AH1-703 Phase II System Impact Study Report

v1.00 released 2026-06-03 17:50

Bergen 230kV

51.254 MW Capacity / 35.61 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Parkway Generation Operating LLC; Parkway Generation Operating, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Public Service Electric and Gas Company.

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $0 $0 = ∞ AND ( $0 - $0 ) 51.3 = $0 per MW

General

The Project Developer has proposed an uprate to a planned/existing Natural Gas facility located in the Public Service Electric and Gas Company zone — Bergen County, New Jersey. This project is an increase to the developer’s AB2-092 project(s), which will share the same Point of Interconnection. The AH1-703 project is a 35.61 MW uprate (51.254 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 670.61 MW with 102.35 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-703
Project Name:
Bergen 230kV
Project Developer Name:
Parkway Generation Operating LLC; Parkway Generation Operating, LLC
State:
New Jersey
County:
Bergen
Transmission Owner:
Public Service Electric and Gas Company
MFO:
670.61
MWE:
35.61
MWC:
51.254
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-703 will interconnect on the Public Service Electric and Gas Company  transmission system at Bergen 230kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-703 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-703Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$0$0$0
Other Scope$0$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$0$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$0$0$0

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-703

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-703
Project ID: AH1-703
20% of cost allocation for Phase II Network Upgrades:(A) $0
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $208,000
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

Transmission Owner Analysis

No impacts identified by Transmission Owner.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. PSEG interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-703 was evaluated as a 35.61 MW (51.254 MW Capacity) injection in the PSEG area.

AH1-703 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 670.61 MW (35.61 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC105.04 %4150.0B4359.2
11.1
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC105.01 %4150.0B4357.8
11.1
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC104.99 %4150.0B4357.18
11.1
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC104.65 %4150.0B4342.89
11.15
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-SL
BreakerAC127.16 %3098.0B3939.34
8.45
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC116.99 %3098.0B3624.44
8.42
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC111.62 %3098.0B3458.01
6.86
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
BreakerAC103.85 %3098.0B3217.41
6.7
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
BG_P7_CNSTN_NWEST2_SRT-A
TowerAC102.61 %3098.0B3178.71
6.25
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
BreakerAC101.69 %3098.0B3150.34
6.65
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_C_SRT-A
BreakerAC133.22 %3486.0B4644.1
10.01
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
BGE_P4_GRACETON_51_SRT-A
BreakerAC133.22 %3486.0B4644.06
10.01
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
BreakerAC133.16 %3486.0B4641.99
10.01
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_B_SRT-A
BreakerAC133.05 %3486.0B4638.14
10.04
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC120.33 %3486.0B4194.82
10.01
GD2PJM
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
BreakerAC111.17 %3486.0B3875.5
10.22
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019E_SRT-SL
BreakerAC150.91 %3620.0B5462.93
13.33
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC145.49 %3620.0B5266.8
12.47
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
BreakerAC140.01 %3620.0B5068.35
11.48
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC136.68 %3620.0B4947.73
13.33
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
BreakerAC134.7 %3620.0B4876.15
11.26
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
SingleAC126.49 %3620.0B4579.06
11.48
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PJM_500_BG_P4_5_CNSTN_M_SRT-A
BreakerAC116.54 %3620.0B4218.81
8.04
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Base Case
SingleAC113.37 %2920.0A3310.31
9.19
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B
BusAC107.12 %3620.0B3877.79
9.91
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_04_P71_001014_SRT-A
TowerAC105.23 %3620.0B3809.42
9.59
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_05_P71_000906_SRT-A
TowerAC104.19 %3620.0B3771.64
9.57
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PL_04_P22_102290_SRT-A
BusAC103.6 %3620.0B3750.31
9.34
GD2PJM
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line
PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK
BreakerAC117.7 %2860.0B3366.11
7.43

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.04 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4359.2
MW Contribution:
11.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232912OH NUG1
Adder
11.528
971195AH1-057 GEN
Solar/Wind Harmer
1.272
233955AB2-172 GEN
Solar/Wind Harmer
6.513
232813VAUGHN
Adder
0.766
231902DC CT7
Adder
14.461
233915AB1-141 GEN
Solar/Wind Harmer
1.275
970453AG2-297 GEN
Solar/Wind Harmer
3.177
964001AG1-254 GEN
Solar/Wind Harmer
8.341
228728W1-130C
Solar/Wind Harmer
0.759
227927V4-067C
Solar/Wind Harmer
0.226
219137THOSOLAR C
Solar/Wind Harmer
1.369
219615MILLCREEK C
Solar/Wind Harmer
0.267
219224BRL12CT4
Adder
9.97
207487AE2-000G4
Solar/Wind Harmer
34.936
207497AE2-000G2
Solar/Wind Harmer
34.936
219620RIDERU C
Solar/Wind Harmer
0.062
20635928PARLN3&4
Adder
8.151
218526CNTRALGAS2 C
Solar/Wind Harmer
0.407
217167KRNY_14
Adder
10.196
971009AG2-626 GEN
Solar/Wind Harmer
1.788
961261AF2-417 GEN
Solar/Wind Harmer
1.055
212266LOR1
Solar/Wind Harmer
1.239
959431AF2-234 GEN
Solar/Wind Harmer
1.982
20334726NME_Y1-047
Adder
2.453
3138133OCRAN
Solar/Wind Helper
0.084
3143873LANEXA
Solar/Wind Helper
0.167
3141873WAN 176
Solar/Wind Helper
0.056
316382AG1-145 C
Solar/Wind Helper
0.373
316159AE1-175 C
Solar/Wind Helper
0.421
316236AE1-162_GEN
Solar/Wind Helper
0.369
3143316POE
Solar/Wind Helper
1.084
316405AF2-144 C
Solar/Wind Helper
0.314
3146486SUNBURY
Solar/Wind Helper
0.271
3146486SUNBURY
Solar/Wind Helper
0.271
3145176PASQUOTANK
Solar/Wind Helper
0.168
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
3130546PLYMOUTH
Solar/Wind Helper
0.264
315733AD1-074 GEN2
Solar/Wind Helper
3.025
946281AF1-292 GEN
Solar/Wind Helper
0.263
3148013FISHERV
Solar/Wind Helper
0.149
3146033SCOT NK
Solar/Wind Helper
1.035
315616AA1-038_C
Solar/Wind Helper
1.138
232904IR4
Adder
105.562
232432Z2-076 GEN
Solar/Wind Harmer
0.172
233968AD2-076_GEN
Solar/Wind Harmer
8.571
231919CHRIST1
Adder
5.581
231920CHRIST2
Adder
5.457
230422AE1-104_GEN1
Solar/Wind Harmer
38.61
230425AE1-104_GEN2
Solar/Wind Harmer
38.61
230430AE1-229_GEN
Solar/Wind Harmer
32.785
230407AD2-065 C
Solar/Wind Harmer
0.15
20720728JCB_W1-129
Solar/Wind Harmer
0.331
207500AE2-000G1
Solar/Wind Harmer
34.936
970025AG2-016 GEN
Solar/Wind Harmer
3.141
20714428HOW_X1-037
Solar/Wind Harmer
1.363
218449LINSOLAR C
Solar/Wind Harmer
1.105
217147KRNY_1212
Adder
9.698
217147KRNY_1212
Adder
9.525
217146KRNY_1234
Adder
9.503
217146KRNY_1234
Adder
9.438
964851AG1-348 GEN
Solar/Wind Harmer
1.491
207408W3-077 C
Solar/Wind Harmer
0.552
20462827N BANGR8
Adder
0.781
209026WIENIPP4
Adder
5.604
209054AE2-059 GEN
Solar/Wind Harmer
1.689
20486527WR_V4-052
Adder
1.063
209067AE2-060 GEN
Solar/Wind Harmer
1.327
200917MEHOOPANY_G
Solar/Wind Harmer
3.649
315651AD1-115 GEN
Solar/Wind Helper
1.009
238169AE2-226 GEN1
Solar/Wind Helper
0.722
238170AE2-226 GEN2
Solar/Wind Helper
0.722
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
316059AD1-063 C
Solar/Wind Helper
0.282
313526AB2-022
Solar/Wind Helper
0.414
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
3146206CASHIE
Solar/Wind Helper
0.263
961941AG1-037 GEN
Solar/Wind Helper
0.088
3146043SEABORD
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.523
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
316486AD2-202 GEN
Solar/Wind Helper
0.373
316274AC1-208 GEN
Solar/Wind Helper
1.57
3148463FAIRFLD
Solar/Wind Helper
0.251
3147173SINAI
Solar/Wind Helper
0.25
3147243WELCO
Solar/Wind Helper
0.156
270455AD2-022 GEN
Solar/Wind Helper
1.372
270197AD1-017 GEN1
Solar/Wind Helper
1.224
200195DELTA ST
50/50
3.37
232920IR10
Adder
4.126
233901CHERRYDALE C
Solar/Wind Harmer
1.468
232913OH NUG2
Adder
11.375
231906DC3 NUG
Adder
18.089
200204Y1-065-CTG1
50/50
4.516
233918AB1-142 GEN
Solar/Wind Harmer
1.275
228206SHRMN CT
Adder
19.057
228260V4-054C
Solar/Wind Harmer
1.177
228729W2-030 C
Solar/Wind Harmer
0.659
219686LUMSOLAR_N C
Solar/Wind Harmer
0.228
219348LDSOLAR C
Solar/Wind Harmer
0.668
213611FALLS1-3
Adder
3.931
214194N WALES4
Adder
0.948
20720428HOL_W1-112
Solar/Wind Harmer
0.381
20635828PARLN1&2
Adder
8.151
20635028RRCT1&2
Adder
12.975
218524CNTRALGAS1 C
Solar/Wind Harmer
0.406
217209CENTRL HS C
Solar/Wind Harmer
0.049
20671828STAW2-080
Solar/Wind Harmer
0.115
207439AE1-081 C O1
Solar/Wind Harmer
0.065
207530AG1-191 GEN
Solar/Wind Harmer
1.503
211065PSPA IPP
Solar/Wind Harmer
0.487
961301AF2-421 GEN
Solar/Wind Harmer
1.052
963151AG1-164 GEN
Solar/Wind Harmer
1.052
961341AF2-425 GEN
Solar/Wind Harmer
1.016
212507AE2-042_GEN
Solar/Wind Harmer
2.994
20328326MANOR_T86
Adder
0.126
316337AD2-073 GEN
Solar/Wind Helper
0.431
3141726DUNNSVL
Solar/Wind Helper
1.127
316132AB2-190 GEN1
Solar/Wind Helper
1.581
315773AC2-141 GEN
Solar/Wind Helper
5.904
316036AC1-147 C
Solar/Wind Helper
0.417
3146516WINFALL
Solar/Wind Helper
0.874
3146516WINFALL
Solar/Wind Helper
0.27
3146776BUCKING
Solar/Wind Helper
0.106
3145893MURPHYS
Solar/Wind Helper
1.053
315607AA1-063A GEN
Solar/Wind Helper
1.497
3146263WOODLND
Solar/Wind Helper
0.261
3145963POPLR C
Solar/Wind Helper
0.26
316494AC1-189 GEN
Solar/Wind Helper
1.554
961671AG1-007 GEN
Solar/Wind Helper
0.182
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.202
238108AE1-109 GEN1
Solar/Wind Helper
0.094
200035PCHBTM 3
50/50
22.888
233971AC1-093 C
Solar/Wind Harmer
3.328
232918OH NUG7
Adder
11.452
232905CHERITON_25
Adder
3.202
233994AC2-023 GEN
Solar/Wind Harmer
3.502
234036AF2-325 C
Solar/Wind Harmer
1.194
232910NRG_G1
Adder
11.218
234014AF1-036_GEN
Solar/Wind Harmer
3.498
232436AB1-176 C
Solar/Wind Harmer
0.296
972233AH1-701 GEN
Adder
4.777
219912AD2-042 GEN
Solar/Wind Harmer
0.895
219607WPEMNERT C
Solar/Wind Harmer
0.468
219304NAMERICA C
Solar/Wind Harmer
0.346
20635028RRCT1&2
Adder
12.775
218418LINDEN_G5
Adder
18.878
219036LINDEN_G7
Adder
18.371
233973AC2-185 C
Solar/Wind Harmer
7.08
970695AG2-447 GEN
Solar/Wind Harmer
4.684
233987AB2-037 GEN
Solar/Wind Harmer
14.844
233923SMA
Solar/Wind Harmer
4.769
233997TMININ_4.2
Solar/Wind Harmer
1.301
232907VN8
Adder
39.184
232417X3-008 C
Solar/Wind Harmer
1.466
233935AB2-179 C
Solar/Wind Harmer
3.169
219221BRL12CT1
Adder
9.97
219223BRL12CT3
Adder
9.97
959561AF2-247 GEN
Solar/Wind Harmer
0.539
20715728PEM_W1-119
Solar/Wind Harmer
0.592
20636028O CRK C1
Adder
7.839
971667AH1-334 GEN
Solar/Wind Harmer
3.043
219727YARDVSOLFA C
Solar/Wind Harmer
1.007
20635828PARLN1&2
Adder
3.692
219249CENTRALDIV C
Solar/Wind Harmer
0.044
207442AE1-156 GEN
Solar/Wind Harmer
0.816
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217194REDH C
Solar/Wind Harmer
0.54
207511W3-106 GEN
Solar/Wind Harmer
0.361
971007AG2-625 GEN
Solar/Wind Harmer
2.804
20466127PORT 5CT
Adder
28.881
20674128FR_U2-059
Solar/Wind Harmer
0.201
211065PSPA IPP
Solar/Wind Harmer
0.487
957921AF2-086 GEN
Solar/Wind Harmer
0.986
3132273ORANGE
Solar/Wind Helper
0.058
316223AC1-118
Solar/Wind Helper
0.435
23546401DTGZ2-030
Solar/Wind Helper
0.089
3144536CHRHLND
Solar/Wind Helper
0.041
3142956BIRDNECK
Solar/Wind Helper
0.184
316305AF2-043 C
Solar/Wind Helper
0.366
316320Y1-086
Solar/Wind Helper
0.122
3146516WINFALL
Solar/Wind Helper
0.27
3146776BUCKING
Solar/Wind Helper
0.095
315735AD1-075 GEN1
Solar/Wind Helper
1.513
3145893MURPHYS
Solar/Wind Helper
0.094
3145893MURPHYS
Solar/Wind Helper
0.263
3146263WOODLND
Solar/Wind Helper
0.261
3145963POPLR C
Solar/Wind Helper
0.26
316011AB1-132 GEN
Solar/Wind Helper
2.806
270494AE1-108_GEN
Solar/Wind Helper
3.414
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
237038AE2-054 C
Solar/Wind Helper
0.23
270173AC1-122 GEN
Solar/Wind Helper
1.533
231907DC10
Adder
4.516
970597AG2-380 GEN
Solar/Wind Harmer
5.382
972141AH1-641 GEN
Solar/Wind Harmer
3.295
213611FALLS1-3
Adder
3.931
213611FALLS1-3
Adder
3.931
20715028HAN_X4-015
Solar/Wind Harmer
0.331
207507AE2-000G3
Solar/Wind Harmer
34.936
207445AB1-138_GEN
Solar/Wind Harmer
0.641
20720628TIN_W1-124
Solar/Wind Harmer
1.098
971521AH1-258 GEN
Solar/Wind Harmer
2.985
20675528CPH_W2-050
Solar/Wind Harmer
0.631
20676428JCR_X2-075
Solar/Wind Harmer
0.375
217086KRNY_131
Adder
10.109
20675128HRM_W1-127
Solar/Wind Harmer
0.185
209029WAYMART-WD
Solar/Wind Harmer
2.676
959421AF2-233 GEN
Solar/Wind Harmer
0.991
203926AA2-133 GEN
Adder
2.266
205951AE1-129_GEN
Solar/Wind Harmer
7.69
3138216PACIFIC
Solar/Wind Helper
0.054
316164AC1-076 GEN
Solar/Wind Helper
1.421
3141813NORNECK
Solar/Wind Helper
0.282
957601AF2-054 GEN
Solar/Wind Helper
0.374
316233AE1-074 FULL
Solar/Wind Helper
0.426
316018AA1-139 ULT2
Solar/Wind Helper
1.173
315800Z1-036_GEN1
Solar/Wind Helper
1.475
315732AD1-074 GEN1
Solar/Wind Helper
3.025
3145893MURPHYS
Solar/Wind Helper
0.711
3145893MURPHYS
Solar/Wind Helper
0.263
316463AE2-346 GEN
Solar/Wind Helper
0.24
3145513AHOSKIE
Solar/Wind Helper
0.118
3145513AHOSKIE
Solar/Wind Helper
0.262
3137643SOCKMAN
Solar/Wind Helper
1.041
316426AA2-053 GEN
Solar/Wind Helper
1.489
316174AB2-169 GEN
Solar/Wind Helper
0.665
3144303KENBRDG
Solar/Wind Helper
0.207
316327AA2-057 GEN
Solar/Wind Helper
1.457
226929AD2-058 GEN
Solar/Wind Helper
0.099
270457AD2-023 GEN
Solar/Wind Helper
0.904
232901NORTHST
Adder
10.881
234033AF1-007_GEN
Solar/Wind Harmer
48.561
233996TM1833_GEN
Solar/Wind Harmer
1.301
232426Y1-080 FULL
Solar/Wind Harmer
0.249
232902EASTMUNI
Adder
16.941
234012AE2-112_GEN
Solar/Wind Harmer
2.974
972251AH1-710 GEN
Adder
57.798
231918WEST 1
Adder
4.242
228732V1-021 C
Adder
0.217
228400MICK 1CT
Adder
13.439
219766PARADISE C
Solar/Wind Harmer
0.355
20714528FRN_Y2-051
Solar/Wind Harmer
0.326
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
217208PARK ELE C
Solar/Wind Harmer
0.028
966261AG1-495 GEN
Solar/Wind Harmer
3.838
20674628WNG_W3-110
Solar/Wind Harmer
0.441
209023WIENIPP1
Adder
11.341
209025WIENIPP3
Adder
5.661
963071AG1-156 GEN
Solar/Wind Harmer
10.329
205967AE2-211_GEN
Solar/Wind Harmer
5.78
316447AC1-158 HLD
Solar/Wind Helper
3.662
316192AB2-158 GEN
Solar/Wind Helper
1.953
3142416OLDCHRC
Solar/Wind Helper
0.728
3142416OLDCHRC
Solar/Wind Helper
0.279
3141766HARMONY
Solar/Wind Helper
0.056
315975AC1-164 GENB
Solar/Wind Helper
0.106
3142433PROV 92
Solar/Wind Helper
1.115
3145336SMITFLD
Solar/Wind Helper
1.096
316375AC2-012 GEN
Solar/Wind Helper
0.719
3146456SLIGO L269
Solar/Wind Helper
0.272
3145663CRESWEL
Solar/Wind Helper
0.744
316023GEN1_S
Solar/Wind Helper
1.006
3146206CASHIE
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
3156021HOLLOMANSOL
Solar/Wind Helper
2.001
3145683EARLEYS
Solar/Wind Helper
0.262
316131AB2-060 GEN
Solar/Wind Helper
1.571
3146083TARBORO
Solar/Wind Helper
0.253
316359AB2-059 GEN
Solar/Wind Helper
1.926
238110AE1-109 GEN3
Solar/Wind Helper
0.094
964991AG1-363 GEN
Solar/Wind Helper
3.5
3147123OTTER R
Solar/Wind Helper
0.138
217086KRNY_131
Adder
10.217
20674328GAR_V4-001
Solar/Wind Harmer
0.12
946751AF1-339 GEN
Solar/Wind Harmer
0.993
316006AB2-029 C
Solar/Wind Helper
0.146
316045AC1-158 PL2
Solar/Wind Helper
5.325
238149AF1-291A_GEN
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.379
315666AE1-190 GEN
Solar/Wind Helper
0.376
316156AD2-030 GEN
Solar/Wind Helper
0.422
316240AF1-291 C
Solar/Wind Helper
0.372
316313AB2-026
Solar/Wind Helper
0.418
316435W1029_GEN3
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
315614AA2-178 GEN
Solar/Wind Helper
1.624
3146776BUCKING
Solar/Wind Helper
1.059
3146776BUCKING
Solar/Wind Helper
0.086
3145893MURPHYS
Solar/Wind Helper
0.378
3145893MURPHYS
Solar/Wind Helper
0.474
316140AB2-099
Solar/Wind Helper
0.1
316005AA1-067
Solar/Wind Helper
0.293
316118AC1-105 GEN
Solar/Wind Helper
0.979
232926CRISFLD1
Adder
2.562
231940T-011
Adder
0.973
234041AC1-190 GEN
Solar/Wind Harmer
11.671
228201CARL#2CT
Adder
7.887
228200CARL#1CT
Adder
7.501
219904AC1-010 C
Solar/Wind Harmer
0.426
219906AC1-017 C
Solar/Wind Harmer
0.249
213815MOSER1-3
Adder
3.966
213815MOSER1-3
Adder
3.966
20720828JCB_W4-025
Solar/Wind Harmer
0.503
20714828MDF_W3-079
Solar/Wind Harmer
0.338
219817TRENTONSOL C
Solar/Wind Harmer
1.217
20641628MLH_W1-032
Solar/Wind Harmer
0.324
20742028HF_AC1-207
Solar/Wind Harmer
0.864
218438BLK ROCK C
Solar/Wind Harmer
0.15
972260AH1-715 GEN1
Adder
15.117
972261AH1-715 GEN2
Adder
17.586
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.08
217206BARNGR HS C
Solar/Wind Harmer
0.034
217204WCALDSOLAR C
Solar/Wind Harmer
0.08
20674828DL_W4-046
Solar/Wind Harmer
0.705
20634528N27_Y2-018
Solar/Wind Harmer
0.294
238147AE2-230_GEN1
Solar/Wind Helper
0.493
315976AC1-164 GENA
Solar/Wind Helper
3.599
316169AC1-164_GENC
Solar/Wind Helper
3.109
3142946ENON
Solar/Wind Helper
0.028
316294AC1-161 GEN
Solar/Wind Helper
5.018
316349AD2-085 GEN
Solar/Wind Helper
1.247
3146386ELIZ CT
Solar/Wind Helper
0.271
316431W1029_GEN1
Solar/Wind Helper
1.092
316433W1029_GEN2
Solar/Wind Helper
1.092
316365GEN2_N
Solar/Wind Helper
1.006
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
316097T157 G90
Solar/Wind Helper
1.209
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3146843MT LREL
Solar/Wind Helper
0.253
3146843MT LREL
Solar/Wind Helper
0.253
237080AD1-060 GEN
Solar/Wind Helper
0.298
232434Z2-077 GEN
Solar/Wind Harmer
0.326
232406W1-004 FULL
Solar/Wind Harmer
1.305
233964AF2-378 GEN
Solar/Wind Harmer
0.166
232422X3-066 FULL
Solar/Wind Harmer
0.323
230415AB2-049 C
Solar/Wind Harmer
0.217
219291REEVESSOUT C
Solar/Wind Harmer
0.068
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213815MOSER1-3
Adder
3.966
20714928UPF_X1-085
Solar/Wind Harmer
0.451
219114HARTZY_C
Solar/Wind Harmer
0.923
219918AC2-009 C
Solar/Wind Harmer
0.028
20674528F3S_W2-016
Solar/Wind Harmer
1.541
209025WIENIPP3
Adder
5.546
209142AF1-226 GEN
Solar/Wind Harmer
5.869
205941AD2-115 GEN
Solar/Wind Harmer
0.936
966881AG1-559 GEN
Solar/Wind Helper
0.389
316473AC1-191 GEN
Solar/Wind Helper
1.72
3142946ENON
Solar/Wind Helper
0.093
3145336SMITFLD
Solar/Wind Helper
0.11
316017AA1-139 ULT1
Solar/Wind Helper
1.247
3146456SLIGO L269
Solar/Wind Helper
0.272
3145273HOLLAND
Solar/Wind Helper
0.202
3146376EDENTON
Solar/Wind Helper
0.268
3146206CASHIE
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
316095T157 G97
Solar/Wind Helper
1.209
316499AE2-029_GEN
Solar/Wind Helper
0.88
316181AB2-040 GEN
Solar/Wind Helper
1.877
3147133PAMPLIN
Solar/Wind Helper
0.818
3147043LAWRENC
Solar/Wind Helper
0.156
316478AD1-087 GEN
Solar/Wind Helper
1.273
316420AA1-050 GEN
Solar/Wind Helper
1.459
3146073TAR RVR
Solar/Wind Helper
0.253
3146083TARBORO
Solar/Wind Helper
0.253
3138543CONSLDL
Solar/Wind Helper
0.167
238109AE1-109 GEN2
Solar/Wind Helper
0.094
200202DELTA2 ST
50/50
6.611
200052ROCKSP 1
50/50
2.841
200053ROCKSP 2
50/50
2.785
233940AF2-379 C
Solar/Wind Harmer
0.243
230434AG1-499 GEN
Solar/Wind Harmer
0.661
219258KINSLEYDEP C
Solar/Wind Harmer
0.365
213942SCHUYLKILL
Adder
3.988
213942SCHUYLKILL
Adder
3.049
213957STHWK3-4
Adder
3.049
213957STHWK3-4
Adder
3.049
213561DLWR9-10
Adder
3.976
213561DLWR9-10
Adder
3.041
219610FLORENCE C
Solar/Wind Harmer
1.547
963401AG1-189 GEN
Solar/Wind Harmer
2.521
971189AH1-054 GEN
Solar/Wind Harmer
1.308
20716228APLW2-078
Solar/Wind Harmer
0.975
20673828FLE_V3-070
Solar/Wind Harmer
0.512
200192DELTA CT1
50/50
2.181
200054ROCKSP 3
50/50
2.874
972177AH1-672 GEN
Solar/Wind Harmer
17.537
232408W1-005 C
Solar/Wind Harmer
1.305
232917OH NUG6
Adder
11.477
232915OH NUG4
Adder
11.452
233944AB2-135 GEN
Solar/Wind Harmer
6.752
219907AC1-030 C
Solar/Wind Harmer
0.156
213958STHWK5-6
Adder
3.049
20716028EGP_W2-019
Solar/Wind Harmer
0.515
207522AF2-254 C
Solar/Wind Harmer
1.593
218428ETC SOLAR C
Solar/Wind Harmer
0.039
219908AB1-139 C
Solar/Wind Harmer
0.418
972275AH1-722 GEN
Adder
34.705
20673628F1S_V4-069
Solar/Wind Harmer
0.197
207528AF2-192 GEN
Solar/Wind Harmer
1.396
217186ESSEX_G9
Adder
4.33
217083KRNY_132
Adder
10.196
20676228FRD_X1-012
Solar/Wind Harmer
0.646
20675828AU_W4-064
Solar/Wind Harmer
0.189
20675728RH_W2-091
Solar/Wind Harmer
0.658
207484AF2-139 C O1
Solar/Wind Harmer
0.551
208909MACR G3
Adder
173.367
209010PEIP 1
Adder
0.666
946731AF1-337 GEN
Solar/Wind Harmer
0.993
209008PAXT IPP
Adder
1.814
316415AF1-147_GEN2
Solar/Wind Helper
1.093
238175AF1-290_GEN
Solar/Wind Helper
0.162
964211AG1-282 GEN
Solar/Wind Helper
0.38
3143526WINTERP
Solar/Wind Helper
1.45
315671AE2-027_GEN
Solar/Wind Helper
2.231
316072AD1-144
Solar/Wind Helper
0.312
3147983MERCK5
Solar/Wind Helper
0.105
3145823KELFORD
Solar/Wind Helper
0.26
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.855
3145796HORNRTN
Solar/Wind Helper
0.259
316034AC1-036 C
Solar/Wind Helper
0.272
316129AC1-054 GEN
Solar/Wind Helper
1.278
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3147312GRETNA
Solar/Wind Helper
0.183
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.847
316003AC1-222 GEN
Solar/Wind Helper
1.078
227287AC2-120 GEN
Solar/Wind Helper
0.335
316222AC1-221 GEN
Solar/Wind Helper
1.39
316283AC2-100 C
Solar/Wind Helper
1.294
200201DELTA2 CT2
50/50
3.904
232899W1-062
Adder
12.558
232410W1-006 C
Solar/Wind Harmer
1.305
233946AB2-136 GEN
Solar/Wind Harmer
5.198
233952AC2-187 GEN
Solar/Wind Harmer
1.466
233954AC2-188 GEN
Solar/Wind Harmer
1.466
233984AB2-036 GEN
Solar/Wind Harmer
16.143
233930AB2-032 GEN
Solar/Wind Harmer
1.073
233982AB2-133 GEN
Solar/Wind Harmer
6.271
230511AF1-262
Solar/Wind Harmer
0.209
228754AB1-001 C
Solar/Wind Harmer
0.159
228307PCLP GT
Adder
13.804
219272CLEANLIGHT C
Solar/Wind Harmer
0.206
213587EDDYSTN3
Adder
89.65
217081WEATEXAS C
Solar/Wind Harmer
0.094
217083KRNY_132
Adder
10.131
207471AF2-354 C
Solar/Wind Harmer
0.559
20675928HOL_W4-097
Solar/Wind Harmer
0.142
961541AF2-445A GEN
Solar/Wind Harmer
3.357
209010PEIP 1
Adder
3.664
209010PEIP 1
Adder
0.537
961431AF2-434 GEN
Solar/Wind Harmer
1.014
209130AF1-271A GEN
Solar/Wind Harmer
2.787
316411AF1-147_GEN1
Solar/Wind Helper
1.093
237061AD1-155 GEN
Solar/Wind Helper
1.762
316312AB1-027
Solar/Wind Helper
0.535
3143526WINTERP
Solar/Wind Helper
1.45
316185AD1-033 GEN
Solar/Wind Helper
1.286
235020AA1-095 C
Solar/Wind Helper
0.051
3144356SAPONY
Solar/Wind Helper
0.483
316315AB2-025 C
Solar/Wind Helper
0.411
3145796HORNRTN
Solar/Wind Helper
0.777
316237AB2-079_GEN
Solar/Wind Helper
0.346
315687AD1-152 GEN
Solar/Wind Helper
1.377
238221AF1-254 C O1
Solar/Wind Helper
0.248
316248AF1-058 C
Solar/Wind Helper
0.337
270013AE1-250 PV
Solar/Wind Helper
0.847
200200DELTA2 CT1
50/50
3.904
200193DELTA CT2
50/50
2.181
200203Y1-065-STG
50/50
7.82
200055ROCKSP 4
50/50
2.824
233939AC1-091 C
Solar/Wind Harmer
3.505
232914OH NUG3
Adder
11.528
232916OH NUG5
Adder
11.528
233933AB2-153 GEN
Solar/Wind Harmer
1.449
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
213958STHWK5-6
Adder
3.049
20716428NHV_W2-082
Solar/Wind Harmer
1.973
963391AG1-188 GEN
Solar/Wind Harmer
4.155
219612MATRIX C
Solar/Wind Harmer
0.203
20716928W4-060COL
Solar/Wind Harmer
0.783
217213AMBOY SO C
Solar/Wind Harmer
0.139
20673728F2S_V4-070
Solar/Wind Harmer
0.197
207510AF2-138 C
Solar/Wind Harmer
1.944
207437AD2-070 GEN
Solar/Wind Harmer
0.328
20671928W4-073
Solar/Wind Harmer
0.471
20633028GILCT9
Adder
30.817
20465427SHAW CT
Adder
4.196
209116AE2-175 GEN
Solar/Wind Harmer
4.448
970095AG2-074 GEN
Solar/Wind Harmer
6.541
961421AF2-433 GEN
Solar/Wind Harmer
1.014
209093AE2-110 GEN
Solar/Wind Harmer
2.535
209120AE2-241 GEN
Solar/Wind Harmer
3.354
946691AF1-333 GEN
Solar/Wind Harmer
0.993
946741AF1-338 GEN
Solar/Wind Harmer
0.993
972221AH1-695 GEN
Adder
123.568
3141196NOKESVL
Solar/Wind Helper
1.257
316077AC2-138 C
Solar/Wind Helper
0.266
316484AD2-074 GEN
Solar/Wind Helper
0.542
316075AC2-137 C
Solar/Wind Helper
0.426
315821AE2-092 GEN
Solar/Wind Helper
2.439
942461AE2-259 GEN
Solar/Wind Helper
1.765
966621AG1-532 GEN
Solar/Wind Helper
0.238
316317KELFORD C
Solar/Wind Helper
0.234
3145823KELFORD
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
1.036
3145796HORNRTN
Solar/Wind Helper
0.259
316212AC1-099_GEN
Solar/Wind Helper
1.157
23583801GRNGAP
Solar/Wind Helper
4.397
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
226910AB2-157 C
Solar/Wind Helper
0.014
316123AC1-075 GEN
Solar/Wind Helper
1.47
3147312GRETNA
Solar/Wind Helper
0.046
237085AD2-009_GEN
Solar/Wind Helper
1.36
20676128MHD_W3-029
Solar/Wind Harmer
0.524
209027LOR2_Q27
Solar/Wind Harmer
4.673
964051AG1-259 GEN
Solar/Wind Harmer
1.329
964061AG1-260 GEN
Solar/Wind Harmer
1.329
208862AG1-362 C
Solar/Wind Harmer
0.769
20390726Y2-042
Adder
2.772
3141426STAFORD
Solar/Wind Helper
0.066
316468AD1-105 GEN
Solar/Wind Helper
1.37
3141913WHIT STONE
Solar/Wind Helper
0.279
957831AF2-077 GEN
Solar/Wind Helper
0.374
315697AD1-025 GEN
Solar/Wind Helper
3.155
315839AE2-212 C
Solar/Wind Helper
0.371
316258AE1-075 C
Solar/Wind Helper
0.376
316316AC1-027 C
Solar/Wind Helper
0.431
316322AB2-045
Solar/Wind Helper
0.296
3148133STUARTS
Solar/Wind Helper
0.156
3145796HORNRTN
Solar/Wind Helper
0.829
3145796HORNRTN
Solar/Wind Helper
0.104
316210AC1-098 GEN
Solar/Wind Helper
2.082
316238AB2-078_GEN
Solar/Wind Helper
0.346
316239AB2-077_GEN
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
1.017
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145573BETHELC
Solar/Wind Helper
0.253
3145573BETHELC
Solar/Wind Helper
0.253
200194DELTA CT3
50/50
2.181
233970AC1-092 C
Solar/Wind Harmer
3.505
232900DEMECSMY
Adder
12.045
232404W1-003 C
Solar/Wind Harmer
1.305
233998TM1NIN_3.36
Solar/Wind Harmer
1.301
232919VN10
Adder
3.661
231917EM10
Adder
2.965
970997AG2-616 GEN
Solar/Wind Harmer
10.984
213497CHSTR7-9
Adder
3.071
213497CHSTR7-9
Adder
3.071
213560DLW11-12
Adder
3.041
219222BRL12CT2
Adder
9.97
20717128DIX_Z2-102
Solar/Wind Harmer
1.465
20715828PEM_W1-120
Solar/Wind Harmer
0.592
963711AG1-223 GEN
Solar/Wind Harmer
1.636
219276PARKLANDSO C
Solar/Wind Harmer
0.51
20715228NPK_W1-113
Solar/Wind Harmer
0.474
20720528MAN_W1-024
Solar/Wind Harmer
0.28
219919AE1-041 FULL
Solar/Wind Harmer
0.044
217121ECCF
Adder
0.476
20676728BRNX1-095
Solar/Wind Harmer
0.193
20676328BVR_Y1-020
Solar/Wind Harmer
0.361
20674928WA_W3-044
Solar/Wind Harmer
0.525
971519AH1-257 GEN
Solar/Wind Harmer
2.751
207518AF1-320_GEN
Solar/Wind Harmer
3.988
20465127PORT CT
Adder
3.272
209018SUNBIPCT
Adder
7.383
20465527S.RDG CT
Adder
2.722
209137AF2-361 C
Solar/Wind Harmer
2.564
941421AE2-139 GEN
Solar/Wind Harmer
2.746
316044AC1-158 PL1
Solar/Wind Helper
1.664
3147666LOUISA
Solar/Wind Helper
1.16
238152AF2-075_GEN
Solar/Wind Helper
0.704
316404AE1-155 C
Solar/Wind Helper
2.406
3138133OCRAN
Solar/Wind Helper
0.168
315662AE1-191 GEN
Solar/Wind Helper
1.504
316280AD1-041 GEN
Solar/Wind Helper
0.94
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316369SG1_INVT
Solar/Wind Helper
1.33
316381AD1-082 GEN
Solar/Wind Helper
1.419
319010AE1-072 C
Solar/Wind Helper
3.113
23777901MDS_W4-102
Solar/Wind Helper
0.171
315611Z1-036_GEN2
Solar/Wind Helper
1.475
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.218
315737AD1-076 GEN
Solar/Wind Helper
2.587
3146926FARMVIL
Solar/Wind Helper
0.158
316087AB2-174 GEN
Solar/Wind Helper
1.832
315785AD2-033 C
Solar/Wind Helper
3.019
3146233WITAKRS
Solar/Wind Helper
1.009
270018AE2-047 C O1
Solar/Wind Helper
0.792
200034PCHBTM 2
50/50
22.757
200205Y1-065-CTG2
50/50
4.516
234015AF2-250 C
Solar/Wind Harmer
0.157
232428Y3-058 C
Solar/Wind Harmer
1.087
232424Y1-079 C
Solar/Wind Harmer
0.728
228251CARLLS#4
Adder
0.724
230433AD2-135 GEN
Solar/Wind Harmer
0.116
228351V2-046C
Solar/Wind Harmer
2.305
219287REEVESEAST C
Solar/Wind Harmer
1.516
213589EDDYSTN4
Adder
89.656
213535CROYDN11
Adder
11.421
214067T20SOLAR
Solar/Wind Harmer
0.281
20636128O CRK C2
Adder
7.147
207459AE1-142 C O1
Solar/Wind Harmer
1.168
20628028LAKEHURS
Adder
1.053
217197RE CRAN C
Solar/Wind Harmer
0.591
924131AB2-057 GEN
Solar/Wind Harmer
1.132
20635128RRCT3&4
Adder
12.332
20635128RRCT3&4
Adder
10.757
218419LINDEN_G6
Adder
18.878
20675428EAM_W2-061
Solar/Wind Harmer
0.207
219035LINDEN_G8
Adder
18.109
972237AH1-703 GEN
Adder
11.098
20465127PORT CT
Adder
4.342
20465527S.RDG CT
Adder
2.634
316450AC1-158 RIC
Solar/Wind Helper
0.444
966001AG1-469 GEN
Solar/Wind Helper
0.309
238148AE2-230_GEN2
Solar/Wind Helper
0.493
316487AF1-042 GEN
Solar/Wind Helper
0.284
316033AB2-134 GEN
Solar/Wind Helper
0.955
3145506HICKORY
Solar/Wind Helper
1.09
3145506HICKORY
Solar/Wind Helper
0.654
3145506HICKORY
Solar/Wind Helper
0.163
316339AD2-160 GEN
Solar/Wind Helper
1.039
316388AE2-253 GEN
Solar/Wind Helper
1.039
3137176SLIGO L2192
Solar/Wind Helper
1.082
3130086AYDLETT
Solar/Wind Helper
1.087
3146626S HERTFORD
Solar/Wind Helper
0.269
3146626S HERTFORD
Solar/Wind Helper
0.269
3132123MT JACKSON
Solar/Wind Helper
0.834
313506AB2-031 GEN
Solar/Wind Helper
1.188
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.156
3145593CAROLNA
Solar/Wind Helper
0.26
3145593CAROLNA
Solar/Wind Helper
0.26
3145933PARMELE
Solar/Wind Helper
0.514
3145933PARMELE
Solar/Wind Helper
0.257
316049AB1-081 GEN
Solar/Wind Helper
1.54
233972AC1-094 C
Solar/Wind Harmer
2.814
232921TASLEY2G
Adder
6.738
233950AC2-186 GEN
Solar/Wind Harmer
0.733
228711V2-041C
Solar/Wind Harmer
0.691
219921AF1-264
Solar/Wind Harmer
0.163
218660EHAMPSOLAR C
Solar/Wind Harmer
0.197
213497CHSTR7-9
Adder
3.071
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.675
213560DLW11-12
Adder
3.041
207454AA2-184 E
Solar/Wind Harmer
1.102
20635928PARLN3&4
Adder
3.692
217169METRODIV C
Solar/Wind Harmer
0.044
963161AG1-165 GEN
Solar/Wind Harmer
1.052
208972BECR K09
Solar/Wind Harmer
1.098
961331AF2-424 GEN
Solar/Wind Harmer
1.016
209071AE2-133 GEN
Solar/Wind Harmer
1.677
3147666LOUISA
Solar/Wind Helper
0.667
3141906WESTMOR
Solar/Wind Helper
0.114
316458AB2-190 GEN2
Solar/Wind Helper
1.581
3144873MCLAUGH
Solar/Wind Helper
0.007
316246AF1-032 C
Solar/Wind Helper
0.311
316321Z2-027
Solar/Wind Helper
0.413
3146626S HERTFORD
Solar/Wind Helper
0.269
3146926FARMVIL
Solar/Wind Helper
0.158
3142666NORTHAMPTON
Solar/Wind Helper
0.26
316190AA2-174 GEN
Solar/Wind Helper
0.018
3148013FISHERV
Solar/Wind Helper
0.26
3145933PARMELE
Solar/Wind Helper
0.257
3146233WITAKRS
Solar/Wind Helper
0.273
3146233WITAKRS
Solar/Wind Helper
0.172
235067AD1-061 GEN
Solar/Wind Helper
0.375
316197AC1-042 GEN
Solar/Wind Helper
0.216
237002AB1-128_GEN
Solar/Wind Helper
0.364
G-007ALTFEXP_G-007A->PJM
CMTX
56.425
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.076
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.554
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.195
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.981
VTFLTFEXP_VFT->PJM
CMTX
148.636
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.489
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.577

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.01 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4357.8
MW Contribution:
11.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232912OH NUG1
Adder
11.528
971195AH1-057 GEN
Solar/Wind Harmer
1.272
233955AB2-172 GEN
Solar/Wind Harmer
6.513
232813VAUGHN
Adder
0.766
231902DC CT7
Adder
14.461
233915AB1-141 GEN
Solar/Wind Harmer
1.275
232904IR4
Adder
105.562
232432Z2-076 GEN
Solar/Wind Harmer
0.172
233968AD2-076_GEN
Solar/Wind Harmer
8.571
231919CHRIST1
Adder
5.581
231920CHRIST2
Adder
5.457
230422AE1-104_GEN1
Solar/Wind Harmer
38.61
230425AE1-104_GEN2
Solar/Wind Harmer
38.61
230430AE1-229_GEN
Solar/Wind Harmer
32.785
230407AD2-065 C
Solar/Wind Harmer
0.15
20720728JCB_W1-129
Solar/Wind Harmer
0.331
207500AE2-000G1
Solar/Wind Harmer
34.936
970025AG2-016 GEN
Solar/Wind Harmer
3.141
20714428HOW_X1-037
Solar/Wind Harmer
1.363
218449LINSOLAR C
Solar/Wind Harmer
1.105
217147KRNY_1212
Adder
9.698
217147KRNY_1212
Adder
9.525
217146KRNY_1234
Adder
9.503
217146KRNY_1234
Adder
9.438
964851AG1-348 GEN
Solar/Wind Harmer
1.491
207408W3-077 C
Solar/Wind Harmer
0.552
20462827N BANGR8
Adder
0.781
209026WIENIPP4
Adder
5.604
209054AE2-059 GEN
Solar/Wind Harmer
1.689
20486527WR_V4-052
Adder
1.063
209067AE2-060 GEN
Solar/Wind Harmer
1.327
200917MEHOOPANY_G
Solar/Wind Harmer
3.649
315651AD1-115 GEN
Solar/Wind Helper
1.009
238169AE2-226 GEN1
Solar/Wind Helper
0.722
238170AE2-226 GEN2
Solar/Wind Helper
0.722
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
970453AG2-297 GEN
Solar/Wind Harmer
3.177
964001AG1-254 GEN
Solar/Wind Harmer
8.341
228728W1-130C
Solar/Wind Harmer
0.759
227927V4-067C
Solar/Wind Harmer
0.226
219137THOSOLAR C
Solar/Wind Harmer
1.369
219615MILLCREEK C
Solar/Wind Harmer
0.267
219224BRL12CT4
Adder
9.97
207487AE2-000G4
Solar/Wind Harmer
34.936
207497AE2-000G2
Solar/Wind Harmer
34.936
219620RIDERU C
Solar/Wind Harmer
0.062
20635928PARLN3&4
Adder
8.151
218526CNTRALGAS2 C
Solar/Wind Harmer
0.407
217167KRNY_14
Adder
10.196
971009AG2-626 GEN
Solar/Wind Harmer
1.788
961261AF2-417 GEN
Solar/Wind Harmer
1.055
212266LOR1
Solar/Wind Harmer
1.239
959431AF2-234 GEN
Solar/Wind Harmer
1.982
20334726NME_Y1-047
Adder
2.453
3138133OCRAN
Solar/Wind Helper
0.084
3143873LANEXA
Solar/Wind Helper
0.167
3141873WAN 176
Solar/Wind Helper
0.056
316382AG1-145 C
Solar/Wind Helper
0.373
316159AE1-175 C
Solar/Wind Helper
0.421
316236AE1-162_GEN
Solar/Wind Helper
0.369
3143316POE
Solar/Wind Helper
1.084
316405AF2-144 C
Solar/Wind Helper
0.314
3146486SUNBURY
Solar/Wind Helper
0.271
3146486SUNBURY
Solar/Wind Helper
0.271
3145176PASQUOTANK
Solar/Wind Helper
0.168
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
3130546PLYMOUTH
Solar/Wind Helper
0.264
315733AD1-074 GEN2
Solar/Wind Helper
3.025
946281AF1-292 GEN
Solar/Wind Helper
0.263
3148013FISHERV
Solar/Wind Helper
0.149
3146033SCOT NK
Solar/Wind Helper
1.035
315616AA1-038_C
Solar/Wind Helper
1.138
200204Y1-065-CTG1
50/50
4.516
233918AB1-142 GEN
Solar/Wind Harmer
1.275
228206SHRMN CT
Adder
19.057
228260V4-054C
Solar/Wind Harmer
1.177
228729W2-030 C
Solar/Wind Harmer
0.659
219686LUMSOLAR_N C
Solar/Wind Harmer
0.228
219348LDSOLAR C
Solar/Wind Harmer
0.668
213611FALLS1-3
Adder
3.931
214194N WALES4
Adder
0.948
20720428HOL_W1-112
Solar/Wind Harmer
0.381
20635828PARLN1&2
Adder
8.151
20635028RRCT1&2
Adder
12.975
218524CNTRALGAS1 C
Solar/Wind Harmer
0.406
217209CENTRL HS C
Solar/Wind Harmer
0.049
233973AC2-185 C
Solar/Wind Harmer
7.08
970695AG2-447 GEN
Solar/Wind Harmer
4.684
233987AB2-037 GEN
Solar/Wind Harmer
14.844
233923SMA
Solar/Wind Harmer
4.769
233997TMININ_4.2
Solar/Wind Harmer
1.301
232907VN8
Adder
39.184
232417X3-008 C
Solar/Wind Harmer
1.466
233935AB2-179 C
Solar/Wind Harmer
3.169
219221BRL12CT1
Adder
9.97
219223BRL12CT3
Adder
9.97
959561AF2-247 GEN
Solar/Wind Harmer
0.539
20715728PEM_W1-119
Solar/Wind Harmer
0.592
20636028O CRK C1
Adder
7.839
971667AH1-334 GEN
Solar/Wind Harmer
3.043
219727YARDVSOLFA C
Solar/Wind Harmer
1.007
20635828PARLN1&2
Adder
3.692
219249CENTRALDIV C
Solar/Wind Harmer
0.044
207442AE1-156 GEN
Solar/Wind Harmer
0.816
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217194REDH C
Solar/Wind Harmer
0.54
207511W3-106 GEN
Solar/Wind Harmer
0.361
971007AG2-625 GEN
Solar/Wind Harmer
2.804
20466127PORT 5CT
Adder
28.881
20674128FR_U2-059
Solar/Wind Harmer
0.201
211065PSPA IPP
Solar/Wind Harmer
0.487
957921AF2-086 GEN
Solar/Wind Harmer
0.986
3132273ORANGE
Solar/Wind Helper
0.058
316223AC1-118
Solar/Wind Helper
0.435
23546401DTGZ2-030
Solar/Wind Helper
0.089
3144536CHRHLND
Solar/Wind Helper
0.041
3142956BIRDNECK
Solar/Wind Helper
0.184
200195DELTA ST
50/50
3.37
232920IR10
Adder
4.126
233901CHERRYDALE C
Solar/Wind Harmer
1.468
232913OH NUG2
Adder
11.375
231906DC3 NUG
Adder
18.089
231907DC10
Adder
4.516
970597AG2-380 GEN
Solar/Wind Harmer
5.382
972141AH1-641 GEN
Solar/Wind Harmer
3.295
213611FALLS1-3
Adder
3.931
213611FALLS1-3
Adder
3.931
20715028HAN_X4-015
Solar/Wind Harmer
0.331
207507AE2-000G3
Solar/Wind Harmer
34.936
207445AB1-138_GEN
Solar/Wind Harmer
0.641
20720628TIN_W1-124
Solar/Wind Harmer
1.098
971521AH1-258 GEN
Solar/Wind Harmer
2.985
20675528CPH_W2-050
Solar/Wind Harmer
0.631
20676428JCR_X2-075
Solar/Wind Harmer
0.375
217086KRNY_131
Adder
10.109
20675128HRM_W1-127
Solar/Wind Harmer
0.185
209029WAYMART-WD
Solar/Wind Harmer
2.676
959421AF2-233 GEN
Solar/Wind Harmer
0.991
203926AA2-133 GEN
Adder
2.266
205951AE1-129_GEN
Solar/Wind Harmer
7.69
3138216PACIFIC
Solar/Wind Helper
0.054
316164AC1-076 GEN
Solar/Wind Helper
1.421
3141813NORNECK
Solar/Wind Helper
0.282
957601AF2-054 GEN
Solar/Wind Helper
0.374
316233AE1-074 FULL
Solar/Wind Helper
0.426
316018AA1-139 ULT2
Solar/Wind Helper
1.173
315800Z1-036_GEN1
Solar/Wind Helper
1.475
315732AD1-074 GEN1
Solar/Wind Helper
3.025
3145893MURPHYS
Solar/Wind Helper
0.711
3145893MURPHYS
Solar/Wind Helper
0.263
316463AE2-346 GEN
Solar/Wind Helper
0.24
3145513AHOSKIE
Solar/Wind Helper
0.118
3145513AHOSKIE
Solar/Wind Helper
0.262
3137643SOCKMAN
Solar/Wind Helper
1.041
316426AA2-053 GEN
Solar/Wind Helper
1.489
316174AB2-169 GEN
Solar/Wind Helper
0.665
3144303KENBRDG
Solar/Wind Helper
0.207
316327AA2-057 GEN
Solar/Wind Helper
1.457
226929AD2-058 GEN
Solar/Wind Helper
0.099
270457AD2-023 GEN
Solar/Wind Helper
0.904
20671828STAW2-080
Solar/Wind Harmer
0.115
207439AE1-081 C O1
Solar/Wind Harmer
0.065
207530AG1-191 GEN
Solar/Wind Harmer
1.503
211065PSPA IPP
Solar/Wind Harmer
0.487
961301AF2-421 GEN
Solar/Wind Harmer
1.052
963151AG1-164 GEN
Solar/Wind Harmer
1.052
961341AF2-425 GEN
Solar/Wind Harmer
1.016
212507AE2-042_GEN
Solar/Wind Harmer
2.994
20328326MANOR_T86
Adder
0.126
316337AD2-073 GEN
Solar/Wind Helper
0.431
3141726DUNNSVL
Solar/Wind Helper
1.127
316132AB2-190 GEN1
Solar/Wind Helper
1.581
315773AC2-141 GEN
Solar/Wind Helper
5.904
316036AC1-147 C
Solar/Wind Helper
0.417
3146516WINFALL
Solar/Wind Helper
0.874
3146516WINFALL
Solar/Wind Helper
0.27
3146776BUCKING
Solar/Wind Helper
0.106
3145893MURPHYS
Solar/Wind Helper
1.053
315607AA1-063A GEN
Solar/Wind Helper
1.497
3146263WOODLND
Solar/Wind Helper
0.261
3145963POPLR C
Solar/Wind Helper
0.26
316494AC1-189 GEN
Solar/Wind Helper
1.554
961671AG1-007 GEN
Solar/Wind Helper
0.182
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.202
238108AE1-109 GEN1
Solar/Wind Helper
0.094
232901NORTHST
Adder
10.881
234033AF1-007_GEN
Solar/Wind Harmer
48.561
233996TM1833_GEN
Solar/Wind Harmer
1.301
232426Y1-080 FULL
Solar/Wind Harmer
0.249
232902EASTMUNI
Adder
16.941
234012AE2-112_GEN
Solar/Wind Harmer
2.974
972251AH1-710 GEN
Adder
57.798
231918WEST 1
Adder
4.242
228732V1-021 C
Adder
0.217
228400MICK 1CT
Adder
13.439
219766PARADISE C
Solar/Wind Harmer
0.355
20714528FRN_Y2-051
Solar/Wind Harmer
0.326
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
217208PARK ELE C
Solar/Wind Harmer
0.028
966261AG1-495 GEN
Solar/Wind Harmer
3.838
20674628WNG_W3-110
Solar/Wind Harmer
0.441
209023WIENIPP1
Adder
11.341
209025WIENIPP3
Adder
5.661
963071AG1-156 GEN
Solar/Wind Harmer
10.329
200035PCHBTM 3
50/50
22.888
233971AC1-093 C
Solar/Wind Harmer
3.328
232918OH NUG7
Adder
11.452
232905CHERITON_25
Adder
3.202
233994AC2-023 GEN
Solar/Wind Harmer
3.502
234036AF2-325 C
Solar/Wind Harmer
1.194
232910NRG_G1
Adder
11.218
234014AF1-036_GEN
Solar/Wind Harmer
3.498
232436AB1-176 C
Solar/Wind Harmer
0.296
972233AH1-701 GEN
Adder
4.777
219912AD2-042 GEN
Solar/Wind Harmer
0.895
219607WPEMNERT C
Solar/Wind Harmer
0.468
219304NAMERICA C
Solar/Wind Harmer
0.346
20635028RRCT1&2
Adder
12.775
218418LINDEN_G5
Adder
18.878
219036LINDEN_G7
Adder
18.371
217086KRNY_131
Adder
10.217
20674328GAR_V4-001
Solar/Wind Harmer
0.12
946751AF1-339 GEN
Solar/Wind Harmer
0.993
316006AB2-029 C
Solar/Wind Helper
0.146
316045AC1-158 PL2
Solar/Wind Helper
5.325
238149AF1-291A_GEN
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.379
315666AE1-190 GEN
Solar/Wind Helper
0.376
316156AD2-030 GEN
Solar/Wind Helper
0.422
316240AF1-291 C
Solar/Wind Helper
0.372
316313AB2-026
Solar/Wind Helper
0.418
316435W1029_GEN3
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
315614AA2-178 GEN
Solar/Wind Helper
1.624
3146776BUCKING
Solar/Wind Helper
1.059
3146776BUCKING
Solar/Wind Helper
0.086
3145893MURPHYS
Solar/Wind Helper
0.378
3145893MURPHYS
Solar/Wind Helper
0.474
316140AB2-099
Solar/Wind Helper
0.1
316005AA1-067
Solar/Wind Helper
0.293
316118AC1-105 GEN
Solar/Wind Helper
0.979
205967AE2-211_GEN
Solar/Wind Harmer
5.78
316447AC1-158 HLD
Solar/Wind Helper
3.662
316192AB2-158 GEN
Solar/Wind Helper
1.953
3142416OLDCHRC
Solar/Wind Helper
0.728
3142416OLDCHRC
Solar/Wind Helper
0.279
3141766HARMONY
Solar/Wind Helper
0.056
315975AC1-164 GENB
Solar/Wind Helper
0.106
3142433PROV 92
Solar/Wind Helper
1.115
3145336SMITFLD
Solar/Wind Helper
1.096
316375AC2-012 GEN
Solar/Wind Helper
0.719
3146456SLIGO L269
Solar/Wind Helper
0.272
3145663CRESWEL
Solar/Wind Helper
0.744
316023GEN1_S
Solar/Wind Helper
1.006
3146206CASHIE
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
3156021HOLLOMANSOL
Solar/Wind Helper
2.001
3145683EARLEYS
Solar/Wind Helper
0.262
316131AB2-060 GEN
Solar/Wind Helper
1.571
3146083TARBORO
Solar/Wind Helper
0.253
316359AB2-059 GEN
Solar/Wind Helper
1.926
238110AE1-109 GEN3
Solar/Wind Helper
0.094
964991AG1-363 GEN
Solar/Wind Helper
3.5
3147123OTTER R
Solar/Wind Helper
0.138
232926CRISFLD1
Adder
2.562
231940T-011
Adder
0.973
234041AC1-190 GEN
Solar/Wind Harmer
11.671
228201CARL#2CT
Adder
7.887
228200CARL#1CT
Adder
7.501
219904AC1-010 C
Solar/Wind Harmer
0.426
219906AC1-017 C
Solar/Wind Harmer
0.249
213815MOSER1-3
Adder
3.966
213815MOSER1-3
Adder
3.966
20720828JCB_W4-025
Solar/Wind Harmer
0.503
20714828MDF_W3-079
Solar/Wind Harmer
0.338
219817TRENTONSOL C
Solar/Wind Harmer
1.217
20641628MLH_W1-032
Solar/Wind Harmer
0.324
20742028HF_AC1-207
Solar/Wind Harmer
0.864
218438BLK ROCK C
Solar/Wind Harmer
0.15
972260AH1-715 GEN1
Adder
15.117
972261AH1-715 GEN2
Adder
17.586
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.08
217206BARNGR HS C
Solar/Wind Harmer
0.034
217204WCALDSOLAR C
Solar/Wind Harmer
0.08
20674828DL_W4-046
Solar/Wind Harmer
0.705
20634528N27_Y2-018
Solar/Wind Harmer
0.294
238147AE2-230_GEN1
Solar/Wind Helper
0.493
315976AC1-164 GENA
Solar/Wind Helper
3.599
316169AC1-164_GENC
Solar/Wind Helper
3.109
3142946ENON
Solar/Wind Helper
0.028
316294AC1-161 GEN
Solar/Wind Helper
5.018
316349AD2-085 GEN
Solar/Wind Helper
1.247
3146386ELIZ CT
Solar/Wind Helper
0.271
316431W1029_GEN1
Solar/Wind Helper
1.092
316433W1029_GEN2
Solar/Wind Helper
1.092
316365GEN2_N
Solar/Wind Helper
1.006
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
316097T157 G90
Solar/Wind Helper
1.209
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3146843MT LREL
Solar/Wind Helper
0.253
3146843MT LREL
Solar/Wind Helper
0.253
237080AD1-060 GEN
Solar/Wind Helper
0.298
200192DELTA CT1
50/50
2.181
200054ROCKSP 3
50/50
2.874
972177AH1-672 GEN
Solar/Wind Harmer
17.537
232408W1-005 C
Solar/Wind Harmer
1.305
232917OH NUG6
Adder
11.477
232915OH NUG4
Adder
11.452
233944AB2-135 GEN
Solar/Wind Harmer
6.752
219907AC1-030 C
Solar/Wind Harmer
0.156
213958STHWK5-6
Adder
3.049
20716028EGP_W2-019
Solar/Wind Harmer
0.515
207522AF2-254 C
Solar/Wind Harmer
1.593
218428ETC SOLAR C
Solar/Wind Harmer
0.039
219908AB1-139 C
Solar/Wind Harmer
0.418
972275AH1-722 GEN
Adder
34.705
20673628F1S_V4-069
Solar/Wind Harmer
0.197
207528AF2-192 GEN
Solar/Wind Harmer
1.396
217186ESSEX_G9
Adder
4.33
217083KRNY_132
Adder
10.196
20676228FRD_X1-012
Solar/Wind Harmer
0.646
20675828AU_W4-064
Solar/Wind Harmer
0.189
20675728RH_W2-091
Solar/Wind Harmer
0.658
207484AF2-139 C O1
Solar/Wind Harmer
0.551
208909MACR G3
Adder
173.367
209010PEIP 1
Adder
0.666
946731AF1-337 GEN
Solar/Wind Harmer
0.993
209008PAXT IPP
Adder
1.814
316415AF1-147_GEN2
Solar/Wind Helper
1.093
238175AF1-290_GEN
Solar/Wind Helper
0.162
964211AG1-282 GEN
Solar/Wind Helper
0.38
3143526WINTERP
Solar/Wind Helper
1.45
315671AE2-027_GEN
Solar/Wind Helper
2.231
316072AD1-144
Solar/Wind Helper
0.312
3147983MERCK5
Solar/Wind Helper
0.105
3145823KELFORD
Solar/Wind Helper
0.26
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.855
3145796HORNRTN
Solar/Wind Helper
0.259
316034AC1-036 C
Solar/Wind Helper
0.272
316129AC1-054 GEN
Solar/Wind Helper
1.278
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3147312GRETNA
Solar/Wind Helper
0.183
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.847
232434Z2-077 GEN
Solar/Wind Harmer
0.326
232406W1-004 FULL
Solar/Wind Harmer
1.305
233964AF2-378 GEN
Solar/Wind Harmer
0.166
232422X3-066 FULL
Solar/Wind Harmer
0.323
230415AB2-049 C
Solar/Wind Harmer
0.217
219291REEVESSOUT C
Solar/Wind Harmer
0.068
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213815MOSER1-3
Adder
3.966
20714928UPF_X1-085
Solar/Wind Harmer
0.451
219114HARTZY_C
Solar/Wind Harmer
0.923
219918AC2-009 C
Solar/Wind Harmer
0.028
20674528F3S_W2-016
Solar/Wind Harmer
1.541
209025WIENIPP3
Adder
5.546
209142AF1-226 GEN
Solar/Wind Harmer
5.869
205941AD2-115 GEN
Solar/Wind Harmer
0.936
966881AG1-559 GEN
Solar/Wind Helper
0.389
316473AC1-191 GEN
Solar/Wind Helper
1.72
3142946ENON
Solar/Wind Helper
0.093
3145336SMITFLD
Solar/Wind Helper
0.11
316017AA1-139 ULT1
Solar/Wind Helper
1.247
3146456SLIGO L269
Solar/Wind Helper
0.272
3145273HOLLAND
Solar/Wind Helper
0.202
3146376EDENTON
Solar/Wind Helper
0.268
3146206CASHIE
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
316095T157 G97
Solar/Wind Helper
1.209
316499AE2-029_GEN
Solar/Wind Helper
0.88
316181AB2-040 GEN
Solar/Wind Helper
1.877
3147133PAMPLIN
Solar/Wind Helper
0.818
3147043LAWRENC
Solar/Wind Helper
0.156
316478AD1-087 GEN
Solar/Wind Helper
1.273
316420AA1-050 GEN
Solar/Wind Helper
1.459
3146073TAR RVR
Solar/Wind Helper
0.253
316059AD1-063 C
Solar/Wind Helper
0.282
313526AB2-022
Solar/Wind Helper
0.414
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
3146206CASHIE
Solar/Wind Helper
0.263
961941AG1-037 GEN
Solar/Wind Helper
0.088
3146043SEABORD
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.523
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
316486AD2-202 GEN
Solar/Wind Helper
0.373
316274AC1-208 GEN
Solar/Wind Helper
1.57
3148463FAIRFLD
Solar/Wind Helper
0.251
3147173SINAI
Solar/Wind Helper
0.25
3147243WELCO
Solar/Wind Helper
0.156
270455AD2-022 GEN
Solar/Wind Helper
1.372
270197AD1-017 GEN1
Solar/Wind Helper
1.224
200201DELTA2 CT2
50/50
3.904
232899W1-062
Adder
12.558
200200DELTA2 CT1
50/50
3.904
200193DELTA CT2
50/50
2.181
200203Y1-065-STG
50/50
7.82
200055ROCKSP 4
50/50
2.824
233939AC1-091 C
Solar/Wind Harmer
3.505
232914OH NUG3
Adder
11.528
232916OH NUG5
Adder
11.528
233933AB2-153 GEN
Solar/Wind Harmer
1.449
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
213958STHWK5-6
Adder
3.049
20716428NHV_W2-082
Solar/Wind Harmer
1.973
963391AG1-188 GEN
Solar/Wind Harmer
4.155
219612MATRIX C
Solar/Wind Harmer
0.203
20716928W4-060COL
Solar/Wind Harmer
0.783
217213AMBOY SO C
Solar/Wind Harmer
0.139
20673728F2S_V4-070
Solar/Wind Harmer
0.197
207510AF2-138 C
Solar/Wind Harmer
1.944
207437AD2-070 GEN
Solar/Wind Harmer
0.328
20671928W4-073
Solar/Wind Harmer
0.471
20633028GILCT9
Adder
30.817
20465427SHAW CT
Adder
4.196
209116AE2-175 GEN
Solar/Wind Harmer
4.448
970095AG2-074 GEN
Solar/Wind Harmer
6.541
961421AF2-433 GEN
Solar/Wind Harmer
1.014
209093AE2-110 GEN
Solar/Wind Harmer
2.535
209120AE2-241 GEN
Solar/Wind Harmer
3.354
946691AF1-333 GEN
Solar/Wind Harmer
0.993
946741AF1-338 GEN
Solar/Wind Harmer
0.993
972221AH1-695 GEN
Adder
123.568
3141196NOKESVL
Solar/Wind Helper
1.257
316077AC2-138 C
Solar/Wind Helper
0.266
316484AD2-074 GEN
Solar/Wind Helper
0.542
316075AC2-137 C
Solar/Wind Helper
0.426
315821AE2-092 GEN
Solar/Wind Helper
2.439
942461AE2-259 GEN
Solar/Wind Helper
1.765
966621AG1-532 GEN
Solar/Wind Helper
0.238
316317KELFORD C
Solar/Wind Helper
0.234
3145823KELFORD
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
1.036
3145796HORNRTN
Solar/Wind Helper
0.259
316212AC1-099_GEN
Solar/Wind Helper
1.157
23583801GRNGAP
Solar/Wind Helper
4.397
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
226910AB2-157 C
Solar/Wind Helper
0.014
316123AC1-075 GEN
Solar/Wind Helper
1.47
3147312GRETNA
Solar/Wind Helper
0.046
237085AD2-009_GEN
Solar/Wind Helper
1.36
200202DELTA2 ST
50/50
6.611
200052ROCKSP 1
50/50
2.841
200053ROCKSP 2
50/50
2.785
233940AF2-379 C
Solar/Wind Harmer
0.243
230434AG1-499 GEN
Solar/Wind Harmer
0.661
219258KINSLEYDEP C
Solar/Wind Harmer
0.365
213942SCHUYLKILL
Adder
3.988
213942SCHUYLKILL
Adder
3.049
213957STHWK3-4
Adder
3.049
213957STHWK3-4
Adder
3.049
213561DLWR9-10
Adder
3.976
213561DLWR9-10
Adder
3.041
219610FLORENCE C
Solar/Wind Harmer
1.547
963401AG1-189 GEN
Solar/Wind Harmer
2.521
971189AH1-054 GEN
Solar/Wind Harmer
1.308
20716228APLW2-078
Solar/Wind Harmer
0.975
20673828FLE_V3-070
Solar/Wind Harmer
0.512
20676128MHD_W3-029
Solar/Wind Harmer
0.524
209027LOR2_Q27
Solar/Wind Harmer
4.673
964051AG1-259 GEN
Solar/Wind Harmer
1.329
964061AG1-260 GEN
Solar/Wind Harmer
1.329
208862AG1-362 C
Solar/Wind Harmer
0.769
20390726Y2-042
Adder
2.772
3141426STAFORD
Solar/Wind Helper
0.066
316468AD1-105 GEN
Solar/Wind Helper
1.37
3141913WHIT STONE
Solar/Wind Helper
0.279
957831AF2-077 GEN
Solar/Wind Helper
0.374
315697AD1-025 GEN
Solar/Wind Helper
3.155
315839AE2-212 C
Solar/Wind Helper
0.371
316258AE1-075 C
Solar/Wind Helper
0.376
316316AC1-027 C
Solar/Wind Helper
0.431
316322AB2-045
Solar/Wind Helper
0.296
3148133STUARTS
Solar/Wind Helper
0.156
3145796HORNRTN
Solar/Wind Helper
0.829
3145796HORNRTN
Solar/Wind Helper
0.104
316210AC1-098 GEN
Solar/Wind Helper
2.082
316238AB2-078_GEN
Solar/Wind Helper
0.346
316239AB2-077_GEN
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
1.017
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145573BETHELC
Solar/Wind Helper
0.253
3145573BETHELC
Solar/Wind Helper
0.253
200194DELTA CT3
50/50
2.181
233970AC1-092 C
Solar/Wind Harmer
3.505
232900DEMECSMY
Adder
12.045
232404W1-003 C
Solar/Wind Harmer
1.305
233998TM1NIN_3.36
Solar/Wind Harmer
1.301
232919VN10
Adder
3.661
231917EM10
Adder
2.965
970997AG2-616 GEN
Solar/Wind Harmer
10.984
213497CHSTR7-9
Adder
3.071
213497CHSTR7-9
Adder
3.071
213560DLW11-12
Adder
3.041
219222BRL12CT2
Adder
9.97
20717128DIX_Z2-102
Solar/Wind Harmer
1.465
20715828PEM_W1-120
Solar/Wind Harmer
0.592
963711AG1-223 GEN
Solar/Wind Harmer
1.636
219276PARKLANDSO C
Solar/Wind Harmer
0.51
20715228NPK_W1-113
Solar/Wind Harmer
0.474
20720528MAN_W1-024
Solar/Wind Harmer
0.28
219919AE1-041 FULL
Solar/Wind Harmer
0.044
217121ECCF
Adder
0.476
20676728BRNX1-095
Solar/Wind Harmer
0.193
20676328BVR_Y1-020
Solar/Wind Harmer
0.361
20674928WA_W3-044
Solar/Wind Harmer
0.525
971519AH1-257 GEN
Solar/Wind Harmer
2.751
207518AF1-320_GEN
Solar/Wind Harmer
3.988
20465127PORT CT
Adder
3.272
209018SUNBIPCT
Adder
7.383
20465527S.RDG CT
Adder
2.722
209137AF2-361 C
Solar/Wind Harmer
2.564
941421AE2-139 GEN
Solar/Wind Harmer
2.746
316044AC1-158 PL1
Solar/Wind Helper
1.664
3147666LOUISA
Solar/Wind Helper
1.16
238152AF2-075_GEN
Solar/Wind Helper
0.704
316404AE1-155 C
Solar/Wind Helper
2.406
3138133OCRAN
Solar/Wind Helper
0.168
315662AE1-191 GEN
Solar/Wind Helper
1.504
316280AD1-041 GEN
Solar/Wind Helper
0.94
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316369SG1_INVT
Solar/Wind Helper
1.33
316381AD1-082 GEN
Solar/Wind Helper
1.419
319010AE1-072 C
Solar/Wind Helper
3.113
23777901MDS_W4-102
Solar/Wind Helper
0.171
315611Z1-036_GEN2
Solar/Wind Helper
1.475
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.218
315737AD1-076 GEN
Solar/Wind Helper
2.587
3146926FARMVIL
Solar/Wind Helper
0.158
316087AB2-174 GEN
Solar/Wind Helper
1.832
315785AD2-033 C
Solar/Wind Helper
3.019
3146233WITAKRS
Solar/Wind Helper
1.009
270018AE2-047 C O1
Solar/Wind Helper
0.792
200034PCHBTM 2
50/50
22.757
200205Y1-065-CTG2
50/50
4.516
234015AF2-250 C
Solar/Wind Harmer
0.157
232428Y3-058 C
Solar/Wind Harmer
1.087
232424Y1-079 C
Solar/Wind Harmer
0.728
228251CARLLS#4
Adder
0.724
230433AD2-135 GEN
Solar/Wind Harmer
0.116
228351V2-046C
Solar/Wind Harmer
2.305
219287REEVESEAST C
Solar/Wind Harmer
1.516
213589EDDYSTN4
Adder
89.656
213535CROYDN11
Adder
11.421
214067T20SOLAR
Solar/Wind Harmer
0.281
20636128O CRK C2
Adder
7.147
207459AE1-142 C O1
Solar/Wind Harmer
1.168
20628028LAKEHURS
Adder
1.053
217197RE CRAN C
Solar/Wind Harmer
0.591
924131AB2-057 GEN
Solar/Wind Harmer
1.132
20635128RRCT3&4
Adder
12.332
20635128RRCT3&4
Adder
10.757
218419LINDEN_G6
Adder
18.878
20675428EAM_W2-061
Solar/Wind Harmer
0.207
219035LINDEN_G8
Adder
18.109
972237AH1-703 GEN
Adder
11.098
20465127PORT CT
Adder
4.342
20465527S.RDG CT
Adder
2.634
316450AC1-158 RIC
Solar/Wind Helper
0.444
966001AG1-469 GEN
Solar/Wind Helper
0.309
238148AE2-230_GEN2
Solar/Wind Helper
0.493
316487AF1-042 GEN
Solar/Wind Helper
0.284
316033AB2-134 GEN
Solar/Wind Helper
0.955
3145506HICKORY
Solar/Wind Helper
1.09
3145506HICKORY
Solar/Wind Helper
0.654
3145506HICKORY
Solar/Wind Helper
0.163
316339AD2-160 GEN
Solar/Wind Helper
1.039
316388AE2-253 GEN
Solar/Wind Helper
1.039
3137176SLIGO L2192
Solar/Wind Helper
1.082
3130086AYDLETT
Solar/Wind Helper
1.087
3146626S HERTFORD
Solar/Wind Helper
0.269
3146626S HERTFORD
Solar/Wind Helper
0.269
3132123MT JACKSON
Solar/Wind Helper
0.834
313506AB2-031 GEN
Solar/Wind Helper
1.188
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.156
3145593CAROLNA
Solar/Wind Helper
0.26
3145593CAROLNA
Solar/Wind Helper
0.26
3145933PARMELE
Solar/Wind Helper
0.514
3145933PARMELE
Solar/Wind Helper
0.257
316049AB1-081 GEN
Solar/Wind Helper
1.54
233972AC1-094 C
Solar/Wind Harmer
2.814
232921TASLEY2G
Adder
6.738
233950AC2-186 GEN
Solar/Wind Harmer
0.733
228711V2-041C
Solar/Wind Harmer
0.691
219921AF1-264
Solar/Wind Harmer
0.163
218660EHAMPSOLAR C
Solar/Wind Harmer
0.197
213497CHSTR7-9
Adder
3.071
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.675
213560DLW11-12
Adder
3.041
207454AA2-184 E
Solar/Wind Harmer
1.102
20635928PARLN3&4
Adder
3.692
217169METRODIV C
Solar/Wind Harmer
0.044
963161AG1-165 GEN
Solar/Wind Harmer
1.052
208972BECR K09
Solar/Wind Harmer
1.098
961331AF2-424 GEN
Solar/Wind Harmer
1.016
209071AE2-133 GEN
Solar/Wind Harmer
1.677
3147666LOUISA
Solar/Wind Helper
0.667
3141906WESTMOR
Solar/Wind Helper
0.114
316458AB2-190 GEN2
Solar/Wind Helper
1.581
3144873MCLAUGH
Solar/Wind Helper
0.007
316246AF1-032 C
Solar/Wind Helper
0.311
316321Z2-027
Solar/Wind Helper
0.413
3146626S HERTFORD
Solar/Wind Helper
0.269
3146926FARMVIL
Solar/Wind Helper
0.158
3142666NORTHAMPTON
Solar/Wind Helper
0.26
316190AA2-174 GEN
Solar/Wind Helper
0.018
3148013FISHERV
Solar/Wind Helper
0.26
316305AF2-043 C
Solar/Wind Helper
0.366
316320Y1-086
Solar/Wind Helper
0.122
3146516WINFALL
Solar/Wind Helper
0.27
3146776BUCKING
Solar/Wind Helper
0.095
315735AD1-075 GEN1
Solar/Wind Helper
1.513
3145893MURPHYS
Solar/Wind Helper
0.094
3145893MURPHYS
Solar/Wind Helper
0.263
3146263WOODLND
Solar/Wind Helper
0.261
3145963POPLR C
Solar/Wind Helper
0.26
316011AB1-132 GEN
Solar/Wind Helper
2.806
270494AE1-108_GEN
Solar/Wind Helper
3.414
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
237038AE2-054 C
Solar/Wind Helper
0.23
270173AC1-122 GEN
Solar/Wind Helper
1.533
232410W1-006 C
Solar/Wind Harmer
1.305
233946AB2-136 GEN
Solar/Wind Harmer
5.198
233952AC2-187 GEN
Solar/Wind Harmer
1.466
233954AC2-188 GEN
Solar/Wind Harmer
1.466
233984AB2-036 GEN
Solar/Wind Harmer
16.143
233930AB2-032 GEN
Solar/Wind Harmer
1.073
233982AB2-133 GEN
Solar/Wind Harmer
6.271
230511AF1-262
Solar/Wind Harmer
0.209
228754AB1-001 C
Solar/Wind Harmer
0.159
228307PCLP GT
Adder
13.804
219272CLEANLIGHT C
Solar/Wind Harmer
0.206
213587EDDYSTN3
Adder
89.65
217081WEATEXAS C
Solar/Wind Harmer
0.094
217083KRNY_132
Adder
10.131
207471AF2-354 C
Solar/Wind Harmer
0.559
20675928HOL_W4-097
Solar/Wind Harmer
0.142
961541AF2-445A GEN
Solar/Wind Harmer
3.357
209010PEIP 1
Adder
3.664
209010PEIP 1
Adder
0.537
961431AF2-434 GEN
Solar/Wind Harmer
1.014
209130AF1-271A GEN
Solar/Wind Harmer
2.787
316411AF1-147_GEN1
Solar/Wind Helper
1.093
237061AD1-155 GEN
Solar/Wind Helper
1.762
316312AB1-027
Solar/Wind Helper
0.535
3143526WINTERP
Solar/Wind Helper
1.45
316185AD1-033 GEN
Solar/Wind Helper
1.286
235020AA1-095 C
Solar/Wind Helper
0.051
3144356SAPONY
Solar/Wind Helper
0.483
316315AB2-025 C
Solar/Wind Helper
0.411
3145796HORNRTN
Solar/Wind Helper
0.777
316237AB2-079_GEN
Solar/Wind Helper
0.346
315687AD1-152 GEN
Solar/Wind Helper
1.377
238221AF1-254 C O1
Solar/Wind Helper
0.248
316248AF1-058 C
Solar/Wind Helper
0.337
270013AE1-250 PV
Solar/Wind Helper
0.847
3145933PARMELE
Solar/Wind Helper
0.257
3146233WITAKRS
Solar/Wind Helper
0.273
3146233WITAKRS
Solar/Wind Helper
0.172
235067AD1-061 GEN
Solar/Wind Helper
0.375
316197AC1-042 GEN
Solar/Wind Helper
0.216
237002AB1-128_GEN
Solar/Wind Helper
0.364
3146083TARBORO
Solar/Wind Helper
0.253
3138543CONSLDL
Solar/Wind Helper
0.167
238109AE1-109 GEN2
Solar/Wind Helper
0.094
316003AC1-222 GEN
Solar/Wind Helper
1.078
227287AC2-120 GEN
Solar/Wind Helper
0.335
316222AC1-221 GEN
Solar/Wind Helper
1.39
316283AC2-100 C
Solar/Wind Helper
1.294
G-007ALTFEXP_G-007A->PJM
CMTX
56.425
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.076
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.554
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.195
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.981
VTFLTFEXP_VFT->PJM
CMTX
148.636
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.489
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.577

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.99 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4357.18
MW Contribution:
11.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232912OH NUG1
Adder
11.524
971195AH1-057 GEN
Solar/Wind Harmer
1.272
233955AB2-172 GEN
Solar/Wind Harmer
6.511
200195DELTA ST
50/50
3.37
232920IR10
Adder
4.124
233901CHERRYDALE C
Solar/Wind Harmer
1.467
232913OH NUG2
Adder
11.371
231906DC3 NUG
Adder
18.083
231907DC10
Adder
4.514
970597AG2-380 GEN
Solar/Wind Harmer
5.38
972141AH1-641 GEN
Solar/Wind Harmer
3.295
213611FALLS1-3
Adder
3.931
213611FALLS1-3
Adder
3.931
20715028HAN_X4-015
Solar/Wind Harmer
0.331
207507AE2-000G3
Solar/Wind Harmer
34.93
207445AB1-138_GEN
Solar/Wind Harmer
0.641
20720628TIN_W1-124
Solar/Wind Harmer
1.098
971521AH1-258 GEN
Solar/Wind Harmer
2.985
20675528CPH_W2-050
Solar/Wind Harmer
0.631
20676428JCR_X2-075
Solar/Wind Harmer
0.375
217086KRNY_131
Adder
10.108
20675128HRM_W1-127
Solar/Wind Harmer
0.185
209029WAYMART-WD
Solar/Wind Harmer
2.676
959421AF2-233 GEN
Solar/Wind Harmer
0.991
205951AE1-129_GEN
Solar/Wind Harmer
7.691
203926AA2-133 GEN
Adder
2.266
3138216PACIFIC
Solar/Wind Helper
0.054
316164AC1-076 GEN
Solar/Wind Helper
1.421
3141813NORNECK
Solar/Wind Helper
0.282
957601AF2-054 GEN
Solar/Wind Helper
0.374
316233AE1-074 FULL
Solar/Wind Helper
0.426
316018AA1-139 ULT2
Solar/Wind Helper
1.173
315800Z1-036_GEN1
Solar/Wind Helper
1.475
315732AD1-074 GEN1
Solar/Wind Helper
3.025
3145893MURPHYS
Solar/Wind Helper
0.711
3145893MURPHYS
Solar/Wind Helper
0.263
316463AE2-346 GEN
Solar/Wind Helper
0.24
3145513AHOSKIE
Solar/Wind Helper
0.117
3145513AHOSKIE
Solar/Wind Helper
0.262
3137643SOCKMAN
Solar/Wind Helper
1.041
316426AA2-053 GEN
Solar/Wind Helper
1.489
316174AB2-169 GEN
Solar/Wind Helper
0.665
3144303KENBRDG
Solar/Wind Helper
0.207
316327AA2-057 GEN
Solar/Wind Helper
1.457
226929AD2-058 GEN
Solar/Wind Helper
0.099
270457AD2-023 GEN
Solar/Wind Helper
0.904
200204Y1-065-CTG1
50/50
4.513
233918AB1-142 GEN
Solar/Wind Harmer
1.274
228206SHRMN CT
Adder
19.053
228260V4-054C
Solar/Wind Harmer
1.177
228729W2-030 C
Solar/Wind Harmer
0.659
219686LUMSOLAR_N C
Solar/Wind Harmer
0.228
219348LDSOLAR C
Solar/Wind Harmer
0.668
213611FALLS1-3
Adder
3.931
214194N WALES4
Adder
0.948
20720428HOL_W1-112
Solar/Wind Harmer
0.381
20635828PARLN1&2
Adder
8.15
20635028RRCT1&2
Adder
12.973
218524CNTRALGAS1 C
Solar/Wind Harmer
0.406
217209CENTRL HS C
Solar/Wind Harmer
0.049
20671828STAW2-080
Solar/Wind Harmer
0.115
207439AE1-081 C O1
Solar/Wind Harmer
0.065
207530AG1-191 GEN
Solar/Wind Harmer
1.503
211065PSPA IPP
Solar/Wind Harmer
0.487
961301AF2-421 GEN
Solar/Wind Harmer
1.052
963151AG1-164 GEN
Solar/Wind Harmer
1.052
961341AF2-425 GEN
Solar/Wind Harmer
1.016
212507AE2-042_GEN
Solar/Wind Harmer
2.994
20328326MANOR_T86
Adder
0.126
316337AD2-073 GEN
Solar/Wind Helper
0.431
3141726DUNNSVL
Solar/Wind Helper
1.126
316132AB2-190 GEN1
Solar/Wind Helper
1.581
315773AC2-141 GEN
Solar/Wind Helper
5.904
316036AC1-147 C
Solar/Wind Helper
0.417
3146516WINFALL
Solar/Wind Helper
0.874
3146516WINFALL
Solar/Wind Helper
0.27
3146776BUCKING
Solar/Wind Helper
0.106
3145893MURPHYS
Solar/Wind Helper
1.053
315607AA1-063A GEN
Solar/Wind Helper
1.496
3146263WOODLND
Solar/Wind Helper
0.261
3145963POPLR C
Solar/Wind Helper
0.26
316494AC1-189 GEN
Solar/Wind Helper
1.554
961671AG1-007 GEN
Solar/Wind Helper
0.182
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.202
238108AE1-109 GEN1
Solar/Wind Helper
0.094
200035PCHBTM 3
50/50
22.891
233971AC1-093 C
Solar/Wind Harmer
3.326
232918OH NUG7
Adder
11.448
232905CHERITON_25
Adder
3.201
233994AC2-023 GEN
Solar/Wind Harmer
3.501
234036AF2-325 C
Solar/Wind Harmer
1.194
232901NORTHST
Adder
10.877
234033AF1-007_GEN
Solar/Wind Harmer
48.544
233996TM1833_GEN
Solar/Wind Harmer
1.3
232426Y1-080 FULL
Solar/Wind Harmer
0.249
232902EASTMUNI
Adder
16.935
234012AE2-112_GEN
Solar/Wind Harmer
2.973
972251AH1-710 GEN
Adder
57.78
231918WEST 1
Adder
4.241
228732V1-021 C
Adder
0.217
228400MICK 1CT
Adder
13.436
219766PARADISE C
Solar/Wind Harmer
0.355
20714528FRN_Y2-051
Solar/Wind Harmer
0.326
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
217208PARK ELE C
Solar/Wind Harmer
0.028
966261AG1-495 GEN
Solar/Wind Harmer
3.838
20674628WNG_W3-110
Solar/Wind Harmer
0.441
209023WIENIPP1
Adder
11.34
209025WIENIPP3
Adder
5.661
963071AG1-156 GEN
Solar/Wind Harmer
10.328
205967AE2-211_GEN
Solar/Wind Harmer
5.78
316447AC1-158 HLD
Solar/Wind Helper
3.661
316192AB2-158 GEN
Solar/Wind Helper
1.952
3142416OLDCHRC
Solar/Wind Helper
0.728
3142416OLDCHRC
Solar/Wind Helper
0.279
3141766HARMONY
Solar/Wind Helper
0.056
315975AC1-164 GENB
Solar/Wind Helper
0.106
3142433PROV 92
Solar/Wind Helper
1.115
3145336SMITFLD
Solar/Wind Helper
1.096
316375AC2-012 GEN
Solar/Wind Helper
0.719
3146456SLIGO L269
Solar/Wind Helper
0.272
3145663CRESWEL
Solar/Wind Helper
0.744
316023GEN1_S
Solar/Wind Helper
1.006
3146206CASHIE
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.262
3156021HOLLOMANSOL
Solar/Wind Helper
2
3145683EARLEYS
Solar/Wind Helper
0.262
316131AB2-060 GEN
Solar/Wind Helper
1.571
3146083TARBORO
Solar/Wind Helper
0.253
316359AB2-059 GEN
Solar/Wind Helper
1.925
238110AE1-109 GEN3
Solar/Wind Helper
0.094
964991AG1-363 GEN
Solar/Wind Helper
3.499
3147123OTTER R
Solar/Wind Helper
0.138
232926CRISFLD1
Adder
2.561
231940T-011
Adder
0.973
234041AC1-190 GEN
Solar/Wind Harmer
11.667
228201CARL#2CT
Adder
7.885
228200CARL#1CT
Adder
7.5
219904AC1-010 C
Solar/Wind Harmer
0.426
219906AC1-017 C
Solar/Wind Harmer
0.249
213815MOSER1-3
Adder
3.966
213815MOSER1-3
Adder
3.966
20720828JCB_W4-025
Solar/Wind Harmer
0.502
20714828MDF_W3-079
Solar/Wind Harmer
0.338
219817TRENTONSOL C
Solar/Wind Harmer
1.217
20641628MLH_W1-032
Solar/Wind Harmer
0.324
20742028HF_AC1-207
Solar/Wind Harmer
0.864
218438BLK ROCK C
Solar/Wind Harmer
0.15
972260AH1-715 GEN1
Adder
15.115
972261AH1-715 GEN2
Adder
17.584
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.08
217206BARNGR HS C
Solar/Wind Harmer
0.034
217204WCALDSOLAR C
Solar/Wind Harmer
0.08
20674828DL_W4-046
Solar/Wind Harmer
0.705
20634528N27_Y2-018
Solar/Wind Harmer
0.294
238147AE2-230_GEN1
Solar/Wind Helper
0.493
315976AC1-164 GENA
Solar/Wind Helper
3.598
316169AC1-164_GENC
Solar/Wind Helper
3.108
3142946ENON
Solar/Wind Helper
0.028
316294AC1-161 GEN
Solar/Wind Helper
5.017
316349AD2-085 GEN
Solar/Wind Helper
1.247
3146386ELIZ CT
Solar/Wind Helper
0.271
316431W1029_GEN1
Solar/Wind Helper
1.092
316433W1029_GEN2
Solar/Wind Helper
1.092
316365GEN2_N
Solar/Wind Helper
1.006
3146173TUNIS
Solar/Wind Helper
0.262
3146173TUNIS
Solar/Wind Helper
0.262
316097T157 G90
Solar/Wind Helper
1.209
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3146843MT LREL
Solar/Wind Helper
0.253
3146843MT LREL
Solar/Wind Helper
0.253
237080AD1-060 GEN
Solar/Wind Helper
0.298
200192DELTA CT1
50/50
2.181
200054ROCKSP 3
50/50
2.872
972177AH1-672 GEN
Solar/Wind Harmer
17.531
232408W1-005 C
Solar/Wind Harmer
1.304
232917OH NUG6
Adder
11.473
232915OH NUG4
Adder
11.448
233944AB2-135 GEN
Solar/Wind Harmer
6.75
219907AC1-030 C
Solar/Wind Harmer
0.156
213958STHWK5-6
Adder
3.049
20716028EGP_W2-019
Solar/Wind Harmer
0.515
207522AF2-254 C
Solar/Wind Harmer
1.592
218428ETC SOLAR C
Solar/Wind Harmer
0.039
219908AB1-139 C
Solar/Wind Harmer
0.418
972275AH1-722 GEN
Adder
34.701
20673628F1S_V4-069
Solar/Wind Harmer
0.197
207528AF2-192 GEN
Solar/Wind Harmer
1.396
217186ESSEX_G9
Adder
4.329
217083KRNY_132
Adder
10.195
20676228FRD_X1-012
Solar/Wind Harmer
0.646
20675828AU_W4-064
Solar/Wind Harmer
0.189
20675728RH_W2-091
Solar/Wind Harmer
0.657
207484AF2-139 C O1
Solar/Wind Harmer
0.551
208909MACR G3
Adder
173.357
209010PEIP 1
Adder
0.666
946731AF1-337 GEN
Solar/Wind Harmer
0.993
209008PAXT IPP
Adder
1.814
316415AF1-147_GEN2
Solar/Wind Helper
1.093
238175AF1-290_GEN
Solar/Wind Helper
0.162
964211AG1-282 GEN
Solar/Wind Helper
0.38
3143526WINTERP
Solar/Wind Helper
1.45
315671AE2-027_GEN
Solar/Wind Helper
2.23
316072AD1-144
Solar/Wind Helper
0.312
3147983MERCK5
Solar/Wind Helper
0.105
3145823KELFORD
Solar/Wind Helper
0.26
232904IR4
Adder
105.525
232432Z2-076 GEN
Solar/Wind Harmer
0.172
233968AD2-076_GEN
Solar/Wind Harmer
8.568
231919CHRIST1
Adder
5.58
231920CHRIST2
Adder
5.456
230422AE1-104_GEN1
Solar/Wind Harmer
38.601
230425AE1-104_GEN2
Solar/Wind Harmer
38.601
230430AE1-229_GEN
Solar/Wind Harmer
32.777
230407AD2-065 C
Solar/Wind Harmer
0.15
20720728JCB_W1-129
Solar/Wind Harmer
0.331
207500AE2-000G1
Solar/Wind Harmer
34.93
970025AG2-016 GEN
Solar/Wind Harmer
3.14
20714428HOW_X1-037
Solar/Wind Harmer
1.363
218449LINSOLAR C
Solar/Wind Harmer
1.105
217147KRNY_1212
Adder
9.697
217147KRNY_1212
Adder
9.524
217146KRNY_1234
Adder
9.502
217146KRNY_1234
Adder
9.437
964851AG1-348 GEN
Solar/Wind Harmer
1.491
207408W3-077 C
Solar/Wind Harmer
0.552
20462827N BANGR8
Adder
0.781
209026WIENIPP4
Adder
5.603
209054AE2-059 GEN
Solar/Wind Harmer
1.689
20486527WR_V4-052
Adder
1.063
209067AE2-060 GEN
Solar/Wind Harmer
1.327
200917MEHOOPANY_G
Solar/Wind Harmer
3.649
315651AD1-115 GEN
Solar/Wind Helper
1.009
238169AE2-226 GEN1
Solar/Wind Helper
0.722
238170AE2-226 GEN2
Solar/Wind Helper
0.722
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
316059AD1-063 C
Solar/Wind Helper
0.282
313526AB2-022
Solar/Wind Helper
0.414
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
3146206CASHIE
Solar/Wind Helper
0.263
961941AG1-037 GEN
Solar/Wind Helper
0.088
3146043SEABORD
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.523
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
316486AD2-202 GEN
Solar/Wind Helper
0.373
316274AC1-208 GEN
Solar/Wind Helper
1.57
3148463FAIRFLD
Solar/Wind Helper
0.251
3147173SINAI
Solar/Wind Helper
0.25
3147243WELCO
Solar/Wind Helper
0.156
270455AD2-022 GEN
Solar/Wind Helper
1.372
270197AD1-017 GEN1
Solar/Wind Helper
1.224
200200DELTA2 CT1
50/50
3.904
200193DELTA CT2
50/50
2.181
200203Y1-065-STG
50/50
7.816
200055ROCKSP 4
50/50
2.823
200202DELTA2 ST
50/50
6.611
200052ROCKSP 1
50/50
2.839
200053ROCKSP 2
50/50
2.784
233940AF2-379 C
Solar/Wind Harmer
0.243
230434AG1-499 GEN
Solar/Wind Harmer
0.661
219258KINSLEYDEP C
Solar/Wind Harmer
0.365
213942SCHUYLKILL
Adder
3.987
213942SCHUYLKILL
Adder
3.049
213957STHWK3-4
Adder
3.049
213957STHWK3-4
Adder
3.049
213561DLWR9-10
Adder
3.976
213561DLWR9-10
Adder
3.04
219610FLORENCE C
Solar/Wind Harmer
1.547
963401AG1-189 GEN
Solar/Wind Harmer
2.52
971189AH1-054 GEN
Solar/Wind Harmer
1.307
20716228APLW2-078
Solar/Wind Harmer
0.975
20673828FLE_V3-070
Solar/Wind Harmer
0.512
20676128MHD_W3-029
Solar/Wind Harmer
0.524
209027LOR2_Q27
Solar/Wind Harmer
4.673
964051AG1-259 GEN
Solar/Wind Harmer
1.329
200194DELTA CT3
50/50
2.181
233970AC1-092 C
Solar/Wind Harmer
3.503
232900DEMECSMY
Adder
12.041
232404W1-003 C
Solar/Wind Harmer
1.304
233998TM1NIN_3.36
Solar/Wind Harmer
1.3
232919VN10
Adder
3.66
231917EM10
Adder
2.964
970997AG2-616 GEN
Solar/Wind Harmer
10.982
213497CHSTR7-9
Adder
3.07
213497CHSTR7-9
Adder
3.07
213560DLW11-12
Adder
3.04
219222BRL12CT2
Adder
9.969
20717128DIX_Z2-102
Solar/Wind Harmer
1.464
20715828PEM_W1-120
Solar/Wind Harmer
0.592
963711AG1-223 GEN
Solar/Wind Harmer
1.636
219276PARKLANDSO C
Solar/Wind Harmer
0.51
20715228NPK_W1-113
Solar/Wind Harmer
0.474
20720528MAN_W1-024
Solar/Wind Harmer
0.28
219919AE1-041 FULL
Solar/Wind Harmer
0.044
217121ECCF
Adder
0.476
20676728BRNX1-095
Solar/Wind Harmer
0.193
20676328BVR_Y1-020
Solar/Wind Harmer
0.361
20674928WA_W3-044
Solar/Wind Harmer
0.525
971519AH1-257 GEN
Solar/Wind Harmer
2.751
207518AF1-320_GEN
Solar/Wind Harmer
3.988
20465127PORT CT
Adder
3.272
209018SUNBIPCT
Adder
7.383
20465527S.RDG CT
Adder
2.722
209137AF2-361 C
Solar/Wind Harmer
2.564
200034PCHBTM 2
50/50
22.744
200205Y1-065-CTG2
50/50
4.513
234015AF2-250 C
Solar/Wind Harmer
0.157
232428Y3-058 C
Solar/Wind Harmer
1.087
232424Y1-079 C
Solar/Wind Harmer
0.728
228251CARLLS#4
Adder
0.723
230433AD2-135 GEN
Solar/Wind Harmer
0.116
228351V2-046C
Solar/Wind Harmer
2.305
219287REEVESEAST C
Solar/Wind Harmer
1.515
213589EDDYSTN4
Adder
89.642
213535CROYDN11
Adder
11.419
214067T20SOLAR
Solar/Wind Harmer
0.281
20636128O CRK C2
Adder
7.146
207459AE1-142 C O1
Solar/Wind Harmer
1.168
20628028LAKEHURS
Adder
1.053
217197RE CRAN C
Solar/Wind Harmer
0.591
924131AB2-057 GEN
Solar/Wind Harmer
1.132
20635128RRCT3&4
Adder
12.33
20635128RRCT3&4
Adder
10.756
218419LINDEN_G6
Adder
18.876
20675428EAM_W2-061
Solar/Wind Harmer
0.207
219035LINDEN_G8
Adder
18.107
972237AH1-703 GEN
Adder
11.097
20465127PORT CT
Adder
4.342
20465527S.RDG CT
Adder
2.634
316450AC1-158 RIC
Solar/Wind Helper
0.444
966001AG1-469 GEN
Solar/Wind Helper
0.309
238148AE2-230_GEN2
Solar/Wind Helper
0.493
316487AF1-042 GEN
Solar/Wind Helper
0.284
316033AB2-134 GEN
Solar/Wind Helper
0.955
3145506HICKORY
Solar/Wind Helper
1.09
3145506HICKORY
Solar/Wind Helper
0.654
3145506HICKORY
Solar/Wind Helper
0.163
316339AD2-160 GEN
Solar/Wind Helper
1.039
316388AE2-253 GEN
Solar/Wind Helper
1.039
3137176SLIGO L2192
Solar/Wind Helper
1.082
3130086AYDLETT
Solar/Wind Helper
1.087
3146626S HERTFORD
Solar/Wind Helper
0.269
3146626S HERTFORD
Solar/Wind Helper
0.269
3132123MT JACKSON
Solar/Wind Helper
0.834
313506AB2-031 GEN
Solar/Wind Helper
1.188
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
3142666NORTHAMPTON
Solar/Wind Helper
0.26
232910NRG_G1
Adder
11.214
234014AF1-036_GEN
Solar/Wind Harmer
3.497
232436AB1-176 C
Solar/Wind Harmer
0.296
972233AH1-701 GEN
Adder
4.776
219912AD2-042 GEN
Solar/Wind Harmer
0.895
219607WPEMNERT C
Solar/Wind Harmer
0.468
219304NAMERICA C
Solar/Wind Harmer
0.346
20635028RRCT1&2
Adder
12.774
218418LINDEN_G5
Adder
18.876
219036LINDEN_G7
Adder
18.369
217086KRNY_131
Adder
10.216
20674328GAR_V4-001
Solar/Wind Harmer
0.12
946751AF1-339 GEN
Solar/Wind Harmer
0.993
316006AB2-029 C
Solar/Wind Helper
0.146
316045AC1-158 PL2
Solar/Wind Helper
5.324
238149AF1-291A_GEN
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.379
315666AE1-190 GEN
Solar/Wind Helper
0.376
316156AD2-030 GEN
Solar/Wind Helper
0.422
316240AF1-291 C
Solar/Wind Helper
0.372
316313AB2-026
Solar/Wind Helper
0.418
316435W1029_GEN3
Solar/Wind Helper
1.092
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
315614AA2-178 GEN
Solar/Wind Helper
1.624
3146776BUCKING
Solar/Wind Helper
1.059
3146776BUCKING
Solar/Wind Helper
0.086
3145893MURPHYS
Solar/Wind Helper
0.378
3145893MURPHYS
Solar/Wind Helper
0.474
316140AB2-099
Solar/Wind Helper
0.1
316005AA1-067
Solar/Wind Helper
0.293
316118AC1-105 GEN
Solar/Wind Helper
0.979
233973AC2-185 C
Solar/Wind Harmer
7.078
970695AG2-447 GEN
Solar/Wind Harmer
4.682
233987AB2-037 GEN
Solar/Wind Harmer
14.839
233923SMA
Solar/Wind Harmer
4.768
233997TMININ_4.2
Solar/Wind Harmer
1.3
232907VN8
Adder
39.17
232417X3-008 C
Solar/Wind Harmer
1.465
233935AB2-179 C
Solar/Wind Harmer
3.168
219221BRL12CT1
Adder
9.969
219223BRL12CT3
Adder
9.969
959561AF2-247 GEN
Solar/Wind Harmer
0.539
20715728PEM_W1-119
Solar/Wind Harmer
0.592
20636028O CRK C1
Adder
7.838
971667AH1-334 GEN
Solar/Wind Harmer
3.043
219727YARDVSOLFA C
Solar/Wind Harmer
1.007
20635828PARLN1&2
Adder
3.691
219249CENTRALDIV C
Solar/Wind Harmer
0.044
207442AE1-156 GEN
Solar/Wind Harmer
0.816
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217194REDH C
Solar/Wind Harmer
0.54
207511W3-106 GEN
Solar/Wind Harmer
0.361
971007AG2-625 GEN
Solar/Wind Harmer
2.804
20466127PORT 5CT
Adder
28.879
20674128FR_U2-059
Solar/Wind Harmer
0.201
211065PSPA IPP
Solar/Wind Harmer
0.487
957921AF2-086 GEN
Solar/Wind Harmer
0.986
3132273ORANGE
Solar/Wind Helper
0.058
316223AC1-118
Solar/Wind Helper
0.435
23546401DTGZ2-030
Solar/Wind Helper
0.089
964061AG1-260 GEN
Solar/Wind Harmer
1.329
208862AG1-362 C
Solar/Wind Harmer
0.769
20390726Y2-042
Adder
2.772
3141426STAFORD
Solar/Wind Helper
0.066
316468AD1-105 GEN
Solar/Wind Helper
1.37
3141913WHIT STONE
Solar/Wind Helper
0.279
957831AF2-077 GEN
Solar/Wind Helper
0.374
315697AD1-025 GEN
Solar/Wind Helper
3.154
315839AE2-212 C
Solar/Wind Helper
0.371
316258AE1-075 C
Solar/Wind Helper
0.376
316316AC1-027 C
Solar/Wind Helper
0.431
316322AB2-045
Solar/Wind Helper
0.296
3148133STUARTS
Solar/Wind Helper
0.156
3145796HORNRTN
Solar/Wind Helper
0.829
3145796HORNRTN
Solar/Wind Helper
0.104
316210AC1-098 GEN
Solar/Wind Helper
2.082
316238AB2-078_GEN
Solar/Wind Helper
0.346
316239AB2-077_GEN
Solar/Wind Helper
0.346
3145746EVERETS
Solar/Wind Helper
1.017
3145746EVERETS
Solar/Wind Helper
0.255
3145746EVERETS
Solar/Wind Helper
0.255
3145746EVERETS
Solar/Wind Helper
0.255
3145573BETHELC
Solar/Wind Helper
0.253
3145573BETHELC
Solar/Wind Helper
0.253
200201DELTA2 CT2
50/50
3.904
232899W1-062
Adder
12.553
232410W1-006 C
Solar/Wind Harmer
1.304
233946AB2-136 GEN
Solar/Wind Harmer
5.197
233952AC2-187 GEN
Solar/Wind Harmer
1.465
233954AC2-188 GEN
Solar/Wind Harmer
1.465
233984AB2-036 GEN
Solar/Wind Harmer
16.137
233930AB2-032 GEN
Solar/Wind Harmer
1.073
233982AB2-133 GEN
Solar/Wind Harmer
6.269
230511AF1-262
Solar/Wind Harmer
0.209
228754AB1-001 C
Solar/Wind Harmer
0.159
228307PCLP GT
Adder
13.801
219272CLEANLIGHT C
Solar/Wind Harmer
0.206
213587EDDYSTN3
Adder
89.636
217081WEATEXAS C
Solar/Wind Harmer
0.094
217083KRNY_132
Adder
10.13
207471AF2-354 C
Solar/Wind Harmer
0.559
20675928HOL_W4-097
Solar/Wind Harmer
0.142
961541AF2-445A GEN
Solar/Wind Harmer
3.357
209010PEIP 1
Adder
3.663
209010PEIP 1
Adder
0.537
961431AF2-434 GEN
Solar/Wind Harmer
1.014
209130AF1-271A GEN
Solar/Wind Harmer
2.787
316411AF1-147_GEN1
Solar/Wind Helper
1.093
237061AD1-155 GEN
Solar/Wind Helper
1.762
316312AB1-027
Solar/Wind Helper
0.535
3143526WINTERP
Solar/Wind Helper
1.45
316185AD1-033 GEN
Solar/Wind Helper
1.286
235020AA1-095 C
Solar/Wind Helper
0.051
3144356SAPONY
Solar/Wind Helper
0.483
316315AB2-025 C
Solar/Wind Helper
0.411
233972AC1-094 C
Solar/Wind Harmer
2.813
232921TASLEY2G
Adder
6.735
233950AC2-186 GEN
Solar/Wind Harmer
0.733
228711V2-041C
Solar/Wind Harmer
0.69
219921AF1-264
Solar/Wind Harmer
0.163
218660EHAMPSOLAR C
Solar/Wind Harmer
0.197
213497CHSTR7-9
Adder
3.07
219688LUMSOLAR_S C
Solar/Wind Harmer
0.228
219914AD2-027 C
Solar/Wind Harmer
0.675
213560DLW11-12
Adder
3.04
207454AA2-184 E
Solar/Wind Harmer
1.102
20635928PARLN3&4
Adder
3.691
217169METRODIV C
Solar/Wind Harmer
0.044
963161AG1-165 GEN
Solar/Wind Harmer
1.052
208972BECR K09
Solar/Wind Harmer
1.098
961331AF2-424 GEN
Solar/Wind Harmer
1.016
209071AE2-133 GEN
Solar/Wind Harmer
1.677
3147666LOUISA
Solar/Wind Helper
0.667
3141906WESTMOR
Solar/Wind Helper
0.114
316458AB2-190 GEN2
Solar/Wind Helper
1.581
3144873MCLAUGH
Solar/Wind Helper
0.007
316246AF1-032 C
Solar/Wind Helper
0.311
316321Z2-027
Solar/Wind Helper
0.413
3146626S HERTFORD
Solar/Wind Helper
0.269
3146926FARMVIL
Solar/Wind Helper
0.158
3142666NORTHAMPTON
Solar/Wind Helper
0.26
316190AA2-174 GEN
Solar/Wind Helper
0.018
3148013FISHERV
Solar/Wind Helper
0.26
3145933PARMELE
Solar/Wind Helper
0.257
3146233WITAKRS
Solar/Wind Helper
0.273
3146233WITAKRS
Solar/Wind Helper
0.172
235067AD1-061 GEN
Solar/Wind Helper
0.374
316197AC1-042 GEN
Solar/Wind Helper
0.216
237002AB1-128_GEN
Solar/Wind Helper
0.364
941421AE2-139 GEN
Solar/Wind Harmer
2.746
316044AC1-158 PL1
Solar/Wind Helper
1.664
3147666LOUISA
Solar/Wind Helper
1.16
238152AF2-075_GEN
Solar/Wind Helper
0.704
316404AE1-155 C
Solar/Wind Helper
2.405
3138133OCRAN
Solar/Wind Helper
0.168
315662AE1-191 GEN
Solar/Wind Helper
1.504
316280AD1-041 GEN
Solar/Wind Helper
0.94
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316369SG1_INVT
Solar/Wind Helper
1.33
316381AD1-082 GEN
Solar/Wind Helper
1.419
319010AE1-072 C
Solar/Wind Helper
3.113
23777901MDS_W4-102
Solar/Wind Helper
0.171
315611Z1-036_GEN2
Solar/Wind Helper
1.475
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.218
315737AD1-076 GEN
Solar/Wind Helper
2.587
3146926FARMVIL
Solar/Wind Helper
0.158
316087AB2-174 GEN
Solar/Wind Helper
1.831
315785AD2-033 C
Solar/Wind Helper
3.018
3146233WITAKRS
Solar/Wind Helper
1.008
270018AE2-047 C O1
Solar/Wind Helper
0.792
3145796HORNRTN
Solar/Wind Helper
0.777
316237AB2-079_GEN
Solar/Wind Helper
0.346
315687AD1-152 GEN
Solar/Wind Helper
1.377
238221AF1-254 C O1
Solar/Wind Helper
0.248
316248AF1-058 C
Solar/Wind Helper
0.337
270013AE1-250 PV
Solar/Wind Helper
0.847
233939AC1-091 C
Solar/Wind Harmer
3.503
232914OH NUG3
Adder
11.524
232916OH NUG5
Adder
11.524
233933AB2-153 GEN
Solar/Wind Harmer
1.448
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
213958STHWK5-6
Adder
3.049
20716428NHV_W2-082
Solar/Wind Harmer
1.973
963391AG1-188 GEN
Solar/Wind Harmer
4.154
219612MATRIX C
Solar/Wind Harmer
0.202
20716928W4-060COL
Solar/Wind Harmer
0.783
217213AMBOY SO C
Solar/Wind Harmer
0.139
20673728F2S_V4-070
Solar/Wind Harmer
0.197
207510AF2-138 C
Solar/Wind Harmer
1.944
207437AD2-070 GEN
Solar/Wind Harmer
0.328
20671928W4-073
Solar/Wind Harmer
0.471
20633028GILCT9
Adder
30.815
20465427SHAW CT
Adder
4.196
209116AE2-175 GEN
Solar/Wind Harmer
4.448
970095AG2-074 GEN
Solar/Wind Harmer
6.541
961421AF2-433 GEN
Solar/Wind Harmer
1.014
209093AE2-110 GEN
Solar/Wind Harmer
2.535
209120AE2-241 GEN
Solar/Wind Harmer
3.354
946691AF1-333 GEN
Solar/Wind Harmer
0.993
946741AF1-338 GEN
Solar/Wind Harmer
0.993
972221AH1-695 GEN
Adder
123.573
3141196NOKESVL
Solar/Wind Helper
1.257
316077AC2-138 C
Solar/Wind Helper
0.266
316484AD2-074 GEN
Solar/Wind Helper
0.542
316075AC2-137 C
Solar/Wind Helper
0.426
315821AE2-092 GEN
Solar/Wind Helper
2.438
942461AE2-259 GEN
Solar/Wind Helper
1.765
966621AG1-532 GEN
Solar/Wind Helper
0.238
316317KELFORD C
Solar/Wind Helper
0.234
3145823KELFORD
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
1.036
3145796HORNRTN
Solar/Wind Helper
0.259
316212AC1-099_GEN
Solar/Wind Helper
1.156
23583801GRNGAP
Solar/Wind Helper
4.397
3145746EVERETS
Solar/Wind Helper
0.255
3145746EVERETS
Solar/Wind Helper
0.255
226910AB2-157 C
Solar/Wind Helper
0.014
232434Z2-077 GEN
Solar/Wind Harmer
0.326
232406W1-004 FULL
Solar/Wind Harmer
1.304
233964AF2-378 GEN
Solar/Wind Harmer
0.166
232422X3-066 FULL
Solar/Wind Harmer
0.323
230415AB2-049 C
Solar/Wind Harmer
0.217
219291REEVESSOUT C
Solar/Wind Harmer
0.068
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213815MOSER1-3
Adder
3.966
20714928UPF_X1-085
Solar/Wind Harmer
0.45
219114HARTZY_C
Solar/Wind Harmer
0.923
219918AC2-009 C
Solar/Wind Harmer
0.028
20674528F3S_W2-016
Solar/Wind Harmer
1.541
209025WIENIPP3
Adder
5.546
209142AF1-226 GEN
Solar/Wind Harmer
5.869
205941AD2-115 GEN
Solar/Wind Harmer
0.936
966881AG1-559 GEN
Solar/Wind Helper
0.389
316473AC1-191 GEN
Solar/Wind Helper
1.72
3142946ENON
Solar/Wind Helper
0.093
3145336SMITFLD
Solar/Wind Helper
0.11
316017AA1-139 ULT1
Solar/Wind Helper
1.247
3146456SLIGO L269
Solar/Wind Helper
0.272
3145273HOLLAND
Solar/Wind Helper
0.202
3146376EDENTON
Solar/Wind Helper
0.268
3146206CASHIE
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.262
316095T157 G97
Solar/Wind Helper
1.209
316499AE2-029_GEN
Solar/Wind Helper
0.88
316181AB2-040 GEN
Solar/Wind Helper
1.876
3147133PAMPLIN
Solar/Wind Helper
0.818
3147043LAWRENC
Solar/Wind Helper
0.156
316478AD1-087 GEN
Solar/Wind Helper
1.273
316420AA1-050 GEN
Solar/Wind Helper
1.459
3146073TAR RVR
Solar/Wind Helper
0.253
3146083TARBORO
Solar/Wind Helper
0.253
3138543CONSLDL
Solar/Wind Helper
0.167
238109AE1-109 GEN2
Solar/Wind Helper
0.094
316003AC1-222 GEN
Solar/Wind Helper
1.078
232813VAUGHN
Adder
0.766
231902DC CT7
Adder
14.456
233915AB1-141 GEN
Solar/Wind Harmer
1.274
970453AG2-297 GEN
Solar/Wind Harmer
3.176
964001AG1-254 GEN
Solar/Wind Harmer
8.339
228728W1-130C
Solar/Wind Harmer
0.759
227927V4-067C
Solar/Wind Harmer
0.226
219137THOSOLAR C
Solar/Wind Harmer
1.369
219615MILLCREEK C
Solar/Wind Harmer
0.267
219224BRL12CT4
Adder
9.969
207487AE2-000G4
Solar/Wind Harmer
34.93
207497AE2-000G2
Solar/Wind Harmer
34.93
219620RIDERU C
Solar/Wind Harmer
0.062
20635928PARLN3&4
Adder
8.15
218526CNTRALGAS2 C
Solar/Wind Harmer
0.407
217167KRNY_14
Adder
10.195
971009AG2-626 GEN
Solar/Wind Harmer
1.788
961261AF2-417 GEN
Solar/Wind Harmer
1.055
212266LOR1
Solar/Wind Harmer
1.239
959431AF2-234 GEN
Solar/Wind Harmer
1.982
20334726NME_Y1-047
Adder
2.453
3138133OCRAN
Solar/Wind Helper
0.084
3143873LANEXA
Solar/Wind Helper
0.167
3141873WAN 176
Solar/Wind Helper
0.056
316382AG1-145 C
Solar/Wind Helper
0.373
316159AE1-175 C
Solar/Wind Helper
0.421
316236AE1-162_GEN
Solar/Wind Helper
0.369
3143316POE
Solar/Wind Helper
1.084
316405AF2-144 C
Solar/Wind Helper
0.314
3146486SUNBURY
Solar/Wind Helper
0.271
3146486SUNBURY
Solar/Wind Helper
0.271
3145176PASQUOTANK
Solar/Wind Helper
0.168
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
3130546PLYMOUTH
Solar/Wind Helper
0.264
315733AD1-074 GEN2
Solar/Wind Helper
3.025
946281AF1-292 GEN
Solar/Wind Helper
0.263
3148013FISHERV
Solar/Wind Helper
0.149
3146033SCOT NK
Solar/Wind Helper
1.034
315616AA1-038_C
Solar/Wind Helper
1.137
3142666NORTHAMPTON
Solar/Wind Helper
0.156
3145593CAROLNA
Solar/Wind Helper
0.26
3145593CAROLNA
Solar/Wind Helper
0.26
3145933PARMELE
Solar/Wind Helper
0.514
3145933PARMELE
Solar/Wind Helper
0.257
316049AB1-081 GEN
Solar/Wind Helper
1.54
227287AC2-120 GEN
Solar/Wind Helper
0.335
316222AC1-221 GEN
Solar/Wind Helper
1.39
316283AC2-100 C
Solar/Wind Helper
1.294
3144536CHRHLND
Solar/Wind Helper
0.041
3142956BIRDNECK
Solar/Wind Helper
0.184
316305AF2-043 C
Solar/Wind Helper
0.366
316320Y1-086
Solar/Wind Helper
0.122
3146516WINFALL
Solar/Wind Helper
0.27
3146776BUCKING
Solar/Wind Helper
0.095
315735AD1-075 GEN1
Solar/Wind Helper
1.513
3145893MURPHYS
Solar/Wind Helper
0.094
3145893MURPHYS
Solar/Wind Helper
0.263
3146263WOODLND
Solar/Wind Helper
0.261
3145963POPLR C
Solar/Wind Helper
0.26
316011AB1-132 GEN
Solar/Wind Helper
2.806
270494AE1-108_GEN
Solar/Wind Helper
3.413
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
237038AE2-054 C
Solar/Wind Helper
0.23
270173AC1-122 GEN
Solar/Wind Helper
1.533
316123AC1-075 GEN
Solar/Wind Helper
1.469
3147312GRETNA
Solar/Wind Helper
0.046
237085AD2-009_GEN
Solar/Wind Helper
1.359
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.855
3145796HORNRTN
Solar/Wind Helper
0.259
316034AC1-036 C
Solar/Wind Helper
0.272
316129AC1-054 GEN
Solar/Wind Helper
1.278
3145746EVERETS
Solar/Wind Helper
0.255
3145746EVERETS
Solar/Wind Helper
0.255
3147312GRETNA
Solar/Wind Helper
0.183
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.847
G-007ALTFEXP_G-007A->PJM
CMTX
56.418
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.553
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.193
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.98
VTFLTFEXP_VFT->PJM
CMTX
148.621
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.489
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.574

