AH1-684 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:15

Remington CT 230 kV

23.0 MW Capacity / 0.0 MW Energy

Introduction

AH1-684 meets the criteria for acceleration at Decision Point II (DP2) .

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia), and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Final Agreement Requirements

This New Service Request meets the criteria for acceleration at Decision Point II (DP2).

Please note that additional requirements apply to accelerated projects at DP2 per PJM Tariff Part VII, Subpart D, section 311. Failure to meet the requirements by the close of DP2 will result in withdrawal.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $0 $0 = ∞ AND ( $0 - $0 ) 23.0 = $0 per MW

General

The Project Developer has proposed a Natural Gas generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Fauquier County, Virginia. The installed facilities will have a total capability of 190.0 MW with 23.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-684
Project Name:
Remington CT 230 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
State:
Virginia
County:
Fauquier
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
190.0
MWE:
0.0
MWC:
23.0
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Physical Interconnection Facility Study

Not Required

A Physical Interconnection Facilities Study is not required for this project.

Point of Interconnection

AH1-684 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system at the Remington CT 230 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-684 project has the following allocation of costs for interconnection.

Cost Summary
DescriptionCost Allocated to AH1-684Cost Subject to Security*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0
AFS - Non-PJM Violations$0$0
Total$0$0
Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Security Requirement

A summary of this New Service Requests costs are summarized in the Cost Summary section, herein. Final security will be shown in the Generation Interconnection Agreement (GIA).

Transmission Owner Scope of Work

AH1-684 is sharing a POI and the TOIF with S93, so there are no associated interconnection costs for this project.

 

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-684 was evaluated as a 0.0 MW (23.0 MW Capacity) injection in the Dominion area.

AH1-684 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 190.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC118.18 %3099.0B3662.4
2.9
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL_SENS
BreakerAC105.83 %3099.0B3279.67
2.43
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
PEPCO_P4_PP41_SRT-A
BreakerAC103.07 %3099.0B3194.05
2.42

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.18 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3662.4
MW Contribution:
2.9
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.58 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3365.01
MW Contribution:
2.92
Bus #Bus NameTypeMW Contribution
3140676OCCOQUN
50/50
0.027
972213AH1-691 GEN
50/50
4.009
944491AF1-114 GEN
Solar/Wind Harmer
5.789
3138133OCRAN
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.004
3143873LANEXA
Solar/Wind Harmer
-0.011
316382AG1-145 C
Solar/Wind Harmer
0.534
316159AE1-175 C
Solar/Wind Harmer
0.475
971281AH1-106 GEN
Solar/Wind Harmer
2.874
3143316POE
Solar/Wind Harmer
-0.069
316236AE1-162_GEN
Solar/Wind Harmer
0.523
970657AG2-426 GEN
Solar/Wind Harmer
1.092
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
316405AF2-144 C
Solar/Wind Harmer
0.433
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970533AG2-339 GEN
Solar/Wind Harmer
11.279
3147346CASHSCORNER
Solar/Wind Harmer
0.259
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315733AD1-074 GEN2
Solar/Wind Harmer
3.333
970601AG2-382 GEN
Solar/Wind Harmer
7.198
946281AF1-292 GEN
Solar/Wind Harmer
0.366
970581AG2-369 GEN
Solar/Wind Harmer
8.731
3146033SCOT NK
Solar/Wind Harmer
-0.064
972205AH1-687 GEN
Adder
6.087
3151881LOWMORC
Adder
1.346
3151881LOWMORC
Adder
1.325
233915AB1-141 GEN
Solar/Wind Helper
0.826
228728W1-130C
Solar/Wind Helper
0.086
227927V4-067C
Solar/Wind Helper
0.016
219615MILLCREEK C
Solar/Wind Helper
0.042
219620RIDERU C
Solar/Wind Helper
0.002
218526CNTRALGAS2 C
Solar/Wind Helper
0.245
961261AF2-417 GEN
Solar/Wind Helper
0.617
212266LOR1
Solar/Wind Helper
0.413
205943AE1-185 GEN
Solar/Wind Helper
0.657
959431AF2-234 GEN
Solar/Wind Helper
1.178
3150411LDYSMT5
50/50
24.76
972215AH1-692 GEN
50/50
4.009
3141813NORNECK
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.542
3138283WHITEMARSH
Solar/Wind Harmer
0.028
316233AE1-074 FULL
Solar/Wind Harmer
0.476
971283AH1-107 GEN
Solar/Wind Harmer
2.874
316164AC1-076 GEN
Solar/Wind Harmer
1.478
3151191GRAVEL3
Adder
11.161
315833AF1-017_GEN
Solar/Wind Harmer
3.27
316018AA1-139 ULT2
Solar/Wind Harmer
1.47
3146406KITTY HAWK
Solar/Wind Harmer
0.014
315800Z1-036_GEN1
Solar/Wind Harmer
4.164
971967AH1-528 GEN
Solar/Wind Harmer
31.193
315732AD1-074 GEN1
Solar/Wind Harmer
3.333
3145893MURPHYS
Solar/Wind Harmer
-0.044
3145893MURPHYS
Solar/Wind Harmer
-0.016
316463AE2-346 GEN
Solar/Wind Harmer
0.264
3145513AHOSKIE
Solar/Wind Harmer
0.142
3145513AHOSKIE
Solar/Wind Harmer
-0.016
970085AG2-068 GEN
Solar/Wind Harmer
10.152
3137643SOCKMAN
Solar/Wind Harmer
-0.064
316426AA2-053 GEN
Solar/Wind Harmer
1.631
315652AC1-086 GEN
Solar/Wind Harmer
18.207
316174AB2-169 GEN
Solar/Wind Harmer
2.485
946301AF1-294 GEN
Solar/Wind Harmer
4.098
3144303KENBRDG
Solar/Wind Harmer
-0.013
3151861LOWMORA
Adder
1.304
226929AD2-058 GEN
Solar/Wind Helper
0.387
233901CHERRYDALE C
Solar/Wind Helper
0.382
20715028HAN_X4-015
Solar/Wind Helper
0.089
207445AB1-138_GEN
Solar/Wind Helper
0.162
20720628TIN_W1-124
Solar/Wind Helper
0.292
20675528CPH_W2-050
Solar/Wind Helper
0.173
20676428JCR_X2-075
Solar/Wind Helper
0.103
20675128HRM_W1-127
Solar/Wind Helper
0.044
205956AE1-196_GEN
Solar/Wind Helper
0.664
209029WAYMART-WD
Solar/Wind Helper
1.131
959421AF2-233 GEN
Solar/Wind Helper
0.589
205917AD1-020 ES
Solar/Wind Helper
0.355
3150091POSSM6B
50/50
1.651
966871AG1-558 GEN
Solar/Wind Harmer
0.554
966871AG1-558 GEN
Solar/Wind Harmer
0.189
3142296MT RD221
Adder
0.517
316156AD2-030 GEN
Solar/Wind Harmer
0.483
315666AE1-190 GEN
Solar/Wind Harmer
0.545
3150671DARBY 1
Adder
11.499
316045AC1-158 PL2
Solar/Wind Harmer
5.578
316240AF1-291 C
Solar/Wind Harmer
0.531
971223AH1-071 GEN
Solar/Wind Harmer
2.193
3150991CHESPKB
Adder
1.611
3150991CHESPKB
Adder
1.572
315835AF2-110_GEN
Solar/Wind Harmer
2.144
316435W1029_GEN3
Solar/Wind Harmer
3.086
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
316006AB2-029 C
Solar/Wind Harmer
0.975
316313AB2-026
Solar/Wind Harmer
0.455
315614AA2-178 GEN
Solar/Wind Harmer
1.793
972187AH1-678 GEN
Adder
4.194
316065AD1-022 GEN
Solar/Wind Harmer
8.239
3145893MURPHYS
Solar/Wind Harmer
0.459
3145893MURPHYS
Solar/Wind Harmer
-0.03
316140AB2-099
Solar/Wind Harmer
0.11
3146776BUCKING
Solar/Wind Harmer
-0.064
3146776BUCKING
Solar/Wind Harmer
-0.005
972193AH1-681 GEN
Adder
3.264
234036AF2-325 C
Solar/Wind Helper
0.07
3150151POSSMC1
50/50
2.222
316337AD2-073 GEN
Solar/Wind Harmer
0.507
3141726DUNNSVL
Solar/Wind Harmer
-0.074
962861AG1-135 GEN
Solar/Wind Harmer
6.949
3150851SPRUNCC
Adder
0.73
316132AB2-190 GEN1
Solar/Wind Harmer
1.772
315773AC2-141 GEN
Solar/Wind Harmer
7.245
316170AC1-121 GEN2
Solar/Wind Harmer
2.162
316036AC1-147 C
Solar/Wind Harmer
0.465
316093AE2-104_GEN
Solar/Wind Harmer
4.987
3146516WINFALL
Solar/Wind Harmer
-0.055
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
0.488
970919AG2-571 GEN
Solar/Wind Harmer
5.165
315607AA1-063A GEN
Solar/Wind Harmer
1.642
3146263WOODLND
Solar/Wind Harmer
-0.016
3145963POPLR C
Solar/Wind Harmer
-0.016
3146776BUCKING
Solar/Wind Harmer
-0.006
233918AB1-142 GEN
Solar/Wind Helper
0.826
228729W2-030 C
Solar/Wind Helper
0.176
219686LUMSOLAR_N C
Solar/Wind Helper
0.063
219348LDSOLAR C
Solar/Wind Helper
0.18
218524CNTRALGAS1 C
Solar/Wind Helper
0.245
957971AF2-091 GEN
Solar/Wind Harmer
1.968
316404AE1-155 C
Solar/Wind Harmer
3.542
3138133OCRAN
Solar/Wind Harmer
-0.011
315662AE1-191 GEN
Solar/Wind Harmer
2.178
316280AD1-041 GEN
Solar/Wind Harmer
1.361
3143096IRON208
Adder
0.667
3142543TWELFTH
Solar/Wind Harmer
-0.002
316044AC1-158 PL1
Solar/Wind Harmer
1.743
3138126ROCKLANDING
Solar/Wind Harmer
0.054
3147666LOUISA
Solar/Wind Harmer
-0.07
3143226MDLTHAN
Solar/Wind Harmer
-0.017
971069AG2-661 GEN
Solar/Wind Harmer
2.776
316369SG1_INVT
Solar/Wind Harmer
3.125
961611AG1-000B GEN
Solar/Wind Harmer
8.626
3151171GRAVELC
Adder
1.652
316381AD1-082 GEN
Solar/Wind Harmer
1.585
316254AC1-120 GEN1
Solar/Wind Harmer
6.487
3150981CHESPKA
Adder
1.92
319010AE1-072 C
Solar/Wind Harmer
3.467
3150281M RUN A
Adder
20.436
3151751LOISA D
Adder
9.775
315611Z1-036_GEN2
Solar/Wind Harmer
4.164
3130156CHOWAN
Solar/Wind Harmer
-0.017
315816AE2-034 GEN
Solar/Wind Harmer
1.345
971163AH1-040 GEN
Solar/Wind Harmer
15.624
315737AD1-076 GEN
Solar/Wind Harmer
3.134
316087AB2-174 GEN
Solar/Wind Harmer
2.317
970087AG2-069 GEN
Solar/Wind Harmer
15.228
957481AF2-042 GEN
Solar/Wind Harmer
50.592
315693AD1-088 GEN
Solar/Wind Harmer
8.067
970685AG2-442 GEN
Solar/Wind Harmer
14.071
3146926FARMVIL
Solar/Wind Harmer
-0.01
971563AH1-280 GEN
Solar/Wind Harmer
1.999
315785AD2-033 C
Solar/Wind Harmer
3.609
208835TUHI V3-051
Solar/Wind Helper
0.035
233998TM1NIN_3.36
Solar/Wind Helper
0.337
232404W1-003 C
Solar/Wind Helper
0.834
20715828PEM_W1-120
Solar/Wind Helper
0.149
219276PARKLANDSO C
Solar/Wind Helper
0.138
963711AG1-223 GEN
Solar/Wind Helper
0.099
20715228NPK_W1-113
Solar/Wind Helper
0.12
20720528MAN_W1-024
Solar/Wind Helper
0.044
219919AE1-041 FULL
Solar/Wind Helper
0.006
20676728BRNX1-095
Solar/Wind Helper
0.045
20676328BVR_Y1-020
Solar/Wind Helper
0.04
20674928WA_W3-044
Solar/Wind Helper
0.146
207518AF1-320_GEN
Solar/Wind Helper
2.321
209137AF2-361 C
Solar/Wind Helper
1.618
3150181POSSMC2
50/50
2.241
3150181POSSMC2
50/50
2.222
3150181POSSMC2
50/50
2.222
972195AH1-682 GEN
50/50
3.238
3150341NORNECKC1
50/50
1.844
3150341NORNECKC1
50/50
1.829
315673AE1-157 GEN
Solar/Wind Harmer
14.418
972189AH1-679 GEN
Adder
2.773
316487AF1-042 GEN
Solar/Wind Harmer
2.431
3150681DARBY 2
Adder
11.513
316450AC1-158 RIC
Solar/Wind Harmer
0.465
316033AB2-134 GEN
Solar/Wind Harmer
5.643
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.158
316388AE2-253 GEN
Solar/Wind Harmer
1.158
3137176SLIGO L2192
Solar/Wind Harmer
-0.068
3130086AYDLETT
Solar/Wind Harmer
-0.068
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
966001AG1-469 GEN
Solar/Wind Harmer
0.32
3151731LOISA B
Adder
9.775
313506AB2-031 GEN
Solar/Wind Harmer
1.302
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
0.134
970301AG2-198 GEN
Solar/Wind Harmer
8.045
970323AG2-213 GEN
Solar/Wind Harmer
7.979
223401AF1-299 GEN
Solar/Wind Helper
0.732
232424Y1-079 C
Solar/Wind Helper
0.191
232428Y3-058 C
Solar/Wind Helper
0.556
234015AF2-250 C
Solar/Wind Helper
0.062
230433AD2-135 GEN
Solar/Wind Helper
0.027
214067T20SOLAR
Solar/Wind Helper
0.018
207459AE1-142 C O1
Solar/Wind Helper
0.451
20675428EAM_W2-061
Solar/Wind Helper
0.024
3150101POSSM6S
50/50
2.517
3150401LDYSMT4
50/50
24.683
3141906WESTMOR
Solar/Wind Harmer
-0.008
3141873WAN 176
Solar/Wind Harmer
2.151
3141843SHACKLE
Adder
0.823
3143096IRON208
Adder
0.667
3143096IRON208
Adder
0.654
3150861SPRUNCD
Adder
0.73
316458AB2-190 GEN2
Solar/Wind Harmer
1.772
3147666LOUISA
Solar/Wind Harmer
-0.04
961611AG1-000B GEN
Solar/Wind Harmer
3.68
3151171GRAVELC
Adder
2.172
970657AG2-426 GEN
Solar/Wind Harmer
3.498
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.347
316321Z2-027
Solar/Wind Harmer
0.46
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3150301M RUN C
Adder
20.424
3156081AA2-088 GEN
Solar/Wind Harmer
5.364
970917AG2-570 GEN
Solar/Wind Harmer
40.801
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.198
3146926FARMVIL
Solar/Wind Harmer
-0.01
970257AG2-171 GEN
Solar/Wind Harmer
5.984
971775AH1-396 GEN
Solar/Wind Harmer
1.126
208835TUHI V3-051
Solar/Wind Helper
0.035
233950AC2-186 GEN
Solar/Wind Helper
0.191
219921AF1-264
Solar/Wind Helper
0.081
219914AD2-027 C
Solar/Wind Helper
0.182
218660EHAMPSOLAR C
Solar/Wind Helper
0.052
219688LUMSOLAR_S C
Solar/Wind Helper
0.063
207454AA2-184 E
Solar/Wind Helper
0.478
217169METRODIV C
Solar/Wind Helper
0.006
963161AG1-165 GEN
Solar/Wind Helper
0.617
208972BECR K09
Solar/Wind Helper
0.454
961331AF2-424 GEN
Solar/Wind Helper
0.601
209071AE2-133 GEN
Solar/Wind Helper
0.107
20671828STAW2-080
Solar/Wind Helper
0.04
217209CENTRL HS C
Solar/Wind Helper
0.013
207439AE1-081 C O1
Solar/Wind Helper
0.028
207530AG1-191 GEN
Solar/Wind Helper
0.099
211065PSPA IPP
Solar/Wind Helper
0.219
961301AF2-421 GEN
Solar/Wind Helper
0.617
963151AG1-164 GEN
Solar/Wind Helper
0.617
961341AF2-425 GEN
Solar/Wind Helper
0.601
212507AE2-042_GEN
Solar/Wind Helper
2.099
232436AB1-176 C
Solar/Wind Helper
0.073
233994AC2-023 GEN
Solar/Wind Helper
1.581
219912AD2-042 GEN
Solar/Wind Helper
0.237
219607WPEMNERT C
Solar/Wind Helper
0.126
219304NAMERICA C
Solar/Wind Helper
0.206
20674328GAR_V4-001
Solar/Wind Helper
0.034
946751AF1-339 GEN
Solar/Wind Helper
0.59
3150151POSSMC1
50/50
2.222
3150151POSSMC1
50/50
2.222
3150331BIRCHWDA
50/50
33.562
3150501FRIVERG
50/50
1.395
316223AC1-118
Solar/Wind Harmer
0.516
316203AE2-005 GEN
Solar/Wind Harmer
7.635
970293AG2-193 GEN
Solar/Wind Harmer
2.255
3150921YORKTN3
Adder
3.941
3144536CHRHLND
Solar/Wind Harmer
-0.003
3142956BIRDNECK
Solar/Wind Harmer
0.926
944581AF1-123 GEN
Solar/Wind Harmer
78.482
316305AF2-043 C
Solar/Wind Harmer
0.517
3132273ORANGE
Solar/Wind Harmer
-0.003
316320Y1-086
Solar/Wind Harmer
1.002
3146516WINFALL
Solar/Wind Harmer
-0.017
3150291M RUN B
Adder
20.272
944011AF1-069 GEN
Solar/Wind Harmer
9.854
315735AD1-075 GEN1
Solar/Wind Harmer
1.667
3145893MURPHYS
Solar/Wind Harmer
0.115
3145893MURPHYS
Solar/Wind Harmer
-0.016
3146263WOODLND
Solar/Wind Harmer
-0.016
3145963POPLR C
Solar/Wind Harmer
-0.016
316011AB1-132 GEN
Solar/Wind Harmer
3.38
3146776BUCKING
Solar/Wind Harmer
-0.006
3151861LOWMORA
Adder
1.357
233987AB2-037 GEN
Solar/Wind Helper
3.859
232417X3-008 C
Solar/Wind Helper
0.383
233923SMA
Solar/Wind Helper
1.237
233997TMININ_4.2
Solar/Wind Helper
0.337
233935AB2-179 C
Solar/Wind Helper
2.086
959561AF2-247 GEN
Solar/Wind Helper
0.032
20715728PEM_W1-119
Solar/Wind Helper
0.149
219249CENTRALDIV C
Solar/Wind Helper
0.015
207442AE1-156 GEN
Solar/Wind Helper
0.494
217211CAMDEN ST C
Solar/Wind Helper
0.007
207511W3-106 GEN
Solar/Wind Helper
0.04
20674128FR_U2-059
Solar/Wind Helper
0.006
211065PSPA IPP
Solar/Wind Helper
0.219
957921AF2-086 GEN
Solar/Wind Helper
0.593
970053AG2-049 GEN
50/50
3.301
3150381LDYSMT2
50/50
23.697
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
316059AD1-063 C
Solar/Wind Harmer
0.409
3142433PROV 92
Adder
0.312
3142433PROV 92
Adder
0.312
3151201GRAVEL4
Adder
11.305
3151221GRAVEL6
Adder
11.292
3151211GRAVEL5
Adder
11.161
315651AD1-115 GEN
Solar/Wind Harmer
7.57
316311AC2-079 GEN
Solar/Wind Harmer
8.685
313526AB2-022
Solar/Wind Harmer
0.46
3146396TANGLEW
Solar/Wind Harmer
0.314
315814AE2-033 C
Solar/Wind Harmer
15.759
3146206CASHIE
Solar/Wind Harmer
-0.016
316318V4-068
Solar/Wind Harmer
0.41
961941AG1-037 GEN
Solar/Wind Harmer
0.123
3146043SEABORD
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
971845AH1-439 GEN
Solar/Wind Harmer
8.52
316486AD2-202 GEN
Solar/Wind Harmer
0.405
961791AG1-021 GEN
Solar/Wind Harmer
1.999
232432Z2-076 GEN
Solar/Wind Helper
0.11
230407AD2-065 C
Solar/Wind Helper
0.064
20720728JCB_W1-129
Solar/Wind Helper
0.089
964851AG1-348 GEN
Solar/Wind Helper
0.093
207408W3-077 C
Solar/Wind Helper
0.124
209054AE2-059 GEN
Solar/Wind Helper
0.108
209067AE2-060 GEN
Solar/Wind Helper
0.097
957191AF2-013 GEN
50/50
16.161
3150691DARBY 3
Adder
11.553
3150701DARBY 4
Adder
11.526
3142366NRTHEST
Adder
0.525
315976AC1-164 GENA
Solar/Wind Harmer
4.091
316169AC1-164_GENC
Solar/Wind Harmer
3.536
3142946ENON
Solar/Wind Harmer
-0.002
316294AC1-161 GEN
Solar/Wind Harmer
5.601
316083AB2-161 GEN
Solar/Wind Harmer
2.811
316349AD2-085 GEN
Solar/Wind Harmer
1.529
3146456SLIGO L269
Solar/Wind Harmer
2.03
3146386ELIZ CT
Solar/Wind Harmer
-0.017
316431W1029_GEN1
Solar/Wind Harmer
3.086
316433W1029_GEN2
Solar/Wind Harmer
3.086
315742AE1-103 GEN
Solar/Wind Harmer
4.005
3146376EDENTON
Solar/Wind Harmer
0.499
3146376EDENTON
Solar/Wind Harmer
0.499
316336AC2-165 C
Solar/Wind Harmer
10.471
970933AG2-581 GEN
Solar/Wind Harmer
15.467
316365GEN2_N
Solar/Wind Harmer
1.106
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3147133PAMPLIN
Solar/Wind Harmer
-0.016
3147133PAMPLIN
Solar/Wind Harmer
-0.013
958211AF2-115 GEN
Solar/Wind Harmer
2.499
219904AC1-010 C
Solar/Wind Helper
0.096
3150011OMF A
50/50
0.364
972197AH1-683 GEN
50/50
3.854
972135AH1-637 GEN
Solar/Wind Harmer
1.956
966881AG1-559 GEN
Solar/Wind Harmer
0.196
958261AF2-120 GEN
Solar/Wind Harmer
7.191
3142416OLDCHRC
Solar/Wind Harmer
-0.047
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.113
3142433PROV 92
Solar/Wind Harmer
-0.072
3142433PROV 92
Adder
0.312
3142433PROV 92
Adder
0.312
315975AC1-164 GENB
Solar/Wind Harmer
0.121
316447AC1-158 HLD
Solar/Wind Harmer
3.833
316192AB2-158 GEN
Solar/Wind Harmer
2.077
3145336SMITFLD
Solar/Wind Harmer
-0.069
316375AC2-012 GEN
Solar/Wind Harmer
5.976
3146456SLIGO L269
Solar/Wind Harmer
-0.017
3150221REMNGT2
Adder
19.031
3150211REMNGT1
Adder
18.905
972201AH1-685 GEN
Adder
3.283
315683AE1-153 C
Solar/Wind Harmer
15.743
3145663CRESWEL
Solar/Wind Harmer
-0.046
3146206CASHIE
Solar/Wind Harmer
-0.016
316023GEN1_S
Solar/Wind Harmer
1.106
3146173TUNIS
Solar/Wind Harmer
-0.016
970937AG2-583 GEN
Solar/Wind Harmer
11.757
3156021HOLLOMANSOL
Solar/Wind Harmer
2.197
3145683EARLEYS
Solar/Wind Harmer
-0.016
3147043LAWRENC
Adder
1.305
232426Y1-080 FULL
Solar/Wind Helper
0.064
233996TM1833_GEN
Solar/Wind Helper
0.337
219766PARADISE C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.088
219680HOPEWELLV C1
Solar/Wind Helper
0.005
218440SUMMTASSOC C
Solar/Wind Helper
0.025
217208PARK ELE C
Solar/Wind Helper
0.007
20674628WNG_W3-110
Solar/Wind Helper
0.133
205932AD2-116_GEN
Solar/Wind Helper
0.664
219906AC1-017 C
Solar/Wind Helper
0.066
20720828JCB_W4-025
Solar/Wind Helper
0.099
20714828MDF_W3-079
Solar/Wind Helper
0.202
20742028HF_AC1-207
Solar/Wind Helper
0.217
218438BLK ROCK C
Solar/Wind Helper
0.042
217202FBANKSOLAR C
Solar/Wind Helper
0.005
217201HACKENSOLA C
Solar/Wind Helper
0.005
217206BARNGR HS C
Solar/Wind Helper
0.01
217204WCALDSOLAR C
Solar/Wind Helper
0.005
20674828DL_W4-046
Solar/Wind Helper
0.012
3150021OMF B
50/50
0.364
3150371LDYSMT1
50/50
23.851
971781AH1-399 GEN
Solar/Wind Harmer
1.18
966881AG1-559 GEN
Solar/Wind Harmer
0.573
961951AG1-038 GEN
Solar/Wind Harmer
2.431
316473AC1-191 GEN
Solar/Wind Harmer
1.982
3142416OLDCHRC
Solar/Wind Harmer
1.832
3141766HARMONY
Solar/Wind Harmer
1.613
3142433PROV 92
Adder
0.312
3142433PROV 92
Adder
0.312
3142946ENON
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
1.982
315813AE1-149 C
Solar/Wind Harmer
10.876
3145336SMITFLD
Solar/Wind Harmer
-0.007
316017AA1-139 ULT1
Solar/Wind Harmer
1.389
3141316ARNOLDS
50/50
0.025
3141426STAFORD
Solar/Wind Harmer
-0.005
316468AD1-105 GEN
Solar/Wind Harmer
2.189
3141913WHIT STONE
Solar/Wind Harmer
-0.018
957831AF2-077 GEN
Solar/Wind Harmer
0.537
971285AH1-108 GEN
Adder
1.194
315839AE2-212 C
Solar/Wind Harmer
0.528
315697AD1-025 GEN
Solar/Wind Harmer
3.535
971445AH1-216 GEN
Solar/Wind Harmer
10.762
3151081ELIZAR1
Adder
14.098
3151091ELIZAR2
Adder
13.853
316316AC1-027 C
Solar/Wind Harmer
0.529
957871AF2-081 GEN
Solar/Wind Harmer
8.605
316258AE1-075 C
Solar/Wind Harmer
0.41
970673AG2-436 GEN
Solar/Wind Harmer
36.553
970683AG2-441 GEN
Solar/Wind Harmer
11.36
970681AG2-440 GEN
Solar/Wind Harmer
7.54
3145796HORNRTN
Solar/Wind Harmer
-0.051
3145796HORNRTN
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Harmer
0.538
233940AF2-379 C
Solar/Wind Helper
0.102
230434AG1-499 GEN
Solar/Wind Helper
0.366
219258KINSLEYDEP C
Solar/Wind Helper
0.122
20673828FLE_V3-070
Solar/Wind Helper
0.131
20676128MHD_W3-029
Solar/Wind Helper
0.145
209027LOR2_Q27
Solar/Wind Helper
1.417
964051AG1-259 GEN
Solar/Wind Helper
0.088
964061AG1-260 GEN
Solar/Wind Helper
0.088
970831AG2-522 GEN
Solar/Wind Harmer
6.103
972223AH1-696 GEN
50/50
17.555
3141346CRANES
50/50
0.243
972219AH1-694 GEN
50/50
2.775
3150351NORNECKC2
50/50
1.756
964211AG1-282 GEN
Solar/Wind Harmer
0.559
316314AB2-024 C
Solar/Wind Harmer
1.548
944631AF1-128 GEN
Adder
75.705
971317AH1-138 GEN
Solar/Wind Harmer
2.215
3143526WINTERP
Solar/Wind Harmer
-0.092
315671AE2-027_GEN
Solar/Wind Harmer
3.182
316072AD1-144
Solar/Wind Harmer
0.348
944591AF1-124 GEN
Solar/Wind Harmer
78.765
939411AE1-173 GEN
Solar/Wind Harmer
85.489
940641AE2-051 GEN
Solar/Wind Harmer
15.983
971685AH1-345 GEN
Solar/Wind Harmer
1.487
3143336POWHATN
Solar/Wind Harmer
2.009
941031AE2-094 GEN
Solar/Wind Harmer
31.448
971547AH1-271 GEN
Solar/Wind Harmer
4.113
960081AF2-299 GEN
Solar/Wind Harmer
1.837
3145823KELFORD
Solar/Wind Harmer
-0.016
3145783HORNRTN
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.016
316034AC1-036 C
Solar/Wind Harmer
0.297
972277AH1-723 GEN
Adder
85.125
3144293JTRSVLE
Adder
0.34
3144293JTRSVLE
Adder
0.268
232408W1-005 C
Solar/Wind Helper
0.834
233944AB2-135 GEN
Solar/Wind Helper
0.97
219907AC1-030 C
Solar/Wind Helper
0.053
20716028EGP_W2-019
Solar/Wind Helper
0.029
218428ETC SOLAR C
Solar/Wind Helper
0.007
219908AB1-139 C
Solar/Wind Helper
0.112
20673628F1S_V4-069
Solar/Wind Helper
0.045
20676228FRD_X1-012
Solar/Wind Helper
0.136
20675828AU_W4-064
Solar/Wind Helper
0.044
207484AF2-139 C O1
Solar/Wind Helper
0.124
20675728RH_W2-091
Solar/Wind Helper
0.121
946731AF1-337 GEN
Solar/Wind Helper
0.59
205916AD1-020 GEN
Solar/Wind Helper
1.651
3150071POSSM 5
50/50
101.578
3150391LDYSMT3
50/50
24.637
316312AB1-027
Solar/Wind Harmer
0.611
316441AF1-014 GEN
Solar/Wind Harmer
1.221
3143526WINTERP
Solar/Wind Harmer
-0.092
944641AF1-129 GEN
Adder
75.002
316185AD1-033 GEN
Solar/Wind Harmer
1.816
3144356SAPONY
Solar/Wind Harmer
0.591
316315AB2-025 C
Solar/Wind Harmer
0.456
972185AH1-677 GEN
Adder
8.299
970099AG2-077 GEN
Solar/Wind Harmer
20.237
962571AG1-106 GEN
Solar/Wind Harmer
2.326
3145783HORNRTN
Solar/Wind Harmer
1.913
3145783HORNRTN
Solar/Wind Harmer
1.53
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
3145796HORNRTN
Solar/Wind Harmer
-0.048
3144293JTRSVLE
Adder
0.34
223402AF1-300 C
Solar/Wind Helper
0.732
233946AB2-136 GEN
Solar/Wind Helper
0.936
233930AB2-032 GEN
Solar/Wind Helper
0.626
233982AB2-133 GEN
Solar/Wind Helper
0.59
232410W1-006 C
Solar/Wind Helper
0.834
233952AC2-187 GEN
Solar/Wind Helper
0.382
233954AC2-188 GEN
Solar/Wind Helper
0.382
230511AF1-262
Solar/Wind Helper
0.023
228754AB1-001 C
Solar/Wind Helper
0.041
219272CLEANLIGHT C
Solar/Wind Helper
0.04
217081WEATEXAS C
Solar/Wind Helper
0.019
207471AF2-354 C
Solar/Wind Helper
0.25
20675928HOL_W4-097
Solar/Wind Helper
0.074
961431AF2-434 GEN
Solar/Wind Helper
0.6
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
1.99
3145273HOLLAND
Solar/Wind Harmer
-0.013
3150241REMNGT4
Adder
19.157
972199AH1-684 GEN
Adder
2.905
3146376EDENTON
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316181AB2-040 GEN
Solar/Wind Harmer
2.263
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.05
959311AF2-222 GEN
Solar/Wind Harmer
16.774
972255AH1-712 GEN
Adder
73.05
316478AD1-087 GEN
Solar/Wind Harmer
1.382
227287AC2-120 GEN
Solar/Wind Helper
1.239
232422X3-066 FULL
Solar/Wind Helper
0.188
233964AF2-378 GEN
Solar/Wind Helper
0.069
232406W1-004 FULL
Solar/Wind Helper
0.834
232434Z2-077 GEN
Solar/Wind Helper
0.209
230415AB2-049 C
Solar/Wind Helper
0.048
219291REEVESSOUT C
Solar/Wind Helper
0.018
219236SOUTHERNHQ C
Solar/Wind Helper
0.008
20714928UPF_X1-085
Solar/Wind Helper
0.008
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.726
3150081POSSM6A
50/50
1.651
3150351NORNECKC2
50/50
1.785
316077AC2-138 C
Solar/Wind Harmer
0.392
316484AD2-074 GEN
Solar/Wind Harmer
4.646
316075AC2-137 C
Solar/Wind Harmer
0.485
3144216WINCHST
Adder
0.59
315778AD1-151 GEN
Solar/Wind Harmer
15.614
3151101ELIZAR3
Adder
14.278
944601AF1-125 GEN
Solar/Wind Harmer
77.257
3141196NOKESVL
Solar/Wind Harmer
-0.068
972217AH1-693 GEN
Adder
2.526
3143336POWHATN
Solar/Wind Harmer
1.708
3151761LOISA E
Adder
19.927
3151721LOISA A
Adder
9.724
966621AG1-532 GEN
Solar/Wind Harmer
0.331
316317KELFORD C
Solar/Wind Harmer
0.749
3145823KELFORD
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.064
3145796HORNRTN
Solar/Wind Harmer
-0.016
942461AE2-259 GEN
Solar/Wind Harmer
2.414
964241AG1-285 GEN
Solar/Wind Harmer
12.529
972003AH1-546 GEN
Solar/Wind Harmer
6.505
3144293JTRSVLE
Adder
0.34
226910AB2-157 C
Solar/Wind Helper
0.048
233933AB2-153 GEN
Solar/Wind Helper
0.383
219623KINSLEYBEA C
Solar/Wind Helper
0.003
219612MATRIX C
Solar/Wind Helper
0.037
20716928W4-060COL
Solar/Wind Helper
0.079
217213AMBOY SO C
Solar/Wind Helper
0.044
20673728F2S_V4-070
Solar/Wind Helper
0.045
207510AF2-138 C
Solar/Wind Helper
0.121
207437AD2-070 GEN
Solar/Wind Helper
0.204
20671928W4-073
Solar/Wind Helper
0.132
209116AE2-175 GEN
Solar/Wind Helper
2.589
961421AF2-433 GEN
Solar/Wind Helper
0.6
946691AF1-333 GEN
Solar/Wind Helper
0.59
946741AF1-338 GEN
Solar/Wind Helper
0.59
CBM West 2LTFEXP_CBM-W2->PJM
CBM
91.109
LGEELTFEXP_LGEE->PJM
CLTF
4.337
MECLTFEXP_MEC->PJM
CLTF
10.565
AH1-155LTFEXP_AH1-155->PJM
LTF
0.205
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.068
CPLELTFEXP_CPLE->PJM
CLTF
10.55
SIGELTFEXP_SIGE->PJM
CLTF
0.334
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.93
WECLTFEXP_WEC->PJM
CLTF
2.304
LAGNLTFEXP_LAGN->PJM
CLTF
14.57
CBM West 1LTFEXP_CBM-W1->PJM
CBM
85.469
NYPJM->LTFIMP_NY
CLTF
6.555
TVALTFEXP_TVA->PJM
CLTF
7.359
AG2-052LTFEXP_AG2-052->PJM
LTF
0.137

