AH1-716 Phase II System Impact Study Report

v1.00 released 2026-06-03 18:43

Surry-Skiffes Creek 500kV

650.0 MW Capacity / 650.0 MW Energy

Introduction

This Phase II System Impact Study (SIS) Report has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 310 for New Service Requests (projects) in Transition Cycle 2 (TC2). The Project Developer/Eligible Customer (developer) is Cardinal Energy Storage East, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase II System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle summary format and (ii) an individual project-level basis. The Phase II System Impact Study Results (for both the summary and individual reports) will be publicly available on PJM’s website. Project Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.5, PJM takes the following actions during the Phase II System Impact Study:

  1. PJM will retool load flow results from the Phase I System Impact Study (summer peak, winter peak and light load) based on decisions made by Project Developers or Eligible Customers during Decision Point I.
  2. PJM will conduct any required voltage analyses.
  3. PJM will perform short circuit and stability analyses as required.
  4. PJM will coordinate with the Affected System to confirm which projects in the PJM Cycle will require Affected System studies. If the Affected System Operator indicates that an Affected System study is required, PJM will:
    1. Notify the Project Developer or Eligible Customer of the need for an Affected System study and the requirement to execute an Affected System study agreement with the impacted Affected System Operator, and;
    2. Include the results of the Affected System Operator’s Affected System Study in the Phase II System Impact Study results, if applicable and available.
  5. The Phase II System Impact Study Results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.

The Transmission Owner takes the following actions during the Phase II System Impact Study:

  1. Verify Interconnection Facilities and Network Upgrades required to accommodate the New Service Request.
  2. Perform a Facilities Study. The Facilities Study in Phase II System Impact Study phase will be for the physical Interconnection Facilities. The Facilities Study requirements are outlined in Attachment C of this manual. The study will be conducted pursuant to Tariff, Part VII, Subpart D, section 307(A)(7) and Tariff, Part VIII, Subpart C, section 404(A)(7).

Decision Point II Requirements

At the close of Phase II System Impact Study, PJM will initiate Decision Point II (DP2). During DP2, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.A. Additional information on these elements is available in PJM Manual 14H sections 4.6, 6, and 7.

Allowable project modifications at Decision Point II are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 311.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

Adverse Test Eligibility

This New Service Request does not meet the Adverse Study Impact Criteria and has the option to either move forward in the Cycle process or withdraw at DP2 with Readiness Deposit #1 forfeited. See adverse study impact calculation below.

This section details whether a Project Developer or Eligible Customer qualifies for the Adverse Study Impact clause outlined in the PJM OATT, Part VII, Subpart D, section 311.B and Manual 14H, section 6.2.2. In order to qualify for an Adverse Study Impact at Decision Point II, the Network Upgrade cost from Phase I to Phase II must:

  1. Increase overall by 25% or more
  2. Increases by more than $10,000 per MW (Includes Costs identified in Affected System studies)

If a New Service Request meets the criteria above and chooses to withdraw the request, PJM will refund the cumulative Readiness Deposit amounts paid at the Application Phase and at Decision Point I (RD1 and RD2, respectively).

The below calculations show the computation of this New Service Request's Adverse Study Impact

DP2 Adverse Eligibility = DP2 Adverse Cost Alloc DP1 Adverse Cost Alloc > 1.25 AND ( DP2 Adverse Cost Alloc - DP1 Adverse Cost Alloc ) Project Size > $10,000 per MW
DP2 Adverse Eligibility = $50,320,099 $280,329,336 = 0.18 AND ( $50,320,099 - $280,329,336 ) 650.0 = $-353,860 per MW

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — James City County, Virginia. The installed facilities will have a total capability of 650.0 MW with 650.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AH1-716
Project Name:
Surry-Skiffes Creek 500kV
Project Developer Name:
Cardinal Energy Storage East, LLC
State:
Virginia
County:
James City
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
650.0
MWE:
650.0
MWC:
650.0
Battery Storage Specification:
3900.0 MWh, 6.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Report Available

The transmission owner has completed the Physical Interconnection Facilities Study. This report is available for download.

Point of Interconnection

AH1-716 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system by tapping the Surry-Skiffes Creek 500 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In Phase II SIS, the interconnected Transmission Owner has performed a facilities study for both the Transmission Owner Interconnection Facilities (TOIF) and Physical Interconnection Network Upgrades. The System Reliability Network Upgrade shown in the table are planning level cost estimates which are subject to change as a result of a facility study performed by the TO during Phase III System Impact Study.

Based on the Phase II SIS results, the AH1-716 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit #3 are also shown below.

Cost Summary
DescriptionCost Allocated to AH1-716Cost Subject to Readiness*Cost Subject to Adverse
Transmission Owner Interconnection Facilities (TOIF)$2,083,467$0$0
Other Scope$552,827$0$0
Option To Build Oversight$0$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$30,540,265$30,540,265$30,540,265
Network Upgrades$19,779,834$19,779,834$19,779,834
System Reliability Network Upgrades
Steady State Thermal & Voltage$0$0$0
Transient Stability$0$0$0
Short Circuit$0$0$0
Transmission Owner Analysis
SubRegional$0$0$0
Distribution$0$0$0
Affected System Reinforcements
AFS - PJM Violations$0$0$0
AFS - Non-PJM Violations$0$0$0
Total$52,956,393$50,320,099$50,320,099

* Contributes to calculation for Readiness Deposit #3 (RD3). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Note 4: Please see the ‘Affected Systems Studies’ section of this Phase II SIS report for details on your project’s need for an Affected Systems Study. If your project requires an Affected Systems Study, the Affected Systems impacts may not be available from the Affected System Operator at the time of the PJM Phase II SIS. Therefore, the cost in this section would not reflect any required upgrades by the Affected System until the study is completed. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 311 (Decision Point II) A.1.b and PJM Manual 14H, section 6.2, Readiness Deposit #3 (RD3) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point II (DP2), the Project Developer or Eligible Customer is required to submit Readiness Deposit #3, which is calculated as 20% of cost allocation for required Phase II Network Upgrades minus Readiness Deposit #1 & Readiness Deposit #2.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Note 4: Readiness Deposit #3 can be zero, but may not be a negative number.

Readiness Deposit #3 Due for Project AH1-716

Readiness Deposit #3 has been calculated for the project based on the Phase II System Impact Study results and is shown in the table below. This Readiness Deposit #3 must be provided at Decision Point II through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit #3 Due for AH1-716
Project ID: AH1-716
20% of cost allocation for Phase II Network Upgrades:(A) $10,064,020
Sum of Readiness Deposit #1 & Readiness Deposit #2 Received:(B) $28,032,934
Readiness Deposit #3 (RD3) due at DP2:(A) - (B) = $0
Note: Failure to provide an acceptable form of Readiness Deposit #3 by the end of Decision Point II will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Build Option
Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

This scope serves to cut in 500 kV line 582 into a new three breaker ring bus substation.

$8,912,322$8,935,710$673,729$862,781$19,384,542$19,384,542
(Pending)

Remote end Network Upgrade at Surry Substation.

$116,626$55,279$18,552$7,189$197,646$197,646
(Pending)

Remote end Network Upgrade at Skiffes Creek.

$116,626$55,279$18,552$7,189$197,646$197,646
Other
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

This scope includes metering accuracy capacitor coupled voltage transformers ("CCVT"), metering accuracy current transformers ("CT") and associated metering equipment.

$233,230$24,592$281,210$13,795$552,827$552,827
Stand-Alone Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

The scope serves to build a 500kV three breaker ring bus to support the new solar farm built by Project Developer.

$13,505,069$11,935,453$3,891,165$1,208,578$30,540,265$30,540,265
Transmission Owner Interconnection Facilities
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

The Transmission Owner Interconnection Facilities include the portion of the interconnection switching station which is associated solely with the single feed to the generating facilities collector station. The equipment associated with the Transmission Owner Interconnection Facilities includes disconnect switch, conductors and connectors.

$986,196$931,535$58,652$107,084$2,083,467$2,083,467
Developer Build Option

Project Developer has the option ("Option to Build") to assume responsibility for the design, procurement and construction of Transmission Owner Interconnection Facilities and/or Stand-Alone Network Upgrades.

If Option to Build is elected, the Project Developer must fulfill additional requirements in accordance to PJM Manual 14C, section 5.1 and PJM Manual 14H, section 8.6.2.

The cost estimates for eligible facilities and Option to Build oversight are highlighted below:

Network Upgrades
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

This scope serves to cut in 500 kV line 582 into a new three breaker ring bus substation.

$8,912,322$8,935,710$673,729$862,781$19,384,542$19,384,542
(Pending)

Remote end Network Upgrade at Surry Substation.

$116,626$55,279$18,552$7,189$197,646$197,646
(Pending)

Remote end Network Upgrade at Skiffes Creek.

$116,626$55,279$18,552$7,189$197,646$197,646
Option to Build Oversight
RTEP IDDescriptionDirectIndirectTotal Cost ($USD)Allocated Cost ($USD)
LaborMaterialsLaborMaterials
(Pending)

Option to Build ("OTB") oversite for the metering accuracy capacitor coupled voltage transformer's ("CCVT"), metering accuracy current transformer's ("CT") and associated equipment.

$31,876$0$3,557$0$35,433$35,433
(Pending)

Option to Build ("OTB") oversite for Stand Alone Network Upgrades ("SANU") required to build a 500kV three breaker ring bus to support the new solar farm built by Project Developer.

$2,424,989$1,469,256$547,931$140,058$4,582,234$4,582,234
(Pending)

Option to Build ("OTB") oversite for the Transmssion Owner Interconnection Facilities ("TOIF") which include the portion of the interconnection switching station which is associated solely with the single feed to the generating facilities collector station including disconnect switch, conductors and connectors.

$130,186$91,459$27,780$16,129$265,554$265,554
Build Option Price Comparison
Build OptionTotal CostAllocated Cost
Transmission Owner Build Option$52,956,393$52,956,393
Developer Build Option$24,663,055$24,663,055

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 96 to 97 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

Note that the TO findings were made from a conceptual review of this project. A more detailed review of the connection facilities and their cost will be identified in a future study phase. Further note that the cost estimate data provided should be considered high level estimates since it was produced without a detailed engineering review. The Project Developer will be responsible for the actual cost of construction. TO herein reserves the right to return to any issues in this document and, upon appropriate justification, request additional monies to complete any reinforcements to the transmission systems.

Remote Terminal Work: During Phase II of the PJM interconnection process, TO’s System Protection Engineering Department will review transmission line protection as well as anti-islanding required to accommodate the new generation and interconnection substation. System Protection Engineering will determine the minimal acceptable protection requirements to reliably interconnect the proposed generating facility with the transmission system. The review is based on maintaining system reliability by reviewing TO’s protection requirements with the known transmission system configuration which includes generating facilities in the area. This review may determine that transmission line protection and communication upgrades are required at remote substations.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AH1-716 was evaluated as a 650.0 MW (650.0 MW Capacity) injection in the Dominion area.

AH1-716 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 650.0 MW (650.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC108.7 %559.3B607.94
32.8
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC124.3 %548.02B681.17
32.8
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC105.53 %548.02B578.33
35.58
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC109.98 %548.02B602.71
32.8
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC124.22 %548.02B680.73
32.8
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC105.43 %548.02B577.77
35.58
GD2DVP
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.35 %571.52B590.65
33.13
GD2DVP
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC101.15 %571.52B578.11
33.08
GD2DVP
6WESTMOR-6OAKGROV 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC100.61 %571.52B575.03
33.03
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC136.05 %3940.0C5360.5
173.71
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 56722_SRT-A
BreakerAC123.17 %3940.0C4852.84
176.3
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 567_SRT-A
SingleAC119.21 %3220.44B3839.19
164.42
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC128.38 %2442.12B3135.29
238.14
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC127.71 %2442.12B3118.81
236.2
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC117.34 %3637.0C4267.68
244.81
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC117.34 %3637.0C4267.68
244.81
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC111.11 %3637.0C4041.18
237.47
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC110.07 %3637.0C4003.16
238.12
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC110.07 %3637.0C4003.16
238.12
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P2-2: ELMONT B1_SRT-S
BusAC179.17 %2858.0C5120.71
153.59
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC159.03 %4070.2B6472.73
220.27
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC146.85 %5011.0C7358.61
220.21
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC146.85 %5011.0C7358.57
220.21
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC146.4 %5011.0C7336.33
219.86
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC141.11 %4070.2B5743.4
193.96
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC159.65 %3220.44B5141.33
170.5
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC152.37 %3940.0C6003.22
172.76
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC151.78 %3940.0C5980.27
190.2
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC150.72 %3940.0C5938.23
170.34
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC130.04 %3940.0C5123.57
156.36
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC122.54 %3220.44B3946.36
164.83
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC154.87 %3220.44B4987.58
138.91
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T581_SRT-S
BreakerAC145.2 %3940.0C5721.05
141.28
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 568_SRT-S
SingleAC143.89 %3220.44B4633.88
123.08
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC142.53 %3940.0C5615.56
138.91
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H1T581_SRT-S
BreakerAC147.59 %3940.0C5814.94
136.54
IPDDVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC102.41 %3940.0C4035.06
189.31
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC124.48 %2931.0C3648.44
234.06
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC124.48 %2931.0C3648.44
234.06
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC123.45 %2931.0C3618.36
232.35
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC114.94 %2442.12B2807.07
230.29
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC111.03 %2931.0C3254.15
225.33
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC111.03 %2931.0C3254.15
225.33
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC104.63 %2442.12B2555.09
225.34
GD2DVP
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC104.8 %571.52B598.97
32.81
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC112.93 %559.3B631.64
32.81

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.7 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:607.94
MW Contribution:
32.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.865
972135AH1-637 GEN
Solar/Wind Harmer
4.388
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.598
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.941
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.803
3151201GRAVEL4
50/50
4.345
3151221GRAVEL6
50/50
4.34
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151191GRAVEL3
Adder
4.043
3151211GRAVEL5
Adder
4.043
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
315749AE2-041 GEN
50/50
4.941
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.926
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
957191AF2-013 GEN
50/50
65.703
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
CPLELTFEXP_CPLE->PJM
CLTF
1.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
TVALTFEXP_TVA->PJM
CLTF
0.74
NYPJM->LTFIMP_NY
CLTF
0.57
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
MECLTFEXP_MEC->PJM
CLTF
0.717
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.3 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:681.17
MW Contribution:
32.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
158.335
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
315749AE2-041 GEN
50/50
4.941
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.926
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.941
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.803
3151201GRAVEL4
50/50
4.345
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151221GRAVEL6
Adder
4.09
3151191GRAVEL3
Adder
4.043
3151211GRAVEL5
Adder
4.043
3141426STAFORD
Solar/Wind Helper
0.031
957191AF2-013 GEN
50/50
65.703
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.865
972135AH1-637 GEN
Solar/Wind Harmer
4.388
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.598
CPLELTFEXP_CPLE->PJM
CLTF
1.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
TVALTFEXP_TVA->PJM
CLTF
0.74
NYPJM->LTFIMP_NY
CLTF
0.57
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
MECLTFEXP_MEC->PJM
CLTF
0.717
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.53 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:578.33
MW Contribution:
35.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.968
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3150641CHESTS8
50/50
0.191
944631AF1-128 GEN
50/50
30.096
3152331SURRY 2
50/50
2.422
972135AH1-637 GEN
Solar/Wind Harmer
4.406
316337AD2-073 GEN
Solar/Wind Harmer
0.297
3141726DUNNSVL
Solar/Wind Harmer
1.048
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.999
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.972
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
972263AH1-716 GEN
50/50
35.581
3150631CHESTG8
50/50
0.372
970603AG2-384 GEN
50/50
1.269
3151201GRAVEL4
50/50
4.397
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.28
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.03
970189AG2-124 GEN
Solar/Wind Harmer
4.094
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.066
3151221GRAVEL6
Adder
4.139
3151191GRAVEL3
Adder
4.091
3151211GRAVEL5
Adder
4.091
3141426STAFORD
Solar/Wind Helper
0.029
3150331BIRCHWDA
50/50
158.939
3150351NORNECKC2
50/50
3.018
966661AG1-536 GEN
50/50
6.881
315749AE2-041 GEN
50/50
4.972
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3150921YORKTN3
50/50
2
3144216WINCHST
50/50
0.289
3150611CHESTG7
50/50
0.378
3151161SURRY 1
50/50
2.319
316223AC1-118
Solar/Wind Harmer
0.294
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.627
3141766HARMONY
Solar/Wind Harmer
1.864
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.022
3151171GRAVELC
Adder
0.796
970293AG2-193 GEN
Solar/Wind Harmer
0.602
962861AG1-135 GEN
Solar/Wind Harmer
7.557
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.421
971317AH1-138 GEN
Solar/Wind Harmer
0.632
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.606
957191AF2-013 GEN
50/50
65.957
3150341NORNECKC1
50/50
3.118
3150341NORNECKC1
50/50
3.093
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.174
316156AD2-030 GEN
Solar/Wind Harmer
0.108
315976AC1-164 GENA
Solar/Wind Harmer
0.838
316169AC1-164_GENC
Solar/Wind Harmer
0.724
3142946ENON
Solar/Wind Harmer
0.007
CPLELTFEXP_CPLE->PJM
CLTF
1.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.033
LAGNLTFEXP_LAGN->PJM
CLTF
1.196
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.02
TVALTFEXP_TVA->PJM
CLTF
0.6
NYPJM->LTFIMP_NY
CLTF
0.471
LGEELTFEXP_LGEE->PJM
CLTF
0.179
WECLTFEXP_WEC->PJM
CLTF
0.088
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.932
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.023
MECLTFEXP_MEC->PJM
CLTF
0.511
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.98 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:602.71
MW Contribution:
32.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.865
972135AH1-637 GEN
Solar/Wind Harmer
4.388
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.598
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.941
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.803
3151201GRAVEL4
50/50
4.345
3151221GRAVEL6
50/50
4.34
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151191GRAVEL3
Adder
4.043
3151211GRAVEL5
Adder
4.043
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
315749AE2-041 GEN
50/50
4.941
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.926
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
957191AF2-013 GEN
50/50
65.703
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
CPLELTFEXP_CPLE->PJM
CLTF
1.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
TVALTFEXP_TVA->PJM
CLTF
0.74
NYPJM->LTFIMP_NY
CLTF
0.57
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
MECLTFEXP_MEC->PJM
CLTF
0.717
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.22 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:680.73
MW Contribution:
32.8
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
158.335
3150351NORNECKC2
50/50
3.004
966661AG1-536 GEN
50/50
6.846
315749AE2-041 GEN
50/50
4.941
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.926
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.608
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.941
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.803
3151201GRAVEL4
50/50
4.345
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.077
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151221GRAVEL6
Adder
4.09
3151191GRAVEL3
Adder
4.043
3151211GRAVEL5
Adder
4.043
3141426STAFORD
Solar/Wind Helper
0.031
957191AF2-013 GEN
50/50
65.703
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.865
972135AH1-637 GEN
Solar/Wind Harmer
4.388
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.043
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.148
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.598
CPLELTFEXP_CPLE->PJM
CLTF
1.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.777
LAGNLTFEXP_LAGN->PJM
CLTF
1.465
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.361
TVALTFEXP_TVA->PJM
CLTF
0.74
NYPJM->LTFIMP_NY
CLTF
0.57
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.583
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.544
MECLTFEXP_MEC->PJM
CLTF
0.717
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:577.77
MW Contribution:
35.58
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3141316ARNOLDS
50/50
0.111
315759AF1-018 GEN
50/50
4.972
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
972263AH1-716 GEN
50/50
35.581
3150631CHESTG8
50/50
0.372
970603AG2-384 GEN
50/50
1.269
3151201GRAVEL4
50/50
4.397
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.28
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.03
970189AG2-124 GEN
Solar/Wind Harmer
4.094
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.066
3151221GRAVEL6
Adder
4.139
3151191GRAVEL3
Adder
4.091
3151211GRAVEL5
Adder
4.091
3141426STAFORD
Solar/Wind Helper
0.029
3150331BIRCHWDA
50/50
158.939
3150351NORNECKC2
50/50
3.018
966661AG1-536 GEN
50/50
6.881
315749AE2-041 GEN
50/50
4.972
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3150921YORKTN3
50/50
2
3144216WINCHST
50/50
0.289
3150611CHESTG7
50/50
0.378
3151161SURRY 1
50/50
2.319
316223AC1-118
Solar/Wind Harmer
0.294
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.627
3141766HARMONY
Solar/Wind Harmer
1.864
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.022
3151171GRAVELC
Adder
0.796
970293AG2-193 GEN
Solar/Wind Harmer
0.602
3150351NORNECKC2
50/50
2.968
3142433PROV 92
50/50
0.217
3142433PROV 92
50/50
0.217
3150641CHESTS8
50/50
0.191
944631AF1-128 GEN
50/50
30.096
3152331SURRY 2
50/50
2.422
972135AH1-637 GEN
Solar/Wind Harmer
4.406
316337AD2-073 GEN
Solar/Wind Harmer
0.297
3141726DUNNSVL
Solar/Wind Harmer
1.048
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.999
962861AG1-135 GEN
Solar/Wind Harmer
7.557
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.421
971317AH1-138 GEN
Solar/Wind Harmer
0.632
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.606
957191AF2-013 GEN
50/50
65.957
3150341NORNECKC1
50/50
3.118
3150341NORNECKC1
50/50
3.093
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.174
316156AD2-030 GEN
Solar/Wind Harmer
0.108
315976AC1-164 GENA
Solar/Wind Harmer
0.838
316169AC1-164_GENC
Solar/Wind Harmer
0.724
3142946ENON
Solar/Wind Harmer
0.007
CPLELTFEXP_CPLE->PJM
CLTF
1.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.033
LAGNLTFEXP_LAGN->PJM
CLTF
1.196
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.02
TVALTFEXP_TVA->PJM
CLTF
0.6
NYPJM->LTFIMP_NY
CLTF
0.471
LGEELTFEXP_LGEE->PJM
CLTF
0.179
WECLTFEXP_WEC->PJM
CLTF
0.088
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.932
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.023
MECLTFEXP_MEC->PJM
CLTF
0.511
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 6NORNECK-6SANDERS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.35 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:590.65
MW Contribution:
33.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.011
966661AG1-536 GEN
50/50
6.862
315749AE2-041 GEN
50/50
4.962
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.941
3144216WINCHST
50/50
0.281
3150611CHESTG7
50/50
0.403
3151161SURRY 1
50/50
2.315
3141873WAN 176
Solar/Wind Harmer
2.618
3141766HARMONY
Solar/Wind Harmer
1.861
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.673
3142416OLDCHRC
Solar/Wind Harmer
0.559
3151171GRAVELC
Adder
0.795
961611AG1-000B GEN
Solar/Wind Harmer
1.51
316223AC1-118
Solar/Wind Helper
2.155
3141906WESTMOR
Solar/Wind Helper
0.564
3150341NORNECKC1
50/50
3.11
3150341NORNECKC1
50/50
3.085
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.185
316156AD2-030 GEN
Solar/Wind Harmer
0.108
315976AC1-164 GENA
Solar/Wind Harmer
0.846
316169AC1-164_GENC
Solar/Wind Harmer
0.731
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.103
316033AB2-134 GEN
Solar/Wind Harmer
0
3150351NORNECKC2
50/50
2.961
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150641CHESTS8
50/50
0.205
944631AF1-128 GEN
50/50
32.152
3141726DUNNSVL
Solar/Wind Harmer
1.046
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.977
962861AG1-135 GEN
Solar/Wind Harmer
7.537
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.617
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.971
316337AD2-073 GEN
Solar/Wind Helper
2.352
315759AF1-018 GEN
50/50
4.962
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150631CHESTG8
50/50
0.397
970603AG2-384 GEN
50/50
1.356
972263AH1-716 GEN
50/50
33.131
3151201GRAVEL4
50/50
4.389
3151221GRAVEL6
50/50
4.384
3141813NORNECK
Solar/Wind Harmer
0.28
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.094
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.065
3151191GRAVEL3
Adder
4.084
3151211GRAVEL5
Adder
4.084
315697AD1-025 GEN
Solar/Wind Harmer
0.061
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
2.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.363
LAGNLTFEXP_LAGN->PJM
CLTF
1.553
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.493
TVALTFEXP_TVA->PJM
CLTF
0.785
NYPJM->LTFIMP_NY
CLTF
0.542
LGEELTFEXP_LGEE->PJM
CLTF
0.298
WECLTFEXP_WEC->PJM
CLTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.217
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.709
MECLTFEXP_MEC->PJM
CLTF
0.79
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 6SANDERS-6WESTMOR 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.15 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:578.11
MW Contribution:
33.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.01
966661AG1-536 GEN
50/50
6.86
315749AE2-041 GEN
50/50
4.959
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.939
3144216WINCHST
50/50
0.28
3150611CHESTG7
50/50
0.403
3151161SURRY 1
50/50
2.311
3141873WAN 176
Solar/Wind Harmer
2.617
3141766HARMONY
Solar/Wind Harmer
1.86
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
0.558
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316223AC1-118
Solar/Wind Helper
2.155
3141906WESTMOR
Solar/Wind Helper
0.564
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.185
316156AD2-030 GEN
Solar/Wind Harmer
0.108
315976AC1-164 GENA
Solar/Wind Harmer
0.845
316169AC1-164_GENC
Solar/Wind Harmer
0.73
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
316033AB2-134 GEN
Solar/Wind Harmer
0
3150351NORNECKC2
50/50
2.96
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.11
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.045
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.975
962861AG1-135 GEN
Solar/Wind Harmer
7.534
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.616
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.966
315759AF1-018 GEN
50/50
4.959
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150631CHESTG8
50/50
0.397
970603AG2-384 GEN
50/50
1.354
972263AH1-716 GEN
50/50
33.083
3151201GRAVEL4
50/50
4.383
3151221GRAVEL6
50/50
4.378
3141813NORNECK
Solar/Wind Harmer
0.28
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.091
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.065
3151191GRAVEL3
Adder
4.078
3151211GRAVEL5
Adder
4.078
315697AD1-025 GEN
Solar/Wind Harmer
0.06
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.278
LAGNLTFEXP_LAGN->PJM
CLTF
1.54
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.474
TVALTFEXP_TVA->PJM
CLTF
0.778
NYPJM->LTFIMP_NY
CLTF
0.546
LGEELTFEXP_LGEE->PJM
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.125
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.685
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 6WESTMOR-6OAKGROV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6WESTMOR-6OAKGROV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.61 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:575.03
MW Contribution:
33.03
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.009
966661AG1-536 GEN
50/50
6.857
315749AE2-041 GEN
50/50
4.955
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.937
3144216WINCHST
50/50
0.28
3150611CHESTG7
50/50
0.402
3151161SURRY 1
50/50
2.308
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.615
3141766HARMONY
Solar/Wind Harmer
1.858
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3150341NORNECKC1
50/50
3.108
3150341NORNECKC1
50/50
3.083
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.185
316156AD2-030 GEN
Solar/Wind Harmer
0.108
315976AC1-164 GENA
Solar/Wind Harmer
0.844
316169AC1-164_GENC
Solar/Wind Harmer
0.729
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
3150351NORNECKC2
50/50
2.959
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.063
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.045
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.972
962861AG1-135 GEN
Solar/Wind Harmer
7.531
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.429
971317AH1-138 GEN
Solar/Wind Harmer
0.615
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.603
961611AG1-000B GEN
Solar/Wind Harmer
2.961
315759AF1-018 GEN
50/50
4.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.396
970603AG2-384 GEN
50/50
1.352
972263AH1-716 GEN
50/50
33.03
3151201GRAVEL4
50/50
4.375
3151221GRAVEL6
50/50
4.37
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.089
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.065
3151191GRAVEL3
Adder
4.071
3151211GRAVEL5
Adder
4.071
3141426STAFORD
Solar/Wind Helper
0.031
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.671
3142416OLDCHRC
Solar/Wind Harmer
0.557
3151171GRAVELC
Adder
0.792
961611AG1-000B GEN
Solar/Wind Harmer
1.506
CPLELTFEXP_CPLE->PJM
CLTF
2.02
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.182
LAGNLTFEXP_LAGN->PJM
CLTF
1.526
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.452
TVALTFEXP_TVA->PJM
CLTF
0.771
NYPJM->LTFIMP_NY
CLTF
0.551
LGEELTFEXP_LGEE->PJM
CLTF
0.289
WECLTFEXP_WEC->PJM
CLTF
0.145
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.022
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.658
MECLTFEXP_MEC->PJM
CLTF
0.768
SIGELTFEXP_SIGE->PJM
CLTF
0.024

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.05 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5360.5
MW Contribution:
173.71
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
6.183
315241AE2-183_GT1
50/50
6.167
972185AH1-677 GEN
50/50
22.351
3151041BRUNSWICKG3
50/50
4.863
972187AH1-678 GEN
50/50
11.159
3150991CHESPKB
50/50
3.454
3150991CHESPKB
50/50
3.371
970933AG2-581 GEN
Solar/Wind Harmer
37.229
316294AC1-161 GEN
Solar/Wind Harmer
11.907
316185AD1-033 GEN
Solar/Wind Harmer
3.714
3145506HICKORY
Solar/Wind Harmer
-0.14
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.362
316388AE2-253 GEN
Solar/Wind Harmer
2.362
970099AG2-077 GEN
Solar/Wind Harmer
43.844
3137176SLIGO L2192
Solar/Wind Harmer
-0.139
3146456SLIGO L269
Solar/Wind Harmer
4.137
3130086AYDLETT
Solar/Wind Harmer
-0.139
3144356SAPONY
Solar/Wind Harmer
1.211
316315AB2-025 C
Solar/Wind Harmer
0.934
3146386ELIZ CT
Solar/Wind Harmer
-0.035
316431W1029_GEN1
Solar/Wind Harmer
6.21
316433W1029_GEN2
Solar/Wind Harmer
6.21
316435W1029_GEN3
Solar/Wind Harmer
6.21
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
315835AF2-110_GEN
Solar/Wind Harmer
4.237
3146376EDENTON
Solar/Wind Harmer
0.994
3146376EDENTON
Solar/Wind Harmer
0.994
315742AE1-103 GEN
Solar/Wind Harmer
7.847
315614AA2-178 GEN
Solar/Wind Harmer
3.54
316349AD2-085 GEN
Solar/Wind Harmer
2.874
316365GEN2_N
Solar/Wind Harmer
2.176
316065AD1-022 GEN
Solar/Wind Harmer
16.1
3145893MURPHYS
Solar/Wind Harmer
0.888
3145893MURPHYS
Solar/Wind Harmer
-0.057
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316140AB2-099
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
962571AG1-106 GEN
Solar/Wind Harmer
4.487
313506AB2-031 GEN
Solar/Wind Harmer
2.496
315687AD1-152 GEN
Solar/Wind Harmer
3.719
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
0.256
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145783HORNRTN
Solar/Wind Harmer
3.646
3145783HORNRTN
Solar/Wind Harmer
2.917
3145783HORNRTN
Solar/Wind Harmer
0.912
3145783HORNRTN
Solar/Wind Harmer
0.365
3145933PARMELE
Solar/Wind Harmer
-0.06
3145933PARMELE
Solar/Wind Harmer
-0.03
316083AB2-161 GEN
Solar/Wind Harmer
4.858
316005AA1-067
Solar/Wind Harmer
0.598
315724AD1-057 GEN
Solar/Wind Harmer
5.794
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
961601AG1-000A GEN
Solar/Wind Harmer
11.242
316049AB1-081 GEN
Solar/Wind Harmer
3.076
316263AC1-034 GEN
Solar/Wind Harmer
13.4
316237AB2-079_GEN
Solar/Wind Harmer
0.822
313527AB2-043 GEN
Solar/Wind Harmer
4.426
962561AG1-105 GEN
Solar/Wind Harmer
15.191
964791AG1-342 GEN
Solar/Wind Harmer
5.759
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
316118AC1-105 GEN
Solar/Wind Harmer
1.842
316248AF1-058 C
Solar/Wind Harmer
0.804
316033AB2-134 GEN
Solar/Wind Harmer
8.285
970323AG2-213 GEN
Solar/Wind Harmer
12.383
970301AG2-198 GEN
Solar/Wind Harmer
11.948
315244AE2-183_ST
50/50
10.737
963041AG1-153 GEN
50/50
9.846
3151081ELIZAR1
50/50
30.344
3151091ELIZAR2
50/50
29.817
941591AE2-156 GEN
50/50
27.672
315779AE2-040
50/50
4.313
972263AH1-716 GEN
50/50
173.708
970533AG2-339 GEN
Solar/Wind Harmer
29.4
970673AG2-436 GEN
Solar/Wind Harmer
94.298
971967AH1-528 GEN
Solar/Wind Harmer
77.483
970085AG2-068 GEN
Solar/Wind Harmer
24.437
970581AG2-369 GEN
Solar/Wind Harmer
21.016
316316AC1-027 C
Solar/Wind Harmer
1.075
316018AA1-139 ULT2
Solar/Wind Harmer
2.999
957871AF2-081 GEN
Solar/Wind Harmer
17.549
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.933
315814AE2-033 C
Solar/Wind Harmer
32.219
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
315800Z1-036_GEN1
Solar/Wind Harmer
8.306
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316486AD2-202 GEN
Solar/Wind Harmer
0.838
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
316311AC2-079 GEN
Solar/Wind Harmer
16.344
315833AF1-017_GEN
Solar/Wind Harmer
6.147
315732AD1-074 GEN1
Solar/Wind Harmer
6.532
315733AD1-074 GEN2
Solar/Wind Harmer
6.532
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
14.045
316318V4-068
Solar/Wind Harmer
0.793
3145893MURPHYS
Solar/Wind Harmer
-0.085
3145893MURPHYS
Solar/Wind Harmer
-0.032
316463AE2-346 GEN
Solar/Wind Harmer
0.51
3145513AHOSKIE
Solar/Wind Harmer
0.275
961941AG1-037 GEN
Solar/Wind Harmer
0.237
3145513AHOSKIE
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
316236AE1-162_GEN
Solar/Wind Harmer
0.947
946281AF1-292 GEN
Solar/Wind Harmer
0.703
3146043SEABORD
Solar/Wind Harmer
-0.031
971445AH1-216 GEN
Solar/Wind Harmer
19.36
315652AC1-086 GEN
Solar/Wind Harmer
35.113
3137643SOCKMAN
Solar/Wind Harmer
-0.123
316426AA2-053 GEN
Solar/Wind Harmer
3.12
316174AB2-169 GEN
Solar/Wind Harmer
4.766
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.122
970657AG2-426 GEN
Solar/Wind Harmer
1.905
316210AC1-098 GEN
Solar/Wind Harmer
4.726
316274AC1-208 GEN
Solar/Wind Harmer
3.228
970831AG2-522 GEN
Solar/Wind Harmer
14.906
3143316POE
Solar/Wind Harmer
-0.117
3145746EVERETS
Solar/Wind Harmer
-0.117
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
2.958
3151201GRAVEL4
Adder
18.995
3151221GRAVEL6
Adder
18.973
3151191GRAVEL3
Adder
18.755
3151211GRAVEL5
Adder
18.755
957861AF2-080 GEN
Solar/Wind Harmer
12.812
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
316238AB2-078_GEN
Solar/Wind Harmer
0.822
316239AB2-077_GEN
Solar/Wind Harmer
0.822
3147173SINAI
Solar/Wind Harmer
-0.027
3147243WELCO
Solar/Wind Harmer
-0.017
316382AG1-145 C
Solar/Wind Harmer
0.793
316159AE1-175 C
Solar/Wind Harmer
0.706
315697AD1-025 GEN
Solar/Wind Harmer
5.193
957831AF2-077 GEN
Solar/Wind Harmer
0.771
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3144303KENBRDG
Solar/Wind Harmer
-0.02
315839AE2-212 C
Solar/Wind Harmer
0.731
970683AG2-441 GEN
Solar/Wind Harmer
16.704
970681AG2-440 GEN
Solar/Wind Harmer
11.087
946301AF1-294 GEN
Solar/Wind Harmer
5.792
961791AG1-021 GEN
Solar/Wind Harmer
2.825
270455AD2-022 GEN
Solar/Wind Harmer
3.829
270457AD2-023 GEN
Solar/Wind Harmer
1.942
957601AF2-054 GEN
Solar/Wind Harmer
0.64
3141873WAN 176
Solar/Wind Harmer
-0.004
316059AD1-063 C
Solar/Wind Harmer
0.471
3141913WHIT STONE
Solar/Wind Harmer
-0.021
3138133OCRAN
Solar/Wind Harmer
-0.006
3143873LANEXA
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
3141813NORNECK
Solar/Wind Harmer
-0.016
316164AC1-076 GEN
Solar/Wind Helper
1.175
315651AD1-115 GEN
Solar/Wind Helper
0.76
315243AE2-183_GT3
50/50
6.183
3151051BRUNSWICKS1
50/50
10.097
3151021BRUNSWICKG1
50/50
4.863
971451AH1-221 GEN
50/50
14.769
3150981CHESPKA
50/50
4.118
3152331SURRY 2
50/50
12.573
940641AE2-051 GEN
Solar/Wind Harmer
41.384
941031AE2-094 GEN
Solar/Wind Harmer
81.975
939411AE1-173 GEN
Solar/Wind Harmer
209.802
970919AG2-571 GEN
Solar/Wind Harmer
12.566
970087AG2-069 GEN
Solar/Wind Harmer
36.656
315773AC2-141 GEN
Solar/Wind Harmer
15.407
944591AF1-124 GEN
Solar/Wind Harmer
163.705
957481AF2-042 GEN
Solar/Wind Harmer
109.611
3146456SLIGO L269
Solar/Wind Harmer
-0.035
319010AE1-072 C
Solar/Wind Harmer
7.065
316375AC2-012 GEN
Solar/Wind Harmer
12.076
316036AC1-147 C
Solar/Wind Harmer
0.94
3146516WINFALL
Solar/Wind Harmer
-0.11
3146516WINFALL
Solar/Wind Harmer
-0.034
316093AE2-104_GEN
Solar/Wind Harmer
9.855
315611Z1-036_GEN2
Solar/Wind Harmer
8.306
3130156CHOWAN
Solar/Wind Harmer
-0.033
316072AD1-144
Solar/Wind Harmer
0.674
315816AE2-034 GEN
Solar/Wind Harmer
2.655
3145663CRESWEL
Solar/Wind Harmer
-0.092
971163AH1-040 GEN
Solar/Wind Harmer
30.849
315693AD1-088 GEN
Solar/Wind Harmer
16.299
315737AD1-076 GEN
Solar/Wind Harmer
6.141
316023GEN1_S
Solar/Wind Harmer
2.176
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
8.026
3145893MURPHYS
Solar/Wind Harmer
-0.127
3145893MURPHYS
Solar/Wind Harmer
0.944
3156021HOLLOMANSOL
Solar/Wind Harmer
4.262
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145336SMITFLD
Solar/Wind Harmer
-0.125
960081AF2-299 GEN
Solar/Wind Harmer
3.532
3146263WOODLND
Solar/Wind Harmer
-0.031
315607AA1-063A GEN
Solar/Wind Harmer
3.153
316087AB2-174 GEN
Solar/Wind Harmer
4.445
3145963POPLR C
Solar/Wind Harmer
-0.031
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3147043LAWRENC
Adder
2.427
3146293MARTNCO
Solar/Wind Harmer
0.186
316381AD1-082 GEN
Solar/Wind Harmer
2.739
316129AC1-054 GEN
Solar/Wind Harmer
2.594
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
971065AG2-659 GEN
Solar/Wind Harmer
14.783
3138126ROCKLANDING
Solar/Wind Harmer
0.09
3151171GRAVELC
Adder
2.776
316494AC1-189 GEN
Solar/Wind Harmer
3.151
316319Z2-044 C
Solar/Wind Harmer
1.6
3146233WITAKRS
Solar/Wind Harmer
-0.115
961671AG1-007 GEN
Solar/Wind Harmer
0.366
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.86
316359AB2-059 GEN
Solar/Wind Harmer
3.844
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3142053HEARTS
Solar/Wind Harmer
0.336
971317AH1-138 GEN
Solar/Wind Harmer
3.512
961611AG1-000B GEN
Solar/Wind Harmer
13.784
316131AB2-060 GEN
Solar/Wind Harmer
2.915
970401AG2-262 GEN
Solar/Wind Harmer
1.76
316369SG1_INVT
Solar/Wind Harmer
4.589
315785AD2-033 C
Solar/Wind Harmer
5.703
971069AG2-661 GEN
Solar/Wind Harmer
3.933
316034AC1-036 C
Solar/Wind Harmer
0.458
316132AB2-190 GEN1
Solar/Wind Harmer
2.38
970685AG2-442 GEN
Solar/Wind Harmer
20.273
971563AH1-280 GEN
Solar/Wind Harmer
2.825
3144293JTRSVLE
Adder
0.48
3144293JTRSVLE
Adder
0.379
315671AE2-027_GEN
Solar/Wind Harmer
4.072
315662AE1-191 GEN
Solar/Wind Harmer
2.532
316280AD1-041 GEN
Solar/Wind Harmer
1.582
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.428
316314AB2-024 C
Solar/Wind Harmer
1.757
3138133OCRAN
Solar/Wind Harmer
-0.012
315975AC1-164 GENB
Solar/Wind Harmer
0.133
3142433PROV 92
Solar/Wind Harmer
-0.075
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
962861AG1-135 GEN
Solar/Wind Harmer
6.696
316404AE1-155 C
Solar/Wind Harmer
3.365
958261AF2-120 GEN
Solar/Wind Harmer
6.831
3146926FARMVIL
Solar/Wind Harmer
-0.01
944631AF1-128 GEN
Adder
73.86
964211AG1-282 GEN
Solar/Wind Harmer
0.495
3141726DUNNSVL
Solar/Wind Harmer
-0.066
3150351NORNECKC2
Adder
1.427
316447AC1-158 HLD
Solar/Wind Helper
3.566
316044AC1-158 PL1
Solar/Wind Helper
1.62
3147666LOUISA
Solar/Wind Helper
1.007
316192AB2-158 GEN
Solar/Wind Helper
1.672
970223AG2-152 GEN
Solar/Wind Harmer
14.028
958211AF2-115 GEN
Solar/Wind Harmer
3.532
3144293JTRSVLE
Adder
0.48
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.017
316156AD2-030 GEN
Solar/Wind Harmer
0.57
315666AE1-190 GEN
Solar/Wind Harmer
0.633
316240AF1-291 C
Solar/Wind Harmer
0.633
316441AF1-014 GEN
Solar/Wind Harmer
1.403
944641AF1-129 GEN
Adder
84.677
315976AC1-164 GENA
Solar/Wind Harmer
4.487
316169AC1-164_GENC
Solar/Wind Harmer
3.877
942751AE2-291 GEN
Solar/Wind Harmer
11.926
316487AF1-042 GEN
Solar/Wind Harmer
2.436
3142946ENON
Solar/Wind Harmer
-0.002
3150341NORNECKC1
Adder
1.498
3150341NORNECKC1
Adder
1.486
316045AC1-158 PL2
Solar/Wind Helper
5.186
316450AC1-158 RIC
Solar/Wind Helper
0.432
3151031BRUNSWICKG2
50/50
4.863
3151101ELIZAR3
50/50
30.733
3151161SURRY 1
50/50
10.631
944011AF1-069 GEN
Solar/Wind Harmer
25.685
970917AG2-570 GEN
Solar/Wind Harmer
99.27
944581AF1-123 GEN
Solar/Wind Harmer
163.117
944601AF1-125 GEN
Solar/Wind Harmer
160.572
3142956BIRDNECK
Solar/Wind Harmer
1.884
316017AA1-139 ULT1
Solar/Wind Harmer
2.832
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.054
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
2.03
316305AF2-043 C
Solar/Wind Harmer
1.042
316246AF1-032 C
Solar/Wind Harmer
0.699
316321Z2-027
Solar/Wind Harmer
0.929
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3144536CHRHLND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.025
316478AD1-087 GEN
Solar/Wind Harmer
2.861
315735AD1-075 GEN1
Solar/Wind Harmer
3.265
3146206CASHIE
Solar/Wind Harmer
-0.032
3156081AA2-088 GEN
Solar/Wind Harmer
10.4
3145893MURPHYS
Solar/Wind Harmer
0.222
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
3145336SMITFLD
Solar/Wind Harmer
-0.012
966621AG1-532 GEN
Solar/Wind Harmer
0.637
3146263WOODLND
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
316011AB1-132 GEN
Solar/Wind Harmer
6.519
3145963POPLR C
Solar/Wind Harmer
-0.031
316181AB2-040 GEN
Solar/Wind Harmer
4.336
316317KELFORD C
Solar/Wind Harmer
1.436
3145823KELFORD
Solar/Wind Harmer
-0.031
316190AA2-174 GEN
Solar/Wind Harmer
0.38
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
970657AG2-426 GEN
Solar/Wind Harmer
6.104
316212AC1-099_GEN
Solar/Wind Harmer
2.626
3147043LAWRENC
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
315722AD1-056 GEN
Solar/Wind Harmer
10.534
3144216WINCHST
Adder
0.991
3150921YORKTN3
Adder
6.598
3151171GRAVELC
Adder
3.65
316420AA1-050 GEN
Solar/Wind Harmer
3.317
3146233WITAKRS
Solar/Wind Harmer
0.606
3146233WITAKRS
Solar/Wind Harmer
-0.019
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
3138543CONSLDL
Solar/Wind Harmer
-0.019
961601AG1-000A GEN
Solar/Wind Harmer
11.385
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.028
315813AE1-149 C
Solar/Wind Harmer
17.763
961611AG1-000B GEN
Solar/Wind Harmer
5.881
964241AG1-285 GEN
Solar/Wind Harmer
20.609
316003AC1-222 GEN
Solar/Wind Harmer
2.469
316222AC1-221 GEN
Solar/Wind Harmer
2.522
316283AC2-100 C
Solar/Wind Harmer
2.342
315778AD1-151 GEN
Solar/Wind Harmer
22.124
970257AG2-171 GEN
Solar/Wind Harmer
9.287
971775AH1-396 GEN
Solar/Wind Harmer
1.747
959311AF2-222 GEN
Solar/Wind Harmer
25.516
971683AH1-343 GEN
Solar/Wind Harmer
10.245
316458AB2-190 GEN2
Solar/Wind Harmer
2.38
3144293JTRSVLE
Adder
0.48
3147133PAMPLIN
Solar/Wind Harmer
-0.068
3141873WAN 176
Solar/Wind Harmer
2.539
970133AG2-095 GEN
Solar/Wind Harmer
2.4
3141766HARMONY
Solar/Wind Harmer
1.858
316203AE2-005 GEN
Solar/Wind Harmer
8.774
3141843SHACKLE
Adder
0.946
316123AC1-075 GEN
Solar/Wind Harmer
2.187
942461AE2-259 GEN
Solar/Wind Harmer
2.975
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
316484AD2-074 GEN
Solar/Wind Harmer
4.655
961951AG1-038 GEN
Solar/Wind Harmer
2.436
3142946ENON
Solar/Wind Harmer
-0.006
3146926FARMVIL
Solar/Wind Harmer
-0.01
316075AC2-137 C
Solar/Wind Harmer
0.449
316077AC2-138 C
Solar/Wind Harmer
0.338
3150351NORNECKC2
Adder
1.45
3147666LOUISA
Solar/Wind Helper
0.579
CPLELTFEXP_CPLE->PJM
CLTF
17.058
CBM West 2LTFEXP_CBM-W2->PJM
CBM
60.267
LAGNLTFEXP_LAGN->PJM
CLTF
11.549
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.65
TVALTFEXP_TVA->PJM
CLTF
5.777
NYPJM->LTFIMP_NY
CLTF
2.971
LGEELTFEXP_LGEE->PJM
CLTF
1.957
WECLTFEXP_WEC->PJM
CLTF
1
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.683
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.714
MECLTFEXP_MEC->PJM
CLTF
5.447
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 56722_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56722_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.17 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4852.84
MW Contribution:
176.3
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
10.582
963041AG1-153 GEN
50/50
9.698
3151081ELIZAR1
50/50
30.032
3151091ELIZAR2
50/50
29.51
941591AE2-156 GEN
50/50
27.368
972263AH1-716 GEN
50/50
176.302
315779AE2-040
50/50
4.11
970533AG2-339 GEN
Solar/Wind Harmer
29.011
970673AG2-436 GEN
Solar/Wind Harmer
93.006
971967AH1-528 GEN
Solar/Wind Harmer
76.268
970085AG2-068 GEN
Solar/Wind Harmer
24.027
970581AG2-369 GEN
Solar/Wind Harmer
20.663
316018AA1-139 ULT2
Solar/Wind Harmer
2.972
957871AF2-081 GEN
Solar/Wind Harmer
17.39
316316AC1-027 C
Solar/Wind Harmer
1.065
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.922
3146396TANGLEW
Solar/Wind Harmer
0.627
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
315800Z1-036_GEN1
Solar/Wind Harmer
8.175
315814AE2-033 C
Solar/Wind Harmer
30.719
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316486AD2-202 GEN
Solar/Wind Harmer
0.816
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
315732AD1-074 GEN1
Solar/Wind Harmer
6.397
315733AD1-074 GEN2
Solar/Wind Harmer
6.397
3146206CASHIE
Solar/Wind Harmer
-0.031
970601AG2-382 GEN
Solar/Wind Harmer
13.732
316311AC2-079 GEN
Solar/Wind Harmer
15.72
315833AF1-017_GEN
Solar/Wind Harmer
5.91
316318V4-068
Solar/Wind Harmer
0.772
3145893MURPHYS
Solar/Wind Harmer
-0.083
3145893MURPHYS
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.496
3145513AHOSKIE
Solar/Wind Harmer
0.268
961941AG1-037 GEN
Solar/Wind Harmer
0.231
3145513AHOSKIE
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.061
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3146043SEABORD
Solar/Wind Harmer
-0.03
316174AB2-169 GEN
Solar/Wind Harmer
4.651
946281AF1-292 GEN
Solar/Wind Harmer
0.676
316236AE1-162_GEN
Solar/Wind Harmer
0.906
315652AC1-086 GEN
Solar/Wind Harmer
33.907
316426AA2-053 GEN
Solar/Wind Harmer
3.022
3137643SOCKMAN
Solar/Wind Harmer
-0.119
971445AH1-216 GEN
Solar/Wind Harmer
18.499
3145796HORNRTN
Solar/Wind Harmer
-0.095
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.118
316210AC1-098 GEN
Solar/Wind Harmer
4.582
316274AC1-208 GEN
Solar/Wind Harmer
3.127
3145746EVERETS
Solar/Wind Harmer
-0.114
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970831AG2-522 GEN
Solar/Wind Harmer
14.407
316327AA2-057 GEN
Solar/Wind Harmer
2.864
957861AF2-080 GEN
Solar/Wind Harmer
12.436
970657AG2-426 GEN
Solar/Wind Harmer
1.778
3145573BETHELC
Solar/Wind Harmer
-0.028
3145573BETHELC
Solar/Wind Harmer
-0.028
3151201GRAVEL4
Adder
17.745
3151221GRAVEL6
Adder
17.724
3151191GRAVEL3
Adder
17.52
3151211GRAVEL5
Adder
17.52
3143316POE
Solar/Wind Harmer
-0.106
316238AB2-078_GEN
Solar/Wind Harmer
0.789
316239AB2-077_GEN
Solar/Wind Harmer
0.789
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
3144303KENBRDG
Solar/Wind Harmer
-0.019
316382AG1-145 C
Solar/Wind Harmer
0.688
316159AE1-175 C
Solar/Wind Harmer
0.613
315697AD1-025 GEN
Solar/Wind Harmer
4.596
957831AF2-077 GEN
Solar/Wind Harmer
0.682
3138283WHITEMARSH
Solar/Wind Harmer
0.035
970683AG2-441 GEN
Solar/Wind Harmer
15.818
970681AG2-440 GEN
Solar/Wind Harmer
10.499
946301AF1-294 GEN
Solar/Wind Harmer
5.458
961791AG1-021 GEN
Solar/Wind Harmer
2.663
315839AE2-212 C
Solar/Wind Harmer
0.625
270455AD2-022 GEN
Solar/Wind Harmer
3.659
270457AD2-023 GEN
Solar/Wind Harmer
1.856
957601AF2-054 GEN
Solar/Wind Harmer
0.511
3141873WAN 176
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.016
3138133OCRAN
Solar/Wind Harmer
-0.005
316059AD1-063 C
Solar/Wind Harmer
0.36
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
315243AE2-183_GT3
50/50
6.094
3151051BRUNSWICKS1
50/50
9.945
3151021BRUNSWICKG1
50/50
4.79
971451AH1-221 GEN
50/50
14.547
3152331SURRY 2
50/50
12.892
3150981CHESPKA
50/50
4.071
940641AE2-051 GEN
Solar/Wind Harmer
41.046
941031AE2-094 GEN
Solar/Wind Harmer
80.89
939411AE1-173 GEN
Solar/Wind Harmer
208.136
970919AG2-571 GEN
Solar/Wind Harmer
12.361
970087AG2-069 GEN
Solar/Wind Harmer
36.041
315773AC2-141 GEN
Solar/Wind Harmer
15.581
944591AF1-124 GEN
Solar/Wind Harmer
163.065
3146456SLIGO L269
Solar/Wind Harmer
-0.035
319010AE1-072 C
Solar/Wind Harmer
6.997
316375AC2-012 GEN
Solar/Wind Harmer
11.939
316036AC1-147 C
Solar/Wind Harmer
0.929
957481AF2-042 GEN
Solar/Wind Harmer
107.048
3146516WINFALL
Solar/Wind Harmer
-0.109
3146516WINFALL
Solar/Wind Harmer
-0.034
316093AE2-104_GEN
Solar/Wind Harmer
9.65
315611Z1-036_GEN2
Solar/Wind Harmer
8.175
3130156CHOWAN
Solar/Wind Harmer
-0.033
316072AD1-144
Solar/Wind Harmer
0.658
315816AE2-034 GEN
Solar/Wind Harmer
2.606
3145663CRESWEL
Solar/Wind Harmer
-0.09
971163AH1-040 GEN
Solar/Wind Harmer
30.277
315737AD1-076 GEN
Solar/Wind Harmer
6.014
315693AD1-088 GEN
Solar/Wind Harmer
15.841
3146206CASHIE
Solar/Wind Harmer
-0.031
971547AH1-271 GEN
Solar/Wind Harmer
7.847
316023GEN1_S
Solar/Wind Harmer
2.091
3145893MURPHYS
Solar/Wind Harmer
-0.123
3145893MURPHYS
Solar/Wind Harmer
0.919
3156021HOLLOMANSOL
Solar/Wind Harmer
4.157
3146173TUNIS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3146263WOODLND
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
315607AA1-063A GEN
Solar/Wind Harmer
3.057
960081AF2-299 GEN
Solar/Wind Harmer
3.397
3145823KELFORD
Solar/Wind Harmer
-0.03
3145336SMITFLD
Solar/Wind Harmer
-0.12
316087AB2-174 GEN
Solar/Wind Harmer
4.284
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145783HORNRTN
Solar/Wind Harmer
-0.03
3146293MARTNCO
Solar/Wind Harmer
0.182
3147043LAWRENC
Adder
2.333
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316129AC1-054 GEN
Solar/Wind Harmer
2.507
971065AG2-659 GEN
Solar/Wind Harmer
14.285
316494AC1-189 GEN
Solar/Wind Harmer
3.058
961671AG1-007 GEN
Solar/Wind Harmer
0.355
3146083TARBORO
Solar/Wind Harmer
-0.028
3145493TOT1
Solar/Wind Harmer
0.833
316319Z2-044 C
Solar/Wind Harmer
1.549
3146233WITAKRS
Solar/Wind Harmer
-0.111
316381AD1-082 GEN
Solar/Wind Harmer
2.546
3138126ROCKLANDING
Solar/Wind Harmer
0.085
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.022
316359AB2-059 GEN
Solar/Wind Harmer
3.72
3142053HEARTS
Solar/Wind Harmer
0.325
3151171GRAVELC
Adder
2.593
316131AB2-060 GEN
Solar/Wind Harmer
2.796
970401AG2-262 GEN
Solar/Wind Harmer
1.692
971317AH1-138 GEN
Solar/Wind Harmer
3.234
961611AG1-000B GEN
Solar/Wind Harmer
12.635
315785AD2-033 C
Solar/Wind Harmer
5.434
316034AC1-036 C
Solar/Wind Harmer
0.435
316369SG1_INVT
Solar/Wind Harmer
4.061
970685AG2-442 GEN
Solar/Wind Harmer
19.156
971069AG2-661 GEN
Solar/Wind Harmer
3.426
971563AH1-280 GEN
Solar/Wind Harmer
2.663
3144293JTRSVLE
Adder
0.453
3144293JTRSVLE
Adder
0.357
316132AB2-190 GEN1
Solar/Wind Harmer
2.021
315671AE2-027_GEN
Solar/Wind Harmer
3.365
315662AE1-191 GEN
Solar/Wind Harmer
1.987
316280AD1-041 GEN
Solar/Wind Harmer
1.242
971777AH1-397 GEN
Solar/Wind Harmer
1.881
3138133OCRAN
Solar/Wind Harmer
-0.01
3141766HARMONY
Solar/Wind Harmer
-0.003
3146926FARMVIL
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
1.308
970223AG2-152 GEN
Solar/Wind Harmer
13.16
270016AE1-250 BESS
Solar/Wind Harmer
2.166
3142433PROV 92
Solar/Wind Harmer
-0.055
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
962861AG1-135 GEN
Solar/Wind Harmer
5.124
316404AE1-155 C
Solar/Wind Harmer
2.566
958261AF2-120 GEN
Solar/Wind Harmer
5.21
3143226MDLTHAN
Solar/Wind Helper
0.266
316447AC1-158 HLD
Solar/Wind Helper
3.088
316044AC1-158 PL1
Solar/Wind Helper
1.404
3147666LOUISA
Solar/Wind Helper
0.913
316192AB2-158 GEN
Solar/Wind Helper
1.518
315242AE2-183_GT2
50/50
6.094
315241AE2-183_GT1
50/50
6.078
972185AH1-677 GEN
50/50
22.028
3151041BRUNSWICKG3
50/50
4.79
972187AH1-678 GEN
50/50
10.991
3150991CHESPKB
50/50
3.415
3150991CHESPKB
50/50
3.333
970933AG2-581 GEN
Solar/Wind Harmer
36.582
316294AC1-161 GEN
Solar/Wind Harmer
12.042
316185AD1-033 GEN
Solar/Wind Harmer
3.684
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.342
316388AE2-253 GEN
Solar/Wind Harmer
2.342
3137176SLIGO L2192
Solar/Wind Harmer
-0.137
3146456SLIGO L269
Solar/Wind Harmer
4.098
3130086AYDLETT
Solar/Wind Harmer
-0.138
3146386ELIZ CT
Solar/Wind Harmer
-0.034
970099AG2-077 GEN
Solar/Wind Harmer
42.819
316431W1029_GEN1
Solar/Wind Harmer
6.125
316433W1029_GEN2
Solar/Wind Harmer
6.125
316435W1029_GEN3
Solar/Wind Harmer
6.125
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.033
315835AF2-110_GEN
Solar/Wind Harmer
4.149
3144356SAPONY
Solar/Wind Harmer
1.154
316315AB2-025 C
Solar/Wind Harmer
0.89
3146376EDENTON
Solar/Wind Harmer
0.978
3146376EDENTON
Solar/Wind Harmer
0.978
315614AA2-178 GEN
Solar/Wind Harmer
3.475
315742AE1-103 GEN
Solar/Wind Harmer
7.663
316065AD1-022 GEN
Solar/Wind Harmer
15.751
316349AD2-085 GEN
Solar/Wind Harmer
2.763
316365GEN2_N
Solar/Wind Harmer
2.091
3145893MURPHYS
Solar/Wind Harmer
0.864
3145893MURPHYS
Solar/Wind Harmer
-0.056
3146173TUNIS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.031
316140AB2-099
Solar/Wind Harmer
0.207
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
962571AG1-106 GEN
Solar/Wind Harmer
4.333
315687AD1-152 GEN
Solar/Wind Harmer
3.613
313506AB2-031 GEN
Solar/Wind Harmer
2.407
3145593CAROLNA
Solar/Wind Harmer
-0.03
3145593CAROLNA
Solar/Wind Harmer
-0.03
3145593CAROLNA
Solar/Wind Harmer
0.248
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145783HORNRTN
Solar/Wind Harmer
3.528
3145783HORNRTN
Solar/Wind Harmer
2.822
3145783HORNRTN
Solar/Wind Harmer
0.882
3145783HORNRTN
Solar/Wind Harmer
0.353
3145933PARMELE
Solar/Wind Harmer
-0.058
3145933PARMELE
Solar/Wind Harmer
-0.029
316005AA1-067
Solar/Wind Harmer
0.581
315724AD1-057 GEN
Solar/Wind Harmer
5.601
3145493TOT1
Solar/Wind Harmer
0.434
3145453TOT5
Solar/Wind Harmer
0.261
3145603CNETO
Solar/Wind Harmer
0.174
316083AB2-161 GEN
Solar/Wind Harmer
4.516
961601AG1-000A GEN
Solar/Wind Harmer
10.878
316049AB1-081 GEN
Solar/Wind Harmer
2.976
316263AC1-034 GEN
Solar/Wind Harmer
12.966
316237AB2-079_GEN
Solar/Wind Harmer
0.789
313527AB2-043 GEN
Solar/Wind Harmer
4.249
962561AG1-105 GEN
Solar/Wind Harmer
14.606
964791AG1-342 GEN
Solar/Wind Harmer
5.539
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
316118AC1-105 GEN
Solar/Wind Harmer
1.773
316248AF1-058 C
Solar/Wind Harmer
0.774
970323AG2-213 GEN
Solar/Wind Harmer
11.78
316033AB2-134 GEN
Solar/Wind Harmer
7.333
970301AG2-198 GEN
Solar/Wind Harmer
11.313
958211AF2-115 GEN
Solar/Wind Harmer
3.328
3144293JTRSVLE
Adder
0.453
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3147133PAMPLIN
Solar/Wind Harmer
-0.016
942751AE2-291 GEN
Solar/Wind Harmer
11.17
316156AD2-030 GEN
Solar/Wind Harmer
0.455
316240AF1-291 C
Solar/Wind Harmer
0.513
315666AE1-190 GEN
Solar/Wind Harmer
0.497
316441AF1-014 GEN
Solar/Wind Harmer
1.087
944641AF1-129 GEN
Adder
67.017
316487AF1-042 GEN
Solar/Wind Harmer
1.881
270013AE1-250 PV
Solar/Wind Harmer
2.166
316045AC1-158 PL2
Solar/Wind Helper
4.491
316450AC1-158 RIC
Solar/Wind Helper
0.374
3151031BRUNSWICKG2
50/50
4.79
3151101ELIZAR3
50/50
30.416
3151161SURRY 1
50/50
9.931
944011AF1-069 GEN
Solar/Wind Harmer
25.346
970917AG2-570 GEN
Solar/Wind Harmer
97.651
944581AF1-123 GEN
Solar/Wind Harmer
162.48
944601AF1-125 GEN
Solar/Wind Harmer
159.944
3142956BIRDNECK
Solar/Wind Harmer
1.866
316017AA1-139 ULT1
Solar/Wind Harmer
2.807
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.016
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
2.008
316305AF2-043 C
Solar/Wind Harmer
1.027
316246AF1-032 C
Solar/Wind Harmer
0.689
316321Z2-027
Solar/Wind Harmer
0.918
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3144536CHRHLND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.024
316478AD1-087 GEN
Solar/Wind Harmer
2.787
315735AD1-075 GEN1
Solar/Wind Harmer
3.198
3146206CASHIE
Solar/Wind Harmer
-0.031
3156081AA2-088 GEN
Solar/Wind Harmer
10.12
3145893MURPHYS
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.031
3146263WOODLND
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
966621AG1-532 GEN
Solar/Wind Harmer
0.613
316317KELFORD C
Solar/Wind Harmer
1.396
3145823KELFORD
Solar/Wind Harmer
-0.03
3145336SMITFLD
Solar/Wind Harmer
-0.012
316011AB1-132 GEN
Solar/Wind Harmer
6.295
316181AB2-040 GEN
Solar/Wind Harmer
4.182
316190AA2-174 GEN
Solar/Wind Harmer
0.368
3145796HORNRTN
Solar/Wind Harmer
-0.119
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145933PARMELE
Solar/Wind Harmer
-0.029
316212AC1-099_GEN
Solar/Wind Harmer
2.546
3147043LAWRENC
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
315722AD1-056 GEN
Solar/Wind Harmer
10.183
316420AA1-050 GEN
Solar/Wind Harmer
3.217
970657AG2-426 GEN
Solar/Wind Harmer
5.696
3146073TAR RVR
Solar/Wind Harmer
-0.028
3146083TARBORO
Solar/Wind Harmer
-0.028
3146233WITAKRS
Solar/Wind Harmer
0.587
3146233WITAKRS
Solar/Wind Harmer
-0.019
3138543CONSLDL
Solar/Wind Harmer
-0.018
3144216WINCHST
Adder
0.933
3150921YORKTN3
Adder
6.218
961601AG1-000A GEN
Solar/Wind Harmer
11.015
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
3.41
315813AE1-149 C
Solar/Wind Harmer
16.101
961611AG1-000B GEN
Solar/Wind Harmer
5.391
964241AG1-285 GEN
Solar/Wind Harmer
19.724
316003AC1-222 GEN
Solar/Wind Harmer
2.37
316222AC1-221 GEN
Solar/Wind Harmer
2.43
316283AC2-100 C
Solar/Wind Harmer
2.257
970257AG2-171 GEN
Solar/Wind Harmer
8.835
971775AH1-396 GEN
Solar/Wind Harmer
1.662
959311AF2-222 GEN
Solar/Wind Harmer
24.244
971683AH1-343 GEN
Solar/Wind Harmer
9.788
315778AD1-151 GEN
Solar/Wind Harmer
19.269
3144293JTRSVLE
Adder
0.453
3147133PAMPLIN
Solar/Wind Harmer
-0.064
316458AB2-190 GEN2
Solar/Wind Harmer
2.021
316123AC1-075 GEN
Solar/Wind Harmer
2.064
942461AE2-259 GEN
Solar/Wind Harmer
2.761
970133AG2-095 GEN
Solar/Wind Harmer
1.925
3141873WAN 176
Solar/Wind Harmer
2.026
316203AE2-005 GEN
Solar/Wind Harmer
6.802
3141843SHACKLE
Adder
0.733
3141766HARMONY
Solar/Wind Harmer
1.422
3146926FARMVIL
Solar/Wind Harmer
-0.009
316484AD2-074 GEN
Solar/Wind Harmer
3.594
961951AG1-038 GEN
Solar/Wind Harmer
1.881
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
3147666LOUISA
Solar/Wind Helper
0.525
3143873LANEXA
Solar/Wind Harmer
-0.009
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
CPLELTFEXP_CPLE->PJM
CLTF
16.412
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.553
LAGNLTFEXP_LAGN->PJM
CLTF
10.604
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.873
TVALTFEXP_TVA->PJM
CLTF
5.289
NYPJM->LTFIMP_NY
CLTF
2.594
LGEELTFEXP_LGEE->PJM
CLTF
1.694
WECLTFEXP_WEC->PJM
CLTF
0.868
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.958
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.952
MECLTFEXP_MEC->PJM
CLTF
4.82
SIGELTFEXP_SIGE->PJM
CLTF
0.143

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.21 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3839.19
MW Contribution:
164.42
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.63
3151101ELIZAR3
50/50
28.603
3151161SURRY 1
50/50
9.064
944011AF1-069 GEN
Solar/Wind Harmer
22.342
970917AG2-570 GEN
Solar/Wind Harmer
29.866
944581AF1-123 GEN
Solar/Wind Harmer
67.511
944601AF1-125 GEN
Solar/Wind Harmer
66.471
316017AA1-139 ULT1
Solar/Wind Harmer
0.156
3146456SLIGO L269
Solar/Wind Harmer
0.291
971153AH1-033 GEN
Solar/Wind Harmer
3.363
3144873MCLAUGH
Solar/Wind Harmer
0.007
316321Z2-027
Solar/Wind Harmer
0.051
316246AF1-032 C
Solar/Wind Harmer
0.127
3146516WINFALL
Solar/Wind Harmer
0.283
3146626S HERTFORD
Solar/Wind Harmer
0.282
3144536CHRHLND
Solar/Wind Harmer
0.041
316478AD1-087 GEN
Solar/Wind Harmer
0.96
3146376EDENTON
Solar/Wind Harmer
0.277
3145273HOLLAND
Solar/Wind Harmer
0.205
315735AD1-075 GEN1
Solar/Wind Harmer
0.76
3146206CASHIE
Solar/Wind Harmer
0.264
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.261
3146173TUNIS
Solar/Wind Harmer
0.26
3146263WOODLND
Solar/Wind Harmer
0.257
3145963POPLR C
Solar/Wind Harmer
0.257
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
316011AB1-132 GEN
Solar/Wind Harmer
4.632
3145823KELFORD
Solar/Wind Harmer
0.255
316181AB2-040 GEN
Solar/Wind Harmer
0.362
3145796HORNRTN
Solar/Wind Harmer
1.009
3145796HORNRTN
Solar/Wind Harmer
0.252
3145933PARMELE
Solar/Wind Harmer
0.248
3145336SMITFLD
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
1.279
3147043LAWRENC
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
315722AD1-056 GEN
Solar/Wind Harmer
8.402
3146073TAR RVR
Solar/Wind Harmer
0.238
3146083TARBORO
Solar/Wind Harmer
0.238
3146233WITAKRS
Solar/Wind Harmer
1.197
3146233WITAKRS
Solar/Wind Harmer
0.162
3138543CONSLDL
Solar/Wind Harmer
0.157
961601AG1-000A GEN
Solar/Wind Harmer
16.741
3145543BTLEBRO
Solar/Wind Harmer
0.235
3145543BTLEBRO
Solar/Wind Harmer
0.235
971623AH1-311 GEN
Solar/Wind Harmer
0.471
970657AG2-426 GEN
Solar/Wind Harmer
5.23
3151171GRAVELC
Adder
3.113
3144216WINCHST
Adder
0.838
3150921YORKTN3
Adder
5.572
964241AG1-285 GEN
Solar/Wind Harmer
14.369
315813AE1-149 C
Solar/Wind Harmer
11.274
315242AE2-183_GT2
50/50
5.891
315241AE2-183_GT1
50/50
5.875
315244AE2-183_ST
50/50
10.23
963041AG1-153 GEN
50/50
9.375
3151081ELIZAR1
50/50
28.242
3151091ELIZAR2
50/50
27.751
941591AE2-156 GEN
50/50
25.729
972263AH1-716 GEN
50/50
164.423
315779AE2-040
50/50
3.911
970533AG2-339 GEN
Solar/Wind Harmer
28.051
970673AG2-436 GEN
Solar/Wind Harmer
45.53
971967AH1-528 GEN
Solar/Wind Harmer
55.835
970085AG2-068 GEN
Solar/Wind Harmer
17.635
970581AG2-369 GEN
Solar/Wind Harmer
15.166
957871AF2-081 GEN
Solar/Wind Harmer
14.516
316316AC1-027 C
Solar/Wind Harmer
0.277
3146406KITTY HAWK
Solar/Wind Harmer
0.036
313526AB2-022
Solar/Wind Harmer
0.153
3146396TANGLEW
Solar/Wind Harmer
0.788
3145176PASQUOTANK
Solar/Wind Harmer
0.177
3146486SUNBURY
Solar/Wind Harmer
0.284
3146486SUNBURY
Solar/Wind Harmer
0.284
315814AE2-033 C
Solar/Wind Harmer
22.101
316486AD2-202 GEN
Solar/Wind Harmer
0.282
3130156CHOWAN
Solar/Wind Harmer
0.277
315243AE2-183_GT3
50/50
5.891
3151051BRUNSWICKS1
50/50
9.613
3151021BRUNSWICKG1
50/50
4.63
971451AH1-221 GEN
50/50
14.062
3152331SURRY 2
50/50
12.09
3150981CHESPKA
50/50
3.827
940641AE2-051 GEN
Solar/Wind Harmer
30.044
941031AE2-094 GEN
Solar/Wind Harmer
68.38
939411AE1-173 GEN
Solar/Wind Harmer
151.626
970919AG2-571 GEN
Solar/Wind Harmer
11.946
970087AG2-069 GEN
Solar/Wind Harmer
26.453
315773AC2-141 GEN
Solar/Wind Harmer
11.439
944591AF1-124 GEN
Solar/Wind Harmer
67.751
957481AF2-042 GEN
Solar/Wind Harmer
78.462
3146456SLIGO L269
Solar/Wind Harmer
0.291
319010AE1-072 C
Solar/Wind Harmer
1.45
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.051
3146516WINFALL
Solar/Wind Harmer
0.918
3146516WINFALL
Solar/Wind Harmer
0.283
316093AE2-104_GEN
Solar/Wind Harmer
4.669
3130156CHOWAN
Solar/Wind Harmer
0.277
315693AD1-088 GEN
Solar/Wind Harmer
13.048
315816AE2-034 GEN
Solar/Wind Harmer
1.159
3145663CRESWEL
Solar/Wind Harmer
0.76
971163AH1-040 GEN
Solar/Wind Harmer
21.74
316072AD1-144
Solar/Wind Harmer
0.096
315737AD1-076 GEN
Solar/Wind Harmer
3.426
3146206CASHIE
Solar/Wind Harmer
0.264
971547AH1-271 GEN
Solar/Wind Harmer
5.645
316023GEN1_S
Solar/Wind Harmer
0.585
3145893MURPHYS
Solar/Wind Harmer
1.044
3145893MURPHYS
Solar/Wind Harmer
1.161
3156021HOLLOMANSOL
Solar/Wind Harmer
1.175
3146173TUNIS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.259
3146263WOODLND
Solar/Wind Harmer
0.257
3145963POPLR C
Solar/Wind Harmer
0.257
315607AA1-063A GEN
Solar/Wind Harmer
0.516
960081AF2-299 GEN
Solar/Wind Harmer
2.459
3145823KELFORD
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.833
3145796HORNRTN
Solar/Wind Harmer
0.252
3145783HORNRTN
Solar/Wind Harmer
0.252
3146293MARTNCO
Solar/Wind Harmer
0.23
3145336SMITFLD
Solar/Wind Harmer
0.992
3147043LAWRENC
Adder
2.228
316129AC1-054 GEN
Solar/Wind Harmer
0.912
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
971065AG2-659 GEN
Solar/Wind Harmer
10.392
316494AC1-189 GEN
Solar/Wind Harmer
0.815
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.238
3145493TOT1
Solar/Wind Harmer
1.061
3146233WITAKRS
Solar/Wind Harmer
0.949
3145543BTLEBRO
Solar/Wind Harmer
0.235
3145543BTLEBRO
Solar/Wind Harmer
0.188
316359AB2-059 GEN
Solar/Wind Harmer
0.836
3142053HEARTS
Solar/Wind Harmer
0.414
316381AD1-082 GEN
Solar/Wind Harmer
0.233
3151171GRAVELC
Adder
2.367
3138126ROCKLANDING
Solar/Wind Harmer
0.102
970401AG2-262 GEN
Solar/Wind Harmer
1.303
316131AB2-060 GEN
Solar/Wind Harmer
0.691
961611AG1-000B GEN
Solar/Wind Harmer
10.821
315785AD2-033 C
Solar/Wind Harmer
1.657
971317AH1-138 GEN
Solar/Wind Harmer
1.51
316034AC1-036 C
Solar/Wind Harmer
0.013
970685AG2-442 GEN
Solar/Wind Harmer
13.927
971563AH1-280 GEN
Solar/Wind Harmer
1.935
3144293JTRSVLE
Adder
0.433
3144293JTRSVLE
Adder
0.342
971069AG2-661 GEN
Solar/Wind Harmer
3.033
316132AB2-190 GEN1
Solar/Wind Harmer
0.832
315671AE2-027_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Harmer
0.081
970223AG2-152 GEN
Solar/Wind Harmer
8.938
3143226MDLTHAN
Solar/Wind Helper
0.285
316447AC1-158 HLD
Solar/Wind Helper
3.026
316044AC1-158 PL1
Solar/Wind Helper
1.375
3147666LOUISA
Solar/Wind Helper
0.895
972185AH1-677 GEN
50/50
21.295
3151041BRUNSWICKG3
50/50
4.63
972187AH1-678 GEN
50/50
10.625
3150991CHESPKB
50/50
3.21
3150991CHESPKB
50/50
3.133
970933AG2-581 GEN
Solar/Wind Harmer
26.844
316294AC1-161 GEN
Solar/Wind Harmer
5.414
970099AG2-077 GEN
Solar/Wind Harmer
31.385
3145506HICKORY
Solar/Wind Harmer
1.172
3145506HICKORY
Solar/Wind Harmer
0.703
3145506HICKORY
Solar/Wind Harmer
0.176
316339AD2-160 GEN
Solar/Wind Harmer
0.467
316388AE2-253 GEN
Solar/Wind Harmer
0.908
3137176SLIGO L2192
Solar/Wind Harmer
1.158
3146456SLIGO L269
Solar/Wind Harmer
5.148
3130086AYDLETT
Solar/Wind Harmer
1.161
3146386ELIZ CT
Solar/Wind Harmer
0.287
3146516WINFALL
Solar/Wind Harmer
0.283
3146516WINFALL
Solar/Wind Harmer
0.283
3146516WINFALL
Solar/Wind Harmer
0.283
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
3144356SAPONY
Solar/Wind Harmer
2.344
316315AB2-025 C
Solar/Wind Harmer
0.224
315835AF2-110_GEN
Solar/Wind Harmer
1.905
3146376EDENTON
Solar/Wind Harmer
1.231
3146376EDENTON
Solar/Wind Harmer
1.231
315614AA2-178 GEN
Solar/Wind Harmer
1.546
315742AE1-103 GEN
Solar/Wind Harmer
4.047
316065AD1-022 GEN
Solar/Wind Harmer
12.226
316365GEN2_N
Solar/Wind Harmer
0.585
3145893MURPHYS
Solar/Wind Harmer
1.748
3145893MURPHYS
Solar/Wind Harmer
0.47
3146173TUNIS
Solar/Wind Harmer
0.26
3146173TUNIS
Solar/Wind Harmer
0.26
316140AB2-099
Solar/Wind Harmer
0.092
316349AD2-085 GEN
Solar/Wind Harmer
0.173
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
962571AG1-106 GEN
Solar/Wind Harmer
3.633
313506AB2-031 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.253
3145593CAROLNA
Solar/Wind Harmer
0.253
3145593CAROLNA
Solar/Wind Harmer
0.315
3145796HORNRTN
Solar/Wind Harmer
0.757
3145783HORNRTN
Solar/Wind Harmer
4.482
3145783HORNRTN
Solar/Wind Harmer
3.585
3145783HORNRTN
Solar/Wind Harmer
1.12
3145783HORNRTN
Solar/Wind Harmer
0.448
3145933PARMELE
Solar/Wind Harmer
0.497
3145933PARMELE
Solar/Wind Harmer
0.248
316005AA1-067
Solar/Wind Harmer
0.261
315724AD1-057 GEN
Solar/Wind Harmer
4.687
3145493TOT1
Solar/Wind Harmer
0.553
3145453TOT5
Solar/Wind Harmer
0.332
3145603CNETO
Solar/Wind Harmer
0.221
961601AG1-000A GEN
Solar/Wind Harmer
4.185
316049AB1-081 GEN
Solar/Wind Harmer
1.339
316263AC1-034 GEN
Solar/Wind Harmer
8.943
962561AG1-105 GEN
Solar/Wind Harmer
10.668
3146843MT LREL
Solar/Wind Harmer
0.222
3146843MT LREL
Solar/Wind Harmer
0.222
964791AG1-342 GEN
Solar/Wind Harmer
4.263
316118AC1-105 GEN
Solar/Wind Harmer
0.567
970323AG2-213 GEN
Solar/Wind Harmer
8.574
970301AG2-198 GEN
Solar/Wind Harmer
8.24
958211AF2-115 GEN
Solar/Wind Harmer
2.177
3144293JTRSVLE
Adder
0.433
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3147133PAMPLIN
Solar/Wind Harmer
0.175
3147133PAMPLIN
Solar/Wind Harmer
0.14
942751AE2-291 GEN
Solar/Wind Harmer
8.202
944641AF1-129 GEN
Adder
58.82
316156AD2-030 GEN
Solar/Wind Harmer
0.087
316045AC1-158 PL2
Solar/Wind Helper
4.4
316450AC1-158 RIC
Solar/Wind Helper
0.367
3130156CHOWAN
Solar/Wind Harmer
0.277
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.522
315733AD1-074 GEN2
Solar/Wind Harmer
1.522
3146206CASHIE
Solar/Wind Harmer
0.264
970601AG2-382 GEN
Solar/Wind Harmer
9.88
3145893MURPHYS
Solar/Wind Harmer
0.705
3145893MURPHYS
Solar/Wind Harmer
0.261
316463AE2-346 GEN
Solar/Wind Harmer
0.222
3145513AHOSKIE
Solar/Wind Harmer
0.543
3145513AHOSKIE
Solar/Wind Harmer
0.259
316311AC2-079 GEN
Solar/Wind Harmer
7.454
3145683EARLEYS
Solar/Wind Harmer
0.518
3145683EARLEYS
Solar/Wind Harmer
0.259
3145683EARLEYS
Solar/Wind Harmer
0.259
3146043SEABORD
Solar/Wind Harmer
0.257
315652AC1-086 GEN
Solar/Wind Harmer
28.089
316426AA2-053 GEN
Solar/Wind Harmer
0.85
3137643SOCKMAN
Solar/Wind Harmer
1.014
3145796HORNRTN
Solar/Wind Harmer
0.808
3145796HORNRTN
Solar/Wind Harmer
0.101
3146033SCOT NK
Solar/Wind Harmer
1.004
316210AC1-098 GEN
Solar/Wind Harmer
2.293
316274AC1-208 GEN
Solar/Wind Harmer
1.271
971445AH1-216 GEN
Solar/Wind Harmer
17.305
970831AG2-522 GEN
Solar/Wind Harmer
10.47
3145746EVERETS
Solar/Wind Harmer
0.972
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
316327AA2-057 GEN
Solar/Wind Harmer
0.357
957861AF2-080 GEN
Solar/Wind Harmer
10.4
3145573BETHELC
Solar/Wind Harmer
0.238
3145573BETHELC
Solar/Wind Harmer
0.238
970657AG2-426 GEN
Solar/Wind Harmer
1.712
3143316POE
Solar/Wind Harmer
0.885
3151201GRAVEL4
Adder
16.197
3151221GRAVEL6
Adder
16.178
3151191GRAVEL3
Adder
15.992
3151211GRAVEL5
Adder
15.992
3147173SINAI
Solar/Wind Harmer
0.221
3147243WELCO
Solar/Wind Harmer
0.138
3144303KENBRDG
Solar/Wind Harmer
0.161
970683AG2-441 GEN
Solar/Wind Harmer
11.504
970681AG2-440 GEN
Solar/Wind Harmer
7.636
946301AF1-294 GEN
Solar/Wind Harmer
3.58
961791AG1-021 GEN
Solar/Wind Harmer
1.741
315697AD1-025 GEN
Solar/Wind Harmer
0.194
3138283WHITEMARSH
Solar/Wind Harmer
0.04
316159AE1-175 C
Solar/Wind Harmer
0.146
3141873WAN 176
Solar/Wind Harmer
0.024
316222AC1-221 GEN
Solar/Wind Harmer
0.851
961611AG1-000B GEN
Solar/Wind Harmer
5.502
316283AC2-100 C
Solar/Wind Harmer
0.402
970257AG2-171 GEN
Solar/Wind Harmer
6.43
971775AH1-396 GEN
Solar/Wind Harmer
0.322
959311AF2-222 GEN
Solar/Wind Harmer
17.606
971683AH1-343 GEN
Solar/Wind Harmer
7.171
3144293JTRSVLE
Adder
0.433
3147133PAMPLIN
Solar/Wind Harmer
0.548
315778AD1-151 GEN
Solar/Wind Harmer
13.647
316123AC1-075 GEN
Solar/Wind Harmer
0.22
942461AE2-259 GEN
Solar/Wind Harmer
0
316458AB2-190 GEN2
Solar/Wind Harmer
0.832
3146926FARMVIL
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
1.244
3141873WAN 176
Solar/Wind Harmer
2.11
3147666LOUISA
Solar/Wind Helper
0.515
CPLELTFEXP_CPLE->PJM
CLTF
15.818
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.33
LAGNLTFEXP_LAGN->PJM
CLTF
10.328
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.69
TVALTFEXP_TVA->PJM
CLTF
5.152
NYPJM->LTFIMP_NY
CLTF
2.487
LGEELTFEXP_LGEE->PJM
CLTF
1.675
WECLTFEXP_WEC->PJM
CLTF
0.859
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.727
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.512
MECLTFEXP_MEC->PJM
CLTF
4.743
SIGELTFEXP_SIGE->PJM
CLTF
0.141

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.38 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3135.29
MW Contribution:
238.14
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150921YORKTN3
50/50
9.827
3144216WINCHST
50/50
1.452
3151101ELIZAR3
50/50
34.636
3151161SURRY 1
50/50
13.076
944581AF1-123 GEN
Solar/Wind Harmer
80.334
944601AF1-125 GEN
Solar/Wind Harmer
79.096
3144873MCLAUGH
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.185
3144536CHRHLND
Solar/Wind Harmer
0.052
3146456SLIGO L269
Solar/Wind Harmer
0.345
971153AH1-033 GEN
Solar/Wind Harmer
3.994
316246AF1-032 C
Solar/Wind Harmer
0.151
316321Z2-027
Solar/Wind Harmer
0.06
3145336SMITFLD
Solar/Wind Harmer
0.133
3146516WINFALL
Solar/Wind Harmer
0.33
3146626S HERTFORD
Solar/Wind Harmer
0.326
3151171GRAVELC
Adder
4.49
3141766HARMONY
Solar/Wind Harmer
4.275
3141873WAN 176
Solar/Wind Harmer
5.649
3146376EDENTON
Solar/Wind Harmer
0.313
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
1.601
3145273HOLLAND
Solar/Wind Harmer
0.235
961611AG1-000B GEN
Solar/Wind Harmer
8.247
315735AD1-075 GEN1
Solar/Wind Harmer
0.823
3142946ENON
Solar/Wind Harmer
0.095
970657AG2-426 GEN
Solar/Wind Harmer
6.37
315778AD1-151 GEN
Solar/Wind Harmer
22.672
3146206CASHIE
Solar/Wind Harmer
0.282
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
3156081AA2-088 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.074
944011AF1-069 GEN
Solar/Wind Harmer
16.455
316458AB2-190 GEN2
Solar/Wind Harmer
1.455
3145893MURPHYS
Solar/Wind Harmer
0.456
3145893MURPHYS
Solar/Wind Harmer
0.272
3146173TUNIS
Solar/Wind Harmer
0.269
3145963POPLR C
Solar/Wind Harmer
0.267
972263AH1-716 GEN
50/50
238.136
3151081ELIZAR1
50/50
34.198
3151091ELIZAR2
50/50
33.604
941591AE2-156 GEN
50/50
31.212
3151201GRAVEL4
50/50
24.793
316159AE1-175 C
Solar/Wind Harmer
0.312
316316AC1-027 C
Solar/Wind Harmer
0.334
957871AF2-081 GEN
Solar/Wind Harmer
17.268
3146406KITTY HAWK
Solar/Wind Harmer
0.043
3138283WHITEMARSH
Solar/Wind Harmer
0.08
313526AB2-022
Solar/Wind Harmer
0.181
3146396TANGLEW
Solar/Wind Harmer
0.925
3145176PASQUOTANK
Solar/Wind Harmer
0.208
3146486SUNBURY
Solar/Wind Harmer
0.335
3146486SUNBURY
Solar/Wind Harmer
0.335
971445AH1-216 GEN
Solar/Wind Harmer
23.343
3151221GRAVEL6
Adder
23.338
3151191GRAVEL3
Adder
23.069
3151211GRAVEL5
Adder
23.069
3141873WAN 176
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.314
3130156CHOWAN
Solar/Wind Harmer
0.314
970189AG2-124 GEN
Solar/Wind Harmer
9.288
316311AC2-079 GEN
Solar/Wind Harmer
8.918
3141913WHIT STONE
Solar/Wind Harmer
0.31
3138133OCRAN
Solar/Wind Harmer
0.092
3143873LANEXA
Solar/Wind Harmer
0.184
3141783LANCAST
Solar/Wind Harmer
0.182
3141783LANCAST
Solar/Wind Harmer
0.121
3130546PLYMOUTH
Solar/Wind Harmer
0.291
315697AD1-025 GEN
Solar/Wind Harmer
0.313
315732AD1-074 GEN1
Solar/Wind Harmer
1.648
315733AD1-074 GEN2
Solar/Wind Harmer
1.648
970657AG2-426 GEN
Solar/Wind Harmer
2.085
3146206CASHIE
Solar/Wind Harmer
0.282
970601AG2-382 GEN
Solar/Wind Harmer
10.547
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
970533AG2-339 GEN
Solar/Wind Harmer
20.659
3145893MURPHYS
Solar/Wind Harmer
0.735
3145893MURPHYS
Solar/Wind Harmer
0.272
970673AG2-436 GEN
Solar/Wind Harmer
33.602
316463AE2-346 GEN
Solar/Wind Harmer
0.229
3145513AHOSKIE
Solar/Wind Harmer
0.561
3145513AHOSKIE
Solar/Wind Harmer
0.268
3145683EARLEYS
Solar/Wind Harmer
0.533
3145683EARLEYS
Solar/Wind Harmer
0.266
3145683EARLEYS
Solar/Wind Harmer
0.266
3141813NORNECK
Solar/Wind Harmer
0.265
971967AH1-528 GEN
Solar/Wind Harmer
41.637
3146043SEABORD
Solar/Wind Harmer
0.257
315814AE2-033 C
Solar/Wind Harmer
20.065
3146033SCOT NK
Solar/Wind Harmer
0.988
970085AG2-068 GEN
Solar/Wind Harmer
13.176
970581AG2-369 GEN
Solar/Wind Harmer
11.332
316426AA2-053 GEN
Solar/Wind Harmer
0.824
3143316POE
Solar/Wind Harmer
0.964
315652AC1-086 GEN
Solar/Wind Harmer
26.755
3137643SOCKMAN
Solar/Wind Harmer
0.963
3145796HORNRTN
Solar/Wind Harmer
0.765
3145796HORNRTN
Solar/Wind Harmer
0.096
316210AC1-098 GEN
Solar/Wind Harmer
2.211
3145746EVERETS
Solar/Wind Harmer
0.95
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316274AC1-208 GEN
Solar/Wind Harmer
1.209
957861AF2-080 GEN
Solar/Wind Harmer
9.942
316327AA2-057 GEN
Solar/Wind Harmer
0.334
3145573BETHELC
Solar/Wind Harmer
0.223
3145573BETHELC
Solar/Wind Harmer
0.223
970831AG2-522 GEN
Solar/Wind Harmer
9.419
316486AD2-202 GEN
Solar/Wind Harmer
0.221
3144303KENBRDG
Solar/Wind Harmer
0.145
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
971285AH1-108 GEN
Adder
1.339
970683AG2-441 GEN
Solar/Wind Harmer
10.637
970681AG2-440 GEN
Solar/Wind Harmer
7.06
946301AF1-294 GEN
Solar/Wind Harmer
3.382
961791AG1-021 GEN
Solar/Wind Harmer
1.645
316233AE1-074 FULL
Solar/Wind Harmer
0.136
971281AH1-106 GEN
Solar/Wind Harmer
2.357
971283AH1-107 GEN
Solar/Wind Harmer
2.357
944491AF1-114 GEN
Solar/Wind Harmer
0
316258AE1-075 C
Solar/Wind Harmer
0.101
971845AH1-439 GEN
Solar/Wind Harmer
5.382
3150991CHESPKB
50/50
3.897
3150991CHESPKB
50/50
3.803
316294AC1-161 GEN
Solar/Wind Harmer
6.584
3145506HICKORY
Solar/Wind Harmer
1.399
3145506HICKORY
Solar/Wind Harmer
0.84
3145506HICKORY
Solar/Wind Harmer
0.21
316339AD2-160 GEN
Solar/Wind Harmer
0.556
316388AE2-253 GEN
Solar/Wind Harmer
1.081
3137176SLIGO L2192
Solar/Wind Harmer
1.375
3146456SLIGO L269
Solar/Wind Harmer
6.114
3130086AYDLETT
Solar/Wind Harmer
1.378
315976AC1-164 GENA
Solar/Wind Harmer
3.57
316169AC1-164_GENC
Solar/Wind Harmer
3.085
3146386ELIZ CT
Solar/Wind Harmer
0.338
3146516WINFALL
Solar/Wind Harmer
0.33
3146516WINFALL
Solar/Wind Harmer
0.33
3146516WINFALL
Solar/Wind Harmer
0.33
315835AF2-110_GEN
Solar/Wind Harmer
2.256
3146626S HERTFORD
Solar/Wind Harmer
0.326
3146626S HERTFORD
Solar/Wind Harmer
0.326
316156AD2-030 GEN
Solar/Wind Harmer
0.233
3146376EDENTON
Solar/Wind Harmer
1.394
3146376EDENTON
Solar/Wind Harmer
1.394
316349AD2-085 GEN
Solar/Wind Harmer
0.207
315742AE1-103 GEN
Solar/Wind Harmer
4.564
315614AA2-178 GEN
Solar/Wind Harmer
1.712
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.028
316065AD1-022 GEN
Solar/Wind Harmer
13.123
3145893MURPHYS
Solar/Wind Harmer
1.823
3145893MURPHYS
Solar/Wind Harmer
0.49
3146173TUNIS
Solar/Wind Harmer
0.269
3146173TUNIS
Solar/Wind Harmer
0.269
316140AB2-099
Solar/Wind Harmer
0.095
3150341NORNECKC1
Adder
2.776
3150341NORNECKC1
Adder
2.754
972185AH1-677 GEN
Adder
14.86
972187AH1-678 GEN
Adder
7.433
3144356SAPONY
Solar/Wind Harmer
2.125
316315AB2-025 C
Solar/Wind Harmer
0.203
970933AG2-581 GEN
Solar/Wind Harmer
20.197
3145933PARMELE
Solar/Wind Harmer
0.495
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316365GEN2_N
Solar/Wind Harmer
0.546
962571AG1-106 GEN
Solar/Wind Harmer
3.461
3145593CAROLNA
Solar/Wind Harmer
0.242
3145593CAROLNA
Solar/Wind Harmer
0.242
3145593CAROLNA
Solar/Wind Harmer
0.301
3145783HORNRTN
Solar/Wind Harmer
4.282
3145783HORNRTN
Solar/Wind Harmer
3.426
3145783HORNRTN
Solar/Wind Harmer
1.071
3145783HORNRTN
Solar/Wind Harmer
0.428
313506AB2-031 GEN
Solar/Wind Harmer
0.736
3145796HORNRTN
Solar/Wind Harmer
0.717
316005AA1-067
Solar/Wind Harmer
0.255
970099AG2-077 GEN
Solar/Wind Harmer
24.343
315724AD1-057 GEN
Solar/Wind Harmer
4.351
3145493TOT1
Solar/Wind Harmer
0.518
3145453TOT5
Solar/Wind Harmer
0.311
3145603CNETO
Solar/Wind Harmer
0.207
961601AG1-000A GEN
Solar/Wind Harmer
3.822
316049AB1-081 GEN
Solar/Wind Harmer
1.222
316263AC1-034 GEN
Solar/Wind Harmer
8.163
944641AF1-129 GEN
Adder
99.85
962561AG1-105 GEN
Solar/Wind Harmer
8.928
964791AG1-342 GEN
Solar/Wind Harmer
3.543
3146843MT LREL
Solar/Wind Harmer
0.184
3146843MT LREL
Solar/Wind Harmer
0.184
3150691DARBY 3
Adder
13.226
3150701DARBY 4
Adder
13.195
3150681DARBY 2
Adder
13.18
3150671DARBY 1
Adder
13.164
970323AG2-213 GEN
Solar/Wind Harmer
7.762
316118AC1-105 GEN
Solar/Wind Harmer
0.464
970301AG2-198 GEN
Solar/Wind Harmer
7.522
971223AH1-071 GEN
Solar/Wind Harmer
1.834
958211AF2-115 GEN
Solar/Wind Harmer
2.057
3144293JTRSVLE
Adder
0.409
3143526WINTERP
Solar/Wind Harmer
0.883
316312AB1-027
Solar/Wind Harmer
0.301
3152331SURRY 2
50/50
17.122
3150981CHESPKA
50/50
4.645
315773AC2-141 GEN
Solar/Wind Harmer
13.911
971317AH1-138 GEN
Solar/Wind Harmer
2.748
3138126ROCKLANDING
Solar/Wind Harmer
0.167
944591AF1-124 GEN
Solar/Wind Harmer
80.619
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.062
3146456SLIGO L269
Solar/Wind Harmer
0.345
319010AE1-072 C
Solar/Wind Harmer
1.721
316072AD1-144
Solar/Wind Harmer
0.121
315975AC1-164 GENB
Solar/Wind Harmer
0.106
3145336SMITFLD
Solar/Wind Harmer
1.33
3146516WINFALL
Solar/Wind Harmer
1.068
3146516WINFALL
Solar/Wind Harmer
0.33
316093AE2-104_GEN
Solar/Wind Harmer
5.529
3151171GRAVELC
Adder
3.415
3141766HARMONY
Solar/Wind Harmer
0.064
939411AE1-173 GEN
Solar/Wind Harmer
134.476
3130156CHOWAN
Solar/Wind Harmer
0.314
971777AH1-397 GEN
Solar/Wind Harmer
0.827
961611AG1-000B GEN
Solar/Wind Harmer
16.22
3138133OCRAN
Solar/Wind Harmer
0.185
940641AE2-051 GEN
Solar/Wind Harmer
24.223
315816AE2-034 GEN
Solar/Wind Harmer
1.284
3145663CRESWEL
Solar/Wind Harmer
0.842
971163AH1-040 GEN
Solar/Wind Harmer
24.077
315737AD1-076 GEN
Solar/Wind Harmer
3.712
971069AG2-661 GEN
Solar/Wind Harmer
5.038
962861AG1-135 GEN
Solar/Wind Harmer
9.047
3146206CASHIE
Solar/Wind Harmer
0.282
971547AH1-271 GEN
Solar/Wind Harmer
6.027
3142433PROV 92
Solar/Wind Harmer
1.127
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
316381AD1-082 GEN
Solar/Wind Harmer
0.284
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
9.274
941031AE2-094 GEN
Solar/Wind Harmer
50.36
316132AB2-190 GEN1
Solar/Wind Harmer
1.455
3156021HOLLOMANSOL
Solar/Wind Harmer
1.227
3145893MURPHYS
Solar/Wind Harmer
1.089
3145893MURPHYS
Solar/Wind Harmer
1.211
3141726DUNNSVL
Solar/Wind Harmer
1.088
3146173TUNIS
Solar/Wind Harmer
0.269
3145963POPLR C
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.266
3150351NORNECKC2
Adder
2.643
944631AF1-128 GEN
Adder
125.485
3146263WOODLND
Solar/Wind Harmer
0.26
3145823KELFORD
Solar/Wind Harmer
0.257
315607AA1-063A GEN
Solar/Wind Harmer
0.513
970919AG2-571 GEN
Solar/Wind Harmer
8.91
3146293MARTNCO
Solar/Wind Harmer
0.23
970087AG2-069 GEN
Solar/Wind Harmer
19.764
316023GEN1_S
Solar/Wind Harmer
0.546
3145783HORNRTN
Solar/Wind Harmer
0.241
316337AD2-073 GEN
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
0.789
3145796HORNRTN
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
960081AF2-299 GEN
Solar/Wind Harmer
2.286
316494AC1-189 GEN
Solar/Wind Harmer
0.779
957481AF2-042 GEN
Solar/Wind Harmer
60.858
315671AE2-027_GEN
Solar/Wind Harmer
0.002
3147043LAWRENC
Adder
2.033
961671AG1-007 GEN
Solar/Wind Harmer
0.034
3146083TARBORO
Solar/Wind Harmer
0.223
3145493TOT1
Solar/Wind Harmer
0.994
3146233WITAKRS
Solar/Wind Harmer
0.877
316129AC1-054 GEN
Solar/Wind Harmer
0.814
315693AD1-088 GEN
Solar/Wind Harmer
10.407
971065AG2-659 GEN
Solar/Wind Harmer
9.207
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.378
3143096IRON208
Adder
0.896
316131AB2-060 GEN
Solar/Wind Harmer
0.601
3142543TWELFTH
Solar/Wind Harmer
0.018
970401AG2-262 GEN
Solar/Wind Harmer
1.083
315785AD2-033 C
Solar/Wind Harmer
1.488
316034AC1-036 C
Solar/Wind Harmer
0.012
3150851SPRUNCC
Adder
0.818
970685AG2-442 GEN
Solar/Wind Harmer
13.003
972135AH1-637 GEN
Solar/Wind Harmer
1.47
3143226MDLTHAN
Solar/Wind Harmer
0.172
971563AH1-280 GEN
Solar/Wind Harmer
1.828
3144293JTRSVLE
Adder
0.409
3144293JTRSVLE
Adder
0.323
3143526WINTERP
Solar/Wind Harmer
0.883
3142416OLDCHRC
Solar/Wind Harmer
0.44
3142416OLDCHRC
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.088
3143336POWHATN
Solar/Wind Harmer
2.4
3146776BUCKING
Solar/Wind Harmer
0.046
3150351NORNECKC2
Adder
2.687
315813AE1-149 C
Solar/Wind Harmer
13.975
3146263WOODLND
Solar/Wind Harmer
0.26
3145823KELFORD
Solar/Wind Harmer
0.257
970133AG2-095 GEN
Solar/Wind Harmer
2.435
970917AG2-570 GEN
Solar/Wind Harmer
22.276
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
316011AB1-132 GEN
Solar/Wind Harmer
4.412
316181AB2-040 GEN
Solar/Wind Harmer
0.341
3145796HORNRTN
Solar/Wind Harmer
0.956
3145796HORNRTN
Solar/Wind Harmer
0.239
316212AC1-099_GEN
Solar/Wind Harmer
1.233
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
970293AG2-193 GEN
Solar/Wind Harmer
2.435
315722AD1-056 GEN
Solar/Wind Harmer
7.8
3147043LAWRENC
Solar/Wind Harmer
0.135
3146073TAR RVR
Solar/Wind Harmer
0.223
3146083TARBORO
Solar/Wind Harmer
0.223
3146233WITAKRS
Solar/Wind Harmer
1.106
3146233WITAKRS
Solar/Wind Harmer
0.15
3138543CONSLDL
Solar/Wind Harmer
0.145
316478AD1-087 GEN
Solar/Wind Harmer
0.752
961601AG1-000A GEN
Solar/Wind Harmer
15.289
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
971623AH1-311 GEN
Solar/Wind Harmer
0.43
3143096IRON208
Adder
0.896
3143096IRON208
Adder
0.878
316223AC1-118
Solar/Wind Harmer
0.151
3141906WESTMOR
Solar/Wind Harmer
0.085
964241AG1-285 GEN
Solar/Wind Harmer
12.653
970257AG2-171 GEN
Solar/Wind Harmer
5.821
971775AH1-396 GEN
Solar/Wind Harmer
0.291
959311AF2-222 GEN
Solar/Wind Harmer
16.033
3150861SPRUNCD
Adder
0.818
3144293JTRSVLE
Adder
0.409
3142416OLDCHRC
Solar/Wind Harmer
1.641
3147133PAMPLIN
Solar/Wind Harmer
0.527
316222AC1-221 GEN
Solar/Wind Harmer
0.676
316283AC2-100 C
Solar/Wind Harmer
0.32
942461AE2-259 GEN
Solar/Wind Harmer
0
971683AH1-343 GEN
Solar/Wind Harmer
5.718
3146926FARMVIL
Solar/Wind Harmer
0.088
3143336POWHATN
Solar/Wind Harmer
2.04
316123AC1-075 GEN
Solar/Wind Harmer
0.173
3146776BUCKING
Solar/Wind Harmer
0.042
3147133PAMPLIN
Solar/Wind Harmer
0.168
3147133PAMPLIN
Solar/Wind Harmer
0.134
3142366NRTHEST
Adder
0.518
316313AB2-026
Solar/Wind Harmer
0.084
316336AC2-165 C
Solar/Wind Harmer
6.351
942751AE2-291 GEN
Solar/Wind Harmer
6.403
3146776BUCKING
Solar/Wind Harmer
0.464
3146776BUCKING
Solar/Wind Harmer
0.038
CPLELTFEXP_CPLE->PJM
CLTF
12.713
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.345
LAGNLTFEXP_LAGN->PJM
CLTF
7.223
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.225
TVALTFEXP_TVA->PJM
CLTF
3.591
NYPJM->LTFIMP_NY
CLTF
2.177
LGEELTFEXP_LGEE->PJM
CLTF
0.93
WECLTFEXP_WEC->PJM
CLTF
0.466
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.36
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.972
MECLTFEXP_MEC->PJM
CLTF
2.839
SIGELTFEXP_SIGE->PJM
CLTF
0.082