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.65 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4342.89
MW Contribution:
11.15
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200195DELTA ST
50/50
3.38
232920IR10
Adder
4.144
233901CHERRYDALE C
Solar/Wind Harmer
1.474
232913OH NUG2
Adder
11.425
231906DC3 NUG
Adder
18.172
231907DC10
Adder
4.537
970597AG2-380 GEN
Solar/Wind Harmer
5.407
972141AH1-641 GEN
Solar/Wind Harmer
3.31
200204Y1-065-CTG1
50/50
4.53
233918AB1-142 GEN
Solar/Wind Harmer
1.281
228206SHRMN CT
Adder
19.144
228260V4-054C
Solar/Wind Harmer
1.183
228729W2-030 C
Solar/Wind Harmer
0.662
219686LUMSOLAR_N C
Solar/Wind Harmer
0.229
219348LDSOLAR C
Solar/Wind Harmer
0.671
213611FALLS1-3
Adder
3.95
214194N WALES4
Adder
0.952
20720428HOL_W1-112
Solar/Wind Harmer
0.383
20635828PARLN1&2
Adder
8.189
20635028RRCT1&2
Adder
13.036
218524CNTRALGAS1 C
Solar/Wind Harmer
0.408
217209CENTRL HS C
Solar/Wind Harmer
0.049
20671828STAW2-080
Solar/Wind Harmer
0.115
207439AE1-081 C O1
Solar/Wind Harmer
0.066
207530AG1-191 GEN
Solar/Wind Harmer
1.51
211065PSPA IPP
Solar/Wind Harmer
0.489
961301AF2-421 GEN
Solar/Wind Harmer
1.057
963151AG1-164 GEN
Solar/Wind Harmer
1.057
961341AF2-425 GEN
Solar/Wind Harmer
1.021
212507AE2-042_GEN
Solar/Wind Harmer
3.007
20328326MANOR_T86
Adder
0.126
316337AD2-073 GEN
Solar/Wind Helper
0.432
3141726DUNNSVL
Solar/Wind Helper
1.129
316132AB2-190 GEN1
Solar/Wind Helper
1.585
315773AC2-141 GEN
Solar/Wind Helper
5.92
316036AC1-147 C
Solar/Wind Helper
0.418
3146516WINFALL
Solar/Wind Helper
0.877
3146516WINFALL
Solar/Wind Helper
0.271
3146776BUCKING
Solar/Wind Helper
0.106
3145893MURPHYS
Solar/Wind Helper
1.056
315607AA1-063A GEN
Solar/Wind Helper
1.501
3146263WOODLND
Solar/Wind Helper
0.262
3145963POPLR C
Solar/Wind Helper
0.261
316494AC1-189 GEN
Solar/Wind Helper
1.559
961671AG1-007 GEN
Solar/Wind Helper
0.182
238108AE1-109 GEN1
Solar/Wind Helper
0.095
3145543BTLEBRO
Solar/Wind Helper
0.253
3145543BTLEBRO
Solar/Wind Helper
0.202
232901NORTHST
Adder
10.928
234033AF1-007_GEN
Solar/Wind Harmer
48.773
233996TM1833_GEN
Solar/Wind Harmer
1.306
232426Y1-080 FULL
Solar/Wind Harmer
0.25
232926CRISFLD1
Adder
2.573
231940T-011
Adder
0.978
234041AC1-190 GEN
Solar/Wind Harmer
11.722
228201CARL#2CT
Adder
7.923
228200CARL#1CT
Adder
7.535
219904AC1-010 C
Solar/Wind Harmer
0.428
219906AC1-017 C
Solar/Wind Harmer
0.251
213815MOSER1-3
Adder
3.985
213815MOSER1-3
Adder
3.985
20720828JCB_W4-025
Solar/Wind Harmer
0.505
20714828MDF_W3-079
Solar/Wind Harmer
0.34
219817TRENTONSOL C
Solar/Wind Harmer
1.223
20641628MLH_W1-032
Solar/Wind Harmer
0.325
20742028HF_AC1-207
Solar/Wind Harmer
0.868
232904IR4
Adder
106.022
232432Z2-076 GEN
Solar/Wind Harmer
0.173
233968AD2-076_GEN
Solar/Wind Harmer
8.611
231919CHRIST1
Adder
5.609
200035PCHBTM 3
50/50
22.955
233971AC1-093 C
Solar/Wind Harmer
3.342
232918OH NUG7
Adder
11.502
232905CHERITON_25
Adder
3.216
233994AC2-023 GEN
Solar/Wind Harmer
3.518
234036AF2-325 C
Solar/Wind Harmer
1.2
232910NRG_G1
Adder
11.268
234014AF1-036_GEN
Solar/Wind Harmer
3.515
232436AB1-176 C
Solar/Wind Harmer
0.297
972233AH1-701 GEN
Adder
4.799
219912AD2-042 GEN
Solar/Wind Harmer
0.899
219607WPEMNERT C
Solar/Wind Harmer
0.47
219304NAMERICA C
Solar/Wind Harmer
0.348
20635028RRCT1&2
Adder
12.835
218418LINDEN_G5
Adder
18.967
219036LINDEN_G7
Adder
18.458
217086KRNY_131
Adder
10.266
20674328GAR_V4-001
Solar/Wind Harmer
0.121
946751AF1-339 GEN
Solar/Wind Harmer
0.997
316006AB2-029 C
Solar/Wind Helper
0.147
316045AC1-158 PL2
Solar/Wind Helper
5.337
238149AF1-291A_GEN
Solar/Wind Helper
0.141
966871AG1-558 GEN
Solar/Wind Helper
0.38
315666AE1-190 GEN
Solar/Wind Helper
0.377
316156AD2-030 GEN
Solar/Wind Helper
0.423
316240AF1-291 C
Solar/Wind Helper
0.373
316313AB2-026
Solar/Wind Helper
0.419
316435W1029_GEN3
Solar/Wind Helper
1.095
3146516WINFALL
Solar/Wind Helper
0.271
3146516WINFALL
Solar/Wind Helper
0.271
3146516WINFALL
Solar/Wind Helper
0.271
200202DELTA2 ST
50/50
6.63
200052ROCKSP 1
50/50
2.85
200053ROCKSP 2
50/50
2.794
233940AF2-379 C
Solar/Wind Harmer
0.244
230434AG1-499 GEN
Solar/Wind Harmer
0.664
219258KINSLEYDEP C
Solar/Wind Harmer
0.367
213942SCHUYLKILL
Adder
4.008
213942SCHUYLKILL
Adder
3.065
213957STHWK3-4
Adder
3.065
213957STHWK3-4
Adder
3.065
213561DLWR9-10
Adder
3.996
213561DLWR9-10
Adder
3.056
219610FLORENCE C
Solar/Wind Harmer
1.554
963401AG1-189 GEN
Solar/Wind Harmer
2.532
971189AH1-054 GEN
Solar/Wind Harmer
1.314
20716228APLW2-078
Solar/Wind Harmer
0.979
20673828FLE_V3-070
Solar/Wind Harmer
0.515
20676128MHD_W3-029
Solar/Wind Harmer
0.527
233972AC1-094 C
Solar/Wind Harmer
2.826
232921TASLEY2G
Adder
6.767
233950AC2-186 GEN
Solar/Wind Harmer
0.736
228711V2-041C
Solar/Wind Harmer
0.694
219921AF1-264
Solar/Wind Harmer
0.164
213497CHSTR7-9
Adder
3.087
218660EHAMPSOLAR C
Solar/Wind Harmer
0.198
219688LUMSOLAR_S C
Solar/Wind Harmer
0.229
219914AD2-027 C
Solar/Wind Harmer
0.678
213560DLW11-12
Adder
3.056
207454AA2-184 E
Solar/Wind Harmer
1.107
20635928PARLN3&4
Adder
3.709
217169METRODIV C
Solar/Wind Harmer
0.044
963161AG1-165 GEN
Solar/Wind Harmer
1.057
208972BECR K09
Solar/Wind Harmer
1.103
961331AF2-424 GEN
Solar/Wind Harmer
1.021
209071AE2-133 GEN
Solar/Wind Harmer
1.685
3147666LOUISA
Solar/Wind Helper
0.669
3141906WESTMOR
Solar/Wind Helper
0.114
316458AB2-190 GEN2
Solar/Wind Helper
1.585
3144873MCLAUGH
Solar/Wind Helper
0.007
316246AF1-032 C
Solar/Wind Helper
0.312
316321Z2-027
Solar/Wind Helper
0.415
3146626S HERTFORD
Solar/Wind Helper
0.27
3146926FARMVIL
Solar/Wind Helper
0.159
3142666NORTHAMPTON
Solar/Wind Helper
0.261
316190AA2-174 GEN
Solar/Wind Helper
0.018
3148013FISHERV
Solar/Wind Helper
0.26
3145933PARMELE
Solar/Wind Helper
0.258
3146233WITAKRS
Solar/Wind Helper
0.274
3146233WITAKRS
Solar/Wind Helper
0.173
235067AD1-061 GEN
Solar/Wind Helper
0.375
316197AC1-042 GEN
Solar/Wind Helper
0.217
237002AB1-128_GEN
Solar/Wind Helper
0.365
200194DELTA CT3
50/50
2.188
233970AC1-092 C
Solar/Wind Harmer
3.52
232900DEMECSMY
Adder
12.097
232404W1-003 C
Solar/Wind Harmer
1.311
233998TM1NIN_3.36
Solar/Wind Harmer
1.306
232919VN10
Adder
3.677
231917EM10
Adder
2.979
970997AG2-616 GEN
Solar/Wind Harmer
11.034
213497CHSTR7-9
Adder
3.087
213497CHSTR7-9
Adder
3.087
213560DLW11-12
Adder
3.056
219222BRL12CT2
Adder
10.018
20717128DIX_Z2-102
Solar/Wind Harmer
1.471
20715828PEM_W1-120
Solar/Wind Harmer
0.595
963711AG1-223 GEN
Solar/Wind Harmer
1.644
219276PARKLANDSO C
Solar/Wind Harmer
0.512
20715228NPK_W1-113
Solar/Wind Harmer
0.476
20720528MAN_W1-024
Solar/Wind Harmer
0.282
219919AE1-041 FULL
Solar/Wind Harmer
0.045
217121ECCF
Adder
0.479
20676728BRNX1-095
Solar/Wind Harmer
0.194
20676328BVR_Y1-020
Solar/Wind Harmer
0.363
20674928WA_W3-044
Solar/Wind Harmer
0.528
971519AH1-257 GEN
Solar/Wind Harmer
2.765
207518AF1-320_GEN
Solar/Wind Harmer
4.008
20465127PORT CT
Adder
3.288
209018SUNBIPCT
Adder
7.415
20465527S.RDG CT
Adder
2.747
209137AF2-361 C
Solar/Wind Harmer
2.578
941421AE2-139 GEN
Solar/Wind Harmer
2.753
316044AC1-158 PL1
Solar/Wind Helper
1.668
3147666LOUISA
Solar/Wind Helper
1.163
238152AF2-075_GEN
Solar/Wind Helper
0.706
316404AE1-155 C
Solar/Wind Helper
2.412
3138133OCRAN
Solar/Wind Helper
0.168
315662AE1-191 GEN
Solar/Wind Helper
1.508
316280AD1-041 GEN
Solar/Wind Helper
0.942
3143226MDLTHAN
Solar/Wind Helper
0.279
3142543TWELFTH
Solar/Wind Helper
0.027
316369SG1_INVT
Solar/Wind Helper
1.333
316381AD1-082 GEN
Solar/Wind Helper
1.423
319010AE1-072 C
Solar/Wind Helper
3.121
23777901MDS_W4-102
Solar/Wind Helper
0.171
315611Z1-036_GEN2
Solar/Wind Helper
1.479
3130156CHOWAN
Solar/Wind Helper
0.268
315816AE2-034 GEN
Solar/Wind Helper
1.221
315737AD1-076 GEN
Solar/Wind Helper
2.594
3146926FARMVIL
Solar/Wind Helper
0.159
316087AB2-174 GEN
Solar/Wind Helper
1.837
315785AD2-033 C
Solar/Wind Helper
3.028
3146233WITAKRS
Solar/Wind Helper
1.012
270018AE2-047 C O1
Solar/Wind Helper
0.795
200201DELTA2 CT2
50/50
3.915
232899W1-062
Adder
12.612
232410W1-006 C
Solar/Wind Harmer
1.311
233946AB2-136 GEN
Solar/Wind Harmer
5.221
233952AC2-187 GEN
Solar/Wind Harmer
1.472
233954AC2-188 GEN
Solar/Wind Harmer
1.472
233984AB2-036 GEN
Solar/Wind Harmer
16.216
233930AB2-032 GEN
Solar/Wind Harmer
1.078
233982AB2-133 GEN
Solar/Wind Harmer
6.3
230511AF1-262
Solar/Wind Harmer
0.21
228754AB1-001 C
Solar/Wind Harmer
0.16
228307PCLP GT
Adder
13.868
219272CLEANLIGHT C
Solar/Wind Harmer
0.207
213587EDDYSTN3
Adder
90.117
217081WEATEXAS C
Solar/Wind Harmer
0.095
217083KRNY_132
Adder
10.179
207471AF2-354 C
Solar/Wind Harmer
0.561
20675928HOL_W4-097
Solar/Wind Harmer
0.143
961541AF2-445A GEN
Solar/Wind Harmer
3.372
209010PEIP 1
Adder
3.68
209010PEIP 1
Adder
0.539
961431AF2-434 GEN
Solar/Wind Harmer
1.018
209130AF1-271A GEN
Solar/Wind Harmer
2.799
316411AF1-147_GEN1
Solar/Wind Helper
1.095
237061AD1-155 GEN
Solar/Wind Helper
1.767
316312AB1-027
Solar/Wind Helper
0.536
3143526WINTERP
Solar/Wind Helper
1.454
316185AD1-033 GEN
Solar/Wind Helper
1.29
235020AA1-095 C
Solar/Wind Helper
0.051
3144356SAPONY
Solar/Wind Helper
0.484
316315AB2-025 C
Solar/Wind Helper
0.413
3145796HORNRTN
Solar/Wind Helper
0.779
316237AB2-079_GEN
Solar/Wind Helper
0.347
315687AD1-152 GEN
Solar/Wind Helper
1.381
238221AF1-254 C O1
Solar/Wind Helper
0.249
316248AF1-058 C
Solar/Wind Helper
0.338
270013AE1-250 PV
Solar/Wind Helper
0.85
231920CHRIST2
Adder
5.484
230422AE1-104_GEN1
Solar/Wind Harmer
38.785
230425AE1-104_GEN2
Solar/Wind Harmer
38.785
230430AE1-229_GEN
Solar/Wind Harmer
32.935
230407AD2-065 C
Solar/Wind Harmer
0.151
20720728JCB_W1-129
Solar/Wind Harmer
0.332
207500AE2-000G1
Solar/Wind Harmer
35.098
970025AG2-016 GEN
Solar/Wind Harmer
3.155
20714428HOW_X1-037
Solar/Wind Harmer
1.37
218449LINSOLAR C
Solar/Wind Harmer
1.11
217147KRNY_1212
Adder
9.744
217147KRNY_1212
Adder
9.57
217146KRNY_1234
Adder
9.548
217146KRNY_1234
Adder
9.483
964851AG1-348 GEN
Solar/Wind Harmer
1.499
207408W3-077 C
Solar/Wind Harmer
0.555
20462827N BANGR8
Adder
0.785
209026WIENIPP4
Adder
5.629
209054AE2-059 GEN
Solar/Wind Harmer
1.696
20486527WR_V4-052
Adder
1.072
209067AE2-060 GEN
Solar/Wind Harmer
1.335
200917MEHOOPANY_G
Solar/Wind Harmer
3.66
315651AD1-115 GEN
Solar/Wind Helper
1.012
238169AE2-226 GEN1
Solar/Wind Helper
0.724
238170AE2-226 GEN2
Solar/Wind Helper
0.724
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
316059AD1-063 C
Solar/Wind Helper
0.283
313526AB2-022
Solar/Wind Helper
0.415
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.008
3146206CASHIE
Solar/Wind Helper
0.264
961941AG1-037 GEN
Solar/Wind Helper
0.089
3146043SEABORD
Solar/Wind Helper
0.263
3145683EARLEYS
Solar/Wind Helper
0.525
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
316486AD2-202 GEN
Solar/Wind Helper
0.374
316274AC1-208 GEN
Solar/Wind Helper
1.575
3148463FAIRFLD
Solar/Wind Helper
0.252
3147173SINAI
Solar/Wind Helper
0.251
3147243WELCO
Solar/Wind Helper
0.157
270455AD2-022 GEN
Solar/Wind Helper
1.377
270197AD1-017 GEN1
Solar/Wind Helper
1.229
232912OH NUG1
Adder
11.579
971195AH1-057 GEN
Solar/Wind Harmer
1.278
233955AB2-172 GEN
Solar/Wind Harmer
6.542
232813VAUGHN
Adder
0.769
231902DC CT7
Adder
14.527
233915AB1-141 GEN
Solar/Wind Harmer
1.281
970453AG2-297 GEN
Solar/Wind Harmer
3.191
964001AG1-254 GEN
Solar/Wind Harmer
8.379
228728W1-130C
Solar/Wind Harmer
0.763
227927V4-067C
Solar/Wind Harmer
0.227
219137THOSOLAR C
Solar/Wind Harmer
1.375
219615MILLCREEK C
Solar/Wind Harmer
0.268
219224BRL12CT4
Adder
10.018
207487AE2-000G4
Solar/Wind Harmer
35.098
207497AE2-000G2
Solar/Wind Harmer
35.098
219620RIDERU C
Solar/Wind Harmer
0.062
20635928PARLN3&4
Adder
8.189
218526CNTRALGAS2 C
Solar/Wind Harmer
0.409
217167KRNY_14
Adder
10.244
971009AG2-626 GEN
Solar/Wind Harmer
1.797
961261AF2-417 GEN
Solar/Wind Harmer
1.059
212266LOR1
Solar/Wind Harmer
1.244
959431AF2-234 GEN
Solar/Wind Harmer
1.991
20334726NME_Y1-047
Adder
2.46
3138133OCRAN
Solar/Wind Helper
0.084
3143873LANEXA
Solar/Wind Helper
0.168
3141873WAN 176
Solar/Wind Helper
0.056
316382AG1-145 C
Solar/Wind Helper
0.374
316159AE1-175 C
Solar/Wind Helper
0.422
316236AE1-162_GEN
Solar/Wind Helper
0.37
3143316POE
Solar/Wind Helper
1.087
316405AF2-144 C
Solar/Wind Helper
0.314
3146486SUNBURY
Solar/Wind Helper
0.272
3146486SUNBURY
Solar/Wind Helper
0.272
3145176PASQUOTANK
Solar/Wind Helper
0.168
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
3130546PLYMOUTH
Solar/Wind Helper
0.265
315733AD1-074 GEN2
Solar/Wind Helper
3.034
946281AF1-292 GEN
Solar/Wind Helper
0.264
3148013FISHERV
Solar/Wind Helper
0.15
3146033SCOT NK
Solar/Wind Helper
1.038
315616AA1-038_C
Solar/Wind Helper
1.141
200034PCHBTM 2
50/50
22.824
200205Y1-065-CTG2
50/50
4.53
234015AF2-250 C
Solar/Wind Harmer
0.158
232428Y3-058 C
Solar/Wind Harmer
1.092
232424Y1-079 C
Solar/Wind Harmer
0.732
228251CARLLS#4
Adder
0.727
230433AD2-135 GEN
Solar/Wind Harmer
0.116
228351V2-046C
Solar/Wind Harmer
2.316
219287REEVESEAST C
Solar/Wind Harmer
1.523
213589EDDYSTN4
Adder
90.123
213535CROYDN11
Adder
11.476
214067T20SOLAR
Solar/Wind Harmer
0.282
20636128O CRK C2
Adder
7.18
207459AE1-142 C O1
Solar/Wind Harmer
1.173
20628028LAKEHURS
Adder
1.058
217197RE CRAN C
Solar/Wind Harmer
0.594
924131AB2-057 GEN
Solar/Wind Harmer
1.138
20635128RRCT3&4
Adder
12.39
20635128RRCT3&4
Adder
10.808
218419LINDEN_G6
Adder
18.967
20675428EAM_W2-061
Solar/Wind Harmer
0.208
219035LINDEN_G8
Adder
18.195
972237AH1-703 GEN
Adder
11.151
20465127PORT CT
Adder
4.364
20465527S.RDG CT
Adder
2.657
316450AC1-158 RIC
Solar/Wind Helper
0.445
966001AG1-469 GEN
Solar/Wind Helper
0.31
238148AE2-230_GEN2
Solar/Wind Helper
0.494
316487AF1-042 GEN
Solar/Wind Helper
0.284
316033AB2-134 GEN
Solar/Wind Helper
0.957
3145506HICKORY
Solar/Wind Helper
1.093
3145506HICKORY
Solar/Wind Helper
0.656
3145506HICKORY
Solar/Wind Helper
0.164
316339AD2-160 GEN
Solar/Wind Helper
1.042
316388AE2-253 GEN
Solar/Wind Helper
1.042
3137176SLIGO L2192
Solar/Wind Helper
1.085
3130086AYDLETT
Solar/Wind Helper
1.09
3146626S HERTFORD
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3132123MT JACKSON
Solar/Wind Helper
0.837
313506AB2-031 GEN
Solar/Wind Helper
1.192
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.157
3145593CAROLNA
Solar/Wind Helper
0.261
3145593CAROLNA
Solar/Wind Helper
0.261
3145933PARMELE
Solar/Wind Helper
0.516
3145933PARMELE
Solar/Wind Helper
0.258
316049AB1-081 GEN
Solar/Wind Helper
1.545
232434Z2-077 GEN
Solar/Wind Harmer
0.328
232406W1-004 FULL
Solar/Wind Harmer
1.311
233964AF2-378 GEN
Solar/Wind Harmer
0.167
232422X3-066 FULL
Solar/Wind Harmer
0.324
230415AB2-049 C
Solar/Wind Harmer
0.218
219291REEVESSOUT C
Solar/Wind Harmer
0.068
219236SOUTHERNHQ C
Solar/Wind Harmer
0.076
213815MOSER1-3
Adder
3.985
20714928UPF_X1-085
Solar/Wind Harmer
0.453
219114HARTZY_C
Solar/Wind Harmer
0.927
219918AC2-009 C
Solar/Wind Harmer
0.029
20674528F3S_W2-016
Solar/Wind Harmer
1.549
209025WIENIPP3
Adder
5.572
205941AD2-115 GEN
Solar/Wind Harmer
0.943
209142AF1-226 GEN
Solar/Wind Harmer
5.895
966881AG1-559 GEN
Solar/Wind Helper
0.39
316473AC1-191 GEN
Solar/Wind Helper
1.724
3142946ENON
Solar/Wind Helper
0.093
3145336SMITFLD
Solar/Wind Helper
0.11
316017AA1-139 ULT1
Solar/Wind Helper
1.25
3146456SLIGO L269
Solar/Wind Helper
0.273
3145273HOLLAND
Solar/Wind Helper
0.203
3146376EDENTON
Solar/Wind Helper
0.268
3146206CASHIE
Solar/Wind Helper
0.264
316095T157 G97
Solar/Wind Helper
1.213
3146173TUNIS
Solar/Wind Helper
0.263
316499AE2-029_GEN
Solar/Wind Helper
0.883
316181AB2-040 GEN
Solar/Wind Helper
1.882
3147133PAMPLIN
Solar/Wind Helper
0.821
3147043LAWRENC
Solar/Wind Helper
0.157
316478AD1-087 GEN
Solar/Wind Helper
1.276
316420AA1-050 GEN
Solar/Wind Helper
1.464
3146073TAR RVR
Solar/Wind Helper
0.254
3146083TARBORO
Solar/Wind Helper
0.254
3138543CONSLDL
Solar/Wind Helper
0.168
238109AE1-109 GEN2
Solar/Wind Helper
0.095
316003AC1-222 GEN
Solar/Wind Helper
1.082
227287AC2-120 GEN
Solar/Wind Helper
0.335
316222AC1-221 GEN
Solar/Wind Helper
1.394
316283AC2-100 C
Solar/Wind Helper
1.299
218438BLK ROCK C
Solar/Wind Harmer
0.151
972260AH1-715 GEN1
Adder
15.188
972261AH1-715 GEN2
Adder
17.669
217202FBANKSOLAR C
Solar/Wind Harmer
0.081
217201HACKENSOLA C
Solar/Wind Harmer
0.081
217206BARNGR HS C
Solar/Wind Harmer
0.034
217204WCALDSOLAR C
Solar/Wind Harmer
0.081
20674828DL_W4-046
Solar/Wind Harmer
0.708
20634528N27_Y2-018
Solar/Wind Harmer
0.295
238147AE2-230_GEN1
Solar/Wind Helper
0.494
315976AC1-164 GENA
Solar/Wind Helper
3.608
316169AC1-164_GENC
Solar/Wind Helper
3.117
3142946ENON
Solar/Wind Helper
0.028
316294AC1-161 GEN
Solar/Wind Helper
5.031
316349AD2-085 GEN
Solar/Wind Helper
1.251
3146386ELIZ CT
Solar/Wind Helper
0.272
316431W1029_GEN1
Solar/Wind Helper
1.095
316433W1029_GEN2
Solar/Wind Helper
1.095
316365GEN2_N
Solar/Wind Helper
1.009
316097T157 G90
Solar/Wind Helper
1.213
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
3147133PAMPLIN
Solar/Wind Helper
0.261
3147133PAMPLIN
Solar/Wind Helper
0.209
3146843MT LREL
Solar/Wind Helper
0.254
3146843MT LREL
Solar/Wind Helper
0.254
237080AD1-060 GEN
Solar/Wind Helper
0.299
233973AC2-185 C
Solar/Wind Harmer
7.11
970695AG2-447 GEN
Solar/Wind Harmer
4.704
233987AB2-037 GEN
Solar/Wind Harmer
14.909
233923SMA
Solar/Wind Harmer
4.79
233997TMININ_4.2
Solar/Wind Harmer
1.306
232907VN8
Adder
39.356
232417X3-008 C
Solar/Wind Harmer
1.472
233935AB2-179 C
Solar/Wind Harmer
3.185
219221BRL12CT1
Adder
10.018
219223BRL12CT3
Adder
10.018
959561AF2-247 GEN
Solar/Wind Harmer
0.542
20715728PEM_W1-119
Solar/Wind Harmer
0.595
20636028O CRK C1
Adder
7.875
971667AH1-334 GEN
Solar/Wind Harmer
3.058
219727YARDVSOLFA C
Solar/Wind Harmer
1.012
20635828PARLN1&2
Adder
3.709
219249CENTRALDIV C
Solar/Wind Harmer
0.044
207442AE1-156 GEN
Solar/Wind Harmer
0.82
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217194REDH C
Solar/Wind Harmer
0.542
207511W3-106 GEN
Solar/Wind Harmer
0.362
971007AG2-625 GEN
Solar/Wind Harmer
2.818
20674128FR_U2-059
Solar/Wind Harmer
0.202
20466127PORT 5CT
Adder
29.023
211065PSPA IPP
Solar/Wind Harmer
0.489
957921AF2-086 GEN
Solar/Wind Harmer
0.99
3132273ORANGE
Solar/Wind Helper
0.059
316223AC1-118
Solar/Wind Helper
0.436
23546401DTGZ2-030
Solar/Wind Helper
0.089
3144536CHRHLND
Solar/Wind Helper
0.041
3142956BIRDNECK
Solar/Wind Helper
0.184
316305AF2-043 C
Solar/Wind Helper
0.367
316320Y1-086
Solar/Wind Helper
0.122
3146516WINFALL
Solar/Wind Helper
0.271
3146776BUCKING
Solar/Wind Helper
0.096
315735AD1-075 GEN1
Solar/Wind Helper
1.517
3145893MURPHYS
Solar/Wind Helper
0.095
3145893MURPHYS
Solar/Wind Helper
0.264
3146263WOODLND
Solar/Wind Helper
0.262
3145963POPLR C
Solar/Wind Helper
0.261
316011AB1-132 GEN
Solar/Wind Helper
2.815
270494AE1-108_GEN
Solar/Wind Helper
3.425
3145543BTLEBRO
Solar/Wind Helper
0.253
3145543BTLEBRO
Solar/Wind Helper
0.253
237038AE2-054 C
Solar/Wind Helper
0.23
270173AC1-122 GEN
Solar/Wind Helper
1.539
232902EASTMUNI
Adder
17.017
234012AE2-112_GEN
Solar/Wind Harmer
2.987
972251AH1-710 GEN
Adder
58.042
231918WEST 1
Adder
4.263
228732V1-021 C
Adder
0.218
228400MICK 1CT
Adder
13.502
219766PARADISE C
Solar/Wind Harmer
0.356
20714528FRN_Y2-051
Solar/Wind Harmer
0.328
219680HOPEWELLV C1
Solar/Wind Harmer
0.084
218440SUMMTASSOC C
Solar/Wind Harmer
0.141
217208PARK ELE C
Solar/Wind Harmer
0.028
966261AG1-495 GEN
Solar/Wind Harmer
3.857
20674628WNG_W3-110
Solar/Wind Harmer
0.443
209023WIENIPP1
Adder
11.393
209025WIENIPP3
Adder
5.687
963071AG1-156 GEN
Solar/Wind Harmer
10.376
205967AE2-211_GEN
Solar/Wind Harmer
5.854
316447AC1-158 HLD
Solar/Wind Helper
3.67
316192AB2-158 GEN
Solar/Wind Helper
1.957
3142416OLDCHRC
Solar/Wind Helper
0.73
3142416OLDCHRC
Solar/Wind Helper
0.28
3141766HARMONY
Solar/Wind Helper
0.056
315975AC1-164 GENB
Solar/Wind Helper
0.107
3142433PROV 92
Solar/Wind Helper
1.118
3145336SMITFLD
Solar/Wind Helper
1.099
316375AC2-012 GEN
Solar/Wind Helper
0.721
3146456SLIGO L269
Solar/Wind Helper
0.273
3145663CRESWEL
Solar/Wind Helper
0.746
316023GEN1_S
Solar/Wind Helper
1.009
3146206CASHIE
Solar/Wind Helper
0.264
3146173TUNIS
Solar/Wind Helper
0.263
3156021HOLLOMANSOL
Solar/Wind Helper
2.006
3145683EARLEYS
Solar/Wind Helper
0.262
316131AB2-060 GEN
Solar/Wind Helper
1.576
3146083TARBORO
Solar/Wind Helper
0.254
238110AE1-109 GEN3
Solar/Wind Helper
0.095
316359AB2-059 GEN
Solar/Wind Helper
1.932
964991AG1-363 GEN
Solar/Wind Helper
3.514
3147123OTTER R
Solar/Wind Helper
0.139
200200DELTA2 CT1
50/50
3.915
200193DELTA CT2
50/50
2.188
200203Y1-065-STG
50/50
7.845
200055ROCKSP 4
50/50
2.833
233939AC1-091 C
Solar/Wind Harmer
3.52
232914OH NUG3
Adder
11.579
232916OH NUG5
Adder
11.579
233933AB2-153 GEN
Solar/Wind Harmer
1.455
219623KINSLEYBEA C
Solar/Wind Harmer
0.485
213958STHWK5-6
Adder
3.065
20716428NHV_W2-082
Solar/Wind Harmer
1.982
963391AG1-188 GEN
Solar/Wind Harmer
4.174
219612MATRIX C
Solar/Wind Harmer
0.203
20716928W4-060COL
Solar/Wind Harmer
0.787
217213AMBOY SO C
Solar/Wind Harmer
0.14
20673728F2S_V4-070
Solar/Wind Harmer
0.198
207510AF2-138 C
Solar/Wind Harmer
1.953
207437AD2-070 GEN
Solar/Wind Harmer
0.33
20671928W4-073
Solar/Wind Harmer
0.474
20633028GILCT9
Adder
30.976
20465427SHAW CT
Adder
4.217
209116AE2-175 GEN
Solar/Wind Harmer
4.469
970095AG2-074 GEN
Solar/Wind Harmer
6.571
961421AF2-433 GEN
Solar/Wind Harmer
1.018
209093AE2-110 GEN
Solar/Wind Harmer
2.546
209120AE2-241 GEN
Solar/Wind Harmer
3.369
946691AF1-333 GEN
Solar/Wind Harmer
0.997
946741AF1-338 GEN
Solar/Wind Harmer
0.997
972221AH1-695 GEN
Adder
124.805
3141196NOKESVL
Solar/Wind Helper
1.26
316077AC2-138 C
Solar/Wind Helper
0.267
316484AD2-074 GEN
Solar/Wind Helper
0.543
316075AC2-137 C
Solar/Wind Helper
0.427
315821AE2-092 GEN
Solar/Wind Helper
2.446
942461AE2-259 GEN
Solar/Wind Helper
1.771
966621AG1-532 GEN
Solar/Wind Helper
0.239
316317KELFORD C
Solar/Wind Helper
0.235
3145823KELFORD
Solar/Wind Helper
0.261
3145796HORNRTN
Solar/Wind Helper
1.039
3145796HORNRTN
Solar/Wind Helper
0.26
316212AC1-099_GEN
Solar/Wind Helper
1.16
23583801GRNGAP
Solar/Wind Helper
4.412
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
226910AB2-157 C
Solar/Wind Helper
0.014
316123AC1-075 GEN
Solar/Wind Helper
1.475
3147312GRETNA
Solar/Wind Helper
0.046
237085AD2-009_GEN
Solar/Wind Helper
1.363
209027LOR2_Q27
Solar/Wind Harmer
4.694
964051AG1-259 GEN
Solar/Wind Harmer
1.335
964061AG1-260 GEN
Solar/Wind Harmer
1.335
208862AG1-362 C
Solar/Wind Harmer
0.777
20390726Y2-042
Adder
2.782
3141426STAFORD
Solar/Wind Helper
0.066
316468AD1-105 GEN
Solar/Wind Helper
1.374
3141913WHIT STONE
Solar/Wind Helper
0.28
957831AF2-077 GEN
Solar/Wind Helper
0.375
315697AD1-025 GEN
Solar/Wind Helper
3.163
315839AE2-212 C
Solar/Wind Helper
0.372
316258AE1-075 C
Solar/Wind Helper
0.377
316316AC1-027 C
Solar/Wind Helper
0.433
316322AB2-045
Solar/Wind Helper
0.297
3148133STUARTS
Solar/Wind Helper
0.156
3145796HORNRTN
Solar/Wind Helper
0.831
3145796HORNRTN
Solar/Wind Helper
0.104
316210AC1-098 GEN
Solar/Wind Helper
2.088
316238AB2-078_GEN
Solar/Wind Helper
0.347
316239AB2-077_GEN
Solar/Wind Helper
0.347
3145746EVERETS
Solar/Wind Helper
1.02
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145573BETHELC
Solar/Wind Helper
0.254
3145573BETHELC
Solar/Wind Helper
0.254
200192DELTA CT1
50/50
2.188
200054ROCKSP 3
50/50
2.883
972177AH1-672 GEN
Solar/Wind Harmer
17.613
232408W1-005 C
Solar/Wind Harmer
1.311
232917OH NUG6
Adder
11.527
232915OH NUG4
Adder
11.502
233944AB2-135 GEN
Solar/Wind Harmer
6.783
219907AC1-030 C
Solar/Wind Harmer
0.156
213958STHWK5-6
Adder
3.065
20716028EGP_W2-019
Solar/Wind Harmer
0.517
207522AF2-254 C
Solar/Wind Harmer
1.6
218428ETC SOLAR C
Solar/Wind Harmer
0.04
219908AB1-139 C
Solar/Wind Harmer
0.42
972275AH1-722 GEN
Adder
34.869
20673628F1S_V4-069
Solar/Wind Harmer
0.198
207528AF2-192 GEN
Solar/Wind Harmer
1.403
217186ESSEX_G9
Adder
4.35
217083KRNY_132
Adder
10.244
20676228FRD_X1-012
Solar/Wind Harmer
0.649
20675828AU_W4-064
Solar/Wind Harmer
0.19
20675728RH_W2-091
Solar/Wind Harmer
0.661
207484AF2-139 C O1
Solar/Wind Harmer
0.554
208909MACR G3
Adder
174.223
209010PEIP 1
Adder
0.669
946731AF1-337 GEN
Solar/Wind Harmer
0.997
209008PAXT IPP
Adder
1.832
316415AF1-147_GEN2
Solar/Wind Helper
1.095
238175AF1-290_GEN
Solar/Wind Helper
0.163
964211AG1-282 GEN
Solar/Wind Helper
0.381
3143526WINTERP
Solar/Wind Helper
1.454
315671AE2-027_GEN
Solar/Wind Helper
2.237
316072AD1-144
Solar/Wind Helper
0.313
3147983MERCK5
Solar/Wind Helper
0.105
3145823KELFORD
Solar/Wind Helper
0.261
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.857
3145796HORNRTN
Solar/Wind Helper
0.26
316034AC1-036 C
Solar/Wind Helper
0.273
316129AC1-054 GEN
Solar/Wind Helper
1.282
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3147312GRETNA
Solar/Wind Helper
0.184
3146802CHATHAM
Solar/Wind Helper
0.172
270016AE1-250 BESS
Solar/Wind Helper
0.85
213611FALLS1-3
Adder
3.95
213611FALLS1-3
Adder
3.95
20715028HAN_X4-015
Solar/Wind Harmer
0.332
207507AE2-000G3
Solar/Wind Harmer
35.098
207445AB1-138_GEN
Solar/Wind Harmer
0.644
20720628TIN_W1-124
Solar/Wind Harmer
1.103
971521AH1-258 GEN
Solar/Wind Harmer
2.999
20675528CPH_W2-050
Solar/Wind Harmer
0.634
20676428JCR_X2-075
Solar/Wind Harmer
0.377
217086KRNY_131
Adder
10.157
20675128HRM_W1-127
Solar/Wind Harmer
0.186
209029WAYMART-WD
Solar/Wind Harmer
2.688
959421AF2-233 GEN
Solar/Wind Harmer
0.995
205951AE1-129_GEN
Solar/Wind Harmer
7.804
203926AA2-133 GEN
Adder
2.272
3138216PACIFIC
Solar/Wind Helper
0.054
316164AC1-076 GEN
Solar/Wind Helper
1.425
3141813NORNECK
Solar/Wind Helper
0.283
957601AF2-054 GEN
Solar/Wind Helper
0.375
316233AE1-074 FULL
Solar/Wind Helper
0.427
316018AA1-139 ULT2
Solar/Wind Helper
1.177
315800Z1-036_GEN1
Solar/Wind Helper
1.479
315732AD1-074 GEN1
Solar/Wind Helper
3.034
3145893MURPHYS
Solar/Wind Helper
0.713
3145893MURPHYS
Solar/Wind Helper
0.264
316463AE2-346 GEN
Solar/Wind Helper
0.241
3145513AHOSKIE
Solar/Wind Helper
0.118
3145513AHOSKIE
Solar/Wind Helper
0.263
3137643SOCKMAN
Solar/Wind Helper
1.044
316426AA2-053 GEN
Solar/Wind Helper
1.494
316174AB2-169 GEN
Solar/Wind Helper
0.667
3144303KENBRDG
Solar/Wind Helper
0.208
316327AA2-057 GEN
Solar/Wind Helper
1.462
226929AD2-058 GEN
Solar/Wind Helper
0.099
270457AD2-023 GEN
Solar/Wind Helper
0.908
315614AA2-178 GEN
Solar/Wind Helper
1.629
3146776BUCKING
Solar/Wind Helper
1.062
3146776BUCKING
Solar/Wind Helper
0.086
3145893MURPHYS
Solar/Wind Helper
0.379
3145893MURPHYS
Solar/Wind Helper
0.475
316140AB2-099
Solar/Wind Helper
0.1
316005AA1-067
Solar/Wind Helper
0.294
316118AC1-105 GEN
Solar/Wind Helper
0.982
G-007ALTFEXP_G-007A->PJM
CMTX
56.69
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.409
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.578
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.27
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.003
VTFLTFEXP_VFT->PJM
CMTX
149.342
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.503
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.687

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.16 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3939.34
MW Contribution:
8.45
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
4.75
200052ROCKSP 1
50/50
2.052
200053ROCKSP 2
50/50
2.012
233940AF2-379 C
Solar/Wind Harmer
0.181
200194DELTA CT3
50/50
1.567
233970AC1-092 C
Solar/Wind Harmer
2.608
233998TM1NIN_3.36
Solar/Wind Harmer
0.97
232404W1-003 C
Solar/Wind Harmer
0.973
232919VN10
Adder
2.73
232900DEMECSMY
Adder
8.973
231917EM10
Adder
2.237
970997AG2-616 GEN
Solar/Wind Harmer
8.249
213497CHSTR7-9
Adder
2.334
213497CHSTR7-9
Adder
2.334
213560DLW11-12
Adder
2.303
219222BRL12CT2
Adder
7.526
20717128DIX_Z2-102
Solar/Wind Harmer
1.105
20715828PEM_W1-120
Solar/Wind Harmer
0.447
963711AG1-223 GEN
Solar/Wind Harmer
1.236
219276PARKLANDSO C
Solar/Wind Harmer
0.386
20715228NPK_W1-113
Solar/Wind Harmer
0.359
20720528MAN_W1-024
Solar/Wind Harmer
0.212
219919AE1-041 FULL
Solar/Wind Harmer
0.034
217121ECCF
Adder
0.362
20676728BRNX1-095
Solar/Wind Harmer
0.147
20676328BVR_Y1-020
Solar/Wind Harmer
0.277
20674928WA_W3-044
Solar/Wind Harmer
0.403
200034PCHBTM 2
50/50
16.353
200205Y1-065-CTG2
50/50
3.262
232428Y3-058 C
Solar/Wind Harmer
0.811
234015AF2-250 C
Solar/Wind Harmer
0.117
232424Y1-079 C
Solar/Wind Harmer
0.545
228251CARLLS#4
Adder
0.543
228351V2-046C
Solar/Wind Harmer
1.732
230433AD2-135 GEN
Solar/Wind Harmer
0.087
213589EDDYSTN4
Adder
68.158
219287REEVESEAST C
Solar/Wind Harmer
1.141
213535CROYDN11
Adder
8.623
214067T20SOLAR
Solar/Wind Harmer
0.212
20636128O CRK C2
Adder
5.392
207459AE1-142 C O1
Solar/Wind Harmer
0.882
20628028LAKEHURS
Adder
0.795
217197RE CRAN C
Solar/Wind Harmer
0.448
924131AB2-057 GEN
Solar/Wind Harmer
0.858
20635128RRCT3&4
Adder
9.351
20635128RRCT3&4
Adder
8.157
218419LINDEN_G6
Adder
14.336
20675428EAM_W2-061
Solar/Wind Harmer
0.158
219035LINDEN_G8
Adder
13.763
200204Y1-065-CTG1
50/50
3.262
233918AB1-142 GEN
Solar/Wind Harmer
0.957
228206SHRMN CT
Adder
14.293
228260V4-054C
Solar/Wind Harmer
0.884
228729W2-030 C
Solar/Wind Harmer
0.495
219686LUMSOLAR_N C
Solar/Wind Harmer
0.172
219348LDSOLAR C
Solar/Wind Harmer
0.504
213611FALLS1-3
Adder
2.97
214194N WALES4
Adder
0.716
20720428HOL_W1-112
Solar/Wind Harmer
0.289
20635828PARLN1&2
Adder
6.178
20635028RRCT1&2
Adder
9.839
218524CNTRALGAS1 C
Solar/Wind Harmer
0.308
217209CENTRL HS C
Solar/Wind Harmer
0.037
20671828STAW2-080
Solar/Wind Harmer
0.088
207439AE1-081 C O1
Solar/Wind Harmer
0.05
207530AG1-191 GEN
Solar/Wind Harmer
1.151
211065PSPA IPP
Solar/Wind Harmer
0.375
961301AF2-421 GEN
Solar/Wind Harmer
0.816
963151AG1-164 GEN
Solar/Wind Harmer
0.816
961341AF2-425 GEN
Solar/Wind Harmer
0.793
212507AE2-042_GEN
Solar/Wind Harmer
2.343
20465027TOLNA CT
Adder
2.298
316337AD2-073 GEN
Solar/Wind Helper
0.391
3141726DUNNSVL
Solar/Wind Helper
1.019
316132AB2-190 GEN1
Solar/Wind Helper
1.416
315773AC2-141 GEN
Solar/Wind Helper
5.274
316036AC1-147 C
Solar/Wind Helper
0.372
3146516WINFALL
Solar/Wind Helper
0.778
3146516WINFALL
Solar/Wind Helper
0.24
3146776BUCKING
Solar/Wind Helper
0.093
3145893MURPHYS
Solar/Wind Helper
0.929
315607AA1-063A GEN
Solar/Wind Helper
1.317
3146263WOODLND
Solar/Wind Helper
0.23
3145963POPLR C
Solar/Wind Helper
0.229
232406W1-004 FULL
Solar/Wind Harmer
0.973
232434Z2-077 GEN
Solar/Wind Harmer
0.243
233964AF2-378 GEN
Solar/Wind Harmer
0.124
232422X3-066 FULL
Solar/Wind Harmer
0.242
230415AB2-049 C
Solar/Wind Harmer
0.163
219291REEVESSOUT C
Solar/Wind Harmer
0.051
219236SOUTHERNHQ C
Solar/Wind Harmer
0.057
213815MOSER1-3
Adder
2.994
20714928UPF_X1-085
Solar/Wind Harmer
0.34
219114HARTZY_C
Solar/Wind Harmer
0.698
219918AC2-009 C
Solar/Wind Harmer
0.021
20674528F3S_W2-016
Solar/Wind Harmer
1.177
205941AD2-115 GEN
Solar/Wind Harmer
0.763
209025WIENIPP3
Adder
4.303
209142AF1-226 GEN
Solar/Wind Harmer
4.58
227287AC2-120 GEN
Solar/Wind Helper
0.415
966881AG1-559 GEN
Solar/Wind Helper
0.355
316473AC1-191 GEN
Solar/Wind Helper
1.553
3142946ENON
Solar/Wind Helper
0.083
3145336SMITFLD
Solar/Wind Helper
0.098
316017AA1-139 ULT1
Solar/Wind Helper
1.112
3146456SLIGO L269
Solar/Wind Helper
0.242
3145273HOLLAND
Solar/Wind Helper
0.179
3146376EDENTON
Solar/Wind Helper
0.237
3146206CASHIE
Solar/Wind Helper
0.232
3146173TUNIS
Solar/Wind Helper
0.231
316181AB2-040 GEN
Solar/Wind Helper
1.651
3147043LAWRENC
Solar/Wind Helper
0.137
3147133PAMPLIN
Solar/Wind Helper
0.717
316478AD1-087 GEN
Solar/Wind Helper
1.116
316499AE2-029_GEN
Solar/Wind Helper
0.757
232912OH NUG1
Adder
8.595
971195AH1-057 GEN
Solar/Wind Harmer
0.948
233955AB2-172 GEN
Solar/Wind Harmer
4.861
232813VAUGHN
Adder
0.572
231902DC CT7
Adder
10.829
233915AB1-141 GEN
Solar/Wind Harmer
0.957
970453AG2-297 GEN
Solar/Wind Harmer
2.381
964001AG1-254 GEN
Solar/Wind Harmer
6.266
228728W1-130C
Solar/Wind Harmer
0.57
227927V4-067C
Solar/Wind Harmer
0.17
219137THOSOLAR C
Solar/Wind Harmer
1.032
219615MILLCREEK C
Solar/Wind Harmer
0.201
219224BRL12CT4
Adder
7.526
207487AE2-000G4
Solar/Wind Harmer
26.357
207497AE2-000G2
Solar/Wind Harmer
26.357
219620RIDERU C
Solar/Wind Harmer
0.047
20635928PARLN3&4
Adder
6.178
218526CNTRALGAS2 C
Solar/Wind Harmer
0.309
217167KRNY_14
Adder
7.76
971009AG2-626 GEN
Solar/Wind Harmer
1.373
961261AF2-417 GEN
Solar/Wind Harmer
0.817
212266LOR1
Solar/Wind Harmer
0.965
959431AF2-234 GEN
Solar/Wind Harmer
1.553
205943AE1-185 GEN
Solar/Wind Harmer
0.574
20334726NME_Y1-047
Adder
2.076
3138133OCRAN
Solar/Wind Helper
0.076
3141873WAN 176
Solar/Wind Helper
0.05
3143873LANEXA
Solar/Wind Helper
0.151
316382AG1-145 C
Solar/Wind Helper
0.335
316159AE1-175 C
Solar/Wind Helper
0.377
316236AE1-162_GEN
Solar/Wind Helper
0.33
3143316POE
Solar/Wind Helper
0.969
316405AF2-144 C
Solar/Wind Helper
0.279
3146486SUNBURY
Solar/Wind Helper
0.241
3146486SUNBURY
Solar/Wind Helper
0.241
3145176PASQUOTANK
Solar/Wind Helper
0.149
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3130546PLYMOUTH
Solar/Wind Helper
0.234
315733AD1-074 GEN2
Solar/Wind Helper
2.672
946281AF1-292 GEN
Solar/Wind Helper
0.232
3146033SCOT NK
Solar/Wind Helper
0.908
3148013FISHERV
Solar/Wind Helper
0.129
233987AB2-037 GEN
Solar/Wind Harmer
11.072
233973AC2-185 C
Solar/Wind Harmer
5.27
970695AG2-447 GEN
Solar/Wind Harmer
3.486
233923SMA
Solar/Wind Harmer
3.556
233997TMININ_4.2
Solar/Wind Harmer
0.97
232907VN8
Adder
29.221
232417X3-008 C
Solar/Wind Harmer
1.094
233935AB2-179 C
Solar/Wind Harmer
2.395
219221BRL12CT1
Adder
7.526
219223BRL12CT3
Adder
7.526
959561AF2-247 GEN
Solar/Wind Harmer
0.407
20715728PEM_W1-119
Solar/Wind Harmer
0.447
20636028O CRK C1
Adder
5.914
971667AH1-334 GEN
Solar/Wind Harmer
2.298
219727YARDVSOLFA C
Solar/Wind Harmer
0.761
20635828PARLN1&2
Adder
2.798
219249CENTRALDIV C
Solar/Wind Harmer
0.033
207442AE1-156 GEN
Solar/Wind Harmer
0.621
217211CAMDEN ST C
Solar/Wind Harmer
0.02
217194REDH C
Solar/Wind Harmer
0.411
207511W3-106 GEN
Solar/Wind Harmer
0.276
971007AG2-625 GEN
Solar/Wind Harmer
2.153
20674128FR_U2-059
Solar/Wind Harmer
0.154
20466127PORT 5CT
Adder
22.184
211065PSPA IPP
Solar/Wind Harmer
0.375
957921AF2-086 GEN
Solar/Wind Harmer
0.769
3132273ORANGE
Solar/Wind Helper
0.052
316223AC1-118
Solar/Wind Helper
0.396
3144536CHRHLND
Solar/Wind Helper
0.037
3142956BIRDNECK
Solar/Wind Helper
0.164
23546401DTGZ2-030
Solar/Wind Helper
0.076
316305AF2-043 C
Solar/Wind Helper
0.327
316320Y1-086
Solar/Wind Helper
0.108
3146516WINFALL
Solar/Wind Helper
0.24
315735AD1-075 GEN1
Solar/Wind Helper
1.336
3146776BUCKING
Solar/Wind Helper
0.084
3145893MURPHYS
Solar/Wind Helper
0.083
3145893MURPHYS
Solar/Wind Helper
0.232
3146263WOODLND
Solar/Wind Helper
0.23
3145963POPLR C
Solar/Wind Helper
0.229
316011AB1-132 GEN
Solar/Wind Helper
2.467
200195DELTA ST
50/50
2.421
233901CHERRYDALE C
Solar/Wind Harmer
1.094
232913OH NUG2
Adder
8.48
232920IR10
Adder
3.075
970597AG2-380 GEN
Solar/Wind Harmer
4.033
231906DC3 NUG
Adder
13.546
231907DC10
Adder
3.382
972141AH1-641 GEN
Solar/Wind Harmer
2.475
213611FALLS1-3
Adder
2.97
213611FALLS1-3
Adder
2.97
20715028HAN_X4-015
Solar/Wind Harmer
0.25
207507AE2-000G3
Solar/Wind Harmer
26.357
207445AB1-138_GEN
Solar/Wind Harmer
0.484
20720628TIN_W1-124
Solar/Wind Harmer
0.831
971521AH1-258 GEN
Solar/Wind Harmer
2.259
20675528CPH_W2-050
Solar/Wind Harmer
0.479
20676428JCR_X2-075
Solar/Wind Harmer
0.285
217086KRNY_131
Adder
7.694
20675128HRM_W1-127
Solar/Wind Harmer
0.143
209029WAYMART-WD
Solar/Wind Harmer
2.083
959421AF2-233 GEN
Solar/Wind Harmer
0.777
209030FRFA O01
Adder
0.192
205951AE1-129_GEN
Solar/Wind Harmer
8.48
205956AE1-196_GEN
Solar/Wind Harmer
0.58
20465027TOLNA CT
Adder
2.389
226929AD2-058 GEN
Solar/Wind Helper
0.119
3138216PACIFIC
Solar/Wind Helper
0.049
316164AC1-076 GEN
Solar/Wind Helper
1.284
3141813NORNECK
Solar/Wind Helper
0.255
957601AF2-054 GEN
Solar/Wind Helper
0.337
316233AE1-074 FULL
Solar/Wind Helper
0.382
316018AA1-139 ULT2
Solar/Wind Helper
1.046
315800Z1-036_GEN1
Solar/Wind Helper
1.309
315732AD1-074 GEN1
Solar/Wind Helper
2.672
3145893MURPHYS
Solar/Wind Helper
0.627
3145893MURPHYS
Solar/Wind Helper
0.232
316463AE2-346 GEN
Solar/Wind Helper
0.212
3145513AHOSKIE
Solar/Wind Helper
0.104
3145513AHOSKIE
Solar/Wind Helper
0.231
3137643SOCKMAN
Solar/Wind Helper
0.915
316426AA2-053 GEN
Solar/Wind Helper
1.309
316174AB2-169 GEN
Solar/Wind Helper
0.584
3144303KENBRDG
Solar/Wind Helper
0.181
232904IR4
Adder
78.673
232432Z2-076 GEN
Solar/Wind Harmer
0.128
233968AD2-076_GEN
Solar/Wind Harmer
6.422
231919CHRIST1
Adder
4.207
231920CHRIST2
Adder
4.114
230430AE1-229_GEN
Solar/Wind Harmer
24.623
230422AE1-104_GEN1
Solar/Wind Harmer
28.972
230425AE1-104_GEN2
Solar/Wind Harmer
28.972
230407AD2-065 C
Solar/Wind Harmer
0.113
20720728JCB_W1-129
Solar/Wind Harmer
0.25
207500AE2-000G1
Solar/Wind Harmer
26.357
970025AG2-016 GEN
Solar/Wind Harmer
2.37
20714428HOW_X1-037
Solar/Wind Harmer
1.031
218449LINSOLAR C
Solar/Wind Harmer
0.84
217147KRNY_1212
Adder
7.381
217147KRNY_1212
Adder
7.249
217146KRNY_1234
Adder
7.232
217146KRNY_1234
Adder
7.183
964851AG1-348 GEN
Solar/Wind Harmer
1.145
207408W3-077 C
Solar/Wind Harmer
0.425
20462827N BANGR8
Adder
0.6
209026WIENIPP4
Adder
4.347
20486527WR_V4-052
Adder
0.887
209054AE2-059 GEN
Solar/Wind Harmer
1.322
209067AE2-060 GEN
Solar/Wind Harmer
1.124
200917MEHOOPANY_G
Solar/Wind Harmer
3.089
315651AD1-115 GEN
Solar/Wind Helper
0.909
3141783LANCAST
Solar/Wind Helper
0.151
3141783LANCAST
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.254
238169AE2-226 GEN1
Solar/Wind Helper
0.612
238170AE2-226 GEN2
Solar/Wind Helper
0.612
313526AB2-022
Solar/Wind Helper
0.369
3146206CASHIE
Solar/Wind Helper
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
961941AG1-037 GEN
Solar/Wind Helper
0.078
3146043SEABORD
Solar/Wind Helper
0.231
3145683EARLEYS
Solar/Wind Helper
0.461
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.23
316486AD2-202 GEN
Solar/Wind Helper
0.327
316274AC1-208 GEN
Solar/Wind Helper
1.374
232901NORTHST
Adder
8.101
234033AF1-007_GEN
Solar/Wind Harmer
36.192
233996TM1833_GEN
Solar/Wind Harmer
0.97
232426Y1-080 FULL
Solar/Wind Harmer
0.186
232902EASTMUNI
Adder
12.659
234012AE2-112_GEN
Solar/Wind Harmer
2.228
972251AH1-710 GEN
Adder
42.982
231918WEST 1
Adder
3.199
228732V1-021 C
Adder
0.163
228400MICK 1CT
Adder
10.117
219766PARADISE C
Solar/Wind Harmer
0.267
20714528FRN_Y2-051
Solar/Wind Harmer
0.246
219680HOPEWELLV C1
Solar/Wind Harmer
0.063
218440SUMMTASSOC C
Solar/Wind Harmer
0.107
217208PARK ELE C
Solar/Wind Harmer
0.021
966261AG1-495 GEN
Solar/Wind Harmer
2.938
20674628WNG_W3-110
Solar/Wind Harmer
0.337
209023WIENIPP1
Adder
8.797
209025WIENIPP3
Adder
4.391
963071AG1-156 GEN
Solar/Wind Harmer
8.021
205967AE2-211_GEN
Solar/Wind Harmer
6.196
205932AD2-116_GEN
Solar/Wind Harmer
0.58
316447AC1-158 HLD
Solar/Wind Helper
3.315
316192AB2-158 GEN
Solar/Wind Helper
1.757
3142416OLDCHRC
Solar/Wind Helper
0.656
3142416OLDCHRC
Solar/Wind Helper
0.251
3141766HARMONY
Solar/Wind Helper
0.05
315975AC1-164 GENB
Solar/Wind Helper
0.096
3142433PROV 92
Solar/Wind Helper
1.003
3145336SMITFLD
Solar/Wind Helper
0.979
316375AC2-012 GEN
Solar/Wind Helper
0.642
3146456SLIGO L269
Solar/Wind Helper
0.242
3145663CRESWEL
Solar/Wind Helper
0.659
316023GEN1_S
Solar/Wind Helper
0.888
3146206CASHIE
Solar/Wind Helper
0.232
3146173TUNIS
Solar/Wind Helper
0.231
3156021HOLLOMANSOL
Solar/Wind Helper
1.763
3145683EARLEYS
Solar/Wind Helper
0.23
316131AB2-060 GEN
Solar/Wind Helper
1.373
972281AH1-725 GEN
50/50
137.759
200201DELTA2 CT2
50/50
2.805
232410W1-006 C
Solar/Wind Harmer
0.973
232899W1-062
Adder
9.354
233946AB2-136 GEN
Solar/Wind Harmer
3.878
233952AC2-187 GEN
Solar/Wind Harmer
1.093
233954AC2-188 GEN
Solar/Wind Harmer
1.093
233984AB2-036 GEN
Solar/Wind Harmer
12.079
233930AB2-032 GEN
Solar/Wind Harmer
0.805
233982AB2-133 GEN
Solar/Wind Harmer
4.706
230511AF1-262
Solar/Wind Harmer
0.157
228307PCLP GT
Adder
10.382
228754AB1-001 C
Solar/Wind Harmer
0.119
213587EDDYSTN3
Adder
68.152
219272CLEANLIGHT C
Solar/Wind Harmer
0.155
217081WEATEXAS C
Solar/Wind Harmer
0.072
217083KRNY_132
Adder
7.71
207471AF2-354 C
Solar/Wind Harmer
0.429
20675928HOL_W4-097
Solar/Wind Harmer
0.11
961541AF2-445A GEN
Solar/Wind Harmer
2.616
209010PEIP 1
Adder
2.851
209010PEIP 1
Adder
0.418
961431AF2-434 GEN
Solar/Wind Harmer
0.791
209130AF1-271A GEN
Solar/Wind Harmer
2.183
20464827MOUNT CT
Adder
1.958
20464827MOUNT CT
Adder
1.9
316411AF1-147_GEN1
Solar/Wind Helper
0.98
316312AB1-027
Solar/Wind Helper
0.481
3143526WINTERP
Solar/Wind Helper
1.301
230434AG1-499 GEN
Solar/Wind Harmer
0.497
219258KINSLEYDEP C
Solar/Wind Harmer
0.275
213942SCHUYLKILL
Adder
3.027
213942SCHUYLKILL
Adder
2.315
213957STHWK3-4
Adder
2.314
213957STHWK3-4
Adder
2.314
213561DLWR9-10
Adder
3.011
213561DLWR9-10
Adder
2.303
219610FLORENCE C
Solar/Wind Harmer
1.168
963401AG1-189 GEN
Solar/Wind Harmer
1.902
971189AH1-054 GEN
Solar/Wind Harmer
0.987
20716228APLW2-078
Solar/Wind Harmer
0.737
20673828FLE_V3-070
Solar/Wind Harmer
0.389
20676128MHD_W3-029
Solar/Wind Harmer
0.399
208862AG1-362 C
Solar/Wind Harmer
0.661
209027LOR2_Q27
Solar/Wind Harmer
3.641
964051AG1-259 GEN
Solar/Wind Harmer
1.041
964061AG1-260 GEN
Solar/Wind Harmer
1.041
20390726Y2-042
Adder
2.289
20464627HAM CT
Adder
1.901
3141426STAFORD
Solar/Wind Helper
0.062
316468AD1-105 GEN
Solar/Wind Helper
1.246
3141913WHIT STONE
Solar/Wind Helper
0.252
957831AF2-077 GEN
Solar/Wind Helper
0.336
315697AD1-025 GEN
Solar/Wind Helper
2.824
315839AE2-212 C
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.335
971519AH1-257 GEN
Solar/Wind Harmer
2.114
207518AF1-320_GEN
Solar/Wind Harmer
3.066
20465127PORT CT
Adder
2.514
20465527S.RDG CT
Adder
2.276
209018SUNBIPCT
Adder
5.784
209137AF2-361 C
Solar/Wind Harmer
2.171
208835TUHI V3-051
Solar/Wind Harmer
0.044
208923BUSO V4-027
Solar/Wind Harmer
0.248
316044AC1-158 PL1
Solar/Wind Helper
1.506
3147666LOUISA
Solar/Wind Helper
1.044
316404AE1-155 C
Solar/Wind Helper
2.174
3138133OCRAN
Solar/Wind Helper
0.151
315662AE1-191 GEN
Solar/Wind Helper
1.354
316280AD1-041 GEN
Solar/Wind Helper
0.846
3142543TWELFTH
Solar/Wind Helper
0.024
3143226MDLTHAN
Solar/Wind Helper
0.25
316369SG1_INVT
Solar/Wind Helper
1.191
238152AF2-075_GEN
Solar/Wind Helper
0.603
316381AD1-082 GEN
Solar/Wind Helper
1.267
319010AE1-072 C
Solar/Wind Helper
2.775
315611Z1-036_GEN2
Solar/Wind Helper
1.309
3130156CHOWAN
Solar/Wind Helper
0.237
315816AE2-034 GEN
Solar/Wind Helper
1.078
315737AD1-076 GEN
Solar/Wind Helper
2.285
3146926FARMVIL
Solar/Wind Helper
0.139
316087AB2-174 GEN
Solar/Wind Helper
1.612
315785AD2-033 C
Solar/Wind Helper
2.641
200035PCHBTM 3
50/50
16.218
233971AC1-093 C
Solar/Wind Harmer
2.477
232918OH NUG7
Adder
8.537
232905CHERITON_25
Adder
2.387
233994AC2-023 GEN
Solar/Wind Harmer
2.612
234036AF2-325 C
Solar/Wind Harmer
0.891
232910NRG_G1
Adder
8.38
234014AF1-036_GEN
Solar/Wind Harmer
2.621
232436AB1-176 C
Solar/Wind Harmer
0.222
972233AH1-701 GEN
Adder
3.596
219912AD2-042 GEN
Solar/Wind Harmer
0.675
219607WPEMNERT C
Solar/Wind Harmer
0.353
219304NAMERICA C
Solar/Wind Harmer
0.262
20635028RRCT1&2
Adder
9.687
218418LINDEN_G5
Adder
14.336
219036LINDEN_G7
Adder
13.962
217086KRNY_131
Adder
7.776
20674328GAR_V4-001
Solar/Wind Harmer
0.092
946751AF1-339 GEN
Solar/Wind Harmer
0.778
316006AB2-029 C
Solar/Wind Helper
0.132
316045AC1-158 PL2
Solar/Wind Helper
4.82
966871AG1-558 GEN
Solar/Wind Helper
0.343
316156AD2-030 GEN
Solar/Wind Helper
0.38
315666AE1-190 GEN
Solar/Wind Helper
0.338
316240AF1-291 C
Solar/Wind Helper
0.334
238149AF1-291A_GEN
Solar/Wind Helper
0.121
316313AB2-026
Solar/Wind Helper
0.372
316435W1029_GEN3
Solar/Wind Helper
0.972
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
315614AA2-178 GEN
Solar/Wind Helper
1.437
3146776BUCKING
Solar/Wind Helper
0.93
3146776BUCKING
Solar/Wind Helper
0.075
3145893MURPHYS
Solar/Wind Helper
0.333
3145893MURPHYS
Solar/Wind Helper
0.418
316140AB2-099
Solar/Wind Helper
0.088
316005AA1-067
Solar/Wind Helper
0.256
232926CRISFLD1
Adder
1.91
231940T-011
Adder
0.726
234041AC1-190 GEN
Solar/Wind Harmer
8.709
228201CARL#2CT
Adder
5.92
228200CARL#1CT
Adder
5.63
219904AC1-010 C
Solar/Wind Harmer
0.321
219906AC1-017 C
Solar/Wind Harmer
0.188
213815MOSER1-3
Adder
2.994
213815MOSER1-3
Adder
2.994
20720828JCB_W4-025
Solar/Wind Harmer
0.379
20714828MDF_W3-079
Solar/Wind Harmer
0.255
219817TRENTONSOL C
Solar/Wind Harmer
0.921
20641628MLH_W1-032
Solar/Wind Harmer
0.245
20742028HF_AC1-207
Solar/Wind Harmer
0.654
218438BLK ROCK C
Solar/Wind Harmer
0.114
972260AH1-715 GEN1
Adder
11.48
972261AH1-715 GEN2
Adder
13.365
217202FBANKSOLAR C
Solar/Wind Harmer
0.061
217201HACKENSOLA C
Solar/Wind Harmer
0.061
217206BARNGR HS C
Solar/Wind Harmer
0.026
217204WCALDSOLAR C
Solar/Wind Harmer
0.061
20674828DL_W4-046
Solar/Wind Harmer
0.541
20634528N27_Y2-018
Solar/Wind Harmer
0.225
315976AC1-164 GENA
Solar/Wind Helper
3.236
316169AC1-164_GENC
Solar/Wind Helper
2.795
3142946ENON
Solar/Wind Helper
0.025
316294AC1-161 GEN
Solar/Wind Helper
4.482
238147AE2-230_GEN1
Solar/Wind Helper
0.422
316349AD2-085 GEN
Solar/Wind Helper
1.112
3146386ELIZ CT
Solar/Wind Helper
0.241
316431W1029_GEN1
Solar/Wind Helper
0.972
316433W1029_GEN2
Solar/Wind Helper
0.972
316365GEN2_N
Solar/Wind Helper
0.888
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3147133PAMPLIN
Solar/Wind Helper
0.228
3147133PAMPLIN
Solar/Wind Helper
0.183
316316AC1-027 C
Solar/Wind Helper
0.385
316322AB2-045
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.728
3145796HORNRTN
Solar/Wind Helper
0.091
316210AC1-098 GEN
Solar/Wind Helper
1.823
316238AB2-078_GEN
Solar/Wind Helper
0.302
316239AB2-077_GEN
Solar/Wind Helper
0.302
3148133STUARTS
Solar/Wind Helper
0.134
3145746EVERETS
Solar/Wind Helper
0.888
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
200192DELTA CT1
50/50
1.567
200054ROCKSP 3
50/50
2.076
232408W1-005 C
Solar/Wind Harmer
0.973
232917OH NUG6
Adder
8.556
232915OH NUG4
Adder
8.537
972177AH1-672 GEN
Solar/Wind Harmer
13.07
233944AB2-135 GEN
Solar/Wind Harmer
5.063
213958STHWK5-6
Adder
2.314
219907AC1-030 C
Solar/Wind Harmer
0.118
20716028EGP_W2-019
Solar/Wind Harmer
0.388
207522AF2-254 C
Solar/Wind Harmer
1.202
218428ETC SOLAR C
Solar/Wind Harmer
0.03
219908AB1-139 C
Solar/Wind Harmer
0.318
972275AH1-722 GEN
Adder
26.355
20673628F1S_V4-069
Solar/Wind Harmer
0.15
207528AF2-192 GEN
Solar/Wind Harmer
1.062
217186ESSEX_G9
Adder
3.295
217083KRNY_132
Adder
7.76
20676228FRD_X1-012
Solar/Wind Harmer
0.494
20675828AU_W4-064
Solar/Wind Harmer
0.145
20675728RH_W2-091
Solar/Wind Harmer
0.506
207484AF2-139 C O1
Solar/Wind Harmer
0.424
208909MACR G3
Adder
133.375
209010PEIP 1
Adder
0.518
946731AF1-337 GEN
Solar/Wind Harmer
0.778
209008PAXT IPP
Adder
1.603
316415AF1-147_GEN2
Solar/Wind Helper
0.98
964211AG1-282 GEN
Solar/Wind Helper
0.343
238175AF1-290_GEN
Solar/Wind Helper
0.137
3143526WINTERP
Solar/Wind Helper
1.301
315671AE2-027_GEN
Solar/Wind Helper
1.998
316072AD1-144
Solar/Wind Helper
0.279
3145823KELFORD
Solar/Wind Helper
0.229
3145783HORNRTN
Solar/Wind Helper
0.228
3145796HORNRTN
Solar/Wind Helper
0.75
3145796HORNRTN
Solar/Wind Helper
0.227
316034AC1-036 C
Solar/Wind Helper
0.238
3147983MERCK5
Solar/Wind Helper
0.09
316129AC1-054 GEN
Solar/Wind Helper
1.119
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
316185AD1-033 GEN
Solar/Wind Helper
1.148
237061AD1-155 GEN
Solar/Wind Helper
1.514
3144356SAPONY
Solar/Wind Helper
0.429
316315AB2-025 C
Solar/Wind Helper
0.366
3145796HORNRTN
Solar/Wind Helper
0.682
316237AB2-079_GEN
Solar/Wind Helper
0.302
315687AD1-152 GEN
Solar/Wind Helper
1.202
200200DELTA2 CT1
50/50
2.805
200193DELTA CT2
50/50
1.567
200203Y1-065-STG
50/50
5.649
200055ROCKSP 4
50/50
2.04
233939AC1-091 C
Solar/Wind Harmer
2.608
232914OH NUG3
Adder
8.595
232916OH NUG5
Adder
8.595
233933AB2-153 GEN
Solar/Wind Harmer
1.087
219623KINSLEYBEA C
Solar/Wind Harmer
0.364
213958STHWK5-6
Adder
2.314
20716428NHV_W2-082
Solar/Wind Harmer
1.489
963391AG1-188 GEN
Solar/Wind Harmer
3.136
219612MATRIX C
Solar/Wind Harmer
0.153
20716928W4-060COL
Solar/Wind Harmer
0.593
217213AMBOY SO C
Solar/Wind Harmer
0.106
20673728F2S_V4-070
Solar/Wind Harmer
0.15
207510AF2-138 C
Solar/Wind Harmer
1.488
207437AD2-070 GEN
Solar/Wind Harmer
0.253
20671928W4-073
Solar/Wind Harmer
0.363
20633028GILCT9
Adder
23.779
20465427SHAW CT
Adder
3.226
209116AE2-175 GEN
Solar/Wind Harmer
3.423
970095AG2-074 GEN
Solar/Wind Harmer
5.08
961421AF2-433 GEN
Solar/Wind Harmer
0.791
209093AE2-110 GEN
Solar/Wind Harmer
1.978
209120AE2-241 GEN
Solar/Wind Harmer
2.617
946691AF1-333 GEN
Solar/Wind Harmer
0.778
946741AF1-338 GEN
Solar/Wind Harmer
0.778
972221AH1-695 GEN
Adder
108.793
226910AB2-157 C
Solar/Wind Helper
0.017
3141196NOKESVL
Solar/Wind Helper
1.133
316077AC2-138 C
Solar/Wind Helper
0.241
316484AD2-074 GEN
Solar/Wind Helper
0.489
316075AC2-137 C
Solar/Wind Helper
0.384
966621AG1-532 GEN
Solar/Wind Helper
0.21
942461AE2-259 GEN
Solar/Wind Helper
1.549
316317KELFORD C
Solar/Wind Helper
0.206
3145823KELFORD
Solar/Wind Helper
0.229
315821AE2-092 GEN
Solar/Wind Helper
2.125
3145796HORNRTN
Solar/Wind Helper
0.909
3145796HORNRTN
Solar/Wind Helper
0.227
316212AC1-099_GEN
Solar/Wind Helper
1.013
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
972237AH1-703 GEN
Adder
8.446
20465127PORT CT
Adder
3.337
20465527S.RDG CT
Adder
2.202
316450AC1-158 RIC
Solar/Wind Helper
0.402
966001AG1-469 GEN
Solar/Wind Helper
0.277
316487AF1-042 GEN
Solar/Wind Helper
0.256
316033AB2-134 GEN
Solar/Wind Helper
0.855
238148AE2-230_GEN2
Solar/Wind Helper
0.422
3145506HICKORY
Solar/Wind Helper
0.972
3145506HICKORY
Solar/Wind Helper
0.583
3145506HICKORY
Solar/Wind Helper
0.146
316339AD2-160 GEN
Solar/Wind Helper
0.927
316388AE2-253 GEN
Solar/Wind Helper
0.927
3137176SLIGO L2192
Solar/Wind Helper
0.965
3130086AYDLETT
Solar/Wind Helper
0.969
3146626S HERTFORD
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
313506AB2-031 GEN
Solar/Wind Helper
1.045
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.137
3132123MT JACKSON
Solar/Wind Helper
0.716
3145593CAROLNA
Solar/Wind Helper
0.228
3145593CAROLNA
Solar/Wind Helper
0.228
3145933PARMELE
Solar/Wind Helper
0.45
3145933PARMELE
Solar/Wind Helper
0.225
233972AC1-094 C
Solar/Wind Harmer
2.095
232921TASLEY2G
Adder
5.023
233950AC2-186 GEN
Solar/Wind Harmer
0.547
228711V2-041C
Solar/Wind Harmer
0.518
213497CHSTR7-9
Adder
2.334
219921AF1-264
Solar/Wind Harmer
0.123
218660EHAMPSOLAR C
Solar/Wind Harmer
0.148
219914AD2-027 C
Solar/Wind Harmer
0.509
219688LUMSOLAR_S C
Solar/Wind Harmer
0.172
213560DLW11-12
Adder
2.303
207454AA2-184 E
Solar/Wind Harmer
0.834
20635928PARLN3&4
Adder
2.798
217169METRODIV C
Solar/Wind Harmer
0.033
963161AG1-165 GEN
Solar/Wind Harmer
0.816
208972BECR K09
Solar/Wind Harmer
0.854
961331AF2-424 GEN
Solar/Wind Harmer
0.793
209071AE2-133 GEN
Solar/Wind Harmer
1.314
208835TUHI V3-051
Solar/Wind Harmer
0.044
3147666LOUISA
Solar/Wind Helper
0.6
3141906WESTMOR
Solar/Wind Helper
0.104
316458AB2-190 GEN2
Solar/Wind Helper
1.416
3144873MCLAUGH
Solar/Wind Helper
0.006
316246AF1-032 C
Solar/Wind Helper
0.278
316321Z2-027
Solar/Wind Helper
0.368
3146626S HERTFORD
Solar/Wind Helper
0.239
3146926FARMVIL
Solar/Wind Helper
0.139
3142666NORTHAMPTON
Solar/Wind Helper
0.229
316190AA2-174 GEN
Solar/Wind Helper
0.015
3145933PARMELE
Solar/Wind Helper
0.225
3148013FISHERV
Solar/Wind Helper
0.224
G-007ALTFEXP_G-007A->PJM
CMTX
42.787
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.935
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.489
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.882
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.043
VTFLTFEXP_VFT->PJM
CMTX
113.065
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.9
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.7

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.99 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3624.44
MW Contribution:
8.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232912OH NUG1
Adder
8.575
971195AH1-057 GEN
Solar/Wind Harmer
0.607
232813VAUGHN
Adder
0.57
231902DC CT7
Adder
10.805
233915AB1-141 GEN
Solar/Wind Harmer
0.246
970453AG2-297 GEN
Solar/Wind Harmer
2.193
964001AG1-254 GEN
Solar/Wind Harmer
4.839
219224BRL12CT4
Adder
7.507
207487AE2-000G4
Solar/Wind Harmer
10.554
207497AE2-000G2
Solar/Wind Harmer
10.554
20635928PARLN3&4
Adder
6.162
218526CNTRALGAS2 C
Solar/Wind Harmer
0.637
217167KRNY_14
Adder
7.739
971009AG2-626 GEN
Solar/Wind Harmer
0.885
205943AE1-185 GEN
Solar/Wind Harmer
0.024
20334726NME_Y1-047
Adder
2.07
232904IR4
Adder
78.494
232432Z2-076 GEN
Solar/Wind Harmer
0.013
233968AD2-076_GEN
Solar/Wind Harmer
2.247
231919CHRIST1
Adder
4.197
231920CHRIST2
Adder
4.104
230430AE1-229_GEN
Solar/Wind Harmer
17.026
230422AE1-104_GEN1
Solar/Wind Harmer
11.603
200200DELTA2 CT1
50/50
2.799
200193DELTA CT2
50/50
1.564
200203Y1-065-STG
50/50
5.638
200055ROCKSP 4
50/50
2.036
233939AC1-091 C
Solar/Wind Harmer
1.751
232914OH NUG3
Adder
8.575
232916OH NUG5
Adder
8.575
213958STHWK5-6
Adder
2.308
963391AG1-188 GEN
Solar/Wind Harmer
1.527
207437AD2-070 GEN
Solar/Wind Harmer
0.055
20633028GILCT9
Adder
23.712
20465427SHAW CT
Adder
3.217
970095AG2-074 GEN
Solar/Wind Harmer
4.061
209093AE2-110 GEN
Solar/Wind Harmer
1.275
209120AE2-241 GEN
Solar/Wind Harmer
1.275
972221AH1-695 GEN
Adder
108.273
970767AG2-484 GEN
Solar/Wind Harmer
0.585
226910AB2-157 C
Solar/Wind Helper
0.017
3141196NOKESVL
Solar/Wind Helper
1.13
316077AC2-138 C
Solar/Wind Helper
0.24
316484AD2-074 GEN
Solar/Wind Helper
0.488
316075AC2-137 C
Solar/Wind Helper
0.383
966621AG1-532 GEN
Solar/Wind Helper
0.209
942461AE2-259 GEN
Solar/Wind Helper
1.545
316317KELFORD C
Solar/Wind Helper
0.205
230425AE1-104_GEN2
Solar/Wind Harmer
11.603
207500AE2-000G1
Solar/Wind Harmer
10.554
970025AG2-016 GEN
Solar/Wind Harmer
1.528
217147KRNY_1212
Adder
7.361
217147KRNY_1212
Adder
7.23
217146KRNY_1234
Adder
7.213
217146KRNY_1234
Adder
7.164
20462827N BANGR8
Adder
0.599
209026WIENIPP4
Adder
4.334
20486527WR_V4-052
Adder
0.884
200917MEHOOPANY_G
Solar/Wind Harmer
0.308
315651AD1-115 GEN
Solar/Wind Helper
0.907
238169AE2-226 GEN1
Solar/Wind Helper
0.616
238170AE2-226 GEN2
Solar/Wind Helper
0.616
3141783LANCAST
Solar/Wind Helper
0.151
3141783LANCAST
Solar/Wind Helper
0.101
316059AD1-063 C
Solar/Wind Helper
0.253
313526AB2-022
Solar/Wind Helper
0.368
3146206CASHIE
Solar/Wind Helper
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
961941AG1-037 GEN
Solar/Wind Helper
0.078
3146043SEABORD
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.46
232406W1-004 FULL
Solar/Wind Harmer
0.627
3138133OCRAN
Solar/Wind Helper
0.075
3141873WAN 176
Solar/Wind Helper
0.05
3143873LANEXA
Solar/Wind Helper
0.15
316382AG1-145 C
Solar/Wind Helper
0.334
316159AE1-175 C
Solar/Wind Helper
0.376
316236AE1-162_GEN
Solar/Wind Helper
0.329
3143316POE
Solar/Wind Helper
0.966
316405AF2-144 C
Solar/Wind Helper
0.278
3146486SUNBURY
Solar/Wind Helper
0.24
3146486SUNBURY
Solar/Wind Helper
0.24
3145176PASQUOTANK
Solar/Wind Helper
0.149
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3130546PLYMOUTH
Solar/Wind Helper
0.233
315733AD1-074 GEN2
Solar/Wind Helper
2.665
946281AF1-292 GEN
Solar/Wind Helper
0.231
3146033SCOT NK
Solar/Wind Helper
0.905
3148013FISHERV
Solar/Wind Helper
0.128
232434Z2-077 GEN
Solar/Wind Harmer
0.04
232422X3-066 FULL
Solar/Wind Harmer
0.08
213815MOSER1-3
Adder
2.986
205941AD2-115 GEN
Solar/Wind Harmer
0.095
209025WIENIPP3
Adder
4.29
209142AF1-226 GEN
Solar/Wind Harmer
2.23
970755AG2-478 GEN
Solar/Wind Harmer
0.059
227287AC2-120 GEN
Solar/Wind Helper
0.416
966881AG1-559 GEN
Solar/Wind Helper
0.354
316473AC1-191 GEN
Solar/Wind Helper
1.549
3142946ENON
Solar/Wind Helper
0.083
3145336SMITFLD
Solar/Wind Helper
0.098
316017AA1-139 ULT1
Solar/Wind Helper
1.109
3146456SLIGO L269
Solar/Wind Helper
0.242
3145273HOLLAND
Solar/Wind Helper
0.179
3146376EDENTON
Solar/Wind Helper
0.237
3146206CASHIE
Solar/Wind Helper
0.232
3146173TUNIS
Solar/Wind Helper
0.231
316181AB2-040 GEN
Solar/Wind Helper
1.646
3147043LAWRENC
Solar/Wind Helper
0.137
3147133PAMPLIN
Solar/Wind Helper
0.715
316478AD1-087 GEN
Solar/Wind Helper
1.113
316499AE2-029_GEN
Solar/Wind Helper
0.755
233987AB2-037 GEN
Solar/Wind Harmer
-0.001
233973AC2-185 C
Solar/Wind Harmer
1.751
970695AG2-447 GEN
Solar/Wind Harmer
2.427
232907VN8
Adder
29.155
233935AB2-179 C
Solar/Wind Harmer
1.314
219221BRL12CT1
Adder
7.507
219223BRL12CT3
Adder
7.507
20636028O CRK C1
Adder
5.899
971667AH1-334 GEN
Solar/Wind Harmer
1.481
20635828PARLN1&2
Adder
2.791
207442AE1-156 GEN
Solar/Wind Harmer
0.049
971007AG2-625 GEN
Solar/Wind Harmer
1.387
20466127PORT 5CT
Adder
22.122
3132273ORANGE
Solar/Wind Helper
0.052
316223AC1-118
Solar/Wind Helper
0.395
3144536CHRHLND
Solar/Wind Helper
0.037
23546401DTGZ2-030
Solar/Wind Helper
0.076
3142956BIRDNECK
Solar/Wind Helper
0.164
316305AF2-043 C
Solar/Wind Helper
0.326
316320Y1-086
Solar/Wind Helper
0.108
3146516WINFALL
Solar/Wind Helper
0.239
315735AD1-075 GEN1
Solar/Wind Helper
1.333
3146776BUCKING
Solar/Wind Helper
0.083
3145893MURPHYS
Solar/Wind Helper
0.083
3145893MURPHYS
Solar/Wind Helper
0.232
3146263WOODLND
Solar/Wind Helper
0.229
3145963POPLR C
Solar/Wind Helper
0.228
316011AB1-132 GEN
Solar/Wind Helper
2.46
200034PCHBTM 2
50/50
16.321
200205Y1-065-CTG2
50/50
3.255
228251CARLLS#4
Adder
0.542
213589EDDYSTN4
Adder
67.989
213535CROYDN11
Adder
8.601
20636128O CRK C2
Adder
5.379
20628028LAKEHURS
Adder
0.793
20635128RRCT3&4
Adder
9.327
20635128RRCT3&4
Adder
8.136
218419LINDEN_G6
Adder
14.298
219035LINDEN_G8
Adder
13.726
972237AH1-703 GEN
Adder
8.423
20465127PORT CT
Adder
3.327
20465527S.RDG CT
Adder
2.194
316450AC1-158 RIC
Solar/Wind Helper
0.401
966001AG1-469 GEN
Solar/Wind Helper
0.276
316487AF1-042 GEN
Solar/Wind Helper
0.255
316033AB2-134 GEN
Solar/Wind Helper
0.853
238148AE2-230_GEN2
Solar/Wind Helper
0.421
3145506HICKORY
Solar/Wind Helper
0.97
3145506HICKORY
Solar/Wind Helper
0.582
3145506HICKORY
Solar/Wind Helper
0.145
316339AD2-160 GEN
Solar/Wind Helper
0.924
316388AE2-253 GEN
Solar/Wind Helper
0.924
3137176SLIGO L2192
Solar/Wind Helper
0.962
3130086AYDLETT
Solar/Wind Helper
0.966
3146626S HERTFORD
Solar/Wind Helper
0.239
3145823KELFORD
Solar/Wind Helper
0.228
315821AE2-092 GEN
Solar/Wind Helper
2.119
3145796HORNRTN
Solar/Wind Helper
0.907
3145796HORNRTN
Solar/Wind Helper
0.227
316212AC1-099_GEN
Solar/Wind Helper
1.01
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
232926CRISFLD1
Adder
1.906
231940T-011
Adder
0.724
234041AC1-190 GEN
Solar/Wind Harmer
7.072
228201CARL#2CT
Adder
5.906
228200CARL#1CT
Adder
5.617
213815MOSER1-3
Adder
2.986
213815MOSER1-3
Adder
2.986
20714828MDF_W3-079
Solar/Wind Harmer
0.082
972260AH1-715 GEN1
Adder
11.449
972261AH1-715 GEN2
Adder
13.33
970761AG2-481 GEN
Solar/Wind Harmer
0.614
315976AC1-164 GENA
Solar/Wind Helper
3.228
316169AC1-164_GENC
Solar/Wind Helper
2.788
3142946ENON
Solar/Wind Helper
0.025
316294AC1-161 GEN
Solar/Wind Helper
4.47
238147AE2-230_GEN1
Solar/Wind Helper
0.421
316349AD2-085 GEN
Solar/Wind Helper
1.109
3146386ELIZ CT
Solar/Wind Helper
0.241
316431W1029_GEN1
Solar/Wind Helper
0.969
316433W1029_GEN2
Solar/Wind Helper
0.969
316365GEN2_N
Solar/Wind Helper
0.885
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3147133PAMPLIN
Solar/Wind Helper
0.228
3147133PAMPLIN
Solar/Wind Helper
0.182
232901NORTHST
Adder
8.082
234033AF1-007_GEN
Solar/Wind Harmer
13.407
232902EASTMUNI
Adder
12.63
234012AE2-112_GEN
Solar/Wind Harmer
2.247
972251AH1-710 GEN
Adder
42.883
231918WEST 1
Adder
3.192
228732V1-021 C
Adder
0.163
228400MICK 1CT
Adder
10.092
966261AG1-495 GEN
Solar/Wind Harmer
1.431
209023WIENIPP1
Adder
8.772
209025WIENIPP3
Adder
4.379
963071AG1-156 GEN
Solar/Wind Harmer
6.123
970757AG2-479 GEN
Solar/Wind Harmer
0.61
205967AE2-211_GEN
Solar/Wind Harmer
3.973
205932AD2-116_GEN
Solar/Wind Harmer
0.072
970753AG2-477 GEN
Solar/Wind Harmer
0.06
316447AC1-158 HLD
Solar/Wind Helper
3.306
316192AB2-158 GEN
Solar/Wind Helper
1.752
3142416OLDCHRC
Solar/Wind Helper
0.654
3142416OLDCHRC
Solar/Wind Helper
0.25
3141766HARMONY
Solar/Wind Helper
0.05
315975AC1-164 GENB
Solar/Wind Helper
0.095
3142433PROV 92
Solar/Wind Helper
1
3145336SMITFLD
Solar/Wind Helper
0.977
316375AC2-012 GEN
Solar/Wind Helper
0.64
3146456SLIGO L269
Solar/Wind Helper
0.242
3145663CRESWEL
Solar/Wind Helper
0.657
316023GEN1_S
Solar/Wind Helper
0.885
3146206CASHIE
Solar/Wind Helper
0.232
3146173TUNIS
Solar/Wind Helper
0.231
3156021HOLLOMANSOL
Solar/Wind Helper
1.758
3145683EARLEYS
Solar/Wind Helper
0.23
316131AB2-060 GEN
Solar/Wind Helper
1.369
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.23
316486AD2-202 GEN
Solar/Wind Helper
0.326
316274AC1-208 GEN
Solar/Wind Helper
1.37
200195DELTA ST
50/50
2.416
232913OH NUG2
Adder
8.461
232920IR10
Adder
3.068
970597AG2-380 GEN
Solar/Wind Harmer
4.024
231906DC3 NUG
Adder
13.515
231907DC10
Adder
3.374
972141AH1-641 GEN
Solar/Wind Harmer
1.34
213611FALLS1-3
Adder
2.963
213611FALLS1-3
Adder
2.963
207507AE2-000G3
Solar/Wind Harmer
10.554
971521AH1-258 GEN
Solar/Wind Harmer
1.456
217086KRNY_131
Adder
7.673
209030FRFA O01
Adder
0.191
205951AE1-129_GEN
Solar/Wind Harmer
0.111
205956AE1-196_GEN
Solar/Wind Harmer
0.024
20465027TOLNA CT
Adder
2.369
226929AD2-058 GEN
Solar/Wind Helper
0.119
3138216PACIFIC
Solar/Wind Helper
0.049
316164AC1-076 GEN
Solar/Wind Helper
1.281
3141813NORNECK
Solar/Wind Helper
0.255
957601AF2-054 GEN
Solar/Wind Helper
0.336
316233AE1-074 FULL
Solar/Wind Helper
0.381
316018AA1-139 ULT2
Solar/Wind Helper
1.043
315800Z1-036_GEN1
Solar/Wind Helper
1.306
315732AD1-074 GEN1
Solar/Wind Helper
2.665
3145893MURPHYS
Solar/Wind Helper
0.625
3145893MURPHYS
Solar/Wind Helper
0.232
316463AE2-346 GEN
Solar/Wind Helper
0.211
3145513AHOSKIE
Solar/Wind Helper
0.103
3145513AHOSKIE
Solar/Wind Helper
0.23
3137643SOCKMAN
Solar/Wind Helper
0.912
316426AA2-053 GEN
Solar/Wind Helper
1.305
316174AB2-169 GEN
Solar/Wind Helper
0.583
3144303KENBRDG
Solar/Wind Helper
0.181
200035PCHBTM 3
50/50
16.185
233971AC1-093 C
Solar/Wind Harmer
1.751
232918OH NUG7
Adder
8.518
232905CHERITON_25
Adder
2.382
232910NRG_G1
Adder
8.361
234014AF1-036_GEN
Solar/Wind Harmer
2.247
972233AH1-701 GEN
Adder
3.587
219304NAMERICA C
Solar/Wind Harmer
0.076
20635028RRCT1&2
Adder
9.662
218418LINDEN_G5
Adder
14.298
219036LINDEN_G7
Adder
13.925
217086KRNY_131
Adder
7.755
316006AB2-029 C
Solar/Wind Helper
0.131
316045AC1-158 PL2
Solar/Wind Helper
4.808
966871AG1-558 GEN
Solar/Wind Helper
0.342
315666AE1-190 GEN
Solar/Wind Helper
0.338
316156AD2-030 GEN
Solar/Wind Helper
0.379
316240AF1-291 C
Solar/Wind Helper
0.333
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.371
316435W1029_GEN3
Solar/Wind Helper
0.969
3146516WINFALL
Solar/Wind Helper
0.239
3146516WINFALL
Solar/Wind Helper
0.239
3146516WINFALL
Solar/Wind Helper
0.239
315614AA2-178 GEN
Solar/Wind Helper
1.434
3146776BUCKING
Solar/Wind Helper
0.928
3146776BUCKING
Solar/Wind Helper
0.075
3145893MURPHYS
Solar/Wind Helper
0.332
3145893MURPHYS
Solar/Wind Helper
0.417
316140AB2-099
Solar/Wind Helper
0.088
316005AA1-067
Solar/Wind Helper
0.255
200202DELTA2 ST
50/50
4.74
200052ROCKSP 1
50/50
2.048
200053ROCKSP 2
50/50
2.008
213942SCHUYLKILL
Adder
3.019
213942SCHUYLKILL
Adder
2.309
213957STHWK3-4
Adder
2.308
213957STHWK3-4
Adder
2.308
213561DLWR9-10
Adder
3.004
213561DLWR9-10
Adder
2.297
963401AG1-189 GEN
Solar/Wind Harmer
0.938
971189AH1-054 GEN
Solar/Wind Harmer
0.636
208862AG1-362 C
Solar/Wind Harmer
0.49
209027LOR2_Q27
Solar/Wind Harmer
0
20390726Y2-042
Adder
2.283
3141426STAFORD
Solar/Wind Helper
0.062
316468AD1-105 GEN
Solar/Wind Helper
1.243
3141913WHIT STONE
Solar/Wind Helper
0.251
957831AF2-077 GEN
Solar/Wind Helper
0.335
315697AD1-025 GEN
Solar/Wind Helper
2.817
315839AE2-212 C
Solar/Wind Helper
0.331
316258AE1-075 C
Solar/Wind Helper
0.334
316316AC1-027 C
Solar/Wind Helper
0.384
316322AB2-045
Solar/Wind Helper
0.259
3145796HORNRTN
Solar/Wind Helper
0.726
3145796HORNRTN
Solar/Wind Helper
0.091
316210AC1-098 GEN
Solar/Wind Helper
1.818
316238AB2-078_GEN
Solar/Wind Helper
0.302
316239AB2-077_GEN
Solar/Wind Helper
0.302
3148133STUARTS
Solar/Wind Helper
0.134
3145746EVERETS
Solar/Wind Helper
0.886
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
972281AH1-725 GEN
50/50
137.55
200201DELTA2 CT2
50/50
2.799
232410W1-006 C
Solar/Wind Harmer
0.627
232899W1-062
Adder
9.333
233984AB2-036 GEN
Solar/Wind Harmer
7.033
233930AB2-032 GEN
Solar/Wind Harmer
0.924
228307PCLP GT
Adder
10.356
213587EDDYSTN3
Adder
67.984
217083KRNY_132
Adder
7.69
961541AF2-445A GEN
Solar/Wind Harmer
1.807
209010PEIP 1
Adder
2.843
209010PEIP 1
Adder
0.416
209130AF1-271A GEN
Solar/Wind Harmer
1.519
20464827MOUNT CT
Adder
1.936
20464827MOUNT CT
Adder
1.879
316411AF1-147_GEN1
Solar/Wind Helper
0.977
316312AB1-027
Solar/Wind Helper
0.48
3143526WINTERP
Solar/Wind Helper
1.298
316185AD1-033 GEN
Solar/Wind Helper
1.145
237061AD1-155 GEN
Solar/Wind Helper
1.511
3144356SAPONY
Solar/Wind Helper
0.428
316315AB2-025 C
Solar/Wind Helper
0.365
3145796HORNRTN
Solar/Wind Helper
0.68
235020AA1-095 C
Solar/Wind Helper
0.042
316237AB2-079_GEN
Solar/Wind Helper
0.302
200192DELTA CT1
50/50
1.564
200054ROCKSP 3
50/50
2.072
232408W1-005 C
Solar/Wind Harmer
0.627
232917OH NUG6
Adder
8.537
232915OH NUG4
Adder
8.518
972177AH1-672 GEN
Solar/Wind Harmer
9.886
213958STHWK5-6
Adder
2.308
207522AF2-254 C
Solar/Wind Harmer
0.775
972275AH1-722 GEN
Adder
26.286
207528AF2-192 GEN
Solar/Wind Harmer
0.598
217186ESSEX_G9
Adder
3.286
217083KRNY_132
Adder
7.739
208909MACR G3
Adder
132.999
209010PEIP 1
Adder
0.517
209008PAXT IPP
Adder
1.596
316415AF1-147_GEN2
Solar/Wind Helper
0.977
238175AF1-290_GEN
Solar/Wind Helper
0.138
964211AG1-282 GEN
Solar/Wind Helper
0.343
3143526WINTERP
Solar/Wind Helper
1.298
315671AE2-027_GEN
Solar/Wind Helper
1.993
316072AD1-144
Solar/Wind Helper
0.278
3145823KELFORD
Solar/Wind Helper
0.228
3145783HORNRTN
Solar/Wind Helper
0.227
3145796HORNRTN
Solar/Wind Helper
0.748
3145796HORNRTN
Solar/Wind Helper
0.227
316034AC1-036 C
Solar/Wind Helper
0.237
3147983MERCK5
Solar/Wind Helper
0.09
316129AC1-054 GEN
Solar/Wind Helper
1.116
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
200204Y1-065-CTG1
50/50
3.255
233918AB1-142 GEN
Solar/Wind Harmer
0.246
228206SHRMN CT
Adder
14.258
213611FALLS1-3
Adder
2.963
214194N WALES4
Adder
0.714
20635828PARLN1&2
Adder
6.162
20635028RRCT1&2
Adder
9.813
218524CNTRALGAS1 C
Solar/Wind Harmer
0.636
212507AE2-042_GEN
Solar/Wind Harmer
0.479
20465027TOLNA CT
Adder
2.278
316337AD2-073 GEN
Solar/Wind Helper
0.39
3141726DUNNSVL
Solar/Wind Helper
1.017
316132AB2-190 GEN1
Solar/Wind Helper
1.413
315773AC2-141 GEN
Solar/Wind Helper
5.26
316036AC1-147 C
Solar/Wind Helper
0.371
3146516WINFALL
Solar/Wind Helper
0.776
3146516WINFALL
Solar/Wind Helper
0.239
3146776BUCKING
Solar/Wind Helper
0.093
3145893MURPHYS
Solar/Wind Helper
0.927
315607AA1-063A GEN
Solar/Wind Helper
1.314
3146263WOODLND
Solar/Wind Helper
0.229
3145963POPLR C
Solar/Wind Helper
0.228
200194DELTA CT3
50/50
1.564
233970AC1-092 C
Solar/Wind Harmer
1.751
232404W1-003 C
Solar/Wind Harmer
0.627
232919VN10
Adder
2.724
232900DEMECSMY
Adder
8.952
231917EM10
Adder
2.231
970997AG2-616 GEN
Solar/Wind Harmer
6.191
213497CHSTR7-9
Adder
2.328
213497CHSTR7-9
Adder
2.328
213560DLW11-12
Adder
2.297
219222BRL12CT2
Adder
7.507
217121ECCF
Adder
0.362
971519AH1-257 GEN
Solar/Wind Harmer
1.362
20465127PORT CT
Adder
2.507
20465527S.RDG CT
Adder
2.267
209018SUNBIPCT
Adder
5.767
316044AC1-158 PL1
Solar/Wind Helper
1.502
3147666LOUISA
Solar/Wind Helper
1.041
316404AE1-155 C
Solar/Wind Helper
2.169
3138133OCRAN
Solar/Wind Helper
0.151
315662AE1-191 GEN
Solar/Wind Helper
1.35
316280AD1-041 GEN
Solar/Wind Helper
0.844
3142543TWELFTH
Solar/Wind Helper
0.024
3143226MDLTHAN
Solar/Wind Helper
0.249
316369SG1_INVT
Solar/Wind Helper
1.187
238152AF2-075_GEN
Solar/Wind Helper
0.602
316381AD1-082 GEN
Solar/Wind Helper
1.264
319010AE1-072 C
Solar/Wind Helper
2.768
315611Z1-036_GEN2
Solar/Wind Helper
1.306
3130156CHOWAN
Solar/Wind Helper
0.237
315816AE2-034 GEN
Solar/Wind Helper
1.075
315737AD1-076 GEN
Solar/Wind Helper
2.279
3146926FARMVIL
Solar/Wind Helper
0.138
316087AB2-174 GEN
Solar/Wind Helper
1.607
315785AD2-033 C
Solar/Wind Helper
2.634
23777901MDS_W4-102
Solar/Wind Helper
0.141
233972AC1-094 C
Solar/Wind Harmer
1.751
232921TASLEY2G
Adder
5.012
213497CHSTR7-9
Adder
2.328
213560DLW11-12
Adder
2.297
20635928PARLN3&4
Adder
2.791
3147666LOUISA
Solar/Wind Helper
0.599
3141906WESTMOR
Solar/Wind Helper
0.103
316458AB2-190 GEN2
Solar/Wind Helper
1.413
3144873MCLAUGH
Solar/Wind Helper
0.006
316246AF1-032 C
Solar/Wind Helper
0.277
316321Z2-027
Solar/Wind Helper
0.367
3146626S HERTFORD
Solar/Wind Helper
0.239
3146926FARMVIL
Solar/Wind Helper
0.138
3142666NORTHAMPTON
Solar/Wind Helper
0.228
316190AA2-174 GEN
Solar/Wind Helper
0.015
3145933PARMELE
Solar/Wind Helper
0.224
3148013FISHERV
Solar/Wind Helper
0.224
3146626S HERTFORD
Solar/Wind Helper
0.239
313506AB2-031 GEN
Solar/Wind Helper
1.042
3142666NORTHAMPTON
Solar/Wind Helper
0.228
3142666NORTHAMPTON
Solar/Wind Helper
0.228
3142666NORTHAMPTON
Solar/Wind Helper
0.228
3142666NORTHAMPTON
Solar/Wind Helper
0.137
3132123MT JACKSON
Solar/Wind Helper
0.715
3145593CAROLNA
Solar/Wind Helper
0.228
3145593CAROLNA
Solar/Wind Helper
0.228
3145933PARMELE
Solar/Wind Helper
0.449
3145933PARMELE
Solar/Wind Helper
0.224
G-007ALTFEXP_G-007A->PJM
CMTX
42.674
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.754
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.476
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.841
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.028
VTFLTFEXP_VFT->PJM
CMTX
112.763
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.891
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.639