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL_SENS


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL_SENS
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.83 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3279.67
MW Contribution:
2.43
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
3150181POSSMC2
50/50
2.006
3150181POSSMC2
50/50
1.99
3150181POSSMC2
50/50
1.99
972195AH1-682 GEN
50/50
2.813
3150341NORNECKC1
50/50
1.594
3150341NORNECKC1
50/50
1.581
315673AE1-157 GEN
Solar/Wind Harmer
12.502
3140676OCCOQUN
50/50
0.024
972213AH1-691 GEN
50/50
3.483
944491AF1-114 GEN
Solar/Wind Harmer
5.051
3138133OCRAN
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.003
3143873LANEXA
Solar/Wind Harmer
-0.009
957191AF2-013 GEN
50/50
14.169
3150021OMF B
50/50
0.319
3150371LDYSMT1
50/50
20.723
971781AH1-399 GEN
Solar/Wind Harmer
1.024
966881AG1-559 GEN
Solar/Wind Harmer
0.497
970053AG2-049 GEN
50/50
2.882
3150381LDYSMT2
50/50
20.589
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
316059AD1-063 C
Solar/Wind Harmer
0.351
3142433PROV 92
Adder
0.268
3150011OMF A
50/50
0.319
972197AH1-683 GEN
50/50
3.349
972135AH1-637 GEN
Solar/Wind Harmer
1.704
966881AG1-559 GEN
Solar/Wind Harmer
0.17
958261AF2-120 GEN
Solar/Wind Harmer
6.21
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.818
3142433PROV 92
Solar/Wind Harmer
-0.062
3142433PROV 92
Adder
0.268
3142433PROV 92
Adder
0.268
315975AC1-164 GENB
Solar/Wind Harmer
0.104
316447AC1-158 HLD
Solar/Wind Harmer
3.258
316192AB2-158 GEN
Solar/Wind Harmer
1.766
3145336SMITFLD
Solar/Wind Harmer
-0.059
316375AC2-012 GEN
Solar/Wind Harmer
5.105
3146456SLIGO L269
Solar/Wind Harmer
-0.015
315683AE1-153 C
Solar/Wind Harmer
13.241
3145663CRESWEL
Solar/Wind Harmer
-0.039
3150221REMNGT2
Adder
15.911
3150211REMNGT1
Adder
15.806
972201AH1-685 GEN
Adder
2.745
3146206CASHIE
Solar/Wind Harmer
-0.014
316023GEN1_S
Solar/Wind Harmer
0.939
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.865
3145683EARLEYS
Solar/Wind Harmer
-0.014
970937AG2-583 GEN
Solar/Wind Harmer
9.936
3147043LAWRENC
Adder
1.105
232426Y1-080 FULL
Solar/Wind Helper
0.048
233996TM1833_GEN
Solar/Wind Helper
0.255
219766PARADISE C
Solar/Wind Helper
0.065
20714528FRN_Y2-051
Solar/Wind Helper
0.066
219680HOPEWELLV C1
Solar/Wind Helper
0.004
218440SUMMTASSOC C
Solar/Wind Helper
0.019
217208PARK ELE C
Solar/Wind Helper
0.005
3150091POSSM6B
50/50
1.478
3150411LDYSMT5
50/50
21.513
972215AH1-692 GEN
50/50
3.483
3141813NORNECK
Solar/Wind Harmer
-0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.466
3150101POSSM6S
50/50
2.254
3150401LDYSMT4
50/50
21.446
3141906WESTMOR
Solar/Wind Harmer
-0.007
957971AF2-091 GEN
Solar/Wind Harmer
1.717
316404AE1-155 C
Solar/Wind Harmer
3.059
3138133OCRAN
Solar/Wind Harmer
-0.009
315662AE1-191 GEN
Solar/Wind Harmer
1.874
316280AD1-041 GEN
Solar/Wind Harmer
1.171
3143096IRON208
Adder
0.572
3142543TWELFTH
Solar/Wind Harmer
-0.001
316044AC1-158 PL1
Solar/Wind Harmer
1.481
3138126ROCKLANDING
Solar/Wind Harmer
0.046
971069AG2-661 GEN
Solar/Wind Harmer
2.376
316369SG1_INVT
Solar/Wind Harmer
2.675
3143226MDLTHAN
Solar/Wind Harmer
-0.015
961611AG1-000B GEN
Solar/Wind Harmer
7.38
3151171GRAVELC
Adder
1.413
3147666LOUISA
Solar/Wind Harmer
-0.059
316381AD1-082 GEN
Solar/Wind Harmer
1.355
3150981CHESPKA
Adder
1.64
319010AE1-072 C
Solar/Wind Harmer
2.96
316254AC1-120 GEN1
Solar/Wind Harmer
5.477
315611Z1-036_GEN2
Solar/Wind Harmer
3.547
3130156CHOWAN
Solar/Wind Harmer
-0.014
3151751LOISA D
Adder
8.253
315816AE2-034 GEN
Solar/Wind Harmer
1.144
971163AH1-040 GEN
Solar/Wind Harmer
13.291
3150281M RUN A
Adder
17.089
315737AD1-076 GEN
Solar/Wind Harmer
2.663
316087AB2-174 GEN
Solar/Wind Harmer
1.965
970087AG2-069 GEN
Solar/Wind Harmer
12.909
957481AF2-042 GEN
Solar/Wind Harmer
42.844
315693AD1-088 GEN
Solar/Wind Harmer
6.826
970685AG2-442 GEN
Solar/Wind Harmer
11.898
3146926FARMVIL
Solar/Wind Harmer
-0.008
971563AH1-280 GEN
Solar/Wind Harmer
1.688
208835TUHI V3-051
Solar/Wind Helper
0.029
233998TM1NIN_3.36
Solar/Wind Helper
0.255
232404W1-003 C
Solar/Wind Helper
0.63
20715828PEM_W1-120
Solar/Wind Helper
0.112
972189AH1-679 GEN
Adder
2.392
316487AF1-042 GEN
Solar/Wind Harmer
2.098
3150151POSSMC1
50/50
1.99
3150151POSSMC1
50/50
1.99
3150331BIRCHWDA
50/50
29.538
3150501FRIVERG
50/50
1.208
316223AC1-118
Solar/Wind Harmer
0.448
3150151POSSMC1
50/50
1.99
3150071POSSM 5
50/50
90.937
3150391LDYSMT3
50/50
21.406
3150081POSSM6A
50/50
1.478
3150351NORNECKC2
50/50
1.543
316077AC2-138 C
Solar/Wind Harmer
0.339
316484AD2-074 GEN
Solar/Wind Harmer
4.009
3141316ARNOLDS
50/50
0.022
3141426STAFORD
Solar/Wind Harmer
-0.004
316468AD1-105 GEN
Solar/Wind Harmer
1.898
3141913WHIT STONE
Solar/Wind Harmer
-0.016
972223AH1-696 GEN
50/50
15.716
3141346CRANES
50/50
0.215
972219AH1-694 GEN
50/50
2.411
3150351NORNECKC2
50/50
1.517
964211AG1-282 GEN
Solar/Wind Harmer
0.483
316314AB2-024 C
Solar/Wind Harmer
1.331
944631AF1-128 GEN
Adder
64.944
971317AH1-138 GEN
Solar/Wind Harmer
1.899
3143526WINTERP
Solar/Wind Harmer
-0.078
315671AE2-027_GEN
Solar/Wind Harmer
2.725
316072AD1-144
Solar/Wind Harmer
0.297
944591AF1-124 GEN
Solar/Wind Harmer
67.278
939411AE1-173 GEN
Solar/Wind Harmer
72.919
940641AE2-051 GEN
Solar/Wind Harmer
13.627
3143336POWHATN
Solar/Wind Harmer
1.708
941031AE2-094 GEN
Solar/Wind Harmer
26.758
971685AH1-345 GEN
Solar/Wind Harmer
1.246
971547AH1-271 GEN
Solar/Wind Harmer
3.494
960081AF2-299 GEN
Solar/Wind Harmer
1.558
3145823KELFORD
Solar/Wind Harmer
-0.014
3145783HORNRTN
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.045
3145796HORNRTN
Solar/Wind Harmer
-0.014
316034AC1-036 C
Solar/Wind Harmer
0.251
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.227
972277AH1-723 GEN
Adder
71.593
232408W1-005 C
Solar/Wind Helper
0.63
233944AB2-135 GEN
Solar/Wind Helper
0.732
219907AC1-030 C
Solar/Wind Helper
0.04
20716028EGP_W2-019
Solar/Wind Helper
0.022
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.084
20673628F1S_V4-069
Solar/Wind Helper
0.034
316312AB1-027
Solar/Wind Harmer
0.525
316441AF1-014 GEN
Solar/Wind Harmer
1.05
944641AF1-129 GEN
Adder
64.259
3143526WINTERP
Solar/Wind Harmer
-0.078
316185AD1-033 GEN
Solar/Wind Harmer
1.551
3144356SAPONY
Solar/Wind Harmer
0.504
316315AB2-025 C
Solar/Wind Harmer
0.389
972185AH1-677 GEN
Adder
7.054
962571AG1-106 GEN
Solar/Wind Harmer
1.972
970099AG2-077 GEN
Solar/Wind Harmer
17.138
3145783HORNRTN
Solar/Wind Harmer
1.62
3145783HORNRTN
Solar/Wind Harmer
1.296
3145783HORNRTN
Solar/Wind Harmer
0.405
3145783HORNRTN
Solar/Wind Harmer
0.162
3145796HORNRTN
Solar/Wind Harmer
-0.041
3144293JTRSVLE
Adder
0.287
223402AF1-300 C
Solar/Wind Helper
0.645
233946AB2-136 GEN
Solar/Wind Helper
0.706
233930AB2-032 GEN
Solar/Wind Helper
0.472
232410W1-006 C
Solar/Wind Helper
0.63
233982AB2-133 GEN
Solar/Wind Helper
0.445
233952AC2-187 GEN
Solar/Wind Helper
0.288
233954AC2-188 GEN
Solar/Wind Helper
0.288
230511AF1-262
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.031
219272CLEANLIGHT C
Solar/Wind Helper
0.03
217081WEATEXAS C
Solar/Wind Helper
0.014
207471AF2-354 C
Solar/Wind Helper
0.185
20675928HOL_W4-097
Solar/Wind Helper
0.055
966871AG1-558 GEN
Solar/Wind Harmer
0.477
966871AG1-558 GEN
Solar/Wind Harmer
0.163
3142296MT RD221
Adder
0.445
316156AD2-030 GEN
Solar/Wind Harmer
0.415
315666AE1-190 GEN
Solar/Wind Harmer
0.468
3150671DARBY 1
Adder
9.878
3138283WHITEMARSH
Solar/Wind Harmer
0.024
316233AE1-074 FULL
Solar/Wind Harmer
0.407
971283AH1-107 GEN
Solar/Wind Harmer
2.46
3151191GRAVEL3
Adder
9.548
316164AC1-076 GEN
Solar/Wind Harmer
1.254
315833AF1-017_GEN
Solar/Wind Harmer
2.792
316018AA1-139 ULT2
Solar/Wind Harmer
1.256
3146406KITTY HAWK
Solar/Wind Harmer
0.012
315800Z1-036_GEN1
Solar/Wind Harmer
3.547
971967AH1-528 GEN
Solar/Wind Harmer
26.504
315732AD1-074 GEN1
Solar/Wind Harmer
2.832
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
3150681DARBY 2
Adder
9.889
316450AC1-158 RIC
Solar/Wind Harmer
0.395
316033AB2-134 GEN
Solar/Wind Harmer
4.829
3145506HICKORY
Solar/Wind Harmer
-0.059
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316339AD2-160 GEN
Solar/Wind Harmer
0.989
316388AE2-253 GEN
Solar/Wind Harmer
0.989
3137176SLIGO L2192
Solar/Wind Harmer
-0.058
3130086AYDLETT
Solar/Wind Harmer
-0.058
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
966001AG1-469 GEN
Solar/Wind Harmer
0.27
3151731LOISA B
Adder
8.253
313506AB2-031 GEN
Solar/Wind Harmer
1.104
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
0.114
970301AG2-198 GEN
Solar/Wind Harmer
6.798
970323AG2-213 GEN
Solar/Wind Harmer
6.74
223401AF1-299 GEN
Solar/Wind Helper
0.645
232424Y1-079 C
Solar/Wind Helper
0.144
232428Y3-058 C
Solar/Wind Helper
0.42
234015AF2-250 C
Solar/Wind Helper
0.047
230433AD2-135 GEN
Solar/Wind Helper
0.02
214067T20SOLAR
Solar/Wind Helper
0.013
207459AE1-142 C O1
Solar/Wind Helper
0.336
20675428EAM_W2-061
Solar/Wind Helper
0.018
316463AE2-346 GEN
Solar/Wind Harmer
0.224
3145513AHOSKIE
Solar/Wind Harmer
0.121
3145513AHOSKIE
Solar/Wind Harmer
-0.014
970085AG2-068 GEN
Solar/Wind Harmer
8.606
3137643SOCKMAN
Solar/Wind Harmer
-0.055
316426AA2-053 GEN
Solar/Wind Harmer
1.382
315652AC1-086 GEN
Solar/Wind Harmer
15.431
316174AB2-169 GEN
Solar/Wind Harmer
2.105
946301AF1-294 GEN
Solar/Wind Harmer
3.461
3144303KENBRDG
Solar/Wind Harmer
-0.011
226929AD2-058 GEN
Solar/Wind Helper
0.389
233901CHERRYDALE C
Solar/Wind Helper
0.289
20715028HAN_X4-015
Solar/Wind Helper
0.067
207445AB1-138_GEN
Solar/Wind Helper
0.121
20720628TIN_W1-124
Solar/Wind Helper
0.218
20675528CPH_W2-050
Solar/Wind Helper
0.128
20676428JCR_X2-075
Solar/Wind Helper
0.076
20675128HRM_W1-127
Solar/Wind Helper
0.032
205956AE1-196_GEN
Solar/Wind Helper
0.53
209029WAYMART-WD
Solar/Wind Helper
0.835
316203AE2-005 GEN
Solar/Wind Harmer
6.567
970293AG2-193 GEN
Solar/Wind Harmer
1.937
3150921YORKTN3
Adder
3.376
3144536CHRHLND
Solar/Wind Harmer
-0.002
3142956BIRDNECK
Solar/Wind Harmer
0.791
944581AF1-123 GEN
Solar/Wind Harmer
67.036
316305AF2-043 C
Solar/Wind Harmer
0.441
316320Y1-086
Solar/Wind Harmer
0.855
3146516WINFALL
Solar/Wind Harmer
-0.014
3132273ORANGE
Solar/Wind Harmer
-0.003
944011AF1-069 GEN
Solar/Wind Harmer
8.384
3150291M RUN B
Adder
16.952
315735AD1-075 GEN1
Solar/Wind Harmer
1.416
3145893MURPHYS
Solar/Wind Harmer
0.097
3145893MURPHYS
Solar/Wind Harmer
-0.014
3146263WOODLND
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.014
316011AB1-132 GEN
Solar/Wind Harmer
2.865
3146776BUCKING
Solar/Wind Harmer
-0.005
233987AB2-037 GEN
Solar/Wind Helper
2.911
232417X3-008 C
Solar/Wind Helper
0.289
233923SMA
Solar/Wind Helper
0.933
233997TMININ_4.2
Solar/Wind Helper
0.255
233935AB2-179 C
Solar/Wind Helper
1.573
959561AF2-247 GEN
Solar/Wind Helper
0.024
20715728PEM_W1-119
Solar/Wind Helper
0.112
219249CENTRALDIV C
Solar/Wind Helper
0.011
207442AE1-156 GEN
Solar/Wind Helper
0.368
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.03
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.162
957921AF2-086 GEN
Solar/Wind Helper
0.436
963711AG1-223 GEN
Solar/Wind Helper
0.074
219276PARKLANDSO C
Solar/Wind Helper
0.103
20715228NPK_W1-113
Solar/Wind Helper
0.09
20720528MAN_W1-024
Solar/Wind Helper
0.032
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.033
20676328BVR_Y1-020
Solar/Wind Helper
0.03
20674928WA_W3-044
Solar/Wind Helper
0.108
207518AF1-320_GEN
Solar/Wind Helper
1.72
957831AF2-077 GEN
Solar/Wind Harmer
0.461
971285AH1-108 GEN
Adder
1.024
315839AE2-212 C
Solar/Wind Harmer
0.452
315697AD1-025 GEN
Solar/Wind Harmer
3.026
971445AH1-216 GEN
Solar/Wind Harmer
9.202
3151081ELIZAR1
Adder
12.044
3151091ELIZAR2
Adder
11.835
316316AC1-027 C
Solar/Wind Harmer
0.452
957871AF2-081 GEN
Solar/Wind Harmer
7.347
316258AE1-075 C
Solar/Wind Harmer
0.348
970673AG2-436 GEN
Solar/Wind Harmer
31.088
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.005
970683AG2-441 GEN
Solar/Wind Harmer
9.607
970681AG2-440 GEN
Solar/Wind Harmer
6.376
316322AB2-045
Solar/Wind Harmer
0.454
316210AC1-098 GEN
Solar/Wind Harmer
2.113
970831AG2-522 GEN
Solar/Wind Harmer
6.744
233940AF2-379 C
Solar/Wind Helper
0.077
230434AG1-499 GEN
Solar/Wind Helper
0.274
219258KINSLEYDEP C
Solar/Wind Helper
0.091
20673828FLE_V3-070
Solar/Wind Helper
0.098
20676128MHD_W3-029
Solar/Wind Helper
0.108
209027LOR2_Q27
Solar/Wind Helper
1.043
20676228FRD_X1-012
Solar/Wind Helper
0.101
20675828AU_W4-064
Solar/Wind Helper
0.033
207484AF2-139 C O1
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.089
316382AG1-145 C
Solar/Wind Harmer
0.458
316159AE1-175 C
Solar/Wind Harmer
0.408
971281AH1-106 GEN
Solar/Wind Harmer
2.46
3143316POE
Solar/Wind Harmer
-0.059
316236AE1-162_GEN
Solar/Wind Harmer
0.447
970657AG2-426 GEN
Solar/Wind Harmer
0.933
3146486SUNBURY
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.015
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
316405AF2-144 C
Solar/Wind Harmer
0.368
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
970533AG2-339 GEN
Solar/Wind Harmer
9.597
3147346CASHSCORNER
Solar/Wind Harmer
0.219
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315733AD1-074 GEN2
Solar/Wind Harmer
2.832
970601AG2-382 GEN
Solar/Wind Harmer
6.114
946281AF1-292 GEN
Solar/Wind Harmer
0.31
970581AG2-369 GEN
Solar/Wind Harmer
7.401
3146033SCOT NK
Solar/Wind Harmer
-0.054
972205AH1-687 GEN
Adder
5.125
233915AB1-141 GEN
Solar/Wind Helper
0.623
228728W1-130C
Solar/Wind Helper
0.064
227927V4-067C
Solar/Wind Helper
0.012
219615MILLCREEK C
Solar/Wind Helper
0.031
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.525
961261AF2-417 GEN
Solar/Wind Helper
0.456
212266LOR1
Solar/Wind Helper
0.304
316337AD2-073 GEN
Solar/Wind Harmer
0.439
3141726DUNNSVL
Solar/Wind Harmer
-0.064
962861AG1-135 GEN
Solar/Wind Harmer
6
3150851SPRUNCC
Adder
0.626
316132AB2-190 GEN1
Solar/Wind Harmer
1.517
315773AC2-141 GEN
Solar/Wind Harmer
6.192
316036AC1-147 C
Solar/Wind Harmer
0.397
316093AE2-104_GEN
Solar/Wind Harmer
4.257
316170AC1-121 GEN2
Solar/Wind Harmer
1.826
3146516WINFALL
Solar/Wind Harmer
-0.047
3146516WINFALL
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
-0.056
3145893MURPHYS
Solar/Wind Harmer
0.414
970919AG2-571 GEN
Solar/Wind Harmer
4.38
315607AA1-063A GEN
Solar/Wind Harmer
1.393
3146263WOODLND
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.014
3146776BUCKING
Solar/Wind Harmer
-0.005
233918AB1-142 GEN
Solar/Wind Helper
0.623
228729W2-030 C
Solar/Wind Helper
0.132
219686LUMSOLAR_N C
Solar/Wind Helper
0.047
219348LDSOLAR C
Solar/Wind Helper
0.135
218524CNTRALGAS1 C
Solar/Wind Helper
0.182
20671828STAW2-080
Solar/Wind Helper
0.03
217209CENTRL HS C
Solar/Wind Helper
0.009
316045AC1-158 PL2
Solar/Wind Harmer
4.741
316240AF1-291 C
Solar/Wind Harmer
0.455
971223AH1-071 GEN
Solar/Wind Harmer
1.875
3150991CHESPKB
Adder
1.376
3150991CHESPKB
Adder
1.343
315835AF2-110_GEN
Solar/Wind Harmer
1.83
316435W1029_GEN3
Solar/Wind Harmer
2.632
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
316313AB2-026
Solar/Wind Harmer
0.387
316006AB2-029 C
Solar/Wind Harmer
0.817
315614AA2-178 GEN
Solar/Wind Harmer
1.525
972187AH1-678 GEN
Adder
3.563
316065AD1-022 GEN
Solar/Wind Harmer
7
3145893MURPHYS
Solar/Wind Harmer
0.39
3145893MURPHYS
Solar/Wind Harmer
-0.025
316140AB2-099
Solar/Wind Harmer
0.093
3146776BUCKING
Solar/Wind Harmer
-0.054
3146776BUCKING
Solar/Wind Harmer
-0.004
972193AH1-681 GEN
Adder
2.745
234036AF2-325 C
Solar/Wind Helper
0.052
232436AB1-176 C
Solar/Wind Helper
0.055
233994AC2-023 GEN
Solar/Wind Helper
1.193
219912AD2-042 GEN
Solar/Wind Helper
0.177
219607WPEMNERT C
Solar/Wind Helper
0.094
219304NAMERICA C
Solar/Wind Helper
0.154
20674328GAR_V4-001
Solar/Wind Helper
0.025
207439AE1-081 C O1
Solar/Wind Helper
0.021
207530AG1-191 GEN
Solar/Wind Helper
0.073
211065PSPA IPP
Solar/Wind Helper
0.162
961301AF2-421 GEN
Solar/Wind Helper
0.455
963151AG1-164 GEN
Solar/Wind Helper
0.455
961341AF2-425 GEN
Solar/Wind Helper
0.442
3150691DARBY 3
Adder
9.924
3150701DARBY 4
Adder
9.901
3142366NRTHEST
Adder
0.451
315976AC1-164 GENA
Solar/Wind Harmer
3.514
316169AC1-164_GENC
Solar/Wind Harmer
3.037
3142946ENON
Solar/Wind Harmer
-0.002
316294AC1-161 GEN
Solar/Wind Harmer
4.787
316083AB2-161 GEN
Solar/Wind Harmer
2.402
316349AD2-085 GEN
Solar/Wind Harmer
1.305
3146456SLIGO L269
Solar/Wind Harmer
1.734
3146386ELIZ CT
Solar/Wind Harmer
-0.015
316431W1029_GEN1
Solar/Wind Harmer
2.632
316433W1029_GEN2
Solar/Wind Harmer
2.632
315742AE1-103 GEN
Solar/Wind Harmer
3.412
3146376EDENTON
Solar/Wind Harmer
0.425
3146376EDENTON
Solar/Wind Harmer
0.425
316336AC2-165 C
Solar/Wind Harmer
8.886
970933AG2-581 GEN
Solar/Wind Harmer
13.132
316365GEN2_N
Solar/Wind Harmer
0.939
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
2.11
219904AC1-010 C
Solar/Wind Helper
0.072
219906AC1-017 C
Solar/Wind Helper
0.049
20720828JCB_W4-025
Solar/Wind Helper
0.074
20714828MDF_W3-079
Solar/Wind Helper
0.15
961951AG1-038 GEN
Solar/Wind Harmer
2.098
316473AC1-191 GEN
Solar/Wind Harmer
1.708
3142416OLDCHRC
Solar/Wind Harmer
1.576
3141766HARMONY
Solar/Wind Harmer
1.387
3142433PROV 92
Adder
0.268
3142433PROV 92
Adder
0.268
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.697
315813AE1-149 C
Solar/Wind Harmer
9.3
3145336SMITFLD
Solar/Wind Harmer
-0.006
316017AA1-139 ULT1
Solar/Wind Harmer
1.186
3146456SLIGO L269
Solar/Wind Harmer
-0.015
971153AH1-033 GEN
Solar/Wind Harmer
1.699
3145273HOLLAND
Solar/Wind Harmer
-0.011
3146376EDENTON
Solar/Wind Harmer
-0.014
3150241REMNGT4
Adder
16.017
972199AH1-684 GEN
Adder
2.428
3146206CASHIE
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.918
3147043LAWRENC
Solar/Wind Harmer
-0.008
959311AF2-222 GEN
Solar/Wind Harmer
14.185
3147133PAMPLIN
Solar/Wind Harmer
-0.042
316478AD1-087 GEN
Solar/Wind Harmer
1.168
972255AH1-712 GEN
Adder
61.437
227287AC2-120 GEN
Solar/Wind Helper
1.237
233964AF2-378 GEN
Solar/Wind Helper
0.052
232422X3-066 FULL
Solar/Wind Helper
0.142
232406W1-004 FULL
Solar/Wind Helper
0.63
232434Z2-077 GEN
Solar/Wind Helper
0.157
230415AB2-049 C
Solar/Wind Helper
0.036
219291REEVESSOUT C
Solar/Wind Helper
0.014
219236SOUTHERNHQ C
Solar/Wind Helper
0.006
20714928UPF_X1-085
Solar/Wind Helper
0.006
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.543
316075AC2-137 C
Solar/Wind Harmer
0.417
3144216WINCHST
Adder
0.506
315778AD1-151 GEN
Solar/Wind Harmer
13.365
3151101ELIZAR3
Adder
12.198
944601AF1-125 GEN
Solar/Wind Harmer
65.99
3143336POWHATN
Solar/Wind Harmer
1.452
3151761LOISA E
Adder
16.826
3151721LOISA A
Adder
8.211
3141196NOKESVL
Solar/Wind Harmer
-0.056
972217AH1-693 GEN
Adder
2.112
966621AG1-532 GEN
Solar/Wind Harmer
0.281
316317KELFORD C
Solar/Wind Harmer
0.635
3145823KELFORD
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.014
964241AG1-285 GEN
Solar/Wind Harmer
10.595
942461AE2-259 GEN
Solar/Wind Harmer
2.038
3144293JTRSVLE
Adder
0.287
316212AC1-099_GEN
Solar/Wind Harmer
1.174
972003AH1-546 GEN
Solar/Wind Harmer
5.477
226910AB2-157 C
Solar/Wind Helper
0.048
233933AB2-153 GEN
Solar/Wind Helper
0.289
219623KINSLEYBEA C
Solar/Wind Helper
0.003
219612MATRIX C
Solar/Wind Helper
0.027
20716928W4-060COL
Solar/Wind Helper
0.059
217213AMBOY SO C
Solar/Wind Helper
0.032
20673728F2S_V4-070
Solar/Wind Helper
0.034
207510AF2-138 C
Solar/Wind Helper
0.09
207437AD2-070 GEN
Solar/Wind Helper
0.151
20671928W4-073
Solar/Wind Helper
0.098
209116AE2-175 GEN
Solar/Wind Helper
1.914
961421AF2-433 GEN
Solar/Wind Helper
0.441
3141873WAN 176
Solar/Wind Harmer
1.85
3141843SHACKLE
Adder
0.708
3143096IRON208
Adder
0.572
3143096IRON208
Adder
0.561
3150861SPRUNCD
Adder
0.626
316458AB2-190 GEN2
Solar/Wind Harmer
1.517
961611AG1-000B GEN
Solar/Wind Harmer
3.149
3151171GRAVELC
Adder
1.858
3147666LOUISA
Solar/Wind Harmer
-0.034
970657AG2-426 GEN
Solar/Wind Harmer
2.99
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.296
316321Z2-027
Solar/Wind Harmer
0.392
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3150301M RUN C
Adder
17.078
3156081AA2-088 GEN
Solar/Wind Harmer
4.559
970917AG2-570 GEN
Solar/Wind Harmer
34.605
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316190AA2-174 GEN
Solar/Wind Harmer
0.168
3146926FARMVIL
Solar/Wind Harmer
-0.008
208835TUHI V3-051
Solar/Wind Helper
0.029
233950AC2-186 GEN
Solar/Wind Helper
0.144
219921AF1-264
Solar/Wind Helper
0.061
219914AD2-027 C
Solar/Wind Helper
0.136
218660EHAMPSOLAR C
Solar/Wind Helper
0.039
219688LUMSOLAR_S C
Solar/Wind Helper
0.047
207454AA2-184 E
Solar/Wind Helper
0.356
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.455
208972BECR K09
Solar/Wind Helper
0.335
961331AF2-424 GEN
Solar/Wind Helper
0.442
970257AG2-171 GEN
Solar/Wind Harmer
4.189
20674628WNG_W3-110
Solar/Wind Helper
0.099
205932AD2-116_GEN
Solar/Wind Helper
0.53
20742028HF_AC1-207
Solar/Wind Helper
0.161
218438BLK ROCK C
Solar/Wind Helper
0.031
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.009
3142433PROV 92
Adder
0.268
3151201GRAVEL4
Adder
9.67
3151221GRAVEL6
Adder
9.659
3151211GRAVEL5
Adder
9.548
316311AC2-079 GEN
Solar/Wind Harmer
7.417
313526AB2-022
Solar/Wind Harmer
0.393
3146396TANGLEW
Solar/Wind Harmer
0.268
315651AD1-115 GEN
Solar/Wind Harmer
6.382
315814AE2-033 C
Solar/Wind Harmer
13.428
3146206CASHIE
Solar/Wind Harmer
-0.014
316318V4-068
Solar/Wind Harmer
0.348
961941AG1-037 GEN
Solar/Wind Harmer
0.104
3146043SEABORD
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.014
316486AD2-202 GEN
Solar/Wind Harmer
0.342
971845AH1-439 GEN
Solar/Wind Harmer
7.184
961791AG1-021 GEN
Solar/Wind Harmer
1.688
232432Z2-076 GEN
Solar/Wind Helper
0.083
230407AD2-065 C
Solar/Wind Helper
0.048
20720728JCB_W1-129
Solar/Wind Helper
0.067
964851AG1-348 GEN
Solar/Wind Helper
0.069
207408W3-077 C
Solar/Wind Helper
0.092
961431AF2-434 GEN
Solar/Wind Helper
0.441
CBM West 2LTFEXP_CBM-W2->PJM
CBM
72.3
LGEELTFEXP_LGEE->PJM
CLTF
3.396
MECLTFEXP_MEC->PJM
CLTF
8.301
AH1-155LTFEXP_AH1-155->PJM
LTF
0.16
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.32
CPLELTFEXP_CPLE->PJM
CLTF
8.786
SIGELTFEXP_SIGE->PJM
CLTF
0.262
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.494
WECLTFEXP_WEC->PJM
CLTF
1.8
LAGNLTFEXP_LAGN->PJM
CLTF
11.662
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.703
NYPJM->LTFIMP_NY
CLTF
4.872
TVALTFEXP_TVA->PJM
CLTF
5.895
AG2-052LTFEXP_AG2-052->PJM
LTF
0.107

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o PEPCO_P4_PP41_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
PEPCO_P4_PP41_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.07 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3194.05
MW Contribution:
2.42
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
PEPCO_P4_PP41_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:98.66 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3057.4
MW Contribution:
2.38
Bus #Bus NameTypeMW Contribution
957971AF2-091 GEN
Solar/Wind Harmer
1.715
316404AE1-155 C
Solar/Wind Harmer
3.053
3138133OCRAN
Solar/Wind Harmer
-0.009
315662AE1-191 GEN
Solar/Wind Harmer
1.87
316280AD1-041 GEN
Solar/Wind Harmer
1.169
3143096IRON208
Adder
0.571
3142543TWELFTH
Solar/Wind Harmer
-0.001
316044AC1-158 PL1
Solar/Wind Harmer
1.478
3138126ROCKLANDING
Solar/Wind Harmer
0.046
971069AG2-661 GEN
Solar/Wind Harmer
2.371
316369SG1_INVT
Solar/Wind Harmer
2.669
3143226MDLTHAN
Solar/Wind Harmer
-0.015
961611AG1-000B GEN
Solar/Wind Harmer
7.364
3151171GRAVELC
Adder
1.41
3147666LOUISA
Solar/Wind Harmer
-0.059
316381AD1-082 GEN
Solar/Wind Harmer
1.352
3150981CHESPKA
Adder
1.637
319010AE1-072 C
Solar/Wind Harmer
2.954
316254AC1-120 GEN1
Solar/Wind Harmer
5.463
315611Z1-036_GEN2
Solar/Wind Harmer
3.539
3130156CHOWAN
Solar/Wind Harmer
-0.014
3151751LOISA D
Adder
8.232
315816AE2-034 GEN
Solar/Wind Harmer
1.141
971163AH1-040 GEN
Solar/Wind Harmer
13.259
3150281M RUN A
Adder
17.041
315737AD1-076 GEN
Solar/Wind Harmer
2.657
316087AB2-174 GEN
Solar/Wind Harmer
1.96
970087AG2-069 GEN
Solar/Wind Harmer
12.875
957481AF2-042 GEN
Solar/Wind Harmer
42.731
315693AD1-088 GEN
Solar/Wind Harmer
6.808
970685AG2-442 GEN
Solar/Wind Harmer
11.866
3146926FARMVIL
Solar/Wind Harmer
-0.008
971563AH1-280 GEN
Solar/Wind Harmer
1.684
208835TUHI V3-051
Solar/Wind Helper
0.029
233998TM1NIN_3.36
Solar/Wind Helper
0.254
232404W1-003 C
Solar/Wind Helper
0.628
20715828PEM_W1-120
Solar/Wind Helper
0.111
3140676OCCOQUN
50/50
0.023
972213AH1-691 GEN
50/50
3.478
944491AF1-114 GEN
Solar/Wind Harmer
5.044
3138133OCRAN
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.003
3143873LANEXA
Solar/Wind Harmer
-0.009
316382AG1-145 C
Solar/Wind Harmer
0.457
316159AE1-175 C
Solar/Wind Harmer
0.407
971281AH1-106 GEN
Solar/Wind Harmer
2.455
3143316POE
Solar/Wind Harmer
-0.059
316236AE1-162_GEN
Solar/Wind Harmer
0.446
970657AG2-426 GEN
Solar/Wind Harmer
0.931
3146486SUNBURY
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.015
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
316405AF2-144 C
Solar/Wind Harmer
0.367
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
970533AG2-339 GEN
Solar/Wind Harmer
9.574
3147346CASHSCORNER
Solar/Wind Harmer
0.218
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315733AD1-074 GEN2
Solar/Wind Harmer
2.825
970601AG2-382 GEN
Solar/Wind Harmer
6.099
946281AF1-292 GEN
Solar/Wind Harmer
0.309
970581AG2-369 GEN
Solar/Wind Harmer
7.382
3146033SCOT NK
Solar/Wind Harmer
-0.054
972205AH1-687 GEN
Adder
5.111
233915AB1-141 GEN
Solar/Wind Helper
0.621
228728W1-130C
Solar/Wind Helper
0.064
227927V4-067C
Solar/Wind Helper
0.012
219615MILLCREEK C
Solar/Wind Helper
0.031
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.181
205943AE1-185 GEN
Solar/Wind Helper
0.513
961261AF2-417 GEN
Solar/Wind Helper
0.453
212266LOR1
Solar/Wind Helper
0.302
3150411LDYSMT5
50/50
21.482
972215AH1-692 GEN
50/50
3.478
3141813NORNECK
Solar/Wind Harmer
-0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.466
3138283WHITEMARSH
Solar/Wind Harmer
0.024
316233AE1-074 FULL
Solar/Wind Harmer
0.406
971283AH1-107 GEN
Solar/Wind Harmer
2.455
3151191GRAVEL3
Adder
9.527
316164AC1-076 GEN
Solar/Wind Harmer
1.251
315833AF1-017_GEN
Solar/Wind Harmer
2.786
316018AA1-139 ULT2
Solar/Wind Harmer
1.253
3146406KITTY HAWK
Solar/Wind Harmer
0.012
315800Z1-036_GEN1
Solar/Wind Harmer
3.539
971967AH1-528 GEN
Solar/Wind Harmer
26.439
315732AD1-074 GEN1
Solar/Wind Harmer
2.825
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
316463AE2-346 GEN
Solar/Wind Harmer
0.223
3145513AHOSKIE
Solar/Wind Harmer
0.121
3145513AHOSKIE
Solar/Wind Harmer
-0.014
970085AG2-068 GEN
Solar/Wind Harmer
8.583
3137643SOCKMAN
Solar/Wind Harmer
-0.054
316426AA2-053 GEN
Solar/Wind Harmer
1.378
315652AC1-086 GEN
Solar/Wind Harmer
15.391
316174AB2-169 GEN
Solar/Wind Harmer
2.1
946301AF1-294 GEN
Solar/Wind Harmer
3.452
3144303KENBRDG
Solar/Wind Harmer
-0.011
226929AD2-058 GEN
Solar/Wind Helper
0.387
233901CHERRYDALE C
Solar/Wind Helper
0.288
20715028HAN_X4-015
Solar/Wind Helper
0.066
207445AB1-138_GEN
Solar/Wind Helper
0.12
20720628TIN_W1-124
Solar/Wind Helper
0.217
20675528CPH_W2-050
Solar/Wind Helper
0.128
20676428JCR_X2-075
Solar/Wind Helper
0.076
20675128HRM_W1-127
Solar/Wind Helper
0.032
205956AE1-196_GEN
Solar/Wind Helper
0.518
209029WAYMART-WD
Solar/Wind Helper
0.83
3150091POSSM6B
50/50
1.477
966871AG1-558 GEN
Solar/Wind Harmer
0.476
966871AG1-558 GEN
Solar/Wind Harmer
0.163
3142296MT RD221
Adder
0.444
316156AD2-030 GEN
Solar/Wind Harmer
0.414
315666AE1-190 GEN
Solar/Wind Harmer
0.468
3150671DARBY 1
Adder
9.859
316045AC1-158 PL2
Solar/Wind Harmer
4.73
316240AF1-291 C
Solar/Wind Harmer
0.454
971223AH1-071 GEN
Solar/Wind Harmer
1.871
3150991CHESPKB
Adder
1.373
3150991CHESPKB
Adder
1.34
315835AF2-110_GEN
Solar/Wind Harmer
1.826
316435W1029_GEN3
Solar/Wind Harmer
2.626
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
316313AB2-026
Solar/Wind Harmer
0.386
316006AB2-029 C
Solar/Wind Harmer
0.814
315614AA2-178 GEN
Solar/Wind Harmer
1.522
972187AH1-678 GEN
Adder
3.554
316065AD1-022 GEN
Solar/Wind Harmer
6.982
3145893MURPHYS
Solar/Wind Harmer
0.389
3145893MURPHYS
Solar/Wind Harmer
-0.025
316140AB2-099
Solar/Wind Harmer
0.093
3146776BUCKING
Solar/Wind Harmer
-0.054
3146776BUCKING
Solar/Wind Harmer
-0.004
972193AH1-681 GEN
Adder
2.737
234036AF2-325 C
Solar/Wind Helper
0.052
232436AB1-176 C
Solar/Wind Helper
0.055
233994AC2-023 GEN
Solar/Wind Helper
1.189
219912AD2-042 GEN
Solar/Wind Helper
0.177
219607WPEMNERT C
Solar/Wind Helper
0.094
219304NAMERICA C
Solar/Wind Helper
0.153
20674328GAR_V4-001
Solar/Wind Helper
0.025
3150151POSSMC1
50/50
1.989
316337AD2-073 GEN
Solar/Wind Harmer
0.438
3141726DUNNSVL
Solar/Wind Harmer
-0.064
962861AG1-135 GEN
Solar/Wind Harmer
5.989
3150851SPRUNCC
Adder
0.624
316132AB2-190 GEN1
Solar/Wind Harmer
1.514
315773AC2-141 GEN
Solar/Wind Harmer
6.178
316036AC1-147 C
Solar/Wind Harmer
0.396
316093AE2-104_GEN
Solar/Wind Harmer
4.247
316170AC1-121 GEN2
Solar/Wind Harmer
1.821
3146516WINFALL
Solar/Wind Harmer
-0.047
3146516WINFALL
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
-0.055
3145893MURPHYS
Solar/Wind Harmer
0.413
970919AG2-571 GEN
Solar/Wind Harmer
4.369
315607AA1-063A GEN
Solar/Wind Harmer
1.389
3146263WOODLND
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.014
3146776BUCKING
Solar/Wind Harmer
-0.005
233918AB1-142 GEN
Solar/Wind Helper
0.621
228729W2-030 C
Solar/Wind Helper
0.131
219686LUMSOLAR_N C
Solar/Wind Helper
0.047
219348LDSOLAR C
Solar/Wind Helper
0.134
218524CNTRALGAS1 C
Solar/Wind Helper
0.181
20671828STAW2-080
Solar/Wind Helper
0.03
217209CENTRL HS C
Solar/Wind Helper
0.009
207439AE1-081 C O1
Solar/Wind Helper
0.02
207530AG1-191 GEN
Solar/Wind Helper
0.073
211065PSPA IPP
Solar/Wind Helper
0.161
961301AF2-421 GEN
Solar/Wind Helper
0.453
963151AG1-164 GEN
Solar/Wind Helper
0.453
963711AG1-223 GEN
Solar/Wind Helper
0.073
219276PARKLANDSO C
Solar/Wind Helper
0.103
20715228NPK_W1-113
Solar/Wind Helper
0.089
20720528MAN_W1-024
Solar/Wind Helper
0.032
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.033
20676328BVR_Y1-020
Solar/Wind Helper
0.03
20674928WA_W3-044
Solar/Wind Helper
0.108
207518AF1-320_GEN
Solar/Wind Helper
1.711
3150181POSSMC2
50/50
2.006
3150181POSSMC2
50/50
1.989
3150181POSSMC2
50/50
1.989
972195AH1-682 GEN
50/50
2.809
3150341NORNECKC1
50/50
1.591
3150341NORNECKC1
50/50
1.578
315673AE1-157 GEN
Solar/Wind Harmer
12.483
972189AH1-679 GEN
Adder
2.388
316487AF1-042 GEN
Solar/Wind Harmer
2.094
3150681DARBY 2
Adder
9.87
316450AC1-158 RIC
Solar/Wind Harmer
0.394
316033AB2-134 GEN
Solar/Wind Harmer
4.819
3145506HICKORY
Solar/Wind Harmer
-0.058
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316339AD2-160 GEN
Solar/Wind Harmer
0.986
316388AE2-253 GEN
Solar/Wind Harmer
0.986
3137176SLIGO L2192
Solar/Wind Harmer
-0.058
3130086AYDLETT
Solar/Wind Harmer
-0.058
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
966001AG1-469 GEN
Solar/Wind Harmer
0.269
3151731LOISA B
Adder
8.232
313506AB2-031 GEN
Solar/Wind Harmer
1.101
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
0.113
970301AG2-198 GEN
Solar/Wind Harmer
6.78
970323AG2-213 GEN
Solar/Wind Harmer
6.721
223401AF1-299 GEN
Solar/Wind Helper
0.64
232424Y1-079 C
Solar/Wind Helper
0.144
232428Y3-058 C
Solar/Wind Helper
0.418
234015AF2-250 C
Solar/Wind Helper
0.047
230433AD2-135 GEN
Solar/Wind Helper
0.02
214067T20SOLAR
Solar/Wind Helper
0.013
207459AE1-142 C O1
Solar/Wind Helper
0.335
20675428EAM_W2-061
Solar/Wind Helper
0.018
3150101POSSM6S
50/50
2.253
3150401LDYSMT4
50/50
21.415
3141906WESTMOR
Solar/Wind Harmer
-0.007
3141873WAN 176
Solar/Wind Harmer
1.847
3141843SHACKLE
Adder
0.707
3143096IRON208
Adder
0.571
3143096IRON208
Adder
0.56
3150861SPRUNCD
Adder
0.624
316458AB2-190 GEN2
Solar/Wind Harmer
1.514
961611AG1-000B GEN
Solar/Wind Harmer
3.142
3151171GRAVELC
Adder
1.854
3147666LOUISA
Solar/Wind Harmer
-0.034
970657AG2-426 GEN
Solar/Wind Harmer
2.983
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.295
316321Z2-027
Solar/Wind Harmer
0.391
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3150301M RUN C
Adder
17.03
3156081AA2-088 GEN
Solar/Wind Harmer
4.547
970917AG2-570 GEN
Solar/Wind Harmer
34.516
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316190AA2-174 GEN
Solar/Wind Harmer
0.168
3146926FARMVIL
Solar/Wind Harmer
-0.008
208835TUHI V3-051
Solar/Wind Helper
0.029
233950AC2-186 GEN
Solar/Wind Helper
0.144
219921AF1-264
Solar/Wind Helper
0.06
219914AD2-027 C
Solar/Wind Helper
0.135
218660EHAMPSOLAR C
Solar/Wind Helper
0.039
219688LUMSOLAR_S C
Solar/Wind Helper
0.047
207454AA2-184 E
Solar/Wind Helper
0.354
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.453
208972BECR K09
Solar/Wind Helper
0.333
970257AG2-171 GEN
Solar/Wind Harmer
4.178
3150151POSSMC1
50/50
1.989
3150151POSSMC1
50/50
1.989
3150331BIRCHWDA
50/50
29.509
3150501FRIVERG
50/50
1.206
316223AC1-118
Solar/Wind Harmer
0.447
316203AE2-005 GEN
Solar/Wind Harmer
6.554
970293AG2-193 GEN
Solar/Wind Harmer
1.933
3150921YORKTN3
Adder
3.369
3144536CHRHLND
Solar/Wind Harmer
-0.002
3142956BIRDNECK
Solar/Wind Harmer
0.79
944581AF1-123 GEN
Solar/Wind Harmer
66.887
316305AF2-043 C
Solar/Wind Harmer
0.44
316320Y1-086
Solar/Wind Harmer
0.853
3146516WINFALL
Solar/Wind Harmer
-0.014
3132273ORANGE
Solar/Wind Harmer
-0.003
944011AF1-069 GEN
Solar/Wind Harmer
8.364
3150291M RUN B
Adder
16.904
315735AD1-075 GEN1
Solar/Wind Harmer
1.413
3145893MURPHYS
Solar/Wind Harmer
0.097
3145893MURPHYS
Solar/Wind Harmer
-0.014
3146263WOODLND
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.014
316011AB1-132 GEN
Solar/Wind Harmer
2.857
3146776BUCKING
Solar/Wind Harmer
-0.005
233987AB2-037 GEN
Solar/Wind Helper
2.902
232417X3-008 C
Solar/Wind Helper
0.288
233923SMA
Solar/Wind Helper
0.931
233997TMININ_4.2
Solar/Wind Helper
0.254
233935AB2-179 C
Solar/Wind Helper
1.568
959561AF2-247 GEN
Solar/Wind Helper
0.024
20715728PEM_W1-119
Solar/Wind Helper
0.111
219249CENTRALDIV C
Solar/Wind Helper
0.011
207442AE1-156 GEN
Solar/Wind Helper
0.366
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.03
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.161
3150021OMF B
50/50
0.319
3150371LDYSMT1
50/50
20.692
971781AH1-399 GEN
Solar/Wind Harmer
1.022
966881AG1-559 GEN
Solar/Wind Harmer
0.496
961951AG1-038 GEN
Solar/Wind Harmer
2.094
316473AC1-191 GEN
Solar/Wind Harmer
1.705
3142416OLDCHRC
Solar/Wind Harmer
1.573
3141766HARMONY
Solar/Wind Harmer
1.384
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.694
315813AE1-149 C
Solar/Wind Harmer
9.28
3145336SMITFLD
Solar/Wind Harmer
-0.006
316017AA1-139 ULT1
Solar/Wind Harmer
1.183
3150011OMF A
50/50
0.319
972197AH1-683 GEN
50/50
3.344
972135AH1-637 GEN
Solar/Wind Harmer
1.702
966881AG1-559 GEN
Solar/Wind Harmer
0.17
958261AF2-120 GEN
Solar/Wind Harmer
6.199
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
970053AG2-049 GEN
50/50
2.879
3150381LDYSMT2
50/50
20.559
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
316059AD1-063 C
Solar/Wind Harmer
0.351
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
3151201GRAVEL4
Adder
9.649
3151221GRAVEL6
Adder
9.638
3151211GRAVEL5
Adder
9.527
316311AC2-079 GEN
Solar/Wind Harmer
7.4
313526AB2-022
Solar/Wind Harmer
0.392
3146396TANGLEW
Solar/Wind Harmer
0.267
315651AD1-115 GEN
Solar/Wind Harmer
6.366
315814AE2-033 C
Solar/Wind Harmer
13.396
3146206CASHIE
Solar/Wind Harmer
-0.014
316318V4-068
Solar/Wind Harmer
0.347
961941AG1-037 GEN
Solar/Wind Harmer
0.104
3146043SEABORD
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.014
316486AD2-202 GEN
Solar/Wind Harmer
0.341
971845AH1-439 GEN
Solar/Wind Harmer
7.164
961791AG1-021 GEN
Solar/Wind Harmer
1.684
232432Z2-076 GEN
Solar/Wind Helper
0.083
230407AD2-065 C
Solar/Wind Helper
0.048
20720728JCB_W1-129
Solar/Wind Helper
0.066
964851AG1-348 GEN
Solar/Wind Helper
0.069
207408W3-077 C
Solar/Wind Helper
0.092
957191AF2-013 GEN
50/50
14.153
3150691DARBY 3
Adder
9.905
3150701DARBY 4
Adder
9.882
3142366NRTHEST
Adder
0.45
315976AC1-164 GENA
Solar/Wind Harmer
3.507
316169AC1-164_GENC
Solar/Wind Harmer
3.031
3142946ENON
Solar/Wind Harmer
-0.002
316294AC1-161 GEN
Solar/Wind Harmer
4.776
316083AB2-161 GEN
Solar/Wind Harmer
2.397
316349AD2-085 GEN
Solar/Wind Harmer
1.303
3146456SLIGO L269
Solar/Wind Harmer
1.73
3146386ELIZ CT
Solar/Wind Harmer
-0.015
316431W1029_GEN1
Solar/Wind Harmer
2.626
316433W1029_GEN2
Solar/Wind Harmer
2.626
315742AE1-103 GEN
Solar/Wind Harmer
3.404
3146376EDENTON
Solar/Wind Harmer
0.424
3146376EDENTON
Solar/Wind Harmer
0.424
316336AC2-165 C
Solar/Wind Harmer
8.865
970933AG2-581 GEN
Solar/Wind Harmer
13.099
316365GEN2_N
Solar/Wind Harmer
0.937
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
2.105
972223AH1-696 GEN
50/50
15.712
3141346CRANES
50/50
0.215
972219AH1-694 GEN
50/50
2.408
3150351NORNECKC2
50/50
1.515
964211AG1-282 GEN
Solar/Wind Harmer
0.482
219904AC1-010 C
Solar/Wind Helper
0.071
219906AC1-017 C
Solar/Wind Helper
0.049
20720828JCB_W4-025
Solar/Wind Helper
0.073
20714828MDF_W3-079
Solar/Wind Helper
0.15
20742028HF_AC1-207
Solar/Wind Helper
0.161
218438BLK ROCK C
Solar/Wind Helper
0.031
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.009
971777AH1-397 GEN
Solar/Wind Harmer
1.814
3142433PROV 92
Solar/Wind Harmer
-0.062
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
315975AC1-164 GENB
Solar/Wind Harmer
0.104
316447AC1-158 HLD
Solar/Wind Harmer
3.25
316192AB2-158 GEN
Solar/Wind Harmer
1.762
3145336SMITFLD
Solar/Wind Harmer
-0.059
316375AC2-012 GEN
Solar/Wind Harmer
5.094
3146456SLIGO L269
Solar/Wind Harmer
-0.015
315683AE1-153 C
Solar/Wind Harmer
13.206
3145663CRESWEL
Solar/Wind Harmer
-0.039
3150221REMNGT2
Adder
15.867
3150211REMNGT1
Adder
15.761
972201AH1-685 GEN
Adder
2.737
3146206CASHIE
Solar/Wind Harmer
-0.014
316023GEN1_S
Solar/Wind Harmer
0.937
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.86
3145683EARLEYS
Solar/Wind Harmer
-0.014
970937AG2-583 GEN
Solar/Wind Harmer
9.91
3147043LAWRENC
Adder
1.103
232426Y1-080 FULL
Solar/Wind Helper
0.048
233996TM1833_GEN
Solar/Wind Helper
0.254
219766PARADISE C
Solar/Wind Helper
0.064
20714528FRN_Y2-051
Solar/Wind Helper
0.065
219680HOPEWELLV C1
Solar/Wind Helper
0.004
218440SUMMTASSOC C
Solar/Wind Helper
0.019
217208PARK ELE C
Solar/Wind Helper
0.005
20674628WNG_W3-110
Solar/Wind Helper
0.098
205932AD2-116_GEN
Solar/Wind Helper
0.518
3141316ARNOLDS
50/50
0.022
3141426STAFORD
Solar/Wind Harmer
-0.004
316468AD1-105 GEN
Solar/Wind Harmer
1.895
3141913WHIT STONE
Solar/Wind Harmer
-0.016
957831AF2-077 GEN
Solar/Wind Harmer
0.46
971285AH1-108 GEN
Adder
1.022
315839AE2-212 C
Solar/Wind Harmer
0.451
315697AD1-025 GEN
Solar/Wind Harmer
3.019
971445AH1-216 GEN
Solar/Wind Harmer
9.181
3151081ELIZAR1
Adder
12.017
3151091ELIZAR2
Adder
11.809
316316AC1-027 C
Solar/Wind Harmer
0.451
957871AF2-081 GEN
Solar/Wind Harmer
7.331
316258AE1-075 C
Solar/Wind Harmer
0.348
970673AG2-436 GEN
Solar/Wind Harmer
31.012
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.005
970683AG2-441 GEN
Solar/Wind Harmer
9.581
970681AG2-440 GEN
Solar/Wind Harmer
6.359
316322AB2-045
Solar/Wind Harmer
0.452
316210AC1-098 GEN
Solar/Wind Harmer
2.107
970831AG2-522 GEN
Solar/Wind Harmer
6.726
233940AF2-379 C
Solar/Wind Helper
0.077
230434AG1-499 GEN
Solar/Wind Helper
0.273
219258KINSLEYDEP C
Solar/Wind Helper
0.091
20673828FLE_V3-070
Solar/Wind Helper
0.097
20676128MHD_W3-029
Solar/Wind Helper
0.108
209027LOR2_Q27
Solar/Wind Helper
1.037
3146456SLIGO L269
Solar/Wind Harmer
-0.015
971153AH1-033 GEN
Solar/Wind Harmer
1.695
3145273HOLLAND
Solar/Wind Harmer
-0.011
3146376EDENTON
Solar/Wind Harmer
-0.014
3150241REMNGT4
Adder
15.972
972199AH1-684 GEN
Adder
2.422
3146206CASHIE
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.913
3147043LAWRENC
Solar/Wind Harmer
-0.008
959311AF2-222 GEN
Solar/Wind Harmer
14.147
3147133PAMPLIN
Solar/Wind Harmer
-0.042
316478AD1-087 GEN
Solar/Wind Harmer
1.165
972255AH1-712 GEN
Adder
61.265
227287AC2-120 GEN
Solar/Wind Helper
1.23
233964AF2-378 GEN
Solar/Wind Helper
0.052
232422X3-066 FULL
Solar/Wind Helper
0.141
232406W1-004 FULL
Solar/Wind Helper
0.628
232434Z2-077 GEN
Solar/Wind Helper
0.157
230415AB2-049 C
Solar/Wind Helper
0.036
219291REEVESSOUT C
Solar/Wind Helper
0.014
219236SOUTHERNHQ C
Solar/Wind Helper
0.006
20714928UPF_X1-085
Solar/Wind Helper
0.006
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.538
316314AB2-024 C
Solar/Wind Harmer
1.329
944631AF1-128 GEN
Adder
64.814
971317AH1-138 GEN
Solar/Wind Harmer
1.895
3143526WINTERP
Solar/Wind Harmer
-0.078
315671AE2-027_GEN
Solar/Wind Harmer
2.72
316072AD1-144
Solar/Wind Harmer
0.297
944591AF1-124 GEN
Solar/Wind Harmer
67.128
939411AE1-173 GEN
Solar/Wind Harmer
72.752
940641AE2-051 GEN
Solar/Wind Harmer
13.596
3143336POWHATN
Solar/Wind Harmer
1.704
941031AE2-094 GEN
Solar/Wind Harmer
26.693
971685AH1-345 GEN
Solar/Wind Harmer
1.242
971547AH1-271 GEN
Solar/Wind Harmer
3.485
960081AF2-299 GEN
Solar/Wind Harmer
1.554
3145823KELFORD
Solar/Wind Harmer
-0.014
3145783HORNRTN
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.045
3145796HORNRTN
Solar/Wind Harmer
-0.014
316034AC1-036 C
Solar/Wind Harmer
0.251
3144293JTRSVLE
Adder
0.286
3144293JTRSVLE
Adder
0.226
972277AH1-723 GEN
Adder
71.392
232408W1-005 C
Solar/Wind Helper
0.628
233944AB2-135 GEN
Solar/Wind Helper
0.729
219907AC1-030 C
Solar/Wind Helper
0.04
20716028EGP_W2-019
Solar/Wind Helper
0.022
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.083
20673628F1S_V4-069
Solar/Wind Helper
0.033
20676228FRD_X1-012
Solar/Wind Helper
0.101
20675828AU_W4-064
Solar/Wind Helper
0.032
207484AF2-139 C O1
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.089
3150071POSSM 5
50/50
90.91
3150391LDYSMT3
50/50
21.375
316312AB1-027
Solar/Wind Harmer
0.524
316441AF1-014 GEN
Solar/Wind Harmer
1.048
944641AF1-129 GEN
Adder
64.126
3143526WINTERP
Solar/Wind Harmer
-0.078
316185AD1-033 GEN
Solar/Wind Harmer
1.548
3144356SAPONY
Solar/Wind Harmer
0.503
316315AB2-025 C
Solar/Wind Harmer
0.388
972185AH1-677 GEN
Adder
7.036
962571AG1-106 GEN
Solar/Wind Harmer
1.967
970099AG2-077 GEN
Solar/Wind Harmer
17.092
3145783HORNRTN
Solar/Wind Harmer
1.616
3145783HORNRTN
Solar/Wind Harmer
1.293
3145783HORNRTN
Solar/Wind Harmer
0.404
3145783HORNRTN
Solar/Wind Harmer
0.162
3145796HORNRTN
Solar/Wind Harmer
-0.041
3144293JTRSVLE
Adder
0.286
223402AF1-300 C
Solar/Wind Helper
0.64
233946AB2-136 GEN
Solar/Wind Helper
0.704
233930AB2-032 GEN
Solar/Wind Helper
0.471
233982AB2-133 GEN
Solar/Wind Helper
0.444
232410W1-006 C
Solar/Wind Helper
0.628
233952AC2-187 GEN
Solar/Wind Helper
0.287
233954AC2-188 GEN
Solar/Wind Helper
0.287
230511AF1-262
Solar/Wind Helper
0.017
228754AB1-001 C
Solar/Wind Helper
0.031
219272CLEANLIGHT C
Solar/Wind Helper
0.03
217081WEATEXAS C
Solar/Wind Helper
0.014
207471AF2-354 C
Solar/Wind Helper
0.184
20675928HOL_W4-097
Solar/Wind Helper
0.055
3150081POSSM6A
50/50
1.477
3150351NORNECKC2
50/50
1.54
316077AC2-138 C
Solar/Wind Harmer
0.339
316484AD2-074 GEN
Solar/Wind Harmer
4.002
316075AC2-137 C
Solar/Wind Harmer
0.416
3144216WINCHST
Adder
0.505
315778AD1-151 GEN
Solar/Wind Harmer
13.337
3151101ELIZAR3
Adder
12.171
944601AF1-125 GEN
Solar/Wind Harmer
65.843
3143336POWHATN
Solar/Wind Harmer
1.448
3151761LOISA E
Adder
16.784
3151721LOISA A
Adder
8.19
3141196NOKESVL
Solar/Wind Harmer
-0.056
972217AH1-693 GEN
Adder
2.106
966621AG1-532 GEN
Solar/Wind Harmer
0.28
316317KELFORD C
Solar/Wind Harmer
0.633
3145823KELFORD
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.014
964241AG1-285 GEN
Solar/Wind Harmer
10.566
942461AE2-259 GEN
Solar/Wind Harmer
2.033
3144293JTRSVLE
Adder
0.286
316212AC1-099_GEN
Solar/Wind Harmer
1.171
972003AH1-546 GEN
Solar/Wind Harmer
5.462
226910AB2-157 C
Solar/Wind Helper
0.048
233933AB2-153 GEN
Solar/Wind Helper
0.288
219623KINSLEYBEA C
Solar/Wind Helper
0.003
219612MATRIX C
Solar/Wind Helper
0.027
20716928W4-060COL
Solar/Wind Helper
0.059
217213AMBOY SO C
Solar/Wind Helper
0.032
20673728F2S_V4-070
Solar/Wind Helper
0.033
207510AF2-138 C
Solar/Wind Helper
0.089
207437AD2-070 GEN
Solar/Wind Helper
0.15
20671928W4-073
Solar/Wind Helper
0.098
209116AE2-175 GEN
Solar/Wind Helper
1.904
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.227
CPLELTFEXP_CPLE->PJM
CLTF
8.755
SIGELTFEXP_SIGE->PJM
CLTF
0.26
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.842
LGEELTFEXP_LGEE->PJM
CLTF
3.372
MECLTFEXP_MEC->PJM
CLTF
8.244
AH1-155LTFEXP_AH1-155->PJM
LTF
0.159
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.22
NYPJM->LTFIMP_NY
CLTF
4.847
TVALTFEXP_TVA->PJM
CLTF
5.861
AG2-052LTFEXP_AG2-052->PJM
LTF
0.106
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.364
WECLTFEXP_WEC->PJM
CLTF
1.787
LAGNLTFEXP_LAGN->PJM
CLTF
11.594
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019F_SRT-SL_SENS'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1          /*BRIGHTON     500.0 - 01DOUBS      500.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 2          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 4          /*01DOUBS      500.0 - 01DOUBS      230.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 1                  /*01DOUBS      500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 237804 CKT 1 /*01DOUBS      500.0 - 01ROCKYPOINT 500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 237804 CKT 2 /*01DOUBS      500.0 - 01ROCKYPOINT 500.0
END
CONTINGENCY 'PEPCO_P4_PP41_SRT-A'
 OPEN BRANCH FROM BUS 200003 TO BUS 224058 CKT 1   /*BRIGHTON     500.0 - BRG 3T 230   230.0
 OPEN BRANCH FROM BUS 200003 TO BUS 235105 CKT 1   /*BRIGHTON     500.0 - 01DOUBS      500.0
END
314922 to 200019 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: H2T560_SRT-A
BreakerAC137.48 %1417.0B1948.14
1.9
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: H1T560_SRT-A
BreakerAC137.48 %1417.0B1948.07
1.9
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: 560T571_SRT-S
BreakerAC136.59 %1417.0B1935.43
1.9
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC132.6 %1417.0B1878.9
1.67
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC131.8 %1331.98B1755.6
2.02
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC121.4 %1417.0B1720.2
1.92
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC121.88 %1478.62B1802.21
2.02
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: H2T560_SRT-A
BreakerAC110.27 %1809.0C1994.82
1.9
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: H1T560_SRT-A
BreakerAC110.27 %1809.0C1994.74
1.9
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: 560T571_SRT-S
BreakerAC109.57 %1809.0C1982.11
1.9
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC106.46 %1809.0C1925.78
1.67
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC102.14 %3099.0B3165.31
2.38

