AG1-060 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:49
Eldred 69 kV
25.7 MW Capacity / 174.8 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-060 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the PPL zone — Schuylkill County, Pennsylvania. The installed facilities will have a total capability of 174.8 MW with 25.7 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-060 |
| Project Name | Eldred 69 kV |
| Developer Name | ANTHRACITE RIDGE LLC |
| State | Pennsylvania |
| County | Schuylkill |
| Transmission Owner | PPL |
| MFO | 174.8 MW |
| MWE | 174.8 MW |
| MWC | 25.7 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-060 will interconnect on the PPL transmission system at the 69 kV Eldred substation.
Summer Peak Analysis
The Queue Project was evaluated as a 174.8 MW (Capacity 25.7 MW) injection in the PPL area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| PL |
AE1-058_TAP-SIEG 230.0 kV Ckt 1 line
938390 to 208072 ckt 1 |
Base Case | Single | AC | 117.97 % | 119.11 % | 513.0 | A | 611.01 | 6.1 | |
| PL |
AE1-058_TAP-SIEG 230.0 kV Ckt 1 line
938390 to 208072 ckt 1 |
PL:18:P12:000083
CONTINGENCY 'PL:18:P12:000083' DISCONNECT BRANCH FROM BUS 200009 TO BUS 200021 CKT 1 /*JUNIATA 500.0 - SUNBURY 500.0 END |
Single | AC | 116.97 % | 118.17 % | 628.0 | B | 742.08 | 7.02 | |
| PL |
AE1-058_TAP-SIEG 230.0 kV Ckt 1 line
938390 to 208072 ckt 1 |
PL:18:P42:000923
CONTINGENCY 'PL:18:P42:000923' DISCONNECT BRANCH FROM BUS 200021 TO BUS 200009 CKT 1 /*SUNBURY 500.0 - JUNIATA 500.0 DISCONNECT BRANCH FROM BUS 200021 TO BUS 208109 CKT 25 /*SUNBURY 500.0 - SUNB 230.0 END |
Breaker | AC | 117.45 % | 125.1 % | 628.0 | B | 785.64 | 49.92 | |
| PL |
AE1-058_TAP-SIEG 230.0 kV Ckt 1 line
938390 to 208072 ckt 1 |
PL:18:P42:000922
CONTINGENCY 'PL:18:P42:000922' DISCONNECT BRANCH FROM BUS 200021 TO BUS 200009 CKT 1 /*SUNBURY 500.0 - JUNIATA 500.0 DISCONNECT BRANCH FROM BUS 200021 TO BUS 208109 CKT 24 /*SUNBURY 500.0 - SUNB 230.0 END |
Breaker | AC | 117.44 % | 125.09 % | 628.0 | B | 785.6 | 49.91 | |
| PL |
JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer
200009 to 208005 ckt 2 |
PL:11:P42:000140
CONTINGENCY 'PL:11:P42:000140' DISCONNECT BRANCH FROM BUS 200009 TO BUS 200016 CKT 1 /*JUNIATA 500.0 - 3 MILE I 500.0 DISCONNECT BRANCH FROM BUS 200009 TO BUS 208004 CKT 1 /*JUNIATA 500.0 - JUNI BU1 230.0 REMOVE SWSHUNT FROM BUS 200009 /*JUNIATA 500.0 END |
Breaker | AC | 109.13 % | 110.23 % | 814.0 | B | 897.3 | 11.99 | |
| PL |
SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer
208072 to 211161 ckt 4 |
PL:20:P42:102406
CONTINGENCY 'PL:20:P42:102406' DISCONNECT BRANCH FROM BUS 208025 TO BUS 208072 CKT 1 /*MACR 230.0 - SIEG 230.0 DISCONNECT BRANCH FROM BUS 208072 TO BUS 211161 CKT 5 /*SIEG 230.0 - SIEG 138.0 END |
Breaker | AC | 99.68 % | 101.94 % | 488.0 | B | 497.48 | 13.01 | |
| PL |
AE1-058_TAP-SIEG 230.0 kV Ckt 1 line
938390 to 208072 ckt 1 |
PL:48:P71:102415
CONTINGENCY 'PL:48:P71:102415' DISCONNECT BRANCH FROM BUS 207977 TO BUS 208113 CKT 1 /*HARW 230.0 - SUSQ 230.0 DISCONNECT BRANCH FROM BUS 207977 TO BUS 208113 CKT 2 /*HARW 230.0 - SUSQ 230.0 END |
Tower | AC | 123.27 % | 129.75 % | 628.0 | B | 814.82 | 41.83 | |
| PL |
AE1-058_TAP-SIEG 230.0 kV Ckt 1 line
938390 to 208072 ckt 1 |
PL:08:P71:101751
CONTINGENCY 'PL:08:P71:101751' DISCONNECT BRANCH FROM BUS 207915 TO BUS 208040 CKT 1 /*GLBR 230.0 - MONT 230.0 DISCONNECT BRANCH FROM BUS 207915 TO BUS 208040 CKT 2 /*GLBR 230.0 - MONT 230.0 END |
Tower | AC | 118.99 % | 126.22 % | 628.0 | B | 792.69 | 47.26 | |
| PL |
GLBR-SU10 230.0 kV Ckt 1 line
207915 to 208120 ckt 1 |
PL:48:P71:102649
CONTINGENCY 'PL:48:P71:102649' DISCONNECT BRANCH FROM BUS 207915 TO BUS 208113 CKT 1 /*GLBR 230.0 - SUSQ 230.0 DISCONNECT BUS 208114 /*SUSQ G1 230.0 END |
