wind Harmer
0.255
964241AG1-285 GEN
Solar/Wind Harmer
10.584
316181AB2-040 GEN
Solar/Wind Harmer
0.224
3146776BUCKING
Solar/Wind Harmer
0.057
316011AB1-132 GEN
Solar/Wind Harmer
2.801
944581AF1-123 GEN
Solar/Wind Harmer
34.751
944601AF1-125 GEN
Solar/Wind Harmer
34.216
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3132273ORANGE
Solar/Wind Harmer
0.031
316017AA1-139 ULT1
Solar/Wind Harmer
0.081
3146456SLIGO L269
Solar/Wind Harmer
0.153
971153AH1-033 GEN
Solar/Wind Harmer
1.765
3145796HORNRTN
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.152
3156081AA2-088 GEN
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.068
3151101ELIZAR3
Adder
14.116
3145273HOLLAND
Solar/Wind Harmer
0.114
316321Z2-027
Solar/Wind Harmer
0.027
3144873MCLAUGH
Solar/Wind Harmer
0.004
3145893MURPHYS
Solar/Wind Harmer
0.254
3145893MURPHYS
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146263WOODLND
Solar/Wind Harmer
0.151
972003AH1-546 GEN
Solar/Wind Harmer
5.229
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.151
970657AG2-426 GEN
Solar/Wind Harmer
3.363
3146206CASHIE
Solar/Wind Harmer
0.149
315735AD1-075 GEN1
Solar/Wind Harmer
0.424
3145823KELFORD
Solar/Wind Harmer
0.149
315813AE1-149 C
Solar/Wind Harmer
7.943
3144536CHRHLND
Solar/Wind Harmer
0.022
316212AC1-099_GEN
Solar/Wind Harmer
0.762
315722AD1-056 GEN
Solar/Wind Harmer
5.057
3145963POPLR C
Solar/Wind Harmer
0.146
3145933PARMELE
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
0.718
3146233WITAKRS
Solar/Wind Harmer
0.097
3152251N ANNA1
50/50
35.999
3151791S ANNAG2
50/50
1.039
3151781S ANNAS1
50/50
0.534
3151741LOISA C
50/50
1.059
3151751LOISA D
50/50
19.365
970119AG2-088 GEN
50/50
30.842
315243AE2-183_GT3
50/50
3.419
3151051BRUNSWICKS1
50/50
5.598
3151021BRUNSWICKG1
50/50
2.696
971451AH1-221 GEN
50/50
8.188
3147666LOUISA
Solar/Wind Harmer
1.942
316192AB2-158 GEN
Solar/Wind Harmer
2.664
3143226MDLTHAN
Solar/Wind Harmer
0.231
941031AE2-094 GEN
Solar/Wind Harmer
39.408
940641AE2-051 GEN
Solar/Wind Harmer
16.774
3143336POWHATN
Solar/Wind Harmer
3.535
970919AG2-571 GEN
Solar/Wind Harmer
6.975
939411AE1-173 GEN
Solar/Wind Harmer
83.435
970087AG2-069 GEN
Solar/Wind Harmer
15.459
3143526WINTERP
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
49.523
315693AD1-088 GEN
Solar/Wind Harmer
8.714
970937AG2-583 GEN
Solar/Wind Harmer
10.332
3146926FARMVIL
Solar/Wind Harmer
0.098
316023GEN1_S
Solar/Wind Harmer
0.362
971563AH1-280 GEN
Solar/Wind Harmer
1.715
3144293JTRSVLE
Adder
0.384
3144293JTRSVLE
Adder
0.303
960081AF2-299 GEN
Solar/Wind Harmer
1.542
970685AG2-442 GEN
Solar/Wind Harmer
11.983
3147043LAWRENC
Adder
1.447
316034AC1-036 C
Solar/Wind Harmer
0.011
315785AD2-033 C
Solar/Wind Harmer
1.289
316131AB2-060 GEN
Solar/Wind Harmer
0.493
3146776BUCKING
Solar/Wind Harmer
0.063
971065AG2-659 GEN
Solar/Wind Harmer
6.684
316129AC1-054 GEN
Solar/Wind Harmer
0.584
944591AF1-124 GEN
Solar/Wind Harmer
34.874
315607AA1-063A GEN
Solar/Wind Harmer
0.309
3145783HORNRTN
Solar/Wind Harmer
0.153
315773AC2-141 GEN
Solar/Wind Harmer
5.569
3146456SLIGO L269
Solar/Wind Harmer
0.153
319010AE1-072 C
Solar/Wind Harmer
0.761
3145796HORNRTN
Solar/Wind Harmer
0.503
3145796HORNRTN
Solar/Wind Harmer
0.152
315683AE1-153 C
Solar/Wind Harmer
12.097
316093AE2-104_GEN
Solar/Wind Harmer
2.554
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.027
3150981CHESPKA
Adder
1.894
3145893MURPHYS
Solar/Wind Harmer
0.606
3145893MURPHYS
Solar/Wind Harmer
0.674
3146516WINFALL
Solar/Wind Harmer
0.491
3146516WINFALL
Solar/Wind Harmer
0.152
3146263WOODLND
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
970401AG2-262 GEN
Solar/Wind Harmer
0.883
3145683EARLEYS
Solar/Wind Harmer
0.15
315816AE2-034 GEN
Solar/Wind Harmer
0.64
3145663CRESWEL
Solar/Wind Harmer
0.419
971163AH1-040 GEN
Solar/Wind Harmer
11.992
316381AD1-082 GEN
Solar/Wind Harmer
0.152
3156021HOLLOMANSOL
Solar/Wind Harmer
0.672
3146206CASHIE
Solar/Wind Harmer
0.149
971547AH1-271 GEN
Solar/Wind Harmer
3.184
315737AD1-076 GEN
Solar/Wind Harmer
1.914
3145823KELFORD
Solar/Wind Harmer
0.149
316072AD1-144
Solar/Wind Harmer
0.052
3145963POPLR C
Solar/Wind Harmer
0.146
3146293MARTNCO
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
0.569
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
316494AC1-189 GEN
Solar/Wind Harmer
0.48
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.142
3145493TOT1
Solar/Wind Harmer
0.629
3145336SMITFLD
Solar/Wind Harmer
0.565
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.502
3142053HEARTS
Solar/Wind Harmer
0.249
3150851SPRUNCC
Adder
0.644
971377AH1-170 GEN
Solar/Wind Harmer
1.464
3147623JAMES R
Solar/Wind Harmer
0.318
3151171GRAVELC
Adder
1.434
315671AE2-027_GEN
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
6.938
971069AG2-661 GEN
Solar/Wind Harmer
2.254
316132AB2-190 GEN1
Solar/Wind Harmer
0.664
3138126ROCKLANDING
Solar/Wind Harmer
0.055
3142543TWELFTH
Solar/Wind Harmer
0.011
3145573BETHELC
Solar/Wind Harmer
0.142
971445AH1-216 GEN
Solar/Wind Harmer
9.907
971285AH1-108 GEN
Adder
1.054
3151201GRAVEL4
Adder
9.812
3151221GRAVEL6
Adder
9.801
3151191GRAVEL3
Adder
9.688
3151211GRAVEL5
Adder
9.688
315697AD1-025 GEN
Solar/Wind Harmer
0.138
3138543CONSLDL
Solar/Wind Harmer
0.094
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
3146073TAR RVR
Solar/Wind Harmer
0.142
3146083TARBORO
Solar/Wind Harmer
0.142
3145336SMITFLD
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.282
961601AG1-000A GEN
Solar/Wind Harmer
10.04
3150861SPRUNCD
Adder
0.644
970221AG2-151 GEN
Solar/Wind Harmer
7.32
3151171GRAVELC
Adder
1.886
961611AG1-000B GEN
Solar/Wind Harmer
3.528
971683AH1-343 GEN
Solar/Wind Harmer
4.779
316222AC1-221 GEN
Solar/Wind Harmer
0.532
316283AC2-100 C
Solar/Wind Harmer
0.251
315778AD1-151 GEN
Solar/Wind Harmer
10.143
316458AB2-190 GEN2
Solar/Wind Harmer
0.664
3144216WINCHST
Adder
0.455
970133AG2-095 GEN
Solar/Wind Harmer
1.156
3150921YORKTN3
Adder
2.975
270494AE1-108_GEN
Solar/Wind Harmer
1.396
316123AC1-075 GEN
Solar/Wind Harmer
0.15
3151731LOISA B
50/50
19.365
315242AE2-183_GT2
50/50
3.419
315241AE2-183_GT1
50/50
3.41
972185AH1-677 GEN
50/50
12.359
3151041BRUNSWICKG3
50/50
2.696
972187AH1-678 GEN
50/50
6.186
966001AG1-469 GEN
Solar/Wind Harmer
0.142
971223AH1-071 GEN
Solar/Wind Harmer
2.467
970933AG2-581 GEN
Solar/Wind Harmer
16.069
316313AB2-026
Solar/Wind Harmer
0.124
316336AC2-165 C
Solar/Wind Harmer
9.642
3143526WINTERP
Solar/Wind Harmer
0.974
970099AG2-077 GEN
Solar/Wind Harmer
19.809
3144356SAPONY
Solar/Wind Harmer
1.481
316315AB2-025 C
Solar/Wind Harmer
0.142
970301AG2-198 GEN
Solar/Wind Harmer
7.304
316365GEN2_N
Solar/Wind Harmer
0.362
3147133PAMPLIN
Solar/Wind Harmer
0.161
3147133PAMPLIN
Solar/Wind Harmer
0.129
958211AF2-115 GEN
Solar/Wind Harmer
1.929
3144293JTRSVLE
Adder
0.384
970323AG2-213 GEN
Solar/Wind Harmer
6.811
313506AB2-031 GEN
Solar/Wind Harmer
0.483
3146776BUCKING
Solar/Wind Harmer
0.629
3146776BUCKING
Solar/Wind Harmer
0.051
962571AG1-106 GEN
Solar/Wind Harmer
2.197
3145593CAROLNA
Solar/Wind Harmer
0.154
3145593CAROLNA
Solar/Wind Harmer
0.154
3145593CAROLNA
Solar/Wind Harmer
0.192
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.092
3145783HORNRTN
Solar/Wind Harmer
2.724
3145783HORNRTN
Solar/Wind Harmer
2.179
3145783HORNRTN
Solar/Wind Harmer
0.681
3145783HORNRTN
Solar/Wind Harmer
0.272
3145506HICKORY
Solar/Wind Harmer
0.612
3145506HICKORY
Solar/Wind Harmer
0.367
3145506HICKORY
Solar/Wind Harmer
0.092
316339AD2-160 GEN
Solar/Wind Harmer
0.245
316388AE2-253 GEN
Solar/Wind Harmer
0.475
316294AC1-161 GEN
Solar/Wind Harmer
2.636
3137176SLIGO L2192
Solar/Wind Harmer
0.607
3146456SLIGO L269
Solar/Wind Harmer
2.701
3130086AYDLETT
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.457
3146386ELIZ CT
Solar/Wind Harmer
0.152
315742AE1-103 GEN
Solar/Wind Harmer
2.272
315835AF2-110_GEN
Solar/Wind Harmer
1.042
3150991CHESPKB
Adder
1.589
3150991CHESPKB
Adder
1.551
962561AG1-105 GEN
Solar/Wind Harmer
7.282
3145893MURPHYS
Solar/Wind Harmer
1.015
3145893MURPHYS
Solar/Wind Harmer
0.273
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146626S HERTFORD
Solar/Wind Harmer
0.151
316349AD2-085 GEN
Solar/Wind Harmer
0.101
3146173TUNIS
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.67
3146376EDENTON
Solar/Wind Harmer
0.67
964791AG1-342 GEN
Solar/Wind Harmer
2.89
3146843MT LREL
Solar/Wind Harmer
0.15
3146843MT LREL
Solar/Wind Harmer
0.15
316140AB2-099
Solar/Wind Harmer
0.053
315614AA2-178 GEN
Solar/Wind Harmer
0.853
316065AD1-022 GEN
Solar/Wind Harmer
6.871
316118AC1-105 GEN
Solar/Wind Harmer
0.378
315724AD1-057 GEN
Solar/Wind Harmer
2.821
3145933PARMELE
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.143
316005AA1-067
Solar/Wind Harmer
0.152
3145493TOT1
Solar/Wind Harmer
0.328
3145453TOT5
Solar/Wind Harmer
0.197
3145603CNETO
Solar/Wind Harmer
0.131
316049AB1-081 GEN
Solar/Wind Harmer
0.803
316263AC1-034 GEN
Solar/Wind Harmer
5.367
961601AG1-000A GEN
Solar/Wind Harmer
2.51
316033AB2-134 GEN
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
60.459
LAGNLTFEXP_LAGN->PJM
CLTF
6.161
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.649
TVALTFEXP_TVA->PJM
CLTF
3.1
CPLELTFEXP_CPLE->PJM
CLTF
9.626
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.951
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.438
MECLTFEXP_MEC->PJM
CLTF
2.59
SIGELTFEXP_SIGE->PJM
CLTF
0.077
NYPJM->LTFIMP_NY
CLTF
2.604
LGEELTFEXP_LGEE->PJM
CLTF
0.909
WECLTFEXP_WEC->PJM
CLTF
0.442

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.53 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4906.62
MW Contribution:
6.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.094
315244AE2-183_ST
50/50
5.906
963041AG1-153 GEN
50/50
5.43
3147346CASHSCORNER
Solar/Wind Harmer
0.448
970533AG2-339 GEN
Solar/Wind Harmer
16.085
970673AG2-436 GEN
Solar/Wind Harmer
51.699
971967AH1-528 GEN
Solar/Wind Harmer
43.187
316258AE1-075 C
Solar/Wind Harmer
0.538
316405AF2-144 C
Solar/Wind Harmer
0.568
970085AG2-068 GEN
Solar/Wind Harmer
13.492
970581AG2-369 GEN
Solar/Wind Harmer
11.603
316233AE1-074 FULL
Solar/Wind Harmer
0.563
971281AH1-106 GEN
Solar/Wind Harmer
3.403
971283AH1-107 GEN
Solar/Wind Harmer
3.403
316486AD2-202 GEN
Solar/Wind Harmer
0.5
315814AE2-033 C
Solar/Wind Harmer
18.34
946301AF1-294 GEN
Solar/Wind Harmer
4.599
961791AG1-021 GEN
Solar/Wind Harmer
2.243
946281AF1-292 GEN
Solar/Wind Harmer
0.401
3143316POE
Solar/Wind Harmer
-0.07
970683AG2-441 GEN
Solar/Wind Harmer
12.629
970681AG2-440 GEN
Solar/Wind Harmer
8.382
3144303KENBRDG
Solar/Wind Harmer
-0.014
971845AH1-439 GEN
Solar/Wind Harmer
9.369
316238AB2-078_GEN
Solar/Wind Harmer
0.529
316239AB2-077_GEN
Solar/Wind Harmer
0.529
316322AB2-045
Solar/Wind Harmer
0.59
970831AG2-522 GEN
Solar/Wind Harmer
8.711
3137643SOCKMAN
Solar/Wind Harmer
-0.069
315652AC1-086 GEN
Solar/Wind Harmer
19.382
316426AA2-053 GEN
Solar/Wind Harmer
1.724
3146043SEABORD
Solar/Wind Harmer
-0.017
316018AA1-139 ULT2
Solar/Wind Harmer
1.456
957871AF2-081 GEN
Solar/Wind Harmer
8.522
3146406KITTY HAWK
Solar/Wind Harmer
0.014
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.007
316316AC1-027 C
Solar/Wind Harmer
0.521
313526AB2-022
Solar/Wind Harmer
0.457
3151081ELIZAR1
Adder
13.839
3151091ELIZAR2
Adder
13.599
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3146396TANGLEW
Solar/Wind Harmer
0.312
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
316318V4-068
Solar/Wind Harmer
0.421
3145893MURPHYS
Solar/Wind Harmer
-0.045
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.5
315833AF1-017_GEN
Solar/Wind Harmer
3.2
315800Z1-036_GEN1
Solar/Wind Harmer
4.156
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
316463AE2-346 GEN
Solar/Wind Harmer
0.271
3145513AHOSKIE
Solar/Wind Harmer
0.146
961941AG1-037 GEN
Solar/Wind Harmer
0.126
3145513AHOSKIE
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
6.367
970657AG2-426 GEN
Solar/Wind Harmer
1.054
3145683EARLEYS
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.282
315732AD1-074 GEN1
Solar/Wind Harmer
3.358
315733AD1-074 GEN2
Solar/Wind Harmer
3.358
3146033SCOT NK
Solar/Wind Harmer
-0.066
316274AC1-208 GEN
Solar/Wind Harmer
1.776
316210AC1-098 GEN
Solar/Wind Harmer
2.58
316174AB2-169 GEN
Solar/Wind Harmer
2.5
3147173SINAI
Solar/Wind Harmer
-0.016
3147243WELCO
Solar/Wind Harmer
-0.01
316327AA2-057 GEN
Solar/Wind Harmer
1.626
3145746EVERETS
Solar/Wind Harmer
-0.063
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
315839AE2-212 C
Solar/Wind Harmer
0.477
957861AF2-080 GEN
Solar/Wind Harmer
6.923
3145573BETHELC
Solar/Wind Harmer
-0.016
3145573BETHELC
Solar/Wind Harmer
-0.016
316236AE1-162_GEN
Solar/Wind Harmer
0.474
971445AH1-216 GEN
Solar/Wind Harmer
9.708
971285AH1-108 GEN
Adder
1.046
3151201GRAVEL4
Adder
9.734
3151221GRAVEL6
Adder
9.723
3151191GRAVEL3
Adder
9.611
3151211GRAVEL5
Adder
9.611
315697AD1-025 GEN
Solar/Wind Harmer
2.886
3152261N ANNA2
50/50
35.976
3151771S ANNAG1
50/50
1.041
3151801S ANNAS2
50/50
0.535
3151761LOISA E
50/50
39.556
3151721LOISA A
50/50
19.302
3151031BRUNSWICKG2
50/50
2.682
3147666LOUISA
Solar/Wind Harmer
-0.125
944011AF1-069 GEN
Solar/Wind Harmer
14.053
3143336POWHATN
Solar/Wind Harmer
2.242
970917AG2-570 GEN
Solar/Wind Harmer
54.791
316478AD1-087 GEN
Solar/Wind Harmer
1.709
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.724
3132273ORANGE
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.056
3144293JTRSVLE
Adder
0.381
966621AG1-532 GEN
Solar/Wind Harmer
0.364
3147043LAWRENC
Solar/Wind Harmer
-0.011
959311AF2-222 GEN
Solar/Wind Harmer
18.614
970257AG2-171 GEN
Solar/Wind Harmer
6.68
971775AH1-396 GEN
Solar/Wind Harmer
1.257
964241AG1-285 GEN
Solar/Wind Harmer
13.84
316181AB2-040 GEN
Solar/Wind Harmer
2.448
3146776BUCKING
Solar/Wind Harmer
-0.006
316011AB1-132 GEN
Solar/Wind Harmer
3.598
944581AF1-123 GEN
Solar/Wind Harmer
78.336
944601AF1-125 GEN
Solar/Wind Harmer
77.114
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316190AA2-174 GEN
Solar/Wind Harmer
0.21
316017AA1-139 ULT1
Solar/Wind Harmer
1.375
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
1.971
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
3142956BIRDNECK
Solar/Wind Harmer
0.912
3156081AA2-088 GEN
Solar/Wind Harmer
5.515
316320Y1-086
Solar/Wind Harmer
0.994
316305AF2-043 C
Solar/Wind Harmer
0.51
316246AF1-032 C
Solar/Wind Harmer
0.342
3151101ELIZAR3
Adder
14.016
3145273HOLLAND
Solar/Wind Harmer
-0.013
316321Z2-027
Solar/Wind Harmer
0.456
3144873MCLAUGH
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146263WOODLND
Solar/Wind Harmer
-0.017
972003AH1-546 GEN
Solar/Wind Harmer
6.843
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
970657AG2-426 GEN
Solar/Wind Harmer
3.378
3146206CASHIE
Solar/Wind Harmer
-0.017
315735AD1-075 GEN1
Solar/Wind Harmer
1.678
316317KELFORD C
Solar/Wind Harmer
0.77
3145823KELFORD
Solar/Wind Harmer
-0.017
315813AE1-149 C
Solar/Wind Harmer
10.383
3144536CHRHLND
Solar/Wind Harmer
-0.003
316212AC1-099_GEN
Solar/Wind Harmer
1.433
315722AD1-056 GEN
Solar/Wind Harmer
5.804
3145963POPLR C
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.016
3146233WITAKRS
Solar/Wind Harmer
0.334
3146233WITAKRS
Solar/Wind Harmer
-0.011
3138543CONSLDL
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
316420AA1-050 GEN
Solar/Wind Harmer
1.8
3146073TAR RVR
Solar/Wind Harmer
-0.016
3146083TARBORO
Solar/Wind Harmer
-0.016
3145336SMITFLD
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.016
961601AG1-000A GEN
Solar/Wind Harmer
6.263
3150861SPRUNCD
Adder
0.639
316003AC1-222 GEN
Solar/Wind Harmer
1.496
970221AG2-151 GEN
Solar/Wind Harmer
9.571
3151171GRAVELC
Adder
1.871
961611AG1-000B GEN
Solar/Wind Harmer
3.105
971683AH1-343 GEN
Solar/Wind Harmer
6.236
316222AC1-221 GEN
Solar/Wind Harmer
1.452
316283AC2-100 C
Solar/Wind Harmer
1.347
315778AD1-151 GEN
Solar/Wind Harmer
12.571
3144216WINCHST
Adder
0.451
3150921YORKTN3
Adder
2.948
316458AB2-190 GEN2
Solar/Wind Harmer
0.196
3151731LOISA B
50/50
19.402
315242AE2-183_GT2
50/50
3.401
315241AE2-183_GT1
50/50
3.392
972185AH1-677 GEN
50/50
12.295
3151041BRUNSWICKG3
50/50
2.682
972187AH1-678 GEN
50/50
6.153
316045AC1-158 PL2
Solar/Wind Harmer
27.473
316450AC1-158 RIC
Solar/Wind Harmer
2.289
966001AG1-469 GEN
Solar/Wind Harmer
0.522
971223AH1-071 GEN
Solar/Wind Harmer
3.234
970933AG2-581 GEN
Solar/Wind Harmer
21.043
316313AB2-026
Solar/Wind Harmer
0.598
316336AC2-165 C
Solar/Wind Harmer
13.283
3143526WINTERP
Solar/Wind Harmer
-0.108
970099AG2-077 GEN
Solar/Wind Harmer
25.929
3144356SAPONY
Solar/Wind Harmer
0.69
316315AB2-025 C
Solar/Wind Harmer
0.532
970301AG2-198 GEN
Solar/Wind Harmer
9.559
315687AD1-152 GEN
Solar/Wind Harmer
2.214
316365GEN2_N
Solar/Wind Harmer
1.221
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.804
3144293JTRSVLE
Adder
0.381
970323AG2-213 GEN
Solar/Wind Harmer
8.907
313527AB2-043 GEN
Solar/Wind Harmer
2.867
316237AB2-079_GEN
Solar/Wind Harmer
0.529
313506AB2-031 GEN
Solar/Wind Harmer
1.409
3146776BUCKING
Solar/Wind Harmer
-0.07
3146776BUCKING
Solar/Wind Harmer
-0.006
962571AG1-106 GEN
Solar/Wind Harmer
2.477
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
0.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145783HORNRTN
Solar/Wind Harmer
2.028
3145783HORNRTN
Solar/Wind Harmer
1.622
3145783HORNRTN
Solar/Wind Harmer
0.507
3145783HORNRTN
Solar/Wind Harmer
0.203
316185AD1-033 GEN
Solar/Wind Harmer
1.796
3145506HICKORY
Solar/Wind Harmer
-0.068
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.147
316388AE2-253 GEN
Solar/Wind Harmer
1.147
316294AC1-161 GEN
Solar/Wind Harmer
5.504
3137176SLIGO L2192
Solar/Wind Harmer
-0.067
3146456SLIGO L269
Solar/Wind Harmer
2.011
3130086AYDLETT
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.051
3146386ELIZ CT
Solar/Wind Harmer
-0.017
315742AE1-103 GEN
Solar/Wind Harmer
4.028
315835AF2-110_GEN
Solar/Wind Harmer
2.118
3150991CHESPKB
Adder
1.578
3150991CHESPKB
Adder
1.54
316431W1029_GEN1
Solar/Wind Harmer
3.065
316433W1029_GEN2
Solar/Wind Harmer
3.065
316435W1029_GEN3
Solar/Wind Harmer
3.065
962561AG1-105 GEN
Solar/Wind Harmer
9.517
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.472
3145893MURPHYS
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
316349AD2-085 GEN
Solar/Wind Harmer
1.496
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
0.499
3146376EDENTON
Solar/Wind Harmer
0.499
964791AG1-342 GEN
Solar/Wind Harmer
3.586
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
316140AB2-099
Solar/Wind Harmer
0.113
315614AA2-178 GEN
Solar/Wind Harmer
1.799
316083AB2-161 GEN
Solar/Wind Harmer
2.709
316065AD1-022 GEN
Solar/Wind Harmer
8.321
316118AC1-105 GEN
Solar/Wind Harmer
1.129
315724AD1-057 GEN
Solar/Wind Harmer
3.192
316248AF1-058 C
Solar/Wind Harmer
0.486
3145933PARMELE
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.016
316005AA1-067
Solar/Wind Harmer
0.32
3145493TOT1
Solar/Wind Harmer
0.244
3145453TOT5
Solar/Wind Harmer
0.146
3145603CNETO
Solar/Wind Harmer
0.098
316049AB1-081 GEN
Solar/Wind Harmer
1.693
316263AC1-034 GEN
Solar/Wind Harmer
7.377
961601AG1-000A GEN
Solar/Wind Harmer
6.184
316240AF1-291 C
Solar/Wind Harmer
0.438
316033AB2-134 GEN
Solar/Wind Harmer
4.605
944641AF1-129 GEN
Adder
59.951
3152251N ANNA1
50/50
35.957
3151791S ANNAG2
50/50
1.041
3151781S ANNAS1
50/50
0.535
3151741LOISA C
50/50
1.061
3151751LOISA D
50/50
19.402
970119AG2-088 GEN
50/50
30.707
315243AE2-183_GT3
50/50
3.401
3151051BRUNSWICKS1
50/50
5.568
3151021BRUNSWICKG1
50/50
2.682
971451AH1-221 GEN
50/50
8.144
316447AC1-158 HLD
Solar/Wind Harmer
18.884
316044AC1-158 PL1
Solar/Wind Harmer
8.585
3147666LOUISA
Solar/Wind Harmer
-0.217
316192AB2-158 GEN
Solar/Wind Harmer
6.323
3143226MDLTHAN
Solar/Wind Harmer
-0.026
941031AE2-094 GEN
Solar/Wind Harmer
44.849
940641AE2-051 GEN
Solar/Wind Harmer
21.973
3143336POWHATN
Solar/Wind Harmer
2.638
970919AG2-571 GEN
Solar/Wind Harmer
6.936
939411AE1-173 GEN
Solar/Wind Harmer
109.255
970087AG2-069 GEN
Solar/Wind Harmer
20.238
3143526WINTERP
Solar/Wind Harmer
-0.108
957481AF2-042 GEN
Solar/Wind Harmer
64.822
315693AD1-088 GEN
Solar/Wind Harmer
10.138
970937AG2-583 GEN
Solar/Wind Harmer
13.528
3146926FARMVIL
Solar/Wind Harmer
-0.011
316023GEN1_S
Solar/Wind Harmer
1.221
971563AH1-280 GEN
Solar/Wind Harmer
2.243
3144293JTRSVLE
Adder
0.381
3144293JTRSVLE
Adder
0.301
960081AF2-299 GEN
Solar/Wind Harmer
2.016
970685AG2-442 GEN
Solar/Wind Harmer
15.673
3147043LAWRENC
Adder
1.437
316034AC1-036 C
Solar/Wind Harmer
0.329
315785AD2-033 C
Solar/Wind Harmer
4.024
316087AB2-174 GEN
Solar/Wind Harmer
2.518
316131AB2-060 GEN
Solar/Wind Harmer
1.901
3146776BUCKING
Solar/Wind Harmer
-0.007
971065AG2-659 GEN
Solar/Wind Harmer
8.737
316129AC1-054 GEN
Solar/Wind Harmer
1.526
944591AF1-124 GEN
Solar/Wind Harmer
78.618
315607AA1-063A GEN
Solar/Wind Harmer
1.725
315683AE1-153 C
Solar/Wind Harmer
15.914
3145783HORNRTN
Solar/Wind Harmer
-0.017
315773AC2-141 GEN
Solar/Wind Harmer
7.121
3146456SLIGO L269
Solar/Wind Harmer
-0.017
319010AE1-072 C
Solar/Wind Harmer
3.437
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
316093AE2-104_GEN
Solar/Wind Harmer
4.926
316375AC2-012 GEN
Solar/Wind Harmer
5.852
316036AC1-147 C
Solar/Wind Harmer
0.455
3150981CHESPKA
Adder
1.88
3146516WINFALL
Solar/Wind Harmer
-0.054
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
0.502
3146263WOODLND
Solar/Wind Harmer
-0.017
315611Z1-036_GEN2
Solar/Wind Harmer
4.156
3146173TUNIS
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.096
315816AE2-034 GEN
Solar/Wind Harmer
1.349
3145663CRESWEL
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.017
971163AH1-040 GEN
Solar/Wind Harmer
15.673
316381AD1-082 GEN
Solar/Wind Harmer
1.528
3156021HOLLOMANSOL
Solar/Wind Harmer
2.238
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.161
315737AD1-076 GEN
Solar/Wind Harmer
3.157
3145823KELFORD
Solar/Wind Harmer
-0.017
316072AD1-144
Solar/Wind Harmer
0.33
3145963POPLR C
Solar/Wind Harmer
-0.016
3146293MARTNCO
Solar/Wind Harmer
0.099
316319Z2-044 C
Solar/Wind Harmer
0.881
3146233WITAKRS
Solar/Wind Harmer
-0.063
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
316494AC1-189 GEN
Solar/Wind Harmer
1.703
961671AG1-007 GEN
Solar/Wind Harmer
0.2
3146083TARBORO
Solar/Wind Harmer
-0.016
3145493TOT1
Solar/Wind Harmer
0.468
3145336SMITFLD
Solar/Wind Harmer
-0.063
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.013
316359AB2-059 GEN
Solar/Wind Harmer
2.116
3142053HEARTS
Solar/Wind Harmer
0.185
3150851SPRUNCC
Adder
0.639
971377AH1-170 GEN
Solar/Wind Harmer
1.914
3147623JAMES R
Solar/Wind Harmer
0.237
3151171GRAVELC
Adder
1.423
315671AE2-027_GEN
Solar/Wind Harmer
2.682
961611AG1-000B GEN
Solar/Wind Harmer
7.277
316369SG1_INVT
Solar/Wind Harmer
2.55
971069AG2-661 GEN
Solar/Wind Harmer
2.235
316132AB2-190 GEN1
Solar/Wind Harmer
0.196
LAGNLTFEXP_LAGN->PJM
CLTF
5.941
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.349
TVALTFEXP_TVA->PJM
CLTF
2.99
CPLELTFEXP_CPLE->PJM
CLTF
9.522
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.463
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.837
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.023
MECLTFEXP_MEC->PJM
CLTF
2.4
SIGELTFEXP_SIGE->PJM
CLTF
0.071
NYPJM->LTFIMP_NY
CLTF
2.688
LGEELTFEXP_LGEE->PJM
CLTF
0.831
WECLTFEXP_WEC->PJM
CLTF
0.398

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.22 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4736.51
MW Contribution:
6.78
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
20.949
315242AE2-183_GT2
50/50
3.263
315241AE2-183_GT1
50/50
3.254
972185AH1-677 GEN
50/50
11.794
3151041BRUNSWICKG3
50/50
2.573
972187AH1-678 GEN
50/50
5.903
316045AC1-158 PL2
Solar/Wind Harmer
25.985
316450AC1-158 RIC
Solar/Wind Harmer
2.165
966001AG1-469 GEN
Solar/Wind Harmer
0.617
971223AH1-071 GEN
Solar/Wind Harmer
3.104
970933AG2-581 GEN
Solar/Wind Harmer
20.204
316313AB2-026
Solar/Wind Harmer
0.58
316336AC2-165 C
Solar/Wind Harmer
12.916
3143526WINTERP
Solar/Wind Harmer
-0.103
970099AG2-077 GEN
Solar/Wind Harmer
24.933
3144356SAPONY
Solar/Wind Harmer
0.658
316315AB2-025 C
Solar/Wind Harmer
0.507
970301AG2-198 GEN
Solar/Wind Harmer
9.275
315687AD1-152 GEN
Solar/Wind Harmer
2.13
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
316303AF2-085
50/50
3.929
315244AE2-183_ST
50/50
5.666
963041AG1-153 GEN
50/50
5.209
316164AC1-076 GEN
Solar/Wind Harmer
2.997
3147346CASHSCORNER
Solar/Wind Harmer
0.486
970533AG2-339 GEN
Solar/Wind Harmer
15.427
970673AG2-436 GEN
Solar/Wind Harmer
49.587
971967AH1-528 GEN
Solar/Wind Harmer
41.447
316258AE1-075 C
Solar/Wind Harmer
0.522
316405AF2-144 C
Solar/Wind Harmer
0.551
315651AD1-115 GEN
Solar/Wind Harmer
9.369
970085AG2-068 GEN
Solar/Wind Harmer
12.943
970581AG2-369 GEN
Solar/Wind Harmer
11.131
316233AE1-074 FULL
Solar/Wind Harmer
0.537
971281AH1-106 GEN
Solar/Wind Harmer
3.244
971283AH1-107 GEN
Solar/Wind Harmer
3.244
316486AD2-202 GEN
Solar/Wind Harmer
0.481
315814AE2-033 C
Solar/Wind Harmer
17.493
946301AF1-294 GEN
Solar/Wind Harmer
4.459
961791AG1-021 GEN
Solar/Wind Harmer
2.175
971845AH1-439 GEN
Solar/Wind Harmer
9.203
970683AG2-441 GEN
Solar/Wind Harmer
12.228
970681AG2-440 GEN
Solar/Wind Harmer
8.116
316322AB2-045
Solar/Wind Harmer
0.58
3144303KENBRDG
Solar/Wind Harmer
-0.014
946281AF1-292 GEN
Solar/Wind Harmer
0.384
316238AB2-078_GEN
Solar/Wind Harmer
0.51
316239AB2-077_GEN
Solar/Wind Harmer
0.51
3143316POE
Solar/Wind Harmer
-0.067
970831AG2-522 GEN
Solar/Wind Harmer
8.351
972205AH1-687 GEN
Adder
6.314
3137643SOCKMAN
Solar/Wind Harmer
-0.066
315652AC1-086 GEN
Solar/Wind Harmer
18.5
316426AA2-053 GEN
Solar/Wind Harmer
1.646
3146043SEABORD
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
316018AA1-139 ULT2
Solar/Wind Harmer
1.379
957871AF2-081 GEN
Solar/Wind Harmer
8.071
3146406KITTY HAWK
Solar/Wind Harmer
0.013
316318V4-068
Solar/Wind Harmer
0.401
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
-0.016
313526AB2-022
Solar/Wind Harmer
0.433
316316AC1-027 C
Solar/Wind Harmer
0.493
3146396TANGLEW
Solar/Wind Harmer
0.296
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3151081ELIZAR1
Adder
13.097
3151091ELIZAR2
Adder
12.87
3146486SUNBURY
Solar/Wind Harmer
-0.016
3146486SUNBURY
Solar/Wind Harmer
-0.016
316463AE2-346 GEN
Solar/Wind Harmer
0.258
3145513AHOSKIE
Solar/Wind Harmer
0.139
961941AG1-037 GEN
Solar/Wind Harmer
0.12
3145513AHOSKIE
Solar/Wind Harmer
-0.016
315800Z1-036_GEN1
Solar/Wind Harmer
3.943
316311AC2-079 GEN
Solar/Wind Harmer
8.048
315833AF1-017_GEN
Solar/Wind Harmer
3.03
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
3146206CASHIE
Solar/Wind Harmer
-0.016
970601AG2-382 GEN
Solar/Wind Harmer
6.927
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315732AD1-074 GEN1
Solar/Wind Harmer
3.193
315733AD1-074 GEN2
Solar/Wind Harmer
3.193
970657AG2-426 GEN
Solar/Wind Harmer
0.997
3146033SCOT NK
Solar/Wind Harmer
-0.063
316274AC1-208 GEN
Solar/Wind Harmer
1.696
316210AC1-098 GEN
Solar/Wind Harmer
2.463
3147173SINAI
Solar/Wind Harmer
-0.015
3147243WELCO
Solar/Wind Harmer
-0.01
316174AB2-169 GEN
Solar/Wind Harmer
2.381
316327AA2-057 GEN
Solar/Wind Harmer
1.554
3145746EVERETS
Solar/Wind Harmer
-0.06
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
957861AF2-080 GEN
Solar/Wind Harmer
6.609
3145573BETHELC
Solar/Wind Harmer
-0.015
3145573BETHELC
Solar/Wind Harmer
-0.015
315839AE2-212 C
Solar/Wind Harmer
0.449
316236AE1-162_GEN
Solar/Wind Harmer
0.447
971445AH1-216 GEN
Solar/Wind Harmer
9.154
971285AH1-108 GEN
Adder
0.985
3151201GRAVEL4
Adder
9.159
3151221GRAVEL6
Adder
9.148
3151191GRAVEL3
Adder
9.043
3151211GRAVEL5
Adder
9.043
315697AD1-025 GEN
Solar/Wind Harmer
2.708
3152261N ANNA2
50/50
34.977
3151771S ANNAG1
50/50
1.115
3151801S ANNAS2
50/50
0.573
3151761LOISA E
50/50
42.709
3151721LOISA A
50/50
20.841
3151031BRUNSWICKG2
50/50
2.573
3147666LOUISA
Solar/Wind Harmer
-0.126
3132273ORANGE
Solar/Wind Harmer
-0.006
944011AF1-069 GEN
Solar/Wind Harmer
13.478
3143336POWHATN
Solar/Wind Harmer
2.173
970917AG2-570 GEN
Solar/Wind Harmer
52.562
316478AD1-087 GEN
Solar/Wind Harmer
1.644
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.651
3147133PAMPLIN
Solar/Wind Harmer
-0.055
3144293JTRSVLE
Adder
0.37
3146776BUCKING
Solar/Wind Harmer
-0.006
959311AF2-222 GEN
Solar/Wind Harmer
18.003
970257AG2-171 GEN
Solar/Wind Harmer
6.458
971775AH1-396 GEN
Solar/Wind Harmer
1.215
966621AG1-532 GEN
Solar/Wind Harmer
0.348
3147043LAWRENC
Solar/Wind Harmer
-0.01
964241AG1-285 GEN
Solar/Wind Harmer
13.35
316181AB2-040 GEN
Solar/Wind Harmer
2.339
972003AH1-546 GEN
Solar/Wind Harmer
6.778
316011AB1-132 GEN
Solar/Wind Harmer
3.434
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.2
944581AF1-123 GEN
Solar/Wind Harmer
74.181
944601AF1-125 GEN
Solar/Wind Harmer
73.023
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.016
3156081AA2-088 GEN
Solar/Wind Harmer
5.251
316017AA1-139 ULT1
Solar/Wind Harmer
1.303
3146456SLIGO L269
Solar/Wind Harmer
-0.016
971153AH1-033 GEN
Solar/Wind Harmer
1.867
3145893MURPHYS
Solar/Wind Harmer
0.112
3145893MURPHYS
Solar/Wind Harmer
-0.016
3142956BIRDNECK
Solar/Wind Harmer
0.864
3145273HOLLAND
Solar/Wind Harmer
-0.012
316320Y1-086
Solar/Wind Harmer
0.942
316305AF2-043 C
Solar/Wind Harmer
0.483
316246AF1-032 C
Solar/Wind Harmer
0.324
316321Z2-027
Solar/Wind Harmer
0.432
3146263WOODLND
Solar/Wind Harmer
-0.016
3151101ELIZAR3
Adder
13.265
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146376EDENTON
Solar/Wind Harmer
-0.016
316317KELFORD C
Solar/Wind Harmer
0.734
3145823KELFORD
Solar/Wind Harmer
-0.016
3146206CASHIE
Solar/Wind Harmer
-0.016
315735AD1-075 GEN1
Solar/Wind Harmer
1.596
970657AG2-426 GEN
Solar/Wind Harmer
3.195
316212AC1-099_GEN
Solar/Wind Harmer
1.369
315813AE1-149 C
Solar/Wind Harmer
9.816
3144536CHRHLND
Solar/Wind Harmer
-0.002
315722AD1-056 GEN
Solar/Wind Harmer
5.545
3145963POPLR C
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
3146233WITAKRS
Solar/Wind Harmer
0.319
3146233WITAKRS
Solar/Wind Harmer
-0.01
3138543CONSLDL
Solar/Wind Harmer
-0.01
970221AG2-151 GEN
Solar/Wind Harmer
9.504
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
316420AA1-050 GEN
Solar/Wind Harmer
1.719
3146073TAR RVR
Solar/Wind Harmer
-0.015
3146083TARBORO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
5.987
3145336SMITFLD
Solar/Wind Harmer
-0.006
316003AC1-222 GEN
Solar/Wind Harmer
1.44
3150861SPRUNCD
Adder
0.602
3151171GRAVELC
Adder
1.76
971683AH1-343 GEN
Solar/Wind Harmer
6.002
961611AG1-000B GEN
Solar/Wind Harmer
2.918
316222AC1-221 GEN
Solar/Wind Harmer
1.395
316283AC2-100 C
Solar/Wind Harmer
1.294
315778AD1-151 GEN
Solar/Wind Harmer
0.601
958211AF2-115 GEN
Solar/Wind Harmer
2.719
3144293JTRSVLE
Adder
0.37
316365GEN2_N
Solar/Wind Harmer
1.165
3146776BUCKING
Solar/Wind Harmer
-0.069
3146776BUCKING
Solar/Wind Harmer
-0.006
970323AG2-213 GEN
Solar/Wind Harmer
8.611
313527AB2-043 GEN
Solar/Wind Harmer
2.762
316237AB2-079_GEN
Solar/Wind Harmer
0.51
313506AB2-031 GEN
Solar/Wind Harmer
1.347
962571AG1-106 GEN
Solar/Wind Harmer
2.364
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
0.136
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145783HORNRTN
Solar/Wind Harmer
1.937
3145783HORNRTN
Solar/Wind Harmer
1.55
3145783HORNRTN
Solar/Wind Harmer
0.484
3145783HORNRTN
Solar/Wind Harmer
0.194
962561AG1-105 GEN
Solar/Wind Harmer
9.163
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.01
316185AD1-033 GEN
Solar/Wind Harmer
1.701
964791AG1-342 GEN
Solar/Wind Harmer
3.452
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.086
316388AE2-253 GEN
Solar/Wind Harmer
1.086
3137176SLIGO L2192
Solar/Wind Harmer
-0.064
3146456SLIGO L269
Solar/Wind Harmer
1.905
3130086AYDLETT
Solar/Wind Harmer
-0.064
316294AC1-161 GEN
Solar/Wind Harmer
5.206
315742AE1-103 GEN
Solar/Wind Harmer
3.824
3145893MURPHYS
Solar/Wind Harmer
0.449
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146386ELIZ CT
Solar/Wind Harmer
-0.016
315835AF2-110_GEN
Solar/Wind Harmer
2.006
316431W1029_GEN1
Solar/Wind Harmer
2.905
316433W1029_GEN2
Solar/Wind Harmer
2.905
316435W1029_GEN3
Solar/Wind Harmer
2.905
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3150991CHESPKB
Adder
1.493
3150991CHESPKB
Adder
1.457
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316140AB2-099
Solar/Wind Harmer
0.107
316349AD2-085 GEN
Solar/Wind Harmer
1.416
3146376EDENTON
Solar/Wind Harmer
0.473
3146376EDENTON
Solar/Wind Harmer
0.473
315614AA2-178 GEN
Solar/Wind Harmer
1.709
316118AC1-105 GEN
Solar/Wind Harmer
1.087
316065AD1-022 GEN
Solar/Wind Harmer
7.914
316083AB2-161 GEN
Solar/Wind Harmer
2.563
315724AD1-057 GEN
Solar/Wind Harmer
3.05
316248AF1-058 C
Solar/Wind Harmer
0.467
3145933PARMELE
Solar/Wind Harmer
-0.03
3145933PARMELE
Solar/Wind Harmer
-0.015
316005AA1-067
Solar/Wind Harmer
0.305
3145493TOT1
Solar/Wind Harmer
0.233
3145453TOT5
Solar/Wind Harmer
0.14
3145603CNETO
Solar/Wind Harmer
0.093
316049AB1-081 GEN
Solar/Wind Harmer
1.619
316263AC1-034 GEN
Solar/Wind Harmer
7.053
961601AG1-000A GEN
Solar/Wind Harmer
5.912
316240AF1-291 C
Solar/Wind Harmer
0.411
316033AB2-134 GEN
Solar/Wind Harmer
4.321
944641AF1-129 GEN
Adder
56.184
3152251N ANNA1
50/50
34.959
3151791S ANNAG2
50/50
1.115
3151781S ANNAS1
50/50
0.573
3151741LOISA C
50/50
1.146
3151751LOISA D
50/50
20.949
970119AG2-088 GEN
50/50
29.468
971507AH1-251 GEN
50/50
9.111
315243AE2-183_GT3
50/50
3.263
3151051BRUNSWICKS1
50/50
5.341
3151021BRUNSWICKG1
50/50
2.573
971451AH1-221 GEN
50/50
7.813
316447AC1-158 HLD
Solar/Wind Harmer
17.861
316044AC1-158 PL1
Solar/Wind Harmer
8.12
3147666LOUISA
Solar/Wind Harmer
-0.219
316192AB2-158 GEN
Solar/Wind Harmer
6.395
316254AC1-120 GEN1
Solar/Wind Harmer
9.625
316170AC1-121 GEN2
Solar/Wind Harmer
3.208
3143226MDLTHAN
Solar/Wind Harmer
-0.025
941031AE2-094 GEN
Solar/Wind Harmer
43.014
940641AE2-051 GEN
Solar/Wind Harmer
21.032
3143336POWHATN
Solar/Wind Harmer
2.557
970919AG2-571 GEN
Solar/Wind Harmer
6.653
939411AE1-173 GEN
Solar/Wind Harmer
104.353
970087AG2-069 GEN
Solar/Wind Harmer
19.415
315683AE1-153 C
Solar/Wind Harmer
18.596
3143526WINTERP
Solar/Wind Harmer
-0.103
957481AF2-042 GEN
Solar/Wind Harmer
62.333
315693AD1-088 GEN
Solar/Wind Harmer
9.765
970937AG2-583 GEN
Solar/Wind Harmer
13.28
3146926FARMVIL
Solar/Wind Harmer
-0.011
971563AH1-280 GEN
Solar/Wind Harmer
2.175
3144293JTRSVLE
Adder
0.37
3144293JTRSVLE
Adder
0.292
970685AG2-442 GEN
Solar/Wind Harmer
15.185
316023GEN1_S
Solar/Wind Harmer
1.165
3146776BUCKING
Solar/Wind Harmer
-0.007
316034AC1-036 C
Solar/Wind Harmer
0.319
315785AD2-033 C
Solar/Wind Harmer
3.888
960081AF2-299 GEN
Solar/Wind Harmer
1.927
3147043LAWRENC
Adder
1.377
316131AB2-060 GEN
Solar/Wind Harmer
1.832
316087AB2-174 GEN
Solar/Wind Harmer
2.407
971065AG2-659 GEN
Solar/Wind Harmer
8.383
316129AC1-054 GEN
Solar/Wind Harmer
1.463
315607AA1-063A GEN
Solar/Wind Harmer
1.646
3145783HORNRTN
Solar/Wind Harmer
-0.016
944591AF1-124 GEN
Solar/Wind Harmer
74.448
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.016
970401AG2-262 GEN
Solar/Wind Harmer
1.055
3146456SLIGO L269
Solar/Wind Harmer
-0.016
319010AE1-072 C
Solar/Wind Harmer
3.256
315773AC2-141 GEN
Solar/Wind Harmer
6.737
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
0.478
3146263WOODLND
Solar/Wind Harmer
-0.016
316093AE2-104_GEN
Solar/Wind Harmer
4.667
3146516WINFALL
Solar/Wind Harmer
-0.052
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316375AC2-012 GEN
Solar/Wind Harmer
5.538
316036AC1-147 C
Solar/Wind Harmer
0.431
3150981CHESPKA
Adder
1.779
315611Z1-036_GEN2
Solar/Wind Harmer
3.943
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
315816AE2-034 GEN
Solar/Wind Harmer
1.282
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.889
3145823KELFORD
Solar/Wind Harmer
-0.016
3156021HOLLOMANSOL
Solar/Wind Harmer
2.13
3146206CASHIE
Solar/Wind Harmer
-0.016
971547AH1-271 GEN
Solar/Wind Harmer
3.958
315737AD1-076 GEN
Solar/Wind Harmer
3.001
316381AD1-082 GEN
Solar/Wind Harmer
1.445
3145963POPLR C
Solar/Wind Harmer
-0.015
316072AD1-144
Solar/Wind Harmer
0.312
3146293MARTNCO
Solar/Wind Harmer
0.094
316319Z2-044 C
Solar/Wind Harmer
0.842
3146233WITAKRS
Solar/Wind Harmer
-0.06
971377AH1-170 GEN
Solar/Wind Harmer
1.901
3147623JAMES R
Solar/Wind Harmer
0.235
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
316494AC1-189 GEN
Solar/Wind Harmer
1.625
961671AG1-007 GEN
Solar/Wind Harmer
0.191
3146083TARBORO
Solar/Wind Harmer
-0.015
3145493TOT1
Solar/Wind Harmer
0.447
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316359AB2-059 GEN
Solar/Wind Harmer
2.023
3142053HEARTS
Solar/Wind Harmer
0.177
3145336SMITFLD
Solar/Wind Harmer
-0.059
3150851SPRUNCC
Adder
0.602
3151171GRAVELC
Adder
1.339
315671AE2-027_GEN
Solar/Wind Harmer
2.521
961611AG1-000B GEN
Solar/Wind Harmer
6.839
316369SG1_INVT
Solar/Wind Harmer
2.393
971069AG2-661 GEN
Solar/Wind Harmer
0.107
LAGNLTFEXP_LAGN->PJM
CLTF
5.716
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.538
TVALTFEXP_TVA->PJM
CLTF
2.877
CPLELTFEXP_CPLE->PJM
CLTF
9.135
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.41
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.649
MECLTFEXP_MEC->PJM
CLTF
2.315
SIGELTFEXP_SIGE->PJM
CLTF
0.069
NYPJM->LTFIMP_NY
CLTF
2.602
LGEELTFEXP_LGEE->PJM
CLTF
0.803
WECLTFEXP_WEC->PJM
CLTF
0.385

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T594_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 515T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.98 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4727.27
MW Contribution:
6.73
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.921
315244AE2-183_ST
50/50
5.655
963041AG1-153 GEN
50/50
5.199
316164AC1-076 GEN
Solar/Wind Harmer
2.957
3147346CASHSCORNER
Solar/Wind Harmer
0.477
970533AG2-339 GEN
Solar/Wind Harmer
15.398
970673AG2-436 GEN
Solar/Wind Harmer
49.493
971967AH1-528 GEN
Solar/Wind Harmer
41.364
316258AE1-075 C
Solar/Wind Harmer
0.52
316405AF2-144 C
Solar/Wind Harmer
0.549
970085AG2-068 GEN
Solar/Wind Harmer
12.917
970581AG2-369 GEN
Solar/Wind Harmer
11.109
315651AD1-115 GEN
Solar/Wind Harmer
8.925
316233AE1-074 FULL
Solar/Wind Harmer
0.536
971281AH1-106 GEN
Solar/Wind Harmer
3.236
971283AH1-107 GEN
Solar/Wind Harmer
3.236
316486AD2-202 GEN
Solar/Wind Harmer
0.48
315814AE2-033 C
Solar/Wind Harmer
17.455
946301AF1-294 GEN
Solar/Wind Harmer
4.441
961791AG1-021 GEN
Solar/Wind Harmer
2.167
970683AG2-441 GEN
Solar/Wind Harmer
12.182
970681AG2-440 GEN
Solar/Wind Harmer
8.086
971845AH1-439 GEN
Solar/Wind Harmer
9.149
316322AB2-045
Solar/Wind Harmer
0.576
3144303KENBRDG
Solar/Wind Harmer
-0.014
946281AF1-292 GEN
Solar/Wind Harmer
0.383
3151731LOISA B
50/50
20.59
315242AE2-183_GT2
50/50
3.256
315241AE2-183_GT1
50/50
3.248
972185AH1-677 GEN
50/50
11.771
3151041BRUNSWICKG3
50/50
2.568
972187AH1-678 GEN
50/50
5.892
316045AC1-158 PL2
Solar/Wind Harmer
25.962
316450AC1-158 RIC
Solar/Wind Harmer
2.164
966001AG1-469 GEN
Solar/Wind Harmer
0.605
971223AH1-071 GEN
Solar/Wind Harmer
3.098
970933AG2-581 GEN
Solar/Wind Harmer
20.162
316313AB2-026
Solar/Wind Harmer
0.577
316336AC2-165 C
Solar/Wind Harmer
12.862
3143526WINTERP
Solar/Wind Harmer
-0.103
970099AG2-077 GEN
Solar/Wind Harmer
24.873
3144356SAPONY
Solar/Wind Harmer
0.656
316315AB2-025 C
Solar/Wind Harmer
0.506
970301AG2-198 GEN
Solar/Wind Harmer
9.239
315687AD1-152 GEN
Solar/Wind Harmer
2.124
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.708
3144293JTRSVLE
Adder
0.368
316365GEN2_N
Solar/Wind Harmer
1.163
3146776BUCKING
Solar/Wind Harmer
-0.068
3146776BUCKING
Solar/Wind Harmer
-0.006
970323AG2-213 GEN
Solar/Wind Harmer
8.58
313527AB2-043 GEN
Solar/Wind Harmer
2.754
316237AB2-079_GEN
Solar/Wind Harmer
0.508
313506AB2-031 GEN
Solar/Wind Harmer
1.343
962571AG1-106 GEN
Solar/Wind Harmer
2.358
3143316POE
Solar/Wind Harmer
-0.067
316238AB2-078_GEN
Solar/Wind Harmer
0.508
316239AB2-077_GEN
Solar/Wind Harmer
0.508
970831AG2-522 GEN
Solar/Wind Harmer
8.329
3137643SOCKMAN
Solar/Wind Harmer
-0.066
972205AH1-687 GEN
Adder
6.268
315652AC1-086 GEN
Solar/Wind Harmer
18.456
316426AA2-053 GEN
Solar/Wind Harmer
1.642
3146043SEABORD
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
316018AA1-139 ULT2
Solar/Wind Harmer
1.376
957871AF2-081 GEN
Solar/Wind Harmer
8.052
3146406KITTY HAWK
Solar/Wind Harmer
0.013
316318V4-068
Solar/Wind Harmer
0.4
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
-0.016
316316AC1-027 C
Solar/Wind Harmer
0.492
313526AB2-022
Solar/Wind Harmer
0.432
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3146396TANGLEW
Solar/Wind Harmer
0.295
3151081ELIZAR1
Adder
13.066
3151091ELIZAR2
Adder
12.839
3146486SUNBURY
Solar/Wind Harmer
-0.016
3146486SUNBURY
Solar/Wind Harmer
-0.016
316463AE2-346 GEN
Solar/Wind Harmer
0.257
3145513AHOSKIE
Solar/Wind Harmer
0.139
961941AG1-037 GEN
Solar/Wind Harmer
0.12
3145513AHOSKIE
Solar/Wind Harmer
-0.016
315800Z1-036_GEN1
Solar/Wind Harmer
3.934
316311AC2-079 GEN
Solar/Wind Harmer
8.029
315833AF1-017_GEN
Solar/Wind Harmer
3.022
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
0.136
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145783HORNRTN
Solar/Wind Harmer
1.932
3145783HORNRTN
Solar/Wind Harmer
1.546
3145783HORNRTN
Solar/Wind Harmer
0.483
3145783HORNRTN
Solar/Wind Harmer
0.193
962561AG1-105 GEN
Solar/Wind Harmer
9.136
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.01
316185AD1-033 GEN
Solar/Wind Harmer
1.696
964791AG1-342 GEN
Solar/Wind Harmer
3.442
316339AD2-160 GEN
Solar/Wind Harmer
1.083
316388AE2-253 GEN
Solar/Wind Harmer
1.083
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
3137176SLIGO L2192
Solar/Wind Harmer
-0.064
3146456SLIGO L269
Solar/Wind Harmer
1.901
3130086AYDLETT
Solar/Wind Harmer
-0.064
316294AC1-161 GEN
Solar/Wind Harmer
5.194
315742AE1-103 GEN
Solar/Wind Harmer
3.815
3145683EARLEYS
Solar/Wind Harmer
-0.016
3146206CASHIE
Solar/Wind Harmer
-0.016
970601AG2-382 GEN
Solar/Wind Harmer
6.911
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315732AD1-074 GEN1
Solar/Wind Harmer
3.185
315733AD1-074 GEN2
Solar/Wind Harmer
3.185
970657AG2-426 GEN
Solar/Wind Harmer
0.995
3146033SCOT NK
Solar/Wind Harmer
-0.063
316274AC1-208 GEN
Solar/Wind Harmer
1.692
316210AC1-098 GEN
Solar/Wind Harmer
2.457
3147173SINAI
Solar/Wind Harmer
-0.015
3147243WELCO
Solar/Wind Harmer
-0.01
316174AB2-169 GEN
Solar/Wind Harmer
2.376
316327AA2-057 GEN
Solar/Wind Harmer
1.55
3145746EVERETS
Solar/Wind Harmer
-0.06
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
957861AF2-080 GEN
Solar/Wind Harmer
6.593
3145573BETHELC
Solar/Wind Harmer
-0.015
3145573BETHELC
Solar/Wind Harmer
-0.015
315839AE2-212 C
Solar/Wind Harmer
0.448
316236AE1-162_GEN
Solar/Wind Harmer
0.446
971445AH1-216 GEN
Solar/Wind Harmer
9.131
971285AH1-108 GEN
Adder
0.982
3151201GRAVEL4
Adder
9.135
3151221GRAVEL6
Adder
9.124
3151191GRAVEL3
Adder
9.019
3151211GRAVEL5
Adder
9.019
315697AD1-025 GEN
Solar/Wind Harmer
2.7
3145893MURPHYS
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146386ELIZ CT
Solar/Wind Harmer
-0.016
315835AF2-110_GEN
Solar/Wind Harmer
2.002
316431W1029_GEN1
Solar/Wind Harmer
2.898
316433W1029_GEN2
Solar/Wind Harmer
2.898
316435W1029_GEN3
Solar/Wind Harmer
2.898
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3150991CHESPKB
Adder
1.489
3150991CHESPKB
Adder
1.454
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316140AB2-099
Solar/Wind Harmer
0.107
316349AD2-085 GEN
Solar/Wind Harmer
1.413
3146376EDENTON
Solar/Wind Harmer
0.472
3146376EDENTON
Solar/Wind Harmer
0.472
315614AA2-178 GEN
Solar/Wind Harmer
1.705
316118AC1-105 GEN
Solar/Wind Harmer
1.084
316065AD1-022 GEN
Solar/Wind Harmer
7.895
316083AB2-161 GEN
Solar/Wind Harmer
2.557
315724AD1-057 GEN
Solar/Wind Harmer
3.042
316248AF1-058 C
Solar/Wind Harmer
0.466
3145933PARMELE
Solar/Wind Harmer
-0.03
3145933PARMELE
Solar/Wind Harmer
-0.015
316005AA1-067
Solar/Wind Harmer
0.305
3145493TOT1
Solar/Wind Harmer
0.233
3145453TOT5
Solar/Wind Harmer
0.14
3145603CNETO
Solar/Wind Harmer
0.093
316049AB1-081 GEN
Solar/Wind Harmer
1.615
316263AC1-034 GEN
Solar/Wind Harmer
7.035
961601AG1-000A GEN
Solar/Wind Harmer
5.897
316240AF1-291 C
Solar/Wind Harmer
0.41
316033AB2-134 GEN
Solar/Wind Harmer
4.309
944641AF1-129 GEN
Adder
56.025
3152261N ANNA2
50/50
34.952
3151771S ANNAG1
50/50
1.097
3151801S ANNAS2
50/50
0.564
3151761LOISA E
50/50
41.976
3151721LOISA A
50/50
20.483
3151031BRUNSWICKG2
50/50
2.568
3147666LOUISA
Solar/Wind Harmer
-0.125
3132273ORANGE
Solar/Wind Harmer
-0.006
944011AF1-069 GEN
Solar/Wind Harmer
13.452
3143336POWHATN
Solar/Wind Harmer
2.165
970917AG2-570 GEN
Solar/Wind Harmer
52.458
316478AD1-087 GEN
Solar/Wind Harmer
1.64
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.639
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3144293JTRSVLE
Adder
0.368
959311AF2-222 GEN
Solar/Wind Harmer
17.938
3146776BUCKING
Solar/Wind Harmer
-0.006
970257AG2-171 GEN
Solar/Wind Harmer
6.435
971775AH1-396 GEN
Solar/Wind Harmer
1.211
966621AG1-532 GEN
Solar/Wind Harmer
0.347
3147043LAWRENC
Solar/Wind Harmer
-0.01
964241AG1-285 GEN
Solar/Wind Harmer
13.307
316181AB2-040 GEN
Solar/Wind Harmer
2.334
972003AH1-546 GEN
Solar/Wind Harmer
6.73
316011AB1-132 GEN
Solar/Wind Harmer
3.426
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.2
944581AF1-123 GEN
Solar/Wind Harmer
74.006
944601AF1-125 GEN
Solar/Wind Harmer
72.851
3145796HORNRTN
Solar/Wind Harmer
-0.064
3145796HORNRTN
Solar/Wind Harmer
-0.016
3156081AA2-088 GEN
Solar/Wind Harmer
5.238
316017AA1-139 ULT1
Solar/Wind Harmer
1.3
3146456SLIGO L269
Solar/Wind Harmer
-0.016
971153AH1-033 GEN
Solar/Wind Harmer
1.862
3145893MURPHYS
Solar/Wind Harmer
0.112
3145893MURPHYS
Solar/Wind Harmer
-0.016
3142956BIRDNECK
Solar/Wind Harmer
0.861
3145273HOLLAND
Solar/Wind Harmer
-0.012
316320Y1-086
Solar/Wind Harmer
0.94
316305AF2-043 C
Solar/Wind Harmer
0.482
316246AF1-032 C
Solar/Wind Harmer
0.324
316321Z2-027
Solar/Wind Harmer
0.431
3146263WOODLND
Solar/Wind Harmer
-0.016
3151101ELIZAR3
Adder
13.233
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146376EDENTON
Solar/Wind Harmer
-0.016
316317KELFORD C
Solar/Wind Harmer
0.732
3145823KELFORD
Solar/Wind Harmer
-0.016
3146206CASHIE
Solar/Wind Harmer
-0.016
315735AD1-075 GEN1
Solar/Wind Harmer
1.592
970657AG2-426 GEN
Solar/Wind Harmer
3.188
316212AC1-099_GEN
Solar/Wind Harmer
1.365
315813AE1-149 C
Solar/Wind Harmer
9.792
3144536CHRHLND
Solar/Wind Harmer
-0.002
315722AD1-056 GEN
Solar/Wind Harmer
5.532
3145963POPLR C
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
3146233WITAKRS
Solar/Wind Harmer
0.318
3146233WITAKRS
Solar/Wind Harmer
-0.01
3138543CONSLDL
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970221AG2-151 GEN
Solar/Wind Harmer
9.432
316420AA1-050 GEN
Solar/Wind Harmer
1.715
3146073TAR RVR
Solar/Wind Harmer
-0.015
3146083TARBORO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
5.972
3145336SMITFLD
Solar/Wind Harmer
-0.006
316003AC1-222 GEN
Solar/Wind Harmer
1.436
3150861SPRUNCD
Adder
0.6
3151171GRAVELC
Adder
1.755
971683AH1-343 GEN
Solar/Wind Harmer
5.984
961611AG1-000B GEN
Solar/Wind Harmer
2.91
316222AC1-221 GEN
Solar/Wind Harmer
1.391
316283AC2-100 C
Solar/Wind Harmer
1.291
315778AD1-151 GEN
Solar/Wind Harmer
0.599
3152251N ANNA1
50/50
34.934
3151791S ANNAG2
50/50
1.097
3151781S ANNAS1
50/50
0.564
3151741LOISA C
50/50
1.126
3151751LOISA D
50/50
20.59
970119AG2-088 GEN
50/50
29.407
971507AH1-251 GEN
50/50
9.041
315243AE2-183_GT3
50/50
3.256
3151051BRUNSWICKS1
50/50
5.331
3151021BRUNSWICKG1
50/50
2.568
971451AH1-221 GEN
50/50
7.798
316447AC1-158 HLD
Solar/Wind Harmer
17.845
316044AC1-158 PL1
Solar/Wind Harmer
8.113
3147666LOUISA
Solar/Wind Harmer
-0.218
316192AB2-158 GEN
Solar/Wind Harmer
6.35
316254AC1-120 GEN1
Solar/Wind Harmer
9.306
316170AC1-121 GEN2
Solar/Wind Harmer
3.102
3143226MDLTHAN
Solar/Wind Harmer
-0.025
941031AE2-094 GEN
Solar/Wind Harmer
42.933
940641AE2-051 GEN
Solar/Wind Harmer
20.992
3143336POWHATN
Solar/Wind Harmer
2.548
970919AG2-571 GEN
Solar/Wind Harmer
6.64
939411AE1-173 GEN
Solar/Wind Harmer
104.147
970087AG2-069 GEN
Solar/Wind Harmer
19.376
3143526WINTERP
Solar/Wind Harmer
-0.103
957481AF2-042 GEN
Solar/Wind Harmer
62.182
315693AD1-088 GEN
Solar/Wind Harmer
9.738
315683AE1-153 C
Solar/Wind Harmer
17.594
970937AG2-583 GEN
Solar/Wind Harmer
13.205
3146926FARMVIL
Solar/Wind Harmer
-0.011
971563AH1-280 GEN
Solar/Wind Harmer
2.167
3144293JTRSVLE
Adder
0.368
3144293JTRSVLE
Adder
0.291
316023GEN1_S
Solar/Wind Harmer
1.163
970685AG2-442 GEN
Solar/Wind Harmer
15.127
3146776BUCKING
Solar/Wind Harmer
-0.007
316034AC1-036 C
Solar/Wind Harmer
0.317
315785AD2-033 C
Solar/Wind Harmer
3.874
960081AF2-299 GEN
Solar/Wind Harmer
1.923
3147043LAWRENC
Adder
1.373
316131AB2-060 GEN
Solar/Wind Harmer
1.826
316087AB2-174 GEN
Solar/Wind Harmer
2.401
971065AG2-659 GEN
Solar/Wind Harmer
8.36
316129AC1-054 GEN
Solar/Wind Harmer
1.459
315607AA1-063A GEN
Solar/Wind Harmer
1.642
3145783HORNRTN
Solar/Wind Harmer
-0.016
944591AF1-124 GEN
Solar/Wind Harmer
74.272
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.016
970401AG2-262 GEN
Solar/Wind Harmer
1.052
3146456SLIGO L269
Solar/Wind Harmer
-0.016
319010AE1-072 C
Solar/Wind Harmer
3.248
315773AC2-141 GEN
Solar/Wind Harmer
6.721
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
0.477
3146263WOODLND
Solar/Wind Harmer
-0.016
316093AE2-104_GEN
Solar/Wind Harmer
4.656
3146516WINFALL
Solar/Wind Harmer
-0.052
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316375AC2-012 GEN
Solar/Wind Harmer
5.524
316036AC1-147 C
Solar/Wind Harmer
0.43
3150981CHESPKA
Adder
1.775
315611Z1-036_GEN2
Solar/Wind Harmer
3.934
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
315816AE2-034 GEN
Solar/Wind Harmer
1.278
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.853
3156021HOLLOMANSOL
Solar/Wind Harmer
2.125
3145823KELFORD
Solar/Wind Harmer
-0.016
3146206CASHIE
Solar/Wind Harmer
-0.016
971547AH1-271 GEN
Solar/Wind Harmer
3.949
315737AD1-076 GEN
Solar/Wind Harmer
2.994
316381AD1-082 GEN
Solar/Wind Harmer
1.442
3145963POPLR C
Solar/Wind Harmer
-0.015
316072AD1-144
Solar/Wind Harmer
0.311
3146293MARTNCO
Solar/Wind Harmer
0.094
316319Z2-044 C
Solar/Wind Harmer
0.84
3146233WITAKRS
Solar/Wind Harmer
-0.06
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
971377AH1-170 GEN
Solar/Wind Harmer
1.886
3147623JAMES R
Solar/Wind Harmer
0.233
316494AC1-189 GEN
Solar/Wind Harmer
1.621
961671AG1-007 GEN
Solar/Wind Harmer
0.19
3146083TARBORO
Solar/Wind Harmer
-0.015
3145493TOT1
Solar/Wind Harmer
0.446
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316359AB2-059 GEN
Solar/Wind Harmer
2.018
3142053HEARTS
Solar/Wind Harmer
0.176
3145336SMITFLD
Solar/Wind Harmer
-0.059
3150851SPRUNCC
Adder
0.6
3151171GRAVELC
Adder
1.335
315671AE2-027_GEN
Solar/Wind Harmer
2.514
961611AG1-000B GEN
Solar/Wind Harmer
6.821
316369SG1_INVT
Solar/Wind Harmer
2.386
971069AG2-661 GEN
Solar/Wind Harmer
0.107
LAGNLTFEXP_LAGN->PJM
CLTF
5.697
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.483
TVALTFEXP_TVA->PJM
CLTF
2.867
CPLELTFEXP_CPLE->PJM
CLTF
9.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.276
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.616
MECLTFEXP_MEC->PJM
CLTF
2.307
SIGELTFEXP_SIGE->PJM
CLTF
0.069
NYPJM->LTFIMP_NY
CLTF
2.593
LGEELTFEXP_LGEE->PJM
CLTF
0.8
WECLTFEXP_WEC->PJM
CLTF
0.383