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.62 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3458.01
MW Contribution:
6.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232912OH NUG1
Adder
7.003
971195AH1-057 GEN
Solar/Wind Harmer
0.773
233955AB2-172 GEN
Solar/Wind Harmer
3.959
232813VAUGHN
Adder
0.466
231902DC CT7
Adder
8.813
233915AB1-141 GEN
Solar/Wind Harmer
0.778
970453AG2-297 GEN
Solar/Wind Harmer
1.938
964001AG1-254 GEN
Solar/Wind Harmer
5.098
228728W1-130C
Solar/Wind Harmer
0.464
227927V4-067C
Solar/Wind Harmer
0.138
219137THOSOLAR C
Solar/Wind Harmer
0.839
219615MILLCREEK C
Solar/Wind Harmer
0.164
219224BRL12CT4
Adder
6.116
207487AE2-000G4
Solar/Wind Harmer
21.434
207497AE2-000G2
Solar/Wind Harmer
21.434
219620RIDERU C
Solar/Wind Harmer
0.038
20635928PARLN3&4
Adder
5.022
218526CNTRALGAS2 C
Solar/Wind Harmer
0.251
217167KRNY_14
Adder
6.305
971009AG2-626 GEN
Solar/Wind Harmer
1.114
961261AF2-417 GEN
Solar/Wind Harmer
0.665
212266LOR1
Solar/Wind Harmer
0.785
959431AF2-234 GEN
Solar/Wind Harmer
1.264
200195DELTA ST
50/50
1.991
232920IR10
Adder
2.506
233901CHERRYDALE C
Solar/Wind Harmer
0.892
232913OH NUG2
Adder
6.91
970597AG2-380 GEN
Solar/Wind Harmer
3.282
231906DC3 NUG
Adder
11.024
231907DC10
Adder
2.752
972141AH1-641 GEN
Solar/Wind Harmer
2.013
213611FALLS1-3
Adder
2.414
213611FALLS1-3
Adder
2.414
20715028HAN_X4-015
Solar/Wind Harmer
0.203
207507AE2-000G3
Solar/Wind Harmer
21.434
207445AB1-138_GEN
Solar/Wind Harmer
0.394
20720628TIN_W1-124
Solar/Wind Harmer
0.675
971521AH1-258 GEN
Solar/Wind Harmer
1.837
20675528CPH_W2-050
Solar/Wind Harmer
0.389
20676428JCR_X2-075
Solar/Wind Harmer
0.232
217086KRNY_131
Adder
6.251
20675128HRM_W1-127
Solar/Wind Harmer
0.116
209029WAYMART-WD
Solar/Wind Harmer
1.696
959421AF2-233 GEN
Solar/Wind Harmer
0.632
226929AD2-058 GEN
Solar/Wind Helper
0.143
3138216PACIFIC
Solar/Wind Helper
0.039
232904IR4
Adder
64.11
232432Z2-076 GEN
Solar/Wind Harmer
0.105
233968AD2-076_GEN
Solar/Wind Harmer
5.226
231919CHRIST1
Adder
3.418
231920CHRIST2
Adder
3.342
230430AE1-229_GEN
Solar/Wind Harmer
20.033
230422AE1-104_GEN1
Solar/Wind Harmer
23.58
230425AE1-104_GEN2
Solar/Wind Harmer
23.58
230407AD2-065 C
Solar/Wind Harmer
0.092
20720728JCB_W1-129
Solar/Wind Harmer
0.203
207500AE2-000G1
Solar/Wind Harmer
21.434
970025AG2-016 GEN
Solar/Wind Harmer
1.927
20714428HOW_X1-037
Solar/Wind Harmer
0.838
218449LINSOLAR C
Solar/Wind Harmer
0.682
217147KRNY_1212
Adder
5.997
217147KRNY_1212
Adder
5.89
217146KRNY_1234
Adder
5.877
217146KRNY_1234
Adder
5.836
964851AG1-348 GEN
Solar/Wind Harmer
0.929
207408W3-077 C
Solar/Wind Harmer
0.345
20462827N BANGR8
Adder
0.487
209026WIENIPP4
Adder
3.535
20486527WR_V4-052
Adder
0.706
209054AE2-059 GEN
Solar/Wind Harmer
1.076
209067AE2-060 GEN
Solar/Wind Harmer
0.909
200204Y1-065-CTG1
50/50
2.679
233918AB1-142 GEN
Solar/Wind Harmer
0.778
228206SHRMN CT
Adder
11.633
228260V4-054C
Solar/Wind Harmer
0.719
228729W2-030 C
Solar/Wind Harmer
0.403
219686LUMSOLAR_N C
Solar/Wind Harmer
0.14
219348LDSOLAR C
Solar/Wind Harmer
0.41
213611FALLS1-3
Adder
2.414
214194N WALES4
Adder
0.581
20720428HOL_W1-112
Solar/Wind Harmer
0.235
20635828PARLN1&2
Adder
5.022
20635028RRCT1&2
Adder
7.997
218524CNTRALGAS1 C
Solar/Wind Harmer
0.251
217209CENTRL HS C
Solar/Wind Harmer
0.03
20671828STAW2-080
Solar/Wind Harmer
0.071
207439AE1-081 C O1
Solar/Wind Harmer
0.041
207530AG1-191 GEN
Solar/Wind Harmer
0.935
211065PSPA IPP
Solar/Wind Harmer
0.305
961301AF2-421 GEN
Solar/Wind Harmer
0.663
963151AG1-164 GEN
Solar/Wind Harmer
0.663
961341AF2-425 GEN
Solar/Wind Harmer
0.645
212507AE2-042_GEN
Solar/Wind Harmer
1.907
200035PCHBTM 3
50/50
13.333
233971AC1-093 C
Solar/Wind Harmer
2.019
232918OH NUG7
Adder
6.956
232905CHERITON_25
Adder
1.945
233994AC2-023 GEN
Solar/Wind Harmer
2.128
234036AF2-325 C
Solar/Wind Harmer
0.726
232910NRG_G1
Adder
6.825
234014AF1-036_GEN
Solar/Wind Harmer
2.133
232436AB1-176 C
Solar/Wind Harmer
0.18
972233AH1-701 GEN
Adder
2.923
219912AD2-042 GEN
Solar/Wind Harmer
0.549
219607WPEMNERT C
Solar/Wind Harmer
0.287
219304NAMERICA C
Solar/Wind Harmer
0.213
20635028RRCT1&2
Adder
7.874
218418LINDEN_G5
Adder
11.65
219036LINDEN_G7
Adder
11.346
217086KRNY_131
Adder
6.318
20674328GAR_V4-001
Solar/Wind Harmer
0.075
946751AF1-339 GEN
Solar/Wind Harmer
0.633
316045AC1-158 PL2
Solar/Wind Helper
3.981
316006AB2-029 C
Solar/Wind Helper
0.107
233987AB2-037 GEN
Solar/Wind Harmer
9.02
233973AC2-185 C
Solar/Wind Harmer
4.296
970695AG2-447 GEN
Solar/Wind Harmer
2.842
233923SMA
Solar/Wind Harmer
2.897
233997TMININ_4.2
Solar/Wind Harmer
0.79
232907VN8
Adder
23.808
232417X3-008 C
Solar/Wind Harmer
0.891
233935AB2-179 C
Solar/Wind Harmer
1.945
219221BRL12CT1
Adder
6.116
219223BRL12CT3
Adder
6.116
959561AF2-247 GEN
Solar/Wind Harmer
0.331
20715728PEM_W1-119
Solar/Wind Harmer
0.364
20636028O CRK C1
Adder
4.809
971667AH1-334 GEN
Solar/Wind Harmer
1.868
219727YARDVSOLFA C
Solar/Wind Harmer
0.619
20635828PARLN1&2
Adder
2.275
219249CENTRALDIV C
Solar/Wind Harmer
0.027
207442AE1-156 GEN
Solar/Wind Harmer
0.504
217211CAMDEN ST C
Solar/Wind Harmer
0.017
217194REDH C
Solar/Wind Harmer
0.334
207511W3-106 GEN
Solar/Wind Harmer
0.224
971007AG2-625 GEN
Solar/Wind Harmer
1.747
20674128FR_U2-059
Solar/Wind Harmer
0.125
20466127PORT 5CT
Adder
18.01
211065PSPA IPP
Solar/Wind Harmer
0.305
957921AF2-086 GEN
Solar/Wind Harmer
0.626
232901NORTHST
Adder
6.603
234033AF1-007_GEN
Solar/Wind Harmer
29.492
233996TM1833_GEN
Solar/Wind Harmer
0.79
232426Y1-080 FULL
Solar/Wind Harmer
0.151
232902EASTMUNI
Adder
10.308
234012AE2-112_GEN
Solar/Wind Harmer
1.813
972251AH1-710 GEN
Adder
35.054
231918WEST 1
Adder
2.599
228732V1-021 C
Adder
0.133
228400MICK 1CT
Adder
8.225
219766PARADISE C
Solar/Wind Harmer
0.217
20714528FRN_Y2-051
Solar/Wind Harmer
0.2
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
218440SUMMTASSOC C
Solar/Wind Harmer
0.087
217208PARK ELE C
Solar/Wind Harmer
0.017
966261AG1-495 GEN
Solar/Wind Harmer
2.384
20674628WNG_W3-110
Solar/Wind Harmer
0.274
209023WIENIPP1
Adder
7.154
209025WIENIPP3
Adder
3.571
963071AG1-156 GEN
Solar/Wind Harmer
6.527
316447AC1-158 HLD
Solar/Wind Helper
2.738
232926CRISFLD1
Adder
1.556
231940T-011
Adder
0.591
234041AC1-190 GEN
Solar/Wind Harmer
7.094
228201CARL#2CT
Adder
4.817
228200CARL#1CT
Adder
4.582
219904AC1-010 C
Solar/Wind Harmer
0.261
219906AC1-017 C
Solar/Wind Harmer
0.153
213815MOSER1-3
Adder
2.431
213815MOSER1-3
Adder
2.431
20720828JCB_W4-025
Solar/Wind Harmer
0.308
20714828MDF_W3-079
Solar/Wind Harmer
0.208
219817TRENTONSOL C
Solar/Wind Harmer
0.748
20641628MLH_W1-032
Solar/Wind Harmer
0.199
20742028HF_AC1-207
Solar/Wind Harmer
0.532
218438BLK ROCK C
Solar/Wind Harmer
0.092
972260AH1-715 GEN1
Adder
9.329
972261AH1-715 GEN2
Adder
10.861
217202FBANKSOLAR C
Solar/Wind Harmer
0.05
217201HACKENSOLA C
Solar/Wind Harmer
0.05
217206BARNGR HS C
Solar/Wind Harmer
0.021
217204WCALDSOLAR C
Solar/Wind Harmer
0.05
20674828DL_W4-046
Solar/Wind Harmer
0.439
20634528N27_Y2-018
Solar/Wind Harmer
0.183
232434Z2-077 GEN
Solar/Wind Harmer
0.198
232406W1-004 FULL
Solar/Wind Harmer
0.793
233964AF2-378 GEN
Solar/Wind Harmer
0.101
232422X3-066 FULL
Solar/Wind Harmer
0.197
230415AB2-049 C
Solar/Wind Harmer
0.132
219291REEVESSOUT C
Solar/Wind Harmer
0.041
219236SOUTHERNHQ C
Solar/Wind Harmer
0.047
213815MOSER1-3
Adder
2.431
20714928UPF_X1-085
Solar/Wind Harmer
0.277
219114HARTZY_C
Solar/Wind Harmer
0.567
219918AC2-009 C
Solar/Wind Harmer
0.017
20674528F3S_W2-016
Solar/Wind Harmer
0.955
209025WIENIPP3
Adder
3.499
205941AD2-115 GEN
Solar/Wind Harmer
0.611
209142AF1-226 GEN
Solar/Wind Harmer
3.728
227287AC2-120 GEN
Solar/Wind Helper
0.516
200202DELTA2 ST
50/50
3.907
200052ROCKSP 1
50/50
1.686
200053ROCKSP 2
50/50
1.653
233940AF2-379 C
Solar/Wind Harmer
0.148
230434AG1-499 GEN
Solar/Wind Harmer
0.404
219258KINSLEYDEP C
Solar/Wind Harmer
0.224
213942SCHUYLKILL
Adder
2.455
213942SCHUYLKILL
Adder
1.877
213957STHWK3-4
Adder
1.876
213957STHWK3-4
Adder
1.876
213561DLWR9-10
Adder
2.444
213561DLWR9-10
Adder
1.869
219610FLORENCE C
Solar/Wind Harmer
0.949
963401AG1-189 GEN
Solar/Wind Harmer
1.547
971189AH1-054 GEN
Solar/Wind Harmer
0.803
20716228APLW2-078
Solar/Wind Harmer
0.599
20673828FLE_V3-070
Solar/Wind Harmer
0.316
20676128MHD_W3-029
Solar/Wind Harmer
0.324
209027LOR2_Q27
Solar/Wind Harmer
2.962
208862AG1-362 C
Solar/Wind Harmer
0.523
964051AG1-259 GEN
Solar/Wind Harmer
0.848
964061AG1-260 GEN
Solar/Wind Harmer
0.848
3141426STAFORD
Solar/Wind Helper
0.053
200192DELTA CT1
50/50
1.289
200054ROCKSP 3
50/50
1.705
232408W1-005 C
Solar/Wind Harmer
0.793
232917OH NUG6
Adder
6.972
232915OH NUG4
Adder
6.956
972177AH1-672 GEN
Solar/Wind Harmer
10.65
233944AB2-135 GEN
Solar/Wind Harmer
4.119
213958STHWK5-6
Adder
1.876
219907AC1-030 C
Solar/Wind Harmer
0.095
20716028EGP_W2-019
Solar/Wind Harmer
0.316
207522AF2-254 C
Solar/Wind Harmer
0.977
218428ETC SOLAR C
Solar/Wind Harmer
0.024
219908AB1-139 C
Solar/Wind Harmer
0.258
972275AH1-722 GEN
Adder
21.418
20673628F1S_V4-069
Solar/Wind Harmer
0.122
207528AF2-192 GEN
Solar/Wind Harmer
0.862
217186ESSEX_G9
Adder
2.678
217083KRNY_132
Adder
6.305
20676228FRD_X1-012
Solar/Wind Harmer
0.401
20675828AU_W4-064
Solar/Wind Harmer
0.117
20675728RH_W2-091
Solar/Wind Harmer
0.41
207484AF2-139 C O1
Solar/Wind Harmer
0.344
208909MACR G3
Adder
108.247
209010PEIP 1
Adder
0.422
946731AF1-337 GEN
Solar/Wind Harmer
0.633
209008PAXT IPP
Adder
1.271
316415AF1-147_GEN2
Solar/Wind Helper
0.781
972281AH1-725 GEN
50/50
114.199
200201DELTA2 CT2
50/50
2.307
232410W1-006 C
Solar/Wind Harmer
0.793
232899W1-062
Adder
7.624
233946AB2-136 GEN
Solar/Wind Harmer
3.159
233952AC2-187 GEN
Solar/Wind Harmer
0.891
233954AC2-188 GEN
Solar/Wind Harmer
0.891
233984AB2-036 GEN
Solar/Wind Harmer
9.832
233930AB2-032 GEN
Solar/Wind Harmer
0.655
233982AB2-133 GEN
Solar/Wind Harmer
3.828
230511AF1-262
Solar/Wind Harmer
0.128
228307PCLP GT
Adder
8.443
228754AB1-001 C
Solar/Wind Harmer
0.097
213587EDDYSTN3
Adder
55.24
219272CLEANLIGHT C
Solar/Wind Harmer
0.126
217081WEATEXAS C
Solar/Wind Harmer
0.058
217083KRNY_132
Adder
6.265
207471AF2-354 C
Solar/Wind Harmer
0.348
20675928HOL_W4-097
Solar/Wind Harmer
0.089
961541AF2-445A GEN
Solar/Wind Harmer
2.128
209010PEIP 1
Adder
2.322
209010PEIP 1
Adder
0.34
961431AF2-434 GEN
Solar/Wind Harmer
0.644
209130AF1-271A GEN
Solar/Wind Harmer
1.778
316411AF1-147_GEN1
Solar/Wind Helper
0.781
200200DELTA2 CT1
50/50
2.307
200193DELTA CT2
50/50
1.289
200203Y1-065-STG
50/50
4.64
200055ROCKSP 4
50/50
1.676
233939AC1-091 C
Solar/Wind Harmer
2.126
232914OH NUG3
Adder
7.003
232916OH NUG5
Adder
7.003
233933AB2-153 GEN
Solar/Wind Harmer
0.884
219623KINSLEYBEA C
Solar/Wind Harmer
0.296
213958STHWK5-6
Adder
1.876
20716428NHV_W2-082
Solar/Wind Harmer
1.21
963391AG1-188 GEN
Solar/Wind Harmer
2.55
219612MATRIX C
Solar/Wind Harmer
0.125
20716928W4-060COL
Solar/Wind Harmer
0.482
217213AMBOY SO C
Solar/Wind Harmer
0.086
20673728F2S_V4-070
Solar/Wind Harmer
0.122
207510AF2-138 C
Solar/Wind Harmer
1.208
207437AD2-070 GEN
Solar/Wind Harmer
0.205
20671928W4-073
Solar/Wind Harmer
0.294
20633028GILCT9
Adder
19.277
20465427SHAW CT
Adder
2.62
209116AE2-175 GEN
Solar/Wind Harmer
2.78
970095AG2-074 GEN
Solar/Wind Harmer
4.134
961421AF2-433 GEN
Solar/Wind Harmer
0.644
209093AE2-110 GEN
Solar/Wind Harmer
1.61
209120AE2-241 GEN
Solar/Wind Harmer
2.13
946691AF1-333 GEN
Solar/Wind Harmer
0.633
946741AF1-338 GEN
Solar/Wind Harmer
0.633
972221AH1-695 GEN
Adder
86.06
226910AB2-157 C
Solar/Wind Helper
0.021
3141196NOKESVL
Solar/Wind Helper
0.919
200194DELTA CT3
50/50
1.289
233970AC1-092 C
Solar/Wind Harmer
2.126
233998TM1NIN_3.36
Solar/Wind Harmer
0.79
232404W1-003 C
Solar/Wind Harmer
0.793
232900DEMECSMY
Adder
7.313
232919VN10
Adder
2.225
231917EM10
Adder
1.817
970997AG2-616 GEN
Solar/Wind Harmer
6.712
213497CHSTR7-9
Adder
1.892
213497CHSTR7-9
Adder
1.892
213560DLW11-12
Adder
1.869
219222BRL12CT2
Adder
6.116
20717128DIX_Z2-102
Solar/Wind Harmer
0.899
20715828PEM_W1-120
Solar/Wind Harmer
0.364
963711AG1-223 GEN
Solar/Wind Harmer
1.005
219276PARKLANDSO C
Solar/Wind Harmer
0.313
20715228NPK_W1-113
Solar/Wind Harmer
0.292
20720528MAN_W1-024
Solar/Wind Harmer
0.172
219919AE1-041 FULL
Solar/Wind Harmer
0.027
217121ECCF
Adder
0.295
20676728BRNX1-095
Solar/Wind Harmer
0.12
20676328BVR_Y1-020
Solar/Wind Harmer
0.225
20674928WA_W3-044
Solar/Wind Harmer
0.327
971519AH1-257 GEN
Solar/Wind Harmer
1.715
207518AF1-320_GEN
Solar/Wind Harmer
2.488
20465127PORT CT
Adder
2.041
20465527S.RDG CT
Adder
1.811
209018SUNBIPCT
Adder
4.709
209137AF2-361 C
Solar/Wind Harmer
1.757
316044AC1-158 PL1
Solar/Wind Helper
1.244
200034PCHBTM 2
50/50
13.449
200205Y1-065-CTG2
50/50
2.679
234015AF2-250 C
Solar/Wind Harmer
0.095
232428Y3-058 C
Solar/Wind Harmer
0.66
232424Y1-079 C
Solar/Wind Harmer
0.444
228251CARLLS#4
Adder
0.442
228351V2-046C
Solar/Wind Harmer
1.409
230433AD2-135 GEN
Solar/Wind Harmer
0.071
213589EDDYSTN4
Adder
55.245
219287REEVESEAST C
Solar/Wind Harmer
0.928
213535CROYDN11
Adder
7.007
214067T20SOLAR
Solar/Wind Harmer
0.172
20636128O CRK C2
Adder
4.385
207459AE1-142 C O1
Solar/Wind Harmer
0.717
20628028LAKEHURS
Adder
0.647
217197RE CRAN C
Solar/Wind Harmer
0.364
924131AB2-057 GEN
Solar/Wind Harmer
0.698
20635128RRCT3&4
Adder
7.6
20635128RRCT3&4
Adder
6.63
218419LINDEN_G6
Adder
11.65
20675428EAM_W2-061
Solar/Wind Harmer
0.128
219035LINDEN_G8
Adder
11.184
972237AH1-703 GEN
Adder
6.863
20465127PORT CT
Adder
2.708
20465527S.RDG CT
Adder
1.753
316450AC1-158 RIC
Solar/Wind Helper
0.332
233972AC1-094 C
Solar/Wind Harmer
1.708
232921TASLEY2G
Adder
4.093
233950AC2-186 GEN
Solar/Wind Harmer
0.445
228711V2-041C
Solar/Wind Harmer
0.421
213497CHSTR7-9
Adder
1.892
219921AF1-264
Solar/Wind Harmer
0.1
218660EHAMPSOLAR C
Solar/Wind Harmer
0.121
219688LUMSOLAR_S C
Solar/Wind Harmer
0.14
219914AD2-027 C
Solar/Wind Harmer
0.414
213560DLW11-12
Adder
1.869
207454AA2-184 E
Solar/Wind Harmer
0.678
20635928PARLN3&4
Adder
2.275
217169METRODIV C
Solar/Wind Harmer
0.027
963161AG1-165 GEN
Solar/Wind Harmer
0.663
208972BECR K09
Solar/Wind Harmer
0.695
961331AF2-424 GEN
Solar/Wind Harmer
0.645
209071AE2-133 GEN
Solar/Wind Harmer
1.07
G-007ALTFEXP_G-007A->PJM
CMTX
34.775
CBM NorthLTFEXP_CBM-N->PJM
CBM
54.028
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.624
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.189
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.03
VTFLTFEXP_VFT->PJM
CMTX
91.873
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.296
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.653

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.85 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3217.41
MW Contribution:
6.7
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200204Y1-065-CTG1
50/50
3.355
233918AB1-142 GEN
Solar/Wind Harmer
0.908
228206SHRMN CT
Adder
12.794
228260V4-054C
Solar/Wind Harmer
0.79
228729W2-030 C
Solar/Wind Harmer
0.439
219686LUMSOLAR_N C
Solar/Wind Harmer
0.15
219348LDSOLAR C
Solar/Wind Harmer
0.436
213611FALLS1-3
Adder
2.544
214194N WALES4
Adder
0.609
20720428HOL_W1-112
Solar/Wind Harmer
0.238
20635828PARLN1&2
Adder
5.042
20635028RRCT1&2
Adder
8.004
218524CNTRALGAS1 C
Solar/Wind Harmer
0.25
217209CENTRL HS C
Solar/Wind Harmer
0.03
20671828STAW2-080
Solar/Wind Harmer
0.069
207439AE1-081 C O1
Solar/Wind Harmer
0.039
207530AG1-191 GEN
Solar/Wind Harmer
0.884
211065PSPA IPP
Solar/Wind Harmer
0.271
961301AF2-421 GEN
Solar/Wind Harmer
0.572
963151AG1-164 GEN
Solar/Wind Harmer
0.572
961341AF2-425 GEN
Solar/Wind Harmer
0.535
232921TASLEY2G
Adder
4.773
233972AC1-094 C
Solar/Wind Harmer
1.987
233950AC2-186 GEN
Solar/Wind Harmer
0.519
228711V2-041C
Solar/Wind Harmer
0.464
213497CHSTR7-9
Adder
2.092
219921AF1-264
Solar/Wind Harmer
0.108
218660EHAMPSOLAR C
Solar/Wind Harmer
0.13
219914AD2-027 C
Solar/Wind Harmer
0.446
200194DELTA CT3
50/50
1.637
233998TM1NIN_3.36
Solar/Wind Harmer
0.922
232404W1-003 C
Solar/Wind Harmer
0.924
232919VN10
Adder
2.595
233970AC1-092 C
Solar/Wind Harmer
2.474
232900DEMECSMY
Adder
8.514
231917EM10
Adder
2.089
970997AG2-616 GEN
Solar/Wind Harmer
7.363
213497CHSTR7-9
Adder
2.092
213497CHSTR7-9
Adder
2.092
213560DLW11-12
Adder
2.015
219222BRL12CT2
Adder
6.508
20717128DIX_Z2-102
Solar/Wind Harmer
0.941
20715828PEM_W1-120
Solar/Wind Harmer
0.381
963711AG1-223 GEN
Solar/Wind Harmer
1.036
219276PARKLANDSO C
Solar/Wind Harmer
0.323
20715228NPK_W1-113
Solar/Wind Harmer
0.297
20720528MAN_W1-024
Solar/Wind Harmer
0.176
219919AE1-041 FULL
Solar/Wind Harmer
0.027
217121ECCF
Adder
0.288
20676728BRNX1-095
Solar/Wind Harmer
0.115
20676328BVR_Y1-020
Solar/Wind Harmer
0.213
20674928WA_W3-044
Solar/Wind Harmer
0.306
971519AH1-257 GEN
Solar/Wind Harmer
1.596
207518AF1-320_GEN
Solar/Wind Harmer
2.303
20465127PORT CT
Adder
1.882
20465527S.RDG CT
Adder
1.478
972281AH1-725 GEN
50/50
140.974
200201DELTA2 CT2
50/50
2.929
232410W1-006 C
Solar/Wind Harmer
0.924
233946AB2-136 GEN
Solar/Wind Harmer
3.686
233952AC2-187 GEN
Solar/Wind Harmer
1.038
233954AC2-188 GEN
Solar/Wind Harmer
1.038
232899W1-062
Adder
8.876
233984AB2-036 GEN
Solar/Wind Harmer
11.477
233930AB2-032 GEN
Solar/Wind Harmer
0.764
233982AB2-133 GEN
Solar/Wind Harmer
4.466
230511AF1-262
Solar/Wind Harmer
0.14
213587EDDYSTN3
Adder
61.027
228307PCLP GT
Adder
9.242
228754AB1-001 C
Solar/Wind Harmer
0.106
219272CLEANLIGHT C
Solar/Wind Harmer
0.136
217081WEATEXAS C
Solar/Wind Harmer
0.057
217083KRNY_132
Adder
6.116
207471AF2-354 C
Solar/Wind Harmer
0.325
20675928HOL_W4-097
Solar/Wind Harmer
0.082
209010PEIP 1
Adder
2.034
209010PEIP 1
Adder
0.298
961541AF2-445A GEN
Solar/Wind Harmer
1.779
961431AF2-434 GEN
Solar/Wind Harmer
0.533
232432Z2-076 GEN
Solar/Wind Harmer
0.122
232904IR4
Adder
74.738
233968AD2-076_GEN
Solar/Wind Harmer
6.099
231919CHRIST1
Adder
3.943
231920CHRIST2
Adder
3.855
230430AE1-229_GEN
Solar/Wind Harmer
21.968
230422AE1-104_GEN1
Solar/Wind Harmer
25.798
230425AE1-104_GEN2
Solar/Wind Harmer
25.798
230407AD2-065 C
Solar/Wind Harmer
0.1
20720728JCB_W1-129
Solar/Wind Harmer
0.213
207500AE2-000G1
Solar/Wind Harmer
22.403
970025AG2-016 GEN
Solar/Wind Harmer
2.009
20714428HOW_X1-037
Solar/Wind Harmer
0.857
218449LINSOLAR C
Solar/Wind Harmer
0.672
217147KRNY_1212
Adder
5.854
217147KRNY_1212
Adder
5.75
217146KRNY_1234
Adder
5.737
217146KRNY_1234
Adder
5.697
964851AG1-348 GEN
Solar/Wind Harmer
0.866
232912OH NUG1
Adder
8.167
971195AH1-057 GEN
Solar/Wind Harmer
0.901
233955AB2-172 GEN
Solar/Wind Harmer
4.62
232813VAUGHN
Adder
0.543
231902DC CT7
Adder
10.276
233915AB1-141 GEN
Solar/Wind Harmer
0.908
970453AG2-297 GEN
Solar/Wind Harmer
2.136
964001AG1-254 GEN
Solar/Wind Harmer
5.591
228728W1-130C
Solar/Wind Harmer
0.507
227927V4-067C
Solar/Wind Harmer
0.151
219137THOSOLAR C
Solar/Wind Harmer
0.911
219615MILLCREEK C
Solar/Wind Harmer
0.175
219224BRL12CT4
Adder
6.508
207487AE2-000G4
Solar/Wind Harmer
22.403
207497AE2-000G2
Solar/Wind Harmer
22.403
219620RIDERU C
Solar/Wind Harmer
0.039
20635928PARLN3&4
Adder
5.042
218526CNTRALGAS2 C
Solar/Wind Harmer
0.25
217167KRNY_14
Adder
6.155
971009AG2-626 GEN
Solar/Wind Harmer
1.038
961261AF2-417 GEN
Solar/Wind Harmer
0.59
212266LOR1
Solar/Wind Harmer
0.656
200034PCHBTM 2
50/50
17.072
200205Y1-065-CTG2
50/50
3.355
232428Y3-058 C
Solar/Wind Harmer
0.77
234015AF2-250 C
Solar/Wind Harmer
0.111
232424Y1-079 C
Solar/Wind Harmer
0.518
228251CARLLS#4
Adder
0.485
228351V2-046C
Solar/Wind Harmer
1.545
230433AD2-135 GEN
Solar/Wind Harmer
0.077
213589EDDYSTN4
Adder
61.041
219287REEVESEAST C
Solar/Wind Harmer
0.998
213535CROYDN11
Adder
7.454
214067T20SOLAR
Solar/Wind Harmer
0.182
20636128O CRK C2
Adder
4.583
207459AE1-142 C O1
Solar/Wind Harmer
0.745
20628028LAKEHURS
Adder
0.671
217197RE CRAN C
Solar/Wind Harmer
0.368
924131AB2-057 GEN
Solar/Wind Harmer
0.7
20635128RRCT3&4
Adder
7.607
20635128RRCT3&4
Adder
6.636
218419LINDEN_G6
Adder
11.534
20675428EAM_W2-061
Solar/Wind Harmer
0.126
219035LINDEN_G8
Adder
11.018
972237AH1-703 GEN
Adder
6.701
20465127PORT CT
Adder
2.498
20465527S.RDG CT
Adder
1.43
232406W1-004 FULL
Solar/Wind Harmer
0.924
232434Z2-077 GEN
Solar/Wind Harmer
0.231
233964AF2-378 GEN
Solar/Wind Harmer
0.118
232422X3-066 FULL
Solar/Wind Harmer
0.23
230415AB2-049 C
Solar/Wind Harmer
0.145
219291REEVESSOUT C
Solar/Wind Harmer
0.045
219236SOUTHERNHQ C
Solar/Wind Harmer
0.05
213815MOSER1-3
Adder
2.587
20714928UPF_X1-085
Solar/Wind Harmer
0.288
219114HARTZY_C
Solar/Wind Harmer
0.59
219918AC2-009 C
Solar/Wind Harmer
0.018
20674528F3S_W2-016
Solar/Wind Harmer
0.928
209025WIENIPP3
Adder
3.019
205941AD2-115 GEN
Solar/Wind Harmer
0.512
209142AF1-226 GEN
Solar/Wind Harmer
3.088
227287AC2-120 GEN
Solar/Wind Helper
0.356
232926CRISFLD1
Adder
1.815
231940T-011
Adder
0.689
234041AC1-190 GEN
Solar/Wind Harmer
8.277
228201CARL#2CT
Adder
5.291
228200CARL#1CT
Adder
5.032
219904AC1-010 C
Solar/Wind Harmer
0.282
219906AC1-017 C
Solar/Wind Harmer
0.163
213815MOSER1-3
Adder
2.587
213815MOSER1-3
Adder
2.587
20720828JCB_W4-025
Solar/Wind Harmer
0.323
20714828MDF_W3-079
Solar/Wind Harmer
0.214
219817TRENTONSOL C
Solar/Wind Harmer
0.767
20641628MLH_W1-032
Solar/Wind Harmer
0.203
20742028HF_AC1-207
Solar/Wind Harmer
0.541
218438BLK ROCK C
Solar/Wind Harmer
0.093
972260AH1-715 GEN1
Adder
9.236
972261AH1-715 GEN2
Adder
10.7
217202FBANKSOLAR C
Solar/Wind Harmer
0.049
217201HACKENSOLA C
Solar/Wind Harmer
0.049
217206BARNGR HS C
Solar/Wind Harmer
0.02
217204WCALDSOLAR C
Solar/Wind Harmer
0.048
20674828DL_W4-046
Solar/Wind Harmer
0.411
20634528N27_Y2-018
Solar/Wind Harmer
0.17
233987AB2-037 GEN
Solar/Wind Harmer
10.537
232907VN8
Adder
27.777
233923SMA
Solar/Wind Harmer
3.379
233997TMININ_4.2
Solar/Wind Harmer
0.922
232417X3-008 C
Solar/Wind Harmer
1.039
233973AC2-185 C
Solar/Wind Harmer
4.999
970695AG2-447 GEN
Solar/Wind Harmer
3.307
233935AB2-179 C
Solar/Wind Harmer
2.269
219221BRL12CT1
Adder
6.508
219223BRL12CT3
Adder
6.508
959561AF2-247 GEN
Solar/Wind Harmer
0.348
20715728PEM_W1-119
Solar/Wind Harmer
0.381
20636028O CRK C1
Adder
5.027
971667AH1-334 GEN
Solar/Wind Harmer
1.941
219727YARDVSOLFA C
Solar/Wind Harmer
0.641
20635828PARLN1&2
Adder
2.283
219249CENTRALDIV C
Solar/Wind Harmer
0.027
207442AE1-156 GEN
Solar/Wind Harmer
0.497
217211CAMDEN ST C
Solar/Wind Harmer
0.016
217194REDH C
Solar/Wind Harmer
0.326
207511W3-106 GEN
Solar/Wind Harmer
0.212
971007AG2-625 GEN
Solar/Wind Harmer
1.627
20466127PORT 5CT
Adder
16.611
20674128FR_U2-059
Solar/Wind Harmer
0.115
211065PSPA IPP
Solar/Wind Harmer
0.271
957921AF2-086 GEN
Solar/Wind Harmer
0.519
233996TM1833_GEN
Solar/Wind Harmer
0.922
232426Y1-080 FULL
Solar/Wind Harmer
0.177
234033AF1-007_GEN
Solar/Wind Harmer
34.381
232901NORTHST
Adder
7.688
232902EASTMUNI
Adder
12.032
234012AE2-112_GEN
Solar/Wind Harmer
2.116
231918WEST 1
Adder
3.001
972251AH1-710 GEN
Adder
40.035
228732V1-021 C
Adder
0.146
228400MICK 1CT
Adder
8.978
219766PARADISE C
Solar/Wind Harmer
0.235
20714528FRN_Y2-051
Solar/Wind Harmer
0.206
219680HOPEWELLV C1
Solar/Wind Harmer
0.053
218440SUMMTASSOC C
Solar/Wind Harmer
0.086
217208PARK ELE C
Solar/Wind Harmer
0.017
966261AG1-495 GEN
Solar/Wind Harmer
2.282
20674628WNG_W3-110
Solar/Wind Harmer
0.259
209023WIENIPP1
Adder
6.173
209025WIENIPP3
Adder
3.081
963071AG1-156 GEN
Solar/Wind Harmer
5.669
200200DELTA2 CT1
50/50
2.929
200193DELTA CT2
50/50
1.637
200203Y1-065-STG
50/50
5.811
200055ROCKSP 4
50/50
2.099
232914OH NUG3
Adder
8.167
232916OH NUG5
Adder
8.167
233939AC1-091 C
Solar/Wind Harmer
2.474
233933AB2-153 GEN
Solar/Wind Harmer
1.032
213958STHWK5-6
Adder
2.044
219623KINSLEYBEA C
Solar/Wind Harmer
0.32
20716428NHV_W2-082
Solar/Wind Harmer
1.269
963391AG1-188 GEN
Solar/Wind Harmer
2.657
219612MATRIX C
Solar/Wind Harmer
0.126
20716928W4-060COL
Solar/Wind Harmer
0.487
217213AMBOY SO C
Solar/Wind Harmer
0.085
20673728F2S_V4-070
Solar/Wind Harmer
0.12
207510AF2-138 C
Solar/Wind Harmer
1.145
207437AD2-070 GEN
Solar/Wind Harmer
0.19
20671928W4-073
Solar/Wind Harmer
0.271
20633028GILCT9
Adder
17.75
20465427SHAW CT
Adder
2.407
209116AE2-175 GEN
Solar/Wind Harmer
2.506
970095AG2-074 GEN
Solar/Wind Harmer
3.59
961421AF2-433 GEN
Solar/Wind Harmer
0.533
209093AE2-110 GEN
Solar/Wind Harmer
1.334
209120AE2-241 GEN
Solar/Wind Harmer
1.764
226910AB2-157 C
Solar/Wind Helper
0.014
3141196NOKESVL
Solar/Wind Helper
0.901
200202DELTA2 ST
50/50
4.96
200052ROCKSP 1
50/50
2.111
200053ROCKSP 2
50/50
2.07
233940AF2-379 C
Solar/Wind Harmer
0.172
230434AG1-499 GEN
Solar/Wind Harmer
0.442
213942SCHUYLKILL
Adder
2.677
213942SCHUYLKILL
Adder
2.047
213957STHWK3-4
Adder
2.044
213957STHWK3-4
Adder
2.044
219258KINSLEYDEP C
Solar/Wind Harmer
0.242
213561DLWR9-10
Adder
2.635
213561DLWR9-10
Adder
2.015
219610FLORENCE C
Solar/Wind Harmer
1.01
963401AG1-189 GEN
Solar/Wind Harmer
1.614
971189AH1-054 GEN
Solar/Wind Harmer
0.836
20716228APLW2-078
Solar/Wind Harmer
0.611
20673828FLE_V3-070
Solar/Wind Harmer
0.313
20676128MHD_W3-029
Solar/Wind Harmer
0.319
209027LOR2_Q27
Solar/Wind Harmer
2.477
3141426STAFORD
Solar/Wind Helper
0.05
200192DELTA CT1
50/50
1.637
200054ROCKSP 3
50/50
2.135
232408W1-005 C
Solar/Wind Harmer
0.924
232917OH NUG6
Adder
8.131
232915OH NUG4
Adder
8.113
972177AH1-672 GEN
Solar/Wind Harmer
12.412
233944AB2-135 GEN
Solar/Wind Harmer
4.805
213958STHWK5-6
Adder
2.044
219907AC1-030 C
Solar/Wind Harmer
0.103
20716028EGP_W2-019
Solar/Wind Harmer
0.331
207522AF2-254 C
Solar/Wind Harmer
1.024
218428ETC SOLAR C
Solar/Wind Harmer
0.024
219908AB1-139 C
Solar/Wind Harmer
0.257
972275AH1-722 GEN
Adder
21.203
20673628F1S_V4-069
Solar/Wind Harmer
0.12
207528AF2-192 GEN
Solar/Wind Harmer
0.85
217186ESSEX_G9
Adder
2.614
217083KRNY_132
Adder
6.155
20676228FRD_X1-012
Solar/Wind Harmer
0.38
20675828AU_W4-064
Solar/Wind Harmer
0.111
20675728RH_W2-091
Solar/Wind Harmer
0.38
207484AF2-139 C O1
Solar/Wind Harmer
0.318
208909MACR G3
Adder
98.632
209010PEIP 1
Adder
0.37
316415AF1-147_GEN2
Solar/Wind Helper
0.776
316411AF1-147_GEN1
Solar/Wind Helper
0.776
200195DELTA ST
50/50
2.528
233901CHERRYDALE C
Solar/Wind Harmer
1.04
232913OH NUG2
Adder
8.058
232920IR10
Adder
2.921
970597AG2-380 GEN
Solar/Wind Harmer
3.83
231906DC3 NUG
Adder
12.854
231907DC10
Adder
3.209
972141AH1-641 GEN
Solar/Wind Harmer
2.209
213611FALLS1-3
Adder
2.544
213611FALLS1-3
Adder
2.544
20715028HAN_X4-015
Solar/Wind Harmer
0.213
207507AE2-000G3
Solar/Wind Harmer
22.403
207445AB1-138_GEN
Solar/Wind Harmer
0.409
20720628TIN_W1-124
Solar/Wind Harmer
0.689
971521AH1-258 GEN
Solar/Wind Harmer
1.866
20675528CPH_W2-050
Solar/Wind Harmer
0.387
20676428JCR_X2-075
Solar/Wind Harmer
0.228
217086KRNY_131
Adder
6.103
20675128HRM_W1-127
Solar/Wind Harmer
0.107
209029WAYMART-WD
Solar/Wind Harmer
1.486
226929AD2-058 GEN
Solar/Wind Helper
0.102
3138216PACIFIC
Solar/Wind Helper
0.039
200035PCHBTM 3
50/50
16.97
232918OH NUG7
Adder
8.113
232905CHERITON_25
Adder
2.269
233994AC2-023 GEN
Solar/Wind Harmer
2.482
234036AF2-325 C
Solar/Wind Harmer
0.847
233971AC1-093 C
Solar/Wind Harmer
2.35
232910NRG_G1
Adder
7.954
234014AF1-036_GEN
Solar/Wind Harmer
2.489
232436AB1-176 C
Solar/Wind Harmer
0.211
972233AH1-701 GEN
Adder
3.192
219912AD2-042 GEN
Solar/Wind Harmer
0.592
219607WPEMNERT C
Solar/Wind Harmer
0.305
219304NAMERICA C
Solar/Wind Harmer
0.226
20635028RRCT1&2
Adder
7.881
218418LINDEN_G5
Adder
11.534
219036LINDEN_G7
Adder
11.177
217086KRNY_131
Adder
6.168
20674328GAR_V4-001
Solar/Wind Harmer
0.071
207408W3-077 C
Solar/Wind Harmer
0.319
20462827N BANGR8
Adder
0.448
209026WIENIPP4
Adder
3.05
20486527WR_V4-052
Adder
0.577
219688LUMSOLAR_S C
Solar/Wind Harmer
0.15
213560DLW11-12
Adder
2.015
207454AA2-184 E
Solar/Wind Harmer
0.692
20635928PARLN3&4
Adder
2.283
217169METRODIV C
Solar/Wind Harmer
0.026
963161AG1-165 GEN
Solar/Wind Harmer
0.572
208972BECR K09
Solar/Wind Harmer
0.599
961331AF2-424 GEN
Solar/Wind Harmer
0.535
G-007ALTFEXP_G-007A->PJM
CMTX
34.806
CBM NorthLTFEXP_CBM-N->PJM
CBM
50.284
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.93
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.138
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.123
VTFLTFEXP_VFT->PJM
CMTX
89.976
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.379
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.987

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o BG_P7_CNSTN_NWEST2_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
BG_P7_CNSTN_NWEST2_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.61 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3178.71
MW Contribution:
6.25
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972281AH1-725 GEN
50/50
123.888
200201DELTA2 CT2
50/50
2.13
232410W1-006 C
Solar/Wind Harmer
0.735
233946AB2-136 GEN
Solar/Wind Harmer
2.93
232899W1-062
Adder
7.061
233952AC2-187 GEN
Solar/Wind Harmer
0.826
233954AC2-188 GEN
Solar/Wind Harmer
0.826
233984AB2-036 GEN
Solar/Wind Harmer
9.131
233930AB2-032 GEN
Solar/Wind Harmer
0.609
233982AB2-133 GEN
Solar/Wind Harmer
3.56
230511AF1-262
Solar/Wind Harmer
0.118
228307PCLP GT
Adder
7.78
213587EDDYSTN3
Adder
51.233
228754AB1-001 C
Solar/Wind Harmer
0.089
200194DELTA CT3
50/50
1.19
233998TM1NIN_3.36
Solar/Wind Harmer
0.732
232404W1-003 C
Solar/Wind Harmer
0.735
232919VN10
Adder
2.062
233970AC1-092 C
Solar/Wind Harmer
1.969
232900DEMECSMY
Adder
6.773
231917EM10
Adder
1.69
970997AG2-616 GEN
Solar/Wind Harmer
6.182
213497CHSTR7-9
Adder
1.754
213497CHSTR7-9
Adder
1.754
213560DLW11-12
Adder
1.724
219222BRL12CT2
Adder
5.621
20717128DIX_Z2-102
Solar/Wind Harmer
0.824
20715828PEM_W1-120
Solar/Wind Harmer
0.333
963711AG1-223 GEN
Solar/Wind Harmer
0.92
219276PARKLANDSO C
Solar/Wind Harmer
0.287
20715228NPK_W1-113
Solar/Wind Harmer
0.267
20720528MAN_W1-024
Solar/Wind Harmer
0.158
219919AE1-041 FULL
Solar/Wind Harmer
0.025
217121ECCF
Adder
0.268
20676728BRNX1-095
Solar/Wind Harmer
0.109
20676328BVR_Y1-020
Solar/Wind Harmer
0.204
20674928WA_W3-044
Solar/Wind Harmer
0.298
971519AH1-257 GEN
Solar/Wind Harmer
1.561
207518AF1-320_GEN
Solar/Wind Harmer
2.263
20465127PORT CT
Adder
1.855
20465527S.RDG CT
Adder
1.698
208835TUHI V3-051
Solar/Wind Harmer
0.038
209018SUNBIPCT
Adder
4.224
200035PCHBTM 3
50/50
12.143
232918OH NUG7
Adder
6.447
232905CHERITON_25
Adder
1.803
233994AC2-023 GEN
Solar/Wind Harmer
1.972
234036AF2-325 C
Solar/Wind Harmer
0.673
233971AC1-093 C
Solar/Wind Harmer
1.869
232910NRG_G1
Adder
6.331
234014AF1-036_GEN
Solar/Wind Harmer
1.982
232436AB1-176 C
Solar/Wind Harmer
0.168
972233AH1-701 GEN
Adder
2.694
219912AD2-042 GEN
Solar/Wind Harmer
0.505
219607WPEMNERT C
Solar/Wind Harmer
0.264
219304NAMERICA C
Solar/Wind Harmer
0.195
20635028RRCT1&2
Adder
7.189
218418LINDEN_G5
Adder
10.628
219036LINDEN_G7
Adder
10.347
217086KRNY_131
Adder
5.758
20674328GAR_V4-001
Solar/Wind Harmer
0.068
946751AF1-339 GEN
Solar/Wind Harmer
0.568
200195DELTA ST
50/50
1.838
233901CHERRYDALE C
Solar/Wind Harmer
0.826
232913OH NUG2
Adder
6.404
232920IR10
Adder
2.322
970597AG2-380 GEN
Solar/Wind Harmer
3.05
231906DC3 NUG
Adder
10.24
231907DC10
Adder
2.556
972141AH1-641 GEN
Solar/Wind Harmer
1.855
213611FALLS1-3
Adder
2.216
213611FALLS1-3
Adder
2.216
20715028HAN_X4-015
Solar/Wind Harmer
0.186
207507AE2-000G3
Solar/Wind Harmer
19.645
207445AB1-138_GEN
Solar/Wind Harmer
0.361
20720628TIN_W1-124
Solar/Wind Harmer
0.618
971521AH1-258 GEN
Solar/Wind Harmer
1.679
20675528CPH_W2-050
Solar/Wind Harmer
0.356
20676428JCR_X2-075
Solar/Wind Harmer
0.211
217086KRNY_131
Adder
5.697
20675128HRM_W1-127
Solar/Wind Harmer
0.105
209029WAYMART-WD
Solar/Wind Harmer
1.532
209030FRFA O01
Adder
0.166
959421AF2-233 GEN
Solar/Wind Harmer
0.567
226929AD2-058 GEN
Solar/Wind Helper
0.114
200204Y1-065-CTG1
50/50
2.474
233918AB1-142 GEN
Solar/Wind Harmer
0.724
200059HUNTR201
50/50
1.547
200060HUNTR301
50/50
1.547
200058HUNTR101
50/50
1.547
232904IR4
Adder
59.406
232432Z2-076 GEN
Solar/Wind Harmer
0.097
233968AD2-076_GEN
Solar/Wind Harmer
4.857
231919CHRIST1
Adder
3.179
231920CHRIST2
Adder
3.109
230430AE1-229_GEN
Solar/Wind Harmer
18.452
230422AE1-104_GEN1
Solar/Wind Harmer
21.702
230425AE1-104_GEN2
Solar/Wind Harmer
21.702
230407AD2-065 C
Solar/Wind Harmer
0.084
20720728JCB_W1-129
Solar/Wind Harmer
0.186
207500AE2-000G1
Solar/Wind Harmer
19.645
970025AG2-016 GEN
Solar/Wind Harmer
1.766
20714428HOW_X1-037
Solar/Wind Harmer
0.767
233996TM1833_GEN
Solar/Wind Harmer
0.732
234033AF1-007_GEN
Solar/Wind Harmer
27.328
232426Y1-080 FULL
Solar/Wind Harmer
0.14
232901NORTHST
Adder
6.114
232902EASTMUNI
Adder
9.566
234012AE2-112_GEN
Solar/Wind Harmer
1.685
972251AH1-710 GEN
Adder
32.338
231918WEST 1
Adder
2.418
228732V1-021 C
Adder
0.122
228400MICK 1CT
Adder
7.579
219766PARADISE C
Solar/Wind Harmer
0.2
20714528FRN_Y2-051
Solar/Wind Harmer
0.183
219680HOPEWELLV C1
Solar/Wind Harmer
0.047
218440SUMMTASSOC C
Solar/Wind Harmer
0.079
217208PARK ELE C
Solar/Wind Harmer
0.016
966261AG1-495 GEN
Solar/Wind Harmer
2.174
20674628WNG_W3-110
Solar/Wind Harmer
0.249
209023WIENIPP1
Adder
6.455
209025WIENIPP3
Adder
3.222
963071AG1-156 GEN
Solar/Wind Harmer
5.892
218449LINSOLAR C
Solar/Wind Harmer
0.622
217147KRNY_1212
Adder
5.466
217147KRNY_1212
Adder
5.368
217146KRNY_1234
Adder
5.356
217146KRNY_1234
Adder
5.319
964851AG1-348 GEN
Solar/Wind Harmer
0.845
207408W3-077 C
Solar/Wind Harmer
0.313
20462827N BANGR8
Adder
0.443
20486527WR_V4-052
Adder
0.661
209026WIENIPP4
Adder
3.19
209054AE2-059 GEN
Solar/Wind Harmer
0.966
200200DELTA2 CT1
50/50
2.13
200193DELTA CT2
50/50
1.19
200203Y1-065-STG
50/50
4.285
200055ROCKSP 4
50/50
1.547
200192DELTA CT1
50/50
1.19
200054ROCKSP 3
50/50
1.575
232408W1-005 C
Solar/Wind Harmer
0.735
232917OH NUG6
Adder
6.462
232915OH NUG4
Adder
6.447
972177AH1-672 GEN
Solar/Wind Harmer
9.868
233944AB2-135 GEN
Solar/Wind Harmer
3.829
213958STHWK5-6
Adder
1.735
219907AC1-030 C
Solar/Wind Harmer
0.088
20716028EGP_W2-019
Solar/Wind Harmer
0.29
207522AF2-254 C
Solar/Wind Harmer
0.896
218428ETC SOLAR C
Solar/Wind Harmer
0.022
219908AB1-139 C
Solar/Wind Harmer
0.236
972275AH1-722 GEN
Adder
19.539
20673628F1S_V4-069
Solar/Wind Harmer
0.111
207528AF2-192 GEN
Solar/Wind Harmer
0.787
217186ESSEX_G9
Adder
2.44
217083KRNY_132
Adder
5.746
20676228FRD_X1-012
Solar/Wind Harmer
0.365
20675828AU_W4-064
Solar/Wind Harmer
0.107
20675728RH_W2-091
Solar/Wind Harmer
0.373
207484AF2-139 C O1
Solar/Wind Harmer
0.313
208909MACR G3
Adder
98.264
209010PEIP 1
Adder
0.381
946731AF1-337 GEN
Solar/Wind Harmer
0.568
209008PAXT IPP
Adder
1.196
200202DELTA2 ST
50/50
3.607
200052ROCKSP 1
50/50
1.556
200053ROCKSP 2
50/50
1.526
233940AF2-379 C
Solar/Wind Harmer
0.137
230434AG1-499 GEN
Solar/Wind Harmer
0.372
219258KINSLEYDEP C
Solar/Wind Harmer
0.206
213942SCHUYLKILL
Adder
2.27
213942SCHUYLKILL
Adder
1.736
213957STHWK3-4
Adder
1.735
213957STHWK3-4
Adder
1.735
213561DLWR9-10
Adder
2.254
213561DLWR9-10
Adder
1.724
219610FLORENCE C
Solar/Wind Harmer
0.872
963401AG1-189 GEN
Solar/Wind Harmer
1.417
971189AH1-054 GEN
Solar/Wind Harmer
0.735
20716228APLW2-078
Solar/Wind Harmer
0.548
20673828FLE_V3-070
Solar/Wind Harmer
0.289
20676128MHD_W3-029
Solar/Wind Harmer
0.295
208862AG1-362 C
Solar/Wind Harmer
0.496
209027LOR2_Q27
Solar/Wind Harmer
2.665
964051AG1-259 GEN
Solar/Wind Harmer
0.761
964061AG1-260 GEN
Solar/Wind Harmer
0.761
219272CLEANLIGHT C
Solar/Wind Harmer
0.116
217081WEATEXAS C
Solar/Wind Harmer
0.053
217083KRNY_132
Adder
5.71
207471AF2-354 C
Solar/Wind Harmer
0.317
20675928HOL_W4-097
Solar/Wind Harmer
0.081
961541AF2-445A GEN
Solar/Wind Harmer
1.915
209010PEIP 1
Adder
2.097
209010PEIP 1
Adder
0.307
961431AF2-434 GEN
Solar/Wind Harmer
0.579
209130AF1-271A GEN
Solar/Wind Harmer
1.594
232914OH NUG3
Adder
6.491
232916OH NUG5
Adder
6.491
233939AC1-091 C
Solar/Wind Harmer
1.969
233933AB2-153 GEN
Solar/Wind Harmer
0.822
219623KINSLEYBEA C
Solar/Wind Harmer
0.272
213958STHWK5-6
Adder
1.735
20716428NHV_W2-082
Solar/Wind Harmer
1.11
963391AG1-188 GEN
Solar/Wind Harmer
2.336
219612MATRIX C
Solar/Wind Harmer
0.114
20716928W4-060COL
Solar/Wind Harmer
0.441
217213AMBOY SO C
Solar/Wind Harmer
0.078
20673728F2S_V4-070
Solar/Wind Harmer
0.111
207510AF2-138 C
Solar/Wind Harmer
1.1
207437AD2-070 GEN
Solar/Wind Harmer
0.187
20633028GILCT9
Adder
17.557
20671928W4-073
Solar/Wind Harmer
0.268
20465427SHAW CT
Adder
2.379
209116AE2-175 GEN
Solar/Wind Harmer
2.519
970095AG2-074 GEN
Solar/Wind Harmer
3.731
961421AF2-433 GEN
Solar/Wind Harmer
0.579
209093AE2-110 GEN
Solar/Wind Harmer
1.447
209120AE2-241 GEN
Solar/Wind Harmer
1.915
946691AF1-333 GEN
Solar/Wind Harmer
0.568
946741AF1-338 GEN
Solar/Wind Harmer
0.568
972221AH1-695 GEN
Adder
80.797
226910AB2-157 C
Solar/Wind Helper
0.017
232912OH NUG1
Adder
6.491
971195AH1-057 GEN
Solar/Wind Harmer
0.716
233955AB2-172 GEN
Solar/Wind Harmer
3.672
232813VAUGHN
Adder
0.432
231902DC CT7
Adder
8.186
233915AB1-141 GEN
Solar/Wind Harmer
0.724
970453AG2-297 GEN
Solar/Wind Harmer
1.785
964001AG1-254 GEN
Solar/Wind Harmer
4.696
228728W1-130C
Solar/Wind Harmer
0.427
227927V4-067C
Solar/Wind Harmer
0.127
219137THOSOLAR C
Solar/Wind Harmer
0.773
219615MILLCREEK C
Solar/Wind Harmer
0.15
219224BRL12CT4
Adder
5.621
207487AE2-000G4
Solar/Wind Harmer
19.645
207497AE2-000G2
Solar/Wind Harmer
19.645
219620RIDERU C
Solar/Wind Harmer
0.035
20635928PARLN3&4
Adder
4.586
218526CNTRALGAS2 C
Solar/Wind Harmer
0.229
217167KRNY_14
Adder
5.746
971009AG2-626 GEN
Solar/Wind Harmer
1.014
961261AF2-417 GEN
Solar/Wind Harmer
0.601
212266LOR1
Solar/Wind Harmer
0.706
959431AF2-234 GEN
Solar/Wind Harmer
1.134
200034PCHBTM 2
50/50
12.417
200205Y1-065-CTG2
50/50
2.474
200061HUNTR401
50/50
2.95
232428Y3-058 C
Solar/Wind Harmer
0.612
234015AF2-250 C
Solar/Wind Harmer
0.088
232424Y1-079 C
Solar/Wind Harmer
0.412
228251CARLLS#4
Adder
0.407
228351V2-046C
Solar/Wind Harmer
1.298
230433AD2-135 GEN
Solar/Wind Harmer
0.065
213589EDDYSTN4
Adder
51.238
219287REEVESEAST C
Solar/Wind Harmer
0.853
213535CROYDN11
Adder
6.441
214067T20SOLAR
Solar/Wind Harmer
0.158
20636128O CRK C2
Adder
4.019
207459AE1-142 C O1
Solar/Wind Harmer
0.657
20628028LAKEHURS
Adder
0.592
217197RE CRAN C
Solar/Wind Harmer
0.333
924131AB2-057 GEN
Solar/Wind Harmer
0.637
20635128RRCT3&4
Adder
6.939
20635128RRCT3&4
Adder
6.053
218419LINDEN_G6
Adder
10.628
20675428EAM_W2-061
Solar/Wind Harmer
0.117
219035LINDEN_G8
Adder
10.199
972237AH1-703 GEN
Adder
6.255
20465127PORT CT
Adder
2.461
20465527S.RDG CT
Adder
1.643
232921TASLEY2G
Adder
3.793
233972AC1-094 C
Solar/Wind Harmer
1.581
233950AC2-186 GEN
Solar/Wind Harmer
0.413
228711V2-041C
Solar/Wind Harmer
0.388
213497CHSTR7-9
Adder
1.754
219921AF1-264
Solar/Wind Harmer
0.092
218660EHAMPSOLAR C
Solar/Wind Harmer
0.111
219914AD2-027 C
Solar/Wind Harmer
0.381
219688LUMSOLAR_S C
Solar/Wind Harmer
0.128
213560DLW11-12
Adder
1.724
207454AA2-184 E
Solar/Wind Harmer
0.62
20635928PARLN3&4
Adder
2.077
217169METRODIV C
Solar/Wind Harmer
0.025
963161AG1-165 GEN
Solar/Wind Harmer
0.599
208972BECR K09
Solar/Wind Harmer
0.627
961331AF2-424 GEN
Solar/Wind Harmer
0.58
208835TUHI V3-051
Solar/Wind Harmer
0.038
209071AE2-133 GEN
Solar/Wind Harmer
0.96
228206SHRMN CT
Adder
10.712
228260V4-054C
Solar/Wind Harmer
0.662
228729W2-030 C
Solar/Wind Harmer
0.371
219686LUMSOLAR_N C
Solar/Wind Harmer
0.128
219348LDSOLAR C
Solar/Wind Harmer
0.377
213611FALLS1-3
Adder
2.216
214194N WALES4
Adder
0.533
20720428HOL_W1-112
Solar/Wind Harmer
0.214
20635828PARLN1&2
Adder
4.586
20635028RRCT1&2
Adder
7.301
218524CNTRALGAS1 C
Solar/Wind Harmer
0.229
217209CENTRL HS C
Solar/Wind Harmer
0.028
20671828STAW2-080
Solar/Wind Harmer
0.065
207439AE1-081 C O1
Solar/Wind Harmer
0.037
207530AG1-191 GEN
Solar/Wind Harmer
0.851
211065PSPA IPP
Solar/Wind Harmer
0.276
961301AF2-421 GEN
Solar/Wind Harmer
0.599
963151AG1-164 GEN
Solar/Wind Harmer
0.599
961341AF2-425 GEN
Solar/Wind Harmer
0.58
212507AE2-042_GEN
Solar/Wind Harmer
1.712
233987AB2-037 GEN
Solar/Wind Harmer
8.365
232907VN8
Adder
22.071
233923SMA
Solar/Wind Harmer
2.685
233997TMININ_4.2
Solar/Wind Harmer
0.732
232417X3-008 C
Solar/Wind Harmer
0.826
233973AC2-185 C
Solar/Wind Harmer
3.977
970695AG2-447 GEN
Solar/Wind Harmer
2.631
233935AB2-179 C
Solar/Wind Harmer
1.815
219221BRL12CT1
Adder
5.621
219223BRL12CT3
Adder
5.621
959561AF2-247 GEN
Solar/Wind Harmer
0.304
20715728PEM_W1-119
Solar/Wind Harmer
0.333
20636028O CRK C1
Adder
4.408
971667AH1-334 GEN
Solar/Wind Harmer
1.712
219727YARDVSOLFA C
Solar/Wind Harmer
0.567
20635828PARLN1&2
Adder
2.077
219249CENTRALDIV C
Solar/Wind Harmer
0.025
207442AE1-156 GEN
Solar/Wind Harmer
0.46
217211CAMDEN ST C
Solar/Wind Harmer
0.015
217194REDH C
Solar/Wind Harmer
0.304
207511W3-106 GEN
Solar/Wind Harmer
0.204
971007AG2-625 GEN
Solar/Wind Harmer
1.589
20674128FR_U2-059
Solar/Wind Harmer
0.114
20466127PORT 5CT
Adder
16.36
211065PSPA IPP
Solar/Wind Harmer
0.276
957921AF2-086 GEN
Solar/Wind Harmer
0.563
232926CRISFLD1
Adder
1.442
231940T-011
Adder
0.548
234041AC1-190 GEN
Solar/Wind Harmer
6.579
228201CARL#2CT
Adder
4.437
228200CARL#1CT
Adder
4.22
219904AC1-010 C
Solar/Wind Harmer
0.24
219906AC1-017 C
Solar/Wind Harmer
0.141
213815MOSER1-3
Adder
2.233
213815MOSER1-3
Adder
2.233
20720828JCB_W4-025
Solar/Wind Harmer
0.283
20714828MDF_W3-079
Solar/Wind Harmer
0.19
219817TRENTONSOL C
Solar/Wind Harmer
0.685
20641628MLH_W1-032
Solar/Wind Harmer
0.182
20742028HF_AC1-207
Solar/Wind Harmer
0.486
218438BLK ROCK C
Solar/Wind Harmer
0.084
972260AH1-715 GEN1
Adder
8.511
972261AH1-715 GEN2
Adder
9.904
217202FBANKSOLAR C
Solar/Wind Harmer
0.045
217201HACKENSOLA C
Solar/Wind Harmer
0.045
217206BARNGR HS C
Solar/Wind Harmer
0.019
217204WCALDSOLAR C
Solar/Wind Harmer
0.045
20674828DL_W4-046
Solar/Wind Harmer
0.399
20634528N27_Y2-018
Solar/Wind Harmer
0.166
232406W1-004 FULL
Solar/Wind Harmer
0.735
232434Z2-077 GEN
Solar/Wind Harmer
0.184
233964AF2-378 GEN
Solar/Wind Harmer
0.094
232422X3-066 FULL
Solar/Wind Harmer
0.183
230415AB2-049 C
Solar/Wind Harmer
0.122
219291REEVESSOUT C
Solar/Wind Harmer
0.038
219236SOUTHERNHQ C
Solar/Wind Harmer
0.043
213815MOSER1-3
Adder
2.233
20714928UPF_X1-085
Solar/Wind Harmer
0.253
219114HARTZY_C
Solar/Wind Harmer
0.52
219918AC2-009 C
Solar/Wind Harmer
0.016
20674528F3S_W2-016
Solar/Wind Harmer
0.872
205941AD2-115 GEN
Solar/Wind Harmer
0.567
209025WIENIPP3
Adder
3.157
209142AF1-226 GEN
Solar/Wind Harmer
3.351
227287AC2-120 GEN
Solar/Wind Helper
0.405
G-007ALTFEXP_G-007A->PJM
CMTX
31.752
CBM NorthLTFEXP_CBM-N->PJM
CBM
49.127
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.52
BlueGrassPJM->LTFIMP_BlueG
CLTF
7.862
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.778
VTFLTFEXP_VFT->PJM
CMTX
83.748
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.16
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
12.114

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.69 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:3150.34
MW Contribution:
6.65
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200204Y1-065-CTG1
50/50
3.41
233920W3-032A-CTG1
50/50
1.973
233918AB1-142 GEN
Solar/Wind Harmer
0.903
228206SHRMN CT
Adder
12.684
200194DELTA CT3
50/50
1.669
232919VN10
50/50
2.744
233998TM1NIN_3.36
Solar/Wind Harmer
0.918
232404W1-003 C
Solar/Wind Harmer
0.921
233970AC1-092 C
Solar/Wind Harmer
2.469
232900DEMECSMY
Adder
8.49
231917EM10
Adder
2.058
970997AG2-616 GEN
Solar/Wind Harmer
7.285
213497CHSTR7-9
Adder
2.026
213497CHSTR7-9
Adder
2.026
213560DLW11-12
Adder
1.97
219222BRL12CT2
Adder
6.417
20717128DIX_Z2-102
Solar/Wind Harmer
0.932
20715828PEM_W1-120
Solar/Wind Harmer
0.377
963711AG1-223 GEN
Solar/Wind Harmer
1.026
219276PARKLANDSO C
Solar/Wind Harmer
0.319
20715228NPK_W1-113
Solar/Wind Harmer
0.295
20720528MAN_W1-024
Solar/Wind Harmer
0.174
219919AE1-041 FULL
Solar/Wind Harmer
0.027
217121ECCF
Adder
0.285
20676728BRNX1-095
Solar/Wind Harmer
0.114
20676328BVR_Y1-020
Solar/Wind Harmer
0.211
20674928WA_W3-044
Solar/Wind Harmer
0.304
971519AH1-257 GEN
Solar/Wind Harmer
1.584
207518AF1-320_GEN
Solar/Wind Harmer
2.286
20465127PORT CT
Adder
1.869
20465527S.RDG CT
Adder
1.473
232912OH NUG1
50/50
8.637
971195AH1-057 GEN
Solar/Wind Harmer
0.898
233955AB2-172 GEN
Solar/Wind Harmer
4.602
232813VAUGHN
Adder
0.541
231902DC CT7
Adder
10.215
233915AB1-141 GEN
Solar/Wind Harmer
0.903
970453AG2-297 GEN
Solar/Wind Harmer
2.118
964001AG1-254 GEN
Solar/Wind Harmer
5.529
228728W1-130C
Solar/Wind Harmer
0.502
227927V4-067C
Solar/Wind Harmer
0.149
219137THOSOLAR C
Solar/Wind Harmer
0.897
219615MILLCREEK C
Solar/Wind Harmer
0.172
219224BRL12CT4
Adder
6.417
207487AE2-000G4
Solar/Wind Harmer
22.203
207497AE2-000G2
Solar/Wind Harmer
22.203
219620RIDERU C
Solar/Wind Harmer
0.038
20635928PARLN3&4
Adder
4.999
218526CNTRALGAS2 C
Solar/Wind Harmer
0.248
217167KRNY_14
Adder
6.105
971009AG2-626 GEN
Solar/Wind Harmer
1.03
961261AF2-417 GEN
Solar/Wind Harmer
0.587
212266LOR1
Solar/Wind Harmer
0.654
200034PCHBTM 2
50/50
17.405
200205Y1-065-CTG2
50/50
3.41
234015AF2-250 C
Solar/Wind Harmer
0.111
232428Y3-058 C
Solar/Wind Harmer
0.768
234034AF2-060
50/50
1.727
233921W3-032A-STG1
50/50
1.275
232406W1-004 FULL
Solar/Wind Harmer
0.921
232434Z2-077 GEN
Solar/Wind Harmer
0.23
233964AF2-378 GEN
Solar/Wind Harmer
0.117
232422X3-066 FULL
Solar/Wind Harmer
0.228
230415AB2-049 C
Solar/Wind Harmer
0.143
219291REEVESSOUT C
Solar/Wind Harmer
0.044
219236SOUTHERNHQ C
Solar/Wind Harmer
0.049
213815MOSER1-3
Adder
2.537
20714928UPF_X1-085
Solar/Wind Harmer
0.285
219114HARTZY_C
Solar/Wind Harmer
0.583
219918AC2-009 C
Solar/Wind Harmer
0.018
20674528F3S_W2-016
Solar/Wind Harmer
0.919
209025WIENIPP3
Adder
3.004
205941AD2-115 GEN
Solar/Wind Harmer
0.51
209142AF1-226 GEN
Solar/Wind Harmer
3.076
227287AC2-120 GEN
Solar/Wind Helper
0.351
232926CRISFLD1
50/50
1.919
231940T-011
Adder
0.687
234041AC1-190 GEN
Solar/Wind Harmer
8.246
228201CARL#2CT
Adder
5.239
228200CARL#1CT
Adder
4.983
219904AC1-010 C
Solar/Wind Harmer
0.278
219906AC1-017 C
Solar/Wind Harmer
0.161
213815MOSER1-3
Adder
2.537
213815MOSER1-3
Adder
2.537
20720828JCB_W4-025
Solar/Wind Harmer
0.32
20714828MDF_W3-079
Solar/Wind Harmer
0.212
219817TRENTONSOL C
Solar/Wind Harmer
0.759
20641628MLH_W1-032
Solar/Wind Harmer
0.201
20742028HF_AC1-207
Solar/Wind Harmer
0.536
218438BLK ROCK C
Solar/Wind Harmer
0.092
972260AH1-715 GEN1
Adder
9.158
972261AH1-715 GEN2
Adder
10.611
217202FBANKSOLAR C
Solar/Wind Harmer
0.048
217201HACKENSOLA C
Solar/Wind Harmer
0.048
217206BARNGR HS C
Solar/Wind Harmer
0.02
217204WCALDSOLAR C
Solar/Wind Harmer
0.048
20674828DL_W4-046
Solar/Wind Harmer
0.408
20634528N27_Y2-018
Solar/Wind Harmer
0.169
231914HR8
50/50
2.016
232907VN8
50/50
29.37
232911NRG_G2
50/50
0.46
233987AB2-037 GEN
Solar/Wind Harmer
10.497
233923SMA
Solar/Wind Harmer
3.368
233997TMININ_4.2
Solar/Wind Harmer
0.918
233973AC2-185 C
Solar/Wind Harmer
4.987
970695AG2-447 GEN
Solar/Wind Harmer
3.299
232417X3-008 C
Solar/Wind Harmer
1.035
233935AB2-179 C
Solar/Wind Harmer
2.248
219221BRL12CT1
Adder
6.417
219223BRL12CT3
Adder
6.417
959561AF2-247 GEN
Solar/Wind Harmer
0.344
20715728PEM_W1-119
Solar/Wind Harmer
0.377
20636028O CRK C1
Adder
4.982
971667AH1-334 GEN
Solar/Wind Harmer
1.923
219727YARDVSOLFA C
Solar/Wind Harmer
0.634
20635828PARLN1&2
Adder
2.264
219249CENTRALDIV C
Solar/Wind Harmer
0.026
207442AE1-156 GEN
Solar/Wind Harmer
0.492
217211CAMDEN ST C
Solar/Wind Harmer
0.016
217194REDH C
Solar/Wind Harmer
0.323
207511W3-106 GEN
Solar/Wind Harmer
0.211
971007AG2-625 GEN
Solar/Wind Harmer
1.615
20466127PORT 5CT
Adder
16.497
20674128FR_U2-059
Solar/Wind Harmer
0.115
211065PSPA IPP
Solar/Wind Harmer
0.27
957921AF2-086 GEN
Solar/Wind Harmer
0.517
233996TM1833_GEN
Solar/Wind Harmer
0.918
234033AF1-007_GEN
Solar/Wind Harmer
34.273
232901NORTHST
Adder
7.669
232426Y1-080 FULL
Solar/Wind Harmer
0.176
232902EASTMUNI
Adder
11.979
234012AE2-112_GEN
Solar/Wind Harmer
2.104
972251AH1-710 GEN
Adder
39.968
231918WEST 1
Adder
2.961
228732V1-021 C
Adder
0.144
228400MICK 1CT
Adder
8.855
219766PARADISE C
Solar/Wind Harmer
0.231
20714528FRN_Y2-051
Solar/Wind Harmer
0.205
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
218440SUMMTASSOC C
Solar/Wind Harmer
0.086
217208PARK ELE C
Solar/Wind Harmer
0.017
966261AG1-495 GEN
Solar/Wind Harmer
2.262
20674628WNG_W3-110
Solar/Wind Harmer
0.257
209023WIENIPP1
Adder
6.142
209025WIENIPP3
Adder
3.066
963071AG1-156 GEN
Solar/Wind Harmer
5.641
200200DELTA2 CT1
50/50
2.986
200193DELTA CT2
50/50
1.669
200203Y1-065-STG
50/50
5.906
200055ROCKSP 4
50/50
2.133
231911HR5
50/50
1.326
232914OH NUG3
50/50
8.637
232916OH NUG5
50/50
8.637
233939AC1-091 C
Solar/Wind Harmer
2.469
233933AB2-153 GEN
Solar/Wind Harmer
1.026
219623KINSLEYBEA C
Solar/Wind Harmer
0.316
213958STHWK5-6
Adder
1.988
20716428NHV_W2-082
Solar/Wind Harmer
1.256
963391AG1-188 GEN
Solar/Wind Harmer
2.633
200202DELTA2 ST
50/50
5.057
200052ROCKSP 1
50/50
2.146
200053ROCKSP 2
50/50
2.104
232616GEN FOOD
50/50
0.159
233940AF2-379 C
Solar/Wind Harmer
0.172
230434AG1-499 GEN
Solar/Wind Harmer
0.437
219258KINSLEYDEP C
Solar/Wind Harmer
0.239
213942SCHUYLKILL
Adder
2.602
213942SCHUYLKILL
Adder
1.989
213957STHWK3-4
Adder
1.988
213957STHWK3-4
Adder
1.988
213561DLWR9-10
Adder
2.576
213561DLWR9-10
Adder
1.97
219610FLORENCE C
Solar/Wind Harmer
0.996
963401AG1-189 GEN
Solar/Wind Harmer
1.599
971189AH1-054 GEN
Solar/Wind Harmer
0.828
20716228APLW2-078
Solar/Wind Harmer
0.606
20673828FLE_V3-070
Solar/Wind Harmer
0.31
20676128MHD_W3-029
Solar/Wind Harmer
0.316
209027LOR2_Q27
Solar/Wind Harmer
2.466
3141426STAFORD
Solar/Wind Helper
0.049
200192DELTA CT1
50/50
1.669
200054ROCKSP 3
50/50
2.17
231912HR6
50/50
1.326
231913HR7
50/50
1.326
232917OH NUG6
50/50
8.599
232915OH NUG4
50/50
8.58
232408W1-005 C
Solar/Wind Harmer
0.921
972177AH1-672 GEN
Solar/Wind Harmer
12.374
233944AB2-135 GEN
Solar/Wind Harmer
4.777
213958STHWK5-6
Adder
1.988
219907AC1-030 C
Solar/Wind Harmer
0.101
20716028EGP_W2-019
Solar/Wind Harmer
0.328
207522AF2-254 C
Solar/Wind Harmer
1.014
218428ETC SOLAR C
Solar/Wind Harmer
0.024
219908AB1-139 C
Solar/Wind Harmer
0.254
972275AH1-722 GEN
Adder
21.024
20673628F1S_V4-069
Solar/Wind Harmer
0.119
207528AF2-192 GEN
Solar/Wind Harmer
0.842
217186ESSEX_G9
Adder
2.593
217083KRNY_132
Adder
6.105
20676228FRD_X1-012
Solar/Wind Harmer
0.377
20675828AU_W4-064
Solar/Wind Harmer
0.11
20675728RH_W2-091
Solar/Wind Harmer
0.377
207484AF2-139 C O1
Solar/Wind Harmer
0.316
208909MACR G3
Adder
97.98
209010PEIP 1
Adder
0.368
316415AF1-147_GEN2
Solar/Wind Helper
0.765
972281AH1-725 GEN
50/50
142.643
200201DELTA2 CT2
50/50
2.986
232410W1-006 C
Solar/Wind Harmer
0.921
233946AB2-136 GEN
Solar/Wind Harmer
3.672
232899W1-062
Adder
8.852
233952AC2-187 GEN
Solar/Wind Harmer
1.035
233954AC2-188 GEN
Solar/Wind Harmer
1.035
233984AB2-036 GEN
Solar/Wind Harmer
11.421
233930AB2-032 GEN
Solar/Wind Harmer
0.76
233982AB2-133 GEN
Solar/Wind Harmer
4.439
230511AF1-262
Solar/Wind Harmer
0.139
228307PCLP GT
Adder
9.126
228754AB1-001 C
Solar/Wind Harmer
0.105
213587EDDYSTN3
Adder
59.094
219272CLEANLIGHT C
Solar/Wind Harmer
0.134
217081WEATEXAS C
Solar/Wind Harmer
0.057
217083KRNY_132
Adder
6.066
207471AF2-354 C
Solar/Wind Harmer
0.323
20675928HOL_W4-097
Solar/Wind Harmer
0.082
209010PEIP 1
Adder
2.024
209010PEIP 1
Adder
0.296
961541AF2-445A GEN
Solar/Wind Harmer
1.772
961431AF2-434 GEN
Solar/Wind Harmer
0.531
316411AF1-147_GEN1
Solar/Wind Helper
0.765
200195DELTA ST
50/50
2.578
232913OH NUG2
50/50
8.522
233901CHERRYDALE C
Solar/Wind Harmer
1.036
232920IR10
Adder
2.912
970597AG2-380 GEN
Solar/Wind Harmer
3.809
231906DC3 NUG
Adder
12.777
231907DC10
Adder
3.19
972141AH1-641 GEN
Solar/Wind Harmer
2.186
213611FALLS1-3
Adder
2.508
213611FALLS1-3
Adder
2.508
20715028HAN_X4-015
Solar/Wind Harmer
0.211
207507AE2-000G3
Solar/Wind Harmer
22.203
207445AB1-138_GEN
Solar/Wind Harmer
0.405
20720628TIN_W1-124
Solar/Wind Harmer
0.683
971521AH1-258 GEN
Solar/Wind Harmer
1.85
20675528CPH_W2-050
Solar/Wind Harmer
0.383
20676428JCR_X2-075
Solar/Wind Harmer
0.226
217086KRNY_131
Adder
6.053
20675128HRM_W1-127
Solar/Wind Harmer
0.106
209029WAYMART-WD
Solar/Wind Harmer
1.478
226929AD2-058 GEN
Solar/Wind Helper
0.1
3138216PACIFIC
Solar/Wind Helper
0.038
200035PCHBTM 3
50/50
17.342
232918OH NUG7
50/50
8.58
232905CHERITON_25
50/50
2.399
232910NRG_G1
50/50
8.406
233994AC2-023 GEN
Solar/Wind Harmer
2.473
233971AC1-093 C
Solar/Wind Harmer
2.344
234036AF2-325 C
Solar/Wind Harmer
0.844
234014AF1-036_GEN
Solar/Wind Harmer
2.476
232436AB1-176 C
Solar/Wind Harmer
0.209
972233AH1-701 GEN
Adder
3.149
219912AD2-042 GEN
Solar/Wind Harmer
0.582
219607WPEMNERT C
Solar/Wind Harmer
0.301
219304NAMERICA C
Solar/Wind Harmer
0.223
20635028RRCT1&2
Adder
7.814
218418LINDEN_G5
Adder
11.436
219036LINDEN_G7
Adder
11.085
217086KRNY_131
Adder
6.118
20674328GAR_V4-001
Solar/Wind Harmer
0.07
232424Y1-079 C
Solar/Wind Harmer
0.515
228251CARLLS#4
Adder
0.481
228351V2-046C
Solar/Wind Harmer
1.528
230433AD2-135 GEN
Solar/Wind Harmer
0.077
213589EDDYSTN4
Adder
59.105
219287REEVESEAST C
Solar/Wind Harmer
0.987
213535CROYDN11
Adder
7.346
214067T20SOLAR
Solar/Wind Harmer
0.179
20636128O CRK C2
Adder
4.542
207459AE1-142 C O1
Solar/Wind Harmer
0.738
20628028LAKEHURS
Adder
0.665
217197RE CRAN C
Solar/Wind Harmer
0.365
924131AB2-057 GEN
Solar/Wind Harmer
0.693
20635128RRCT3&4
Adder
7.542
20635128RRCT3&4
Adder
6.579
218419LINDEN_G6
Adder
11.436
219035LINDEN_G8
Adder
10.926
20675428EAM_W2-061
Solar/Wind Harmer
0.125
972237AH1-703 GEN
Adder
6.647
20465127PORT CT
Adder
2.48
20465527S.RDG CT
Adder
1.426
232904IR4
Adder
74.501
232432Z2-076 GEN
Solar/Wind Harmer
0.122
233968AD2-076_GEN
Solar/Wind Harmer
6.066
231919CHRIST1
Adder
3.889
231920CHRIST2
Adder
3.803
230430AE1-229_GEN
Solar/Wind Harmer
21.736
230422AE1-104_GEN1
Solar/Wind Harmer
25.577
230425AE1-104_GEN2
Solar/Wind Harmer
25.577
230407AD2-065 C
Solar/Wind Harmer
0.099
20720728JCB_W1-129
Solar/Wind Harmer
0.211
207500AE2-000G1
Solar/Wind Harmer
22.203
970025AG2-016 GEN
Solar/Wind Harmer
1.991
20714428HOW_X1-037
Solar/Wind Harmer
0.849
218449LINSOLAR C
Solar/Wind Harmer
0.666
217147KRNY_1212
Adder
5.807
217147KRNY_1212
Adder
5.703
217146KRNY_1234
Adder
5.69
217146KRNY_1234
Adder
5.652
964851AG1-348 GEN
Solar/Wind Harmer
0.859
207408W3-077 C
Solar/Wind Harmer
0.317
20462827N BANGR8
Adder
0.445
209026WIENIPP4
Adder
3.035
20486527WR_V4-052
Adder
0.575
219612MATRIX C
Solar/Wind Harmer
0.125
20716928W4-060COL
Solar/Wind Harmer
0.483
217213AMBOY SO C
Solar/Wind Harmer
0.084
20673728F2S_V4-070
Solar/Wind Harmer
0.119
207510AF2-138 C
Solar/Wind Harmer
1.136
207437AD2-070 GEN
Solar/Wind Harmer
0.188
20671928W4-073
Solar/Wind Harmer
0.269
20633028GILCT9
Adder
17.624
20465427SHAW CT
Adder
2.391
209116AE2-175 GEN
Solar/Wind Harmer
2.49
970095AG2-074 GEN
Solar/Wind Harmer
3.572
961421AF2-433 GEN
Solar/Wind Harmer
0.531
209093AE2-110 GEN
Solar/Wind Harmer
1.328
209120AE2-241 GEN
Solar/Wind Harmer
1.758
226910AB2-157 C
Solar/Wind Helper
0.014
228260V4-054C
Solar/Wind Harmer
0.782
228729W2-030 C
Solar/Wind Harmer
0.436
219686LUMSOLAR_N C
Solar/Wind Harmer
0.148
219348LDSOLAR C
Solar/Wind Harmer
0.43
213611FALLS1-3
Adder
2.508
214194N WALES4
Adder
0.6
20720428HOL_W1-112
Solar/Wind Harmer
0.236
20635828PARLN1&2
Adder
4.999
20635028RRCT1&2
Adder
7.936
218524CNTRALGAS1 C
Solar/Wind Harmer
0.247
217209CENTRL HS C
Solar/Wind Harmer
0.029
20671828STAW2-080
Solar/Wind Harmer
0.069
207439AE1-081 C O1
Solar/Wind Harmer
0.038
207530AG1-191 GEN
Solar/Wind Harmer
0.877
211065PSPA IPP
Solar/Wind Harmer
0.27
961301AF2-421 GEN
Solar/Wind Harmer
0.57
963151AG1-164 GEN
Solar/Wind Harmer
0.57
961341AF2-425 GEN
Solar/Wind Harmer
0.533
232921TASLEY2G
50/50
5.048
233972AC1-094 C
Solar/Wind Harmer
1.982
233950AC2-186 GEN
Solar/Wind Harmer
0.517
228711V2-041C
Solar/Wind Harmer
0.46
213497CHSTR7-9
Adder
2.026
219921AF1-264
Solar/Wind Harmer
0.106
218660EHAMPSOLAR C
Solar/Wind Harmer
0.128
219688LUMSOLAR_S C
Solar/Wind Harmer
0.148
219914AD2-027 C
Solar/Wind Harmer
0.439
213560DLW11-12
Adder
1.97
207454AA2-184 E
Solar/Wind Harmer
0.686
20635928PARLN3&4
Adder
2.264
217169METRODIV C
Solar/Wind Harmer
0.026
963161AG1-165 GEN
Solar/Wind Harmer
0.57
208972BECR K09
Solar/Wind Harmer
0.596
961331AF2-424 GEN
Solar/Wind Harmer
0.533
G-007ALTFEXP_G-007A->PJM
CMTX
34.511
CBM NorthLTFEXP_CBM-N->PJM
CBM
50.042
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.862
BlueGrassPJM->LTFIMP_BlueG
CLTF
8.924
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.048
VTFLTFEXP_VFT->PJM
CMTX
89.246
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.334
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
13.668

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_C_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4644.1
MW Contribution:
10.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232904IR4
Adder
152.888
232432Z2-076 GEN
Solar/Wind Harmer
0.249
233968AD2-076_GEN
Solar/Wind Harmer
12.392
231919CHRIST1
Adder
7.82
231920CHRIST2
Adder
7.647
230430AE1-229_GEN
Solar/Wind Harmer
40.959
230422AE1-104_GEN1
Solar/Wind Harmer
48.023
230425AE1-104_GEN2
Solar/Wind Harmer
48.023
230407AD2-065 C
Solar/Wind Harmer
0.185
20720728JCB_W1-129
Solar/Wind Harmer
0.368
207500AE2-000G1
Solar/Wind Harmer
38.529
970025AG2-016 GEN
Solar/Wind Harmer
3.437
20714428HOW_X1-037
Solar/Wind Harmer
1.414
218449LINSOLAR C
Solar/Wind Harmer
1.025
217147KRNY_1212
Adder
8.742
217147KRNY_1212
Adder
8.586
217146KRNY_1234
Adder
8.566
217146KRNY_1234
Adder
8.508
964851AG1-348 GEN
Solar/Wind Harmer
1.14
207408W3-077 C
Solar/Wind Harmer
0.414
20462827N BANGR8
Adder
0.568
209026WIENIPP4
Adder
3.161
238169AE2-226 GEN1
Solar/Wind Helper
0.573
238170AE2-226 GEN2
Solar/Wind Helper
0.573
315651AD1-115 GEN
Solar/Wind Helper
0.788
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.09
316059AD1-063 C
Solar/Wind Helper
0.229
313526AB2-022
Solar/Wind Helper
0.341
200204Y1-065-CTG1
50/50
7.742
233918AB1-142 GEN
Solar/Wind Harmer
1.84
228206SHRMN CT
Adder
24.016
228260V4-054C
Solar/Wind Harmer
1.477
228729W2-030 C
Solar/Wind Harmer
0.814
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
219348LDSOLAR C
Solar/Wind Harmer
0.771
213611FALLS1-3
Adder
4.418
214194N WALES4
Adder
1.05
20720428HOL_W1-112
Solar/Wind Harmer
0.387
20635828PARLN1&2
Adder
8.013
20635028RRCT1&2
Adder
12.64
218524CNTRALGAS1 C
Solar/Wind Harmer
0.39
217209CENTRL HS C
Solar/Wind Harmer
0.045
233987AB2-037 GEN
Solar/Wind Harmer
21.579
232907VN8
Adder
56.823
233923SMA
Solar/Wind Harmer
6.912
233997TMININ_4.2
Solar/Wind Harmer
1.885
232417X3-008 C
Solar/Wind Harmer
2.124
233973AC2-185 C
Solar/Wind Harmer
10.224
970695AG2-447 GEN
Solar/Wind Harmer
6.764
233935AB2-179 C
Solar/Wind Harmer
4.545
219221BRL12CT1
Adder
11.498
219223BRL12CT3
Adder
11.498
959561AF2-247 GEN
Solar/Wind Harmer
0.603
20715728PEM_W1-119
Solar/Wind Harmer
0.656
20636028O CRK C1
Adder
8.645
971667AH1-334 GEN
Solar/Wind Harmer
3.298
219727YARDVSOLFA C
Solar/Wind Harmer
1.084
20635828PARLN1&2
Adder
3.63
219249CENTRALDIV C
Solar/Wind Harmer
0.041
207442AE1-156 GEN
Solar/Wind Harmer
0.756
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217194REDH C
Solar/Wind Harmer
0.486
207511W3-106 GEN
Solar/Wind Harmer
0.293
971007AG2-625 GEN
Solar/Wind Harmer
2.14
20466127PORT 5CT
Adder
21.35
20674128FR_U2-059
Solar/Wind Harmer
0.147
211065PSPA IPP
Solar/Wind Harmer
0.315
3132273ORANGE
Solar/Wind Helper
0.046
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.348
3144536CHRHLND
Solar/Wind Helper
0.034
3142956BIRDNECK
Solar/Wind Helper
0.151
316305AF2-043 C
Solar/Wind Helper
0.301
316320Y1-086
Solar/Wind Helper
0.1
3146516WINFALL
Solar/Wind Helper
0.223
200201DELTA2 CT2
50/50
6.893
232410W1-006 C
Solar/Wind Harmer
1.891
233946AB2-136 GEN
Solar/Wind Harmer
7.536
232899W1-062
Adder
18.143
233952AC2-187 GEN
Solar/Wind Harmer
2.12
233954AC2-188 GEN
Solar/Wind Harmer
2.12
233984AB2-036 GEN
Solar/Wind Harmer
23.374
233930AB2-032 GEN
Solar/Wind Harmer
1.549
233982AB2-133 GEN
Solar/Wind Harmer
9.047
230511AF1-262
Solar/Wind Harmer
0.261
228307PCLP GT
Adder
17.145
200202DELTA2 ST
50/50
11.673
200052ROCKSP 1
50/50
4.871
200053ROCKSP 2
50/50
4.775
233940AF2-379 C
Solar/Wind Harmer
0.353
230434AG1-499 GEN
Solar/Wind Harmer
0.818
219258KINSLEYDEP C
Solar/Wind Harmer
0.441
213942SCHUYLKILL
Adder
4.854
213942SCHUYLKILL
Adder
3.712
213957STHWK3-4
Adder
3.704
213957STHWK3-4
Adder
3.704
213561DLWR9-10
Adder
4.719
213561DLWR9-10
Adder
3.609
219610FLORENCE C
Solar/Wind Harmer
1.784
963401AG1-189 GEN
Solar/Wind Harmer
2.766
971189AH1-054 GEN
Solar/Wind Harmer
1.429
20716228APLW2-078
Solar/Wind Harmer
1.003
20673828FLE_V3-070
Solar/Wind Harmer
0.481
20676128MHD_W3-029
Solar/Wind Harmer
0.485
3141426STAFORD
Solar/Wind Helper
0.051
316468AD1-105 GEN
Solar/Wind Helper
1.097
3141913WHIT STONE
Solar/Wind Helper
0.226
957831AF2-077 GEN
Solar/Wind Helper
0.304
315697AD1-025 GEN
Solar/Wind Helper
2.575
315839AE2-212 C
Solar/Wind Helper
0.303
316258AE1-075 C
Solar/Wind Helper
0.308
316316AC1-027 C
Solar/Wind Helper
0.354
232926CRISFLD1
Adder
3.713
231940T-011
Adder
1.41
234041AC1-190 GEN
Solar/Wind Harmer
16.918
228201CARL#2CT
Adder
9.896
228200CARL#1CT
Adder
9.412
219904AC1-010 C
Solar/Wind Harmer
0.511
219906AC1-017 C
Solar/Wind Harmer
0.29
213815MOSER1-3
Adder
4.565
213815MOSER1-3
Adder
4.565
20720828JCB_W4-025
Solar/Wind Harmer
0.559
20714828MDF_W3-079
Solar/Wind Harmer
0.358
219817TRENTONSOL C
Solar/Wind Harmer
1.268
20641628MLH_W1-032
Solar/Wind Harmer
0.334
20742028HF_AC1-207
Solar/Wind Harmer
0.885
218438BLK ROCK C
Solar/Wind Harmer
0.151
972260AH1-715 GEN1
Adder
14.243
972261AH1-715 GEN2
Adder
16.32
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
217206BARNGR HS C
Solar/Wind Harmer
0.03
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674828DL_W4-046
Solar/Wind Harmer
0.549
20634528N27_Y2-018
Solar/Wind Harmer
0.224
238147AE2-230_GEN1
Solar/Wind Helper
0.397
315976AC1-164 GENA
Solar/Wind Helper
2.917
316169AC1-164_GENC
Solar/Wind Helper
2.52
3142946ENON
Solar/Wind Helper
0.023
316294AC1-161 GEN
Solar/Wind Helper
4.111
316349AD2-085 GEN
Solar/Wind Helper
1.025
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.902
316433W1029_GEN2
Solar/Wind Helper
0.902
200195DELTA ST
50/50
5.95
233901CHERRYDALE C
Solar/Wind Harmer
2.127
232913OH NUG2
Adder
16.483
232920IR10
Adder
5.976
970597AG2-380 GEN
Solar/Wind Harmer
7.782
231906DC3 NUG
Adder
26.105
231907DC10
Adder
6.517
972141AH1-641 GEN
Solar/Wind Harmer
4.122
213611FALLS1-3
Adder
4.418
213611FALLS1-3
Adder
4.418
20715028HAN_X4-015
Solar/Wind Harmer
0.368
207507AE2-000G3
Solar/Wind Harmer
38.529
207445AB1-138_GEN
Solar/Wind Harmer
0.693
20720628TIN_W1-124
Solar/Wind Harmer
1.133
971521AH1-258 GEN
Solar/Wind Harmer
3.04
20675528CPH_W2-050
Solar/Wind Harmer
0.6
20676428JCR_X2-075
Solar/Wind Harmer
0.345
217086KRNY_131
Adder
9.113
20675128HRM_W1-127
Solar/Wind Harmer
0.136
209029WAYMART-WD
Solar/Wind Harmer
1.61
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.112
3141813NORNECK
Solar/Wind Helper
0.227
316233AE1-074 FULL
Solar/Wind Helper
0.345
957601AF2-054 GEN
Solar/Wind Helper
0.303
316018AA1-139 ULT2
Solar/Wind Helper
0.965
200200DELTA2 CT1
50/50
6.893
200193DELTA CT2
50/50
3.851
200203Y1-065-STG
50/50
13.408
200055ROCKSP 4
50/50
4.842
232914OH NUG3
Adder
16.706
232916OH NUG5
Adder
16.706
233939AC1-091 C
Solar/Wind Harmer
5.061
233933AB2-153 GEN
Solar/Wind Harmer
2.091
219623KINSLEYBEA C
Solar/Wind Harmer
0.583
213958STHWK5-6
Adder
3.704
20716428NHV_W2-082
Solar/Wind Harmer
2.192
963391AG1-188 GEN
Solar/Wind Harmer
4.545
219612MATRIX C
Solar/Wind Harmer
0.204
20716928W4-060COL
Solar/Wind Harmer
0.784
217213AMBOY SO C
Solar/Wind Harmer
0.132
20673728F2S_V4-070
Solar/Wind Harmer
0.182
207510AF2-138 C
Solar/Wind Harmer
1.581
207437AD2-070 GEN
Solar/Wind Harmer
0.243
20671928W4-073
Solar/Wind Harmer
0.345
20633028GILCT9
Adder
22.394
20465427SHAW CT
Adder
3.06
209116AE2-175 GEN
Solar/Wind Harmer
3.018
970095AG2-074 GEN
Solar/Wind Harmer
3.797
3141196NOKESVL
Solar/Wind Helper
0.957
316077AC2-138 C
Solar/Wind Helper
0.214
316484AD2-074 GEN
Solar/Wind Helper
0.438
316075AC2-137 C
Solar/Wind Helper
0.345
200035PCHBTM 3
50/50
40.545
232918OH NUG7
Adder
16.595
232905CHERITON_25
Adder
4.641
233994AC2-023 GEN
Solar/Wind Harmer
5.076
234036AF2-325 C
Solar/Wind Harmer
1.732
233971AC1-093 C
Solar/Wind Harmer
4.806
232910NRG_G1
Adder
16.207
234014AF1-036_GEN
Solar/Wind Harmer
5.058
232436AB1-176 C
Solar/Wind Harmer
0.427
972233AH1-701 GEN
Adder
5.893
219912AD2-042 GEN
Solar/Wind Harmer
1.067
219607WPEMNERT C
Solar/Wind Harmer
0.539
219304NAMERICA C
Solar/Wind Harmer
0.4
20635028RRCT1&2
Adder
12.446
218418LINDEN_G5
Adder
17.787
219036LINDEN_G7
Adder
17.049
217086KRNY_131
Adder
9.21
20674328GAR_V4-001
Solar/Wind Harmer
0.097
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.153
238149AF1-291A_GEN
Solar/Wind Helper
0.113
966871AG1-558 GEN
Solar/Wind Helper
0.306
315666AE1-190 GEN
Solar/Wind Helper
0.305
316156AD2-030 GEN
Solar/Wind Helper
0.342
316240AF1-291 C
Solar/Wind Helper
0.303
316313AB2-026
Solar/Wind Helper
0.343
316435W1029_GEN3
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
200034PCHBTM 2
50/50
40.156
200205Y1-065-CTG2
50/50
7.742
232428Y3-058 C
Solar/Wind Harmer
1.575
234015AF2-250 C
Solar/Wind Harmer
0.227
232424Y1-079 C
Solar/Wind Harmer
1.054
228251CARLLS#4
Adder
0.908
228351V2-046C
Solar/Wind Harmer
2.879
230433AD2-135 GEN
Solar/Wind Harmer
0.144
213589EDDYSTN4
Adder
112.532
219287REEVESEAST C
Solar/Wind Harmer
1.8
213535CROYDN11
Adder
13.157
214067T20SOLAR
Solar/Wind Harmer
0.316
20636128O CRK C2
Adder
7.882
207459AE1-142 C O1
Solar/Wind Harmer
1.266
20628028LAKEHURS
Adder
1.137
217197RE CRAN C
Solar/Wind Harmer
0.594
924131AB2-057 GEN
Solar/Wind Harmer
1.109
20635128RRCT3&4
Adder
12.014
20635128RRCT3&4
Adder
10.48
218419LINDEN_G6
Adder
17.787
219035LINDEN_G8
Adder
16.806
20675428EAM_W2-061
Solar/Wind Harmer
0.192
972237AH1-703 GEN
Adder
10.013
20465127PORT CT
Adder
3.204
316450AC1-158 RIC
Solar/Wind Helper
0.346
966001AG1-469 GEN
Solar/Wind Helper
0.246
238148AE2-230_GEN2
Solar/Wind Helper
0.397
316487AF1-042 GEN
Solar/Wind Helper
0.229
316033AB2-134 GEN
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.895
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316339AD2-160 GEN
Solar/Wind Helper
0.854
316388AE2-253 GEN
Solar/Wind Helper
0.854
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.894
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
200194DELTA CT3
50/50
3.851
233998TM1NIN_3.36
Solar/Wind Harmer
1.885
232404W1-003 C
Solar/Wind Harmer
1.891
232919VN10
Adder
5.307
233970AC1-092 C
Solar/Wind Harmer
5.061
232900DEMECSMY
Adder
17.402
231917EM10
Adder
4.123
970997AG2-616 GEN
Solar/Wind Harmer
13.739
213497CHSTR7-9
Adder
3.862
213497CHSTR7-9
Adder
3.862
213560DLW11-12
Adder
3.609
219222BRL12CT2
Adder
11.498
20717128DIX_Z2-102
Solar/Wind Harmer
1.624
20715828PEM_W1-120
Solar/Wind Harmer
0.656
963711AG1-223 GEN
Solar/Wind Harmer
1.734
219276PARKLANDSO C
Solar/Wind Harmer
0.538
20715228NPK_W1-113
Solar/Wind Harmer
0.488
20720528MAN_W1-024
Solar/Wind Harmer
0.288
219919AE1-041 FULL
Solar/Wind Harmer
0.042
217121ECCF
Adder
0.429
20676728BRNX1-095
Solar/Wind Harmer
0.166
20676328BVR_Y1-020
Solar/Wind Harmer
0.296
20674928WA_W3-044
Solar/Wind Harmer
0.407
971519AH1-257 GEN
Solar/Wind Harmer
2.093
207518AF1-320_GEN
Solar/Wind Harmer
2.977
20465127PORT CT
Adder
2.415
316044AC1-158 PL1
Solar/Wind Helper
1.298
3147666LOUISA
Solar/Wind Helper
0.921
238152AF2-075_GEN
Solar/Wind Helper
0.567
23777901MDS_W4-102
Solar/Wind Helper
0.144
316404AE1-155 C
Solar/Wind Helper
1.941
3138133OCRAN
Solar/Wind Helper
0.136
315662AE1-191 GEN
Solar/Wind Helper
1.219
316280AD1-041 GEN
Solar/Wind Helper
0.762
3143226MDLTHAN
Solar/Wind Helper
0.226
3142543TWELFTH
Solar/Wind Helper
0.022
316369SG1_INVT
Solar/Wind Helper
1.086
316381AD1-082 GEN
Solar/Wind Helper
1.164
319010AE1-072 C
Solar/Wind Helper
2.561
233996TM1833_GEN
Solar/Wind Harmer
1.885
234033AF1-007_GEN
Solar/Wind Harmer
70.332
232901NORTHST
Adder
15.731
232426Y1-080 FULL
Solar/Wind Harmer
0.361
232902EASTMUNI
Adder
24.554
234012AE2-112_GEN
Solar/Wind Harmer
4.299
972251AH1-710 GEN
Adder
80.133
231918WEST 1
Adder
5.957
228732V1-021 C
Adder
0.272
228400MICK 1CT
Adder
16.558
219766PARADISE C
Solar/Wind Harmer
0.425
20714528FRN_Y2-051
Solar/Wind Harmer
0.345
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
217208PARK ELE C
Solar/Wind Harmer
0.025
966261AG1-495 GEN
Solar/Wind Harmer
3.222
20674628WNG_W3-110
Solar/Wind Harmer
0.359
963071AG1-156 GEN
Solar/Wind Harmer
5.996
209023WIENIPP1
Adder
6.397
209025WIENIPP3
Adder
3.193
316447AC1-158 HLD
Solar/Wind Helper
2.856
316192AB2-158 GEN
Solar/Wind Helper
1.55
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.226
3141766HARMONY
Solar/Wind Helper
0.045
315975AC1-164 GENB
Solar/Wind Helper
0.086
3142433PROV 92
Solar/Wind Helper
0.904
3145336SMITFLD
Solar/Wind Helper
0.897
316375AC2-012 GEN
Solar/Wind Helper
0.59
3146456SLIGO L269
Solar/Wind Helper
0.224
200192DELTA CT1
50/50
3.851
200054ROCKSP 3
50/50
4.927
232408W1-005 C
Solar/Wind Harmer
1.891
232917OH NUG6
Adder
16.632
232915OH NUG4
Adder
16.595
972177AH1-672 GEN
Solar/Wind Harmer
25.383
233944AB2-135 GEN
Solar/Wind Harmer
9.744
213958STHWK5-6
Adder
3.704
219907AC1-030 C
Solar/Wind Harmer
0.184
20716028EGP_W2-019
Solar/Wind Harmer
0.573
207522AF2-254 C
Solar/Wind Harmer
1.768
218428ETC SOLAR C
Solar/Wind Harmer
0.038
219908AB1-139 C
Solar/Wind Harmer
0.399
972275AH1-722 GEN
Adder
32.699
20673628F1S_V4-069
Solar/Wind Harmer
0.182
207528AF2-192 GEN
Solar/Wind Harmer
1.293
217186ESSEX_G9
Adder
3.904
217083KRNY_132
Adder
9.191
20676228FRD_X1-012
Solar/Wind Harmer
0.523
20675828AU_W4-064
Solar/Wind Harmer
0.152
20675728RH_W2-091
Solar/Wind Harmer
0.493
207484AF2-139 C O1
Solar/Wind Harmer
0.409
208909MACR G3
Adder
122.298
209010PEIP 1
Adder
0.401
316415AF1-147_GEN2
Solar/Wind Helper
0.819
238175AF1-290_GEN
Solar/Wind Helper
0.128
964211AG1-282 GEN
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.176
315671AE2-027_GEN
Solar/Wind Helper
1.819
316072AD1-144
Solar/Wind Helper
0.256
20671828STAW2-080
Solar/Wind Harmer
0.103
207439AE1-081 C O1
Solar/Wind Harmer
0.054
207530AG1-191 GEN
Solar/Wind Harmer
1.213
211065PSPA IPP
Solar/Wind Harmer
0.315
961301AF2-421 GEN
Solar/Wind Harmer
0.593
963151AG1-164 GEN
Solar/Wind Harmer
0.593
316337AD2-073 GEN
Solar/Wind Helper
0.346
3141726DUNNSVL
Solar/Wind Helper
0.908
316132AB2-190 GEN1
Solar/Wind Helper
1.289
315773AC2-141 GEN
Solar/Wind Helper
4.837
316036AC1-147 C
Solar/Wind Helper
0.342
3146516WINFALL
Solar/Wind Helper
0.722
3146516WINFALL
Solar/Wind Helper
0.223
232921TASLEY2G
Adder
9.764
233972AC1-094 C
Solar/Wind Harmer
4.064
233950AC2-186 GEN
Solar/Wind Harmer
1.06
228711V2-041C
Solar/Wind Harmer
0.871
213497CHSTR7-9
Adder
3.862
219921AF1-264
Solar/Wind Harmer
0.196
218660EHAMPSOLAR C
Solar/Wind Harmer
0.235
219914AD2-027 C
Solar/Wind Harmer
0.805
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213560DLW11-12
Adder
3.609
207454AA2-184 E
Solar/Wind Harmer
1.137
20635928PARLN3&4
Adder
3.63
217169METRODIV C
Solar/Wind Harmer
0.039
963161AG1-165 GEN
Solar/Wind Harmer
0.593
208972BECR K09
Solar/Wind Harmer
0.618
3147666LOUISA
Solar/Wind Helper
0.529
3141906WESTMOR
Solar/Wind Helper
0.091
316458AB2-190 GEN2
Solar/Wind Helper
1.289
3144873MCLAUGH
Solar/Wind Helper
0.006
316246AF1-032 C
Solar/Wind Helper
0.256
316321Z2-027
Solar/Wind Helper
0.341
3146626S HERTFORD
Solar/Wind Helper
0.223
232912OH NUG1
Adder
16.706
971195AH1-057 GEN
Solar/Wind Harmer
1.843
233955AB2-172 GEN
Solar/Wind Harmer
9.442
232813VAUGHN
Adder
1.107
231902DC CT7
Adder
20.869
233915AB1-141 GEN
Solar/Wind Harmer
1.84
970453AG2-297 GEN
Solar/Wind Harmer
4.023
964001AG1-254 GEN
Solar/Wind Harmer
10.423
228728W1-130C
Solar/Wind Harmer
0.942
227927V4-067C
Solar/Wind Harmer
0.279
219137THOSOLAR C
Solar/Wind Harmer
1.666
219615MILLCREEK C
Solar/Wind Harmer
0.311
219224BRL12CT4
Adder
11.498
207487AE2-000G4
Solar/Wind Harmer
38.529
207497AE2-000G2
Solar/Wind Harmer
38.529
219620RIDERU C
Solar/Wind Harmer
0.064
20635928PARLN3&4
Adder
8.013
218526CNTRALGAS2 C
Solar/Wind Harmer
0.393
217167KRNY_14
Adder
9.191
971009AG2-626 GEN
Solar/Wind Harmer
1.365
961261AF2-417 GEN
Solar/Wind Harmer
0.67
3138133OCRAN
Solar/Wind Helper
0.068
3143873LANEXA
Solar/Wind Helper
0.136
3141873WAN 176
Solar/Wind Helper
0.045
316382AG1-145 C
Solar/Wind Helper
0.304
316159AE1-175 C
Solar/Wind Helper
0.343
316236AE1-162_GEN
Solar/Wind Helper
0.302
316405AF2-144 C
Solar/Wind Helper
0.257
3143316POE
Solar/Wind Helper
0.888
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
3145176PASQUOTANK
Solar/Wind Helper
0.138
213587EDDYSTN3
Adder
112.486
228754AB1-001 C
Solar/Wind Harmer
0.196
219272CLEANLIGHT C
Solar/Wind Harmer
0.246
217081WEATEXAS C
Solar/Wind Harmer
0.087
217083KRNY_132
Adder
9.132
207471AF2-354 C
Solar/Wind Harmer
0.433
20675928HOL_W4-097
Solar/Wind Harmer
0.106
209010PEIP 1
Adder
2.204
209010PEIP 1
Adder
0.323
316411AF1-147_GEN1
Solar/Wind Helper
0.819
235020AA1-095 C
Solar/Wind Helper
0.043
237061AD1-155 GEN
Solar/Wind Helper
1.429
316312AB1-027
Solar/Wind Helper
0.432
3143526WINTERP
Solar/Wind Helper
1.176
316185AD1-033 GEN
Solar/Wind Helper
1.056
238221AF1-254 C O1
Solar/Wind Helper
0.22
3144356SAPONY
Solar/Wind Helper
0.399
316315AB2-025 C
Solar/Wind Helper
0.34
232406W1-004 FULL
Solar/Wind Harmer
1.891
232434Z2-077 GEN
Solar/Wind Harmer
0.473
233964AF2-378 GEN
Solar/Wind Harmer
0.241
232422X3-066 FULL
Solar/Wind Harmer
0.466
230415AB2-049 C
Solar/Wind Harmer
0.269
219291REEVESSOUT C
Solar/Wind Harmer
0.081
219236SOUTHERNHQ C
Solar/Wind Harmer
0.089
213815MOSER1-3
Adder
4.565
20714928UPF_X1-085
Solar/Wind Harmer
0.49
219114HARTZY_C
Solar/Wind Harmer
1.002
219918AC2-009 C
Solar/Wind Harmer
0.029
20674528F3S_W2-016
Solar/Wind Harmer
1.358
209025WIENIPP3
Adder
3.128
966881AG1-559 GEN
Solar/Wind Helper
0.309
316473AC1-191 GEN
Solar/Wind Helper
1.387
3142946ENON
Solar/Wind Helper
0.075
3145336SMITFLD
Solar/Wind Helper
0.09
316017AA1-139 ULT1
Solar/Wind Helper
1.025
3146456SLIGO L269
Solar/Wind Helper
0.224
3145273HOLLAND
Solar/Wind Helper
0.167
G-007ALTFEXP_G-007A->PJM
CMTX
54.971
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.973
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.798
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.944
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.425
VTFLTFEXP_VFT->PJM
CMTX
135.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.24
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.424