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.71 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3118.81
MW Contribution:
236.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
236.196
3151081ELIZAR1
50/50
34.031
3151091ELIZAR2
50/50
33.44
941591AE2-156 GEN
50/50
31.049
3151201GRAVEL4
50/50
23.986
316159AE1-175 C
Solar/Wind Harmer
0.301
316316AC1-027 C
Solar/Wind Harmer
0.333
957871AF2-081 GEN
Solar/Wind Harmer
17.21
3146406KITTY HAWK
Solar/Wind Harmer
0.043
313526AB2-022
Solar/Wind Harmer
0.18
3146396TANGLEW
Solar/Wind Harmer
0.921
3145176PASQUOTANK
Solar/Wind Harmer
0.207
3146486SUNBURY
Solar/Wind Harmer
0.333
3146486SUNBURY
Solar/Wind Harmer
0.333
3138283WHITEMARSH
Solar/Wind Harmer
0.077
971445AH1-216 GEN
Solar/Wind Harmer
22.818
3130156CHOWAN
Solar/Wind Harmer
0.313
3130156CHOWAN
Solar/Wind Harmer
0.313
3151221GRAVEL6
Adder
22.578
3151191GRAVEL3
Adder
22.318
3151211GRAVEL5
Adder
22.318
316311AC2-079 GEN
Solar/Wind Harmer
8.763
3141873WAN 176
Solar/Wind Harmer
0.06
970189AG2-124 GEN
Solar/Wind Harmer
8.775
3141913WHIT STONE
Solar/Wind Harmer
0.294
3138133OCRAN
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.29
3152331SURRY 2
50/50
17.021
3150981CHESPKA
50/50
4.62
315773AC2-141 GEN
Solar/Wind Harmer
13.931
971317AH1-138 GEN
Solar/Wind Harmer
2.673
944591AF1-124 GEN
Solar/Wind Harmer
80.492
3138126ROCKLANDING
Solar/Wind Harmer
0.163
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.062
3146456SLIGO L269
Solar/Wind Harmer
0.344
319010AE1-072 C
Solar/Wind Harmer
1.715
316072AD1-144
Solar/Wind Harmer
0.12
3146516WINFALL
Solar/Wind Harmer
1.064
3146516WINFALL
Solar/Wind Harmer
0.328
316093AE2-104_GEN
Solar/Wind Harmer
5.485
3145336SMITFLD
Solar/Wind Harmer
1.301
939411AE1-173 GEN
Solar/Wind Harmer
137.491
315975AC1-164 GENB
Solar/Wind Harmer
0.099
3130156CHOWAN
Solar/Wind Harmer
0.313
940641AE2-051 GEN
Solar/Wind Harmer
25.004
3151171GRAVELC
Adder
3.304
3141766HARMONY
Solar/Wind Harmer
0.061
315816AE2-034 GEN
Solar/Wind Harmer
1.28
3145663CRESWEL
Solar/Wind Harmer
0.84
971163AH1-040 GEN
Solar/Wind Harmer
24.005
961611AG1-000B GEN
Solar/Wind Harmer
15.55
971777AH1-397 GEN
Solar/Wind Harmer
0.782
3138133OCRAN
Solar/Wind Harmer
0.175
315737AD1-076 GEN
Solar/Wind Harmer
3.702
941031AE2-094 GEN
Solar/Wind Harmer
52.313
3146206CASHIE
Solar/Wind Harmer
0.282
971547AH1-271 GEN
Solar/Wind Harmer
6.011
3156021HOLLOMANSOL
Solar/Wind Harmer
1.224
3145893MURPHYS
Solar/Wind Harmer
1.085
3145893MURPHYS
Solar/Wind Harmer
1.206
316381AD1-082 GEN
Solar/Wind Harmer
0.274
3146173TUNIS
Solar/Wind Harmer
0.269
962861AG1-135 GEN
Solar/Wind Harmer
8.56
3145963POPLR C
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.266
971069AG2-661 GEN
Solar/Wind Harmer
4.72
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
8.772
3146263WOODLND
Solar/Wind Harmer
0.259
970919AG2-571 GEN
Solar/Wind Harmer
9.213
3142433PROV 92
Solar/Wind Harmer
1.036
3150921YORKTN3
50/50
9.598
3144216WINCHST
50/50
1.417
3151101ELIZAR3
50/50
34.466
3151161SURRY 1
50/50
12.65
944581AF1-123 GEN
Solar/Wind Harmer
80.207
944601AF1-125 GEN
Solar/Wind Harmer
78.971
3144873MCLAUGH
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.184
3146456SLIGO L269
Solar/Wind Harmer
0.344
971153AH1-033 GEN
Solar/Wind Harmer
3.981
3144536CHRHLND
Solar/Wind Harmer
0.051
316246AF1-032 C
Solar/Wind Harmer
0.151
316321Z2-027
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.328
3145336SMITFLD
Solar/Wind Harmer
0.13
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146376EDENTON
Solar/Wind Harmer
0.312
3145273HOLLAND
Solar/Wind Harmer
0.233
3151171GRAVELC
Adder
4.344
3141766HARMONY
Solar/Wind Harmer
4.049
3141873WAN 176
Solar/Wind Harmer
5.369
961611AG1-000B GEN
Solar/Wind Harmer
7.907
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
1.513
315735AD1-075 GEN1
Solar/Wind Harmer
0.821
944011AF1-069 GEN
Solar/Wind Harmer
17.093
3146206CASHIE
Solar/Wind Harmer
0.282
3156081AA2-088 GEN
Solar/Wind Harmer
0
970657AG2-426 GEN
Solar/Wind Harmer
6.158
3145893MURPHYS
Solar/Wind Harmer
0.454
3145893MURPHYS
Solar/Wind Harmer
0.271
3146173TUNIS
Solar/Wind Harmer
0.269
3145963POPLR C
Solar/Wind Harmer
0.267
315778AD1-151 GEN
Solar/Wind Harmer
21.239
3146263WOODLND
Solar/Wind Harmer
0.259
970917AG2-570 GEN
Solar/Wind Harmer
23.033
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
3142946ENON
Solar/Wind Harmer
0.086
3145823KELFORD
Solar/Wind Harmer
0.256
316458AB2-190 GEN2
Solar/Wind Harmer
1.348
316075AC2-137 C
Solar/Wind Harmer
0.067
3150351NORNECKC2
Adder
2.536
315813AE1-149 C
Solar/Wind Harmer
13.293
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
316011AB1-132 GEN
Solar/Wind Harmer
4.4
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316212AC1-099_GEN
Solar/Wind Harmer
1.232
316181AB2-040 GEN
Solar/Wind Harmer
0.34
3145796HORNRTN
Solar/Wind Harmer
0.954
3145796HORNRTN
Solar/Wind Harmer
0.238
970133AG2-095 GEN
Solar/Wind Harmer
2.207
315722AD1-056 GEN
Solar/Wind Harmer
7.803
3146073TAR RVR
Solar/Wind Harmer
0.224
3146083TARBORO
Solar/Wind Harmer
0.224
3147043LAWRENC
Solar/Wind Harmer
0.134
3146233WITAKRS
Solar/Wind Harmer
1.108
3146233WITAKRS
Solar/Wind Harmer
0.15
3138543CONSLDL
Solar/Wind Harmer
0.145
316478AD1-087 GEN
Solar/Wind Harmer
0.76
961601AG1-000A GEN
Solar/Wind Harmer
15.327
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
971623AH1-311 GEN
Solar/Wind Harmer
0.431
316223AC1-118
Solar/Wind Harmer
0.142
3141906WESTMOR
Solar/Wind Harmer
0.08
970293AG2-193 GEN
Solar/Wind Harmer
2.104
964241AG1-285 GEN
Solar/Wind Harmer
12.302
970257AG2-171 GEN
Solar/Wind Harmer
5.566
971775AH1-396 GEN
Solar/Wind Harmer
0.278
3143096IRON208
Adder
0.722
3143096IRON208
Adder
0.708
959311AF2-222 GEN
Solar/Wind Harmer
15.274
316222AC1-221 GEN
Solar/Wind Harmer
0.682
316283AC2-100 C
Solar/Wind Harmer
0.322
3144293JTRSVLE
Adder
0.381
3147133PAMPLIN
Solar/Wind Harmer
0.486
971683AH1-343 GEN
Solar/Wind Harmer
5.699
942461AE2-259 GEN
Solar/Wind Harmer
0
3142416OLDCHRC
Solar/Wind Harmer
1.365
316123AC1-075 GEN
Solar/Wind Harmer
0.171
3146926FARMVIL
Solar/Wind Harmer
0.076
3150861SPRUNCD
Adder
0.529
315732AD1-074 GEN1
Solar/Wind Harmer
1.644
315733AD1-074 GEN2
Solar/Wind Harmer
1.644
3141783LANCAST
Solar/Wind Harmer
0.173
3141783LANCAST
Solar/Wind Harmer
0.115
3143873LANEXA
Solar/Wind Harmer
0.173
970533AG2-339 GEN
Solar/Wind Harmer
21.46
3146206CASHIE
Solar/Wind Harmer
0.282
970601AG2-382 GEN
Solar/Wind Harmer
10.52
970673AG2-436 GEN
Solar/Wind Harmer
34.876
970657AG2-426 GEN
Solar/Wind Harmer
2.015
315697AD1-025 GEN
Solar/Wind Harmer
0.295
3145893MURPHYS
Solar/Wind Harmer
0.732
3145893MURPHYS
Solar/Wind Harmer
0.271
971967AH1-528 GEN
Solar/Wind Harmer
43.008
316463AE2-346 GEN
Solar/Wind Harmer
0.228
3145513AHOSKIE
Solar/Wind Harmer
0.559
3145513AHOSKIE
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.532
3145683EARLEYS
Solar/Wind Harmer
0.266
3145683EARLEYS
Solar/Wind Harmer
0.266
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
3146043SEABORD
Solar/Wind Harmer
0.256
970085AG2-068 GEN
Solar/Wind Harmer
13.617
970581AG2-369 GEN
Solar/Wind Harmer
11.711
315814AE2-033 C
Solar/Wind Harmer
19.928
3141813NORNECK
Solar/Wind Harmer
0.25
3146033SCOT NK
Solar/Wind Harmer
0.986
316426AA2-053 GEN
Solar/Wind Harmer
0.821
315652AC1-086 GEN
Solar/Wind Harmer
26.681
3137643SOCKMAN
Solar/Wind Harmer
0.959
3145746EVERETS
Solar/Wind Harmer
0.95
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316210AC1-098 GEN
Solar/Wind Harmer
2.208
3145796HORNRTN
Solar/Wind Harmer
0.763
3145796HORNRTN
Solar/Wind Harmer
0.095
316274AC1-208 GEN
Solar/Wind Harmer
1.208
3143316POE
Solar/Wind Harmer
0.919
957861AF2-080 GEN
Solar/Wind Harmer
9.954
316327AA2-057 GEN
Solar/Wind Harmer
0.334
3145573BETHELC
Solar/Wind Harmer
0.224
3145573BETHELC
Solar/Wind Harmer
0.224
970831AG2-522 GEN
Solar/Wind Harmer
9.378
316486AD2-202 GEN
Solar/Wind Harmer
0.223
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
10.042
970681AG2-440 GEN
Solar/Wind Harmer
6.665
946301AF1-294 GEN
Solar/Wind Harmer
3.152
961791AG1-021 GEN
Solar/Wind Harmer
1.533
944491AF1-114 GEN
Solar/Wind Harmer
0
971285AH1-108 GEN
Adder
0.865
3150991CHESPKB
50/50
3.876
3150991CHESPKB
50/50
3.783
316294AC1-161 GEN
Solar/Wind Harmer
6.594
3145506HICKORY
Solar/Wind Harmer
1.395
3145506HICKORY
Solar/Wind Harmer
0.837
3145506HICKORY
Solar/Wind Harmer
0.209
316339AD2-160 GEN
Solar/Wind Harmer
0.554
316388AE2-253 GEN
Solar/Wind Harmer
1.078
3137176SLIGO L2192
Solar/Wind Harmer
1.371
3146456SLIGO L269
Solar/Wind Harmer
6.093
3130086AYDLETT
Solar/Wind Harmer
1.373
3146386ELIZ CT
Solar/Wind Harmer
0.337
3146516WINFALL
Solar/Wind Harmer
0.328
3146516WINFALL
Solar/Wind Harmer
0.328
3146516WINFALL
Solar/Wind Harmer
0.328
315835AF2-110_GEN
Solar/Wind Harmer
2.238
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146626S HERTFORD
Solar/Wind Harmer
0.325
315976AC1-164 GENA
Solar/Wind Harmer
3.337
316169AC1-164_GENC
Solar/Wind Harmer
2.883
3146376EDENTON
Solar/Wind Harmer
1.39
3146376EDENTON
Solar/Wind Harmer
1.39
316349AD2-085 GEN
Solar/Wind Harmer
0.203
315742AE1-103 GEN
Solar/Wind Harmer
4.533
316156AD2-030 GEN
Solar/Wind Harmer
0.221
315614AA2-178 GEN
Solar/Wind Harmer
1.707
316065AD1-022 GEN
Solar/Wind Harmer
13.089
972185AH1-677 GEN
Adder
15.403
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
1.815
3145893MURPHYS
Solar/Wind Harmer
0.488
972187AH1-678 GEN
Adder
7.697
3146173TUNIS
Solar/Wind Harmer
0.269
3146173TUNIS
Solar/Wind Harmer
0.269
316140AB2-099
Solar/Wind Harmer
0.095
970933AG2-581 GEN
Solar/Wind Harmer
20.776
3142946ENON
Solar/Wind Harmer
0.026
3144356SAPONY
Solar/Wind Harmer
2.11
316315AB2-025 C
Solar/Wind Harmer
0.202
3150341NORNECKC1
Adder
2.619
3150341NORNECKC1
Adder
2.598
3145933PARMELE
Solar/Wind Harmer
0.495
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316365GEN2_N
Solar/Wind Harmer
0.544
962571AG1-106 GEN
Solar/Wind Harmer
3.451
3145593CAROLNA
Solar/Wind Harmer
0.241
3145593CAROLNA
Solar/Wind Harmer
0.241
3145593CAROLNA
Solar/Wind Harmer
0.3
3145783HORNRTN
Solar/Wind Harmer
4.268
3145783HORNRTN
Solar/Wind Harmer
3.415
3145783HORNRTN
Solar/Wind Harmer
1.067
3145783HORNRTN
Solar/Wind Harmer
0.427
316005AA1-067
Solar/Wind Harmer
0.255
313506AB2-031 GEN
Solar/Wind Harmer
0.732
3145796HORNRTN
Solar/Wind Harmer
0.716
970099AG2-077 GEN
Solar/Wind Harmer
24.701
315724AD1-057 GEN
Solar/Wind Harmer
4.353
3145493TOT1
Solar/Wind Harmer
0.519
3145453TOT5
Solar/Wind Harmer
0.311
3145603CNETO
Solar/Wind Harmer
0.208
961601AG1-000A GEN
Solar/Wind Harmer
3.832
316049AB1-081 GEN
Solar/Wind Harmer
1.225
316263AC1-034 GEN
Solar/Wind Harmer
8.183
962561AG1-105 GEN
Solar/Wind Harmer
8.839
944641AF1-129 GEN
Adder
87.24
964791AG1-342 GEN
Solar/Wind Harmer
3.514
3146843MT LREL
Solar/Wind Harmer
0.183
3146843MT LREL
Solar/Wind Harmer
0.183
316118AC1-105 GEN
Solar/Wind Harmer
0.462
970323AG2-213 GEN
Solar/Wind Harmer
7.421
970301AG2-198 GEN
Solar/Wind Harmer
7.027
958211AF2-115 GEN
Solar/Wind Harmer
1.917
3144293JTRSVLE
Adder
0.381
3147133PAMPLIN
Solar/Wind Harmer
0.155
3147133PAMPLIN
Solar/Wind Harmer
0.124
3150691DARBY 3
Adder
10.678
3150701DARBY 4
Adder
10.653
3150681DARBY 2
Adder
10.641
3150671DARBY 1
Adder
10.629
316312AB1-027
Solar/Wind Harmer
0.25
3142366NRTHEST
Adder
0.394
942751AE2-291 GEN
Solar/Wind Harmer
6.318
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
3141726DUNNSVL
Solar/Wind Harmer
1.026
3145823KELFORD
Solar/Wind Harmer
0.256
970087AG2-069 GEN
Solar/Wind Harmer
20.426
315607AA1-063A GEN
Solar/Wind Harmer
0.511
316132AB2-190 GEN1
Solar/Wind Harmer
1.348
3150351NORNECKC2
Adder
2.494
3146293MARTNCO
Solar/Wind Harmer
0.23
316023GEN1_S
Solar/Wind Harmer
0.544
3145783HORNRTN
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.787
3145796HORNRTN
Solar/Wind Harmer
0.238
960081AF2-299 GEN
Solar/Wind Harmer
2.272
944631AF1-128 GEN
Adder
111.26
957481AF2-042 GEN
Solar/Wind Harmer
61.753
316494AC1-189 GEN
Solar/Wind Harmer
0.78
316337AD2-073 GEN
Solar/Wind Harmer
0.195
961671AG1-007 GEN
Solar/Wind Harmer
0.034
3146083TARBORO
Solar/Wind Harmer
0.224
3145493TOT1
Solar/Wind Harmer
0.995
3147043LAWRENC
Adder
2.014
3146233WITAKRS
Solar/Wind Harmer
0.878
315693AD1-088 GEN
Solar/Wind Harmer
10.418
316129AC1-054 GEN
Solar/Wind Harmer
0.81
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.765
3142053HEARTS
Solar/Wind Harmer
0.379
971065AG2-659 GEN
Solar/Wind Harmer
9.166
315671AE2-027_GEN
Solar/Wind Harmer
0.001
316131AB2-060 GEN
Solar/Wind Harmer
0.589
970401AG2-262 GEN
Solar/Wind Harmer
1.074
315785AD2-033 C
Solar/Wind Harmer
1.43
316034AC1-036 C
Solar/Wind Harmer
0.012
3143096IRON208
Adder
0.722
970685AG2-442 GEN
Solar/Wind Harmer
12.204
972135AH1-637 GEN
Solar/Wind Harmer
1.375
971563AH1-280 GEN
Solar/Wind Harmer
1.704
3144293JTRSVLE
Adder
0.381
3144293JTRSVLE
Adder
0.301
3142543TWELFTH
Solar/Wind Harmer
0.014
3142416OLDCHRC
Solar/Wind Harmer
0.366
3142416OLDCHRC
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.076
3150851SPRUNCC
Adder
0.529
CPLELTFEXP_CPLE->PJM
CLTF
12.852
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.176
LAGNLTFEXP_LAGN->PJM
CLTF
7.216
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.448
TVALTFEXP_TVA->PJM
CLTF
3.583
NYPJM->LTFIMP_NY
CLTF
2.098
LGEELTFEXP_LGEE->PJM
CLTF
0.91
WECLTFEXP_WEC->PJM
CLTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.08
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.926
MECLTFEXP_MEC->PJM
CLTF
2.807
SIGELTFEXP_SIGE->PJM
CLTF
0.081

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.34 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:4267.68
MW Contribution:
244.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
17.624
3150981CHESPKA
50/50
4.831
315773AC2-141 GEN
Solar/Wind Harmer
18.651
971317AH1-138 GEN
Solar/Wind Harmer
5.253
3138126ROCKLANDING
Solar/Wind Harmer
0.128
944591AF1-124 GEN
Solar/Wind Harmer
190.732
316375AC2-012 GEN
Solar/Wind Harmer
14.168
316036AC1-147 C
Solar/Wind Harmer
1.102
3146456SLIGO L269
Solar/Wind Harmer
-0.04
319010AE1-072 C
Solar/Wind Harmer
8.153
316072AD1-144
Solar/Wind Harmer
0.8
3146516WINFALL
Solar/Wind Harmer
-0.124
3146516WINFALL
Solar/Wind Harmer
-0.039
3145336SMITFLD
Solar/Wind Harmer
-0.153
316093AE2-104_GEN
Solar/Wind Harmer
11.18
939411AE1-173 GEN
Solar/Wind Harmer
189.867
315975AC1-164 GENB
Solar/Wind Harmer
0.254
315611Z1-036_GEN2
Solar/Wind Harmer
9.181
3151171GRAVELC
Adder
3.494
940641AE2-051 GEN
Solar/Wind Harmer
34.581
3130156CHOWAN
Solar/Wind Harmer
-0.037
316314AB2-024 C
Solar/Wind Harmer
3.085
3141766HARMONY
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
17.476
315662AE1-191 GEN
Solar/Wind Harmer
4.258
316280AD1-041 GEN
Solar/Wind Harmer
2.661
315816AE2-034 GEN
Solar/Wind Harmer
2.857
3145663CRESWEL
Solar/Wind Harmer
-0.099
971163AH1-040 GEN
Solar/Wind Harmer
33.187
971777AH1-397 GEN
Solar/Wind Harmer
4.102
3138133OCRAN
Solar/Wind Harmer
-0.021
315737AD1-076 GEN
Solar/Wind Harmer
6.467
941031AE2-094 GEN
Solar/Wind Harmer
63.112
3146206CASHIE
Solar/Wind Harmer
-0.033
971547AH1-271 GEN
Solar/Wind Harmer
8.329
316369SG1_INVT
Solar/Wind Harmer
5.892
316381AD1-082 GEN
Solar/Wind Harmer
2.975
3156021HOLLOMANSOL
Solar/Wind Harmer
4.329
3145893MURPHYS
Solar/Wind Harmer
-0.128
3145893MURPHYS
Solar/Wind Harmer
0.955
971069AG2-661 GEN
Solar/Wind Harmer
5.079
3146173TUNIS
Solar/Wind Harmer
-0.032
962861AG1-135 GEN
Solar/Wind Harmer
11.879
3145963POPLR C
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
316404AE1-155 C
Solar/Wind Harmer
5.997
958261AF2-120 GEN
Solar/Wind Harmer
12.173
3142433PROV 92
Solar/Wind Harmer
-0.125
3142433PROV 92
Adder
0.541
3142433PROV 92
Adder
0.541
3146263WOODLND
Solar/Wind Harmer
-0.031
970919AG2-571 GEN
Solar/Wind Harmer
9.736
316132AB2-190 GEN1
Solar/Wind Harmer
3.101
3145823KELFORD
Solar/Wind Harmer
-0.03
964211AG1-282 GEN
Solar/Wind Harmer
0.914
3141726DUNNSVL
Solar/Wind Harmer
-0.121
970087AG2-069 GEN
Solar/Wind Harmer
28.424
315607AA1-063A GEN
Solar/Wind Harmer
3.045
3150351NORNECKC2
Adder
2.629
3146293MARTNCO
Solar/Wind Harmer
0.182
316023GEN1_S
Solar/Wind Harmer
1.969
944631AF1-128 GEN
Adder
122.194
3145783HORNRTN
Solar/Wind Harmer
-0.029
316087AB2-174 GEN
Solar/Wind Harmer
4.056
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
960081AF2-299 GEN
Solar/Wind Harmer
3.189
957481AF2-042 GEN
Solar/Wind Harmer
86.687
316494AC1-189 GEN
Solar/Wind Harmer
2.953
3147043LAWRENC
Adder
2.154
316337AD2-073 GEN
Solar/Wind Harmer
0.717
961671AG1-007 GEN
Solar/Wind Harmer
0.337
3146083TARBORO
Solar/Wind Harmer
-0.027
3145493TOT1
Solar/Wind Harmer
0.791
316319Z2-044 C
Solar/Wind Harmer
1.453
3146233WITAKRS
Solar/Wind Harmer
-0.104
315693AD1-088 GEN
Solar/Wind Harmer
13.085
316129AC1-054 GEN
Solar/Wind Harmer
2.275
971065AG2-659 GEN
Solar/Wind Harmer
12.889
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
316359AB2-059 GEN
Solar/Wind Harmer
3.451
3142053HEARTS
Solar/Wind Harmer
0.302
315671AE2-027_GEN
Solar/Wind Harmer
4.607
316131AB2-060 GEN
Solar/Wind Harmer
2.473
3143096IRON208
Adder
0.838
970401AG2-262 GEN
Solar/Wind Harmer
1.444
315785AD2-033 C
Solar/Wind Harmer
4.91
3150991CHESPKB
50/50
4.053
3150991CHESPKB
50/50
3.955
316294AC1-161 GEN
Solar/Wind Harmer
14.414
316185AD1-033 GEN
Solar/Wind Harmer
4.326
3145506HICKORY
Solar/Wind Harmer
-0.163
3145506HICKORY
Solar/Wind Harmer
-0.098
3145506HICKORY
Solar/Wind Harmer
-0.024
316339AD2-160 GEN
Solar/Wind Harmer
2.736
316388AE2-253 GEN
Solar/Wind Harmer
2.736
3137176SLIGO L2192
Solar/Wind Harmer
-0.16
3146456SLIGO L269
Solar/Wind Harmer
4.778
3130086AYDLETT
Solar/Wind Harmer
-0.161
3146386ELIZ CT
Solar/Wind Harmer
-0.04
316431W1029_GEN1
Solar/Wind Harmer
7.028
316433W1029_GEN2
Solar/Wind Harmer
7.028
316435W1029_GEN3
Solar/Wind Harmer
7.028
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
315835AF2-110_GEN
Solar/Wind Harmer
4.807
3146626S HERTFORD
Solar/Wind Harmer
-0.038
3146626S HERTFORD
Solar/Wind Harmer
-0.038
315976AC1-164 GENA
Solar/Wind Harmer
8.571
316169AC1-164_GENC
Solar/Wind Harmer
7.405
3146376EDENTON
Solar/Wind Harmer
1.093
3146376EDENTON
Solar/Wind Harmer
1.093
316349AD2-085 GEN
Solar/Wind Harmer
3.211
315742AE1-103 GEN
Solar/Wind Harmer
8.513
316156AD2-030 GEN
Solar/Wind Harmer
0.952
315666AE1-190 GEN
Solar/Wind Harmer
1.064
315614AA2-178 GEN
Solar/Wind Harmer
3.809
316441AF1-014 GEN
Solar/Wind Harmer
2.37
316065AD1-022 GEN
Solar/Wind Harmer
16.799
316033AB2-134 GEN
Solar/Wind Harmer
10.639
972185AH1-677 GEN
Adder
16.261
316083AB2-161 GEN
Solar/Wind Harmer
5.277
316487AF1-042 GEN
Solar/Wind Harmer
4.269
3145893MURPHYS
Solar/Wind Harmer
0.898
3145893MURPHYS
Solar/Wind Harmer
-0.058
972187AH1-678 GEN
Adder
8.129
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316140AB2-099
Solar/Wind Harmer
0.213
3142946ENON
Solar/Wind Harmer
-0.003
970933AG2-581 GEN
Solar/Wind Harmer
28.982
3144356SAPONY
Solar/Wind Harmer
1.057
316315AB2-025 C
Solar/Wind Harmer
0.815
3150341NORNECKC1
Adder
2.761
3150341NORNECKC1
Adder
2.739
3145933PARMELE
Solar/Wind Harmer
-0.058
3145933PARMELE
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316365GEN2_N
Solar/Wind Harmer
1.969
962571AG1-106 GEN
Solar/Wind Harmer
4.16
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
0.239
3145783HORNRTN
Solar/Wind Harmer
3.398
3145783HORNRTN
Solar/Wind Harmer
2.718
3145783HORNRTN
Solar/Wind Harmer
0.849
3145783HORNRTN
Solar/Wind Harmer
0.34
313506AB2-031 GEN
Solar/Wind Harmer
2.288
3145796HORNRTN
Solar/Wind Harmer
-0.085
316005AA1-067
Solar/Wind Harmer
0.572
970099AG2-077 GEN
Solar/Wind Harmer
34.675
315724AD1-057 GEN
Solar/Wind Harmer
5.268
3145493TOT1
Solar/Wind Harmer
0.412
3145453TOT5
Solar/Wind Harmer
0.247
3145603CNETO
Solar/Wind Harmer
0.165
961601AG1-000A GEN
Solar/Wind Harmer
10.097
316049AB1-081 GEN
Solar/Wind Harmer
2.762
316263AC1-034 GEN
Solar/Wind Harmer
12.031
315687AD1-152 GEN
Solar/Wind Harmer
2.96
316240AF1-291 C
Solar/Wind Harmer
0.715
944641AF1-129 GEN
Adder
98.424
316237AB2-079_GEN
Solar/Wind Harmer
0.695
313527AB2-043 GEN
Solar/Wind Harmer
3.751
962561AG1-105 GEN
Solar/Wind Harmer
12.531
964791AG1-342 GEN
Solar/Wind Harmer
4.727
3146843MT LREL
Solar/Wind Harmer
-0.022
3146843MT LREL
Solar/Wind Harmer
-0.022
316118AC1-105 GEN
Solar/Wind Harmer
1.493
316248AF1-058 C
Solar/Wind Harmer
0.644
970323AG2-213 GEN
Solar/Wind Harmer
10.701
970301AG2-198 GEN
Solar/Wind Harmer
10.283
958211AF2-115 GEN
Solar/Wind Harmer
3.114
3144293JTRSVLE
Adder
0.423
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3147133PAMPLIN
Solar/Wind Harmer
-0.016
3150691DARBY 3
Adder
12.389
3150701DARBY 4
Adder
12.36
3150681DARBY 2
Adder
12.346
3150671DARBY 1
Adder
12.332
316312AB1-027
Solar/Wind Harmer
0.606
3142366NRTHEST
Adder
0.476
942751AE2-291 GEN
Solar/Wind Harmer
9.027
3143526WINTERP
Solar/Wind Harmer
-0.072
3150921YORKTN3
50/50
10.027
3144216WINCHST
50/50
1.482
3151101ELIZAR3
50/50
36.03
3151161SURRY 1
50/50
13.382
944581AF1-123 GEN
Solar/Wind Harmer
190.047
944601AF1-125 GEN
Solar/Wind Harmer
187.081
3142956BIRDNECK
Solar/Wind Harmer
2.201
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
3.277
3146456SLIGO L269
Solar/Wind Harmer
-0.04
971153AH1-033 GEN
Solar/Wind Harmer
4.682
3144536CHRHLND
Solar/Wind Harmer
-0.006
316305AF2-043 C
Solar/Wind Harmer
1.199
316246AF1-032 C
Solar/Wind Harmer
0.804
316320Y1-086
Solar/Wind Harmer
2.322
972263AH1-716 GEN
50/50
244.812
3151081ELIZAR1
50/50
35.575
3151091ELIZAR2
50/50
34.957
941591AE2-156 GEN
50/50
32.462
3151201GRAVEL4
50/50
25.372
316382AG1-145 C
Solar/Wind Harmer
1.244
316159AE1-175 C
Solar/Wind Harmer
1.107
316316AC1-027 C
Solar/Wind Harmer
1.256
316018AA1-139 ULT2
Solar/Wind Harmer
3.469
957871AF2-081 GEN
Solar/Wind Harmer
20.303
3146406KITTY HAWK
Solar/Wind Harmer
0.034
313526AB2-022
Solar/Wind Harmer
1.067
3146396TANGLEW
Solar/Wind Harmer
0.723
3145176PASQUOTANK
Solar/Wind Harmer
-0.024
3146486SUNBURY
Solar/Wind Harmer
-0.039
3146486SUNBURY
Solar/Wind Harmer
-0.039
957831AF2-077 GEN
Solar/Wind Harmer
1.177
3138283WHITEMARSH
Solar/Wind Harmer
0.061
316236AE1-162_GEN
Solar/Wind Harmer
1.157
971445AH1-216 GEN
Solar/Wind Harmer
23.731
315800Z1-036_GEN1
Solar/Wind Harmer
9.181
3151221GRAVEL6
Adder
23.883
3151191GRAVEL3
Adder
23.608
3151211GRAVEL5
Adder
23.608
3130156CHOWAN
Solar/Wind Harmer
-0.037
3130156CHOWAN
Solar/Wind Harmer
-0.037
316311AC2-079 GEN
Solar/Wind Harmer
18.266
315833AF1-017_GEN
Solar/Wind Harmer
6.868
316059AD1-063 C
Solar/Wind Harmer
0.811
957601AF2-054 GEN
Solar/Wind Harmer
1.069
3141873WAN 176
Solar/Wind Harmer
-0.007
3141913WHIT STONE
Solar/Wind Harmer
-0.035
3138133OCRAN
Solar/Wind Harmer
-0.01
3143873LANEXA
Solar/Wind Harmer
-0.02
3130546PLYMOUTH
Solar/Wind Harmer
-0.034
315732AD1-074 GEN1
Solar/Wind Harmer
6.879
315733AD1-074 GEN2
Solar/Wind Harmer
6.879
3141783LANCAST
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.013
970533AG2-339 GEN
Solar/Wind Harmer
22.635
3146206CASHIE
Solar/Wind Harmer
-0.033
970601AG2-382 GEN
Solar/Wind Harmer
14.576
970673AG2-436 GEN
Solar/Wind Harmer
72.677
315697AD1-025 GEN
Solar/Wind Harmer
6.668
970657AG2-426 GEN
Solar/Wind Harmer
2.076
316318V4-068
Solar/Wind Harmer
0.802
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
60.041
316463AE2-346 GEN
Solar/Wind Harmer
0.511
3145513AHOSKIE
Solar/Wind Harmer
0.276
961941AG1-037 GEN
Solar/Wind Harmer
0.238
3145513AHOSKIE
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3142433PROV 92
Adder
0.541
3142433PROV 92
Adder
0.541
316174AB2-169 GEN
Solar/Wind Harmer
4.791
3146043SEABORD
Solar/Wind Harmer
-0.03
970085AG2-068 GEN
Solar/Wind Harmer
18.949
970581AG2-369 GEN
Solar/Wind Harmer
16.297
315814AE2-033 C
Solar/Wind Harmer
28.178
3141813NORNECK
Solar/Wind Harmer
-0.03
3146033SCOT NK
Solar/Wind Harmer
-0.117
316426AA2-053 GEN
Solar/Wind Harmer
2.948
315652AC1-086 GEN
Solar/Wind Harmer
32.554
3137643SOCKMAN
Solar/Wind Harmer
-0.114
3145796HORNRTN
Solar/Wind Harmer
-0.091
3145796HORNRTN
Solar/Wind Harmer
-0.011
316210AC1-098 GEN
Solar/Wind Harmer
4.452
3145746EVERETS
Solar/Wind Harmer
-0.112
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
3143316POE
Solar/Wind Harmer
-0.111
946281AF1-292 GEN
Solar/Wind Harmer
0.635
316274AC1-208 GEN
Solar/Wind Harmer
3.002
957861AF2-080 GEN
Solar/Wind Harmer
12.007
316327AA2-057 GEN
Solar/Wind Harmer
2.712
3145573BETHELC
Solar/Wind Harmer
-0.027
3145573BETHELC
Solar/Wind Harmer
-0.027
970831AG2-522 GEN
Solar/Wind Harmer
13.172
316486AD2-202 GEN
Solar/Wind Harmer
0.666
315839AE2-212 C
Solar/Wind Harmer
0.764
316238AB2-078_GEN
Solar/Wind Harmer
0.695
316239AB2-077_GEN
Solar/Wind Harmer
0.695
3147173SINAI
Solar/Wind Harmer
-0.021
3147243WELCO
Solar/Wind Harmer
-0.013
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
14.579
970681AG2-440 GEN
Solar/Wind Harmer
9.677
946301AF1-294 GEN
Solar/Wind Harmer
5.106
961791AG1-021 GEN
Solar/Wind Harmer
2.491
971285AH1-108 GEN
Adder
1.152
270455AD2-022 GEN
Solar/Wind Harmer
2.996
270457AD2-023 GEN
Solar/Wind Harmer
1.519
944491AF1-114 GEN
Solar/Wind Harmer
4.855
316233AE1-074 FULL
Solar/Wind Harmer
0.372
971281AH1-106 GEN
Solar/Wind Harmer
0.896
316321Z2-027
Solar/Wind Harmer
1.058
3146516WINFALL
Solar/Wind Harmer
-0.039
3145336SMITFLD
Solar/Wind Harmer
-0.015
3146626S HERTFORD
Solar/Wind Harmer
-0.038
3151171GRAVELC
Adder
4.595
3146376EDENTON
Solar/Wind Harmer
-0.037
3145273HOLLAND
Solar/Wind Harmer
-0.027
3141766HARMONY
Solar/Wind Harmer
3.201
3141873WAN 176
Solar/Wind Harmer
4.243
961611AG1-000B GEN
Solar/Wind Harmer
7.457
316203AE2-005 GEN
Solar/Wind Harmer
14.824
3141843SHACKLE
Adder
1.599
315735AD1-075 GEN1
Solar/Wind Harmer
3.438
944011AF1-069 GEN
Solar/Wind Harmer
19.775
3146206CASHIE
Solar/Wind Harmer
-0.033
970657AG2-426 GEN
Solar/Wind Harmer
6.652
3156081AA2-088 GEN
Solar/Wind Harmer
10.624
316484AD2-074 GEN
Solar/Wind Harmer
8.159
961951AG1-038 GEN
Solar/Wind Harmer
4.269
3145893MURPHYS
Solar/Wind Harmer
0.225
3145893MURPHYS
Solar/Wind Harmer
-0.032
315778AD1-151 GEN
Solar/Wind Harmer
28.569
3146173TUNIS
Solar/Wind Harmer
-0.032
3145963POPLR C
Solar/Wind Harmer
-0.031
3142946ENON
Solar/Wind Harmer
-0.01
3142433PROV 92
Adder
0.541
3142433PROV 92
Adder
0.541
3146263WOODLND
Solar/Wind Harmer
-0.031
970917AG2-570 GEN
Solar/Wind Harmer
76.913
316458AB2-190 GEN2
Solar/Wind Harmer
3.101
316317KELFORD C
Solar/Wind Harmer
1.408
3145823KELFORD
Solar/Wind Harmer
-0.03
316075AC2-137 C
Solar/Wind Harmer
0.817
315813AE1-149 C
Solar/Wind Harmer
18.895
316077AC2-138 C
Solar/Wind Harmer
0.624
3150351NORNECKC2
Adder
2.673
3145933PARMELE
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
316190AA2-174 GEN
Solar/Wind Harmer
0.359
316011AB1-132 GEN
Solar/Wind Harmer
6.043
316181AB2-040 GEN
Solar/Wind Harmer
3.975
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.028
316212AC1-099_GEN
Solar/Wind Harmer
2.474
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
966621AG1-532 GEN
Solar/Wind Harmer
0.575
970133AG2-095 GEN
Solar/Wind Harmer
3.184
316420AA1-050 GEN
Solar/Wind Harmer
3.076
315722AD1-056 GEN
Solar/Wind Harmer
9.578
3147043LAWRENC
Solar/Wind Harmer
-0.016
3146073TAR RVR
Solar/Wind Harmer
-0.027
3146083TARBORO
Solar/Wind Harmer
-0.027
316478AD1-087 GEN
Solar/Wind Harmer
2.275
3146233WITAKRS
Solar/Wind Harmer
0.551
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
961601AG1-000A GEN
Solar/Wind Harmer
10.225
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
970293AG2-193 GEN
Solar/Wind Harmer
3.077
316223AC1-118
Solar/Wind Harmer
0.637
3141906WESTMOR
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
17.58
3143096IRON208
Adder
0.838
3143096IRON208
Adder
0.821
970257AG2-171 GEN
Solar/Wind Harmer
8.026
971775AH1-396 GEN
Solar/Wind Harmer
1.51
959311AF2-222 GEN
Solar/Wind Harmer
22.112
316003AC1-222 GEN
Solar/Wind Harmer
1.964
3144293JTRSVLE
Adder
0.423
316222AC1-221 GEN
Solar/Wind Harmer
2.006
316283AC2-100 C
Solar/Wind Harmer
1.863
3147133PAMPLIN
Solar/Wind Harmer
-0.061
971683AH1-343 GEN
Solar/Wind Harmer
8.075
3142416OLDCHRC
Solar/Wind Harmer
1.817
942461AE2-259 GEN
Solar/Wind Harmer
2.708
3150861SPRUNCD
Adder
0.704
3146926FARMVIL
Solar/Wind Harmer
-0.01
316123AC1-075 GEN
Solar/Wind Harmer
1.681
316034AC1-036 C
Solar/Wind Harmer
0.396
970685AG2-442 GEN
Solar/Wind Harmer
17.775
971563AH1-280 GEN
Solar/Wind Harmer
2.491
3144293JTRSVLE
Adder
0.423
3144293JTRSVLE
Adder
0.334
3142543TWELFTH
Solar/Wind Harmer
-0.002
972135AH1-637 GEN
Solar/Wind Harmer
1.907
3142416OLDCHRC
Solar/Wind Harmer
-0.047
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3150851SPRUNCC
Adder
0.704
957971AF2-091 GEN
Solar/Wind Harmer
1.651
3146926FARMVIL
Solar/Wind Harmer
-0.01
3143526WINTERP
Solar/Wind Harmer
-0.072
CPLELTFEXP_CPLE->PJM
CLTF
13.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.498
LAGNLTFEXP_LAGN->PJM
CLTF
7.839
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.295
TVALTFEXP_TVA->PJM
CLTF
3.897
NYPJM->LTFIMP_NY
CLTF
2.292
LGEELTFEXP_LGEE->PJM
CLTF
1.026
WECLTFEXP_WEC->PJM
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.096
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.007
MECLTFEXP_MEC->PJM
CLTF
3.116
SIGELTFEXP_SIGE->PJM
CLTF
0.09

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.34 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:4267.68
MW Contribution:
244.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150991CHESPKB
50/50
4.053
3150991CHESPKB
50/50
3.955
316294AC1-161 GEN
Solar/Wind Harmer
14.414
316185AD1-033 GEN
Solar/Wind Harmer
4.326
3145506HICKORY
Solar/Wind Harmer
-0.163
3145506HICKORY
Solar/Wind Harmer
-0.098
3145506HICKORY
Solar/Wind Harmer
-0.024
316339AD2-160 GEN
Solar/Wind Harmer
2.736
316388AE2-253 GEN
Solar/Wind Harmer
2.736
3137176SLIGO L2192
Solar/Wind Harmer
-0.16
3146456SLIGO L269
Solar/Wind Harmer
4.778
3130086AYDLETT
Solar/Wind Harmer
-0.161
3146386ELIZ CT
Solar/Wind Harmer
-0.04
316431W1029_GEN1
Solar/Wind Harmer
7.028
316433W1029_GEN2
Solar/Wind Harmer
7.028
316435W1029_GEN3
Solar/Wind Harmer
7.028
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
315835AF2-110_GEN
Solar/Wind Harmer
4.807
3146626S HERTFORD
Solar/Wind Harmer
-0.038
3146626S HERTFORD
Solar/Wind Harmer
-0.038
315976AC1-164 GENA
Solar/Wind Harmer
8.571
316169AC1-164_GENC
Solar/Wind Harmer
7.405
3146376EDENTON
Solar/Wind Harmer
1.093
3146376EDENTON
Solar/Wind Harmer
1.093
316349AD2-085 GEN
Solar/Wind Harmer
3.211
315742AE1-103 GEN
Solar/Wind Harmer
8.513
316156AD2-030 GEN
Solar/Wind Harmer
0.952
315666AE1-190 GEN
Solar/Wind Harmer
1.064
315614AA2-178 GEN
Solar/Wind Harmer
3.809
316441AF1-014 GEN
Solar/Wind Harmer
2.37
316065AD1-022 GEN
Solar/Wind Harmer
16.799
316033AB2-134 GEN
Solar/Wind Harmer
10.639
972185AH1-677 GEN
Adder
16.261
316083AB2-161 GEN
Solar/Wind Harmer
5.277
316487AF1-042 GEN
Solar/Wind Harmer
4.269
3145893MURPHYS
Solar/Wind Harmer
0.898
3145893MURPHYS
Solar/Wind Harmer
-0.058
972187AH1-678 GEN
Adder
8.129
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316140AB2-099
Solar/Wind Harmer
0.213
3142946ENON
Solar/Wind Harmer
-0.003
970933AG2-581 GEN
Solar/Wind Harmer
28.982
3144356SAPONY
Solar/Wind Harmer
1.057
316315AB2-025 C
Solar/Wind Harmer
0.815
3150341NORNECKC1
Adder
2.761
3150341NORNECKC1
Adder
2.739
3145933PARMELE
Solar/Wind Harmer
-0.058
3145933PARMELE
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316365GEN2_N
Solar/Wind Harmer
1.969
962571AG1-106 GEN
Solar/Wind Harmer
4.16
3145593CAROLNA
Solar/Wind Harmer
-0.029
972263AH1-716 GEN
50/50
244.812
3151081ELIZAR1
50/50
35.575
3151091ELIZAR2
50/50
34.957
941591AE2-156 GEN
50/50
32.462
3151201GRAVEL4
50/50
25.372
316382AG1-145 C
Solar/Wind Harmer
1.244
316159AE1-175 C
Solar/Wind Harmer
1.107
316316AC1-027 C
Solar/Wind Harmer
1.256
316018AA1-139 ULT2
Solar/Wind Harmer
3.469
957871AF2-081 GEN
Solar/Wind Harmer
20.303
3146406KITTY HAWK
Solar/Wind Harmer
0.034
313526AB2-022
Solar/Wind Harmer
1.067
3146396TANGLEW
Solar/Wind Harmer
0.723
3145176PASQUOTANK
Solar/Wind Harmer
-0.024
3146486SUNBURY
Solar/Wind Harmer
-0.039
3146486SUNBURY
Solar/Wind Harmer
-0.039
957831AF2-077 GEN
Solar/Wind Harmer
1.177
3138283WHITEMARSH
Solar/Wind Harmer
0.061
316236AE1-162_GEN
Solar/Wind Harmer
1.157
971445AH1-216 GEN
Solar/Wind Harmer
23.731
315800Z1-036_GEN1
Solar/Wind Harmer
9.181
3151221GRAVEL6
Adder
23.883
3151191GRAVEL3
Adder
23.608
3151211GRAVEL5
Adder
23.608
3130156CHOWAN
Solar/Wind Harmer
-0.037
3130156CHOWAN
Solar/Wind Harmer
-0.037
316311AC2-079 GEN
Solar/Wind Harmer
18.266
315833AF1-017_GEN
Solar/Wind Harmer
6.868
316059AD1-063 C
Solar/Wind Harmer
0.811
957601AF2-054 GEN
Solar/Wind Harmer
1.069
3141873WAN 176
Solar/Wind Harmer
-0.007
3141913WHIT STONE
Solar/Wind Harmer
-0.035
3138133OCRAN
Solar/Wind Harmer
-0.01
3143873LANEXA
Solar/Wind Harmer
-0.02
3130546PLYMOUTH
Solar/Wind Harmer
-0.034
315732AD1-074 GEN1
Solar/Wind Harmer
6.879
315733AD1-074 GEN2
Solar/Wind Harmer
6.879
3141783LANCAST
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.013
970533AG2-339 GEN
Solar/Wind Harmer
22.635
3146206CASHIE
Solar/Wind Harmer
-0.033
970601AG2-382 GEN
Solar/Wind Harmer
14.576
970673AG2-436 GEN
Solar/Wind Harmer
72.677
315697AD1-025 GEN
Solar/Wind Harmer
6.668
970657AG2-426 GEN
Solar/Wind Harmer
2.076
316318V4-068
Solar/Wind Harmer
0.802
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
60.041
316463AE2-346 GEN
Solar/Wind Harmer
0.511
3145513AHOSKIE
Solar/Wind Harmer
0.276
961941AG1-037 GEN
Solar/Wind Harmer
0.238
3145513AHOSKIE
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3142433PROV 92
Adder
0.541
3142433PROV 92
Adder
0.541
316174AB2-169 GEN
Solar/Wind Harmer
4.791
3146043SEABORD
Solar/Wind Harmer
-0.03
970085AG2-068 GEN
Solar/Wind Harmer
18.949
970581AG2-369 GEN
Solar/Wind Harmer
16.297
315814AE2-033 C
Solar/Wind Harmer
28.178
3141813NORNECK
Solar/Wind Harmer
-0.03
3146033SCOT NK
Solar/Wind Harmer
-0.117
316426AA2-053 GEN
Solar/Wind Harmer
2.948
315652AC1-086 GEN
Solar/Wind Harmer
32.554
3137643SOCKMAN
Solar/Wind Harmer
-0.114
3145796HORNRTN
Solar/Wind Harmer
-0.091
3145796HORNRTN
Solar/Wind Harmer
-0.011
316210AC1-098 GEN
Solar/Wind Harmer
4.452
3145746EVERETS
Solar/Wind Harmer
-0.112
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
3143316POE
Solar/Wind Harmer
-0.111
946281AF1-292 GEN
Solar/Wind Harmer
0.635
316274AC1-208 GEN
Solar/Wind Harmer
3.002
957861AF2-080 GEN
Solar/Wind Harmer
12.007
316327AA2-057 GEN
Solar/Wind Harmer
2.712
3145573BETHELC
Solar/Wind Harmer
-0.027
3145573BETHELC
Solar/Wind Harmer
-0.027
970831AG2-522 GEN
Solar/Wind Harmer
13.172
316486AD2-202 GEN
Solar/Wind Harmer
0.666
315839AE2-212 C
Solar/Wind Harmer
0.764
316238AB2-078_GEN
Solar/Wind Harmer
0.695
316239AB2-077_GEN
Solar/Wind Harmer
0.695
3147173SINAI
Solar/Wind Harmer
-0.021
3147243WELCO
Solar/Wind Harmer
-0.013
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
14.579
970681AG2-440 GEN
Solar/Wind Harmer
9.677
946301AF1-294 GEN
Solar/Wind Harmer
5.106
961791AG1-021 GEN
Solar/Wind Harmer
2.491
971285AH1-108 GEN
Adder
1.152
270455AD2-022 GEN
Solar/Wind Harmer
2.996
270457AD2-023 GEN
Solar/Wind Harmer
1.519
944491AF1-114 GEN
Solar/Wind Harmer
4.855
316233AE1-074 FULL
Solar/Wind Harmer
0.372
971281AH1-106 GEN
Solar/Wind Harmer
0.896
3150921YORKTN3
50/50
10.027
3144216WINCHST
50/50
1.482
3151101ELIZAR3
50/50
36.03
3151161SURRY 1
50/50
13.382
944581AF1-123 GEN
Solar/Wind Harmer
190.047
944601AF1-125 GEN
Solar/Wind Harmer
187.081
3142956BIRDNECK
Solar/Wind Harmer
2.201
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
3.277
3146456SLIGO L269
Solar/Wind Harmer
-0.04
971153AH1-033 GEN
Solar/Wind Harmer
4.682
3144536CHRHLND
Solar/Wind Harmer
-0.006
316305AF2-043 C
Solar/Wind Harmer
1.199
316246AF1-032 C
Solar/Wind Harmer
0.804
316320Y1-086
Solar/Wind Harmer
2.322
316321Z2-027
Solar/Wind Harmer
1.058
3146516WINFALL
Solar/Wind Harmer
-0.039
3145336SMITFLD
Solar/Wind Harmer
-0.015
3146626S HERTFORD
Solar/Wind Harmer
-0.038
3151171GRAVELC
Adder
4.595
3146376EDENTON
Solar/Wind Harmer
-0.037
3145273HOLLAND
Solar/Wind Harmer
-0.027
3141766HARMONY
Solar/Wind Harmer
3.201
3141873WAN 176
Solar/Wind Harmer
4.243
961611AG1-000B GEN
Solar/Wind Harmer
7.457
316203AE2-005 GEN
Solar/Wind Harmer
14.824
3141843SHACKLE
Adder
1.599
315735AD1-075 GEN1
Solar/Wind Harmer
3.438
944011AF1-069 GEN
Solar/Wind Harmer
19.775
3146206CASHIE
Solar/Wind Harmer
-0.033
970657AG2-426 GEN
Solar/Wind Harmer
6.652
3156081AA2-088 GEN
Solar/Wind Harmer
10.624
316484AD2-074 GEN
Solar/Wind Harmer
8.159
961951AG1-038 GEN
Solar/Wind Harmer
4.269
3145893MURPHYS
Solar/Wind Harmer
0.225
3145893MURPHYS
Solar/Wind Harmer
-0.032
315778AD1-151 GEN
Solar/Wind Harmer
28.569
3146173TUNIS
Solar/Wind Harmer
-0.032
3145963POPLR C
Solar/Wind Harmer
-0.031
3142946ENON
Solar/Wind Harmer
-0.01
3142433PROV 92
Adder
0.541
3142433PROV 92
Adder
0.541
3146263WOODLND
Solar/Wind Harmer
-0.031
970917AG2-570 GEN
Solar/Wind Harmer
76.913
316458AB2-190 GEN2
Solar/Wind Harmer
3.101
316317KELFORD C
Solar/Wind Harmer
1.408
3145823KELFORD
Solar/Wind Harmer
-0.03
316075AC2-137 C
Solar/Wind Harmer
0.817
315813AE1-149 C
Solar/Wind Harmer
18.895
316077AC2-138 C
Solar/Wind Harmer
0.624
3150351NORNECKC2
Adder
2.673
3145933PARMELE
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
316190AA2-174 GEN
Solar/Wind Harmer
0.359
316011AB1-132 GEN
Solar/Wind Harmer
6.043
316181AB2-040 GEN
Solar/Wind Harmer
3.975
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.028
316212AC1-099_GEN
Solar/Wind Harmer
2.474
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
966621AG1-532 GEN
Solar/Wind Harmer
0.575
970133AG2-095 GEN
Solar/Wind Harmer
3.184
316420AA1-050 GEN
Solar/Wind Harmer
3.076
315722AD1-056 GEN
Solar/Wind Harmer
9.578
3147043LAWRENC
Solar/Wind Harmer
-0.016
3146073TAR RVR
Solar/Wind Harmer
-0.027
3146083TARBORO
Solar/Wind Harmer
-0.027
316478AD1-087 GEN
Solar/Wind Harmer
2.275
3146233WITAKRS
Solar/Wind Harmer
0.551
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
961601AG1-000A GEN
Solar/Wind Harmer
10.225
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
970293AG2-193 GEN
Solar/Wind Harmer
3.077
316223AC1-118
Solar/Wind Harmer
0.637
3141906WESTMOR
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
17.58
3143096IRON208
Adder
0.838
3143096IRON208
Adder
0.821
970257AG2-171 GEN
Solar/Wind Harmer
8.026
971775AH1-396 GEN
Solar/Wind Harmer
1.51
959311AF2-222 GEN
Solar/Wind Harmer
22.112
316003AC1-222 GEN
Solar/Wind Harmer
1.964
3144293JTRSVLE
Adder
0.423
316222AC1-221 GEN
Solar/Wind Harmer
2.006
316283AC2-100 C
Solar/Wind Harmer
1.863
3147133PAMPLIN
Solar/Wind Harmer
-0.061
971683AH1-343 GEN
Solar/Wind Harmer
8.075
3142416OLDCHRC
Solar/Wind Harmer
1.817
942461AE2-259 GEN
Solar/Wind Harmer
2.708
3150861SPRUNCD
Adder
0.704
3146926FARMVIL
Solar/Wind Harmer
-0.01
316123AC1-075 GEN
Solar/Wind Harmer
1.681
3152331SURRY 2
50/50
17.624
3150981CHESPKA
50/50
4.831
315773AC2-141 GEN
Solar/Wind Harmer
18.651
971317AH1-138 GEN
Solar/Wind Harmer
5.253
3138126ROCKLANDING
Solar/Wind Harmer
0.128
944591AF1-124 GEN
Solar/Wind Harmer
190.732
316375AC2-012 GEN
Solar/Wind Harmer
14.168
316036AC1-147 C
Solar/Wind Harmer
1.102
3146456SLIGO L269
Solar/Wind Harmer
-0.04
319010AE1-072 C
Solar/Wind Harmer
8.153
316072AD1-144
Solar/Wind Harmer
0.8
3146516WINFALL
Solar/Wind Harmer
-0.124
3146516WINFALL
Solar/Wind Harmer
-0.039
3145336SMITFLD
Solar/Wind Harmer
-0.153
316093AE2-104_GEN
Solar/Wind Harmer
11.18
939411AE1-173 GEN
Solar/Wind Harmer
189.867
315975AC1-164 GENB
Solar/Wind Harmer
0.254
315611Z1-036_GEN2
Solar/Wind Harmer
9.181
3151171GRAVELC
Adder
3.494
940641AE2-051 GEN
Solar/Wind Harmer
34.581
3130156CHOWAN
Solar/Wind Harmer
-0.037
316314AB2-024 C
Solar/Wind Harmer
3.085
3141766HARMONY
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
17.476
315662AE1-191 GEN
Solar/Wind Harmer
4.258
316280AD1-041 GEN
Solar/Wind Harmer
2.661
315816AE2-034 GEN
Solar/Wind Harmer
2.857
3145663CRESWEL
Solar/Wind Harmer
-0.099
971163AH1-040 GEN
Solar/Wind Harmer
33.187
971777AH1-397 GEN
Solar/Wind Harmer
4.102
3138133OCRAN
Solar/Wind Harmer
-0.021
315737AD1-076 GEN
Solar/Wind Harmer
6.467
941031AE2-094 GEN
Solar/Wind Harmer
63.112
3146206CASHIE
Solar/Wind Harmer
-0.033
971547AH1-271 GEN
Solar/Wind Harmer
8.329
316369SG1_INVT
Solar/Wind Harmer
5.892
316381AD1-082 GEN
Solar/Wind Harmer
2.975
3156021HOLLOMANSOL
Solar/Wind Harmer
4.329
3145893MURPHYS
Solar/Wind Harmer
-0.128
3145893MURPHYS
Solar/Wind Harmer
0.955
971069AG2-661 GEN
Solar/Wind Harmer
5.079
3146173TUNIS
Solar/Wind Harmer
-0.032
962861AG1-135 GEN
Solar/Wind Harmer
11.879
3145963POPLR C
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
316404AE1-155 C
Solar/Wind Harmer
5.997
958261AF2-120 GEN
Solar/Wind Harmer
12.173
3142433PROV 92
Solar/Wind Harmer
-0.125
3142433PROV 92
Adder
0.541
3142433PROV 92
Adder
0.541
3146263WOODLND
Solar/Wind Harmer
-0.031
970919AG2-571 GEN
Solar/Wind Harmer
9.736
316132AB2-190 GEN1
Solar/Wind Harmer
3.101
3145823KELFORD
Solar/Wind Harmer
-0.03
964211AG1-282 GEN
Solar/Wind Harmer
0.914
3141726DUNNSVL
Solar/Wind Harmer
-0.121
970087AG2-069 GEN
Solar/Wind Harmer
28.424
315607AA1-063A GEN
Solar/Wind Harmer
3.045
3150351NORNECKC2
Adder
2.629
3146293MARTNCO
Solar/Wind Harmer
0.182
316023GEN1_S
Solar/Wind Harmer
1.969
944631AF1-128 GEN
Adder
122.194
3145783HORNRTN
Solar/Wind Harmer
-0.029
316087AB2-174 GEN
Solar/Wind Harmer
4.056
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
960081AF2-299 GEN
Solar/Wind Harmer
3.189
957481AF2-042 GEN
Solar/Wind Harmer
86.687
316494AC1-189 GEN
Solar/Wind Harmer
2.953
3147043LAWRENC
Adder
2.154
316337AD2-073 GEN
Solar/Wind Harmer
0.717
961671AG1-007 GEN
Solar/Wind Harmer
0.337
3146083TARBORO
Solar/Wind Harmer
-0.027
3145493TOT1
Solar/Wind Harmer
0.791
316319Z2-044 C
Solar/Wind Harmer
1.453
3146233WITAKRS
Solar/Wind Harmer
-0.104
315693AD1-088 GEN
Solar/Wind Harmer
13.085
316129AC1-054 GEN
Solar/Wind Harmer
2.275
971065AG2-659 GEN
Solar/Wind Harmer
12.889
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
316359AB2-059 GEN
Solar/Wind Harmer
3.451
3142053HEARTS
Solar/Wind Harmer
0.302
315671AE2-027_GEN
Solar/Wind Harmer
4.607
316131AB2-060 GEN
Solar/Wind Harmer
2.473
3143096IRON208
Adder
0.838
970401AG2-262 GEN
Solar/Wind Harmer
1.444
315785AD2-033 C
Solar/Wind Harmer
4.91
316034AC1-036 C
Solar/Wind Harmer
0.396
970685AG2-442 GEN
Solar/Wind Harmer
17.775
971563AH1-280 GEN
Solar/Wind Harmer
2.491
3144293JTRSVLE
Adder
0.423
3144293JTRSVLE
Adder
0.334
3142543TWELFTH
Solar/Wind Harmer
-0.002
972135AH1-637 GEN
Solar/Wind Harmer
1.907
3142416OLDCHRC
Solar/Wind Harmer
-0.047
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3150851SPRUNCC
Adder
0.704
957971AF2-091 GEN
Solar/Wind Harmer
1.651
3146926FARMVIL
Solar/Wind Harmer
-0.01
3143526WINTERP
Solar/Wind Harmer
-0.072
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
0.239
3145783HORNRTN
Solar/Wind Harmer
3.398
3145783HORNRTN
Solar/Wind Harmer
2.718
3145783HORNRTN
Solar/Wind Harmer
0.849
3145783HORNRTN
Solar/Wind Harmer
0.34
313506AB2-031 GEN
Solar/Wind Harmer
2.288
3145796HORNRTN
Solar/Wind Harmer
-0.085
316005AA1-067
Solar/Wind Harmer
0.572
970099AG2-077 GEN
Solar/Wind Harmer
34.675
315724AD1-057 GEN
Solar/Wind Harmer
5.268
3145493TOT1
Solar/Wind Harmer
0.412
3145453TOT5
Solar/Wind Harmer
0.247
3145603CNETO
Solar/Wind Harmer
0.165
961601AG1-000A GEN
Solar/Wind Harmer
10.097
316049AB1-081 GEN
Solar/Wind Harmer
2.762
316263AC1-034 GEN
Solar/Wind Harmer
12.031
315687AD1-152 GEN
Solar/Wind Harmer
2.96
316240AF1-291 C
Solar/Wind Harmer
0.715
944641AF1-129 GEN
Adder
98.424
316237AB2-079_GEN
Solar/Wind Harmer
0.695
313527AB2-043 GEN
Solar/Wind Harmer
3.751
962561AG1-105 GEN
Solar/Wind Harmer
12.531
964791AG1-342 GEN
Solar/Wind Harmer
4.727
3146843MT LREL
Solar/Wind Harmer
-0.022
3146843MT LREL
Solar/Wind Harmer
-0.022
316118AC1-105 GEN
Solar/Wind Harmer
1.493
316248AF1-058 C
Solar/Wind Harmer
0.644
970323AG2-213 GEN
Solar/Wind Harmer
10.701
970301AG2-198 GEN
Solar/Wind Harmer
10.283
958211AF2-115 GEN
Solar/Wind Harmer
3.114
3144293JTRSVLE
Adder
0.423
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3147133PAMPLIN
Solar/Wind Harmer
-0.016
3150691DARBY 3
Adder
12.389
3150701DARBY 4
Adder
12.36
3150681DARBY 2
Adder
12.346
3150671DARBY 1
Adder
12.332
316312AB1-027
Solar/Wind Harmer
0.606
3142366NRTHEST
Adder
0.476
942751AE2-291 GEN
Solar/Wind Harmer
9.027
3143526WINTERP
Solar/Wind Harmer
-0.072
CPLELTFEXP_CPLE->PJM
CLTF
13.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.498
LAGNLTFEXP_LAGN->PJM
CLTF
7.839
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.295
TVALTFEXP_TVA->PJM
CLTF
3.897
NYPJM->LTFIMP_NY
CLTF
2.292
LGEELTFEXP_LGEE->PJM
CLTF
1.026
WECLTFEXP_WEC->PJM
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.096
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.007
MECLTFEXP_MEC->PJM
CLTF
3.116
SIGELTFEXP_SIGE->PJM
CLTF
0.09

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.11 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:4041.18
MW Contribution:
237.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
237.47
3151081ELIZAR1
50/50
34.251
3151091ELIZAR2
50/50
33.656
941591AE2-156 GEN
50/50
31.247
3151201GRAVEL4
50/50
23.968
316382AG1-145 C
Solar/Wind Harmer
1.188
316159AE1-175 C
Solar/Wind Harmer
1.058
316316AC1-027 C
Solar/Wind Harmer
1.21
316018AA1-139 ULT2
Solar/Wind Harmer
3.34
957871AF2-081 GEN
Solar/Wind Harmer
19.546
3146406KITTY HAWK
Solar/Wind Harmer
0.032
313526AB2-022
Solar/Wind Harmer
1.025
3146396TANGLEW
Solar/Wind Harmer
0.695
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
3146486SUNBURY
Solar/Wind Harmer
-0.038
3146486SUNBURY
Solar/Wind Harmer
-0.038
957831AF2-077 GEN
Solar/Wind Harmer
1.123
3138283WHITEMARSH
Solar/Wind Harmer
0.058
316236AE1-162_GEN
Solar/Wind Harmer
1.102
971445AH1-216 GEN
Solar/Wind Harmer
22.576
315800Z1-036_GEN1
Solar/Wind Harmer
8.791
3130156CHOWAN
Solar/Wind Harmer
-0.035
3130156CHOWAN
Solar/Wind Harmer
-0.035
3151221GRAVEL6
Adder
22.562
3151191GRAVEL3
Adder
22.302
3151211GRAVEL5
Adder
22.302
316311AC2-079 GEN
Solar/Wind Harmer
17.214
315833AF1-017_GEN
Solar/Wind Harmer
6.47
316059AD1-063 C
Solar/Wind Harmer
0.767
957601AF2-054 GEN
Solar/Wind Harmer
1.013
3141873WAN 176
Solar/Wind Harmer
-0.007
3141913WHIT STONE
Solar/Wind Harmer
-0.033
3138133OCRAN
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.033
970533AG2-339 GEN
Solar/Wind Harmer
21.942
315732AD1-074 GEN1
Solar/Wind Harmer
6.552
315733AD1-074 GEN2
Solar/Wind Harmer
6.552
3141783LANCAST
Solar/Wind Harmer
-0.019
3141783LANCAST
Solar/Wind Harmer
-0.013
970673AG2-436 GEN
Solar/Wind Harmer
70.413
3143873LANEXA
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
13.854
971967AH1-528 GEN
Solar/Wind Harmer
58.009
315697AD1-025 GEN
Solar/Wind Harmer
6.174
316318V4-068
Solar/Wind Harmer
0.757
3145893MURPHYS
Solar/Wind Harmer
-0.082
3145893MURPHYS
Solar/Wind Harmer
-0.03
970657AG2-426 GEN
Solar/Wind Harmer
1.911
316463AE2-346 GEN
Solar/Wind Harmer
0.483
3145513AHOSKIE
Solar/Wind Harmer
0.261
961941AG1-037 GEN
Solar/Wind Harmer
0.225
3145513AHOSKIE
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.059
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.03
316174AB2-169 GEN
Solar/Wind Harmer
4.551
970085AG2-068 GEN
Solar/Wind Harmer
18.304
970581AG2-369 GEN
Solar/Wind Harmer
15.741
3142433PROV 92
Adder
0.499
3142433PROV 92
Adder
0.499
3146043SEABORD
Solar/Wind Harmer
-0.029
3141813NORNECK
Solar/Wind Harmer
-0.028
3146033SCOT NK
Solar/Wind Harmer
-0.11
316426AA2-053 GEN
Solar/Wind Harmer
2.761
315814AE2-033 C
Solar/Wind Harmer
25.013
315652AC1-086 GEN
Solar/Wind Harmer
30.211
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316210AC1-098 GEN
Solar/Wind Harmer
4.187
3137643SOCKMAN
Solar/Wind Harmer
-0.106
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.01
316274AC1-208 GEN
Solar/Wind Harmer
2.818
946281AF1-292 GEN
Solar/Wind Harmer
0.584
957861AF2-080 GEN
Solar/Wind Harmer
11.342
316327AA2-057 GEN
Solar/Wind Harmer
2.549
3145573BETHELC
Solar/Wind Harmer
-0.025
3145573BETHELC
Solar/Wind Harmer
-0.025
316486AD2-202 GEN
Solar/Wind Harmer
0.635
3143316POE
Solar/Wind Harmer
-0.097
970831AG2-522 GEN
Solar/Wind Harmer
12.347
315839AE2-212 C
Solar/Wind Harmer
0.658
316238AB2-078_GEN
Solar/Wind Harmer
0.648
316239AB2-077_GEN
Solar/Wind Harmer
0.648
3147173SINAI
Solar/Wind Harmer
-0.02
3147243WELCO
Solar/Wind Harmer
-0.013
3144303KENBRDG
Solar/Wind Harmer
-0.016
970683AG2-441 GEN
Solar/Wind Harmer
13.337
970681AG2-440 GEN
Solar/Wind Harmer
8.852
946301AF1-294 GEN
Solar/Wind Harmer
4.642
961791AG1-021 GEN
Solar/Wind Harmer
2.265
270455AD2-022 GEN
Solar/Wind Harmer
2.837
270457AD2-023 GEN
Solar/Wind Harmer
1.439
944491AF1-114 GEN
Solar/Wind Harmer
4.581
3150921YORKTN3
50/50
9.622
3144216WINCHST
50/50
1.42
3151101ELIZAR3
50/50
34.689
3151161SURRY 1
50/50
12.641
944581AF1-123 GEN
Solar/Wind Harmer
183.421
944601AF1-125 GEN
Solar/Wind Harmer
180.558
3142956BIRDNECK
Solar/Wind Harmer
2.119
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
3.155
3146456SLIGO L269
Solar/Wind Harmer
-0.039
971153AH1-033 GEN
Solar/Wind Harmer
4.506
3144536CHRHLND
Solar/Wind Harmer
-0.006
316305AF2-043 C
Solar/Wind Harmer
1.152
316246AF1-032 C
Solar/Wind Harmer
0.773
316320Y1-086
Solar/Wind Harmer
2.232
316321Z2-027
Solar/Wind Harmer
1.016
3146516WINFALL
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3145336SMITFLD
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.035
3145273HOLLAND
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
4.341
3141766HARMONY
Solar/Wind Harmer
3.029
3141873WAN 176
Solar/Wind Harmer
4.019
961611AG1-000B GEN
Solar/Wind Harmer
6.993
316203AE2-005 GEN
Solar/Wind Harmer
13.985
3141843SHACKLE
Adder
1.508
944011AF1-069 GEN
Solar/Wind Harmer
19.169
315735AD1-075 GEN1
Solar/Wind Harmer
3.275
3146206CASHIE
Solar/Wind Harmer
-0.032
3156081AA2-088 GEN
Solar/Wind Harmer
10.042
316484AD2-074 GEN
Solar/Wind Harmer
7.721
961951AG1-038 GEN
Solar/Wind Harmer
4.04
3145893MURPHYS
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
-0.03
970657AG2-426 GEN
Solar/Wind Harmer
6.122
3146173TUNIS
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
970917AG2-570 GEN
Solar/Wind Harmer
74.323
315778AD1-151 GEN
Solar/Wind Harmer
26.303
3146263WOODLND
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.499
3142433PROV 92
Adder
0.499
3142946ENON
Solar/Wind Harmer
-0.009
316317KELFORD C
Solar/Wind Harmer
1.329
3145823KELFORD
Solar/Wind Harmer
-0.029
316458AB2-190 GEN2
Solar/Wind Harmer
2.83
316077AC2-138 C
Solar/Wind Harmer
0.59
3150351NORNECKC2
Adder
2.527
316075AC2-137 C
Solar/Wind Harmer
0.752
3145933PARMELE
Solar/Wind Harmer
-0.028
316190AA2-174 GEN
Solar/Wind Harmer
0.336
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
315813AE1-149 C
Solar/Wind Harmer
16.979
316011AB1-132 GEN
Solar/Wind Harmer
5.609
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316212AC1-099_GEN
Solar/Wind Harmer
2.326
3145796HORNRTN
Solar/Wind Harmer
-0.105
3145796HORNRTN
Solar/Wind Harmer
-0.026
316181AB2-040 GEN
Solar/Wind Harmer
3.682
966621AG1-532 GEN
Solar/Wind Harmer
0.529
316420AA1-050 GEN
Solar/Wind Harmer
2.902
970133AG2-095 GEN
Solar/Wind Harmer
2.852
315722AD1-056 GEN
Solar/Wind Harmer
8.957
3146073TAR RVR
Solar/Wind Harmer
-0.025
3146083TARBORO
Solar/Wind Harmer
-0.025
316478AD1-087 GEN
Solar/Wind Harmer
2.168
3146233WITAKRS
Solar/Wind Harmer
0.518
3146233WITAKRS
Solar/Wind Harmer
-0.017
3147043LAWRENC
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.016
961601AG1-000A GEN
Solar/Wind Harmer
9.615
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
316223AC1-118
Solar/Wind Harmer
0.602
3141906WESTMOR
Solar/Wind Harmer
-0.009
970293AG2-193 GEN
Solar/Wind Harmer
2.739
964241AG1-285 GEN
Solar/Wind Harmer
16.313
970257AG2-171 GEN
Solar/Wind Harmer
7.387
971775AH1-396 GEN
Solar/Wind Harmer
1.39
959311AF2-222 GEN
Solar/Wind Harmer
20.317
3143096IRON208
Adder
0.711
3143096IRON208
Adder
0.696
316003AC1-222 GEN
Solar/Wind Harmer
1.854
316222AC1-221 GEN
Solar/Wind Harmer
1.904
316283AC2-100 C
Solar/Wind Harmer
1.768
3144293JTRSVLE
Adder
0.385
971683AH1-343 GEN
Solar/Wind Harmer
7.609
3147133PAMPLIN
Solar/Wind Harmer
-0.055
942461AE2-259 GEN
Solar/Wind Harmer
2.414
3142416OLDCHRC
Solar/Wind Harmer
1.574
316123AC1-075 GEN
Solar/Wind Harmer
1.576
3146926FARMVIL
Solar/Wind Harmer
-0.009
3152331SURRY 2
50/50
17.12
3150981CHESPKA
50/50
4.649
315773AC2-141 GEN
Solar/Wind Harmer
18.095
944591AF1-124 GEN
Solar/Wind Harmer
184.081
971317AH1-138 GEN
Solar/Wind Harmer
5.037
3138126ROCKLANDING
Solar/Wind Harmer
0.123
316375AC2-012 GEN
Solar/Wind Harmer
13.635
316036AC1-147 C
Solar/Wind Harmer
1.061
3146456SLIGO L269
Solar/Wind Harmer
-0.039
319010AE1-072 C
Solar/Wind Harmer
7.846
316072AD1-144
Solar/Wind Harmer
0.766
3146516WINFALL
Solar/Wind Harmer
-0.119
3146516WINFALL
Solar/Wind Harmer
-0.037
939411AE1-173 GEN
Solar/Wind Harmer
183.964
316093AE2-104_GEN
Solar/Wind Harmer
10.68
3145336SMITFLD
Solar/Wind Harmer
-0.146
940641AE2-051 GEN
Solar/Wind Harmer
33.573
315611Z1-036_GEN2
Solar/Wind Harmer
8.791
315975AC1-164 GENB
Solar/Wind Harmer
0.239
3130156CHOWAN
Solar/Wind Harmer
-0.035
3151171GRAVELC
Adder
3.301
316314AB2-024 C
Solar/Wind Harmer
2.917
3141766HARMONY
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.727
3145663CRESWEL
Solar/Wind Harmer
-0.094
971163AH1-040 GEN
Solar/Wind Harmer
31.686
315662AE1-191 GEN
Solar/Wind Harmer
4.024
316280AD1-041 GEN
Solar/Wind Harmer
2.515
961611AG1-000B GEN
Solar/Wind Harmer
16.39
971777AH1-397 GEN
Solar/Wind Harmer
3.87
3138133OCRAN
Solar/Wind Harmer
-0.019
941031AE2-094 GEN
Solar/Wind Harmer
61.179
315737AD1-076 GEN
Solar/Wind Harmer
6.16
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
7.917
316369SG1_INVT
Solar/Wind Harmer
5.456
3156021HOLLOMANSOL
Solar/Wind Harmer
4.101
3145893MURPHYS
Solar/Wind Harmer
-0.121
3145893MURPHYS
Solar/Wind Harmer
0.902
3146173TUNIS
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
962861AG1-135 GEN
Solar/Wind Harmer
11.239
316381AD1-082 GEN
Solar/Wind Harmer
2.73
3145683EARLEYS
Solar/Wind Harmer
-0.03
970919AG2-571 GEN
Solar/Wind Harmer
9.408
316404AE1-155 C
Solar/Wind Harmer
5.673
958261AF2-120 GEN
Solar/Wind Harmer
11.516
971069AG2-661 GEN
Solar/Wind Harmer
4.676
970087AG2-069 GEN
Solar/Wind Harmer
27.456
3146263WOODLND
Solar/Wind Harmer
-0.029
3142433PROV 92
Solar/Wind Harmer
-0.115
3142433PROV 92
Adder
0.499
3142433PROV 92
Adder
0.499
964211AG1-282 GEN
Solar/Wind Harmer
0.864
3141726DUNNSVL
Solar/Wind Harmer
-0.114
3145823KELFORD
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.859
316132AB2-190 GEN1
Solar/Wind Harmer
2.83
3150351NORNECKC2
Adder
2.485
3146293MARTNCO
Solar/Wind Harmer
0.172
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145783HORNRTN
Solar/Wind Harmer
-0.027
316023GEN1_S
Solar/Wind Harmer
1.797
957481AF2-042 GEN
Solar/Wind Harmer
82.879
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.026
316087AB2-174 GEN
Solar/Wind Harmer
3.749
960081AF2-299 GEN
Solar/Wind Harmer
2.931
316494AC1-189 GEN
Solar/Wind Harmer
2.789
944631AF1-128 GEN
Adder
109.871
316337AD2-073 GEN
Solar/Wind Harmer
0.677
961671AG1-007 GEN
Solar/Wind Harmer
0.318
3146083TARBORO
Solar/Wind Harmer
-0.025
3145493TOT1
Solar/Wind Harmer
0.745
315693AD1-088 GEN
Solar/Wind Harmer
12.418
316319Z2-044 C
Solar/Wind Harmer
1.366
3146233WITAKRS
Solar/Wind Harmer
-0.098
3147043LAWRENC
Adder
1.987
316129AC1-054 GEN
Solar/Wind Harmer
2.134
971065AG2-659 GEN
Solar/Wind Harmer
12.093
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.246
3142053HEARTS
Solar/Wind Harmer
0.284
315671AE2-027_GEN
Solar/Wind Harmer
3.993
316131AB2-060 GEN
Solar/Wind Harmer
2.302
970401AG2-262 GEN
Solar/Wind Harmer
1.357
315785AD2-033 C
Solar/Wind Harmer
4.53
316034AC1-036 C
Solar/Wind Harmer
0.364
3143096IRON208
Adder
0.711
970685AG2-442 GEN
Solar/Wind Harmer
16.215
971563AH1-280 GEN
Solar/Wind Harmer
2.265
3144293JTRSVLE
Adder
0.385
3144293JTRSVLE
Adder
0.304
972135AH1-637 GEN
Solar/Wind Harmer
1.801
957971AF2-091 GEN
Solar/Wind Harmer
1.558
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
-0.009
3150991CHESPKB
50/50
3.9
3150991CHESPKB
50/50
3.807
316294AC1-161 GEN
Solar/Wind Harmer
13.985
316185AD1-033 GEN
Solar/Wind Harmer
4.167
3145506HICKORY
Solar/Wind Harmer
-0.157
3145506HICKORY
Solar/Wind Harmer
-0.094
3145506HICKORY
Solar/Wind Harmer
-0.023
316339AD2-160 GEN
Solar/Wind Harmer
2.634
316388AE2-253 GEN
Solar/Wind Harmer
2.634
3137176SLIGO L2192
Solar/Wind Harmer
-0.154
3146456SLIGO L269
Solar/Wind Harmer
4.598
3130086AYDLETT
Solar/Wind Harmer
-0.155
3146386ELIZ CT
Solar/Wind Harmer
-0.038
316431W1029_GEN1
Solar/Wind Harmer
6.745
316433W1029_GEN2
Solar/Wind Harmer
6.745
316435W1029_GEN3
Solar/Wind Harmer
6.745
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
315835AF2-110_GEN
Solar/Wind Harmer
4.592
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
315976AC1-164 GENA
Solar/Wind Harmer
8.066
316169AC1-164_GENC
Solar/Wind Harmer
6.969
3146376EDENTON
Solar/Wind Harmer
1.046
3146376EDENTON
Solar/Wind Harmer
1.046
315742AE1-103 GEN
Solar/Wind Harmer
8.097
316349AD2-085 GEN
Solar/Wind Harmer
3.025
316156AD2-030 GEN
Solar/Wind Harmer
0.902
315614AA2-178 GEN
Solar/Wind Harmer
3.637
315666AE1-190 GEN
Solar/Wind Harmer
1.006
316441AF1-014 GEN
Solar/Wind Harmer
2.236
316065AD1-022 GEN
Solar/Wind Harmer
15.98
972185AH1-677 GEN
Adder
15.741
972187AH1-678 GEN
Adder
7.864
316487AF1-042 GEN
Solar/Wind Harmer
4.04
316033AB2-134 GEN
Solar/Wind Harmer
9.851
3145893MURPHYS
Solar/Wind Harmer
0.848
3145893MURPHYS
Solar/Wind Harmer
-0.055
3146173TUNIS
Solar/Wind Harmer
-0.03
3146173TUNIS
Solar/Wind Harmer
-0.03
316140AB2-099
Solar/Wind Harmer
0.201
316083AB2-161 GEN
Solar/Wind Harmer
4.841
970933AG2-581 GEN
Solar/Wind Harmer
27.935
3142946ENON
Solar/Wind Harmer
-0.003
3150341NORNECKC1
Adder
2.611
3150341NORNECKC1
Adder
2.59
3145933PARMELE
Solar/Wind Harmer
-0.055
3145933PARMELE
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.027
3145593CAROLNA
Solar/Wind Harmer
-0.027
3145593CAROLNA
Solar/Wind Harmer
0.223
3144356SAPONY
Solar/Wind Harmer
0.937
316315AB2-025 C
Solar/Wind Harmer
0.723
962571AG1-106 GEN
Solar/Wind Harmer
3.86
316005AA1-067
Solar/Wind Harmer
0.542
3145783HORNRTN
Solar/Wind Harmer
3.177
3145783HORNRTN
Solar/Wind Harmer
2.541
3145783HORNRTN
Solar/Wind Harmer
0.794
3145783HORNRTN
Solar/Wind Harmer
0.318
316365GEN2_N
Solar/Wind Harmer
1.797
970099AG2-077 GEN
Solar/Wind Harmer
33.152
3145796HORNRTN
Solar/Wind Harmer
-0.079
313506AB2-031 GEN
Solar/Wind Harmer
2.12
315724AD1-057 GEN
Solar/Wind Harmer
4.926
3145493TOT1
Solar/Wind Harmer
0.389
3145453TOT5
Solar/Wind Harmer
0.233
3145603CNETO
Solar/Wind Harmer
0.156
961601AG1-000A GEN
Solar/Wind Harmer
9.494
316049AB1-081 GEN
Solar/Wind Harmer
2.597
316263AC1-034 GEN
Solar/Wind Harmer
11.316
315687AD1-152 GEN
Solar/Wind Harmer
2.817
316237AB2-079_GEN
Solar/Wind Harmer
0.648
313527AB2-043 GEN
Solar/Wind Harmer
3.495
962561AG1-105 GEN
Solar/Wind Harmer
11.755
964791AG1-342 GEN
Solar/Wind Harmer
4.44
3146843MT LREL
Solar/Wind Harmer
-0.021
3146843MT LREL
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
1.407
316240AF1-291 C
Solar/Wind Harmer
0.612
316248AF1-058 C
Solar/Wind Harmer
0.609
944641AF1-129 GEN
Adder
84
970323AG2-213 GEN
Solar/Wind Harmer
9.85
970301AG2-198 GEN
Solar/Wind Harmer
9.405
958211AF2-115 GEN
Solar/Wind Harmer
2.831
3144293JTRSVLE
Adder
0.385
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3150691DARBY 3
Adder
10.483
3150701DARBY 4
Adder
10.459
3150681DARBY 2
Adder
10.447
3150671DARBY 1
Adder
10.434
316312AB1-027
Solar/Wind Harmer
0.525
942751AE2-291 GEN
Solar/Wind Harmer
8.439
3142366NRTHEST
Adder
0.385
CPLELTFEXP_CPLE->PJM
CLTF
13
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.773
LAGNLTFEXP_LAGN->PJM
CLTF
7.329
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.787
TVALTFEXP_TVA->PJM
CLTF
3.639
NYPJM->LTFIMP_NY
CLTF
2.117
LGEELTFEXP_LGEE->PJM
CLTF
0.93
WECLTFEXP_WEC->PJM
CLTF
0.468
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.455
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.119
MECLTFEXP_MEC->PJM
CLTF
2.863
SIGELTFEXP_SIGE->PJM
CLTF
0.082