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: XT573_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.04 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4650.81
MW Contribution:
6.75
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.152
315244AE2-183_ST
50/50
5.997
963041AG1-153 GEN
50/50
5.513
315779AE2-040
50/50
2.501
3147346CASHSCORNER
Solar/Wind Harmer
0.403
970533AG2-339 GEN
Solar/Wind Harmer
16.334
970673AG2-436 GEN
Solar/Wind Harmer
52.499
971967AH1-528 GEN
Solar/Wind Harmer
43.835
316258AE1-075 C
Solar/Wind Harmer
0.541
316405AF2-144 C
Solar/Wind Harmer
0.571
970085AG2-068 GEN
Solar/Wind Harmer
13.703
970581AG2-369 GEN
Solar/Wind Harmer
11.784
316233AE1-074 FULL
Solar/Wind Harmer
0.573
971281AH1-106 GEN
Solar/Wind Harmer
3.463
971283AH1-107 GEN
Solar/Wind Harmer
3.463
316486AD2-202 GEN
Solar/Wind Harmer
0.507
315814AE2-033 C
Solar/Wind Harmer
18.673
3143316POE
Solar/Wind Harmer
-0.072
946281AF1-292 GEN
Solar/Wind Harmer
0.408
946301AF1-294 GEN
Solar/Wind Harmer
4.626
961791AG1-021 GEN
Solar/Wind Harmer
2.256
970683AG2-441 GEN
Solar/Wind Harmer
12.72
970681AG2-440 GEN
Solar/Wind Harmer
8.442
3144303KENBRDG
Solar/Wind Harmer
-0.014
316238AB2-078_GEN
Solar/Wind Harmer
0.536
316239AB2-077_GEN
Solar/Wind Harmer
0.536
970831AG2-522 GEN
Solar/Wind Harmer
8.845
3137643SOCKMAN
Solar/Wind Harmer
-0.07
315652AC1-086 GEN
Solar/Wind Harmer
19.736
971845AH1-439 GEN
Solar/Wind Harmer
9.312
316322AB2-045
Solar/Wind Harmer
0.586
3146043SEABORD
Solar/Wind Harmer
-0.017
316426AA2-053 GEN
Solar/Wind Harmer
1.754
316018AA1-139 ULT2
Solar/Wind Harmer
1.488
957871AF2-081 GEN
Solar/Wind Harmer
8.706
3146406KITTY HAWK
Solar/Wind Harmer
0.014
316316AC1-027 C
Solar/Wind Harmer
0.532
313526AB2-022
Solar/Wind Harmer
0.467
3151081ELIZAR1
Adder
14.142
3151091ELIZAR2
Adder
13.896
3145796HORNRTN
Solar/Wind Harmer
-0.055
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3146396TANGLEW
Solar/Wind Harmer
0.319
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
316318V4-068
Solar/Wind Harmer
0.43
3151731LOISA B
50/50
17.422
315242AE2-183_GT2
50/50
3.454
315241AE2-183_GT1
50/50
3.444
972185AH1-677 GEN
50/50
12.484
3151041BRUNSWICKG3
50/50
2.723
972187AH1-678 GEN
50/50
6.248
971223AH1-071 GEN
Solar/Wind Harmer
3.28
966001AG1-469 GEN
Solar/Wind Harmer
0.464
970933AG2-581 GEN
Solar/Wind Harmer
21.35
316313AB2-026
Solar/Wind Harmer
0.601
316336AC2-165 C
Solar/Wind Harmer
13.317
3143526WINTERP
Solar/Wind Harmer
-0.11
970099AG2-077 GEN
Solar/Wind Harmer
26.277
3144356SAPONY
Solar/Wind Harmer
0.702
316315AB2-025 C
Solar/Wind Harmer
0.542
970301AG2-198 GEN
Solar/Wind Harmer
9.608
315687AD1-152 GEN
Solar/Wind Harmer
2.245
316365GEN2_N
Solar/Wind Harmer
1.243
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.821
3144293JTRSVLE
Adder
0.384
970323AG2-213 GEN
Solar/Wind Harmer
8.983
3145893MURPHYS
Solar/Wind Harmer
-0.046
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.685
315833AF1-017_GEN
Solar/Wind Harmer
3.269
315800Z1-036_GEN1
Solar/Wind Harmer
4.242
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970657AG2-426 GEN
Solar/Wind Harmer
1.077
316463AE2-346 GEN
Solar/Wind Harmer
0.276
3145513AHOSKIE
Solar/Wind Harmer
0.149
961941AG1-037 GEN
Solar/Wind Harmer
0.128
3145513AHOSKIE
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.426
315732AD1-074 GEN1
Solar/Wind Harmer
3.425
315733AD1-074 GEN2
Solar/Wind Harmer
3.425
3146033SCOT NK
Solar/Wind Harmer
-0.067
316274AC1-208 GEN
Solar/Wind Harmer
1.808
316210AC1-098 GEN
Solar/Wind Harmer
2.627
316174AB2-169 GEN
Solar/Wind Harmer
2.549
972205AH1-687 GEN
Adder
6.272
316327AA2-057 GEN
Solar/Wind Harmer
1.656
3147173SINAI
Solar/Wind Harmer
-0.016
3147243WELCO
Solar/Wind Harmer
-0.01
315839AE2-212 C
Solar/Wind Harmer
0.488
3145746EVERETS
Solar/Wind Harmer
-0.064
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
316236AE1-162_GEN
Solar/Wind Harmer
0.485
957861AF2-080 GEN
Solar/Wind Harmer
7.052
3145573BETHELC
Solar/Wind Harmer
-0.016
3145573BETHELC
Solar/Wind Harmer
-0.016
971445AH1-216 GEN
Solar/Wind Harmer
9.938
971285AH1-108 GEN
Adder
1.071
3151201GRAVEL4
Adder
9.974
3151221GRAVEL6
Adder
9.963
3151191GRAVEL3
Adder
9.848
3151211GRAVEL5
Adder
9.848
315697AD1-025 GEN
Solar/Wind Harmer
2.961
313506AB2-031 GEN
Solar/Wind Harmer
1.434
313527AB2-043 GEN
Solar/Wind Harmer
2.901
316237AB2-079_GEN
Solar/Wind Harmer
0.536
962571AG1-106 GEN
Solar/Wind Harmer
2.522
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3146776BUCKING
Solar/Wind Harmer
-0.069
3146776BUCKING
Solar/Wind Harmer
-0.006
316185AD1-033 GEN
Solar/Wind Harmer
1.835
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.042
3145506HICKORY
Solar/Wind Harmer
-0.01
316294AC1-161 GEN
Solar/Wind Harmer
5.625
316339AD2-160 GEN
Solar/Wind Harmer
1.171
316388AE2-253 GEN
Solar/Wind Harmer
1.171
3137176SLIGO L2192
Solar/Wind Harmer
-0.069
3146456SLIGO L269
Solar/Wind Harmer
2.055
3130086AYDLETT
Solar/Wind Harmer
-0.069
3145783HORNRTN
Solar/Wind Harmer
2.063
3145783HORNRTN
Solar/Wind Harmer
1.651
3145783HORNRTN
Solar/Wind Harmer
0.516
3145783HORNRTN
Solar/Wind Harmer
0.206
3146386ELIZ CT
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.052
315742AE1-103 GEN
Solar/Wind Harmer
4.11
315835AF2-110_GEN
Solar/Wind Harmer
2.163
3150991CHESPKB
Adder
1.612
3150991CHESPKB
Adder
1.573
316431W1029_GEN1
Solar/Wind Harmer
3.13
316433W1029_GEN2
Solar/Wind Harmer
3.13
316435W1029_GEN3
Solar/Wind Harmer
3.13
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.481
3145893MURPHYS
Solar/Wind Harmer
-0.031
316349AD2-085 GEN
Solar/Wind Harmer
1.528
3146376EDENTON
Solar/Wind Harmer
0.509
3146376EDENTON
Solar/Wind Harmer
0.509
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
962561AG1-105 GEN
Solar/Wind Harmer
9.638
316140AB2-099
Solar/Wind Harmer
0.115
316083AB2-161 GEN
Solar/Wind Harmer
2.769
315614AA2-178 GEN
Solar/Wind Harmer
1.835
964791AG1-342 GEN
Solar/Wind Harmer
3.632
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
316065AD1-022 GEN
Solar/Wind Harmer
8.487
316118AC1-105 GEN
Solar/Wind Harmer
1.145
315724AD1-057 GEN
Solar/Wind Harmer
3.25
316248AF1-058 C
Solar/Wind Harmer
0.492
3145933PARMELE
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.016
316005AA1-067
Solar/Wind Harmer
0.326
3145493TOT1
Solar/Wind Harmer
0.249
3145453TOT5
Solar/Wind Harmer
0.149
3145603CNETO
Solar/Wind Harmer
0.099
316049AB1-081 GEN
Solar/Wind Harmer
1.724
316263AC1-034 GEN
Solar/Wind Harmer
7.511
961601AG1-000A GEN
Solar/Wind Harmer
6.297
316240AF1-291 C
Solar/Wind Harmer
0.449
316033AB2-134 GEN
Solar/Wind Harmer
4.724
944641AF1-129 GEN
Adder
61.525
3152261N ANNA2
50/50
36.305
3151771S ANNAG1
50/50
0.935
3151801S ANNAS2
50/50
0.481
3151761LOISA E
50/50
35.519
3151721LOISA A
50/50
17.333
3151031BRUNSWICKG2
50/50
2.723
3147666LOUISA
Solar/Wind Harmer
-0.113
944011AF1-069 GEN
Solar/Wind Harmer
14.27
3143336POWHATN
Solar/Wind Harmer
2.254
970917AG2-570 GEN
Solar/Wind Harmer
55.643
316478AD1-087 GEN
Solar/Wind Harmer
1.732
3146926FARMVIL
Solar/Wind Harmer
-0.011
966621AG1-532 GEN
Solar/Wind Harmer
0.37
942461AE2-259 GEN
Solar/Wind Harmer
2.73
3147043LAWRENC
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.057
3144293JTRSVLE
Adder
0.384
959311AF2-222 GEN
Solar/Wind Harmer
18.765
970257AG2-171 GEN
Solar/Wind Harmer
6.737
971775AH1-396 GEN
Solar/Wind Harmer
1.268
964241AG1-285 GEN
Solar/Wind Harmer
13.986
316181AB2-040 GEN
Solar/Wind Harmer
2.49
944581AF1-123 GEN
Solar/Wind Harmer
80.028
944601AF1-125 GEN
Solar/Wind Harmer
78.779
316011AB1-132 GEN
Solar/Wind Harmer
3.664
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
316190AA2-174 GEN
Solar/Wind Harmer
0.214
316017AA1-139 ULT1
Solar/Wind Harmer
1.405
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.014
3142956BIRDNECK
Solar/Wind Harmer
0.932
316320Y1-086
Solar/Wind Harmer
1.015
316305AF2-043 C
Solar/Wind Harmer
0.521
316246AF1-032 C
Solar/Wind Harmer
0.35
3151101ELIZAR3
Adder
14.323
3156081AA2-088 GEN
Solar/Wind Harmer
5.622
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.017
316321Z2-027
Solar/Wind Harmer
0.466
3145273HOLLAND
Solar/Wind Harmer
-0.013
3144873MCLAUGH
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.12
3145893MURPHYS
Solar/Wind Harmer
-0.017
3146263WOODLND
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
970657AG2-426 GEN
Solar/Wind Harmer
3.452
315813AE1-149 C
Solar/Wind Harmer
10.615
3146206CASHIE
Solar/Wind Harmer
-0.017
315735AD1-075 GEN1
Solar/Wind Harmer
1.712
3144536CHRHLND
Solar/Wind Harmer
-0.003
316317KELFORD C
Solar/Wind Harmer
0.784
3145823KELFORD
Solar/Wind Harmer
-0.017
316212AC1-099_GEN
Solar/Wind Harmer
1.46
3145963POPLR C
Solar/Wind Harmer
-0.017
972003AH1-546 GEN
Solar/Wind Harmer
6.747
315722AD1-056 GEN
Solar/Wind Harmer
5.91
3145933PARMELE
Solar/Wind Harmer
-0.016
3146233WITAKRS
Solar/Wind Harmer
0.34
3146233WITAKRS
Solar/Wind Harmer
-0.011
3138543CONSLDL
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
3145336SMITFLD
Solar/Wind Harmer
-0.006
316420AA1-050 GEN
Solar/Wind Harmer
1.834
3146073TAR RVR
Solar/Wind Harmer
-0.016
3146083TARBORO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.016
961601AG1-000A GEN
Solar/Wind Harmer
6.377
3150861SPRUNCD
Adder
0.655
316003AC1-222 GEN
Solar/Wind Harmer
1.517
3151171GRAVELC
Adder
1.917
3132273ORANGE
Solar/Wind Harmer
-0.003
961611AG1-000B GEN
Solar/Wind Harmer
3.183
970221AG2-151 GEN
Solar/Wind Harmer
9.418
971683AH1-343 GEN
Solar/Wind Harmer
6.324
316222AC1-221 GEN
Solar/Wind Harmer
1.476
316283AC2-100 C
Solar/Wind Harmer
1.369
315778AD1-151 GEN
Solar/Wind Harmer
12.901
316458AB2-190 GEN2
Solar/Wind Harmer
1.436
3144216WINCHST
Adder
0.463
970133AG2-095 GEN
Solar/Wind Harmer
1.551
3150921YORKTN3
Adder
3.031
270494AE1-108_GEN
Solar/Wind Harmer
3.339
316123AC1-075 GEN
Solar/Wind Harmer
1.31
3152251N ANNA1
50/50
36.286
3151791S ANNAG2
50/50
0.935
3151781S ANNAS1
50/50
0.481
3151741LOISA C
50/50
0.953
3151751LOISA D
50/50
17.422
970119AG2-088 GEN
50/50
31.139
315243AE2-183_GT3
50/50
3.454
3151051BRUNSWICKS1
50/50
5.653
3151021BRUNSWICKG1
50/50
2.723
971451AH1-221 GEN
50/50
8.27
3147666LOUISA
Solar/Wind Harmer
-0.196
316192AB2-158 GEN
Solar/Wind Harmer
5.705
3143226MDLTHAN
Solar/Wind Harmer
-0.026
941031AE2-094 GEN
Solar/Wind Harmer
45.544
940641AE2-051 GEN
Solar/Wind Harmer
22.335
3143336POWHATN
Solar/Wind Harmer
2.652
970919AG2-571 GEN
Solar/Wind Harmer
7.043
939411AE1-173 GEN
Solar/Wind Harmer
111.163
970087AG2-069 GEN
Solar/Wind Harmer
20.554
3143526WINTERP
Solar/Wind Harmer
-0.11
957481AF2-042 GEN
Solar/Wind Harmer
65.693
315693AD1-088 GEN
Solar/Wind Harmer
10.259
970937AG2-583 GEN
Solar/Wind Harmer
13.448
316023GEN1_S
Solar/Wind Harmer
1.243
3146926FARMVIL
Solar/Wind Harmer
-0.011
960081AF2-299 GEN
Solar/Wind Harmer
2.051
3147043LAWRENC
Adder
1.459
971563AH1-280 GEN
Solar/Wind Harmer
2.256
3144293JTRSVLE
Adder
0.384
3144293JTRSVLE
Adder
0.303
970685AG2-442 GEN
Solar/Wind Harmer
15.775
316087AB2-174 GEN
Solar/Wind Harmer
2.562
316034AC1-036 C
Solar/Wind Harmer
0.332
315785AD2-033 C
Solar/Wind Harmer
4.06
316131AB2-060 GEN
Solar/Wind Harmer
1.923
971065AG2-659 GEN
Solar/Wind Harmer
8.867
316129AC1-054 GEN
Solar/Wind Harmer
1.549
944591AF1-124 GEN
Solar/Wind Harmer
80.317
3146776BUCKING
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
1.756
315773AC2-141 GEN
Solar/Wind Harmer
7.278
3146456SLIGO L269
Solar/Wind Harmer
-0.017
319010AE1-072 C
Solar/Wind Harmer
3.511
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.017
316093AE2-104_GEN
Solar/Wind Harmer
5.032
316375AC2-012 GEN
Solar/Wind Harmer
5.98
316036AC1-147 C
Solar/Wind Harmer
0.465
3150981CHESPKA
Adder
1.922
3146516WINFALL
Solar/Wind Harmer
-0.056
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.511
315611Z1-036_GEN2
Solar/Wind Harmer
4.242
3146263WOODLND
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
316381AD1-082 GEN
Solar/Wind Harmer
1.562
315816AE2-034 GEN
Solar/Wind Harmer
1.377
3145663CRESWEL
Solar/Wind Harmer
-0.048
971163AH1-040 GEN
Solar/Wind Harmer
15.993
3145683EARLEYS
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.11
3156021HOLLOMANSOL
Solar/Wind Harmer
2.281
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.244
315737AD1-076 GEN
Solar/Wind Harmer
3.22
3145823KELFORD
Solar/Wind Harmer
-0.017
316072AD1-144
Solar/Wind Harmer
0.337
3145963POPLR C
Solar/Wind Harmer
-0.017
3146293MARTNCO
Solar/Wind Harmer
0.101
316319Z2-044 C
Solar/Wind Harmer
0.897
3146233WITAKRS
Solar/Wind Harmer
-0.064
3145746EVERETS
Solar/Wind Harmer
-0.016
3145746EVERETS
Solar/Wind Harmer
-0.016
3145336SMITFLD
Solar/Wind Harmer
-0.064
316494AC1-189 GEN
Solar/Wind Harmer
1.734
961671AG1-007 GEN
Solar/Wind Harmer
0.203
3146083TARBORO
Solar/Wind Harmer
-0.016
3145493TOT1
Solar/Wind Harmer
0.477
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.013
316359AB2-059 GEN
Solar/Wind Harmer
2.155
3142053HEARTS
Solar/Wind Harmer
0.188
3150851SPRUNCC
Adder
0.655
3151171GRAVELC
Adder
1.458
315671AE2-027_GEN
Solar/Wind Harmer
2.749
961611AG1-000B GEN
Solar/Wind Harmer
7.459
971377AH1-170 GEN
Solar/Wind Harmer
1.884
3147623JAMES R
Solar/Wind Harmer
0.233
315683AE1-153 C
Solar/Wind Harmer
14.03
316369SG1_INVT
Solar/Wind Harmer
2.616
971069AG2-661 GEN
Solar/Wind Harmer
2.293
316132AB2-190 GEN1
Solar/Wind Harmer
1.436
3138126ROCKLANDING
Solar/Wind Harmer
0.042
3142543TWELFTH
Solar/Wind Harmer
-0.001
LAGNLTFEXP_LAGN->PJM
CLTF
6.167
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.771
TVALTFEXP_TVA->PJM
CLTF
3.101
CPLELTFEXP_CPLE->PJM
CLTF
9.697
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.907
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.331
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.435
MECLTFEXP_MEC->PJM
CLTF
2.575
SIGELTFEXP_SIGE->PJM
CLTF
0.077
NYPJM->LTFIMP_NY
CLTF
2.605
LGEELTFEXP_LGEE->PJM
CLTF
0.901
WECLTFEXP_WEC->PJM
CLTF
0.437

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.92 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6576.66
MW Contribution:
9.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.422
315244AE2-183_ST
50/50
7.881
963041AG1-153 GEN
50/50
7.256
315779AE2-040
50/50
3.633
3151081ELIZAR1
50/50
24.693
3151091ELIZAR2
50/50
24.264
941591AE2-156 GEN
50/50
22.557
970533AG2-339 GEN
Solar/Wind Harmer
21.389
970673AG2-436 GEN
Solar/Wind Harmer
68.838
316233AE1-074 FULL
Solar/Wind Harmer
0.842
971281AH1-106 GEN
Solar/Wind Harmer
5.087
971283AH1-107 GEN
Solar/Wind Harmer
5.087
971967AH1-528 GEN
Solar/Wind Harmer
57.688
316258AE1-075 C
Solar/Wind Harmer
0.716
316405AF2-144 C
Solar/Wind Harmer
0.756
315814AE2-033 C
Solar/Wind Harmer
27.128
970085AG2-068 GEN
Solar/Wind Harmer
18.156
970581AG2-369 GEN
Solar/Wind Harmer
15.614
3143316POE
Solar/Wind Harmer
-0.114
316316AC1-027 C
Solar/Wind Harmer
0.873
316018AA1-139 ULT2
Solar/Wind Harmer
2.426
957871AF2-081 GEN
Solar/Wind Harmer
14.195
3146406KITTY HAWK
Solar/Wind Harmer
0.024
970657AG2-426 GEN
Solar/Wind Harmer
1.774
315833AF1-017_GEN
Solar/Wind Harmer
5.342
316311AC2-079 GEN
Solar/Wind Harmer
14.19
313526AB2-022
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.028
3146486SUNBURY
Solar/Wind Harmer
-0.028
3146396TANGLEW
Solar/Wind Harmer
0.516
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971285AH1-108 GEN
Adder
1.88
316236AE1-162_GEN
Solar/Wind Harmer
0.837
315839AE2-212 C
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
17.195
3151201GRAVEL4
Adder
17.753
3151221GRAVEL6
Adder
17.732
3151191GRAVEL3
Adder
17.528
3151211GRAVEL5
Adder
17.528
315800Z1-036_GEN1
Solar/Wind Harmer
6.767
3130156CHOWAN
Solar/Wind Harmer
-0.027
3130156CHOWAN
Solar/Wind Harmer
-0.027
315697AD1-025 GEN
Solar/Wind Harmer
5.452
316486AD2-202 GEN
Solar/Wind Harmer
0.681
946281AF1-292 GEN
Solar/Wind Harmer
0.594
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
315732AD1-074 GEN1
Solar/Wind Harmer
5.341
315733AD1-074 GEN2
Solar/Wind Harmer
5.341
316318V4-068
Solar/Wind Harmer
0.657
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
-0.026
3146206CASHIE
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
11.504
3146043SEABORD
Solar/Wind Harmer
-0.026
316463AE2-346 GEN
Solar/Wind Harmer
0.421
3145513AHOSKIE
Solar/Wind Harmer
0.227
961941AG1-037 GEN
Solar/Wind Harmer
0.196
3145513AHOSKIE
Solar/Wind Harmer
-0.026
3137643SOCKMAN
Solar/Wind Harmer
-0.103
3145683EARLEYS
Solar/Wind Harmer
-0.052
3145683EARLEYS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
315652AC1-086 GEN
Solar/Wind Harmer
29.162
316426AA2-053 GEN
Solar/Wind Harmer
2.6
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Harmer
0.768
316159AE1-175 C
Solar/Wind Harmer
0.684
316174AB2-169 GEN
Solar/Wind Harmer
3.897
970831AG2-522 GEN
Solar/Wind Harmer
12.628
3146033SCOT NK
Solar/Wind Harmer
-0.1
316210AC1-098 GEN
Solar/Wind Harmer
3.903
316274AC1-208 GEN
Solar/Wind Harmer
2.671
3144303KENBRDG
Solar/Wind Harmer
-0.02
970683AG2-441 GEN
Solar/Wind Harmer
17.496
970681AG2-440 GEN
Solar/Wind Harmer
11.612
946301AF1-294 GEN
Solar/Wind Harmer
6.347
961791AG1-021 GEN
Solar/Wind Harmer
3.096
3147346CASHSCORNER
Solar/Wind Harmer
0.383
316238AB2-078_GEN
Solar/Wind Harmer
0.743
316239AB2-077_GEN
Solar/Wind Harmer
0.743
957831AF2-077 GEN
Solar/Wind Harmer
0.74
3138283WHITEMARSH
Solar/Wind Harmer
0.038
3145746EVERETS
Solar/Wind Harmer
-0.096
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316327AA2-057 GEN
Solar/Wind Harmer
2.436
957861AF2-080 GEN
Solar/Wind Harmer
10.486
971845AH1-439 GEN
Solar/Wind Harmer
12.658
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
316322AB2-045
Solar/Wind Harmer
0.797
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
3143873LANEXA
Solar/Wind Harmer
-0.014
316059AD1-063 C
Solar/Wind Harmer
0.513
3147173SINAI
Solar/Wind Harmer
-0.023
3147243WELCO
Solar/Wind Harmer
-0.014
957601AF2-054 GEN
Solar/Wind Harmer
0.679
3141873WAN 176
Solar/Wind Harmer
-0.004
972205AH1-687 GEN
Adder
8.563
3141913WHIT STONE
Solar/Wind Harmer
-0.022
3138133OCRAN
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.154
226929AD2-058 GEN
Solar/Wind Helper
0.089
315242AE2-183_GT2
50/50
4.538
315241AE2-183_GT1
50/50
4.526
972185AH1-677 GEN
50/50
16.405
3151041BRUNSWICKG3
50/50
3.584
972187AH1-678 GEN
50/50
8.224
3150991CHESPKB
50/50
2.818
3150991CHESPKB
50/50
2.751
971223AH1-071 GEN
Solar/Wind Harmer
4.283
3143526WINTERP
Solar/Wind Harmer
-0.162
970933AG2-581 GEN
Solar/Wind Harmer
28.183
316313AB2-026
Solar/Wind Harmer
0.795
3144356SAPONY
Solar/Wind Harmer
1.02
316315AB2-025 C
Solar/Wind Harmer
0.787
316294AC1-161 GEN
Solar/Wind Harmer
9.323
316185AD1-033 GEN
Solar/Wind Harmer
3.002
3145506HICKORY
Solar/Wind Harmer
-0.113
3145506HICKORY
Solar/Wind Harmer
-0.068
3145506HICKORY
Solar/Wind Harmer
-0.017
316339AD2-160 GEN
Solar/Wind Harmer
1.911
316388AE2-253 GEN
Solar/Wind Harmer
1.911
3137176SLIGO L2192
Solar/Wind Harmer
-0.112
3146456SLIGO L269
Solar/Wind Harmer
3.348
316336AC2-165 C
Solar/Wind Harmer
17.698
3130086AYDLETT
Solar/Wind Harmer
-0.113
316083AB2-161 GEN
Solar/Wind Harmer
4.565
316349AD2-085 GEN
Solar/Wind Harmer
2.497
315835AF2-110_GEN
Solar/Wind Harmer
3.516
3146386ELIZ CT
Solar/Wind Harmer
-0.028
970099AG2-077 GEN
Solar/Wind Harmer
35.063
316431W1029_GEN1
Solar/Wind Harmer
5.052
316433W1029_GEN2
Solar/Wind Harmer
5.052
316435W1029_GEN3
Solar/Wind Harmer
5.052
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.028
315742AE1-103 GEN
Solar/Wind Harmer
6.515
3146376EDENTON
Solar/Wind Harmer
0.81
3146376EDENTON
Solar/Wind Harmer
0.81
316240AF1-291 C
Solar/Wind Harmer
0.816
316365GEN2_N
Solar/Wind Harmer
1.821
316033AB2-134 GEN
Solar/Wind Harmer
8.699
944641AF1-129 GEN
Adder
114.245
315614AA2-178 GEN
Solar/Wind Harmer
2.89
3151731LOISA B
Adder
15.34
3145893MURPHYS
Solar/Wind Harmer
0.736
3145893MURPHYS
Solar/Wind Harmer
-0.047
316065AD1-022 GEN
Solar/Wind Harmer
13.178
313506AB2-031 GEN
Solar/Wind Harmer
2.099
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
316140AB2-099
Solar/Wind Harmer
0.175
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
962571AG1-106 GEN
Solar/Wind Harmer
3.726
970301AG2-198 GEN
Solar/Wind Harmer
12.953
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
0.214
3145783HORNRTN
Solar/Wind Harmer
3.041
3145783HORNRTN
Solar/Wind Harmer
2.433
3145783HORNRTN
Solar/Wind Harmer
0.76
3145783HORNRTN
Solar/Wind Harmer
0.304
3145796HORNRTN
Solar/Wind Harmer
-0.076
315687AD1-152 GEN
Solar/Wind Harmer
3.044
3142946ENON
Solar/Wind Harmer
-0.003
313527AB2-043 GEN
Solar/Wind Harmer
4.024
970323AG2-213 GEN
Solar/Wind Harmer
12.389
958211AF2-115 GEN
Solar/Wind Harmer
3.87
3144293JTRSVLE
Adder
0.526
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
316237AB2-079_GEN
Solar/Wind Harmer
0.743
3145933PARMELE
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.025
3142366NRTHEST
Adder
0.711
315724AD1-057 GEN
Solar/Wind Harmer
4.774
3150691DARBY 3
Adder
15.576
3150701DARBY 4
Adder
15.539
3150681DARBY 2
Adder
15.521
3150671DARBY 1
Adder
15.503
316005AA1-067
Solar/Wind Harmer
0.489
315976AC1-164 GENA
Solar/Wind Harmer
5.442
316169AC1-164_GENC
Solar/Wind Harmer
4.702
962561AG1-105 GEN
Solar/Wind Harmer
13.368
3146776BUCKING
Solar/Wind Harmer
-0.094
3146776BUCKING
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.367
3145453TOT5
Solar/Wind Harmer
0.22
3145603CNETO
Solar/Wind Harmer
0.147
964791AG1-342 GEN
Solar/Wind Harmer
5.037
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
961601AG1-000A GEN
Solar/Wind Harmer
9.214
316049AB1-081 GEN
Solar/Wind Harmer
2.522
316263AC1-034 GEN
Solar/Wind Harmer
10.986
316118AC1-105 GEN
Solar/Wind Harmer
1.587
316441AF1-014 GEN
Solar/Wind Harmer
1.543
316312AB1-027
Solar/Wind Harmer
0.767
315666AE1-190 GEN
Solar/Wind Harmer
0.685
316248AF1-058 C
Solar/Wind Harmer
0.683
316156AD2-030 GEN
Solar/Wind Harmer
0.604
3142296MT RD221
Adder
0.636
966001AG1-469 GEN
Solar/Wind Harmer
0.412
3150341NORNECKC1
Adder
1.676
3150341NORNECKC1
Adder
1.663
972189AH1-679 GEN
Adder
2.224
972193AH1-681 GEN
Adder
2.816
316045AC1-158 PL2
Solar/Wind Helper
11.245
316450AC1-158 RIC
Solar/Wind Helper
0.937
316411AF1-147_GEN1
Solar/Wind Helper
0.851
3152261N ANNA2
50/50
31.565
3151031BRUNSWICKG2
50/50
3.584
3151101ELIZAR3
50/50
25.009
3151771S ANNAG1
50/50
0.877
3147666LOUISA
Solar/Wind Harmer
-0.108
944011AF1-069 GEN
Solar/Wind Harmer
18.686
3143336POWHATN
Solar/Wind Harmer
2.983
970917AG2-570 GEN
Solar/Wind Harmer
73.596
944581AF1-123 GEN
Solar/Wind Harmer
130.558
944601AF1-125 GEN
Solar/Wind Harmer
128.52
3142956BIRDNECK
Solar/Wind Harmer
1.529
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
2.291
3146456SLIGO L269
Solar/Wind Harmer
-0.028
971153AH1-033 GEN
Solar/Wind Harmer
3.28
3144536CHRHLND
Solar/Wind Harmer
-0.004
316305AF2-043 C
Solar/Wind Harmer
0.85
316246AF1-032 C
Solar/Wind Harmer
0.57
315813AE1-149 C
Solar/Wind Harmer
17.597
970657AG2-426 GEN
Solar/Wind Harmer
5.685
316320Y1-086
Solar/Wind Harmer
1.647
316321Z2-027
Solar/Wind Harmer
0.754
3150861SPRUNCD
Adder
1.149
3146516WINFALL
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.011
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3145273HOLLAND
Solar/Wind Harmer
-0.021
3151171GRAVELC
Adder
3.412
3146376EDENTON
Solar/Wind Harmer
-0.027
961611AG1-000B GEN
Solar/Wind Harmer
5.739
316478AD1-087 GEN
Solar/Wind Harmer
2.326
315778AD1-151 GEN
Solar/Wind Harmer
23.962
316458AB2-190 GEN2
Solar/Wind Harmer
2.702
3156081AA2-088 GEN
Solar/Wind Harmer
8.64
3151761LOISA E
Adder
31.273
3151721LOISA A
Adder
15.26
970133AG2-095 GEN
Solar/Wind Harmer
2.986
966621AG1-532 GEN
Solar/Wind Harmer
0.539
3144216WINCHST
Adder
0.89
315735AD1-075 GEN1
Solar/Wind Harmer
2.67
3150921YORKTN3
Adder
5.9
3145893MURPHYS
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.026
3146206CASHIE
Solar/Wind Harmer
-0.026
316181AB2-040 GEN
Solar/Wind Harmer
3.646
3146173TUNIS
Solar/Wind Harmer
-0.026
3147043LAWRENC
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
316011AB1-132 GEN
Solar/Wind Harmer
5.414
3146263WOODLND
Solar/Wind Harmer
-0.026
316190AA2-174 GEN
Solar/Wind Harmer
0.317
3143096IRON208
Adder
0.961
3143096IRON208
Adder
0.942
316317KELFORD C
Solar/Wind Harmer
1.184
3145823KELFORD
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.025
3142946ENON
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
2.168
964241AG1-285 GEN
Solar/Wind Harmer
19.363
970257AG2-171 GEN
Solar/Wind Harmer
9.291
971775AH1-396 GEN
Solar/Wind Harmer
1.748
959311AF2-222 GEN
Solar/Wind Harmer
25.861
3144293JTRSVLE
Adder
0.526
3147133PAMPLIN
Solar/Wind Harmer
-0.077
942461AE2-259 GEN
Solar/Wind Harmer
3.722
3152251N ANNA1
50/50
31.549
970119AG2-088 GEN
50/50
40.661
315243AE2-183_GT3
50/50
4.538
3151051BRUNSWICKS1
50/50
7.441
3151021BRUNSWICKG1
50/50
3.584
971451AH1-221 GEN
50/50
10.884
3150981CHESPKA
50/50
3.359
3151781S ANNAS1
50/50
0.45
3147666LOUISA
Solar/Wind Harmer
-0.188
316192AB2-158 GEN
Solar/Wind Harmer
5.459
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
30.184
941031AE2-094 GEN
Solar/Wind Harmer
59.637
3143526WINTERP
Solar/Wind Harmer
-0.162
939411AE1-173 GEN
Solar/Wind Harmer
156.409
3143336POWHATN
Solar/Wind Harmer
3.509
970919AG2-571 GEN
Solar/Wind Harmer
9.316
970087AG2-069 GEN
Solar/Wind Harmer
27.234
315773AC2-141 GEN
Solar/Wind Harmer
12.062
944591AF1-124 GEN
Solar/Wind Harmer
131.028
316375AC2-012 GEN
Solar/Wind Harmer
9.852
316036AC1-147 C
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.028
319010AE1-072 C
Solar/Wind Harmer
5.718
316381AD1-082 GEN
Solar/Wind Harmer
2.574
316093AE2-104_GEN
Solar/Wind Harmer
8.178
957481AF2-042 GEN
Solar/Wind Harmer
87.657
3150851SPRUNCC
Adder
1.149
316072AD1-144
Solar/Wind Harmer
0.564
3146516WINFALL
Solar/Wind Harmer
-0.09
3146516WINFALL
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.111
315693AD1-088 GEN
Solar/Wind Harmer
13.738
3151171GRAVELC
Adder
2.594
315611Z1-036_GEN2
Solar/Wind Harmer
6.767
3130156CHOWAN
Solar/Wind Harmer
-0.027
961611AG1-000B GEN
Solar/Wind Harmer
13.45
315671AE2-027_GEN
Solar/Wind Harmer
4.916
316023GEN1_S
Solar/Wind Harmer
1.821
316369SG1_INVT
Solar/Wind Harmer
4.818
971069AG2-661 GEN
Solar/Wind Harmer
4.26
315816AE2-034 GEN
Solar/Wind Harmer
2.168
3145663CRESWEL
Solar/Wind Harmer
-0.075
971163AH1-040 GEN
Solar/Wind Harmer
25.183
316132AB2-190 GEN1
Solar/Wind Harmer
2.702
3151751LOISA D
Adder
15.34
960081AF2-299 GEN
Solar/Wind Harmer
2.986
3146926FARMVIL
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.025
315722AD1-056 GEN
Solar/Wind Harmer
8.68
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970293AG2-193 GEN
Solar/Wind Harmer
3.011
316075AC2-137 C
Solar/Wind Harmer
0.641
316420AA1-050 GEN
Solar/Wind Harmer
2.715
3146233WITAKRS
Solar/Wind Harmer
0.498
3146233WITAKRS
Solar/Wind Harmer
-0.016
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
3138543CONSLDL
Solar/Wind Harmer
-0.016
3146776BUCKING
Solar/Wind Harmer
-0.008
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.331
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3141843SHACKLE
Adder
1.041
316203AE2-005 GEN
Solar/Wind Harmer
9.649
3142416OLDCHRC
Solar/Wind Harmer
2.302
3141766HARMONY
Solar/Wind Harmer
2.024
3141873WAN 176
Solar/Wind Harmer
2.693
972003AH1-546 GEN
Solar/Wind Harmer
9.207
316003AC1-222 GEN
Solar/Wind Harmer
2.119
3150351NORNECKC2
Adder
1.623
972255AH1-712 GEN
Adder
63.02
3141196NOKESVL
Solar/Wind Helper
1.08
227287AC2-120 GEN
Solar/Wind Helper
0.306
226910AB2-157 C
Solar/Wind Helper
0.013
970221AG2-151 GEN
Solar/Wind Harmer
11.852
3138126ROCKLANDING
Solar/Wind Harmer
0.081
315737AD1-076 GEN
Solar/Wind Harmer
5.021
3142543TWELFTH
Solar/Wind Harmer
-0.003
3145893MURPHYS
Solar/Wind Harmer
-0.105
3145893MURPHYS
Solar/Wind Harmer
0.782
3146206CASHIE
Solar/Wind Harmer
-0.026
971547AH1-271 GEN
Solar/Wind Harmer
6.574
316087AB2-174 GEN
Solar/Wind Harmer
3.744
3146173TUNIS
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.628
3156021HOLLOMANSOL
Solar/Wind Harmer
3.5
3147043LAWRENC
Adder
2.094
3145683EARLEYS
Solar/Wind Harmer
-0.026
3146263WOODLND
Solar/Wind Harmer
-0.026
3143096IRON208
Adder
0.961
971317AH1-138 GEN
Solar/Wind Harmer
3.219
3145783HORNRTN
Solar/Wind Harmer
-0.026
3145823KELFORD
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.025
944631AF1-128 GEN
Adder
107.855
970937AG2-583 GEN
Solar/Wind Harmer
18.106
316129AC1-054 GEN
Solar/Wind Harmer
2.202
971065AG2-659 GEN
Solar/Wind Harmer
12.568
316131AB2-060 GEN
Solar/Wind Harmer
2.667
315785AD2-033 C
Solar/Wind Harmer
5.606
316034AC1-036 C
Solar/Wind Harmer
0.458
970685AG2-442 GEN
Solar/Wind Harmer
21.675
971563AH1-280 GEN
Solar/Wind Harmer
3.096
3144293JTRSVLE
Adder
0.526
3144293JTRSVLE
Adder
0.415
3146926FARMVIL
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.153
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316494AC1-189 GEN
Solar/Wind Harmer
2.579
315975AC1-164 GENB
Solar/Wind Harmer
0.161
316319Z2-044 C
Solar/Wind Harmer
1.315
3146233WITAKRS
Solar/Wind Harmer
-0.094
3142433PROV 92
Solar/Wind Harmer
-0.095
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
3146776BUCKING
Solar/Wind Harmer
-0.009
961671AG1-007 GEN
Solar/Wind Harmer
0.3
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.704
970401AG2-262 GEN
Solar/Wind Harmer
1.539
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.152
3142053HEARTS
Solar/Wind Harmer
0.275
971777AH1-397 GEN
Solar/Wind Harmer
2.671
3142416OLDCHRC
Solar/Wind Harmer
-0.059
3142416OLDCHRC
Solar/Wind Harmer
-0.023
315662AE1-191 GEN
Solar/Wind Harmer
2.742
316280AD1-041 GEN
Solar/Wind Harmer
1.714
316314AB2-024 C
Solar/Wind Harmer
1.946
3141766HARMONY
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.013
3150351NORNECKC2
Adder
1.596
972277AH1-723 GEN
Adder
73.438
316447AC1-158 HLD
Solar/Wind Helper
7.733
316044AC1-158 PL1
Solar/Wind Helper
3.514
316415AF1-147_GEN2
Solar/Wind Helper
0.851
LAGNLTFEXP_LAGN->PJM
CLTF
9.785
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.34
TVALTFEXP_TVA->PJM
CLTF
4.945
CPLELTFEXP_CPLE->PJM
CLTF
13.857
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.882
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.551
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.863
MECLTFEXP_MEC->PJM
CLTF
4.525
SIGELTFEXP_SIGE->PJM
CLTF
0.138
NYPJM->LTFIMP_NY
CLTF
3.849
LGEELTFEXP_LGEE->PJM
CLTF
1.663
WECLTFEXP_WEC->PJM
CLTF
0.817

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 57502_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57502_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:158.88 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4954.02
MW Contribution:
7.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
3.727
315241AE2-183_GT1
50/50
3.717
972185AH1-677 GEN
50/50
13.473
3151041BRUNSWICKG3
50/50
2.941
972187AH1-678 GEN
50/50
6.747
3151731LOISA B
50/50
14.467
971223AH1-071 GEN
Solar/Wind Harmer
3.552
3143526WINTERP
Solar/Wind Harmer
-0.128
970933AG2-581 GEN
Solar/Wind Harmer
23.075
316313AB2-026
Solar/Wind Harmer
0.649
3144356SAPONY
Solar/Wind Harmer
0.804
316315AB2-025 C
Solar/Wind Harmer
0.62
316336AC2-165 C
Solar/Wind Harmer
14.373
970099AG2-077 GEN
Solar/Wind Harmer
28.51
316294AC1-161 GEN
Solar/Wind Harmer
6.928
316185AD1-033 GEN
Solar/Wind Harmer
2.246
3145506HICKORY
Solar/Wind Harmer
-0.085
3145506HICKORY
Solar/Wind Harmer
-0.051
3145506HICKORY
Solar/Wind Harmer
-0.013
316339AD2-160 GEN
Solar/Wind Harmer
1.431
316388AE2-253 GEN
Solar/Wind Harmer
1.431
3150991CHESPKB
Adder
1.982
3150991CHESPKB
Adder
1.934
3137176SLIGO L2192
Solar/Wind Harmer
-0.084
3146456SLIGO L269
Solar/Wind Harmer
2.508
3130086AYDLETT
Solar/Wind Harmer
-0.084
316365GEN2_N
Solar/Wind Harmer
1.426
315835AF2-110_GEN
Solar/Wind Harmer
2.639
3146386ELIZ CT
Solar/Wind Harmer
-0.021
316349AD2-085 GEN
Solar/Wind Harmer
1.874
316083AB2-161 GEN
Solar/Wind Harmer
3.422
316431W1029_GEN1
Solar/Wind Harmer
3.799
316433W1029_GEN2
Solar/Wind Harmer
3.799
316435W1029_GEN3
Solar/Wind Harmer
3.799
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
970301AG2-198 GEN
Solar/Wind Harmer
10.413
315742AE1-103 GEN
Solar/Wind Harmer
4.937
3152261N ANNA2
50/50
32.032
3151031BRUNSWICKG2
50/50
2.941
3151771S ANNAG1
50/50
0.78
3151801S ANNAS2
50/50
0.401
3151761LOISA E
50/50
29.494
3151721LOISA A
50/50
14.392
3147666LOUISA
Solar/Wind Harmer
-0.097
944011AF1-069 GEN
Solar/Wind Harmer
15.379
3143336POWHATN
Solar/Wind Harmer
2.435
970917AG2-570 GEN
Solar/Wind Harmer
60.216
316478AD1-087 GEN
Solar/Wind Harmer
1.884
944581AF1-123 GEN
Solar/Wind Harmer
97.75
944601AF1-125 GEN
Solar/Wind Harmer
96.225
3142956BIRDNECK
Solar/Wind Harmer
1.143
3151101ELIZAR3
Adder
17.595
316017AA1-139 ULT1
Solar/Wind Harmer
1.716
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.021
971153AH1-033 GEN
Solar/Wind Harmer
2.458
316305AF2-043 C
Solar/Wind Harmer
0.637
316246AF1-032 C
Solar/Wind Harmer
0.427
316320Y1-086
Solar/Wind Harmer
1.236
970657AG2-426 GEN
Solar/Wind Harmer
4.262
315813AE1-149 C
Solar/Wind Harmer
13.182
316321Z2-027
Solar/Wind Harmer
0.566
3144536CHRHLND
Solar/Wind Harmer
-0.003
3146516WINFALL
Solar/Wind Harmer
-0.021
3145273HOLLAND
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.021
966621AG1-532 GEN
Solar/Wind Harmer
0.422
3150861SPRUNCD
Adder
0.848
3146376EDENTON
Solar/Wind Harmer
-0.021
3147043LAWRENC
Solar/Wind Harmer
-0.012
316181AB2-040 GEN
Solar/Wind Harmer
2.851
3145336SMITFLD
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
6.624
3145893MURPHYS
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
-0.02
316011AB1-132 GEN
Solar/Wind Harmer
4.218
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
315735AD1-075 GEN1
Solar/Wind Harmer
2.034
3146173TUNIS
Solar/Wind Harmer
-0.02
3146206CASHIE
Solar/Wind Harmer
-0.02
316190AA2-174 GEN
Solar/Wind Harmer
0.246
3146263WOODLND
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
2.481
3145796HORNRTN
Solar/Wind Harmer
-0.079
3145796HORNRTN
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.012
942461AE2-259 GEN
Solar/Wind Harmer
2.969
3147133PAMPLIN
Solar/Wind Harmer
-0.062
3144293JTRSVLE
Adder
0.42
959311AF2-222 GEN
Solar/Wind Harmer
20.609
961611AG1-000B GEN
Solar/Wind Harmer
4.158
970257AG2-171 GEN
Solar/Wind Harmer
7.404
316303AF2-085
50/50
4.496
315244AE2-183_ST
50/50
6.472
963041AG1-153 GEN
50/50
5.954
315779AE2-040
50/50
2.863
970533AG2-339 GEN
Solar/Wind Harmer
17.603
970673AG2-436 GEN
Solar/Wind Harmer
56.607
971967AH1-528 GEN
Solar/Wind Harmer
47.325
316233AE1-074 FULL
Solar/Wind Harmer
0.665
971281AH1-106 GEN
Solar/Wind Harmer
4.017
971283AH1-107 GEN
Solar/Wind Harmer
4.017
316258AE1-075 C
Solar/Wind Harmer
0.584
316405AF2-144 C
Solar/Wind Harmer
0.617
970085AG2-068 GEN
Solar/Wind Harmer
14.84
970581AG2-369 GEN
Solar/Wind Harmer
12.763
315814AE2-033 C
Solar/Wind Harmer
21.375
3143316POE
Solar/Wind Harmer
-0.087
316486AD2-202 GEN
Solar/Wind Harmer
0.552
3147346CASHSCORNER
Solar/Wind Harmer
0.337
971775AH1-396 GEN
Solar/Wind Harmer
1.393
964241AG1-285 GEN
Solar/Wind Harmer
15.423
316317KELFORD C
Solar/Wind Harmer
0.913
3145823KELFORD
Solar/Wind Harmer
-0.02
3145963POPLR C
Solar/Wind Harmer
-0.019
316212AC1-099_GEN
Solar/Wind Harmer
1.683
315778AD1-151 GEN
Solar/Wind Harmer
17.212
316458AB2-190 GEN2
Solar/Wind Harmer
1.934
315722AD1-056 GEN
Solar/Wind Harmer
6.769
3145933PARMELE
Solar/Wind Harmer
-0.019
970133AG2-095 GEN
Solar/Wind Harmer
2.123
3146776BUCKING
Solar/Wind Harmer
-0.007
3144216WINCHST
Adder
0.629
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
3150921YORKTN3
Adder
4.155
3146233WITAKRS
Solar/Wind Harmer
0.389
3146233WITAKRS
Solar/Wind Harmer
-0.012
3138543CONSLDL
Solar/Wind Harmer
-0.012
316420AA1-050 GEN
Solar/Wind Harmer
2.109
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145543BTLEBRO
Solar/Wind Harmer
-0.018
961601AG1-000A GEN
Solar/Wind Harmer
7.281
972003AH1-546 GEN
Solar/Wind Harmer
7.25
3143096IRON208
Adder
0.664
3143096IRON208
Adder
0.651
316003AC1-222 GEN
Solar/Wind Harmer
1.679
3142946ENON
Solar/Wind Harmer
-0.006
970221AG2-151 GEN
Solar/Wind Harmer
10.195
971683AH1-343 GEN
Solar/Wind Harmer
7.022
316222AC1-221 GEN
Solar/Wind Harmer
1.638
316283AC2-100 C
Solar/Wind Harmer
1.52
3142433PROV 92
Adder
0.279
3142433PROV 92
Adder
0.279
970293AG2-193 GEN
Solar/Wind Harmer
1.954
3141843SHACKLE
Adder
0.702
316203AE2-005 GEN
Solar/Wind Harmer
6.509
3141873WAN 176
Solar/Wind Harmer
1.128
316316AC1-027 C
Solar/Wind Harmer
0.653
3151081ELIZAR1
Adder
17.373
3151091ELIZAR2
Adder
17.071
316018AA1-139 ULT2
Solar/Wind Harmer
1.817
957871AF2-081 GEN
Solar/Wind Harmer
10.633
3146406KITTY HAWK
Solar/Wind Harmer
0.018
313526AB2-022
Solar/Wind Harmer
0.568
315833AF1-017_GEN
Solar/Wind Harmer
4.008
316311AC2-079 GEN
Solar/Wind Harmer
10.646
970657AG2-426 GEN
Solar/Wind Harmer
1.33
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146396TANGLEW
Solar/Wind Harmer
0.387
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
946281AF1-292 GEN
Solar/Wind Harmer
0.466
315800Z1-036_GEN1
Solar/Wind Harmer
5.111
971285AH1-108 GEN
Adder
1.387
3130156CHOWAN
Solar/Wind Harmer
-0.021
3130156CHOWAN
Solar/Wind Harmer
-0.021
315839AE2-212 C
Solar/Wind Harmer
0.62
316236AE1-162_GEN
Solar/Wind Harmer
0.615
971445AH1-216 GEN
Solar/Wind Harmer
12.622
3137643SOCKMAN
Solar/Wind Harmer
-0.081
316318V4-068
Solar/Wind Harmer
0.505
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
-0.02
3146043SEABORD
Solar/Wind Harmer
-0.02
3130546PLYMOUTH
Solar/Wind Harmer
-0.02
315652AC1-086 GEN
Solar/Wind Harmer
22.722
315732AD1-074 GEN1
Solar/Wind Harmer
4.069
315733AD1-074 GEN2
Solar/Wind Harmer
4.069
3146206CASHIE
Solar/Wind Harmer
-0.02
970601AG2-382 GEN
Solar/Wind Harmer
8.788
316426AA2-053 GEN
Solar/Wind Harmer
2.022
316463AE2-346 GEN
Solar/Wind Harmer
0.323
3145513AHOSKIE
Solar/Wind Harmer
0.175
961941AG1-037 GEN
Solar/Wind Harmer
0.151
3145513AHOSKIE
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.04
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
3151201GRAVEL4
Adder
12.911
3151221GRAVEL6
Adder
12.896
3151191GRAVEL3
Adder
12.748
3151211GRAVEL5
Adder
12.748
3145796HORNRTN
Solar/Wind Harmer
-0.063
3145796HORNRTN
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
9.959
946301AF1-294 GEN
Solar/Wind Harmer
5.06
961791AG1-021 GEN
Solar/Wind Harmer
2.468
970683AG2-441 GEN
Solar/Wind Harmer
13.946
970681AG2-440 GEN
Solar/Wind Harmer
9.256
3144303KENBRDG
Solar/Wind Harmer
-0.016
316238AB2-078_GEN
Solar/Wind Harmer
0.592
316239AB2-077_GEN
Solar/Wind Harmer
0.592
3146033SCOT NK
Solar/Wind Harmer
-0.078
315697AD1-025 GEN
Solar/Wind Harmer
3.926
316174AB2-169 GEN
Solar/Wind Harmer
2.991
316210AC1-098 GEN
Solar/Wind Harmer
3.03
316274AC1-208 GEN
Solar/Wind Harmer
2.078
971845AH1-439 GEN
Solar/Wind Harmer
10.047
316327AA2-057 GEN
Solar/Wind Harmer
1.898
316322AB2-045
Solar/Wind Harmer
0.632
3145746EVERETS
Solar/Wind Harmer
-0.074
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
957861AF2-080 GEN
Solar/Wind Harmer
8.131
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
972205AH1-687 GEN
Adder
6.735
316382AG1-145 C
Solar/Wind Harmer
0.524
316159AE1-175 C
Solar/Wind Harmer
0.466
957831AF2-077 GEN
Solar/Wind Harmer
0.513
3138283WHITEMARSH
Solar/Wind Harmer
0.026
3142433PROV 92
Adder
0.279
3142433PROV 92
Adder
0.279
3143873LANEXA
Solar/Wind Harmer
-0.009
957601AF2-054 GEN
Solar/Wind Harmer
0.46
3141873WAN 176
Solar/Wind Harmer
-0.003
3146376EDENTON
Solar/Wind Harmer
0.612
3146376EDENTON
Solar/Wind Harmer
0.612
313506AB2-031 GEN
Solar/Wind Harmer
1.641
315687AD1-152 GEN
Solar/Wind Harmer
2.453
315614AA2-178 GEN
Solar/Wind Harmer
2.194
3145893MURPHYS
Solar/Wind Harmer
0.565
3145893MURPHYS
Solar/Wind Harmer
-0.036
962571AG1-106 GEN
Solar/Wind Harmer
2.903
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.012
316065AD1-022 GEN
Solar/Wind Harmer
10.057
3146173TUNIS
Solar/Wind Harmer
-0.02
3146173TUNIS
Solar/Wind Harmer
-0.02
3145593CAROLNA
Solar/Wind Harmer
-0.02
3145593CAROLNA
Solar/Wind Harmer
-0.02
3145593CAROLNA
Solar/Wind Harmer
0.167
316140AB2-099
Solar/Wind Harmer
0.135
3145783HORNRTN
Solar/Wind Harmer
2.37
3145783HORNRTN
Solar/Wind Harmer
1.896
3145783HORNRTN
Solar/Wind Harmer
0.592
3145783HORNRTN
Solar/Wind Harmer
0.237
3145796HORNRTN
Solar/Wind Harmer
-0.059
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3147133PAMPLIN
Solar/Wind Harmer
-0.016
958211AF2-115 GEN
Solar/Wind Harmer
3.086
3144293JTRSVLE
Adder
0.42
970323AG2-213 GEN
Solar/Wind Harmer
9.872
313527AB2-043 GEN
Solar/Wind Harmer
3.205
316240AF1-291 C
Solar/Wind Harmer
0.593
316237AB2-079_GEN
Solar/Wind Harmer
0.592
966001AG1-469 GEN
Solar/Wind Harmer
0.368
316033AB2-134 GEN
Solar/Wind Harmer
6.264
944641AF1-129 GEN
Adder
82.444
315724AD1-057 GEN
Solar/Wind Harmer
3.723
3145933PARMELE
Solar/Wind Harmer
-0.038
3145933PARMELE
Solar/Wind Harmer
-0.019
962561AG1-105 GEN
Solar/Wind Harmer
10.642
3146776BUCKING
Solar/Wind Harmer
-0.075
3146776BUCKING
Solar/Wind Harmer
-0.006
964791AG1-342 GEN
Solar/Wind Harmer
4.01
3146843MT LREL
Solar/Wind Harmer
-0.019
3146843MT LREL
Solar/Wind Harmer
-0.019
316005AA1-067
Solar/Wind Harmer
0.378
3145493TOT1
Solar/Wind Harmer
0.285
3145453TOT5
Solar/Wind Harmer
0.171
3145603CNETO
Solar/Wind Harmer
0.114
316118AC1-105 GEN
Solar/Wind Harmer
1.263
316049AB1-081 GEN
Solar/Wind Harmer
1.968
961601AG1-000A GEN
Solar/Wind Harmer
7.19
316263AC1-034 GEN
Solar/Wind Harmer
8.574
316248AF1-058 C
Solar/Wind Harmer
0.543
3142946ENON
Solar/Wind Harmer
-0.002
3142366NRTHEST
Adder
0.47
3150691DARBY 3
Adder
10.23
3150701DARBY 4
Adder
10.206
3150681DARBY 2
Adder
10.194
3150671DARBY 1
Adder
10.182
316441AF1-014 GEN
Solar/Wind Harmer
1.041
315666AE1-190 GEN
Solar/Wind Harmer
0.463
316156AD2-030 GEN
Solar/Wind Harmer
0.409
3142296MT RD221
Adder
0.387
316045AC1-158 PL2
Solar/Wind Helper
10.523
316450AC1-158 RIC
Solar/Wind Helper
0.877
3152251N ANNA1
50/50
32.016
970119AG2-088 GEN
50/50
33.717
315243AE2-183_GT3
50/50
3.727
3151051BRUNSWICKS1
50/50
6.105
3151021BRUNSWICKG1
50/50
2.941
971451AH1-221 GEN
50/50
8.93
3151791S ANNAG2
50/50
0.78
3151781S ANNAS1
50/50
0.401
3151741LOISA C
50/50
0.791
3151751LOISA D
50/50
14.467
3147666LOUISA
Solar/Wind Harmer
-0.169
316192AB2-158 GEN
Solar/Wind Harmer
4.913
3143226MDLTHAN
Solar/Wind Harmer
-0.028
941031AE2-094 GEN
Solar/Wind Harmer
49.08
940641AE2-051 GEN
Solar/Wind Harmer
24.496
939411AE1-173 GEN
Solar/Wind Harmer
124.678
3143526WINTERP
Solar/Wind Harmer
-0.128
3143336POWHATN
Solar/Wind Harmer
2.865
970919AG2-571 GEN
Solar/Wind Harmer
7.622
970087AG2-069 GEN
Solar/Wind Harmer
22.261
957481AF2-042 GEN
Solar/Wind Harmer
71.276
315693AD1-088 GEN
Solar/Wind Harmer
11.138
944591AF1-124 GEN
Solar/Wind Harmer
98.102
315773AC2-141 GEN
Solar/Wind Harmer
8.964
316375AC2-012 GEN
Solar/Wind Harmer
7.352
316036AC1-147 C
Solar/Wind Harmer
0.572
3150981CHESPKA
Adder
2.363
3146456SLIGO L269
Solar/Wind Harmer
-0.021
319010AE1-072 C
Solar/Wind Harmer
4.285
316023GEN1_S
Solar/Wind Harmer
1.426
316093AE2-104_GEN
Solar/Wind Harmer
6.139
316381AD1-082 GEN
Solar/Wind Harmer
1.929
3146516WINFALL
Solar/Wind Harmer
-0.067
3146516WINFALL
Solar/Wind Harmer
-0.021
960081AF2-299 GEN
Solar/Wind Harmer
2.341
316072AD1-144
Solar/Wind Harmer
0.419
315611Z1-036_GEN2
Solar/Wind Harmer
5.111
3150851SPRUNCC
Adder
0.848
3130156CHOWAN
Solar/Wind Harmer
-0.021
316087AB2-174 GEN
Solar/Wind Harmer
2.93
3147043LAWRENC
Adder
1.65
3145336SMITFLD
Solar/Wind Harmer
-0.081
315816AE2-034 GEN
Solar/Wind Harmer
1.645
3145663CRESWEL
Solar/Wind Harmer
-0.057
971163AH1-040 GEN
Solar/Wind Harmer
19.115
3145893MURPHYS
Solar/Wind Harmer
-0.081
3145893MURPHYS
Solar/Wind Harmer
0.601
315607AA1-063A GEN
Solar/Wind Harmer
2.036
315737AD1-076 GEN
Solar/Wind Harmer
3.825
970937AG2-583 GEN
Solar/Wind Harmer
14.48
3146173TUNIS
Solar/Wind Harmer
-0.02
3146206CASHIE
Solar/Wind Harmer
-0.02
971547AH1-271 GEN
Solar/Wind Harmer
5.021
3146263WOODLND
Solar/Wind Harmer
-0.02
3156021HOLLOMANSOL
Solar/Wind Harmer
2.684
3145783HORNRTN
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
1.887
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.02
315671AE2-027_GEN
Solar/Wind Harmer
3.594
316129AC1-054 GEN
Solar/Wind Harmer
1.739
971065AG2-659 GEN
Solar/Wind Harmer
9.938
3146926FARMVIL
Solar/Wind Harmer
-0.012
971563AH1-280 GEN
Solar/Wind Harmer
2.468
3144293JTRSVLE
Adder
0.42
3144293JTRSVLE
Adder
0.331
970685AG2-442 GEN
Solar/Wind Harmer
17.279
316034AC1-036 C
Solar/Wind Harmer
0.365
961611AG1-000B GEN
Solar/Wind Harmer
9.744
315785AD2-033 C
Solar/Wind Harmer
4.467
3145823KELFORD
Solar/Wind Harmer
-0.02
316131AB2-060 GEN
Solar/Wind Harmer
2.124
3145963POPLR C
Solar/Wind Harmer
-0.019
316369SG1_INVT
Solar/Wind Harmer
3.469
971069AG2-661 GEN
Solar/Wind Harmer
3.06
316132AB2-190 GEN1
Solar/Wind Harmer
1.934
3146293MARTNCO
Solar/Wind Harmer
0.118
3146776BUCKING
Solar/Wind Harmer
-0.007
970401AG2-262 GEN
Solar/Wind Harmer
1.225
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
3142543TWELFTH
Solar/Wind Harmer
-0.002
3138126ROCKLANDING
Solar/Wind Harmer
0.057
316494AC1-189 GEN
Solar/Wind Harmer
2
316319Z2-044 C
Solar/Wind Harmer
1.026
3146233WITAKRS
Solar/Wind Harmer
-0.073
961671AG1-007 GEN
Solar/Wind Harmer
0.233
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.547
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145543BTLEBRO
Solar/Wind Harmer
-0.015
316359AB2-059 GEN
Solar/Wind Harmer
2.46
3142053HEARTS
Solar/Wind Harmer
0.215
971317AH1-138 GEN
Solar/Wind Harmer
2.237
3143096IRON208
Adder
0.664
944631AF1-128 GEN
Adder
73.66
971377AH1-170 GEN
Solar/Wind Harmer
2.039
3147623JAMES R
Solar/Wind Harmer
0.252
3142433PROV 92
Solar/Wind Harmer
-0.064
3142433PROV 92
Adder
0.279
3142433PROV 92
Adder
0.279
971777AH1-397 GEN
Solar/Wind Harmer
1.802
315662AE1-191 GEN
Solar/Wind Harmer
1.853
316280AD1-041 GEN
Solar/Wind Harmer
1.158
316447AC1-158 HLD
Solar/Wind Helper
7.236
316044AC1-158 PL1
Solar/Wind Helper
3.288
LAGNLTFEXP_LAGN->PJM
CLTF
7.093
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.402
TVALTFEXP_TVA->PJM
CLTF
3.576
CPLELTFEXP_CPLE->PJM
CLTF
10.857
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.818
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.07
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.068
MECLTFEXP_MEC->PJM
CLTF
3.021
SIGELTFEXP_SIGE->PJM
CLTF
0.091
NYPJM->LTFIMP_NY
CLTF
2.894
LGEELTFEXP_LGEE->PJM
CLTF
1.073
WECLTFEXP_WEC->PJM
CLTF
0.519