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o BGE_P4_GRACETON_51_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
BGE_P4_GRACETON_51_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4644.06
MW Contribution:
10.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232904IR4
Adder
152.888
232432Z2-076 GEN
Solar/Wind Harmer
0.249
233968AD2-076_GEN
Solar/Wind Harmer
12.392
231919CHRIST1
Adder
7.82
231920CHRIST2
Adder
7.647
230430AE1-229_GEN
Solar/Wind Harmer
40.959
230422AE1-104_GEN1
Solar/Wind Harmer
48.023
230425AE1-104_GEN2
Solar/Wind Harmer
48.023
230407AD2-065 C
Solar/Wind Harmer
0.185
20720728JCB_W1-129
Solar/Wind Harmer
0.368
207500AE2-000G1
Solar/Wind Harmer
38.529
970025AG2-016 GEN
Solar/Wind Harmer
3.437
20714428HOW_X1-037
Solar/Wind Harmer
1.414
218449LINSOLAR C
Solar/Wind Harmer
1.025
217147KRNY_1212
Adder
8.742
217147KRNY_1212
Adder
8.586
217146KRNY_1234
Adder
8.566
217146KRNY_1234
Adder
8.508
964851AG1-348 GEN
Solar/Wind Harmer
1.14
207408W3-077 C
Solar/Wind Harmer
0.414
20462827N BANGR8
Adder
0.568
209026WIENIPP4
Adder
3.161
238169AE2-226 GEN1
Solar/Wind Helper
0.573
238170AE2-226 GEN2
Solar/Wind Helper
0.573
315651AD1-115 GEN
Solar/Wind Helper
0.788
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.09
316059AD1-063 C
Solar/Wind Helper
0.229
313526AB2-022
Solar/Wind Helper
0.341
233987AB2-037 GEN
Solar/Wind Harmer
21.579
232907VN8
Adder
56.823
233923SMA
Solar/Wind Harmer
6.912
233997TMININ_4.2
Solar/Wind Harmer
1.885
232417X3-008 C
Solar/Wind Harmer
2.124
233973AC2-185 C
Solar/Wind Harmer
10.224
970695AG2-447 GEN
Solar/Wind Harmer
6.764
233935AB2-179 C
Solar/Wind Harmer
4.545
219221BRL12CT1
Adder
11.498
219223BRL12CT3
Adder
11.498
959561AF2-247 GEN
Solar/Wind Harmer
0.603
20715728PEM_W1-119
Solar/Wind Harmer
0.656
20636028O CRK C1
Adder
8.645
971667AH1-334 GEN
Solar/Wind Harmer
3.298
219727YARDVSOLFA C
Solar/Wind Harmer
1.084
20635828PARLN1&2
Adder
3.63
219249CENTRALDIV C
Solar/Wind Harmer
0.041
207442AE1-156 GEN
Solar/Wind Harmer
0.756
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217194REDH C
Solar/Wind Harmer
0.486
207511W3-106 GEN
Solar/Wind Harmer
0.293
971007AG2-625 GEN
Solar/Wind Harmer
2.14
20466127PORT 5CT
Adder
21.35
20674128FR_U2-059
Solar/Wind Harmer
0.147
211065PSPA IPP
Solar/Wind Harmer
0.315
3132273ORANGE
Solar/Wind Helper
0.046
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.348
3144536CHRHLND
Solar/Wind Helper
0.034
3142956BIRDNECK
Solar/Wind Helper
0.151
316305AF2-043 C
Solar/Wind Helper
0.301
316320Y1-086
Solar/Wind Helper
0.1
3146516WINFALL
Solar/Wind Helper
0.223
200202DELTA2 ST
50/50
11.673
200052ROCKSP 1
50/50
4.871
200053ROCKSP 2
50/50
4.775
233940AF2-379 C
Solar/Wind Harmer
0.353
230434AG1-499 GEN
Solar/Wind Harmer
0.818
219258KINSLEYDEP C
Solar/Wind Harmer
0.441
213942SCHUYLKILL
Adder
4.854
213942SCHUYLKILL
Adder
3.712
213957STHWK3-4
Adder
3.704
213957STHWK3-4
Adder
3.704
213561DLWR9-10
Adder
4.719
213561DLWR9-10
Adder
3.609
219610FLORENCE C
Solar/Wind Harmer
1.784
963401AG1-189 GEN
Solar/Wind Harmer
2.766
971189AH1-054 GEN
Solar/Wind Harmer
1.429
20716228APLW2-078
Solar/Wind Harmer
1.003
20673828FLE_V3-070
Solar/Wind Harmer
0.481
20676128MHD_W3-029
Solar/Wind Harmer
0.485
3141426STAFORD
Solar/Wind Helper
0.051
316468AD1-105 GEN
Solar/Wind Helper
1.097
3141913WHIT STONE
Solar/Wind Helper
0.226
957831AF2-077 GEN
Solar/Wind Helper
0.304
315697AD1-025 GEN
Solar/Wind Helper
2.575
315839AE2-212 C
Solar/Wind Helper
0.303
316258AE1-075 C
Solar/Wind Helper
0.308
316316AC1-027 C
Solar/Wind Helper
0.354
232926CRISFLD1
Adder
3.713
231940T-011
Adder
1.41
234041AC1-190 GEN
Solar/Wind Harmer
16.918
228201CARL#2CT
Adder
9.896
228200CARL#1CT
Adder
9.412
219904AC1-010 C
Solar/Wind Harmer
0.511
219906AC1-017 C
Solar/Wind Harmer
0.29
213815MOSER1-3
Adder
4.565
213815MOSER1-3
Adder
4.565
20720828JCB_W4-025
Solar/Wind Harmer
0.559
20714828MDF_W3-079
Solar/Wind Harmer
0.358
219817TRENTONSOL C
Solar/Wind Harmer
1.268
20641628MLH_W1-032
Solar/Wind Harmer
0.334
20742028HF_AC1-207
Solar/Wind Harmer
0.885
218438BLK ROCK C
Solar/Wind Harmer
0.151
972260AH1-715 GEN1
Adder
14.243
972261AH1-715 GEN2
Adder
16.32
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
217206BARNGR HS C
Solar/Wind Harmer
0.03
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674828DL_W4-046
Solar/Wind Harmer
0.549
20634528N27_Y2-018
Solar/Wind Harmer
0.224
238147AE2-230_GEN1
Solar/Wind Helper
0.397
315976AC1-164 GENA
Solar/Wind Helper
2.917
316169AC1-164_GENC
Solar/Wind Helper
2.52
3142946ENON
Solar/Wind Helper
0.023
316294AC1-161 GEN
Solar/Wind Helper
4.111
316349AD2-085 GEN
Solar/Wind Helper
1.025
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.902
316433W1029_GEN2
Solar/Wind Helper
0.902
200195DELTA ST
50/50
5.95
233901CHERRYDALE C
Solar/Wind Harmer
2.127
232913OH NUG2
Adder
16.483
232920IR10
Adder
5.976
970597AG2-380 GEN
Solar/Wind Harmer
7.782
231906DC3 NUG
Adder
26.105
231907DC10
Adder
6.517
972141AH1-641 GEN
Solar/Wind Harmer
4.122
213611FALLS1-3
Adder
4.418
213611FALLS1-3
Adder
4.418
20715028HAN_X4-015
Solar/Wind Harmer
0.368
207507AE2-000G3
Solar/Wind Harmer
38.529
207445AB1-138_GEN
Solar/Wind Harmer
0.693
20720628TIN_W1-124
Solar/Wind Harmer
1.133
971521AH1-258 GEN
Solar/Wind Harmer
3.04
20675528CPH_W2-050
Solar/Wind Harmer
0.6
20676428JCR_X2-075
Solar/Wind Harmer
0.345
217086KRNY_131
Adder
9.113
20675128HRM_W1-127
Solar/Wind Harmer
0.136
209029WAYMART-WD
Solar/Wind Harmer
1.61
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.112
3141813NORNECK
Solar/Wind Helper
0.227
316233AE1-074 FULL
Solar/Wind Helper
0.345
957601AF2-054 GEN
Solar/Wind Helper
0.303
316018AA1-139 ULT2
Solar/Wind Helper
0.965
200200DELTA2 CT1
50/50
6.893
200193DELTA CT2
50/50
3.851
200203Y1-065-STG
50/50
13.408
200055ROCKSP 4
50/50
4.842
232914OH NUG3
Adder
16.706
232916OH NUG5
Adder
16.706
233939AC1-091 C
Solar/Wind Harmer
5.061
233933AB2-153 GEN
Solar/Wind Harmer
2.091
219623KINSLEYBEA C
Solar/Wind Harmer
0.583
213958STHWK5-6
Adder
3.704
20716428NHV_W2-082
Solar/Wind Harmer
2.192
963391AG1-188 GEN
Solar/Wind Harmer
4.545
219612MATRIX C
Solar/Wind Harmer
0.204
20716928W4-060COL
Solar/Wind Harmer
0.784
217213AMBOY SO C
Solar/Wind Harmer
0.132
20673728F2S_V4-070
Solar/Wind Harmer
0.182
207510AF2-138 C
Solar/Wind Harmer
1.581
207437AD2-070 GEN
Solar/Wind Harmer
0.243
20671928W4-073
Solar/Wind Harmer
0.345
20633028GILCT9
Adder
22.394
20465427SHAW CT
Adder
3.06
209116AE2-175 GEN
Solar/Wind Harmer
3.018
970095AG2-074 GEN
Solar/Wind Harmer
3.797
3141196NOKESVL
Solar/Wind Helper
0.957
316077AC2-138 C
Solar/Wind Helper
0.214
316484AD2-074 GEN
Solar/Wind Helper
0.438
316075AC2-137 C
Solar/Wind Helper
0.345
200035PCHBTM 3
50/50
40.545
232918OH NUG7
Adder
16.595
232905CHERITON_25
Adder
4.641
233994AC2-023 GEN
Solar/Wind Harmer
5.076
234036AF2-325 C
Solar/Wind Harmer
1.732
233971AC1-093 C
Solar/Wind Harmer
4.806
232910NRG_G1
Adder
16.207
234014AF1-036_GEN
Solar/Wind Harmer
5.058
232436AB1-176 C
Solar/Wind Harmer
0.427
972233AH1-701 GEN
Adder
5.893
219912AD2-042 GEN
Solar/Wind Harmer
1.067
219607WPEMNERT C
Solar/Wind Harmer
0.539
219304NAMERICA C
Solar/Wind Harmer
0.4
20635028RRCT1&2
Adder
12.446
218418LINDEN_G5
Adder
17.787
219036LINDEN_G7
Adder
17.049
217086KRNY_131
Adder
9.21
20674328GAR_V4-001
Solar/Wind Harmer
0.097
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.153
238149AF1-291A_GEN
Solar/Wind Helper
0.113
966871AG1-558 GEN
Solar/Wind Helper
0.306
315666AE1-190 GEN
Solar/Wind Helper
0.305
316156AD2-030 GEN
Solar/Wind Helper
0.342
316240AF1-291 C
Solar/Wind Helper
0.303
316313AB2-026
Solar/Wind Helper
0.343
316435W1029_GEN3
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
200034PCHBTM 2
50/50
40.156
200194DELTA CT3
50/50
3.851
233998TM1NIN_3.36
Solar/Wind Harmer
1.885
232404W1-003 C
Solar/Wind Harmer
1.891
233996TM1833_GEN
Solar/Wind Harmer
1.885
234033AF1-007_GEN
Solar/Wind Harmer
70.332
232901NORTHST
Adder
15.731
232426Y1-080 FULL
Solar/Wind Harmer
0.361
232902EASTMUNI
Adder
24.554
234012AE2-112_GEN
Solar/Wind Harmer
4.299
972251AH1-710 GEN
Adder
80.133
231918WEST 1
Adder
5.957
228732V1-021 C
Adder
0.272
228400MICK 1CT
Adder
16.558
219766PARADISE C
Solar/Wind Harmer
0.425
20714528FRN_Y2-051
Solar/Wind Harmer
0.345
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
217208PARK ELE C
Solar/Wind Harmer
0.025
966261AG1-495 GEN
Solar/Wind Harmer
3.222
20674628WNG_W3-110
Solar/Wind Harmer
0.359
963071AG1-156 GEN
Solar/Wind Harmer
5.996
209023WIENIPP1
Adder
6.397
209025WIENIPP3
Adder
3.193
200192DELTA CT1
50/50
3.851
200054ROCKSP 3
50/50
4.927
232408W1-005 C
Solar/Wind Harmer
1.891
232917OH NUG6
Adder
16.632
232915OH NUG4
Adder
16.595
972177AH1-672 GEN
Solar/Wind Harmer
25.383
233944AB2-135 GEN
Solar/Wind Harmer
9.744
213958STHWK5-6
Adder
3.704
219907AC1-030 C
Solar/Wind Harmer
0.184
20716028EGP_W2-019
Solar/Wind Harmer
0.573
207522AF2-254 C
Solar/Wind Harmer
1.768
218428ETC SOLAR C
Solar/Wind Harmer
0.038
219908AB1-139 C
Solar/Wind Harmer
0.399
972275AH1-722 GEN
Adder
32.699
20673628F1S_V4-069
Solar/Wind Harmer
0.182
207528AF2-192 GEN
Solar/Wind Harmer
1.293
217186ESSEX_G9
Adder
3.904
217083KRNY_132
Adder
9.191
20676228FRD_X1-012
Solar/Wind Harmer
0.523
20675828AU_W4-064
Solar/Wind Harmer
0.152
20675728RH_W2-091
Solar/Wind Harmer
0.493
207484AF2-139 C O1
Solar/Wind Harmer
0.409
208909MACR G3
Adder
122.298
209010PEIP 1
Adder
0.401
316415AF1-147_GEN2
Solar/Wind Helper
0.819
238175AF1-290_GEN
Solar/Wind Helper
0.128
964211AG1-282 GEN
Solar/Wind Helper
0.306
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
200204Y1-065-CTG1
50/50
7.742
233918AB1-142 GEN
Solar/Wind Harmer
1.84
228206SHRMN CT
Adder
24.016
228260V4-054C
Solar/Wind Harmer
1.477
228729W2-030 C
Solar/Wind Harmer
0.814
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
219348LDSOLAR C
Solar/Wind Harmer
0.771
213611FALLS1-3
Adder
4.418
214194N WALES4
Adder
1.05
20720428HOL_W1-112
Solar/Wind Harmer
0.387
20635828PARLN1&2
Adder
8.013
20635028RRCT1&2
Adder
12.64
218524CNTRALGAS1 C
Solar/Wind Harmer
0.39
217209CENTRL HS C
Solar/Wind Harmer
0.045
20671828STAW2-080
Solar/Wind Harmer
0.103
207439AE1-081 C O1
Solar/Wind Harmer
0.054
207530AG1-191 GEN
Solar/Wind Harmer
1.213
211065PSPA IPP
Solar/Wind Harmer
0.315
961301AF2-421 GEN
Solar/Wind Harmer
0.593
963151AG1-164 GEN
Solar/Wind Harmer
0.593
316337AD2-073 GEN
Solar/Wind Helper
0.346
3141726DUNNSVL
Solar/Wind Helper
0.908
316132AB2-190 GEN1
Solar/Wind Helper
1.289
315773AC2-141 GEN
Solar/Wind Helper
4.837
316036AC1-147 C
Solar/Wind Helper
0.342
3146516WINFALL
Solar/Wind Helper
0.722
3146516WINFALL
Solar/Wind Helper
0.223
232919VN10
Adder
5.307
233970AC1-092 C
Solar/Wind Harmer
5.061
232900DEMECSMY
Adder
17.402
231917EM10
Adder
4.123
232921TASLEY2G
Adder
9.764
233972AC1-094 C
Solar/Wind Harmer
4.064
233950AC2-186 GEN
Solar/Wind Harmer
1.06
228711V2-041C
Solar/Wind Harmer
0.871
213497CHSTR7-9
Adder
3.862
219921AF1-264
Solar/Wind Harmer
0.196
218660EHAMPSOLAR C
Solar/Wind Harmer
0.235
219914AD2-027 C
Solar/Wind Harmer
0.805
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213560DLW11-12
Adder
3.609
207454AA2-184 E
Solar/Wind Harmer
1.137
20635928PARLN3&4
Adder
3.63
217169METRODIV C
Solar/Wind Harmer
0.039
963161AG1-165 GEN
Solar/Wind Harmer
0.593
208972BECR K09
Solar/Wind Harmer
0.618
3147666LOUISA
Solar/Wind Helper
0.529
3141906WESTMOR
Solar/Wind Helper
0.091
316458AB2-190 GEN2
Solar/Wind Helper
1.289
3144873MCLAUGH
Solar/Wind Helper
0.006
316246AF1-032 C
Solar/Wind Helper
0.256
316321Z2-027
Solar/Wind Helper
0.341
3146626S HERTFORD
Solar/Wind Helper
0.223
232912OH NUG1
Adder
16.706
971195AH1-057 GEN
Solar/Wind Harmer
1.843
233955AB2-172 GEN
Solar/Wind Harmer
9.442
232813VAUGHN
Adder
1.107
231902DC CT7
Adder
20.869
233915AB1-141 GEN
Solar/Wind Harmer
1.84
970453AG2-297 GEN
Solar/Wind Harmer
4.023
964001AG1-254 GEN
Solar/Wind Harmer
10.423
228728W1-130C
Solar/Wind Harmer
0.942
227927V4-067C
Solar/Wind Harmer
0.279
219137THOSOLAR C
Solar/Wind Harmer
1.666
219615MILLCREEK C
Solar/Wind Harmer
0.311
219224BRL12CT4
Adder
11.498
207487AE2-000G4
Solar/Wind Harmer
38.529
207497AE2-000G2
Solar/Wind Harmer
38.529
219620RIDERU C
Solar/Wind Harmer
0.064
20635928PARLN3&4
Adder
8.013
218526CNTRALGAS2 C
Solar/Wind Harmer
0.393
217167KRNY_14
Adder
9.191
971009AG2-626 GEN
Solar/Wind Harmer
1.365
961261AF2-417 GEN
Solar/Wind Harmer
0.67
3138133OCRAN
Solar/Wind Helper
0.068
3143873LANEXA
Solar/Wind Helper
0.136
3141873WAN 176
Solar/Wind Helper
0.045
316382AG1-145 C
Solar/Wind Helper
0.304
316159AE1-175 C
Solar/Wind Helper
0.343
316236AE1-162_GEN
Solar/Wind Helper
0.302
316405AF2-144 C
Solar/Wind Helper
0.257
3143316POE
Solar/Wind Helper
0.888
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
3145176PASQUOTANK
Solar/Wind Helper
0.138
970997AG2-616 GEN
Solar/Wind Harmer
13.739
213497CHSTR7-9
Adder
3.862
213497CHSTR7-9
Adder
3.862
213560DLW11-12
Adder
3.609
219222BRL12CT2
Adder
11.498
20717128DIX_Z2-102
Solar/Wind Harmer
1.624
20715828PEM_W1-120
Solar/Wind Harmer
0.656
963711AG1-223 GEN
Solar/Wind Harmer
1.734
219276PARKLANDSO C
Solar/Wind Harmer
0.538
20715228NPK_W1-113
Solar/Wind Harmer
0.488
20720528MAN_W1-024
Solar/Wind Harmer
0.288
219919AE1-041 FULL
Solar/Wind Harmer
0.042
217121ECCF
Adder
0.429
20676728BRNX1-095
Solar/Wind Harmer
0.166
20676328BVR_Y1-020
Solar/Wind Harmer
0.296
20674928WA_W3-044
Solar/Wind Harmer
0.407
971519AH1-257 GEN
Solar/Wind Harmer
2.093
207518AF1-320_GEN
Solar/Wind Harmer
2.977
20465127PORT CT
Adder
2.415
316044AC1-158 PL1
Solar/Wind Helper
1.298
3147666LOUISA
Solar/Wind Helper
0.921
238152AF2-075_GEN
Solar/Wind Helper
0.567
23777901MDS_W4-102
Solar/Wind Helper
0.144
316404AE1-155 C
Solar/Wind Helper
1.941
3138133OCRAN
Solar/Wind Helper
0.136
315662AE1-191 GEN
Solar/Wind Helper
1.219
316280AD1-041 GEN
Solar/Wind Helper
0.762
3143226MDLTHAN
Solar/Wind Helper
0.226
3142543TWELFTH
Solar/Wind Helper
0.022
316369SG1_INVT
Solar/Wind Helper
1.086
316381AD1-082 GEN
Solar/Wind Helper
1.164
319010AE1-072 C
Solar/Wind Helper
2.561
200205Y1-065-CTG2
50/50
7.742
232428Y3-058 C
Solar/Wind Harmer
1.575
234015AF2-250 C
Solar/Wind Harmer
0.227
232424Y1-079 C
Solar/Wind Harmer
1.054
228251CARLLS#4
Adder
0.908
228351V2-046C
Solar/Wind Harmer
2.879
230433AD2-135 GEN
Solar/Wind Harmer
0.144
213589EDDYSTN4
Adder
112.532
219287REEVESEAST C
Solar/Wind Harmer
1.8
213535CROYDN11
Adder
13.157
214067T20SOLAR
Solar/Wind Harmer
0.316
20636128O CRK C2
Adder
7.882
207459AE1-142 C O1
Solar/Wind Harmer
1.266
20628028LAKEHURS
Adder
1.137
217197RE CRAN C
Solar/Wind Harmer
0.594
924131AB2-057 GEN
Solar/Wind Harmer
1.109
20635128RRCT3&4
Adder
12.014
20635128RRCT3&4
Adder
10.48
218419LINDEN_G6
Adder
17.787
219035LINDEN_G8
Adder
16.806
20675428EAM_W2-061
Solar/Wind Harmer
0.192
972237AH1-703 GEN
Adder
10.013
20465127PORT CT
Adder
3.204
316450AC1-158 RIC
Solar/Wind Helper
0.346
966001AG1-469 GEN
Solar/Wind Helper
0.246
238148AE2-230_GEN2
Solar/Wind Helper
0.397
316487AF1-042 GEN
Solar/Wind Helper
0.229
316033AB2-134 GEN
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.895
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316339AD2-160 GEN
Solar/Wind Helper
0.854
316388AE2-253 GEN
Solar/Wind Helper
0.854
3143526WINTERP
Solar/Wind Helper
1.176
315671AE2-027_GEN
Solar/Wind Helper
1.819
316072AD1-144
Solar/Wind Helper
0.256
200201DELTA2 CT2
50/50
6.893
232410W1-006 C
Solar/Wind Harmer
1.891
233946AB2-136 GEN
Solar/Wind Harmer
7.536
232899W1-062
Adder
18.143
233952AC2-187 GEN
Solar/Wind Harmer
2.12
233954AC2-188 GEN
Solar/Wind Harmer
2.12
233984AB2-036 GEN
Solar/Wind Harmer
23.374
233930AB2-032 GEN
Solar/Wind Harmer
1.549
233982AB2-133 GEN
Solar/Wind Harmer
9.047
230511AF1-262
Solar/Wind Harmer
0.261
228307PCLP GT
Adder
17.145
213587EDDYSTN3
Adder
112.486
228754AB1-001 C
Solar/Wind Harmer
0.196
219272CLEANLIGHT C
Solar/Wind Harmer
0.246
217081WEATEXAS C
Solar/Wind Harmer
0.087
217083KRNY_132
Adder
9.132
207471AF2-354 C
Solar/Wind Harmer
0.433
20675928HOL_W4-097
Solar/Wind Harmer
0.106
209010PEIP 1
Adder
2.204
209010PEIP 1
Adder
0.323
316411AF1-147_GEN1
Solar/Wind Helper
0.819
235020AA1-095 C
Solar/Wind Helper
0.043
237061AD1-155 GEN
Solar/Wind Helper
1.429
316312AB1-027
Solar/Wind Helper
0.432
3143526WINTERP
Solar/Wind Helper
1.176
316185AD1-033 GEN
Solar/Wind Helper
1.056
238221AF1-254 C O1
Solar/Wind Helper
0.22
3144356SAPONY
Solar/Wind Helper
0.399
316315AB2-025 C
Solar/Wind Helper
0.34
316447AC1-158 HLD
Solar/Wind Helper
2.856
316192AB2-158 GEN
Solar/Wind Helper
1.55
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.226
3141766HARMONY
Solar/Wind Helper
0.045
315975AC1-164 GENB
Solar/Wind Helper
0.086
3142433PROV 92
Solar/Wind Helper
0.904
3145336SMITFLD
Solar/Wind Helper
0.897
316375AC2-012 GEN
Solar/Wind Helper
0.59
3146456SLIGO L269
Solar/Wind Helper
0.224
232406W1-004 FULL
Solar/Wind Harmer
1.891
232434Z2-077 GEN
Solar/Wind Harmer
0.473
233964AF2-378 GEN
Solar/Wind Harmer
0.241
232422X3-066 FULL
Solar/Wind Harmer
0.466
230415AB2-049 C
Solar/Wind Harmer
0.269
219291REEVESSOUT C
Solar/Wind Harmer
0.081
219236SOUTHERNHQ C
Solar/Wind Harmer
0.089
213815MOSER1-3
Adder
4.565
20714928UPF_X1-085
Solar/Wind Harmer
0.49
219114HARTZY_C
Solar/Wind Harmer
1.002
219918AC2-009 C
Solar/Wind Harmer
0.029
20674528F3S_W2-016
Solar/Wind Harmer
1.358
209025WIENIPP3
Adder
3.128
966881AG1-559 GEN
Solar/Wind Helper
0.309
316473AC1-191 GEN
Solar/Wind Helper
1.387
3142946ENON
Solar/Wind Helper
0.075
3145336SMITFLD
Solar/Wind Helper
0.09
316017AA1-139 ULT1
Solar/Wind Helper
1.025
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.894
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3146456SLIGO L269
Solar/Wind Helper
0.224
3145273HOLLAND
Solar/Wind Helper
0.167
G-007ALTFEXP_G-007A->PJM
CMTX
54.971
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.973
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.798
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.944
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.425
VTFLTFEXP_VFT->PJM
CMTX
135.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.24
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.424

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH235_SRT-A/* $ CHESCO $ PECO_P4_PEACH235 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.16 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4641.99
MW Contribution:
10.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232904IR4
Adder
152.764
233987AB2-037 GEN
Solar/Wind Harmer
21.561
232907VN8
Adder
56.777
233923SMA
Solar/Wind Harmer
6.906
233997TMININ_4.2
Solar/Wind Harmer
1.884
232417X3-008 C
Solar/Wind Harmer
2.123
233973AC2-185 C
Solar/Wind Harmer
10.216
970695AG2-447 GEN
Solar/Wind Harmer
6.758
233935AB2-179 C
Solar/Wind Harmer
4.541
219221BRL12CT1
Adder
11.493
219223BRL12CT3
Adder
11.493
959561AF2-247 GEN
Solar/Wind Harmer
0.602
20715728PEM_W1-119
Solar/Wind Harmer
0.655
20636028O CRK C1
Adder
8.641
971667AH1-334 GEN
Solar/Wind Harmer
3.296
219727YARDVSOLFA C
Solar/Wind Harmer
1.083
20635828PARLN1&2
Adder
3.628
219249CENTRALDIV C
Solar/Wind Harmer
0.041
207442AE1-156 GEN
Solar/Wind Harmer
0.755
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217194REDH C
Solar/Wind Harmer
0.486
207511W3-106 GEN
Solar/Wind Harmer
0.293
200202DELTA2 ST
50/50
11.676
200052ROCKSP 1
50/50
4.865
200053ROCKSP 2
50/50
4.77
233940AF2-379 C
Solar/Wind Harmer
0.352
230434AG1-499 GEN
Solar/Wind Harmer
0.818
219258KINSLEYDEP C
Solar/Wind Harmer
0.44
213942SCHUYLKILL
Adder
4.852
213942SCHUYLKILL
Adder
3.71
213957STHWK3-4
Adder
3.702
213957STHWK3-4
Adder
3.702
213561DLWR9-10
Adder
4.717
213561DLWR9-10
Adder
3.607
219610FLORENCE C
Solar/Wind Harmer
1.783
963401AG1-189 GEN
Solar/Wind Harmer
2.764
971189AH1-054 GEN
Solar/Wind Harmer
1.428
20716228APLW2-078
Solar/Wind Harmer
1.002
20673828FLE_V3-070
Solar/Wind Harmer
0.48
20676128MHD_W3-029
Solar/Wind Harmer
0.485
3141426STAFORD
Solar/Wind Helper
0.051
316468AD1-105 GEN
Solar/Wind Helper
1.096
3141913WHIT STONE
Solar/Wind Helper
0.226
957831AF2-077 GEN
Solar/Wind Helper
0.304
315697AD1-025 GEN
Solar/Wind Helper
2.574
315839AE2-212 C
Solar/Wind Helper
0.303
316258AE1-075 C
Solar/Wind Helper
0.308
316316AC1-027 C
Solar/Wind Helper
0.354
232432Z2-076 GEN
Solar/Wind Harmer
0.249
233968AD2-076_GEN
Solar/Wind Harmer
12.382
231919CHRIST1
Adder
7.815
231920CHRIST2
Adder
7.641
232926CRISFLD1
Adder
3.71
231940T-011
Adder
1.409
234041AC1-190 GEN
Solar/Wind Harmer
16.904
228201CARL#2CT
Adder
9.89
228200CARL#1CT
Adder
9.406
219904AC1-010 C
Solar/Wind Harmer
0.511
219906AC1-017 C
Solar/Wind Harmer
0.29
213815MOSER1-3
Adder
4.564
213815MOSER1-3
Adder
4.564
20720828JCB_W4-025
Solar/Wind Harmer
0.558
20714828MDF_W3-079
Solar/Wind Harmer
0.358
219817TRENTONSOL C
Solar/Wind Harmer
1.268
20641628MLH_W1-032
Solar/Wind Harmer
0.334
20742028HF_AC1-207
Solar/Wind Harmer
0.884
218438BLK ROCK C
Solar/Wind Harmer
0.151
972260AH1-715 GEN1
Adder
14.237
972261AH1-715 GEN2
Adder
16.314
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
217206BARNGR HS C
Solar/Wind Harmer
0.03
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674828DL_W4-046
Solar/Wind Harmer
0.548
20634528N27_Y2-018
Solar/Wind Harmer
0.224
238147AE2-230_GEN1
Solar/Wind Helper
0.397
315976AC1-164 GENA
Solar/Wind Helper
2.916
316169AC1-164_GENC
Solar/Wind Helper
2.519
3142946ENON
Solar/Wind Helper
0.023
316294AC1-161 GEN
Solar/Wind Helper
4.109
316349AD2-085 GEN
Solar/Wind Helper
1.025
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.901
316433W1029_GEN2
Solar/Wind Helper
0.901
971007AG2-625 GEN
Solar/Wind Harmer
2.14
20466127PORT 5CT
Adder
21.343
20674128FR_U2-059
Solar/Wind Harmer
0.147
211065PSPA IPP
Solar/Wind Harmer
0.315
200195DELTA ST
50/50
5.952
233901CHERRYDALE C
Solar/Wind Harmer
2.126
232913OH NUG2
Adder
16.47
232920IR10
Adder
5.971
970597AG2-380 GEN
Solar/Wind Harmer
7.775
231906DC3 NUG
Adder
26.084
231907DC10
Adder
6.512
972141AH1-641 GEN
Solar/Wind Harmer
4.119
213611FALLS1-3
Adder
4.416
213611FALLS1-3
Adder
4.416
20715028HAN_X4-015
Solar/Wind Harmer
0.368
207507AE2-000G3
Solar/Wind Harmer
38.509
207445AB1-138_GEN
Solar/Wind Harmer
0.692
20720628TIN_W1-124
Solar/Wind Harmer
1.133
971521AH1-258 GEN
Solar/Wind Harmer
3.038
20675528CPH_W2-050
Solar/Wind Harmer
0.6
20676428JCR_X2-075
Solar/Wind Harmer
0.345
217086KRNY_131
Adder
9.109
20675128HRM_W1-127
Solar/Wind Harmer
0.136
209029WAYMART-WD
Solar/Wind Harmer
1.609
200200DELTA2 CT1
50/50
6.895
200193DELTA CT2
50/50
3.853
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.112
3141813NORNECK
Solar/Wind Helper
0.227
316233AE1-074 FULL
Solar/Wind Helper
0.345
957601AF2-054 GEN
Solar/Wind Helper
0.303
316018AA1-139 ULT2
Solar/Wind Helper
0.964
200203Y1-065-STG
50/50
13.394
200055ROCKSP 4
50/50
4.837
232914OH NUG3
Adder
16.693
232916OH NUG5
Adder
16.693
233939AC1-091 C
Solar/Wind Harmer
5.057
233933AB2-153 GEN
Solar/Wind Harmer
2.09
219623KINSLEYBEA C
Solar/Wind Harmer
0.583
213958STHWK5-6
Adder
3.702
20716428NHV_W2-082
Solar/Wind Harmer
2.191
963391AG1-188 GEN
Solar/Wind Harmer
4.542
219612MATRIX C
Solar/Wind Harmer
0.203
20716928W4-060COL
Solar/Wind Harmer
0.784
217213AMBOY SO C
Solar/Wind Harmer
0.132
20673728F2S_V4-070
Solar/Wind Harmer
0.182
207510AF2-138 C
Solar/Wind Harmer
1.581
207437AD2-070 GEN
Solar/Wind Harmer
0.243
20671928W4-073
Solar/Wind Harmer
0.345
20633028GILCT9
Adder
22.387
20465427SHAW CT
Adder
3.059
209116AE2-175 GEN
Solar/Wind Harmer
3.017
970095AG2-074 GEN
Solar/Wind Harmer
3.796
3141196NOKESVL
Solar/Wind Helper
0.956
316077AC2-138 C
Solar/Wind Helper
0.214
316484AD2-074 GEN
Solar/Wind Helper
0.438
316075AC2-137 C
Solar/Wind Helper
0.345
200035PCHBTM 3
50/50
40.556
232918OH NUG7
Adder
16.581
232905CHERITON_25
Adder
4.637
233994AC2-023 GEN
Solar/Wind Harmer
5.072
234036AF2-325 C
Solar/Wind Harmer
1.73
233971AC1-093 C
Solar/Wind Harmer
4.802
232910NRG_G1
Adder
16.194
234014AF1-036_GEN
Solar/Wind Harmer
5.054
232436AB1-176 C
Solar/Wind Harmer
0.427
972233AH1-701 GEN
Adder
5.89
219912AD2-042 GEN
Solar/Wind Harmer
1.067
219607WPEMNERT C
Solar/Wind Harmer
0.539
219304NAMERICA C
Solar/Wind Harmer
0.399
20635028RRCT1&2
Adder
12.441
218418LINDEN_G5
Adder
17.78
219036LINDEN_G7
Adder
17.043
217086KRNY_131
Adder
9.207
20674328GAR_V4-001
Solar/Wind Harmer
0.097
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.152
238149AF1-291A_GEN
Solar/Wind Helper
0.113
966871AG1-558 GEN
Solar/Wind Helper
0.306
315666AE1-190 GEN
Solar/Wind Helper
0.305
316156AD2-030 GEN
Solar/Wind Helper
0.342
316240AF1-291 C
Solar/Wind Helper
0.303
316313AB2-026
Solar/Wind Helper
0.343
316435W1029_GEN3
Solar/Wind Helper
0.901
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
200204Y1-065-CTG1
50/50
7.734
233918AB1-142 GEN
Solar/Wind Harmer
1.839
228206SHRMN CT
Adder
24.001
228260V4-054C
Solar/Wind Harmer
1.476
228729W2-030 C
Solar/Wind Harmer
0.813
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
219348LDSOLAR C
Solar/Wind Harmer
0.77
213611FALLS1-3
Adder
4.416
214194N WALES4
Adder
1.05
20720428HOL_W1-112
Solar/Wind Harmer
0.387
20635828PARLN1&2
Adder
8.01
20635028RRCT1&2
Adder
12.635
218524CNTRALGAS1 C
Solar/Wind Harmer
0.39
232921TASLEY2G
Adder
9.756
233972AC1-094 C
Solar/Wind Harmer
4.061
233950AC2-186 GEN
Solar/Wind Harmer
1.059
228711V2-041C
Solar/Wind Harmer
0.87
213497CHSTR7-9
Adder
3.861
219921AF1-264
Solar/Wind Harmer
0.196
218660EHAMPSOLAR C
Solar/Wind Harmer
0.234
219914AD2-027 C
Solar/Wind Harmer
0.804
219688LUMSOLAR_S C
Solar/Wind Harmer
0.27
213560DLW11-12
Adder
3.607
207454AA2-184 E
Solar/Wind Harmer
1.136
20635928PARLN3&4
Adder
3.628
217169METRODIV C
Solar/Wind Harmer
0.039
963161AG1-165 GEN
Solar/Wind Harmer
0.593
208972BECR K09
Solar/Wind Harmer
0.618
3147666LOUISA
Solar/Wind Helper
0.529
3141906WESTMOR
Solar/Wind Helper
0.091
316458AB2-190 GEN2
Solar/Wind Helper
1.289
3144873MCLAUGH
Solar/Wind Helper
0.006
232912OH NUG1
Adder
16.693
971195AH1-057 GEN
Solar/Wind Harmer
1.842
233955AB2-172 GEN
Solar/Wind Harmer
9.434
232813VAUGHN
Adder
1.106
231902DC CT7
Adder
20.853
233915AB1-141 GEN
Solar/Wind Harmer
1.839
970453AG2-297 GEN
Solar/Wind Harmer
4.02
964001AG1-254 GEN
Solar/Wind Harmer
10.417
228728W1-130C
Solar/Wind Harmer
0.941
227927V4-067C
Solar/Wind Harmer
0.279
219137THOSOLAR C
Solar/Wind Harmer
1.665
219615MILLCREEK C
Solar/Wind Harmer
0.31
219224BRL12CT4
Adder
11.493
207487AE2-000G4
Solar/Wind Harmer
38.509
207497AE2-000G2
Solar/Wind Harmer
38.509
219620RIDERU C
Solar/Wind Harmer
0.064
20635928PARLN3&4
Adder
8.01
218526CNTRALGAS2 C
Solar/Wind Harmer
0.392
217167KRNY_14
Adder
9.187
971009AG2-626 GEN
Solar/Wind Harmer
1.365
200194DELTA CT3
50/50
3.853
233998TM1NIN_3.36
Solar/Wind Harmer
1.884
232404W1-003 C
Solar/Wind Harmer
1.889
232919VN10
Adder
5.302
233970AC1-092 C
Solar/Wind Harmer
5.057
232900DEMECSMY
Adder
17.388
231917EM10
Adder
4.121
970997AG2-616 GEN
Solar/Wind Harmer
13.731
213497CHSTR7-9
Adder
3.861
213497CHSTR7-9
Adder
3.861
213560DLW11-12
Adder
3.607
219222BRL12CT2
Adder
11.493
20717128DIX_Z2-102
Solar/Wind Harmer
1.623
20715828PEM_W1-120
Solar/Wind Harmer
0.655
963711AG1-223 GEN
Solar/Wind Harmer
1.733
219276PARKLANDSO C
Solar/Wind Harmer
0.537
20715228NPK_W1-113
Solar/Wind Harmer
0.488
20720528MAN_W1-024
Solar/Wind Harmer
0.288
219919AE1-041 FULL
Solar/Wind Harmer
0.042
217121ECCF
Adder
0.429
20676728BRNX1-095
Solar/Wind Harmer
0.166
20676328BVR_Y1-020
Solar/Wind Harmer
0.296
20674928WA_W3-044
Solar/Wind Harmer
0.407
971519AH1-257 GEN
Solar/Wind Harmer
2.092
207518AF1-320_GEN
Solar/Wind Harmer
2.976
20465127PORT CT
Adder
2.414
316044AC1-158 PL1
Solar/Wind Helper
1.297
3147666LOUISA
Solar/Wind Helper
0.92
238152AF2-075_GEN
Solar/Wind Helper
0.567
23777901MDS_W4-102
Solar/Wind Helper
0.144
316404AE1-155 C
Solar/Wind Helper
1.94
3138133OCRAN
Solar/Wind Helper
0.136
315662AE1-191 GEN
Solar/Wind Helper
1.218
316280AD1-041 GEN
Solar/Wind Helper
0.761
3143226MDLTHAN
Solar/Wind Helper
0.226
3142543TWELFTH
Solar/Wind Helper
0.022
316369SG1_INVT
Solar/Wind Helper
1.085
316381AD1-082 GEN
Solar/Wind Helper
1.164
319010AE1-072 C
Solar/Wind Helper
2.56
200192DELTA CT1
50/50
3.853
200054ROCKSP 3
50/50
4.922
232408W1-005 C
Solar/Wind Harmer
1.889
232917OH NUG6
Adder
16.619
232915OH NUG4
Adder
16.581
972177AH1-672 GEN
Solar/Wind Harmer
25.363
233944AB2-135 GEN
Solar/Wind Harmer
9.736
213958STHWK5-6
Adder
3.702
219907AC1-030 C
Solar/Wind Harmer
0.184
20716028EGP_W2-019
Solar/Wind Harmer
0.572
207522AF2-254 C
Solar/Wind Harmer
1.767
218428ETC SOLAR C
Solar/Wind Harmer
0.038
219908AB1-139 C
Solar/Wind Harmer
0.399
972275AH1-722 GEN
Adder
32.686
20673628F1S_V4-069
Solar/Wind Harmer
0.182
207528AF2-192 GEN
Solar/Wind Harmer
1.292
217186ESSEX_G9
Adder
3.903
217083KRNY_132
Adder
9.187
20676228FRD_X1-012
Solar/Wind Harmer
0.523
20675828AU_W4-064
Solar/Wind Harmer
0.152
20675728RH_W2-091
Solar/Wind Harmer
0.493
207484AF2-139 C O1
Solar/Wind Harmer
0.409
208909MACR G3
Adder
122.265
209010PEIP 1
Adder
0.401
316415AF1-147_GEN2
Solar/Wind Helper
0.819
238175AF1-290_GEN
Solar/Wind Helper
0.127
964211AG1-282 GEN
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.175
315671AE2-027_GEN
Solar/Wind Helper
1.818
316072AD1-144
Solar/Wind Helper
0.256
200201DELTA2 CT2
50/50
6.895
232410W1-006 C
Solar/Wind Harmer
1.889
233946AB2-136 GEN
Solar/Wind Harmer
7.529
232899W1-062
Adder
18.128
233952AC2-187 GEN
Solar/Wind Harmer
2.119
233996TM1833_GEN
Solar/Wind Harmer
1.884
234033AF1-007_GEN
Solar/Wind Harmer
70.275
232901NORTHST
Adder
15.719
232426Y1-080 FULL
Solar/Wind Harmer
0.361
232902EASTMUNI
Adder
24.534
234012AE2-112_GEN
Solar/Wind Harmer
4.296
972251AH1-710 GEN
Adder
80.071
231918WEST 1
Adder
5.953
228732V1-021 C
Adder
0.272
228400MICK 1CT
Adder
16.549
219766PARADISE C
Solar/Wind Harmer
0.425
20714528FRN_Y2-051
Solar/Wind Harmer
0.345
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
217208PARK ELE C
Solar/Wind Harmer
0.025
966261AG1-495 GEN
Solar/Wind Harmer
3.221
20674628WNG_W3-110
Solar/Wind Harmer
0.359
963071AG1-156 GEN
Solar/Wind Harmer
5.994
209023WIENIPP1
Adder
6.395
209025WIENIPP3
Adder
3.192
316447AC1-158 HLD
Solar/Wind Helper
2.855
316192AB2-158 GEN
Solar/Wind Helper
1.55
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.225
3141766HARMONY
Solar/Wind Helper
0.045
315975AC1-164 GENB
Solar/Wind Helper
0.086
3142433PROV 92
Solar/Wind Helper
0.904
3145336SMITFLD
Solar/Wind Helper
0.897
316375AC2-012 GEN
Solar/Wind Helper
0.59
3146456SLIGO L269
Solar/Wind Helper
0.224
200034PCHBTM 2
50/50
40.112
200205Y1-065-CTG2
50/50
7.734
232428Y3-058 C
Solar/Wind Harmer
1.574
234015AF2-250 C
Solar/Wind Harmer
0.227
232424Y1-079 C
Solar/Wind Harmer
1.053
228251CARLLS#4
Adder
0.907
228351V2-046C
Solar/Wind Harmer
2.877
230433AD2-135 GEN
Solar/Wind Harmer
0.144
213589EDDYSTN4
Adder
112.484
219287REEVESEAST C
Solar/Wind Harmer
1.799
213535CROYDN11
Adder
13.151
214067T20SOLAR
Solar/Wind Harmer
0.316
20636128O CRK C2
Adder
7.878
207459AE1-142 C O1
Solar/Wind Harmer
1.266
20628028LAKEHURS
Adder
1.137
217197RE CRAN C
Solar/Wind Harmer
0.594
924131AB2-057 GEN
Solar/Wind Harmer
1.109
20635128RRCT3&4
Adder
12.009
20635128RRCT3&4
Adder
10.475
218419LINDEN_G6
Adder
17.78
219035LINDEN_G8
Adder
16.799
20675428EAM_W2-061
Solar/Wind Harmer
0.192
972237AH1-703 GEN
Adder
10.01
20465127PORT CT
Adder
3.203
316450AC1-158 RIC
Solar/Wind Helper
0.346
966001AG1-469 GEN
Solar/Wind Helper
0.246
238148AE2-230_GEN2
Solar/Wind Helper
0.397
316487AF1-042 GEN
Solar/Wind Helper
0.229
316033AB2-134 GEN
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.895
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316339AD2-160 GEN
Solar/Wind Helper
0.854
316388AE2-253 GEN
Solar/Wind Helper
0.854
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.894
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
961261AF2-417 GEN
Solar/Wind Harmer
0.669
3138133OCRAN
Solar/Wind Helper
0.068
3143873LANEXA
Solar/Wind Helper
0.136
3141873WAN 176
Solar/Wind Helper
0.045
316382AG1-145 C
Solar/Wind Helper
0.304
316159AE1-175 C
Solar/Wind Helper
0.342
316236AE1-162_GEN
Solar/Wind Helper
0.302
217209CENTRL HS C
Solar/Wind Harmer
0.045
20671828STAW2-080
Solar/Wind Harmer
0.103
207439AE1-081 C O1
Solar/Wind Harmer
0.054
207530AG1-191 GEN
Solar/Wind Harmer
1.213
211065PSPA IPP
Solar/Wind Harmer
0.315
961301AF2-421 GEN
Solar/Wind Harmer
0.593
963151AG1-164 GEN
Solar/Wind Harmer
0.593
316337AD2-073 GEN
Solar/Wind Helper
0.346
3141726DUNNSVL
Solar/Wind Helper
0.907
316132AB2-190 GEN1
Solar/Wind Helper
1.289
315773AC2-141 GEN
Solar/Wind Helper
4.835
316036AC1-147 C
Solar/Wind Helper
0.342
3146516WINFALL
Solar/Wind Helper
0.722
3146516WINFALL
Solar/Wind Helper
0.223
3132273ORANGE
Solar/Wind Helper
0.046
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.348
3144536CHRHLND
Solar/Wind Helper
0.034
3142956BIRDNECK
Solar/Wind Helper
0.151
316305AF2-043 C
Solar/Wind Helper
0.301
316320Y1-086
Solar/Wind Helper
0.1
3146516WINFALL
Solar/Wind Helper
0.223
232406W1-004 FULL
Solar/Wind Harmer
1.889
232434Z2-077 GEN
Solar/Wind Harmer
0.472
233964AF2-378 GEN
Solar/Wind Harmer
0.241
232422X3-066 FULL
Solar/Wind Harmer
0.466
230415AB2-049 C
Solar/Wind Harmer
0.269
219291REEVESSOUT C
Solar/Wind Harmer
0.081
219236SOUTHERNHQ C
Solar/Wind Harmer
0.089
213815MOSER1-3
Adder
4.564
20714928UPF_X1-085
Solar/Wind Harmer
0.49
219114HARTZY_C
Solar/Wind Harmer
1.002
219918AC2-009 C
Solar/Wind Harmer
0.029
20674528F3S_W2-016
Solar/Wind Harmer
1.357
209025WIENIPP3
Adder
3.128
966881AG1-559 GEN
Solar/Wind Helper
0.309
316473AC1-191 GEN
Solar/Wind Helper
1.386
3142946ENON
Solar/Wind Helper
0.075
3145336SMITFLD
Solar/Wind Helper
0.09
316017AA1-139 ULT1
Solar/Wind Helper
1.025
3146456SLIGO L269
Solar/Wind Helper
0.224
3145273HOLLAND
Solar/Wind Helper
0.167
230430AE1-229_GEN
Solar/Wind Harmer
40.934
230422AE1-104_GEN1
Solar/Wind Harmer
47.994
230425AE1-104_GEN2
Solar/Wind Harmer
47.994
230407AD2-065 C
Solar/Wind Harmer
0.185
20720728JCB_W1-129
Solar/Wind Harmer
0.368
207500AE2-000G1
Solar/Wind Harmer
38.509
970025AG2-016 GEN
Solar/Wind Harmer
3.436
20714428HOW_X1-037
Solar/Wind Harmer
1.413
218449LINSOLAR C
Solar/Wind Harmer
1.025
217147KRNY_1212
Adder
8.739
217147KRNY_1212
Adder
8.583
217146KRNY_1234
Adder
8.563
217146KRNY_1234
Adder
8.505
964851AG1-348 GEN
Solar/Wind Harmer
1.14
207408W3-077 C
Solar/Wind Harmer
0.414
20462827N BANGR8
Adder
0.568
209026WIENIPP4
Adder
3.16
238169AE2-226 GEN1
Solar/Wind Helper
0.572
238170AE2-226 GEN2
Solar/Wind Helper
0.572
315651AD1-115 GEN
Solar/Wind Helper
0.787
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.09
316059AD1-063 C
Solar/Wind Helper
0.228
313526AB2-022
Solar/Wind Helper
0.341
316405AF2-144 C
Solar/Wind Helper
0.257
3143316POE
Solar/Wind Helper
0.888
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
3145176PASQUOTANK
Solar/Wind Helper
0.138
233954AC2-188 GEN
Solar/Wind Harmer
2.119
233984AB2-036 GEN
Solar/Wind Harmer
23.356
233930AB2-032 GEN
Solar/Wind Harmer
1.548
233982AB2-133 GEN
Solar/Wind Harmer
9.04
230511AF1-262
Solar/Wind Harmer
0.261
228307PCLP GT
Adder
17.135
213587EDDYSTN3
Adder
112.438
228754AB1-001 C
Solar/Wind Harmer
0.196
219272CLEANLIGHT C
Solar/Wind Harmer
0.246
217081WEATEXAS C
Solar/Wind Harmer
0.087
217083KRNY_132
Adder
9.129
207471AF2-354 C
Solar/Wind Harmer
0.433
20675928HOL_W4-097
Solar/Wind Harmer
0.106
209010PEIP 1
Adder
2.203
209010PEIP 1
Adder
0.323
316411AF1-147_GEN1
Solar/Wind Helper
0.819
235020AA1-095 C
Solar/Wind Helper
0.043
237061AD1-155 GEN
Solar/Wind Helper
1.429
316312AB1-027
Solar/Wind Helper
0.432
3143526WINTERP
Solar/Wind Helper
1.175
316185AD1-033 GEN
Solar/Wind Helper
1.056
3144356SAPONY
Solar/Wind Helper
0.399
238221AF1-254 C O1
Solar/Wind Helper
0.22
316315AB2-025 C
Solar/Wind Helper
0.34
316246AF1-032 C
Solar/Wind Helper
0.256
316321Z2-027
Solar/Wind Helper
0.341
3146626S HERTFORD
Solar/Wind Helper
0.223
G-007ALTFEXP_G-007A->PJM
CMTX
54.948
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.953
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.796
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.937
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.422
VTFLTFEXP_VFT->PJM
CMTX
135.337
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.239
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.415

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.05 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4638.14
MW Contribution:
10.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200202DELTA2 ST
50/50
11.684
200052ROCKSP 1
50/50
4.876
200053ROCKSP 2
50/50
4.78
233940AF2-379 C
Solar/Wind Harmer
0.353
230434AG1-499 GEN
Solar/Wind Harmer
0.82
219258KINSLEYDEP C
Solar/Wind Harmer
0.442
213942SCHUYLKILL
Adder
4.865
213942SCHUYLKILL
Adder
3.72
213957STHWK3-4
Adder
3.712
213957STHWK3-4
Adder
3.712
213561DLWR9-10
Adder
4.73
213561DLWR9-10
Adder
3.617
219610FLORENCE C
Solar/Wind Harmer
1.788
963401AG1-189 GEN
Solar/Wind Harmer
2.772
971189AH1-054 GEN
Solar/Wind Harmer
1.432
20716228APLW2-078
Solar/Wind Harmer
1.005
20673828FLE_V3-070
Solar/Wind Harmer
0.482
20676128MHD_W3-029
Solar/Wind Harmer
0.487
3141426STAFORD
Solar/Wind Helper
0.051
316468AD1-105 GEN
Solar/Wind Helper
1.099
3141913WHIT STONE
Solar/Wind Helper
0.227
957831AF2-077 GEN
Solar/Wind Helper
0.304
315697AD1-025 GEN
Solar/Wind Helper
2.58
315839AE2-212 C
Solar/Wind Helper
0.304
232926CRISFLD1
Adder
3.719
231940T-011
Adder
1.412
316258AE1-075 C
Solar/Wind Helper
0.309
316316AC1-027 C
Solar/Wind Helper
0.355
200195DELTA ST
50/50
5.956
233901CHERRYDALE C
Solar/Wind Harmer
2.131
232913OH NUG2
Adder
16.511
232920IR10
Adder
5.986
970597AG2-380 GEN
Solar/Wind Harmer
7.795
231906DC3 NUG
Adder
26.15
231907DC10
Adder
6.528
972141AH1-641 GEN
Solar/Wind Harmer
4.13
213611FALLS1-3
Adder
4.428
213611FALLS1-3
Adder
4.428
20715028HAN_X4-015
Solar/Wind Harmer
0.369
207507AE2-000G3
Solar/Wind Harmer
38.617
207445AB1-138_GEN
Solar/Wind Harmer
0.694
20720628TIN_W1-124
Solar/Wind Harmer
1.136
971521AH1-258 GEN
Solar/Wind Harmer
3.047
20675528CPH_W2-050
Solar/Wind Harmer
0.602
20676428JCR_X2-075
Solar/Wind Harmer
0.346
217086KRNY_131
Adder
9.139
20675128HRM_W1-127
Solar/Wind Harmer
0.136
209029WAYMART-WD
Solar/Wind Harmer
1.616
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.114
3141813NORNECK
Solar/Wind Helper
0.227
316233AE1-074 FULL
Solar/Wind Helper
0.346
234041AC1-190 GEN
Solar/Wind Harmer
16.946
228201CARL#2CT
Adder
9.916
228200CARL#1CT
Adder
9.431
219904AC1-010 C
Solar/Wind Harmer
0.512
219906AC1-017 C
Solar/Wind Harmer
0.291
213815MOSER1-3
Adder
4.575
213815MOSER1-3
Adder
4.575
20720828JCB_W4-025
Solar/Wind Harmer
0.56
20714828MDF_W3-079
Solar/Wind Harmer
0.359
219817TRENTONSOL C
Solar/Wind Harmer
1.272
20641628MLH_W1-032
Solar/Wind Harmer
0.335
20742028HF_AC1-207
Solar/Wind Harmer
0.887
218438BLK ROCK C
Solar/Wind Harmer
0.151
972260AH1-715 GEN1
Adder
14.282
972261AH1-715 GEN2
Adder
16.366
217202FBANKSOLAR C
Solar/Wind Harmer
0.074
217201HACKENSOLA C
Solar/Wind Harmer
0.073
217206BARNGR HS C
Solar/Wind Harmer
0.031
217204WCALDSOLAR C
Solar/Wind Harmer
0.072
20674828DL_W4-046
Solar/Wind Harmer
0.551
20634528N27_Y2-018
Solar/Wind Harmer
0.225
238147AE2-230_GEN1
Solar/Wind Helper
0.398
315976AC1-164 GENA
Solar/Wind Helper
2.922
316169AC1-164_GENC
Solar/Wind Helper
2.525
3142946ENON
Solar/Wind Helper
0.023
316294AC1-161 GEN
Solar/Wind Helper
4.118
316349AD2-085 GEN
Solar/Wind Helper
1.027
3146386ELIZ CT
Solar/Wind Helper
0.224
316431W1029_GEN1
Solar/Wind Helper
0.903
200200DELTA2 CT1
50/50
6.899
200193DELTA CT2
50/50
3.855
200203Y1-065-STG
50/50
13.421
200055ROCKSP 4
50/50
4.847
232914OH NUG3
Adder
16.734
232916OH NUG5
Adder
16.734
233939AC1-091 C
Solar/Wind Harmer
5.069
200035PCHBTM 3
50/50
40.582
232918OH NUG7
Adder
16.622
232905CHERITON_25
Adder
4.648
233994AC2-023 GEN
Solar/Wind Harmer
5.084
234036AF2-325 C
Solar/Wind Harmer
1.734
233971AC1-093 C
Solar/Wind Harmer
4.813
232910NRG_G1
Adder
16.235
234014AF1-036_GEN
Solar/Wind Harmer
5.067
232436AB1-176 C
Solar/Wind Harmer
0.428
972233AH1-701 GEN
Adder
5.905
219912AD2-042 GEN
Solar/Wind Harmer
1.07
219607WPEMNERT C
Solar/Wind Harmer
0.541
219304NAMERICA C
Solar/Wind Harmer
0.4
20635028RRCT1&2
Adder
12.479
218418LINDEN_G5
Adder
17.836
219036LINDEN_G7
Adder
17.097
217086KRNY_131
Adder
9.237
20674328GAR_V4-001
Solar/Wind Harmer
0.097
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.16
238149AF1-291A_GEN
Solar/Wind Helper
0.114
966871AG1-558 GEN
Solar/Wind Helper
0.306
315666AE1-190 GEN
Solar/Wind Helper
0.305
316156AD2-030 GEN
Solar/Wind Helper
0.342
200194DELTA CT3
50/50
3.855
233998TM1NIN_3.36
Solar/Wind Harmer
1.888
232404W1-003 C
Solar/Wind Harmer
1.894
232919VN10
Adder
5.316
233970AC1-092 C
Solar/Wind Harmer
5.069
232900DEMECSMY
Adder
17.431
231917EM10
Adder
4.131
970997AG2-616 GEN
Solar/Wind Harmer
13.766
213497CHSTR7-9
Adder
3.871
213497CHSTR7-9
Adder
3.871
213560DLW11-12
Adder
3.617
219222BRL12CT2
Adder
11.524
20717128DIX_Z2-102
Solar/Wind Harmer
1.628
20715828PEM_W1-120
Solar/Wind Harmer
0.657
963711AG1-223 GEN
Solar/Wind Harmer
1.738
219276PARKLANDSO C
Solar/Wind Harmer
0.539
20715228NPK_W1-113
Solar/Wind Harmer
0.489
20720528MAN_W1-024
Solar/Wind Harmer
0.289
219919AE1-041 FULL
Solar/Wind Harmer
0.042
217121ECCF
Adder
0.431
20676728BRNX1-095
Solar/Wind Harmer
0.167
20676328BVR_Y1-020
Solar/Wind Harmer
0.297
20674928WA_W3-044
Solar/Wind Harmer
0.409
971519AH1-257 GEN
Solar/Wind Harmer
2.1
207518AF1-320_GEN
Solar/Wind Harmer
2.988
20465127PORT CT
Adder
2.423
316044AC1-158 PL1
Solar/Wind Helper
1.3
3147666LOUISA
Solar/Wind Helper
0.922
238152AF2-075_GEN
Solar/Wind Helper
0.568
23777901MDS_W4-102
Solar/Wind Helper
0.144
316404AE1-155 C
Solar/Wind Helper
1.944
3138133OCRAN
Solar/Wind Helper
0.136
315662AE1-191 GEN
Solar/Wind Helper
1.221
316280AD1-041 GEN
Solar/Wind Helper
0.763
3143226MDLTHAN
Solar/Wind Helper
0.226
3142543TWELFTH
Solar/Wind Helper
0.022
316369SG1_INVT
Solar/Wind Helper
1.087
316381AD1-082 GEN
Solar/Wind Helper
1.166
319010AE1-072 C
Solar/Wind Helper
2.565
315611Z1-036_GEN2
Solar/Wind Helper
1.226
200192DELTA CT1
50/50
3.855
200054ROCKSP 3
50/50
4.932
232408W1-005 C
Solar/Wind Harmer
1.894
232917OH NUG6
Adder
16.66
232915OH NUG4
Adder
16.622
972177AH1-672 GEN
Solar/Wind Harmer
25.425
233944AB2-135 GEN
Solar/Wind Harmer
9.761
213958STHWK5-6
Adder
3.712
219907AC1-030 C
Solar/Wind Harmer
0.184
20716028EGP_W2-019
Solar/Wind Harmer
0.574
207522AF2-254 C
Solar/Wind Harmer
1.772
218428ETC SOLAR C
Solar/Wind Harmer
0.038
219908AB1-139 C
Solar/Wind Harmer
0.4
972275AH1-722 GEN
Adder
32.789
20673628F1S_V4-069
Solar/Wind Harmer
0.183
207528AF2-192 GEN
Solar/Wind Harmer
1.296
217186ESSEX_G9
Adder
3.916
217083KRNY_132
Adder
9.217
20676228FRD_X1-012
Solar/Wind Harmer
0.525
20675828AU_W4-064
Solar/Wind Harmer
0.152
20675728RH_W2-091
Solar/Wind Harmer
0.495
207484AF2-139 C O1
Solar/Wind Harmer
0.41
208909MACR G3
Adder
122.768
209010PEIP 1
Adder
0.402
233996TM1833_GEN
Solar/Wind Harmer
1.888
234033AF1-007_GEN
Solar/Wind Harmer
70.448
232901NORTHST
Adder
15.757
232426Y1-080 FULL
Solar/Wind Harmer
0.362
232902EASTMUNI
Adder
24.596
234012AE2-112_GEN
Solar/Wind Harmer
4.307
972251AH1-710 GEN
Adder
80.267
231918WEST 1
Adder
5.968
228732V1-021 C
Adder
0.273
228400MICK 1CT
Adder
16.592
219766PARADISE C
Solar/Wind Harmer
0.426
20714528FRN_Y2-051
Solar/Wind Harmer
0.346
219680HOPEWELLV C1
Solar/Wind Harmer
0.087
218440SUMMTASSOC C
Solar/Wind Harmer
0.135
217208PARK ELE C
Solar/Wind Harmer
0.025
200034PCHBTM 2
50/50
40.193
200205Y1-065-CTG2
50/50
7.75
232428Y3-058 C
Solar/Wind Harmer
1.578
234015AF2-250 C
Solar/Wind Harmer
0.228
232424Y1-079 C
Solar/Wind Harmer
1.056
228251CARLLS#4
Adder
0.91
228351V2-046C
Solar/Wind Harmer
2.884
230433AD2-135 GEN
Solar/Wind Harmer
0.144
213589EDDYSTN4
Adder
112.788
219287REEVESEAST C
Solar/Wind Harmer
1.804
213535CROYDN11
Adder
13.187
214067T20SOLAR
Solar/Wind Harmer
0.316
20636128O CRK C2
Adder
7.9
207459AE1-142 C O1
Solar/Wind Harmer
1.269
20628028LAKEHURS
Adder
1.14
217197RE CRAN C
Solar/Wind Harmer
0.596
924131AB2-057 GEN
Solar/Wind Harmer
1.112
20635128RRCT3&4
Adder
12.046
20635128RRCT3&4
Adder
10.507
218419LINDEN_G6
Adder
17.836
219035LINDEN_G8
Adder
16.853
20675428EAM_W2-061
Solar/Wind Harmer
0.192
972237AH1-703 GEN
Adder
10.042
20465127PORT CT
Adder
3.216
316450AC1-158 RIC
Solar/Wind Helper
0.347
966001AG1-469 GEN
Solar/Wind Helper
0.247
238148AE2-230_GEN2
Solar/Wind Helper
0.398
316487AF1-042 GEN
Solar/Wind Helper
0.229
316033AB2-134 GEN
Solar/Wind Helper
0.781
3145506HICKORY
Solar/Wind Helper
0.897
3145506HICKORY
Solar/Wind Helper
0.538
3145506HICKORY
Solar/Wind Helper
0.134
316339AD2-160 GEN
Solar/Wind Helper
0.856
316388AE2-253 GEN
Solar/Wind Helper
0.856
3137176SLIGO L2192
Solar/Wind Helper
0.892
3130086AYDLETT
Solar/Wind Helper
0.896
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
3132123MT JACKSON
Solar/Wind Helper
0.698
200204Y1-065-CTG1
50/50
7.75
233918AB1-142 GEN
Solar/Wind Harmer
1.844
228206SHRMN CT
Adder
24.063
228260V4-054C
Solar/Wind Harmer
1.48
228729W2-030 C
Solar/Wind Harmer
0.815
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
219348LDSOLAR C
Solar/Wind Harmer
0.772
213611FALLS1-3
Adder
4.428
214194N WALES4
Adder
1.052
20720428HOL_W1-112
Solar/Wind Harmer
0.388
20635828PARLN1&2
Adder
8.034
20635028RRCT1&2
Adder
12.674
218524CNTRALGAS1 C
Solar/Wind Harmer
0.391
217209CENTRL HS C
Solar/Wind Harmer
0.045
20671828STAW2-080
Solar/Wind Harmer
0.103
207439AE1-081 C O1
Solar/Wind Harmer
0.054
207530AG1-191 GEN
Solar/Wind Harmer
1.217
211065PSPA IPP
Solar/Wind Harmer
0.316
961301AF2-421 GEN
Solar/Wind Harmer
0.596
963151AG1-164 GEN
Solar/Wind Harmer
0.596
316337AD2-073 GEN
Solar/Wind Helper
0.347
3141726DUNNSVL
Solar/Wind Helper
0.909
316132AB2-190 GEN1
Solar/Wind Helper
1.291
315773AC2-141 GEN
Solar/Wind Helper
4.846
316036AC1-147 C
Solar/Wind Helper
0.343
3146516WINFALL
Solar/Wind Helper
0.724
3146516WINFALL
Solar/Wind Helper
0.223
233987AB2-037 GEN
Solar/Wind Harmer
21.615
232907VN8
Adder
56.917
233923SMA
Solar/Wind Harmer
6.923
233997TMININ_4.2
Solar/Wind Harmer
1.888
232417X3-008 C
Solar/Wind Harmer
2.128
233973AC2-185 C
Solar/Wind Harmer
10.241
970695AG2-447 GEN
Solar/Wind Harmer
6.775
233935AB2-179 C
Solar/Wind Harmer
4.553
219221BRL12CT1
Adder
11.524
219223BRL12CT3
Adder
11.524
959561AF2-247 GEN
Solar/Wind Harmer
0.604
20715728PEM_W1-119
Solar/Wind Harmer
0.657
20636028O CRK C1
Adder
8.665
971667AH1-334 GEN
Solar/Wind Harmer
3.305
219727YARDVSOLFA C
Solar/Wind Harmer
1.086
20635828PARLN1&2
Adder
3.639
219249CENTRALDIV C
Solar/Wind Harmer
0.041
207442AE1-156 GEN
Solar/Wind Harmer
0.758
217211CAMDEN ST C
Solar/Wind Harmer
0.025
217194REDH C
Solar/Wind Harmer
0.487
232406W1-004 FULL
Solar/Wind Harmer
1.894
232434Z2-077 GEN
Solar/Wind Harmer
0.473
233964AF2-378 GEN
Solar/Wind Harmer
0.241
232422X3-066 FULL
Solar/Wind Harmer
0.467
230415AB2-049 C
Solar/Wind Harmer
0.269
219291REEVESSOUT C
Solar/Wind Harmer
0.081
219236SOUTHERNHQ C
Solar/Wind Harmer
0.09
213815MOSER1-3
Adder
4.575
20714928UPF_X1-085
Solar/Wind Harmer
0.491
219114HARTZY_C
Solar/Wind Harmer
1.005
219918AC2-009 C
Solar/Wind Harmer
0.029
20674528F3S_W2-016
Solar/Wind Harmer
1.362
209025WIENIPP3
Adder
3.142
966881AG1-559 GEN
Solar/Wind Helper
0.31
316473AC1-191 GEN
Solar/Wind Helper
1.389
3142946ENON
Solar/Wind Helper
0.076
3145336SMITFLD
Solar/Wind Helper
0.09
316017AA1-139 ULT1
Solar/Wind Helper
1.027
3146456SLIGO L269
Solar/Wind Helper
0.224
3145273HOLLAND
Solar/Wind Helper
0.167
232904IR4
Adder
153.14
232432Z2-076 GEN
Solar/Wind Harmer
0.25
233968AD2-076_GEN
Solar/Wind Harmer
12.414
231919CHRIST1
Adder
7.835
231920CHRIST2
Adder
7.661
230430AE1-229_GEN
Solar/Wind Harmer
41.041
232912OH NUG1
Adder
16.734
971195AH1-057 GEN
Solar/Wind Harmer
1.846
233955AB2-172 GEN
Solar/Wind Harmer
9.457
232813VAUGHN
Adder
1.109
231902DC CT7
Adder
20.906
233915AB1-141 GEN
Solar/Wind Harmer
1.844
970453AG2-297 GEN
Solar/Wind Harmer
4.03
964001AG1-254 GEN
Solar/Wind Harmer
10.444
228728W1-130C
Solar/Wind Harmer
0.944
227927V4-067C
Solar/Wind Harmer
0.28
219137THOSOLAR C
Solar/Wind Harmer
1.669
219615MILLCREEK C
Solar/Wind Harmer
0.311
219224BRL12CT4
Adder
11.524
207487AE2-000G4
Solar/Wind Harmer
38.617
207497AE2-000G2
Solar/Wind Harmer
38.617
219620RIDERU C
Solar/Wind Harmer
0.064
20635928PARLN3&4
Adder
8.034
218526CNTRALGAS2 C
Solar/Wind Harmer
0.394
217167KRNY_14
Adder
9.217
971009AG2-626 GEN
Solar/Wind Harmer
1.37
961261AF2-417 GEN
Solar/Wind Harmer
0.672
3138133OCRAN
Solar/Wind Helper
0.068
3143873LANEXA
Solar/Wind Helper
0.136
3141873WAN 176
Solar/Wind Helper
0.045
316382AG1-145 C
Solar/Wind Helper
0.304
316159AE1-175 C
Solar/Wind Helper
0.343
316236AE1-162_GEN
Solar/Wind Helper
0.303
316405AF2-144 C
Solar/Wind Helper
0.257
3143316POE
Solar/Wind Helper
0.89
3146486SUNBURY
Solar/Wind Helper
0.224
3146486SUNBURY
Solar/Wind Helper
0.224
3145176PASQUOTANK
Solar/Wind Helper
0.139
207511W3-106 GEN
Solar/Wind Harmer
0.294
971007AG2-625 GEN
Solar/Wind Harmer
2.148
20466127PORT 5CT
Adder
21.427
20674128FR_U2-059
Solar/Wind Harmer
0.147
211065PSPA IPP
Solar/Wind Harmer
0.316
3132273ORANGE
Solar/Wind Helper
0.046
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.349
3144536CHRHLND
Solar/Wind Helper
0.034
3142956BIRDNECK
Solar/Wind Helper
0.151
316305AF2-043 C
Solar/Wind Helper
0.302
316320Y1-086
Solar/Wind Helper
0.101
3146516WINFALL
Solar/Wind Helper
0.223
957601AF2-054 GEN
Solar/Wind Helper
0.304
316018AA1-139 ULT2
Solar/Wind Helper
0.967
315800Z1-036_GEN1
Solar/Wind Helper
1.226
230422AE1-104_GEN1
Solar/Wind Harmer
48.119
230425AE1-104_GEN2
Solar/Wind Harmer
48.119
230407AD2-065 C
Solar/Wind Harmer
0.186
20720728JCB_W1-129
Solar/Wind Harmer
0.369
207500AE2-000G1
Solar/Wind Harmer
38.617
970025AG2-016 GEN
Solar/Wind Harmer
3.445
20714428HOW_X1-037
Solar/Wind Harmer
1.417
218449LINSOLAR C
Solar/Wind Harmer
1.028
217147KRNY_1212
Adder
8.767
217147KRNY_1212
Adder
8.611
217146KRNY_1234
Adder
8.591
217146KRNY_1234
Adder
8.532
964851AG1-348 GEN
Solar/Wind Harmer
1.144
207408W3-077 C
Solar/Wind Harmer
0.415
20462827N BANGR8
Adder
0.57
209026WIENIPP4
Adder
3.175
238169AE2-226 GEN1
Solar/Wind Helper
0.574
238170AE2-226 GEN2
Solar/Wind Helper
0.574
315651AD1-115 GEN
Solar/Wind Helper
0.789
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.091
316059AD1-063 C
Solar/Wind Helper
0.229
313526AB2-022
Solar/Wind Helper
0.342
966261AG1-495 GEN
Solar/Wind Harmer
3.233
20674628WNG_W3-110
Solar/Wind Harmer
0.36
963071AG1-156 GEN
Solar/Wind Harmer
6.022
209023WIENIPP1
Adder
6.425
209025WIENIPP3
Adder
3.207
316447AC1-158 HLD
Solar/Wind Helper
2.861
316192AB2-158 GEN
Solar/Wind Helper
1.553
3142416OLDCHRC
Solar/Wind Helper
0.59
3142416OLDCHRC
Solar/Wind Helper
0.226
3141766HARMONY
Solar/Wind Helper
0.045
315975AC1-164 GENB
Solar/Wind Helper
0.086
3142433PROV 92
Solar/Wind Helper
0.905
3145336SMITFLD
Solar/Wind Helper
0.899
316375AC2-012 GEN
Solar/Wind Helper
0.591
3146456SLIGO L269
Solar/Wind Helper
0.224
200201DELTA2 CT2
50/50
6.899
232410W1-006 C
Solar/Wind Harmer
1.894
233946AB2-136 GEN
Solar/Wind Harmer
7.548
232899W1-062
Adder
18.173
233952AC2-187 GEN
Solar/Wind Harmer
2.124
233954AC2-188 GEN
Solar/Wind Harmer
2.124
233984AB2-036 GEN
Solar/Wind Harmer
23.415
233930AB2-032 GEN
Solar/Wind Harmer
1.552
233982AB2-133 GEN
Solar/Wind Harmer
9.063
230511AF1-262
Solar/Wind Harmer
0.261
228307PCLP GT
Adder
17.18
213587EDDYSTN3
Adder
112.742
228754AB1-001 C
Solar/Wind Harmer
0.196
219272CLEANLIGHT C
Solar/Wind Harmer
0.246
217081WEATEXAS C
Solar/Wind Harmer
0.087
217083KRNY_132
Adder
9.159
207471AF2-354 C
Solar/Wind Harmer
0.435
20675928HOL_W4-097
Solar/Wind Harmer
0.106
209010PEIP 1
Adder
2.213
209010PEIP 1
Adder
0.324
316411AF1-147_GEN1
Solar/Wind Helper
0.82
235020AA1-095 C
Solar/Wind Helper
0.043
237061AD1-155 GEN
Solar/Wind Helper
1.432
316312AB1-027
Solar/Wind Helper
0.433
3143526WINTERP
Solar/Wind Helper
1.178
316185AD1-033 GEN
Solar/Wind Helper
1.058
3144356SAPONY
Solar/Wind Helper
0.4
316315AB2-025 C
Solar/Wind Helper
0.341
238221AF1-254 C O1
Solar/Wind Helper
0.22
316240AF1-291 C
Solar/Wind Helper
0.304
316313AB2-026
Solar/Wind Helper
0.343
316435W1029_GEN3
Solar/Wind Helper
0.903
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
316433W1029_GEN2
Solar/Wind Helper
0.903
316415AF1-147_GEN2
Solar/Wind Helper
0.82
238175AF1-290_GEN
Solar/Wind Helper
0.128
964211AG1-282 GEN
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.178
315671AE2-027_GEN
Solar/Wind Helper
1.822
316072AD1-144
Solar/Wind Helper
0.257
233933AB2-153 GEN
Solar/Wind Harmer
2.095
219623KINSLEYBEA C
Solar/Wind Harmer
0.584
213958STHWK5-6
Adder
3.712
20716428NHV_W2-082
Solar/Wind Harmer
2.197
963391AG1-188 GEN
Solar/Wind Harmer
4.555
219612MATRIX C
Solar/Wind Harmer
0.204
20716928W4-060COL
Solar/Wind Harmer
0.786
217213AMBOY SO C
Solar/Wind Harmer
0.133
20673728F2S_V4-070
Solar/Wind Harmer
0.183
207510AF2-138 C
Solar/Wind Harmer
1.587
207437AD2-070 GEN
Solar/Wind Harmer
0.244
20671928W4-073
Solar/Wind Harmer
0.347
20633028GILCT9
Adder
22.481
20465427SHAW CT
Adder
3.071
209116AE2-175 GEN
Solar/Wind Harmer
3.03
970095AG2-074 GEN
Solar/Wind Harmer
3.814
3141196NOKESVL
Solar/Wind Helper
0.958
316077AC2-138 C
Solar/Wind Helper
0.215
316484AD2-074 GEN
Solar/Wind Helper
0.439
316075AC2-137 C
Solar/Wind Helper
0.346
232921TASLEY2G
Adder
9.78
233972AC1-094 C
Solar/Wind Harmer
4.071
233950AC2-186 GEN
Solar/Wind Harmer
1.062
228711V2-041C
Solar/Wind Harmer
0.872
213497CHSTR7-9
Adder
3.871
219921AF1-264
Solar/Wind Harmer
0.196
218660EHAMPSOLAR C
Solar/Wind Harmer
0.235
219914AD2-027 C
Solar/Wind Harmer
0.807
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213560DLW11-12
Adder
3.617
207454AA2-184 E
Solar/Wind Harmer
1.14
20635928PARLN3&4
Adder
3.639
217169METRODIV C
Solar/Wind Harmer
0.039
963161AG1-165 GEN
Solar/Wind Harmer
0.596
208972BECR K09
Solar/Wind Harmer
0.62
3147666LOUISA
Solar/Wind Helper
0.53
3141906WESTMOR
Solar/Wind Helper
0.091
316458AB2-190 GEN2
Solar/Wind Helper
1.291
3144873MCLAUGH
Solar/Wind Helper
0.006
316246AF1-032 C
Solar/Wind Helper
0.257
316321Z2-027
Solar/Wind Helper
0.342
3146626S HERTFORD
Solar/Wind Helper
0.223
G-007ALTFEXP_G-007A->PJM
CMTX
55.116
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.156
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.811
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.985
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.437
VTFLTFEXP_VFT->PJM
CMTX
135.774
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.247
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.485

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.33 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:4194.82
MW Contribution:
10.01
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232912OH NUG1
Adder
16.706
971195AH1-057 GEN
Solar/Wind Harmer
1.182
232813VAUGHN
Adder
1.107
231902DC CT7
Adder
20.869
233915AB1-141 GEN
Solar/Wind Harmer
0.474
970453AG2-297 GEN
Solar/Wind Harmer
3.713
964001AG1-254 GEN
Solar/Wind Harmer
8.069
219224BRL12CT4
Adder
11.498
207487AE2-000G4
Solar/Wind Harmer
15.467
207497AE2-000G2
Solar/Wind Harmer
15.467
20635928PARLN3&4
Adder
8.013
218526CNTRALGAS2 C
Solar/Wind Harmer
0.812
217167KRNY_14
Adder
9.191
971009AG2-626 GEN
Solar/Wind Harmer
0.882
3138133OCRAN
Solar/Wind Helper
0.068
3143873LANEXA
Solar/Wind Helper
0.136
3141873WAN 176
Solar/Wind Helper
0.045
316382AG1-145 C
Solar/Wind Helper
0.304
316159AE1-175 C
Solar/Wind Helper
0.343
316236AE1-162_GEN
Solar/Wind Helper
0.302
316405AF2-144 C
Solar/Wind Helper
0.257
3143316POE
Solar/Wind Helper
0.888
3146486SUNBURY
Solar/Wind Helper
0.223
3146486SUNBURY
Solar/Wind Helper
0.223
3145176PASQUOTANK
Solar/Wind Helper
0.138
232904IR4
Adder
152.888
232432Z2-076 GEN
Solar/Wind Harmer
0.025
233968AD2-076_GEN
Solar/Wind Harmer
4.345
231919CHRIST1
Adder
7.82
231920CHRIST2
Adder
7.647
230430AE1-229_GEN
Solar/Wind Harmer
28.391
230422AE1-104_GEN1
Solar/Wind Harmer
19.279
230425AE1-104_GEN2
Solar/Wind Harmer
19.279
207500AE2-000G1
Solar/Wind Harmer
15.467
970025AG2-016 GEN
Solar/Wind Harmer
2.221
217147KRNY_1212
Adder
8.742
217147KRNY_1212
Adder
8.586
217146KRNY_1234
Adder
8.566
217146KRNY_1234
Adder
8.508
20462827N BANGR8
Adder
0.568
209026WIENIPP4
Adder
3.161
238169AE2-226 GEN1
Solar/Wind Helper
0.573
238170AE2-226 GEN2
Solar/Wind Helper
0.573
315651AD1-115 GEN
Solar/Wind Helper
0.788
3141783LANCAST
Solar/Wind Helper
0.136
3141783LANCAST
Solar/Wind Helper
0.09
316059AD1-063 C
Solar/Wind Helper
0.229
313526AB2-022
Solar/Wind Helper
0.341
200200DELTA2 CT1
50/50
6.893
200193DELTA CT2
50/50
3.851
200203Y1-065-STG
50/50
13.408
200055ROCKSP 4
50/50
4.842
232914OH NUG3
Adder
16.706
232916OH NUG5
Adder
16.706
233939AC1-091 C
Solar/Wind Harmer
3.406
213958STHWK5-6
Adder
3.704
963391AG1-188 GEN
Solar/Wind Harmer
2.219
207437AD2-070 GEN
Solar/Wind Harmer
0.053
20633028GILCT9
Adder
22.394
20465427SHAW CT
Adder
3.06
970095AG2-074 GEN
Solar/Wind Harmer
3.044
3141196NOKESVL
Solar/Wind Helper
0.957
316077AC2-138 C
Solar/Wind Helper
0.214
316484AD2-074 GEN
Solar/Wind Helper
0.438
316075AC2-137 C
Solar/Wind Helper
0.345
232406W1-004 FULL
Solar/Wind Harmer
1.221
232434Z2-077 GEN
Solar/Wind Harmer
0.079
232422X3-066 FULL
Solar/Wind Harmer
0.155
213815MOSER1-3
Adder
4.565
209025WIENIPP3
Adder
3.128
966881AG1-559 GEN
Solar/Wind Helper
0.309
316473AC1-191 GEN
Solar/Wind Helper
1.387
3142946ENON
Solar/Wind Helper
0.075
3145336SMITFLD
Solar/Wind Helper
0.09
316017AA1-139 ULT1
Solar/Wind Helper
1.025
3146456SLIGO L269
Solar/Wind Helper
0.224
3145273HOLLAND
Solar/Wind Helper
0.167
200034PCHBTM 2
50/50
40.156
200205Y1-065-CTG2
50/50
7.742
228251CARLLS#4
Adder
0.908
232926CRISFLD1
Adder
3.713
231940T-011
Adder
1.41
234041AC1-190 GEN
Solar/Wind Harmer
13.77
233987AB2-037 GEN
Solar/Wind Harmer
-0.003
232907VN8
Adder
56.823
233973AC2-185 C
Solar/Wind Harmer
3.406
970695AG2-447 GEN
Solar/Wind Harmer
4.719
233935AB2-179 C
Solar/Wind Harmer
2.5
219221BRL12CT1
Adder
11.498
219223BRL12CT3
Adder
11.498
20636028O CRK C1
Adder
8.645
971667AH1-334 GEN
Solar/Wind Harmer
2.131
20635828PARLN1&2
Adder
3.63
207442AE1-156 GEN
Solar/Wind Harmer
0.06
971007AG2-625 GEN
Solar/Wind Harmer
1.383
20466127PORT 5CT
Adder
21.35
3132273ORANGE
Solar/Wind Helper
0.046
23546401DTGZ2-030
Solar/Wind Helper
0.072
316223AC1-118
Solar/Wind Helper
0.348
3144536CHRHLND
Solar/Wind Helper
0.034
3142956BIRDNECK
Solar/Wind Helper
0.151
316305AF2-043 C
Solar/Wind Helper
0.301
316320Y1-086
Solar/Wind Helper
0.1
3146516WINFALL
Solar/Wind Helper
0.223
200195DELTA ST
50/50
5.95
232913OH NUG2
Adder
16.483
232920IR10
Adder
5.976
970597AG2-380 GEN
Solar/Wind Harmer
7.782
231906DC3 NUG
Adder
26.105
231907DC10
Adder
6.517
972141AH1-641 GEN
Solar/Wind Harmer
2.237
213611FALLS1-3
Adder
4.418
213611FALLS1-3
Adder
4.418
207507AE2-000G3
Solar/Wind Harmer
15.467
971521AH1-258 GEN
Solar/Wind Harmer
1.964
217086KRNY_131
Adder
9.113
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.112
3141813NORNECK
Solar/Wind Helper
0.227
316233AE1-074 FULL
Solar/Wind Helper
0.345
957601AF2-054 GEN
Solar/Wind Helper
0.303
316018AA1-139 ULT2
Solar/Wind Helper
0.965
213589EDDYSTN4
Adder
112.532
213535CROYDN11
Adder
13.157
20636128O CRK C2
Adder
7.882
20628028LAKEHURS
Adder
1.137
20635128RRCT3&4
Adder
12.014
20635128RRCT3&4
Adder
10.48
218419LINDEN_G6
Adder
17.787
219035LINDEN_G8
Adder
16.806
972237AH1-703 GEN
Adder
10.013
20465127PORT CT
Adder
3.204
316450AC1-158 RIC
Solar/Wind Helper
0.346
966001AG1-469 GEN
Solar/Wind Helper
0.246
238148AE2-230_GEN2
Solar/Wind Helper
0.397
316487AF1-042 GEN
Solar/Wind Helper
0.229
316033AB2-134 GEN
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.895
3145506HICKORY
Solar/Wind Helper
0.537
3145506HICKORY
Solar/Wind Helper
0.134
316339AD2-160 GEN
Solar/Wind Helper
0.854
316388AE2-253 GEN
Solar/Wind Helper
0.854
3137176SLIGO L2192
Solar/Wind Helper
0.89
3130086AYDLETT
Solar/Wind Helper
0.894
3146626S HERTFORD
Solar/Wind Helper
0.223
3146626S HERTFORD
Solar/Wind Helper
0.223
200202DELTA2 ST
50/50
11.673
200052ROCKSP 1
50/50
4.871
200053ROCKSP 2
50/50
4.775
213942SCHUYLKILL
Adder
4.854
213942SCHUYLKILL
Adder
3.712
213957STHWK3-4
Adder
3.704
213957STHWK3-4
Adder
3.704
213561DLWR9-10
Adder
4.719
213561DLWR9-10
Adder
3.609
963401AG1-189 GEN
Solar/Wind Harmer
1.367
971189AH1-054 GEN
Solar/Wind Harmer
0.923
3141426STAFORD
Solar/Wind Helper
0.051
316468AD1-105 GEN
Solar/Wind Helper
1.097
3141913WHIT STONE
Solar/Wind Helper
0.226
957831AF2-077 GEN
Solar/Wind Helper
0.304
315697AD1-025 GEN
Solar/Wind Helper
2.575
315839AE2-212 C
Solar/Wind Helper
0.303
228201CARL#2CT
Adder
9.896
228200CARL#1CT
Adder
9.412
213815MOSER1-3
Adder
4.565
213815MOSER1-3
Adder
4.565
20714828MDF_W3-079
Solar/Wind Harmer
0.115
972260AH1-715 GEN1
Adder
14.243
972261AH1-715 GEN2
Adder
16.32
238147AE2-230_GEN1
Solar/Wind Helper
0.397
315976AC1-164 GENA
Solar/Wind Helper
2.917
316169AC1-164_GENC
Solar/Wind Helper
2.52
3142946ENON
Solar/Wind Helper
0.023
316294AC1-161 GEN
Solar/Wind Helper
4.111
316349AD2-085 GEN
Solar/Wind Helper
1.025
3146386ELIZ CT
Solar/Wind Helper
0.223
316431W1029_GEN1
Solar/Wind Helper
0.902
316433W1029_GEN2
Solar/Wind Helper
0.902
234033AF1-007_GEN
Solar/Wind Harmer
26.113
232901NORTHST
Adder
15.731
232902EASTMUNI
Adder
24.554
234012AE2-112_GEN
Solar/Wind Harmer
4.345
972251AH1-710 GEN
Adder
80.133
231918WEST 1
Adder
5.957
228732V1-021 C
Adder
0.272
228400MICK 1CT
Adder
16.558
966261AG1-495 GEN
Solar/Wind Harmer
1.574
963071AG1-156 GEN
Solar/Wind Harmer
4.59
209023WIENIPP1
Adder
6.397
209025WIENIPP3
Adder
3.193
316447AC1-158 HLD
Solar/Wind Helper
2.856
316192AB2-158 GEN
Solar/Wind Helper
1.55
3142416OLDCHRC
Solar/Wind Helper
0.589
3142416OLDCHRC
Solar/Wind Helper
0.226
3141766HARMONY
Solar/Wind Helper
0.045
315975AC1-164 GENB
Solar/Wind Helper
0.086
3142433PROV 92
Solar/Wind Helper
0.904
3145336SMITFLD
Solar/Wind Helper
0.897
316375AC2-012 GEN
Solar/Wind Helper
0.59
3146456SLIGO L269
Solar/Wind Helper
0.224
200035PCHBTM 3
50/50
40.545
232918OH NUG7
Adder
16.595
232905CHERITON_25
Adder
4.641
233971AC1-093 C
Solar/Wind Harmer
3.406
232910NRG_G1
Adder
16.207
234014AF1-036_GEN
Solar/Wind Harmer
4.345
972233AH1-701 GEN
Adder
5.893
219304NAMERICA C
Solar/Wind Harmer
0.117
20635028RRCT1&2
Adder
12.446
218418LINDEN_G5
Adder
17.787
219036LINDEN_G7
Adder
17.049
217086KRNY_131
Adder
9.21
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.153
238149AF1-291A_GEN
Solar/Wind Helper
0.113
966871AG1-558 GEN
Solar/Wind Helper
0.306
315666AE1-190 GEN
Solar/Wind Helper
0.305
316156AD2-030 GEN
Solar/Wind Helper
0.342
316240AF1-291 C
Solar/Wind Helper
0.303
316313AB2-026
Solar/Wind Helper
0.343
316435W1029_GEN3
Solar/Wind Helper
0.902
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
3146516WINFALL
Solar/Wind Helper
0.223
316258AE1-075 C
Solar/Wind Helper
0.308
316316AC1-027 C
Solar/Wind Helper
0.354
200201DELTA2 CT2
50/50
6.893
232410W1-006 C
Solar/Wind Harmer
1.221
232899W1-062
Adder
18.143
233984AB2-036 GEN
Solar/Wind Harmer
13.642
233930AB2-032 GEN
Solar/Wind Harmer
1.782
228307PCLP GT
Adder
17.145
213587EDDYSTN3
Adder
112.486
217083KRNY_132
Adder
9.132
209010PEIP 1
Adder
2.204
209010PEIP 1
Adder
0.323
316411AF1-147_GEN1
Solar/Wind Helper
0.819
235020AA1-095 C
Solar/Wind Helper
0.043
237061AD1-155 GEN
Solar/Wind Helper
1.429
316312AB1-027
Solar/Wind Helper
0.432
3143526WINTERP
Solar/Wind Helper
1.176
316185AD1-033 GEN
Solar/Wind Helper
1.056
238221AF1-254 C O1
Solar/Wind Helper
0.22
3144356SAPONY
Solar/Wind Helper
0.399
316315AB2-025 C
Solar/Wind Helper
0.34
200192DELTA CT1
50/50
3.851
200054ROCKSP 3
50/50
4.927
232408W1-005 C
Solar/Wind Harmer
1.221
232917OH NUG6
Adder
16.632
232915OH NUG4
Adder
16.595
972177AH1-672 GEN
Solar/Wind Harmer
19.244
213958STHWK5-6
Adder
3.704
207522AF2-254 C
Solar/Wind Harmer
1.142
972275AH1-722 GEN
Adder
32.699
207528AF2-192 GEN
Solar/Wind Harmer
0.73
217186ESSEX_G9
Adder
3.904
217083KRNY_132
Adder
9.191
208909MACR G3
Adder
122.298
209010PEIP 1
Adder
0.401
316415AF1-147_GEN2
Solar/Wind Helper
0.819
238175AF1-290_GEN
Solar/Wind Helper
0.128
964211AG1-282 GEN
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.176
315671AE2-027_GEN
Solar/Wind Helper
1.819
316072AD1-144
Solar/Wind Helper
0.256
200204Y1-065-CTG1
50/50
7.742
233918AB1-142 GEN
Solar/Wind Harmer
0.474
228206SHRMN CT
Adder
24.016
213611FALLS1-3
Adder
4.418
214194N WALES4
Adder
1.05
20635828PARLN1&2
Adder
8.013
20635028RRCT1&2
Adder
12.64
218524CNTRALGAS1 C
Solar/Wind Harmer
0.807
316337AD2-073 GEN
Solar/Wind Helper
0.346
3141726DUNNSVL
Solar/Wind Helper
0.908
316132AB2-190 GEN1
Solar/Wind Helper
1.289
315773AC2-141 GEN
Solar/Wind Helper
4.837
316036AC1-147 C
Solar/Wind Helper
0.342
3146516WINFALL
Solar/Wind Helper
0.722
3146516WINFALL
Solar/Wind Helper
0.223
200194DELTA CT3
50/50
3.851
232404W1-003 C
Solar/Wind Harmer
1.221
232919VN10
Adder
5.307
233970AC1-092 C
Solar/Wind Harmer
3.406
232900DEMECSMY
Adder
17.402
231917EM10
Adder
4.123
970997AG2-616 GEN
Solar/Wind Harmer
10.336
213497CHSTR7-9
Adder
3.862
213497CHSTR7-9
Adder
3.862
213560DLW11-12
Adder
3.609
219222BRL12CT2
Adder
11.498
217121ECCF
Adder
0.429
971519AH1-257 GEN
Solar/Wind Harmer
1.352
20465127PORT CT
Adder
2.415
316044AC1-158 PL1
Solar/Wind Helper
1.298
3147666LOUISA
Solar/Wind Helper
0.921
238152AF2-075_GEN
Solar/Wind Helper
0.567
23777901MDS_W4-102
Solar/Wind Helper
0.144
316404AE1-155 C
Solar/Wind Helper
1.941
3138133OCRAN
Solar/Wind Helper
0.136
315662AE1-191 GEN
Solar/Wind Helper
1.219
316280AD1-041 GEN
Solar/Wind Helper
0.762
3143226MDLTHAN
Solar/Wind Helper
0.226
3142543TWELFTH
Solar/Wind Helper
0.022
316369SG1_INVT
Solar/Wind Helper
1.086
316381AD1-082 GEN
Solar/Wind Helper
1.164
319010AE1-072 C
Solar/Wind Helper
2.561
232921TASLEY2G
Adder
9.764
233972AC1-094 C
Solar/Wind Harmer
3.406
213497CHSTR7-9
Adder
3.862
213560DLW11-12
Adder
3.609
20635928PARLN3&4
Adder
3.63
3147666LOUISA
Solar/Wind Helper
0.529
3141906WESTMOR
Solar/Wind Helper
0.091
316458AB2-190 GEN2
Solar/Wind Helper
1.289
3144873MCLAUGH
Solar/Wind Helper
0.006
316246AF1-032 C
Solar/Wind Helper
0.256
316321Z2-027
Solar/Wind Helper
0.341
3146626S HERTFORD
Solar/Wind Helper
0.223
G-007ALTFEXP_G-007A->PJM
CMTX
54.971
CBM NorthLTFEXP_CBM-N->PJM
CBM
62.973
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.798
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.944
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.425
VTFLTFEXP_VFT->PJM
CMTX
135.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.24
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.424

