AH1-704 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:21

Hannibal 138 kV

20.0 MW Capacity / 24.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Long Ridge Energy Generation LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is AEP Ohio Transmission Company, Inc..

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $0 $0 = ∞ AND ( $0 - $0 ) 24.0 = $0 per MW

General

The Project Developer has proposed an uprate to a planned/existing Natural Gas facility located in the AEP Ohio Transmission Company, Inc. zone — Monroe County, Ohio. This project is an increase to the developer’s AB2-093 project(s), which will share the same Point of Interconnection. The AH1-704 project is a 24.0 MW uprate (20.0 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 509.0 MW with 505.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-704
Project Name:
Hannibal 138 kV
Project Developer Name:
Long Ridge Energy Generation LLC
State:
Ohio
County:
Monroe
Transmission Owner:
AEP Ohio Transmission Company, Inc.
MFO:
509.0
MWE:
24.0
MWC:
20.0
Fuel Type:
Natural Gas
Basecase Study Year:
2028

Physical Interconnection Facility Study

Not Required

A Physical Interconnection Facilities Study is not required for this project.

Point of Interconnection

AH1-704 will interconnect on the American Electric Power system at the Hannibal 138 kV Substation. 

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-704 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-704Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$0$0$0
Other Scope$0$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0$0
Network Upgrades$0$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$0$0$0

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-704

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-704
Project ID: AH1-704
20% of cost allocation for Phase II Network Upgrades:(A) $0
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $108,000
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

No interconnections facilities required to support the interconnection

(Pending Facilities Study)$0$0
Developer Build Option

(No Developer Build Option for this project.)

Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$0$0
Developer Build Option(No Developer Build Option)

Based on the scope of work for the Interconnection Facilities, it is expected to take 0 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

No Transmission Owner impacts identified.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-704 was evaluated as a 24.0 MW (20.0 MW Capacity) injection in the AEP area.

AH1-704 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 509.0 MW (24.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.25 %3729.0B5006.21
2.66
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.4 %3729.0B4974.31
2.67
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC133.01 %3729.0B4959.97
2.68
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC133.01 %3729.0B4959.97
2.68
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.87 %3729.0B4917.49
2.68
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.69 %3729.0B4873.53
3.1
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.24 %3729.0B4632.89
2.77
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC135.56 %3792.0B5140.38
2.66
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC134.72 %3792.0B5108.61
2.67
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC134.34 %3792.0B5094.21
2.68
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC134.34 %3792.0B5094.21
2.68
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC133.22 %3792.0B5051.83
2.68
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC132.01 %3792.0B5005.84
3.1
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.57 %3792.0B4761.71
2.77

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.25 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:5006.21
MW Contribution:
2.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962761AG1-125 GEN
Solar/Wind Harmer
41.016
270520AE2-214 GEN
Solar/Wind Harmer
7.243
270391AF1-285 GEN3
Solar/Wind Harmer
1.393
253333AC1-068 GEN
Solar/Wind Harmer
1.191
270317AD1-130_GEN
Solar/Wind Harmer
3.64
270273AD2-016 GEN
Solar/Wind Harmer
3.013
25326309TAIT D
Adder
1.195
241813AF1-122_GEN
Solar/Wind Harmer
5.897
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.062
270437AC2-090 C
Solar/Wind Harmer
5.862
270216AD2-079_GEN
Solar/Wind Harmer
0.634
274754CRETE EC ;4U
Adder
8.473
274802UNIV PARK;5U
Adder
5.968
274732ELWOOD EC;7P
Adder
16.762
274674JOLIET 9 ;6U
Adder
15.699
235067AD1-061 GEN
Solar/Wind Helper
0.451
237002AB1-128_GEN
Solar/Wind Helper
0.448
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.118
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.313
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.443
961331AF2-424 GEN
Solar/Wind Helper
0.442
270224U2-072_GEN2
Solar/Wind Harmer
2.274
270291AC1-194 GEN
Solar/Wind Harmer
5.61
253406AD2-031_GEN
Solar/Wind Harmer
1.383
965051AG1-369 GEN
Solar/Wind Harmer
5.355
270377AD1-106 GEN
Solar/Wind Harmer
5.62
971985AH1-537 GEN
Solar/Wind Harmer
18.964
945581AF1-223 GEN
Solar/Wind Harmer
4.795
971029AG2-637 GEN
Solar/Wind Harmer
15.851
970031AG2-029 GEN
Solar/Wind Harmer
26.415
270404AC1-167 GEN
Solar/Wind Harmer
1.144
247536S-71 GEN
Solar/Wind Harmer
4.271
961761AG1-017 GEN
Solar/Wind Harmer
0.451
274775LINCOLN ;6U
Adder
8.673
274777LINCOLN ;8U
Adder
8.673
24318905MLG2
50/50
7.027
270349AD2-093_GEN
Solar/Wind Harmer
4.455
270471AD2-092_GEN
Solar/Wind Harmer
4.455
253383AE2-342_GEN
Solar/Wind Harmer
1.04
25322209TAIT E
Adder
10.635
25322209TAIT E
Adder
10.396
253370AE2-315 SEC1
Adder
2.18
270246TR4_N_V150
Solar/Wind Harmer
0.912
247621Y3-024
Adder
0.255
316097T157 G90
Solar/Wind Helper
1.515
238147AE2-230_GEN1
Solar/Wind Helper
0.501
237080AD1-060 GEN
Solar/Wind Helper
0.346
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.028
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
962771AG1-126 GEN
Solar/Wind Harmer
41.016
970153AG2-106 GEN
Solar/Wind Harmer
17.885
270284AF1-227 GEN1
Solar/Wind Harmer
6.768
24721905FLATG4
Adder
24.045
276820AF1-078_GEN
Solar/Wind Harmer
1.776
960071AF2-298 GEN
Solar/Wind Harmer
1.647
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
253317AC1-085 GEN4
Solar/Wind Harmer
8.992
946181AF1-283 GEN
Solar/Wind Harmer
13.963
24695305TIMB G C
Solar/Wind Harmer
3.573
270588AE1-091_GEN
Solar/Wind Harmer
11.753
252519AF1-045_GEN
Solar/Wind Harmer
3.859
252524AE2-267 GEN
Solar/Wind Harmer
1.667
25194608D.CRK4
Adder
1.739
946031AF1-268 GEN
Solar/Wind Harmer
8.725
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.137
24728505AND G1
Adder
3.925
274676JOLIET 29;8U
Adder
30.174
274734ELWOOD EC;8P
Adder
16.762
274736ELWOOD EC;9P
Adder
16.762
274682WAUKEGAN ;7U
Adder
18.178
964991AG1-363 GEN
Solar/Wind Helper
5.171
238110AE1-109 GEN3
Solar/Wind Helper
0.115
235063AE1-101 C2
Solar/Wind Helper
1.678
205932AD2-116_GEN
Solar/Wind Helper
0.514
233996TM1833_GEN
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
316447AC1-158 HLD
Solar/Wind Helper
2.876
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.526
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
270166AC1-044 GEN3
50/50
7.109
270485AE1-090_GEN
Solar/Wind Harmer
0.688
972269AH1-719 GEN
Adder
2.545
253398AE2-221_GEN2
Solar/Wind Harmer
4.9
246936BC-WTG1
Solar/Wind Harmer
4.216
270489AE1-102 GEN1
Solar/Wind Harmer
1.401
965011AG1-365 GEN
Solar/Wind Harmer
10.725
958861AF2-177 GEN
Solar/Wind Harmer
11.586
252510AF1-249 C
Solar/Wind Harmer
0.441
945371AF1-202 GEN
Solar/Wind Harmer
7.376
270005AE1-210 C O1
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
6.717
270209AC1-174_GEN
Solar/Wind Harmer
4.274
270239V3-007_GEN1
Solar/Wind Harmer
1.807
270331AC1-082 GEN3
Solar/Wind Harmer
0.501
25196808ZIMRHP
Adder
79.685
970825AG2-519 GEN
Solar/Wind Harmer
2.203
25196008MFTGT1
Adder
1.45
274751CRETE EC ;1U
Adder
8.473
274773LINCOLN ;4U
Adder
8.673
274774LINCOLN ;5U
Adder
8.673
274723RIVER EC ;12
Adder
18.412
23583801GRNGAP
Solar/Wind Helper
5.644
238126S14_GEN_1
Solar/Wind Helper
0.836
237085AD2-009_GEN
Solar/Wind Helper
1.667
3141196NOKESVL
Solar/Wind Helper
1.039
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.235
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.091
209116AE2-175 GEN
Solar/Wind Helper
1.799
961421AF2-433 GEN
Solar/Wind Helper
0.441
270594AE1-207 GEN
Solar/Wind Harmer
13.371
270032AE2-172
Solar/Wind Harmer
4.579
270459AD2-067 GEN
Solar/Wind Harmer
10.212
940611AE2-048 GEN
Solar/Wind Harmer
24.76
941391AE2-136 GEN
Solar/Wind Harmer
12.83
270435AC2-044 GEN
Solar/Wind Harmer
2.156
270007AE1-245 C
Solar/Wind Harmer
5.779
24729505KEY G4
Adder
6.914
971567AH1-282 GEN
Solar/Wind Harmer
5.316
270071AF1-092 GEN
Solar/Wind Harmer
15.971
958711AF2-162 GEN
Solar/Wind Harmer
1.074
25196408WSDLE3
Adder
9.339
25196308WSDLE2
Adder
9.258
25196208WSDLE1
Adder
9.235
25196708WSDLE6
Adder
9.211
270543AE2-219 C
Solar/Wind Harmer
10.561
25196108MFTGT2
Adder
1.598
25196108MFTGT2
Adder
1.484
274728ELWOOD EC;5P
Adder
16.762
20390526W1-045 C
Solar/Wind Helper
0.354
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.078
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.036
270051AF1-062 GEN
50/50
11.798
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
970879AG2-548 GEN
Solar/Wind Harmer
8.771
970065AG2-057 GEN
Solar/Wind Harmer
0.921
253394AE2-221_GEN
Solar/Wind Harmer
4.9
246938BC-WTG3
Solar/Wind Harmer
4.289
971191AH1-055 GEN
Solar/Wind Harmer
20.077
965021AG1-366 GEN
Solar/Wind Harmer
2.494
270043AE2-236 GEN
Solar/Wind Harmer
5.865
270367AC2-061_GEN
Solar/Wind Harmer
3.367
270044AE2-322 C
Solar/Wind Harmer
1.388
962031AG1-047 GEN
Solar/Wind Harmer
3.189
957741AF2-068 GEN
Solar/Wind Harmer
15.82
270512AE1-227 GEN2
Solar/Wind Harmer
2.212
270186AC1-089 GEN
Solar/Wind Harmer
6.425
270240V3-007_GEN2
Solar/Wind Harmer
6.498
970825AG2-519 GEN
Solar/Wind Harmer
5.915
25196008MFTGT1
Adder
1.404
274772LINCOLN ;3U
Adder
8.673
274724RIVER EC ;11
Adder
18.196
972259AH1-714 GEN
Adder
19.5
274729ELWOOD EC;1P
Adder
16.762
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.186
316415AF1-147_GEN2
Solar/Wind Helper
0.898
205916AD1-020 GEN
Solar/Wind Helper
1.732
233944AB2-135 GEN
Solar/Wind Helper
0.596
232408W1-005 C
Solar/Wind Helper
0.513
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.075
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.093
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
23559101PLEAS2
50/50
6.362
970149AG2-104 GEN
Solar/Wind Harmer
25.328
270286AF1-227 GEN2
Solar/Wind Harmer
2.504
270578AF1-285 GEN2
Solar/Wind Harmer
1.393
971073AG2-665 GEN
Solar/Wind Harmer
1.275
960001AF2-291 GEN
Solar/Wind Harmer
3.25
270258AD1-119 GEN
Solar/Wind Harmer
2.156
270297AD1-101 GEN
Solar/Wind Harmer
2.147
270222AC2-111 GEN
Solar/Wind Harmer
4.718
270510AE1-227 GEN1
Solar/Wind Harmer
2.605
970091AG2-072 GEN
Adder
77.647
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.283
233987AB2-037 GEN
Solar/Wind Helper
2.369
232417X3-008 C
Solar/Wind Helper
0.235
233923SMA
Solar/Wind Helper
0.76
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.329
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
957921AF2-086 GEN
Solar/Wind Helper
0.436
972037AH1-567 GEN1
Adder
0.187
23559001PLEAS1
50/50
6.362
961921AG1-034 GEN
Solar/Wind Harmer
15.551
270287AF1-227 GEN3
Solar/Wind Harmer
2.504
942051AE2-217 GEN
Solar/Wind Harmer
20.995
942871AE2-306 GEN
Solar/Wind Harmer
1.045
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
958581AF2-149 GEN
Solar/Wind Harmer
4.712
957541AF2-048 GEN
Solar/Wind Harmer
1.717
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.358
25196608WSDLE5
Adder
9.072
252507AC2-088 GEN
Solar/Wind Harmer
1.892
270063AE2-323 C
Solar/Wind Harmer
2.32
971347AH1-153 GEN
Solar/Wind Harmer
5.266
270330AC1-082 GEN2
Solar/Wind Harmer
0.5
274752CRETE EC ;2U
Adder
8.473
24728705AND G3
Adder
8.209
274826FISK ;BP
Adder
11.201
274730ELWOOD EC;6P
Adder
16.762
238127S14_GEN_2
Solar/Wind Helper
0.836
238152AF2-075_GEN
Solar/Wind Helper
0.715
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.513
316044AC1-158 PL1
Solar/Wind Helper
1.307
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.586
202652Y1-033 WT C
Solar/Wind Helper
0.504
270120AB2-067 GEN2
50/50
7.109
270054AF2-122 C O1
Solar/Wind Harmer
3.972
938701AE1-092 GEN
Solar/Wind Harmer
23.766
270462AD2-086
Solar/Wind Harmer
7.908
253415AE1-040 GEN
Solar/Wind Harmer
1.242
253349AC2-067 GEN
Solar/Wind Harmer
2.203
270247TR4_N_V136
Solar/Wind Harmer
0.912
942801AE2-298 GEN
Solar/Wind Harmer
1.621
960971AF2-388 GEN
Solar/Wind Harmer
11.601
25194408D.CRK1
Adder
8
970883AG2-550 GEN
Solar/Wind Harmer
10.561
970349AG2-230 GEN
Solar/Wind Harmer
15.797
270599AE1-208 GEN
Solar/Wind Harmer
8.576
926881AC1-175 GEN
Solar/Wind Harmer
5.862
944231AF1-091 GEN
Solar/Wind Harmer
18.887
24728905RICHG2
Adder
3.96
274808UNIV PK N;4U
Adder
5.115
274674JOLIET 9 ;6U
Adder
15.699
274693ROCKY RD ;1P
Adder
11.156
274683WAUKEGAN ;8U
Adder
21.305
274683WAUKEGAN ;8U
Adder
9.68
23585401KL_K28_T16
Solar/Wind Helper
1.5
238117U2-030
Solar/Wind Helper
0.345
238148AE2-230_GEN2
Solar/Wind Helper
0.501
235062AE1-101 C1
Solar/Wind Helper
1.678
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.371
232424Y1-079 C
Solar/Wind Helper
0.118
232428Y3-058 C
Solar/Wind Helper
0.342
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.293
20675428EAM_W2-061
Solar/Wind Helper
0.016
970155AG2-107 GEN
Solar/Wind Harmer
17.885
971995AH1-542 GEN
Solar/Wind Harmer
12.463
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
965421AG1-410 GEN
Solar/Wind Harmer
32.318
253316AC1-085 GEN3
Solar/Wind Harmer
8.992
946171AF1-282 GEN
Solar/Wind Harmer
10.741
965651AG1-433 GEN
Solar/Wind Harmer
5.801
252516AE2-318_GEN
Solar/Wind Harmer
10.604
270024AE2-089 GEN
Solar/Wind Harmer
4.961
25194608D.CRK4
Adder
1.739
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.137
24728605AND G2
Adder
3.925
274676JOLIET 29;8U
Adder
31.291
972203AH1-686 GEN
Adder
2.344
274745AC1-111 GEN9
Adder
5.677
274682WAUKEGAN ;7U
Adder
18.178
316095T157 G97
Solar/Wind Helper
1.515
238185AF2-356 C
Solar/Wind Helper
2.686
238109AE1-109 GEN2
Solar/Wind Helper
0.115
238120AE2-309 GEN
Solar/Wind Helper
0.534
23751101LEADS_P59
Solar/Wind Helper
2.15
23777801MSM_W1-116
Solar/Wind Helper
0.116
227287AC2-120 GEN
Solar/Wind Helper
0.35
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.513
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.501
24318805MLG1
50/50
10.127
270475AD2-096_GEN
50/50
7.137
270518AE2-148 GEN
Solar/Wind Harmer
13.818
253325AC1-069 GEN
Solar/Wind Harmer
1.191
971199AH1-059 GEN
Solar/Wind Harmer
2.312
270491AE1-102 GEN2
Solar/Wind Harmer
1.401
270004AE1-209 GEN
Solar/Wind Harmer
5.743
24379505HDWTR1G C
Solar/Wind Harmer
8.305
270329AC1-082 GEN1
Solar/Wind Harmer
0.5
274753CRETE EC ;3U
Adder
8.473
274814UNIV PK N;0U
Adder
5.182
274807UNIV PK N;3U
Adder
5.171
274803UNIV PARK;6U
Adder
5.968
972038AH1-567 GEN2
Adder
0.373
238108AE1-109 GEN1
Solar/Wind Helper
0.115
23562501BACKB
Solar/Wind Helper
1.023
237001AB1-127_GEN
Solar/Wind Helper
0.446
233918AB1-142 GEN
Solar/Wind Helper
0.508
228729W2-030 C
Solar/Wind Helper
0.112
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.443
963151AG1-164 GEN
Solar/Wind Helper
0.443
961341AF2-425 GEN
Solar/Wind Helper
0.442
946101AF1-275 GEN
Solar/Wind Harmer
1.811
942861AE2-305 GEN
Solar/Wind Harmer
9.069
270269AC2-059
Solar/Wind Harmer
10.571
972159AH1-661 GEN
Adder
1.106
241960AC2-195 GEN
Solar/Wind Harmer
3.055
971073AG2-665 GEN
Solar/Wind Harmer
8.771
25326109MON D
Adder
1.442
927014AC1-188 GEN
Solar/Wind Harmer
1.717
253400AC2-068 GEN
Solar/Wind Harmer
0.886
25183208HLCRTG
Solar/Wind Harmer
6.427
944541AF1-119 GEN
Solar/Wind Harmer
4.444
25194508D.CRK3
Adder
1.496
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.456
270201AC2-176 GEN
Solar/Wind Harmer
5.42
964611AG1-324 GEN
Solar/Wind Harmer
0.551
270031AE2-169
Solar/Wind Harmer
8.576
270383AD1-128 GEN
Solar/Wind Harmer
6.419
247620Y3-023
Adder
0.483
24728805RICHG1
Adder
3.96
274695ROCKY RD ;2P
Adder
11.267
235054AD2-180 GEN
Solar/Wind Helper
2.054
235531U2-073 GEN
Solar/Wind Helper
3.347
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.972
316045AC1-158 PL2
Solar/Wind Helper
4.182
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
20674328GAR_V4-001
Solar/Wind Helper
0.023
972228AH1-698 GEN2
Adder
3.789
274675JOLIET 29;7U
Adder
31.291
274675JOLIET 29;7U
Adder
30.174
23750701CROSSCHOOL
Solar/Wind Helper
1.517
205943AE1-185 GEN
Solar/Wind Helper
0.515
233915AB1-141 GEN
Solar/Wind Helper
0.508
228728W1-130C
Solar/Wind Helper
0.055
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
203955AF1-039 C O1
Solar/Wind Helper
0.332
212266LOR1
Solar/Wind Helper
0.302
961821AG1-024 GEN
Solar/Wind Harmer
10.368
972239AH1-704 GEN
Adder
2.66
945631AF1-228 GEN
Solar/Wind Harmer
5.449
270223U2-072_GEN1
Solar/Wind Harmer
2.274
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
8.025
253338AC1-165 GEN
Solar/Wind Harmer
1.235
270263AC1-001 GEN
Solar/Wind Harmer
1.17
241972AD1-140 GEN
Solar/Wind Harmer
5.01
270340AC2-060 GEN
Solar/Wind Harmer
3.331
270191TR4_S_V150
Solar/Wind Harmer
3.216
959331AF2-224 GEN
Solar/Wind Harmer
10.725
965041AG1-368 GEN
Solar/Wind Harmer
10.701
966831AG1-554 GEN
Solar/Wind Harmer
1.275
25196508WSDLE4
Adder
8.979
964611AG1-324 GEN
Solar/Wind Harmer
4.11
274776LINCOLN ;7U
Adder
8.673
274687WILL CNTY;4U
Adder
28.512
274687WILL CNTY;4U
Adder
28.512
274731ELWOOD EC;2P
Adder
16.762
274733ELWOOD EC;3P
Adder
16.762
274746AC1-111 G10
Adder
5.677
238118U2-030_1
Solar/Wind Helper
0.345
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.647
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.372
205956AE1-196_GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.235
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
20720628TIN_W1-124
Solar/Wind Helper
0.192
316164AC1-076 GEN
Solar/Wind Helper
1.108
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.069
20675128HRM_W1-127
Solar/Wind Helper
0.03
241955AC1-078 GEN
Solar/Wind Harmer
8.781
241973AD2-163_GEN1
Solar/Wind Harmer
2.319
241974AD2-163_GEN2
Solar/Wind Harmer
2.319
943861AF1-054 GEN
Solar/Wind Harmer
4.476
943851AF1-053 GEN
Solar/Wind Harmer
2.163
270227U2-072_GEN3
Solar/Wind Harmer
2.274
270228U2-072_GEN4
Solar/Wind Harmer
2.274
270231U2-072_GEN5
Solar/Wind Harmer
2.274
253343AC1-166 GEN
Solar/Wind Harmer
1.235
270302AB2-170 GEN
Solar/Wind Harmer
9.522
970179AG2-119 GEN
Solar/Wind Harmer
8.806
253372AE2-315 SEC3
Adder
2.062
253372AE2-315 SEC3
Adder
2.062
25306009OHH W.
Adder
3.128
957201AF2-014 GEN
Solar/Wind Harmer
4.888
253433AC1-085 GEN1
Solar/Wind Harmer
5.708
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.604
963791AG1-232 GEN
Solar/Wind Harmer
14.371
274827FISK ;RP
Adder
7.938
274800UNIV PARK;3U
Adder
5.964
274801UNIV PARK;4U
Adder
5.964
972227AH1-698 GEN1
Adder
2.668
274735ELWOOD EC;4P
Adder
16.762
274744AC1-111 GEN8
Adder
5.677
238169AE2-226 GEN1
Solar/Wind Helper
0.708
238170AE2-226 GEN2
Solar/Wind Helper
0.708
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.36
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.795
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.064
207408W3-077 C
Solar/Wind Helper
0.085
209054AE2-059 GEN
Solar/Wind Helper
0.08
270119AB2-067 GEN1
50/50
7.109
253378AE2-206_GEN
Solar/Wind Harmer
3.997
25326509SID D
Adder
1.451
970879AG2-548 GEN
Solar/Wind Harmer
1.275
246937BC-WTG2
Solar/Wind Harmer
4.216
247607V1-011 GEN
Solar/Wind Harmer
4.231
962581AG1-107 GEN
Solar/Wind Harmer
5.356
961491AF2-440 GEN
Solar/Wind Harmer
2.226
942221AE2-234 GEN
Solar/Wind Harmer
3.71
274770LINCOLN ;1U
Adder
8.673
274771LINCOLN ;2U
Adder
8.673
274805UNIV PK N;1U
Adder
5.149
274696ROCKY RD ;4P
Adder
11.533
274697ROCKY RD ;3P
Adder
3.061
23751201ROTHROCK
Solar/Wind Helper
0.836
235020AA1-095 C
Solar/Wind Helper
0.054
237061AD1-155 GEN
Solar/Wind Helper
1.772
238221AF1-254 C O1
Solar/Wind Helper
0.278
316411AF1-147_GEN1
Solar/Wind Helper
0.898
223402AF1-300 C
Solar/Wind Helper
0.371
233930AB2-032 GEN
Solar/Wind Helper
0.385
233982AB2-133 GEN
Solar/Wind Helper
0.363
233946AB2-136 GEN
Solar/Wind Helper
0.575
232410W1-006 C
Solar/Wind Helper
0.513
233952AC2-187 GEN
Solar/Wind Helper
0.235
233954AC2-188 GEN
Solar/Wind Helper
0.235
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.051
207471AF2-354 C
Solar/Wind Helper
0.17
961431AF2-434 GEN
Solar/Wind Helper
0.441
212507AE2-042_GEN
Solar/Wind Helper
1.561
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.944
NYPJM->LTFIMP_NY
CLTF
4.85
TVALTFEXP_TVA->PJM
CLTF
7.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.743
LGEELTFEXP_LGEE->PJM
CLTF
6.747
MECLTFEXP_MEC->PJM
CLTF
15.894
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.079
WECLTFEXP_WEC->PJM
CLTF
3.823
LAGNLTFEXP_LAGN->PJM
CLTF
14.823
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.742
CPLELTFEXP_CPLE->PJM
CLTF
0.593
SIGELTFEXP_SIGE->PJM
CLTF
0.505