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:154.87 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4987.58
MW Contribution:
5.88
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.718
971285AH1-108 GEN
50/50
1.988
972263AH1-716 GEN
50/50
138.906
3151081ELIZAR1
50/50
23.355
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971281AH1-106 GEN
Solar/Wind Harmer
3.576
971283AH1-107 GEN
Solar/Wind Harmer
3.576
3143316POE
Solar/Wind Harmer
0.962
970533AG2-339 GEN
Solar/Wind Harmer
18.309
3151091ELIZAR2
Adder
21.627
315697AD1-025 GEN
Solar/Wind Harmer
0.258
970673AG2-436 GEN
Solar/Wind Harmer
29.845
316316AC1-027 C
Solar/Wind Harmer
0.228
971445AH1-216 GEN
Solar/Wind Harmer
16.871
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3151201GRAVEL4
Adder
17.422
3151221GRAVEL6
Adder
17.402
3151191GRAVEL3
Adder
17.202
3151211GRAVEL5
Adder
17.202
957871AF2-081 GEN
Solar/Wind Harmer
11.848
316311AC2-079 GEN
Solar/Wind Harmer
6.816
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316159AE1-175 C
Solar/Wind Harmer
0.202
313526AB2-022
Solar/Wind Harmer
0.125
315814AE2-033 C
Solar/Wind Harmer
18.566
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
3146396TANGLEW
Solar/Wind Harmer
0.646
3145176PASQUOTANK
Solar/Wind Harmer
0.145
971967AH1-528 GEN
Solar/Wind Harmer
37.439
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3143873LANEXA
Solar/Wind Harmer
0.137
970189AG2-124 GEN
Solar/Wind Harmer
6.721
316258AE1-075 C
Solar/Wind Harmer
0.169
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
3141913WHIT STONE
Solar/Wind Harmer
0.222
970085AG2-068 GEN
Solar/Wind Harmer
11.838
970581AG2-369 GEN
Solar/Wind Harmer
10.181
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.24
315733AD1-074 GEN2
Solar/Wind Harmer
1.24
3150411LDYSMT5
Adder
29.211
3150381LDYSMT2
Adder
27.956
972213AH1-691 GEN
Adder
4.729
972215AH1-692 GEN
Adder
4.729
3146206CASHIE
Solar/Wind Harmer
0.215
970601AG2-382 GEN
Solar/Wind Harmer
8.052
3145893MURPHYS
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
0.215
316463AE2-346 GEN
Solar/Wind Harmer
0.181
3145513AHOSKIE
Solar/Wind Harmer
0.444
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.423
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315652AC1-086 GEN
Solar/Wind Harmer
22.938
3137643SOCKMAN
Solar/Wind Harmer
0.831
316426AA2-053 GEN
Solar/Wind Harmer
0.694
316486AD2-202 GEN
Solar/Wind Harmer
0.21
3145796HORNRTN
Solar/Wind Harmer
0.657
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.204
3146033SCOT NK
Solar/Wind Harmer
0.814
316210AC1-098 GEN
Solar/Wind Harmer
1.852
3152261N ANNA2
50/50
20.065
3150861SPRUNCD
50/50
1.215
3143096IRON208
50/50
1.077
3143096IRON208
50/50
1.055
3150801HOPHCF4
50/50
1.422
3150761HOPPOLC
50/50
0.611
3151101ELIZAR3
50/50
23.654
3151161SURRY 1
50/50
9.75
3147666LOUISA
Solar/Wind Harmer
0.591
944011AF1-069 GEN
Solar/Wind Harmer
14.582
315813AE1-149 C
Solar/Wind Harmer
12.858
970133AG2-095 GEN
Solar/Wind Harmer
2.311
944581AF1-123 GEN
Solar/Wind Harmer
54.154
944601AF1-125 GEN
Solar/Wind Harmer
53.32
316458AB2-190 GEN2
Solar/Wind Harmer
1.282
315778AD1-151 GEN
Solar/Wind Harmer
19.211
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.096
961611AG1-000B GEN
Solar/Wind Harmer
6.389
970657AG2-426 GEN
Solar/Wind Harmer
5.372
3151171GRAVELC
Adder
3.348
970293AG2-193 GEN
Solar/Wind Harmer
2.545
3142946ENON
Solar/Wind Harmer
0.08
316017AA1-139 ULT1
Solar/Wind Harmer
0.127
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.746
3142416OLDCHRC
Solar/Wind Harmer
2.302
3144216WINCHST
Adder
0.895
316246AF1-032 C
Solar/Wind Harmer
0.105
3150921YORKTN3
Adder
5.96
316075AC2-137 C
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.042
3146516WINFALL
Solar/Wind Harmer
0.232
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316473AC1-191 GEN
Solar/Wind Harmer
0.777
3141843SHACKLE
Adder
1.159
316203AE2-005 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.425
3146376EDENTON
Solar/Wind Harmer
0.226
3141766HARMONY
Solar/Wind Harmer
3.02
3141873WAN 176
Solar/Wind Harmer
4.006
970917AG2-570 GEN
Solar/Wind Harmer
19.985
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.619
3150401LDYSMT4
Adder
29.12
3150371LDYSMT1
Adder
28.138
3146206CASHIE
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
3146173TUNIS
Solar/Wind Harmer
0.213
3146263WOODLND
Solar/Wind Harmer
0.21
316181AB2-040 GEN
Solar/Wind Harmer
0.298
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
316011AB1-132 GEN
Solar/Wind Harmer
3.783
3145963POPLR C
Solar/Wind Harmer
0.208
3145823KELFORD
Solar/Wind Harmer
0.207
316478AD1-087 GEN
Solar/Wind Harmer
0.714
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.821
944641AF1-129 GEN
50/50
122.63
3142366NRTHEST
50/50
0.835
3150781HOPHCF2
50/50
0.976
3150791HOPHCF3
50/50
0.976
971223AH1-071 GEN
Solar/Wind Harmer
2.831
3143526WINTERP
Solar/Wind Harmer
1.34
316294AC1-161 GEN
Solar/Wind Harmer
4.187
3150691DARBY 3
Adder
17.276
3150701DARBY 4
Adder
17.236
3150681DARBY 2
Adder
17.216
3150671DARBY 1
Adder
17.196
3150991CHESPKB
Adder
2.514
3150991CHESPKB
Adder
2.453
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3142296MT RD221
Adder
0.762
3145506HICKORY
Solar/Wind Harmer
0.956
3145506HICKORY
Solar/Wind Harmer
0.573
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.072
316212AC1-099_GEN
Solar/Wind Harmer
1.033
3145933PARMELE
Solar/Wind Harmer
0.199
3145506HICKORY
Solar/Wind Harmer
0.143
3142946ENON
Solar/Wind Harmer
0.024
316339AD2-160 GEN
Solar/Wind Harmer
0.381
316388AE2-253 GEN
Solar/Wind Harmer
0.741
3137176SLIGO L2192
Solar/Wind Harmer
0.945
3146456SLIGO L269
Solar/Wind Harmer
4.203
316312AB1-027
Solar/Wind Harmer
0.422
316349AD2-085 GEN
Solar/Wind Harmer
0.158
3130086AYDLETT
Solar/Wind Harmer
0.949
315835AF2-110_GEN
Solar/Wind Harmer
1.619
972185AH1-677 GEN
Adder
13.245
3144356SAPONY
Solar/Wind Harmer
1.97
316315AB2-025 C
Solar/Wind Harmer
0.188
315976AC1-164 GENA
Solar/Wind Harmer
2.477
316169AC1-164_GENC
Solar/Wind Harmer
2.14
3146386ELIZ CT
Solar/Wind Harmer
0.235
972189AH1-679 GEN
Adder
3.909
972187AH1-678 GEN
Adder
6.642
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
18.348
315742AE1-103 GEN
Solar/Wind Harmer
3.403
316313AB2-026
Solar/Wind Harmer
0.141
3146376EDENTON
Solar/Wind Harmer
1.007
3152251N ANNA1
50/50
20.055
970119AG2-088 GEN
50/50
35.386
3150851SPRUNCC
50/50
1.215
3143096IRON208
50/50
1.077
3152331SURRY 2
50/50
9.863
3150771HOPHCF1
50/50
0.976
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.34
3147666LOUISA
Solar/Wind Harmer
1.027
316192AB2-158 GEN
Solar/Wind Harmer
1.403
940641AE2-051 GEN
Solar/Wind Harmer
19.942
939411AE1-173 GEN
Solar/Wind Harmer
105.31
3142543TWELFTH
Solar/Wind Harmer
0.023
315773AC2-141 GEN
Solar/Wind Harmer
8.846
941031AE2-094 GEN
Solar/Wind Harmer
44.63
315671AE2-027_GEN
Solar/Wind Harmer
0.002
944591AF1-124 GEN
Solar/Wind Harmer
54.347
316132AB2-190 GEN1
Solar/Wind Harmer
1.282
971069AG2-661 GEN
Solar/Wind Harmer
4.269
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.043
3150981CHESPKA
Adder
2.996
3145336SMITFLD
Solar/Wind Harmer
0.958
316381AD1-082 GEN
Solar/Wind Harmer
0.243
944631AF1-128 GEN
Adder
114.228
961611AG1-000B GEN
Solar/Wind Harmer
12.565
3151171GRAVELC
Adder
2.546
3146456SLIGO L269
Solar/Wind Harmer
0.237
3142416OLDCHRC
Solar/Wind Harmer
0.617
3142416OLDCHRC
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.084
319010AE1-072 C
Solar/Wind Harmer
1.184
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316093AE2-104_GEN
Solar/Wind Harmer
3.969
971317AH1-138 GEN
Solar/Wind Harmer
1.76
315975AC1-164 GENB
Solar/Wind Harmer
0.073
3146516WINFALL
Solar/Wind Harmer
0.753
3146516WINFALL
Solar/Wind Harmer
0.232
3142433PROV 92
Solar/Wind Harmer
0.927
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
971777AH1-397 GEN
Solar/Wind Harmer
0.599
3143336POWHATN
Solar/Wind Harmer
4.029
3130156CHOWAN
Solar/Wind Harmer
0.226
3141766HARMONY
Solar/Wind Harmer
0.045
970919AG2-571 GEN
Solar/Wind Harmer
7.994
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
17.757
315816AE2-034 GEN
Solar/Wind Harmer
0.947
3145663CRESWEL
Solar/Wind Harmer
0.621
971163AH1-040 GEN
Solar/Wind Harmer
17.754
3138133OCRAN
Solar/Wind Harmer
0.133
316023GEN1_S
Solar/Wind Harmer
0.484
315737AD1-076 GEN
Solar/Wind Harmer
2.793
972197AH1-683 GEN
Adder
4.547
972219AH1-694 GEN
Adder
3.274
3146206CASHIE
Solar/Wind Harmer
0.215
971547AH1-271 GEN
Solar/Wind Harmer
4.601
3145893MURPHYS
Solar/Wind Harmer
0.861
3145893MURPHYS
Solar/Wind Harmer
0.957
957481AF2-042 GEN
Solar/Wind Harmer
57.175
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.958
960081AF2-299 GEN
Solar/Wind Harmer
2.039
962861AG1-135 GEN
Solar/Wind Harmer
6.765
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.424
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.961
3146263WOODLND
Solar/Wind Harmer
0.21
315693AD1-088 GEN
Solar/Wind Harmer
10.078
3145963POPLR C
Solar/Wind Harmer
0.208
3145823KELFORD
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.829
3147043LAWRENC
Adder
1.865
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.038
3146376EDENTON
Solar/Wind Harmer
1.007
316156AD2-030 GEN
Solar/Wind Harmer
0.165
315614AA2-178 GEN
Solar/Wind Harmer
1.262
315673AE1-157 GEN
Solar/Wind Harmer
15.346
316365GEN2_N
Solar/Wind Harmer
0.484
3150391LDYSMT3
Adder
29.065
972195AH1-682 GEN
Adder
3.82
316336AC2-165 C
Solar/Wind Harmer
10.968
316065AD1-022 GEN
Solar/Wind Harmer
9.965
3145893MURPHYS
Solar/Wind Harmer
1.44
3145893MURPHYS
Solar/Wind Harmer
0.387
970099AG2-077 GEN
Solar/Wind Harmer
22.87
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
316140AB2-099
Solar/Wind Harmer
0.075
313506AB2-031 GEN
Solar/Wind Harmer
0.643
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
962571AG1-106 GEN
Solar/Wind Harmer
2.967
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.257
3145783HORNRTN
Solar/Wind Harmer
3.656
3145783HORNRTN
Solar/Wind Harmer
2.925
3145783HORNRTN
Solar/Wind Harmer
0.914
3145783HORNRTN
Solar/Wind Harmer
0.366
3145796HORNRTN
Solar/Wind Harmer
0.616
3150341NORNECKC1
Adder
2.14
3150341NORNECKC1
Adder
2.123
3145933PARMELE
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.199
971781AH1-399 GEN
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
6.743
964241AG1-285 GEN
Solar/Wind Harmer
12.775
970257AG2-171 GEN
Solar/Wind Harmer
6.108
971775AH1-396 GEN
Solar/Wind Harmer
0.305
959311AF2-222 GEN
Solar/Wind Harmer
16.954
3146233WITAKRS
Solar/Wind Harmer
0.954
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.19
3146083TARBORO
Solar/Wind Harmer
0.19
3144293JTRSVLE
Adder
0.453
3138543CONSLDL
Solar/Wind Harmer
0.125
3147133PAMPLIN
Solar/Wind Harmer
0.595
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
13.28
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.187
971623AH1-311 GEN
Solar/Wind Harmer
0.373
316223AC1-118
Solar/Wind Harmer
0.131
3141906WESTMOR
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.064
972003AH1-546 GEN
Solar/Wind Harmer
5.879
971683AH1-343 GEN
Solar/Wind Harmer
5.882
316222AC1-221 GEN
Solar/Wind Harmer
0.654
316283AC2-100 C
Solar/Wind Harmer
0.309
970221AG2-151 GEN
Solar/Wind Harmer
8.401
972255AH1-712 GEN
Adder
74.821
316123AC1-075 GEN
Solar/Wind Harmer
0.189
270494AE1-108_GEN
Solar/Wind Harmer
1.66
315821AE2-092 GEN
Solar/Wind Harmer
0
3151761LOISA E
Adder
17.635
3151721LOISA A
Adder
8.605
3141196NOKESVL
Solar/Wind Helper
1.133
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.74
971065AG2-659 GEN
Solar/Wind Harmer
8.423
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
316337AD2-073 GEN
Solar/Wind Harmer
0.168
316494AC1-189 GEN
Solar/Wind Harmer
0.65
316131AB2-060 GEN
Solar/Wind Harmer
0.597
315785AD2-033 C
Solar/Wind Harmer
1.545
316034AC1-036 C
Solar/Wind Harmer
0.013
970937AG2-583 GEN
Solar/Wind Harmer
11.679
970685AG2-442 GEN
Solar/Wind Harmer
14.197
3146233WITAKRS
Solar/Wind Harmer
0.756
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.19
3145493TOT1
Solar/Wind Harmer
0.844
971563AH1-280 GEN
Solar/Wind Harmer
2.025
3144293JTRSVLE
Adder
0.453
3144293JTRSVLE
Adder
0.358
3146926FARMVIL
Solar/Wind Harmer
0.113
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.663
3142053HEARTS
Solar/Wind Harmer
0.329
970401AG2-262 GEN
Solar/Wind Harmer
1.069
3146776BUCKING
Solar/Wind Harmer
0.072
972135AH1-637 GEN
Solar/Wind Harmer
1.429
971377AH1-170 GEN
Solar/Wind Harmer
1.68
3147623JAMES R
Solar/Wind Harmer
0.365
972277AH1-723 GEN
Adder
87.189
3151751LOISA D
Adder
8.65
316447AC1-158 HLD
Solar/Wind Helper
11.517
316044AC1-158 PL1
Solar/Wind Helper
5.234
316415AF1-147_GEN2
Solar/Wind Helper
0.794
970831AG2-522 GEN
Solar/Wind Harmer
8.499
316274AC1-208 GEN
Solar/Wind Harmer
1.026
3145746EVERETS
Solar/Wind Harmer
0.778
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
316327AA2-057 GEN
Solar/Wind Harmer
0.286
957861AF2-080 GEN
Solar/Wind Harmer
8.299
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
11.473
970681AG2-440 GEN
Solar/Wind Harmer
7.615
3145573BETHELC
Solar/Wind Harmer
0.19
3145573BETHELC
Solar/Wind Harmer
0.19
946301AF1-294 GEN
Solar/Wind Harmer
3.747
961791AG1-021 GEN
Solar/Wind Harmer
1.823
971845AH1-439 GEN
Solar/Wind Harmer
8.142
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.192
944491AF1-114 GEN
Solar/Wind Harmer
0
3147346CASHSCORNER
Solar/Wind Harmer
0.293
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.386
3138216PACIFIC
Solar/Wind Helper
0.038
970301AG2-198 GEN
Solar/Wind Harmer
8.407
316005AA1-067
Solar/Wind Harmer
0.209
315724AD1-057 GEN
Solar/Wind Harmer
3.762
970323AG2-213 GEN
Solar/Wind Harmer
8.144
3145493TOT1
Solar/Wind Harmer
0.44
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.278
3144293JTRSVLE
Adder
0.453
3147133PAMPLIN
Solar/Wind Harmer
0.189
3147133PAMPLIN
Solar/Wind Harmer
0.151
961601AG1-000A GEN
Solar/Wind Harmer
3.32
316049AB1-081 GEN
Solar/Wind Harmer
1.062
316263AC1-034 GEN
Solar/Wind Harmer
7.094
962561AG1-105 GEN
Solar/Wind Harmer
8.822
964791AG1-342 GEN
Solar/Wind Harmer
3.5
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
3146776BUCKING
Solar/Wind Harmer
0.715
3146776BUCKING
Solar/Wind Harmer
0.058
316118AC1-105 GEN
Solar/Wind Harmer
0.458
972193AH1-681 GEN
Adder
3.343
942751AE2-291 GEN
Solar/Wind Harmer
7.275
3151731LOISA B
Adder
8.65
316045AC1-158 PL2
Solar/Wind Helper
16.749
316450AC1-158 RIC
Solar/Wind Helper
1.396
316006AB2-029 C
Solar/Wind Helper
0.141
316411AF1-147_GEN1
Solar/Wind Helper
0.794
LAGNLTFEXP_LAGN->PJM
CLTF
8.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.444
TVALTFEXP_TVA->PJM
CLTF
4.232
CPLELTFEXP_CPLE->PJM
CLTF
12.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.908
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.749
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.367
MECLTFEXP_MEC->PJM
CLTF
3.719
SIGELTFEXP_SIGE->PJM
CLTF
0.113
NYPJM->LTFIMP_NY
CLTF
3.279
LGEELTFEXP_LGEE->PJM
CLTF
1.357
WECLTFEXP_WEC->PJM
CLTF
0.655

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:154.04 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4960.85
MW Contribution:
5.93
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.176
3150861SPRUNCD
50/50
1.237
3143096IRON208
50/50
1.098
3143096IRON208
50/50
1.076
316303AF2-085
50/50
4.786
971285AH1-108 GEN
50/50
2.024
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971281AH1-106 GEN
Solar/Wind Harmer
3.634
971283AH1-107 GEN
Solar/Wind Harmer
3.634
3143316POE
Solar/Wind Harmer
0.979
970533AG2-339 GEN
Solar/Wind Harmer
18.574
315697AD1-025 GEN
Solar/Wind Harmer
0.263
3151081ELIZAR1
Adder
22.39
3151091ELIZAR2
Adder
22.001
971445AH1-216 GEN
Solar/Wind Harmer
17.171
316316AC1-027 C
Solar/Wind Harmer
0.232
3151201GRAVEL4
Adder
17.737
3151221GRAVEL6
Adder
17.716
3151191GRAVEL3
Adder
17.512
3151211GRAVEL5
Adder
17.512
970657AG2-426 GEN
Solar/Wind Harmer
1.788
970673AG2-436 GEN
Solar/Wind Harmer
30.277
957871AF2-081 GEN
Solar/Wind Harmer
12.052
316311AC2-079 GEN
Solar/Wind Harmer
6.933
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316159AE1-175 C
Solar/Wind Harmer
0.206
313526AB2-022
Solar/Wind Harmer
0.128
3146486SUNBURY
Solar/Wind Harmer
0.238
3146486SUNBURY
Solar/Wind Harmer
0.238
315814AE2-033 C
Solar/Wind Harmer
18.861
3146396TANGLEW
Solar/Wind Harmer
0.657
3145176PASQUOTANK
Solar/Wind Harmer
0.148
971967AH1-528 GEN
Solar/Wind Harmer
37.977
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3138283WHITEMARSH
Solar/Wind Harmer
0.055
3143873LANEXA
Solar/Wind Harmer
0.14
970189AG2-124 GEN
Solar/Wind Harmer
6.858
3130156CHOWAN
Solar/Wind Harmer
0.23
3130156CHOWAN
Solar/Wind Harmer
0.23
3141873WAN 176
Solar/Wind Harmer
0.046
316258AE1-075 C
Solar/Wind Harmer
0.171
3141913WHIT STONE
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
970085AG2-068 GEN
Solar/Wind Harmer
12.01
970581AG2-369 GEN
Solar/Wind Harmer
10.328
3141783LANCAST
Solar/Wind Harmer
0.134
3141783LANCAST
Solar/Wind Harmer
0.09
3150411LDYSMT5
Adder
30.115
3150381LDYSMT2
Adder
28.821
972213AH1-691 GEN
Adder
4.875
972215AH1-692 GEN
Adder
4.875
3130546PLYMOUTH
Solar/Wind Harmer
0.222
315732AD1-074 GEN1
Solar/Wind Harmer
1.261
315733AD1-074 GEN2
Solar/Wind Harmer
1.261
3146206CASHIE
Solar/Wind Harmer
0.219
970601AG2-382 GEN
Solar/Wind Harmer
8.185
3145893MURPHYS
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
0.219
316463AE2-346 GEN
Solar/Wind Harmer
0.184
3145513AHOSKIE
Solar/Wind Harmer
0.451
3145513AHOSKIE
Solar/Wind Harmer
0.216
3146043SEABORD
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.429
3145683EARLEYS
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.215
315652AC1-086 GEN
Solar/Wind Harmer
23.301
3137643SOCKMAN
Solar/Wind Harmer
0.844
316426AA2-053 GEN
Solar/Wind Harmer
0.705
316486AD2-202 GEN
Solar/Wind Harmer
0.213
3141813NORNECK
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.667
3145796HORNRTN
Solar/Wind Harmer
0.083
3146033SCOT NK
Solar/Wind Harmer
0.827
316210AC1-098 GEN
Solar/Wind Harmer
1.881
316274AC1-208 GEN
Solar/Wind Harmer
1.042
970831AG2-522 GEN
Solar/Wind Harmer
8.626
3145746EVERETS
Solar/Wind Harmer
0.79
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316327AA2-057 GEN
Solar/Wind Harmer
0.29
957861AF2-080 GEN
Solar/Wind Harmer
8.43
3144303KENBRDG
Solar/Wind Harmer
0.155
3145573BETHELC
Solar/Wind Harmer
0.193
3145573BETHELC
Solar/Wind Harmer
0.193
970683AG2-441 GEN
Solar/Wind Harmer
11.621
970681AG2-440 GEN
Solar/Wind Harmer
7.713
946301AF1-294 GEN
Solar/Wind Harmer
3.794
961791AG1-021 GEN
Solar/Wind Harmer
1.846
3150801HOPHCF4
50/50
1.448
3150761HOPPOLC
50/50
0.622
3151161SURRY 1
50/50
9.926
3147666LOUISA
Solar/Wind Harmer
0.584
944011AF1-069 GEN
Solar/Wind Harmer
14.794
315813AE1-149 C
Solar/Wind Harmer
13.082
970133AG2-095 GEN
Solar/Wind Harmer
2.355
316458AB2-190 GEN2
Solar/Wind Harmer
1.306
944581AF1-123 GEN
Solar/Wind Harmer
55.085
944601AF1-125 GEN
Solar/Wind Harmer
54.236
315778AD1-151 GEN
Solar/Wind Harmer
19.565
3151101ELIZAR3
Adder
22.676
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
6.505
3145336SMITFLD
Solar/Wind Harmer
0.098
3151171GRAVELC
Adder
3.409
970657AG2-426 GEN
Solar/Wind Harmer
5.465
970293AG2-193 GEN
Solar/Wind Harmer
2.597
3142946ENON
Solar/Wind Harmer
0.081
3142416OLDCHRC
Solar/Wind Harmer
2.351
316017AA1-139 ULT1
Solar/Wind Harmer
0.129
3144216WINCHST
Adder
0.912
316075AC2-137 C
Solar/Wind Harmer
0.064
3146456SLIGO L269
Solar/Wind Harmer
0.241
971153AH1-033 GEN
Solar/Wind Harmer
2.793
3150921YORKTN3
Adder
6.071
316246AF1-032 C
Solar/Wind Harmer
0.107
316321Z2-027
Solar/Wind Harmer
0.042
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.236
316473AC1-191 GEN
Solar/Wind Harmer
0.795
3146626S HERTFORD
Solar/Wind Harmer
0.235
3145273HOLLAND
Solar/Wind Harmer
0.176
3141843SHACKLE
Adder
1.183
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
3.082
3146376EDENTON
Solar/Wind Harmer
0.23
3141873WAN 176
Solar/Wind Harmer
4.087
3143336POWHATN
Solar/Wind Harmer
3.467
970917AG2-570 GEN
Solar/Wind Harmer
20.275
3150401LDYSMT4
Adder
30.021
3150371LDYSMT1
Adder
29.008
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.629
3146206CASHIE
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
0.366
3145893MURPHYS
Solar/Wind Harmer
0.219
3146173TUNIS
Solar/Wind Harmer
0.217
3146263WOODLND
Solar/Wind Harmer
0.213
316181AB2-040 GEN
Solar/Wind Harmer
0.303
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
316011AB1-132 GEN
Solar/Wind Harmer
3.842
3145963POPLR C
Solar/Wind Harmer
0.211
3145823KELFORD
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Harmer
0.724
3150351NORNECKC2
Adder
2.117
3145796HORNRTN
Solar/Wind Harmer
0.834
3145796HORNRTN
Solar/Wind Harmer
0.208
316212AC1-099_GEN
Solar/Wind Harmer
1.049
3145933PARMELE
Solar/Wind Harmer
0.202
971781AH1-399 GEN
Solar/Wind Harmer
0.266
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
315722AD1-056 GEN
Solar/Wind Harmer
6.849
964241AG1-285 GEN
Solar/Wind Harmer
12.949
970257AG2-171 GEN
Solar/Wind Harmer
6.188
971775AH1-396 GEN
Solar/Wind Harmer
0.309
959311AF2-222 GEN
Solar/Wind Harmer
17.176
3146233WITAKRS
Solar/Wind Harmer
0.969
3146233WITAKRS
Solar/Wind Harmer
0.131
3146073TAR RVR
Solar/Wind Harmer
0.193
3146083TARBORO
Solar/Wind Harmer
0.193
3138543CONSLDL
Solar/Wind Harmer
0.127
3144293JTRSVLE
Adder
0.459
3147133PAMPLIN
Solar/Wind Harmer
0.602
942461AE2-259 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
13.487
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.189
971623AH1-311 GEN
Solar/Wind Harmer
0.379
316223AC1-118
Solar/Wind Harmer
0.134
3141906WESTMOR
Solar/Wind Harmer
0.075
3146776BUCKING
Solar/Wind Harmer
0.065
972003AH1-546 GEN
Solar/Wind Harmer
5.927
971683AH1-343 GEN
Solar/Wind Harmer
5.965
316222AC1-221 GEN
Solar/Wind Harmer
0.664
316283AC2-100 C
Solar/Wind Harmer
0.314
970221AG2-151 GEN
Solar/Wind Harmer
8.466
972255AH1-712 GEN
Adder
76.496
316123AC1-075 GEN
Solar/Wind Harmer
0.192
270494AE1-108_GEN
Solar/Wind Harmer
1.675
315821AE2-092 GEN
Solar/Wind Harmer
0
3151761LOISA E
Adder
16.773
3151721LOISA A
Adder
8.185
3150331BIRCHWDA
Adder
19.202
3141196NOKESVL
Solar/Wind Helper
1.154
971845AH1-439 GEN
Solar/Wind Harmer
8.222
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
972205AH1-687 GEN
Adder
7.248
944491AF1-114 GEN
Solar/Wind Harmer
0
3147346CASHSCORNER
Solar/Wind Harmer
0.278
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
2.205
315651AD1-115 GEN
Solar/Wind Helper
1.033
3138216PACIFIC
Solar/Wind Helper
0.039
944641AF1-129 GEN
50/50
124.896
3142366NRTHEST
50/50
0.852
3150781HOPHCF2
50/50
0.994
3150791HOPHCF3
50/50
0.994
3150691DARBY 3
50/50
18.706
3150701DARBY 4
50/50
18.663
971223AH1-071 GEN
Solar/Wind Harmer
2.872
3143526WINTERP
Solar/Wind Harmer
1.362
316294AC1-161 GEN
Solar/Wind Harmer
4.26
3150681DARBY 2
Adder
17.567
3150671DARBY 1
Adder
17.547
3142296MT RD221
Adder
0.778
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3150991CHESPKB
Adder
2.557
3150991CHESPKB
Adder
2.496
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.972
3145506HICKORY
Solar/Wind Harmer
0.583
3145506HICKORY
Solar/Wind Harmer
0.146
316312AB1-027
Solar/Wind Harmer
0.431
316339AD2-160 GEN
Solar/Wind Harmer
0.388
316388AE2-253 GEN
Solar/Wind Harmer
0.754
3137176SLIGO L2192
Solar/Wind Harmer
0.962
3146456SLIGO L269
Solar/Wind Harmer
4.275
316349AD2-085 GEN
Solar/Wind Harmer
0.161
3130086AYDLETT
Solar/Wind Harmer
0.965
315976AC1-164 GENA
Solar/Wind Harmer
2.528
316169AC1-164_GENC
Solar/Wind Harmer
2.185
315835AF2-110_GEN
Solar/Wind Harmer
1.647
972185AH1-677 GEN
Adder
13.436
3144356SAPONY
Solar/Wind Harmer
2.002
316315AB2-025 C
Solar/Wind Harmer
0.191
3146386ELIZ CT
Solar/Wind Harmer
0.239
972189AH1-679 GEN
Adder
4.004
972187AH1-678 GEN
Adder
6.738
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
966871AG1-558 GEN
Solar/Wind Harmer
0.272
3146626S HERTFORD
Solar/Wind Harmer
0.235
3146626S HERTFORD
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
18.61
315742AE1-103 GEN
Solar/Wind Harmer
3.46
3146376EDENTON
Solar/Wind Harmer
1.024
3146376EDENTON
Solar/Wind Harmer
1.024
316156AD2-030 GEN
Solar/Wind Harmer
0.168
316313AB2-026
Solar/Wind Harmer
0.143
315673AE1-157 GEN
Solar/Wind Harmer
15.789
315614AA2-178 GEN
Solar/Wind Harmer
1.284
3150391LDYSMT3
Adder
29.965
972195AH1-682 GEN
Adder
3.938
316365GEN2_N
Solar/Wind Harmer
0.492
316065AD1-022 GEN
Solar/Wind Harmer
10.129
316336AC2-165 C
Solar/Wind Harmer
11.098
3145893MURPHYS
Solar/Wind Harmer
1.464
3145893MURPHYS
Solar/Wind Harmer
0.393
970099AG2-077 GEN
Solar/Wind Harmer
23.191
3146173TUNIS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.217
316140AB2-099
Solar/Wind Harmer
0.077
313506AB2-031 GEN
Solar/Wind Harmer
0.653
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.127
962571AG1-106 GEN
Solar/Wind Harmer
3.014
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.261
3145783HORNRTN
Solar/Wind Harmer
3.713
3145783HORNRTN
Solar/Wind Harmer
2.97
3145783HORNRTN
Solar/Wind Harmer
0.928
3145783HORNRTN
Solar/Wind Harmer
0.371
3150341NORNECKC1
Adder
2.187
3150341NORNECKC1
Adder
2.169
3145796HORNRTN
Solar/Wind Harmer
0.626
3145933PARMELE
Solar/Wind Harmer
0.405
3145933PARMELE
Solar/Wind Harmer
0.202
970301AG2-198 GEN
Solar/Wind Harmer
8.511
316005AA1-067
Solar/Wind Harmer
0.212
315724AD1-057 GEN
Solar/Wind Harmer
3.821
970323AG2-213 GEN
Solar/Wind Harmer
8.251
3145493TOT1
Solar/Wind Harmer
0.447
3145453TOT5
Solar/Wind Harmer
0.268
3145603CNETO
Solar/Wind Harmer
0.179
958211AF2-115 GEN
Solar/Wind Harmer
2.307
3144293JTRSVLE
Adder
0.459
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.153
961601AG1-000A GEN
Solar/Wind Harmer
3.372
316049AB1-081 GEN
Solar/Wind Harmer
1.078
316263AC1-034 GEN
Solar/Wind Harmer
7.204
962561AG1-105 GEN
Solar/Wind Harmer
8.945
964791AG1-342 GEN
Solar/Wind Harmer
3.549
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
316118AC1-105 GEN
Solar/Wind Harmer
0.464
3146776BUCKING
Solar/Wind Harmer
0.722
3146776BUCKING
Solar/Wind Harmer
0.058
972193AH1-681 GEN
Adder
3.418
942751AE2-291 GEN
Solar/Wind Harmer
7.377
3151731LOISA B
Adder
8.227
316045AC1-158 PL2
Solar/Wind Helper
16.87
316450AC1-158 RIC
Solar/Wind Helper
1.406
316006AB2-029 C
Solar/Wind Helper
0.153
316411AF1-147_GEN1
Solar/Wind Helper
0.806
3152251N ANNA1
50/50
20.166
970119AG2-088 GEN
50/50
35.895
3150851SPRUNCC
50/50
1.237
3143096IRON208
50/50
1.098
3152331SURRY 2
50/50
10.043
3150771HOPHCF1
50/50
0.994
3143226MDLTHAN
Solar/Wind Harmer
0.269
3143526WINTERP
Solar/Wind Harmer
1.362
3147666LOUISA
Solar/Wind Harmer
1.015
940641AE2-051 GEN
Solar/Wind Harmer
20.241
939411AE1-173 GEN
Solar/Wind Harmer
106.947
3142543TWELFTH
Solar/Wind Harmer
0.024
315773AC2-141 GEN
Solar/Wind Harmer
9
316192AB2-158 GEN
Solar/Wind Harmer
1.386
315671AE2-027_GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
45.277
316132AB2-190 GEN1
Solar/Wind Harmer
1.306
944591AF1-124 GEN
Solar/Wind Harmer
55.281
971069AG2-661 GEN
Solar/Wind Harmer
4.348
944631AF1-128 GEN
Adder
116.464
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.043
3150981CHESPKA
Adder
3.048
961611AG1-000B GEN
Solar/Wind Harmer
12.793
3145336SMITFLD
Solar/Wind Harmer
0.975
316381AD1-082 GEN
Solar/Wind Harmer
0.247
3151171GRAVELC
Adder
2.592
3142416OLDCHRC
Solar/Wind Harmer
0.631
3142416OLDCHRC
Solar/Wind Harmer
0.242
3138126ROCKLANDING
Solar/Wind Harmer
0.111
3146456SLIGO L269
Solar/Wind Harmer
0.241
316072AD1-144
Solar/Wind Harmer
0.086
319010AE1-072 C
Solar/Wind Harmer
1.204
315975AC1-164 GENB
Solar/Wind Harmer
0.075
971317AH1-138 GEN
Solar/Wind Harmer
1.794
316093AE2-104_GEN
Solar/Wind Harmer
4.037
3142433PROV 92
Solar/Wind Harmer
0.946
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.765
3146516WINFALL
Solar/Wind Harmer
0.236
971777AH1-397 GEN
Solar/Wind Harmer
0.611
3141766HARMONY
Solar/Wind Harmer
0.046
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3130156CHOWAN
Solar/Wind Harmer
0.23
3143336POWHATN
Solar/Wind Harmer
4.079
970919AG2-571 GEN
Solar/Wind Harmer
8.11
3138133OCRAN
Solar/Wind Harmer
0.136
315816AE2-034 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.631
971163AH1-040 GEN
Solar/Wind Harmer
18.05
970087AG2-069 GEN
Solar/Wind Harmer
18.014
972197AH1-683 GEN
Adder
4.688
972219AH1-694 GEN
Adder
3.375
315737AD1-076 GEN
Solar/Wind Harmer
2.839
316023GEN1_S
Solar/Wind Harmer
0.492
3146206CASHIE
Solar/Wind Harmer
0.219
971547AH1-271 GEN
Solar/Wind Harmer
4.677
3145893MURPHYS
Solar/Wind Harmer
0.875
3145893MURPHYS
Solar/Wind Harmer
0.973
957481AF2-042 GEN
Solar/Wind Harmer
57.978
3146173TUNIS
Solar/Wind Harmer
0.217
3156021HOLLOMANSOL
Solar/Wind Harmer
0.973
962861AG1-135 GEN
Solar/Wind Harmer
6.908
960081AF2-299 GEN
Solar/Wind Harmer
2.07
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.108
3145683EARLEYS
Solar/Wind Harmer
0.215
315607AA1-063A GEN
Solar/Wind Harmer
0.431
3146263WOODLND
Solar/Wind Harmer
0.213
315693AD1-088 GEN
Solar/Wind Harmer
10.217
3141726DUNNSVL
Solar/Wind Harmer
0.846
3145963POPLR C
Solar/Wind Harmer
0.211
3145823KELFORD
Solar/Wind Harmer
0.211
3147043LAWRENC
Adder
1.893
3145783HORNRTN
Solar/Wind Harmer
0.209
3150351NORNECKC2
Adder
2.082
3145796HORNRTN
Solar/Wind Harmer
0.688
3145796HORNRTN
Solar/Wind Harmer
0.208
3146293MARTNCO
Solar/Wind Harmer
0.188
316129AC1-054 GEN
Solar/Wind Harmer
0.751
971065AG2-659 GEN
Solar/Wind Harmer
8.547
316337AD2-073 GEN
Solar/Wind Harmer
0.171
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316494AC1-189 GEN
Solar/Wind Harmer
0.66
316131AB2-060 GEN
Solar/Wind Harmer
0.605
315785AD2-033 C
Solar/Wind Harmer
1.566
316034AC1-036 C
Solar/Wind Harmer
0.013
3146233WITAKRS
Solar/Wind Harmer
0.768
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.193
3145493TOT1
Solar/Wind Harmer
0.857
970685AG2-442 GEN
Solar/Wind Harmer
14.378
970937AG2-583 GEN
Solar/Wind Harmer
11.795
971563AH1-280 GEN
Solar/Wind Harmer
2.051
3144293JTRSVLE
Adder
0.459
3144293JTRSVLE
Adder
0.362
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.152
316359AB2-059 GEN
Solar/Wind Harmer
0.674
3142053HEARTS
Solar/Wind Harmer
0.334
970401AG2-262 GEN
Solar/Wind Harmer
1.085
3146776BUCKING
Solar/Wind Harmer
0.072
972135AH1-637 GEN
Solar/Wind Harmer
1.463
971377AH1-170 GEN
Solar/Wind Harmer
1.693
3147623JAMES R
Solar/Wind Harmer
0.368
972277AH1-723 GEN
Adder
89.141
3151751LOISA D
Adder
8.227
970223AG2-152 GEN
Solar/Wind Harmer
7.994
316447AC1-158 HLD
Solar/Wind Helper
11.601
316044AC1-158 PL1
Solar/Wind Helper
5.272
316415AF1-147_GEN2
Solar/Wind Helper
0.806
LAGNLTFEXP_LAGN->PJM
CLTF
8.482
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.834
TVALTFEXP_TVA->PJM
CLTF
4.295
CPLELTFEXP_CPLE->PJM
CLTF
12.293
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.07
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.579
MECLTFEXP_MEC->PJM
CLTF
3.774
SIGELTFEXP_SIGE->PJM
CLTF
0.115
NYPJM->LTFIMP_NY
CLTF
3.323
LGEELTFEXP_LGEE->PJM
CLTF
1.377
WECLTFEXP_WEC->PJM
CLTF
0.665

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.64 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4319.87
MW Contribution:
7.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.762
971285AH1-108 GEN
50/50
1.512
315244AE2-183_ST
50/50
5.372
963041AG1-153 GEN
50/50
4.95
3147346CASHSCORNER
Solar/Wind Harmer
0.409
316233AE1-074 FULL
Solar/Wind Harmer
0.608
971281AH1-106 GEN
Solar/Wind Harmer
3.673
971283AH1-107 GEN
Solar/Wind Harmer
3.673
970533AG2-339 GEN
Solar/Wind Harmer
14.554
970673AG2-436 GEN
Solar/Wind Harmer
46.871
316258AE1-075 C
Solar/Wind Harmer
0.514
316405AF2-144 C
Solar/Wind Harmer
0.542
3143316POE
Solar/Wind Harmer
-0.083
971967AH1-528 GEN
Solar/Wind Harmer
39.41
315839AE2-212 C
Solar/Wind Harmer
0.625
3151081ELIZAR1
Adder
16.872
3151091ELIZAR2
Adder
16.579
316316AC1-027 C
Solar/Wind Harmer
0.633
970657AG2-426 GEN
Solar/Wind Harmer
1.299
315814AE2-033 C
Solar/Wind Harmer
19.184
316018AA1-139 ULT2
Solar/Wind Harmer
1.755
957871AF2-081 GEN
Solar/Wind Harmer
10.267
316236AE1-162_GEN
Solar/Wind Harmer
0.617
971445AH1-216 GEN
Solar/Wind Harmer
12.688
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.887
3152261N ANNA2
50/50
17.537
3151771S ANNAG1
50/50
0.882
3151801S ANNAS2
50/50
0.453
3151761LOISA E
50/50
34.815
3151721LOISA A
50/50
16.989
3150861SPRUNCD
50/50
0.924
3151031BRUNSWICKG2
50/50
2.445
3147666LOUISA
Solar/Wind Harmer
-0.078
944011AF1-069 GEN
Solar/Wind Harmer
12.715
3143336POWHATN
Solar/Wind Harmer
2.14
944581AF1-123 GEN
Solar/Wind Harmer
94.347
944601AF1-125 GEN
Solar/Wind Harmer
92.874
315813AE1-149 C
Solar/Wind Harmer
12.955
316311AC2-079 GEN
Solar/Wind Harmer
10.325
3151201GRAVEL4
Adder
13.223
3151221GRAVEL6
Adder
13.208
3151191GRAVEL3
Adder
13.056
3151211GRAVEL5
Adder
13.056
315697AD1-025 GEN
Solar/Wind Harmer
4.113
313526AB2-022
Solar/Wind Harmer
0.547
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146396TANGLEW
Solar/Wind Harmer
0.372
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.411
970581AG2-369 GEN
Solar/Wind Harmer
10.673
316382AG1-145 C
Solar/Wind Harmer
0.596
316159AE1-175 C
Solar/Wind Harmer
0.53
315800Z1-036_GEN1
Solar/Wind Harmer
4.874
3130156CHOWAN
Solar/Wind Harmer
-0.02
3130156CHOWAN
Solar/Wind Harmer
-0.02
957831AF2-077 GEN
Solar/Wind Harmer
0.583
3138283WHITEMARSH
Solar/Wind Harmer
0.03
3142433PROV 92
Adder
0.333
3142433PROV 92
Adder
0.333
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
315732AD1-074 GEN1
Solar/Wind Harmer
3.828
315733AD1-074 GEN2
Solar/Wind Harmer
3.828
3143873LANEXA
Solar/Wind Harmer
-0.011
316318V4-068
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
-0.051
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
970601AG2-382 GEN
Solar/Wind Harmer
8.234
3151101ELIZAR3
Adder
17.088
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142956BIRDNECK
Solar/Wind Harmer
1.108
3144536CHRHLND
Solar/Wind Harmer
-0.003
970657AG2-426 GEN
Solar/Wind Harmer
4.164
316017AA1-139 ULT1
Solar/Wind Harmer
1.657
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.372
316305AF2-043 C
Solar/Wind Harmer
0.615
316246AF1-032 C
Solar/Wind Harmer
0.413
3151171GRAVELC
Adder
2.541
961611AG1-000B GEN
Solar/Wind Harmer
4.296
315778AD1-151 GEN
Solar/Wind Harmer
18.134
316458AB2-190 GEN2
Solar/Wind Harmer
2.054
970133AG2-095 GEN
Solar/Wind Harmer
2.289
316320Y1-086
Solar/Wind Harmer
1.19
3143096IRON208
Adder
0.757
3143096IRON208
Adder
0.741
316321Z2-027
Solar/Wind Harmer
0.545
970917AG2-570 GEN
Solar/Wind Harmer
50.28
3146516WINFALL
Solar/Wind Harmer
-0.02
3144216WINCHST
Adder
0.674
3150921YORKTN3
Adder
4.48
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.007
970293AG2-193 GEN
Solar/Wind Harmer
2.458
3146376EDENTON
Solar/Wind Harmer
-0.02
316075AC2-137 C
Solar/Wind Harmer
0.524
3151731LOISA B
50/50
17.077
315242AE2-183_GT2
50/50
3.093
315241AE2-183_GT1
50/50
3.085
972185AH1-677 GEN
50/50
11.182
3151041BRUNSWICKG3
50/50
2.445
972187AH1-678 GEN
50/50
5.61
966001AG1-469 GEN
Solar/Wind Harmer
0.52
971223AH1-071 GEN
Solar/Wind Harmer
2.972
3143526WINTERP
Solar/Wind Harmer
-0.117
316313AB2-026
Solar/Wind Harmer
0.571
316294AC1-161 GEN
Solar/Wind Harmer
6.742
3144356SAPONY
Solar/Wind Harmer
0.721
316315AB2-025 C
Solar/Wind Harmer
0.556
3150991CHESPKB
Adder
1.927
3150991CHESPKB
Adder
1.88
316185AD1-033 GEN
Solar/Wind Harmer
2.173
316083AB2-161 GEN
Solar/Wind Harmer
3.346
316240AF1-291 C
Solar/Wind Harmer
0.62
3145506HICKORY
Solar/Wind Harmer
-0.082
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
19.306
944641AF1-129 GEN
Adder
87.225
316339AD2-160 GEN
Solar/Wind Harmer
1.382
316388AE2-253 GEN
Solar/Wind Harmer
1.382
316336AC2-165 C
Solar/Wind Harmer
12.829
3137176SLIGO L2192
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
2.421
3130086AYDLETT
Solar/Wind Harmer
-0.081
316349AD2-085 GEN
Solar/Wind Harmer
1.817
316033AB2-134 GEN
Solar/Wind Harmer
6.563
315835AF2-110_GEN
Solar/Wind Harmer
2.547
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.648
316433W1029_GEN2
Solar/Wind Harmer
3.648
316435W1029_GEN3
Solar/Wind Harmer
3.648
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.579
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.7
3150701DARBY 4
Adder
12.671
3150681DARBY 2
Adder
12.656
3150671DARBY 1
Adder
12.641
315742AE1-103 GEN
Solar/Wind Harmer
4.695
3146376EDENTON
Solar/Wind Harmer
0.583
3146376EDENTON
Solar/Wind Harmer
0.583
315976AC1-164 GENA
Solar/Wind Harmer
4.408
316169AC1-164_GENC
Solar/Wind Harmer
3.809
3142296MT RD221
Adder
0.549
970099AG2-077 GEN
Solar/Wind Harmer
24.232
316312AB1-027
Solar/Wind Harmer
0.65
315614AA2-178 GEN
Solar/Wind Harmer
2.076
316365GEN2_N
Solar/Wind Harmer
1.29
316065AD1-022 GEN
Solar/Wind Harmer
9.437
3145893MURPHYS
Solar/Wind Harmer
0.526
3145893MURPHYS
Solar/Wind Harmer
-0.034
316441AF1-014 GEN
Solar/Wind Harmer
1.266
315666AE1-190 GEN
Solar/Wind Harmer
0.563
3146173TUNIS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
316156AD2-030 GEN
Solar/Wind Harmer
0.497
316140AB2-099
Solar/Wind Harmer
0.125
966871AG1-558 GEN
Solar/Wind Harmer
0.559
966871AG1-558 GEN
Solar/Wind Harmer
0.191
313506AB2-031 GEN
Solar/Wind Harmer
1.487
970301AG2-198 GEN
Solar/Wind Harmer
9.265
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
962571AG1-106 GEN
Solar/Wind Harmer
2.641
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
0.152
972189AH1-679 GEN
Adder
2.717
3145783HORNRTN
Solar/Wind Harmer
2.156
3145783HORNRTN
Solar/Wind Harmer
1.725
3145783HORNRTN
Solar/Wind Harmer
0.539
3145783HORNRTN
Solar/Wind Harmer
0.216
3145796HORNRTN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.78
3144293JTRSVLE
Adder
0.378
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
970323AG2-213 GEN
Solar/Wind Harmer
8.831
315687AD1-152 GEN
Solar/Wind Harmer
2.115
316487AF1-042 GEN
Solar/Wind Harmer
2.314
3145933PARMELE
Solar/Wind Harmer
-0.035
3145933PARMELE
Solar/Wind Harmer
-0.017
313527AB2-043 GEN
Solar/Wind Harmer
2.843
316237AB2-079_GEN
Solar/Wind Harmer
0.525
315724AD1-057 GEN
Solar/Wind Harmer
3.374
316005AA1-067
Solar/Wind Harmer
0.347
3145493TOT1
Solar/Wind Harmer
0.26
3145453TOT5
Solar/Wind Harmer
0.156
3145603CNETO
Solar/Wind Harmer
0.104
3150341NORNECKC1
Adder
1.553
3150341NORNECKC1
Adder
1.54
3150391LDYSMT3
Adder
18.203
972195AH1-682 GEN
Adder
2.392
316045AC1-158 PL2
Solar/Wind Helper
17.361
316450AC1-158 RIC
Solar/Wind Helper
1.447
316006AB2-029 C
Solar/Wind Helper
0.163
962561AG1-105 GEN
Solar/Wind Harmer
8.932
3152251N ANNA1
50/50
17.528
3151791S ANNAG2
50/50
0.882
3151781S ANNAS1
50/50
0.453
3151741LOISA C
50/50
0.934
3151751LOISA D
50/50
17.077
970119AG2-088 GEN
50/50
28.212
3150851SPRUNCC
50/50
0.924
315243AE2-183_GT3
50/50
3.093
3151051BRUNSWICKS1
50/50
5.076
3151021BRUNSWICKG1
50/50
2.445
971451AH1-221 GEN
50/50
7.425
3147666LOUISA
Solar/Wind Harmer
-0.135
316192AB2-158 GEN
Solar/Wind Harmer
3.987
315683AE1-153 C
Solar/Wind Harmer
25.64
3143226MDLTHAN
Solar/Wind Harmer
-0.024
3143526WINTERP
Solar/Wind Harmer
-0.117
940641AE2-051 GEN
Solar/Wind Harmer
20.714
939411AE1-173 GEN
Solar/Wind Harmer
108.665
941031AE2-094 GEN
Solar/Wind Harmer
40.579
3143336POWHATN
Solar/Wind Harmer
2.518
315773AC2-141 GEN
Solar/Wind Harmer
8.724
944591AF1-124 GEN
Solar/Wind Harmer
94.686
316375AC2-012 GEN
Solar/Wind Harmer
7.147
316036AC1-147 C
Solar/Wind Harmer
0.556
3150981CHESPKA
Adder
2.297
316381AD1-082 GEN
Solar/Wind Harmer
1.887
315671AE2-027_GEN
Solar/Wind Harmer
3.716
3142543TWELFTH
Solar/Wind Harmer
-0.002
3145336SMITFLD
Solar/Wind Harmer
-0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.02
319010AE1-072 C
Solar/Wind Harmer
4.135
316072AD1-144
Solar/Wind Harmer
0.412
3151171GRAVELC
Adder
1.932
961611AG1-000B GEN
Solar/Wind Harmer
10.067
316369SG1_INVT
Solar/Wind Harmer
3.635
316093AE2-104_GEN
Solar/Wind Harmer
5.924
971069AG2-661 GEN
Solar/Wind Harmer
3.224
316132AB2-190 GEN1
Solar/Wind Harmer
2.054
3143096IRON208
Adder
0.757
970919AG2-571 GEN
Solar/Wind Harmer
6.365
3146516WINFALL
Solar/Wind Harmer
-0.065
3146516WINFALL
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.061
944631AF1-128 GEN
Adder
84.951
970087AG2-069 GEN
Solar/Wind Harmer
18.616
971317AH1-138 GEN
Solar/Wind Harmer
2.477
315611Z1-036_GEN2
Solar/Wind Harmer
4.874
3130156CHOWAN
Solar/Wind Harmer
-0.02
315975AC1-164 GENB
Solar/Wind Harmer
0.13
957481AF2-042 GEN
Solar/Wind Harmer
60.581
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
315816AE2-034 GEN
Solar/Wind Harmer
1.557
3145663CRESWEL
Solar/Wind Harmer
-0.054
971163AH1-040 GEN
Solar/Wind Harmer
18.087
3142433PROV 92
Solar/Wind Harmer
-0.077
3142433PROV 92
Adder
0.333
3142433PROV 92
Adder
0.333
316023GEN1_S
Solar/Wind Harmer
1.29
315693AD1-088 GEN
Solar/Wind Harmer
9.562
315737AD1-076 GEN
Solar/Wind Harmer
3.599
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.559
970937AG2-583 GEN
Solar/Wind Harmer
13.532
3146206CASHIE
Solar/Wind Harmer
-0.019
971547AH1-271 GEN
Solar/Wind Harmer
4.705
960081AF2-299 GEN
Solar/Wind Harmer
2.114
971777AH1-397 GEN
Solar/Wind Harmer
2.192
316314AB2-024 C
Solar/Wind Harmer
1.603
315662AE1-191 GEN
Solar/Wind Harmer
2.253
316280AD1-041 GEN
Solar/Wind Harmer
1.408
3141766HARMONY
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.019
316087AB2-174 GEN
Solar/Wind Harmer
2.652
3156021HOLLOMANSOL
Solar/Wind Harmer
2.5
315607AA1-063A GEN
Solar/Wind Harmer
1.87
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.482
3138133OCRAN
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
971563AH1-280 GEN
Solar/Wind Harmer
2.224
3144293JTRSVLE
Adder
0.378
3144293JTRSVLE
Adder
0.298
3146776BUCKING
Solar/Wind Harmer
-0.007
316129AC1-054 GEN
Solar/Wind Harmer
1.552
970685AG2-442 GEN
Solar/Wind Harmer
15.537
971065AG2-659 GEN
Solar/Wind Harmer
8.855
316034AC1-036 C
Solar/Wind Harmer
0.327
315785AD2-033 C
Solar/Wind Harmer
3.99
316131AB2-060 GEN
Solar/Wind Harmer
1.885
3146293MARTNCO
Solar/Wind Harmer
0.108
962861AG1-135 GEN
Solar/Wind Harmer
6.499
316404AE1-155 C
Solar/Wind Harmer
3.292
958261AF2-120 GEN
Solar/Wind Harmer
6.682
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
316494AC1-189 GEN
Solar/Wind Harmer
1.827
964211AG1-282 GEN
Solar/Wind Harmer
0.508
3141726DUNNSVL
Solar/Wind Harmer
-0.067
316319Z2-044 C
Solar/Wind Harmer
0.929
3146233WITAKRS
Solar/Wind Harmer
-0.067
961671AG1-007 GEN
Solar/Wind Harmer
0.212
3146083TARBORO
Solar/Wind Harmer
-0.017
3145493TOT1
Solar/Wind Harmer
0.498
3150351NORNECKC2
Adder
1.478
972197AH1-683 GEN
Adder
2.848
972219AH1-694 GEN
Adder
2.05
316447AC1-158 HLD
Solar/Wind Helper
11.938
316044AC1-158 PL1
Solar/Wind Helper
5.425
946281AF1-292 GEN
Solar/Wind Harmer
0.421
316059AD1-063 C
Solar/Wind Harmer
0.422
316486AD2-202 GEN
Solar/Wind Harmer
0.472
957601AF2-054 GEN
Solar/Wind Harmer
0.558
3141873WAN 176
Solar/Wind Harmer
-0.004
3146043SEABORD
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.073
315652AC1-086 GEN
Solar/Wind Harmer
20.671
3141913WHIT STONE
Solar/Wind Harmer
-0.018
316426AA2-053 GEN
Solar/Wind Harmer
1.846
3138133OCRAN
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
2.78
3146033SCOT NK
Solar/Wind Harmer
-0.071
970831AG2-522 GEN
Solar/Wind Harmer
8.909
971845AH1-439 GEN
Solar/Wind Harmer
9.453
946301AF1-294 GEN
Solar/Wind Harmer
4.558
961791AG1-021 GEN
Solar/Wind Harmer
2.224
316322AB2-045
Solar/Wind Harmer
0.596
970683AG2-441 GEN
Solar/Wind Harmer
12.52
970681AG2-440 GEN
Solar/Wind Harmer
8.31
316210AC1-098 GEN
Solar/Wind Harmer
2.768
3144303KENBRDG
Solar/Wind Harmer
-0.014
316274AC1-208 GEN
Solar/Wind Harmer
1.892
316238AB2-078_GEN
Solar/Wind Harmer
0.525
316239AB2-077_GEN
Solar/Wind Harmer
0.525
972205AH1-687 GEN
Adder
6.605
3145746EVERETS
Solar/Wind Harmer
-0.068
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
316327AA2-057 GEN
Solar/Wind Harmer
1.723
957861AF2-080 GEN
Solar/Wind Harmer
7.427
3145573BETHELC
Solar/Wind Harmer
-0.017
3145573BETHELC
Solar/Wind Harmer
-0.017
3150411LDYSMT5
Adder
18.294
3150381LDYSMT2
Adder
17.508
972213AH1-691 GEN
Adder
2.962
972215AH1-692 GEN
Adder
2.962
316164AC1-076 GEN
Solar/Wind Helper
2.456
315651AD1-115 GEN
Solar/Wind Helper
1.465
3142416OLDCHRC
Solar/Wind Harmer
1.949
3142433PROV 92
Adder
0.333
3142433PROV 92
Adder
0.333
3156081AA2-088 GEN
Solar/Wind Harmer
6.184
315735AD1-075 GEN1
Solar/Wind Harmer
1.913
3145893MURPHYS
Solar/Wind Harmer
0.132
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
966621AG1-532 GEN
Solar/Wind Harmer
0.381
3141843SHACKLE
Adder
0.854
316203AE2-005 GEN
Solar/Wind Harmer
7.92
3141766HARMONY
Solar/Wind Harmer
1.667
3146173TUNIS
Solar/Wind Harmer
-0.019
316478AD1-087 GEN
Solar/Wind Harmer
1.612
3141873WAN 176
Solar/Wind Harmer
2.215
316473AC1-191 GEN
Solar/Wind Harmer
1.999
316181AB2-040 GEN
Solar/Wind Harmer
2.583
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316011AB1-132 GEN
Solar/Wind Harmer
3.838
316190AA2-174 GEN
Solar/Wind Harmer
0.225
316317KELFORD C
Solar/Wind Harmer
0.843
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.699
3147133PAMPLIN
Solar/Wind Harmer
-0.056
3144293JTRSVLE
Adder
0.378
3146776BUCKING
Solar/Wind Harmer
-0.006
959311AF2-222 GEN
Solar/Wind Harmer
18.454
316212AC1-099_GEN
Solar/Wind Harmer
1.538
970257AG2-171 GEN
Solar/Wind Harmer
6.623
971775AH1-396 GEN
Solar/Wind Harmer
1.246
316484AD2-074 GEN
Solar/Wind Harmer
4.423
961951AG1-038 GEN
Solar/Wind Harmer
2.314
964241AG1-285 GEN
Solar/Wind Harmer
13.724
3145933PARMELE
Solar/Wind Harmer
-0.017
972003AH1-546 GEN
Solar/Wind Harmer
7.076
315722AD1-056 GEN
Solar/Wind Harmer
6.135
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
316420AA1-050 GEN
Solar/Wind Harmer
1.921
3146233WITAKRS
Solar/Wind Harmer
0.352
3146233WITAKRS
Solar/Wind Harmer
-0.011
3138543CONSLDL
Solar/Wind Harmer
-0.011
3146073TAR RVR
Solar/Wind Harmer
-0.017
3146083TARBORO
Solar/Wind Harmer
-0.017
3150351NORNECKC2
Adder
1.503
3150401LDYSMT4
Adder
18.237
3150371LDYSMT1
Adder
17.622
LAGNLTFEXP_LAGN->PJM
CLTF
6.793
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.212
TVALTFEXP_TVA->PJM
CLTF
3.442
CPLELTFEXP_CPLE->PJM
CLTF
9.674
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.07
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.707
MECLTFEXP_MEC->PJM
CLTF
3.071
SIGELTFEXP_SIGE->PJM
CLTF
0.093
NYPJM->LTFIMP_NY
CLTF
2.642
LGEELTFEXP_LGEE->PJM
CLTF
1.128
WECLTFEXP_WEC->PJM
CLTF
0.546

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.38 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4309.68
MW Contribution:
7.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
17.528
3151791S ANNAG2
50/50
0.882
3151781S ANNAS1
50/50
0.453
3151741LOISA C
50/50
0.934
3151751LOISA D
50/50
17.077
970119AG2-088 GEN
50/50
28.212
3150851SPRUNCC
50/50
0.924
315243AE2-183_GT3
50/50
3.093
3151051BRUNSWICKS1
50/50
5.076
3151021BRUNSWICKG1
50/50
2.445
971451AH1-221 GEN
50/50
7.425
3147666LOUISA
Solar/Wind Harmer
-0.135
316192AB2-158 GEN
Solar/Wind Harmer
3.987
3143226MDLTHAN
Solar/Wind Harmer
-0.024
3143526WINTERP
Solar/Wind Harmer
-0.117
940641AE2-051 GEN
Solar/Wind Harmer
20.714
939411AE1-173 GEN
Solar/Wind Harmer
108.665
941031AE2-094 GEN
Solar/Wind Harmer
40.579
3143336POWHATN
Solar/Wind Harmer
2.518
315773AC2-141 GEN
Solar/Wind Harmer
8.724
944591AF1-124 GEN
Solar/Wind Harmer
94.686
316375AC2-012 GEN
Solar/Wind Harmer
7.147
316036AC1-147 C
Solar/Wind Harmer
0.556
3150981CHESPKA
Adder
2.297
316381AD1-082 GEN
Solar/Wind Harmer
1.887
315671AE2-027_GEN
Solar/Wind Harmer
3.716
3142543TWELFTH
Solar/Wind Harmer
-0.002
3145336SMITFLD
Solar/Wind Harmer
-0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.02
319010AE1-072 C
Solar/Wind Harmer
4.135
316072AD1-144
Solar/Wind Harmer
0.412
3151171GRAVELC
Adder
1.932
961611AG1-000B GEN
Solar/Wind Harmer
10.067
316369SG1_INVT
Solar/Wind Harmer
3.635
316093AE2-104_GEN
Solar/Wind Harmer
5.924
971069AG2-661 GEN
Solar/Wind Harmer
3.224
316132AB2-190 GEN1
Solar/Wind Harmer
2.054
3143096IRON208
Adder
0.757
970919AG2-571 GEN
Solar/Wind Harmer
6.365
3146516WINFALL
Solar/Wind Harmer
-0.065
3146516WINFALL
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.061
944631AF1-128 GEN
Adder
84.951
970087AG2-069 GEN
Solar/Wind Harmer
18.616
971317AH1-138 GEN
Solar/Wind Harmer
2.477
315611Z1-036_GEN2
Solar/Wind Harmer
4.874
3130156CHOWAN
Solar/Wind Harmer
-0.02
315975AC1-164 GENB
Solar/Wind Harmer
0.13
957481AF2-042 GEN
Solar/Wind Harmer
60.581
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
315816AE2-034 GEN
Solar/Wind Harmer
1.557
3145663CRESWEL
Solar/Wind Harmer
-0.054
971163AH1-040 GEN
Solar/Wind Harmer
18.087
3142433PROV 92
Solar/Wind Harmer
-0.077
3142433PROV 92
Adder
0.333
3142433PROV 92
Adder
0.333
316023GEN1_S
Solar/Wind Harmer
1.29
315693AD1-088 GEN
Solar/Wind Harmer
9.562
315737AD1-076 GEN
Solar/Wind Harmer
3.599
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.559
970937AG2-583 GEN
Solar/Wind Harmer
13.532
316303AF2-085
50/50
3.762
971285AH1-108 GEN
50/50
1.512
315244AE2-183_ST
50/50
5.372
963041AG1-153 GEN
50/50
4.95
3147346CASHSCORNER
Solar/Wind Harmer
0.409
316233AE1-074 FULL
Solar/Wind Harmer
0.608
971281AH1-106 GEN
Solar/Wind Harmer
3.673
971283AH1-107 GEN
Solar/Wind Harmer
3.673
970533AG2-339 GEN
Solar/Wind Harmer
14.554
970673AG2-436 GEN
Solar/Wind Harmer
46.871
316258AE1-075 C
Solar/Wind Harmer
0.514
316405AF2-144 C
Solar/Wind Harmer
0.542
3143316POE
Solar/Wind Harmer
-0.083
971967AH1-528 GEN
Solar/Wind Harmer
39.41
315839AE2-212 C
Solar/Wind Harmer
0.625
3151081ELIZAR1
Adder
16.872
3151091ELIZAR2
Adder
16.579
316316AC1-027 C
Solar/Wind Harmer
0.633
970657AG2-426 GEN
Solar/Wind Harmer
1.299
315814AE2-033 C
Solar/Wind Harmer
19.184
316018AA1-139 ULT2
Solar/Wind Harmer
1.755
957871AF2-081 GEN
Solar/Wind Harmer
10.267
316236AE1-162_GEN
Solar/Wind Harmer
0.617
971445AH1-216 GEN
Solar/Wind Harmer
12.688
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.887
316311AC2-079 GEN
Solar/Wind Harmer
10.325
3151201GRAVEL4
Adder
13.223
3151221GRAVEL6
Adder
13.208
3151191GRAVEL3
Adder
13.056
3151211GRAVEL5
Adder
13.056
315697AD1-025 GEN
Solar/Wind Harmer
4.113
313526AB2-022
Solar/Wind Harmer
0.547
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146396TANGLEW
Solar/Wind Harmer
0.372
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.411
970581AG2-369 GEN
Solar/Wind Harmer
10.673
316382AG1-145 C
Solar/Wind Harmer
0.596
316159AE1-175 C
Solar/Wind Harmer
0.53
315800Z1-036_GEN1
Solar/Wind Harmer
4.874
3130156CHOWAN
Solar/Wind Harmer
-0.02
3130156CHOWAN
Solar/Wind Harmer
-0.02
957831AF2-077 GEN
Solar/Wind Harmer
0.583
3138283WHITEMARSH
Solar/Wind Harmer
0.03
3142433PROV 92
Adder
0.333
3142433PROV 92
Adder
0.333
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
315732AD1-074 GEN1
Solar/Wind Harmer
3.828
315733AD1-074 GEN2
Solar/Wind Harmer
3.828
3143873LANEXA
Solar/Wind Harmer
-0.011
316318V4-068
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
-0.051
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
970601AG2-382 GEN
Solar/Wind Harmer
8.234
946281AF1-292 GEN
Solar/Wind Harmer
0.421
316059AD1-063 C
Solar/Wind Harmer
0.422
316486AD2-202 GEN
Solar/Wind Harmer
0.472
957601AF2-054 GEN
Solar/Wind Harmer
0.558
3141873WAN 176
Solar/Wind Harmer
-0.004
3146043SEABORD
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.073
315652AC1-086 GEN
Solar/Wind Harmer
20.671
3141913WHIT STONE
Solar/Wind Harmer
-0.018
316426AA2-053 GEN
Solar/Wind Harmer
1.846
3138133OCRAN
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
2.78
3146033SCOT NK
Solar/Wind Harmer
-0.071
970831AG2-522 GEN
Solar/Wind Harmer
8.909
971845AH1-439 GEN
Solar/Wind Harmer
9.453
946301AF1-294 GEN
Solar/Wind Harmer
4.558
961791AG1-021 GEN
Solar/Wind Harmer
2.224
316322AB2-045
Solar/Wind Harmer
0.596
970683AG2-441 GEN
Solar/Wind Harmer
12.52
970681AG2-440 GEN
Solar/Wind Harmer
8.31
316210AC1-098 GEN
Solar/Wind Harmer
2.768
3144303KENBRDG
Solar/Wind Harmer
-0.014
316274AC1-208 GEN
Solar/Wind Harmer
1.892
316238AB2-078_GEN
Solar/Wind Harmer
0.525
316239AB2-077_GEN
Solar/Wind Harmer
0.525
972205AH1-687 GEN
Adder
6.605
3145746EVERETS
Solar/Wind Harmer
-0.068
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
316327AA2-057 GEN
Solar/Wind Harmer
1.723
957861AF2-080 GEN
Solar/Wind Harmer
7.427
3145573BETHELC
Solar/Wind Harmer
-0.017
3145573BETHELC
Solar/Wind Harmer
-0.017
3141813NORNECK
Solar/Wind Harmer
-0.017
3150411LDYSMT5
Adder
18.294
3150381LDYSMT2
Adder
17.508
972213AH1-691 GEN
Adder
2.962
972215AH1-692 GEN
Adder
2.962
316164AC1-076 GEN
Solar/Wind Helper
2.456
315651AD1-115 GEN
Solar/Wind Helper
1.465
3152261N ANNA2
50/50
17.537
3151771S ANNAG1
50/50
0.882
3151801S ANNAS2
50/50
0.453
3151761LOISA E
50/50
34.815
3151721LOISA A
50/50
16.989
3150861SPRUNCD
50/50
0.924
3151031BRUNSWICKG2
50/50
2.445
3147666LOUISA
Solar/Wind Harmer
-0.078
944011AF1-069 GEN
Solar/Wind Harmer
12.715
3143336POWHATN
Solar/Wind Harmer
2.14
944581AF1-123 GEN
Solar/Wind Harmer
94.347
944601AF1-125 GEN
Solar/Wind Harmer
92.874
315813AE1-149 C
Solar/Wind Harmer
12.955
3151101ELIZAR3
Adder
17.088
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142956BIRDNECK
Solar/Wind Harmer
1.108
3144536CHRHLND
Solar/Wind Harmer
-0.003
970657AG2-426 GEN
Solar/Wind Harmer
4.164
316017AA1-139 ULT1
Solar/Wind Harmer
1.657
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.372
316305AF2-043 C
Solar/Wind Harmer
0.615
316246AF1-032 C
Solar/Wind Harmer
0.413
3151171GRAVELC
Adder
2.541
961611AG1-000B GEN
Solar/Wind Harmer
4.296
315778AD1-151 GEN
Solar/Wind Harmer
18.134
316458AB2-190 GEN2
Solar/Wind Harmer
2.054
970133AG2-095 GEN
Solar/Wind Harmer
2.289
316320Y1-086
Solar/Wind Harmer
1.19
3143096IRON208
Adder
0.757
3143096IRON208
Adder
0.741
316321Z2-027
Solar/Wind Harmer
0.545
970917AG2-570 GEN
Solar/Wind Harmer
50.28
3146516WINFALL
Solar/Wind Harmer
-0.02
3144216WINCHST
Adder
0.674
3150921YORKTN3
Adder
4.48
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.007
970293AG2-193 GEN
Solar/Wind Harmer
2.458
3146376EDENTON
Solar/Wind Harmer
-0.02
316075AC2-137 C
Solar/Wind Harmer
0.524
3142416OLDCHRC
Solar/Wind Harmer
1.949
3142433PROV 92
Adder
0.333
3142433PROV 92
Adder
0.333
3156081AA2-088 GEN
Solar/Wind Harmer
6.184
315735AD1-075 GEN1
Solar/Wind Harmer
1.913
3145893MURPHYS
Solar/Wind Harmer
0.132
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
966621AG1-532 GEN
Solar/Wind Harmer
0.381
3141843SHACKLE
Adder
0.854
316203AE2-005 GEN
Solar/Wind Harmer
7.92
3141766HARMONY
Solar/Wind Harmer
1.667
3146173TUNIS
Solar/Wind Harmer
-0.019
316478AD1-087 GEN
Solar/Wind Harmer
1.612
3141873WAN 176
Solar/Wind Harmer
2.215
316473AC1-191 GEN
Solar/Wind Harmer
1.999
316181AB2-040 GEN
Solar/Wind Harmer
2.583
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316011AB1-132 GEN
Solar/Wind Harmer
3.838
316190AA2-174 GEN
Solar/Wind Harmer
0.225
316317KELFORD C
Solar/Wind Harmer
0.843
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.699
3147133PAMPLIN
Solar/Wind Harmer
-0.056
3144293JTRSVLE
Adder
0.378
3146776BUCKING
Solar/Wind Harmer
-0.006
959311AF2-222 GEN
Solar/Wind Harmer
18.454
316212AC1-099_GEN
Solar/Wind Harmer
1.538
970257AG2-171 GEN
Solar/Wind Harmer
6.623
971775AH1-396 GEN
Solar/Wind Harmer
1.246
316484AD2-074 GEN
Solar/Wind Harmer
4.423
961951AG1-038 GEN
Solar/Wind Harmer
2.314
964241AG1-285 GEN
Solar/Wind Harmer
13.724
3145933PARMELE
Solar/Wind Harmer
-0.017
972003AH1-546 GEN
Solar/Wind Harmer
7.076
315722AD1-056 GEN
Solar/Wind Harmer
6.135
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
316420AA1-050 GEN
Solar/Wind Harmer
1.921
3146233WITAKRS
Solar/Wind Harmer
0.352
3146233WITAKRS
Solar/Wind Harmer
-0.011
3138543CONSLDL
Solar/Wind Harmer
-0.011
3146073TAR RVR
Solar/Wind Harmer
-0.017
3146083TARBORO
Solar/Wind Harmer
-0.017
316077AC2-138 C
Solar/Wind Harmer
0.351
3150351NORNECKC2
Adder
1.503
966881AG1-559 GEN
Solar/Wind Harmer
0.501
3150401LDYSMT4
Adder
18.237
3150371LDYSMT1
Adder
17.622
961601AG1-000A GEN
Solar/Wind Harmer
4.708
3151731LOISA B
50/50
17.077
315242AE2-183_GT2
50/50
3.093
315241AE2-183_GT1
50/50
3.085
972185AH1-677 GEN
50/50
11.182
3151041BRUNSWICKG3
50/50
2.445
972187AH1-678 GEN
50/50
5.61
966001AG1-469 GEN
Solar/Wind Harmer
0.52
971223AH1-071 GEN
Solar/Wind Harmer
2.972
3143526WINTERP
Solar/Wind Harmer
-0.117
316313AB2-026
Solar/Wind Harmer
0.571
316294AC1-161 GEN
Solar/Wind Harmer
6.742
3144356SAPONY
Solar/Wind Harmer
0.721
316315AB2-025 C
Solar/Wind Harmer
0.556
3150991CHESPKB
Adder
1.927
3150991CHESPKB
Adder
1.88
316185AD1-033 GEN
Solar/Wind Harmer
2.173
316083AB2-161 GEN
Solar/Wind Harmer
3.346
316240AF1-291 C
Solar/Wind Harmer
0.62
3145506HICKORY
Solar/Wind Harmer
-0.082
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
19.306
944641AF1-129 GEN
Adder
87.225
316339AD2-160 GEN
Solar/Wind Harmer
1.382
316388AE2-253 GEN
Solar/Wind Harmer
1.382
316336AC2-165 C
Solar/Wind Harmer
12.829
3137176SLIGO L2192
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
2.421
3130086AYDLETT
Solar/Wind Harmer
-0.081
316349AD2-085 GEN
Solar/Wind Harmer
1.817
316033AB2-134 GEN
Solar/Wind Harmer
6.563
315835AF2-110_GEN
Solar/Wind Harmer
2.547
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.648
316433W1029_GEN2
Solar/Wind Harmer
3.648
316435W1029_GEN3
Solar/Wind Harmer
3.648
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.579
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.7
3150701DARBY 4
Adder
12.671
3150681DARBY 2
Adder
12.656
3150671DARBY 1
Adder
12.641
315742AE1-103 GEN
Solar/Wind Harmer
4.695
3146376EDENTON
Solar/Wind Harmer
0.583
3146376EDENTON
Solar/Wind Harmer
0.583
315976AC1-164 GENA
Solar/Wind Harmer
4.408
316169AC1-164_GENC
Solar/Wind Harmer
3.809
3142296MT RD221
Adder
0.549
970099AG2-077 GEN
Solar/Wind Harmer
24.232
316312AB1-027
Solar/Wind Harmer
0.65
315614AA2-178 GEN
Solar/Wind Harmer
2.076
316365GEN2_N
Solar/Wind Harmer
1.29
316065AD1-022 GEN
Solar/Wind Harmer
9.437
3145893MURPHYS
Solar/Wind Harmer
0.526
3145893MURPHYS
Solar/Wind Harmer
-0.034
316441AF1-014 GEN
Solar/Wind Harmer
1.266
315666AE1-190 GEN
Solar/Wind Harmer
0.563
3146173TUNIS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
316156AD2-030 GEN
Solar/Wind Harmer
0.497
316140AB2-099
Solar/Wind Harmer
0.125
966871AG1-558 GEN
Solar/Wind Harmer
0.559
966871AG1-558 GEN
Solar/Wind Harmer
0.191
313506AB2-031 GEN
Solar/Wind Harmer
1.487
970301AG2-198 GEN
Solar/Wind Harmer
9.265
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
962571AG1-106 GEN
Solar/Wind Harmer
2.641
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
0.152
972189AH1-679 GEN
Adder
2.717
3145783HORNRTN
Solar/Wind Harmer
2.156
3145783HORNRTN
Solar/Wind Harmer
1.725
3145783HORNRTN
Solar/Wind Harmer
0.539
3145783HORNRTN
Solar/Wind Harmer
0.216
3145796HORNRTN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.78
3144293JTRSVLE
Adder
0.378
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
970323AG2-213 GEN
Solar/Wind Harmer
8.831
315687AD1-152 GEN
Solar/Wind Harmer
2.115
316487AF1-042 GEN
Solar/Wind Harmer
2.314
3145933PARMELE
Solar/Wind Harmer
-0.035
3145933PARMELE
Solar/Wind Harmer
-0.017
313527AB2-043 GEN
Solar/Wind Harmer
2.843
316237AB2-079_GEN
Solar/Wind Harmer
0.525
315724AD1-057 GEN
Solar/Wind Harmer
3.374
316005AA1-067
Solar/Wind Harmer
0.347
3145493TOT1
Solar/Wind Harmer
0.26
3145453TOT5
Solar/Wind Harmer
0.156
3145603CNETO
Solar/Wind Harmer
0.104
962561AG1-105 GEN
Solar/Wind Harmer
9.404
3150341NORNECKC1
Adder
1.553
3150341NORNECKC1
Adder
1.54
964791AG1-342 GEN
Solar/Wind Harmer
3.54
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
3150391LDYSMT3
Adder
18.203
972195AH1-682 GEN
Adder
2.392
316045AC1-158 PL2
Solar/Wind Helper
17.361
316450AC1-158 RIC
Solar/Wind Helper
1.447
316006AB2-029 C
Solar/Wind Helper
0.163
961601AG1-000A GEN
Solar/Wind Harmer
4.649
3146206CASHIE
Solar/Wind Harmer
-0.019
971547AH1-271 GEN
Solar/Wind Harmer
4.705
960081AF2-299 GEN
Solar/Wind Harmer
2.114
971777AH1-397 GEN
Solar/Wind Harmer
2.192
316314AB2-024 C
Solar/Wind Harmer
1.603
315662AE1-191 GEN
Solar/Wind Harmer
2.253
316280AD1-041 GEN
Solar/Wind Harmer
1.408
3141766HARMONY
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.019
316087AB2-174 GEN
Solar/Wind Harmer
2.652
3156021HOLLOMANSOL
Solar/Wind Harmer
2.5
315607AA1-063A GEN
Solar/Wind Harmer
1.87
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.482
3138133OCRAN
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
971563AH1-280 GEN
Solar/Wind Harmer
2.224
3144293JTRSVLE
Adder
0.378
3144293JTRSVLE
Adder
0.298
3146776BUCKING
Solar/Wind Harmer
-0.007
316129AC1-054 GEN
Solar/Wind Harmer
1.552
970685AG2-442 GEN
Solar/Wind Harmer
15.537
971065AG2-659 GEN
Solar/Wind Harmer
8.855
316034AC1-036 C
Solar/Wind Harmer
0.327
315785AD2-033 C
Solar/Wind Harmer
3.99
316131AB2-060 GEN
Solar/Wind Harmer
1.885
3146293MARTNCO
Solar/Wind Harmer
0.108
962861AG1-135 GEN
Solar/Wind Harmer
6.499
316404AE1-155 C
Solar/Wind Harmer
3.292
958261AF2-120 GEN
Solar/Wind Harmer
6.682
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
316494AC1-189 GEN
Solar/Wind Harmer
1.827
964211AG1-282 GEN
Solar/Wind Harmer
0.508
3141726DUNNSVL
Solar/Wind Harmer
-0.067
316319Z2-044 C
Solar/Wind Harmer
0.929
3146233WITAKRS
Solar/Wind Harmer
-0.067
961671AG1-007 GEN
Solar/Wind Harmer
0.212
3146083TARBORO
Solar/Wind Harmer
-0.017
3145493TOT1
Solar/Wind Harmer
0.498
3150351NORNECKC2
Adder
1.478
966881AG1-559 GEN
Solar/Wind Harmer
0.171
970401AG2-262 GEN
Solar/Wind Harmer
1.082
972197AH1-683 GEN
Adder
2.848
972219AH1-694 GEN
Adder
2.05
316447AC1-158 HLD
Solar/Wind Helper
11.938
316044AC1-158 PL1
Solar/Wind Helper
5.425
LAGNLTFEXP_LAGN->PJM
CLTF
6.793
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.212
TVALTFEXP_TVA->PJM
CLTF
3.442
CPLELTFEXP_CPLE->PJM
CLTF
9.674
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.07
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.707
MECLTFEXP_MEC->PJM
CLTF
3.071
SIGELTFEXP_SIGE->PJM
CLTF
0.093
NYPJM->LTFIMP_NY
CLTF
2.642
LGEELTFEXP_LGEE->PJM
CLTF
1.128
WECLTFEXP_WEC->PJM
CLTF
0.546