Details for PCHBTM1N-CHAN 500.0 kV Ckt 1 line l/o PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1N-CHAN 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH245_SRT-A/* $ CHESCO $ PECO_P4_PEACH245 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.17 %
Rating:3486.0 MVA
Rating Type:B
MVA to Mitigate:3875.5
MW Contribution:
10.22
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232912OH NUG1
Adder
16.886
971195AH1-057 GEN
Solar/Wind Harmer
1.863
233955AB2-172 GEN
Solar/Wind Harmer
9.543
232813VAUGHN
Adder
1.119
231902DC CT7
Adder
21.097
233915AB1-141 GEN
Solar/Wind Harmer
1.861
970453AG2-297 GEN
Solar/Wind Harmer
4.075
964001AG1-254 GEN
Solar/Wind Harmer
10.561
228728W1-130C
Solar/Wind Harmer
0.954
227927V4-067C
Solar/Wind Harmer
0.283
219137THOSOLAR C
Solar/Wind Harmer
1.689
219615MILLCREEK C
Solar/Wind Harmer
0.315
219224BRL12CT4
Adder
11.669
207487AE2-000G4
Solar/Wind Harmer
39.134
207497AE2-000G2
Solar/Wind Harmer
39.134
219620RIDERU C
Solar/Wind Harmer
0.065
20635928PARLN3&4
Adder
8.16
218526CNTRALGAS2 C
Solar/Wind Harmer
0.4
217167KRNY_14
Adder
9.379
971009AG2-626 GEN
Solar/Wind Harmer
1.4
961261AF2-417 GEN
Solar/Wind Harmer
0.692
233901CHERRYDALE C
Solar/Wind Harmer
2.15
232913OH NUG2
Adder
16.661
232920IR10
Adder
6.04
970597AG2-380 GEN
Solar/Wind Harmer
7.866
232904IR4
Adder
154.535
232432Z2-076 GEN
Solar/Wind Harmer
0.252
233968AD2-076_GEN
Solar/Wind Harmer
12.527
231919CHRIST1
Adder
7.91
231920CHRIST2
Adder
7.735
230430AE1-229_GEN
Solar/Wind Harmer
41.503
230422AE1-104_GEN1
Solar/Wind Harmer
48.665
230425AE1-104_GEN2
Solar/Wind Harmer
48.665
230407AD2-065 C
Solar/Wind Harmer
0.188
20720728JCB_W1-129
Solar/Wind Harmer
0.374
207500AE2-000G1
Solar/Wind Harmer
39.134
970025AG2-016 GEN
Solar/Wind Harmer
3.492
20714428HOW_X1-037
Solar/Wind Harmer
1.438
218449LINSOLAR C
Solar/Wind Harmer
1.045
217147KRNY_1212
Adder
8.921
217147KRNY_1212
Adder
8.762
217146KRNY_1234
Adder
8.742
217146KRNY_1234
Adder
8.682
964851AG1-348 GEN
Solar/Wind Harmer
1.169
207408W3-077 C
Solar/Wind Harmer
0.425
20462827N BANGR8
Adder
0.583
209026WIENIPP4
Adder
3.278
238169AE2-226 GEN1
Solar/Wind Helper
0.549
238170AE2-226 GEN2
Solar/Wind Helper
0.549
315651AD1-115 GEN
Solar/Wind Helper
0.756
231906DC3 NUG
Adder
26.39
231907DC10
Adder
6.588
972141AH1-641 GEN
Solar/Wind Harmer
4.176
213611FALLS1-3
Adder
4.486
213611FALLS1-3
Adder
4.486
20715028HAN_X4-015
Solar/Wind Harmer
0.373
207507AE2-000G3
Solar/Wind Harmer
39.134
207445AB1-138_GEN
Solar/Wind Harmer
0.704
20720628TIN_W1-124
Solar/Wind Harmer
1.153
971521AH1-258 GEN
Solar/Wind Harmer
3.093
20675528CPH_W2-050
Solar/Wind Harmer
0.611
20676428JCR_X2-075
Solar/Wind Harmer
0.352
217086KRNY_131
Adder
9.299
20675128HRM_W1-127
Solar/Wind Harmer
0.139
209029WAYMART-WD
Solar/Wind Harmer
1.667
3138216PACIFIC
Solar/Wind Helper
0.039
316164AC1-076 GEN
Solar/Wind Helper
1.067
200204Y1-065-CTG1
50/50
7.804
233918AB1-142 GEN
Solar/Wind Harmer
1.861
228206SHRMN CT
Adder
24.331
228260V4-054C
Solar/Wind Harmer
1.497
228729W2-030 C
Solar/Wind Harmer
0.825
219686LUMSOLAR_N C
Solar/Wind Harmer
0.275
219348LDSOLAR C
Solar/Wind Harmer
0.782
213611FALLS1-3
Adder
4.486
214194N WALES4
Adder
1.066
20720428HOL_W1-112
Solar/Wind Harmer
0.393
20635828PARLN1&2
Adder
8.16
20635028RRCT1&2
Adder
12.874
218524CNTRALGAS1 C
Solar/Wind Harmer
0.397
217209CENTRL HS C
Solar/Wind Harmer
0.046
20671828STAW2-080
Solar/Wind Harmer
0.105
207439AE1-081 C O1
Solar/Wind Harmer
0.055
207530AG1-191 GEN
Solar/Wind Harmer
1.242
211065PSPA IPP
Solar/Wind Harmer
0.325
961301AF2-421 GEN
Solar/Wind Harmer
0.615
963151AG1-164 GEN
Solar/Wind Harmer
0.615
200035PCHBTM 3
50/50
40.849
232918OH NUG7
Adder
16.774
232905CHERITON_25
Adder
4.691
233994AC2-023 GEN
Solar/Wind Harmer
5.131
234036AF2-325 C
Solar/Wind Harmer
1.75
233971AC1-093 C
Solar/Wind Harmer
4.857
232910NRG_G1
Adder
16.383
234014AF1-036_GEN
Solar/Wind Harmer
5.113
232436AB1-176 C
Solar/Wind Harmer
0.432
972233AH1-701 GEN
Adder
5.973
219912AD2-042 GEN
Solar/Wind Harmer
1.082
219607WPEMNERT C
Solar/Wind Harmer
0.547
219304NAMERICA C
Solar/Wind Harmer
0.405
20635028RRCT1&2
Adder
12.676
218418LINDEN_G5
Adder
18.131
219036LINDEN_G7
Adder
17.385
217086KRNY_131
Adder
9.399
20674328GAR_V4-001
Solar/Wind Harmer
0.099
316006AB2-029 C
Solar/Wind Helper
0.108
316045AC1-158 PL2
Solar/Wind Helper
3.985
233987AB2-037 GEN
Solar/Wind Harmer
21.811
232907VN8
Adder
57.434
233923SMA
Solar/Wind Harmer
6.986
233997TMININ_4.2
Solar/Wind Harmer
1.905
232417X3-008 C
Solar/Wind Harmer
2.147
233973AC2-185 C
Solar/Wind Harmer
10.335
970695AG2-447 GEN
Solar/Wind Harmer
6.837
233935AB2-179 C
Solar/Wind Harmer
4.596
219221BRL12CT1
Adder
11.669
219223BRL12CT3
Adder
11.669
959561AF2-247 GEN
Solar/Wind Harmer
0.612
20715728PEM_W1-119
Solar/Wind Harmer
0.666
20636028O CRK C1
Adder
8.781
971667AH1-334 GEN
Solar/Wind Harmer
3.351
219727YARDVSOLFA C
Solar/Wind Harmer
1.101
20635828PARLN1&2
Adder
3.696
219249CENTRALDIV C
Solar/Wind Harmer
0.042
207442AE1-156 GEN
Solar/Wind Harmer
0.771
217211CAMDEN ST C
Solar/Wind Harmer
0.025
217194REDH C
Solar/Wind Harmer
0.496
207511W3-106 GEN
Solar/Wind Harmer
0.3
971007AG2-625 GEN
Solar/Wind Harmer
2.194
20466127PORT 5CT
Adder
21.911
20674128FR_U2-059
Solar/Wind Harmer
0.151
211065PSPA IPP
Solar/Wind Harmer
0.325
233996TM1833_GEN
Solar/Wind Harmer
1.905
234033AF1-007_GEN
Solar/Wind Harmer
71.09
232901NORTHST
Adder
15.901
232426Y1-080 FULL
Solar/Wind Harmer
0.365
232902EASTMUNI
Adder
24.819
234012AE2-112_GEN
Solar/Wind Harmer
4.346
972251AH1-710 GEN
Adder
81.045
231918WEST 1
Adder
6.025
228732V1-021 C
Adder
0.276
228400MICK 1CT
Adder
16.783
219766PARADISE C
Solar/Wind Harmer
0.431
20714528FRN_Y2-051
Solar/Wind Harmer
0.351
219680HOPEWELLV C1
Solar/Wind Harmer
0.088
218440SUMMTASSOC C
Solar/Wind Harmer
0.137
217208PARK ELE C
Solar/Wind Harmer
0.026
966261AG1-495 GEN
Solar/Wind Harmer
3.294
20674628WNG_W3-110
Solar/Wind Harmer
0.367
963071AG1-156 GEN
Solar/Wind Harmer
6.215
209023WIENIPP1
Adder
6.634
209025WIENIPP3
Adder
3.312
316447AC1-158 HLD
Solar/Wind Helper
2.741
232926CRISFLD1
Adder
3.753
231940T-011
Adder
1.425
234041AC1-190 GEN
Solar/Wind Harmer
17.1
228201CARL#2CT
Adder
10.027
228200CARL#1CT
Adder
9.536
219904AC1-010 C
Solar/Wind Harmer
0.518
219906AC1-017 C
Solar/Wind Harmer
0.295
213815MOSER1-3
Adder
4.633
213815MOSER1-3
Adder
4.633
20720828JCB_W4-025
Solar/Wind Harmer
0.567
20714828MDF_W3-079
Solar/Wind Harmer
0.364
219817TRENTONSOL C
Solar/Wind Harmer
1.29
20641628MLH_W1-032
Solar/Wind Harmer
0.34
20742028HF_AC1-207
Solar/Wind Harmer
0.9
218438BLK ROCK C
Solar/Wind Harmer
0.153
972260AH1-715 GEN1
Adder
14.518
972261AH1-715 GEN2
Adder
16.642
217202FBANKSOLAR C
Solar/Wind Harmer
0.075
217201HACKENSOLA C
Solar/Wind Harmer
0.074
217206BARNGR HS C
Solar/Wind Harmer
0.031
217204WCALDSOLAR C
Solar/Wind Harmer
0.073
20674828DL_W4-046
Solar/Wind Harmer
0.562
20634528N27_Y2-018
Solar/Wind Harmer
0.23
232406W1-004 FULL
Solar/Wind Harmer
1.911
232434Z2-077 GEN
Solar/Wind Harmer
0.478
233964AF2-378 GEN
Solar/Wind Harmer
0.244
232422X3-066 FULL
Solar/Wind Harmer
0.471
230415AB2-049 C
Solar/Wind Harmer
0.272
219291REEVESSOUT C
Solar/Wind Harmer
0.082
219236SOUTHERNHQ C
Solar/Wind Harmer
0.091
213815MOSER1-3
Adder
4.633
20714928UPF_X1-085
Solar/Wind Harmer
0.498
219114HARTZY_C
Solar/Wind Harmer
1.018
219918AC2-009 C
Solar/Wind Harmer
0.03
20674528F3S_W2-016
Solar/Wind Harmer
1.386
209025WIENIPP3
Adder
3.245
200052ROCKSP 1
50/50
4.909
200053ROCKSP 2
50/50
4.813
233940AF2-379 C
Solar/Wind Harmer
0.356
230434AG1-499 GEN
Solar/Wind Harmer
0.829
219258KINSLEYDEP C
Solar/Wind Harmer
0.447
213942SCHUYLKILL
Adder
4.922
213942SCHUYLKILL
Adder
3.764
213957STHWK3-4
Adder
3.756
213957STHWK3-4
Adder
3.756
213561DLWR9-10
Adder
4.787
213561DLWR9-10
Adder
3.661
219610FLORENCE C
Solar/Wind Harmer
1.81
963401AG1-189 GEN
Solar/Wind Harmer
2.809
971189AH1-054 GEN
Solar/Wind Harmer
1.452
20716228APLW2-078
Solar/Wind Harmer
1.02
20673828FLE_V3-070
Solar/Wind Harmer
0.49
20676128MHD_W3-029
Solar/Wind Harmer
0.495
3141426STAFORD
Solar/Wind Helper
0.049
200054ROCKSP 3
50/50
4.966
232408W1-005 C
Solar/Wind Harmer
1.911
232917OH NUG6
Adder
16.811
232915OH NUG4
Adder
16.774
972177AH1-672 GEN
Solar/Wind Harmer
25.657
233944AB2-135 GEN
Solar/Wind Harmer
9.85
213958STHWK5-6
Adder
3.756
219907AC1-030 C
Solar/Wind Harmer
0.186
20716028EGP_W2-019
Solar/Wind Harmer
0.581
207522AF2-254 C
Solar/Wind Harmer
1.796
218428ETC SOLAR C
Solar/Wind Harmer
0.038
219908AB1-139 C
Solar/Wind Harmer
0.406
972275AH1-722 GEN
Adder
33.331
20673628F1S_V4-069
Solar/Wind Harmer
0.186
207528AF2-192 GEN
Solar/Wind Harmer
1.318
217186ESSEX_G9
Adder
3.984
217083KRNY_132
Adder
9.379
20676228FRD_X1-012
Solar/Wind Harmer
0.535
20675828AU_W4-064
Solar/Wind Harmer
0.155
20675728RH_W2-091
Solar/Wind Harmer
0.505
207484AF2-139 C O1
Solar/Wind Harmer
0.419
208909MACR G3
Adder
125.696
209010PEIP 1
Adder
0.415
316415AF1-147_GEN2
Solar/Wind Helper
0.787
238175AF1-290_GEN
Solar/Wind Helper
0.122
232410W1-006 C
Solar/Wind Harmer
1.911
233946AB2-136 GEN
Solar/Wind Harmer
7.617
232899W1-062
Adder
18.339
233952AC2-187 GEN
Solar/Wind Harmer
2.143
233954AC2-188 GEN
Solar/Wind Harmer
2.143
233984AB2-036 GEN
Solar/Wind Harmer
23.628
233930AB2-032 GEN
Solar/Wind Harmer
1.566
233982AB2-133 GEN
Solar/Wind Harmer
9.146
230511AF1-262
Solar/Wind Harmer
0.264
228307PCLP GT
Adder
17.375
213587EDDYSTN3
Adder
114.005
228754AB1-001 C
Solar/Wind Harmer
0.198
219272CLEANLIGHT C
Solar/Wind Harmer
0.249
217081WEATEXAS C
Solar/Wind Harmer
0.088
217083KRNY_132
Adder
9.319
207471AF2-354 C
Solar/Wind Harmer
0.444
20675928HOL_W4-097
Solar/Wind Harmer
0.108
209010PEIP 1
Adder
2.283
209010PEIP 1
Adder
0.334
316411AF1-147_GEN1
Solar/Wind Helper
0.787
200203Y1-065-STG
50/50
13.515
200055ROCKSP 4
50/50
4.881
232914OH NUG3
Adder
16.886
232916OH NUG5
Adder
16.886
233939AC1-091 C
Solar/Wind Harmer
5.116
233933AB2-153 GEN
Solar/Wind Harmer
2.114
219623KINSLEYBEA C
Solar/Wind Harmer
0.591
213958STHWK5-6
Adder
3.756
20716428NHV_W2-082
Solar/Wind Harmer
2.226
963391AG1-188 GEN
Solar/Wind Harmer
4.617
219612MATRIX C
Solar/Wind Harmer
0.207
20716928W4-060COL
Solar/Wind Harmer
0.798
217213AMBOY SO C
Solar/Wind Harmer
0.135
20673728F2S_V4-070
Solar/Wind Harmer
0.186
207510AF2-138 C
Solar/Wind Harmer
1.618
207437AD2-070 GEN
Solar/Wind Harmer
0.25
20671928W4-073
Solar/Wind Harmer
0.354
20633028GILCT9
Adder
22.995
20465427SHAW CT
Adder
3.143
209116AE2-175 GEN
Solar/Wind Harmer
3.106
970095AG2-074 GEN
Solar/Wind Harmer
3.936
3141196NOKESVL
Solar/Wind Helper
0.919
233998TM1NIN_3.36
Solar/Wind Harmer
1.905
232404W1-003 C
Solar/Wind Harmer
1.911
232919VN10
Adder
5.364
233970AC1-092 C
Solar/Wind Harmer
5.116
232900DEMECSMY
Adder
17.59
231917EM10
Adder
4.171
970997AG2-616 GEN
Solar/Wind Harmer
13.921
213497CHSTR7-9
Adder
3.914
213497CHSTR7-9
Adder
3.914
213560DLW11-12
Adder
3.661
219222BRL12CT2
Adder
11.669
20717128DIX_Z2-102
Solar/Wind Harmer
1.649
20715828PEM_W1-120
Solar/Wind Harmer
0.666
963711AG1-223 GEN
Solar/Wind Harmer
1.763
219276PARKLANDSO C
Solar/Wind Harmer
0.547
20715228NPK_W1-113
Solar/Wind Harmer
0.496
20720528MAN_W1-024
Solar/Wind Harmer
0.293
219919AE1-041 FULL
Solar/Wind Harmer
0.043
217121ECCF
Adder
0.438
20676728BRNX1-095
Solar/Wind Harmer
0.17
20676328BVR_Y1-020
Solar/Wind Harmer
0.303
20674928WA_W3-044
Solar/Wind Harmer
0.417
971519AH1-257 GEN
Solar/Wind Harmer
2.146
207518AF1-320_GEN
Solar/Wind Harmer
3.054
20465127PORT CT
Adder
2.478
316044AC1-158 PL1
Solar/Wind Helper
1.245
200034PCHBTM 2
50/50
40.459
200205Y1-065-CTG2
50/50
7.804
232428Y3-058 C
Solar/Wind Harmer
1.592
234015AF2-250 C
Solar/Wind Harmer
0.23
232424Y1-079 C
Solar/Wind Harmer
1.066
228251CARLLS#4
Adder
0.92
228351V2-046C
Solar/Wind Harmer
2.917
230433AD2-135 GEN
Solar/Wind Harmer
0.146
213589EDDYSTN4
Adder
114.051
219287REEVESEAST C
Solar/Wind Harmer
1.826
213535CROYDN11
Adder
13.353
214067T20SOLAR
Solar/Wind Harmer
0.321
20636128O CRK C2
Adder
8.006
207459AE1-142 C O1
Solar/Wind Harmer
1.287
20628028LAKEHURS
Adder
1.156
217197RE CRAN C
Solar/Wind Harmer
0.605
924131AB2-057 GEN
Solar/Wind Harmer
1.13
20635128RRCT3&4
Adder
12.236
20635128RRCT3&4
Adder
10.674
218419LINDEN_G6
Adder
18.131
219035LINDEN_G8
Adder
17.137
20675428EAM_W2-061
Solar/Wind Harmer
0.196
972237AH1-703 GEN
Adder
10.218
20465127PORT CT
Adder
3.289
316450AC1-158 RIC
Solar/Wind Helper
0.332
232921TASLEY2G
Adder
9.869
233972AC1-094 C
Solar/Wind Harmer
4.108
233950AC2-186 GEN
Solar/Wind Harmer
1.072
228711V2-041C
Solar/Wind Harmer
0.882
213497CHSTR7-9
Adder
3.914
219921AF1-264
Solar/Wind Harmer
0.199
218660EHAMPSOLAR C
Solar/Wind Harmer
0.238
219914AD2-027 C
Solar/Wind Harmer
0.816
219688LUMSOLAR_S C
Solar/Wind Harmer
0.274
213560DLW11-12
Adder
3.661
207454AA2-184 E
Solar/Wind Harmer
1.156
20635928PARLN3&4
Adder
3.696
217169METRODIV C
Solar/Wind Harmer
0.04
963161AG1-165 GEN
Solar/Wind Harmer
0.615
208972BECR K09
Solar/Wind Harmer
0.641
G-007ALTFEXP_G-007A->PJM
CMTX
55.987
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.052
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.562
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.209
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.18
VTFLTFEXP_VFT->PJM
CMTX
138.123
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.091
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.329

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019E_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019E_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.91 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5462.93
MW Contribution:
13.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232434Z2-077 GEN
Solar/Wind Harmer
0.434
232406W1-004 FULL
Solar/Wind Harmer
1.737
233964AF2-378 GEN
Solar/Wind Harmer
0.221
232422X3-066 FULL
Solar/Wind Harmer
0.427
230415AB2-049 C
Solar/Wind Harmer
0.277
219291REEVESSOUT C
Solar/Wind Harmer
0.086
219236SOUTHERNHQ C
Solar/Wind Harmer
0.096
213815MOSER1-3
Adder
4.95
20714928UPF_X1-085
Solar/Wind Harmer
0.561
219114HARTZY_C
Solar/Wind Harmer
1.146
219918AC2-009 C
Solar/Wind Harmer
0.035
20674528F3S_W2-016
Solar/Wind Harmer
1.838
209025WIENIPP3
Adder
6.232
209142AF1-226 GEN
Solar/Wind Harmer
6.458
205941AD2-115 GEN
Solar/Wind Harmer
0.964
227287AC2-120 GEN
Solar/Wind Helper
0.513
233973AC2-185 C
Solar/Wind Harmer
9.43
970695AG2-447 GEN
Solar/Wind Harmer
6.238
233987AB2-037 GEN
Solar/Wind Harmer
19.759
233923SMA
Solar/Wind Harmer
6.347
233997TMININ_4.2
Solar/Wind Harmer
1.731
232907VN8
Adder
52.14
232417X3-008 C
Solar/Wind Harmer
1.949
200200DELTA2 CT1
50/50
5.62
200193DELTA CT2
50/50
3.14
200203Y1-065-STG
50/50
11.128
232926CRISFLD1
Adder
3.409
231940T-011
Adder
1.295
234041AC1-190 GEN
Solar/Wind Harmer
15.52
228201CARL#2CT
Adder
10.119
228200CARL#1CT
Adder
9.623
219904AC1-010 C
Solar/Wind Harmer
0.539
219906AC1-017 C
Solar/Wind Harmer
0.314
213815MOSER1-3
Adder
4.95
213815MOSER1-3
Adder
4.95
20720828JCB_W4-025
Solar/Wind Harmer
0.628
20714828MDF_W3-079
Solar/Wind Harmer
0.418
219817TRENTONSOL C
Solar/Wind Harmer
1.5
20641628MLH_W1-032
Solar/Wind Harmer
0.399
20742028HF_AC1-207
Solar/Wind Harmer
1.063
218438BLK ROCK C
Solar/Wind Harmer
0.184
972260AH1-715 GEN1
Adder
18.301
972261AH1-715 GEN2
Adder
21.231
217202FBANKSOLAR C
Solar/Wind Harmer
0.097
217201HACKENSOLA C
Solar/Wind Harmer
0.097
217206BARNGR HS C
Solar/Wind Harmer
0.041
217204WCALDSOLAR C
Solar/Wind Harmer
0.096
20674828DL_W4-046
Solar/Wind Harmer
0.825
20634528N27_Y2-018
Solar/Wind Harmer
0.343
232904IR4
Adder
140.512
232432Z2-076 GEN
Solar/Wind Harmer
0.229
233968AD2-076_GEN
Solar/Wind Harmer
11.349
231919CHRIST1
Adder
7.292
231920CHRIST2
Adder
7.13
230422AE1-104_GEN1
Solar/Wind Harmer
49.478
230425AE1-104_GEN2
Solar/Wind Harmer
49.478
230430AE1-229_GEN
Solar/Wind Harmer
41.994
230407AD2-065 C
Solar/Wind Harmer
0.192
20720728JCB_W1-129
Solar/Wind Harmer
0.413
207500AE2-000G1
Solar/Wind Harmer
43.606
970025AG2-016 GEN
Solar/Wind Harmer
3.914
20714428HOW_X1-037
Solar/Wind Harmer
1.681
218449LINSOLAR C
Solar/Wind Harmer
1.334
217147KRNY_1212
Adder
11.647
217147KRNY_1212
Adder
11.439
217146KRNY_1234
Adder
11.413
217146KRNY_1234
Adder
11.335
964851AG1-348 GEN
Solar/Wind Harmer
1.74
207408W3-077 C
Solar/Wind Harmer
0.642
20462827N BANGR8
Adder
0.904
209026WIENIPP4
Adder
6.296
209054AE2-059 GEN
Solar/Wind Harmer
1.841
20486527WR_V4-052
Adder
1.044
209067AE2-060 GEN
Solar/Wind Harmer
1.216
200917MEHOOPANY_G
Solar/Wind Harmer
3.765
315651AD1-115 GEN
Solar/Wind Helper
1.04
3141783LANCAST
Solar/Wind Helper
0.178
3141783LANCAST
Solar/Wind Helper
0.119
316059AD1-063 C
Solar/Wind Helper
0.299
238169AE2-226 GEN1
Solar/Wind Helper
0.718
238170AE2-226 GEN2
Solar/Wind Helper
0.718
313526AB2-022
Solar/Wind Helper
0.44
3146206CASHIE
Solar/Wind Helper
0.281
961941AG1-037 GEN
Solar/Wind Helper
0.094
3138266HYDRAULIC
Solar/Wind Helper
0.013
3138266HYDRAULIC
Solar/Wind Helper
0.008
3146043SEABORD
Solar/Wind Helper
0.28
3145683EARLEYS
Solar/Wind Helper
0.559
3145683EARLEYS
Solar/Wind Helper
0.279
3145683EARLEYS
Solar/Wind Helper
0.279
316486AD2-202 GEN
Solar/Wind Helper
0.398
316274AC1-208 GEN
Solar/Wind Helper
1.681
3147173SINAI
Solar/Wind Helper
0.268
3147243WELCO
Solar/Wind Helper
0.168
3148463FAIRFLD
Solar/Wind Helper
0.266
270455AD2-022 GEN
Solar/Wind Helper
1.49
270197AD1-017 GEN1
Solar/Wind Helper
1.336
237030AB1-096 C
Solar/Wind Helper
0.058
237025AB1-124 C
Solar/Wind Helper
0.143
200195DELTA ST
50/50
4.852
232920IR10
Adder
5.492
233901CHERRYDALE C
Solar/Wind Harmer
1.954
200035PCHBTM 3
50/50
32.261
233971AC1-093 C
Solar/Wind Harmer
4.432
232918OH NUG7
Adder
15.24
200202DELTA2 ST
50/50
9.518
200052ROCKSP 1
50/50
4.043
200053ROCKSP 2
50/50
3.963
233940AF2-379 C
Solar/Wind Harmer
0.324
200201DELTA2 CT2
50/50
5.62
232899W1-062
Adder
16.714
232410W1-006 C
Solar/Wind Harmer
1.737
233946AB2-136 GEN
Solar/Wind Harmer
6.914
233952AC2-187 GEN
Solar/Wind Harmer
1.949
233954AC2-188 GEN
Solar/Wind Harmer
1.949
233984AB2-036 GEN
Solar/Wind Harmer
21.408
233930AB2-032 GEN
Solar/Wind Harmer
1.418
233982AB2-133 GEN
Solar/Wind Harmer
8.287
230511AF1-262
Solar/Wind Harmer
0.268
228754AB1-001 C
Solar/Wind Harmer
0.203
228307PCLP GT
Adder
17.631
219272CLEANLIGHT C
Solar/Wind Harmer
0.261
213587EDDYSTN3
Adder
113.248
217081WEATEXAS C
Solar/Wind Harmer
0.114
217083KRNY_132
Adder
12.167
207471AF2-354 C
Solar/Wind Harmer
0.653
20675928HOL_W4-097
Solar/Wind Harmer
0.165
209010PEIP 1
Adder
4.136
209010PEIP 1
Adder
0.606
961541AF2-445A GEN
Solar/Wind Harmer
3.712
961431AF2-434 GEN
Solar/Wind Harmer
1.116
209130AF1-271A GEN
Solar/Wind Harmer
3.025
223402AF1-300 C
Solar/Wind Helper
0.532
316411AF1-147_GEN1
Solar/Wind Helper
1.087
200192DELTA CT1
50/50
3.14
200054ROCKSP 3
50/50
4.089
972177AH1-672 GEN
Solar/Wind Harmer
23.34
232408W1-005 C
Solar/Wind Harmer
1.737
232917OH NUG6
Adder
15.275
232915OH NUG4
Adder
15.24
233944AB2-135 GEN
Solar/Wind Harmer
8.93
219907AC1-030 C
Solar/Wind Harmer
0.196
213958STHWK5-6
Adder
3.834
20716028EGP_W2-019
Solar/Wind Harmer
0.643
207522AF2-254 C
Solar/Wind Harmer
1.989
218428ETC SOLAR C
Solar/Wind Harmer
0.048
200055ROCKSP 4
50/50
4.019
233939AC1-091 C
Solar/Wind Harmer
4.668
232914OH NUG3
Adder
15.343
232916OH NUG5
Adder
15.343
233933AB2-153 GEN
Solar/Wind Harmer
1.915
219623KINSLEYBEA C
Solar/Wind Harmer
0.612
213958STHWK5-6
Adder
3.834
20716428NHV_W2-082
Solar/Wind Harmer
2.464
963391AG1-188 GEN
Solar/Wind Harmer
5.177
219612MATRIX C
Solar/Wind Harmer
0.248
20716928W4-060COL
Solar/Wind Harmer
0.959
217213AMBOY SO C
Solar/Wind Harmer
0.169
20673728F2S_V4-070
Solar/Wind Harmer
0.238
207510AF2-138 C
Solar/Wind Harmer
2.292
207437AD2-070 GEN
Solar/Wind Harmer
0.381
20671928W4-073
Solar/Wind Harmer
0.546
20633028GILCT9
Adder
35.572
20465427SHAW CT
Adder
4.868
209116AE2-175 GEN
Solar/Wind Harmer
5.114
970095AG2-074 GEN
Solar/Wind Harmer
7.367
961421AF2-433 GEN
Solar/Wind Harmer
1.116
209093AE2-110 GEN
Solar/Wind Harmer
2.789
209120AE2-241 GEN
Solar/Wind Harmer
3.69
946691AF1-333 GEN
Solar/Wind Harmer
1.079
946741AF1-338 GEN
Solar/Wind Harmer
1.079
972221AH1-695 GEN
Adder
101.532
226910AB2-157 C
Solar/Wind Helper
0.021
3141196NOKESVL
Solar/Wind Helper
1.272
316077AC2-138 C
Solar/Wind Helper
0.282
316484AD2-074 GEN
Solar/Wind Helper
0.575
316075AC2-137 C
Solar/Wind Helper
0.451
966621AG1-532 GEN
Solar/Wind Helper
0.254
942461AE2-259 GEN
Solar/Wind Helper
1.878
316317KELFORD C
Solar/Wind Helper
0.25
3145823KELFORD
Solar/Wind Helper
0.278
315821AE2-092 GEN
Solar/Wind Helper
2.579
3145796HORNRTN
Solar/Wind Helper
1.108
3145796HORNRTN
Solar/Wind Helper
0.277
316212AC1-099_GEN
Solar/Wind Helper
1.238
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
23583801GRNGAP
Solar/Wind Helper
4.532
316123AC1-075 GEN
Solar/Wind Helper
1.588
3147312GRETNA
Solar/Wind Helper
0.05
237085AD2-009_GEN
Solar/Wind Helper
1.436
238126S14_GEN_1
Solar/Wind Helper
0.637
966881AG1-559 GEN
Solar/Wind Helper
0.411
316473AC1-191 GEN
Solar/Wind Helper
1.82
3142946ENON
Solar/Wind Helper
0.098
3145336SMITFLD
Solar/Wind Helper
0.116
316017AA1-139 ULT1
Solar/Wind Helper
1.323
3146456SLIGO L269
Solar/Wind Helper
0.289
3145273HOLLAND
Solar/Wind Helper
0.215
3146376EDENTON
Solar/Wind Helper
0.285
3146206CASHIE
Solar/Wind Helper
0.281
3146173TUNIS
Solar/Wind Helper
0.28
316181AB2-040 GEN
Solar/Wind Helper
2.004
3147043LAWRENC
Solar/Wind Helper
0.167
3147133PAMPLIN
Solar/Wind Helper
0.872
316478AD1-087 GEN
Solar/Wind Helper
1.359
316499AE2-029_GEN
Solar/Wind Helper
0.923
316420AA1-050 GEN
Solar/Wind Helper
1.566
3146073TAR RVR
Solar/Wind Helper
0.272
3146083TARBORO
Solar/Wind Helper
0.272
3138543CONSLDL
Solar/Wind Helper
0.179
316095T157 G97
Solar/Wind Helper
1.231
316003AC1-222 GEN
Solar/Wind Helper
1.16
316222AC1-221 GEN
Solar/Wind Helper
1.502
316283AC2-100 C
Solar/Wind Helper
1.399
238109AE1-109 GEN2
Solar/Wind Helper
0.095
23777801MSM_W1-116
Solar/Wind Helper
0.106
943811AF1-049 GEN
Solar/Wind Helper
1.492
270336AE1-100 GEN
Solar/Wind Helper
1.039
238120AE2-309 GEN
Solar/Wind Helper
0.408
238185AF2-356 C
Solar/Wind Helper
1.927
200204Y1-065-CTG1
50/50
6.426
233918AB1-142 GEN
Solar/Wind Harmer
1.685
228206SHRMN CT
Adder
24.494
228260V4-054C
Solar/Wind Harmer
1.51
228729W2-030 C
Solar/Wind Harmer
0.843
219686LUMSOLAR_N C
Solar/Wind Harmer
0.289
219348LDSOLAR C
Solar/Wind Harmer
0.839
213611FALLS1-3
Adder
4.906
214194N WALES4
Adder
1.176
20720428HOL_W1-112
Solar/Wind Harmer
0.468
20635828PARLN1&2
Adder
9.946
20635028RRCT1&2
Adder
15.806
218524CNTRALGAS1 C
Solar/Wind Harmer
0.494
217209CENTRL HS C
Solar/Wind Harmer
0.059
20671828STAW2-080
Solar/Wind Harmer
0.138
207439AE1-081 C O1
Solar/Wind Harmer
0.077
207530AG1-191 GEN
Solar/Wind Harmer
1.769
211065PSPA IPP
Solar/Wind Harmer
0.556
961301AF2-421 GEN
Solar/Wind Harmer
1.182
963151AG1-164 GEN
Solar/Wind Harmer
1.182
961341AF2-425 GEN
Solar/Wind Harmer
1.119
212507AE2-042_GEN
Solar/Wind Harmer
3.264
20328326MANOR_T86
Adder
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.457
3141726DUNNSVL
Solar/Wind Helper
1.194
316132AB2-190 GEN1
Solar/Wind Helper
1.675
315773AC2-141 GEN
Solar/Wind Helper
6.262
316036AC1-147 C
Solar/Wind Helper
0.442
3146516WINFALL
Solar/Wind Helper
0.929
3146516WINFALL
Solar/Wind Helper
0.287
3145893MURPHYS
Solar/Wind Helper
1.123
3146776BUCKING
Solar/Wind Helper
0.112
315607AA1-063A GEN
Solar/Wind Helper
1.598
3146263WOODLND
Solar/Wind Helper
0.279
3145963POPLR C
Solar/Wind Helper
0.278
233935AB2-179 C
Solar/Wind Harmer
4.154
219221BRL12CT1
Adder
12.513
219223BRL12CT3
Adder
12.513
959561AF2-247 GEN
Solar/Wind Harmer
0.673
20715728PEM_W1-119
Solar/Wind Harmer
0.74
20636028O CRK C1
Adder
9.784
971667AH1-334 GEN
Solar/Wind Harmer
3.784
219727YARDVSOLFA C
Solar/Wind Harmer
1.248
20635828PARLN1&2
Adder
4.505
219249CENTRALDIV C
Solar/Wind Harmer
0.053
315976AC1-164 GENA
Solar/Wind Helper
3.81
316169AC1-164_GENC
Solar/Wind Helper
3.291
3142946ENON
Solar/Wind Helper
0.03
316294AC1-161 GEN
Solar/Wind Helper
5.321
316349AD2-085 GEN
Solar/Wind Helper
1.324
3146386ELIZ CT
Solar/Wind Helper
0.288
316431W1029_GEN1
Solar/Wind Helper
1.161
316433W1029_GEN2
Solar/Wind Helper
1.161
238147AE2-230_GEN1
Solar/Wind Helper
0.497
316365GEN2_N
Solar/Wind Helper
1.073
3146173TUNIS
Solar/Wind Helper
0.28
3146173TUNIS
Solar/Wind Helper
0.28
3147133PAMPLIN
Solar/Wind Helper
0.278
3147133PAMPLIN
Solar/Wind Helper
0.222
3146843MT LREL
Solar/Wind Helper
0.271
3146843MT LREL
Solar/Wind Helper
0.271
316097T157 G90
Solar/Wind Helper
1.231
237080AD1-060 GEN
Solar/Wind Helper
0.312
270214AC2-123 GEN
Solar/Wind Helper
0.81
207442AE1-156 GEN
Solar/Wind Harmer
0.984
217211CAMDEN ST C
Solar/Wind Harmer
0.032
217194REDH C
Solar/Wind Harmer
0.648
207511W3-106 GEN
Solar/Wind Harmer
0.425
971007AG2-625 GEN
Solar/Wind Harmer
3.271
20466127PORT 5CT
Adder
33.565
20674128FR_U2-059
Solar/Wind Harmer
0.232
211065PSPA IPP
Solar/Wind Harmer
0.556
957921AF2-086 GEN
Solar/Wind Harmer
1.085
3132273ORANGE
Solar/Wind Helper
0.061
316223AC1-118
Solar/Wind Helper
0.461
3144536CHRHLND
Solar/Wind Helper
0.044
3142956BIRDNECK
Solar/Wind Helper
0.195
316305AF2-043 C
Solar/Wind Helper
0.389
316320Y1-086
Solar/Wind Helper
0.129
23546401DTGZ2-030
Solar/Wind Helper
0.09
3146516WINFALL
Solar/Wind Helper
0.287
315735AD1-075 GEN1
Solar/Wind Helper
1.613
3145893MURPHYS
Solar/Wind Helper
0.101
3145893MURPHYS
Solar/Wind Helper
0.281
3146776BUCKING
Solar/Wind Helper
0.101
3146263WOODLND
Solar/Wind Helper
0.279
3145963POPLR C
Solar/Wind Helper
0.278
316011AB1-132 GEN
Solar/Wind Helper
2.999
270494AE1-108_GEN
Solar/Wind Helper
3.639
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.271
237038AE2-054 C
Solar/Wind Helper
0.243
270173AC1-122 GEN
Solar/Wind Helper
1.674
232913OH NUG2
Adder
15.138
231906DC3 NUG
Adder
23.95
231907DC10
Adder
5.979
970597AG2-380 GEN
Solar/Wind Harmer
7.126
972141AH1-641 GEN
Solar/Wind Harmer
4.222
213611FALLS1-3
Adder
4.906
213611FALLS1-3
Adder
4.906
20715028HAN_X4-015
Solar/Wind Harmer
0.413
207507AE2-000G3
Solar/Wind Harmer
43.606
207445AB1-138_GEN
Solar/Wind Harmer
0.797
20720628TIN_W1-124
Solar/Wind Harmer
1.353
971521AH1-258 GEN
Solar/Wind Harmer
3.667
20675528CPH_W2-050
Solar/Wind Harmer
0.764
20676428JCR_X2-075
Solar/Wind Harmer
0.452
217086KRNY_131
Adder
12.141
20675128HRM_W1-127
Solar/Wind Harmer
0.215
209029WAYMART-WD
Solar/Wind Harmer
3.021
959421AF2-233 GEN
Solar/Wind Harmer
1.076
203926AA2-133 GEN
Adder
2.289
226929AD2-058 GEN
Solar/Wind Helper
0.145
3138216PACIFIC
Solar/Wind Helper
0.054
316164AC1-076 GEN
Solar/Wind Helper
1.472
3141813NORNECK
Solar/Wind Helper
0.299
957601AF2-054 GEN
Solar/Wind Helper
0.396
316233AE1-074 FULL
Solar/Wind Helper
0.45
316018AA1-139 ULT2
Solar/Wind Helper
1.246
315800Z1-036_GEN1
Solar/Wind Helper
1.569
315732AD1-074 GEN1
Solar/Wind Helper
3.225
3145893MURPHYS
Solar/Wind Helper
0.758
3145893MURPHYS
Solar/Wind Helper
0.281
316463AE2-346 GEN
Solar/Wind Helper
0.256
3145513AHOSKIE
Solar/Wind Helper
0.125
3145513AHOSKIE
Solar/Wind Helper
0.28
3137643SOCKMAN
Solar/Wind Helper
1.112
316426AA2-053 GEN
Solar/Wind Helper
1.591
316174AB2-169 GEN
Solar/Wind Helper
0.711
3144303KENBRDG
Solar/Wind Helper
0.221
316327AA2-057 GEN
Solar/Wind Helper
1.562
270457AD2-023 GEN
Solar/Wind Helper
0.982
23779801AA1-109
Solar/Wind Helper
0.183
238118U2-030_1
Solar/Wind Helper
0.261
232905CHERITON_25
Adder
4.262
233994AC2-023 GEN
Solar/Wind Harmer
4.66
234036AF2-325 C
Solar/Wind Harmer
1.589
232910NRG_G1
Adder
14.893
234014AF1-036_GEN
Solar/Wind Harmer
4.632
232436AB1-176 C
Solar/Wind Harmer
0.392
972233AH1-701 GEN
Adder
6.088
219912AD2-042 GEN
Solar/Wind Harmer
1.13
219607WPEMNERT C
Solar/Wind Harmer
0.587
219304NAMERICA C
Solar/Wind Harmer
0.435
20635028RRCT1&2
Adder
15.563
218418LINDEN_G5
Adder
22.854
219036LINDEN_G7
Adder
22.179
217086KRNY_131
Adder
12.271
20674328GAR_V4-001
Solar/Wind Harmer
0.141
946751AF1-339 GEN
Solar/Wind Harmer
1.079
316006AB2-029 C
Solar/Wind Helper
0.149
316045AC1-158 PL2
Solar/Wind Helper
5.511
966871AG1-558 GEN
Solar/Wind Helper
0.402
316156AD2-030 GEN
Solar/Wind Helper
0.447
315666AE1-190 GEN
Solar/Wind Helper
0.398
316240AF1-291 C
Solar/Wind Helper
0.394
316313AB2-026
Solar/Wind Helper
0.442
316435W1029_GEN3
Solar/Wind Helper
1.161
238149AF1-291A_GEN
Solar/Wind Helper
0.142
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
315614AA2-178 GEN
Solar/Wind Helper
1.73
3145893MURPHYS
Solar/Wind Helper
0.403
3145893MURPHYS
Solar/Wind Helper
0.506
3146776BUCKING
Solar/Wind Helper
1.123
3146776BUCKING
Solar/Wind Helper
0.091
316140AB2-099
Solar/Wind Helper
0.107
316005AA1-067
Solar/Wind Helper
0.314
316118AC1-105 GEN
Solar/Wind Helper
1.051
235531U2-073 GEN
Solar/Wind Helper
2.561
235054AD2-180 GEN
Solar/Wind Helper
1.52
316494AC1-189 GEN
Solar/Wind Helper
1.667
961671AG1-007 GEN
Solar/Wind Helper
0.195
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.217
238108AE1-109 GEN1
Solar/Wind Helper
0.095
237001AB1-127_GEN
Solar/Wind Helper
0.385
232901NORTHST
Adder
14.493
234033AF1-007_GEN
Solar/Wind Harmer
64.639
233996TM1833_GEN
Solar/Wind Harmer
1.731
232426Y1-080 FULL
Solar/Wind Harmer
0.331
232902EASTMUNI
Adder
22.499
234012AE2-112_GEN
Solar/Wind Harmer
3.937
972251AH1-710 GEN
Adder
76.383
231918WEST 1
Adder
5.544
228732V1-021 C
Adder
0.279
228400MICK 1CT
Adder
17.12
219766PARADISE C
Solar/Wind Harmer
0.449
20714528FRN_Y2-051
Solar/Wind Harmer
0.404
219680HOPEWELLV C1
Solar/Wind Harmer
0.103
218440SUMMTASSOC C
Solar/Wind Harmer
0.171
217208PARK ELE C
Solar/Wind Harmer
0.033
966261AG1-495 GEN
Solar/Wind Harmer
4.539
20674628WNG_W3-110
Solar/Wind Harmer
0.52
209023WIENIPP1
Adder
12.742
209025WIENIPP3
Adder
6.36
963071AG1-156 GEN
Solar/Wind Harmer
11.632
316447AC1-158 HLD
Solar/Wind Helper
3.79
316192AB2-158 GEN
Solar/Wind Helper
2.036
3142416OLDCHRC
Solar/Wind Helper
0.77
3142416OLDCHRC
Solar/Wind Helper
0.295
3141766HARMONY
Solar/Wind Helper
0.059
315975AC1-164 GENB
Solar/Wind Helper
0.113
3142433PROV 92
Solar/Wind Helper
1.181
3145336SMITFLD
Solar/Wind Helper
1.162
316375AC2-012 GEN
Solar/Wind Helper
0.763
3146456SLIGO L269
Solar/Wind Helper
0.289
3145663CRESWEL
Solar/Wind Helper
0.793
316023GEN1_S
Solar/Wind Helper
1.073
3146206CASHIE
Solar/Wind Helper
0.281
3146173TUNIS
Solar/Wind Helper
0.28
3156021HOLLOMANSOL
Solar/Wind Helper
2.135
3145683EARLEYS
Solar/Wind Helper
0.279
316131AB2-060 GEN
Solar/Wind Helper
1.68
3146083TARBORO
Solar/Wind Helper
0.272
316359AB2-059 GEN
Solar/Wind Helper
2.068
238110AE1-109 GEN3
Solar/Wind Helper
0.095
3147123OTTER R
Solar/Wind Helper
0.15
964991AG1-363 GEN
Solar/Wind Helper
3.563
235063AE1-101 C2
Solar/Wind Helper
1.421
200194DELTA CT3
50/50
3.14
233970AC1-092 C
Solar/Wind Harmer
4.668
232900DEMECSMY
Adder
16.032
232404W1-003 C
Solar/Wind Harmer
1.737
233998TM1NIN_3.36
Solar/Wind Harmer
1.731
232919VN10
Adder
4.87
231917EM10
Adder
3.863
970997AG2-616 GEN
Solar/Wind Harmer
14.073
213497CHSTR7-9
Adder
3.882
213497CHSTR7-9
Adder
3.882
213560DLW11-12
Adder
3.816
219222BRL12CT2
Adder
12.513
20717128DIX_Z2-102
Solar/Wind Harmer
1.829
20715828PEM_W1-120
Solar/Wind Harmer
0.74
963711AG1-223 GEN
Solar/Wind Harmer
2.026
219276PARKLANDSO C
Solar/Wind Harmer
0.629
20715228NPK_W1-113
Solar/Wind Harmer
0.584
230434AG1-499 GEN
Solar/Wind Harmer
0.844
219258KINSLEYDEP C
Solar/Wind Harmer
0.463
213942SCHUYLKILL
Adder
5.014
213942SCHUYLKILL
Adder
3.835
213957STHWK3-4
Adder
3.834
213957STHWK3-4
Adder
3.834
213561DLWR9-10
Adder
4.99
213561DLWR9-10
Adder
3.816
219610FLORENCE C
Solar/Wind Harmer
1.941
963401AG1-189 GEN
Solar/Wind Harmer
3.143
971189AH1-054 GEN
Solar/Wind Harmer
1.629
20716228APLW2-078
Solar/Wind Harmer
1.2
20673828FLE_V3-070
Solar/Wind Harmer
0.619
20676128MHD_W3-029
Solar/Wind Harmer
0.632
209027LOR2_Q27
Solar/Wind Harmer
5.166
964051AG1-259 GEN
Solar/Wind Harmer
1.443
964061AG1-260 GEN
Solar/Wind Harmer
1.443
208862AG1-362 C
Solar/Wind Harmer
0.705
20390726Y2-042
Adder
2.941
3141426STAFORD
Solar/Wind Helper
0.07
316468AD1-105 GEN
Solar/Wind Helper
1.452
3141913WHIT STONE
Solar/Wind Helper
0.296
957831AF2-077 GEN
Solar/Wind Helper
0.396
315697AD1-025 GEN
Solar/Wind Helper
3.344
315839AE2-212 C
Solar/Wind Helper
0.393
316316AC1-027 C
Solar/Wind Helper
0.458
316258AE1-075 C
Solar/Wind Helper
0.398
316322AB2-045
Solar/Wind Helper
0.314
3145796HORNRTN
Solar/Wind Helper
0.886
3145796HORNRTN
Solar/Wind Helper
0.111
316210AC1-098 GEN
Solar/Wind Helper
2.228
316238AB2-078_GEN
Solar/Wind Helper
0.37
316239AB2-077_GEN
Solar/Wind Helper
0.37
3145746EVERETS
Solar/Wind Helper
1.09
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3148133STUARTS
Solar/Wind Helper
0.164
3145573BETHELC
Solar/Wind Helper
0.272
3145573BETHELC
Solar/Wind Helper
0.272
316312AB1-027
Solar/Wind Helper
0.566
3143526WINTERP
Solar/Wind Helper
1.533
316185AD1-033 GEN
Solar/Wind Helper
1.365
3144356SAPONY
Solar/Wind Helper
0.513
316315AB2-025 C
Solar/Wind Helper
0.437
237061AD1-155 GEN
Solar/Wind Helper
1.79
3145796HORNRTN
Solar/Wind Helper
0.831
316237AB2-079_GEN
Solar/Wind Helper
0.37
235020AA1-095 C
Solar/Wind Helper
0.051
315687AD1-152 GEN
Solar/Wind Helper
1.474
316248AF1-058 C
Solar/Wind Helper
0.362
238221AF1-254 C O1
Solar/Wind Helper
0.258
270013AE1-250 PV
Solar/Wind Helper
0.924
20720528MAN_W1-024
Solar/Wind Harmer
0.345
219919AE1-041 FULL
Solar/Wind Harmer
0.054
217121ECCF
Adder
0.572
20676728BRNX1-095
Solar/Wind Harmer
0.23
20676328BVR_Y1-020
Solar/Wind Harmer
0.427
20674928WA_W3-044
Solar/Wind Harmer
0.614
971519AH1-257 GEN
Solar/Wind Harmer
3.206
207518AF1-320_GEN
Solar/Wind Harmer
4.635
20465127PORT CT
Adder
3.8
209018SUNBIPCT
Adder
8.014
20465527S.RDG CT
Adder
2.667
209137AF2-361 C
Solar/Wind Harmer
2.349
941421AE2-139 GEN
Solar/Wind Harmer
2.714
316044AC1-158 PL1
Solar/Wind Helper
1.722
3147666LOUISA
Solar/Wind Helper
1.21
316404AE1-155 C
Solar/Wind Helper
2.55
3138133OCRAN
Solar/Wind Helper
0.178
315662AE1-191 GEN
Solar/Wind Helper
1.593
316280AD1-041 GEN
Solar/Wind Helper
0.996
3142543TWELFTH
Solar/Wind Helper
0.028
3143226MDLTHAN
Solar/Wind Helper
0.294
316369SG1_INVT
Solar/Wind Helper
1.409
316381AD1-082 GEN
Solar/Wind Helper
1.506
319010AE1-072 C
Solar/Wind Helper
3.305
238152AF2-075_GEN
Solar/Wind Helper
0.709
315611Z1-036_GEN2
Solar/Wind Helper
1.569
3130156CHOWAN
Solar/Wind Helper
0.285
315816AE2-034 GEN
Solar/Wind Helper
1.297
315737AD1-076 GEN
Solar/Wind Helper
2.758
3146926FARMVIL
Solar/Wind Helper
0.168
316087AB2-174 GEN
Solar/Wind Helper
1.955
315785AD2-033 C
Solar/Wind Helper
3.223
23777901MDS_W4-102
Solar/Wind Helper
0.173
3146233WITAKRS
Solar/Wind Helper
1.082
270018AE2-047 C O1
Solar/Wind Helper
0.867
958121AF2-106 GEN
Solar/Wind Helper
1.718
238127S14_GEN_2
Solar/Wind Helper
0.637
219908AB1-139 C
Solar/Wind Harmer
0.508
972275AH1-722 GEN
Adder
42.015
20673628F1S_V4-069
Solar/Wind Harmer
0.238
207528AF2-192 GEN
Solar/Wind Harmer
1.682
217186ESSEX_G9
Adder
5.2
217083KRNY_132
Adder
12.245
20676228FRD_X1-012
Solar/Wind Harmer
0.761
20675828AU_W4-064
Solar/Wind Harmer
0.222
20675728RH_W2-091
Solar/Wind Harmer
0.764
207484AF2-139 C O1
Solar/Wind Harmer
0.639
208909MACR G3
Adder
200.108
209010PEIP 1
Adder
0.752
946731AF1-337 GEN
Solar/Wind Harmer
1.079
209008PAXT IPP
Adder
1.516
316415AF1-147_GEN2
Solar/Wind Helper
1.087
964211AG1-282 GEN
Solar/Wind Helper
0.402
238175AF1-290_GEN
Solar/Wind Helper
0.16
3143526WINTERP
Solar/Wind Helper
1.533
315671AE2-027_GEN
Solar/Wind Helper
2.364
316072AD1-144
Solar/Wind Helper
0.331
3145823KELFORD
Solar/Wind Helper
0.278
3145783HORNRTN
Solar/Wind Helper
0.277
3145796HORNRTN
Solar/Wind Helper
0.914
3145796HORNRTN
Solar/Wind Helper
0.277
316034AC1-036 C
Solar/Wind Helper
0.29
316129AC1-054 GEN
Solar/Wind Helper
1.367
3147983MERCK5
Solar/Wind Helper
0.11
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
270016AE1-250 BESS
Solar/Wind Helper
0.924
3147312GRETNA
Solar/Wind Helper
0.199
3146802CHATHAM
Solar/Wind Helper
0.187
233972AC1-094 C
Solar/Wind Harmer
3.748
232921TASLEY2G
Adder
8.967
233950AC2-186 GEN
Solar/Wind Harmer
0.975
228711V2-041C
Solar/Wind Harmer
0.888
219921AF1-264
Solar/Wind Harmer
0.206
218660EHAMPSOLAR C
Solar/Wind Harmer
0.249
213497CHSTR7-9
Adder
3.882
219688LUMSOLAR_S C
Solar/Wind Harmer
0.288
219914AD2-027 C
Solar/Wind Harmer
0.852
213560DLW11-12
Adder
3.816
207454AA2-184 E
Solar/Wind Harmer
1.357
20635928PARLN3&4
Adder
4.505
217169METRODIV C
Solar/Wind Harmer
0.052
963161AG1-165 GEN
Solar/Wind Harmer
1.182
208972BECR K09
Solar/Wind Harmer
1.232
961331AF2-424 GEN
Solar/Wind Harmer
1.119
209071AE2-133 GEN
Solar/Wind Harmer
1.821
3147666LOUISA
Solar/Wind Helper
0.695
3141906WESTMOR
Solar/Wind Helper
0.121
316458AB2-190 GEN2
Solar/Wind Helper
1.675
3144873MCLAUGH
Solar/Wind Helper
0.007
316246AF1-032 C
Solar/Wind Helper
0.331
316321Z2-027
Solar/Wind Helper
0.439
3146626S HERTFORD
Solar/Wind Helper
0.286
3146926FARMVIL
Solar/Wind Helper
0.168
3142666NORTHAMPTON
Solar/Wind Helper
0.278
316190AA2-174 GEN
Solar/Wind Helper
0.019
3145933PARMELE
Solar/Wind Helper
0.275
3148013FISHERV
Solar/Wind Helper
0.274
3146233WITAKRS
Solar/Wind Helper
0.293
3146233WITAKRS
Solar/Wind Helper
0.185
316197AC1-042 GEN
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.395
237002AB1-128_GEN
Solar/Wind Helper
0.388
232912OH NUG1
Adder
15.343
971195AH1-057 GEN
Solar/Wind Harmer
1.693
233955AB2-172 GEN
Solar/Wind Harmer
8.661
232813VAUGHN
Adder
1.017
231902DC CT7
Adder
19.147
233915AB1-141 GEN
Solar/Wind Harmer
1.685
970453AG2-297 GEN
Solar/Wind Harmer
4.089
964001AG1-254 GEN
Solar/Wind Harmer
10.68
228728W1-130C
Solar/Wind Harmer
0.971
227927V4-067C
Solar/Wind Harmer
0.29
219137THOSOLAR C
Solar/Wind Harmer
1.737
219615MILLCREEK C
Solar/Wind Harmer
0.335
219224BRL12CT4
Adder
12.513
207487AE2-000G4
Solar/Wind Harmer
43.606
207497AE2-000G2
Solar/Wind Harmer
43.606
219620RIDERU C
Solar/Wind Harmer
0.076
20635928PARLN3&4
Adder
9.946
218526CNTRALGAS2 C
Solar/Wind Harmer
0.495
217167KRNY_14
Adder
12.245
971009AG2-626 GEN
Solar/Wind Harmer
2.086
961261AF2-417 GEN
Solar/Wind Harmer
1.2
212266LOR1
Solar/Wind Harmer
1.369
959431AF2-234 GEN
Solar/Wind Harmer
2.152
20334726NME_Y1-047
Adder
2.531
3138133OCRAN
Solar/Wind Helper
0.089
3141873WAN 176
Solar/Wind Helper
0.059
3143873LANEXA
Solar/Wind Helper
0.177
316382AG1-145 C
Solar/Wind Helper
0.395
316159AE1-175 C
Solar/Wind Helper
0.446
316236AE1-162_GEN
Solar/Wind Helper
0.392
3143316POE
Solar/Wind Helper
1.15
316405AF2-144 C
Solar/Wind Helper
0.331
3146486SUNBURY
Solar/Wind Helper
0.288
3146486SUNBURY
Solar/Wind Helper
0.288
3145176PASQUOTANK
Solar/Wind Helper
0.178
3130156CHOWAN
Solar/Wind Helper
0.285
3130156CHOWAN
Solar/Wind Helper
0.285
3130546PLYMOUTH
Solar/Wind Helper
0.282
315733AD1-074 GEN2
Solar/Wind Helper
3.225
946281AF1-292 GEN
Solar/Wind Helper
0.281
3146033SCOT NK
Solar/Wind Helper
1.107
3148013FISHERV
Solar/Wind Helper
0.157
315616AA1-038_C
Solar/Wind Helper
1.207
23750701CROSSCHOOL
Solar/Wind Helper
1.107
200034PCHBTM 2
50/50
32.756
200205Y1-065-CTG2
50/50
6.426
234015AF2-250 C
Solar/Wind Harmer
0.209
232428Y3-058 C
Solar/Wind Harmer
1.447
232424Y1-079 C
Solar/Wind Harmer
0.966
228251CARLLS#4
Adder
0.928
230433AD2-135 GEN
Solar/Wind Harmer
0.148
228351V2-046C
Solar/Wind Harmer
2.951
219287REEVESEAST C
Solar/Wind Harmer
1.918
213589EDDYSTN4
Adder
113.261
213535CROYDN11
Adder
14.326
214067T20SOLAR
Solar/Wind Harmer
0.351
20636128O CRK C2
Adder
8.921
207459AE1-142 C O1
Solar/Wind Harmer
1.453
20628028LAKEHURS
Adder
1.309
217197RE CRAN C
Solar/Wind Harmer
0.724
924131AB2-057 GEN
Solar/Wind Harmer
1.381
20635128RRCT3&4
Adder
15.022
20635128RRCT3&4
Adder
13.104
218419LINDEN_G6
Adder
22.854
219035LINDEN_G8
Adder
21.863
20675428EAM_W2-061
Solar/Wind Harmer
0.25
972237AH1-703 GEN
Adder
13.331
20465127PORT CT
Adder
5.043
20465527S.RDG CT
Adder
2.58
223401AF1-299 GEN
Solar/Wind Helper
0.532
316450AC1-158 RIC
Solar/Wind Helper
0.459
966001AG1-469 GEN
Solar/Wind Helper
0.321
316487AF1-042 GEN
Solar/Wind Helper
0.301
316033AB2-134 GEN
Solar/Wind Helper
1.012
3145506HICKORY
Solar/Wind Helper
1.157
3145506HICKORY
Solar/Wind Helper
0.694
3145506HICKORY
Solar/Wind Helper
0.173
316339AD2-160 GEN
Solar/Wind Helper
1.103
316388AE2-253 GEN
Solar/Wind Helper
1.103
3137176SLIGO L2192
Solar/Wind Helper
1.149
3130086AYDLETT
Solar/Wind Helper
1.154
238148AE2-230_GEN2
Solar/Wind Helper
0.497
3146626S HERTFORD
Solar/Wind Helper
0.286
3146626S HERTFORD
Solar/Wind Helper
0.286
313506AB2-031 GEN
Solar/Wind Helper
1.269
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.167
3145593CAROLNA
Solar/Wind Helper
0.278
3145593CAROLNA
Solar/Wind Helper
0.278
3132123MT JACKSON
Solar/Wind Helper
0.866
3145933PARMELE
Solar/Wind Helper
0.55
3145933PARMELE
Solar/Wind Helper
0.275
316049AB1-081 GEN
Solar/Wind Helper
1.654
235062AE1-101 C1
Solar/Wind Helper
1.421
237006AB1-125 GEN
Solar/Wind Helper
0.107
238117U2-030
Solar/Wind Helper
0.261
G-007ALTFEXP_G-007A->PJM
CMTX
68.737
CBM NorthLTFEXP_CBM-N->PJM
CBM
95.237
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.231
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.299
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.524
VTFLTFEXP_VFT->PJM
CMTX
178.849
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.833
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
24.665

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.49 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5266.8
MW Contribution:
12.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232904IR4
Adder
132.596
232432Z2-076 GEN
Solar/Wind Harmer
0.216
233968AD2-076_GEN
Solar/Wind Harmer
10.698
231919CHRIST1
Adder
6.863
231920CHRIST2
Adder
6.711
230422AE1-104_GEN1
Solar/Wind Harmer
46.549
230425AE1-104_GEN2
Solar/Wind Harmer
46.549
230430AE1-229_GEN
Solar/Wind Harmer
39.5
230407AD2-065 C
Solar/Wind Harmer
0.18
20720728JCB_W1-129
Solar/Wind Harmer
0.388
207500AE2-000G1
Solar/Wind Harmer
40.932
970025AG2-016 GEN
Solar/Wind Harmer
3.673
20714428HOW_X1-037
Solar/Wind Harmer
1.576
218449LINSOLAR C
Solar/Wind Harmer
1.248
217147KRNY_1212
Adder
10.896
217147KRNY_1212
Adder
10.701
217146KRNY_1234
Adder
10.677
217146KRNY_1234
Adder
10.604
964851AG1-348 GEN
Solar/Wind Harmer
1.623
207408W3-077 C
Solar/Wind Harmer
0.599
20462827N BANGR8
Adder
0.843
209026WIENIPP4
Adder
5.855
209054AE2-059 GEN
Solar/Wind Harmer
1.708
20486527WR_V4-052
Adder
0.947
209067AE2-060 GEN
Solar/Wind Harmer
1.1
200917MEHOOPANY_G
Solar/Wind Harmer
3.476
315651AD1-115 GEN
Solar/Wind Helper
0.951
3141783LANCAST
Solar/Wind Helper
0.164
3141783LANCAST
Solar/Wind Helper
0.11
316059AD1-063 C
Solar/Wind Helper
0.276
313526AB2-022
Solar/Wind Helper
0.405
238169AE2-226 GEN1
Solar/Wind Helper
0.638
238170AE2-226 GEN2
Solar/Wind Helper
0.638
3146206CASHIE
Solar/Wind Helper
0.259
961941AG1-037 GEN
Solar/Wind Helper
0.087
3146043SEABORD
Solar/Wind Helper
0.257
3145683EARLEYS
Solar/Wind Helper
0.514
3145683EARLEYS
Solar/Wind Helper
0.257
3145683EARLEYS
Solar/Wind Helper
0.257
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316486AD2-202 GEN
Solar/Wind Helper
0.366
316274AC1-208 GEN
Solar/Wind Helper
1.545
3147173SINAI
Solar/Wind Helper
0.246
3147243WELCO
Solar/Wind Helper
0.154
3148463FAIRFLD
Solar/Wind Helper
0.242
270455AD2-022 GEN
Solar/Wind Helper
1.365
270197AD1-017 GEN1
Solar/Wind Helper
1.22
200200DELTA2 CT1
50/50
5.349
200193DELTA CT2
50/50
2.989
200203Y1-065-STG
50/50
10.579
200055ROCKSP 4
50/50
3.821
233939AC1-091 C
Solar/Wind Harmer
4.406
232914OH NUG3
Adder
14.478
232916OH NUG5
Adder
14.478
233933AB2-153 GEN
Solar/Wind Harmer
1.805
219623KINSLEYBEA C
Solar/Wind Harmer
0.575
213958STHWK5-6
Adder
3.596
20716428NHV_W2-082
Solar/Wind Harmer
2.313
963391AG1-188 GEN
Solar/Wind Harmer
4.858
219612MATRIX C
Solar/Wind Harmer
0.232
20716928W4-060COL
Solar/Wind Harmer
0.899
217213AMBOY SO C
Solar/Wind Harmer
0.158
20673728F2S_V4-070
Solar/Wind Harmer
0.222
207510AF2-138 C
Solar/Wind Harmer
2.14
207437AD2-070 GEN
Solar/Wind Harmer
0.355
20671928W4-073
Solar/Wind Harmer
0.509
20633028GILCT9
Adder
33.129
20465427SHAW CT
Adder
4.539
209116AE2-175 GEN
Solar/Wind Harmer
4.765
970095AG2-074 GEN
Solar/Wind Harmer
6.853
961421AF2-433 GEN
Solar/Wind Harmer
1.036
209093AE2-110 GEN
Solar/Wind Harmer
2.589
209120AE2-241 GEN
Solar/Wind Harmer
3.426
946691AF1-333 GEN
Solar/Wind Harmer
1
946741AF1-338 GEN
Solar/Wind Harmer
1
972221AH1-695 GEN
Adder
89.251
226910AB2-157 C
Solar/Wind Helper
0.024
3141196NOKESVL
Solar/Wind Helper
1.155
316077AC2-138 C
Solar/Wind Helper
0.261
316484AD2-074 GEN
Solar/Wind Helper
0.531
316075AC2-137 C
Solar/Wind Helper
0.417
966621AG1-532 GEN
Solar/Wind Helper
0.234
942461AE2-259 GEN
Solar/Wind Helper
1.724
316317KELFORD C
Solar/Wind Helper
0.23
3145823KELFORD
Solar/Wind Helper
0.256
3145796HORNRTN
Solar/Wind Helper
1.019
3145796HORNRTN
Solar/Wind Helper
0.255
315821AE2-092 GEN
Solar/Wind Helper
2.356
316212AC1-099_GEN
Solar/Wind Helper
1.138
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
316123AC1-075 GEN
Solar/Wind Helper
1.454
23583801GRNGAP
Solar/Wind Helper
4.045
3147312GRETNA
Solar/Wind Helper
0.045
232434Z2-077 GEN
Solar/Wind Harmer
0.41
232406W1-004 FULL
Solar/Wind Harmer
1.639
233964AF2-378 GEN
Solar/Wind Harmer
0.209
232422X3-066 FULL
Solar/Wind Harmer
0.403
230415AB2-049 C
Solar/Wind Harmer
0.261
219291REEVESSOUT C
Solar/Wind Harmer
0.081
219236SOUTHERNHQ C
Solar/Wind Harmer
0.09
213815MOSER1-3
Adder
4.644
20714928UPF_X1-085
Solar/Wind Harmer
0.526
219114HARTZY_C
Solar/Wind Harmer
1.075
219918AC2-009 C
Solar/Wind Harmer
0.033
20674528F3S_W2-016
Solar/Wind Harmer
1.718
209025WIENIPP3
Adder
5.796
209142AF1-226 GEN
Solar/Wind Harmer
5.995
205941AD2-115 GEN
Solar/Wind Harmer
0.881
227287AC2-120 GEN
Solar/Wind Helper
0.568
966881AG1-559 GEN
Solar/Wind Helper
0.381
316473AC1-191 GEN
Solar/Wind Helper
1.682
3142946ENON
Solar/Wind Helper
0.091
3145336SMITFLD
Solar/Wind Helper
0.107
316017AA1-139 ULT1
Solar/Wind Helper
1.22
3146456SLIGO L269
Solar/Wind Helper
0.266
3145273HOLLAND
Solar/Wind Helper
0.198
3146376EDENTON
Solar/Wind Helper
0.262
3146206CASHIE
Solar/Wind Helper
0.259
3146173TUNIS
Solar/Wind Helper
0.258
316181AB2-040 GEN
Solar/Wind Helper
1.843
3147043LAWRENC
Solar/Wind Helper
0.153
3147133PAMPLIN
Solar/Wind Helper
0.8
316478AD1-087 GEN
Solar/Wind Helper
1.249
316420AA1-050 GEN
Solar/Wind Helper
1.439
3146073TAR RVR
Solar/Wind Helper
0.25
3146083TARBORO
Solar/Wind Helper
0.25
3138543CONSLDL
Solar/Wind Helper
0.165
316499AE2-029_GEN
Solar/Wind Helper
0.837
316003AC1-222 GEN
Solar/Wind Helper
1.064
316222AC1-221 GEN
Solar/Wind Helper
1.377
316283AC2-100 C
Solar/Wind Helper
1.283
316095T157 G97
Solar/Wind Helper
1.092
23777801MSM_W1-116
Solar/Wind Helper
0.1
238109AE1-109 GEN2
Solar/Wind Helper
0.084
232926CRISFLD1
Adder
3.217
231940T-011
Adder
1.222
234041AC1-190 GEN
Solar/Wind Harmer
14.642
228201CARL#2CT
Adder
9.519
228200CARL#1CT
Adder
9.054
219904AC1-010 C
Solar/Wind Harmer
0.506
219906AC1-017 C
Solar/Wind Harmer
0.294
213815MOSER1-3
Adder
4.644
213815MOSER1-3
Adder
4.644
20720828JCB_W4-025
Solar/Wind Harmer
0.589
20714828MDF_W3-079
Solar/Wind Harmer
0.393
219817TRENTONSOL C
Solar/Wind Harmer
1.407
20641628MLH_W1-032
Solar/Wind Harmer
0.374
20742028HF_AC1-207
Solar/Wind Harmer
0.997
218438BLK ROCK C
Solar/Wind Harmer
0.172
972260AH1-715 GEN1
Adder
17.133
972261AH1-715 GEN2
Adder
19.871
217202FBANKSOLAR C
Solar/Wind Harmer
0.091
217201HACKENSOLA C
Solar/Wind Harmer
0.09
217206BARNGR HS C
Solar/Wind Harmer
0.038
217204WCALDSOLAR C
Solar/Wind Harmer
0.09
20674828DL_W4-046
Solar/Wind Harmer
0.769
20634528N27_Y2-018
Solar/Wind Harmer
0.319
315976AC1-164 GENA
Solar/Wind Helper
3.518
316169AC1-164_GENC
Solar/Wind Helper
3.039
3142946ENON
Solar/Wind Helper
0.027
316294AC1-161 GEN
Solar/Wind Helper
4.906
316349AD2-085 GEN
Solar/Wind Helper
1.22
3146386ELIZ CT
Solar/Wind Helper
0.265
316431W1029_GEN1
Solar/Wind Helper
1.07
316433W1029_GEN2
Solar/Wind Helper
1.07
316365GEN2_N
Solar/Wind Helper
0.987
3146173TUNIS
Solar/Wind Helper
0.258
3146173TUNIS
Solar/Wind Helper
0.258
238147AE2-230_GEN1
Solar/Wind Helper
0.443
3147133PAMPLIN
Solar/Wind Helper
0.255
3147133PAMPLIN
Solar/Wind Helper
0.204
3146843MT LREL
Solar/Wind Helper
0.249
3146843MT LREL
Solar/Wind Helper
0.249
316097T157 G90
Solar/Wind Helper
1.092
237080AD1-060 GEN
Solar/Wind Helper
0.28
233973AC2-185 C
Solar/Wind Harmer
8.9
970695AG2-447 GEN
Solar/Wind Harmer
5.888
233987AB2-037 GEN
Solar/Wind Harmer
18.643
233923SMA
Solar/Wind Harmer
5.989
233997TMININ_4.2
Solar/Wind Harmer
1.633
232907VN8
Adder
49.197
232417X3-008 C
Solar/Wind Harmer
1.839
233935AB2-179 C
Solar/Wind Harmer
3.909
219221BRL12CT1
Adder
11.748
219223BRL12CT3
Adder
11.748
959561AF2-247 GEN
Solar/Wind Harmer
0.631
20715728PEM_W1-119
Solar/Wind Harmer
0.694
20636028O CRK C1
Adder
9.184
971667AH1-334 GEN
Solar/Wind Harmer
3.551
219727YARDVSOLFA C
Solar/Wind Harmer
1.17
20635828PARLN1&2
Adder
4.221
219249CENTRALDIV C
Solar/Wind Harmer
0.05
207442AE1-156 GEN
Solar/Wind Harmer
0.92
217211CAMDEN ST C
Solar/Wind Harmer
0.03
217194REDH C
Solar/Wind Harmer
0.606
207511W3-106 GEN
Solar/Wind Harmer
0.397
971007AG2-625 GEN
Solar/Wind Harmer
3.05
20466127PORT 5CT
Adder
31.299
20674128FR_U2-059
Solar/Wind Harmer
0.217
211065PSPA IPP
Solar/Wind Harmer
0.518
957921AF2-086 GEN
Solar/Wind Harmer
1.007
316223AC1-118
Solar/Wind Helper
0.428
3132273ORANGE
Solar/Wind Helper
0.055
3144536CHRHLND
Solar/Wind Helper
0.04
3142956BIRDNECK
Solar/Wind Helper
0.18
316305AF2-043 C
Solar/Wind Helper
0.359
316320Y1-086
Solar/Wind Helper
0.119
3146516WINFALL
Solar/Wind Helper
0.264
315735AD1-075 GEN1
Solar/Wind Helper
1.485
3145893MURPHYS
Solar/Wind Helper
0.093
3145893MURPHYS
Solar/Wind Helper
0.258
3146776BUCKING
Solar/Wind Helper
0.093
23546401DTGZ2-030
Solar/Wind Helper
0.081
3146263WOODLND
Solar/Wind Helper
0.257
3145963POPLR C
Solar/Wind Helper
0.256
316011AB1-132 GEN
Solar/Wind Helper
2.758
3145543BTLEBRO
Solar/Wind Helper
0.249
3145543BTLEBRO
Solar/Wind Helper
0.249
270494AE1-108_GEN
Solar/Wind Helper
3.328
270173AC1-122 GEN
Solar/Wind Helper
1.527
200195DELTA ST
50/50
4.618
232920IR10
Adder
5.182
233901CHERRYDALE C
Solar/Wind Harmer
1.843
232913OH NUG2
Adder
14.285
231906DC3 NUG
Adder
22.579
231907DC10
Adder
5.637
970597AG2-380 GEN
Solar/Wind Harmer
6.718
972141AH1-641 GEN
Solar/Wind Harmer
3.971
20715028HAN_X4-015
Solar/Wind Harmer
0.388
213611FALLS1-3
Adder
4.604
213611FALLS1-3
Adder
4.604
207507AE2-000G3
Solar/Wind Harmer
40.932
207445AB1-138_GEN
Solar/Wind Harmer
0.748
20720628TIN_W1-124
Solar/Wind Harmer
1.268
971521AH1-258 GEN
Solar/Wind Harmer
3.437
20675528CPH_W2-050
Solar/Wind Harmer
0.715
20676428JCR_X2-075
Solar/Wind Harmer
0.423
217086KRNY_131
Adder
11.358
20675128HRM_W1-127
Solar/Wind Harmer
0.2
209029WAYMART-WD
Solar/Wind Harmer
2.811
959421AF2-233 GEN
Solar/Wind Harmer
0.998
203926AA2-133 GEN
Adder
2.109
226929AD2-058 GEN
Solar/Wind Helper
0.158
3138216PACIFIC
Solar/Wind Helper
0.049
316164AC1-076 GEN
Solar/Wind Helper
1.35
3141813NORNECK
Solar/Wind Helper
0.277
957601AF2-054 GEN
Solar/Wind Helper
0.366
316233AE1-074 FULL
Solar/Wind Helper
0.415
316018AA1-139 ULT2
Solar/Wind Helper
1.148
315800Z1-036_GEN1
Solar/Wind Helper
1.446
315732AD1-074 GEN1
Solar/Wind Helper
2.969
3145893MURPHYS
Solar/Wind Helper
0.698
3145893MURPHYS
Solar/Wind Helper
0.258
316463AE2-346 GEN
Solar/Wind Helper
0.236
3145513AHOSKIE
Solar/Wind Helper
0.115
3145513AHOSKIE
Solar/Wind Helper
0.257
3137643SOCKMAN
Solar/Wind Helper
1.023
316426AA2-053 GEN
Solar/Wind Helper
1.463
316174AB2-169 GEN
Solar/Wind Helper
0.654
3144303KENBRDG
Solar/Wind Helper
0.203
316327AA2-057 GEN
Solar/Wind Helper
1.436
23779801AA1-109
Solar/Wind Helper
0.172
270457AD2-023 GEN
Solar/Wind Helper
0.899
200035PCHBTM 3
50/50
30.692
233971AC1-093 C
Solar/Wind Harmer
4.183
232918OH NUG7
Adder
14.381
232905CHERITON_25
Adder
4.022
233994AC2-023 GEN
Solar/Wind Harmer
4.397
234036AF2-325 C
Solar/Wind Harmer
1.499
232910NRG_G1
Adder
14.048
234014AF1-036_GEN
Solar/Wind Harmer
4.367
232436AB1-176 C
Solar/Wind Harmer
0.369
972233AH1-701 GEN
Adder
5.723
219912AD2-042 GEN
Solar/Wind Harmer
1.062
219607WPEMNERT C
Solar/Wind Harmer
0.551
219304NAMERICA C
Solar/Wind Harmer
0.408
20635028RRCT1&2
Adder
14.578
218418LINDEN_G5
Adder
21.396
219036LINDEN_G7
Adder
20.759
217086KRNY_131
Adder
11.48
20674328GAR_V4-001
Solar/Wind Harmer
0.132
946751AF1-339 GEN
Solar/Wind Harmer
1
316006AB2-029 C
Solar/Wind Helper
0.136
316045AC1-158 PL2
Solar/Wind Helper
5.056
966871AG1-558 GEN
Solar/Wind Helper
0.371
316156AD2-030 GEN
Solar/Wind Helper
0.413
315666AE1-190 GEN
Solar/Wind Helper
0.368
316240AF1-291 C
Solar/Wind Helper
0.364
316313AB2-026
Solar/Wind Helper
0.406
316435W1029_GEN3
Solar/Wind Helper
1.07
3146516WINFALL
Solar/Wind Helper
0.264
3146516WINFALL
Solar/Wind Helper
0.264
3146516WINFALL
Solar/Wind Helper
0.264
315614AA2-178 GEN
Solar/Wind Helper
1.593
3145893MURPHYS
Solar/Wind Helper
0.371
3145893MURPHYS
Solar/Wind Helper
0.465
316140AB2-099
Solar/Wind Helper
0.098
3146776BUCKING
Solar/Wind Helper
1.029
3146776BUCKING
Solar/Wind Helper
0.083
238149AF1-291A_GEN
Solar/Wind Helper
0.127
316005AA1-067
Solar/Wind Helper
0.288
316118AC1-105 GEN
Solar/Wind Helper
0.964
200204Y1-065-CTG1
50/50
6.109
233918AB1-142 GEN
Solar/Wind Harmer
1.588
228206SHRMN CT
Adder
23.049
228260V4-054C
Solar/Wind Harmer
1.421
228729W2-030 C
Solar/Wind Harmer
0.793
219686LUMSOLAR_N C
Solar/Wind Harmer
0.271
219348LDSOLAR C
Solar/Wind Harmer
0.787
213611FALLS1-3
Adder
4.604
214194N WALES4
Adder
1.103
20720428HOL_W1-112
Solar/Wind Harmer
0.439
20635828PARLN1&2
Adder
9.318
20635028RRCT1&2
Adder
14.806
218524CNTRALGAS1 C
Solar/Wind Harmer
0.462
217209CENTRL HS C
Solar/Wind Harmer
0.055
20671828STAW2-080
Solar/Wind Harmer
0.129
207439AE1-081 C O1
Solar/Wind Harmer
0.072
207530AG1-191 GEN
Solar/Wind Harmer
1.651
211065PSPA IPP
Solar/Wind Harmer
0.518
961301AF2-421 GEN
Solar/Wind Harmer
1.099
963151AG1-164 GEN
Solar/Wind Harmer
1.099
961341AF2-425 GEN
Solar/Wind Harmer
1.038
212507AE2-042_GEN
Solar/Wind Harmer
3.028
316337AD2-073 GEN
Solar/Wind Helper
0.423
3141726DUNNSVL
Solar/Wind Helper
1.105
316132AB2-190 GEN1
Solar/Wind Helper
1.545
315773AC2-141 GEN
Solar/Wind Helper
5.773
316036AC1-147 C
Solar/Wind Helper
0.408
3146516WINFALL
Solar/Wind Helper
0.856
3146516WINFALL
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
1.034
3146776BUCKING
Solar/Wind Helper
0.103
315607AA1-063A GEN
Solar/Wind Helper
1.47
3146263WOODLND
Solar/Wind Helper
0.257
3145963POPLR C
Solar/Wind Helper
0.256
316494AC1-189 GEN
Solar/Wind Helper
1.532
961671AG1-007 GEN
Solar/Wind Helper
0.179
3145543BTLEBRO
Solar/Wind Helper
0.249
3145543BTLEBRO
Solar/Wind Helper
0.199
232901NORTHST
Adder
13.679
234033AF1-007_GEN
Solar/Wind Harmer
60.997
233996TM1833_GEN
Solar/Wind Harmer
1.633
232426Y1-080 FULL
Solar/Wind Harmer
0.313
232902EASTMUNI
Adder
21.221
234012AE2-112_GEN
Solar/Wind Harmer
3.712
972251AH1-710 GEN
Adder
72.075
231918WEST 1
Adder
5.218
228732V1-021 C
Adder
0.263
228400MICK 1CT
Adder
16.092
219766PARADISE C
Solar/Wind Harmer
0.421
20714528FRN_Y2-051
Solar/Wind Harmer
0.379
219680HOPEWELLV C1
Solar/Wind Harmer
0.097
218440SUMMTASSOC C
Solar/Wind Harmer
0.16
217208PARK ELE C
Solar/Wind Harmer
0.031
966261AG1-495 GEN
Solar/Wind Harmer
4.238
20674628WNG_W3-110
Solar/Wind Harmer
0.485
209023WIENIPP1
Adder
11.85
209025WIENIPP3
Adder
5.915
963071AG1-156 GEN
Solar/Wind Harmer
10.821
316447AC1-158 HLD
Solar/Wind Helper
3.477
316192AB2-158 GEN
Solar/Wind Helper
1.869
3142416OLDCHRC
Solar/Wind Helper
0.711
3142416OLDCHRC
Solar/Wind Helper
0.273
3141766HARMONY
Solar/Wind Helper
0.055
3142433PROV 92
Solar/Wind Helper
1.09
315975AC1-164 GENB
Solar/Wind Helper
0.104
3145336SMITFLD
Solar/Wind Helper
1.072
316375AC2-012 GEN
Solar/Wind Helper
0.703
3146456SLIGO L269
Solar/Wind Helper
0.266
3145663CRESWEL
Solar/Wind Helper
0.73
3146206CASHIE
Solar/Wind Helper
0.259
316023GEN1_S
Solar/Wind Helper
0.987
3146173TUNIS
Solar/Wind Helper
0.258
3156021HOLLOMANSOL
Solar/Wind Helper
1.965
3145683EARLEYS
Solar/Wind Helper
0.257
316131AB2-060 GEN
Solar/Wind Helper
1.543
3146083TARBORO
Solar/Wind Helper
0.25
316359AB2-059 GEN
Solar/Wind Helper
1.9
3147123OTTER R
Solar/Wind Helper
0.137
238110AE1-109 GEN3
Solar/Wind Helper
0.084
238108AE1-109 GEN1
Solar/Wind Helper
0.084
200202DELTA2 ST
50/50
9.059
200052ROCKSP 1
50/50
3.843
200053ROCKSP 2
50/50
3.768
233940AF2-379 C
Solar/Wind Harmer
0.305
230434AG1-499 GEN
Solar/Wind Harmer
0.794
219258KINSLEYDEP C
Solar/Wind Harmer
0.435
213942SCHUYLKILL
Adder
4.704
213942SCHUYLKILL
Adder
3.597
213957STHWK3-4
Adder
3.596
213957STHWK3-4
Adder
3.596
213561DLWR9-10
Adder
4.682
213561DLWR9-10
Adder
3.58
219610FLORENCE C
Solar/Wind Harmer
1.822
963401AG1-189 GEN
Solar/Wind Harmer
2.95
971189AH1-054 GEN
Solar/Wind Harmer
1.528
20716228APLW2-078
Solar/Wind Harmer
1.125
20673828FLE_V3-070
Solar/Wind Harmer
0.579
20676128MHD_W3-029
Solar/Wind Harmer
0.591
209027LOR2_Q27
Solar/Wind Harmer
4.798
964051AG1-259 GEN
Solar/Wind Harmer
1.338
964061AG1-260 GEN
Solar/Wind Harmer
1.338
208862AG1-362 C
Solar/Wind Harmer
0.63
20390726Y2-042
Adder
2.722
3141426STAFORD
Solar/Wind Helper
0.066
316468AD1-105 GEN
Solar/Wind Helper
1.346
3141913WHIT STONE
Solar/Wind Helper
0.274
957831AF2-077 GEN
Solar/Wind Helper
0.366
315697AD1-025 GEN
Solar/Wind Helper
3.084
315839AE2-212 C
Solar/Wind Helper
0.363
316316AC1-027 C
Solar/Wind Helper
0.422
316258AE1-075 C
Solar/Wind Helper
0.366
316322AB2-045
Solar/Wind Helper
0.288
3145796HORNRTN
Solar/Wind Helper
0.815
3145796HORNRTN
Solar/Wind Helper
0.102
316210AC1-098 GEN
Solar/Wind Helper
2.049
316238AB2-078_GEN
Solar/Wind Helper
0.34
316239AB2-077_GEN
Solar/Wind Helper
0.34
3145746EVERETS
Solar/Wind Helper
1.002
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
3145573BETHELC
Solar/Wind Helper
0.25
3145573BETHELC
Solar/Wind Helper
0.25
3148133STUARTS
Solar/Wind Helper
0.149
200201DELTA2 CT2
50/50
5.349
232899W1-062
Adder
15.774
232410W1-006 C
Solar/Wind Harmer
1.639
233946AB2-136 GEN
Solar/Wind Harmer
6.523
233952AC2-187 GEN
Solar/Wind Harmer
1.839
233954AC2-188 GEN
Solar/Wind Harmer
1.839
233984AB2-036 GEN
Solar/Wind Harmer
20.187
233930AB2-032 GEN
Solar/Wind Harmer
1.337
233982AB2-133 GEN
Solar/Wind Harmer
7.809
230511AF1-262
Solar/Wind Harmer
0.252
228754AB1-001 C
Solar/Wind Harmer
0.191
228307PCLP GT
Adder
16.578
219272CLEANLIGHT C
Solar/Wind Harmer
0.245
213587EDDYSTN3
Adder
106.232
217081WEATEXAS C
Solar/Wind Harmer
0.106
217083KRNY_132
Adder
11.382
207471AF2-354 C
Solar/Wind Harmer
0.609
20675928HOL_W4-097
Solar/Wind Harmer
0.154
209010PEIP 1
Adder
3.849
209010PEIP 1
Adder
0.564
961541AF2-445A GEN
Solar/Wind Harmer
3.447
961431AF2-434 GEN
Solar/Wind Harmer
1.036
209130AF1-271A GEN
Solar/Wind Harmer
2.805
223402AF1-300 C
Solar/Wind Helper
0.612
316411AF1-147_GEN1
Solar/Wind Helper
0.979
316312AB1-027
Solar/Wind Helper
0.523
3143526WINTERP
Solar/Wind Helper
1.413
316185AD1-033 GEN
Solar/Wind Helper
1.258
3144356SAPONY
Solar/Wind Helper
0.473
316315AB2-025 C
Solar/Wind Helper
0.403
237061AD1-155 GEN
Solar/Wind Helper
1.604
3145796HORNRTN
Solar/Wind Helper
0.764
316237AB2-079_GEN
Solar/Wind Helper
0.34
315687AD1-152 GEN
Solar/Wind Helper
1.354
316248AF1-058 C
Solar/Wind Helper
0.332
235020AA1-095 C
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.231
270013AE1-250 PV
Solar/Wind Helper
0.844
200194DELTA CT3
50/50
2.989
233970AC1-092 C
Solar/Wind Harmer
4.406
232900DEMECSMY
Adder
15.13
232404W1-003 C
Solar/Wind Harmer
1.639
233998TM1NIN_3.36
Solar/Wind Harmer
1.633
232919VN10
Adder
4.595
231917EM10
Adder
3.635
970997AG2-616 GEN
Solar/Wind Harmer
13.238
213497CHSTR7-9
Adder
3.642
213497CHSTR7-9
Adder
3.642
213560DLW11-12
Adder
3.58
219222BRL12CT2
Adder
11.748
20717128DIX_Z2-102
Solar/Wind Harmer
1.717
20715828PEM_W1-120
Solar/Wind Harmer
0.694
963711AG1-223 GEN
Solar/Wind Harmer
1.9
219276PARKLANDSO C
Solar/Wind Harmer
0.59
20715228NPK_W1-113
Solar/Wind Harmer
0.547
20720528MAN_W1-024
Solar/Wind Harmer
0.323
219919AE1-041 FULL
Solar/Wind Harmer
0.05
217121ECCF
Adder
0.535
20676728BRNX1-095
Solar/Wind Harmer
0.215
20676328BVR_Y1-020
Solar/Wind Harmer
0.398
20674928WA_W3-044
Solar/Wind Harmer
0.573
971519AH1-257 GEN
Solar/Wind Harmer
2.99
207518AF1-320_GEN
Solar/Wind Harmer
4.321
20465127PORT CT
Adder
3.543
209018SUNBIPCT
Adder
7.431
20465527S.RDG CT
Adder
2.415
209137AF2-361 C
Solar/Wind Harmer
2.125
316044AC1-158 PL1
Solar/Wind Helper
1.58
3147666LOUISA
Solar/Wind Helper
1.111
316404AE1-155 C
Solar/Wind Helper
2.359
3138133OCRAN
Solar/Wind Helper
0.164
315662AE1-191 GEN
Solar/Wind Helper
1.472
316280AD1-041 GEN
Solar/Wind Helper
0.92
3142543TWELFTH
Solar/Wind Helper
0.026
3143226MDLTHAN
Solar/Wind Helper
0.271
316369SG1_INVT
Solar/Wind Helper
1.3
316381AD1-082 GEN
Solar/Wind Helper
1.388
319010AE1-072 C
Solar/Wind Helper
3.046
315611Z1-036_GEN2
Solar/Wind Helper
1.446
3130156CHOWAN
Solar/Wind Helper
0.262
315816AE2-034 GEN
Solar/Wind Helper
1.195
315737AD1-076 GEN
Solar/Wind Helper
2.539
3146926FARMVIL
Solar/Wind Helper
0.154
316087AB2-174 GEN
Solar/Wind Helper
1.799
238152AF2-075_GEN
Solar/Wind Helper
0.633
315785AD2-033 C
Solar/Wind Helper
2.96
3146233WITAKRS
Solar/Wind Helper
0.994
23777901MDS_W4-102
Solar/Wind Helper
0.154
270018AE2-047 C O1
Solar/Wind Helper
0.792
200192DELTA CT1
50/50
2.989
200054ROCKSP 3
50/50
3.888
972177AH1-672 GEN
Solar/Wind Harmer
22.025
232408W1-005 C
Solar/Wind Harmer
1.639
232917OH NUG6
Adder
14.413
232915OH NUG4
Adder
14.381
233944AB2-135 GEN
Solar/Wind Harmer
8.417
219907AC1-030 C
Solar/Wind Harmer
0.184
213958STHWK5-6
Adder
3.596
20716028EGP_W2-019
Solar/Wind Harmer
0.604
207522AF2-254 C
Solar/Wind Harmer
1.867
218428ETC SOLAR C
Solar/Wind Harmer
0.045
233972AC1-094 C
Solar/Wind Harmer
3.538
232921TASLEY2G
Adder
8.461
233950AC2-186 GEN
Solar/Wind Harmer
0.92
228711V2-041C
Solar/Wind Harmer
0.835
219921AF1-264
Solar/Wind Harmer
0.194
218660EHAMPSOLAR C
Solar/Wind Harmer
0.234
219688LUMSOLAR_S C
Solar/Wind Harmer
0.271
213497CHSTR7-9
Adder
3.642
219914AD2-027 C
Solar/Wind Harmer
0.801
213560DLW11-12
Adder
3.58
207454AA2-184 E
Solar/Wind Harmer
1.272
219908AB1-139 C
Solar/Wind Harmer
0.475
972275AH1-722 GEN
Adder
39.333
20673628F1S_V4-069
Solar/Wind Harmer
0.222
207528AF2-192 GEN
Solar/Wind Harmer
1.574
217186ESSEX_G9
Adder
4.865
217083KRNY_132
Adder
11.455
20676228FRD_X1-012
Solar/Wind Harmer
0.711
20675828AU_W4-064
Solar/Wind Harmer
0.208
20675728RH_W2-091
Solar/Wind Harmer
0.713
207484AF2-139 C O1
Solar/Wind Harmer
0.596
208909MACR G3
Adder
186.471
209010PEIP 1
Adder
0.7
946731AF1-337 GEN
Solar/Wind Harmer
1
209008PAXT IPP
Adder
1.337
316415AF1-147_GEN2
Solar/Wind Helper
0.979
964211AG1-282 GEN
Solar/Wind Helper
0.372
3143526WINTERP
Solar/Wind Helper
1.413
315671AE2-027_GEN
Solar/Wind Helper
2.18
316072AD1-144
Solar/Wind Helper
0.306
238175AF1-290_GEN
Solar/Wind Helper
0.141
3145823KELFORD
Solar/Wind Helper
0.256
3145783HORNRTN
Solar/Wind Helper
0.255
3145796HORNRTN
Solar/Wind Helper
0.841
3145796HORNRTN
Solar/Wind Helper
0.255
316034AC1-036 C
Solar/Wind Helper
0.266
316129AC1-054 GEN
Solar/Wind Helper
1.256
3145746EVERETS
Solar/Wind Helper
0.252
3145746EVERETS
Solar/Wind Helper
0.252
3147983MERCK5
Solar/Wind Helper
0.099
270016AE1-250 BESS
Solar/Wind Helper
0.844
3147312GRETNA
Solar/Wind Helper
0.182
3146802CHATHAM
Solar/Wind Helper
0.171
20635928PARLN3&4
Adder
4.221
217169METRODIV C
Solar/Wind Harmer
0.049
963161AG1-165 GEN
Solar/Wind Harmer
1.099
208972BECR K09
Solar/Wind Harmer
1.145
961331AF2-424 GEN
Solar/Wind Harmer
1.038
209071AE2-133 GEN
Solar/Wind Harmer
1.688
3141906WESTMOR
Solar/Wind Helper
0.112
3147666LOUISA
Solar/Wind Helper
0.639
316458AB2-190 GEN2
Solar/Wind Helper
1.545
3144873MCLAUGH
Solar/Wind Helper
0.007
316246AF1-032 C
Solar/Wind Helper
0.305
316321Z2-027
Solar/Wind Helper
0.405
232912OH NUG1
Adder
14.478
971195AH1-057 GEN
Solar/Wind Harmer
1.597
233955AB2-172 GEN
Solar/Wind Harmer
8.171
232813VAUGHN
Adder
0.96
231902DC CT7
Adder
18.051
233915AB1-141 GEN
Solar/Wind Harmer
1.588
970453AG2-297 GEN
Solar/Wind Harmer
3.848
964001AG1-254 GEN
Solar/Wind Harmer
10.045
228728W1-130C
Solar/Wind Harmer
0.913
227927V4-067C
Solar/Wind Harmer
0.272
219137THOSOLAR C
Solar/Wind Harmer
1.632
219615MILLCREEK C
Solar/Wind Harmer
0.315
219224BRL12CT4
Adder
11.748
207487AE2-000G4
Solar/Wind Harmer
40.932
207497AE2-000G2
Solar/Wind Harmer
40.932
219620RIDERU C
Solar/Wind Harmer
0.071
20635928PARLN3&4
Adder
9.318
218526CNTRALGAS2 C
Solar/Wind Harmer
0.464
217167KRNY_14
Adder
11.455
971009AG2-626 GEN
Solar/Wind Harmer
1.946
961261AF2-417 GEN
Solar/Wind Harmer
1.117
212266LOR1
Solar/Wind Harmer
1.272
959431AF2-234 GEN
Solar/Wind Harmer
1.995
20334726NME_Y1-047
Adder
2.337
3138133OCRAN
Solar/Wind Helper
0.082
3141873WAN 176
Solar/Wind Helper
0.055
3143873LANEXA
Solar/Wind Helper
0.164
316382AG1-145 C
Solar/Wind Helper
0.365
316159AE1-175 C
Solar/Wind Helper
0.411
316236AE1-162_GEN
Solar/Wind Helper
0.361
3143316POE
Solar/Wind Helper
1.06
316405AF2-144 C
Solar/Wind Helper
0.305
3146486SUNBURY
Solar/Wind Helper
0.265
3146486SUNBURY
Solar/Wind Helper
0.265
3145176PASQUOTANK
Solar/Wind Helper
0.164
3130156CHOWAN
Solar/Wind Helper
0.262
3130156CHOWAN
Solar/Wind Helper
0.262
3130546PLYMOUTH
Solar/Wind Helper
0.26
315733AD1-074 GEN2
Solar/Wind Helper
2.969
946281AF1-292 GEN
Solar/Wind Helper
0.258
3146033SCOT NK
Solar/Wind Helper
1.018
3148013FISHERV
Solar/Wind Helper
0.143
315616AA1-038_C
Solar/Wind Helper
1.098
200034PCHBTM 2
50/50
31.177
200205Y1-065-CTG2
50/50
6.109
234015AF2-250 C
Solar/Wind Harmer
0.197
232428Y3-058 C
Solar/Wind Harmer
1.365
232424Y1-079 C
Solar/Wind Harmer
0.911
228251CARLLS#4
Adder
0.873
230433AD2-135 GEN
Solar/Wind Harmer
0.139
228351V2-046C
Solar/Wind Harmer
2.776
219287REEVESEAST C
Solar/Wind Harmer
1.802
213589EDDYSTN4
Adder
106.245
213535CROYDN11
Adder
13.448
214067T20SOLAR
Solar/Wind Harmer
0.329
20636128O CRK C2
Adder
8.374
207459AE1-142 C O1
Solar/Wind Harmer
1.363
20628028LAKEHURS
Adder
1.228
217197RE CRAN C
Solar/Wind Harmer
0.679
924131AB2-057 GEN
Solar/Wind Harmer
1.293
20635128RRCT3&4
Adder
14.072
20635128RRCT3&4
Adder
12.275
218419LINDEN_G6
Adder
21.396
219035LINDEN_G8
Adder
20.463
20675428EAM_W2-061
Solar/Wind Harmer
0.234
972237AH1-703 GEN
Adder
12.471
20465127PORT CT
Adder
4.701
20465527S.RDG CT
Adder
2.337
223401AF1-299 GEN
Solar/Wind Helper
0.612
316450AC1-158 RIC
Solar/Wind Helper
0.421
316487AF1-042 GEN
Solar/Wind Helper
0.278
966001AG1-469 GEN
Solar/Wind Helper
0.294
316033AB2-134 GEN
Solar/Wind Helper
0.933
3145506HICKORY
Solar/Wind Helper
1.066
3145506HICKORY
Solar/Wind Helper
0.64
3145506HICKORY
Solar/Wind Helper
0.16
316339AD2-160 GEN
Solar/Wind Helper
1.017
316388AE2-253 GEN
Solar/Wind Helper
1.017
3137176SLIGO L2192
Solar/Wind Helper
1.059
3130086AYDLETT
Solar/Wind Helper
1.064
3146626S HERTFORD
Solar/Wind Helper
0.264
3146626S HERTFORD
Solar/Wind Helper
0.264
313506AB2-031 GEN
Solar/Wind Helper
1.167
238148AE2-230_GEN2
Solar/Wind Helper
0.443
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.256
3142666NORTHAMPTON
Solar/Wind Helper
0.154
3145593CAROLNA
Solar/Wind Helper
0.256
3145593CAROLNA
Solar/Wind Helper
0.256
3145933PARMELE
Solar/Wind Helper
0.506
3145933PARMELE
Solar/Wind Helper
0.253
3132123MT JACKSON
Solar/Wind Helper
0.782
316049AB1-081 GEN
Solar/Wind Helper
1.52
3146626S HERTFORD
Solar/Wind Helper
0.264
3146926FARMVIL
Solar/Wind Helper
0.154
3142666NORTHAMPTON
Solar/Wind Helper
0.256
316190AA2-174 GEN
Solar/Wind Helper
0.017
3145933PARMELE
Solar/Wind Helper
0.253
3146233WITAKRS
Solar/Wind Helper
0.269
3146233WITAKRS
Solar/Wind Helper
0.17
3148013FISHERV
Solar/Wind Helper
0.249
316197AC1-042 GEN
Solar/Wind Helper
0.215
G-007ALTFEXP_G-007A->PJM
CMTX
64.386
CBM NorthLTFEXP_CBM-N->PJM
CBM
88.776
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.761
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.838
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.974
VTFLTFEXP_VFT->PJM
CMTX
167.343
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.505
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.469