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T560_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.48 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1948.14
MW Contribution:
1.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150221REMNGT2
Adder
12.445
3150211REMNGT1
Adder
12.362
972201AH1-685 GEN
Adder
2.147
316447AC1-158 HLD
Solar/Wind Harmer
2.285
972197AH1-683 GEN
Adder
1.979
972135AH1-637 GEN
Solar/Wind Harmer
1.029
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
9.488
316192AB2-158 GEN
Solar/Wind Harmer
1.18
958261AF2-120 GEN
Solar/Wind Harmer
3.763
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
316415AF1-147_GEN2
Solar/Wind Harmer
1.097
972223AH1-696 GEN
Adder
8.557
3141346CRANES
Adder
0.12
971685AH1-345 GEN
Solar/Wind Harmer
0.96
972219AH1-694 GEN
Adder
1.425
3150351NORNECKC2
Adder
0.869
964211AG1-282 GEN
Solar/Wind Harmer
0.294
316314AB2-024 C
Solar/Wind Harmer
0.812
3143526WINTERP
Solar/Wind Harmer
-0.049
944631AF1-128 GEN
Adder
39.787
971317AH1-138 GEN
Solar/Wind Harmer
1.161
315671AE2-027_GEN
Solar/Wind Harmer
1.668
944591AF1-124 GEN
Solar/Wind Harmer
41.27
316072AD1-144
Solar/Wind Harmer
0.182
939411AE1-173 GEN
Solar/Wind Harmer
44.9
940641AE2-051 GEN
Solar/Wind Harmer
8.405
3143336POWHATN
Solar/Wind Harmer
1.057
315747AE2-019 GEN
50/50
13.164
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.652
316077AC2-138 C
Solar/Wind Harmer
0.206
3150181POSSMC2
Adder
1.092
3150181POSSMC2
Adder
1.083
3150181POSSMC2
Adder
1.083
316450AC1-158 RIC
Solar/Wind Harmer
0.277
972195AH1-682 GEN
Adder
1.662
315673AE1-157 GEN
Solar/Wind Harmer
7.788
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3151731LOISA B
Adder
5.589
316487AF1-042 GEN
Solar/Wind Harmer
1.273
3150681DARBY 2
Adder
6.038
316033AB2-134 GEN
Solar/Wind Harmer
2.966
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.605
316388AE2-253 GEN
Solar/Wind Harmer
0.605
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
0.664
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.712
972215AH1-692 GEN
Adder
2.058
316164AC1-076 GEN
Solar/Wind Harmer
0.884
3141813NORNECK
Solar/Wind Harmer
-0.01
957601AF2-054 GEN
Solar/Wind Harmer
0.284
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971283AH1-107 GEN
Solar/Wind Harmer
1.526
3138283WHITEMARSH
Solar/Wind Harmer
0.014
3151191GRAVEL3
Adder
5.855
315833AF1-017_GEN
Solar/Wind Harmer
1.708
316018AA1-139 ULT2
Solar/Wind Harmer
0.768
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315800Z1-036_GEN1
Solar/Wind Harmer
2.158
971967AH1-528 GEN
Solar/Wind Harmer
16.231
315732AD1-074 GEN1
Solar/Wind Harmer
1.714
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.23
316463AE2-346 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.278
316426AA2-053 GEN
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
1.265
946301AF1-294 GEN
Solar/Wind Harmer
2.073
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205956AE1-196_GEN
Solar/Wind Helper
0.386
233901CHERRYDALE C
Solar/Wind Helper
0.14
20715028HAN_X4-015
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
20676428JCR_X2-075
Solar/Wind Helper
0.039
20675128HRM_W1-127
Solar/Wind Helper
0.017
209029WAYMART-WD
Solar/Wind Helper
0.444
959421AF2-233 GEN
Solar/Wind Helper
0.233
3152111X4-039 GT1
50/50
1.844
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3150151POSSMC1
Adder
1.083
3150151POSSMC1
Adder
1.083
3150291M RUN B
Adder
13.227
3150331BIRCHWDA
Adder
16.668
316223AC1-118
Solar/Wind Harmer
0.271
3132273ORANGE
Solar/Wind Harmer
-0.002
316203AE2-005 GEN
Solar/Wind Harmer
4.002
970293AG2-193 GEN
Solar/Wind Harmer
1.182
3150921YORKTN3
Adder
2.065
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
41.122
3142956BIRDNECK
Solar/Wind Harmer
0.485
316305AF2-043 C
Solar/Wind Harmer
0.27
316320Y1-086
Solar/Wind Harmer
0.522
3146516WINFALL
Solar/Wind Harmer
-0.009
944011AF1-069 GEN
Solar/Wind Harmer
5.155
315735AD1-075 GEN1
Solar/Wind Harmer
0.857
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.722
3146776BUCKING
Solar/Wind Harmer
-0.003
3151861LOWMORA
Adder
0.643
237038AE2-054 C
Solar/Wind Helper
0.174
233935AB2-179 C
Solar/Wind Helper
0.775
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
207442AE1-156 GEN
Solar/Wind Helper
0.189
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
3150301M RUN C
Adder
13.326
3150401LDYSMT4
Adder
12.673
3141906WESTMOR
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.023
3141873WAN 176
Solar/Wind Harmer
1.127
3150281M RUN A
Adder
13.334
316044AC1-158 PL1
Solar/Wind Harmer
1.039
316254AC1-120 GEN1
Solar/Wind Harmer
3.939
957971AF2-091 GEN
Solar/Wind Harmer
1.036
3147666LOUISA
Solar/Wind Harmer
-0.04
316404AE1-155 C
Solar/Wind Harmer
1.854
3151751LOISA D
Adder
5.589
3138133OCRAN
Solar/Wind Harmer
-0.006
315662AE1-191 GEN
Solar/Wind Harmer
1.142
316280AD1-041 GEN
Solar/Wind Harmer
0.714
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.46
316369SG1_INVT
Solar/Wind Harmer
1.642
961611AG1-000B GEN
Solar/Wind Harmer
4.528
3151171GRAVELC
Adder
0.867
316381AD1-082 GEN
Solar/Wind Harmer
0.829
3150981CHESPKA
Adder
1.005
319010AE1-072 C
Solar/Wind Harmer
1.811
315611Z1-036_GEN2
Solar/Wind Harmer
2.158
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.694
971163AH1-040 GEN
Solar/Wind Harmer
8.061
315737AD1-076 GEN
Solar/Wind Harmer
1.612
3141426STAFORD
Solar/Wind Harmer
-0.003
316468AD1-105 GEN
Solar/Wind Harmer
1.148
3141913WHIT STONE
Solar/Wind Harmer
-0.01
971285AH1-108 GEN
Adder
0.63
957831AF2-077 GEN
Solar/Wind Harmer
0.281
315697AD1-025 GEN
Solar/Wind Harmer
1.859
315839AE2-212 C
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
5.641
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.277
941031AE2-094 GEN
Solar/Wind Harmer
16.452
971547AH1-271 GEN
Solar/Wind Harmer
2.111
970087AG2-069 GEN
Solar/Wind Harmer
7.846
957481AF2-042 GEN
Solar/Wind Harmer
25.978
316087AB2-174 GEN
Solar/Wind Harmer
1.182
315693AD1-088 GEN
Solar/Wind Harmer
4.141
3146926FARMVIL
Solar/Wind Harmer
-0.005
971563AH1-280 GEN
Solar/Wind Harmer
1.011
970685AG2-442 GEN
Solar/Wind Harmer
7.066
3146293MARTNCO
Solar/Wind Harmer
0.05
208835TUHI V3-051
Solar/Wind Helper
0.017
23777901MDS_W4-102
Solar/Wind Helper
0.106
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
219919AE1-041 FULL
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
20674928WA_W3-044
Solar/Wind Helper
0.057
20676328BVR_Y1-020
Solar/Wind Helper
0.015
207518AF1-320_GEN
Solar/Wind Helper
0.902
209137AF2-361 C
Solar/Wind Helper
0.711
957921AF2-086 GEN
Solar/Wind Helper
0.234
970221AG2-151 GEN
Solar/Wind Harmer
1.345
3150151POSSMC1
Adder
1.083
316170AC1-121 GEN2
Solar/Wind Harmer
1.313
316337AD2-073 GEN
Solar/Wind Harmer
0.266
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.636
3150851SPRUNCC
Adder
0.385
316132AB2-190 GEN1
Solar/Wind Harmer
0.932
315773AC2-141 GEN
Solar/Wind Harmer
3.799
316036AC1-147 C
Solar/Wind Harmer
0.243
316093AE2-104_GEN
Solar/Wind Harmer
2.602
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.25
316006AB2-029 C
Solar/Wind Harmer
0.629
316045AC1-158 PL2
Solar/Wind Harmer
3.324
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316156AD2-030 GEN
Solar/Wind Harmer
0.253
315666AE1-190 GEN
Solar/Wind Harmer
0.285
3150671DARBY 1
Adder
6.031
971223AH1-071 GEN
Solar/Wind Harmer
1.17
316240AF1-291 C
Solar/Wind Harmer
0.278
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
315835AF2-110_GEN
Solar/Wind Harmer
1.119
316313AB2-026
Solar/Wind Harmer
0.24
316435W1029_GEN3
Solar/Wind Harmer
1.606
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.925
316065AD1-022 GEN
Solar/Wind Harmer
4.231
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
-0.015
316140AB2-099
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
972193AH1-681 GEN
Adder
1.639
232436AB1-176 C
Solar/Wind Helper
0.027
234036AF2-325 C
Solar/Wind Helper
0.025
233994AC2-023 GEN
Solar/Wind Helper
0.579
219912AD2-042 GEN
Solar/Wind Helper
0.089
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
20674328GAR_V4-001
Solar/Wind Helper
0.013
946751AF1-339 GEN
Solar/Wind Helper
0.234
963691AG1-221 GEN
Solar/Wind Harmer
2.31
3150241REMNGT4
Adder
12.527
972199AH1-684 GEN
Adder
1.899
3150371LDYSMT1
Adder
12.245
966881AG1-559 GEN
Solar/Wind Harmer
0.308
971781AH1-399 GEN
Solar/Wind Harmer
0.619
961951AG1-038 GEN
Solar/Wind Harmer
1.273
316473AC1-191 GEN
Solar/Wind Harmer
1.038
3142416OLDCHRC
Solar/Wind Harmer
0.959
3141766HARMONY
Solar/Wind Harmer
0.845
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
1.044
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.697
316017AA1-139 ULT1
Solar/Wind Harmer
0.725
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.039
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.154
3147043LAWRENC
Solar/Wind Harmer
-0.005
316478AD1-087 GEN
Solar/Wind Harmer
0.704
3147133PAMPLIN
Solar/Wind Harmer
-0.025
972255AH1-712 GEN
Adder
36.692
959311AF2-222 GEN
Solar/Wind Harmer
8.394
3150351NORNECKC2
Adder
0.884
3151761LOISA E
Adder
11.393
3151721LOISA A
Adder
5.56
316484AD2-074 GEN
Solar/Wind Harmer
2.432
316075AC2-137 C
Solar/Wind Harmer
0.254
315778AD1-151 GEN
Solar/Wind Harmer
8.21
3144216WINCHST
Adder
0.309
3151101ELIZAR3
Adder
7.475
944601AF1-125 GEN
Solar/Wind Harmer
40.48
3143336POWHATN
Solar/Wind Harmer
0.898
966621AG1-532 GEN
Solar/Wind Harmer
0.169
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
972003AH1-546 GEN
Solar/Wind Harmer
3.341
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.227
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.702
226910AB2-157 C
Solar/Wind Helper
0.021
237085AD2-009_GEN
Solar/Wind Helper
0.975
233933AB2-153 GEN
Solar/Wind Helper
0.141
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
209116AE2-175 GEN
Solar/Wind Helper
1.008
972213AH1-691 GEN
Adder
2.058
944491AF1-114 GEN
Solar/Wind Harmer
3.046
3138133OCRAN
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3141873WAN 176
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.526
316382AG1-145 C
Solar/Wind Harmer
0.28
316159AE1-175 C
Solar/Wind Harmer
0.249
316236AE1-162_GEN
Solar/Wind Harmer
0.274
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.571
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316405AF2-144 C
Solar/Wind Harmer
0.228
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
970533AG2-339 GEN
Solar/Wind Harmer
5.901
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.714
970601AG2-382 GEN
Solar/Wind Harmer
3.694
970581AG2-369 GEN
Solar/Wind Harmer
4.498
946281AF1-292 GEN
Solar/Wind Harmer
0.187
972205AH1-687 GEN
Adder
3.127
3146033SCOT NK
Solar/Wind Harmer
-0.032
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
205943AE1-185 GEN
Solar/Wind Helper
0.388
233915AB1-141 GEN
Solar/Wind Helper
0.305
228728W1-130C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
961261AF2-417 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.163
959431AF2-234 GEN
Solar/Wind Helper
0.467
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316458AB2-190 GEN2
Solar/Wind Harmer
0.932
961611AG1-000B GEN
Solar/Wind Harmer
1.932
3151171GRAVELC
Adder
1.14
970657AG2-426 GEN
Solar/Wind Harmer
1.83
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.181
316321Z2-027
Solar/Wind Harmer
0.239
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.758
970917AG2-570 GEN
Solar/Wind Harmer
21.069
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.101
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.008
970257AG2-171 GEN
Solar/Wind Harmer
3.013
971775AH1-396 GEN
Solar/Wind Harmer
0.567
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
235067AD1-061 GEN
Solar/Wind Helper
0.282
233950AC2-186 GEN
Solar/Wind Helper
0.07
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
207454AA2-184 E
Solar/Wind Helper
0.181
217169METRODIV C
Solar/Wind Helper
0.002
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
209071AE2-133 GEN
Solar/Wind Helper
0.042
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.124
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
970919AG2-571 GEN
Solar/Wind Harmer
2.667
315607AA1-063A GEN
Solar/Wind Harmer
0.839
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.003
237001AB1-127_GEN
Solar/Wind Helper
0.308
233918AB1-142 GEN
Solar/Wind Helper
0.305
228729W2-030 C
Solar/Wind Helper
0.065
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
207530AG1-191 GEN
Solar/Wind Helper
0.038
207439AE1-081 C O1
Solar/Wind Helper
0.011
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
970323AG2-213 GEN
Solar/Wind Harmer
4.017
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
235062AE1-101 C1
Solar/Wind Helper
1.069
232424Y1-079 C
Solar/Wind Helper
0.07
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
230433AD2-135 GEN
Solar/Wind Helper
0.01
214067T20SOLAR
Solar/Wind Helper
0.007
207459AE1-142 C O1
Solar/Wind Helper
0.17
20675428EAM_W2-061
Solar/Wind Helper
0.009
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
971777AH1-397 GEN
Solar/Wind Harmer
1.108
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3145336SMITFLD
Solar/Wind Harmer
-0.036
316375AC2-012 GEN
Solar/Wind Harmer
3.128
3146456SLIGO L269
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.097
3146206CASHIE
Solar/Wind Harmer
-0.008
316023GEN1_S
Solar/Wind Harmer
0.568
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
315976AC1-164 GENA
Solar/Wind Harmer
2.145
316169AC1-164_GENC
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
-0.001
316294AC1-161 GEN
Solar/Wind Harmer
2.936
316083AB2-161 GEN
Solar/Wind Harmer
1.471
316349AD2-085 GEN
Solar/Wind Harmer
0.799
3146456SLIGO L269
Solar/Wind Harmer
1.06
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.606
316433W1029_GEN2
Solar/Wind Harmer
1.606
316336AC2-165 C
Solar/Wind Harmer
5.487
315742AE1-103 GEN
Solar/Wind Harmer
2.076
3146376EDENTON
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.258
970933AG2-581 GEN
Solar/Wind Harmer
8.024
316365GEN2_N
Solar/Wind Harmer
0.568
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.264
237080AD1-060 GEN
Solar/Wind Helper
0.222
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674828DL_W4-046
Solar/Wind Helper
0.005
970053AG2-049 GEN
50/50
2.025
3150381LDYSMT2
Adder
12.166
315651AD1-115 GEN
Solar/Wind Harmer
4.651
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.214
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151211GRAVEL5
Adder
5.855
316311AC2-079 GEN
Solar/Wind Harmer
4.537
313526AB2-022
Solar/Wind Harmer
0.24
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.19
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.21
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
971845AH1-439 GEN
Solar/Wind Harmer
4.369
316486AD2-202 GEN
Solar/Wind Harmer
0.206
961791AG1-021 GEN
Solar/Wind Harmer
1.011
316274AC1-208 GEN
Solar/Wind Harmer
0.865
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
959381AF2-229 GEN
Solar/Wind Helper
0.257
232432Z2-076 GEN
Solar/Wind Helper
0.04
230407AD2-065 C
Solar/Wind Helper
0.024
20720728JCB_W1-129
Solar/Wind Helper
0.034
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232406W1-004 FULL
Solar/Wind Helper
0.305
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.125
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.662
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
203975AE1-071-GEN
Solar/Wind Helper
1.719
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
219766PARADISE C
Solar/Wind Helper
0.032
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
218440SUMMTASSOC C
Solar/Wind Helper
0.01
217208PARK ELE C
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.051
961421AF2-433 GEN
Solar/Wind Helper
0.237
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
960081AF2-299 GEN
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
972277AH1-723 GEN
Adder
42.757
316129AC1-054 GEN
Solar/Wind Harmer
0.703
316034AC1-036 C
Solar/Wind Harmer
0.149
205916AD1-020 GEN
Solar/Wind Helper
1.485
233944AB2-135 GEN
Solar/Wind Helper
0.357
232408W1-005 C
Solar/Wind Helper
0.305
219907AC1-030 C
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.011
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
219908AB1-139 C
Solar/Wind Helper
0.043
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.047
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.234
957871AF2-081 GEN
Solar/Wind Harmer
4.495
316258AE1-075 C
Solar/Wind Harmer
0.216
970673AG2-436 GEN
Solar/Wind Harmer
19.089
316322AB2-045
Solar/Wind Harmer
0.276
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.264
970683AG2-441 GEN
Solar/Wind Harmer
5.694
970681AG2-440 GEN
Solar/Wind Harmer
3.78
970831AG2-522 GEN
Solar/Wind Harmer
4.03
20390526W1-045 C
Solar/Wind Helper
0.253
233940AF2-379 C
Solar/Wind Helper
0.037
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
20673828FLE_V3-070
Solar/Wind Helper
0.05
20676128MHD_W3-029
Solar/Wind Helper
0.056
209027LOR2_Q27
Solar/Wind Helper
0.559
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
316411AF1-147_GEN1
Solar/Wind Harmer
1.097
3150071POSSM 5
Adder
49.515
3150391LDYSMT3
Adder
12.649
316312AB1-027
Solar/Wind Harmer
0.32
316441AF1-014 GEN
Solar/Wind Harmer
0.64
3143526WINTERP
Solar/Wind Harmer
-0.049
944641AF1-129 GEN
Adder
39.347
316185AD1-033 GEN
Solar/Wind Harmer
0.95
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.237
972185AH1-677 GEN
Adder
4.322
970099AG2-077 GEN
Solar/Wind Harmer
10.391
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.778
3145783HORNRTN
Solar/Wind Harmer
0.243
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3144293JTRSVLE
Adder
0.172
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
233946AB2-136 GEN
Solar/Wind Helper
0.343
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
961431AF2-434 GEN
Solar/Wind Helper
0.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.815
LGEELTFEXP_LGEE->PJM
CLTF
1.797
MECLTFEXP_MEC->PJM
CLTF
4.43
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.53
CPLELTFEXP_CPLE->PJM
CLTF
5.052
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.55
WECLTFEXP_WEC->PJM
CLTF
0.958
LAGNLTFEXP_LAGN->PJM
CLTF
6.302
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.322
NYPJM->LTFIMP_NY
CLTF
2.582
TVALTFEXP_TVA->PJM
CLTF
3.176

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T560_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.48 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1948.07
MW Contribution:
1.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150181POSSMC2
Adder
1.093
3150181POSSMC2
Adder
1.084
3150181POSSMC2
Adder
1.084
972195AH1-682 GEN
Adder
1.662
316450AC1-158 RIC
Solar/Wind Harmer
0.277
315673AE1-157 GEN
Solar/Wind Harmer
7.788
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3151731LOISA B
Adder
5.588
316487AF1-042 GEN
Solar/Wind Harmer
1.273
3150681DARBY 2
Adder
6.038
316033AB2-134 GEN
Solar/Wind Harmer
2.966
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.605
316388AE2-253 GEN
Solar/Wind Harmer
0.605
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
0.664
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.124
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
970323AG2-213 GEN
Solar/Wind Harmer
4.017
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
235062AE1-101 C1
Solar/Wind Helper
1.069
232424Y1-079 C
Solar/Wind Helper
0.07
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
230433AD2-135 GEN
Solar/Wind Helper
0.01
972213AH1-691 GEN
Adder
2.058
944491AF1-114 GEN
Solar/Wind Harmer
3.046
3138133OCRAN
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3141873WAN 176
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.526
316382AG1-145 C
Solar/Wind Harmer
0.28
316159AE1-175 C
Solar/Wind Harmer
0.249
316236AE1-162_GEN
Solar/Wind Harmer
0.274
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.571
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316405AF2-144 C
Solar/Wind Harmer
0.228
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
970533AG2-339 GEN
Solar/Wind Harmer
5.901
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.714
970601AG2-382 GEN
Solar/Wind Harmer
3.694
970581AG2-369 GEN
Solar/Wind Harmer
4.498
946281AF1-292 GEN
Solar/Wind Harmer
0.187
972205AH1-687 GEN
Adder
3.127
3146033SCOT NK
Solar/Wind Harmer
-0.032
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
205943AE1-185 GEN
Solar/Wind Helper
0.388
233915AB1-141 GEN
Solar/Wind Helper
0.305
228728W1-130C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
3150301M RUN C
Adder
13.326
3150401LDYSMT4
Adder
12.674
3141906WESTMOR
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.023
3141873WAN 176
Solar/Wind Harmer
1.127
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316458AB2-190 GEN2
Solar/Wind Harmer
0.932
961611AG1-000B GEN
Solar/Wind Harmer
1.932
3151171GRAVELC
Adder
1.14
970657AG2-426 GEN
Solar/Wind Harmer
1.83
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.181
316321Z2-027
Solar/Wind Harmer
0.239
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.758
970917AG2-570 GEN
Solar/Wind Harmer
21.069
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.101
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.008
970257AG2-171 GEN
Solar/Wind Harmer
3.013
971775AH1-396 GEN
Solar/Wind Harmer
0.567
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
315976AC1-164 GENA
Solar/Wind Harmer
2.145
316169AC1-164_GENC
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
-0.001
316294AC1-161 GEN
Solar/Wind Harmer
2.936
316083AB2-161 GEN
Solar/Wind Harmer
1.471
316349AD2-085 GEN
Solar/Wind Harmer
0.799
3146456SLIGO L269
Solar/Wind Harmer
1.06
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.606
316433W1029_GEN2
Solar/Wind Harmer
1.606
316336AC2-165 C
Solar/Wind Harmer
5.487
315742AE1-103 GEN
Solar/Wind Harmer
2.076
3146376EDENTON
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.258
970933AG2-581 GEN
Solar/Wind Harmer
8.024
316365GEN2_N
Solar/Wind Harmer
0.568
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.264
237080AD1-060 GEN
Solar/Wind Helper
0.222
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674828DL_W4-046
Solar/Wind Helper
0.005
963691AG1-221 GEN
Solar/Wind Harmer
2.31
3150241REMNGT4
Adder
12.527
972199AH1-684 GEN
Adder
1.899
3150371LDYSMT1
Adder
12.247
966881AG1-559 GEN
Solar/Wind Harmer
0.308
971781AH1-399 GEN
Solar/Wind Harmer
0.619
961951AG1-038 GEN
Solar/Wind Harmer
1.273
316473AC1-191 GEN
Solar/Wind Harmer
1.038
3142416OLDCHRC
Solar/Wind Harmer
0.959
3141766HARMONY
Solar/Wind Harmer
0.845
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
1.044
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.697
316017AA1-139 ULT1
Solar/Wind Harmer
0.725
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.039
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.154
3147043LAWRENC
Solar/Wind Harmer
-0.005
316478AD1-087 GEN
Solar/Wind Harmer
0.704
3147133PAMPLIN
Solar/Wind Harmer
-0.025
972255AH1-712 GEN
Adder
36.691
959311AF2-222 GEN
Solar/Wind Harmer
8.394
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232406W1-004 FULL
Solar/Wind Helper
0.305
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
970053AG2-049 GEN
50/50
2.025
3150381LDYSMT2
Adder
12.168
315651AD1-115 GEN
Solar/Wind Harmer
4.651
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.214
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151211GRAVEL5
Adder
5.855
316311AC2-079 GEN
Solar/Wind Harmer
4.537
313526AB2-022
Solar/Wind Harmer
0.24
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.19
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.21
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
971845AH1-439 GEN
Solar/Wind Harmer
4.369
316486AD2-202 GEN
Solar/Wind Harmer
0.206
961791AG1-021 GEN
Solar/Wind Harmer
1.011
316274AC1-208 GEN
Solar/Wind Harmer
0.865
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
959381AF2-229 GEN
Solar/Wind Helper
0.257
232432Z2-076 GEN
Solar/Wind Helper
0.04
230407AD2-065 C
Solar/Wind Helper
0.024
20720728JCB_W1-129
Solar/Wind Helper
0.034
3150221REMNGT2
Adder
12.445
3150211REMNGT1
Adder
12.362
972201AH1-685 GEN
Adder
2.147
972197AH1-683 GEN
Adder
1.979
316447AC1-158 HLD
Solar/Wind Harmer
2.285
972135AH1-637 GEN
Solar/Wind Harmer
1.029
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
9.487
316192AB2-158 GEN
Solar/Wind Harmer
1.18
958261AF2-120 GEN
Solar/Wind Harmer
3.763
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.108
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3145336SMITFLD
Solar/Wind Harmer
-0.036
316375AC2-012 GEN
Solar/Wind Harmer
3.128
3146456SLIGO L269
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.097
3146206CASHIE
Solar/Wind Harmer
-0.008
316023GEN1_S
Solar/Wind Harmer
0.568
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.125
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.662
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
203975AE1-071-GEN
Solar/Wind Helper
1.719
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
219766PARADISE C
Solar/Wind Helper
0.032
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
218440SUMMTASSOC C
Solar/Wind Helper
0.01
217208PARK ELE C
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.051
316006AB2-029 C
Solar/Wind Harmer
0.629
316045AC1-158 PL2
Solar/Wind Harmer
3.324
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316156AD2-030 GEN
Solar/Wind Harmer
0.253
315666AE1-190 GEN
Solar/Wind Harmer
0.285
3150671DARBY 1
Adder
6.031
971223AH1-071 GEN
Solar/Wind Harmer
1.17
316240AF1-291 C
Solar/Wind Harmer
0.278
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
315835AF2-110_GEN
Solar/Wind Harmer
1.119
316313AB2-026
Solar/Wind Harmer
0.24
316435W1029_GEN3
Solar/Wind Harmer
1.606
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.925
316065AD1-022 GEN
Solar/Wind Harmer
4.231
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
-0.015
316140AB2-099
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
972193AH1-681 GEN
Adder
1.639
232436AB1-176 C
Solar/Wind Helper
0.027
234036AF2-325 C
Solar/Wind Helper
0.025
233994AC2-023 GEN
Solar/Wind Helper
0.579
219912AD2-042 GEN
Solar/Wind Helper
0.089
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.714
972215AH1-692 GEN
Adder
2.058
316164AC1-076 GEN
Solar/Wind Harmer
0.884
3141813NORNECK
Solar/Wind Harmer
-0.01
957601AF2-054 GEN
Solar/Wind Harmer
0.284
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971283AH1-107 GEN
Solar/Wind Harmer
1.526
3138283WHITEMARSH
Solar/Wind Harmer
0.014
3151191GRAVEL3
Adder
5.855
315833AF1-017_GEN
Solar/Wind Harmer
1.708
316018AA1-139 ULT2
Solar/Wind Harmer
0.768
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315800Z1-036_GEN1
Solar/Wind Harmer
2.158
971967AH1-528 GEN
Solar/Wind Harmer
16.231
315732AD1-074 GEN1
Solar/Wind Harmer
1.714
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.23
316463AE2-346 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.278
316426AA2-053 GEN
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
1.265
946301AF1-294 GEN
Solar/Wind Harmer
2.073
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205956AE1-196_GEN
Solar/Wind Helper
0.386
233901CHERRYDALE C
Solar/Wind Helper
0.14
20715028HAN_X4-015
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
3152111X4-039 GT1
50/50
1.844
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3150151POSSMC1
Adder
1.084
3150151POSSMC1
Adder
1.084
3150331BIRCHWDA
Adder
16.674
3150291M RUN B
Adder
13.227
316223AC1-118
Solar/Wind Harmer
0.271
3132273ORANGE
Solar/Wind Harmer
-0.002
316203AE2-005 GEN
Solar/Wind Harmer
4.002
970293AG2-193 GEN
Solar/Wind Harmer
1.182
3150921YORKTN3
Adder
2.065
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
41.121
3142956BIRDNECK
Solar/Wind Harmer
0.485
316305AF2-043 C
Solar/Wind Harmer
0.27
316320Y1-086
Solar/Wind Harmer
0.522
3146516WINFALL
Solar/Wind Harmer
-0.009
944011AF1-069 GEN
Solar/Wind Harmer
5.155
315735AD1-075 GEN1
Solar/Wind Harmer
0.857
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.722
3146776BUCKING
Solar/Wind Harmer
-0.003
235067AD1-061 GEN
Solar/Wind Helper
0.282
233950AC2-186 GEN
Solar/Wind Helper
0.07
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
207454AA2-184 E
Solar/Wind Helper
0.181
217169METRODIV C
Solar/Wind Helper
0.002
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
209071AE2-133 GEN
Solar/Wind Helper
0.042
3150281M RUN A
Adder
13.334
316044AC1-158 PL1
Solar/Wind Harmer
1.039
316254AC1-120 GEN1
Solar/Wind Harmer
3.939
957971AF2-091 GEN
Solar/Wind Harmer
1.036
3147666LOUISA
Solar/Wind Harmer
-0.04
316404AE1-155 C
Solar/Wind Harmer
1.854
3151751LOISA D
Adder
5.588
3138133OCRAN
Solar/Wind Harmer
-0.006
315662AE1-191 GEN
Solar/Wind Harmer
1.142
316280AD1-041 GEN
Solar/Wind Harmer
0.714
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.46
316369SG1_INVT
Solar/Wind Harmer
1.642
961611AG1-000B GEN
Solar/Wind Harmer
4.528
3151171GRAVELC
Adder
0.867
316381AD1-082 GEN
Solar/Wind Harmer
0.829
3150981CHESPKA
Adder
1.005
319010AE1-072 C
Solar/Wind Harmer
1.811
315611Z1-036_GEN2
Solar/Wind Harmer
2.158
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.694
971163AH1-040 GEN
Solar/Wind Harmer
8.061
315737AD1-076 GEN
Solar/Wind Harmer
1.612
970087AG2-069 GEN
Solar/Wind Harmer
7.846
957481AF2-042 GEN
Solar/Wind Harmer
25.978
316087AB2-174 GEN
Solar/Wind Harmer
1.182
315693AD1-088 GEN
Solar/Wind Harmer
4.14
3146926FARMVIL
Solar/Wind Harmer
-0.005
971563AH1-280 GEN
Solar/Wind Harmer
1.011
970685AG2-442 GEN
Solar/Wind Harmer
7.066
3146293MARTNCO
Solar/Wind Harmer
0.05
208835TUHI V3-051
Solar/Wind Helper
0.017
23777901MDS_W4-102
Solar/Wind Helper
0.106
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
219919AE1-041 FULL
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
20674928WA_W3-044
Solar/Wind Helper
0.057
20676328BVR_Y1-020
Solar/Wind Helper
0.015
207518AF1-320_GEN
Solar/Wind Helper
0.902
209137AF2-361 C
Solar/Wind Helper
0.711
214067T20SOLAR
Solar/Wind Helper
0.007
207459AE1-142 C O1
Solar/Wind Helper
0.17
20675428EAM_W2-061
Solar/Wind Helper
0.009
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
3151861LOWMORA
Adder
0.643
237038AE2-054 C
Solar/Wind Helper
0.174
233935AB2-179 C
Solar/Wind Helper
0.775
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
959561AF2-247 GEN
Solar/Wind Helper
0.012
3150151POSSMC1
Adder
1.084
316170AC1-121 GEN2
Solar/Wind Harmer
1.313
316337AD2-073 GEN
Solar/Wind Harmer
0.266
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.637
3150851SPRUNCC
Adder
0.385
316132AB2-190 GEN1
Solar/Wind Harmer
0.932
315773AC2-141 GEN
Solar/Wind Harmer
3.799
316036AC1-147 C
Solar/Wind Harmer
0.243
316093AE2-104_GEN
Solar/Wind Harmer
2.602
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.25
970919AG2-571 GEN
Solar/Wind Harmer
2.667
315607AA1-063A GEN
Solar/Wind Harmer
0.839
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.003
237001AB1-127_GEN
Solar/Wind Helper
0.308
233918AB1-142 GEN
Solar/Wind Helper
0.305
228729W2-030 C
Solar/Wind Helper
0.065
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
207530AG1-191 GEN
Solar/Wind Helper
0.038
207439AE1-081 C O1
Solar/Wind Helper
0.011
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
20676428JCR_X2-075
Solar/Wind Helper
0.039
20675128HRM_W1-127
Solar/Wind Helper
0.017
209029WAYMART-WD
Solar/Wind Helper
0.444
959421AF2-233 GEN
Solar/Wind Helper
0.233
20715728PEM_W1-119
Solar/Wind Helper
0.056
207442AE1-156 GEN
Solar/Wind Helper
0.189
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
957921AF2-086 GEN
Solar/Wind Helper
0.234
970221AG2-151 GEN
Solar/Wind Harmer
1.345
20674328GAR_V4-001
Solar/Wind Helper
0.013
946751AF1-339 GEN
Solar/Wind Helper
0.234
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
961261AF2-417 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.163
959431AF2-234 GEN
Solar/Wind Helper
0.467
316411AF1-147_GEN1
Solar/Wind Harmer
1.097
3150071POSSM 5
Adder
49.547
3150391LDYSMT3
Adder
12.65
316312AB1-027
Solar/Wind Harmer
0.32
316441AF1-014 GEN
Solar/Wind Harmer
0.64
3143526WINTERP
Solar/Wind Harmer
-0.049
944641AF1-129 GEN
Adder
39.347
316185AD1-033 GEN
Solar/Wind Harmer
0.95
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.237
972185AH1-677 GEN
Adder
4.322
970099AG2-077 GEN
Solar/Wind Harmer
10.391
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.778
3145783HORNRTN
Solar/Wind Harmer
0.243
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3144293JTRSVLE
Adder
0.172
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
233946AB2-136 GEN
Solar/Wind Helper
0.343
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
961431AF2-434 GEN
Solar/Wind Helper
0.237
315747AE2-019 GEN
50/50
13.164
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.652
316077AC2-138 C
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
0.884
3151761LOISA E
Adder
11.393
3151721LOISA A
Adder
5.56
316484AD2-074 GEN
Solar/Wind Harmer
2.432
316075AC2-137 C
Solar/Wind Harmer
0.254
315778AD1-151 GEN
Solar/Wind Harmer
8.21
3144216WINCHST
Adder
0.309
3151101ELIZAR3
Adder
7.475
944601AF1-125 GEN
Solar/Wind Harmer
40.48
3143336POWHATN
Solar/Wind Harmer
0.898
966621AG1-532 GEN
Solar/Wind Harmer
0.169
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
972003AH1-546 GEN
Solar/Wind Harmer
3.341
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.227
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.702
226910AB2-157 C
Solar/Wind Helper
0.021
237085AD2-009_GEN
Solar/Wind Helper
0.975
233933AB2-153 GEN
Solar/Wind Helper
0.141
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
209116AE2-175 GEN
Solar/Wind Helper
1.008
961421AF2-433 GEN
Solar/Wind Helper
0.237
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
3141426STAFORD
Solar/Wind Harmer
-0.003
316468AD1-105 GEN
Solar/Wind Harmer
1.148
3141913WHIT STONE
Solar/Wind Harmer
-0.01
971285AH1-108 GEN
Adder
0.63
957831AF2-077 GEN
Solar/Wind Harmer
0.281
315697AD1-025 GEN
Solar/Wind Harmer
1.859
315839AE2-212 C
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
5.641
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.277
957871AF2-081 GEN
Solar/Wind Harmer
4.495
316258AE1-075 C
Solar/Wind Harmer
0.216
970673AG2-436 GEN
Solar/Wind Harmer
19.089
316322AB2-045
Solar/Wind Harmer
0.276
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.264
970683AG2-441 GEN
Solar/Wind Harmer
5.694
970681AG2-440 GEN
Solar/Wind Harmer
3.779
970831AG2-522 GEN
Solar/Wind Harmer
4.03
20390526W1-045 C
Solar/Wind Helper
0.253
233940AF2-379 C
Solar/Wind Helper
0.037
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
20673828FLE_V3-070
Solar/Wind Helper
0.05
20676128MHD_W3-029
Solar/Wind Helper
0.056
209027LOR2_Q27
Solar/Wind Helper
0.559
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
316415AF1-147_GEN2
Solar/Wind Harmer
1.097
972223AH1-696 GEN
Adder
8.563
3141346CRANES
Adder
0.12
971685AH1-345 GEN
Solar/Wind Harmer
0.96
972219AH1-694 GEN
Adder
1.425
3150351NORNECKC2
Adder
0.869
964211AG1-282 GEN
Solar/Wind Harmer
0.294
316314AB2-024 C
Solar/Wind Harmer
0.812
3143526WINTERP
Solar/Wind Harmer
-0.049
944631AF1-128 GEN
Adder
39.787
971317AH1-138 GEN
Solar/Wind Harmer
1.161
315671AE2-027_GEN
Solar/Wind Harmer
1.668
944591AF1-124 GEN
Solar/Wind Harmer
41.27
316072AD1-144
Solar/Wind Harmer
0.182
939411AE1-173 GEN
Solar/Wind Harmer
44.9
940641AE2-051 GEN
Solar/Wind Harmer
8.405
3143336POWHATN
Solar/Wind Harmer
1.057
941031AE2-094 GEN
Solar/Wind Harmer
16.452
971547AH1-271 GEN
Solar/Wind Harmer
2.111
960081AF2-299 GEN
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
972277AH1-723 GEN
Adder
42.756
316129AC1-054 GEN
Solar/Wind Harmer
0.703
316034AC1-036 C
Solar/Wind Harmer
0.149
205916AD1-020 GEN
Solar/Wind Helper
1.485
233944AB2-135 GEN
Solar/Wind Helper
0.357
232408W1-005 C
Solar/Wind Helper
0.305
219907AC1-030 C
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.011
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
219908AB1-139 C
Solar/Wind Helper
0.043
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.047
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.234
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.815
LGEELTFEXP_LGEE->PJM
CLTF
1.797
MECLTFEXP_MEC->PJM
CLTF
4.43
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.53
CPLELTFEXP_CPLE->PJM
CLTF
5.052
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.549
WECLTFEXP_WEC->PJM
CLTF
0.958
LAGNLTFEXP_LAGN->PJM
CLTF
6.301
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.321
NYPJM->LTFIMP_NY
CLTF
2.582
TVALTFEXP_TVA->PJM
CLTF
3.176