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.67 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3470.14
MW Contribution:
4.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.63
971285AH1-108 GEN
50/50
1.467
315244AE2-183_ST
50/50
5.2
963041AG1-153 GEN
50/50
4.788
3151081ELIZAR1
50/50
17.404
3151091ELIZAR2
50/50
17.102
941591AE2-156 GEN
50/50
15.904
315779AE2-040
50/50
2.49
316233AE1-074 FULL
Solar/Wind Harmer
0.156
971281AH1-106 GEN
Solar/Wind Harmer
2.699
971283AH1-107 GEN
Solar/Wind Harmer
2.699
970533AG2-339 GEN
Solar/Wind Harmer
14.109
970673AG2-436 GEN
Solar/Wind Harmer
22.993
3143316POE
Solar/Wind Harmer
0.72
971967AH1-528 GEN
Solar/Wind Harmer
28.823
316316AC1-027 C
Solar/Wind Harmer
0.17
970657AG2-426 GEN
Solar/Wind Harmer
1.309
315814AE2-033 C
Solar/Wind Harmer
14.057
957871AF2-081 GEN
Solar/Wind Harmer
8.839
971445AH1-216 GEN
Solar/Wind Harmer
12.494
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316311AC2-079 GEN
Solar/Wind Harmer
5.081
3151201GRAVEL4
Adder
12.861
3151221GRAVEL6
Adder
12.846
3151191GRAVEL3
Adder
12.698
3151211GRAVEL5
Adder
12.698
315697AD1-025 GEN
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.094
3146486SUNBURY
Solar/Wind Harmer
0.175
3146486SUNBURY
Solar/Wind Harmer
0.175
3146396TANGLEW
Solar/Wind Harmer
0.482
3145176PASQUOTANK
Solar/Wind Harmer
0.108
316258AE1-075 C
Solar/Wind Harmer
0.13
316159AE1-175 C
Solar/Wind Harmer
0.147
970085AG2-068 GEN
Solar/Wind Harmer
9.103
970581AG2-369 GEN
Solar/Wind Harmer
7.829
3130156CHOWAN
Solar/Wind Harmer
0.169
3130156CHOWAN
Solar/Wind Harmer
0.169
3138283WHITEMARSH
Solar/Wind Harmer
0.039
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3143873LANEXA
Solar/Wind Harmer
0.099
3130546PLYMOUTH
Solar/Wind Harmer
0.164
315732AD1-074 GEN1
Solar/Wind Harmer
0.93
315733AD1-074 GEN2
Solar/Wind Harmer
0.93
970189AG2-124 GEN
Solar/Wind Harmer
4.836
3141873WAN 176
Solar/Wind Harmer
0.032
3146206CASHIE
Solar/Wind Harmer
0.162
970601AG2-382 GEN
Solar/Wind Harmer
6.045
3145893MURPHYS
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.162
316463AE2-346 GEN
Solar/Wind Harmer
0.136
3145513AHOSKIE
Solar/Wind Harmer
0.334
3145513AHOSKIE
Solar/Wind Harmer
0.16
3141913WHIT STONE
Solar/Wind Harmer
0.16
3146043SEABORD
Solar/Wind Harmer
0.159
3138133OCRAN
Solar/Wind Harmer
0.048
3145683EARLEYS
Solar/Wind Harmer
0.318
3145683EARLEYS
Solar/Wind Harmer
0.159
3145683EARLEYS
Solar/Wind Harmer
0.159
316486AD2-202 GEN
Solar/Wind Harmer
0.161
3141783LANCAST
Solar/Wind Harmer
0.095
3141783LANCAST
Solar/Wind Harmer
0.063
315652AC1-086 GEN
Solar/Wind Harmer
17.328
3137643SOCKMAN
Solar/Wind Harmer
0.629
316426AA2-053 GEN
Solar/Wind Harmer
0.524
3145796HORNRTN
Solar/Wind Harmer
0.496
3145796HORNRTN
Solar/Wind Harmer
0.062
3146033SCOT NK
Solar/Wind Harmer
0.614
316210AC1-098 GEN
Solar/Wind Harmer
1.398
970831AG2-522 GEN
Solar/Wind Harmer
6.453
316274AC1-208 GEN
Solar/Wind Harmer
0.775
3145746EVERETS
Solar/Wind Harmer
0.586
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
316327AA2-057 GEN
Solar/Wind Harmer
0.216
3144303KENBRDG
Solar/Wind Harmer
0.116
3141813NORNECK
Solar/Wind Harmer
0.145
957861AF2-080 GEN
Solar/Wind Harmer
6.264
970683AG2-441 GEN
Solar/Wind Harmer
8.755
970681AG2-440 GEN
Solar/Wind Harmer
5.811
946301AF1-294 GEN
Solar/Wind Harmer
2.86
961791AG1-021 GEN
Solar/Wind Harmer
1.391
3145573BETHELC
Solar/Wind Harmer
0.143
3145573BETHELC
Solar/Wind Harmer
0.143
971845AH1-439 GEN
Solar/Wind Harmer
6.215
3150411LDYSMT5
Adder
18.379
3150381LDYSMT2
Adder
17.59
972213AH1-691 GEN
Adder
2.976
972215AH1-692 GEN
Adder
2.976
3147173SINAI
Solar/Wind Harmer
0.134
3147243WELCO
Solar/Wind Harmer
0.084
972205AH1-687 GEN
Adder
5.48
316164AC1-076 GEN
Solar/Wind Helper
1.643
315651AD1-115 GEN
Solar/Wind Helper
0.751
315242AE2-183_GT2
50/50
2.994
315241AE2-183_GT1
50/50
2.986
972185AH1-677 GEN
50/50
10.823
3151041BRUNSWICKG3
50/50
2.365
972187AH1-678 GEN
50/50
5.426
3150991CHESPKB
50/50
1.987
3150991CHESPKB
50/50
1.94
971223AH1-071 GEN
Solar/Wind Harmer
2.178
3143526WINTERP
Solar/Wind Harmer
1.011
316294AC1-161 GEN
Solar/Wind Harmer
3.119
3144356SAPONY
Solar/Wind Harmer
1.492
316315AB2-025 C
Solar/Wind Harmer
0.143
3145506HICKORY
Solar/Wind Harmer
0.713
3145506HICKORY
Solar/Wind Harmer
0.428
3145506HICKORY
Solar/Wind Harmer
0.107
944641AF1-129 GEN
Adder
84.836
316339AD2-160 GEN
Solar/Wind Harmer
0.284
316388AE2-253 GEN
Solar/Wind Harmer
0.553
3137176SLIGO L2192
Solar/Wind Harmer
0.705
3146456SLIGO L269
Solar/Wind Harmer
3.136
3130086AYDLETT
Solar/Wind Harmer
0.708
316349AD2-085 GEN
Solar/Wind Harmer
0.118
316033AB2-134 GEN
Solar/Wind Harmer
0.001
970933AG2-581 GEN
Solar/Wind Harmer
14.117
315835AF2-110_GEN
Solar/Wind Harmer
1.208
3146386ELIZ CT
Solar/Wind Harmer
0.175
316313AB2-026
Solar/Wind Harmer
0.108
3146516WINFALL
Solar/Wind Harmer
0.173
3146516WINFALL
Solar/Wind Harmer
0.173
3146516WINFALL
Solar/Wind Harmer
0.173
3142366NRTHEST
Adder
0.564
3146626S HERTFORD
Solar/Wind Harmer
0.172
3146626S HERTFORD
Solar/Wind Harmer
0.172
3142946ENON
Solar/Wind Harmer
0.017
3150691DARBY 3
Adder
12.373
3150701DARBY 4
Adder
12.344
3150681DARBY 2
Adder
12.33
3150671DARBY 1
Adder
12.316
315742AE1-103 GEN
Solar/Wind Harmer
2.547
3146376EDENTON
Solar/Wind Harmer
0.753
3146376EDENTON
Solar/Wind Harmer
0.753
3142296MT RD221
Adder
0.536
315976AC1-164 GENA
Solar/Wind Harmer
1.77
316169AC1-164_GENC
Solar/Wind Harmer
1.529
316312AB1-027
Solar/Wind Harmer
0.298
315614AA2-178 GEN
Solar/Wind Harmer
0.946
316336AC2-165 C
Solar/Wind Harmer
8.407
316365GEN2_N
Solar/Wind Harmer
0.366
970099AG2-077 GEN
Solar/Wind Harmer
17.56
316065AD1-022 GEN
Solar/Wind Harmer
7.478
316156AD2-030 GEN
Solar/Wind Harmer
0.119
3145893MURPHYS
Solar/Wind Harmer
1.083
3145893MURPHYS
Solar/Wind Harmer
0.291
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
0.16
3146173TUNIS
Solar/Wind Harmer
0.16
316140AB2-099
Solar/Wind Harmer
0.057
972189AH1-679 GEN
Adder
2.669
313506AB2-031 GEN
Solar/Wind Harmer
0.486
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.095
962571AG1-106 GEN
Solar/Wind Harmer
2.241
3145593CAROLNA
Solar/Wind Harmer
0.156
3145593CAROLNA
Solar/Wind Harmer
0.156
3145593CAROLNA
Solar/Wind Harmer
0.195
3145783HORNRTN
Solar/Wind Harmer
2.763
3145783HORNRTN
Solar/Wind Harmer
2.21
3145783HORNRTN
Solar/Wind Harmer
0.691
3145783HORNRTN
Solar/Wind Harmer
0.276
3145796HORNRTN
Solar/Wind Harmer
0.465
970301AG2-198 GEN
Solar/Wind Harmer
6.437
3145933PARMELE
Solar/Wind Harmer
0.3
3145933PARMELE
Solar/Wind Harmer
0.15
315724AD1-057 GEN
Solar/Wind Harmer
2.844
316005AA1-067
Solar/Wind Harmer
0.157
970323AG2-213 GEN
Solar/Wind Harmer
6.213
3150341NORNECKC1
Adder
1.523
3150341NORNECKC1
Adder
1.511
958211AF2-115 GEN
Solar/Wind Harmer
1.739
3144293JTRSVLE
Adder
0.346
3147133PAMPLIN
Solar/Wind Harmer
0.145
3147133PAMPLIN
Solar/Wind Harmer
0.116
3145493TOT1
Solar/Wind Harmer
0.333
3145453TOT5
Solar/Wind Harmer
0.199
3145603CNETO
Solar/Wind Harmer
0.133
315673AE1-157 GEN
Solar/Wind Harmer
9.911
961601AG1-000A GEN
Solar/Wind Harmer
2.512
316049AB1-081 GEN
Solar/Wind Harmer
0.803
316263AC1-034 GEN
Solar/Wind Harmer
5.367
962561AG1-105 GEN
Solar/Wind Harmer
6.727
964791AG1-342 GEN
Solar/Wind Harmer
2.669
3146843MT LREL
Solar/Wind Harmer
0.139
3146843MT LREL
Solar/Wind Harmer
0.139
3150391LDYSMT3
Adder
18.288
972195AH1-682 GEN
Adder
2.403
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316118AC1-105 GEN
Solar/Wind Harmer
0.349
316045AC1-158 PL2
Solar/Wind Helper
17.222
3152261N ANNA2
50/50
17.378
3150861SPRUNCD
50/50
0.897
3151031BRUNSWICKG2
50/50
2.365
3151101ELIZAR3
50/50
17.627
3147666LOUISA
Solar/Wind Harmer
0.506
944011AF1-069 GEN
Solar/Wind Harmer
11.238
944581AF1-123 GEN
Solar/Wind Harmer
40.402
944601AF1-125 GEN
Solar/Wind Harmer
39.78
315813AE1-149 C
Solar/Wind Harmer
9.563
3144873MCLAUGH
Solar/Wind Harmer
0.004
3144536CHRHLND
Solar/Wind Harmer
0.027
970657AG2-426 GEN
Solar/Wind Harmer
3.999
316017AA1-139 ULT1
Solar/Wind Harmer
0.095
3145336SMITFLD
Solar/Wind Harmer
0.071
3146456SLIGO L269
Solar/Wind Harmer
0.177
971153AH1-033 GEN
Solar/Wind Harmer
2.049
316246AF1-032 C
Solar/Wind Harmer
0.079
3151171GRAVELC
Adder
2.471
961611AG1-000B GEN
Solar/Wind Harmer
4.709
315778AD1-151 GEN
Solar/Wind Harmer
14.112
316458AB2-190 GEN2
Solar/Wind Harmer
0.94
970133AG2-095 GEN
Solar/Wind Harmer
1.692
3143096IRON208
Adder
0.736
3143096IRON208
Adder
0.721
316321Z2-027
Solar/Wind Harmer
0.031
3144216WINCHST
Adder
0.656
3143336POWHATN
Solar/Wind Harmer
2.627
3146516WINFALL
Solar/Wind Harmer
0.173
3150921YORKTN3
Adder
4.362
970917AG2-570 GEN
Solar/Wind Harmer
15.373
3146626S HERTFORD
Solar/Wind Harmer
0.172
3145273HOLLAND
Solar/Wind Harmer
0.129
3142946ENON
Solar/Wind Harmer
0.057
970293AG2-193 GEN
Solar/Wind Harmer
1.819
3146376EDENTON
Solar/Wind Harmer
0.169
316075AC2-137 C
Solar/Wind Harmer
0.045
3142416OLDCHRC
Solar/Wind Harmer
1.626
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.464
3141843SHACKLE
Adder
0.834
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
2.17
3141873WAN 176
Solar/Wind Harmer
2.884
3146206CASHIE
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
0.271
3145893MURPHYS
Solar/Wind Harmer
0.162
316473AC1-191 GEN
Solar/Wind Harmer
0.546
3146173TUNIS
Solar/Wind Harmer
0.16
316181AB2-040 GEN
Solar/Wind Harmer
0.226
3146263WOODLND
Solar/Wind Harmer
0.158
316478AD1-087 GEN
Solar/Wind Harmer
0.548
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
316011AB1-132 GEN
Solar/Wind Harmer
2.857
3147043LAWRENC
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
0.156
3145823KELFORD
Solar/Wind Harmer
0.156
3145796HORNRTN
Solar/Wind Harmer
0.62
3145796HORNRTN
Solar/Wind Harmer
0.155
316212AC1-099_GEN
Solar/Wind Harmer
0.78
3145933PARMELE
Solar/Wind Harmer
0.15
315722AD1-056 GEN
Solar/Wind Harmer
5.099
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
964241AG1-285 GEN
Solar/Wind Harmer
9.742
970257AG2-171 GEN
Solar/Wind Harmer
4.66
971775AH1-396 GEN
Solar/Wind Harmer
0.233
959311AF2-222 GEN
Solar/Wind Harmer
12.935
3150351NORNECKC2
Adder
1.474
3144293JTRSVLE
Adder
0.346
3147133PAMPLIN
Solar/Wind Harmer
0.454
942461AE2-259 GEN
Solar/Wind Harmer
0
3146233WITAKRS
Solar/Wind Harmer
0.721
3146233WITAKRS
Solar/Wind Harmer
0.098
3146073TAR RVR
Solar/Wind Harmer
0.143
3146083TARBORO
Solar/Wind Harmer
0.143
3138543CONSLDL
Solar/Wind Harmer
0.095
3146926FARMVIL
Solar/Wind Harmer
0.086
961601AG1-000A GEN
Solar/Wind Harmer
10.047
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.282
971781AH1-399 GEN
Solar/Wind Harmer
0.18
3150401LDYSMT4
Adder
18.322
3150371LDYSMT1
Adder
17.704
3146776BUCKING
Solar/Wind Harmer
0.049
316223AC1-118
Solar/Wind Harmer
0.092
3141906WESTMOR
Solar/Wind Harmer
0.052
972003AH1-546 GEN
Solar/Wind Harmer
4.48
971683AH1-343 GEN
Solar/Wind Harmer
4.474
316222AC1-221 GEN
Solar/Wind Harmer
0.498
316283AC2-100 C
Solar/Wind Harmer
0.235
970221AG2-151 GEN
Solar/Wind Harmer
6.378
316450AC1-158 RIC
Solar/Wind Helper
1.435
316006AB2-029 C
Solar/Wind Helper
0.113
3152251N ANNA1
50/50
17.37
970119AG2-088 GEN
50/50
27.228
3150851SPRUNCC
50/50
0.897
315243AE2-183_GT3
50/50
2.994
3151051BRUNSWICKS1
50/50
4.91
3151021BRUNSWICKG1
50/50
2.365
971451AH1-221 GEN
50/50
7.182
3150981CHESPKA
50/50
2.369
3147666LOUISA
Solar/Wind Harmer
0.88
316192AB2-158 GEN
Solar/Wind Harmer
1.202
3143226MDLTHAN
Solar/Wind Harmer
0.204
3143526WINTERP
Solar/Wind Harmer
1.011
940641AE2-051 GEN
Solar/Wind Harmer
15.286
939411AE1-173 GEN
Solar/Wind Harmer
80.194
941031AE2-094 GEN
Solar/Wind Harmer
34.394
315773AC2-141 GEN
Solar/Wind Harmer
6.589
944591AF1-124 GEN
Solar/Wind Harmer
40.546
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.032
316381AD1-082 GEN
Solar/Wind Harmer
0.181
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3142543TWELFTH
Solar/Wind Harmer
0.017
3145336SMITFLD
Solar/Wind Harmer
0.71
3146456SLIGO L269
Solar/Wind Harmer
0.177
319010AE1-072 C
Solar/Wind Harmer
0.883
3151171GRAVELC
Adder
1.88
316072AD1-144
Solar/Wind Harmer
0.063
961611AG1-000B GEN
Solar/Wind Harmer
9.261
971069AG2-661 GEN
Solar/Wind Harmer
3.136
316132AB2-190 GEN1
Solar/Wind Harmer
0.94
316093AE2-104_GEN
Solar/Wind Harmer
2.962
3143096IRON208
Adder
0.736
3143336POWHATN
Solar/Wind Harmer
3.091
3138126ROCKLANDING
Solar/Wind Harmer
0.08
3146516WINFALL
Solar/Wind Harmer
0.562
3146516WINFALL
Solar/Wind Harmer
0.173
944631AF1-128 GEN
Adder
82.709
970919AG2-571 GEN
Solar/Wind Harmer
6.149
971317AH1-138 GEN
Solar/Wind Harmer
1.283
970087AG2-069 GEN
Solar/Wind Harmer
13.655
3130156CHOWAN
Solar/Wind Harmer
0.169
315975AC1-164 GENB
Solar/Wind Harmer
0.052
3142416OLDCHRC
Solar/Wind Harmer
0.436
3142416OLDCHRC
Solar/Wind Harmer
0.167
3142433PROV 92
Solar/Wind Harmer
0.668
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
0.709
3145663CRESWEL
Solar/Wind Harmer
0.465
971163AH1-040 GEN
Solar/Wind Harmer
13.3
316023GEN1_S
Solar/Wind Harmer
0.366
957481AF2-042 GEN
Solar/Wind Harmer
43.899
315737AD1-076 GEN
Solar/Wind Harmer
2.095
971777AH1-397 GEN
Solar/Wind Harmer
0.431
3141766HARMONY
Solar/Wind Harmer
0.033
3146206CASHIE
Solar/Wind Harmer
0.162
971547AH1-271 GEN
Solar/Wind Harmer
3.454
3145893MURPHYS
Solar/Wind Harmer
0.647
3145893MURPHYS
Solar/Wind Harmer
0.72
315693AD1-088 GEN
Solar/Wind Harmer
7.732
960081AF2-299 GEN
Solar/Wind Harmer
1.543
3146173TUNIS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.72
3138133OCRAN
Solar/Wind Harmer
0.095
315607AA1-063A GEN
Solar/Wind Harmer
0.32
3145683EARLEYS
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.158
3147043LAWRENC
Adder
1.415
3145963POPLR C
Solar/Wind Harmer
0.156
3145823KELFORD
Solar/Wind Harmer
0.156
3145783HORNRTN
Solar/Wind Harmer
0.155
3145796HORNRTN
Solar/Wind Harmer
0.512
3145796HORNRTN
Solar/Wind Harmer
0.155
962861AG1-135 GEN
Solar/Wind Harmer
4.834
316129AC1-054 GEN
Solar/Wind Harmer
0.562
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.972
3146293MARTNCO
Solar/Wind Harmer
0.139
971065AG2-659 GEN
Solar/Wind Harmer
6.402
3141726DUNNSVL
Solar/Wind Harmer
0.59
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
966881AG1-559 GEN
Solar/Wind Harmer
0.17
316131AB2-060 GEN
Solar/Wind Harmer
0.455
315785AD2-033 C
Solar/Wind Harmer
1.179
316034AC1-036 C
Solar/Wind Harmer
0.01
970937AG2-583 GEN
Solar/Wind Harmer
8.926
3150351NORNECKC2
Adder
1.45
316494AC1-189 GEN
Solar/Wind Harmer
0.491
970685AG2-442 GEN
Solar/Wind Harmer
10.835
971563AH1-280 GEN
Solar/Wind Harmer
1.546
3144293JTRSVLE
Adder
0.346
3144293JTRSVLE
Adder
0.273
3146233WITAKRS
Solar/Wind Harmer
0.572
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.143
3145493TOT1
Solar/Wind Harmer
0.638
3146926FARMVIL
Solar/Wind Harmer
0.086
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.502
3142053HEARTS
Solar/Wind Harmer
0.249
970401AG2-262 GEN
Solar/Wind Harmer
0.816
316337AD2-073 GEN
Solar/Wind Harmer
0.119
972197AH1-683 GEN
Adder
2.861
972219AH1-694 GEN
Adder
2.06
3146776BUCKING
Solar/Wind Harmer
0.055
971377AH1-170 GEN
Solar/Wind Harmer
1.276
3147623JAMES R
Solar/Wind Harmer
0.277
972135AH1-637 GEN
Solar/Wind Harmer
0.996
316447AC1-158 HLD
Solar/Wind Helper
11.843
316044AC1-158 PL1
Solar/Wind Helper
5.382
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.005
TVALTFEXP_TVA->PJM
CLTF
3.158
CPLELTFEXP_CPLE->PJM
CLTF
9.197
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.862
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.772
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.7
MECLTFEXP_MEC->PJM
CLTF
2.734
SIGELTFEXP_SIGE->PJM
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
2.436
LGEELTFEXP_LGEE->PJM
CLTF
0.991
WECLTFEXP_WEC->PJM
CLTF
0.477

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.46 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4194.66
MW Contribution:
5.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.724
971285AH1-108 GEN
50/50
1.5
315244AE2-183_ST
50/50
5.325
963041AG1-153 GEN
50/50
4.905
316233AE1-074 FULL
Solar/Wind Harmer
0.603
971281AH1-106 GEN
Solar/Wind Harmer
3.641
971283AH1-107 GEN
Solar/Wind Harmer
3.641
970533AG2-339 GEN
Solar/Wind Harmer
14.434
970673AG2-436 GEN
Solar/Wind Harmer
46.475
3143316POE
Solar/Wind Harmer
-0.082
3147346CASHSCORNER
Solar/Wind Harmer
0.322
971967AH1-528 GEN
Solar/Wind Harmer
39.026
316258AE1-075 C
Solar/Wind Harmer
0.5
316405AF2-144 C
Solar/Wind Harmer
0.527
315839AE2-212 C
Solar/Wind Harmer
0.62
3151081ELIZAR1
Adder
16.755
3151091ELIZAR2
Adder
16.464
316316AC1-027 C
Solar/Wind Harmer
0.628
970657AG2-426 GEN
Solar/Wind Harmer
1.29
315814AE2-033 C
Solar/Wind Harmer
19.026
316018AA1-139 ULT2
Solar/Wind Harmer
1.742
957871AF2-081 GEN
Solar/Wind Harmer
10.193
316236AE1-162_GEN
Solar/Wind Harmer
0.613
971445AH1-216 GEN
Solar/Wind Harmer
12.601
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.859
316311AC2-079 GEN
Solar/Wind Harmer
10.249
3151201GRAVEL4
Adder
13.134
3151221GRAVEL6
Adder
13.119
3151191GRAVEL3
Adder
12.968
3151211GRAVEL5
Adder
12.968
315697AD1-025 GEN
Solar/Wind Harmer
4.086
313526AB2-022
Solar/Wind Harmer
0.543
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146396TANGLEW
Solar/Wind Harmer
0.37
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
316382AG1-145 C
Solar/Wind Harmer
0.592
316159AE1-175 C
Solar/Wind Harmer
0.527
970085AG2-068 GEN
Solar/Wind Harmer
12.291
970581AG2-369 GEN
Solar/Wind Harmer
10.57
315800Z1-036_GEN1
Solar/Wind Harmer
4.834
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
957831AF2-077 GEN
Solar/Wind Harmer
0.579
3138283WHITEMARSH
Solar/Wind Harmer
0.03
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
3143873LANEXA
Solar/Wind Harmer
-0.011
315732AD1-074 GEN1
Solar/Wind Harmer
3.794
315733AD1-074 GEN2
Solar/Wind Harmer
3.794
316318V4-068
Solar/Wind Harmer
0.465
3145893MURPHYS
Solar/Wind Harmer
-0.05
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
970601AG2-382 GEN
Solar/Wind Harmer
8.158
316059AD1-063 C
Solar/Wind Harmer
0.42
946281AF1-292 GEN
Solar/Wind Harmer
0.416
957601AF2-054 GEN
Solar/Wind Harmer
0.555
3141873WAN 176
Solar/Wind Harmer
-0.004
316463AE2-346 GEN
Solar/Wind Harmer
0.297
3145513AHOSKIE
Solar/Wind Harmer
0.161
3151731LOISA B
50/50
13.488
315242AE2-183_GT2
50/50
3.066
315241AE2-183_GT1
50/50
3.058
972185AH1-677 GEN
50/50
11.084
3151041BRUNSWICKG3
50/50
2.423
972187AH1-678 GEN
50/50
5.559
971223AH1-071 GEN
Solar/Wind Harmer
2.942
3143526WINTERP
Solar/Wind Harmer
-0.116
316294AC1-161 GEN
Solar/Wind Harmer
6.697
316313AB2-026
Solar/Wind Harmer
0.555
3150991CHESPKB
Adder
1.913
3150991CHESPKB
Adder
1.867
3144356SAPONY
Solar/Wind Harmer
0.715
316315AB2-025 C
Solar/Wind Harmer
0.552
316185AD1-033 GEN
Solar/Wind Harmer
2.158
316083AB2-161 GEN
Solar/Wind Harmer
3.322
316240AF1-291 C
Solar/Wind Harmer
0.616
3145506HICKORY
Solar/Wind Harmer
-0.081
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
944641AF1-129 GEN
Adder
86.641
316339AD2-160 GEN
Solar/Wind Harmer
1.372
316388AE2-253 GEN
Solar/Wind Harmer
1.372
970933AG2-581 GEN
Solar/Wind Harmer
19.098
3137176SLIGO L2192
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
2.403
3130086AYDLETT
Solar/Wind Harmer
-0.081
316349AD2-085 GEN
Solar/Wind Harmer
1.804
316033AB2-134 GEN
Solar/Wind Harmer
6.519
315835AF2-110_GEN
Solar/Wind Harmer
2.528
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.621
316433W1029_GEN2
Solar/Wind Harmer
3.621
316435W1029_GEN3
Solar/Wind Harmer
3.621
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
12.414
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.576
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.625
3150701DARBY 4
Adder
12.596
3150681DARBY 2
Adder
12.581
3150671DARBY 1
Adder
12.567
315742AE1-103 GEN
Solar/Wind Harmer
4.656
3146376EDENTON
Solar/Wind Harmer
0.578
3146376EDENTON
Solar/Wind Harmer
0.578
3142296MT RD221
Adder
0.547
315976AC1-164 GENA
Solar/Wind Harmer
4.384
316169AC1-164_GENC
Solar/Wind Harmer
3.788
316312AB1-027
Solar/Wind Harmer
0.646
315614AA2-178 GEN
Solar/Wind Harmer
2.058
970099AG2-077 GEN
Solar/Wind Harmer
23.889
316365GEN2_N
Solar/Wind Harmer
1.277
316065AD1-022 GEN
Solar/Wind Harmer
9.351
316441AF1-014 GEN
Solar/Wind Harmer
1.26
3145893MURPHYS
Solar/Wind Harmer
0.521
3145893MURPHYS
Solar/Wind Harmer
-0.034
315666AE1-190 GEN
Solar/Wind Harmer
0.56
316156AD2-030 GEN
Solar/Wind Harmer
0.495
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
966871AG1-558 GEN
Solar/Wind Harmer
0.556
966871AG1-558 GEN
Solar/Wind Harmer
0.19
316140AB2-099
Solar/Wind Harmer
0.124
313506AB2-031 GEN
Solar/Wind Harmer
1.47
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
962571AG1-106 GEN
Solar/Wind Harmer
2.614
972189AH1-679 GEN
Adder
2.71
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
0.15
970301AG2-198 GEN
Solar/Wind Harmer
8.992
3145783HORNRTN
Solar/Wind Harmer
2.131
3145783HORNRTN
Solar/Wind Harmer
1.705
3145783HORNRTN
Solar/Wind Harmer
0.533
3145783HORNRTN
Solar/Wind Harmer
0.213
3145796HORNRTN
Solar/Wind Harmer
-0.053
966001AG1-469 GEN
Solar/Wind Harmer
0.337
316487AF1-042 GEN
Solar/Wind Harmer
2.305
3145933PARMELE
Solar/Wind Harmer
-0.034
3145933PARMELE
Solar/Wind Harmer
-0.017
315687AD1-152 GEN
Solar/Wind Harmer
2.082
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.698
3144293JTRSVLE
Adder
0.367
970323AG2-213 GEN
Solar/Wind Harmer
8.61
313527AB2-043 GEN
Solar/Wind Harmer
2.787
316237AB2-079_GEN
Solar/Wind Harmer
0.515
315724AD1-057 GEN
Solar/Wind Harmer
3.336
316005AA1-067
Solar/Wind Harmer
0.343
3146776BUCKING
Solar/Wind Harmer
-0.067
3146776BUCKING
Solar/Wind Harmer
-0.005
3150341NORNECKC1
Adder
1.548
3150341NORNECKC1
Adder
1.535
3145493TOT1
Solar/Wind Harmer
0.257
3145453TOT5
Solar/Wind Harmer
0.154
3145603CNETO
Solar/Wind Harmer
0.103
962561AG1-105 GEN
Solar/Wind Harmer
9.226
3150391LDYSMT3
Adder
18.328
972195AH1-682 GEN
Adder
2.409
316045AC1-158 PL2
Solar/Wind Helper
17.253
316450AC1-158 RIC
Solar/Wind Helper
1.438
316006AB2-029 C
Solar/Wind Helper
0.134
3152261N ANNA2
50/50
17.529
3151771S ANNAG1
50/50
0.706
3151801S ANNAS2
50/50
0.363
3151761LOISA E
50/50
27.498
3151721LOISA A
50/50
13.418
3150861SPRUNCD
50/50
0.917
3151031BRUNSWICKG2
50/50
2.423
3147666LOUISA
Solar/Wind Harmer
-0.07
944011AF1-069 GEN
Solar/Wind Harmer
12.61
3143336POWHATN
Solar/Wind Harmer
2.082
944581AF1-123 GEN
Solar/Wind Harmer
93.687
944601AF1-125 GEN
Solar/Wind Harmer
92.225
315813AE1-149 C
Solar/Wind Harmer
12.864
3151101ELIZAR3
Adder
16.969
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142956BIRDNECK
Solar/Wind Harmer
1.1
3144536CHRHLND
Solar/Wind Harmer
-0.003
970657AG2-426 GEN
Solar/Wind Harmer
4.134
316017AA1-139 ULT1
Solar/Wind Harmer
1.645
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.355
316305AF2-043 C
Solar/Wind Harmer
0.611
316246AF1-032 C
Solar/Wind Harmer
0.41
3151171GRAVELC
Adder
2.524
961611AG1-000B GEN
Solar/Wind Harmer
4.267
315778AD1-151 GEN
Solar/Wind Harmer
18.014
316458AB2-190 GEN2
Solar/Wind Harmer
2.041
970133AG2-095 GEN
Solar/Wind Harmer
2.274
316320Y1-086
Solar/Wind Harmer
1.181
3143096IRON208
Adder
0.752
3143096IRON208
Adder
0.737
316321Z2-027
Solar/Wind Harmer
0.541
3144216WINCHST
Adder
0.67
3146516WINFALL
Solar/Wind Harmer
-0.02
970917AG2-570 GEN
Solar/Wind Harmer
49.802
3150921YORKTN3
Adder
4.451
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.006
970293AG2-193 GEN
Solar/Wind Harmer
2.444
3146376EDENTON
Solar/Wind Harmer
-0.019
316075AC2-137 C
Solar/Wind Harmer
0.521
3142416OLDCHRC
Solar/Wind Harmer
1.939
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3156081AA2-088 GEN
Solar/Wind Harmer
6.124
315735AD1-075 GEN1
Solar/Wind Harmer
1.896
3141843SHACKLE
Adder
0.85
316203AE2-005 GEN
Solar/Wind Harmer
7.879
3145893MURPHYS
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
3141766HARMONY
Solar/Wind Harmer
1.658
966621AG1-532 GEN
Solar/Wind Harmer
0.377
3152251N ANNA1
50/50
17.52
970119AG2-088 GEN
50/50
27.933
3151791S ANNAG2
50/50
0.706
3151781S ANNAS1
50/50
0.363
3151741LOISA C
50/50
0.738
3151751LOISA D
50/50
13.488
3150851SPRUNCC
50/50
0.917
315243AE2-183_GT3
50/50
3.066
3151051BRUNSWICKS1
50/50
5.03
3151021BRUNSWICKG1
50/50
2.423
971451AH1-221 GEN
50/50
7.358
3147666LOUISA
Solar/Wind Harmer
-0.121
316192AB2-158 GEN
Solar/Wind Harmer
3.56
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.116
940641AE2-051 GEN
Solar/Wind Harmer
20.562
939411AE1-173 GEN
Solar/Wind Harmer
107.874
315683AE1-153 C
Solar/Wind Harmer
20.08
941031AE2-094 GEN
Solar/Wind Harmer
40.246
315773AC2-141 GEN
Solar/Wind Harmer
8.665
3143336POWHATN
Solar/Wind Harmer
2.449
944591AF1-124 GEN
Solar/Wind Harmer
94.024
316375AC2-012 GEN
Solar/Wind Harmer
7.097
316036AC1-147 C
Solar/Wind Harmer
0.552
3150981CHESPKA
Adder
2.28
316381AD1-082 GEN
Solar/Wind Harmer
1.873
315671AE2-027_GEN
Solar/Wind Harmer
3.691
3142543TWELFTH
Solar/Wind Harmer
-0.002
3145336SMITFLD
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
-0.02
319010AE1-072 C
Solar/Wind Harmer
4.105
316072AD1-144
Solar/Wind Harmer
0.409
3151171GRAVELC
Adder
1.919
961611AG1-000B GEN
Solar/Wind Harmer
10
316369SG1_INVT
Solar/Wind Harmer
3.61
971069AG2-661 GEN
Solar/Wind Harmer
3.202
316132AB2-190 GEN1
Solar/Wind Harmer
2.041
316093AE2-104_GEN
Solar/Wind Harmer
5.88
961941AG1-037 GEN
Solar/Wind Harmer
0.138
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316486AD2-202 GEN
Solar/Wind Harmer
0.465
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3143096IRON208
Adder
0.752
3146516WINFALL
Solar/Wind Harmer
-0.064
3146516WINFALL
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.061
970919AG2-571 GEN
Solar/Wind Harmer
6.304
944631AF1-128 GEN
Adder
84.423
971317AH1-138 GEN
Solar/Wind Harmer
2.462
970087AG2-069 GEN
Solar/Wind Harmer
18.436
315611Z1-036_GEN2
Solar/Wind Harmer
4.834
3130156CHOWAN
Solar/Wind Harmer
-0.019
315975AC1-164 GENB
Solar/Wind Harmer
0.13
3141873WAN 176
Solar/Wind Harmer
2.204
3146173TUNIS
Solar/Wind Harmer
-0.018
316473AC1-191 GEN
Solar/Wind Harmer
1.99
316478AD1-087 GEN
Solar/Wind Harmer
1.588
316181AB2-040 GEN
Solar/Wind Harmer
2.554
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.005
3137643SOCKMAN
Solar/Wind Harmer
-0.072
315652AC1-086 GEN
Solar/Wind Harmer
20.457
316426AA2-053 GEN
Solar/Wind Harmer
1.825
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
2.752
3146033SCOT NK
Solar/Wind Harmer
-0.071
970831AG2-522 GEN
Solar/Wind Harmer
8.781
316210AC1-098 GEN
Solar/Wind Harmer
2.737
316274AC1-208 GEN
Solar/Wind Harmer
1.87
946301AF1-294 GEN
Solar/Wind Harmer
4.425
961791AG1-021 GEN
Solar/Wind Harmer
2.159
970683AG2-441 GEN
Solar/Wind Harmer
12.18
970681AG2-440 GEN
Solar/Wind Harmer
8.084
3144303KENBRDG
Solar/Wind Harmer
-0.014
316238AB2-078_GEN
Solar/Wind Harmer
0.515
316239AB2-077_GEN
Solar/Wind Harmer
0.515
3145746EVERETS
Solar/Wind Harmer
-0.067
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
971845AH1-439 GEN
Solar/Wind Harmer
8.995
316327AA2-057 GEN
Solar/Wind Harmer
1.703
316322AB2-045
Solar/Wind Harmer
0.567
957861AF2-080 GEN
Solar/Wind Harmer
7.344
3141813NORNECK
Solar/Wind Harmer
-0.017
3145573BETHELC
Solar/Wind Harmer
-0.017
3145573BETHELC
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
6.192
3150411LDYSMT5
Adder
18.419
3150381LDYSMT2
Adder
17.628
972213AH1-691 GEN
Adder
2.982
972215AH1-692 GEN
Adder
2.982
316164AC1-076 GEN
Solar/Wind Helper
1.521
3146263WOODLND
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316011AB1-132 GEN
Solar/Wind Harmer
3.798
3147043LAWRENC
Solar/Wind Harmer
-0.011
316190AA2-174 GEN
Solar/Wind Harmer
0.222
316317KELFORD C
Solar/Wind Harmer
0.834
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.018
316484AD2-074 GEN
Solar/Wind Harmer
4.405
961951AG1-038 GEN
Solar/Wind Harmer
2.305
316212AC1-099_GEN
Solar/Wind Harmer
1.521
3146926FARMVIL
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.017
942461AE2-259 GEN
Solar/Wind Harmer
2.606
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3144293JTRSVLE
Adder
0.367
959311AF2-222 GEN
Solar/Wind Harmer
17.982
970257AG2-171 GEN
Solar/Wind Harmer
6.458
971775AH1-396 GEN
Solar/Wind Harmer
1.215
964241AG1-285 GEN
Solar/Wind Harmer
13.426
315722AD1-056 GEN
Solar/Wind Harmer
6.066
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
966881AG1-559 GEN
Solar/Wind Harmer
0.502
316420AA1-050 GEN
Solar/Wind Harmer
1.9
3146233WITAKRS
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
-0.011
316077AC2-138 C
Solar/Wind Harmer
0.349
3150351NORNECKC2
Adder
1.498
3138543CONSLDL
Solar/Wind Harmer
-0.011
3146073TAR RVR
Solar/Wind Harmer
-0.017
3146083TARBORO
Solar/Wind Harmer
-0.017
3150401LDYSMT4
Adder
18.362
3150371LDYSMT1
Adder
17.743
972003AH1-546 GEN
Solar/Wind Harmer
5.196
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142433PROV 92
Solar/Wind Harmer
-0.076
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
315816AE2-034 GEN
Solar/Wind Harmer
1.544
3145663CRESWEL
Solar/Wind Harmer
-0.053
971163AH1-040 GEN
Solar/Wind Harmer
17.933
957481AF2-042 GEN
Solar/Wind Harmer
59.722
316023GEN1_S
Solar/Wind Harmer
1.277
315737AD1-076 GEN
Solar/Wind Harmer
3.566
315693AD1-088 GEN
Solar/Wind Harmer
9.398
971777AH1-397 GEN
Solar/Wind Harmer
2.181
316314AB2-024 C
Solar/Wind Harmer
1.595
3145893MURPHYS
Solar/Wind Harmer
-0.074
3145893MURPHYS
Solar/Wind Harmer
0.554
3146206CASHIE
Solar/Wind Harmer
-0.019
971547AH1-271 GEN
Solar/Wind Harmer
4.662
315662AE1-191 GEN
Solar/Wind Harmer
2.241
316280AD1-041 GEN
Solar/Wind Harmer
1.401
3141766HARMONY
Solar/Wind Harmer
-0.004
960081AF2-299 GEN
Solar/Wind Harmer
2.09
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.477
316087AB2-174 GEN
Solar/Wind Harmer
2.622
315607AA1-063A GEN
Solar/Wind Harmer
1.85
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.011
3147043LAWRENC
Adder
1.461
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
970937AG2-583 GEN
Solar/Wind Harmer
12.89
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.018
316129AC1-054 GEN
Solar/Wind Harmer
1.53
971065AG2-659 GEN
Solar/Wind Harmer
8.722
3146926FARMVIL
Solar/Wind Harmer
-0.01
3146293MARTNCO
Solar/Wind Harmer
0.107
971563AH1-280 GEN
Solar/Wind Harmer
2.159
3144293JTRSVLE
Adder
0.367
3144293JTRSVLE
Adder
0.29
962861AG1-135 GEN
Solar/Wind Harmer
6.474
970685AG2-442 GEN
Solar/Wind Harmer
15.1
316034AC1-036 C
Solar/Wind Harmer
0.318
315785AD2-033 C
Solar/Wind Harmer
3.894
316404AE1-155 C
Solar/Wind Harmer
3.279
958261AF2-120 GEN
Solar/Wind Harmer
6.657
316131AB2-060 GEN
Solar/Wind Harmer
1.847
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.007
964211AG1-282 GEN
Solar/Wind Harmer
0.507
3141726DUNNSVL
Solar/Wind Harmer
-0.067
316494AC1-189 GEN
Solar/Wind Harmer
1.806
966881AG1-559 GEN
Solar/Wind Harmer
0.172
316319Z2-044 C
Solar/Wind Harmer
0.918
3146233WITAKRS
Solar/Wind Harmer
-0.066
3150351NORNECKC2
Adder
1.473
961671AG1-007 GEN
Solar/Wind Harmer
0.21
3146083TARBORO
Solar/Wind Harmer
-0.017
3145493TOT1
Solar/Wind Harmer
0.492
972197AH1-683 GEN
Adder
2.867
972219AH1-694 GEN
Adder
2.064
316447AC1-158 HLD
Solar/Wind Helper
11.864
316044AC1-158 PL1
Solar/Wind Helper
5.392
LAGNLTFEXP_LAGN->PJM
CLTF
6.601
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.818
TVALTFEXP_TVA->PJM
CLTF
3.342
CPLELTFEXP_CPLE->PJM
CLTF
9.523
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.927
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.297
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.352
MECLTFEXP_MEC->PJM
CLTF
2.948
SIGELTFEXP_SIGE->PJM
CLTF
0.09
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.077
WECLTFEXP_WEC->PJM
CLTF
0.521