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH025_SRT-A/* $ CHESCO $ PECO_P4_PEACH025 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.01 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5068.35
MW Contribution:
11.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232904IR4
Adder
150.952
200200DELTA2 CT1
50/50
6.589
200193DELTA CT2
50/50
3.682
200203Y1-065-STG
50/50
12.879
200055ROCKSP 4
50/50
4.651
233939AC1-091 C
Solar/Wind Harmer
5.006
232914OH NUG3
Adder
16.488
232916OH NUG5
Adder
16.488
233933AB2-153 GEN
Solar/Wind Harmer
2.057
219623KINSLEYBEA C
Solar/Wind Harmer
0.604
213958STHWK5-6
Adder
3.797
20716428NHV_W2-082
Solar/Wind Harmer
2.336
963391AG1-188 GEN
Solar/Wind Harmer
4.87
219612MATRIX C
Solar/Wind Harmer
0.224
20716928W4-060COL
Solar/Wind Harmer
0.866
217213AMBOY SO C
Solar/Wind Harmer
0.149
20673728F2S_V4-070
Solar/Wind Harmer
0.207
207510AF2-138 C
Solar/Wind Harmer
1.884
207437AD2-070 GEN
Solar/Wind Harmer
0.3
20671928W4-073
Solar/Wind Harmer
0.428
20465427SHAW CT
Adder
3.814
20633028GILCT9
Adder
27.819
209116AE2-175 GEN
Solar/Wind Harmer
3.885
970095AG2-074 GEN
Solar/Wind Harmer
5.249
961421AF2-433 GEN
Solar/Wind Harmer
0.727
232432Z2-076 GEN
Solar/Wind Harmer
0.246
233968AD2-076_GEN
Solar/Wind Harmer
12.195
231919CHRIST1
Adder
7.728
231920CHRIST2
Adder
7.557
230430AE1-229_GEN
Solar/Wind Harmer
42.068
230422AE1-104_GEN1
Solar/Wind Harmer
49.451
230425AE1-104_GEN2
Solar/Wind Harmer
49.451
230407AD2-065 C
Solar/Wind Harmer
0.191
20720728JCB_W1-129
Solar/Wind Harmer
0.392
207500AE2-000G1
Solar/Wind Harmer
41.181
970025AG2-016 GEN
Solar/Wind Harmer
3.683
20714428HOW_X1-037
Solar/Wind Harmer
1.542
218449LINSOLAR C
Solar/Wind Harmer
1.163
232434Z2-077 GEN
Solar/Wind Harmer
0.467
232406W1-004 FULL
Solar/Wind Harmer
1.866
233964AF2-378 GEN
Solar/Wind Harmer
0.238
232422X3-066 FULL
Solar/Wind Harmer
0.459
230415AB2-049 C
Solar/Wind Harmer
0.277
219291REEVESSOUT C
Solar/Wind Harmer
0.084
219236SOUTHERNHQ C
Solar/Wind Harmer
0.093
213815MOSER1-3
Adder
4.773
20714928UPF_X1-085
Solar/Wind Harmer
0.526
219114HARTZY_C
Solar/Wind Harmer
1.074
219918AC2-009 C
Solar/Wind Harmer
0.032
20674528F3S_W2-016
Solar/Wind Harmer
1.565
209025WIENIPP3
Adder
4.39
209142AF1-226 GEN
Solar/Wind Harmer
4.21
205941AD2-115 GEN
Solar/Wind Harmer
0.583
227287AC2-120 GEN
Solar/Wind Helper
0.426
966881AG1-559 GEN
Solar/Wind Helper
0.334
316473AC1-191 GEN
Solar/Wind Helper
1.489
3142946ENON
Solar/Wind Helper
0.081
3145336SMITFLD
Solar/Wind Helper
0.096
316017AA1-139 ULT1
Solar/Wind Helper
1.093
3146456SLIGO L269
Solar/Wind Helper
0.239
3145273HOLLAND
Solar/Wind Helper
0.178
3146376EDENTON
Solar/Wind Helper
0.236
3146206CASHIE
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
316181AB2-040 GEN
Solar/Wind Helper
1.675
3147043LAWRENC
Solar/Wind Helper
0.14
3147133PAMPLIN
Solar/Wind Helper
0.729
316478AD1-087 GEN
Solar/Wind Helper
1.138
316420AA1-050 GEN
Solar/Wind Helper
1.319
23777801MSM_W1-116
Solar/Wind Helper
0.099
3146073TAR RVR
Solar/Wind Helper
0.229
3146083TARBORO
Solar/Wind Helper
0.229
316499AE2-029_GEN
Solar/Wind Helper
0.772
3138543CONSLDL
Solar/Wind Helper
0.151
316003AC1-222 GEN
Solar/Wind Helper
0.984
316095T157 G97
Solar/Wind Helper
1.03
316222AC1-221 GEN
Solar/Wind Helper
1.283
316283AC2-100 C
Solar/Wind Helper
1.195
232926CRISFLD1
Adder
3.664
231940T-011
Adder
1.392
234041AC1-190 GEN
Solar/Wind Harmer
16.684
228201CARL#2CT
Adder
10.156
228200CARL#1CT
Adder
9.66
219904AC1-010 C
Solar/Wind Harmer
0.53
219906AC1-017 C
Solar/Wind Harmer
0.304
213815MOSER1-3
Adder
4.773
213815MOSER1-3
Adder
4.773
233987AB2-037 GEN
Solar/Wind Harmer
21.269
233973AC2-185 C
Solar/Wind Harmer
10.113
970695AG2-447 GEN
Solar/Wind Harmer
6.69
233923SMA
Solar/Wind Harmer
6.821
233997TMININ_4.2
Solar/Wind Harmer
1.86
232907VN8
Adder
56.056
232417X3-008 C
Solar/Wind Harmer
2.095
233935AB2-179 C
Solar/Wind Harmer
4.455
219221BRL12CT1
Adder
12.074
219223BRL12CT3
Adder
12.074
959561AF2-247 GEN
Solar/Wind Harmer
0.64
20715728PEM_W1-119
Solar/Wind Harmer
0.7
20636028O CRK C1
Adder
9.24
971667AH1-334 GEN
Solar/Wind Harmer
3.545
219727YARDVSOLFA C
Solar/Wind Harmer
1.165
20635828PARLN1&2
Adder
4.033
219249CENTRALDIV C
Solar/Wind Harmer
0.046
207442AE1-156 GEN
Solar/Wind Harmer
0.857
217211CAMDEN ST C
Solar/Wind Harmer
0.028
217194REDH C
Solar/Wind Harmer
0.557
207511W3-106 GEN
Solar/Wind Harmer
0.35
971007AG2-625 GEN
Solar/Wind Harmer
2.614
20466127PORT 5CT
Adder
26.45
20674128FR_U2-059
Solar/Wind Harmer
0.182
211065PSPA IPP
Solar/Wind Harmer
0.414
957921AF2-086 GEN
Solar/Wind Harmer
0.707
316223AC1-118
Solar/Wind Helper
0.376
3132273ORANGE
Solar/Wind Helper
0.049
3144536CHRHLND
Solar/Wind Helper
0.036
3142956BIRDNECK
Solar/Wind Helper
0.161
316305AF2-043 C
Solar/Wind Helper
0.321
316320Y1-086
Solar/Wind Helper
0.107
3146516WINFALL
Solar/Wind Helper
0.238
23546401DTGZ2-030
Solar/Wind Helper
0.074
315735AD1-075 GEN1
Solar/Wind Helper
1.344
3145893MURPHYS
Solar/Wind Helper
0.084
3145893MURPHYS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.084
3146263WOODLND
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
316011AB1-132 GEN
Solar/Wind Helper
2.509
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.229
270494AE1-108_GEN
Solar/Wind Helper
3.067
200195DELTA ST
50/50
5.688
232920IR10
Adder
5.9
233901CHERRYDALE C
Solar/Wind Harmer
2.1
232913OH NUG2
Adder
16.268
970597AG2-380 GEN
Solar/Wind Harmer
7.658
231906DC3 NUG
Adder
25.712
231907DC10
Adder
6.419
972141AH1-641 GEN
Solar/Wind Harmer
4.232
213611FALLS1-3
Adder
4.677
213611FALLS1-3
Adder
4.677
20715028HAN_X4-015
Solar/Wind Harmer
0.392
207507AE2-000G3
Solar/Wind Harmer
41.181
207445AB1-138_GEN
Solar/Wind Harmer
0.745
20720628TIN_W1-124
Solar/Wind Harmer
1.238
971521AH1-258 GEN
Solar/Wind Harmer
3.337
20675528CPH_W2-050
Solar/Wind Harmer
0.673
20676428JCR_X2-075
Solar/Wind Harmer
0.392
217086KRNY_131
Adder
10.447
20675128HRM_W1-127
Solar/Wind Harmer
0.168
209029WAYMART-WD
Solar/Wind Harmer
2.183
959421AF2-233 GEN
Solar/Wind Harmer
0.664
226929AD2-058 GEN
Solar/Wind Helper
0.12
3138216PACIFIC
Solar/Wind Helper
0.042
316164AC1-076 GEN
Solar/Wind Helper
1.186
3141813NORNECK
Solar/Wind Helper
0.244
957601AF2-054 GEN
Solar/Wind Helper
0.325
316233AE1-074 FULL
Solar/Wind Helper
0.369
316018AA1-139 ULT2
Solar/Wind Helper
1.029
315800Z1-036_GEN1
Solar/Wind Helper
1.302
315732AD1-074 GEN1
Solar/Wind Helper
2.687
3145893MURPHYS
Solar/Wind Helper
0.632
3145893MURPHYS
Solar/Wind Helper
0.234
316463AE2-346 GEN
Solar/Wind Helper
0.214
3145513AHOSKIE
Solar/Wind Helper
0.105
3145513AHOSKIE
Solar/Wind Helper
0.234
3137643SOCKMAN
Solar/Wind Helper
0.93
316426AA2-053 GEN
Solar/Wind Helper
1.331
316174AB2-169 GEN
Solar/Wind Helper
0.595
3144303KENBRDG
Solar/Wind Helper
0.185
23779801AA1-109
Solar/Wind Helper
0.167
316327AA2-057 GEN
Solar/Wind Helper
1.315
200035PCHBTM 3
50/50
38.06
233971AC1-093 C
Solar/Wind Harmer
4.753
232918OH NUG7
Adder
16.378
232905CHERITON_25
Adder
4.58
233994AC2-023 GEN
Solar/Wind Harmer
5.009
234036AF2-325 C
Solar/Wind Harmer
1.708
232910NRG_G1
Adder
15.988
234014AF1-036_GEN
Solar/Wind Harmer
4.978
232436AB1-176 C
Solar/Wind Harmer
0.421
972233AH1-701 GEN
Adder
6.064
219912AD2-042 GEN
Solar/Wind Harmer
1.108
219607WPEMNERT C
Solar/Wind Harmer
0.566
219304NAMERICA C
Solar/Wind Harmer
0.42
20635028RRCT1&2
Adder
13.875
218418LINDEN_G5
Adder
20.066
219036LINDEN_G7
Adder
19.339
217086KRNY_131
Adder
10.559
20674328GAR_V4-001
Solar/Wind Harmer
0.116
946751AF1-339 GEN
Solar/Wind Harmer
0.669
316006AB2-029 C
Solar/Wind Helper
0.12
316045AC1-158 PL2
Solar/Wind Helper
4.434
966871AG1-558 GEN
Solar/Wind Helper
0.329
315666AE1-190 GEN
Solar/Wind Helper
0.327
316156AD2-030 GEN
Solar/Wind Helper
0.367
316240AF1-291 C
Solar/Wind Helper
0.324
316313AB2-026
Solar/Wind Helper
0.365
316435W1029_GEN3
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
315614AA2-178 GEN
Solar/Wind Helper
1.439
238149AF1-291A_GEN
Solar/Wind Helper
0.116
3145893MURPHYS
Solar/Wind Helper
0.336
3145893MURPHYS
Solar/Wind Helper
0.422
3146776BUCKING
Solar/Wind Helper
0.935
3146776BUCKING
Solar/Wind Helper
0.076
316140AB2-099
Solar/Wind Helper
0.089
316005AA1-067
Solar/Wind Helper
0.264
316118AC1-105 GEN
Solar/Wind Helper
0.888
20720828JCB_W4-025
Solar/Wind Harmer
0.595
20714828MDF_W3-079
Solar/Wind Harmer
0.388
219817TRENTONSOL C
Solar/Wind Harmer
1.38
20641628MLH_W1-032
Solar/Wind Harmer
0.365
20742028HF_AC1-207
Solar/Wind Harmer
0.97
218438BLK ROCK C
Solar/Wind Harmer
0.166
972260AH1-715 GEN1
Adder
16.068
972261AH1-715 GEN2
Adder
18.513
217202FBANKSOLAR C
Solar/Wind Harmer
0.084
217201HACKENSOLA C
Solar/Wind Harmer
0.083
217206BARNGR HS C
Solar/Wind Harmer
0.035
217204WCALDSOLAR C
Solar/Wind Harmer
0.082
20674828DL_W4-046
Solar/Wind Harmer
0.665
20634528N27_Y2-018
Solar/Wind Harmer
0.274
315976AC1-164 GENA
Solar/Wind Helper
3.126
316169AC1-164_GENC
Solar/Wind Helper
2.7
3142946ENON
Solar/Wind Helper
0.024
316294AC1-161 GEN
Solar/Wind Helper
4.388
316349AD2-085 GEN
Solar/Wind Helper
1.094
3146386ELIZ CT
Solar/Wind Helper
0.238
316431W1029_GEN1
Solar/Wind Helper
0.961
316433W1029_GEN2
Solar/Wind Helper
0.961
238147AE2-230_GEN1
Solar/Wind Helper
0.406
316365GEN2_N
Solar/Wind Helper
0.894
3146173TUNIS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3147133PAMPLIN
Solar/Wind Helper
0.232
3147133PAMPLIN
Solar/Wind Helper
0.186
3146843MT LREL
Solar/Wind Helper
0.229
3146843MT LREL
Solar/Wind Helper
0.229
316097T157 G90
Solar/Wind Helper
1.03
232901NORTHST
Adder
15.553
234033AF1-007_GEN
Solar/Wind Harmer
69.442
233996TM1833_GEN
Solar/Wind Harmer
1.86
232426Y1-080 FULL
Solar/Wind Harmer
0.356
232902EASTMUNI
Adder
24.193
234012AE2-112_GEN
Solar/Wind Harmer
4.231
972251AH1-710 GEN
Adder
80.304
231918WEST 1
Adder
5.882
228732V1-021 C
Adder
0.28
228400MICK 1CT
Adder
17.044
219766PARADISE C
Solar/Wind Harmer
0.441
20714528FRN_Y2-051
Solar/Wind Harmer
0.374
219680HOPEWELLV C1
Solar/Wind Harmer
0.095
218440SUMMTASSOC C
Solar/Wind Harmer
0.151
217208PARK ELE C
Solar/Wind Harmer
0.029
966261AG1-495 GEN
Solar/Wind Harmer
3.783
20674628WNG_W3-110
Solar/Wind Harmer
0.427
963071AG1-156 GEN
Solar/Wind Harmer
8.288
209023WIENIPP1
Adder
8.977
209025WIENIPP3
Adder
4.481
316447AC1-158 HLD
Solar/Wind Helper
3.049
316192AB2-158 GEN
Solar/Wind Helper
1.653
3142416OLDCHRC
Solar/Wind Helper
0.631
3142416OLDCHRC
Solar/Wind Helper
0.242
3141766HARMONY
Solar/Wind Helper
0.048
3142433PROV 92
Solar/Wind Helper
0.969
315975AC1-164 GENB
Solar/Wind Helper
0.092
3145336SMITFLD
Solar/Wind Helper
0.958
316375AC2-012 GEN
Solar/Wind Helper
0.63
3146456SLIGO L269
Solar/Wind Helper
0.239
3145663CRESWEL
Solar/Wind Helper
0.659
316023GEN1_S
Solar/Wind Helper
0.894
3146206CASHIE
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3156021HOLLOMANSOL
Solar/Wind Helper
1.783
3145683EARLEYS
Solar/Wind Helper
0.233
316131AB2-060 GEN
Solar/Wind Helper
1.41
3146083TARBORO
Solar/Wind Helper
0.229
316359AB2-059 GEN
Solar/Wind Helper
1.746
217147KRNY_1212
Adder
10.022
217147KRNY_1212
Adder
9.843
217146KRNY_1234
Adder
9.821
217146KRNY_1234
Adder
9.754
964851AG1-348 GEN
Solar/Wind Harmer
1.391
207408W3-077 C
Solar/Wind Harmer
0.509
20462827N BANGR8
Adder
0.708
209026WIENIPP4
Adder
4.436
209054AE2-059 GEN
Solar/Wind Harmer
1.158
315651AD1-115 GEN
Solar/Wind Helper
0.837
3141783LANCAST
Solar/Wind Helper
0.146
3141783LANCAST
Solar/Wind Helper
0.097
316059AD1-063 C
Solar/Wind Helper
0.245
238169AE2-226 GEN1
Solar/Wind Helper
0.583
238170AE2-226 GEN2
Solar/Wind Helper
0.583
313526AB2-022
Solar/Wind Helper
0.364
3146206CASHIE
Solar/Wind Helper
0.234
961941AG1-037 GEN
Solar/Wind Helper
0.079
3146043SEABORD
Solar/Wind Helper
0.233
3145683EARLEYS
Solar/Wind Helper
0.467
3145683EARLEYS
Solar/Wind Helper
0.233
3145683EARLEYS
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
316486AD2-202 GEN
Solar/Wind Helper
0.333
316274AC1-208 GEN
Solar/Wind Helper
1.411
3147173SINAI
Solar/Wind Helper
0.227
3147243WELCO
Solar/Wind Helper
0.142
237030AB1-096 C
Solar/Wind Helper
0.058
237025AB1-124 C
Solar/Wind Helper
0.142
3148463FAIRFLD
Solar/Wind Helper
0.225
200204Y1-065-CTG1
50/50
7.437
233918AB1-142 GEN
Solar/Wind Harmer
1.81
228206SHRMN CT
Adder
24.633
228260V4-054C
Solar/Wind Harmer
1.516
228729W2-030 C
Solar/Wind Harmer
0.84
219686LUMSOLAR_N C
Solar/Wind Harmer
0.282
219348LDSOLAR C
Solar/Wind Harmer
0.809
213611FALLS1-3
Adder
4.677
214194N WALES4
Adder
1.114
20720428HOL_W1-112
Solar/Wind Harmer
0.425
20635828PARLN1&2
Adder
8.905
20635028RRCT1&2
Adder
14.092
218524CNTRALGAS1 C
Solar/Wind Harmer
0.437
217209CENTRL HS C
Solar/Wind Harmer
0.051
20671828STAW2-080
Solar/Wind Harmer
0.118
207439AE1-081 C O1
Solar/Wind Harmer
0.064
207530AG1-191 GEN
Solar/Wind Harmer
1.449
211065PSPA IPP
Solar/Wind Harmer
0.414
961301AF2-421 GEN
Solar/Wind Harmer
0.832
963151AG1-164 GEN
Solar/Wind Harmer
0.832
961341AF2-425 GEN
Solar/Wind Harmer
0.73
212507AE2-042_GEN
Solar/Wind Harmer
2.052
316337AD2-073 GEN
Solar/Wind Helper
0.373
3141726DUNNSVL
Solar/Wind Helper
0.977
316132AB2-190 GEN1
Solar/Wind Helper
1.378
315773AC2-141 GEN
Solar/Wind Helper
5.163
316036AC1-147 C
Solar/Wind Helper
0.365
3146516WINFALL
Solar/Wind Helper
0.769
3146516WINFALL
Solar/Wind Helper
0.238
3145893MURPHYS
Solar/Wind Helper
0.937
3146776BUCKING
Solar/Wind Helper
0.093
315607AA1-063A GEN
Solar/Wind Helper
1.335
3146263WOODLND
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
316494AC1-189 GEN
Solar/Wind Helper
1.404
961671AG1-007 GEN
Solar/Wind Helper
0.165
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.183
209093AE2-110 GEN
Solar/Wind Harmer
1.818
209120AE2-241 GEN
Solar/Wind Harmer
2.406
946691AF1-333 GEN
Solar/Wind Harmer
0.669
946741AF1-338 GEN
Solar/Wind Harmer
0.669
226910AB2-157 C
Solar/Wind Helper
0.018
3141196NOKESVL
Solar/Wind Helper
1.01
316077AC2-138 C
Solar/Wind Helper
0.231
316484AD2-074 GEN
Solar/Wind Helper
0.47
316075AC2-137 C
Solar/Wind Helper
0.37
966621AG1-532 GEN
Solar/Wind Helper
0.212
942461AE2-259 GEN
Solar/Wind Helper
1.569
316317KELFORD C
Solar/Wind Helper
0.21
3145823KELFORD
Solar/Wind Helper
0.233
3145796HORNRTN
Solar/Wind Helper
0.928
3145796HORNRTN
Solar/Wind Helper
0.232
200202DELTA2 ST
50/50
11.158
200052ROCKSP 1
50/50
4.679
200053ROCKSP 2
50/50
4.587
233940AF2-379 C
Solar/Wind Harmer
0.348
230434AG1-499 GEN
Solar/Wind Harmer
0.842
219258KINSLEYDEP C
Solar/Wind Harmer
0.456
213942SCHUYLKILL
Adder
4.971
213942SCHUYLKILL
Adder
3.801
213957STHWK3-4
Adder
3.797
213957STHWK3-4
Adder
3.797
213561DLWR9-10
Adder
4.885
213561DLWR9-10
Adder
3.736
219610FLORENCE C
Solar/Wind Harmer
1.873
963401AG1-189 GEN
Solar/Wind Harmer
2.961
971189AH1-054 GEN
Solar/Wind Harmer
1.531
20716228APLW2-078
Solar/Wind Harmer
1.097
20673828FLE_V3-070
Solar/Wind Harmer
0.542
20676128MHD_W3-029
Solar/Wind Harmer
0.55
209027LOR2_Q27
Solar/Wind Harmer
3.43
964051AG1-259 GEN
Solar/Wind Harmer
0.891
964061AG1-260 GEN
Solar/Wind Harmer
0.891
3141426STAFORD
Solar/Wind Helper
0.056
316468AD1-105 GEN
Solar/Wind Helper
1.184
3141913WHIT STONE
Solar/Wind Helper
0.243
957831AF2-077 GEN
Solar/Wind Helper
0.325
315697AD1-025 GEN
Solar/Wind Helper
2.753
315839AE2-212 C
Solar/Wind Helper
0.324
316316AC1-027 C
Solar/Wind Helper
0.378
316258AE1-075 C
Solar/Wind Helper
0.328
316322AB2-045
Solar/Wind Helper
0.261
3145796HORNRTN
Solar/Wind Helper
0.743
3145796HORNRTN
Solar/Wind Helper
0.093
316210AC1-098 GEN
Solar/Wind Helper
1.87
316238AB2-078_GEN
Solar/Wind Helper
0.311
316239AB2-077_GEN
Solar/Wind Helper
0.311
3145746EVERETS
Solar/Wind Helper
0.917
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
3148133STUARTS
Solar/Wind Helper
0.138
3145573BETHELC
Solar/Wind Helper
0.229
3145573BETHELC
Solar/Wind Helper
0.229
200201DELTA2 CT2
50/50
6.589
232410W1-006 C
Solar/Wind Harmer
1.866
232899W1-062
Adder
17.933
233946AB2-136 GEN
Solar/Wind Harmer
7.433
233952AC2-187 GEN
Solar/Wind Harmer
2.093
233954AC2-188 GEN
Solar/Wind Harmer
2.093
233984AB2-036 GEN
Solar/Wind Harmer
23.015
233930AB2-032 GEN
Solar/Wind Harmer
1.524
233982AB2-133 GEN
Solar/Wind Harmer
8.899
230511AF1-262
Solar/Wind Harmer
0.268
228307PCLP GT
Adder
17.618
228754AB1-001 C
Solar/Wind Harmer
0.202
213587EDDYSTN3
Adder
113.958
219272CLEANLIGHT C
Solar/Wind Harmer
0.256
217081WEATEXAS C
Solar/Wind Harmer
0.099
217083KRNY_132
Adder
10.47
200194DELTA CT3
50/50
3.682
233970AC1-092 C
Solar/Wind Harmer
5.006
232404W1-003 C
Solar/Wind Harmer
1.866
233998TM1NIN_3.36
Solar/Wind Harmer
1.86
232919VN10
Adder
5.235
232900DEMECSMY
Adder
17.201
231917EM10
Adder
4.08
970997AG2-616 GEN
Solar/Wind Harmer
14.106
207471AF2-354 C
Solar/Wind Harmer
0.525
20675928HOL_W4-097
Solar/Wind Harmer
0.13
209010PEIP 1
Adder
2.989
209010PEIP 1
Adder
0.438
961541AF2-445A GEN
Solar/Wind Harmer
2.465
961431AF2-434 GEN
Solar/Wind Harmer
0.727
209130AF1-271A GEN
Solar/Wind Harmer
1.867
223402AF1-300 C
Solar/Wind Helper
0.484
316411AF1-147_GEN1
Solar/Wind Helper
0.856
316312AB1-027
Solar/Wind Helper
0.464
3143526WINTERP
Solar/Wind Helper
1.257
316185AD1-033 GEN
Solar/Wind Helper
1.127
3144356SAPONY
Solar/Wind Helper
0.425
316315AB2-025 C
Solar/Wind Helper
0.362
237061AD1-155 GEN
Solar/Wind Helper
1.469
3145796HORNRTN
Solar/Wind Helper
0.696
316237AB2-079_GEN
Solar/Wind Helper
0.311
235020AA1-095 C
Solar/Wind Helper
0.043
315687AD1-152 GEN
Solar/Wind Helper
1.24
316248AF1-058 C
Solar/Wind Helper
0.306
238221AF1-254 C O1
Solar/Wind Helper
0.222
200192DELTA CT1
50/50
3.682
200054ROCKSP 3
50/50
4.733
232408W1-005 C
Solar/Wind Harmer
1.866
232917OH NUG6
Adder
16.415
232915OH NUG4
Adder
16.378
972177AH1-672 GEN
Solar/Wind Harmer
25.067
233944AB2-135 GEN
Solar/Wind Harmer
9.589
213958STHWK5-6
Adder
3.797
219907AC1-030 C
Solar/Wind Harmer
0.191
20716028EGP_W2-019
Solar/Wind Harmer
0.61
207522AF2-254 C
Solar/Wind Harmer
1.885
218428ETC SOLAR C
Solar/Wind Harmer
0.042
219908AB1-139 C
Solar/Wind Harmer
0.448
972275AH1-722 GEN
Adder
36.889
20673628F1S_V4-069
Solar/Wind Harmer
0.207
207528AF2-192 GEN
Solar/Wind Harmer
1.466
217186ESSEX_G9
Adder
4.476
217083KRNY_132
Adder
10.537
20676228FRD_X1-012
Solar/Wind Harmer
0.624
20675828AU_W4-064
Solar/Wind Harmer
0.182
20675728RH_W2-091
Solar/Wind Harmer
0.606
207484AF2-139 C O1
Solar/Wind Harmer
0.504
208909MACR G3
Adder
154.549
209010PEIP 1
Adder
0.543
946731AF1-337 GEN
Solar/Wind Harmer
0.669
316415AF1-147_GEN2
Solar/Wind Helper
0.856
964211AG1-282 GEN
Solar/Wind Helper
0.329
3143526WINTERP
Solar/Wind Helper
1.257
315671AE2-027_GEN
Solar/Wind Helper
1.945
238175AF1-290_GEN
Solar/Wind Helper
0.129
316072AD1-144
Solar/Wind Helper
0.274
3145823KELFORD
Solar/Wind Helper
0.233
3145783HORNRTN
Solar/Wind Helper
0.232
3145796HORNRTN
Solar/Wind Helper
0.766
3145796HORNRTN
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.243
316129AC1-054 GEN
Solar/Wind Helper
1.147
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
3147983MERCK5
Solar/Wind Helper
0.092
315821AE2-092 GEN
Solar/Wind Helper
2.154
316212AC1-099_GEN
Solar/Wind Helper
1.039
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
23583801GRNGAP
Solar/Wind Helper
3.821
232912OH NUG1
Adder
16.488
971195AH1-057 GEN
Solar/Wind Harmer
1.819
233955AB2-172 GEN
Solar/Wind Harmer
9.311
232813VAUGHN
Adder
1.092
231902DC CT7
Adder
20.555
233915AB1-141 GEN
Solar/Wind Harmer
1.81
970453AG2-297 GEN
Solar/Wind Harmer
4.121
964001AG1-254 GEN
Solar/Wind Harmer
10.701
228728W1-130C
Solar/Wind Harmer
0.97
227927V4-067C
Solar/Wind Harmer
0.288
219137THOSOLAR C
Solar/Wind Harmer
1.719
219615MILLCREEK C
Solar/Wind Harmer
0.325
219224BRL12CT4
Adder
12.074
207487AE2-000G4
Solar/Wind Harmer
41.181
207497AE2-000G2
Solar/Wind Harmer
41.181
219620RIDERU C
Solar/Wind Harmer
0.07
20635928PARLN3&4
Adder
8.905
218526CNTRALGAS2 C
Solar/Wind Harmer
0.439
217167KRNY_14
Adder
10.537
971009AG2-626 GEN
Solar/Wind Harmer
1.667
961261AF2-417 GEN
Solar/Wind Harmer
0.886
212266LOR1
Solar/Wind Harmer
0.909
959431AF2-234 GEN
Solar/Wind Harmer
1.328
3138133OCRAN
Solar/Wind Helper
0.073
3141873WAN 176
Solar/Wind Helper
0.048
3143873LANEXA
Solar/Wind Helper
0.145
316382AG1-145 C
Solar/Wind Helper
0.325
316159AE1-175 C
Solar/Wind Helper
0.366
316236AE1-162_GEN
Solar/Wind Helper
0.323
3143316POE
Solar/Wind Helper
0.948
316405AF2-144 C
Solar/Wind Helper
0.273
3146486SUNBURY
Solar/Wind Helper
0.238
3146486SUNBURY
Solar/Wind Helper
0.238
3145176PASQUOTANK
Solar/Wind Helper
0.147
3130156CHOWAN
Solar/Wind Helper
0.236
200034PCHBTM 2
50/50
38.39
200205Y1-065-CTG2
50/50
7.437
234015AF2-250 C
Solar/Wind Harmer
0.224
232428Y3-058 C
Solar/Wind Harmer
1.555
232424Y1-079 C
Solar/Wind Harmer
1.038
228251CARLLS#4
Adder
0.932
228351V2-046C
Solar/Wind Harmer
2.956
230433AD2-135 GEN
Solar/Wind Harmer
0.148
213589EDDYSTN4
Adder
113.991
219287REEVESEAST C
Solar/Wind Harmer
1.876
213535CROYDN11
Adder
13.816
214067T20SOLAR
Solar/Wind Harmer
0.334
20636128O CRK C2
Adder
8.425
207459AE1-142 C O1
Solar/Wind Harmer
1.361
20628028LAKEHURS
Adder
1.224
217197RE CRAN C
Solar/Wind Harmer
0.655
924131AB2-057 GEN
Solar/Wind Harmer
1.234
20635128RRCT3&4
Adder
13.393
20635128RRCT3&4
Adder
11.683
218419LINDEN_G6
Adder
20.066
219035LINDEN_G8
Adder
19.063
20675428EAM_W2-061
Solar/Wind Harmer
0.218
972237AH1-703 GEN
Adder
11.476
20465127PORT CT
Adder
3.97
223401AF1-299 GEN
Solar/Wind Helper
0.484
316450AC1-158 RIC
Solar/Wind Helper
0.37
966001AG1-469 GEN
Solar/Wind Helper
0.261
316487AF1-042 GEN
Solar/Wind Helper
0.246
316033AB2-134 GEN
Solar/Wind Helper
0.833
3145506HICKORY
Solar/Wind Helper
0.955
3145506HICKORY
Solar/Wind Helper
0.573
3145506HICKORY
Solar/Wind Helper
0.143
316339AD2-160 GEN
Solar/Wind Helper
0.911
316388AE2-253 GEN
Solar/Wind Helper
0.911
3137176SLIGO L2192
Solar/Wind Helper
0.949
3130086AYDLETT
Solar/Wind Helper
0.954
3146626S HERTFORD
Solar/Wind Helper
0.237
3146626S HERTFORD
Solar/Wind Helper
0.237
238148AE2-230_GEN2
Solar/Wind Helper
0.406
313506AB2-031 GEN
Solar/Wind Helper
1.061
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.14
3145593CAROLNA
Solar/Wind Helper
0.233
3145593CAROLNA
Solar/Wind Helper
0.233
3145933PARMELE
Solar/Wind Helper
0.462
3145933PARMELE
Solar/Wind Helper
0.231
3132123MT JACKSON
Solar/Wind Helper
0.721
316049AB1-081 GEN
Solar/Wind Helper
1.397
237006AB1-125 GEN
Solar/Wind Helper
0.106
213497CHSTR7-9
Adder
3.911
213497CHSTR7-9
Adder
3.911
213560DLW11-12
Adder
3.736
219222BRL12CT2
Adder
12.074
20717128DIX_Z2-102
Solar/Wind Harmer
1.732
20715828PEM_W1-120
Solar/Wind Harmer
0.7
963711AG1-223 GEN
Solar/Wind Harmer
1.878
219276PARKLANDSO C
Solar/Wind Harmer
0.582
20715228NPK_W1-113
Solar/Wind Harmer
0.534
20720528MAN_W1-024
Solar/Wind Harmer
0.315
219919AE1-041 FULL
Solar/Wind Harmer
0.048
217121ECCF
Adder
0.492
20676728BRNX1-095
Solar/Wind Harmer
0.194
20676328BVR_Y1-020
Solar/Wind Harmer
0.352
20674928WA_W3-044
Solar/Wind Harmer
0.494
971519AH1-257 GEN
Solar/Wind Harmer
2.558
207518AF1-320_GEN
Solar/Wind Harmer
3.668
20465127PORT CT
Adder
2.992
209018SUNBIPCT
Adder
4.947
316044AC1-158 PL1
Solar/Wind Helper
1.386
3147666LOUISA
Solar/Wind Helper
0.982
316404AE1-155 C
Solar/Wind Helper
2.087
3138133OCRAN
Solar/Wind Helper
0.146
315662AE1-191 GEN
Solar/Wind Helper
1.307
316280AD1-041 GEN
Solar/Wind Helper
0.817
3142543TWELFTH
Solar/Wind Helper
0.023
3143226MDLTHAN
Solar/Wind Helper
0.242
316369SG1_INVT
Solar/Wind Helper
1.16
316381AD1-082 GEN
Solar/Wind Helper
1.242
319010AE1-072 C
Solar/Wind Helper
2.731
315611Z1-036_GEN2
Solar/Wind Helper
1.302
3130156CHOWAN
Solar/Wind Helper
0.236
315816AE2-034 GEN
Solar/Wind Helper
1.079
238152AF2-075_GEN
Solar/Wind Helper
0.58
315737AD1-076 GEN
Solar/Wind Helper
2.298
3146926FARMVIL
Solar/Wind Helper
0.14
316087AB2-174 GEN
Solar/Wind Helper
1.634
315785AD2-033 C
Solar/Wind Helper
2.702
23777901MDS_W4-102
Solar/Wind Helper
0.145
3146233WITAKRS
Solar/Wind Helper
0.912
233972AC1-094 C
Solar/Wind Harmer
4.02
232921TASLEY2G
Adder
9.636
233950AC2-186 GEN
Solar/Wind Harmer
1.047
228711V2-041C
Solar/Wind Harmer
0.893
213497CHSTR7-9
Adder
3.911
219921AF1-264
Solar/Wind Harmer
0.203
218660EHAMPSOLAR C
Solar/Wind Harmer
0.244
219688LUMSOLAR_S C
Solar/Wind Harmer
0.282
219914AD2-027 C
Solar/Wind Harmer
0.836
213560DLW11-12
Adder
3.736
207454AA2-184 E
Solar/Wind Harmer
1.242
20635928PARLN3&4
Adder
4.033
217169METRODIV C
Solar/Wind Harmer
0.045
963161AG1-165 GEN
Solar/Wind Harmer
0.832
208972BECR K09
Solar/Wind Harmer
0.867
961331AF2-424 GEN
Solar/Wind Harmer
0.73
209071AE2-133 GEN
Solar/Wind Harmer
1.124
3141906WESTMOR
Solar/Wind Helper
0.098
3147666LOUISA
Solar/Wind Helper
0.565
316458AB2-190 GEN2
Solar/Wind Helper
1.378
3144873MCLAUGH
Solar/Wind Helper
0.006
316246AF1-032 C
Solar/Wind Helper
0.273
316321Z2-027
Solar/Wind Helper
0.363
3146626S HERTFORD
Solar/Wind Helper
0.237
3146926FARMVIL
Solar/Wind Helper
0.14
3142666NORTHAMPTON
Solar/Wind Helper
0.233
316190AA2-174 GEN
Solar/Wind Helper
0.016
3145933PARMELE
Solar/Wind Helper
0.231
3148013FISHERV
Solar/Wind Helper
0.229
3146233WITAKRS
Solar/Wind Helper
0.247
3146233WITAKRS
Solar/Wind Helper
0.156
3130156CHOWAN
Solar/Wind Helper
0.236
3130546PLYMOUTH
Solar/Wind Helper
0.235
315733AD1-074 GEN2
Solar/Wind Helper
2.687
946281AF1-292 GEN
Solar/Wind Helper
0.234
3146033SCOT NK
Solar/Wind Helper
0.927
3148013FISHERV
Solar/Wind Helper
0.132
315616AA1-038_C
Solar/Wind Helper
1.022
G-007ALTFEXP_G-007A->PJM
CMTX
61.282
CBM NorthLTFEXP_CBM-N->PJM
CBM
75.829
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.876
BlueGrassPJM->LTFIMP_BlueG
CLTF
15.187
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.656
VTFLTFEXP_VFT->PJM
CMTX
154.628
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.362
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.841

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.68 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4947.73
MW Contribution:
13.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232912OH NUG1
Adder
15.338
971195AH1-057 GEN
Solar/Wind Harmer
1.085
232813VAUGHN
Adder
1.017
231902DC CT7
Adder
19.141
233915AB1-141 GEN
Solar/Wind Harmer
0.434
970453AG2-297 GEN
Solar/Wind Harmer
3.773
964001AG1-254 GEN
Solar/Wind Harmer
8.266
219224BRL12CT4
Adder
12.509
207487AE2-000G4
Solar/Wind Harmer
17.499
207497AE2-000G2
Solar/Wind Harmer
17.499
20635928PARLN3&4
Adder
9.943
218526CNTRALGAS2 C
Solar/Wind Harmer
1.024
217167KRNY_14
Adder
12.24
971009AG2-626 GEN
Solar/Wind Harmer
1.347
20334726NME_Y1-047
Adder
2.53
3138133OCRAN
Solar/Wind Helper
0.089
3141873WAN 176
Solar/Wind Helper
0.059
3143873LANEXA
Solar/Wind Helper
0.177
316382AG1-145 C
Solar/Wind Helper
0.395
316159AE1-175 C
Solar/Wind Helper
0.446
316236AE1-162_GEN
Solar/Wind Helper
0.391
3143316POE
Solar/Wind Helper
1.149
316405AF2-144 C
Solar/Wind Helper
0.331
3146486SUNBURY
Solar/Wind Helper
0.288
3146486SUNBURY
Solar/Wind Helper
0.288
3145176PASQUOTANK
Solar/Wind Helper
0.178
3130156CHOWAN
Solar/Wind Helper
0.285
3130156CHOWAN
Solar/Wind Helper
0.285
3130546PLYMOUTH
Solar/Wind Helper
0.282
315733AD1-074 GEN2
Solar/Wind Helper
3.224
946281AF1-292 GEN
Solar/Wind Helper
0.281
3146033SCOT NK
Solar/Wind Helper
1.106
3148013FISHERV
Solar/Wind Helper
0.157
315616AA1-038_C
Solar/Wind Helper
1.206
23750701CROSSCHOOL
Solar/Wind Helper
1.106
232904IR4
Adder
140.471
232432Z2-076 GEN
Solar/Wind Harmer
0.023
233968AD2-076_GEN
Solar/Wind Harmer
3.978
231919CHRIST1
Adder
7.29
231920CHRIST2
Adder
7.128
230422AE1-104_GEN1
Solar/Wind Harmer
19.857
230425AE1-104_GEN2
Solar/Wind Harmer
19.857
230430AE1-229_GEN
Solar/Wind Harmer
29.099
207500AE2-000G1
Solar/Wind Harmer
17.499
970025AG2-016 GEN
Solar/Wind Harmer
2.528
217147KRNY_1212
Adder
11.643
217147KRNY_1212
Adder
11.435
217146KRNY_1234
Adder
11.409
217146KRNY_1234
Adder
11.331
20462827N BANGR8
Adder
0.904
209026WIENIPP4
Adder
6.293
20486527WR_V4-052
Adder
1.044
200917MEHOOPANY_G
Solar/Wind Harmer
0.376
315651AD1-115 GEN
Solar/Wind Helper
1.039
3141783LANCAST
Solar/Wind Helper
0.178
3141783LANCAST
Solar/Wind Helper
0.118
316059AD1-063 C
Solar/Wind Helper
0.299
238169AE2-226 GEN1
Solar/Wind Helper
0.719
238170AE2-226 GEN2
Solar/Wind Helper
0.719
313526AB2-022
Solar/Wind Helper
0.439
3146206CASHIE
Solar/Wind Helper
0.281
961941AG1-037 GEN
Solar/Wind Helper
0.094
3138266HYDRAULIC
Solar/Wind Helper
0.013
3138266HYDRAULIC
Solar/Wind Helper
0.008
3146043SEABORD
Solar/Wind Helper
0.279
3145683EARLEYS
Solar/Wind Helper
0.558
3145683EARLEYS
Solar/Wind Helper
0.279
3145683EARLEYS
Solar/Wind Helper
0.279
316486AD2-202 GEN
Solar/Wind Helper
0.398
316274AC1-208 GEN
Solar/Wind Helper
1.68
3147173SINAI
Solar/Wind Helper
0.268
3147243WELCO
Solar/Wind Helper
0.168
3148463FAIRFLD
Solar/Wind Helper
0.266
270455AD2-022 GEN
Solar/Wind Helper
1.489
270197AD1-017 GEN1
Solar/Wind Helper
1.335
237030AB1-096 C
Solar/Wind Helper
0.059
237025AB1-124 C
Solar/Wind Helper
0.144
200200DELTA2 CT1
50/50
5.619
200193DELTA CT2
50/50
3.14
200203Y1-065-STG
50/50
11.126
200055ROCKSP 4
50/50
4.018
233939AC1-091 C
Solar/Wind Harmer
3.14
232914OH NUG3
Adder
15.338
232916OH NUG5
Adder
15.338
213958STHWK5-6
Adder
3.833
963391AG1-188 GEN
Solar/Wind Harmer
2.527
207437AD2-070 GEN
Solar/Wind Harmer
0.082
20633028GILCT9
Adder
35.557
20465427SHAW CT
Adder
4.866
970095AG2-074 GEN
Solar/Wind Harmer
5.903
209093AE2-110 GEN
Solar/Wind Harmer
1.801
209120AE2-241 GEN
Solar/Wind Harmer
1.801
970767AG2-484 GEN
Solar/Wind Harmer
0.635
972221AH1-695 GEN
Adder
101.413
226910AB2-157 C
Solar/Wind Helper
0.021
3141196NOKESVL
Solar/Wind Helper
1.271
316077AC2-138 C
Solar/Wind Helper
0.282
316484AD2-074 GEN
Solar/Wind Helper
0.574
316075AC2-137 C
Solar/Wind Helper
0.451
966621AG1-532 GEN
Solar/Wind Helper
0.254
942461AE2-259 GEN
Solar/Wind Helper
1.877
316317KELFORD C
Solar/Wind Helper
0.25
3145823KELFORD
Solar/Wind Helper
0.278
315821AE2-092 GEN
Solar/Wind Helper
2.577
3145796HORNRTN
Solar/Wind Helper
1.107
3145796HORNRTN
Solar/Wind Helper
0.277
316212AC1-099_GEN
Solar/Wind Helper
1.237
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
23583801GRNGAP
Solar/Wind Helper
4.529
316123AC1-075 GEN
Solar/Wind Helper
1.587
3147312GRETNA
Solar/Wind Helper
0.05
237085AD2-009_GEN
Solar/Wind Helper
1.441
238126S14_GEN_1
Solar/Wind Helper
0.637
232434Z2-077 GEN
Solar/Wind Harmer
0.072
232406W1-004 FULL
Solar/Wind Harmer
1.121
232422X3-066 FULL
Solar/Wind Harmer
0.142
213815MOSER1-3
Adder
4.948
209025WIENIPP3
Adder
6.229
209142AF1-226 GEN
Solar/Wind Harmer
3.152
205941AD2-115 GEN
Solar/Wind Harmer
0.12
227287AC2-120 GEN
Solar/Wind Helper
0.514
966881AG1-559 GEN
Solar/Wind Helper
0.411
316473AC1-191 GEN
Solar/Wind Helper
1.819
3142946ENON
Solar/Wind Helper
0.098
3145336SMITFLD
Solar/Wind Helper
0.116
316017AA1-139 ULT1
Solar/Wind Helper
1.323
3146456SLIGO L269
Solar/Wind Helper
0.289
3145273HOLLAND
Solar/Wind Helper
0.215
3146376EDENTON
Solar/Wind Helper
0.285
3146206CASHIE
Solar/Wind Helper
0.281
3146173TUNIS
Solar/Wind Helper
0.28
316181AB2-040 GEN
Solar/Wind Helper
2.003
3147043LAWRENC
Solar/Wind Helper
0.167
3147133PAMPLIN
Solar/Wind Helper
0.871
316478AD1-087 GEN
Solar/Wind Helper
1.358
316499AE2-029_GEN
Solar/Wind Helper
0.922
316420AA1-050 GEN
Solar/Wind Helper
1.565
3146073TAR RVR
Solar/Wind Helper
0.272
3146083TARBORO
Solar/Wind Helper
0.272
3138543CONSLDL
Solar/Wind Helper
0.179
316095T157 G97
Solar/Wind Helper
1.23
316003AC1-222 GEN
Solar/Wind Helper
1.159
316222AC1-221 GEN
Solar/Wind Helper
1.501
316283AC2-100 C
Solar/Wind Helper
1.398
238109AE1-109 GEN2
Solar/Wind Helper
0.095
23777801MSM_W1-116
Solar/Wind Helper
0.107
943811AF1-049 GEN
Solar/Wind Helper
1.491
270336AE1-100 GEN
Solar/Wind Helper
1.038
238120AE2-309 GEN
Solar/Wind Helper
0.408
238185AF2-356 C
Solar/Wind Helper
1.926
200034PCHBTM 2
50/50
32.749
200205Y1-065-CTG2
50/50
6.424
228251CARLLS#4
Adder
0.928
213589EDDYSTN4
Adder
113.222
213535CROYDN11
Adder
14.321
20636128O CRK C2
Adder
8.918
20628028LAKEHURS
Adder
1.308
20635128RRCT3&4
Adder
15.017
20635128RRCT3&4
Adder
13.099
218419LINDEN_G6
Adder
22.846
219035LINDEN_G8
Adder
21.855
972237AH1-703 GEN
Adder
13.326
20465127PORT CT
Adder
5.04
20465527S.RDG CT
Adder
2.578
223401AF1-299 GEN
Solar/Wind Helper
0.532
316450AC1-158 RIC
Solar/Wind Helper
0.459
966001AG1-469 GEN
Solar/Wind Helper
0.321
316487AF1-042 GEN
Solar/Wind Helper
0.3
316033AB2-134 GEN
Solar/Wind Helper
1.012
3145506HICKORY
Solar/Wind Helper
1.156
3145506HICKORY
Solar/Wind Helper
0.694
3145506HICKORY
Solar/Wind Helper
0.173
316339AD2-160 GEN
Solar/Wind Helper
1.103
316388AE2-253 GEN
Solar/Wind Helper
1.103
3137176SLIGO L2192
Solar/Wind Helper
1.148
3130086AYDLETT
Solar/Wind Helper
1.154
238148AE2-230_GEN2
Solar/Wind Helper
0.496
3146626S HERTFORD
Solar/Wind Helper
0.286
3146626S HERTFORD
Solar/Wind Helper
0.286
313506AB2-031 GEN
Solar/Wind Helper
1.268
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.167
3145593CAROLNA
Solar/Wind Helper
0.278
3145593CAROLNA
Solar/Wind Helper
0.278
3132123MT JACKSON
Solar/Wind Helper
0.865
3145933PARMELE
Solar/Wind Helper
0.55
3145933PARMELE
Solar/Wind Helper
0.275
316049AB1-081 GEN
Solar/Wind Helper
1.653
235062AE1-101 C1
Solar/Wind Helper
1.427
237006AB1-125 GEN
Solar/Wind Helper
0.108
238117U2-030
Solar/Wind Helper
0.261
232926CRISFLD1
Adder
3.408
231940T-011
Adder
1.295
234041AC1-190 GEN
Solar/Wind Harmer
12.629
228201CARL#2CT
Adder
10.115
228200CARL#1CT
Adder
9.62
213815MOSER1-3
Adder
4.948
213815MOSER1-3
Adder
4.948
20714828MDF_W3-079
Solar/Wind Harmer
0.134
972260AH1-715 GEN1
Adder
18.294
972261AH1-715 GEN2
Adder
21.223
970761AG2-481 GEN
Solar/Wind Harmer
0.858
315976AC1-164 GENA
Solar/Wind Helper
3.808
316169AC1-164_GENC
Solar/Wind Helper
3.29
3142946ENON
Solar/Wind Helper
0.03
316294AC1-161 GEN
Solar/Wind Helper
5.319
316349AD2-085 GEN
Solar/Wind Helper
1.323
3146386ELIZ CT
Solar/Wind Helper
0.288
238147AE2-230_GEN1
Solar/Wind Helper
0.496
316431W1029_GEN1
Solar/Wind Helper
1.16
316433W1029_GEN2
Solar/Wind Helper
1.16
316365GEN2_N
Solar/Wind Helper
1.072
3146173TUNIS
Solar/Wind Helper
0.28
3146173TUNIS
Solar/Wind Helper
0.28
3147133PAMPLIN
Solar/Wind Helper
0.277
3147133PAMPLIN
Solar/Wind Helper
0.222
3146843MT LREL
Solar/Wind Helper
0.271
3146843MT LREL
Solar/Wind Helper
0.271
316097T157 G90
Solar/Wind Helper
1.23
237080AD1-060 GEN
Solar/Wind Helper
0.314
270214AC2-123 GEN
Solar/Wind Helper
0.81
233973AC2-185 C
Solar/Wind Harmer
3.14
970695AG2-447 GEN
Solar/Wind Harmer
4.351
233987AB2-037 GEN
Solar/Wind Harmer
-0.002
232907VN8
Adder
52.124
233935AB2-179 C
Solar/Wind Harmer
2.284
219221BRL12CT1
Adder
12.509
219223BRL12CT3
Adder
12.509
20636028O CRK C1
Adder
9.781
971667AH1-334 GEN
Solar/Wind Harmer
2.444
20635828PARLN1&2
Adder
4.503
207442AE1-156 GEN
Solar/Wind Harmer
0.078
971007AG2-625 GEN
Solar/Wind Harmer
2.113
20466127PORT 5CT
Adder
33.551
3132273ORANGE
Solar/Wind Helper
0.061
316223AC1-118
Solar/Wind Helper
0.461
3144536CHRHLND
Solar/Wind Helper
0.044
3142956BIRDNECK
Solar/Wind Helper
0.195
316305AF2-043 C
Solar/Wind Helper
0.389
316320Y1-086
Solar/Wind Helper
0.129
23546401DTGZ2-030
Solar/Wind Helper
0.09
3146516WINFALL
Solar/Wind Helper
0.287
315735AD1-075 GEN1
Solar/Wind Helper
1.612
3145893MURPHYS
Solar/Wind Helper
0.101
3145893MURPHYS
Solar/Wind Helper
0.281
3146776BUCKING
Solar/Wind Helper
0.101
3146263WOODLND
Solar/Wind Helper
0.279
3145963POPLR C
Solar/Wind Helper
0.278
316011AB1-132 GEN
Solar/Wind Helper
2.997
270494AE1-108_GEN
Solar/Wind Helper
3.637
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.271
237038AE2-054 C
Solar/Wind Helper
0.244
270173AC1-122 GEN
Solar/Wind Helper
1.673
200195DELTA ST
50/50
4.851
232920IR10
Adder
5.49
232913OH NUG2
Adder
15.134
231906DC3 NUG
Adder
23.943
231907DC10
Adder
5.977
970597AG2-380 GEN
Solar/Wind Harmer
7.124
972141AH1-641 GEN
Solar/Wind Harmer
2.29
213611FALLS1-3
Adder
4.905
213611FALLS1-3
Adder
4.905
207507AE2-000G3
Solar/Wind Harmer
17.499
971521AH1-258 GEN
Solar/Wind Harmer
2.369
217086KRNY_131
Adder
12.136
203926AA2-133 GEN
Adder
2.288
226929AD2-058 GEN
Solar/Wind Helper
0.145
3138216PACIFIC
Solar/Wind Helper
0.054
316164AC1-076 GEN
Solar/Wind Helper
1.471
3141813NORNECK
Solar/Wind Helper
0.299
957601AF2-054 GEN
Solar/Wind Helper
0.396
316233AE1-074 FULL
Solar/Wind Helper
0.45
316018AA1-139 ULT2
Solar/Wind Helper
1.245
315800Z1-036_GEN1
Solar/Wind Helper
1.569
315732AD1-074 GEN1
Solar/Wind Helper
3.224
3145893MURPHYS
Solar/Wind Helper
0.758
3145893MURPHYS
Solar/Wind Helper
0.281
316463AE2-346 GEN
Solar/Wind Helper
0.256
3145513AHOSKIE
Solar/Wind Helper
0.125
3145513AHOSKIE
Solar/Wind Helper
0.28
3137643SOCKMAN
Solar/Wind Helper
1.111
316426AA2-053 GEN
Solar/Wind Helper
1.59
316174AB2-169 GEN
Solar/Wind Helper
0.71
3144303KENBRDG
Solar/Wind Helper
0.221
316327AA2-057 GEN
Solar/Wind Helper
1.561
270457AD2-023 GEN
Solar/Wind Helper
0.981
23779801AA1-109
Solar/Wind Helper
0.184
238118U2-030_1
Solar/Wind Helper
0.261
200194DELTA CT3
50/50
3.14
233970AC1-092 C
Solar/Wind Harmer
3.14
232900DEMECSMY
Adder
16.028
232404W1-003 C
Solar/Wind Harmer
1.121
232919VN10
Adder
4.869
231917EM10
Adder
3.862
970997AG2-616 GEN
Solar/Wind Harmer
10.584
213497CHSTR7-9
Adder
3.881
213497CHSTR7-9
Adder
3.881
213560DLW11-12
Adder
3.815
219222BRL12CT2
Adder
12.509
217121ECCF
Adder
0.572
971519AH1-257 GEN
Solar/Wind Harmer
2.071
20465127PORT CT
Adder
3.798
209018SUNBIPCT
Adder
8.01
20465527S.RDG CT
Adder
2.665
941421AE2-139 GEN
Solar/Wind Harmer
0
316044AC1-158 PL1
Solar/Wind Helper
1.721
3147666LOUISA
Solar/Wind Helper
1.209
316404AE1-155 C
Solar/Wind Helper
2.549
3138133OCRAN
Solar/Wind Helper
0.178
315662AE1-191 GEN
Solar/Wind Helper
1.593
316280AD1-041 GEN
Solar/Wind Helper
0.995
3142543TWELFTH
Solar/Wind Helper
0.028
3143226MDLTHAN
Solar/Wind Helper
0.294
316369SG1_INVT
Solar/Wind Helper
1.409
316381AD1-082 GEN
Solar/Wind Helper
1.505
319010AE1-072 C
Solar/Wind Helper
3.303
238152AF2-075_GEN
Solar/Wind Helper
0.709
315611Z1-036_GEN2
Solar/Wind Helper
1.569
3130156CHOWAN
Solar/Wind Helper
0.285
315816AE2-034 GEN
Solar/Wind Helper
1.297
315737AD1-076 GEN
Solar/Wind Helper
2.757
3146926FARMVIL
Solar/Wind Helper
0.168
316087AB2-174 GEN
Solar/Wind Helper
1.954
23777901MDS_W4-102
Solar/Wind Helper
0.174
315785AD2-033 C
Solar/Wind Helper
3.221
3146233WITAKRS
Solar/Wind Helper
1.082
270018AE2-047 C O1
Solar/Wind Helper
0.867
958121AF2-106 GEN
Solar/Wind Helper
1.717
238127S14_GEN_2
Solar/Wind Helper
0.637
200202DELTA2 ST
50/50
9.516
200052ROCKSP 1
50/50
4.042
200053ROCKSP 2
50/50
3.962
213942SCHUYLKILL
Adder
5.013
213942SCHUYLKILL
Adder
3.833
213957STHWK3-4
Adder
3.833
213957STHWK3-4
Adder
3.833
213561DLWR9-10
Adder
4.989
213561DLWR9-10
Adder
3.815
963401AG1-189 GEN
Solar/Wind Harmer
1.552
971189AH1-054 GEN
Solar/Wind Harmer
1.052
209027LOR2_Q27
Solar/Wind Harmer
0
208862AG1-362 C
Solar/Wind Harmer
0.524
20390726Y2-042
Adder
2.94
3141426STAFORD
Solar/Wind Helper
0.07
316468AD1-105 GEN
Solar/Wind Helper
1.451
3141913WHIT STONE
Solar/Wind Helper
0.296
957831AF2-077 GEN
Solar/Wind Helper
0.396
315697AD1-025 GEN
Solar/Wind Helper
3.342
315839AE2-212 C
Solar/Wind Helper
0.393
316316AC1-027 C
Solar/Wind Helper
0.458
316258AE1-075 C
Solar/Wind Helper
0.398
316322AB2-045
Solar/Wind Helper
0.314
3145796HORNRTN
Solar/Wind Helper
0.886
3145796HORNRTN
Solar/Wind Helper
0.111
316210AC1-098 GEN
Solar/Wind Helper
2.227
316238AB2-078_GEN
Solar/Wind Helper
0.37
316239AB2-077_GEN
Solar/Wind Helper
0.37
3145746EVERETS
Solar/Wind Helper
1.089
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3148133STUARTS
Solar/Wind Helper
0.164
3145573BETHELC
Solar/Wind Helper
0.272
3145573BETHELC
Solar/Wind Helper
0.272
232901NORTHST
Adder
14.489
234033AF1-007_GEN
Solar/Wind Harmer
23.992
232902EASTMUNI
Adder
22.492
234012AE2-112_GEN
Solar/Wind Harmer
3.978
972251AH1-710 GEN
Adder
76.361
231918WEST 1
Adder
5.542
228732V1-021 C
Adder
0.279
228400MICK 1CT
Adder
17.114
966261AG1-495 GEN
Solar/Wind Harmer
2.216
209023WIENIPP1
Adder
12.736
209025WIENIPP3
Adder
6.357
963071AG1-156 GEN
Solar/Wind Harmer
8.9
970757AG2-479 GEN
Solar/Wind Harmer
0.848
316447AC1-158 HLD
Solar/Wind Helper
3.788
316192AB2-158 GEN
Solar/Wind Helper
2.035
3142416OLDCHRC
Solar/Wind Helper
0.77
3142416OLDCHRC
Solar/Wind Helper
0.295
3141766HARMONY
Solar/Wind Helper
0.059
315975AC1-164 GENB
Solar/Wind Helper
0.113
3142433PROV 92
Solar/Wind Helper
1.18
3145336SMITFLD
Solar/Wind Helper
1.162
316375AC2-012 GEN
Solar/Wind Helper
0.763
3146456SLIGO L269
Solar/Wind Helper
0.289
3145663CRESWEL
Solar/Wind Helper
0.792
316023GEN1_S
Solar/Wind Helper
1.072
3146206CASHIE
Solar/Wind Helper
0.281
3146173TUNIS
Solar/Wind Helper
0.28
3156021HOLLOMANSOL
Solar/Wind Helper
2.134
3145683EARLEYS
Solar/Wind Helper
0.279
316131AB2-060 GEN
Solar/Wind Helper
1.679
3146083TARBORO
Solar/Wind Helper
0.272
316359AB2-059 GEN
Solar/Wind Helper
2.067
238110AE1-109 GEN3
Solar/Wind Helper
0.095
3147123OTTER R
Solar/Wind Helper
0.15
964991AG1-363 GEN
Solar/Wind Helper
3.56
235063AE1-101 C2
Solar/Wind Helper
1.427
200035PCHBTM 3
50/50
32.254
233971AC1-093 C
Solar/Wind Harmer
3.14
232918OH NUG7
Adder
15.236
232905CHERITON_25
Adder
4.261
232910NRG_G1
Adder
14.889
234014AF1-036_GEN
Solar/Wind Harmer
3.978
972233AH1-701 GEN
Adder
6.086
219304NAMERICA C
Solar/Wind Harmer
0.127
20635028RRCT1&2
Adder
15.557
218418LINDEN_G5
Adder
22.846
219036LINDEN_G7
Adder
22.171
217086KRNY_131
Adder
12.266
316006AB2-029 C
Solar/Wind Helper
0.149
316045AC1-158 PL2
Solar/Wind Helper
5.508
966871AG1-558 GEN
Solar/Wind Helper
0.401
315666AE1-190 GEN
Solar/Wind Helper
0.398
316156AD2-030 GEN
Solar/Wind Helper
0.447
316240AF1-291 C
Solar/Wind Helper
0.394
316313AB2-026
Solar/Wind Helper
0.442
238149AF1-291A_GEN
Solar/Wind Helper
0.142
316435W1029_GEN3
Solar/Wind Helper
1.16
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
315614AA2-178 GEN
Solar/Wind Helper
1.729
3145893MURPHYS
Solar/Wind Helper
0.403
3145893MURPHYS
Solar/Wind Helper
0.505
3146776BUCKING
Solar/Wind Helper
1.122
3146776BUCKING
Solar/Wind Helper
0.091
316140AB2-099
Solar/Wind Helper
0.107
316005AA1-067
Solar/Wind Helper
0.314
316118AC1-105 GEN
Solar/Wind Helper
1.05
235531U2-073 GEN
Solar/Wind Helper
2.561
235054AD2-180 GEN
Solar/Wind Helper
1.519
200204Y1-065-CTG1
50/50
6.424
233918AB1-142 GEN
Solar/Wind Harmer
0.434
228206SHRMN CT
Adder
24.486
213611FALLS1-3
Adder
4.905
214194N WALES4
Adder
1.176
20635828PARLN1&2
Adder
9.943
20635028RRCT1&2
Adder
15.8
218524CNTRALGAS1 C
Solar/Wind Harmer
1.021
212507AE2-042_GEN
Solar/Wind Harmer
0.669
20328326MANOR_T86
Adder
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.457
3141726DUNNSVL
Solar/Wind Helper
1.194
316132AB2-190 GEN1
Solar/Wind Helper
1.674
315773AC2-141 GEN
Solar/Wind Helper
6.258
316036AC1-147 C
Solar/Wind Helper
0.442
3146516WINFALL
Solar/Wind Helper
0.929
3146516WINFALL
Solar/Wind Helper
0.287
3145893MURPHYS
Solar/Wind Helper
1.123
3146776BUCKING
Solar/Wind Helper
0.112
315607AA1-063A GEN
Solar/Wind Helper
1.597
3146263WOODLND
Solar/Wind Helper
0.279
3145963POPLR C
Solar/Wind Helper
0.278
316494AC1-189 GEN
Solar/Wind Helper
1.666
961671AG1-007 GEN
Solar/Wind Helper
0.195
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.217
238108AE1-109 GEN1
Solar/Wind Helper
0.095
237001AB1-127_GEN
Solar/Wind Helper
0.387
200201DELTA2 CT2
50/50
5.619
232899W1-062
Adder
16.71
232410W1-006 C
Solar/Wind Harmer
1.121
233984AB2-036 GEN
Solar/Wind Harmer
12.49
233930AB2-032 GEN
Solar/Wind Harmer
1.631
228307PCLP GT
Adder
17.625
213587EDDYSTN3
Adder
113.209
217083KRNY_132
Adder
12.162
209010PEIP 1
Adder
4.134
209010PEIP 1
Adder
0.606
961541AF2-445A GEN
Solar/Wind Harmer
2.571
209130AF1-271A GEN
Solar/Wind Harmer
2.109
223402AF1-300 C
Solar/Wind Helper
0.532
316411AF1-147_GEN1
Solar/Wind Helper
1.087
316312AB1-027
Solar/Wind Helper
0.566
3143526WINTERP
Solar/Wind Helper
1.532
316185AD1-033 GEN
Solar/Wind Helper
1.364
3144356SAPONY
Solar/Wind Helper
0.513
316315AB2-025 C
Solar/Wind Helper
0.437
237061AD1-155 GEN
Solar/Wind Helper
1.789
3145796HORNRTN
Solar/Wind Helper
0.831
235020AA1-095 C
Solar/Wind Helper
0.052
316237AB2-079_GEN
Solar/Wind Helper
0.37
315687AD1-152 GEN
Solar/Wind Helper
1.474
316248AF1-058 C
Solar/Wind Helper
0.362
238221AF1-254 C O1
Solar/Wind Helper
0.259
270013AE1-250 PV
Solar/Wind Helper
0.923
200192DELTA CT1
50/50
3.14
200054ROCKSP 3
50/50
4.089
972177AH1-672 GEN
Solar/Wind Harmer
17.69
232408W1-005 C
Solar/Wind Harmer
1.121
232917OH NUG6
Adder
15.27
232915OH NUG4
Adder
15.236
213958STHWK5-6
Adder
3.833
207522AF2-254 C
Solar/Wind Harmer
1.285
972275AH1-722 GEN
Adder
41.999
207528AF2-192 GEN
Solar/Wind Harmer
0.95
217186ESSEX_G9
Adder
5.198
217083KRNY_132
Adder
12.24
208909MACR G3
Adder
200.022
209010PEIP 1
Adder
0.752
209008PAXT IPP
Adder
1.515
316415AF1-147_GEN2
Solar/Wind Helper
1.087
964211AG1-282 GEN
Solar/Wind Helper
0.402
238175AF1-290_GEN
Solar/Wind Helper
0.16
3143526WINTERP
Solar/Wind Helper
1.532
315671AE2-027_GEN
Solar/Wind Helper
2.363
316072AD1-144
Solar/Wind Helper
0.331
3145823KELFORD
Solar/Wind Helper
0.278
3145783HORNRTN
Solar/Wind Helper
0.277
3145796HORNRTN
Solar/Wind Helper
0.914
3145796HORNRTN
Solar/Wind Helper
0.277
316034AC1-036 C
Solar/Wind Helper
0.29
316129AC1-054 GEN
Solar/Wind Helper
1.366
3147983MERCK5
Solar/Wind Helper
0.11
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
270016AE1-250 BESS
Solar/Wind Helper
0.923
3147312GRETNA
Solar/Wind Helper
0.199
3146802CHATHAM
Solar/Wind Helper
0.187
233972AC1-094 C
Solar/Wind Harmer
3.14
232921TASLEY2G
Adder
8.964
213497CHSTR7-9
Adder
3.881
213560DLW11-12
Adder
3.815
20635928PARLN3&4
Adder
4.503
3147666LOUISA
Solar/Wind Helper
0.695
3141906WESTMOR
Solar/Wind Helper
0.121
316458AB2-190 GEN2
Solar/Wind Helper
1.674
3144873MCLAUGH
Solar/Wind Helper
0.007
316246AF1-032 C
Solar/Wind Helper
0.33
316321Z2-027
Solar/Wind Helper
0.439
3146626S HERTFORD
Solar/Wind Helper
0.286
3146926FARMVIL
Solar/Wind Helper
0.168
3142666NORTHAMPTON
Solar/Wind Helper
0.278
316190AA2-174 GEN
Solar/Wind Helper
0.019
3145933PARMELE
Solar/Wind Helper
0.275
3148013FISHERV
Solar/Wind Helper
0.274
3146233WITAKRS
Solar/Wind Helper
0.292
3146233WITAKRS
Solar/Wind Helper
0.185
316197AC1-042 GEN
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.397
237002AB1-128_GEN
Solar/Wind Helper
0.39
G-007ALTFEXP_G-007A->PJM
CMTX
68.711
CBM NorthLTFEXP_CBM-N->PJM
CBM
95.196
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.228
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.29
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.521
VTFLTFEXP_VFT->PJM
CMTX
178.78
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.831
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
24.651

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P4_PEACH035_SRT-A/* $ CHESCO $ PECO_P4_PEACH035 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.7 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4876.15
MW Contribution:
11.26
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
233921W3-032A-STG1
50/50
2.57
234034AF2-060
50/50
3.473
233900O-025 C
50/50
0.127
232434Z2-077 GEN
Solar/Wind Harmer
0.463
232406W1-004 FULL
Solar/Wind Harmer
1.852
233964AF2-378 GEN
Solar/Wind Harmer
0.236
232422X3-066 FULL
Solar/Wind Harmer
0.454
230415AB2-049 C
Solar/Wind Harmer
0.271
219291REEVESSOUT C
Solar/Wind Harmer
0.082
219236SOUTHERNHQ C
Solar/Wind Harmer
0.09
213815MOSER1-3
Adder
4.592
20714928UPF_X1-085
Solar/Wind Harmer
0.515
219114HARTZY_C
Solar/Wind Harmer
1.048
219918AC2-009 C
Solar/Wind Harmer
0.031
20674528F3S_W2-016
Solar/Wind Harmer
1.531
209025WIENIPP3
Adder
4.32
209142AF1-226 GEN
Solar/Wind Harmer
4.148
205941AD2-115 GEN
Solar/Wind Harmer
0.572
227287AC2-120 GEN
Solar/Wind Helper
0.412
231914HR8
50/50
4.087
232911NRG_G2
50/50
0.92
233973AC2-185 C
Solar/Wind Harmer
10.055
200195DELTA ST
50/50
5.846
232920IR10
50/50
6.216
232913OH NUG2
50/50
17.135
233901CHERRYDALE C
Solar/Wind Harmer
2.084
970597AG2-380 GEN
Solar/Wind Harmer
7.573
231906DC3 NUG
Adder
25.408
231907DC10
Adder
6.343
200035PCHBTM 3
50/50
39.25
232918OH NUG7
50/50
17.251
232905CHERITON_25
50/50
4.824
232910NRG_G1
50/50
16.819
233971AC1-093 C
Solar/Wind Harmer
4.726
233994AC2-023 GEN
Solar/Wind Harmer
4.971
234036AF2-325 C
Solar/Wind Harmer
1.694
234014AF1-036_GEN
Solar/Wind Harmer
4.923
232436AB1-176 C
Solar/Wind Harmer
0.416
972233AH1-701 GEN
Adder
5.906
219912AD2-042 GEN
Solar/Wind Harmer
1.075
219607WPEMNERT C
Solar/Wind Harmer
0.551
219304NAMERICA C
Solar/Wind Harmer
0.408
20635028RRCT1&2
Adder
13.611
218418LINDEN_G5
Adder
19.68
219036LINDEN_G7
Adder
18.97
217086KRNY_131
Adder
10.36
232926CRISFLD1
50/50
3.859
231940T-011
50/50
1.466
234041AC1-190 GEN
Solar/Wind Harmer
16.548
228201CARL#2CT
Adder
9.961
228200CARL#1CT
Adder
9.473
219904AC1-010 C
Solar/Wind Harmer
0.514
219906AC1-017 C
Solar/Wind Harmer
0.295
213815MOSER1-3
Adder
4.592
213815MOSER1-3
Adder
4.592
20720828JCB_W4-025
Solar/Wind Harmer
0.583
20714828MDF_W3-079
Solar/Wind Harmer
0.38
219817TRENTONSOL C
Solar/Wind Harmer
1.35
20641628MLH_W1-032
Solar/Wind Harmer
0.358
20742028HF_AC1-207
Solar/Wind Harmer
0.951
218438BLK ROCK C
Solar/Wind Harmer
0.163
972260AH1-715 GEN1
Adder
15.759
972261AH1-715 GEN2
Adder
18.159
217202FBANKSOLAR C
Solar/Wind Harmer
0.082
217201HACKENSOLA C
Solar/Wind Harmer
0.082
217206BARNGR HS C
Solar/Wind Harmer
0.034
217204WCALDSOLAR C
Solar/Wind Harmer
0.081
20674828DL_W4-046
Solar/Wind Harmer
0.652
20634528N27_Y2-018
Solar/Wind Harmer
0.269
315976AC1-164 GENA
Solar/Wind Helper
3.015
316169AC1-164_GENC
Solar/Wind Helper
2.604
3142946ENON
Solar/Wind Helper
0.023
316294AC1-161 GEN
Solar/Wind Helper
4.232
316349AD2-085 GEN
Solar/Wind Helper
1.055
3146386ELIZ CT
Solar/Wind Helper
0.23
316431W1029_GEN1
Solar/Wind Helper
0.926
316433W1029_GEN2
Solar/Wind Helper
0.926
232901NORTHST
50/50
16.404
234033AF1-007_GEN
Solar/Wind Harmer
68.948
233996TM1833_GEN
Solar/Wind Harmer
1.847
232426Y1-080 FULL
Solar/Wind Harmer
0.353
232902EASTMUNI
Adder
23.97
234012AE2-112_GEN
Solar/Wind Harmer
4.184
972251AH1-710 GEN
Adder
79.924
232904IR4
50/50
159.039
232432Z2-076 GEN
Solar/Wind Harmer
0.245
233968AD2-076_GEN
Solar/Wind Harmer
12.06
231919CHRIST1
Adder
7.534
231920CHRIST2
Adder
7.366
230422AE1-104_GEN1
Solar/Wind Harmer
48.602
230425AE1-104_GEN2
Solar/Wind Harmer
48.602
230430AE1-229_GEN
Solar/Wind Harmer
41.196
230407AD2-065 C
Solar/Wind Harmer
0.187
20720728JCB_W1-129
Solar/Wind Harmer
0.384
207500AE2-000G1
Solar/Wind Harmer
40.407
970025AG2-016 GEN
Solar/Wind Harmer
3.613
20714428HOW_X1-037
Solar/Wind Harmer
1.513
218449LINSOLAR C
Solar/Wind Harmer
1.141
217147KRNY_1212
Adder
9.833
217147KRNY_1212
Adder
9.658
217146KRNY_1234
Adder
9.636
217146KRNY_1234
Adder
9.57
964851AG1-348 GEN
Solar/Wind Harmer
1.366
207408W3-077 C
Solar/Wind Harmer
0.499
20462827N BANGR8
Adder
0.695
209026WIENIPP4
Adder
4.365
209054AE2-059 GEN
Solar/Wind Harmer
1.141
315651AD1-115 GEN
Solar/Wind Helper
0.807
3141783LANCAST
Solar/Wind Helper
0.141
3141783LANCAST
Solar/Wind Helper
0.094
316059AD1-063 C
Solar/Wind Helper
0.236
238169AE2-226 GEN1
Solar/Wind Helper
0.562
238170AE2-226 GEN2
Solar/Wind Helper
0.562
313526AB2-022
Solar/Wind Helper
0.351
3146206CASHIE
Solar/Wind Helper
0.226
961941AG1-037 GEN
Solar/Wind Helper
0.076
3146043SEABORD
Solar/Wind Helper
0.225
3145683EARLEYS
Solar/Wind Helper
0.45
3145683EARLEYS
Solar/Wind Helper
0.225
3145683EARLEYS
Solar/Wind Helper
0.225
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.006
316486AD2-202 GEN
Solar/Wind Helper
0.321
316274AC1-208 GEN
Solar/Wind Helper
1.36
200204Y1-065-CTG1
50/50
7.611
233920W3-032A-CTG1
50/50
3.977
233918AB1-142 GEN
Solar/Wind Harmer
1.788
228206SHRMN CT
Adder
24.208
228260V4-054C
Solar/Wind Harmer
1.487
228729W2-030 C
Solar/Wind Harmer
0.825
219686LUMSOLAR_N C
Solar/Wind Harmer
0.276
219348LDSOLAR C
Solar/Wind Harmer
0.787
213611FALLS1-3
Adder
4.544
214194N WALES4
Adder
1.078
20720428HOL_W1-112
Solar/Wind Harmer
0.417
20635828PARLN1&2
Adder
8.735
20635028RRCT1&2
Adder
13.824
218524CNTRALGAS1 C
Solar/Wind Harmer
0.429
217209CENTRL HS C
Solar/Wind Harmer
0.05
20671828STAW2-080
Solar/Wind Harmer
0.116
207439AE1-081 C O1
Solar/Wind Harmer
0.062
207530AG1-191 GEN
Solar/Wind Harmer
1.422
211065PSPA IPP
Solar/Wind Harmer
0.407
961301AF2-421 GEN
Solar/Wind Harmer
0.819
963151AG1-164 GEN
Solar/Wind Harmer
0.819
961341AF2-425 GEN
Solar/Wind Harmer
0.719
212507AE2-042_GEN
Solar/Wind Harmer
2.023
316337AD2-073 GEN
Solar/Wind Helper
0.36
3141726DUNNSVL
Solar/Wind Helper
0.942
316132AB2-190 GEN1
Solar/Wind Helper
1.329
315773AC2-141 GEN
Solar/Wind Helper
4.98
316036AC1-147 C
Solar/Wind Helper
0.352
3146516WINFALL
Solar/Wind Helper
0.742
3146516WINFALL
Solar/Wind Helper
0.229
3145893MURPHYS
Solar/Wind Helper
0.903
3146776BUCKING
Solar/Wind Helper
0.09
315607AA1-063A GEN
Solar/Wind Helper
1.287
3146263WOODLND
Solar/Wind Helper
0.225
3145963POPLR C
Solar/Wind Helper
0.224
970695AG2-447 GEN
Solar/Wind Harmer
6.652
233987AB2-037 GEN
Solar/Wind Harmer
21.095
233923SMA
Solar/Wind Harmer
6.771
233997TMININ_4.2
Solar/Wind Harmer
1.847
232907VN8
Adder
55.622
232417X3-008 C
Solar/Wind Harmer
2.078
233935AB2-179 C
Solar/Wind Harmer
4.378
219221BRL12CT1
Adder
11.738
219223BRL12CT3
Adder
11.738
20715728PEM_W1-119
Solar/Wind Harmer
0.685
959561AF2-247 GEN
Solar/Wind Harmer
0.623
20636028O CRK C1
Adder
9.066
971667AH1-334 GEN
Solar/Wind Harmer
3.476
219727YARDVSOLFA C
Solar/Wind Harmer
1.137
20635828PARLN1&2
Adder
3.957
219249CENTRALDIV C
Solar/Wind Harmer
0.046
207442AE1-156 GEN
Solar/Wind Harmer
0.839
217211CAMDEN ST C
Solar/Wind Harmer
0.027
217194REDH C
Solar/Wind Harmer
0.547
207511W3-106 GEN
Solar/Wind Harmer
0.343
971007AG2-625 GEN
Solar/Wind Harmer
2.565
20466127PORT 5CT
Adder
25.97
20674128FR_U2-059
Solar/Wind Harmer
0.179
211065PSPA IPP
Solar/Wind Harmer
0.407
957921AF2-086 GEN
Solar/Wind Harmer
0.697
316223AC1-118
Solar/Wind Helper
0.363
3132273ORANGE
Solar/Wind Helper
0.047
3144536CHRHLND
Solar/Wind Helper
0.035
3142956BIRDNECK
Solar/Wind Helper
0.155
316305AF2-043 C
Solar/Wind Helper
0.31
316320Y1-086
Solar/Wind Helper
0.103
3146516WINFALL
Solar/Wind Helper
0.229
23546401DTGZ2-030
Solar/Wind Helper
0.071
315735AD1-075 GEN1
Solar/Wind Helper
1.296
3145893MURPHYS
Solar/Wind Helper
0.081
3145893MURPHYS
Solar/Wind Helper
0.226
3146776BUCKING
Solar/Wind Helper
0.081
3146263WOODLND
Solar/Wind Helper
0.225
3145963POPLR C
Solar/Wind Helper
0.224
316011AB1-132 GEN
Solar/Wind Helper
2.418
200202DELTA2 ST
50/50
11.469
200052ROCKSP 1
50/50
4.788
200053ROCKSP 2
50/50
4.695
232616GEN FOOD
50/50
0.321
233940AF2-379 C
Solar/Wind Harmer
0.345
230434AG1-499 GEN
Solar/Wind Harmer
0.823
219258KINSLEYDEP C
Solar/Wind Harmer
0.443
200201DELTA2 CT2
50/50
6.772
232899W1-062
50/50
18.906
232410W1-006 C
Solar/Wind Harmer
1.852
233946AB2-136 GEN
Solar/Wind Harmer
7.373
233952AC2-187 GEN
Solar/Wind Harmer
2.078
233954AC2-188 GEN
Solar/Wind Harmer
2.078
233984AB2-036 GEN
Solar/Wind Harmer
22.782
233930AB2-032 GEN
Solar/Wind Harmer
1.505
233982AB2-133 GEN
Solar/Wind Harmer
8.791
230511AF1-262
Solar/Wind Harmer
0.262
228754AB1-001 C
Solar/Wind Harmer
0.199
228307PCLP GT
Adder
17.187
219272CLEANLIGHT C
Solar/Wind Harmer
0.25
213587EDDYSTN3
Adder
107.22
217081WEATEXAS C
Solar/Wind Harmer
0.097
217083KRNY_132
Adder
10.272
207471AF2-354 C
Solar/Wind Harmer
0.515
20675928HOL_W4-097
Solar/Wind Harmer
0.128
209010PEIP 1
Adder
2.942
209010PEIP 1
Adder
0.431
961541AF2-445A GEN
Solar/Wind Harmer
2.427
961431AF2-434 GEN
Solar/Wind Harmer
0.717
209130AF1-271A GEN
Solar/Wind Harmer
1.841
223402AF1-300 C
Solar/Wind Helper
0.473
316411AF1-147_GEN1
Solar/Wind Helper
0.827
316312AB1-027
Solar/Wind Helper
0.447
3143526WINTERP
Solar/Wind Helper
1.213
316185AD1-033 GEN
Solar/Wind Helper
1.087
3144356SAPONY
Solar/Wind Helper
0.41
316315AB2-025 C
Solar/Wind Helper
0.349
237061AD1-155 GEN
Solar/Wind Helper
1.416
3145796HORNRTN
Solar/Wind Helper
0.671
200192DELTA CT1
50/50
3.784
200054ROCKSP 3
50/50
4.844
231912HR6
50/50
2.689
231913HR7
50/50
2.689
232917OH NUG6
50/50
17.289
232915OH NUG4
50/50
17.251
232408W1-005 C
Solar/Wind Harmer
1.852
972177AH1-672 GEN
Solar/Wind Harmer
24.89
233944AB2-135 GEN
Solar/Wind Harmer
9.48
219907AC1-030 C
Solar/Wind Harmer
0.186
213958STHWK5-6
Adder
3.599
20716028EGP_W2-019
Solar/Wind Harmer
0.597
207522AF2-254 C
Solar/Wind Harmer
1.846
218428ETC SOLAR C
Solar/Wind Harmer
0.041
219908AB1-139 C
Solar/Wind Harmer
0.439
972275AH1-722 GEN
Adder
36.179
20673628F1S_V4-069
Solar/Wind Harmer
0.203
207528AF2-192 GEN
Solar/Wind Harmer
1.435
213942SCHUYLKILL
Adder
4.707
213942SCHUYLKILL
Adder
3.6
213957STHWK3-4
Adder
3.599
213957STHWK3-4
Adder
3.599
213561DLWR9-10
Adder
4.673
213561DLWR9-10
Adder
3.573
219610FLORENCE C
Solar/Wind Harmer
1.821
963401AG1-189 GEN
Solar/Wind Harmer
2.905
971189AH1-054 GEN
Solar/Wind Harmer
1.501
20716228APLW2-078
Solar/Wind Harmer
1.076
20673828FLE_V3-070
Solar/Wind Harmer
0.531
20676128MHD_W3-029
Solar/Wind Harmer
0.539
209027LOR2_Q27
Solar/Wind Harmer
3.378
964051AG1-259 GEN
Solar/Wind Harmer
0.878
964061AG1-260 GEN
Solar/Wind Harmer
0.878
3141426STAFORD
Solar/Wind Helper
0.054
316468AD1-105 GEN
Solar/Wind Helper
1.142
3141913WHIT STONE
Solar/Wind Helper
0.234
957831AF2-077 GEN
Solar/Wind Helper
0.314
315697AD1-025 GEN
Solar/Wind Helper
2.655
315839AE2-212 C
Solar/Wind Helper
0.312
316316AC1-027 C
Solar/Wind Helper
0.364
316258AE1-075 C
Solar/Wind Helper
0.316
316322AB2-045
Solar/Wind Helper
0.252
3145796HORNRTN
Solar/Wind Helper
0.716
3145796HORNRTN
Solar/Wind Helper
0.089
316210AC1-098 GEN
Solar/Wind Helper
1.802
238147AE2-230_GEN1
Solar/Wind Helper
0.391
316365GEN2_N
Solar/Wind Helper
0.862
3146173TUNIS
Solar/Wind Helper
0.225
3146173TUNIS
Solar/Wind Helper
0.225
3147133PAMPLIN
Solar/Wind Helper
0.224
3147133PAMPLIN
Solar/Wind Helper
0.179
972141AH1-641 GEN
Solar/Wind Harmer
4.144
20715028HAN_X4-015
Solar/Wind Harmer
0.384
213611FALLS1-3
Adder
4.544
213611FALLS1-3
Adder
4.544
207507AE2-000G3
Solar/Wind Harmer
40.407
207445AB1-138_GEN
Solar/Wind Harmer
0.731
20720628TIN_W1-124
Solar/Wind Harmer
1.215
971521AH1-258 GEN
Solar/Wind Harmer
3.273
20675528CPH_W2-050
Solar/Wind Harmer
0.659
20676428JCR_X2-075
Solar/Wind Harmer
0.384
217086KRNY_131
Adder
10.25
20675128HRM_W1-127
Solar/Wind Harmer
0.165
209029WAYMART-WD
Solar/Wind Harmer
2.149
959421AF2-233 GEN
Solar/Wind Harmer
0.655
226929AD2-058 GEN
Solar/Wind Helper
0.116
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.145
3141813NORNECK
Solar/Wind Helper
0.236
957601AF2-054 GEN
Solar/Wind Helper
0.314
316233AE1-074 FULL
Solar/Wind Helper
0.356
316018AA1-139 ULT2
Solar/Wind Helper
0.992
315800Z1-036_GEN1
Solar/Wind Helper
1.255
315732AD1-074 GEN1
Solar/Wind Helper
2.59
3145893MURPHYS
Solar/Wind Helper
0.609
3145893MURPHYS
Solar/Wind Helper
0.226
316463AE2-346 GEN
Solar/Wind Helper
0.206
3145513AHOSKIE
Solar/Wind Helper
0.101
3145513AHOSKIE
Solar/Wind Helper
0.225
3137643SOCKMAN
Solar/Wind Helper
0.896
316426AA2-053 GEN
Solar/Wind Helper
1.283
316174AB2-169 GEN
Solar/Wind Helper
0.574
3144303KENBRDG
Solar/Wind Helper
0.178
200200DELTA2 CT1
50/50
6.772
200193DELTA CT2
50/50
3.784
200203Y1-065-STG
50/50
13.181
200055ROCKSP 4
50/50
4.76
231911HR5
50/50
2.689
232914OH NUG3
50/50
17.366
232916OH NUG5
50/50
17.366
233939AC1-091 C
Solar/Wind Harmer
4.977
233933AB2-153 GEN
Solar/Wind Harmer
2.032
219623KINSLEYBEA C
Solar/Wind Harmer
0.587
213958STHWK5-6
Adder
3.599
20716428NHV_W2-082
Solar/Wind Harmer
2.288
963391AG1-188 GEN
Solar/Wind Harmer
4.777
219612MATRIX C
Solar/Wind Harmer
0.22
20716928W4-060COL
Solar/Wind Harmer
0.849
217213AMBOY SO C
Solar/Wind Harmer
0.146
20673728F2S_V4-070
Solar/Wind Harmer
0.203
207510AF2-138 C
Solar/Wind Harmer
1.848
207437AD2-070 GEN
Solar/Wind Harmer
0.294
20671928W4-073
Solar/Wind Harmer
0.42
20465427SHAW CT
Adder
3.745
20633028GILCT9
Adder
27.292
209116AE2-175 GEN
Solar/Wind Harmer
3.818
970095AG2-074 GEN
Solar/Wind Harmer
5.165
961421AF2-433 GEN
Solar/Wind Harmer
0.717
209093AE2-110 GEN
Solar/Wind Harmer
1.791
209120AE2-241 GEN
Solar/Wind Harmer
2.37
946691AF1-333 GEN
Solar/Wind Harmer
0.66
946741AF1-338 GEN
Solar/Wind Harmer
0.66
226910AB2-157 C
Solar/Wind Helper
0.017
3141196NOKESVL
Solar/Wind Helper
0.975
316077AC2-138 C
Solar/Wind Helper
0.222
316484AD2-074 GEN
Solar/Wind Helper
0.454
316075AC2-137 C
Solar/Wind Helper
0.357
966621AG1-532 GEN
Solar/Wind Helper
0.205
942461AE2-259 GEN
Solar/Wind Helper
1.512
316317KELFORD C
Solar/Wind Helper
0.202
3145823KELFORD
Solar/Wind Helper
0.224
3145796HORNRTN
Solar/Wind Helper
0.895
3145796HORNRTN
Solar/Wind Helper
0.224
315821AE2-092 GEN
Solar/Wind Helper
2.076
316212AC1-099_GEN
Solar/Wind Helper
1.001
20674328GAR_V4-001
Solar/Wind Harmer
0.113
946751AF1-339 GEN
Solar/Wind Harmer
0.66
316006AB2-029 C
Solar/Wind Helper
0.115
316045AC1-158 PL2
Solar/Wind Helper
4.279
966871AG1-558 GEN
Solar/Wind Helper
0.317
315666AE1-190 GEN
Solar/Wind Helper
0.315
316156AD2-030 GEN
Solar/Wind Helper
0.354
316240AF1-291 C
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.351
316435W1029_GEN3
Solar/Wind Helper
0.926
3146516WINFALL
Solar/Wind Helper
0.229
3146516WINFALL
Solar/Wind Helper
0.229
3146516WINFALL
Solar/Wind Helper
0.229
315614AA2-178 GEN
Solar/Wind Helper
1.387
238149AF1-291A_GEN
Solar/Wind Helper
0.112
3145893MURPHYS
Solar/Wind Helper
0.324
3145893MURPHYS
Solar/Wind Helper
0.406
3146776BUCKING
Solar/Wind Helper
0.901
3146776BUCKING
Solar/Wind Helper
0.073
316140AB2-099
Solar/Wind Helper
0.086
200034PCHBTM 2
50/50
39.455
200205Y1-065-CTG2
50/50
7.611
234015AF2-250 C
Solar/Wind Harmer
0.223
232428Y3-058 C
Solar/Wind Harmer
1.543
232424Y1-079 C
Solar/Wind Harmer
1.027
228251CARLLS#4
Adder
0.914
230433AD2-135 GEN
Solar/Wind Harmer
0.145
228351V2-046C
Solar/Wind Harmer
2.892
219287REEVESEAST C
Solar/Wind Harmer
1.833
213589EDDYSTN4
Adder
107.242
213535CROYDN11
Adder
13.421
214067T20SOLAR
Solar/Wind Harmer
0.325
20636128O CRK C2
Adder
8.267
207459AE1-142 C O1
Solar/Wind Harmer
1.335
20628028LAKEHURS
Adder
1.2
217197RE CRAN C
Solar/Wind Harmer
0.641
924131AB2-057 GEN
Solar/Wind Harmer
1.209
20635128RRCT3&4
Adder
13.138
20635128RRCT3&4
Adder
11.461
218419LINDEN_G6
Adder
19.68
219035LINDEN_G8
Adder
18.699
20675428EAM_W2-061
Solar/Wind Harmer
0.213
972237AH1-703 GEN
Adder
11.259
20465127PORT CT
Adder
3.898
223401AF1-299 GEN
Solar/Wind Helper
0.473
316450AC1-158 RIC
Solar/Wind Helper
0.357
966001AG1-469 GEN
Solar/Wind Helper
0.252
316487AF1-042 GEN
Solar/Wind Helper
0.237
316033AB2-134 GEN
Solar/Wind Helper
0.803
3145506HICKORY
Solar/Wind Helper
0.921
3145506HICKORY
Solar/Wind Helper
0.553
3145506HICKORY
Solar/Wind Helper
0.138
316339AD2-160 GEN
Solar/Wind Helper
0.879
316388AE2-253 GEN
Solar/Wind Helper
0.879
3137176SLIGO L2192
Solar/Wind Helper
0.915
3130086AYDLETT
Solar/Wind Helper
0.92
3146626S HERTFORD
Solar/Wind Helper
0.229
3146626S HERTFORD
Solar/Wind Helper
0.229
238148AE2-230_GEN2
Solar/Wind Helper
0.391
313506AB2-031 GEN
Solar/Wind Helper
1.022
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3142666NORTHAMPTON
Solar/Wind Helper
0.224
3142666NORTHAMPTON
Solar/Wind Helper
0.135
3145593CAROLNA
Solar/Wind Helper
0.224
3145593CAROLNA
Solar/Wind Helper
0.224
3145933PARMELE
Solar/Wind Helper
0.445
3145933PARMELE
Solar/Wind Helper
0.223
200194DELTA CT3
50/50
3.784
232900DEMECSMY
50/50
18.135
233970AC1-092 C
Solar/Wind Harmer
4.977
232404W1-003 C
Solar/Wind Harmer
1.852
233998TM1NIN_3.36
Solar/Wind Harmer
1.847
232919VN10
Adder
5.194
231917EM10
Adder
3.965
970997AG2-616 GEN
Solar/Wind Harmer
13.813
213497CHSTR7-9
Adder
3.683
213497CHSTR7-9
Adder
3.683
213560DLW11-12
Adder
3.573
219222BRL12CT2
Adder
11.738
20717128DIX_Z2-102
Solar/Wind Harmer
1.696
20715828PEM_W1-120
Solar/Wind Harmer
0.685
963711AG1-223 GEN
Solar/Wind Harmer
1.842
219276PARKLANDSO C
Solar/Wind Harmer
0.569
20715228NPK_W1-113
Solar/Wind Harmer
0.524
20720528MAN_W1-024
Solar/Wind Harmer
0.309
219919AE1-041 FULL
Solar/Wind Harmer
0.047
217121ECCF
Adder
0.483
20676728BRNX1-095
Solar/Wind Harmer
0.19
20676328BVR_Y1-020
Solar/Wind Harmer
0.345
20674928WA_W3-044
Solar/Wind Harmer
0.485
971519AH1-257 GEN
Solar/Wind Harmer
2.51
207518AF1-320_GEN
Solar/Wind Harmer
3.599
20465127PORT CT
Adder
2.937
209018SUNBIPCT
Adder
4.879
316044AC1-158 PL1
Solar/Wind Helper
1.337
3147666LOUISA
Solar/Wind Helper
0.947
316404AE1-155 C
Solar/Wind Helper
2.013
3138133OCRAN
Solar/Wind Helper
0.14
315662AE1-191 GEN
Solar/Wind Helper
1.261
316280AD1-041 GEN
Solar/Wind Helper
0.788
3142543TWELFTH
Solar/Wind Helper
0.022
3143226MDLTHAN
Solar/Wind Helper
0.233
316369SG1_INVT
Solar/Wind Helper
1.119
316381AD1-082 GEN
Solar/Wind Helper
1.198
319010AE1-072 C
Solar/Wind Helper
2.633
315611Z1-036_GEN2
Solar/Wind Helper
1.255
3130156CHOWAN
Solar/Wind Helper
0.228
315816AE2-034 GEN
Solar/Wind Helper
1.04
238152AF2-075_GEN
Solar/Wind Helper
0.559
315737AD1-076 GEN
Solar/Wind Helper
2.215
3146926FARMVIL
Solar/Wind Helper
0.135
316087AB2-174 GEN
Solar/Wind Helper
1.575
315785AD2-033 C
Solar/Wind Helper
2.605
23777901MDS_W4-102
Solar/Wind Helper
0.14
231918WEST 1
Adder
5.736
228732V1-021 C
Adder
0.275
228400MICK 1CT
Adder
16.591
219766PARADISE C
Solar/Wind Harmer
0.428
20714528FRN_Y2-051
Solar/Wind Harmer
0.367
219680HOPEWELLV C1
Solar/Wind Harmer
0.092
218440SUMMTASSOC C
Solar/Wind Harmer
0.148
217208PARK ELE C
Solar/Wind Harmer
0.028
966261AG1-495 GEN
Solar/Wind Harmer
3.703
20674628WNG_W3-110
Solar/Wind Harmer
0.419
963071AG1-156 GEN
Solar/Wind Harmer
8.156
209023WIENIPP1
Adder
8.833
209025WIENIPP3
Adder
4.409
316447AC1-158 HLD
Solar/Wind Helper
2.942
316192AB2-158 GEN
Solar/Wind Helper
1.594
3142416OLDCHRC
Solar/Wind Helper
0.609
3142416OLDCHRC
Solar/Wind Helper
0.233
3141766HARMONY
Solar/Wind Helper
0.047
3142433PROV 92
Solar/Wind Helper
0.934
315975AC1-164 GENB
Solar/Wind Helper
0.089
3145336SMITFLD
Solar/Wind Helper
0.924
316375AC2-012 GEN
Solar/Wind Helper
0.607
3146456SLIGO L269
Solar/Wind Helper
0.23
3145663CRESWEL
Solar/Wind Helper
0.636
316023GEN1_S
Solar/Wind Helper
0.862
3146206CASHIE
Solar/Wind Helper
0.226
3146173TUNIS
Solar/Wind Helper
0.225
3156021HOLLOMANSOL
Solar/Wind Helper
1.719
3145683EARLEYS
Solar/Wind Helper
0.225
217186ESSEX_G9
Adder
4.391
217083KRNY_132
Adder
10.338
20676228FRD_X1-012
Solar/Wind Harmer
0.613
20675828AU_W4-064
Solar/Wind Harmer
0.178
20675728RH_W2-091
Solar/Wind Harmer
0.595
207484AF2-139 C O1
Solar/Wind Harmer
0.495
208909MACR G3
Adder
151.771
209010PEIP 1
Adder
0.535
946731AF1-337 GEN
Solar/Wind Harmer
0.66
316415AF1-147_GEN2
Solar/Wind Helper
0.827
964211AG1-282 GEN
Solar/Wind Helper
0.318
3143526WINTERP
Solar/Wind Helper
1.213
315671AE2-027_GEN
Solar/Wind Helper
1.876
238175AF1-290_GEN
Solar/Wind Helper
0.124
316072AD1-144
Solar/Wind Helper
0.264
3145823KELFORD
Solar/Wind Helper
0.224
3145783HORNRTN
Solar/Wind Helper
0.224
3145796HORNRTN
Solar/Wind Helper
0.738
3145796HORNRTN
Solar/Wind Helper
0.224
316034AC1-036 C
Solar/Wind Helper
0.234
316129AC1-054 GEN
Solar/Wind Helper
1.106
232921TASLEY2G
50/50
10.15
233972AC1-094 C
Solar/Wind Harmer
3.997
233950AC2-186 GEN
Solar/Wind Harmer
1.039
228711V2-041C
Solar/Wind Harmer
0.878
218660EHAMPSOLAR C
Solar/Wind Harmer
0.239
219921AF1-264
Solar/Wind Harmer
0.197
219688LUMSOLAR_S C
Solar/Wind Harmer
0.275
213497CHSTR7-9
Adder
3.683
219914AD2-027 C
Solar/Wind Harmer
0.81
213560DLW11-12
Adder
3.573
207454AA2-184 E
Solar/Wind Harmer
1.219
20635928PARLN3&4
Adder
3.957
217169METRODIV C
Solar/Wind Harmer
0.044
963161AG1-165 GEN
Solar/Wind Harmer
0.819
208972BECR K09
Solar/Wind Harmer
0.853
961331AF2-424 GEN
Solar/Wind Harmer
0.719
209071AE2-133 GEN
Solar/Wind Harmer
1.108
3141906WESTMOR
Solar/Wind Helper
0.095
3147666LOUISA
Solar/Wind Helper
0.545
316458AB2-190 GEN2
Solar/Wind Helper
1.329
3144873MCLAUGH
Solar/Wind Helper
0.006
316246AF1-032 C
Solar/Wind Helper
0.263
316321Z2-027
Solar/Wind Helper
0.35
3146626S HERTFORD
Solar/Wind Helper
0.229
3146926FARMVIL
Solar/Wind Helper
0.135
3142666NORTHAMPTON
Solar/Wind Helper
0.224
316190AA2-174 GEN
Solar/Wind Helper
0.015
3145933PARMELE
Solar/Wind Helper
0.223
232912OH NUG1
50/50
17.366
971195AH1-057 GEN
Solar/Wind Harmer
1.806
233955AB2-172 GEN
Solar/Wind Harmer
9.235
232813VAUGHN
Adder
1.083
231902DC CT7
Adder
20.312
233915AB1-141 GEN
Solar/Wind Harmer
1.788
970453AG2-297 GEN
Solar/Wind Harmer
4.055
964001AG1-254 GEN
Solar/Wind Harmer
10.469
228728W1-130C
Solar/Wind Harmer
0.95
227927V4-067C
Solar/Wind Harmer
0.283
219137THOSOLAR C
Solar/Wind Harmer
1.669
219615MILLCREEK C
Solar/Wind Harmer
0.316
219224BRL12CT4
Adder
11.738
207487AE2-000G4
Solar/Wind Harmer
40.407
207497AE2-000G2
Solar/Wind Harmer
40.407
219620RIDERU C
Solar/Wind Harmer
0.068
20635928PARLN3&4
Adder
8.735
218526CNTRALGAS2 C
Solar/Wind Harmer
0.431
217167KRNY_14
Adder
10.338
971009AG2-626 GEN
Solar/Wind Harmer
1.636
961261AF2-417 GEN
Solar/Wind Harmer
0.872
212266LOR1
Solar/Wind Harmer
0.895
959431AF2-234 GEN
Solar/Wind Harmer
1.31
3138133OCRAN
Solar/Wind Helper
0.07
3141873WAN 176
Solar/Wind Helper
0.047
3143873LANEXA
Solar/Wind Helper
0.14
316382AG1-145 C
Solar/Wind Helper
0.313
316159AE1-175 C
Solar/Wind Helper
0.353
316236AE1-162_GEN
Solar/Wind Helper
0.311
3143316POE
Solar/Wind Helper
0.914
316405AF2-144 C
Solar/Wind Helper
0.264
3146486SUNBURY
Solar/Wind Helper
0.229
3146486SUNBURY
Solar/Wind Helper
0.229
3145176PASQUOTANK
Solar/Wind Helper
0.142
3130156CHOWAN
Solar/Wind Helper
0.228
3130156CHOWAN
Solar/Wind Helper
0.228
3130546PLYMOUTH
Solar/Wind Helper
0.226
315733AD1-074 GEN2
Solar/Wind Helper
2.59
946281AF1-292 GEN
Solar/Wind Helper
0.226
3146033SCOT NK
Solar/Wind Helper
0.894
966881AG1-559 GEN
Solar/Wind Helper
0.323
316473AC1-191 GEN
Solar/Wind Helper
1.437
3142946ENON
Solar/Wind Helper
0.078
3145336SMITFLD
Solar/Wind Helper
0.092
316017AA1-139 ULT1
Solar/Wind Helper
1.054
3146456SLIGO L269
Solar/Wind Helper
0.23
3145273HOLLAND
Solar/Wind Helper
0.172
3146376EDENTON
Solar/Wind Helper
0.228
3146206CASHIE
Solar/Wind Helper
0.226
3146173TUNIS
Solar/Wind Helper
0.225
316181AB2-040 GEN
Solar/Wind Helper
1.615
3147043LAWRENC
Solar/Wind Helper
0.134
3147133PAMPLIN
Solar/Wind Helper
0.703
316478AD1-087 GEN
Solar/Wind Helper
1.097
G-007ALTFEXP_G-007A->PJM
CMTX
60.116
CBM NorthLTFEXP_CBM-N->PJM
CBM
74.656
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.686
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.598
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.447
VTFLTFEXP_VFT->PJM
CMTX
151.705
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.236
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.958

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.49 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4579.06
MW Contribution:
11.48
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232912OH NUG1
Adder
16.488
971195AH1-057 GEN
Solar/Wind Harmer
1.166
232813VAUGHN
Adder
1.092
231902DC CT7
Adder
20.555
233915AB1-141 GEN
Solar/Wind Harmer
0.466
970453AG2-297 GEN
Solar/Wind Harmer
3.805
964001AG1-254 GEN
Solar/Wind Harmer
8.287
219224BRL12CT4
Adder
12.079
207487AE2-000G4
Solar/Wind Harmer
16.538
207497AE2-000G2
Solar/Wind Harmer
16.538
20635928PARLN3&4
Adder
8.909
218526CNTRALGAS2 C
Solar/Wind Harmer
0.909
217167KRNY_14
Adder
10.543
971009AG2-626 GEN
Solar/Wind Harmer
1.078
3138133OCRAN
Solar/Wind Helper
0.073
3141873WAN 176
Solar/Wind Helper
0.048
3143873LANEXA
Solar/Wind Helper
0.145
316382AG1-145 C
Solar/Wind Helper
0.325
316159AE1-175 C
Solar/Wind Helper
0.367
316236AE1-162_GEN
Solar/Wind Helper
0.323
3143316POE
Solar/Wind Helper
0.949
316405AF2-144 C
Solar/Wind Helper
0.273
3146486SUNBURY
Solar/Wind Helper
0.238
3146486SUNBURY
Solar/Wind Helper
0.238
3145176PASQUOTANK
Solar/Wind Helper
0.148
3130156CHOWAN
Solar/Wind Helper
0.236
3130156CHOWAN
Solar/Wind Helper
0.236
3130546PLYMOUTH
Solar/Wind Helper
0.235
315733AD1-074 GEN2
Solar/Wind Helper
2.688
946281AF1-292 GEN
Solar/Wind Helper
0.235
3146033SCOT NK
Solar/Wind Helper
0.928
3148013FISHERV
Solar/Wind Helper
0.132
315616AA1-038_C
Solar/Wind Helper
1.022
232904IR4
Adder
150.945
232432Z2-076 GEN
Solar/Wind Harmer
0.024
233968AD2-076_GEN
Solar/Wind Harmer
4.276
231919CHRIST1
Adder
7.729
231920CHRIST2
Adder
7.557
230430AE1-229_GEN
Solar/Wind Harmer
29.168
230422AE1-104_GEN1
Solar/Wind Harmer
19.857
230425AE1-104_GEN2
Solar/Wind Harmer
19.857
207500AE2-000G1
Solar/Wind Harmer
16.538
970025AG2-016 GEN
Solar/Wind Harmer
2.381
217147KRNY_1212
Adder
10.028
217147KRNY_1212
Adder
9.849
217146KRNY_1234
Adder
9.827
217146KRNY_1234
Adder
9.76
20462827N BANGR8
Adder
0.708
209026WIENIPP4
Adder
4.439
315651AD1-115 GEN
Solar/Wind Helper
0.837
3141783LANCAST
Solar/Wind Helper
0.146
3141783LANCAST
Solar/Wind Helper
0.097
316059AD1-063 C
Solar/Wind Helper
0.245
238169AE2-226 GEN1
Solar/Wind Helper
0.583
238170AE2-226 GEN2
Solar/Wind Helper
0.583
313526AB2-022
Solar/Wind Helper
0.364
3146206CASHIE
Solar/Wind Helper
0.234
961941AG1-037 GEN
Solar/Wind Helper
0.079
3146043SEABORD
Solar/Wind Helper
0.234
3145683EARLEYS
Solar/Wind Helper
0.467
3145683EARLEYS
Solar/Wind Helper
0.233
3145683EARLEYS
Solar/Wind Helper
0.233
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.007
316486AD2-202 GEN
Solar/Wind Helper
0.333
316274AC1-208 GEN
Solar/Wind Helper
1.412
3147173SINAI
Solar/Wind Helper
0.227
3147243WELCO
Solar/Wind Helper
0.142
237030AB1-096 C
Solar/Wind Helper
0.058
237025AB1-124 C
Solar/Wind Helper
0.142
3148463FAIRFLD
Solar/Wind Helper
0.225
200200DELTA2 CT1
50/50
6.586
200193DELTA CT2
50/50
3.68
200203Y1-065-STG
50/50
12.873
200055ROCKSP 4
50/50
4.649
233939AC1-091 C
Solar/Wind Harmer
3.368
232914OH NUG3
Adder
16.488
232916OH NUG5
Adder
16.488
213958STHWK5-6
Adder
3.799
963391AG1-188 GEN
Solar/Wind Harmer
2.379
207437AD2-070 GEN
Solar/Wind Harmer
0.065
20465427SHAW CT
Adder
3.816
20633028GILCT9
Adder
27.838
970095AG2-074 GEN
Solar/Wind Harmer
4.211
209093AE2-110 GEN
Solar/Wind Harmer
1.176
209120AE2-241 GEN
Solar/Wind Harmer
1.176
226910AB2-157 C
Solar/Wind Helper
0.018
3141196NOKESVL
Solar/Wind Helper
1.011
316077AC2-138 C
Solar/Wind Helper
0.231
316484AD2-074 GEN
Solar/Wind Helper
0.471
316075AC2-137 C
Solar/Wind Helper
0.37
966621AG1-532 GEN
Solar/Wind Helper
0.212
942461AE2-259 GEN
Solar/Wind Helper
1.569
316317KELFORD C
Solar/Wind Helper
0.21
3145823KELFORD
Solar/Wind Helper
0.233
3145796HORNRTN
Solar/Wind Helper
0.929
3145796HORNRTN
Solar/Wind Helper
0.232
315821AE2-092 GEN
Solar/Wind Helper
2.155
316212AC1-099_GEN
Solar/Wind Helper
1.039
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
23583801GRNGAP
Solar/Wind Helper
3.822
232434Z2-077 GEN
Solar/Wind Harmer
0.078
232406W1-004 FULL
Solar/Wind Harmer
1.205
232422X3-066 FULL
Solar/Wind Harmer
0.153
213815MOSER1-3
Adder
4.777
209025WIENIPP3
Adder
4.394
209142AF1-226 GEN
Solar/Wind Harmer
2.058
205941AD2-115 GEN
Solar/Wind Harmer
0.073
227287AC2-120 GEN
Solar/Wind Helper
0.426
966881AG1-559 GEN
Solar/Wind Helper
0.334
316473AC1-191 GEN
Solar/Wind Helper
1.49
3142946ENON
Solar/Wind Helper
0.081
3145336SMITFLD
Solar/Wind Helper
0.096
316017AA1-139 ULT1
Solar/Wind Helper
1.094
3146456SLIGO L269
Solar/Wind Helper
0.239
3145273HOLLAND
Solar/Wind Helper
0.178
3146376EDENTON
Solar/Wind Helper
0.236
3146206CASHIE
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
316181AB2-040 GEN
Solar/Wind Helper
1.676
3147043LAWRENC
Solar/Wind Helper
0.14
3147133PAMPLIN
Solar/Wind Helper
0.729
316478AD1-087 GEN
Solar/Wind Helper
1.138
316420AA1-050 GEN
Solar/Wind Helper
1.32
23777801MSM_W1-116
Solar/Wind Helper
0.099
316499AE2-029_GEN
Solar/Wind Helper
0.773
3146073TAR RVR
Solar/Wind Helper
0.229
3146083TARBORO
Solar/Wind Helper
0.229
3138543CONSLDL
Solar/Wind Helper
0.151
316003AC1-222 GEN
Solar/Wind Helper
0.985
316095T157 G97
Solar/Wind Helper
1.031
316222AC1-221 GEN
Solar/Wind Helper
1.283
316283AC2-100 C
Solar/Wind Helper
1.196
200034PCHBTM 2
50/50
38.371
200205Y1-065-CTG2
50/50
7.433
228251CARLLS#4
Adder
0.932
213589EDDYSTN4
Adder
114.049
213535CROYDN11
Adder
13.823
20636128O CRK C2
Adder
8.428
20628028LAKEHURS
Adder
1.224
20635128RRCT3&4
Adder
13.4
20635128RRCT3&4
Adder
11.689
218419LINDEN_G6
Adder
20.077
219035LINDEN_G8
Adder
19.074
972237AH1-703 GEN
Adder
11.483
20465127PORT CT
Adder
3.973
223401AF1-299 GEN
Solar/Wind Helper
0.484
316450AC1-158 RIC
Solar/Wind Helper
0.37
966001AG1-469 GEN
Solar/Wind Helper
0.262
316487AF1-042 GEN
Solar/Wind Helper
0.246
316033AB2-134 GEN
Solar/Wind Helper
0.833
3145506HICKORY
Solar/Wind Helper
0.955
3145506HICKORY
Solar/Wind Helper
0.573
3145506HICKORY
Solar/Wind Helper
0.143
316339AD2-160 GEN
Solar/Wind Helper
0.912
316388AE2-253 GEN
Solar/Wind Helper
0.912
3137176SLIGO L2192
Solar/Wind Helper
0.95
3130086AYDLETT
Solar/Wind Helper
0.954
3146626S HERTFORD
Solar/Wind Helper
0.237
3146626S HERTFORD
Solar/Wind Helper
0.237
238148AE2-230_GEN2
Solar/Wind Helper
0.406
313506AB2-031 GEN
Solar/Wind Helper
1.061
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.14
3145593CAROLNA
Solar/Wind Helper
0.233
3145593CAROLNA
Solar/Wind Helper
0.233
3145933PARMELE
Solar/Wind Helper
0.462
3145933PARMELE
Solar/Wind Helper
0.231
3132123MT JACKSON
Solar/Wind Helper
0.721
316049AB1-081 GEN
Solar/Wind Helper
1.397
237006AB1-125 GEN
Solar/Wind Helper
0.106
232926CRISFLD1
Adder
3.664
231940T-011
Adder
1.392
234041AC1-190 GEN
Solar/Wind Harmer
13.58
228201CARL#2CT
Adder
10.159
228200CARL#1CT
Adder
9.662
213815MOSER1-3
Adder
4.777
213815MOSER1-3
Adder
4.777
20714828MDF_W3-079
Solar/Wind Harmer
0.125
972260AH1-715 GEN1
Adder
16.077
972261AH1-715 GEN2
Adder
18.523
970761AG2-481 GEN
Solar/Wind Harmer
0.54
315976AC1-164 GENA
Solar/Wind Helper
3.127
316169AC1-164_GENC
Solar/Wind Helper
2.701
3142946ENON
Solar/Wind Helper
0.024
316294AC1-161 GEN
Solar/Wind Helper
4.39
316349AD2-085 GEN
Solar/Wind Helper
1.094
3146386ELIZ CT
Solar/Wind Helper
0.238
316431W1029_GEN1
Solar/Wind Helper
0.961
316433W1029_GEN2
Solar/Wind Helper
0.961
238147AE2-230_GEN1
Solar/Wind Helper
0.406
316365GEN2_N
Solar/Wind Helper
0.895
3146173TUNIS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3147133PAMPLIN
Solar/Wind Helper
0.232
3147133PAMPLIN
Solar/Wind Helper
0.186
3146843MT LREL
Solar/Wind Helper
0.229
3146843MT LREL
Solar/Wind Helper
0.229
316097T157 G90
Solar/Wind Helper
1.031
233987AB2-037 GEN
Solar/Wind Harmer
-0.003
233973AC2-185 C
Solar/Wind Harmer
3.368
970695AG2-447 GEN
Solar/Wind Harmer
4.668
232907VN8
Adder
56.053
233935AB2-179 C
Solar/Wind Harmer
2.45
219221BRL12CT1
Adder
12.079
219223BRL12CT3
Adder
12.079
20636028O CRK C1
Adder
9.244
971667AH1-334 GEN
Solar/Wind Harmer
2.291
20635828PARLN1&2
Adder
4.035
207442AE1-156 GEN
Solar/Wind Harmer
0.068
971007AG2-625 GEN
Solar/Wind Harmer
1.69
20466127PORT 5CT
Adder
26.468
316223AC1-118
Solar/Wind Helper
0.376
3132273ORANGE
Solar/Wind Helper
0.049
3144536CHRHLND
Solar/Wind Helper
0.036
3142956BIRDNECK
Solar/Wind Helper
0.161
316305AF2-043 C
Solar/Wind Helper
0.322
316320Y1-086
Solar/Wind Helper
0.107
3146516WINFALL
Solar/Wind Helper
0.238
23546401DTGZ2-030
Solar/Wind Helper
0.074
315735AD1-075 GEN1
Solar/Wind Helper
1.344
3145893MURPHYS
Solar/Wind Helper
0.084
3145893MURPHYS
Solar/Wind Helper
0.234
3146776BUCKING
Solar/Wind Helper
0.084
3146263WOODLND
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
316011AB1-132 GEN
Solar/Wind Helper
2.51
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.229
270494AE1-108_GEN
Solar/Wind Helper
3.068
200195DELTA ST
50/50
5.685
232920IR10
Adder
5.899
232913OH NUG2
Adder
16.268
970597AG2-380 GEN
Solar/Wind Harmer
7.658
231906DC3 NUG
Adder
25.711
231907DC10
Adder
6.419
972141AH1-641 GEN
Solar/Wind Harmer
2.297
213611FALLS1-3
Adder
4.679
213611FALLS1-3
Adder
4.679
207507AE2-000G3
Solar/Wind Harmer
16.538
971521AH1-258 GEN
Solar/Wind Harmer
2.157
217086KRNY_131
Adder
10.453
226929AD2-058 GEN
Solar/Wind Helper
0.12
3138216PACIFIC
Solar/Wind Helper
0.042
316164AC1-076 GEN
Solar/Wind Helper
1.187
3141813NORNECK
Solar/Wind Helper
0.245
957601AF2-054 GEN
Solar/Wind Helper
0.325
316233AE1-074 FULL
Solar/Wind Helper
0.37
316018AA1-139 ULT2
Solar/Wind Helper
1.029
315800Z1-036_GEN1
Solar/Wind Helper
1.302
315732AD1-074 GEN1
Solar/Wind Helper
2.688
3145893MURPHYS
Solar/Wind Helper
0.632
3145893MURPHYS
Solar/Wind Helper
0.234
316463AE2-346 GEN
Solar/Wind Helper
0.214
3145513AHOSKIE
Solar/Wind Helper
0.105
3145513AHOSKIE
Solar/Wind Helper
0.234
3137643SOCKMAN
Solar/Wind Helper
0.93
316426AA2-053 GEN
Solar/Wind Helper
1.331
316174AB2-169 GEN
Solar/Wind Helper
0.595
3144303KENBRDG
Solar/Wind Helper
0.185
23779801AA1-109
Solar/Wind Helper
0.167
316327AA2-057 GEN
Solar/Wind Helper
1.316
200194DELTA CT3
50/50
3.68
233970AC1-092 C
Solar/Wind Harmer
3.368
232404W1-003 C
Solar/Wind Harmer
1.205
232919VN10
Adder
5.235
232900DEMECSMY
Adder
17.2
231917EM10
Adder
4.081
970997AG2-616 GEN
Solar/Wind Harmer
10.615
213497CHSTR7-9
Adder
3.913
213497CHSTR7-9
Adder
3.913
213560DLW11-12
Adder
3.738
219222BRL12CT2
Adder
12.079
217121ECCF
Adder
0.493
971519AH1-257 GEN
Solar/Wind Harmer
1.654
20465127PORT CT
Adder
2.994
209018SUNBIPCT
Adder
4.951
316044AC1-158 PL1
Solar/Wind Helper
1.386
3147666LOUISA
Solar/Wind Helper
0.982
316404AE1-155 C
Solar/Wind Helper
2.088
3138133OCRAN
Solar/Wind Helper
0.146
315662AE1-191 GEN
Solar/Wind Helper
1.308
200202DELTA2 ST
50/50
11.153
200052ROCKSP 1
50/50
4.677
200053ROCKSP 2
50/50
4.585
213942SCHUYLKILL
Adder
4.974
213942SCHUYLKILL
Adder
3.803
213957STHWK3-4
Adder
3.799
213957STHWK3-4
Adder
3.799
213561DLWR9-10
Adder
4.888
213561DLWR9-10
Adder
3.738
963401AG1-189 GEN
Solar/Wind Harmer
1.464
971189AH1-054 GEN
Solar/Wind Harmer
0.99
209027LOR2_Q27
Solar/Wind Harmer
0
3141426STAFORD
Solar/Wind Helper
0.056
316468AD1-105 GEN
Solar/Wind Helper
1.184
3141913WHIT STONE
Solar/Wind Helper
0.243
957831AF2-077 GEN
Solar/Wind Helper
0.326
315697AD1-025 GEN
Solar/Wind Helper
2.754
315839AE2-212 C
Solar/Wind Helper
0.324
316316AC1-027 C
Solar/Wind Helper
0.378
316258AE1-075 C
Solar/Wind Helper
0.328
316322AB2-045
Solar/Wind Helper
0.262
3145796HORNRTN
Solar/Wind Helper
0.743
3145796HORNRTN
Solar/Wind Helper
0.093
316210AC1-098 GEN
Solar/Wind Helper
1.871
316238AB2-078_GEN
Solar/Wind Helper
0.311
316239AB2-077_GEN
Solar/Wind Helper
0.311
3145746EVERETS
Solar/Wind Helper
0.917
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
3148133STUARTS
Solar/Wind Helper
0.138
3145573BETHELC
Solar/Wind Helper
0.229
3145573BETHELC
Solar/Wind Helper
0.229
232901NORTHST
Adder
15.552
234033AF1-007_GEN
Solar/Wind Harmer
25.781
232902EASTMUNI
Adder
24.192
234012AE2-112_GEN
Solar/Wind Harmer
4.276
972251AH1-710 GEN
Adder
80.305
231918WEST 1
Adder
5.882
228732V1-021 C
Adder
0.28
228400MICK 1CT
Adder
17.049
966261AG1-495 GEN
Solar/Wind Harmer
1.849
963071AG1-156 GEN
Solar/Wind Harmer
6.349
209023WIENIPP1
Adder
8.983
209025WIENIPP3
Adder
4.484
970757AG2-479 GEN
Solar/Wind Harmer
0.524
316447AC1-158 HLD
Solar/Wind Helper
3.051
316192AB2-158 GEN
Solar/Wind Helper
1.654
3142416OLDCHRC
Solar/Wind Helper
0.632
3142416OLDCHRC
Solar/Wind Helper
0.242
3141766HARMONY
Solar/Wind Helper
0.048
3142433PROV 92
Solar/Wind Helper
0.969
315975AC1-164 GENB
Solar/Wind Helper
0.093
3145336SMITFLD
Solar/Wind Helper
0.959
316375AC2-012 GEN
Solar/Wind Helper
0.63
3146456SLIGO L269
Solar/Wind Helper
0.239
3145663CRESWEL
Solar/Wind Helper
0.659
316023GEN1_S
Solar/Wind Helper
0.895
3146206CASHIE
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3156021HOLLOMANSOL
Solar/Wind Helper
1.783
3145683EARLEYS
Solar/Wind Helper
0.233
316131AB2-060 GEN
Solar/Wind Helper
1.411
3146083TARBORO
Solar/Wind Helper
0.229
316359AB2-059 GEN
Solar/Wind Helper
1.747
200035PCHBTM 3
50/50
38.112
233971AC1-093 C
Solar/Wind Harmer
3.368
232918OH NUG7
Adder
16.378
232905CHERITON_25
Adder
4.58
232910NRG_G1
Adder
15.987
234014AF1-036_GEN
Solar/Wind Harmer
4.276
972233AH1-701 GEN
Adder
6.066
219304NAMERICA C
Solar/Wind Harmer
0.123
20635028RRCT1&2
Adder
13.882
218418LINDEN_G5
Adder
20.077
219036LINDEN_G7
Adder
19.35
217086KRNY_131
Adder
10.565
316006AB2-029 C
Solar/Wind Helper
0.12
316045AC1-158 PL2
Solar/Wind Helper
4.436
966871AG1-558 GEN
Solar/Wind Helper
0.329
316156AD2-030 GEN
Solar/Wind Helper
0.367
315666AE1-190 GEN
Solar/Wind Helper
0.327
316240AF1-291 C
Solar/Wind Helper
0.325
316313AB2-026
Solar/Wind Helper
0.365
316435W1029_GEN3
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
315614AA2-178 GEN
Solar/Wind Helper
1.439
238149AF1-291A_GEN
Solar/Wind Helper
0.116
3145893MURPHYS
Solar/Wind Helper
0.336
3145893MURPHYS
Solar/Wind Helper
0.422
3146776BUCKING
Solar/Wind Helper
0.935
3146776BUCKING
Solar/Wind Helper
0.076
316140AB2-099
Solar/Wind Helper
0.089
316005AA1-067
Solar/Wind Helper
0.264
316118AC1-105 GEN
Solar/Wind Helper
0.888
200204Y1-065-CTG1
50/50
7.433
233918AB1-142 GEN
Solar/Wind Harmer
0.466
228206SHRMN CT
Adder
24.638
213611FALLS1-3
Adder
4.679
214194N WALES4
Adder
1.114
20635828PARLN1&2
Adder
8.909
20635028RRCT1&2
Adder
14.099
218524CNTRALGAS1 C
Solar/Wind Harmer
0.905
200201DELTA2 CT2
50/50
6.586
232410W1-006 C
Solar/Wind Harmer
1.205
232899W1-062
Adder
17.932
233984AB2-036 GEN
Solar/Wind Harmer
13.432
233930AB2-032 GEN
Solar/Wind Harmer
1.752
228307PCLP GT
Adder
17.623
213587EDDYSTN3
Adder
114.017
217083KRNY_132
Adder
10.476
209010PEIP 1
Adder
2.991
209010PEIP 1
Adder
0.438
961541AF2-445A GEN
Solar/Wind Harmer
1.709
209130AF1-271A GEN
Solar/Wind Harmer
1.304
223402AF1-300 C
Solar/Wind Helper
0.484
316411AF1-147_GEN1
Solar/Wind Helper
0.857
316312AB1-027
Solar/Wind Helper
0.464
3143526WINTERP
Solar/Wind Helper
1.258
316185AD1-033 GEN
Solar/Wind Helper
1.127
3144356SAPONY
Solar/Wind Helper
0.425
316315AB2-025 C
Solar/Wind Helper
0.362
237061AD1-155 GEN
Solar/Wind Helper
1.469
3145796HORNRTN
Solar/Wind Helper
0.696
316237AB2-079_GEN
Solar/Wind Helper
0.311
235020AA1-095 C
Solar/Wind Helper
0.043
315687AD1-152 GEN
Solar/Wind Helper
1.241
316248AF1-058 C
Solar/Wind Helper
0.306
238221AF1-254 C O1
Solar/Wind Helper
0.222
200192DELTA CT1
50/50
3.68
200054ROCKSP 3
50/50
4.731
232408W1-005 C
Solar/Wind Harmer
1.205
232917OH NUG6
Adder
16.414
232915OH NUG4
Adder
16.378
972177AH1-672 GEN
Solar/Wind Harmer
19.003
213958STHWK5-6
Adder
3.799
207522AF2-254 C
Solar/Wind Harmer
1.218
972275AH1-722 GEN
Adder
36.909
207528AF2-192 GEN
Solar/Wind Harmer
0.828
217186ESSEX_G9
Adder
4.478
217083KRNY_132
Adder
10.543
208909MACR G3
Adder
154.656
209010PEIP 1
Adder
0.544
316415AF1-147_GEN2
Solar/Wind Helper
0.857
964211AG1-282 GEN
Solar/Wind Helper
0.329
3143526WINTERP
Solar/Wind Helper
1.258
315671AE2-027_GEN
Solar/Wind Helper
1.946
238175AF1-290_GEN
Solar/Wind Helper
0.129
316072AD1-144
Solar/Wind Helper
0.274
3145823KELFORD
Solar/Wind Helper
0.233
3145783HORNRTN
Solar/Wind Helper
0.232
3145796HORNRTN
Solar/Wind Helper
0.766
3145796HORNRTN
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.243
316129AC1-054 GEN
Solar/Wind Helper
1.148
3145746EVERETS
Solar/Wind Helper
0.23
3145746EVERETS
Solar/Wind Helper
0.23
3147983MERCK5
Solar/Wind Helper
0.092
212507AE2-042_GEN
Solar/Wind Harmer
0.421
316337AD2-073 GEN
Solar/Wind Helper
0.373
3141726DUNNSVL
Solar/Wind Helper
0.977
316132AB2-190 GEN1
Solar/Wind Helper
1.379
315773AC2-141 GEN
Solar/Wind Helper
5.166
316036AC1-147 C
Solar/Wind Helper
0.365
3146516WINFALL
Solar/Wind Helper
0.77
3146516WINFALL
Solar/Wind Helper
0.238
3145893MURPHYS
Solar/Wind Helper
0.937
3146776BUCKING
Solar/Wind Helper
0.094
315607AA1-063A GEN
Solar/Wind Helper
1.335
3146263WOODLND
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
316494AC1-189 GEN
Solar/Wind Helper
1.404
961671AG1-007 GEN
Solar/Wind Helper
0.165
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.183
316280AD1-041 GEN
Solar/Wind Helper
0.817
3142543TWELFTH
Solar/Wind Helper
0.023
3143226MDLTHAN
Solar/Wind Helper
0.242
316369SG1_INVT
Solar/Wind Helper
1.161
316381AD1-082 GEN
Solar/Wind Helper
1.243
319010AE1-072 C
Solar/Wind Helper
2.732
315611Z1-036_GEN2
Solar/Wind Helper
1.302
3130156CHOWAN
Solar/Wind Helper
0.236
315816AE2-034 GEN
Solar/Wind Helper
1.079
238152AF2-075_GEN
Solar/Wind Helper
0.58
315737AD1-076 GEN
Solar/Wind Helper
2.299
3146926FARMVIL
Solar/Wind Helper
0.14
316087AB2-174 GEN
Solar/Wind Helper
1.635
315785AD2-033 C
Solar/Wind Helper
2.703
23777901MDS_W4-102
Solar/Wind Helper
0.146
3146233WITAKRS
Solar/Wind Helper
0.913
233972AC1-094 C
Solar/Wind Harmer
3.368
232921TASLEY2G
Adder
9.636
213497CHSTR7-9
Adder
3.913
213560DLW11-12
Adder
3.738
20635928PARLN3&4
Adder
4.035
3141906WESTMOR
Solar/Wind Helper
0.099
3147666LOUISA
Solar/Wind Helper
0.565
316458AB2-190 GEN2
Solar/Wind Helper
1.379
3144873MCLAUGH
Solar/Wind Helper
0.006
316246AF1-032 C
Solar/Wind Helper
0.273
316321Z2-027
Solar/Wind Helper
0.363
3146626S HERTFORD
Solar/Wind Helper
0.237
3146926FARMVIL
Solar/Wind Helper
0.14
3142666NORTHAMPTON
Solar/Wind Helper
0.233
316190AA2-174 GEN
Solar/Wind Helper
0.016
3145933PARMELE
Solar/Wind Helper
0.231
3148013FISHERV
Solar/Wind Helper
0.23
3146233WITAKRS
Solar/Wind Helper
0.247
3146233WITAKRS
Solar/Wind Helper
0.156
G-007ALTFEXP_G-007A->PJM
CMTX
61.314
CBM NorthLTFEXP_CBM-N->PJM
CBM
75.878
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.877
BlueGrassPJM->LTFIMP_BlueG
CLTF
15.193
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.659
VTFLTFEXP_VFT->PJM
CMTX
154.716
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.363
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.85