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.07 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:4003.16
MW Contribution:
238.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
17.121
3150981CHESPKA
50/50
4.645
315773AC2-141 GEN
Solar/Wind Harmer
17.914
971317AH1-138 GEN
Solar/Wind Harmer
5.168
3138126ROCKLANDING
Solar/Wind Harmer
0.126
944591AF1-124 GEN
Solar/Wind Harmer
183.011
316375AC2-012 GEN
Solar/Wind Harmer
13.623
316036AC1-147 C
Solar/Wind Harmer
1.06
3146456SLIGO L269
Solar/Wind Harmer
-0.039
319010AE1-072 C
Solar/Wind Harmer
7.824
316072AD1-144
Solar/Wind Harmer
0.771
315975AC1-164 GENB
Solar/Wind Harmer
0.256
3145336SMITFLD
Solar/Wind Harmer
-0.149
3146516WINFALL
Solar/Wind Harmer
-0.119
3146516WINFALL
Solar/Wind Harmer
-0.037
316093AE2-104_GEN
Solar/Wind Harmer
10.739
316314AB2-024 C
Solar/Wind Harmer
3.094
3151171GRAVELC
Adder
3.414
3141766HARMONY
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
8.787
315662AE1-191 GEN
Solar/Wind Harmer
4.259
316280AD1-041 GEN
Solar/Wind Harmer
2.662
939411AE1-173 GEN
Solar/Wind Harmer
177.059
3130156CHOWAN
Solar/Wind Harmer
-0.035
971777AH1-397 GEN
Solar/Wind Harmer
4.109
961611AG1-000B GEN
Solar/Wind Harmer
17.148
3138133OCRAN
Solar/Wind Harmer
-0.021
940641AE2-051 GEN
Solar/Wind Harmer
31.894
315816AE2-034 GEN
Solar/Wind Harmer
2.729
3145663CRESWEL
Solar/Wind Harmer
-0.094
971163AH1-040 GEN
Solar/Wind Harmer
31.702
316369SG1_INVT
Solar/Wind Harmer
5.825
315737AD1-076 GEN
Solar/Wind Harmer
6.168
971069AG2-661 GEN
Solar/Wind Harmer
5.038
962861AG1-135 GEN
Solar/Wind Harmer
11.91
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
7.936
3142433PROV 92
Solar/Wind Harmer
-0.126
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
316381AD1-082 GEN
Solar/Wind Harmer
2.884
316404AE1-155 C
Solar/Wind Harmer
6.014
958261AF2-120 GEN
Solar/Wind Harmer
12.208
941031AE2-094 GEN
Solar/Wind Harmer
57.605
3156021HOLLOMANSOL
Solar/Wind Harmer
4.118
316132AB2-190 GEN1
Solar/Wind Harmer
3.091
3145893MURPHYS
Solar/Wind Harmer
-0.122
3145893MURPHYS
Solar/Wind Harmer
0.908
964211AG1-282 GEN
Solar/Wind Harmer
0.92
3141726DUNNSVL
Solar/Wind Harmer
-0.122
3146173TUNIS
Solar/Wind Harmer
-0.03
3150991CHESPKB
50/50
3.897
3150991CHESPKB
50/50
3.803
316294AC1-161 GEN
Solar/Wind Harmer
13.845
316185AD1-033 GEN
Solar/Wind Harmer
4.154
3145506HICKORY
Solar/Wind Harmer
-0.157
3145506HICKORY
Solar/Wind Harmer
-0.094
3145506HICKORY
Solar/Wind Harmer
-0.023
316339AD2-160 GEN
Solar/Wind Harmer
2.626
316388AE2-253 GEN
Solar/Wind Harmer
2.626
3137176SLIGO L2192
Solar/Wind Harmer
-0.154
3146456SLIGO L269
Solar/Wind Harmer
4.585
3130086AYDLETT
Solar/Wind Harmer
-0.154
972263AH1-716 GEN
50/50
238.124
3151081ELIZAR1
50/50
34.197
3151091ELIZAR2
50/50
33.603
941591AE2-156 GEN
50/50
31.211
3151201GRAVEL4
50/50
24.792
316382AG1-145 C
Solar/Wind Harmer
1.231
316159AE1-175 C
Solar/Wind Harmer
1.096
316316AC1-027 C
Solar/Wind Harmer
1.207
316018AA1-139 ULT2
Solar/Wind Harmer
3.33
957871AF2-081 GEN
Solar/Wind Harmer
19.488
3146406KITTY HAWK
Solar/Wind Harmer
0.032
957831AF2-077 GEN
Solar/Wind Harmer
1.163
3138283WHITEMARSH
Solar/Wind Harmer
0.06
313526AB2-022
Solar/Wind Harmer
1.023
3146396TANGLEW
Solar/Wind Harmer
0.693
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
3146486SUNBURY
Solar/Wind Harmer
-0.038
3146486SUNBURY
Solar/Wind Harmer
-0.038
316236AE1-162_GEN
Solar/Wind Harmer
1.124
971445AH1-216 GEN
Solar/Wind Harmer
23.05
3151221GRAVEL6
Adder
23.337
3151191GRAVEL3
Adder
23.068
3151211GRAVEL5
Adder
23.068
316059AD1-063 C
Solar/Wind Harmer
0.812
957601AF2-054 GEN
Solar/Wind Harmer
1.068
3141873WAN 176
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
8.787
3130156CHOWAN
Solar/Wind Harmer
-0.035
3130156CHOWAN
Solar/Wind Harmer
-0.035
316311AC2-079 GEN
Solar/Wind Harmer
17.6
315833AF1-017_GEN
Solar/Wind Harmer
6.618
3141913WHIT STONE
Solar/Wind Harmer
-0.035
3138133OCRAN
Solar/Wind Harmer
-0.01
3143873LANEXA
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.013
3130546PLYMOUTH
Solar/Wind Harmer
-0.033
315697AD1-025 GEN
Solar/Wind Harmer
6.592
315732AD1-074 GEN1
Solar/Wind Harmer
6.561
315733AD1-074 GEN2
Solar/Wind Harmer
6.561
970657AG2-426 GEN
Solar/Wind Harmer
2.011
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
13.887
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
970533AG2-339 GEN
Solar/Wind Harmer
20.66
316318V4-068
Solar/Wind Harmer
0.763
3145893MURPHYS
Solar/Wind Harmer
-0.082
3145893MURPHYS
Solar/Wind Harmer
-0.031
970673AG2-436 GEN
Solar/Wind Harmer
66.368
316463AE2-346 GEN
Solar/Wind Harmer
0.486
3145513AHOSKIE
Solar/Wind Harmer
0.263
3150921YORKTN3
50/50
9.827
3144216WINCHST
50/50
1.452
3151101ELIZAR3
50/50
34.635
3151161SURRY 1
50/50
13.075
944581AF1-123 GEN
Solar/Wind Harmer
182.354
944601AF1-125 GEN
Solar/Wind Harmer
179.508
3142956BIRDNECK
Solar/Wind Harmer
2.115
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
3.145
3144536CHRHLND
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.039
971153AH1-033 GEN
Solar/Wind Harmer
4.493
316305AF2-043 C
Solar/Wind Harmer
1.151
316246AF1-032 C
Solar/Wind Harmer
0.772
316320Y1-086
Solar/Wind Harmer
2.227
316321Z2-027
Solar/Wind Harmer
1.014
3145336SMITFLD
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3151171GRAVELC
Adder
4.49
3141766HARMONY
Solar/Wind Harmer
3.206
3141873WAN 176
Solar/Wind Harmer
4.236
3146376EDENTON
Solar/Wind Harmer
-0.035
316203AE2-005 GEN
Solar/Wind Harmer
14.847
3141843SHACKLE
Adder
1.601
3145273HOLLAND
Solar/Wind Harmer
-0.026
961611AG1-000B GEN
Solar/Wind Harmer
7.317
315735AD1-075 GEN1
Solar/Wind Harmer
3.279
316484AD2-074 GEN
Solar/Wind Harmer
8.174
961951AG1-038 GEN
Solar/Wind Harmer
4.277
3142946ENON
Solar/Wind Harmer
-0.011
970657AG2-426 GEN
Solar/Wind Harmer
6.443
315778AD1-151 GEN
Solar/Wind Harmer
28.337
3146206CASHIE
Solar/Wind Harmer
-0.032
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
3156081AA2-088 GEN
Solar/Wind Harmer
10.122
316075AC2-137 C
Solar/Wind Harmer
0.836
944011AF1-069 GEN
Solar/Wind Harmer
18.05
316458AB2-190 GEN2
Solar/Wind Harmer
3.091
3145893MURPHYS
Solar/Wind Harmer
0.214
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
316077AC2-138 C
Solar/Wind Harmer
0.627
3150351NORNECKC2
Adder
2.687
315813AE1-149 C
Solar/Wind Harmer
18.399
3146263WOODLND
Solar/Wind Harmer
-0.029
316317KELFORD C
Solar/Wind Harmer
1.336
3145823KELFORD
Solar/Wind Harmer
-0.029
970133AG2-095 GEN
Solar/Wind Harmer
3.206
970917AG2-570 GEN
Solar/Wind Harmer
70.397
3145933PARMELE
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
316190AA2-174 GEN
Solar/Wind Harmer
0.34
316011AB1-132 GEN
Solar/Wind Harmer
5.71
316181AB2-040 GEN
Solar/Wind Harmer
3.755
316212AC1-099_GEN
Solar/Wind Harmer
2.339
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
966621AG1-532 GEN
Solar/Wind Harmer
0.543
970293AG2-193 GEN
Solar/Wind Harmer
3.205
316420AA1-050 GEN
Solar/Wind Harmer
2.902
315722AD1-056 GEN
Solar/Wind Harmer
9.024
3147043LAWRENC
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.025
3146083TARBORO
Solar/Wind Harmer
-0.025
3146233WITAKRS
Solar/Wind Harmer
0.518
3146233WITAKRS
Solar/Wind Harmer
-0.017
3138543CONSLDL
Solar/Wind Harmer
-0.016
316478AD1-087 GEN
Solar/Wind Harmer
2.108
961601AG1-000A GEN
Solar/Wind Harmer
9.617
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3143096IRON208
Adder
0.896
3143096IRON208
Adder
0.878
316223AC1-118
Solar/Wind Harmer
0.643
3141906WESTMOR
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
16.667
970257AG2-171 GEN
Solar/Wind Harmer
7.669
971775AH1-396 GEN
Solar/Wind Harmer
1.443
959311AF2-222 GEN
Solar/Wind Harmer
21.164
3150861SPRUNCD
Adder
0.818
3144293JTRSVLE
Adder
0.409
3142416OLDCHRC
Solar/Wind Harmer
1.919
3147133PAMPLIN
Solar/Wind Harmer
-0.059
316003AC1-222 GEN
Solar/Wind Harmer
1.831
316222AC1-221 GEN
Solar/Wind Harmer
1.862
316283AC2-100 C
Solar/Wind Harmer
1.729
942461AE2-259 GEN
Solar/Wind Harmer
2.666
971683AH1-343 GEN
Solar/Wind Harmer
7.531
3146926FARMVIL
Solar/Wind Harmer
-0.01
3143336POWHATN
Solar/Wind Harmer
1.532
316123AC1-075 GEN
Solar/Wind Harmer
0.943
961941AG1-037 GEN
Solar/Wind Harmer
0.226
3145513AHOSKIE
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.06
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.03
3141813NORNECK
Solar/Wind Harmer
-0.03
316174AB2-169 GEN
Solar/Wind Harmer
4.552
971967AH1-528 GEN
Solar/Wind Harmer
54.973
3146043SEABORD
Solar/Wind Harmer
-0.029
315814AE2-033 C
Solar/Wind Harmer
26.538
3146033SCOT NK
Solar/Wind Harmer
-0.111
970085AG2-068 GEN
Solar/Wind Harmer
17.35
970581AG2-369 GEN
Solar/Wind Harmer
14.921
316426AA2-053 GEN
Solar/Wind Harmer
2.79
3143316POE
Solar/Wind Harmer
-0.108
315652AC1-086 GEN
Solar/Wind Harmer
30.758
3137643SOCKMAN
Solar/Wind Harmer
-0.108
316210AC1-098 GEN
Solar/Wind Harmer
4.209
3145796HORNRTN
Solar/Wind Harmer
-0.085
3145796HORNRTN
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
946281AF1-292 GEN
Solar/Wind Harmer
0.599
316274AC1-208 GEN
Solar/Wind Harmer
2.835
957861AF2-080 GEN
Solar/Wind Harmer
11.337
316327AA2-057 GEN
Solar/Wind Harmer
2.557
315839AE2-212 C
Solar/Wind Harmer
0.756
3145573BETHELC
Solar/Wind Harmer
-0.025
3145573BETHELC
Solar/Wind Harmer
-0.025
970831AG2-522 GEN
Solar/Wind Harmer
12.404
316486AD2-202 GEN
Solar/Wind Harmer
0.617
316238AB2-078_GEN
Solar/Wind Harmer
0.656
316239AB2-077_GEN
Solar/Wind Harmer
0.656
3144303KENBRDG
Solar/Wind Harmer
-0.016
3147173SINAI
Solar/Wind Harmer
-0.02
3147243WELCO
Solar/Wind Harmer
-0.012
971285AH1-108 GEN
Adder
1.339
970683AG2-441 GEN
Solar/Wind Harmer
14.014
970681AG2-440 GEN
Solar/Wind Harmer
9.302
946301AF1-294 GEN
Solar/Wind Harmer
4.938
961791AG1-021 GEN
Solar/Wind Harmer
2.409
316233AE1-074 FULL
Solar/Wind Harmer
0.514
971281AH1-106 GEN
Solar/Wind Harmer
3.103
971283AH1-107 GEN
Solar/Wind Harmer
3.103
944491AF1-114 GEN
Solar/Wind Harmer
4.943
270455AD2-022 GEN
Solar/Wind Harmer
2.781
270457AD2-023 GEN
Solar/Wind Harmer
1.41
316258AE1-075 C
Solar/Wind Harmer
0.368
316405AF2-144 C
Solar/Wind Harmer
0.388
3145963POPLR C
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.03
3150351NORNECKC2
Adder
2.642
944631AF1-128 GEN
Adder
125.472
3146263WOODLND
Solar/Wind Harmer
-0.029
3145823KELFORD
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.888
970919AG2-571 GEN
Solar/Wind Harmer
8.911
3146293MARTNCO
Solar/Wind Harmer
0.172
970087AG2-069 GEN
Solar/Wind Harmer
26.025
316023GEN1_S
Solar/Wind Harmer
1.858
3145783HORNRTN
Solar/Wind Harmer
-0.027
316337AD2-073 GEN
Solar/Wind Harmer
0.722
316087AB2-174 GEN
Solar/Wind Harmer
3.832
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
960081AF2-299 GEN
Solar/Wind Harmer
3.011
316494AC1-189 GEN
Solar/Wind Harmer
2.788
957481AF2-042 GEN
Solar/Wind Harmer
80.145
315671AE2-027_GEN
Solar/Wind Harmer
4.604
3147043LAWRENC
Adder
2.034
961671AG1-007 GEN
Solar/Wind Harmer
0.318
3146083TARBORO
Solar/Wind Harmer
-0.025
3145493TOT1
Solar/Wind Harmer
0.745
316319Z2-044 C
Solar/Wind Harmer
1.368
3146233WITAKRS
Solar/Wind Harmer
-0.098
316129AC1-054 GEN
Solar/Wind Harmer
2.141
315693AD1-088 GEN
Solar/Wind Harmer
12.184
971065AG2-659 GEN
Solar/Wind Harmer
12.124
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.246
3142053HEARTS
Solar/Wind Harmer
0.284
3143096IRON208
Adder
0.896
316131AB2-060 GEN
Solar/Wind Harmer
2.337
3142543TWELFTH
Solar/Wind Harmer
-0.002
970401AG2-262 GEN
Solar/Wind Harmer
1.354
315785AD2-033 C
Solar/Wind Harmer
4.681
316034AC1-036 C
Solar/Wind Harmer
0.378
3150851SPRUNCC
Adder
0.818
970685AG2-442 GEN
Solar/Wind Harmer
17.132
972135AH1-637 GEN
Solar/Wind Harmer
1.935
3143226MDLTHAN
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.409
3144293JTRSVLE
Adder
0.409
3144293JTRSVLE
Adder
0.323
3143526WINTERP
Solar/Wind Harmer
-0.099
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
957971AF2-091 GEN
Solar/Wind Harmer
1.681
3146926FARMVIL
Solar/Wind Harmer
-0.01
3143336POWHATN
Solar/Wind Harmer
1.802
315976AC1-164 GENA
Solar/Wind Harmer
8.669
316169AC1-164_GENC
Solar/Wind Harmer
7.49
3146386ELIZ CT
Solar/Wind Harmer
-0.038
316431W1029_GEN1
Solar/Wind Harmer
6.738
316433W1029_GEN2
Solar/Wind Harmer
6.738
316435W1029_GEN3
Solar/Wind Harmer
6.738
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
315835AF2-110_GEN
Solar/Wind Harmer
4.617
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
316156AD2-030 GEN
Solar/Wind Harmer
0.951
315666AE1-190 GEN
Solar/Wind Harmer
1.065
3146376EDENTON
Solar/Wind Harmer
1.046
3146376EDENTON
Solar/Wind Harmer
1.046
316441AF1-014 GEN
Solar/Wind Harmer
2.374
316349AD2-085 GEN
Solar/Wind Harmer
3.094
315742AE1-103 GEN
Solar/Wind Harmer
8.15
315614AA2-178 GEN
Solar/Wind Harmer
3.638
316033AB2-134 GEN
Solar/Wind Harmer
10.518
316487AF1-042 GEN
Solar/Wind Harmer
4.277
3142946ENON
Solar/Wind Harmer
-0.003
316065AD1-022 GEN
Solar/Wind Harmer
16.011
316083AB2-161 GEN
Solar/Wind Harmer
5.115
3145893MURPHYS
Solar/Wind Harmer
0.854
3145893MURPHYS
Solar/Wind Harmer
-0.055
3146173TUNIS
Solar/Wind Harmer
-0.03
3146173TUNIS
Solar/Wind Harmer
-0.03
316140AB2-099
Solar/Wind Harmer
0.203
3150341NORNECKC1
Adder
2.775
3150341NORNECKC1
Adder
2.753
972185AH1-677 GEN
Adder
14.861
972187AH1-678 GEN
Adder
7.433
3144356SAPONY
Solar/Wind Harmer
0.996
316315AB2-025 C
Solar/Wind Harmer
0.768
970933AG2-581 GEN
Solar/Wind Harmer
26.595
3145933PARMELE
Solar/Wind Harmer
-0.055
3145933PARMELE
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
316365GEN2_N
Solar/Wind Harmer
1.858
962571AG1-106 GEN
Solar/Wind Harmer
3.93
3145593CAROLNA
Solar/Wind Harmer
-0.027
3145593CAROLNA
Solar/Wind Harmer
-0.027
3145593CAROLNA
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
3.212
3145783HORNRTN
Solar/Wind Harmer
2.57
3145783HORNRTN
Solar/Wind Harmer
0.803
3145783HORNRTN
Solar/Wind Harmer
0.321
313506AB2-031 GEN
Solar/Wind Harmer
2.162
3145796HORNRTN
Solar/Wind Harmer
-0.08
316005AA1-067
Solar/Wind Harmer
0.541
970099AG2-077 GEN
Solar/Wind Harmer
32.058
315724AD1-057 GEN
Solar/Wind Harmer
4.963
3145493TOT1
Solar/Wind Harmer
0.389
3145453TOT5
Solar/Wind Harmer
0.233
3145603CNETO
Solar/Wind Harmer
0.155
961601AG1-000A GEN
Solar/Wind Harmer
9.497
316049AB1-081 GEN
Solar/Wind Harmer
2.597
316263AC1-034 GEN
Solar/Wind Harmer
11.315
316240AF1-291 C
Solar/Wind Harmer
0.721
944641AF1-129 GEN
Adder
99.841
315687AD1-152 GEN
Solar/Wind Harmer
2.745
316237AB2-079_GEN
Solar/Wind Harmer
0.656
313527AB2-043 GEN
Solar/Wind Harmer
3.542
962561AG1-105 GEN
Solar/Wind Harmer
11.759
964791AG1-342 GEN
Solar/Wind Harmer
4.431
3146843MT LREL
Solar/Wind Harmer
-0.021
3146843MT LREL
Solar/Wind Harmer
-0.021
3150691DARBY 3
Adder
13.223
3150701DARBY 4
Adder
13.192
3150681DARBY 2
Adder
13.177
3150671DARBY 1
Adder
13.162
970323AG2-213 GEN
Solar/Wind Harmer
10.225
316118AC1-105 GEN
Solar/Wind Harmer
1.396
316248AF1-058 C
Solar/Wind Harmer
0.6
970301AG2-198 GEN
Solar/Wind Harmer
9.911
971223AH1-071 GEN
Solar/Wind Harmer
2.416
958211AF2-115 GEN
Solar/Wind Harmer
3.011
3144293JTRSVLE
Adder
0.409
3143526WINTERP
Solar/Wind Harmer
-0.099
316312AB1-027
Solar/Wind Harmer
0.64
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3147133PAMPLIN
Solar/Wind Harmer
-0.015
3142366NRTHEST
Adder
0.518
316313AB2-026
Solar/Wind Harmer
0.408
CPLELTFEXP_CPLE->PJM
CLTF
12.716
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.375
LAGNLTFEXP_LAGN->PJM
CLTF
7.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.233
TVALTFEXP_TVA->PJM
CLTF
3.594
NYPJM->LTFIMP_NY
CLTF
2.179
LGEELTFEXP_LGEE->PJM
CLTF
0.932
WECLTFEXP_WEC->PJM
CLTF
0.467
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.386
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.981
MECLTFEXP_MEC->PJM
CLTF
2.842
SIGELTFEXP_SIGE->PJM
CLTF
0.082

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.07 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:4003.16
MW Contribution:
238.12
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150921YORKTN3
50/50
9.827
3144216WINCHST
50/50
1.452
3151101ELIZAR3
50/50
34.635
3151161SURRY 1
50/50
13.075
944581AF1-123 GEN
Solar/Wind Harmer
182.354
944601AF1-125 GEN
Solar/Wind Harmer
179.508
3142956BIRDNECK
Solar/Wind Harmer
2.115
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
3.145
3144536CHRHLND
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.039
971153AH1-033 GEN
Solar/Wind Harmer
4.493
316305AF2-043 C
Solar/Wind Harmer
1.151
316246AF1-032 C
Solar/Wind Harmer
0.772
972263AH1-716 GEN
50/50
238.124
3151081ELIZAR1
50/50
34.197
3151091ELIZAR2
50/50
33.603
941591AE2-156 GEN
50/50
31.211
3151201GRAVEL4
50/50
24.792
316382AG1-145 C
Solar/Wind Harmer
1.231
316159AE1-175 C
Solar/Wind Harmer
1.096
316316AC1-027 C
Solar/Wind Harmer
1.207
316018AA1-139 ULT2
Solar/Wind Harmer
3.33
957871AF2-081 GEN
Solar/Wind Harmer
19.488
3146406KITTY HAWK
Solar/Wind Harmer
0.032
957831AF2-077 GEN
Solar/Wind Harmer
1.163
3138283WHITEMARSH
Solar/Wind Harmer
0.06
313526AB2-022
Solar/Wind Harmer
1.023
3146396TANGLEW
Solar/Wind Harmer
0.693
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
3146486SUNBURY
Solar/Wind Harmer
-0.038
3146486SUNBURY
Solar/Wind Harmer
-0.038
316236AE1-162_GEN
Solar/Wind Harmer
1.124
971445AH1-216 GEN
Solar/Wind Harmer
23.05
3151221GRAVEL6
Adder
23.337
3151191GRAVEL3
Adder
23.068
3151211GRAVEL5
Adder
23.068
316059AD1-063 C
Solar/Wind Harmer
0.812
957601AF2-054 GEN
Solar/Wind Harmer
1.068
3141873WAN 176
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
8.787
3130156CHOWAN
Solar/Wind Harmer
-0.035
3130156CHOWAN
Solar/Wind Harmer
-0.035
316311AC2-079 GEN
Solar/Wind Harmer
17.6
315833AF1-017_GEN
Solar/Wind Harmer
6.618
3141913WHIT STONE
Solar/Wind Harmer
-0.035
3138133OCRAN
Solar/Wind Harmer
-0.01
3143873LANEXA
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.013
3130546PLYMOUTH
Solar/Wind Harmer
-0.033
315697AD1-025 GEN
Solar/Wind Harmer
6.592
315732AD1-074 GEN1
Solar/Wind Harmer
6.561
315733AD1-074 GEN2
Solar/Wind Harmer
6.561
970657AG2-426 GEN
Solar/Wind Harmer
2.011
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
13.887
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
970533AG2-339 GEN
Solar/Wind Harmer
20.66
316318V4-068
Solar/Wind Harmer
0.763
3145893MURPHYS
Solar/Wind Harmer
-0.082
3145893MURPHYS
Solar/Wind Harmer
-0.031
970673AG2-436 GEN
Solar/Wind Harmer
66.367
316463AE2-346 GEN
Solar/Wind Harmer
0.486
3145513AHOSKIE
Solar/Wind Harmer
0.263
961941AG1-037 GEN
Solar/Wind Harmer
0.226
3145513AHOSKIE
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.06
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.03
3141813NORNECK
Solar/Wind Harmer
-0.03
316174AB2-169 GEN
Solar/Wind Harmer
4.552
971967AH1-528 GEN
Solar/Wind Harmer
54.973
3146043SEABORD
Solar/Wind Harmer
-0.029
315814AE2-033 C
Solar/Wind Harmer
26.538
3146033SCOT NK
Solar/Wind Harmer
-0.111
970085AG2-068 GEN
Solar/Wind Harmer
17.35
970581AG2-369 GEN
Solar/Wind Harmer
14.921
316426AA2-053 GEN
Solar/Wind Harmer
2.79
3143316POE
Solar/Wind Harmer
-0.108
315652AC1-086 GEN
Solar/Wind Harmer
30.758
3137643SOCKMAN
Solar/Wind Harmer
-0.108
316210AC1-098 GEN
Solar/Wind Harmer
4.209
3145796HORNRTN
Solar/Wind Harmer
-0.085
3145796HORNRTN
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
946281AF1-292 GEN
Solar/Wind Harmer
0.599
316274AC1-208 GEN
Solar/Wind Harmer
2.835
957861AF2-080 GEN
Solar/Wind Harmer
11.337
316327AA2-057 GEN
Solar/Wind Harmer
2.557
315839AE2-212 C
Solar/Wind Harmer
0.756
3145573BETHELC
Solar/Wind Harmer
-0.025
3145573BETHELC
Solar/Wind Harmer
-0.025
970831AG2-522 GEN
Solar/Wind Harmer
12.404
316486AD2-202 GEN
Solar/Wind Harmer
0.617
316238AB2-078_GEN
Solar/Wind Harmer
0.656
316239AB2-077_GEN
Solar/Wind Harmer
0.656
3144303KENBRDG
Solar/Wind Harmer
-0.016
3147173SINAI
Solar/Wind Harmer
-0.02
3147243WELCO
Solar/Wind Harmer
-0.012
971285AH1-108 GEN
Adder
1.339
970683AG2-441 GEN
Solar/Wind Harmer
14.014
970681AG2-440 GEN
Solar/Wind Harmer
9.302
946301AF1-294 GEN
Solar/Wind Harmer
4.938
961791AG1-021 GEN
Solar/Wind Harmer
2.409
316233AE1-074 FULL
Solar/Wind Harmer
0.514
971281AH1-106 GEN
Solar/Wind Harmer
3.103
971283AH1-107 GEN
Solar/Wind Harmer
3.103
944491AF1-114 GEN
Solar/Wind Harmer
4.943
270455AD2-022 GEN
Solar/Wind Harmer
2.781
270457AD2-023 GEN
Solar/Wind Harmer
1.41
316258AE1-075 C
Solar/Wind Harmer
0.368
316405AF2-144 C
Solar/Wind Harmer
0.388
3152331SURRY 2
50/50
17.121
3150981CHESPKA
50/50
4.645
315773AC2-141 GEN
Solar/Wind Harmer
17.914
971317AH1-138 GEN
Solar/Wind Harmer
5.168
3138126ROCKLANDING
Solar/Wind Harmer
0.126
944591AF1-124 GEN
Solar/Wind Harmer
183.011
316375AC2-012 GEN
Solar/Wind Harmer
13.623
316036AC1-147 C
Solar/Wind Harmer
1.06
3146456SLIGO L269
Solar/Wind Harmer
-0.039
319010AE1-072 C
Solar/Wind Harmer
7.824
316072AD1-144
Solar/Wind Harmer
0.771
315975AC1-164 GENB
Solar/Wind Harmer
0.256
3145336SMITFLD
Solar/Wind Harmer
-0.149
3146516WINFALL
Solar/Wind Harmer
-0.119
3146516WINFALL
Solar/Wind Harmer
-0.037
316093AE2-104_GEN
Solar/Wind Harmer
10.739
316314AB2-024 C
Solar/Wind Harmer
3.094
3151171GRAVELC
Adder
3.414
3141766HARMONY
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
8.787
315662AE1-191 GEN
Solar/Wind Harmer
4.259
316280AD1-041 GEN
Solar/Wind Harmer
2.662
939411AE1-173 GEN
Solar/Wind Harmer
177.059
3130156CHOWAN
Solar/Wind Harmer
-0.035
971777AH1-397 GEN
Solar/Wind Harmer
4.109
961611AG1-000B GEN
Solar/Wind Harmer
17.148
3138133OCRAN
Solar/Wind Harmer
-0.021
940641AE2-051 GEN
Solar/Wind Harmer
31.894
315816AE2-034 GEN
Solar/Wind Harmer
2.729
3145663CRESWEL
Solar/Wind Harmer
-0.094
971163AH1-040 GEN
Solar/Wind Harmer
31.702
316369SG1_INVT
Solar/Wind Harmer
5.825
315737AD1-076 GEN
Solar/Wind Harmer
6.168
971069AG2-661 GEN
Solar/Wind Harmer
5.038
962861AG1-135 GEN
Solar/Wind Harmer
11.91
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
7.936
3142433PROV 92
Solar/Wind Harmer
-0.126
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
316381AD1-082 GEN
Solar/Wind Harmer
2.884
316404AE1-155 C
Solar/Wind Harmer
6.014
958261AF2-120 GEN
Solar/Wind Harmer
12.208
941031AE2-094 GEN
Solar/Wind Harmer
57.605
3156021HOLLOMANSOL
Solar/Wind Harmer
4.118
316132AB2-190 GEN1
Solar/Wind Harmer
3.091
3145893MURPHYS
Solar/Wind Harmer
-0.122
3145893MURPHYS
Solar/Wind Harmer
0.908
964211AG1-282 GEN
Solar/Wind Harmer
0.92
3141726DUNNSVL
Solar/Wind Harmer
-0.122
3146173TUNIS
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.03
3150351NORNECKC2
Adder
2.642
944631AF1-128 GEN
Adder
125.472
3146263WOODLND
Solar/Wind Harmer
-0.029
3145823KELFORD
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.888
970919AG2-571 GEN
Solar/Wind Harmer
8.911
3146293MARTNCO
Solar/Wind Harmer
0.172
970087AG2-069 GEN
Solar/Wind Harmer
26.025
316023GEN1_S
Solar/Wind Harmer
1.858
3145783HORNRTN
Solar/Wind Harmer
-0.027
316337AD2-073 GEN
Solar/Wind Harmer
0.722
316087AB2-174 GEN
Solar/Wind Harmer
3.832
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
960081AF2-299 GEN
Solar/Wind Harmer
3.011
316494AC1-189 GEN
Solar/Wind Harmer
2.788
957481AF2-042 GEN
Solar/Wind Harmer
80.145
315671AE2-027_GEN
Solar/Wind Harmer
4.604
3147043LAWRENC
Adder
2.034
961671AG1-007 GEN
Solar/Wind Harmer
0.318
3146083TARBORO
Solar/Wind Harmer
-0.025
3145493TOT1
Solar/Wind Harmer
0.745
316319Z2-044 C
Solar/Wind Harmer
1.368
3146233WITAKRS
Solar/Wind Harmer
-0.098
316129AC1-054 GEN
Solar/Wind Harmer
2.141
315693AD1-088 GEN
Solar/Wind Harmer
12.184
971065AG2-659 GEN
Solar/Wind Harmer
12.124
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.246
3142053HEARTS
Solar/Wind Harmer
0.284
3143096IRON208
Adder
0.896
316131AB2-060 GEN
Solar/Wind Harmer
2.337
3142543TWELFTH
Solar/Wind Harmer
-0.002
970401AG2-262 GEN
Solar/Wind Harmer
1.354
315785AD2-033 C
Solar/Wind Harmer
4.681
316034AC1-036 C
Solar/Wind Harmer
0.378
3150851SPRUNCC
Adder
0.818
970685AG2-442 GEN
Solar/Wind Harmer
17.132
972135AH1-637 GEN
Solar/Wind Harmer
1.935
3143226MDLTHAN
Solar/Wind Harmer
-0.019
971563AH1-280 GEN
Solar/Wind Harmer
2.409
3144293JTRSVLE
Adder
0.409
3144293JTRSVLE
Adder
0.323
3143526WINTERP
Solar/Wind Harmer
-0.099
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
957971AF2-091 GEN
Solar/Wind Harmer
1.681
3146926FARMVIL
Solar/Wind Harmer
-0.01
3143336POWHATN
Solar/Wind Harmer
1.802
3150991CHESPKB
50/50
3.897
3150991CHESPKB
50/50
3.803
316294AC1-161 GEN
Solar/Wind Harmer
13.845
316185AD1-033 GEN
Solar/Wind Harmer
4.154
3145506HICKORY
Solar/Wind Harmer
-0.157
3145506HICKORY
Solar/Wind Harmer
-0.094
3145506HICKORY
Solar/Wind Harmer
-0.023
316339AD2-160 GEN
Solar/Wind Harmer
2.626
316388AE2-253 GEN
Solar/Wind Harmer
2.626
3137176SLIGO L2192
Solar/Wind Harmer
-0.154
3146456SLIGO L269
Solar/Wind Harmer
4.585
3130086AYDLETT
Solar/Wind Harmer
-0.154
315976AC1-164 GENA
Solar/Wind Harmer
8.669
316169AC1-164_GENC
Solar/Wind Harmer
7.49
3146386ELIZ CT
Solar/Wind Harmer
-0.038
316431W1029_GEN1
Solar/Wind Harmer
6.738
316433W1029_GEN2
Solar/Wind Harmer
6.738
316435W1029_GEN3
Solar/Wind Harmer
6.738
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
315835AF2-110_GEN
Solar/Wind Harmer
4.617
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
316156AD2-030 GEN
Solar/Wind Harmer
0.951
315666AE1-190 GEN
Solar/Wind Harmer
1.065
3146376EDENTON
Solar/Wind Harmer
1.046
3146376EDENTON
Solar/Wind Harmer
1.046
316441AF1-014 GEN
Solar/Wind Harmer
2.374
316349AD2-085 GEN
Solar/Wind Harmer
3.094
315742AE1-103 GEN
Solar/Wind Harmer
8.15
315614AA2-178 GEN
Solar/Wind Harmer
3.638
316033AB2-134 GEN
Solar/Wind Harmer
10.518
316487AF1-042 GEN
Solar/Wind Harmer
4.277
3142946ENON
Solar/Wind Harmer
-0.003
316065AD1-022 GEN
Solar/Wind Harmer
16.011
316083AB2-161 GEN
Solar/Wind Harmer
5.115
3145893MURPHYS
Solar/Wind Harmer
0.854
3145893MURPHYS
Solar/Wind Harmer
-0.055
3146173TUNIS
Solar/Wind Harmer
-0.03
3146173TUNIS
Solar/Wind Harmer
-0.03
316140AB2-099
Solar/Wind Harmer
0.203
3150341NORNECKC1
Adder
2.775
3150341NORNECKC1
Adder
2.753
972185AH1-677 GEN
Adder
14.861
972187AH1-678 GEN
Adder
7.433
3144356SAPONY
Solar/Wind Harmer
0.996
316315AB2-025 C
Solar/Wind Harmer
0.768
970933AG2-581 GEN
Solar/Wind Harmer
26.595
3145933PARMELE
Solar/Wind Harmer
-0.055
3145933PARMELE
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
316365GEN2_N
Solar/Wind Harmer
1.858
962571AG1-106 GEN
Solar/Wind Harmer
3.93
3145593CAROLNA
Solar/Wind Harmer
-0.027
3145593CAROLNA
Solar/Wind Harmer
-0.027
3145593CAROLNA
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
3.212
3145783HORNRTN
Solar/Wind Harmer
2.57
3145783HORNRTN
Solar/Wind Harmer
0.803
3145783HORNRTN
Solar/Wind Harmer
0.321
313506AB2-031 GEN
Solar/Wind Harmer
2.162
3145796HORNRTN
Solar/Wind Harmer
-0.08
316005AA1-067
Solar/Wind Harmer
0.541
970099AG2-077 GEN
Solar/Wind Harmer
32.058
315724AD1-057 GEN
Solar/Wind Harmer
4.963
3145493TOT1
Solar/Wind Harmer
0.389
3145453TOT5
Solar/Wind Harmer
0.233
3145603CNETO
Solar/Wind Harmer
0.155
961601AG1-000A GEN
Solar/Wind Harmer
9.497
316049AB1-081 GEN
Solar/Wind Harmer
2.597
316263AC1-034 GEN
Solar/Wind Harmer
11.315
316240AF1-291 C
Solar/Wind Harmer
0.721
944641AF1-129 GEN
Adder
99.841
315687AD1-152 GEN
Solar/Wind Harmer
2.745
316237AB2-079_GEN
Solar/Wind Harmer
0.656
313527AB2-043 GEN
Solar/Wind Harmer
3.542
962561AG1-105 GEN
Solar/Wind Harmer
11.759
964791AG1-342 GEN
Solar/Wind Harmer
4.431
3146843MT LREL
Solar/Wind Harmer
-0.021
3146843MT LREL
Solar/Wind Harmer
-0.021
3150691DARBY 3
Adder
13.223
3150701DARBY 4
Adder
13.192
3150681DARBY 2
Adder
13.177
3150671DARBY 1
Adder
13.162
970323AG2-213 GEN
Solar/Wind Harmer
10.225
316118AC1-105 GEN
Solar/Wind Harmer
1.396
316248AF1-058 C
Solar/Wind Harmer
0.6
970301AG2-198 GEN
Solar/Wind Harmer
9.911
971223AH1-071 GEN
Solar/Wind Harmer
2.416
958211AF2-115 GEN
Solar/Wind Harmer
3.011
3144293JTRSVLE
Adder
0.409
3143526WINTERP
Solar/Wind Harmer
-0.099
316312AB1-027
Solar/Wind Harmer
0.64
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3147133PAMPLIN
Solar/Wind Harmer
-0.015
3142366NRTHEST
Adder
0.518
316313AB2-026
Solar/Wind Harmer
0.408
316320Y1-086
Solar/Wind Harmer
2.227
316321Z2-027
Solar/Wind Harmer
1.014
3145336SMITFLD
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3151171GRAVELC
Adder
4.49
3141766HARMONY
Solar/Wind Harmer
3.206
3141873WAN 176
Solar/Wind Harmer
4.236
3146376EDENTON
Solar/Wind Harmer
-0.035
316203AE2-005 GEN
Solar/Wind Harmer
14.847
3141843SHACKLE
Adder
1.601
3145273HOLLAND
Solar/Wind Harmer
-0.026
961611AG1-000B GEN
Solar/Wind Harmer
7.317
315735AD1-075 GEN1
Solar/Wind Harmer
3.279
316484AD2-074 GEN
Solar/Wind Harmer
8.174
961951AG1-038 GEN
Solar/Wind Harmer
4.277
3142946ENON
Solar/Wind Harmer
-0.011
970657AG2-426 GEN
Solar/Wind Harmer
6.443
315778AD1-151 GEN
Solar/Wind Harmer
28.337
3146206CASHIE
Solar/Wind Harmer
-0.032
3142433PROV 92
Adder
0.548
3142433PROV 92
Adder
0.548
3156081AA2-088 GEN
Solar/Wind Harmer
10.122
316075AC2-137 C
Solar/Wind Harmer
0.836
944011AF1-069 GEN
Solar/Wind Harmer
18.05
316458AB2-190 GEN2
Solar/Wind Harmer
3.091
3145893MURPHYS
Solar/Wind Harmer
0.214
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
316077AC2-138 C
Solar/Wind Harmer
0.627
3150351NORNECKC2
Adder
2.687
315813AE1-149 C
Solar/Wind Harmer
18.399
3146263WOODLND
Solar/Wind Harmer
-0.029
316317KELFORD C
Solar/Wind Harmer
1.336
3145823KELFORD
Solar/Wind Harmer
-0.029
970133AG2-095 GEN
Solar/Wind Harmer
3.206
970917AG2-570 GEN
Solar/Wind Harmer
70.397
3145933PARMELE
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
316190AA2-174 GEN
Solar/Wind Harmer
0.34
316011AB1-132 GEN
Solar/Wind Harmer
5.71
316181AB2-040 GEN
Solar/Wind Harmer
3.755
316212AC1-099_GEN
Solar/Wind Harmer
2.339
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
966621AG1-532 GEN
Solar/Wind Harmer
0.543
970293AG2-193 GEN
Solar/Wind Harmer
3.205
316420AA1-050 GEN
Solar/Wind Harmer
2.902
315722AD1-056 GEN
Solar/Wind Harmer
9.024
3147043LAWRENC
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.025
3146083TARBORO
Solar/Wind Harmer
-0.025
3146233WITAKRS
Solar/Wind Harmer
0.518
3146233WITAKRS
Solar/Wind Harmer
-0.017
3138543CONSLDL
Solar/Wind Harmer
-0.016
316478AD1-087 GEN
Solar/Wind Harmer
2.108
961601AG1-000A GEN
Solar/Wind Harmer
9.617
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3143096IRON208
Adder
0.896
3143096IRON208
Adder
0.878
316223AC1-118
Solar/Wind Harmer
0.643
3141906WESTMOR
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
16.667
970257AG2-171 GEN
Solar/Wind Harmer
7.669
971775AH1-396 GEN
Solar/Wind Harmer
1.443
959311AF2-222 GEN
Solar/Wind Harmer
21.164
3150861SPRUNCD
Adder
0.818
3144293JTRSVLE
Adder
0.409
3142416OLDCHRC
Solar/Wind Harmer
1.919
3147133PAMPLIN
Solar/Wind Harmer
-0.059
316003AC1-222 GEN
Solar/Wind Harmer
1.831
316222AC1-221 GEN
Solar/Wind Harmer
1.862
316283AC2-100 C
Solar/Wind Harmer
1.729
942461AE2-259 GEN
Solar/Wind Harmer
2.666
971683AH1-343 GEN
Solar/Wind Harmer
7.531
3146926FARMVIL
Solar/Wind Harmer
-0.01
3143336POWHATN
Solar/Wind Harmer
1.532
316123AC1-075 GEN
Solar/Wind Harmer
0.943
CPLELTFEXP_CPLE->PJM
CLTF
12.716
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.375
LAGNLTFEXP_LAGN->PJM
CLTF
7.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.233
TVALTFEXP_TVA->PJM
CLTF
3.594
NYPJM->LTFIMP_NY
CLTF
2.179
LGEELTFEXP_LGEE->PJM
CLTF
0.932
WECLTFEXP_WEC->PJM
CLTF
0.467
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.386
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.981
MECLTFEXP_MEC->PJM
CLTF
2.842
SIGELTFEXP_SIGE->PJM
CLTF
0.082

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P2-2: ELMONT B1_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ELMONT B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:179.17 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:5120.71
MW Contribution:
153.59
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
153.586
316382AG1-145 C
Solar/Wind Harmer
0.911
316159AE1-175 C
Solar/Wind Harmer
0.811
3143873LANEXA
Solar/Wind Harmer
-0.017
957831AF2-077 GEN
Solar/Wind Harmer
0.849
3138283WHITEMARSH
Solar/Wind Harmer
0.044
316059AD1-063 C
Solar/Wind Harmer
0.636
3142433PROV 92
Adder
0.484
3142433PROV 92
Adder
0.484
957601AF2-054 GEN
Solar/Wind Harmer
0.821
3141873WAN 176
Solar/Wind Harmer
-0.005
315697AD1-025 GEN
Solar/Wind Harmer
5.428
3151201GRAVEL4
Adder
17.406
3151221GRAVEL6
Adder
17.386
3151191GRAVEL3
Adder
17.186
3151211GRAVEL5
Adder
17.186
3141913WHIT STONE
Solar/Wind Harmer
-0.027
971445AH1-216 GEN
Solar/Wind Harmer
16.461
316236AE1-162_GEN
Solar/Wind Harmer
0.799
3138133OCRAN
Solar/Wind Harmer
-0.008
3151081ELIZAR1
Adder
21.28
3151091ELIZAR2
Adder
20.91
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
316316AC1-027 C
Solar/Wind Harmer
0.796
316018AA1-139 ULT2
Solar/Wind Harmer
2.192
957871AF2-081 GEN
Solar/Wind Harmer
12.83
3146406KITTY HAWK
Solar/Wind Harmer
0.021
313526AB2-022
Solar/Wind Harmer
0.678
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146396TANGLEW
Solar/Wind Harmer
0.46
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
316311AC2-079 GEN
Solar/Wind Harmer
12.548
315833AF1-017_GEN
Solar/Wind Harmer
4.723
970657AG2-426 GEN
Solar/Wind Harmer
1.551
315839AE2-212 C
Solar/Wind Harmer
0.734
971285AH1-108 GEN
Adder
1.635
315800Z1-036_GEN1
Solar/Wind Harmer
5.905
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
3143316POE
Solar/Wind Harmer
-0.091
3130546PLYMOUTH
Solar/Wind Harmer
-0.022
315732AD1-074 GEN1
Solar/Wind Harmer
4.492
315733AD1-074 GEN2
Solar/Wind Harmer
4.492
3141813NORNECK
Solar/Wind Harmer
-0.022
3146206CASHIE
Solar/Wind Harmer
-0.022
970601AG2-382 GEN
Solar/Wind Harmer
9.563
316318V4-068
Solar/Wind Harmer
0.533
3145893MURPHYS
Solar/Wind Harmer
-0.057
3145893MURPHYS
Solar/Wind Harmer
-0.021
316463AE2-346 GEN
Solar/Wind Harmer
0.34
3145513AHOSKIE
Solar/Wind Harmer
0.183
961941AG1-037 GEN
Solar/Wind Harmer
0.158
3145513AHOSKIE
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.042
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.021
972277AH1-723 GEN
50/50
204.678
3152331SURRY 2
50/50
10.909
315975AC1-164 GENB
Solar/Wind Harmer
0.216
3142416OLDCHRC
Solar/Wind Harmer
-0.08
3142416OLDCHRC
Solar/Wind Harmer
-0.031
971317AH1-138 GEN
Solar/Wind Harmer
3.665
3138126ROCKLANDING
Solar/Wind Harmer
0.088
944631AF1-128 GEN
Adder
122.106
316314AB2-024 C
Solar/Wind Harmer
2.448
3141766HARMONY
Solar/Wind Harmer
-0.006
3142433PROV 92
Solar/Wind Harmer
-0.111
3142433PROV 92
Adder
0.484
3142433PROV 92
Adder
0.484
971777AH1-397 GEN
Solar/Wind Harmer
3.249
315662AE1-191 GEN
Solar/Wind Harmer
3.328
316280AD1-041 GEN
Solar/Wind Harmer
2.08
3143096IRON208
Adder
1.031
315773AC2-141 GEN
Solar/Wind Harmer
11.32
316132AB2-190 GEN1
Solar/Wind Harmer
2.715
971069AG2-661 GEN
Solar/Wind Harmer
4.257
316369SG1_INVT
Solar/Wind Harmer
4.797
961611AG1-000B GEN
Solar/Wind Harmer
13.265
3151171GRAVELC
Adder
2.544
3145336SMITFLD
Solar/Wind Harmer
-0.106
3138133OCRAN
Solar/Wind Harmer
-0.016
3142543TWELFTH
Solar/Wind Harmer
-0.002
316375AC2-012 GEN
Solar/Wind Harmer
9.018
316036AC1-147 C
Solar/Wind Harmer
0.702
3150981CHESPKA
Adder
2.898
944591AF1-124 GEN
Solar/Wind Harmer
118.899
316072AD1-144
Solar/Wind Harmer
0.524
3146456SLIGO L269
Solar/Wind Harmer
-0.026
319010AE1-072 C
Solar/Wind Harmer
5.158
315671AE2-027_GEN
Solar/Wind Harmer
4.536
316093AE2-104_GEN
Solar/Wind Harmer
7.287
3146516WINFALL
Solar/Wind Harmer
-0.08
3146516WINFALL
Solar/Wind Harmer
-0.025
316381AD1-082 GEN
Solar/Wind Harmer
2.248
3150851SPRUNCC
Adder
0.999
962861AG1-135 GEN
Solar/Wind Harmer
8.977
315611Z1-036_GEN2
Solar/Wind Harmer
5.905
3130156CHOWAN
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.526
958261AF2-120 GEN
Solar/Wind Harmer
9.188
964211AG1-282 GEN
Solar/Wind Harmer
0.694
3141726DUNNSVL
Solar/Wind Harmer
-0.092
315816AE2-034 GEN
Solar/Wind Harmer
1.853
3145663CRESWEL
Solar/Wind Harmer
-0.064
971163AH1-040 GEN
Solar/Wind Harmer
21.526
315737AD1-076 GEN
Solar/Wind Harmer
4.223
3150351NORNECKC2
Adder
1.967
3146206CASHIE
Solar/Wind Harmer
-0.022
971547AH1-271 GEN
Solar/Wind Harmer
5.465
939411AE1-173 GEN
Solar/Wind Harmer
108.312
3152181CUNINGC
50/50
2.666
3152171CUNINGB
50/50
2.509
3152161CUNINGA
50/50
2.495
972193AH1-681 GEN
50/50
7.848
3142296MT RD221
50/50
0.892
3150691DARBY 3
50/50
19.758
3150701DARBY 4
50/50
19.712
3150681DARBY 2
50/50
19.689
315976AC1-164 GENA
Solar/Wind Harmer
7.312
316169AC1-164_GENC
Solar/Wind Harmer
6.317
316312AB1-027
Solar/Wind Harmer
1.039
3142946ENON
Solar/Wind Harmer
-0.003
3150671DARBY 1
Adder
18.533
3142366NRTHEST
Adder
0.828
316441AF1-014 GEN
Solar/Wind Harmer
1.876
315666AE1-190 GEN
Solar/Wind Harmer
0.832
316156AD2-030 GEN
Solar/Wind Harmer
0.731
966871AG1-558 GEN
Solar/Wind Harmer
0.821
966871AG1-558 GEN
Solar/Wind Harmer
0.281
316294AC1-161 GEN
Solar/Wind Harmer
8.749
316033AB2-134 GEN
Solar/Wind Harmer
8.661
3150991CHESPKB
Adder
2.431
3150991CHESPKB
Adder
2.373
316185AD1-033 GEN
Solar/Wind Harmer
2.728
3145893MURPHYS
Solar/Wind Harmer
-0.085
3145893MURPHYS
Solar/Wind Harmer
0.634
3156021HOLLOMANSOL
Solar/Wind Harmer
2.86
3146173TUNIS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145963POPLR C
Solar/Wind Harmer
-0.021
3143526WINTERP
Solar/Wind Harmer
-0.107
3146263WOODLND
Solar/Wind Harmer
-0.02
3145823KELFORD
Solar/Wind Harmer
-0.02
315607AA1-063A GEN
Solar/Wind Harmer
2.045
940641AE2-051 GEN
Solar/Wind Harmer
18.978
316023GEN1_S
Solar/Wind Harmer
1.341
3146293MARTNCO
Solar/Wind Harmer
0.122
315814AE2-033 C
Solar/Wind Harmer
19.297
316174AB2-169 GEN
Solar/Wind Harmer
3.176
316233AE1-074 FULL
Solar/Wind Harmer
0.555
971281AH1-106 GEN
Solar/Wind Harmer
3.35
971283AH1-107 GEN
Solar/Wind Harmer
3.35
3146043SEABORD
Solar/Wind Harmer
-0.02
316426AA2-053 GEN
Solar/Wind Harmer
1.988
3146033SCOT NK
Solar/Wind Harmer
-0.078
315652AC1-086 GEN
Solar/Wind Harmer
22.066
3137643SOCKMAN
Solar/Wind Harmer
-0.077
946281AF1-292 GEN
Solar/Wind Harmer
0.435
3145796HORNRTN
Solar/Wind Harmer
-0.061
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.728
316388AE2-253 GEN
Solar/Wind Harmer
1.728
944641AF1-129 GEN
Adder
108.637
3137176SLIGO L2192
Solar/Wind Harmer
-0.101
3146456SLIGO L269
Solar/Wind Harmer
3.021
3130086AYDLETT
Solar/Wind Harmer
-0.102
316240AF1-291 C
Solar/Wind Harmer
0.761
3146386ELIZ CT
Solar/Wind Harmer
-0.025
315835AF2-110_GEN
Solar/Wind Harmer
3.133
316349AD2-085 GEN
Solar/Wind Harmer
2.208
316431W1029_GEN1
Solar/Wind Harmer
4.49
316433W1029_GEN2
Solar/Wind Harmer
4.49
316435W1029_GEN3
Solar/Wind Harmer
4.49
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316083AB2-161 GEN
Solar/Wind Harmer
3.986
316487AF1-042 GEN
Solar/Wind Harmer
3.237
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
0.704
3146376EDENTON
Solar/Wind Harmer
0.704
315742AE1-103 GEN
Solar/Wind Harmer
5.591
315614AA2-178 GEN
Solar/Wind Harmer
2.47
3150341NORNECKC1
Adder
2.066
3150341NORNECKC1
Adder
2.05
316065AD1-022 GEN
Solar/Wind Harmer
11.003
3145893MURPHYS
Solar/Wind Harmer
0.596
3145893MURPHYS
Solar/Wind Harmer
-0.038
3146173TUNIS
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.021
316140AB2-099
Solar/Wind Harmer
0.141
3144356SAPONY
Solar/Wind Harmer
0.724
316315AB2-025 C
Solar/Wind Harmer
0.559
3143526WINTERP
Solar/Wind Harmer
-0.107
316365GEN2_N
Solar/Wind Harmer
1.341
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.012
3145933PARMELE
Solar/Wind Harmer
-0.039
3145933PARMELE
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
2.82
3145593CAROLNA
Solar/Wind Harmer
-0.019
3145593CAROLNA
Solar/Wind Harmer
-0.019
3145593CAROLNA
Solar/Wind Harmer
0.162
313506AB2-031 GEN
Solar/Wind Harmer
1.558
972189AH1-679 GEN
Adder
2.896
3145783HORNRTN
Solar/Wind Harmer
2.3
3145783HORNRTN
Solar/Wind Harmer
1.84
3145783HORNRTN
Solar/Wind Harmer
0.575
3145783HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
-0.058
316005AA1-067
Solar/Wind Harmer
0.386
315724AD1-057 GEN
Solar/Wind Harmer
3.602
3145493TOT1
Solar/Wind Harmer
0.281
3145453TOT5
Solar/Wind Harmer
0.169
3145603CNETO
Solar/Wind Harmer
0.113
972185AH1-677 GEN
Adder
9.001
972187AH1-678 GEN
Adder
4.535
970933AG2-581 GEN
Solar/Wind Harmer
16.625
961601AG1-000A GEN
Solar/Wind Harmer
6.942
316049AB1-081 GEN
Solar/Wind Harmer
1.899
316263AC1-034 GEN
Solar/Wind Harmer
8.272
971223AH1-071 GEN
Solar/Wind Harmer
2.151
970099AG2-077 GEN
Solar/Wind Harmer
21.346
313527AB2-043 GEN
Solar/Wind Harmer
2.699
316237AB2-079_GEN
Solar/Wind Harmer
0.499
970323AG2-213 GEN
Solar/Wind Harmer
8.174
315687AD1-152 GEN
Solar/Wind Harmer
1.946
958211AF2-115 GEN
Solar/Wind Harmer
2.517
3144293JTRSVLE
Adder
0.342
970301AG2-198 GEN
Solar/Wind Harmer
8.051
962561AG1-105 GEN
Solar/Wind Harmer
9.025
3147133PAMPLIN
Solar/Wind Harmer
-0.016
3147133PAMPLIN
Solar/Wind Harmer
-0.013
316313AB2-026
Solar/Wind Harmer
0.431
964791AG1-342 GEN
Solar/Wind Harmer
3.405
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
9.809
316118AC1-105 GEN
Solar/Wind Harmer
1.076
316248AF1-058 C
Solar/Wind Harmer
0.464
316045AC1-158 PL2
Solar/Wind Helper
5.208
316450AC1-158 RIC
Solar/Wind Helper
0.434
316006AB2-029 C
Solar/Wind Helper
0.116
316411AF1-147_GEN1
Solar/Wind Helper
0.787
316337AD2-073 GEN
Solar/Wind Harmer
0.521
316087AB2-174 GEN
Solar/Wind Harmer
2.767
960081AF2-299 GEN
Solar/Wind Harmer
2.183
3145783HORNRTN
Solar/Wind Harmer
-0.019
3145796HORNRTN
Solar/Wind Harmer
-0.063
3145796HORNRTN
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
316494AC1-189 GEN
Solar/Wind Harmer
2.003
3147043LAWRENC
Adder
1.495
941031AE2-094 GEN
Solar/Wind Harmer
34.328
961671AG1-007 GEN
Solar/Wind Harmer
0.23
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.54
316319Z2-044 C
Solar/Wind Harmer
0.995
3146233WITAKRS
Solar/Wind Harmer
-0.071
316129AC1-054 GEN
Solar/Wind Harmer
1.557
971065AG2-659 GEN
Solar/Wind Harmer
8.829
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145543BTLEBRO
Solar/Wind Harmer
-0.014
316359AB2-059 GEN
Solar/Wind Harmer
2.373
3142053HEARTS
Solar/Wind Harmer
0.207
970919AG2-571 GEN
Solar/Wind Harmer
5.539
970087AG2-069 GEN
Solar/Wind Harmer
16.286
3143226MDLTHAN
Solar/Wind Harmer
-0.017
957481AF2-042 GEN
Solar/Wind Harmer
53.366
315693AD1-088 GEN
Solar/Wind Harmer
8.434
316131AB2-060 GEN
Solar/Wind Harmer
1.787
316210AC1-098 GEN
Solar/Wind Harmer
3.01
3145746EVERETS
Solar/Wind Harmer
-0.076
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
316274AC1-208 GEN
Solar/Wind Harmer
2.037
957861AF2-080 GEN
Solar/Wind Harmer
8.145
316468AD1-105 GEN
Solar/Wind Harmer
2.129
316327AA2-057 GEN
Solar/Wind Harmer
1.85
970533AG2-339 GEN
Solar/Wind Harmer
12.312
970673AG2-436 GEN
Solar/Wind Harmer
39.799
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
970831AG2-522 GEN
Solar/Wind Harmer
9
971967AH1-528 GEN
Solar/Wind Harmer
33.722
970085AG2-068 GEN
Solar/Wind Harmer
10.857
970581AG2-369 GEN
Solar/Wind Harmer
9.337
316486AD2-202 GEN
Solar/Wind Harmer
0.423
316238AB2-078_GEN
Solar/Wind Harmer
0.499
316239AB2-077_GEN
Solar/Wind Harmer
0.499
3144303KENBRDG
Solar/Wind Harmer
-0.013
970683AG2-441 GEN
Solar/Wind Harmer
11.458
970681AG2-440 GEN
Solar/Wind Harmer
7.605
315616AA1-038_C
Solar/Wind Harmer
3.309
3148463FAIRFLD
Solar/Wind Harmer
-0.016
3151881LOWMORC
Adder
1.531
3151881LOWMORC
Adder
1.507
3151861LOWMORA
Adder
1.483
3148133STUARTS
Solar/Wind Harmer
-0.01
3148013FISHERV
Solar/Wind Harmer
-0.009
946301AF1-294 GEN
Solar/Wind Harmer
4.127
961791AG1-021 GEN
Solar/Wind Harmer
2.013
316258AE1-075 C
Solar/Wind Harmer
0.388
316405AF2-144 C
Solar/Wind Harmer
0.409
3147173SINAI
Solar/Wind Harmer
-0.015
3147243WELCO
Solar/Wind Harmer
-0.01
972205AH1-687 GEN
Adder
5.412
316164AC1-076 GEN
Solar/Wind Helper
1.275
226929AD2-058 GEN
Solar/Wind Helper
0.095
315651AD1-115 GEN
Solar/Wind Helper
0.788
3138216PACIFIC
Solar/Wind Helper
0.038
315785AD2-033 C
Solar/Wind Harmer
3.71
316034AC1-036 C
Solar/Wind Harmer
0.302
970685AG2-442 GEN
Solar/Wind Harmer
14.149
971563AH1-280 GEN
Solar/Wind Harmer
2.013
3144293JTRSVLE
Adder
0.342
3144293JTRSVLE
Adder
0.27
3143336POWHATN
Solar/Wind Harmer
1.901
970401AG2-262 GEN
Solar/Wind Harmer
1.04
3146926FARMVIL
Solar/Wind Harmer
-0.009
316447AC1-158 HLD
Solar/Wind Helper
3.581
316044AC1-158 PL1
Solar/Wind Helper
1.628
316415AF1-147_GEN2
Solar/Wind Helper
0.787
971845AH1-439 GEN
Solar/Wind Harmer
4.534
3152191CUNINGD
50/50
5.803
972255AH1-712 GEN
50/50
175.644
3151161SURRY 1
50/50
9.741
316075AC2-137 C
Solar/Wind Harmer
0.841
3142416OLDCHRC
Solar/Wind Harmer
3.118
970293AG2-193 GEN
Solar/Wind Harmer
3.766
3142946ENON
Solar/Wind Harmer
-0.01
3150921YORKTN3
Adder
6.481
3144216WINCHST
Adder
0.964
3141766HARMONY
Solar/Wind Harmer
2.509
3142433PROV 92
Adder
0.484
3142433PROV 92
Adder
0.484
3141843SHACKLE
Adder
1.266
316203AE2-005 GEN
Solar/Wind Harmer
11.735
3143096IRON208
Adder
1.031
3143096IRON208
Adder
1.011
3141873WAN 176
Solar/Wind Harmer
3.258
316473AC1-191 GEN
Solar/Wind Harmer
2.937
970133AG2-095 GEN
Solar/Wind Harmer
3.03
316458AB2-190 GEN2
Solar/Wind Harmer
2.715
315778AD1-151 GEN
Solar/Wind Harmer
23.946
961611AG1-000B GEN
Solar/Wind Harmer
5.66
3151171GRAVELC
Adder
3.345
3145336SMITFLD
Solar/Wind Harmer
-0.011
3144536CHRHLND
Solar/Wind Harmer
-0.004
3151101ELIZAR3
Adder
21.552
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
118.473
944601AF1-125 GEN
Solar/Wind Harmer
116.624
3142956BIRDNECK
Solar/Wind Harmer
1.394
316017AA1-139 ULT1
Solar/Wind Harmer
2.071
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
2.961
316305AF2-043 C
Solar/Wind Harmer
0.765
316246AF1-032 C
Solar/Wind Harmer
0.513
316320Y1-086
Solar/Wind Harmer
1.475
316321Z2-027
Solar/Wind Harmer
0.673
3146516WINFALL
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
4.971
316484AD2-074 GEN
Solar/Wind Harmer
6.185
961951AG1-038 GEN
Solar/Wind Harmer
3.237
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315813AE1-149 C
Solar/Wind Harmer
15.241
3150861SPRUNCD
Adder
0.999
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146376EDENTON
Solar/Wind Harmer
-0.024
315735AD1-075 GEN1
Solar/Wind Harmer
2.245
316077AC2-138 C
Solar/Wind Harmer
0.467
3150351NORNECKC2
Adder
2
3146206CASHIE
Solar/Wind Harmer
-0.022
3156081AA2-088 GEN
Solar/Wind Harmer
7.053
3145893MURPHYS
Solar/Wind Harmer
0.149
3145893MURPHYS
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.021
3145963POPLR C
Solar/Wind Harmer
-0.021
3146263WOODLND
Solar/Wind Harmer
-0.02
316317KELFORD C
Solar/Wind Harmer
0.94
3145823KELFORD
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
316190AA2-174 GEN
Solar/Wind Harmer
0.242
3145933PARMELE
Solar/Wind Harmer
-0.02
316011AB1-132 GEN
Solar/Wind Harmer
4.096
316181AB2-040 GEN
Solar/Wind Harmer
2.706
966621AG1-532 GEN
Solar/Wind Harmer
0.394
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.019
316212AC1-099_GEN
Solar/Wind Harmer
1.672
3145746EVERETS
Solar/Wind Harmer
-0.019
3145746EVERETS
Solar/Wind Harmer
-0.019
971781AH1-399 GEN
Solar/Wind Harmer
1.148
3147043LAWRENC
Solar/Wind Harmer
-0.011
315722AD1-056 GEN
Solar/Wind Harmer
6.548
316420AA1-050 GEN
Solar/Wind Harmer
2.093
944011AF1-069 GEN
Solar/Wind Harmer
10.756
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146233WITAKRS
Solar/Wind Harmer
0.377
3146233WITAKRS
Solar/Wind Harmer
-0.012
3138543CONSLDL
Solar/Wind Harmer
-0.012
961601AG1-000A GEN
Solar/Wind Harmer
7.03
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145543BTLEBRO
Solar/Wind Harmer
-0.018
970917AG2-570 GEN
Solar/Wind Harmer
43.761
316478AD1-087 GEN
Solar/Wind Harmer
1.444
964241AG1-285 GEN
Solar/Wind Harmer
12.912
316223AC1-118
Solar/Wind Harmer
0.442
3141906WESTMOR
Solar/Wind Harmer
-0.007
970257AG2-171 GEN
Solar/Wind Harmer
6.13
971775AH1-396 GEN
Solar/Wind Harmer
1.153
959311AF2-222 GEN
Solar/Wind Harmer
17.026
3151861LOWMORA
Adder
1.543
3148013FISHERV
Solar/Wind Harmer
-0.016
3144293JTRSVLE
Adder
0.342
3147133PAMPLIN
Solar/Wind Harmer
-0.05
3143336POWHATN
Solar/Wind Harmer
1.616
942461AE2-259 GEN
Solar/Wind Harmer
2.374
3146926FARMVIL
Solar/Wind Harmer
-0.009
316003AC1-222 GEN
Solar/Wind Harmer
1.472
3141196NOKESVL
Solar/Wind Helper
1.012
227287AC2-120 GEN
Solar/Wind Helper
0.323
226910AB2-157 C
Solar/Wind Helper
0.013
CPLELTFEXP_CPLE->PJM
CLTF
10.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.034
LAGNLTFEXP_LAGN->PJM
CLTF
9.566
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.912
TVALTFEXP_TVA->PJM
CLTF
4.87
NYPJM->LTFIMP_NY
CLTF
3.28
LGEELTFEXP_LGEE->PJM
CLTF
2.161
WECLTFEXP_WEC->PJM
CLTF
1.091
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.122
MECLTFEXP_MEC->PJM
CLTF
5.465
SIGELTFEXP_SIGE->PJM
CLTF
0.171

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:159.03 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:6472.73
MW Contribution:
220.27
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
2.388
3151161SURRY 1
50/50
14.898
3142416OLDCHRC
Solar/Wind Harmer
3.766
316075AC2-137 C
Solar/Wind Harmer
0.103
970293AG2-193 GEN
Solar/Wind Harmer
4.088
3142946ENON
Solar/Wind Harmer
0.127
3143096IRON208
Adder
1.568
3143096IRON208
Adder
1.537
3150921YORKTN3
Adder
9.345
3144216WINCHST
Adder
1.4
970133AG2-095 GEN
Solar/Wind Harmer
3.539
316458AB2-190 GEN2
Solar/Wind Harmer
1.962
315778AD1-151 GEN
Solar/Wind Harmer
29.389
961611AG1-000B GEN
Solar/Wind Harmer
9.766
3151171GRAVELC
Adder
5.116
3150861SPRUNCD
Adder
1.68
3145336SMITFLD
Solar/Wind Harmer
0.146
3144536CHRHLND
Solar/Wind Harmer
0.054
944581AF1-123 GEN
Solar/Wind Harmer
81.688
944601AF1-125 GEN
Solar/Wind Harmer
80.429
3151101ELIZAR3
Adder
33.663
3144873MCLAUGH
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.191
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.357
971153AH1-033 GEN
Solar/Wind Harmer
4.134
316473AC1-191 GEN
Solar/Wind Harmer
1.208
316246AF1-032 C
Solar/Wind Harmer
0.158
315813AE1-149 C
Solar/Wind Harmer
18.999
970657AG2-426 GEN
Solar/Wind Harmer
7.973
316321Z2-027
Solar/Wind Harmer
0.063
3141766HARMONY
Solar/Wind Harmer
4.65
3146516WINFALL
Solar/Wind Harmer
0.348
3141843SHACKLE
Adder
1.775
316203AE2-005 GEN
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
0.346
3145273HOLLAND
Solar/Wind Harmer
0.257
3141873WAN 176
Solar/Wind Harmer
6.09
3146376EDENTON
Solar/Wind Harmer
0.338
944011AF1-069 GEN
Solar/Wind Harmer
19.64
315735AD1-075 GEN1
Solar/Wind Harmer
0.917
972255AH1-712 GEN
Adder
164.477
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.318
3145893MURPHYS
Solar/Wind Harmer
0.528
3145893MURPHYS
Solar/Wind Harmer
0.315
3146173TUNIS
Solar/Wind Harmer
0.312
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
970917AG2-570 GEN
Solar/Wind Harmer
27.157
3145823KELFORD
Solar/Wind Harmer
0.303
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
316011AB1-132 GEN
Solar/Wind Harmer
5.448
316181AB2-040 GEN
Solar/Wind Harmer
0.427
3145796HORNRTN
Solar/Wind Harmer
1.183
3145796HORNRTN
Solar/Wind Harmer
0.296
3145933PARMELE
Solar/Wind Harmer
0.292
3147043LAWRENC
Solar/Wind Harmer
0.175
316212AC1-099_GEN
Solar/Wind Harmer
1.498
3143336POWHATN
Solar/Wind Harmer
4.37
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
315722AD1-056 GEN
Solar/Wind Harmer
9.736
316478AD1-087 GEN
Solar/Wind Harmer
0.974
3150351NORNECKC2
Adder
2.799
3146073TAR RVR
Solar/Wind Harmer
0.275
3146083TARBORO
Solar/Wind Harmer
0.275
3146233WITAKRS
Solar/Wind Harmer
1.38
3146233WITAKRS
Solar/Wind Harmer
0.187
3138543CONSLDL
Solar/Wind Harmer
0.181
961601AG1-000A GEN
Solar/Wind Harmer
19.208
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.27
971623AH1-311 GEN
Solar/Wind Harmer
0.54
964241AG1-285 GEN
Solar/Wind Harmer
17.565
970257AG2-171 GEN
Solar/Wind Harmer
8.322
971775AH1-396 GEN
Solar/Wind Harmer
0.416
959311AF2-222 GEN
Solar/Wind Harmer
23.056
3144293JTRSVLE
Adder
0.61
3147133PAMPLIN
Solar/Wind Harmer
0.797
971781AH1-399 GEN
Solar/Wind Harmer
0.329
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.147
3146776BUCKING
Solar/Wind Harmer
0.082
971683AH1-343 GEN
Solar/Wind Harmer
8.387
316222AC1-221 GEN
Solar/Wind Harmer
0.936
316283AC2-100 C
Solar/Wind Harmer
0.443
972003AH1-546 GEN
Solar/Wind Harmer
7.301
316223AC1-118
Solar/Wind Harmer
0.148
3141906WESTMOR
Solar/Wind Harmer
0.083
316123AC1-075 GEN
Solar/Wind Harmer
0.276
970221AG2-151 GEN
Solar/Wind Harmer
10.604
270494AE1-108_GEN
Solar/Wind Harmer
2.19
315821AE2-092 GEN
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.032
3148013FISHERV
Solar/Wind Harmer
0.153
3151861LOWMORA
Adder
1.602
958131AF2-107 GEN
Solar/Wind Harmer
4.284
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3141196NOKESVL
Solar/Wind Helper
1.392
3147666LOUISA
Solar/Wind Helper
0.739
227287AC2-120 GEN
Solar/Wind Helper
0.434
226910AB2-157 C
Solar/Wind Helper
0.018
3132273ORANGE
Solar/Wind Helper
0.053
23777801MSM_W1-116
Solar/Wind Helper
0.111
208835TUHI V3-051
Solar/Wind Helper
0.021
237002AB1-128_GEN
Solar/Wind Helper
0.386
237038AE2-054 C
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.384
237085AD2-009_GEN
Solar/Wind Helper
1.397
233935AB2-179 C
Solar/Wind Helper
1.236
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
233987AB2-037 GEN
Solar/Wind Helper
2.28
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.732
233997TMININ_4.2
Solar/Wind Helper
0.2
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
233950AC2-186 GEN
Solar/Wind Helper
0.113
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.049
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
972263AH1-716 GEN
50/50
220.273
3150631CHESTG8
50/50
2.35
316159AE1-175 C
Solar/Wind Harmer
0.323
315697AD1-025 GEN
Solar/Wind Harmer
0.395
3151201GRAVEL4
Adder
26.62
3151221GRAVEL6
Adder
26.59
3151191GRAVEL3
Adder
26.283
3151211GRAVEL5
Adder
26.283
971445AH1-216 GEN
Solar/Wind Harmer
25.675
971285AH1-108 GEN
Adder
2.749
3151081ELIZAR1
Adder
33.238
3151091ELIZAR2
Adder
32.66
316316AC1-027 C
Solar/Wind Harmer
0.345
957871AF2-081 GEN
Solar/Wind Harmer
17.845
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3138283WHITEMARSH
Solar/Wind Harmer
0.083
3146406KITTY HAWK
Solar/Wind Harmer
0.044
970657AG2-426 GEN
Solar/Wind Harmer
2.609
316311AC2-079 GEN
Solar/Wind Harmer
10.174
3143873LANEXA
Solar/Wind Harmer
0.212
316233AE1-074 FULL
Solar/Wind Harmer
0.283
971281AH1-106 GEN
Solar/Wind Harmer
4.907
971283AH1-107 GEN
Solar/Wind Harmer
4.907
313526AB2-022
Solar/Wind Harmer
0.189
3146486SUNBURY
Solar/Wind Harmer
0.352
3146486SUNBURY
Solar/Wind Harmer
0.352
3143316POE
Solar/Wind Harmer
1.394
3146396TANGLEW
Solar/Wind Harmer
0.969
3145176PASQUOTANK
Solar/Wind Harmer
0.218
970189AG2-124 GEN
Solar/Wind Harmer
10.294
3141873WAN 176
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.338
3130156CHOWAN
Solar/Wind Harmer
0.338
3141913WHIT STONE
Solar/Wind Harmer
0.332
315814AE2-033 C
Solar/Wind Harmer
26.224
3138133OCRAN
Solar/Wind Harmer
0.099
970533AG2-339 GEN
Solar/Wind Harmer
24.659
3141783LANCAST
Solar/Wind Harmer
0.195
3141783LANCAST
Solar/Wind Harmer
0.13
3130546PLYMOUTH
Solar/Wind Harmer
0.323
970673AG2-436 GEN
Solar/Wind Harmer
40.239
315732AD1-074 GEN1
Solar/Wind Harmer
1.836
315733AD1-074 GEN2
Solar/Wind Harmer
1.836
3146206CASHIE
Solar/Wind Harmer
0.318
970601AG2-382 GEN
Solar/Wind Harmer
11.886
971967AH1-528 GEN
Solar/Wind Harmer
50.538
3145893MURPHYS
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.315
316463AE2-346 GEN
Solar/Wind Harmer
0.265
3145513AHOSKIE
Solar/Wind Harmer
0.65
3145513AHOSKIE
Solar/Wind Harmer
0.311
3145683EARLEYS
Solar/Wind Harmer
0.619
3145683EARLEYS
Solar/Wind Harmer
0.309
3145683EARLEYS
Solar/Wind Harmer
0.309
3146043SEABORD
Solar/Wind Harmer
0.307
970085AG2-068 GEN
Solar/Wind Harmer
16.114
970581AG2-369 GEN
Solar/Wind Harmer
13.858
315652AC1-086 GEN
Solar/Wind Harmer
33.038
316426AA2-053 GEN
Solar/Wind Harmer
1.002
3137643SOCKMAN
Solar/Wind Harmer
1.193
3145796HORNRTN
Solar/Wind Harmer
0.947
3145796HORNRTN
Solar/Wind Harmer
0.118
3146033SCOT NK
Solar/Wind Harmer
1.183
316210AC1-098 GEN
Solar/Wind Harmer
2.685
316258AE1-075 C
Solar/Wind Harmer
0.216
316274AC1-208 GEN
Solar/Wind Harmer
1.484
3145746EVERETS
Solar/Wind Harmer
1.136
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
970831AG2-522 GEN
Solar/Wind Harmer
12.02
316486AD2-202 GEN
Solar/Wind Harmer
0.286
957861AF2-080 GEN
Solar/Wind Harmer
12.085
316327AA2-057 GEN
Solar/Wind Harmer
0.413
3141813NORNECK
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.275
3145573BETHELC
Solar/Wind Harmer
0.275
3144303KENBRDG
Solar/Wind Harmer
0.208
970683AG2-441 GEN
Solar/Wind Harmer
15.53
970681AG2-440 GEN
Solar/Wind Harmer
10.308
946301AF1-294 GEN
Solar/Wind Harmer
5.041
961791AG1-021 GEN
Solar/Wind Harmer
2.452
3147173SINAI
Solar/Wind Harmer
0.246
3147243WELCO
Solar/Wind Harmer
0.154
971845AH1-439 GEN
Solar/Wind Harmer
10.407
972205AH1-687 GEN
Adder
8.897
270197AD1-017 GEN1
Solar/Wind Harmer
1.05
3148133STUARTS
Solar/Wind Harmer
0.092
3148013FISHERV
Solar/Wind Harmer
0.088
3148463FAIRFLD
Solar/Wind Harmer
0.149
3151881LOWMORC
Adder
1.59
3151881LOWMORC
Adder
1.565
3151861LOWMORA
Adder
1.54
270069AE2-166 C O1
Solar/Wind Harmer
6.438
944491AF1-114 GEN
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.855
315651AD1-115 GEN
Solar/Wind Helper
1.155
226929AD2-058 GEN
Solar/Wind Helper
0.127
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
23779801AA1-109
Solar/Wind Helper
0.186
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.161
205917AD1-020 ES
Solar/Wind Helper
0.356
233915AB1-141 GEN
Solar/Wind Helper
0.489
205943AE1-185 GEN
Solar/Wind Helper
0.494
205956AE1-196_GEN
Solar/Wind Helper
0.494
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219615MILLCREEK C
Solar/Wind Helper
0.026
3142296MT RD221
50/50
1.309
3150691DARBY 3
50/50
29.078
3150701DARBY 4
50/50
29.01
3150681DARBY 2
50/50
28.977
3150671DARBY 1
50/50
28.943
3142366NRTHEST
50/50
1.316
3150621CHESTS7
50/50
1.097
316312AB1-027
Solar/Wind Harmer
0.691
315976AC1-164 GENA
Solar/Wind Harmer
4.068
316169AC1-164_GENC
Solar/Wind Harmer
3.515
3142946ENON
Solar/Wind Harmer
0.038
316294AC1-161 GEN
Solar/Wind Harmer
6.385
316033AB2-134 GEN
Solar/Wind Harmer
0.002
944641AF1-129 GEN
Adder
173.96
3150991CHESPKB
Adder
3.796
3150991CHESPKB
Adder
3.705
3145506HICKORY
Solar/Wind Harmer
1.441
3145506HICKORY
Solar/Wind Harmer
0.864
3145506HICKORY
Solar/Wind Harmer
0.216
316339AD2-160 GEN
Solar/Wind Harmer
0.574
316388AE2-253 GEN
Solar/Wind Harmer
1.117
3137176SLIGO L2192
Solar/Wind Harmer
1.423
3146456SLIGO L269
Solar/Wind Harmer
6.328
966871AG1-558 GEN
Solar/Wind Harmer
0.413
3130086AYDLETT
Solar/Wind Harmer
1.428
316349AD2-085 GEN
Solar/Wind Harmer
0.236
3143526WINTERP
Solar/Wind Harmer
1.839
315835AF2-110_GEN
Solar/Wind Harmer
2.427
3146386ELIZ CT
Solar/Wind Harmer
0.353
3146516WINFALL
Solar/Wind Harmer
0.348
3146516WINFALL
Solar/Wind Harmer
0.348
3146516WINFALL
Solar/Wind Harmer
0.348
3146626S HERTFORD
Solar/Wind Harmer
0.346
3146626S HERTFORD
Solar/Wind Harmer
0.346
971223AH1-071 GEN
Solar/Wind Harmer
3.659
316156AD2-030 GEN
Solar/Wind Harmer
0.251
315742AE1-103 GEN
Solar/Wind Harmer
5.052
3146376EDENTON
Solar/Wind Harmer
1.502
3146376EDENTON
Solar/Wind Harmer
1.502
3144356SAPONY
Solar/Wind Harmer
2.782
316315AB2-025 C
Solar/Wind Harmer
0.266
315614AA2-178 GEN
Solar/Wind Harmer
1.876
972193AH1-681 GEN
Adder
7.349
316065AD1-022 GEN
Solar/Wind Harmer
14.725
972185AH1-677 GEN
Adder
17.888
3145893MURPHYS
Solar/Wind Harmer
2.11
3145893MURPHYS
Solar/Wind Harmer
0.567
972187AH1-678 GEN
Adder
8.982
3146173TUNIS
Solar/Wind Harmer
0.312
3146173TUNIS
Solar/Wind Harmer
0.312
316365GEN2_N
Solar/Wind Harmer
0.691
316140AB2-099
Solar/Wind Harmer
0.111
970933AG2-581 GEN
Solar/Wind Harmer
24.793
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.181
962571AG1-106 GEN
Solar/Wind Harmer
4.273
313506AB2-031 GEN
Solar/Wind Harmer
0.92
3145593CAROLNA
Solar/Wind Harmer
0.297
3145593CAROLNA
Solar/Wind Harmer
0.297
3145593CAROLNA
Solar/Wind Harmer
0.37
3145796HORNRTN
Solar/Wind Harmer
0.888
3145783HORNRTN
Solar/Wind Harmer
5.262
3145783HORNRTN
Solar/Wind Harmer
4.209
3145783HORNRTN
Solar/Wind Harmer
1.315
3145783HORNRTN
Solar/Wind Harmer
0.526
3145933PARMELE
Solar/Wind Harmer
0.584
3145933PARMELE
Solar/Wind Harmer
0.292
970099AG2-077 GEN
Solar/Wind Harmer
31.038
316313AB2-026
Solar/Wind Harmer
0.18
316005AA1-067
Solar/Wind Harmer
0.305
315724AD1-057 GEN
Solar/Wind Harmer
5.431
3150341NORNECKC1
Adder
2.892
3150341NORNECKC1
Adder
2.869
3145493TOT1
Solar/Wind Harmer
0.639
3145453TOT5
Solar/Wind Harmer
0.383
3145603CNETO
Solar/Wind Harmer
0.256
316336AC2-165 C
Solar/Wind Harmer
13.939
961601AG1-000A GEN
Solar/Wind Harmer
4.802
316049AB1-081 GEN
Solar/Wind Harmer
1.536
316263AC1-034 GEN
Solar/Wind Harmer
10.258
970301AG2-198 GEN
Solar/Wind Harmer
11.151
970323AG2-213 GEN
Solar/Wind Harmer
11.095
972189AH1-679 GEN
Adder
4.352
962561AG1-105 GEN
Solar/Wind Harmer
12.278
958211AF2-115 GEN
Solar/Wind Harmer
3.066
3144293JTRSVLE
Adder
0.61
964791AG1-342 GEN
Solar/Wind Harmer
4.878
3146843MT LREL
Solar/Wind Harmer
0.254
3146843MT LREL
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.203
316118AC1-105 GEN
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.912
3146776BUCKING
Solar/Wind Harmer
0.074
942751AE2-291 GEN
Solar/Wind Harmer
10.74
942671AE2-283 GEN
Solar/Wind Harmer
3.934
316045AC1-158 PL2
Solar/Wind Helper
8.047
316450AC1-158 RIC
Solar/Wind Helper
0.671
316006AB2-029 C
Solar/Wind Helper
0.166
316411AF1-147_GEN1
Solar/Wind Helper
1.085
223401AF1-299 GEN
Solar/Wind Helper
0.395
223402AF1-300 C
Solar/Wind Helper
0.395
237006AB1-125 GEN
Solar/Wind Helper
0.121
238221AF1-254 C O1
Solar/Wind Helper
0.239
235020AA1-095 C
Solar/Wind Helper
0.045
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.432
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232436AB1-176 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.113
233946AB2-136 GEN
Solar/Wind Helper
0.553
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.935
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.329
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.016
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.058
219912AD2-042 GEN
Solar/Wind Helper
0.145
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.077
219304NAMERICA C
Solar/Wind Helper
0.126
3152331SURRY 2
50/50
15.655
3150641CHESTS8
50/50
1.21
3142416OLDCHRC
Solar/Wind Harmer
1.01
3142416OLDCHRC
Solar/Wind Harmer
0.387
315975AC1-164 GENB
Solar/Wind Harmer
0.12
944631AF1-128 GEN
Adder
179.295
3143096IRON208
Adder
1.568
3138126ROCKLANDING
Solar/Wind Harmer
0.17
971317AH1-138 GEN
Solar/Wind Harmer
2.77
315773AC2-141 GEN
Solar/Wind Harmer
13.491
3142543TWELFTH
Solar/Wind Harmer
0.035
316132AB2-190 GEN1
Solar/Wind Harmer
1.962
971069AG2-661 GEN
Solar/Wind Harmer
6.531
961611AG1-000B GEN
Solar/Wind Harmer
19.206
3151171GRAVELC
Adder
3.89
3150851SPRUNCC
Adder
1.68
3145336SMITFLD
Solar/Wind Harmer
1.457
944591AF1-124 GEN
Solar/Wind Harmer
81.978
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.064
3150981CHESPKA
Adder
4.525
315671AE2-027_GEN
Solar/Wind Harmer
0.002
316072AD1-144
Solar/Wind Harmer
0.128
3142433PROV 92
Solar/Wind Harmer
1.431
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.357
319010AE1-072 C
Solar/Wind Harmer
1.782
316381AD1-082 GEN
Solar/Wind Harmer
0.36
3143526WINTERP
Solar/Wind Harmer
1.839
316093AE2-104_GEN
Solar/Wind Harmer
5.948
3141766HARMONY
Solar/Wind Harmer
0.07
3146516WINFALL
Solar/Wind Harmer
1.128
3146516WINFALL
Solar/Wind Harmer
0.348
971777AH1-397 GEN
Solar/Wind Harmer
0.917
939411AE1-173 GEN
Solar/Wind Harmer
148.2
3143226MDLTHAN
Solar/Wind Harmer
0.343
940641AE2-051 GEN
Solar/Wind Harmer
27.419
3130156CHOWAN
Solar/Wind Harmer
0.338
3138133OCRAN
Solar/Wind Harmer
0.198
315816AE2-034 GEN
Solar/Wind Harmer
1.407
3145663CRESWEL
Solar/Wind Harmer
0.923
971163AH1-040 GEN
Solar/Wind Harmer
26.382
941031AE2-094 GEN
Solar/Wind Harmer
60.109
315737AD1-076 GEN
Solar/Wind Harmer
4.134
972277AH1-723 GEN
Adder
191.666
3146206CASHIE
Solar/Wind Harmer
0.318
971547AH1-271 GEN
Solar/Wind Harmer
6.792
3145893MURPHYS
Solar/Wind Harmer
1.261
3145893MURPHYS
Solar/Wind Harmer
1.402
3156021HOLLOMANSOL
Solar/Wind Harmer
1.407
3146173TUNIS
Solar/Wind Harmer
0.312
316023GEN1_S
Solar/Wind Harmer
0.691
3145683EARLEYS
Solar/Wind Harmer
0.309
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
315607AA1-063A GEN
Solar/Wind Harmer
0.615
970919AG2-571 GEN
Solar/Wind Harmer
10.863
3145823KELFORD
Solar/Wind Harmer
0.303
960081AF2-299 GEN
Solar/Wind Harmer
2.903
970087AG2-069 GEN
Solar/Wind Harmer
24.172
962861AG1-135 GEN
Solar/Wind Harmer
9.549
3145796HORNRTN
Solar/Wind Harmer
0.976
3145796HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.296
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
9.772
3146293MARTNCO
Solar/Wind Harmer
0.271
3147043LAWRENC
Adder
2.634
957481AF2-042 GEN
Solar/Wind Harmer
77.596
3143336POWHATN
Solar/Wind Harmer
5.141
3141726DUNNSVL
Solar/Wind Harmer
1.144
3145746EVERETS
Solar/Wind Harmer
0.285
3145746EVERETS
Solar/Wind Harmer
0.285
315693AD1-088 GEN
Solar/Wind Harmer
13.636
316494AC1-189 GEN
Solar/Wind Harmer
0.947
316129AC1-054 GEN
Solar/Wind Harmer
1.044
971065AG2-659 GEN
Solar/Wind Harmer
11.863
3150351NORNECKC2
Adder
2.753
961671AG1-007 GEN
Solar/Wind Harmer
0.042
3146083TARBORO
Solar/Wind Harmer
0.275
3145493TOT1
Solar/Wind Harmer
1.225
3146233WITAKRS
Solar/Wind Harmer
1.094
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.216
316359AB2-059 GEN
Solar/Wind Harmer
0.959
3142053HEARTS
Solar/Wind Harmer
0.475
316131AB2-060 GEN
Solar/Wind Harmer
0.824
315785AD2-033 C
Solar/Wind Harmer
2.11
316034AC1-036 C
Solar/Wind Harmer
0.017
970685AG2-442 GEN
Solar/Wind Harmer
19.165
971563AH1-280 GEN
Solar/Wind Harmer
2.725
3144293JTRSVLE
Adder
0.61
3144293JTRSVLE
Adder
0.481
970401AG2-262 GEN
Solar/Wind Harmer
1.491
3146926FARMVIL
Solar/Wind Harmer
0.147
316337AD2-073 GEN
Solar/Wind Harmer
0.21
970937AG2-583 GEN
Solar/Wind Harmer
14.653
3146776BUCKING
Solar/Wind Harmer
0.091
971377AH1-170 GEN
Solar/Wind Harmer
2.121
3147623JAMES R
Solar/Wind Harmer
0.461
970223AG2-152 GEN
Solar/Wind Harmer
12.092
3147123OTTER R
Solar/Wind Harmer
0.099
3147312GRETNA
Solar/Wind Harmer
0.126
3146802CHATHAM
Solar/Wind Harmer
0.118
941801AE2-185 GEN
Solar/Wind Harmer
5.057
972135AH1-637 GEN
Solar/Wind Harmer
1.313
270030AE2-140 GEN
Solar/Wind Harmer
15.083
962751AG1-124 GEN
Solar/Wind Harmer
6.345
316447AC1-158 HLD
Solar/Wind Helper
5.534
316044AC1-158 PL1
Solar/Wind Helper
2.515
316415AF1-147_GEN2
Solar/Wind Helper
1.085
3147666LOUISA
Solar/Wind Helper
1.286
316192AB2-158 GEN
Solar/Wind Helper
2.116
23777901MDS_W4-102
Solar/Wind Helper
0.153
237001AB1-127_GEN
Solar/Wind Helper
0.387
208835TUHI V3-051
Solar/Wind Helper
0.021
235063AE1-101 C2
Solar/Wind Helper
1.432
205916AD1-020 GEN
Solar/Wind Helper
1.655
233918AB1-142 GEN
Solar/Wind Helper
0.489
233944AB2-135 GEN
Solar/Wind Helper
0.574
205932AD2-116_GEN
Solar/Wind Helper
0.494
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.2
233998TM1NIN_3.36
Solar/Wind Helper
0.2
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
238175AF1-290_GEN
Solar/Wind Helper
0.121
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219348LDSOLAR C
Solar/Wind Helper
0.11
CPLELTFEXP_CPLE->PJM
CLTF
17.675
CBM West 2LTFEXP_CBM-W2->PJM
CBM
79.931
LAGNLTFEXP_LAGN->PJM
CLTF
14.557
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.893
TVALTFEXP_TVA->PJM
CLTF
7.369
NYPJM->LTFIMP_NY
CLTF
4.657
LGEELTFEXP_LGEE->PJM
CLTF
2.991
WECLTFEXP_WEC->PJM
CLTF
1.512
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.074
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.634
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.24

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.85 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:7358.61
MW Contribution:
220.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
2.387
3151161SURRY 1
50/50
14.895
3142416OLDCHRC
Solar/Wind Harmer
4.403
316075AC2-137 C
Solar/Wind Harmer
1.165
970293AG2-193 GEN
Solar/Wind Harmer
5.379
3142946ENON
Solar/Wind Harmer
-0.014
3143096IRON208
Adder
1.568
3143096IRON208
Adder
1.536
3150921YORKTN3
Adder
9.342
3144216WINCHST
Adder
1.4
970133AG2-095 GEN
Solar/Wind Harmer
4.659
316458AB2-190 GEN2
Solar/Wind Harmer
4.168
315778AD1-151 GEN
Solar/Wind Harmer
36.726
961611AG1-000B GEN
Solar/Wind Harmer
8.662
3151171GRAVELC
Adder
5.115
3150861SPRUNCD
Adder
1.68
3145336SMITFLD
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
185.404
944601AF1-125 GEN
Solar/Wind Harmer
182.51
3151101ELIZAR3
Adder
33.657
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142956BIRDNECK
Solar/Wind Harmer
2.18
316017AA1-139 ULT1
Solar/Wind Harmer
3.25
3142433PROV 92
Adder
0.695
3142433PROV 92
Adder
0.695
3146456SLIGO L269
Solar/Wind Harmer
-0.04
971153AH1-033 GEN
Solar/Wind Harmer
4.65
316473AC1-191 GEN
Solar/Wind Harmer
4.32
316305AF2-043 C
Solar/Wind Harmer
1.204
316246AF1-032 C
Solar/Wind Harmer
0.808
315813AE1-149 C
Solar/Wind Harmer
25.011
970657AG2-426 GEN
Solar/Wind Harmer
8.064
316320Y1-086
Solar/Wind Harmer
2.326
316321Z2-027
Solar/Wind Harmer
1.063
3141766HARMONY
Solar/Wind Harmer
3.485
3146516WINFALL
Solar/Wind Harmer
-0.039
3141843SHACKLE
Adder
1.774
316203AE2-005 GEN
Solar/Wind Harmer
16.448
3146626S HERTFORD
Solar/Wind Harmer
-0.039
3145273HOLLAND
Solar/Wind Harmer
-0.029
3141873WAN 176
Solar/Wind Harmer
4.565
3146376EDENTON
Solar/Wind Harmer
-0.038
944011AF1-069 GEN
Solar/Wind Harmer
21.546
315735AD1-075 GEN1
Solar/Wind Harmer
3.653
972255AH1-712 GEN
Adder
164.613
3156081AA2-088 GEN
Solar/Wind Harmer
11.655
3146206CASHIE
Solar/Wind Harmer
-0.036
3145893MURPHYS
Solar/Wind Harmer
0.247
3145893MURPHYS
Solar/Wind Harmer
-0.035
3146173TUNIS
Solar/Wind Harmer
-0.035
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
316484AD2-074 GEN
Solar/Wind Harmer
8.659
961951AG1-038 GEN
Solar/Wind Harmer
4.531
970917AG2-570 GEN
Solar/Wind Harmer
85.84
316317KELFORD C
Solar/Wind Harmer
1.575
3145823KELFORD
Solar/Wind Harmer
-0.034
966621AG1-532 GEN
Solar/Wind Harmer
0.69
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
316011AB1-132 GEN
Solar/Wind Harmer
7.052
316181AB2-040 GEN
Solar/Wind Harmer
4.696
316190AA2-174 GEN
Solar/Wind Harmer
0.413
3145796HORNRTN
Solar/Wind Harmer
-0.132
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145933PARMELE
Solar/Wind Harmer
-0.033
3147043LAWRENC
Solar/Wind Harmer
-0.019
316212AC1-099_GEN
Solar/Wind Harmer
2.841
3143336POWHATN
Solar/Wind Harmer
3.285
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315722AD1-056 GEN
Solar/Wind Harmer
11.266
316478AD1-087 GEN
Solar/Wind Harmer
2.732
316420AA1-050 GEN
Solar/Wind Harmer
3.556
316077AC2-138 C
Solar/Wind Harmer
0.652
3150351NORNECKC2
Adder
2.797
3146073TAR RVR
Solar/Wind Harmer
-0.031
3146083TARBORO
Solar/Wind Harmer
-0.031
3146233WITAKRS
Solar/Wind Harmer
0.647
3146233WITAKRS
Solar/Wind Harmer
-0.021
3138543CONSLDL
Solar/Wind Harmer
-0.02
961601AG1-000A GEN
Solar/Wind Harmer
12.085
3145543BTLEBRO
Solar/Wind Harmer
-0.03
3145543BTLEBRO
Solar/Wind Harmer
-0.03
964241AG1-285 GEN
Solar/Wind Harmer
23.162
970257AG2-171 GEN
Solar/Wind Harmer
10.977
971775AH1-396 GEN
Solar/Wind Harmer
2.065
959311AF2-222 GEN
Solar/Wind Harmer
30.476
3144293JTRSVLE
Adder
0.611
3147133PAMPLIN
Solar/Wind Harmer
-0.089
942461AE2-259 GEN
Solar/Wind Harmer
4.227
971781AH1-399 GEN
Solar/Wind Harmer
1.729
3146926FARMVIL
Solar/Wind Harmer
-0.016
3151861LOWMORA
Adder
1.611
3141196NOKESVL
Solar/Wind Helper
1.395
227287AC2-120 GEN
Solar/Wind Helper
0.435
226910AB2-157 C
Solar/Wind Helper
0.018
3147666LOUISA
Solar/Wind Helper
0.668
23777801MSM_W1-116
Solar/Wind Helper
0.111
3132273ORANGE
Solar/Wind Helper
0.05
208835TUHI V3-051
Solar/Wind Helper
0.022
237002AB1-128_GEN
Solar/Wind Helper
0.387
237038AE2-054 C
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.384
237085AD2-009_GEN
Solar/Wind Helper
1.4
233935AB2-179 C
Solar/Wind Helper
1.238
233933AB2-153 GEN
Solar/Wind Helper
0.227
232422X3-066 FULL
Solar/Wind Helper
0.111
233987AB2-037 GEN
Solar/Wind Helper
2.284
232417X3-008 C
Solar/Wind Helper
0.227
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.733
233997TMININ_4.2
Solar/Wind Helper
0.2
232406W1-004 FULL
Solar/Wind Helper
0.494
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.124
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.049
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
959561AF2-247 GEN
Solar/Wind Helper
0.02
972263AH1-716 GEN
50/50
220.214
3150631CHESTG8
50/50
2.349
316382AG1-145 C
Solar/Wind Harmer
1.277
316159AE1-175 C
Solar/Wind Harmer
1.137
315697AD1-025 GEN
Solar/Wind Harmer
8.32
3151201GRAVEL4
Adder
26.614
3151221GRAVEL6
Adder
26.584
3151191GRAVEL3
Adder
26.277
3151211GRAVEL5
Adder
26.277
971445AH1-216 GEN
Solar/Wind Harmer
25.349
971285AH1-108 GEN
Adder
2.748
316236AE1-162_GEN
Solar/Wind Harmer
1.231
3151081ELIZAR1
Adder
33.232
3151091ELIZAR2
Adder
32.655
316316AC1-027 C
Solar/Wind Harmer
1.245
315839AE2-212 C
Solar/Wind Harmer
1.212
316018AA1-139 ULT2
Solar/Wind Harmer
3.441
957871AF2-081 GEN
Solar/Wind Harmer
20.137
3142433PROV 92
Adder
0.695
3142433PROV 92
Adder
0.695
957831AF2-077 GEN
Solar/Wind Harmer
1.208
3138283WHITEMARSH
Solar/Wind Harmer
0.062
3146406KITTY HAWK
Solar/Wind Harmer
0.033
970657AG2-426 GEN
Solar/Wind Harmer
2.517
315833AF1-017_GEN
Solar/Wind Harmer
7.559
316311AC2-079 GEN
Solar/Wind Harmer
20.077
316233AE1-074 FULL
Solar/Wind Harmer
1.07
3143873LANEXA
Solar/Wind Harmer
-0.024
971281AH1-106 GEN
Solar/Wind Harmer
6.461
971283AH1-107 GEN
Solar/Wind Harmer
6.461
313526AB2-022
Solar/Wind Harmer
1.069
3146486SUNBURY
Solar/Wind Harmer
-0.039
3146486SUNBURY
Solar/Wind Harmer
-0.039
3143316POE
Solar/Wind Harmer
-0.156
3146396TANGLEW
Solar/Wind Harmer
0.727
3145176PASQUOTANK
Solar/Wind Harmer
-0.024
316059AD1-063 C
Solar/Wind Harmer
0.883
957601AF2-054 GEN
Solar/Wind Harmer
1.151
3141873WAN 176
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
9.432
3130156CHOWAN
Solar/Wind Harmer
-0.038
3130156CHOWAN
Solar/Wind Harmer
-0.038
3141913WHIT STONE
Solar/Wind Harmer
-0.037
315814AE2-033 C
Solar/Wind Harmer
34.685
3138133OCRAN
Solar/Wind Harmer
-0.011
970533AG2-339 GEN
Solar/Wind Harmer
24.662
3141783LANCAST
Solar/Wind Harmer
-0.022
3141783LANCAST
Solar/Wind Harmer
-0.014
3130546PLYMOUTH
Solar/Wind Harmer
-0.036
970673AG2-436 GEN
Solar/Wind Harmer
79.486
315732AD1-074 GEN1
Solar/Wind Harmer
7.308
315733AD1-074 GEN2
Solar/Wind Harmer
7.308
3146206CASHIE
Solar/Wind Harmer
-0.036
970601AG2-382 GEN
Solar/Wind Harmer
15.65
971967AH1-528 GEN
Solar/Wind Harmer
66.74
316318V4-068
Solar/Wind Harmer
0.883
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
-0.035
316463AE2-346 GEN
Solar/Wind Harmer
0.564
3145513AHOSKIE
Solar/Wind Harmer
0.305
961941AG1-037 GEN
Solar/Wind Harmer
0.263
3145513AHOSKIE
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.069
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146043SEABORD
Solar/Wind Harmer
-0.034
316174AB2-169 GEN
Solar/Wind Harmer
5.247
946281AF1-292 GEN
Solar/Wind Harmer
0.761
970085AG2-068 GEN
Solar/Wind Harmer
21.224
970581AG2-369 GEN
Solar/Wind Harmer
18.252
315652AC1-086 GEN
Solar/Wind Harmer
37.988
316426AA2-053 GEN
Solar/Wind Harmer
3.393
3137643SOCKMAN
Solar/Wind Harmer
-0.133
3145796HORNRTN
Solar/Wind Harmer
-0.106
3145796HORNRTN
Solar/Wind Harmer
-0.013
3146033SCOT NK
Solar/Wind Harmer
-0.132
316210AC1-098 GEN
Solar/Wind Harmer
5.114
316258AE1-075 C
Solar/Wind Harmer
0.788
316405AF2-144 C
Solar/Wind Harmer
0.832
316274AC1-208 GEN
Solar/Wind Harmer
3.48
3145746EVERETS
Solar/Wind Harmer
-0.127
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
970831AG2-522 GEN
Solar/Wind Harmer
15.837
316486AD2-202 GEN
Solar/Wind Harmer
0.8
957861AF2-080 GEN
Solar/Wind Harmer
13.784
316327AA2-057 GEN
Solar/Wind Harmer
3.168
3141813NORNECK
Solar/Wind Harmer
-0.031
3145573BETHELC
Solar/Wind Harmer
-0.031
3145573BETHELC
Solar/Wind Harmer
-0.031
316238AB2-078_GEN
Solar/Wind Harmer
0.896
316239AB2-077_GEN
Solar/Wind Harmer
0.896
3144303KENBRDG
Solar/Wind Harmer
-0.023
970683AG2-441 GEN
Solar/Wind Harmer
20.491
970681AG2-440 GEN
Solar/Wind Harmer
13.6
946301AF1-294 GEN
Solar/Wind Harmer
7.372
961791AG1-021 GEN
Solar/Wind Harmer
3.596
316468AD1-105 GEN
Solar/Wind Harmer
3.206
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
8.96
3151881LOWMORC
Adder
1.598
3151881LOWMORC
Adder
1.573
3151861LOWMORA
Adder
1.548
316164AC1-076 GEN
Solar/Wind Helper
1.84
315651AD1-115 GEN
Solar/Wind Helper
1.14
226929AD2-058 GEN
Solar/Wind Helper
0.128
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
23779801AA1-109
Solar/Wind Helper
0.186
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.161
205917AD1-020 ES
Solar/Wind Helper
0.357
233915AB1-141 GEN
Solar/Wind Helper
0.49
205943AE1-185 GEN
Solar/Wind Helper
0.495
205956AE1-196_GEN
Solar/Wind Helper
0.495
233901CHERRYDALE C
Solar/Wind Helper
0.227
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219615MILLCREEK C
Solar/Wind Helper
0.026
3152331SURRY 2
50/50
15.651
3150641CHESTS8
50/50
1.21
3142416OLDCHRC
Solar/Wind Harmer
-0.113
3142416OLDCHRC
Solar/Wind Harmer
-0.043
315975AC1-164 GENB
Solar/Wind Harmer
0.292
944631AF1-128 GEN
Adder
179.228
3143096IRON208
Adder
1.568
3138126ROCKLANDING
Solar/Wind Harmer
0.128
971317AH1-138 GEN
Solar/Wind Harmer
5.208
315773AC2-141 GEN
Solar/Wind Harmer
17.37
3142543TWELFTH
Solar/Wind Harmer
-0.004
316132AB2-190 GEN1
Solar/Wind Harmer
4.168
971069AG2-661 GEN
Solar/Wind Harmer
6.529
316369SG1_INVT
Solar/Wind Harmer
7.352
961611AG1-000B GEN
Solar/Wind Harmer
20.302
3151171GRAVELC
Adder
3.89
3150851SPRUNCC
Adder
1.68
3145336SMITFLD
Solar/Wind Harmer
-0.163
944591AF1-124 GEN
Solar/Wind Harmer
186.072
316375AC2-012 GEN
Solar/Wind Harmer
14.08
316036AC1-147 C
Solar/Wind Harmer
1.096
3150981CHESPKA
Adder
4.525
315671AE2-027_GEN
Solar/Wind Harmer
7.317
316072AD1-144
Solar/Wind Harmer
0.814
3142433PROV 92
Solar/Wind Harmer
-0.16
3142433PROV 92
Adder
0.695
3142433PROV 92
Adder
0.695
3146456SLIGO L269
Solar/Wind Harmer
-0.04
319010AE1-072 C
Solar/Wind Harmer
8.103
316381AD1-082 GEN
Solar/Wind Harmer
3.652
3143526WINTERP
Solar/Wind Harmer
-0.206
316093AE2-104_GEN
Solar/Wind Harmer
11.551
316314AB2-024 C
Solar/Wind Harmer
3.382
3141766HARMONY
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.126
3146516WINFALL
Solar/Wind Harmer
-0.039
939411AE1-173 GEN
Solar/Wind Harmer
195.127
971777AH1-397 GEN
Solar/Wind Harmer
4.553
315662AE1-191 GEN
Solar/Wind Harmer
4.664
316280AD1-041 GEN
Solar/Wind Harmer
2.915
3143226MDLTHAN
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
36.103
315611Z1-036_GEN2
Solar/Wind Harmer
9.432
3130156CHOWAN
Solar/Wind Harmer
-0.038
3138133OCRAN
Solar/Wind Harmer
-0.022
315816AE2-034 GEN
Solar/Wind Harmer
2.99
3145663CRESWEL
Solar/Wind Harmer
-0.103
971163AH1-040 GEN
Solar/Wind Harmer
34.736
941031AE2-094 GEN
Solar/Wind Harmer
68.765
315737AD1-076 GEN
Solar/Wind Harmer
6.87
972277AH1-723 GEN
Adder
191.824
3146206CASHIE
Solar/Wind Harmer
-0.036
971547AH1-271 GEN
Solar/Wind Harmer
8.943
3145893MURPHYS
Solar/Wind Harmer
-0.141
3145893MURPHYS
Solar/Wind Harmer
1.051
3156021HOLLOMANSOL
Solar/Wind Harmer
4.722
3146173TUNIS
Solar/Wind Harmer
-0.035
316023GEN1_S
Solar/Wind Harmer
2.35
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
315607AA1-063A GEN
Solar/Wind Harmer
3.46
970919AG2-571 GEN
Solar/Wind Harmer
10.866
3145823KELFORD
Solar/Wind Harmer
-0.034
960081AF2-299 GEN
Solar/Wind Harmer
3.823
970087AG2-069 GEN
Solar/Wind Harmer
31.835
316087AB2-174 GEN
Solar/Wind Harmer
4.814
962861AG1-135 GEN
Solar/Wind Harmer
12.563
3145796HORNRTN
Solar/Wind Harmer
-0.109
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145783HORNRTN
Solar/Wind Harmer
-0.033
316404AE1-155 C
Solar/Wind Harmer
6.334
958261AF2-120 GEN
Solar/Wind Harmer
12.857
3146293MARTNCO
Solar/Wind Harmer
0.203
3147043LAWRENC
Adder
2.635
957481AF2-042 GEN
Solar/Wind Harmer
102.244
3143336POWHATN
Solar/Wind Harmer
3.865
964211AG1-282 GEN
Solar/Wind Harmer
0.966
3141726DUNNSVL
Solar/Wind Harmer
-0.128
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315693AD1-088 GEN
Solar/Wind Harmer
15.977
316494AC1-189 GEN
Solar/Wind Harmer
3.39
316129AC1-054 GEN
Solar/Wind Harmer
2.749
971065AG2-659 GEN
Solar/Wind Harmer
15.632
3150351NORNECKC2
Adder
2.751
961671AG1-007 GEN
Solar/Wind Harmer
0.392
3146083TARBORO
Solar/Wind Harmer
-0.031
3145493TOT1
Solar/Wind Harmer
0.919
316319Z2-044 C
Solar/Wind Harmer
1.707
3146233WITAKRS
Solar/Wind Harmer
-0.122
3145543BTLEBRO
Solar/Wind Harmer
-0.03
3145543BTLEBRO
Solar/Wind Harmer
-0.024
316359AB2-059 GEN
Solar/Wind Harmer
4.08
3142053HEARTS
Solar/Wind Harmer
0.357
316131AB2-060 GEN
Solar/Wind Harmer
3.207
315785AD2-033 C
Solar/Wind Harmer
6.646
316034AC1-036 C
Solar/Wind Harmer
0.541
970685AG2-442 GEN
Solar/Wind Harmer
25.289
971563AH1-280 GEN
Solar/Wind Harmer
3.596
3144293JTRSVLE
Adder
0.611
3144293JTRSVLE
Adder
0.483
970401AG2-262 GEN
Solar/Wind Harmer
1.865
3146926FARMVIL
Solar/Wind Harmer
-0.016
316337AD2-073 GEN
Solar/Wind Harmer
0.732
316447AC1-158 HLD
Solar/Wind Helper
5.558
316044AC1-158 PL1
Solar/Wind Helper
2.526
316415AF1-147_GEN2
Solar/Wind Helper
1.087
3147666LOUISA
Solar/Wind Helper
1.162
316192AB2-158 GEN
Solar/Wind Helper
1.911
23777901MDS_W4-102
Solar/Wind Helper
0.153
237001AB1-127_GEN
Solar/Wind Helper
0.388
208835TUHI V3-051
Solar/Wind Helper
0.022
235063AE1-101 C2
Solar/Wind Helper
1.435
205916AD1-020 GEN
Solar/Wind Helper
1.658
233918AB1-142 GEN
Solar/Wind Helper
0.49
233944AB2-135 GEN
Solar/Wind Helper
0.575
205932AD2-116_GEN
Solar/Wind Helper
0.495
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.2
233998TM1NIN_3.36
Solar/Wind Helper
0.2
232404W1-003 C
Solar/Wind Helper
0.494
232408W1-005 C
Solar/Wind Helper
0.494
238175AF1-290_GEN
Solar/Wind Helper
0.122
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219348LDSOLAR C
Solar/Wind Helper
0.11
970937AG2-583 GEN
Solar/Wind Harmer
16.933
3142296MT RD221
50/50
1.308
3150691DARBY 3
50/50
29.065
3150701DARBY 4
50/50
28.997
3150681DARBY 2
50/50
28.964
3150671DARBY 1
50/50
28.93
3142366NRTHEST
50/50
1.315
3150621CHESTS7
50/50
1.097
316312AB1-027
Solar/Wind Harmer
1.468
315976AC1-164 GENA
Solar/Wind Harmer
9.874
316169AC1-164_GENC
Solar/Wind Harmer
8.531
3142946ENON
Solar/Wind Harmer
-0.004
316294AC1-161 GEN
Solar/Wind Harmer
13.425
316033AB2-134 GEN
Solar/Wind Harmer
13.275
944641AF1-129 GEN
Adder
173.913
316240AF1-291 C
Solar/Wind Harmer
1.228
3150991CHESPKB
Adder
3.796
3150991CHESPKB
Adder
3.705
316185AD1-033 GEN
Solar/Wind Harmer
4.27
3145506HICKORY
Solar/Wind Harmer
-0.161
3145506HICKORY
Solar/Wind Harmer
-0.097
3145506HICKORY
Solar/Wind Harmer
-0.024
316339AD2-160 GEN
Solar/Wind Harmer
2.711
316388AE2-253 GEN
Solar/Wind Harmer
2.711
3137176SLIGO L2192
Solar/Wind Harmer
-0.159
3146456SLIGO L269
Solar/Wind Harmer
4.746
966871AG1-558 GEN
Solar/Wind Harmer
1.207
966871AG1-558 GEN
Solar/Wind Harmer
0.413
3130086AYDLETT
Solar/Wind Harmer
-0.16
316083AB2-161 GEN
Solar/Wind Harmer
6.477
316349AD2-085 GEN
Solar/Wind Harmer
3.534
3143526WINTERP
Solar/Wind Harmer
-0.206
315835AF2-110_GEN
Solar/Wind Harmer
4.966
3146386ELIZ CT
Solar/Wind Harmer
-0.04
316431W1029_GEN1
Solar/Wind Harmer
7.108
316433W1029_GEN2
Solar/Wind Harmer
7.108
316435W1029_GEN3
Solar/Wind Harmer
7.108
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
316441AF1-014 GEN
Solar/Wind Harmer
2.63
3146626S HERTFORD
Solar/Wind Harmer
-0.039
3146626S HERTFORD
Solar/Wind Harmer
-0.039
315666AE1-190 GEN
Solar/Wind Harmer
1.166
971223AH1-071 GEN
Solar/Wind Harmer
4.82
316156AD2-030 GEN
Solar/Wind Harmer
1.024
315742AE1-103 GEN
Solar/Wind Harmer
9.021
3146376EDENTON
Solar/Wind Harmer
1.127
3146376EDENTON
Solar/Wind Harmer
1.127
3144356SAPONY
Solar/Wind Harmer
1.303
316315AB2-025 C
Solar/Wind Harmer
1.005
315614AA2-178 GEN
Solar/Wind Harmer
3.987
972193AH1-681 GEN
Adder
7.355
316065AD1-022 GEN
Solar/Wind Harmer
17.966
972185AH1-677 GEN
Adder
17.892
972187AH1-678 GEN
Adder
8.984
3145893MURPHYS
Solar/Wind Harmer
0.989
3145893MURPHYS
Solar/Wind Harmer
-0.064
3146173TUNIS
Solar/Wind Harmer
-0.035
3146173TUNIS
Solar/Wind Harmer
-0.035
316365GEN2_N
Solar/Wind Harmer
2.35
316140AB2-099
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
32.658
316487AF1-042 GEN
Solar/Wind Harmer
4.531
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
4.854
313506AB2-031 GEN
Solar/Wind Harmer
2.703
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145783HORNRTN
Solar/Wind Harmer
3.948
3145783HORNRTN
Solar/Wind Harmer
3.158
3145783HORNRTN
Solar/Wind Harmer
0.987
3145783HORNRTN
Solar/Wind Harmer
0.395
3145933PARMELE
Solar/Wind Harmer
-0.065
3145933PARMELE
Solar/Wind Harmer
-0.033
970099AG2-077 GEN
Solar/Wind Harmer
40.898
316313AB2-026
Solar/Wind Harmer
0.876
316005AA1-067
Solar/Wind Harmer
0.648
315724AD1-057 GEN
Solar/Wind Harmer
6.196
3150341NORNECKC1
Adder
2.89
3150341NORNECKC1
Adder
2.866
316336AC2-165 C
Solar/Wind Harmer
19.356
3145493TOT1
Solar/Wind Harmer
0.479
3145453TOT5
Solar/Wind Harmer
0.288
3145603CNETO
Solar/Wind Harmer
0.192
961601AG1-000A GEN
Solar/Wind Harmer
11.934
316049AB1-081 GEN
Solar/Wind Harmer
3.265
316263AC1-034 GEN
Solar/Wind Harmer
14.222
315687AD1-152 GEN
Solar/Wind Harmer
3.62
313527AB2-043 GEN
Solar/Wind Harmer
4.847
316237AB2-079_GEN
Solar/Wind Harmer
0.896
970301AG2-198 GEN
Solar/Wind Harmer
14.719
970323AG2-213 GEN
Solar/Wind Harmer
14.636
972189AH1-679 GEN
Adder
4.346
962561AG1-105 GEN
Solar/Wind Harmer
16.185
958211AF2-115 GEN
Solar/Wind Harmer
4.495
3144293JTRSVLE
Adder
0.611
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
6.105
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.928
316248AF1-058 C
Solar/Wind Harmer
0.832
316045AC1-158 PL2
Solar/Wind Helper
8.083
316450AC1-158 RIC
Solar/Wind Helper
0.674
316006AB2-029 C
Solar/Wind Helper
0.165
316411AF1-147_GEN1
Solar/Wind Helper
1.087
223401AF1-299 GEN
Solar/Wind Helper
0.396
223402AF1-300 C
Solar/Wind Helper
0.396
237006AB1-125 GEN
Solar/Wind Helper
0.121
238221AF1-254 C O1
Solar/Wind Helper
0.24
235020AA1-095 C
Solar/Wind Helper
0.045
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.435
233982AB2-133 GEN
Solar/Wind Helper
0.35
233930AB2-032 GEN
Solar/Wind Helper
0.371
232436AB1-176 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.113
233946AB2-136 GEN
Solar/Wind Helper
0.554
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.937
232410W1-006 C
Solar/Wind Helper
0.494
232428Y3-058 C
Solar/Wind Helper
0.33
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.227
233954AC2-188 GEN
Solar/Wind Helper
0.227
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.016
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.145
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.077
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
CPLELTFEXP_CPLE->PJM
CLTF
17.688
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.076
LAGNLTFEXP_LAGN->PJM
CLTF
14.58
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.933
TVALTFEXP_TVA->PJM
CLTF
7.381
NYPJM->LTFIMP_NY
CLTF
4.665
LGEELTFEXP_LGEE->PJM
CLTF
2.997
WECLTFEXP_WEC->PJM
CLTF
1.516
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.201
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.678
MECLTFEXP_MEC->PJM
CLTF
7.796
SIGELTFEXP_SIGE->PJM
CLTF
0.241