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.14 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3165.31
MW Contribution:
5.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3140676OCCOQUN
50/50
0.023
3141316ARNOLDS
50/50
0.022
970053AG2-049 GEN
50/50
2.78
3150411LDYSMT5
50/50
22.212
3150381LDYSMT2
50/50
21.258
972213AH1-691 GEN
50/50
3.596
972215AH1-692 GEN
50/50
3.596
971531AH1-263 GEN
50/50
25.524
3141426STAFORD
Solar/Wind Harmer
-0.004
944491AF1-114 GEN
Solar/Wind Harmer
5.021
316468AD1-105 GEN
Solar/Wind Harmer
1.878
3141813NORNECK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
3138133OCRAN
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.015
957601AF2-054 GEN
Solar/Wind Harmer
0.461
316059AD1-063 C
Solar/Wind Harmer
0.347
3141873WAN 176
Solar/Wind Harmer
-0.003
3143873LANEXA
Solar/Wind Harmer
-0.009
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
957831AF2-077 GEN
Solar/Wind Harmer
0.455
3138283WHITEMARSH
Solar/Wind Harmer
0.023
971285AH1-108 GEN
Adder
1.013
316382AG1-145 C
Solar/Wind Harmer
0.452
316159AE1-175 C
Solar/Wind Harmer
0.403
316233AE1-074 FULL
Solar/Wind Harmer
0.405
971281AH1-106 GEN
Solar/Wind Harmer
2.444
971283AH1-107 GEN
Solar/Wind Harmer
2.444
316164AC1-076 GEN
Solar/Wind Harmer
1.258
315697AD1-025 GEN
Solar/Wind Harmer
2.998
315839AE2-212 C
Solar/Wind Harmer
0.446
3151201GRAVEL4
Adder
9.562
3151221GRAVEL6
Adder
9.551
3151191GRAVEL3
Adder
9.441
3151211GRAVEL5
Adder
9.441
971445AH1-216 GEN
Solar/Wind Harmer
9.094
316236AE1-162_GEN
Solar/Wind Harmer
0.442
3143316POE
Solar/Wind Harmer
-0.058
970657AG2-426 GEN
Solar/Wind Harmer
0.92
3151081ELIZAR1
Adder
11.889
3151091ELIZAR2
Adder
11.683
316316AC1-027 C
Solar/Wind Harmer
0.446
315833AF1-017_GEN
Solar/Wind Harmer
2.753
316311AC2-079 GEN
Solar/Wind Harmer
7.311
316018AA1-139 ULT2
Solar/Wind Harmer
1.238
957871AF2-081 GEN
Solar/Wind Harmer
7.242
3146406KITTY HAWK
Solar/Wind Harmer
0.012
315651AD1-115 GEN
Solar/Wind Harmer
6.333
313526AB2-022
Solar/Wind Harmer
0.387
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
3146396TANGLEW
Solar/Wind Harmer
0.264
316258AE1-075 C
Solar/Wind Harmer
0.343
316405AF2-144 C
Solar/Wind Harmer
0.362
315814AE2-033 C
Solar/Wind Harmer
13.181
315800Z1-036_GEN1
Solar/Wind Harmer
3.483
970533AG2-339 GEN
Solar/Wind Harmer
9.467
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
970673AG2-436 GEN
Solar/Wind Harmer
30.638
3147346CASHSCORNER
Solar/Wind Harmer
0.215
971967AH1-528 GEN
Solar/Wind Harmer
26.063
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315732AD1-074 GEN1
Solar/Wind Harmer
2.771
315733AD1-074 GEN2
Solar/Wind Harmer
2.771
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
5.972
316318V4-068
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
316463AE2-346 GEN
Solar/Wind Harmer
0.218
3145513AHOSKIE
Solar/Wind Harmer
0.118
961941AG1-037 GEN
Solar/Wind Harmer
0.102
3145513AHOSKIE
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.013
3146043SEABORD
Solar/Wind Harmer
-0.013
970085AG2-068 GEN
Solar/Wind Harmer
8.424
970581AG2-369 GEN
Solar/Wind Harmer
7.245
946281AF1-292 GEN
Solar/Wind Harmer
0.302
3137643SOCKMAN
Solar/Wind Harmer
-0.053
315652AC1-086 GEN
Solar/Wind Harmer
15.006
316426AA2-053 GEN
Solar/Wind Harmer
1.343
316174AB2-169 GEN
Solar/Wind Harmer
2.049
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.005
3146033SCOT NK
Solar/Wind Harmer
-0.053
316486AD2-202 GEN
Solar/Wind Harmer
0.332
971845AH1-439 GEN
Solar/Wind Harmer
6.949
316210AC1-098 GEN
Solar/Wind Harmer
2.048
316322AB2-045
Solar/Wind Harmer
0.439
970831AG2-522 GEN
Solar/Wind Harmer
6.516
316274AC1-208 GEN
Solar/Wind Harmer
1.402
972205AH1-687 GEN
Adder
4.951
946301AF1-294 GEN
Solar/Wind Harmer
3.327
961791AG1-021 GEN
Solar/Wind Harmer
1.623
970683AG2-441 GEN
Solar/Wind Harmer
9.15
970681AG2-440 GEN
Solar/Wind Harmer
6.073
3144303KENBRDG
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.051
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
226929AD2-058 GEN
Solar/Wind Helper
0.404
233915AB1-141 GEN
Solar/Wind Helper
0.494
233940AF2-379 C
Solar/Wind Helper
0.06
233901CHERRYDALE C
Solar/Wind Helper
0.227
232432Z2-076 GEN
Solar/Wind Helper
0.065
3150101POSSM6S
50/50
2.207
3150081POSSM6A
50/50
1.449
3150151POSSMC1
50/50
1.949
3150151POSSMC1
50/50
1.949
3150331BIRCHWDA
50/50
29.448
3150021OMF B
50/50
0.31
3150401LDYSMT4
50/50
22.143
3150371LDYSMT1
50/50
21.396
3150501FRIVERG
50/50
1.196
966881AG1-559 GEN
Solar/Wind Harmer
0.505
316223AC1-118
Solar/Wind Harmer
0.444
3141906WESTMOR
Solar/Wind Harmer
-0.007
971781AH1-399 GEN
Solar/Wind Harmer
1.013
316077AC2-138 C
Solar/Wind Harmer
0.336
3150351NORNECKC2
Adder
1.441
316484AD2-074 GEN
Solar/Wind Harmer
3.957
961951AG1-038 GEN
Solar/Wind Harmer
2.07
316473AC1-191 GEN
Solar/Wind Harmer
1.685
3141873WAN 176
Solar/Wind Harmer
1.828
3142416OLDCHRC
Solar/Wind Harmer
1.554
3141766HARMONY
Solar/Wind Harmer
1.371
316203AE2-005 GEN
Solar/Wind Harmer
6.488
3141843SHACKLE
Adder
0.7
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
316075AC2-137 C
Solar/Wind Harmer
0.412
970293AG2-193 GEN
Solar/Wind Harmer
1.912
3142946ENON
Solar/Wind Harmer
-0.005
3143096IRON208
Adder
0.566
3143096IRON208
Adder
0.555
3150861SPRUNCD
Adder
0.619
970133AG2-095 GEN
Solar/Wind Harmer
1.685
316458AB2-190 GEN2
Solar/Wind Harmer
1.504
3150921YORKTN3
Adder
3.335
3144216WINCHST
Adder
0.5
315778AD1-151 GEN
Solar/Wind Harmer
13.243
3147666LOUISA
Solar/Wind Harmer
-0.034
961611AG1-000B GEN
Solar/Wind Harmer
3.116
3151171GRAVELC
Adder
1.838
3145336SMITFLD
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
9.176
3144536CHRHLND
Solar/Wind Harmer
-0.002
970657AG2-426 GEN
Solar/Wind Harmer
2.949
3151101ELIZAR3
Adder
12.041
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
66.227
944601AF1-125 GEN
Solar/Wind Harmer
65.193
3142956BIRDNECK
Solar/Wind Harmer
0.781
316017AA1-139 ULT1
Solar/Wind Harmer
1.169
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.674
316305AF2-043 C
Solar/Wind Harmer
0.435
316246AF1-032 C
Solar/Wind Harmer
0.292
316320Y1-086
Solar/Wind Harmer
0.842
316321Z2-027
Solar/Wind Harmer
0.386
3132273ORANGE
Solar/Wind Harmer
-0.003
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3145273HOLLAND
Solar/Wind Harmer
-0.011
3143336POWHATN
Solar/Wind Harmer
1.429
944011AF1-069 GEN
Solar/Wind Harmer
8.27
3151761LOISA E
Adder
16.567
3151721LOISA A
Adder
8.084
3146376EDENTON
Solar/Wind Harmer
-0.014
3150301M RUN C
Adder
16.761
3150291M RUN B
Adder
16.636
3150241REMNGT4
Adder
15.69
972199AH1-684 GEN
Adder
2.379
972217AH1-693 GEN
Adder
2.069
3156081AA2-088 GEN
Solar/Wind Harmer
4.454
315735AD1-075 GEN1
Solar/Wind Harmer
1.385
3146206CASHIE
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
-0.014
970917AG2-570 GEN
Solar/Wind Harmer
33.913
3146173TUNIS
Solar/Wind Harmer
-0.014
966621AG1-532 GEN
Solar/Wind Harmer
0.273
3141196NOKESVL
Solar/Wind Harmer
-0.054
3146263WOODLND
Solar/Wind Harmer
-0.013
316181AB2-040 GEN
Solar/Wind Harmer
1.864
3145963POPLR C
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316317KELFORD C
Solar/Wind Harmer
0.617
3145823KELFORD
Solar/Wind Harmer
-0.013
316011AB1-132 GEN
Solar/Wind Harmer
2.786
316190AA2-174 GEN
Solar/Wind Harmer
0.163
972223AH1-696 GEN
50/50
15.393
3150151POSSMC1
50/50
1.949
3141346CRANES
50/50
0.214
3150011OMF A
50/50
0.31
972197AH1-683 GEN
50/50
3.458
972219AH1-694 GEN
50/50
2.49
957971AF2-091 GEN
Solar/Wind Harmer
1.707
972135AH1-637 GEN
Solar/Wind Harmer
1.693
966881AG1-559 GEN
Solar/Wind Harmer
0.173
316337AD2-073 GEN
Solar/Wind Harmer
0.435
3150351NORNECKC2
Adder
1.418
964211AG1-282 GEN
Solar/Wind Harmer
0.478
3141726DUNNSVL
Solar/Wind Harmer
-0.063
316404AE1-155 C
Solar/Wind Harmer
3.018
958261AF2-120 GEN
Solar/Wind Harmer
6.126
962861AG1-135 GEN
Solar/Wind Harmer
5.92
3138133OCRAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
316314AB2-024 C
Solar/Wind Harmer
1.316
315662AE1-191 GEN
Solar/Wind Harmer
1.851
316280AD1-041 GEN
Solar/Wind Harmer
1.157
971777AH1-397 GEN
Solar/Wind Harmer
1.796
3142433PROV 92
Solar/Wind Harmer
-0.061
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
315975AC1-164 GENB
Solar/Wind Harmer
0.103
3143096IRON208
Adder
0.566
316447AC1-158 HLD
Solar/Wind Harmer
3.264
316044AC1-158 PL1
Solar/Wind Harmer
1.484
944631AF1-128 GEN
Adder
64.269
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.619
3143526WINTERP
Solar/Wind Harmer
-0.078
971317AH1-138 GEN
Solar/Wind Harmer
1.876
3143226MDLTHAN
Solar/Wind Harmer
-0.015
316132AB2-190 GEN1
Solar/Wind Harmer
1.504
3138126ROCKLANDING
Solar/Wind Harmer
0.046
315671AE2-027_GEN
Solar/Wind Harmer
2.688
971069AG2-661 GEN
Solar/Wind Harmer
2.354
316369SG1_INVT
Solar/Wind Harmer
2.649
3147666LOUISA
Solar/Wind Harmer
-0.059
961611AG1-000B GEN
Solar/Wind Harmer
7.302
316192AB2-158 GEN
Solar/Wind Harmer
1.754
3151171GRAVELC
Adder
1.397
3145336SMITFLD
Solar/Wind Harmer
-0.058
315773AC2-141 GEN
Solar/Wind Harmer
6.117
316381AD1-082 GEN
Solar/Wind Harmer
1.336
316375AC2-012 GEN
Solar/Wind Harmer
5.039
316036AC1-147 C
Solar/Wind Harmer
0.392
3150981CHESPKA
Adder
1.619
944591AF1-124 GEN
Solar/Wind Harmer
66.465
316072AD1-144
Solar/Wind Harmer
0.293
316254AC1-120 GEN1
Solar/Wind Harmer
5.447
316170AC1-121 GEN2
Solar/Wind Harmer
1.816
3146456SLIGO L269
Solar/Wind Harmer
-0.014
319010AE1-072 C
Solar/Wind Harmer
2.919
316093AE2-104_GEN
Solar/Wind Harmer
4.194
939411AE1-173 GEN
Solar/Wind Harmer
72.085
940641AE2-051 GEN
Solar/Wind Harmer
13.479
3146516WINFALL
Solar/Wind Harmer
-0.046
3146516WINFALL
Solar/Wind Harmer
-0.014
3143336POWHATN
Solar/Wind Harmer
1.681
315611Z1-036_GEN2
Solar/Wind Harmer
3.483
3147043LAWRENC
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.135
3146926FARMVIL
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
1.138
3146776BUCKING
Solar/Wind Harmer
-0.005
942461AE2-259 GEN
Solar/Wind Harmer
1.963
3145933PARMELE
Solar/Wind Harmer
-0.013
972255AH1-712 GEN
Adder
59.346
972003AH1-546 GEN
Solar/Wind Harmer
5.292
3147133PAMPLIN
Solar/Wind Harmer
-0.041
3144293JTRSVLE
Adder
0.276
959311AF2-222 GEN
Solar/Wind Harmer
13.501
970257AG2-171 GEN
Solar/Wind Harmer
4.847
971775AH1-396 GEN
Solar/Wind Harmer
0.912
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
227287AC2-120 GEN
Solar/Wind Helper
1.296
226910AB2-157 C
Solar/Wind Helper
0.05
208835TUHI V3-051
Solar/Wind Helper
0.028
233935AB2-179 C
Solar/Wind Helper
1.256
233933AB2-153 GEN
Solar/Wind Helper
0.228
232422X3-066 FULL
Solar/Wind Helper
0.112
233987AB2-037 GEN
Solar/Wind Helper
2.288
232417X3-008 C
Solar/Wind Helper
0.227
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.733
233997TMININ_4.2
Solar/Wind Helper
0.2
232406W1-004 FULL
Solar/Wind Helper
0.494
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.124
941031AE2-094 GEN
Solar/Wind Harmer
26.395
3151751LOISA D
Adder
8.126
3130156CHOWAN
Solar/Wind Harmer
-0.014
971685AH1-345 GEN
Solar/Wind Harmer
1.224
315683AE1-153 C
Solar/Wind Harmer
13.012
3150281M RUN A
Adder
16.771
315816AE2-034 GEN
Solar/Wind Harmer
1.121
3145663CRESWEL
Solar/Wind Harmer
-0.039
971163AH1-040 GEN
Solar/Wind Harmer
13.019
3150221REMNGT2
Adder
15.587
3150211REMNGT1
Adder
15.484
972201AH1-685 GEN
Adder
2.689
315737AD1-076 GEN
Solar/Wind Harmer
2.605
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.413
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
0.404
316023GEN1_S
Solar/Wind Harmer
0.916
970919AG2-571 GEN
Solar/Wind Harmer
4.293
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.819
3145683EARLEYS
Solar/Wind Harmer
-0.013
970087AG2-069 GEN
Solar/Wind Harmer
12.637
960081AF2-299 GEN
Solar/Wind Harmer
1.515
315607AA1-063A GEN
Solar/Wind Harmer
1.355
970937AG2-583 GEN
Solar/Wind Harmer
9.671
3146263WOODLND
Solar/Wind Harmer
-0.013
316087AB2-174 GEN
Solar/Wind Harmer
1.91
957481AF2-042 GEN
Solar/Wind Harmer
41.796
3145963POPLR C
Solar/Wind Harmer
-0.013
3145823KELFORD
Solar/Wind Harmer
-0.013
315693AD1-088 GEN
Solar/Wind Harmer
6.657
3147043LAWRENC
Adder
1.069
3145783HORNRTN
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.013
3146926FARMVIL
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.005
3146293MARTNCO
Solar/Wind Harmer
0.081
972277AH1-723 GEN
Adder
69.157
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971563AH1-280 GEN
Solar/Wind Harmer
1.623
3144293JTRSVLE
Adder
0.276
3144293JTRSVLE
Adder
0.218
970685AG2-442 GEN
Solar/Wind Harmer
11.348
971065AG2-659 GEN
Solar/Wind Harmer
6.485
316034AC1-036 C
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
208835TUHI V3-051
Solar/Wind Helper
0.028
233918AB1-142 GEN
Solar/Wind Helper
0.494
233944AB2-135 GEN
Solar/Wind Helper
0.579
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.2
233998TM1NIN_3.36
Solar/Wind Helper
0.2
232404W1-003 C
Solar/Wind Helper
0.494
232408W1-005 C
Solar/Wind Helper
0.494
315785AD2-033 C
Solar/Wind Harmer
1.614
3150091POSSM6B
50/50
1.449
3150071POSSM 5
50/50
89.066
3150181POSSMC2
50/50
1.965
3150181POSSMC2
50/50
1.949
3150181POSSMC2
50/50
1.949
957191AF2-013 GEN
50/50
14.107
3150391LDYSMT3
50/50
22.101
972195AH1-682 GEN
50/50
2.904
315673AE1-157 GEN
Solar/Wind Harmer
12.782
972189AH1-679 GEN
Adder
2.385
3150341NORNECKC1
Adder
1.489
3150341NORNECKC1
Adder
1.477
316487AF1-042 GEN
Solar/Wind Harmer
2.07
966871AG1-558 GEN
Solar/Wind Harmer
0.471
966871AG1-558 GEN
Solar/Wind Harmer
0.161
3142296MT RD221
Adder
0.438
316312AB1-027
Solar/Wind Harmer
0.518
316156AD2-030 GEN
Solar/Wind Harmer
0.41
315666AE1-190 GEN
Solar/Wind Harmer
0.463
316441AF1-014 GEN
Solar/Wind Harmer
1.037
3150691DARBY 3
Adder
9.796
3150701DARBY 4
Adder
9.773
3150681DARBY 2
Adder
9.762
3150671DARBY 1
Adder
9.75
3142366NRTHEST
Adder
0.445
315976AC1-164 GENA
Solar/Wind Harmer
3.472
316169AC1-164_GENC
Solar/Wind Harmer
3
3142946ENON
Solar/Wind Harmer
-0.002
316045AC1-158 PL2
Solar/Wind Harmer
4.749
316450AC1-158 RIC
Solar/Wind Harmer
0.396
3143526WINTERP
Solar/Wind Harmer
-0.078
944641AF1-129 GEN
Adder
63.441
971223AH1-071 GEN
Solar/Wind Harmer
1.867
316240AF1-291 C
Solar/Wind Harmer
0.449
316033AB2-134 GEN
Solar/Wind Harmer
4.783
316294AC1-161 GEN
Solar/Wind Harmer
4.728
316083AB2-161 GEN
Solar/Wind Harmer
2.37
3150991CHESPKB
Adder
1.358
3150991CHESPKB
Adder
1.326
316185AD1-033 GEN
Solar/Wind Harmer
1.53
3145506HICKORY
Solar/Wind Harmer
-0.058
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316349AD2-085 GEN
Solar/Wind Harmer
1.287
316339AD2-160 GEN
Solar/Wind Harmer
0.975
316388AE2-253 GEN
Solar/Wind Harmer
0.975
3137176SLIGO L2192
Solar/Wind Harmer
-0.057
3146456SLIGO L269
Solar/Wind Harmer
1.708
3130086AYDLETT
Solar/Wind Harmer
-0.058
315835AF2-110_GEN
Solar/Wind Harmer
1.803
3146386ELIZ CT
Solar/Wind Harmer
-0.014
316431W1029_GEN1
Solar/Wind Harmer
2.59
316433W1029_GEN2
Solar/Wind Harmer
2.59
316435W1029_GEN3
Solar/Wind Harmer
2.59
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3144356SAPONY
Solar/Wind Harmer
0.495
316315AB2-025 C
Solar/Wind Harmer
0.382
316313AB2-026
Solar/Wind Harmer
0.381
315742AE1-103 GEN
Solar/Wind Harmer
3.349
966001AG1-469 GEN
Solar/Wind Harmer
0.266
3151731LOISA B
Adder
8.126
3146376EDENTON
Solar/Wind Harmer
0.417
3146376EDENTON
Solar/Wind Harmer
0.417
316006AB2-029 C
Solar/Wind Harmer
0.802
316336AC2-165 C
Solar/Wind Harmer
8.722
972185AH1-677 GEN
Adder
6.942
315614AA2-178 GEN
Solar/Wind Harmer
1.494
972187AH1-678 GEN
Adder
3.503
970933AG2-581 GEN
Solar/Wind Harmer
12.891
316065AD1-022 GEN
Solar/Wind Harmer
6.84
3145893MURPHYS
Solar/Wind Harmer
0.38
3145893MURPHYS
Solar/Wind Harmer
-0.024
316365GEN2_N
Solar/Wind Harmer
0.916
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316140AB2-099
Solar/Wind Harmer
0.091
313506AB2-031 GEN
Solar/Wind Harmer
1.073
970099AG2-077 GEN
Solar/Wind Harmer
16.718
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
962571AG1-106 GEN
Solar/Wind Harmer
1.917
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
0.11
3145783HORNRTN
Solar/Wind Harmer
1.573
3145783HORNRTN
Solar/Wind Harmer
1.258
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
3145796HORNRTN
Solar/Wind Harmer
-0.039
970301AG2-198 GEN
Solar/Wind Harmer
6.602
3146776BUCKING
Solar/Wind Harmer
-0.052
3146776BUCKING
Solar/Wind Harmer
-0.004
3145933PARMELE
Solar/Wind Harmer
-0.026
3145933PARMELE
Solar/Wind Harmer
-0.013
972193AH1-681 GEN
Adder
2.652
3147133PAMPLIN
Solar/Wind Harmer
-0.013
3147133PAMPLIN
Solar/Wind Harmer
-0.01
958211AF2-115 GEN
Solar/Wind Harmer
2.029
3144293JTRSVLE
Adder
0.276
970323AG2-213 GEN
Solar/Wind Harmer
6.463
316005AA1-067
Solar/Wind Harmer
0.261
223401AF1-299 GEN
Solar/Wind Helper
0.71
223402AF1-300 C
Solar/Wind Helper
0.71
233982AB2-133 GEN
Solar/Wind Helper
0.353
233930AB2-032 GEN
Solar/Wind Helper
0.374
232436AB1-176 C
Solar/Wind Helper
0.044
232424Y1-079 C
Solar/Wind Helper
0.114
234036AF2-325 C
Solar/Wind Helper
0.041
233946AB2-136 GEN
Solar/Wind Helper
0.555
233994AC2-023 GEN
Solar/Wind Helper
0.937
232428Y3-058 C
Solar/Wind Helper
0.33
234015AF2-250 C
Solar/Wind Helper
0.037
232410W1-006 C
Solar/Wind Helper
0.494
233952AC2-187 GEN
Solar/Wind Helper
0.227
233954AC2-188 GEN
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
10.93
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.864
TVALTFEXP_TVA->PJM
CLTF
5.501
CPLELTFEXP_CPLE->PJM
CLTF
8.311
CBM West 2LTFEXP_CBM-W2->PJM
CBM
68.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.085
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.104
MECLTFEXP_MEC->PJM
CLTF
7.907
SIGELTFEXP_SIGE->PJM
CLTF
0.248
NYPJM->LTFIMP_NY
CLTF
3.83
LGEELTFEXP_LGEE->PJM
CLTF
3.215
WECLTFEXP_WEC->PJM
CLTF
1.726
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:168.62 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6643.56
MW Contribution:
9.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
30.366
3151771S ANNAG1
50/50
0.957
3151801S ANNAS2
50/50
0.492
3151031BRUNSWICKG2
50/50
3.469
3151761LOISA E
50/50
36.63
3151721LOISA A
50/50
17.874
3147666LOUISA
Solar/Wind Harmer
-0.109
944011AF1-069 GEN
Solar/Wind Harmer
18.084
3143336POWHATN
Solar/Wind Harmer
2.914
970917AG2-570 GEN
Solar/Wind Harmer
71.224
944581AF1-123 GEN
Solar/Wind Harmer
126.535
944601AF1-125 GEN
Solar/Wind Harmer
124.56
3151101ELIZAR3
Adder
22.845
3142956BIRDNECK
Solar/Wind Harmer
1.482
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
2.22
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.179
3144536CHRHLND
Solar/Wind Harmer
-0.004
316305AF2-043 C
Solar/Wind Harmer
0.824
316246AF1-032 C
Solar/Wind Harmer
0.553
315813AE1-149 C
Solar/Wind Harmer
17.066
970657AG2-426 GEN
Solar/Wind Harmer
5.513
316320Y1-086
Solar/Wind Harmer
1.596
3132273ORANGE
Solar/Wind Harmer
-0.005
3150861SPRUNCD
Adder
1.116
316321Z2-027
Solar/Wind Harmer
0.731
3145336SMITFLD
Solar/Wind Harmer
-0.011
3146516WINFALL
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3145273HOLLAND
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
3.309
3146376EDENTON
Solar/Wind Harmer
-0.026
961611AG1-000B GEN
Solar/Wind Harmer
5.568
315778AD1-151 GEN
Solar/Wind Harmer
23.257
3152251N ANNA1
50/50
30.35
970119AG2-088 GEN
50/50
39.43
3151791S ANNAG2
50/50
0.957
3151781S ANNAS1
50/50
0.492
315243AE2-183_GT3
50/50
4.392
3151051BRUNSWICKS1
50/50
7.202
3151021BRUNSWICKG1
50/50
3.469
971451AH1-221 GEN
50/50
10.535
3151741LOISA C
50/50
0.983
3151751LOISA D
50/50
17.967
316447AC1-158 HLD
Solar/Wind Harmer
18.659
316044AC1-158 PL1
Solar/Wind Harmer
8.483
3147666LOUISA
Solar/Wind Harmer
-0.189
316303AF2-085
50/50
5.257
315244AE2-183_ST
50/50
7.628
963041AG1-153 GEN
50/50
7.023
315779AE2-040
50/50
3.519
316164AC1-076 GEN
Solar/Wind Harmer
2.928
970533AG2-339 GEN
Solar/Wind Harmer
20.699
970673AG2-436 GEN
Solar/Wind Harmer
66.62
316233AE1-074 FULL
Solar/Wind Harmer
0.817
971281AH1-106 GEN
Solar/Wind Harmer
4.936
971283AH1-107 GEN
Solar/Wind Harmer
4.936
971967AH1-528 GEN
Solar/Wind Harmer
55.854
316258AE1-075 C
Solar/Wind Harmer
0.699
316405AF2-144 C
Solar/Wind Harmer
0.738
315814AE2-033 C
Solar/Wind Harmer
26.281
970085AG2-068 GEN
Solar/Wind Harmer
17.57
970581AG2-369 GEN
Solar/Wind Harmer
15.11
3143316POE
Solar/Wind Harmer
-0.11
3151081ELIZAR1
Adder
22.556
3151091ELIZAR2
Adder
22.164
316316AC1-027 C
Solar/Wind Harmer
0.846
316018AA1-139 ULT2
Solar/Wind Harmer
2.351
957871AF2-081 GEN
Solar/Wind Harmer
13.758
3146406KITTY HAWK
Solar/Wind Harmer
0.023
3147346CASHSCORNER
Solar/Wind Harmer
0.424
970657AG2-426 GEN
Solar/Wind Harmer
1.721
315833AF1-017_GEN
Solar/Wind Harmer
5.179
316311AC2-079 GEN
Solar/Wind Harmer
13.756
313526AB2-022
Solar/Wind Harmer
0.733
971285AH1-108 GEN
Adder
1.826
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146396TANGLEW
Solar/Wind Harmer
0.5
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
315839AE2-212 C
Solar/Wind Harmer
0.812
316236AE1-162_GEN
Solar/Wind Harmer
0.811
971445AH1-216 GEN
Solar/Wind Harmer
16.675
316192AB2-158 GEN
Solar/Wind Harmer
5.526
3143226MDLTHAN
Solar/Wind Harmer
-0.033
940641AE2-051 GEN
Solar/Wind Harmer
29.215
941031AE2-094 GEN
Solar/Wind Harmer
57.714
3143526WINTERP
Solar/Wind Harmer
-0.157
939411AE1-173 GEN
Solar/Wind Harmer
151.436
3143336POWHATN
Solar/Wind Harmer
3.428
970919AG2-571 GEN
Solar/Wind Harmer
9.016
970087AG2-069 GEN
Solar/Wind Harmer
26.355
315773AC2-141 GEN
Solar/Wind Harmer
11.691
944591AF1-124 GEN
Solar/Wind Harmer
126.991
316375AC2-012 GEN
Solar/Wind Harmer
9.55
316036AC1-147 C
Solar/Wind Harmer
0.743
3150981CHESPKA
Adder
3.069
3146456SLIGO L269
Solar/Wind Harmer
-0.027
319010AE1-072 C
Solar/Wind Harmer
5.542
316381AD1-082 GEN
Solar/Wind Harmer
2.496
316093AE2-104_GEN
Solar/Wind Harmer
7.926
3150851SPRUNCC
Adder
1.116
957481AF2-042 GEN
Solar/Wind Harmer
84.992
316072AD1-144
Solar/Wind Harmer
0.547
3145336SMITFLD
Solar/Wind Harmer
-0.107
3146516WINFALL
Solar/Wind Harmer
-0.087
3146516WINFALL
Solar/Wind Harmer
-0.027
315693AD1-088 GEN
Solar/Wind Harmer
13.337
3151171GRAVELC
Adder
2.517
315611Z1-036_GEN2
Solar/Wind Harmer
6.557
3130156CHOWAN
Solar/Wind Harmer
-0.026
315671AE2-027_GEN
Solar/Wind Harmer
4.772
961611AG1-000B GEN
Solar/Wind Harmer
13.049
316023GEN1_S
Solar/Wind Harmer
1.764
316369SG1_INVT
Solar/Wind Harmer
4.675
971069AG2-661 GEN
Solar/Wind Harmer
4.135
315816AE2-034 GEN
Solar/Wind Harmer
2.1
3145663CRESWEL
Solar/Wind Harmer
-0.072
971163AH1-040 GEN
Solar/Wind Harmer
24.399
316132AB2-190 GEN1
Solar/Wind Harmer
2.623
960081AF2-299 GEN
Solar/Wind Harmer
2.894
3138126ROCKLANDING
Solar/Wind Harmer
0.079
3142543TWELFTH
Solar/Wind Harmer
-0.002
315737AD1-076 GEN
Solar/Wind Harmer
4.864
3145893MURPHYS
Solar/Wind Harmer
-0.102
3145893MURPHYS
Solar/Wind Harmer
0.758
316087AB2-174 GEN
Solar/Wind Harmer
3.628
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.368
3146173TUNIS
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.547
3156021HOLLOMANSOL
Solar/Wind Harmer
3.391
3147043LAWRENC
Adder
2.031
3145683EARLEYS
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3143096IRON208
Adder
0.934
971317AH1-138 GEN
Solar/Wind Harmer
3.125
970937AG2-583 GEN
Solar/Wind Harmer
17.847
3145783HORNRTN
Solar/Wind Harmer
-0.025
3145823KELFORD
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.025
944631AF1-128 GEN
Adder
104.81
3145963POPLR C
Solar/Wind Harmer
-0.025
316129AC1-054 GEN
Solar/Wind Harmer
2.135
971065AG2-659 GEN
Solar/Wind Harmer
12.188
3146926FARMVIL
Solar/Wind Harmer
-0.014
971563AH1-280 GEN
Solar/Wind Harmer
3.022
3144293JTRSVLE
Adder
0.514
3144293JTRSVLE
Adder
0.406
970685AG2-442 GEN
Solar/Wind Harmer
21.144
316034AC1-036 C
Solar/Wind Harmer
0.446
315785AD2-033 C
Solar/Wind Harmer
5.458
316131AB2-060 GEN
Solar/Wind Harmer
2.592
3146293MARTNCO
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3146776BUCKING
Solar/Wind Harmer
-0.009
315975AC1-164 GENB
Solar/Wind Harmer
0.157
316494AC1-189 GEN
Solar/Wind Harmer
2.497
3142433PROV 92
Solar/Wind Harmer
-0.092
3142433PROV 92
Adder
0.4
3142433PROV 92
Adder
0.4
316319Z2-044 C
Solar/Wind Harmer
1.273
3146233WITAKRS
Solar/Wind Harmer
-0.091
961671AG1-007 GEN
Solar/Wind Harmer
0.29
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.682
970401AG2-262 GEN
Solar/Wind Harmer
1.494
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.018
316359AB2-059 GEN
Solar/Wind Harmer
3.051
3142053HEARTS
Solar/Wind Harmer
0.267
971777AH1-397 GEN
Solar/Wind Harmer
2.597
3142416OLDCHRC
Solar/Wind Harmer
-0.057
3142416OLDCHRC
Solar/Wind Harmer
-0.022
315662AE1-191 GEN
Solar/Wind Harmer
2.666
316280AD1-041 GEN
Solar/Wind Harmer
1.666
3151201GRAVEL4
Adder
17.221
3151221GRAVEL6
Adder
17.201
3151191GRAVEL3
Adder
17.003
3151211GRAVEL5
Adder
17.003
315800Z1-036_GEN1
Solar/Wind Harmer
6.557
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
315697AD1-025 GEN
Solar/Wind Harmer
5.291
316486AD2-202 GEN
Solar/Wind Harmer
0.661
946281AF1-292 GEN
Solar/Wind Harmer
0.576
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
315732AD1-074 GEN1
Solar/Wind Harmer
5.174
315733AD1-074 GEN2
Solar/Wind Harmer
5.174
316318V4-068
Solar/Wind Harmer
0.637
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
11.144
3146043SEABORD
Solar/Wind Harmer
-0.025
316463AE2-346 GEN
Solar/Wind Harmer
0.407
3145513AHOSKIE
Solar/Wind Harmer
0.22
961941AG1-037 GEN
Solar/Wind Harmer
0.19
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3137643SOCKMAN
Solar/Wind Harmer
-0.1
3145683EARLEYS
Solar/Wind Harmer
-0.05
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.247
316426AA2-053 GEN
Solar/Wind Harmer
2.519
316382AG1-145 C
Solar/Wind Harmer
0.746
316159AE1-175 C
Solar/Wind Harmer
0.664
3145796HORNRTN
Solar/Wind Harmer
-0.079
3145796HORNRTN
Solar/Wind Harmer
-0.01
316174AB2-169 GEN
Solar/Wind Harmer
3.775
970831AG2-522 GEN
Solar/Wind Harmer
12.245
3146033SCOT NK
Solar/Wind Harmer
-0.097
946301AF1-294 GEN
Solar/Wind Harmer
6.195
961791AG1-021 GEN
Solar/Wind Harmer
3.022
970683AG2-441 GEN
Solar/Wind Harmer
17.059
970681AG2-440 GEN
Solar/Wind Harmer
11.323
3144303KENBRDG
Solar/Wind Harmer
-0.019
316210AC1-098 GEN
Solar/Wind Harmer
3.78
316274AC1-208 GEN
Solar/Wind Harmer
2.586
316238AB2-078_GEN
Solar/Wind Harmer
0.722
316239AB2-077_GEN
Solar/Wind Harmer
0.722
957831AF2-077 GEN
Solar/Wind Harmer
0.719
3138283WHITEMARSH
Solar/Wind Harmer
0.037
971845AH1-439 GEN
Solar/Wind Harmer
12.475
3145746EVERETS
Solar/Wind Harmer
-0.093
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316327AA2-057 GEN
Solar/Wind Harmer
2.359
316322AB2-045
Solar/Wind Harmer
0.786
957861AF2-080 GEN
Solar/Wind Harmer
10.152
3142433PROV 92
Adder
0.4
3142433PROV 92
Adder
0.4
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
3143873LANEXA
Solar/Wind Harmer
-0.013
972205AH1-687 GEN
Adder
8.501
316059AD1-063 C
Solar/Wind Harmer
0.499
957601AF2-054 GEN
Solar/Wind Harmer
0.66
3141873WAN 176
Solar/Wind Harmer
-0.004
3138216PACIFIC
Solar/Wind Helper
0.042
226929AD2-058 GEN
Solar/Wind Helper
0.088
316314AB2-024 C
Solar/Wind Harmer
1.892
3141766HARMONY
Solar/Wind Harmer
-0.004
3150351NORNECKC2
Adder
1.555
972277AH1-723 GEN
Adder
71.991
316415AF1-147_GEN2
Solar/Wind Helper
0.853
315242AE2-183_GT2
50/50
4.392
315241AE2-183_GT1
50/50
4.381
972185AH1-677 GEN
50/50
15.877
3151041BRUNSWICKG3
50/50
3.469
972187AH1-678 GEN
50/50
7.96
3151731LOISA B
50/50
17.967
316045AC1-158 PL2
Solar/Wind Harmer
27.146
316450AC1-158 RIC
Solar/Wind Harmer
2.262
971223AH1-071 GEN
Solar/Wind Harmer
4.153
3143526WINTERP
Solar/Wind Harmer
-0.157
970933AG2-581 GEN
Solar/Wind Harmer
27.297
316313AB2-026
Solar/Wind Harmer
0.777
3144356SAPONY
Solar/Wind Harmer
0.988
316315AB2-025 C
Solar/Wind Harmer
0.762
966001AG1-469 GEN
Solar/Wind Harmer
0.531
316294AC1-161 GEN
Solar/Wind Harmer
9.035
316336AC2-165 C
Solar/Wind Harmer
17.326
316185AD1-033 GEN
Solar/Wind Harmer
2.91
3150991CHESPKB
Adder
2.574
3150991CHESPKB
Adder
2.513
3145506HICKORY
Solar/Wind Harmer
-0.11
3145506HICKORY
Solar/Wind Harmer
-0.066
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.852
316388AE2-253 GEN
Solar/Wind Harmer
1.852
3137176SLIGO L2192
Solar/Wind Harmer
-0.109
3146456SLIGO L269
Solar/Wind Harmer
3.244
3130086AYDLETT
Solar/Wind Harmer
-0.109
316083AB2-161 GEN
Solar/Wind Harmer
4.427
316349AD2-085 GEN
Solar/Wind Harmer
2.421
315835AF2-110_GEN
Solar/Wind Harmer
3.408
3146386ELIZ CT
Solar/Wind Harmer
-0.027
970099AG2-077 GEN
Solar/Wind Harmer
33.997
316431W1029_GEN1
Solar/Wind Harmer
4.896
316433W1029_GEN2
Solar/Wind Harmer
4.896
316435W1029_GEN3
Solar/Wind Harmer
4.896
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
315742AE1-103 GEN
Solar/Wind Harmer
6.315
3146376EDENTON
Solar/Wind Harmer
0.785
3146376EDENTON
Solar/Wind Harmer
0.785
316240AF1-291 C
Solar/Wind Harmer
0.792
316365GEN2_N
Solar/Wind Harmer
1.764
316033AB2-134 GEN
Solar/Wind Harmer
8.442
944641AF1-129 GEN
Adder
110.929
315614AA2-178 GEN
Solar/Wind Harmer
2.8
3145893MURPHYS
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
-0.046
316065AD1-022 GEN
Solar/Wind Harmer
12.767
313506AB2-031 GEN
Solar/Wind Harmer
2.034
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
12.647
316140AB2-099
Solar/Wind Harmer
0.17
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
962571AG1-106 GEN
Solar/Wind Harmer
3.609
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
0.208
3145783HORNRTN
Solar/Wind Harmer
2.947
3145783HORNRTN
Solar/Wind Harmer
2.357
3145783HORNRTN
Solar/Wind Harmer
0.737
3145783HORNRTN
Solar/Wind Harmer
0.295
3145796HORNRTN
Solar/Wind Harmer
-0.074
315687AD1-152 GEN
Solar/Wind Harmer
2.951
3142946ENON
Solar/Wind Harmer
-0.002
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
958211AF2-115 GEN
Solar/Wind Harmer
3.777
3144293JTRSVLE
Adder
0.514
970323AG2-213 GEN
Solar/Wind Harmer
12.066
313527AB2-043 GEN
Solar/Wind Harmer
3.91
316237AB2-079_GEN
Solar/Wind Harmer
0.722
3145933PARMELE
Solar/Wind Harmer
-0.047
3145933PARMELE
Solar/Wind Harmer
-0.024
3142366NRTHEST
Adder
0.692
3150691DARBY 3
Adder
15.153
3150701DARBY 4
Adder
15.118
3150681DARBY 2
Adder
15.1
3150671DARBY 1
Adder
15.083
315724AD1-057 GEN
Solar/Wind Harmer
4.622
316005AA1-067
Solar/Wind Harmer
0.474
3146776BUCKING
Solar/Wind Harmer
-0.093
3146776BUCKING
Solar/Wind Harmer
-0.008
315976AC1-164 GENA
Solar/Wind Harmer
5.291
316169AC1-164_GENC
Solar/Wind Harmer
4.572
962561AG1-105 GEN
Solar/Wind Harmer
12.975
3145493TOT1
Solar/Wind Harmer
0.355
3145453TOT5
Solar/Wind Harmer
0.213
3145603CNETO
Solar/Wind Harmer
0.142
964791AG1-342 GEN
Solar/Wind Harmer
4.888
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
961601AG1-000A GEN
Solar/Wind Harmer
8.919
316049AB1-081 GEN
Solar/Wind Harmer
2.441
316263AC1-034 GEN
Solar/Wind Harmer
10.634
316118AC1-105 GEN
Solar/Wind Harmer
1.54
316441AF1-014 GEN
Solar/Wind Harmer
1.5
316312AB1-027
Solar/Wind Harmer
0.747
315666AE1-190 GEN
Solar/Wind Harmer
0.666
316156AD2-030 GEN
Solar/Wind Harmer
0.587
3142296MT RD221
Adder
0.62
3150341NORNECKC1
Adder
1.634
3150341NORNECKC1
Adder
1.621
972189AH1-679 GEN
Adder
2.197
972193AH1-681 GEN
Adder
2.76
316411AF1-147_GEN1
Solar/Wind Helper
0.853
316478AD1-087 GEN
Solar/Wind Harmer
2.256
316458AB2-190 GEN2
Solar/Wind Harmer
2.623
3156081AA2-088 GEN
Solar/Wind Harmer
8.373
970133AG2-095 GEN
Solar/Wind Harmer
2.9
3144216WINCHST
Adder
0.864
966621AG1-532 GEN
Solar/Wind Harmer
0.522
315735AD1-075 GEN1
Solar/Wind Harmer
2.586
3150921YORKTN3
Adder
5.726
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
316181AB2-040 GEN
Solar/Wind Harmer
3.533
3146173TUNIS
Solar/Wind Harmer
-0.025
3147043LAWRENC
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
316011AB1-132 GEN
Solar/Wind Harmer
5.244
3146263WOODLND
Solar/Wind Harmer
-0.025
3143096IRON208
Adder
0.934
3143096IRON208
Adder
0.915
316190AA2-174 GEN
Solar/Wind Harmer
0.307
316317KELFORD C
Solar/Wind Harmer
1.147
3145823KELFORD
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.025
3142946ENON
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.014
942461AE2-259 GEN
Solar/Wind Harmer
3.642
3147133PAMPLIN
Solar/Wind Harmer
-0.076
3144293JTRSVLE
Adder
0.514
959311AF2-222 GEN
Solar/Wind Harmer
25.196
970257AG2-171 GEN
Solar/Wind Harmer
9.05
971775AH1-396 GEN
Solar/Wind Harmer
1.703
316212AC1-099_GEN
Solar/Wind Harmer
2.1
964241AG1-285 GEN
Solar/Wind Harmer
18.83
3145933PARMELE
Solar/Wind Harmer
-0.024
315722AD1-056 GEN
Solar/Wind Harmer
8.404
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
970293AG2-193 GEN
Solar/Wind Harmer
2.929
3146776BUCKING
Solar/Wind Harmer
-0.008
316075AC2-137 C
Solar/Wind Harmer
0.624
3142433PROV 92
Adder
0.4
3142433PROV 92
Adder
0.4
316420AA1-050 GEN
Solar/Wind Harmer
2.629
3146233WITAKRS
Solar/Wind Harmer
0.483
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
961601AG1-000A GEN
Solar/Wind Harmer
9.032
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
972003AH1-546 GEN
Solar/Wind Harmer
9.134
3141843SHACKLE
Adder
1.012
316203AE2-005 GEN
Solar/Wind Harmer
9.381
3142416OLDCHRC
Solar/Wind Harmer
2.241
3141766HARMONY
Solar/Wind Harmer
1.968
3141873WAN 176
Solar/Wind Harmer
1.544
3150351NORNECKC2
Adder
1.582
972255AH1-712 GEN
Adder
61.779
3141196NOKESVL
Solar/Wind Helper
1.075
227287AC2-120 GEN
Solar/Wind Helper
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
9.282
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.237
TVALTFEXP_TVA->PJM
CLTF
4.694
CPLELTFEXP_CPLE->PJM
CLTF
13.386
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.828
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.763
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.956
MECLTFEXP_MEC->PJM
CLTF
4.179
SIGELTFEXP_SIGE->PJM
CLTF
0.127
NYPJM->LTFIMP_NY
CLTF
3.886
LGEELTFEXP_LGEE->PJM
CLTF
1.527
WECLTFEXP_WEC->PJM
CLTF
0.742

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:161.05 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5186.56
MW Contribution:
6.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
60.361
316303AF2-085
50/50
4.708
971285AH1-108 GEN
50/50
1.989
316164AC1-076 GEN
Solar/Wind Harmer
0.439
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971281AH1-106 GEN
Solar/Wind Harmer
3.573
971283AH1-107 GEN
Solar/Wind Harmer
3.573
3143316POE
Solar/Wind Harmer
0.961
970533AG2-339 GEN
Solar/Wind Harmer
18.235
315697AD1-025 GEN
Solar/Wind Harmer
0.258
3151081ELIZAR1
Adder
21.982
3151091ELIZAR2
Adder
21.6
971445AH1-216 GEN
Solar/Wind Harmer
16.859
316316AC1-027 C
Solar/Wind Harmer
0.228
3151201GRAVEL4
Adder
17.415
3151221GRAVEL6
Adder
17.395
3151191GRAVEL3
Adder
17.195
3151211GRAVEL5
Adder
17.195
970657AG2-426 GEN
Solar/Wind Harmer
1.756
970673AG2-436 GEN
Solar/Wind Harmer
29.727
957871AF2-081 GEN
Solar/Wind Harmer
11.832
316311AC2-079 GEN
Solar/Wind Harmer
6.807
3146406KITTY HAWK
Solar/Wind Harmer
0.029
944641AF1-129 GEN
50/50
122.663
3152261N ANNA2
50/50
19.702
3150861SPRUNCD
50/50
1.215
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.422
3150761HOPPOLC
50/50
0.611
3151161SURRY 1
50/50
9.746
3147666LOUISA
Solar/Wind Harmer
0.63
944011AF1-069 GEN
Solar/Wind Harmer
14.524
970133AG2-095 GEN
Solar/Wind Harmer
2.312
315813AE1-149 C
Solar/Wind Harmer
12.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.282
944581AF1-123 GEN
Solar/Wind Harmer
54.082
944601AF1-125 GEN
Solar/Wind Harmer
53.249
315778AD1-151 GEN
Solar/Wind Harmer
19.212
3151101ELIZAR3
Adder
22.264
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
6.387
3145336SMITFLD
Solar/Wind Harmer
0.096
3151171GRAVELC
Adder
3.347
970657AG2-426 GEN
Solar/Wind Harmer
5.366
970293AG2-193 GEN
Solar/Wind Harmer
2.551
3142946ENON
Solar/Wind Harmer
0.08
3142416OLDCHRC
Solar/Wind Harmer
2.309
316017AA1-139 ULT1
Solar/Wind Harmer
0.127
3144216WINCHST
Adder
0.895
316075AC2-137 C
Solar/Wind Harmer
0.063
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.742
316159AE1-175 C
Solar/Wind Harmer
0.203
313526AB2-022
Solar/Wind Harmer
0.125
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
315814AE2-033 C
Solar/Wind Harmer
18.521
3146396TANGLEW
Solar/Wind Harmer
0.645
3145176PASQUOTANK
Solar/Wind Harmer
0.145
971967AH1-528 GEN
Solar/Wind Harmer
37.313
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3143873LANEXA
Solar/Wind Harmer
0.137
316258AE1-075 C
Solar/Wind Harmer
0.17
970189AG2-124 GEN
Solar/Wind Harmer
6.729
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
970085AG2-068 GEN
Solar/Wind Harmer
11.793
970581AG2-369 GEN
Solar/Wind Harmer
10.142
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3150411LDYSMT5
Adder
29.454
3150381LDYSMT2
Adder
28.188
972213AH1-691 GEN
Adder
4.768
972215AH1-692 GEN
Adder
4.768
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.238
315733AD1-074 GEN2
Solar/Wind Harmer
1.238
3146206CASHIE
Solar/Wind Harmer
0.215
970601AG2-382 GEN
Solar/Wind Harmer
8.037
3145893MURPHYS
Solar/Wind Harmer
0.58
3145893MURPHYS
Solar/Wind Harmer
0.215
316463AE2-346 GEN
Solar/Wind Harmer
0.181
3145513AHOSKIE
Solar/Wind Harmer
0.443
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.422
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315652AC1-086 GEN
Solar/Wind Harmer
22.888
3137643SOCKMAN
Solar/Wind Harmer
0.83
316426AA2-053 GEN
Solar/Wind Harmer
0.693
316486AD2-202 GEN
Solar/Wind Harmer
0.21
3145796HORNRTN
Solar/Wind Harmer
0.655
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.204
3146033SCOT NK
Solar/Wind Harmer
0.812
316210AC1-098 GEN
Solar/Wind Harmer
1.848
970831AG2-522 GEN
Solar/Wind Harmer
8.491
316274AC1-208 GEN
Solar/Wind Harmer
1.024
3145746EVERETS
Solar/Wind Harmer
0.776
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3142366NRTHEST
50/50
0.837
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150691DARBY 3
50/50
18.374
3150701DARBY 4
50/50
18.331
3150921YORKTN3
Adder
5.961
316246AF1-032 C
Solar/Wind Harmer
0.105
316321Z2-027
Solar/Wind Harmer
0.042
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
0.232
316473AC1-191 GEN
Solar/Wind Harmer
0.78
3146626S HERTFORD
Solar/Wind Harmer
0.23
3145273HOLLAND
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
3.45
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
3.024
3146376EDENTON
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
4.01
970917AG2-570 GEN
Solar/Wind Harmer
19.909
3150401LDYSMT4
Adder
29.362
3150371LDYSMT1
Adder
28.372
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.618
3146206CASHIE
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
3146173TUNIS
Solar/Wind Harmer
0.213
3146263WOODLND
Solar/Wind Harmer
0.21
316181AB2-040 GEN
Solar/Wind Harmer
0.298
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
316011AB1-132 GEN
Solar/Wind Harmer
3.774
3145963POPLR C
Solar/Wind Harmer
0.207
3145823KELFORD
Solar/Wind Harmer
0.207
3147043LAWRENC
Solar/Wind Harmer
0.124
316478AD1-087 GEN
Solar/Wind Harmer
0.713
3145796HORNRTN
Solar/Wind Harmer
0.819
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.073
316212AC1-099_GEN
Solar/Wind Harmer
1.031
3145933PARMELE
Solar/Wind Harmer
0.199
971781AH1-399 GEN
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
6.726
964241AG1-285 GEN
Solar/Wind Harmer
12.809
970257AG2-171 GEN
Solar/Wind Harmer
6.136
971775AH1-396 GEN
Solar/Wind Harmer
0.307
959311AF2-222 GEN
Solar/Wind Harmer
17.039
3144293JTRSVLE
Adder
0.457
3147133PAMPLIN
Solar/Wind Harmer
0.6
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.952
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.189
3146083TARBORO
Solar/Wind Harmer
0.189
3138543CONSLDL
Solar/Wind Harmer
0.125
3132273ORANGE
Solar/Wind Harmer
0.038
961601AG1-000A GEN
Solar/Wind Harmer
13.243
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.186
971623AH1-311 GEN
Solar/Wind Harmer
0.372
316223AC1-118
Solar/Wind Harmer
0.131
3141906WESTMOR
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.066
972003AH1-546 GEN
Solar/Wind Harmer
6.047
3151761LOISA E
Adder
22.171
3151721LOISA A
Adder
10.819
970221AG2-151 GEN
Solar/Wind Harmer
8.658
971683AH1-343 GEN
Solar/Wind Harmer
5.878
316222AC1-221 GEN
Solar/Wind Harmer
0.652
316283AC2-100 C
Solar/Wind Harmer
0.308
972255AH1-712 GEN
Adder
75.929
270494AE1-108_GEN
Solar/Wind Harmer
1.705
316123AC1-075 GEN
Solar/Wind Harmer
0.189
315821AE2-092 GEN
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.165
316045AC1-158 PL2
Solar/Wind Harmer
9.684
316450AC1-158 RIC
Solar/Wind Harmer
0.807
971223AH1-071 GEN
Solar/Wind Harmer
2.825
3143526WINTERP
Solar/Wind Harmer
1.339
316294AC1-161 GEN
Solar/Wind Harmer
4.182
3150681DARBY 2
Adder
17.255
3150671DARBY 1
Adder
17.235
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3150991CHESPKB
Adder
2.511
3150991CHESPKB
Adder
2.45
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.954
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
316312AB1-027
Solar/Wind Harmer
0.424
316339AD2-160 GEN
Solar/Wind Harmer
0.381
316388AE2-253 GEN
Solar/Wind Harmer
0.74
3137176SLIGO L2192
Solar/Wind Harmer
0.944
3146456SLIGO L269
Solar/Wind Harmer
4.197
316349AD2-085 GEN
Solar/Wind Harmer
0.158
3130086AYDLETT
Solar/Wind Harmer
0.947
315976AC1-164 GENA
Solar/Wind Harmer
2.483
316169AC1-164_GENC
Solar/Wind Harmer
2.145
315835AF2-110_GEN
Solar/Wind Harmer
1.617
972185AH1-677 GEN
Adder
13.194
3144356SAPONY
Solar/Wind Harmer
1.966
316315AB2-025 C
Solar/Wind Harmer
0.188
3146386ELIZ CT
Solar/Wind Harmer
0.235
972189AH1-679 GEN
Adder
3.929
972187AH1-678 GEN
Adder
6.617
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.23
3146626S HERTFORD
Solar/Wind Harmer
0.23
970933AG2-581 GEN
Solar/Wind Harmer
18.296
316313AB2-026
Solar/Wind Harmer
0.142
315742AE1-103 GEN
Solar/Wind Harmer
3.398
3146376EDENTON
Solar/Wind Harmer
1.005
3146376EDENTON
Solar/Wind Harmer
1.005
316156AD2-030 GEN
Solar/Wind Harmer
0.165
315673AE1-157 GEN
Solar/Wind Harmer
15.458
315614AA2-178 GEN
Solar/Wind Harmer
1.26
3150391LDYSMT3
Adder
29.307
972195AH1-682 GEN
Adder
3.851
316336AC2-165 C
Solar/Wind Harmer
11.083
316365GEN2_N
Solar/Wind Harmer
0.483
316065AD1-022 GEN
Solar/Wind Harmer
9.946
3145893MURPHYS
Solar/Wind Harmer
1.438
3145893MURPHYS
Solar/Wind Harmer
0.387
970099AG2-077 GEN
Solar/Wind Harmer
22.839
3146173TUNIS
Solar/Wind Harmer
0.213
3152251N ANNA1
50/50
19.692
971507AH1-251 GEN
50/50
16.761
970119AG2-088 GEN
50/50
35.314
3150851SPRUNCC
50/50
1.215
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.861
3150771HOPHCF1
50/50
0.977
316447AC1-158 HLD
Solar/Wind Harmer
6.655
316044AC1-158 PL1
Solar/Wind Harmer
3.026
3147666LOUISA
Solar/Wind Harmer
1.095
316192AB2-158 GEN
Solar/Wind Harmer
1.504
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.339
940641AE2-051 GEN
Solar/Wind Harmer
19.868
939411AE1-173 GEN
Solar/Wind Harmer
104.983
3142543TWELFTH
Solar/Wind Harmer
0.023
315773AC2-141 GEN
Solar/Wind Harmer
8.836
315671AE2-027_GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
44.451
316132AB2-190 GEN1
Solar/Wind Harmer
1.282
944591AF1-124 GEN
Solar/Wind Harmer
54.274
971069AG2-661 GEN
Solar/Wind Harmer
4.269
944631AF1-128 GEN
Adder
114.38
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.043
3150981CHESPKA
Adder
2.993
961611AG1-000B GEN
Solar/Wind Harmer
12.562
3145336SMITFLD
Solar/Wind Harmer
0.957
316381AD1-082 GEN
Solar/Wind Harmer
0.243
3145746EVERETS
Solar/Wind Harmer
0.195
316327AA2-057 GEN
Solar/Wind Harmer
0.285
957861AF2-080 GEN
Solar/Wind Harmer
8.277
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
11.541
970681AG2-440 GEN
Solar/Wind Harmer
7.66
946301AF1-294 GEN
Solar/Wind Harmer
3.774
961791AG1-021 GEN
Solar/Wind Harmer
1.836
3145573BETHELC
Solar/Wind Harmer
0.189
3145573BETHELC
Solar/Wind Harmer
0.189
971845AH1-439 GEN
Solar/Wind Harmer
8.303
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.109
972205AH1-687 GEN
Adder
7.406
3147346CASHSCORNER
Solar/Wind Harmer
0.369
944491AF1-114 GEN
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.003
315651AD1-115 GEN
Solar/Wind Harmer
0
3138216PACIFIC
Solar/Wind Helper
0.04
3146173TUNIS
Solar/Wind Harmer
0.213
316140AB2-099
Solar/Wind Harmer
0.075
313506AB2-031 GEN
Solar/Wind Harmer
0.642
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
3142666NORTHAMPTON
Solar/Wind Harmer
0.208
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
962571AG1-106 GEN
Solar/Wind Harmer
2.96
3145593CAROLNA
Solar/Wind Harmer
0.206
3145593CAROLNA
Solar/Wind Harmer
0.206
3145593CAROLNA
Solar/Wind Harmer
0.257
3145783HORNRTN
Solar/Wind Harmer
3.649
3145783HORNRTN
Solar/Wind Harmer
2.919
3145783HORNRTN
Solar/Wind Harmer
0.912
3145783HORNRTN
Solar/Wind Harmer
0.365
3145796HORNRTN
Solar/Wind Harmer
0.615
3150341NORNECKC1
Adder
2.142
3150341NORNECKC1
Adder
2.124
3145933PARMELE
Solar/Wind Harmer
0.398
3145933PARMELE
Solar/Wind Harmer
0.199
970301AG2-198 GEN
Solar/Wind Harmer
8.471
316005AA1-067
Solar/Wind Harmer
0.208
315724AD1-057 GEN
Solar/Wind Harmer
3.752
970323AG2-213 GEN
Solar/Wind Harmer
8.181
958211AF2-115 GEN
Solar/Wind Harmer
2.295
3144293JTRSVLE
Adder
0.457
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.153
3145493TOT1
Solar/Wind Harmer
0.439
3145453TOT5
Solar/Wind Harmer
0.263
3145603CNETO
Solar/Wind Harmer
0.176
961601AG1-000A GEN
Solar/Wind Harmer
3.311
316049AB1-081 GEN
Solar/Wind Harmer
1.059
316263AC1-034 GEN
Solar/Wind Harmer
7.074
962561AG1-105 GEN
Solar/Wind Harmer
8.825
3146776BUCKING
Solar/Wind Harmer
0.73
3146776BUCKING
Solar/Wind Harmer
0.059
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
316118AC1-105 GEN
Solar/Wind Harmer
0.457
966001AG1-469 GEN
Solar/Wind Harmer
0.098
3151731LOISA B
Adder
10.875
972193AH1-681 GEN
Adder
3.393
942751AE2-291 GEN
Solar/Wind Harmer
7.272
316411AF1-147_GEN1
Solar/Wind Helper
0.823
3151171GRAVELC
Adder
2.545
3142416OLDCHRC
Solar/Wind Harmer
0.619
3142416OLDCHRC
Solar/Wind Harmer
0.237
3138126ROCKLANDING
Solar/Wind Harmer
0.109
3146456SLIGO L269
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.084
319010AE1-072 C
Solar/Wind Harmer
1.182
315975AC1-164 GENB
Solar/Wind Harmer
0.073
971317AH1-138 GEN
Solar/Wind Harmer
1.761
316093AE2-104_GEN
Solar/Wind Harmer
3.964
3142433PROV 92
Solar/Wind Harmer
0.928
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
0.752
3146516WINFALL
Solar/Wind Harmer
0.232
3143336POWHATN
Solar/Wind Harmer
4.059
971777AH1-397 GEN
Solar/Wind Harmer
0.599
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.226
966881AG1-559 GEN
Solar/Wind Harmer
0.261
970919AG2-571 GEN
Solar/Wind Harmer
7.964
3138133OCRAN
Solar/Wind Harmer
0.133
315816AE2-034 GEN
Solar/Wind Harmer
0.945
3145663CRESWEL
Solar/Wind Harmer
0.62
971163AH1-040 GEN
Solar/Wind Harmer
17.724
970087AG2-069 GEN
Solar/Wind Harmer
17.689
972197AH1-683 GEN
Adder
4.585
972219AH1-694 GEN
Adder
3.301
316023GEN1_S
Solar/Wind Harmer
0.483
315737AD1-076 GEN
Solar/Wind Harmer
2.787
3146206CASHIE
Solar/Wind Harmer
0.215
971547AH1-271 GEN
Solar/Wind Harmer
4.593
3145893MURPHYS
Solar/Wind Harmer
0.859
3145893MURPHYS
Solar/Wind Harmer
0.955
957481AF2-042 GEN
Solar/Wind Harmer
57.098
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.956
960081AF2-299 GEN
Solar/Wind Harmer
2.035
962861AG1-135 GEN
Solar/Wind Harmer
6.77
3145683EARLEYS
Solar/Wind Harmer
0.211
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.965
315607AA1-063A GEN
Solar/Wind Harmer
0.423
315693AD1-088 GEN
Solar/Wind Harmer
10.082
3146263WOODLND
Solar/Wind Harmer
0.21
3145963POPLR C
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.829
3145823KELFORD
Solar/Wind Harmer
0.207
3147043LAWRENC
Adder
1.864
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.676
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.039
3146293MARTNCO
Solar/Wind Harmer
0.184
316129AC1-054 GEN
Solar/Wind Harmer
0.739
971065AG2-659 GEN
Solar/Wind Harmer
8.417
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
316337AD2-073 GEN
Solar/Wind Harmer
0.168
970937AG2-583 GEN
Solar/Wind Harmer
11.909
316131AB2-060 GEN
Solar/Wind Harmer
0.598
316494AC1-189 GEN
Solar/Wind Harmer
0.649
315785AD2-033 C
Solar/Wind Harmer
1.551
316034AC1-036 C
Solar/Wind Harmer
0.013
970685AG2-442 GEN
Solar/Wind Harmer
14.29
971563AH1-280 GEN
Solar/Wind Harmer
2.04
3144293JTRSVLE
Adder
0.457
3144293JTRSVLE
Adder
0.36
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.754
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.189
3145493TOT1
Solar/Wind Harmer
0.842
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.662
3142053HEARTS
Solar/Wind Harmer
0.328
3146776BUCKING
Solar/Wind Harmer
0.073
970401AG2-262 GEN
Solar/Wind Harmer
1.07
316254AC1-120 GEN1
Solar/Wind Harmer
6.037
316170AC1-121 GEN2
Solar/Wind Harmer
2.073
3151751LOISA D
Adder
10.875
972135AH1-637 GEN
Solar/Wind Harmer
1.428
971377AH1-170 GEN
Solar/Wind Harmer
1.732
3147623JAMES R
Solar/Wind Harmer
0.376
972277AH1-723 GEN
Adder
88.48
316415AF1-147_GEN2
Solar/Wind Helper
0.823
LAGNLTFEXP_LAGN->PJM
CLTF
8.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.265
TVALTFEXP_TVA->PJM
CLTF
4.142
CPLELTFEXP_CPLE->PJM
CLTF
12.057
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.986
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.014
MECLTFEXP_MEC->PJM
CLTF
3.532
SIGELTFEXP_SIGE->PJM
CLTF
0.107
NYPJM->LTFIMP_NY
CLTF
3.442
LGEELTFEXP_LGEE->PJM
CLTF
1.281
WECLTFEXP_WEC->PJM
CLTF
0.611

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:156.69 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5046.02
MW Contribution:
5.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.637
971285AH1-108 GEN
50/50
1.958
316233AE1-074 FULL
Solar/Wind Harmer
0.203
971281AH1-106 GEN
Solar/Wind Harmer
3.518
971283AH1-107 GEN
Solar/Wind Harmer
3.518
3143316POE
Solar/Wind Harmer
0.946
970533AG2-339 GEN
Solar/Wind Harmer
17.962
315697AD1-025 GEN
Solar/Wind Harmer
0.254
3151081ELIZAR1
Adder
21.641
3151091ELIZAR2
Adder
21.266
971445AH1-216 GEN
Solar/Wind Harmer
16.596
316316AC1-027 C
Solar/Wind Harmer
0.225
3151201GRAVEL4
Adder
17.143
3151221GRAVEL6
Adder
17.123
3151191GRAVEL3
Adder
16.926
3151211GRAVEL5
Adder
16.926
970657AG2-426 GEN
Solar/Wind Harmer
1.729
970673AG2-436 GEN
Solar/Wind Harmer
29.28
957871AF2-081 GEN
Solar/Wind Harmer
11.649
316164AC1-076 GEN
Solar/Wind Harmer
0.322
316311AC2-079 GEN
Solar/Wind Harmer
6.702
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316159AE1-175 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.123
3146486SUNBURY
Solar/Wind Harmer
0.23
3146486SUNBURY
Solar/Wind Harmer
0.23
315814AE2-033 C
Solar/Wind Harmer
18.237
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
971967AH1-528 GEN
Solar/Wind Harmer
36.746
3142433PROV 92
Adder
0.444
3142433PROV 92
Adder
0.444
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143873LANEXA
Solar/Wind Harmer
0.135
316258AE1-075 C
Solar/Wind Harmer
0.168
970189AG2-124 GEN
Solar/Wind Harmer
6.622
3130156CHOWAN
Solar/Wind Harmer
0.223
3130156CHOWAN
Solar/Wind Harmer
0.223
3141873WAN 176
Solar/Wind Harmer
0.044
3141913WHIT STONE
Solar/Wind Harmer
0.219
3138133OCRAN
Solar/Wind Harmer
0.065
970085AG2-068 GEN
Solar/Wind Harmer
11.614
970581AG2-369 GEN
Solar/Wind Harmer
9.988
3141783LANCAST
Solar/Wind Harmer
0.13
3141783LANCAST
Solar/Wind Harmer
0.087
3150411LDYSMT5
Adder
28.955
3150381LDYSMT2
Adder
27.711
972213AH1-691 GEN
Adder
4.688
972215AH1-692 GEN
Adder
4.688
3130546PLYMOUTH
Solar/Wind Harmer
0.214
315732AD1-074 GEN1
Solar/Wind Harmer
1.219
315733AD1-074 GEN2
Solar/Wind Harmer
1.219
3146206CASHIE
Solar/Wind Harmer
0.212
970601AG2-382 GEN
Solar/Wind Harmer
7.912
3145893MURPHYS
Solar/Wind Harmer
0.571
3145893MURPHYS
Solar/Wind Harmer
0.211
316463AE2-346 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
0.436
3145513AHOSKIE
Solar/Wind Harmer
0.208
3146043SEABORD
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.415
3145683EARLEYS
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.208
315652AC1-086 GEN
Solar/Wind Harmer
22.53
944641AF1-129 GEN
50/50
120.732
3142366NRTHEST
50/50
0.824
3150781HOPHCF2
50/50
0.961
3150791HOPHCF3
50/50
0.961
3150691DARBY 3
50/50
18.078
3150701DARBY 4
50/50
18.036
316045AC1-158 PL2
Solar/Wind Harmer
9.608
316450AC1-158 RIC
Solar/Wind Harmer
0.801
971223AH1-071 GEN
Solar/Wind Harmer
2.782
3143526WINTERP
Solar/Wind Harmer
1.318
316294AC1-161 GEN
Solar/Wind Harmer
4.117
3150681DARBY 2
Adder
16.977
3150671DARBY 1
Adder
16.957
3142296MT RD221
Adder
0.752
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3150991CHESPKB
Adder
2.472
3150991CHESPKB
Adder
2.412
3145506HICKORY
Solar/Wind Harmer
0.94
3145506HICKORY
Solar/Wind Harmer
0.564
3145506HICKORY
Solar/Wind Harmer
0.141
3142946ENON
Solar/Wind Harmer
0.023
316312AB1-027
Solar/Wind Harmer
0.417
316339AD2-160 GEN
Solar/Wind Harmer
0.375
316388AE2-253 GEN
Solar/Wind Harmer
0.729
3137176SLIGO L2192
Solar/Wind Harmer
0.929
3146456SLIGO L269
Solar/Wind Harmer
4.132
316349AD2-085 GEN
Solar/Wind Harmer
0.156
3130086AYDLETT
Solar/Wind Harmer
0.933
315976AC1-164 GENA
Solar/Wind Harmer
2.443
316169AC1-164_GENC
Solar/Wind Harmer
2.111
315835AF2-110_GEN
Solar/Wind Harmer
1.592
972185AH1-677 GEN
Adder
12.995
3144356SAPONY
Solar/Wind Harmer
1.936
316315AB2-025 C
Solar/Wind Harmer
0.185
3146386ELIZ CT
Solar/Wind Harmer
0.231
972189AH1-679 GEN
Adder
3.864
972187AH1-678 GEN
Adder
6.517
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
966871AG1-558 GEN
Solar/Wind Harmer
0.262
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
970933AG2-581 GEN
Solar/Wind Harmer
18.015
316313AB2-026
Solar/Wind Harmer
0.14
315742AE1-103 GEN
Solar/Wind Harmer
3.345
3146376EDENTON
Solar/Wind Harmer
0.99
3146376EDENTON
Solar/Wind Harmer
0.99
316156AD2-030 GEN
Solar/Wind Harmer
0.163
315673AE1-157 GEN
Solar/Wind Harmer
15.198
315614AA2-178 GEN
Solar/Wind Harmer
1.241
3150391LDYSMT3
Adder
28.81
972195AH1-682 GEN
Adder
3.786
316336AC2-165 C
Solar/Wind Harmer
10.886
316365GEN2_N
Solar/Wind Harmer
0.476
316065AD1-022 GEN
Solar/Wind Harmer
9.791
3145893MURPHYS
Solar/Wind Harmer
1.415
3145893MURPHYS
Solar/Wind Harmer
0.38
970099AG2-077 GEN
Solar/Wind Harmer
22.48
3146173TUNIS
Solar/Wind Harmer
0.21
3146173TUNIS
Solar/Wind Harmer
0.21
316140AB2-099
Solar/Wind Harmer
0.074
313506AB2-031 GEN
Solar/Wind Harmer
0.632
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.123
3152251N ANNA1
50/50
19.462
970119AG2-088 GEN
50/50
34.777
3150851SPRUNCC
50/50
1.196
3143096IRON208
50/50
1.061
3152331SURRY 2
50/50
9.706
3150771HOPHCF1
50/50
0.961
316447AC1-158 HLD
Solar/Wind Harmer
6.603
316044AC1-158 PL1
Solar/Wind Harmer
3.003
3147666LOUISA
Solar/Wind Harmer
1.066
3143226MDLTHAN
Solar/Wind Harmer
0.261
316192AB2-158 GEN
Solar/Wind Harmer
1.463
3143526WINTERP
Solar/Wind Harmer
1.318
940641AE2-051 GEN
Solar/Wind Harmer
19.57
939411AE1-173 GEN
Solar/Wind Harmer
103.394
3142543TWELFTH
Solar/Wind Harmer
0.023
315773AC2-141 GEN
Solar/Wind Harmer
8.699
315671AE2-027_GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
43.784
316132AB2-190 GEN1
Solar/Wind Harmer
1.262
944591AF1-124 GEN
Solar/Wind Harmer
53.433
971069AG2-661 GEN
Solar/Wind Harmer
4.202
944631AF1-128 GEN
Adder
112.557
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.042
3150981CHESPKA
Adder
2.946
3145336SMITFLD
Solar/Wind Harmer
0.942
961611AG1-000B GEN
Solar/Wind Harmer
12.365
316381AD1-082 GEN
Solar/Wind Harmer
0.239
3151171GRAVELC
Adder
2.505
3142416OLDCHRC
Solar/Wind Harmer
0.609
3142416OLDCHRC
Solar/Wind Harmer
0.233
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3146456SLIGO L269
Solar/Wind Harmer
0.233
316072AD1-144
Solar/Wind Harmer
0.083
319010AE1-072 C
Solar/Wind Harmer
1.164
315975AC1-164 GENB
Solar/Wind Harmer
0.072
971317AH1-138 GEN
Solar/Wind Harmer
1.733
316093AE2-104_GEN
Solar/Wind Harmer
3.902
3142433PROV 92
Solar/Wind Harmer
0.913
3142433PROV 92
Adder
0.444
3142433PROV 92
Adder
0.444
3146516WINFALL
Solar/Wind Harmer
0.74
3146516WINFALL
Solar/Wind Harmer
0.228
3143336POWHATN
Solar/Wind Harmer
3.989
971777AH1-397 GEN
Solar/Wind Harmer
0.59
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.223
966881AG1-559 GEN
Solar/Wind Harmer
0.257
970919AG2-571 GEN
Solar/Wind Harmer
7.843
3138133OCRAN
Solar/Wind Harmer
0.131
315816AE2-034 GEN
Solar/Wind Harmer
0.931
3145663CRESWEL
Solar/Wind Harmer
0.61
971163AH1-040 GEN
Solar/Wind Harmer
17.448
970087AG2-069 GEN
Solar/Wind Harmer
17.42
972197AH1-683 GEN
Adder
4.507
972219AH1-694 GEN
Adder
3.245
316023GEN1_S
Solar/Wind Harmer
0.476
315737AD1-076 GEN
Solar/Wind Harmer
2.744
3146206CASHIE
Solar/Wind Harmer
0.212
971547AH1-271 GEN
Solar/Wind Harmer
4.521
3145893MURPHYS
Solar/Wind Harmer
0.846
3145893MURPHYS
Solar/Wind Harmer
0.94
957481AF2-042 GEN
Solar/Wind Harmer
56.201
3146173TUNIS
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.941
960081AF2-299 GEN
Solar/Wind Harmer
2.003
962861AG1-135 GEN
Solar/Wind Harmer
6.663
3145683EARLEYS
Solar/Wind Harmer
0.208
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.856
315607AA1-063A GEN
Solar/Wind Harmer
0.417
315693AD1-088 GEN
Solar/Wind Harmer
9.92
3146263WOODLND
Solar/Wind Harmer
0.206
3152261N ANNA2
50/50
19.472
3150861SPRUNCD
50/50
1.196
3143096IRON208
50/50
1.061
3143096IRON208
50/50
1.04
3150801HOPHCF4
50/50
1.4
3150761HOPPOLC
50/50
0.601
3151161SURRY 1
50/50
9.594
3147666LOUISA
Solar/Wind Harmer
0.613
944011AF1-069 GEN
Solar/Wind Harmer
14.306
315813AE1-149 C
Solar/Wind Harmer
12.647
970133AG2-095 GEN
Solar/Wind Harmer
2.276
316458AB2-190 GEN2
Solar/Wind Harmer
1.262
944581AF1-123 GEN
Solar/Wind Harmer
53.244
944601AF1-125 GEN
Solar/Wind Harmer
52.424
315778AD1-151 GEN
Solar/Wind Harmer
18.91
3151101ELIZAR3
Adder
21.918
3144536CHRHLND
Solar/Wind Harmer
0.035
3144873MCLAUGH
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.094
961611AG1-000B GEN
Solar/Wind Harmer
6.287
3151171GRAVELC
Adder
3.294
970657AG2-426 GEN
Solar/Wind Harmer
5.282
970293AG2-193 GEN
Solar/Wind Harmer
2.509
3142946ENON
Solar/Wind Harmer
0.079
3142416OLDCHRC
Solar/Wind Harmer
2.272
316017AA1-139 ULT1
Solar/Wind Harmer
0.125
3144216WINCHST
Adder
0.881
316075AC2-137 C
Solar/Wind Harmer
0.062
3146456SLIGO L269
Solar/Wind Harmer
0.233
971153AH1-033 GEN
Solar/Wind Harmer
2.699
3150921YORKTN3
Adder
5.867
316246AF1-032 C
Solar/Wind Harmer
0.104
316321Z2-027
Solar/Wind Harmer
0.041
3142433PROV 92
Adder
0.444
3142433PROV 92
Adder
0.444
3146516WINFALL
Solar/Wind Harmer
0.228
316473AC1-191 GEN
Solar/Wind Harmer
0.767
3146626S HERTFORD
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.17
3143336POWHATN
Solar/Wind Harmer
3.391
3141843SHACKLE
Adder
1.142
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
2.976
3146376EDENTON
Solar/Wind Harmer
0.223
3141873WAN 176
Solar/Wind Harmer
3.946
970917AG2-570 GEN
Solar/Wind Harmer
19.607
3150401LDYSMT4
Adder
28.865
3150371LDYSMT1
Adder
27.891
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.608
3146206CASHIE
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.21
3146263WOODLND
Solar/Wind Harmer
0.206
316181AB2-040 GEN
Solar/Wind Harmer
0.293
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
316011AB1-132 GEN
Solar/Wind Harmer
3.715
3137643SOCKMAN
Solar/Wind Harmer
0.817
316426AA2-053 GEN
Solar/Wind Harmer
0.682
316486AD2-202 GEN
Solar/Wind Harmer
0.206
3145796HORNRTN
Solar/Wind Harmer
0.645
3145796HORNRTN
Solar/Wind Harmer
0.081
3141813NORNECK
Solar/Wind Harmer
0.201
3146033SCOT NK
Solar/Wind Harmer
0.799
316210AC1-098 GEN
Solar/Wind Harmer
1.819
970831AG2-522 GEN
Solar/Wind Harmer
8.356
316274AC1-208 GEN
Solar/Wind Harmer
1.008
3145746EVERETS
Solar/Wind Harmer
0.764
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
316327AA2-057 GEN
Solar/Wind Harmer
0.281
957861AF2-080 GEN
Solar/Wind Harmer
8.147
3144303KENBRDG
Solar/Wind Harmer
0.151
970683AG2-441 GEN
Solar/Wind Harmer
11.342
970681AG2-440 GEN
Solar/Wind Harmer
7.528
946301AF1-294 GEN
Solar/Wind Harmer
3.708
961791AG1-021 GEN
Solar/Wind Harmer
1.804
3145573BETHELC
Solar/Wind Harmer
0.186
3145573BETHELC
Solar/Wind Harmer
0.186
971845AH1-439 GEN
Solar/Wind Harmer
8.139
3147173SINAI
Solar/Wind Harmer
0.172
3147243WELCO
Solar/Wind Harmer
0.108
972205AH1-687 GEN
Adder
7.246
944491AF1-114 GEN
Solar/Wind Harmer
0
3147346CASHSCORNER
Solar/Wind Harmer
0.349
3145963POPLR C
Solar/Wind Harmer
0.204
3141726DUNNSVL
Solar/Wind Harmer
0.816
3145823KELFORD
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
1.834
3145783HORNRTN
Solar/Wind Harmer
0.202
3145796HORNRTN
Solar/Wind Harmer
0.665
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.007
3146293MARTNCO
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.727
971065AG2-659 GEN
Solar/Wind Harmer
8.282
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
316337AD2-073 GEN
Solar/Wind Harmer
0.165
970937AG2-583 GEN
Solar/Wind Harmer
11.675
316131AB2-060 GEN
Solar/Wind Harmer
0.588
316494AC1-189 GEN
Solar/Wind Harmer
0.638
315785AD2-033 C
Solar/Wind Harmer
1.525
316034AC1-036 C
Solar/Wind Harmer
0.013
970685AG2-442 GEN
Solar/Wind Harmer
14.042
971563AH1-280 GEN
Solar/Wind Harmer
2.004
3144293JTRSVLE
Adder
0.449
3144293JTRSVLE
Adder
0.354
3146233WITAKRS
Solar/Wind Harmer
0.742
3146926FARMVIL
Solar/Wind Harmer
0.112
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.186
3145493TOT1
Solar/Wind Harmer
0.829
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.146
316359AB2-059 GEN
Solar/Wind Harmer
0.651
3142053HEARTS
Solar/Wind Harmer
0.323
970401AG2-262 GEN
Solar/Wind Harmer
1.052
3146776BUCKING
Solar/Wind Harmer
0.072
972135AH1-637 GEN
Solar/Wind Harmer
1.406
971377AH1-170 GEN
Solar/Wind Harmer
1.694
3147623JAMES R
Solar/Wind Harmer
0.368
3151751LOISA D
Adder
10.304
972277AH1-723 GEN
Adder
86.737
316254AC1-120 GEN1
Solar/Wind Harmer
4.284
316170AC1-121 GEN2
Solar/Wind Harmer
1.471
316415AF1-147_GEN2
Solar/Wind Helper
0.808
3145963POPLR C
Solar/Wind Harmer
0.204
3145823KELFORD
Solar/Wind Harmer
0.204
316478AD1-087 GEN
Solar/Wind Harmer
0.702
3147043LAWRENC
Solar/Wind Harmer
0.122
3145796HORNRTN
Solar/Wind Harmer
0.806
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.041
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3145933PARMELE
Solar/Wind Harmer
0.196
971781AH1-399 GEN
Solar/Wind Harmer
0.256
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315722AD1-056 GEN
Solar/Wind Harmer
6.621
964241AG1-285 GEN
Solar/Wind Harmer
12.595
970257AG2-171 GEN
Solar/Wind Harmer
6.032
971775AH1-396 GEN
Solar/Wind Harmer
0.302
959311AF2-222 GEN
Solar/Wind Harmer
16.747
3144293JTRSVLE
Adder
0.449
3147133PAMPLIN
Solar/Wind Harmer
0.589
942461AE2-259 GEN
Solar/Wind Harmer
0
3146233WITAKRS
Solar/Wind Harmer
0.937
3146233WITAKRS
Solar/Wind Harmer
0.127
3146926FARMVIL
Solar/Wind Harmer
0.112
3146073TAR RVR
Solar/Wind Harmer
0.186
3146083TARBORO
Solar/Wind Harmer
0.186
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.035
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.183
971623AH1-311 GEN
Solar/Wind Harmer
0.366
316223AC1-118
Solar/Wind Harmer
0.129
3141906WESTMOR
Solar/Wind Harmer
0.072
3146776BUCKING
Solar/Wind Harmer
0.064
972003AH1-546 GEN
Solar/Wind Harmer
5.918
970221AG2-151 GEN
Solar/Wind Harmer
8.468
3151761LOISA E
Adder
21.008
3151721LOISA A
Adder
10.251
971683AH1-343 GEN
Solar/Wind Harmer
5.78
316222AC1-221 GEN
Solar/Wind Harmer
0.642
3132273ORANGE
Solar/Wind Harmer
0.031
316283AC2-100 C
Solar/Wind Harmer
0.303
972255AH1-712 GEN
Adder
74.433
316123AC1-075 GEN
Solar/Wind Harmer
0.186
270494AE1-108_GEN
Solar/Wind Harmer
1.668
315821AE2-092 GEN
Solar/Wind Harmer
0
3141196NOKESVL
Solar/Wind Helper
1.14
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138216PACIFIC
Solar/Wind Helper
0.039
962571AG1-106 GEN
Solar/Wind Harmer
2.914
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
3.592
3145783HORNRTN
Solar/Wind Harmer
2.873
3145783HORNRTN
Solar/Wind Harmer
0.898
3145783HORNRTN
Solar/Wind Harmer
0.359
3145796HORNRTN
Solar/Wind Harmer
0.605
3150341NORNECKC1
Adder
2.108
3150341NORNECKC1
Adder
2.091
3145933PARMELE
Solar/Wind Harmer
0.392
3145933PARMELE
Solar/Wind Harmer
0.196
970301AG2-198 GEN
Solar/Wind Harmer
8.323
316005AA1-067
Solar/Wind Harmer
0.205
315724AD1-057 GEN
Solar/Wind Harmer
3.693
970323AG2-213 GEN
Solar/Wind Harmer
8.042
958211AF2-115 GEN
Solar/Wind Harmer
2.255
3144293JTRSVLE
Adder
0.449
3147133PAMPLIN
Solar/Wind Harmer
0.188
3147133PAMPLIN
Solar/Wind Harmer
0.15
3145493TOT1
Solar/Wind Harmer
0.432
3145453TOT5
Solar/Wind Harmer
0.259
3145603CNETO
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
3.259
316049AB1-081 GEN
Solar/Wind Harmer
1.042
316263AC1-034 GEN
Solar/Wind Harmer
6.963
962561AG1-105 GEN
Solar/Wind Harmer
8.681
964791AG1-342 GEN
Solar/Wind Harmer
3.444
3146843MT LREL
Solar/Wind Harmer
0.179
3146843MT LREL
Solar/Wind Harmer
0.179
3146776BUCKING
Solar/Wind Harmer
0.715
3146776BUCKING
Solar/Wind Harmer
0.058
316118AC1-105 GEN
Solar/Wind Harmer
0.45
3151731LOISA B
Adder
10.304
966001AG1-469 GEN
Solar/Wind Harmer
0.09
972193AH1-681 GEN
Adder
3.326
942751AE2-291 GEN
Solar/Wind Harmer
7.147
316411AF1-147_GEN1
Solar/Wind Helper
0.808
LAGNLTFEXP_LAGN->PJM
CLTF
8.025
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.831
TVALTFEXP_TVA->PJM
CLTF
4.067
CPLELTFEXP_CPLE->PJM
CLTF
11.863
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.77
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.544
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.756
MECLTFEXP_MEC->PJM
CLTF
3.461
SIGELTFEXP_SIGE->PJM
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
3.379
LGEELTFEXP_LGEE->PJM
CLTF
1.254
WECLTFEXP_WEC->PJM
CLTF
0.598