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PJM_500_BG_P4_5_CNSTN_M_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PJM_500_BG_P4_5_CNSTN_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.54 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:4218.81
MW Contribution:
8.04
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232912OH NUG1
Adder
9.718
971195AH1-057 GEN
Solar/Wind Harmer
1.072
233955AB2-172 GEN
Solar/Wind Harmer
5.479
232813VAUGHN
Adder
0.643
231902DC CT7
Adder
12.055
233915AB1-141 GEN
Solar/Wind Harmer
1.059
970453AG2-297 GEN
Solar/Wind Harmer
2.549
964001AG1-254 GEN
Solar/Wind Harmer
6.629
228728W1-130C
Solar/Wind Harmer
0.603
227927V4-067C
Solar/Wind Harmer
0.18
219137THOSOLAR C
Solar/Wind Harmer
1.071
219615MILLCREEK C
Solar/Wind Harmer
0.206
219224BRL12CT4
Adder
7.676
207487AE2-000G4
Solar/Wind Harmer
26.768
207497AE2-000G2
Solar/Wind Harmer
26.768
219620RIDERU C
Solar/Wind Harmer
0.046
20635928PARLN3&4
Adder
6.039
218526CNTRALGAS2 C
Solar/Wind Harmer
0.3
217167KRNY_14
Adder
7.38
971009AG2-626 GEN
Solar/Wind Harmer
1.236
961261AF2-417 GEN
Solar/Wind Harmer
0.714
212266LOR1
Solar/Wind Harmer
0.809
959431AF2-234 GEN
Solar/Wind Harmer
1.27
233973AC2-185 C
Solar/Wind Harmer
5.984
970695AG2-447 GEN
Solar/Wind Harmer
3.958
233987AB2-037 GEN
Solar/Wind Harmer
12.509
233923SMA
Solar/Wind Harmer
4.02
233997TMININ_4.2
Solar/Wind Harmer
1.096
232907VN8
Adder
33.013
232417X3-008 C
Solar/Wind Harmer
1.233
233935AB2-179 C
Solar/Wind Harmer
2.584
219221BRL12CT1
Adder
7.676
219223BRL12CT3
Adder
7.676
20715728PEM_W1-119
Solar/Wind Harmer
0.454
20636028O CRK C1
Adder
6.006
959561AF2-247 GEN
Solar/Wind Harmer
0.412
971667AH1-334 GEN
Solar/Wind Harmer
2.318
219727YARDVSOLFA C
Solar/Wind Harmer
0.762
20635828PARLN1&2
Adder
2.735
219249CENTRALDIV C
Solar/Wind Harmer
0.032
207442AE1-156 GEN
Solar/Wind Harmer
0.593
217211CAMDEN ST C
Solar/Wind Harmer
0.019
217194REDH C
Solar/Wind Harmer
0.39
207511W3-106 GEN
Solar/Wind Harmer
0.254
971007AG2-625 GEN
Solar/Wind Harmer
1.937
20466127PORT 5CT
Adder
19.892
200195DELTA ST
50/50
3.243
232920IR10
Adder
3.479
233901CHERRYDALE C
Solar/Wind Harmer
1.237
232913OH NUG2
Adder
9.588
231906DC3 NUG
Adder
15.08
231907DC10
Adder
3.765
970597AG2-380 GEN
Solar/Wind Harmer
4.485
972141AH1-641 GEN
Solar/Wind Harmer
2.622
20715028HAN_X4-015
Solar/Wind Harmer
0.254
207507AE2-000G3
Solar/Wind Harmer
26.768
213611FALLS1-3
Adder
3.001
213611FALLS1-3
Adder
3.001
207445AB1-138_GEN
Solar/Wind Harmer
0.488
20720628TIN_W1-124
Solar/Wind Harmer
0.825
971521AH1-258 GEN
Solar/Wind Harmer
2.234
20675528CPH_W2-050
Solar/Wind Harmer
0.461
20676428JCR_X2-075
Solar/Wind Harmer
0.272
217086KRNY_131
Adder
7.317
20675128HRM_W1-127
Solar/Wind Harmer
0.127
209029WAYMART-WD
Solar/Wind Harmer
1.804
959421AF2-233 GEN
Solar/Wind Harmer
0.635
226929AD2-058 GEN
Solar/Wind Helper
0.133
232904IR4
Adder
89.03
232432Z2-076 GEN
Solar/Wind Harmer
0.145
233968AD2-076_GEN
Solar/Wind Harmer
7.142
231919CHRIST1
Adder
4.54
231920CHRIST2
Adder
4.439
230422AE1-104_GEN1
Solar/Wind Harmer
30.772
230425AE1-104_GEN2
Solar/Wind Harmer
30.772
230430AE1-229_GEN
Solar/Wind Harmer
26.078
230407AD2-065 C
Solar/Wind Harmer
0.119
20720728JCB_W1-129
Solar/Wind Harmer
0.254
207500AE2-000G1
Solar/Wind Harmer
26.768
970025AG2-016 GEN
Solar/Wind Harmer
2.4
20714428HOW_X1-037
Solar/Wind Harmer
1.025
218449LINSOLAR C
Solar/Wind Harmer
0.806
217147KRNY_1212
Adder
7.02
217147KRNY_1212
Adder
6.894
217146KRNY_1234
Adder
6.879
217146KRNY_1234
Adder
6.832
964851AG1-348 GEN
Solar/Wind Harmer
1.031
207408W3-077 C
Solar/Wind Harmer
0.379
20462827N BANGR8
Adder
0.534
209026WIENIPP4
Adder
3.726
209054AE2-059 GEN
Solar/Wind Harmer
1.088
232901NORTHST
Adder
9.195
234033AF1-007_GEN
Solar/Wind Harmer
40.956
233996TM1833_GEN
Solar/Wind Harmer
1.096
232426Y1-080 FULL
Solar/Wind Harmer
0.21
232902EASTMUNI
Adder
14.21
972251AH1-710 GEN
Adder
48.401
234012AE2-112_GEN
Solar/Wind Harmer
2.478
231918WEST 1
Adder
3.451
228732V1-021 C
Adder
0.174
228400MICK 1CT
Adder
10.582
219766PARADISE C
Solar/Wind Harmer
0.276
20714528FRN_Y2-051
Solar/Wind Harmer
0.247
219680HOPEWELLV C1
Solar/Wind Harmer
0.063
218440SUMMTASSOC C
Solar/Wind Harmer
0.103
217208PARK ELE C
Solar/Wind Harmer
0.02
966261AG1-495 GEN
Solar/Wind Harmer
2.703
200204Y1-065-CTG1
50/50
4.264
233918AB1-142 GEN
Solar/Wind Harmer
1.059
228206SHRMN CT
Adder
15.254
228260V4-054C
Solar/Wind Harmer
0.939
228729W2-030 C
Solar/Wind Harmer
0.524
219686LUMSOLAR_N C
Solar/Wind Harmer
0.178
219348LDSOLAR C
Solar/Wind Harmer
0.514
213611FALLS1-3
Adder
3.001
214194N WALES4
Adder
0.715
20720428HOL_W1-112
Solar/Wind Harmer
0.285
20635828PARLN1&2
Adder
6.039
20635028RRCT1&2
Adder
9.589
218524CNTRALGAS1 C
Solar/Wind Harmer
0.299
217209CENTRL HS C
Solar/Wind Harmer
0.036
20671828STAW2-080
Solar/Wind Harmer
0.083
207439AE1-081 C O1
Solar/Wind Harmer
0.046
207530AG1-191 GEN
Solar/Wind Harmer
1.053
211065PSPA IPP
Solar/Wind Harmer
0.328
961301AF2-421 GEN
Solar/Wind Harmer
0.699
963151AG1-164 GEN
Solar/Wind Harmer
0.699
961341AF2-425 GEN
Solar/Wind Harmer
0.661
212507AE2-042_GEN
Solar/Wind Harmer
1.928
200194DELTA CT3
50/50
2.099
233970AC1-092 C
Solar/Wind Harmer
2.962
232900DEMECSMY
Adder
10.163
232404W1-003 C
Solar/Wind Harmer
1.1
233998TM1NIN_3.36
Solar/Wind Harmer
1.096
232919VN10
Adder
3.083
231917EM10
Adder
2.4
970997AG2-616 GEN
Solar/Wind Harmer
8.74
213497CHSTR7-9
Adder
2.365
213497CHSTR7-9
Adder
2.365
219222BRL12CT2
Adder
7.676
213560DLW11-12
Adder
2.328
20717128DIX_Z2-102
Solar/Wind Harmer
1.122
20715828PEM_W1-120
Solar/Wind Harmer
0.454
963711AG1-223 GEN
Solar/Wind Harmer
1.238
219276PARKLANDSO C
Solar/Wind Harmer
0.384
200035PCHBTM 3
50/50
21.288
233971AC1-093 C
Solar/Wind Harmer
2.812
232918OH NUG7
Adder
9.653
232905CHERITON_25
Adder
2.699
233994AC2-023 GEN
Solar/Wind Harmer
2.951
234036AF2-325 C
Solar/Wind Harmer
1.005
232910NRG_G1
Adder
9.408
234014AF1-036_GEN
Solar/Wind Harmer
2.915
232436AB1-176 C
Solar/Wind Harmer
0.246
972233AH1-701 GEN
Adder
3.765
219912AD2-042 GEN
Solar/Wind Harmer
0.695
219607WPEMNERT C
Solar/Wind Harmer
0.36
219304NAMERICA C
Solar/Wind Harmer
0.267
20635028RRCT1&2
Adder
9.441
218418LINDEN_G5
Adder
13.824
219036LINDEN_G7
Adder
13.399
217086KRNY_131
Adder
7.396
20674328GAR_V4-001
Solar/Wind Harmer
0.084
946751AF1-339 GEN
Solar/Wind Harmer
0.637
20674128FR_U2-059
Solar/Wind Harmer
0.137
211065PSPA IPP
Solar/Wind Harmer
0.328
957921AF2-086 GEN
Solar/Wind Harmer
0.641
20674628WNG_W3-110
Solar/Wind Harmer
0.31
209023WIENIPP1
Adder
7.541
209025WIENIPP3
Adder
3.764
963071AG1-156 GEN
Solar/Wind Harmer
6.911
232926CRISFLD1
Adder
2.159
231940T-011
Adder
0.821
234041AC1-190 GEN
Solar/Wind Harmer
9.819
228201CARL#2CT
Adder
6.292
228200CARL#1CT
Adder
5.984
219904AC1-010 C
Solar/Wind Harmer
0.332
219906AC1-017 C
Solar/Wind Harmer
0.192
213815MOSER1-3
Adder
3.015
213815MOSER1-3
Adder
3.015
20720828JCB_W4-025
Solar/Wind Harmer
0.385
20714828MDF_W3-079
Solar/Wind Harmer
0.256
219817TRENTONSOL C
Solar/Wind Harmer
0.914
20641628MLH_W1-032
Solar/Wind Harmer
0.243
20742028HF_AC1-207
Solar/Wind Harmer
0.648
218438BLK ROCK C
Solar/Wind Harmer
0.112
972260AH1-715 GEN1
Adder
11.069
972261AH1-715 GEN2
Adder
12.826
217202FBANKSOLAR C
Solar/Wind Harmer
0.059
217201HACKENSOLA C
Solar/Wind Harmer
0.058
217206BARNGR HS C
Solar/Wind Harmer
0.024
217204WCALDSOLAR C
Solar/Wind Harmer
0.058
20674828DL_W4-046
Solar/Wind Harmer
0.489
20634528N27_Y2-018
Solar/Wind Harmer
0.203
232434Z2-077 GEN
Solar/Wind Harmer
0.275
232406W1-004 FULL
Solar/Wind Harmer
1.1
233964AF2-378 GEN
Solar/Wind Harmer
0.14
232422X3-066 FULL
Solar/Wind Harmer
0.269
230415AB2-049 C
Solar/Wind Harmer
0.172
219291REEVESSOUT C
Solar/Wind Harmer
0.053
219236SOUTHERNHQ C
Solar/Wind Harmer
0.059
213815MOSER1-3
Adder
3.015
20714928UPF_X1-085
Solar/Wind Harmer
0.343
219114HARTZY_C
Solar/Wind Harmer
0.7
219918AC2-009 C
Solar/Wind Harmer
0.021
20674528F3S_W2-016
Solar/Wind Harmer
1.099
209025WIENIPP3
Adder
3.688
209142AF1-226 GEN
Solar/Wind Harmer
3.816
205941AD2-115 GEN
Solar/Wind Harmer
0.496
227287AC2-120 GEN
Solar/Wind Helper
0.486
200202DELTA2 ST
50/50
6.362
200052ROCKSP 1
50/50
2.683
200053ROCKSP 2
50/50
2.63
233940AF2-379 C
Solar/Wind Harmer
0.205
230434AG1-499 GEN
Solar/Wind Harmer
0.523
219258KINSLEYDEP C
Solar/Wind Harmer
0.285
213957STHWK3-4
Adder
2.334
213957STHWK3-4
Adder
2.334
219610FLORENCE C
Solar/Wind Harmer
1.191
213942SCHUYLKILL
Adder
3.052
213942SCHUYLKILL
Adder
2.334
213561DLWR9-10
Adder
3.044
213561DLWR9-10
Adder
2.328
963401AG1-189 GEN
Solar/Wind Harmer
1.928
971189AH1-054 GEN
Solar/Wind Harmer
0.998
20716228APLW2-078
Solar/Wind Harmer
0.732
20673828FLE_V3-070
Solar/Wind Harmer
0.373
20676128MHD_W3-029
Solar/Wind Harmer
0.381
209027LOR2_Q27
Solar/Wind Harmer
3.052
964051AG1-259 GEN
Solar/Wind Harmer
0.852
964061AG1-260 GEN
Solar/Wind Harmer
0.852
3141426STAFORD
Solar/Wind Helper
0.05
200192DELTA CT1
50/50
2.099
200054ROCKSP 3
50/50
2.714
972177AH1-672 GEN
Solar/Wind Harmer
14.788
232408W1-005 C
Solar/Wind Harmer
1.1
232917OH NUG6
Adder
9.675
232915OH NUG4
Adder
9.653
233944AB2-135 GEN
Solar/Wind Harmer
5.614
219907AC1-030 C
Solar/Wind Harmer
0.121
213958STHWK5-6
Adder
2.334
20716028EGP_W2-019
Solar/Wind Harmer
0.395
207522AF2-254 C
Solar/Wind Harmer
1.221
218428ETC SOLAR C
Solar/Wind Harmer
0.029
219908AB1-139 C
Solar/Wind Harmer
0.307
972275AH1-722 GEN
Adder
25.413
20673628F1S_V4-069
Solar/Wind Harmer
0.143
207528AF2-192 GEN
Solar/Wind Harmer
1.014
217186ESSEX_G9
Adder
3.134
217083KRNY_132
Adder
7.38
20676228FRD_X1-012
Solar/Wind Harmer
0.455
20675828AU_W4-064
Solar/Wind Harmer
0.133
20675728RH_W2-091
Solar/Wind Harmer
0.452
207484AF2-139 C O1
Solar/Wind Harmer
0.376
208909MACR G3
Adder
118.084
209010PEIP 1
Adder
0.449
946731AF1-337 GEN
Solar/Wind Harmer
0.637
200201DELTA2 CT2
50/50
3.757
232899W1-062
Adder
10.596
232410W1-006 C
Solar/Wind Harmer
1.1
233946AB2-136 GEN
Solar/Wind Harmer
4.375
233952AC2-187 GEN
Solar/Wind Harmer
1.234
233954AC2-188 GEN
Solar/Wind Harmer
1.234
233984AB2-036 GEN
Solar/Wind Harmer
13.498
233930AB2-032 GEN
Solar/Wind Harmer
0.891
233982AB2-133 GEN
Solar/Wind Harmer
5.204
230511AF1-262
Solar/Wind Harmer
0.166
228754AB1-001 C
Solar/Wind Harmer
0.126
228307PCLP GT
Adder
10.92
219272CLEANLIGHT C
Solar/Wind Harmer
0.161
213587EDDYSTN3
Adder
68.948
217081WEATEXAS C
Solar/Wind Harmer
0.069
217083KRNY_132
Adder
7.333
207471AF2-354 C
Solar/Wind Harmer
0.387
20675928HOL_W4-097
Solar/Wind Harmer
0.097
209010PEIP 1
Adder
2.47
209010PEIP 1
Adder
0.362
961541AF2-445A GEN
Solar/Wind Harmer
2.192
961431AF2-434 GEN
Solar/Wind Harmer
0.659
209130AF1-271A GEN
Solar/Wind Harmer
1.786
223402AF1-300 C
Solar/Wind Helper
0.718
200200DELTA2 CT1
50/50
3.757
200193DELTA CT2
50/50
2.099
200203Y1-065-STG
50/50
7.384
200055ROCKSP 4
50/50
2.667
233939AC1-091 C
Solar/Wind Harmer
2.962
232914OH NUG3
Adder
9.718
232916OH NUG5
Adder
9.718
233933AB2-153 GEN
Solar/Wind Harmer
1.203
219623KINSLEYBEA C
Solar/Wind Harmer
0.377
213958STHWK5-6
Adder
2.334
20716428NHV_W2-082
Solar/Wind Harmer
1.512
963391AG1-188 GEN
Solar/Wind Harmer
3.175
219612MATRIX C
Solar/Wind Harmer
0.151
20716928W4-060COL
Solar/Wind Harmer
0.583
217213AMBOY SO C
Solar/Wind Harmer
0.102
20673728F2S_V4-070
Solar/Wind Harmer
0.143
207510AF2-138 C
Solar/Wind Harmer
1.367
207437AD2-070 GEN
Solar/Wind Harmer
0.224
20671928W4-073
Solar/Wind Harmer
0.322
20465427SHAW CT
Adder
2.889
20633028GILCT9
Adder
20.866
209116AE2-175 GEN
Solar/Wind Harmer
3.024
970095AG2-074 GEN
Solar/Wind Harmer
4.377
961421AF2-433 GEN
Solar/Wind Harmer
0.659
209093AE2-110 GEN
Solar/Wind Harmer
1.648
209120AE2-241 GEN
Solar/Wind Harmer
2.181
946691AF1-333 GEN
Solar/Wind Harmer
0.637
946741AF1-338 GEN
Solar/Wind Harmer
0.637
226910AB2-157 C
Solar/Wind Helper
0.02
20715228NPK_W1-113
Solar/Wind Harmer
0.356
20720528MAN_W1-024
Solar/Wind Harmer
0.21
219919AE1-041 FULL
Solar/Wind Harmer
0.033
217121ECCF
Adder
0.345
20676728BRNX1-095
Solar/Wind Harmer
0.138
20676328BVR_Y1-020
Solar/Wind Harmer
0.255
20674928WA_W3-044
Solar/Wind Harmer
0.364
971519AH1-257 GEN
Solar/Wind Harmer
1.897
207518AF1-320_GEN
Solar/Wind Harmer
2.738
20465127PORT CT
Adder
2.248
209018SUNBIPCT
Adder
4.731
208835TUHI V3-051
Solar/Wind Helper
0.022
200034PCHBTM 2
50/50
21.89
200205Y1-065-CTG2
50/50
4.264
234015AF2-250 C
Solar/Wind Harmer
0.132
232428Y3-058 C
Solar/Wind Harmer
0.916
232424Y1-079 C
Solar/Wind Harmer
0.609
228251CARLLS#4
Adder
0.577
230433AD2-135 GEN
Solar/Wind Harmer
0.092
228351V2-046C
Solar/Wind Harmer
1.832
219287REEVESEAST C
Solar/Wind Harmer
1.183
213589EDDYSTN4
Adder
68.955
213535CROYDN11
Adder
8.783
20636128O CRK C2
Adder
5.476
214067T20SOLAR
Solar/Wind Harmer
0.214
207459AE1-142 C O1
Solar/Wind Harmer
0.89
20628028LAKEHURS
Adder
0.802
217197RE CRAN C
Solar/Wind Harmer
0.44
924131AB2-057 GEN
Solar/Wind Harmer
0.838
20635128RRCT3&4
Adder
9.113
20635128RRCT3&4
Adder
7.949
218419LINDEN_G6
Adder
13.824
219035LINDEN_G8
Adder
13.208
20675428EAM_W2-061
Solar/Wind Harmer
0.151
972237AH1-703 GEN
Adder
8.035
20465127PORT CT
Adder
2.983
223401AF1-299 GEN
Solar/Wind Helper
0.718
233972AC1-094 C
Solar/Wind Harmer
2.378
232921TASLEY2G
Adder
5.68
233950AC2-186 GEN
Solar/Wind Harmer
0.617
228711V2-041C
Solar/Wind Harmer
0.553
218660EHAMPSOLAR C
Solar/Wind Harmer
0.154
219921AF1-264
Solar/Wind Harmer
0.127
219688LUMSOLAR_S C
Solar/Wind Harmer
0.178
219914AD2-027 C
Solar/Wind Harmer
0.524
213497CHSTR7-9
Adder
2.365
213560DLW11-12
Adder
2.328
207454AA2-184 E
Solar/Wind Harmer
0.828
20635928PARLN3&4
Adder
2.735
217169METRODIV C
Solar/Wind Harmer
0.032
963161AG1-165 GEN
Solar/Wind Harmer
0.699
208972BECR K09
Solar/Wind Harmer
0.732
961331AF2-424 GEN
Solar/Wind Harmer
0.661
209071AE2-133 GEN
Solar/Wind Harmer
1.075
208835TUHI V3-051
Solar/Wind Helper
0.022
G-007ALTFEXP_G-007A->PJM
CMTX
41.698
CBM NorthLTFEXP_CBM-N->PJM
CBM
58.927
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.032
BlueGrassPJM->LTFIMP_BlueG
CLTF
9.452
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.146
VTFLTFEXP_VFT->PJM
CMTX
107.886
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.401
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
14.432

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o Base Case


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.37 %
Rating:2920.0 MVA
Rating Type:A
MVA to Mitigate:3310.31
MW Contribution:
9.19
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232912OH NUG1
Adder
11.372
971195AH1-057 GEN
Solar/Wind Harmer
0.804
232813VAUGHN
Adder
0.753
231902DC CT7
Adder
14.144
233915AB1-141 GEN
Solar/Wind Harmer
0.32
232434Z2-077 GEN
Solar/Wind Harmer
0.054
232406W1-004 FULL
Solar/Wind Harmer
0.831
232422X3-066 FULL
Solar/Wind Harmer
0.105
213815MOSER1-3
Adder
3.51
209025WIENIPP3
Adder
4.066
209142AF1-226 GEN
Solar/Wind Harmer
2.02
205941AD2-115 GEN
Solar/Wind Harmer
0.072
227287AC2-120 GEN
Solar/Wind Helper
0.413
233973AC2-185 C
Solar/Wind Harmer
2.329
970695AG2-447 GEN
Solar/Wind Harmer
3.227
233987AB2-037 GEN
Solar/Wind Harmer
-0.002
232907VN8
Adder
38.641
233935AB2-179 C
Solar/Wind Harmer
1.677
219221BRL12CT1
Adder
8.911
219223BRL12CT3
Adder
8.911
20636028O CRK C1
Adder
6.94
971667AH1-334 GEN
Solar/Wind Harmer
1.73
20635828PARLN1&2
Adder
3.143
207442AE1-156 GEN
Solar/Wind Harmer
0.054
971007AG2-625 GEN
Solar/Wind Harmer
1.423
20466127PORT 5CT
Adder
22.534
200200DELTA2 CT1
50/50
4.37
200193DELTA CT2
50/50
2.442
200203Y1-065-STG
50/50
8.594
200055ROCKSP 4
50/50
3.104
233939AC1-091 C
Solar/Wind Harmer
2.329
232914OH NUG3
Adder
11.372
232916OH NUG5
Adder
11.372
213958STHWK5-6
Adder
2.734
963391AG1-188 GEN
Solar/Wind Harmer
1.791
207437AD2-070 GEN
Solar/Wind Harmer
0.055
20465427SHAW CT
Adder
3.263
20633028GILCT9
Adder
23.749
970095AG2-074 GEN
Solar/Wind Harmer
3.861
209093AE2-110 GEN
Solar/Wind Harmer
1.154
209120AE2-241 GEN
Solar/Wind Harmer
1.154
226910AB2-157 C
Solar/Wind Helper
0.017
232926CRISFLD1
Adder
2.527
231940T-011
Adder
0.96
234041AC1-190 GEN
Solar/Wind Harmer
9.358
228201CARL#2CT
Adder
7.318
228200CARL#1CT
Adder
6.96
213815MOSER1-3
Adder
3.51
213815MOSER1-3
Adder
3.51
20714828MDF_W3-079
Solar/Wind Harmer
0.095
972260AH1-715 GEN1
Adder
12.69
972261AH1-715 GEN2
Adder
14.691
970761AG2-481 GEN
Solar/Wind Harmer
0.545
232901NORTHST
Adder
10.748
234033AF1-007_GEN
Solar/Wind Harmer
17.79
232902EASTMUNI
Adder
16.653
234012AE2-112_GEN
Solar/Wind Harmer
2.939
972251AH1-710 GEN
Adder
56.355
231918WEST 1
Adder
4.06
228732V1-021 C
Adder
0.202
228400MICK 1CT
Adder
12.321
966261AG1-495 GEN
Solar/Wind Harmer
1.51
209023WIENIPP1
Adder
8.313
209025WIENIPP3
Adder
4.15
232904IR4
Adder
104.156
232432Z2-076 GEN
Solar/Wind Harmer
0.017
233968AD2-076_GEN
Solar/Wind Harmer
2.939
231919CHRIST1
Adder
5.34
231920CHRIST2
Adder
5.221
230422AE1-104_GEN1
Solar/Wind Harmer
14.354
230425AE1-104_GEN2
Solar/Wind Harmer
14.354
230430AE1-229_GEN
Solar/Wind Harmer
21.028
207500AE2-000G1
Solar/Wind Harmer
12.416
970025AG2-016 GEN
Solar/Wind Harmer
1.792
217147KRNY_1212
Adder
8.027
217147KRNY_1212
Adder
7.884
217146KRNY_1234
Adder
7.866
217146KRNY_1234
Adder
7.812
20462827N BANGR8
Adder
0.606
209026WIENIPP4
Adder
4.108
20486527WR_V4-052
Adder
0.596
200195DELTA ST
50/50
3.772
232920IR10
Adder
4.071
232913OH NUG2
Adder
11.22
231906DC3 NUG
Adder
17.692
231907DC10
Adder
4.417
970597AG2-380 GEN
Solar/Wind Harmer
5.264
972141AH1-641 GEN
Solar/Wind Harmer
1.655
213611FALLS1-3
Adder
3.48
213611FALLS1-3
Adder
3.48
207507AE2-000G3
Solar/Wind Harmer
12.416
971521AH1-258 GEN
Solar/Wind Harmer
1.661
217086KRNY_131
Adder
8.367
226929AD2-058 GEN
Solar/Wind Helper
0.114
200035PCHBTM 3
50/50
24.778
233971AC1-093 C
Solar/Wind Harmer
2.329
232918OH NUG7
Adder
11.296
232905CHERITON_25
Adder
3.159
232910NRG_G1
Adder
11.021
234014AF1-036_GEN
Solar/Wind Harmer
2.939
972233AH1-701 GEN
Adder
4.383
219304NAMERICA C
Solar/Wind Harmer
0.091
20635028RRCT1&2
Adder
10.843
218418LINDEN_G5
Adder
15.848
219036LINDEN_G7
Adder
15.347
217086KRNY_131
Adder
8.457
200202DELTA2 ST
50/50
7.401
200052ROCKSP 1
50/50
3.122
200053ROCKSP 2
50/50
3.061
213942SCHUYLKILL
Adder
3.576
213942SCHUYLKILL
Adder
2.735
213957STHWK3-4
Adder
2.734
213957STHWK3-4
Adder
2.734
213561DLWR9-10
Adder
3.554
213561DLWR9-10
Adder
2.717
963401AG1-189 GEN
Solar/Wind Harmer
1.101
971189AH1-054 GEN
Solar/Wind Harmer
0.745
209027LOR2_Q27
Solar/Wind Harmer
0
200201DELTA2 CT2
50/50
4.37
232899W1-062
Adder
12.389
232410W1-006 C
Solar/Wind Harmer
0.831
233984AB2-036 GEN
Solar/Wind Harmer
9.239
233930AB2-032 GEN
Solar/Wind Harmer
1.204
228307PCLP GT
Adder
12.712
213587EDDYSTN3
Adder
81.02
217083KRNY_132
Adder
8.385
209010PEIP 1
Adder
2.71
209010PEIP 1
Adder
0.397
961541AF2-445A GEN
Solar/Wind Harmer
1.654
209130AF1-271A GEN
Solar/Wind Harmer
1.335
223402AF1-300 C
Solar/Wind Helper
0.595
200192DELTA CT1
50/50
2.442
200054ROCKSP 3
50/50
3.158
972177AH1-672 GEN
Solar/Wind Harmer
13.116
232408W1-005 C
Solar/Wind Harmer
0.831
232917OH NUG6
Adder
11.321
232915OH NUG4
Adder
11.296
213958STHWK5-6
Adder
2.734
207522AF2-254 C
Solar/Wind Harmer
0.912
972275AH1-722 GEN
Adder
29.134
207528AF2-192 GEN
Solar/Wind Harmer
0.657
217186ESSEX_G9
Adder
3.584
217083KRNY_132
Adder
8.439
208909MACR G3
Adder
133.592
209010PEIP 1
Adder
0.493
200204Y1-065-CTG1
50/50
4.963
233918AB1-142 GEN
Solar/Wind Harmer
0.32
228206SHRMN CT
Adder
17.736
213611FALLS1-3
Adder
3.48
214194N WALES4
Adder
0.831
20635828PARLN1&2
Adder
6.939
20635028RRCT1&2
Adder
11.012
218524CNTRALGAS1 C
Solar/Wind Harmer
0.71
212507AE2-042_GEN
Solar/Wind Harmer
0.425
963071AG1-156 GEN
Solar/Wind Harmer
5.821
970757AG2-479 GEN
Solar/Wind Harmer
0.537
200194DELTA CT3
50/50
2.442
233970AC1-092 C
Solar/Wind Harmer
2.329
232900DEMECSMY
Adder
11.884
232404W1-003 C
Solar/Wind Harmer
0.831
232919VN10
Adder
3.609
231917EM10
Adder
2.824
970997AG2-616 GEN
Solar/Wind Harmer
7.65
213497CHSTR7-9
Adder
2.779
213497CHSTR7-9
Adder
2.779
213560DLW11-12
Adder
2.717
219222BRL12CT2
Adder
8.911
217121ECCF
Adder
0.394
971519AH1-257 GEN
Solar/Wind Harmer
1.394
20465127PORT CT
Adder
2.549
209018SUNBIPCT
Adder
5.068
20465527S.RDG CT
Adder
1.516
233972AC1-094 C
Solar/Wind Harmer
2.329
232921TASLEY2G
Adder
6.646
213497CHSTR7-9
Adder
2.779
213560DLW11-12
Adder
2.717
20635928PARLN3&4
Adder
3.143
970453AG2-297 GEN
Solar/Wind Harmer
2.736
964001AG1-254 GEN
Solar/Wind Harmer
5.972
219224BRL12CT4
Adder
8.911
207487AE2-000G4
Solar/Wind Harmer
12.416
207497AE2-000G2
Solar/Wind Harmer
12.416
20635928PARLN3&4
Adder
6.939
218526CNTRALGAS2 C
Solar/Wind Harmer
0.712
217167KRNY_14
Adder
8.439
971009AG2-626 GEN
Solar/Wind Harmer
0.908
200034PCHBTM 2
50/50
25.466
200205Y1-065-CTG2
50/50
4.963
228251CARLLS#4
Adder
0.671
213589EDDYSTN4
Adder
81.033
213535CROYDN11
Adder
10.198
20636128O CRK C2
Adder
6.328
20628028LAKEHURS
Adder
0.925
20635128RRCT3&4
Adder
10.466
20635128RRCT3&4
Adder
9.13
218419LINDEN_G6
Adder
15.848
219035LINDEN_G8
Adder
15.128
972237AH1-703 GEN
Adder
9.189
20465127PORT CT
Adder
3.383
20465527S.RDG CT
Adder
1.467
223401AF1-299 GEN
Solar/Wind Helper
0.595
G-007ALTFEXP_G-007A->PJM
CMTX
47.889
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.477
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.832
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.145
VTFLTFEXP_VFT->PJM
CMTX
123.44
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.451
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.33

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P2-2_NOTT230B_SRT-A/* $ CHESCO $ PECO_P2-2_NOTT230B $ B
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.12 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:3877.79
MW Contribution:
9.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200194DELTA CT3
50/50
2.478
232919VN10
Adder
3.951
233998TM1NIN_3.36
Solar/Wind Harmer
1.402
232404W1-003 C
Solar/Wind Harmer
1.407
232900DEMECSMY
Adder
12.945
233955AB2-172 GEN
Solar/Wind Harmer
7.035
232912OH NUG1
Adder
12.428
971195AH1-057 GEN
Solar/Wind Harmer
1.371
232813VAUGHN
Adder
0.827
233915AB1-141 GEN
Solar/Wind Harmer
1.388
233964AF2-378 GEN
Solar/Wind Harmer
0.18
232406W1-004 FULL
Solar/Wind Harmer
1.407
232434Z2-077 GEN
Solar/Wind Harmer
0.352
232422X3-066 FULL
Solar/Wind Harmer
0.351
230415AB2-049 C
Solar/Wind Harmer
0.218
219291REEVESSOUT C
Solar/Wind Harmer
0.067
219236SOUTHERNHQ C
Solar/Wind Harmer
0.075
213815MOSER1-3
Adder
3.886
234041AC1-190 GEN
Solar/Wind Harmer
12.605
232926CRISFLD1
Adder
2.762
231940T-011
Adder
1.049
228201CARL#2CT
Adder
7.979
228200CARL#1CT
Adder
7.588
219904AC1-010 C
Solar/Wind Harmer
0.425
219906AC1-017 C
Solar/Wind Harmer
0.246
213815MOSER1-3
Adder
3.886
213815MOSER1-3
Adder
3.886
20720828JCB_W4-025
Solar/Wind Harmer
0.485
20714828MDF_W3-079
Solar/Wind Harmer
0.32
219817TRENTONSOL C
Solar/Wind Harmer
1.146
20641628MLH_W1-032
Solar/Wind Harmer
0.303
20742028HF_AC1-207
Solar/Wind Harmer
0.808
218438BLK ROCK C
Solar/Wind Harmer
0.139
972260AH1-715 GEN1
Adder
13.713
972261AH1-715 GEN2
Adder
15.867
217202FBANKSOLAR C
Solar/Wind Harmer
0.072
217201HACKENSOLA C
Solar/Wind Harmer
0.072
217206BARNGR HS C
Solar/Wind Harmer
0.03
217204WCALDSOLAR C
Solar/Wind Harmer
0.071
20674828DL_W4-046
Solar/Wind Harmer
0.598
20634528N27_Y2-018
Solar/Wind Harmer
0.248
233987AB2-037 GEN
Solar/Wind Harmer
16.045
232907VN8
Adder
42.282
232417X3-008 C
Solar/Wind Harmer
1.583
233923SMA
Solar/Wind Harmer
5.142
233997TMININ_4.2
Solar/Wind Harmer
1.402
233973AC2-185 C
Solar/Wind Harmer
7.595
970695AG2-447 GEN
Solar/Wind Harmer
5.025
233935AB2-179 C
Solar/Wind Harmer
3.486
219221BRL12CT1
Adder
9.781
219223BRL12CT3
Adder
9.781
959561AF2-247 GEN
Solar/Wind Harmer
0.522
20715728PEM_W1-119
Solar/Wind Harmer
0.57
20636028O CRK C1
Adder
7.531
971667AH1-334 GEN
Solar/Wind Harmer
2.905
219727YARDVSOLFA C
Solar/Wind Harmer
0.96
20635828PARLN1&2
Adder
3.399
219249CENTRALDIV C
Solar/Wind Harmer
0.04
207442AE1-156 GEN
Solar/Wind Harmer
0.735
217211CAMDEN ST C
Solar/Wind Harmer
0.024
217194REDH C
Solar/Wind Harmer
0.482
207511W3-106 GEN
Solar/Wind Harmer
0.311
971007AG2-625 GEN
Solar/Wind Harmer
2.366
20466127PORT 5CT
Adder
24.184
20674128FR_U2-059
Solar/Wind Harmer
0.167
211065PSPA IPP
Solar/Wind Harmer
0.394
957921AF2-086 GEN
Solar/Wind Harmer
0.739
232426Y1-080 FULL
Solar/Wind Harmer
0.269
232902EASTMUNI
Adder
18.342
233996TM1833_GEN
Solar/Wind Harmer
1.402
234033AF1-007_GEN
Solar/Wind Harmer
52.304
234012AE2-112_GEN
Solar/Wind Harmer
3.232
232901NORTHST
Adder
11.685
231918WEST 1
Adder
4.589
972251AH1-710 GEN
Adder
60.551
228732V1-021 C
Adder
0.219
228400MICK 1CT
Adder
13.542
219766PARADISE C
Solar/Wind Harmer
0.354
20714528FRN_Y2-051
Solar/Wind Harmer
0.309
219680HOPEWELLV C1
Solar/Wind Harmer
0.079
218440SUMMTASSOC C
Solar/Wind Harmer
0.128
217208PARK ELE C
Solar/Wind Harmer
0.025
966261AG1-495 GEN
Solar/Wind Harmer
3.335
20674628WNG_W3-110
Solar/Wind Harmer
0.38
209023WIENIPP1
Adder
8.875
209025WIENIPP3
Adder
4.43
963071AG1-156 GEN
Solar/Wind Harmer
8.125
200202DELTA2 ST
50/50
7.511
200052ROCKSP 1
50/50
3.197
200053ROCKSP 2
50/50
3.135
233940AF2-379 C
Solar/Wind Harmer
0.262
230434AG1-499 GEN
Solar/Wind Harmer
0.666
213942SCHUYLKILL
Adder
4.052
213942SCHUYLKILL
Adder
3.099
213957STHWK3-4
Adder
3.094
213957STHWK3-4
Adder
3.094
219258KINSLEYDEP C
Solar/Wind Harmer
0.365
213561DLWR9-10
Adder
3.975
213561DLWR9-10
Adder
3.04
219610FLORENCE C
Solar/Wind Harmer
1.517
963401AG1-189 GEN
Solar/Wind Harmer
2.417
971189AH1-054 GEN
Solar/Wind Harmer
1.252
20716228APLW2-078
Solar/Wind Harmer
0.912
20673828FLE_V3-070
Solar/Wind Harmer
0.464
20676128MHD_W3-029
Solar/Wind Harmer
0.472
209027LOR2_Q27
Solar/Wind Harmer
3.539
964051AG1-259 GEN
Solar/Wind Harmer
0.969
964061AG1-260 GEN
Solar/Wind Harmer
0.969
200192DELTA CT1
50/50
2.478
200054ROCKSP 3
50/50
3.234
232408W1-005 C
Solar/Wind Harmer
1.407
232917OH NUG6
Adder
12.373
232915OH NUG4
Adder
12.345
972177AH1-672 GEN
Solar/Wind Harmer
18.882
233944AB2-135 GEN
Solar/Wind Harmer
7.341
213958STHWK5-6
Adder
3.094
219907AC1-030 C
Solar/Wind Harmer
0.154
20716028EGP_W2-019
Solar/Wind Harmer
0.497
207522AF2-254 C
Solar/Wind Harmer
1.535
218428ETC SOLAR C
Solar/Wind Harmer
0.036
219908AB1-139 C
Solar/Wind Harmer
0.381
972275AH1-722 GEN
Adder
31.482
20673628F1S_V4-069
Solar/Wind Harmer
0.178
207528AF2-192 GEN
Solar/Wind Harmer
1.257
217186ESSEX_G9
Adder
3.868
217083KRNY_132
Adder
9.106
20676228FRD_X1-012
Solar/Wind Harmer
0.556
20675828AU_W4-064
Solar/Wind Harmer
0.162
20675728RH_W2-091
Solar/Wind Harmer
0.551
207484AF2-139 C O1
Solar/Wind Harmer
0.46
208909MACR G3
Adder
143.189
209010PEIP 1
Adder
0.527
946731AF1-337 GEN
Solar/Wind Harmer
0.725
200201DELTA2 CT2
50/50
4.435
233946AB2-136 GEN
Solar/Wind Harmer
5.612
232410W1-006 C
Solar/Wind Harmer
1.407
233984AB2-036 GEN
Solar/Wind Harmer
17.513
233952AC2-187 GEN
Solar/Wind Harmer
1.58
233954AC2-188 GEN
Solar/Wind Harmer
1.58
232899W1-062
Adder
13.496
233930AB2-032 GEN
Solar/Wind Harmer
1.168
233982AB2-133 GEN
Solar/Wind Harmer
6.828
213587EDDYSTN3
Adder
92.725
230511AF1-262
Solar/Wind Harmer
0.211
228307PCLP GT
Adder
13.942
228754AB1-001 C
Solar/Wind Harmer
0.159
219272CLEANLIGHT C
Solar/Wind Harmer
0.204
217081WEATEXAS C
Solar/Wind Harmer
0.085
217083KRNY_132
Adder
9.048
207471AF2-354 C
Solar/Wind Harmer
0.473
20675928HOL_W4-097
Solar/Wind Harmer
0.119
209010PEIP 1
Adder
2.898
209010PEIP 1
Adder
0.424
961541AF2-445A GEN
Solar/Wind Harmer
2.543
961431AF2-434 GEN
Solar/Wind Harmer
0.76
209130AF1-271A GEN
Solar/Wind Harmer
2.032
223402AF1-300 C
Solar/Wind Helper
0.702
200195DELTA ST
50/50
3.829
233901CHERRYDALE C
Solar/Wind Harmer
1.582
232913OH NUG2
Adder
12.262
232920IR10
Adder
4.444
970597AG2-380 GEN
Solar/Wind Harmer
5.85
231906DC3 NUG
Adder
19.617
231907DC10
Adder
4.897
972141AH1-641 GEN
Solar/Wind Harmer
3.332
213611FALLS1-3
Adder
3.817
213611FALLS1-3
Adder
3.817
20715028HAN_X4-015
Solar/Wind Harmer
0.319
207507AE2-000G3
Solar/Wind Harmer
33.561
207445AB1-138_GEN
Solar/Wind Harmer
0.611
20720628TIN_W1-124
Solar/Wind Harmer
1.029
971521AH1-258 GEN
Solar/Wind Harmer
2.784
20675528CPH_W2-050
Solar/Wind Harmer
0.574
20676428JCR_X2-075
Solar/Wind Harmer
0.337
217086KRNY_131
Adder
9.029
20675128HRM_W1-127
Solar/Wind Harmer
0.154
209029WAYMART-WD
Solar/Wind Harmer
2.117
959421AF2-233 GEN
Solar/Wind Harmer
0.723
226929AD2-058 GEN
Solar/Wind Helper
0.123
200035PCHBTM 3
50/50
25.177
234036AF2-325 C
Solar/Wind Harmer
1.29
233994AC2-023 GEN
Solar/Wind Harmer
3.777
232918OH NUG7
Adder
12.345
232905CHERITON_25
Adder
3.452
234014AF1-036_GEN
Solar/Wind Harmer
3.802
232436AB1-176 C
Solar/Wind Harmer
0.322
232910NRG_G1
Adder
12.119
233971AC1-093 C
Solar/Wind Harmer
3.57
972233AH1-701 GEN
Adder
4.815
219912AD2-042 GEN
Solar/Wind Harmer
0.891
219607WPEMNERT C
Solar/Wind Harmer
0.459
219304NAMERICA C
Solar/Wind Harmer
0.34
20635028RRCT1&2
Adder
11.725
218418LINDEN_G5
Adder
17.125
219036LINDEN_G7
Adder
16.576
217086KRNY_131
Adder
9.125
20674328GAR_V4-001
Solar/Wind Harmer
0.103
946751AF1-339 GEN
Solar/Wind Harmer
0.725
200034PCHBTM 2
50/50
25.851
200205Y1-065-CTG2
50/50
5.082
232428Y3-058 C
Solar/Wind Harmer
1.172
234015AF2-250 C
Solar/Wind Harmer
0.169
232424Y1-079 C
Solar/Wind Harmer
0.79
213589EDDYSTN4
Adder
92.75
228251CARLLS#4
Adder
0.732
228351V2-046C
Solar/Wind Harmer
2.33
230433AD2-135 GEN
Solar/Wind Harmer
0.117
219287REEVESEAST C
Solar/Wind Harmer
1.501
213535CROYDN11
Adder
11.202
214067T20SOLAR
Solar/Wind Harmer
0.273
20636128O CRK C2
Adder
6.866
207459AE1-142 C O1
Solar/Wind Harmer
1.115
20628028LAKEHURS
Adder
1.004
217197RE CRAN C
Solar/Wind Harmer
0.549
924131AB2-057 GEN
Solar/Wind Harmer
1.042
20635128RRCT3&4
Adder
11.318
20635128RRCT3&4
Adder
9.872
218419LINDEN_G6
Adder
17.125
219035LINDEN_G8
Adder
16.339
20675428EAM_W2-061
Solar/Wind Harmer
0.187
972237AH1-703 GEN
Adder
9.915
20465127PORT CT
Adder
3.631
20465527S.RDG CT
Adder
1.52
223401AF1-299 GEN
Solar/Wind Helper
0.702
233970AC1-092 C
Solar/Wind Harmer
3.76
231917EM10
Adder
3.193
213497CHSTR7-9
Adder
3.178
213497CHSTR7-9
Adder
3.178
970997AG2-616 GEN
Solar/Wind Harmer
11.105
213560DLW11-12
Adder
3.04
219222BRL12CT2
Adder
9.781
20717128DIX_Z2-102
Solar/Wind Harmer
1.411
20715828PEM_W1-120
Solar/Wind Harmer
0.57
963711AG1-223 GEN
Solar/Wind Harmer
1.549
219276PARKLANDSO C
Solar/Wind Harmer
0.482
20715228NPK_W1-113
Solar/Wind Harmer
0.444
20720528MAN_W1-024
Solar/Wind Harmer
0.262
219919AE1-041 FULL
Solar/Wind Harmer
0.04
217121ECCF
Adder
0.425
20676728BRNX1-095
Solar/Wind Harmer
0.169
20676328BVR_Y1-020
Solar/Wind Harmer
0.312
20674928WA_W3-044
Solar/Wind Harmer
0.445
971519AH1-257 GEN
Solar/Wind Harmer
2.317
207518AF1-320_GEN
Solar/Wind Harmer
3.34
20465127PORT CT
Adder
2.736
209018SUNBIPCT
Adder
5.383
20465527S.RDG CT
Adder
1.571
208835TUHI V3-051
Solar/Wind Helper
0.021
232432Z2-076 GEN
Solar/Wind Harmer
0.186
232904IR4
Adder
113.698
233968AD2-076_GEN
Solar/Wind Harmer
9.315
231919CHRIST1
Adder
6.026
231920CHRIST2
Adder
5.892
230430AE1-229_GEN
Solar/Wind Harmer
33.13
230422AE1-104_GEN1
Solar/Wind Harmer
38.875
230425AE1-104_GEN2
Solar/Wind Harmer
38.875
230407AD2-065 C
Solar/Wind Harmer
0.151
20720728JCB_W1-129
Solar/Wind Harmer
0.319
207500AE2-000G1
Solar/Wind Harmer
33.561
970025AG2-016 GEN
Solar/Wind Harmer
3.009
20714428HOW_X1-037
Solar/Wind Harmer
1.28
218449LINSOLAR C
Solar/Wind Harmer
0.997
217147KRNY_1212
Adder
8.661
217147KRNY_1212
Adder
8.507
217146KRNY_1234
Adder
8.487
217146KRNY_1234
Adder
8.429
964851AG1-348 GEN
Solar/Wind Harmer
1.259
207408W3-077 C
Solar/Wind Harmer
0.463
20462827N BANGR8
Adder
0.65
209026WIENIPP4
Adder
4.386
209054AE2-059 GEN
Solar/Wind Harmer
1.243
20486527WR_V4-052
Adder
0.618
200200DELTA2 CT1
50/50
4.435
200193DELTA CT2
50/50
2.478
200203Y1-065-STG
50/50
8.801
200055ROCKSP 4
50/50
3.179
232914OH NUG3
Adder
12.428
232916OH NUG5
Adder
12.428
233939AC1-091 C
Solar/Wind Harmer
3.76
233933AB2-153 GEN
Solar/Wind Harmer
1.577
213958STHWK5-6
Adder
3.094
219623KINSLEYBEA C
Solar/Wind Harmer
0.483
20716428NHV_W2-082
Solar/Wind Harmer
1.902
963391AG1-188 GEN
Solar/Wind Harmer
3.979
219612MATRIX C
Solar/Wind Harmer
0.188
20716928W4-060COL
Solar/Wind Harmer
0.726
217213AMBOY SO C
Solar/Wind Harmer
0.127
20673728F2S_V4-070
Solar/Wind Harmer
0.178
207510AF2-138 C
Solar/Wind Harmer
1.675
207437AD2-070 GEN
Solar/Wind Harmer
0.274
20671928W4-073
Solar/Wind Harmer
0.392
20465427SHAW CT
Adder
3.501
20633028GILCT9
Adder
25.478
209116AE2-175 GEN
Solar/Wind Harmer
3.644
970095AG2-074 GEN
Solar/Wind Harmer
5.146
961421AF2-433 GEN
Solar/Wind Harmer
0.76
209093AE2-110 GEN
Solar/Wind Harmer
1.901
209120AE2-241 GEN
Solar/Wind Harmer
2.515
946691AF1-333 GEN
Solar/Wind Harmer
0.725
946741AF1-338 GEN
Solar/Wind Harmer
0.725
226910AB2-157 C
Solar/Wind Helper
0.019
231902DC CT7
Adder
15.683
970453AG2-297 GEN
Solar/Wind Harmer
3.221
964001AG1-254 GEN
Solar/Wind Harmer
8.434
228728W1-130C
Solar/Wind Harmer
0.765
227927V4-067C
Solar/Wind Harmer
0.227
219137THOSOLAR C
Solar/Wind Harmer
1.374
219615MILLCREEK C
Solar/Wind Harmer
0.263
219224BRL12CT4
Adder
9.781
207487AE2-000G4
Solar/Wind Harmer
33.561
207497AE2-000G2
Solar/Wind Harmer
33.561
219620RIDERU C
Solar/Wind Harmer
0.058
20635928PARLN3&4
Adder
7.505
218526CNTRALGAS2 C
Solar/Wind Harmer
0.372
217167KRNY_14
Adder
9.106
971009AG2-626 GEN
Solar/Wind Harmer
1.509
961261AF2-417 GEN
Solar/Wind Harmer
0.847
212266LOR1
Solar/Wind Harmer
0.938
959431AF2-234 GEN
Solar/Wind Harmer
1.445
200204Y1-065-CTG1
50/50
5.082
233918AB1-142 GEN
Solar/Wind Harmer
1.388
228206SHRMN CT
Adder
19.293
228260V4-054C
Solar/Wind Harmer
1.191
228729W2-030 C
Solar/Wind Harmer
0.662
219686LUMSOLAR_N C
Solar/Wind Harmer
0.226
219348LDSOLAR C
Solar/Wind Harmer
0.656
213611FALLS1-3
Adder
3.817
214194N WALES4
Adder
0.913
20720428HOL_W1-112
Solar/Wind Harmer
0.355
20635828PARLN1&2
Adder
7.505
20635028RRCT1&2
Adder
11.908
218524CNTRALGAS1 C
Solar/Wind Harmer
0.371
217209CENTRL HS C
Solar/Wind Harmer
0.044
20671828STAW2-080
Solar/Wind Harmer
0.102
207439AE1-081 C O1
Solar/Wind Harmer
0.057
207530AG1-191 GEN
Solar/Wind Harmer
1.291
211065PSPA IPP
Solar/Wind Harmer
0.394
961301AF2-421 GEN
Solar/Wind Harmer
0.823
963151AG1-164 GEN
Solar/Wind Harmer
0.823
961341AF2-425 GEN
Solar/Wind Harmer
0.763
212507AE2-042_GEN
Solar/Wind Harmer
2.203
232921TASLEY2G
Adder
7.263
233950AC2-186 GEN
Solar/Wind Harmer
0.79
233972AC1-094 C
Solar/Wind Harmer
3.019
228711V2-041C
Solar/Wind Harmer
0.699
213497CHSTR7-9
Adder
3.178
219921AF1-264
Solar/Wind Harmer
0.163
219914AD2-027 C
Solar/Wind Harmer
0.672
218660EHAMPSOLAR C
Solar/Wind Harmer
0.195
213560DLW11-12
Adder
3.04
219688LUMSOLAR_S C
Solar/Wind Harmer
0.226
207454AA2-184 E
Solar/Wind Harmer
1.032
20635928PARLN3&4
Adder
3.399
217169METRODIV C
Solar/Wind Harmer
0.039
963161AG1-165 GEN
Solar/Wind Harmer
0.823
208972BECR K09
Solar/Wind Harmer
0.857
961331AF2-424 GEN
Solar/Wind Harmer
0.763
209071AE2-133 GEN
Solar/Wind Harmer
1.223
208835TUHI V3-051
Solar/Wind Helper
0.021
20714928UPF_X1-085
Solar/Wind Harmer
0.431
219114HARTZY_C
Solar/Wind Harmer
0.884
219918AC2-009 C
Solar/Wind Harmer
0.027
20674528F3S_W2-016
Solar/Wind Harmer
1.362
209025WIENIPP3
Adder
4.341
209142AF1-226 GEN
Solar/Wind Harmer
4.401
205941AD2-115 GEN
Solar/Wind Harmer
0.608
227287AC2-120 GEN
Solar/Wind Helper
0.447
G-007ALTFEXP_G-007A->PJM
CMTX
51.785
CBM NorthLTFEXP_CBM-N->PJM
CBM
68.166
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.729
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.619
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.462
VTFLTFEXP_VFT->PJM
CMTX
133.231
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.637
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
17.523

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_04_P71_001014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_04_P71_001014_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.23 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:3809.42
MW Contribution:
9.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232926CRISFLD1
Adder
2.563
231940T-011
Adder
0.974
234041AC1-190 GEN
Solar/Wind Harmer
11.66
228201CARL#2CT
Adder
7.495
228200CARL#1CT
Adder
7.128
219904AC1-010 C
Solar/Wind Harmer
0.396
219906AC1-017 C
Solar/Wind Harmer
0.23
213815MOSER1-3
Adder
3.619
213815MOSER1-3
Adder
3.619
20720828JCB_W4-025
Solar/Wind Harmer
0.46
20714828MDF_W3-079
Solar/Wind Harmer
0.305
233973AC2-185 C
Solar/Wind Harmer
7.095
970695AG2-447 GEN
Solar/Wind Harmer
4.694
233987AB2-037 GEN
Solar/Wind Harmer
14.851
233923SMA
Solar/Wind Harmer
4.771
233997TMININ_4.2
Solar/Wind Harmer
1.301
232907VN8
Adder
39.19
232417X3-008 C
Solar/Wind Harmer
1.464
233935AB2-179 C
Solar/Wind Harmer
3.091
219221BRL12CT1
Adder
9.177
219223BRL12CT3
Adder
9.177
20715728PEM_W1-119
Solar/Wind Harmer
0.541
959561AF2-247 GEN
Solar/Wind Harmer
0.492
20636028O CRK C1
Adder
7.163
971667AH1-334 GEN
Solar/Wind Harmer
2.766
219727YARDVSOLFA C
Solar/Wind Harmer
0.91
20635828PARLN1&2
Adder
3.265
219249CENTRALDIV C
Solar/Wind Harmer
0.038
207442AE1-156 GEN
Solar/Wind Harmer
0.71
217211CAMDEN ST C
Solar/Wind Harmer
0.023
217194REDH C
Solar/Wind Harmer
0.466
207511W3-106 GEN
Solar/Wind Harmer
0.304
971007AG2-625 GEN
Solar/Wind Harmer
2.328
20466127PORT 5CT
Adder
23.797
20674128FR_U2-059
Solar/Wind Harmer
0.165
211065PSPA IPP
Solar/Wind Harmer
0.389
957921AF2-086 GEN
Solar/Wind Harmer
0.73
219817TRENTONSOL C
Solar/Wind Harmer
1.092
20641628MLH_W1-032
Solar/Wind Harmer
0.29
20742028HF_AC1-207
Solar/Wind Harmer
0.773
218438BLK ROCK C
Solar/Wind Harmer
0.133
200202DELTA2 ST
50/50
7.421
200052ROCKSP 1
50/50
3.136
200053ROCKSP 2
50/50
3.075
233940AF2-379 C
Solar/Wind Harmer
0.243
230434AG1-499 GEN
Solar/Wind Harmer
0.624
219258KINSLEYDEP C
Solar/Wind Harmer
0.34
213942SCHUYLKILL
Adder
3.671
213942SCHUYLKILL
Adder
2.807
213957STHWK3-4
Adder
2.807
213957STHWK3-4
Adder
2.807
213561DLWR9-10
Adder
3.655
213561DLWR9-10
Adder
2.795
219610FLORENCE C
Solar/Wind Harmer
1.424
963401AG1-189 GEN
Solar/Wind Harmer
2.3
971189AH1-054 GEN
Solar/Wind Harmer
1.191
20716228APLW2-078
Solar/Wind Harmer
0.873
20673828FLE_V3-070
Solar/Wind Harmer
0.447
20676128MHD_W3-029
Solar/Wind Harmer
0.456
209027LOR2_Q27
Solar/Wind Harmer
3.497
208862AG1-362 C
Solar/Wind Harmer
0.591
964051AG1-259 GEN
Solar/Wind Harmer
0.958
964061AG1-260 GEN
Solar/Wind Harmer
0.958
200201DELTA2 CT2
50/50
4.382
232899W1-062
Adder
12.57
232410W1-006 C
Solar/Wind Harmer
1.305
200195DELTA ST
50/50
3.783
232920IR10
Adder
4.129
233901CHERRYDALE C
Solar/Wind Harmer
1.469
232913OH NUG2
Adder
11.38
231906DC3 NUG
Adder
17.944
231907DC10
Adder
4.48
970597AG2-380 GEN
Solar/Wind Harmer
5.338
972141AH1-641 GEN
Solar/Wind Harmer
3.125
20715028HAN_X4-015
Solar/Wind Harmer
0.303
213611FALLS1-3
Adder
3.59
213611FALLS1-3
Adder
3.59
207507AE2-000G3
Solar/Wind Harmer
31.924
200035PCHBTM 3
50/50
24.86
200194DELTA CT3
50/50
2.449
233970AC1-092 C
Solar/Wind Harmer
3.512
232900DEMECSMY
Adder
12.056
232404W1-003 C
Solar/Wind Harmer
1.305
233998TM1NIN_3.36
Solar/Wind Harmer
1.301
232919VN10
Adder
3.66
231917EM10
Adder
2.87
970997AG2-616 GEN
Solar/Wind Harmer
10.417
213497CHSTR7-9
Adder
2.845
232901NORTHST
Adder
10.904
234033AF1-007_GEN
Solar/Wind Harmer
48.601
233996TM1833_GEN
Solar/Wind Harmer
1.301
232426Y1-080 FULL
Solar/Wind Harmer
0.249
232902EASTMUNI
Adder
16.888
234012AE2-112_GEN
Solar/Wind Harmer
2.949
972251AH1-710 GEN
Adder
57.346
231918WEST 1
Adder
4.124
228732V1-021 C
Adder
0.207
228400MICK 1CT
Adder
12.634
219766PARADISE C
Solar/Wind Harmer
0.33
20714528FRN_Y2-051
Solar/Wind Harmer
0.294
219680HOPEWELLV C1
Solar/Wind Harmer
0.075
218440SUMMTASSOC C
Solar/Wind Harmer
0.124
217208PARK ELE C
Solar/Wind Harmer
0.024
966261AG1-495 GEN
Solar/Wind Harmer
3.255
232904IR4
Adder
105.649
232432Z2-076 GEN
Solar/Wind Harmer
0.172
233968AD2-076_GEN
Solar/Wind Harmer
8.501
231919CHRIST1
Adder
5.425
231920CHRIST2
Adder
5.305
230422AE1-104_GEN1
Solar/Wind Harmer
36.639
230425AE1-104_GEN2
Solar/Wind Harmer
36.639
230430AE1-229_GEN
Solar/Wind Harmer
31.08
233946AB2-136 GEN
Solar/Wind Harmer
5.195
233952AC2-187 GEN
Solar/Wind Harmer
1.465
233954AC2-188 GEN
Solar/Wind Harmer
1.465
233984AB2-036 GEN
Solar/Wind Harmer
16.053
233930AB2-032 GEN
Solar/Wind Harmer
1.061
233982AB2-133 GEN
Solar/Wind Harmer
6.2
230511AF1-262
Solar/Wind Harmer
0.198
228754AB1-001 C
Solar/Wind Harmer
0.15
228307PCLP GT
Adder
13.029
219272CLEANLIGHT C
Solar/Wind Harmer
0.192
213587EDDYSTN3
Adder
82.967
217081WEATEXAS C
Solar/Wind Harmer
0.082
217083KRNY_132
Adder
8.753
207471AF2-354 C
Solar/Wind Harmer
0.465
20675928HOL_W4-097
Solar/Wind Harmer
0.117
209010PEIP 1
Adder
2.848
209010PEIP 1
Adder
0.417
961541AF2-445A GEN
Solar/Wind Harmer
2.513
961431AF2-434 GEN
Solar/Wind Harmer
0.751
209130AF1-271A GEN
Solar/Wind Harmer
2.009
223402AF1-300 C
Solar/Wind Helper
0.631
213497CHSTR7-9
Adder
2.845
213560DLW11-12
Adder
2.795
219222BRL12CT2
Adder
9.177
20717128DIX_Z2-102
Solar/Wind Harmer
1.339
20715828PEM_W1-120
Solar/Wind Harmer
0.541
963711AG1-223 GEN
Solar/Wind Harmer
1.478
219276PARKLANDSO C
Solar/Wind Harmer
0.458
20715228NPK_W1-113
Solar/Wind Harmer
0.425
20720528MAN_W1-024
Solar/Wind Harmer
0.251
219919AE1-041 FULL
Solar/Wind Harmer
0.039
217121ECCF
Adder
0.412
20676728BRNX1-095
Solar/Wind Harmer
0.165
20676328BVR_Y1-020
Solar/Wind Harmer
0.305
20674928WA_W3-044
Solar/Wind Harmer
0.438
971519AH1-257 GEN
Solar/Wind Harmer
2.282
207518AF1-320_GEN
Solar/Wind Harmer
3.296
20465127PORT CT
Adder
2.696
20465527S.RDG CT
Adder
2.051
209018SUNBIPCT
Adder
5.322
208835TUHI V3-051
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Harmer
3.335
232918OH NUG7
Adder
11.457
232905CHERITON_25
Adder
3.204
233994AC2-023 GEN
Solar/Wind Harmer
3.503
234036AF2-325 C
Solar/Wind Harmer
1.194
232910NRG_G1
Adder
11.179
234014AF1-036_GEN
Solar/Wind Harmer
3.47
232436AB1-176 C
Solar/Wind Harmer
0.293
972233AH1-701 GEN
Adder
4.494
219912AD2-042 GEN
Solar/Wind Harmer
0.831
219607WPEMNERT C
Solar/Wind Harmer
0.431
219304NAMERICA C
Solar/Wind Harmer
0.319
20635028RRCT1&2
Adder
11.271
218418LINDEN_G5
Adder
16.503
219036LINDEN_G7
Adder
15.995
217086KRNY_131
Adder
8.828
20674328GAR_V4-001
Solar/Wind Harmer
0.101
946751AF1-339 GEN
Solar/Wind Harmer
0.717
207445AB1-138_GEN
Solar/Wind Harmer
0.582
20720628TIN_W1-124
Solar/Wind Harmer
0.984
971521AH1-258 GEN
Solar/Wind Harmer
2.666
20675528CPH_W2-050
Solar/Wind Harmer
0.552
20676428JCR_X2-075
Solar/Wind Harmer
0.326
217086KRNY_131
Adder
8.734
20675128HRM_W1-127
Solar/Wind Harmer
0.152
209029WAYMART-WD
Solar/Wind Harmer
2.08
959421AF2-233 GEN
Solar/Wind Harmer
0.715
226929AD2-058 GEN
Solar/Wind Helper
0.117
200204Y1-065-CTG1
50/50
4.985
233918AB1-142 GEN
Solar/Wind Harmer
1.261
228206SHRMN CT
Adder
18.159
228260V4-054C
Solar/Wind Harmer
1.119
228729W2-030 C
Solar/Wind Harmer
0.624
219686LUMSOLAR_N C
Solar/Wind Harmer
0.212
219348LDSOLAR C
Solar/Wind Harmer
0.615
213611FALLS1-3
Adder
3.59
214194N WALES4
Adder
0.859
20720428HOL_W1-112
Solar/Wind Harmer
0.34
20635828PARLN1&2
Adder
7.209
20635028RRCT1&2
Adder
11.447
218524CNTRALGAS1 C
Solar/Wind Harmer
0.357
217209CENTRL HS C
Solar/Wind Harmer
0.042
20671828STAW2-080
Solar/Wind Harmer
0.099
207439AE1-081 C O1
Solar/Wind Harmer
0.055
207530AG1-191 GEN
Solar/Wind Harmer
1.263
211065PSPA IPP
Solar/Wind Harmer
0.389
961301AF2-421 GEN
Solar/Wind Harmer
0.812
963151AG1-164 GEN
Solar/Wind Harmer
0.812
961341AF2-425 GEN
Solar/Wind Harmer
0.754
212507AE2-042_GEN
Solar/Wind Harmer
2.178
230407AD2-065 C
Solar/Wind Harmer
0.142
20720728JCB_W1-129
Solar/Wind Harmer
0.303
207500AE2-000G1
Solar/Wind Harmer
31.924
970025AG2-016 GEN
Solar/Wind Harmer
2.863
20714428HOW_X1-037
Solar/Wind Harmer
1.224
218449LINSOLAR C
Solar/Wind Harmer
0.962
217147KRNY_1212
Adder
8.379
217147KRNY_1212
Adder
8.229
217146KRNY_1234
Adder
8.211
217146KRNY_1234
Adder
8.155
964851AG1-348 GEN
Solar/Wind Harmer
1.239
207408W3-077 C
Solar/Wind Harmer
0.457
20462827N BANGR8
Adder
0.642
209026WIENIPP4
Adder
4.329
20486527WR_V4-052
Adder
0.793
209054AE2-059 GEN
Solar/Wind Harmer
1.228
20674628WNG_W3-110
Solar/Wind Harmer
0.371
209023WIENIPP1
Adder
8.76
209025WIENIPP3
Adder
4.373
963071AG1-156 GEN
Solar/Wind Harmer
8.001
972260AH1-715 GEN1
Adder
13.215
200200DELTA2 CT1
50/50
4.382
200193DELTA CT2
50/50
2.449
200203Y1-065-STG
50/50
8.633
200055ROCKSP 4
50/50
3.118
233939AC1-091 C
Solar/Wind Harmer
3.512
232914OH NUG3
Adder
11.534
232916OH NUG5
Adder
11.534
233933AB2-153 GEN
Solar/Wind Harmer
1.433
219623KINSLEYBEA C
Solar/Wind Harmer
0.451
213958STHWK5-6
Adder
2.807
20716428NHV_W2-082
Solar/Wind Harmer
1.805
963391AG1-188 GEN
Solar/Wind Harmer
3.787
219612MATRIX C
Solar/Wind Harmer
0.18
20716928W4-060COL
Solar/Wind Harmer
0.696
217213AMBOY SO C
Solar/Wind Harmer
0.122
20673728F2S_V4-070
Solar/Wind Harmer
0.171
207510AF2-138 C
Solar/Wind Harmer
1.637
207437AD2-070 GEN
Solar/Wind Harmer
0.271
20671928W4-073
Solar/Wind Harmer
0.388
20633028GILCT9
Adder
25.303
20465427SHAW CT
Adder
3.442
209116AE2-175 GEN
Solar/Wind Harmer
3.595
970095AG2-074 GEN
Solar/Wind Harmer
5.068
961421AF2-433 GEN
Solar/Wind Harmer
0.751
209093AE2-110 GEN
Solar/Wind Harmer
1.878
209120AE2-241 GEN
Solar/Wind Harmer
2.485
946691AF1-333 GEN
Solar/Wind Harmer
0.717
946741AF1-338 GEN
Solar/Wind Harmer
0.717
226910AB2-157 C
Solar/Wind Helper
0.018
200192DELTA CT1
50/50
2.449
200054ROCKSP 3
50/50
3.173
972177AH1-672 GEN
Solar/Wind Harmer
17.548
232408W1-005 C
Solar/Wind Harmer
1.305
232917OH NUG6
Adder
11.483
232915OH NUG4
Adder
11.457
233944AB2-135 GEN
Solar/Wind Harmer
6.685
219907AC1-030 C
Solar/Wind Harmer
0.144
213958STHWK5-6
Adder
2.807
20716028EGP_W2-019
Solar/Wind Harmer
0.471
207522AF2-254 C
Solar/Wind Harmer
1.457
218428ETC SOLAR C
Solar/Wind Harmer
0.035
219908AB1-139 C
Solar/Wind Harmer
0.367
972275AH1-722 GEN
Adder
30.338
20673628F1S_V4-069
Solar/Wind Harmer
0.171
207528AF2-192 GEN
Solar/Wind Harmer
1.214
217186ESSEX_G9
Adder
3.741
217083KRNY_132
Adder
8.809
20676228FRD_X1-012
Solar/Wind Harmer
0.543
20675828AU_W4-064
Solar/Wind Harmer
0.158
20675728RH_W2-091
Solar/Wind Harmer
0.544
207484AF2-139 C O1
Solar/Wind Harmer
0.455
208909MACR G3
Adder
141.49
209010PEIP 1
Adder
0.518
946731AF1-337 GEN
Solar/Wind Harmer
0.717
232912OH NUG1
Adder
11.534
971195AH1-057 GEN
Solar/Wind Harmer
1.272
233955AB2-172 GEN
Solar/Wind Harmer
6.507
232813VAUGHN
Adder
0.764
231902DC CT7
Adder
14.345
233915AB1-141 GEN
Solar/Wind Harmer
1.261
970453AG2-297 GEN
Solar/Wind Harmer
3.034
964001AG1-254 GEN
Solar/Wind Harmer
7.902
228728W1-130C
Solar/Wind Harmer
0.718
227927V4-067C
Solar/Wind Harmer
0.214
219137THOSOLAR C
Solar/Wind Harmer
1.28
219615MILLCREEK C
Solar/Wind Harmer
0.246
219224BRL12CT4
Adder
9.177
207487AE2-000G4
Solar/Wind Harmer
31.924
207497AE2-000G2
Solar/Wind Harmer
31.924
219620RIDERU C
Solar/Wind Harmer
0.055
20635928PARLN3&4
Adder
7.209
218526CNTRALGAS2 C
Solar/Wind Harmer
0.358
217167KRNY_14
Adder
8.809
971009AG2-626 GEN
Solar/Wind Harmer
1.485
961261AF2-417 GEN
Solar/Wind Harmer
0.833
212266LOR1
Solar/Wind Harmer
0.927
959431AF2-234 GEN
Solar/Wind Harmer
1.429
200034PCHBTM 2
50/50
25.537
200205Y1-065-CTG2
50/50
4.985
234015AF2-250 C
Solar/Wind Harmer
0.157
232428Y3-058 C
Solar/Wind Harmer
1.087
232424Y1-079 C
Solar/Wind Harmer
0.724
228251CARLLS#4
Adder
0.688
230433AD2-135 GEN
Solar/Wind Harmer
0.11
228351V2-046C
Solar/Wind Harmer
2.184
219287REEVESEAST C
Solar/Wind Harmer
1.412
213589EDDYSTN4
Adder
82.978
213535CROYDN11
Adder
10.504
214067T20SOLAR
Solar/Wind Harmer
0.257
20636128O CRK C2
Adder
6.531
207459AE1-142 C O1
Solar/Wind Harmer
1.062
20628028LAKEHURS
Adder
0.956
217197RE CRAN C
Solar/Wind Harmer
0.526
924131AB2-057 GEN
Solar/Wind Harmer
1
20635128RRCT3&4
Adder
10.88
20635128RRCT3&4
Adder
9.49
218419LINDEN_G6
Adder
16.503
219035LINDEN_G8
Adder
15.767
20675428EAM_W2-061
Solar/Wind Harmer
0.18
972237AH1-703 GEN
Adder
9.591
20465127PORT CT
Adder
3.578
20465527S.RDG CT
Adder
1.984
223401AF1-299 GEN
Solar/Wind Helper
0.631
233972AC1-094 C
Solar/Wind Harmer
2.82
232921TASLEY2G
Adder
6.741
233950AC2-186 GEN
Solar/Wind Harmer
0.732
228711V2-041C
Solar/Wind Harmer
0.658
218660EHAMPSOLAR C
Solar/Wind Harmer
0.184
219921AF1-264
Solar/Wind Harmer
0.152
219688LUMSOLAR_S C
Solar/Wind Harmer
0.212
213497CHSTR7-9
Adder
2.845
219914AD2-027 C
Solar/Wind Harmer
0.627
213560DLW11-12
Adder
2.795
207454AA2-184 E
Solar/Wind Harmer
0.988
20635928PARLN3&4
Adder
3.265
217169METRODIV C
Solar/Wind Harmer
0.038
963161AG1-165 GEN
Solar/Wind Harmer
0.812
208972BECR K09
Solar/Wind Harmer
0.844
961331AF2-424 GEN
Solar/Wind Harmer
0.754
209071AE2-133 GEN
Solar/Wind Harmer
1.209
208835TUHI V3-051
Solar/Wind Helper
0.023
972261AH1-715 GEN2
Adder
15.311
217202FBANKSOLAR C
Solar/Wind Harmer
0.07
217201HACKENSOLA C
Solar/Wind Harmer
0.069
217206BARNGR HS C
Solar/Wind Harmer
0.029
217204WCALDSOLAR C
Solar/Wind Harmer
0.069
20674828DL_W4-046
Solar/Wind Harmer
0.588
20634528N27_Y2-018
Solar/Wind Harmer
0.244
232434Z2-077 GEN
Solar/Wind Harmer
0.327
232406W1-004 FULL
Solar/Wind Harmer
1.305
233964AF2-378 GEN
Solar/Wind Harmer
0.166
232422X3-066 FULL
Solar/Wind Harmer
0.32
230415AB2-049 C
Solar/Wind Harmer
0.205
219291REEVESSOUT C
Solar/Wind Harmer
0.063
219236SOUTHERNHQ C
Solar/Wind Harmer
0.07
213815MOSER1-3
Adder
3.619
20714928UPF_X1-085
Solar/Wind Harmer
0.41
219114HARTZY_C
Solar/Wind Harmer
0.836
219918AC2-009 C
Solar/Wind Harmer
0.025
20674528F3S_W2-016
Solar/Wind Harmer
1.322
209025WIENIPP3
Adder
4.284
209142AF1-226 GEN
Solar/Wind Harmer
4.349
205941AD2-115 GEN
Solar/Wind Harmer
0.676
227287AC2-120 GEN
Solar/Wind Helper
0.427
G-007ALTFEXP_G-007A->PJM
CMTX
49.782
CBM NorthLTFEXP_CBM-N->PJM
CBM
66.182
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.566
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.109
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.265
VTFLTFEXP_VFT->PJM
CMTX
128.779
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.521
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.753

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_05_P71_000906_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_05_P71_000906_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.19 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:3771.64
MW Contribution:
9.57
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
233973AC2-185 C
Solar/Wind Harmer
7.039
970695AG2-447 GEN
Solar/Wind Harmer
4.656
233987AB2-037 GEN
Solar/Wind Harmer
14.725
233923SMA
Solar/Wind Harmer
4.732
233997TMININ_4.2
Solar/Wind Harmer
1.29
232907VN8
Adder
38.859
232417X3-008 C
Solar/Wind Harmer
1.452
233935AB2-179 C
Solar/Wind Harmer
3.057
219221BRL12CT1
Adder
9.118
219223BRL12CT3
Adder
9.118
20715728PEM_W1-119
Solar/Wind Harmer
0.538
20636028O CRK C1
Adder
7.126
959561AF2-247 GEN
Solar/Wind Harmer
0.489
971667AH1-334 GEN
Solar/Wind Harmer
2.752
219727YARDVSOLFA C
Solar/Wind Harmer
0.905
20635828PARLN1&2
Adder
3.253
219249CENTRALDIV C
Solar/Wind Harmer
0.038
207442AE1-156 GEN
Solar/Wind Harmer
0.707
217211CAMDEN ST C
Solar/Wind Harmer
0.023
217194REDH C
Solar/Wind Harmer
0.465
207511W3-106 GEN
Solar/Wind Harmer
0.303
200202DELTA2 ST
50/50
7.377
200052ROCKSP 1
50/50
3.117
200053ROCKSP 2
50/50
3.056
233940AF2-379 C
Solar/Wind Harmer
0.241
230434AG1-499 GEN
Solar/Wind Harmer
0.62
971007AG2-625 GEN
Solar/Wind Harmer
2.325
20466127PORT 5CT
Adder
23.789
20674128FR_U2-059
Solar/Wind Harmer
0.165
200201DELTA2 CT2
50/50
4.356
232899W1-062
Adder
12.467
232410W1-006 C
Solar/Wind Harmer
1.295
233946AB2-136 GEN
Solar/Wind Harmer
5.151
233952AC2-187 GEN
Solar/Wind Harmer
1.453
233954AC2-188 GEN
Solar/Wind Harmer
1.453
233984AB2-036 GEN
Solar/Wind Harmer
15.908
233930AB2-032 GEN
Solar/Wind Harmer
1.051
233982AB2-133 GEN
Solar/Wind Harmer
6.14
230511AF1-262
Solar/Wind Harmer
0.197
228754AB1-001 C
Solar/Wind Harmer
0.149
228307PCLP GT
Adder
12.936
219272CLEANLIGHT C
Solar/Wind Harmer
0.191
213587EDDYSTN3
Adder
82.138
217081WEATEXAS C
Solar/Wind Harmer
0.082
217083KRNY_132
Adder
8.73
207471AF2-354 C
Solar/Wind Harmer
0.465
20675928HOL_W4-097
Solar/Wind Harmer
0.117
209010PEIP 1
Adder
2.868
209010PEIP 1
Adder
0.42
961541AF2-445A GEN
Solar/Wind Harmer
2.543
961431AF2-434 GEN
Solar/Wind Harmer
0.762
209130AF1-271A GEN
Solar/Wind Harmer
2.045
223402AF1-300 C
Solar/Wind Helper
0.683
200194DELTA CT3
50/50
2.434
233970AC1-092 C
Solar/Wind Harmer
3.484
232900DEMECSMY
Adder
11.959
232404W1-003 C
Solar/Wind Harmer
1.295
233998TM1NIN_3.36
Solar/Wind Harmer
1.29
232919VN10
Adder
3.629
231917EM10
Adder
2.841
970997AG2-616 GEN
Solar/Wind Harmer
10.344
213497CHSTR7-9
Adder
2.817
213497CHSTR7-9
Adder
2.817
219222BRL12CT2
Adder
9.118
213560DLW11-12
Adder
2.772
20717128DIX_Z2-102
Solar/Wind Harmer
1.332
20715828PEM_W1-120
Solar/Wind Harmer
0.538
963711AG1-223 GEN
Solar/Wind Harmer
1.471
219276PARKLANDSO C
Solar/Wind Harmer
0.456
20715228NPK_W1-113
Solar/Wind Harmer
0.423
20720528MAN_W1-024
Solar/Wind Harmer
0.25
219919AE1-041 FULL
Solar/Wind Harmer
0.039
217121ECCF
Adder
0.41
20676728BRNX1-095
Solar/Wind Harmer
0.164
20676328BVR_Y1-020
Solar/Wind Harmer
0.304
20674928WA_W3-044
Solar/Wind Harmer
0.437
971519AH1-257 GEN
Solar/Wind Harmer
2.279
207518AF1-320_GEN
Solar/Wind Harmer
3.291
20465127PORT CT
Adder
2.695
209018SUNBIPCT
Adder
5.417
20465527S.RDG CT
Adder
1.939
200035PCHBTM 3
50/50
24.719
233971AC1-093 C
Solar/Wind Harmer
3.308
232918OH NUG7
Adder
11.362
232905CHERITON_25
Adder
3.177
233994AC2-023 GEN
Solar/Wind Harmer
3.474
234036AF2-325 C
Solar/Wind Harmer
1.183
232910NRG_G1
Adder
11.082
234014AF1-036_GEN
Solar/Wind Harmer
3.437
232436AB1-176 C
Solar/Wind Harmer
0.29
972233AH1-701 GEN
Adder
4.462
219912AD2-042 GEN
Solar/Wind Harmer
0.825
219607WPEMNERT C
Solar/Wind Harmer
0.428
219304NAMERICA C
Solar/Wind Harmer
0.317
20635028RRCT1&2
Adder
11.229
218418LINDEN_G5
Adder
16.449
219036LINDEN_G7
Adder
15.946
217086KRNY_131
Adder
8.805
20674328GAR_V4-001
Solar/Wind Harmer
0.101
946751AF1-339 GEN
Solar/Wind Harmer
0.73
200195DELTA ST
50/50
3.76
232920IR10
Adder
4.095
233901CHERRYDALE C
Solar/Wind Harmer
1.456
232913OH NUG2
Adder
11.285
231906DC3 NUG
Adder
17.779
231907DC10
Adder
4.439
970597AG2-380 GEN
Solar/Wind Harmer
5.288
972141AH1-641 GEN
Solar/Wind Harmer
3.103
20715028HAN_X4-015
Solar/Wind Harmer
0.301
213611FALLS1-3
Adder
3.567
213611FALLS1-3
Adder
3.567
207507AE2-000G3
Solar/Wind Harmer
31.757
207445AB1-138_GEN
Solar/Wind Harmer
0.579
20720628TIN_W1-124
Solar/Wind Harmer
0.98
971521AH1-258 GEN
Solar/Wind Harmer
2.655
20675528CPH_W2-050
Solar/Wind Harmer
0.55
20676428JCR_X2-075
Solar/Wind Harmer
0.325
217086KRNY_131
Adder
8.711
20675128HRM_W1-127
Solar/Wind Harmer
0.152
209029WAYMART-WD
Solar/Wind Harmer
2.095
959421AF2-233 GEN
Solar/Wind Harmer
0.727
226929AD2-058 GEN
Solar/Wind Helper
0.121
200204Y1-065-CTG1
50/50
4.954
233918AB1-142 GEN
Solar/Wind Harmer
1.249
228206SHRMN CT
Adder
18.037
228260V4-054C
Solar/Wind Harmer
1.111
228729W2-030 C
Solar/Wind Harmer
0.62
219686LUMSOLAR_N C
Solar/Wind Harmer
0.211
219348LDSOLAR C
Solar/Wind Harmer
0.611
213611FALLS1-3
Adder
3.567
214194N WALES4
Adder
0.853
20720428HOL_W1-112
Solar/Wind Harmer
0.339
20635828PARLN1&2
Adder
7.181
20635028RRCT1&2
Adder
11.405
218524CNTRALGAS1 C
Solar/Wind Harmer
0.356
217209CENTRL HS C
Solar/Wind Harmer
0.042
20671828STAW2-080
Solar/Wind Harmer
0.099
207439AE1-081 C O1
Solar/Wind Harmer
0.055
207530AG1-191 GEN
Solar/Wind Harmer
1.261
211065PSPA IPP
Solar/Wind Harmer
0.39
961301AF2-421 GEN
Solar/Wind Harmer
0.819
963151AG1-164 GEN
Solar/Wind Harmer
0.819
961341AF2-425 GEN
Solar/Wind Harmer
0.764
212507AE2-042_GEN
Solar/Wind Harmer
2.213
232904IR4
Adder
104.776
232432Z2-076 GEN
Solar/Wind Harmer
0.171
233968AD2-076_GEN
Solar/Wind Harmer
8.422
231919CHRIST1
Adder
5.371
231920CHRIST2
Adder
5.251
230422AE1-104_GEN1
Solar/Wind Harmer
36.397
230425AE1-104_GEN2
Solar/Wind Harmer
36.397
230430AE1-229_GEN
Solar/Wind Harmer
30.864
230407AD2-065 C
Solar/Wind Harmer
0.141
20720728JCB_W1-129
Solar/Wind Harmer
0.301
207500AE2-000G1
Solar/Wind Harmer
31.757
970025AG2-016 GEN
Solar/Wind Harmer
2.848
20714428HOW_X1-037
Solar/Wind Harmer
1.218
218449LINSOLAR C
Solar/Wind Harmer
0.959
217147KRNY_1212
Adder
8.357
217147KRNY_1212
Adder
8.208
217146KRNY_1234
Adder
8.189
217146KRNY_1234
Adder
8.133
964851AG1-348 GEN
Solar/Wind Harmer
1.237
207408W3-077 C
Solar/Wind Harmer
0.456
20462827N BANGR8
Adder
0.641
209026WIENIPP4
Adder
4.362
209054AE2-059 GEN
Solar/Wind Harmer
1.249
20486527WR_V4-052
Adder
0.756
232901NORTHST
Adder
10.817
234033AF1-007_GEN
Solar/Wind Harmer
48.199
233996TM1833_GEN
Solar/Wind Harmer
1.29
232426Y1-080 FULL
Solar/Wind Harmer
0.247
232902EASTMUNI
Adder
16.739
972251AH1-710 GEN
Adder
56.95
234012AE2-112_GEN
Solar/Wind Harmer
2.922
231918WEST 1
Adder
4.082
228732V1-021 C
Adder
0.205
228400MICK 1CT
Adder
12.543
219766PARADISE C
Solar/Wind Harmer
0.328
20714528FRN_Y2-051
Solar/Wind Harmer
0.293
219680HOPEWELLV C1
Solar/Wind Harmer
0.075
218440SUMMTASSOC C
Solar/Wind Harmer
0.123
217208PARK ELE C
Solar/Wind Harmer
0.024
966261AG1-495 GEN
Solar/Wind Harmer
3.245
20674628WNG_W3-110
Solar/Wind Harmer
0.371
209023WIENIPP1
Adder
8.828
209025WIENIPP3
Adder
4.407
963071AG1-156 GEN
Solar/Wind Harmer
8.062
200200DELTA2 CT1
50/50
4.356
200193DELTA CT2
50/50
2.434
200203Y1-065-STG
50/50
8.58
200055ROCKSP 4
50/50
3.099
233939AC1-091 C
Solar/Wind Harmer
3.484
232914OH NUG3
Adder
11.438
232916OH NUG5
Adder
11.438
233933AB2-153 GEN
Solar/Wind Harmer
1.419
219623KINSLEYBEA C
Solar/Wind Harmer
0.448
213958STHWK5-6
Adder
2.781
20716428NHV_W2-082
Solar/Wind Harmer
1.795
963391AG1-188 GEN
Solar/Wind Harmer
3.767
219612MATRIX C
Solar/Wind Harmer
0.179
20716928W4-060COL
Solar/Wind Harmer
0.693
217213AMBOY SO C
Solar/Wind Harmer
0.121
20673728F2S_V4-070
Solar/Wind Harmer
0.171
207510AF2-138 C
Solar/Wind Harmer
1.635
207437AD2-070 GEN
Solar/Wind Harmer
0.27
20671928W4-073
Solar/Wind Harmer
0.387
20633028GILCT9
Adder
25.259
20465427SHAW CT
Adder
3.444
209116AE2-175 GEN
Solar/Wind Harmer
3.601
970095AG2-074 GEN
Solar/Wind Harmer
5.106
961421AF2-433 GEN
Solar/Wind Harmer
0.762
209093AE2-110 GEN
Solar/Wind Harmer
1.904
209120AE2-241 GEN
Solar/Wind Harmer
2.519
946691AF1-333 GEN
Solar/Wind Harmer
0.73
946741AF1-338 GEN
Solar/Wind Harmer
0.73
226910AB2-157 C
Solar/Wind Helper
0.019
200192DELTA CT1
50/50
2.434
200054ROCKSP 3
50/50
3.153
972177AH1-672 GEN
Solar/Wind Harmer
17.404
232408W1-005 C
Solar/Wind Harmer
1.295
232917OH NUG6
Adder
11.387
232915OH NUG4
Adder
11.362
233944AB2-135 GEN
Solar/Wind Harmer
6.622
219907AC1-030 C
Solar/Wind Harmer
0.143
213958STHWK5-6
Adder
2.781
20716028EGP_W2-019
Solar/Wind Harmer
0.468
207522AF2-254 C
Solar/Wind Harmer
1.449
218428ETC SOLAR C
Solar/Wind Harmer
0.034
219908AB1-139 C
Solar/Wind Harmer
0.366
972275AH1-722 GEN
Adder
30.239
20673628F1S_V4-069
Solar/Wind Harmer
0.171
207528AF2-192 GEN
Solar/Wind Harmer
1.21
217186ESSEX_G9
Adder
3.732
217083KRNY_132
Adder
8.786
20676228FRD_X1-012
Solar/Wind Harmer
0.543
20675828AU_W4-064
Solar/Wind Harmer
0.158
20675728RH_W2-091
Solar/Wind Harmer
0.543
207484AF2-139 C O1
Solar/Wind Harmer
0.454
208909MACR G3
Adder
141.493
209010PEIP 1
Adder
0.522
946731AF1-337 GEN
Solar/Wind Harmer
0.73
219258KINSLEYDEP C
Solar/Wind Harmer
0.338
213957STHWK3-4
Adder
2.781
213957STHWK3-4
Adder
2.781
213942SCHUYLKILL
Adder
3.637
213942SCHUYLKILL
Adder
2.781
219610FLORENCE C
Solar/Wind Harmer
1.414
213561DLWR9-10
Adder
3.625
213561DLWR9-10
Adder
2.772
963401AG1-189 GEN
Solar/Wind Harmer
2.288
971189AH1-054 GEN
Solar/Wind Harmer
1.185
20716228APLW2-078
Solar/Wind Harmer
0.869
20673828FLE_V3-070
Solar/Wind Harmer
0.445
20676128MHD_W3-029
Solar/Wind Harmer
0.454
209027LOR2_Q27
Solar/Wind Harmer
3.54
964051AG1-259 GEN
Solar/Wind Harmer
0.975
964061AG1-260 GEN
Solar/Wind Harmer
0.975
208862AG1-362 C
Solar/Wind Harmer
0.529
232912OH NUG1
Adder
11.438
971195AH1-057 GEN
Solar/Wind Harmer
1.262
233955AB2-172 GEN
Solar/Wind Harmer
6.451
232813VAUGHN
Adder
0.757
231902DC CT7
Adder
14.214
233915AB1-141 GEN
Solar/Wind Harmer
1.249
970453AG2-297 GEN
Solar/Wind Harmer
3.013
964001AG1-254 GEN
Solar/Wind Harmer
7.847
228728W1-130C
Solar/Wind Harmer
0.714
227927V4-067C
Solar/Wind Harmer
0.213
219137THOSOLAR C
Solar/Wind Harmer
1.27
219615MILLCREEK C
Solar/Wind Harmer
0.245
219224BRL12CT4
Adder
9.118
207487AE2-000G4
Solar/Wind Harmer
31.757
207497AE2-000G2
Solar/Wind Harmer
31.757
219620RIDERU C
Solar/Wind Harmer
0.055
20635928PARLN3&4
Adder
7.181
218526CNTRALGAS2 C
Solar/Wind Harmer
0.357
217167KRNY_14
Adder
8.786
971009AG2-626 GEN
Solar/Wind Harmer
1.483
961261AF2-417 GEN
Solar/Wind Harmer
0.837
212266LOR1
Solar/Wind Harmer
0.938
959431AF2-234 GEN
Solar/Wind Harmer
1.454
200034PCHBTM 2
50/50
25.385
200205Y1-065-CTG2
50/50
4.954
234015AF2-250 C
Solar/Wind Harmer
0.156
232428Y3-058 C
Solar/Wind Harmer
1.078
232424Y1-079 C
Solar/Wind Harmer
0.717
228251CARLLS#4
Adder
0.683
230433AD2-135 GEN
Solar/Wind Harmer
0.109
228351V2-046C
Solar/Wind Harmer
2.168
219287REEVESEAST C
Solar/Wind Harmer
1.403
213589EDDYSTN4
Adder
82.148
213535CROYDN11
Adder
10.435
214067T20SOLAR
Solar/Wind Harmer
0.255
20636128O CRK C2
Adder
6.497
207459AE1-142 C O1
Solar/Wind Harmer
1.056
20628028LAKEHURS
Adder
0.952
217197RE CRAN C
Solar/Wind Harmer
0.523
924131AB2-057 GEN
Solar/Wind Harmer
0.996
20635128RRCT3&4
Adder
10.839
20635128RRCT3&4
Adder
9.455
218419LINDEN_G6
Adder
16.449
219035LINDEN_G8
Adder
15.719
20675428EAM_W2-061
Solar/Wind Harmer
0.18
972237AH1-703 GEN
Adder
9.566
20465127PORT CT
Adder
3.576
20465527S.RDG CT
Adder
1.876
223401AF1-299 GEN
Solar/Wind Helper
0.683
233972AC1-094 C
Solar/Wind Harmer
2.798
232921TASLEY2G
Adder
6.685
233950AC2-186 GEN
Solar/Wind Harmer
0.726
228711V2-041C
Solar/Wind Harmer
0.654
218660EHAMPSOLAR C
Solar/Wind Harmer
0.182
219921AF1-264
Solar/Wind Harmer
0.151
219688LUMSOLAR_S C
Solar/Wind Harmer
0.211
219914AD2-027 C
Solar/Wind Harmer
0.622
213497CHSTR7-9
Adder
2.817
213560DLW11-12
Adder
2.772
207454AA2-184 E
Solar/Wind Harmer
0.983
20635928PARLN3&4
Adder
3.253
217169METRODIV C
Solar/Wind Harmer
0.038
963161AG1-165 GEN
Solar/Wind Harmer
0.819
208972BECR K09
Solar/Wind Harmer
0.851
961331AF2-424 GEN
Solar/Wind Harmer
0.764
209071AE2-133 GEN
Solar/Wind Harmer
1.231
211065PSPA IPP
Solar/Wind Harmer
0.39
957921AF2-086 GEN
Solar/Wind Harmer
0.74
232926CRISFLD1
Adder
2.541
231940T-011
Adder
0.966
234041AC1-190 GEN
Solar/Wind Harmer
11.561
228201CARL#2CT
Adder
7.443
228200CARL#1CT
Adder
7.079
219904AC1-010 C
Solar/Wind Harmer
0.394
219906AC1-017 C
Solar/Wind Harmer
0.229
213815MOSER1-3
Adder
3.593
213815MOSER1-3
Adder
3.593
20720828JCB_W4-025
Solar/Wind Harmer
0.457
20714828MDF_W3-079
Solar/Wind Harmer
0.304
219817TRENTONSOL C
Solar/Wind Harmer
1.087
20641628MLH_W1-032
Solar/Wind Harmer
0.289
20742028HF_AC1-207
Solar/Wind Harmer
0.77
218438BLK ROCK C
Solar/Wind Harmer
0.133
972260AH1-715 GEN1
Adder
13.171
972261AH1-715 GEN2
Adder
15.265
217202FBANKSOLAR C
Solar/Wind Harmer
0.07
217201HACKENSOLA C
Solar/Wind Harmer
0.069
217206BARNGR HS C
Solar/Wind Harmer
0.029
217204WCALDSOLAR C
Solar/Wind Harmer
0.069
20674828DL_W4-046
Solar/Wind Harmer
0.587
20634528N27_Y2-018
Solar/Wind Harmer
0.244
232434Z2-077 GEN
Solar/Wind Harmer
0.324
232406W1-004 FULL
Solar/Wind Harmer
1.295
233964AF2-378 GEN
Solar/Wind Harmer
0.165
232422X3-066 FULL
Solar/Wind Harmer
0.317
230415AB2-049 C
Solar/Wind Harmer
0.204
219291REEVESSOUT C
Solar/Wind Harmer
0.063
219236SOUTHERNHQ C
Solar/Wind Harmer
0.07
213815MOSER1-3
Adder
3.593
20714928UPF_X1-085
Solar/Wind Harmer
0.408
219114HARTZY_C
Solar/Wind Harmer
0.832
219918AC2-009 C
Solar/Wind Harmer
0.025
20674528F3S_W2-016
Solar/Wind Harmer
1.317
209025WIENIPP3
Adder
4.317
209142AF1-226 GEN
Solar/Wind Harmer
4.408
205941AD2-115 GEN
Solar/Wind Harmer
0.678
227287AC2-120 GEN
Solar/Wind Helper
0.44
G-007ALTFEXP_G-007A->PJM
CMTX
49.597
CBM NorthLTFEXP_CBM-N->PJM
CBM
66.353
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.605
BlueGrassPJM->LTFIMP_BlueG
CLTF
11.231
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.341
VTFLTFEXP_VFT->PJM
CMTX
128.422
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.563
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.947

