AD2-194 System Impact Study Report
v1.00 released 2023-02-23 12:18
Elwood 345 kV
120.0 MW Capacity / 60.0 MW Energy
Introduction
This System Impact Study Report (SIS) has been prepared in accordance with the PJM Open Access Transmission Tariff, 205, as well as the System Impact Study Agreement between Jackson Generation, LLC, the Interconnection Customer (IC), and PJM Interconnection, LLC (PJM), Transmission Provider (TP). The Interconnected Transmission Owner (ITO) is Commonwealth Edison Company.
Revision 0 – Issued December 2021
Revision 1 – Issued June 2022. The revised report updates the Summer Peak Analysis to include retooled load flow analysis results.
Revision 2 – Issued February 2023. The revised report updates the Transmission Owner scope of work.
Preface
The intent of the System Impact is to determine a plan, with approximate cost and construction time estimates, to connect the subject generation interconnection project to the PJM network at a location specified by the Interconnection Customer. As a requirement for interconnection, the Interconnection Customer may be responsible for the cost of constructing: Network Upgrades, which are facility additions, or upgrades to existing facilities, that are needed to maintain the reliability of the PJM system. All facilities required for interconnection of a generation interconnection project must be designed to meet the technical specifications (on PJM web site) for the appropriate transmission owner.
In some instances an Interconnection Customer may not be responsible for 100% of the identified network upgrade cost because other transmission network uses, e.g. another generation interconnection or merchant transmission upgrade, may also contribute to the need for the same network reinforcement. The possibility of sharing the reinforcement costs with other projects may be identified in the Feasibility Study, but the actual allocation will be deferred until the System Impact Study is performed.
The System Impact study estimates do not include the feasibility, cost, or time required to obtain property rights and permits for construction of the required facilities. The project developer is responsible for the right of way, real estate, and construction permit issues. For properties currently owned by Transmission Owners, the costs may be included in the study.
An Interconnection Customer with a proposed new Customer Facility that has a Maximum Facility Output equal to or greater than 100 MW shall install and maintain, at its expense, phasor measurement units (PMUs). See Section 8.5.3 of Appendix 2 to the Interconnection Service Agreement as well as section 4.3 of PJM Manual 14D for additional information.
General
The Interconnection Customer (IC) has proposed an uprate to a planned/existing generating facility located in Will, Illinois. This project is an increase to the Interconnection Customer's AC1-204 project, which will share the same point of interconnection. The queue position is a 60.0 MW uprate (120.0 MW Capacity uprate) to the previous project. The total installed facilities will have a capability of 1260.9 MW with 120.0 MW of this output being recognized by PJM as Capacity. The proposed in-service date for this uprate project is . This study does not imply a TO commitment to this in-service date.
Project Information | |
Queue Number | AD2-194 |
Project Name | Elwood 345 kV |
Developer Name | Jackson Generation, LLC |
State | Illinois |
County | Will |
Transmission Owner | ComEd |
MFO | 1260.9 MW |
MWE | 60.0 MW |
MWC | 120.0 MW |
Fuel Type | Natural Gas |
Basecase Study Year | 2021 |
Point of Interconnection
AD2-194 will interconnect with on the ComEd transmission system via the 345kV bus at TSS 900 Elwood.
Cost Summary
The project may be responsible for a contribution to the following costs:
| Description | Total Cost |
|---|---|
| Attachment Facilities | $0 |
| Direct Connect Facilities | $0 |
| Non-Direct Connect Facilities | $0 |
| Physical Interconnection | $350,000 |
| System Reinforcements | $19,770,779 |
Note 1: PJM Open Access Transmission Tariff (OATT) section 217.3A outline cost allocation rules. The rules are further clarified in PJM Manual 14A Attachment B. The allocation of costs for a network upgrade will start with the first Queue project to cause the need for the upgrade. Later queue projects will receive cost allocation contingent on their contribution to the violation and are allocated to the queues that have not closed less than 5 years following the execution of the first Interconnection Service Agreement which identifies the need for this upgrade.
Note 2: For customers with System Reinforcements listed: If your present cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as prior queued projects withdrawing from the queue, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to your project. In addition, although your present cost allocation to a System Reinforcement is presently $0, your project may need this system reinforcement completed to be deliverable to the PJM system. If your project comes into service prior to completion of the system reinforcement, an interim deliverability study for your project will be required.
Transmission Owner Scope of Work
The total preliminary cost estimate is given in the table below. These costs do not include CIAC Tax Gross-up.
| RTEP ID | Description | Cost Estimate |
|---|---|---|
| (TBD) | ComEd will need to perform project management, engineering review, drawings and system updates, relay setting changes and testing oversight and coordination to accommodate the AD2-194 interconnection.
|
$350,000 |
Based on the scope of work for the interconnection facilities, it is expected to take a range of 1 to 6 month(s) after the signing of an Interconnection Construction Service Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.
The schedule for any required Network Impact Reinforcements will be more clearly identified in future study phases. The estimated time to complete each of the required reinforcements is identified in the "System Reinforcements" section of the report.
Transmission Owner Analysis
None.
Interconnection Customer Requirements
The Interconnection Customer is responsible for all design and construction related activities on the Interconnection Customer’s side of the Point of Interconnection. ComEd interconnection requirements can be found at https://www.pjm.com/planning/design-engineering/totech-standards/private-comed.aspx