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2-2199_SRT-A-1


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.02 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4571.15
MW Contribution:
7.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.71
971285AH1-108 GEN
50/50
1.495
315244AE2-183_ST
50/50
5.289
963041AG1-153 GEN
50/50
4.873
316164AC1-076 GEN
Solar/Wind Harmer
3.456
315651AD1-115 GEN
Solar/Wind Harmer
16.764
3147346CASHSCORNER
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.6
971281AH1-106 GEN
Solar/Wind Harmer
3.628
971283AH1-107 GEN
Solar/Wind Harmer
3.628
970533AG2-339 GEN
Solar/Wind Harmer
14.33
970673AG2-436 GEN
Solar/Wind Harmer
46.15
316258AE1-075 C
Solar/Wind Harmer
0.508
316405AF2-144 C
Solar/Wind Harmer
0.537
3143316POE
Solar/Wind Harmer
-0.082
971967AH1-528 GEN
Solar/Wind Harmer
38.809
315839AE2-212 C
Solar/Wind Harmer
0.617
3151081ELIZAR1
Adder
16.659
3151091ELIZAR2
Adder
16.37
316316AC1-027 C
Solar/Wind Harmer
0.625
970657AG2-426 GEN
Solar/Wind Harmer
1.283
315814AE2-033 C
Solar/Wind Harmer
18.914
316018AA1-139 ULT2
Solar/Wind Harmer
1.732
957871AF2-081 GEN
Solar/Wind Harmer
10.135
316236AE1-162_GEN
Solar/Wind Harmer
0.609
971445AH1-216 GEN
Solar/Wind Harmer
12.534
315833AF1-017_GEN
Solar/Wind Harmer
3.838
3146406KITTY HAWK
Solar/Wind Harmer
0.017
316311AC2-079 GEN
Solar/Wind Harmer
10.193
3151201GRAVEL4
Adder
13.067
3151221GRAVEL6
Adder
13.052
3151191GRAVEL3
Adder
12.901
3151211GRAVEL5
Adder
12.901
315697AD1-025 GEN
Solar/Wind Harmer
4.066
313526AB2-022
Solar/Wind Harmer
0.54
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146396TANGLEW
Solar/Wind Harmer
0.368
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
316382AG1-145 C
Solar/Wind Harmer
0.589
316159AE1-175 C
Solar/Wind Harmer
0.525
970085AG2-068 GEN
Solar/Wind Harmer
12.213
970581AG2-369 GEN
Solar/Wind Harmer
10.504
315800Z1-036_GEN1
Solar/Wind Harmer
4.808
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
957831AF2-077 GEN
Solar/Wind Harmer
0.576
3138283WHITEMARSH
Solar/Wind Harmer
0.03
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
315732AD1-074 GEN1
Solar/Wind Harmer
3.774
315733AD1-074 GEN2
Solar/Wind Harmer
3.774
316318V4-068
Solar/Wind Harmer
0.463
3145893MURPHYS
Solar/Wind Harmer
-0.05
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
8.117
316059AD1-063 C
Solar/Wind Harmer
0.418
946281AF1-292 GEN
Solar/Wind Harmer
0.415
957601AF2-054 GEN
Solar/Wind Harmer
0.553
3152251N ANNA1
50/50
17.125
971507AH1-251 GEN
50/50
12.679
3151791S ANNAG2
50/50
0.914
3151781S ANNAS1
50/50
0.47
3151741LOISA C
50/50
0.971
3151751LOISA D
50/50
17.751
970119AG2-088 GEN
50/50
27.829
3150851SPRUNCC
50/50
0.914
315243AE2-183_GT3
50/50
3.046
3151051BRUNSWICKS1
50/50
4.997
3151021BRUNSWICKG1
50/50
2.407
971451AH1-221 GEN
50/50
7.31
316447AC1-158 HLD
Solar/Wind Harmer
14.763
316044AC1-158 PL1
Solar/Wind Harmer
6.712
316254AC1-120 GEN1
Solar/Wind Harmer
14.319
316170AC1-121 GEN2
Solar/Wind Harmer
4.773
3147666LOUISA
Solar/Wind Harmer
-0.136
316192AB2-158 GEN
Solar/Wind Harmer
4.022
315683AE1-153 C
Solar/Wind Harmer
26.703
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.116
940641AE2-051 GEN
Solar/Wind Harmer
20.408
939411AE1-173 GEN
Solar/Wind Harmer
107.112
941031AE2-094 GEN
Solar/Wind Harmer
39.956
3143336POWHATN
Solar/Wind Harmer
2.493
315773AC2-141 GEN
Solar/Wind Harmer
8.615
944591AF1-124 GEN
Solar/Wind Harmer
93.479
316375AC2-012 GEN
Solar/Wind Harmer
7.056
316036AC1-147 C
Solar/Wind Harmer
0.549
3150981CHESPKA
Adder
2.267
316381AD1-082 GEN
Solar/Wind Harmer
1.863
315671AE2-027_GEN
Solar/Wind Harmer
3.673
3142543TWELFTH
Solar/Wind Harmer
-0.002
3145336SMITFLD
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
-0.02
319010AE1-072 C
Solar/Wind Harmer
4.082
3151171GRAVELC
Adder
1.91
316072AD1-144
Solar/Wind Harmer
0.407
961611AG1-000B GEN
Solar/Wind Harmer
9.95
3151731LOISA B
50/50
17.751
315242AE2-183_GT2
50/50
3.046
315241AE2-183_GT1
50/50
3.038
972185AH1-677 GEN
50/50
11.009
3151041BRUNSWICKG3
50/50
2.407
972187AH1-678 GEN
50/50
5.523
316045AC1-158 PL2
Solar/Wind Harmer
21.478
316450AC1-158 RIC
Solar/Wind Harmer
1.79
966001AG1-469 GEN
Solar/Wind Harmer
0.563
971223AH1-071 GEN
Solar/Wind Harmer
2.931
3143526WINTERP
Solar/Wind Harmer
-0.116
316313AB2-026
Solar/Wind Harmer
0.565
316294AC1-161 GEN
Solar/Wind Harmer
6.658
3150991CHESPKB
Adder
1.902
3150991CHESPKB
Adder
1.857
3144356SAPONY
Solar/Wind Harmer
0.711
316315AB2-025 C
Solar/Wind Harmer
0.548
316185AD1-033 GEN
Solar/Wind Harmer
2.145
316240AF1-291 C
Solar/Wind Harmer
0.613
316083AB2-161 GEN
Solar/Wind Harmer
3.304
316336AC2-165 C
Solar/Wind Harmer
12.714
3145506HICKORY
Solar/Wind Harmer
-0.081
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
944641AF1-129 GEN
Adder
86.254
316339AD2-160 GEN
Solar/Wind Harmer
1.364
316388AE2-253 GEN
Solar/Wind Harmer
1.364
970933AG2-581 GEN
Solar/Wind Harmer
19.014
3137176SLIGO L2192
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.39
316349AD2-085 GEN
Solar/Wind Harmer
1.794
3130086AYDLETT
Solar/Wind Harmer
-0.08
316033AB2-134 GEN
Solar/Wind Harmer
6.488
315835AF2-110_GEN
Solar/Wind Harmer
2.514
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.6
316433W1029_GEN2
Solar/Wind Harmer
3.6
316435W1029_GEN3
Solar/Wind Harmer
3.6
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.574
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3150691DARBY 3
Adder
12.585
3150701DARBY 4
Adder
12.556
3150681DARBY 2
Adder
12.541
3150671DARBY 1
Adder
12.527
3142946ENON
Solar/Wind Harmer
-0.002
3152261N ANNA2
50/50
17.133
3151771S ANNAG1
50/50
0.914
3151801S ANNAS2
50/50
0.47
3151761LOISA E
50/50
36.189
3151721LOISA A
50/50
17.659
3150861SPRUNCD
50/50
0.914
3151031BRUNSWICKG2
50/50
2.407
3147666LOUISA
Solar/Wind Harmer
-0.078
3132273ORANGE
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
12.52
3143336POWHATN
Solar/Wind Harmer
2.119
944581AF1-123 GEN
Solar/Wind Harmer
93.144
944601AF1-125 GEN
Solar/Wind Harmer
91.69
315813AE1-149 C
Solar/Wind Harmer
12.795
3151101ELIZAR3
Adder
16.872
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142956BIRDNECK
Solar/Wind Harmer
1.094
3144536CHRHLND
Solar/Wind Harmer
-0.003
970657AG2-426 GEN
Solar/Wind Harmer
4.111
316017AA1-139 ULT1
Solar/Wind Harmer
1.636
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.342
316305AF2-043 C
Solar/Wind Harmer
0.607
316246AF1-032 C
Solar/Wind Harmer
0.408
3151171GRAVELC
Adder
2.511
961611AG1-000B GEN
Solar/Wind Harmer
4.245
315778AD1-151 GEN
Solar/Wind Harmer
17.929
316458AB2-190 GEN2
Solar/Wind Harmer
2.031
970133AG2-095 GEN
Solar/Wind Harmer
2.264
3143096IRON208
Adder
0.749
3143096IRON208
Adder
0.734
316320Y1-086
Solar/Wind Harmer
1.174
316321Z2-027
Solar/Wind Harmer
0.538
3144216WINCHST
Adder
0.666
3146516WINFALL
Solar/Wind Harmer
-0.02
3150921YORKTN3
Adder
4.429
970917AG2-570 GEN
Solar/Wind Harmer
49.486
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.006
970293AG2-193 GEN
Solar/Wind Harmer
2.436
3146376EDENTON
Solar/Wind Harmer
-0.019
316075AC2-137 C
Solar/Wind Harmer
0.519
3142416OLDCHRC
Solar/Wind Harmer
1.934
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
3156081AA2-088 GEN
Solar/Wind Harmer
6.097
315735AD1-075 GEN1
Solar/Wind Harmer
1.886
3141843SHACKLE
Adder
0.846
316203AE2-005 GEN
Solar/Wind Harmer
7.839
3145893MURPHYS
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
3141766HARMONY
Solar/Wind Harmer
1.65
966621AG1-532 GEN
Solar/Wind Harmer
0.376
3141873WAN 176
Solar/Wind Harmer
2.192
316473AC1-191 GEN
Solar/Wind Harmer
1.984
3146173TUNIS
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.588
316181AB2-040 GEN
Solar/Wind Harmer
2.545
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316011AB1-132 GEN
Solar/Wind Harmer
3.78
316190AA2-174 GEN
Solar/Wind Harmer
0.221
316317KELFORD C
Solar/Wind Harmer
0.831
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.018
942461AE2-259 GEN
Solar/Wind Harmer
2.673
3146776BUCKING
Solar/Wind Harmer
-0.006
3147133PAMPLIN
Solar/Wind Harmer
-0.055
3144293JTRSVLE
Adder
0.374
959311AF2-222 GEN
Solar/Wind Harmer
18.224
970257AG2-171 GEN
Solar/Wind Harmer
6.539
971775AH1-396 GEN
Solar/Wind Harmer
1.23
316212AC1-099_GEN
Solar/Wind Harmer
1.514
316484AD2-074 GEN
Solar/Wind Harmer
4.378
316369SG1_INVT
Solar/Wind Harmer
3.593
971069AG2-661 GEN
Solar/Wind Harmer
3.187
316132AB2-190 GEN1
Solar/Wind Harmer
2.031
316093AE2-104_GEN
Solar/Wind Harmer
5.848
3143096IRON208
Adder
0.749
3138126ROCKLANDING
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
-0.064
3146516WINFALL
Solar/Wind Harmer
-0.02
944631AF1-128 GEN
Adder
84.098
970919AG2-571 GEN
Solar/Wind Harmer
6.264
971317AH1-138 GEN
Solar/Wind Harmer
2.45
970087AG2-069 GEN
Solar/Wind Harmer
18.32
315611Z1-036_GEN2
Solar/Wind Harmer
4.808
3130156CHOWAN
Solar/Wind Harmer
-0.019
315975AC1-164 GENB
Solar/Wind Harmer
0.129
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
957481AF2-042 GEN
Solar/Wind Harmer
59.683
3142433PROV 92
Solar/Wind Harmer
-0.076
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
315816AE2-034 GEN
Solar/Wind Harmer
1.535
3145663CRESWEL
Solar/Wind Harmer
-0.053
971163AH1-040 GEN
Solar/Wind Harmer
17.838
316023GEN1_S
Solar/Wind Harmer
1.271
315693AD1-088 GEN
Solar/Wind Harmer
9.427
970937AG2-583 GEN
Solar/Wind Harmer
13.454
315737AD1-076 GEN
Solar/Wind Harmer
3.548
971777AH1-397 GEN
Solar/Wind Harmer
2.17
316314AB2-024 C
Solar/Wind Harmer
1.587
3145893MURPHYS
Solar/Wind Harmer
-0.074
3145893MURPHYS
Solar/Wind Harmer
0.551
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.638
315662AE1-191 GEN
Solar/Wind Harmer
2.23
316280AD1-041 GEN
Solar/Wind Harmer
1.394
3141766HARMONY
Solar/Wind Harmer
-0.004
960081AF2-299 GEN
Solar/Wind Harmer
2.084
3146173TUNIS
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.614
3156021HOLLOMANSOL
Solar/Wind Harmer
2.464
315607AA1-063A GEN
Solar/Wind Harmer
1.843
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.461
3138133OCRAN
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.007
971563AH1-280 GEN
Solar/Wind Harmer
2.198
3144293JTRSVLE
Adder
0.374
3144293JTRSVLE
Adder
0.295
970685AG2-442 GEN
Solar/Wind Harmer
15.354
316129AC1-054 GEN
Solar/Wind Harmer
1.529
971065AG2-659 GEN
Solar/Wind Harmer
8.723
316034AC1-036 C
Solar/Wind Harmer
0.323
315785AD2-033 C
Solar/Wind Harmer
3.938
316131AB2-060 GEN
Solar/Wind Harmer
1.859
3146293MARTNCO
Solar/Wind Harmer
0.107
962861AG1-135 GEN
Solar/Wind Harmer
6.432
316404AE1-155 C
Solar/Wind Harmer
3.258
958261AF2-120 GEN
Solar/Wind Harmer
6.613
3150351NORNECKC2
Adder
1.463
972197AH1-683 GEN
Adder
2.851
972219AH1-694 GEN
Adder
2.053
3141873WAN 176
Solar/Wind Harmer
-0.004
316486AD2-202 GEN
Solar/Wind Harmer
0.465
3146043SEABORD
Solar/Wind Harmer
-0.018
316463AE2-346 GEN
Solar/Wind Harmer
0.296
3145513AHOSKIE
Solar/Wind Harmer
0.16
961941AG1-037 GEN
Solar/Wind Harmer
0.138
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.072
3138133OCRAN
Solar/Wind Harmer
-0.005
315652AC1-086 GEN
Solar/Wind Harmer
20.363
316426AA2-053 GEN
Solar/Wind Harmer
1.819
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
2.738
971845AH1-439 GEN
Solar/Wind Harmer
9.395
316322AB2-045
Solar/Wind Harmer
0.593
3146033SCOT NK
Solar/Wind Harmer
-0.07
946301AF1-294 GEN
Solar/Wind Harmer
4.506
961791AG1-021 GEN
Solar/Wind Harmer
2.198
970831AG2-522 GEN
Solar/Wind Harmer
8.776
970683AG2-441 GEN
Solar/Wind Harmer
12.37
970681AG2-440 GEN
Solar/Wind Harmer
8.21
3144303KENBRDG
Solar/Wind Harmer
-0.014
316210AC1-098 GEN
Solar/Wind Harmer
2.725
972205AH1-687 GEN
Adder
6.588
316274AC1-208 GEN
Solar/Wind Harmer
1.863
316238AB2-078_GEN
Solar/Wind Harmer
0.518
316239AB2-077_GEN
Solar/Wind Harmer
0.518
3150411LDYSMT5
Adder
18.313
3150381LDYSMT2
Adder
17.526
972213AH1-691 GEN
Adder
2.965
972215AH1-692 GEN
Adder
2.965
961951AG1-038 GEN
Solar/Wind Harmer
2.291
972003AH1-546 GEN
Solar/Wind Harmer
7.054
964241AG1-285 GEN
Solar/Wind Harmer
13.538
3145933PARMELE
Solar/Wind Harmer
-0.017
3150351NORNECKC2
Adder
1.487
3150401LDYSMT4
Adder
18.256
3150371LDYSMT1
Adder
17.64
315722AD1-056 GEN
Solar/Wind Harmer
3.777
315742AE1-103 GEN
Solar/Wind Harmer
4.632
3146376EDENTON
Solar/Wind Harmer
0.575
3146376EDENTON
Solar/Wind Harmer
0.575
3142296MT RD221
Adder
0.545
315976AC1-164 GENA
Solar/Wind Harmer
4.368
316169AC1-164_GENC
Solar/Wind Harmer
3.774
316312AB1-027
Solar/Wind Harmer
0.645
970099AG2-077 GEN
Solar/Wind Harmer
23.873
315614AA2-178 GEN
Solar/Wind Harmer
2.047
316365GEN2_N
Solar/Wind Harmer
1.271
316065AD1-022 GEN
Solar/Wind Harmer
9.303
316441AF1-014 GEN
Solar/Wind Harmer
1.253
3145893MURPHYS
Solar/Wind Harmer
0.518
3145893MURPHYS
Solar/Wind Harmer
-0.033
315666AE1-190 GEN
Solar/Wind Harmer
0.557
316156AD2-030 GEN
Solar/Wind Harmer
0.492
966871AG1-558 GEN
Solar/Wind Harmer
0.554
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316140AB2-099
Solar/Wind Harmer
0.123
970301AG2-198 GEN
Solar/Wind Harmer
9.163
313506AB2-031 GEN
Solar/Wind Harmer
1.465
972189AH1-679 GEN
Adder
2.703
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
962571AG1-106 GEN
Solar/Wind Harmer
2.602
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
0.15
3145783HORNRTN
Solar/Wind Harmer
2.124
3145783HORNRTN
Solar/Wind Harmer
1.699
3145783HORNRTN
Solar/Wind Harmer
0.531
3145783HORNRTN
Solar/Wind Harmer
0.212
3145796HORNRTN
Solar/Wind Harmer
-0.053
3146776BUCKING
Solar/Wind Harmer
-0.07
3146776BUCKING
Solar/Wind Harmer
-0.006
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.748
3144293JTRSVLE
Adder
0.374
970323AG2-213 GEN
Solar/Wind Harmer
8.719
316487AF1-042 GEN
Solar/Wind Harmer
2.291
315687AD1-152 GEN
Solar/Wind Harmer
2.082
313527AB2-043 GEN
Solar/Wind Harmer
2.803
3145933PARMELE
Solar/Wind Harmer
-0.034
3145933PARMELE
Solar/Wind Harmer
-0.017
316237AB2-079_GEN
Solar/Wind Harmer
0.518
3150341NORNECKC1
Adder
1.536
3150341NORNECKC1
Adder
1.524
3150391LDYSMT3
Adder
18.222
972195AH1-682 GEN
Adder
2.395
316006AB2-029 C
Solar/Wind Helper
0.153
315724AD1-057 GEN
Solar/Wind Harmer
2.077
LAGNLTFEXP_LAGN->PJM
CLTF
6.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.688
TVALTFEXP_TVA->PJM
CLTF
3.273
CPLELTFEXP_CPLE->PJM
CLTF
9.477
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.819
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.756
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.074
MECLTFEXP_MEC->PJM
CLTF
2.789
SIGELTFEXP_SIGE->PJM
CLTF
0.085
NYPJM->LTFIMP_NY
CLTF
2.762
LGEELTFEXP_LGEE->PJM
CLTF
1.014
WECLTFEXP_WEC->PJM
CLTF
0.482

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.83 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3730.18
MW Contribution:
4.56
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
16.849
971507AH1-251 GEN
50/50
10.955
970119AG2-088 GEN
50/50
26.735
3150851SPRUNCC
50/50
0.881
315243AE2-183_GT3
50/50
2.933
3151051BRUNSWICKS1
50/50
4.81
3151021BRUNSWICKG1
50/50
2.317
971451AH1-221 GEN
50/50
7.036
3150981CHESPKA
50/50
2.325
316447AC1-158 HLD
Solar/Wind Harmer
6.489
316044AC1-158 PL1
Solar/Wind Harmer
2.951
3147666LOUISA
Solar/Wind Harmer
0.934
316192AB2-158 GEN
Solar/Wind Harmer
1.283
3143226MDLTHAN
Solar/Wind Harmer
0.2
3143526WINTERP
Solar/Wind Harmer
0.994
940641AE2-051 GEN
Solar/Wind Harmer
14.975
939411AE1-173 GEN
Solar/Wind Harmer
78.594
941031AE2-094 GEN
Solar/Wind Harmer
33.689
315773AC2-141 GEN
Solar/Wind Harmer
6.466
944591AF1-124 GEN
Solar/Wind Harmer
39.785
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.031
316381AD1-082 GEN
Solar/Wind Harmer
0.177
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3142543TWELFTH
Solar/Wind Harmer
0.017
3145336SMITFLD
Solar/Wind Harmer
0.697
3146456SLIGO L269
Solar/Wind Harmer
0.174
319010AE1-072 C
Solar/Wind Harmer
0.867
3151171GRAVELC
Adder
1.846
961611AG1-000B GEN
Solar/Wind Harmer
9.095
316072AD1-144
Solar/Wind Harmer
0.062
971069AG2-661 GEN
Solar/Wind Harmer
3.081
316132AB2-190 GEN1
Solar/Wind Harmer
0.924
3143096IRON208
Adder
0.724
316093AE2-104_GEN
Solar/Wind Harmer
2.906
3143336POWHATN
Solar/Wind Harmer
3.07
3138126ROCKLANDING
Solar/Wind Harmer
0.078
944631AF1-128 GEN
Adder
81.325
3146516WINFALL
Solar/Wind Harmer
0.552
3146516WINFALL
Solar/Wind Harmer
0.17
970919AG2-571 GEN
Solar/Wind Harmer
6.024
971317AH1-138 GEN
Solar/Wind Harmer
1.26
970087AG2-069 GEN
Solar/Wind Harmer
13.376
316303AF2-085
50/50
3.565
971285AH1-108 GEN
50/50
1.442
315244AE2-183_ST
50/50
5.094
963041AG1-153 GEN
50/50
4.691
3151081ELIZAR1
50/50
17.079
3151091ELIZAR2
50/50
16.782
941591AE2-156 GEN
50/50
15.607
315779AE2-040
50/50
2.441
316164AC1-076 GEN
Solar/Wind Harmer
0.359
316233AE1-074 FULL
Solar/Wind Harmer
0.153
971281AH1-106 GEN
Solar/Wind Harmer
2.652
971283AH1-107 GEN
Solar/Wind Harmer
2.652
970533AG2-339 GEN
Solar/Wind Harmer
13.82
970673AG2-436 GEN
Solar/Wind Harmer
22.523
3143316POE
Solar/Wind Harmer
0.706
971967AH1-528 GEN
Solar/Wind Harmer
28.253
316316AC1-027 C
Solar/Wind Harmer
0.167
970657AG2-426 GEN
Solar/Wind Harmer
1.285
957871AF2-081 GEN
Solar/Wind Harmer
8.673
315814AE2-033 C
Solar/Wind Harmer
13.784
971445AH1-216 GEN
Solar/Wind Harmer
12.266
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316311AC2-079 GEN
Solar/Wind Harmer
4.986
3151201GRAVEL4
Adder
12.628
3151221GRAVEL6
Adder
12.614
3151191GRAVEL3
Adder
12.468
3151211GRAVEL5
Adder
12.468
315697AD1-025 GEN
Solar/Wind Harmer
0.186
316258AE1-075 C
Solar/Wind Harmer
0.129
313526AB2-022
Solar/Wind Harmer
0.092
3146486SUNBURY
Solar/Wind Harmer
0.172
3146486SUNBURY
Solar/Wind Harmer
0.172
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
0.106
316159AE1-175 C
Solar/Wind Harmer
0.144
970085AG2-068 GEN
Solar/Wind Harmer
8.917
970581AG2-369 GEN
Solar/Wind Harmer
7.669
3130156CHOWAN
Solar/Wind Harmer
0.166
3130156CHOWAN
Solar/Wind Harmer
0.166
3138283WHITEMARSH
Solar/Wind Harmer
0.038
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
3143873LANEXA
Solar/Wind Harmer
0.097
3130546PLYMOUTH
Solar/Wind Harmer
0.16
970189AG2-124 GEN
Solar/Wind Harmer
4.752
315732AD1-074 GEN1
Solar/Wind Harmer
0.912
315733AD1-074 GEN2
Solar/Wind Harmer
0.912
3141873WAN 176
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.429
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
970601AG2-382 GEN
Solar/Wind Harmer
5.929
3141913WHIT STONE
Solar/Wind Harmer
0.157
316463AE2-346 GEN
Solar/Wind Harmer
0.134
3145513AHOSKIE
Solar/Wind Harmer
0.328
3152261N ANNA2
50/50
16.858
3150861SPRUNCD
50/50
0.881
3151031BRUNSWICKG2
50/50
2.317
3151101ELIZAR3
50/50
17.297
3147666LOUISA
Solar/Wind Harmer
0.537
944011AF1-069 GEN
Solar/Wind Harmer
11.007
944581AF1-123 GEN
Solar/Wind Harmer
39.644
944601AF1-125 GEN
Solar/Wind Harmer
39.034
315813AE1-149 C
Solar/Wind Harmer
9.387
3144873MCLAUGH
Solar/Wind Harmer
0.004
3144536CHRHLND
Solar/Wind Harmer
0.026
970657AG2-426 GEN
Solar/Wind Harmer
3.925
3145336SMITFLD
Solar/Wind Harmer
0.07
316017AA1-139 ULT1
Solar/Wind Harmer
0.093
3146456SLIGO L269
Solar/Wind Harmer
0.174
971153AH1-033 GEN
Solar/Wind Harmer
2.01
316246AF1-032 C
Solar/Wind Harmer
0.077
3151171GRAVELC
Adder
2.427
961611AG1-000B GEN
Solar/Wind Harmer
4.624
315778AD1-151 GEN
Solar/Wind Harmer
13.863
316458AB2-190 GEN2
Solar/Wind Harmer
0.924
970133AG2-095 GEN
Solar/Wind Harmer
1.662
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.709
3143336POWHATN
Solar/Wind Harmer
2.609
316321Z2-027
Solar/Wind Harmer
0.031
3144216WINCHST
Adder
0.644
3150921YORKTN3
Adder
4.284
3146516WINFALL
Solar/Wind Harmer
0.17
970917AG2-570 GEN
Solar/Wind Harmer
15.059
3146626S HERTFORD
Solar/Wind Harmer
0.169
3142946ENON
Solar/Wind Harmer
0.057
3145273HOLLAND
Solar/Wind Harmer
0.127
970293AG2-193 GEN
Solar/Wind Harmer
1.79
316075AC2-137 C
Solar/Wind Harmer
0.044
3146376EDENTON
Solar/Wind Harmer
0.166
3142416OLDCHRC
Solar/Wind Harmer
1.601
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
3156081AA2-088 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.819
316203AE2-005 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.456
3141766HARMONY
Solar/Wind Harmer
2.132
3141873WAN 176
Solar/Wind Harmer
2.833
316473AC1-191 GEN
Solar/Wind Harmer
0.537
3145513AHOSKIE
Solar/Wind Harmer
0.157
3146043SEABORD
Solar/Wind Harmer
0.156
3138133OCRAN
Solar/Wind Harmer
0.047
3145683EARLEYS
Solar/Wind Harmer
0.312
3145683EARLEYS
Solar/Wind Harmer
0.156
3145683EARLEYS
Solar/Wind Harmer
0.156
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3141783LANCAST
Solar/Wind Harmer
0.093
3141783LANCAST
Solar/Wind Harmer
0.062
315652AC1-086 GEN
Solar/Wind Harmer
16.992
3137643SOCKMAN
Solar/Wind Harmer
0.617
316426AA2-053 GEN
Solar/Wind Harmer
0.515
3145796HORNRTN
Solar/Wind Harmer
0.487
3145796HORNRTN
Solar/Wind Harmer
0.061
3146033SCOT NK
Solar/Wind Harmer
0.602
970831AG2-522 GEN
Solar/Wind Harmer
6.339
316210AC1-098 GEN
Solar/Wind Harmer
1.371
316274AC1-208 GEN
Solar/Wind Harmer
0.76
3145746EVERETS
Solar/Wind Harmer
0.575
3145893MURPHYS
Solar/Wind Harmer
0.266
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
3132273ORANGE
Solar/Wind Harmer
0.032
3146173TUNIS
Solar/Wind Harmer
0.157
316181AB2-040 GEN
Solar/Wind Harmer
0.221
316478AD1-087 GEN
Solar/Wind Harmer
0.538
3146263WOODLND
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
316011AB1-132 GEN
Solar/Wind Harmer
2.802
3147043LAWRENC
Solar/Wind Harmer
0.092
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.608
3145796HORNRTN
Solar/Wind Harmer
0.152
316212AC1-099_GEN
Solar/Wind Harmer
0.765
3145933PARMELE
Solar/Wind Harmer
0.147
315722AD1-056 GEN
Solar/Wind Harmer
4.998
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
964241AG1-285 GEN
Solar/Wind Harmer
9.615
970257AG2-171 GEN
Solar/Wind Harmer
4.61
971775AH1-396 GEN
Solar/Wind Harmer
0.23
959311AF2-222 GEN
Solar/Wind Harmer
12.803
3144293JTRSVLE
Adder
0.343
3147133PAMPLIN
Solar/Wind Harmer
0.451
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.086
3150351NORNECKC2
Adder
1.447
3151761LOISA E
Adder
18.814
3151721LOISA A
Adder
9.181
3146233WITAKRS
Solar/Wind Harmer
0.707
3146233WITAKRS
Solar/Wind Harmer
0.096
3146073TAR RVR
Solar/Wind Harmer
0.14
3146083TARBORO
Solar/Wind Harmer
0.14
3138543CONSLDL
Solar/Wind Harmer
0.093
961601AG1-000A GEN
Solar/Wind Harmer
9.845
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.138
971623AH1-311 GEN
Solar/Wind Harmer
0.277
3146776BUCKING
Solar/Wind Harmer
0.05
3150401LDYSMT4
Adder
18.084
3150371LDYSMT1
Adder
17.474
971781AH1-399 GEN
Solar/Wind Harmer
0.177
972003AH1-546 GEN
Solar/Wind Harmer
4.563
316223AC1-118
Solar/Wind Harmer
0.09
3141906WESTMOR
Solar/Wind Harmer
0.051
970221AG2-151 GEN
Solar/Wind Harmer
6.511
971683AH1-343 GEN
Solar/Wind Harmer
4.395
316222AC1-221 GEN
Solar/Wind Harmer
0.488
316283AC2-100 C
Solar/Wind Harmer
0.231
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
3144303KENBRDG
Solar/Wind Harmer
0.115
970683AG2-441 GEN
Solar/Wind Harmer
8.676
970681AG2-440 GEN
Solar/Wind Harmer
5.758
946301AF1-294 GEN
Solar/Wind Harmer
2.839
961791AG1-021 GEN
Solar/Wind Harmer
1.381
316327AA2-057 GEN
Solar/Wind Harmer
0.212
3141813NORNECK
Solar/Wind Harmer
0.143
957861AF2-080 GEN
Solar/Wind Harmer
6.139
3145573BETHELC
Solar/Wind Harmer
0.14
3145573BETHELC
Solar/Wind Harmer
0.14
971845AH1-439 GEN
Solar/Wind Harmer
6.264
3150411LDYSMT5
Adder
18.14
3150381LDYSMT2
Adder
17.361
972213AH1-691 GEN
Adder
2.937
972215AH1-692 GEN
Adder
2.937
3147346CASHSCORNER
Solar/Wind Harmer
0.311
3147173SINAI
Solar/Wind Harmer
0.131
3147243WELCO
Solar/Wind Harmer
0.082
972205AH1-687 GEN
Adder
5.588
3130156CHOWAN
Solar/Wind Harmer
0.166
315975AC1-164 GENB
Solar/Wind Harmer
0.052
3142416OLDCHRC
Solar/Wind Harmer
0.429
3142416OLDCHRC
Solar/Wind Harmer
0.164
3142433PROV 92
Solar/Wind Harmer
0.657
3142433PROV 92
Adder
0.319
3142433PROV 92
Adder
0.319
315816AE2-034 GEN
Solar/Wind Harmer
0.696
3145663CRESWEL
Solar/Wind Harmer
0.456
971163AH1-040 GEN
Solar/Wind Harmer
13.046
957481AF2-042 GEN
Solar/Wind Harmer
43.129
316023GEN1_S
Solar/Wind Harmer
0.359
971777AH1-397 GEN
Solar/Wind Harmer
0.423
315737AD1-076 GEN
Solar/Wind Harmer
2.054
3141766HARMONY
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.635
3145893MURPHYS
Solar/Wind Harmer
0.706
3146206CASHIE
Solar/Wind Harmer
0.159
971547AH1-271 GEN
Solar/Wind Harmer
3.388
315693AD1-088 GEN
Solar/Wind Harmer
7.611
960081AF2-299 GEN
Solar/Wind Harmer
1.515
3146173TUNIS
Solar/Wind Harmer
0.157
3156021HOLLOMANSOL
Solar/Wind Harmer
0.706
3138133OCRAN
Solar/Wind Harmer
0.094
315607AA1-063A GEN
Solar/Wind Harmer
0.314
3145683EARLEYS
Solar/Wind Harmer
0.156
3146263WOODLND
Solar/Wind Harmer
0.155
3147043LAWRENC
Adder
1.39
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145783HORNRTN
Solar/Wind Harmer
0.152
3145796HORNRTN
Solar/Wind Harmer
0.502
3145796HORNRTN
Solar/Wind Harmer
0.152
962861AG1-135 GEN
Solar/Wind Harmer
4.747
316129AC1-054 GEN
Solar/Wind Harmer
0.552
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
4.881
971065AG2-659 GEN
Solar/Wind Harmer
6.291
3146293MARTNCO
Solar/Wind Harmer
0.137
970937AG2-583 GEN
Solar/Wind Harmer
8.995
966881AG1-559 GEN
Solar/Wind Harmer
0.168
3141726DUNNSVL
Solar/Wind Harmer
0.579
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
316131AB2-060 GEN
Solar/Wind Harmer
0.449
315785AD2-033 C
Solar/Wind Harmer
1.165
316034AC1-036 C
Solar/Wind Harmer
0.01
316254AC1-120 GEN1
Solar/Wind Harmer
5.066
316170AC1-121 GEN2
Solar/Wind Harmer
1.74
970685AG2-442 GEN
Solar/Wind Harmer
10.745
971563AH1-280 GEN
Solar/Wind Harmer
1.534
3144293JTRSVLE
Adder
0.343
3144293JTRSVLE
Adder
0.271
3146926FARMVIL
Solar/Wind Harmer
0.086
3150351NORNECKC2
Adder
1.423
316494AC1-189 GEN
Solar/Wind Harmer
0.481
3151751LOISA D
Adder
9.228
3146233WITAKRS
Solar/Wind Harmer
0.561
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.14
3145493TOT1
Solar/Wind Harmer
0.625
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.111
316359AB2-059 GEN
Solar/Wind Harmer
0.492
3142053HEARTS
Solar/Wind Harmer
0.244
3146776BUCKING
Solar/Wind Harmer
0.055
970401AG2-262 GEN
Solar/Wind Harmer
0.802
316337AD2-073 GEN
Solar/Wind Harmer
0.116
972197AH1-683 GEN
Adder
2.824
972219AH1-694 GEN
Adder
2.033
971377AH1-170 GEN
Solar/Wind Harmer
1.302
3147623JAMES R
Solar/Wind Harmer
0.283
972135AH1-637 GEN
Solar/Wind Harmer
0.975
315242AE2-183_GT2
50/50
2.933
315241AE2-183_GT1
50/50
2.925
972185AH1-677 GEN
50/50
10.603
3151041BRUNSWICKG3
50/50
2.317
972187AH1-678 GEN
50/50
5.316
3150991CHESPKB
50/50
1.95
3150991CHESPKB
50/50
1.903
316045AC1-158 PL2
Solar/Wind Harmer
9.443
316450AC1-158 RIC
Solar/Wind Harmer
0.787
971223AH1-071 GEN
Solar/Wind Harmer
2.139
3143526WINTERP
Solar/Wind Harmer
0.994
316294AC1-161 GEN
Solar/Wind Harmer
3.06
3145506HICKORY
Solar/Wind Harmer
0.699
3145506HICKORY
Solar/Wind Harmer
0.42
3145506HICKORY
Solar/Wind Harmer
0.105
3144356SAPONY
Solar/Wind Harmer
1.463
316315AB2-025 C
Solar/Wind Harmer
0.14
944641AF1-129 GEN
Adder
83.354
316339AD2-160 GEN
Solar/Wind Harmer
0.279
316388AE2-253 GEN
Solar/Wind Harmer
0.543
3137176SLIGO L2192
Solar/Wind Harmer
0.692
3146456SLIGO L269
Solar/Wind Harmer
3.077
3130086AYDLETT
Solar/Wind Harmer
0.694
316349AD2-085 GEN
Solar/Wind Harmer
0.116
316033AB2-134 GEN
Solar/Wind Harmer
0.001
970933AG2-581 GEN
Solar/Wind Harmer
13.846
315835AF2-110_GEN
Solar/Wind Harmer
1.186
316313AB2-026
Solar/Wind Harmer
0.107
3146386ELIZ CT
Solar/Wind Harmer
0.172
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3142366NRTHEST
Adder
0.555
3146626S HERTFORD
Solar/Wind Harmer
0.169
3146626S HERTFORD
Solar/Wind Harmer
0.169
3150691DARBY 3
Adder
12.175
3150701DARBY 4
Adder
12.147
3150681DARBY 2
Adder
12.133
3150671DARBY 1
Adder
12.119
3142946ENON
Solar/Wind Harmer
0.017
315742AE1-103 GEN
Solar/Wind Harmer
2.499
3146376EDENTON
Solar/Wind Harmer
0.739
3146376EDENTON
Solar/Wind Harmer
0.739
3142296MT RD221
Adder
0.528
315976AC1-164 GENA
Solar/Wind Harmer
1.741
316169AC1-164_GENC
Solar/Wind Harmer
1.505
316336AC2-165 C
Solar/Wind Harmer
8.379
316312AB1-027
Solar/Wind Harmer
0.294
315614AA2-178 GEN
Solar/Wind Harmer
0.928
970099AG2-077 GEN
Solar/Wind Harmer
17.252
316365GEN2_N
Solar/Wind Harmer
0.359
316156AD2-030 GEN
Solar/Wind Harmer
0.117
316065AD1-022 GEN
Solar/Wind Harmer
7.335
966871AG1-558 GEN
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
1.062
3145893MURPHYS
Solar/Wind Harmer
0.286
3146173TUNIS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.157
972189AH1-679 GEN
Adder
2.631
316140AB2-099
Solar/Wind Harmer
0.056
313506AB2-031 GEN
Solar/Wind Harmer
0.477
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.093
962571AG1-106 GEN
Solar/Wind Harmer
2.198
3145593CAROLNA
Solar/Wind Harmer
0.153
3145593CAROLNA
Solar/Wind Harmer
0.153
3145593CAROLNA
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
2.711
3145783HORNRTN
Solar/Wind Harmer
2.168
3145783HORNRTN
Solar/Wind Harmer
0.678
3145783HORNRTN
Solar/Wind Harmer
0.271
3145796HORNRTN
Solar/Wind Harmer
0.456
970301AG2-198 GEN
Solar/Wind Harmer
6.393
3145933PARMELE
Solar/Wind Harmer
0.294
3145933PARMELE
Solar/Wind Harmer
0.147
315724AD1-057 GEN
Solar/Wind Harmer
2.788
316005AA1-067
Solar/Wind Harmer
0.154
970323AG2-213 GEN
Solar/Wind Harmer
6.147
958211AF2-115 GEN
Solar/Wind Harmer
1.726
3144293JTRSVLE
Adder
0.343
3147133PAMPLIN
Solar/Wind Harmer
0.144
3147133PAMPLIN
Solar/Wind Harmer
0.115
3150341NORNECKC1
Adder
1.495
3150341NORNECKC1
Adder
1.483
966001AG1-469 GEN
Solar/Wind Harmer
0.083
3151731LOISA B
Adder
9.228
315673AE1-157 GEN
Solar/Wind Harmer
9.777
3145493TOT1
Solar/Wind Harmer
0.326
3145453TOT5
Solar/Wind Harmer
0.195
3145603CNETO
Solar/Wind Harmer
0.13
961601AG1-000A GEN
Solar/Wind Harmer
2.461
316049AB1-081 GEN
Solar/Wind Harmer
0.787
316263AC1-034 GEN
Solar/Wind Harmer
5.259
962561AG1-105 GEN
Solar/Wind Harmer
6.62
3146776BUCKING
Solar/Wind Harmer
0.55
3146776BUCKING
Solar/Wind Harmer
0.045
964791AG1-342 GEN
Solar/Wind Harmer
2.626
3146843MT LREL
Solar/Wind Harmer
0.137
3146843MT LREL
Solar/Wind Harmer
0.137
3150391LDYSMT3
Adder
18.05
972195AH1-682 GEN
Adder
2.372
316118AC1-105 GEN
Solar/Wind Harmer
0.343
LAGNLTFEXP_LAGN->PJM
CLTF
5.944
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.49
TVALTFEXP_TVA->PJM
CLTF
3.011
CPLELTFEXP_CPLE->PJM
CLTF
8.989
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.916
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.684
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.151
MECLTFEXP_MEC->PJM
CLTF
2.494
SIGELTFEXP_SIGE->PJM
CLTF
0.075
NYPJM->LTFIMP_NY
CLTF
2.553
LGEELTFEXP_LGEE->PJM
CLTF
0.894
WECLTFEXP_WEC->PJM
CLTF
0.423

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2-2199_SRT-A-2


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.74 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4560.31
MW Contribution:
7.05
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.71
971285AH1-108 GEN
50/50
1.495
315244AE2-183_ST
50/50
5.289
963041AG1-153 GEN
50/50
4.873
316164AC1-076 GEN
Solar/Wind Harmer
3.456
315651AD1-115 GEN
Solar/Wind Harmer
16.764
3147346CASHSCORNER
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.6
971281AH1-106 GEN
Solar/Wind Harmer
3.628
971283AH1-107 GEN
Solar/Wind Harmer
3.628
970533AG2-339 GEN
Solar/Wind Harmer
14.33
970673AG2-436 GEN
Solar/Wind Harmer
46.15
316258AE1-075 C
Solar/Wind Harmer
0.508
316405AF2-144 C
Solar/Wind Harmer
0.537
3143316POE
Solar/Wind Harmer
-0.082
971967AH1-528 GEN
Solar/Wind Harmer
38.809
315839AE2-212 C
Solar/Wind Harmer
0.617
3151081ELIZAR1
Adder
16.659
3151091ELIZAR2
Adder
16.37
316316AC1-027 C
Solar/Wind Harmer
0.625
970657AG2-426 GEN
Solar/Wind Harmer
1.283
315814AE2-033 C
Solar/Wind Harmer
18.914
316018AA1-139 ULT2
Solar/Wind Harmer
1.732
957871AF2-081 GEN
Solar/Wind Harmer
10.135
316236AE1-162_GEN
Solar/Wind Harmer
0.609
971445AH1-216 GEN
Solar/Wind Harmer
12.534
315833AF1-017_GEN
Solar/Wind Harmer
3.838
3146406KITTY HAWK
Solar/Wind Harmer
0.017
316311AC2-079 GEN
Solar/Wind Harmer
10.193
3151201GRAVEL4
Adder
13.067
3151221GRAVEL6
Adder
13.052
3151191GRAVEL3
Adder
12.901
3151211GRAVEL5
Adder
12.901
315697AD1-025 GEN
Solar/Wind Harmer
4.066
313526AB2-022
Solar/Wind Harmer
0.54
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146396TANGLEW
Solar/Wind Harmer
0.368
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
316382AG1-145 C
Solar/Wind Harmer
0.589
316159AE1-175 C
Solar/Wind Harmer
0.525
970085AG2-068 GEN
Solar/Wind Harmer
12.213
970581AG2-369 GEN
Solar/Wind Harmer
10.504
315800Z1-036_GEN1
Solar/Wind Harmer
4.808
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
957831AF2-077 GEN
Solar/Wind Harmer
0.576
3138283WHITEMARSH
Solar/Wind Harmer
0.03
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
315732AD1-074 GEN1
Solar/Wind Harmer
3.774
315733AD1-074 GEN2
Solar/Wind Harmer
3.774
316318V4-068
Solar/Wind Harmer
0.463
3145893MURPHYS
Solar/Wind Harmer
-0.05
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
8.117
316059AD1-063 C
Solar/Wind Harmer
0.418
946281AF1-292 GEN
Solar/Wind Harmer
0.415
957601AF2-054 GEN
Solar/Wind Harmer
0.553
3141873WAN 176
Solar/Wind Harmer
-0.004
316486AD2-202 GEN
Solar/Wind Harmer
0.465
3146043SEABORD
Solar/Wind Harmer
-0.018
316463AE2-346 GEN
Solar/Wind Harmer
0.296
3145513AHOSKIE
Solar/Wind Harmer
0.16
961941AG1-037 GEN
Solar/Wind Harmer
0.138
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3152251N ANNA1
50/50
17.125
971507AH1-251 GEN
50/50
12.679
3151791S ANNAG2
50/50
0.914
3151781S ANNAS1
50/50
0.47
3151741LOISA C
50/50
0.971
3151751LOISA D
50/50
17.751
970119AG2-088 GEN
50/50
27.829
3150851SPRUNCC
50/50
0.914
315243AE2-183_GT3
50/50
3.046
3151051BRUNSWICKS1
50/50
4.997
3151021BRUNSWICKG1
50/50
2.407
971451AH1-221 GEN
50/50
7.31
316447AC1-158 HLD
Solar/Wind Harmer
14.763
316044AC1-158 PL1
Solar/Wind Harmer
6.712
316254AC1-120 GEN1
Solar/Wind Harmer
14.319
316170AC1-121 GEN2
Solar/Wind Harmer
4.773
3147666LOUISA
Solar/Wind Harmer
-0.136
316192AB2-158 GEN
Solar/Wind Harmer
4.022
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.116
940641AE2-051 GEN
Solar/Wind Harmer
20.408
939411AE1-173 GEN
Solar/Wind Harmer
107.112
941031AE2-094 GEN
Solar/Wind Harmer
39.956
3143336POWHATN
Solar/Wind Harmer
2.493
315773AC2-141 GEN
Solar/Wind Harmer
8.615
944591AF1-124 GEN
Solar/Wind Harmer
93.479
316375AC2-012 GEN
Solar/Wind Harmer
7.056
316036AC1-147 C
Solar/Wind Harmer
0.549
3150981CHESPKA
Adder
2.267
316381AD1-082 GEN
Solar/Wind Harmer
1.863
315671AE2-027_GEN
Solar/Wind Harmer
3.673
3142543TWELFTH
Solar/Wind Harmer
-0.002
3145336SMITFLD
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
-0.02
319010AE1-072 C
Solar/Wind Harmer
4.082
3151171GRAVELC
Adder
1.91
316072AD1-144
Solar/Wind Harmer
0.407
961611AG1-000B GEN
Solar/Wind Harmer
9.95
316369SG1_INVT
Solar/Wind Harmer
3.593
971069AG2-661 GEN
Solar/Wind Harmer
3.187
316132AB2-190 GEN1
Solar/Wind Harmer
2.031
316093AE2-104_GEN
Solar/Wind Harmer
5.848
3143096IRON208
Adder
0.749
3138126ROCKLANDING
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
-0.064
3146516WINFALL
Solar/Wind Harmer
-0.02
944631AF1-128 GEN
Adder
84.098
970919AG2-571 GEN
Solar/Wind Harmer
6.264
971317AH1-138 GEN
Solar/Wind Harmer
2.45
970087AG2-069 GEN
Solar/Wind Harmer
18.32
315611Z1-036_GEN2
Solar/Wind Harmer
4.808
3130156CHOWAN
Solar/Wind Harmer
-0.019
315975AC1-164 GENB
Solar/Wind Harmer
0.129
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
957481AF2-042 GEN
Solar/Wind Harmer
59.683
3152261N ANNA2
50/50
17.133
3151771S ANNAG1
50/50
0.914
3151801S ANNAS2
50/50
0.47
3151761LOISA E
50/50
36.189
3151721LOISA A
50/50
17.659
3150861SPRUNCD
50/50
0.914
3151031BRUNSWICKG2
50/50
2.407
3147666LOUISA
Solar/Wind Harmer
-0.078
3132273ORANGE
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
12.52
3143336POWHATN
Solar/Wind Harmer
2.119
944581AF1-123 GEN
Solar/Wind Harmer
93.144
944601AF1-125 GEN
Solar/Wind Harmer
91.69
315813AE1-149 C
Solar/Wind Harmer
12.795
3151101ELIZAR3
Adder
16.872
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142956BIRDNECK
Solar/Wind Harmer
1.094
3144536CHRHLND
Solar/Wind Harmer
-0.003
970657AG2-426 GEN
Solar/Wind Harmer
4.111
316017AA1-139 ULT1
Solar/Wind Harmer
1.636
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.342
316305AF2-043 C
Solar/Wind Harmer
0.607
316246AF1-032 C
Solar/Wind Harmer
0.408
3151171GRAVELC
Adder
2.511
961611AG1-000B GEN
Solar/Wind Harmer
4.245
315778AD1-151 GEN
Solar/Wind Harmer
17.929
316458AB2-190 GEN2
Solar/Wind Harmer
2.031
970133AG2-095 GEN
Solar/Wind Harmer
2.264
3143096IRON208
Adder
0.749
3143096IRON208
Adder
0.734
316320Y1-086
Solar/Wind Harmer
1.174
316321Z2-027
Solar/Wind Harmer
0.538
3144216WINCHST
Adder
0.666
3146516WINFALL
Solar/Wind Harmer
-0.02
3150921YORKTN3
Adder
4.429
970917AG2-570 GEN
Solar/Wind Harmer
49.486
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.006
970293AG2-193 GEN
Solar/Wind Harmer
2.436
3146376EDENTON
Solar/Wind Harmer
-0.019
316075AC2-137 C
Solar/Wind Harmer
0.519
3142416OLDCHRC
Solar/Wind Harmer
1.934
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
3156081AA2-088 GEN
Solar/Wind Harmer
6.097
315735AD1-075 GEN1
Solar/Wind Harmer
1.886
3141843SHACKLE
Adder
0.846
316203AE2-005 GEN
Solar/Wind Harmer
7.839
3145893MURPHYS
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
3141766HARMONY
Solar/Wind Harmer
1.65
3151731LOISA B
50/50
17.751
315242AE2-183_GT2
50/50
3.046
315241AE2-183_GT1
50/50
3.038
972185AH1-677 GEN
50/50
11.009
3151041BRUNSWICKG3
50/50
2.407
972187AH1-678 GEN
50/50
5.523
316045AC1-158 PL2
Solar/Wind Harmer
21.478
316450AC1-158 RIC
Solar/Wind Harmer
1.79
966001AG1-469 GEN
Solar/Wind Harmer
0.563
971223AH1-071 GEN
Solar/Wind Harmer
2.931
3143526WINTERP
Solar/Wind Harmer
-0.116
316313AB2-026
Solar/Wind Harmer
0.565
316294AC1-161 GEN
Solar/Wind Harmer
6.658
3150991CHESPKB
Adder
1.902
3150991CHESPKB
Adder
1.857
3144356SAPONY
Solar/Wind Harmer
0.711
316315AB2-025 C
Solar/Wind Harmer
0.548
316185AD1-033 GEN
Solar/Wind Harmer
2.145
316240AF1-291 C
Solar/Wind Harmer
0.613
316083AB2-161 GEN
Solar/Wind Harmer
3.304
316336AC2-165 C
Solar/Wind Harmer
12.714
3145506HICKORY
Solar/Wind Harmer
-0.081
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
944641AF1-129 GEN
Adder
86.254
316339AD2-160 GEN
Solar/Wind Harmer
1.364
316388AE2-253 GEN
Solar/Wind Harmer
1.364
970933AG2-581 GEN
Solar/Wind Harmer
19.014
3137176SLIGO L2192
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.39
316349AD2-085 GEN
Solar/Wind Harmer
1.794
3130086AYDLETT
Solar/Wind Harmer
-0.08
316033AB2-134 GEN
Solar/Wind Harmer
6.488
315835AF2-110_GEN
Solar/Wind Harmer
2.514
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.6
316433W1029_GEN2
Solar/Wind Harmer
3.6
316435W1029_GEN3
Solar/Wind Harmer
3.6
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.574
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3150691DARBY 3
Adder
12.585
3150701DARBY 4
Adder
12.556
3150681DARBY 2
Adder
12.541
3150671DARBY 1
Adder
12.527
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
4.632
3146376EDENTON
Solar/Wind Harmer
0.575
3146376EDENTON
Solar/Wind Harmer
0.575
3142296MT RD221
Adder
0.545
315976AC1-164 GENA
Solar/Wind Harmer
4.368
316169AC1-164_GENC
Solar/Wind Harmer
3.774
316312AB1-027
Solar/Wind Harmer
0.645
970099AG2-077 GEN
Solar/Wind Harmer
23.873
315614AA2-178 GEN
Solar/Wind Harmer
2.047
316365GEN2_N
Solar/Wind Harmer
1.271
316065AD1-022 GEN
Solar/Wind Harmer
9.303
316441AF1-014 GEN
Solar/Wind Harmer
1.253
3145893MURPHYS
Solar/Wind Harmer
0.518
3145893MURPHYS
Solar/Wind Harmer
-0.033
315666AE1-190 GEN
Solar/Wind Harmer
0.557
316156AD2-030 GEN
Solar/Wind Harmer
0.492
966871AG1-558 GEN
Solar/Wind Harmer
0.554
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316140AB2-099
Solar/Wind Harmer
0.123
970301AG2-198 GEN
Solar/Wind Harmer
9.163
313506AB2-031 GEN
Solar/Wind Harmer
1.465
972189AH1-679 GEN
Adder
2.703
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142433PROV 92
Solar/Wind Harmer
-0.076
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
315816AE2-034 GEN
Solar/Wind Harmer
1.535
3145663CRESWEL
Solar/Wind Harmer
-0.053
971163AH1-040 GEN
Solar/Wind Harmer
17.838
316023GEN1_S
Solar/Wind Harmer
1.271
315693AD1-088 GEN
Solar/Wind Harmer
9.427
970937AG2-583 GEN
Solar/Wind Harmer
13.454
315737AD1-076 GEN
Solar/Wind Harmer
3.548
971777AH1-397 GEN
Solar/Wind Harmer
2.17
316314AB2-024 C
Solar/Wind Harmer
1.587
3145893MURPHYS
Solar/Wind Harmer
-0.074
3145893MURPHYS
Solar/Wind Harmer
0.551
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.638
315662AE1-191 GEN
Solar/Wind Harmer
2.23
316280AD1-041 GEN
Solar/Wind Harmer
1.394
3141766HARMONY
Solar/Wind Harmer
-0.004
960081AF2-299 GEN
Solar/Wind Harmer
2.084
3146173TUNIS
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.614
3156021HOLLOMANSOL
Solar/Wind Harmer
2.464
315607AA1-063A GEN
Solar/Wind Harmer
1.843
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.461
3138133OCRAN
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.007
971563AH1-280 GEN
Solar/Wind Harmer
2.198
3144293JTRSVLE
Adder
0.374
3144293JTRSVLE
Adder
0.295
970685AG2-442 GEN
Solar/Wind Harmer
15.354
316129AC1-054 GEN
Solar/Wind Harmer
1.529
971065AG2-659 GEN
Solar/Wind Harmer
8.723
316034AC1-036 C
Solar/Wind Harmer
0.323
315785AD2-033 C
Solar/Wind Harmer
3.938
316131AB2-060 GEN
Solar/Wind Harmer
1.859
3146293MARTNCO
Solar/Wind Harmer
0.107
962861AG1-135 GEN
Solar/Wind Harmer
6.432
316404AE1-155 C
Solar/Wind Harmer
3.258
958261AF2-120 GEN
Solar/Wind Harmer
6.613
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
964211AG1-282 GEN
Solar/Wind Harmer
0.503
3141726DUNNSVL
Solar/Wind Harmer
-0.067
316494AC1-189 GEN
Solar/Wind Harmer
1.798
966881AG1-559 GEN
Solar/Wind Harmer
0.171
3150351NORNECKC2
Adder
1.463
972197AH1-683 GEN
Adder
2.851
972219AH1-694 GEN
Adder
2.053
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.072
3138133OCRAN
Solar/Wind Harmer
-0.005
315652AC1-086 GEN
Solar/Wind Harmer
20.363
316426AA2-053 GEN
Solar/Wind Harmer
1.819
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
2.738
971845AH1-439 GEN
Solar/Wind Harmer
9.395
316322AB2-045
Solar/Wind Harmer
0.593
3146033SCOT NK
Solar/Wind Harmer
-0.07
946301AF1-294 GEN
Solar/Wind Harmer
4.506
961791AG1-021 GEN
Solar/Wind Harmer
2.198
970831AG2-522 GEN
Solar/Wind Harmer
8.776
970683AG2-441 GEN
Solar/Wind Harmer
12.37
970681AG2-440 GEN
Solar/Wind Harmer
8.21
3144303KENBRDG
Solar/Wind Harmer
-0.014
316210AC1-098 GEN
Solar/Wind Harmer
2.725
966621AG1-532 GEN
Solar/Wind Harmer
0.376
3141873WAN 176
Solar/Wind Harmer
2.192
316473AC1-191 GEN
Solar/Wind Harmer
1.984
3146173TUNIS
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.588
316181AB2-040 GEN
Solar/Wind Harmer
2.545
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316011AB1-132 GEN
Solar/Wind Harmer
3.78
316190AA2-174 GEN
Solar/Wind Harmer
0.221
316317KELFORD C
Solar/Wind Harmer
0.831
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.018
942461AE2-259 GEN
Solar/Wind Harmer
2.673
3146776BUCKING
Solar/Wind Harmer
-0.006
3147133PAMPLIN
Solar/Wind Harmer
-0.055
972205AH1-687 GEN
Adder
6.588
316274AC1-208 GEN
Solar/Wind Harmer
1.863
316238AB2-078_GEN
Solar/Wind Harmer
0.518
316239AB2-077_GEN
Solar/Wind Harmer
0.518
3145746EVERETS
Solar/Wind Harmer
-0.067
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
316327AA2-057 GEN
Solar/Wind Harmer
1.696
957861AF2-080 GEN
Solar/Wind Harmer
7.309
3150411LDYSMT5
Adder
18.313
3150381LDYSMT2
Adder
17.526
972213AH1-691 GEN
Adder
2.965
972215AH1-692 GEN
Adder
2.965
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
962571AG1-106 GEN
Solar/Wind Harmer
2.602
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
0.15
3145783HORNRTN
Solar/Wind Harmer
2.124
3145783HORNRTN
Solar/Wind Harmer
1.699
3145783HORNRTN
Solar/Wind Harmer
0.531
3145783HORNRTN
Solar/Wind Harmer
0.212
3145796HORNRTN
Solar/Wind Harmer
-0.053
3146776BUCKING
Solar/Wind Harmer
-0.07
3146776BUCKING
Solar/Wind Harmer
-0.006
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.748
3144293JTRSVLE
Adder
0.374
970323AG2-213 GEN
Solar/Wind Harmer
8.719
316487AF1-042 GEN
Solar/Wind Harmer
2.291
315687AD1-152 GEN
Solar/Wind Harmer
2.082
313527AB2-043 GEN
Solar/Wind Harmer
2.803
3145933PARMELE
Solar/Wind Harmer
-0.034
3145933PARMELE
Solar/Wind Harmer
-0.017
316237AB2-079_GEN
Solar/Wind Harmer
0.518
315724AD1-057 GEN
Solar/Wind Harmer
3.321
316005AA1-067
Solar/Wind Harmer
0.342
3150341NORNECKC1
Adder
1.536
3150341NORNECKC1
Adder
1.524
3150391LDYSMT3
Adder
18.222
972195AH1-682 GEN
Adder
2.395
316006AB2-029 C
Solar/Wind Helper
0.153
3144293JTRSVLE
Adder
0.374
959311AF2-222 GEN
Solar/Wind Harmer
18.224
970257AG2-171 GEN
Solar/Wind Harmer
6.539
971775AH1-396 GEN
Solar/Wind Harmer
1.23
316212AC1-099_GEN
Solar/Wind Harmer
1.514
316484AD2-074 GEN
Solar/Wind Harmer
4.378
961951AG1-038 GEN
Solar/Wind Harmer
2.291
972003AH1-546 GEN
Solar/Wind Harmer
7.054
964241AG1-285 GEN
Solar/Wind Harmer
13.538
3145933PARMELE
Solar/Wind Harmer
-0.017
315722AD1-056 GEN
Solar/Wind Harmer
6.038
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
966881AG1-559 GEN
Solar/Wind Harmer
0.499
3150351NORNECKC2
Adder
1.487
3150401LDYSMT4
Adder
18.256
3150371LDYSMT1
Adder
17.64
316420AA1-050 GEN
Solar/Wind Harmer
0.051
LAGNLTFEXP_LAGN->PJM
CLTF
6.454
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.688
TVALTFEXP_TVA->PJM
CLTF
3.273
CPLELTFEXP_CPLE->PJM
CLTF
9.477
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.819
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.756
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.074
MECLTFEXP_MEC->PJM
CLTF
2.789
SIGELTFEXP_SIGE->PJM
CLTF
0.085
NYPJM->LTFIMP_NY
CLTF
2.762
LGEELTFEXP_LGEE->PJM
CLTF
1.014
WECLTFEXP_WEC->PJM
CLTF
0.482