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.4 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4974.31
MW Contribution:
2.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962761AG1-125 GEN
Solar/Wind Harmer
40.857
270520AE2-214 GEN
Solar/Wind Harmer
7.233
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.008
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.894
971201AH1-060 GEN
Solar/Wind Harmer
1.842
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.845
24318905MLG2
50/50
7.035
270349AD2-093_GEN
Solar/Wind Harmer
4.445
270471AD2-092_GEN
Solar/Wind Harmer
4.445
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.371
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.5
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
962771AG1-126 GEN
Solar/Wind Harmer
40.857
970153AG2-106 GEN
Solar/Wind Harmer
17.815
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.892
276820AF1-078_GEN
Solar/Wind Harmer
1.772
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
24695305TIMB G C
Solar/Wind Harmer
3.564
270588AE1-091_GEN
Solar/Wind Harmer
11.739
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.7
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.122
24728505AND G1
Adder
3.913
274676JOLIET 29;8U
Adder
30.081
274734ELWOOD EC;8P
Adder
16.71
274736ELWOOD EC;9P
Adder
16.71
274682WAUKEGAN ;7U
Adder
18.122
964991AG1-363 GEN
Solar/Wind Helper
5.16
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.674
205932AD2-116_GEN
Solar/Wind Helper
0.513
233996TM1833_GEN
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.519
20714528FRN_Y2-051
Solar/Wind Helper
0.057
270166AC1-044 GEN3
50/50
7.082
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.564
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.696
958861AF2-177 GEN
Solar/Wind Harmer
11.552
252510AF1-249 C
Solar/Wind Harmer
0.44
945371AF1-202 GEN
Solar/Wind Harmer
7.355
270005AE1-210 C O1
Solar/Wind Harmer
5.726
25196808ZIMRHP
Adder
79.465
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
942081AE2-220 GEN
Solar/Wind Harmer
6.698
270209AC1-174_GEN
Solar/Wind Harmer
4.262
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.448
274773LINCOLN ;4U
Adder
8.646
274774LINCOLN ;5U
Adder
8.646
274723RIVER EC ;12
Adder
18.356
23583801GRNGAP
Solar/Wind Helper
5.632
238126S14_GEN_1
Solar/Wind Helper
0.833
237085AD2-009_GEN
Solar/Wind Helper
1.663
270459AD2-067 GEN
Solar/Wind Harmer
10.203
940611AE2-048 GEN
Solar/Wind Harmer
24.928
941391AE2-136 GEN
Solar/Wind Harmer
12.917
270435AC2-044 GEN
Solar/Wind Harmer
2.151
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.319
24729505KEY G4
Adder
6.894
270071AF1-092 GEN
Solar/Wind Harmer
15.924
958711AF2-162 GEN
Solar/Wind Harmer
1.071
25196408WSDLE3
Adder
9.314
25196308WSDLE2
Adder
9.233
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.531
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.48
274728ELWOOD EC;5P
Adder
16.71
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
270051AF1-062 GEN
50/50
11.783
960801AF2-371 GEN
Solar/Wind Harmer
2.935
964871AG1-351 GEN
Solar/Wind Harmer
2.026
970879AG2-548 GEN
Solar/Wind Harmer
8.757
23559101PLEAS2
50/50
6.18
970149AG2-104 GEN
Solar/Wind Harmer
25.229
23559001PLEAS1
50/50
6.18
961921AG1-034 GEN
Solar/Wind Harmer
15.539
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.96
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.716
957541AF2-048 GEN
Solar/Wind Harmer
1.713
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.25
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.25
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.448
24728705AND G3
Adder
8.184
274826FISK ;BP
Adder
11.167
274730ELWOOD EC;6P
Adder
16.71
238127S14_GEN_2
Solar/Wind Helper
0.833
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.582
202652Y1-033 WT C
Solar/Wind Helper
0.501
270120AB2-067 GEN2
50/50
7.082
270054AF2-122 C O1
Solar/Wind Harmer
3.971
938701AE1-092 GEN
Solar/Wind Harmer
23.731
270462AD2-086
Solar/Wind Harmer
7.892
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
960971AF2-388 GEN
Solar/Wind Harmer
11.568
25194408D.CRK1
Adder
7.978
970883AG2-550 GEN
Solar/Wind Harmer
10.531
970349AG2-230 GEN
Solar/Wind Harmer
15.75
270599AE1-208 GEN
Solar/Wind Harmer
8.551
926881AC1-175 GEN
Solar/Wind Harmer
5.845
944231AF1-091 GEN
Solar/Wind Harmer
18.84
24728905RICHG2
Adder
3.949
274808UNIV PK N;4U
Adder
5.099
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
970155AG2-107 GEN
Solar/Wind Harmer
17.815
971995AH1-542 GEN
Solar/Wind Harmer
12.451
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.241
946101AF1-275 GEN
Solar/Wind Harmer
1.808
942861AE2-305 GEN
Solar/Wind Harmer
9.053
270269AC2-059
Solar/Wind Harmer
10.554
972159AH1-661 GEN
Adder
1.111
241960AC2-195 GEN
Solar/Wind Harmer
3.053
971073AG2-665 GEN
Solar/Wind Harmer
8.757
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.713
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.41
944541AF1-119 GEN
Solar/Wind Harmer
4.431
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.405
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.551
270383AD1-128 GEN
Solar/Wind Harmer
6.401
247620Y3-023
Adder
0.482
24728805RICHG1
Adder
3.949
274695ROCKY RD ;2P
Adder
11.232
235054AD2-180 GEN
Solar/Wind Helper
2.044
235531U2-073 GEN
Solar/Wind Helper
3.333
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
274674JOLIET 9 ;6U
Adder
15.65
274693ROCKY RD ;1P
Adder
11.121
274683WAUKEGAN ;8U
Adder
21.239
274683WAUKEGAN ;8U
Adder
9.65
23585401KL_K28_T16
Solar/Wind Helper
1.493
238117U2-030
Solar/Wind Helper
0.344
238148AE2-230_GEN2
Solar/Wind Helper
0.5
235062AE1-101 C1
Solar/Wind Helper
1.674
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.603
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.62
965051AG1-369 GEN
Solar/Wind Harmer
5.342
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.781
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.807
970031AG2-029 GEN
Solar/Wind Harmer
26.342
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.646
274777LINCOLN ;8U
Adder
8.646
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.777
274675JOLIET 29;7U
Adder
31.195
274675JOLIET 29;7U
Adder
30.081
23750701CROSSCHOOL
Solar/Wind Helper
1.512
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.507
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
203955AF1-039 C O1
Solar/Wind Helper
0.331
972239AH1-704 GEN
Adder
2.673
961821AG1-024 GEN
Solar/Wind Harmer
10.359
945631AF1-228 GEN
Solar/Wind Harmer
5.44
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.013
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.168
241972AD1-140 GEN
Solar/Wind Harmer
4.999
270340AC2-060 GEN
Solar/Wind Harmer
3.323
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.696
965041AG1-368 GEN
Solar/Wind Harmer
10.674
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.955
964611AG1-324 GEN
Solar/Wind Harmer
4.099
274776LINCOLN ;7U
Adder
8.646
274687WILL CNTY;4U
Adder
28.425
274687WILL CNTY;4U
Adder
28.425
274731ELWOOD EC;2P
Adder
16.71
274733ELWOOD EC;3P
Adder
16.71
274746AC1-111 G10
Adder
5.66
238118U2-030_1
Solar/Wind Helper
0.344
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.644
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.784
252516AE2-318_GEN
Solar/Wind Harmer
10.575
270024AE2-089 GEN
Solar/Wind Harmer
4.947
25194608D.CRK4
Adder
1.734
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.122
24728605AND G2
Adder
3.913
274676JOLIET 29;8U
Adder
31.195
972203AH1-686 GEN
Adder
2.333
274745AC1-111 GEN9
Adder
5.66
274682WAUKEGAN ;7U
Adder
18.122
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.674
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.532
23751101LEADS_P59
Solar/Wind Helper
2.129
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
241955AC1-078 GEN
Solar/Wind Harmer
8.768
241973AD2-163_GEN1
Solar/Wind Harmer
2.315
241974AD2-163_GEN2
Solar/Wind Harmer
2.315
943861AF1-054 GEN
Solar/Wind Harmer
4.468
943851AF1-053 GEN
Solar/Wind Harmer
2.159
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.8
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.877
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.332
274827FISK ;RP
Adder
7.914
274800UNIV PARK;3U
Adder
5.946
274801UNIV PARK;4U
Adder
5.946
972227AH1-698 GEN1
Adder
2.66
274735ELWOOD EC;4P
Adder
16.71
274744AC1-111 GEN8
Adder
5.66
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
970065AG2-057 GEN
Solar/Wind Harmer
0.921
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.279
971191AH1-055 GEN
Solar/Wind Harmer
20.022
965021AG1-366 GEN
Solar/Wind Harmer
2.488
270043AE2-236 GEN
Solar/Wind Harmer
5.848
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
962031AG1-047 GEN
Solar/Wind Harmer
3.18
957741AF2-068 GEN
Solar/Wind Harmer
15.775
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.479
970825AG2-519 GEN
Solar/Wind Harmer
5.897
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.646
274724RIVER EC ;11
Adder
18.141
972259AH1-714 GEN
Adder
19.441
274729ELWOOD EC;1P
Adder
16.71
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.185
316415AF1-147_GEN2
Solar/Wind Helper
0.896
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
270119AB2-067 GEN1
50/50
7.082
253378AE2-206_GEN
Solar/Wind Harmer
3.988
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.273
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.646
274771LINCOLN ;2U
Adder
8.646
274805UNIV PK N;1U
Adder
5.133
274696ROCKY RD ;4P
Adder
11.497
274697ROCKY RD ;3P
Adder
3.051
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.83
237061AD1-155 GEN
Solar/Wind Helper
1.768
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233930AB2-032 GEN
Solar/Wind Helper
0.384
233982AB2-133 GEN
Solar/Wind Helper
0.362
233946AB2-136 GEN
Solar/Wind Helper
0.574
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.235
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.331
270032AE2-172
Solar/Wind Harmer
4.566
24318805MLG1
50/50
10.084
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.795
253325AC1-069 GEN
Solar/Wind Harmer
1.189
971199AH1-059 GEN
Solar/Wind Harmer
2.315
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270004AE1-209 GEN
Solar/Wind Harmer
5.726
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
24379505HDWTR1G C
Solar/Wind Harmer
8.281
274753CRETE EC ;3U
Adder
8.448
274814UNIV PK N;0U
Adder
5.166
274807UNIV PK N;3U
Adder
5.155
274803UNIV PARK;6U
Adder
5.949
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.015
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.507
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.448
274802UNIV PARK;5U
Adder
5.949
274732ELWOOD EC;7P
Adder
16.71
274674JOLIET 9 ;6U
Adder
15.65
235067AD1-061 GEN
Solar/Wind Helper
0.45
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.441
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.441
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
971073AG2-665 GEN
Solar/Wind Harmer
1.273
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
960001AF2-291 GEN
Solar/Wind Harmer
3.242
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.376
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.363
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.966
WECLTFEXP_WEC->PJM
CLTF
3.811
LAGNLTFEXP_LAGN->PJM
CLTF
14.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.682
CPLELTFEXP_CPLE->PJM
CLTF
0.578
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.545
NYPJM->LTFIMP_NY
CLTF
4.834
TVALTFEXP_TVA->PJM
CLTF
7.257
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.337
LGEELTFEXP_LGEE->PJM
CLTF
6.725
MECLTFEXP_MEC->PJM
CLTF
15.842
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.01 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4959.97
MW Contribution:
2.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
7.043
270349AD2-093_GEN
Solar/Wind Harmer
4.444
23559001PLEAS1
50/50
6.109
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.967
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.723
957541AF2-048 GEN
Solar/Wind Harmer
1.714
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.241
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.445
24728705AND G3
Adder
8.182
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.852
276820AF1-078_GEN
Solar/Wind Harmer
1.772
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.698
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.12
24728505AND G1
Adder
3.912
274676JOLIET 29;8U
Adder
30.072
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
946101AF1-275 GEN
Solar/Wind Harmer
1.809
942861AE2-305 GEN
Solar/Wind Harmer
9.054
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
247620Y3-023
Adder
0.482
24728805RICHG1
Adder
3.948
274695ROCKY RD ;2P
Adder
11.229
235054AD2-180 GEN
Solar/Wind Helper
2.035
235531U2-073 GEN
Solar/Wind Helper
3.323
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
270120AB2-067 GEN2
50/50
7.073
270054AF2-122 C O1
Solar/Wind Harmer
3.974
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
960971AF2-388 GEN
Solar/Wind Harmer
11.565
25194408D.CRK1
Adder
7.977
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270599AE1-208 GEN
Solar/Wind Harmer
8.55
926881AC1-175 GEN
Solar/Wind Harmer
5.844
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728905RICHG2
Adder
3.948
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274693ROCKY RD ;1P
Adder
11.118
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
23585401KL_K28_T16
Solar/Wind Helper
1.485
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.673
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.607
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.625
965051AG1-369 GEN
Solar/Wind Harmer
5.341
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
247536S-71 GEN
Solar/Wind Harmer
4.259
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
972239AH1-704 GEN
Adder
2.68
961821AG1-024 GEN
Solar/Wind Harmer
10.365
945631AF1-228 GEN
Solar/Wind Harmer
5.442
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270340AC2-060 GEN
Solar/Wind Harmer
3.324
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.694
965041AG1-368 GEN
Solar/Wind Harmer
10.672
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.954
964611AG1-324 GEN
Solar/Wind Harmer
4.098
274776LINCOLN ;7U
Adder
8.644
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274746AC1-111 G10
Adder
5.658
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
970155AG2-107 GEN
Solar/Wind Harmer
17.802
971995AH1-542 GEN
Solar/Wind Harmer
12.457
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.239
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
24639705ELKHART HY
Adder
0.16
274812UNIV PK N;8U
Adder
5.12
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.805
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.876
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.329
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972227AH1-698 GEN1
Adder
2.659
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.673
205932AD2-116_GEN
Solar/Wind Helper
0.513
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.518
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
270051AF1-062 GEN
50/50
11.788
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
970065AG2-057 GEN
Solar/Wind Harmer
0.922
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
971191AH1-055 GEN
Solar/Wind Harmer
20.024
965021AG1-366 GEN
Solar/Wind Harmer
2.487
270043AE2-236 GEN
Solar/Wind Harmer
5.847
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
270119AB2-067 GEN1
50/50
7.073
23684101S70BUS1
50/50
0.165
253378AE2-206_GEN
Solar/Wind Harmer
3.989
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.274
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274696ROCKY RD ;4P
Adder
11.494
274697ROCKY RD ;3P
Adder
3.05
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
270459AD2-067 GEN
Solar/Wind Harmer
10.209
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.325
24729505KEY G4
Adder
6.892
270071AF1-092 GEN
Solar/Wind Harmer
15.92
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.53
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274728ELWOOD EC;5P
Adder
16.705
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
972259AH1-714 GEN
Adder
19.435
274729ELWOOD EC;1P
Adder
16.705
238175AF1-290_GEN
Solar/Wind Helper
0.158
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
270166AC1-044 GEN3
50/50
7.073
23684201S70BUS2
50/50
0.168
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.576
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.694
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
23583801GRNGAP
Solar/Wind Helper
5.632
238126S14_GEN_1
Solar/Wind Helper
0.83
237085AD2-009_GEN
Solar/Wind Helper
1.662
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.776
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
23750701CROSSCHOOL
Solar/Wind Helper
1.507
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
274826FISK ;BP
Adder
11.164
274730ELWOOD EC;6P
Adder
16.705
238127S14_GEN_2
Solar/Wind Helper
0.83
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
270471AD2-092_GEN
Solar/Wind Harmer
4.444
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.581
962761AG1-125 GEN
Solar/Wind Harmer
40.825
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.01
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.844
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.445
274802UNIV PARK;5U
Adder
5.948
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
24318805MLG1
50/50
10.069
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
274753CRETE EC ;3U
Adder
8.445
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274803UNIV PARK;6U
Adder
5.948
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.006
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
23559101PLEAS2
50/50
6.109
970149AG2-104 GEN
Solar/Wind Harmer
25.209
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
960001AF2-291 GEN
Solar/Wind Harmer
3.243
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.346
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
NYPJM->LTFIMP_NY
CLTF
4.833
TVALTFEXP_TVA->PJM
CLTF
7.253
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
LGEELTFEXP_LGEE->PJM
CLTF
6.723
MECLTFEXP_MEC->PJM
CLTF
15.837
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
WECLTFEXP_WEC->PJM
CLTF
3.81
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
CPLELTFEXP_CPLE->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.503

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.01 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4959.97
MW Contribution:
2.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270120AB2-067 GEN2
50/50
7.073
946101AF1-275 GEN
Solar/Wind Harmer
1.809
942861AE2-305 GEN
Solar/Wind Harmer
9.054
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
972239AH1-704 GEN
Adder
2.68
961821AG1-024 GEN
Solar/Wind Harmer
10.365
945631AF1-228 GEN
Solar/Wind Harmer
5.442
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270340AC2-060 GEN
Solar/Wind Harmer
3.324
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.694
965041AG1-368 GEN
Solar/Wind Harmer
10.672
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.954
964611AG1-324 GEN
Solar/Wind Harmer
4.098
274776LINCOLN ;7U
Adder
8.644
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274746AC1-111 G10
Adder
5.658
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.805
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.876
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.329
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972227AH1-698 GEN1
Adder
2.659
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.852
276820AF1-078_GEN
Solar/Wind Harmer
1.772
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.698
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.12
24728505AND G1
Adder
3.912
274676JOLIET 29;8U
Adder
30.072
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.673
205932AD2-116_GEN
Solar/Wind Helper
0.513
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.518
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
970155AG2-107 GEN
Solar/Wind Harmer
17.802
971995AH1-542 GEN
Solar/Wind Harmer
12.457
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.239
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
270119AB2-067 GEN1
50/50
7.073
23684101S70BUS1
50/50
0.165
253378AE2-206_GEN
Solar/Wind Harmer
3.989
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.274
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
270459AD2-067 GEN
Solar/Wind Harmer
10.209
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.325
24729505KEY G4
Adder
6.892
270071AF1-092 GEN
Solar/Wind Harmer
15.92
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.53
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274728ELWOOD EC;5P
Adder
16.705
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
270051AF1-062 GEN
50/50
11.788
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
970065AG2-057 GEN
Solar/Wind Harmer
0.922
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
971191AH1-055 GEN
Solar/Wind Harmer
20.024
965021AG1-366 GEN
Solar/Wind Harmer
2.487
270043AE2-236 GEN
Solar/Wind Harmer
5.847
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
972259AH1-714 GEN
Adder
19.435
274729ELWOOD EC;1P
Adder
16.705
238175AF1-290_GEN
Solar/Wind Helper
0.158
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
270166AC1-044 GEN3
50/50
7.073
23684201S70BUS2
50/50
0.168
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.576
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.694
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
23583801GRNGAP
Solar/Wind Helper
5.632
238126S14_GEN_1
Solar/Wind Helper
0.83
237085AD2-009_GEN
Solar/Wind Helper
1.662
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.607
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.625
965051AG1-369 GEN
Solar/Wind Harmer
5.341
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.776
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
23750701CROSSCHOOL
Solar/Wind Helper
1.507
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
24639705ELKHART HY
Adder
0.16
274812UNIV PK N;8U
Adder
5.12
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
274696ROCKY RD ;4P
Adder
11.494
274697ROCKY RD ;3P
Adder
3.05
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
24318905MLG2
50/50
7.043
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
23559001PLEAS1
50/50
6.109
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.967
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.723
957541AF2-048 GEN
Solar/Wind Harmer
1.714
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.241
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.445
24728705AND G3
Adder
8.182
274826FISK ;BP
Adder
11.164
274730ELWOOD EC;6P
Adder
16.705
238127S14_GEN_2
Solar/Wind Helper
0.83
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.581
962761AG1-125 GEN
Solar/Wind Harmer
40.825
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.01
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.844
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.445
274802UNIV PARK;5U
Adder
5.948
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270054AF2-122 C O1
Solar/Wind Harmer
3.974
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
960971AF2-388 GEN
Solar/Wind Harmer
11.565
25194408D.CRK1
Adder
7.977
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270599AE1-208 GEN
Solar/Wind Harmer
8.55
926881AC1-175 GEN
Solar/Wind Harmer
5.844
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728905RICHG2
Adder
3.948
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274693ROCKY RD ;1P
Adder
11.118
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
23585401KL_K28_T16
Solar/Wind Helper
1.485
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.673
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
24318805MLG1
50/50
10.069
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
274753CRETE EC ;3U
Adder
8.445
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274803UNIV PARK;6U
Adder
5.948
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.006
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
23559101PLEAS2
50/50
6.109
970149AG2-104 GEN
Solar/Wind Harmer
25.209
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
960001AF2-291 GEN
Solar/Wind Harmer
3.243
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.346
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
247620Y3-023
Adder
0.482
24728805RICHG1
Adder
3.948
274695ROCKY RD ;2P
Adder
11.229
235054AD2-180 GEN
Solar/Wind Helper
2.035
235531U2-073 GEN
Solar/Wind Helper
3.323
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
WECLTFEXP_WEC->PJM
CLTF
3.81
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
CPLELTFEXP_CPLE->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
NYPJM->LTFIMP_NY
CLTF
4.833
TVALTFEXP_TVA->PJM
CLTF
7.253
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
LGEELTFEXP_LGEE->PJM
CLTF
6.723
MECLTFEXP_MEC->PJM
CLTF
15.837
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.87 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4917.49
MW Contribution:
2.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.069
972269AH1-719 GEN
Adder
2.573
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965011AG1-365 GEN
Solar/Wind Harmer
7.453
958861AF2-177 GEN
Solar/Wind Harmer
3.191
252510AF1-249 C
Solar/Wind Harmer
0.056
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.589
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
25196008MFTGT1
Adder
1.443
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.68
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
23583801GRNGAP
Solar/Wind Helper
5.626
238126S14_GEN_1
Solar/Wind Helper
0.831
237085AD2-009_GEN
Solar/Wind Helper
1.661
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.792
942861AE2-305 GEN
Solar/Wind Harmer
6.31
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
971073AG2-665 GEN
Solar/Wind Harmer
5.597
25326109MON D
Adder
1.437
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.492
25194508D.CRK3
Adder
1.49
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970885AG2-551 GEN
Solar/Wind Harmer
2.446
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270031AE2-169
Solar/Wind Harmer
4.021
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
24728805RICHG1
Adder
3.944
24699105WLD G1 C
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.638
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
10.234
274695ROCKY RD ;2P
Adder
11.216
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
2.04
235531U2-073 GEN
Solar/Wind Helper
3.327
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.118
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
316045AC1-158 PL2
Solar/Wind Helper
4.17
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
270119AB2-067 GEN1
50/50
7.069
25326509SID D
Adder
1.446
970879AG2-548 GEN
Solar/Wind Harmer
1.272
246937BC-WTG2
Solar/Wind Harmer
0.302
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970623AG2-406 GEN
Solar/Wind Harmer
1.351
942221AE2-234 GEN
Solar/Wind Harmer
2.958
970621AG2-405 GEN
Solar/Wind Harmer
1.345
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.126
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
274696ROCKY RD ;4P
Adder
11.481
274697ROCKY RD ;3P
Adder
3.047
962691AG1-118 GEN
Solar/Wind Harmer
21.036
942111AE2-223 GEN
Solar/Wind Harmer
2.266
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.895
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
270120AB2-067 GEN2
50/50
7.069
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.867
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.048
960971AF2-388 GEN
Solar/Wind Harmer
4.326
25194408D.CRK1
Adder
7.968
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270599AE1-208 GEN
Solar/Wind Harmer
6.701
926881AC1-175 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728905RICHG2
Adder
3.944
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274808UNIV PK N;4U
Adder
5.092
274674JOLIET 9 ;6U
Adder
15.628
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274693ROCKY RD ;1P
Adder
11.106
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
23585401KL_K28_T16
Solar/Wind Helper
1.489
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.672
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.559
270377AD1-106 GEN
Solar/Wind Harmer
2.842
965051AG1-369 GEN
Solar/Wind Harmer
3.723
971985AH1-537 GEN
Solar/Wind Harmer
2.196
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
247536S-71 GEN
Solar/Wind Harmer
0.293
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
274775LINCOLN ;6U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
972228AH1-698 GEN2
Adder
3.772
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
971411AH1-196 GEN
Solar/Wind Harmer
10.47
23750701CROSSCHOOL
Solar/Wind Helper
1.509
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
970155AG2-107 GEN
Solar/Wind Harmer
21.963
971995AH1-542 GEN
Solar/Wind Harmer
2.894
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
965421AG1-410 GEN
Solar/Wind Harmer
22.47
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.732
970613AG2-401 GEN
Solar/Wind Harmer
5.351
24639705ELKHART HY
Adder
0.16
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
274676JOLIET 29;8U
Adder
31.151
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
18.096
316095T157 G97
Solar/Wind Helper
1.51
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
957471AF2-041 GEN
Solar/Wind Harmer
13.586
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
252519AF1-045_GEN
Solar/Wind Harmer
3.844
25194608D.CRK4
Adder
1.732
946031AF1-268 GEN
Solar/Wind Harmer
6.95
970289AG2-191 GEN
Solar/Wind Harmer
0.8
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
5.114
24728505AND G1
Adder
3.908
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274676JOLIET 29;8U
Adder
30.039
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
274682WAUKEGAN ;7U
Adder
18.096
964991AG1-363 GEN
Solar/Wind Helper
5.155
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.672
205932AD2-116_GEN
Solar/Wind Helper
0.512
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.868
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.516
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
959091AF2-200 GEN
Solar/Wind Harmer
9.057
972239AH1-704 GEN
Adder
2.678
961821AG1-024 GEN
Solar/Wind Harmer
5.057
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.217
965041AG1-368 GEN
Solar/Wind Harmer
7.438
25196508WSDLE4
Adder
8.944
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.634
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274746AC1-111 G10
Adder
5.652
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.512
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
270051AF1-062 GEN
50/50
11.777
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
971191AH1-055 GEN
Solar/Wind Harmer
19.175
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270043AE2-236 GEN
Solar/Wind Harmer
4.754
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
270186AC1-089 GEN
Solar/Wind Harmer
0
23559001PLEAS1
50/50
6.097
961921AG1-034 GEN
Solar/Wind Harmer
7.586
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
944531AF1-118 GEN
Solar/Wind Harmer
33.233
25196608WSDLE5
Adder
9.036
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
3.658
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
945111AF1-176 GEN
Solar/Wind Harmer
5.891
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
972167AH1-666 GEN
Solar/Wind Harmer
5.69
972259AH1-714 GEN
Adder
19.413
274729ELWOOD EC;1P
Adder
16.687
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970571AG2-364 GEN
Solar/Wind Harmer
13.944
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
233944AB2-135 GEN
Solar/Wind Helper
0.594
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
23559101PLEAS2
50/50
6.097
970149AG2-104 GEN
Solar/Wind Harmer
18.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
971917AH1-482 GEN
Solar/Wind Harmer
9.365
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
276882AE2-255 GEN
Solar/Wind Harmer
0.818
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.274
274752CRETE EC ;2U
Adder
8.436
24728705AND G3
Adder
8.173
274887GEN-1.85
Solar/Wind Harmer
0.185
274826FISK ;BP
Adder
11.151
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
274730ELWOOD EC;6P
Adder
16.687
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
970193AG2-126 GEN
Solar/Wind Harmer
10.468
238127S14_GEN_2
Solar/Wind Helper
0.831
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.303
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.58
202652Y1-033 WT C
Solar/Wind Helper
0.5
962761AG1-125 GEN
Solar/Wind Harmer
34.394
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.807
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.095
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.436
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.941
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
939401AE1-172 GEN
Solar/Wind Harmer
5.275
962781AG1-127 GEN
Solar/Wind Harmer
6.668
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.441
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.843
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
270246TR4_N_V150
Solar/Wind Harmer
0.048
247621Y3-024
Adder
0.253
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
965681AG1-436 GEN
Solar/Wind Harmer
9.052
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.758
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.51
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.344
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
970179AG2-119 GEN
Solar/Wind Harmer
6.854
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.27
963791AG1-232 GEN
Solar/Wind Harmer
9.987
970289AG2-191 GEN
Solar/Wind Harmer
1.382
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972227AH1-698 GEN1
Adder
2.656
274735ELWOOD EC;4P
Adder
16.687
274744AC1-111 GEN8
Adder
5.652
970169AG2-114 GEN
Solar/Wind Harmer
7.011
959341AF2-225 GEN
Solar/Wind Harmer
7.32
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.057
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270007AE1-245 C
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
270071AF1-092 GEN
Solar/Wind Harmer
14.177
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
270543AE2-219 C
Solar/Wind Harmer
5.137
971771AH1-392 GEN
Solar/Wind Harmer
7.271
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
971549AH1-272 GEN
Solar/Wind Harmer
14.794
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.687
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.062
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
209027LOR2_Q27
Solar/Wind Helper
1.031
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
24318805MLG1
50/50
10.065
270475AD2-096_GEN
50/50
7.114
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
970191AG2-125 GEN
Solar/Wind Harmer
1.937
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.436
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274803UNIV PARK;6U
Adder
5.941
276843GEN-1.7
Solar/Wind Harmer
0.23
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.012
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
WECLTFEXP_WEC->PJM
CLTF
3.806
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
CPLELTFEXP_CPLE->PJM
CLTF
0.571
SIGELTFEXP_SIGE->PJM
CLTF
0.502
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
NYPJM->LTFIMP_NY
CLTF
4.827
TVALTFEXP_TVA->PJM
CLTF
7.243
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
LGEELTFEXP_LGEE->PJM
CLTF
6.715
MECLTFEXP_MEC->PJM
CLTF
15.818
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.69 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4873.53
MW Contribution:
3.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
270302AB2-170 GEN
Solar/Wind Harmer
9.776
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253343AC1-166 GEN
Solar/Wind Harmer
1.249
957201AF2-014 GEN
Solar/Wind Harmer
5.019
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
25306009OHH W.
Adder
3.158
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
944161AF1-084 GEN
Solar/Wind Harmer
2.352
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972227AH1-698 GEN1
Adder
2.695
274735ELWOOD EC;4P
Adder
16.929
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
315651AD1-115 GEN
Solar/Wind Helper
0.883
959381AF2-229 GEN
Solar/Wind Helper
0.368
232432Z2-076 GEN
Solar/Wind Helper
0.068
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
24721905FLATG4
Adder
23.444
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
24695305TIMB G C
Solar/Wind Harmer
3.661
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
247643Z2-116 C
Solar/Wind Harmer
0.074
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25194608D.CRK4
Adder
1.747
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
274811UNIV PK N;7U
Adder
5.194
274676JOLIET 29;8U
Adder
30.477
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238110AE1-109 GEN3
Solar/Wind Helper
0.122
235063AE1-101 C2
Solar/Wind Helper
1.786
316447AC1-158 HLD
Solar/Wind Helper
3.193
205932AD2-116_GEN
Solar/Wind Helper
0.521
232426Y1-080 FULL
Solar/Wind Helper
0.04
233996TM1833_GEN
Solar/Wind Helper
0.21
316192AB2-158 GEN
Solar/Wind Helper
1.618
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
270459AD2-067 GEN
Solar/Wind Harmer
10.428
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
971567AH1-282 GEN
Solar/Wind Harmer
5.635
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
958711AF2-162 GEN
Solar/Wind Harmer
1.086
270543AE2-219 C
Solar/Wind Harmer
10.668
971771AH1-392 GEN
Solar/Wind Harmer
9.58
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274728ELWOOD EC;5P
Adder
16.929
3141426STAFORD
Solar/Wind Helper
0.058
20390526W1-045 C
Solar/Wind Helper
0.361
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.234
219258KINSLEYDEP C
Solar/Wind Helper
0.078
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
270051AF1-062 GEN
50/50
11.971
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
970065AG2-057 GEN
Solar/Wind Harmer
0.972
246938BC-WTG3
Solar/Wind Harmer
4.404
970879AG2-548 GEN
Solar/Wind Harmer
8.835
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
270043AE2-236 GEN
Solar/Wind Harmer
5.961
971191AH1-055 GEN
Solar/Wind Harmer
20.005
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
270367AC2-061_GEN
Solar/Wind Harmer
3.375
25196008MFTGT1
Adder
1.409
274724RIVER EC ;11
Adder
18.401
274772LINCOLN ;3U
Adder
8.764
972259AH1-714 GEN
Adder
19.698
274729ELWOOD EC;1P
Adder
16.929
238175AF1-290_GEN
Solar/Wind Helper
0.173
316415AF1-147_GEN2
Solar/Wind Helper
0.984
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
233944AB2-135 GEN
Solar/Wind Helper
0.603
232408W1-005 C
Solar/Wind Helper
0.518
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.084
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270377AD1-106 GEN
Solar/Wind Harmer
5.917
270291AC1-194 GEN
Solar/Wind Harmer
5.669
965051AG1-369 GEN
Solar/Wind Harmer
5.479
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
274775LINCOLN ;6U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
972228AH1-698 GEN2
Adder
3.828
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
23750701CROSSCHOOL
Solar/Wind Helper
1.591
205943AE1-185 GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
228728W1-130C
Solar/Wind Helper
0.055
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
972239AH1-704 GEN
50/50
3.095
961821AG1-024 GEN
Solar/Wind Harmer
10.588
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270432AC2-029 GEN
Solar/Wind Harmer
8.117
253338AC1-165 GEN
Solar/Wind Harmer
1.249
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270340AC2-060 GEN
Solar/Wind Harmer
3.354
270191TR4_S_V150
Solar/Wind Harmer
3.29
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
270499AE1-146 GEN
Solar/Wind Harmer
2.679
964611AG1-324 GEN
Solar/Wind Harmer
4.154
25196508WSDLE4
Adder
9.023
274776LINCOLN ;7U
Adder
8.764
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
23779801AA1-109
Solar/Wind Helper
0.208
226929AD2-058 GEN
Solar/Wind Helper
0.108
316164AC1-076 GEN
Solar/Wind Helper
1.232
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
205956AE1-196_GEN
Solar/Wind Helper
0.521
233901CHERRYDALE C
Solar/Wind Helper
0.238
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
970155AG2-107 GEN
Solar/Wind Harmer
17.82
971995AH1-542 GEN
Solar/Wind Harmer
12.942
965421AG1-410 GEN
Solar/Wind Harmer
33.164
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
24639705ELKHART HY
Adder
0.164
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
25194608D.CRK4
Adder
1.747
23906502RICHG2&3
Adder
1.268
274812UNIV PK N;8U
Adder
5.194
274676JOLIET 29;8U
Adder
31.606
316095T157 G97
Solar/Wind Helper
1.71
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
238120AE2-309 GEN
Solar/Wind Helper
0.557
23777801MSM_W1-116
Solar/Wind Helper
0.123
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
232422X3-066 FULL
Solar/Wind Helper
0.117
233964AF2-378 GEN
Solar/Wind Helper
0.043
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
966881AG1-559 GEN
Solar/Wind Helper
0.313
205941AD2-115 GEN
Solar/Wind Helper
0.499
270166AC1-044 GEN3
50/50
7.05
972269AH1-719 GEN
Adder
2.693
270485AE1-090_GEN
Solar/Wind Harmer
0.706
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965011AG1-365 GEN
Solar/Wind Harmer
10.939
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
958861AF2-177 GEN
Solar/Wind Harmer
11.712
945371AF1-202 GEN
Solar/Wind Harmer
7.453
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25196808ZIMRHP
Adder
79.955
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
23583801GRNGAP
Solar/Wind Helper
6.383
238126S14_GEN_1
Solar/Wind Helper
0.87
237085AD2-009_GEN
Solar/Wind Helper
1.776
3141196NOKESVL
Solar/Wind Helper
1.144
226910AB2-157 C
Solar/Wind Helper
0.016
233933AB2-153 GEN
Solar/Wind Helper
0.238
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.777
960841AF2-375 GEN
Solar/Wind Harmer
0.624
270119AB2-067 GEN1
50/50
7.05
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
246937BC-WTG2
Solar/Wind Harmer
4.329
970879AG2-548 GEN
Solar/Wind Harmer
1.284
247607V1-011 GEN
Solar/Wind Harmer
4.348
247522W1-056 GEN
Solar/Wind Harmer
2.469
942221AE2-234 GEN
Solar/Wind Harmer
3.759
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
237061AD1-155 GEN
Solar/Wind Helper
1.974
235020AA1-095 C
Solar/Wind Helper
0.058
238221AF1-254 C O1
Solar/Wind Helper
0.297
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
223402AF1-300 C
Solar/Wind Helper
0.389
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
233946AB2-136 GEN
Solar/Wind Helper
0.581
232410W1-006 C
Solar/Wind Helper
0.518
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
24318905MLG2
50/50
7.451
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
253383AE2-342_GEN
Solar/Wind Harmer
1.057
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
247621Y3-024
Adder
0.257
970935AG2-582 GEN
Adder
238.716
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
237080AD1-060 GEN
Solar/Wind Helper
0.369
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
23559001PLEAS1
50/50
5.445
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
958581AF2-149 GEN
Solar/Wind Harmer
4.955
958091AF2-103 GEN
Solar/Wind Harmer
0.178
957541AF2-048 GEN
Solar/Wind Harmer
1.72
944531AF1-118 GEN
Solar/Wind Harmer
37.819
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971347AH1-153 GEN
Solar/Wind Harmer
5.342
25196608WSDLE5
Adder
9.116
274752CRETE EC ;2U
Adder
8.571
274826FISK ;BP
Adder
11.319
274730ELWOOD EC;6P
Adder
16.929
238152AF2-075_GEN
Solar/Wind Helper
0.794
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
316044AC1-158 PL1
Solar/Wind Helper
1.451
208835TUHI V3-051
Solar/Wind Helper
0.022
3147666LOUISA
Solar/Wind Helper
0.962
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.573
962761AG1-125 GEN
Solar/Wind Harmer
40.867
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270317AD1-130_GEN
Solar/Wind Harmer
3.738
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
25326309TAIT D
Adder
1.207
270216AD2-079_GEN
Solar/Wind Harmer
0.645
944031AF1-071 GEN
Solar/Wind Harmer
1.069
274754CRETE EC ;4U
Adder
8.571
274802UNIV PARK;5U
Adder
6.031
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
235067AD1-061 GEN
Solar/Wind Helper
0.481
237002AB1-128_GEN
Solar/Wind Helper
0.477
208835TUHI V3-051
Solar/Wind Helper
0.022
3147666LOUISA
Solar/Wind Helper
0.553
233950AC2-186 GEN
Solar/Wind Helper
0.119
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.313
217169METRODIV C
Solar/Wind Helper
0.004
270120AB2-067 GEN2
50/50
7.05
270054AF2-122 C O1
Solar/Wind Harmer
4.054
938701AE1-092 GEN
Solar/Wind Harmer
24.428
270462AD2-086
Solar/Wind Harmer
8.12
253415AE1-040 GEN
Solar/Wind Harmer
1.252
942801AE2-298 GEN
Solar/Wind Harmer
1.666
270247TR4_N_V136
Solar/Wind Harmer
0.933
253349AC2-067 GEN
Solar/Wind Harmer
2.225
944231AF1-091 GEN
Solar/Wind Harmer
19.433
960971AF2-388 GEN
Solar/Wind Harmer
11.731
970349AG2-230 GEN
Solar/Wind Harmer
16.027
970883AG2-550 GEN
Solar/Wind Harmer
10.668
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
24728905RICHG2
Adder
3.989
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
238148AE2-230_GEN2
Solar/Wind Helper
0.556
23585401KL_K28_T16
Solar/Wind Helper
1.534
238117U2-030
Solar/Wind Helper
0.357
235062AE1-101 C1
Solar/Wind Helper
1.786
237006AB1-125 GEN
Solar/Wind Helper
0.132
223401AF1-299 GEN
Solar/Wind Helper
0.389
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
232424Y1-079 C
Solar/Wind Helper
0.119
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
966001AG1-469 GEN
Solar/Wind Helper
0.256
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.293
20675428EAM_W2-061
Solar/Wind Helper
0.016
24318805MLG1
50/50
10
270518AE2-148 GEN
Solar/Wind Harmer
13.997
971199AH1-059 GEN
Solar/Wind Harmer
2.432
253325AC1-069 GEN
Solar/Wind Harmer
1.205
961961AG1-039 GEN
Solar/Wind Harmer
3.18
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
274753CRETE EC ;3U
Adder
8.571
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274803UNIV PARK;6U
Adder
6.031
972038AH1-567 GEN2
Adder
0.377
238108AE1-109 GEN1
Solar/Wind Helper
0.122
237001AB1-127_GEN
Solar/Wind Helper
0.476
23562501BACKB
Solar/Wind Helper
1
233918AB1-142 GEN
Solar/Wind Helper
0.514
228729W2-030 C
Solar/Wind Helper
0.112
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.151
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
970149AG2-104 GEN
Solar/Wind Harmer
25.235
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
971073AG2-665 GEN
Solar/Wind Harmer
1.284
270297AD1-101 GEN
Solar/Wind Harmer
2.226
270258AD1-119 GEN
Solar/Wind Harmer
2.219
960001AF2-291 GEN
Solar/Wind Harmer
3.236
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
23920202STRYCT
Adder
1.44
23546401DTGZ2-030
Solar/Wind Helper
0.1
237038AE2-054 C
Solar/Wind Helper
0.294
3132273ORANGE
Solar/Wind Helper
0.049
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
232417X3-008 C
Solar/Wind Helper
0.238
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.151
946101AF1-275 GEN
Solar/Wind Harmer
1.838
942861AE2-305 GEN
Solar/Wind Harmer
9.201
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
25326109MON D
Adder
1.457
971073AG2-665 GEN
Solar/Wind Harmer
8.835
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944541AF1-119 GEN
Solar/Wind Harmer
4.494
247620Y3-023
Adder
0.492
25183208HLCRTG
Solar/Wind Harmer
6.454
970885AG2-551 GEN
Solar/Wind Harmer
2.481
270201AC2-176 GEN
Solar/Wind Harmer
5.48
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
238149AF1-291A_GEN
Solar/Wind Helper
0.159
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
316006AB2-029 C
Solar/Wind Helper
0.131
316045AC1-158 PL2
Solar/Wind Helper
4.643
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
219912AD2-042 GEN
Solar/Wind Helper
0.152
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
20674328GAR_V4-001
Solar/Wind Helper
0.023
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
NYPJM->LTFIMP_NY
CLTF
4.574
MECLTFEXP_MEC->PJM
CLTF
15.924
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
LGEELTFEXP_LGEE->PJM
CLTF
6.731
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
WECLTFEXP_WEC->PJM
CLTF
3.853
SIGELTFEXP_SIGE->PJM
CLTF
0.504