To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.
Revenue Metering and SCADA Requirements
The Interconnection Customer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for IC's generating Resource. See PJM Manuals M-01 and M14D, and PJM Tariff Section 8 of Attachment O.
Summer Peak Analysis
The Queue Project was evaluated as a 60.0 MW (Capacity 120.0 MW) injection in the area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts were as follows:
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution |
|---|---|---|---|---|---|---|---|---|---|---|
| CE |
ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line
270737 to 270769 ckt 1 |
COMED_P2-2_116_GG-345B__4
CONTINGENCY 'COMED_P2-2_116_GG-345B__4' DISCONNECT BUS 270770 /*GOODINGS ;4B 345.0 END |
Bus | AC | 103.96 % | 106.33 % | 1568.0 | STE | 1667.28 | 40.11 |
| CE |
ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line
270736 to 270770 ckt 1 |
COMED_P2-2_116_GG-345R__2
CONTINGENCY 'COMED_P2-2_116_GG-345R__2' DISCONNECT BUS 270769 /*GOODINGS ;2R 345.0 END |
Bus | AC | 102.96 % | 105.27 % | 1568.0 | STE | 1650.71 | 39.12 |
| CE |
ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line
270737 to 270769 ckt 1 |
COMED_P4_116-45-L11613_
CONTINGENCY 'COMED_P4_116-45-L11613_' DISCONNECT BUS 270770 /*GOODINGS ;4B 345.0 TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1 /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1 /*BLUE ISL ;BT 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1 /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0 END |
Breaker | AC | 104.71 % | 107.09 % | 1568.0 | STE | 1679.11 | 40.09 |
| CE |
ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line
270737 to 270769 ckt 1 |
COMED_P4_116-45-TR84___
CONTINGENCY 'COMED_P4_116-45-TR84___' DISCONNECT BUS 270770 /*GOODINGS ;4B 345.0 TRIP BRANCH FROM BUS 270770 TO BUS 271564 TO BUS 275368 CKT 1 /*GOODINGS ;4B 345.0 - GOODINGS ; B 138.0 - GOODINGS ;4C 34.5 END |
Breaker | AC | 103.96 % | 106.33 % | 1568.0 | STE | 1667.28 | 40.11 |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
AEP_P4_#2978_05DUMONT 765
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765' OPEN BRANCH FROM BUS 243206 TO BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 111.69 % | 112.79 % | 1409.0 | B | 1589.21 | 18.11 |
| CE |
ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line
270736 to 270770 ckt 1 |
COMED_P4_116-45-L11614_
CONTINGENCY 'COMED_P4_116-45-L11614_' DISCONNECT BUS 270769 /*GOODINGS ;2R 345.0 TRIP BRANCH FROM BUS 270667 TO BUS 270665 CKT 1 /*BLUE ISL ;RT 345.0 - BLUE ISL ; R 345.0 TRIP BRANCH FROM BUS 270667 TO BUS 270927 CKT 1 /*BLUE ISL ;RT 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 270769 TO BUS 270667 CKT 1 /*GOODINGS ;2R 345.0 - BLUE ISL ;RT 345.0 END |
Breaker | AC | 103.78 % | 106.1 % | 1568.0 | STE | 1663.58 | 39.11 |
| CE |
ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line
270736 to 270770 ckt 1 |
COMED_P4_116-45-TR82___
CONTINGENCY 'COMED_P4_116-45-TR82___' DISCONNECT BUS 270769 /*GOODINGS ;2R 345.0 TRIP BRANCH FROM BUS 270769 TO BUS 271565 TO BUS 275324 CKT 1 /*GOODINGS ;2R 345.0 - GOODINGS ; R 138.0 - GOODINGS ;2C 34.5 END |
Breaker | AC | 102.96 % | 105.27 % | 1568.0 | STE | 1650.71 | 39.12 |
| CE |
ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line
270737 to 270769 ckt 1 |
COMED_P1-2_345-L11620_B-S
CONTINGENCY 'COMED_P1-2_345-L11620_B-S' TRIP BRANCH FROM BUS 270736 TO BUS 270770 CKT 1 /*ELWOOD ; B 345.0 - GOODINGS ;4B 345.0 END |
Single | AC | 107.1 % | 109.69 % | 1568.0 | STE | 1719.93 | 39.27 |
| CE |
ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line
270737 to 270769 ckt 1 |
Base Case | Single | AC | 104.28 % | 106.76 % | 1201.0 | A | 1282.19 | 29.27 |
| CE |
ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line
270736 to 270770 ckt 1 |
COMED_P1-2_345-L11622_R-S
CONTINGENCY 'COMED_P1-2_345-L11622_R-S' TRIP BRANCH FROM BUS 270737 TO BUS 270769 CKT 1 /*ELWOOD ; R 345.0 - GOODINGS ;2R 345.0 END |
Single | AC | 106.26 % | 108.81 % | 1568.0 | STE | 1706.17 | 39.09 |
| CE |
ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line
270736 to 270770 ckt 1 |
Base Case | Single | AC | 102.25 % | 104.68 % | 1201.0 | A | 1257.21 | 28.88 |
Details for ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345B__4
| Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
|---|---|---|---|---|
| 290021 | O50 E | Adder | 16.67 MW | 14.17 MW |
| 935001 | AD1-133 C O1 | Adder | 17.56 MW | 14.92 MW |
| 935002 | AD1-133 E O1 | Adder | 11.7 MW | 9.95 MW |
| 936511 | AD2-066 C O1 | Adder | 5.74 MW | 4.88 MW |
| 936512 | AD2-066 E O1 | Adder | 3.83 MW | 3.25 MW |
| 274729 | ELWOOD EC;1P | 50/50 | 8.97 MW | 8.97 MW |
| 274731 | ELWOOD EC;2P | 50/50 | 8.97 MW | 8.97 MW |
| 274732 | ELWOOD EC;7P | 50/50 | 8.92 MW | 8.92 MW |
| 274733 | ELWOOD EC;3P | 50/50 | 8.97 MW | 8.97 MW |
| 274734 | ELWOOD EC;8P | 50/50 | 8.92 MW | 8.92 MW |
| 274735 | ELWOOD EC;4P | 50/50 | 8.97 MW | 8.97 MW |
| 274736 | ELWOOD EC;9P | 50/50 | 8.92 MW | 8.92 MW |
| 927091 | AC1-204 1 | Adder | 185.93 MW | 158.04 MW |
| 927101 | AC1-204 2 | 50/50 | 187.03 MW | 187.03 MW |
| 934101 | AD2-000 1 | Adder | 6.63 MW | 5.64 MW |
| 934111 | AD2-000 2 | Adder | 7.63 MW | 6.49 MW |
| 930761 | AB1-122 1 | Adder | 82.02 MW | 69.72 MW |
| 930771 | AB1-122 2 | Adder | 94.4 MW | 80.24 MW |
| 937401 | AD2-194 C1 | Adder | 19.99 MW | 17.0 MW |
| 937411 | AD2-194 C2 | 50/50 | 20.11 MW | 20.11 MW |
| CANNELTON | LTFEXP_CANNELTON->LTFIMP_CANNELTON | CLTF | 0.03 MW | 0.03 MW |
| BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.7 MW | 0.7 MW |
| CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 16.26 MW | 16.26 MW |
| CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.26 MW | 0.26 MW |
| CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.91 MW | 12.91 MW |
| WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.74 MW | 1.74 MW |
| O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 4.36 MW | 4.36 MW |
| CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.71 MW | 0.71 MW |
| CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.08 MW | 0.08 MW |
| G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.68 MW | 0.68 MW |
| HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.15 MW | 0.15 MW |
| ELMERSMITH | LTFEXP_ELMERSMITH->LTFIMP_ELMERSMITH | CLTF | 0.05 MW | 0.05 MW |
| MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.33 MW | 13.33 MW |
| CLIFTY | LTFEXP_CLIFTY->LTFIMP_CLIFTY | CLTF | 4.11 MW | 4.11 MW |
| GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.14 MW | 0.14 MW |
| RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.2 MW | 0.2 MW |
Details for ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2
| Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
|---|---|---|---|---|
| 290021 | O50 E | Adder | 14.29 MW | 12.15 MW |
| 935001 | AD1-133 C O1 | Adder | 17.41 MW | 14.8 MW |
| 935002 | AD1-133 E O1 | Adder | 11.61 MW | 9.87 MW |
| 936511 | AD2-066 C O1 | Adder | 5.24 MW | 4.46 MW |
| 936512 | AD2-066 E O1 | Adder | 3.5 MW | 2.97 MW |
| 274728 | ELWOOD EC;5P | 50/50 | 8.76 MW | 8.76 MW |
| 274730 | ELWOOD EC;6P | 50/50 | 8.76 MW | 8.76 MW |
| 274732 | ELWOOD EC;7P | 50/50 | 8.76 MW | 8.76 MW |
| 274733 | ELWOOD EC;3P | 50/50 | 8.7 MW | 8.7 MW |
| 274734 | ELWOOD EC;8P | 50/50 | 8.76 MW | 8.76 MW |
| 274735 | ELWOOD EC;4P | 50/50 | 8.7 MW | 8.7 MW |
| 274736 | ELWOOD EC;9P | 50/50 | 8.76 MW | 8.76 MW |
| 927091 | AC1-204 1 | 50/50 | 182.49 MW | 182.49 MW |
| 927101 | AC1-204 2 | Adder | 181.26 MW | 154.07 MW |
| 934101 | AD2-000 1 | Adder | 6.55 MW | 5.57 MW |
| 934111 | AD2-000 2 | Adder | 6.69 MW | 5.68 MW |
| 930761 | AB1-122 1 | Adder | 80.99 MW | 68.84 MW |
| 930771 | AB1-122 2 | Adder | 82.69 MW | 70.29 MW |
| 937401 | AD2-194 C1 | 50/50 | 19.62 MW | 19.62 MW |
| 937411 | AD2-194 C2 | Adder | 19.49 MW | 16.57 MW |
| CANNELTON | LTFEXP_CANNELTON->LTFIMP_CANNELTON | CLTF | 0.03 MW | 0.03 MW |
| BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.62 MW | 0.62 MW |
| CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.08 MW | 14.08 MW |
| CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.23 MW | 0.23 MW |
| CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 8.35 MW | 8.35 MW |
| WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.12 MW | 1.12 MW |
| O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 3.9 MW | 3.9 MW |
| CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.58 MW | 0.58 MW |
| CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.07 MW | 0.07 MW |
| G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.61 MW | 0.61 MW |
| HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.14 MW | 0.14 MW |
| ELMERSMITH | LTFEXP_ELMERSMITH->LTFIMP_ELMERSMITH | CLTF | 0.04 MW | 0.04 MW |
| MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.77 MW | 10.77 MW |
| CLIFTY | LTFEXP_CLIFTY->LTFIMP_CLIFTY | CLTF | 3.65 MW | 3.65 MW |
| GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.18 MW | 0.18 MW |
Details for ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11613_
| Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
|---|---|---|---|---|
| 290021 | O50 E | Adder | 16.66 MW | 14.16 MW |
| 935001 | AD1-133 C O1 | Adder | 17.59 MW | 14.95 MW |
| 935002 | AD1-133 E O1 | Adder | 11.73 MW | 9.97 MW |
| 936511 | AD2-066 C O1 | Adder | 5.74 MW | 4.88 MW |
| 936512 | AD2-066 E O1 | Adder | 3.82 MW | 3.25 MW |
| 274729 | ELWOOD EC;1P | 50/50 | 8.97 MW | 8.97 MW |
| 274731 | ELWOOD EC;2P | 50/50 | 8.97 MW | 8.97 MW |
| 274732 | ELWOOD EC;7P | 50/50 | 8.92 MW | 8.92 MW |
| 274733 | ELWOOD EC;3P | 50/50 | 8.97 MW | 8.97 MW |
| 274734 | ELWOOD EC;8P | 50/50 | 8.92 MW | 8.92 MW |
| 274735 | ELWOOD EC;4P | 50/50 | 8.97 MW | 8.97 MW |
| 274736 | ELWOOD EC;9P | 50/50 | 8.92 MW | 8.92 MW |
| 927091 | AC1-204 1 | Adder | 185.87 MW | 157.99 MW |
| 927101 | AC1-204 2 | 50/50 | 186.96 MW | 186.96 MW |
| 934101 | AD2-000 1 | Adder | 6.64 MW | 5.64 MW |
| 934111 | AD2-000 2 | Adder | 7.63 MW | 6.48 MW |
| 930761 | AB1-122 1 | Adder | 82.05 MW | 69.74 MW |
| 930771 | AB1-122 2 | Adder | 94.31 MW | 80.17 MW |
| 937401 | AD2-194 C1 | Adder | 19.99 MW | 16.99 MW |
| 937411 | AD2-194 C2 | 50/50 | 20.11 MW | 20.11 MW |
| CANNELTON | LTFEXP_CANNELTON->LTFIMP_CANNELTON | CLTF | 0.03 MW | 0.03 MW |
| BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.69 MW | 0.69 MW |
| CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 16.33 MW | 16.33 MW |
| CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.26 MW | 0.26 MW |
| CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.81 MW | 12.81 MW |
| WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.74 MW | 1.74 MW |
| O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 4.35 MW | 4.35 MW |
| CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.72 MW | 0.72 MW |
| CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.07 MW | 0.07 MW |
| G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.68 MW | 0.68 MW |
| HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.15 MW | 0.15 MW |
| ELMERSMITH | LTFEXP_ELMERSMITH->LTFIMP_ELMERSMITH | CLTF | 0.05 MW | 0.05 MW |
| MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.33 MW | 13.33 MW |
| CLIFTY | LTFEXP_CLIFTY->LTFIMP_CLIFTY | CLTF | 4.1 MW | 4.1 MW |
| GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.14 MW | 0.14 MW |
| RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.2 MW | 0.2 MW |
Details for ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR84___
| Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
|---|---|---|---|---|
| 290021 | O50 E | Adder | 16.67 MW | 14.17 MW |
| 935001 | AD1-133 C O1 | Adder | 17.56 MW | 14.92 MW |
| 935002 | AD1-133 E O1 | Adder | 11.7 MW | 9.95 MW |
| 936511 | AD2-066 C O1 | Adder | 5.74 MW | 4.88 MW |
| 936512 | AD2-066 E O1 | Adder | 3.83 MW | 3.25 MW |
| 274729 | ELWOOD EC;1P | 50/50 | 8.97 MW | 8.97 MW |
| 274731 | ELWOOD EC;2P | 50/50 | 8.97 MW | 8.97 MW |
| 274732 | ELWOOD EC;7P | 50/50 | 8.92 MW | 8.92 MW |
| 274733 | ELWOOD EC;3P | 50/50 | 8.97 MW | 8.97 MW |
| 274734 | ELWOOD EC;8P | 50/50 | 8.92 MW | 8.92 MW |
| 274735 | ELWOOD EC;4P | 50/50 | 8.97 MW | 8.97 MW |
| 274736 | ELWOOD EC;9P | 50/50 | 8.92 MW | 8.92 MW |
| 927091 | AC1-204 1 | Adder | 185.93 MW | 158.04 MW |
| 927101 | AC1-204 2 | 50/50 | 187.03 MW | 187.03 MW |
| 934101 | AD2-000 1 | Adder | 6.63 MW | 5.64 MW |
| 934111 | AD2-000 2 | Adder | 7.63 MW | 6.49 MW |
| 930761 | AB1-122 1 | Adder | 82.02 MW | 69.72 MW |
| 930771 | AB1-122 2 | Adder | 94.4 MW | 80.24 MW |
| 937401 | AD2-194 C1 | Adder | 19.99 MW | 17.0 MW |
| 937411 | AD2-194 C2 | 50/50 | 20.11 MW | 20.11 MW |
| CANNELTON | LTFEXP_CANNELTON->LTFIMP_CANNELTON | CLTF | 0.03 MW | 0.03 MW |
| BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.7 MW | 0.7 MW |
| CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 16.26 MW | 16.26 MW |
| CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.26 MW | 0.26 MW |
| CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 12.91 MW | 12.91 MW |
| WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.74 MW | 1.74 MW |
| O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 4.36 MW | 4.36 MW |
| CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.71 MW | 0.71 MW |
| CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.08 MW | 0.08 MW |
| G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.68 MW | 0.68 MW |
| HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.15 MW | 0.15 MW |
| ELMERSMITH | LTFEXP_ELMERSMITH->LTFIMP_ELMERSMITH | CLTF | 0.05 MW | 0.05 MW |
| MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.33 MW | 13.33 MW |
| CLIFTY | LTFEXP_CLIFTY->LTFIMP_CLIFTY | CLTF | 4.11 MW | 4.11 MW |
| GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.14 MW | 0.14 MW |
| RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.2 MW | 0.2 MW |
Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765
| Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
|---|---|---|---|---|
| 290021 | O50 E | Adder | 22.59 MW | 19.2 MW |
| 290051 | GSG-6; E | Adder | 12.16 MW | 10.34 MW |
| 290108 | LEEDK;1U E | Adder | 28.24 MW | 24.01 MW |
| 295109 | WESTBROOK E | Adder | 6.51 MW | 5.54 MW |
| 295111 | SUBLETTE E | Adder | 3.17 MW | 2.69 MW |
| 910542 | X3-005 E | Adder | 1.01 MW | 0.86 MW |
| 920272 | AA2-123 E | Adder | 3.34 MW | 2.84 MW |
| 926311 | AC1-109 1 | Adder | 2.21 MW | 1.88 MW |
| 926321 | AC1-109 2 | Adder | 2.21 MW | 1.88 MW |
| 926331 | AC1-110 1 | Adder | 2.21 MW | 1.88 MW |
| 926341 | AC1-110 2 | Adder | 2.21 MW | 1.88 MW |
| 926351 | AC1-111 1 | Adder | 0.89 MW | 0.75 MW |
| 926361 | AC1-111 2 | Adder | 0.89 MW | 0.75 MW |
| 926371 | AC1-111 3 | Adder | 0.89 MW | 0.75 MW |
| 926381 | AC1-111 4 | Adder | 0.89 MW | 0.75 MW |
| 926391 | AC1-111 5 | Adder | 0.89 MW | 0.75 MW |
| 926401 | AC1-111 6 | Adder | 0.89 MW | 0.75 MW |
| 926431 | AC1-114 | Adder | 1.39 MW | 1.18 MW |
| 927451 | AC1-142A 1 | Adder | 4.89 MW | 4.16 MW |
| 927461 | AC1-142A 2 | Adder | 4.89 MW | 4.16 MW |
| 927511 | AC1-113 1 | Adder | 0.28 MW | 0.24 MW |
| 933931 | AD1-016 C | Adder | 1.08 MW | 0.92 MW |
| 933932 | AD1-016 E | Adder | 1.76 MW | 1.5 MW |
| 934051 | AD1-031 C O1 | Adder | 3.32 MW | 2.82 MW |
| 934052 | AD1-031 E O1 | Adder | 5.42 MW | 4.61 MW |
| 934431 | AD1-067 C | Adder | 0.15 MW | 0.13 MW |
| 934432 | AD1-067 E | Adder | 0.64 MW | 0.55 MW |
| 934701 | AD1-098 C O1 | Adder | 8.01 MW | 6.81 MW |
| 934702 | AD1-098 E O1 | Adder | 5.85 MW | 4.97 MW |
| 934721 | AD1-100 C | Adder | 22.64 MW | 19.24 MW |
| 934722 | AD1-100 E | Adder | 105.64 MW | 89.8 MW |
| 934971 | AD1-129 C | Adder | 1.05 MW | 0.89 MW |
| 934972 | AD1-129 E | Adder | 0.7 MW | 0.6 MW |
| 935001 | AD1-133 C O1 | Adder | 24.37 MW | 20.71 MW |
| 935002 | AD1-133 E O1 | Adder | 16.25 MW | 13.81 MW |
| 936291 | AD2-038 C O1 | Adder | 3.69 MW | 3.14 MW |
| 936292 | AD2-038 E O1 | Adder | 17.27 MW | 14.68 MW |
| 936371 | AD2-047 C O1 | Adder | 5.47 MW | 4.65 MW |
| 936372 | AD2-047 E O1 | Adder | 26.72 MW | 22.71 MW |
| 936461 | AD2-060 | Adder | 3.22 MW | 2.74 MW |
| 936511 | AD2-066 C O1 | Adder | 9.79 MW | 8.32 MW |
| 936512 | AD2-066 E O1 | Adder | 6.53 MW | 5.55 MW |
| 936791 | AD2-102 C | Adder | 16.5 MW | 14.03 MW |
| 936792 | AD2-102 E | Adder | 11.0 MW | 9.35 MW |
| 937001 | AD2-134 C | Adder | 2.94 MW | 2.5 MW |
| 937002 | AD2-134 E | Adder | 11.76 MW | 10.0 MW |
| 937311 | AD2-172 C | Adder | 2.87 MW | 2.44 MW |
| 937312 | AD2-172 E | Adder | 3.96 MW | 3.37 MW |
| 937531 | AD2-214 C | Adder | 5.16 MW | 4.39 MW |
| 937532 | AD2-214 E | Adder | 3.44 MW | 2.93 MW |
| 274789 | SE CHICAG;6U | 50/50 | 1.34 MW | 1.34 MW |
| 274790 | SE CHICAG;7U | 50/50 | 1.34 MW | 1.34 MW |
| 274791 | SE CHICAG;8U | 50/50 | 1.34 MW | 1.34 MW |
| 274849 | CRESCENT ;1U | Adder | 5.64 MW | 4.79 MW |
| 274850 | MENDOTA H;RU | Adder | 6.28 MW | 5.33 MW |
| 274859 | EASYR;U1 E | Adder | 12.83 MW | 10.91 MW |
| 274860 | EASYR;U2 E | Adder | 12.83 MW | 10.91 MW |
| 293061 | N-015 E | Adder | 17.74 MW | 15.08 MW |
| 293516 | O-009 E1 | Adder | 10.64 MW | 9.04 MW |
| 293517 | O-009 E2 | Adder | 5.4 MW | 4.59 MW |
| 293518 | O-009 E3 | Adder | 5.95 MW | 5.06 MW |
| 293644 | O22 E1 | Adder | 12.1 MW | 10.29 MW |
| 293645 | O22 E2 | Adder | 23.49 MW | 19.97 MW |
| 293715 | O-029 E | Adder | 8.13 MW | 6.91 MW |
| 293716 | O-029 E | Adder | 6.24 MW | 5.3 MW |
| 293717 | O-029 E | Adder | 5.73 MW | 4.87 MW |
| 293771 | O-035 E | Adder | 7.46 MW | 6.34 MW |
| 294392 | P-010 E | Adder | 22.52 MW | 19.15 MW |
| 294401 | BSHIL;1U E | Adder | 9.99 MW | 8.49 MW |
| 294410 | BSHIL;2U E | Adder | 9.99 MW | 8.49 MW |
| 294763 | P-046 E | Adder | 10.94 MW | 9.3 MW |
| 915011 | Y3-013 1 | Adder | 4.37 MW | 3.71 MW |
| 915021 | Y3-013 2 | Adder | 4.37 MW | 3.71 MW |
| 915031 | Y3-013 3 | Adder | 4.37 MW | 3.71 MW |
| 917502 | Z2-087 E | Adder | 21.53 MW | 18.3 MW |
| 925581 | AC1-033 C | Adder | 1.64 MW | 1.39 MW |
| 925582 | AC1-033 E | Adder | 10.95 MW | 9.31 MW |
| 932881 | AC2-115 1 | Adder | 2.77 MW | 2.36 MW |
| 932891 | AC2-115 2 | Adder | 2.77 MW | 2.36 MW |
| 932921 | AC2-116 | Adder | 0.97 MW | 0.82 MW |
| 933411 | AC2-154 C | Adder | 3.06 MW | 2.6 MW |
| 933412 | AC2-154 E | Adder | 4.99 MW | 4.24 MW |
| 990901 | L-005 E | Adder | 14.7 MW | 12.49 MW |
| 274890 | CAYUG;1U E | Adder | 15.98 MW | 13.59 MW |
| 274891 | CAYUG;2U E | Adder | 15.98 MW | 13.59 MW |
| 919581 | AA2-030 | Adder | 20.55 MW | 17.47 MW |
| 930481 | AB1-089 | Adder | 76.61 MW | 65.12 MW |
| 932931 | AC2-117 | Adder | 5.87 MW | 4.99 MW |
| 917501 | Z2-087 C | Adder | 3.22 MW | 2.73 MW |
| 927091 | AC1-204 1 | Adder | 84.21 MW | 71.58 MW |
| 927101 | AC1-204 2 | Adder | 84.18 MW | 71.56 MW |
| 927531 | AC1-185 1 | Adder | 0.8 MW | 0.68 MW |
| 927541 | AC1-185 2 | Adder | 0.8 MW | 0.68 MW |
| 927551 | AC1-185 3 | Adder | 0.8 MW | 0.68 MW |
| 927561 | AC1-185 4 | Adder | 0.8 MW | 0.68 MW |
| 927571 | AC1-185 5 | Adder | 0.8 MW | 0.68 MW |
| 927581 | AC1-185 6 | Adder | 0.8 MW | 0.68 MW |
| 927591 | AC1-185 7 | Adder | 0.8 MW | 0.68 MW |
| 927601 | AC1-185 8 | Adder | 0.8 MW | 0.68 MW |
| 934101 | AD2-000 1 | Adder | 6.74 MW | 5.73 MW |