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.89 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4447.98
MW Contribution:
6.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.668
971285AH1-108 GEN
50/50
1.479
315244AE2-183_ST
50/50
5.231
963041AG1-153 GEN
50/50
4.819
316164AC1-076 GEN
Solar/Wind Harmer
2.593
3147346CASHSCORNER
Solar/Wind Harmer
0.387
316233AE1-074 FULL
Solar/Wind Harmer
0.594
971281AH1-106 GEN
Solar/Wind Harmer
3.587
971283AH1-107 GEN
Solar/Wind Harmer
3.587
970533AG2-339 GEN
Solar/Wind Harmer
14.177
970673AG2-436 GEN
Solar/Wind Harmer
45.651
316258AE1-075 C
Solar/Wind Harmer
0.499
316405AF2-144 C
Solar/Wind Harmer
0.527
3143316POE
Solar/Wind Harmer
-0.081
971967AH1-528 GEN
Solar/Wind Harmer
38.369
315839AE2-212 C
Solar/Wind Harmer
0.611
3151081ELIZAR1
Adder
16.483
3151091ELIZAR2
Adder
16.196
316316AC1-027 C
Solar/Wind Harmer
0.618
970657AG2-426 GEN
Solar/Wind Harmer
1.269
315814AE2-033 C
Solar/Wind Harmer
18.707
316018AA1-139 ULT2
Solar/Wind Harmer
1.714
957871AF2-081 GEN
Solar/Wind Harmer
10.027
316236AE1-162_GEN
Solar/Wind Harmer
0.603
971445AH1-216 GEN
Solar/Wind Harmer
12.402
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.797
316311AC2-079 GEN
Solar/Wind Harmer
10.084
3151201GRAVEL4
Adder
12.928
3151221GRAVEL6
Adder
12.913
3151191GRAVEL3
Adder
12.765
3151211GRAVEL5
Adder
12.765
315697AD1-025 GEN
Solar/Wind Harmer
4.023
313526AB2-022
Solar/Wind Harmer
0.534
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146396TANGLEW
Solar/Wind Harmer
0.364
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
316382AG1-145 C
Solar/Wind Harmer
0.583
316159AE1-175 C
Solar/Wind Harmer
0.519
970085AG2-068 GEN
Solar/Wind Harmer
12.076
970581AG2-369 GEN
Solar/Wind Harmer
10.385
315800Z1-036_GEN1
Solar/Wind Harmer
4.756
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
957831AF2-077 GEN
Solar/Wind Harmer
0.57
3138283WHITEMARSH
Solar/Wind Harmer
0.029
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.732
315733AD1-074 GEN2
Solar/Wind Harmer
3.732
316318V4-068
Solar/Wind Harmer
0.458
3145893MURPHYS
Solar/Wind Harmer
-0.049
3145893MURPHYS
Solar/Wind Harmer
-0.018
316059AD1-063 C
Solar/Wind Harmer
0.414
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
8.025
946281AF1-292 GEN
Solar/Wind Harmer
0.41
957601AF2-054 GEN
Solar/Wind Harmer
0.547
3141873WAN 176
Solar/Wind Harmer
-0.004
316486AD2-202 GEN
Solar/Wind Harmer
0.459
3146043SEABORD
Solar/Wind Harmer
-0.018
316463AE2-346 GEN
Solar/Wind Harmer
0.292
3145513AHOSKIE
Solar/Wind Harmer
0.158
961941AG1-037 GEN
Solar/Wind Harmer
0.136
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.005
3137643SOCKMAN
Solar/Wind Harmer
-0.071
315652AC1-086 GEN
Solar/Wind Harmer
20.124
316426AA2-053 GEN
Solar/Wind Harmer
1.797
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
2.707
3146033SCOT NK
Solar/Wind Harmer
-0.069
970831AG2-522 GEN
Solar/Wind Harmer
8.659
946301AF1-294 GEN
Solar/Wind Harmer
4.419
961791AG1-021 GEN
Solar/Wind Harmer
2.156
971845AH1-439 GEN
Solar/Wind Harmer
9.138
316210AC1-098 GEN
Solar/Wind Harmer
2.693
970683AG2-441 GEN
Solar/Wind Harmer
12.14
970681AG2-440 GEN
Solar/Wind Harmer
8.058
316322AB2-045
Solar/Wind Harmer
0.576
3144303KENBRDG
Solar/Wind Harmer
-0.014
316274AC1-208 GEN
Solar/Wind Harmer
1.84
316238AB2-078_GEN
Solar/Wind Harmer
0.509
316239AB2-077_GEN
Solar/Wind Harmer
0.509
972205AH1-687 GEN
Adder
6.37
3151731LOISA B
50/50
16.158
315242AE2-183_GT2
50/50
3.012
315241AE2-183_GT1
50/50
3.004
972185AH1-677 GEN
50/50
10.889
3151041BRUNSWICKG3
50/50
2.38
972187AH1-678 GEN
50/50
5.462
316045AC1-158 PL2
Solar/Wind Harmer
21.415
316450AC1-158 RIC
Solar/Wind Harmer
1.785
966001AG1-469 GEN
Solar/Wind Harmer
0.484
971223AH1-071 GEN
Solar/Wind Harmer
2.898
3143526WINTERP
Solar/Wind Harmer
-0.114
316313AB2-026
Solar/Wind Harmer
0.554
316294AC1-161 GEN
Solar/Wind Harmer
6.588
3150991CHESPKB
Adder
1.882
3150991CHESPKB
Adder
1.837
316185AD1-033 GEN
Solar/Wind Harmer
2.122
3144356SAPONY
Solar/Wind Harmer
0.703
316315AB2-025 C
Solar/Wind Harmer
0.542
316240AF1-291 C
Solar/Wind Harmer
0.606
316083AB2-161 GEN
Solar/Wind Harmer
3.269
3145506HICKORY
Solar/Wind Harmer
-0.08
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
944641AF1-129 GEN
Adder
85.336
316339AD2-160 GEN
Solar/Wind Harmer
1.35
316388AE2-253 GEN
Solar/Wind Harmer
1.35
970933AG2-581 GEN
Solar/Wind Harmer
18.79
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.364
3130086AYDLETT
Solar/Wind Harmer
-0.08
316349AD2-085 GEN
Solar/Wind Harmer
1.775
316336AC2-165 C
Solar/Wind Harmer
12.451
316033AB2-134 GEN
Solar/Wind Harmer
6.419
315835AF2-110_GEN
Solar/Wind Harmer
2.487
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.562
316433W1029_GEN2
Solar/Wind Harmer
3.562
316435W1029_GEN3
Solar/Wind Harmer
3.562
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.568
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3150691DARBY 3
Adder
12.452
3150701DARBY 4
Adder
12.423
3150681DARBY 2
Adder
12.409
3150671DARBY 1
Adder
12.394
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
4.581
3146376EDENTON
Solar/Wind Harmer
0.569
3146376EDENTON
Solar/Wind Harmer
0.569
3142296MT RD221
Adder
0.54
315976AC1-164 GENA
Solar/Wind Harmer
4.322
316169AC1-164_GENC
Solar/Wind Harmer
3.734
316312AB1-027
Solar/Wind Harmer
0.638
970099AG2-077 GEN
Solar/Wind Harmer
23.558
315614AA2-178 GEN
Solar/Wind Harmer
2.024
316365GEN2_N
Solar/Wind Harmer
1.256
316441AF1-014 GEN
Solar/Wind Harmer
1.24
316065AD1-022 GEN
Solar/Wind Harmer
9.198
3145893MURPHYS
Solar/Wind Harmer
0.512
3145893MURPHYS
Solar/Wind Harmer
-0.033
315666AE1-190 GEN
Solar/Wind Harmer
0.552
316156AD2-030 GEN
Solar/Wind Harmer
0.487
966871AG1-558 GEN
Solar/Wind Harmer
0.549
966871AG1-558 GEN
Solar/Wind Harmer
0.188
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316140AB2-099
Solar/Wind Harmer
0.122
313506AB2-031 GEN
Solar/Wind Harmer
1.447
970301AG2-198 GEN
Solar/Wind Harmer
8.984
972189AH1-679 GEN
Adder
2.676
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
962571AG1-106 GEN
Solar/Wind Harmer
2.571
3145593CAROLNA
Solar/Wind Harmer
-0.018
3152261N ANNA2
50/50
17.024
3151771S ANNAG1
50/50
0.836
3151801S ANNAS2
50/50
0.429
3151761LOISA E
50/50
32.94
3151721LOISA A
50/50
16.074
3150861SPRUNCD
50/50
0.904
3151031BRUNSWICKG2
50/50
2.38
3147666LOUISA
Solar/Wind Harmer
-0.074
3132273ORANGE
Solar/Wind Harmer
-0.005
944011AF1-069 GEN
Solar/Wind Harmer
12.385
3143336POWHATN
Solar/Wind Harmer
2.079
944581AF1-123 GEN
Solar/Wind Harmer
92.159
944601AF1-125 GEN
Solar/Wind Harmer
90.721
315813AE1-149 C
Solar/Wind Harmer
12.659
3151101ELIZAR3
Adder
16.694
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142956BIRDNECK
Solar/Wind Harmer
1.082
3144536CHRHLND
Solar/Wind Harmer
-0.003
970657AG2-426 GEN
Solar/Wind Harmer
4.067
316017AA1-139 ULT1
Solar/Wind Harmer
1.618
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.317
316305AF2-043 C
Solar/Wind Harmer
0.601
316246AF1-032 C
Solar/Wind Harmer
0.403
3151171GRAVELC
Adder
2.484
961611AG1-000B GEN
Solar/Wind Harmer
4.2
315778AD1-151 GEN
Solar/Wind Harmer
17.739
316458AB2-190 GEN2
Solar/Wind Harmer
2.01
970133AG2-095 GEN
Solar/Wind Harmer
2.24
3143096IRON208
Adder
0.741
3143096IRON208
Adder
0.726
316320Y1-086
Solar/Wind Harmer
1.162
316321Z2-027
Solar/Wind Harmer
0.532
3144216WINCHST
Adder
0.659
3146516WINFALL
Solar/Wind Harmer
-0.02
3150921YORKTN3
Adder
4.383
970917AG2-570 GEN
Solar/Wind Harmer
48.93
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.006
970293AG2-193 GEN
Solar/Wind Harmer
2.41
3146376EDENTON
Solar/Wind Harmer
-0.019
316075AC2-137 C
Solar/Wind Harmer
0.514
3142416OLDCHRC
Solar/Wind Harmer
1.913
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
3156081AA2-088 GEN
Solar/Wind Harmer
6.027
315735AD1-075 GEN1
Solar/Wind Harmer
1.865
3141843SHACKLE
Adder
0.837
316203AE2-005 GEN
Solar/Wind Harmer
7.759
3145893MURPHYS
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
-0.018
3141766HARMONY
Solar/Wind Harmer
1.633
3146206CASHIE
Solar/Wind Harmer
-0.018
966621AG1-532 GEN
Solar/Wind Harmer
0.371
3141873WAN 176
Solar/Wind Harmer
2.17
316473AC1-191 GEN
Solar/Wind Harmer
1.963
3146173TUNIS
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.567
316181AB2-040 GEN
Solar/Wind Harmer
2.514
3146263WOODLND
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
316011AB1-132 GEN
Solar/Wind Harmer
3.736
316190AA2-174 GEN
Solar/Wind Harmer
0.219
316317KELFORD C
Solar/Wind Harmer
0.821
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.01
942461AE2-259 GEN
Solar/Wind Harmer
2.615
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3144293JTRSVLE
Adder
0.366
316484AD2-074 GEN
Solar/Wind Harmer
4.334
961951AG1-038 GEN
Solar/Wind Harmer
2.268
316212AC1-099_GEN
Solar/Wind Harmer
1.496
3146776BUCKING
Solar/Wind Harmer
-0.006
959311AF2-222 GEN
Solar/Wind Harmer
17.898
970257AG2-171 GEN
Solar/Wind Harmer
6.424
971775AH1-396 GEN
Solar/Wind Harmer
1.209
3145933PARMELE
Solar/Wind Harmer
-0.017
964241AG1-285 GEN
Solar/Wind Harmer
13.317
972003AH1-546 GEN
Solar/Wind Harmer
6.826
315722AD1-056 GEN
Solar/Wind Harmer
5.965
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
3150351NORNECKC2
Adder
1.473
3150401LDYSMT4
Adder
18.127
3150371LDYSMT1
Adder
17.516
3152251N ANNA1
50/50
17.015
971507AH1-251 GEN
50/50
11.142
3151791S ANNAG2
50/50
0.836
3151781S ANNAS1
50/50
0.429
3151741LOISA C
50/50
0.884
3151751LOISA D
50/50
16.158
970119AG2-088 GEN
50/50
27.51
3150851SPRUNCC
50/50
0.904
315243AE2-183_GT3
50/50
3.012
3151051BRUNSWICKS1
50/50
4.942
3151021BRUNSWICKG1
50/50
2.38
971451AH1-221 GEN
50/50
7.229
316447AC1-158 HLD
Solar/Wind Harmer
14.719
316044AC1-158 PL1
Solar/Wind Harmer
6.692
3147666LOUISA
Solar/Wind Harmer
-0.13
316192AB2-158 GEN
Solar/Wind Harmer
3.821
315683AE1-153 C
Solar/Wind Harmer
24.24
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.114
940641AE2-051 GEN
Solar/Wind Harmer
20.195
939411AE1-173 GEN
Solar/Wind Harmer
105.991
941031AE2-094 GEN
Solar/Wind Harmer
39.528
3143336POWHATN
Solar/Wind Harmer
2.446
315773AC2-141 GEN
Solar/Wind Harmer
8.524
944591AF1-124 GEN
Solar/Wind Harmer
92.491
316375AC2-012 GEN
Solar/Wind Harmer
6.982
316036AC1-147 C
Solar/Wind Harmer
0.543
3150981CHESPKA
Adder
2.243
316381AD1-082 GEN
Solar/Wind Harmer
1.843
315671AE2-027_GEN
Solar/Wind Harmer
3.634
3142543TWELFTH
Solar/Wind Harmer
-0.002
3145336SMITFLD
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
-0.02
319010AE1-072 C
Solar/Wind Harmer
4.038
3151171GRAVELC
Adder
1.889
316072AD1-144
Solar/Wind Harmer
0.402
961611AG1-000B GEN
Solar/Wind Harmer
9.844
316369SG1_INVT
Solar/Wind Harmer
3.555
971069AG2-661 GEN
Solar/Wind Harmer
3.154
316132AB2-190 GEN1
Solar/Wind Harmer
2.01
316093AE2-104_GEN
Solar/Wind Harmer
5.785
3143096IRON208
Adder
0.741
3138126ROCKLANDING
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
-0.063
3146516WINFALL
Solar/Wind Harmer
-0.02
944631AF1-128 GEN
Adder
83.207
970919AG2-571 GEN
Solar/Wind Harmer
6.194
971317AH1-138 GEN
Solar/Wind Harmer
2.425
970087AG2-069 GEN
Solar/Wind Harmer
18.113
315611Z1-036_GEN2
Solar/Wind Harmer
4.756
3130156CHOWAN
Solar/Wind Harmer
-0.019
315975AC1-164 GENB
Solar/Wind Harmer
0.128
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142433PROV 92
Solar/Wind Harmer
-0.075
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
957481AF2-042 GEN
Solar/Wind Harmer
58.896
315816AE2-034 GEN
Solar/Wind Harmer
1.518
3145663CRESWEL
Solar/Wind Harmer
-0.052
971163AH1-040 GEN
Solar/Wind Harmer
17.639
316023GEN1_S
Solar/Wind Harmer
1.256
315693AD1-088 GEN
Solar/Wind Harmer
9.291
315737AD1-076 GEN
Solar/Wind Harmer
3.508
971777AH1-397 GEN
Solar/Wind Harmer
2.148
316314AB2-024 C
Solar/Wind Harmer
1.571
3145893MURPHYS
Solar/Wind Harmer
-0.073
3145893MURPHYS
Solar/Wind Harmer
0.545
315662AE1-191 GEN
Solar/Wind Harmer
2.207
316280AD1-041 GEN
Solar/Wind Harmer
1.379
3145746EVERETS
Solar/Wind Harmer
-0.066
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
316327AA2-057 GEN
Solar/Wind Harmer
1.675
3150411LDYSMT5
Adder
18.184
3150381LDYSMT2
Adder
17.403
972213AH1-691 GEN
Adder
2.944
972215AH1-692 GEN
Adder
2.944
957861AF2-080 GEN
Solar/Wind Harmer
1.277
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
0.148
3145783HORNRTN
Solar/Wind Harmer
2.098
3145783HORNRTN
Solar/Wind Harmer
1.679
3145783HORNRTN
Solar/Wind Harmer
0.525
3145783HORNRTN
Solar/Wind Harmer
0.21
3145796HORNRTN
Solar/Wind Harmer
-0.053
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.694
3144293JTRSVLE
Adder
0.366
316487AF1-042 GEN
Solar/Wind Harmer
2.268
3146776BUCKING
Solar/Wind Harmer
-0.068
3146776BUCKING
Solar/Wind Harmer
-0.006
970323AG2-213 GEN
Solar/Wind Harmer
8.565
315687AD1-152 GEN
Solar/Wind Harmer
2.053
3145933PARMELE
Solar/Wind Harmer
-0.034
3145933PARMELE
Solar/Wind Harmer
-0.017
313527AB2-043 GEN
Solar/Wind Harmer
2.76
316237AB2-079_GEN
Solar/Wind Harmer
0.509
315724AD1-057 GEN
Solar/Wind Harmer
3.281
316005AA1-067
Solar/Wind Harmer
0.338
3150341NORNECKC1
Adder
1.522
3150341NORNECKC1
Adder
1.51
3150391LDYSMT3
Adder
18.093
972195AH1-682 GEN
Adder
2.378
3141766HARMONY
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.585
960081AF2-299 GEN
Solar/Wind Harmer
2.058
970937AG2-583 GEN
Solar/Wind Harmer
13.092
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.436
316087AB2-174 GEN
Solar/Wind Harmer
2.582
315607AA1-063A GEN
Solar/Wind Harmer
1.821
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
316254AC1-120 GEN1
Solar/Wind Harmer
6.739
316170AC1-121 GEN2
Solar/Wind Harmer
2.246
3138133OCRAN
Solar/Wind Harmer
-0.011
3147043LAWRENC
Adder
1.441
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.01
316129AC1-054 GEN
Solar/Wind Harmer
1.509
971563AH1-280 GEN
Solar/Wind Harmer
2.156
3144293JTRSVLE
Adder
0.366
3144293JTRSVLE
Adder
0.289
970685AG2-442 GEN
Solar/Wind Harmer
15.063
971065AG2-659 GEN
Solar/Wind Harmer
8.604
3146776BUCKING
Solar/Wind Harmer
-0.007
316034AC1-036 C
Solar/Wind Harmer
0.317
315785AD2-033 C
Solar/Wind Harmer
3.87
3146293MARTNCO
Solar/Wind Harmer
0.106
316131AB2-060 GEN
Solar/Wind Harmer
1.83
962861AG1-135 GEN
Solar/Wind Harmer
6.369
316404AE1-155 C
Solar/Wind Harmer
3.226
958261AF2-120 GEN
Solar/Wind Harmer
6.549
3145746EVERETS
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.017
964211AG1-282 GEN
Solar/Wind Harmer
0.498
3141726DUNNSVL
Solar/Wind Harmer
-0.066
3150351NORNECKC2
Adder
1.449
972197AH1-683 GEN
Adder
2.831
972219AH1-694 GEN
Adder
2.038
316494AC1-189 GEN
Solar/Wind Harmer
0.314
LAGNLTFEXP_LAGN->PJM
CLTF
6.338
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.383
TVALTFEXP_TVA->PJM
CLTF
3.213
CPLELTFEXP_CPLE->PJM
CLTF
9.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.866
MECLTFEXP_MEC->PJM
CLTF
2.729
SIGELTFEXP_SIGE->PJM
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
2.706
LGEELTFEXP_LGEE->PJM
CLTF
0.989
WECLTFEXP_WEC->PJM
CLTF
0.471

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.15 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:898.18
MW Contribution:
16.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.285
3151601KERR 3
50/50
0.118
3151611KERR 4
50/50
0.118
3151621KERR 5
50/50
0.118
3151631KERR 6
50/50
0.118
971845AH1-439 GEN
Solar/Wind Harmer
16.79
946301AF1-294 GEN
Solar/Wind Harmer
3.609
961791AG1-021 GEN
Solar/Wind Harmer
1.756
970683AG2-441 GEN
Solar/Wind Harmer
9.764
970681AG2-440 GEN
Solar/Wind Harmer
6.481
3144303KENBRDG
Solar/Wind Harmer
0.112
316258AE1-075 C
Solar/Wind Helper
0.865
316405AF2-144 C
Solar/Wind Helper
0.721
316233AE1-074 FULL
Solar/Wind Helper
0.266
3151921BEARGRDN G2
50/50
4.561
3144293JTRSVLE
50/50
0.463
972003AH1-546 GEN
Solar/Wind Harmer
16.576
970221AG2-151 GEN
Solar/Wind Harmer
23.304
3146776BUCKING
Solar/Wind Harmer
0.136
270494AE1-108_GEN
Solar/Wind Harmer
4.12
315821AE2-092 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.62
959311AF2-222 GEN
Solar/Wind Harmer
12.996
958131AF2-107 GEN
Solar/Wind Harmer
4.142
970257AG2-171 GEN
Solar/Wind Harmer
4.475
971775AH1-396 GEN
Solar/Wind Harmer
0.224
964241AG1-285 GEN
Solar/Wind Harmer
7.182
3151931BEARGRDN S1
50/50
5.893
3151911BEARGRDN G1
50/50
4.561
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.366
3151591KERR 2
50/50
0.118
3151641KERR 7
50/50
0.118
970937AG2-583 GEN
Solar/Wind Harmer
37.476
971377AH1-170 GEN
Solar/Wind Harmer
4.661
3147623JAMES R
Solar/Wind Harmer
1.013
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
971563AH1-280 GEN
Solar/Wind Harmer
1.951
970685AG2-442 GEN
Solar/Wind Harmer
12.815
316034AC1-036 C
Solar/Wind Harmer
0.009
315785AD2-033 C
Solar/Wind Harmer
1.06
316131AB2-060 GEN
Solar/Wind Harmer
0.291
315693AD1-088 GEN
Solar/Wind Harmer
3.817
970401AG2-262 GEN
Solar/Wind Harmer
0.396
962751AG1-124 GEN
Solar/Wind Harmer
2.979
3143226MDLTHAN
Solar/Wind Helper
0.214
3143526WINTERP
Solar/Wind Helper
0.905
970909AG2-566 GEN
50/50
2.109
3144293JTRSVLE
50/50
0.463
970535AG2-341 GEN
50/50
1.296
3151581KERR 1
50/50
0.042
316336AC2-165 C
Solar/Wind Harmer
38.103
3146776BUCKING
Solar/Wind Harmer
1.512
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
8.437
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.195
970323AG2-213 GEN
Solar/Wind Harmer
5.966
962561AG1-105 GEN
Solar/Wind Harmer
3.404
964791AG1-342 GEN
Solar/Wind Harmer
1.295
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
316118AC1-105 GEN
Solar/Wind Harmer
0.151
316313AB2-026
Solar/Wind Helper
0.961
3143526WINTERP
Solar/Wind Helper
0.905
LAGNLTFEXP_LAGN->PJM
CLTF
1.351
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.16
TVALTFEXP_TVA->PJM
CLTF
0.693
CPLELTFEXP_CPLE->PJM
CLTF
1.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.769
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.753
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.453
MECLTFEXP_MEC->PJM
CLTF
0.803
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.408
LGEELTFEXP_LGEE->PJM
CLTF
0.324
WECLTFEXP_WEC->PJM
CLTF
0.162

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.87 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:895.98
MW Contribution:
10.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
970937AG2-583 GEN
Solar/Wind Harmer
28.694
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
316336AC2-165 C
Solar/Wind Harmer
32.605
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2054_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.54 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1014.73
MW Contribution:
21.84
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.298
316322AB2-045
Solar/Wind Harmer
1.427
971845AH1-439 GEN
Solar/Wind Harmer
22.116
946301AF1-294 GEN
Solar/Wind Harmer
5.267
961791AG1-021 GEN
Solar/Wind Harmer
2.569
970683AG2-441 GEN
Solar/Wind Harmer
12.858
970681AG2-440 GEN
Solar/Wind Harmer
8.534
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.295
316239AB2-077_GEN
Solar/Wind Harmer
0.295
316258AE1-075 C
Solar/Wind Helper
0.866
316405AF2-144 C
Solar/Wind Helper
0.721
316233AE1-074 FULL
Solar/Wind Helper
0.267
970909AG2-566 GEN
50/50
2.109
3144293JTRSVLE
50/50
0.463
316336AC2-165 C
Solar/Wind Harmer
52.75
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.109
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.212
970323AG2-213 GEN
Solar/Wind Harmer
7.856
313527AB2-043 GEN
Solar/Wind Harmer
1.643
316237AB2-079_GEN
Solar/Wind Harmer
0.295
962561AG1-105 GEN
Solar/Wind Harmer
4.484
964791AG1-342 GEN
Solar/Wind Harmer
1.62
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.456
316313AB2-026
Solar/Wind Helper
0.962
3143526WINTERP
Solar/Wind Helper
0.91
3151921BEARGRDN G2
50/50
4.563
3144293JTRSVLE
50/50
0.463
972003AH1-546 GEN
Solar/Wind Harmer
21.837
970221AG2-151 GEN
Solar/Wind Harmer
30.726
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
10.091
315821AE2-092 GEN
Solar/Wind Harmer
6.911
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.035
3147133PAMPLIN
Solar/Wind Harmer
-0.069
959311AF2-222 GEN
Solar/Wind Harmer
17.147
958131AF2-107 GEN
Solar/Wind Harmer
5.549
970257AG2-171 GEN
Solar/Wind Harmer
5.892
971775AH1-396 GEN
Solar/Wind Harmer
1.109
964241AG1-285 GEN
Solar/Wind Harmer
9.456
3151931BEARGRDN S1
50/50
5.896
3151911BEARGRDN G1
50/50
4.563
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.366
970937AG2-583 GEN
Solar/Wind Harmer
49.352
971377AH1-170 GEN
Solar/Wind Harmer
6.145
3147623JAMES R
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.569
970685AG2-442 GEN
Solar/Wind Harmer
16.876
316034AC1-036 C
Solar/Wind Harmer
0.291
315785AD2-033 C
Solar/Wind Harmer
3.332
316131AB2-060 GEN
Solar/Wind Harmer
1.131
315693AD1-088 GEN
Solar/Wind Harmer
4.459
970401AG2-262 GEN
Solar/Wind Harmer
0.495
962751AG1-124 GEN
Solar/Wind Harmer
4.417
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.91
LAGNLTFEXP_LAGN->PJM
CLTF
1.417
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.233
TVALTFEXP_TVA->PJM
CLTF
0.727
CPLELTFEXP_CPLE->PJM
CLTF
1.3
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.581
MECLTFEXP_MEC->PJM
CLTF
0.856
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.425
LGEELTFEXP_LGEE->PJM
CLTF
0.347
WECLTFEXP_WEC->PJM
CLTF
0.174

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.07 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1000.24
MW Contribution:
14.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.455
316322AB2-045
Solar/Wind Harmer
0.989
971845AH1-439 GEN
Solar/Wind Harmer
15.423
946301AF1-294 GEN
Solar/Wind Harmer
4.291
961791AG1-021 GEN
Solar/Wind Harmer
2.093
970683AG2-441 GEN
Solar/Wind Harmer
10.743
970681AG2-440 GEN
Solar/Wind Harmer
7.13
3144303KENBRDG
Solar/Wind Harmer
-0.011
971967AH1-528 GEN
Solar/Wind Harmer
23.665
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
316486AD2-202 GEN
Solar/Wind Harmer
0.291
316238AB2-078_GEN
Solar/Wind Harmer
0.293
316239AB2-077_GEN
Solar/Wind Harmer
0.293
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.004
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316258AE1-075 C
Solar/Wind Helper
1.125
316405AF2-144 C
Solar/Wind Helper
0.938
316233AE1-074 FULL
Solar/Wind Helper
0.383
315839AE2-212 C
Solar/Wind Helper
0.158
970909AG2-566 GEN
50/50
1.872
3144293JTRSVLE
50/50
0.378
316336AC2-165 C
Solar/Wind Harmer
45.111
3146776BUCKING
Solar/Wind Harmer
-0.117
3146776BUCKING
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
9.858
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.617
970323AG2-213 GEN
Solar/Wind Harmer
6.791
970933AG2-581 GEN
Solar/Wind Harmer
11.802
970099AG2-077 GEN
Solar/Wind Harmer
15.433
313527AB2-043 GEN
Solar/Wind Harmer
1.612
315687AD1-152 GEN
Solar/Wind Harmer
1.172
316237AB2-079_GEN
Solar/Wind Harmer
0.293
962561AG1-105 GEN
Solar/Wind Harmer
4.994
964791AG1-342 GEN
Solar/Wind Harmer
1.856
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
316118AC1-105 GEN
Solar/Wind Harmer
0.565
316248AF1-058 C
Solar/Wind Harmer
0.234
316313AB2-026
Solar/Wind Helper
1.25
3143526WINTERP
Solar/Wind Helper
1.302
316240AF1-291 C
Solar/Wind Helper
0.165
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.159
316312AB1-027
Solar/Wind Helper
0.221
3151921BEARGRDN G2
50/50
2.958
3144293JTRSVLE
50/50
0.378
972003AH1-546 GEN
Solar/Wind Harmer
14.248
970221AG2-151 GEN
Solar/Wind Harmer
19.91
3146776BUCKING
Solar/Wind Harmer
-0.01
270494AE1-108_GEN
Solar/Wind Harmer
6.621
3146926FARMVIL
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
4.824
942461AE2-259 GEN
Solar/Wind Harmer
3.135
3147133PAMPLIN
Solar/Wind Harmer
-0.056
959311AF2-222 GEN
Solar/Wind Harmer
14.664
970257AG2-171 GEN
Solar/Wind Harmer
5.093
971775AH1-396 GEN
Solar/Wind Harmer
0.958
958131AF2-107 GEN
Solar/Wind Harmer
3.937
316478AD1-087 GEN
Solar/Wind Harmer
0.995
964241AG1-285 GEN
Solar/Wind Harmer
8.768
3148013FISHERV
Solar/Wind Harmer
-0.008
316003AC1-222 GEN
Solar/Wind Harmer
0.73
971683AH1-343 GEN
Solar/Wind Harmer
3.086
316123AC1-075 GEN
Solar/Wind Harmer
0.691
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.719
316075AC2-137 C
Solar/Wind Helper
0.175
316458AB2-190 GEN2
Solar/Wind Helper
0.652
3151931BEARGRDN S1
50/50
3.822
3151911BEARGRDN G1
50/50
2.958
3144293JTRSVLE
50/50
0.378
3144293JTRSVLE
50/50
0.298
970937AG2-583 GEN
Solar/Wind Harmer
37.754
971377AH1-170 GEN
Solar/Wind Harmer
3.982
3147623JAMES R
Solar/Wind Harmer
0.493
3146776BUCKING
Solar/Wind Harmer
-0.012
3146926FARMVIL
Solar/Wind Harmer
-0.014
971563AH1-280 GEN
Solar/Wind Harmer
2.093
970685AG2-442 GEN
Solar/Wind Harmer
13.928
316034AC1-036 C
Solar/Wind Harmer
0.252
315693AD1-088 GEN
Solar/Wind Harmer
6.787
315785AD2-033 C
Solar/Wind Harmer
2.927
957481AF2-042 GEN
Solar/Wind Harmer
38.582
316131AB2-060 GEN
Solar/Wind Harmer
1.096
970401AG2-262 GEN
Solar/Wind Harmer
0.567
3143226MDLTHAN
Solar/Wind Helper
0.302
3143526WINTERP
Solar/Wind Helper
1.302
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.964
3142416OLDCHRC
Solar/Wind Helper
0.3
3142416OLDCHRC
Solar/Wind Helper
0.115
316132AB2-190 GEN1
Solar/Wind Helper
0.652
3142433PROV 92
Solar/Wind Helper
0.451
LAGNLTFEXP_LAGN->PJM
CLTF
1.476
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.272
TVALTFEXP_TVA->PJM
CLTF
0.766
CPLELTFEXP_CPLE->PJM
CLTF
0.716
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.41
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.768
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.821
MECLTFEXP_MEC->PJM
CLTF
1.1
SIGELTFEXP_SIGE->PJM
CLTF
0.036
NYPJM->LTFIMP_NY
CLTF
0.347
LGEELTFEXP_LGEE->PJM
CLTF
0.469
WECLTFEXP_WEC->PJM
CLTF
0.24

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.06 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1000.22
MW Contribution:
14.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.455
316322AB2-045
Solar/Wind Harmer
0.989
971845AH1-439 GEN
Solar/Wind Harmer
15.423
946301AF1-294 GEN
Solar/Wind Harmer
4.291
961791AG1-021 GEN
Solar/Wind Harmer
2.093
970683AG2-441 GEN
Solar/Wind Harmer
10.743
970681AG2-440 GEN
Solar/Wind Harmer
7.13
3144303KENBRDG
Solar/Wind Harmer
-0.011
971967AH1-528 GEN
Solar/Wind Harmer
23.665
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
316486AD2-202 GEN
Solar/Wind Harmer
0.291
316238AB2-078_GEN
Solar/Wind Harmer
0.293
316239AB2-077_GEN
Solar/Wind Harmer
0.293
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.004
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316258AE1-075 C
Solar/Wind Helper
1.125
316405AF2-144 C
Solar/Wind Helper
0.938
316233AE1-074 FULL
Solar/Wind Helper
0.383
315839AE2-212 C
Solar/Wind Helper
0.158
970909AG2-566 GEN
50/50
1.872
3144293JTRSVLE
50/50
0.378
316336AC2-165 C
Solar/Wind Harmer
45.111
3146776BUCKING
Solar/Wind Harmer
-0.117
3146776BUCKING
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
9.858
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.617
970323AG2-213 GEN
Solar/Wind Harmer
6.791
970933AG2-581 GEN
Solar/Wind Harmer
11.802
970099AG2-077 GEN
Solar/Wind Harmer
15.433
313527AB2-043 GEN
Solar/Wind Harmer
1.612
315687AD1-152 GEN
Solar/Wind Harmer
1.172
316237AB2-079_GEN
Solar/Wind Harmer
0.293
962561AG1-105 GEN
Solar/Wind Harmer
4.994
964791AG1-342 GEN
Solar/Wind Harmer
1.856
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
316118AC1-105 GEN
Solar/Wind Harmer
0.565
316248AF1-058 C
Solar/Wind Harmer
0.234
316313AB2-026
Solar/Wind Helper
1.25
3143526WINTERP
Solar/Wind Helper
1.302
316240AF1-291 C
Solar/Wind Helper
0.165
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.159
316312AB1-027
Solar/Wind Helper
0.221
3151921BEARGRDN G2
50/50
2.958
3144293JTRSVLE
50/50
0.378
972003AH1-546 GEN
Solar/Wind Harmer
14.248
970221AG2-151 GEN
Solar/Wind Harmer
19.91
3146776BUCKING
Solar/Wind Harmer
-0.01
270494AE1-108_GEN
Solar/Wind Harmer
6.621
3146926FARMVIL
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
4.824
942461AE2-259 GEN
Solar/Wind Harmer
3.135
3147133PAMPLIN
Solar/Wind Harmer
-0.056
959311AF2-222 GEN
Solar/Wind Harmer
14.664
970257AG2-171 GEN
Solar/Wind Harmer
5.093
971775AH1-396 GEN
Solar/Wind Harmer
0.958
958131AF2-107 GEN
Solar/Wind Harmer
3.937
316478AD1-087 GEN
Solar/Wind Harmer
0.995
964241AG1-285 GEN
Solar/Wind Harmer
8.768
3148013FISHERV
Solar/Wind Harmer
-0.008
316003AC1-222 GEN
Solar/Wind Harmer
0.73
971683AH1-343 GEN
Solar/Wind Harmer
3.086
316123AC1-075 GEN
Solar/Wind Harmer
0.691
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.719
316075AC2-137 C
Solar/Wind Helper
0.175
316458AB2-190 GEN2
Solar/Wind Helper
0.652
3151931BEARGRDN S1
50/50
3.822
3151911BEARGRDN G1
50/50
2.958
3144293JTRSVLE
50/50
0.378
3144293JTRSVLE
50/50
0.298
970937AG2-583 GEN
Solar/Wind Harmer
37.754
971377AH1-170 GEN
Solar/Wind Harmer
3.982
3147623JAMES R
Solar/Wind Harmer
0.493
3146776BUCKING
Solar/Wind Harmer
-0.012
3146926FARMVIL
Solar/Wind Harmer
-0.014
971563AH1-280 GEN
Solar/Wind Harmer
2.093
970685AG2-442 GEN
Solar/Wind Harmer
13.928
316034AC1-036 C
Solar/Wind Harmer
0.252
315693AD1-088 GEN
Solar/Wind Harmer
6.787
315785AD2-033 C
Solar/Wind Harmer
2.927
957481AF2-042 GEN
Solar/Wind Harmer
38.582
316131AB2-060 GEN
Solar/Wind Harmer
1.096
970401AG2-262 GEN
Solar/Wind Harmer
0.567
3143226MDLTHAN
Solar/Wind Helper
0.302
3143526WINTERP
Solar/Wind Helper
1.302
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.964
3142416OLDCHRC
Solar/Wind Helper
0.3
3142416OLDCHRC
Solar/Wind Helper
0.115
316132AB2-190 GEN1
Solar/Wind Helper
0.652
3142433PROV 92
Solar/Wind Helper
0.451
LAGNLTFEXP_LAGN->PJM
CLTF
1.476
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.272
TVALTFEXP_TVA->PJM
CLTF
0.766
CPLELTFEXP_CPLE->PJM
CLTF
0.716
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.41
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.768
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.821
MECLTFEXP_MEC->PJM
CLTF
1.1
SIGELTFEXP_SIGE->PJM
CLTF
0.036
NYPJM->LTFIMP_NY
CLTF
0.347
LGEELTFEXP_LGEE->PJM
CLTF
0.469
WECLTFEXP_WEC->PJM
CLTF
0.24

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 233T2028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.82 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:997.84
MW Contribution:
21.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.287
316322AB2-045
Solar/Wind Harmer
1.426
971845AH1-439 GEN
Solar/Wind Harmer
22.108
946301AF1-294 GEN
Solar/Wind Harmer
5.266
961791AG1-021 GEN
Solar/Wind Harmer
2.569
970683AG2-441 GEN
Solar/Wind Harmer
12.856
970681AG2-440 GEN
Solar/Wind Harmer
8.533
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.295
316239AB2-077_GEN
Solar/Wind Harmer
0.295
316258AE1-075 C
Solar/Wind Helper
0.865
316405AF2-144 C
Solar/Wind Helper
0.721
316233AE1-074 FULL
Solar/Wind Helper
0.266
970909AG2-566 GEN
50/50
2.109
3144293JTRSVLE
50/50
0.463
316336AC2-165 C
Solar/Wind Harmer
52.756
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.109
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.211
970323AG2-213 GEN
Solar/Wind Harmer
7.856
313527AB2-043 GEN
Solar/Wind Harmer
1.644
316237AB2-079_GEN
Solar/Wind Harmer
0.295
962561AG1-105 GEN
Solar/Wind Harmer
4.482
964791AG1-342 GEN
Solar/Wind Harmer
1.619
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.456
316313AB2-026
Solar/Wind Helper
0.961
3143526WINTERP
Solar/Wind Helper
0.905
3151921BEARGRDN G2
50/50
4.561
3144293JTRSVLE
50/50
0.463
972003AH1-546 GEN
Solar/Wind Harmer
21.826
970221AG2-151 GEN
Solar/Wind Harmer
30.689
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
10.073
315821AE2-092 GEN
Solar/Wind Harmer
6.871
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.034
3147133PAMPLIN
Solar/Wind Harmer
-0.069
959311AF2-222 GEN
Solar/Wind Harmer
17.146
958131AF2-107 GEN
Solar/Wind Harmer
5.519
970257AG2-171 GEN
Solar/Wind Harmer
5.892
971775AH1-396 GEN
Solar/Wind Harmer
1.109
964241AG1-285 GEN
Solar/Wind Harmer
9.457
3151931BEARGRDN S1
50/50
5.893
3151911BEARGRDN G1
50/50
4.561
3144293JTRSVLE
50/50
0.463
3144293JTRSVLE
50/50
0.366
970937AG2-583 GEN
Solar/Wind Harmer
49.344
971377AH1-170 GEN
Solar/Wind Harmer
6.138
3147623JAMES R
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.569
970685AG2-442 GEN
Solar/Wind Harmer
16.873
316034AC1-036 C
Solar/Wind Harmer
0.291
315785AD2-033 C
Solar/Wind Harmer
3.332
316131AB2-060 GEN
Solar/Wind Harmer
1.131
315693AD1-088 GEN
Solar/Wind Harmer
4.466
970401AG2-262 GEN
Solar/Wind Harmer
0.495
962751AG1-124 GEN
Solar/Wind Harmer
4.358
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.905
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.17
TVALTFEXP_TVA->PJM
CLTF
0.697
CPLELTFEXP_CPLE->PJM
CLTF
1.287
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.825
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.469
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.026
NYPJM->LTFIMP_NY
CLTF
0.41
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.164

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.77 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:997.37
MW Contribution:
22.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.565
316322AB2-045
Solar/Wind Harmer
1.445
971845AH1-439 GEN
Solar/Wind Harmer
22.392
946301AF1-294 GEN
Solar/Wind Harmer
5.341
961791AG1-021 GEN
Solar/Wind Harmer
2.605
970683AG2-441 GEN
Solar/Wind Harmer
13.043
970681AG2-440 GEN
Solar/Wind Harmer
8.657
3144303KENBRDG
Solar/Wind Harmer
-0.013
316238AB2-078_GEN
Solar/Wind Harmer
0.3
316239AB2-077_GEN
Solar/Wind Harmer
0.3
316258AE1-075 C
Solar/Wind Helper
0.856
316405AF2-144 C
Solar/Wind Helper
0.714
316233AE1-074 FULL
Solar/Wind Helper
0.262
3151931BEARGRDN S1
50/50
5.966
3151911BEARGRDN G1
50/50
4.618
3144293JTRSVLE
50/50
0.47
3144293JTRSVLE
50/50
0.371
970937AG2-583 GEN
Solar/Wind Harmer
49.752
971377AH1-170 GEN
Solar/Wind Harmer
5.883
3147623JAMES R
Solar/Wind Harmer
0.728
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.605
970685AG2-442 GEN
Solar/Wind Harmer
17.117
316034AC1-036 C
Solar/Wind Harmer
0.296
315785AD2-033 C
Solar/Wind Harmer
3.382
316131AB2-060 GEN
Solar/Wind Harmer
1.15
315693AD1-088 GEN
Solar/Wind Harmer
4.553
970401AG2-262 GEN
Solar/Wind Harmer
0.503
962751AG1-124 GEN
Solar/Wind Harmer
4.191
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.893
3151921BEARGRDN G2
50/50
4.618
3144293JTRSVLE
50/50
0.47
972003AH1-546 GEN
Solar/Wind Harmer
22.099
970221AG2-151 GEN
Solar/Wind Harmer
29.417
3146776BUCKING
Solar/Wind Harmer
-0.015
270494AE1-108_GEN
Solar/Wind Harmer
9.657
3146926FARMVIL
Solar/Wind Harmer
-0.019
315821AE2-092 GEN
Solar/Wind Harmer
6.506
942461AE2-259 GEN
Solar/Wind Harmer
4.09
3147133PAMPLIN
Solar/Wind Harmer
-0.07
959311AF2-222 GEN
Solar/Wind Harmer
17.401
970257AG2-171 GEN
Solar/Wind Harmer
5.98
971775AH1-396 GEN
Solar/Wind Harmer
1.125
958131AF2-107 GEN
Solar/Wind Harmer
5.296
964241AG1-285 GEN
Solar/Wind Harmer
9.607
970909AG2-566 GEN
50/50
2.14
3144293JTRSVLE
50/50
0.47
316336AC2-165 C
Solar/Wind Harmer
53.022
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
11.269
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.257
970323AG2-213 GEN
Solar/Wind Harmer
7.973
313527AB2-043 GEN
Solar/Wind Harmer
1.671
316237AB2-079_GEN
Solar/Wind Harmer
0.3
962561AG1-105 GEN
Solar/Wind Harmer
4.556
964791AG1-342 GEN
Solar/Wind Harmer
1.645
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.463
316313AB2-026
Solar/Wind Helper
0.951
3143526WINTERP
Solar/Wind Helper
0.893
LAGNLTFEXP_LAGN->PJM
CLTF
1.342
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.206
TVALTFEXP_TVA->PJM
CLTF
0.688
CPLELTFEXP_CPLE->PJM
CLTF
1.316
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.679
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.609
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.431
MECLTFEXP_MEC->PJM
CLTF
0.788
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.407
LGEELTFEXP_LGEE->PJM
CLTF
0.317
WECLTFEXP_WEC->PJM
CLTF
0.159

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.1 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:873.8
MW Contribution:
10.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
970937AG2-583 GEN
Solar/Wind Harmer
28.694
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.71 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:870.6
MW Contribution:
10.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.464
3151541CLOVER2
50/50
2.174
3151601KERR 3
50/50
0.133
3151611KERR 4
50/50
0.133
3151621KERR 5
50/50
0.133
3151631KERR 6
50/50
0.133
971845AH1-439 GEN
Solar/Wind Harmer
11.713
946301AF1-294 GEN
Solar/Wind Harmer
2.935
961791AG1-021 GEN
Solar/Wind Harmer
1.428
970683AG2-441 GEN
Solar/Wind Harmer
8.138
970681AG2-440 GEN
Solar/Wind Harmer
5.401
3144303KENBRDG
Solar/Wind Harmer
0.096
971967AH1-528 GEN
Solar/Wind Harmer
17.83
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316486AD2-202 GEN
Solar/Wind Harmer
0.104
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
316258AE1-075 C
Solar/Wind Helper
1.124
316405AF2-144 C
Solar/Wind Helper
0.936
316233AE1-074 FULL
Solar/Wind Helper
0.38
315839AE2-212 C
Solar/Wind Helper
0.156
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.96
3144293JTRSVLE
50/50
0.377
3144293JTRSVLE
50/50
0.297
3151531CLOVER1
50/50
2.19
3151591KERR 2
50/50
0.133
3151641KERR 7
50/50
0.133
970937AG2-583 GEN
Solar/Wind Harmer
28.694
971377AH1-170 GEN
Solar/Wind Harmer
3.026
3147623JAMES R
Solar/Wind Harmer
0.657
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
971563AH1-280 GEN
Solar/Wind Harmer
1.586
970685AG2-442 GEN
Solar/Wind Harmer
10.553
316034AC1-036 C
Solar/Wind Harmer
0.008
315693AD1-088 GEN
Solar/Wind Harmer
5.773
315785AD2-033 C
Solar/Wind Harmer
0.928
957481AF2-042 GEN
Solar/Wind Harmer
29.141
316131AB2-060 GEN
Solar/Wind Harmer
0.281
970401AG2-262 GEN
Solar/Wind Harmer
0.45
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.295
3142543TWELFTH
Solar/Wind Helper
0.014
315671AE2-027_GEN
Solar/Wind Helper
0.95
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.114
316132AB2-190 GEN1
Solar/Wind Helper
0.642
970909AG2-566 GEN
50/50
1.868
3144293JTRSVLE
50/50
0.377
970535AG2-341 GEN
50/50
1.347
3152661PLYWOOD A
50/50
0.155
3151581KERR 1
50/50
0.047
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
970301AG2-198 GEN
Solar/Wind Harmer
7.473
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.785
970323AG2-213 GEN
Solar/Wind Harmer
5.141
970933AG2-581 GEN
Solar/Wind Harmer
8.916
970099AG2-077 GEN
Solar/Wind Harmer
11.656
962561AG1-105 GEN
Solar/Wind Harmer
3.765
964791AG1-342 GEN
Solar/Wind Harmer
1.473
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
0.186
316313AB2-026
Solar/Wind Helper
1.248
3143526WINTERP
Solar/Wind Helper
1.295
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316312AB1-027
Solar/Wind Helper
0.218
3151921BEARGRDN G2
50/50
2.96
3144293JTRSVLE
50/50
0.377
970413AG2-270 GEN
50/50
9.539
972003AH1-546 GEN
Solar/Wind Harmer
10.827
970221AG2-151 GEN
Solar/Wind Harmer
15.131
3146776BUCKING
Solar/Wind Harmer
0.094
270494AE1-108_GEN
Solar/Wind Harmer
2.709
3146926FARMVIL
Solar/Wind Harmer
0.129
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
3147133PAMPLIN
Solar/Wind Harmer
0.497
959311AF2-222 GEN
Solar/Wind Harmer
11.082
970257AG2-171 GEN
Solar/Wind Harmer
3.856
971775AH1-396 GEN
Solar/Wind Harmer
0.193
958131AF2-107 GEN
Solar/Wind Harmer
2.952
316478AD1-087 GEN
Solar/Wind Harmer
0.353
964241AG1-285 GEN
Solar/Wind Harmer
6.631
3148013FISHERV
Solar/Wind Harmer
0.071
971683AH1-343 GEN
Solar/Wind Harmer
2.319
316123AC1-075 GEN
Solar/Wind Harmer
0.075
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.71
316075AC2-137 C
Solar/Wind Helper
0.173
316458AB2-190 GEN2
Solar/Wind Helper
0.642
LAGNLTFEXP_LAGN->PJM
CLTF
1.394
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
TVALTFEXP_TVA->PJM
CLTF
0.725
CPLELTFEXP_CPLE->PJM
CLTF
0.604
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.975
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.497
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.681
MECLTFEXP_MEC->PJM
CLTF
1.059
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.335
LGEELTFEXP_LGEE->PJM
CLTF
0.455
WECLTFEXP_WEC->PJM
CLTF
0.232

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.44 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:736.99
MW Contribution:
39.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970909AG2-566 GEN
50/50
4.033
3144293JTRSVLE
50/50
0.884
970535AG2-341 GEN
50/50
2.831
3151581KERR 1
50/50
0.097
3152661PLYWOOD A
50/50
0.263
3146776BUCKING
Solar/Wind Harmer
-0.306
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.243
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.129
970323AG2-213 GEN
Solar/Wind Harmer
15.419
313527AB2-043 GEN
Solar/Wind Harmer
3.435
316237AB2-079_GEN
Solar/Wind Harmer
0.618
962561AG1-105 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.417
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.061
316118AC1-105 GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
1.604
316248AF1-058 C
Solar/Wind Harmer
0.369
970933AG2-581 GEN
Solar/Wind Harmer
9.052
313506AB2-031 GEN
Solar/Wind Harmer
0.652
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.721
3145783HORNRTN
Solar/Wind Harmer
0.225
3145783HORNRTN
Solar/Wind Harmer
0.09
942751AE2-291 GEN
Solar/Wind Harmer
4.314
972187AH1-678 GEN
Adder
1.622
316313AB2-026
Solar/Wind Helper
0.342
3144293JTRSVLE
50/50
0.884
3144293JTRSVLE
50/50
0.698
3151591KERR 2
50/50
0.273
3151641KERR 7
50/50
0.273
3151531CLOVER1
50/50
2.843
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
971563AH1-280 GEN
Solar/Wind Harmer
4.903
970685AG2-442 GEN
Solar/Wind Harmer
32.4
316034AC1-036 C
Solar/Wind Harmer
0.571
315785AD2-033 C
Solar/Wind Harmer
6.591
316131AB2-060 GEN
Solar/Wind Harmer
2.349
315693AD1-088 GEN
Solar/Wind Harmer
9.984
970401AG2-262 GEN
Solar/Wind Harmer
1.044
957481AF2-042 GEN
Solar/Wind Harmer
45.152
971065AG2-659 GEN
Solar/Wind Harmer
6.457
316129AC1-054 GEN
Solar/Wind Harmer
1.092
3151601KERR 3
50/50
0.273
3151611KERR 4
50/50
0.273
3151621KERR 5
50/50
0.273
3151631KERR 6
50/50
0.273
3151541CLOVER2
50/50
2.821
316322AB2-045
Solar/Wind Harmer
2.582
971845AH1-439 GEN
Solar/Wind Harmer
40.071
946301AF1-294 GEN
Solar/Wind Harmer
10.051
961791AG1-021 GEN
Solar/Wind Harmer
4.903
970683AG2-441 GEN
Solar/Wind Harmer
24.83
970681AG2-440 GEN
Solar/Wind Harmer
16.48
3144303KENBRDG
Solar/Wind Harmer
-0.025
316238AB2-078_GEN
Solar/Wind Harmer
0.618
316239AB2-077_GEN
Solar/Wind Harmer
0.618
316486AD2-202 GEN
Solar/Wind Harmer
0.376
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
5.971
946281AF1-292 GEN
Solar/Wind Harmer
0.189
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.903
316426AA2-053 GEN
Solar/Wind Harmer
0.743
3146043SEABORD
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.712
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
0.884
970413AG2-270 GEN
50/50
12.38
972003AH1-546 GEN
Solar/Wind Harmer
39.017
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.534
3147133PAMPLIN
Solar/Wind Harmer
-0.131
959311AF2-222 GEN
Solar/Wind Harmer
33.483
970257AG2-171 GEN
Solar/Wind Harmer
11.564
971775AH1-396 GEN
Solar/Wind Harmer
2.176
964241AG1-285 GEN
Solar/Wind Harmer
19.21
316478AD1-087 GEN
Solar/Wind Harmer
1.284
3147043LAWRENC
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
1.102
971683AH1-343 GEN
Solar/Wind Harmer
4.41
966621AG1-532 GEN
Solar/Wind Harmer
0.171
316181AB2-040 GEN
Solar/Wind Harmer
1.132
316123AC1-075 GEN
Solar/Wind Harmer
0.848
316222AC1-221 GEN
Solar/Wind Harmer
0.764
316283AC2-100 C
Solar/Wind Harmer
0.702
316190AA2-174 GEN
Solar/Wind Harmer
0.09
270494AE1-108_GEN
Solar/Wind Helper
4.516
315821AE2-092 GEN
Solar/Wind Helper
3.008
3148013FISHERV
Solar/Wind Helper
0.125
3147043LAWRENC
Adder
0.991
960081AF2-299 GEN
Solar/Wind Harmer
0.95
316087AB2-174 GEN
Solar/Wind Harmer
1.171
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.71
LAGNLTFEXP_LAGN->PJM
CLTF
1.802
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.396
TVALTFEXP_TVA->PJM
CLTF
0.884
CPLELTFEXP_CPLE->PJM
CLTF
3.694
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.383
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.9
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.89
MECLTFEXP_MEC->PJM
CLTF
0.611
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.353
LGEELTFEXP_LGEE->PJM
CLTF
0.173
WECLTFEXP_WEC->PJM
CLTF
0.09

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.97 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:705.81
MW Contribution:
39.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.285
3151611KERR 4
50/50
0.285
3151621KERR 5
50/50
0.285
3151631KERR 6
50/50
0.285
3151541CLOVER2
50/50
2.933
316322AB2-045
Solar/Wind Harmer
2.594
971845AH1-439 GEN
Solar/Wind Harmer
40.261
946301AF1-294 GEN
Solar/Wind Harmer
10.181
961791AG1-021 GEN
Solar/Wind Harmer
4.966
970683AG2-441 GEN
Solar/Wind Harmer
25.2
970681AG2-440 GEN
Solar/Wind Harmer
16.726
3144303KENBRDG
Solar/Wind Harmer
-0.025
316238AB2-078_GEN
Solar/Wind Harmer
0.636
316239AB2-077_GEN
Solar/Wind Harmer
0.636
316486AD2-202 GEN
Solar/Wind Harmer
0.391
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.293
946281AF1-292 GEN
Solar/Wind Harmer
0.203
3137643SOCKMAN
Solar/Wind Harmer
-0.034
971967AH1-528 GEN
Solar/Wind Harmer
15.92
316426AA2-053 GEN
Solar/Wind Harmer
0.807
3146043SEABORD
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.788
316210AC1-098 GEN
Solar/Wind Harmer
1.098
316327AA2-057 GEN
Solar/Wind Harmer
0.702
970085AG2-068 GEN
Solar/Wind Harmer
4.3
970581AG2-369 GEN
Solar/Wind Harmer
3.698
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.528
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
316258AE1-075 C
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.25
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
0.896
970413AG2-270 GEN
50/50
12.873
972003AH1-546 GEN
Solar/Wind Harmer
39.131
3146776BUCKING
Solar/Wind Harmer
-0.028
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.603
3147133PAMPLIN
Solar/Wind Harmer
-0.133
959311AF2-222 GEN
Solar/Wind Harmer
34.045
970257AG2-171 GEN
Solar/Wind Harmer
11.768
971775AH1-396 GEN
Solar/Wind Harmer
2.214
964241AG1-285 GEN
Solar/Wind Harmer
19.657
316478AD1-087 GEN
Solar/Wind Harmer
1.336
3147043LAWRENC
Solar/Wind Harmer
-0.008
316003AC1-222 GEN
Solar/Wind Harmer
1.157
971683AH1-343 GEN
Solar/Wind Harmer
4.627
966621AG1-532 GEN
Solar/Wind Harmer
0.184
316181AB2-040 GEN
Solar/Wind Harmer
1.219
316222AC1-221 GEN
Solar/Wind Harmer
0.851
316283AC2-100 C
Solar/Wind Harmer
0.784
316123AC1-075 GEN
Solar/Wind Harmer
0.888
316190AA2-174 GEN
Solar/Wind Harmer
0.098
316212AC1-099_GEN
Solar/Wind Harmer
0.61
970917AG2-570 GEN
Solar/Wind Harmer
17.254
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.398
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
2.351
961601AG1-000A GEN
Solar/Wind Harmer
2.603
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.079
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.481
315821AE2-092 GEN
Solar/Wind Helper
2.977
3148013FISHERV
Solar/Wind Helper
0.124
970909AG2-566 GEN
50/50
4.079
3144293JTRSVLE
50/50
0.896
970535AG2-341 GEN
50/50
2.929
3151581KERR 1
50/50
0.102
3152661PLYWOOD A
50/50
0.275
3146776BUCKING
Solar/Wind Harmer
-0.308
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.48
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.208
970323AG2-213 GEN
Solar/Wind Harmer
15.691
313527AB2-043 GEN
Solar/Wind Harmer
3.53
316237AB2-079_GEN
Solar/Wind Harmer
0.636
962561AG1-105 GEN
Solar/Wind Harmer
9.778
964791AG1-342 GEN
Solar/Wind Harmer
3.545
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.773
316118AC1-105 GEN
Solar/Wind Harmer
1.009
315687AD1-152 GEN
Solar/Wind Harmer
1.681
316248AF1-058 C
Solar/Wind Harmer
0.387
970933AG2-581 GEN
Solar/Wind Harmer
9.564
313506AB2-031 GEN
Solar/Wind Harmer
0.702
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.978
3145783HORNRTN
Solar/Wind Harmer
0.783
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
942751AE2-291 GEN
Solar/Wind Harmer
4.517
972187AH1-678 GEN
Adder
1.766
962571AG1-106 GEN
Solar/Wind Harmer
0.962
972185AH1-677 GEN
Adder
3.335
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316049AB1-081 GEN
Solar/Wind Harmer
0.714
316263AC1-034 GEN
Solar/Wind Harmer
3.112
315724AD1-057 GEN
Solar/Wind Harmer
1.293
316365GEN2_N
Solar/Wind Harmer
0.44
961601AG1-000A GEN
Solar/Wind Harmer
2.571
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316313AB2-026
Solar/Wind Helper
0.334
3144293JTRSVLE
50/50
0.896
3144293JTRSVLE
50/50
0.707
3151591KERR 2
50/50
0.285
3151641KERR 7
50/50
0.285
3151531CLOVER1
50/50
2.956
3147043LAWRENC
50/50
1.103
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
971563AH1-280 GEN
Solar/Wind Harmer
4.966
970685AG2-442 GEN
Solar/Wind Harmer
32.852
316034AC1-036 C
Solar/Wind Harmer
0.582
315785AD2-033 C
Solar/Wind Harmer
6.715
316131AB2-060 GEN
Solar/Wind Harmer
2.412
315693AD1-088 GEN
Solar/Wind Harmer
10.261
970401AG2-262 GEN
Solar/Wind Harmer
1.083
957481AF2-042 GEN
Solar/Wind Harmer
46.933
971065AG2-659 GEN
Solar/Wind Harmer
6.779
316129AC1-054 GEN
Solar/Wind Harmer
1.148
960081AF2-299 GEN
Solar/Wind Harmer
1.018
316087AB2-174 GEN
Solar/Wind Harmer
1.259
3145783HORNRTN
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.773
970919AG2-571 GEN
Solar/Wind Harmer
2.184
970087AG2-069 GEN
Solar/Wind Harmer
6.45
316319Z2-044 C
Solar/Wind Harmer
0.377
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.893
3142053HEARTS
Solar/Wind Harmer
0.078
316023GEN1_S
Solar/Wind Harmer
0.44
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.188
LAGNLTFEXP_LAGN->PJM
CLTF
2.464
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.192
TVALTFEXP_TVA->PJM
CLTF
1.196
CPLELTFEXP_CPLE->PJM
CLTF
4.521
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.285
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.813
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.884
MECLTFEXP_MEC->PJM
CLTF
0.804
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.206
WECLTFEXP_WEC->PJM
CLTF
0.115
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: WT576_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P2-2: BREMO B3_SRT-A'
 OPEN BRANCH FROM BUS 313708 TO BUS 314744 CKT 2   /*3FORK UNION  115.0 - 3BREMO       115.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314746 CKT 1   /*3BREMO       115.0 - 4BREMO       138.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 2   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BUS 314868                                   /*3BREMO_1     115.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 553_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1                /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H2T560_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313908 TO BUS 314922 CKT 1   /*6POS PT TAP2 230.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: H1T560_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313058 TO BUS 314922 CKT 1   /*6POSS PT TAP 230.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 560T571_SRT-S'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1                /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313383 TO BUS 314922 CKT 1                /*8OCCOQUN     500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019F_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1          /*BRIGHTON     500.0 - 01DOUBS      500.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 2          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 4          /*01DOUBS      500.0 - 01DOUBS      230.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 1                  /*01DOUBS      500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
END
CONTINGENCY 'PEPCO_P1_5070_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'DVP_P4-2: 202712_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1                /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1                /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                                /*6POWHATN     230.0
 OPEN BUS 316258                                                /*AE1-075 C    230.0
 OPEN BUS 316313                                                /*AB2-026      230.0
 OPEN BUS 316405                                                /*AF2-144 C    230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1   /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 2028_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P4-2: 2028T2054_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1   /*6CHARLVL     230.0 - 6PROFFIT     230.0
 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1   /*6HOLLYMD     230.0 - 6PROFFIT     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
 OPEN BUS 314772                                   /*6PROFFIT     230.0
END
CONTINGENCY 'DVP_P4-2: 233T2028_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1   /*6HYDRAULIC   230.0 - 6BARRCK2     230.0
 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1   /*6HYDRAULIC   230.0 - 6CHARLVL     230.0
 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1   /*6BARRCK2     230.0 - 6CROZET1     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1   /*6CROZET1     230.0 - 6DOOMS       230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 313826                                   /*6HYDRAULIC   230.0
 OPEN BUS 314742                                   /*6BARRCK2     230.0
 OPEN BUS 314751                                   /*6CROZET1     230.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P4-2: 2028T2193_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P4-2: WT2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313708 CKT 1   /*6FORK UNION  230.0 - 3FORK UNION  115.0
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P1-2: LN 298_SRT-A-4'
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P7-1: LN 2054-2135_SRT-A'
 OPEN BRANCH FROM BUS 314734 TO BUS 314758 CKT 1   /*6CASHSCORNER 230.0 - 6GORDNVL     230.0
 OPEN BRANCH FROM BUS 314734 TO BUS 314759 CKT 1   /*6CASHSCORNER 230.0 - 6HOLLYMD     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1   /*6CHARLVL     230.0 - 6PROFFIT     230.0
 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1   /*6HOLLYMD     230.0 - 6PROFFIT     230.0
 OPEN BUS 314734                                   /*6CASHSCORNER 230.0
 OPEN BUS 314772                                   /*6PROFFIT     230.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-1: G202_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 315226 CKT 1                /*8NO ANNA     500.0 - 1N ANNA2      22.0
 OPEN BUS 315226                                                /*1N ANNA2      22.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P2-2: NORTH ANNA B2_SRT-S'
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P2-2: NORTH ANNA B1_SRT-S'
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P7-1: LN 2090-256_SRT-S'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1                /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1                /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1                /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 314150 TO BUS 314212 CKT 1                /*6STJOHN      230.0 - 6FOUR RIVERS 230.0
 OPEN BRANCH FROM BUS 314197 TO BUS 315672 CKT 1                /*6LDYSMITH CT 230.0 - AE1-157 TAP  230.0
 OPEN BUS 313837                                                /*6SUMMIT      230.0
 OPEN BUS 314138                                                /*6MINE RD     230.0
 OPEN BUS 314149                                                /*3STJOHND     115.0
 OPEN BUS 314150                                                /*6STJOHN      230.0
 OPEN BUS 314154                                                /*3STJOHNS     115.0
 OPEN BUS 315672                                                /*AE1-157 TAP  230.0
 OPEN BUS 315673                                                /*AE1-157 GEN    0.6
 OPEN BUS 315803                                                /*AE1-157 MAIN 230.0
 OPEN BUS 315804                                                /*AE1-157 COL1  34.5
 OPEN BUS 315805                                                /*AE1-157 COL2  34.5
 SET POSTCONTRATING 657 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
 SET PRECONTRATING 598 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
END
CONTINGENCY 'DVP_P4-2: 57302_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P4-2: 515T594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314934 TO BUS 314944 CKT 1                /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 OPEN BUS 314944                                                /*8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: XT573_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 574T575_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 57502_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-1'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-2'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'DVP_P2-2: GERMANNA_SRT-A'
 OPEN BRANCH FROM BUS 313671 TO BUS 313678 CKT 1   /*6GERMANNA    230.0 - 6KYSER       230.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
END
CONTINGENCY 'DVP_P7-1: LN 2-2199_SRT-A-1'
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314078 TO BUS 314743 CKT 1   /*3REMNGTN     115.0 - 3BRANDY      115.0
 OPEN BRANCH FROM BUS 314743 TO BUS 316256 CKT 1   /*3BRANDY      115.0 - AC1-043 TAP  115.0
 OPEN BUS 314743                                   /*3BRANDY      115.0
END
CONTINGENCY 'DVP_P7-1: LN 2-2199_SRT-A-2'
 OPEN BRANCH FROM BUS 314078 TO BUS 314743 CKT 1   /*3REMNGTN     115.0 - 3BRANDY      115.0
 OPEN BRANCH FROM BUS 314743 TO BUS 316256 CKT 1   /*3BRANDY      115.0 - AC1-043 TAP  115.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BUS 314743                                   /*3BRANDY      115.0
END
CONTINGENCY 'DVP_P4-2: 587T591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P7-1: LN 2106-2111_SRT-A'
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
END
CONTINGENCY 'AEP_P2-2_#1377_05J.FERR 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1   /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1   /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1   /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1   /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
314744 to 313708 ckt 2
314747 to 313867 ckt 1
314747 to 970936 ckt 1
313867 to 313707 ckt 1
313868 to 316335 ckt 1
314749 to 314772 ckt 1
314290 to 223938 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314759 to 314734 ckt 1
314322 to 314914 ckt 1
314765 to 314749 ckt 1
314333 to 314322 ckt 1
314772 to 314759 ckt 1
313911 to 314290 ckt 1
314902 to 314914 ckt 1
314905 to 314900 ckt 1
314908 to 314911 ckt 1
314911 to 314905 ckt 1
314911 to 314922 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314922 to 200019 ckt 1
314934 to 314916 ckt 1
316335 to 314333 ckt 1
970936 to 313868 ckt 1
972002 to 314747 ckt 1

Winter Peak Analysis

The New Service Request AH1-546 was evaluated as a 65.0 MW (39.0 MW Capacity) injection in the Dominion area.