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4632.89
MW Contribution:
2.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270120AB2-067 GEN2
50/50
6.887
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.459
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.046
960971AF2-388 GEN
Solar/Wind Harmer
4.179
25194408D.CRK1
Adder
7.692
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270599AE1-208 GEN
Solar/Wind Harmer
6.473
944231AF1-091 GEN
Solar/Wind Harmer
16.273
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.809
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
24725505WLD G2 C
Solar/Wind Harmer
0
970155AG2-107 GEN
Solar/Wind Harmer
21.201
971995AH1-542 GEN
Solar/Wind Harmer
2.804
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
942861AE2-305 GEN
Solar/Wind Harmer
6.105
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
25194508D.CRK3
Adder
1.438
970885AG2-551 GEN
Solar/Wind Harmer
2.363
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
270031AE2-169
Solar/Wind Harmer
3.884
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.465
24728805RICHG1
Adder
3.809
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
9.886
270119AB2-067 GEN1
50/50
6.887
25326509SID D
Adder
1.398
970879AG2-548 GEN
Solar/Wind Harmer
1.228
246937BC-WTG2
Solar/Wind Harmer
0.292
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971985AH1-537 GEN
Solar/Wind Harmer
2.117
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
10.639
247536S-71 GEN
Solar/Wind Harmer
0.283
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
274775LINCOLN ;6U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
972228AH1-698 GEN2
Adder
3.644
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.63
971411AH1-196 GEN
Solar/Wind Harmer
10.113
23750701CROSSCHOOL
Solar/Wind Helper
1.401
270051AF1-062 GEN
50/50
11.411
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
270043AE2-236 GEN
Solar/Wind Harmer
4.595
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
270166AC1-044 GEN3
50/50
6.887
972269AH1-719 GEN
Adder
2.495
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965011AG1-365 GEN
Solar/Wind Harmer
7.206
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252510AF1-249 C
Solar/Wind Harmer
0.054
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
76.605
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
25196008MFTGT1
Adder
1.393
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
24386605FR-22G C
Solar/Wind Harmer
0
972239AH1-704 GEN
50/50
2.774
961821AG1-024 GEN
Solar/Wind Harmer
4.899
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.044
23559001PLEAS1
50/50
5.39
961921AG1-034 GEN
Solar/Wind Harmer
7.349
942051AE2-217 GEN
Solar/Wind Harmer
14.139
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
944531AF1-118 GEN
Solar/Wind Harmer
32.112
25196608WSDLE5
Adder
8.723
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
971347AH1-153 GEN
Solar/Wind Harmer
3.535
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
962761AG1-125 GEN
Solar/Wind Harmer
33.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.78
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.818
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.15
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
939401AE1-172 GEN
Solar/Wind Harmer
5.095
962781AG1-127 GEN
Solar/Wind Harmer
6.441
235067AD1-061 GEN
Solar/Wind Helper
0.432
237002AB1-128_GEN
Solar/Wind Helper
0.43
208835TUHI V3-051
Solar/Wind Helper
0.021
233950AC2-186 GEN
Solar/Wind Helper
0.113
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
207454AA2-184 E
Solar/Wind Helper
0.301
962771AG1-126 GEN
Solar/Wind Harmer
33.201
970153AG2-106 GEN
Solar/Wind Harmer
21.201
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
22.814
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
24695305TIMB G C
Solar/Wind Harmer
0.609
252519AF1-045_GEN
Solar/Wind Harmer
3.711
25194608D.CRK4
Adder
1.672
946031AF1-268 GEN
Solar/Wind Harmer
6.713
970289AG2-191 GEN
Solar/Wind Harmer
0.773
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
4.941
276806AD2-047 C O1
Solar/Wind Harmer
3.89
24728505AND G1
Adder
3.773
274676JOLIET 29;8U
Adder
29.018
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.753
970935AG2-582 GEN
Adder
241.832
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.046
247621Y3-024
Adder
0.245
971613AH1-306 GEN
Solar/Wind Harmer
3.374
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
965681AG1-436 GEN
Solar/Wind Harmer
8.747
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.732
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
237080AD1-060 GEN
Solar/Wind Helper
0.332
219904AC1-010 C
Solar/Wind Helper
0.059
219906AC1-017 C
Solar/Wind Helper
0.041
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
970179AG2-119 GEN
Solar/Wind Harmer
6.643
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.261
963791AG1-232 GEN
Solar/Wind Harmer
9.652
970289AG2-191 GEN
Solar/Wind Harmer
1.334
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972227AH1-698 GEN1
Adder
2.566
274735ELWOOD EC;4P
Adder
16.119
970169AG2-114 GEN
Solar/Wind Harmer
6.772
959341AF2-225 GEN
Solar/Wind Harmer
7.07
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
959381AF2-229 GEN
Solar/Wind Helper
0.346
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230407AD2-065 C
Solar/Wind Helper
0.039
20720728JCB_W1-129
Solar/Wind Helper
0.055
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
964991AG1-363 GEN
Solar/Wind Helper
4.979
238110AE1-109 GEN3
Solar/Wind Helper
0.107
235063AE1-101 C2
Solar/Wind Helper
1.608
205932AD2-116_GEN
Solar/Wind Helper
0.494
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
316447AC1-158 HLD
Solar/Wind Helper
2.771
219766PARADISE C
Solar/Wind Helper
0.053
203975AE1-071-GEN
Solar/Wind Helper
2.421
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
959091AF2-200 GEN
Solar/Wind Harmer
8.748
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.554
970569AG2-363 GEN
Solar/Wind Harmer
20.202
939741AE1-205 GEN
Solar/Wind Harmer
9.427
23583801GRNGAP
Solar/Wind Helper
5.433
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.596
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.226
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.023
20716928W4-060COL
Solar/Wind Helper
0.05
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270435AC2-044 GEN
Solar/Wind Harmer
0.918
971567AH1-282 GEN
Solar/Wind Harmer
5.517
270007AE1-245 C
Solar/Wind Harmer
0
24729505KEY G4
Adder
6.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
270543AE2-219 C
Solar/Wind Harmer
4.962
971771AH1-392 GEN
Solar/Wind Harmer
7.027
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
971549AH1-272 GEN
Solar/Wind Harmer
14.305
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
970149AG2-104 GEN
Solar/Wind Harmer
17.929
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
971917AH1-482 GEN
Solar/Wind Harmer
9.046
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.086
237038AE2-054 C
Solar/Wind Helper
0.264
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
232417X3-008 C
Solar/Wind Helper
0.226
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
965041AG1-368 GEN
Solar/Wind Harmer
7.193
25196508WSDLE4
Adder
8.634
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.341
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
23750501ELLIOTTS
Solar/Wind Helper
0.573
205956AE1-196_GEN
Solar/Wind Helper
0.494
233901CHERRYDALE C
Solar/Wind Helper
0.226
20715028HAN_X4-015
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.119
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
20390526W1-045 C
Solar/Wind Helper
0.339
3141426STAFORD
Solar/Wind Helper
0.051
233940AF2-379 C
Solar/Wind Helper
0.06
230434AG1-499 GEN
Solar/Wind Helper
0.223
219258KINSLEYDEP C
Solar/Wind Helper
0.075
945111AF1-176 GEN
Solar/Wind Harmer
5.694
270505AE1-170 C O1
Solar/Wind Harmer
7.374
25196008MFTGT1
Adder
1.349
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
972167AH1-666 GEN
Solar/Wind Harmer
5.491
972259AH1-714 GEN
Adder
18.754
274729ELWOOD EC;1P
Adder
16.119
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970571AG2-364 GEN
Solar/Wind Harmer
13.468
238175AF1-290_GEN
Solar/Wind Helper
0.152
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
205916AD1-020 GEN
Solar/Wind Helper
1.664
233944AB2-135 GEN
Solar/Wind Helper
0.573
232408W1-005 C
Solar/Wind Helper
0.493
219907AC1-030 C
Solar/Wind Helper
0.033
20716028EGP_W2-019
Solar/Wind Helper
0.018
20720628TIN_W1-124
Solar/Wind Helper
0.184
24318805MLG1
50/50
9.823
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
970191AG2-125 GEN
Solar/Wind Harmer
1.872
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.15
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
276843GEN-1.7
Solar/Wind Harmer
0.222
972038AH1-567 GEN2
Adder
0.359
238108AE1-109 GEN1
Solar/Wind Helper
0.107
237001AB1-127_GEN
Solar/Wind Helper
0.428
23562501BACKB
Solar/Wind Helper
0.845
233918AB1-142 GEN
Solar/Wind Helper
0.488
228729W2-030 C
Solar/Wind Helper
0.107
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
958491AF2-143 GEN
Solar/Wind Harmer
10.177
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
316006AB2-029 C
Solar/Wind Helper
0.114
232436AB1-176 C
Solar/Wind Helper
0.043
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
316045AC1-158 PL2
Solar/Wind Helper
4.03
219912AD2-042 GEN
Solar/Wind Helper
0.146
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
965651AG1-433 GEN
Solar/Wind Harmer
2.09
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.672
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.941
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
274676JOLIET 29;8U
Adder
30.093
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.459
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.111
227287AC2-120 GEN
Solar/Wind Helper
0.337
232422X3-066 FULL
Solar/Wind Helper
0.111
233964AF2-378 GEN
Solar/Wind Helper
0.041
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.481
957471AF2-041 GEN
Solar/Wind Harmer
13.123
24387305FR-4G C
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
962691AG1-118 GEN
Solar/Wind Harmer
20.32
942111AE2-223 GEN
Solar/Wind Harmer
2.188
235020AA1-095 C
Solar/Wind Helper
0.051
237061AD1-155 GEN
Solar/Wind Helper
1.703
238221AF1-254 C O1
Solar/Wind Helper
0.267
316411AF1-147_GEN1
Solar/Wind Helper
0.865
223402AF1-300 C
Solar/Wind Helper
0.357
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
233946AB2-136 GEN
Solar/Wind Helper
0.553
232410W1-006 C
Solar/Wind Helper
0.493
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274887GEN-1.85
Solar/Wind Harmer
0.178
274826FISK ;BP
Adder
10.773
24728705AND G3
Adder
7.891
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274730ELWOOD EC;6P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
970193AG2-126 GEN
Solar/Wind Harmer
10.106
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
208835TUHI V3-051
Solar/Wind Helper
0.021
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
316044AC1-158 PL1
Solar/Wind Helper
1.259
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
24697605MDL-3G C
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.919
966841AG1-555 GEN
Solar/Wind Harmer
0.78
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238117U2-030
Solar/Wind Helper
0.315
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
232424Y1-079 C
Solar/Wind Helper
0.113
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
316450AC1-158 RIC
Solar/Wind Helper
0.336
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.282
205943AE1-185 GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
228728W1-130C
Solar/Wind Helper
0.052
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.026
219620RIDERU C
Solar/Wind Helper
0.001
971171AH1-044 GEN
Solar/Wind Harmer
8.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
WECLTFEXP_WEC->PJM
CLTF
3.676
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
CPLELTFEXP_CPLE->PJM
CLTF
0.539
SIGELTFEXP_SIGE->PJM
CLTF
0.485
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
NYPJM->LTFIMP_NY
CLTF
4.644
TVALTFEXP_TVA->PJM
CLTF
6.984
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
LGEELTFEXP_LGEE->PJM
CLTF
6.478
MECLTFEXP_MEC->PJM
CLTF
15.273
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.56 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5140.38
MW Contribution:
2.66
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962761AG1-125 GEN
Solar/Wind Harmer
41.016
270520AE2-214 GEN
Solar/Wind Harmer
7.243
270391AF1-285 GEN3
Solar/Wind Harmer
1.393
253333AC1-068 GEN
Solar/Wind Harmer
1.191
270317AD1-130_GEN
Solar/Wind Harmer
3.64
270273AD2-016 GEN
Solar/Wind Harmer
3.013
25326309TAIT D
Adder
1.195
241813AF1-122_GEN
Solar/Wind Harmer
5.897
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.062
270437AC2-090 C
Solar/Wind Harmer
5.862
270216AD2-079_GEN
Solar/Wind Harmer
0.634
274754CRETE EC ;4U
Adder
8.473
274802UNIV PARK;5U
Adder
5.968
274732ELWOOD EC;7P
Adder
16.762
274674JOLIET 9 ;6U
Adder
15.699
235067AD1-061 GEN
Solar/Wind Helper
0.451
237002AB1-128_GEN
Solar/Wind Helper
0.448
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.118
24318905MLG2
50/50
7.027
270349AD2-093_GEN
Solar/Wind Harmer
4.455
270471AD2-092_GEN
Solar/Wind Harmer
4.455
253383AE2-342_GEN
Solar/Wind Harmer
1.04
25322209TAIT E
Adder
10.635
25322209TAIT E
Adder
10.396
253370AE2-315 SEC1
Adder
2.18
270246TR4_N_V150
Solar/Wind Harmer
0.912
241955AC1-078 GEN
Solar/Wind Harmer
8.781
241973AD2-163_GEN1
Solar/Wind Harmer
2.319
241974AD2-163_GEN2
Solar/Wind Harmer
2.319
943861AF1-054 GEN
Solar/Wind Harmer
4.476
943851AF1-053 GEN
Solar/Wind Harmer
2.163
270227U2-072_GEN3
Solar/Wind Harmer
2.274
270228U2-072_GEN4
Solar/Wind Harmer
2.274
962771AG1-126 GEN
Solar/Wind Harmer
41.016
970153AG2-106 GEN
Solar/Wind Harmer
17.885
270284AF1-227 GEN1
Solar/Wind Harmer
6.768
24721905FLATG4
Adder
24.045
276820AF1-078_GEN
Solar/Wind Harmer
1.776
960071AF2-298 GEN
Solar/Wind Harmer
1.647
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
253317AC1-085 GEN4
Solar/Wind Harmer
8.992
946181AF1-283 GEN
Solar/Wind Harmer
13.963
24695305TIMB G C
Solar/Wind Harmer
3.573
270588AE1-091_GEN
Solar/Wind Harmer
11.753
252519AF1-045_GEN
Solar/Wind Harmer
3.859
252524AE2-267 GEN
Solar/Wind Harmer
1.667
25194608D.CRK4
Adder
1.739
946031AF1-268 GEN
Solar/Wind Harmer
8.725
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.137
24728505AND G1
Adder
3.925
274676JOLIET 29;8U
Adder
30.174
274734ELWOOD EC;8P
Adder
16.762
274736ELWOOD EC;9P
Adder
16.762
274682WAUKEGAN ;7U
Adder
18.178
964991AG1-363 GEN
Solar/Wind Helper
5.171
238110AE1-109 GEN3
Solar/Wind Helper
0.115
235063AE1-101 C2
Solar/Wind Helper
1.678
205932AD2-116_GEN
Solar/Wind Helper
0.514
233996TM1833_GEN
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
316447AC1-158 HLD
Solar/Wind Helper
2.876
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.526
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
270166AC1-044 GEN3
50/50
7.109
270485AE1-090_GEN
Solar/Wind Harmer
0.688
972269AH1-719 GEN
Adder
2.545
253398AE2-221_GEN2
Solar/Wind Harmer
4.9
246936BC-WTG1
Solar/Wind Harmer
4.216
270489AE1-102 GEN1
Solar/Wind Harmer
1.401
965011AG1-365 GEN
Solar/Wind Harmer
10.725
958861AF2-177 GEN
Solar/Wind Harmer
11.586
252510AF1-249 C
Solar/Wind Harmer
0.441
945371AF1-202 GEN
Solar/Wind Harmer
7.376
270005AE1-210 C O1
Solar/Wind Harmer
5.743
942081AE2-220 GEN
Solar/Wind Harmer
6.717
270209AC1-174_GEN
Solar/Wind Harmer
4.274
270239V3-007_GEN1
Solar/Wind Harmer
1.807
270331AC1-082 GEN3
Solar/Wind Harmer
0.501
25196808ZIMRHP
Adder
79.685
970825AG2-519 GEN
Solar/Wind Harmer
2.203
25196008MFTGT1
Adder
1.45
274751CRETE EC ;1U
Adder
8.473
274773LINCOLN ;4U
Adder
8.673
274774LINCOLN ;5U
Adder
8.673
274723RIVER EC ;12
Adder
18.412
23583801GRNGAP
Solar/Wind Helper
5.644
238126S14_GEN_1
Solar/Wind Helper
0.836
237085AD2-009_GEN
Solar/Wind Helper
1.667
3141196NOKESVL
Solar/Wind Helper
1.039
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.235
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.091
209116AE2-175 GEN
Solar/Wind Helper
1.799
961421AF2-433 GEN
Solar/Wind Helper
0.441
270594AE1-207 GEN
Solar/Wind Harmer
13.371
270032AE2-172
Solar/Wind Harmer
4.579
23559101PLEAS2
50/50
6.362
970149AG2-104 GEN
Solar/Wind Harmer
25.328
270286AF1-227 GEN2
Solar/Wind Harmer
2.504
270578AF1-285 GEN2
Solar/Wind Harmer
1.393
971073AG2-665 GEN
Solar/Wind Harmer
1.275
270459AD2-067 GEN
Solar/Wind Harmer
10.212
940611AE2-048 GEN
Solar/Wind Harmer
24.76
941391AE2-136 GEN
Solar/Wind Harmer
12.83
270435AC2-044 GEN
Solar/Wind Harmer
2.156
270007AE1-245 C
Solar/Wind Harmer
5.779
24729505KEY G4
Adder
6.914
971567AH1-282 GEN
Solar/Wind Harmer
5.316
270071AF1-092 GEN
Solar/Wind Harmer
15.971
958711AF2-162 GEN
Solar/Wind Harmer
1.074
25196408WSDLE3
Adder
9.339
25196308WSDLE2
Adder
9.258
25196208WSDLE1
Adder
9.235
270051AF1-062 GEN
50/50
11.798
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
970879AG2-548 GEN
Solar/Wind Harmer
8.771
970065AG2-057 GEN
Solar/Wind Harmer
0.921
253394AE2-221_GEN
Solar/Wind Harmer
4.9
246938BC-WTG3
Solar/Wind Harmer
4.289
971191AH1-055 GEN
Solar/Wind Harmer
20.077
965021AG1-366 GEN
Solar/Wind Harmer
2.494
270043AE2-236 GEN
Solar/Wind Harmer
5.865
270367AC2-061_GEN
Solar/Wind Harmer
3.367
270044AE2-322 C
Solar/Wind Harmer
1.388
962031AG1-047 GEN
Solar/Wind Harmer
3.189
957741AF2-068 GEN
Solar/Wind Harmer
15.82
270512AE1-227 GEN2
Solar/Wind Harmer
2.212
270186AC1-089 GEN
Solar/Wind Harmer
6.425
270240V3-007_GEN2
Solar/Wind Harmer
6.498
970825AG2-519 GEN
Solar/Wind Harmer
5.915
25196008MFTGT1
Adder
1.404
274772LINCOLN ;3U
Adder
8.673
274724RIVER EC ;11
Adder
18.196
972259AH1-714 GEN
Adder
19.5
274729ELWOOD EC;1P
Adder
16.762
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.186
316415AF1-147_GEN2
Solar/Wind Helper
0.898
205916AD1-020 GEN
Solar/Wind Helper
1.732
233944AB2-135 GEN
Solar/Wind Helper
0.596
232408W1-005 C
Solar/Wind Helper
0.513
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
218428ETC SOLAR C
Solar/Wind Helper
0.005
219908AB1-139 C
Solar/Wind Helper
0.075
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.093
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
961821AG1-024 GEN
Solar/Wind Harmer
10.368
972239AH1-704 GEN
Adder
2.66
945631AF1-228 GEN
Solar/Wind Harmer
5.449
270223U2-072_GEN1
Solar/Wind Harmer
2.274
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
8.025
253338AC1-165 GEN
Solar/Wind Harmer
1.235
270263AC1-001 GEN
Solar/Wind Harmer
1.17
241972AD1-140 GEN
Solar/Wind Harmer
5.01
270340AC2-060 GEN
Solar/Wind Harmer
3.331
270191TR4_S_V150
Solar/Wind Harmer
3.216
959331AF2-224 GEN
Solar/Wind Harmer
10.725
965041AG1-368 GEN
Solar/Wind Harmer
10.701
966831AG1-554 GEN
Solar/Wind Harmer
1.275
25196508WSDLE4
Adder
8.979
964611AG1-324 GEN
Solar/Wind Harmer
4.11
274776LINCOLN ;7U
Adder
8.673
274687WILL CNTY;4U
Adder
28.512
274687WILL CNTY;4U
Adder
28.512
274731ELWOOD EC;2P
Adder
16.762
274733ELWOOD EC;3P
Adder
16.762
274746AC1-111 G10
Adder
5.677
238118U2-030_1
Solar/Wind Helper
0.345
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.647
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.372
205956AE1-196_GEN
Solar/Wind Helper
0.514
233901CHERRYDALE C
Solar/Wind Helper
0.235
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
20720628TIN_W1-124
Solar/Wind Helper
0.192
316164AC1-076 GEN
Solar/Wind Helper
1.108
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.069
20675128HRM_W1-127
Solar/Wind Helper
0.03
24318805MLG1
50/50
10.127
270475AD2-096_GEN
50/50
7.137
270518AE2-148 GEN
Solar/Wind Harmer
13.818
253325AC1-069 GEN
Solar/Wind Harmer
1.191
971199AH1-059 GEN
Solar/Wind Harmer
2.312
270491AE1-102 GEN2
Solar/Wind Harmer
1.401
270004AE1-209 GEN
Solar/Wind Harmer
5.743
24379505HDWTR1G C
Solar/Wind Harmer
8.305
270329AC1-082 GEN1
Solar/Wind Harmer
0.5
274753CRETE EC ;3U
Adder
8.473
274814UNIV PK N;0U
Adder
5.182
274807UNIV PK N;3U
Adder
5.171
274803UNIV PARK;6U
Adder
5.968
972038AH1-567 GEN2
Adder
0.373
238108AE1-109 GEN1
Solar/Wind Helper
0.115
23562501BACKB
Solar/Wind Helper
1.023
237001AB1-127_GEN
Solar/Wind Helper
0.446
233918AB1-142 GEN
Solar/Wind Helper
0.508
228729W2-030 C
Solar/Wind Helper
0.112
946101AF1-275 GEN
Solar/Wind Harmer
1.811
942861AE2-305 GEN
Solar/Wind Harmer
9.069
270269AC2-059
Solar/Wind Harmer
10.571
972159AH1-661 GEN
Adder
1.106
241960AC2-195 GEN
Solar/Wind Harmer
3.055
971073AG2-665 GEN
Solar/Wind Harmer
8.771
25326109MON D
Adder
1.442
927014AC1-188 GEN
Solar/Wind Harmer
1.717
253400AC2-068 GEN
Solar/Wind Harmer
0.886
25183208HLCRTG
Solar/Wind Harmer
6.427
944541AF1-119 GEN
Solar/Wind Harmer
4.444
25194508D.CRK3
Adder
1.496
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.456
270201AC2-176 GEN
Solar/Wind Harmer
5.42
964611AG1-324 GEN
Solar/Wind Harmer
0.551
270031AE2-169
Solar/Wind Harmer
8.576
270383AD1-128 GEN
Solar/Wind Harmer
6.419
247620Y3-023
Adder
0.483
24728805RICHG1
Adder
3.96
274695ROCKY RD ;2P
Adder
11.267
235054AD2-180 GEN
Solar/Wind Helper
2.054
235531U2-073 GEN
Solar/Wind Helper
3.347
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.972
316045AC1-158 PL2
Solar/Wind Helper
4.182
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
20674328GAR_V4-001
Solar/Wind Helper
0.023
970155AG2-107 GEN
Solar/Wind Harmer
17.885
971995AH1-542 GEN
Solar/Wind Harmer
12.463
253370AE2-315 SEC1
Adder
2.18
253371AE2-315 SEC2
Adder
2.062
965421AG1-410 GEN
Solar/Wind Harmer
32.318
253316AC1-085 GEN3
Solar/Wind Harmer
8.992
946171AF1-282 GEN
Solar/Wind Harmer
10.741
965651AG1-433 GEN
Solar/Wind Harmer
5.801
252516AE2-318_GEN
Solar/Wind Harmer
10.604
270024AE2-089 GEN
Solar/Wind Harmer
4.961
25194608D.CRK4
Adder
1.739
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.137
24728605AND G2
Adder
3.925
274676JOLIET 29;8U
Adder
31.291
972203AH1-686 GEN
Adder
2.344
274745AC1-111 GEN9
Adder
5.677
274682WAUKEGAN ;7U
Adder
18.178
316095T157 G97
Solar/Wind Helper
1.515
238185AF2-356 C
Solar/Wind Helper
2.686
238109AE1-109 GEN2
Solar/Wind Helper
0.115
238120AE2-309 GEN
Solar/Wind Helper
0.534
23751101LEADS_P59
Solar/Wind Helper
2.15
23777801MSM_W1-116
Solar/Wind Helper
0.116
227287AC2-120 GEN
Solar/Wind Helper
0.35
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.513
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.501
270119AB2-067 GEN1
50/50
7.109
253378AE2-206_GEN
Solar/Wind Harmer
3.997
25326509SID D
Adder
1.451
970879AG2-548 GEN
Solar/Wind Harmer
1.275
246937BC-WTG2
Solar/Wind Harmer
4.216
247607V1-011 GEN
Solar/Wind Harmer
4.231
962581AG1-107 GEN
Solar/Wind Harmer
5.356
961491AF2-440 GEN
Solar/Wind Harmer
2.226
942221AE2-234 GEN
Solar/Wind Harmer
3.71
274770LINCOLN ;1U
Adder
8.673
274771LINCOLN ;2U
Adder
8.673
274805UNIV PK N;1U
Adder
5.149
274696ROCKY RD ;4P
Adder
11.533
274697ROCKY RD ;3P
Adder
3.061
23751201ROTHROCK
Solar/Wind Helper
0.836
235020AA1-095 C
Solar/Wind Helper
0.054
237061AD1-155 GEN
Solar/Wind Helper
1.772
238221AF1-254 C O1
Solar/Wind Helper
0.278
316411AF1-147_GEN1
Solar/Wind Helper
0.898
223402AF1-300 C
Solar/Wind Helper
0.371
233930AB2-032 GEN
Solar/Wind Helper
0.385
233982AB2-133 GEN
Solar/Wind Helper
0.363
233946AB2-136 GEN
Solar/Wind Helper
0.575
232410W1-006 C
Solar/Wind Helper
0.513
233952AC2-187 GEN
Solar/Wind Helper
0.235
233954AC2-188 GEN
Solar/Wind Helper
0.235
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.051
207471AF2-354 C
Solar/Wind Helper
0.17
23559001PLEAS1
50/50
6.362
961921AG1-034 GEN
Solar/Wind Harmer
15.551
270287AF1-227 GEN3
Solar/Wind Harmer
2.504
942051AE2-217 GEN
Solar/Wind Harmer
20.995
942871AE2-306 GEN
Solar/Wind Harmer
1.045
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
958581AF2-149 GEN
Solar/Wind Harmer
4.712
957541AF2-048 GEN
Solar/Wind Harmer
1.717
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.358
25196608WSDLE5
Adder
9.072
252507AC2-088 GEN
Solar/Wind Harmer
1.892
270063AE2-323 C
Solar/Wind Harmer
2.32
971347AH1-153 GEN
Solar/Wind Harmer
5.266
270330AC1-082 GEN2
Solar/Wind Harmer
0.5
274752CRETE EC ;2U
Adder
8.473
24728705AND G3
Adder
8.209
274826FISK ;BP
Adder
11.201
274730ELWOOD EC;6P
Adder
16.762
238127S14_GEN_2
Solar/Wind Helper
0.836
238152AF2-075_GEN
Solar/Wind Helper
0.715
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.513
316044AC1-158 PL1
Solar/Wind Helper
1.307
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.586
202652Y1-033 WT C
Solar/Wind Helper
0.504
270120AB2-067 GEN2
50/50
7.109
270054AF2-122 C O1
Solar/Wind Harmer
3.972
938701AE1-092 GEN
Solar/Wind Harmer
23.766
270462AD2-086
Solar/Wind Harmer
7.908
253415AE1-040 GEN
Solar/Wind Harmer
1.242
253349AC2-067 GEN
Solar/Wind Harmer
2.203
270247TR4_N_V136
Solar/Wind Harmer
0.912
942801AE2-298 GEN
Solar/Wind Harmer
1.621
960971AF2-388 GEN
Solar/Wind Harmer
11.601
25194408D.CRK1
Adder
8
970883AG2-550 GEN
Solar/Wind Harmer
10.561
970349AG2-230 GEN
Solar/Wind Harmer
15.797
270599AE1-208 GEN
Solar/Wind Harmer
8.576
926881AC1-175 GEN
Solar/Wind Harmer
5.862
944231AF1-091 GEN
Solar/Wind Harmer
18.887
24728905RICHG2
Adder
3.96
274808UNIV PK N;4U
Adder
5.115
274674JOLIET 9 ;6U
Adder
15.699
274693ROCKY RD ;1P
Adder
11.156
274683WAUKEGAN ;8U
Adder
21.305
274683WAUKEGAN ;8U
Adder
9.68
23585401KL_K28_T16
Solar/Wind Helper
1.5
238117U2-030
Solar/Wind Helper
0.345
238148AE2-230_GEN2
Solar/Wind Helper
0.501
235062AE1-101 C1
Solar/Wind Helper
1.678
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.371
232424Y1-079 C
Solar/Wind Helper
0.118
232428Y3-058 C
Solar/Wind Helper
0.342
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.293
20675428EAM_W2-061
Solar/Wind Helper
0.016
961431AF2-434 GEN
Solar/Wind Helper
0.441
960001AF2-291 GEN
Solar/Wind Harmer
3.25
270258AD1-119 GEN
Solar/Wind Harmer
2.156
270297AD1-101 GEN
Solar/Wind Harmer
2.147
270222AC2-111 GEN
Solar/Wind Harmer
4.718
270510AE1-227 GEN1
Solar/Wind Harmer
2.605
970091AG2-072 GEN
Adder
77.647
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.283
233987AB2-037 GEN
Solar/Wind Helper
2.369
232417X3-008 C
Solar/Wind Helper
0.235
233923SMA
Solar/Wind Helper
0.76
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.329
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
957921AF2-086 GEN
Solar/Wind Helper
0.436
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.313
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.443
961331AF2-424 GEN
Solar/Wind Helper
0.442
270224U2-072_GEN2
Solar/Wind Harmer
2.274
270291AC1-194 GEN
Solar/Wind Harmer
5.61
253406AD2-031_GEN
Solar/Wind Harmer
1.383
965051AG1-369 GEN
Solar/Wind Harmer
5.355
270377AD1-106 GEN
Solar/Wind Harmer
5.62
971985AH1-537 GEN
Solar/Wind Harmer
18.964
945581AF1-223 GEN
Solar/Wind Harmer
4.795
971029AG2-637 GEN
Solar/Wind Harmer
15.851
970031AG2-029 GEN
Solar/Wind Harmer
26.415
270404AC1-167 GEN
Solar/Wind Harmer
1.144
247536S-71 GEN
Solar/Wind Harmer
4.271
961761AG1-017 GEN
Solar/Wind Harmer
0.451
274775LINCOLN ;6U
Adder
8.673
274777LINCOLN ;8U
Adder
8.673
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.789
274675JOLIET 29;7U
Adder
31.291
274675JOLIET 29;7U
Adder
30.174
23750701CROSSCHOOL
Solar/Wind Helper
1.517
205943AE1-185 GEN
Solar/Wind Helper
0.515
233915AB1-141 GEN
Solar/Wind Helper
0.508
228728W1-130C
Solar/Wind Helper
0.055
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
203955AF1-039 C O1
Solar/Wind Helper
0.332
212266LOR1
Solar/Wind Helper
0.302
247621Y3-024
Adder
0.255
316097T157 G90
Solar/Wind Helper
1.515
238147AE2-230_GEN1
Solar/Wind Helper
0.501
237080AD1-060 GEN
Solar/Wind Helper
0.346
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.028
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
270231U2-072_GEN5
Solar/Wind Harmer
2.274
253343AC1-166 GEN
Solar/Wind Harmer
1.235
270302AB2-170 GEN
Solar/Wind Harmer
9.522
970179AG2-119 GEN
Solar/Wind Harmer
8.806
253372AE2-315 SEC3
Adder
2.062
253372AE2-315 SEC3
Adder
2.062
25306009OHH W.
Adder
3.128
957201AF2-014 GEN
Solar/Wind Harmer
4.888
253433AC1-085 GEN1
Solar/Wind Harmer
5.708
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.604
963791AG1-232 GEN
Solar/Wind Harmer
14.371
274827FISK ;RP
Adder
7.938
274800UNIV PARK;3U
Adder
5.964
274801UNIV PARK;4U
Adder
5.964
972227AH1-698 GEN1
Adder
2.668
274735ELWOOD EC;4P
Adder
16.762
274744AC1-111 GEN8
Adder
5.677
238169AE2-226 GEN1
Solar/Wind Helper
0.708
238170AE2-226 GEN2
Solar/Wind Helper
0.708
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.36
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.795
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.064
207408W3-077 C
Solar/Wind Helper
0.085
209054AE2-059 GEN
Solar/Wind Helper
0.08
25196708WSDLE6
Adder
9.211
270543AE2-219 C
Solar/Wind Harmer
10.561
25196108MFTGT2
Adder
1.598
25196108MFTGT2
Adder
1.484
274728ELWOOD EC;5P
Adder
16.762
20390526W1-045 C
Solar/Wind Helper
0.354
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.078
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.036
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.443
963151AG1-164 GEN
Solar/Wind Helper
0.443
961341AF2-425 GEN
Solar/Wind Helper
0.442
212507AE2-042_GEN
Solar/Wind Helper
1.561
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.944
NYPJM->LTFIMP_NY
CLTF
4.85
TVALTFEXP_TVA->PJM
CLTF
7.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.743
LGEELTFEXP_LGEE->PJM
CLTF
6.747
MECLTFEXP_MEC->PJM
CLTF
15.894
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.079
WECLTFEXP_WEC->PJM
CLTF
3.823
LAGNLTFEXP_LAGN->PJM
CLTF
14.823
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.742
CPLELTFEXP_CPLE->PJM
CLTF
0.593
SIGELTFEXP_SIGE->PJM
CLTF
0.505