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: 560T571_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 560T571_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.59 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1935.43
MW Contribution:
1.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150221REMNGT2
Adder
12.465
3150211REMNGT1
Adder
12.382
972201AH1-685 GEN
Adder
2.151
316447AC1-158 HLD
Solar/Wind Harmer
2.28
972197AH1-683 GEN
Adder
1.958
315683AE1-153 C
Solar/Wind Harmer
9.479
972135AH1-637 GEN
Solar/Wind Harmer
1.017
966881AG1-559 GEN
Solar/Wind Harmer
0.104
316192AB2-158 GEN
Solar/Wind Harmer
1.176
958261AF2-120 GEN
Solar/Wind Harmer
3.727
3142416OLDCHRC
Solar/Wind Harmer
-0.024
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.099
3142433PROV 92
Solar/Wind Harmer
-0.037
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3145336SMITFLD
Solar/Wind Harmer
-0.036
316375AC2-012 GEN
Solar/Wind Harmer
3.106
3146456SLIGO L269
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.064
3146206CASHIE
Solar/Wind Harmer
-0.008
316023GEN1_S
Solar/Wind Harmer
0.564
3150281M RUN A
Adder
13.356
316044AC1-158 PL1
Solar/Wind Harmer
1.037
316254AC1-120 GEN1
Solar/Wind Harmer
3.935
957971AF2-091 GEN
Solar/Wind Harmer
1.023
3147666LOUISA
Solar/Wind Harmer
-0.039
3151751LOISA D
Adder
5.574
316404AE1-155 C
Solar/Wind Harmer
1.836
3138133OCRAN
Solar/Wind Harmer
-0.006
315662AE1-191 GEN
Solar/Wind Harmer
1.132
316280AD1-041 GEN
Solar/Wind Harmer
0.708
3143096IRON208
Adder
0.348
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.449
316369SG1_INVT
Solar/Wind Harmer
1.63
961611AG1-000B GEN
Solar/Wind Harmer
4.495
3151171GRAVELC
Adder
0.86
316381AD1-082 GEN
Solar/Wind Harmer
0.823
3150981CHESPKA
Adder
0.998
319010AE1-072 C
Solar/Wind Harmer
1.799
315611Z1-036_GEN2
Solar/Wind Harmer
2.143
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.689
971163AH1-040 GEN
Solar/Wind Harmer
8.006
315737AD1-076 GEN
Solar/Wind Harmer
1.601
963691AG1-221 GEN
Solar/Wind Harmer
2.315
3150241REMNGT4
Adder
12.548
972199AH1-684 GEN
Adder
1.902
3150371LDYSMT1
Adder
12.114
966881AG1-559 GEN
Solar/Wind Harmer
0.305
971781AH1-399 GEN
Solar/Wind Harmer
0.613
961951AG1-038 GEN
Solar/Wind Harmer
1.261
316473AC1-191 GEN
Solar/Wind Harmer
1.029
3142416OLDCHRC
Solar/Wind Harmer
0.952
3141766HARMONY
Solar/Wind Harmer
0.838
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
1.036
315813AE1-149 C
Solar/Wind Harmer
5.656
3145336SMITFLD
Solar/Wind Harmer
-0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.032
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.146
3147043LAWRENC
Solar/Wind Harmer
-0.005
316478AD1-087 GEN
Solar/Wind Harmer
0.7
3147133PAMPLIN
Solar/Wind Harmer
-0.025
972255AH1-712 GEN
Adder
36.481
959311AF2-222 GEN
Solar/Wind Harmer
8.345
227287AC2-120 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.131
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232406W1-004 FULL
Solar/Wind Helper
0.305
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
230415AB2-049 C
Solar/Wind Helper
0.018
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
3142366NRTHEST
Adder
0.273
3150691DARBY 3
Adder
6.012
3150701DARBY 4
Adder
5.998
315976AC1-164 GENA
Solar/Wind Harmer
2.128
316169AC1-164_GENC
Solar/Wind Harmer
1.839
3142946ENON
Solar/Wind Harmer
-0.001
316294AC1-161 GEN
Solar/Wind Harmer
2.915
316083AB2-161 GEN
Solar/Wind Harmer
1.46
316349AD2-085 GEN
Solar/Wind Harmer
0.793
3146456SLIGO L269
Solar/Wind Harmer
1.053
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.595
316433W1029_GEN2
Solar/Wind Harmer
1.595
316336AC2-165 C
Solar/Wind Harmer
5.454
315742AE1-103 GEN
Solar/Wind Harmer
2.062
3146376EDENTON
Solar/Wind Harmer
0.257
3146376EDENTON
Solar/Wind Harmer
0.257
970933AG2-581 GEN
Solar/Wind Harmer
7.973
316365GEN2_N
Solar/Wind Harmer
0.564
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.257
237080AD1-060 GEN
Solar/Wind Helper
0.221
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674828DL_W4-046
Solar/Wind Helper
0.005
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.576
972215AH1-692 GEN
Adder
2.036
316164AC1-076 GEN
Solar/Wind Harmer
0.882
3141813NORNECK
Solar/Wind Harmer
-0.01
957601AF2-054 GEN
Solar/Wind Harmer
0.282
316233AE1-074 FULL
Solar/Wind Harmer
0.251
971283AH1-107 GEN
Solar/Wind Harmer
1.515
3138283WHITEMARSH
Solar/Wind Harmer
0.014
3151191GRAVEL3
Adder
5.812
315833AF1-017_GEN
Solar/Wind Harmer
1.696
316018AA1-139 ULT2
Solar/Wind Harmer
0.763
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315800Z1-036_GEN1
Solar/Wind Harmer
2.143
971967AH1-528 GEN
Solar/Wind Harmer
16.126
315732AD1-074 GEN1
Solar/Wind Harmer
1.703
3145893MURPHYS
Solar/Wind Harmer
-0.022
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.197
316463AE2-346 GEN
Solar/Wind Harmer
0.134
3145513AHOSKIE
Solar/Wind Harmer
0.072
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.218
316426AA2-053 GEN
Solar/Wind Harmer
0.825
316174AB2-169 GEN
Solar/Wind Harmer
1.257
946301AF1-294 GEN
Solar/Wind Harmer
2.061
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151861LOWMORA
Adder
0.616
226929AD2-058 GEN
Solar/Wind Helper
0.144
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205956AE1-196_GEN
Solar/Wind Helper
0.385
233901CHERRYDALE C
Solar/Wind Helper
0.14
20715028HAN_X4-015
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
20720628TIN_W1-124
Solar/Wind Helper
0.11
20675528CPH_W2-050
Solar/Wind Helper
0.066
20676428JCR_X2-075
Solar/Wind Helper
0.039
20675128HRM_W1-127
Solar/Wind Helper
0.017
209029WAYMART-WD
Solar/Wind Helper
0.442
959421AF2-233 GEN
Solar/Wind Helper
0.233
3152111X4-039 GT1
50/50
1.847
971455AH1-223 GEN
Solar/Wind Harmer
2.315
3150151POSSMC1
Adder
1.062
3150151POSSMC1
Adder
1.062
3150291M RUN B
Adder
13.249
3150331BIRCHWDA
Adder
16.425
3132273ORANGE
Solar/Wind Harmer
-0.002
316223AC1-118
Solar/Wind Harmer
0.268
316203AE2-005 GEN
Solar/Wind Harmer
3.969
970293AG2-193 GEN
Solar/Wind Harmer
1.173
3150921YORKTN3
Adder
2.05
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
40.831
3142956BIRDNECK
Solar/Wind Harmer
0.481
316305AF2-043 C
Solar/Wind Harmer
0.268
316320Y1-086
Solar/Wind Harmer
0.519
3146516WINFALL
Solar/Wind Harmer
-0.009
944011AF1-069 GEN
Solar/Wind Harmer
5.121
315735AD1-075 GEN1
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.711
3146776BUCKING
Solar/Wind Harmer
-0.003
3151861LOWMORA
Adder
0.641
237038AE2-054 C
Solar/Wind Helper
0.174
233935AB2-179 C
Solar/Wind Helper
0.773
233987AB2-037 GEN
Solar/Wind Helper
1.408
232417X3-008 C
Solar/Wind Helper
0.14
233923SMA
Solar/Wind Helper
0.452
233997TMININ_4.2
Solar/Wind Helper
0.123
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
207442AE1-156 GEN
Solar/Wind Helper
0.188
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
957921AF2-086 GEN
Solar/Wind Helper
0.233
970221AG2-151 GEN
Solar/Wind Harmer
1.339
316006AB2-029 C
Solar/Wind Harmer
0.63
316045AC1-158 PL2
Solar/Wind Harmer
3.317
966871AG1-558 GEN
Solar/Wind Harmer
0.288
966871AG1-558 GEN
Solar/Wind Harmer
0.098
3142296MT RD221
Adder
0.268
316156AD2-030 GEN
Solar/Wind Harmer
0.251
315666AE1-190 GEN
Solar/Wind Harmer
0.283
3150671DARBY 1
Adder
5.984
971223AH1-071 GEN
Solar/Wind Harmer
1.162
316240AF1-291 C
Solar/Wind Harmer
0.276
3150991CHESPKB
Adder
0.837
3150991CHESPKB
Adder
0.817
315835AF2-110_GEN
Solar/Wind Harmer
1.111
316313AB2-026
Solar/Wind Harmer
0.238
316435W1029_GEN3
Solar/Wind Harmer
1.595
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.166
315614AA2-178 GEN
Solar/Wind Harmer
0.919
316065AD1-022 GEN
Solar/Wind Harmer
4.203
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.015
316140AB2-099
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
972193AH1-681 GEN
Adder
1.63
232436AB1-176 C
Solar/Wind Helper
0.027
234036AF2-325 C
Solar/Wind Helper
0.025
233994AC2-023 GEN
Solar/Wind Helper
0.577
3150181POSSMC2
Adder
1.071
3150181POSSMC2
Adder
1.062
3150181POSSMC2
Adder
1.062
316450AC1-158 RIC
Solar/Wind Harmer
0.276
972195AH1-682 GEN
Adder
1.644
315673AE1-157 GEN
Solar/Wind Harmer
7.709
972189AH1-679 GEN
Adder
1.453
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3150341NORNECKC1
Adder
0.904
3150341NORNECKC1
Adder
0.897
3151731LOISA B
Adder
5.574
316487AF1-042 GEN
Solar/Wind Harmer
1.261
3150681DARBY 2
Adder
5.991
316033AB2-134 GEN
Solar/Wind Harmer
2.944
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.601
316388AE2-253 GEN
Solar/Wind Harmer
0.601
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3130086AYDLETT
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
0.66
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.1
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
970323AG2-213 GEN
Solar/Wind Harmer
3.993
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
235062AE1-101 C1
Solar/Wind Helper
1.066
232424Y1-079 C
Solar/Wind Helper
0.07
232428Y3-058 C
Solar/Wind Helper
0.203
234015AF2-250 C
Solar/Wind Helper
0.023
230433AD2-135 GEN
Solar/Wind Helper
0.01
972213AH1-691 GEN
Adder
2.036
944491AF1-114 GEN
Solar/Wind Harmer
3.009
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
-0.003
3141873WAN 176
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.515
316382AG1-145 C
Solar/Wind Harmer
0.278
316159AE1-175 C
Solar/Wind Harmer
0.247
316236AE1-162_GEN
Solar/Wind Harmer
0.272
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.567
316405AF2-144 C
Solar/Wind Harmer
0.226
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
970533AG2-339 GEN
Solar/Wind Harmer
5.862
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.703
970601AG2-382 GEN
Solar/Wind Harmer
3.67
970581AG2-369 GEN
Solar/Wind Harmer
4.47
946281AF1-292 GEN
Solar/Wind Harmer
0.186
972205AH1-687 GEN
Adder
3.111
3146033SCOT NK
Solar/Wind Harmer
-0.032
3151881LOWMORC
Adder
0.636
3151881LOWMORC
Adder
0.626
205943AE1-185 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.304
228728W1-130C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
961261AF2-417 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.162
959431AF2-234 GEN
Solar/Wind Helper
0.465
214067T20SOLAR
Solar/Wind Helper
0.007
207459AE1-142 C O1
Solar/Wind Helper
0.169
20675428EAM_W2-061
Solar/Wind Helper
0.009
3152131X4-039 ST
50/50
2.888
3152121X4-039 GT2
50/50
1.835
316415AF1-147_GEN2
Solar/Wind Harmer
1.1
972223AH1-696 GEN
Adder
8.389
3141346CRANES
Adder
0.118
971685AH1-345 GEN
Solar/Wind Harmer
0.961
972219AH1-694 GEN
Adder
1.41
3150351NORNECKC2
Adder
0.861
964211AG1-282 GEN
Solar/Wind Harmer
0.291
316314AB2-024 C
Solar/Wind Harmer
0.805
3143526WINTERP
Solar/Wind Harmer
-0.048
944631AF1-128 GEN
Adder
39.483
971317AH1-138 GEN
Solar/Wind Harmer
1.152
315671AE2-027_GEN
Solar/Wind Harmer
1.655
944591AF1-124 GEN
Solar/Wind Harmer
40.978
316072AD1-144
Solar/Wind Harmer
0.181
939411AE1-173 GEN
Solar/Wind Harmer
44.594
940641AE2-051 GEN
Solar/Wind Harmer
8.349
3143336POWHATN
Solar/Wind Harmer
1.05
941031AE2-094 GEN
Solar/Wind Harmer
16.344
971547AH1-271 GEN
Solar/Wind Harmer
2.097
315747AE2-019 GEN
50/50
13.195
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.654
316077AC2-138 C
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.875
3151761LOISA E
Adder
11.363
3151721LOISA A
Adder
5.545
316484AD2-074 GEN
Solar/Wind Harmer
2.41
316075AC2-137 C
Solar/Wind Harmer
0.252
315778AD1-151 GEN
Solar/Wind Harmer
8.149
3144216WINCHST
Adder
0.307
3151101ELIZAR3
Adder
7.422
944601AF1-125 GEN
Solar/Wind Harmer
40.194
3143336POWHATN
Solar/Wind Harmer
0.893
966621AG1-532 GEN
Solar/Wind Harmer
0.168
316317KELFORD C
Solar/Wind Harmer
0.379
3145823KELFORD
Solar/Wind Harmer
-0.008
972003AH1-546 GEN
Solar/Wind Harmer
3.324
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.22
3144293JTRSVLE
Adder
0.171
316212AC1-099_GEN
Solar/Wind Harmer
0.698
226910AB2-157 C
Solar/Wind Helper
0.021
237085AD2-009_GEN
Solar/Wind Helper
0.972
233933AB2-153 GEN
Solar/Wind Helper
0.141
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.051
209116AE2-175 GEN
Solar/Wind Helper
1.005
961421AF2-433 GEN
Solar/Wind Helper
0.236
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
316411AF1-147_GEN1
Solar/Wind Harmer
1.1
3150071POSSM 5
Adder
48.541
3150391LDYSMT3
Adder
12.514
316312AB1-027
Solar/Wind Harmer
0.317
316441AF1-014 GEN
Solar/Wind Harmer
0.635
3143526WINTERP
Solar/Wind Harmer
-0.048
944641AF1-129 GEN
Adder
39.056
316185AD1-033 GEN
Solar/Wind Harmer
0.943
3144356SAPONY
Solar/Wind Harmer
0.305
316315AB2-025 C
Solar/Wind Harmer
0.235
972185AH1-677 GEN
Adder
4.294
970099AG2-077 GEN
Solar/Wind Harmer
10.327
962571AG1-106 GEN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.966
3145783HORNRTN
Solar/Wind Harmer
0.773
3145783HORNRTN
Solar/Wind Harmer
0.242
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3144293JTRSVLE
Adder
0.171
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.217
233930AB2-032 GEN
Solar/Wind Helper
0.23
233946AB2-136 GEN
Solar/Wind Helper
0.342
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
961431AF2-434 GEN
Solar/Wind Helper
0.236
3141426STAFORD
Solar/Wind Harmer
-0.002
316468AD1-105 GEN
Solar/Wind Harmer
1.136
3141913WHIT STONE
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
0.625
957831AF2-077 GEN
Solar/Wind Harmer
0.279
315697AD1-025 GEN
Solar/Wind Harmer
1.845
315839AE2-212 C
Solar/Wind Harmer
0.275
971445AH1-216 GEN
Solar/Wind Harmer
5.601
3151081ELIZAR1
Adder
7.328
3151091ELIZAR2
Adder
7.201
316316AC1-027 C
Solar/Wind Harmer
0.275
957871AF2-081 GEN
Solar/Wind Harmer
4.463
316258AE1-075 C
Solar/Wind Harmer
0.214
970673AG2-436 GEN
Solar/Wind Harmer
18.965
316322AB2-045
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.256
970683AG2-441 GEN
Solar/Wind Harmer
5.661
970681AG2-440 GEN
Solar/Wind Harmer
3.757
970831AG2-522 GEN
Solar/Wind Harmer
4.005
219912AD2-042 GEN
Solar/Wind Helper
0.089
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.077
20674328GAR_V4-001
Solar/Wind Helper
0.013
946751AF1-339 GEN
Solar/Wind Helper
0.233
3150301M RUN C
Adder
13.348
3150401LDYSMT4
Adder
12.537
3141906WESTMOR
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.023
3141873WAN 176
Solar/Wind Harmer
1.118
3141843SHACKLE
Adder
0.428
3143096IRON208
Adder
0.348
3143096IRON208
Adder
0.341
3150861SPRUNCD
Adder
0.382
316458AB2-190 GEN2
Solar/Wind Harmer
0.926
961611AG1-000B GEN
Solar/Wind Harmer
1.918
3151171GRAVELC
Adder
1.131
970657AG2-426 GEN
Solar/Wind Harmer
1.817
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.18
316321Z2-027
Solar/Wind Harmer
0.238
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.74
970917AG2-570 GEN
Solar/Wind Harmer
20.934
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.1
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.008
970257AG2-171 GEN
Solar/Wind Harmer
2.995
971775AH1-396 GEN
Solar/Wind Harmer
0.564
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
235067AD1-061 GEN
Solar/Wind Helper
0.281
233950AC2-186 GEN
Solar/Wind Helper
0.07
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
207454AA2-184 E
Solar/Wind Helper
0.18
217169METRODIV C
Solar/Wind Helper
0.002
963161AG1-165 GEN
Solar/Wind Helper
0.241
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
209071AE2-133 GEN
Solar/Wind Helper
0.042
970087AG2-069 GEN
Solar/Wind Harmer
7.796
957481AF2-042 GEN
Solar/Wind Harmer
25.816
316087AB2-174 GEN
Solar/Wind Harmer
1.175
315693AD1-088 GEN
Solar/Wind Harmer
4.115
3146926FARMVIL
Solar/Wind Harmer
-0.005
971563AH1-280 GEN
Solar/Wind Harmer
1.005
970685AG2-442 GEN
Solar/Wind Harmer
7.025
3146293MARTNCO
Solar/Wind Harmer
0.05
208835TUHI V3-051
Solar/Wind Helper
0.017
23777901MDS_W4-102
Solar/Wind Helper
0.105
233998TM1NIN_3.36
Solar/Wind Helper
0.123
232404W1-003 C
Solar/Wind Helper
0.305
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20715228NPK_W1-113
Solar/Wind Helper
0.045
20720528MAN_W1-024
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
20674928WA_W3-044
Solar/Wind Helper
0.056
20676328BVR_Y1-020
Solar/Wind Helper
0.015
207518AF1-320_GEN
Solar/Wind Helper
0.899
209137AF2-361 C
Solar/Wind Helper
0.709
20390526W1-045 C
Solar/Wind Helper
0.252
233940AF2-379 C
Solar/Wind Helper
0.037
230434AG1-499 GEN
Solar/Wind Helper
0.136
219258KINSLEYDEP C
Solar/Wind Helper
0.045
20673828FLE_V3-070
Solar/Wind Helper
0.05
20676128MHD_W3-029
Solar/Wind Helper
0.055
209027LOR2_Q27
Solar/Wind Helper
0.557
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
960081AF2-299 GEN
Solar/Wind Harmer
0.932
3145823KELFORD
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.171
3144293JTRSVLE
Adder
0.135
972277AH1-723 GEN
Adder
42.511
316129AC1-054 GEN
Solar/Wind Harmer
0.698
316034AC1-036 C
Solar/Wind Harmer
0.148
205916AD1-020 GEN
Solar/Wind Helper
1.482
233944AB2-135 GEN
Solar/Wind Helper
0.356
232408W1-005 C
Solar/Wind Helper
0.305
219907AC1-030 C
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.011
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
218428ETC SOLAR C
Solar/Wind Helper
0.003
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.047
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.233
3150151POSSMC1
Adder
1.062
316170AC1-121 GEN2
Solar/Wind Harmer
1.312
316337AD2-073 GEN
Solar/Wind Harmer
0.263
3141726DUNNSVL
Solar/Wind Harmer
-0.038
962861AG1-135 GEN
Solar/Wind Harmer
3.603
3150851SPRUNCC
Adder
0.382
316132AB2-190 GEN1
Solar/Wind Harmer
0.926
315773AC2-141 GEN
Solar/Wind Harmer
3.772
316036AC1-147 C
Solar/Wind Harmer
0.242
316093AE2-104_GEN
Solar/Wind Harmer
2.584
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.249
970919AG2-571 GEN
Solar/Wind Harmer
2.65
315607AA1-063A GEN
Solar/Wind Harmer
0.833
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.003
237001AB1-127_GEN
Solar/Wind Helper
0.307
233918AB1-142 GEN
Solar/Wind Helper
0.304
228729W2-030 C
Solar/Wind Helper
0.065
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219348LDSOLAR C
Solar/Wind Helper
0.067
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
207530AG1-191 GEN
Solar/Wind Helper
0.038
207439AE1-081 C O1
Solar/Wind Helper
0.011
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.241
963151AG1-164 GEN
Solar/Wind Helper
0.241
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.828
970053AG2-049 GEN
50/50
2.017
315651AD1-115 GEN
Solar/Wind Harmer
4.648
3150381LDYSMT2
Adder
12.036
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.212
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3151201GRAVEL4
Adder
5.887
3151221GRAVEL6
Adder
5.88
3151211GRAVEL5
Adder
5.812
316311AC2-079 GEN
Solar/Wind Harmer
4.505
313526AB2-022
Solar/Wind Harmer
0.238
3146396TANGLEW
Solar/Wind Harmer
0.163
315814AE2-033 C
Solar/Wind Harmer
8.134
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.209
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
971845AH1-439 GEN
Solar/Wind Harmer
4.345
316486AD2-202 GEN
Solar/Wind Harmer
0.205
961791AG1-021 GEN
Solar/Wind Harmer
1.005
316274AC1-208 GEN
Solar/Wind Harmer
0.859
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
959381AF2-229 GEN
Solar/Wind Helper
0.257
232432Z2-076 GEN
Solar/Wind Helper
0.04
230407AD2-065 C
Solar/Wind Helper
0.024
20720728JCB_W1-129
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
209054AE2-059 GEN
Solar/Wind Helper
0.042
209067AE2-060 GEN
Solar/Wind Helper
0.042
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.118
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.658
205932AD2-116_GEN
Solar/Wind Helper
0.385
235063AE1-101 C2
Solar/Wind Helper
1.066
203975AE1-071-GEN
Solar/Wind Helper
1.715
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.123
219766PARADISE C
Solar/Wind Helper
0.032
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
218440SUMMTASSOC C
Solar/Wind Helper
0.01
217208PARK ELE C
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.051
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.711
LGEELTFEXP_LGEE->PJM
CLTF
1.794
MECLTFEXP_MEC->PJM
CLTF
4.421
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.471
CPLELTFEXP_CPLE->PJM
CLTF
5.025
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.515
WECLTFEXP_WEC->PJM
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
6.282
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.264
NYPJM->LTFIMP_NY
CLTF
2.573
TVALTFEXP_TVA->PJM
CLTF
3.166

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.6 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1878.9
MW Contribution:
1.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150281M RUN A
Adder
11.691
316254AC1-120 GEN1
Solar/Wind Harmer
3.304
316044AC1-158 PL1
Solar/Wind Harmer
0.851
3147666LOUISA
Solar/Wind Harmer
-0.032
3151751LOISA D
Adder
4.646
957971AF2-091 GEN
Solar/Wind Harmer
0.749
316404AE1-155 C
Solar/Wind Harmer
1.394
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
0.87
316280AD1-041 GEN
Solar/Wind Harmer
0.544
3143096IRON208
Adder
0.27
3142543TWELFTH
Solar/Wind Harmer
-0.001
971069AG2-661 GEN
Solar/Wind Harmer
1.128
3138126ROCKLANDING
Solar/Wind Harmer
0.022
316369SG1_INVT
Solar/Wind Harmer
1.27
961611AG1-000B GEN
Solar/Wind Harmer
3.506
3151171GRAVELC
Adder
0.672
316381AD1-082 GEN
Solar/Wind Harmer
0.645
3150981CHESPKA
Adder
0.782
319010AE1-072 C
Solar/Wind Harmer
1.412
315611Z1-036_GEN2
Solar/Wind Harmer
1.693
3130156CHOWAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.546
971163AH1-040 GEN
Solar/Wind Harmer
6.349
315737AD1-076 GEN
Solar/Wind Harmer
1.273
3146926FARMVIL
Solar/Wind Harmer
-0.004
970087AG2-069 GEN
Solar/Wind Harmer
6.243
957481AF2-042 GEN
Solar/Wind Harmer
20.758
971377AH1-170 GEN
Solar/Wind Harmer
0.83
3152111X4-039 GT1
50/50
1.834
971455AH1-223 GEN
Solar/Wind Harmer
2.258
3150291M RUN B
Adder
11.597
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.712
316006AB2-029 C
Solar/Wind Harmer
0.548
316045AC1-158 PL2
Solar/Wind Harmer
2.723
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
3142296MT RD221
Adder
0.206
971223AH1-071 GEN
Solar/Wind Harmer
0.911
3150671DARBY 1
Adder
4.621
315666AE1-190 GEN
Solar/Wind Harmer
0.217
316156AD2-030 GEN
Solar/Wind Harmer
0.193
316240AF1-291 C
Solar/Wind Harmer
0.215
316313AB2-026
Solar/Wind Harmer
0.19
3150991CHESPKB
Adder
0.656
3150991CHESPKB
Adder
0.641
315835AF2-110_GEN
Solar/Wind Harmer
0.873
316435W1029_GEN3
Solar/Wind Harmer
1.256
971761AH1-387 GEN
Solar/Wind Harmer
3.866
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
972187AH1-678 GEN
Adder
1.725
315614AA2-178 GEN
Solar/Wind Harmer
0.729
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
316065AD1-022 GEN
Solar/Wind Harmer
3.346
3145893MURPHYS
Solar/Wind Harmer
0.186
3145893MURPHYS
Solar/Wind Harmer
-0.012
316140AB2-099
Solar/Wind Harmer
0.045
3147346CASHSCORNER
Solar/Wind Harmer
0.123
972213AH1-691 GEN
Adder
1.49
944491AF1-114 GEN
Solar/Wind Harmer
2.202
971281AH1-106 GEN
Solar/Wind Harmer
1.182
3138133OCRAN
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.004
3141873WAN 176
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.215
316159AE1-175 C
Solar/Wind Harmer
0.192
3143316POE
Solar/Wind Harmer
-0.028
316405AF2-144 C
Solar/Wind Harmer
0.181
316236AE1-162_GEN
Solar/Wind Harmer
0.213
970657AG2-426 GEN
Solar/Wind Harmer
0.444
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
970533AG2-339 GEN
Solar/Wind Harmer
4.647
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
Adder
2.57
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315733AD1-074 GEN2
Solar/Wind Harmer
1.354
970601AG2-382 GEN
Solar/Wind Harmer
2.923
970581AG2-369 GEN
Solar/Wind Harmer
3.579
946281AF1-292 GEN
Solar/Wind Harmer
0.149
3150301M RUN C
Adder
11.683
3147666LOUISA
Solar/Wind Harmer
-0.018
3150401LDYSMT4
Adder
9.178
3141906WESTMOR
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.297
3141873WAN 176
Solar/Wind Harmer
0.858
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.264
316458AB2-190 GEN2
Solar/Wind Harmer
0.72
961611AG1-000B GEN
Solar/Wind Harmer
1.496
3151171GRAVELC
Adder
0.883
970657AG2-426 GEN
Solar/Wind Harmer
1.423
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.141
315693AD1-088 GEN
Solar/Wind Harmer
3.317
316087AB2-174 GEN
Solar/Wind Harmer
0.941
971563AH1-280 GEN
Solar/Wind Harmer
0.819
970685AG2-442 GEN
Solar/Wind Harmer
5.722
208835TUHI V3-051
Solar/Wind Helper
0.017
23777901MDS_W4-102
Solar/Wind Helper
0.113
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.306
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20715228NPK_W1-113
Solar/Wind Helper
0.045
20720528MAN_W1-024
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
20674928WA_W3-044
Solar/Wind Helper
0.056
20676328BVR_Y1-020
Solar/Wind Helper
0.015
207518AF1-320_GEN
Solar/Wind Helper
0.895
209137AF2-361 C
Solar/Wind Helper
0.706
3146033SCOT NK
Solar/Wind Harmer
-0.026
205943AE1-185 GEN
Solar/Wind Helper
0.41
233915AB1-141 GEN
Solar/Wind Helper
0.305
228728W1-130C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
961261AF2-417 GEN
Solar/Wind Helper
0.239
212266LOR1
Solar/Wind Helper
0.16
959431AF2-234 GEN
Solar/Wind Helper
0.459
316170AC1-121 GEN2
Solar/Wind Harmer
1.101
3150151POSSMC1
Adder
0.712
316337AD2-073 GEN
Solar/Wind Harmer
0.198
3141726DUNNSVL
Solar/Wind Harmer
-0.029
962861AG1-135 GEN
Solar/Wind Harmer
2.737
3150851SPRUNCC
Adder
0.297
316132AB2-190 GEN1
Solar/Wind Harmer
0.72
315773AC2-141 GEN
Solar/Wind Harmer
2.954
316036AC1-147 C
Solar/Wind Harmer
0.189
316093AE2-104_GEN
Solar/Wind Harmer
2.03
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.119
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.198
315607AA1-063A GEN
Solar/Wind Harmer
0.667
3146263WOODLND
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
237001AB1-127_GEN
Solar/Wind Helper
0.343
233918AB1-142 GEN
Solar/Wind Helper
0.305
228729W2-030 C
Solar/Wind Helper
0.065
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219348LDSOLAR C
Solar/Wind Helper
0.067
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
207530AG1-191 GEN
Solar/Wind Helper
0.038
207439AE1-081 C O1
Solar/Wind Helper
0.011
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.239
963151AG1-164 GEN
Solar/Wind Helper
0.239
961341AF2-425 GEN
Solar/Wind Helper
0.234
212507AE2-042_GEN
Solar/Wind Helper
0.818
316164AC1-076 GEN
Solar/Wind Harmer
0.727
3150411LDYSMT5
Adder
9.207
972215AH1-692 GEN
Adder
1.49
3141813NORNECK
Solar/Wind Harmer
-0.007
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971283AH1-107 GEN
Solar/Wind Harmer
1.182
957601AF2-054 GEN
Solar/Wind Harmer
0.216
3138283WHITEMARSH
Solar/Wind Harmer
0.011
3151191GRAVEL3
Adder
4.537
315833AF1-017_GEN
Solar/Wind Harmer
1.331
316018AA1-139 ULT2
Solar/Wind Harmer
0.599
3146406KITTY HAWK
Solar/Wind Harmer
0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.693
971967AH1-528 GEN
Solar/Wind Harmer
12.837
315732AD1-074 GEN1
Solar/Wind Harmer
1.354
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.162
316463AE2-346 GEN
Solar/Wind Harmer
0.107
3145513AHOSKIE
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3137643SOCKMAN
Solar/Wind Harmer
-0.026
316426AA2-053 GEN
Solar/Wind Harmer
0.662
315652AC1-086 GEN
Solar/Wind Harmer
7.388
946301AF1-294 GEN
Solar/Wind Harmer
1.679
316450AC1-158 RIC
Solar/Wind Harmer
0.227
966001AG1-469 GEN
Solar/Wind Harmer
0.153
3151731LOISA B
Adder
4.646
3150181POSSMC2
Adder
0.718
3150181POSSMC2
Adder
0.712
3150181POSSMC2
Adder
0.712
972195AH1-682 GEN
Adder
1.204
315673AE1-157 GEN
Solar/Wind Harmer
5.701
972189AH1-679 GEN
Adder
1.102
3150341NORNECKC1
Adder
0.683
3150341NORNECKC1
Adder
0.678
316487AF1-042 GEN
Solar/Wind Harmer
0.96
3150681DARBY 2
Adder
4.627
316033AB2-134 GEN
Solar/Wind Harmer
2.294
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.471
316388AE2-253 GEN
Solar/Wind Harmer
0.471
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
970301AG2-198 GEN
Solar/Wind Harmer
3.329
313506AB2-031 GEN
Solar/Wind Harmer
0.529
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.054
970323AG2-213 GEN
Solar/Wind Harmer
3.251
237006AB1-125 GEN
Solar/Wind Helper
0.175
223401AF1-299 GEN
Solar/Wind Helper
0.386
235062AE1-101 C1
Solar/Wind Helper
1.173
232424Y1-079 C
Solar/Wind Helper
0.07
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
230433AD2-135 GEN
Solar/Wind Helper
0.01
214067T20SOLAR
Solar/Wind Helper
0.007
207459AE1-142 C O1
Solar/Wind Helper
0.169
20675428EAM_W2-061
Solar/Wind Helper
0.009
316174AB2-169 GEN
Solar/Wind Harmer
1.007
3144303KENBRDG
Solar/Wind Harmer
-0.005
23779801AA1-109
Solar/Wind Helper
0.262
205917AD1-020 ES
Solar/Wind Helper
0.358
226929AD2-058 GEN
Solar/Wind Helper
0.079
205956AE1-196_GEN
Solar/Wind Helper
0.407
233901CHERRYDALE C
Solar/Wind Helper
0.14
20715028HAN_X4-015
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
20720628TIN_W1-124
Solar/Wind Helper
0.11
20675528CPH_W2-050
Solar/Wind Helper
0.065
20676428JCR_X2-075
Solar/Wind Helper
0.039
20675128HRM_W1-127
Solar/Wind Helper
0.017
209029WAYMART-WD
Solar/Wind Helper
0.438
959421AF2-233 GEN
Solar/Wind Helper
0.23
972193AH1-681 GEN
Adder
1.345
232436AB1-176 C
Solar/Wind Helper
0.027
234036AF2-325 C
Solar/Wind Helper
0.026
233994AC2-023 GEN
Solar/Wind Helper
0.58
219912AD2-042 GEN
Solar/Wind Helper
0.089
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.077
20674328GAR_V4-001
Solar/Wind Helper
0.013
946751AF1-339 GEN
Solar/Wind Helper
0.23
3142366NRTHEST
Adder
0.211
3150691DARBY 3
Adder
4.643
3150701DARBY 4
Adder
4.632
315976AC1-164 GENA
Solar/Wind Harmer
1.643
316169AC1-164_GENC
Solar/Wind Harmer
1.419
3142946ENON
Solar/Wind Harmer
-0.001
316294AC1-161 GEN
Solar/Wind Harmer
2.283
316083AB2-161 GEN
Solar/Wind Harmer
1.144
316336AC2-165 C
Solar/Wind Harmer
4.383
316349AD2-085 GEN
Solar/Wind Harmer
0.622
3146456SLIGO L269
Solar/Wind Harmer
0.827
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.256
316433W1029_GEN2
Solar/Wind Harmer
1.256
315742AE1-103 GEN
Solar/Wind Harmer
1.629
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
970933AG2-581 GEN
Solar/Wind Harmer
6.362
316365GEN2_N
Solar/Wind Harmer
0.45
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.187
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.18
970917AG2-570 GEN
Solar/Wind Harmer
16.739
3146926FARMVIL
Solar/Wind Harmer
-0.004
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
237002AB1-128_GEN
Solar/Wind Helper
0.332
208835TUHI V3-051
Solar/Wind Helper
0.017
235067AD1-061 GEN
Solar/Wind Helper
0.308
233950AC2-186 GEN
Solar/Wind Helper
0.07
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
207454AA2-184 E
Solar/Wind Helper
0.18
217169METRODIV C
Solar/Wind Helper
0.002
963161AG1-165 GEN
Solar/Wind Helper
0.239
208972BECR K09
Solar/Wind Helper
0.176
961331AF2-424 GEN
Solar/Wind Helper
0.234
209071AE2-133 GEN
Solar/Wind Helper
0.042
970257AG2-171 GEN
Solar/Wind Harmer
0.153
3150151POSSMC1
Adder
0.712
3150331BIRCHWDA
Adder
11.656
316223AC1-118
Solar/Wind Harmer
0.2
970293AG2-193 GEN
Solar/Wind Harmer
0.906
316203AE2-005 GEN
Solar/Wind Harmer
3.049
3150921YORKTN3
Adder
1.594
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
32.014
3142956BIRDNECK
Solar/Wind Harmer
0.377
316305AF2-043 C
Solar/Wind Harmer
0.21
316320Y1-086
Solar/Wind Harmer
0.408
3146516WINFALL
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
4.06
3146776BUCKING
Solar/Wind Harmer
-0.002
315735AD1-075 GEN1
Solar/Wind Harmer
0.677
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
4.15
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.372
3145963POPLR C
Solar/Wind Harmer
-0.007
237038AE2-054 C
Solar/Wind Helper
0.191
233935AB2-179 C
Solar/Wind Helper
0.776
233987AB2-037 GEN
Solar/Wind Helper
1.415
232417X3-008 C
Solar/Wind Helper
0.14
233923SMA
Solar/Wind Helper
0.454
233997TMININ_4.2
Solar/Wind Helper
0.124
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
207442AE1-156 GEN
Solar/Wind Helper
0.188
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
957921AF2-086 GEN
Solar/Wind Helper
0.231
970053AG2-049 GEN
Adder
1.473
315651AD1-115 GEN
Solar/Wind Harmer
3.931
3150381LDYSMT2
Adder
8.811
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.163
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3151201GRAVEL4
Adder
4.595
3151221GRAVEL6
Adder
4.59
3151211GRAVEL5
Adder
4.537
316311AC2-079 GEN
Solar/Wind Harmer
3.535
313526AB2-022
Solar/Wind Harmer
0.187
3146396TANGLEW
Solar/Wind Harmer
0.128
315814AE2-033 C
Solar/Wind Harmer
6.429
971845AH1-439 GEN
Solar/Wind Harmer
3.565
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.166
961941AG1-037 GEN
Solar/Wind Harmer
0.05
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
961791AG1-021 GEN
Solar/Wind Harmer
0.819
316486AD2-202 GEN
Solar/Wind Harmer
0.166
963691AG1-221 GEN
Solar/Wind Harmer
2.258
3150241REMNGT4
Adder
10.998
972199AH1-684 GEN
Adder
1.667
3150371LDYSMT1
Adder
8.868
966881AG1-559 GEN
Solar/Wind Harmer
0.227
971781AH1-399 GEN
Solar/Wind Harmer
0.458
316473AC1-191 GEN
Solar/Wind Harmer
0.787
961951AG1-038 GEN
Solar/Wind Harmer
0.96
3142416OLDCHRC
Solar/Wind Harmer
0.733
3141766HARMONY
Solar/Wind Harmer
0.644
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142946ENON
Solar/Wind Harmer
-0.002
970133AG2-095 GEN
Solar/Wind Harmer
0.806
315813AE1-149 C
Solar/Wind Harmer
4.424
3145336SMITFLD
Solar/Wind Harmer
-0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.565
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.81
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
30.111
316181AB2-040 GEN
Solar/Wind Harmer
0.919
3147043LAWRENC
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316478AD1-087 GEN
Solar/Wind Harmer
0.565
959311AF2-222 GEN
Solar/Wind Harmer
6.794
23777801MSM_W1-116
Solar/Wind Helper
0.157
227287AC2-120 GEN
Solar/Wind Helper
0.31
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232406W1-004 FULL
Solar/Wind Helper
0.306
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
3150221REMNGT2
Adder
10.925
3150211REMNGT1
Adder
10.853
972201AH1-685 GEN
Adder
1.885
316447AC1-158 HLD
Solar/Wind Harmer
1.872
315683AE1-153 C
Solar/Wind Harmer
8.072
316192AB2-158 GEN
Solar/Wind Harmer
0.957
972197AH1-683 GEN
Adder
1.433
966881AG1-559 GEN
Solar/Wind Harmer
0.078
972135AH1-637 GEN
Solar/Wind Harmer
0.749
958261AF2-120 GEN
Solar/Wind Harmer
2.829
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3141766HARMONY
Solar/Wind Harmer
-0.001
971777AH1-397 GEN
Solar/Wind Harmer
0.844
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
315975AC1-164 GENB
Solar/Wind Harmer
0.049
3145336SMITFLD
Solar/Wind Harmer
-0.028
316375AC2-012 GEN
Solar/Wind Harmer
2.434
3146456SLIGO L269
Solar/Wind Harmer
-0.007
970937AG2-583 GEN
Solar/Wind Harmer
4.944
3145663CRESWEL
Solar/Wind Harmer
-0.019
316023GEN1_S
Solar/Wind Harmer
0.45
3146206CASHIE
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3156021HOLLOMANSOL
Solar/Wind Harmer
0.892
3145683EARLEYS
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.529
235063AE1-101 C2
Solar/Wind Helper
1.173
205932AD2-116_GEN
Solar/Wind Helper
0.407
203975AE1-071-GEN
Solar/Wind Helper
1.876
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
219766PARADISE C
Solar/Wind Helper
0.032
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217208PARK ELE C
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.051
237030AB1-096 C
Solar/Wind Helper
0.095
237025AB1-124 C
Solar/Wind Helper
0.234
959381AF2-229 GEN
Solar/Wind Helper
0.283
232432Z2-076 GEN
Solar/Wind Helper
0.04
230407AD2-065 C
Solar/Wind Helper
0.024
20720728JCB_W1-129
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
209067AE2-060 GEN
Solar/Wind Helper
0.042
209054AE2-059 GEN
Solar/Wind Helper
0.042
315747AE2-019 GEN
50/50
12.529
3141196NOKESVL
Solar/Wind Harmer
-0.043
972217AH1-693 GEN
Adder
1.45
3151761LOISA E
Adder
9.471
3151721LOISA A
Adder
4.622
316077AC2-138 C
Solar/Wind Harmer
0.154
3150351NORNECKC2
Adder
0.661
316484AD2-074 GEN
Solar/Wind Harmer
1.834
316075AC2-137 C
Solar/Wind Harmer
0.195
315778AD1-151 GEN
Solar/Wind Harmer
6.347
3144216WINCHST
Adder
0.239
3143336POWHATN
Solar/Wind Harmer
0.714
3151101ELIZAR3
Adder
5.817
944601AF1-125 GEN
Solar/Wind Harmer
31.514
3152131X4-039 ST
50/50
2.868
3152121X4-039 GT2
50/50
1.822
316415AF1-147_GEN2
Solar/Wind Harmer
1.073
971685AH1-345 GEN
Solar/Wind Harmer
0.836
972223AH1-696 GEN
Adder
5.622
3141346CRANES
Adder
0.082
972219AH1-694 GEN
Adder
1.032
3150351NORNECKC2
Adder
0.65
964211AG1-282 GEN
Solar/Wind Harmer
0.22
3143526WINTERP
Solar/Wind Harmer
-0.038
316314AB2-024 C
Solar/Wind Harmer
0.618
944631AF1-128 GEN
Adder
30.58
971317AH1-138 GEN
Solar/Wind Harmer
0.894
315671AE2-027_GEN
Solar/Wind Harmer
1.289
3143336POWHATN
Solar/Wind Harmer
0.84
944591AF1-124 GEN
Solar/Wind Harmer
32.129
316072AD1-144
Solar/Wind Harmer
0.142
939411AE1-173 GEN
Solar/Wind Harmer
35.115
940641AE2-051 GEN
Solar/Wind Harmer
6.583
941031AE2-094 GEN
Solar/Wind Harmer
12.958
971547AH1-271 GEN
Solar/Wind Harmer
1.67
3147623JAMES R
Solar/Wind Harmer
0.103
960081AF2-299 GEN
Solar/Wind Harmer
0.746
972277AH1-723 GEN
Adder
35.088
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
958211AF2-115 GEN
Solar/Wind Harmer
1.024
237080AD1-060 GEN
Solar/Wind Helper
0.243
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674828DL_W4-046
Solar/Wind Helper
0.005
3145823KELFORD
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.139
3144293JTRSVLE
Adder
0.11
3145783HORNRTN
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.007
316034AC1-036 C
Solar/Wind Harmer
0.12
205916AD1-020 GEN
Solar/Wind Helper
1.663
233944AB2-135 GEN
Solar/Wind Helper
0.358
232408W1-005 C
Solar/Wind Helper
0.306
219907AC1-030 C
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.011
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
218428ETC SOLAR C
Solar/Wind Helper
0.003
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.047
20676228FRD_X1-012
Solar/Wind Helper
0.052
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.23
3141426STAFORD
Solar/Wind Harmer
-0.002
316468AD1-105 GEN
Solar/Wind Harmer
0.85
3141913WHIT STONE
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.486
957831AF2-077 GEN
Solar/Wind Harmer
0.216
315839AE2-212 C
Solar/Wind Harmer
0.214
315697AD1-025 GEN
Solar/Wind Harmer
1.438
316258AE1-075 C
Solar/Wind Harmer
0.171
971445AH1-216 GEN
Solar/Wind Harmer
4.378
3151081ELIZAR1
Adder
5.744
3151091ELIZAR2
Adder
5.644
316316AC1-027 C
Solar/Wind Harmer
0.215
957871AF2-081 GEN
Solar/Wind Harmer
3.504
970673AG2-436 GEN
Solar/Wind Harmer
15.054
316322AB2-045
Solar/Wind Harmer
0.225
970683AG2-441 GEN
Solar/Wind Harmer
4.61
970681AG2-440 GEN
Solar/Wind Harmer
3.06
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
20390526W1-045 C
Solar/Wind Helper
0.278
233940AF2-379 C
Solar/Wind Helper
0.037
230434AG1-499 GEN
Solar/Wind Helper
0.136
219258KINSLEYDEP C
Solar/Wind Helper
0.045
20673828FLE_V3-070
Solar/Wind Helper
0.05
20676128MHD_W3-029
Solar/Wind Helper
0.055
209027LOR2_Q27
Solar/Wind Helper
0.551
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
316411AF1-147_GEN1
Solar/Wind Harmer
1.073
3150071POSSM 5
Adder
32.531
3150391LDYSMT3
Adder
9.161
3143526WINTERP
Solar/Wind Harmer
-0.038
316312AB1-027
Solar/Wind Harmer
0.244
316441AF1-014 GEN
Solar/Wind Harmer
0.488
944641AF1-129 GEN
Adder
30.387
316185AD1-033 GEN
Solar/Wind Harmer
0.74
3144356SAPONY
Solar/Wind Harmer
0.241
316315AB2-025 C
Solar/Wind Harmer
0.186
972185AH1-677 GEN
Adder
3.415
970099AG2-077 GEN
Solar/Wind Harmer
8.303
962571AG1-106 GEN
Solar/Wind Harmer
0.944
3144293JTRSVLE
Adder
0.139
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.621
3145783HORNRTN
Solar/Wind Harmer
0.194
3145783HORNRTN
Solar/Wind Harmer
0.078
3145796HORNRTN
Solar/Wind Harmer
-0.019
223402AF1-300 C
Solar/Wind Helper
0.386
238221AF1-254 C O1
Solar/Wind Helper
0.198
235020AA1-095 C
Solar/Wind Helper
0.031
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
233946AB2-136 GEN
Solar/Wind Helper
0.343
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.306
230511AF1-262
Solar/Wind Helper
0.009
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.096
961431AF2-434 GEN
Solar/Wind Helper
0.233
972003AH1-546 GEN
Solar/Wind Harmer
2.743
966621AG1-532 GEN
Solar/Wind Harmer
0.135
942461AE2-259 GEN
Solar/Wind Harmer
0.995
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.139
315821AE2-092 GEN
Solar/Wind Harmer
1.353
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
226910AB2-157 C
Solar/Wind Helper
0.014
237085AD2-009_GEN
Solar/Wind Helper
1.053
233933AB2-153 GEN
Solar/Wind Helper
0.141
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.046
20671928W4-073
Solar/Wind Helper
0.051
209116AE2-175 GEN
Solar/Wind Helper
0.998
961421AF2-433 GEN
Solar/Wind Helper
0.233
946691AF1-333 GEN
Solar/Wind Helper
0.23
946741AF1-338 GEN
Solar/Wind Helper
0.23
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.589
LGEELTFEXP_LGEE->PJM
CLTF
1.748
MECLTFEXP_MEC->PJM
CLTF
4.279
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.752
CPLELTFEXP_CPLE->PJM
CLTF
4.221
SIGELTFEXP_SIGE->PJM
CLTF
0.135
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.743
WECLTFEXP_WEC->PJM
CLTF
0.938
LAGNLTFEXP_LAGN->PJM
CLTF
5.819
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.807
NYPJM->LTFIMP_NY
CLTF
2.537
TVALTFEXP_TVA->PJM
CLTF
2.93