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.85 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:7358.57
MW Contribution:
220.21
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
2.387
3151161SURRY 1
50/50
14.895
3142416OLDCHRC
Solar/Wind Harmer
4.403
316075AC2-137 C
Solar/Wind Harmer
1.165
970293AG2-193 GEN
Solar/Wind Harmer
5.379
3142946ENON
Solar/Wind Harmer
-0.014
3143096IRON208
Adder
1.568
3143096IRON208
Adder
1.537
3150921YORKTN3
Adder
9.342
3144216WINCHST
Adder
1.4
970133AG2-095 GEN
Solar/Wind Harmer
4.659
316458AB2-190 GEN2
Solar/Wind Harmer
4.168
315778AD1-151 GEN
Solar/Wind Harmer
36.726
961611AG1-000B GEN
Solar/Wind Harmer
8.662
3151171GRAVELC
Adder
5.115
3150861SPRUNCD
Adder
1.68
3145336SMITFLD
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
185.404
944601AF1-125 GEN
Solar/Wind Harmer
182.511
3151101ELIZAR3
Adder
33.658
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142956BIRDNECK
Solar/Wind Harmer
2.18
316017AA1-139 ULT1
Solar/Wind Harmer
3.25
3142433PROV 92
Adder
0.695
3142433PROV 92
Adder
0.695
3146456SLIGO L269
Solar/Wind Harmer
-0.04
971153AH1-033 GEN
Solar/Wind Harmer
4.65
316473AC1-191 GEN
Solar/Wind Harmer
4.32
316305AF2-043 C
Solar/Wind Harmer
1.204
316246AF1-032 C
Solar/Wind Harmer
0.808
315813AE1-149 C
Solar/Wind Harmer
25.011
970657AG2-426 GEN
Solar/Wind Harmer
8.064
316320Y1-086
Solar/Wind Harmer
2.326
316321Z2-027
Solar/Wind Harmer
1.063
3141766HARMONY
Solar/Wind Harmer
3.485
3146516WINFALL
Solar/Wind Harmer
-0.039
3141843SHACKLE
Adder
1.774
316203AE2-005 GEN
Solar/Wind Harmer
16.448
3146626S HERTFORD
Solar/Wind Harmer
-0.039
3145273HOLLAND
Solar/Wind Harmer
-0.029
3141873WAN 176
Solar/Wind Harmer
4.565
3146376EDENTON
Solar/Wind Harmer
-0.038
944011AF1-069 GEN
Solar/Wind Harmer
21.546
315735AD1-075 GEN1
Solar/Wind Harmer
3.653
972255AH1-712 GEN
Adder
164.612
3156081AA2-088 GEN
Solar/Wind Harmer
11.655
3146206CASHIE
Solar/Wind Harmer
-0.036
3145893MURPHYS
Solar/Wind Harmer
0.247
3145893MURPHYS
Solar/Wind Harmer
-0.035
3146173TUNIS
Solar/Wind Harmer
-0.035
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
316484AD2-074 GEN
Solar/Wind Harmer
8.659
961951AG1-038 GEN
Solar/Wind Harmer
4.531
970917AG2-570 GEN
Solar/Wind Harmer
85.84
316317KELFORD C
Solar/Wind Harmer
1.575
3145823KELFORD
Solar/Wind Harmer
-0.034
966621AG1-532 GEN
Solar/Wind Harmer
0.69
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
316011AB1-132 GEN
Solar/Wind Harmer
7.052
316181AB2-040 GEN
Solar/Wind Harmer
4.696
316190AA2-174 GEN
Solar/Wind Harmer
0.413
3145796HORNRTN
Solar/Wind Harmer
-0.132
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145933PARMELE
Solar/Wind Harmer
-0.033
3147043LAWRENC
Solar/Wind Harmer
-0.019
316212AC1-099_GEN
Solar/Wind Harmer
2.841
3143336POWHATN
Solar/Wind Harmer
3.285
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315722AD1-056 GEN
Solar/Wind Harmer
11.266
316478AD1-087 GEN
Solar/Wind Harmer
2.731
316420AA1-050 GEN
Solar/Wind Harmer
3.556
316077AC2-138 C
Solar/Wind Harmer
0.652
3150351NORNECKC2
Adder
2.797
3146073TAR RVR
Solar/Wind Harmer
-0.031
3146083TARBORO
Solar/Wind Harmer
-0.031
3146233WITAKRS
Solar/Wind Harmer
0.647
3146233WITAKRS
Solar/Wind Harmer
-0.021
3138543CONSLDL
Solar/Wind Harmer
-0.02
961601AG1-000A GEN
Solar/Wind Harmer
12.085
3145543BTLEBRO
Solar/Wind Harmer
-0.03
3145543BTLEBRO
Solar/Wind Harmer
-0.03
964241AG1-285 GEN
Solar/Wind Harmer
23.162
970257AG2-171 GEN
Solar/Wind Harmer
10.977
971775AH1-396 GEN
Solar/Wind Harmer
2.065
959311AF2-222 GEN
Solar/Wind Harmer
30.475
3144293JTRSVLE
Adder
0.611
3147133PAMPLIN
Solar/Wind Harmer
-0.089
942461AE2-259 GEN
Solar/Wind Harmer
4.227
971781AH1-399 GEN
Solar/Wind Harmer
1.729
3146926FARMVIL
Solar/Wind Harmer
-0.016
3151861LOWMORA
Adder
1.611
3141196NOKESVL
Solar/Wind Helper
1.395
227287AC2-120 GEN
Solar/Wind Helper
0.435
226910AB2-157 C
Solar/Wind Helper
0.018
3147666LOUISA
Solar/Wind Helper
0.669
23777801MSM_W1-116
Solar/Wind Helper
0.111
3132273ORANGE
Solar/Wind Helper
0.051
208835TUHI V3-051
Solar/Wind Helper
0.022
237002AB1-128_GEN
Solar/Wind Helper
0.387
237038AE2-054 C
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.384
237085AD2-009_GEN
Solar/Wind Helper
1.4
233935AB2-179 C
Solar/Wind Helper
1.238
233933AB2-153 GEN
Solar/Wind Helper
0.227
232422X3-066 FULL
Solar/Wind Helper
0.111
233987AB2-037 GEN
Solar/Wind Helper
2.284
232417X3-008 C
Solar/Wind Helper
0.227
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.733
233997TMININ_4.2
Solar/Wind Helper
0.2
232406W1-004 FULL
Solar/Wind Helper
0.494
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.124
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
972263AH1-716 GEN
50/50
220.214
3150631CHESTG8
50/50
2.349
316382AG1-145 C
Solar/Wind Harmer
1.277
316159AE1-175 C
Solar/Wind Harmer
1.137
315697AD1-025 GEN
Solar/Wind Harmer
8.32
3151201GRAVEL4
Adder
26.614
3151221GRAVEL6
Adder
26.584
3151191GRAVEL3
Adder
26.277
3151211GRAVEL5
Adder
26.277
971445AH1-216 GEN
Solar/Wind Harmer
25.349
971285AH1-108 GEN
Adder
2.748
316236AE1-162_GEN
Solar/Wind Harmer
1.231
3151081ELIZAR1
Adder
33.232
3151091ELIZAR2
Adder
32.655
316316AC1-027 C
Solar/Wind Harmer
1.245
315839AE2-212 C
Solar/Wind Harmer
1.212
316018AA1-139 ULT2
Solar/Wind Harmer
3.441
957871AF2-081 GEN
Solar/Wind Harmer
20.137
3142433PROV 92
Adder
0.695
3142433PROV 92
Adder
0.695
957831AF2-077 GEN
Solar/Wind Harmer
1.208
3138283WHITEMARSH
Solar/Wind Harmer
0.062
3146406KITTY HAWK
Solar/Wind Harmer
0.033
970657AG2-426 GEN
Solar/Wind Harmer
2.517
315833AF1-017_GEN
Solar/Wind Harmer
7.559
316311AC2-079 GEN
Solar/Wind Harmer
20.077
316233AE1-074 FULL
Solar/Wind Harmer
1.07
3143873LANEXA
Solar/Wind Harmer
-0.024
971281AH1-106 GEN
Solar/Wind Harmer
6.461
971283AH1-107 GEN
Solar/Wind Harmer
6.461
313526AB2-022
Solar/Wind Harmer
1.069
3146486SUNBURY
Solar/Wind Harmer
-0.039
3146486SUNBURY
Solar/Wind Harmer
-0.039
3143316POE
Solar/Wind Harmer
-0.156
3146396TANGLEW
Solar/Wind Harmer
0.727
3145176PASQUOTANK
Solar/Wind Harmer
-0.024
316059AD1-063 C
Solar/Wind Harmer
0.883
957601AF2-054 GEN
Solar/Wind Harmer
1.151
3141873WAN 176
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
9.432
3130156CHOWAN
Solar/Wind Harmer
-0.038
3130156CHOWAN
Solar/Wind Harmer
-0.038
3141913WHIT STONE
Solar/Wind Harmer
-0.037
315814AE2-033 C
Solar/Wind Harmer
34.685
3138133OCRAN
Solar/Wind Harmer
-0.011
970533AG2-339 GEN
Solar/Wind Harmer
24.662
3141783LANCAST
Solar/Wind Harmer
-0.022
3141783LANCAST
Solar/Wind Harmer
-0.014
3130546PLYMOUTH
Solar/Wind Harmer
-0.036
970673AG2-436 GEN
Solar/Wind Harmer
79.486
315732AD1-074 GEN1
Solar/Wind Harmer
7.308
315733AD1-074 GEN2
Solar/Wind Harmer
7.308
3146206CASHIE
Solar/Wind Harmer
-0.036
970601AG2-382 GEN
Solar/Wind Harmer
15.65
971967AH1-528 GEN
Solar/Wind Harmer
66.74
316318V4-068
Solar/Wind Harmer
0.883
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
-0.035
316463AE2-346 GEN
Solar/Wind Harmer
0.564
3145513AHOSKIE
Solar/Wind Harmer
0.305
961941AG1-037 GEN
Solar/Wind Harmer
0.263
3145513AHOSKIE
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.069
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146043SEABORD
Solar/Wind Harmer
-0.034
316174AB2-169 GEN
Solar/Wind Harmer
5.247
946281AF1-292 GEN
Solar/Wind Harmer
0.761
970085AG2-068 GEN
Solar/Wind Harmer
21.223
970581AG2-369 GEN
Solar/Wind Harmer
18.252
315652AC1-086 GEN
Solar/Wind Harmer
37.987
316426AA2-053 GEN
Solar/Wind Harmer
3.393
3137643SOCKMAN
Solar/Wind Harmer
-0.133
3145796HORNRTN
Solar/Wind Harmer
-0.106
3145796HORNRTN
Solar/Wind Harmer
-0.013
3146033SCOT NK
Solar/Wind Harmer
-0.132
316210AC1-098 GEN
Solar/Wind Harmer
5.114
316258AE1-075 C
Solar/Wind Harmer
0.788
316405AF2-144 C
Solar/Wind Harmer
0.832
316274AC1-208 GEN
Solar/Wind Harmer
3.48
3145746EVERETS
Solar/Wind Harmer
-0.127
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
970831AG2-522 GEN
Solar/Wind Harmer
15.837
316486AD2-202 GEN
Solar/Wind Harmer
0.8
957861AF2-080 GEN
Solar/Wind Harmer
13.784
316327AA2-057 GEN
Solar/Wind Harmer
3.168
3141813NORNECK
Solar/Wind Harmer
-0.031
3145573BETHELC
Solar/Wind Harmer
-0.031
3145573BETHELC
Solar/Wind Harmer
-0.031
316238AB2-078_GEN
Solar/Wind Harmer
0.896
316239AB2-077_GEN
Solar/Wind Harmer
0.896
3144303KENBRDG
Solar/Wind Harmer
-0.023
970683AG2-441 GEN
Solar/Wind Harmer
20.491
970681AG2-440 GEN
Solar/Wind Harmer
13.6
946301AF1-294 GEN
Solar/Wind Harmer
7.372
961791AG1-021 GEN
Solar/Wind Harmer
3.596
316468AD1-105 GEN
Solar/Wind Harmer
3.206
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
8.959
3151881LOWMORC
Adder
1.598
3151881LOWMORC
Adder
1.573
3151861LOWMORA
Adder
1.548
316164AC1-076 GEN
Solar/Wind Helper
1.84
315651AD1-115 GEN
Solar/Wind Helper
1.14
226929AD2-058 GEN
Solar/Wind Helper
0.128
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
23779801AA1-109
Solar/Wind Helper
0.186
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.161
205917AD1-020 ES
Solar/Wind Helper
0.357
233915AB1-141 GEN
Solar/Wind Helper
0.49
205943AE1-185 GEN
Solar/Wind Helper
0.495
205956AE1-196_GEN
Solar/Wind Helper
0.495
233940AF2-379 C
Solar/Wind Helper
0.06
233901CHERRYDALE C
Solar/Wind Helper
0.227
232432Z2-076 GEN
Solar/Wind Helper
0.065
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219615MILLCREEK C
Solar/Wind Helper
0.026
3152331SURRY 2
50/50
15.651
3150641CHESTS8
50/50
1.21
3142416OLDCHRC
Solar/Wind Harmer
-0.113
3142416OLDCHRC
Solar/Wind Harmer
-0.043
315975AC1-164 GENB
Solar/Wind Harmer
0.292
944631AF1-128 GEN
Adder
179.229
3143096IRON208
Adder
1.568
3138126ROCKLANDING
Solar/Wind Harmer
0.128
971317AH1-138 GEN
Solar/Wind Harmer
5.208
315773AC2-141 GEN
Solar/Wind Harmer
17.37
3142543TWELFTH
Solar/Wind Harmer
-0.004
316132AB2-190 GEN1
Solar/Wind Harmer
4.168
971069AG2-661 GEN
Solar/Wind Harmer
6.529
316369SG1_INVT
Solar/Wind Harmer
7.352
961611AG1-000B GEN
Solar/Wind Harmer
20.302
3151171GRAVELC
Adder
3.89
3150851SPRUNCC
Adder
1.68
3145336SMITFLD
Solar/Wind Harmer
-0.163
944591AF1-124 GEN
Solar/Wind Harmer
186.072
316375AC2-012 GEN
Solar/Wind Harmer
14.08
316036AC1-147 C
Solar/Wind Harmer
1.096
3150981CHESPKA
Adder
4.525
315671AE2-027_GEN
Solar/Wind Harmer
7.317
316072AD1-144
Solar/Wind Harmer
0.814
3142433PROV 92
Solar/Wind Harmer
-0.16
3142433PROV 92
Adder
0.695
3142433PROV 92
Adder
0.695
3146456SLIGO L269
Solar/Wind Harmer
-0.04
319010AE1-072 C
Solar/Wind Harmer
8.103
316381AD1-082 GEN
Solar/Wind Harmer
3.652
3143526WINTERP
Solar/Wind Harmer
-0.206
316093AE2-104_GEN
Solar/Wind Harmer
11.551
316314AB2-024 C
Solar/Wind Harmer
3.382
3141766HARMONY
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.126
3146516WINFALL
Solar/Wind Harmer
-0.039
939411AE1-173 GEN
Solar/Wind Harmer
195.127
971777AH1-397 GEN
Solar/Wind Harmer
4.553
315662AE1-191 GEN
Solar/Wind Harmer
4.664
316280AD1-041 GEN
Solar/Wind Harmer
2.915
3143226MDLTHAN
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
36.103
315611Z1-036_GEN2
Solar/Wind Harmer
9.432
3130156CHOWAN
Solar/Wind Harmer
-0.038
3138133OCRAN
Solar/Wind Harmer
-0.022
315816AE2-034 GEN
Solar/Wind Harmer
2.99
3145663CRESWEL
Solar/Wind Harmer
-0.103
971163AH1-040 GEN
Solar/Wind Harmer
34.736
941031AE2-094 GEN
Solar/Wind Harmer
68.765
315737AD1-076 GEN
Solar/Wind Harmer
6.87
972277AH1-723 GEN
Adder
191.822
3146206CASHIE
Solar/Wind Harmer
-0.036
971547AH1-271 GEN
Solar/Wind Harmer
8.943
3145893MURPHYS
Solar/Wind Harmer
-0.141
3145893MURPHYS
Solar/Wind Harmer
1.051
3156021HOLLOMANSOL
Solar/Wind Harmer
4.722
3146173TUNIS
Solar/Wind Harmer
-0.035
316023GEN1_S
Solar/Wind Harmer
2.35
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
315607AA1-063A GEN
Solar/Wind Harmer
3.46
970919AG2-571 GEN
Solar/Wind Harmer
10.866
3145823KELFORD
Solar/Wind Harmer
-0.034
960081AF2-299 GEN
Solar/Wind Harmer
3.823
970087AG2-069 GEN
Solar/Wind Harmer
31.835
316087AB2-174 GEN
Solar/Wind Harmer
4.814
962861AG1-135 GEN
Solar/Wind Harmer
12.564
3145796HORNRTN
Solar/Wind Harmer
-0.109
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145783HORNRTN
Solar/Wind Harmer
-0.033
316404AE1-155 C
Solar/Wind Harmer
6.334
958261AF2-120 GEN
Solar/Wind Harmer
12.858
3146293MARTNCO
Solar/Wind Harmer
0.203
3147043LAWRENC
Adder
2.635
957481AF2-042 GEN
Solar/Wind Harmer
102.243
3143336POWHATN
Solar/Wind Harmer
3.865
964211AG1-282 GEN
Solar/Wind Harmer
0.966
3141726DUNNSVL
Solar/Wind Harmer
-0.128
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315693AD1-088 GEN
Solar/Wind Harmer
15.976
316494AC1-189 GEN
Solar/Wind Harmer
3.39
316129AC1-054 GEN
Solar/Wind Harmer
2.749
971065AG2-659 GEN
Solar/Wind Harmer
15.631
3150351NORNECKC2
Adder
2.751
961671AG1-007 GEN
Solar/Wind Harmer
0.392
3146083TARBORO
Solar/Wind Harmer
-0.031
3145493TOT1
Solar/Wind Harmer
0.919
316319Z2-044 C
Solar/Wind Harmer
1.707
3146233WITAKRS
Solar/Wind Harmer
-0.122
3145543BTLEBRO
Solar/Wind Harmer
-0.03
3145543BTLEBRO
Solar/Wind Harmer
-0.024
316359AB2-059 GEN
Solar/Wind Harmer
4.08
3142053HEARTS
Solar/Wind Harmer
0.357
316131AB2-060 GEN
Solar/Wind Harmer
3.207
315785AD2-033 C
Solar/Wind Harmer
6.645
316034AC1-036 C
Solar/Wind Harmer
0.541
970685AG2-442 GEN
Solar/Wind Harmer
25.289
971563AH1-280 GEN
Solar/Wind Harmer
3.596
3144293JTRSVLE
Adder
0.611
3144293JTRSVLE
Adder
0.483
970401AG2-262 GEN
Solar/Wind Harmer
1.865
3146926FARMVIL
Solar/Wind Harmer
-0.016
316337AD2-073 GEN
Solar/Wind Harmer
0.732
316447AC1-158 HLD
Solar/Wind Helper
5.558
316044AC1-158 PL1
Solar/Wind Helper
2.526
316415AF1-147_GEN2
Solar/Wind Helper
1.087
3147666LOUISA
Solar/Wind Helper
1.163
316192AB2-158 GEN
Solar/Wind Helper
1.913
23777901MDS_W4-102
Solar/Wind Helper
0.153
237001AB1-127_GEN
Solar/Wind Helper
0.388
208835TUHI V3-051
Solar/Wind Helper
0.022
235063AE1-101 C2
Solar/Wind Helper
1.435
205916AD1-020 GEN
Solar/Wind Helper
1.658
233918AB1-142 GEN
Solar/Wind Helper
0.49
233944AB2-135 GEN
Solar/Wind Helper
0.575
205932AD2-116_GEN
Solar/Wind Helper
0.495
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.2
233998TM1NIN_3.36
Solar/Wind Helper
0.2
232404W1-003 C
Solar/Wind Helper
0.494
232408W1-005 C
Solar/Wind Helper
0.494
238175AF1-290_GEN
Solar/Wind Helper
0.122
228729W2-030 C
Solar/Wind Helper
0.107
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219348LDSOLAR C
Solar/Wind Helper
0.11
970937AG2-583 GEN
Solar/Wind Harmer
16.932
3142296MT RD221
50/50
1.308
3150691DARBY 3
50/50
29.065
3150701DARBY 4
50/50
28.998
3150681DARBY 2
50/50
28.964
3150671DARBY 1
50/50
28.93
3142366NRTHEST
50/50
1.315
3150621CHESTS7
50/50
1.097
316312AB1-027
Solar/Wind Harmer
1.468
315976AC1-164 GENA
Solar/Wind Harmer
9.874
316169AC1-164_GENC
Solar/Wind Harmer
8.531
3142946ENON
Solar/Wind Harmer
-0.004
316294AC1-161 GEN
Solar/Wind Harmer
13.425
316033AB2-134 GEN
Solar/Wind Harmer
13.275
944641AF1-129 GEN
Adder
173.913
316240AF1-291 C
Solar/Wind Harmer
1.228
3150991CHESPKB
Adder
3.796
3150991CHESPKB
Adder
3.705
316185AD1-033 GEN
Solar/Wind Harmer
4.27
3145506HICKORY
Solar/Wind Harmer
-0.161
3145506HICKORY
Solar/Wind Harmer
-0.097
3145506HICKORY
Solar/Wind Harmer
-0.024
316339AD2-160 GEN
Solar/Wind Harmer
2.711
316388AE2-253 GEN
Solar/Wind Harmer
2.711
3137176SLIGO L2192
Solar/Wind Harmer
-0.159
3146456SLIGO L269
Solar/Wind Harmer
4.746
966871AG1-558 GEN
Solar/Wind Harmer
1.207
966871AG1-558 GEN
Solar/Wind Harmer
0.413
3130086AYDLETT
Solar/Wind Harmer
-0.16
316083AB2-161 GEN
Solar/Wind Harmer
6.477
316349AD2-085 GEN
Solar/Wind Harmer
3.534
3143526WINTERP
Solar/Wind Harmer
-0.206
315835AF2-110_GEN
Solar/Wind Harmer
4.966
3146386ELIZ CT
Solar/Wind Harmer
-0.04
316431W1029_GEN1
Solar/Wind Harmer
7.108
316433W1029_GEN2
Solar/Wind Harmer
7.108
316435W1029_GEN3
Solar/Wind Harmer
7.108
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
316441AF1-014 GEN
Solar/Wind Harmer
2.63
3146626S HERTFORD
Solar/Wind Harmer
-0.039
3146626S HERTFORD
Solar/Wind Harmer
-0.039
315666AE1-190 GEN
Solar/Wind Harmer
1.166
971223AH1-071 GEN
Solar/Wind Harmer
4.819
316156AD2-030 GEN
Solar/Wind Harmer
1.024
315742AE1-103 GEN
Solar/Wind Harmer
9.021
3146376EDENTON
Solar/Wind Harmer
1.127
3146376EDENTON
Solar/Wind Harmer
1.127
3144356SAPONY
Solar/Wind Harmer
1.303
316315AB2-025 C
Solar/Wind Harmer
1.005
315614AA2-178 GEN
Solar/Wind Harmer
3.987
972193AH1-681 GEN
Adder
7.355
316065AD1-022 GEN
Solar/Wind Harmer
17.966
972185AH1-677 GEN
Adder
17.892
972187AH1-678 GEN
Adder
8.984
3145893MURPHYS
Solar/Wind Harmer
0.989
3145893MURPHYS
Solar/Wind Harmer
-0.064
3146173TUNIS
Solar/Wind Harmer
-0.035
3146173TUNIS
Solar/Wind Harmer
-0.035
316365GEN2_N
Solar/Wind Harmer
2.35
316140AB2-099
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
32.657
316487AF1-042 GEN
Solar/Wind Harmer
4.531
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
4.854
313506AB2-031 GEN
Solar/Wind Harmer
2.703
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145783HORNRTN
Solar/Wind Harmer
3.948
3145783HORNRTN
Solar/Wind Harmer
3.158
3145783HORNRTN
Solar/Wind Harmer
0.987
3145783HORNRTN
Solar/Wind Harmer
0.395
3145933PARMELE
Solar/Wind Harmer
-0.065
3145933PARMELE
Solar/Wind Harmer
-0.033
970099AG2-077 GEN
Solar/Wind Harmer
40.897
316313AB2-026
Solar/Wind Harmer
0.876
316005AA1-067
Solar/Wind Harmer
0.648
315724AD1-057 GEN
Solar/Wind Harmer
6.196
3150341NORNECKC1
Adder
2.89
3150341NORNECKC1
Adder
2.866
316336AC2-165 C
Solar/Wind Harmer
19.355
3145493TOT1
Solar/Wind Harmer
0.479
3145453TOT5
Solar/Wind Harmer
0.288
3145603CNETO
Solar/Wind Harmer
0.192
961601AG1-000A GEN
Solar/Wind Harmer
11.934
316049AB1-081 GEN
Solar/Wind Harmer
3.264
316263AC1-034 GEN
Solar/Wind Harmer
14.222
315687AD1-152 GEN
Solar/Wind Harmer
3.62
313527AB2-043 GEN
Solar/Wind Harmer
4.847
316237AB2-079_GEN
Solar/Wind Harmer
0.896
970301AG2-198 GEN
Solar/Wind Harmer
14.718
970323AG2-213 GEN
Solar/Wind Harmer
14.636
972189AH1-679 GEN
Adder
4.346
962561AG1-105 GEN
Solar/Wind Harmer
16.185
958211AF2-115 GEN
Solar/Wind Harmer
4.495
3144293JTRSVLE
Adder
0.611
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
6.105
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.928
316248AF1-058 C
Solar/Wind Harmer
0.832
316045AC1-158 PL2
Solar/Wind Helper
8.083
316450AC1-158 RIC
Solar/Wind Helper
0.674
316006AB2-029 C
Solar/Wind Helper
0.165
316411AF1-147_GEN1
Solar/Wind Helper
1.087
223401AF1-299 GEN
Solar/Wind Helper
0.396
223402AF1-300 C
Solar/Wind Helper
0.396
237006AB1-125 GEN
Solar/Wind Helper
0.121
238221AF1-254 C O1
Solar/Wind Helper
0.24
235020AA1-095 C
Solar/Wind Helper
0.045
237080AD1-060 GEN
Solar/Wind Helper
0.297
235062AE1-101 C1
Solar/Wind Helper
1.435
233930AB2-032 GEN
Solar/Wind Helper
0.371
233982AB2-133 GEN
Solar/Wind Helper
0.35
232436AB1-176 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.113
233946AB2-136 GEN
Solar/Wind Helper
0.554
234036AF2-325 C
Solar/Wind Helper
0.041
233994AC2-023 GEN
Solar/Wind Helper
0.937
232428Y3-058 C
Solar/Wind Helper
0.33
234015AF2-250 C
Solar/Wind Helper
0.037
232410W1-006 C
Solar/Wind Helper
0.494
233952AC2-187 GEN
Solar/Wind Helper
0.227
233954AC2-188 GEN
Solar/Wind Helper
0.227
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.016
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.059
219912AD2-042 GEN
Solar/Wind Helper
0.145
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219906AC1-017 C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.077
219304NAMERICA C
Solar/Wind Helper
0.127
214067T20SOLAR
Solar/Wind Helper
0.011
219921AF1-264
Solar/Wind Helper
0.049
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
959561AF2-247 GEN
Solar/Wind Helper
0.02
CPLELTFEXP_CPLE->PJM
CLTF
17.688
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.075
LAGNLTFEXP_LAGN->PJM
CLTF
14.58
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.933
TVALTFEXP_TVA->PJM
CLTF
7.381
NYPJM->LTFIMP_NY
CLTF
4.665
LGEELTFEXP_LGEE->PJM
CLTF
2.997
WECLTFEXP_WEC->PJM
CLTF
1.516
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.2
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.677
MECLTFEXP_MEC->PJM
CLTF
7.796
SIGELTFEXP_SIGE->PJM
CLTF
0.241

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.4 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:7336.33
MW Contribution:
219.86
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
219.857
3150631CHESTG8
50/50
2.353
316382AG1-145 C
Solar/Wind Harmer
1.277
316159AE1-175 C
Solar/Wind Harmer
1.136
315697AD1-025 GEN
Solar/Wind Harmer
8.318
971285AH1-108 GEN
Adder
2.761
3151201GRAVEL4
Adder
26.586
3151221GRAVEL6
Adder
26.556
3151191GRAVEL3
Adder
26.25
3151211GRAVEL5
Adder
26.25
971445AH1-216 GEN
Solar/Wind Harmer
25.312
316236AE1-162_GEN
Solar/Wind Harmer
1.229
3151081ELIZAR1
Adder
33.157
3151091ELIZAR2
Adder
32.581
316316AC1-027 C
Solar/Wind Harmer
1.242
315839AE2-212 C
Solar/Wind Harmer
1.212
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
957831AF2-077 GEN
Solar/Wind Harmer
1.208
3138283WHITEMARSH
Solar/Wind Harmer
0.062
316018AA1-139 ULT2
Solar/Wind Harmer
3.433
957871AF2-081 GEN
Solar/Wind Harmer
20.089
316233AE1-074 FULL
Solar/Wind Harmer
1.078
971281AH1-106 GEN
Solar/Wind Harmer
6.514
971283AH1-107 GEN
Solar/Wind Harmer
6.514
3146406KITTY HAWK
Solar/Wind Harmer
0.033
970657AG2-426 GEN
Solar/Wind Harmer
2.513
3143873LANEXA
Solar/Wind Harmer
-0.024
315833AF1-017_GEN
Solar/Wind Harmer
7.544
316311AC2-079 GEN
Solar/Wind Harmer
20.038
313526AB2-022
Solar/Wind Harmer
1.066
3143316POE
Solar/Wind Harmer
-0.155
3146486SUNBURY
Solar/Wind Harmer
-0.039
3146486SUNBURY
Solar/Wind Harmer
-0.039
3146396TANGLEW
Solar/Wind Harmer
0.725
3145176PASQUOTANK
Solar/Wind Harmer
-0.024
316059AD1-063 C
Solar/Wind Harmer
0.883
957601AF2-054 GEN
Solar/Wind Harmer
1.151
3141873WAN 176
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
9.408
3130156CHOWAN
Solar/Wind Harmer
-0.038
3130156CHOWAN
Solar/Wind Harmer
-0.038
3141913WHIT STONE
Solar/Wind Harmer
-0.037
315814AE2-033 C
Solar/Wind Harmer
34.582
3138133OCRAN
Solar/Wind Harmer
-0.011
970533AG2-339 GEN
Solar/Wind Harmer
24.536
3141783LANCAST
Solar/Wind Harmer
-0.022
3141783LANCAST
Solar/Wind Harmer
-0.014
3130546PLYMOUTH
Solar/Wind Harmer
-0.036
970673AG2-436 GEN
Solar/Wind Harmer
79.079
315732AD1-074 GEN1
Solar/Wind Harmer
7.288
315733AD1-074 GEN2
Solar/Wind Harmer
7.288
3146206CASHIE
Solar/Wind Harmer
-0.036
970601AG2-382 GEN
Solar/Wind Harmer
15.606
316318V4-068
Solar/Wind Harmer
0.88
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
-0.035
971967AH1-528 GEN
Solar/Wind Harmer
66.404
316463AE2-346 GEN
Solar/Wind Harmer
0.562
3145513AHOSKIE
Solar/Wind Harmer
0.304
961941AG1-037 GEN
Solar/Wind Harmer
0.262
3145513AHOSKIE
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.069
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146043SEABORD
Solar/Wind Harmer
-0.034
316174AB2-169 GEN
Solar/Wind Harmer
5.232
946281AF1-292 GEN
Solar/Wind Harmer
0.759
970085AG2-068 GEN
Solar/Wind Harmer
21.118
970581AG2-369 GEN
Solar/Wind Harmer
18.161
315652AC1-086 GEN
Solar/Wind Harmer
37.867
316426AA2-053 GEN
Solar/Wind Harmer
3.382
3137643SOCKMAN
Solar/Wind Harmer
-0.133
3146033SCOT NK
Solar/Wind Harmer
-0.132
3145796HORNRTN
Solar/Wind Harmer
-0.105
3145796HORNRTN
Solar/Wind Harmer
-0.013
316258AE1-075 C
Solar/Wind Harmer
0.794
316405AF2-144 C
Solar/Wind Harmer
0.838
316210AC1-098 GEN
Solar/Wind Harmer
5.097
316274AC1-208 GEN
Solar/Wind Harmer
3.469
3145746EVERETS
Solar/Wind Harmer
-0.127
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
970831AG2-522 GEN
Solar/Wind Harmer
15.779
316486AD2-202 GEN
Solar/Wind Harmer
0.796
957861AF2-080 GEN
Solar/Wind Harmer
13.738
316327AA2-057 GEN
Solar/Wind Harmer
3.157
3141813NORNECK
Solar/Wind Harmer
-0.031
3145573BETHELC
Solar/Wind Harmer
-0.031
3145573BETHELC
Solar/Wind Harmer
-0.031
316238AB2-078_GEN
Solar/Wind Harmer
0.893
316239AB2-077_GEN
Solar/Wind Harmer
0.893
3144303KENBRDG
Solar/Wind Harmer
-0.023
970683AG2-441 GEN
Solar/Wind Harmer
20.413
970681AG2-440 GEN
Solar/Wind Harmer
13.548
946301AF1-294 GEN
Solar/Wind Harmer
7.344
961791AG1-021 GEN
Solar/Wind Harmer
3.583
316468AD1-105 GEN
Solar/Wind Harmer
3.218
3147173SINAI
Solar/Wind Harmer
-0.027
3147243WELCO
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
8.939
3151881LOWMORC
Adder
1.592
3151881LOWMORC
Adder
1.567
3151861LOWMORA
Adder
1.542
316164AC1-076 GEN
Solar/Wind Helper
1.852
315651AD1-115 GEN
Solar/Wind Helper
1.153
226929AD2-058 GEN
Solar/Wind Helper
0.127
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
23779801AA1-109
Solar/Wind Helper
0.185
237030AB1-096 C
Solar/Wind Helper
0.065
237025AB1-124 C
Solar/Wind Helper
0.161
205917AD1-020 ES
Solar/Wind Helper
0.355
233915AB1-141 GEN
Solar/Wind Helper
0.488
205943AE1-185 GEN
Solar/Wind Helper
0.493
205956AE1-196_GEN
Solar/Wind Helper
0.493
233901CHERRYDALE C
Solar/Wind Helper
0.226
233940AF2-379 C
Solar/Wind Helper
0.06
232432Z2-076 GEN
Solar/Wind Helper
0.065
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
230407AD2-065 C
Solar/Wind Helper
0.039
227927V4-067C
Solar/Wind Helper
0.01
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219615MILLCREEK C
Solar/Wind Helper
0.026
3152331SURRY 2
50/50
15.624
3150641CHESTS8
50/50
1.212
3142416OLDCHRC
Solar/Wind Harmer
-0.113
3142416OLDCHRC
Solar/Wind Harmer
-0.043
315975AC1-164 GENB
Solar/Wind Harmer
0.292
944631AF1-128 GEN
Adder
179.5
3143096IRON208
Adder
1.572
3138126ROCKLANDING
Solar/Wind Harmer
0.128
971317AH1-138 GEN
Solar/Wind Harmer
5.205
3142543TWELFTH
Solar/Wind Harmer
-0.004
315773AC2-141 GEN
Solar/Wind Harmer
17.328
316132AB2-190 GEN1
Solar/Wind Harmer
4.168
971069AG2-661 GEN
Solar/Wind Harmer
6.528
316369SG1_INVT
Solar/Wind Harmer
7.35
3150851SPRUNCC
Adder
1.687
961611AG1-000B GEN
Solar/Wind Harmer
20.286
3151171GRAVELC
Adder
3.885
3145336SMITFLD
Solar/Wind Harmer
-0.163
944591AF1-124 GEN
Solar/Wind Harmer
185.62
316375AC2-012 GEN
Solar/Wind Harmer
14.049
316036AC1-147 C
Solar/Wind Harmer
1.093
3150981CHESPKA
Adder
4.514
315671AE2-027_GEN
Solar/Wind Harmer
7.319
316072AD1-144
Solar/Wind Harmer
0.813
3142433PROV 92
Solar/Wind Harmer
-0.16
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
-0.04
3143526WINTERP
Solar/Wind Harmer
-0.207
319010AE1-072 C
Solar/Wind Harmer
8.084
316381AD1-082 GEN
Solar/Wind Harmer
3.647
316093AE2-104_GEN
Solar/Wind Harmer
11.525
316314AB2-024 C
Solar/Wind Harmer
3.384
3141766HARMONY
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.126
3146516WINFALL
Solar/Wind Harmer
-0.039
971777AH1-397 GEN
Solar/Wind Harmer
4.556
3143226MDLTHAN
Solar/Wind Harmer
-0.039
939411AE1-173 GEN
Solar/Wind Harmer
194.333
315662AE1-191 GEN
Solar/Wind Harmer
4.666
316280AD1-041 GEN
Solar/Wind Harmer
2.916
940641AE2-051 GEN
Solar/Wind Harmer
35.935
315611Z1-036_GEN2
Solar/Wind Harmer
9.408
3130156CHOWAN
Solar/Wind Harmer
-0.038
3138133OCRAN
Solar/Wind Harmer
-0.022
315816AE2-034 GEN
Solar/Wind Harmer
2.982
3145663CRESWEL
Solar/Wind Harmer
-0.103
971163AH1-040 GEN
Solar/Wind Harmer
34.644
941031AE2-094 GEN
Solar/Wind Harmer
68.411
972277AH1-723 GEN
Adder
191.818
315737AD1-076 GEN
Solar/Wind Harmer
6.851
3146206CASHIE
Solar/Wind Harmer
-0.036
971547AH1-271 GEN
Solar/Wind Harmer
8.918
3145893MURPHYS
Solar/Wind Harmer
-0.141
3145893MURPHYS
Solar/Wind Harmer
1.048
3156021HOLLOMANSOL
Solar/Wind Harmer
4.709
3146173TUNIS
Solar/Wind Harmer
-0.035
316023GEN1_S
Solar/Wind Harmer
2.343
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
315607AA1-063A GEN
Solar/Wind Harmer
3.449
970919AG2-571 GEN
Solar/Wind Harmer
10.811
3145823KELFORD
Solar/Wind Harmer
-0.034
960081AF2-299 GEN
Solar/Wind Harmer
3.811
970087AG2-069 GEN
Solar/Wind Harmer
31.677
316087AB2-174 GEN
Solar/Wind Harmer
4.798
962861AG1-135 GEN
Solar/Wind Harmer
12.575
316404AE1-155 C
Solar/Wind Harmer
6.34
958261AF2-120 GEN
Solar/Wind Harmer
12.869
3145796HORNRTN
Solar/Wind Harmer
-0.109
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145783HORNRTN
Solar/Wind Harmer
-0.033
3143336POWHATN
Solar/Wind Harmer
3.892
3146293MARTNCO
Solar/Wind Harmer
0.203
3147043LAWRENC
Adder
2.626
957481AF2-042 GEN
Solar/Wind Harmer
101.759
964211AG1-282 GEN
Solar/Wind Harmer
0.967
3141726DUNNSVL
Solar/Wind Harmer
-0.128
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315693AD1-088 GEN
Solar/Wind Harmer
15.903
316494AC1-189 GEN
Solar/Wind Harmer
3.379
316129AC1-054 GEN
Solar/Wind Harmer
2.738
971065AG2-659 GEN
Solar/Wind Harmer
15.572
3150351NORNECKC2
Adder
2.754
961671AG1-007 GEN
Solar/Wind Harmer
0.39
3146083TARBORO
Solar/Wind Harmer
-0.031
3145493TOT1
Solar/Wind Harmer
0.916
316319Z2-044 C
Solar/Wind Harmer
1.701
3146233WITAKRS
Solar/Wind Harmer
-0.122
3145543BTLEBRO
Solar/Wind Harmer
-0.03
3145543BTLEBRO
Solar/Wind Harmer
-0.024
316359AB2-059 GEN
Solar/Wind Harmer
4.066
3142053HEARTS
Solar/Wind Harmer
0.355
316131AB2-060 GEN
Solar/Wind Harmer
3.195
315785AD2-033 C
Solar/Wind Harmer
6.62
316034AC1-036 C
Solar/Wind Harmer
0.539
970685AG2-442 GEN
Solar/Wind Harmer
25.193
971563AH1-280 GEN
Solar/Wind Harmer
3.583
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.481
970401AG2-262 GEN
Solar/Wind Harmer
1.858
3146926FARMVIL
Solar/Wind Harmer
-0.016
316337AD2-073 GEN
Solar/Wind Harmer
0.733
316447AC1-158 HLD
Solar/Wind Helper
5.527
316044AC1-158 PL1
Solar/Wind Helper
2.512
316415AF1-147_GEN2
Solar/Wind Helper
1.084
3147666LOUISA
Solar/Wind Helper
1.284
316192AB2-158 GEN
Solar/Wind Helper
2.112
23777901MDS_W4-102
Solar/Wind Helper
0.153
237001AB1-127_GEN
Solar/Wind Helper
0.387
208835TUHI V3-051
Solar/Wind Helper
0.021
235063AE1-101 C2
Solar/Wind Helper
1.43
205916AD1-020 GEN
Solar/Wind Helper
1.653
233918AB1-142 GEN
Solar/Wind Helper
0.488
233944AB2-135 GEN
Solar/Wind Helper
0.573
205932AD2-116_GEN
Solar/Wind Helper
0.493
232426Y1-080 FULL
Solar/Wind Helper
0.038
233996TM1833_GEN
Solar/Wind Helper
0.199
233998TM1NIN_3.36
Solar/Wind Helper
0.199
232404W1-003 C
Solar/Wind Helper
0.493
232408W1-005 C
Solar/Wind Helper
0.493
238175AF1-290_GEN
Solar/Wind Helper
0.121
228729W2-030 C
Solar/Wind Helper
0.106
219766PARADISE C
Solar/Wind Helper
0.053
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219348LDSOLAR C
Solar/Wind Helper
0.11
970937AG2-583 GEN
Solar/Wind Harmer
16.966
3142296MT RD221
50/50
1.312
3150691DARBY 3
50/50
29.133
3150701DARBY 4
50/50
29.066
3150681DARBY 2
50/50
29.032
3150671DARBY 1
50/50
28.998
3142366NRTHEST
50/50
1.318
3150621CHESTS7
50/50
1.098
316312AB1-027
Solar/Wind Harmer
1.471
315976AC1-164 GENA
Solar/Wind Harmer
9.885
316169AC1-164_GENC
Solar/Wind Harmer
8.54
3142946ENON
Solar/Wind Harmer
-0.004
316294AC1-161 GEN
Solar/Wind Harmer
13.392
316033AB2-134 GEN
Solar/Wind Harmer
13.271
944641AF1-129 GEN
Adder
174.049
316240AF1-291 C
Solar/Wind Harmer
1.228
3150991CHESPKB
Adder
3.787
3150991CHESPKB
Adder
3.696
316185AD1-033 GEN
Solar/Wind Harmer
4.26
3145506HICKORY
Solar/Wind Harmer
-0.161
3145506HICKORY
Solar/Wind Harmer
-0.096
3145506HICKORY
Solar/Wind Harmer
-0.024
966871AG1-558 GEN
Solar/Wind Harmer
1.21
966871AG1-558 GEN
Solar/Wind Harmer
0.414
316339AD2-160 GEN
Solar/Wind Harmer
2.705
316388AE2-253 GEN
Solar/Wind Harmer
2.705
3137176SLIGO L2192
Solar/Wind Harmer
-0.159
3146456SLIGO L269
Solar/Wind Harmer
4.734
3143526WINTERP
Solar/Wind Harmer
-0.207
3130086AYDLETT
Solar/Wind Harmer
-0.159
316083AB2-161 GEN
Solar/Wind Harmer
6.468
316349AD2-085 GEN
Solar/Wind Harmer
3.527
315835AF2-110_GEN
Solar/Wind Harmer
4.955
3146386ELIZ CT
Solar/Wind Harmer
-0.04
316431W1029_GEN1
Solar/Wind Harmer
7.091
316433W1029_GEN2
Solar/Wind Harmer
7.091
316435W1029_GEN3
Solar/Wind Harmer
7.091
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
316441AF1-014 GEN
Solar/Wind Harmer
2.631
971223AH1-071 GEN
Solar/Wind Harmer
4.872
315666AE1-190 GEN
Solar/Wind Harmer
1.167
3146626S HERTFORD
Solar/Wind Harmer
-0.039
3146626S HERTFORD
Solar/Wind Harmer
-0.039
316156AD2-030 GEN
Solar/Wind Harmer
1.025
315742AE1-103 GEN
Solar/Wind Harmer
8.998
3146376EDENTON
Solar/Wind Harmer
1.124
3146376EDENTON
Solar/Wind Harmer
1.124
3144356SAPONY
Solar/Wind Harmer
1.3
316315AB2-025 C
Solar/Wind Harmer
1.002
315614AA2-178 GEN
Solar/Wind Harmer
3.976
972193AH1-681 GEN
Adder
7.355
316065AD1-022 GEN
Solar/Wind Harmer
17.916
972185AH1-677 GEN
Adder
17.801
3145893MURPHYS
Solar/Wind Harmer
0.986
3145893MURPHYS
Solar/Wind Harmer
-0.063
972187AH1-678 GEN
Adder
8.938
3146173TUNIS
Solar/Wind Harmer
-0.035
3146173TUNIS
Solar/Wind Harmer
-0.035
316365GEN2_N
Solar/Wind Harmer
2.343
316140AB2-099
Solar/Wind Harmer
0.234
970933AG2-581 GEN
Solar/Wind Harmer
32.495
316487AF1-042 GEN
Solar/Wind Harmer
4.534
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
4.839
313506AB2-031 GEN
Solar/Wind Harmer
2.695
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
0.277
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145783HORNRTN
Solar/Wind Harmer
3.935
3145783HORNRTN
Solar/Wind Harmer
3.148
3145783HORNRTN
Solar/Wind Harmer
0.984
3145783HORNRTN
Solar/Wind Harmer
0.393
316313AB2-026
Solar/Wind Harmer
0.882
3145933PARMELE
Solar/Wind Harmer
-0.065
3145933PARMELE
Solar/Wind Harmer
-0.033
970099AG2-077 GEN
Solar/Wind Harmer
40.704
316005AA1-067
Solar/Wind Harmer
0.646
315724AD1-057 GEN
Solar/Wind Harmer
6.175
316336AC2-165 C
Solar/Wind Harmer
19.468
3150341NORNECKC1
Adder
2.893
3150341NORNECKC1
Adder
2.87
3145493TOT1
Solar/Wind Harmer
0.478
3145453TOT5
Solar/Wind Harmer
0.287
3145603CNETO
Solar/Wind Harmer
0.191
961601AG1-000A GEN
Solar/Wind Harmer
11.892
316049AB1-081 GEN
Solar/Wind Harmer
3.253
316263AC1-034 GEN
Solar/Wind Harmer
14.172
315687AD1-152 GEN
Solar/Wind Harmer
3.603
313527AB2-043 GEN
Solar/Wind Harmer
4.827
316237AB2-079_GEN
Solar/Wind Harmer
0.893
970301AG2-198 GEN
Solar/Wind Harmer
14.659
972189AH1-679 GEN
Adder
4.363
970323AG2-213 GEN
Solar/Wind Harmer
14.579
958211AF2-115 GEN
Solar/Wind Harmer
4.478
3144293JTRSVLE
Adder
0.609
962561AG1-105 GEN
Solar/Wind Harmer
16.118
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
6.079
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316118AC1-105 GEN
Solar/Wind Harmer
1.92
316248AF1-058 C
Solar/Wind Harmer
0.828
316045AC1-158 PL2
Solar/Wind Helper
8.038
316450AC1-158 RIC
Solar/Wind Helper
0.67
316006AB2-029 C
Solar/Wind Helper
0.166
316411AF1-147_GEN1
Solar/Wind Helper
1.084
223401AF1-299 GEN
Solar/Wind Helper
0.395
223402AF1-300 C
Solar/Wind Helper
0.395
237006AB1-125 GEN
Solar/Wind Helper
0.12
238221AF1-254 C O1
Solar/Wind Helper
0.239
235020AA1-095 C
Solar/Wind Helper
0.045
237080AD1-060 GEN
Solar/Wind Helper
0.296
235062AE1-101 C1
Solar/Wind Helper
1.43
233982AB2-133 GEN
Solar/Wind Helper
0.349
233930AB2-032 GEN
Solar/Wind Helper
0.37
232436AB1-176 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.113
234036AF2-325 C
Solar/Wind Helper
0.041
233946AB2-136 GEN
Solar/Wind Helper
0.553
233994AC2-023 GEN
Solar/Wind Helper
0.934
232410W1-006 C
Solar/Wind Helper
0.493
232428Y3-058 C
Solar/Wind Helper
0.328
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233954AC2-188 GEN
Solar/Wind Helper
0.226
230511AF1-262
Solar/Wind Helper
0.014
230433AD2-135 GEN
Solar/Wind Helper
0.016
228754AB1-001 C
Solar/Wind Helper
0.025
219904AC1-010 C
Solar/Wind Helper
0.058
219912AD2-042 GEN
Solar/Wind Helper
0.144
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219906AC1-017 C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.077
219304NAMERICA C
Solar/Wind Helper
0.126
3150611CHESTG7
50/50
2.39
3151161SURRY 1
50/50
14.879
3142416OLDCHRC
Solar/Wind Harmer
4.412
316075AC2-137 C
Solar/Wind Harmer
1.167
970293AG2-193 GEN
Solar/Wind Harmer
5.39
3142946ENON
Solar/Wind Harmer
-0.014
3143096IRON208
Adder
1.572
3143096IRON208
Adder
1.541
3150921YORKTN3
Adder
9.333
3144216WINCHST
Adder
1.398
970133AG2-095 GEN
Solar/Wind Harmer
4.662
316458AB2-190 GEN2
Solar/Wind Harmer
4.168
315778AD1-151 GEN
Solar/Wind Harmer
36.722
3150861SPRUNCD
Adder
1.687
961611AG1-000B GEN
Solar/Wind Harmer
8.656
3151171GRAVELC
Adder
5.109
3145336SMITFLD
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
184.954
944601AF1-125 GEN
Solar/Wind Harmer
182.068
3151101ELIZAR3
Adder
33.581
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142956BIRDNECK
Solar/Wind Harmer
2.175
316473AC1-191 GEN
Solar/Wind Harmer
4.332
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
316017AA1-139 ULT1
Solar/Wind Harmer
3.242
3146456SLIGO L269
Solar/Wind Harmer
-0.04
971153AH1-033 GEN
Solar/Wind Harmer
4.639
315813AE1-149 C
Solar/Wind Harmer
24.984
316305AF2-043 C
Solar/Wind Harmer
1.202
316246AF1-032 C
Solar/Wind Harmer
0.806
970657AG2-426 GEN
Solar/Wind Harmer
8.052
316320Y1-086
Solar/Wind Harmer
2.32
316321Z2-027
Solar/Wind Harmer
1.061
3141766HARMONY
Solar/Wind Harmer
3.487
3146516WINFALL
Solar/Wind Harmer
-0.039
3141843SHACKLE
Adder
1.775
316203AE2-005 GEN
Solar/Wind Harmer
16.457
3146626S HERTFORD
Solar/Wind Harmer
-0.039
3141873WAN 176
Solar/Wind Harmer
4.567
3145273HOLLAND
Solar/Wind Harmer
-0.029
3146376EDENTON
Solar/Wind Harmer
-0.038
944011AF1-069 GEN
Solar/Wind Harmer
21.435
972255AH1-712 GEN
Adder
164.608
315735AD1-075 GEN1
Solar/Wind Harmer
3.642
3156081AA2-088 GEN
Solar/Wind Harmer
11.622
3146206CASHIE
Solar/Wind Harmer
-0.036
3145893MURPHYS
Solar/Wind Harmer
0.247
3145893MURPHYS
Solar/Wind Harmer
-0.035
3146173TUNIS
Solar/Wind Harmer
-0.035
316484AD2-074 GEN
Solar/Wind Harmer
8.666
961951AG1-038 GEN
Solar/Wind Harmer
4.534
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
970917AG2-570 GEN
Solar/Wind Harmer
85.41
316317KELFORD C
Solar/Wind Harmer
1.57
3145823KELFORD
Solar/Wind Harmer
-0.034
966621AG1-532 GEN
Solar/Wind Harmer
0.687
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
316011AB1-132 GEN
Solar/Wind Harmer
7.03
316181AB2-040 GEN
Solar/Wind Harmer
4.681
316190AA2-174 GEN
Solar/Wind Harmer
0.412
3145796HORNRTN
Solar/Wind Harmer
-0.132
3145796HORNRTN
Solar/Wind Harmer
-0.033
3143336POWHATN
Solar/Wind Harmer
3.308
3145933PARMELE
Solar/Wind Harmer
-0.033
3147043LAWRENC
Solar/Wind Harmer
-0.019
316212AC1-099_GEN
Solar/Wind Harmer
2.832
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315722AD1-056 GEN
Solar/Wind Harmer
11.228
316478AD1-087 GEN
Solar/Wind Harmer
2.719
316420AA1-050 GEN
Solar/Wind Harmer
3.544
316077AC2-138 C
Solar/Wind Harmer
0.653
3150351NORNECKC2
Adder
2.8
3146073TAR RVR
Solar/Wind Harmer
-0.031
3146083TARBORO
Solar/Wind Harmer
-0.031
3146233WITAKRS
Solar/Wind Harmer
0.644
3146233WITAKRS
Solar/Wind Harmer
-0.021
3138543CONSLDL
Solar/Wind Harmer
-0.02
961601AG1-000A GEN
Solar/Wind Harmer
12.043
3145543BTLEBRO
Solar/Wind Harmer
-0.03
3145543BTLEBRO
Solar/Wind Harmer
-0.03
964241AG1-285 GEN
Solar/Wind Harmer
23.07
970257AG2-171 GEN
Solar/Wind Harmer
10.934
971775AH1-396 GEN
Solar/Wind Harmer
2.057
959311AF2-222 GEN
Solar/Wind Harmer
30.358
3144293JTRSVLE
Adder
0.609
3147133PAMPLIN
Solar/Wind Harmer
-0.089
971781AH1-399 GEN
Solar/Wind Harmer
1.735
942461AE2-259 GEN
Solar/Wind Harmer
4.211
3146926FARMVIL
Solar/Wind Harmer
-0.016
3151861LOWMORA
Adder
1.605
3141196NOKESVL
Solar/Wind Helper
1.391
3147666LOUISA
Solar/Wind Helper
0.738
227287AC2-120 GEN
Solar/Wind Helper
0.434
226910AB2-157 C
Solar/Wind Helper
0.018
3132273ORANGE
Solar/Wind Helper
0.053
23777801MSM_W1-116
Solar/Wind Helper
0.11
208835TUHI V3-051
Solar/Wind Helper
0.021
237002AB1-128_GEN
Solar/Wind Helper
0.386
237038AE2-054 C
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.383
237085AD2-009_GEN
Solar/Wind Helper
1.395
233935AB2-179 C
Solar/Wind Helper
1.234
233933AB2-153 GEN
Solar/Wind Helper
0.226
232422X3-066 FULL
Solar/Wind Helper
0.111
233987AB2-037 GEN
Solar/Wind Helper
2.277
232417X3-008 C
Solar/Wind Helper
0.226
233964AF2-378 GEN
Solar/Wind Helper
0.041
233923SMA
Solar/Wind Helper
0.731
233997TMININ_4.2
Solar/Wind Helper
0.199
232406W1-004 FULL
Solar/Wind Helper
0.493
232434Z2-077 GEN
Solar/Wind Helper
0.123
233950AC2-186 GEN
Solar/Wind Helper
0.113
230415AB2-049 C
Solar/Wind Helper
0.029
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219921AF1-264
Solar/Wind Helper
0.049
219914AD2-027 C
Solar/Wind Helper
0.111
219291REEVESSOUT C
Solar/Wind Helper
0.011
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
CPLELTFEXP_CPLE->PJM
CLTF
17.614
CBM West 2LTFEXP_CBM-W2->PJM
CBM
79.735
LAGNLTFEXP_LAGN->PJM
CLTF
14.519
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.764
TVALTFEXP_TVA->PJM
CLTF
7.35
NYPJM->LTFIMP_NY
CLTF
4.65
LGEELTFEXP_LGEE->PJM
CLTF
2.985
WECLTFEXP_WEC->PJM
CLTF
1.509
AG2-052LTFEXP_AG2-052->PJM
LTF
0.083
AH1-155LTFEXP_AH1-155->PJM
LTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.965
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.569
MECLTFEXP_MEC->PJM
CLTF
7.763
SIGELTFEXP_SIGE->PJM
CLTF
0.24

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.11 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5743.4
MW Contribution:
193.96
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150921YORKTN3
50/50
8.613
3144216WINCHST
50/50
1.287
3151101ELIZAR3
50/50
30.933
3151161SURRY 1
50/50
12.681
3142416OLDCHRC
Solar/Wind Harmer
3.204
316075AC2-137 C
Solar/Wind Harmer
0.087
970293AG2-193 GEN
Solar/Wind Harmer
3.393
944581AF1-123 GEN
Solar/Wind Harmer
70.914
944601AF1-125 GEN
Solar/Wind Harmer
69.822
3142946ENON
Solar/Wind Harmer
0.105
3144873MCLAUGH
Solar/Wind Harmer
0.008
3144536CHRHLND
Solar/Wind Harmer
0.047
3145336SMITFLD
Solar/Wind Harmer
0.125
3151171GRAVELC
Adder
4.355
316017AA1-139 ULT1
Solar/Wind Harmer
0.166
3146456SLIGO L269
Solar/Wind Harmer
0.31
971153AH1-033 GEN
Solar/Wind Harmer
3.58
961611AG1-000B GEN
Solar/Wind Harmer
8.261
316246AF1-032 C
Solar/Wind Harmer
0.137
972255AH1-712 GEN
Adder
157.324
315778AD1-151 GEN
Solar/Wind Harmer
24.517
316458AB2-190 GEN2
Solar/Wind Harmer
1.627
316321Z2-027
Solar/Wind Harmer
0.054
970133AG2-095 GEN
Solar/Wind Harmer
2.906
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
316473AC1-191 GEN
Solar/Wind Harmer
1.012
3141766HARMONY
Solar/Wind Harmer
3.989
970657AG2-426 GEN
Solar/Wind Harmer
6.706
3146626S HERTFORD
Solar/Wind Harmer
0.298
3141843SHACKLE
Adder
1.517
316203AE2-005 GEN
Solar/Wind Harmer
0
315813AE1-149 C
Solar/Wind Harmer
15.797
3145273HOLLAND
Solar/Wind Harmer
0.221
3141873WAN 176
Solar/Wind Harmer
5.225
3143096IRON208
Adder
1.224
3143096IRON208
Adder
1.2
3152331SURRY 2
50/50
13.811
3150981CHESPKA
50/50
4.157
315975AC1-164 GENB
Solar/Wind Harmer
0.103
3142416OLDCHRC
Solar/Wind Harmer
0.859
3142416OLDCHRC
Solar/Wind Harmer
0.329
315773AC2-141 GEN
Solar/Wind Harmer
11.798
971317AH1-138 GEN
Solar/Wind Harmer
2.407
3138126ROCKLANDING
Solar/Wind Harmer
0.148
944591AF1-124 GEN
Solar/Wind Harmer
71.166
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.056
3145336SMITFLD
Solar/Wind Harmer
1.249
3151171GRAVELC
Adder
3.312
316072AD1-144
Solar/Wind Harmer
0.11
3146456SLIGO L269
Solar/Wind Harmer
0.31
961611AG1-000B GEN
Solar/Wind Harmer
16.246
319010AE1-072 C
Solar/Wind Harmer
1.543
944631AF1-128 GEN
Adder
146.631
972277AH1-723 GEN
Adder
183.33
971069AG2-661 GEN
Solar/Wind Harmer
5.448
316132AB2-190 GEN1
Solar/Wind Harmer
1.627
316093AE2-104_GEN
Solar/Wind Harmer
5.119
3146516WINFALL
Solar/Wind Harmer
0.975
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Solar/Wind Harmer
1.198
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
3141766HARMONY
Solar/Wind Harmer
0.06
939411AE1-173 GEN
Solar/Wind Harmer
127.42
316381AD1-082 GEN
Solar/Wind Harmer
0.302
971777AH1-397 GEN
Solar/Wind Harmer
0.784
315671AE2-027_GEN
Solar/Wind Harmer
0.002
940641AE2-051 GEN
Solar/Wind Harmer
23.504
3143096IRON208
Adder
1.224
3130156CHOWAN
Solar/Wind Harmer
0.291
315816AE2-034 GEN
Solar/Wind Harmer
1.211
3145663CRESWEL
Solar/Wind Harmer
0.794
971163AH1-040 GEN
Solar/Wind Harmer
22.704
3138133OCRAN
Solar/Wind Harmer
0.17
3142543TWELFTH
Solar/Wind Harmer
0.027
941031AE2-094 GEN
Solar/Wind Harmer
51.201
315737AD1-076 GEN
Solar/Wind Harmer
3.552
3146206CASHIE
Solar/Wind Harmer
0.273
971547AH1-271 GEN
Solar/Wind Harmer
5.827
3146376EDENTON
Solar/Wind Harmer
0.291
944011AF1-069 GEN
Solar/Wind Harmer
16.729
315735AD1-075 GEN1
Solar/Wind Harmer
0.788
3146206CASHIE
Solar/Wind Harmer
0.273
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
0.269
3146173TUNIS
Solar/Wind Harmer
0.267
3145963POPLR C
Solar/Wind Harmer
0.262
3146263WOODLND
Solar/Wind Harmer
0.261
970917AG2-570 GEN
Solar/Wind Harmer
23.102
3145823KELFORD
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
316011AB1-132 GEN
Solar/Wind Harmer
4.62
316181AB2-040 GEN
Solar/Wind Harmer
0.36
3150861SPRUNCD
Adder
1.159
3145796HORNRTN
Solar/Wind Harmer
1.004
3145796HORNRTN
Solar/Wind Harmer
0.251
3145933PARMELE
Solar/Wind Harmer
0.25
316212AC1-099_GEN
Solar/Wind Harmer
1.275
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3147043LAWRENC
Solar/Wind Harmer
0.146
315722AD1-056 GEN
Solar/Wind Harmer
8.274
3150351NORNECKC2
Adder
2.387
316478AD1-087 GEN
Solar/Wind Harmer
0.815
3146073TAR RVR
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
0.235
3146233WITAKRS
Solar/Wind Harmer
1.174
3146233WITAKRS
Solar/Wind Harmer
0.159
3138543CONSLDL
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
16.35
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.23
971623AH1-311 GEN
Solar/Wind Harmer
0.459
964241AG1-285 GEN
Solar/Wind Harmer
14.365
970257AG2-171 GEN
Solar/Wind Harmer
6.712
971775AH1-396 GEN
Solar/Wind Harmer
0.336
959311AF2-222 GEN
Solar/Wind Harmer
18.544
971781AH1-399 GEN
Solar/Wind Harmer
0.272
3144293JTRSVLE
Adder
0.482
3147133PAMPLIN
Solar/Wind Harmer
0.626
316222AC1-221 GEN
Solar/Wind Harmer
0.794
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.376
971683AH1-343 GEN
Solar/Wind Harmer
7.057
3146926FARMVIL
Solar/Wind Harmer
0.11
316223AC1-118
Solar/Wind Harmer
0.125
3141906WESTMOR
Solar/Wind Harmer
0.07
316123AC1-075 GEN
Solar/Wind Harmer
0.233
3146776BUCKING
Solar/Wind Harmer
0.058
972003AH1-546 GEN
Solar/Wind Harmer
4.79
3151861LOWMORA
Adder
1.473
3147312GRETNA
Solar/Wind Harmer
0.027
3148013FISHERV
Solar/Wind Harmer
0.135
3143336POWHATN
Solar/Wind Harmer
2.027
315821AE2-092 GEN
Solar/Wind Harmer
0
970221AG2-151 GEN
Solar/Wind Harmer
7.102
270494AE1-108_GEN
Solar/Wind Harmer
1.538
943811AF1-049 GEN
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
3.412
3141196NOKESVL
Solar/Wind Helper
1.219
227287AC2-120 GEN
Solar/Wind Helper
0.385
226910AB2-157 C
Solar/Wind Helper
0.016
3147666LOUISA
Solar/Wind Helper
0.593
23777801MSM_W1-116
Solar/Wind Helper
0.097
3132273ORANGE
Solar/Wind Helper
0.045
972263AH1-716 GEN
50/50
193.959
3151081ELIZAR1
50/50
30.542
3151091ELIZAR2
50/50
30.012
941591AE2-156 GEN
50/50
27.909
3151201GRAVEL4
50/50
24.044
316159AE1-175 C
Solar/Wind Harmer
0.28
316316AC1-027 C
Solar/Wind Harmer
0.299
971445AH1-216 GEN
Solar/Wind Harmer
21.985
3151221GRAVEL6
Adder
22.633
3151191GRAVEL3
Adder
22.373
3151211GRAVEL5
Adder
22.373
957871AF2-081 GEN
Solar/Wind Harmer
15.456
3146406KITTY HAWK
Solar/Wind Harmer
0.038
3138283WHITEMARSH
Solar/Wind Harmer
0.072
315697AD1-025 GEN
Solar/Wind Harmer
0.33
313526AB2-022
Solar/Wind Harmer
0.163
3146486SUNBURY
Solar/Wind Harmer
0.304
3146486SUNBURY
Solar/Wind Harmer
0.304
3146396TANGLEW
Solar/Wind Harmer
0.838
3145176PASQUOTANK
Solar/Wind Harmer
0.188
316311AC2-079 GEN
Solar/Wind Harmer
8.676
3143873LANEXA
Solar/Wind Harmer
0.181
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
970657AG2-426 GEN
Solar/Wind Harmer
2.194
970189AG2-124 GEN
Solar/Wind Harmer
8.799
3141873WAN 176
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.291
3130156CHOWAN
Solar/Wind Harmer
0.291
3143316POE
Solar/Wind Harmer
1.152
3141913WHIT STONE
Solar/Wind Harmer
0.285
3138133OCRAN
Solar/Wind Harmer
0.085
315814AE2-033 C
Solar/Wind Harmer
22.007
970533AG2-339 GEN
Solar/Wind Harmer
21.004
3130546PLYMOUTH
Solar/Wind Harmer
0.278
3141783LANCAST
Solar/Wind Harmer
0.167
3141783LANCAST
Solar/Wind Harmer
0.111
315732AD1-074 GEN1
Solar/Wind Harmer
1.577
315733AD1-074 GEN2
Solar/Wind Harmer
1.577
970673AG2-436 GEN
Solar/Wind Harmer
34.262
3146206CASHIE
Solar/Wind Harmer
0.273
970601AG2-382 GEN
Solar/Wind Harmer
10.197
3145893MURPHYS
Solar/Wind Harmer
0.727
3145893MURPHYS
Solar/Wind Harmer
0.269
971967AH1-528 GEN
Solar/Wind Harmer
42.871
316463AE2-346 GEN
Solar/Wind Harmer
0.227
3145513AHOSKIE
Solar/Wind Harmer
0.556
3145513AHOSKIE
Solar/Wind Harmer
0.265
3145683EARLEYS
Solar/Wind Harmer
0.529
3145683EARLEYS
Solar/Wind Harmer
0.264
3145683EARLEYS
Solar/Wind Harmer
0.264
3146043SEABORD
Solar/Wind Harmer
0.261
970085AG2-068 GEN
Solar/Wind Harmer
13.709
970581AG2-369 GEN
Solar/Wind Harmer
11.79
315652AC1-086 GEN
Solar/Wind Harmer
28.018
316426AA2-053 GEN
Solar/Wind Harmer
0.85
3137643SOCKMAN
Solar/Wind Harmer
1.009
3146033SCOT NK
Solar/Wind Harmer
1.008
971285AH1-108 GEN
Adder
1.896
3145796HORNRTN
Solar/Wind Harmer
0.803
3145796HORNRTN
Solar/Wind Harmer
0.1
316210AC1-098 GEN
Solar/Wind Harmer
2.286
316274AC1-208 GEN
Solar/Wind Harmer
1.261
3145746EVERETS
Solar/Wind Harmer
0.971
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
957861AF2-080 GEN
Solar/Wind Harmer
10.316
316327AA2-057 GEN
Solar/Wind Harmer
0.352
970831AG2-522 GEN
Solar/Wind Harmer
10.103
3141813NORNECK
Solar/Wind Harmer
0.235
316486AD2-202 GEN
Solar/Wind Harmer
0.239
3145573BETHELC
Solar/Wind Harmer
0.235
3145573BETHELC
Solar/Wind Harmer
0.235
3144303KENBRDG
Solar/Wind Harmer
0.168
3147173SINAI
Solar/Wind Harmer
0.206
3147243WELCO
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
12.403
970681AG2-440 GEN
Solar/Wind Harmer
8.232
946301AF1-294 GEN
Solar/Wind Harmer
3.988
961791AG1-021 GEN
Solar/Wind Harmer
1.94
316233AE1-074 FULL
Solar/Wind Harmer
0.149
971281AH1-106 GEN
Solar/Wind Harmer
2.577
971283AH1-107 GEN
Solar/Wind Harmer
2.577
971845AH1-439 GEN
Solar/Wind Harmer
7.42
270197AD1-017 GEN1
Solar/Wind Harmer
0.905
3148463FAIRFLD
Solar/Wind Harmer
0.137
3151881LOWMORC
Adder
1.462
3151881LOWMORC
Adder
1.439
3151861LOWMORA
Adder
1.416
3148133STUARTS
Solar/Wind Harmer
0.081
3148013FISHERV
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.767
316258AE1-075 C
Solar/Wind Harmer
0.1
270069AE2-166 C O1
Solar/Wind Harmer
5.596
316164AC1-076 GEN
Solar/Wind Helper
1.581
315651AD1-115 GEN
Solar/Wind Helper
0.988
226929AD2-058 GEN
Solar/Wind Helper
0.113
3138216PACIFIC
Solar/Wind Helper
0.046
3141426STAFORD
Solar/Wind Helper
0.056
23779801AA1-109
Solar/Wind Helper
0.162
237030AB1-096 C
Solar/Wind Helper
0.057
237025AB1-124 C
Solar/Wind Helper
0.141
3142296MT RD221
50/50
1.095
3150991CHESPKB
50/50
3.487
3150991CHESPKB
50/50
3.403
315976AC1-164 GENA
Solar/Wind Harmer
3.491
316169AC1-164_GENC
Solar/Wind Harmer
3.016
316312AB1-027
Solar/Wind Harmer
0.588
316294AC1-161 GEN
Solar/Wind Harmer
5.584
3142946ENON
Solar/Wind Harmer
0.031
3145506HICKORY
Solar/Wind Harmer
1.248
3145506HICKORY
Solar/Wind Harmer
0.749
3145506HICKORY
Solar/Wind Harmer
0.187
316339AD2-160 GEN
Solar/Wind Harmer
0.497
316388AE2-253 GEN
Solar/Wind Harmer
0.967
3150691DARBY 3
Adder
22.312
3150701DARBY 4
Adder
22.26
3150681DARBY 2
Adder
22.234
3150671DARBY 1
Adder
22.208
3137176SLIGO L2192
Solar/Wind Harmer
1.233
3146456SLIGO L269
Solar/Wind Harmer
5.48
3130086AYDLETT
Solar/Wind Harmer
1.236
316033AB2-134 GEN
Solar/Wind Harmer
0.001
972193AH1-681 GEN
Adder
7.029
3146386ELIZ CT
Solar/Wind Harmer
0.306
3142366NRTHEST
Adder
0.998
315835AF2-110_GEN
Solar/Wind Harmer
2.089
316349AD2-085 GEN
Solar/Wind Harmer
0.201
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
966871AG1-558 GEN
Solar/Wind Harmer
0.346
3146626S HERTFORD
Solar/Wind Harmer
0.298
3146626S HERTFORD
Solar/Wind Harmer
0.298
944641AF1-129 GEN
Adder
140.43
316156AD2-030 GEN
Solar/Wind Harmer
0.215
3146376EDENTON
Solar/Wind Harmer
1.295
3146376EDENTON
Solar/Wind Harmer
1.295
315742AE1-103 GEN
Solar/Wind Harmer
4.334
315614AA2-178 GEN
Solar/Wind Harmer
1.614
3144356SAPONY
Solar/Wind Harmer
2.334
316315AB2-025 C
Solar/Wind Harmer
0.223
316065AD1-022 GEN
Solar/Wind Harmer
12.64
972185AH1-677 GEN
Adder
15.221
3145893MURPHYS
Solar/Wind Harmer
1.802
3145893MURPHYS
Solar/Wind Harmer
0.484
972187AH1-678 GEN
Adder
7.639
3146173TUNIS
Solar/Wind Harmer
0.267
3146173TUNIS
Solar/Wind Harmer
0.267
316140AB2-099
Solar/Wind Harmer
0.094
316365GEN2_N
Solar/Wind Harmer
0.583
970933AG2-581 GEN
Solar/Wind Harmer
20.966
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
962571AG1-106 GEN
Solar/Wind Harmer
3.624
313506AB2-031 GEN
Solar/Wind Harmer
0.777
3145593CAROLNA
Solar/Wind Harmer
0.252
3145593CAROLNA
Solar/Wind Harmer
0.252
3145593CAROLNA
Solar/Wind Harmer
0.314
3145796HORNRTN
Solar/Wind Harmer
0.753
3145783HORNRTN
Solar/Wind Harmer
4.46
3145783HORNRTN
Solar/Wind Harmer
3.568
3145783HORNRTN
Solar/Wind Harmer
1.115
3145783HORNRTN
Solar/Wind Harmer
0.446
3145933PARMELE
Solar/Wind Harmer
0.5
3145933PARMELE
Solar/Wind Harmer
0.25
316005AA1-067
Solar/Wind Harmer
0.26
970099AG2-077 GEN
Solar/Wind Harmer
26.001
315724AD1-057 GEN
Solar/Wind Harmer
4.616
3150341NORNECKC1
Adder
2.466
3150341NORNECKC1
Adder
2.447
3145493TOT1
Solar/Wind Harmer
0.545
3145453TOT5
Solar/Wind Harmer
0.327
3145603CNETO
Solar/Wind Harmer
0.218
961601AG1-000A GEN
Solar/Wind Harmer
4.087
316049AB1-081 GEN
Solar/Wind Harmer
1.307
316263AC1-034 GEN
Solar/Wind Harmer
8.73
972189AH1-679 GEN
Adder
3.65
962561AG1-105 GEN
Solar/Wind Harmer
10.202
964791AG1-342 GEN
Solar/Wind Harmer
4.06
3146843MT LREL
Solar/Wind Harmer
0.211
3146843MT LREL
Solar/Wind Harmer
0.211
970323AG2-213 GEN
Solar/Wind Harmer
8.949
316118AC1-105 GEN
Solar/Wind Harmer
0.535
970301AG2-198 GEN
Solar/Wind Harmer
8.779
958211AF2-115 GEN
Solar/Wind Harmer
2.425
3144293JTRSVLE
Adder
0.482
3147133PAMPLIN
Solar/Wind Harmer
0.199
3147133PAMPLIN
Solar/Wind Harmer
0.159
3143526WINTERP
Solar/Wind Harmer
0.966
942751AE2-291 GEN
Solar/Wind Harmer
9.096
3146776BUCKING
Solar/Wind Harmer
0.647
3146776BUCKING
Solar/Wind Harmer
0.052
942671AE2-283 GEN
Solar/Wind Harmer
3.372
316336AC2-165 C
Solar/Wind Harmer
6.804
316313AB2-026
Solar/Wind Harmer
0.083
971223AH1-071 GEN
Solar/Wind Harmer
1.425
316045AC1-158 PL2
Solar/Wind Helper
6.574
316450AC1-158 RIC
Solar/Wind Helper
0.548
316006AB2-029 C
Solar/Wind Helper
0.143
316411AF1-147_GEN1
Solar/Wind Helper
0.951
223401AF1-299 GEN
Solar/Wind Helper
0.348
223402AF1-300 C
Solar/Wind Helper
0.348
237006AB1-125 GEN
Solar/Wind Helper
0.105
3145893MURPHYS
Solar/Wind Harmer
1.077
3145893MURPHYS
Solar/Wind Harmer
1.197
3156021HOLLOMANSOL
Solar/Wind Harmer
1.205
3146173TUNIS
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.264
3145963POPLR C
Solar/Wind Harmer
0.262
316023GEN1_S
Solar/Wind Harmer
0.583
3146263WOODLND
Solar/Wind Harmer
0.261
970919AG2-571 GEN
Solar/Wind Harmer
9.241
315607AA1-063A GEN
Solar/Wind Harmer
0.522
3145823KELFORD
Solar/Wind Harmer
0.258
970087AG2-069 GEN
Solar/Wind Harmer
20.564
962861AG1-135 GEN
Solar/Wind Harmer
8.162
960081AF2-299 GEN
Solar/Wind Harmer
2.444
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
8.351
3150851SPRUNCC
Adder
1.159
3145796HORNRTN
Solar/Wind Harmer
0.828
3145796HORNRTN
Solar/Wind Harmer
0.251
3145783HORNRTN
Solar/Wind Harmer
0.251
3146293MARTNCO
Solar/Wind Harmer
0.232
3141726DUNNSVL
Solar/Wind Harmer
0.977
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
957481AF2-042 GEN
Solar/Wind Harmer
65.003
3147043LAWRENC
Adder
2.204
316494AC1-189 GEN
Solar/Wind Harmer
0.808
3150351NORNECKC2
Adder
2.348
315693AD1-088 GEN
Solar/Wind Harmer
11.298
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.235
3145493TOT1
Solar/Wind Harmer
1.045
316129AC1-054 GEN
Solar/Wind Harmer
0.877
3146233WITAKRS
Solar/Wind Harmer
0.931
971065AG2-659 GEN
Solar/Wind Harmer
9.952
316359AB2-059 GEN
Solar/Wind Harmer
0.816
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.184
3142053HEARTS
Solar/Wind Harmer
0.405
316131AB2-060 GEN
Solar/Wind Harmer
0.678
970401AG2-262 GEN
Solar/Wind Harmer
1.241
315785AD2-033 C
Solar/Wind Harmer
1.709
316034AC1-036 C
Solar/Wind Harmer
0.014
316337AD2-073 GEN
Solar/Wind Harmer
0.178
970685AG2-442 GEN
Solar/Wind Harmer
15.239
971563AH1-280 GEN
Solar/Wind Harmer
2.155
3144293JTRSVLE
Adder
0.482
3144293JTRSVLE
Adder
0.381
3143526WINTERP
Solar/Wind Harmer
0.966
3146926FARMVIL
Solar/Wind Harmer
0.11
3146776BUCKING
Solar/Wind Harmer
0.065
970223AG2-152 GEN
Solar/Wind Harmer
10.386
3147123OTTER R
Solar/Wind Harmer
0.085
3147312GRETNA
Solar/Wind Harmer
0.108
3146802CHATHAM
Solar/Wind Harmer
0.102
941801AE2-185 GEN
Solar/Wind Harmer
4.336
970937AG2-583 GEN
Solar/Wind Harmer
8.26
3143336POWHATN
Solar/Wind Harmer
2.385
3143226MDLTHAN
Solar/Wind Harmer
0.133
971377AH1-170 GEN
Solar/Wind Harmer
1.42
3147623JAMES R
Solar/Wind Harmer
0.309
972135AH1-637 GEN
Solar/Wind Harmer
1.094
270030AE2-140 GEN
Solar/Wind Harmer
13.071
962751AG1-124 GEN
Solar/Wind Harmer
5.382
316447AC1-158 HLD
Solar/Wind Helper
4.521
316044AC1-158 PL1
Solar/Wind Helper
2.054
316415AF1-147_GEN2
Solar/Wind Helper
0.951
3147666LOUISA
Solar/Wind Helper
1.032
316192AB2-158 GEN
Solar/Wind Helper
1.7
CPLELTFEXP_CPLE->PJM
CLTF
15.088
CBM West 2LTFEXP_CBM-W2->PJM
CBM
69.748
LAGNLTFEXP_LAGN->PJM
CLTF
12.647
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.213
TVALTFEXP_TVA->PJM
CLTF
6.406
NYPJM->LTFIMP_NY
CLTF
4.065
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.334
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.903
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.32
MECLTFEXP_MEC->PJM
CLTF
6.832
SIGELTFEXP_SIGE->PJM
CLTF
0.211