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.72 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5108.61
MW Contribution:
2.67
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
40.857
970153AG2-106 GEN
Solar/Wind Harmer
17.815
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.892
276820AF1-078_GEN
Solar/Wind Harmer
1.772
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
24695305TIMB G C
Solar/Wind Harmer
3.564
270588AE1-091_GEN
Solar/Wind Harmer
11.739
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.7
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.122
24728505AND G1
Adder
3.913
274676JOLIET 29;8U
Adder
30.081
274734ELWOOD EC;8P
Adder
16.71
274736ELWOOD EC;9P
Adder
16.71
274682WAUKEGAN ;7U
Adder
18.122
964991AG1-363 GEN
Solar/Wind Helper
5.16
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.674
205932AD2-116_GEN
Solar/Wind Helper
0.513
233996TM1833_GEN
Solar/Wind Helper
0.207
232426Y1-080 FULL
Solar/Wind Helper
0.039
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.519
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
270166AC1-044 GEN3
50/50
7.082
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.564
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.696
958861AF2-177 GEN
Solar/Wind Harmer
11.552
252510AF1-249 C
Solar/Wind Harmer
0.44
945371AF1-202 GEN
Solar/Wind Harmer
7.355
270005AE1-210 C O1
Solar/Wind Harmer
5.726
25196808ZIMRHP
Adder
79.465
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
942081AE2-220 GEN
Solar/Wind Harmer
6.698
270209AC1-174_GEN
Solar/Wind Harmer
4.262
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.448
274773LINCOLN ;4U
Adder
8.646
274774LINCOLN ;5U
Adder
8.646
274723RIVER EC ;12
Adder
18.356
23583801GRNGAP
Solar/Wind Helper
5.632
238126S14_GEN_1
Solar/Wind Helper
0.833
237085AD2-009_GEN
Solar/Wind Helper
1.663
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.235
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.331
270032AE2-172
Solar/Wind Harmer
4.566
270051AF1-062 GEN
50/50
11.783
960801AF2-371 GEN
Solar/Wind Harmer
2.935
964871AG1-351 GEN
Solar/Wind Harmer
2.026
970879AG2-548 GEN
Solar/Wind Harmer
8.757
970065AG2-057 GEN
Solar/Wind Harmer
0.921
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.279
971191AH1-055 GEN
Solar/Wind Harmer
20.022
965021AG1-366 GEN
Solar/Wind Harmer
2.488
270043AE2-236 GEN
Solar/Wind Harmer
5.848
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
962031AG1-047 GEN
Solar/Wind Harmer
3.18
957741AF2-068 GEN
Solar/Wind Harmer
15.775
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.479
970825AG2-519 GEN
Solar/Wind Harmer
5.897
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.646
274724RIVER EC ;11
Adder
18.141
972259AH1-714 GEN
Adder
19.441
274729ELWOOD EC;1P
Adder
16.71
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.185
972239AH1-704 GEN
Adder
2.673
961821AG1-024 GEN
Solar/Wind Harmer
10.359
945631AF1-228 GEN
Solar/Wind Harmer
5.44
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.013
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.168
241972AD1-140 GEN
Solar/Wind Harmer
4.999
270340AC2-060 GEN
Solar/Wind Harmer
3.323
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.696
965041AG1-368 GEN
Solar/Wind Harmer
10.674
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.955
964611AG1-324 GEN
Solar/Wind Harmer
4.099
274776LINCOLN ;7U
Adder
8.646
274687WILL CNTY;4U
Adder
28.425
274687WILL CNTY;4U
Adder
28.425
274731ELWOOD EC;2P
Adder
16.71
274733ELWOOD EC;3P
Adder
16.71
274746AC1-111 G10
Adder
5.66
238118U2-030_1
Solar/Wind Helper
0.344
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.644
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
946101AF1-275 GEN
Solar/Wind Harmer
1.808
942861AE2-305 GEN
Solar/Wind Harmer
9.053
270269AC2-059
Solar/Wind Harmer
10.554
972159AH1-661 GEN
Adder
1.111
241960AC2-195 GEN
Solar/Wind Harmer
3.053
971073AG2-665 GEN
Solar/Wind Harmer
8.757
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.713
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.41
944541AF1-119 GEN
Solar/Wind Harmer
4.431
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.405
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.551
270383AD1-128 GEN
Solar/Wind Harmer
6.401
247620Y3-023
Adder
0.482
24728805RICHG1
Adder
3.949
274695ROCKY RD ;2P
Adder
11.232
235054AD2-180 GEN
Solar/Wind Helper
2.044
235531U2-073 GEN
Solar/Wind Helper
3.333
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
970155AG2-107 GEN
Solar/Wind Harmer
17.815
971995AH1-542 GEN
Solar/Wind Harmer
12.451
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.241
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.784
252516AE2-318_GEN
Solar/Wind Harmer
10.575
270024AE2-089 GEN
Solar/Wind Harmer
4.947
25194608D.CRK4
Adder
1.734
316415AF1-147_GEN2
Solar/Wind Helper
0.896
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
23559001PLEAS1
50/50
6.18
961921AG1-034 GEN
Solar/Wind Harmer
15.539
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.96
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.716
957541AF2-048 GEN
Solar/Wind Harmer
1.713
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.25
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.25
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.448
24728705AND G3
Adder
8.184
274826FISK ;BP
Adder
11.167
274730ELWOOD EC;6P
Adder
16.71
238127S14_GEN_2
Solar/Wind Helper
0.833
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.582
202652Y1-033 WT C
Solar/Wind Helper
0.501
270120AB2-067 GEN2
50/50
7.082
270054AF2-122 C O1
Solar/Wind Harmer
3.971
938701AE1-092 GEN
Solar/Wind Harmer
23.731
270462AD2-086
Solar/Wind Harmer
7.892
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
960971AF2-388 GEN
Solar/Wind Harmer
11.568
25194408D.CRK1
Adder
7.978
970883AG2-550 GEN
Solar/Wind Harmer
10.531
970349AG2-230 GEN
Solar/Wind Harmer
15.75
270599AE1-208 GEN
Solar/Wind Harmer
8.551
926881AC1-175 GEN
Solar/Wind Harmer
5.845
944231AF1-091 GEN
Solar/Wind Harmer
18.84
24728905RICHG2
Adder
3.949
274808UNIV PK N;4U
Adder
5.099
274674JOLIET 9 ;6U
Adder
15.65
274693ROCKY RD ;1P
Adder
11.121
274683WAUKEGAN ;8U
Adder
21.239
274683WAUKEGAN ;8U
Adder
9.65
23585401KL_K28_T16
Solar/Wind Helper
1.493
238117U2-030
Solar/Wind Helper
0.344
238148AE2-230_GEN2
Solar/Wind Helper
0.5
235062AE1-101 C1
Solar/Wind Helper
1.674
270119AB2-067 GEN1
50/50
7.082
253378AE2-206_GEN
Solar/Wind Harmer
3.988
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.273
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.646
274771LINCOLN ;2U
Adder
8.646
274805UNIV PK N;1U
Adder
5.133
274696ROCKY RD ;4P
Adder
11.497
274697ROCKY RD ;3P
Adder
3.051
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.83
237061AD1-155 GEN
Solar/Wind Helper
1.768
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233930AB2-032 GEN
Solar/Wind Helper
0.384
233982AB2-133 GEN
Solar/Wind Helper
0.362
233946AB2-136 GEN
Solar/Wind Helper
0.574
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
23559101PLEAS2
50/50
6.18
970149AG2-104 GEN
Solar/Wind Harmer
25.229
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
971073AG2-665 GEN
Solar/Wind Harmer
1.273
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
960001AF2-291 GEN
Solar/Wind Harmer
3.242
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.376
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.363
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
962761AG1-125 GEN
Solar/Wind Harmer
40.857
270520AE2-214 GEN
Solar/Wind Harmer
7.233
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.008
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.894
971201AH1-060 GEN
Solar/Wind Harmer
1.842
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.845
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.448
274802UNIV PARK;5U
Adder
5.949
274732ELWOOD EC;7P
Adder
16.71
274674JOLIET 9 ;6U
Adder
15.65
235067AD1-061 GEN
Solar/Wind Helper
0.45
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.441
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.603
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.62
965051AG1-369 GEN
Solar/Wind Harmer
5.342
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.781
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.807
970031AG2-029 GEN
Solar/Wind Harmer
26.342
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.646
274777LINCOLN ;8U
Adder
8.646
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.777
274675JOLIET 29;7U
Adder
31.195
274675JOLIET 29;7U
Adder
30.081
23750701CROSSCHOOL
Solar/Wind Helper
1.512
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.507
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
203955AF1-039 C O1
Solar/Wind Helper
0.331
24639705ELKHART HY
Adder
0.161
274812UNIV PK N;8U
Adder
5.122
24728605AND G2
Adder
3.913
274676JOLIET 29;8U
Adder
31.195
972203AH1-686 GEN
Adder
2.333
274745AC1-111 GEN9
Adder
5.66
274682WAUKEGAN ;7U
Adder
18.122
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.674
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.532
23751101LEADS_P59
Solar/Wind Helper
2.129
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
24318905MLG2
50/50
7.035
270349AD2-093_GEN
Solar/Wind Harmer
4.445
270471AD2-092_GEN
Solar/Wind Harmer
4.445
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.371
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.5
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
241955AC1-078 GEN
Solar/Wind Harmer
8.768
241973AD2-163_GEN1
Solar/Wind Harmer
2.315
241974AD2-163_GEN2
Solar/Wind Harmer
2.315
943861AF1-054 GEN
Solar/Wind Harmer
4.468
943851AF1-053 GEN
Solar/Wind Harmer
2.159
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.8
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.877
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.332
274827FISK ;RP
Adder
7.914
274800UNIV PARK;3U
Adder
5.946
274801UNIV PARK;4U
Adder
5.946
972227AH1-698 GEN1
Adder
2.66
274735ELWOOD EC;4P
Adder
16.71
274744AC1-111 GEN8
Adder
5.66
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
270459AD2-067 GEN
Solar/Wind Harmer
10.203
940611AE2-048 GEN
Solar/Wind Harmer
24.928
941391AE2-136 GEN
Solar/Wind Harmer
12.917
270435AC2-044 GEN
Solar/Wind Harmer
2.151
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.319
24729505KEY G4
Adder
6.894
270071AF1-092 GEN
Solar/Wind Harmer
15.924
958711AF2-162 GEN
Solar/Wind Harmer
1.071
25196408WSDLE3
Adder
9.314
25196308WSDLE2
Adder
9.233
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.531
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.48
274728ELWOOD EC;5P
Adder
16.71
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
24318805MLG1
50/50
10.084
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.795
253325AC1-069 GEN
Solar/Wind Harmer
1.189
971199AH1-059 GEN
Solar/Wind Harmer
2.315
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270004AE1-209 GEN
Solar/Wind Harmer
5.726
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
24379505HDWTR1G C
Solar/Wind Harmer
8.281
274753CRETE EC ;3U
Adder
8.448
274814UNIV PK N;0U
Adder
5.166
274807UNIV PK N;3U
Adder
5.155
274803UNIV PARK;6U
Adder
5.949
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.015
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.507
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.441
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.966
WECLTFEXP_WEC->PJM
CLTF
3.811
LAGNLTFEXP_LAGN->PJM
CLTF
14.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.682
CPLELTFEXP_CPLE->PJM
CLTF
0.578
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.545
NYPJM->LTFIMP_NY
CLTF
4.834
TVALTFEXP_TVA->PJM
CLTF
7.257
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.337
LGEELTFEXP_LGEE->PJM
CLTF
6.725
MECLTFEXP_MEC->PJM
CLTF
15.842
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.34 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5094.21
MW Contribution:
2.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.852
276820AF1-078_GEN
Solar/Wind Harmer
1.772
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
270166AC1-044 GEN3
50/50
7.073
23684201S70BUS2
50/50
0.168
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.576
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.694
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
972239AH1-704 GEN
Adder
2.68
961821AG1-024 GEN
Solar/Wind Harmer
10.365
945631AF1-228 GEN
Solar/Wind Harmer
5.442
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270340AC2-060 GEN
Solar/Wind Harmer
3.324
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.694
965041AG1-368 GEN
Solar/Wind Harmer
10.672
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.954
964611AG1-324 GEN
Solar/Wind Harmer
4.098
274776LINCOLN ;7U
Adder
8.644
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274746AC1-111 G10
Adder
5.658
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
946101AF1-275 GEN
Solar/Wind Harmer
1.809
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.698
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.12
24728505AND G1
Adder
3.912
274676JOLIET 29;8U
Adder
30.072
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.673
205932AD2-116_GEN
Solar/Wind Helper
0.513
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.518
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
270051AF1-062 GEN
50/50
11.788
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
970065AG2-057 GEN
Solar/Wind Harmer
0.922
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
971191AH1-055 GEN
Solar/Wind Harmer
20.024
965021AG1-366 GEN
Solar/Wind Harmer
2.487
270043AE2-236 GEN
Solar/Wind Harmer
5.847
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
972259AH1-714 GEN
Adder
19.435
274729ELWOOD EC;1P
Adder
16.705
238175AF1-290_GEN
Solar/Wind Helper
0.158
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
23559001PLEAS1
50/50
6.109
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.967
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.723
957541AF2-048 GEN
Solar/Wind Harmer
1.714
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.241
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.445
24728705AND G3
Adder
8.182
274826FISK ;BP
Adder
11.164
274730ELWOOD EC;6P
Adder
16.705
238127S14_GEN_2
Solar/Wind Helper
0.83
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
270119AB2-067 GEN1
50/50
7.073
23684101S70BUS1
50/50
0.165
253378AE2-206_GEN
Solar/Wind Harmer
3.989
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.274
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.644
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274696ROCKY RD ;4P
Adder
11.494
274697ROCKY RD ;3P
Adder
3.05
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
23583801GRNGAP
Solar/Wind Helper
5.632
238126S14_GEN_1
Solar/Wind Helper
0.83
237085AD2-009_GEN
Solar/Wind Helper
1.662
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
942861AE2-305 GEN
Solar/Wind Harmer
9.054
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
247620Y3-023
Adder
0.482
24728805RICHG1
Adder
3.948
274695ROCKY RD ;2P
Adder
11.229
235054AD2-180 GEN
Solar/Wind Helper
2.035
235531U2-073 GEN
Solar/Wind Helper
3.323
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
23559101PLEAS2
50/50
6.109
970149AG2-104 GEN
Solar/Wind Harmer
25.209
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
270120AB2-067 GEN2
50/50
7.073
270054AF2-122 C O1
Solar/Wind Harmer
3.974
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
960971AF2-388 GEN
Solar/Wind Harmer
11.565
25194408D.CRK1
Adder
7.977
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270599AE1-208 GEN
Solar/Wind Harmer
8.55
926881AC1-175 GEN
Solar/Wind Harmer
5.844
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728905RICHG2
Adder
3.948
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274693ROCKY RD ;1P
Adder
11.118
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
23585401KL_K28_T16
Solar/Wind Helper
1.485
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.673
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
962761AG1-125 GEN
Solar/Wind Harmer
40.825
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.01
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.844
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.445
274802UNIV PARK;5U
Adder
5.948
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.607
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.625
965051AG1-369 GEN
Solar/Wind Harmer
5.341
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.776
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
23750701CROSSCHOOL
Solar/Wind Helper
1.507
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
970155AG2-107 GEN
Solar/Wind Harmer
17.802
971995AH1-542 GEN
Solar/Wind Harmer
12.457
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.239
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
24639705ELKHART HY
Adder
0.16
274812UNIV PK N;8U
Adder
5.12
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
24318905MLG2
50/50
7.043
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.805
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.876
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.329
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972227AH1-698 GEN1
Adder
2.659
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
270459AD2-067 GEN
Solar/Wind Harmer
10.209
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.325
24729505KEY G4
Adder
6.892
270071AF1-092 GEN
Solar/Wind Harmer
15.92
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.53
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274728ELWOOD EC;5P
Adder
16.705
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
960001AF2-291 GEN
Solar/Wind Harmer
3.243
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.346
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.581
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
24318805MLG1
50/50
10.069
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
274753CRETE EC ;3U
Adder
8.445
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274803UNIV PARK;6U
Adder
5.948
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.006
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
NYPJM->LTFIMP_NY
CLTF
4.833
TVALTFEXP_TVA->PJM
CLTF
7.253
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
LGEELTFEXP_LGEE->PJM
CLTF
6.723
MECLTFEXP_MEC->PJM
CLTF
15.837
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
WECLTFEXP_WEC->PJM
CLTF
3.81
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
CPLELTFEXP_CPLE->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.503