Tower | AC | 117.91 % | 120.94 % | 801.0 | B | 968.73 | 30.02 | |
| PL |
SU10-SUSQ 230.0 kV Ckt 1 line
208120 to 208113 ckt 1 |
PL:48:P71:102649
CONTINGENCY 'PL:48:P71:102649' DISCONNECT BRANCH FROM BUS 207915 TO BUS 208113 CKT 1 /*GLBR 230.0 - SUSQ 230.0 DISCONNECT BUS 208114 /*SUSQ G1 230.0 END |
Tower | AC | 98.38 % | 100.63 % | 801.0 | B | 806.03 | 22.28 | |
| PL |
FRAC-AE1-058_TAP 230.0 kV Ckt 1 line
207973 to 938390 ckt 1 |
PL:48:P71:102415
CONTINGENCY 'PL:48:P71:102415' DISCONNECT BRANCH FROM BUS 207977 TO BUS 208113 CKT 1 /*HARW 230.0 - SUSQ 230.0 DISCONNECT BRANCH FROM BUS 207977 TO BUS 208113 CKT 2 /*HARW 230.0 - SUSQ 230.0 END |
Tower | AC | 94.0 % | 100.42 % | 628.0 | B | 630.66 | 41.83 | |
| Details for AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 942281 | AE2-241 C | 80/20 | 1.35 MW | 1.35 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 942561 | AE2-271 C | 80/20 | 6.0 MW | 6.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 943721 | AF1-040 C | 80/20 | 0.08 MW | 0.08 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 945611 | AF1-226 C | 80/20 | 2.37 MW | 2.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 959421 | AF2-233 C | 80/20 | 0.96 MW | 0.96 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 959431 | AF2-234 C | 80/20 | 1.91 MW | 1.91 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 960401 | AF2-331 C | 80/20 | 2.95 MW | 2.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 960411 | AF2-332 C | 80/20 | 2.95 MW | 2.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 960421 | AF2-333 C | 80/20 | 1.18 MW | 1.18 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 960431 | AF2-334 C | 80/20 | 1.18 MW | 1.18 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 961331 | AF2-424 C | 80/20 | 2.85 MW | 2.85 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 961341 | AF2-425 C | 80/20 | 2.85 MW | 2.85 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 961421 | AF2-433 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 961431 | AF2-434 C O1 | 80/20 | 1.93 MW | 1.93 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 961531 | AF2-444 C | 80/20 | 2.8 MW | 2.8 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 961541 | AF2-445AC | 80/20 | 3.71 MW | 3.71 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 962061 | AG1-050 | 80/20 | 1.76 MW | 1.76 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 962151 | AG1-060 C | 80/20 | 6.1 MW | 6.1 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 208911 | MONT G1 | 80/20 | 12.72 MW | 12.72 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 208912 | MONT G2 | 80/20 | 12.71 MW | 12.71 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 208941 | FISH CT | 80/20 | 1.5 MW | 1.5 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 208945 | LOHA CT | 80/20 | 0.21 MW | 0.21 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 208948 | WILL CT | 80/20 | 0.43 MW | 0.43 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 208981 | FOWH IPP | 80/20 | 1.73 MW | 1.73 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 208982 | GLBT IPP | 80/20 | 4.39 MW | 4.39 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 209013 | SCEN IPP | 80/20 | 4.6 MW | 4.6 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 209018 | SUNBIPCT | 80/20 | 0.49 MW | 0.