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:159.65 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5141.33
MW Contribution:
170.5
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
49.095
315243AE2-183_GT3
50/50
5.538
3151051BRUNSWICKS1
50/50
9.073
3151021BRUNSWICKG1
50/50
4.37
971451AH1-221 GEN
50/50
13.272
3150981CHESPKA
50/50
4.067
3150851SPRUNCC
50/50
1.46
3152331SURRY 2
50/50
12.176
3143226MDLTHAN
Solar/Wind Harmer
0.368
940641AE2-051 GEN
Solar/Wind Harmer
28.032
941031AE2-094 GEN
Solar/Wind Harmer
63.736
939411AE1-173 GEN
Solar/Wind Harmer
144.938
3143526WINTERP
Solar/Wind Harmer
1.741
970919AG2-571 GEN
Solar/Wind Harmer
11.354
970087AG2-069 GEN
Solar/Wind Harmer
25.203
315773AC2-141 GEN
Solar/Wind Harmer
11.346
944591AF1-124 GEN
Solar/Wind Harmer
69.917
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.055
3146456SLIGO L269
Solar/Wind Harmer
0.305
319010AE1-072 C
Solar/Wind Harmer
1.522
316093AE2-104_GEN
Solar/Wind Harmer
5.094
316381AD1-082 GEN
Solar/Wind Harmer
0.307
316072AD1-144
Solar/Wind Harmer
0.107
3146516WINFALL
Solar/Wind Harmer
0.971
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
1.196
957481AF2-042 GEN
Solar/Wind Harmer
79.621
3143336POWHATN
Solar/Wind Harmer
5.245
3130156CHOWAN
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
3.127
961611AG1-000B GEN
Solar/Wind Harmer
15.32
315671AE2-027_GEN
Solar/Wind Harmer
0.002
316023GEN1_S
Solar/Wind Harmer
0.648
315816AE2-034 GEN
Solar/Wind Harmer
1.234
3145663CRESWEL
Solar/Wind Harmer
0.809
971163AH1-040 GEN
Solar/Wind Harmer
23.139
315693AD1-088 GEN
Solar/Wind Harmer
13.86
971069AG2-661 GEN
Solar/Wind Harmer
5.121
316132AB2-190 GEN1
Solar/Wind Harmer
1.527
315737AD1-076 GEN
Solar/Wind Harmer
3.655
960081AF2-299 GEN
Solar/Wind Harmer
2.727
3138126ROCKLANDING
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
1.132
3145893MURPHYS
Solar/Wind Harmer
1.259
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.038
3146173TUNIS
Solar/Wind Harmer
0.281
3142543TWELFTH
Solar/Wind Harmer
0.027
3156021HOLLOMANSOL
Solar/Wind Harmer
1.261
315607AA1-063A GEN
Solar/Wind Harmer
0.562
3145683EARLEYS
Solar/Wind Harmer
0.279
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Adder
2.497
971317AH1-138 GEN
Solar/Wind Harmer
2.055
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
0.906
3145796HORNRTN
Solar/Wind Harmer
0.275
3145783HORNRTN
Solar/Wind Harmer
0.274
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.146
944631AF1-128 GEN
Adder
128.737
316129AC1-054 GEN
Solar/Wind Harmer
0.998
971065AG2-659 GEN
Solar/Wind Harmer
11.366
3146293MARTNCO
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316494AC1-189 GEN
Solar/Wind Harmer
0.871
316131AB2-060 GEN
Solar/Wind Harmer
0.8
3146233WITAKRS
Solar/Wind Harmer
1.018
961671AG1-007 GEN
Solar/Wind Harmer
0.039
3146083TARBORO
Solar/Wind Harmer
0.255
3145493TOT1
Solar/Wind Harmer
1.135
315975AC1-164 GENB
Solar/Wind Harmer
0.079
3142433PROV 92
Solar/Wind Harmer
1.011
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
315785AD2-033 C
Solar/Wind Harmer
2.043
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.201
316359AB2-059 GEN
Solar/Wind Harmer
0.895
3142053HEARTS
Solar/Wind Harmer
0.444
316034AC1-036 C
Solar/Wind Harmer
0.017
970685AG2-442 GEN
Solar/Wind Harmer
18.502
970401AG2-262 GEN
Solar/Wind Harmer
1.45
971563AH1-280 GEN
Solar/Wind Harmer
2.629
3144293JTRSVLE
Adder
0.588
3144293JTRSVLE
Adder
0.464
971777AH1-397 GEN
Solar/Wind Harmer
0.642
3141766HARMONY
Solar/Wind Harmer
0.048
3142416OLDCHRC
Solar/Wind Harmer
0.622
3142416OLDCHRC
Solar/Wind Harmer
0.238
3146926FARMVIL
Solar/Wind Harmer
0.14
3138133OCRAN
Solar/Wind Harmer
0.139
3151031BRUNSWICKG2
50/50
4.37
3151101ELIZAR3
50/50
30.278
3150861SPRUNCD
50/50
1.46
3151161SURRY 1
50/50
11.976
944011AF1-069 GEN
Solar/Wind Harmer
20.825
970917AG2-570 GEN
Solar/Wind Harmer
28.384
944581AF1-123 GEN
Solar/Wind Harmer
69.669
944601AF1-125 GEN
Solar/Wind Harmer
68.596
3144873MCLAUGH
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.163
3146456SLIGO L269
Solar/Wind Harmer
0.305
971153AH1-033 GEN
Solar/Wind Harmer
3.53
3144536CHRHLND
Solar/Wind Harmer
0.046
316246AF1-032 C
Solar/Wind Harmer
0.135
970657AG2-426 GEN
Solar/Wind Harmer
6.791
315813AE1-149 C
Solar/Wind Harmer
16.138
316321Z2-027
Solar/Wind Harmer
0.054
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
0.12
3146626S HERTFORD
Solar/Wind Harmer
0.298
3145273HOLLAND
Solar/Wind Harmer
0.223
3143336POWHATN
Solar/Wind Harmer
4.458
3146376EDENTON
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
4.113
961611AG1-000B GEN
Solar/Wind Harmer
7.79
315778AD1-151 GEN
Solar/Wind Harmer
23.043
316458AB2-190 GEN2
Solar/Wind Harmer
1.527
3156081AA2-088 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.99
315735AD1-075 GEN1
Solar/Wind Harmer
0.81
3144216WINCHST
Adder
1.071
970133AG2-095 GEN
Solar/Wind Harmer
2.72
3145893MURPHYS
Solar/Wind Harmer
0.474
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
3150921YORKTN3
Adder
7.096
3146173TUNIS
Solar/Wind Harmer
0.281
316181AB2-040 GEN
Solar/Wind Harmer
0.399
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
316011AB1-132 GEN
Solar/Wind Harmer
5.054
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Solar/Wind Harmer
0.166
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
1.099
3145796HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.146
3143096IRON208
Adder
1.123
316212AC1-099_GEN
Solar/Wind Harmer
1.379
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.089
315722AD1-056 GEN
Solar/Wind Harmer
9.066
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3146233WITAKRS
Solar/Wind Harmer
1.285
3146233WITAKRS
Solar/Wind Harmer
0.174
3138543CONSLDL
Solar/Wind Harmer
0.169
964241AG1-285 GEN
Solar/Wind Harmer
17.033
3146073TAR RVR
Solar/Wind Harmer
0.255
3146083TARBORO
Solar/Wind Harmer
0.255
970293AG2-193 GEN
Solar/Wind Harmer
2.714
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
961601AG1-000A GEN
Solar/Wind Harmer
17.927
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.252
971623AH1-311 GEN
Solar/Wind Harmer
0.504
316075AC2-137 C
Solar/Wind Harmer
0.067
970257AG2-171 GEN
Solar/Wind Harmer
8.052
971775AH1-396 GEN
Solar/Wind Harmer
0.403
959311AF2-222 GEN
Solar/Wind Harmer
22.299
3144293JTRSVLE
Adder
0.588
3147133PAMPLIN
Solar/Wind Harmer
0.768
3141843SHACKLE
Adder
1.242
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
3.22
3141873WAN 176
Solar/Wind Harmer
4.288
942461AE2-259 GEN
Solar/Wind Harmer
0
3142416OLDCHRC
Solar/Wind Harmer
2.32
3146926FARMVIL
Solar/Wind Harmer
0.14
316222AC1-221 GEN
Solar/Wind Harmer
0.904
316283AC2-100 C
Solar/Wind Harmer
0.427
971683AH1-343 GEN
Solar/Wind Harmer
7.996
316473AC1-191 GEN
Solar/Wind Harmer
0.733
3146776BUCKING
Solar/Wind Harmer
0.076
316123AC1-075 GEN
Solar/Wind Harmer
0.255
3150351NORNECKC2
Adder
1.93
972003AH1-546 GEN
Solar/Wind Harmer
6.525
970221AG2-151 GEN
Solar/Wind Harmer
9.098
270494AE1-108_GEN
Solar/Wind Harmer
1.833
971781AH1-399 GEN
Solar/Wind Harmer
0.197
316223AC1-118
Solar/Wind Harmer
0.101
3141906WESTMOR
Solar/Wind Harmer
0.057
315821AE2-092 GEN
Solar/Wind Harmer
0
3147312GRETNA
Solar/Wind Harmer
0.026
972255AH1-712 GEN
Adder
65.866
943811AF1-049 GEN
Solar/Wind Harmer
0
958131AF2-107 GEN
Solar/Wind Harmer
3.325
3147666LOUISA
Solar/Wind Helper
0.716
3141196NOKESVL
Solar/Wind Helper
1.04
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.313
226910AB2-157 C
Solar/Wind Helper
0.013
316303AF2-085
50/50
6.546
315244AE2-183_ST
50/50
9.618
963041AG1-153 GEN
50/50
8.848
315779AE2-040
50/50
4.41
3151081ELIZAR1
50/50
29.895
3151091ELIZAR2
50/50
29.376
941591AE2-156 GEN
50/50
27.307
971285AH1-108 GEN
50/50
2.389
972263AH1-716 GEN
50/50
170.5
970533AG2-339 GEN
Solar/Wind Harmer
26.147
970673AG2-436 GEN
Solar/Wind Harmer
42.579
316233AE1-074 FULL
Solar/Wind Harmer
0.268
971281AH1-106 GEN
Solar/Wind Harmer
4.646
971283AH1-107 GEN
Solar/Wind Harmer
4.646
971967AH1-528 GEN
Solar/Wind Harmer
53.128
970085AG2-068 GEN
Solar/Wind Harmer
16.802
970581AG2-369 GEN
Solar/Wind Harmer
14.45
315814AE2-033 C
Solar/Wind Harmer
24.896
3143316POE
Solar/Wind Harmer
1.231
316316AC1-027 C
Solar/Wind Harmer
0.293
957871AF2-081 GEN
Solar/Wind Harmer
15.23
3146406KITTY HAWK
Solar/Wind Harmer
0.038
313526AB2-022
Solar/Wind Harmer
0.162
316311AC2-079 GEN
Solar/Wind Harmer
8.694
970657AG2-426 GEN
Solar/Wind Harmer
2.222
3146486SUNBURY
Solar/Wind Harmer
0.302
3146486SUNBURY
Solar/Wind Harmer
0.302
3146396TANGLEW
Solar/Wind Harmer
0.832
3145176PASQUOTANK
Solar/Wind Harmer
0.187
971445AH1-216 GEN
Solar/Wind Harmer
21.022
316258AE1-075 C
Solar/Wind Harmer
0.22
3130156CHOWAN
Solar/Wind Harmer
0.294
3130156CHOWAN
Solar/Wind Harmer
0.294
3151201GRAVEL4
Adder
21.4
3151221GRAVEL6
Adder
21.375
3151191GRAVEL3
Adder
21.129
3151211GRAVEL5
Adder
21.129
315697AD1-025 GEN
Solar/Wind Harmer
0.311
316486AD2-202 GEN
Solar/Wind Harmer
0.291
3130546PLYMOUTH
Solar/Wind Harmer
0.285
315732AD1-074 GEN1
Solar/Wind Harmer
1.623
315733AD1-074 GEN2
Solar/Wind Harmer
1.623
3145893MURPHYS
Solar/Wind Harmer
0.765
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.566
3146043SEABORD
Solar/Wind Harmer
0.28
316463AE2-346 GEN
Solar/Wind Harmer
0.239
3145513AHOSKIE
Solar/Wind Harmer
0.586
3145513AHOSKIE
Solar/Wind Harmer
0.28
3145683EARLEYS
Solar/Wind Harmer
0.558
3145683EARLEYS
Solar/Wind Harmer
0.279
3145683EARLEYS
Solar/Wind Harmer
0.279
315652AC1-086 GEN
Solar/Wind Harmer
30.648
3137643SOCKMAN
Solar/Wind Harmer
1.11
316426AA2-053 GEN
Solar/Wind Harmer
0.925
3145796HORNRTN
Solar/Wind Harmer
0.879
3145796HORNRTN
Solar/Wind Harmer
0.11
316159AE1-175 C
Solar/Wind Harmer
0.233
3146033SCOT NK
Solar/Wind Harmer
1.083
970831AG2-522 GEN
Solar/Wind Harmer
11.444
316210AC1-098 GEN
Solar/Wind Harmer
2.473
316274AC1-208 GEN
Solar/Wind Harmer
1.374
3138283WHITEMARSH
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
1.038
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316327AA2-057 GEN
Solar/Wind Harmer
0.384
957861AF2-080 GEN
Solar/Wind Harmer
11.117
3145573BETHELC
Solar/Wind Harmer
0.255
3145573BETHELC
Solar/Wind Harmer
0.255
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
3144303KENBRDG
Solar/Wind Harmer
0.201
970683AG2-441 GEN
Solar/Wind Harmer
15.004
970681AG2-440 GEN
Solar/Wind Harmer
9.958
946301AF1-294 GEN
Solar/Wind Harmer
4.863
961791AG1-021 GEN
Solar/Wind Harmer
2.366
3143873LANEXA
Solar/Wind Harmer
0.147
970189AG2-124 GEN
Solar/Wind Harmer
7.205
3141873WAN 176
Solar/Wind Harmer
0.048
3147173SINAI
Solar/Wind Harmer
0.24
3147243WELCO
Solar/Wind Harmer
0.15
3141913WHIT STONE
Solar/Wind Harmer
0.233
3138133OCRAN
Solar/Wind Harmer
0.069
3141783LANCAST
Solar/Wind Harmer
0.136
3141783LANCAST
Solar/Wind Harmer
0.091
971845AH1-439 GEN
Solar/Wind Harmer
9.695
3141813NORNECK
Solar/Wind Harmer
0.19
972205AH1-687 GEN
Adder
7.904
270197AD1-017 GEN1
Solar/Wind Harmer
0.884
316164AC1-076 GEN
Solar/Wind Helper
1.502
315651AD1-115 GEN
Solar/Wind Helper
0.943
3138216PACIFIC
Solar/Wind Helper
0.039
226929AD2-058 GEN
Solar/Wind Helper
0.091
315242AE2-183_GT2
50/50
5.538
315241AE2-183_GT1
50/50
5.524
972185AH1-677 GEN
50/50
20.02
3151041BRUNSWICKG3
50/50
4.37
972187AH1-678 GEN
50/50
10.028
3150991CHESPKB
50/50
3.412
3150991CHESPKB
50/50
3.33
971223AH1-071 GEN
Solar/Wind Harmer
3.928
3143526WINTERP
Solar/Wind Harmer
1.741
970933AG2-581 GEN
Solar/Wind Harmer
25.921
3144356SAPONY
Solar/Wind Harmer
2.643
316315AB2-025 C
Solar/Wind Harmer
0.253
316294AC1-161 GEN
Solar/Wind Harmer
5.37
3145506HICKORY
Solar/Wind Harmer
1.227
3145506HICKORY
Solar/Wind Harmer
0.736
3145506HICKORY
Solar/Wind Harmer
0.184
316339AD2-160 GEN
Solar/Wind Harmer
0.49
316388AE2-253 GEN
Solar/Wind Harmer
0.953
3137176SLIGO L2192
Solar/Wind Harmer
1.215
3146456SLIGO L269
Solar/Wind Harmer
5.404
3130086AYDLETT
Solar/Wind Harmer
1.22
3146386ELIZ CT
Solar/Wind Harmer
0.303
315835AF2-110_GEN
Solar/Wind Harmer
2.079
316349AD2-085 GEN
Solar/Wind Harmer
0.202
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
970099AG2-077 GEN
Solar/Wind Harmer
31.848
3146626S HERTFORD
Solar/Wind Harmer
0.298
3146626S HERTFORD
Solar/Wind Harmer
0.298
315742AE1-103 GEN
Solar/Wind Harmer
4.41
316313AB2-026
Solar/Wind Harmer
0.184
3146376EDENTON
Solar/Wind Harmer
1.307
3146376EDENTON
Solar/Wind Harmer
1.307
316365GEN2_N
Solar/Wind Harmer
0.648
315614AA2-178 GEN
Solar/Wind Harmer
1.645
316033AB2-134 GEN
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
137.077
316065AD1-022 GEN
Solar/Wind Harmer
13.063
3145893MURPHYS
Solar/Wind Harmer
1.895
3145893MURPHYS
Solar/Wind Harmer
0.509
3146173TUNIS
Solar/Wind Harmer
0.281
3146173TUNIS
Solar/Wind Harmer
0.281
313506AB2-031 GEN
Solar/Wind Harmer
0.859
316140AB2-099
Solar/Wind Harmer
0.1
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.167
962571AG1-106 GEN
Solar/Wind Harmer
3.964
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.344
316336AC2-165 C
Solar/Wind Harmer
13.978
3145796HORNRTN
Solar/Wind Harmer
0.824
3145783HORNRTN
Solar/Wind Harmer
4.881
3145783HORNRTN
Solar/Wind Harmer
3.905
3145783HORNRTN
Solar/Wind Harmer
1.22
3145783HORNRTN
Solar/Wind Harmer
0.488
3145933PARMELE
Solar/Wind Harmer
0.53
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.026
315724AD1-057 GEN
Solar/Wind Harmer
5.057
316005AA1-067
Solar/Wind Harmer
0.278
3142366NRTHEST
Adder
0.843
970301AG2-198 GEN
Solar/Wind Harmer
10.98
3150691DARBY 3
Adder
18.476
3150701DARBY 4
Adder
18.433
3150681DARBY 2
Adder
18.412
3150671DARBY 1
Adder
18.39
3145493TOT1
Solar/Wind Harmer
0.592
3145453TOT5
Solar/Wind Harmer
0.355
3145603CNETO
Solar/Wind Harmer
0.237
315976AC1-164 GENA
Solar/Wind Harmer
2.665
316169AC1-164_GENC
Solar/Wind Harmer
2.302
961601AG1-000A GEN
Solar/Wind Harmer
4.482
316049AB1-081 GEN
Solar/Wind Harmer
1.434
316263AC1-034 GEN
Solar/Wind Harmer
9.576
970323AG2-213 GEN
Solar/Wind Harmer
10.736
962561AG1-105 GEN
Solar/Wind Harmer
11.943
964791AG1-342 GEN
Solar/Wind Harmer
4.747
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
958211AF2-115 GEN
Solar/Wind Harmer
2.957
3144293JTRSVLE
Adder
0.588
3147133PAMPLIN
Solar/Wind Harmer
0.244
3147133PAMPLIN
Solar/Wind Harmer
0.196
316118AC1-105 GEN
Solar/Wind Harmer
0.623
316156AD2-030 GEN
Solar/Wind Harmer
0.177
316312AB1-027
Solar/Wind Harmer
0.426
3142296MT RD221
Adder
0.747
966871AG1-558 GEN
Solar/Wind Harmer
0.251
3146776BUCKING
Solar/Wind Harmer
0.847
3146776BUCKING
Solar/Wind Harmer
0.069
3150341NORNECKC1
Adder
1.994
3150341NORNECKC1
Adder
1.978
942751AE2-291 GEN
Solar/Wind Harmer
9.753
972189AH1-679 GEN
Adder
2.484
942671AE2-283 GEN
Solar/Wind Harmer
3.241
972193AH1-681 GEN
Adder
2.943
316045AC1-158 PL2
Solar/Wind Helper
7.063
316450AC1-158 RIC
Solar/Wind Helper
0.589
316006AB2-029 C
Solar/Wind Helper
0.131
316411AF1-147_GEN1
Solar/Wind Helper
0.811
970937AG2-583 GEN
Solar/Wind Harmer
13.903
3146776BUCKING
Solar/Wind Harmer
0.085
962861AG1-135 GEN
Solar/Wind Harmer
6.638
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.787
3141726DUNNSVL
Solar/Wind Harmer
0.785
3150351NORNECKC2
Adder
1.898
971377AH1-170 GEN
Solar/Wind Harmer
1.82
3147623JAMES R
Solar/Wind Harmer
0.395
316337AD2-073 GEN
Solar/Wind Harmer
0.144
970223AG2-152 GEN
Solar/Wind Harmer
10.638
3147123OTTER R
Solar/Wind Harmer
0.084
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.167
972277AH1-723 GEN
Adder
76.754
270030AE2-140 GEN
Solar/Wind Harmer
12.682
316447AC1-158 HLD
Solar/Wind Helper
4.857
316044AC1-158 PL1
Solar/Wind Helper
2.207
3147666LOUISA
Solar/Wind Helper
1.246
316192AB2-158 GEN
Solar/Wind Helper
2.054
316415AF1-147_GEN2
Solar/Wind Helper
0.811
CPLELTFEXP_CPLE->PJM
CLTF
16.77
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.592
LAGNLTFEXP_LAGN->PJM
CLTF
12.446
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.855
TVALTFEXP_TVA->PJM
CLTF
6.264
NYPJM->LTFIMP_NY
CLTF
3.58
LGEELTFEXP_LGEE->PJM
CLTF
2.327
WECLTFEXP_WEC->PJM
CLTF
1.181
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.214
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.577
MECLTFEXP_MEC->PJM
CLTF
6.248
SIGELTFEXP_SIGE->PJM
CLTF
0.19

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.37 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6003.22
MW Contribution:
172.76
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
49.522
315243AE2-183_GT3
50/50
5.578
3151051BRUNSWICKS1
50/50
9.138
3151021BRUNSWICKG1
50/50
4.402
971451AH1-221 GEN
50/50
13.367
3150981CHESPKA
50/50
4.114
3150851SPRUNCC
50/50
1.484
3152331SURRY 2
50/50
12.333
3143226MDLTHAN
Solar/Wind Harmer
-0.042
940641AE2-051 GEN
Solar/Wind Harmer
37.191
941031AE2-094 GEN
Solar/Wind Harmer
73.415
939411AE1-173 GEN
Solar/Wind Harmer
192.459
3143526WINTERP
Solar/Wind Harmer
-0.197
970919AG2-571 GEN
Solar/Wind Harmer
11.435
970087AG2-069 GEN
Solar/Wind Harmer
33.424
315773AC2-141 GEN
Solar/Wind Harmer
14.777
944591AF1-124 GEN
Solar/Wind Harmer
160.522
316375AC2-012 GEN
Solar/Wind Harmer
12.066
316036AC1-147 C
Solar/Wind Harmer
0.939
3146456SLIGO L269
Solar/Wind Harmer
-0.035
319010AE1-072 C
Solar/Wind Harmer
7.002
316381AD1-082 GEN
Solar/Wind Harmer
3.15
316093AE2-104_GEN
Solar/Wind Harmer
10.01
316072AD1-144
Solar/Wind Harmer
0.691
3146516WINFALL
Solar/Wind Harmer
-0.11
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.135
957481AF2-042 GEN
Solar/Wind Harmer
105.613
315611Z1-036_GEN2
Solar/Wind Harmer
8.279
3151171GRAVELC
Adder
3.171
3143336POWHATN
Solar/Wind Harmer
3.968
3130156CHOWAN
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
16.434
315671AE2-027_GEN
Solar/Wind Harmer
6.005
316023GEN1_S
Solar/Wind Harmer
2.224
316369SG1_INVT
Solar/Wind Harmer
5.883
971069AG2-661 GEN
Solar/Wind Harmer
5.2
315816AE2-034 GEN
Solar/Wind Harmer
2.651
3145663CRESWEL
Solar/Wind Harmer
-0.091
971163AH1-040 GEN
Solar/Wind Harmer
30.797
316132AB2-190 GEN1
Solar/Wind Harmer
3.297
315693AD1-088 GEN
Solar/Wind Harmer
16.343
315737AD1-076 GEN
Solar/Wind Harmer
6.138
3138126ROCKLANDING
Solar/Wind Harmer
0.099
960081AF2-299 GEN
Solar/Wind Harmer
3.626
3145893MURPHYS
Solar/Wind Harmer
-0.128
3145893MURPHYS
Solar/Wind Harmer
0.954
3142543TWELFTH
Solar/Wind Harmer
-0.003
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
8.033
316087AB2-174 GEN
Solar/Wind Harmer
4.547
3146173TUNIS
Solar/Wind Harmer
-0.032
3156021HOLLOMANSOL
Solar/Wind Harmer
4.276
315607AA1-063A GEN
Solar/Wind Harmer
3.198
3145683EARLEYS
Solar/Wind Harmer
-0.032
3146263WOODLND
Solar/Wind Harmer
-0.031
971317AH1-138 GEN
Solar/Wind Harmer
3.93
3143096IRON208
Adder
1.168
3147043LAWRENC
Adder
2.521
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
944631AF1-128 GEN
Adder
131.218
316129AC1-054 GEN
Solar/Wind Harmer
2.648
971065AG2-659 GEN
Solar/Wind Harmer
15.097
3146293MARTNCO
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316494AC1-189 GEN
Solar/Wind Harmer
3.148
316131AB2-060 GEN
Solar/Wind Harmer
3.135
315975AC1-164 GENB
Solar/Wind Harmer
0.196
3142433PROV 92
Solar/Wind Harmer
-0.116
3142433PROV 92
Adder
0.502
3142433PROV 92
Adder
0.502
316319Z2-044 C
Solar/Wind Harmer
1.603
3146233WITAKRS
Solar/Wind Harmer
-0.115
961671AG1-007 GEN
Solar/Wind Harmer
0.366
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.859
315785AD2-033 C
Solar/Wind Harmer
6.476
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.023
316359AB2-059 GEN
Solar/Wind Harmer
3.843
3142053HEARTS
Solar/Wind Harmer
0.336
316034AC1-036 C
Solar/Wind Harmer
0.527
970685AG2-442 GEN
Solar/Wind Harmer
24.564
970401AG2-262 GEN
Solar/Wind Harmer
1.828
971777AH1-397 GEN
Solar/Wind Harmer
3.262
971563AH1-280 GEN
Solar/Wind Harmer
3.49
3144293JTRSVLE
Adder
0.593
3144293JTRSVLE
Adder
0.468
315662AE1-191 GEN
Solar/Wind Harmer
3.35
316280AD1-041 GEN
Solar/Wind Harmer
2.094
316314AB2-024 C
Solar/Wind Harmer
2.375
3141766HARMONY
Solar/Wind Harmer
-0.005
3142416OLDCHRC
Solar/Wind Harmer
-0.071
3142416OLDCHRC
Solar/Wind Harmer
-0.027
3138133OCRAN
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.016
970937AG2-583 GEN
Solar/Wind Harmer
18.469
3150351NORNECKC2
Adder
1.968
972277AH1-723 GEN
Adder
78.545
316447AC1-158 HLD
Solar/Wind Helper
4.938
316044AC1-158 PL1
Solar/Wind Helper
2.244
3147666LOUISA
Solar/Wind Helper
1.267
316192AB2-158 GEN
Solar/Wind Helper
2.089
316415AF1-147_GEN2
Solar/Wind Helper
0.821
315242AE2-183_GT2
50/50
5.578
315241AE2-183_GT1
50/50
5.563
972185AH1-677 GEN
50/50
20.162
3151041BRUNSWICKG3
50/50
4.402
972187AH1-678 GEN
50/50
10.099
3150991CHESPKB
50/50
3.452
3150991CHESPKB
50/50
3.369
971223AH1-071 GEN
Solar/Wind Harmer
5.216
3143526WINTERP
Solar/Wind Harmer
-0.197
970933AG2-581 GEN
Solar/Wind Harmer
34.375
3144356SAPONY
Solar/Wind Harmer
1.25
316315AB2-025 C
Solar/Wind Harmer
0.965
316294AC1-161 GEN
Solar/Wind Harmer
11.421
316185AD1-033 GEN
Solar/Wind Harmer
3.677
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.34
316388AE2-253 GEN
Solar/Wind Harmer
2.34
3137176SLIGO L2192
Solar/Wind Harmer
-0.137
3146456SLIGO L269
Solar/Wind Harmer
4.1
3130086AYDLETT
Solar/Wind Harmer
-0.138
316083AB2-161 GEN
Solar/Wind Harmer
5.586
3146386ELIZ CT
Solar/Wind Harmer
-0.034
316349AD2-085 GEN
Solar/Wind Harmer
3.057
315835AF2-110_GEN
Solar/Wind Harmer
4.304
316431W1029_GEN1
Solar/Wind Harmer
6.184
316433W1029_GEN2
Solar/Wind Harmer
6.184
316435W1029_GEN3
Solar/Wind Harmer
6.184
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
970099AG2-077 GEN
Solar/Wind Harmer
42.245
315742AE1-103 GEN
Solar/Wind Harmer
7.962
316313AB2-026
Solar/Wind Harmer
0.9
3146376EDENTON
Solar/Wind Harmer
0.991
3146376EDENTON
Solar/Wind Harmer
0.991
316240AF1-291 C
Solar/Wind Harmer
0.996
316365GEN2_N
Solar/Wind Harmer
2.224
316033AB2-134 GEN
Solar/Wind Harmer
10.623
944641AF1-129 GEN
Adder
139.37
315614AA2-178 GEN
Solar/Wind Harmer
3.534
316065AD1-022 GEN
Solar/Wind Harmer
16.107
3145893MURPHYS
Solar/Wind Harmer
0.897
3145893MURPHYS
Solar/Wind Harmer
-0.058
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
313506AB2-031 GEN
Solar/Wind Harmer
2.549
316140AB2-099
Solar/Wind Harmer
0.214
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
962571AG1-106 GEN
Solar/Wind Harmer
4.546
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
0.26
316336AC2-165 C
Solar/Wind Harmer
19.525
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145783HORNRTN
Solar/Wind Harmer
3.697
3145783HORNRTN
Solar/Wind Harmer
2.957
3145783HORNRTN
Solar/Wind Harmer
0.924
3145783HORNRTN
Solar/Wind Harmer
0.37
315687AD1-152 GEN
Solar/Wind Harmer
3.659
3142946ENON
Solar/Wind Harmer
-0.003
3145933PARMELE
Solar/Wind Harmer
-0.06
3145933PARMELE
Solar/Wind Harmer
-0.03
315724AD1-057 GEN
Solar/Wind Harmer
5.823
3142366NRTHEST
Adder
0.863
316005AA1-067
Solar/Wind Harmer
0.597
3150691DARBY 3
Adder
18.9
3150701DARBY 4
Adder
18.856
3150681DARBY 2
Adder
18.834
3150671DARBY 1
Adder
18.812
313527AB2-043 GEN
Solar/Wind Harmer
4.738
316237AB2-079_GEN
Solar/Wind Harmer
0.876
970301AG2-198 GEN
Solar/Wind Harmer
14.571
315976AC1-164 GENA
Solar/Wind Harmer
6.61
316169AC1-164_GENC
Solar/Wind Harmer
5.711
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
961601AG1-000A GEN
Solar/Wind Harmer
11.238
316049AB1-081 GEN
Solar/Wind Harmer
3.075
316263AC1-034 GEN
Solar/Wind Harmer
13.396
970323AG2-213 GEN
Solar/Wind Harmer
14.253
962561AG1-105 GEN
Solar/Wind Harmer
15.855
964791AG1-342 GEN
Solar/Wind Harmer
5.982
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
316441AF1-014 GEN
Solar/Wind Harmer
1.884
958211AF2-115 GEN
Solar/Wind Harmer
4.362
3144293JTRSVLE
Adder
0.593
315666AE1-190 GEN
Solar/Wind Harmer
0.838
316156AD2-030 GEN
Solar/Wind Harmer
0.739
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.022
316312AB1-027
Solar/Wind Harmer
0.929
316118AC1-105 GEN
Solar/Wind Harmer
1.891
316248AF1-058 C
Solar/Wind Harmer
0.816
3142296MT RD221
Adder
0.769
966871AG1-558 GEN
Solar/Wind Harmer
0.757
966871AG1-558 GEN
Solar/Wind Harmer
0.259
316487AF1-042 GEN
Solar/Wind Harmer
3.254
3150341NORNECKC1
Adder
2.068
3150341NORNECKC1
Adder
2.051
972189AH1-679 GEN
Adder
2.707
972193AH1-681 GEN
Adder
3.012
316045AC1-158 PL2
Solar/Wind Helper
7.181
316450AC1-158 RIC
Solar/Wind Helper
0.598
316006AB2-029 C
Solar/Wind Helper
0.133
316411AF1-147_GEN1
Solar/Wind Helper
0.821
3151031BRUNSWICKG2
50/50
4.402
3151101ELIZAR3
50/50
30.63
3150861SPRUNCD
50/50
1.484
3151161SURRY 1
50/50
12.144
944011AF1-069 GEN
Solar/Wind Harmer
23.003
970917AG2-570 GEN
Solar/Wind Harmer
90.338
944581AF1-123 GEN
Solar/Wind Harmer
159.946
944601AF1-125 GEN
Solar/Wind Harmer
157.45
3142956BIRDNECK
Solar/Wind Harmer
1.873
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
2.806
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.017
3144536CHRHLND
Solar/Wind Harmer
-0.005
316305AF2-043 C
Solar/Wind Harmer
1.041
316246AF1-032 C
Solar/Wind Harmer
0.698
315813AE1-149 C
Solar/Wind Harmer
21.531
970657AG2-426 GEN
Solar/Wind Harmer
6.957
316320Y1-086
Solar/Wind Harmer
2.016
316321Z2-027
Solar/Wind Harmer
0.923
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3145273HOLLAND
Solar/Wind Harmer
-0.025
3151171GRAVELC
Adder
4.17
3143336POWHATN
Solar/Wind Harmer
3.373
3146376EDENTON
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
7.012
315778AD1-151 GEN
Solar/Wind Harmer
29.252
316458AB2-190 GEN2
Solar/Wind Harmer
3.297
3156081AA2-088 GEN
Solar/Wind Harmer
10.537
3144216WINCHST
Adder
1.087
970133AG2-095 GEN
Solar/Wind Harmer
3.642
316478AD1-087 GEN
Solar/Wind Harmer
2.795
315735AD1-075 GEN1
Solar/Wind Harmer
3.263
966621AG1-532 GEN
Solar/Wind Harmer
0.654
3150921YORKTN3
Adder
7.206
3145893MURPHYS
Solar/Wind Harmer
0.224
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316181AB2-040 GEN
Solar/Wind Harmer
4.428
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
316011AB1-132 GEN
Solar/Wind Harmer
6.605
3146263WOODLND
Solar/Wind Harmer
-0.031
316190AA2-174 GEN
Solar/Wind Harmer
0.385
3143096IRON208
Adder
1.168
3143096IRON208
Adder
1.145
3147043LAWRENC
Solar/Wind Harmer
-0.019
316317KELFORD C
Solar/Wind Harmer
1.444
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.124
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
3142946ENON
Solar/Wind Harmer
-0.01
316212AC1-099_GEN
Solar/Wind Harmer
2.642
3145933PARMELE
Solar/Wind Harmer
-0.03
315722AD1-056 GEN
Solar/Wind Harmer
10.588
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
970293AG2-193 GEN
Solar/Wind Harmer
3.654
316420AA1-050 GEN
Solar/Wind Harmer
3.314
3142433PROV 92
Adder
0.502
3142433PROV 92
Adder
0.502
3146233WITAKRS
Solar/Wind Harmer
0.608
3146233WITAKRS
Solar/Wind Harmer
-0.02
3138543CONSLDL
Solar/Wind Harmer
-0.019
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
964241AG1-285 GEN
Solar/Wind Harmer
22.614
316075AC2-137 C
Solar/Wind Harmer
0.778
961601AG1-000A GEN
Solar/Wind Harmer
11.38
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.028
970257AG2-171 GEN
Solar/Wind Harmer
10.69
971775AH1-396 GEN
Solar/Wind Harmer
2.011
959311AF2-222 GEN
Solar/Wind Harmer
29.664
3141843SHACKLE
Adder
1.271
316203AE2-005 GEN
Solar/Wind Harmer
11.785
3144293JTRSVLE
Adder
0.593
3141766HARMONY
Solar/Wind Harmer
2.472
3141873WAN 176
Solar/Wind Harmer
3.291
3147133PAMPLIN
Solar/Wind Harmer
-0.087
3142416OLDCHRC
Solar/Wind Harmer
2.787
942461AE2-259 GEN
Solar/Wind Harmer
4.082
3146926FARMVIL
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
2.53
316473AC1-191 GEN
Solar/Wind Harmer
2.71
316222AC1-221 GEN
Solar/Wind Harmer
2.507
316283AC2-100 C
Solar/Wind Harmer
2.329
316484AD2-074 GEN
Solar/Wind Harmer
6.22
961951AG1-038 GEN
Solar/Wind Harmer
3.254
971683AH1-343 GEN
Solar/Wind Harmer
10.615
3150351NORNECKC2
Adder
2.001
972255AH1-712 GEN
Adder
67.403
3147666LOUISA
Solar/Wind Helper
0.729
3141196NOKESVL
Solar/Wind Helper
1.054
3132273ORANGE
Solar/Wind Helper
0.048
227287AC2-120 GEN
Solar/Wind Helper
0.316
226910AB2-157 C
Solar/Wind Helper
0.013
316303AF2-085
50/50
6.603
315244AE2-183_ST
50/50
9.686
963041AG1-153 GEN
50/50
8.911
315779AE2-040
50/50
4.454
3151081ELIZAR1
50/50
30.243
3151091ELIZAR2
50/50
29.718
941591AE2-156 GEN
50/50
27.626
971285AH1-108 GEN
50/50
2.428
972263AH1-716 GEN
50/50
172.765
970533AG2-339 GEN
Solar/Wind Harmer
26.33
970673AG2-436 GEN
Solar/Wind Harmer
84.687
316233AE1-074 FULL
Solar/Wind Harmer
1.025
971281AH1-106 GEN
Solar/Wind Harmer
6.19
971283AH1-107 GEN
Solar/Wind Harmer
6.19
971967AH1-528 GEN
Solar/Wind Harmer
70.638
315814AE2-033 C
Solar/Wind Harmer
33.255
970085AG2-068 GEN
Solar/Wind Harmer
22.282
970581AG2-369 GEN
Solar/Wind Harmer
19.163
3143316POE
Solar/Wind Harmer
-0.139
316316AC1-027 C
Solar/Wind Harmer
1.07
316018AA1-139 ULT2
Solar/Wind Harmer
2.971
957871AF2-081 GEN
Solar/Wind Harmer
17.385
3146406KITTY HAWK
Solar/Wind Harmer
0.029
970657AG2-426 GEN
Solar/Wind Harmer
2.171
313526AB2-022
Solar/Wind Harmer
0.926
315833AF1-017_GEN
Solar/Wind Harmer
6.538
316311AC2-079 GEN
Solar/Wind Harmer
17.367
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146396TANGLEW
Solar/Wind Harmer
0.631
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
316236AE1-162_GEN
Solar/Wind Harmer
1.023
315839AE2-212 C
Solar/Wind Harmer
1.022
971445AH1-216 GEN
Solar/Wind Harmer
21.033
315800Z1-036_GEN1
Solar/Wind Harmer
8.279
3151201GRAVEL4
Adder
21.7
3151221GRAVEL6
Adder
21.675
3151191GRAVEL3
Adder
21.426
3151211GRAVEL5
Adder
21.426
316258AE1-075 C
Solar/Wind Harmer
0.81
316405AF2-144 C
Solar/Wind Harmer
0.855
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
315697AD1-025 GEN
Solar/Wind Harmer
6.658
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
316486AD2-202 GEN
Solar/Wind Harmer
0.818
315732AD1-074 GEN1
Solar/Wind Harmer
6.529
315733AD1-074 GEN2
Solar/Wind Harmer
6.529
946281AF1-292 GEN
Solar/Wind Harmer
0.722
316318V4-068
Solar/Wind Harmer
0.801
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
14.059
3146043SEABORD
Solar/Wind Harmer
-0.032
316463AE2-346 GEN
Solar/Wind Harmer
0.513
3145513AHOSKIE
Solar/Wind Harmer
0.277
961941AG1-037 GEN
Solar/Wind Harmer
0.239
3145513AHOSKIE
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
315652AC1-086 GEN
Solar/Wind Harmer
35.578
3137643SOCKMAN
Solar/Wind Harmer
-0.125
316426AA2-053 GEN
Solar/Wind Harmer
3.162
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.012
316382AG1-145 C
Solar/Wind Harmer
0.936
316159AE1-175 C
Solar/Wind Harmer
0.833
316174AB2-169 GEN
Solar/Wind Harmer
4.762
3146033SCOT NK
Solar/Wind Harmer
-0.122
970831AG2-522 GEN
Solar/Wind Harmer
15.204
316210AC1-098 GEN
Solar/Wind Harmer
4.755
316274AC1-208 GEN
Solar/Wind Harmer
3.252
957831AF2-077 GEN
Solar/Wind Harmer
0.904
3138283WHITEMARSH
Solar/Wind Harmer
0.047
3145746EVERETS
Solar/Wind Harmer
-0.117
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
2.969
957861AF2-080 GEN
Solar/Wind Harmer
12.799
316238AB2-078_GEN
Solar/Wind Harmer
0.876
316239AB2-077_GEN
Solar/Wind Harmer
0.876
3142433PROV 92
Adder
0.502
3142433PROV 92
Adder
0.502
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
3144303KENBRDG
Solar/Wind Harmer
-0.023
3143873LANEXA
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
19.92
970681AG2-440 GEN
Solar/Wind Harmer
13.221
946301AF1-294 GEN
Solar/Wind Harmer
7.154
961791AG1-021 GEN
Solar/Wind Harmer
3.49
316059AD1-063 C
Solar/Wind Harmer
0.626
957601AF2-054 GEN
Solar/Wind Harmer
0.83
3141873WAN 176
Solar/Wind Harmer
-0.005
3147173SINAI
Solar/Wind Harmer
-0.027
3147243WELCO
Solar/Wind Harmer
-0.017
3141913WHIT STONE
Solar/Wind Harmer
-0.027
3138133OCRAN
Solar/Wind Harmer
-0.008
3141783LANCAST
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.01
972205AH1-687 GEN
Adder
7.976
316164AC1-076 GEN
Solar/Wind Helper
1.532
315651AD1-115 GEN
Solar/Wind Helper
0.96
3138216PACIFIC
Solar/Wind Helper
0.04
226929AD2-058 GEN
Solar/Wind Helper
0.092
971845AH1-439 GEN
Solar/Wind Harmer
9.393
CPLELTFEXP_CPLE->PJM
CLTF
16.911
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.146
LAGNLTFEXP_LAGN->PJM
CLTF
12.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.167
TVALTFEXP_TVA->PJM
CLTF
6.318
NYPJM->LTFIMP_NY
CLTF
3.625
LGEELTFEXP_LGEE->PJM
CLTF
2.346
WECLTFEXP_WEC->PJM
CLTF
1.191
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.526
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.76
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.192

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.78 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5980.27
MW Contribution:
190.2
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
49.573
315243AE2-183_GT3
50/50
5.813
3151051BRUNSWICKS1
50/50
9.521
3151021BRUNSWICKG1
50/50
4.586
971451AH1-221 GEN
50/50
13.927
3150981CHESPKA
50/50
4.42
3152331SURRY 2
50/50
13.6
3143226MDLTHAN
Solar/Wind Harmer
-0.042
940641AE2-051 GEN
Solar/Wind Harmer
39.057
941031AE2-094 GEN
Solar/Wind Harmer
76.547
939411AE1-173 GEN
Solar/Wind Harmer
203.212
315773AC2-141 GEN
Solar/Wind Harmer
16.033
3143526WINTERP
Solar/Wind Harmer
-0.197
944591AF1-124 GEN
Solar/Wind Harmer
172.781
970919AG2-571 GEN
Solar/Wind Harmer
11.909
316375AC2-012 GEN
Solar/Wind Harmer
12.964
316036AC1-147 C
Solar/Wind Harmer
1.009
3146456SLIGO L269
Solar/Wind Harmer
-0.037
319010AE1-072 C
Solar/Wind Harmer
7.517
970087AG2-069 GEN
Solar/Wind Harmer
34.802
316093AE2-104_GEN
Solar/Wind Harmer
10.689
316072AD1-144
Solar/Wind Harmer
0.74
3146516WINFALL
Solar/Wind Harmer
-0.117
3146516WINFALL
Solar/Wind Harmer
-0.036
3145336SMITFLD
Solar/Wind Harmer
-0.145
316381AD1-082 GEN
Solar/Wind Harmer
3.297
315611Z1-036_GEN2
Solar/Wind Harmer
8.837
3130156CHOWAN
Solar/Wind Harmer
-0.036
3151171GRAVELC
Adder
3.374
961611AG1-000B GEN
Solar/Wind Harmer
17.402
957481AF2-042 GEN
Solar/Wind Harmer
109.633
3138126ROCKLANDING
Solar/Wind Harmer
0.107
315816AE2-034 GEN
Solar/Wind Harmer
2.82
3145663CRESWEL
Solar/Wind Harmer
-0.097
971163AH1-040 GEN
Solar/Wind Harmer
32.764
316369SG1_INVT
Solar/Wind Harmer
6.183
316023GEN1_S
Solar/Wind Harmer
2.319
971069AG2-661 GEN
Solar/Wind Harmer
5.449
315737AD1-076 GEN
Solar/Wind Harmer
6.514
971317AH1-138 GEN
Solar/Wind Harmer
4.276
3150851SPRUNCC
Adder
1.399
316132AB2-190 GEN1
Solar/Wind Harmer
3.44
315671AE2-027_GEN
Solar/Wind Harmer
6.145
3146206CASHIE
Solar/Wind Harmer
-0.034
971547AH1-271 GEN
Solar/Wind Harmer
8.511
3145893MURPHYS
Solar/Wind Harmer
-0.135
3145893MURPHYS
Solar/Wind Harmer
1.007
315693AD1-088 GEN
Solar/Wind Harmer
16.931
3146173TUNIS
Solar/Wind Harmer
-0.034
3156021HOLLOMANSOL
Solar/Wind Harmer
4.518
960081AF2-299 GEN
Solar/Wind Harmer
3.779
3145683EARLEYS
Solar/Wind Harmer
-0.033
3143336POWHATN
Solar/Wind Harmer
3.962
315607AA1-063A GEN
Solar/Wind Harmer
3.359
316087AB2-174 GEN
Solar/Wind Harmer
4.746
3146263WOODLND
Solar/Wind Harmer
-0.033
3145963POPLR C
Solar/Wind Harmer
-0.033
3145823KELFORD
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145783HORNRTN
Solar/Wind Harmer
-0.032
3147043LAWRENC
Adder
2.621
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
136.394
3143096IRON208
Adder
1.187
3146293MARTNCO
Solar/Wind Harmer
0.196
316129AC1-054 GEN
Solar/Wind Harmer
2.756
971065AG2-659 GEN
Solar/Wind Harmer
15.705
315975AC1-164 GENB
Solar/Wind Harmer
0.211
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
316494AC1-189 GEN
Solar/Wind Harmer
3.3
3142433PROV 92
Solar/Wind Harmer
-0.122
3142433PROV 92
Adder
0.529
3142433PROV 92
Adder
0.529
316319Z2-044 C
Solar/Wind Harmer
1.676
3146233WITAKRS
Solar/Wind Harmer
-0.12
961671AG1-007 GEN
Solar/Wind Harmer
0.383
3146083TARBORO
Solar/Wind Harmer
-0.03
3145493TOT1
Solar/Wind Harmer
0.899
316131AB2-060 GEN
Solar/Wind Harmer
3.241
971777AH1-397 GEN
Solar/Wind Harmer
3.5
316314AB2-024 C
Solar/Wind Harmer
2.558
315662AE1-191 GEN
Solar/Wind Harmer
3.6
316280AD1-041 GEN
Solar/Wind Harmer
2.25
3141766HARMONY
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.03
3145543BTLEBRO
Solar/Wind Harmer
-0.024
316359AB2-059 GEN
Solar/Wind Harmer
4.013
3142053HEARTS
Solar/Wind Harmer
0.351
315785AD2-033 C
Solar/Wind Harmer
6.676
316034AC1-036 C
Solar/Wind Harmer
0.543
970401AG2-262 GEN
Solar/Wind Harmer
1.889
970685AG2-442 GEN
Solar/Wind Harmer
25.243
3138133OCRAN
Solar/Wind Harmer
-0.017
971563AH1-280 GEN
Solar/Wind Harmer
3.583
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.481
3142416OLDCHRC
Solar/Wind Harmer
-0.071
3142416OLDCHRC
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.016
962861AG1-135 GEN
Solar/Wind Harmer
9.674
970937AG2-583 GEN
Solar/Wind Harmer
18.361
316404AE1-155 C
Solar/Wind Harmer
4.874
315242AE2-183_GT2
50/50
5.813
315241AE2-183_GT1
50/50
5.797
972185AH1-677 GEN
50/50
21.011
3151041BRUNSWICKG3
50/50
4.586
972187AH1-678 GEN
50/50
10.522
3150991CHESPKB
50/50
3.708
3150991CHESPKB
50/50
3.619
971223AH1-071 GEN
Solar/Wind Harmer
5.222
316294AC1-161 GEN
Solar/Wind Harmer
12.391
970933AG2-581 GEN
Solar/Wind Harmer
35.775
3143526WINTERP
Solar/Wind Harmer
-0.197
316185AD1-033 GEN
Solar/Wind Harmer
3.952
3145506HICKORY
Solar/Wind Harmer
-0.149
3145506HICKORY
Solar/Wind Harmer
-0.09
3145506HICKORY
Solar/Wind Harmer
-0.022
316339AD2-160 GEN
Solar/Wind Harmer
2.513
316388AE2-253 GEN
Solar/Wind Harmer
2.513
3137176SLIGO L2192
Solar/Wind Harmer
-0.147
3146456SLIGO L269
Solar/Wind Harmer
4.401
3130086AYDLETT
Solar/Wind Harmer
-0.148
3144356SAPONY
Solar/Wind Harmer
1.298
316315AB2-025 C
Solar/Wind Harmer
1.001
3146386ELIZ CT
Solar/Wind Harmer
-0.037
315835AF2-110_GEN
Solar/Wind Harmer
4.595
316431W1029_GEN1
Solar/Wind Harmer
6.619
316433W1029_GEN2
Solar/Wind Harmer
6.619
316435W1029_GEN3
Solar/Wind Harmer
6.619
316349AD2-085 GEN
Solar/Wind Harmer
3.239
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
316083AB2-161 GEN
Solar/Wind Harmer
5.847
315742AE1-103 GEN
Solar/Wind Harmer
8.462
3146376EDENTON
Solar/Wind Harmer
1.057
3146376EDENTON
Solar/Wind Harmer
1.057
970099AG2-077 GEN
Solar/Wind Harmer
43.853
315614AA2-178 GEN
Solar/Wind Harmer
3.76
316033AB2-134 GEN
Solar/Wind Harmer
11.165
316365GEN2_N
Solar/Wind Harmer
2.319
316065AD1-022 GEN
Solar/Wind Harmer
17.074
3145893MURPHYS
Solar/Wind Harmer
0.947
3145893MURPHYS
Solar/Wind Harmer
-0.061
316240AF1-291 C
Solar/Wind Harmer
1.013
3146173TUNIS
Solar/Wind Harmer
-0.034
3146173TUNIS
Solar/Wind Harmer
-0.034
316140AB2-099
Solar/Wind Harmer
0.226
316313AB2-026
Solar/Wind Harmer
0.898
944641AF1-129 GEN
Adder
141.504
313506AB2-031 GEN
Solar/Wind Harmer
2.662
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
962571AG1-106 GEN
Solar/Wind Harmer
4.755
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
0.272
3145796HORNRTN
Solar/Wind Harmer
-0.097
3145783HORNRTN
Solar/Wind Harmer
3.869
3145783HORNRTN
Solar/Wind Harmer
3.095
3145783HORNRTN
Solar/Wind Harmer
0.967
3145783HORNRTN
Solar/Wind Harmer
0.387
3142946ENON
Solar/Wind Harmer
-0.003
3145933PARMELE
Solar/Wind Harmer
-0.063
3145933PARMELE
Solar/Wind Harmer
-0.032
315687AD1-152 GEN
Solar/Wind Harmer
3.791
315976AC1-164 GENA
Solar/Wind Harmer
7.126
316169AC1-164_GENC
Solar/Wind Harmer
6.157
316336AC2-165 C
Solar/Wind Harmer
19.473
316005AA1-067
Solar/Wind Harmer
0.628
315724AD1-057 GEN
Solar/Wind Harmer
6.084
3145493TOT1
Solar/Wind Harmer
0.469
3145453TOT5
Solar/Wind Harmer
0.281
3145603CNETO
Solar/Wind Harmer
0.188
313527AB2-043 GEN
Solar/Wind Harmer
4.9
316237AB2-079_GEN
Solar/Wind Harmer
0.906
316441AF1-014 GEN
Solar/Wind Harmer
2.022
315666AE1-190 GEN
Solar/Wind Harmer
0.9
970301AG2-198 GEN
Solar/Wind Harmer
14.956
316156AD2-030 GEN
Solar/Wind Harmer
0.795
961601AG1-000A GEN
Solar/Wind Harmer
11.734
316049AB1-081 GEN
Solar/Wind Harmer
3.211
316263AC1-034 GEN
Solar/Wind Harmer
13.988
3150691DARBY 3
Adder
18.923
3150701DARBY 4
Adder
18.879
3150681DARBY 2
Adder
18.857
3150671DARBY 1
Adder
18.835
970323AG2-213 GEN
Solar/Wind Harmer
14.684
3142366NRTHEST
Adder
0.853
962561AG1-105 GEN
Solar/Wind Harmer
16.387
964791AG1-342 GEN
Solar/Wind Harmer
6.183
3146843MT LREL
Solar/Wind Harmer
-0.029
3146843MT LREL
Solar/Wind Harmer
-0.029
958211AF2-115 GEN
Solar/Wind Harmer
4.479
3144293JTRSVLE
Adder
0.609
316118AC1-105 GEN
Solar/Wind Harmer
1.954
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.023
316248AF1-058 C
Solar/Wind Harmer
0.843
316312AB1-027
Solar/Wind Harmer
0.922
316487AF1-042 GEN
Solar/Wind Harmer
3.494
3142296MT RD221
Adder
0.721
3150341NORNECKC1
Adder
2.214
3150341NORNECKC1
Adder
2.196
972189AH1-679 GEN
Adder
2.342
316045AC1-158 PL2
Solar/Wind Helper
7.026
316450AC1-158 RIC
Solar/Wind Helper
0.586
316006AB2-029 C
Solar/Wind Helper
0.131
316411AF1-147_GEN1
Solar/Wind Helper
0.815
3151031BRUNSWICKG2
50/50
4.586
3151101ELIZAR3
50/50
32.918
3151161SURRY 1
50/50
12.919
944011AF1-069 GEN
Solar/Wind Harmer
23.985
944581AF1-123 GEN
Solar/Wind Harmer
172.161
944601AF1-125 GEN
Solar/Wind Harmer
169.474
970917AG2-570 GEN
Solar/Wind Harmer
94.078
3142956BIRDNECK
Solar/Wind Harmer
2.013
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
3.013
3146456SLIGO L269
Solar/Wind Harmer
-0.037
971153AH1-033 GEN
Solar/Wind Harmer
4.313
3144536CHRHLND
Solar/Wind Harmer
-0.006
316305AF2-043 C
Solar/Wind Harmer
1.115
316246AF1-032 C
Solar/Wind Harmer
0.749
316320Y1-086
Solar/Wind Harmer
2.161
316321Z2-027
Solar/Wind Harmer
0.989
3146516WINFALL
Solar/Wind Harmer
-0.036
3145336SMITFLD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
7.292
3145273HOLLAND
Solar/Wind Harmer
-0.027
315813AE1-149 C
Solar/Wind Harmer
22.361
3151171GRAVELC
Adder
4.436
3146376EDENTON
Solar/Wind Harmer
-0.036
961611AG1-000B GEN
Solar/Wind Harmer
7.425
3144216WINCHST
Adder
1.178
3150921YORKTN3
Adder
7.829
315778AD1-151 GEN
Solar/Wind Harmer
30.652
315735AD1-075 GEN1
Solar/Wind Harmer
3.463
3156081AA2-088 GEN
Solar/Wind Harmer
11.13
3150861SPRUNCD
Adder
1.399
316458AB2-190 GEN2
Solar/Wind Harmer
3.44
3146206CASHIE
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.237
3145893MURPHYS
Solar/Wind Harmer
-0.034
3146173TUNIS
Solar/Wind Harmer
-0.034
966621AG1-532 GEN
Solar/Wind Harmer
0.682
316478AD1-087 GEN
Solar/Wind Harmer
2.898
970133AG2-095 GEN
Solar/Wind Harmer
3.769
3143336POWHATN
Solar/Wind Harmer
3.367
3146263WOODLND
Solar/Wind Harmer
-0.033
316181AB2-040 GEN
Solar/Wind Harmer
4.624
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
316011AB1-132 GEN
Solar/Wind Harmer
6.909
3145963POPLR C
Solar/Wind Harmer
-0.033
316190AA2-174 GEN
Solar/Wind Harmer
0.403
316317KELFORD C
Solar/Wind Harmer
1.52
3145823KELFORD
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.13
3145796HORNRTN
Solar/Wind Harmer
-0.033
3147043LAWRENC
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.01
3143096IRON208
Adder
1.187
3143096IRON208
Adder
1.163
316212AC1-099_GEN
Solar/Wind Harmer
2.77
3145933PARMELE
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
315722AD1-056 GEN
Solar/Wind Harmer
11.062
3142433PROV 92
Adder
0.529
3142433PROV 92
Adder
0.529
316420AA1-050 GEN
Solar/Wind Harmer
3.471
3146233WITAKRS
Solar/Wind Harmer
0.635
3146233WITAKRS
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.03
3146083TARBORO
Solar/Wind Harmer
-0.03
316075AC2-137 C
Solar/Wind Harmer
0.815
3138543CONSLDL
Solar/Wind Harmer
-0.02
3141843SHACKLE
Adder
1.364
316203AE2-005 GEN
Solar/Wind Harmer
12.646
3141766HARMONY
Solar/Wind Harmer
2.662
970293AG2-193 GEN
Solar/Wind Harmer
3.738
964241AG1-285 GEN
Solar/Wind Harmer
23.354
3141873WAN 176
Solar/Wind Harmer
3.543
961601AG1-000A GEN
Solar/Wind Harmer
11.883
3145543BTLEBRO
Solar/Wind Harmer
-0.03
3145543BTLEBRO
Solar/Wind Harmer
-0.03
970257AG2-171 GEN
Solar/Wind Harmer
11.013
971775AH1-396 GEN
Solar/Wind Harmer
2.072
959311AF2-222 GEN
Solar/Wind Harmer
30.545
3144293JTRSVLE
Adder
0.609
3147133PAMPLIN
Solar/Wind Harmer
-0.089
942461AE2-259 GEN
Solar/Wind Harmer
4.172
3142416OLDCHRC
Solar/Wind Harmer
2.765
3146926FARMVIL
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
2.608
316484AD2-074 GEN
Solar/Wind Harmer
6.678
961951AG1-038 GEN
Solar/Wind Harmer
3.494
316222AC1-221 GEN
Solar/Wind Harmer
2.591
316283AC2-100 C
Solar/Wind Harmer
2.407
3150351NORNECKC2
Adder
2.143
3147666LOUISA
Solar/Wind Helper
0.718
3141196NOKESVL
Solar/Wind Helper
1.043
3132273ORANGE
Solar/Wind Helper
0.048
227287AC2-120 GEN
Solar/Wind Helper
0.314
226910AB2-157 C
Solar/Wind Helper
0.013
971683AH1-343 GEN
Solar/Wind Harmer
0.34
316303AF2-085
50/50
6.61
315244AE2-183_ST
50/50
10.094
963041AG1-153 GEN
50/50
9.284
3151081ELIZAR1
50/50
32.503
3151091ELIZAR2
50/50
31.938
941591AE2-156 GEN
50/50
29.685
315779AE2-040
50/50
4.623
972263AH1-716 GEN
50/50
190.203
970533AG2-339 GEN
Solar/Wind Harmer
27.453
970673AG2-436 GEN
Solar/Wind Harmer
88.282
971967AH1-528 GEN
Solar/Wind Harmer
73.57
316233AE1-074 FULL
Solar/Wind Harmer
1.024
971281AH1-106 GEN
Solar/Wind Harmer
6.184
971283AH1-107 GEN
Solar/Wind Harmer
6.184
316316AC1-027 C
Solar/Wind Harmer
1.149
316018AA1-139 ULT2
Solar/Wind Harmer
3.19
957871AF2-081 GEN
Solar/Wind Harmer
18.67
3146406KITTY HAWK
Solar/Wind Harmer
0.031
970085AG2-068 GEN
Solar/Wind Harmer
23.201
970581AG2-369 GEN
Solar/Wind Harmer
19.953
315814AE2-033 C
Solar/Wind Harmer
34.527
313526AB2-022
Solar/Wind Harmer
0.993
3146486SUNBURY
Solar/Wind Harmer
-0.037
3146486SUNBURY
Solar/Wind Harmer
-0.037
3146396TANGLEW
Solar/Wind Harmer
0.676
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
316311AC2-079 GEN
Solar/Wind Harmer
18.406
315833AF1-017_GEN
Solar/Wind Harmer
6.928
3143316POE
Solar/Wind Harmer
-0.143
316236AE1-162_GEN
Solar/Wind Harmer
1.093
971445AH1-216 GEN
Solar/Wind Harmer
22.456
970657AG2-426 GEN
Solar/Wind Harmer
2.276
315800Z1-036_GEN1
Solar/Wind Harmer
8.837
3130156CHOWAN
Solar/Wind Harmer
-0.036
3130156CHOWAN
Solar/Wind Harmer
-0.036
3151201GRAVEL4
Adder
23.084
3151221GRAVEL6
Adder
23.058
3151191GRAVEL3
Adder
22.792
3151211GRAVEL5
Adder
22.792
315839AE2-212 C
Solar/Wind Harmer
1.045
315697AD1-025 GEN
Solar/Wind Harmer
6.997
3130546PLYMOUTH
Solar/Wind Harmer
-0.034
315732AD1-074 GEN1
Solar/Wind Harmer
6.929
315733AD1-074 GEN2
Solar/Wind Harmer
6.929
971285AH1-108 GEN
Adder
2.29
3146206CASHIE
Solar/Wind Harmer
-0.034
970601AG2-382 GEN
Solar/Wind Harmer
14.893
316318V4-068
Solar/Wind Harmer
0.846
3145893MURPHYS
Solar/Wind Harmer
-0.091
3145893MURPHYS
Solar/Wind Harmer
-0.034
316382AG1-145 C
Solar/Wind Harmer
1.017
316159AE1-175 C
Solar/Wind Harmer
0.905
946281AF1-292 GEN
Solar/Wind Harmer
0.752
316486AD2-202 GEN
Solar/Wind Harmer
0.849
316463AE2-346 GEN
Solar/Wind Harmer
0.541
3145513AHOSKIE
Solar/Wind Harmer
0.292
961941AG1-037 GEN
Solar/Wind Harmer
0.252
3145513AHOSKIE
Solar/Wind Harmer
-0.033
3146043SEABORD
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.066
3145683EARLEYS
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.033
316258AE1-075 C
Solar/Wind Harmer
0.808
316405AF2-144 C
Solar/Wind Harmer
0.853
315652AC1-086 GEN
Solar/Wind Harmer
37.214
3137643SOCKMAN
Solar/Wind Harmer
-0.131
316426AA2-053 GEN
Solar/Wind Harmer
3.314
316174AB2-169 GEN
Solar/Wind Harmer
5.028
3145796HORNRTN
Solar/Wind Harmer
-0.104
3145796HORNRTN
Solar/Wind Harmer
-0.013
957831AF2-077 GEN
Solar/Wind Harmer
0.978
3138283WHITEMARSH
Solar/Wind Harmer
0.05
3146033SCOT NK
Solar/Wind Harmer
-0.128
316210AC1-098 GEN
Solar/Wind Harmer
4.985
970831AG2-522 GEN
Solar/Wind Harmer
15.835
316274AC1-208 GEN
Solar/Wind Harmer
3.405
3145746EVERETS
Solar/Wind Harmer
-0.123
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
316327AA2-057 GEN
Solar/Wind Harmer
3.105
957861AF2-080 GEN
Solar/Wind Harmer
13.42
3142433PROV 92
Adder
0.529
3142433PROV 92
Adder
0.529
3145573BETHELC
Solar/Wind Harmer
-0.03
3145573BETHELC
Solar/Wind Harmer
-0.03
3143873LANEXA
Solar/Wind Harmer
-0.018
316238AB2-078_GEN
Solar/Wind Harmer
0.906
316239AB2-077_GEN
Solar/Wind Harmer
0.906
316059AD1-063 C
Solar/Wind Harmer
0.674
957601AF2-054 GEN
Solar/Wind Harmer
0.893
3141873WAN 176
Solar/Wind Harmer
-0.006
3144303KENBRDG
Solar/Wind Harmer
-0.023
970683AG2-441 GEN
Solar/Wind Harmer
20.486
970681AG2-440 GEN
Solar/Wind Harmer
13.597
3141913WHIT STONE
Solar/Wind Harmer
-0.029
3138133OCRAN
Solar/Wind Harmer
-0.009
946301AF1-294 GEN
Solar/Wind Harmer
7.345
961791AG1-021 GEN
Solar/Wind Harmer
3.583
3141783LANCAST
Solar/Wind Harmer
-0.017
3141783LANCAST
Solar/Wind Harmer
-0.011
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
7.897
316164AC1-076 GEN
Solar/Wind Helper
1.502
315651AD1-115 GEN
Solar/Wind Helper
0.946
3138216PACIFIC
Solar/Wind Helper
0.04
226929AD2-058 GEN
Solar/Wind Helper
0.092
958261AF2-120 GEN
Solar/Wind Harmer
9.894
3150351NORNECKC2
Adder
2.108
316447AC1-158 HLD
Solar/Wind Helper
4.832
316044AC1-158 PL1
Solar/Wind Helper
2.196
3147666LOUISA
Solar/Wind Helper
1.248
316192AB2-158 GEN
Solar/Wind Helper
2.059
316415AF1-147_GEN2
Solar/Wind Helper
0.815
CPLELTFEXP_CPLE->PJM
CLTF
17.484
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.229
LAGNLTFEXP_LAGN->PJM
CLTF
12.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
38.177
TVALTFEXP_TVA->PJM
CLTF
6.362
NYPJM->LTFIMP_NY
CLTF
3.638
LGEELTFEXP_LGEE->PJM
CLTF
2.305
WECLTFEXP_WEC->PJM
CLTF
1.169
AG2-052LTFEXP_AG2-052->PJM
LTF
0.062
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094
CBM West 1LTFEXP_CBM-W1->PJM
CBM
40.68
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.857
MECLTFEXP_MEC->PJM
CLTF
6.239
SIGELTFEXP_SIGE->PJM
CLTF
0.189

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.72 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5938.23
MW Contribution:
170.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
5.543
315241AE2-183_GT1
50/50
5.529
972185AH1-677 GEN
50/50
20.038
3151041BRUNSWICKG3
50/50
4.374
972187AH1-678 GEN
50/50
10.037
3150991CHESPKB
50/50
3.413
3150991CHESPKB
50/50
3.331
971223AH1-071 GEN
Solar/Wind Harmer
5.194
3143526WINTERP
Solar/Wind Harmer
-0.196
970933AG2-581 GEN
Solar/Wind Harmer
34.16
3144356SAPONY
Solar/Wind Harmer
1.241
316315AB2-025 C
Solar/Wind Harmer
0.957
316294AC1-161 GEN
Solar/Wind Harmer
11.288
316185AD1-033 GEN
Solar/Wind Harmer
3.636
3145506HICKORY
Solar/Wind Harmer
-0.137
3145506HICKORY
Solar/Wind Harmer
-0.082
3145506HICKORY
Solar/Wind Harmer
-0.02
316339AD2-160 GEN
Solar/Wind Harmer
2.314
316388AE2-253 GEN
Solar/Wind Harmer
2.314
3137176SLIGO L2192
Solar/Wind Harmer
-0.136
3146456SLIGO L269
Solar/Wind Harmer
4.054
3130086AYDLETT
Solar/Wind Harmer
-0.136
316083AB2-161 GEN
Solar/Wind Harmer
5.529
316349AD2-085 GEN
Solar/Wind Harmer
3.024
3146386ELIZ CT
Solar/Wind Harmer
-0.034
315835AF2-110_GEN
Solar/Wind Harmer
4.257
316431W1029_GEN1
Solar/Wind Harmer
6.117
316433W1029_GEN2
Solar/Wind Harmer
6.117
316435W1029_GEN3
Solar/Wind Harmer
6.117
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
970099AG2-077 GEN
Solar/Wind Harmer
41.967
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.033
316313AB2-026
Solar/Wind Harmer
0.895
315742AE1-103 GEN
Solar/Wind Harmer
7.88
3146376EDENTON
Solar/Wind Harmer
0.98
3146376EDENTON
Solar/Wind Harmer
0.98
316365GEN2_N
Solar/Wind Harmer
2.206
316240AF1-291 C
Solar/Wind Harmer
0.986
316033AB2-134 GEN
Solar/Wind Harmer
10.493
315614AA2-178 GEN
Solar/Wind Harmer
3.498
944641AF1-129 GEN
Adder
137.874
316065AD1-022 GEN
Solar/Wind Harmer
15.946
3145893MURPHYS
Solar/Wind Harmer
0.889
3145893MURPHYS
Solar/Wind Harmer
-0.057
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
313506AB2-031 GEN
Solar/Wind Harmer
2.528
316140AB2-099
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
962571AG1-106 GEN
Solar/Wind Harmer
4.507
316336AC2-165 C
Solar/Wind Harmer
19.415
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
0.258
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145783HORNRTN
Solar/Wind Harmer
3.664
3145783HORNRTN
Solar/Wind Harmer
2.932
3145783HORNRTN
Solar/Wind Harmer
0.916
3145783HORNRTN
Solar/Wind Harmer
0.366
315687AD1-152 GEN
Solar/Wind Harmer
3.633
3142946ENON
Solar/Wind Harmer
-0.003
3145933PARMELE
Solar/Wind Harmer
-0.059
3145933PARMELE
Solar/Wind Harmer
-0.03
315724AD1-057 GEN
Solar/Wind Harmer
5.773
316005AA1-067
Solar/Wind Harmer
0.592
3142366NRTHEST
Adder
0.851
3150691DARBY 3
Adder
18.637
3150701DARBY 4
Adder
18.594
3150681DARBY 2
Adder
18.572
3150671DARBY 1
Adder
18.55
313527AB2-043 GEN
Solar/Wind Harmer
4.703
970301AG2-198 GEN
Solar/Wind Harmer
14.468
316237AB2-079_GEN
Solar/Wind Harmer
0.87
3145493TOT1
Solar/Wind Harmer
0.444
3145453TOT5
Solar/Wind Harmer
0.266
3145603CNETO
Solar/Wind Harmer
0.178
315976AC1-164 GENA
Solar/Wind Harmer
6.489
316169AC1-164_GENC
Solar/Wind Harmer
5.606
961601AG1-000A GEN
Solar/Wind Harmer
11.141
316049AB1-081 GEN
Solar/Wind Harmer
3.048
316263AC1-034 GEN
Solar/Wind Harmer
13.281
970323AG2-213 GEN
Solar/Wind Harmer
14.146
962561AG1-105 GEN
Solar/Wind Harmer
15.735
964791AG1-342 GEN
Solar/Wind Harmer
5.937
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
958211AF2-115 GEN
Solar/Wind Harmer
4.33
3144293JTRSVLE
Adder
0.589
3147133PAMPLIN
Solar/Wind Harmer
-0.027
3147133PAMPLIN
Solar/Wind Harmer
-0.022
316441AF1-014 GEN
Solar/Wind Harmer
1.846
316118AC1-105 GEN
Solar/Wind Harmer
1.877
315666AE1-190 GEN
Solar/Wind Harmer
0.82
316312AB1-027
Solar/Wind Harmer
0.914
316156AD2-030 GEN
Solar/Wind Harmer
0.723
316248AF1-058 C
Solar/Wind Harmer
0.81
3142296MT RD221
Adder
0.759
966871AG1-558 GEN
Solar/Wind Harmer
0.744
966871AG1-558 GEN
Solar/Wind Harmer
0.255
316487AF1-042 GEN
Solar/Wind Harmer
3.168
3150341NORNECKC1
Adder
2
3150341NORNECKC1
Adder
1.984
972189AH1-679 GEN
Adder
2.537
972193AH1-681 GEN
Adder
2.89
316045AC1-158 PL2
Solar/Wind Helper
7.048
316450AC1-158 RIC
Solar/Wind Helper
0.587
316006AB2-029 C
Solar/Wind Helper
0.13
316411AF1-147_GEN1
Solar/Wind Helper
0.81
3151031BRUNSWICKG2
50/50
4.374
3151101ELIZAR3
50/50
30.285
3150861SPRUNCD
50/50
1.47
3151161SURRY 1
50/50
11.996
944011AF1-069 GEN
Solar/Wind Harmer
22.864
970917AG2-570 GEN
Solar/Wind Harmer
89.768
944581AF1-123 GEN
Solar/Wind Harmer
158.16
944601AF1-125 GEN
Solar/Wind Harmer
155.692
3142956BIRDNECK
Solar/Wind Harmer
1.852
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
2.775
3146456SLIGO L269
Solar/Wind Harmer
-0.034
971153AH1-033 GEN
Solar/Wind Harmer
3.973
3144536CHRHLND
Solar/Wind Harmer
-0.005
316305AF2-043 C
Solar/Wind Harmer
1.029
316246AF1-032 C
Solar/Wind Harmer
0.691
315813AE1-149 C
Solar/Wind Harmer
21.315
970657AG2-426 GEN
Solar/Wind Harmer
6.885
316320Y1-086
Solar/Wind Harmer
1.994
316321Z2-027
Solar/Wind Harmer
0.913
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.025
3143336POWHATN
Solar/Wind Harmer
3.355
3151171GRAVELC
Adder
4.119
3146376EDENTON
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
6.926
315778AD1-151 GEN
Solar/Wind Harmer
28.895
316458AB2-190 GEN2
Solar/Wind Harmer
3.257
3156081AA2-088 GEN
Solar/Wind Harmer
10.435
316478AD1-087 GEN
Solar/Wind Harmer
2.776
315735AD1-075 GEN1
Solar/Wind Harmer
3.231
970133AG2-095 GEN
Solar/Wind Harmer
3.597
966621AG1-532 GEN
Solar/Wind Harmer
0.649
3144216WINCHST
Adder
1.072
3145893MURPHYS
Solar/Wind Harmer
0.222
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
3150921YORKTN3
Adder
7.099
3146173TUNIS
Solar/Wind Harmer
-0.032
316181AB2-040 GEN
Solar/Wind Harmer
4.391
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
316011AB1-132 GEN
Solar/Wind Harmer
6.548
3146263WOODLND
Solar/Wind Harmer
-0.031
316190AA2-174 GEN
Solar/Wind Harmer
0.382
3147043LAWRENC
Solar/Wind Harmer
-0.018
3143096IRON208
Adder
1.153
3143096IRON208
Adder
1.13
316317KELFORD C
Solar/Wind Harmer
1.431
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316212AC1-099_GEN
Solar/Wind Harmer
2.618
3142946ENON
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.03
315722AD1-056 GEN
Solar/Wind Harmer
10.496
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316420AA1-050 GEN
Solar/Wind Harmer
3.284
970293AG2-193 GEN
Solar/Wind Harmer
3.598
3146233WITAKRS
Solar/Wind Harmer
0.602
3146233WITAKRS
Solar/Wind Harmer
-0.019
3138543CONSLDL
Solar/Wind Harmer
-0.019
964241AG1-285 GEN
Solar/Wind Harmer
22.443
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
316075AC2-137 C
Solar/Wind Harmer
0.765
961601AG1-000A GEN
Solar/Wind Harmer
11.282
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.028
970257AG2-171 GEN
Solar/Wind Harmer
10.61
971775AH1-396 GEN
Solar/Wind Harmer
1.996
959311AF2-222 GEN
Solar/Wind Harmer
29.441
3144293JTRSVLE
Adder
0.589
3147133PAMPLIN
Solar/Wind Harmer
-0.086
3141843SHACKLE
Adder
1.246
316203AE2-005 GEN
Solar/Wind Harmer
11.547
3141766HARMONY
Solar/Wind Harmer
2.421
3142416OLDCHRC
Solar/Wind Harmer
2.743
3141873WAN 176
Solar/Wind Harmer
3.223
942461AE2-259 GEN
Solar/Wind Harmer
4.052
3146926FARMVIL
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
2.51
316473AC1-191 GEN
Solar/Wind Harmer
2.663
316222AC1-221 GEN
Solar/Wind Harmer
2.488
316283AC2-100 C
Solar/Wind Harmer
2.311
971683AH1-343 GEN
Solar/Wind Harmer
10.53
316484AD2-074 GEN
Solar/Wind Harmer
6.055
961951AG1-038 GEN
Solar/Wind Harmer
3.168
3150351NORNECKC2
Adder
1.936
972255AH1-712 GEN
Adder
64.681
3147666LOUISA
Solar/Wind Helper
0.715
3141196NOKESVL
Solar/Wind Helper
1.038
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.312
226910AB2-157 C
Solar/Wind Helper
0.013
316303AF2-085
50/50
6.575
315244AE2-183_ST
50/50
9.626
963041AG1-153 GEN
50/50
8.856
315779AE2-040
50/50
4.419
3151081ELIZAR1
50/50
29.902
3151091ELIZAR2
50/50
29.383
941591AE2-156 GEN
50/50
27.314
971285AH1-108 GEN
50/50
2.405
972263AH1-716 GEN
50/50
170.337
970533AG2-339 GEN
Solar/Wind Harmer
26.171
970673AG2-436 GEN
Solar/Wind Harmer
84.171
316233AE1-074 FULL
Solar/Wind Harmer
1.018
971281AH1-106 GEN
Solar/Wind Harmer
6.15
971283AH1-107 GEN
Solar/Wind Harmer
6.15
971967AH1-528 GEN
Solar/Wind Harmer
70.201
315814AE2-033 C
Solar/Wind Harmer
32.994
970085AG2-068 GEN
Solar/Wind Harmer
22.141
970581AG2-369 GEN
Solar/Wind Harmer
19.041
3143316POE
Solar/Wind Harmer
-0.138
316316AC1-027 C
Solar/Wind Harmer
1.058
316018AA1-139 ULT2
Solar/Wind Harmer
2.938
957871AF2-081 GEN
Solar/Wind Harmer
17.192
3146406KITTY HAWK
Solar/Wind Harmer
0.028
970657AG2-426 GEN
Solar/Wind Harmer
2.149
315833AF1-017_GEN
Solar/Wind Harmer
6.469
316311AC2-079 GEN
Solar/Wind Harmer
17.182
313526AB2-022
Solar/Wind Harmer
0.916
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146396TANGLEW
Solar/Wind Harmer
0.624
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
315839AE2-212 C
Solar/Wind Harmer
1.012
316236AE1-162_GEN
Solar/Wind Harmer
1.011
971445AH1-216 GEN
Solar/Wind Harmer
20.783
316258AE1-075 C
Solar/Wind Harmer
0.805
316405AF2-144 C
Solar/Wind Harmer
0.85
315800Z1-036_GEN1
Solar/Wind Harmer
8.192
3151201GRAVEL4
Adder
21.435
3151221GRAVEL6
Adder
21.41
3151191GRAVEL3
Adder
21.164
3151211GRAVEL5
Adder
21.164
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
315697AD1-025 GEN
Solar/Wind Harmer
6.576
316486AD2-202 GEN
Solar/Wind Harmer
0.813
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
315732AD1-074 GEN1
Solar/Wind Harmer
6.463
315733AD1-074 GEN2
Solar/Wind Harmer
6.463
946281AF1-292 GEN
Solar/Wind Harmer
0.716
316318V4-068
Solar/Wind Harmer
0.794
3145893MURPHYS
Solar/Wind Harmer
-0.085
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
13.919
3146043SEABORD
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.508
3145513AHOSKIE
Solar/Wind Harmer
0.275
961941AG1-037 GEN
Solar/Wind Harmer
0.237
3145513AHOSKIE
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.062
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
35.27
3137643SOCKMAN
Solar/Wind Harmer
-0.124
316426AA2-053 GEN
Solar/Wind Harmer
3.134
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.012
316382AG1-145 C
Solar/Wind Harmer
0.921
316159AE1-175 C
Solar/Wind Harmer
0.82
316174AB2-169 GEN
Solar/Wind Harmer
4.716
3146033SCOT NK
Solar/Wind Harmer
-0.121
970831AG2-522 GEN
Solar/Wind Harmer
15.081
316210AC1-098 GEN
Solar/Wind Harmer
4.713
316274AC1-208 GEN
Solar/Wind Harmer
3.223
957831AF2-077 GEN
Solar/Wind Harmer
0.889
3138283WHITEMARSH
Solar/Wind Harmer
0.046
3145746EVERETS
Solar/Wind Harmer
-0.116
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316327AA2-057 GEN
Solar/Wind Harmer
2.943
957861AF2-080 GEN
Solar/Wind Harmer
12.684
316238AB2-078_GEN
Solar/Wind Harmer
0.87
316239AB2-077_GEN
Solar/Wind Harmer
0.87
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
3144303KENBRDG
Solar/Wind Harmer
-0.023
970683AG2-441 GEN
Solar/Wind Harmer
19.77
970681AG2-440 GEN
Solar/Wind Harmer
13.122
946301AF1-294 GEN
Solar/Wind Harmer
7.101
961791AG1-021 GEN
Solar/Wind Harmer
3.464
3143873LANEXA
Solar/Wind Harmer
-0.016
316059AD1-063 C
Solar/Wind Harmer
0.613
957601AF2-054 GEN
Solar/Wind Harmer
0.812
3141873WAN 176
Solar/Wind Harmer
-0.005
3147173SINAI
Solar/Wind Harmer
-0.027
3147243WELCO
Solar/Wind Harmer
-0.017
3141913WHIT STONE
Solar/Wind Harmer
-0.026
3138133OCRAN
Solar/Wind Harmer
-0.008
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
972205AH1-687 GEN
Adder
7.911
316164AC1-076 GEN
Solar/Wind Helper
1.499
315651AD1-115 GEN
Solar/Wind Helper
0.941
3138216PACIFIC
Solar/Wind Helper
0.039
226929AD2-058 GEN
Solar/Wind Helper
0.091
971845AH1-439 GEN
Solar/Wind Harmer
9.322
970119AG2-088 GEN
50/50
49.309
315243AE2-183_GT3
50/50
5.543
3151051BRUNSWICKS1
50/50
9.081
3151021BRUNSWICKG1
50/50
4.374
971451AH1-221 GEN
50/50
13.284
3150981CHESPKA
50/50
4.068
3150851SPRUNCC
50/50
1.47
3152331SURRY 2
50/50
12.162
3143226MDLTHAN
Solar/Wind Harmer
-0.041
940641AE2-051 GEN
Solar/Wind Harmer
36.935
941031AE2-094 GEN
Solar/Wind Harmer
72.971
939411AE1-173 GEN
Solar/Wind Harmer
190.948
3143526WINTERP
Solar/Wind Harmer
-0.196
970919AG2-571 GEN
Solar/Wind Harmer
11.363
970087AG2-069 GEN
Solar/Wind Harmer
33.211
315773AC2-141 GEN
Solar/Wind Harmer
14.605
944591AF1-124 GEN
Solar/Wind Harmer
158.73
316375AC2-012 GEN
Solar/Wind Harmer
11.93
316036AC1-147 C
Solar/Wind Harmer
0.928
3146456SLIGO L269
Solar/Wind Harmer
-0.034
319010AE1-072 C
Solar/Wind Harmer
6.925
316381AD1-082 GEN
Solar/Wind Harmer
3.118
316093AE2-104_GEN
Solar/Wind Harmer
9.901
316072AD1-144
Solar/Wind Harmer
0.683
3146516WINFALL
Solar/Wind Harmer
-0.109
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.134
957481AF2-042 GEN
Solar/Wind Harmer
104.919
3143336POWHATN
Solar/Wind Harmer
3.948
315611Z1-036_GEN2
Solar/Wind Harmer
8.192
3151171GRAVELC
Adder
3.133
3130156CHOWAN
Solar/Wind Harmer
-0.033
315671AE2-027_GEN
Solar/Wind Harmer
5.94
961611AG1-000B GEN
Solar/Wind Harmer
16.233
316023GEN1_S
Solar/Wind Harmer
2.206
316369SG1_INVT
Solar/Wind Harmer
5.811
315816AE2-034 GEN
Solar/Wind Harmer
2.624
3145663CRESWEL
Solar/Wind Harmer
-0.091
971163AH1-040 GEN
Solar/Wind Harmer
30.48
315693AD1-088 GEN
Solar/Wind Harmer
16.234
971069AG2-661 GEN
Solar/Wind Harmer
5.137
316132AB2-190 GEN1
Solar/Wind Harmer
3.257
315737AD1-076 GEN
Solar/Wind Harmer
6.076
960081AF2-299 GEN
Solar/Wind Harmer
3.596
3138126ROCKLANDING
Solar/Wind Harmer
0.098
3145893MURPHYS
Solar/Wind Harmer
-0.127
3145893MURPHYS
Solar/Wind Harmer
0.945
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
7.954
3142543TWELFTH
Solar/Wind Harmer
-0.003
316087AB2-174 GEN
Solar/Wind Harmer
4.509
3146173TUNIS
Solar/Wind Harmer
-0.032
3156021HOLLOMANSOL
Solar/Wind Harmer
4.234
315607AA1-063A GEN
Solar/Wind Harmer
3.169
3145683EARLEYS
Solar/Wind Harmer
-0.031
3146263WOODLND
Solar/Wind Harmer
-0.031
3147043LAWRENC
Adder
2.5
971317AH1-138 GEN
Solar/Wind Harmer
3.867
3143096IRON208
Adder
1.153
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
944631AF1-128 GEN
Adder
129.362
316129AC1-054 GEN
Solar/Wind Harmer
2.627
971065AG2-659 GEN
Solar/Wind Harmer
14.977
3146293MARTNCO
Solar/Wind Harmer
0.185
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316494AC1-189 GEN
Solar/Wind Harmer
3.119
316131AB2-060 GEN
Solar/Wind Harmer
3.111
316319Z2-044 C
Solar/Wind Harmer
1.589
3146233WITAKRS
Solar/Wind Harmer
-0.114
961671AG1-007 GEN
Solar/Wind Harmer
0.363
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.851
315975AC1-164 GENB
Solar/Wind Harmer
0.192
3142433PROV 92
Solar/Wind Harmer
-0.114
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
315785AD2-033 C
Solar/Wind Harmer
6.428
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.023
316359AB2-059 GEN
Solar/Wind Harmer
3.81
3142053HEARTS
Solar/Wind Harmer
0.333
316034AC1-036 C
Solar/Wind Harmer
0.523
970685AG2-442 GEN
Solar/Wind Harmer
24.381
970401AG2-262 GEN
Solar/Wind Harmer
1.814
971563AH1-280 GEN
Solar/Wind Harmer
3.464
3144293JTRSVLE
Adder
0.589
3144293JTRSVLE
Adder
0.465
971777AH1-397 GEN
Solar/Wind Harmer
3.196
315662AE1-191 GEN
Solar/Wind Harmer
3.282
316280AD1-041 GEN
Solar/Wind Harmer
2.051
316314AB2-024 C
Solar/Wind Harmer
2.326
3141766HARMONY
Solar/Wind Harmer
-0.005
3142416OLDCHRC
Solar/Wind Harmer
-0.07
3142416OLDCHRC
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.016
3138133OCRAN
Solar/Wind Harmer
-0.015
970937AG2-583 GEN
Solar/Wind Harmer
18.345
3150351NORNECKC2
Adder
1.904
972277AH1-723 GEN
Adder
75.373
316447AC1-158 HLD
Solar/Wind Helper
4.846
316044AC1-158 PL1
Solar/Wind Helper
2.202
3147666LOUISA
Solar/Wind Helper
1.244
316192AB2-158 GEN
Solar/Wind Helper
2.051
316415AF1-147_GEN2
Solar/Wind Helper
0.81
CPLELTFEXP_CPLE->PJM
CLTF
16.773
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.431
LAGNLTFEXP_LAGN->PJM
CLTF
12.423
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.843
TVALTFEXP_TVA->PJM
CLTF
6.252
NYPJM->LTFIMP_NY
CLTF
3.575
LGEELTFEXP_LGEE->PJM
CLTF
2.318
WECLTFEXP_WEC->PJM
CLTF
1.177
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.037
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.531
MECLTFEXP_MEC->PJM
CLTF
6.227
SIGELTFEXP_SIGE->PJM
CLTF
0.189

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.04 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5123.57
MW Contribution:
156.36
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.955
315244AE2-183_ST
50/50
8.732
963041AG1-153 GEN
50/50
8.032
315779AE2-040
50/50
4.022
3151081ELIZAR1
50/50
27.347
3151091ELIZAR2
50/50
26.872
941591AE2-156 GEN
50/50
24.98
971285AH1-108 GEN
50/50
2.2
972263AH1-716 GEN
50/50
156.362
970533AG2-339 GEN
Solar/Wind Harmer
23.743
970673AG2-436 GEN
Solar/Wind Harmer
76.358
316233AE1-074 FULL
Solar/Wind Harmer
0.926
971281AH1-106 GEN
Solar/Wind Harmer
5.595
971283AH1-107 GEN
Solar/Wind Harmer
5.595
971967AH1-528 GEN
Solar/Wind Harmer
63.649
315814AE2-033 C
Solar/Wind Harmer
30.033
970085AG2-068 GEN
Solar/Wind Harmer
20.08
970581AG2-369 GEN
Solar/Wind Harmer
17.269
3143316POE
Solar/Wind Harmer
-0.126
316316AC1-027 C
Solar/Wind Harmer
0.967
316018AA1-139 ULT2
Solar/Wind Harmer
2.686
957871AF2-081 GEN
Solar/Wind Harmer
15.716
3146406KITTY HAWK
Solar/Wind Harmer
0.026
970657AG2-426 GEN
Solar/Wind Harmer
1.965
315833AF1-017_GEN
Solar/Wind Harmer
5.913
316311AC2-079 GEN
Solar/Wind Harmer
15.706
313526AB2-022
Solar/Wind Harmer
0.837
3146486SUNBURY
Solar/Wind Harmer
-0.031
3146486SUNBURY
Solar/Wind Harmer
-0.031
3146396TANGLEW
Solar/Wind Harmer
0.571
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
315839AE2-212 C
Solar/Wind Harmer
0.926
316236AE1-162_GEN
Solar/Wind Harmer
0.926
971445AH1-216 GEN
Solar/Wind Harmer
19.038
3151201GRAVEL4
Adder
19.652
3151221GRAVEL6
Adder
19.63
3151191GRAVEL3
Adder
19.404
3151211GRAVEL5
Adder
19.404
315800Z1-036_GEN1
Solar/Wind Harmer
7.481
3130156CHOWAN
Solar/Wind Harmer
-0.03
3130156CHOWAN
Solar/Wind Harmer
-0.03
315697AD1-025 GEN
Solar/Wind Harmer
6.034
316258AE1-075 C
Solar/Wind Harmer
0.722
970119AG2-088 GEN
50/50
44.663
315243AE2-183_GT3
50/50
5.028
3151051BRUNSWICKS1
50/50
8.237
3151021BRUNSWICKG1
50/50
3.967
316405AF2-144 C
Solar/Wind Harmer
0.762
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
315732AD1-074 GEN1
Solar/Wind Harmer
5.895
315733AD1-074 GEN2
Solar/Wind Harmer
5.895
316486AD2-202 GEN
Solar/Wind Harmer
0.735
946281AF1-292 GEN
Solar/Wind Harmer
0.651
316318V4-068
Solar/Wind Harmer
0.723
3145893MURPHYS
Solar/Wind Harmer
-0.078
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.691
316463AE2-346 GEN
Solar/Wind Harmer
0.463
3145513AHOSKIE
Solar/Wind Harmer
0.25
961941AG1-037 GEN
Solar/Wind Harmer
0.216
3145513AHOSKIE
Solar/Wind Harmer
-0.029
3146043SEABORD
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.057
3145683EARLEYS
Solar/Wind Harmer
-0.028
3145683EARLEYS
Solar/Wind Harmer
-0.028
315652AC1-086 GEN
Solar/Wind Harmer
32.088
3137643SOCKMAN
Solar/Wind Harmer
-0.113
316426AA2-053 GEN
Solar/Wind Harmer
2.85
316382AG1-145 C
Solar/Wind Harmer
0.85
316159AE1-175 C
Solar/Wind Harmer
0.756
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
4.296
3146033SCOT NK
Solar/Wind Harmer
-0.11
316210AC1-098 GEN
Solar/Wind Harmer
4.287
957831AF2-077 GEN
Solar/Wind Harmer
0.823
3138283WHITEMARSH
Solar/Wind Harmer
0.042
970831AG2-522 GEN
Solar/Wind Harmer
13.676
316274AC1-208 GEN
Solar/Wind Harmer
2.931
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316327AA2-057 GEN
Solar/Wind Harmer
2.675
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
957861AF2-080 GEN
Solar/Wind Harmer
11.537
316238AB2-078_GEN
Solar/Wind Harmer
0.785
316239AB2-077_GEN
Solar/Wind Harmer
0.785
3145573BETHELC
Solar/Wind Harmer
-0.026
3145573BETHELC
Solar/Wind Harmer
-0.026
3143873LANEXA
Solar/Wind Harmer
-0.015
3144303KENBRDG
Solar/Wind Harmer
-0.02
316059AD1-063 C
Solar/Wind Harmer
0.572
957601AF2-054 GEN
Solar/Wind Harmer
0.758
3141873WAN 176
Solar/Wind Harmer
-0.005
970683AG2-441 GEN
Solar/Wind Harmer
17.766
970681AG2-440 GEN
Solar/Wind Harmer
11.792
946301AF1-294 GEN
Solar/Wind Harmer
6.371
961791AG1-021 GEN
Solar/Wind Harmer
3.108
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.014
3141783LANCAST
Solar/Wind Harmer
-0.01
972205AH1-687 GEN
Adder
6.884
316164AC1-076 GEN
Solar/Wind Helper
1.634
315651AD1-115 GEN
Solar/Wind Helper
1.021
971451AH1-221 GEN
50/50
12.048
3150981CHESPKA
50/50
3.72
3150851SPRUNCC
50/50
1.345
3152331SURRY 2
50/50
11.159
3143226MDLTHAN
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
33.561
941031AE2-094 GEN
Solar/Wind Harmer
66.202
939411AE1-173 GEN
Solar/Wind Harmer
173.75
3143526WINTERP
Solar/Wind Harmer
-0.178
970919AG2-571 GEN
Solar/Wind Harmer
10.306
970087AG2-069 GEN
Solar/Wind Harmer
30.12
315773AC2-141 GEN
Solar/Wind Harmer
13.36
944591AF1-124 GEN
Solar/Wind Harmer
145.122
316375AC2-012 GEN
Solar/Wind Harmer
10.911
316036AC1-147 C
Solar/Wind Harmer
0.849
3146456SLIGO L269
Solar/Wind Harmer
-0.031
319010AE1-072 C
Solar/Wind Harmer
6.33
316381AD1-082 GEN
Solar/Wind Harmer
2.851
316093AE2-104_GEN
Solar/Wind Harmer
9.05
316072AD1-144
Solar/Wind Harmer
0.625
3145336SMITFLD
Solar/Wind Harmer
-0.123
3146516WINFALL
Solar/Wind Harmer
-0.099
3146516WINFALL
Solar/Wind Harmer
-0.031
957481AF2-042 GEN
Solar/Wind Harmer
94.939
3151171GRAVELC
Adder
2.872
315611Z1-036_GEN2
Solar/Wind Harmer
7.481
3130156CHOWAN
Solar/Wind Harmer
-0.03
315671AE2-027_GEN
Solar/Wind Harmer
5.444
961611AG1-000B GEN
Solar/Wind Harmer
14.887
316369SG1_INVT
Solar/Wind Harmer
5.332
316023GEN1_S
Solar/Wind Harmer
2.007
3143336POWHATN
Solar/Wind Harmer
3.541
971069AG2-661 GEN
Solar/Wind Harmer
4.714
315816AE2-034 GEN
Solar/Wind Harmer
2.394
3145663CRESWEL
Solar/Wind Harmer
-0.083
971163AH1-040 GEN
Solar/Wind Harmer
27.815
316132AB2-190 GEN1
Solar/Wind Harmer
2.99
315693AD1-088 GEN
Solar/Wind Harmer
14.666
3138126ROCKLANDING
Solar/Wind Harmer
0.09
315737AD1-076 GEN
Solar/Wind Harmer
5.542
3142543TWELFTH
Solar/Wind Harmer
-0.003
960081AF2-299 GEN
Solar/Wind Harmer
3.268
3145893MURPHYS
Solar/Wind Harmer
-0.116
3145893MURPHYS
Solar/Wind Harmer
0.861
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.252
3146173TUNIS
Solar/Wind Harmer
-0.029
316087AB2-174 GEN
Solar/Wind Harmer
4.098
3156021HOLLOMANSOL
Solar/Wind Harmer
3.859
315607AA1-063A GEN
Solar/Wind Harmer
2.884
3145683EARLEYS
Solar/Wind Harmer
-0.028
971317AH1-138 GEN
Solar/Wind Harmer
3.567
3146263WOODLND
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.061
3147043LAWRENC
Adder
2.268
3145823KELFORD
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
119.22
3145783HORNRTN
Solar/Wind Harmer
-0.028
316129AC1-054 GEN
Solar/Wind Harmer
2.381
971065AG2-659 GEN
Solar/Wind Harmer
13.573
3146293MARTNCO
Solar/Wind Harmer
0.168
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
315975AC1-164 GENB
Solar/Wind Harmer
0.178
316494AC1-189 GEN
Solar/Wind Harmer
2.837
316319Z2-044 C
Solar/Wind Harmer
1.445
3146233WITAKRS
Solar/Wind Harmer
-0.103
316131AB2-060 GEN
Solar/Wind Harmer
2.809
961671AG1-007 GEN
Solar/Wind Harmer
0.33
3146083TARBORO
Solar/Wind Harmer
-0.026
3145493TOT1
Solar/Wind Harmer
0.774
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
316359AB2-059 GEN
Solar/Wind Harmer
3.462
3142053HEARTS
Solar/Wind Harmer
0.303
315785AD2-033 C
Solar/Wind Harmer
5.788
971777AH1-397 GEN
Solar/Wind Harmer
2.979
316034AC1-036 C
Solar/Wind Harmer
0.471
315662AE1-191 GEN
Solar/Wind Harmer
3.06
316280AD1-041 GEN
Solar/Wind Harmer
1.912
316314AB2-024 C
Solar/Wind Harmer
2.168
3141766HARMONY
Solar/Wind Harmer
-0.005
3142416OLDCHRC
Solar/Wind Harmer
-0.065
3142416OLDCHRC
Solar/Wind Harmer
-0.025
970401AG2-262 GEN
Solar/Wind Harmer
1.639
970685AG2-442 GEN
Solar/Wind Harmer
21.894
971563AH1-280 GEN
Solar/Wind Harmer
3.108
3144293JTRSVLE
Adder
0.528
3144293JTRSVLE
Adder
0.417
3138133OCRAN
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.014
970937AG2-583 GEN
Solar/Wind Harmer
16.205
962861AG1-135 GEN
Solar/Wind Harmer
8.312
3150351NORNECKC2
Adder
1.825
972277AH1-723 GEN
Adder
69.685
316447AC1-158 HLD
Solar/Wind Helper
6.065
316044AC1-158 PL1
Solar/Wind Helper
2.756
3147666LOUISA
Solar/Wind Helper
1.719
316192AB2-158 GEN
Solar/Wind Helper
2.833
316404AE1-155 C
Solar/Wind Harmer
0.278
315242AE2-183_GT2
50/50
5.028
315241AE2-183_GT1
50/50
5.015
972185AH1-677 GEN
50/50
18.176
3151041BRUNSWICKG3
50/50
3.967
972187AH1-678 GEN
50/50
9.103
3150991CHESPKB
50/50
3.121
3150991CHESPKB
50/50
3.046
971223AH1-071 GEN
Solar/Wind Harmer
4.704
3143526WINTERP
Solar/Wind Harmer
-0.178
970933AG2-581 GEN
Solar/Wind Harmer
30.957
3144356SAPONY
Solar/Wind Harmer
1.129
316315AB2-025 C
Solar/Wind Harmer
0.871
316294AC1-161 GEN
Solar/Wind Harmer
10.325
316185AD1-033 GEN
Solar/Wind Harmer
3.325
3145506HICKORY
Solar/Wind Harmer
-0.126
3145506HICKORY
Solar/Wind Harmer
-0.075
3145506HICKORY
Solar/Wind Harmer
-0.019
316339AD2-160 GEN
Solar/Wind Harmer
2.115
316388AE2-253 GEN
Solar/Wind Harmer
2.115
3137176SLIGO L2192
Solar/Wind Harmer
-0.124
3146456SLIGO L269
Solar/Wind Harmer
3.706
3130086AYDLETT
Solar/Wind Harmer
-0.125
316083AB2-161 GEN
Solar/Wind Harmer
5.055
316349AD2-085 GEN
Solar/Wind Harmer
2.764
3146386ELIZ CT
Solar/Wind Harmer
-0.031
315835AF2-110_GEN
Solar/Wind Harmer
3.891
316431W1029_GEN1
Solar/Wind Harmer
5.589
316433W1029_GEN2
Solar/Wind Harmer
5.589
316435W1029_GEN3
Solar/Wind Harmer
5.589
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
970099AG2-077 GEN
Solar/Wind Harmer
37.976
315742AE1-103 GEN
Solar/Wind Harmer
7.193
3146376EDENTON
Solar/Wind Harmer
0.895
3146376EDENTON
Solar/Wind Harmer
0.895
316240AF1-291 C
Solar/Wind Harmer
0.903
316033AB2-134 GEN
Solar/Wind Harmer
9.627
316365GEN2_N
Solar/Wind Harmer
2.007
316313AB2-026
Solar/Wind Harmer
0.803
944641AF1-129 GEN
Adder
126.417
315614AA2-178 GEN
Solar/Wind Harmer
3.192
316065AD1-022 GEN
Solar/Wind Harmer
14.541
3145893MURPHYS
Solar/Wind Harmer
0.81
3145893MURPHYS
Solar/Wind Harmer
-0.052
3146173TUNIS
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
316140AB2-099
Solar/Wind Harmer
0.193
313506AB2-031 GEN
Solar/Wind Harmer
2.298
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
962571AG1-106 GEN
Solar/Wind Harmer
4.1
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
0.235
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145783HORNRTN
Solar/Wind Harmer
3.332
3145783HORNRTN
Solar/Wind Harmer
2.665
3145783HORNRTN
Solar/Wind Harmer
0.833
3145783HORNRTN
Solar/Wind Harmer
0.333
316336AC2-165 C
Solar/Wind Harmer
17.353
3142946ENON
Solar/Wind Harmer
-0.003
315687AD1-152 GEN
Solar/Wind Harmer
3.287
3145933PARMELE
Solar/Wind Harmer
-0.054
3145933PARMELE
Solar/Wind Harmer
-0.027
3142366NRTHEST
Adder
0.785
3150691DARBY 3
Adder
17.207
3150701DARBY 4
Adder
17.167
3150681DARBY 2
Adder
17.147
3150671DARBY 1
Adder
17.127
315724AD1-057 GEN
Solar/Wind Harmer
5.249
316005AA1-067
Solar/Wind Harmer
0.538
315976AC1-164 GENA
Solar/Wind Harmer
6.015
316169AC1-164_GENC
Solar/Wind Harmer
5.197
313527AB2-043 GEN
Solar/Wind Harmer
4.246
316237AB2-079_GEN
Solar/Wind Harmer
0.785
3145493TOT1
Solar/Wind Harmer
0.404
3145453TOT5
Solar/Wind Harmer
0.242
3145603CNETO
Solar/Wind Harmer
0.161
970301AG2-198 GEN
Solar/Wind Harmer
12.972
961601AG1-000A GEN
Solar/Wind Harmer
10.125
316049AB1-081 GEN
Solar/Wind Harmer
2.77
316263AC1-034 GEN
Solar/Wind Harmer
12.069
316441AF1-014 GEN
Solar/Wind Harmer
1.72
970323AG2-213 GEN
Solar/Wind Harmer
12.731
315666AE1-190 GEN
Solar/Wind Harmer
0.765
316156AD2-030 GEN
Solar/Wind Harmer
0.675
962561AG1-105 GEN
Solar/Wind Harmer
14.217
316312AB1-027
Solar/Wind Harmer
0.848
964791AG1-342 GEN
Solar/Wind Harmer
5.365
3146843MT LREL
Solar/Wind Harmer
-0.025
3146843MT LREL
Solar/Wind Harmer
-0.025
958211AF2-115 GEN
Solar/Wind Harmer
3.885
3144293JTRSVLE
Adder
0.528
3142296MT RD221
Adder
0.703
316118AC1-105 GEN
Solar/Wind Harmer
1.697
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
316248AF1-058 C
Solar/Wind Harmer
0.733
966871AG1-558 GEN
Solar/Wind Harmer
0.695
966871AG1-558 GEN
Solar/Wind Harmer
0.238
316487AF1-042 GEN
Solar/Wind Harmer
2.995
3150341NORNECKC1
Adder
1.917
3150341NORNECKC1
Adder
1.902
972189AH1-679 GEN
Adder
2.57
972193AH1-681 GEN
Adder
2.672
316045AC1-158 PL2
Solar/Wind Helper
8.819
316450AC1-158 RIC
Solar/Wind Helper
0.735
316006AB2-029 C
Solar/Wind Helper
0.132
966001AG1-469 GEN
Solar/Wind Helper
0.286
3151031BRUNSWICKG2
50/50
3.967
3151101ELIZAR3
50/50
27.697
3150861SPRUNCD
50/50
1.345
3151161SURRY 1
50/50
10.998
944011AF1-069 GEN
Solar/Wind Harmer
20.743
970917AG2-570 GEN
Solar/Wind Harmer
81.414
944581AF1-123 GEN
Solar/Wind Harmer
144.601
944601AF1-125 GEN
Solar/Wind Harmer
142.345
3142956BIRDNECK
Solar/Wind Harmer
1.694
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
2.537
3146456SLIGO L269
Solar/Wind Harmer
-0.031
971153AH1-033 GEN
Solar/Wind Harmer
3.632
3144536CHRHLND
Solar/Wind Harmer
-0.005
316305AF2-043 C
Solar/Wind Harmer
0.941
316246AF1-032 C
Solar/Wind Harmer
0.631
315813AE1-149 C
Solar/Wind Harmer
19.491
970657AG2-426 GEN
Solar/Wind Harmer
6.295
316320Y1-086
Solar/Wind Harmer
1.822
316321Z2-027
Solar/Wind Harmer
0.834
3145336SMITFLD
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
3145273HOLLAND
Solar/Wind Harmer
-0.023
3151171GRAVELC
Adder
3.777
3146376EDENTON
Solar/Wind Harmer
-0.03
961611AG1-000B GEN
Solar/Wind Harmer
6.352
3143336POWHATN
Solar/Wind Harmer
3.009
315778AD1-151 GEN
Solar/Wind Harmer
26.517
316458AB2-190 GEN2
Solar/Wind Harmer
2.99
3144216WINCHST
Adder
0.986
970133AG2-095 GEN
Solar/Wind Harmer
3.304
3156081AA2-088 GEN
Solar/Wind Harmer
9.51
3150921YORKTN3
Adder
6.534
315735AD1-075 GEN1
Solar/Wind Harmer
2.947
316478AD1-087 GEN
Solar/Wind Harmer
2.511
966621AG1-532 GEN
Solar/Wind Harmer
0.589
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
316181AB2-040 GEN
Solar/Wind Harmer
3.991
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
316011AB1-132 GEN
Solar/Wind Harmer
5.957
3146263WOODLND
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.061
3143096IRON208
Adder
1.04
316190AA2-174 GEN
Solar/Wind Harmer
0.347
3147043LAWRENC
Solar/Wind Harmer
-0.017
316317KELFORD C
Solar/Wind Harmer
1.303
3145823KELFORD
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.112
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3142946ENON
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
2.381
3145933PARMELE
Solar/Wind Harmer
-0.027
315722AD1-056 GEN
Solar/Wind Harmer
9.543
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970293AG2-193 GEN
Solar/Wind Harmer
3.327
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
316075AC2-137 C
Solar/Wind Harmer
0.709
316420AA1-050 GEN
Solar/Wind Harmer
2.987
3146233WITAKRS
Solar/Wind Harmer
0.547
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
3146073TAR RVR
Solar/Wind Harmer
-0.026
3146083TARBORO
Solar/Wind Harmer
-0.026
964241AG1-285 GEN
Solar/Wind Harmer
20.243
961601AG1-000A GEN
Solar/Wind Harmer
10.253
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3141843SHACKLE
Adder
1.161
316203AE2-005 GEN
Solar/Wind Harmer
10.762
970257AG2-171 GEN
Solar/Wind Harmer
9.549
971775AH1-396 GEN
Solar/Wind Harmer
1.797
959311AF2-222 GEN
Solar/Wind Harmer
26.485
3141766HARMONY
Solar/Wind Harmer
2.257
3141873WAN 176
Solar/Wind Harmer
3.007
3142416OLDCHRC
Solar/Wind Harmer
2.543
3144293JTRSVLE
Adder
0.528
3147133PAMPLIN
Solar/Wind Harmer
-0.077
942461AE2-259 GEN
Solar/Wind Harmer
3.621
3146926FARMVIL
Solar/Wind Harmer
-0.014
316003AC1-222 GEN
Solar/Wind Harmer
2.269
316473AC1-191 GEN
Solar/Wind Harmer
2.489
316484AD2-074 GEN
Solar/Wind Harmer
5.724
961951AG1-038 GEN
Solar/Wind Harmer
2.995
316222AC1-221 GEN
Solar/Wind Harmer
2.252
316283AC2-100 C
Solar/Wind Harmer
2.092
971683AH1-343 GEN
Solar/Wind Harmer
9.514
3150351NORNECKC2
Adder
1.856
972255AH1-712 GEN
Adder
59.8
3147666LOUISA
Solar/Wind Helper
0.988
3132273ORANGE
Solar/Wind Helper
0.058
3141196NOKESVL
Solar/Wind Helper
0.933
CPLELTFEXP_CPLE->PJM
CLTF
15.201
CBM West 2LTFEXP_CBM-W2->PJM
CBM
60.042
LAGNLTFEXP_LAGN->PJM
CLTF
11.232
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.361
TVALTFEXP_TVA->PJM
CLTF
5.651
NYPJM->LTFIMP_NY
CLTF
3.103
LGEELTFEXP_LGEE->PJM
CLTF
2.092
WECLTFEXP_WEC->PJM
CLTF
1.063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.098
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.459
MECLTFEXP_MEC->PJM
CLTF
5.626
SIGELTFEXP_SIGE->PJM
CLTF
0.171