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.34 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5094.21
MW Contribution:
2.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
40.825
970153AG2-106 GEN
Solar/Wind Harmer
17.802
270284AF1-227 GEN1
Solar/Wind Harmer
6.753
24721905FLATG4
Adder
23.852
276820AF1-078_GEN
Solar/Wind Harmer
1.772
270119AB2-067 GEN1
50/50
7.073
23684101S70BUS1
50/50
0.165
253378AE2-206_GEN
Solar/Wind Harmer
3.989
25326509SID D
Adder
1.448
970879AG2-548 GEN
Solar/Wind Harmer
1.274
246937BC-WTG2
Solar/Wind Harmer
4.206
247607V1-011 GEN
Solar/Wind Harmer
4.221
962581AG1-107 GEN
Solar/Wind Harmer
5.341
961491AF2-440 GEN
Solar/Wind Harmer
2.22
942221AE2-234 GEN
Solar/Wind Harmer
3.699
274770LINCOLN ;1U
Adder
8.644
270166AC1-044 GEN3
50/50
7.073
23684201S70BUS2
50/50
0.168
946101AF1-275 GEN
Solar/Wind Harmer
1.809
942861AE2-305 GEN
Solar/Wind Harmer
9.054
270269AC2-059
Solar/Wind Harmer
10.558
972159AH1-661 GEN
Adder
1.114
241960AC2-195 GEN
Solar/Wind Harmer
3.054
971073AG2-665 GEN
Solar/Wind Harmer
8.762
25326109MON D
Adder
1.438
927014AC1-188 GEN
Solar/Wind Harmer
1.714
253400AC2-068 GEN
Solar/Wind Harmer
0.884
25183208HLCRTG
Solar/Wind Harmer
6.409
944541AF1-119 GEN
Solar/Wind Harmer
4.43
25194508D.CRK3
Adder
1.491
252509AD1-136 GEN
Solar/Wind Harmer
0.27
970885AG2-551 GEN
Solar/Wind Harmer
2.449
270201AC2-176 GEN
Solar/Wind Harmer
5.404
964611AG1-324 GEN
Solar/Wind Harmer
0.55
270031AE2-169
Solar/Wind Harmer
8.55
270383AD1-128 GEN
Solar/Wind Harmer
6.399
247620Y3-023
Adder
0.482
270120AB2-067 GEN2
50/50
7.073
270054AF2-122 C O1
Solar/Wind Harmer
3.974
938701AE1-092 GEN
Solar/Wind Harmer
23.739
270462AD2-086
Solar/Wind Harmer
7.893
253415AE1-040 GEN
Solar/Wind Harmer
1.24
253349AC2-067 GEN
Solar/Wind Harmer
2.197
270247TR4_N_V136
Solar/Wind Harmer
0.91
942801AE2-298 GEN
Solar/Wind Harmer
1.617
962761AG1-125 GEN
Solar/Wind Harmer
40.825
270520AE2-214 GEN
Solar/Wind Harmer
7.236
270391AF1-285 GEN3
Solar/Wind Harmer
1.39
253333AC1-068 GEN
Solar/Wind Harmer
1.189
270317AD1-130_GEN
Solar/Wind Harmer
3.633
270273AD2-016 GEN
Solar/Wind Harmer
3.01
25326309TAIT D
Adder
1.192
241813AF1-122_GEN
Solar/Wind Harmer
5.898
971201AH1-060 GEN
Solar/Wind Harmer
1.843
944031AF1-071 GEN
Solar/Wind Harmer
1.059
270437AC2-090 C
Solar/Wind Harmer
5.844
270216AD2-079_GEN
Solar/Wind Harmer
0.632
274754CRETE EC ;4U
Adder
8.445
274802UNIV PARK;5U
Adder
5.948
274732ELWOOD EC;7P
Adder
16.705
274674JOLIET 9 ;6U
Adder
15.646
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.447
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.442
961331AF2-424 GEN
Solar/Wind Helper
0.44
270224U2-072_GEN2
Solar/Wind Harmer
2.27
270291AC1-194 GEN
Solar/Wind Harmer
5.607
253406AD2-031_GEN
Solar/Wind Harmer
1.379
270377AD1-106 GEN
Solar/Wind Harmer
5.625
965051AG1-369 GEN
Solar/Wind Harmer
5.341
971985AH1-537 GEN
Solar/Wind Harmer
18.912
945581AF1-223 GEN
Solar/Wind Harmer
4.78
270404AC1-167 GEN
Solar/Wind Harmer
1.141
971029AG2-637 GEN
Solar/Wind Harmer
15.805
970031AG2-029 GEN
Solar/Wind Harmer
26.336
247536S-71 GEN
Solar/Wind Harmer
4.259
961761AG1-017 GEN
Solar/Wind Harmer
0.45
274775LINCOLN ;6U
Adder
8.644
274777LINCOLN ;8U
Adder
8.644
972037AH1-567 GEN1
Adder
0.187
972228AH1-698 GEN2
Adder
3.776
274675JOLIET 29;7U
Adder
31.186
274675JOLIET 29;7U
Adder
30.072
23750701CROSSCHOOL
Solar/Wind Helper
1.507
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.301
24318905MLG2
50/50
7.043
270349AD2-093_GEN
Solar/Wind Harmer
4.444
270471AD2-092_GEN
Solar/Wind Harmer
4.444
253383AE2-342_GEN
Solar/Wind Harmer
1.038
25322209TAIT E
Adder
10.61
25322209TAIT E
Adder
10.372
253370AE2-315 SEC1
Adder
2.175
270246TR4_N_V150
Solar/Wind Harmer
0.91
247621Y3-024
Adder
0.254
316097T157 G90
Solar/Wind Helper
1.512
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.345
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
241955AC1-078 GEN
Solar/Wind Harmer
8.772
241973AD2-163_GEN1
Solar/Wind Harmer
2.316
241974AD2-163_GEN2
Solar/Wind Harmer
2.316
943861AF1-054 GEN
Solar/Wind Harmer
4.469
943851AF1-053 GEN
Solar/Wind Harmer
2.16
270227U2-072_GEN3
Solar/Wind Harmer
2.27
270228U2-072_GEN4
Solar/Wind Harmer
2.27
270231U2-072_GEN5
Solar/Wind Harmer
2.27
253343AC1-166 GEN
Solar/Wind Harmer
1.233
270302AB2-170 GEN
Solar/Wind Harmer
9.503
970179AG2-119 GEN
Solar/Wind Harmer
8.805
253372AE2-315 SEC3
Adder
2.057
253372AE2-315 SEC3
Adder
2.057
25306009OHH W.
Adder
3.121
957201AF2-014 GEN
Solar/Wind Harmer
4.876
253433AC1-085 GEN1
Solar/Wind Harmer
5.693
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
247521TR3_G114
Solar/Wind Harmer
3.595
963791AG1-232 GEN
Solar/Wind Harmer
14.329
274827FISK ;RP
Adder
7.912
274800UNIV PARK;3U
Adder
5.944
274801UNIV PARK;4U
Adder
5.944
972227AH1-698 GEN1
Adder
2.659
274735ELWOOD EC;4P
Adder
16.705
274744AC1-111 GEN8
Adder
5.658
238169AE2-226 GEN1
Solar/Wind Helper
0.707
238170AE2-226 GEN2
Solar/Wind Helper
0.707
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.166
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.068
315651AD1-115 GEN
Solar/Wind Helper
0.793
960071AF2-298 GEN
Solar/Wind Harmer
1.643
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
253317AC1-085 GEN4
Solar/Wind Harmer
8.97
946181AF1-283 GEN
Solar/Wind Harmer
13.928
270588AE1-091_GEN
Solar/Wind Harmer
11.743
24695305TIMB G C
Solar/Wind Harmer
3.563
252519AF1-045_GEN
Solar/Wind Harmer
3.849
252524AE2-267 GEN
Solar/Wind Harmer
1.662
25194608D.CRK4
Adder
1.734
946031AF1-268 GEN
Solar/Wind Harmer
8.698
247643Z2-116 C
Solar/Wind Harmer
0.073
274811UNIV PK N;7U
Adder
5.12
24728505AND G1
Adder
3.912
274676JOLIET 29;8U
Adder
30.072
274734ELWOOD EC;8P
Adder
16.705
274736ELWOOD EC;9P
Adder
16.705
274682WAUKEGAN ;7U
Adder
18.116
964991AG1-363 GEN
Solar/Wind Helper
5.159
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.673
205932AD2-116_GEN
Solar/Wind Helper
0.513
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.87
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.518
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
270485AE1-090_GEN
Solar/Wind Harmer
0.686
972269AH1-719 GEN
Adder
2.576
253398AE2-221_GEN2
Solar/Wind Harmer
4.888
246936BC-WTG1
Solar/Wind Harmer
4.206
270489AE1-102 GEN1
Solar/Wind Harmer
1.398
965011AG1-365 GEN
Solar/Wind Harmer
10.694
958861AF2-177 GEN
Solar/Wind Harmer
11.549
252510AF1-249 C
Solar/Wind Harmer
0.44
945371AF1-202 GEN
Solar/Wind Harmer
7.353
270331AC1-082 GEN3
Solar/Wind Harmer
0.499
270005AE1-210 C O1
Solar/Wind Harmer
5.725
25196808ZIMRHP
Adder
79.46
942081AE2-220 GEN
Solar/Wind Harmer
6.696
270209AC1-174_GEN
Solar/Wind Harmer
4.261
270239V3-007_GEN1
Solar/Wind Harmer
1.802
970825AG2-519 GEN
Solar/Wind Harmer
2.196
25196008MFTGT1
Adder
1.445
274751CRETE EC ;1U
Adder
8.445
274773LINCOLN ;4U
Adder
8.644
274774LINCOLN ;5U
Adder
8.644
274723RIVER EC ;12
Adder
18.35
23583801GRNGAP
Solar/Wind Helper
5.632
238126S14_GEN_1
Solar/Wind Helper
0.83
237085AD2-009_GEN
Solar/Wind Helper
1.662
3141196NOKESVL
Solar/Wind Helper
1.037
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.794
270594AE1-207 GEN
Solar/Wind Harmer
13.328
270032AE2-172
Solar/Wind Harmer
4.564
270459AD2-067 GEN
Solar/Wind Harmer
10.209
940611AE2-048 GEN
Solar/Wind Harmer
25.038
941391AE2-136 GEN
Solar/Wind Harmer
12.974
270435AC2-044 GEN
Solar/Wind Harmer
2.15
270007AE1-245 C
Solar/Wind Harmer
5.766
971567AH1-282 GEN
Solar/Wind Harmer
5.325
24729505KEY G4
Adder
6.892
270071AF1-092 GEN
Solar/Wind Harmer
15.92
958711AF2-162 GEN
Solar/Wind Harmer
1.07
25196408WSDLE3
Adder
9.313
25196308WSDLE2
Adder
9.232
25196208WSDLE1
Adder
9.209
25196708WSDLE6
Adder
9.186
270543AE2-219 C
Solar/Wind Harmer
10.53
25196108MFTGT2
Adder
1.593
25196108MFTGT2
Adder
1.479
274728ELWOOD EC;5P
Adder
16.705
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
209027LOR2_Q27
Solar/Wind Helper
1.033
270051AF1-062 GEN
50/50
11.788
960801AF2-371 GEN
Solar/Wind Harmer
2.937
964871AG1-351 GEN
Solar/Wind Harmer
2.028
270512AE1-227 GEN2
Solar/Wind Harmer
2.305
970879AG2-548 GEN
Solar/Wind Harmer
8.762
970065AG2-057 GEN
Solar/Wind Harmer
0.922
253394AE2-221_GEN
Solar/Wind Harmer
4.888
246938BC-WTG3
Solar/Wind Harmer
4.278
971191AH1-055 GEN
Solar/Wind Harmer
20.024
965021AG1-366 GEN
Solar/Wind Harmer
2.487
270043AE2-236 GEN
Solar/Wind Harmer
5.847
270367AC2-061_GEN
Solar/Wind Harmer
3.358
270044AE2-322 C
Solar/Wind Harmer
1.385
962031AG1-047 GEN
Solar/Wind Harmer
3.179
957741AF2-068 GEN
Solar/Wind Harmer
15.772
270186AC1-089 GEN
Solar/Wind Harmer
6.407
270240V3-007_GEN2
Solar/Wind Harmer
6.478
970825AG2-519 GEN
Solar/Wind Harmer
5.896
25196008MFTGT1
Adder
1.4
274772LINCOLN ;3U
Adder
8.644
274724RIVER EC ;11
Adder
18.136
972259AH1-714 GEN
Adder
19.435
274729ELWOOD EC;1P
Adder
16.705
238175AF1-290_GEN
Solar/Wind Helper
0.158
316415AF1-147_GEN2
Solar/Wind Helper
0.896
237048AF1-022 C
Solar/Wind Helper
0.184
205916AD1-020 GEN
Solar/Wind Helper
1.727
233944AB2-135 GEN
Solar/Wind Helper
0.595
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
23559101PLEAS2
50/50
6.109
970149AG2-104 GEN
Solar/Wind Harmer
25.209
270286AF1-227 GEN2
Solar/Wind Harmer
2.498
270578AF1-285 GEN2
Solar/Wind Harmer
1.39
270510AE1-227 GEN1
Solar/Wind Harmer
2.716
971073AG2-665 GEN
Solar/Wind Harmer
1.274
960001AF2-291 GEN
Solar/Wind Harmer
3.243
270258AD1-119 GEN
Solar/Wind Harmer
2.151
270297AD1-101 GEN
Solar/Wind Harmer
2.142
270222AC2-111 GEN
Solar/Wind Harmer
4.705
970091AG2-072 GEN
Adder
77.346
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.275
233935AB2-179 C
Solar/Wind Helper
1.279
233987AB2-037 GEN
Solar/Wind Helper
2.362
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.758
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.153
23559001PLEAS1
50/50
6.109
961921AG1-034 GEN
Solar/Wind Harmer
15.548
270287AF1-227 GEN3
Solar/Wind Harmer
2.498
942051AE2-217 GEN
Solar/Wind Harmer
20.967
942871AE2-306 GEN
Solar/Wind Harmer
1.043
270391AF1-285 GEN3
Solar/Wind Harmer
0.535
958581AF2-149 GEN
Solar/Wind Harmer
4.723
957541AF2-048 GEN
Solar/Wind Harmer
1.714
958091AF2-103 GEN
Solar/Wind Harmer
0.172
944531AF1-118 GEN
Solar/Wind Harmer
37.241
25196608WSDLE5
Adder
9.047
252507AC2-088 GEN
Solar/Wind Harmer
1.887
270063AE2-323 C
Solar/Wind Harmer
2.313
971347AH1-153 GEN
Solar/Wind Harmer
5.249
270330AC1-082 GEN2
Solar/Wind Harmer
0.498
274752CRETE EC ;2U
Adder
8.445
24728705AND G3
Adder
8.182
274826FISK ;BP
Adder
11.164
274730ELWOOD EC;6P
Adder
16.705
238127S14_GEN_2
Solar/Wind Helper
0.83
238152AF2-075_GEN
Solar/Wind Helper
0.714
23777901MDS_W4-102
Solar/Wind Helper
0.179
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.304
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.581
960971AF2-388 GEN
Solar/Wind Harmer
11.565
25194408D.CRK1
Adder
7.977
970883AG2-550 GEN
Solar/Wind Harmer
10.53
970349AG2-230 GEN
Solar/Wind Harmer
15.746
270599AE1-208 GEN
Solar/Wind Harmer
8.55
926881AC1-175 GEN
Solar/Wind Harmer
5.844
944231AF1-091 GEN
Solar/Wind Harmer
18.838
24728905RICHG2
Adder
3.948
274808UNIV PK N;4U
Adder
5.098
274674JOLIET 9 ;6U
Adder
15.646
274693ROCKY RD ;1P
Adder
11.118
274683WAUKEGAN ;8U
Adder
21.233
274683WAUKEGAN ;8U
Adder
9.373
23585401KL_K28_T16
Solar/Wind Helper
1.485
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.673
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
970155AG2-107 GEN
Solar/Wind Harmer
17.802
971995AH1-542 GEN
Solar/Wind Harmer
12.457
253370AE2-315 SEC1
Adder
2.175
253371AE2-315 SEC2
Adder
2.057
965421AG1-410 GEN
Solar/Wind Harmer
32.239
253316AC1-085 GEN3
Solar/Wind Harmer
8.97
946171AF1-282 GEN
Solar/Wind Harmer
10.714
965651AG1-433 GEN
Solar/Wind Harmer
5.783
252516AE2-318_GEN
Solar/Wind Harmer
10.575
270024AE2-089 GEN
Solar/Wind Harmer
4.946
25194608D.CRK4
Adder
1.734
24639705ELKHART HY
Adder
0.16
274812UNIV PK N;8U
Adder
5.12
24728605AND G2
Adder
3.912
274676JOLIET 29;8U
Adder
31.186
972203AH1-686 GEN
Adder
2.33
274745AC1-111 GEN9
Adder
5.658
274682WAUKEGAN ;7U
Adder
18.116
316095T157 G97
Solar/Wind Helper
1.512
238185AF2-356 C
Solar/Wind Helper
2.664
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.53
23777801MSM_W1-116
Solar/Wind Helper
0.115
23751101LEADS_P59
Solar/Wind Helper
2.095
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
24318805MLG1
50/50
10.069
270475AD2-096_GEN
50/50
7.121
270518AE2-148 GEN
Solar/Wind Harmer
13.799
253325AC1-069 GEN
Solar/Wind Harmer
1.189
971199AH1-059 GEN
Solar/Wind Harmer
2.318
270491AE1-102 GEN2
Solar/Wind Harmer
1.398
270329AC1-082 GEN1
Solar/Wind Harmer
0.498
270004AE1-209 GEN
Solar/Wind Harmer
5.725
24379505HDWTR1G C
Solar/Wind Harmer
8.279
274753CRETE EC ;3U
Adder
8.445
274814UNIV PK N;0U
Adder
5.165
274807UNIV PK N;3U
Adder
5.154
274803UNIV PARK;6U
Adder
5.948
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.006
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.153
961301AF2-421 GEN
Solar/Wind Helper
0.442
963151AG1-164 GEN
Solar/Wind Helper
0.442
961341AF2-425 GEN
Solar/Wind Helper
0.44
24728805RICHG1
Adder
3.948
274695ROCKY RD ;2P
Adder
11.229
235054AD2-180 GEN
Solar/Wind Helper
2.035
235531U2-073 GEN
Solar/Wind Helper
3.323
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.119
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.969
316045AC1-158 PL2
Solar/Wind Helper
4.174
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
972239AH1-704 GEN
Adder
2.68
961821AG1-024 GEN
Solar/Wind Harmer
10.365
945631AF1-228 GEN
Solar/Wind Harmer
5.442
270223U2-072_GEN1
Solar/Wind Harmer
2.27
270578AF1-285 GEN2
Solar/Wind Harmer
0.535
270432AC2-029 GEN
Solar/Wind Harmer
8.017
253338AC1-165 GEN
Solar/Wind Harmer
1.233
270263AC1-001 GEN
Solar/Wind Harmer
1.169
241972AD1-140 GEN
Solar/Wind Harmer
5
270340AC2-060 GEN
Solar/Wind Harmer
3.324
270191TR4_S_V150
Solar/Wind Harmer
3.208
959331AF2-224 GEN
Solar/Wind Harmer
10.694
965041AG1-368 GEN
Solar/Wind Harmer
10.672
966831AG1-554 GEN
Solar/Wind Harmer
1.274
25196508WSDLE4
Adder
8.954
964611AG1-324 GEN
Solar/Wind Harmer
4.098
274776LINCOLN ;7U
Adder
8.644
274687WILL CNTY;4U
Adder
28.416
274687WILL CNTY;4U
Adder
28.416
274731ELWOOD EC;2P
Adder
16.705
274733ELWOOD EC;3P
Adder
16.705
274746AC1-111 G10
Adder
5.658
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.195
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.64
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.513
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.106
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
274771LINCOLN ;2U
Adder
8.644
274805UNIV PK N;1U
Adder
5.131
274696ROCKY RD ;4P
Adder
11.494
274697ROCKY RD ;3P
Adder
3.05
235020AA1-095 C
Solar/Wind Helper
0.053
237061AD1-155 GEN
Solar/Wind Helper
1.768
23751201ROTHROCK
Solar/Wind Helper
0.823
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.896
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.384
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.953
WECLTFEXP_WEC->PJM
CLTF
3.81
LAGNLTFEXP_LAGN->PJM
CLTF
14.758
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.672
CPLELTFEXP_CPLE->PJM
CLTF
0.575
SIGELTFEXP_SIGE->PJM
CLTF
0.503
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.516
NYPJM->LTFIMP_NY
CLTF
4.833
TVALTFEXP_TVA->PJM
CLTF
7.253
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.294
LGEELTFEXP_LGEE->PJM
CLTF
6.723
MECLTFEXP_MEC->PJM
CLTF
15.837
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.83
MW Contribution:
2.68
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.069
972269AH1-719 GEN
Adder
2.573
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.302
270489AE1-102 GEN1
Solar/Wind Harmer
0.974
965011AG1-365 GEN
Solar/Wind Harmer
7.453
958861AF2-177 GEN
Solar/Wind Harmer
3.191
252510AF1-249 C
Solar/Wind Harmer
0.056
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.582
25196808ZIMRHP
Adder
79.365
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
2.589
270594AE1-207 GEN
Solar/Wind Harmer
8.151
270032AE2-172
Solar/Wind Harmer
4.852
945111AF1-176 GEN
Solar/Wind Harmer
12.968
957891AF2-083 GEN
Solar/Wind Harmer
12.11
25196008MFTGT1
Adder
1.443
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.989
274751CRETE EC ;1U
Adder
8.436
274773LINCOLN ;4U
Adder
8.634
274774LINCOLN ;5U
Adder
8.634
274723RIVER EC ;12
Adder
18.33
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.68
970569AG2-363 GEN
Solar/Wind Harmer
20.915
939741AE1-205 GEN
Solar/Wind Harmer
9.761
23583801GRNGAP
Solar/Wind Helper
5.626
238126S14_GEN_1
Solar/Wind Helper
0.831
237085AD2-009_GEN
Solar/Wind Helper
1.661
3141196NOKESVL
Solar/Wind Helper
1.036
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.234
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.139
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.792
942861AE2-305 GEN
Solar/Wind Harmer
6.31
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.113
970329AG2-216 GEN
Solar/Wind Harmer
3.341
971073AG2-665 GEN
Solar/Wind Harmer
5.597
25326109MON D
Adder
1.437
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.492
25194508D.CRK3
Adder
1.49
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970885AG2-551 GEN
Solar/Wind Harmer
2.446
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.549
270031AE2-169
Solar/Wind Harmer
4.021
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.481
24728805RICHG1
Adder
3.944
24699105WLD G1 C
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
6.638
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
10.234
274695ROCKY RD ;2P
Adder
11.216
958491AF2-143 GEN
Solar/Wind Harmer
10.536
276872AE1-163_GEN1
Solar/Wind Harmer
0
235054AD2-180 GEN
Solar/Wind Helper
2.04
235531U2-073 GEN
Solar/Wind Helper
3.327
238149AF1-291A_GEN
Solar/Wind Helper
0.143
316006AB2-029 C
Solar/Wind Helper
0.118
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.968
316045AC1-158 PL2
Solar/Wind Helper
4.17
219912AD2-042 GEN
Solar/Wind Helper
0.151
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.132
20674328GAR_V4-001
Solar/Wind Helper
0.023
270119AB2-067 GEN1
50/50
7.069
25326509SID D
Adder
1.446
970879AG2-548 GEN
Solar/Wind Harmer
1.272
246937BC-WTG2
Solar/Wind Harmer
0.302
247607V1-011 GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970623AG2-406 GEN
Solar/Wind Harmer
1.351
942221AE2-234 GEN
Solar/Wind Harmer
2.958
970621AG2-405 GEN
Solar/Wind Harmer
1.345
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.634
274771LINCOLN ;2U
Adder
8.634
24387305FR-4G C
Solar/Wind Harmer
0
274805UNIV PK N;1U
Adder
5.126
274888KELLY CRK;1U
Solar/Wind Harmer
0.414
970941AG2-585 GEN
Solar/Wind Harmer
3.909
276897AD1-100 C
Solar/Wind Harmer
17.749
276893AG1-478 C
Solar/Wind Harmer
0.472
970241AG2-163 GEN
Solar/Wind Harmer
4.124
274696ROCKY RD ;4P
Adder
11.481
274697ROCKY RD ;3P
Adder
3.047
962691AG1-118 GEN
Solar/Wind Harmer
21.036
942111AE2-223 GEN
Solar/Wind Harmer
2.266
235020AA1-095 C
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.828
237061AD1-155 GEN
Solar/Wind Helper
1.767
238221AF1-254 C O1
Solar/Wind Helper
0.277
316411AF1-147_GEN1
Solar/Wind Helper
0.895
223402AF1-300 C
Solar/Wind Helper
0.37
233982AB2-133 GEN
Solar/Wind Helper
0.362
233930AB2-032 GEN
Solar/Wind Helper
0.383
233946AB2-136 GEN
Solar/Wind Helper
0.573
232410W1-006 C
Solar/Wind Helper
0.511
233952AC2-187 GEN
Solar/Wind Helper
0.234
233954AC2-188 GEN
Solar/Wind Helper
0.234
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
270120AB2-067 GEN2
50/50
7.069
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.867
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.048
960971AF2-388 GEN
Solar/Wind Harmer
4.326
25194408D.CRK1
Adder
7.968
970883AG2-550 GEN
Solar/Wind Harmer
7.338
970349AG2-230 GEN
Solar/Wind Harmer
10.973
270599AE1-208 GEN
Solar/Wind Harmer
6.701
926881AC1-175 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
16.825
24728905RICHG2
Adder
3.944
961051AF2-396 GEN
Solar/Wind Harmer
14.52
961051AF2-396 GEN
Solar/Wind Harmer
9.68
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.807
274808UNIV PK N;4U
Adder
5.092
274674JOLIET 9 ;6U
Adder
15.628
958481AF2-142 GEN
Solar/Wind Harmer
10.569
274693ROCKY RD ;1P
Adder
11.106
274683WAUKEGAN ;8U
Adder
21.209
274683WAUKEGAN ;8U
Adder
9.636
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.415
23585401KL_K28_T16
Solar/Wind Helper
1.489
238117U2-030
Solar/Wind Helper
0.343
238148AE2-230_GEN2
Solar/Wind Helper
0.499
235062AE1-101 C1
Solar/Wind Helper
1.672
237006AB1-125 GEN
Solar/Wind Helper
0.124
223401AF1-299 GEN
Solar/Wind Helper
0.37
232424Y1-079 C
Solar/Wind Helper
0.117
232428Y3-058 C
Solar/Wind Helper
0.341
234015AF2-250 C
Solar/Wind Helper
0.038
316450AC1-158 RIC
Solar/Wind Helper
0.348
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.292
20675428EAM_W2-061
Solar/Wind Helper
0.016
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.559
270377AD1-106 GEN
Solar/Wind Harmer
2.842
965051AG1-369 GEN
Solar/Wind Harmer
3.723
971985AH1-537 GEN
Solar/Wind Harmer
2.196
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
11.014
970031AG2-029 GEN
Solar/Wind Harmer
3.977
247536S-71 GEN
Solar/Wind Harmer
0.293
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.281
274775LINCOLN ;6U
Adder
8.634
274777LINCOLN ;8U
Adder
8.634
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.186
960591AF2-350 GEN
Solar/Wind Harmer
7.107
972228AH1-698 GEN2
Adder
3.772
972165AH1-665 GEN
Solar/Wind Harmer
6.324
274675JOLIET 29;7U
Adder
31.151
274675JOLIET 29;7U
Adder
30.039
970833AG2-524 GEN
Solar/Wind Harmer
7.786
970833AG2-524 GEN
Solar/Wind Harmer
5.191
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.723
971411AH1-196 GEN
Solar/Wind Harmer
10.47
23750701CROSSCHOOL
Solar/Wind Helper
1.509
205943AE1-185 GEN
Solar/Wind Helper
0.513
233915AB1-141 GEN
Solar/Wind Helper
0.506
228728W1-130C
Solar/Wind Helper
0.054
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
212266LOR1
Solar/Wind Helper
0.3
203955AF1-039 C O1
Solar/Wind Helper
0.33
971171AH1-044 GEN
Solar/Wind Harmer
9.057
970155AG2-107 GEN
Solar/Wind Harmer
21.963
971995AH1-542 GEN
Solar/Wind Harmer
2.894
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
965421AG1-410 GEN
Solar/Wind Harmer
22.47
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.466
965651AG1-433 GEN
Solar/Wind Harmer
2.163
252516AE2-318_GEN
Solar/Wind Harmer
8.253
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.732
970613AG2-401 GEN
Solar/Wind Harmer
5.351
24639705ELKHART HY
Adder
0.16
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.114
24728605AND G2
Adder
3.908
945681AF1-233 GEN
Solar/Wind Harmer
13.398
274676JOLIET 29;8U
Adder
31.151
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
5.652
972203AH1-686 GEN
Adder
2.327
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
18.096
316095T157 G97
Solar/Wind Helper
1.51
238185AF2-356 C
Solar/Wind Helper
2.669
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238120AE2-309 GEN
Solar/Wind Helper
0.531
23751101LEADS_P59
Solar/Wind Helper
2.119
23777801MSM_W1-116
Solar/Wind Helper
0.115
227287AC2-120 GEN
Solar/Wind Helper
0.349
232422X3-066 FULL
Solar/Wind Helper
0.115
233964AF2-378 GEN
Solar/Wind Helper
0.042
232406W1-004 FULL
Solar/Wind Helper
0.511
232434Z2-077 GEN
Solar/Wind Helper
0.128
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.499
957471AF2-041 GEN
Solar/Wind Harmer
13.586
962771AG1-126 GEN
Solar/Wind Harmer
34.394
970153AG2-106 GEN
Solar/Wind Harmer
21.963
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
23.821
253370AE2-315 SEC1
Adder
2.172
253371AE2-315 SEC2
Adder
2.055
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.706
270588AE1-091_GEN
Solar/Wind Harmer
5.82
24695305TIMB G C
Solar/Wind Harmer
0.63
252519AF1-045_GEN
Solar/Wind Harmer
3.844
25194608D.CRK4
Adder
1.732
946031AF1-268 GEN
Solar/Wind Harmer
6.95
970289AG2-191 GEN
Solar/Wind Harmer
0.8
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
5.114
24728505AND G1
Adder
3.908
276806AD2-047 C O1
Solar/Wind Harmer
4.027
274676JOLIET 29;8U
Adder
30.039
274734ELWOOD EC;8P
Adder
16.687
274736ELWOOD EC;9P
Adder
16.687
943121AE2-341 GEN
Solar/Wind Harmer
11.83
943591AF1-030 GEN
Solar/Wind Harmer
7.867
274682WAUKEGAN ;7U
Adder
18.096
964991AG1-363 GEN
Solar/Wind Helper
5.155
238110AE1-109 GEN3
Solar/Wind Helper
0.114
235063AE1-101 C2
Solar/Wind Helper
1.672
205932AD2-116_GEN
Solar/Wind Helper
0.512
232426Y1-080 FULL
Solar/Wind Helper
0.039
233996TM1833_GEN
Solar/Wind Helper
0.207
316447AC1-158 HLD
Solar/Wind Helper
2.868
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.516
20714528FRN_Y2-051
Solar/Wind Helper
0.057
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
959091AF2-200 GEN
Solar/Wind Harmer
9.057
972239AH1-704 GEN
Adder
2.678
961821AG1-024 GEN
Solar/Wind Harmer
5.057
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.534
270432AC2-029 GEN
Solar/Wind Harmer
3.538
270263AC1-001 GEN
Solar/Wind Harmer
0.78
241972AD1-140 GEN
Solar/Wind Harmer
0.849
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.217
965041AG1-368 GEN
Solar/Wind Harmer
7.438
25196508WSDLE4
Adder
8.944
964611AG1-324 GEN
Solar/Wind Harmer
2.856
971609AH1-304 GEN
Solar/Wind Harmer
1.194
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.634
963841AG1-237 GEN
Solar/Wind Harmer
3.075
972163AH1-664 GEN
Solar/Wind Harmer
7.896
274687WILL CNTY;4U
Adder
28.385
274687WILL CNTY;4U
Adder
28.385
274731ELWOOD EC;2P
Adder
16.687
274733ELWOOD EC;3P
Adder
16.687
274746AC1-111 G10
Adder
5.652
926823AC1-168 GEN
Solar/Wind Harmer
1.186
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.343
23779801AA1-109
Solar/Wind Helper
0.194
3138216PACIFIC
Solar/Wind Helper
0.045
23750501ELLIOTTS
Solar/Wind Helper
0.642
226929AD2-058 GEN
Solar/Wind Helper
0.1
205917AD1-020 ES
Solar/Wind Helper
0.371
205956AE1-196_GEN
Solar/Wind Helper
0.512
233901CHERRYDALE C
Solar/Wind Helper
0.234
20715028HAN_X4-015
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
20720628TIN_W1-124
Solar/Wind Helper
0.191
316164AC1-076 GEN
Solar/Wind Helper
1.105
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
270051AF1-062 GEN
50/50
11.777
270512AE1-227 GEN2
Solar/Wind Harmer
1.954
970879AG2-548 GEN
Solar/Wind Harmer
5.597
970065AG2-057 GEN
Solar/Wind Harmer
0.757
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.27
971191AH1-055 GEN
Solar/Wind Harmer
19.175
965021AG1-366 GEN
Solar/Wind Harmer
2.484
270043AE2-236 GEN
Solar/Wind Harmer
4.754
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.991
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.494
945111AF1-176 GEN
Solar/Wind Harmer
5.891
270505AE1-170 C O1
Solar/Wind Harmer
7.629
25196008MFTGT1
Adder
1.398
274772LINCOLN ;3U
Adder
8.634
274724RIVER EC ;11
Adder
18.116
972167AH1-666 GEN
Solar/Wind Harmer
5.69
972259AH1-714 GEN
Adder
19.413
274729ELWOOD EC;1P
Adder
16.687
946671AF1-331 GEN
Solar/Wind Harmer
0.745
274850MENDOTA H;RU
Solar/Wind Harmer
0.081
970571AG2-364 GEN
Solar/Wind Harmer
13.944
238175AF1-290_GEN
Solar/Wind Helper
0.158
237048AF1-022 C
Solar/Wind Helper
0.184
316415AF1-147_GEN2
Solar/Wind Helper
0.895
205916AD1-020 GEN
Solar/Wind Helper
1.725
233944AB2-135 GEN
Solar/Wind Helper
0.594
232408W1-005 C
Solar/Wind Helper
0.511
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.085
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
23559001PLEAS1
50/50
6.097
961921AG1-034 GEN
Solar/Wind Harmer
7.586
942051AE2-217 GEN
Solar/Wind Harmer
14.613
270391AF1-285 GEN3
Solar/Wind Harmer
0.534
944531AF1-118 GEN
Solar/Wind Harmer
33.233
25196608WSDLE5
Adder
9.036
252507AC2-088 GEN
Solar/Wind Harmer
0.33
270063AE2-323 C
Solar/Wind Harmer
0
971347AH1-153 GEN
Solar/Wind Harmer
3.658
970781AG2-491 GEN
Solar/Wind Harmer
7.162
958171AF2-111 GEN
Solar/Wind Harmer
17.857
274752CRETE EC ;2U
Adder
8.436
24728705AND G3
Adder
8.173
274887GEN-1.85
Solar/Wind Harmer
0.185
274826FISK ;BP
Adder
11.151
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
23.191
274730ELWOOD EC;6P
Adder
16.687
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.951
276868AE1-113 GEN
Solar/Wind Harmer
1.403
274879MINONK ;1U
Solar/Wind Harmer
0.293
274855GSG-6 ;RU
Solar/Wind Harmer
0.255
970193AG2-126 GEN
Solar/Wind Harmer
10.468
238127S14_GEN_2
Solar/Wind Helper
0.831
238152AF2-075_GEN
Solar/Wind Helper
0.713
23777901MDS_W4-102
Solar/Wind Helper
0.178
208835TUHI V3-051
Solar/Wind Helper
0.022
233998TM1NIN_3.36
Solar/Wind Helper
0.207
232404W1-003 C
Solar/Wind Helper
0.511
316044AC1-158 PL1
Solar/Wind Helper
1.303
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.064
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.58
202652Y1-033 WT C
Solar/Wind Helper
0.5
23559101PLEAS2
50/50
6.097
970149AG2-104 GEN
Solar/Wind Harmer
18.573
270510AE1-227 GEN1
Solar/Wind Harmer
1.954
971073AG2-665 GEN
Solar/Wind Harmer
1.272
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.787
970773AG2-487 GEN
Solar/Wind Harmer
1.277
970373AG2-245 GEN
Solar/Wind Harmer
15.17
971917AH1-482 GEN
Solar/Wind Harmer
9.365
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.733
276691AA1-018 GEN1
Solar/Wind Harmer
1.145
274861TOP CROP ;1U
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
77.252
276882AE2-255 GEN
Solar/Wind Harmer
0.818
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.09
237038AE2-054 C
Solar/Wind Helper
0.274
233935AB2-179 C
Solar/Wind Helper
1.278
233987AB2-037 GEN
Solar/Wind Helper
2.36
232417X3-008 C
Solar/Wind Helper
0.234
233923SMA
Solar/Wind Helper
0.757
233997TMININ_4.2
Solar/Wind Helper
0.207
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.152
959081AF2-199 GEN
Solar/Wind Harmer
4.529
971067AG2-660 GEN
Solar/Wind Harmer
1.51
962761AG1-125 GEN
Solar/Wind Harmer
34.394
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.807
25326309TAIT D
Adder
1.191
241813AF1-122_GEN
Solar/Wind Harmer
3.39
971201AH1-060 GEN
Solar/Wind Harmer
1.514
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
8.095
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.436
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.941
274732ELWOOD EC;7P
Adder
16.687
274674JOLIET 9 ;6U
Adder
15.628
939401AE1-172 GEN
Solar/Wind Harmer
5.275
962781AG1-127 GEN
Solar/Wind Harmer
6.668
235067AD1-061 GEN
Solar/Wind Helper
0.449
237002AB1-128_GEN
Solar/Wind Helper
0.446
208835TUHI V3-051
Solar/Wind Helper
0.022
233950AC2-186 GEN
Solar/Wind Helper
0.117
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.116
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.312
217169METRODIV C
Solar/Wind Helper
0.004
963161AG1-165 GEN
Solar/Wind Helper
0.441
24318905MLG2
50/50
7.039
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.843
25322209TAIT E
Adder
10.598
25322209TAIT E
Adder
10.36
253370AE2-315 SEC1
Adder
2.172
270246TR4_N_V150
Solar/Wind Harmer
0.048
247621Y3-024
Adder
0.253
971613AH1-306 GEN
Solar/Wind Harmer
3.493
970291AG2-192 GEN
Solar/Wind Harmer
0.945
970291AG2-192 GEN
Solar/Wind Harmer
0.436
965681AG1-436 GEN
Solar/Wind Harmer
9.052
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.758
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.51
238147AE2-230_GEN1
Solar/Wind Helper
0.499
237080AD1-060 GEN
Solar/Wind Helper
0.344
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
971341AH1-150 GEN
Solar/Wind Harmer
9.057
971343AH1-151 GEN
Solar/Wind Harmer
9.057
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.115
943851AF1-053 GEN
Solar/Wind Harmer
2.157
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.113
970179AG2-119 GEN
Solar/Wind Harmer
6.854
253372AE2-315 SEC3
Adder
2.055
253372AE2-315 SEC3
Adder
2.055
25306009OHH W.
Adder
3.117
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.27
963791AG1-232 GEN
Solar/Wind Harmer
9.987
970289AG2-191 GEN
Solar/Wind Harmer
1.382
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.903
274800UNIV PARK;3U
Adder
5.937
274801UNIV PARK;4U
Adder
5.937
972227AH1-698 GEN1
Adder
2.656
274735ELWOOD EC;4P
Adder
16.687
274744AC1-111 GEN8
Adder
5.652
970169AG2-114 GEN
Solar/Wind Harmer
7.011
959341AF2-225 GEN
Solar/Wind Harmer
7.32
238169AE2-226 GEN1
Solar/Wind Helper
0.706
238170AE2-226 GEN2
Solar/Wind Helper
0.706
237030AB1-096 C
Solar/Wind Helper
0.067
237025AB1-124 C
Solar/Wind Helper
0.165
959381AF2-229 GEN
Solar/Wind Helper
0.359
232432Z2-076 GEN
Solar/Wind Helper
0.067
315651AD1-115 GEN
Solar/Wind Helper
0.793
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.057
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.085
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
19.52
941391AE2-136 GEN
Solar/Wind Harmer
10.996
270435AC2-044 GEN
Solar/Wind Harmer
0.949
270007AE1-245 C
Solar/Wind Harmer
0
971567AH1-282 GEN
Solar/Wind Harmer
5.69
24729505KEY G4
Adder
6.885
270071AF1-092 GEN
Solar/Wind Harmer
14.177
25196408WSDLE3
Adder
9.302
25196308WSDLE2
Adder
9.221
25196208WSDLE1
Adder
9.198
25196708WSDLE6
Adder
9.175
270543AE2-219 C
Solar/Wind Harmer
5.137
971771AH1-392 GEN
Solar/Wind Harmer
7.271
25196108MFTGT2
Adder
1.591
25196108MFTGT2
Adder
1.478
971549AH1-272 GEN
Solar/Wind Harmer
14.794
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.687
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.341
276861AD2-134 GEN
Solar/Wind Harmer
0.124
276863AD2-134 GEN
Solar/Wind Harmer
0.124
20390526W1-045 C
Solar/Wind Helper
0.353
3141426STAFORD
Solar/Wind Helper
0.053
233940AF2-379 C
Solar/Wind Helper
0.062
230434AG1-499 GEN
Solar/Wind Helper
0.232
219258KINSLEYDEP C
Solar/Wind Helper
0.077
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.096
209027LOR2_Q27
Solar/Wind Helper
1.031
24318805MLG1
50/50
10.065
270475AD2-096_GEN
50/50
7.114
270518AE2-148 GEN
Solar/Wind Harmer
0.653
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.615
970191AG2-125 GEN
Solar/Wind Harmer
1.937
270491AE1-102 GEN2
Solar/Wind Harmer
0.974
270004AE1-209 GEN
Solar/Wind Harmer
1.582
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.436
24386205FR-12G C
Solar/Wind Harmer
0
274814UNIV PK N;0U
Adder
5.159
274807UNIV PK N;3U
Adder
5.148
274803UNIV PARK;6U
Adder
5.941
276843GEN-1.7
Solar/Wind Harmer
0.23
972038AH1-567 GEN2
Adder
0.372
238108AE1-109 GEN1
Solar/Wind Helper
0.114
23562501BACKB
Solar/Wind Helper
1.012
237001AB1-127_GEN
Solar/Wind Helper
0.445
233918AB1-142 GEN
Solar/Wind Helper
0.506
228729W2-030 C
Solar/Wind Helper
0.111
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.115
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.067
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.152
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
CBM West 1LTFEXP_CBM-W1->PJM
CBM
142.362
NYPJM->LTFIMP_NY
CLTF
4.827
TVALTFEXP_TVA->PJM
CLTF
7.243
AG2-052LTFEXP_AG2-052->PJM
LTF
0.238
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.151
LGEELTFEXP_LGEE->PJM
CLTF
6.715
MECLTFEXP_MEC->PJM
CLTF
15.818
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.914
WECLTFEXP_WEC->PJM
CLTF
3.806
LAGNLTFEXP_LAGN->PJM
CLTF
14.738
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.655
CPLELTFEXP_CPLE->PJM
CLTF
0.571
SIGELTFEXP_SIGE->PJM
CLTF
0.502