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PL_04_P22_102290_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PL_04_P22_102290_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.6 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:3750.31
MW Contribution:
9.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
232926CRISFLD1
Adder
2.545
231940T-011
Adder
0.967
234041AC1-190 GEN
Solar/Wind Harmer
11.58
228201CARL#2CT
Adder
7.394
228200CARL#1CT
Adder
7.033
219904AC1-010 C
Solar/Wind Harmer
0.39
219906AC1-017 C
Solar/Wind Harmer
0.226
213815MOSER1-3
Adder
3.555
213815MOSER1-3
Adder
3.555
20720828JCB_W4-025
Solar/Wind Harmer
0.451
20714828MDF_W3-079
Solar/Wind Harmer
0.299
219817TRENTONSOL C
Solar/Wind Harmer
1.07
20641628MLH_W1-032
Solar/Wind Harmer
0.284
20742028HF_AC1-207
Solar/Wind Harmer
0.757
218438BLK ROCK C
Solar/Wind Harmer
0.13
972260AH1-715 GEN1
Adder
12.895
972261AH1-715 GEN2
Adder
14.928
217202FBANKSOLAR C
Solar/Wind Harmer
0.068
217201HACKENSOLA C
Solar/Wind Harmer
0.068
217206BARNGR HS C
Solar/Wind Harmer
0.028
217204WCALDSOLAR C
Solar/Wind Harmer
0.067
20674828DL_W4-046
Solar/Wind Harmer
0.563
20634528N27_Y2-018
Solar/Wind Harmer
0.233
233973AC2-185 C
Solar/Wind Harmer
7.044
970695AG2-447 GEN
Solar/Wind Harmer
4.66
233987AB2-037 GEN
Solar/Wind Harmer
14.75
233923SMA
Solar/Wind Harmer
4.738
233997TMININ_4.2
Solar/Wind Harmer
1.292
232907VN8
Adder
38.919
232417X3-008 C
Solar/Wind Harmer
1.454
233935AB2-179 C
Solar/Wind Harmer
3.07
219221BRL12CT1
Adder
9.019
219223BRL12CT3
Adder
9.019
20715728PEM_W1-119
Solar/Wind Harmer
0.532
959561AF2-247 GEN
Solar/Wind Harmer
0.483
20636028O CRK C1
Adder
7.034
971667AH1-334 GEN
Solar/Wind Harmer
2.714
219727YARDVSOLFA C
Solar/Wind Harmer
0.893
20635828PARLN1&2
Adder
3.192
219249CENTRALDIV C
Solar/Wind Harmer
0.037
207442AE1-156 GEN
Solar/Wind Harmer
0.69
217211CAMDEN ST C
Solar/Wind Harmer
0.023
217194REDH C
Solar/Wind Harmer
0.454
207511W3-106 GEN
Solar/Wind Harmer
0.293
971007AG2-625 GEN
Solar/Wind Harmer
2.226
20466127PORT 5CT
Adder
22.85
20674128FR_U2-059
Solar/Wind Harmer
0.157
211065PSPA IPP
Solar/Wind Harmer
0.375
957921AF2-086 GEN
Solar/Wind Harmer
0.71
232901NORTHST
Adder
10.827
234033AF1-007_GEN
Solar/Wind Harmer
48.262
233996TM1833_GEN
Solar/Wind Harmer
1.292
232426Y1-080 FULL
Solar/Wind Harmer
0.247
232902EASTMUNI
Adder
16.772
234012AE2-112_GEN
Solar/Wind Harmer
2.929
200202DELTA2 ST
50/50
7.427
200052ROCKSP 1
50/50
3.135
200053ROCKSP 2
50/50
3.074
233940AF2-379 C
Solar/Wind Harmer
0.242
230434AG1-499 GEN
Solar/Wind Harmer
0.615
219258KINSLEYDEP C
Solar/Wind Harmer
0.335
213942SCHUYLKILL
Adder
3.612
213942SCHUYLKILL
Adder
2.762
213957STHWK3-4
Adder
2.762
213957STHWK3-4
Adder
2.762
213561DLWR9-10
Adder
3.592
213561DLWR9-10
Adder
2.747
219610FLORENCE C
Solar/Wind Harmer
1.399
963401AG1-189 GEN
Solar/Wind Harmer
2.258
971189AH1-054 GEN
Solar/Wind Harmer
1.169
20716228APLW2-078
Solar/Wind Harmer
0.855
20673828FLE_V3-070
Solar/Wind Harmer
0.434
20676128MHD_W3-029
Solar/Wind Harmer
0.443
209027LOR2_Q27
Solar/Wind Harmer
3.393
964051AG1-259 GEN
Solar/Wind Harmer
0.933
964061AG1-260 GEN
Solar/Wind Harmer
0.933
200192DELTA CT1
50/50
2.451
200054ROCKSP 3
50/50
3.172
972177AH1-672 GEN
Solar/Wind Harmer
17.425
232408W1-005 C
Solar/Wind Harmer
1.296
200201DELTA2 CT2
50/50
4.386
232899W1-062
Adder
12.48
232410W1-006 C
Solar/Wind Harmer
1.296
233946AB2-136 GEN
Solar/Wind Harmer
5.159
233952AC2-187 GEN
Solar/Wind Harmer
1.455
233954AC2-188 GEN
Solar/Wind Harmer
1.455
233984AB2-036 GEN
Solar/Wind Harmer
15.943
233930AB2-032 GEN
Solar/Wind Harmer
1.054
233982AB2-133 GEN
Solar/Wind Harmer
6.157
230511AF1-262
Solar/Wind Harmer
0.195
228754AB1-001 C
Solar/Wind Harmer
0.148
228307PCLP GT
Adder
12.846
219272CLEANLIGHT C
Solar/Wind Harmer
0.189
213587EDDYSTN3
Adder
81.794
217081WEATEXAS C
Solar/Wind Harmer
0.08
217083KRNY_132
Adder
8.52
207471AF2-354 C
Solar/Wind Harmer
0.445
20675928HOL_W4-097
Solar/Wind Harmer
0.111
209010PEIP 1
Adder
2.769
209010PEIP 1
Adder
0.406
961541AF2-445A GEN
Solar/Wind Harmer
2.438
961431AF2-434 GEN
Solar/Wind Harmer
0.73
209130AF1-271A GEN
Solar/Wind Harmer
1.957
223402AF1-300 C
Solar/Wind Helper
0.609
200195DELTA ST
50/50
3.786
232920IR10
Adder
4.1
233901CHERRYDALE C
Solar/Wind Harmer
1.458
232913OH NUG2
Adder
11.301
231906DC3 NUG
Adder
17.818
231907DC10
Adder
4.448
970597AG2-380 GEN
Solar/Wind Harmer
5.301
972141AH1-641 GEN
Solar/Wind Harmer
3.083
20715028HAN_X4-015
Solar/Wind Harmer
0.297
213611FALLS1-3
Adder
3.524
213611FALLS1-3
Adder
3.524
207507AE2-000G3
Solar/Wind Harmer
31.35
207445AB1-138_GEN
Solar/Wind Harmer
0.571
20720628TIN_W1-124
Solar/Wind Harmer
0.964
971521AH1-258 GEN
Solar/Wind Harmer
2.61
20675528CPH_W2-050
Solar/Wind Harmer
0.537
20676428JCR_X2-075
Solar/Wind Harmer
0.316
217086KRNY_131
Adder
8.502
20675128HRM_W1-127
Solar/Wind Harmer
0.145
209029WAYMART-WD
Solar/Wind Harmer
2.022
959421AF2-233 GEN
Solar/Wind Harmer
0.696
226929AD2-058 GEN
Solar/Wind Helper
0.115
200035PCHBTM 3
50/50
24.877
233971AC1-093 C
Solar/Wind Harmer
3.311
232918OH NUG7
Adder
11.377
232905CHERITON_25
Adder
3.182
233994AC2-023 GEN
Solar/Wind Harmer
3.479
234036AF2-325 C
Solar/Wind Harmer
1.185
232910NRG_G1
Adder
11.1
234014AF1-036_GEN
Solar/Wind Harmer
3.446
232436AB1-176 C
Solar/Wind Harmer
0.291
972233AH1-701 GEN
Adder
4.43
219912AD2-042 GEN
Solar/Wind Harmer
0.818
219607WPEMNERT C
Solar/Wind Harmer
0.423
219304NAMERICA C
Solar/Wind Harmer
0.313
20635028RRCT1&2
Adder
11.013
218418LINDEN_G5
Adder
16.104
219036LINDEN_G7
Adder
15.595
217086KRNY_131
Adder
8.593
20674328GAR_V4-001
Solar/Wind Harmer
0.097
946751AF1-339 GEN
Solar/Wind Harmer
0.698
200034PCHBTM 2
50/50
25.558
200205Y1-065-CTG2
50/50
4.983
234015AF2-250 C
Solar/Wind Harmer
0.156
232428Y3-058 C
Solar/Wind Harmer
1.08
232424Y1-079 C
Solar/Wind Harmer
0.719
228251CARLLS#4
Adder
0.678
200194DELTA CT3
50/50
2.451
233970AC1-092 C
Solar/Wind Harmer
3.487
232900DEMECSMY
Adder
11.971
232404W1-003 C
Solar/Wind Harmer
1.296
233998TM1NIN_3.36
Solar/Wind Harmer
1.292
232919VN10
Adder
3.635
231917EM10
Adder
2.845
970997AG2-616 GEN
Solar/Wind Harmer
10.275
213497CHSTR7-9
Adder
2.805
213497CHSTR7-9
Adder
2.805
213560DLW11-12
Adder
2.747
219222BRL12CT2
Adder
9.019
20717128DIX_Z2-102
Solar/Wind Harmer
1.315
20715828PEM_W1-120
Solar/Wind Harmer
0.532
963711AG1-223 GEN
Solar/Wind Harmer
1.449
219276PARKLANDSO C
Solar/Wind Harmer
0.449
20715228NPK_W1-113
Solar/Wind Harmer
0.416
20720528MAN_W1-024
Solar/Wind Harmer
0.246
219919AE1-041 FULL
Solar/Wind Harmer
0.038
217121ECCF
Adder
0.401
20676728BRNX1-095
Solar/Wind Harmer
0.159
20676328BVR_Y1-020
Solar/Wind Harmer
0.294
20674928WA_W3-044
Solar/Wind Harmer
0.419
971519AH1-257 GEN
Solar/Wind Harmer
2.178
207518AF1-320_GEN
Solar/Wind Harmer
3.142
20465127PORT CT
Adder
2.581
209018SUNBIPCT
Adder
5.184
972251AH1-710 GEN
Adder
56.833
231918WEST 1
Adder
4.09
228732V1-021 C
Adder
0.204
228400MICK 1CT
Adder
12.452
219766PARADISE C
Solar/Wind Harmer
0.325
20714528FRN_Y2-051
Solar/Wind Harmer
0.289
219680HOPEWELLV C1
Solar/Wind Harmer
0.074
218440SUMMTASSOC C
Solar/Wind Harmer
0.121
217208PARK ELE C
Solar/Wind Harmer
0.023
966261AG1-495 GEN
Solar/Wind Harmer
3.119
20674628WNG_W3-110
Solar/Wind Harmer
0.358
209023WIENIPP1
Adder
8.486
209025WIENIPP3
Adder
4.236
963071AG1-156 GEN
Solar/Wind Harmer
7.764
232904IR4
Adder
104.911
232432Z2-076 GEN
Solar/Wind Harmer
0.171
233968AD2-076_GEN
Solar/Wind Harmer
8.443
231919CHRIST1
Adder
5.38
231920CHRIST2
Adder
5.26
230422AE1-104_GEN1
Solar/Wind Harmer
36.14
230425AE1-104_GEN2
Solar/Wind Harmer
36.14
230430AE1-229_GEN
Solar/Wind Harmer
30.656
230407AD2-065 C
Solar/Wind Harmer
0.14
20720728JCB_W1-129
Solar/Wind Harmer
0.297
207500AE2-000G1
Solar/Wind Harmer
31.35
970025AG2-016 GEN
Solar/Wind Harmer
2.811
20714428HOW_X1-037
Solar/Wind Harmer
1.199
218449LINSOLAR C
Solar/Wind Harmer
0.938
217147KRNY_1212
Adder
8.156
217147KRNY_1212
Adder
8.01
217146KRNY_1234
Adder
7.992
217146KRNY_1234
Adder
7.938
964851AG1-348 GEN
Solar/Wind Harmer
1.185
207408W3-077 C
Solar/Wind Harmer
0.435
20462827N BANGR8
Adder
0.613
209026WIENIPP4
Adder
4.193
209054AE2-059 GEN
Solar/Wind Harmer
1.196
200200DELTA2 CT1
50/50
4.386
200193DELTA CT2
50/50
2.451
200203Y1-065-STG
50/50
8.63
200055ROCKSP 4
50/50
3.117
233939AC1-091 C
Solar/Wind Harmer
3.487
232914OH NUG3
Adder
11.454
232912OH NUG1
Adder
11.454
971195AH1-057 GEN
Solar/Wind Harmer
1.264
233955AB2-172 GEN
Solar/Wind Harmer
6.462
232813VAUGHN
Adder
0.759
231902DC CT7
Adder
14.245
233915AB1-141 GEN
Solar/Wind Harmer
1.252
970453AG2-297 GEN
Solar/Wind Harmer
2.995
964001AG1-254 GEN
Solar/Wind Harmer
7.794
228728W1-130C
Solar/Wind Harmer
0.708
227927V4-067C
Solar/Wind Harmer
0.211
219137THOSOLAR C
Solar/Wind Harmer
1.26
219615MILLCREEK C
Solar/Wind Harmer
0.242
219224BRL12CT4
Adder
9.019
207487AE2-000G4
Solar/Wind Harmer
31.35
207497AE2-000G2
Solar/Wind Harmer
31.35
200204Y1-065-CTG1
50/50
4.983
233918AB1-142 GEN
Solar/Wind Harmer
1.252
228206SHRMN CT
Adder
17.921
228260V4-054C
Solar/Wind Harmer
1.104
228729W2-030 C
Solar/Wind Harmer
0.615
219686LUMSOLAR_N C
Solar/Wind Harmer
0.209
219348LDSOLAR C
Solar/Wind Harmer
0.604
213611FALLS1-3
Adder
3.524
214194N WALES4
Adder
0.841
20720428HOL_W1-112
Solar/Wind Harmer
0.333
20635828PARLN1&2
Adder
7.047
20635028RRCT1&2
Adder
11.185
218524CNTRALGAS1 C
Solar/Wind Harmer
0.349
217209CENTRL HS C
Solar/Wind Harmer
0.041
20671828STAW2-080
Solar/Wind Harmer
0.096
207439AE1-081 C O1
Solar/Wind Harmer
0.053
207530AG1-191 GEN
Solar/Wind Harmer
1.213
211065PSPA IPP
Solar/Wind Harmer
0.375
961301AF2-421 GEN
Solar/Wind Harmer
0.787
963151AG1-164 GEN
Solar/Wind Harmer
0.787
961341AF2-425 GEN
Solar/Wind Harmer
0.732
212507AE2-042_GEN
Solar/Wind Harmer
2.12
232916OH NUG5
Adder
11.454
233933AB2-153 GEN
Solar/Wind Harmer
1.423
219623KINSLEYBEA C
Solar/Wind Harmer
0.444
213958STHWK5-6
Adder
2.762
20716428NHV_W2-082
Solar/Wind Harmer
1.772
963391AG1-188 GEN
Solar/Wind Harmer
3.718
219612MATRIX C
Solar/Wind Harmer
0.176
20716928W4-060COL
Solar/Wind Harmer
0.681
217213AMBOY SO C
Solar/Wind Harmer
0.119
20673728F2S_V4-070
Solar/Wind Harmer
0.167
207510AF2-138 C
Solar/Wind Harmer
1.577
207437AD2-070 GEN
Solar/Wind Harmer
0.257
20465427SHAW CT
Adder
3.313
20671928W4-073
Solar/Wind Harmer
0.368
20633028GILCT9
Adder
23.798
209116AE2-175 GEN
Solar/Wind Harmer
3.463
970095AG2-074 GEN
Solar/Wind Harmer
4.917
961421AF2-433 GEN
Solar/Wind Harmer
0.73
209093AE2-110 GEN
Solar/Wind Harmer
1.825
209120AE2-241 GEN
Solar/Wind Harmer
2.415
946691AF1-333 GEN
Solar/Wind Harmer
0.698
946741AF1-338 GEN
Solar/Wind Harmer
0.698
226910AB2-157 C
Solar/Wind Helper
0.018
232917OH NUG6
Adder
11.403
232915OH NUG4
Adder
11.377
233944AB2-135 GEN
Solar/Wind Harmer
6.639
219907AC1-030 C
Solar/Wind Harmer
0.142
213958STHWK5-6
Adder
2.762
20716028EGP_W2-019
Solar/Wind Harmer
0.463
207522AF2-254 C
Solar/Wind Harmer
1.43
218428ETC SOLAR C
Solar/Wind Harmer
0.034
219908AB1-139 C
Solar/Wind Harmer
0.358
972275AH1-722 GEN
Adder
29.605
20673628F1S_V4-069
Solar/Wind Harmer
0.167
207528AF2-192 GEN
Solar/Wind Harmer
1.179
217186ESSEX_G9
Adder
3.642
217083KRNY_132
Adder
8.575
20676228FRD_X1-012
Solar/Wind Harmer
0.524
20675828AU_W4-064
Solar/Wind Harmer
0.153
20675728RH_W2-091
Solar/Wind Harmer
0.518
207484AF2-139 C O1
Solar/Wind Harmer
0.431
208909MACR G3
Adder
135.411
209010PEIP 1
Adder
0.503
946731AF1-337 GEN
Solar/Wind Harmer
0.698
219620RIDERU C
Solar/Wind Harmer
0.054
20635928PARLN3&4
Adder
7.047
218526CNTRALGAS2 C
Solar/Wind Harmer
0.35
217167KRNY_14
Adder
8.575
971009AG2-626 GEN
Solar/Wind Harmer
1.42
961261AF2-417 GEN
Solar/Wind Harmer
0.807
212266LOR1
Solar/Wind Harmer
0.899
959431AF2-234 GEN
Solar/Wind Harmer
1.392
230433AD2-135 GEN
Solar/Wind Harmer
0.108
228351V2-046C
Solar/Wind Harmer
2.154
219287REEVESEAST C
Solar/Wind Harmer
1.39
213589EDDYSTN4
Adder
81.805
213535CROYDN11
Adder
10.321
214067T20SOLAR
Solar/Wind Harmer
0.252
20636128O CRK C2
Adder
6.414
207459AE1-142 C O1
Solar/Wind Harmer
1.042
20628028LAKEHURS
Adder
0.938
217197RE CRAN C
Solar/Wind Harmer
0.514
924131AB2-057 GEN
Solar/Wind Harmer
0.978
20635128RRCT3&4
Adder
10.631
20635128RRCT3&4
Adder
9.273
218419LINDEN_G6
Adder
16.104
219035LINDEN_G8
Adder
15.372
20675428EAM_W2-061
Solar/Wind Harmer
0.175
972237AH1-703 GEN
Adder
9.336
20465127PORT CT
Adder
3.425
223401AF1-299 GEN
Solar/Wind Helper
0.609
233972AC1-094 C
Solar/Wind Harmer
2.8
232921TASLEY2G
Adder
6.694
233950AC2-186 GEN
Solar/Wind Harmer
0.727
228711V2-041C
Solar/Wind Harmer
0.65
218660EHAMPSOLAR C
Solar/Wind Harmer
0.181
219921AF1-264
Solar/Wind Harmer
0.15
219688LUMSOLAR_S C
Solar/Wind Harmer
0.209
213497CHSTR7-9
Adder
2.805
219914AD2-027 C
Solar/Wind Harmer
0.617
213560DLW11-12
Adder
2.747
207454AA2-184 E
Solar/Wind Harmer
0.967
20635928PARLN3&4
Adder
3.192
217169METRODIV C
Solar/Wind Harmer
0.037
963161AG1-165 GEN
Solar/Wind Harmer
0.787
208972BECR K09
Solar/Wind Harmer
0.82
961331AF2-424 GEN
Solar/Wind Harmer
0.732
209071AE2-133 GEN
Solar/Wind Harmer
1.178
232434Z2-077 GEN
Solar/Wind Harmer
0.324
232406W1-004 FULL
Solar/Wind Harmer
1.296
233964AF2-378 GEN
Solar/Wind Harmer
0.165
232422X3-066 FULL
Solar/Wind Harmer
0.318
230415AB2-049 C
Solar/Wind Harmer
0.202
219291REEVESSOUT C
Solar/Wind Harmer
0.062
219236SOUTHERNHQ C
Solar/Wind Harmer
0.069
213815MOSER1-3
Adder
3.555
20714928UPF_X1-085
Solar/Wind Harmer
0.402
219114HARTZY_C
Solar/Wind Harmer
0.82
219918AC2-009 C
Solar/Wind Harmer
0.025
20674528F3S_W2-016
Solar/Wind Harmer
1.273
209025WIENIPP3
Adder
4.15
209142AF1-226 GEN
Solar/Wind Harmer
4.226
205941AD2-115 GEN
Solar/Wind Harmer
0.506
227287AC2-120 GEN
Solar/Wind Helper
0.417
G-007ALTFEXP_G-007A->PJM
CMTX
48.643
CBM NorthLTFEXP_CBM-N->PJM
CBM
64.461
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.489
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.87
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.168
VTFLTFEXP_VFT->PJM
CMTX
125.427
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.464
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.391

Details for PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line l/o PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM2S-PCHBTM1S 500.0 kV Ckt Z1 line
Contingency Name:
PECO_P4_PEACH255_SRT-A/* $ CHESCO $ PECO_P4_PEACH255 $ STBK
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.7 %
Rating:2860.0 MVA
Rating Type:B
MVA to Mitigate:3366.11
MW Contribution:
7.43
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
200204Y1-065-CTG1
50/50
8.911
233920W3-032A-CTG1
50/50
3.941
233918AB1-142 GEN
Solar/Wind Harmer
1.753
233921W3-032A-STG1
50/50
2.547
234034AF2-060
50/50
3.44
233900O-025 C
50/50
0.125
232434Z2-077 GEN
Solar/Wind Harmer
0.459
232912OH NUG1
50/50
17.199
232813VAUGHN
50/50
1.135
971195AH1-057 GEN
Solar/Wind Harmer
1.788
233955AB2-172 GEN
Solar/Wind Harmer
9.136
231902DC CT7
Adder
19.887
233915AB1-141 GEN
Solar/Wind Harmer
1.753
970453AG2-297 GEN
Solar/Wind Harmer
3.467
227927V4-067C
Solar/Wind Harmer
0.236
964001AG1-254 GEN
Solar/Wind Harmer
8.616
228728W1-130C
Solar/Wind Harmer
0.784
219137THOSOLAR C
Solar/Wind Harmer
1.285
219615MILLCREEK C
Solar/Wind Harmer
0.231
207487AE2-000G4
Solar/Wind Harmer
30.588
207497AE2-000G2
Solar/Wind Harmer
30.588
219224BRL12CT4
Adder
8.544
219620RIDERU C
Solar/Wind Harmer
0.047
20635928PARLN3&4
Adder
6.048
218526CNTRALGAS2 C
Solar/Wind Harmer
0.291
217167KRNY_14
Adder
6.819
971009AG2-626 GEN
Solar/Wind Harmer
1.022
961261AF2-417 GEN
Solar/Wind Harmer
0.534
231914HR8
50/50
4.093
232907VN8
50/50
58.449
232911NRG_G2
50/50
0.907
233973AC2-185 C
Solar/Wind Harmer
9.961
970695AG2-447 GEN
Solar/Wind Harmer
6.59
233987AB2-037 GEN
Solar/Wind Harmer
20.91
233923SMA
Solar/Wind Harmer
6.705
233997TMININ_4.2
Solar/Wind Harmer
1.829
232417X3-008 C
Solar/Wind Harmer
2.056
233935AB2-179 C
Solar/Wind Harmer
4.237
20636028O CRK C1
Adder
6.863
20715728PEM_W1-119
Solar/Wind Harmer
0.514
219221BRL12CT1
Adder
8.544
219223BRL12CT3
Adder
8.544
971667AH1-334 GEN
Solar/Wind Harmer
2.583
959561AF2-247 GEN
Solar/Wind Harmer
0.447
219727YARDVSOLFA C
Solar/Wind Harmer
0.8
20635828PARLN1&2
Adder
2.739
219249CENTRALDIV C
Solar/Wind Harmer
0.03
217211CAMDEN ST C
Solar/Wind Harmer
0.018
207442AE1-156 GEN
Solar/Wind Harmer
0.544
217194REDH C
Solar/Wind Harmer
0.361
207511W3-106 GEN
Solar/Wind Harmer
0.219
971007AG2-625 GEN
Solar/Wind Harmer
1.602
20466127PORT 5CT
Adder
16.112
20674128FR_U2-059
Solar/Wind Harmer
0.11
211065PSPA IPP
Solar/Wind Harmer
0.245
232920IR10
50/50
6.156
232913OH NUG2
50/50
16.97
233901CHERRYDALE C
Solar/Wind Harmer
2.064
970597AG2-380 GEN
Solar/Wind Harmer
7.444
231906DC3 NUG
Adder
24.876
231907DC10
Adder
6.21
972141AH1-641 GEN
Solar/Wind Harmer
3.43
207507AE2-000G3
Solar/Wind Harmer
30.588
20715028HAN_X4-015
Solar/Wind Harmer
0.288
207445AB1-138_GEN
Solar/Wind Harmer
0.542
213611FALLS1-3
Adder
3.189
213611FALLS1-3
Adder
3.189
20720628TIN_W1-124
Solar/Wind Harmer
0.87
971521AH1-258 GEN
Solar/Wind Harmer
2.323
20675528CPH_W2-050
Solar/Wind Harmer
0.427
20676428JCR_X2-075
Solar/Wind Harmer
0.249
217086KRNY_131
Adder
6.762
20675128HRM_W1-127
Solar/Wind Harmer
0.102
232904IR4
50/50
157.523
232432Z2-076 GEN
Solar/Wind Harmer
0.242
233968AD2-076_GEN
Solar/Wind Harmer
11.855
231919CHRIST1
Adder
6.963
231920CHRIST2
Adder
6.809
230422AE1-104_GEN1
Solar/Wind Harmer
40.798
230425AE1-104_GEN2
Solar/Wind Harmer
40.798
230430AE1-229_GEN
Solar/Wind Harmer
34.063
230407AD2-065 C
Solar/Wind Harmer
0.153
207500AE2-000G1
Solar/Wind Harmer
30.588
20720728JCB_W1-129
Solar/Wind Harmer
0.288
970025AG2-016 GEN
Solar/Wind Harmer
2.713
20714428HOW_X1-037
Solar/Wind Harmer
1.087
218449LINSOLAR C
Solar/Wind Harmer
0.761
217147KRNY_1212
Adder
6.486
217147KRNY_1212
Adder
6.371
217146KRNY_1234
Adder
6.356
217146KRNY_1234
Adder
6.313
964851AG1-348 GEN
Solar/Wind Harmer
0.853
207408W3-077 C
Solar/Wind Harmer
0.31
20462827N BANGR8
Adder
0.427
232901NORTHST
50/50
16.255
234033AF1-007_GEN
Solar/Wind Harmer
68.291
233996TM1833_GEN
Solar/Wind Harmer
1.829
232426Y1-080 FULL
Solar/Wind Harmer
0.35
232902EASTMUNI
Adder
23.674
234012AE2-112_GEN
Solar/Wind Harmer
4.113
972251AH1-710 GEN
Adder
76.732
231918WEST 1
Adder
5.321
228732V1-021 C
Adder
0.233
228400MICK 1CT
Adder
13.159
219766PARADISE C
Solar/Wind Harmer
0.321
20714528FRN_Y2-051
Solar/Wind Harmer
0.268
219680HOPEWELLV C1
Solar/Wind Harmer
0.063
218440SUMMTASSOC C
Solar/Wind Harmer
0.1
217208PARK ELE C
Solar/Wind Harmer
0.019
966261AG1-495 GEN
Solar/Wind Harmer
2.328
20674628WNG_W3-110
Solar/Wind Harmer
0.268
228206SHRMN CT
Adder
20.518
228260V4-054C
Solar/Wind Harmer
1.243
228729W2-030 C
Solar/Wind Harmer
0.688
219686LUMSOLAR_N C
Solar/Wind Harmer
0.214
219348LDSOLAR C
Solar/Wind Harmer
0.573
213611FALLS1-3
Adder
3.189
20720428HOL_W1-112
Solar/Wind Harmer
0.295
20635828PARLN1&2
Adder
6.048
20635028RRCT1&2
Adder
9.508
218524CNTRALGAS1 C
Solar/Wind Harmer
0.29
217209CENTRL HS C
Solar/Wind Harmer
0.033
214194N WALES4
Adder
0.581
20671828STAW2-080
Solar/Wind Harmer
0.075
207439AE1-081 C O1
Solar/Wind Harmer
0.04
207530AG1-191 GEN
Solar/Wind Harmer
0.906
211065PSPA IPP
Solar/Wind Harmer
0.245
232900DEMECSMY
50/50
17.951
232919VN10
50/50
5.456
233970AC1-092 C
Solar/Wind Harmer
4.931
232404W1-003 C
Solar/Wind Harmer
1.835
233998TM1NIN_3.36
Solar/Wind Harmer
1.829
231917EM10
Adder
3.612
970997AG2-616 GEN
Solar/Wind Harmer
11.432
213497CHSTR7-9
Adder
2.674
213497CHSTR7-9
Adder
2.674
20717128DIX_Z2-102
Solar/Wind Harmer
1.272
20715828PEM_W1-120
Solar/Wind Harmer
0.514
219222BRL12CT2
Adder
8.544
963711AG1-223 GEN
Solar/Wind Harmer
1.345
213560DLW11-12
Adder
2.41
20720528MAN_W1-024
Solar/Wind Harmer
0.22
20715228NPK_W1-113
Solar/Wind Harmer
0.372
219276PARKLANDSO C
Solar/Wind Harmer
0.396
219919AE1-041 FULL
Solar/Wind Harmer
0.031
217121ECCF
Adder
0.319
20676728BRNX1-095
Solar/Wind Harmer
0.124
20676328BVR_Y1-020
Solar/Wind Harmer
0.221
20674928WA_W3-044
Solar/Wind Harmer
0.304
971519AH1-257 GEN
Solar/Wind Harmer
1.565
207518AF1-320_GEN
Solar/Wind Harmer
2.23
20465127PORT CT
Adder
1.817
232918OH NUG7
50/50
17.084
232905CHERITON_25
50/50
4.777
232910NRG_G1
50/50
16.591
233971AC1-093 C
Solar/Wind Harmer
4.682
233994AC2-023 GEN
Solar/Wind Harmer
4.922
234036AF2-325 C
Solar/Wind Harmer
1.676
234014AF1-036_GEN
Solar/Wind Harmer
4.839
232436AB1-176 C
Solar/Wind Harmer
0.409
972233AH1-701 GEN
Adder
4.699
219912AD2-042 GEN
Solar/Wind Harmer
0.795
219607WPEMNERT C
Solar/Wind Harmer
0.401
219304NAMERICA C
Solar/Wind Harmer
0.297
20635028RRCT1&2
Adder
9.362
218418LINDEN_G5
Adder
13.212
219036LINDEN_G7
Adder
12.66
217086KRNY_131
Adder
6.834
20674328GAR_V4-001
Solar/Wind Harmer
0.072
232926CRISFLD1
50/50
3.822
231940T-011
50/50
1.452
234041AC1-190 GEN
Solar/Wind Harmer
16.372
228201CARL#2CT
Adder
8.327
228200CARL#1CT
Adder
7.92
219904AC1-010 C
Solar/Wind Harmer
0.385
219906AC1-017 C
Solar/Wind Harmer
0.216
20720828JCB_W4-025
Solar/Wind Harmer
0.437
20714828MDF_W3-079
Solar/Wind Harmer
0.278
20641628MLH_W1-032
Solar/Wind Harmer
0.255
20742028HF_AC1-207
Solar/Wind Harmer
0.675
219817TRENTONSOL C
Solar/Wind Harmer
0.929
218438BLK ROCK C
Solar/Wind Harmer
0.111
972260AH1-715 GEN1
Adder
10.58
972261AH1-715 GEN2
Adder
12.119
217202FBANKSOLAR C
Solar/Wind Harmer
0.055
217201HACKENSOLA C
Solar/Wind Harmer
0.054
217206BARNGR HS C
Solar/Wind Harmer
0.023
217204WCALDSOLAR C
Solar/Wind Harmer
0.053
213815MOSER1-3
Adder
2.391
213815MOSER1-3
Adder
2.391
20674828DL_W4-046
Solar/Wind Harmer
0.41
20634528N27_Y2-018
Solar/Wind Harmer
0.168
232406W1-004 FULL
Solar/Wind Harmer
1.835
233964AF2-378 GEN
Solar/Wind Harmer
0.233
232422X3-066 FULL
Solar/Wind Harmer
0.446
230415AB2-049 C
Solar/Wind Harmer
0.223
219291REEVESSOUT C
Solar/Wind Harmer
0.064
219236SOUTHERNHQ C
Solar/Wind Harmer
0.067
20714928UPF_X1-085
Solar/Wind Harmer
0.38
219114HARTZY_C
Solar/Wind Harmer
0.741
219918AC2-009 C
Solar/Wind Harmer
0.021
213815MOSER1-3
Adder
2.391
20674528F3S_W2-016
Solar/Wind Harmer
0.97
200052ROCKSP 1
50/50
5.606
200053ROCKSP 2
50/50
5.496
232616GEN FOOD
50/50
0.319
233940AF2-379 C
Solar/Wind Harmer
0.342
230434AG1-499 GEN
Solar/Wind Harmer
0.668
219258KINSLEYDEP C
Solar/Wind Harmer
0.336
219610FLORENCE C
Solar/Wind Harmer
1.325
963401AG1-189 GEN
Solar/Wind Harmer
2.187
971189AH1-054 GEN
Solar/Wind Harmer
1.12
213942SCHUYLKILL
Adder
3.227
213942SCHUYLKILL
Adder
2.467
213957STHWK3-4
Adder
2.467
213957STHWK3-4
Adder
2.467
213561DLWR9-10
Adder
3.151
213561DLWR9-10
Adder
2.41
20716228APLW2-078
Solar/Wind Harmer
0.764
20673828FLE_V3-070
Solar/Wind Harmer
0.344
20676128MHD_W3-029
Solar/Wind Harmer
0.35
200054ROCKSP 3
50/50
5.671
231912HR6
50/50
2.693
231913HR7
50/50
2.693
232917OH NUG6
50/50
17.122
232915OH NUG4
50/50
17.084
232408W1-005 C
Solar/Wind Harmer
1.835
972177AH1-672 GEN
Solar/Wind Harmer
24.646
233944AB2-135 GEN
Solar/Wind Harmer
9.301
219907AC1-030 C
Solar/Wind Harmer
0.137
20716028EGP_W2-019
Solar/Wind Harmer
0.448
207522AF2-254 C
Solar/Wind Harmer
1.384
213958STHWK5-6
Adder
2.467
218428ETC SOLAR C
Solar/Wind Harmer
0.028
219908AB1-139 C
Solar/Wind Harmer
0.296
972275AH1-722 GEN
Adder
24.289
20673628F1S_V4-069
Solar/Wind Harmer
0.131
207528AF2-192 GEN
Solar/Wind Harmer
0.931
217186ESSEX_G9
Adder
2.897
217083KRNY_132
Adder
6.819
20676228FRD_X1-012
Solar/Wind Harmer
0.392
20675828AU_W4-064
Solar/Wind Harmer
0.114
20675728RH_W2-091
Solar/Wind Harmer
0.369
207484AF2-139 C O1
Solar/Wind Harmer
0.305
208909MACR G3
Adder
92.554
232899W1-062
50/50
18.715
232410W1-006 C
Solar/Wind Harmer
1.835
233946AB2-136 GEN
Solar/Wind Harmer
7.297
233952AC2-187 GEN
Solar/Wind Harmer
2.055
233954AC2-188 GEN
Solar/Wind Harmer
2.055
233984AB2-036 GEN
Solar/Wind Harmer
22.451
233930AB2-032 GEN
Solar/Wind Harmer
1.476
233982AB2-133 GEN
Solar/Wind Harmer
8.615
228754AB1-001 C
Solar/Wind Harmer
0.165
230511AF1-262
Solar/Wind Harmer
0.217
228307PCLP GT
Adder
13.88
219272CLEANLIGHT C
Solar/Wind Harmer
0.194
213587EDDYSTN3
Adder
77.39
217081WEATEXAS C
Solar/Wind Harmer
0.064
217083KRNY_132
Adder
6.776
207471AF2-354 C
Solar/Wind Harmer
0.323
20675928HOL_W4-097
Solar/Wind Harmer
0.079
223402AF1-300 C
Solar/Wind Helper
0.35
200203Y1-065-STG
50/50
15.433
200055ROCKSP 4
50/50
5.573
231911HR5
50/50
2.693
232914OH NUG3
50/50
17.199
232916OH NUG5
50/50
17.199
233939AC1-091 C
Solar/Wind Harmer
4.931
233933AB2-153 GEN
Solar/Wind Harmer
1.993
219623KINSLEYBEA C
Solar/Wind Harmer
0.448
20716428NHV_W2-082
Solar/Wind Harmer
1.716
963391AG1-188 GEN
Solar/Wind Harmer
3.585
213958STHWK5-6
Adder
2.467
20716928W4-060COL
Solar/Wind Harmer
0.596
219612MATRIX C
Solar/Wind Harmer
0.15
217213AMBOY SO C
Solar/Wind Harmer
0.098
20673728F2S_V4-070
Solar/Wind Harmer
0.131
207510AF2-138 C
Solar/Wind Harmer
1.181
207437AD2-070 GEN
Solar/Wind Harmer
0.181
20671928W4-073
Solar/Wind Harmer
0.259
20465427SHAW CT
Adder
2.326
20633028GILCT9
Adder
16.799
209116AE2-175 GEN
Solar/Wind Harmer
2.317
200034PCHBTM 2
50/50
47.255
200205Y1-065-CTG2
50/50
8.911
234015AF2-250 C
Solar/Wind Harmer
0.22
232428Y3-058 C
Solar/Wind Harmer
1.528
232424Y1-079 C
Solar/Wind Harmer
1.012
228251CARLLS#4
Adder
0.764
230433AD2-135 GEN
Solar/Wind Harmer
0.12
228351V2-046C
Solar/Wind Harmer
2.378
219287REEVESEAST C
Solar/Wind Harmer
1.426
213589EDDYSTN4
Adder
77.452
20636128O CRK C2
Adder
6.258
213535CROYDN11
Adder
9.671
207459AE1-142 C O1
Solar/Wind Harmer
0.995
20628028LAKEHURS
Adder
0.889
214067T20SOLAR
Solar/Wind Harmer
0.228
217197RE CRAN C
Solar/Wind Harmer
0.439
20635128RRCT3&4
Adder
9.037
20635128RRCT3&4
Adder
7.883
924131AB2-057 GEN
Solar/Wind Harmer
0.821
218419LINDEN_G6
Adder
13.212
219035LINDEN_G8
Adder
12.48
20675428EAM_W2-061
Solar/Wind Harmer
0.138
972237AH1-703 GEN
Adder
7.43
20465127PORT CT
Adder
2.411
223401AF1-299 GEN
Solar/Wind Helper
0.35
232921TASLEY2G
50/50
10.052
233972AC1-094 C
Solar/Wind Harmer
3.96
233950AC2-186 GEN
Solar/Wind Harmer
1.027
228711V2-041C
Solar/Wind Harmer
0.745
218660EHAMPSOLAR C
Solar/Wind Harmer
0.186
219688LUMSOLAR_S C
Solar/Wind Harmer
0.212
219921AF1-264
Solar/Wind Harmer
0.149
219914AD2-027 C
Solar/Wind Harmer
0.6
213497CHSTR7-9
Adder
2.674
213560DLW11-12
Adder
2.41
207454AA2-184 E
Solar/Wind Harmer
0.873
20635928PARLN3&4
Adder
2.739
217169METRODIV C
Solar/Wind Harmer
0.029
G-007ALTFEXP_G-007A->PJM
CMTX
41.35
CBM NorthLTFEXP_CBM-N->PJM
CBM
47.408
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.265
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.171
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.755
VTFLTFEXP_VFT->PJM
CMTX
100.535
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.235
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
15.286
CONTINGENCY 'PJM_500_BG_P4_5_CNSTN_C_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200064 CKT 1    /*CNASTONE     500.0 - PCHBTM1S     500.0
 OPEN BRANCH FROM BUS 200004 TO BUS 200100 CKT ZC   /*CNASTONE     500.0 - CNASTCAP     500.0
END
CONTINGENCY 'BGE_P4_GRACETON_51_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200064 CKT 1   /*CNASTONE     500.0 - PCHBTM1S     500.0
END
CONTINGENCY 'PECO_P4_PEACH235_SRT-A
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1    /*PCHBTM1S     500.0 - CNASTONE     500.0
 TRIP BRANCH FROM BUS 200064 TO BUS 200065 CKT Z1   /*PCHBTM1S     500.0 - PCHBTM2S     500.0
END
CONTINGENCY 'PJM_500_BG_P4_5_CNSTN_B_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200064 CKT 1   /*CNASTONE     500.0 - PCHBTM1S     500.0
 OPEN BRANCH FROM BUS 200004 TO BUS 220963 CKT 2   /*CNASTONE     500.0 - CONASTON     230.0
END
CONTINGENCY 'AP_P2-3_PE-500-019E_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 1          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 3          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1          /*CHAN         500.0 - 01DOUBS      500.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 2                  /*01DOUBS      500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 235098 CKT 1 /*01DOUBS      500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_PE-500-3835T_SRT-A'
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'PECO_P4_PEACH025_SRT-A
 TRIP BRANCH FROM BUS 200013 TO BUS 200066 CKT Z1   /*PCHBTM2N     500.0 - PCHBTM1N     500.0
 TRIP BRANCH FROM BUS 200013 TO BUS 214347 CKT Z1   /*PCHBTM2N     500.0 - PBN_EXP_BAY  500.0
 TRIP BRANCH FROM BUS 270095 TO BUS 200066 CKT 1    /*CHAN         500.0 - PCHBTM1N     500.0
END
CONTINGENCY 'BG_P7_CNSTN_NWEST2_SRT-A'
 OPEN BRANCH FROM BUS 220961 TO BUS 220963 CKT 1   /*NWEST326     230.0 - CONASTON     230.0
 OPEN BRANCH FROM BUS 220962 TO BUS 220963 CKT 1   /*NWEST311     230.0 - CONASTON     230.0
END
CONTINGENCY 'PECO_P4_PEACH035_SRT-A
 DISCONNECT BUS 213791                             /*MDDYRN07     230.0
 DISCONNECT BUS 213794                             /*MDYRN5-6      13.8
 DISCONNECT BUS 213795                             /*MDYRN7-8      13.8
 DISCONNECT BUS 213866                             /*PCHBTM       230.0
 DISCONNECT BUS 213867                             /*PCHBTM        35.0
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
CONTINGENCY 'PECO_P1-2_5012_SRT-A'
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1   /*PCHBTM1S     500.0 - CNASTONE     500.0
END
CONTINGENCY 'PECO_P4_PEACH245_SRT-A
 DISCONNECT BUS 200122                             /*DELTA        500.0
 DISCONNECT BUS 200192                             /*DELTA CT1     13.8
 DISCONNECT BUS 200193                             /*DELTA CT2     13.8
 DISCONNECT BUS 200194                             /*DELTA CT3     13.8
 DISCONNECT BUS 200195                             /*DELTA ST      18.0
 DISCONNECT BUS 200199                             /*DELTA2 POI   500.0
 DISCONNECT BUS 200200                             /*DELTA2 CT1    18.0
 DISCONNECT BUS 200201                             /*DELTA2 CT2    18.0
 DISCONNECT BUS 200202                             /*DELTA2 ST     19.5
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1   /*PCHBTM1S     500.0 - CNASTONE     500.0
END
CONTINGENCY 'PECO_P1-2_5007_SRT-A
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
CONTINGENCY 'PJM_500_BG_P4_5_CNSTN_M_SRT-A'
 OPEN BRANCH FROM BUS 200004 TO BUS 200026 CKT 1    /*CNASTONE     500.0 - HUNTERTN     500.0
 OPEN BRANCH FROM BUS 200004 TO BUS 200100 CKT ZC   /*CNASTONE     500.0 - CNASTCAP     500.0
END
CONTINGENCY 'PECO_P2-2_NOTT230B_SRT-A
 DISCONNECT BUS 213844   /*NOTTNGHM     230.0
END
CONTINGENCY 'PL_04_P71_001014_SRT-A'
 DISCONNECT BRANCH FROM BUS 208045 TO BUS 208078 CKT 3   /*LAUS         230.0 - SAKR         230.0
 DISCONNECT BRANCH FROM BUS 208045 TO BUS 208078 CKT 4   /*LAUS         230.0 - SAKR         230.0
END
CONTINGENCY 'PL_05_P71_000906_SRT-A'
 DISCONNECT BRANCH FROM BUS 208019 TO BUS 208020 CKT 1   /*MANO         230.0 - MANO TR3     230.0
 DISCONNECT BRANCH FROM BUS 208019 TO BUS 208021 CKT 1   /*MANO         230.0 - MANO TR4     230.0
 DISCONNECT BRANCH FROM BUS 208066 TO BUS 208914 CKT 1   /*SAHA0102     230.0 - SAHA 34       13.8
 DISCONNECT BRANCH FROM BUS 208066 TO BUS 208915 CKT 1   /*SAHA0102     230.0 - SAHA 567      13.8
 DISCONNECT BRANCH FROM BUS 208067 TO BUS 208916 CKT 1   /*SAHA0304     230.0 - SAHA8910      13.8
 DISCONNECT BRANCH FROM BUS 208067 TO BUS 208917 CKT 1   /*SAHA0304     230.0 - SAHA1112      13.8
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208019 CKT 1   /*SAHA12TP     230.0 - MANO         230.0
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208048 CKT 1   /*SAHA12TP     230.0 - OTCR         230.0
 DISCONNECT BRANCH FROM BUS 208070 TO BUS 208066 CKT 1   /*SAHA12TP     230.0 - SAHA0102     230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 208019 CKT 1   /*SAHA34TP     230.0 - MANO         230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 208067 CKT 1   /*SAHA34TP     230.0 - SAHA0304     230.0
 DISCONNECT BRANCH FROM BUS 208071 TO BUS 220964 CKT 1   /*SAHA34TP     230.0 - GRACETON     230.0
END
CONTINGENCY 'PL_04_P22_102290_SRT-A'
 DISCONNECT BRANCH FROM BUS 200099 TO BUS 208045 CKT 3   /*LAUS         500.0 - LAUS         230.0
END
CONTINGENCY 'PECO_P4_PEACH255_SRT-A
 DISCONNECT BUS 200122                              /*DELTA        500.0
 DISCONNECT BUS 200192                              /*DELTA CT1     13.8
 DISCONNECT BUS 200193                              /*DELTA CT2     13.8
 DISCONNECT BUS 200194                              /*DELTA CT3     13.8
 DISCONNECT BUS 200195                              /*DELTA ST      18.0
 DISCONNECT BUS 200199                              /*DELTA2 POI   500.0
 DISCONNECT BUS 200200                              /*DELTA2 CT1    18.0
 DISCONNECT BUS 200201                              /*DELTA2 CT2    18.0
 DISCONNECT BUS 200202                              /*DELTA2 ST     19.5
 TRIP BRANCH FROM BUS 200064 TO BUS 200065 CKT Z2   /*PCHBTM1S     500.0 - PCHBTM2S     500.0
 TRIP BRANCH FROM BUS 214347 TO BUS 200064 CKT 2    /*PBN_EXP_BAY  500.0 - PCHBTM1S     500.0
END
270095 to 235105 ckt 1
200004 to 200003 ckt 1
200066 to 270095 ckt 1
200064 to 200004 ckt 1
200065 to 200064 ckt Z1

Winter Peak Analysis

The New Service Request AH1-703 was evaluated as a 35.61 MW (51.254 MW Capacity) injection in the PSEG area.

AH1-703 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 670.61 MW (35.61 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2PSEG
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
PS_P1-2_R-2218_SRT-A
SingleAC104.12 %978.0B1018.33
5.46
GD2PSEG
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
PS_P2-3_LIND2_1-9_SRT-A
BreakerAC104.12 %978.0B1018.33
5.46
GD2PSEG
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
PS_P1-2_R-2218_LT_SRT-A
SingleAC103.44 %978.0B1011.62
5.46
GD2PSEG
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
PS_P2-3_LIND2_1-9_LT_SRT-A
BreakerAC103.44 %978.0B1011.62
5.46
GD2PSEG
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
PS_P7-1_R2218+T2325_SRT-A
TowerAC101.81 %978.0B995.67
5.39
GD2PSEG
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
PS_P7-1_R2218+T2325_LT_SRT-A
TowerAC100.88 %978.0B986.58
5.39
GD2PSEG
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
PS_P1-2_Q-2348_SRT-A
SingleAC102.73 %980.0B1006.79
5.4
GD2PSEG
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
PS_P2-3_SEW_2-14_SRT-A
BreakerAC102.73 %980.0B1006.79
5.4
GD2PSEG
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
PS_P2-2_DEANS_7_SRT-A
BusAC102.73 %980.0B1006.79
5.4
GD2PSEG
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
PS_P1-2_Q-2348_LT_SRT-A
SingleAC102.02 %980.0B999.81
5.4
GD2PSEG
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
PS_P2-3_SEW_2-14_LT_SRT-A
BreakerAC102.02 %980.0B999.81
5.4
GD2PSEG
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
PS_P2-2_DEANS_7_LT_SRT-A
BusAC102.02 %980.0B999.81
5.4
GD2PSEG
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
PS_P1-2_R-2218_LT_SRT-A
SingleAC114.14 %885.0B1010.18
5.46
GD2PSEG
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
PS_P2-3_LIND2_1-9_LT_SRT-A
BreakerAC114.14 %885.0B1010.18
5.46
GD2PSEG
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
PS_P2-3_LIND2_9-10_LT_SRT-A
BreakerAC112.76 %885.0B997.93
5.57
GD2PSEG
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
PS_P1-2_R-2218_SRT-A
SingleAC111.38 %885.0B985.75
5.46
GD2PSEG
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
PS_P7-1_R2218+T2325_LT_SRT-A
TowerAC110.43 %885.0B977.34
5.39
GD2PSEG
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
PS_P7-1_R2218+T2325_SRT-A
TowerAC108.82 %885.0B963.04
5.39
GD2PSEG
MINUEST_R-SEWAREN 230.0 kV Ckt 1 line
PS_P1-2_Q-2348_LT_SRT-A
SingleAC101.88 %980.0B998.38
5.4
GD2PSEG
MINUEST_R-SEWAREN 230.0 kV Ckt 1 line
PS_P2-3_SEW_2-14_LT_SRT-A
BreakerAC101.88 %980.0B998.38
5.4
GD2PSEG
MINUEST_R-SEWAREN 230.0 kV Ckt 1 line
PS_P2-2_DEANS_7_LT_SRT-A
BusAC101.88 %980.0B998.38
5.4

Details for LINDEN-MINUEST_G 230.0 kV Ckt 1 line l/o PS_P1-2_R-2218_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_R-2218_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.12 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:1018.33
MW Contribution:
5.46
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_R-2218_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.54 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:1012.58
MW Contribution:
5.45
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.368
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.183
217118BERGEN 1 ST
50/50
1.211
217138BERGEN_2CT1
50/50
1.563
217139BERGEN_2CT2
50/50
1.563
217140BERGEN_2ST
50/50
2.2
217176GREATFALLS
50/50
0.09
217186ESSEX_G9
50/50
2.937
217191NEC_CT1
50/50
1.855
217192NEC_CT2
50/50
1.855
217193NEC_ST
50/50
2.351
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.367
218418LINDEN_G5
50/50
52.249
218419LINDEN_G6
50/50
52.249
218423LINDEN_G21
50/50
6.012
218424LINDEN_G22
50/50
6.012
218425LINDEN_1201
50/50
6.012
218426LINDEN_2ST
50/50
10.438
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.24
218436LINDEN_1001
50/50
7.362
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.876
219035LINDEN_G8
50/50
42.85
219036LINDEN_G7
50/50
42.85
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.042
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.354
217916BERGEN_12
50/50
1.353
217917BERGEN_13
50/50
1.353
217918BERGEN_14
50/50
1.353
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.463
972275AH1-722 GEN
50/50
79.224
945801AF1-245 GEN
50/50
11.681
961241AF2-415 GEN
50/50
29.102
972260AH1-715 GEN1
50/50
30.96
972261AH1-715 GEN2
50/50
32.651
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.441
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.879
G-007ALTFEXP_G-007A->PJM
CMTX
0.807
VFTLTFEXP_VFT->PJM
CMTX
89.723
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.411
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.248
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.775
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.381
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.188
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINDEN-MINUEST_G 230.0 kV Ckt 1 line l/o PS_P2-3_LIND2_1-9_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_LIND2_1-9_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.12 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:1018.33
MW Contribution:
5.46
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_LIND2_1-9_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:1012.57
MW Contribution:
5.45
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.368
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.183
217118BERGEN 1 ST
50/50
1.211
217138BERGEN_2CT1
50/50
1.563
217139BERGEN_2CT2
50/50
1.563
217140BERGEN_2ST
50/50
2.2
217176GREATFALLS
50/50
0.09
217186ESSEX_G9
50/50
2.937
217191NEC_CT1
50/50
1.855
217192NEC_CT2
50/50
1.855
217193NEC_ST
50/50
2.351
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.367
218418LINDEN_G5
50/50
52.249
218419LINDEN_G6
50/50
52.249
218423LINDEN_G21
50/50
6.012
218424LINDEN_G22
50/50
6.012
218425LINDEN_1201
50/50
6.012
218426LINDEN_2ST
50/50
10.438
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.24
218436LINDEN_1001
50/50
7.362
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.876
219035LINDEN_G8
50/50
42.85
219036LINDEN_G7
50/50
42.85
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.042
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.354
217916BERGEN_12
50/50
1.353
217917BERGEN_13
50/50
1.353
217918BERGEN_14
50/50
1.353
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.463
972275AH1-722 GEN
50/50
79.224
945801AF1-245 GEN
50/50
11.681
961241AF2-415 GEN
50/50
29.102
972260AH1-715 GEN1
50/50
30.96
972261AH1-715 GEN2
50/50
32.651
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.441
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.879
G-007ALTFEXP_G-007A->PJM
CMTX
0.807
VFTLTFEXP_VFT->PJM
CMTX
89.723
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.411
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.248
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.775
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.381
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.188
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINDEN-MINUEST_G 230.0 kV Ckt 1 line l/o PS_P1-2_R-2218_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_R-2218_LT_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.44 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:1011.62
MW Contribution:
5.46
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_R-2218_LT_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.85 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:1005.88
MW Contribution:
5.45
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.368
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.183
217118BERGEN 1 ST
50/50
1.211
217138BERGEN_2CT1
50/50
1.563
217139BERGEN_2CT2
50/50
1.563
217140BERGEN_2ST
50/50
2.2
217176GREATFALLS
50/50
0.09
217186ESSEX_G9
50/50
2.937
217191NEC_CT1
50/50
1.855
217192NEC_CT2
50/50
1.855
217193NEC_ST
50/50
2.351
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.367
218418LINDEN_G5
50/50
52.249
218419LINDEN_G6
50/50
52.249
218423LINDEN_G21
50/50
6.012
218424LINDEN_G22
50/50
6.012
218425LINDEN_1201
50/50
6.012
218426LINDEN_2ST
50/50
10.438
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.24
218436LINDEN_1001
50/50
7.362
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.876
219035LINDEN_G8
50/50
42.85
219036LINDEN_G7
50/50
42.85
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.042
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.354
217916BERGEN_12
50/50
1.353
217917BERGEN_13
50/50
1.353
217918BERGEN_14
50/50
1.353
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.463
972275AH1-722 GEN
50/50
79.224
945801AF1-245 GEN
50/50
11.681
961241AF2-415 GEN
50/50
29.102
972260AH1-715 GEN1
50/50
30.96
972261AH1-715 GEN2
50/50
32.651
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.441
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.879
G-007ALTFEXP_G-007A->PJM
CMTX
0.807
VFTLTFEXP_VFT->PJM
CMTX
89.723
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.411
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.248
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.775
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.381
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.188
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINDEN-MINUEST_G 230.0 kV Ckt 1 line l/o PS_P2-3_LIND2_1-9_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_LIND2_1-9_LT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.44 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:1011.62
MW Contribution:
5.46
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_LIND2_1-9_LT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.85 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:1005.87
MW Contribution:
5.45
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.368
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.183
217118BERGEN 1 ST
50/50
1.211
217138BERGEN_2CT1
50/50
1.563
217139BERGEN_2CT2
50/50
1.563
217140BERGEN_2ST
50/50
2.2
217176GREATFALLS
50/50
0.09
217186ESSEX_G9
50/50
2.937
217191NEC_CT1
50/50
1.855
217192NEC_CT2
50/50
1.855
217193NEC_ST
50/50
2.351
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.367
218418LINDEN_G5
50/50
52.249
218419LINDEN_G6
50/50
52.249
218423LINDEN_G21
50/50
6.012
218424LINDEN_G22
50/50
6.012
218425LINDEN_1201
50/50
6.012
218426LINDEN_2ST
50/50
10.438
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.24
218436LINDEN_1001
50/50
7.362
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.876
219035LINDEN_G8
50/50
42.85
219036LINDEN_G7
50/50
42.85
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.042
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.354
217916BERGEN_12
50/50
1.353
217917BERGEN_13
50/50
1.353
217918BERGEN_14
50/50
1.353
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.463
972275AH1-722 GEN
50/50
79.224
945801AF1-245 GEN
50/50
11.681
961241AF2-415 GEN
50/50
29.102
972260AH1-715 GEN1
50/50
30.96
972261AH1-715 GEN2
50/50
32.651
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.441
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.879
G-007ALTFEXP_G-007A->PJM
CMTX
0.807
VFTLTFEXP_VFT->PJM
CMTX
89.723
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.411
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.248
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.775
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.381
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.188
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINDEN-MINUEST_G 230.0 kV Ckt 1 line l/o PS_P7-1_R2218+T2325_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P7-1_R2218+T2325_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.81 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:995.67
MW Contribution:
5.39
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P7-1_R2218+T2325_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.23 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:990.02
MW Contribution:
5.38
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.362
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.166
217118BERGEN 1 ST
50/50
1.194
217138BERGEN_2CT1
50/50
1.541
217139BERGEN_2CT2
50/50
1.541
217140BERGEN_2ST
50/50
2.17
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.897
217191NEC_CT1
50/50
1.83
217192NEC_CT2
50/50
1.83
217193NEC_ST
50/50
2.319
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.362
218418LINDEN_G5
50/50
51.463
218419LINDEN_G6
50/50
51.463
218423LINDEN_G21
50/50
5.922
218424LINDEN_G22
50/50
5.922
218425LINDEN_1201
50/50
5.922
218426LINDEN_2ST
50/50
10.281
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.177
218436LINDEN_1001
50/50
7.252
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.863
219035LINDEN_G8
50/50
42.21
219036LINDEN_G7
50/50
42.21
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.043
218526CNTRALGAS2 C
Solar/Wind Helper
0.04
219908AB1-139 C
Solar/Wind Helper
0.04
217915BERGEN_11
50/50
1.335
217916BERGEN_12
50/50
1.334
217917BERGEN_13
50/50
1.334
217918BERGEN_14
50/50
1.334
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.388
972275AH1-722 GEN
50/50
78.032
945801AF1-245 GEN
50/50
11.522
961241AF2-415 GEN
50/50
28.69
972260AH1-715 GEN1
50/50
30.495
972261AH1-715 GEN2
50/50
32.164
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.304
G-007ALTFEXP_G-007A->PJM
CMTX
0.822
VFTLTFEXP_VFT->PJM
CMTX
88.423
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.402
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.243
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.735
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.373
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.161
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINDEN-MINUEST_G 230.0 kV Ckt 1 line l/o PS_P7-1_R2218+T2325_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P7-1_R2218+T2325_LT_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.88 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:986.58
MW Contribution:
5.39
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_G 230.0 kV Ckt 1 line
Contingency Name:
PS_P7-1_R2218+T2325_LT_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.3 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:980.95
MW Contribution:
5.38
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.362
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.166
217118BERGEN 1 ST
50/50
1.194
217138BERGEN_2CT1
50/50
1.541
217139BERGEN_2CT2
50/50
1.541
217140BERGEN_2ST
50/50
2.17
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.897
217191NEC_CT1
50/50
1.83
217192NEC_CT2
50/50
1.83
217193NEC_ST
50/50
2.319
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.362
218418LINDEN_G5
50/50
51.463
218419LINDEN_G6
50/50
51.463
218423LINDEN_G21
50/50
5.922
218424LINDEN_G22
50/50
5.922
218425LINDEN_1201
50/50
5.922
218426LINDEN_2ST
50/50
10.281
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.177
218436LINDEN_1001
50/50
7.252
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.863
219035LINDEN_G8
50/50
42.21
219036LINDEN_G7
50/50
42.21
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.043
218526CNTRALGAS2 C
Solar/Wind Helper
0.04
219908AB1-139 C
Solar/Wind Helper
0.04
217915BERGEN_11
50/50
1.335
217916BERGEN_12
50/50
1.334
217917BERGEN_13
50/50
1.334
217918BERGEN_14
50/50
1.334
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.388
972275AH1-722 GEN
50/50
78.032
945801AF1-245 GEN
50/50
11.522
961241AF2-415 GEN
50/50
28.69
972260AH1-715 GEN1
50/50
30.495
972261AH1-715 GEN2
50/50
32.164
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.304
G-007ALTFEXP_G-007A->PJM
CMTX
0.822
VFTLTFEXP_VFT->PJM
CMTX
88.423
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.402
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.243
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.735
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.373
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.161
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINDEN-MINUEST_R 230.0 kV Ckt 1 line l/o PS_P1-2_Q-2348_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_Q-2348_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.73 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1006.79
MW Contribution:
5.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_Q-2348_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.16 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1001.14
MW Contribution:
5.39
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.363
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.169
217118BERGEN 1 ST
50/50
1.197
217138BERGEN_2CT1
50/50
1.544
217139BERGEN_2CT2
50/50
1.544
217140BERGEN_2ST
50/50
2.174
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.903
217191NEC_CT1
50/50
1.834
217192NEC_CT2
50/50
1.834
217193NEC_ST
50/50
2.324
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.363
218418LINDEN_G5
50/50
51.643
218419LINDEN_G6
50/50
51.643
218423LINDEN_G21
50/50
5.942
218424LINDEN_G22
50/50
5.942
218425LINDEN_1201
50/50
5.942
218426LINDEN_2ST
50/50
10.317
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.191
218436LINDEN_1001
50/50
7.277
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.866
219035LINDEN_G8
50/50
42.353
219036LINDEN_G7
50/50
42.353
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.041
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.339
217916BERGEN_12
50/50
1.337
217917BERGEN_13
50/50
1.337
217918BERGEN_14
50/50
1.337
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.4
972275AH1-722 GEN
50/50
78.306
945801AF1-245 GEN
50/50
11.546
961241AF2-415 GEN
50/50
28.765
972260AH1-715 GEN1
50/50
30.602
972261AH1-715 GEN2
50/50
32.273
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.394
G-007ALTFEXP_G-007A->PJM
CMTX
0.798
VFTLTFEXP_VFT->PJM
CMTX
88.684
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.754
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.377
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.174
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINDEN-MINUEST_R 230.0 kV Ckt 1 line l/o PS_P2-3_SEW_2-14_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_SEW_2-14_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.73 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1006.79
MW Contribution:
5.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_SEW_2-14_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.16 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1001.13
MW Contribution:
5.39
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.363
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.169
217118BERGEN 1 ST
50/50
1.197
217138BERGEN_2CT1
50/50
1.544
217139BERGEN_2CT2
50/50
1.544
217140BERGEN_2ST
50/50
2.174
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.903
217191NEC_CT1
50/50
1.834
217192NEC_CT2
50/50
1.834
217193NEC_ST
50/50
2.324
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.363
218418LINDEN_G5
50/50
51.643
218419LINDEN_G6
50/50
51.643
218423LINDEN_G21
50/50
5.942
218424LINDEN_G22
50/50
5.942
218425LINDEN_1201
50/50
5.942
218426LINDEN_2ST
50/50
10.317
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.191
218436LINDEN_1001
50/50
7.277
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.866
219035LINDEN_G8
50/50
42.353
219036LINDEN_G7
50/50
42.353
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.041
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.339
217916BERGEN_12
50/50
1.337
217917BERGEN_13
50/50
1.337
217918BERGEN_14
50/50
1.337
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.4
972275AH1-722 GEN
50/50
78.306
945801AF1-245 GEN
50/50
11.546
961241AF2-415 GEN
50/50
28.765
972260AH1-715 GEN1
50/50
30.602
972261AH1-715 GEN2
50/50
32.273
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.394
G-007ALTFEXP_G-007A->PJM
CMTX
0.798
VFTLTFEXP_VFT->PJM
CMTX
88.684
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.754
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.377
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.174
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINDEN-MINUEST_R 230.0 kV Ckt 1 line l/o PS_P2-2_DEANS_7_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-2_DEANS_7_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.73 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1006.79
MW Contribution:
5.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-2_DEANS_7_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.16 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1001.14
MW Contribution:
5.39
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.363
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.169
217118BERGEN 1 ST
50/50
1.197
217138BERGEN_2CT1
50/50
1.544
217139BERGEN_2CT2
50/50
1.544
217140BERGEN_2ST
50/50
2.174
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.903
217191NEC_CT1
50/50
1.834
217192NEC_CT2
50/50
1.834
217193NEC_ST
50/50
2.324
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.363
218418LINDEN_G5
50/50
51.643
218419LINDEN_G6
50/50
51.643
218423LINDEN_G21
50/50
5.942
218424LINDEN_G22
50/50
5.942
218425LINDEN_1201
50/50
5.942
218426LINDEN_2ST
50/50
10.317
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.191
218436LINDEN_1001
50/50
7.277
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.866
219035LINDEN_G8
50/50
42.353
219036LINDEN_G7
50/50
42.353
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.041
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.339
217916BERGEN_12
50/50
1.337
217917BERGEN_13
50/50
1.337
217918BERGEN_14
50/50
1.337
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.4
972275AH1-722 GEN
50/50
78.306
945801AF1-245 GEN
50/50
11.546
961241AF2-415 GEN
50/50
28.765
972260AH1-715 GEN1
50/50
30.602
972261AH1-715 GEN2
50/50
32.273
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.394
G-007ALTFEXP_G-007A->PJM
CMTX
0.798
VFTLTFEXP_VFT->PJM
CMTX
88.684
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.754
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.377
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.174
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINDEN-MINUEST_R 230.0 kV Ckt 1 line l/o PS_P1-2_Q-2348_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_Q-2348_LT_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.02 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:999.81
MW Contribution:
5.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_Q-2348_LT_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.45 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:994.17
MW Contribution:
5.39
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.363
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.169
217118BERGEN 1 ST
50/50
1.197
217138BERGEN_2CT1
50/50
1.544
217139BERGEN_2CT2
50/50
1.544
217140BERGEN_2ST
50/50
2.174
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.903
217191NEC_CT1
50/50
1.834
217192NEC_CT2
50/50
1.834
217193NEC_ST
50/50
2.324
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.363
218418LINDEN_G5
50/50
51.643
218419LINDEN_G6
50/50
51.643
218423LINDEN_G21
50/50
5.942
218424LINDEN_G22
50/50
5.942
218425LINDEN_1201
50/50
5.942
218426LINDEN_2ST
50/50
10.317
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.191
218436LINDEN_1001
50/50
7.277
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.866
219035LINDEN_G8
50/50
42.353
219036LINDEN_G7
50/50
42.353
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.041
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.339
217916BERGEN_12
50/50
1.337
217917BERGEN_13
50/50
1.337
217918BERGEN_14
50/50
1.337
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.4
972275AH1-722 GEN
50/50
78.306
945801AF1-245 GEN
50/50
11.546
961241AF2-415 GEN
50/50
28.765
972260AH1-715 GEN1
50/50
30.602
972261AH1-715 GEN2
50/50
32.273
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.394
G-007ALTFEXP_G-007A->PJM
CMTX
0.798
VFTLTFEXP_VFT->PJM
CMTX
88.684
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.754
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.377
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.174
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINDEN-MINUEST_R 230.0 kV Ckt 1 line l/o PS_P2-3_SEW_2-14_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_SEW_2-14_LT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.02 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:999.81
MW Contribution:
5.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_SEW_2-14_LT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.44 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:994.16
MW Contribution:
5.39
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.363
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.169
217118BERGEN 1 ST
50/50
1.197
217138BERGEN_2CT1
50/50
1.544
217139BERGEN_2CT2
50/50
1.544
217140BERGEN_2ST
50/50
2.174
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.903
217191NEC_CT1
50/50
1.834
217192NEC_CT2
50/50
1.834
217193NEC_ST
50/50
2.324
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.363
218418LINDEN_G5
50/50
51.643
218419LINDEN_G6
50/50
51.643
218423LINDEN_G21
50/50
5.942
218424LINDEN_G22
50/50
5.942
218425LINDEN_1201
50/50
5.942
218426LINDEN_2ST
50/50
10.317
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.191
218436LINDEN_1001
50/50
7.277
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.866
219035LINDEN_G8
50/50
42.353
219036LINDEN_G7
50/50
42.353
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.041
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.339
217916BERGEN_12
50/50
1.337
217917BERGEN_13
50/50
1.337
217918BERGEN_14
50/50
1.337
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.4
972275AH1-722 GEN
50/50
78.306
945801AF1-245 GEN
50/50
11.546
961241AF2-415 GEN
50/50
28.765
972260AH1-715 GEN1
50/50
30.602
972261AH1-715 GEN2
50/50
32.273
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.394
G-007ALTFEXP_G-007A->PJM
CMTX
0.798
VFTLTFEXP_VFT->PJM
CMTX
88.684
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.754
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.377
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.174
MDUPJM->LTFIMP_MDU
CLTF
0

Details for LINDEN-MINUEST_R 230.0 kV Ckt 1 line l/o PS_P2-2_DEANS_7_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-2_DEANS_7_LT_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.02 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:999.81
MW Contribution:
5.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
LINDEN-MINUEST_R 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-2_DEANS_7_LT_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.45 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:994.17
MW Contribution:
5.39
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.363
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.169
217118BERGEN 1 ST
50/50
1.197
217138BERGEN_2CT1
50/50
1.544
217139BERGEN_2CT2
50/50
1.544
217140BERGEN_2ST
50/50
2.174
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.903
217191NEC_CT1
50/50
1.834
217192NEC_CT2
50/50
1.834
217193NEC_ST
50/50
2.324
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.363
218418LINDEN_G5
50/50
51.643
218419LINDEN_G6
50/50
51.643
218423LINDEN_G21
50/50
5.942
218424LINDEN_G22
50/50
5.942
218425LINDEN_1201
50/50
5.942
218426LINDEN_2ST
50/50
10.317
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.191
218436LINDEN_1001
50/50
7.277
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.866
219035LINDEN_G8
50/50
42.353
219036LINDEN_G7
50/50
42.353
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.041
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.339
217916BERGEN_12
50/50
1.337
217917BERGEN_13
50/50
1.337
217918BERGEN_14
50/50
1.337
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.4
972275AH1-722 GEN
50/50
78.306
945801AF1-245 GEN
50/50
11.546
961241AF2-415 GEN
50/50
28.765
972260AH1-715 GEN1
50/50
30.602
972261AH1-715 GEN2
50/50
32.273
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.394
G-007ALTFEXP_G-007A->PJM
CMTX
0.798
VFTLTFEXP_VFT->PJM
CMTX
88.684
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.754
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.377
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.174
MDUPJM->LTFIMP_MDU
CLTF
0

Details for MINUEST_G-SEWAREN 230.0 kV Ckt 1 line l/o PS_P1-2_R-2218_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_R-2218_LT_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.14 %
Rating:885.0 MVA
Rating Type:B
MVA to Mitigate:1010.18
MW Contribution:
5.46
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_R-2218_LT_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.7 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:1004.44
MW Contribution:
5.45
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.368
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.183
217118BERGEN 1 ST
50/50
1.211
217138BERGEN_2CT1
50/50
1.563
217139BERGEN_2CT2
50/50
1.563
217140BERGEN_2ST
50/50
2.2
217176GREATFALLS
50/50
0.09
217186ESSEX_G9
50/50
2.937
217191NEC_CT1
50/50
1.855
217192NEC_CT2
50/50
1.855
217193NEC_ST
50/50
2.351
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.367
218418LINDEN_G5
50/50
52.249
218419LINDEN_G6
50/50
52.249
218423LINDEN_G21
50/50
6.012
218424LINDEN_G22
50/50
6.012
218425LINDEN_1201
50/50
6.012
218426LINDEN_2ST
50/50
10.438
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.24
218436LINDEN_1001
50/50
7.362
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.876
219035LINDEN_G8
50/50
42.85
219036LINDEN_G7
50/50
42.85
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.042
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.354
217916BERGEN_12
50/50
1.353
217917BERGEN_13
50/50
1.353
217918BERGEN_14
50/50
1.353
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.463
972275AH1-722 GEN
50/50
79.224
945801AF1-245 GEN
50/50
11.681
961241AF2-415 GEN
50/50
29.102
972260AH1-715 GEN1
50/50
30.96
972261AH1-715 GEN2
50/50
32.651
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.441
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.879
G-007ALTFEXP_G-007A->PJM
CMTX
0.807
VFTLTFEXP_VFT->PJM
CMTX
89.723
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.411
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.248
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.775
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.381
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.188
MDUPJM->LTFIMP_MDU
CLTF
0

Details for MINUEST_G-SEWAREN 230.0 kV Ckt 1 line l/o PS_P2-3_LIND2_1-9_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_LIND2_1-9_LT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.14 %
Rating:885.0 MVA
Rating Type:B
MVA to Mitigate:1010.18
MW Contribution:
5.46
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_LIND2_1-9_LT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.7 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:1004.43
MW Contribution:
5.45
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.368
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.183
217118BERGEN 1 ST
50/50
1.211
217138BERGEN_2CT1
50/50
1.563
217139BERGEN_2CT2
50/50
1.563
217140BERGEN_2ST
50/50
2.2
217176GREATFALLS
50/50
0.09
217186ESSEX_G9
50/50
2.937
217191NEC_CT1
50/50
1.855
217192NEC_CT2
50/50
1.855
217193NEC_ST
50/50
2.351
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.367
218418LINDEN_G5
50/50
52.249
218419LINDEN_G6
50/50
52.249
218423LINDEN_G21
50/50
6.012
218424LINDEN_G22
50/50
6.012
218425LINDEN_1201
50/50
6.012
218426LINDEN_2ST
50/50
10.438
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.24
218436LINDEN_1001
50/50
7.362
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.876
219035LINDEN_G8
50/50
42.85
219036LINDEN_G7
50/50
42.85
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.042
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.354
217916BERGEN_12
50/50
1.353
217917BERGEN_13
50/50
1.353
217918BERGEN_14
50/50
1.353
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.463
972275AH1-722 GEN
50/50
79.224
945801AF1-245 GEN
50/50
11.681
961241AF2-415 GEN
50/50
29.102
972260AH1-715 GEN1
50/50
30.96
972261AH1-715 GEN2
50/50
32.651
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.441
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.879
G-007ALTFEXP_G-007A->PJM
CMTX
0.807
VFTLTFEXP_VFT->PJM
CMTX
89.723
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.411
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.248
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.775
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.381
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.188
MDUPJM->LTFIMP_MDU
CLTF
0

Details for MINUEST_G-SEWAREN 230.0 kV Ckt 1 line l/o PS_P2-3_LIND2_9-10_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_LIND2_9-10_LT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.76 %
Rating:885.0 MVA
Rating Type:B
MVA to Mitigate:997.93
MW Contribution:
5.57
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_LIND2_9-10_LT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.42 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:991.9
MW Contribution:
5.55
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.375
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.206
217118BERGEN 1 ST
50/50
1.235
217138BERGEN_2CT1
50/50
1.593
217139BERGEN_2CT2
50/50
1.593
217140BERGEN_2ST
50/50
2.243
217176GREATFALLS
50/50
0.092
217186ESSEX_G9
50/50
2.995
217191NEC_CT1
50/50
1.892
217192NEC_CT2
50/50
1.892
217193NEC_ST
50/50
2.397
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.375
218418LINDEN_G5
50/50
53.273
218419LINDEN_G6
50/50
53.273
218423LINDEN_G21
50/50
6.13
218424LINDEN_G22
50/50
6.13
218425LINDEN_1201
50/50
6.13
218426LINDEN_2ST
50/50
10.643
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.323
218436LINDEN_1001
50/50
7.506
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.893
219035LINDEN_G8
50/50
43.69
219036LINDEN_G7
50/50
43.69
219612MATRIX C
Solar/Wind Helper
0.008
218524CNTRALGAS1 C
Solar/Wind Helper
0.045
218526CNTRALGAS2 C
Solar/Wind Helper
0.043
219908AB1-139 C
Solar/Wind Helper
0.042
217915BERGEN_11
50/50
1.381
217916BERGEN_12
50/50
1.38
217917BERGEN_13
50/50
1.38
217918BERGEN_14
50/50
1.38
924131AB2-057 GEN
Solar/Wind Helper
0.03
972237AH1-703 GEN
50/50
5.57
972275AH1-722 GEN
50/50
80.777
945801AF1-245 GEN
50/50
11.91
961241AF2-415 GEN
50/50
29.673
972260AH1-715 GEN1
50/50
31.568
972261AH1-715 GEN2
50/50
33.292
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.449
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.865
G-007ALTFEXP_G-007A->PJM
CMTX
0.823
VFTLTFEXP_VFT->PJM
CMTX
91.483
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.419
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.253
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.81
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.389
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.211
MDUPJM->LTFIMP_MDU
CLTF
0

Details for MINUEST_G-SEWAREN 230.0 kV Ckt 1 line l/o PS_P1-2_R-2218_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_R-2218_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.38 %
Rating:885.0 MVA
Rating Type:B
MVA to Mitigate:985.75
MW Contribution:
5.46
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_R-2218_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.2 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:980.0
MW Contribution:
5.45
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.368
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.183
217118BERGEN 1 ST
50/50
1.211
217138BERGEN_2CT1
50/50
1.563
217139BERGEN_2CT2
50/50
1.563
217140BERGEN_2ST
50/50
2.2
217176GREATFALLS
50/50
0.09
217186ESSEX_G9
50/50
2.937
217191NEC_CT1
50/50
1.855
217192NEC_CT2
50/50
1.855
217193NEC_ST
50/50
2.351
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.367
218418LINDEN_G5
50/50
52.249
218419LINDEN_G6
50/50
52.249
218423LINDEN_G21
50/50
6.012
218424LINDEN_G22
50/50
6.012
218425LINDEN_1201
50/50
6.012
218426LINDEN_2ST
50/50
10.438
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.24
218436LINDEN_1001
50/50
7.362
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.876
219035LINDEN_G8
50/50
42.85
219036LINDEN_G7
50/50
42.85
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.042
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.354
217916BERGEN_12
50/50
1.353
217917BERGEN_13
50/50
1.353
217918BERGEN_14
50/50
1.353
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.463
972275AH1-722 GEN
50/50
79.224
945801AF1-245 GEN
50/50
11.681
961241AF2-415 GEN
50/50
29.102
972260AH1-715 GEN1
50/50
30.96
972261AH1-715 GEN2
50/50
32.651
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.441
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.879
G-007ALTFEXP_G-007A->PJM
CMTX
0.807
VFTLTFEXP_VFT->PJM
CMTX
89.723
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.411
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.248
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.775
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.381
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.188
MDUPJM->LTFIMP_MDU
CLTF
0

Details for MINUEST_G-SEWAREN 230.0 kV Ckt 1 line l/o PS_P7-1_R2218+T2325_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P7-1_R2218+T2325_LT_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.43 %
Rating:885.0 MVA
Rating Type:B
MVA to Mitigate:977.34
MW Contribution:
5.39
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P7-1_R2218+T2325_LT_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:99.36 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:971.7
MW Contribution:
5.38
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.362
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.166
217118BERGEN 1 ST
50/50
1.194
217138BERGEN_2CT1
50/50
1.541
217139BERGEN_2CT2
50/50
1.541
217140BERGEN_2ST
50/50
2.17
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.897
217191NEC_CT1
50/50
1.83
217192NEC_CT2
50/50
1.83
217193NEC_ST
50/50
2.319
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.362
218418LINDEN_G5
50/50
51.463
218419LINDEN_G6
50/50
51.463
218423LINDEN_G21
50/50
5.922
218424LINDEN_G22
50/50
5.922
218425LINDEN_1201
50/50
5.922
218426LINDEN_2ST
50/50
10.281
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.177
218436LINDEN_1001
50/50
7.252
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.863
219035LINDEN_G8
50/50
42.21
219036LINDEN_G7
50/50
42.21
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.043
218526CNTRALGAS2 C
Solar/Wind Helper
0.04
219908AB1-139 C
Solar/Wind Helper
0.04
217915BERGEN_11
50/50
1.335
217916BERGEN_12
50/50
1.334
217917BERGEN_13
50/50
1.334
217918BERGEN_14
50/50
1.334
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.388
972275AH1-722 GEN
50/50
78.032
945801AF1-245 GEN
50/50
11.522
961241AF2-415 GEN
50/50
28.69
972260AH1-715 GEN1
50/50
30.495
972261AH1-715 GEN2
50/50
32.164
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.304
G-007ALTFEXP_G-007A->PJM
CMTX
0.822
VFTLTFEXP_VFT->PJM
CMTX
88.423
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.402
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.243
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.735
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.373
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.161
MDUPJM->LTFIMP_MDU
CLTF
0

Details for MINUEST_G-SEWAREN 230.0 kV Ckt 1 line l/o PS_P7-1_R2218+T2325_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P7-1_R2218+T2325_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.82 %
Rating:885.0 MVA
Rating Type:B
MVA to Mitigate:963.04
MW Contribution:
5.39
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
MINUEST_G-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P7-1_R2218+T2325_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:97.89 %
Rating:978.0 MVA
Rating Type:B
MVA to Mitigate:957.4
MW Contribution:
5.38
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.362
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.166
217118BERGEN 1 ST
50/50
1.194
217138BERGEN_2CT1
50/50
1.541
217139BERGEN_2CT2
50/50
1.541
217140BERGEN_2ST
50/50
2.17
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.897
217191NEC_CT1
50/50
1.83
217192NEC_CT2
50/50
1.83
217193NEC_ST
50/50
2.319
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.362
218418LINDEN_G5
50/50
51.463
218419LINDEN_G6
50/50
51.463
218423LINDEN_G21
50/50
5.922
218424LINDEN_G22
50/50
5.922
218425LINDEN_1201
50/50
5.922
218426LINDEN_2ST
50/50
10.281
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.177
218436LINDEN_1001
50/50
7.252
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.863
219035LINDEN_G8
50/50
42.21
219036LINDEN_G7
50/50
42.21
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.043
218526CNTRALGAS2 C
Solar/Wind Helper
0.04
219908AB1-139 C
Solar/Wind Helper
0.04
217915BERGEN_11
50/50
1.335
217916BERGEN_12
50/50
1.334
217917BERGEN_13
50/50
1.334
217918BERGEN_14
50/50
1.334
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.388
972275AH1-722 GEN
50/50
78.032
945801AF1-245 GEN
50/50
11.522
961241AF2-415 GEN
50/50
28.69
972260AH1-715 GEN1
50/50
30.495
972261AH1-715 GEN2
50/50
32.164
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.304
G-007ALTFEXP_G-007A->PJM
CMTX
0.822
VFTLTFEXP_VFT->PJM
CMTX
88.423
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.402
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.243
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.735
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.373
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.161
MDUPJM->LTFIMP_MDU
CLTF
0

Details for MINUEST_R-SEWAREN 230.0 kV Ckt 1 line l/o PS_P1-2_Q-2348_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
MINUEST_R-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_Q-2348_LT_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.88 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:998.38
MW Contribution:
5.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
MINUEST_R-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P1-2_Q-2348_LT_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.3 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:992.73
MW Contribution:
5.39
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.363
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.169
217118BERGEN 1 ST
50/50
1.197
217138BERGEN_2CT1
50/50
1.544
217139BERGEN_2CT2
50/50
1.544
217140BERGEN_2ST
50/50
2.174
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.903
217191NEC_CT1
50/50
1.834
217192NEC_CT2
50/50
1.834
217193NEC_ST
50/50
2.324
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.363
218418LINDEN_G5
50/50
51.643
218419LINDEN_G6
50/50
51.643
218423LINDEN_G21
50/50
5.942
218424LINDEN_G22
50/50
5.942
218425LINDEN_1201
50/50
5.942
218426LINDEN_2ST
50/50
10.317
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.191
218436LINDEN_1001
50/50
7.277
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.866
219035LINDEN_G8
50/50
42.353
219036LINDEN_G7
50/50
42.353
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.041
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.339
217916BERGEN_12
50/50
1.337
217917BERGEN_13
50/50
1.337
217918BERGEN_14
50/50
1.337
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.4
972275AH1-722 GEN
50/50
78.306
945801AF1-245 GEN
50/50
11.546
961241AF2-415 GEN
50/50
28.765
972260AH1-715 GEN1
50/50
30.602
972261AH1-715 GEN2
50/50
32.273
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.394
G-007ALTFEXP_G-007A->PJM
CMTX
0.798
VFTLTFEXP_VFT->PJM
CMTX
88.684
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.754
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.377
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.174
MDUPJM->LTFIMP_MDU
CLTF
0

Details for MINUEST_R-SEWAREN 230.0 kV Ckt 1 line l/o PS_P2-3_SEW_2-14_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
MINUEST_R-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_SEW_2-14_LT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.88 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:998.38
MW Contribution:
5.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
MINUEST_R-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-3_SEW_2-14_LT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.3 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:992.73
MW Contribution:
5.39
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.363
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.169
217118BERGEN 1 ST
50/50
1.197
217138BERGEN_2CT1
50/50
1.544
217139BERGEN_2CT2
50/50
1.544
217140BERGEN_2ST
50/50
2.174
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.903
217191NEC_CT1
50/50
1.834
217192NEC_CT2
50/50
1.834
217193NEC_ST
50/50
2.324
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.363
218418LINDEN_G5
50/50
51.643
218419LINDEN_G6
50/50
51.643
218423LINDEN_G21
50/50
5.942
218424LINDEN_G22
50/50
5.942
218425LINDEN_1201
50/50
5.942
218426LINDEN_2ST
50/50
10.317
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.191
218436LINDEN_1001
50/50
7.277
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.866
219035LINDEN_G8
50/50
42.353
219036LINDEN_G7
50/50
42.353
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.041
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.339
217916BERGEN_12
50/50
1.337
217917BERGEN_13
50/50
1.337
217918BERGEN_14
50/50
1.337
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.4
972275AH1-722 GEN
50/50
78.306
945801AF1-245 GEN
50/50
11.546
961241AF2-415 GEN
50/50
28.765
972260AH1-715 GEN1
50/50
30.602
972261AH1-715 GEN2
50/50
32.273
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.394
G-007ALTFEXP_G-007A->PJM
CMTX
0.798
VFTLTFEXP_VFT->PJM
CMTX
88.684
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.754
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.377
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.174
MDUPJM->LTFIMP_MDU
CLTF
0

Details for MINUEST_R-SEWAREN 230.0 kV Ckt 1 line l/o PS_P2-2_DEANS_7_LT_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Increase to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:PSEG
Facility Description:
MINUEST_R-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-2_DEANS_7_LT_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.88 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:998.38
MW Contribution:
5.4
Impact of Topology Modeling:
Increase

Base Case Flowgate

Area:PSEG
Facility Description:
MINUEST_R-SEWAREN 230.0 kV Ckt 1 line
Contingency Name:
PS_P2-2_DEANS_7_LT_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.3 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:992.74
MW Contribution:
5.39
Bus #Bus NameTypeMW Contribution
217206BARNGR HS C
Solar/Wind Harmer
0
217208PARK ELE C
Solar/Wind Harmer
0
217209CENTRL HS C
Solar/Wind Harmer
0
217211CAMDEN ST C
Solar/Wind Harmer
0
217213AMBOY SO C
Solar/Wind Helper
0.017
217065ECRRF_1
50/50
0.363
217081WEATEXAS C
Solar/Wind Harmer
0
217118BERGEN 1 ST
50/50
1.169
217118BERGEN 1 ST
50/50
1.197
217138BERGEN_2CT1
50/50
1.544
217139BERGEN_2CT2
50/50
1.544
217140BERGEN_2ST
50/50
2.174
217176GREATFALLS
50/50
0.089
217186ESSEX_G9
50/50
2.903
217191NEC_CT1
50/50
1.834
217192NEC_CT2
50/50
1.834
217193NEC_ST
50/50
2.324
217197RE CRAN C
Solar/Wind Helper
0.013
217323ECRRF_2
50/50
0.363
218418LINDEN_G5
50/50
51.643
218419LINDEN_G6
50/50
51.643
218423LINDEN_G21
50/50
5.942
218424LINDEN_G22
50/50
5.942
218425LINDEN_1201
50/50
5.942
218426LINDEN_2ST
50/50
10.317
218428ETC SOLAR C
Solar/Wind Helper
0.003
218435LINDEN_1101
50/50
4.191
218436LINDEN_1001
50/50
7.277
218438BLK ROCK C
Solar/Wind Helper
0.006
218440SUMMTASSOC C
Solar/Wind Helper
0.01
218449LINSOLAR C
Solar/Wind Harmer
0
218516UCRR
50/50
0.866
219035LINDEN_G8
50/50
42.353
219036LINDEN_G7
50/50
42.353
219612MATRIX C
Solar/Wind Helper
0.007
218524CNTRALGAS1 C
Solar/Wind Helper
0.044
218526CNTRALGAS2 C
Solar/Wind Helper
0.041
219908AB1-139 C
Solar/Wind Helper
0.041
217915BERGEN_11
50/50
1.339
217916BERGEN_12
50/50
1.337
217917BERGEN_13
50/50
1.337
217918BERGEN_14
50/50
1.337
924131AB2-057 GEN
Solar/Wind Helper
0.029
972237AH1-703 GEN
50/50
5.4
972275AH1-722 GEN
50/50
78.306
945801AF1-245 GEN
50/50
11.546
961241AF2-415 GEN
50/50
28.765
972260AH1-715 GEN1
50/50
30.602
972261AH1-715 GEN2
50/50
32.273
219919AE1-041 FULL
Solar/Wind Helper
0.004
217121ECCF
50/50
0.435
CBM NorthLTFEXP_CBM-N->PJM
CBM
41.394
G-007ALTFEXP_G-007A->PJM
CMTX
0.798
VFTLTFEXP_VFT->PJM
CMTX
88.684
GibsonPJM->LTFIMP_GIBSON
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.407
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.245
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.754
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.377
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.174
MDUPJM->LTFIMP_MDU
CLTF
0
CONTINGENCY 'PS_P1-2_R-2218_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 DISCONNECT BUS 218353                            /*MINUEST_R    230.0
END
CONTINGENCY 'PS_P2-3_LIND2_1-9_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 DISCONNECT BUS 218353                            /*MINUEST_R    230.0
END
CONTINGENCY 'PS_P1-2_R-2218_LT_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 DISCONNECT BUS 218353                            /*MINUEST_R    230.0
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218410     /*MINUEST_L1    13.2 - WARINICO_L1   13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218413     /*MINUEST_L1    13.2 - WDBRDG_L3     13.2
END
CONTINGENCY 'PS_P2-3_LIND2_1-9_LT_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 DISCONNECT BUS 218353                            /*MINUEST_R    230.0
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218410     /*MINUEST_L1    13.2 - WARINICO_L1   13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218413     /*MINUEST_L1    13.2 - WDBRDG_L3     13.2
END
CONTINGENCY 'PS_P7-1_R2218+T2325_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 CLOSE LINE FROM BUS 218412 TO BUS 218413 CKT Z   /*WDBRDG_L2     13.2 - WDBRDG_L3     13.2
 CLOSE LINE FROM BUS 218412 TO BUS 218414 CKT Z   /*WDBRDG_L2     13.2 - WDBRDG_L1     13.2
 DISCONNECT BUS 218341                            /*WDBRDG_T     230.0
 DISCONNECT BUS 218353                            /*MINUEST_R    230.0
END
CONTINGENCY 'PS_P7-1_R2218+T2325_LT_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 CLOSE LINE FROM BUS 218412 TO BUS 218413 CKT Z   /*WDBRDG_L2     13.2 - WDBRDG_L3     13.2
 CLOSE LINE FROM BUS 218412 TO BUS 218414 CKT Z   /*WDBRDG_L2     13.2 - WDBRDG_L1     13.2
 DISCONNECT BUS 218341                            /*WDBRDG_T     230.0
 DISCONNECT BUS 218353                            /*MINUEST_R    230.0
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218410     /*MINUEST_L1    13.2 - WARINICO_L1   13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218413     /*MINUEST_L1    13.2 - WDBRDG_L3     13.2
 MOVE 8 MW LOAD FROM BUS 218412 TO BUS 218398     /*WDBRDG_L2     13.2 - NEWDOVR_L1    13.2
 MOVE 8 MW LOAD FROM BUS 218413 TO BUS 218402     /*WDBRDG_L3     13.2 - PRSNAVS_L2    13.2
 MOVE 8 MW LOAD FROM BUS 218413 TO BUS 218411     /*WDBRDG_L3     13.2 - WARINICO_L2   13.2
END
CONTINGENCY 'PS_P1-2_Q-2348_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 DISCONNECT BUS 218354                            /*MINUEST_G    230.0
END
CONTINGENCY 'PS_P2-3_SEW_2-14_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 DISCONNECT BUS 218354                            /*MINUEST_G    230.0
END
CONTINGENCY 'PS_P2-2_DEANS_7_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 DISCONNECT BUS 218354                            /*MINUEST_G    230.0
END
CONTINGENCY 'PS_P1-2_Q-2348_LT_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 DISCONNECT BUS 218354                            /*MINUEST_G    230.0
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218410     /*MINUEST_L1    13.2 - WARINICO_L1   13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218413     /*MINUEST_L1    13.2 - WDBRDG_L3     13.2
END
CONTINGENCY 'PS_P2-3_SEW_2-14_LT_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 DISCONNECT BUS 218354                            /*MINUEST_G    230.0
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218410     /*MINUEST_L1    13.2 - WARINICO_L1   13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218413     /*MINUEST_L1    13.2 - WDBRDG_L3     13.2
END
CONTINGENCY 'PS_P2-2_DEANS_7_LT_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 DISCONNECT BUS 218354                            /*MINUEST_G    230.0
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218410     /*MINUEST_L1    13.2 - WARINICO_L1   13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218413     /*MINUEST_L1    13.2 - WDBRDG_L3     13.2
END
CONTINGENCY 'PS_P2-3_LIND2_9-10_LT_SRT-A'
 CLOSE LINE FROM BUS 218396 TO BUS 218397 CKT Z   /*MINUEST_L2    13.2 - MINUEST_L1    13.2
 DISCONNECT BUS 126284                            /*GOTHLS R     345.0
 DISCONNECT BUS 126321                            /*GOETHALS     230.0
 DISCONNECT BUS 126724                            /*GOETH 13      13.6
 DISCONNECT BUS 218353                            /*MINUEST_R    230.0
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218396 TO BUS 218414     /*MINUEST_L2    13.2 - WDBRDG_L1     13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218410     /*MINUEST_L1    13.2 - WARINICO_L1   13.2
 MOVE 8 MW LOAD FROM BUS 218397 TO BUS 218413     /*MINUEST_L1    13.2 - WDBRDG_L3     13.2
END
218300 to 218354 ckt 1
218300 to 218353 ckt 1
218354 to 218311 ckt 1
218353 to 218311 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-703 was evaluated as a 35.61 MW injection

AH1-703 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 670.61 MW (35.61 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary:

New Service Requests (projects) in PJM Transition Cycle 2, Cluster 93 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 93 projects.

This analysis is effectively a screening study to determine whether the addition of the Cluster 93 projects will meet the dynamics requirements of the NERC, PJM, and Transmission Owner reliability standards.

The load flow scenario for the analysis was based on the RTEP 2028 light load case, modified to include applicable projects. Cluster 93 projects have been dispatched online at maximum power output.

Cluster 93 projects were tested for compliance with NERC, PJM, Transmission Owner and other applicable criteria. Steady-state condition and 374 contingencies were studied, each with a 20 second simulation time period. Studied faults included:

  1. Steady-state operation (20 second run);
  2. Three-phase faults with normal clearing time; (and with unsuccessful high speed reclosing, when applicable);
  3. Single-phase bus faults with normal clearing time;
  4. Single-phase faults with stuck breaker;
  5. Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure;
  6. Single-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing, when applicable).

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism, with all states returning to an acceptable new condition following the disturbance.

For all of the fault contingencies tested on the 2028 light load case:

  1. Cluster 93 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),
  2. The system with Cluster 93 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.
  3. Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).
  4. No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

AH1-703, AH1-710, AH1-715 and AH1-722 meet the leading and lagging PF requirements.

The initial results showed that, when using the standard clearing times provided by PJM for each area, the AH1-710 units tripped due to angle deviation for three P1 contingencies and one P5 contingency involving the loss of the Salem–Hope Creek 500 kV circuit or the Hope Creek–Red Lion 500 kV circuit (P1.04, P1.15, P1.17, and P5.02). Impact study reports for prior uprates of this plant were reviewed, and it was found that shorter clearing times had been used for 500 kV circuit breakers in Salem and nearby substations for uprate H17. Accordingly, these tripping events were addressed, for those contingencies only, by adopting the clearing times used in the impact study report of the prior uprate H17.

In the initial results, the response of all generators associated with the cluster queue projects, as well as some nearby generators, exhibited undamped oscillations under several contingencies. These oscillations were observed to persist beyond 40 seconds of simulation. Further analysis indicated that they were driven by the response of the two AH1-710 units. To address this issue, the voltage regulator gain (Ka) in the excitation system models of the two AH1-710 units was reduced from 500 to 100 pu and from 800 to 100 pu, respectively.

In multiple contingencies (P1.01, P1.02, P1.14, P4.01-P4.04, P4.06, P4.08, P4.27, P4.28, P4.30 and P4.32), a well-damped oscillation is observed in the system response after approximately 15 seconds of simulation. To investigate this, the queue projects were GNETted and the contingencies were re-simulated. The results indicate that these oscillations are not related to the queue projects. Accordingly, the normal simulations for these contingencies were extended to 35 seconds, and it was confirmed that the system remains stable and these oscillations completely damp out.

In three contingencies (P1.01, P1.02, and P1.14), the active power of the two combustion turbine units of AH1-715 (GTG1 and GTG2) settles slightly above the pre-fault value (approximately 1%). Since the deviation is small, occurs in only three contingencies, and does not cause instability in either the system or the units, no further action is required. Further investigation can be conducted upon request.

 

For contingencies in which the corresponding Cluster 93 units are tripped according to the contingency definition (e.g., P1.02), the rotor angle exhibits large deviations because the machine is no longer electrically connected to the system. With electrical torque reduced to zero, the rotor accelerates freely based on its mechanical input and inertia. Consequently, the reported rotor angle drifts relative to the system reference and is not meaningful for stability evaluation.

No mitigations were found to be required.

Table 1: TC2 Cluster 93 Projects

Project

Fuel Type

Transmission Owner

MFO

MWE

MWC

Point of Interconnection

AH1-703

Gas

PSEG

670.61

35.61

51.254

Bergen 230 kV

AH1-710

Nuclear

PSEG

2650.8

256.8

228.2

Salem 500 kV

AH1-715

Gas

PSEG

803.17

127.17

149.369

Linden 230 kV & Linden 138 kV

AH1-722

Gas

PSEG

806.4

130.4

158.1

Linden 230 kV

 

Reactive Power Analysis

The AH1-703 facility met the 0.9 lagging and 1.0 leading power factor requirements for uprate at the generator terminals.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AB1-139Metuchen 26kVIn Service
AB2-057Brunswick 26kVIn Service
AE1-041Edison 4kVIn Service
AF1-245Hudson 230 kVEngineering & Procurement
AF2-415Bergen 138 kVEngineering & Procurement
AH1-715Linden 138kV & 230kVActive
AH1-722Linden 230kVActive

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Study Pending
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b3780.7
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.7
Title
Build new Batavia Road substation (Projected ISD 12/31/2028)
Description
Build Batavia Road substation. Add 4 x 230kV breaker bays
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.8
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.8
Title
Graceton 500 kV substation expansion (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breaker bays, 2x 500/230 kV auto transformer, 1x 500 kV caps
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.9
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.9
Title
Graceton to Batavia Road 230 kV double circuit pole line (Projected ISD 12/31/2028)
Description
Graceton to Batavia Road 230 kV double circuit pole line New rating: 1331 MVA SN/ 1594 MVA SE
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.5
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.5
Title
Build Solley Road substation + Statcom (Projected ISD 12/31/2028)
Description
Build Solley Road substation + Statcom. New STATCOM rating: 350 MVAR Add 4x 230 kV breakers bays.
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.13
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.13
Title
Batavia Road to Riverside 230 kV reconductor
Description
Batavia Road to Riverside 230 kV reconductor New rating: 1941 MVA SN / 2181 MVA SE
Cost Information
Time Estimate
Dec 31 2027

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.11
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3780.11
Title
Brighton Statcom and Capacitor (Projected ISD 12/31/2028)
Description
Brighton Statcom and capacitor New STATCOM rating: 350 MVAR New capacitor rating: 350 MVAR
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.15
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.15
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta.
Cost Information
Time Estimate
Apr 10 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.17
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.17
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub (Transource)
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta (Transource Scope).
Cost Information
Time Estimate
May 31 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.1
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.1
Title
Peach Bottom North upgrades – substation work (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breakers to form a breaker-and-a-half bay.
Cost Information
Time Estimate
Oct 15 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.14
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.14
Title
Reconfigure Cooper transmission feeds by establishing new Cooper-North Delta 230 kV line and rerouting existing transmissions lines by Cooper.
Description
None
Cost Information
Time Estimate
Oct 23 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.16
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.16
Title
Terminate new Cooper-North Delta 230 kV line (Transource Scope) at North Delta 230 kV
Description
None
Cost Information
Time Estimate
Oct 15 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.6
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.6
Title
Build Granite substation + Statcom (Projected ISD 12/31/2028)
Description
Build Granite substation + Statcom. New STATCOM rating: 350 MVAR. Add 4x 230 kV breaker bays.
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.37
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.37
Title
Replace terminal equipment limitations at Conastone 500 kV - on the (existing Peach Bottom-Conastone) or (new Graceton-Conastone) 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.34
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.34
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV and cut into North Delta 500kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.35
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.35
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV (Projected ISD 12/1/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Apr 10 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.36
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.36
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.52
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.52
Title
Reconfigure Peach Bottom North and South 500 kV yards (Projected ISD 12/1/2030)
Description
Reconfigure Peach Bottom North and South yards to allow for termination of 500 kV lines from Peach Bottom to North Delta. North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line.
Cost Information
Time Estimate
Dec 01 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.45
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.45
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Jan 31 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.50
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.50
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Jan 23 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.46
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.46
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Dec 11 2029

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.48
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.48
Title
North Delta termination for the North Delta-High Ridge 500 line (Transource work).
Description
None
Cost Information
Time Estimate
Dec 15 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.51
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.51
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
May 31 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.44
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.44
Title
North Delta termination for the North Delta-High Ridge 500 line (PECO work).
Description
None
Cost Information
Time Estimate
Dec 15 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.31
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.31
Title
Build new North Delta-High Ridge 500 kV line - PECO Portion (Projected ISD 12/1/2030)
Description
None
Cost Information
Time Estimate
Dec 15 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.29
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.29
Title
High Ridge termination for the North Delta-High Ridge 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.27
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.27
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) - Waugh Chapel side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.28
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.28
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) -Brighton side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.26
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.26
Title
Build High Ridge 500 kV substation - Three bay breaker and half configuration (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.32
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.32
Title
Build new North Delta-High Ridge 500 kV line - BGE Portion (Projected ISD 12/31/2030)
Description
Build new North Delta-High Ridge 500 kV line. (~59 miles)
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.30
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.30
Title
High Ridge - Install two 500/230 kV transformers (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.47
Title
Build new Peach Bottom South-North Delta 500 kV line (Projected ISD 12/1/2030)
Description
Build new Peach Bottom South-North Delta 500 kV line – cut in to Peach Bottom tie No. 1 and extending line to North Delta (~1.25 miles new ROW).
Cost Information
Time Estimate
Jan 14 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.42
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.42
Title
Peach Bottom 500kV North bus upgrade (Projected ISD 12/1/2030)
Description
Peach Bottom 500kV North bus upgrade - Replace 11 – Instances of strain bus conductor used for breaker drops or CT drops, 7 – 500 kV disconnect switches, 7 – Free Standing CTs, 1 – 500 kV breaker, 2 – Breaker relays or meters.
Cost Information
Time Estimate
Dec 01 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.49
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.49
Title
North Delta 500 kV termination for the Calpine generator (Calpine/Transource work).
Description
None
Cost Information
Time Estimate
Oct 06 2027

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3737.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3737.47
Title
Build New North Delta 500 kV substation (Four bay breaker and half configuration)
Description
Build New North Delta 500 kV substation (four bay breaker and half configuration) - the substation will include 12 - 500kV breakers and one 500/230 kV transformer, will allow the termination of six - 500 kV lines
Cost Information
Time Estimate
Oct 06 2027

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3800.33
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.33
Title
Replace terminal equipment limitations at Brighton 500 kV - on the existing Brighton-Waugh Chapel 500 kV (5053) or new Brighton-High Ridge 500 kV.
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.2
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.2
Title
Peach Bottom to Graceton (PECO Portion) – New 500kV Line
Description
Peach Bottom to Graceton (PECO Portion) – New 500kV Line. New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Oct 23 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3780.4
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.4
Title
Peach Bottom to Graceton (BGE Portion) – New 500kV Line
Description
New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Dec 31 2028

Not ContingentTopology Changing

Note 1: AH1-703 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-703 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
PCHBTM1S-PCHBTM2S 500.0 kV Ckt Z1 line(Any)
No new ratings for this Flowgate.
PCHBTM1N-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: n9751.0
Type
Load Flow
TO
PSEG
RTEP ID / TO ID
n9751.0 / PSEG-TC2_PH1_LindenMinueQ
Title
Upgrade Linden to Minue St Q-2348 230 kV
Description
Upgrade circuit to 1590kcmil Falcon ACSS to achieve a rating of 934/1080 SNR/SER.
Total Cost ($USD)
$9,183,000
Discounted Total Cost ($USD)
$9,183,000
Allocated Cost ($USD)
$0
Time Estimate
30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-703 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-703 could receive cost allocation. Although AH1-703 may not presently have cost responsibility for this upgrade, AH1-703 is a potential Aggregate Pool Contributor.

FacilityContingency
LINDEN-MINUEST_G 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA934.0 MVA
SUMB1080.0 MVA
WINA999.0 MVA
WINB1143.0 MVA

System Reinforcement: n9715.0
Type
Load Flow
TO
PSEG
RTEP ID / TO ID
n9715.0 / PSEG-TC2_PH1_LindenMinueR
Title
Upgrade Linden to Minue St R-2218 230 kV circuit
Description
Upgrade circuit to 1590kcmil Falcon ACSS to achieve a rating of 934/1080 SNR/SER.
Total Cost ($USD)
$9,000,000
Discounted Total Cost ($USD)
$9,000,000
Allocated Cost ($USD)
$0
Time Estimate
30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-703 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-703 could receive cost allocation. Although AH1-703 may not presently have cost responsibility for this upgrade, AH1-703 is a potential Aggregate Pool Contributor.

FacilityContingency
LINDEN-MINUEST_R 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA934.0 MVA
SUMB1080.0 MVA
WINA999.0 MVA
WINB1143.0 MVA

System Reinforcement: n9752.0
Type
Load Flow
TO
PSEG
RTEP ID / TO ID
n9752.0 / PSEG-TC2_PH1_MinueSewarenQ
Title
Upgrade Minue St to Sewaren Q-2348 230kV circuit
Description
Upgrade circuit to 1590kcmil Falcon ACSS to achieve a rating of 934/1080 SNR/SER.
Total Cost ($USD)
$8,180,000
Discounted Total Cost ($USD)
$8,180,000
Allocated Cost ($USD)
$0
Time Estimate
30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-703 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-703 could receive cost allocation. Although AH1-703 may not presently have cost responsibility for this upgrade, AH1-703 is a potential Aggregate Pool Contributor.

FacilityContingency
SEWAREN-MINUEST_G 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA934.0 MVA
SUMB1080.0 MVA
WINA999.0 MVA
WINB1143.0 MVA

System Reinforcement: n9716.0
Type
Load Flow
TO
PSEG
RTEP ID / TO ID
n9716.0 / PSEG-TC2_PH1_MinueSewarenR
Title
Upgrade Minue St to Sewaren R-2218 230kV circuit
Description
Upgrade circuit to 1590kcmil Falcon ACSS to achieve a rating of 934/1080 SNR/SER.
Total Cost ($USD)
$8,332,000
Discounted Total Cost ($USD)
$8,332,000
Allocated Cost ($USD)
$0
Time Estimate
30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AH1-703 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AH1-703 could receive cost allocation. Although AH1-703 may not presently have cost responsibility for this upgrade, AH1-703 is a potential Aggregate Pool Contributor.

FacilityContingency
SEWAREN-MINUEST_R 230.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
SUMA934.0 MVA
SUMB1080.0 MVA
WINA999.0 MVA
WINB1143.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-703


AH1-703 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-703 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-703 One Line Diagram

AH1-703 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.