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.54 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3946.36
MW Contribution:
164.83
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.168
3151101ELIZAR3
50/50
28.753
3151161SURRY 1
50/50
10.916
944011AF1-069 GEN
Solar/Wind Harmer
19.938
970917AG2-570 GEN
Solar/Wind Harmer
26.983
944581AF1-123 GEN
Solar/Wind Harmer
66.518
944601AF1-125 GEN
Solar/Wind Harmer
65.493
3144873MCLAUGH
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.155
3146456SLIGO L269
Solar/Wind Harmer
0.29
971153AH1-033 GEN
Solar/Wind Harmer
3.354
316246AF1-032 C
Solar/Wind Harmer
0.128
3144536CHRHLND
Solar/Wind Harmer
0.043
316321Z2-027
Solar/Wind Harmer
0.051
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3145273HOLLAND
Solar/Wind Harmer
0.209
3146376EDENTON
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
0.111
970657AG2-426 GEN
Solar/Wind Harmer
6.123
3151171GRAVELC
Adder
3.748
315735AD1-075 GEN1
Solar/Wind Harmer
0.76
315813AE1-149 C
Solar/Wind Harmer
14.247
316478AD1-087 GEN
Solar/Wind Harmer
0.925
3156081AA2-088 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.265
3144216WINCHST
Adder
0.998
3145893MURPHYS
Solar/Wind Harmer
0.442
3145893MURPHYS
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
6.632
961611AG1-000B GEN
Solar/Wind Harmer
7.007
3146173TUNIS
Solar/Wind Harmer
0.262
3146263WOODLND
Solar/Wind Harmer
0.259
316181AB2-040 GEN
Solar/Wind Harmer
0.368
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
316011AB1-132 GEN
Solar/Wind Harmer
4.67
3145963POPLR C
Solar/Wind Harmer
0.256
3145823KELFORD
Solar/Wind Harmer
0.255
3143336POWHATN
Solar/Wind Harmer
3.841
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Solar/Wind Harmer
0.152
315778AD1-151 GEN
Solar/Wind Harmer
20.108
316212AC1-099_GEN
Solar/Wind Harmer
1.277
316458AB2-190 GEN2
Solar/Wind Harmer
1.316
3145933PARMELE
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
8.364
3150861SPRUNCD
Adder
1.1
970133AG2-095 GEN
Solar/Wind Harmer
2.287
3146233WITAKRS
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.161
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
3138543CONSLDL
Solar/Wind Harmer
0.155
964241AG1-285 GEN
Solar/Wind Harmer
15.514
961601AG1-000A GEN
Solar/Wind Harmer
16.523
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.232
971623AH1-311 GEN
Solar/Wind Harmer
0.465
970257AG2-171 GEN
Solar/Wind Harmer
7.288
971775AH1-396 GEN
Solar/Wind Harmer
0.364
959311AF2-222 GEN
Solar/Wind Harmer
20.157
3142946ENON
Solar/Wind Harmer
0.074
3144293JTRSVLE
Adder
0.528
3147133PAMPLIN
Solar/Wind Harmer
0.687
3141873WAN 176
Solar/Wind Harmer
3.844
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
1.101
3143096IRON208
Adder
0.901
3143096IRON208
Adder
0.883
3141766HARMONY
Solar/Wind Harmer
2.864
3142433PROV 92
Adder
0.417
3142433PROV 92
Adder
0.417
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.123
316075AC2-137 C
Solar/Wind Harmer
0.054
316222AC1-221 GEN
Solar/Wind Harmer
0.822
316283AC2-100 C
Solar/Wind Harmer
0.389
971683AH1-343 GEN
Solar/Wind Harmer
7.173
970293AG2-193 GEN
Solar/Wind Harmer
2.062
3146776BUCKING
Solar/Wind Harmer
0.065
3150351NORNECKC2
Adder
1.742
316123AC1-075 GEN
Solar/Wind Harmer
0.223
3142416OLDCHRC
Solar/Wind Harmer
1.548
972003AH1-546 GEN
Solar/Wind Harmer
5.242
316223AC1-118
Solar/Wind Harmer
0.094
3141906WESTMOR
Solar/Wind Harmer
0.053
970221AG2-151 GEN
Solar/Wind Harmer
7.035
316473AC1-191 GEN
Solar/Wind Harmer
0.411
270494AE1-108_GEN
Solar/Wind Harmer
1.393
3147666LOUISA
Solar/Wind Helper
0.597
316303AF2-085
50/50
5.781
315244AE2-183_ST
50/50
9.183
963041AG1-153 GEN
50/50
8.438
3151081ELIZAR1
50/50
28.39
3151091ELIZAR2
50/50
27.897
941591AE2-156 GEN
50/50
25.918
315779AE2-040
50/50
4.045
972263AH1-716 GEN
50/50
164.827
970533AG2-339 GEN
Solar/Wind Harmer
25.033
315242AE2-183_GT2
50/50
5.288
315241AE2-183_GT1
50/50
5.274
972185AH1-677 GEN
50/50
19.115
3151041BRUNSWICKG3
50/50
4.168
972187AH1-678 GEN
50/50
9.563
3150991CHESPKB
50/50
3.237
3150991CHESPKB
50/50
3.159
971223AH1-071 GEN
Solar/Wind Harmer
3.469
970933AG2-581 GEN
Solar/Wind Harmer
24.61
316294AC1-161 GEN
Solar/Wind Harmer
5.188
3145506HICKORY
Solar/Wind Harmer
1.167
3145506HICKORY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
0.175
316339AD2-160 GEN
Solar/Wind Harmer
0.466
316388AE2-253 GEN
Solar/Wind Harmer
0.906
3137176SLIGO L2192
Solar/Wind Harmer
1.155
3146456SLIGO L269
Solar/Wind Harmer
5.134
3130086AYDLETT
Solar/Wind Harmer
1.159
3144356SAPONY
Solar/Wind Harmer
2.424
316315AB2-025 C
Solar/Wind Harmer
0.232
3146386ELIZ CT
Solar/Wind Harmer
0.287
315835AF2-110_GEN
Solar/Wind Harmer
1.954
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3143526WINTERP
Solar/Wind Harmer
1.468
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
970099AG2-077 GEN
Solar/Wind Harmer
29.893
316349AD2-085 GEN
Solar/Wind Harmer
0.187
3146376EDENTON
Solar/Wind Harmer
1.232
3146376EDENTON
Solar/Wind Harmer
1.232
315742AE1-103 GEN
Solar/Wind Harmer
4.13
315614AA2-178 GEN
Solar/Wind Harmer
1.547
316365GEN2_N
Solar/Wind Harmer
0.597
316065AD1-022 GEN
Solar/Wind Harmer
12.234
3145893MURPHYS
Solar/Wind Harmer
1.766
3145893MURPHYS
Solar/Wind Harmer
0.475
3146173TUNIS
Solar/Wind Harmer
0.262
3146173TUNIS
Solar/Wind Harmer
0.262
316140AB2-099
Solar/Wind Harmer
0.093
313506AB2-031 GEN
Solar/Wind Harmer
0.793
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
962571AG1-106 GEN
Solar/Wind Harmer
3.663
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.318
316033AB2-134 GEN
Solar/Wind Harmer
0.001
316313AB2-026
Solar/Wind Harmer
0.158
3145783HORNRTN
Solar/Wind Harmer
4.516
3145783HORNRTN
Solar/Wind Harmer
3.613
3145783HORNRTN
Solar/Wind Harmer
1.129
3145783HORNRTN
Solar/Wind Harmer
0.452
3145796HORNRTN
Solar/Wind Harmer
0.761
3145933PARMELE
Solar/Wind Harmer
0.493
3145933PARMELE
Solar/Wind Harmer
0.246
316005AA1-067
Solar/Wind Harmer
0.258
315724AD1-057 GEN
Solar/Wind Harmer
4.666
3145493TOT1
Solar/Wind Harmer
0.547
3145453TOT5
Solar/Wind Harmer
0.328
3145603CNETO
Solar/Wind Harmer
0.219
316336AC2-165 C
Solar/Wind Harmer
11.937
944641AF1-129 GEN
Adder
111.423
970301AG2-198 GEN
Solar/Wind Harmer
9.914
961601AG1-000A GEN
Solar/Wind Harmer
4.131
316049AB1-081 GEN
Solar/Wind Harmer
1.321
316263AC1-034 GEN
Solar/Wind Harmer
8.826
970323AG2-213 GEN
Solar/Wind Harmer
9.717
962561AG1-105 GEN
Solar/Wind Harmer
10.908
964791AG1-342 GEN
Solar/Wind Harmer
4.335
3146843MT LREL
Solar/Wind Harmer
0.226
3146843MT LREL
Solar/Wind Harmer
0.226
316118AC1-105 GEN
Solar/Wind Harmer
0.569
3142946ENON
Solar/Wind Harmer
0.022
958211AF2-115 GEN
Solar/Wind Harmer
2.653
3144293JTRSVLE
Adder
0.528
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
315976AC1-164 GENA
Solar/Wind Harmer
2.291
316169AC1-164_GENC
Solar/Wind Harmer
1.979
316156AD2-030 GEN
Solar/Wind Harmer
0.158
3150691DARBY 3
Adder
13.39
3150701DARBY 4
Adder
13.359
3150681DARBY 2
Adder
13.343
3150671DARBY 1
Adder
13.328
3142366NRTHEST
Adder
0.595
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
3150341NORNECKC1
Adder
1.8
3150341NORNECKC1
Adder
1.786
316312AB1-027
Solar/Wind Harmer
0.284
942751AE2-291 GEN
Solar/Wind Harmer
8.407
3142296MT RD221
Adder
0.414
966871AG1-558 GEN
Solar/Wind Harmer
0.141
316045AC1-158 PL2
Solar/Wind Helper
5.537
316450AC1-158 RIC
Solar/Wind Helper
0.461
970119AG2-088 GEN
50/50
43.358
315243AE2-183_GT3
50/50
5.288
3151051BRUNSWICKS1
50/50
8.652
3151021BRUNSWICKG1
50/50
4.168
971451AH1-221 GEN
50/50
12.657
3150981CHESPKA
50/50
3.859
3152331SURRY 2
50/50
11.829
940641AE2-051 GEN
Solar/Wind Harmer
26.953
941031AE2-094 GEN
Solar/Wind Harmer
61.021
939411AE1-173 GEN
Solar/Wind Harmer
139.056
3143226MDLTHAN
Solar/Wind Harmer
0.325
970919AG2-571 GEN
Solar/Wind Harmer
10.793
315773AC2-141 GEN
Solar/Wind Harmer
10.96
970087AG2-069 GEN
Solar/Wind Harmer
23.933
944591AF1-124 GEN
Solar/Wind Harmer
66.754
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.052
3146456SLIGO L269
Solar/Wind Harmer
0.29
970673AG2-436 GEN
Solar/Wind Harmer
40.723
971967AH1-528 GEN
Solar/Wind Harmer
50.609
970085AG2-068 GEN
Solar/Wind Harmer
15.955
970581AG2-369 GEN
Solar/Wind Harmer
13.722
316316AC1-027 C
Solar/Wind Harmer
0.278
957871AF2-081 GEN
Solar/Wind Harmer
14.474
3146406KITTY HAWK
Solar/Wind Harmer
0.036
315814AE2-033 C
Solar/Wind Harmer
22.84
313526AB2-022
Solar/Wind Harmer
0.153
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
3146486SUNBURY
Solar/Wind Harmer
0.286
3146486SUNBURY
Solar/Wind Harmer
0.286
316233AE1-074 FULL
Solar/Wind Harmer
0.226
971281AH1-106 GEN
Solar/Wind Harmer
3.918
971283AH1-107 GEN
Solar/Wind Harmer
3.918
316311AC2-079 GEN
Solar/Wind Harmer
8.039
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
19.444
3143316POE
Solar/Wind Harmer
1.084
970657AG2-426 GEN
Solar/Wind Harmer
2.004
3151201GRAVEL4
Adder
19.505
3151221GRAVEL6
Adder
19.482
3151191GRAVEL3
Adder
19.258
3151211GRAVEL5
Adder
19.258
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.522
315733AD1-074 GEN2
Solar/Wind Harmer
1.522
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3146206CASHIE
Solar/Wind Harmer
0.265
970601AG2-382 GEN
Solar/Wind Harmer
9.889
3145893MURPHYS
Solar/Wind Harmer
0.712
3145893MURPHYS
Solar/Wind Harmer
0.264
316463AE2-346 GEN
Solar/Wind Harmer
0.223
3145513AHOSKIE
Solar/Wind Harmer
0.546
3145513AHOSKIE
Solar/Wind Harmer
0.261
3146043SEABORD
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.52
3145683EARLEYS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.26
315652AC1-086 GEN
Solar/Wind Harmer
28.319
3137643SOCKMAN
Solar/Wind Harmer
1.026
316426AA2-053 GEN
Solar/Wind Harmer
0.857
315697AD1-025 GEN
Solar/Wind Harmer
0.274
316258AE1-075 C
Solar/Wind Harmer
0.19
3145796HORNRTN
Solar/Wind Harmer
0.812
3145796HORNRTN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
1.005
316159AE1-175 C
Solar/Wind Harmer
0.213
316210AC1-098 GEN
Solar/Wind Harmer
2.291
970831AG2-522 GEN
Solar/Wind Harmer
10.561
316274AC1-208 GEN
Solar/Wind Harmer
1.27
3145746EVERETS
Solar/Wind Harmer
0.963
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3138283WHITEMARSH
Solar/Wind Harmer
0.056
316327AA2-057 GEN
Solar/Wind Harmer
0.355
971285AH1-108 GEN
Adder
1.8
957861AF2-080 GEN
Solar/Wind Harmer
10.29
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
3144303KENBRDG
Solar/Wind Harmer
0.182
970683AG2-441 GEN
Solar/Wind Harmer
13.519
970681AG2-440 GEN
Solar/Wind Harmer
8.973
946301AF1-294 GEN
Solar/Wind Harmer
4.363
961791AG1-021 GEN
Solar/Wind Harmer
2.122
3147173SINAI
Solar/Wind Harmer
0.219
3147243WELCO
Solar/Wind Harmer
0.137
3141873WAN 176
Solar/Wind Harmer
0.043
970189AG2-124 GEN
Solar/Wind Harmer
6.385
3142433PROV 92
Adder
0.417
3142433PROV 92
Adder
0.417
3143873LANEXA
Solar/Wind Harmer
0.129
3141913WHIT STONE
Solar/Wind Harmer
0.209
3138133OCRAN
Solar/Wind Harmer
0.062
3141783LANCAST
Solar/Wind Harmer
0.122
3141783LANCAST
Solar/Wind Harmer
0.082
971845AH1-439 GEN
Solar/Wind Harmer
8.224
3141813NORNECK
Solar/Wind Harmer
0.172
972205AH1-687 GEN
Adder
6.299
316164AC1-076 GEN
Solar/Wind Helper
1.144
319010AE1-072 C
Solar/Wind Harmer
1.446
316093AE2-104_GEN
Solar/Wind Harmer
4.79
3146516WINFALL
Solar/Wind Harmer
0.919
3146516WINFALL
Solar/Wind Harmer
0.284
316072AD1-144
Solar/Wind Harmer
0.101
3143526WINTERP
Solar/Wind Harmer
1.468
957481AF2-042 GEN
Solar/Wind Harmer
74.732
3130156CHOWAN
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
1.107
316381AD1-082 GEN
Solar/Wind Harmer
0.276
315816AE2-034 GEN
Solar/Wind Harmer
1.16
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.754
315693AD1-088 GEN
Solar/Wind Harmer
12.912
316023GEN1_S
Solar/Wind Harmer
0.597
3151171GRAVELC
Adder
2.851
315737AD1-076 GEN
Solar/Wind Harmer
3.427
3146206CASHIE
Solar/Wind Harmer
0.265
971547AH1-271 GEN
Solar/Wind Harmer
5.651
3138126ROCKLANDING
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
1.055
3145893MURPHYS
Solar/Wind Harmer
1.173
961611AG1-000B GEN
Solar/Wind Harmer
13.781
3146173TUNIS
Solar/Wind Harmer
0.262
960081AF2-299 GEN
Solar/Wind Harmer
2.512
3156021HOLLOMANSOL
Solar/Wind Harmer
1.177
3145683EARLEYS
Solar/Wind Harmer
0.26
315607AA1-063A GEN
Solar/Wind Harmer
0.522
3146263WOODLND
Solar/Wind Harmer
0.259
3145963POPLR C
Solar/Wind Harmer
0.256
971317AH1-138 GEN
Solar/Wind Harmer
1.911
3145823KELFORD
Solar/Wind Harmer
0.255
3143336POWHATN
Solar/Wind Harmer
4.519
3145783HORNRTN
Solar/Wind Harmer
0.254
3145796HORNRTN
Solar/Wind Harmer
0.837
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Adder
2.295
971069AG2-661 GEN
Solar/Wind Harmer
4.468
316132AB2-190 GEN1
Solar/Wind Harmer
1.316
3146293MARTNCO
Solar/Wind Harmer
0.229
316129AC1-054 GEN
Solar/Wind Harmer
0.92
971065AG2-659 GEN
Solar/Wind Harmer
10.482
315671AE2-027_GEN
Solar/Wind Harmer
0.002
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3150851SPRUNCC
Adder
1.1
316494AC1-189 GEN
Solar/Wind Harmer
0.806
3146233WITAKRS
Solar/Wind Harmer
0.94
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.048
316131AB2-060 GEN
Solar/Wind Harmer
0.731
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.186
316359AB2-059 GEN
Solar/Wind Harmer
0.825
3142053HEARTS
Solar/Wind Harmer
0.409
315785AD2-033 C
Solar/Wind Harmer
1.852
316034AC1-036 C
Solar/Wind Harmer
0.015
970401AG2-262 GEN
Solar/Wind Harmer
1.325
970685AG2-442 GEN
Solar/Wind Harmer
16.639
944631AF1-128 GEN
Adder
106.053
971563AH1-280 GEN
Solar/Wind Harmer
2.358
3144293JTRSVLE
Adder
0.528
3144293JTRSVLE
Adder
0.417
3142543TWELFTH
Solar/Wind Harmer
0.021
315975AC1-164 GENB
Solar/Wind Harmer
0.068
971777AH1-397 GEN
Solar/Wind Harmer
0.569
3143096IRON208
Adder
0.901
3141766HARMONY
Solar/Wind Harmer
0.043
3142433PROV 92
Solar/Wind Harmer
0.859
3142433PROV 92
Adder
0.417
3142433PROV 92
Adder
0.417
3138133OCRAN
Solar/Wind Harmer
0.125
3146926FARMVIL
Solar/Wind Harmer
0.123
970937AG2-583 GEN
Solar/Wind Harmer
11.523
962861AG1-135 GEN
Solar/Wind Harmer
5.976
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.112
3146776BUCKING
Solar/Wind Harmer
0.072
3141726DUNNSVL
Solar/Wind Harmer
0.705
3150351NORNECKC2
Adder
1.714
3142416OLDCHRC
Solar/Wind Harmer
0.415
3142416OLDCHRC
Solar/Wind Harmer
0.159
316337AD2-073 GEN
Solar/Wind Harmer
0.131
971377AH1-170 GEN
Solar/Wind Harmer
1.407
3147623JAMES R
Solar/Wind Harmer
0.306
970223AG2-152 GEN
Solar/Wind Harmer
8.971
316447AC1-158 HLD
Solar/Wind Helper
3.807
316044AC1-158 PL1
Solar/Wind Helper
1.73
3147666LOUISA
Solar/Wind Helper
1.038
316192AB2-158 GEN
Solar/Wind Helper
1.716
CPLELTFEXP_CPLE->PJM
CLTF
15.186
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.739
LAGNLTFEXP_LAGN->PJM
CLTF
10.159
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.539
TVALTFEXP_TVA->PJM
CLTF
5.085
NYPJM->LTFIMP_NY
CLTF
2.76
LGEELTFEXP_LGEE->PJM
CLTF
1.69
WECLTFEXP_WEC->PJM
CLTF
0.859
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.619
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.321
MECLTFEXP_MEC->PJM
CLTF
4.72
SIGELTFEXP_SIGE->PJM
CLTF
0.141

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:154.87 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4987.58
MW Contribution:
138.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.065
3150861SPRUNCD
50/50
1.215
3143096IRON208
50/50
1.077
3143096IRON208
50/50
1.055
3150801HOPHCF4
50/50
1.422
3150761HOPPOLC
50/50
0.611
3151101ELIZAR3
50/50
23.654
3151161SURRY 1
50/50
9.75
3147666LOUISA
Solar/Wind Harmer
0.591
944011AF1-069 GEN
Solar/Wind Harmer
14.582
315813AE1-149 C
Solar/Wind Harmer
12.858
970133AG2-095 GEN
Solar/Wind Harmer
2.311
944581AF1-123 GEN
Solar/Wind Harmer
54.154
944601AF1-125 GEN
Solar/Wind Harmer
53.32
316458AB2-190 GEN2
Solar/Wind Harmer
1.282
315778AD1-151 GEN
Solar/Wind Harmer
19.211
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.096
961611AG1-000B GEN
Solar/Wind Harmer
6.389
970657AG2-426 GEN
Solar/Wind Harmer
5.372
3151171GRAVELC
Adder
3.348
970293AG2-193 GEN
Solar/Wind Harmer
2.545
3142946ENON
Solar/Wind Harmer
0.08
316017AA1-139 ULT1
Solar/Wind Harmer
0.127
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.746
3142416OLDCHRC
Solar/Wind Harmer
2.302
3144216WINCHST
Adder
0.895
316246AF1-032 C
Solar/Wind Harmer
0.105
3150921YORKTN3
Adder
5.96
316075AC2-137 C
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.042
3146516WINFALL
Solar/Wind Harmer
0.232
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316473AC1-191 GEN
Solar/Wind Harmer
0.777
3141843SHACKLE
Adder
1.159
316203AE2-005 GEN
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
3.425
3146376EDENTON
Solar/Wind Harmer
0.226
3141766HARMONY
Solar/Wind Harmer
3.02
3141873WAN 176
Solar/Wind Harmer
4.006
970917AG2-570 GEN
Solar/Wind Harmer
19.985
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.619
3150401LDYSMT4
Adder
29.12
3150371LDYSMT1
Adder
28.138
3146206CASHIE
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
3146173TUNIS
Solar/Wind Harmer
0.213
3146263WOODLND
Solar/Wind Harmer
0.21
316181AB2-040 GEN
Solar/Wind Harmer
0.298
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
316011AB1-132 GEN
Solar/Wind Harmer
3.783
3145963POPLR C
Solar/Wind Harmer
0.208
3145823KELFORD
Solar/Wind Harmer
0.207
316478AD1-087 GEN
Solar/Wind Harmer
0.714
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.821
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.072
316212AC1-099_GEN
Solar/Wind Harmer
1.033
3145933PARMELE
Solar/Wind Harmer
0.199
971781AH1-399 GEN
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
6.743
964241AG1-285 GEN
Solar/Wind Harmer
12.775
970257AG2-171 GEN
Solar/Wind Harmer
6.108
971775AH1-396 GEN
Solar/Wind Harmer
0.305
959311AF2-222 GEN
Solar/Wind Harmer
16.954
3146233WITAKRS
Solar/Wind Harmer
0.954
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.19
3146083TARBORO
Solar/Wind Harmer
0.19
3144293JTRSVLE
Adder
0.453
3138543CONSLDL
Solar/Wind Harmer
0.125
3147133PAMPLIN
Solar/Wind Harmer
0.595
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
13.28
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.187
971623AH1-311 GEN
Solar/Wind Harmer
0.373
316223AC1-118
Solar/Wind Harmer
0.131
3141906WESTMOR
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.064
972003AH1-546 GEN
Solar/Wind Harmer
5.879
971683AH1-343 GEN
Solar/Wind Harmer
5.882
316222AC1-221 GEN
Solar/Wind Harmer
0.654
316283AC2-100 C
Solar/Wind Harmer
0.309
970221AG2-151 GEN
Solar/Wind Harmer
8.401
972255AH1-712 GEN
Adder
74.821
316123AC1-075 GEN
Solar/Wind Harmer
0.189
270494AE1-108_GEN
Solar/Wind Harmer
1.66
315821AE2-092 GEN
Solar/Wind Harmer
0
3151761LOISA E
Adder
17.635
3151721LOISA A
Adder
8.605
3141196NOKESVL
Solar/Wind Helper
1.133
316303AF2-085
50/50
4.718
971285AH1-108 GEN
50/50
1.988
972263AH1-716 GEN
50/50
138.906
3151081ELIZAR1
50/50
23.355
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971281AH1-106 GEN
Solar/Wind Harmer
3.576
971283AH1-107 GEN
Solar/Wind Harmer
3.576
3143316POE
Solar/Wind Harmer
0.962
970533AG2-339 GEN
Solar/Wind Harmer
18.309
3151091ELIZAR2
Adder
21.627
315697AD1-025 GEN
Solar/Wind Harmer
0.258
970673AG2-436 GEN
Solar/Wind Harmer
29.845
316316AC1-027 C
Solar/Wind Harmer
0.228
971445AH1-216 GEN
Solar/Wind Harmer
16.871
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3151201GRAVEL4
Adder
17.422
3151221GRAVEL6
Adder
17.402
3151191GRAVEL3
Adder
17.202
3151211GRAVEL5
Adder
17.202
957871AF2-081 GEN
Solar/Wind Harmer
11.848
316311AC2-079 GEN
Solar/Wind Harmer
6.816
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316159AE1-175 C
Solar/Wind Harmer
0.202
313526AB2-022
Solar/Wind Harmer
0.125
315814AE2-033 C
Solar/Wind Harmer
18.566
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
3146396TANGLEW
Solar/Wind Harmer
0.646
3145176PASQUOTANK
Solar/Wind Harmer
0.145
971967AH1-528 GEN
Solar/Wind Harmer
37.439
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3143873LANEXA
Solar/Wind Harmer
0.137
970189AG2-124 GEN
Solar/Wind Harmer
6.721
316258AE1-075 C
Solar/Wind Harmer
0.169
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
3141913WHIT STONE
Solar/Wind Harmer
0.222
970085AG2-068 GEN
Solar/Wind Harmer
11.838
970581AG2-369 GEN
Solar/Wind Harmer
10.181
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.24
315733AD1-074 GEN2
Solar/Wind Harmer
1.24
3150411LDYSMT5
Adder
29.211
3150381LDYSMT2
Adder
27.956
972213AH1-691 GEN
Adder
4.729
972215AH1-692 GEN
Adder
4.729
3146206CASHIE
Solar/Wind Harmer
0.215
970601AG2-382 GEN
Solar/Wind Harmer
8.052
3145893MURPHYS
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
0.215
316463AE2-346 GEN
Solar/Wind Harmer
0.181
3145513AHOSKIE
Solar/Wind Harmer
0.444
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.423
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315652AC1-086 GEN
Solar/Wind Harmer
22.938
3137643SOCKMAN
Solar/Wind Harmer
0.831
316426AA2-053 GEN
Solar/Wind Harmer
0.694
316486AD2-202 GEN
Solar/Wind Harmer
0.21
3145796HORNRTN
Solar/Wind Harmer
0.657
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.204
3146033SCOT NK
Solar/Wind Harmer
0.814
316210AC1-098 GEN
Solar/Wind Harmer
1.852
970831AG2-522 GEN
Solar/Wind Harmer
8.499
316274AC1-208 GEN
Solar/Wind Harmer
1.026
3145746EVERETS
Solar/Wind Harmer
0.778
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
316327AA2-057 GEN
Solar/Wind Harmer
0.286
957861AF2-080 GEN
Solar/Wind Harmer
8.299
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
11.473
970681AG2-440 GEN
Solar/Wind Harmer
7.615
3145573BETHELC
Solar/Wind Harmer
0.19
3145573BETHELC
Solar/Wind Harmer
0.19
946301AF1-294 GEN
Solar/Wind Harmer
3.747
961791AG1-021 GEN
Solar/Wind Harmer
1.823
971845AH1-439 GEN
Solar/Wind Harmer
8.142
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
944641AF1-129 GEN
50/50
122.63
3142366NRTHEST
50/50
0.835
3150781HOPHCF2
50/50
0.976
3150791HOPHCF3
50/50
0.976
971223AH1-071 GEN
Solar/Wind Harmer
2.831
3143526WINTERP
Solar/Wind Harmer
1.34
316294AC1-161 GEN
Solar/Wind Harmer
4.187
3150691DARBY 3
Adder
17.276
3150701DARBY 4
Adder
17.236
3150681DARBY 2
Adder
17.216
3150671DARBY 1
Adder
17.196
3150991CHESPKB
Adder
2.514
3150991CHESPKB
Adder
2.453
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3142296MT RD221
Adder
0.762
3145506HICKORY
Solar/Wind Harmer
0.956
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
3142946ENON
Solar/Wind Harmer
0.024
316339AD2-160 GEN
Solar/Wind Harmer
0.381
316388AE2-253 GEN
Solar/Wind Harmer
0.741
3137176SLIGO L2192
Solar/Wind Harmer
0.945
3146456SLIGO L269
Solar/Wind Harmer
4.203
316312AB1-027
Solar/Wind Harmer
0.422
316349AD2-085 GEN
Solar/Wind Harmer
0.158
3130086AYDLETT
Solar/Wind Harmer
0.949
315835AF2-110_GEN
Solar/Wind Harmer
1.619
972185AH1-677 GEN
Adder
13.245
3144356SAPONY
Solar/Wind Harmer
1.97
316315AB2-025 C
Solar/Wind Harmer
0.188
315976AC1-164 GENA
Solar/Wind Harmer
2.477
316169AC1-164_GENC
Solar/Wind Harmer
2.14
3146386ELIZ CT
Solar/Wind Harmer
0.235
972189AH1-679 GEN
Adder
3.909
972187AH1-678 GEN
Adder
6.642
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
18.348
315742AE1-103 GEN
Solar/Wind Harmer
3.403
316313AB2-026
Solar/Wind Harmer
0.141
3146376EDENTON
Solar/Wind Harmer
1.007
3146376EDENTON
Solar/Wind Harmer
1.007
316156AD2-030 GEN
Solar/Wind Harmer
0.165
315614AA2-178 GEN
Solar/Wind Harmer
1.262
315673AE1-157 GEN
Solar/Wind Harmer
15.346
316365GEN2_N
Solar/Wind Harmer
0.484
3150391LDYSMT3
Adder
29.065
972195AH1-682 GEN
Adder
3.82
316336AC2-165 C
Solar/Wind Harmer
10.968
316065AD1-022 GEN
Solar/Wind Harmer
9.965
3145893MURPHYS
Solar/Wind Harmer
1.44
3145893MURPHYS
Solar/Wind Harmer
0.387
970099AG2-077 GEN
Solar/Wind Harmer
22.87
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
316140AB2-099
Solar/Wind Harmer
0.075
313506AB2-031 GEN
Solar/Wind Harmer
0.643
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
962571AG1-106 GEN
Solar/Wind Harmer
2.967
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.257
3145783HORNRTN
Solar/Wind Harmer
3.656
3145783HORNRTN
Solar/Wind Harmer
2.925
3145783HORNRTN
Solar/Wind Harmer
0.914
3145783HORNRTN
Solar/Wind Harmer
0.366
3145796HORNRTN
Solar/Wind Harmer
0.616
3150341NORNECKC1
Adder
2.14
3150341NORNECKC1
Adder
2.123
3145933PARMELE
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.199
970301AG2-198 GEN
Solar/Wind Harmer
8.407
316005AA1-067
Solar/Wind Harmer
0.209
315724AD1-057 GEN
Solar/Wind Harmer
3.762
970323AG2-213 GEN
Solar/Wind Harmer
8.144
3145493TOT1
Solar/Wind Harmer
0.44
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.278
3144293JTRSVLE
Adder
0.453
3147133PAMPLIN
Solar/Wind Harmer
0.189
3147133PAMPLIN
Solar/Wind Harmer
0.151
961601AG1-000A GEN
Solar/Wind Harmer
3.32
316049AB1-081 GEN
Solar/Wind Harmer
1.062
316263AC1-034 GEN
Solar/Wind Harmer
7.094
962561AG1-105 GEN
Solar/Wind Harmer
8.822
964791AG1-342 GEN
Solar/Wind Harmer
3.5
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
3146776BUCKING
Solar/Wind Harmer
0.715
3146776BUCKING
Solar/Wind Harmer
0.058
316118AC1-105 GEN
Solar/Wind Harmer
0.458
972193AH1-681 GEN
Adder
3.343
942751AE2-291 GEN
Solar/Wind Harmer
7.275
3151731LOISA B
Adder
8.65
316045AC1-158 PL2
Solar/Wind Helper
16.749
316450AC1-158 RIC
Solar/Wind Helper
1.396
316006AB2-029 C
Solar/Wind Helper
0.141
316411AF1-147_GEN1
Solar/Wind Helper
0.794
3152251N ANNA1
50/50
20.055
970119AG2-088 GEN
50/50
35.386
3150851SPRUNCC
50/50
1.215
3143096IRON208
50/50
1.077
3152331SURRY 2
50/50
9.863
3150771HOPHCF1
50/50
0.976
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.34
3147666LOUISA
Solar/Wind Harmer
1.027
316192AB2-158 GEN
Solar/Wind Harmer
1.403
940641AE2-051 GEN
Solar/Wind Harmer
19.942
939411AE1-173 GEN
Solar/Wind Harmer
105.31
3142543TWELFTH
Solar/Wind Harmer
0.023
315773AC2-141 GEN
Solar/Wind Harmer
8.846
941031AE2-094 GEN
Solar/Wind Harmer
44.63
315671AE2-027_GEN
Solar/Wind Harmer
0.002
944591AF1-124 GEN
Solar/Wind Harmer
54.347
316132AB2-190 GEN1
Solar/Wind Harmer
1.282
971069AG2-661 GEN
Solar/Wind Harmer
4.269
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.043
3150981CHESPKA
Adder
2.996
3145336SMITFLD
Solar/Wind Harmer
0.958
316381AD1-082 GEN
Solar/Wind Harmer
0.243
944631AF1-128 GEN
Adder
114.228
961611AG1-000B GEN
Solar/Wind Harmer
12.565
3151171GRAVELC
Adder
2.546
3146456SLIGO L269
Solar/Wind Harmer
0.237
3142416OLDCHRC
Solar/Wind Harmer
0.617
3142416OLDCHRC
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.084
319010AE1-072 C
Solar/Wind Harmer
1.184
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316093AE2-104_GEN
Solar/Wind Harmer
3.969
971317AH1-138 GEN
Solar/Wind Harmer
1.76
315975AC1-164 GENB
Solar/Wind Harmer
0.073
3146516WINFALL
Solar/Wind Harmer
0.753
3146516WINFALL
Solar/Wind Harmer
0.232
3142433PROV 92
Solar/Wind Harmer
0.927
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
971777AH1-397 GEN
Solar/Wind Harmer
0.599
3143336POWHATN
Solar/Wind Harmer
4.029
3130156CHOWAN
Solar/Wind Harmer
0.226
3141766HARMONY
Solar/Wind Harmer
0.045
970919AG2-571 GEN
Solar/Wind Harmer
7.994
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
17.757
315816AE2-034 GEN
Solar/Wind Harmer
0.947
3145663CRESWEL
Solar/Wind Harmer
0.621
971163AH1-040 GEN
Solar/Wind Harmer
17.754
3138133OCRAN
Solar/Wind Harmer
0.133
316023GEN1_S
Solar/Wind Harmer
0.484
315737AD1-076 GEN
Solar/Wind Harmer
2.793
972197AH1-683 GEN
Adder
4.547
972219AH1-694 GEN
Adder
3.274
3146206CASHIE
Solar/Wind Harmer
0.215
971547AH1-271 GEN
Solar/Wind Harmer
4.601
3145893MURPHYS
Solar/Wind Harmer
0.861
3145893MURPHYS
Solar/Wind Harmer
0.957
957481AF2-042 GEN
Solar/Wind Harmer
57.175
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.958
960081AF2-299 GEN
Solar/Wind Harmer
2.039
962861AG1-135 GEN
Solar/Wind Harmer
6.765
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.424
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
6.961
3146263WOODLND
Solar/Wind Harmer
0.21
315693AD1-088 GEN
Solar/Wind Harmer
10.078
3145963POPLR C
Solar/Wind Harmer
0.208
3145823KELFORD
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.829
3147043LAWRENC
Adder
1.865
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.038
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.74
971065AG2-659 GEN
Solar/Wind Harmer
8.423
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
316337AD2-073 GEN
Solar/Wind Harmer
0.168
316494AC1-189 GEN
Solar/Wind Harmer
0.65
316131AB2-060 GEN
Solar/Wind Harmer
0.597
315785AD2-033 C
Solar/Wind Harmer
1.545
316034AC1-036 C
Solar/Wind Harmer
0.013
970937AG2-583 GEN
Solar/Wind Harmer
11.679
970685AG2-442 GEN
Solar/Wind Harmer
14.197
3146233WITAKRS
Solar/Wind Harmer
0.756
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.19
3145493TOT1
Solar/Wind Harmer
0.844
971563AH1-280 GEN
Solar/Wind Harmer
2.025
3144293JTRSVLE
Adder
0.453
3144293JTRSVLE
Adder
0.358
3146926FARMVIL
Solar/Wind Harmer
0.113
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.663
3142053HEARTS
Solar/Wind Harmer
0.329
970401AG2-262 GEN
Solar/Wind Harmer
1.069
3146776BUCKING
Solar/Wind Harmer
0.072
972135AH1-637 GEN
Solar/Wind Harmer
1.429
971377AH1-170 GEN
Solar/Wind Harmer
1.68
3147623JAMES R
Solar/Wind Harmer
0.365
972277AH1-723 GEN
Adder
87.189
3151751LOISA D
Adder
8.65
316447AC1-158 HLD
Solar/Wind Helper
11.517
316044AC1-158 PL1
Solar/Wind Helper
5.234
316415AF1-147_GEN2
Solar/Wind Helper
0.794
972205AH1-687 GEN
Adder
7.192
944491AF1-114 GEN
Solar/Wind Harmer
0
3147346CASHSCORNER
Solar/Wind Harmer
0.293
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.386
3138216PACIFIC
Solar/Wind Helper
0.038
CPLELTFEXP_CPLE->PJM
CLTF
12.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.908
LAGNLTFEXP_LAGN->PJM
CLTF
8.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.444
TVALTFEXP_TVA->PJM
CLTF
4.232
NYPJM->LTFIMP_NY
CLTF
3.279
LGEELTFEXP_LGEE->PJM
CLTF
1.357
WECLTFEXP_WEC->PJM
CLTF
0.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.749
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.367
MECLTFEXP_MEC->PJM
CLTF
3.719
SIGELTFEXP_SIGE->PJM
CLTF
0.113

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.2 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5721.05
MW Contribution:
141.28
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.777
971285AH1-108 GEN
50/50
2.015
972263AH1-716 GEN
50/50
141.284
3151081ELIZAR1
50/50
23.729
316233AE1-074 FULL
Solar/Wind Harmer
0.789
971281AH1-106 GEN
Solar/Wind Harmer
4.769
971283AH1-107 GEN
Solar/Wind Harmer
4.769
3143316POE
Solar/Wind Harmer
-0.109
315839AE2-212 C
Solar/Wind Harmer
0.832
970533AG2-339 GEN
Solar/Wind Harmer
18.572
3151091ELIZAR2
Adder
21.974
315697AD1-025 GEN
Solar/Wind Harmer
5.524
316316AC1-027 C
Solar/Wind Harmer
0.838
316236AE1-162_GEN
Solar/Wind Harmer
0.822
971445AH1-216 GEN
Solar/Wind Harmer
16.921
970673AG2-436 GEN
Solar/Wind Harmer
59.791
3151201GRAVEL4
Adder
17.693
3151221GRAVEL6
Adder
17.672
3151191GRAVEL3
Adder
17.469
3151211GRAVEL5
Adder
17.469
970657AG2-426 GEN
Solar/Wind Harmer
1.721
316018AA1-139 ULT2
Solar/Wind Harmer
2.322
957871AF2-081 GEN
Solar/Wind Harmer
13.585
3146406KITTY HAWK
Solar/Wind Harmer
0.023
315833AF1-017_GEN
Solar/Wind Harmer
5.143
316311AC2-079 GEN
Solar/Wind Harmer
13.659
316382AG1-145 C
Solar/Wind Harmer
0.812
316159AE1-175 C
Solar/Wind Harmer
0.723
313526AB2-022
Solar/Wind Harmer
0.722
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
315814AE2-033 C
Solar/Wind Harmer
24.909
3146396TANGLEW
Solar/Wind Harmer
0.492
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971967AH1-528 GEN
Solar/Wind Harmer
50.132
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
957831AF2-077 GEN
Solar/Wind Harmer
0.793
3152251N ANNA1
50/50
20.269
970119AG2-088 GEN
50/50
35.826
3150851SPRUNCC
50/50
1.231
3143096IRON208
50/50
1.092
3152331SURRY 2
50/50
10.034
3150771HOPHCF1
50/50
0.99
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.152
3147666LOUISA
Solar/Wind Harmer
-0.114
940641AE2-051 GEN
Solar/Wind Harmer
26.645
939411AE1-173 GEN
Solar/Wind Harmer
140.751
316192AB2-158 GEN
Solar/Wind Harmer
3.311
3142543TWELFTH
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
11.58
941031AE2-094 GEN
Solar/Wind Harmer
51.784
315671AE2-027_GEN
Solar/Wind Harmer
4.972
944591AF1-124 GEN
Solar/Wind Harmer
125.361
316132AB2-190 GEN1
Solar/Wind Harmer
2.765
316375AC2-012 GEN
Solar/Wind Harmer
9.473
316036AC1-147 C
Solar/Wind Harmer
0.737
3150981CHESPKA
Adder
3.044
971069AG2-661 GEN
Solar/Wind Harmer
4.333
316369SG1_INVT
Solar/Wind Harmer
4.881
3145336SMITFLD
Solar/Wind Harmer
-0.109
961611AG1-000B GEN
Solar/Wind Harmer
13.489
316381AD1-082 GEN
Solar/Wind Harmer
2.499
944631AF1-128 GEN
Adder
115.908
3151171GRAVELC
Adder
2.586
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.547
319010AE1-072 C
Solar/Wind Harmer
5.47
3138126ROCKLANDING
Solar/Wind Harmer
0.083
3142416OLDCHRC
Solar/Wind Harmer
-0.07
3142416OLDCHRC
Solar/Wind Harmer
-0.027
316093AE2-104_GEN
Solar/Wind Harmer
7.831
971317AH1-138 GEN
Solar/Wind Harmer
3.363
315975AC1-164 GENB
Solar/Wind Harmer
0.181
3146516WINFALL
Solar/Wind Harmer
-0.085
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
315611Z1-036_GEN2
Solar/Wind Harmer
6.416
316314AB2-024 C
Solar/Wind Harmer
2.21
3130156CHOWAN
Solar/Wind Harmer
-0.026
971777AH1-397 GEN
Solar/Wind Harmer
3.013
3141766HARMONY
Solar/Wind Harmer
-0.005
3143336POWHATN
Solar/Wind Harmer
3.056
315662AE1-191 GEN
Solar/Wind Harmer
3.095
316280AD1-041 GEN
Solar/Wind Harmer
1.935
970919AG2-571 GEN
Solar/Wind Harmer
8.109
315816AE2-034 GEN
Solar/Wind Harmer
2.044
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.741
970087AG2-069 GEN
Solar/Wind Harmer
23.717
3138133OCRAN
Solar/Wind Harmer
-0.015
315737AD1-076 GEN
Solar/Wind Harmer
4.712
316023GEN1_S
Solar/Wind Harmer
1.67
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.152
3145893MURPHYS
Solar/Wind Harmer
-0.098
3145893MURPHYS
Solar/Wind Harmer
0.729
957481AF2-042 GEN
Solar/Wind Harmer
76.335
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.262
960081AF2-299 GEN
Solar/Wind Harmer
2.723
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.423
966881AG1-559 GEN
Solar/Wind Harmer
0.247
316087AB2-174 GEN
Solar/Wind Harmer
3.418
3146263WOODLND
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
8.983
315693AD1-088 GEN
Solar/Wind Harmer
11.957
316404AE1-155 C
Solar/Wind Harmer
4.552
958261AF2-120 GEN
Solar/Wind Harmer
9.24
3145963POPLR C
Solar/Wind Harmer
-0.024
3145823KELFORD
Solar/Wind Harmer
-0.024
3147043LAWRENC
Adder
1.892
964211AG1-282 GEN
Solar/Wind Harmer
0.705
3141726DUNNSVL
Solar/Wind Harmer
-0.093
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.05
3146293MARTNCO
Solar/Wind Harmer
0.141
316129AC1-054 GEN
Solar/Wind Harmer
1.975
971065AG2-659 GEN
Solar/Wind Harmer
11.249
972197AH1-683 GEN
Adder
4.169
972219AH1-694 GEN
Adder
3.002
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.362
316337AD2-073 GEN
Solar/Wind Harmer
0.587
316131AB2-060 GEN
Solar/Wind Harmer
2.352
315785AD2-033 C
Solar/Wind Harmer
4.921
316034AC1-036 C
Solar/Wind Harmer
0.402
316319Z2-044 C
Solar/Wind Harmer
1.197
3146233WITAKRS
Solar/Wind Harmer
-0.086
961671AG1-007 GEN
Solar/Wind Harmer
0.274
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.643
970685AG2-442 GEN
Solar/Wind Harmer
18.931
970937AG2-583 GEN
Solar/Wind Harmer
15.526
971563AH1-280 GEN
Solar/Wind Harmer
2.7
3144293JTRSVLE
Adder
0.459
3144293JTRSVLE
Adder
0.362
3146926FARMVIL
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316359AB2-059 GEN
Solar/Wind Harmer
2.863
972277AH1-723 GEN
Adder
89.469
3151751LOISA D
Adder
8.294
316447AC1-158 HLD
Solar/Wind Helper
11.566
316044AC1-158 PL1
Solar/Wind Helper
5.256
316415AF1-147_GEN2
Solar/Wind Helper
0.807
944641AF1-129 GEN
50/50
124.35
3150781HOPHCF2
50/50
0.99
3150791HOPHCF3
50/50
0.99
3142366NRTHEST
50/50
0.847
971223AH1-071 GEN
Solar/Wind Harmer
3.774
3143526WINTERP
Solar/Wind Harmer
-0.152
316294AC1-161 GEN
Solar/Wind Harmer
8.95
316240AF1-291 C
Solar/Wind Harmer
0.831
3150991CHESPKB
Adder
2.554
3150991CHESPKB
Adder
2.493
316033AB2-134 GEN
Solar/Wind Harmer
8.813
3150691DARBY 3
Adder
17.517
3150701DARBY 4
Adder
17.476
3150681DARBY 2
Adder
17.456
3150671DARBY 1
Adder
17.435
316185AD1-033 GEN
Solar/Wind Harmer
2.877
316083AB2-161 GEN
Solar/Wind Harmer
4.432
3145506HICKORY
Solar/Wind Harmer
-0.109
3145506HICKORY
Solar/Wind Harmer
-0.065
3145506HICKORY
Solar/Wind Harmer
-0.016
3142296MT RD221
Adder
0.772
316339AD2-160 GEN
Solar/Wind Harmer
1.829
316388AE2-253 GEN
Solar/Wind Harmer
1.829
3142946ENON
Solar/Wind Harmer
-0.003
3137176SLIGO L2192
Solar/Wind Harmer
-0.107
3146456SLIGO L269
Solar/Wind Harmer
3.203
3130086AYDLETT
Solar/Wind Harmer
-0.108
316349AD2-085 GEN
Solar/Wind Harmer
2.404
316312AB1-027
Solar/Wind Harmer
0.91
315835AF2-110_GEN
Solar/Wind Harmer
3.367
972185AH1-677 GEN
Adder
13.435
315976AC1-164 GENA
Solar/Wind Harmer
6.111
316169AC1-164_GENC
Solar/Wind Harmer
5.279
3146386ELIZ CT
Solar/Wind Harmer
-0.027
3144356SAPONY
Solar/Wind Harmer
0.937
316315AB2-025 C
Solar/Wind Harmer
0.722
316431W1029_GEN1
Solar/Wind Harmer
4.816
316433W1029_GEN2
Solar/Wind Harmer
4.816
316435W1029_GEN3
Solar/Wind Harmer
4.816
972187AH1-678 GEN
Adder
6.737
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.502
966871AG1-558 GEN
Solar/Wind Harmer
0.786
966871AG1-558 GEN
Solar/Wind Harmer
0.269
315742AE1-103 GEN
Solar/Wind Harmer
6.17
972189AH1-679 GEN
Adder
3.874
3146376EDENTON
Solar/Wind Harmer
0.767
3146376EDENTON
Solar/Wind Harmer
0.767
316441AF1-014 GEN
Solar/Wind Harmer
1.74
316313AB2-026
Solar/Wind Harmer
0.693
315666AE1-190 GEN
Solar/Wind Harmer
0.774
316156AD2-030 GEN
Solar/Wind Harmer
0.683
315614AA2-178 GEN
Solar/Wind Harmer
2.725
316365GEN2_N
Solar/Wind Harmer
1.67
316065AD1-022 GEN
Solar/Wind Harmer
12.346
316336AC2-165 C
Solar/Wind Harmer
15.352
3145893MURPHYS
Solar/Wind Harmer
0.685
3145893MURPHYS
Solar/Wind Harmer
-0.044
970099AG2-077 GEN
Solar/Wind Harmer
30.534
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316487AF1-042 GEN
Solar/Wind Harmer
3.195
316140AB2-099
Solar/Wind Harmer
0.163
313506AB2-031 GEN
Solar/Wind Harmer
1.917
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
962571AG1-106 GEN
Solar/Wind Harmer
3.419
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
0.196
3145783HORNRTN
Solar/Wind Harmer
2.782
3145783HORNRTN
Solar/Wind Harmer
2.226
3145783HORNRTN
Solar/Wind Harmer
0.696
3145783HORNRTN
Solar/Wind Harmer
0.278
315673AE1-157 GEN
Solar/Wind Harmer
17.576
3145796HORNRTN
Solar/Wind Harmer
-0.07
3150341NORNECKC1
Adder
2.154
3150341NORNECKC1
Adder
2.136
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.023
970301AG2-198 GEN
Solar/Wind Harmer
11.207
3150391LDYSMT3
Adder
26.651
972195AH1-682 GEN
Adder
3.502
316005AA1-067
Solar/Wind Harmer
0.45
3152261N ANNA2
50/50
20.28
3150861SPRUNCD
50/50
1.231
3143096IRON208
50/50
1.092
3143096IRON208
50/50
1.07
3150801HOPHCF4
50/50
1.442
3150761HOPPOLC
50/50
0.62
3151101ELIZAR3
50/50
24.033
3151161SURRY 1
50/50
9.902
3147666LOUISA
Solar/Wind Harmer
-0.066
944011AF1-069 GEN
Solar/Wind Harmer
16.226
315813AE1-149 C
Solar/Wind Harmer
17.178
944581AF1-123 GEN
Solar/Wind Harmer
124.911
944601AF1-125 GEN
Solar/Wind Harmer
122.962
970133AG2-095 GEN
Solar/Wind Harmer
3.088
316458AB2-190 GEN2
Solar/Wind Harmer
2.765
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315778AD1-151 GEN
Solar/Wind Harmer
24.374
3142956BIRDNECK
Solar/Wind Harmer
1.468
3145336SMITFLD
Solar/Wind Harmer
-0.011
961611AG1-000B GEN
Solar/Wind Harmer
5.756
3151171GRAVELC
Adder
3.4
970657AG2-426 GEN
Solar/Wind Harmer
5.515
3142946ENON
Solar/Wind Harmer
-0.009
970293AG2-193 GEN
Solar/Wind Harmer
3.399
316017AA1-139 ULT1
Solar/Wind Harmer
2.193
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.138
3144216WINCHST
Adder
0.91
316305AF2-043 C
Solar/Wind Harmer
0.814
316246AF1-032 C
Solar/Wind Harmer
0.546
3150921YORKTN3
Adder
6.055
3142416OLDCHRC
Solar/Wind Harmer
2.73
316075AC2-137 C
Solar/Wind Harmer
0.727
316320Y1-086
Solar/Wind Harmer
1.572
316321Z2-027
Solar/Wind Harmer
0.719
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.02
316473AC1-191 GEN
Solar/Wind Harmer
2.812
3146376EDENTON
Solar/Wind Harmer
-0.026
3141843SHACKLE
Adder
1.174
316203AE2-005 GEN
Solar/Wind Harmer
10.885
3141766HARMONY
Solar/Wind Harmer
2.295
3143336POWHATN
Solar/Wind Harmer
2.597
3141873WAN 176
Solar/Wind Harmer
3.043
970917AG2-570 GEN
Solar/Wind Harmer
64.063
3156081AA2-088 GEN
Solar/Wind Harmer
8.067
315735AD1-075 GEN1
Solar/Wind Harmer
2.505
3146206CASHIE
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.171
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316484AD2-074 GEN
Solar/Wind Harmer
6.107
961951AG1-038 GEN
Solar/Wind Harmer
3.195
966621AG1-532 GEN
Solar/Wind Harmer
0.491
966881AG1-559 GEN
Solar/Wind Harmer
0.723
3146263WOODLND
Solar/Wind Harmer
-0.024
316181AB2-040 GEN
Solar/Wind Harmer
3.33
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
316011AB1-132 GEN
Solar/Wind Harmer
4.968
3145963POPLR C
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.29
316317KELFORD C
Solar/Wind Harmer
1.095
3145823KELFORD
Solar/Wind Harmer
-0.024
316478AD1-087 GEN
Solar/Wind Harmer
2.029
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.023
316077AC2-138 C
Solar/Wind Harmer
0.486
3150351NORNECKC2
Adder
2.085
316212AC1-099_GEN
Solar/Wind Harmer
1.988
3145933PARMELE
Solar/Wind Harmer
-0.023
3150401LDYSMT4
Adder
26.701
3150371LDYSMT1
Adder
25.801
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
315722AD1-056 GEN
Solar/Wind Harmer
7.917
971781AH1-399 GEN
Solar/Wind Harmer
1.369
964241AG1-285 GEN
Solar/Wind Harmer
17.047
316420AA1-050 GEN
Solar/Wind Harmer
2.482
970257AG2-171 GEN
Solar/Wind Harmer
8.148
971775AH1-396 GEN
Solar/Wind Harmer
1.533
959311AF2-222 GEN
Solar/Wind Harmer
22.659
3146233WITAKRS
Solar/Wind Harmer
0.454
3146233WITAKRS
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
3138543CONSLDL
Solar/Wind Harmer
-0.014
3144293JTRSVLE
Adder
0.459
3147133PAMPLIN
Solar/Wind Harmer
-0.067
942461AE2-259 GEN
Solar/Wind Harmer
3.223
3146926FARMVIL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.477
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.021
972255AH1-712 GEN
Adder
76.777
3151761LOISA E
Adder
16.91
3151721LOISA A
Adder
8.252
3141196NOKESVL
Solar/Wind Helper
1.154
3138283WHITEMARSH
Solar/Wind Harmer
0.041
3143873LANEXA
Solar/Wind Harmer
-0.015
315800Z1-036_GEN1
Solar/Wind Harmer
6.416
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
316059AD1-063 C
Solar/Wind Harmer
0.581
316258AE1-075 C
Solar/Wind Harmer
0.623
316405AF2-144 C
Solar/Wind Harmer
0.658
957601AF2-054 GEN
Solar/Wind Harmer
0.767
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.812
970581AG2-369 GEN
Solar/Wind Harmer
13.598
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.013
315733AD1-074 GEN2
Solar/Wind Harmer
5.013
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.766
316318V4-068
Solar/Wind Harmer
0.612
3145893MURPHYS
Solar/Wind Harmer
-0.066
3145893MURPHYS
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.391
3145513AHOSKIE
Solar/Wind Harmer
0.211
961941AG1-037 GEN
Solar/Wind Harmer
0.182
3145513AHOSKIE
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.542
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.048
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315652AC1-086 GEN
Solar/Wind Harmer
26.76
3137643SOCKMAN
Solar/Wind Harmer
-0.094
316426AA2-053 GEN
Solar/Wind Harmer
2.386
316174AB2-169 GEN
Solar/Wind Harmer
3.622
316486AD2-202 GEN
Solar/Wind Harmer
0.594
3145796HORNRTN
Solar/Wind Harmer
-0.074
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.092
3141813NORNECK
Solar/Wind Harmer
-0.023
316210AC1-098 GEN
Solar/Wind Harmer
3.579
970831AG2-522 GEN
Solar/Wind Harmer
11.352
316274AC1-208 GEN
Solar/Wind Harmer
2.442
3150411LDYSMT5
Adder
26.785
3150381LDYSMT2
Adder
25.634
972213AH1-691 GEN
Adder
4.336
972215AH1-692 GEN
Adder
4.336
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316468AD1-105 GEN
Solar/Wind Harmer
2.538
316327AA2-057 GEN
Solar/Wind Harmer
2.222
957861AF2-080 GEN
Solar/Wind Harmer
9.605
316238AB2-078_GEN
Solar/Wind Harmer
0.656
316239AB2-077_GEN
Solar/Wind Harmer
0.656
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
15.3
970681AG2-440 GEN
Solar/Wind Harmer
10.155
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
946301AF1-294 GEN
Solar/Wind Harmer
5.536
961791AG1-021 GEN
Solar/Wind Harmer
2.7
972205AH1-687 GEN
Adder
7.252
316164AC1-076 GEN
Solar/Wind Helper
2.196
315651AD1-115 GEN
Solar/Wind Helper
1.028
3138216PACIFIC
Solar/Wind Helper
0.039
315724AD1-057 GEN
Solar/Wind Harmer
4.354
315687AD1-152 GEN
Solar/Wind Harmer
2.662
313527AB2-043 GEN
Solar/Wind Harmer
3.551
316237AB2-079_GEN
Solar/Wind Harmer
0.656
970323AG2-213 GEN
Solar/Wind Harmer
10.863
3145493TOT1
Solar/Wind Harmer
0.335
3145453TOT5
Solar/Wind Harmer
0.201
3145603CNETO
Solar/Wind Harmer
0.134
958211AF2-115 GEN
Solar/Wind Harmer
3.375
3144293JTRSVLE
Adder
0.459
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3147133PAMPLIN
Solar/Wind Harmer
-0.017
961601AG1-000A GEN
Solar/Wind Harmer
8.371
316049AB1-081 GEN
Solar/Wind Harmer
2.29
972193AH1-681 GEN
Adder
3.43
3151731LOISA B
Adder
8.294
316045AC1-158 PL2
Solar/Wind Helper
16.819
316450AC1-158 RIC
Solar/Wind Helper
1.402
316006AB2-029 C
Solar/Wind Helper
0.153
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316263AC1-034 GEN
Solar/Wind Harmer
9.01
CPLELTFEXP_CPLE->PJM
CLTF
12.294
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.637
LAGNLTFEXP_LAGN->PJM
CLTF
8.496
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.845
TVALTFEXP_TVA->PJM
CLTF
4.302
NYPJM->LTFIMP_NY
CLTF
3.323
LGEELTFEXP_LGEE->PJM
CLTF
1.383
WECLTFEXP_WEC->PJM
CLTF
0.668
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.182
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.606
MECLTFEXP_MEC->PJM
CLTF
3.787
SIGELTFEXP_SIGE->PJM
CLTF
0.115

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 568_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 568_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.89 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4633.88
MW Contribution:
123.08
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
19.18
3150861SPRUNCD
50/50
1.078
3151101ELIZAR3
50/50
21.096
3143096IRON208
50/50
0.947
3143096IRON208
50/50
0.928
3151161SURRY 1
50/50
8.651
3147666LOUISA
Solar/Wind Harmer
0.573
944011AF1-069 GEN
Solar/Wind Harmer
13.227
944581AF1-123 GEN
Solar/Wind Harmer
48.328
944601AF1-125 GEN
Solar/Wind Harmer
47.584
315813AE1-149 C
Solar/Wind Harmer
11.452
3144873MCLAUGH
Solar/Wind Harmer
0.005
3144536CHRHLND
Solar/Wind Harmer
0.032
970657AG2-426 GEN
Solar/Wind Harmer
4.788
3145336SMITFLD
Solar/Wind Harmer
0.085
970133AG2-095 GEN
Solar/Wind Harmer
2.041
316458AB2-190 GEN2
Solar/Wind Harmer
1.134
315778AD1-151 GEN
Solar/Wind Harmer
17.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.113
961611AG1-000B GEN
Solar/Wind Harmer
5.664
3151171GRAVELC
Adder
2.971
3146456SLIGO L269
Solar/Wind Harmer
0.212
971153AH1-033 GEN
Solar/Wind Harmer
2.451
316246AF1-032 C
Solar/Wind Harmer
0.094
3144216WINCHST
Adder
0.791
3150921YORKTN3
Adder
5.261
316321Z2-027
Solar/Wind Harmer
0.037
3142946ENON
Solar/Wind Harmer
0.07
970293AG2-193 GEN
Solar/Wind Harmer
2.221
3146516WINFALL
Solar/Wind Harmer
0.207
316075AC2-137 C
Solar/Wind Harmer
0.055
3146626S HERTFORD
Solar/Wind Harmer
0.206
3142416OLDCHRC
Solar/Wind Harmer
1.998
3145273HOLLAND
Solar/Wind Harmer
0.154
3143336POWHATN
Solar/Wind Harmer
3.113
970917AG2-570 GEN
Solar/Wind Harmer
18.137
3146376EDENTON
Solar/Wind Harmer
0.203
3142433PROV 92
Adder
0.394
3142433PROV 92
Adder
0.394
316473AC1-191 GEN
Solar/Wind Harmer
0.67
3141843SHACKLE
Adder
1.009
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
2.627
3141873WAN 176
Solar/Wind Harmer
3.486
3156081AA2-088 GEN
Solar/Wind Harmer
0
315735AD1-075 GEN1
Solar/Wind Harmer
0.555
3146206CASHIE
Solar/Wind Harmer
0.193
3145893MURPHYS
Solar/Wind Harmer
0.323
3145893MURPHYS
Solar/Wind Harmer
0.193
3146173TUNIS
Solar/Wind Harmer
0.192
316181AB2-040 GEN
Solar/Wind Harmer
0.269
3146263WOODLND
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.188
316011AB1-132 GEN
Solar/Wind Harmer
3.407
316478AD1-087 GEN
Solar/Wind Harmer
0.649
3145963POPLR C
Solar/Wind Harmer
0.187
3145823KELFORD
Solar/Wind Harmer
0.186
3147043LAWRENC
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.74
3145796HORNRTN
Solar/Wind Harmer
0.185
316212AC1-099_GEN
Solar/Wind Harmer
0.931
3145933PARMELE
Solar/Wind Harmer
0.179
3145746EVERETS
Solar/Wind Harmer
0.176
3145746EVERETS
Solar/Wind Harmer
0.176
315722AD1-056 GEN
Solar/Wind Harmer
6.085
3150401LDYSMT4
Adder
23.49
3150371LDYSMT1
Adder
22.697
3150351NORNECKC2
Adder
1.769
964241AG1-285 GEN
Solar/Wind Harmer
11.603
970257AG2-171 GEN
Solar/Wind Harmer
5.552
971775AH1-396 GEN
Solar/Wind Harmer
0.278
959311AF2-222 GEN
Solar/Wind Harmer
15.414
3144293JTRSVLE
Adder
0.413
3147133PAMPLIN
Solar/Wind Harmer
0.541
942461AE2-259 GEN
Solar/Wind Harmer
0
3146233WITAKRS
Solar/Wind Harmer
0.861
3146233WITAKRS
Solar/Wind Harmer
0.117
3146073TAR RVR
Solar/Wind Harmer
0.171
3146083TARBORO
Solar/Wind Harmer
0.171
3138543CONSLDL
Solar/Wind Harmer
0.113
3146926FARMVIL
Solar/Wind Harmer
0.103
961601AG1-000A GEN
Solar/Wind Harmer
11.999
3145543BTLEBRO
Solar/Wind Harmer
0.169
3145543BTLEBRO
Solar/Wind Harmer
0.169
971623AH1-311 GEN
Solar/Wind Harmer
0.337
971781AH1-399 GEN
Solar/Wind Harmer
0.218
3146776BUCKING
Solar/Wind Harmer
0.059
972003AH1-546 GEN
Solar/Wind Harmer
5.393
316223AC1-118
Solar/Wind Harmer
0.109
3141906WESTMOR
Solar/Wind Harmer
0.061
971683AH1-343 GEN
Solar/Wind Harmer
5.358
970221AG2-151 GEN
Solar/Wind Harmer
7.716
316222AC1-221 GEN
Solar/Wind Harmer
0.596
316283AC2-100 C
Solar/Wind Harmer
0.282
3151761LOISA E
Adder
17.71
3151721LOISA A
Adder
8.642
316123AC1-075 GEN
Solar/Wind Harmer
0.173
270494AE1-108_GEN
Solar/Wind Harmer
1.527
972255AH1-712 GEN
Adder
65.068
315821AE2-092 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
108.491
315242AE2-183_GT2
50/50
3.527
315241AE2-183_GT1
50/50
3.518
972185AH1-677 GEN
50/50
12.75
3150991CHESPKB
50/50
2.379
3150991CHESPKB
50/50
2.322
971223AH1-071 GEN
Solar/Wind Harmer
2.562
3143526WINTERP
Solar/Wind Harmer
1.201
316294AC1-161 GEN
Solar/Wind Harmer
3.734
3145506HICKORY
Solar/Wind Harmer
0.853
3145506HICKORY
Solar/Wind Harmer
0.512
3145506HICKORY
Solar/Wind Harmer
0.128
316339AD2-160 GEN
Solar/Wind Harmer
0.34
316388AE2-253 GEN
Solar/Wind Harmer
0.662
316033AB2-134 GEN
Solar/Wind Harmer
0.001
3137176SLIGO L2192
Solar/Wind Harmer
0.844
3146456SLIGO L269
Solar/Wind Harmer
3.752
3144356SAPONY
Solar/Wind Harmer
1.772
316315AB2-025 C
Solar/Wind Harmer
0.17
3130086AYDLETT
Solar/Wind Harmer
0.847
316349AD2-085 GEN
Solar/Wind Harmer
0.141
972187AH1-678 GEN
Adder
6.026
3142366NRTHEST
Adder
0.688
315835AF2-110_GEN
Solar/Wind Harmer
1.446
3146386ELIZ CT
Solar/Wind Harmer
0.21
3150691DARBY 3
Adder
15.097
3150701DARBY 4
Adder
15.062
3150681DARBY 2
Adder
15.045
3150671DARBY 1
Adder
15.027
3142946ENON
Solar/Wind Harmer
0.021
970933AG2-581 GEN
Solar/Wind Harmer
16.652
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.207
3142296MT RD221
Adder
0.661
3146626S HERTFORD
Solar/Wind Harmer
0.206
3146626S HERTFORD
Solar/Wind Harmer
0.206
316312AB1-027
Solar/Wind Harmer
0.367
316313AB2-026
Solar/Wind Harmer
0.128
315976AC1-164 GENA
Solar/Wind Harmer
2.161
316169AC1-164_GENC
Solar/Wind Harmer
1.867
315742AE1-103 GEN
Solar/Wind Harmer
3.044
3146376EDENTON
Solar/Wind Harmer
0.901
3146376EDENTON
Solar/Wind Harmer
0.901
315614AA2-178 GEN
Solar/Wind Harmer
1.131
972189AH1-679 GEN
Adder
3.327
966871AG1-558 GEN
Solar/Wind Harmer
0.229
316336AC2-165 C
Solar/Wind Harmer
9.982
316365GEN2_N
Solar/Wind Harmer
0.436
316156AD2-030 GEN
Solar/Wind Harmer
0.144
970099AG2-077 GEN
Solar/Wind Harmer
20.771
316065AD1-022 GEN
Solar/Wind Harmer
8.937
3145893MURPHYS
Solar/Wind Harmer
1.293
3145893MURPHYS
Solar/Wind Harmer
0.348
3146173TUNIS
Solar/Wind Harmer
0.192
3146173TUNIS
Solar/Wind Harmer
0.192
316140AB2-099
Solar/Wind Harmer
0.068
313506AB2-031 GEN
Solar/Wind Harmer
0.579
3142666NORTHAMPTON
Solar/Wind Harmer
0.188
3142666NORTHAMPTON
Solar/Wind Harmer
0.188
3142666NORTHAMPTON
Solar/Wind Harmer
0.188
3142666NORTHAMPTON
Solar/Wind Harmer
0.113
962571AG1-106 GEN
Solar/Wind Harmer
2.672
3145593CAROLNA
Solar/Wind Harmer
0.186
3145593CAROLNA
Solar/Wind Harmer
0.186
3145593CAROLNA
Solar/Wind Harmer
0.232
3145783HORNRTN
Solar/Wind Harmer
3.295
3145783HORNRTN
Solar/Wind Harmer
2.636
3145783HORNRTN
Solar/Wind Harmer
0.824
3145783HORNRTN
Solar/Wind Harmer
0.329
3145796HORNRTN
Solar/Wind Harmer
0.555
315673AE1-157 GEN
Solar/Wind Harmer
12.591
3145933PARMELE
Solar/Wind Harmer
0.359
3145933PARMELE
Solar/Wind Harmer
0.179
970301AG2-198 GEN
Solar/Wind Harmer
7.658
316005AA1-067
Solar/Wind Harmer
0.188
315724AD1-057 GEN
Solar/Wind Harmer
3.394
3150391LDYSMT3
Adder
23.446
972195AH1-682 GEN
Adder
3.081
3150341NORNECKC1
Adder
1.828
3152251N ANNA1
50/50
19.17
970119AG2-088 GEN
50/50
32.03
3150851SPRUNCC
50/50
1.078
315243AE2-183_GT3
50/50
3.527
3150981CHESPKA
50/50
2.835
3152331SURRY 2
50/50
8.746
3143096IRON208
50/50
0.947
3147666LOUISA
Solar/Wind Harmer
0.997
316192AB2-158 GEN
Solar/Wind Harmer
1.364
3143226MDLTHAN
Solar/Wind Harmer
0.24
3143526WINTERP
Solar/Wind Harmer
1.201
940641AE2-051 GEN
Solar/Wind Harmer
18.029
939411AE1-173 GEN
Solar/Wind Harmer
94.909
941031AE2-094 GEN
Solar/Wind Harmer
40.481
315773AC2-141 GEN
Solar/Wind Harmer
7.888
3142543TWELFTH
Solar/Wind Harmer
0.021
944591AF1-124 GEN
Solar/Wind Harmer
48.5
315671AE2-027_GEN
Solar/Wind Harmer
0.001
316375AC2-012 GEN
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.038
316381AD1-082 GEN
Solar/Wind Harmer
0.216
3145336SMITFLD
Solar/Wind Harmer
0.852
316132AB2-190 GEN1
Solar/Wind Harmer
1.134
971069AG2-661 GEN
Solar/Wind Harmer
3.778
961611AG1-000B GEN
Solar/Wind Harmer
11.139
3151171GRAVELC
Adder
2.259
3146456SLIGO L269
Solar/Wind Harmer
0.212
319010AE1-072 C
Solar/Wind Harmer
1.057
316072AD1-144
Solar/Wind Harmer
0.075
316093AE2-104_GEN
Solar/Wind Harmer
3.543
944631AF1-128 GEN
Adder
100.322
3138126ROCKLANDING
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.672
3146516WINFALL
Solar/Wind Harmer
0.207
971317AH1-138 GEN
Solar/Wind Harmer
1.55
3142416OLDCHRC
Solar/Wind Harmer
0.536
3142416OLDCHRC
Solar/Wind Harmer
0.205
3143336POWHATN
Solar/Wind Harmer
3.662
315975AC1-164 GENB
Solar/Wind Harmer
0.064
970919AG2-571 GEN
Solar/Wind Harmer
7.255
3130156CHOWAN
Solar/Wind Harmer
0.203
3142433PROV 92
Solar/Wind Harmer
0.81
3142433PROV 92
Adder
0.394
3142433PROV 92
Adder
0.394
970087AG2-069 GEN
Solar/Wind Harmer
16.117
315816AE2-034 GEN
Solar/Wind Harmer
0.848
3145663CRESWEL
Solar/Wind Harmer
0.556
971163AH1-040 GEN
Solar/Wind Harmer
15.901
971777AH1-397 GEN
Solar/Wind Harmer
0.521
3141766HARMONY
Solar/Wind Harmer
0.039
316023GEN1_S
Solar/Wind Harmer
0.436
315737AD1-076 GEN
Solar/Wind Harmer
2.504
957481AF2-042 GEN
Solar/Wind Harmer
51.926
3146206CASHIE
Solar/Wind Harmer
0.193
971547AH1-271 GEN
Solar/Wind Harmer
4.128
3145893MURPHYS
Solar/Wind Harmer
0.773
3145893MURPHYS
Solar/Wind Harmer
0.859
3138133OCRAN
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
0.192
960081AF2-299 GEN
Solar/Wind Harmer
1.838
3156021HOLLOMANSOL
Solar/Wind Harmer
0.86
315693AD1-088 GEN
Solar/Wind Harmer
9.158
3145683EARLEYS
Solar/Wind Harmer
0.19
315607AA1-063A GEN
Solar/Wind Harmer
0.382
3146263WOODLND
Solar/Wind Harmer
0.189
3145963POPLR C
Solar/Wind Harmer
0.187
3145823KELFORD
Solar/Wind Harmer
0.186
3147043LAWRENC
Adder
1.685
966881AG1-559 GEN
Solar/Wind Harmer
0.215
3145783HORNRTN
Solar/Wind Harmer
0.185
3145796HORNRTN
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.185
962861AG1-135 GEN
Solar/Wind Harmer
5.816
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
5.979
3146293MARTNCO
Solar/Wind Harmer
0.166
316129AC1-054 GEN
Solar/Wind Harmer
0.669
971065AG2-659 GEN
Solar/Wind Harmer
7.624
3141726DUNNSVL
Solar/Wind Harmer
0.709
3145746EVERETS
Solar/Wind Harmer
0.176
3145746EVERETS
Solar/Wind Harmer
0.176
972197AH1-683 GEN
Adder
3.668
972219AH1-694 GEN
Adder
2.641
3150351NORNECKC2
Adder
1.74
316131AB2-060 GEN
Solar/Wind Harmer
0.542
970937AG2-583 GEN
Solar/Wind Harmer
10.672
315785AD2-033 C
Solar/Wind Harmer
1.404
316494AC1-189 GEN
Solar/Wind Harmer
0.586
316034AC1-036 C
Solar/Wind Harmer
0.012
970685AG2-442 GEN
Solar/Wind Harmer
12.917
971563AH1-280 GEN
Solar/Wind Harmer
1.843
3144293JTRSVLE
Adder
0.413
3144293JTRSVLE
Adder
0.326
3146233WITAKRS
Solar/Wind Harmer
0.683
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.171
3145493TOT1
Solar/Wind Harmer
0.762
3146926FARMVIL
Solar/Wind Harmer
0.103
3145543BTLEBRO
Solar/Wind Harmer
0.169
3145543BTLEBRO
Solar/Wind Harmer
0.135
316359AB2-059 GEN
Solar/Wind Harmer
0.599
3142053HEARTS
Solar/Wind Harmer
0.297
970401AG2-262 GEN
Solar/Wind Harmer
0.972
316337AD2-073 GEN
Solar/Wind Harmer
0.142
3146776BUCKING
Solar/Wind Harmer
0.065
971377AH1-170 GEN
Solar/Wind Harmer
1.543
3147623JAMES R
Solar/Wind Harmer
0.335
972135AH1-637 GEN
Solar/Wind Harmer
1.169
3151751LOISA D
Adder
8.687
972277AH1-723 GEN
Adder
75.824
316447AC1-158 HLD
Solar/Wind Helper
11.282
316044AC1-158 PL1
Solar/Wind Helper
5.127
316303AF2-085
50/50
4.271
971285AH1-108 GEN
50/50
1.763
3151081ELIZAR1
50/50
20.829
3151091ELIZAR2
50/50
20.468
941591AE2-156 GEN
50/50
19.035
315244AE2-183_ST
50/50
6.125
972263AH1-716 GEN
50/50
123.081
316233AE1-074 FULL
Solar/Wind Harmer
0.185
971281AH1-106 GEN
Solar/Wind Harmer
3.206
971283AH1-107 GEN
Solar/Wind Harmer
3.206
970533AG2-339 GEN
Solar/Wind Harmer
16.607
970673AG2-436 GEN
Solar/Wind Harmer
27.072
3143316POE
Solar/Wind Harmer
0.86
316316AC1-027 C
Solar/Wind Harmer
0.204
970657AG2-426 GEN
Solar/Wind Harmer
1.567
971445AH1-216 GEN
Solar/Wind Harmer
14.995
315697AD1-025 GEN
Solar/Wind Harmer
0.228
957871AF2-081 GEN
Solar/Wind Harmer
10.575
3151201GRAVEL4
Adder
15.458
3151221GRAVEL6
Adder
15.44
3151191GRAVEL3
Adder
15.262
3151211GRAVEL5
Adder
15.262
971967AH1-528 GEN
Solar/Wind Harmer
33.97
3146406KITTY HAWK
Solar/Wind Harmer
0.026
316311AC2-079 GEN
Solar/Wind Harmer
6.08
315814AE2-033 C
Solar/Wind Harmer
16.697
313526AB2-022
Solar/Wind Harmer
0.112
3146486SUNBURY
Solar/Wind Harmer
0.209
3146486SUNBURY
Solar/Wind Harmer
0.209
3146396TANGLEW
Solar/Wind Harmer
0.577
3145176PASQUOTANK
Solar/Wind Harmer
0.13
316159AE1-175 C
Solar/Wind Harmer
0.178
316258AE1-075 C
Solar/Wind Harmer
0.154
3138283WHITEMARSH
Solar/Wind Harmer
0.047
3130156CHOWAN
Solar/Wind Harmer
0.203
3130156CHOWAN
Solar/Wind Harmer
0.203
3142433PROV 92
Adder
0.394
3142433PROV 92
Adder
0.394
970085AG2-068 GEN
Solar/Wind Harmer
10.744
970581AG2-369 GEN
Solar/Wind Harmer
9.24
3143873LANEXA
Solar/Wind Harmer
0.12
970189AG2-124 GEN
Solar/Wind Harmer
5.852
3141873WAN 176
Solar/Wind Harmer
0.039
3130546PLYMOUTH
Solar/Wind Harmer
0.196
315732AD1-074 GEN1
Solar/Wind Harmer
1.112
315733AD1-074 GEN2
Solar/Wind Harmer
1.112
3146206CASHIE
Solar/Wind Harmer
0.193
970601AG2-382 GEN
Solar/Wind Harmer
7.224
3145893MURPHYS
Solar/Wind Harmer
0.522
3145893MURPHYS
Solar/Wind Harmer
0.193
3141913WHIT STONE
Solar/Wind Harmer
0.193
3138133OCRAN
Solar/Wind Harmer
0.058
316463AE2-346 GEN
Solar/Wind Harmer
0.163
3145513AHOSKIE
Solar/Wind Harmer
0.399
3145513AHOSKIE
Solar/Wind Harmer
0.191
3146043SEABORD
Solar/Wind Harmer
0.19
3141783LANCAST
Solar/Wind Harmer
0.114
3141783LANCAST
Solar/Wind Harmer
0.076
3145683EARLEYS
Solar/Wind Harmer
0.38
3145683EARLEYS
Solar/Wind Harmer
0.19
3145683EARLEYS
Solar/Wind Harmer
0.19
315652AC1-086 GEN
Solar/Wind Harmer
20.658
3137643SOCKMAN
Solar/Wind Harmer
0.749
316486AD2-202 GEN
Solar/Wind Harmer
0.191
316426AA2-053 GEN
Solar/Wind Harmer
0.626
3145796HORNRTN
Solar/Wind Harmer
0.592
3145796HORNRTN
Solar/Wind Harmer
0.074
3146033SCOT NK
Solar/Wind Harmer
0.733
316210AC1-098 GEN
Solar/Wind Harmer
1.669
970831AG2-522 GEN
Solar/Wind Harmer
7.686
316274AC1-208 GEN
Solar/Wind Harmer
0.925
3145746EVERETS
Solar/Wind Harmer
0.701
3145746EVERETS
Solar/Wind Harmer
0.176
3145746EVERETS
Solar/Wind Harmer
0.176
3145746EVERETS
Solar/Wind Harmer
0.176
3150411LDYSMT5
Adder
23.563
3150381LDYSMT2
Adder
22.551
972213AH1-691 GEN
Adder
3.815
972215AH1-692 GEN
Adder
3.815
316327AA2-057 GEN
Solar/Wind Harmer
0.258
3141813NORNECK
Solar/Wind Harmer
0.174
957861AF2-080 GEN
Solar/Wind Harmer
7.484
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
10.435
970681AG2-440 GEN
Solar/Wind Harmer
6.926
946301AF1-294 GEN
Solar/Wind Harmer
3.41
961791AG1-021 GEN
Solar/Wind Harmer
1.659
3145573BETHELC
Solar/Wind Harmer
0.171
3145573BETHELC
Solar/Wind Harmer
0.171
971845AH1-439 GEN
Solar/Wind Harmer
7.446
3147173SINAI
Solar/Wind Harmer
0.159
3147243WELCO
Solar/Wind Harmer
0.1
972205AH1-687 GEN
Adder
6.6
944491AF1-114 GEN
Solar/Wind Harmer
0
3147346CASHSCORNER
Solar/Wind Harmer
0.293
316164AC1-076 GEN
Solar/Wind Helper
1.438
3150341NORNECKC1
Adder
1.813
970323AG2-213 GEN
Solar/Wind Harmer
7.403
958211AF2-115 GEN
Solar/Wind Harmer
2.074
3144293JTRSVLE
Adder
0.413
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.138
3145493TOT1
Solar/Wind Harmer
0.397
3145453TOT5
Solar/Wind Harmer
0.238
3145603CNETO
Solar/Wind Harmer
0.159
961601AG1-000A GEN
Solar/Wind Harmer
3
316049AB1-081 GEN
Solar/Wind Harmer
0.96
316263AC1-034 GEN
Solar/Wind Harmer
6.41
962561AG1-105 GEN
Solar/Wind Harmer
8.016
964791AG1-342 GEN
Solar/Wind Harmer
3.181
3146843MT LREL
Solar/Wind Harmer
0.165
3146843MT LREL
Solar/Wind Harmer
0.165
3146776BUCKING
Solar/Wind Harmer
0.654
3146776BUCKING
Solar/Wind Harmer
0.053
316118AC1-105 GEN
Solar/Wind Harmer
0.416
3151731LOISA B
Adder
8.687
972193AH1-681 GEN
Adder
2.907
942751AE2-291 GEN
Solar/Wind Harmer
6.647
316045AC1-158 PL2
Solar/Wind Helper
16.406
316450AC1-158 RIC
Solar/Wind Helper
1.367
316006AB2-029 C
Solar/Wind Helper
0.109
CPLELTFEXP_CPLE->PJM
CLTF
11.039
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.128
LAGNLTFEXP_LAGN->PJM
CLTF
7.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.234
TVALTFEXP_TVA->PJM
CLTF
3.99
NYPJM->LTFIMP_NY
CLTF
3.051
LGEELTFEXP_LGEE->PJM
CLTF
1.357
WECLTFEXP_WEC->PJM
CLTF
0.665
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.454
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.621
MECLTFEXP_MEC->PJM
CLTF
3.673
SIGELTFEXP_SIGE->PJM
CLTF
0.112