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.8 %
Rating:1331.98 MVA
Rating Type:B
MVA to Mitigate:1755.6
MW Contribution:
2.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3140676OCCOQUN
50/50
0.016
972213AH1-691 GEN
Adder
2.056
944491AF1-114 GEN
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.025
3147346CASHSCORNER
Solar/Wind Harmer
0.196
3141873WAN 176
Solar/Wind Harmer
0.017
3143873LANEXA
Solar/Wind Harmer
0.051
971281AH1-106 GEN
Solar/Wind Harmer
1.159
316159AE1-175 C
Solar/Wind Harmer
0.071
3143316POE
Solar/Wind Harmer
0.321
970657AG2-426 GEN
Solar/Wind Harmer
0.592
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
3145176PASQUOTANK
Solar/Wind Harmer
0.049
970533AG2-339 GEN
Solar/Wind Harmer
5.901
3130156CHOWAN
Solar/Wind Harmer
0.077
3130156CHOWAN
Solar/Wind Harmer
0.077
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315733AD1-074 GEN2
Solar/Wind Harmer
0.431
970601AG2-382 GEN
Solar/Wind Harmer
2.806
970581AG2-369 GEN
Solar/Wind Harmer
3.417
972205AH1-687 GEN
Adder
3.128
3146033SCOT NK
Solar/Wind Harmer
0.29
3148013FISHERV
Solar/Wind Harmer
0.037
3151881LOWMORC
Adder
0.639
3151881LOWMORC
Adder
0.628
205943AE1-185 GEN
Solar/Wind Helper
0.388
233915AB1-141 GEN
Solar/Wind Helper
0.305
228728W1-130C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
315976AC1-164 GENA
Solar/Wind Harmer
0.883
316169AC1-164_GENC
Solar/Wind Harmer
0.763
3142946ENON
Solar/Wind Harmer
0.008
316294AC1-161 GEN
Solar/Wind Harmer
1.396
316349AD2-085 GEN
Solar/Wind Harmer
0.053
3146456SLIGO L269
Solar/Wind Harmer
1.414
3146386ELIZ CT
Solar/Wind Harmer
0.079
316336AC2-165 C
Solar/Wind Harmer
3.964
315742AE1-103 GEN
Solar/Wind Harmer
1.163
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
970933AG2-581 GEN
Solar/Wind Harmer
6.095
316365GEN2_N
Solar/Wind Harmer
0.167
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.864
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
237080AD1-060 GEN
Solar/Wind Helper
0.222
3150021OMF B
50/50
0.213
3150231REMNGT3
50/50
0.781
3150241REMNGT4
50/50
13.296
972199AH1-684 GEN
50/50
2.016
963691AG1-221 GEN
Solar/Wind Harmer
2.31
3150371LDYSMT1
Adder
12.232
971781AH1-399 GEN
Solar/Wind Harmer
0.117
316473AC1-191 GEN
Solar/Wind Harmer
0.29
3142416OLDCHRC
Solar/Wind Harmer
0.82
3141766HARMONY
Solar/Wind Harmer
1.127
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3142946ENON
Solar/Wind Harmer
0.028
970133AG2-095 GEN
Solar/Wind Harmer
0.793
315813AE1-149 C
Solar/Wind Harmer
4.327
3145336SMITFLD
Solar/Wind Harmer
0.032
316017AA1-139 ULT1
Solar/Wind Harmer
0.043
970053AG2-049 GEN
50/50
2.019
3150381LDYSMT2
Adder
12.153
315651AD1-115 GEN
Solar/Wind Harmer
0
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151211GRAVEL5
Adder
5.855
316311AC2-079 GEN
Solar/Wind Harmer
2.299
313526AB2-022
Solar/Wind Harmer
0.042
3146396TANGLEW
Solar/Wind Harmer
0.218
315814AE2-033 C
Solar/Wind Harmer
6.193
3146206CASHIE
Solar/Wind Harmer
0.075
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.148
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
971845AH1-439 GEN
Solar/Wind Harmer
3.318
316486AD2-202 GEN
Solar/Wind Harmer
0.074
961791AG1-021 GEN
Solar/Wind Harmer
0.691
316274AC1-208 GEN
Solar/Wind Harmer
0.369
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
3148463FAIRFLD
Solar/Wind Harmer
0.06
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
959381AF2-229 GEN
Solar/Wind Helper
0.257
232432Z2-076 GEN
Solar/Wind Helper
0.04
230407AD2-065 C
Solar/Wind Helper
0.024
20720728JCB_W1-129
Solar/Wind Helper
0.034
3150011OMF A
50/50
0.213
3150221REMNGT2
50/50
13.208
3150211REMNGT1
50/50
13.121
972201AH1-685 GEN
50/50
2.279
316447AC1-158 HLD
Solar/Wind Harmer
1.006
972197AH1-683 GEN
Adder
1.977
972135AH1-637 GEN
Solar/Wind Harmer
0.78
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.208
316192AB2-158 GEN
Solar/Wind Harmer
0.497
958261AF2-120 GEN
Solar/Wind Harmer
2.855
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3142433PROV 92
Solar/Wind Harmer
0.336
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
315975AC1-164 GENB
Solar/Wind Harmer
0.026
3145336SMITFLD
Solar/Wind Harmer
0.324
316375AC2-012 GEN
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.08
3145663CRESWEL
Solar/Wind Harmer
0.214
970937AG2-583 GEN
Solar/Wind Harmer
4.632
3146206CASHIE
Solar/Wind Harmer
0.075
316023GEN1_S
Solar/Wind Harmer
0.167
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.335
3145683EARLEYS
Solar/Wind Harmer
0.074
3147043LAWRENC
Adder
0.663
316131AB2-060 GEN
Solar/Wind Harmer
0.221
3146083TARBORO
Solar/Wind Harmer
0.07
316359AB2-059 GEN
Solar/Wind Harmer
0.245
3142053HEARTS
Solar/Wind Harmer
0.121
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
203975AE1-071-GEN
Solar/Wind Helper
1.719
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
219766PARADISE C
Solar/Wind Helper
0.032
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
218440SUMMTASSOC C
Solar/Wind Helper
0.01
217208PARK ELE C
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.051
3150091POSSM6B
50/50
0.849
316045AC1-158 PL2
Solar/Wind Harmer
1.464
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316156AD2-030 GEN
Solar/Wind Harmer
0.062
3150671DARBY 1
Adder
6.03
971223AH1-071 GEN
Solar/Wind Harmer
0.889
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
315835AF2-110_GEN
Solar/Wind Harmer
0.547
316313AB2-026
Solar/Wind Harmer
0.049
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.435
316065AD1-022 GEN
Solar/Wind Harmer
3.468
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.026
3146776BUCKING
Solar/Wind Harmer
0.293
3146776BUCKING
Solar/Wind Harmer
0.024
972193AH1-681 GEN
Adder
1.64
316005AA1-067
Solar/Wind Harmer
0.076
3145453TOT5
Solar/Wind Harmer
0.097
961601AG1-000A GEN
Solar/Wind Harmer
1.225
964791AG1-342 GEN
Solar/Wind Harmer
1.319
316118AC1-105 GEN
Solar/Wind Harmer
0.174
971761AH1-387 GEN
Solar/Wind Harmer
1.229
942751AE2-291 GEN
Solar/Wind Harmer
3.269
232436AB1-176 C
Solar/Wind Helper
0.027
234036AF2-325 C
Solar/Wind Helper
0.025
233994AC2-023 GEN
Solar/Wind Helper
0.579
3138216PACIFIC
Solar/Wind Harmer
0.025
3150411LDYSMT5
Adder
12.698
972215AH1-692 GEN
Adder
2.056
316164AC1-076 GEN
Solar/Wind Harmer
0.129
3141813NORNECK
Solar/Wind Harmer
0.087
970189AG2-124 GEN
Solar/Wind Harmer
2.502
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971283AH1-107 GEN
Solar/Wind Harmer
1.159
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3151191GRAVEL3
Adder
5.855
3146406KITTY HAWK
Solar/Wind Harmer
0.01
971967AH1-528 GEN
Solar/Wind Harmer
12.296
315732AD1-074 GEN1
Solar/Wind Harmer
0.431
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
3.973
316463AE2-346 GEN
Solar/Wind Harmer
0.064
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3137643SOCKMAN
Solar/Wind Harmer
0.293
315652AC1-086 GEN
Solar/Wind Harmer
8.072
316426AA2-053 GEN
Solar/Wind Harmer
0.245
946301AF1-294 GEN
Solar/Wind Harmer
1.421
3144303KENBRDG
Solar/Wind Harmer
0.057
3150101POSSM6S
50/50
1.293
3150301M RUN C
Adder
13.329
3150401LDYSMT4
Adder
12.659
3141906WESTMOR
Solar/Wind Harmer
0.036
3147666LOUISA
Solar/Wind Harmer
0.204
3141873WAN 176
Solar/Wind Harmer
1.502
3141843SHACKLE
Adder
0.431
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316458AB2-190 GEN2
Solar/Wind Harmer
0.439
961611AG1-000B GEN
Solar/Wind Harmer
2.178
3151171GRAVELC
Adder
1.14
970657AG2-426 GEN
Solar/Wind Harmer
1.809
3144873MCLAUGH
Solar/Wind Harmer
0.002
316246AF1-032 C
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.014
3146626S HERTFORD
Solar/Wind Harmer
0.078
3156081AA2-088 GEN
Solar/Wind Harmer
0
970917AG2-570 GEN
Solar/Wind Harmer
6.668
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3146926FARMVIL
Solar/Wind Harmer
0.044
3145933PARMELE
Solar/Wind Harmer
0.072
970257AG2-171 GEN
Solar/Wind Harmer
2.288
971775AH1-396 GEN
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3148013FISHERV
Solar/Wind Harmer
0.065
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
235067AD1-061 GEN
Solar/Wind Helper
0.282
3150281M RUN A
Adder
13.337
316044AC1-158 PL1
Solar/Wind Harmer
0.458
316254AC1-120 GEN1
Solar/Wind Harmer
3.292
3147666LOUISA
Solar/Wind Harmer
0.355
316404AE1-155 C
Solar/Wind Harmer
0
3151751LOISA D
Adder
5.59
3138133OCRAN
Solar/Wind Harmer
0.051
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
0.008
3143226MDLTHAN
Solar/Wind Harmer
0.083
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.459
961611AG1-000B GEN
Solar/Wind Harmer
4.282
3151171GRAVELC
Adder
0.867
316381AD1-082 GEN
Solar/Wind Harmer
0.082
3150981CHESPKA
Adder
1.005
319010AE1-072 C
Solar/Wind Harmer
0.398
3130156CHOWAN
Solar/Wind Harmer
0.077
315816AE2-034 GEN
Solar/Wind Harmer
0.327
971163AH1-040 GEN
Solar/Wind Harmer
6.123
315737AD1-076 GEN
Solar/Wind Harmer
0.97
970087AG2-069 GEN
Solar/Wind Harmer
5.959
957481AF2-042 GEN
Solar/Wind Harmer
19.733
315693AD1-088 GEN
Solar/Wind Harmer
3.538
3146926FARMVIL
Solar/Wind Harmer
0.044
971563AH1-280 GEN
Solar/Wind Harmer
0.768
970685AG2-442 GEN
Solar/Wind Harmer
5.367
3146293MARTNCO
Solar/Wind Harmer
0.066
971377AH1-170 GEN
Solar/Wind Harmer
0.762
315785AD2-033 C
Solar/Wind Harmer
0.577
3146233WITAKRS
Solar/Wind Harmer
0.277
3145493TOT1
Solar/Wind Harmer
0.309
208835TUHI V3-051
Solar/Wind Helper
0.017
23777901MDS_W4-102
Solar/Wind Helper
0.106
3150181POSSMC2
50/50
1.151
3150181POSSMC2
50/50
1.141
3150181POSSMC2
50/50
1.141
316450AC1-158 RIC
Solar/Wind Harmer
0.122
972195AH1-682 GEN
Adder
1.66
315673AE1-157 GEN
Solar/Wind Harmer
6.386
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.912
3150341NORNECKC1
Adder
0.905
966001AG1-469 GEN
Solar/Wind Harmer
0.051
3151731LOISA B
Adder
5.59
3150681DARBY 2
Adder
6.037
316033AB2-134 GEN
Solar/Wind Harmer
0
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.192
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.128
316388AE2-253 GEN
Solar/Wind Harmer
0.249
3137176SLIGO L2192
Solar/Wind Harmer
0.318
3130086AYDLETT
Solar/Wind Harmer
0.319
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146626S HERTFORD
Solar/Wind Harmer
0.078
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
970301AG2-198 GEN
Solar/Wind Harmer
3.132
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.091
3145933PARMELE
Solar/Wind Harmer
0.143
3145933PARMELE
Solar/Wind Harmer
0.072
970323AG2-213 GEN
Solar/Wind Harmer
3.051
3145493TOT1
Solar/Wind Harmer
0.161
316049AB1-081 GEN
Solar/Wind Harmer
0.392
3132123MT JACKSON
Solar/Wind Harmer
0.182
970117AG2-086 GEN
Solar/Wind Harmer
1.398
970117AG2-086 GEN
Solar/Wind Harmer
0.932
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
235062AE1-101 C1
Solar/Wind Helper
1.069
232424Y1-079 C
Solar/Wind Helper
0.07
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.924
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.077
3146206CASHIE
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
316181AB2-040 GEN
Solar/Wind Harmer
0.105
3147043LAWRENC
Solar/Wind Harmer
0.044
316478AD1-087 GEN
Solar/Wind Harmer
0.251
3147133PAMPLIN
Solar/Wind Harmer
0.226
972255AH1-712 GEN
Adder
36.701
959311AF2-222 GEN
Solar/Wind Harmer
6.364
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316283AC2-100 C
Solar/Wind Harmer
0.124
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
3152111X4-039 GT1
50/50
1.844
3150151POSSMC1
50/50
1.141
3150151POSSMC1
50/50
1.141
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3150291M RUN B
Adder
13.23
3150331BIRCHWDA
Adder
16.601
316223AC1-118
Solar/Wind Harmer
0.064
3132273ORANGE
Solar/Wind Harmer
0.018
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.898
3150921YORKTN3
Adder
2.065
3144536CHRHLND
Solar/Wind Harmer
0.012
944581AF1-123 GEN
Solar/Wind Harmer
18.116
3146516WINFALL
Solar/Wind Harmer
0.079
944011AF1-069 GEN
Solar/Wind Harmer
4.7
315735AD1-075 GEN1
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
3146263WOODLND
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.073
316011AB1-132 GEN
Solar/Wind Harmer
1.331
3146776BUCKING
Solar/Wind Harmer
0.026
970221AG2-151 GEN
Solar/Wind Harmer
3.81
961601AG1-000A GEN
Solar/Wind Harmer
4.902
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
270494AE1-108_GEN
Solar/Wind Harmer
0.797
3151861LOWMORA
Adder
0.644
237038AE2-054 C
Solar/Wind Helper
0.174
233935AB2-179 C
Solar/Wind Helper
0.775
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233923SMA
Solar/Wind Helper
0.453
3150151POSSMC1
50/50
1.141
316170AC1-121 GEN2
Solar/Wind Harmer
1.13
316337AD2-073 GEN
Solar/Wind Harmer
0.076
3141726DUNNSVL
Solar/Wind Harmer
0.347
962861AG1-135 GEN
Solar/Wind Harmer
2.759
3150851SPRUNCC
Adder
0.385
316132AB2-190 GEN1
Solar/Wind Harmer
0.439
315773AC2-141 GEN
Solar/Wind Harmer
2.95
316036AC1-147 C
Solar/Wind Harmer
0.014
316093AE2-104_GEN
Solar/Wind Harmer
1.34
3146516WINFALL
Solar/Wind Harmer
0.255
3146516WINFALL
Solar/Wind Harmer
0.079
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.667
315607AA1-063A GEN
Solar/Wind Harmer
0.149
3146263WOODLND
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.029
316494AC1-189 GEN
Solar/Wind Harmer
0.237
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
237001AB1-127_GEN
Solar/Wind Helper
0.308
233918AB1-142 GEN
Solar/Wind Helper
0.305
316327AA2-057 GEN
Solar/Wind Harmer
0.104
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205956AE1-196_GEN
Solar/Wind Helper
0.386
233901CHERRYDALE C
Solar/Wind Helper
0.14
20715028HAN_X4-015
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
3150071POSSM 5
50/50
52.154
3150391LDYSMT3
Adder
12.635
316312AB1-027
Solar/Wind Harmer
0.15
3143526WINTERP
Solar/Wind Harmer
0.434
944641AF1-129 GEN
Adder
39.347
3144356SAPONY
Solar/Wind Harmer
0.656
316315AB2-025 C
Solar/Wind Harmer
0.063
972185AH1-677 GEN
Adder
4.323
970099AG2-077 GEN
Solar/Wind Harmer
7.893
962571AG1-106 GEN
Solar/Wind Harmer
1.044
3145783HORNRTN
Solar/Wind Harmer
1.297
3145783HORNRTN
Solar/Wind Harmer
1.037
3145783HORNRTN
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.218
3144293JTRSVLE
Adder
0.172
315724AD1-057 GEN
Solar/Wind Harmer
1.362
3145603CNETO
Solar/Wind Harmer
0.065
962561AG1-105 GEN
Solar/Wind Harmer
3.315
316263AC1-034 GEN
Solar/Wind Harmer
2.619
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
233946AB2-136 GEN
Solar/Wind Helper
0.343
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
315747AE2-019 GEN
50/50
13.161
3150081POSSM6A
50/50
0.849
972217AH1-693 GEN
50/50
1.753
3141196NOKESVL
Solar/Wind Harmer
0.428
3150351NORNECKC2
Adder
0.883
3151761LOISA E
Adder
11.397
3151721LOISA A
Adder
5.561
316075AC2-137 C
Solar/Wind Harmer
0.022
315778AD1-151 GEN
Solar/Wind Harmer
6.568
3144216WINCHST
Adder
0.309
3151101ELIZAR3
Adder
7.476
944601AF1-125 GEN
Solar/Wind Harmer
17.837
3143336POWHATN
Solar/Wind Harmer
1.198
3145823KELFORD
Solar/Wind Harmer
0.073
972003AH1-546 GEN
Solar/Wind Harmer
2.538
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.37
964241AG1-285 GEN
Solar/Wind Harmer
4.743
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
2.442
315821AE2-092 GEN
Solar/Wind Harmer
0
971683AH1-343 GEN
Solar/Wind Harmer
2.374
316123AC1-075 GEN
Solar/Wind Harmer
0.082
226910AB2-157 C
Solar/Wind Helper
0.021
237085AD2-009_GEN
Solar/Wind Helper
0.975
233933AB2-153 GEN
Solar/Wind Helper
0.141
3141426STAFORD
Solar/Wind Harmer
0.023
3141913WHIT STONE
Solar/Wind Harmer
0.085
971285AH1-108 GEN
Adder
0.63
315697AD1-025 GEN
Solar/Wind Harmer
0.088
971445AH1-216 GEN
Solar/Wind Harmer
5.713
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.077
957871AF2-081 GEN
Solar/Wind Harmer
3.983
316258AE1-075 C
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
9.667
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
316210AC1-098 GEN
Solar/Wind Harmer
0.664
970683AG2-441 GEN
Solar/Wind Harmer
4.325
970681AG2-440 GEN
Solar/Wind Harmer
2.871
970831AG2-522 GEN
Solar/Wind Harmer
3.061
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
957861AF2-080 GEN
Solar/Wind Harmer
3.026
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
3148133STUARTS
Solar/Wind Harmer
0.039
20390526W1-045 C
Solar/Wind Helper
0.253
233940AF2-379 C
Solar/Wind Helper
0.037
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
20673828FLE_V3-070
Solar/Wind Helper
0.05
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
972223AH1-696 GEN
50/50
9.014
3141346CRANES
50/50
0.127
971685AH1-345 GEN
Solar/Wind Harmer
0.729
972219AH1-694 GEN
Adder
1.423
3150351NORNECKC2
Adder
0.868
3143526WINTERP
Solar/Wind Harmer
0.434
944631AF1-128 GEN
Adder
39.784
971317AH1-138 GEN
Solar/Wind Harmer
0.617
315671AE2-027_GEN
Solar/Wind Harmer
0.001
944591AF1-124 GEN
Solar/Wind Harmer
18.181
316072AD1-144
Solar/Wind Harmer
0.029
939411AE1-173 GEN
Solar/Wind Harmer
34.104
940641AE2-051 GEN
Solar/Wind Harmer
6.384
3143336POWHATN
Solar/Wind Harmer
1.41
941031AE2-094 GEN
Solar/Wind Harmer
14.385
971547AH1-271 GEN
Solar/Wind Harmer
1.603
960081AF2-299 GEN
Solar/Wind Harmer
0.713
3145823KELFORD
Solar/Wind Harmer
0.073
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
972277AH1-723 GEN
Adder
42.768
316129AC1-054 GEN
Solar/Wind Harmer
0.267
316034AC1-036 C
Solar/Wind Harmer
0.005
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.047
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970401AG2-262 GEN
Solar/Wind Harmer
0.403
3147983MERCK5
Solar/Wind Harmer
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.485
233944AB2-135 GEN
Solar/Wind Helper
0.357
232408W1-005 C
Solar/Wind Helper
0.305
219907AC1-030 C
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.011
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
218428ETC SOLAR C
Solar/Wind Helper
0.003
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.047
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
209116AE2-175 GEN
Solar/Wind Helper
1.008
961421AF2-433 GEN
Solar/Wind Helper
0.237
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.009
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
230433AD2-135 GEN
Solar/Wind Helper
0.01
214067T20SOLAR
Solar/Wind Helper
0.007
207459AE1-142 C O1
Solar/Wind Helper
0.17
20675428EAM_W2-061
Solar/Wind Helper
0.009
233950AC2-186 GEN
Solar/Wind Helper
0.07
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
207454AA2-184 E
Solar/Wind Helper
0.181
217169METRODIV C
Solar/Wind Helper
0.002
20676428JCR_X2-075
Solar/Wind Helper
0.039
20675128HRM_W1-127
Solar/Wind Helper
0.017
209029WAYMART-WD
Solar/Wind Helper
0.444
959421AF2-233 GEN
Solar/Wind Helper
0.233
233997TMININ_4.2
Solar/Wind Helper
0.124
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
207442AE1-156 GEN
Solar/Wind Helper
0.189
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
957921AF2-086 GEN
Solar/Wind Helper
0.234
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
209071AE2-133 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
219919AE1-041 FULL
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
20674928WA_W3-044
Solar/Wind Helper
0.057
20676328BVR_Y1-020
Solar/Wind Helper
0.015
207518AF1-320_GEN
Solar/Wind Helper
0.902
209137AF2-361 C
Solar/Wind Helper
0.711
20676128MHD_W3-029
Solar/Wind Helper
0.056
209027LOR2_Q27
Solar/Wind Helper
0.559
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
961261AF2-417 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.163
228729W2-030 C
Solar/Wind Helper
0.065
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
207530AG1-191 GEN
Solar/Wind Helper
0.038
207439AE1-081 C O1
Solar/Wind Helper
0.011
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
219912AD2-042 GEN
Solar/Wind Helper
0.089
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
20674328GAR_V4-001
Solar/Wind Helper
0.013
946751AF1-339 GEN
Solar/Wind Helper
0.234
232406W1-004 FULL
Solar/Wind Helper
0.305
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
959431AF2-234 GEN
Solar/Wind Helper
0.467
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674828DL_W4-046
Solar/Wind Helper
0.005
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
961431AF2-434 GEN
Solar/Wind Helper
0.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.822
LGEELTFEXP_LGEE->PJM
CLTF
1.798
MECLTFEXP_MEC->PJM
CLTF
4.431
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.532
CPLELTFEXP_CPLE->PJM
CLTF
5.053
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.552
WECLTFEXP_WEC->PJM
CLTF
0.958
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.329
NYPJM->LTFIMP_NY
CLTF
2.582
TVALTFEXP_TVA->PJM
CLTF
3.177

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.4 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1720.2
MW Contribution:
1.92
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3142366NRTHEST
Adder
0.249
3150691DARBY 3
Adder
5.482
3150701DARBY 4
Adder
5.469
315976AC1-164 GENA
Solar/Wind Harmer
1.94
316169AC1-164_GENC
Solar/Wind Harmer
1.676
3142946ENON
Solar/Wind Harmer
-0.001
316294AC1-161 GEN
Solar/Wind Harmer
2.694
316083AB2-161 GEN
Solar/Wind Harmer
1.35
316336AC2-165 C
Solar/Wind Harmer
5.168
316349AD2-085 GEN
Solar/Wind Harmer
0.734
3146456SLIGO L269
Solar/Wind Harmer
0.976
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.483
316433W1029_GEN2
Solar/Wind Harmer
1.483
315742AE1-103 GEN
Solar/Wind Harmer
1.923
3146376EDENTON
Solar/Wind Harmer
0.24
3146376EDENTON
Solar/Wind Harmer
0.24
970933AG2-581 GEN
Solar/Wind Harmer
7.508
316365GEN2_N
Solar/Wind Harmer
0.531
3146173TUNIS
Solar/Wind Harmer
-0.008
3150221REMNGT2
Adder
12.544
3150211REMNGT1
Adder
12.461
972201AH1-685 GEN
Adder
2.164
316447AC1-158 HLD
Solar/Wind Harmer
2.175
315683AE1-153 C
Solar/Wind Harmer
9.352
316192AB2-158 GEN
Solar/Wind Harmer
1.118
972197AH1-683 GEN
Adder
1.696
966881AG1-559 GEN
Solar/Wind Harmer
0.092
972135AH1-637 GEN
Solar/Wind Harmer
0.886
958261AF2-120 GEN
Solar/Wind Harmer
3.344
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3142416OLDCHRC
Solar/Wind Harmer
-0.008
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.997
3142433PROV 92
Solar/Wind Harmer
-0.034
315975AC1-164 GENB
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3145336SMITFLD
Solar/Wind Harmer
-0.033
316375AC2-012 GEN
Solar/Wind Harmer
2.873
3146456SLIGO L269
Solar/Wind Harmer
-0.008
970937AG2-583 GEN
Solar/Wind Harmer
5.831
3145663CRESWEL
Solar/Wind Harmer
-0.022
316023GEN1_S
Solar/Wind Harmer
0.531
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.054
3150301M RUN C
Adder
13.419
3150281M RUN A
Adder
13.427
316254AC1-120 GEN1
Solar/Wind Harmer
3.829
316044AC1-158 PL1
Solar/Wind Harmer
0.989
3147666LOUISA
Solar/Wind Harmer
-0.038
3151751LOISA D
Adder
5.418
957971AF2-091 GEN
Solar/Wind Harmer
0.887
316404AE1-155 C
Solar/Wind Harmer
1.647
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3138133OCRAN
Solar/Wind Harmer
-0.005
315662AE1-191 GEN
Solar/Wind Harmer
1.027
316280AD1-041 GEN
Solar/Wind Harmer
0.642
3143096IRON208
Adder
0.318
3142543TWELFTH
Solar/Wind Harmer
-0.001
971069AG2-661 GEN
Solar/Wind Harmer
1.332
3138126ROCKLANDING
Solar/Wind Harmer
0.026
316369SG1_INVT
Solar/Wind Harmer
1.5
961611AG1-000B GEN
Solar/Wind Harmer
4.139
3151171GRAVELC
Adder
0.793
316381AD1-082 GEN
Solar/Wind Harmer
0.761
3150981CHESPKA
Adder
0.923
319010AE1-072 C
Solar/Wind Harmer
1.667
315611Z1-036_GEN2
Solar/Wind Harmer
1.999
3130156CHOWAN
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.645
971163AH1-040 GEN
Solar/Wind Harmer
7.498
315737AD1-076 GEN
Solar/Wind Harmer
1.504
3146926FARMVIL
Solar/Wind Harmer
-0.005
970087AG2-069 GEN
Solar/Wind Harmer
7.37
957481AF2-042 GEN
Solar/Wind Harmer
24.507
971377AH1-170 GEN
Solar/Wind Harmer
0.98
316450AC1-158 RIC
Solar/Wind Harmer
0.264
3150181POSSMC2
Adder
0.854
3150181POSSMC2
Adder
0.847
3150181POSSMC2
Adder
0.847
966001AG1-469 GEN
Solar/Wind Harmer
0.179
3151731LOISA B
Adder
5.418
972195AH1-682 GEN
Adder
1.424
315673AE1-157 GEN
Solar/Wind Harmer
6.743
972189AH1-679 GEN
Adder
1.303
3150341NORNECKC1
Adder
0.808
3150341NORNECKC1
Adder
0.801
316487AF1-042 GEN
Solar/Wind Harmer
1.134
3150681DARBY 2
Adder
5.463
316033AB2-134 GEN
Solar/Wind Harmer
2.708
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.02
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.556
316388AE2-253 GEN
Solar/Wind Harmer
0.556
3137176SLIGO L2192
Solar/Wind Harmer
-0.033
3130086AYDLETT
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
970301AG2-198 GEN
Solar/Wind Harmer
3.93
313506AB2-031 GEN
Solar/Wind Harmer
0.625
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.064
970323AG2-213 GEN
Solar/Wind Harmer
3.839
237006AB1-125 GEN
Solar/Wind Helper
0.127
223401AF1-299 GEN
Solar/Wind Helper
0.38
232424Y1-079 C
Solar/Wind Helper
0.092
963691AG1-221 GEN
Solar/Wind Harmer
2.518
3150241REMNGT4
Adder
12.627
972199AH1-684 GEN
Adder
1.915
3150371LDYSMT1
Adder
10.492
966881AG1-559 GEN
Solar/Wind Harmer
0.268
971781AH1-399 GEN
Solar/Wind Harmer
0.542
316473AC1-191 GEN
Solar/Wind Harmer
0.93
961951AG1-038 GEN
Solar/Wind Harmer
1.134
3142416OLDCHRC
Solar/Wind Harmer
0.866
3141766HARMONY
Solar/Wind Harmer
0.761
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
0.951
315813AE1-149 C
Solar/Wind Harmer
5.222
3145336SMITFLD
Solar/Wind Harmer
-0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.667
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.956
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
972255AH1-712 GEN
Adder
35.633
316181AB2-040 GEN
Solar/Wind Harmer
1.085
3147043LAWRENC
Solar/Wind Harmer
-0.005
3147133PAMPLIN
Solar/Wind Harmer
-0.024
316478AD1-087 GEN
Solar/Wind Harmer
0.668
959311AF2-222 GEN
Solar/Wind Harmer
8.024
23777801MSM_W1-116
Solar/Wind Helper
0.111
3146173TUNIS
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.209
316170AC1-121 GEN2
Solar/Wind Harmer
1.276
3150151POSSMC1
Adder
0.847
316337AD2-073 GEN
Solar/Wind Harmer
0.234
3141726DUNNSVL
Solar/Wind Harmer
-0.034
962861AG1-135 GEN
Solar/Wind Harmer
3.234
3150851SPRUNCC
Adder
0.35
316132AB2-190 GEN1
Solar/Wind Harmer
0.85
315773AC2-141 GEN
Solar/Wind Harmer
3.486
316036AC1-147 C
Solar/Wind Harmer
0.224
316093AE2-104_GEN
Solar/Wind Harmer
2.397
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.501
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3138216PACIFIC
Solar/Wind Harmer
-0.003
316164AC1-076 GEN
Solar/Wind Harmer
0.844
3150411LDYSMT5
Adder
10.892
972215AH1-692 GEN
Adder
1.763
3141813NORNECK
Solar/Wind Harmer
-0.009
316233AE1-074 FULL
Solar/Wind Harmer
0.231
971283AH1-107 GEN
Solar/Wind Harmer
1.394
957601AF2-054 GEN
Solar/Wind Harmer
0.256
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3151191GRAVEL3
Adder
5.356
315833AF1-017_GEN
Solar/Wind Harmer
1.571
316018AA1-139 ULT2
Solar/Wind Harmer
0.707
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.999
971967AH1-528 GEN
Solar/Wind Harmer
15.148
315732AD1-074 GEN1
Solar/Wind Harmer
1.599
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.913
316463AE2-346 GEN
Solar/Wind Harmer
0.126
3145513AHOSKIE
Solar/Wind Harmer
0.068
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.031
316426AA2-053 GEN
Solar/Wind Harmer
0.782
315652AC1-086 GEN
Solar/Wind Harmer
8.728
946301AF1-294 GEN
Solar/Wind Harmer
1.983
316174AB2-169 GEN
Solar/Wind Harmer
1.19
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151861LOWMORA
Adder
0.647
23779801AA1-109
Solar/Wind Helper
0.182
205917AD1-020 ES
Solar/Wind Helper
0.323
205956AE1-196_GEN
Solar/Wind Helper
0.424
233901CHERRYDALE C
Solar/Wind Helper
0.184
3152111X4-039 GT1
50/50
2.013
971455AH1-223 GEN
Solar/Wind Harmer
2.518
3150291M RUN B
Adder
13.319
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.847
3150151POSSMC1
Adder
0.847
3150331BIRCHWDA
Adder
13.822
316223AC1-118
Solar/Wind Harmer
0.236
970293AG2-193 GEN
Solar/Wind Harmer
1.069
316203AE2-005 GEN
Solar/Wind Harmer
3.602
3150921YORKTN3
Adder
1.882
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
37.785
3142956BIRDNECK
Solar/Wind Harmer
0.445
316305AF2-043 C
Solar/Wind Harmer
0.248
316320Y1-086
Solar/Wind Harmer
0.482
3146516WINFALL
Solar/Wind Harmer
-0.008
944011AF1-069 GEN
Solar/Wind Harmer
4.79
315735AD1-075 GEN1
Solar/Wind Harmer
0.799
3146776BUCKING
Solar/Wind Harmer
-0.003
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
970221AG2-151 GEN
Solar/Wind Harmer
4.898
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.62
3151861LOWMORA
Adder
0.673
316006AB2-029 C
Solar/Wind Harmer
0.63
316045AC1-158 PL2
Solar/Wind Harmer
3.165
966871AG1-558 GEN
Solar/Wind Harmer
0.26
966871AG1-558 GEN
Solar/Wind Harmer
0.089
3142296MT RD221
Adder
0.244
971223AH1-071 GEN
Solar/Wind Harmer
1.073
3150671DARBY 1
Adder
5.457
315666AE1-190 GEN
Solar/Wind Harmer
0.257
316156AD2-030 GEN
Solar/Wind Harmer
0.227
316240AF1-291 C
Solar/Wind Harmer
0.254
316313AB2-026
Solar/Wind Harmer
0.224
3150991CHESPKB
Adder
0.775
3150991CHESPKB
Adder
0.756
315835AF2-110_GEN
Solar/Wind Harmer
1.03
316435W1029_GEN3
Solar/Wind Harmer
1.483
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
971761AH1-387 GEN
Solar/Wind Harmer
4.557
972187AH1-678 GEN
Adder
2.035
315614AA2-178 GEN
Solar/Wind Harmer
0.86
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
316065AD1-022 GEN
Solar/Wind Harmer
3.952
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
316140AB2-099
Solar/Wind Harmer
0.053
972193AH1-681 GEN
Adder
1.592
232436AB1-176 C
Solar/Wind Helper
0.035
3147346CASHSCORNER
Solar/Wind Harmer
0.143
972213AH1-691 GEN
Adder
1.763
944491AF1-114 GEN
Solar/Wind Harmer
2.607
971281AH1-106 GEN
Solar/Wind Harmer
1.394
3138133OCRAN
Solar/Wind Harmer
-0.003
3143873LANEXA
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.002
316382AG1-145 C
Solar/Wind Harmer
0.254
316159AE1-175 C
Solar/Wind Harmer
0.226
3143316POE
Solar/Wind Harmer
-0.033
316236AE1-162_GEN
Solar/Wind Harmer
0.251
316405AF2-144 C
Solar/Wind Harmer
0.213
970657AG2-426 GEN
Solar/Wind Harmer
0.524
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
970533AG2-339 GEN
Solar/Wind Harmer
5.483
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
972205AH1-687 GEN
Adder
3.031
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.599
970601AG2-382 GEN
Solar/Wind Harmer
3.452
970581AG2-369 GEN
Solar/Wind Harmer
4.225
946281AF1-292 GEN
Solar/Wind Harmer
0.175
3146033SCOT NK
Solar/Wind Harmer
-0.031
3151881LOWMORC
Adder
0.668
3151881LOWMORC
Adder
0.657
205943AE1-185 GEN
Solar/Wind Helper
0.425
233915AB1-141 GEN
Solar/Wind Helper
0.398
316411AF1-147_GEN1
Solar/Wind Harmer
1.196
3150071POSSM 5
Adder
38.706
3150391LDYSMT3
Adder
10.838
316312AB1-027
Solar/Wind Harmer
0.289
3143526WINTERP
Solar/Wind Harmer
-0.044
316441AF1-014 GEN
Solar/Wind Harmer
0.576
944641AF1-129 GEN
Adder
35.868
316185AD1-033 GEN
Solar/Wind Harmer
0.873
3144356SAPONY
Solar/Wind Harmer
0.285
316315AB2-025 C
Solar/Wind Harmer
0.22
972185AH1-677 GEN
Adder
4.03
970099AG2-077 GEN
Solar/Wind Harmer
9.803
315747AE2-019 GEN
50/50
14.046
3141196NOKESVL
Solar/Wind Harmer
-0.049
972217AH1-693 GEN
Adder
1.665
3151761LOISA E
Adder
11.045
3151721LOISA A
Adder
5.39
3141426STAFORD
Solar/Wind Harmer
-0.002
316468AD1-105 GEN
Solar/Wind Harmer
1.005
3141913WHIT STONE
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
0.573
957831AF2-077 GEN
Solar/Wind Harmer
0.255
315839AE2-212 C
Solar/Wind Harmer
0.253
315697AD1-025 GEN
Solar/Wind Harmer
1.697
971445AH1-216 GEN
Solar/Wind Harmer
5.168
316258AE1-075 C
Solar/Wind Harmer
0.202
3152131X4-039 ST
50/50
3.148
3152121X4-039 GT2
50/50
2
316415AF1-147_GEN2
Solar/Wind Harmer
1.196
971685AH1-345 GEN
Solar/Wind Harmer
0.962
972223AH1-696 GEN
Adder
6.689
3141346CRANES
Adder
0.097
972219AH1-694 GEN
Adder
1.221
3150351NORNECKC2
Adder
0.769
964211AG1-282 GEN
Solar/Wind Harmer
0.26
3143526WINTERP
Solar/Wind Harmer
-0.044
316314AB2-024 C
Solar/Wind Harmer
0.73
944631AF1-128 GEN
Adder
36.103
971317AH1-138 GEN
Solar/Wind Harmer
1.055
315671AE2-027_GEN
Solar/Wind Harmer
1.522
3143336POWHATN
Solar/Wind Harmer
0.99
944591AF1-124 GEN
Solar/Wind Harmer
37.921
316072AD1-144
Solar/Wind Harmer
0.167
939411AE1-173 GEN
Solar/Wind Harmer
41.429
940641AE2-051 GEN
Solar/Wind Harmer
7.765
941031AE2-094 GEN
Solar/Wind Harmer
15.288
971547AH1-271 GEN
Solar/Wind Harmer
1.973
3147623JAMES R
Solar/Wind Harmer
0.121
316077AC2-138 C
Solar/Wind Harmer
0.182
3150351NORNECKC2
Adder
0.782
316484AD2-074 GEN
Solar/Wind Harmer
2.167
316075AC2-137 C
Solar/Wind Harmer
0.23
315778AD1-151 GEN
Solar/Wind Harmer
7.492
3144216WINCHST
Adder
0.282
3143336POWHATN
Solar/Wind Harmer
0.841
3151101ELIZAR3
Adder
6.866
944601AF1-125 GEN
Solar/Wind Harmer
37.195
972003AH1-546 GEN
Solar/Wind Harmer
3.236
966621AG1-532 GEN
Solar/Wind Harmer
0.159
942461AE2-259 GEN
Solar/Wind Harmer
1.175
316317KELFORD C
Solar/Wind Harmer
0.359
3145823KELFORD
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.164
315821AE2-092 GEN
Solar/Wind Harmer
1.599
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
226910AB2-157 C
Solar/Wind Helper
0.012
962571AG1-106 GEN
Solar/Wind Harmer
1.115
3144293JTRSVLE
Adder
0.164
3145783HORNRTN
Solar/Wind Harmer
0.917
3145783HORNRTN
Solar/Wind Harmer
0.733
3145783HORNRTN
Solar/Wind Harmer
0.229
3145783HORNRTN
Solar/Wind Harmer
0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
223402AF1-300 C
Solar/Wind Helper
0.38
233930AB2-032 GEN
Solar/Wind Helper
0.302
233982AB2-133 GEN
Solar/Wind Helper
0.284
3151081ELIZAR1
Adder
6.78
3151091ELIZAR2
Adder
6.662
316316AC1-027 C
Solar/Wind Harmer
0.254
957871AF2-081 GEN
Solar/Wind Harmer
4.136
970673AG2-436 GEN
Solar/Wind Harmer
17.761
316322AB2-045
Solar/Wind Harmer
0.266
970683AG2-441 GEN
Solar/Wind Harmer
5.445
970681AG2-440 GEN
Solar/Wind Harmer
3.614
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
23544701WINZ1-113
Adder
0.24
233940AF2-379 C
Solar/Wind Helper
0.049
3147666LOUISA
Solar/Wind Harmer
-0.022
3150401LDYSMT4
Adder
10.858
3141906WESTMOR
Solar/Wind Harmer
-0.003
3141873WAN 176
Solar/Wind Harmer
1.014
3141843SHACKLE
Adder
0.389
3150861SPRUNCD
Adder
0.35
3143096IRON208
Adder
0.318
3143096IRON208
Adder
0.312
316458AB2-190 GEN2
Solar/Wind Harmer
0.85
961611AG1-000B GEN
Solar/Wind Harmer
1.766
3151171GRAVELC
Adder
1.042
970657AG2-426 GEN
Solar/Wind Harmer
1.68
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.167
316321Z2-027
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
2.574
970917AG2-570 GEN
Solar/Wind Harmer
19.76
3146926FARMVIL
Solar/Wind Harmer
-0.005
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.095
3152541MT STMG
Adder
0.592
315693AD1-088 GEN
Solar/Wind Harmer
3.916
316087AB2-174 GEN
Solar/Wind Harmer
1.111
971563AH1-280 GEN
Solar/Wind Harmer
0.967
970685AG2-442 GEN
Solar/Wind Harmer
6.757
208835TUHI V3-051
Solar/Wind Helper
0.019
233998TM1NIN_3.36
Solar/Wind Helper
0.162
232404W1-003 C
Solar/Wind Helper
0.401
20715828PEM_W1-120
Solar/Wind Helper
0.073
219276PARKLANDSO C
Solar/Wind Helper
0.068
963711AG1-223 GEN
Solar/Wind Helper
0.049
20715228NPK_W1-113
Solar/Wind Helper
0.059
20720528MAN_W1-024
Solar/Wind Helper
0.021
219919AE1-041 FULL
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.022
20676328BVR_Y1-020
Solar/Wind Helper
0.02
20674928WA_W3-044
Solar/Wind Helper
0.073
207518AF1-320_GEN
Solar/Wind Helper
1.157
209137AF2-361 C
Solar/Wind Helper
0.867
960081AF2-299 GEN
Solar/Wind Harmer
0.881
972277AH1-723 GEN
Adder
41.523
3145823KELFORD
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.164
3144293JTRSVLE
Adder
0.13
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.008
316034AC1-036 C
Solar/Wind Harmer
0.142
205916AD1-020 GEN
Solar/Wind Helper
1.501
233944AB2-135 GEN
Solar/Wind Helper
0.467
232408W1-005 C
Solar/Wind Helper
0.401
219907AC1-030 C
Solar/Wind Helper
0.026
20716028EGP_W2-019
Solar/Wind Helper
0.014
218428ETC SOLAR C
Solar/Wind Helper
0.004
219908AB1-139 C
Solar/Wind Helper
0.055
20673628F1S_V4-069
Solar/Wind Helper
0.022
207484AF2-139 C O1
Solar/Wind Helper
0.062
20676228FRD_X1-012
Solar/Wind Helper
0.068
20675728RH_W2-091
Solar/Wind Helper
0.06
20675828AU_W4-064
Solar/Wind Helper
0.022
946731AF1-337 GEN
Solar/Wind Helper
0.298
315607AA1-063A GEN
Solar/Wind Harmer
0.787
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
233918AB1-142 GEN
Solar/Wind Helper
0.398
228729W2-030 C
Solar/Wind Helper
0.085
219686LUMSOLAR_N C
Solar/Wind Helper
0.031
219348LDSOLAR C
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.121
20671828STAW2-080
Solar/Wind Helper
0.02
217209CENTRL HS C
Solar/Wind Helper
0.006
207530AG1-191 GEN
Solar/Wind Helper
0.049
207439AE1-081 C O1
Solar/Wind Helper
0.014
211065PSPA IPP
Solar/Wind Helper
0.11
961301AF2-421 GEN
Solar/Wind Helper
0.31
963151AG1-164 GEN
Solar/Wind Helper
0.31
961341AF2-425 GEN
Solar/Wind Helper
0.303
212507AE2-042_GEN
Solar/Wind Helper
1.059
237001AB1-127_GEN
Solar/Wind Helper
0.222
234036AF2-325 C
Solar/Wind Helper
0.033
233994AC2-023 GEN
Solar/Wind Helper
0.76
219912AD2-042 GEN
Solar/Wind Helper
0.116
219607WPEMNERT C
Solar/Wind Helper
0.062
219304NAMERICA C
Solar/Wind Helper
0.101
20674328GAR_V4-001
Solar/Wind Helper
0.017
946751AF1-339 GEN
Solar/Wind Helper
0.298
970053AG2-049 GEN
Adder
1.705
315651AD1-115 GEN
Solar/Wind Harmer
4.548
3150381LDYSMT2
Adder
10.424
3141783LANCAST
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.193
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3151201GRAVEL4
Adder
5.424
3151221GRAVEL6
Adder
5.418
3151211GRAVEL5
Adder
5.356
316311AC2-079 GEN
Solar/Wind Harmer
4.173
313526AB2-022
Solar/Wind Harmer
0.221
3146396TANGLEW
Solar/Wind Harmer
0.151
315814AE2-033 C
Solar/Wind Harmer
7.588
971845AH1-439 GEN
Solar/Wind Harmer
4.206
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.197
961941AG1-037 GEN
Solar/Wind Harmer
0.059
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
961791AG1-021 GEN
Solar/Wind Harmer
0.967
316486AD2-202 GEN
Solar/Wind Harmer
0.195
972257AH1-713 GEN
Adder
0.696
237030AB1-096 C
Solar/Wind Helper
0.069
237025AB1-124 C
Solar/Wind Helper
0.169
232432Z2-076 GEN
Solar/Wind Helper
0.053
228728W1-130C
Solar/Wind Helper
0.042
227927V4-067C
Solar/Wind Helper
0.008
219615MILLCREEK C
Solar/Wind Helper
0.02
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.121
961261AF2-417 GEN
Solar/Wind Helper
0.309
212266LOR1
Solar/Wind Helper
0.208
959431AF2-234 GEN
Solar/Wind Helper
0.595
208835TUHI V3-051
Solar/Wind Helper
0.019
233950AC2-186 GEN
Solar/Wind Helper
0.092
219921AF1-264
Solar/Wind Helper
0.039
219914AD2-027 C
Solar/Wind Helper
0.089
218660EHAMPSOLAR C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.031
207454AA2-184 E
Solar/Wind Helper
0.234
217169METRODIV C
Solar/Wind Helper
0.003
963161AG1-165 GEN
Solar/Wind Helper
0.31
208972BECR K09
Solar/Wind Helper
0.228
961331AF2-424 GEN
Solar/Wind Helper
0.303
209071AE2-133 GEN
Solar/Wind Helper
0.054
237002AB1-128_GEN
Solar/Wind Helper
0.213
235067AD1-061 GEN
Solar/Wind Helper
0.193
970257AG2-171 GEN
Solar/Wind Harmer
0.181
232428Y3-058 C
Solar/Wind Helper
0.267
234015AF2-250 C
Solar/Wind Helper
0.03
230433AD2-135 GEN
Solar/Wind Helper
0.013
214067T20SOLAR
Solar/Wind Helper
0.009
207459AE1-142 C O1
Solar/Wind Helper
0.221
20675428EAM_W2-061
Solar/Wind Helper
0.012
235062AE1-101 C1
Solar/Wind Helper
0.75
20715028HAN_X4-015
Solar/Wind Helper
0.044
207445AB1-138_GEN
Solar/Wind Helper
0.079
20720628TIN_W1-124
Solar/Wind Helper
0.144
20675528CPH_W2-050
Solar/Wind Helper
0.085
20676428JCR_X2-075
Solar/Wind Helper
0.051
226929AD2-058 GEN
Solar/Wind Helper
0.066
20675128HRM_W1-127
Solar/Wind Helper
0.022
209029WAYMART-WD
Solar/Wind Helper
0.567
959421AF2-233 GEN
Solar/Wind Helper
0.297
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.625
205932AD2-116_GEN
Solar/Wind Helper
0.424
232426Y1-080 FULL
Solar/Wind Helper
0.031
233996TM1833_GEN
Solar/Wind Helper
0.162
219766PARADISE C
Solar/Wind Helper
0.042
20714528FRN_Y2-051
Solar/Wind Helper
0.043
219680HOPEWELLV C1
Solar/Wind Helper
0.002
218440SUMMTASSOC C
Solar/Wind Helper
0.012
217208PARK ELE C
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.066
203975AE1-071-GEN
Solar/Wind Helper
1.568
235063AE1-101 C2
Solar/Wind Helper
0.75
219904AC1-010 C
Solar/Wind Helper
0.047
219906AC1-017 C
Solar/Wind Helper
0.032
20720828JCB_W4-025
Solar/Wind Helper
0.048
20714828MDF_W3-079
Solar/Wind Helper
0.099
20742028HF_AC1-207
Solar/Wind Helper
0.106
218438BLK ROCK C
Solar/Wind Helper
0.021
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.005
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674828DL_W4-046
Solar/Wind Helper
0.006
237080AD1-060 GEN
Solar/Wind Helper
0.152
233935AB2-179 C
Solar/Wind Helper
1.008
233987AB2-037 GEN
Solar/Wind Helper
1.854
232417X3-008 C
Solar/Wind Helper
0.184
233923SMA
Solar/Wind Helper
0.594
233997TMININ_4.2
Solar/Wind Helper
0.162
959561AF2-247 GEN
Solar/Wind Helper
0.016
20715728PEM_W1-119
Solar/Wind Helper
0.073
219249CENTRALDIV C
Solar/Wind Helper
0.008
207442AE1-156 GEN
Solar/Wind Helper
0.244
217211CAMDEN ST C
Solar/Wind Helper
0.003
207511W3-106 GEN
Solar/Wind Helper
0.02
20674128FR_U2-059
Solar/Wind Helper
0.003
211065PSPA IPP
Solar/Wind Helper
0.11
957921AF2-086 GEN
Solar/Wind Helper
0.299
237038AE2-054 C
Solar/Wind Helper
0.12
230407AD2-065 C
Solar/Wind Helper
0.031
20720728JCB_W1-129
Solar/Wind Helper
0.044
964851AG1-348 GEN
Solar/Wind Helper
0.046
207408W3-077 C
Solar/Wind Helper
0.062
959381AF2-229 GEN
Solar/Wind Helper
0.231
209054AE2-059 GEN
Solar/Wind Helper
0.054
209067AE2-060 GEN
Solar/Wind Helper
0.052
227287AC2-120 GEN
Solar/Wind Helper
0.268
232422X3-066 FULL
Solar/Wind Helper
0.09
233964AF2-378 GEN
Solar/Wind Helper
0.033
232406W1-004 FULL
Solar/Wind Helper
0.401
232434Z2-077 GEN
Solar/Wind Helper
0.1
230415AB2-049 C
Solar/Wind Helper
0.023
219291REEVESSOUT C
Solar/Wind Helper
0.009
219236SOUTHERNHQ C
Solar/Wind Helper
0.004
20714928UPF_X1-085
Solar/Wind Helper
0.004
205941AD2-115 GEN
Solar/Wind Helper
0.376
219918AC2-009 C
Solar/Wind Helper
0.001
233933AB2-153 GEN
Solar/Wind Helper
0.184
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.022
20673728F2S_V4-070
Solar/Wind Helper
0.022
207510AF2-138 C
Solar/Wind Helper
0.06
207437AD2-070 GEN
Solar/Wind Helper
0.102
20671928W4-073
Solar/Wind Helper
0.066
209116AE2-175 GEN
Solar/Wind Helper
1.293
961421AF2-433 GEN
Solar/Wind Helper
0.302
946691AF1-333 GEN
Solar/Wind Helper
0.298
946741AF1-338 GEN
Solar/Wind Helper
0.298
230434AG1-499 GEN
Solar/Wind Helper
0.178
219258KINSLEYDEP C
Solar/Wind Helper
0.059
20673828FLE_V3-070
Solar/Wind Helper
0.065
20676128MHD_W3-029
Solar/Wind Helper
0.072
20390526W1-045 C
Solar/Wind Helper
0.226
209027LOR2_Q27
Solar/Wind Helper
0.713
964051AG1-259 GEN
Solar/Wind Helper
0.044
964061AG1-260 GEN
Solar/Wind Helper
0.044
233946AB2-136 GEN
Solar/Wind Helper
0.45
232410W1-006 C
Solar/Wind Helper
0.401
233952AC2-187 GEN
Solar/Wind Helper
0.184
233954AC2-188 GEN
Solar/Wind Helper
0.184
230511AF1-262
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.02
219272CLEANLIGHT C
Solar/Wind Helper
0.02
217081WEATEXAS C
Solar/Wind Helper
0.009
20675928HOL_W4-097
Solar/Wind Helper
0.037
207471AF2-354 C
Solar/Wind Helper
0.124
961431AF2-434 GEN
Solar/Wind Helper
0.302
238221AF1-254 C O1
Solar/Wind Helper
0.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.695
LGEELTFEXP_LGEE->PJM
CLTF
2.092
MECLTFEXP_MEC->PJM
CLTF
5.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.1
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.759
CPLELTFEXP_CPLE->PJM
CLTF
5
SIGELTFEXP_SIGE->PJM
CLTF
0.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.818
WECLTFEXP_WEC->PJM
CLTF
1.123
LAGNLTFEXP_LAGN->PJM
CLTF
6.94
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.692
NYPJM->LTFIMP_NY
CLTF
3.275
TVALTFEXP_TVA->PJM
CLTF
3.494
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.88 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:1802.21
MW Contribution:
2.02
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150181POSSMC2
50/50
1.151
3150181POSSMC2
50/50
1.141
3150181POSSMC2
50/50
1.141
316450AC1-158 RIC
Solar/Wind Harmer
0.122
972195AH1-682 GEN
Adder
1.66
315673AE1-157 GEN
Solar/Wind Harmer
6.386
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.912
3150341NORNECKC1
Adder
0.905
966001AG1-469 GEN
Solar/Wind Harmer
0.051
3151731LOISA B
Adder
5.59
3150681DARBY 2
Adder
6.037
316033AB2-134 GEN
Solar/Wind Harmer
0
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.192
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.128
316388AE2-253 GEN
Solar/Wind Harmer
0.249
3137176SLIGO L2192
Solar/Wind Harmer
0.318
3130086AYDLETT
Solar/Wind Harmer
0.319
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146626S HERTFORD
Solar/Wind Harmer
0.078
313506AB2-031 GEN
Solar/Wind Harmer
0.226
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
970301AG2-198 GEN
Solar/Wind Harmer
3.132
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.091
3145933PARMELE
Solar/Wind Harmer
0.143
3145933PARMELE
Solar/Wind Harmer
0.072
970323AG2-213 GEN
Solar/Wind Harmer
3.051
3145493TOT1
Solar/Wind Harmer
0.161
316049AB1-081 GEN
Solar/Wind Harmer
0.392
3132123MT JACKSON
Solar/Wind Harmer
0.182
970117AG2-086 GEN
Solar/Wind Harmer
1.398
970117AG2-086 GEN
Solar/Wind Harmer
0.932
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
235062AE1-101 C1
Solar/Wind Helper
1.069
232424Y1-079 C
Solar/Wind Helper
0.07
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
3140676OCCOQUN
50/50
0.016
972213AH1-691 GEN
Adder
2.056
944491AF1-114 GEN
Solar/Wind Harmer
0
3138133OCRAN
Solar/Wind Harmer
0.025
3147346CASHSCORNER
Solar/Wind Harmer
0.196
3141873WAN 176
Solar/Wind Harmer
0.017
3143873LANEXA
Solar/Wind Harmer
0.051
971281AH1-106 GEN
Solar/Wind Harmer
1.159
316159AE1-175 C
Solar/Wind Harmer
0.071
3143316POE
Solar/Wind Harmer
0.321
970657AG2-426 GEN
Solar/Wind Harmer
0.592
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
3145176PASQUOTANK
Solar/Wind Harmer
0.049
970533AG2-339 GEN
Solar/Wind Harmer
5.901
3130156CHOWAN
Solar/Wind Harmer
0.077
3130156CHOWAN
Solar/Wind Harmer
0.077
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315733AD1-074 GEN2
Solar/Wind Harmer
0.431
970601AG2-382 GEN
Solar/Wind Harmer
2.806
970581AG2-369 GEN
Solar/Wind Harmer
3.417
972205AH1-687 GEN
Adder
3.128
3146033SCOT NK
Solar/Wind Harmer
0.29
3148013FISHERV
Solar/Wind Harmer
0.037
3151881LOWMORC
Adder
0.639
3151881LOWMORC
Adder
0.628
205943AE1-185 GEN
Solar/Wind Helper
0.388
233915AB1-141 GEN
Solar/Wind Helper
0.305
228728W1-130C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
3150101POSSM6S
50/50
1.293
3150301M RUN C
Adder
13.329
3150401LDYSMT4
Adder
12.659
3141906WESTMOR
Solar/Wind Harmer
0.036
3147666LOUISA
Solar/Wind Harmer
0.204
3141873WAN 176
Solar/Wind Harmer
1.502
3141843SHACKLE
Adder
0.431
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316458AB2-190 GEN2
Solar/Wind Harmer
0.439
961611AG1-000B GEN
Solar/Wind Harmer
2.178
3151171GRAVELC
Adder
1.14
970657AG2-426 GEN
Solar/Wind Harmer
1.809
3144873MCLAUGH
Solar/Wind Harmer
0.002
316246AF1-032 C
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.014
3146626S HERTFORD
Solar/Wind Harmer
0.078
3156081AA2-088 GEN
Solar/Wind Harmer
0
970917AG2-570 GEN
Solar/Wind Harmer
6.668
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3146926FARMVIL
Solar/Wind Harmer
0.044
3145933PARMELE
Solar/Wind Harmer
0.072
970257AG2-171 GEN
Solar/Wind Harmer
2.288
971775AH1-396 GEN
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3148013FISHERV
Solar/Wind Harmer
0.065
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
235067AD1-061 GEN
Solar/Wind Helper
0.282
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
315976AC1-164 GENA
Solar/Wind Harmer
0.883
316169AC1-164_GENC
Solar/Wind Harmer
0.763
3142946ENON
Solar/Wind Harmer
0.008
316294AC1-161 GEN
Solar/Wind Harmer
1.396
316349AD2-085 GEN
Solar/Wind Harmer
0.053
3146456SLIGO L269
Solar/Wind Harmer
1.414
3146386ELIZ CT
Solar/Wind Harmer
0.079
316336AC2-165 C
Solar/Wind Harmer
3.964
315742AE1-103 GEN
Solar/Wind Harmer
1.163
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
970933AG2-581 GEN
Solar/Wind Harmer
6.095
316365GEN2_N
Solar/Wind Harmer
0.167
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.864
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
237080AD1-060 GEN
Solar/Wind Helper
0.222
3150021OMF B
50/50
0.213
3150231REMNGT3
50/50
0.781
3150241REMNGT4
50/50
13.296
972199AH1-684 GEN
50/50
2.016
963691AG1-221 GEN
Solar/Wind Harmer
2.31
3150371LDYSMT1
Adder
12.232
971781AH1-399 GEN
Solar/Wind Harmer
0.117
316473AC1-191 GEN
Solar/Wind Harmer
0.29
3142416OLDCHRC
Solar/Wind Harmer
0.82
3141766HARMONY
Solar/Wind Harmer
1.127
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3142946ENON
Solar/Wind Harmer
0.028
970133AG2-095 GEN
Solar/Wind Harmer
0.793
315813AE1-149 C
Solar/Wind Harmer
4.327
3145336SMITFLD
Solar/Wind Harmer
0.032
316017AA1-139 ULT1
Solar/Wind Harmer
0.043
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.924
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.077
3146206CASHIE
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
316181AB2-040 GEN
Solar/Wind Harmer
0.105
3147043LAWRENC
Solar/Wind Harmer
0.044
316478AD1-087 GEN
Solar/Wind Harmer
0.251
3147133PAMPLIN
Solar/Wind Harmer
0.226
972255AH1-712 GEN
Adder
36.701
959311AF2-222 GEN
Solar/Wind Harmer
6.364
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316283AC2-100 C
Solar/Wind Harmer
0.124
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
970053AG2-049 GEN
50/50
2.019
3150381LDYSMT2
Adder
12.153
315651AD1-115 GEN
Solar/Wind Harmer
0
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151211GRAVEL5
Adder
5.855
316311AC2-079 GEN
Solar/Wind Harmer
2.299
313526AB2-022
Solar/Wind Harmer
0.042
3146396TANGLEW
Solar/Wind Harmer
0.218
315814AE2-033 C
Solar/Wind Harmer
6.193
3146206CASHIE
Solar/Wind Harmer
0.075
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.148
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
971845AH1-439 GEN
Solar/Wind Harmer
3.318
316486AD2-202 GEN
Solar/Wind Harmer
0.074
961791AG1-021 GEN
Solar/Wind Harmer
0.691
316274AC1-208 GEN
Solar/Wind Harmer
0.369
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
3148463FAIRFLD
Solar/Wind Harmer
0.06
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
959381AF2-229 GEN
Solar/Wind Helper
0.257
232432Z2-076 GEN
Solar/Wind Helper
0.04
230407AD2-065 C
Solar/Wind Helper
0.024
20720728JCB_W1-129
Solar/Wind Helper
0.034
3150011OMF A
50/50
0.213
3150221REMNGT2
50/50
13.208
3150211REMNGT1
50/50
13.121
972201AH1-685 GEN
50/50
2.279
316447AC1-158 HLD
Solar/Wind Harmer
1.006
972197AH1-683 GEN
Adder
1.977
972135AH1-637 GEN
Solar/Wind Harmer
0.78
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.208
316192AB2-158 GEN
Solar/Wind Harmer
0.497
958261AF2-120 GEN
Solar/Wind Harmer
2.855
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3142433PROV 92
Solar/Wind Harmer
0.336
3142433PROV 92
Adder
0.163
3142433PROV 92
Adder
0.163
315975AC1-164 GENB
Solar/Wind Harmer
0.026
3145336SMITFLD
Solar/Wind Harmer
0.324
316375AC2-012 GEN
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.08
3145663CRESWEL
Solar/Wind Harmer
0.214
970937AG2-583 GEN
Solar/Wind Harmer
4.632
3146206CASHIE
Solar/Wind Harmer
0.075
316023GEN1_S
Solar/Wind Harmer
0.167
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.335
3145683EARLEYS
Solar/Wind Harmer
0.074
3147043LAWRENC
Adder
0.663
316131AB2-060 GEN
Solar/Wind Harmer
0.221
3146083TARBORO
Solar/Wind Harmer
0.07
316359AB2-059 GEN
Solar/Wind Harmer
0.245
3142053HEARTS
Solar/Wind Harmer
0.121
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
203975AE1-071-GEN
Solar/Wind Helper
1.719
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
219766PARADISE C
Solar/Wind Helper
0.032
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
218440SUMMTASSOC C
Solar/Wind Helper
0.01
217208PARK ELE C
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.051
3150091POSSM6B
50/50
0.849
316045AC1-158 PL2
Solar/Wind Harmer
1.464
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316156AD2-030 GEN
Solar/Wind Harmer
0.062
3150671DARBY 1
Adder
6.03
971223AH1-071 GEN
Solar/Wind Harmer
0.889
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
315835AF2-110_GEN
Solar/Wind Harmer
0.547
316313AB2-026
Solar/Wind Harmer
0.049
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.435
316065AD1-022 GEN
Solar/Wind Harmer
3.468
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.026
3146776BUCKING
Solar/Wind Harmer
0.293
3146776BUCKING
Solar/Wind Harmer
0.024
972193AH1-681 GEN
Adder
1.64
316005AA1-067
Solar/Wind Harmer
0.076
3145453TOT5
Solar/Wind Harmer
0.097
961601AG1-000A GEN
Solar/Wind Harmer
1.225
964791AG1-342 GEN
Solar/Wind Harmer
1.319
316118AC1-105 GEN
Solar/Wind Harmer
0.174
971761AH1-387 GEN
Solar/Wind Harmer
1.229
942751AE2-291 GEN
Solar/Wind Harmer
3.269
232436AB1-176 C
Solar/Wind Helper
0.027
234036AF2-325 C
Solar/Wind Helper
0.025
233994AC2-023 GEN
Solar/Wind Helper
0.579
3138216PACIFIC
Solar/Wind Harmer
0.025
3150411LDYSMT5
Adder
12.698
972215AH1-692 GEN
Adder
2.056
316164AC1-076 GEN
Solar/Wind Harmer
0.129
3141813NORNECK
Solar/Wind Harmer
0.087
970189AG2-124 GEN
Solar/Wind Harmer
2.502
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971283AH1-107 GEN
Solar/Wind Harmer
1.159
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3151191GRAVEL3
Adder
5.855
3146406KITTY HAWK
Solar/Wind Harmer
0.01
971967AH1-528 GEN
Solar/Wind Harmer
12.296
315732AD1-074 GEN1
Solar/Wind Harmer
0.431
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
3.973
316463AE2-346 GEN
Solar/Wind Harmer
0.064
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3137643SOCKMAN
Solar/Wind Harmer
0.293
315652AC1-086 GEN
Solar/Wind Harmer
8.072
316426AA2-053 GEN
Solar/Wind Harmer
0.245
946301AF1-294 GEN
Solar/Wind Harmer
1.421
3144303KENBRDG
Solar/Wind Harmer
0.057
316327AA2-057 GEN
Solar/Wind Harmer
0.104
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205956AE1-196_GEN
Solar/Wind Helper
0.386
233901CHERRYDALE C
Solar/Wind Helper
0.14
20715028HAN_X4-015
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
3152111X4-039 GT1
50/50
1.844
3150151POSSMC1
50/50
1.141
3150151POSSMC1
50/50
1.141
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3150291M RUN B
Adder
13.23
3150331BIRCHWDA
Adder
16.601
316223AC1-118
Solar/Wind Harmer
0.064
3132273ORANGE
Solar/Wind Harmer
0.018
316203AE2-005 GEN
Solar/Wind Harmer
0
970293AG2-193 GEN
Solar/Wind Harmer
0.898
3150921YORKTN3
Adder
2.065
3144536CHRHLND
Solar/Wind Harmer
0.012
944581AF1-123 GEN
Solar/Wind Harmer
18.116
3146516WINFALL
Solar/Wind Harmer
0.079
944011AF1-069 GEN
Solar/Wind Harmer
4.7
315735AD1-075 GEN1
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
3146263WOODLND
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.073
316011AB1-132 GEN
Solar/Wind Harmer
1.331
3146776BUCKING
Solar/Wind Harmer
0.026
970221AG2-151 GEN
Solar/Wind Harmer
3.81
961601AG1-000A GEN
Solar/Wind Harmer
4.902
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
270494AE1-108_GEN
Solar/Wind Harmer
0.797
3151861LOWMORA
Adder
0.644
237038AE2-054 C
Solar/Wind Helper
0.174
233935AB2-179 C
Solar/Wind Helper
0.775
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233923SMA
Solar/Wind Helper
0.453
3150281M RUN A
Adder
13.337
316044AC1-158 PL1
Solar/Wind Harmer
0.458
316254AC1-120 GEN1
Solar/Wind Harmer
3.292
3147666LOUISA
Solar/Wind Harmer
0.355
316404AE1-155 C
Solar/Wind Harmer
0
3151751LOISA D
Adder
5.59
3138133OCRAN
Solar/Wind Harmer
0.051
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
0.008
3143226MDLTHAN
Solar/Wind Harmer
0.083
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.459
961611AG1-000B GEN
Solar/Wind Harmer
4.282
3151171GRAVELC
Adder
0.867
316381AD1-082 GEN
Solar/Wind Harmer
0.082
3150981CHESPKA
Adder
1.005
319010AE1-072 C
Solar/Wind Harmer
0.398
3130156CHOWAN
Solar/Wind Harmer
0.077
315816AE2-034 GEN
Solar/Wind Harmer
0.327
971163AH1-040 GEN
Solar/Wind Harmer
6.123
315737AD1-076 GEN
Solar/Wind Harmer
0.97
970087AG2-069 GEN
Solar/Wind Harmer
5.959
957481AF2-042 GEN
Solar/Wind Harmer
19.733
315693AD1-088 GEN
Solar/Wind Harmer
3.538
3146926FARMVIL
Solar/Wind Harmer
0.044
971563AH1-280 GEN
Solar/Wind Harmer
0.768
970685AG2-442 GEN
Solar/Wind Harmer
5.367
3146293MARTNCO
Solar/Wind Harmer
0.066
971377AH1-170 GEN
Solar/Wind Harmer
0.762
315785AD2-033 C
Solar/Wind Harmer
0.577
3146233WITAKRS
Solar/Wind Harmer
0.277
3145493TOT1
Solar/Wind Harmer
0.309
208835TUHI V3-051
Solar/Wind Helper
0.017
23777901MDS_W4-102
Solar/Wind Helper
0.106
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
219919AE1-041 FULL
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
20674928WA_W3-044
Solar/Wind Helper
0.057
20676328BVR_Y1-020
Solar/Wind Helper
0.015
207518AF1-320_GEN
Solar/Wind Helper
0.902
209137AF2-361 C
Solar/Wind Helper
0.711
230433AD2-135 GEN
Solar/Wind Helper
0.01
214067T20SOLAR
Solar/Wind Helper
0.007
207459AE1-142 C O1
Solar/Wind Helper
0.17
232406W1-004 FULL
Solar/Wind Helper
0.305
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674828DL_W4-046
Solar/Wind Helper
0.005
3150151POSSMC1
50/50
1.141
316170AC1-121 GEN2
Solar/Wind Harmer
1.13
316337AD2-073 GEN
Solar/Wind Harmer
0.076
3141726DUNNSVL
Solar/Wind Harmer
0.347
962861AG1-135 GEN
Solar/Wind Harmer
2.759
3150851SPRUNCC
Adder
0.385
316132AB2-190 GEN1
Solar/Wind Harmer
0.439
315773AC2-141 GEN
Solar/Wind Harmer
2.95
316036AC1-147 C
Solar/Wind Harmer
0.014
316093AE2-104_GEN
Solar/Wind Harmer
1.34
3146516WINFALL
Solar/Wind Harmer
0.255
3146516WINFALL
Solar/Wind Harmer
0.079
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.667
315607AA1-063A GEN
Solar/Wind Harmer
0.149
3146263WOODLND
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.029
316494AC1-189 GEN
Solar/Wind Harmer
0.237
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
237001AB1-127_GEN
Solar/Wind Helper
0.308
233918AB1-142 GEN
Solar/Wind Helper
0.305
228729W2-030 C
Solar/Wind Helper
0.065
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
207530AG1-191 GEN
Solar/Wind Helper
0.038
207439AE1-081 C O1
Solar/Wind Helper
0.011
20676428JCR_X2-075
Solar/Wind Helper
0.039
20675128HRM_W1-127
Solar/Wind Helper
0.017
209029WAYMART-WD
Solar/Wind Helper
0.444
959421AF2-233 GEN
Solar/Wind Helper
0.233
233997TMININ_4.2
Solar/Wind Helper
0.124
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
207442AE1-156 GEN
Solar/Wind Helper
0.189
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
957921AF2-086 GEN
Solar/Wind Helper
0.234
219912AD2-042 GEN
Solar/Wind Helper
0.089
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
20674328GAR_V4-001
Solar/Wind Helper
0.013
946751AF1-339 GEN
Solar/Wind Helper
0.234
20675428EAM_W2-061
Solar/Wind Helper
0.009
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
961261AF2-417 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.163
959431AF2-234 GEN
Solar/Wind Helper
0.467
3150071POSSM 5
50/50
52.154
3150391LDYSMT3
Adder
12.635
316312AB1-027
Solar/Wind Harmer
0.15
3143526WINTERP
Solar/Wind Harmer
0.434
944641AF1-129 GEN
Adder
39.347
3144356SAPONY
Solar/Wind Harmer
0.656
316315AB2-025 C
Solar/Wind Harmer
0.063
972185AH1-677 GEN
Adder
4.323
970099AG2-077 GEN
Solar/Wind Harmer
7.893
962571AG1-106 GEN
Solar/Wind Harmer
1.044
3145783HORNRTN
Solar/Wind Harmer
1.297
3145783HORNRTN
Solar/Wind Harmer
1.037
3145783HORNRTN
Solar/Wind Harmer
0.324
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.218
3144293JTRSVLE
Adder
0.172
315724AD1-057 GEN
Solar/Wind Harmer
1.362
3145603CNETO
Solar/Wind Harmer
0.065
962561AG1-105 GEN
Solar/Wind Harmer
3.315
316263AC1-034 GEN
Solar/Wind Harmer
2.619
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
233946AB2-136 GEN
Solar/Wind Helper
0.343
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
315747AE2-019 GEN
50/50
13.161
3150081POSSM6A
50/50
0.849
972217AH1-693 GEN
50/50
1.753
3141196NOKESVL
Solar/Wind Harmer
0.428
3150351NORNECKC2
Adder
0.883
3151761LOISA E
Adder
11.397
3151721LOISA A
Adder
5.561
316075AC2-137 C
Solar/Wind Harmer
0.022
315778AD1-151 GEN
Solar/Wind Harmer
6.568
3144216WINCHST
Adder
0.309
3151101ELIZAR3
Adder
7.476
944601AF1-125 GEN
Solar/Wind Harmer
17.837
3143336POWHATN
Solar/Wind Harmer
1.198
3145823KELFORD
Solar/Wind Harmer
0.073
972003AH1-546 GEN
Solar/Wind Harmer
2.538
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.37
964241AG1-285 GEN
Solar/Wind Harmer
4.743
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
2.442
315821AE2-092 GEN
Solar/Wind Harmer
0
971683AH1-343 GEN
Solar/Wind Harmer
2.374
316123AC1-075 GEN
Solar/Wind Harmer
0.082
226910AB2-157 C
Solar/Wind Helper
0.021
237085AD2-009_GEN
Solar/Wind Helper
0.975
233933AB2-153 GEN
Solar/Wind Helper
0.141
3141426STAFORD
Solar/Wind Harmer
0.023
3141913WHIT STONE
Solar/Wind Harmer
0.085
971285AH1-108 GEN
Adder
0.63
315697AD1-025 GEN
Solar/Wind Harmer
0.088
971445AH1-216 GEN
Solar/Wind Harmer
5.713
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.077
957871AF2-081 GEN
Solar/Wind Harmer
3.983
316258AE1-075 C
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
9.667
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
316210AC1-098 GEN
Solar/Wind Harmer
0.664
970683AG2-441 GEN
Solar/Wind Harmer
4.325
970681AG2-440 GEN
Solar/Wind Harmer
2.871
970831AG2-522 GEN
Solar/Wind Harmer
3.061
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
957861AF2-080 GEN
Solar/Wind Harmer
3.026
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
3148133STUARTS
Solar/Wind Harmer
0.039
20390526W1-045 C
Solar/Wind Helper
0.253
233940AF2-379 C
Solar/Wind Helper
0.037
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
20673828FLE_V3-070
Solar/Wind Helper
0.05
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
972223AH1-696 GEN
50/50
9.014
3141346CRANES
50/50
0.127
971685AH1-345 GEN
Solar/Wind Harmer
0.729
972219AH1-694 GEN
Adder
1.423
3150351NORNECKC2
Adder
0.868
3143526WINTERP
Solar/Wind Harmer
0.434
944631AF1-128 GEN
Adder
39.784
971317AH1-138 GEN
Solar/Wind Harmer
0.617
315671AE2-027_GEN
Solar/Wind Harmer
0.001
944591AF1-124 GEN
Solar/Wind Harmer
18.181
316072AD1-144
Solar/Wind Harmer
0.029
939411AE1-173 GEN
Solar/Wind Harmer
34.104
940641AE2-051 GEN
Solar/Wind Harmer
6.384
3143336POWHATN
Solar/Wind Harmer
1.41
941031AE2-094 GEN
Solar/Wind Harmer
14.385
971547AH1-271 GEN
Solar/Wind Harmer
1.603
960081AF2-299 GEN
Solar/Wind Harmer
0.713
3145823KELFORD
Solar/Wind Harmer
0.073
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
972277AH1-723 GEN
Adder
42.768
316129AC1-054 GEN
Solar/Wind Harmer
0.267
316034AC1-036 C
Solar/Wind Harmer
0.005
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.047
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970401AG2-262 GEN
Solar/Wind Harmer
0.403
3147983MERCK5
Solar/Wind Harmer
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.485
233944AB2-135 GEN
Solar/Wind Helper
0.357
232408W1-005 C
Solar/Wind Helper
0.305
219907AC1-030 C
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.011
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
218428ETC SOLAR C
Solar/Wind Helper
0.003
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.047
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
209116AE2-175 GEN
Solar/Wind Helper
1.008
961421AF2-433 GEN
Solar/Wind Helper
0.237
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.009
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
961431AF2-434 GEN
Solar/Wind Helper
0.237
20676128MHD_W3-029
Solar/Wind Helper
0.056
209027LOR2_Q27
Solar/Wind Helper
0.559
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
233950AC2-186 GEN
Solar/Wind Helper
0.07
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
207454AA2-184 E
Solar/Wind Helper
0.181
217169METRODIV C
Solar/Wind Helper
0.002
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
209071AE2-133 GEN
Solar/Wind Helper
0.042
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.822
LGEELTFEXP_LGEE->PJM
CLTF
1.798
MECLTFEXP_MEC->PJM
CLTF
4.431
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.532
CPLELTFEXP_CPLE->PJM
CLTF
5.053
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.552
WECLTFEXP_WEC->PJM
CLTF
0.958
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.329
NYPJM->LTFIMP_NY
CLTF
2.582
TVALTFEXP_TVA->PJM
CLTF
3.177