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5005.84
MW Contribution:
3.1
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
241955AC1-078 GEN
Solar/Wind Harmer
8.918
241973AD2-163_GEN1
Solar/Wind Harmer
2.358
241974AD2-163_GEN2
Solar/Wind Harmer
2.358
270227U2-072_GEN3
Solar/Wind Harmer
2.33
270228U2-072_GEN4
Solar/Wind Harmer
2.33
270231U2-072_GEN5
Solar/Wind Harmer
2.33
943861AF1-054 GEN
Solar/Wind Harmer
4.542
943851AF1-053 GEN
Solar/Wind Harmer
2.195
270302AB2-170 GEN
Solar/Wind Harmer
9.776
970179AG2-119 GEN
Solar/Wind Harmer
9.237
253343AC1-166 GEN
Solar/Wind Harmer
1.249
957201AF2-014 GEN
Solar/Wind Harmer
5.019
253372AE2-315 SEC3
Adder
2.081
253372AE2-315 SEC3
Adder
2.081
247521TR3_G114
Solar/Wind Harmer
3.687
25306009OHH W.
Adder
3.158
963791AG1-232 GEN
Solar/Wind Harmer
14.614
253433AC1-085 GEN1
Solar/Wind Harmer
5.738
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
944161AF1-084 GEN
Solar/Wind Harmer
2.352
274827FISK ;RP
Adder
8.022
274800UNIV PARK;3U
Adder
6.026
274801UNIV PARK;4U
Adder
6.026
972227AH1-698 GEN1
Adder
2.695
274735ELWOOD EC;4P
Adder
16.929
238169AE2-226 GEN1
Solar/Wind Helper
0.777
238170AE2-226 GEN2
Solar/Wind Helper
0.777
237030AB1-096 C
Solar/Wind Helper
0.071
237025AB1-124 C
Solar/Wind Helper
0.176
315651AD1-115 GEN
Solar/Wind Helper
0.883
959381AF2-229 GEN
Solar/Wind Helper
0.368
232432Z2-076 GEN
Solar/Wind Helper
0.068
230407AD2-065 C
Solar/Wind Helper
0.041
20720728JCB_W1-129
Solar/Wind Helper
0.058
964851AG1-348 GEN
Solar/Wind Helper
0.063
207408W3-077 C
Solar/Wind Helper
0.084
962771AG1-126 GEN
Solar/Wind Harmer
40.867
970153AG2-106 GEN
Solar/Wind Harmer
17.82
270284AF1-227 GEN1
Solar/Wind Harmer
6.884
24721905FLATG4
Adder
23.444
276820AF1-078_GEN
Solar/Wind Harmer
1.81
270588AE1-091_GEN
Solar/Wind Harmer
12.281
960071AF2-298 GEN
Solar/Wind Harmer
1.664
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
24695305TIMB G C
Solar/Wind Harmer
3.661
253317AC1-085 GEN4
Solar/Wind Harmer
9.041
946181AF1-283 GEN
Solar/Wind Harmer
14.038
247643Z2-116 C
Solar/Wind Harmer
0.074
252519AF1-045_GEN
Solar/Wind Harmer
3.876
252524AE2-267 GEN
Solar/Wind Harmer
1.675
25194608D.CRK4
Adder
1.747
23906502RICHG2&3
Adder
1.268
23906402RICHG1
Adder
1.268
274811UNIV PK N;7U
Adder
5.194
274676JOLIET 29;8U
Adder
30.477
274734ELWOOD EC;8P
Adder
16.929
274736ELWOOD EC;9P
Adder
16.929
964991AG1-363 GEN
Solar/Wind Helper
5.569
238110AE1-109 GEN3
Solar/Wind Helper
0.122
235063AE1-101 C2
Solar/Wind Helper
1.786
316447AC1-158 HLD
Solar/Wind Helper
3.193
205932AD2-116_GEN
Solar/Wind Helper
0.521
232426Y1-080 FULL
Solar/Wind Helper
0.04
233996TM1833_GEN
Solar/Wind Helper
0.21
316192AB2-158 GEN
Solar/Wind Helper
1.618
219766PARADISE C
Solar/Wind Helper
0.055
203975AE1-071-GEN
Solar/Wind Helper
2.543
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219680HOPEWELLV C1
Solar/Wind Helper
0.003
218440SUMMTASSOC C
Solar/Wind Helper
0.017
217208PARK ELE C
Solar/Wind Helper
0.004
20674628WNG_W3-110
Solar/Wind Helper
0.09
270459AD2-067 GEN
Solar/Wind Harmer
10.428
940611AE2-048 GEN
Solar/Wind Harmer
26.008
941391AE2-136 GEN
Solar/Wind Harmer
13.477
971567AH1-282 GEN
Solar/Wind Harmer
5.635
270435AC2-044 GEN
Solar/Wind Harmer
2.213
270007AE1-245 C
Solar/Wind Harmer
5.939
270071AF1-092 GEN
Solar/Wind Harmer
16.191
24729505KEY G4
Adder
6.997
958711AF2-162 GEN
Solar/Wind Harmer
1.086
270543AE2-219 C
Solar/Wind Harmer
10.668
971771AH1-392 GEN
Solar/Wind Harmer
9.58
25196408WSDLE3
Adder
9.385
25196308WSDLE2
Adder
9.303
25196208WSDLE1
Adder
9.28
25196708WSDLE6
Adder
9.256
25196108MFTGT2
Adder
1.604
25196108MFTGT2
Adder
1.489
274728ELWOOD EC;5P
Adder
16.929
3141426STAFORD
Solar/Wind Helper
0.058
20390526W1-045 C
Solar/Wind Helper
0.361
233940AF2-379 C
Solar/Wind Helper
0.063
230434AG1-499 GEN
Solar/Wind Helper
0.234
219258KINSLEYDEP C
Solar/Wind Helper
0.078
20673828FLE_V3-070
Solar/Wind Helper
0.087
20676128MHD_W3-029
Solar/Wind Helper
0.097
270051AF1-062 GEN
50/50
11.971
960801AF2-371 GEN
Solar/Wind Harmer
2.983
964871AG1-351 GEN
Solar/Wind Harmer
2.06
270512AE1-227 GEN2
Solar/Wind Harmer
2.449
970065AG2-057 GEN
Solar/Wind Harmer
0.972
246938BC-WTG3
Solar/Wind Harmer
4.404
970879AG2-548 GEN
Solar/Wind Harmer
8.835
965021AG1-366 GEN
Solar/Wind Harmer
2.544
270044AE2-322 C
Solar/Wind Harmer
1.431
253394AE2-221_GEN
Solar/Wind Harmer
4.932
270043AE2-236 GEN
Solar/Wind Harmer
5.961
971191AH1-055 GEN
Solar/Wind Harmer
20.005
962031AG1-047 GEN
Solar/Wind Harmer
3.224
957741AF2-068 GEN
Solar/Wind Harmer
15.993
945111AF1-176 GEN
Solar/Wind Harmer
6.028
270505AE1-170 C O1
Solar/Wind Harmer
15.984
270367AC2-061_GEN
Solar/Wind Harmer
3.375
25196008MFTGT1
Adder
1.409
274724RIVER EC ;11
Adder
18.401
274772LINCOLN ;3U
Adder
8.764
972259AH1-714 GEN
Adder
19.698
274729ELWOOD EC;1P
Adder
16.929
238175AF1-290_GEN
Solar/Wind Helper
0.173
316415AF1-147_GEN2
Solar/Wind Helper
0.984
237048AF1-022 C
Solar/Wind Helper
0.18
205916AD1-020 GEN
Solar/Wind Helper
1.77
233944AB2-135 GEN
Solar/Wind Helper
0.603
232408W1-005 C
Solar/Wind Helper
0.518
219907AC1-030 C
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.019
219908AB1-139 C
Solar/Wind Helper
0.074
218428ETC SOLAR C
Solar/Wind Helper
0.005
20673628F1S_V4-069
Solar/Wind Helper
0.03
207484AF2-139 C O1
Solar/Wind Helper
0.084
20676228FRD_X1-012
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.082
20675828AU_W4-064
Solar/Wind Helper
0.03
270166AC1-044 GEN3
50/50
7.05
972269AH1-719 GEN
Adder
2.693
270485AE1-090_GEN
Solar/Wind Harmer
0.706
246936BC-WTG1
Solar/Wind Harmer
4.329
270489AE1-102 GEN1
Solar/Wind Harmer
1.439
965011AG1-365 GEN
Solar/Wind Harmer
10.939
253398AE2-221_GEN2
Solar/Wind Harmer
4.932
958861AF2-177 GEN
Solar/Wind Harmer
11.712
945371AF1-202 GEN
Solar/Wind Harmer
7.453
945111AF1-176 GEN
Solar/Wind Harmer
19.021
957891AF2-083 GEN
Solar/Wind Harmer
15.982
24441205WTRV SLR C
Solar/Wind Harmer
0.143
252510AF1-249 C
Solar/Wind Harmer
0.443
25196808ZIMRHP
Adder
79.955
25196008MFTGT1
Adder
1.455
274751CRETE EC ;1U
Adder
8.571
274723RIVER EC ;12
Adder
18.619
270224U2-072_GEN2
Solar/Wind Harmer
2.33
270377AD1-106 GEN
Solar/Wind Harmer
5.917
270291AC1-194 GEN
Solar/Wind Harmer
5.669
965051AG1-369 GEN
Solar/Wind Harmer
5.479
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.18
945641AF1-229 GEN
Solar/Wind Harmer
3.912
970031AG2-029 GEN
Solar/Wind Harmer
26.913
945581AF1-223 GEN
Solar/Wind Harmer
4.845
971029AG2-637 GEN
Solar/Wind Harmer
16.005
247536S-71 GEN
Solar/Wind Harmer
4.316
961761AG1-017 GEN
Solar/Wind Harmer
0.456
274775LINCOLN ;6U
Adder
8.764
274777LINCOLN ;8U
Adder
8.764
972037AH1-567 GEN1
Adder
0.189
972228AH1-698 GEN2
Adder
3.828
274675JOLIET 29;7U
Adder
31.606
274675JOLIET 29;7U
Adder
30.477
23750701CROSSCHOOL
Solar/Wind Helper
1.591
205943AE1-185 GEN
Solar/Wind Helper
0.521
233915AB1-141 GEN
Solar/Wind Helper
0.514
228728W1-130C
Solar/Wind Helper
0.055
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.027
219620RIDERU C
Solar/Wind Helper
0.001
218526CNTRALGAS2 C
Solar/Wind Helper
0.162
972239AH1-704 GEN
50/50
3.095
961821AG1-024 GEN
Solar/Wind Harmer
10.588
270223U2-072_GEN1
Solar/Wind Harmer
2.33
270578AF1-285 GEN2
Solar/Wind Harmer
0.549
945631AF1-228 GEN
Solar/Wind Harmer
5.525
270432AC2-029 GEN
Solar/Wind Harmer
8.117
253338AC1-165 GEN
Solar/Wind Harmer
1.249
241972AD1-140 GEN
Solar/Wind Harmer
5.07
270263AC1-001 GEN
Solar/Wind Harmer
1.18
966831AG1-554 GEN
Solar/Wind Harmer
1.337
270340AC2-060 GEN
Solar/Wind Harmer
3.354
270191TR4_S_V150
Solar/Wind Harmer
3.29
965041AG1-368 GEN
Solar/Wind Harmer
10.944
959331AF2-224 GEN
Solar/Wind Harmer
10.939
270499AE1-146 GEN
Solar/Wind Harmer
2.679
964611AG1-324 GEN
Solar/Wind Harmer
4.154
25196508WSDLE4
Adder
9.023
274776LINCOLN ;7U
Adder
8.764
274687WILL CNTY;4U
Adder
28.802
274687WILL CNTY;4U
Adder
28.802
274731ELWOOD EC;2P
Adder
16.929
274733ELWOOD EC;3P
Adder
16.929
238118U2-030_1
Solar/Wind Helper
0.357
3138216PACIFIC
Solar/Wind Helper
0.049
23779801AA1-109
Solar/Wind Helper
0.208
226929AD2-058 GEN
Solar/Wind Helper
0.108
316164AC1-076 GEN
Solar/Wind Helper
1.232
23750501ELLIOTTS
Solar/Wind Helper
0.631
205917AD1-020 ES
Solar/Wind Helper
0.381
205956AE1-196_GEN
Solar/Wind Helper
0.521
233901CHERRYDALE C
Solar/Wind Helper
0.238
20715028HAN_X4-015
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
20720628TIN_W1-124
Solar/Wind Helper
0.192
20675528CPH_W2-050
Solar/Wind Helper
0.114
20676428JCR_X2-075
Solar/Wind Helper
0.068
20675128HRM_W1-127
Solar/Wind Helper
0.03
970155AG2-107 GEN
Solar/Wind Harmer
17.82
971995AH1-542 GEN
Solar/Wind Harmer
12.942
965421AG1-410 GEN
Solar/Wind Harmer
33.164
253370AE2-315 SEC1
Adder
2.2
253371AE2-315 SEC2
Adder
2.081
253316AC1-085 GEN3
Solar/Wind Harmer
9.041
946171AF1-282 GEN
Solar/Wind Harmer
10.799
965651AG1-433 GEN
Solar/Wind Harmer
5.866
270024AE2-089 GEN
Solar/Wind Harmer
5.027
24639705ELKHART HY
Adder
0.164
252516AE2-318_GEN
Solar/Wind Harmer
10.65
270449AD2-020 GEN
Solar/Wind Harmer
2.984
25194608D.CRK4
Adder
1.747
23906502RICHG2&3
Adder
1.268
274812UNIV PK N;8U
Adder
5.194
274676JOLIET 29;8U
Adder
31.606
316095T157 G97
Solar/Wind Helper
1.71
238109AE1-109 GEN2
Solar/Wind Helper
0.122
238185AF2-356 C
Solar/Wind Helper
2.787
238120AE2-309 GEN
Solar/Wind Helper
0.557
23777801MSM_W1-116
Solar/Wind Helper
0.123
227287AC2-120 GEN
Solar/Wind Helper
0.377
23751101LEADS_P59
Solar/Wind Helper
1.984
232422X3-066 FULL
Solar/Wind Helper
0.117
233964AF2-378 GEN
Solar/Wind Helper
0.043
232406W1-004 FULL
Solar/Wind Helper
0.518
232434Z2-077 GEN
Solar/Wind Helper
0.13
230415AB2-049 C
Solar/Wind Helper
0.031
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
966881AG1-559 GEN
Solar/Wind Helper
0.313
205941AD2-115 GEN
Solar/Wind Helper
0.499
274773LINCOLN ;4U
Adder
8.764
274774LINCOLN ;5U
Adder
8.764
23583801GRNGAP
Solar/Wind Helper
6.383
238126S14_GEN_1
Solar/Wind Helper
0.87
237085AD2-009_GEN
Solar/Wind Helper
1.776
3141196NOKESVL
Solar/Wind Helper
1.144
226910AB2-157 C
Solar/Wind Helper
0.016
233933AB2-153 GEN
Solar/Wind Helper
0.238
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.024
20716928W4-060COL
Solar/Wind Helper
0.052
217213AMBOY SO C
Solar/Wind Helper
0.029
20673728F2S_V4-070
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.082
207437AD2-070 GEN
Solar/Wind Helper
0.138
20671928W4-073
Solar/Wind Helper
0.09
209116AE2-175 GEN
Solar/Wind Helper
1.777
960841AF2-375 GEN
Solar/Wind Harmer
0.624
270119AB2-067 GEN1
50/50
7.05
253378AE2-206_GEN
Solar/Wind Harmer
4.074
25326509SID D
Adder
1.478
246937BC-WTG2
Solar/Wind Harmer
4.329
970879AG2-548 GEN
Solar/Wind Harmer
1.284
247607V1-011 GEN
Solar/Wind Harmer
4.348
247522W1-056 GEN
Solar/Wind Harmer
2.469
942221AE2-234 GEN
Solar/Wind Harmer
3.759
962581AG1-107 GEN
Solar/Wind Harmer
5.371
961491AF2-440 GEN
Solar/Wind Harmer
2.232
274770LINCOLN ;1U
Adder
8.764
274771LINCOLN ;2U
Adder
8.764
274805UNIV PK N;1U
Adder
5.205
237061AD1-155 GEN
Solar/Wind Helper
1.974
235020AA1-095 C
Solar/Wind Helper
0.058
238221AF1-254 C O1
Solar/Wind Helper
0.297
316411AF1-147_GEN1
Solar/Wind Helper
0.984
23751201ROTHROCK
Solar/Wind Helper
0.821
223402AF1-300 C
Solar/Wind Helper
0.389
233930AB2-032 GEN
Solar/Wind Helper
0.389
233982AB2-133 GEN
Solar/Wind Helper
0.367
233946AB2-136 GEN
Solar/Wind Helper
0.581
232410W1-006 C
Solar/Wind Helper
0.518
233952AC2-187 GEN
Solar/Wind Helper
0.238
233954AC2-188 GEN
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.015
228754AB1-001 C
Solar/Wind Helper
0.026
219272CLEANLIGHT C
Solar/Wind Helper
0.026
217081WEATEXAS C
Solar/Wind Helper
0.013
20675928HOL_W4-097
Solar/Wind Helper
0.05
207471AF2-354 C
Solar/Wind Helper
0.169
24318905MLG2
50/50
7.451
270349AD2-093_GEN
Solar/Wind Harmer
4.513
270471AD2-092_GEN
Solar/Wind Harmer
4.513
253383AE2-342_GEN
Solar/Wind Harmer
1.057
25322209TAIT E
Adder
10.744
25322209TAIT E
Adder
10.502
253370AE2-315 SEC1
Adder
2.2
270246TR4_N_V150
Solar/Wind Harmer
0.933
247621Y3-024
Adder
0.257
970935AG2-582 GEN
Adder
238.716
316097T157 G90
Solar/Wind Helper
1.71
238147AE2-230_GEN1
Solar/Wind Helper
0.556
237080AD1-060 GEN
Solar/Wind Helper
0.369
219904AC1-010 C
Solar/Wind Helper
0.061
219906AC1-017 C
Solar/Wind Helper
0.042
20720828JCB_W4-025
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.132
20742028HF_AC1-207
Solar/Wind Helper
0.142
218438BLK ROCK C
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20674828DL_W4-046
Solar/Wind Helper
0.008
23559001PLEAS1
50/50
5.445
961921AG1-034 GEN
Solar/Wind Harmer
15.881
270287AF1-227 GEN3
Solar/Wind Harmer
2.547
942051AE2-217 GEN
Solar/Wind Harmer
21.323
942871AE2-306 GEN
Solar/Wind Harmer
1.07
270391AF1-285 GEN3
Solar/Wind Harmer
0.549
958581AF2-149 GEN
Solar/Wind Harmer
4.955
958091AF2-103 GEN
Solar/Wind Harmer
0.178
957541AF2-048 GEN
Solar/Wind Harmer
1.72
944531AF1-118 GEN
Solar/Wind Harmer
37.819
270063AE2-323 C
Solar/Wind Harmer
2.363
270541AE2-072 C
Solar/Wind Harmer
4.86
971347AH1-153 GEN
Solar/Wind Harmer
5.342
25196608WSDLE5
Adder
9.116
274752CRETE EC ;2U
Adder
8.571
274826FISK ;BP
Adder
11.319
274730ELWOOD EC;6P
Adder
16.929
238152AF2-075_GEN
Solar/Wind Helper
0.794
238127S14_GEN_2
Solar/Wind Helper
0.87
23777901MDS_W4-102
Solar/Wind Helper
0.192
316044AC1-158 PL1
Solar/Wind Helper
1.451
208835TUHI V3-051
Solar/Wind Helper
0.022
3147666LOUISA
Solar/Wind Helper
0.962
233998TM1NIN_3.36
Solar/Wind Helper
0.21
232404W1-003 C
Solar/Wind Helper
0.518
20715828PEM_W1-120
Solar/Wind Helper
0.097
219276PARKLANDSO C
Solar/Wind Helper
0.09
963711AG1-223 GEN
Solar/Wind Helper
0.065
20715228NPK_W1-113
Solar/Wind Helper
0.079
20720528MAN_W1-024
Solar/Wind Helper
0.029
219919AE1-041 FULL
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674928WA_W3-044
Solar/Wind Helper
0.099
207518AF1-320_GEN
Solar/Wind Helper
1.573
962761AG1-125 GEN
Solar/Wind Harmer
40.867
270520AE2-214 GEN
Solar/Wind Harmer
7.352
270391AF1-285 GEN3
Solar/Wind Harmer
1.427
270317AD1-130_GEN
Solar/Wind Harmer
3.738
253333AC1-068 GEN
Solar/Wind Harmer
1.205
241813AF1-122_GEN
Solar/Wind Harmer
6.22
971201AH1-060 GEN
Solar/Wind Harmer
1.944
270273AD2-016 GEN
Solar/Wind Harmer
3.042
241847AF2-150_GEN
Solar/Wind Harmer
4.61
25326309TAIT D
Adder
1.207
270216AD2-079_GEN
Solar/Wind Harmer
0.645
944031AF1-071 GEN
Solar/Wind Harmer
1.069
274754CRETE EC ;4U
Adder
8.571
274802UNIV PARK;5U
Adder
6.031
274732ELWOOD EC;7P
Adder
16.929
274674JOLIET 9 ;6U
Adder
15.855
235067AD1-061 GEN
Solar/Wind Helper
0.481
237002AB1-128_GEN
Solar/Wind Helper
0.477
208835TUHI V3-051
Solar/Wind Helper
0.022
3147666LOUISA
Solar/Wind Helper
0.553
233950AC2-186 GEN
Solar/Wind Helper
0.119
219921AF1-264
Solar/Wind Helper
0.052
219914AD2-027 C
Solar/Wind Helper
0.117
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
207454AA2-184 E
Solar/Wind Helper
0.313
217169METRODIV C
Solar/Wind Helper
0.004
270120AB2-067 GEN2
50/50
7.05
270054AF2-122 C O1
Solar/Wind Harmer
4.054
938701AE1-092 GEN
Solar/Wind Harmer
24.428
270462AD2-086
Solar/Wind Harmer
8.12
253415AE1-040 GEN
Solar/Wind Harmer
1.252
942801AE2-298 GEN
Solar/Wind Harmer
1.666
270247TR4_N_V136
Solar/Wind Harmer
0.933
253349AC2-067 GEN
Solar/Wind Harmer
2.225
944231AF1-091 GEN
Solar/Wind Harmer
19.433
960971AF2-388 GEN
Solar/Wind Harmer
11.731
970349AG2-230 GEN
Solar/Wind Harmer
16.027
970883AG2-550 GEN
Solar/Wind Harmer
10.668
961051AF2-396 GEN
Solar/Wind Harmer
16.91
961051AF2-396 GEN
Solar/Wind Harmer
7.865
270599AE1-208 GEN
Solar/Wind Harmer
8.665
25194408D.CRK1
Adder
8.037
24728905RICHG2
Adder
3.989
274808UNIV PK N;4U
Adder
5.171
274674JOLIET 9 ;6U
Adder
0.246
238148AE2-230_GEN2
Solar/Wind Helper
0.556
23585401KL_K28_T16
Solar/Wind Helper
1.534
238117U2-030
Solar/Wind Helper
0.357
235062AE1-101 C1
Solar/Wind Helper
1.786
237006AB1-125 GEN
Solar/Wind Helper
0.132
223401AF1-299 GEN
Solar/Wind Helper
0.389
316450AC1-158 RIC
Solar/Wind Helper
0.387
3132123MT JACKSON
Solar/Wind Helper
0.767
232424Y1-079 C
Solar/Wind Helper
0.119
232428Y3-058 C
Solar/Wind Helper
0.346
234015AF2-250 C
Solar/Wind Helper
0.039
966001AG1-469 GEN
Solar/Wind Helper
0.256
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.293
20675428EAM_W2-061
Solar/Wind Helper
0.016
24318805MLG1
50/50
10
270518AE2-148 GEN
Solar/Wind Harmer
13.997
971199AH1-059 GEN
Solar/Wind Harmer
2.432
253325AC1-069 GEN
Solar/Wind Harmer
1.205
961961AG1-039 GEN
Solar/Wind Harmer
3.18
270491AE1-102 GEN2
Solar/Wind Harmer
1.439
274753CRETE EC ;3U
Adder
8.571
274814UNIV PK N;0U
Adder
5.24
274807UNIV PK N;3U
Adder
5.228
274803UNIV PARK;6U
Adder
6.031
972038AH1-567 GEN2
Adder
0.377
238108AE1-109 GEN1
Solar/Wind Helper
0.122
237001AB1-127_GEN
Solar/Wind Helper
0.476
23562501BACKB
Solar/Wind Helper
1
233918AB1-142 GEN
Solar/Wind Helper
0.514
228729W2-030 C
Solar/Wind Helper
0.112
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.116
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
20671828STAW2-080
Solar/Wind Helper
0.027
217209CENTRL HS C
Solar/Wind Helper
0.008
207530AG1-191 GEN
Solar/Wind Helper
0.066
207439AE1-081 C O1
Solar/Wind Helper
0.019
211065PSPA IPP
Solar/Wind Helper
0.151
23559101PLEAS2
50/50
5.445
270122AB2-093 CT
50/50
4.1
970149AG2-104 GEN
Solar/Wind Harmer
25.235
270286AF1-227 GEN2
Solar/Wind Harmer
2.547
270578AF1-285 GEN2
Solar/Wind Harmer
1.427
270510AE1-227 GEN1
Solar/Wind Harmer
2.885
971073AG2-665 GEN
Solar/Wind Harmer
1.284
270297AD1-101 GEN
Solar/Wind Harmer
2.226
270258AD1-119 GEN
Solar/Wind Harmer
2.219
960001AF2-291 GEN
Solar/Wind Harmer
3.236
943021AE2-325 GEN
Solar/Wind Harmer
3.878
270222AC2-111 GEN
Solar/Wind Harmer
4.753
23920202STRYCT
Adder
1.44
23546401DTGZ2-030
Solar/Wind Helper
0.1
237038AE2-054 C
Solar/Wind Helper
0.294
3132273ORANGE
Solar/Wind Helper
0.049
233935AB2-179 C
Solar/Wind Helper
1.297
233987AB2-037 GEN
Solar/Wind Helper
2.395
232417X3-008 C
Solar/Wind Helper
0.238
233923SMA
Solar/Wind Helper
0.769
233997TMININ_4.2
Solar/Wind Helper
0.21
959561AF2-247 GEN
Solar/Wind Helper
0.021
20715728PEM_W1-119
Solar/Wind Helper
0.097
219249CENTRALDIV C
Solar/Wind Helper
0.01
207442AE1-156 GEN
Solar/Wind Helper
0.328
217211CAMDEN ST C
Solar/Wind Helper
0.005
207511W3-106 GEN
Solar/Wind Helper
0.027
20674128FR_U2-059
Solar/Wind Helper
0.004
211065PSPA IPP
Solar/Wind Helper
0.151
946101AF1-275 GEN
Solar/Wind Harmer
1.838
942861AE2-305 GEN
Solar/Wind Harmer
9.201
972159AH1-661 GEN
Adder
1.163
241960AC2-195 GEN
Solar/Wind Harmer
3.204
270269AC2-059
Solar/Wind Harmer
10.672
25326109MON D
Adder
1.457
971073AG2-665 GEN
Solar/Wind Harmer
8.835
253400AC2-068 GEN
Solar/Wind Harmer
0.895
927014AC1-188 GEN
Solar/Wind Harmer
1.72
944541AF1-119 GEN
Solar/Wind Harmer
4.494
247620Y3-023
Adder
0.492
25183208HLCRTG
Solar/Wind Harmer
6.454
970885AG2-551 GEN
Solar/Wind Harmer
2.481
270201AC2-176 GEN
Solar/Wind Harmer
5.48
964611AG1-324 GEN
Solar/Wind Harmer
0.557
270031AE2-169
Solar/Wind Harmer
8.665
25194508D.CRK3
Adder
1.503
24728805RICHG1
Adder
3.989
238149AF1-291A_GEN
Solar/Wind Helper
0.159
235054AD2-180 GEN
Solar/Wind Helper
2.118
235531U2-073 GEN
Solar/Wind Helper
3.481
316006AB2-029 C
Solar/Wind Helper
0.131
316045AC1-158 PL2
Solar/Wind Helper
4.643
232436AB1-176 C
Solar/Wind Helper
0.045
234036AF2-325 C
Solar/Wind Helper
0.043
233994AC2-023 GEN
Solar/Wind Helper
0.982
219912AD2-042 GEN
Solar/Wind Helper
0.152
219607WPEMNERT C
Solar/Wind Helper
0.081
219304NAMERICA C
Solar/Wind Helper
0.133
20674328GAR_V4-001
Solar/Wind Helper
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.111
NYPJM->LTFIMP_NY
CLTF
4.574
MECLTFEXP_MEC->PJM
CLTF
15.924
AH1-155LTFEXP_AH1-155->PJM
LTF
0.363
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.457
LGEELTFEXP_LGEE->PJM
CLTF
6.731
LAGNLTFEXP_LAGN->PJM
CLTF
14.456
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.423
WECLTFEXP_WEC->PJM
CLTF
3.853
SIGELTFEXP_SIGE->PJM
CLTF
0.504
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.226
TVALTFEXP_TVA->PJM
CLTF
7.078
AG2-052LTFEXP_AG2-052->PJM
LTF
0.242