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.53 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5615.56
MW Contribution:
138.91
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
20.055
970119AG2-088 GEN
50/50
35.386
3150851SPRUNCC
50/50
1.215
3143096IRON208
50/50
1.077
3152331SURRY 2
50/50
9.863
3150771HOPHCF1
50/50
0.976
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
3147666LOUISA
Solar/Wind Harmer
-0.115
316192AB2-158 GEN
Solar/Wind Harmer
3.331
3152261N ANNA2
50/50
20.065
3150861SPRUNCD
50/50
1.215
3143096IRON208
50/50
1.077
3143096IRON208
50/50
1.055
3150801HOPHCF4
50/50
1.422
3150761HOPPOLC
50/50
0.611
3151101ELIZAR3
50/50
23.654
3151161SURRY 1
50/50
9.75
3147666LOUISA
Solar/Wind Harmer
-0.066
944011AF1-069 GEN
Solar/Wind Harmer
15.995
315813AE1-149 C
Solar/Wind Harmer
16.93
970133AG2-095 GEN
Solar/Wind Harmer
3.043
944581AF1-123 GEN
Solar/Wind Harmer
122.931
944601AF1-125 GEN
Solar/Wind Harmer
121.012
316458AB2-190 GEN2
Solar/Wind Harmer
2.724
315778AD1-151 GEN
Solar/Wind Harmer
24.014
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142956BIRDNECK
Solar/Wind Harmer
1.445
3145336SMITFLD
Solar/Wind Harmer
-0.011
961611AG1-000B GEN
Solar/Wind Harmer
5.669
970657AG2-426 GEN
Solar/Wind Harmer
5.434
3151171GRAVELC
Adder
3.348
970293AG2-193 GEN
Solar/Wind Harmer
3.35
3142946ENON
Solar/Wind Harmer
-0.009
316017AA1-139 ULT1
Solar/Wind Harmer
2.158
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.089
3142416OLDCHRC
Solar/Wind Harmer
2.693
3144216WINCHST
Adder
0.895
316305AF2-043 C
Solar/Wind Harmer
0.801
316246AF1-032 C
Solar/Wind Harmer
0.538
3150921YORKTN3
Adder
5.96
316075AC2-137 C
Solar/Wind Harmer
0.716
316320Y1-086
Solar/Wind Harmer
1.548
316321Z2-027
Solar/Wind Harmer
0.708
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316473AC1-191 GEN
Solar/Wind Harmer
2.782
3141843SHACKLE
Adder
1.159
316203AE2-005 GEN
Solar/Wind Harmer
10.745
3143336POWHATN
Solar/Wind Harmer
2.568
3146376EDENTON
Solar/Wind Harmer
-0.025
3141766HARMONY
Solar/Wind Harmer
2.265
3141873WAN 176
Solar/Wind Harmer
3.004
970917AG2-570 GEN
Solar/Wind Harmer
63.153
966881AG1-559 GEN
Solar/Wind Harmer
0.759
3156081AA2-088 GEN
Solar/Wind Harmer
7.946
315735AD1-075 GEN1
Solar/Wind Harmer
2.467
3150401LDYSMT4
Adder
29.12
3150371LDYSMT1
Adder
28.138
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
316484AD2-074 GEN
Solar/Wind Harmer
6.051
961951AG1-038 GEN
Solar/Wind Harmer
3.166
3146173TUNIS
Solar/Wind Harmer
-0.024
966621AG1-532 GEN
Solar/Wind Harmer
0.484
3146263WOODLND
Solar/Wind Harmer
-0.024
316181AB2-040 GEN
Solar/Wind Harmer
3.282
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
316011AB1-132 GEN
Solar/Wind Harmer
4.895
3145963POPLR C
Solar/Wind Harmer
-0.023
316190AA2-174 GEN
Solar/Wind Harmer
0.286
316317KELFORD C
Solar/Wind Harmer
1.079
3145823KELFORD
Solar/Wind Harmer
-0.023
316478AD1-087 GEN
Solar/Wind Harmer
2.001
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
316077AC2-138 C
Solar/Wind Harmer
0.483
3150351NORNECKC2
Adder
2.072
316212AC1-099_GEN
Solar/Wind Harmer
1.959
3145933PARMELE
Solar/Wind Harmer
-0.022
971781AH1-399 GEN
Solar/Wind Harmer
1.368
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
315722AD1-056 GEN
Solar/Wind Harmer
7.801
964241AG1-285 GEN
Solar/Wind Harmer
16.82
316420AA1-050 GEN
Solar/Wind Harmer
2.445
970257AG2-171 GEN
Solar/Wind Harmer
8.042
971775AH1-396 GEN
Solar/Wind Harmer
1.513
959311AF2-222 GEN
Solar/Wind Harmer
22.367
3146233WITAKRS
Solar/Wind Harmer
0.447
3146233WITAKRS
Solar/Wind Harmer
-0.014
3146073TAR RVR
Solar/Wind Harmer
-0.021
316303AF2-085
50/50
4.718
971285AH1-108 GEN
50/50
1.988
972263AH1-716 GEN
50/50
138.906
3151081ELIZAR1
50/50
23.355
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971281AH1-106 GEN
Solar/Wind Harmer
4.709
971283AH1-107 GEN
Solar/Wind Harmer
4.709
3143316POE
Solar/Wind Harmer
-0.107
315839AE2-212 C
Solar/Wind Harmer
0.82
970533AG2-339 GEN
Solar/Wind Harmer
18.309
3151091ELIZAR2
Adder
21.627
315697AD1-025 GEN
Solar/Wind Harmer
5.442
970673AG2-436 GEN
Solar/Wind Harmer
58.944
316316AC1-027 C
Solar/Wind Harmer
0.825
316236AE1-162_GEN
Solar/Wind Harmer
0.81
971445AH1-216 GEN
Solar/Wind Harmer
16.66
970657AG2-426 GEN
Solar/Wind Harmer
1.696
3151201GRAVEL4
Adder
17.422
3151221GRAVEL6
Adder
17.402
3151191GRAVEL3
Adder
17.202
3151211GRAVEL5
Adder
17.202
316018AA1-139 ULT2
Solar/Wind Harmer
2.285
957871AF2-081 GEN
Solar/Wind Harmer
13.371
315833AF1-017_GEN
Solar/Wind Harmer
5.065
316311AC2-079 GEN
Solar/Wind Harmer
13.452
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316382AG1-145 C
Solar/Wind Harmer
0.8
316159AE1-175 C
Solar/Wind Harmer
0.712
313526AB2-022
Solar/Wind Harmer
0.711
315814AE2-033 C
Solar/Wind Harmer
24.555
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146396TANGLEW
Solar/Wind Harmer
0.484
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
971967AH1-528 GEN
Solar/Wind Harmer
49.426
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
944641AF1-129 GEN
50/50
122.63
3142366NRTHEST
50/50
0.835
3150781HOPHCF2
50/50
0.976
3150791HOPHCF3
50/50
0.976
971223AH1-071 GEN
Solar/Wind Harmer
3.727
3143526WINTERP
Solar/Wind Harmer
-0.15
316294AC1-161 GEN
Solar/Wind Harmer
8.805
316240AF1-291 C
Solar/Wind Harmer
0.819
3150691DARBY 3
Adder
17.276
3150701DARBY 4
Adder
17.236
3150681DARBY 2
Adder
17.216
3150671DARBY 1
Adder
17.196
3150991CHESPKB
Adder
2.514
3150991CHESPKB
Adder
2.453
316033AB2-134 GEN
Solar/Wind Harmer
8.682
316083AB2-161 GEN
Solar/Wind Harmer
4.367
316185AD1-033 GEN
Solar/Wind Harmer
2.832
3142296MT RD221
Adder
0.762
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
3142946ENON
Solar/Wind Harmer
-0.003
316339AD2-160 GEN
Solar/Wind Harmer
1.8
316388AE2-253 GEN
Solar/Wind Harmer
1.8
3137176SLIGO L2192
Solar/Wind Harmer
-0.106
3146456SLIGO L269
Solar/Wind Harmer
3.152
316312AB1-027
Solar/Wind Harmer
0.898
316349AD2-085 GEN
Solar/Wind Harmer
2.368
3130086AYDLETT
Solar/Wind Harmer
-0.106
315835AF2-110_GEN
Solar/Wind Harmer
3.314
972185AH1-677 GEN
Adder
13.245
3144356SAPONY
Solar/Wind Harmer
0.923
316315AB2-025 C
Solar/Wind Harmer
0.712
315976AC1-164 GENA
Solar/Wind Harmer
6.016
316169AC1-164_GENC
Solar/Wind Harmer
5.197
3146386ELIZ CT
Solar/Wind Harmer
-0.026
972189AH1-679 GEN
Adder
3.909
972187AH1-678 GEN
Adder
6.642
316431W1029_GEN1
Solar/Wind Harmer
4.741
316433W1029_GEN2
Solar/Wind Harmer
4.741
316435W1029_GEN3
Solar/Wind Harmer
4.741
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.777
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
24.158
315742AE1-103 GEN
Solar/Wind Harmer
6.076
316441AF1-014 GEN
Solar/Wind Harmer
1.718
316313AB2-026
Solar/Wind Harmer
0.685
3146376EDENTON
Solar/Wind Harmer
0.755
3146376EDENTON
Solar/Wind Harmer
0.755
315666AE1-190 GEN
Solar/Wind Harmer
0.764
316156AD2-030 GEN
Solar/Wind Harmer
0.674
315614AA2-178 GEN
Solar/Wind Harmer
2.683
315673AE1-157 GEN
Solar/Wind Harmer
18.699
316365GEN2_N
Solar/Wind Harmer
1.646
3150391LDYSMT3
Adder
29.065
972195AH1-682 GEN
Adder
3.82
316336AC2-165 C
Solar/Wind Harmer
15.187
316065AD1-022 GEN
Solar/Wind Harmer
12.158
3145893MURPHYS
Solar/Wind Harmer
0.675
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.112
316487AF1-042 GEN
Solar/Wind Harmer
3.166
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316140AB2-099
Solar/Wind Harmer
0.16
313506AB2-031 GEN
Solar/Wind Harmer
1.889
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
962571AG1-106 GEN
Solar/Wind Harmer
3.369
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.742
3145783HORNRTN
Solar/Wind Harmer
2.193
3145783HORNRTN
Solar/Wind Harmer
0.685
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
3150341NORNECKC1
Adder
2.14
3150341NORNECKC1
Adder
2.123
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.022
970301AG2-198 GEN
Solar/Wind Harmer
11.07
316005AA1-067
Solar/Wind Harmer
0.443
315724AD1-057 GEN
Solar/Wind Harmer
4.29
315687AD1-152 GEN
Solar/Wind Harmer
2.625
313527AB2-043 GEN
Solar/Wind Harmer
3.503
316237AB2-079_GEN
Solar/Wind Harmer
0.647
970323AG2-213 GEN
Solar/Wind Harmer
10.723
3145493TOT1
Solar/Wind Harmer
0.33
3145453TOT5
Solar/Wind Harmer
0.198
3145603CNETO
Solar/Wind Harmer
0.132
958211AF2-115 GEN
Solar/Wind Harmer
3.333
3144293JTRSVLE
Adder
0.453
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3147133PAMPLIN
Solar/Wind Harmer
-0.017
961601AG1-000A GEN
Solar/Wind Harmer
8.248
316049AB1-081 GEN
Solar/Wind Harmer
2.257
972193AH1-681 GEN
Adder
3.343
3151731LOISA B
Adder
8.65
316045AC1-158 PL2
Solar/Wind Helper
16.749
316450AC1-158 RIC
Solar/Wind Helper
1.396
316006AB2-029 C
Solar/Wind Helper
0.141
316411AF1-147_GEN1
Solar/Wind Helper
0.794
316263AC1-034 GEN
Solar/Wind Harmer
8.878
957831AF2-077 GEN
Solar/Wind Harmer
0.782
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143873LANEXA
Solar/Wind Harmer
-0.015
315800Z1-036_GEN1
Solar/Wind Harmer
6.317
316258AE1-075 C
Solar/Wind Harmer
0.616
316405AF2-144 C
Solar/Wind Harmer
0.651
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316059AD1-063 C
Solar/Wind Harmer
0.574
957601AF2-054 GEN
Solar/Wind Harmer
0.757
3141873WAN 176
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.025
970085AG2-068 GEN
Solar/Wind Harmer
15.587
970581AG2-369 GEN
Solar/Wind Harmer
13.405
3138133OCRAN
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.936
315733AD1-074 GEN2
Solar/Wind Harmer
4.936
3150411LDYSMT5
Adder
29.211
3150381LDYSMT2
Adder
27.956
972213AH1-691 GEN
Adder
4.729
972215AH1-692 GEN
Adder
4.729
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.602
316318V4-068
Solar/Wind Harmer
0.603
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.534
316463AE2-346 GEN
Solar/Wind Harmer
0.385
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315652AC1-086 GEN
Solar/Wind Harmer
26.368
3137643SOCKMAN
Solar/Wind Harmer
-0.093
316426AA2-053 GEN
Solar/Wind Harmer
2.351
316486AD2-202 GEN
Solar/Wind Harmer
0.586
316174AB2-169 GEN
Solar/Wind Harmer
3.567
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
316210AC1-098 GEN
Solar/Wind Harmer
3.526
970831AG2-522 GEN
Solar/Wind Harmer
11.191
316274AC1-208 GEN
Solar/Wind Harmer
2.407
316468AD1-105 GEN
Solar/Wind Harmer
2.537
3145746EVERETS
Solar/Wind Harmer
-0.087
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316327AA2-057 GEN
Solar/Wind Harmer
2.189
957861AF2-080 GEN
Solar/Wind Harmer
9.462
316238AB2-078_GEN
Solar/Wind Harmer
0.647
316239AB2-077_GEN
Solar/Wind Harmer
0.647
3144303KENBRDG
Solar/Wind Harmer
-0.017
970683AG2-441 GEN
Solar/Wind Harmer
15.105
970681AG2-440 GEN
Solar/Wind Harmer
10.026
3145573BETHELC
Solar/Wind Harmer
-0.021
3145573BETHELC
Solar/Wind Harmer
-0.021
946301AF1-294 GEN
Solar/Wind Harmer
5.467
961791AG1-021 GEN
Solar/Wind Harmer
2.667
972205AH1-687 GEN
Adder
7.192
316164AC1-076 GEN
Solar/Wind Helper
1.386
3138216PACIFIC
Solar/Wind Helper
0.038
940641AE2-051 GEN
Solar/Wind Harmer
26.257
939411AE1-173 GEN
Solar/Wind Harmer
138.658
3142543TWELFTH
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
11.392
941031AE2-094 GEN
Solar/Wind Harmer
51.049
315671AE2-027_GEN
Solar/Wind Harmer
4.903
944591AF1-124 GEN
Solar/Wind Harmer
123.374
316132AB2-190 GEN1
Solar/Wind Harmer
2.724
971069AG2-661 GEN
Solar/Wind Harmer
4.269
316375AC2-012 GEN
Solar/Wind Harmer
9.324
316036AC1-147 C
Solar/Wind Harmer
0.725
3150981CHESPKA
Adder
2.996
316369SG1_INVT
Solar/Wind Harmer
4.808
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.463
944631AF1-128 GEN
Adder
114.228
961611AG1-000B GEN
Solar/Wind Harmer
13.285
3151171GRAVELC
Adder
2.546
3146456SLIGO L269
Solar/Wind Harmer
-0.027
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.538
319010AE1-072 C
Solar/Wind Harmer
5.383
3138126ROCKLANDING
Solar/Wind Harmer
0.082
316093AE2-104_GEN
Solar/Wind Harmer
7.709
971317AH1-138 GEN
Solar/Wind Harmer
3.311
315975AC1-164 GENB
Solar/Wind Harmer
0.178
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
315611Z1-036_GEN2
Solar/Wind Harmer
6.317
316314AB2-024 C
Solar/Wind Harmer
2.181
971777AH1-397 GEN
Solar/Wind Harmer
2.974
3143336POWHATN
Solar/Wind Harmer
3.022
3130156CHOWAN
Solar/Wind Harmer
-0.025
3141766HARMONY
Solar/Wind Harmer
-0.005
315662AE1-191 GEN
Solar/Wind Harmer
3.056
316280AD1-041 GEN
Solar/Wind Harmer
1.91
970919AG2-571 GEN
Solar/Wind Harmer
7.994
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
23.38
315816AE2-034 GEN
Solar/Wind Harmer
2.012
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.376
3138133OCRAN
Solar/Wind Harmer
-0.015
316023GEN1_S
Solar/Wind Harmer
1.646
315737AD1-076 GEN
Solar/Wind Harmer
4.64
972197AH1-683 GEN
Adder
4.547
972219AH1-694 GEN
Adder
3.274
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.058
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.718
957481AF2-042 GEN
Solar/Wind Harmer
75.28
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.213
960081AF2-299 GEN
Solar/Wind Harmer
2.684
962861AG1-135 GEN
Solar/Wind Harmer
8.908
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.387
316087AB2-174 GEN
Solar/Wind Harmer
3.369
316404AE1-155 C
Solar/Wind Harmer
4.515
958261AF2-120 GEN
Solar/Wind Harmer
9.165
3146263WOODLND
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.795
3145963POPLR C
Solar/Wind Harmer
-0.023
3145823KELFORD
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.7
3141726DUNNSVL
Solar/Wind Harmer
-0.093
3147043LAWRENC
Adder
1.865
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.038
3146293MARTNCO
Solar/Wind Harmer
0.139
316129AC1-054 GEN
Solar/Wind Harmer
1.947
971065AG2-659 GEN
Solar/Wind Harmer
11.09
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316337AD2-073 GEN
Solar/Wind Harmer
0.585
316494AC1-189 GEN
Solar/Wind Harmer
2.327
316131AB2-060 GEN
Solar/Wind Harmer
2.32
315785AD2-033 C
Solar/Wind Harmer
4.857
316034AC1-036 C
Solar/Wind Harmer
0.397
970937AG2-583 GEN
Solar/Wind Harmer
15.377
970685AG2-442 GEN
Solar/Wind Harmer
18.693
316319Z2-044 C
Solar/Wind Harmer
1.18
3146233WITAKRS
Solar/Wind Harmer
-0.085
961671AG1-007 GEN
Solar/Wind Harmer
0.27
3146083TARBORO
Solar/Wind Harmer
-0.021
3145493TOT1
Solar/Wind Harmer
0.633
971563AH1-280 GEN
Solar/Wind Harmer
2.667
3144293JTRSVLE
Adder
0.453
3144293JTRSVLE
Adder
0.358
3146926FARMVIL
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316359AB2-059 GEN
Solar/Wind Harmer
2.821
972277AH1-723 GEN
Adder
87.189
3151751LOISA D
Adder
8.65
316447AC1-158 HLD
Solar/Wind Helper
11.517
316044AC1-158 PL1
Solar/Wind Helper
5.234
316415AF1-147_GEN2
Solar/Wind Helper
0.794
3146083TARBORO
Solar/Wind Harmer
-0.021
3144293JTRSVLE
Adder
0.453
3138543CONSLDL
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.067
942461AE2-259 GEN
Solar/Wind Harmer
3.185
3146926FARMVIL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.352
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.021
972255AH1-712 GEN
Adder
74.821
3151761LOISA E
Adder
17.635
3151721LOISA A
Adder
8.605
3141196NOKESVL
Solar/Wind Helper
1.133
CPLELTFEXP_CPLE->PJM
CLTF
12.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.908
LAGNLTFEXP_LAGN->PJM
CLTF
8.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.444
TVALTFEXP_TVA->PJM
CLTF
4.232
NYPJM->LTFIMP_NY
CLTF
3.279
LGEELTFEXP_LGEE->PJM
CLTF
1.357
WECLTFEXP_WEC->PJM
CLTF
0.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.749
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.367
MECLTFEXP_MEC->PJM
CLTF
3.719
SIGELTFEXP_SIGE->PJM
CLTF
0.113

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.59 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5814.94
MW Contribution:
136.54
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
944641AF1-129 GEN
50/50
120.203
3150781HOPHCF2
50/50
0.957
3150791HOPHCF3
50/50
0.957
3142366NRTHEST
50/50
0.818
316045AC1-158 PL2
Solar/Wind Harmer
21.873
316450AC1-158 RIC
Solar/Wind Harmer
1.823
971223AH1-071 GEN
Solar/Wind Harmer
3.656
3143526WINTERP
Solar/Wind Harmer
-0.147
316294AC1-161 GEN
Solar/Wind Harmer
8.651
316240AF1-291 C
Solar/Wind Harmer
0.803
3150991CHESPKB
Adder
2.468
3150991CHESPKB
Adder
2.409
316033AB2-134 GEN
Solar/Wind Harmer
8.518
3150691DARBY 3
Adder
16.928
3150701DARBY 4
Adder
16.889
3150681DARBY 2
Adder
16.869
3150671DARBY 1
Adder
16.849
316185AD1-033 GEN
Solar/Wind Harmer
2.781
316083AB2-161 GEN
Solar/Wind Harmer
4.285
3145506HICKORY
Solar/Wind Harmer
-0.105
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
3142296MT RD221
Adder
0.746
316339AD2-160 GEN
Solar/Wind Harmer
1.768
316388AE2-253 GEN
Solar/Wind Harmer
1.768
3142946ENON
Solar/Wind Harmer
-0.003
3137176SLIGO L2192
Solar/Wind Harmer
-0.104
3146456SLIGO L269
Solar/Wind Harmer
3.096
316349AD2-085 GEN
Solar/Wind Harmer
2.324
3130086AYDLETT
Solar/Wind Harmer
-0.104
316312AB1-027
Solar/Wind Harmer
0.879
315835AF2-110_GEN
Solar/Wind Harmer
3.254
972185AH1-677 GEN
Adder
12.993
315976AC1-164 GENA
Solar/Wind Harmer
5.903
316169AC1-164_GENC
Solar/Wind Harmer
5.1
3144356SAPONY
Solar/Wind Harmer
0.906
316315AB2-025 C
Solar/Wind Harmer
0.698
3146386ELIZ CT
Solar/Wind Harmer
-0.026
972187AH1-678 GEN
Adder
6.516
316431W1029_GEN1
Solar/Wind Harmer
4.655
316433W1029_GEN2
Solar/Wind Harmer
4.655
316435W1029_GEN3
Solar/Wind Harmer
4.655
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
970933AG2-581 GEN
Solar/Wind Harmer
23.719
966871AG1-558 GEN
Solar/Wind Harmer
0.759
966871AG1-558 GEN
Solar/Wind Harmer
0.26
316313AB2-026
Solar/Wind Harmer
0.677
315742AE1-103 GEN
Solar/Wind Harmer
5.965
972189AH1-679 GEN
Adder
3.738
3146376EDENTON
Solar/Wind Harmer
0.742
3146376EDENTON
Solar/Wind Harmer
0.742
316441AF1-014 GEN
Solar/Wind Harmer
1.68
315666AE1-190 GEN
Solar/Wind Harmer
0.747
316156AD2-030 GEN
Solar/Wind Harmer
0.659
315614AA2-178 GEN
Solar/Wind Harmer
2.634
316336AC2-165 C
Solar/Wind Harmer
15.058
316365GEN2_N
Solar/Wind Harmer
1.615
316065AD1-022 GEN
Solar/Wind Harmer
11.934
3145893MURPHYS
Solar/Wind Harmer
0.662
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
29.598
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316140AB2-099
Solar/Wind Harmer
0.157
316487AF1-042 GEN
Solar/Wind Harmer
3.083
313506AB2-031 GEN
Solar/Wind Harmer
1.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
962571AG1-106 GEN
Solar/Wind Harmer
3.306
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
0.19
3145783HORNRTN
Solar/Wind Harmer
2.692
3145783HORNRTN
Solar/Wind Harmer
2.153
3145783HORNRTN
Solar/Wind Harmer
0.673
3145783HORNRTN
Solar/Wind Harmer
0.269
3145796HORNRTN
Solar/Wind Harmer
-0.068
315673AE1-157 GEN
Solar/Wind Harmer
16.906
3150341NORNECKC1
Adder
2.076
3150341NORNECKC1
Adder
2.06
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
3152261N ANNA2
50/50
19.573
3150861SPRUNCD
50/50
1.191
3143096IRON208
50/50
1.055
3143096IRON208
50/50
1.034
3150801HOPHCF4
50/50
1.394
3150761HOPPOLC
50/50
0.599
3151101ELIZAR3
50/50
23.229
3151161SURRY 1
50/50
9.57
3147666LOUISA
Solar/Wind Harmer
-0.069
944011AF1-069 GEN
Solar/Wind Harmer
15.691
315813AE1-149 C
Solar/Wind Harmer
16.605
944581AF1-123 GEN
Solar/Wind Harmer
120.737
944601AF1-125 GEN
Solar/Wind Harmer
118.853
970133AG2-095 GEN
Solar/Wind Harmer
2.984
316458AB2-190 GEN2
Solar/Wind Harmer
2.672
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315778AD1-151 GEN
Solar/Wind Harmer
23.558
3142956BIRDNECK
Solar/Wind Harmer
1.419
3145336SMITFLD
Solar/Wind Harmer
-0.01
961611AG1-000B GEN
Solar/Wind Harmer
5.563
970657AG2-426 GEN
Solar/Wind Harmer
5.331
3151171GRAVELC
Adder
3.286
3142946ENON
Solar/Wind Harmer
-0.009
970293AG2-193 GEN
Solar/Wind Harmer
3.284
316017AA1-139 ULT1
Solar/Wind Harmer
2.119
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.033
3144216WINCHST
Adder
0.879
316305AF2-043 C
Solar/Wind Harmer
0.787
316246AF1-032 C
Solar/Wind Harmer
0.528
3150921YORKTN3
Adder
5.851
3142416OLDCHRC
Solar/Wind Harmer
2.638
316075AC2-137 C
Solar/Wind Harmer
0.702
316320Y1-086
Solar/Wind Harmer
1.52
316321Z2-027
Solar/Wind Harmer
0.695
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.441
3142433PROV 92
Adder
0.441
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
316473AC1-191 GEN
Solar/Wind Harmer
2.715
3143336POWHATN
Solar/Wind Harmer
2.54
3146376EDENTON
Solar/Wind Harmer
-0.025
3141843SHACKLE
Adder
1.134
316203AE2-005 GEN
Solar/Wind Harmer
10.51
3141766HARMONY
Solar/Wind Harmer
2.216
970917AG2-570 GEN
Solar/Wind Harmer
61.952
3141873WAN 176
Solar/Wind Harmer
2.938
3156081AA2-088 GEN
Solar/Wind Harmer
7.801
315735AD1-075 GEN1
Solar/Wind Harmer
2.422
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.166
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.023
966621AG1-532 GEN
Solar/Wind Harmer
0.475
316484AD2-074 GEN
Solar/Wind Harmer
5.891
961951AG1-038 GEN
Solar/Wind Harmer
3.083
3146263WOODLND
Solar/Wind Harmer
-0.023
966881AG1-559 GEN
Solar/Wind Harmer
0.696
316181AB2-040 GEN
Solar/Wind Harmer
3.222
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
316011AB1-132 GEN
Solar/Wind Harmer
4.804
3145963POPLR C
Solar/Wind Harmer
-0.023
316190AA2-174 GEN
Solar/Wind Harmer
0.281
316317KELFORD C
Solar/Wind Harmer
1.059
3145823KELFORD
Solar/Wind Harmer
-0.023
316478AD1-087 GEN
Solar/Wind Harmer
1.967
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.023
316077AC2-138 C
Solar/Wind Harmer
0.469
3150351NORNECKC2
Adder
2.01
316212AC1-099_GEN
Solar/Wind Harmer
1.923
3145933PARMELE
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
315722AD1-056 GEN
Solar/Wind Harmer
7.653
3150401LDYSMT4
Adder
25.644
3150371LDYSMT1
Adder
24.779
971781AH1-399 GEN
Solar/Wind Harmer
1.318
964241AG1-285 GEN
Solar/Wind Harmer
16.582
970257AG2-171 GEN
Solar/Wind Harmer
7.941
971775AH1-396 GEN
Solar/Wind Harmer
1.494
959311AF2-222 GEN
Solar/Wind Harmer
22.094
3144293JTRSVLE
Adder
0.449
3147133PAMPLIN
Solar/Wind Harmer
-0.066
316420AA1-050 GEN
Solar/Wind Harmer
2.399
942461AE2-259 GEN
Solar/Wind Harmer
3.161
3146926FARMVIL
Solar/Wind Harmer
-0.012
3146233WITAKRS
Solar/Wind Harmer
0.439
3146233WITAKRS
Solar/Wind Harmer
-0.014
3146073TAR RVR
Solar/Wind Harmer
-0.021
3146083TARBORO
Solar/Wind Harmer
-0.021
3138543CONSLDL
Solar/Wind Harmer
-0.014
3151761LOISA E
Adder
21.14
3151721LOISA A
Adder
10.316
972255AH1-712 GEN
Adder
74.706
3141196NOKESVL
Solar/Wind Helper
1.14
961601AG1-000A GEN
Solar/Wind Harmer
7.419
316303AF2-085
50/50
4.628
971285AH1-108 GEN
50/50
1.949
972263AH1-716 GEN
50/50
136.539
3151081ELIZAR1
50/50
22.936
316233AE1-074 FULL
Solar/Wind Harmer
0.764
971281AH1-106 GEN
Solar/Wind Harmer
4.617
971283AH1-107 GEN
Solar/Wind Harmer
4.617
3143316POE
Solar/Wind Harmer
-0.105
315839AE2-212 C
Solar/Wind Harmer
0.804
970533AG2-339 GEN
Solar/Wind Harmer
17.96
3151091ELIZAR2
Adder
21.239
315697AD1-025 GEN
Solar/Wind Harmer
5.339
316316AC1-027 C
Solar/Wind Harmer
0.81
316236AE1-162_GEN
Solar/Wind Harmer
0.795
970673AG2-436 GEN
Solar/Wind Harmer
57.823
971445AH1-216 GEN
Solar/Wind Harmer
16.355
3151201GRAVEL4
Adder
17.1
3151221GRAVEL6
Adder
17.08
3151191GRAVEL3
Adder
16.884
3151211GRAVEL5
Adder
16.884
970657AG2-426 GEN
Solar/Wind Harmer
1.664
316164AC1-076 GEN
Solar/Wind Harmer
2.217
316018AA1-139 ULT2
Solar/Wind Harmer
2.244
957871AF2-081 GEN
Solar/Wind Harmer
13.131
315833AF1-017_GEN
Solar/Wind Harmer
4.971
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316311AC2-079 GEN
Solar/Wind Harmer
13.204
316382AG1-145 C
Solar/Wind Harmer
0.785
316159AE1-175 C
Solar/Wind Harmer
0.699
313526AB2-022
Solar/Wind Harmer
0.698
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
315814AE2-033 C
Solar/Wind Harmer
24.085
3146396TANGLEW
Solar/Wind Harmer
0.476
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
971967AH1-528 GEN
Solar/Wind Harmer
48.508
3142433PROV 92
Adder
0.441
3142433PROV 92
Adder
0.441
957831AF2-077 GEN
Solar/Wind Harmer
0.766
3138283WHITEMARSH
Solar/Wind Harmer
0.039
316258AE1-075 C
Solar/Wind Harmer
0.61
316405AF2-144 C
Solar/Wind Harmer
0.643
3143873LANEXA
Solar/Wind Harmer
-0.015
315800Z1-036_GEN1
Solar/Wind Harmer
6.202
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316059AD1-063 C
Solar/Wind Harmer
0.561
957601AF2-054 GEN
Solar/Wind Harmer
0.74
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.29
970581AG2-369 GEN
Solar/Wind Harmer
13.149
3141913WHIT STONE
Solar/Wind Harmer
-0.024
3138133OCRAN
Solar/Wind Harmer
-0.007
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
3141783LANCAST
Solar/Wind Harmer
-0.014
3141783LANCAST
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
4.845
315733AD1-074 GEN2
Solar/Wind Harmer
4.845
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.407
316318V4-068
Solar/Wind Harmer
0.592
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.525
316463AE2-346 GEN
Solar/Wind Harmer
0.378
3145513AHOSKIE
Solar/Wind Harmer
0.204
961941AG1-037 GEN
Solar/Wind Harmer
0.176
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
315652AC1-086 GEN
Solar/Wind Harmer
25.875
3137643SOCKMAN
Solar/Wind Harmer
-0.091
316426AA2-053 GEN
Solar/Wind Harmer
2.308
316486AD2-202 GEN
Solar/Wind Harmer
0.576
316174AB2-169 GEN
Solar/Wind Harmer
3.5
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.089
3141813NORNECK
Solar/Wind Harmer
-0.022
316210AC1-098 GEN
Solar/Wind Harmer
3.461
970831AG2-522 GEN
Solar/Wind Harmer
10.996
316274AC1-208 GEN
Solar/Wind Harmer
2.362
3145746EVERETS
Solar/Wind Harmer
-0.085
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3150411LDYSMT5
Adder
25.724
3150381LDYSMT2
Adder
24.619
972213AH1-691 GEN
Adder
4.165
972215AH1-692 GEN
Adder
4.165
316468AD1-105 GEN
Solar/Wind Harmer
2.445
316327AA2-057 GEN
Solar/Wind Harmer
2.148
957861AF2-080 GEN
Solar/Wind Harmer
9.283
316238AB2-078_GEN
Solar/Wind Harmer
0.637
316239AB2-077_GEN
Solar/Wind Harmer
0.637
3144303KENBRDG
Solar/Wind Harmer
-0.017
3152251N ANNA1
50/50
19.563
970119AG2-088 GEN
50/50
34.71
3150851SPRUNCC
50/50
1.191
3143096IRON208
50/50
1.055
3152331SURRY 2
50/50
9.697
3150771HOPHCF1
50/50
0.957
316447AC1-158 HLD
Solar/Wind Harmer
15.034
316044AC1-158 PL1
Solar/Wind Harmer
6.835
3147666LOUISA
Solar/Wind Harmer
-0.12
316192AB2-158 GEN
Solar/Wind Harmer
3.493
3143226MDLTHAN
Solar/Wind Harmer
-0.029
3143526WINTERP
Solar/Wind Harmer
-0.147
940641AE2-051 GEN
Solar/Wind Harmer
25.761
939411AE1-173 GEN
Solar/Wind Harmer
136.075
3142543TWELFTH
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
11.193
941031AE2-094 GEN
Solar/Wind Harmer
50.077
315671AE2-027_GEN
Solar/Wind Harmer
4.806
944591AF1-124 GEN
Solar/Wind Harmer
121.172
316132AB2-190 GEN1
Solar/Wind Harmer
2.672
316375AC2-012 GEN
Solar/Wind Harmer
9.157
316036AC1-147 C
Solar/Wind Harmer
0.712
3150981CHESPKA
Adder
2.942
971069AG2-661 GEN
Solar/Wind Harmer
4.188
316369SG1_INVT
Solar/Wind Harmer
4.718
3145336SMITFLD
Solar/Wind Harmer
-0.105
316381AD1-082 GEN
Solar/Wind Harmer
2.416
961611AG1-000B GEN
Solar/Wind Harmer
13.038
944631AF1-128 GEN
Adder
112.018
3151171GRAVELC
Adder
2.499
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.529
319010AE1-072 C
Solar/Wind Harmer
5.287
3138126ROCKLANDING
Solar/Wind Harmer
0.08
3142416OLDCHRC
Solar/Wind Harmer
-0.068
3142416OLDCHRC
Solar/Wind Harmer
-0.026
316093AE2-104_GEN
Solar/Wind Harmer
7.569
971317AH1-138 GEN
Solar/Wind Harmer
3.249
315975AC1-164 GENB
Solar/Wind Harmer
0.175
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.102
3142433PROV 92
Adder
0.441
3142433PROV 92
Adder
0.441
3143336POWHATN
Solar/Wind Harmer
2.988
315611Z1-036_GEN2
Solar/Wind Harmer
6.202
3130156CHOWAN
Solar/Wind Harmer
-0.025
316314AB2-024 C
Solar/Wind Harmer
2.134
971777AH1-397 GEN
Solar/Wind Harmer
2.909
3141766HARMONY
Solar/Wind Harmer
-0.005
315662AE1-191 GEN
Solar/Wind Harmer
2.989
316280AD1-041 GEN
Solar/Wind Harmer
1.868
970919AG2-571 GEN
Solar/Wind Harmer
7.842
315816AE2-034 GEN
Solar/Wind Harmer
1.975
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.948
970087AG2-069 GEN
Solar/Wind Harmer
22.935
3138133OCRAN
Solar/Wind Harmer
-0.014
316023GEN1_S
Solar/Wind Harmer
1.615
315737AD1-076 GEN
Solar/Wind Harmer
4.555
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.947
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.705
957481AF2-042 GEN
Solar/Wind Harmer
73.995
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.153
960081AF2-299 GEN
Solar/Wind Harmer
2.635
3145683EARLEYS
Solar/Wind Harmer
-0.023
315607AA1-063A GEN
Solar/Wind Harmer
2.344
316087AB2-174 GEN
Solar/Wind Harmer
3.308
315693AD1-088 GEN
Solar/Wind Harmer
11.61
3146263WOODLND
Solar/Wind Harmer
-0.023
966881AG1-559 GEN
Solar/Wind Harmer
0.238
962861AG1-135 GEN
Solar/Wind Harmer
8.665
316404AE1-155 C
Solar/Wind Harmer
4.39
958261AF2-120 GEN
Solar/Wind Harmer
8.912
3145963POPLR C
Solar/Wind Harmer
-0.023
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Adder
1.833
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.074
3145796HORNRTN
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.68
3141726DUNNSVL
Solar/Wind Harmer
-0.09
3150351NORNECKC2
Adder
1.977
3146293MARTNCO
Solar/Wind Harmer
0.136
316129AC1-054 GEN
Solar/Wind Harmer
1.913
971065AG2-659 GEN
Solar/Wind Harmer
10.9
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
972197AH1-683 GEN
Adder
4.004
972219AH1-694 GEN
Adder
2.883
970937AG2-583 GEN
Solar/Wind Harmer
15.369
316131AB2-060 GEN
Solar/Wind Harmer
2.286
316494AC1-189 GEN
Solar/Wind Harmer
2.283
970683AG2-441 GEN
Solar/Wind Harmer
14.933
970681AG2-440 GEN
Solar/Wind Harmer
9.911
946301AF1-294 GEN
Solar/Wind Harmer
5.41
961791AG1-021 GEN
Solar/Wind Harmer
2.639
3145573BETHELC
Solar/Wind Harmer
-0.021
3145573BETHELC
Solar/Wind Harmer
-0.021
972205AH1-687 GEN
Adder
7.25
3138216PACIFIC
Solar/Wind Helper
0.039
315785AD2-033 C
Solar/Wind Harmer
4.794
316034AC1-036 C
Solar/Wind Harmer
0.392
970685AG2-442 GEN
Solar/Wind Harmer
18.489
971563AH1-280 GEN
Solar/Wind Harmer
2.639
3144293JTRSVLE
Adder
0.449
3144293JTRSVLE
Adder
0.354
316337AD2-073 GEN
Solar/Wind Harmer
0.565
3146926FARMVIL
Solar/Wind Harmer
-0.012
316319Z2-044 C
Solar/Wind Harmer
1.157
3146233WITAKRS
Solar/Wind Harmer
-0.083
961671AG1-007 GEN
Solar/Wind Harmer
0.265
3146083TARBORO
Solar/Wind Harmer
-0.021
3145493TOT1
Solar/Wind Harmer
0.621
3151751LOISA D
Adder
10.369
972277AH1-723 GEN
Adder
87.055
316415AF1-147_GEN2
Solar/Wind Helper
0.809
970301AG2-198 GEN
Solar/Wind Harmer
10.96
316005AA1-067
Solar/Wind Harmer
0.435
315724AD1-057 GEN
Solar/Wind Harmer
4.209
3150391LDYSMT3
Adder
25.596
972195AH1-682 GEN
Adder
3.364
315687AD1-152 GEN
Solar/Wind Harmer
2.58
313527AB2-043 GEN
Solar/Wind Harmer
3.45
316237AB2-079_GEN
Solar/Wind Harmer
0.637
970323AG2-213 GEN
Solar/Wind Harmer
10.588
958211AF2-115 GEN
Solar/Wind Harmer
3.299
3144293JTRSVLE
Adder
0.449
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3145493TOT1
Solar/Wind Harmer
0.324
3145453TOT5
Solar/Wind Harmer
0.194
3145603CNETO
Solar/Wind Harmer
0.13
3151731LOISA B
Adder
10.369
972193AH1-681 GEN
Adder
3.338
316411AF1-147_GEN1
Solar/Wind Helper
0.809
961601AG1-000A GEN
Solar/Wind Harmer
7.326
CPLELTFEXP_CPLE->PJM
CLTF
11.864
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.864
LAGNLTFEXP_LAGN->PJM
CLTF
8.039
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.841
TVALTFEXP_TVA->PJM
CLTF
4.074
NYPJM->LTFIMP_NY
CLTF
3.378
LGEELTFEXP_LGEE->PJM
CLTF
1.259
WECLTFEXP_WEC->PJM
CLTF
0.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.782
MECLTFEXP_MEC->PJM
CLTF
3.473
SIGELTFEXP_SIGE->PJM
CLTF
0.105

Details for [AH1-716] 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.41 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4035.06
MW Contribution:
189.31
IPD Plant:AH1-716
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
PJM_IPD
189.314

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.48 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3648.44
MW Contribution:
234.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
234.064
3151081ELIZAR1
50/50
32.032
3151091ELIZAR2
50/50
31.475
941591AE2-156 GEN
50/50
29.166
3151151S HAMPT1
50/50
0.685
315244AE2-183_ST
50/50
7.358
316316AC1-027 C
Solar/Wind Harmer
1.133
316018AA1-139 ULT2
Solar/Wind Harmer
3.142
957871AF2-081 GEN
Solar/Wind Harmer
18.384
3146406KITTY HAWK
Solar/Wind Harmer
0.03
313526AB2-022
Solar/Wind Harmer
0.961
3146396TANGLEW
Solar/Wind Harmer
0.65
3145176PASQUOTANK
Solar/Wind Harmer
-0.022
3146486SUNBURY
Solar/Wind Harmer
-0.035
3146486SUNBURY
Solar/Wind Harmer
-0.035
315800Z1-036_GEN1
Solar/Wind Harmer
8.186
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316236AE1-162_GEN
Solar/Wind Harmer
0.936
971445AH1-216 GEN
Solar/Wind Harmer
19.05
3130546PLYMOUTH
Solar/Wind Harmer
-0.03
315732AD1-074 GEN1
Solar/Wind Harmer
6.077
315733AD1-074 GEN2
Solar/Wind Harmer
6.077
316311AC2-079 GEN
Solar/Wind Harmer
15.157
315833AF1-017_GEN
Solar/Wind Harmer
5.693
970533AG2-339 GEN
Solar/Wind Harmer
20.111
970673AG2-436 GEN
Solar/Wind Harmer
64.547
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.826
971967AH1-528 GEN
Solar/Wind Harmer
53.182
316318V4-068
Solar/Wind Harmer
0.696
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
-0.028
316463AE2-346 GEN
Solar/Wind Harmer
0.445
3145513AHOSKIE
Solar/Wind Harmer
0.24
961941AG1-037 GEN
Solar/Wind Harmer
0.207
3145513AHOSKIE
Solar/Wind Harmer
-0.027
3151201GRAVEL4
Adder
17.836
3151221GRAVEL6
Adder
17.815
3151191GRAVEL3
Adder
17.61
3151211GRAVEL5
Adder
17.61
3145683EARLEYS
Solar/Wind Harmer
-0.055
3145683EARLEYS
Solar/Wind Harmer
-0.027
3152331SURRY 2
50/50
17.431
3150981CHESPKA
50/50
4.335
315243AE2-183_GT3
50/50
4.237
315773AC2-141 GEN
Solar/Wind Harmer
17.942
944591AF1-124 GEN
Solar/Wind Harmer
175.379
316375AC2-012 GEN
Solar/Wind Harmer
12.714
316036AC1-147 C
Solar/Wind Harmer
0.989
3146456SLIGO L269
Solar/Wind Harmer
-0.036
319010AE1-072 C
Solar/Wind Harmer
7.373
3146516WINFALL
Solar/Wind Harmer
-0.111
3146516WINFALL
Solar/Wind Harmer
-0.034
939411AE1-173 GEN
Solar/Wind Harmer
172.217
316072AD1-144
Solar/Wind Harmer
0.685
316093AE2-104_GEN
Solar/Wind Harmer
9.772
940641AE2-051 GEN
Solar/Wind Harmer
31.321
315611Z1-036_GEN2
Solar/Wind Harmer
8.186
3130156CHOWAN
Solar/Wind Harmer
-0.033
315816AE2-034 GEN
Solar/Wind Harmer
2.534
3145663CRESWEL
Solar/Wind Harmer
-0.087
971163AH1-040 GEN
Solar/Wind Harmer
29.44
3145336SMITFLD
Solar/Wind Harmer
-0.124
3138126ROCKLANDING
Solar/Wind Harmer
0.095
315737AD1-076 GEN
Solar/Wind Harmer
5.713
941031AE2-094 GEN
Solar/Wind Harmer
56.074
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.329
971317AH1-138 GEN
Solar/Wind Harmer
3.528
3156021HOLLOMANSOL
Solar/Wind Harmer
3.786
3145893MURPHYS
Solar/Wind Harmer
-0.111
3145893MURPHYS
Solar/Wind Harmer
0.828
3145963POPLR C
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
2.607
3145683EARLEYS
Solar/Wind Harmer
-0.027
970919AG2-571 GEN
Solar/Wind Harmer
8.634
970087AG2-069 GEN
Solar/Wind Harmer
25.205
3146263WOODLND
Solar/Wind Harmer
-0.027
3145823KELFORD
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.62
3146293MARTNCO
Solar/Wind Harmer
0.159
961611AG1-000B GEN
Solar/Wind Harmer
12.31
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145783HORNRTN
Solar/Wind Harmer
-0.024
957481AF2-042 GEN
Solar/Wind Harmer
76.029
316023GEN1_S
Solar/Wind Harmer
1.632
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
316381AD1-082 GEN
Solar/Wind Harmer
2.213
316087AB2-174 GEN
Solar/Wind Harmer
3.421
316494AC1-189 GEN
Solar/Wind Harmer
2.574
960081AF2-299 GEN
Solar/Wind Harmer
2.669
961671AG1-007 GEN
Solar/Wind Harmer
0.293
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.687
316319Z2-044 C
Solar/Wind Harmer
1.257
3146233WITAKRS
Solar/Wind Harmer
-0.09
315693AD1-088 GEN
Solar/Wind Harmer
11.384
3147043LAWRENC
Adder
1.813
316129AC1-054 GEN
Solar/Wind Harmer
1.958
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.018
316359AB2-059 GEN
Solar/Wind Harmer
2.99
3142053HEARTS
Solar/Wind Harmer
0.261
971065AG2-659 GEN
Solar/Wind Harmer
11.097
316369SG1_INVT
Solar/Wind Harmer
3.718
316131AB2-060 GEN
Solar/Wind Harmer
2.111
971069AG2-661 GEN
Solar/Wind Harmer
3.042
970401AG2-262 GEN
Solar/Wind Harmer
1.249
315785AD2-033 C
Solar/Wind Harmer
4.147
316034AC1-036 C
Solar/Wind Harmer
0.333
970685AG2-442 GEN
Solar/Wind Harmer
14.821
316132AB2-190 GEN1
Solar/Wind Harmer
1.703
971563AH1-280 GEN
Solar/Wind Harmer
2.069
3144293JTRSVLE
Adder
0.352
3144293JTRSVLE
Adder
0.278
3146926FARMVIL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
2.294
3150991CHESPKB
50/50
3.637
3150991CHESPKB
50/50
3.55
315242AE2-183_GT2
50/50
4.237
315241AE2-183_GT1
50/50
4.226
972185AH1-677 GEN
50/50
15.316
316294AC1-161 GEN
Solar/Wind Harmer
13.867
316185AD1-033 GEN
Solar/Wind Harmer
3.925
3145506HICKORY
Solar/Wind Harmer
-0.148
3145506HICKORY
Solar/Wind Harmer
-0.089
3145506HICKORY
Solar/Wind Harmer
-0.022
316339AD2-160 GEN
Solar/Wind Harmer
2.478
316388AE2-253 GEN
Solar/Wind Harmer
2.478
3137176SLIGO L2192
Solar/Wind Harmer
-0.145
3146456SLIGO L269
Solar/Wind Harmer
4.323
3130086AYDLETT
Solar/Wind Harmer
-0.145
3146386ELIZ CT
Solar/Wind Harmer
-0.036
316431W1029_GEN1
Solar/Wind Harmer
6.287
316433W1029_GEN2
Solar/Wind Harmer
6.287
316435W1029_GEN3
Solar/Wind Harmer
6.287
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
315835AF2-110_GEN
Solar/Wind Harmer
4.201
3146376EDENTON
Solar/Wind Harmer
0.974
3146376EDENTON
Solar/Wind Harmer
0.974
315614AA2-178 GEN
Solar/Wind Harmer
3.379
315742AE1-103 GEN
Solar/Wind Harmer
7.415
316349AD2-085 GEN
Solar/Wind Harmer
2.661
316065AD1-022 GEN
Solar/Wind Harmer
14.803
972187AH1-678 GEN
Adder
7.212
3145893MURPHYS
Solar/Wind Harmer
0.779
3145893MURPHYS
Solar/Wind Harmer
-0.05
3146173TUNIS
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
316140AB2-099
Solar/Wind Harmer
0.186
970933AG2-581 GEN
Solar/Wind Harmer
25.613
3145933PARMELE
Solar/Wind Harmer
-0.051
3145933PARMELE
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
316005AA1-067
Solar/Wind Harmer
0.5
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
0.205
962571AG1-106 GEN
Solar/Wind Harmer
3.531
3145783HORNRTN
Solar/Wind Harmer
2.912
3145783HORNRTN
Solar/Wind Harmer
2.33
3145783HORNRTN
Solar/Wind Harmer
0.728
3145783HORNRTN
Solar/Wind Harmer
0.291
970099AG2-077 GEN
Solar/Wind Harmer
30.412
316365GEN2_N
Solar/Wind Harmer
1.632
3145796HORNRTN
Solar/Wind Harmer
-0.072
316083AB2-161 GEN
Solar/Wind Harmer
3.925
313506AB2-031 GEN
Solar/Wind Harmer
1.936
3144356SAPONY
Solar/Wind Harmer
0.839
316315AB2-025 C
Solar/Wind Harmer
0.647
3145493TOT1
Solar/Wind Harmer
0.358
3145453TOT5
Solar/Wind Harmer
0.215
3145603CNETO
Solar/Wind Harmer
0.143
315724AD1-057 GEN
Solar/Wind Harmer
4.524
961601AG1-000A GEN
Solar/Wind Harmer
8.744
316049AB1-081 GEN
Solar/Wind Harmer
2.392
316263AC1-034 GEN
Solar/Wind Harmer
10.421
315687AD1-152 GEN
Solar/Wind Harmer
2.591
316033AB2-134 GEN
Solar/Wind Harmer
6.714
316237AB2-079_GEN
Solar/Wind Harmer
0.595
313527AB2-043 GEN
Solar/Wind Harmer
3.205
962561AG1-105 GEN
Solar/Wind Harmer
10.812
964791AG1-342 GEN
Solar/Wind Harmer
4.086
3146843MT LREL
Solar/Wind Harmer
-0.019
3146843MT LREL
Solar/Wind Harmer
-0.019
316118AC1-105 GEN
Solar/Wind Harmer
1.297
316248AF1-058 C
Solar/Wind Harmer
0.562
970323AG2-213 GEN
Solar/Wind Harmer
9.015
970301AG2-198 GEN
Solar/Wind Harmer
8.586
958211AF2-115 GEN
Solar/Wind Harmer
2.586
3144293JTRSVLE
Adder
0.352
3147133PAMPLIN
Solar/Wind Harmer
-0.016
3147133PAMPLIN
Solar/Wind Harmer
-0.013
316156AD2-030 GEN
Solar/Wind Harmer
0.343
3151101ELIZAR3
50/50
32.441
3150921YORKTN3
50/50
7.395
3144216WINCHST
50/50
1.098
3151161SURRY 1
50/50
9.982
944581AF1-123 GEN
Solar/Wind Harmer
174.75
944601AF1-125 GEN
Solar/Wind Harmer
172.023
3142956BIRDNECK
Solar/Wind Harmer
1.987
316017AA1-139 ULT1
Solar/Wind Harmer
2.967
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.036
971153AH1-033 GEN
Solar/Wind Harmer
4.236
316320Y1-086
Solar/Wind Harmer
2.091
316305AF2-043 C
Solar/Wind Harmer
1.067
316246AF1-032 C
Solar/Wind Harmer
0.716
316321Z2-027
Solar/Wind Harmer
0.95
3144536CHRHLND
Solar/Wind Harmer
-0.005
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.012
315735AD1-075 GEN1
Solar/Wind Harmer
3.037
944011AF1-069 GEN
Solar/Wind Harmer
17.57
3146206CASHIE
Solar/Wind Harmer
-0.029
3156081AA2-088 GEN
Solar/Wind Harmer
9.208
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
3.428
970917AG2-570 GEN
Solar/Wind Harmer
68.211
3146263WOODLND
Solar/Wind Harmer
-0.027
316317KELFORD C
Solar/Wind Harmer
1.224
3145823KELFORD
Solar/Wind Harmer
-0.026
3145933PARMELE
Solar/Wind Harmer
-0.026
316190AA2-174 GEN
Solar/Wind Harmer
0.308
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
961611AG1-000B GEN
Solar/Wind Harmer
5.253
970657AG2-426 GEN
Solar/Wind Harmer
5.015
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316212AC1-099_GEN
Solar/Wind Harmer
2.14
316011AB1-132 GEN
Solar/Wind Harmer
5.13
3145796HORNRTN
Solar/Wind Harmer
-0.096
3145796HORNRTN
Solar/Wind Harmer
-0.024
316181AB2-040 GEN
Solar/Wind Harmer
3.363
966621AG1-532 GEN
Solar/Wind Harmer
0.481
316420AA1-050 GEN
Solar/Wind Harmer
2.677
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
315722AD1-056 GEN
Solar/Wind Harmer
8.226
316478AD1-087 GEN
Solar/Wind Harmer
1.991
3146233WITAKRS
Solar/Wind Harmer
0.476
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
3147043LAWRENC
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.854
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
315813AE1-149 C
Solar/Wind Harmer
12.837
315778AD1-151 GEN
Solar/Wind Harmer
17.109
964241AG1-285 GEN
Solar/Wind Harmer
14.949
970257AG2-171 GEN
Solar/Wind Harmer
6.761
971775AH1-396 GEN
Solar/Wind Harmer
1.272
959311AF2-222 GEN
Solar/Wind Harmer
18.592
316003AC1-222 GEN
Solar/Wind Harmer
1.715
316222AC1-221 GEN
Solar/Wind Harmer
1.764
316283AC2-100 C
Solar/Wind Harmer
1.638
316458AB2-190 GEN2
Solar/Wind Harmer
1.703
3144293JTRSVLE
Adder
0.352
971683AH1-343 GEN
Solar/Wind Harmer
7.057
3147133PAMPLIN
Solar/Wind Harmer
-0.05
942461AE2-259 GEN
Solar/Wind Harmer
2.199
316123AC1-075 GEN
Solar/Wind Harmer
1.474
3146926FARMVIL
Solar/Wind Harmer
-0.008
3141873WAN 176
Solar/Wind Harmer
1.527
970133AG2-095 GEN
Solar/Wind Harmer
1.424
3145683EARLEYS
Solar/Wind Harmer
-0.027
316174AB2-169 GEN
Solar/Wind Harmer
4.212
970085AG2-068 GEN
Solar/Wind Harmer
16.803
970581AG2-369 GEN
Solar/Wind Harmer
14.451
3146043SEABORD
Solar/Wind Harmer
-0.026
3146033SCOT NK
Solar/Wind Harmer
-0.101
316426AA2-053 GEN
Solar/Wind Harmer
2.532
970657AG2-426 GEN
Solar/Wind Harmer
1.565
3145746EVERETS
Solar/Wind Harmer
-0.098
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316210AC1-098 GEN
Solar/Wind Harmer
3.852
315652AC1-086 GEN
Solar/Wind Harmer
27.634
3137643SOCKMAN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.01
316274AC1-208 GEN
Solar/Wind Harmer
2.59
315814AE2-033 C
Solar/Wind Harmer
22.412
957861AF2-080 GEN
Solar/Wind Harmer
10.466
946281AF1-292 GEN
Solar/Wind Harmer
0.531
316327AA2-057 GEN
Solar/Wind Harmer
2.345
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
316486AD2-202 GEN
Solar/Wind Harmer
0.583
970831AG2-522 GEN
Solar/Wind Harmer
11.327
957831AF2-077 GEN
Solar/Wind Harmer
0.674
3138283WHITEMARSH
Solar/Wind Harmer
0.035
316382AG1-145 C
Solar/Wind Harmer
0.657
316159AE1-175 C
Solar/Wind Harmer
0.585
315697AD1-025 GEN
Solar/Wind Harmer
4.208
316238AB2-078_GEN
Solar/Wind Harmer
0.595
316239AB2-077_GEN
Solar/Wind Harmer
0.595
3143316POE
Solar/Wind Harmer
-0.076
3147173SINAI
Solar/Wind Harmer
-0.019
3147243WELCO
Solar/Wind Harmer
-0.012
3144303KENBRDG
Solar/Wind Harmer
-0.014
970683AG2-441 GEN
Solar/Wind Harmer
12.196
970681AG2-440 GEN
Solar/Wind Harmer
8.095
946301AF1-294 GEN
Solar/Wind Harmer
4.241
961791AG1-021 GEN
Solar/Wind Harmer
2.069
270455AD2-022 GEN
Solar/Wind Harmer
2.646
270457AD2-023 GEN
Solar/Wind Harmer
1.342
315839AE2-212 C
Solar/Wind Harmer
0.438
957601AF2-054 GEN
Solar/Wind Harmer
0.385
3141873WAN 176
Solar/Wind Harmer
-0.003
CPLELTFEXP_CPLE->PJM
CLTF
12.083
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.051
LAGNLTFEXP_LAGN->PJM
CLTF
7.203
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.146
TVALTFEXP_TVA->PJM
CLTF
3.583
NYPJM->LTFIMP_NY
CLTF
1.906
LGEELTFEXP_LGEE->PJM
CLTF
1.025
WECLTFEXP_WEC->PJM
CLTF
0.521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.04
MECLTFEXP_MEC->PJM
CLTF
3.031
SIGELTFEXP_SIGE->PJM
CLTF
0.088

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.48 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3648.44
MW Contribution:
234.06
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
17.431
3150981CHESPKA
50/50
4.335
315243AE2-183_GT3
50/50
4.237
315773AC2-141 GEN
Solar/Wind Harmer
17.942
944591AF1-124 GEN
Solar/Wind Harmer
175.379
316375AC2-012 GEN
Solar/Wind Harmer
12.714
316036AC1-147 C
Solar/Wind Harmer
0.989
3146456SLIGO L269
Solar/Wind Harmer
-0.036
319010AE1-072 C
Solar/Wind Harmer
7.373
3146516WINFALL
Solar/Wind Harmer
-0.111
3146516WINFALL
Solar/Wind Harmer
-0.034
939411AE1-173 GEN
Solar/Wind Harmer
172.217
316072AD1-144
Solar/Wind Harmer
0.685
316093AE2-104_GEN
Solar/Wind Harmer
9.772
940641AE2-051 GEN
Solar/Wind Harmer
31.321
315611Z1-036_GEN2
Solar/Wind Harmer
8.186
3130156CHOWAN
Solar/Wind Harmer
-0.033
315816AE2-034 GEN
Solar/Wind Harmer
2.534
3145663CRESWEL
Solar/Wind Harmer
-0.087
971163AH1-040 GEN
Solar/Wind Harmer
29.44
3145336SMITFLD
Solar/Wind Harmer
-0.124
3138126ROCKLANDING
Solar/Wind Harmer
0.095
315737AD1-076 GEN
Solar/Wind Harmer
5.713
941031AE2-094 GEN
Solar/Wind Harmer
56.074
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.329
971317AH1-138 GEN
Solar/Wind Harmer
3.528
3156021HOLLOMANSOL
Solar/Wind Harmer
3.786
3145893MURPHYS
Solar/Wind Harmer
-0.111
3145893MURPHYS
Solar/Wind Harmer
0.828
3145963POPLR C
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
2.607
3145683EARLEYS
Solar/Wind Harmer
-0.027
970919AG2-571 GEN
Solar/Wind Harmer
8.634
970087AG2-069 GEN
Solar/Wind Harmer
25.205
3146263WOODLND
Solar/Wind Harmer
-0.027
3145823KELFORD
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.62
3146293MARTNCO
Solar/Wind Harmer
0.159
961611AG1-000B GEN
Solar/Wind Harmer
12.31
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145783HORNRTN
Solar/Wind Harmer
-0.024
957481AF2-042 GEN
Solar/Wind Harmer
76.029
316023GEN1_S
Solar/Wind Harmer
1.632
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
316381AD1-082 GEN
Solar/Wind Harmer
2.213
316087AB2-174 GEN
Solar/Wind Harmer
3.421
316494AC1-189 GEN
Solar/Wind Harmer
2.574
960081AF2-299 GEN
Solar/Wind Harmer
2.669
961671AG1-007 GEN
Solar/Wind Harmer
0.293
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.687
316319Z2-044 C
Solar/Wind Harmer
1.257
3146233WITAKRS
Solar/Wind Harmer
-0.09
315693AD1-088 GEN
Solar/Wind Harmer
11.384
3147043LAWRENC
Adder
1.813
316129AC1-054 GEN
Solar/Wind Harmer
1.958
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.018
316359AB2-059 GEN
Solar/Wind Harmer
2.99
3142053HEARTS
Solar/Wind Harmer
0.261
971065AG2-659 GEN
Solar/Wind Harmer
11.097
316369SG1_INVT
Solar/Wind Harmer
3.718
316131AB2-060 GEN
Solar/Wind Harmer
2.111
971069AG2-661 GEN
Solar/Wind Harmer
3.042
970401AG2-262 GEN
Solar/Wind Harmer
1.249
315785AD2-033 C
Solar/Wind Harmer
4.147
316034AC1-036 C
Solar/Wind Harmer
0.333
970685AG2-442 GEN
Solar/Wind Harmer
14.821
316132AB2-190 GEN1
Solar/Wind Harmer
1.703
971563AH1-280 GEN
Solar/Wind Harmer
2.069
3144293JTRSVLE
Adder
0.352
3144293JTRSVLE
Adder
0.278
3146926FARMVIL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
2.294
3150991CHESPKB
50/50
3.637
3150991CHESPKB
50/50
3.55
315242AE2-183_GT2
50/50
4.237
315241AE2-183_GT1
50/50
4.226
972185AH1-677 GEN
50/50
15.316
316294AC1-161 GEN
Solar/Wind Harmer
13.867
316185AD1-033 GEN
Solar/Wind Harmer
3.925
3145506HICKORY
Solar/Wind Harmer
-0.148
3145506HICKORY
Solar/Wind Harmer
-0.089
3145506HICKORY
Solar/Wind Harmer
-0.022
316339AD2-160 GEN
Solar/Wind Harmer
2.478
316388AE2-253 GEN
Solar/Wind Harmer
2.478
3137176SLIGO L2192
Solar/Wind Harmer
-0.145
3146456SLIGO L269
Solar/Wind Harmer
4.323
3130086AYDLETT
Solar/Wind Harmer
-0.145
3146386ELIZ CT
Solar/Wind Harmer
-0.036
316431W1029_GEN1
Solar/Wind Harmer
6.287
316433W1029_GEN2
Solar/Wind Harmer
6.287
316435W1029_GEN3
Solar/Wind Harmer
6.287
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
315835AF2-110_GEN
Solar/Wind Harmer
4.201
3146376EDENTON
Solar/Wind Harmer
0.974
3146376EDENTON
Solar/Wind Harmer
0.974
315614AA2-178 GEN
Solar/Wind Harmer
3.379
315742AE1-103 GEN
Solar/Wind Harmer
7.415
316349AD2-085 GEN
Solar/Wind Harmer
2.661
316065AD1-022 GEN
Solar/Wind Harmer
14.803
972187AH1-678 GEN
Adder
7.212
3145893MURPHYS
Solar/Wind Harmer
0.779
3145893MURPHYS
Solar/Wind Harmer
-0.05
3146173TUNIS
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
316140AB2-099
Solar/Wind Harmer
0.186
970933AG2-581 GEN
Solar/Wind Harmer
25.613
3145933PARMELE
Solar/Wind Harmer
-0.051
3145933PARMELE
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
316005AA1-067
Solar/Wind Harmer
0.5
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
0.205
962571AG1-106 GEN
Solar/Wind Harmer
3.531
3145783HORNRTN
Solar/Wind Harmer
2.912
3145783HORNRTN
Solar/Wind Harmer
2.33
3145783HORNRTN
Solar/Wind Harmer
0.728
3145783HORNRTN
Solar/Wind Harmer
0.291
970099AG2-077 GEN
Solar/Wind Harmer
30.412
316365GEN2_N
Solar/Wind Harmer
1.632
3145796HORNRTN
Solar/Wind Harmer
-0.072
316083AB2-161 GEN
Solar/Wind Harmer
3.925
313506AB2-031 GEN
Solar/Wind Harmer
1.936
3144356SAPONY
Solar/Wind Harmer
0.839
316315AB2-025 C
Solar/Wind Harmer
0.647
3145493TOT1
Solar/Wind Harmer
0.358
3145453TOT5
Solar/Wind Harmer
0.215
3145603CNETO
Solar/Wind Harmer
0.143
315724AD1-057 GEN
Solar/Wind Harmer
4.524
961601AG1-000A GEN
Solar/Wind Harmer
8.744
316049AB1-081 GEN
Solar/Wind Harmer
2.392
316263AC1-034 GEN
Solar/Wind Harmer
10.421
315687AD1-152 GEN
Solar/Wind Harmer
2.591
316033AB2-134 GEN
Solar/Wind Harmer
6.714
316237AB2-079_GEN
Solar/Wind Harmer
0.595
313527AB2-043 GEN
Solar/Wind Harmer
3.205
962561AG1-105 GEN
Solar/Wind Harmer
10.812
964791AG1-342 GEN
Solar/Wind Harmer
4.086
3146843MT LREL
Solar/Wind Harmer
-0.019
3146843MT LREL
Solar/Wind Harmer
-0.019
316118AC1-105 GEN
Solar/Wind Harmer
1.297
316248AF1-058 C
Solar/Wind Harmer
0.562
970323AG2-213 GEN
Solar/Wind Harmer
9.015
970301AG2-198 GEN
Solar/Wind Harmer
8.586
958211AF2-115 GEN
Solar/Wind Harmer
2.586
3144293JTRSVLE
Adder
0.352
3147133PAMPLIN
Solar/Wind Harmer
-0.016
3147133PAMPLIN
Solar/Wind Harmer
-0.013
316156AD2-030 GEN
Solar/Wind Harmer
0.343
3151101ELIZAR3
50/50
32.441
3150921YORKTN3
50/50
7.395
3144216WINCHST
50/50
1.098
3151161SURRY 1
50/50
9.982
944581AF1-123 GEN
Solar/Wind Harmer
174.75
944601AF1-125 GEN
Solar/Wind Harmer
172.023
3142956BIRDNECK
Solar/Wind Harmer
1.987
316017AA1-139 ULT1
Solar/Wind Harmer
2.967
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.036
971153AH1-033 GEN
Solar/Wind Harmer
4.236
316320Y1-086
Solar/Wind Harmer
2.091
316305AF2-043 C
Solar/Wind Harmer
1.067
316246AF1-032 C
Solar/Wind Harmer
0.716
316321Z2-027
Solar/Wind Harmer
0.95
3144536CHRHLND
Solar/Wind Harmer
-0.005
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.012
315735AD1-075 GEN1
Solar/Wind Harmer
3.037
944011AF1-069 GEN
Solar/Wind Harmer
17.57
3146206CASHIE
Solar/Wind Harmer
-0.029
3156081AA2-088 GEN
Solar/Wind Harmer
9.208
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
3.428
970917AG2-570 GEN
Solar/Wind Harmer
68.211
3146263WOODLND
Solar/Wind Harmer
-0.027
316317KELFORD C
Solar/Wind Harmer
1.224
3145823KELFORD
Solar/Wind Harmer
-0.026
3145933PARMELE
Solar/Wind Harmer
-0.026
316190AA2-174 GEN
Solar/Wind Harmer
0.308
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
961611AG1-000B GEN
Solar/Wind Harmer
5.253
970657AG2-426 GEN
Solar/Wind Harmer
5.015
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316212AC1-099_GEN
Solar/Wind Harmer
2.14
316011AB1-132 GEN
Solar/Wind Harmer
5.13
3145796HORNRTN
Solar/Wind Harmer
-0.096
3145796HORNRTN
Solar/Wind Harmer
-0.024
316181AB2-040 GEN
Solar/Wind Harmer
3.363
966621AG1-532 GEN
Solar/Wind Harmer
0.481
316420AA1-050 GEN
Solar/Wind Harmer
2.677
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
315722AD1-056 GEN
Solar/Wind Harmer
8.226
316478AD1-087 GEN
Solar/Wind Harmer
1.991
3146233WITAKRS
Solar/Wind Harmer
0.476
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
3147043LAWRENC
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.854
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
315813AE1-149 C
Solar/Wind Harmer
12.837
315778AD1-151 GEN
Solar/Wind Harmer
17.109
964241AG1-285 GEN
Solar/Wind Harmer
14.949
970257AG2-171 GEN
Solar/Wind Harmer
6.761
971775AH1-396 GEN
Solar/Wind Harmer
1.272
959311AF2-222 GEN
Solar/Wind Harmer
18.592
316003AC1-222 GEN
Solar/Wind Harmer
1.715
316222AC1-221 GEN
Solar/Wind Harmer
1.764
316283AC2-100 C
Solar/Wind Harmer
1.638
316458AB2-190 GEN2
Solar/Wind Harmer
1.703
3144293JTRSVLE
Adder
0.352
971683AH1-343 GEN
Solar/Wind Harmer
7.057
3147133PAMPLIN
Solar/Wind Harmer
-0.05
942461AE2-259 GEN
Solar/Wind Harmer
2.199
316123AC1-075 GEN
Solar/Wind Harmer
1.474
3146926FARMVIL
Solar/Wind Harmer
-0.008
3141873WAN 176
Solar/Wind Harmer
1.527
970133AG2-095 GEN
Solar/Wind Harmer
1.424
972263AH1-716 GEN
50/50
234.064
3151081ELIZAR1
50/50
32.032
3151091ELIZAR2
50/50
31.475
941591AE2-156 GEN
50/50
29.166
3151151S HAMPT1
50/50
0.685
315244AE2-183_ST
50/50
7.358
316316AC1-027 C
Solar/Wind Harmer
1.133
316018AA1-139 ULT2
Solar/Wind Harmer
3.142
957871AF2-081 GEN
Solar/Wind Harmer
18.384
3146406KITTY HAWK
Solar/Wind Harmer
0.03
313526AB2-022
Solar/Wind Harmer
0.961
3146396TANGLEW
Solar/Wind Harmer
0.65
3145176PASQUOTANK
Solar/Wind Harmer
-0.022
3146486SUNBURY
Solar/Wind Harmer
-0.035
3146486SUNBURY
Solar/Wind Harmer
-0.035
315800Z1-036_GEN1
Solar/Wind Harmer
8.186
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316236AE1-162_GEN
Solar/Wind Harmer
0.936
971445AH1-216 GEN
Solar/Wind Harmer
19.05
3130546PLYMOUTH
Solar/Wind Harmer
-0.03
315732AD1-074 GEN1
Solar/Wind Harmer
6.077
315733AD1-074 GEN2
Solar/Wind Harmer
6.077
316311AC2-079 GEN
Solar/Wind Harmer
15.157
315833AF1-017_GEN
Solar/Wind Harmer
5.693
970533AG2-339 GEN
Solar/Wind Harmer
20.111
970673AG2-436 GEN
Solar/Wind Harmer
64.547
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.826
971967AH1-528 GEN
Solar/Wind Harmer
53.182
316318V4-068
Solar/Wind Harmer
0.696
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
-0.028
316463AE2-346 GEN
Solar/Wind Harmer
0.445
3145513AHOSKIE
Solar/Wind Harmer
0.24
961941AG1-037 GEN
Solar/Wind Harmer
0.207
3145513AHOSKIE
Solar/Wind Harmer
-0.027
3151201GRAVEL4
Adder
17.836
3151221GRAVEL6
Adder
17.815
3151191GRAVEL3
Adder
17.61
3151211GRAVEL5
Adder
17.61
3145683EARLEYS
Solar/Wind Harmer
-0.055
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.027
316174AB2-169 GEN
Solar/Wind Harmer
4.212
970085AG2-068 GEN
Solar/Wind Harmer
16.803
970581AG2-369 GEN
Solar/Wind Harmer
14.451
3146043SEABORD
Solar/Wind Harmer
-0.026
3146033SCOT NK
Solar/Wind Harmer
-0.101
316426AA2-053 GEN
Solar/Wind Harmer
2.532
970657AG2-426 GEN
Solar/Wind Harmer
1.565
3145746EVERETS
Solar/Wind Harmer
-0.098
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316210AC1-098 GEN
Solar/Wind Harmer
3.852
315652AC1-086 GEN
Solar/Wind Harmer
27.634
3137643SOCKMAN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.01
316274AC1-208 GEN
Solar/Wind Harmer
2.59
315814AE2-033 C
Solar/Wind Harmer
22.412
957861AF2-080 GEN
Solar/Wind Harmer
10.466
946281AF1-292 GEN
Solar/Wind Harmer
0.531
316327AA2-057 GEN
Solar/Wind Harmer
2.345
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
316486AD2-202 GEN
Solar/Wind Harmer
0.583
970831AG2-522 GEN
Solar/Wind Harmer
11.327
957831AF2-077 GEN
Solar/Wind Harmer
0.674
3138283WHITEMARSH
Solar/Wind Harmer
0.035
316382AG1-145 C
Solar/Wind Harmer
0.657
316159AE1-175 C
Solar/Wind Harmer
0.585
315697AD1-025 GEN
Solar/Wind Harmer
4.208
316238AB2-078_GEN
Solar/Wind Harmer
0.595
316239AB2-077_GEN
Solar/Wind Harmer
0.595
3143316POE
Solar/Wind Harmer
-0.076
3147173SINAI
Solar/Wind Harmer
-0.019
3147243WELCO
Solar/Wind Harmer
-0.012
3144303KENBRDG
Solar/Wind Harmer
-0.014
970683AG2-441 GEN
Solar/Wind Harmer
12.196
970681AG2-440 GEN
Solar/Wind Harmer
8.095
946301AF1-294 GEN
Solar/Wind Harmer
4.241
961791AG1-021 GEN
Solar/Wind Harmer
2.069
270455AD2-022 GEN
Solar/Wind Harmer
2.646
270457AD2-023 GEN
Solar/Wind Harmer
1.342
315839AE2-212 C
Solar/Wind Harmer
0.438
957601AF2-054 GEN
Solar/Wind Harmer
0.385
3141873WAN 176
Solar/Wind Harmer
-0.003
CPLELTFEXP_CPLE->PJM
CLTF
12.083
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.051
LAGNLTFEXP_LAGN->PJM
CLTF
7.203
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.146
TVALTFEXP_TVA->PJM
CLTF
3.583
NYPJM->LTFIMP_NY
CLTF
1.906
LGEELTFEXP_LGEE->PJM
CLTF
1.025
WECLTFEXP_WEC->PJM
CLTF
0.521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.04
MECLTFEXP_MEC->PJM
CLTF
3.031
SIGELTFEXP_SIGE->PJM
CLTF
0.088

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.45 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3618.36
MW Contribution:
232.35
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
17.326
3150981CHESPKA
50/50
4.29
315243AE2-183_GT3
50/50
4.287
315773AC2-141 GEN
Solar/Wind Harmer
17.88
944591AF1-124 GEN
Solar/Wind Harmer
174.062
316375AC2-012 GEN
Solar/Wind Harmer
12.581
316036AC1-147 C
Solar/Wind Harmer
0.979
3146456SLIGO L269
Solar/Wind Harmer
-0.036
319010AE1-072 C
Solar/Wind Harmer
7.296
939411AE1-173 GEN
Solar/Wind Harmer
173.089
3146516WINFALL
Solar/Wind Harmer
-0.11
3146516WINFALL
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
31.647
316072AD1-144
Solar/Wind Harmer
0.674
316093AE2-104_GEN
Solar/Wind Harmer
9.583
315611Z1-036_GEN2
Solar/Wind Harmer
8.055
3130156CHOWAN
Solar/Wind Harmer
-0.032
315816AE2-034 GEN
Solar/Wind Harmer
2.486
3145663CRESWEL
Solar/Wind Harmer
-0.086
971163AH1-040 GEN
Solar/Wind Harmer
28.876
3145336SMITFLD
Solar/Wind Harmer
-0.121
3138126ROCKLANDING
Solar/Wind Harmer
0.093
941031AE2-094 GEN
Solar/Wind Harmer
56.81
315737AD1-076 GEN
Solar/Wind Harmer
5.589
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.15
971317AH1-138 GEN
Solar/Wind Harmer
3.445
970919AG2-571 GEN
Solar/Wind Harmer
8.72
3156021HOLLOMANSOL
Solar/Wind Harmer
3.679
970087AG2-069 GEN
Solar/Wind Harmer
25.443
3145963POPLR C
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.108
3145893MURPHYS
Solar/Wind Harmer
0.802
3146173TUNIS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.027
3151171GRAVELC
Adder
2.519
3146263WOODLND
Solar/Wind Harmer
-0.026
3145823KELFORD
Solar/Wind Harmer
-0.026
3146293MARTNCO
Solar/Wind Harmer
0.155
315607AA1-063A GEN
Solar/Wind Harmer
2.518
957481AF2-042 GEN
Solar/Wind Harmer
76.214
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
11.774
3145783HORNRTN
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.5
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.023
315693AD1-088 GEN
Solar/Wind Harmer
11.357
316087AB2-174 GEN
Solar/Wind Harmer
3.213
961671AG1-007 GEN
Solar/Wind Harmer
0.284
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.666
316381AD1-082 GEN
Solar/Wind Harmer
2.043
3150991CHESPKB
50/50
3.599
3150991CHESPKB
50/50
3.513
315242AE2-183_GT2
50/50
4.287
315241AE2-183_GT1
50/50
4.276
972185AH1-677 GEN
50/50
15.497
316294AC1-161 GEN
Solar/Wind Harmer
13.819
316185AD1-033 GEN
Solar/Wind Harmer
3.888
3145506HICKORY
Solar/Wind Harmer
-0.146
3145506HICKORY
Solar/Wind Harmer
-0.088
3145506HICKORY
Solar/Wind Harmer
-0.022
316339AD2-160 GEN
Solar/Wind Harmer
2.453
316388AE2-253 GEN
Solar/Wind Harmer
2.453
3137176SLIGO L2192
Solar/Wind Harmer
-0.143
3146456SLIGO L269
Solar/Wind Harmer
4.278
3130086AYDLETT
Solar/Wind Harmer
-0.144
3146386ELIZ CT
Solar/Wind Harmer
-0.035
316431W1029_GEN1
Solar/Wind Harmer
6.202
316433W1029_GEN2
Solar/Wind Harmer
6.202
316435W1029_GEN3
Solar/Wind Harmer
6.202
3151101ELIZAR3
50/50
32.117
3150921YORKTN3
50/50
7.246
3144216WINCHST
50/50
1.074
3151161SURRY 1
50/50
9.646
944581AF1-123 GEN
Solar/Wind Harmer
173.438
944601AF1-125 GEN
Solar/Wind Harmer
170.731
3142956BIRDNECK
Solar/Wind Harmer
1.967
316017AA1-139 ULT1
Solar/Wind Harmer
2.937
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.036
971153AH1-033 GEN
Solar/Wind Harmer
4.192
316320Y1-086
Solar/Wind Harmer
2.066
316305AF2-043 C
Solar/Wind Harmer
1.054
316246AF1-032 C
Solar/Wind Harmer
0.707
316321Z2-027
Solar/Wind Harmer
0.939
3144536CHRHLND
Solar/Wind Harmer
-0.005
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146376EDENTON
Solar/Wind Harmer
-0.032
3145273HOLLAND
Solar/Wind Harmer
-0.023
3145336SMITFLD
Solar/Wind Harmer
-0.012
944011AF1-069 GEN
Solar/Wind Harmer
17.8
315735AD1-075 GEN1
Solar/Wind Harmer
2.971
3146206CASHIE
Solar/Wind Harmer
-0.029
970917AG2-570 GEN
Solar/Wind Harmer
68.888
3156081AA2-088 GEN
Solar/Wind Harmer
8.922
3145963POPLR C
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.189
3145893MURPHYS
Solar/Wind Harmer
-0.027
3146173TUNIS
Solar/Wind Harmer
-0.027
3151171GRAVELC
Adder
3.312
3146263WOODLND
Solar/Wind Harmer
-0.026
316317KELFORD C
Solar/Wind Harmer
1.185
3145823KELFORD
Solar/Wind Harmer
-0.026
3145933PARMELE
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.295
961611AG1-000B GEN
Solar/Wind Harmer
5.024
316212AC1-099_GEN
Solar/Wind Harmer
2.064
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
316011AB1-132 GEN
Solar/Wind Harmer
4.839
316478AD1-087 GEN
Solar/Wind Harmer
1.99
970657AG2-426 GEN
Solar/Wind Harmer
4.656
3145796HORNRTN
Solar/Wind Harmer
-0.091
3145796HORNRTN
Solar/Wind Harmer
-0.023
316420AA1-050 GEN
Solar/Wind Harmer
2.597
316181AB2-040 GEN
Solar/Wind Harmer
3.17
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
315722AD1-056 GEN
Solar/Wind Harmer
7.872
966621AG1-532 GEN
Solar/Wind Harmer
0.448
3146233WITAKRS
Solar/Wind Harmer
0.46
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.021
961601AG1-000A GEN
Solar/Wind Harmer
8.558
3147043LAWRENC
Solar/Wind Harmer
-0.013
964241AG1-285 GEN
Solar/Wind Harmer
14.529
315813AE1-149 C
Solar/Wind Harmer
11.379
315778AD1-151 GEN
Solar/Wind Harmer
15.827
970257AG2-171 GEN
Solar/Wind Harmer
6.551
971775AH1-396 GEN
Solar/Wind Harmer
1.233
316003AC1-222 GEN
Solar/Wind Harmer
1.696
316222AC1-221 GEN
Solar/Wind Harmer
1.749
316283AC2-100 C
Solar/Wind Harmer
1.625
959311AF2-222 GEN
Solar/Wind Harmer
18.001
971683AH1-343 GEN
Solar/Wind Harmer
6.977
972263AH1-716 GEN
50/50
232.348
3151081ELIZAR1
50/50
31.711
3151091ELIZAR2
50/50
31.16
941591AE2-156 GEN
50/50
28.866
315244AE2-183_ST
50/50
7.445
3151151S HAMPT1
50/50
0.667
316316AC1-027 C
Solar/Wind Harmer
1.122
316018AA1-139 ULT2
Solar/Wind Harmer
3.11
957871AF2-081 GEN
Solar/Wind Harmer
18.197
3146406KITTY HAWK
Solar/Wind Harmer
0.03
313526AB2-022
Solar/Wind Harmer
0.949
3146396TANGLEW
Solar/Wind Harmer
0.642
3145176PASQUOTANK
Solar/Wind Harmer
-0.022
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
315800Z1-036_GEN1
Solar/Wind Harmer
8.055
3130156CHOWAN
Solar/Wind Harmer
-0.032
3130156CHOWAN
Solar/Wind Harmer
-0.032
316236AE1-162_GEN
Solar/Wind Harmer
0.914
970533AG2-339 GEN
Solar/Wind Harmer
20.375
971445AH1-216 GEN
Solar/Wind Harmer
18.596
970673AG2-436 GEN
Solar/Wind Harmer
65.363
3130546PLYMOUTH
Solar/Wind Harmer
-0.03
315732AD1-074 GEN1
Solar/Wind Harmer
5.945
315733AD1-074 GEN2
Solar/Wind Harmer
5.945
316311AC2-079 GEN
Solar/Wind Harmer
14.599
315833AF1-017_GEN
Solar/Wind Harmer
5.481
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.513
971967AH1-528 GEN
Solar/Wind Harmer
53.742
970085AG2-068 GEN
Solar/Wind Harmer
16.962
970581AG2-369 GEN
Solar/Wind Harmer
14.587
316318V4-068
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.073
3145893MURPHYS
Solar/Wind Harmer
-0.027
316463AE2-346 GEN
Solar/Wind Harmer
0.431
3145513AHOSKIE
Solar/Wind Harmer
0.233
961941AG1-037 GEN
Solar/Wind Harmer
0.201
3145513AHOSKIE
Solar/Wind Harmer
-0.027
316174AB2-169 GEN
Solar/Wind Harmer
4.111
3145683EARLEYS
Solar/Wind Harmer
-0.053
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.027
3151201GRAVEL4
Adder
17.236
3151221GRAVEL6
Adder
17.216
3151191GRAVEL3
Adder
17.018
3151211GRAVEL5
Adder
17.018
3146043SEABORD
Solar/Wind Harmer
-0.025
3146033SCOT NK
Solar/Wind Harmer
-0.098
3145746EVERETS
Solar/Wind Harmer
-0.096
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316426AA2-053 GEN
Solar/Wind Harmer
2.427
316210AC1-098 GEN
Solar/Wind Harmer
3.716
957861AF2-080 GEN
Solar/Wind Harmer
10.165
3137643SOCKMAN
Solar/Wind Harmer
-0.092
316274AC1-208 GEN
Solar/Wind Harmer
2.493
315652AC1-086 GEN
Solar/Wind Harmer
26.064
316486AD2-202 GEN
Solar/Wind Harmer
0.583
970657AG2-426 GEN
Solar/Wind Harmer
1.453
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
316327AA2-057 GEN
Solar/Wind Harmer
2.263
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
946281AF1-292 GEN
Solar/Wind Harmer
0.494
970831AG2-522 GEN
Solar/Wind Harmer
10.964
957831AF2-077 GEN
Solar/Wind Harmer
0.651
3138283WHITEMARSH
Solar/Wind Harmer
0.034
316382AG1-145 C
Solar/Wind Harmer
0.634
316159AE1-175 C
Solar/Wind Harmer
0.564
315814AE2-033 C
Solar/Wind Harmer
19.442
315697AD1-025 GEN
Solar/Wind Harmer
3.937
316238AB2-078_GEN
Solar/Wind Harmer
0.579
316239AB2-077_GEN
Solar/Wind Harmer
0.579
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
3144303KENBRDG
Solar/Wind Harmer
-0.014
970683AG2-441 GEN
Solar/Wind Harmer
11.788
970681AG2-440 GEN
Solar/Wind Harmer
7.824
3143316POE
Solar/Wind Harmer
-0.063
946301AF1-294 GEN
Solar/Wind Harmer
4.089
961791AG1-021 GEN
Solar/Wind Harmer
1.995
270455AD2-022 GEN
Solar/Wind Harmer
2.619
270457AD2-023 GEN
Solar/Wind Harmer
1.328
316023GEN1_S
Solar/Wind Harmer
1.495
960081AF2-299 GEN
Solar/Wind Harmer
2.484
316319Z2-044 C
Solar/Wind Harmer
1.215
3146233WITAKRS
Solar/Wind Harmer
-0.087
316129AC1-054 GEN
Solar/Wind Harmer
1.898
971065AG2-659 GEN
Solar/Wind Harmer
10.777
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316359AB2-059 GEN
Solar/Wind Harmer
2.891
3142053HEARTS
Solar/Wind Harmer
0.253
3147043LAWRENC
Adder
1.708
316369SG1_INVT
Solar/Wind Harmer
3.479
316131AB2-060 GEN
Solar/Wind Harmer
2.054
970401AG2-262 GEN
Solar/Wind Harmer
1.227
971069AG2-661 GEN
Solar/Wind Harmer
2.814
315785AD2-033 C
Solar/Wind Harmer
4.022
316034AC1-036 C
Solar/Wind Harmer
0.323
970685AG2-442 GEN
Solar/Wind Harmer
14.31
971563AH1-280 GEN
Solar/Wind Harmer
1.995
3144293JTRSVLE
Adder
0.339
3144293JTRSVLE
Adder
0.268
316132AB2-190 GEN1
Solar/Wind Harmer
1.543
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
315835AF2-110_GEN
Solar/Wind Harmer
4.12
3146376EDENTON
Solar/Wind Harmer
0.958
3146376EDENTON
Solar/Wind Harmer
0.958
315614AA2-178 GEN
Solar/Wind Harmer
3.314
315742AE1-103 GEN
Solar/Wind Harmer
7.236
316065AD1-022 GEN
Solar/Wind Harmer
14.457
316349AD2-085 GEN
Solar/Wind Harmer
2.562
972187AH1-678 GEN
Adder
7.293
970933AG2-581 GEN
Solar/Wind Harmer
25.836
3145893MURPHYS
Solar/Wind Harmer
0.754
3145893MURPHYS
Solar/Wind Harmer
-0.049
3146173TUNIS
Solar/Wind Harmer
-0.027
3146173TUNIS
Solar/Wind Harmer
-0.027
316140AB2-099
Solar/Wind Harmer
0.18
3145933PARMELE
Solar/Wind Harmer
-0.05
3145933PARMELE
Solar/Wind Harmer
-0.025
970099AG2-077 GEN
Solar/Wind Harmer
30.485
316005AA1-067
Solar/Wind Harmer
0.487
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
0.196
3145783HORNRTN
Solar/Wind Harmer
2.787
3145783HORNRTN
Solar/Wind Harmer
2.229
3145783HORNRTN
Solar/Wind Harmer
0.697
3145783HORNRTN
Solar/Wind Harmer
0.279
962571AG1-106 GEN
Solar/Wind Harmer
3.33
3145796HORNRTN
Solar/Wind Harmer
-0.068
313506AB2-031 GEN
Solar/Wind Harmer
1.825
3145493TOT1
Solar/Wind Harmer
0.347
3145453TOT5
Solar/Wind Harmer
0.208
3145603CNETO
Solar/Wind Harmer
0.139
316083AB2-161 GEN
Solar/Wind Harmer
3.623
316365GEN2_N
Solar/Wind Harmer
1.495
315724AD1-057 GEN
Solar/Wind Harmer
4.329
316049AB1-081 GEN
Solar/Wind Harmer
2.313
316263AC1-034 GEN
Solar/Wind Harmer
10.078
961601AG1-000A GEN
Solar/Wind Harmer
8.451
315687AD1-152 GEN
Solar/Wind Harmer
2.584
3144356SAPONY
Solar/Wind Harmer
0.725
316315AB2-025 C
Solar/Wind Harmer
0.56
316033AB2-134 GEN
Solar/Wind Harmer
6.282
316237AB2-079_GEN
Solar/Wind Harmer
0.579
313527AB2-043 GEN
Solar/Wind Harmer
3.12
962561AG1-105 GEN
Solar/Wind Harmer
10.611
964791AG1-342 GEN
Solar/Wind Harmer
4.016
3146843MT LREL
Solar/Wind Harmer
-0.019
3146843MT LREL
Solar/Wind Harmer
-0.019
316118AC1-105 GEN
Solar/Wind Harmer
1.279
316248AF1-058 C
Solar/Wind Harmer
0.556
970323AG2-213 GEN
Solar/Wind Harmer
8.735
970301AG2-198 GEN
Solar/Wind Harmer
8.382
958211AF2-115 GEN
Solar/Wind Harmer
2.493
3144293JTRSVLE
Adder
0.339
3147133PAMPLIN
Solar/Wind Harmer
-0.015
3147133PAMPLIN
Solar/Wind Harmer
-0.012
3144293JTRSVLE
Adder
0.339
3147133PAMPLIN
Solar/Wind Harmer
-0.048
316458AB2-190 GEN2
Solar/Wind Harmer
1.543
942461AE2-259 GEN
Solar/Wind Harmer
2.104
316123AC1-075 GEN
Solar/Wind Harmer
1.454
CPLELTFEXP_CPLE->PJM
CLTF
11.954
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.562
LAGNLTFEXP_LAGN->PJM
CLTF
7.113
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.884
TVALTFEXP_TVA->PJM
CLTF
3.536
NYPJM->LTFIMP_NY
CLTF
1.852
LGEELTFEXP_LGEE->PJM
CLTF
1.007
WECLTFEXP_WEC->PJM
CLTF
0.513
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.364
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.877
MECLTFEXP_MEC->PJM
CLTF
2.986
SIGELTFEXP_SIGE->PJM
CLTF
0.087

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.94 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2807.07
MW Contribution:
230.29
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
17.166
3150981CHESPKA
50/50
4.243
315243AE2-183_GT3
50/50
4.127
315773AC2-141 GEN
Solar/Wind Harmer
13.691
944591AF1-124 GEN
Solar/Wind Harmer
75.71
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.057
3146456SLIGO L269
Solar/Wind Harmer
0.319
319010AE1-072 C
Solar/Wind Harmer
1.587
3146516WINFALL
Solar/Wind Harmer
0.975
3146516WINFALL
Solar/Wind Harmer
0.301
939411AE1-173 GEN
Solar/Wind Harmer
127.856
316072AD1-144
Solar/Wind Harmer
0.105
316093AE2-104_GEN
Solar/Wind Harmer
4.912
940641AE2-051 GEN
Solar/Wind Harmer
23.236
3130156CHOWAN
Solar/Wind Harmer
0.285
315816AE2-034 GEN
Solar/Wind Harmer
1.164
3145663CRESWEL
Solar/Wind Harmer
0.764
971163AH1-040 GEN
Solar/Wind Harmer
21.834
3145336SMITFLD
Solar/Wind Harmer
1.077
3138126ROCKLANDING
Solar/Wind Harmer
0.123
315737AD1-076 GEN
Solar/Wind Harmer
3.355
941031AE2-094 GEN
Solar/Wind Harmer
47.768
3146206CASHIE
Solar/Wind Harmer
0.254
971547AH1-271 GEN
Solar/Wind Harmer
5.428
3156021HOLLOMANSOL
Solar/Wind Harmer
1.1
971317AH1-138 GEN
Solar/Wind Harmer
1.823
3145893MURPHYS
Solar/Wind Harmer
0.967
3145893MURPHYS
Solar/Wind Harmer
1.075
3145963POPLR C
Solar/Wind Harmer
0.241
3146173TUNIS
Solar/Wind Harmer
0.24
3145683EARLEYS
Solar/Wind Harmer
0.238
3151171GRAVELC
Adder
2.523
970919AG2-571 GEN
Solar/Wind Harmer
8.405
970087AG2-069 GEN
Solar/Wind Harmer
18.633
3146263WOODLND
Solar/Wind Harmer
0.231
3145823KELFORD
Solar/Wind Harmer
0.229
315607AA1-063A GEN
Solar/Wind Harmer
0.452
3146293MARTNCO
Solar/Wind Harmer
0.207
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
961611AG1-000B GEN
Solar/Wind Harmer
11.214
3145783HORNRTN
Solar/Wind Harmer
0.212
957481AF2-042 GEN
Solar/Wind Harmer
55.953
3145796HORNRTN
Solar/Wind Harmer
0.69
3145796HORNRTN
Solar/Wind Harmer
0.209
316023GEN1_S
Solar/Wind Harmer
0.464
316381AD1-082 GEN
Solar/Wind Harmer
0.21
316494AC1-189 GEN
Solar/Wind Harmer
0.699
960081AF2-299 GEN
Solar/Wind Harmer
1.961
961671AG1-007 GEN
Solar/Wind Harmer
0.031
3146083TARBORO
Solar/Wind Harmer
0.2
3145493TOT1
Solar/Wind Harmer
0.891
3146233WITAKRS
Solar/Wind Harmer
0.783
315693AD1-088 GEN
Solar/Wind Harmer
9.393
3147043LAWRENC
Adder
1.751
316129AC1-054 GEN
Solar/Wind Harmer
0.72
3145543BTLEBRO
Solar/Wind Harmer
0.192
3145543BTLEBRO
Solar/Wind Harmer
0.154
316359AB2-059 GEN
Solar/Wind Harmer
0.683
3142053HEARTS
Solar/Wind Harmer
0.338
971065AG2-659 GEN
Solar/Wind Harmer
8.155
316131AB2-060 GEN
Solar/Wind Harmer
0.522
970401AG2-262 GEN
Solar/Wind Harmer
0.963
971069AG2-661 GEN
Solar/Wind Harmer
2.884
315785AD2-033 C
Solar/Wind Harmer
1.261
316034AC1-036 C
Solar/Wind Harmer
0.01
970685AG2-442 GEN
Solar/Wind Harmer
10.689
316132AB2-190 GEN1
Solar/Wind Harmer
0.753
971563AH1-280 GEN
Solar/Wind Harmer
1.489
3144293JTRSVLE
Adder
0.333
3144293JTRSVLE
Adder
0.263
3150991CHESPKB
50/50
3.559
3150991CHESPKB
50/50
3.474
315242AE2-183_GT2
50/50
4.127
315241AE2-183_GT1
50/50
4.116
972185AH1-677 GEN
50/50
14.917
316294AC1-161 GEN
Solar/Wind Harmer
6.48
3145506HICKORY
Solar/Wind Harmer
1.295
3145506HICKORY
Solar/Wind Harmer
0.777
3145506HICKORY
Solar/Wind Harmer
0.194
316339AD2-160 GEN
Solar/Wind Harmer
0.514
316388AE2-253 GEN
Solar/Wind Harmer
0.999
3137176SLIGO L2192
Solar/Wind Harmer
1.269
3146456SLIGO L269
Solar/Wind Harmer
5.642
3130086AYDLETT
Solar/Wind Harmer
1.271
3146386ELIZ CT
Solar/Wind Harmer
0.311
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146626S HERTFORD
Solar/Wind Harmer
0.297
3146626S HERTFORD
Solar/Wind Harmer
0.297
315835AF2-110_GEN
Solar/Wind Harmer
2.004
3146376EDENTON
Solar/Wind Harmer
1.269
3146376EDENTON
Solar/Wind Harmer
1.269
315614AA2-178 GEN
Solar/Wind Harmer
1.553
315742AE1-103 GEN
Solar/Wind Harmer
4.049
316349AD2-085 GEN
Solar/Wind Harmer
0.173
316065AD1-022 GEN
Solar/Wind Harmer
11.835
972187AH1-678 GEN
Adder
7.022
972263AH1-716 GEN
50/50
230.288
3151081ELIZAR1
50/50
31.355
3151091ELIZAR2
50/50
30.81
941591AE2-156 GEN
50/50
28.546
3151151S HAMPT1
50/50
0.668
315244AE2-183_ST
50/50
7.166
316316AC1-027 C
Solar/Wind Harmer
0.307
957871AF2-081 GEN
Solar/Wind Harmer
15.948
3146406KITTY HAWK
Solar/Wind Harmer
0.04
313526AB2-022
Solar/Wind Harmer
0.166
3146396TANGLEW
Solar/Wind Harmer
0.848
3145176PASQUOTANK
Solar/Wind Harmer
0.191
3146486SUNBURY
Solar/Wind Harmer
0.305
3146486SUNBURY
Solar/Wind Harmer
0.305
3130156CHOWAN
Solar/Wind Harmer
0.285
3130156CHOWAN
Solar/Wind Harmer
0.285
971445AH1-216 GEN
Solar/Wind Harmer
18.76
3130546PLYMOUTH
Solar/Wind Harmer
0.263
315732AD1-074 GEN1
Solar/Wind Harmer
1.49
315733AD1-074 GEN2
Solar/Wind Harmer
1.49
316311AC2-079 GEN
Solar/Wind Harmer
7.464
970533AG2-339 GEN
Solar/Wind Harmer
19.596
970673AG2-436 GEN
Solar/Wind Harmer
31.84
3146206CASHIE
Solar/Wind Harmer
0.254
970601AG2-382 GEN
Solar/Wind Harmer
9.5
971967AH1-528 GEN
Solar/Wind Harmer
39.201
3145893MURPHYS
Solar/Wind Harmer
0.653
3145893MURPHYS
Solar/Wind Harmer
0.242
316463AE2-346 GEN
Solar/Wind Harmer
0.204
3145513AHOSKIE
Solar/Wind Harmer
0.5
3145513AHOSKIE
Solar/Wind Harmer
0.239
3145683EARLEYS
Solar/Wind Harmer
0.476
3145683EARLEYS
Solar/Wind Harmer
0.238
3145683EARLEYS
Solar/Wind Harmer
0.238
3151201GRAVEL4
Adder
17.263
3151221GRAVEL6
Adder
17.243
3151191GRAVEL3
Adder
17.045
3151211GRAVEL5
Adder
17.045
970085AG2-068 GEN
Solar/Wind Harmer
12.422
970581AG2-369 GEN
Solar/Wind Harmer
10.683
3146043SEABORD
Solar/Wind Harmer
0.227
3146033SCOT NK
Solar/Wind Harmer
0.88
316426AA2-053 GEN
Solar/Wind Harmer
0.727
3145746EVERETS
Solar/Wind Harmer
0.855
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
970657AG2-426 GEN
Solar/Wind Harmer
1.563
316210AC1-098 GEN
Solar/Wind Harmer
1.966
315652AC1-086 GEN
Solar/Wind Harmer
23.321
3137643SOCKMAN
Solar/Wind Harmer
0.841
3145796HORNRTN
Solar/Wind Harmer
0.669
3145796HORNRTN
Solar/Wind Harmer
0.084
316274AC1-208 GEN
Solar/Wind Harmer
1.073
957861AF2-080 GEN
Solar/Wind Harmer
8.927
315814AE2-033 C
Solar/Wind Harmer
16.342
316327AA2-057 GEN
Solar/Wind Harmer
0.297
3145573BETHELC
Solar/Wind Harmer
0.2
3145573BETHELC
Solar/Wind Harmer
0.2
316486AD2-202 GEN
Solar/Wind Harmer
0.202
970831AG2-522 GEN
Solar/Wind Harmer
8.329
3138283WHITEMARSH
Solar/Wind Harmer
0.045
316159AE1-175 C
Solar/Wind Harmer
0.16
315697AD1-025 GEN
Solar/Wind Harmer
0.19
3143316POE
Solar/Wind Harmer
0.643
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.1
3144303KENBRDG
Solar/Wind Harmer
0.122
970683AG2-441 GEN
Solar/Wind Harmer
8.811
970681AG2-440 GEN
Solar/Wind Harmer
5.848
946301AF1-294 GEN
Solar/Wind Harmer
2.754
961791AG1-021 GEN
Solar/Wind Harmer
1.34
3151101ELIZAR3
50/50
31.756
3150921YORKTN3
50/50
7.207
3144216WINCHST
50/50
1.069
3151161SURRY 1
50/50
9.661
944581AF1-123 GEN
Solar/Wind Harmer
75.442
944601AF1-125 GEN
Solar/Wind Harmer
74.28
316017AA1-139 ULT1
Solar/Wind Harmer
0.171
3144873MCLAUGH
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.319
971153AH1-033 GEN
Solar/Wind Harmer
3.686
316246AF1-032 C
Solar/Wind Harmer
0.137
316321Z2-027
Solar/Wind Harmer
0.055
3144536CHRHLND
Solar/Wind Harmer
0.046
3146516WINFALL
Solar/Wind Harmer
0.301
3146626S HERTFORD
Solar/Wind Harmer
0.297
3146376EDENTON
Solar/Wind Harmer
0.285
3145273HOLLAND
Solar/Wind Harmer
0.208
3145336SMITFLD
Solar/Wind Harmer
0.108
315735AD1-075 GEN1
Solar/Wind Harmer
0.744
944011AF1-069 GEN
Solar/Wind Harmer
15.608
3146206CASHIE
Solar/Wind Harmer
0.254
3156081AA2-088 GEN
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.405
3145893MURPHYS
Solar/Wind Harmer
0.242
3145963POPLR C
Solar/Wind Harmer
0.241
3146173TUNIS
Solar/Wind Harmer
0.24
3151171GRAVELC
Adder
3.318
970917AG2-570 GEN
Solar/Wind Harmer
21.013
3146263WOODLND
Solar/Wind Harmer
0.231
3145823KELFORD
Solar/Wind Harmer
0.229
3145933PARMELE
Solar/Wind Harmer
0.223
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
961611AG1-000B GEN
Solar/Wind Harmer
5.702
970657AG2-426 GEN
Solar/Wind Harmer
4.775
316212AC1-099_GEN
Solar/Wind Harmer
1.096
316011AB1-132 GEN
Solar/Wind Harmer
3.846
3145796HORNRTN
Solar/Wind Harmer
0.836
3145796HORNRTN
Solar/Wind Harmer
0.209
316181AB2-040 GEN
Solar/Wind Harmer
0.296
3146073TAR RVR
Solar/Wind Harmer
0.2
3146083TARBORO
Solar/Wind Harmer
0.2
315722AD1-056 GEN
Solar/Wind Harmer
6.902
316478AD1-087 GEN
Solar/Wind Harmer
0.688
3146233WITAKRS
Solar/Wind Harmer
0.988
3146233WITAKRS
Solar/Wind Harmer
0.134
3138543CONSLDL
Solar/Wind Harmer
0.129
3147043LAWRENC
Solar/Wind Harmer
0.116
961601AG1-000A GEN
Solar/Wind Harmer
13.67
3145543BTLEBRO
Solar/Wind Harmer
0.192
3145543BTLEBRO
Solar/Wind Harmer
0.192
971623AH1-311 GEN
Solar/Wind Harmer
0.384
315813AE1-149 C
Solar/Wind Harmer
9.286
964241AG1-285 GEN
Solar/Wind Harmer
10.893
315778AD1-151 GEN
Solar/Wind Harmer
12.979
970257AG2-171 GEN
Solar/Wind Harmer
4.903
971775AH1-396 GEN
Solar/Wind Harmer
0.245
959311AF2-222 GEN
Solar/Wind Harmer
13.441
316222AC1-221 GEN
Solar/Wind Harmer
0.621
316283AC2-100 C
Solar/Wind Harmer
0.293
316458AB2-190 GEN2
Solar/Wind Harmer
0.753
971683AH1-343 GEN
Solar/Wind Harmer
5.17
3144293JTRSVLE
Adder
0.333
3147133PAMPLIN
Solar/Wind Harmer
0.423
942461AE2-259 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Harmer
0.156
3145893MURPHYS
Solar/Wind Harmer
1.619
3145893MURPHYS
Solar/Wind Harmer
0.435
3146173TUNIS
Solar/Wind Harmer
0.24
3146173TUNIS
Solar/Wind Harmer
0.24
316140AB2-099
Solar/Wind Harmer
0.085
970933AG2-581 GEN
Solar/Wind Harmer
18.911
3145933PARMELE
Solar/Wind Harmer
0.446
3145933PARMELE
Solar/Wind Harmer
0.223
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3142666NORTHAMPTON
Solar/Wind Harmer
0.13
316005AA1-067
Solar/Wind Harmer
0.229
3145593CAROLNA
Solar/Wind Harmer
0.213
3145593CAROLNA
Solar/Wind Harmer
0.213
3145593CAROLNA
Solar/Wind Harmer
0.265
962571AG1-106 GEN
Solar/Wind Harmer
3.016
3145783HORNRTN
Solar/Wind Harmer
3.768
3145783HORNRTN
Solar/Wind Harmer
3.015
3145783HORNRTN
Solar/Wind Harmer
0.942
3145783HORNRTN
Solar/Wind Harmer
0.377
970099AG2-077 GEN
Solar/Wind Harmer
22.381
3145796HORNRTN
Solar/Wind Harmer
0.627
316365GEN2_N
Solar/Wind Harmer
0.464
313506AB2-031 GEN
Solar/Wind Harmer
0.638
3144356SAPONY
Solar/Wind Harmer
1.726
316315AB2-025 C
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.464
3145453TOT5
Solar/Wind Harmer
0.279
3145603CNETO
Solar/Wind Harmer
0.186
315724AD1-057 GEN
Solar/Wind Harmer
3.85
961601AG1-000A GEN
Solar/Wind Harmer
3.418
316049AB1-081 GEN
Solar/Wind Harmer
1.093
316263AC1-034 GEN
Solar/Wind Harmer
7.301
316033AB2-134 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
7.915
964791AG1-342 GEN
Solar/Wind Harmer
3.152
3146843MT LREL
Solar/Wind Harmer
0.164
3146843MT LREL
Solar/Wind Harmer
0.164
316118AC1-105 GEN
Solar/Wind Harmer
0.416
970323AG2-213 GEN
Solar/Wind Harmer
6.537
970301AG2-198 GEN
Solar/Wind Harmer
6.178
958211AF2-115 GEN
Solar/Wind Harmer
1.675
3144293JTRSVLE
Adder
0.333
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
CPLELTFEXP_CPLE->PJM
CLTF
11.715
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.595
LAGNLTFEXP_LAGN->PJM
CLTF
6.931
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.337
TVALTFEXP_TVA->PJM
CLTF
3.445
NYPJM->LTFIMP_NY
CLTF
1.821
LGEELTFEXP_LGEE->PJM
CLTF
0.974
WECLTFEXP_WEC->PJM
CLTF
0.496
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.757
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.566
MECLTFEXP_MEC->PJM
CLTF
2.895
SIGELTFEXP_SIGE->PJM
CLTF
0.084