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T560_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.27 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1994.82
MW Contribution:
1.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
963691AG1-221 GEN
Solar/Wind Harmer
2.31
3150241REMNGT4
Adder
12.527
972199AH1-684 GEN
Adder
1.899
3150371LDYSMT1
Adder
12.245
966881AG1-559 GEN
Solar/Wind Harmer
0.308
971781AH1-399 GEN
Solar/Wind Harmer
0.619
961951AG1-038 GEN
Solar/Wind Harmer
1.273
316473AC1-191 GEN
Solar/Wind Harmer
1.038
3142416OLDCHRC
Solar/Wind Harmer
0.959
3141766HARMONY
Solar/Wind Harmer
0.845
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
1.044
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.697
316017AA1-139 ULT1
Solar/Wind Harmer
0.725
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.039
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.154
3147043LAWRENC
Solar/Wind Harmer
-0.005
316478AD1-087 GEN
Solar/Wind Harmer
0.704
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
315976AC1-164 GENA
Solar/Wind Harmer
2.145
316169AC1-164_GENC
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
-0.001
316294AC1-161 GEN
Solar/Wind Harmer
2.936
316083AB2-161 GEN
Solar/Wind Harmer
1.471
316349AD2-085 GEN
Solar/Wind Harmer
0.799
3146456SLIGO L269
Solar/Wind Harmer
1.06
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.606
316433W1029_GEN2
Solar/Wind Harmer
1.606
316336AC2-165 C
Solar/Wind Harmer
5.487
315742AE1-103 GEN
Solar/Wind Harmer
2.076
3146376EDENTON
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.258
970933AG2-581 GEN
Solar/Wind Harmer
8.024
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.712
972215AH1-692 GEN
Adder
2.058
316164AC1-076 GEN
Solar/Wind Harmer
0.884
3141813NORNECK
Solar/Wind Harmer
-0.01
957601AF2-054 GEN
Solar/Wind Harmer
0.284
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971283AH1-107 GEN
Solar/Wind Harmer
1.526
3138283WHITEMARSH
Solar/Wind Harmer
0.014
3151191GRAVEL3
Adder
5.855
315833AF1-017_GEN
Solar/Wind Harmer
1.708
316018AA1-139 ULT2
Solar/Wind Harmer
0.768
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315800Z1-036_GEN1
Solar/Wind Harmer
2.158
971967AH1-528 GEN
Solar/Wind Harmer
16.231
315732AD1-074 GEN1
Solar/Wind Harmer
1.714
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.23
316463AE2-346 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.278
316426AA2-053 GEN
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
1.265
946301AF1-294 GEN
Solar/Wind Harmer
2.073
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205956AE1-196_GEN
Solar/Wind Helper
0.386
233901CHERRYDALE C
Solar/Wind Helper
0.14
20715028HAN_X4-015
Solar/Wind Helper
0.034
3152111X4-039 GT1
50/50
1.844
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3150151POSSMC1
Adder
1.083
3150151POSSMC1
Adder
1.083
3150291M RUN B
Adder
13.227
3150331BIRCHWDA
Adder
16.668
316223AC1-118
Solar/Wind Harmer
0.271
3132273ORANGE
Solar/Wind Harmer
-0.002
316203AE2-005 GEN
Solar/Wind Harmer
4.002
970293AG2-193 GEN
Solar/Wind Harmer
1.182
3150921YORKTN3
Adder
2.065
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
41.122
3142956BIRDNECK
Solar/Wind Harmer
0.485
316305AF2-043 C
Solar/Wind Harmer
0.27
316320Y1-086
Solar/Wind Harmer
0.522
3146516WINFALL
Solar/Wind Harmer
-0.009
944011AF1-069 GEN
Solar/Wind Harmer
5.155
315735AD1-075 GEN1
Solar/Wind Harmer
0.857
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.722
3146776BUCKING
Solar/Wind Harmer
-0.003
3151861LOWMORA
Adder
0.643
237038AE2-054 C
Solar/Wind Helper
0.174
233935AB2-179 C
Solar/Wind Helper
0.775
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
207442AE1-156 GEN
Solar/Wind Helper
0.189
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
957921AF2-086 GEN
Solar/Wind Helper
0.234
970221AG2-151 GEN
Solar/Wind Harmer
1.345
972213AH1-691 GEN
Adder
2.058
944491AF1-114 GEN
Solar/Wind Harmer
3.046
3138133OCRAN
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3141873WAN 176
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.526
316382AG1-145 C
Solar/Wind Harmer
0.28
316159AE1-175 C
Solar/Wind Harmer
0.249
316236AE1-162_GEN
Solar/Wind Harmer
0.274
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.571
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316405AF2-144 C
Solar/Wind Harmer
0.228
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
970533AG2-339 GEN
Solar/Wind Harmer
5.901
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.714
970601AG2-382 GEN
Solar/Wind Harmer
3.694
970581AG2-369 GEN
Solar/Wind Harmer
4.498
946281AF1-292 GEN
Solar/Wind Harmer
0.187
972205AH1-687 GEN
Adder
3.127
3146033SCOT NK
Solar/Wind Harmer
-0.032
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
205943AE1-185 GEN
Solar/Wind Helper
0.388
233915AB1-141 GEN
Solar/Wind Helper
0.305
228728W1-130C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
961261AF2-417 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.163
959431AF2-234 GEN
Solar/Wind Helper
0.467
3150181POSSMC2
Adder
1.092
3150181POSSMC2
Adder
1.083
3150181POSSMC2
Adder
1.083
316450AC1-158 RIC
Solar/Wind Harmer
0.277
972195AH1-682 GEN
Adder
1.662
315673AE1-157 GEN
Solar/Wind Harmer
7.788
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3151731LOISA B
Adder
5.589
316487AF1-042 GEN
Solar/Wind Harmer
1.273
3150681DARBY 2
Adder
6.038
316033AB2-134 GEN
Solar/Wind Harmer
2.966
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.605
316388AE2-253 GEN
Solar/Wind Harmer
0.605
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
0.664
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.124
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
970323AG2-213 GEN
Solar/Wind Harmer
4.017
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
315747AE2-019 GEN
50/50
13.164
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.652
316077AC2-138 C
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
0.884
3151761LOISA E
Adder
11.393
3151721LOISA A
Adder
5.56
316484AD2-074 GEN
Solar/Wind Harmer
2.432
316075AC2-137 C
Solar/Wind Harmer
0.254
315778AD1-151 GEN
Solar/Wind Harmer
8.21
3144216WINCHST
Adder
0.309
3151101ELIZAR3
Adder
7.475
944601AF1-125 GEN
Solar/Wind Harmer
40.48
3143336POWHATN
Solar/Wind Harmer
0.898
966621AG1-532 GEN
Solar/Wind Harmer
0.169
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
972003AH1-546 GEN
Solar/Wind Harmer
3.341
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.227
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.702
226910AB2-157 C
Solar/Wind Helper
0.021
237085AD2-009_GEN
Solar/Wind Helper
0.975
233933AB2-153 GEN
Solar/Wind Helper
0.141
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
209116AE2-175 GEN
Solar/Wind Helper
1.008
961421AF2-433 GEN
Solar/Wind Helper
0.237
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
316411AF1-147_GEN1
Solar/Wind Harmer
1.097
3150071POSSM 5
Adder
49.515
3150391LDYSMT3
Adder
12.649
316312AB1-027
Solar/Wind Harmer
0.32
316441AF1-014 GEN
Solar/Wind Harmer
0.64
3143526WINTERP
Solar/Wind Harmer
-0.049
944641AF1-129 GEN
Adder
39.347
316185AD1-033 GEN
Solar/Wind Harmer
0.95
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.237
972185AH1-677 GEN
Adder
4.322
970099AG2-077 GEN
Solar/Wind Harmer
10.391
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.778
3145783HORNRTN
Solar/Wind Harmer
0.243
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3144293JTRSVLE
Adder
0.172
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
233946AB2-136 GEN
Solar/Wind Helper
0.343
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
961431AF2-434 GEN
Solar/Wind Helper
0.237
316006AB2-029 C
Solar/Wind Harmer
0.629
316045AC1-158 PL2
Solar/Wind Harmer
3.324
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316156AD2-030 GEN
Solar/Wind Harmer
0.253
315666AE1-190 GEN
Solar/Wind Harmer
0.285
3150671DARBY 1
Adder
6.031
971223AH1-071 GEN
Solar/Wind Harmer
1.17
316240AF1-291 C
Solar/Wind Harmer
0.278
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
315835AF2-110_GEN
Solar/Wind Harmer
1.119
316313AB2-026
Solar/Wind Harmer
0.24
316435W1029_GEN3
Solar/Wind Harmer
1.606
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.925
316065AD1-022 GEN
Solar/Wind Harmer
4.231
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
-0.015
316140AB2-099
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
972193AH1-681 GEN
Adder
1.639
232436AB1-176 C
Solar/Wind Helper
0.027
234036AF2-325 C
Solar/Wind Helper
0.025
233994AC2-023 GEN
Solar/Wind Helper
0.579
219912AD2-042 GEN
Solar/Wind Helper
0.089
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
20674328GAR_V4-001
Solar/Wind Helper
0.013
946751AF1-339 GEN
Solar/Wind Helper
0.234
207445AB1-138_GEN
Solar/Wind Helper
0.061
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
20676428JCR_X2-075
Solar/Wind Helper
0.039
20675128HRM_W1-127
Solar/Wind Helper
0.017
209029WAYMART-WD
Solar/Wind Helper
0.444
959421AF2-233 GEN
Solar/Wind Helper
0.233
235062AE1-101 C1
Solar/Wind Helper
1.069
232424Y1-079 C
Solar/Wind Helper
0.07
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
230433AD2-135 GEN
Solar/Wind Helper
0.01
214067T20SOLAR
Solar/Wind Helper
0.007
207459AE1-142 C O1
Solar/Wind Helper
0.17
20675428EAM_W2-061
Solar/Wind Helper
0.009
3150301M RUN C
Adder
13.326
3150401LDYSMT4
Adder
12.673
3141906WESTMOR
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.023
3141873WAN 176
Solar/Wind Harmer
1.127
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316458AB2-190 GEN2
Solar/Wind Harmer
0.932
961611AG1-000B GEN
Solar/Wind Harmer
1.932
3151171GRAVELC
Adder
1.14
970657AG2-426 GEN
Solar/Wind Harmer
1.83
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.181
316321Z2-027
Solar/Wind Harmer
0.239
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.758
970917AG2-570 GEN
Solar/Wind Harmer
21.069
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.101
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.008
970257AG2-171 GEN
Solar/Wind Harmer
3.013
971775AH1-396 GEN
Solar/Wind Harmer
0.567
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
235067AD1-061 GEN
Solar/Wind Helper
0.282
233950AC2-186 GEN
Solar/Wind Helper
0.07
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
207454AA2-184 E
Solar/Wind Helper
0.181
217169METRODIV C
Solar/Wind Helper
0.002
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
209071AE2-133 GEN
Solar/Wind Helper
0.042
3150281M RUN A
Adder
13.334
316044AC1-158 PL1
Solar/Wind Harmer
1.039
316254AC1-120 GEN1
Solar/Wind Harmer
3.939
957971AF2-091 GEN
Solar/Wind Harmer
1.036
3147666LOUISA
Solar/Wind Harmer
-0.04
316404AE1-155 C
Solar/Wind Harmer
1.854
3151751LOISA D
Adder
5.589
3138133OCRAN
Solar/Wind Harmer
-0.006
315662AE1-191 GEN
Solar/Wind Harmer
1.142
316280AD1-041 GEN
Solar/Wind Harmer
0.714
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.46
316369SG1_INVT
Solar/Wind Harmer
1.642
961611AG1-000B GEN
Solar/Wind Harmer
4.528
3151171GRAVELC
Adder
0.867
316381AD1-082 GEN
Solar/Wind Harmer
0.829
3150981CHESPKA
Adder
1.005
319010AE1-072 C
Solar/Wind Harmer
1.811
315611Z1-036_GEN2
Solar/Wind Harmer
2.158
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.694
971163AH1-040 GEN
Solar/Wind Harmer
8.061
315737AD1-076 GEN
Solar/Wind Harmer
1.612
970087AG2-069 GEN
Solar/Wind Harmer
7.846
957481AF2-042 GEN
Solar/Wind Harmer
25.978
316087AB2-174 GEN
Solar/Wind Harmer
1.182
315693AD1-088 GEN
Solar/Wind Harmer
4.141
3146926FARMVIL
Solar/Wind Harmer
-0.005
971563AH1-280 GEN
Solar/Wind Harmer
1.011
970685AG2-442 GEN
Solar/Wind Harmer
7.066
3146293MARTNCO
Solar/Wind Harmer
0.05
208835TUHI V3-051
Solar/Wind Helper
0.017
23777901MDS_W4-102
Solar/Wind Helper
0.106
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
219919AE1-041 FULL
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
20674928WA_W3-044
Solar/Wind Helper
0.057
20676328BVR_Y1-020
Solar/Wind Helper
0.015
207518AF1-320_GEN
Solar/Wind Helper
0.902
209137AF2-361 C
Solar/Wind Helper
0.711
3141426STAFORD
Solar/Wind Harmer
-0.003
316468AD1-105 GEN
Solar/Wind Harmer
1.148
3141913WHIT STONE
Solar/Wind Harmer
-0.01
971285AH1-108 GEN
Adder
0.63
957831AF2-077 GEN
Solar/Wind Harmer
0.281
315697AD1-025 GEN
Solar/Wind Harmer
1.859
315839AE2-212 C
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
5.641
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.277
957871AF2-081 GEN
Solar/Wind Harmer
4.495
316258AE1-075 C
Solar/Wind Harmer
0.216
970673AG2-436 GEN
Solar/Wind Harmer
19.089
316322AB2-045
Solar/Wind Harmer
0.276
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.264
970683AG2-441 GEN
Solar/Wind Harmer
5.694
970681AG2-440 GEN
Solar/Wind Harmer
3.78
970831AG2-522 GEN
Solar/Wind Harmer
4.03
20390526W1-045 C
Solar/Wind Helper
0.253
233940AF2-379 C
Solar/Wind Helper
0.037
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
20673828FLE_V3-070
Solar/Wind Helper
0.05
20676128MHD_W3-029
Solar/Wind Helper
0.056
209027LOR2_Q27
Solar/Wind Helper
0.559
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
316415AF1-147_GEN2
Solar/Wind Harmer
1.097
972223AH1-696 GEN
Adder
8.557
3141346CRANES
Adder
0.12
971685AH1-345 GEN
Solar/Wind Harmer
0.96
972219AH1-694 GEN
Adder
1.425
3150351NORNECKC2
Adder
0.869
964211AG1-282 GEN
Solar/Wind Harmer
0.294
316314AB2-024 C
Solar/Wind Harmer
0.812
3143526WINTERP
Solar/Wind Harmer
-0.049
944631AF1-128 GEN
Adder
39.787
971317AH1-138 GEN
Solar/Wind Harmer
1.161
315671AE2-027_GEN
Solar/Wind Harmer
1.668
944591AF1-124 GEN
Solar/Wind Harmer
41.27
316072AD1-144
Solar/Wind Harmer
0.182
939411AE1-173 GEN
Solar/Wind Harmer
44.9
940641AE2-051 GEN
Solar/Wind Harmer
8.405
3143336POWHATN
Solar/Wind Harmer
1.057
941031AE2-094 GEN
Solar/Wind Harmer
16.452
971547AH1-271 GEN
Solar/Wind Harmer
2.111
960081AF2-299 GEN
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
972277AH1-723 GEN
Adder
42.757
316129AC1-054 GEN
Solar/Wind Harmer
0.703
316034AC1-036 C
Solar/Wind Harmer
0.149
205916AD1-020 GEN
Solar/Wind Helper
1.485
233944AB2-135 GEN
Solar/Wind Helper
0.357
232408W1-005 C
Solar/Wind Helper
0.305
219907AC1-030 C
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.011
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
219908AB1-139 C
Solar/Wind Helper
0.043
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.047
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.234
3150151POSSMC1
Adder
1.083
316170AC1-121 GEN2
Solar/Wind Harmer
1.313
316337AD2-073 GEN
Solar/Wind Harmer
0.266
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.636
3150851SPRUNCC
Adder
0.385
316132AB2-190 GEN1
Solar/Wind Harmer
0.932
315773AC2-141 GEN
Solar/Wind Harmer
3.799
316036AC1-147 C
Solar/Wind Harmer
0.243
316093AE2-104_GEN
Solar/Wind Harmer
2.602
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.25
970919AG2-571 GEN
Solar/Wind Harmer
2.667
315607AA1-063A GEN
Solar/Wind Harmer
0.839
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.003
237001AB1-127_GEN
Solar/Wind Helper
0.308
233918AB1-142 GEN
Solar/Wind Helper
0.305
228729W2-030 C
Solar/Wind Helper
0.065
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
207530AG1-191 GEN
Solar/Wind Helper
0.038
207439AE1-081 C O1
Solar/Wind Helper
0.011
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
316365GEN2_N
Solar/Wind Harmer
0.568
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.264
237080AD1-060 GEN
Solar/Wind Helper
0.222
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674828DL_W4-046
Solar/Wind Helper
0.005
970053AG2-049 GEN
50/50
2.025
3150381LDYSMT2
Adder
12.166
315651AD1-115 GEN
Solar/Wind Harmer
4.651
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.214
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151211GRAVEL5
Adder
5.855
316311AC2-079 GEN
Solar/Wind Harmer
4.537
313526AB2-022
Solar/Wind Harmer
0.24
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.19
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.21
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
971845AH1-439 GEN
Solar/Wind Harmer
4.369
316486AD2-202 GEN
Solar/Wind Harmer
0.206
961791AG1-021 GEN
Solar/Wind Harmer
1.011
316274AC1-208 GEN
Solar/Wind Harmer
0.865
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
959381AF2-229 GEN
Solar/Wind Helper
0.257
232432Z2-076 GEN
Solar/Wind Helper
0.04
230407AD2-065 C
Solar/Wind Helper
0.024
20720728JCB_W1-129
Solar/Wind Helper
0.034
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
972255AH1-712 GEN
Adder
36.692
959311AF2-222 GEN
Solar/Wind Harmer
8.394
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232406W1-004 FULL
Solar/Wind Helper
0.305
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
3150221REMNGT2
Adder
12.445
3150211REMNGT1
Adder
12.362
972201AH1-685 GEN
Adder
2.147
316447AC1-158 HLD
Solar/Wind Harmer
2.285
972197AH1-683 GEN
Adder
1.979
972135AH1-637 GEN
Solar/Wind Harmer
1.029
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
9.488
316192AB2-158 GEN
Solar/Wind Harmer
1.18
958261AF2-120 GEN
Solar/Wind Harmer
3.763
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.108
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3145336SMITFLD
Solar/Wind Harmer
-0.036
316375AC2-012 GEN
Solar/Wind Harmer
3.128
3146456SLIGO L269
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.097
3146206CASHIE
Solar/Wind Harmer
-0.008
316023GEN1_S
Solar/Wind Harmer
0.568
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.125
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.662
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
203975AE1-071-GEN
Solar/Wind Helper
1.719
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
219766PARADISE C
Solar/Wind Helper
0.032
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
218440SUMMTASSOC C
Solar/Wind Helper
0.01
217208PARK ELE C
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.051
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.53
CPLELTFEXP_CPLE->PJM
CLTF
5.052
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.815
LGEELTFEXP_LGEE->PJM
CLTF
1.797
MECLTFEXP_MEC->PJM
CLTF
4.43
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.322
NYPJM->LTFIMP_NY
CLTF
2.582
TVALTFEXP_TVA->PJM
CLTF
3.176
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.55
WECLTFEXP_WEC->PJM
CLTF
0.958
LAGNLTFEXP_LAGN->PJM
CLTF
6.302

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T560_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.27 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1994.74
MW Contribution:
1.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150281M RUN A
Adder
13.334
316044AC1-158 PL1
Solar/Wind Harmer
1.039
316254AC1-120 GEN1
Solar/Wind Harmer
3.939
957971AF2-091 GEN
Solar/Wind Harmer
1.036
3147666LOUISA
Solar/Wind Harmer
-0.04
316404AE1-155 C
Solar/Wind Harmer
1.854
3151751LOISA D
Adder
5.588
3138133OCRAN
Solar/Wind Harmer
-0.006
315662AE1-191 GEN
Solar/Wind Harmer
1.142
316280AD1-041 GEN
Solar/Wind Harmer
0.714
3143096IRON208
Adder
0.351
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.46
316369SG1_INVT
Solar/Wind Harmer
1.642
961611AG1-000B GEN
Solar/Wind Harmer
4.528
3151171GRAVELC
Adder
0.867
316381AD1-082 GEN
Solar/Wind Harmer
0.829
3150981CHESPKA
Adder
1.005
319010AE1-072 C
Solar/Wind Harmer
1.811
315611Z1-036_GEN2
Solar/Wind Harmer
2.158
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.694
971163AH1-040 GEN
Solar/Wind Harmer
8.061
315737AD1-076 GEN
Solar/Wind Harmer
1.612
970087AG2-069 GEN
Solar/Wind Harmer
7.846
957481AF2-042 GEN
Solar/Wind Harmer
25.978
316087AB2-174 GEN
Solar/Wind Harmer
1.182
315693AD1-088 GEN
Solar/Wind Harmer
4.14
3146926FARMVIL
Solar/Wind Harmer
-0.005
971563AH1-280 GEN
Solar/Wind Harmer
1.011
970685AG2-442 GEN
Solar/Wind Harmer
7.066
3146293MARTNCO
Solar/Wind Harmer
0.05
208835TUHI V3-051
Solar/Wind Helper
0.017
23777901MDS_W4-102
Solar/Wind Helper
0.106
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.305
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20715228NPK_W1-113
Solar/Wind Helper
0.046
20720528MAN_W1-024
Solar/Wind Helper
0.017
972213AH1-691 GEN
Adder
2.058
944491AF1-114 GEN
Solar/Wind Harmer
3.046
3138133OCRAN
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3141873WAN 176
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.526
316382AG1-145 C
Solar/Wind Harmer
0.28
316159AE1-175 C
Solar/Wind Harmer
0.249
316236AE1-162_GEN
Solar/Wind Harmer
0.274
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.571
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316405AF2-144 C
Solar/Wind Harmer
0.228
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
970533AG2-339 GEN
Solar/Wind Harmer
5.901
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.714
970601AG2-382 GEN
Solar/Wind Harmer
3.694
970581AG2-369 GEN
Solar/Wind Harmer
4.498
946281AF1-292 GEN
Solar/Wind Harmer
0.187
972205AH1-687 GEN
Adder
3.127
3146033SCOT NK
Solar/Wind Harmer
-0.032
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
205943AE1-185 GEN
Solar/Wind Helper
0.388
233915AB1-141 GEN
Solar/Wind Helper
0.305
228728W1-130C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
961261AF2-417 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.163
959431AF2-234 GEN
Solar/Wind Helper
0.467
3150151POSSMC1
Adder
1.084
3150181POSSMC2
Adder
1.093
3150181POSSMC2
Adder
1.084
3150181POSSMC2
Adder
1.084
972195AH1-682 GEN
Adder
1.662
316450AC1-158 RIC
Solar/Wind Harmer
0.277
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.714
972215AH1-692 GEN
Adder
2.058
316164AC1-076 GEN
Solar/Wind Harmer
0.884
3141813NORNECK
Solar/Wind Harmer
-0.01
957601AF2-054 GEN
Solar/Wind Harmer
0.284
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971283AH1-107 GEN
Solar/Wind Harmer
1.526
3138283WHITEMARSH
Solar/Wind Harmer
0.014
3151191GRAVEL3
Adder
5.855
315833AF1-017_GEN
Solar/Wind Harmer
1.708
316018AA1-139 ULT2
Solar/Wind Harmer
0.768
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315800Z1-036_GEN1
Solar/Wind Harmer
2.158
971967AH1-528 GEN
Solar/Wind Harmer
16.231
315732AD1-074 GEN1
Solar/Wind Harmer
1.714
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.23
316463AE2-346 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.278
316426AA2-053 GEN
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
1.265
946301AF1-294 GEN
Solar/Wind Harmer
2.073
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151861LOWMORA
Adder
0.618
226929AD2-058 GEN
Solar/Wind Helper
0.144
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205956AE1-196_GEN
Solar/Wind Helper
0.386
233901CHERRYDALE C
Solar/Wind Helper
0.14
20715028HAN_X4-015
Solar/Wind Helper
0.034
207445AB1-138_GEN
Solar/Wind Helper
0.061
20720628TIN_W1-124
Solar/Wind Helper
0.111
20675528CPH_W2-050
Solar/Wind Helper
0.066
20676428JCR_X2-075
Solar/Wind Helper
0.039
20675128HRM_W1-127
Solar/Wind Helper
0.017
209029WAYMART-WD
Solar/Wind Helper
0.444
959421AF2-233 GEN
Solar/Wind Helper
0.233
316006AB2-029 C
Solar/Wind Harmer
0.629
316045AC1-158 PL2
Solar/Wind Harmer
3.324
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.27
316156AD2-030 GEN
Solar/Wind Harmer
0.253
315666AE1-190 GEN
Solar/Wind Harmer
0.285
3150671DARBY 1
Adder
6.031
971223AH1-071 GEN
Solar/Wind Harmer
1.17
316240AF1-291 C
Solar/Wind Harmer
0.278
3150991CHESPKB
Adder
0.843
3150991CHESPKB
Adder
0.823
315835AF2-110_GEN
Solar/Wind Harmer
1.119
316313AB2-026
Solar/Wind Harmer
0.24
316435W1029_GEN3
Solar/Wind Harmer
1.606
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.18
315614AA2-178 GEN
Solar/Wind Harmer
0.925
316065AD1-022 GEN
Solar/Wind Harmer
4.231
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
-0.015
316140AB2-099
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
972193AH1-681 GEN
Adder
1.639
232436AB1-176 C
Solar/Wind Helper
0.027
234036AF2-325 C
Solar/Wind Helper
0.025
233994AC2-023 GEN
Solar/Wind Helper
0.579
219912AD2-042 GEN
Solar/Wind Helper
0.089
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.078
20674328GAR_V4-001
Solar/Wind Helper
0.013
946751AF1-339 GEN
Solar/Wind Helper
0.234
316170AC1-121 GEN2
Solar/Wind Harmer
1.313
316337AD2-073 GEN
Solar/Wind Harmer
0.266
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.637
3150851SPRUNCC
Adder
0.385
316132AB2-190 GEN1
Solar/Wind Harmer
0.932
315773AC2-141 GEN
Solar/Wind Harmer
3.799
316036AC1-147 C
Solar/Wind Harmer
0.243
316093AE2-104_GEN
Solar/Wind Harmer
2.602
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.25
970919AG2-571 GEN
Solar/Wind Harmer
2.667
315607AA1-063A GEN
Solar/Wind Harmer
0.839
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.003
237001AB1-127_GEN
Solar/Wind Helper
0.308
233918AB1-142 GEN
Solar/Wind Helper
0.305
228729W2-030 C
Solar/Wind Helper
0.065
219686LUMSOLAR_N C
Solar/Wind Helper
0.024
219348LDSOLAR C
Solar/Wind Helper
0.068
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
207530AG1-191 GEN
Solar/Wind Helper
0.038
207439AE1-081 C O1
Solar/Wind Helper
0.011
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.831
315673AE1-157 GEN
Solar/Wind Harmer
7.788
972189AH1-679 GEN
Adder
1.465
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.184
219919AE1-041 FULL
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
20674928WA_W3-044
Solar/Wind Helper
0.057
20676328BVR_Y1-020
Solar/Wind Helper
0.015
207518AF1-320_GEN
Solar/Wind Helper
0.902
209137AF2-361 C
Solar/Wind Helper
0.711
3151731LOISA B
Adder
5.588
316487AF1-042 GEN
Solar/Wind Harmer
1.273
3150681DARBY 2
Adder
6.038
316033AB2-134 GEN
Solar/Wind Harmer
2.966
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.605
316388AE2-253 GEN
Solar/Wind Harmer
0.605
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
0.664
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.124
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
970323AG2-213 GEN
Solar/Wind Harmer
4.017
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
235062AE1-101 C1
Solar/Wind Helper
1.069
232424Y1-079 C
Solar/Wind Helper
0.07
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
230433AD2-135 GEN
Solar/Wind Helper
0.01
214067T20SOLAR
Solar/Wind Helper
0.007
207459AE1-142 C O1
Solar/Wind Helper
0.17
20675428EAM_W2-061
Solar/Wind Helper
0.009
3150301M RUN C
Adder
13.326
3150401LDYSMT4
Adder
12.674
3141906WESTMOR
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.023
3141873WAN 176
Solar/Wind Harmer
1.127
3141843SHACKLE
Adder
0.432
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3150861SPRUNCD
Adder
0.385
316458AB2-190 GEN2
Solar/Wind Harmer
0.932
961611AG1-000B GEN
Solar/Wind Harmer
1.932
3151171GRAVELC
Adder
1.14
970657AG2-426 GEN
Solar/Wind Harmer
1.83
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.181
316321Z2-027
Solar/Wind Harmer
0.239
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.758
970917AG2-570 GEN
Solar/Wind Harmer
21.069
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.101
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.008
970257AG2-171 GEN
Solar/Wind Harmer
3.013
971775AH1-396 GEN
Solar/Wind Harmer
0.567
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
235067AD1-061 GEN
Solar/Wind Helper
0.282
233950AC2-186 GEN
Solar/Wind Helper
0.07
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.02
219688LUMSOLAR_S C
Solar/Wind Helper
0.024
207454AA2-184 E
Solar/Wind Helper
0.181
217169METRODIV C
Solar/Wind Helper
0.002
963161AG1-165 GEN
Solar/Wind Helper
0.242
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
209071AE2-133 GEN
Solar/Wind Helper
0.042
3152111X4-039 GT1
50/50
1.844
971455AH1-223 GEN
Solar/Wind Harmer
2.31
3150151POSSMC1
Adder
1.084
3150151POSSMC1
Adder
1.084
3150331BIRCHWDA
Adder
16.674
3150291M RUN B
Adder
13.227
316223AC1-118
Solar/Wind Harmer
0.271
3132273ORANGE
Solar/Wind Harmer
-0.002
316203AE2-005 GEN
Solar/Wind Harmer
4.002
970293AG2-193 GEN
Solar/Wind Harmer
1.182
3150921YORKTN3
Adder
2.065
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
41.121
3142956BIRDNECK
Solar/Wind Harmer
0.485
316305AF2-043 C
Solar/Wind Harmer
0.27
316320Y1-086
Solar/Wind Harmer
0.522
3146516WINFALL
Solar/Wind Harmer
-0.009
944011AF1-069 GEN
Solar/Wind Harmer
5.155
315735AD1-075 GEN1
Solar/Wind Harmer
0.857
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.722
3146776BUCKING
Solar/Wind Harmer
-0.003
3151861LOWMORA
Adder
0.643
237038AE2-054 C
Solar/Wind Helper
0.174
233935AB2-179 C
Solar/Wind Helper
0.775
233987AB2-037 GEN
Solar/Wind Helper
1.413
232417X3-008 C
Solar/Wind Helper
0.14
233923SMA
Solar/Wind Helper
0.453
233997TMININ_4.2
Solar/Wind Helper
0.124
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
207442AE1-156 GEN
Solar/Wind Helper
0.189
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
957921AF2-086 GEN
Solar/Wind Helper
0.234
970221AG2-151 GEN
Solar/Wind Harmer
1.345
963691AG1-221 GEN
Solar/Wind Harmer
2.31
3150241REMNGT4
Adder
12.527
972199AH1-684 GEN
Adder
1.899
3150371LDYSMT1
Adder
12.247
966881AG1-559 GEN
Solar/Wind Harmer
0.308
971781AH1-399 GEN
Solar/Wind Harmer
0.619
961951AG1-038 GEN
Solar/Wind Harmer
1.273
316473AC1-191 GEN
Solar/Wind Harmer
1.038
3142416OLDCHRC
Solar/Wind Harmer
0.959
3141766HARMONY
Solar/Wind Harmer
0.845
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3142946ENON
Solar/Wind Harmer
-0.003
3150221REMNGT2
Adder
12.445
3150211REMNGT1
Adder
12.362
972201AH1-685 GEN
Adder
2.147
972197AH1-683 GEN
Adder
1.979
316447AC1-158 HLD
Solar/Wind Harmer
2.285
972135AH1-637 GEN
Solar/Wind Harmer
1.029
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
9.487
316192AB2-158 GEN
Solar/Wind Harmer
1.18
958261AF2-120 GEN
Solar/Wind Harmer
3.763
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.108
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3145336SMITFLD
Solar/Wind Harmer
-0.036
316375AC2-012 GEN
Solar/Wind Harmer
3.128
3146456SLIGO L269
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.097
3146206CASHIE
Solar/Wind Harmer
-0.008
316023GEN1_S
Solar/Wind Harmer
0.568
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.125
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.662
205932AD2-116_GEN
Solar/Wind Helper
0.386
235063AE1-101 C2
Solar/Wind Helper
1.069
203975AE1-071-GEN
Solar/Wind Helper
1.719
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
219766PARADISE C
Solar/Wind Helper
0.032
20714528FRN_Y2-051
Solar/Wind Helper
0.033
970053AG2-049 GEN
50/50
2.025
3150381LDYSMT2
Adder
12.168
315651AD1-115 GEN
Solar/Wind Harmer
4.651
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.214
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3151201GRAVEL4
Adder
5.93
3151221GRAVEL6
Adder
5.923
3151211GRAVEL5
Adder
5.855
316311AC2-079 GEN
Solar/Wind Harmer
4.537
313526AB2-022
Solar/Wind Harmer
0.24
3146396TANGLEW
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
8.19
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.21
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
971845AH1-439 GEN
Solar/Wind Harmer
4.369
316486AD2-202 GEN
Solar/Wind Harmer
0.206
961791AG1-021 GEN
Solar/Wind Harmer
1.011
316274AC1-208 GEN
Solar/Wind Harmer
0.865
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
959381AF2-229 GEN
Solar/Wind Helper
0.257
232432Z2-076 GEN
Solar/Wind Helper
0.04
230407AD2-065 C
Solar/Wind Helper
0.024
20720728JCB_W1-129
Solar/Wind Helper
0.034
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
209054AE2-059 GEN
Solar/Wind Helper
0.043
209067AE2-060 GEN
Solar/Wind Helper
0.042
3142366NRTHEST
Adder
0.275
3150691DARBY 3
Adder
6.059
3150701DARBY 4
Adder
6.045
315976AC1-164 GENA
Solar/Wind Harmer
2.145
316169AC1-164_GENC
Solar/Wind Harmer
1.853
3142946ENON
Solar/Wind Harmer
-0.001
316294AC1-161 GEN
Solar/Wind Harmer
2.936
316083AB2-161 GEN
Solar/Wind Harmer
1.471
316349AD2-085 GEN
Solar/Wind Harmer
0.799
3146456SLIGO L269
Solar/Wind Harmer
1.06
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.606
316433W1029_GEN2
Solar/Wind Harmer
1.606
316336AC2-165 C
Solar/Wind Harmer
5.487
3152131X4-039 ST
50/50
2.883
3152121X4-039 GT2
50/50
1.832
316415AF1-147_GEN2
Solar/Wind Harmer
1.097
972223AH1-696 GEN
Adder
8.563
3141346CRANES
Adder
0.12
971685AH1-345 GEN
Solar/Wind Harmer
0.96
972219AH1-694 GEN
Adder
1.425
3150351NORNECKC2
Adder
0.869
964211AG1-282 GEN
Solar/Wind Harmer
0.294
316314AB2-024 C
Solar/Wind Harmer
0.812
315742AE1-103 GEN
Solar/Wind Harmer
2.076
3146376EDENTON
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.258
970933AG2-581 GEN
Solar/Wind Harmer
8.024
316365GEN2_N
Solar/Wind Harmer
0.568
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.264
237080AD1-060 GEN
Solar/Wind Helper
0.222
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674828DL_W4-046
Solar/Wind Helper
0.005
219680HOPEWELLV C1
Solar/Wind Helper
0.002
218440SUMMTASSOC C
Solar/Wind Helper
0.01
217208PARK ELE C
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.051
3141426STAFORD
Solar/Wind Harmer
-0.003
316468AD1-105 GEN
Solar/Wind Harmer
1.148
3141913WHIT STONE
Solar/Wind Harmer
-0.01
971285AH1-108 GEN
Adder
0.63
957831AF2-077 GEN
Solar/Wind Harmer
0.281
315697AD1-025 GEN
Solar/Wind Harmer
1.859
315839AE2-212 C
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
5.641
3151081ELIZAR1
Adder
7.381
3151091ELIZAR2
Adder
7.253
316316AC1-027 C
Solar/Wind Harmer
0.277
957871AF2-081 GEN
Solar/Wind Harmer
4.495
316258AE1-075 C
Solar/Wind Harmer
0.216
970673AG2-436 GEN
Solar/Wind Harmer
19.089
316322AB2-045
Solar/Wind Harmer
0.276
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.264
970683AG2-441 GEN
Solar/Wind Harmer
5.694
970681AG2-440 GEN
Solar/Wind Harmer
3.779
970133AG2-095 GEN
Solar/Wind Harmer
1.044
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.697
316017AA1-139 ULT1
Solar/Wind Harmer
0.725
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.039
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.154
3147043LAWRENC
Solar/Wind Harmer
-0.005
316478AD1-087 GEN
Solar/Wind Harmer
0.704
3147133PAMPLIN
Solar/Wind Harmer
-0.025
972255AH1-712 GEN
Adder
36.691
959311AF2-222 GEN
Solar/Wind Harmer
8.394
227287AC2-120 GEN
Solar/Wind Helper
0.492
23777801MSM_W1-116
Solar/Wind Helper
0.131
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232406W1-004 FULL
Solar/Wind Helper
0.305
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
970831AG2-522 GEN
Solar/Wind Harmer
4.03
20390526W1-045 C
Solar/Wind Helper
0.253
233940AF2-379 C
Solar/Wind Helper
0.037
230434AG1-499 GEN
Solar/Wind Helper
0.137
219258KINSLEYDEP C
Solar/Wind Helper
0.046
20673828FLE_V3-070
Solar/Wind Helper
0.05
20676128MHD_W3-029
Solar/Wind Helper
0.056
209027LOR2_Q27
Solar/Wind Helper
0.559
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
316411AF1-147_GEN1
Solar/Wind Harmer
1.097
3150071POSSM 5
Adder
49.547
3150391LDYSMT3
Adder
12.65
316312AB1-027
Solar/Wind Harmer
0.32
316441AF1-014 GEN
Solar/Wind Harmer
0.64
3143526WINTERP
Solar/Wind Harmer
-0.049
944631AF1-128 GEN
Adder
39.787
971317AH1-138 GEN
Solar/Wind Harmer
1.161
315671AE2-027_GEN
Solar/Wind Harmer
1.668
944591AF1-124 GEN
Solar/Wind Harmer
41.27
316072AD1-144
Solar/Wind Harmer
0.182
939411AE1-173 GEN
Solar/Wind Harmer
44.9
940641AE2-051 GEN
Solar/Wind Harmer
8.405
3143336POWHATN
Solar/Wind Harmer
1.057
941031AE2-094 GEN
Solar/Wind Harmer
16.452
971547AH1-271 GEN
Solar/Wind Harmer
2.111
960081AF2-299 GEN
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.172
3144293JTRSVLE
Adder
0.136
972277AH1-723 GEN
Adder
42.756
316129AC1-054 GEN
Solar/Wind Harmer
0.703
316034AC1-036 C
Solar/Wind Harmer
0.149
205916AD1-020 GEN
Solar/Wind Helper
1.485
233944AB2-135 GEN
Solar/Wind Helper
0.357
232408W1-005 C
Solar/Wind Helper
0.305
219907AC1-030 C
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.011
20673628F1S_V4-069
Solar/Wind Helper
0.017
218428ETC SOLAR C
Solar/Wind Helper
0.003
219908AB1-139 C
Solar/Wind Helper
0.043
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.047
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.234
3143526WINTERP
Solar/Wind Harmer
-0.049
944641AF1-129 GEN
Adder
39.347
316185AD1-033 GEN
Solar/Wind Harmer
0.95
3144356SAPONY
Solar/Wind Harmer
0.307
316315AB2-025 C
Solar/Wind Harmer
0.237
972185AH1-677 GEN
Adder
4.322
970099AG2-077 GEN
Solar/Wind Harmer
10.391
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
0.972
3145783HORNRTN
Solar/Wind Harmer
0.778
3145783HORNRTN
Solar/Wind Harmer
0.243
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3144293JTRSVLE
Adder
0.172
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
233946AB2-136 GEN
Solar/Wind Helper
0.343
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
961431AF2-434 GEN
Solar/Wind Helper
0.237
315747AE2-019 GEN
50/50
13.164
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.652
316077AC2-138 C
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
0.884
3151761LOISA E
Adder
11.393
3151721LOISA A
Adder
5.56
316484AD2-074 GEN
Solar/Wind Harmer
2.432
316075AC2-137 C
Solar/Wind Harmer
0.254
315778AD1-151 GEN
Solar/Wind Harmer
8.21
3144216WINCHST
Adder
0.309
3151101ELIZAR3
Adder
7.475
944601AF1-125 GEN
Solar/Wind Harmer
40.48
3143336POWHATN
Solar/Wind Harmer
0.898
966621AG1-532 GEN
Solar/Wind Harmer
0.169
316317KELFORD C
Solar/Wind Harmer
0.381
3145823KELFORD
Solar/Wind Harmer
-0.008
972003AH1-546 GEN
Solar/Wind Harmer
3.341
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.227
3144293JTRSVLE
Adder
0.172
316212AC1-099_GEN
Solar/Wind Harmer
0.702
226910AB2-157 C
Solar/Wind Helper
0.021
237085AD2-009_GEN
Solar/Wind Helper
0.975
233933AB2-153 GEN
Solar/Wind Helper
0.141
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.052
209116AE2-175 GEN
Solar/Wind Helper
1.008
961421AF2-433 GEN
Solar/Wind Helper
0.237
946691AF1-333 GEN
Solar/Wind Helper
0.234
946741AF1-338 GEN
Solar/Wind Helper
0.234
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.53
CPLELTFEXP_CPLE->PJM
CLTF
5.052
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.815
LGEELTFEXP_LGEE->PJM
CLTF
1.797
MECLTFEXP_MEC->PJM
CLTF
4.43
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.321
NYPJM->LTFIMP_NY
CLTF
2.582
TVALTFEXP_TVA->PJM
CLTF
3.176
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.549
WECLTFEXP_WEC->PJM
CLTF
0.958
LAGNLTFEXP_LAGN->PJM
CLTF
6.301