| 934111 | AD2-000 2 | Adder | 6.95 MW | 5.91 MW |
| 274888 | PILOT HIL;1E | Adder | 22.53 MW | 19.15 MW |
| 275149 | KEMPTON ;1E | Adder | 22.53 MW | 19.15 MW |
| 916502 | Z1-106 E1 | Adder | 1.73 MW | 1.47 MW |
| 916504 | Z1-106 E2 | Adder | 1.73 MW | 1.47 MW |
| 916512 | Z1-107 E | Adder | 3.6 MW | 3.06 MW |
| 916522 | Z1-108 E | Adder | 3.4 MW | 2.89 MW |
| 918052 | AA1-018 E | Adder | 18.94 MW | 16.1 MW |
| 919221 | AA1-146 | Adder | 20.55 MW | 17.47 MW |
| 924041 | AB2-047 C O1 | Adder | 4.02 MW | 3.42 MW |
| 924042 | AB2-047 E O1 | Adder | 26.91 MW | 22.88 MW |
| 925302 | AB2-191 E | Adder | 1.61 MW | 1.37 MW |
| 918051 | AA1-018 C | Adder | 2.83 MW | 2.4 MW |
| 925301 | AB2-191 C | Adder | 1.17 MW | 0.99 MW |
| 299993 | U3-031C | Adder | 6.3 MW | 5.36 MW |
| 926821 | AC1-168 C | Adder | 1.35 MW | 1.15 MW |
| 926822 | AC1-168 E | Adder | 9.05 MW | 7.69 MW |
| 927201 | AC1-214 C | Adder | 2.39 MW | 2.04 MW |
| 927202 | AC1-214 E | Adder | 7.61 MW | 6.47 MW |
| 927522 | AC1-113 2 | Adder | 0.28 MW | 0.24 MW |
| 930761 | AB1-122 1 | Adder | 83.4 MW | 70.89 MW |
| 930771 | AB1-122 2 | Adder | 85.94 MW | 73.05 MW |
| 933911 | AD1-013 C O1 | Adder | 2.14 MW | 1.82 MW |
| 933912 | AD1-013 E O1 | Adder | 3.42 MW | 2.91 MW |
| 937401 | AD2-194 C1 | Adder | 9.06 MW | 7.7 MW |
| 937411 | AD2-194 C2 | Adder | 9.05 MW | 7.7 MW |
| 938961 | J847 | External Queue | 13.12 MW | 13.12 MW |
| 940531 | J351 | External Queue | 434.12 MW | 434.12 MW |
| 951131 | J643 | External Queue | 25.78 MW | 25.78 MW |
| CIN | LTFEXP_CIN->LTFIMP_CIN | CLTF | 3.03 MW | 3.03 MW |
| BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.2 MW | 0.2 MW |
| IPL | LTFEXP_IPL->LTFIMP_IPL | CLTF | 1.29 MW | 1.29 MW |
| CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 62.69 MW | 62.69 MW |
| CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.91 MW | 0.91 MW |
| CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 73.51 MW | 73.51 MW |
| WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 9.32 MW | 9.32 MW |
| O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 15.32 MW | 15.32 MW |
| BIG_CAJUN1 | LTFEXP_BIG_CAJUN1->LTFIMP_BIG_CAJUN1 | LTF | 0.0 MW | 0.0 MW |
| ROWAN | LTFEXP_ROWAN->LTFIMP_ROWAN | LTF | 0.0 MW | 0.0 MW |
| CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 4.04 MW | 4.04 MW |
| CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.18 MW | 0.18 MW |
| G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 2.39 MW | 2.39 MW |
| HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.41 MW | 0.41 MW |
| MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 45.43 MW | 45.43 MW |
| CLIFTY | LTFEXP_CLIFTY->LTFIMP_CLIFTY | CLTF | 8.19 MW | 8.19 MW |
| TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.72 MW | 0.72 MW |
Details for ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614_
| Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
|---|---|---|---|---|
| 290021 | O50 E | Adder | 14.28 MW | 12.14 MW |
| 935001 | AD1-133 C O1 | Adder | 17.46 MW | 14.84 MW |
| 935002 | AD1-133 E O1 | Adder | 11.64 MW | 9.89 MW |
| 936511 | AD2-066 C O1 | Adder | 5.24 MW | 4.45 MW |
| 936512 | AD2-066 E O1 | Adder | 3.49 MW | 2.97 MW |
| 274728 | ELWOOD EC;5P | 50/50 | 8.76 MW | 8.76 MW |
| 274730 | ELWOOD EC;6P | 50/50 | 8.76 MW | 8.76 MW |
| 274732 | ELWOOD EC;7P | 50/50 | 8.76 MW | 8.76 MW |
| 274733 | ELWOOD EC;3P | 50/50 | 8.7 MW | 8.7 MW |
| 274734 | ELWOOD EC;8P | 50/50 | 8.76 MW | 8.76 MW |
| 274735 | ELWOOD EC;4P | 50/50 | 8.7 MW | 8.7 MW |
| 274736 | ELWOOD EC;9P | 50/50 | 8.76 MW | 8.76 MW |
| 927091 | AC1-204 1 | 50/50 | 182.46 MW | 182.46 MW |
| 927101 | AC1-204 2 | Adder | 181.22 MW | 154.04 MW |
| 934101 | AD2-000 1 | Adder | 6.55 MW | 5.57 MW |
| 934111 | AD2-000 2 | Adder | 6.68 MW | 5.68 MW |
| 930761 | AB1-122 1 | Adder | 81.05 MW | 68.89 MW |
| 930771 | AB1-122 2 | Adder | 82.62 MW | 70.23 MW |
| 937401 | AD2-194 C1 | 50/50 | 19.62 MW | 19.62 MW |
| 937411 | AD2-194 C2 | Adder | 19.49 MW | 16.57 MW |
| CANNELTON | LTFEXP_CANNELTON->LTFIMP_CANNELTON | CLTF | 0.03 MW | 0.03 MW |
| BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.61 MW | 0.61 MW |
| CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.15 MW | 14.15 MW |
| CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.23 MW | 0.23 MW |
| CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 8.23 MW | 8.23 MW |
| WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.12 MW | 1.12 MW |
| O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 3.9 MW | 3.9 MW |
| CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.59 MW | 0.59 MW |
| CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.07 MW | 0.07 MW |
| G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.61 MW | 0.61 MW |
| HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.14 MW | 0.14 MW |
| ELMERSMITH | LTFEXP_ELMERSMITH->LTFIMP_ELMERSMITH | CLTF | 0.04 MW | 0.04 MW |
| MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.78 MW | 10.78 MW |
| CLIFTY | LTFEXP_CLIFTY->LTFIMP_CLIFTY | CLTF | 3.64 MW | 3.64 MW |
| GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.12 MW | 0.12 MW |
| RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.18 MW | 0.18 MW |
Details for ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82___
| Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
|---|---|---|---|---|
| 290021 | O50 E | Adder | 14.29 MW | 12.15 MW |
| 935001 | AD1-133 C O1 | Adder | 17.41 MW | 14.8 MW |
| 935002 | AD1-133 E O1 | Adder | 11.61 MW | 9.87 MW |
| 936511 | AD2-066 C O1 | Adder | 5.24 MW | 4.46 MW |
| 936512 | AD2-066 E O1 | Adder | 3.5 MW | 2.97 MW |
| 274728 | ELWOOD EC;5P | 50/50 | 8.76 MW | 8.76 MW |
| 274730 | ELWOOD EC;6P | 50/50 | 8.76 MW | 8.76 MW |
| 274732 | ELWOOD EC;7P | 50/50 | 8.76 MW | 8.76 MW |
| 274733 | ELWOOD EC;3P | 50/50 | 8.7 MW | 8.7 MW |
| 274734 | ELWOOD EC;8P | 50/50 | 8.76 MW | 8.76 MW |
| 274735 | ELWOOD EC;4P | 50/50 | 8.7 MW | 8.7 MW |
| 274736 | ELWOOD EC;9P | 50/50 | 8.76 MW | 8.76 MW |
| 927091 | AC1-204 1 | 50/50 | 182.49 MW | 182.49 MW |
| 927101 | AC1-204 2 | Adder | 181.26 MW | 154.07 MW |
| 934101 | AD2-000 1 | Adder | 6.55 MW | 5.57 MW |
| 934111 | AD2-000 2 | Adder | 6.69 MW | 5.68 MW |
| 930761 | AB1-122 1 | Adder | 80.99 MW | 68.84 MW |
| 930771 | AB1-122 2 | Adder | 82.69 MW | 70.29 MW |
| 937401 | AD2-194 C1 | 50/50 | 19.62 MW | 19.62 MW |
| 937411 | AD2-194 C2 | Adder | 19.49 MW | 16.57 MW |