AH1-546 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 65.0 MW (65.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-546 was evaluated as a 65.0 MW injection

AH1-546 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 65.0 MW (65.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
DVP_P1-2: LN 2193_SRT-A
SingleAC106.22 %179.54B190.71
4.04
GD2DVP
3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2193_SRT-A
SingleAC106.28 %332.2B353.07
6.58
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC115.7 %830.96B961.39
15.94
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC110.58 %830.96B918.86
15.07
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC115.51 %830.96B959.87
15.94
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC110.39 %830.96B917.31
15.07
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC117.38 %830.96B975.35
14.85
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC114.63 %830.96B952.49
13.96
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC120.16 %808.4B971.38
14.85
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC117.33 %808.4B948.5
13.96
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC119.55 %808.4B966.48
14.85
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC116.72 %808.4B943.57
13.96
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC111.3 %698.42B777.36
28.63
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.09 %698.42B775.9
30.1

Details for 3BREMO-3FORK UNION 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.22 %
Rating:179.54 MVA
Rating Type:B
MVA to Mitigate:190.71
MW Contribution:
4.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
1.009
3146776BUCKING
Solar/Wind Harmer
0.082
958131AF2-107 GEN
Solar/Wind Harmer
1.515
970221AG2-151 GEN
Solar/Wind Harmer
10.497
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.091
3146776BUCKING
Solar/Wind Harmer
0.101
3146926FARMVIL
Solar/Wind Harmer
0.119
3146926FARMVIL
Solar/Wind Harmer
0.119
970301AG2-198 GEN
Solar/Wind Harmer
2.36
972205AH1-687 GEN
50/50
5.598
971377AH1-170 GEN
Solar/Wind Harmer
2.099
3147133PAMPLIN
Solar/Wind Harmer
0.146
970937AG2-583 GEN
Solar/Wind Harmer
5.978
971845AH1-439 GEN
Solar/Wind Harmer
4.212
316336AC2-165 C
Solar/Wind Harmer
3.814
3147133PAMPLIN
Solar/Wind Harmer
0.458
3147133PAMPLIN
Solar/Wind Harmer
0.117
970909AG2-566 GEN
50/50
1.526
3147623JAMES R
Solar/Wind Harmer
0.274
972003AH1-546 GEN
Solar/Wind Harmer
4.037
315821AE2-092 GEN
Solar/Wind Helper
6.339
942461AE2-259 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.656
3143336POWHATN
Solar/Wind Harmer
0.558
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.467
CPLELTFEXP_CPLE->PJM
CLTF
0.775
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.048
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.057
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.017
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.507
TVALTFEXP_TVA->PJM
CLTF
0.155
LAGNLTFEXP_LAGN->PJM
CLTF
0.298
NYPJM->LTFIMP_NY
CLTF
0.138
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.217

Details for 3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.28 %
Rating:332.2 MVA
Rating Type:B
MVA to Mitigate:353.07
MW Contribution:
6.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
1.644
3146776BUCKING
Solar/Wind Harmer
0.133
946301AF1-294 GEN
Solar/Wind Harmer
1.826
3144303KENBRDG
Solar/Wind Harmer
0.145
958131AF2-107 GEN
Solar/Wind Harmer
2.492
970221AG2-151 GEN
Solar/Wind Harmer
17.151
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.148
3146776BUCKING
Solar/Wind Harmer
0.164
3146926FARMVIL
Solar/Wind Harmer
0.193
3146926FARMVIL
Solar/Wind Harmer
0.193
970301AG2-198 GEN
Solar/Wind Harmer
3.832
970685AG2-442 GEN
Solar/Wind Harmer
5.929
970323AG2-213 GEN
Solar/Wind Harmer
2.892
315785AD2-033 C
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
9.128
971563AH1-280 GEN
Solar/Wind Harmer
0.891
971775AH1-396 GEN
Solar/Wind Harmer
0.43
971377AH1-170 GEN
Solar/Wind Harmer
3.43
970257AG2-171 GEN
Solar/Wind Harmer
2.169
3147133PAMPLIN
Solar/Wind Harmer
0.237
958211AF2-115 GEN
Solar/Wind Harmer
1.114
959311AF2-222 GEN
Solar/Wind Harmer
6.245
970937AG2-583 GEN
Solar/Wind Harmer
9.732
971845AH1-439 GEN
Solar/Wind Harmer
6.86
316336AC2-165 C
Solar/Wind Harmer
6.192
3147133PAMPLIN
Solar/Wind Harmer
0.744
3147133PAMPLIN
Solar/Wind Harmer
0.19
961791AG1-021 GEN
Solar/Wind Harmer
0.891
970909AG2-566 GEN
50/50
2.477
970683AG2-441 GEN
Solar/Wind Harmer
4.574
3147623JAMES R
Solar/Wind Harmer
0.447
315821AE2-092 GEN
Solar/Wind Harmer
0
972003AH1-546 GEN
Solar/Wind Harmer
6.581
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
3.738
3143336POWHATN
Solar/Wind Harmer
1.063
3143336POWHATN
Solar/Wind Harmer
0.904
970681AG2-440 GEN
Solar/Wind Harmer
3.036
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.466
TVALTFEXP_TVA->PJM
CLTF
0.268
LAGNLTFEXP_LAGN->PJM
CLTF
0.513
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.818
CPLELTFEXP_CPLE->PJM
CLTF
1.252
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.049
NYPJM->LTFIMP_NY
CLTF
0.266
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.019
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.904
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.049
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.698

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.7 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:961.39
MW Contribution:
15.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
4.029
3146776BUCKING
Solar/Wind Harmer
0.326
946301AF1-294 GEN
Solar/Wind Harmer
4.669
3144303KENBRDG
Solar/Wind Harmer
0.377
970119AG2-088 GEN
50/50
16.372
3146776BUCKING
Solar/Wind Harmer
0.363
970221AG2-151 GEN
Solar/Wind Harmer
6.657
971223AH1-071 GEN
Solar/Wind Harmer
1.266
970535AG2-341 GEN
50/50
5.498
972187AH1-678 GEN
50/50
2.536
315779AE2-040
50/50
1.06
3146776BUCKING
Solar/Wind Harmer
0.403
941591AE2-156 GEN
50/50
5.873
3146926FARMVIL
Solar/Wind Harmer
0.482
3146926FARMVIL
Solar/Wind Harmer
0.482
970301AG2-198 GEN
Solar/Wind Harmer
9.825
970685AG2-442 GEN
Solar/Wind Harmer
15.222
3143226MDLTHAN
Solar/Wind Harmer
0.317
966001AG1-469 GEN
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
1.096
957481AF2-042 GEN
Solar/Wind Harmer
8.44
970323AG2-213 GEN
Solar/Wind Harmer
7.534
315785AD2-033 C
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
22.076
970533AG2-339 GEN
50/50
6.242
971563AH1-280 GEN
Solar/Wind Harmer
2.278
971775AH1-396 GEN
Solar/Wind Harmer
1.12
315693AD1-088 GEN
Solar/Wind Harmer
5.728
970257AG2-171 GEN
Solar/Wind Harmer
5.65
971377AH1-170 GEN
Solar/Wind Harmer
1.331
963041AG1-153 GEN
50/50
5.594
3147133PAMPLIN
Solar/Wind Harmer
0.603
958211AF2-115 GEN
Solar/Wind Harmer
2.847
959311AF2-222 GEN
Solar/Wind Harmer
16.214
970937AG2-583 GEN
Solar/Wind Harmer
23.961
971845AH1-439 GEN
Solar/Wind Harmer
16.828
316336AC2-165 C
Solar/Wind Harmer
15.777
3147133PAMPLIN
Solar/Wind Harmer
1.893
316499AE2-029_GEN
Solar/Wind Helper
0.952
316303AF2-085
50/50
2.183
3147043LAWRENC
50/50
0.978
3147133PAMPLIN
Solar/Wind Harmer
0.482
961791AG1-021 GEN
Solar/Wind Harmer
2.278
316192AB2-158 GEN
Solar/Wind Helper
1.359
970909AG2-566 GEN
50/50
6.352
970413AG2-270 GEN
50/50
15.273
970683AG2-441 GEN
Solar/Wind Harmer
11.789
972003AH1-546 GEN
Solar/Wind Harmer
15.936
3147623JAMES R
Solar/Wind Harmer
0.174
972185AH1-677 GEN
50/50
4.974
944641AF1-129 GEN
50/50
16.687
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
9.936
970099AG2-077 GEN
Solar/Wind Harmer
3.376
3143336POWHATN
Solar/Wind Harmer
2.766
3143336POWHATN
Solar/Wind Harmer
2.351
970681AG2-440 GEN
Solar/Wind Harmer
7.824
962561AG1-105 GEN
Solar/Wind Harmer
5.385
NYPJM->LTFIMP_NY
CLTF
0.692
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.095
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.518
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.42
TVALTFEXP_TVA->PJM
CLTF
0.734
LAGNLTFEXP_LAGN->PJM
CLTF
1.421
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.957
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.068
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.193
CPLELTFEXP_CPLE->PJM
CLTF
3.886
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.269

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.58 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:918.86
MW Contribution:
15.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.765
3146776BUCKING
Solar/Wind Harmer
0.305
946301AF1-294 GEN
Solar/Wind Harmer
4.175
3144303KENBRDG
Solar/Wind Harmer
0.33
970119AG2-088 GEN
50/50
11.148
3146776BUCKING
Solar/Wind Harmer
0.339
970221AG2-151 GEN
Solar/Wind Harmer
5.451
970535AG2-341 GEN
50/50
4.553
3146776BUCKING
Solar/Wind Harmer
0.376
964791AG1-342 GEN
Solar/Wind Harmer
1.745
3146926FARMVIL
Solar/Wind Harmer
0.442
3146926FARMVIL
Solar/Wind Harmer
0.442
970301AG2-198 GEN
Solar/Wind Harmer
8.757
970685AG2-442 GEN
Solar/Wind Harmer
13.551
315616AA1-038_C
Solar/Wind Helper
1.717
966001AG1-469 GEN
Solar/Wind Helper
0.328
957481AF2-042 GEN
Solar/Wind Harmer
5.432
970323AG2-213 GEN
Solar/Wind Harmer
6.607
315785AD2-033 C
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
20.909
971563AH1-280 GEN
Solar/Wind Harmer
2.037
971775AH1-396 GEN
Solar/Wind Harmer
0.982
315693AD1-088 GEN
Solar/Wind Harmer
4.641
315760AF1-028 GEN
50/50
Charging
15.654
970117AG2-086 GEN
50/50
Charging
1.264
970257AG2-171 GEN
Solar/Wind Harmer
4.955
971377AH1-170 GEN
Solar/Wind Harmer
1.09
3147133PAMPLIN
Solar/Wind Harmer
0.542
958211AF2-115 GEN
Solar/Wind Harmer
2.546
959311AF2-222 GEN
Solar/Wind Harmer
14.268
3146843MT LREL
Solar/Wind Harmer
0.242
3146843MT LREL
Solar/Wind Harmer
0.242
970937AG2-583 GEN
Solar/Wind Harmer
22.254
971845AH1-439 GEN
Solar/Wind Harmer
15.705
316336AC2-165 C
Solar/Wind Harmer
14.108
3147133PAMPLIN
Solar/Wind Harmer
1.701
316499AE2-029_GEN
Solar/Wind Helper
1.241
316303AF2-085
50/50
1.486
3147043LAWRENC
50/50
0.752
3147133PAMPLIN
Solar/Wind Harmer
0.433
961791AG1-021 GEN
Solar/Wind Harmer
2.037
316192AB2-158 GEN
Solar/Wind Helper
1.365
970909AG2-566 GEN
50/50
5.662
970413AG2-270 GEN
50/50
11.968
970683AG2-441 GEN
Solar/Wind Harmer
10.452
972003AH1-546 GEN
Solar/Wind Harmer
15.074
3147623JAMES R
Solar/Wind Harmer
0.142
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
8.531
970401AG2-262 GEN
Solar/Wind Harmer
0.533
970099AG2-077 GEN
Solar/Wind Harmer
2.173
3143336POWHATN
Solar/Wind Harmer
2.417
3143336POWHATN
Solar/Wind Harmer
2.055
970681AG2-440 GEN
Solar/Wind Harmer
6.937
962561AG1-105 GEN
Solar/Wind Harmer
4.526
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.449
NYPJM->LTFIMP_NY
CLTF
0.698
TVALTFEXP_TVA->PJM
CLTF
1.131
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
9.964
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.939
CPLELTFEXP_CPLE->PJM
CLTF
3.189
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.719
LGEELTFEXP_LGEE->PJM
CLTF
0.289
MECLTFEXP_MEC->PJM
CLTF
0.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.78
WECLTFEXP_WEC->PJM
CLTF
0.139
LAGNLTFEXP_LAGN->PJM
CLTF
2.161

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.51 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:959.87
MW Contribution:
15.94
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
4.029
3146776BUCKING
Solar/Wind Harmer
0.326
946301AF1-294 GEN
Solar/Wind Harmer
4.669
3144303KENBRDG
Solar/Wind Harmer
0.377
970119AG2-088 GEN
50/50
16.372
3146776BUCKING
Solar/Wind Harmer
0.363
970221AG2-151 GEN
Solar/Wind Harmer
6.657
971223AH1-071 GEN
Solar/Wind Harmer
1.266
970535AG2-341 GEN
50/50
5.498
972187AH1-678 GEN
50/50
2.536
315779AE2-040
50/50
1.06
3146776BUCKING
Solar/Wind Harmer
0.403
941591AE2-156 GEN
50/50
5.873
3146926FARMVIL
Solar/Wind Harmer
0.482
3146926FARMVIL
Solar/Wind Harmer
0.482
970301AG2-198 GEN
Solar/Wind Harmer
9.825
970685AG2-442 GEN
Solar/Wind Harmer
15.222
3143226MDLTHAN
Solar/Wind Harmer
0.317
966001AG1-469 GEN
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
1.096
957481AF2-042 GEN
Solar/Wind Harmer
8.44
970323AG2-213 GEN
Solar/Wind Harmer
7.534
315785AD2-033 C
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
22.076
970533AG2-339 GEN
50/50
6.242
971563AH1-280 GEN
Solar/Wind Harmer
2.278
971775AH1-396 GEN
Solar/Wind Harmer
1.12
315693AD1-088 GEN
Solar/Wind Harmer
5.728
970257AG2-171 GEN
Solar/Wind Harmer
5.65
971377AH1-170 GEN
Solar/Wind Harmer
1.331
963041AG1-153 GEN
50/50
5.594
3147133PAMPLIN
Solar/Wind Harmer
0.603
958211AF2-115 GEN
Solar/Wind Harmer
2.847
959311AF2-222 GEN
Solar/Wind Harmer
16.214
970937AG2-583 GEN
Solar/Wind Harmer
23.961
971845AH1-439 GEN
Solar/Wind Harmer
16.828
316336AC2-165 C
Solar/Wind Harmer
15.777
3147133PAMPLIN
Solar/Wind Harmer
1.893
316499AE2-029_GEN
Solar/Wind Helper
0.952
316303AF2-085
50/50
2.183
3147043LAWRENC
50/50
0.978
3147133PAMPLIN
Solar/Wind Harmer
0.482
961791AG1-021 GEN
Solar/Wind Harmer
2.278
316192AB2-158 GEN
Solar/Wind Helper
1.359
970909AG2-566 GEN
50/50
6.352
970413AG2-270 GEN
50/50
15.273
970683AG2-441 GEN
Solar/Wind Harmer
11.789
972003AH1-546 GEN
Solar/Wind Harmer
15.936
3147623JAMES R
Solar/Wind Harmer
0.174
972185AH1-677 GEN
50/50
4.974
944641AF1-129 GEN
50/50
16.687
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
9.936
970099AG2-077 GEN
Solar/Wind Harmer
3.376
3143336POWHATN
Solar/Wind Harmer
2.766
3143336POWHATN
Solar/Wind Harmer
2.351
970681AG2-440 GEN
Solar/Wind Harmer
7.824
962561AG1-105 GEN
Solar/Wind Harmer
5.385
NYPJM->LTFIMP_NY
CLTF
0.692
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.095
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.518
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.42
TVALTFEXP_TVA->PJM
CLTF
0.734
LAGNLTFEXP_LAGN->PJM
CLTF
1.421
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.957
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MECLTFEXP_MEC->PJM
CLTF
0.068
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.193
CPLELTFEXP_CPLE->PJM
CLTF
3.886
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.269

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.39 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:917.31
MW Contribution:
15.07
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.765
3146776BUCKING
Solar/Wind Harmer
0.305
946301AF1-294 GEN
Solar/Wind Harmer
4.175
3144303KENBRDG
Solar/Wind Harmer
0.33
970119AG2-088 GEN
50/50
11.148
3146776BUCKING
Solar/Wind Harmer
0.339
970221AG2-151 GEN
Solar/Wind Harmer
5.451
970535AG2-341 GEN
50/50
4.553
3146776BUCKING
Solar/Wind Harmer
0.376
964791AG1-342 GEN
Solar/Wind Harmer
1.745
3146926FARMVIL
Solar/Wind Harmer
0.442
3146926FARMVIL
Solar/Wind Harmer
0.442
970301AG2-198 GEN
Solar/Wind Harmer
8.757
970685AG2-442 GEN
Solar/Wind Harmer
13.551
315616AA1-038_C
Solar/Wind Helper
1.717
966001AG1-469 GEN
Solar/Wind Helper
0.328
957481AF2-042 GEN
Solar/Wind Harmer
5.432
970323AG2-213 GEN
Solar/Wind Harmer
6.607
315785AD2-033 C
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
20.909
971563AH1-280 GEN
Solar/Wind Harmer
2.037
971775AH1-396 GEN
Solar/Wind Harmer
0.982
315693AD1-088 GEN
Solar/Wind Harmer
4.641
315760AF1-028 GEN
50/50
Charging
15.654
970117AG2-086 GEN
50/50
Charging
1.264
970257AG2-171 GEN
Solar/Wind Harmer
4.955
971377AH1-170 GEN
Solar/Wind Harmer
1.09
3147133PAMPLIN
Solar/Wind Harmer
0.542
958211AF2-115 GEN
Solar/Wind Harmer
2.546
959311AF2-222 GEN
Solar/Wind Harmer
14.268
3146843MT LREL
Solar/Wind Harmer
0.242
3146843MT LREL
Solar/Wind Harmer
0.242
970937AG2-583 GEN
Solar/Wind Harmer
22.254
971845AH1-439 GEN
Solar/Wind Harmer
15.705
316336AC2-165 C
Solar/Wind Harmer
14.108
3147133PAMPLIN
Solar/Wind Harmer
1.701
316499AE2-029_GEN
Solar/Wind Helper
1.241
316303AF2-085
50/50
1.486
3147043LAWRENC
50/50
0.752
3147133PAMPLIN
Solar/Wind Harmer
0.433
961791AG1-021 GEN
Solar/Wind Harmer
2.037
316192AB2-158 GEN
Solar/Wind Helper
1.365
970909AG2-566 GEN
50/50
5.662
970413AG2-270 GEN
50/50
11.968
970683AG2-441 GEN
Solar/Wind Harmer
10.452
972003AH1-546 GEN
Solar/Wind Harmer
15.074
3147623JAMES R
Solar/Wind Harmer
0.142
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
8.531
970401AG2-262 GEN
Solar/Wind Harmer
0.533
970099AG2-077 GEN
Solar/Wind Harmer
2.173
3143336POWHATN
Solar/Wind Harmer
2.417
3143336POWHATN
Solar/Wind Harmer
2.055
970681AG2-440 GEN
Solar/Wind Harmer
6.937
962561AG1-105 GEN
Solar/Wind Harmer
4.526
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.939
CPLELTFEXP_CPLE->PJM
CLTF
3.189
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.78
WECLTFEXP_WEC->PJM
CLTF
0.139
LAGNLTFEXP_LAGN->PJM
CLTF
2.161
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.449
NYPJM->LTFIMP_NY
CLTF
0.698
TVALTFEXP_TVA->PJM
CLTF
1.131
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
9.964
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.719
LGEELTFEXP_LGEE->PJM
CLTF
0.289
MECLTFEXP_MEC->PJM
CLTF
0.859

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.38 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:975.35
MW Contribution:
14.85
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.755
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.367
3144303KENBRDG
Solar/Wind Harmer
0.353
958131AF2-107 GEN
Solar/Wind Harmer
3.053
970119AG2-088 GEN
50/50
15.11
970221AG2-151 GEN
Solar/Wind Harmer
20.797
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
971223AH1-071 GEN
Solar/Wind Harmer
1.169
970535AG2-341 GEN
50/50
5.173
972187AH1-678 GEN
50/50
2.361
315779AE2-040
50/50
0.981
3146776BUCKING
Solar/Wind Harmer
0.376
941591AE2-156 GEN
50/50
5.394
3146926FARMVIL
Solar/Wind Harmer
0.449
3146926FARMVIL
Solar/Wind Harmer
0.449
970301AG2-198 GEN
Solar/Wind Harmer
9.17
970685AG2-442 GEN
Solar/Wind Harmer
14.242
3143226MDLTHAN
Solar/Wind Harmer
0.292
966001AG1-469 GEN
Solar/Wind Helper
0.335
315616AA1-038_C
Solar/Wind Helper
1.054
957481AF2-042 GEN
Solar/Wind Harmer
6.021
970323AG2-213 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
20.567
970533AG2-339 GEN
50/50
5.794
971563AH1-280 GEN
Solar/Wind Harmer
2.13
971775AH1-396 GEN
Solar/Wind Harmer
1.049
315693AD1-088 GEN
Solar/Wind Harmer
5.357
315760AF1-028 GEN
50/50
Charging
11.367
971377AH1-170 GEN
Solar/Wind Harmer
4.159
970257AG2-171 GEN
Solar/Wind Harmer
5.295
963041AG1-153 GEN
50/50
5.208
3147133PAMPLIN
Solar/Wind Harmer
0.563
958211AF2-115 GEN
Solar/Wind Harmer
2.663
959311AF2-222 GEN
Solar/Wind Harmer
15.189
970937AG2-583 GEN
Solar/Wind Harmer
22.308
971845AH1-439 GEN
Solar/Wind Harmer
15.686
316336AC2-165 C
Solar/Wind Harmer
14.671
3147133PAMPLIN
Solar/Wind Harmer
1.769
316499AE2-029_GEN
Solar/Wind Helper
0.93
316303AF2-085
50/50
2.015
3147043LAWRENC
50/50
0.917
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.13
316192AB2-158 GEN
Solar/Wind Helper
1.485
970909AG2-566 GEN
50/50
5.929
970413AG2-270 GEN
50/50
14.332
970683AG2-441 GEN
Solar/Wind Harmer
11.035
972003AH1-546 GEN
Solar/Wind Harmer
14.847
3147623JAMES R
Solar/Wind Harmer
0.542
315821AE2-092 GEN
Solar/Wind Harmer
0
972185AH1-677 GEN
50/50
4.626
944641AF1-129 GEN
50/50
25.925
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
9.33
970099AG2-077 GEN
Solar/Wind Harmer
2.409
3143336POWHATN
Solar/Wind Harmer
2.57
3143336POWHATN
Solar/Wind Harmer
2.185
970681AG2-440 GEN
Solar/Wind Harmer
7.324
962561AG1-105 GEN
Solar/Wind Harmer
5.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.388
TVALTFEXP_TVA->PJM
CLTF
0.837
LAGNLTFEXP_LAGN->PJM
CLTF
1.615
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.599
CPLELTFEXP_CPLE->PJM
CLTF
3.766
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.728
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.01
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.414
LGEELTFEXP_LGEE->PJM
CLTF
0.006
MECLTFEXP_MEC->PJM
CLTF
0.263
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.464

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.63 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:952.49
MW Contribution:
13.96
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.488
3146776BUCKING
Solar/Wind Harmer
0.282
946301AF1-294 GEN
Solar/Wind Harmer
3.878
3144303KENBRDG
Solar/Wind Harmer
0.308
958131AF2-107 GEN
Solar/Wind Harmer
3.307
970119AG2-088 GEN
50/50
9.919
970221AG2-151 GEN
Solar/Wind Harmer
19.558
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
970535AG2-341 GEN
50/50
4.255
3146776BUCKING
Solar/Wind Harmer
0.349
964791AG1-342 GEN
Solar/Wind Harmer
1.658
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970301AG2-198 GEN
Solar/Wind Harmer
8.11
970685AG2-442 GEN
Solar/Wind Harmer
12.594
966001AG1-469 GEN
Solar/Wind Helper
0.359
315616AA1-038_C
Solar/Wind Helper
1.731
957481AF2-042 GEN
Solar/Wind Harmer
3.595
970323AG2-213 GEN
Solar/Wind Harmer
6.151
315785AD2-033 C
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
19.37
971563AH1-280 GEN
Solar/Wind Harmer
1.892
971775AH1-396 GEN
Solar/Wind Harmer
0.914
315693AD1-088 GEN
Solar/Wind Harmer
4.291
315760AF1-028 GEN
50/50
Charging
15.733
970117AG2-086 GEN
50/50
Charging
1.277
971377AH1-170 GEN
Solar/Wind Harmer
3.912
970257AG2-171 GEN
Solar/Wind Harmer
4.613
3147133PAMPLIN
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
2.365
959311AF2-222 GEN
Solar/Wind Harmer
13.277
3146843MT LREL
Solar/Wind Harmer
0.23
3146843MT LREL
Solar/Wind Harmer
0.23
970937AG2-583 GEN
Solar/Wind Harmer
20.574
971845AH1-439 GEN
Solar/Wind Harmer
14.549
316336AC2-165 C
Solar/Wind Harmer
12.991
3147133PAMPLIN
Solar/Wind Harmer
1.579
316499AE2-029_GEN
Solar/Wind Helper
1.245
316303AF2-085
50/50
1.323
3147043LAWRENC
50/50
0.696
3147133PAMPLIN
Solar/Wind Harmer
0.402
961791AG1-021 GEN
Solar/Wind Harmer
1.892
316192AB2-158 GEN
Solar/Wind Helper
1.526
970909AG2-566 GEN
50/50
5.243
970413AG2-270 GEN
50/50
11.112
970683AG2-441 GEN
Solar/Wind Harmer
9.719
972003AH1-546 GEN
Solar/Wind Harmer
13.964
3147623JAMES R
Solar/Wind Harmer
0.51
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
7.96
970401AG2-262 GEN
Solar/Wind Harmer
0.507
970099AG2-077 GEN
Solar/Wind Harmer
1.438
3143336POWHATN
Solar/Wind Harmer
2.22
3143336POWHATN
Solar/Wind Harmer
1.887
970681AG2-440 GEN
Solar/Wind Harmer
6.45
962561AG1-105 GEN
Solar/Wind Harmer
4.288
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.207
CPLELTFEXP_CPLE->PJM
CLTF
3.164
SIGELTFEXP_SIGE->PJM
CLTF
0.036
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.536
WECLTFEXP_WEC->PJM
CLTF
0.212
LAGNLTFEXP_LAGN->PJM
CLTF
2.539
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.108
NYPJM->LTFIMP_NY
CLTF
0.768
TVALTFEXP_TVA->PJM
CLTF
1.33
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.318
LGEELTFEXP_LGEE->PJM
CLTF
0.434
MECLTFEXP_MEC->PJM
CLTF
1.183

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.16 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:971.38
MW Contribution:
14.85
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.755
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.367
3144303KENBRDG
Solar/Wind Harmer
0.353
958131AF2-107 GEN
Solar/Wind Harmer
3.053
970119AG2-088 GEN
50/50
15.11
970221AG2-151 GEN
Solar/Wind Harmer
20.797
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
971223AH1-071 GEN
Solar/Wind Harmer
1.169
970535AG2-341 GEN
50/50
5.173
972187AH1-678 GEN
50/50
2.361
315779AE2-040
50/50
0.981
3146776BUCKING
Solar/Wind Harmer
0.376
941591AE2-156 GEN
50/50
5.394
3146926FARMVIL
Solar/Wind Harmer
0.449
3146926FARMVIL
Solar/Wind Harmer
0.449
970301AG2-198 GEN
Solar/Wind Harmer
9.17
970685AG2-442 GEN
Solar/Wind Harmer
14.242
3143226MDLTHAN
Solar/Wind Harmer
0.292
966001AG1-469 GEN
Solar/Wind Helper
0.335
315616AA1-038_C
Solar/Wind Helper
1.054
957481AF2-042 GEN
Solar/Wind Harmer
6.021
970323AG2-213 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
20.567
970533AG2-339 GEN
50/50
5.794
971563AH1-280 GEN
Solar/Wind Harmer
2.13
971775AH1-396 GEN
Solar/Wind Harmer
1.049
315693AD1-088 GEN
Solar/Wind Harmer
5.357
315760AF1-028 GEN
50/50
Charging
11.367
971377AH1-170 GEN
Solar/Wind Harmer
4.159
970257AG2-171 GEN
Solar/Wind Harmer
5.295
963041AG1-153 GEN
50/50
5.208
3147133PAMPLIN
Solar/Wind Harmer
0.563
958211AF2-115 GEN
Solar/Wind Harmer
2.663
959311AF2-222 GEN
Solar/Wind Harmer
15.189
970937AG2-583 GEN
Solar/Wind Harmer
22.308
971845AH1-439 GEN
Solar/Wind Harmer
15.686
316336AC2-165 C
Solar/Wind Harmer
14.671
3147133PAMPLIN
Solar/Wind Harmer
1.769
316499AE2-029_GEN
Solar/Wind Helper
0.93
316303AF2-085
50/50
2.015
3147043LAWRENC
50/50
0.917
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.13
316192AB2-158 GEN
Solar/Wind Helper
1.485
970909AG2-566 GEN
50/50
5.929
970413AG2-270 GEN
50/50
14.332
970683AG2-441 GEN
Solar/Wind Harmer
11.035
972003AH1-546 GEN
Solar/Wind Harmer
14.847
3147623JAMES R
Solar/Wind Harmer
0.542
315821AE2-092 GEN
Solar/Wind Harmer
0
972185AH1-677 GEN
50/50
4.626
944641AF1-129 GEN
50/50
25.925
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
9.33
970099AG2-077 GEN
Solar/Wind Harmer
2.409
3143336POWHATN
Solar/Wind Harmer
2.57
3143336POWHATN
Solar/Wind Harmer
2.185
970681AG2-440 GEN
Solar/Wind Harmer
7.324
962561AG1-105 GEN
Solar/Wind Harmer
5.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.414
LGEELTFEXP_LGEE->PJM
CLTF
0.006
MECLTFEXP_MEC->PJM
CLTF
0.263
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.464
NYPJM->LTFIMP_NY
CLTF
0.728
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.01
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.599
CPLELTFEXP_CPLE->PJM
CLTF
3.766
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.005
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.388
TVALTFEXP_TVA->PJM
CLTF
0.837
LAGNLTFEXP_LAGN->PJM
CLTF
1.615

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.33 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:948.5
MW Contribution:
13.96
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.488
3146776BUCKING
Solar/Wind Harmer
0.282
946301AF1-294 GEN
Solar/Wind Harmer
3.878
3144303KENBRDG
Solar/Wind Harmer
0.308
958131AF2-107 GEN
Solar/Wind Harmer
3.307
970119AG2-088 GEN
50/50
9.919
970221AG2-151 GEN
Solar/Wind Harmer
19.558
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
970535AG2-341 GEN
50/50
4.255
3146776BUCKING
Solar/Wind Harmer
0.349
964791AG1-342 GEN
Solar/Wind Harmer
1.658
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970301AG2-198 GEN
Solar/Wind Harmer
8.11
970685AG2-442 GEN
Solar/Wind Harmer
12.594
966001AG1-469 GEN
Solar/Wind Helper
0.359
315616AA1-038_C
Solar/Wind Helper
1.731
957481AF2-042 GEN
Solar/Wind Harmer
3.595
970323AG2-213 GEN
Solar/Wind Harmer
6.151
315785AD2-033 C
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
19.37
971563AH1-280 GEN
Solar/Wind Harmer
1.892
971775AH1-396 GEN
Solar/Wind Harmer
0.914
315693AD1-088 GEN
Solar/Wind Harmer
4.291
315760AF1-028 GEN
50/50
Charging
15.733
970117AG2-086 GEN
50/50
Charging
1.277
971377AH1-170 GEN
Solar/Wind Harmer
3.912
970257AG2-171 GEN
Solar/Wind Harmer
4.613
3147133PAMPLIN
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
2.365
959311AF2-222 GEN
Solar/Wind Harmer
13.277
3146843MT LREL
Solar/Wind Harmer
0.23
3146843MT LREL
Solar/Wind Harmer
0.23
970937AG2-583 GEN
Solar/Wind Harmer
20.574
971845AH1-439 GEN
Solar/Wind Harmer
14.549
316336AC2-165 C
Solar/Wind Harmer
12.991
3147133PAMPLIN
Solar/Wind Harmer
1.579
316499AE2-029_GEN
Solar/Wind Helper
1.245
316303AF2-085
50/50
1.323
3147043LAWRENC
50/50
0.696
3147133PAMPLIN
Solar/Wind Harmer
0.402
961791AG1-021 GEN
Solar/Wind Harmer
1.892
316192AB2-158 GEN
Solar/Wind Helper
1.526
970909AG2-566 GEN
50/50
5.243
970413AG2-270 GEN
50/50
11.112
970683AG2-441 GEN
Solar/Wind Harmer
9.719
972003AH1-546 GEN
Solar/Wind Harmer
13.964
3147623JAMES R
Solar/Wind Harmer
0.51
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
7.96
970401AG2-262 GEN
Solar/Wind Harmer
0.507
970099AG2-077 GEN
Solar/Wind Harmer
1.438
3143336POWHATN
Solar/Wind Harmer
2.22
3143336POWHATN
Solar/Wind Harmer
1.887
970681AG2-440 GEN
Solar/Wind Harmer
6.45
962561AG1-105 GEN
Solar/Wind Harmer
4.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.318
LGEELTFEXP_LGEE->PJM
CLTF
0.434
MECLTFEXP_MEC->PJM
CLTF
1.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.108
NYPJM->LTFIMP_NY
CLTF
0.768
TVALTFEXP_TVA->PJM
CLTF
1.33
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.536
WECLTFEXP_WEC->PJM
CLTF
0.212
LAGNLTFEXP_LAGN->PJM
CLTF
2.539
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.207
CPLELTFEXP_CPLE->PJM
CLTF
3.164
SIGELTFEXP_SIGE->PJM
CLTF
0.036

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.55 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:966.48
MW Contribution:
14.85
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.755
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.367
3144303KENBRDG
Solar/Wind Harmer
0.353
958131AF2-107 GEN
Solar/Wind Harmer
3.053
970119AG2-088 GEN
50/50
15.11
970221AG2-151 GEN
Solar/Wind Harmer
20.797
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
971223AH1-071 GEN
Solar/Wind Harmer
1.169
970535AG2-341 GEN
50/50
5.173
972187AH1-678 GEN
50/50
2.361
315779AE2-040
50/50
0.981
3146776BUCKING
Solar/Wind Harmer
0.376
941591AE2-156 GEN
50/50
5.394
3146926FARMVIL
Solar/Wind Harmer
0.449
3146926FARMVIL
Solar/Wind Harmer
0.449
970301AG2-198 GEN
Solar/Wind Harmer
9.17
970685AG2-442 GEN
Solar/Wind Harmer
14.242
3143226MDLTHAN
Solar/Wind Harmer
0.292
966001AG1-469 GEN
Solar/Wind Helper
0.335
315616AA1-038_C
Solar/Wind Helper
1.054
957481AF2-042 GEN
Solar/Wind Harmer
6.021
970323AG2-213 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
20.567
970533AG2-339 GEN
50/50
5.794
971563AH1-280 GEN
Solar/Wind Harmer
2.13
971775AH1-396 GEN
Solar/Wind Harmer
1.049
315693AD1-088 GEN
Solar/Wind Harmer
5.357
315760AF1-028 GEN
50/50
Charging
11.367
971377AH1-170 GEN
Solar/Wind Harmer
4.159
970257AG2-171 GEN
Solar/Wind Harmer
5.295
963041AG1-153 GEN
50/50
5.208
3147133PAMPLIN
Solar/Wind Harmer
0.563
958211AF2-115 GEN
Solar/Wind Harmer
2.663
959311AF2-222 GEN
Solar/Wind Harmer
15.189
970937AG2-583 GEN
Solar/Wind Harmer
22.308
971845AH1-439 GEN
Solar/Wind Harmer
15.686
316336AC2-165 C
Solar/Wind Harmer
14.671
3147133PAMPLIN
Solar/Wind Harmer
1.769
316499AE2-029_GEN
Solar/Wind Helper
0.93
316303AF2-085
50/50
2.015
3147043LAWRENC
50/50
0.917
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.13
316192AB2-158 GEN
Solar/Wind Helper
1.485
970909AG2-566 GEN
50/50
5.929
970413AG2-270 GEN
50/50
14.332
970683AG2-441 GEN
Solar/Wind Harmer
11.035
972003AH1-546 GEN
Solar/Wind Harmer
14.847
3147623JAMES R
Solar/Wind Harmer
0.542
315821AE2-092 GEN
Solar/Wind Harmer
0
972185AH1-677 GEN
50/50
4.626
944641AF1-129 GEN
50/50
25.925
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
9.33
970099AG2-077 GEN
Solar/Wind Harmer
2.409
3143336POWHATN
Solar/Wind Harmer
2.57
3143336POWHATN
Solar/Wind Harmer
2.185
970681AG2-440 GEN
Solar/Wind Harmer
7.324
962561AG1-105 GEN
Solar/Wind Harmer
5.111
NYPJM->LTFIMP_NY
CLTF
0.728
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.01
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.388
TVALTFEXP_TVA->PJM
CLTF
0.837
LAGNLTFEXP_LAGN->PJM
CLTF
1.615
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.414
LGEELTFEXP_LGEE->PJM
CLTF
0.006
MECLTFEXP_MEC->PJM
CLTF
0.263
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.464
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.599
CPLELTFEXP_CPLE->PJM
CLTF
3.766
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.005

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.72 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:943.57
MW Contribution:
13.96
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.488
3146776BUCKING
Solar/Wind Harmer
0.282
946301AF1-294 GEN
Solar/Wind Harmer
3.878
3144303KENBRDG
Solar/Wind Harmer
0.308
958131AF2-107 GEN
Solar/Wind Harmer
3.307
970119AG2-088 GEN
50/50
9.919
970221AG2-151 GEN
Solar/Wind Harmer
19.558
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
970535AG2-341 GEN
50/50
4.255
3146776BUCKING
Solar/Wind Harmer
0.349
964791AG1-342 GEN
Solar/Wind Harmer
1.658
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970301AG2-198 GEN
Solar/Wind Harmer
8.11
970685AG2-442 GEN
Solar/Wind Harmer
12.594
966001AG1-469 GEN
Solar/Wind Helper
0.359
315616AA1-038_C
Solar/Wind Helper
1.731
957481AF2-042 GEN
Solar/Wind Harmer
3.595
970323AG2-213 GEN
Solar/Wind Harmer
6.151
315785AD2-033 C
Solar/Wind Harmer
0
972205AH1-687 GEN
50/50
19.37
971563AH1-280 GEN
Solar/Wind Harmer
1.892
971775AH1-396 GEN
Solar/Wind Harmer
0.914
315693AD1-088 GEN
Solar/Wind Harmer
4.291
315760AF1-028 GEN
50/50
Charging
15.733
970117AG2-086 GEN
50/50
Charging
1.277
971377AH1-170 GEN
Solar/Wind Harmer
3.912
970257AG2-171 GEN
Solar/Wind Harmer
4.613
3147133PAMPLIN
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
2.365
959311AF2-222 GEN
Solar/Wind Harmer
13.277
3146843MT LREL
Solar/Wind Harmer
0.23
3146843MT LREL
Solar/Wind Harmer
0.23
970937AG2-583 GEN
Solar/Wind Harmer
20.574
971845AH1-439 GEN
Solar/Wind Harmer
14.549
316336AC2-165 C
Solar/Wind Harmer
12.991
3147133PAMPLIN
Solar/Wind Harmer
1.579
316499AE2-029_GEN
Solar/Wind Helper
1.245
316303AF2-085
50/50
1.323
3147043LAWRENC
50/50
0.696
3147133PAMPLIN
Solar/Wind Harmer
0.402
961791AG1-021 GEN
Solar/Wind Harmer
1.892
316192AB2-158 GEN
Solar/Wind Helper
1.526
970909AG2-566 GEN
50/50
5.243
970413AG2-270 GEN
50/50
11.112
970683AG2-441 GEN
Solar/Wind Harmer
9.719
972003AH1-546 GEN
Solar/Wind Harmer
13.964
3147623JAMES R
Solar/Wind Harmer
0.51
315821AE2-092 GEN
Solar/Wind Harmer
0
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
7.96
970401AG2-262 GEN
Solar/Wind Harmer
0.507
970099AG2-077 GEN
Solar/Wind Harmer
1.438
3143336POWHATN
Solar/Wind Harmer
2.22
3143336POWHATN
Solar/Wind Harmer
1.887
970681AG2-440 GEN
Solar/Wind Harmer
6.45
962561AG1-105 GEN
Solar/Wind Harmer
4.288
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.108
NYPJM->LTFIMP_NY
CLTF
0.768
TVALTFEXP_TVA->PJM
CLTF
1.33
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.207
CPLELTFEXP_CPLE->PJM
CLTF
3.164
SIGELTFEXP_SIGE->PJM
CLTF
0.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.318
LGEELTFEXP_LGEE->PJM
CLTF
0.434
MECLTFEXP_MEC->PJM
CLTF
1.183
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.536
WECLTFEXP_WEC->PJM
CLTF
0.212
LAGNLTFEXP_LAGN->PJM
CLTF
2.539

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.3 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:777.36
MW Contribution:
28.63
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
7.104
3146776BUCKING
Solar/Wind Harmer
0.575
946301AF1-294 GEN
Solar/Wind Harmer
7.634
3144303KENBRDG
Solar/Wind Harmer
0.594
3146776BUCKING
Solar/Wind Harmer
0.639
270494AE1-108_GEN
Solar/Wind Helper
6.779
316313AB2-026
Solar/Wind Helper
0.586
970535AG2-341 GEN
50/50
7.78
972187AH1-678 GEN
50/50
2.477
315779AE2-040
50/50
0.832
3146776BUCKING
Solar/Wind Harmer
0.71
964791AG1-342 GEN
Solar/Wind Harmer
2.924
3146926FARMVIL
Solar/Wind Harmer
0.827
3146926FARMVIL
Solar/Wind Harmer
0.827
970301AG2-198 GEN
Solar/Wind Harmer
16.132
970685AG2-442 GEN
Solar/Wind Harmer
24.684
957481AF2-042 GEN
Solar/Wind Harmer
29.784
970323AG2-213 GEN
Solar/Wind Harmer
11.877
315785AD2-033 C
Solar/Wind Harmer
0
970533AG2-339 GEN
50/50
5.696
971563AH1-280 GEN
Solar/Wind Harmer
3.724
971775AH1-396 GEN
Solar/Wind Harmer
1.765
315693AD1-088 GEN
Solar/Wind Harmer
8.111
316405AF2-144 C
50/50
Charging
1.194
970257AG2-171 GEN
Solar/Wind Harmer
8.908
963041AG1-153 GEN
50/50
5.464
3147133PAMPLIN
Solar/Wind Harmer
0.995
958211AF2-115 GEN
Solar/Wind Harmer
4.655
959311AF2-222 GEN
Solar/Wind Harmer
25.726
3146843MT LREL
Solar/Wind Harmer
0.405
3146843MT LREL
Solar/Wind Harmer
0.405
971845AH1-439 GEN
Solar/Wind Harmer
29.619
3147133PAMPLIN
Solar/Wind Harmer
3.124
3147043LAWRENC
50/50
1.212
3147133PAMPLIN
Solar/Wind Harmer
0.796
961791AG1-021 GEN
Solar/Wind Harmer
3.724
970909AG2-566 GEN
50/50
10.43
970413AG2-270 GEN
50/50
20.271
970683AG2-441 GEN
Solar/Wind Harmer
18.972
316258AE1-075 C
Solar/Wind Helper
0.527
972003AH1-546 GEN
Solar/Wind Harmer
28.628
315821AE2-092 GEN
Solar/Wind Helper
5.466
972185AH1-677 GEN
50/50
4.762
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
15.043
970401AG2-262 GEN
Solar/Wind Harmer
0.893
970099AG2-077 GEN
Solar/Wind Harmer
11.914
970681AG2-440 GEN
Solar/Wind Harmer
12.592
962561AG1-105 GEN
Solar/Wind Harmer
7.634
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.025
WECLTFEXP_WEC->PJM
CLTF
0.125
LAGNLTFEXP_LAGN->PJM
CLTF
2.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.321
LGEELTFEXP_LGEE->PJM
CLTF
0.232
MECLTFEXP_MEC->PJM
CLTF
0.841
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.981
CPLELTFEXP_CPLE->PJM
CLTF
4.418
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.152
NYPJM->LTFIMP_NY
CLTF
0.591
TVALTFEXP_TVA->PJM
CLTF
1.227
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.09 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:775.9
MW Contribution:
30.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
7.851
3146776BUCKING
Solar/Wind Harmer
0.636
946301AF1-294 GEN
Solar/Wind Harmer
9.591
3144303KENBRDG
Solar/Wind Harmer
0.779
3146776BUCKING
Solar/Wind Harmer
0.707
270494AE1-108_GEN
Solar/Wind Helper
5.532
316313AB2-026
Solar/Wind Helper
0.506
970535AG2-341 GEN
50/50
11.523
3146776BUCKING
Solar/Wind Harmer
0.785
3146926FARMVIL
Solar/Wind Harmer
0.98
3146926FARMVIL
Solar/Wind Harmer
0.98
970301AG2-198 GEN
Solar/Wind Harmer
21.524
970685AG2-442 GEN
Solar/Wind Harmer
31.319
957481AF2-042 GEN
Solar/Wind Harmer
87.558
970323AG2-213 GEN
Solar/Wind Harmer
15.588
315785AD2-033 C
Solar/Wind Harmer
0
971563AH1-280 GEN
Solar/Wind Harmer
4.679
971775AH1-396 GEN
Solar/Wind Harmer
2.317
315693AD1-088 GEN
Solar/Wind Harmer
15.284
316405AF2-144 C
50/50
Charging
1.03
970257AG2-171 GEN
Solar/Wind Harmer
11.691
3147133PAMPLIN
Solar/Wind Harmer
1.236
958211AF2-115 GEN
Solar/Wind Harmer
5.848
959311AF2-222 GEN
Solar/Wind Harmer
33.506
971845AH1-439 GEN
Solar/Wind Harmer
32.89
3147133PAMPLIN
Solar/Wind Harmer
3.88
3147043LAWRENC
50/50
1.472
971629AH1-314 GEN
50/50
5.91
3147133PAMPLIN
Solar/Wind Harmer
0.989
961791AG1-021 GEN
Solar/Wind Harmer
4.679
970909AG2-566 GEN
50/50
13.916
970413AG2-270 GEN
50/50
42.63
970683AG2-441 GEN
Solar/Wind Harmer
24.293
316258AE1-075 C
Solar/Wind Helper
0.455
972003AH1-546 GEN
Solar/Wind Harmer
30.103
315821AE2-092 GEN
Solar/Wind Helper
4.587
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970099AG2-077 GEN
Solar/Wind Harmer
35.023
964241AG1-285 GEN
Solar/Wind Harmer
18.877
970681AG2-440 GEN
Solar/Wind Harmer
16.124
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.51
LGEELTFEXP_LGEE->PJM
CLTF
0.458
MECLTFEXP_MEC->PJM
CLTF
1.369
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.645
NYPJM->LTFIMP_NY
CLTF
0.539
TVALTFEXP_TVA->PJM
CLTF
1.544
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.222
WECLTFEXP_WEC->PJM
CLTF
0.245
LAGNLTFEXP_LAGN->PJM
CLTF
3.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.588
CPLELTFEXP_CPLE->PJM
CLTF
4.408
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-L'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-L'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3359 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 3377 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
314744 to 313708 ckt 2
313708 to 313707 ckt 1
314747 to 313867 ckt 1
313867 to 313707 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1
972002 to 314747 ckt 1

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 2 Cluster 3 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 3 projects.

 

Table 1: Transition Cycle 2 Cluster 3 Projects

 

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Trans. Owner

MFO (MW)

MWE

(MW)

MWC

(MW)

Point of Interconnection

3

AG2-151

PV

Dominion

100

100

60

Trices Lake - James River Tap 115 kV

AG2-198

PV

Dominion

80

80

48

Briery - Finneywood 230 kV

AG2-566

BS

Dominion

30

30

12

Briery - Finneywood 230 kV

AG2-583

PV

Dominion

115

115

69

Bremo - Cartersville 230 kV

AH1-170

PV

Dominion

20

20

12

Columbia DP 115 kV

AH1-439

PV

Dominion

85

85

51

Buckingham - Farmville 230 kV

AH1-546

PV

Dominion

65

65

39

Bremo - Buckingham 230 kV

 

The purpose of the transient stability analysis is to determine the system impact of the generation facility. This study will determine system improvements, if any, needed to reduce violations in the transient stability analysis caused by the addition of the projects in Cluster 3.

 

The load flow scenario for the analysis was based on the Regional Transmission Expansion Plan (RTEP) 2028 summer peak case, modified to include applicable projects. The TC2 Cluster 3 projects have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer.

 

Cluster 3 projects were tested for compliance with NERC, PJM, Dominion Energy and other applicable criteria. 264 contingencies were studied, each with a 20 second simulation time period. The contingencies studied included:

 

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults placed at 80% of the line with delayed clearing at remote line end because of primary communications/relaying failure
  • Single-phase faults with loss of multiple-circuit tower line

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

The results of the analysis were evaluated against the following recovery criteria per PJM’s Regional Transmission Planning Process and Dominion Energy’s transmission planning criteria:

 

  • Cluster 3 projects were able to ride through the faults (except for faults where protective action trips a generator(s)).
  • The system with Cluster 3 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

 

 

AH1-546: Main Power Transformer High side to Tertiary impedance from Next Gen data (0.0033 + j0.141) does not match PSSE case (0.0033 + j0.0002). Main Power Transformer Low side to Tertiary impedance from Next Gen data (0.0033 + j0.0288) does not match PSSE case (0.0033 + j0.141). Case was set up using the PSSE case provided during DP1 Round 2 data. The IC should review the impedance and align the sav case and Next Gen data in the DP2 submittal.

 

No mitigation is required.

 

The following settings were adjusted in order to meet the evaluation criteria. The generator owners should provide their preferred adjustment for the issues described in the summary of results.

 

AG2-566 Results

No voltage-reactive droop setting was identified for AG2-566; implementation of a 4% voltage reactive droop is recommended to coordinate voltage and reactive power control with nearby generating facilities.

 

AG2-583 Results

No voltage-reactive droop setting was identified for AG2-583; implementation of a 4% voltage reactive droop is recommended to coordinate voltage and reactive power control with nearby generating facilities.

 

AH1-170 Results

AH1-170 experienced numerical convergency issues post fault for certain contingencies. Updating the REPCA RefFlag from 0 to 1 prevented any convergency issues for the generator.

 

Voltage-reactive droop setting was identified for AH1-170; implementation of a 4% voltage reactive droop is recommended to coordinate voltage and reactive power control with nearby generating facilities.

 

AH1-546 Results

No voltage-reactive droop setting was identified for AH1-546; implementation of a 4% voltage reactive droop is recommended to coordinate voltage and reactive power control with nearby generating facilities.

 

AE2-092 Results

No voltage-reactive droop setting was identified for AE2-092; Updating the REPCA VCFlag from 1 to 0 is recommended to coordinate voltage and reactive power control with nearby generating facilities.

 

Note: PJM will contact the project developer to verify the model tuning recommendation for non TC2 Cycle project.

Reactive Power Analysis

AH1-546 met the 0.95 leading and 0.95 lagging power factor requirements measured at the high side of the main transformer.

 

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVPartially in Service - Under Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVIn Service
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVPartially in Service - Under Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVEngineering & Procurement
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVUnder Construction
AC1-098Dawson-South Justice 115kVIn Service
AC1-099Dawson-South Justice 115kVIn Service
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-009Pennington 13 kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVSuspended
AC2-079Ivor-Oak Ridge 115kVUnder Construction
AC2-100Halifax-Person 230kVIn Service
AC2-120Ripley 69kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-041Edison 4kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-108Bremo-Scottsville 138 kVUnder Construction
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVUnder Construction
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-250Smith Mountain-E. Danville 138 kVUnder Construction
AE2-005Harmony Village-Shackleford 115 kVSuspended
AE2-027Harrowgate-Locks 115kVSuspended
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVIn Service
AE2-042Milton 69 kVIn Service
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVWithdrawn
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVEngineering & Procurement
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVEngineering & Procurement
AE2-346Ahoskie 34.5 kVIn Service
AF1-014Harmony Village-Shackleford 115 kVSuspended
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVUnder Construction
AF1-124Harper 230 kVPartially in Service - Under Construction
AF1-125Harper 230 kVUnder Construction
AF1-128Chesterfield 230 kVUnder Construction
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVUnder Construction
AF1-294Jetersville-Ponton 115 kVEngineering & Procurement
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVEngineering & Procurement
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVWithdrawn
AF2-081Moyock 230 kVEngineering & Procurement
AF2-085Midlothian 34.5 kVIn Service
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-107Clifford 138 kVWithdrawn
AF2-110Suffolk 115 kVWithdrawn
AF2-115Jetersville-Ponton 115 kVEngineering & Procurement
AF2-120Garner-Northern Neck 115 kVPartially in Service - Under Construction
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-299Fields 34.5 kVEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIPartially in Service - Under Construction
AF2-361Mifflintown Tap 69 kVUnder Construction
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVUnder Construction
AF2-425Reed-Reed Tap#1 69 kVUnder Construction
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AG1-007Tar River 12.5 kVWithdrawn
AG1-021Jetersville-Ponton 115 kVEngineering & Procurement
AG1-037Ahoskie 34.5 kVWithdrawn
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-105Mount Laurel-Barnes Junction 115 kVUnder Construction
AG1-106Thelma 230 kVWithdrawn
AG1-124Riverville - Gladstone 138 kVEngineering & Procurement
AG1-135Garner-Lancaster 115 kVUnder Construction
AG1-145Lightfoot 34.5 kVIn Service
AG1-153Heritage 500 kVUnder Construction
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVIn Service
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-285Chase City-Central 115 kVEngineering & Procurement
AG1-342Dryburg 115 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-499Lambs 12.47 kVUnder Construction
AG1-532Fields 34.5 kVUnder Construction
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-049Van Dorn 34.5 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-088Midlothian 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-171Lunenburg - Nutbush 115 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-522Five Forks DP - Littleton DP 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings - Unity 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-659Palmer Springs - Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-170Columbia DP 115kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-221Heritage 500 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-345Remington 324 34.5 kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesfords 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-684Remington CT 230 kVActive
AH1-685Remington CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-693Remington CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-696Possum Point 230kVActive
AH1-712Cunningham 500 kVActive
AH1-723Cunningham 500 kVActive
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-068Murphy's 34.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W3-106Sussex-Wykertown 34.5kVIn Service
X3-008Todd 69kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AH1-546 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Identified Impacts
Note: This reflects the Affected System studies results provided by the Affected System Operator. These results may be subject to adjustments based on the outcome of any studies in the remaining phases of the Affected System Operator's Generator Interconnection Process.
Impacted FacilityTransmission OwnerReinforcementCostCost Allocated to AH1-546Scenarios
  • Person 230.0 - Hendricks 230.0 CKT 1
CPLE Construction of the line Person-Hendricks 230 kV
this is the contingent upgrade identified for TC2
projects in DEP AFS report issued on 5/14/2026.
new rating to be 1195 MVA
$7,727,000$0
  • Contingent
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AH1-546 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionn9221.0Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).Cost Allocated$174,120N/A
Dominionn9730.0Replace switches 29824 and 29825 at Bremo 230 kVCost Allocated$67,707N/A
Dominionn9726.0Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.Cost Allocated$38,316N/A
Dominionn9728.0Replace wave trap 298 WT at Bremo 230 kVCost Allocated$33,854N/A
AEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Contingent$0N/A
Dominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Contingent$0N/A
Dominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Contingent$0N/A
Dominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Contingent$0N/A
Dominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
Dominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Contingent$0N/A
Dominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Contingent$0N/A
Dominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Contingent$0N/A
Dominionn9220.0Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.Contingent$0N/A
Dominionb4030.9Charlottesville-Fork Union 230 kV rebuild: Wreck and rebuild ~24 miles of Charlottesville-Fork Union 230 kV line.New ReinforcementContingent$0N/A
Dominionb4030.11Replace all terminal equipment at Charlottesville 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.Contingent$0N/A
Dominionb4030.15Upgrade disconnect switches at Mt. Eagle tap 230 kV substation to 4000A.Contingent$0N/A
Dominionb4030.12Replace all terminal equipment at Fork Union 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.Contingent$0N/A
Dominionb4030.10Fork Union-Bremo 230 kV rebuild: Wreck and Rebuild approximately 1.74 miles of Fork Union-Bremo 230 kV line.Contingent$0N/A
Dominionb4030.14Replace all terminal equipment at Bremo 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.Contingent$0N/A
Dominionb4030.13Replace all terminal equipment at Fork Union 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.Contingent$0N/A
Grand Total:$313,997

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9221.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9221.0 / TC1-PH3-DOM-015-TC2
Title
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Description
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Total Cost ($USD)
$2,057,335
Discounted Total Cost ($USD)
$2,057,335
Allocated Cost ($USD)
$174,120
Time Estimate
38 to 39 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1035.0 MVA
LLB1091.0 MVA
LLC1201.0 MVA
SUMA900.0 MVA
SUMB964.0 MVA
SUMC1115.0 MVA
WINA1067.0 MVA
WINB1123.0 MVA
WINC1219.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07747.4 MW9.8%$201,196
AG2-17116.2 MW3.3%$68,920
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
29.2 MW6.0%$123,866
AG2-21321.6 MW4.5%$91,895
AG2-27029.7 MW6.1%$125,997
AG2-3417.8 MW1.6%$33,027
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
20.7 MW4.3%$87,777
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
31.2 MW6.4%$132,254
AG2-44240.5 MW8.4%$171,840
AG2-5229.9 MW2.0%$41,934
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
10.4 MW2.2%$44,277
AG2-58136.2 MW7.5%$153,578
AG2-65910.9 MW2.3%$46,485
AH1-3145.7 MW1.2%$24,329
AH1-3438.9 MW1.8%$37,956
AH1-43944.7 MW9.2%$189,912
AH1-52872.5 MW15.0%$307,970
AH1-54641.0 MW8.5%$174,120

System Reinforcement: n9730.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9730.0 / TC2-PH1-DOM-2077
Title
Replace switches 29824 and 29825 at Bremo 230 kV
Description
Replace switches 29824 and 29825 at Bremo 230 kV
Total Cost ($USD)
$800,000
Discounted Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$67,707
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1145.0 MVA
LLB1183.0 MVA
LLC1201.0 MVA
SUMA1050.0 MVA
SUMB1094.0 MVA
SUMC1115.0 MVA
WINA1164.0 MVA
WINB1201.0 MVA
WINC1219.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07747.4 MW9.8%$78,236
AG2-17116.2 MW3.3%$26,800
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
29.2 MW6.0%$48,166
AG2-21321.6 MW4.5%$35,734
AG2-27029.7 MW6.1%$48,994
AG2-3417.8 MW1.6%$12,843
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
20.7 MW4.3%$34,133
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
31.2 MW6.4%$51,427
AG2-44240.5 MW8.4%$66,821
AG2-5229.9 MW2.0%$16,306
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
10.4 MW2.2%$17,217
AG2-58136.2 MW7.5%$59,719
AG2-65910.9 MW2.3%$18,076
AH1-3145.7 MW1.2%$9,460
AH1-3438.9 MW1.8%$14,759
AH1-43944.7 MW9.2%$73,848
AH1-52872.5 MW15.0%$119,755
AH1-54641.0 MW8.5%$67,707

System Reinforcement: n9726.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9726.0 / TC2-PH1-DOM-2043
Title
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Description
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Total Cost ($USD)
$3,534,000
Discounted Total Cost ($USD)
$3,534,000
Allocated Cost ($USD)
$38,316
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA1410.0 MVA
LLB1481.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1446.0 MVA
WINB1517.0 MVA
WINC1631.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07765.1 MW12.5%$442,733
AG2-1517.1 MW1.4%$48,582
AG2-17114.3 MW2.7%$97,022
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
18.8 MW3.6%$128,145
AG2-21319.0 MW3.7%$129,362
AG2-27065.2 MW12.5%$443,182
AG2-34113.8 MW2.7%$93,867
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
20.7 MW4.0%$140,410
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
31.1 MW6.0%$211,550
AG2-44237.5 MW7.2%$255,006
AG2-52210.2 MW2.0%$69,114
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
9.0 MW1.7%$60,956
AG2-58148.0 MW9.2%$326,635
AG2-5837.4 MW1.4%$50,309
AG2-65911.7 MW2.2%$79,434
AH1-34321.5 MW4.1%$146,168
AH1-43912.2 MW2.4%$83,058
AH1-52896.3 MW18.5%$655,010
AH1-5465.6 MW1.1%$38,316
AH1-6875.2 MW1.0%$35,142

System Reinforcement: n9728.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9728.0 / TC2-PH1-DOM-2076
Title
Replace wave trap 298 WT at Bremo 230 kV
Description
Replace wave trap 298 WT at Bremo 230 kV
Total Cost ($USD)
$400,000
Discounted Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$33,854
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA956.0 MVA
LLB1011.0 MVA
LLC1091.0 MVA
SUMA812.0 MVA
SUMB876.0 MVA
SUMC964.0 MVA
WINA979.0 MVA
WINB1043.0 MVA
WINC1115.0 MVA
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-07747.4 MW9.8%$39,118
AG2-17116.2 MW3.3%$13,400
AG2-198 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
29.2 MW6.0%$24,083
AG2-21321.6 MW4.5%$17,867
AG2-27029.7 MW6.1%$24,497
AG2-3417.8 MW1.6%$6,421
AG2-440 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
20.7 MW4.3%$17,066
AG2-441 ⧉ AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-440, AG2-441
31.2 MW6.4%$25,714
AG2-44240.5 MW8.4%$33,410
AG2-5229.9 MW2.0%$8,153
AG2-566 ⧉ AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. The following project shared this POI:
AG2-198, AG2-566
10.4 MW2.2%$8,609
AG2-58136.2 MW7.5%$29,860
AG2-65910.9 MW2.3%$9,038
AH1-3145.7 MW1.2%$4,730
AH1-3438.9 MW1.8%$7,380
AH1-43944.7 MW9.2%$36,924
AH1-52872.5 MW15.0%$59,878
AH1-54641.0 MW8.5%$33,854

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P7-1: LN 2106-2111_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-L
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FORK UNION-3FORK UNION 230.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: WT2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FORK UNION-3FORK UNION 230.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: WT2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FORK UNION-3FORK UNION 230.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: WT2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FORK UNION-3FORK UNION 230.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: WT2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 594_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P1-2: LN 573_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 lineDVP_P4-2: 545T594_SRT-S
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FORK UNION-3FORK UNION 230.0/115.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 56372_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: WT576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 576_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P1-2: LN 563_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 57602_SRT-S
No new ratings for this Flowgate.
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformerDVP_P4-2: 562T563_SRT-S
No new ratings for this Flowgate.
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: WT2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P1-2: LN 2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 233T2028_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2193_SRT-A
No new ratings for this Flowgate.
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 lineDVP_P4-2: 2028T2054_SRT-A
No new ratings for this Flowgate.
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)
No new ratings for this Flowgate.
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.10
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.10
Title
Construct one new 500 kV line terminal position at the proposed Thornburg (formerly Kraken) substation.
Description
Construct one new 500 kV line terminal position at the proposed Thornburg (formerly Kraken) substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.8
Title
Build a new 500 kV line from Elmont-Thornburg (formerly Kraken) (approximately 31 miles).
Description
Build a new 500 kV line from Elmont-Thornburg (formerly Kraken) (approximately 31 miles). The new line will be constructed primarily of double-circuit 500 kV/230 kV monopole structures. The proposed route follows existing 230 kV line No. 2032 from Elmont-Hanover-Four Rivers and 230 kV line No. 256 from Four Rivers-Kings Dominion-St Johns-Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.9
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.9
Title
Construct one new 500 kV line terminal position at the existing Elmont substation.
Description
Construct one new 500 kV line terminal position at the existing Elmont substation.
Cost Information
Time Estimate
Jun 01 2032

Not ContingentTopology Changing

Note 1: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.49 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Discounted Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Contingent

Note: Based on PJM cost allocation criteria, AH1-546 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AH1-546 may not have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA940.0 MVA
LLB987.0 MVA
LLC1091.0 MVA
SUMA812.0 MVA
SUMB868.0 MVA
SUMC964.0 MVA
WINA964.0 MVA
WINB1011.0 MVA
WINC1115.0 MVA

System Reinforcement: b3800.300
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.300
Title
Wreck/Rebuild 230kV Line #2135 segment Hollymeade Junction – Cash’s Corner using double-circuit capable 230 kV poles. (The second 230kV circuit will be wired but not have terminal ends.)
Description
Wreck/Rebuild 230kV Line #2135 segment Hollymeade Junction – Cash’s Corner using double-circuit capable 230 kV poles. (The second 230kV circuit will be wired but not have terminal ends.)
Cost Information
Time Estimate
Jun 30 2028

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CASHSCORNER-6HOLLYMD 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1648.0 MVA

System Reinforcement: b3800.302
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.302
Title
Upgrade Cash's Corner switches 213576 and 213579 and line leads to 4000A continuous current rating of 230kV Line #2135.
Description
Upgrade Cash's Corner switches 213576 and 213579 and line leads to 4000A continuous current rating of 230kV Line #2135.
Cost Information
Time Estimate
Jun 30 2028

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CASHSCORNER-6HOLLYMD 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1648.0 MVA

System Reinforcement: b4030.9
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.9
Title
Charlottesville-Fork Union 230 kV rebuild: Wreck and rebuild ~24 miles of Charlottesville-Fork Union 230 kV line.New Reinforcement
Description
Charlottesville-Fork Union 230 kV rebuild: Wreck and rebuild ~24 miles of Charlottesville-Fork Union 230 kV line.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
LLA1410.0 MVA
LLB1481.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1446.0 MVA
WINB1517.0 MVA
WINC1631.0 MVA
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
LLA1442.0 MVA
LLB1540.0 MVA
LLC1587.0 MVA
SUMA1174.0 MVA
SUMB1302.0 MVA
SUMC1360.0 MVA
WINA1493.0 MVA
WINB1587.0 MVA
WINC1631.0 MVA

System Reinforcement: b4030.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.11
Title
Replace all terminal equipment at Charlottesville 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Description
Charlottesville 230 kV substation scope: Replace all terminal equipment at Charlottesville 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC16480.0 MVA

System Reinforcement: b4030.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.15
Title
Upgrade disconnect switches at Mt. Eagle tap 230 kV substation to 4000A.
Description
Mt. Eagle tap 230 kV substation scope: Upgrade disconnect switches at Mt. Eagle tap 230 kV substation to 4000A.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
LLA1585.0 MVA
LLB1634.0 MVA
LLC1879.0 MVA
SUMA1524.0 MVA
SUMB1571.0 MVA
SUMC1801.0 MVA
WINA1598.0 MVA
WINB1648.0 MVA
WINC1895.0 MVA

System Reinforcement: b4030.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.12
Title
Replace all terminal equipment at Fork Union 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Description
Fork Union 230 kV substation scope: Replace all terminal equipment at Fork Union 230 kV substation to support the new line conductor ratings of the Charlottesville-Fork Union 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
LLA1585.0 MVA
LLB1634.0 MVA
LLC1879.0 MVA
SUMA1524.0 MVA
SUMB1571.0 MVA
SUMC1801.0 MVA
WINA1598.0 MVA
WINB1648.0 MVA
WINC1895.0 MVA

System Reinforcement: b4030.10
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.10
Title
Fork Union-Bremo 230 kV rebuild: Wreck and Rebuild approximately 1.74 miles of Fork Union-Bremo 230 kV line.
Description
Fork Union-Bremo 230 kV rebuild: Wreck and Rebuild approximately 1.74 miles of Fork Union-Bremo 230 kV line.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB16480.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.14
Title
Replace all terminal equipment at Bremo 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Description
Bremo 230 kV substation scope: Replace all terminal equipment at Bremo 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement: b4030.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4030.13
Title
Replace all terminal equipment at Fork Union 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Description
Fork Union 230 kV substation scope: Replace all terminal equipment at Fork Union 230 kV substation to support the new conductor ratings of the Fork Union-Bremo 230 kV rebuild.
Cost Information
Time Estimate
Jun 01 2030

Contingent

Note: Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 may need this upgrade in-service to be deliverable to the PJM system. If AH1-546 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A1573.0 MVA
(All)B1573.0 MVA
(All)C1573.0 MVA
WINA1648.0 MVA
WINB1648.0 MVA
WINC1648.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
DVP Rating: 961/961/1106 MVA
Description
DVP Rating: 961/961/1106 MVA
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A961.0 MVA
(All)B961.0 MVA
(All)C1106.0 MVA

System Reinforcement: n9727.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9727.0 / TC2-PH1-DOM-2091
Title
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Total Cost ($USD)
$38,000,000
Discounted Total Cost ($USD)
$38,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-546 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-546 could receive cost allocation. Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 is a potential Aggregate Pool Contributor.

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 1 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2304.0 MVA

System Reinforcement: n9729.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9729.0 / TC2-PH1-DOM-2092
Title
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Total Cost ($USD)
$38,000,000
Discounted Total Cost ($USD)
$38,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-546 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-546 could receive cost allocation. Although AH1-546 may not presently have cost responsibility for this upgrade, AH1-546 is a potential Aggregate Pool Contributor.

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 2 transformer(Any)
Rating SetRating TypeRating Value
LLA2016.0 MVA
LLB2083.0 MVA
LLC2239.0 MVA
SUMA1707.0 MVA
SUMB1758.0 MVA
SUMC1873.0 MVA
WINA2196.0 MVA
WINB2228.0 MVA
WINC2304.0 MVA

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
No overload on Dominion equipment for 8POSSUM - BURCHES (TC2)
Description
Dominion End Ratings Winter: 5414/5581/6107 Light Load: 5227/5388/5941 Summer: 4257/4388/5046
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA5227.0 MVA
LLB5388.0 MVA
LLC5941.0 MVA
SUMA4257.0 MVA
SUMB4388.0 MVA
SUMC5046.0 MVA
WINA5414.0 MVA
WINB5581.0 MVA
WINC6107.0 MVA

System Reinforcement: b4053.29
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4053.29
Title
Uprate 500 kV line No. 560 terminal equipment at Burches Hill substation in PEPCO so as not to limit the conductor rating.
Description
Uprate 500 kV line No. 560 terminal equipment at Burches Hill substation in PEPCO so as not to limit the conductor rating. The scope includes upgrading/replacing two circuit breakers, four switches and two different portions of stranded bus.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4087.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA4673.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4052.11
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.11
Title
Replace Bells Mill T3 XF with new PEPCO standard 260 MVA 230/138 kV transformer.
Description
Replace Bells Mill T3 XF with new PEPCO standard 260 MVA 230/138 kV transformer. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.10
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.10
Title
Replace one stranded bus conductor, three thermal relays, two disconnect switches at Quince Orchard 230 kV substation.
Description
Replace one stranded bus conductor, three thermal relays, two disconnect switches at Quince Orchard 230 kV substation. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.9
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.9
Title
Replace two breakers, one bushing CT, one stranded bus conductor, four disconnect switches at Brighton 500 kV substation.
Description
Replace two breakers, one bushing CT, one stranded bus conductor, four disconnect switches at Brighton 500 kV substation.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.8
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.8
Title
Relocate Dickerson "D"-Quince Orchard 23035 to terminate at Dickerson "H" at Dickerson No. 2 tie location.
Description
Relocate Dickerson "D"-Quince Orchard 23035 to terminate at Dickerson "H" at Dickerson No. 2 tie location. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.7
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.7
Title
Install 3.2% 230 kV series reactor at Dickerson "H" terminal side of the Edwards Ferry-Dickerson circuit.
Description
Install 3.2% 230 kV series reactor at Dickerson "H" terminal side of the Edwards Ferry-Dickerson circuit. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.6
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4052.6
Title
Aspen 500 kV remote work for Dickerson (new 500 kV) - Aspen line
Description
Aspen 500 kV remote work for Dickerson (new 500 kV) - Aspen line (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4052.5
Title
Rocky Point 500 kV remote work for Dickerson (new 500 kV)-Rocky Point line
Description
Rocky Point 500 kV remote work for Dickerson (new 500 kV)-Rocky Point line. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.1
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.1
Title
New 500/230 kV substation (Dickerson) by cutting into the Aspen-Rocky Point 500 kV line
Description
New 500/230 kV substation (Dickerson) by cutting into the Aspen-Rocky Point 500 kV line. (2025-W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.4
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.4
Title
Aspen-Dickerson (new 500 kV) termination work at Dickerson 500 kV
Description
Aspen-Dickerson (new 500 kV) termination work at Dickerson 500 kV (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.3
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.3
Title
Rocky Point-Dickerson (new 500 kV) termination work at Dickerson 500 kV
Description
Rocky Point-Dickerson (new 500 kV) termination work at Dickerson 500 kV (2025 W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.2
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.2
Title
Install two 500/230 kV transformers connecting a new 500 kV Dickerson station and DIckeson "H" 230 kV station including 230 kV substation work.
Description
Install two 500/230 kV transformers connecting a new 500 kV Dickerson station and DIckeson "H" 230 kV station including 230 kV substation work. (2025 W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-546 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-546 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-546


AH1-546 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowAEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Topology-0.0%Contingent$0
Load FlowDominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Topology-0.0%Contingent$0
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Topology-0.0%Contingent$0
Load FlowDominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Topology-0.0%Contingent$0
Load FlowDominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Topology-0.0%Contingent$0
Load FlowDominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Topology-0.0%Contingent$0
Load FlowDominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Topology-0.0%Contingent$0
Load FlowDominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-546 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-546 One Line Diagram

AH1-546 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.