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: 560T571_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 560T571_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.57 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1982.11
MW Contribution:
1.9
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150281M RUN A
Adder
13.356
316044AC1-158 PL1
Solar/Wind Harmer
1.037
316254AC1-120 GEN1
Solar/Wind Harmer
3.935
957971AF2-091 GEN
Solar/Wind Harmer
1.023
3147666LOUISA
Solar/Wind Harmer
-0.039
3151751LOISA D
Adder
5.574
316404AE1-155 C
Solar/Wind Harmer
1.836
3138133OCRAN
Solar/Wind Harmer
-0.006
315662AE1-191 GEN
Solar/Wind Harmer
1.132
316280AD1-041 GEN
Solar/Wind Harmer
0.708
3143096IRON208
Adder
0.348
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.449
316369SG1_INVT
Solar/Wind Harmer
1.63
961611AG1-000B GEN
Solar/Wind Harmer
4.495
3151171GRAVELC
Adder
0.86
316381AD1-082 GEN
Solar/Wind Harmer
0.823
3152131X4-039 ST
50/50
2.888
3152121X4-039 GT2
50/50
1.835
316415AF1-147_GEN2
Solar/Wind Harmer
1.1
972223AH1-696 GEN
Adder
8.389
3141346CRANES
Adder
0.118
971685AH1-345 GEN
Solar/Wind Harmer
0.961
972219AH1-694 GEN
Adder
1.41
3150351NORNECKC2
Adder
0.861
964211AG1-282 GEN
Solar/Wind Harmer
0.291
316314AB2-024 C
Solar/Wind Harmer
0.805
3143526WINTERP
Solar/Wind Harmer
-0.048
944631AF1-128 GEN
Adder
39.483
971317AH1-138 GEN
Solar/Wind Harmer
1.152
315671AE2-027_GEN
Solar/Wind Harmer
1.655
3150151POSSMC1
Adder
1.062
316170AC1-121 GEN2
Solar/Wind Harmer
1.312
316337AD2-073 GEN
Solar/Wind Harmer
0.263
3141726DUNNSVL
Solar/Wind Harmer
-0.038
962861AG1-135 GEN
Solar/Wind Harmer
3.603
3150851SPRUNCC
Adder
0.382
316132AB2-190 GEN1
Solar/Wind Harmer
0.926
315773AC2-141 GEN
Solar/Wind Harmer
3.772
316006AB2-029 C
Solar/Wind Harmer
0.63
316045AC1-158 PL2
Solar/Wind Harmer
3.317
966871AG1-558 GEN
Solar/Wind Harmer
0.288
966871AG1-558 GEN
Solar/Wind Harmer
0.098
3142296MT RD221
Adder
0.268
316156AD2-030 GEN
Solar/Wind Harmer
0.251
315666AE1-190 GEN
Solar/Wind Harmer
0.283
3150671DARBY 1
Adder
5.984
971223AH1-071 GEN
Solar/Wind Harmer
1.162
316240AF1-291 C
Solar/Wind Harmer
0.276
3150991CHESPKB
Adder
0.837
3150991CHESPKB
Adder
0.817
3150301M RUN C
Adder
13.348
3150401LDYSMT4
Adder
12.537
3141906WESTMOR
Solar/Wind Harmer
-0.004
3150981CHESPKA
Adder
0.998
319010AE1-072 C
Solar/Wind Harmer
1.799
315611Z1-036_GEN2
Solar/Wind Harmer
2.143
3130156CHOWAN
Solar/Wind Harmer
-0.009
315816AE2-034 GEN
Solar/Wind Harmer
0.689
971163AH1-040 GEN
Solar/Wind Harmer
8.006
315737AD1-076 GEN
Solar/Wind Harmer
1.601
970087AG2-069 GEN
Solar/Wind Harmer
7.796
957481AF2-042 GEN
Solar/Wind Harmer
25.816
316087AB2-174 GEN
Solar/Wind Harmer
1.175
315693AD1-088 GEN
Solar/Wind Harmer
4.115
3146926FARMVIL
Solar/Wind Harmer
-0.005
971563AH1-280 GEN
Solar/Wind Harmer
1.005
970685AG2-442 GEN
Solar/Wind Harmer
7.025
3146293MARTNCO
Solar/Wind Harmer
0.05
208835TUHI V3-051
Solar/Wind Helper
0.017
23777901MDS_W4-102
Solar/Wind Helper
0.105
233998TM1NIN_3.36
Solar/Wind Helper
0.123
232404W1-003 C
Solar/Wind Helper
0.305
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20715228NPK_W1-113
Solar/Wind Helper
0.045
20720528MAN_W1-024
Solar/Wind Helper
0.016
219919AE1-041 FULL
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
20674928WA_W3-044
Solar/Wind Helper
0.056
20676328BVR_Y1-020
Solar/Wind Helper
0.015
207518AF1-320_GEN
Solar/Wind Helper
0.899
209137AF2-361 C
Solar/Wind Helper
0.709
972213AH1-691 GEN
Adder
2.036
944491AF1-114 GEN
Solar/Wind Harmer
3.009
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
-0.003
3141873WAN 176
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.006
971281AH1-106 GEN
Solar/Wind Harmer
1.515
316382AG1-145 C
Solar/Wind Harmer
0.278
316159AE1-175 C
Solar/Wind Harmer
0.247
316236AE1-162_GEN
Solar/Wind Harmer
0.272
3143316POE
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
0.567
316405AF2-144 C
Solar/Wind Harmer
0.226
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
970533AG2-339 GEN
Solar/Wind Harmer
5.862
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.703
970601AG2-382 GEN
Solar/Wind Harmer
3.67
970581AG2-369 GEN
Solar/Wind Harmer
4.47
946281AF1-292 GEN
Solar/Wind Harmer
0.186
972205AH1-687 GEN
Adder
3.111
3146033SCOT NK
Solar/Wind Harmer
-0.032
3151881LOWMORC
Adder
0.636
3151881LOWMORC
Adder
0.626
205943AE1-185 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.304
228728W1-130C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
961261AF2-417 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.162
959431AF2-234 GEN
Solar/Wind Helper
0.465
316036AC1-147 C
Solar/Wind Harmer
0.242
316093AE2-104_GEN
Solar/Wind Harmer
2.584
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.249
970919AG2-571 GEN
Solar/Wind Harmer
2.65
315607AA1-063A GEN
Solar/Wind Harmer
0.833
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.003
3150181POSSMC2
Adder
1.071
3150181POSSMC2
Adder
1.062
3150181POSSMC2
Adder
1.062
316450AC1-158 RIC
Solar/Wind Harmer
0.276
972195AH1-682 GEN
Adder
1.644
315673AE1-157 GEN
Solar/Wind Harmer
7.709
972189AH1-679 GEN
Adder
1.453
966001AG1-469 GEN
Solar/Wind Harmer
0.184
3150341NORNECKC1
Adder
0.904
3150341NORNECKC1
Adder
0.897
3151731LOISA B
Adder
5.574
316487AF1-042 GEN
Solar/Wind Harmer
1.261
3150681DARBY 2
Adder
5.991
316033AB2-134 GEN
Solar/Wind Harmer
2.944
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.601
316388AE2-253 GEN
Solar/Wind Harmer
0.601
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3130086AYDLETT
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
0.66
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970301AG2-198 GEN
Solar/Wind Harmer
4.1
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.068
3138216PACIFIC
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.576
972215AH1-692 GEN
Adder
2.036
316164AC1-076 GEN
Solar/Wind Harmer
0.882
3141813NORNECK
Solar/Wind Harmer
-0.01
957601AF2-054 GEN
Solar/Wind Harmer
0.282
316233AE1-074 FULL
Solar/Wind Harmer
0.251
971283AH1-107 GEN
Solar/Wind Harmer
1.515
3138283WHITEMARSH
Solar/Wind Harmer
0.014
3151191GRAVEL3
Adder
5.812
315833AF1-017_GEN
Solar/Wind Harmer
1.696
316018AA1-139 ULT2
Solar/Wind Harmer
0.763
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315800Z1-036_GEN1
Solar/Wind Harmer
2.143
971967AH1-528 GEN
Solar/Wind Harmer
16.126
315732AD1-074 GEN1
Solar/Wind Harmer
1.703
3145893MURPHYS
Solar/Wind Harmer
-0.022
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.197
316463AE2-346 GEN
Solar/Wind Harmer
0.134
3145513AHOSKIE
Solar/Wind Harmer
0.072
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3137643SOCKMAN
Solar/Wind Harmer
-0.033
315652AC1-086 GEN
Solar/Wind Harmer
9.218
316426AA2-053 GEN
Solar/Wind Harmer
0.825
316174AB2-169 GEN
Solar/Wind Harmer
1.257
946301AF1-294 GEN
Solar/Wind Harmer
2.061
3144303KENBRDG
Solar/Wind Harmer
-0.006
3151861LOWMORA
Adder
0.616
226929AD2-058 GEN
Solar/Wind Helper
0.144
23779801AA1-109
Solar/Wind Helper
0.218
205917AD1-020 ES
Solar/Wind Helper
0.319
205956AE1-196_GEN
Solar/Wind Helper
0.385
233901CHERRYDALE C
Solar/Wind Helper
0.14
20715028HAN_X4-015
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
20720628TIN_W1-124
Solar/Wind Helper
0.11
20675528CPH_W2-050
Solar/Wind Helper
0.066
20676428JCR_X2-075
Solar/Wind Helper
0.039
20675128HRM_W1-127
Solar/Wind Helper
0.017
209029WAYMART-WD
Solar/Wind Helper
0.442
959421AF2-233 GEN
Solar/Wind Helper
0.233
315835AF2-110_GEN
Solar/Wind Harmer
1.111
316313AB2-026
Solar/Wind Harmer
0.238
316435W1029_GEN3
Solar/Wind Harmer
1.595
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
972187AH1-678 GEN
Adder
2.166
315614AA2-178 GEN
Solar/Wind Harmer
0.919
316065AD1-022 GEN
Solar/Wind Harmer
4.203
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.015
316140AB2-099
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Harmer
-0.033
3146776BUCKING
Solar/Wind Harmer
-0.003
972193AH1-681 GEN
Adder
1.63
232436AB1-176 C
Solar/Wind Helper
0.027
234036AF2-325 C
Solar/Wind Helper
0.025
233994AC2-023 GEN
Solar/Wind Helper
0.577
219912AD2-042 GEN
Solar/Wind Helper
0.089
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.077
20674328GAR_V4-001
Solar/Wind Helper
0.013
946751AF1-339 GEN
Solar/Wind Helper
0.233
237001AB1-127_GEN
Solar/Wind Helper
0.307
233918AB1-142 GEN
Solar/Wind Helper
0.304
228729W2-030 C
Solar/Wind Helper
0.065
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219348LDSOLAR C
Solar/Wind Helper
0.067
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
207530AG1-191 GEN
Solar/Wind Helper
0.038
207439AE1-081 C O1
Solar/Wind Helper
0.011
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.241
963151AG1-164 GEN
Solar/Wind Helper
0.241
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.828
3150221REMNGT2
Adder
12.465
3150211REMNGT1
Adder
12.382
972201AH1-685 GEN
Adder
2.151
316447AC1-158 HLD
Solar/Wind Harmer
2.28
972197AH1-683 GEN
Adder
1.958
315683AE1-153 C
Solar/Wind Harmer
9.479
972135AH1-637 GEN
Solar/Wind Harmer
1.017
966881AG1-559 GEN
Solar/Wind Harmer
0.104
316192AB2-158 GEN
Solar/Wind Harmer
1.176
958261AF2-120 GEN
Solar/Wind Harmer
3.727
3142416OLDCHRC
Solar/Wind Harmer
-0.024
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.099
3142433PROV 92
Solar/Wind Harmer
-0.037
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
315975AC1-164 GENB
Solar/Wind Harmer
0.063
3145336SMITFLD
Solar/Wind Harmer
-0.036
3142366NRTHEST
Adder
0.273
3150691DARBY 3
Adder
6.012
3150701DARBY 4
Adder
5.998
315976AC1-164 GENA
Solar/Wind Harmer
2.128
316169AC1-164_GENC
Solar/Wind Harmer
1.839
3142946ENON
Solar/Wind Harmer
-0.001
316294AC1-161 GEN
Solar/Wind Harmer
2.915
316083AB2-161 GEN
Solar/Wind Harmer
1.46
316349AD2-085 GEN
Solar/Wind Harmer
0.793
3146456SLIGO L269
Solar/Wind Harmer
1.053
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.595
316433W1029_GEN2
Solar/Wind Harmer
1.595
316336AC2-165 C
Solar/Wind Harmer
5.454
315742AE1-103 GEN
Solar/Wind Harmer
2.062
3146376EDENTON
Solar/Wind Harmer
0.257
3146376EDENTON
Solar/Wind Harmer
0.257
970933AG2-581 GEN
Solar/Wind Harmer
7.973
316365GEN2_N
Solar/Wind Harmer
0.564
3146173TUNIS
Solar/Wind Harmer
-0.008
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
970323AG2-213 GEN
Solar/Wind Harmer
3.993
237006AB1-125 GEN
Solar/Wind Helper
0.146
223401AF1-299 GEN
Solar/Wind Helper
0.398
235062AE1-101 C1
Solar/Wind Helper
1.066
232424Y1-079 C
Solar/Wind Helper
0.07
232428Y3-058 C
Solar/Wind Helper
0.203
234015AF2-250 C
Solar/Wind Helper
0.023
230433AD2-135 GEN
Solar/Wind Helper
0.01
214067T20SOLAR
Solar/Wind Helper
0.007
207459AE1-142 C O1
Solar/Wind Helper
0.169
20675428EAM_W2-061
Solar/Wind Helper
0.009
3147666LOUISA
Solar/Wind Harmer
-0.023
3141873WAN 176
Solar/Wind Harmer
1.118
3141843SHACKLE
Adder
0.428
3143096IRON208
Adder
0.348
3143096IRON208
Adder
0.341
3150861SPRUNCD
Adder
0.382
316458AB2-190 GEN2
Solar/Wind Harmer
0.926
961611AG1-000B GEN
Solar/Wind Harmer
1.918
3151171GRAVELC
Adder
1.131
970657AG2-426 GEN
Solar/Wind Harmer
1.817
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.18
316321Z2-027
Solar/Wind Harmer
0.238
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.74
970917AG2-570 GEN
Solar/Wind Harmer
20.934
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.1
3146926FARMVIL
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.008
970257AG2-171 GEN
Solar/Wind Harmer
2.995
971775AH1-396 GEN
Solar/Wind Harmer
0.564
208835TUHI V3-051
Solar/Wind Helper
0.017
237002AB1-128_GEN
Solar/Wind Helper
0.299
235067AD1-061 GEN
Solar/Wind Helper
0.281
233950AC2-186 GEN
Solar/Wind Helper
0.07
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
207454AA2-184 E
Solar/Wind Helper
0.18
217169METRODIV C
Solar/Wind Helper
0.002
963161AG1-165 GEN
Solar/Wind Helper
0.241
208972BECR K09
Solar/Wind Helper
0.178
961331AF2-424 GEN
Solar/Wind Helper
0.237
209071AE2-133 GEN
Solar/Wind Helper
0.042
3152111X4-039 GT1
50/50
1.847
971455AH1-223 GEN
Solar/Wind Harmer
2.315
3150151POSSMC1
Adder
1.062
3150151POSSMC1
Adder
1.062
3150291M RUN B
Adder
13.249
3150331BIRCHWDA
Adder
16.425
3132273ORANGE
Solar/Wind Harmer
-0.002
316223AC1-118
Solar/Wind Harmer
0.268
316203AE2-005 GEN
Solar/Wind Harmer
3.969
970293AG2-193 GEN
Solar/Wind Harmer
1.173
3150921YORKTN3
Adder
2.05
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
40.831
3142956BIRDNECK
Solar/Wind Harmer
0.481
316305AF2-043 C
Solar/Wind Harmer
0.268
316320Y1-086
Solar/Wind Harmer
0.519
3146516WINFALL
Solar/Wind Harmer
-0.009
944011AF1-069 GEN
Solar/Wind Harmer
5.121
315735AD1-075 GEN1
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.058
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.008
3145963POPLR C
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.711
3146776BUCKING
Solar/Wind Harmer
-0.003
3151861LOWMORA
Adder
0.641
237038AE2-054 C
Solar/Wind Helper
0.174
233935AB2-179 C
Solar/Wind Helper
0.773
233987AB2-037 GEN
Solar/Wind Helper
1.408
232417X3-008 C
Solar/Wind Helper
0.14
233923SMA
Solar/Wind Helper
0.452
233997TMININ_4.2
Solar/Wind Helper
0.123
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
207442AE1-156 GEN
Solar/Wind Helper
0.188
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
957921AF2-086 GEN
Solar/Wind Helper
0.233
970221AG2-151 GEN
Solar/Wind Harmer
1.339
970053AG2-049 GEN
50/50
2.017
315651AD1-115 GEN
Solar/Wind Harmer
4.648
3150381LDYSMT2
Adder
12.036
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.212
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3151201GRAVEL4
Adder
5.887
3151221GRAVEL6
Adder
5.88
3151211GRAVEL5
Adder
5.812
316311AC2-079 GEN
Solar/Wind Harmer
4.505
313526AB2-022
Solar/Wind Harmer
0.238
3146396TANGLEW
Solar/Wind Harmer
0.163
315814AE2-033 C
Solar/Wind Harmer
8.134
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.209
961941AG1-037 GEN
Solar/Wind Harmer
0.062
963691AG1-221 GEN
Solar/Wind Harmer
2.315
3150241REMNGT4
Adder
12.548
972199AH1-684 GEN
Adder
1.902
3150371LDYSMT1
Adder
12.114
966881AG1-559 GEN
Solar/Wind Harmer
0.305
971781AH1-399 GEN
Solar/Wind Harmer
0.613
961951AG1-038 GEN
Solar/Wind Harmer
1.261
316473AC1-191 GEN
Solar/Wind Harmer
1.029
3142416OLDCHRC
Solar/Wind Harmer
0.952
3141766HARMONY
Solar/Wind Harmer
0.838
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3142946ENON
Solar/Wind Harmer
-0.003
970133AG2-095 GEN
Solar/Wind Harmer
1.036
315813AE1-149 C
Solar/Wind Harmer
5.656
3145336SMITFLD
Solar/Wind Harmer
-0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.72
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.032
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316181AB2-040 GEN
Solar/Wind Harmer
1.146
3147043LAWRENC
Solar/Wind Harmer
-0.005
316478AD1-087 GEN
Solar/Wind Harmer
0.7
3147133PAMPLIN
Solar/Wind Harmer
-0.025
972255AH1-712 GEN
Adder
36.481
959311AF2-222 GEN
Solar/Wind Harmer
8.345
227287AC2-120 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.131
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232406W1-004 FULL
Solar/Wind Helper
0.305
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.302
230415AB2-049 C
Solar/Wind Helper
0.018
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
316375AC2-012 GEN
Solar/Wind Harmer
3.106
3146456SLIGO L269
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
970937AG2-583 GEN
Solar/Wind Harmer
6.064
3146206CASHIE
Solar/Wind Harmer
-0.008
316023GEN1_S
Solar/Wind Harmer
0.564
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.118
3145683EARLEYS
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.658
205932AD2-116_GEN
Solar/Wind Helper
0.385
235063AE1-101 C2
Solar/Wind Helper
1.066
203975AE1-071-GEN
Solar/Wind Helper
1.715
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.123
219766PARADISE C
Solar/Wind Helper
0.032
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
218440SUMMTASSOC C
Solar/Wind Helper
0.01
217208PARK ELE C
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.051
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
971845AH1-439 GEN
Solar/Wind Harmer
4.345
316486AD2-202 GEN
Solar/Wind Harmer
0.205
961791AG1-021 GEN
Solar/Wind Harmer
1.005
316274AC1-208 GEN
Solar/Wind Harmer
0.859
237030AB1-096 C
Solar/Wind Helper
0.079
237025AB1-124 C
Solar/Wind Helper
0.194
959381AF2-229 GEN
Solar/Wind Helper
0.257
232432Z2-076 GEN
Solar/Wind Helper
0.04
230407AD2-065 C
Solar/Wind Helper
0.024
20720728JCB_W1-129
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
209054AE2-059 GEN
Solar/Wind Helper
0.042
209067AE2-060 GEN
Solar/Wind Helper
0.042
315747AE2-019 GEN
50/50
13.195
3141196NOKESVL
Solar/Wind Harmer
-0.048
972217AH1-693 GEN
Adder
1.654
316077AC2-138 C
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.875
3151761LOISA E
Adder
11.363
3151721LOISA A
Adder
5.545
316484AD2-074 GEN
Solar/Wind Harmer
2.41
316075AC2-137 C
Solar/Wind Harmer
0.252
315778AD1-151 GEN
Solar/Wind Harmer
8.149
3146173TUNIS
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3147133PAMPLIN
Solar/Wind Harmer
-0.006
958211AF2-115 GEN
Solar/Wind Harmer
1.257
237080AD1-060 GEN
Solar/Wind Helper
0.221
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674828DL_W4-046
Solar/Wind Helper
0.005
944591AF1-124 GEN
Solar/Wind Harmer
40.978
316072AD1-144
Solar/Wind Harmer
0.181
939411AE1-173 GEN
Solar/Wind Harmer
44.594
940641AE2-051 GEN
Solar/Wind Harmer
8.349
3143336POWHATN
Solar/Wind Harmer
1.05
941031AE2-094 GEN
Solar/Wind Harmer
16.344
971547AH1-271 GEN
Solar/Wind Harmer
2.097
960081AF2-299 GEN
Solar/Wind Harmer
0.932
3145823KELFORD
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.171
3144293JTRSVLE
Adder
0.135
972277AH1-723 GEN
Adder
42.511
316129AC1-054 GEN
Solar/Wind Harmer
0.698
316034AC1-036 C
Solar/Wind Harmer
0.148
205916AD1-020 GEN
Solar/Wind Helper
1.482
233944AB2-135 GEN
Solar/Wind Helper
0.356
232408W1-005 C
Solar/Wind Helper
0.305
219907AC1-030 C
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.011
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
218428ETC SOLAR C
Solar/Wind Helper
0.003
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.047
20676228FRD_X1-012
Solar/Wind Helper
0.053
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.233
3141426STAFORD
Solar/Wind Harmer
-0.002
316468AD1-105 GEN
Solar/Wind Harmer
1.136
3141913WHIT STONE
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
0.625
957831AF2-077 GEN
Solar/Wind Harmer
0.279
315697AD1-025 GEN
Solar/Wind Harmer
1.845
315839AE2-212 C
Solar/Wind Harmer
0.275
971445AH1-216 GEN
Solar/Wind Harmer
5.601
3151081ELIZAR1
Adder
7.328
3151091ELIZAR2
Adder
7.201
316316AC1-027 C
Solar/Wind Harmer
0.275
957871AF2-081 GEN
Solar/Wind Harmer
4.463
316258AE1-075 C
Solar/Wind Harmer
0.214
970673AG2-436 GEN
Solar/Wind Harmer
18.965
316322AB2-045
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.003
316210AC1-098 GEN
Solar/Wind Harmer
1.256
970683AG2-441 GEN
Solar/Wind Harmer
5.661
970681AG2-440 GEN
Solar/Wind Harmer
3.757
970831AG2-522 GEN
Solar/Wind Harmer
4.005
20390526W1-045 C
Solar/Wind Helper
0.252
233940AF2-379 C
Solar/Wind Helper
0.037
230434AG1-499 GEN
Solar/Wind Helper
0.136
219258KINSLEYDEP C
Solar/Wind Helper
0.045
20673828FLE_V3-070
Solar/Wind Helper
0.05
20676128MHD_W3-029
Solar/Wind Helper
0.055
209027LOR2_Q27
Solar/Wind Helper
0.557
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
316411AF1-147_GEN1
Solar/Wind Harmer
1.1
3150071POSSM 5
Adder
48.541
3150391LDYSMT3
Adder
12.514
316312AB1-027
Solar/Wind Harmer
0.317
316441AF1-014 GEN
Solar/Wind Harmer
0.635
3143526WINTERP
Solar/Wind Harmer
-0.048
944641AF1-129 GEN
Adder
39.056
316185AD1-033 GEN
Solar/Wind Harmer
0.943
3144356SAPONY
Solar/Wind Harmer
0.305
316315AB2-025 C
Solar/Wind Harmer
0.235
972185AH1-677 GEN
Adder
4.294
970099AG2-077 GEN
Solar/Wind Harmer
10.327
962571AG1-106 GEN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.966
3145783HORNRTN
Solar/Wind Harmer
0.773
3145783HORNRTN
Solar/Wind Harmer
0.242
3145783HORNRTN
Solar/Wind Harmer
0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3144293JTRSVLE
Adder
0.171
223402AF1-300 C
Solar/Wind Helper
0.398
238221AF1-254 C O1
Solar/Wind Helper
0.18
235020AA1-095 C
Solar/Wind Helper
0.029
233982AB2-133 GEN
Solar/Wind Helper
0.217
233930AB2-032 GEN
Solar/Wind Helper
0.23
233946AB2-136 GEN
Solar/Wind Helper
0.342
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.305
230511AF1-262
Solar/Wind Helper
0.009
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.097
961431AF2-434 GEN
Solar/Wind Helper
0.236
3144216WINCHST
Adder
0.307
3151101ELIZAR3
Adder
7.422
944601AF1-125 GEN
Solar/Wind Harmer
40.194
3143336POWHATN
Solar/Wind Harmer
0.893
966621AG1-532 GEN
Solar/Wind Harmer
0.168
316317KELFORD C
Solar/Wind Harmer
0.379
3145823KELFORD
Solar/Wind Harmer
-0.008
972003AH1-546 GEN
Solar/Wind Harmer
3.324
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.008
942461AE2-259 GEN
Solar/Wind Harmer
1.22
3144293JTRSVLE
Adder
0.171
316212AC1-099_GEN
Solar/Wind Harmer
0.698
226910AB2-157 C
Solar/Wind Helper
0.021
237085AD2-009_GEN
Solar/Wind Helper
0.972
233933AB2-153 GEN
Solar/Wind Helper
0.141
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.047
20671928W4-073
Solar/Wind Helper
0.051
209116AE2-175 GEN
Solar/Wind Helper
1.005
961421AF2-433 GEN
Solar/Wind Helper
0.236
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.471
CPLELTFEXP_CPLE->PJM
CLTF
5.025
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.711
LGEELTFEXP_LGEE->PJM
CLTF
1.794
MECLTFEXP_MEC->PJM
CLTF
4.421
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.264
NYPJM->LTFIMP_NY
CLTF
2.573
TVALTFEXP_TVA->PJM
CLTF
3.166
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.515
WECLTFEXP_WEC->PJM
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
6.282