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.57 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4761.71
MW Contribution:
2.77
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
6.887
972269AH1-719 GEN
Adder
2.495
253398AE2-221_GEN2
Solar/Wind Harmer
0
246936BC-WTG1
Solar/Wind Harmer
0.292
270489AE1-102 GEN1
Solar/Wind Harmer
0.942
965011AG1-365 GEN
Solar/Wind Harmer
7.206
958861AF2-177 GEN
Solar/Wind Harmer
3.083
252510AF1-249 C
Solar/Wind Harmer
0.054
945371AF1-202 GEN
Solar/Wind Harmer
0
270005AE1-210 C O1
Solar/Wind Harmer
1.528
942081AE2-220 GEN
Solar/Wind Harmer
0
270209AC1-174_GEN
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
76.605
942861AE2-305 GEN
Solar/Wind Harmer
6.105
270269AC2-059
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
1.079
970329AG2-216 GEN
Solar/Wind Harmer
3.232
25326109MON D
Adder
1.388
971073AG2-665 GEN
Solar/Wind Harmer
5.401
25183208HLCRTG
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.476
25194508D.CRK3
Adder
1.438
970885AG2-551 GEN
Solar/Wind Harmer
2.363
252509AD1-136 GEN
Solar/Wind Harmer
0.035
270201AC2-176 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.531
270031AE2-169
Solar/Wind Harmer
3.884
270383AD1-128 GEN
Solar/Wind Harmer
0
247620Y3-023
Adder
0.465
24728805RICHG1
Adder
3.809
965791AG1-447 GEN
Solar/Wind Harmer
6.414
24699105WLD G1 C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0
270180AB1-006 GEN1
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
9.886
958491AF2-143 GEN
Solar/Wind Harmer
10.177
276872AE1-163_GEN1
Solar/Wind Harmer
0
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.071
235054AD2-180 GEN
Solar/Wind Helper
1.845
316006AB2-029 C
Solar/Wind Helper
0.114
232436AB1-176 C
Solar/Wind Helper
0.043
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.934
316045AC1-158 PL2
Solar/Wind Helper
4.03
970825AG2-519 GEN
Solar/Wind Harmer
2.501
270594AE1-207 GEN
Solar/Wind Harmer
7.872
270032AE2-172
Solar/Wind Harmer
4.686
945111AF1-176 GEN
Solar/Wind Harmer
12.534
957891AF2-083 GEN
Solar/Wind Harmer
11.704
25196008MFTGT1
Adder
1.393
964861AG1-349 GEN
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.682
274751CRETE EC ;1U
Adder
8.15
274773LINCOLN ;4U
Adder
8.341
274774LINCOLN ;5U
Adder
8.341
274723RIVER EC ;12
Adder
17.708
24386605FR-22G C
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
3.554
970569AG2-363 GEN
Solar/Wind Harmer
20.202
939741AE1-205 GEN
Solar/Wind Harmer
9.427
23583801GRNGAP
Solar/Wind Helper
5.433
238126S14_GEN_1
Solar/Wind Helper
0.769
237085AD2-009_GEN
Solar/Wind Helper
1.596
3141196NOKESVL
Solar/Wind Helper
1.002
226910AB2-157 C
Solar/Wind Helper
0.014
233933AB2-153 GEN
Solar/Wind Helper
0.226
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219612MATRIX C
Solar/Wind Helper
0.023
270120AB2-067 GEN2
50/50
6.887
270054AF2-122 C O1
Solar/Wind Harmer
0
938701AE1-092 GEN
Solar/Wind Harmer
12.459
270462AD2-086
Solar/Wind Harmer
0
270247TR4_N_V136
Solar/Wind Harmer
0.046
960971AF2-388 GEN
Solar/Wind Harmer
4.179
25194408D.CRK1
Adder
7.692
970883AG2-550 GEN
Solar/Wind Harmer
7.088
970349AG2-230 GEN
Solar/Wind Harmer
10.604
270599AE1-208 GEN
Solar/Wind Harmer
6.473
944231AF1-091 GEN
Solar/Wind Harmer
16.273
926881AC1-175 GEN
Solar/Wind Harmer
0
24728905RICHG2
Adder
3.809
961051AF2-396 GEN
Solar/Wind Harmer
14.035
961051AF2-396 GEN
Solar/Wind Harmer
9.356
24725505WLD G2 C
Solar/Wind Harmer
0
24697605MDL-3G C
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.919
966841AG1-555 GEN
Solar/Wind Harmer
0.78
958481AF2-142 GEN
Solar/Wind Harmer
10.21
276876AE1-163_GEN2
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
7.158
238148AE2-230_GEN2
Solar/Wind Helper
0.481
238117U2-030
Solar/Wind Helper
0.315
23585401KL_K28_T16
Solar/Wind Helper
1.332
235062AE1-101 C1
Solar/Wind Helper
1.608
237006AB1-125 GEN
Solar/Wind Helper
0.12
223401AF1-299 GEN
Solar/Wind Helper
0.357
232424Y1-079 C
Solar/Wind Helper
0.113
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
316450AC1-158 RIC
Solar/Wind Helper
0.336
230433AD2-135 GEN
Solar/Wind Helper
0.017
214067T20SOLAR
Solar/Wind Helper
0.011
207459AE1-142 C O1
Solar/Wind Helper
0.282
270291AC1-194 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Harmer
0.539
270377AD1-106 GEN
Solar/Wind Harmer
2.755
965051AG1-369 GEN
Solar/Wind Harmer
3.6
971985AH1-537 GEN
Solar/Wind Harmer
2.117
970031AG2-029 GEN
Solar/Wind Harmer
3.844
945581AF1-223 GEN
Solar/Wind Harmer
0
970155AG2-107 GEN
Solar/Wind Harmer
21.201
971995AH1-542 GEN
Solar/Wind Harmer
2.804
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
965421AG1-410 GEN
Solar/Wind Harmer
21.735
253316AC1-085 GEN3
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.209
965651AG1-433 GEN
Solar/Wind Harmer
2.09
252516AE2-318_GEN
Solar/Wind Harmer
7.967
270024AE2-089 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.672
970613AG2-401 GEN
Solar/Wind Harmer
5.168
24639705ELKHART HY
Adder
0.155
270449AD2-020 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.941
24728605AND G2
Adder
3.773
945681AF1-233 GEN
Solar/Wind Harmer
12.929
274676JOLIET 29;8U
Adder
30.093
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
316095T157 G97
Solar/Wind Helper
1.459
238109AE1-109 GEN2
Solar/Wind Helper
0.107
238185AF2-356 C
Solar/Wind Helper
2.442
238120AE2-309 GEN
Solar/Wind Helper
0.491
23777801MSM_W1-116
Solar/Wind Helper
0.111
227287AC2-120 GEN
Solar/Wind Helper
0.337
232422X3-066 FULL
Solar/Wind Helper
0.111
233964AF2-378 GEN
Solar/Wind Helper
0.041
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
230415AB2-049 C
Solar/Wind Helper
0.029
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
20714928UPF_X1-085
Solar/Wind Helper
0.005
219918AC2-009 C
Solar/Wind Helper
0.001
205941AD2-115 GEN
Solar/Wind Helper
0.481
957471AF2-041 GEN
Solar/Wind Harmer
13.123
962771AG1-126 GEN
Solar/Wind Harmer
33.201
219912AD2-042 GEN
Solar/Wind Helper
0.146
219607WPEMNERT C
Solar/Wind Helper
0.078
219304NAMERICA C
Solar/Wind Helper
0.127
270119AB2-067 GEN1
50/50
6.887
25326509SID D
Adder
1.398
970879AG2-548 GEN
Solar/Wind Harmer
1.228
246937BC-WTG2
Solar/Wind Harmer
0.292
247607V1-011 GEN
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.306
962581AG1-107 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
2.858
970621AG2-405 GEN
Solar/Wind Harmer
1.302
957841AF2-078 GEN
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
8.341
274771LINCOLN ;2U
Adder
8.341
274805UNIV PK N;1U
Adder
4.952
24387305FR-4G C
Solar/Wind Harmer
0
274888KELLY CRK;1U
Solar/Wind Harmer
0.4
970941AG2-585 GEN
Solar/Wind Harmer
3.776
276897AD1-100 C
Solar/Wind Harmer
17.145
276893AG1-478 C
Solar/Wind Harmer
0.456
970241AG2-163 GEN
Solar/Wind Harmer
3.982
962691AG1-118 GEN
Solar/Wind Harmer
20.32
942111AE2-223 GEN
Solar/Wind Harmer
2.188
235020AA1-095 C
Solar/Wind Helper
0.051
237061AD1-155 GEN
Solar/Wind Helper
1.703
238221AF1-254 C O1
Solar/Wind Helper
0.267
316411AF1-147_GEN1
Solar/Wind Helper
0.865
223402AF1-300 C
Solar/Wind Helper
0.357
23751201ROTHROCK
Solar/Wind Helper
0.696
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
233946AB2-136 GEN
Solar/Wind Helper
0.553
232410W1-006 C
Solar/Wind Helper
0.493
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
228754AB1-001 C
Solar/Wind Helper
0.025
219272CLEANLIGHT C
Solar/Wind Helper
0.025
971029AG2-637 GEN
Solar/Wind Harmer
10.639
247536S-71 GEN
Solar/Wind Harmer
0.283
959141AF2-205 GEN
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
4.135
274775LINCOLN ;6U
Adder
8.341
274777LINCOLN ;8U
Adder
8.341
24386405FR-21G C
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.18
960591AF2-350 GEN
Solar/Wind Harmer
6.866
972228AH1-698 GEN2
Adder
3.644
972165AH1-665 GEN
Solar/Wind Harmer
6.102
274675JOLIET 29;7U
Adder
30.093
274675JOLIET 29;7U
Adder
29.018
970833AG2-524 GEN
Solar/Wind Harmer
7.521
970833AG2-524 GEN
Solar/Wind Harmer
5.014
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
2.63
971411AH1-196 GEN
Solar/Wind Harmer
10.113
23750701CROSSCHOOL
Solar/Wind Helper
1.401
205943AE1-185 GEN
Solar/Wind Helper
0.494
233915AB1-141 GEN
Solar/Wind Helper
0.488
228728W1-130C
Solar/Wind Helper
0.052
227927V4-067C
Solar/Wind Helper
0.01
219615MILLCREEK C
Solar/Wind Helper
0.026
219620RIDERU C
Solar/Wind Helper
0.001
971171AH1-044 GEN
Solar/Wind Harmer
8.748
270051AF1-062 GEN
50/50
11.411
270512AE1-227 GEN2
Solar/Wind Harmer
1.899
970879AG2-548 GEN
Solar/Wind Harmer
5.401
970065AG2-057 GEN
Solar/Wind Harmer
0.734
253394AE2-221_GEN
Solar/Wind Harmer
0
246938BC-WTG3
Solar/Wind Harmer
0.261
965021AG1-366 GEN
Solar/Wind Harmer
2.402
971191AH1-055 GEN
Solar/Wind Harmer
18.47
270043AE2-236 GEN
Solar/Wind Harmer
4.595
270367AC2-061_GEN
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
10.618
270186AC1-089 GEN
Solar/Wind Harmer
0
270240V3-007_GEN2
Solar/Wind Harmer
0
970825AG2-519 GEN
Solar/Wind Harmer
5.307
945111AF1-176 GEN
Solar/Wind Harmer
5.694
270505AE1-170 C O1
Solar/Wind Harmer
7.374
25196008MFTGT1
Adder
1.349
274772LINCOLN ;3U
Adder
8.341
274724RIVER EC ;11
Adder
17.501
972167AH1-666 GEN
Solar/Wind Harmer
5.491
972259AH1-714 GEN
Adder
18.754
274729ELWOOD EC;1P
Adder
16.119
946671AF1-331 GEN
Solar/Wind Harmer
0.719
274850MENDOTA H;RU
Solar/Wind Harmer
0.078
970571AG2-364 GEN
Solar/Wind Harmer
13.468
238175AF1-290_GEN
Solar/Wind Helper
0.152
316415AF1-147_GEN2
Solar/Wind Helper
0.865
237048AF1-022 C
Solar/Wind Helper
0.164
205916AD1-020 GEN
Solar/Wind Helper
1.664
233944AB2-135 GEN
Solar/Wind Helper
0.573
232408W1-005 C
Solar/Wind Helper
0.493
219907AC1-030 C
Solar/Wind Helper
0.033
20716028EGP_W2-019
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.05
972239AH1-704 GEN
50/50
2.774
961821AG1-024 GEN
Solar/Wind Harmer
4.899
945631AF1-228 GEN
Solar/Wind Harmer
0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.517
270432AC2-029 GEN
Solar/Wind Harmer
3.42
270263AC1-001 GEN
Solar/Wind Harmer
0.753
241972AD1-140 GEN
Solar/Wind Harmer
0.821
270340AC2-060 GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
5.044
965041AG1-368 GEN
Solar/Wind Harmer
7.193
25196508WSDLE4
Adder
8.634
964611AG1-324 GEN
Solar/Wind Harmer
2.759
971609AH1-304 GEN
Solar/Wind Harmer
1.153
270526AF1-158 GEN
Solar/Wind Harmer
0
960681AF2-359 GEN
Solar/Wind Harmer
0
270356AE2-297 GEN
Solar/Wind Harmer
0
946581AF1-322 GEN
Solar/Wind Harmer
-0.001
274776LINCOLN ;7U
Adder
8.341
963841AG1-237 GEN
Solar/Wind Harmer
2.97
274687WILL CNTY;4U
Adder
27.42
274687WILL CNTY;4U
Adder
27.42
972163AH1-664 GEN
Solar/Wind Harmer
7.619
274731ELWOOD EC;2P
Adder
16.119
274733ELWOOD EC;3P
Adder
16.119
926823AC1-168 GEN
Solar/Wind Harmer
1.145
276726Z2-087_GEN
Solar/Wind Harmer
0
238118U2-030_1
Solar/Wind Helper
0.315
23779801AA1-109
Solar/Wind Helper
0.188
3138216PACIFIC
Solar/Wind Helper
0.043
226929AD2-058 GEN
Solar/Wind Helper
0.096
205917AD1-020 ES
Solar/Wind Helper
0.358
23750501ELLIOTTS
Solar/Wind Helper
0.573
205956AE1-196_GEN
Solar/Wind Helper
0.494
233901CHERRYDALE C
Solar/Wind Helper
0.226
20715028HAN_X4-015
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
316164AC1-076 GEN
Solar/Wind Helper
1.068
20720628TIN_W1-124
Solar/Wind Helper
0.184
23559001PLEAS1
50/50
5.39
961921AG1-034 GEN
Solar/Wind Harmer
7.349
942051AE2-217 GEN
Solar/Wind Harmer
14.139
270391AF1-285 GEN3
Solar/Wind Harmer
0.517
944531AF1-118 GEN
Solar/Wind Harmer
32.112
25196608WSDLE5
Adder
8.723
270063AE2-323 C
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Harmer
0.319
971347AH1-153 GEN
Solar/Wind Harmer
3.535
970781AG2-491 GEN
Solar/Wind Harmer
6.916
274752CRETE EC ;2U
Adder
8.15
958171AF2-111 GEN
Solar/Wind Harmer
17.234
274887GEN-1.85
Solar/Wind Harmer
0.178
274826FISK ;BP
Adder
10.773
24728705AND G3
Adder
7.891
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.403
274730ELWOOD EC;6P
Adder
16.119
270541AE2-072 C
Solar/Wind Harmer
0
274862TOP CROP ;2U
Solar/Wind Harmer
0.919
276868AE1-113 GEN
Solar/Wind Harmer
1.355
274879MINONK ;1U
Solar/Wind Harmer
0.283
274855GSG-6 ;RU
Solar/Wind Harmer
0.246
970193AG2-126 GEN
Solar/Wind Harmer
10.106
238152AF2-075_GEN
Solar/Wind Helper
0.687
23777901MDS_W4-102
Solar/Wind Helper
0.172
238127S14_GEN_2
Solar/Wind Helper
0.769
208835TUHI V3-051
Solar/Wind Helper
0.021
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
316044AC1-158 PL1
Solar/Wind Helper
1.259
20715828PEM_W1-120
Solar/Wind Helper
0.093
219276PARKLANDSO C
Solar/Wind Helper
0.087
963711AG1-223 GEN
Solar/Wind Helper
0.062
20715228NPK_W1-113
Solar/Wind Helper
0.076
20720528MAN_W1-024
Solar/Wind Helper
0.027
962761AG1-125 GEN
Solar/Wind Harmer
33.201
270520AE2-214 GEN
Solar/Wind Harmer
0
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270317AD1-130_GEN
Solar/Wind Harmer
0
270273AD2-016 GEN
Solar/Wind Harmer
0.78
241813AF1-122_GEN
Solar/Wind Harmer
3.287
971201AH1-060 GEN
Solar/Wind Harmer
1.467
25326309TAIT D
Adder
1.151
270437AC2-090 C
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
7.818
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
8.15
24385905FR-11G C
Solar/Wind Harmer
0
274802UNIV PARK;5U
Adder
5.739
274732ELWOOD EC;7P
Adder
16.119
274674JOLIET 9 ;6U
Adder
4.855
939401AE1-172 GEN
Solar/Wind Harmer
5.095
962781AG1-127 GEN
Solar/Wind Harmer
6.441
235067AD1-061 GEN
Solar/Wind Helper
0.432
237002AB1-128_GEN
Solar/Wind Helper
0.43
208835TUHI V3-051
Solar/Wind Helper
0.021
233950AC2-186 GEN
Solar/Wind Helper
0.113
219921AF1-264
Solar/Wind Helper
0.05
219914AD2-027 C
Solar/Wind Helper
0.111
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219688LUMSOLAR_S C
Solar/Wind Helper
0.039
207454AA2-184 E
Solar/Wind Helper
0.301
970153AG2-106 GEN
Solar/Wind Harmer
21.201
270284AF1-227 GEN1
Solar/Wind Harmer
-0.001
24721905FLATG4
Adder
22.814
253370AE2-315 SEC1
Adder
2.099
253371AE2-315 SEC2
Adder
1.985
253317AC1-085 GEN4
Solar/Wind Harmer
0
946181AF1-283 GEN
Solar/Wind Harmer
9.372
270588AE1-091_GEN
Solar/Wind Harmer
5.637
24695305TIMB G C
Solar/Wind Harmer
0.609
252519AF1-045_GEN
Solar/Wind Harmer
3.711
25194608D.CRK4
Adder
1.672
946031AF1-268 GEN
Solar/Wind Harmer
6.713
970289AG2-191 GEN
Solar/Wind Harmer
0.773
247642Z2-115 C
Solar/Wind Harmer
0.003
274811UNIV PK N;7U
Adder
4.941
276806AD2-047 C O1
Solar/Wind Harmer
3.89
24728505AND G1
Adder
3.773
274676JOLIET 29;8U
Adder
29.018
274734ELWOOD EC;8P
Adder
16.119
274736ELWOOD EC;9P
Adder
16.119
943121AE2-341 GEN
Solar/Wind Harmer
11.428
943591AF1-030 GEN
Solar/Wind Harmer
7.6
964991AG1-363 GEN
Solar/Wind Helper
4.979
238110AE1-109 GEN3
Solar/Wind Helper
0.107
235063AE1-101 C2
Solar/Wind Helper
1.608
205932AD2-116_GEN
Solar/Wind Helper
0.494
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
316447AC1-158 HLD
Solar/Wind Helper
2.771
219766PARADISE C
Solar/Wind Helper
0.053
203975AE1-071-GEN
Solar/Wind Helper
2.421
20714528FRN_Y2-051
Solar/Wind Helper
0.055
219680HOPEWELLV C1
Solar/Wind Helper
0.003
959091AF2-200 GEN
Solar/Wind Harmer
8.748
24318905MLG2
50/50
6.869
270349AD2-093_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.001
971655AH1-328 GEN
Solar/Wind Harmer
2.753
970935AG2-582 GEN
Adder
241.832
25322209TAIT E
Adder
10.24
25322209TAIT E
Adder
10.01
253370AE2-315 SEC1
Adder
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.046
247621Y3-024
Adder
0.245
971613AH1-306 GEN
Solar/Wind Harmer
3.374
970291AG2-192 GEN
Solar/Wind Harmer
0.913
970291AG2-192 GEN
Solar/Wind Harmer
0.421
965681AG1-436 GEN
Solar/Wind Harmer
8.747
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.732
276901AD2-066 C O1
Solar/Wind Harmer
0
316097T157 G90
Solar/Wind Helper
1.459
238147AE2-230_GEN1
Solar/Wind Helper
0.481
237080AD1-060 GEN
Solar/Wind Helper
0.332
219904AC1-010 C
Solar/Wind Helper
0.059
219906AC1-017 C
Solar/Wind Helper
0.041
20720828JCB_W4-025
Solar/Wind Helper
0.061
20714828MDF_W3-079
Solar/Wind Helper
0.127
20742028HF_AC1-207
Solar/Wind Helper
0.137
218438BLK ROCK C
Solar/Wind Helper
0.026
971341AH1-150 GEN
Solar/Wind Harmer
8.748
971343AH1-151 GEN
Solar/Wind Harmer
8.748
241955AC1-078 GEN
Solar/Wind Harmer
-0.001
943861AF1-054 GEN
Solar/Wind Harmer
3.014
943851AF1-053 GEN
Solar/Wind Harmer
2.087
270302AB2-170 GEN
Solar/Wind Harmer
0
971653AH1-327 GEN
Solar/Wind Harmer
1.077
970179AG2-119 GEN
Solar/Wind Harmer
6.643
253372AE2-315 SEC3
Adder
1.985
253372AE2-315 SEC3
Adder
1.985
25306009OHH W.
Adder
3.011
957201AF2-014 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.261
963791AG1-232 GEN
Solar/Wind Harmer
9.652
970289AG2-191 GEN
Solar/Wind Harmer
1.334
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
7.635
274800UNIV PARK;3U
Adder
5.736
274801UNIV PARK;4U
Adder
5.736
972227AH1-698 GEN1
Adder
2.566
274735ELWOOD EC;4P
Adder
16.119
970169AG2-114 GEN
Solar/Wind Harmer
6.772
959341AF2-225 GEN
Solar/Wind Harmer
7.07
238169AE2-226 GEN1
Solar/Wind Helper
0.681
238170AE2-226 GEN2
Solar/Wind Helper
0.681
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.16
959381AF2-229 GEN
Solar/Wind Helper
0.346
232432Z2-076 GEN
Solar/Wind Helper
0.065
315651AD1-115 GEN
Solar/Wind Helper
0.766
230407AD2-065 C
Solar/Wind Helper
0.039
20720728JCB_W1-129
Solar/Wind Helper
0.055
270459AD2-067 GEN
Solar/Wind Harmer
0
940611AE2-048 GEN
Solar/Wind Harmer
18.925
941391AE2-136 GEN
Solar/Wind Harmer
10.66
270435AC2-044 GEN
Solar/Wind Harmer
0.918
971567AH1-282 GEN
Solar/Wind Harmer
5.517
270007AE1-245 C
Solar/Wind Harmer
0
24729505KEY G4
Adder
6.652
270071AF1-092 GEN
Solar/Wind Harmer
13.7
25196408WSDLE3
Adder
8.98
25196308WSDLE2
Adder
8.902
25196208WSDLE1
Adder
8.879
25196708WSDLE6
Adder
8.857
270543AE2-219 C
Solar/Wind Harmer
4.962
971771AH1-392 GEN
Solar/Wind Harmer
7.027
25196108MFTGT2
Adder
1.536
25196108MFTGT2
Adder
1.426
971549AH1-272 GEN
Solar/Wind Harmer
14.305
24691005MDL-2G C
Solar/Wind Harmer
0
274728ELWOOD EC;5P
Adder
16.119
274863CRW1-WTG
Solar/Wind Harmer
0
274864CRW2-WTG
Solar/Wind Harmer
0
970073AG2-061 GEN
Solar/Wind Harmer
2.262
276861AD2-134 GEN
Solar/Wind Harmer
0.12
276863AD2-134 GEN
Solar/Wind Harmer
0.12
20390526W1-045 C
Solar/Wind Helper
0.339
3141426STAFORD
Solar/Wind Helper
0.051
233940AF2-379 C
Solar/Wind Helper
0.06
230434AG1-499 GEN
Solar/Wind Helper
0.223
219258KINSLEYDEP C
Solar/Wind Helper
0.075
23559101PLEAS2
50/50
5.39
270122AB2-093 CT
50/50
3.675
970149AG2-104 GEN
Solar/Wind Harmer
17.929
270510AE1-227 GEN1
Solar/Wind Harmer
1.899
971073AG2-665 GEN
Solar/Wind Harmer
1.228
960001AF2-291 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.661
970773AG2-487 GEN
Solar/Wind Harmer
1.233
970373AG2-245 GEN
Solar/Wind Harmer
14.656
971917AH1-482 GEN
Solar/Wind Harmer
9.046
941551AE2-152 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
16.157
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274861TOP CROP ;1U
Solar/Wind Harmer
0
276882AE2-255 GEN
Solar/Wind Harmer
0.791
274872LEEDK;1U
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0
23546401DTGZ2-030
Solar/Wind Helper
0.086
237038AE2-054 C
Solar/Wind Helper
0.264
233935AB2-179 C
Solar/Wind Helper
1.233
233987AB2-037 GEN
Solar/Wind Helper
2.277
232417X3-008 C
Solar/Wind Helper
0.226
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
959561AF2-247 GEN
Solar/Wind Helper
0.02
20715728PEM_W1-119
Solar/Wind Helper
0.093
959081AF2-199 GEN
Solar/Wind Harmer
4.374
971067AG2-660 GEN
Solar/Wind Harmer
1.458
24318805MLG1
50/50
9.823
270518AE2-148 GEN
Solar/Wind Harmer
0.631
253325AC1-069 GEN
Solar/Wind Harmer
0.009
971199AH1-059 GEN
Solar/Wind Harmer
1.566
970191AG2-125 GEN
Solar/Wind Harmer
1.872
270491AE1-102 GEN2
Solar/Wind Harmer
0.942
270004AE1-209 GEN
Solar/Wind Harmer
1.528
24379505HDWTR1G C
Solar/Wind Harmer
0
964401AG1-302 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0
274753CRETE EC ;3U
Adder
8.15
274814UNIV PK N;0U
Adder
4.984
274807UNIV PK N;3U
Adder
4.973
24386205FR-12G C
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
5.739
276843GEN-1.7
Solar/Wind Harmer
0.222
972038AH1-567 GEN2
Adder
0.359
238108AE1-109 GEN1
Solar/Wind Helper
0.107
237001AB1-127_GEN
Solar/Wind Helper
0.428
23562501BACKB
Solar/Wind Helper
0.845
233918AB1-142 GEN
Solar/Wind Helper
0.488
228729W2-030 C
Solar/Wind Helper
0.107
219686LUMSOLAR_N C
Solar/Wind Helper
0.039
219348LDSOLAR C
Solar/Wind Helper
0.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.595
NYPJM->LTFIMP_NY
CLTF
4.644
TVALTFEXP_TVA->PJM
CLTF
6.984
AG2-052LTFEXP_AG2-052->PJM
LTF
0.23
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.215
LGEELTFEXP_LGEE->PJM
CLTF
6.478
MECLTFEXP_MEC->PJM
CLTF
15.273
AH1-155LTFEXP_AH1-155->PJM
LTF
0.345
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.883
WECLTFEXP_WEC->PJM
CLTF
3.676
LAGNLTFEXP_LAGN->PJM
CLTF
14.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.353
CPLELTFEXP_CPLE->PJM
CLTF
0.539
SIGELTFEXP_SIGE->PJM
CLTF
0.485
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
235117 to 235111 ckt 1
242925 to 235117 ckt 1