| CANNELTON | LTFEXP_CANNELTON->LTFIMP_CANNELTON | CLTF | 0.03 MW | 0.03 MW |
| BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.62 MW | 0.62 MW |
| CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 14.08 MW | 14.08 MW |
| CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.23 MW | 0.23 MW |
| CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 8.35 MW | 8.35 MW |
| WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.12 MW | 1.12 MW |
| O-066 | LTFEXP_O-066->LTFIMP_O-066 | CLTF | 3.9 MW | 3.9 MW |
| CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.58 MW | 0.58 MW |
| CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.07 MW | 0.07 MW |
| G-007 | LTFEXP_G-007->LTFIMP_G-007 | CLTF | 0.61 MW | 0.61 MW |
| HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.14 MW | 0.14 MW |
| ELMERSMITH | LTFEXP_ELMERSMITH->LTFIMP_ELMERSMITH | CLTF | 0.04 MW | 0.04 MW |
| MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.77 MW | 10.77 MW |
| CLIFTY | LTFEXP_CLIFTY->LTFIMP_CLIFTY | CLTF | 3.65 MW | 3.65 MW |
| GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.18 MW | 0.18 MW |
Details for ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11620_B-S
| Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
|---|---|---|---|---|
| 274837 | EQUISTAR ; B | 80/20 | 0.68 MW | 0.68 MW |
| 274836 | EQUISTAR ; R | 80/20 | 1.27 MW | 1.27 MW |
| 935001 | AD1-133 C O1 | 80/20 | 16.84 MW | 16.84 MW |
| 936511 | AD2-066 C O1 | 80/20 | 5.2 MW | 5.2 MW |
| 274658 | DRESDEN ;2U | 80/20 | 24.8 MW | 24.8 MW |
| 274659 | DRESDEN ;3U | 80/20 | 22.22 MW | 22.22 MW |
| 274704 | KENDALL ;1C | 80/20 | 3.49 MW | 3.49 MW |
| 274705 | KENDALL ;1S | 80/20 | 2.33 MW | 2.33 MW |
| 274706 | KENDALL ;2C | 80/20 | 3.49 MW | 3.49 MW |
| 274707 | KENDALL ;2S | 80/20 | 2.33 MW | 2.33 MW |
| 274728 | ELWOOD EC;5P | 80/20 | 8.74 MW | 8.74 MW |
| 274729 | ELWOOD EC;1P | 80/20 | 8.79 MW | 8.79 MW |
| 274730 | ELWOOD EC;6P | 80/20 | 8.74 MW | 8.74 MW |
| 274731 | ELWOOD EC;2P | 80/20 | 8.79 MW | 8.79 MW |
| 274732 | ELWOOD EC;7P | 80/20 | 8.74 MW | 8.74 MW |
| 274733 | ELWOOD EC;3P | 80/20 | 8.79 MW | 8.79 MW |
| 274734 | ELWOOD EC;8P | 80/20 | 8.74 MW | 8.74 MW |
| 274735 | ELWOOD EC;4P | 80/20 | 8.79 MW | 8.79 MW |
| 274736 | ELWOOD EC;9P | 80/20 | 8.74 MW | 8.74 MW |
| 274879 | MINONK ;1U | 80/20 | 0.64 MW | 0.64 MW |
| 927091 | AC1-204 1 | 80/20 | 182.04 MW | 182.04 MW |
| 927101 | AC1-204 2 | 80/20 | 183.16 MW | 183.16 MW |
| 934101 | AD2-000 1 | 80/20 | 6.35 MW | 6.35 MW |
| 934111 | AD2-000 2 | 80/20 | 7.05 MW | 7.05 MW |
| 905493 | W4-086 | 80/20 | 0.03 MW | 0.03 MW |
| 930761 | AB1-122 1 | 80/20 | 78.49 MW | 78.49 MW |
| 930771 | AB1-122 2 | 80/20 | 87.19 MW | 87.19 MW |
| 937401 | AD2-194 C1 | 80/20 | 19.58 MW | 19.58 MW |
| 937411 | AD2-194 C2 | 80/20 | 19.7 MW | 19.7 MW |
| 918111 | AA1-040 1 | 80/20 | 0.17 MW | 0.17 MW |
| 918121 | AA1-040 2 | 80/20 | 0.14 MW | 0.14 MW |
| CANNELTON | LTFEXP_CANNELTON->LTFIMP_CANNELTON | CLTF | 0.03 MW | 0.03 MW |
| BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.58 MW | 0.58 MW |
| CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 13.06 MW | 13.06 MW |
| CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.22 MW | 0.22 MW |
| CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 8.23 MW | 8.23 MW |
| WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.06 MW | 1.06 MW |
| CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.52 MW | 0.52 MW |
| CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.07 MW | 0.07 MW |
| HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.14 MW | 0.14 MW |
| ELMERSMITH | LTFEXP_ELMERSMITH->LTFIMP_ELMERSMITH | CLTF | 0.04 MW | 0.04 MW |
| MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.09 MW | 10.09 MW |
| CLIFTY | LTFEXP_CLIFTY->LTFIMP_CLIFTY | CLTF | 3.48 MW | 3.48 MW |
| GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.12 MW | 0.12 MW |
| RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.17 MW | 0.17 MW |
Details for ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line l/o Base Case
| Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
|---|---|---|---|---|
| 274837 | EQUISTAR ; B | 80/20 | 0.49 MW | 0.49 MW |
| 274836 | EQUISTAR ; R | 80/20 | 0.95 MW | 0.95 MW |
| 935001 | AD1-133 C O1 | 80/20 | 12.36 MW | 12.36 MW |
| 936511 | AD2-066 C O1 | 80/20 | 3.9 MW | 3.9 MW |
| 274658 | DRESDEN ;2U | 80/20 | 19.02 MW | 19.02 MW |
| 274659 | DRESDEN ;3U | 80/20 | 16.32 MW | 16.32 MW |
| 274704 | KENDALL ;1C | 80/20 | 2.84 MW | 2.84 MW |
| 274705 | KENDALL ;1S | 80/20 | 1.89 MW | 1.89 MW |
| 274706 | KENDALL ;2C | 80/20 | 2.84 MW | 2.84 MW |
| 274707 | KENDALL ;2S | 80/20 | 1.89 MW | 1.89 MW |
| 274728 | ELWOOD EC;5P | 80/20 | 6.49 MW | 6.49 MW |
| 274729 | ELWOOD EC;1P | 80/20 | 6.57 MW | 6.57 MW |
| 274730 | ELWOOD EC;6P | 80/20 | 6.49 MW | 6.49 MW |
| 274731 | ELWOOD EC;2P | 80/20 | 6.57 MW | 6.57 MW |
| 274732 | ELWOOD EC;7P | 80/20 | 6.49 MW | 6.49 MW |
| 274733 | ELWOOD EC;3P | 80/20 | 6.57 MW | 6.57 MW |
| 274734 | ELWOOD EC;8P | 80/20 | 6.49 MW | 6.49 MW |
| 274735 | ELWOOD EC;4P | 80/20 | 6.57 MW | 6.57 MW |
| 274736 | ELWOOD EC;9P | 80/20 | 6.49 MW | 6.49 MW |
| 274879 | MINONK ;1U | 80/20 | 0.49 MW | 0.49 MW |
| 927091 | AC1-204 1 | 80/20 | 135.22 MW | 135.22 MW |
| 927101 | AC1-204 2 | 80/20 | 136.99 MW | 136.99 MW |
| 934101 | AD2-000 1 | 80/20 | 4.66 MW | 4.66 MW |
| 934111 | AD2-000 2 | 80/20 | 5.41 MW | 5.41 MW |
| 918051 | AA1-018 C | Adder | -1.29 MW | -1.1 MW |
| 905493 | W4-086 | 80/20 | 0.02 MW | 0.02 MW |
| 930761 | AB1-122 1 | 80/20 | 57.68 MW | 57.68 MW |
| 930771 | AB1-122 2 | 80/20 | 66.88 MW | 66.88 MW |
| 937401 | AD2-194 C1 | 80/20 | 14.54 MW | 14.54 MW |
| 937411 | AD2-194 C2 | 80/20 | 14.73 MW | 14.73 MW |
| 918111 | AA1-040 1 | 80/20 | 0.13 MW | 0.13 MW |
| 918121 | AA1-040 2 | 80/20 | 0.1 MW | 0.1 MW |
| CANNELTON | LTFEXP_CANNELTON->LTFIMP_CANNELTON | CLTF | 0.02 MW | 0.02 MW |
| BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.43 MW | 0.43 MW |
| CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 9.88 MW | 9.88 MW |
| CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.16 MW | 0.16 MW |
| CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 6.48 MW | 6.48 MW |
| WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.8 MW | 0.8 MW |
| CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.41 MW | 0.41 MW |
| CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.05 MW | 0.05 MW |
| HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.1 MW | 0.1 MW |
| ELMERSMITH | LTFEXP_ELMERSMITH->LTFIMP_ELMERSMITH | CLTF | 0.03 MW | 0.03 MW |
| MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.64 MW | 7.64 MW |
| CLIFTY | LTFEXP_CLIFTY->LTFIMP_CLIFTY | CLTF | 2.57 MW | 2.57 MW |
| GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.09 MW | 0.09 MW |
| RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.13 MW | 0.13 MW |
Details for ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11622_R-S
| Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
|---|---|---|---|---|
| 274837 | EQUISTAR ; B | 80/20 | 0.71 MW | 0.71 MW |
| 274836 | EQUISTAR ; R | 80/20 | 1.25 MW | 1.25 MW |
| 935001 | AD1-133 C O1 | 80/20 | 17.25 MW | 17.25 MW |
| 936511 | AD2-066 C O1 | 80/20 | 5.12 MW | 5.12 MW |
| 274658 | DRESDEN ;2U | 80/20 | 23.32 MW | 23.32 MW |
| 274659 | DRESDEN ;3U | 80/20 | 22.72 MW | 22.72 MW |
| 274704 | KENDALL ;1C | 80/20 | 2.87 MW | 2.87 MW |
| 274705 | KENDALL ;1S | 80/20 | 1.92 MW | 1.92 MW |
| 274706 | KENDALL ;2C | 80/20 | 2.87 MW | 2.87 MW |
| 274707 | KENDALL ;2S | 80/20 | 1.92 MW | 1.92 MW |
| 274728 | ELWOOD EC;5P | 80/20 | 8.75 MW | 8.75 MW |
| 274729 | ELWOOD EC;1P | 80/20 | 8.69 MW | 8.69 MW |
| 274730 | ELWOOD EC;6P | 80/20 | 8.75 MW | 8.75 MW |
| 274731 | ELWOOD EC;2P | 80/20 | 8.69 MW | 8.69 MW |
| 274732 | ELWOOD EC;7P | 80/20 | 8.75 MW | 8.75 MW |
| 274733 | ELWOOD EC;3P | 80/20 | 8.69 MW | 8.69 MW |
| 274734 | ELWOOD EC;8P | 80/20 | 8.75 MW | 8.75 MW |
| 274735 | ELWOOD EC;4P | 80/20 | 8.69 MW | 8.69 MW |
| 274736 | ELWOOD EC;9P | 80/20 | 8.75 MW | 8.75 MW |
| 274879 | MINONK ;1U | 80/20 | 0.59 MW | 0.59 MW |
| 927091 | AC1-204 1 | 80/20 | 182.37 MW | 182.37 MW |
| 927101 | AC1-204 2 | 80/20 | 181.13 MW | 181.13 MW |
| 934101 | AD2-000 1 | 80/20 | 6.49 MW | 6.49 MW |
| 934111 | AD2-000 2 | 80/20 | 6.63 MW | 6.63 MW |
| 905493 | W4-086 | 80/20 | 0.03 MW | 0.03 MW |
| 930761 | AB1-122 1 | 80/20 | 80.22 MW | 80.22 MW |
| 930771 | AB1-122 2 | 80/20 | 82.0 MW | 82.0 MW |
| 937401 | AD2-194 C1 | 80/20 | 19.61 MW | 19.61 MW |
| 937411 | AD2-194 C2 | 80/20 | 19.48 MW | 19.48 MW |
| 918111 | AA1-040 1 | 80/20 | 0.17 MW | 0.17 MW |
| 918121 | AA1-040 2 | 80/20 | 0.15 MW | 0.15 MW |
| CANNELTON | LTFEXP_CANNELTON->LTFIMP_CANNELTON | CLTF | 0.03 MW | 0.03 MW |
| BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.6 MW | 0.6 MW |
| CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 12.65 MW | 12.65 MW |
| CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.22 MW | 0.22 MW |
| CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 7.35 MW | 7.35 MW |
| WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.02 MW | 1.02 MW |
| CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.48 MW | 0.48 MW |
| CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.07 MW | 0.07 MW |
| HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.14 MW | 0.14 MW |
| ELMERSMITH | LTFEXP_ELMERSMITH->LTFIMP_ELMERSMITH | CLTF | 0.05 MW | 0.05 MW |
| MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.74 MW | 9.74 MW |
| CLIFTY | LTFEXP_CLIFTY->LTFIMP_CLIFTY | CLTF | 3.51 MW | 3.51 MW |
| GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.12 MW | 0.12 MW |
| RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.17 MW | 0.17 MW |
Details for ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line l/o Base Case
| Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
|---|---|---|---|---|
| 274837 | EQUISTAR ; B | 80/20 | 0.53 MW | 0.53 MW |
| 274836 | EQUISTAR ; R | 80/20 | 0.92 MW | 0.92 MW |
| 935001 | AD1-133 C O1 | 80/20 | 12.94 MW | 12.94 MW |
| 936511 | AD2-066 C O1 | 80/20 | 3.76 MW | 3.76 MW |
| 274658 | DRESDEN ;2U | 80/20 | 16.69 MW | 16.69 MW |
| 274659 | DRESDEN ;3U | 80/20 | 17.02 MW | 17.02 MW |
| 274704 | KENDALL ;1C | 80/20 | 1.88 MW | 1.88 MW |
| 274705 | KENDALL ;1S | 80/20 | 1.25 MW | 1.25 MW |
| 274706 | KENDALL ;2C | 80/20 | 1.88 MW | 1.88 MW |
| 274707 | KENDALL ;2S | 80/20 | 1.25 MW | 1.25 MW |
| 274728 | ELWOOD EC;5P | 80/20 | 6.49 MW | 6.49 MW |
| 274729 | ELWOOD EC;1P | 80/20 | 6.4 MW | 6.4 MW |
| 274730 | ELWOOD EC;6P | 80/20 | 6.49 MW | 6.49 MW |
| 274731 | ELWOOD EC;2P | 80/20 | 6.4 MW | 6.4 MW |
| 274732 | ELWOOD EC;7P | 80/20 | 6.49 MW | 6.49 MW |
| 274733 | ELWOOD EC;3P | 80/20 | 6.4 MW | 6.4 MW |
| 274734 | ELWOOD EC;8P | 80/20 | 6.49 MW | 6.49 MW |
| 274735 | ELWOOD EC;4P | 80/20 | 6.4 MW | 6.4 MW |
| 274736 | ELWOOD EC;9P | 80/20 | 6.49 MW | 6.49 MW |
| 274879 | MINONK ;1U | 80/20 | 0.42 MW | 0.42 MW |
| 927091 | AC1-204 1 | 80/20 | 135.19 MW | 135.19 MW |
| 927101 | AC1-204 2 | 80/20 | 133.33 MW | 133.33 MW |
| 934101 | AD2-000 1 | 80/20 | 4.86 MW | 4.86 MW |
| 934111 | AD2-000 2 | 80/20 | 4.74 MW | 4.74 MW |
| 905493 | W4-086 | 80/20 | 0.03 MW | 0.03 MW |
| 930761 | AB1-122 1 | 80/20 | 60.09 MW | 60.09 MW |
| 930771 | AB1-122 2 | 80/20 | 58.66 MW | 58.66 MW |
| 937401 | AD2-194 C1 | 80/20 | 14.54 MW | 14.54 MW |
| 937411 | AD2-194 C2 | 80/20 | 14.34 MW | 14.34 MW |
| 918111 | AA1-040 1 | 80/20 | 0.13 MW | 0.13 MW |
| 918121 | AA1-040 2 | 80/20 | 0.11 MW | 0.11 MW |
| CANNELTON | LTFEXP_CANNELTON->LTFIMP_CANNELTON | CLTF | 0.02 MW | 0.02 MW |
| BLUEG | LTFEXP_BLUEG->LTFIMP_BLUEG | CLTF | 0.45 MW | 0.45 MW |
| CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CLTF | 9.2 MW | 9.2 MW |
| CARR | LTFEXP_CARR->LTFIMP_CARR | CLTF | 0.16 MW | 0.16 MW |
| CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CLTF | 5.08 MW | 5.08 MW |
| WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.75 MW | 0.75 MW |
| CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CLTF | 0.33 MW | 0.33 MW |
| CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.06 MW | 0.06 MW |
| HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.11 MW | 0.11 MW |
| ELMERSMITH | LTFEXP_ELMERSMITH->LTFIMP_ELMERSMITH | CLTF | 0.04 MW | 0.04 MW |
| MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.08 MW | 7.08 MW |
| CLIFTY | LTFEXP_CLIFTY->LTFIMP_CLIFTY | CLTF | 2.61 MW | 2.61 MW |
| GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.09 MW | 0.09 MW |
| RENSSELAER | LTFEXP_RENSSELAER->LTFIMP_RENSSELAER | CLTF | 0.13 MW | 0.13 MW |
Summer Potential Congestion due to Local Energy Deliverability
(No impacts were found for this analysis)
Winter Peak Analysis
At this time winter peak analysis not required for this project.