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.46 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1925.78
MW Contribution:
1.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
1.834
3147346CASHSCORNER
Solar/Wind Harmer
0.123
972213AH1-691 GEN
Adder
1.49
944491AF1-114 GEN
Solar/Wind Harmer
2.202
971281AH1-106 GEN
Solar/Wind Harmer
1.182
3138133OCRAN
Solar/Wind Harmer
-0.002
3143873LANEXA
Solar/Wind Harmer
-0.004
3141873WAN 176
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.215
316159AE1-175 C
Solar/Wind Harmer
0.192
3143316POE
Solar/Wind Harmer
-0.028
316405AF2-144 C
Solar/Wind Harmer
0.181
316236AE1-162_GEN
Solar/Wind Harmer
0.213
970657AG2-426 GEN
Solar/Wind Harmer
0.444
315747AE2-019 GEN
50/50
12.529
3141196NOKESVL
Solar/Wind Harmer
-0.043
972217AH1-693 GEN
Adder
1.45
3151761LOISA E
Adder
9.471
3151721LOISA A
Adder
4.622
316077AC2-138 C
Solar/Wind Harmer
0.154
3150351NORNECKC2
Adder
0.661
316484AD2-074 GEN
Solar/Wind Harmer
1.834
316075AC2-137 C
Solar/Wind Harmer
0.195
316411AF1-147_GEN1
Solar/Wind Harmer
1.073
3150071POSSM 5
Adder
32.531
3150391LDYSMT3
Adder
9.161
3143526WINTERP
Solar/Wind Harmer
-0.038
316312AB1-027
Solar/Wind Harmer
0.244
316441AF1-014 GEN
Solar/Wind Harmer
0.488
944641AF1-129 GEN
Adder
30.387
316185AD1-033 GEN
Solar/Wind Harmer
0.74
3144356SAPONY
Solar/Wind Harmer
0.241
316315AB2-025 C
Solar/Wind Harmer
0.186
316006AB2-029 C
Solar/Wind Harmer
0.548
316045AC1-158 PL2
Solar/Wind Harmer
2.723
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
3142296MT RD221
Adder
0.206
971223AH1-071 GEN
Solar/Wind Harmer
0.911
3150671DARBY 1
Adder
4.621
315666AE1-190 GEN
Solar/Wind Harmer
0.217
316156AD2-030 GEN
Solar/Wind Harmer
0.193
316240AF1-291 C
Solar/Wind Harmer
0.215
316313AB2-026
Solar/Wind Harmer
0.19
3150991CHESPKB
Adder
0.656
3150991CHESPKB
Adder
0.641
315835AF2-110_GEN
Solar/Wind Harmer
0.873
316435W1029_GEN3
Solar/Wind Harmer
1.256
971761AH1-387 GEN
Solar/Wind Harmer
3.866
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3138216PACIFIC
Solar/Wind Harmer
-0.003
316164AC1-076 GEN
Solar/Wind Harmer
0.727
3150411LDYSMT5
Adder
9.207
972215AH1-692 GEN
Adder
1.49
3141813NORNECK
Solar/Wind Harmer
-0.007
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971283AH1-107 GEN
Solar/Wind Harmer
1.182
957601AF2-054 GEN
Solar/Wind Harmer
0.216
3138283WHITEMARSH
Solar/Wind Harmer
0.011
3151191GRAVEL3
Adder
4.537
315833AF1-017_GEN
Solar/Wind Harmer
1.331
316018AA1-139 ULT2
Solar/Wind Harmer
0.599
3146406KITTY HAWK
Solar/Wind Harmer
0.006
315800Z1-036_GEN1
Solar/Wind Harmer
1.693
971967AH1-528 GEN
Solar/Wind Harmer
12.837
315732AD1-074 GEN1
Solar/Wind Harmer
1.354
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.162
316463AE2-346 GEN
Solar/Wind Harmer
0.107
3145513AHOSKIE
Solar/Wind Harmer
0.058
316450AC1-158 RIC
Solar/Wind Harmer
0.227
966001AG1-469 GEN
Solar/Wind Harmer
0.153
3151731LOISA B
Adder
4.646
3150181POSSMC2
Adder
0.718
3150181POSSMC2
Adder
0.712
3150181POSSMC2
Adder
0.712
972195AH1-682 GEN
Adder
1.204
315673AE1-157 GEN
Solar/Wind Harmer
5.701
972189AH1-679 GEN
Adder
1.102
3150341NORNECKC1
Adder
0.683
3150341NORNECKC1
Adder
0.678
316487AF1-042 GEN
Solar/Wind Harmer
0.96
3150681DARBY 2
Adder
4.627
316033AB2-134 GEN
Solar/Wind Harmer
2.294
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.471
316388AE2-253 GEN
Solar/Wind Harmer
0.471
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3130086AYDLETT
Solar/Wind Harmer
-0.028
3150301M RUN C
Adder
11.683
3147666LOUISA
Solar/Wind Harmer
-0.018
3150401LDYSMT4
Adder
9.178
3141906WESTMOR
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.297
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3137643SOCKMAN
Solar/Wind Harmer
-0.026
316426AA2-053 GEN
Solar/Wind Harmer
0.662
315652AC1-086 GEN
Solar/Wind Harmer
7.388
946301AF1-294 GEN
Solar/Wind Harmer
1.679
316174AB2-169 GEN
Solar/Wind Harmer
1.007
3144303KENBRDG
Solar/Wind Harmer
-0.005
23779801AA1-109
Solar/Wind Helper
0.262
205917AD1-020 ES
Solar/Wind Helper
0.358
226929AD2-058 GEN
Solar/Wind Helper
0.079
205956AE1-196_GEN
Solar/Wind Helper
0.407
233901CHERRYDALE C
Solar/Wind Helper
0.14
20715028HAN_X4-015
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
20720628TIN_W1-124
Solar/Wind Helper
0.11
20675528CPH_W2-050
Solar/Wind Helper
0.065
20676428JCR_X2-075
Solar/Wind Helper
0.039
20675128HRM_W1-127
Solar/Wind Helper
0.017
209029WAYMART-WD
Solar/Wind Helper
0.438
959421AF2-233 GEN
Solar/Wind Helper
0.23
971455AH1-223 GEN
Solar/Wind Harmer
2.258
3150291M RUN B
Adder
11.597
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.712
3150151POSSMC1
Adder
0.712
3150331BIRCHWDA
Adder
11.656
316223AC1-118
Solar/Wind Harmer
0.2
970293AG2-193 GEN
Solar/Wind Harmer
0.906
316203AE2-005 GEN
Solar/Wind Harmer
3.049
3150921YORKTN3
Adder
1.594
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
32.014
3142956BIRDNECK
Solar/Wind Harmer
0.377
316305AF2-043 C
Solar/Wind Harmer
0.21
316320Y1-086
Solar/Wind Harmer
0.408
3146516WINFALL
Solar/Wind Harmer
-0.007
944011AF1-069 GEN
Solar/Wind Harmer
4.06
3146776BUCKING
Solar/Wind Harmer
-0.002
315735AD1-075 GEN1
Solar/Wind Harmer
0.677
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
4.15
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.372
3145963POPLR C
Solar/Wind Harmer
-0.007
237038AE2-054 C
Solar/Wind Helper
0.191
233935AB2-179 C
Solar/Wind Helper
0.776
233987AB2-037 GEN
Solar/Wind Helper
1.415
232417X3-008 C
Solar/Wind Helper
0.14
233923SMA
Solar/Wind Helper
0.454
233997TMININ_4.2
Solar/Wind Helper
0.124
959561AF2-247 GEN
Solar/Wind Helper
0.012
20715728PEM_W1-119
Solar/Wind Helper
0.056
207442AE1-156 GEN
Solar/Wind Helper
0.188
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
207511W3-106 GEN
Solar/Wind Helper
0.015
20674128FR_U2-059
Solar/Wind Helper
0.002
211065PSPA IPP
Solar/Wind Helper
0.085
957921AF2-086 GEN
Solar/Wind Helper
0.231
3150281M RUN A
Adder
11.691
316254AC1-120 GEN1
Solar/Wind Harmer
3.304
316044AC1-158 PL1
Solar/Wind Harmer
0.851
3147666LOUISA
Solar/Wind Harmer
-0.032
3151751LOISA D
Adder
4.646
957971AF2-091 GEN
Solar/Wind Harmer
0.749
316404AE1-155 C
Solar/Wind Harmer
1.394
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
0.87
316280AD1-041 GEN
Solar/Wind Harmer
0.544
3143096IRON208
Adder
0.27
3142543TWELFTH
Solar/Wind Harmer
-0.001
971069AG2-661 GEN
Solar/Wind Harmer
1.128
3138126ROCKLANDING
Solar/Wind Harmer
0.022
316369SG1_INVT
Solar/Wind Harmer
1.27
961611AG1-000B GEN
Solar/Wind Harmer
3.506
3151171GRAVELC
Adder
0.672
316381AD1-082 GEN
Solar/Wind Harmer
0.645
3150981CHESPKA
Adder
0.782
319010AE1-072 C
Solar/Wind Harmer
1.412
315611Z1-036_GEN2
Solar/Wind Harmer
1.693
3130156CHOWAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.546
971163AH1-040 GEN
Solar/Wind Harmer
6.349
315737AD1-076 GEN
Solar/Wind Harmer
1.273
3146926FARMVIL
Solar/Wind Harmer
-0.004
970087AG2-069 GEN
Solar/Wind Harmer
6.243
957481AF2-042 GEN
Solar/Wind Harmer
20.758
971377AH1-170 GEN
Solar/Wind Harmer
0.83
315693AD1-088 GEN
Solar/Wind Harmer
3.317
316087AB2-174 GEN
Solar/Wind Harmer
0.941
971563AH1-280 GEN
Solar/Wind Harmer
0.819
970685AG2-442 GEN
Solar/Wind Harmer
5.722
208835TUHI V3-051
Solar/Wind Helper
0.017
23777901MDS_W4-102
Solar/Wind Helper
0.113
233998TM1NIN_3.36
Solar/Wind Helper
0.124
232404W1-003 C
Solar/Wind Helper
0.306
20715828PEM_W1-120
Solar/Wind Helper
0.056
219276PARKLANDSO C
Solar/Wind Helper
0.052
963711AG1-223 GEN
Solar/Wind Helper
0.037
20715228NPK_W1-113
Solar/Wind Helper
0.045
20720528MAN_W1-024
Solar/Wind Helper
0.016
3141426STAFORD
Solar/Wind Harmer
-0.002
316468AD1-105 GEN
Solar/Wind Harmer
0.85
3141913WHIT STONE
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.486
957831AF2-077 GEN
Solar/Wind Harmer
0.216
315839AE2-212 C
Solar/Wind Harmer
0.214
315697AD1-025 GEN
Solar/Wind Harmer
1.438
316258AE1-075 C
Solar/Wind Harmer
0.171
971445AH1-216 GEN
Solar/Wind Harmer
4.378
3151081ELIZAR1
Adder
5.744
3151091ELIZAR2
Adder
5.644
316316AC1-027 C
Solar/Wind Harmer
0.215
957871AF2-081 GEN
Solar/Wind Harmer
3.504
970673AG2-436 GEN
Solar/Wind Harmer
15.054
316322AB2-045
Solar/Wind Harmer
0.225
3152131X4-039 ST
50/50
2.868
3152121X4-039 GT2
50/50
1.822
316415AF1-147_GEN2
Solar/Wind Harmer
1.073
971685AH1-345 GEN
Solar/Wind Harmer
0.836
972223AH1-696 GEN
Adder
5.622
3141346CRANES
Adder
0.082
972219AH1-694 GEN
Adder
1.032
3150351NORNECKC2
Adder
0.65
964211AG1-282 GEN
Solar/Wind Harmer
0.22
3143526WINTERP
Solar/Wind Harmer
-0.038
219919AE1-041 FULL
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
20674928WA_W3-044
Solar/Wind Helper
0.056
20676328BVR_Y1-020
Solar/Wind Helper
0.015
207518AF1-320_GEN
Solar/Wind Helper
0.895
209137AF2-361 C
Solar/Wind Helper
0.706
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
970533AG2-339 GEN
Solar/Wind Harmer
4.647
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
Adder
2.57
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315733AD1-074 GEN2
Solar/Wind Harmer
1.354
970601AG2-382 GEN
Solar/Wind Harmer
2.923
970581AG2-369 GEN
Solar/Wind Harmer
3.579
946281AF1-292 GEN
Solar/Wind Harmer
0.149
972187AH1-678 GEN
Adder
1.725
315614AA2-178 GEN
Solar/Wind Harmer
0.729
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
316065AD1-022 GEN
Solar/Wind Harmer
3.346
3145893MURPHYS
Solar/Wind Harmer
0.186
3145893MURPHYS
Solar/Wind Harmer
-0.012
316140AB2-099
Solar/Wind Harmer
0.045
972193AH1-681 GEN
Adder
1.345
232436AB1-176 C
Solar/Wind Helper
0.027
234036AF2-325 C
Solar/Wind Helper
0.026
233994AC2-023 GEN
Solar/Wind Helper
0.58
219912AD2-042 GEN
Solar/Wind Helper
0.089
219607WPEMNERT C
Solar/Wind Helper
0.047
219304NAMERICA C
Solar/Wind Helper
0.077
20674328GAR_V4-001
Solar/Wind Helper
0.013
946751AF1-339 GEN
Solar/Wind Helper
0.23
316170AC1-121 GEN2
Solar/Wind Harmer
1.101
3150151POSSMC1
Adder
0.712
316337AD2-073 GEN
Solar/Wind Harmer
0.198
3141726DUNNSVL
Solar/Wind Harmer
-0.029
962861AG1-135 GEN
Solar/Wind Harmer
2.737
3150851SPRUNCC
Adder
0.297
316132AB2-190 GEN1
Solar/Wind Harmer
0.72
315773AC2-141 GEN
Solar/Wind Harmer
2.954
316036AC1-147 C
Solar/Wind Harmer
0.189
316093AE2-104_GEN
Solar/Wind Harmer
2.03
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.119
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.198
315607AA1-063A GEN
Solar/Wind Harmer
0.667
3146263WOODLND
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
237001AB1-127_GEN
Solar/Wind Helper
0.343
233918AB1-142 GEN
Solar/Wind Helper
0.305
3142366NRTHEST
Adder
0.211
3150691DARBY 3
Adder
4.643
3150701DARBY 4
Adder
4.632
315976AC1-164 GENA
Solar/Wind Harmer
1.643
316169AC1-164_GENC
Solar/Wind Harmer
1.419
3142946ENON
Solar/Wind Harmer
-0.001
316294AC1-161 GEN
Solar/Wind Harmer
2.283
316083AB2-161 GEN
Solar/Wind Harmer
1.144
316336AC2-165 C
Solar/Wind Harmer
4.383
316349AD2-085 GEN
Solar/Wind Harmer
0.622
3146456SLIGO L269
Solar/Wind Harmer
0.827
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.256
316433W1029_GEN2
Solar/Wind Harmer
1.256
970053AG2-049 GEN
Adder
1.473
315651AD1-115 GEN
Solar/Wind Harmer
3.931
3150381LDYSMT2
Adder
8.811
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
316059AD1-063 C
Solar/Wind Harmer
0.163
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3151201GRAVEL4
Adder
4.595
3151221GRAVEL6
Adder
4.59
3151211GRAVEL5
Adder
4.537
316311AC2-079 GEN
Solar/Wind Harmer
3.535
313526AB2-022
Solar/Wind Harmer
0.187
3146396TANGLEW
Solar/Wind Harmer
0.128
315814AE2-033 C
Solar/Wind Harmer
6.429
971845AH1-439 GEN
Solar/Wind Harmer
3.565
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.166
961941AG1-037 GEN
Solar/Wind Harmer
0.05
963691AG1-221 GEN
Solar/Wind Harmer
2.258
3150241REMNGT4
Adder
10.998
972199AH1-684 GEN
Adder
1.667
3150371LDYSMT1
Adder
8.868
966881AG1-559 GEN
Solar/Wind Harmer
0.227
971781AH1-399 GEN
Solar/Wind Harmer
0.458
316473AC1-191 GEN
Solar/Wind Harmer
0.787
961951AG1-038 GEN
Solar/Wind Harmer
0.96
3142416OLDCHRC
Solar/Wind Harmer
0.733
3141766HARMONY
Solar/Wind Harmer
0.644
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142946ENON
Solar/Wind Harmer
-0.002
970133AG2-095 GEN
Solar/Wind Harmer
0.806
315813AE1-149 C
Solar/Wind Harmer
4.424
3145336SMITFLD
Solar/Wind Harmer
-0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.565
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.81
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
30.111
316181AB2-040 GEN
Solar/Wind Harmer
0.919
3147043LAWRENC
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.021
316478AD1-087 GEN
Solar/Wind Harmer
0.565
959311AF2-222 GEN
Solar/Wind Harmer
6.794
23777801MSM_W1-116
Solar/Wind Helper
0.157
227287AC2-120 GEN
Solar/Wind Helper
0.31
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232406W1-004 FULL
Solar/Wind Helper
0.306
232434Z2-077 GEN
Solar/Wind Helper
0.076
205941AD2-115 GEN
Solar/Wind Helper
0.303
230415AB2-049 C
Solar/Wind Helper
0.018
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
20714928UPF_X1-085
Solar/Wind Helper
0.003
219918AC2-009 C
Solar/Wind Helper
0.001
316314AB2-024 C
Solar/Wind Harmer
0.618
944631AF1-128 GEN
Adder
30.58
971317AH1-138 GEN
Solar/Wind Harmer
0.894
315671AE2-027_GEN
Solar/Wind Harmer
1.289
3143336POWHATN
Solar/Wind Harmer
0.84
944591AF1-124 GEN
Solar/Wind Harmer
32.129
316072AD1-144
Solar/Wind Harmer
0.142
939411AE1-173 GEN
Solar/Wind Harmer
35.115
940641AE2-051 GEN
Solar/Wind Harmer
6.583
941031AE2-094 GEN
Solar/Wind Harmer
12.958
971547AH1-271 GEN
Solar/Wind Harmer
1.67
3147623JAMES R
Solar/Wind Harmer
0.103
960081AF2-299 GEN
Solar/Wind Harmer
0.746
972277AH1-723 GEN
Adder
35.088
315778AD1-151 GEN
Solar/Wind Harmer
6.347
3144216WINCHST
Adder
0.239
3143336POWHATN
Solar/Wind Harmer
0.714
3151101ELIZAR3
Adder
5.817
944601AF1-125 GEN
Solar/Wind Harmer
31.514
972003AH1-546 GEN
Solar/Wind Harmer
2.743
966621AG1-532 GEN
Solar/Wind Harmer
0.135
942461AE2-259 GEN
Solar/Wind Harmer
0.995
316317KELFORD C
Solar/Wind Harmer
0.304
3145823KELFORD
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.139
315821AE2-092 GEN
Solar/Wind Harmer
1.353
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
226910AB2-157 C
Solar/Wind Helper
0.014
237085AD2-009_GEN
Solar/Wind Helper
1.053
233933AB2-153 GEN
Solar/Wind Helper
0.141
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219612MATRIX C
Solar/Wind Helper
0.014
20716928W4-060COL
Solar/Wind Helper
0.03
20673728F2S_V4-070
Solar/Wind Helper
0.017
217213AMBOY SO C
Solar/Wind Helper
0.017
207437AD2-070 GEN
Solar/Wind Helper
0.079
207510AF2-138 C
Solar/Wind Helper
0.046
20671928W4-073
Solar/Wind Helper
0.051
209116AE2-175 GEN
Solar/Wind Helper
0.998
961421AF2-433 GEN
Solar/Wind Helper
0.233
946691AF1-333 GEN
Solar/Wind Helper
0.23
946741AF1-338 GEN
Solar/Wind Helper
0.23
3146033SCOT NK
Solar/Wind Harmer
-0.026
205943AE1-185 GEN
Solar/Wind Helper
0.41
233915AB1-141 GEN
Solar/Wind Helper
0.305
228728W1-130C
Solar/Wind Helper
0.032
227927V4-067C
Solar/Wind Helper
0.006
219615MILLCREEK C
Solar/Wind Helper
0.016
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
961261AF2-417 GEN
Solar/Wind Helper
0.239
212266LOR1
Solar/Wind Helper
0.16
959431AF2-234 GEN
Solar/Wind Helper
0.459
3141873WAN 176
Solar/Wind Harmer
0.858
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.264
316458AB2-190 GEN2
Solar/Wind Harmer
0.72
961611AG1-000B GEN
Solar/Wind Harmer
1.496
3151171GRAVELC
Adder
0.883
970657AG2-426 GEN
Solar/Wind Harmer
1.423
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.141
316321Z2-027
Solar/Wind Harmer
0.187
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.18
970917AG2-570 GEN
Solar/Wind Harmer
16.739
3146926FARMVIL
Solar/Wind Harmer
-0.004
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
237002AB1-128_GEN
Solar/Wind Helper
0.332
208835TUHI V3-051
Solar/Wind Helper
0.017
235067AD1-061 GEN
Solar/Wind Helper
0.308
233950AC2-186 GEN
Solar/Wind Helper
0.07
219921AF1-264
Solar/Wind Helper
0.03
219914AD2-027 C
Solar/Wind Helper
0.068
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
207454AA2-184 E
Solar/Wind Helper
0.18
217169METRODIV C
Solar/Wind Helper
0.002
963161AG1-165 GEN
Solar/Wind Helper
0.239
208972BECR K09
Solar/Wind Helper
0.176
961331AF2-424 GEN
Solar/Wind Helper
0.234
209071AE2-133 GEN
Solar/Wind Helper
0.042
970257AG2-171 GEN
Solar/Wind Harmer
0.153
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
970301AG2-198 GEN
Solar/Wind Harmer
3.329
313506AB2-031 GEN
Solar/Wind Harmer
0.529
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.054
970323AG2-213 GEN
Solar/Wind Harmer
3.251
237006AB1-125 GEN
Solar/Wind Helper
0.175
228729W2-030 C
Solar/Wind Helper
0.065
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219348LDSOLAR C
Solar/Wind Helper
0.067
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
20671828STAW2-080
Solar/Wind Helper
0.015
217209CENTRL HS C
Solar/Wind Helper
0.005
207530AG1-191 GEN
Solar/Wind Helper
0.038
207439AE1-081 C O1
Solar/Wind Helper
0.011
211065PSPA IPP
Solar/Wind Helper
0.085
961301AF2-421 GEN
Solar/Wind Helper
0.239
963151AG1-164 GEN
Solar/Wind Helper
0.239
961341AF2-425 GEN
Solar/Wind Helper
0.234
212507AE2-042_GEN
Solar/Wind Helper
0.818
223401AF1-299 GEN
Solar/Wind Helper
0.386
235062AE1-101 C1
Solar/Wind Helper
1.173
232424Y1-079 C
Solar/Wind Helper
0.07
232428Y3-058 C
Solar/Wind Helper
0.204
234015AF2-250 C
Solar/Wind Helper
0.023
230433AD2-135 GEN
Solar/Wind Helper
0.01
214067T20SOLAR
Solar/Wind Helper
0.007
207459AE1-142 C O1
Solar/Wind Helper
0.169
20675428EAM_W2-061
Solar/Wind Helper
0.009
3150221REMNGT2
Adder
10.925
3150211REMNGT1
Adder
10.853
972201AH1-685 GEN
Adder
1.885
316447AC1-158 HLD
Solar/Wind Harmer
1.872
315683AE1-153 C
Solar/Wind Harmer
8.072
316192AB2-158 GEN
Solar/Wind Harmer
0.957
972197AH1-683 GEN
Adder
1.433
966881AG1-559 GEN
Solar/Wind Harmer
0.078
972135AH1-637 GEN
Solar/Wind Harmer
0.749
958261AF2-120 GEN
Solar/Wind Harmer
2.829
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3141766HARMONY
Solar/Wind Harmer
-0.001
971777AH1-397 GEN
Solar/Wind Harmer
0.844
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
315975AC1-164 GENB
Solar/Wind Harmer
0.049
3145336SMITFLD
Solar/Wind Harmer
-0.028
316375AC2-012 GEN
Solar/Wind Harmer
2.434
3146456SLIGO L269
Solar/Wind Harmer
-0.007
970937AG2-583 GEN
Solar/Wind Harmer
4.944
3145663CRESWEL
Solar/Wind Harmer
-0.019
316023GEN1_S
Solar/Wind Harmer
0.45
3146206CASHIE
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3156021HOLLOMANSOL
Solar/Wind Harmer
0.892
3145683EARLEYS
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.529
235063AE1-101 C2
Solar/Wind Helper
1.173
315742AE1-103 GEN
Solar/Wind Harmer
1.629
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
970933AG2-581 GEN
Solar/Wind Harmer
6.362
316365GEN2_N
Solar/Wind Harmer
0.45
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
958211AF2-115 GEN
Solar/Wind Harmer
1.024
237080AD1-060 GEN
Solar/Wind Helper
0.243
219904AC1-010 C
Solar/Wind Helper
0.036
219906AC1-017 C
Solar/Wind Helper
0.025
20720828JCB_W4-025
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
20742028HF_AC1-207
Solar/Wind Helper
0.082
218438BLK ROCK C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
20674828DL_W4-046
Solar/Wind Helper
0.005
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
961791AG1-021 GEN
Solar/Wind Harmer
0.819
316486AD2-202 GEN
Solar/Wind Harmer
0.166
237030AB1-096 C
Solar/Wind Helper
0.095
237025AB1-124 C
Solar/Wind Helper
0.234
959381AF2-229 GEN
Solar/Wind Helper
0.283
232432Z2-076 GEN
Solar/Wind Helper
0.04
230407AD2-065 C
Solar/Wind Helper
0.024
20720728JCB_W1-129
Solar/Wind Helper
0.033
207408W3-077 C
Solar/Wind Helper
0.048
964851AG1-348 GEN
Solar/Wind Helper
0.036
209067AE2-060 GEN
Solar/Wind Helper
0.042
209054AE2-059 GEN
Solar/Wind Helper
0.042
205932AD2-116_GEN
Solar/Wind Helper
0.407
203975AE1-071-GEN
Solar/Wind Helper
1.876
232426Y1-080 FULL
Solar/Wind Helper
0.023
233996TM1833_GEN
Solar/Wind Helper
0.124
219766PARADISE C
Solar/Wind Helper
0.032
20714528FRN_Y2-051
Solar/Wind Helper
0.033
219680HOPEWELLV C1
Solar/Wind Helper
0.002
218440SUMMTASSOC C
Solar/Wind Helper
0.009
217208PARK ELE C
Solar/Wind Helper
0.003
20674628WNG_W3-110
Solar/Wind Helper
0.051
3145823KELFORD
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.139
3144293JTRSVLE
Adder
0.11
3145783HORNRTN
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.007
316034AC1-036 C
Solar/Wind Harmer
0.12
205916AD1-020 GEN
Solar/Wind Helper
1.663
233944AB2-135 GEN
Solar/Wind Helper
0.358
232408W1-005 C
Solar/Wind Helper
0.306
219907AC1-030 C
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.011
20673628F1S_V4-069
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
218428ETC SOLAR C
Solar/Wind Helper
0.003
207484AF2-139 C O1
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.047
20676228FRD_X1-012
Solar/Wind Helper
0.052
20675828AU_W4-064
Solar/Wind Helper
0.017
946731AF1-337 GEN
Solar/Wind Helper
0.23
970683AG2-441 GEN
Solar/Wind Harmer
4.61
970681AG2-440 GEN
Solar/Wind Harmer
3.06
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
20390526W1-045 C
Solar/Wind Helper
0.278
233940AF2-379 C
Solar/Wind Helper
0.037
230434AG1-499 GEN
Solar/Wind Helper
0.136
219258KINSLEYDEP C
Solar/Wind Helper
0.045
20673828FLE_V3-070
Solar/Wind Helper
0.05
20676128MHD_W3-029
Solar/Wind Helper
0.055
209027LOR2_Q27
Solar/Wind Helper
0.551
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
972185AH1-677 GEN
Adder
3.415
970099AG2-077 GEN
Solar/Wind Harmer
8.303
962571AG1-106 GEN
Solar/Wind Harmer
0.944
3144293JTRSVLE
Adder
0.139
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.621
3145783HORNRTN
Solar/Wind Harmer
0.194
3145783HORNRTN
Solar/Wind Harmer
0.078
3145796HORNRTN
Solar/Wind Harmer
-0.019
223402AF1-300 C
Solar/Wind Helper
0.386
238221AF1-254 C O1
Solar/Wind Helper
0.198
235020AA1-095 C
Solar/Wind Helper
0.031
233982AB2-133 GEN
Solar/Wind Helper
0.218
233930AB2-032 GEN
Solar/Wind Helper
0.231
233946AB2-136 GEN
Solar/Wind Helper
0.343
233952AC2-187 GEN
Solar/Wind Helper
0.14
233954AC2-188 GEN
Solar/Wind Helper
0.14
232410W1-006 C
Solar/Wind Helper
0.306
230511AF1-262
Solar/Wind Helper
0.009
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
20675928HOL_W4-097
Solar/Wind Helper
0.029
207471AF2-354 C
Solar/Wind Helper
0.096
961431AF2-434 GEN
Solar/Wind Helper
0.233
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.752
CPLELTFEXP_CPLE->PJM
CLTF
4.221
SIGELTFEXP_SIGE->PJM
CLTF
0.135
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.589
LGEELTFEXP_LGEE->PJM
CLTF
1.748
MECLTFEXP_MEC->PJM
CLTF
4.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.807
NYPJM->LTFIMP_NY
CLTF
2.537
TVALTFEXP_TVA->PJM
CLTF
2.93
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.743
WECLTFEXP_WEC->PJM
CLTF
0.938
LAGNLTFEXP_LAGN->PJM
CLTF
5.819

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.14 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3165.31
MW Contribution:
2.38
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150181POSSMC2
50/50
1.965
3150181POSSMC2
50/50
1.949
3150181POSSMC2
50/50
1.949
972195AH1-682 GEN
50/50
2.904
315673AE1-157 GEN
Solar/Wind Harmer
12.782
972189AH1-679 GEN
Adder
2.385
3150341NORNECKC1
Adder
1.489
3150341NORNECKC1
Adder
1.477
316487AF1-042 GEN
Solar/Wind Harmer
2.07
3150681DARBY 2
Adder
9.762
316450AC1-158 RIC
Solar/Wind Harmer
0.396
316033AB2-134 GEN
Solar/Wind Harmer
4.783
3145506HICKORY
Solar/Wind Harmer
-0.058
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316339AD2-160 GEN
Solar/Wind Harmer
0.975
316388AE2-253 GEN
Solar/Wind Harmer
0.975
3137176SLIGO L2192
Solar/Wind Harmer
-0.057
3130086AYDLETT
Solar/Wind Harmer
-0.058
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
966001AG1-469 GEN
Solar/Wind Harmer
0.266
3151731LOISA B
Adder
8.126
313506AB2-031 GEN
Solar/Wind Harmer
1.073
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
0.11
970301AG2-198 GEN
Solar/Wind Harmer
6.602
3145933PARMELE
Solar/Wind Harmer
-0.026
3145933PARMELE
Solar/Wind Harmer
-0.013
970323AG2-213 GEN
Solar/Wind Harmer
6.463
223401AF1-299 GEN
Solar/Wind Helper
0.71
232424Y1-079 C
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.33
234015AF2-250 C
Solar/Wind Helper
0.037
3140676OCCOQUN
50/50
0.023
972213AH1-691 GEN
50/50
3.596
971531AH1-263 GEN
50/50
25.524
944491AF1-114 GEN
Solar/Wind Harmer
5.021
3138133OCRAN
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.003
3143873LANEXA
Solar/Wind Harmer
-0.009
316382AG1-145 C
Solar/Wind Harmer
0.452
316159AE1-175 C
Solar/Wind Harmer
0.403
971281AH1-106 GEN
Solar/Wind Harmer
2.444
316236AE1-162_GEN
Solar/Wind Harmer
0.442
3143316POE
Solar/Wind Harmer
-0.058
970657AG2-426 GEN
Solar/Wind Harmer
0.92
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
316405AF2-144 C
Solar/Wind Harmer
0.362
970533AG2-339 GEN
Solar/Wind Harmer
9.467
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
3147346CASHSCORNER
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315733AD1-074 GEN2
Solar/Wind Harmer
2.771
970601AG2-382 GEN
Solar/Wind Harmer
5.972
970581AG2-369 GEN
Solar/Wind Harmer
7.245
946281AF1-292 GEN
Solar/Wind Harmer
0.302
3146033SCOT NK
Solar/Wind Harmer
-0.053
972205AH1-687 GEN
Adder
4.951
233915AB1-141 GEN
Solar/Wind Helper
0.494
957191AF2-013 GEN
50/50
14.107
3150691DARBY 3
Adder
9.796
3150701DARBY 4
Adder
9.773
3142366NRTHEST
Adder
0.445
315976AC1-164 GENA
Solar/Wind Harmer
3.472
316169AC1-164_GENC
Solar/Wind Harmer
3
3142946ENON
Solar/Wind Harmer
-0.002
316294AC1-161 GEN
Solar/Wind Harmer
4.728
316083AB2-161 GEN
Solar/Wind Harmer
2.37
316349AD2-085 GEN
Solar/Wind Harmer
1.287
3146456SLIGO L269
Solar/Wind Harmer
1.708
3146386ELIZ CT
Solar/Wind Harmer
-0.014
316431W1029_GEN1
Solar/Wind Harmer
2.59
316433W1029_GEN2
Solar/Wind Harmer
2.59
315742AE1-103 GEN
Solar/Wind Harmer
3.349
3146376EDENTON
Solar/Wind Harmer
0.417
3146376EDENTON
Solar/Wind Harmer
0.417
316336AC2-165 C
Solar/Wind Harmer
8.722
970933AG2-581 GEN
Solar/Wind Harmer
12.891
316365GEN2_N
Solar/Wind Harmer
0.916
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.013
3147133PAMPLIN
Solar/Wind Harmer
-0.01
958211AF2-115 GEN
Solar/Wind Harmer
2.029
3150021OMF B
50/50
0.31
3150371LDYSMT1
50/50
21.396
966881AG1-559 GEN
Solar/Wind Harmer
0.505
971781AH1-399 GEN
Solar/Wind Harmer
1.013
961951AG1-038 GEN
Solar/Wind Harmer
2.07
316473AC1-191 GEN
Solar/Wind Harmer
1.685
3142416OLDCHRC
Solar/Wind Harmer
1.554
3141766HARMONY
Solar/Wind Harmer
1.371
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
3142946ENON
Solar/Wind Harmer
-0.005
970133AG2-095 GEN
Solar/Wind Harmer
1.685
3145336SMITFLD
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
9.176
316017AA1-139 ULT1
Solar/Wind Harmer
1.169
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.674
3145273HOLLAND
Solar/Wind Harmer
-0.011
3146376EDENTON
Solar/Wind Harmer
-0.014
3150241REMNGT4
Adder
15.69
972199AH1-684 GEN
Adder
2.379
3146206CASHIE
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.864
3147043LAWRENC
Solar/Wind Harmer
-0.008
316478AD1-087 GEN
Solar/Wind Harmer
1.135
972255AH1-712 GEN
Adder
59.346
3147133PAMPLIN
Solar/Wind Harmer
-0.041
959311AF2-222 GEN
Solar/Wind Harmer
13.501
227287AC2-120 GEN
Solar/Wind Helper
1.296
232422X3-066 FULL
Solar/Wind Helper
0.112
233964AF2-378 GEN
Solar/Wind Helper
0.041
232406W1-004 FULL
Solar/Wind Helper
0.494
232434Z2-077 GEN
Solar/Wind Helper
0.124
970053AG2-049 GEN
50/50
2.78
3150381LDYSMT2
50/50
21.258
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
316059AD1-063 C
Solar/Wind Harmer
0.347
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
3151201GRAVEL4
Adder
9.562
3151221GRAVEL6
Adder
9.551
3151211GRAVEL5
Adder
9.441
316311AC2-079 GEN
Solar/Wind Harmer
7.311
315651AD1-115 GEN
Solar/Wind Harmer
6.333
313526AB2-022
Solar/Wind Harmer
0.387
3146396TANGLEW
Solar/Wind Harmer
0.264
315814AE2-033 C
Solar/Wind Harmer
13.181
3146206CASHIE
Solar/Wind Harmer
-0.014
316318V4-068
Solar/Wind Harmer
0.34
961941AG1-037 GEN
Solar/Wind Harmer
0.102
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.013
3146043SEABORD
Solar/Wind Harmer
-0.013
316486AD2-202 GEN
Solar/Wind Harmer
0.332
971845AH1-439 GEN
Solar/Wind Harmer
6.949
316274AC1-208 GEN
Solar/Wind Harmer
1.402
961791AG1-021 GEN
Solar/Wind Harmer
1.623
232432Z2-076 GEN
Solar/Wind Helper
0.065
3150011OMF A
50/50
0.31
972197AH1-683 GEN
50/50
3.458
972135AH1-637 GEN
Solar/Wind Harmer
1.693
966881AG1-559 GEN
Solar/Wind Harmer
0.173
958261AF2-120 GEN
Solar/Wind Harmer
6.126
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.796
3142433PROV 92
Solar/Wind Harmer
-0.061
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
315975AC1-164 GENB
Solar/Wind Harmer
0.103
316447AC1-158 HLD
Solar/Wind Harmer
3.264
316192AB2-158 GEN
Solar/Wind Harmer
1.754
3145336SMITFLD
Solar/Wind Harmer
-0.058
316375AC2-012 GEN
Solar/Wind Harmer
5.039
3146456SLIGO L269
Solar/Wind Harmer
-0.014
315683AE1-153 C
Solar/Wind Harmer
13.012
3145663CRESWEL
Solar/Wind Harmer
-0.039
3150221REMNGT2
Adder
15.587
3150211REMNGT1
Adder
15.484
972201AH1-685 GEN
Adder
2.689
3146206CASHIE
Solar/Wind Harmer
-0.014
316023GEN1_S
Solar/Wind Harmer
0.916
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.819
3145683EARLEYS
Solar/Wind Harmer
-0.013
970937AG2-583 GEN
Solar/Wind Harmer
9.671
3147043LAWRENC
Adder
1.069
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.2
3150091POSSM6B
50/50
1.449
966871AG1-558 GEN
Solar/Wind Harmer
0.471
966871AG1-558 GEN
Solar/Wind Harmer
0.161
3142296MT RD221
Adder
0.438
316156AD2-030 GEN
Solar/Wind Harmer
0.41
315666AE1-190 GEN
Solar/Wind Harmer
0.463
3150671DARBY 1
Adder
9.75
316045AC1-158 PL2
Solar/Wind Harmer
4.749
971223AH1-071 GEN
Solar/Wind Harmer
1.867
316240AF1-291 C
Solar/Wind Harmer
0.449
3150991CHESPKB
Adder
1.358
3150991CHESPKB
Adder
1.326
315835AF2-110_GEN
Solar/Wind Harmer
1.803
316435W1029_GEN3
Solar/Wind Harmer
2.59
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
316313AB2-026
Solar/Wind Harmer
0.381
316006AB2-029 C
Solar/Wind Harmer
0.802
315614AA2-178 GEN
Solar/Wind Harmer
1.494
972187AH1-678 GEN
Adder
3.503
316065AD1-022 GEN
Solar/Wind Harmer
6.84
3145893MURPHYS
Solar/Wind Harmer
0.38
3145893MURPHYS
Solar/Wind Harmer
-0.024
316140AB2-099
Solar/Wind Harmer
0.091
3146776BUCKING
Solar/Wind Harmer
-0.052
3146776BUCKING
Solar/Wind Harmer
-0.004
972193AH1-681 GEN
Adder
2.652
316005AA1-067
Solar/Wind Harmer
0.261
232436AB1-176 C
Solar/Wind Helper
0.044
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.937
3150411LDYSMT5
50/50
22.212
972215AH1-692 GEN
50/50
3.596
3141813NORNECK
Solar/Wind Harmer
-0.016
957601AF2-054 GEN
Solar/Wind Harmer
0.461
3138283WHITEMARSH
Solar/Wind Harmer
0.023
316233AE1-074 FULL
Solar/Wind Harmer
0.405
971283AH1-107 GEN
Solar/Wind Harmer
2.444
316164AC1-076 GEN
Solar/Wind Harmer
1.258
3151191GRAVEL3
Adder
9.441
315833AF1-017_GEN
Solar/Wind Harmer
2.753
316018AA1-139 ULT2
Solar/Wind Harmer
1.238
3146406KITTY HAWK
Solar/Wind Harmer
0.012
315800Z1-036_GEN1
Solar/Wind Harmer
3.483
971967AH1-528 GEN
Solar/Wind Harmer
26.063
315732AD1-074 GEN1
Solar/Wind Harmer
2.771
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
316463AE2-346 GEN
Solar/Wind Harmer
0.218
3145513AHOSKIE
Solar/Wind Harmer
0.118
3145513AHOSKIE
Solar/Wind Harmer
-0.013
970085AG2-068 GEN
Solar/Wind Harmer
8.424
3137643SOCKMAN
Solar/Wind Harmer
-0.053
315652AC1-086 GEN
Solar/Wind Harmer
15.006
316426AA2-053 GEN
Solar/Wind Harmer
1.343
316174AB2-169 GEN
Solar/Wind Harmer
2.049
946301AF1-294 GEN
Solar/Wind Harmer
3.327
3144303KENBRDG
Solar/Wind Harmer
-0.01
226929AD2-058 GEN
Solar/Wind Helper
0.404
233901CHERRYDALE C
Solar/Wind Helper
0.227
3150101POSSM6S
50/50
2.207
3150401LDYSMT4
50/50
22.143
3141906WESTMOR
Solar/Wind Harmer
-0.007
3141873WAN 176
Solar/Wind Harmer
1.828
3141843SHACKLE
Adder
0.7
3143096IRON208
Adder
0.566
3143096IRON208
Adder
0.555
3150861SPRUNCD
Adder
0.619
316458AB2-190 GEN2
Solar/Wind Harmer
1.504
3147666LOUISA
Solar/Wind Harmer
-0.034
961611AG1-000B GEN
Solar/Wind Harmer
3.116
3151171GRAVELC
Adder
1.838
970657AG2-426 GEN
Solar/Wind Harmer
2.949
3144873MCLAUGH
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.292
316321Z2-027
Solar/Wind Harmer
0.386
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3150301M RUN C
Adder
16.761
3156081AA2-088 GEN
Solar/Wind Harmer
4.454
970917AG2-570 GEN
Solar/Wind Harmer
33.913
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316190AA2-174 GEN
Solar/Wind Harmer
0.163
3146926FARMVIL
Solar/Wind Harmer
-0.008
3145933PARMELE
Solar/Wind Harmer
-0.013
970257AG2-171 GEN
Solar/Wind Harmer
4.847
971775AH1-396 GEN
Solar/Wind Harmer
0.912
208835TUHI V3-051
Solar/Wind Helper
0.028
233950AC2-186 GEN
Solar/Wind Helper
0.113
957971AF2-091 GEN
Solar/Wind Harmer
1.707
316404AE1-155 C
Solar/Wind Harmer
3.018
3138133OCRAN
Solar/Wind Harmer
-0.009
315662AE1-191 GEN
Solar/Wind Harmer
1.851
316280AD1-041 GEN
Solar/Wind Harmer
1.157
3143096IRON208
Adder
0.566
316044AC1-158 PL1
Solar/Wind Harmer
1.484
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.015
3138126ROCKLANDING
Solar/Wind Harmer
0.046
971069AG2-661 GEN
Solar/Wind Harmer
2.354
316369SG1_INVT
Solar/Wind Harmer
2.649
3147666LOUISA
Solar/Wind Harmer
-0.059
961611AG1-000B GEN
Solar/Wind Harmer
7.302
3151171GRAVELC
Adder
1.397
316381AD1-082 GEN
Solar/Wind Harmer
1.336
3150981CHESPKA
Adder
1.619
316254AC1-120 GEN1
Solar/Wind Harmer
5.447
319010AE1-072 C
Solar/Wind Harmer
2.919
315611Z1-036_GEN2
Solar/Wind Harmer
3.483
3151751LOISA D
Adder
8.126
3130156CHOWAN
Solar/Wind Harmer
-0.014
3150281M RUN A
Adder
16.771
315816AE2-034 GEN
Solar/Wind Harmer
1.121
971163AH1-040 GEN
Solar/Wind Harmer
13.019
315737AD1-076 GEN
Solar/Wind Harmer
2.605
970087AG2-069 GEN
Solar/Wind Harmer
12.637
316087AB2-174 GEN
Solar/Wind Harmer
1.91
957481AF2-042 GEN
Solar/Wind Harmer
41.796
315693AD1-088 GEN
Solar/Wind Harmer
6.657
3146926FARMVIL
Solar/Wind Harmer
-0.008
3146293MARTNCO
Solar/Wind Harmer
0.081
971563AH1-280 GEN
Solar/Wind Harmer
1.623
970685AG2-442 GEN
Solar/Wind Harmer
11.348
208835TUHI V3-051
Solar/Wind Helper
0.028
233998TM1NIN_3.36
Solar/Wind Helper
0.2
232404W1-003 C
Solar/Wind Helper
0.494
315785AD2-033 C
Solar/Wind Harmer
1.614
3150151POSSMC1
50/50
1.949
3150151POSSMC1
50/50
1.949
3150331BIRCHWDA
50/50
29.448
3150501FRIVERG
50/50
1.196
316223AC1-118
Solar/Wind Harmer
0.444
316203AE2-005 GEN
Solar/Wind Harmer
6.488
970293AG2-193 GEN
Solar/Wind Harmer
1.912
3150921YORKTN3
Adder
3.335
3144536CHRHLND
Solar/Wind Harmer
-0.002
944581AF1-123 GEN
Solar/Wind Harmer
66.227
3142956BIRDNECK
Solar/Wind Harmer
0.781
316305AF2-043 C
Solar/Wind Harmer
0.435
316320Y1-086
Solar/Wind Harmer
0.842
3132273ORANGE
Solar/Wind Harmer
-0.003
3146516WINFALL
Solar/Wind Harmer
-0.014
944011AF1-069 GEN
Solar/Wind Harmer
8.27
3150291M RUN B
Adder
16.636
315735AD1-075 GEN1
Solar/Wind Harmer
1.385
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
-0.014
3146263WOODLND
Solar/Wind Harmer
-0.013
3145963POPLR C
Solar/Wind Harmer
-0.013
316011AB1-132 GEN
Solar/Wind Harmer
2.786
3146776BUCKING
Solar/Wind Harmer
-0.005
233935AB2-179 C
Solar/Wind Helper
1.256
233987AB2-037 GEN
Solar/Wind Helper
2.288
232417X3-008 C
Solar/Wind Helper
0.227
233923SMA
Solar/Wind Helper
0.733
233997TMININ_4.2
Solar/Wind Helper
0.2
3150151POSSMC1
50/50
1.949
316337AD2-073 GEN
Solar/Wind Harmer
0.435
3141726DUNNSVL
Solar/Wind Harmer
-0.063
962861AG1-135 GEN
Solar/Wind Harmer
5.92
3150851SPRUNCC
Adder
0.619
316132AB2-190 GEN1
Solar/Wind Harmer
1.504
315773AC2-141 GEN
Solar/Wind Harmer
6.117
316036AC1-147 C
Solar/Wind Harmer
0.392
316170AC1-121 GEN2
Solar/Wind Harmer
1.816
316093AE2-104_GEN
Solar/Wind Harmer
4.194
3146516WINFALL
Solar/Wind Harmer
-0.046
3146516WINFALL
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
0.404
970919AG2-571 GEN
Solar/Wind Harmer
4.293
315607AA1-063A GEN
Solar/Wind Harmer
1.355
3146263WOODLND
Solar/Wind Harmer
-0.013
3145963POPLR C
Solar/Wind Harmer
-0.013
3146776BUCKING
Solar/Wind Harmer
-0.005
233918AB1-142 GEN
Solar/Wind Helper
0.494
3150071POSSM 5
50/50
89.066
3150391LDYSMT3
50/50
22.101
316312AB1-027
Solar/Wind Harmer
0.518
316441AF1-014 GEN
Solar/Wind Harmer
1.037
3143526WINTERP
Solar/Wind Harmer
-0.078
944641AF1-129 GEN
Adder
63.441
316185AD1-033 GEN
Solar/Wind Harmer
1.53
3144356SAPONY
Solar/Wind Harmer
0.495
316315AB2-025 C
Solar/Wind Harmer
0.382
972185AH1-677 GEN
Adder
6.942
970099AG2-077 GEN
Solar/Wind Harmer
16.718
962571AG1-106 GEN
Solar/Wind Harmer
1.917
3145783HORNRTN
Solar/Wind Harmer
1.573
3145783HORNRTN
Solar/Wind Harmer
1.258
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
3145796HORNRTN
Solar/Wind Harmer
-0.039
3144293JTRSVLE
Adder
0.276
223402AF1-300 C
Solar/Wind Helper
0.71
233982AB2-133 GEN
Solar/Wind Helper
0.353
233930AB2-032 GEN
Solar/Wind Helper
0.374
233946AB2-136 GEN
Solar/Wind Helper
0.555
232410W1-006 C
Solar/Wind Helper
0.494
233952AC2-187 GEN
Solar/Wind Helper
0.227
233954AC2-188 GEN
Solar/Wind Helper
0.227
3150081POSSM6A
50/50
1.449
316077AC2-138 C
Solar/Wind Harmer
0.336
3150351NORNECKC2
Adder
1.441
316484AD2-074 GEN
Solar/Wind Harmer
3.957
316075AC2-137 C
Solar/Wind Harmer
0.412
3144216WINCHST
Adder
0.5
315778AD1-151 GEN
Solar/Wind Harmer
13.243
3151101ELIZAR3
Adder
12.041
944601AF1-125 GEN
Solar/Wind Harmer
65.193
3143336POWHATN
Solar/Wind Harmer
1.429
3151761LOISA E
Adder
16.567
3151721LOISA A
Adder
8.084
972217AH1-693 GEN
Adder
2.069
966621AG1-532 GEN
Solar/Wind Harmer
0.273
3141196NOKESVL
Solar/Wind Harmer
-0.054
316317KELFORD C
Solar/Wind Harmer
0.617
3145823KELFORD
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.013
316212AC1-099_GEN
Solar/Wind Harmer
1.138
942461AE2-259 GEN
Solar/Wind Harmer
1.963
972003AH1-546 GEN
Solar/Wind Harmer
5.292
3144293JTRSVLE
Adder
0.276
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
226910AB2-157 C
Solar/Wind Helper
0.05
233933AB2-153 GEN
Solar/Wind Helper
0.228
3141316ARNOLDS
50/50
0.022
3141426STAFORD
Solar/Wind Harmer
-0.004
316468AD1-105 GEN
Solar/Wind Harmer
1.878
3141913WHIT STONE
Solar/Wind Harmer
-0.015
957831AF2-077 GEN
Solar/Wind Harmer
0.455
971285AH1-108 GEN
Adder
1.013
315697AD1-025 GEN
Solar/Wind Harmer
2.998
315839AE2-212 C
Solar/Wind Harmer
0.446
971445AH1-216 GEN
Solar/Wind Harmer
9.094
3151081ELIZAR1
Adder
11.889
3151091ELIZAR2
Adder
11.683
316316AC1-027 C
Solar/Wind Harmer
0.446
957871AF2-081 GEN
Solar/Wind Harmer
7.242
316258AE1-075 C
Solar/Wind Harmer
0.343
970673AG2-436 GEN
Solar/Wind Harmer
30.638
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.005
316210AC1-098 GEN
Solar/Wind Harmer
2.048
316322AB2-045
Solar/Wind Harmer
0.439
970831AG2-522 GEN
Solar/Wind Harmer
6.516
970683AG2-441 GEN
Solar/Wind Harmer
9.15
970681AG2-440 GEN
Solar/Wind Harmer
6.073
3145746EVERETS
Solar/Wind Harmer
-0.051
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
233940AF2-379 C
Solar/Wind Helper
0.06
972223AH1-696 GEN
50/50
15.393
3141346CRANES
50/50
0.214
972219AH1-694 GEN
50/50
2.49
3150351NORNECKC2
Adder
1.418
964211AG1-282 GEN
Solar/Wind Harmer
0.478
316314AB2-024 C
Solar/Wind Harmer
1.316
944631AF1-128 GEN
Adder
64.269
3143526WINTERP
Solar/Wind Harmer
-0.078
971317AH1-138 GEN
Solar/Wind Harmer
1.876
315671AE2-027_GEN
Solar/Wind Harmer
2.688
944591AF1-124 GEN
Solar/Wind Harmer
66.465
316072AD1-144
Solar/Wind Harmer
0.293
939411AE1-173 GEN
Solar/Wind Harmer
72.085
940641AE2-051 GEN
Solar/Wind Harmer
13.479
3143336POWHATN
Solar/Wind Harmer
1.681
941031AE2-094 GEN
Solar/Wind Harmer
26.395
971685AH1-345 GEN
Solar/Wind Harmer
1.224
971547AH1-271 GEN
Solar/Wind Harmer
3.413
960081AF2-299 GEN
Solar/Wind Harmer
1.515
3145823KELFORD
Solar/Wind Harmer
-0.013
3145783HORNRTN
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.013
972277AH1-723 GEN
Adder
69.157
316129AC1-054 GEN
Solar/Wind Harmer
1.136
3144293JTRSVLE
Adder
0.276
3144293JTRSVLE
Adder
0.218
971065AG2-659 GEN
Solar/Wind Harmer
6.485
316034AC1-036 C
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.013
233944AB2-135 GEN
Solar/Wind Helper
0.579
232408W1-005 C
Solar/Wind Helper
0.494
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.864
CPLELTFEXP_CPLE->PJM
CLTF
8.311
SIGELTFEXP_SIGE->PJM
CLTF
0.248
CBM West 2LTFEXP_CBM-W2->PJM
CBM
68.184
LGEELTFEXP_LGEE->PJM
CLTF
3.215
MECLTFEXP_MEC->PJM
CLTF
7.907
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.085
NYPJM->LTFIMP_NY
CLTF
3.83
TVALTFEXP_TVA->PJM
CLTF
5.501
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.104
WECLTFEXP_WEC->PJM
CLTF
1.726
LAGNLTFEXP_LAGN->PJM
CLTF
10.93
CONTINGENCY 'DVP_P4-2: H2T560_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313908 TO BUS 314922 CKT 1   /*6POS PT TAP2 230.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: H1T560_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313058 TO BUS 314922 CKT 1   /*6POSS PT TAP 230.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 560T571_SRT-S'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1                /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313383 TO BUS 314922 CKT 1                /*8OCCOQUN     500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019F_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1          /*BRIGHTON     500.0 - 01DOUBS      500.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 2          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 4          /*01DOUBS      500.0 - 01DOUBS      230.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 1                  /*01DOUBS      500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
END
CONTINGENCY 'PEPCO_P1_5070_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
314290 to 223938 ckt 1
313911 to 314290 ckt 1
314922 to 200019 ckt 1

Winter Peak Analysis

The New Service Request AH1-684 was evaluated as a 0.0 MW (23.0 MW Capacity) injection in the Dominion area.

AH1-684 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 190.0 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-684 was evaluated as a 0.0 MW injection

AH1-684 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 190.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Stability Analysis

PJM has reviewed this project submission and determined that a stability study is not required as this is a CIR only increase with no changes to equipment/electrical parameters (no change to MFO).

 

Reactive Power Analysis

Not Required

Reactive Power Analysis was not performed. This project is responsible for meeting all applicable power factor requirements based on the project Agreements per PJM’s Tariff, Part IX, Subpart B, App. 2, section 4.6.1.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-132Thelma 230kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVPartially in Service - Under Construction
AB2-040Brink 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVIn Service
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVPartially in Service - Under Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-036Twittys Creek 34.5kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVUnder Construction
AC1-098Dawson-South Justice 115kVIn Service
AC1-099Dawson-South Justice 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-191Elmont 115kVEngineering & Procurement
AC2-009Pennington 13 kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVSuspended
AC2-079Ivor-Oak Ridge 115kVUnder Construction
AC2-120Ripley 69kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVIn Service
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVWithdrawn
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVUnder Construction
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-041Edison 4kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-103Holland-Union Camp 115 kVSuspended
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVUnder Construction
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVIn Service
AE1-191Harmony Village-Shackleford 115 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE2-005Harmony Village-Shackleford 115 kVSuspended
AE2-027Harrowgate-Locks 115kVSuspended
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-042Milton 69 kVIn Service
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVWithdrawn
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-346Ahoskie 34.5 kVIn Service
AF1-014Harmony Village-Shackleford 115 kVSuspended
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVUnder Construction
AF1-124Harper 230 kVPartially in Service - Under Construction
AF1-125Harper 230 kVUnder Construction
AF1-128Chesterfield 230 kVUnder Construction
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVUnder Construction
AF1-294Jetersville-Ponton 115 kVEngineering & Procurement
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVEngineering & Procurement
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-081Moyock 230 kVEngineering & Procurement
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-110Suffolk 115 kVWithdrawn
AF2-115Jetersville-Ponton 115 kVEngineering & Procurement
AF2-120Garner-Northern Neck 115 kVPartially in Service - Under Construction
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-299Fields 34.5 kVEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIPartially in Service - Under Construction
AF2-361Mifflintown Tap 69 kVUnder Construction
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVUnder Construction
AF2-425Reed-Reed Tap#1 69 kVUnder Construction
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AG1-021Jetersville-Ponton 115 kVEngineering & Procurement
AG1-037Ahoskie 34.5 kVWithdrawn
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-106Thelma 230 kVWithdrawn
AG1-135Garner-Lancaster 115 kVUnder Construction
AG1-145Lightfoot 34.5 kVIn Service
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVIn Service
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVWithdrawn
AG1-285Chase City-Central 115 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-469Gordonsville 34.5 kVWithdrawn
AG1-499Lambs 12.47 kVUnder Construction
AG1-532Fields 34.5 kVUnder Construction
AG1-558Buckner 34.5 kVWithdrawn
AG1-559Caroline Pines 22 kVWithdrawn
AG2-049Van Dorn 34.5 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-171Lunenburg - Nutbush 115 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-522Five Forks DP - Littleton DP 115 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings - Unity 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-345Remington 324 34.5 kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesfords 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-685Remington CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-693Remington CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-696Possum Point 230kVActive
AH1-712Cunningham 500 kVActive
AH1-723Cunningham 500 kVActive
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-068Murphy's 34.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W3-106Sussex-Wykertown 34.5kVIn Service
X3-008Todd 69kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
No overload on Dominion equipment for 8POSSUM - BURCHES (TC2)
Description
Dominion End Ratings Winter: 5414/5581/6107 Light Load: 5227/5388/5941 Summer: 4257/4388/5046
Total Cost ($USD)
$0
Discounted Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
LLA5227.0 MVA
LLB5388.0 MVA
LLC5941.0 MVA
SUMA4257.0 MVA
SUMB4388.0 MVA
SUMC5046.0 MVA
WINA5414.0 MVA
WINB5581.0 MVA
WINC6107.0 MVA

System Reinforcement: b4053.29
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4053.29
Title
Uprate 500 kV line No. 560 terminal equipment at Burches Hill substation in PEPCO so as not to limit the conductor rating.
Description
Uprate 500 kV line No. 560 terminal equipment at Burches Hill substation in PEPCO so as not to limit the conductor rating. The scope includes upgrading/replacing two circuit breakers, four switches and two different portions of stranded bus.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4087.0 MVA
(All)B4357.0 MVA
(All)C5011.0 MVA
WINA4673.0 MVA
WINB5155.0 MVA
WINC5928.0 MVA

System Reinforcement: b4052.11
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.11
Title
Replace Bells Mill T3 XF with new PEPCO standard 260 MVA 230/138 kV transformer.
Description
Replace Bells Mill T3 XF with new PEPCO standard 260 MVA 230/138 kV transformer. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.10
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.10
Title
Replace one stranded bus conductor, three thermal relays, two disconnect switches at Quince Orchard 230 kV substation.
Description
Replace one stranded bus conductor, three thermal relays, two disconnect switches at Quince Orchard 230 kV substation. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.9
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.9
Title
Replace two breakers, one bushing CT, one stranded bus conductor, four disconnect switches at Brighton 500 kV substation.
Description
Replace two breakers, one bushing CT, one stranded bus conductor, four disconnect switches at Brighton 500 kV substation.
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.8
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.8
Title
Relocate Dickerson "D"-Quince Orchard 23035 to terminate at Dickerson "H" at Dickerson No. 2 tie location.
Description
Relocate Dickerson "D"-Quince Orchard 23035 to terminate at Dickerson "H" at Dickerson No. 2 tie location. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.7
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.7
Title
Install 3.2% 230 kV series reactor at Dickerson "H" terminal side of the Edwards Ferry-Dickerson circuit.
Description
Install 3.2% 230 kV series reactor at Dickerson "H" terminal side of the Edwards Ferry-Dickerson circuit. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.6
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4052.6
Title
Aspen 500 kV remote work for Dickerson (new 500 kV) - Aspen line
Description
Aspen 500 kV remote work for Dickerson (new 500 kV) - Aspen line (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4052.5
Title
Rocky Point 500 kV remote work for Dickerson (new 500 kV)-Rocky Point line
Description
Rocky Point 500 kV remote work for Dickerson (new 500 kV)-Rocky Point line. (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.1
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.1
Title
New 500/230 kV substation (Dickerson) by cutting into the Aspen-Rocky Point 500 kV line
Description
New 500/230 kV substation (Dickerson) by cutting into the Aspen-Rocky Point 500 kV line. (2025-W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.4
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.4
Title
Aspen-Dickerson (new 500 kV) termination work at Dickerson 500 kV
Description
Aspen-Dickerson (new 500 kV) termination work at Dickerson 500 kV (2025 W1 919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.3
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.3
Title
Rocky Point-Dickerson (new 500 kV) termination work at Dickerson 500 kV
Description
Rocky Point-Dickerson (new 500 kV) termination work at Dickerson 500 kV (2025 W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4052.2
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b4052.2
Title
Install two 500/230 kV transformers connecting a new 500 kV Dickerson station and DIckeson "H" 230 kV station including 230 kV substation work.
Description
Install two 500/230 kV transformers connecting a new 500 kV Dickerson station and DIckeson "H" 230 kV station including 230 kV substation work. (2025 W1-919)
Cost Information
Time Estimate
Jun 01 2032

Not Contingent

Note: AH1-684 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-684 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-684


AH1-684 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-684 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-684 One Line Diagram

AH1-684 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.