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.03 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3254.15
MW Contribution:
225.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
225.327
3151081ELIZAR1
50/50
30.231
3151091ELIZAR2
50/50
29.706
941591AE2-156 GEN
50/50
27.53
3151151S HAMPT1
50/50
0.639
316316AC1-027 C
Solar/Wind Harmer
1.069
316018AA1-139 ULT2
Solar/Wind Harmer
2.96
957871AF2-081 GEN
Solar/Wind Harmer
17.319
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.904
3146396TANGLEW
Solar/Wind Harmer
0.611
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.033
3146486SUNBURY
Solar/Wind Harmer
-0.033
315800Z1-036_GEN1
Solar/Wind Harmer
7.672
3130156CHOWAN
Solar/Wind Harmer
-0.031
3130156CHOWAN
Solar/Wind Harmer
-0.031
3151101ELIZAR3
50/50
30.618
3150921YORKTN3
50/50
7.134
3144216WINCHST
50/50
1.058
3151161SURRY 1
50/50
9.582
944581AF1-123 GEN
Solar/Wind Harmer
164.695
944601AF1-125 GEN
Solar/Wind Harmer
162.125
3142956BIRDNECK
Solar/Wind Harmer
1.874
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
2.795
3146456SLIGO L269
Solar/Wind Harmer
-0.034
971153AH1-033 GEN
Solar/Wind Harmer
3.99
316320Y1-086
Solar/Wind Harmer
1.967
316305AF2-043 C
Solar/Wind Harmer
1.005
316246AF1-032 C
Solar/Wind Harmer
0.674
3144536CHRHLND
Solar/Wind Harmer
-0.005
316321Z2-027
Solar/Wind Harmer
0.894
3146516WINFALL
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
3146376EDENTON
Solar/Wind Harmer
-0.031
3145273HOLLAND
Solar/Wind Harmer
-0.022
3145336SMITFLD
Solar/Wind Harmer
-0.012
315735AD1-075 GEN1
Solar/Wind Harmer
2.829
3146206CASHIE
Solar/Wind Harmer
-0.027
3151171GRAVELC
Adder
3.29
3156081AA2-088 GEN
Solar/Wind Harmer
8.551
944011AF1-069 GEN
Solar/Wind Harmer
15.314
3145893MURPHYS
Solar/Wind Harmer
0.181
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145963POPLR C
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3146263WOODLND
Solar/Wind Harmer
-0.025
316317KELFORD C
Solar/Wind Harmer
1.13
3145823KELFORD
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
5.07
970917AG2-570 GEN
Solar/Wind Harmer
59.69
3145933PARMELE
Solar/Wind Harmer
-0.024
970657AG2-426 GEN
Solar/Wind Harmer
4.743
316190AA2-174 GEN
Solar/Wind Harmer
0.283
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316212AC1-099_GEN
Solar/Wind Harmer
1.963
316011AB1-132 GEN
Solar/Wind Harmer
4.694
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.022
316181AB2-040 GEN
Solar/Wind Harmer
3.076
966621AG1-532 GEN
Solar/Wind Harmer
0.439
316420AA1-050 GEN
Solar/Wind Harmer
2.449
3146073TAR RVR
Solar/Wind Harmer
-0.021
3146083TARBORO
Solar/Wind Harmer
-0.021
3152331SURRY 2
50/50
16.773
3150981CHESPKA
50/50
4.092
315773AC2-141 GEN
Solar/Wind Harmer
16.979
944591AF1-124 GEN
Solar/Wind Harmer
165.288
316375AC2-012 GEN
Solar/Wind Harmer
12.002
316036AC1-147 C
Solar/Wind Harmer
0.934
3146456SLIGO L269
Solar/Wind Harmer
-0.034
319010AE1-072 C
Solar/Wind Harmer
6.944
3146516WINFALL
Solar/Wind Harmer
-0.105
3146516WINFALL
Solar/Wind Harmer
-0.032
316072AD1-144
Solar/Wind Harmer
0.647
316093AE2-104_GEN
Solar/Wind Harmer
9.196
939411AE1-173 GEN
Solar/Wind Harmer
155.472
315611Z1-036_GEN2
Solar/Wind Harmer
7.672
3130156CHOWAN
Solar/Wind Harmer
-0.031
3138126ROCKLANDING
Solar/Wind Harmer
0.091
940641AE2-051 GEN
Solar/Wind Harmer
27.808
3145336SMITFLD
Solar/Wind Harmer
-0.118
315816AE2-034 GEN
Solar/Wind Harmer
2.367
3145663CRESWEL
Solar/Wind Harmer
-0.082
971163AH1-040 GEN
Solar/Wind Harmer
27.498
315737AD1-076 GEN
Solar/Wind Harmer
5.322
971317AH1-138 GEN
Solar/Wind Harmer
3.417
3146206CASHIE
Solar/Wind Harmer
-0.027
971547AH1-271 GEN
Solar/Wind Harmer
6.814
3151171GRAVELC
Adder
2.502
3156021HOLLOMANSOL
Solar/Wind Harmer
3.51
941031AE2-094 GEN
Solar/Wind Harmer
48.873
3145893MURPHYS
Solar/Wind Harmer
-0.103
3145893MURPHYS
Solar/Wind Harmer
0.768
3145963POPLR C
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3145823KELFORD
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
11.883
315607AA1-063A GEN
Solar/Wind Harmer
2.415
970919AG2-571 GEN
Solar/Wind Harmer
7.556
3146293MARTNCO
Solar/Wind Harmer
0.147
970087AG2-069 GEN
Solar/Wind Harmer
22.067
316381AD1-082 GEN
Solar/Wind Harmer
2.094
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
316023GEN1_S
Solar/Wind Harmer
1.487
316087AB2-174 GEN
Solar/Wind Harmer
3.127
316494AC1-189 GEN
Solar/Wind Harmer
2.358
960081AF2-299 GEN
Solar/Wind Harmer
2.435
957481AF2-042 GEN
Solar/Wind Harmer
67.467
961671AG1-007 GEN
Solar/Wind Harmer
0.268
3146083TARBORO
Solar/Wind Harmer
-0.021
3145493TOT1
Solar/Wind Harmer
0.628
316319Z2-044 C
Solar/Wind Harmer
1.147
3146233WITAKRS
Solar/Wind Harmer
-0.082
3147043LAWRENC
Adder
1.655
315693AD1-088 GEN
Solar/Wind Harmer
10.204
316129AC1-054 GEN
Solar/Wind Harmer
1.782
316369SG1_INVT
Solar/Wind Harmer
3.631
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316359AB2-059 GEN
Solar/Wind Harmer
2.721
3142053HEARTS
Solar/Wind Harmer
0.238
971065AG2-659 GEN
Solar/Wind Harmer
10.096
971069AG2-661 GEN
Solar/Wind Harmer
2.988
316131AB2-060 GEN
Solar/Wind Harmer
1.933
970401AG2-262 GEN
Solar/Wind Harmer
1.13
315785AD2-033 C
Solar/Wind Harmer
3.847
316034AC1-036 C
Solar/Wind Harmer
0.31
316132AB2-190 GEN1
Solar/Wind Harmer
1.69
970685AG2-442 GEN
Solar/Wind Harmer
13.975
971563AH1-280 GEN
Solar/Wind Harmer
1.96
3144293JTRSVLE
Adder
0.333
3144293JTRSVLE
Adder
0.263
3146926FARMVIL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
2.29
3150991CHESPKB
50/50
3.433
3150991CHESPKB
50/50
3.351
316294AC1-161 GEN
Solar/Wind Harmer
13.122
316185AD1-033 GEN
Solar/Wind Harmer
3.7
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.335
316388AE2-253 GEN
Solar/Wind Harmer
2.335
3137176SLIGO L2192
Solar/Wind Harmer
-0.136
3146456SLIGO L269
Solar/Wind Harmer
4.071
3130086AYDLETT
Solar/Wind Harmer
-0.137
3146386ELIZ CT
Solar/Wind Harmer
-0.033
316431W1029_GEN1
Solar/Wind Harmer
5.908
316433W1029_GEN2
Solar/Wind Harmer
5.908
316435W1029_GEN3
Solar/Wind Harmer
5.908
3146516WINFALL
Solar/Wind Harmer
-0.032
3146516WINFALL
Solar/Wind Harmer
-0.032
3146516WINFALL
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
315835AF2-110_GEN
Solar/Wind Harmer
3.954
3146376EDENTON
Solar/Wind Harmer
0.912
3146376EDENTON
Solar/Wind Harmer
0.912
315614AA2-178 GEN
Solar/Wind Harmer
3.156
315742AE1-103 GEN
Solar/Wind Harmer
6.94
316349AD2-085 GEN
Solar/Wind Harmer
2.509
316065AD1-022 GEN
Solar/Wind Harmer
13.774
3145893MURPHYS
Solar/Wind Harmer
0.722
3145893MURPHYS
Solar/Wind Harmer
-0.046
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
316140AB2-099
Solar/Wind Harmer
0.172
972185AH1-677 GEN
Adder
12.602
972187AH1-678 GEN
Adder
6.302
970933AG2-581 GEN
Solar/Wind Harmer
22.491
3145933PARMELE
Solar/Wind Harmer
-0.047
3145933PARMELE
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316083AB2-161 GEN
Solar/Wind Harmer
3.714
316005AA1-067
Solar/Wind Harmer
0.46
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
0.188
3145783HORNRTN
Solar/Wind Harmer
2.67
3145783HORNRTN
Solar/Wind Harmer
2.136
3145783HORNRTN
Solar/Wind Harmer
0.667
3145783HORNRTN
Solar/Wind Harmer
0.267
962571AG1-106 GEN
Solar/Wind Harmer
3.231
3145796HORNRTN
Solar/Wind Harmer
-0.066
316365GEN2_N
Solar/Wind Harmer
1.487
313506AB2-031 GEN
Solar/Wind Harmer
1.771
3144356SAPONY
Solar/Wind Harmer
0.758
316315AB2-025 C
Solar/Wind Harmer
0.585
970099AG2-077 GEN
Solar/Wind Harmer
26.987
3145493TOT1
Solar/Wind Harmer
0.327
3145453TOT5
Solar/Wind Harmer
0.196
3145603CNETO
Solar/Wind Harmer
0.131
315724AD1-057 GEN
Solar/Wind Harmer
4.126
316033AB2-134 GEN
Solar/Wind Harmer
6.556
961601AG1-000A GEN
Solar/Wind Harmer
7.958
316049AB1-081 GEN
Solar/Wind Harmer
2.177
316263AC1-034 GEN
Solar/Wind Harmer
9.485
315687AD1-152 GEN
Solar/Wind Harmer
2.31
316237AB2-079_GEN
Solar/Wind Harmer
0.543
313527AB2-043 GEN
Solar/Wind Harmer
2.93
962561AG1-105 GEN
Solar/Wind Harmer
9.801
964791AG1-342 GEN
Solar/Wind Harmer
3.698
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
316118AC1-105 GEN
Solar/Wind Harmer
1.169
316248AF1-058 C
Solar/Wind Harmer
0.504
970323AG2-213 GEN
Solar/Wind Harmer
8.391
970301AG2-198 GEN
Solar/Wind Harmer
8.096
958211AF2-115 GEN
Solar/Wind Harmer
2.45
3144293JTRSVLE
Adder
0.333
3147133PAMPLIN
Solar/Wind Harmer
-0.015
3147133PAMPLIN
Solar/Wind Harmer
-0.012
316156AD2-030 GEN
Solar/Wind Harmer
0.341
316236AE1-162_GEN
Solar/Wind Harmer
0.891
971445AH1-216 GEN
Solar/Wind Harmer
18.161
316311AC2-079 GEN
Solar/Wind Harmer
14.288
315833AF1-017_GEN
Solar/Wind Harmer
5.366
3130546PLYMOUTH
Solar/Wind Harmer
-0.028
315732AD1-074 GEN1
Solar/Wind Harmer
5.661
315733AD1-074 GEN2
Solar/Wind Harmer
5.661
3146206CASHIE
Solar/Wind Harmer
-0.027
970601AG2-382 GEN
Solar/Wind Harmer
11.925
3151201GRAVEL4
Adder
17.121
3151221GRAVEL6
Adder
17.101
3151191GRAVEL3
Adder
16.904
3151211GRAVEL5
Adder
16.904
970533AG2-339 GEN
Solar/Wind Harmer
17.528
316318V4-068
Solar/Wind Harmer
0.645
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
-0.026
970673AG2-436 GEN
Solar/Wind Harmer
56.297
316463AE2-346 GEN
Solar/Wind Harmer
0.412
3145513AHOSKIE
Solar/Wind Harmer
0.223
961941AG1-037 GEN
Solar/Wind Harmer
0.192
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.051
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
316174AB2-169 GEN
Solar/Wind Harmer
3.899
971967AH1-528 GEN
Solar/Wind Harmer
46.554
3146043SEABORD
Solar/Wind Harmer
-0.024
970085AG2-068 GEN
Solar/Wind Harmer
14.711
970581AG2-369 GEN
Solar/Wind Harmer
12.652
970657AG2-426 GEN
Solar/Wind Harmer
1.48
3146033SCOT NK
Solar/Wind Harmer
-0.093
316426AA2-053 GEN
Solar/Wind Harmer
2.326
3145746EVERETS
Solar/Wind Harmer
-0.09
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316210AC1-098 GEN
Solar/Wind Harmer
3.534
315652AC1-086 GEN
Solar/Wind Harmer
25.285
3137643SOCKMAN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
2.372
957861AF2-080 GEN
Solar/Wind Harmer
9.59
957831AF2-077 GEN
Solar/Wind Harmer
0.656
3138283WHITEMARSH
Solar/Wind Harmer
0.034
315814AE2-033 C
Solar/Wind Harmer
20.268
946281AF1-292 GEN
Solar/Wind Harmer
0.485
316382AG1-145 C
Solar/Wind Harmer
0.64
316159AE1-175 C
Solar/Wind Harmer
0.57
316327AA2-057 GEN
Solar/Wind Harmer
2.143
3145573BETHELC
Solar/Wind Harmer
-0.021
3145573BETHELC
Solar/Wind Harmer
-0.021
970831AG2-522 GEN
Solar/Wind Harmer
10.322
316486AD2-202 GEN
Solar/Wind Harmer
0.519
315697AD1-025 GEN
Solar/Wind Harmer
4.109
316238AB2-078_GEN
Solar/Wind Harmer
0.543
316239AB2-077_GEN
Solar/Wind Harmer
0.543
3143316POE
Solar/Wind Harmer
-0.071
3147173SINAI
Solar/Wind Harmer
-0.017
3144303KENBRDG
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.01
970683AG2-441 GEN
Solar/Wind Harmer
11.453
970681AG2-440 GEN
Solar/Wind Harmer
7.601
946301AF1-294 GEN
Solar/Wind Harmer
4.019
961791AG1-021 GEN
Solar/Wind Harmer
1.96
315839AE2-212 C
Solar/Wind Harmer
0.428
270455AD2-022 GEN
Solar/Wind Harmer
2.364
270457AD2-023 GEN
Solar/Wind Harmer
1.199
957601AF2-054 GEN
Solar/Wind Harmer
0.383
3141873WAN 176
Solar/Wind Harmer
-0.003
315722AD1-056 GEN
Solar/Wind Harmer
7.502
3146233WITAKRS
Solar/Wind Harmer
0.435
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
3147043LAWRENC
Solar/Wind Harmer
-0.012
316478AD1-087 GEN
Solar/Wind Harmer
1.773
961601AG1-000A GEN
Solar/Wind Harmer
8.059
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
315813AE1-149 C
Solar/Wind Harmer
12.189
315778AD1-151 GEN
Solar/Wind Harmer
16.807
964241AG1-285 GEN
Solar/Wind Harmer
13.751
970257AG2-171 GEN
Solar/Wind Harmer
6.293
971775AH1-396 GEN
Solar/Wind Harmer
1.184
316458AB2-190 GEN2
Solar/Wind Harmer
1.69
959311AF2-222 GEN
Solar/Wind Harmer
17.347
316003AC1-222 GEN
Solar/Wind Harmer
1.54
3144293JTRSVLE
Adder
0.333
316222AC1-221 GEN
Solar/Wind Harmer
1.576
316283AC2-100 C
Solar/Wind Harmer
1.463
3147133PAMPLIN
Solar/Wind Harmer
-0.048
971683AH1-343 GEN
Solar/Wind Harmer
6.345
942461AE2-259 GEN
Solar/Wind Harmer
2.143
3146926FARMVIL
Solar/Wind Harmer
-0.008
970133AG2-095 GEN
Solar/Wind Harmer
1.454
3141873WAN 176
Solar/Wind Harmer
1.519
CPLELTFEXP_CPLE->PJM
CLTF
10.805
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.952
LAGNLTFEXP_LAGN->PJM
CLTF
6.402
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.446
TVALTFEXP_TVA->PJM
CLTF
3.185
NYPJM->LTFIMP_NY
CLTF
1.757
LGEELTFEXP_LGEE->PJM
CLTF
0.901
WECLTFEXP_WEC->PJM
CLTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.391
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.694
MECLTFEXP_MEC->PJM
CLTF
2.671
SIGELTFEXP_SIGE->PJM
CLTF
0.078

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.03 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3254.15
MW Contribution:
225.33
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
16.773
3150981CHESPKA
50/50
4.092
315773AC2-141 GEN
Solar/Wind Harmer
16.979
944591AF1-124 GEN
Solar/Wind Harmer
165.288
316375AC2-012 GEN
Solar/Wind Harmer
12.002
316036AC1-147 C
Solar/Wind Harmer
0.934
3146456SLIGO L269
Solar/Wind Harmer
-0.034
319010AE1-072 C
Solar/Wind Harmer
6.944
3146516WINFALL
Solar/Wind Harmer
-0.105
3146516WINFALL
Solar/Wind Harmer
-0.032
316072AD1-144
Solar/Wind Harmer
0.647
316093AE2-104_GEN
Solar/Wind Harmer
9.196
939411AE1-173 GEN
Solar/Wind Harmer
155.472
315611Z1-036_GEN2
Solar/Wind Harmer
7.672
3130156CHOWAN
Solar/Wind Harmer
-0.031
3138126ROCKLANDING
Solar/Wind Harmer
0.091
940641AE2-051 GEN
Solar/Wind Harmer
27.808
3145336SMITFLD
Solar/Wind Harmer
-0.118
315816AE2-034 GEN
Solar/Wind Harmer
2.367
3145663CRESWEL
Solar/Wind Harmer
-0.082
971163AH1-040 GEN
Solar/Wind Harmer
27.498
315737AD1-076 GEN
Solar/Wind Harmer
5.322
971317AH1-138 GEN
Solar/Wind Harmer
3.417
3146206CASHIE
Solar/Wind Harmer
-0.027
971547AH1-271 GEN
Solar/Wind Harmer
6.814
3151171GRAVELC
Adder
2.502
3156021HOLLOMANSOL
Solar/Wind Harmer
3.51
941031AE2-094 GEN
Solar/Wind Harmer
48.873
3145893MURPHYS
Solar/Wind Harmer
-0.103
3145893MURPHYS
Solar/Wind Harmer
0.768
3145963POPLR C
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3145823KELFORD
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
11.883
315607AA1-063A GEN
Solar/Wind Harmer
2.415
970919AG2-571 GEN
Solar/Wind Harmer
7.556
3146293MARTNCO
Solar/Wind Harmer
0.147
970087AG2-069 GEN
Solar/Wind Harmer
22.067
316381AD1-082 GEN
Solar/Wind Harmer
2.094
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
316023GEN1_S
Solar/Wind Harmer
1.487
316087AB2-174 GEN
Solar/Wind Harmer
3.127
316494AC1-189 GEN
Solar/Wind Harmer
2.358
960081AF2-299 GEN
Solar/Wind Harmer
2.435
957481AF2-042 GEN
Solar/Wind Harmer
67.467
961671AG1-007 GEN
Solar/Wind Harmer
0.268
3146083TARBORO
Solar/Wind Harmer
-0.021
3145493TOT1
Solar/Wind Harmer
0.628
316319Z2-044 C
Solar/Wind Harmer
1.147
3146233WITAKRS
Solar/Wind Harmer
-0.082
3147043LAWRENC
Adder
1.655
315693AD1-088 GEN
Solar/Wind Harmer
10.204
316129AC1-054 GEN
Solar/Wind Harmer
1.782
316369SG1_INVT
Solar/Wind Harmer
3.631
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316359AB2-059 GEN
Solar/Wind Harmer
2.721
3142053HEARTS
Solar/Wind Harmer
0.238
971065AG2-659 GEN
Solar/Wind Harmer
10.096
971069AG2-661 GEN
Solar/Wind Harmer
2.988
316131AB2-060 GEN
Solar/Wind Harmer
1.933
970401AG2-262 GEN
Solar/Wind Harmer
1.13
315785AD2-033 C
Solar/Wind Harmer
3.847
316034AC1-036 C
Solar/Wind Harmer
0.31
316132AB2-190 GEN1
Solar/Wind Harmer
1.69
970685AG2-442 GEN
Solar/Wind Harmer
13.975
971563AH1-280 GEN
Solar/Wind Harmer
1.96
3144293JTRSVLE
Adder
0.333
3144293JTRSVLE
Adder
0.263
3146926FARMVIL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
2.29
3150991CHESPKB
50/50
3.433
3150991CHESPKB
50/50
3.351
316294AC1-161 GEN
Solar/Wind Harmer
13.122
316185AD1-033 GEN
Solar/Wind Harmer
3.7
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.335
316388AE2-253 GEN
Solar/Wind Harmer
2.335
3137176SLIGO L2192
Solar/Wind Harmer
-0.136
3146456SLIGO L269
Solar/Wind Harmer
4.071
3130086AYDLETT
Solar/Wind Harmer
-0.137
3146386ELIZ CT
Solar/Wind Harmer
-0.033
316431W1029_GEN1
Solar/Wind Harmer
5.908
316433W1029_GEN2
Solar/Wind Harmer
5.908
316435W1029_GEN3
Solar/Wind Harmer
5.908
3146516WINFALL
Solar/Wind Harmer
-0.032
3146516WINFALL
Solar/Wind Harmer
-0.032
3146516WINFALL
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
315835AF2-110_GEN
Solar/Wind Harmer
3.954
3146376EDENTON
Solar/Wind Harmer
0.912
3146376EDENTON
Solar/Wind Harmer
0.912
315614AA2-178 GEN
Solar/Wind Harmer
3.156
315742AE1-103 GEN
Solar/Wind Harmer
6.94
316349AD2-085 GEN
Solar/Wind Harmer
2.509
316065AD1-022 GEN
Solar/Wind Harmer
13.774
3145893MURPHYS
Solar/Wind Harmer
0.722
3145893MURPHYS
Solar/Wind Harmer
-0.046
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
316140AB2-099
Solar/Wind Harmer
0.172
972185AH1-677 GEN
Adder
12.602
972187AH1-678 GEN
Adder
6.302
970933AG2-581 GEN
Solar/Wind Harmer
22.491
3145933PARMELE
Solar/Wind Harmer
-0.047
3145933PARMELE
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316083AB2-161 GEN
Solar/Wind Harmer
3.714
316005AA1-067
Solar/Wind Harmer
0.46
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
0.188
3145783HORNRTN
Solar/Wind Harmer
2.67
3145783HORNRTN
Solar/Wind Harmer
2.136
3145783HORNRTN
Solar/Wind Harmer
0.667
3145783HORNRTN
Solar/Wind Harmer
0.267
962571AG1-106 GEN
Solar/Wind Harmer
3.231
3145796HORNRTN
Solar/Wind Harmer
-0.066
316365GEN2_N
Solar/Wind Harmer
1.487
313506AB2-031 GEN
Solar/Wind Harmer
1.771
3144356SAPONY
Solar/Wind Harmer
0.758
316315AB2-025 C
Solar/Wind Harmer
0.585
970099AG2-077 GEN
Solar/Wind Harmer
26.987
3145493TOT1
Solar/Wind Harmer
0.327
3145453TOT5
Solar/Wind Harmer
0.196
3145603CNETO
Solar/Wind Harmer
0.131
315724AD1-057 GEN
Solar/Wind Harmer
4.126
316033AB2-134 GEN
Solar/Wind Harmer
6.556
961601AG1-000A GEN
Solar/Wind Harmer
7.958
316049AB1-081 GEN
Solar/Wind Harmer
2.177
316263AC1-034 GEN
Solar/Wind Harmer
9.485
315687AD1-152 GEN
Solar/Wind Harmer
2.31
316237AB2-079_GEN
Solar/Wind Harmer
0.543
313527AB2-043 GEN
Solar/Wind Harmer
2.93
962561AG1-105 GEN
Solar/Wind Harmer
9.801
964791AG1-342 GEN
Solar/Wind Harmer
3.698
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
316118AC1-105 GEN
Solar/Wind Harmer
1.169
316248AF1-058 C
Solar/Wind Harmer
0.504
970323AG2-213 GEN
Solar/Wind Harmer
8.391
970301AG2-198 GEN
Solar/Wind Harmer
8.096
958211AF2-115 GEN
Solar/Wind Harmer
2.45
3144293JTRSVLE
Adder
0.333
3147133PAMPLIN
Solar/Wind Harmer
-0.015
3147133PAMPLIN
Solar/Wind Harmer
-0.012
316156AD2-030 GEN
Solar/Wind Harmer
0.341
972263AH1-716 GEN
50/50
225.327
3151081ELIZAR1
50/50
30.231
3151091ELIZAR2
50/50
29.706
941591AE2-156 GEN
50/50
27.53
3151151S HAMPT1
50/50
0.639
316316AC1-027 C
Solar/Wind Harmer
1.069
316018AA1-139 ULT2
Solar/Wind Harmer
2.96
957871AF2-081 GEN
Solar/Wind Harmer
17.319
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.904
3146396TANGLEW
Solar/Wind Harmer
0.611
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.033
3146486SUNBURY
Solar/Wind Harmer
-0.033
315800Z1-036_GEN1
Solar/Wind Harmer
7.672
3130156CHOWAN
Solar/Wind Harmer
-0.031
3130156CHOWAN
Solar/Wind Harmer
-0.031
316236AE1-162_GEN
Solar/Wind Harmer
0.891
971445AH1-216 GEN
Solar/Wind Harmer
18.161
316311AC2-079 GEN
Solar/Wind Harmer
14.288
315833AF1-017_GEN
Solar/Wind Harmer
5.366
3130546PLYMOUTH
Solar/Wind Harmer
-0.028
315732AD1-074 GEN1
Solar/Wind Harmer
5.661
315733AD1-074 GEN2
Solar/Wind Harmer
5.661
3146206CASHIE
Solar/Wind Harmer
-0.027
970601AG2-382 GEN
Solar/Wind Harmer
11.925
3151201GRAVEL4
Adder
17.121
3151221GRAVEL6
Adder
17.101
3151191GRAVEL3
Adder
16.904
3151211GRAVEL5
Adder
16.904
970533AG2-339 GEN
Solar/Wind Harmer
17.528
316318V4-068
Solar/Wind Harmer
0.645
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
-0.026
970673AG2-436 GEN
Solar/Wind Harmer
56.297
316463AE2-346 GEN
Solar/Wind Harmer
0.412
3145513AHOSKIE
Solar/Wind Harmer
0.223
961941AG1-037 GEN
Solar/Wind Harmer
0.192
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.051
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
316174AB2-169 GEN
Solar/Wind Harmer
3.899
971967AH1-528 GEN
Solar/Wind Harmer
46.554
3146043SEABORD
Solar/Wind Harmer
-0.024
970085AG2-068 GEN
Solar/Wind Harmer
14.711
970581AG2-369 GEN
Solar/Wind Harmer
12.652
970657AG2-426 GEN
Solar/Wind Harmer
1.48
3146033SCOT NK
Solar/Wind Harmer
-0.093
316426AA2-053 GEN
Solar/Wind Harmer
2.326
3145746EVERETS
Solar/Wind Harmer
-0.09
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316210AC1-098 GEN
Solar/Wind Harmer
3.534
315652AC1-086 GEN
Solar/Wind Harmer
25.285
3137643SOCKMAN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
316274AC1-208 GEN
Solar/Wind Harmer
2.372
957861AF2-080 GEN
Solar/Wind Harmer
9.59
957831AF2-077 GEN
Solar/Wind Harmer
0.656
3138283WHITEMARSH
Solar/Wind Harmer
0.034
315814AE2-033 C
Solar/Wind Harmer
20.268
946281AF1-292 GEN
Solar/Wind Harmer
0.485
316382AG1-145 C
Solar/Wind Harmer
0.64
316159AE1-175 C
Solar/Wind Harmer
0.57
316327AA2-057 GEN
Solar/Wind Harmer
2.143
3145573BETHELC
Solar/Wind Harmer
-0.021
3145573BETHELC
Solar/Wind Harmer
-0.021
970831AG2-522 GEN
Solar/Wind Harmer
10.322
316486AD2-202 GEN
Solar/Wind Harmer
0.519
315697AD1-025 GEN
Solar/Wind Harmer
4.109
316238AB2-078_GEN
Solar/Wind Harmer
0.543
316239AB2-077_GEN
Solar/Wind Harmer
0.543
3143316POE
Solar/Wind Harmer
-0.071
3147173SINAI
Solar/Wind Harmer
-0.017
3144303KENBRDG
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.01
970683AG2-441 GEN
Solar/Wind Harmer
11.453
970681AG2-440 GEN
Solar/Wind Harmer
7.601
946301AF1-294 GEN
Solar/Wind Harmer
4.019
961791AG1-021 GEN
Solar/Wind Harmer
1.96
315839AE2-212 C
Solar/Wind Harmer
0.428
270455AD2-022 GEN
Solar/Wind Harmer
2.364
270457AD2-023 GEN
Solar/Wind Harmer
1.199
957601AF2-054 GEN
Solar/Wind Harmer
0.383
3141873WAN 176
Solar/Wind Harmer
-0.003
3151101ELIZAR3
50/50
30.618
3150921YORKTN3
50/50
7.134
3144216WINCHST
50/50
1.058
3151161SURRY 1
50/50
9.582
944581AF1-123 GEN
Solar/Wind Harmer
164.695
944601AF1-125 GEN
Solar/Wind Harmer
162.125
3142956BIRDNECK
Solar/Wind Harmer
1.874
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316017AA1-139 ULT1
Solar/Wind Harmer
2.795
3146456SLIGO L269
Solar/Wind Harmer
-0.034
971153AH1-033 GEN
Solar/Wind Harmer
3.99
316320Y1-086
Solar/Wind Harmer
1.967
316305AF2-043 C
Solar/Wind Harmer
1.005
316246AF1-032 C
Solar/Wind Harmer
0.674
3144536CHRHLND
Solar/Wind Harmer
-0.005
316321Z2-027
Solar/Wind Harmer
0.894
3146516WINFALL
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
3146376EDENTON
Solar/Wind Harmer
-0.031
3145273HOLLAND
Solar/Wind Harmer
-0.022
3145336SMITFLD
Solar/Wind Harmer
-0.012
315735AD1-075 GEN1
Solar/Wind Harmer
2.829
3146206CASHIE
Solar/Wind Harmer
-0.027
3151171GRAVELC
Adder
3.29
3156081AA2-088 GEN
Solar/Wind Harmer
8.551
944011AF1-069 GEN
Solar/Wind Harmer
15.314
3145893MURPHYS
Solar/Wind Harmer
0.181
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145963POPLR C
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3146263WOODLND
Solar/Wind Harmer
-0.025
316317KELFORD C
Solar/Wind Harmer
1.13
3145823KELFORD
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
5.07
970917AG2-570 GEN
Solar/Wind Harmer
59.69
3145933PARMELE
Solar/Wind Harmer
-0.024
970657AG2-426 GEN
Solar/Wind Harmer
4.743
316190AA2-174 GEN
Solar/Wind Harmer
0.283
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316212AC1-099_GEN
Solar/Wind Harmer
1.963
316011AB1-132 GEN
Solar/Wind Harmer
4.694
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.022
316181AB2-040 GEN
Solar/Wind Harmer
3.076
966621AG1-532 GEN
Solar/Wind Harmer
0.439
316420AA1-050 GEN
Solar/Wind Harmer
2.449
3146073TAR RVR
Solar/Wind Harmer
-0.021
3146083TARBORO
Solar/Wind Harmer
-0.021
315722AD1-056 GEN
Solar/Wind Harmer
7.502
3146233WITAKRS
Solar/Wind Harmer
0.435
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
3147043LAWRENC
Solar/Wind Harmer
-0.012
316478AD1-087 GEN
Solar/Wind Harmer
1.773
961601AG1-000A GEN
Solar/Wind Harmer
8.059
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
315813AE1-149 C
Solar/Wind Harmer
12.189
315778AD1-151 GEN
Solar/Wind Harmer
16.807
964241AG1-285 GEN
Solar/Wind Harmer
13.751
970257AG2-171 GEN
Solar/Wind Harmer
6.293
971775AH1-396 GEN
Solar/Wind Harmer
1.184
316458AB2-190 GEN2
Solar/Wind Harmer
1.69
959311AF2-222 GEN
Solar/Wind Harmer
17.347
316003AC1-222 GEN
Solar/Wind Harmer
1.54
3144293JTRSVLE
Adder
0.333
316222AC1-221 GEN
Solar/Wind Harmer
1.576
316283AC2-100 C
Solar/Wind Harmer
1.463
3147133PAMPLIN
Solar/Wind Harmer
-0.048
971683AH1-343 GEN
Solar/Wind Harmer
6.345
942461AE2-259 GEN
Solar/Wind Harmer
2.143
3146926FARMVIL
Solar/Wind Harmer
-0.008
970133AG2-095 GEN
Solar/Wind Harmer
1.454
3141873WAN 176
Solar/Wind Harmer
1.519
CPLELTFEXP_CPLE->PJM
CLTF
10.805
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.952
LAGNLTFEXP_LAGN->PJM
CLTF
6.402
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.446
TVALTFEXP_TVA->PJM
CLTF
3.185
NYPJM->LTFIMP_NY
CLTF
1.757
LGEELTFEXP_LGEE->PJM
CLTF
0.901
WECLTFEXP_WEC->PJM
CLTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.391
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.694
MECLTFEXP_MEC->PJM
CLTF
2.671
SIGELTFEXP_SIGE->PJM
CLTF
0.078

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.63 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2555.09
MW Contribution:
225.34
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
225.336
3151081ELIZAR1
50/50
30.232
3151091ELIZAR2
50/50
29.707
941591AE2-156 GEN
50/50
27.531
3151151S HAMPT1
50/50
0.639
316316AC1-027 C
Solar/Wind Harmer
0.296
957871AF2-081 GEN
Solar/Wind Harmer
15.346
3146406KITTY HAWK
Solar/Wind Harmer
0.038
313526AB2-022
Solar/Wind Harmer
0.16
3146396TANGLEW
Solar/Wind Harmer
0.815
3145176PASQUOTANK
Solar/Wind Harmer
0.183
3146486SUNBURY
Solar/Wind Harmer
0.293
3146486SUNBURY
Solar/Wind Harmer
0.293
3130156CHOWAN
Solar/Wind Harmer
0.273
3130156CHOWAN
Solar/Wind Harmer
0.273
971445AH1-216 GEN
Solar/Wind Harmer
18.391
316311AC2-079 GEN
Solar/Wind Harmer
7.239
3130546PLYMOUTH
Solar/Wind Harmer
0.251
315732AD1-074 GEN1
Solar/Wind Harmer
1.422
315733AD1-074 GEN2
Solar/Wind Harmer
1.422
3146206CASHIE
Solar/Wind Harmer
0.242
970601AG2-382 GEN
Solar/Wind Harmer
9.057
3151201GRAVEL4
Adder
17.122
3151221GRAVEL6
Adder
17.102
3151191GRAVEL3
Adder
16.905
3151211GRAVEL5
Adder
16.905
970533AG2-339 GEN
Solar/Wind Harmer
17.528
3145893MURPHYS
Solar/Wind Harmer
0.622
3145893MURPHYS
Solar/Wind Harmer
0.23
970673AG2-436 GEN
Solar/Wind Harmer
28.504
316463AE2-346 GEN
Solar/Wind Harmer
0.194
3145513AHOSKIE
Solar/Wind Harmer
0.475
3145513AHOSKIE
Solar/Wind Harmer
0.227
3145683EARLEYS
Solar/Wind Harmer
0.452
3145683EARLEYS
Solar/Wind Harmer
0.226
3145683EARLEYS
Solar/Wind Harmer
0.226
971967AH1-528 GEN
Solar/Wind Harmer
35.261
3146043SEABORD
Solar/Wind Harmer
0.215
970085AG2-068 GEN
Solar/Wind Harmer
11.172
970581AG2-369 GEN
Solar/Wind Harmer
9.608
970657AG2-426 GEN
Solar/Wind Harmer
1.535
3146033SCOT NK
Solar/Wind Harmer
0.832
316426AA2-053 GEN
Solar/Wind Harmer
0.687
3145746EVERETS
Solar/Wind Harmer
0.807
3145746EVERETS
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.203
316210AC1-098 GEN
Solar/Wind Harmer
1.856
315652AC1-086 GEN
Solar/Wind Harmer
21.994
3137643SOCKMAN
Solar/Wind Harmer
0.794
3145796HORNRTN
Solar/Wind Harmer
0.63
3145796HORNRTN
Solar/Wind Harmer
0.079
316274AC1-208 GEN
Solar/Wind Harmer
1.011
957861AF2-080 GEN
Solar/Wind Harmer
8.41
3138283WHITEMARSH
Solar/Wind Harmer
0.045
315814AE2-033 C
Solar/Wind Harmer
15.324
316159AE1-175 C
Solar/Wind Harmer
0.162
316327AA2-057 GEN
Solar/Wind Harmer
0.28
3145573BETHELC
Solar/Wind Harmer
0.188
3145573BETHELC
Solar/Wind Harmer
0.188
970831AG2-522 GEN
Solar/Wind Harmer
7.838
316486AD2-202 GEN
Solar/Wind Harmer
0.186
315697AD1-025 GEN
Solar/Wind Harmer
0.195
3143316POE
Solar/Wind Harmer
0.633
3147173SINAI
Solar/Wind Harmer
0.149
3147243WELCO
Solar/Wind Harmer
0.093
3144303KENBRDG
Solar/Wind Harmer
0.119
970683AG2-441 GEN
Solar/Wind Harmer
8.693
3151101ELIZAR3
50/50
30.619
3150921YORKTN3
50/50
7.134
3144216WINCHST
50/50
1.059
3151161SURRY 1
50/50
9.582
944581AF1-123 GEN
Solar/Wind Harmer
72.554
944601AF1-125 GEN
Solar/Wind Harmer
71.437
3144873MCLAUGH
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.164
3146456SLIGO L269
Solar/Wind Harmer
0.307
971153AH1-033 GEN
Solar/Wind Harmer
3.546
316246AF1-032 C
Solar/Wind Harmer
0.132
3144536CHRHLND
Solar/Wind Harmer
0.044
316321Z2-027
Solar/Wind Harmer
0.053
3146516WINFALL
Solar/Wind Harmer
0.289
3146626S HERTFORD
Solar/Wind Harmer
0.285
3146376EDENTON
Solar/Wind Harmer
0.273
3145273HOLLAND
Solar/Wind Harmer
0.2
3152331SURRY 2
50/50
16.774
3150981CHESPKA
50/50
4.092
315773AC2-141 GEN
Solar/Wind Harmer
13.184
944591AF1-124 GEN
Solar/Wind Harmer
72.812
316375AC2-012 GEN
Solar/Wind Harmer
-0.001
316036AC1-147 C
Solar/Wind Harmer
0.055
3146456SLIGO L269
Solar/Wind Harmer
0.307
319010AE1-072 C
Solar/Wind Harmer
1.527
3146516WINFALL
Solar/Wind Harmer
0.937
3146516WINFALL
Solar/Wind Harmer
0.289
316072AD1-144
Solar/Wind Harmer
0.102
316093AE2-104_GEN
Solar/Wind Harmer
4.734
939411AE1-173 GEN
Solar/Wind Harmer
118.081
3130156CHOWAN
Solar/Wind Harmer
0.273
3138126ROCKLANDING
Solar/Wind Harmer
0.122
940641AE2-051 GEN
Solar/Wind Harmer
21.12
3145336SMITFLD
Solar/Wind Harmer
1.055
315816AE2-034 GEN
Solar/Wind Harmer
1.114
3145663CRESWEL
Solar/Wind Harmer
0.731
971163AH1-040 GEN
Solar/Wind Harmer
20.885
315737AD1-076 GEN
Solar/Wind Harmer
3.202
971317AH1-138 GEN
Solar/Wind Harmer
1.817
3146206CASHIE
Solar/Wind Harmer
0.242
971547AH1-271 GEN
Solar/Wind Harmer
5.175
3151171GRAVELC
Adder
2.502
3156021HOLLOMANSOL
Solar/Wind Harmer
1.046
941031AE2-094 GEN
Solar/Wind Harmer
42.726
3145893MURPHYS
Solar/Wind Harmer
0.921
3145893MURPHYS
Solar/Wind Harmer
1.024
3145963POPLR C
Solar/Wind Harmer
0.229
3146173TUNIS
Solar/Wind Harmer
0.228
3145683EARLEYS
Solar/Wind Harmer
0.226
3146263WOODLND
Solar/Wind Harmer
0.219
3145823KELFORD
Solar/Wind Harmer
0.217
961611AG1-000B GEN
Solar/Wind Harmer
11.24
315607AA1-063A GEN
Solar/Wind Harmer
0.429
970919AG2-571 GEN
Solar/Wind Harmer
7.555
3146293MARTNCO
Solar/Wind Harmer
0.196
970087AG2-069 GEN
Solar/Wind Harmer
16.759
316381AD1-082 GEN
Solar/Wind Harmer
0.207
3145746EVERETS
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.203
3145783HORNRTN
Solar/Wind Harmer
0.2
3145796HORNRTN
Solar/Wind Harmer
0.65
3145796HORNRTN
Solar/Wind Harmer
0.197
316023GEN1_S
Solar/Wind Harmer
0.437
316494AC1-189 GEN
Solar/Wind Harmer
0.659
960081AF2-299 GEN
Solar/Wind Harmer
1.85
957481AF2-042 GEN
Solar/Wind Harmer
51.232
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.188
3145493TOT1
Solar/Wind Harmer
0.837
3146233WITAKRS
Solar/Wind Harmer
0.735
3147043LAWRENC
Adder
1.655
315693AD1-088 GEN
Solar/Wind Harmer
8.716
316129AC1-054 GEN
Solar/Wind Harmer
0.677
3145543BTLEBRO
Solar/Wind Harmer
0.18
3150991CHESPKB
50/50
3.433
3150991CHESPKB
50/50
3.351
316294AC1-161 GEN
Solar/Wind Harmer
6.24
3145506HICKORY
Solar/Wind Harmer
1.246
3145506HICKORY
Solar/Wind Harmer
0.748
3145506HICKORY
Solar/Wind Harmer
0.187
316339AD2-160 GEN
Solar/Wind Harmer
0.494
3145336SMITFLD
Solar/Wind Harmer
0.106
315735AD1-075 GEN1
Solar/Wind Harmer
0.71
3146206CASHIE
Solar/Wind Harmer
0.242
3151171GRAVELC
Adder
3.29
3156081AA2-088 GEN
Solar/Wind Harmer
0
944011AF1-069 GEN
Solar/Wind Harmer
13.96
3145893MURPHYS
Solar/Wind Harmer
0.385
3145893MURPHYS
Solar/Wind Harmer
0.23
3145963POPLR C
Solar/Wind Harmer
0.229
3146173TUNIS
Solar/Wind Harmer
0.228
3146263WOODLND
Solar/Wind Harmer
0.219
3145823KELFORD
Solar/Wind Harmer
0.217
961611AG1-000B GEN
Solar/Wind Harmer
5.715
970917AG2-570 GEN
Solar/Wind Harmer
18.888
3145933PARMELE
Solar/Wind Harmer
0.211
970657AG2-426 GEN
Solar/Wind Harmer
4.689
3142666NORTHAMPTON
Solar/Wind Harmer
0.204
3145746EVERETS
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.203
316212AC1-099_GEN
Solar/Wind Harmer
1.035
316011AB1-132 GEN
Solar/Wind Harmer
3.627
3145796HORNRTN
Solar/Wind Harmer
0.788
3145796HORNRTN
Solar/Wind Harmer
0.197
316181AB2-040 GEN
Solar/Wind Harmer
0.28
3146073TAR RVR
Solar/Wind Harmer
0.188
3146083TARBORO
Solar/Wind Harmer
0.188
315722AD1-056 GEN
Solar/Wind Harmer
6.485
3146233WITAKRS
Solar/Wind Harmer
0.927
3146233WITAKRS
Solar/Wind Harmer
0.126
3138543CONSLDL
Solar/Wind Harmer
0.122
3147043LAWRENC
Solar/Wind Harmer
0.11
316478AD1-087 GEN
Solar/Wind Harmer
0.633
961601AG1-000A GEN
Solar/Wind Harmer
12.813
3145543BTLEBRO
Solar/Wind Harmer
0.18
3145543BTLEBRO
Solar/Wind Harmer
0.18
971623AH1-311 GEN
Solar/Wind Harmer
0.36
315813AE1-149 C
Solar/Wind Harmer
9.258
315778AD1-151 GEN
Solar/Wind Harmer
13.447
964241AG1-285 GEN
Solar/Wind Harmer
10.439
970257AG2-171 GEN
Solar/Wind Harmer
4.777
971775AH1-396 GEN
Solar/Wind Harmer
0.239
316458AB2-190 GEN2
Solar/Wind Harmer
0.795
959311AF2-222 GEN
Solar/Wind Harmer
13.141
3144293JTRSVLE
Adder
0.333
316222AC1-221 GEN
Solar/Wind Harmer
0.572
316283AC2-100 C
Solar/Wind Harmer
0.27
3147133PAMPLIN
Solar/Wind Harmer
0.427
971683AH1-343 GEN
Solar/Wind Harmer
4.817
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.07
970133AG2-095 GEN
Solar/Wind Harmer
1.104
3141873WAN 176
Solar/Wind Harmer
2.026
316388AE2-253 GEN
Solar/Wind Harmer
0.961
3137176SLIGO L2192
Solar/Wind Harmer
1.221
3146456SLIGO L269
Solar/Wind Harmer
5.429
3130086AYDLETT
Solar/Wind Harmer
1.222
3146386ELIZ CT
Solar/Wind Harmer
0.299
3146516WINFALL
Solar/Wind Harmer
0.289
3146516WINFALL
Solar/Wind Harmer
0.289
3146516WINFALL
Solar/Wind Harmer
0.289
3146626S HERTFORD
Solar/Wind Harmer
0.285
3146626S HERTFORD
Solar/Wind Harmer
0.285
315835AF2-110_GEN
Solar/Wind Harmer
1.932
3146376EDENTON
Solar/Wind Harmer
1.216
3146376EDENTON
Solar/Wind Harmer
1.216
315614AA2-178 GEN
Solar/Wind Harmer
1.485
315742AE1-103 GEN
Solar/Wind Harmer
3.886
316349AD2-085 GEN
Solar/Wind Harmer
0.168
316065AD1-022 GEN
Solar/Wind Harmer
11.289
3145893MURPHYS
Solar/Wind Harmer
1.541
3145893MURPHYS
Solar/Wind Harmer
0.414
3146173TUNIS
Solar/Wind Harmer
0.228
3146173TUNIS
Solar/Wind Harmer
0.228
316140AB2-099
Solar/Wind Harmer
0.081
972185AH1-677 GEN
Adder
12.602
972187AH1-678 GEN
Adder
6.302
970933AG2-581 GEN
Solar/Wind Harmer
17.08
3145933PARMELE
Solar/Wind Harmer
0.422
3145933PARMELE
Solar/Wind Harmer
0.211
3142666NORTHAMPTON
Solar/Wind Harmer
0.204
3142666NORTHAMPTON
Solar/Wind Harmer
0.204
3142666NORTHAMPTON
Solar/Wind Harmer
0.204
3142666NORTHAMPTON
Solar/Wind Harmer
0.122
316005AA1-067
Solar/Wind Harmer
0.216
3145593CAROLNA
Solar/Wind Harmer
0.201
3145593CAROLNA
Solar/Wind Harmer
0.201
3145593CAROLNA
Solar/Wind Harmer
0.25
3145783HORNRTN
Solar/Wind Harmer
3.559
3145783HORNRTN
Solar/Wind Harmer
2.847
3145783HORNRTN
Solar/Wind Harmer
0.89
3145783HORNRTN
Solar/Wind Harmer
0.356
962571AG1-106 GEN
Solar/Wind Harmer
2.845
3145796HORNRTN
Solar/Wind Harmer
0.591
316365GEN2_N
Solar/Wind Harmer
0.437
313506AB2-031 GEN
Solar/Wind Harmer
0.602
3144356SAPONY
Solar/Wind Harmer
1.619
316315AB2-025 C
Solar/Wind Harmer
0.155
970099AG2-077 GEN
Solar/Wind Harmer
20.493
3145493TOT1
Solar/Wind Harmer
0.437
3145453TOT5
Solar/Wind Harmer
0.262
3145603CNETO
Solar/Wind Harmer
0.175
315724AD1-057 GEN
Solar/Wind Harmer
3.617
316033AB2-134 GEN
Solar/Wind Harmer
0.001
961601AG1-000A GEN
Solar/Wind Harmer
3.203
316049AB1-081 GEN
Solar/Wind Harmer
1.024
316263AC1-034 GEN
Solar/Wind Harmer
6.843
962561AG1-105 GEN
Solar/Wind Harmer
7.442
964791AG1-342 GEN
Solar/Wind Harmer
2.957
3146843MT LREL
Solar/Wind Harmer
0.154
3146843MT LREL
Solar/Wind Harmer
0.154
316118AC1-105 GEN
Solar/Wind Harmer
0.388
970323AG2-213 GEN
Solar/Wind Harmer
6.369
970301AG2-198 GEN
Solar/Wind Harmer
6.144
958211AF2-115 GEN
Solar/Wind Harmer
1.674
3144293JTRSVLE
Adder
0.333
3147133PAMPLIN
Solar/Wind Harmer
0.136
3147133PAMPLIN
Solar/Wind Harmer
0.109
316156AD2-030 GEN
Solar/Wind Harmer
0.083
3145543BTLEBRO
Solar/Wind Harmer
0.144
316359AB2-059 GEN
Solar/Wind Harmer
0.64
3142053HEARTS
Solar/Wind Harmer
0.317
971065AG2-659 GEN
Solar/Wind Harmer
7.666
971069AG2-661 GEN
Solar/Wind Harmer
2.988
316131AB2-060 GEN
Solar/Wind Harmer
0.497
970401AG2-262 GEN
Solar/Wind Harmer
0.904
315785AD2-033 C
Solar/Wind Harmer
1.223
316034AC1-036 C
Solar/Wind Harmer
0.01
316132AB2-190 GEN1
Solar/Wind Harmer
0.795
970685AG2-442 GEN
Solar/Wind Harmer
10.607
971563AH1-280 GEN
Solar/Wind Harmer
1.488
3144293JTRSVLE
Adder
0.333
3144293JTRSVLE
Adder
0.263
3146926FARMVIL
Solar/Wind Harmer
0.07
315671AE2-027_GEN
Solar/Wind Harmer
0.001
970681AG2-440 GEN
Solar/Wind Harmer
5.77
946301AF1-294 GEN
Solar/Wind Harmer
2.753
961791AG1-021 GEN
Solar/Wind Harmer
1.339
3141873WAN 176
Solar/Wind Harmer
0.023
CPLELTFEXP_CPLE->PJM
CLTF
10.803
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.929
LAGNLTFEXP_LAGN->PJM
CLTF
6.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.44
TVALTFEXP_TVA->PJM
CLTF
3.183
NYPJM->LTFIMP_NY
CLTF
1.756
LGEELTFEXP_LGEE->PJM
CLTF
0.9
WECLTFEXP_WEC->PJM
CLTF
0.456
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.371
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.687
MECLTFEXP_MEC->PJM
CLTF
2.668
SIGELTFEXP_SIGE->PJM
CLTF
0.078

Details for AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.8 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:598.97
MW Contribution:
32.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.942
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.813
3151201GRAVEL4
50/50
4.347
3151221GRAVEL6
50/50
4.342
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.078
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151191GRAVEL3
Adder
4.044
3151211GRAVEL5
Adder
4.044
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.005
966661AG1-536 GEN
50/50
6.847
315749AE2-041 GEN
50/50
4.942
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.927
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.609
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.874
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.044
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.599
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
CPLELTFEXP_CPLE->PJM
CLTF
1.988
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.795
LAGNLTFEXP_LAGN->PJM
CLTF
1.468
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.366
TVALTFEXP_TVA->PJM
CLTF
0.742
NYPJM->LTFIMP_NY
CLTF
0.569
LGEELTFEXP_LGEE->PJM
CLTF
0.269
WECLTFEXP_WEC->PJM
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.602
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.549
MECLTFEXP_MEC->PJM
CLTF
0.719
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.93 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:631.64
MW Contribution:
32.81
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.955
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.874
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.296
3141726DUNNSVL
Solar/Wind Harmer
1.044
316404AE1-155 C
Solar/Wind Harmer
0
958261AF2-120 GEN
Solar/Wind Harmer
7.959
962861AG1-135 GEN
Solar/Wind Harmer
7.519
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
315975AC1-164 GENB
Solar/Wind Harmer
0.025
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.599
315759AF1-018 GEN
50/50
4.942
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150631CHESTG8
50/50
0.394
970603AG2-384 GEN
50/50
1.344
972263AH1-716 GEN
50/50
32.813
3151201GRAVEL4
50/50
4.347
3151221GRAVEL6
50/50
4.342
944491AF1-114 GEN
Solar/Wind Harmer
0
3141813NORNECK
Solar/Wind Harmer
0.279
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
970189AG2-124 GEN
Solar/Wind Harmer
4.078
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
316159AE1-175 C
Solar/Wind Harmer
0.064
3151191GRAVEL3
Adder
4.044
3151211GRAVEL5
Adder
4.044
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.005
966661AG1-536 GEN
50/50
6.847
315749AE2-041 GEN
50/50
4.942
3141843SHACKLE
50/50
0.745
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.927
3144216WINCHST
50/50
0.279
3150611CHESTG7
50/50
0.4
3151161SURRY 1
50/50
2.292
316223AC1-118
Solar/Wind Harmer
0.293
3141906WESTMOR
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
2.609
3141766HARMONY
Solar/Wind Harmer
1.853
316203AE2-005 GEN
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.667
3142416OLDCHRC
Solar/Wind Harmer
0.554
3151171GRAVELC
Adder
0.787
957191AF2-013 GEN
50/50
65.704
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.079
3141843SHACKLE
50/50
0.041
3150621CHESTS7
50/50
0.184
316156AD2-030 GEN
Solar/Wind Harmer
0.107
315976AC1-164 GENA
Solar/Wind Harmer
0.84
316169AC1-164_GENC
Solar/Wind Harmer
0.726
3142946ENON
Solar/Wind Harmer
0.007
316312AB1-027
Solar/Wind Harmer
0.102
CPLELTFEXP_CPLE->PJM
CLTF
1.988
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.795
LAGNLTFEXP_LAGN->PJM
CLTF
1.468
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.366
TVALTFEXP_TVA->PJM
CLTF
0.742
NYPJM->LTFIMP_NY
CLTF
0.569
LGEELTFEXP_LGEE->PJM
CLTF
0.269
WECLTFEXP_WEC->PJM
CLTF
0.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.602
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.549
MECLTFEXP_MEC->PJM
CLTF
0.719
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56722_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1   /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: WT576_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P2-2: ELMONT B1_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 574T575_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 1                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 568_SRT-S'
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1                /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H1T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: 568T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1                /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
314131 to 314175 ckt 1
314132 to 314163 ckt 1
314175 to 314132 ckt 1
314163 to 314137 ckt 1
314182 to 314183 ckt 1
314183 to 314190 ckt 1
314190 to 314139 ckt 1
314902 to 314914 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314914 to 314918 ckt 1
314918 to 314934 ckt 1
314934 to 314916 ckt 1
314924 to 314903 ckt 1
944490 to 313810 ckt 1
957190 to 314131 ckt 1

Winter Peak Analysis

The New Service Request AH1-716 was evaluated as a 650.0 MW (650.0 MW Capacity) injection in the Dominion area.

AH1-716 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 650.0 MW (650.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

(No impacts were found for this analysis)

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

(No flowgates were eliminated after considering the topology reinforcements required by the cycle.)

Light Load Analysis

The New Service Request AH1-716 was evaluated as a 650.0 MW injection and 650.0 MW withdrawal in the Dominion area.

AH1-716 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 650.0 MW (650.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

The following flowgates remain after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC100.62 %1180.0B1187.27
61.84
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
BreakerAC100.62 %1180.0B1187.27
61.84
IPDAEP
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
DVP_P4-2: 56602_SRT-A
BreakerAC100.61 %1180.0B1187.16
61.84

Details for [AH1-716] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.62 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1187.27
MW Contribution:
61.84
IPD Plant:AH1-716
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
PJM_IPD_CHARGING
Charging
61.843

Details for [AH1-716] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.62 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1187.27
MW Contribution:
61.84
IPD Plant:AH1-716
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
PJM_IPD_CHARGING
Charging
61.843

Details for [AH1-716] 05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line l/o DVP_P4-2: 56602_SRT-A


This cycle required topology changing upgrades. After applying these topology changing upgrades to the study case, this flowgate was a Addition to the base run which does not include the topology changing upgrades.

Topology Case Flowgate

Area:AEP
Facility Description:
05CLOVRD_RJO-05JOSHUA 765.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56602_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.61 %
Rating:1180.0 MVA
Rating Type:B
MVA to Mitigate:1187.16
MW Contribution:
61.84
IPD Plant:AH1-716
Impact of Topology Modeling:
Addition
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
PJM_IPD_CHARGING
Charging
61.844
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P4_#7422_05CLOVRD 500_EE2_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P4-2: 56602_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1   /*6LEXNGT2     230.0 - 8LEXNGTN     500.0
END
290614 to 242515 ckt 1

The following flowgates were eliminated after considering the topology reinforcements required by the cycle.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-L
SingleAC104.4 %673.04B702.63
33.13
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-L
SingleAC104.33 %673.04B702.17
33.13
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-L
BreakerAC105.16 %4628.0C4866.67
70.47

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.4 %
Rating:673.04 MVA
Rating Type:B
MVA to Mitigate:702.63
MW Contribution:
33.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3141906WESTMOR
Solar/Wind Harmer
0.424
3142433PROV 92
Solar/Wind Harmer
1.069
3142433PROV 92
50/50
0.214
3142433PROV 92
50/50
0.214
3142433PROV 92
50/50
0.214
3142433PROV 92
50/50
0.214
3142433PROV 92
50/50
0.214
3142433PROV 92
50/50
0.214
3150331BIRCHWDA
50/50
158.638
3150921YORKTN3
50/50
1.955
3138133OCRAN
Solar/Wind Harmer
0.264
3138133OCRAN
Solar/Wind Harmer
0.132
3138283WHITEMARSH
Solar/Wind Harmer
0.015
3141766HARMONY
Solar/Wind Harmer
1.068
3141766HARMONY
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.282
3141783LANCAST
Solar/Wind Harmer
0.188
3141813NORNECK
Solar/Wind Harmer
0.719
3141913WHIT STONE
Solar/Wind Harmer
0.428
3143873LANEXA
Solar/Wind Harmer
0.19
3141726DUNNSVL
Solar/Wind Harmer
2.686
3141873WAN 176
Solar/Wind Harmer
1.506
3141873WAN 176
Solar/Wind Harmer
0.075
316404AE1-155 C
Solar/Wind Harmer
0
316203AE2-005 GEN
Solar/Wind Harmer
0
315749AE2-041 GEN
50/50
4.913
315759AF1-018 GEN
50/50
4.913
316337AD2-073 GEN
Solar/Wind Harmer
0
3138126ROCKLANDING
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.055
3142946ENON
Solar/Wind Harmer
0.016
944491AF1-114 GEN
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
8.672
944591AF1-124 GEN
Solar/Wind Harmer
34.983
962861AG1-135 GEN
Solar/Wind Harmer
7.255
966661AG1-536 GEN
50/50
16.02
971317AH1-138 GEN
Solar/Wind Harmer
0.856
957191AF2-013 GEN
50/50
65.808
958261AF2-120 GEN
Solar/Wind Harmer
7.681
971777AH1-397 GEN
Solar/Wind Harmer
1.383
972135AH1-637 GEN
Solar/Wind Harmer
4.245
972263AH1-716 GEN
50/50
33.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.134
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.336
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.591
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.443
NYPJM->LTFIMP_NY
CLTF
0.553
LGEELTFEXP_LGEE->PJM
CLTF
0.086
WECLTFEXP_WEC->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
1.696
TVALTFEXP_TVA->PJM
CLTF
0.487
MECLTFEXP_MEC->PJM
CLTF
0.3
LAGNLTFEXP_LAGN->PJM
CLTF
0.935
SIGELTFEXP_SIGE->PJM
CLTF
0.009
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.989

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.33 %
Rating:673.04 MVA
Rating Type:B
MVA to Mitigate:702.17
MW Contribution:
33.13
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
3141906WESTMOR
Solar/Wind Harmer
0.424
3142433PROV 92
Solar/Wind Harmer
1.069
3142433PROV 92
50/50
0.214
3142433PROV 92
50/50
0.214
3142433PROV 92
50/50
0.214
3142433PROV 92
50/50
0.214
3142433PROV 92
50/50
0.214
3142433PROV 92
50/50
0.214
3150331BIRCHWDA
50/50
158.638
3150921YORKTN3
50/50
1.955
3138133OCRAN
Solar/Wind Harmer
0.264
3138133OCRAN
Solar/Wind Harmer
0.132
3138283WHITEMARSH
Solar/Wind Harmer
0.015
3141766HARMONY
Solar/Wind Harmer
1.068
3141766HARMONY
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.282
3141783LANCAST
Solar/Wind Harmer
0.188
3141813NORNECK
Solar/Wind Harmer
0.719
3141913WHIT STONE
Solar/Wind Harmer
0.428
3143873LANEXA
Solar/Wind Harmer
0.19
3141726DUNNSVL
Solar/Wind Harmer
2.686
3141873WAN 176
Solar/Wind Harmer
1.506
3141873WAN 176
Solar/Wind Harmer
0.075
316404AE1-155 C
Solar/Wind Harmer
0
316203AE2-005 GEN
Solar/Wind Harmer
0
315749AE2-041 GEN
50/50
4.913
315759AF1-018 GEN
50/50
4.913
316337AD2-073 GEN
Solar/Wind Harmer
0
3138126ROCKLANDING
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.055
3142946ENON
Solar/Wind Harmer
0.016
944491AF1-114 GEN
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
8.672
944591AF1-124 GEN
Solar/Wind Harmer
34.983
962861AG1-135 GEN
Solar/Wind Harmer
7.255
966661AG1-536 GEN
50/50
16.02
971317AH1-138 GEN
Solar/Wind Harmer
0.856
957191AF2-013 GEN
50/50
65.808
958261AF2-120 GEN
Solar/Wind Harmer
7.681
971777AH1-397 GEN
Solar/Wind Harmer
1.383
972135AH1-637 GEN
Solar/Wind Harmer
4.245
972263AH1-716 GEN
50/50
33.134
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.134
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.336
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.591
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.443
NYPJM->LTFIMP_NY
CLTF
0.553
LGEELTFEXP_LGEE->PJM
CLTF
0.086
WECLTFEXP_WEC->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
1.696
TVALTFEXP_TVA->PJM
CLTF
0.487
MECLTFEXP_MEC->PJM
CLTF
0.3
LAGNLTFEXP_LAGN->PJM
CLTF
0.935
SIGELTFEXP_SIGE->PJM
CLTF
0.009
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.989

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-L


This cycle required topology changing upgrades. This base run flowgate was eliminated as a result of the topology changing upgrades.

Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-L
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.16 %
Rating:4628.0 MVA
Rating Type:C
MVA to Mitigate:4866.67
MW Contribution:
70.47
Impact of Topology Modeling:
Elimination
Bus #Bus NameTypeMW Contribution
20390526W1-045 C
Solar/Wind Helper
0.458
23546401DTGZ2-030
Solar/Wind Helper
0.319
20634528N27_Y2-018
Solar/Wind Helper
0.062
20641628MLH_W1-032
Solar/Wind Helper
0.09
20671828STAW2-080
Solar/Wind Helper
0.06
20671928W4-073
Solar/Wind Helper
0.236
20673628F1S_V4-069
Solar/Wind Helper
0.09
20673728F2S_V4-070
Solar/Wind Helper
0.09
20673828FLE_V3-070
Solar/Wind Helper
0.239
20674128FR_U2-059
Solar/Wind Helper
0.065
20674328GAR_V4-001
Solar/Wind Helper
0.059
20674528F3S_W2-016
Solar/Wind Helper
0.448
20674628WNG_W3-110
Solar/Wind Helper
0.222
20674828DL_W4-046
Solar/Wind Helper
0.255
20675128HRM_W1-127
Solar/Wind Helper
0.089
20675428EAM_W2-061
Solar/Wind Helper
0.083
20675528CPH_W2-050
Solar/Wind Helper
0.3
20675728RH_W2-091
Solar/Wind Helper
0.296
20675828AU_W4-064
Solar/Wind Helper
0.089
20675928HOL_W4-097
Solar/Wind Helper
0.089
20676128MHD_W3-029
Solar/Wind Helper
0.251
20676228FRD_X1-012
Solar/Wind Helper
0.296
20676328BVR_Y1-020
Solar/Wind Helper
0.147
20676428JCR_X2-075
Solar/Wind Helper
0.179
20676728BRNX1-095
Solar/Wind Helper
0.089
20714428HOW_X1-037
Solar/Wind Helper
0.444
20714528FRN_Y2-051
Solar/Wind Helper
0.151
20714828MDF_W3-079
Solar/Wind Helper
0.211
20714928UPF_X1-085
Solar/Wind Helper
0.151
20715028HAN_X4-015
Solar/Wind Helper
0.151
20715228NPK_W1-113
Solar/Wind Helper
0.217
20715728PEM_W1-119
Solar/Wind Helper
0.266
20715828PEM_W1-120
Solar/Wind Helper
0.266
20716028EGP_W2-019
Solar/Wind Helper
0.182
20716228APLW2-078
Solar/Wind Helper
0.295
20716428NHV_W2-082
Solar/Wind Helper
0.514
20716928W4-060COL
Solar/Wind Helper
0.3
20717128DIX_Z2-102
Solar/Wind Helper
0.393
20720428HOL_W1-112
Solar/Wind Helper
0.12
20720528MAN_W1-024
Solar/Wind Helper
0.114
20720628TIN_W1-124
Solar/Wind Helper
0.508
20720728JCB_W1-129
Solar/Wind Helper
0.151
20720828JCB_W4-025
Solar/Wind Helper
0.212
207408W3-077 C
Solar/Wind Helper
0.26
207439AE1-081 C O1
Solar/Wind Helper
0.037
214067T20SOLAR
Solar/Wind Helper
0.1
217206BARNGR HS C
Solar/Wind Helper
0.016
217208PARK ELE C
Solar/Wind Helper
0.013
217209CENTRL HS C
Solar/Wind Helper
0.023
217211CAMDEN ST C
Solar/Wind Helper
0.013
217213AMBOY SO C
Solar/Wind Helper
0.069
232404W1-003 C
Solar/Wind Helper
0.686
232408W1-005 C
Solar/Wind Helper
0.686
232410W1-006 C
Solar/Wind Helper
0.686
232417X3-008 C
Solar/Wind Helper
0.62
232426Y1-080 FULL
Solar/Wind Helper
0.105
232428Y3-058 C
Solar/Wind Helper
0.514
23777801MSM_W1-116
Solar/Wind Helper
0.522
23777901MDS_W4-102
Solar/Wind Helper
0.723
3142416OLDCHRC
Solar/Wind Harmer
2.931
3142416OLDCHRC
Solar/Wind Harmer
2.241
3142416OLDCHRC
Solar/Wind Harmer
0.859
3143316POE
Solar/Wind Harmer
3.363
209027LOR2_Q27
Solar/Wind Helper
2.145
212266LOR1
Solar/Wind Helper
0.586
217081WEATEXAS C
Solar/Wind Helper
0.042
217169METRODIV C
Solar/Wind Helper
0.018
217197RE CRAN C
Solar/Wind Helper
0.15
217201HACKENSOLA C
Solar/Wind Helper
0.03
217202FBANKSOLAR C
Solar/Wind Helper
0.03
218428ETC SOLAR C
Solar/Wind Helper
0.017
218438BLK ROCK C
Solar/Wind Helper
0.071
218440SUMMTASSOC C
Solar/Wind Helper
0.06
218449LINSOLAR C
Solar/Wind Helper
0.259
218660EHAMPSOLAR C
Solar/Wind Helper
0.088
219114HARTZY_C
Solar/Wind Helper
0.242
219137THOSOLAR C
Solar/Wind Helper
0.265
219236SOUTHERNHQ C
Solar/Wind Helper
0.028
219249CENTRALDIV C
Solar/Wind Helper
0.022
219272CLEANLIGHT C
Solar/Wind Helper
0.085
219276PARKLANDSO C
Solar/Wind Helper
0.236
219287REEVESEAST C
Solar/Wind Helper
0.335
219291REEVESSOUT C
Solar/Wind Helper
0.03
219348LDSOLAR C
Solar/Wind Helper
0.304
219607WPEMNERT C
Solar/Wind Helper
0.213
219610FLORENCE C
Solar/Wind Helper
0.456
219612MATRIX C
Solar/Wind Helper
0.086
219615MILLCREEK C
Solar/Wind Helper
0.106
219620RIDERU C
Solar/Wind Helper
0.021
219766PARADISE C
Solar/Wind Helper
0.155
219817TRENTONSOL C
Solar/Wind Helper
0.261
227927V4-067C
Solar/Wind Helper
0.079
228260V4-054C
Solar/Wind Helper
0.306
228711V2-041C
Solar/Wind Helper
0.135
235020AA1-095 C
Solar/Wind Helper
0.138
228728W1-130C
Solar/Wind Helper
0.281
228729W2-030 C
Solar/Wind Helper
0.293
3143226MDLTHAN
Solar/Wind Harmer
0.909
232406W1-004 FULL
Solar/Wind Helper
0.686
232436AB1-176 C
Solar/Wind Helper
0.124
217194REDH C
Solar/Wind Helper
0.149
316303AF2-085
50/50
6.269
223402AF1-300 C
Solar/Wind Helper
0.564
230415AB2-049 C
Solar/Wind Helper
0.092
20742028HF_AC1-207
Solar/Wind Helper
0.394
207454AA2-184 E
Solar/Wind Helper
0.602
207459AE1-142 C O1
Solar/Wind Helper
0.604
207471AF2-354 C
Solar/Wind Helper
0.326
208835TUHI V3-051
Solar/Wind Helper
0.038
208835TUHI V3-051
Solar/Wind Helper
0.038
208923BUSO V4-027
Solar/Wind Helper
0.179
232424Y1-079 C
Solar/Wind Helper
0.31
218524CNTRALGAS1 C
Solar/Wind Helper
0.26
218526CNTRALGAS2 C
Solar/Wind Helper
0.26
226910AB2-157 C
Solar/Wind Helper
0.092
233901CHERRYDALE C
Solar/Wind Helper
0.619
233940AF2-379 C
Solar/Wind Helper
0.121
212507AE2-042_GEN
Solar/Wind Helper
2.042
219727YARDVSOLFA C
Solar/Wind Helper
0.262
219907AC1-030 C
Solar/Wind Helper
0.076
237025AB1-124 C
Solar/Wind Helper
0.741
237030AB1-096 C
Solar/Wind Helper
0.303
237034AC2-136 C
Solar/Wind Helper
0.392
237038AE2-054 C
Solar/Wind Helper
0.637
3143526WINTERP
Solar/Wind Harmer
4.656
3143526WINTERP
Solar/Wind Harmer
4.656
316411AF1-147_GEN1
Solar/Wind Helper
2.056
316415AF1-147_GEN2
Solar/Wind Helper
2.056
316033AB2-134 GEN
Solar/Wind Harmer
0
228754AB1-001 C
Solar/Wind Helper
0.07
228351V2-046C
Solar/Wind Helper
0.608
235062AE1-101 C1
Solar/Wind Helper
2.375
205956AE1-196_GEN
Solar/Wind Helper
0.686
217204WCALDSOLAR C
Solar/Wind Helper
0.03
3142543TWELFTH
Solar/Wind Harmer
0.083
237080AD1-060 GEN
Solar/Wind Helper
0.482
235067AD1-061 GEN
Solar/Wind Helper
0.636
237001AB1-127_GEN
Solar/Wind Helper
0.64
237002AB1-128_GEN
Solar/Wind Helper
0.639
238175AF1-290_GEN
Solar/Wind Helper
2.52
238221AF1-254 C O1
Solar/Wind Helper
0.647
238169AE2-226 GEN1
Solar/Wind Helper
1.522
238170AE2-226 GEN2
Solar/Wind Helper
1.522
237085AD2-009_GEN
Solar/Wind Helper
2.203
233944AB2-135 GEN
Solar/Wind Helper
2.196
233946AB2-136 GEN
Solar/Wind Helper
1.753
233994AC2-023 GEN
Solar/Wind Helper
1.571
316312AB1-027
Solar/Wind Harmer
-0.126
315651AD1-115 GEN
Solar/Wind Helper
5.022
237061AD1-155 GEN
Solar/Wind Helper
2.251
237006AB1-125 GEN
Solar/Wind Helper
0.556
23779801AA1-109
Solar/Wind Helper
0.336
233982AB2-133 GEN
Solar/Wind Helper
1.915
233915AB1-141 GEN
Solar/Wind Helper
0.679
233918AB1-142 GEN
Solar/Wind Helper
0.679
315671AE2-027_GEN
Solar/Wind Harmer
0
233930AB2-032 GEN
Solar/Wind Helper
0.62
233987AB2-037 GEN
Solar/Wind Helper
6.26
315813AE1-149 C
Solar/Wind Harmer
16.907
315697AD1-025 GEN
Solar/Wind Harmer
0
233933AB2-153 GEN
Solar/Wind Helper
0.62
233955AB2-172 GEN
Solar/Wind Helper
1.715
315773AC2-141 GEN
Solar/Wind Harmer
0
233935AB2-179 C
Solar/Wind Helper
1.716
316447AC1-158 HLD
Solar/Wind Helper
16.928
316044AC1-158 PL1
Solar/Wind Helper
7.694
316045AC1-158 PL2
Solar/Wind Helper
24.623
316450AC1-158 RIC
Solar/Wind Helper
2.052
315778AD1-151 GEN
Solar/Wind Harmer
25.468
234015AF2-250 C
Solar/Wind Helper
0.067
234036AF2-325 C
Solar/Wind Helper
0.206
207484AF2-139 C O1
Solar/Wind Helper
0.26
207510AF2-138 C
Solar/Wind Helper
0.65
207518AF1-320_GEN
Solar/Wind Helper
2.291
207442AE1-156 GEN
Solar/Wind Helper
0.526
226929AD2-058 GEN
Solar/Wind Helper
0.207
207437AD2-070 GEN
Solar/Wind Helper
0.222
209054AE2-059 GEN
Solar/Wind Helper
0.628
207445AB1-138_GEN
Solar/Wind Helper
0.29
209071AE2-133 GEN
Solar/Wind Helper
0.627
209116AE2-175 GEN
Solar/Wind Helper
2.594
233923SMA
Solar/Wind Helper
2.01
230433AD2-135 GEN
Solar/Wind Helper
0.049
219680HOPEWELLV C1
Solar/Wind Helper
0.03
219686LUMSOLAR_N C
Solar/Wind Helper
0.103
219688LUMSOLAR_S C
Solar/Wind Helper
0.103
219908AB1-139 C
Solar/Wind Helper
0.197
219904AC1-010 C
Solar/Wind Helper
0.183
219906AC1-017 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.156
219258KINSLEYDEP C
Solar/Wind Helper
0.176
219304NAMERICA C
Solar/Wind Helper
0.213
219921AF1-264
Solar/Wind Helper
0.091
203975AE1-071-GEN
Solar/Wind Helper
3.281
211065PSPA IPP
Solar/Wind Helper
0.292
211065PSPA IPP
Solar/Wind Helper
0.292
207530AG1-191 GEN
Solar/Wind Helper
0.505
230511AF1-262
Solar/Wind Helper
0.068
205932AD2-116_GEN
Solar/Wind Helper
0.686
205941AD2-115 GEN
Solar/Wind Helper
0.664
205943AE1-185 GEN
Solar/Wind Helper
0.687
205917AD1-020 ES
Solar/Wind Helper
0.496
205916AD1-020 GEN
Solar/Wind Helper
2.308
316006AB2-029 C
Solar/Wind Helper
0.784
316164AC1-076 GEN
Solar/Wind Helper
3.287
316294AC1-161 GEN
Solar/Wind Harmer
-14.993
315975AC1-164 GENB
Solar/Wind Harmer
-0.283
315976AC1-164 GENA
Solar/Wind Harmer
-9.566
316169AC1-164_GENC
Solar/Wind Harmer
-8.264
230434AG1-499 GEN
Solar/Wind Helper
0.338
233964AF2-378 GEN
Solar/Wind Helper
0.077
207511W3-106 GEN
Solar/Wind Helper
0.147
208972BECR K09
Solar/Wind Helper
0.556
209029WAYMART-WD
Solar/Wind Helper
1.372
223401AF1-299 GEN
Solar/Wind Helper
0.564
230407AD2-065 C
Solar/Wind Helper
0.078
232432Z2-076 GEN
Solar/Wind Helper
0.091
232434Z2-077 GEN
Solar/Wind Helper
0.171
233996TM1833_GEN
Solar/Wind Helper
0.548
233997TMININ_4.2
Solar/Wind Helper
0.548
233998TM1NIN_3.36
Solar/Wind Helper
0.548
3142946ENON
Solar/Wind Harmer
0.285
3142946ENON
Solar/Wind Harmer
0.085
944631AF1-128 GEN
50/50
167.753
944641AF1-129 GEN
50/50
168.302
946691AF1-333 GEN
Solar/Wind Helper
0.628
946731AF1-337 GEN
Solar/Wind Helper
0.628
946741AF1-338 GEN
Solar/Wind Helper
0.628
946751AF1-339 GEN
Solar/Wind Helper
0.628
959381AF2-229 GEN
Solar/Wind Helper
0.678
959421AF2-233 GEN
Solar/Wind Helper
0.376
959431AF2-234 GEN
Solar/Wind Helper
0.752
959561AF2-247 GEN
Solar/Wind Helper
0.168
961261AF2-417 GEN
Solar/Wind Helper
0.636
961301AF2-421 GEN
Solar/Wind Helper
0.637
961331AF2-424 GEN
Solar/Wind Helper
0.632
961341AF2-425 GEN
Solar/Wind Helper
0.632
961421AF2-433 GEN
Solar/Wind Helper
0.631
961431AF2-434 GEN
Solar/Wind Helper
0.631
961611AG1-000B GEN
Solar/Wind Harmer
0.183
961611AG1-000B GEN
Solar/Wind Harmer
0.266
963151AG1-164 GEN
Solar/Wind Helper
0.637
963161AG1-165 GEN
Solar/Wind Helper
0.637
970119AG2-088 GEN
50/50
47.017
970133AG2-095 GEN
Solar/Wind Harmer
3.072
970293AG2-193 GEN
Solar/Wind Harmer
3.433
970603AG2-384 GEN
50/50
17.689
971069AG2-661 GEN
Solar/Wind Harmer
14.637
971223AH1-071 GEN
Solar/Wind Harmer
3.636
971281AH1-106 GEN
Solar/Wind Harmer
4.656
971283AH1-107 GEN
Solar/Wind Harmer
4.656
219918AC2-009 C
Solar/Wind Helper
0.01
227287AC2-120 GEN
Solar/Wind Helper
1.012
924131AB2-057 GEN
Solar/Wind Helper
0.332
939411AE1-173 GEN
Solar/Wind Harmer
136.244
940641AE2-051 GEN
Solar/Wind Harmer
25.678
957921AF2-086 GEN
Solar/Wind Helper
0.618
963711AG1-223 GEN
Solar/Wind Helper
0.514
964851AG1-348 GEN
Solar/Wind Helper
0.504
972263AH1-716 GEN
50/50
70.467
970365AG2-240 GEN
Solar/Wind Harmer
3.246
233950AC2-186 GEN
Solar/Wind Helper
0.31
233952AC2-187 GEN
Solar/Wind Helper
0.619
233954AC2-188 GEN
Solar/Wind Helper
0.619
238147AE2-230_GEN1
Solar/Wind Helper
1.032
238148AE2-230_GEN2
Solar/Wind Helper
1.032
238149AF1-291A_GEN
Solar/Wind Helper
0.295
238152AF2-075_GEN
Solar/Wind Helper
1.475
972287SS25-0012
Solar/Wind Harmer
44.57
972291SS25-0013
Solar/Wind Harmer
57.366
972293SS25-0014
50/50
Charging
189.987
232422X3-066 FULL
Solar/Wind Helper
0.186
219919AE1-041 FULL
Solar/Wind Helper
0.018
219912AD2-042 GEN
Solar/Wind Helper
0.402
219914AD2-027 C
Solar/Wind Helper
0.305
235063AE1-101 C2
Solar/Wind Helper
2.375
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
56.648
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.785
NYPJM->LTFIMP_NY
CLTF
5.235
LGEELTFEXP_LGEE->PJM
CLTF
1.705
WECLTFEXP_WEC->PJM
CLTF
0.84
CPLELTFEXP_CPLE->PJM
CLTF
15.623
TVALTFEXP_TVA->PJM
CLTF
5.757
MECLTFEXP_MEC->PJM
CLTF
4.854
LAGNLTFEXP_LAGN->PJM
CLTF
11.056
SIGELTFEXP_SIGE->PJM
CLTF
0.147
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
47.391
CONTINGENCY 'DVP_P1-2: LN 557_SRT-L'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 3300 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3118 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 568T581_SRT-L'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1                /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3559 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3559 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 3377 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3377 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
314132 to 314163 ckt 1
314163 to 314137 ckt 1
314918 to 314934 ckt 1

Short Circuit Analysis

Analysis Complete - No Issues

Based on PJM’s TC2 Phase II Short Circuit Analysis, this project did not contribute >1% fault duty to any previously identified overdutied breakers, nor did it cause any new overdutied breakers.

Please note that in TC2 Phase III, PJM will perform additional analysis including the evaluation of impacts from topology upgrades which may have potential effects on breaker duties not seen in the Phase II analysis.

Stability Analysis

Analysis Complete - No Issues

Executive Summary

New Service Requests (projects) in PJM Transition Cycle 2 Cluster 10 are listed in Table 1 below. This report will cover the dynamic analysis of Cluster 10 projects.

 

Table 1: Transition Cycle 2 Cluster 10 Projects

 

 

 

 

 

 

 

 

Cluster

Project

Fuel Type

Trans. Owner

MFO (MW)

MWE

(MW)

MWC

(MW)

Point of Interconnection

10

AH1-716

Battery

Dominion

650

650

650

Surry – Skiffes Creek 500 kV

 

The purpose of the transient stability analysis is to determine the system impact of the generation facility. This study will determine system improvements, if any, needed to reduce violations in the transient stability analysis caused by the addition of the projects in Cluster 10.

 

The load flow scenario for the analysis was based on the Regional Transmission Expansion Plan (RTEP) 2028 summer peak case, modified to include applicable projects. Cluster 10 projects have been dispatched online at maximum power output with near unity power factor measured at the high-side of the main substation transformer.

 

Cluster 10 projects were tested for compliance with NERC, PJM, Dominion Energy and other applicable criteria. 99 contingencies were studied, each with a 20 second simulation time period. The contingencies studied included:

 

  • Steady-state operation (30 seconds)
  • Three-phase faults with normal clearing time
  • Single-phase bus faults with normal clearing time
  • Single-phase faults with stuck breaker
  • Single-phase faults with loss of multiple-circuit tower line.

 

For all simulations, the projects under study along with the rest of the PJM system were required to maintain synchronism and with all states returning to an acceptable new condition following the disturbance.

 

The results of the analysis were evaluated against the following recovery criteria per PJM’s Regional Transmission Planning Process and Dominion Energy’s transmission planning criteria:

 

  • Cluster 10 projects were able to ride through the faults (except for faults where protective action trips a generator(s)).
  • The system with Cluster 10 projects included is transiently stable and post-contingency oscillations were positively damped with a damping margin of at least 3%.
  • Following fault clearing, all bus voltages recovered to a minimum of 0.7 per unit after 2.5 seconds (except where protective action isolates that bus) and the final voltages are within the steady-state voltage ranges below per Dominion Energy’s transmission planning criteria.
    • P1 Category Contingencies:
      • 0.93 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.93 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.01 to 1.096 p.u. for 500 kV facilities
    • P2, P4, P5, and P7 Category Contingencies:
      • 0.90 to 1.05 p.u. for 230, 115, 69 kV facilities
      • 0.90 to 1.03 p.u. for 138 kV facilities due to legacy switches
      • 1.00 to 1.096 p.u. for 500 kV facilities
  • No transmission element tripped, other than those either directly connected or designed to trip as a consequence of that fault.

No migration was required.

 

The following settings were adjusted to meet the evaluation criteria.  The generator owners should provide their preferred adjustment for the issues described in the summary of results.

 

  • AH1-716:
    • REECA:
      • Vup: set to 1.15 p.u. instead of 1.1 p.u.
  • AF2-013:
    • REPCA:
      • Kp: set to 1 instead of 0
      • Kc: set to 0.04 instead of 0
      • Kpg: set to 1 instead of 0
      • Ddn: set to 25 instead of 0.04
      • Dup: set to 25 instead of 0.04
  • AF2-110: 1.2 p.u. protection pickup time was increased from 0.012 sec to 0.029 sec
  • AD2-085: 1.2 p.u. protection pickup time was increased from 0.017 sec to 0.029 sec
  • AC1-161: 1.4 p.u. protection pickup time was increased from 0 sec to 0.0126 sec. Note the latest as built model was used to ungnet both AC1-161 and AC2-141 queue projects which share a common POI. Both projects are undergoing the PJMs model quality review process. AC2-141’s as built model included a 210 MW MFO instead of the previous 240 MW MFO which was utilized as the modeling submittal considered the 210 MW MFO.

 

Note: PJM will contact the project developer to verify the model tuning recommendation for non TC2 Cycle project.

Reactive Power Analysis

The reactive power capability of AH1-716 met the 0.95 leading and lagging power factor requirement at the high side of the main transformer.

Steady-State Voltage Analysis

Analysis Complete - No Issues

Steady State Voltage Analysis complete, no voltage issues identified.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

(No dependencies were identified)

Affected System - PJM Identified Violations

As part of PJM's analysis, per Tariff Part VII.G.336 & Manual 14H, Section 13, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In accordance with PJM Tariff Part VII, Subpart D, section 310.A and as outlined in PJM Manual 14H, Sections 4.5 and 13, in Phase II of the Cycle, PJM provides the Affected System Operator any updates on the PJM projects that require an Affected Systems Study based on their response at DP1. New Service Requests that require an Affected Systems Study are required to enter into an Affected Systems Study Agreement with the Affected System Operator, as applicable, prior to the close of DP2 or they will be withdrawn from the Cycle.

If the Project Developer already entered into the necessary agreement and the results are available, PJM will supply them in the Phase II SIS report. See below for the status of any required Affected Systems Study. A status of “Pending” means that the study is not yet completed by the Affected System Operator. If your project requires an Affected Systems Study and your results are not provided for Phase II SIS, PJM anticipates providing them in the Phase III SIS per Tariff Part VII.D.312.

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase II System Impact Study analysis results, this project is contingent on and may have cost responsibility for the following System Reinforcements:

AH1-716 System Reinforcements:
TORTEP IDTitleCategoryAllocated Cost ($USD)Facilities Study
Dominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Contingent$0N/A
Dominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Contingent$0N/A
AEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Contingent$0N/A
Dominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Contingent$0N/A
Dominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Contingent$0N/A
Dominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Contingent$0N/A
Dominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationContingent$0N/A
Dominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Contingent$0N/A
Dominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Contingent$0N/A
Dominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Contingent$0N/A
Dominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Contingent$0N/A
Dominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Contingent$0N/A
Dominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Contingent$0N/A
Dominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Contingent$0N/A
Dominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Contingent$0N/A
AEPb4000.251Replace the wave trap and upgrade the relay at Cloverdale 765kV substationContingent$0N/A
AEPb4000.252Replace the wave trap and upgrade the relay at Joshua Falls 765kV substationContingent$0N/A
Dominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Contingent$0N/A
Dominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Contingent$0N/A
Dominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Contingent$0N/A
Dominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Contingent$0N/A
Dominionb4053.10Construct one new 500 kV line terminal position at the proposed Thornburg (formerly Kraken) substation.Contingent$0N/A
Dominionb4053.8Build a new 500 kV line from Elmont-Thornburg (formerly Kraken) (approximately 31 miles).Contingent$0N/A
Dominionb4053.9Construct one new 500 kV line terminal position at the existing Elmont substation.Contingent$0N/A
Dominionb3692Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.Contingent$0N/A
Dominionb4053.21Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.Contingent$0N/A
Dominionb4053.22Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.Contingent$0N/A
Grand Total:$0

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.355
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Description
Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Thornburg (formerly Kraken) to accommodate the new 500kV line from North Anna to Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Description
Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.13
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.13
Title
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.
Description
Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat. Develop two 765 kV line terminal positions and three 500 kV line terminal positions. Install one 765/500 kV transformer, with provisions for a future second transformer.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.14
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.14
Title
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Description
Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.15
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.15
Title
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Description
Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.16
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.16
Title
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Description
Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.28
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.28
Title
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Description
Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-2
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineAEP_P2-2_#1377_05J.FERR 765_1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P2-2: BREMO B1_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 2003-205_SRT-S
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 249-69_SRT-A
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P7-1: LN 208-259_SRT-S
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4000.251
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.251
Title
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Description
Replace the wave trap and upgrade the relay at Cloverdale 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4000.252
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.252
Title
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Description
Replace the wave trap and upgrade the relay at Joshua Falls 765kV substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOSHUA-05CLOVRD_RJO 765.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4047.0 MVA
(All)B4571.0 MVA

System Reinforcement: b4053.3
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.3
Title
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.
Description
Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW. The HVDC link, approximately 185 miles in length, will be fully routed underground between the two new proposed converter stations, one at Heritage and one at Mosby.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.4
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.5
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.5
Title
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Description
Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.12
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.12
Title
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.
Description
Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement. Upgrade existing terminal equipment to 500 kV, 5000A 63 kAIC standards including breaker (XT590), disconnect switches (59078, X74), leads and bus work.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.11
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.11
Title
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Description
Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.
Cost Information
Time Estimate
Jun 01 2030

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-L
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.10
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.10
Title
Construct one new 500 kV line terminal position at the proposed Thornburg (formerly Kraken) substation.
Description
Construct one new 500 kV line terminal position at the proposed Thornburg (formerly Kraken) substation.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.8
Title
Build a new 500 kV line from Elmont-Thornburg (formerly Kraken) (approximately 31 miles).
Description
Build a new 500 kV line from Elmont-Thornburg (formerly Kraken) (approximately 31 miles). The new line will be constructed primarily of double-circuit 500 kV/230 kV monopole structures. The proposed route follows existing 230 kV line No. 2032 from Elmont-Hanover-Four Rivers and 230 kV line No. 256 from Four Rivers-Kings Dominion-St Johns-Thornburg (formerly Kraken).
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b4053.9
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.9
Title
Construct one new 500 kV line terminal position at the existing Elmont substation.
Description
Construct one new 500 kV line terminal position at the existing Elmont substation.
Cost Information
Time Estimate
Jun 01 2032

ContingentTopology Changing

Note 1: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

Note 2: This topology changing reinforcement was developed by the transmission owner and modeled in PJM analysis to address cycle overload(s). A flowgate that this project contributed to was identified as requiring this topology reinforcement.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
No new ratings for this Flowgate.
6FREDBRG-6FINES 230.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
No new ratings for this Flowgate.
6OAKGROV-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
No new ratings for this Flowgate.

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
TBD

Contingent

Note: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A4330.0 MVA
(All)B4330.0 MVA
(All)C5011.0 MVA

System Reinforcement: b4053.21
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.21
Title
Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.
Description
Uprate 500 kV line No. 567 associated terminal equipment at Chickahominy to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3322.0 MVA
(All)B3425.0 MVA
(All)C3939.0 MVA
WINA4191.0 MVA
WINB4376.0 MVA
WINC5032.0 MVA

System Reinforcement: b4053.22
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4053.22
Title
Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.
Description
Uprate 500 kV line No. 567 associated terminal equipment at Surry to 5000A standards.
Cost Information
Time Estimate
Jun 01 2032

Contingent

Note: Although AH1-716 may not presently have cost responsibility for this upgrade, AH1-716 may need this upgrade in-service to be deliverable to the PJM system. If AH1-716 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Rating SetRating TypeRating Value
(All)A3322.0 MVA
(All)B3425.0 MVA
(All)C3939.0 MVA
WINA4191.0 MVA
WINB4376.0 MVA
WINC5032.0 MVA

Conversion from Impacts into Topology or Eliminated Reinforcements into Region Topology Contingent Reinforcements for AH1-716


AH1-716 Contributions into Topology or Eliminated Reinforcements:
TypeTORTEP ID / TO IDTitleTopo or ElimMW ImpactPercent AllocationCategoryAllocated Cost ($USD)
Load FlowDominionb4000.357Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4000.356Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).Topology-0.0%Contingent$0
Load FlowAEPb4000.355Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).Topology-0.0%Contingent$0
Load FlowDominionb4000.352Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating new Line #568 Thornburg (formerly Kraken) to Possum Point.Topology-0.0%Contingent$0
Load FlowDominionb4000.351Cut in Line #568 Ladysmith - Possum Point into Thornburg (formerly Kraken), creating Line #9517 Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.350Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.349Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Thornburg (formerly Kraken).Topology-0.0%Contingent$0
Load FlowDominionb4000.348Build a new 500/230kV substation called Thornburg (formerly Kraken). The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.Topology-0.0%Contingent$0
Load FlowDominionb4000.346Cut-in 500kV line from Thornburg (formerly Kraken) substation into Yeat substationTopology-0.0%Contingent$0
Load FlowDominionb4000.345Build a 500kV line from a new substation called Thornburg (formerly Kraken) to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4000.344Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Thornburg (formerly Kraken). New conductor to have a minimum summer normal rating of 4357MVA.Topology-0.0%Contingent$0
Load FlowDominionb4053.13Construct a new 765/500 kV Vontay switching station at the crossing of 500 kV line No. 553 Cunningham-Elmont and 765 kV line Joshua Falls-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.14Loop 500 kV line No. 553 into the new Vontay substation, which will result in two 500 kV lines: Cunningham-Vontay and Vontay-Elmont.Topology-0.0%Contingent$0
Load FlowDominionb4053.15Loop 500 kV line No. 576 into the new Vontay substation, which will result in two 500 kV lines: from North Anna-Vontay and Vontay-Midlothian.Topology-0.0%Contingent$0
Load FlowDominionb4053.16Loop 765 kV Joshua Falls-Yeat into the new Vontay substation, which will result in two 765 kV lines: from Joshua Falls-Vontay and Vontay-Yeat.Topology-0.0%Contingent$0
Load FlowDominionb4053.28Replace 500 kV circuit breakers (54265 and 553T564) and all associated equipment to line No. 553 including switches and CT with 5000A equipment at Cunningham substation.Topology-0.0%Contingent$0
Load FlowDominionb4000.342Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.Topology-0.0%Contingent$0
Load FlowDominionb4000.341Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.Topology-0.0%Contingent$0
Load FlowDominionb4053.3Construct a new bipolar +/- 525 kV HVDC link connecting Heritage and Mosby substations, where the link has a capability of transmitting 3,000 MW.Topology-0.0%Contingent$0
Load FlowDominionb4053.4Design and construct a new Voltage Source Converter (VSC) HVDC station at Heritage substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.5Design and construct a new Voltage Source Converter (VSC) HVDC station at Mosby substation to support the new HVDC link.Topology-0.0%Contingent$0
Load FlowDominionb4053.12Install two 500 kV breakers and all associated terminal equipment in the available bay adjacent to existing breaker XT590 to achieve a redundant breaker arrangement.Topology-0.0%Contingent$0
Load FlowDominionb4053.11Cut and loop line No. 5008 into Mosby substation, which will result in two 500 kV lines: line No. 5008 Morrisville-Mosby and line No. 9573 Mosby-Wishing Star.Topology-0.0%Contingent$0
Load FlowDominionb4053.10Construct one new 500 kV line terminal position at the proposed Thornburg (formerly Kraken) substation.Topology-0.0%Contingent$0
Load FlowDominionb4053.8Build a new 500 kV line from Elmont-Thornburg (formerly Kraken) (approximately 31 miles).Topology-0.0%Contingent$0
Load FlowDominionb4053.9Construct one new 500 kV line terminal position at the existing Elmont substation.Topology-0.0%Contingent$0
Contributions into Topology or Eliminated Reinforcement Total:$0
AH1-716 Contingent Region Topology Upgrades:
TORTEP IDTitleCategoryAllocated Cost ($USD)
Region Topology Upgrade Total:$0

Attachments

AH1-716 One Line Diagram

AH1-716 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.