Winter Potential Congestion due to Local Energy Deliverability
At this time winter peak analysis not required for this project.
Light Load Analysis
At this time light load analysis not required for this project.
Light Load Potential Congestion due to Local Energy Deliverability
At this time light load analysis not required for this project.
Short Circuit Analysis
PJM Short Circuit Analysis did not identify any new overduty breakers or >3% contribution to previously identified overduty breakers.
Stability Analysis
No mitigation was found to be required due to transient stability.
Reactive Power Analysis
This project meets the power factor requirements.
Steady-State Voltage Analysis
Steady State Voltage analysis is not required for this queue project at this time.
Queue Dependencies
The Queue Projects below are listed in one or more dispatch for the overloads identified in your report. These projects contribute to the loading of the overloaded facilities identified in your report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of these earlier projects. The status of each project at the time of the analysis is presented in the table. This list may change as earlier projects withdraw or modify their requests. This table is valid for load flow analyses only.
| Queue Number | Project Name | Status |
|---|---|---|
| AA1-018 | Powerton-Goodings Grove | In Service |
| AA1-040 | Morris | In Service |
| AA1-146 | Nelson | Under Construction |
| AA2-030 | Nelson | Under Construction |
| AA2-123 | Marengo 34kV | In Service |
| AB1-089 | Byron-Wayne 345kV #1 | Suspended |
| AB1-122 | Kendall-Tazewell & Dresden-Mole Creek | Partially in Service - Under Construction |
| AB2-047 | Brokaw-Pontiac Midpoint | In Service |
| AB2-191 | Mendota Hills | In Service |
| AC1-033 | Kewanee 138 kV | Engineering & Procurement |
| AC1-109 | Aurora 345kV | In Service |
| AC1-110 | Aurora 138kV | Partially in Service - Under Construction |
| AC1-111 | Aurora 138kV | In Service |
| AC1-113 | Rockford | In Service |
| AC1-114 | Rockford II | In Service |
| AC1-142A | Joliet | In Service |
| AC1-168 | Kewanee-Streator | Engineering & Procurement |
| AC1-185 | Lee County | In Service |
| AC1-204 | Elwood | In Service |
| AC1-214 | Crescent Ridge | In Service |
| AC2-115 | Rockford | In Service |
| AC2-116 | Rockford II | In Service |
| AC2-117 | University Park North | Engineering & Procurement |
| AC2-154 | Davis Creek 138kV | Engineering & Procurement |
| AD1-013 | Twombly Road 138kV | Engineering & Procurement |
| AD1-016 | Marengo | Suspended |
| AD1-031 | Kewanee - E.D. Edwards 138 kV | Active |
| AD1-067 | Mendota Hills | In Service |
| AD1-098 | Dixon - McGirr 138 kV | Active |
| AD1-100 | Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kV | Active |
| AD1-129 | Belvidere 34 kV | Suspended |
| AD1-133 | Pontiac MidPoint-Dresden | Active |
| AD2-038 | Powerton | Active |
| AD2-047 | Davis Creek 138 kV | Active |
| AD2-060 | Davis Creek 138kV | Engineering & Procurement |
| AD2-066 | Mazon-Crescent Ridge 138 kV | Active |
| AD2-102 | Wempletown 345 kV | Active |
| AD2-134 | Shady Oaks | Active |
| AD2-172 | Lena 138kV | Under Construction |
| AD2-214 * | Rock Falls-Garden Plains | Active |
| U3-031 | Lincoln Generating Facility | In Service |
| W4-086 | Goose Lake 34.5kV | Deactivated |
| X3-005 | Wildwood 12kV | In Service |
| Y3-013 | Zion Energy Center | In Service |
| Z1-106 | West Chicago 34kV | Deactivated |
| Z1-107 | Joliet 34kV | Deactivated |
| Z1-108 | McHenry 34kV | In Service |
| Z2-087 | Pontiac MidPoint-Brokaw 345kV | In Service |
* = Queue Project is after AD2-194 in queue order. Withdrawal of this project is unlikely to affect cost allocation for AD2-194.
Affected Systems
System Reinforcements
| RTEP ID | Title | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|---|
| n5915 | Elwood - Goodings B 345 kV line Reconductoring | 39.1 MW | 33.9% | $10,448,104 |
| n5916 | Elwood - Goodings R 345 kV Line Reconductoring | 39.3 MW | 29.6% | $9,322,676 |
| Grand Total: | $19,770,780 | |||
| RTEP ID | Title | Total Cost | Time Estimate |
|---|---|---|---|
| n4058 | Sag Mitigation Work on the Stillwell - Dumont 345 kV line | $1,971,000 | 12 - 13 Months |
Note: Based on PJM cost allocation criteria, AD2-194 currently does not receive cost allocation towards this upgrade. As changes to the PJM queue process occur (such as prior queued projects withdrawing from the queue, reducing in size, etc.) AD2-194 could receive cost allocation. Although Queue Project AD2-194 may not presently have cost responsibility for this upgrade, Queue Project AD2-194 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AD2-194 comes into service prior to completion of the upgrade, Queue Project AD2-194 will need an interim study.
Description: A sag study was performed on this section of conductor. The following reinforcements were identified by the sag study and will be required to mitigate the overload: AEP will replace structure #20 with a single circuit custom steel pole structure and structure #24 with a custom steel H-frame structure on the Stillwell - Dumont 345 kV circuit. The replacements include removal of the two (2) existing lattice structures. AEP will also modify one (1) existing lattice structure, replacing a bottom swing angle bracket with a 3” tee. SE rating will be 1718 MVA limited by a Dumont wave trap. (Provided by AEP per AD1-098 FAC study).
| Facility | Contingency |
|---|---|
| 05DUMONT-17STILLWELL 345.0 kV Ckt 1 line | (Any) |
| Facility | Rating Set | Rating Type | Rating Value |
|---|---|---|---|
| 05DUMONT-17STILLWELL 345.0 kV Ckt 1 line | (All) | B | 1718.0 MVA |
| RTEP ID | Title | Total Cost | Time Estimate |
|---|---|---|---|
| n5915 | Elwood - Goodings B 345 kV line Reconductoring | $30,831,127 | 0 Months |
AD2-194 is a Contributor
Description: The upgrade will be to Reconductor 18.1 miles of the line with 2156 kcmil ACSR (84/19) Str Bluebird conductor and replace some towers.
| Facility | Contingency |
|---|---|
| ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line | (Any) |
| Facility | Rating Set | Rating Type | Rating Value |
|---|---|---|---|
| ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line | (All) | A | 1334.0 MVA |
| ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line | (All) | ALDR | 2084.0 MVA |
| ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line | (All) | B | 1726.0 MVA |
| ELWOOD ; B-GOODINGS ;4B 345.0 kV Ckt 1 line | (All) | STE | 1837.0 MVA |
| Queue Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
| AC1-204 | 59.0 MW | 51.1% | $15,769,714 |
| AD1-133 | 17.3 MW | 15.0% | $4,613,310 |
| AD2-194 | 39.1 MW | 33.9% | $10,448,104 |
| RTEP ID | Title | Total Cost | Time Estimate |
|---|---|---|---|
| n5916 | Elwood - Goodings R 345 kV Line Reconductoring | $31,529,018 | 0 Months |
AD2-194 is a Contributor
Description: The upgrade will be to Reconductor 18.1 miles of the line with 2156 kcmil ACSR (84/19) Str Bluebird conductor and replace some towers.
| Facility | Contingency |
|---|---|
| ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line | (Any) |
| Facility | Rating Set | Rating Type | Rating Value |
|---|---|---|---|
| ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line | (All) | A | 1334.0 MVA |
| ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line | (All) | ALDR | 2084.0 MVA |
| ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line | (All) | B | 1726.0 MVA |
| ELWOOD ; R-GOODINGS ;2R 345.0 kV Ckt 1 line | (All) | STE | 1837.0 MVA |
| Queue Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
| AC1-204 | 76.7 MW | 57.8% | $18,208,536 |
| AD1-133 | 16.8 MW | 12.7% | $3,997,806 |
| AD2-194 | 39.3 MW | 29.6% | $9,322,676 |