Surry Skiffes Creek 500kV

Surry Skiffes Creek
   

Dominion Assigned Baseline Project with PJM Id

b1905.1 through b1905.9

Scope

  • Build a new 7.7 mile Surry to Skiffes Creek 500kV line
  • Build a new 20.25 mile Skiffes Creek – Whealton 230kV line
  • Build a new Skiffes Creek 500 / 230kV switching station
  • Upgrade Surry, Whealton, and seven other substations

Need

Based on the Generation Retirement study of Chesapeake Units 1 – 4 and Yorktown 1

  • Criteria Violation: Overload of James River Crossing Double Circuit Towerline
  • Contingency: Loss of Surry - Winchester 230 kV, Chuckatuck – Newport News 230 kV, Chickahominy – Waller 230 kV
  • Criteria test: Dominion Criteria (Surry #2 or Yorktown #3 out)

Permits

  • All major permits have been received

Energization

  • PJM required date of 6.1.2015 for 500kV portion and 6/1/2016 for 230kV portion
  • Dominion projected date for energization:
    • 500kv Line 12.31.2018
    • 230kv Line 12.31.2018

Land Acquisition

ROW acquisition is complete

Engineering / Design

  • 500kV line 75% complete
  • 230kV Line 100% complete
  • Skiffes Creek Switching Station 100% complete
  • Whealton Substation – 95% complete
  • Other Stations 35% complete

Equipment Procurement / Delivery

  • 500kV Line material 85% complete
  • 230kV Line material 100% complete
  • Skiffes Creek Switching station 100% complete

Construction

Dominion has started construction with plans to complete at the end of 2018

Outages

  • eDART 491070 Denbigh – Waller 230kV
  • eDART 491068 Denbigh – Yorktown 230kV
  • eDART 548864 Lebanon – Yorktown 115kV
  • eDART 490919 Rock Landing – Yorktown 230kV
  • eDART 490918 Rock Landing – Warwick 230kV
  • eDART 490915 Warwick – Whealton 230kV