Winter Peak Analysis

The New Service Request AH1-704 was evaluated as a 24.0 MW (20.0 MW Capacity) injection in the AEP area.

AH1-704 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 509.0 MW (24.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-704 was evaluated as a 24.0 MW injection

AH1-704 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 509.0 MW (24.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

 

New Service Requests AG2-082, AG2-568, AG2-657, AH1-580, AH1-686, AH1-704 and AH1-719 in PJM Transition Cycle 2, Cluster 32 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 32 projects.

 

This analysis is effectively a screening study to determine whether the addition of the Cluster 32 projects will meet the dynamics requirements of the NERC, AEP and PJM reliability standards.

 

The load flow scenario for the analysis was based on the RTEP 2028 Summer Peak, modified to include applicable projects. Cluster 32 projects have been dispatched online at maximum power output, with 1.0 voltage at the terminal bus.

 

Transition Cycle 2 Cluster 32 will be tested for compliance with NERC, PJM and other applicable criteria. The contingencies will be studied with a 20 second simulation time. Contingencies to be studied include:

       a)       Steady-state operation (Category P0);

       b)       Three-phase faults with normal clearing time (and with unsuccessful high-speed reclosing) (Category P1);

       c)       Single-phase bus faults with normal clearing time (Category P2);

       d)       Single-phase faults with stuck breaker (Category P4);

       e)       Single-phase faults placed at 80% of the line with delayed (Zone 2) clearing at line end remote from the fault due to primary communications/relay failure (Category P5);

       f)       Three-phase faults with loss of multiple-circuit tower line; (and with unsuccessful high-speed reclosing) (Category P7).

 

High Speed Reclosing (HSR) facilities were found in the vicinity of TC2 Cluster 32 projects.

 

Prior outage scenarios will not be considered for this study.

 

For all simulations, the queue project under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

For all the fault contingencies tested on the 2028 Summer Peak case:

       a)       Cluster 32 projects were able to ride through the faults (except for faults where protective action trips a generator(s)),

       b)       The system with Cluster 32 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3% for interarea modes and 4% for local modes.

       c)       Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus).

       d)       No transmission element tripped, other than those either directly connected or designed to trip because of that fault.

 

In several contingencies, AG2-657 shows slow reactive power recovery. Although this issue did not cause instability in the system, the model was tuned to achieve satisfactory reactive power recovery. This was accomplished by adjusting Kc in the plant controller model (REPCA1) by setting Kc from 0 to 0.15. The parameters modification is pending developer’s confirmation.

 

The IPCMD and IQCMD states in the REPCA1 models of AG2-082 showed erratic behavior for some contingencies in which AG2-082 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

The IPCMD and IQCMD states in the REPCA1 models of AG2-568 showed erratic behavior for some contingencies in which AG2-568 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

The IPCMD and IQCMD states in the REPCA1 models of AG2-657 showed erratic behavior for some contingencies in which AG2-657 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

The IPCMD and IQCMD states in the REPCA1 models of AH1-580 showed erratic behavior for some contingencies in which AH1-580 has been disconnected as part of the contingency event. Since the machines are disconnected and no active or reactive power is injected into the system, this behavior is likely fictitious and a limitation of the software. This does not cause instability in the system.

 

No mitigations were found to be required.

 

Table 1: Transition Cycle 2 Cluster 32 Projects

 

 

 

 

Project

Fuel Type

Transmission Owner

MFO (MW)

Point of Interconnection

AG2-082

Solar

AEP

200

Nottingham substation 138 kV

AG2-568

Solar

AEP

80

Bim - Sundial 138 kV

AG2-657

Solar

AEP

90

Kanawha River - Carbondale 138 kV

AH1-580

Solar

AEP

200

Nottingham station 138 kV

AH1-686

Natural Gas

AEP

24

Hanging Rock substation 765 kV

AH1-704

Natural Gas

AEP

24

Hannibal substation 138 kV

AH1-719

Natural Gas

AEP

24

Beverly substation 345 kV

 

Reactive Power Analysis

The reactive power capability of AH1-704 meets the 1.00 leading and 0.90 lagging power factor at the generator terminals.

Steady-State Voltage Analysis

Not Required

A steady state voltage analysis is evaluated on a project-by-project basis and depends on specific project parameters. For this project, a steady state voltage analysis is not required per PJM's Manual 14H, Section 4.5.2.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

(No dependencies were identified)

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase II System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not ContingentTopology Changing

Note 1: AH1-704 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AH1-704 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
No new ratings for this Flowgate.

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-704


AH1-704 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-704 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-704 One Line Diagram

AH1-704 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.