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 209021 | WEST IPP | 80/20 | 1.31 MW | 1.31 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 209022 | WHFR IPP | 80/20 | 13.51 MW | 13.51 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 209027 | LOR2_Q27 | 80/20 | 0.61 MW | 0.61 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 212005 | ALWD | 80/20 | 0.05 MW | 0.05 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 212099 | COLA IPP | 80/20 | 0.32 MW | 0.32 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 212174 | INGE | 80/20 | 0.25 MW | 0.25 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 212266 | LOR1 | 80/20 | 0.19 MW | 0.19 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 938393 | AE1-058_GEN2 | 80/20 | 97.48 MW | 97.48 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 939891 | AE1-225 C O1 | 80/20 | 0.75 MW | 0.75 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 940561 | AE2-042 C | 80/20 | 4.13 MW | 4.13 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 940721 | AE2-059 C | 80/20 | 0.74 MW | 0.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 940941 | AE2-084 C | 80/20 | 0.74 MW | 0.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 941161 | AE2-110 C | 80/20 | 1.35 MW | 1.35 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 941371 | AE2-133 C | 80/20 | 0.67 MW | 0.67 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 946691 | AF1-333 C O1 | 80/20 | 1.0 MW | 1.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 946731 | AF1-337 C | 80/20 | 1.0 MW | 1.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 946741 | AF1-338 C | 80/20 | 1.0 MW | 1.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 946751 | AF1-339 C O1 | 80/20 | 1.0 MW | 1.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 946761 | AF1-271AC | 80/20 | 0.81 MW | 0.81 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 957621 | AF2-056 C | 80/20 | 10.37 MW | 10.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 964051 | AG1-259 C | 80/20 | 0.53 MW | 0.53 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 964061 | AG1-260 C | 80/20 | 0.53 MW | 0.53 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 212345 | PENS | 80/20 | 0.04 MW | 0.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 212369 | PATRIOT 1 | 80/20 | 6.2 MW | 6.2 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 212370 | PATRIOT 2 | 80/20 | 6.2 MW | 6.2 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 212435 | SMIL | 80/20 | 0.03 MW | 0.03 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 957881 | AF2-082 C | 80/20 | 2.63 MW | 2.63 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 957921 | AF2-086 C | 80/20 | 1.9 MW | 1.9 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 958461 | AF2-140 | 80/20 | 2.85 MW | 2.85 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | 938392 | AE1-058_GEN1 | 80/20 | 97.48 MW | 97.48 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.03 MW | 0.03 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.81 MW | 0.81 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.94 MW | 1.94 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.08 MW | 1.08 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.04 MW | 0.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.2 MW | 0.2 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.08 MW | 0.08 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.2 MW | 0.2 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.16 MW | 0.16 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 208930 | HUST CT11 | 80/20 | 3.17 MW | 3.17 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 208931 | HUST CT12 | 80/20 | 3.44 MW | 3.44 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 208932 | HUST CT13 | 80/20 | 3.17 MW | 3.17 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 208933 | HUST ST10 | 80/20 | 5.63 MW | 5.63 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 942281 | AE2-241 C | 80/20 | 1.65 MW | 1.65 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 942561 | AE2-271 C | 80/20 | 8.22 MW | 8.22 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 943721 | AF1-040 C | 80/20 | 0.12 MW | 0.12 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 945611 | AF1-226 C | 80/20 | 2.89 MW | 2.89 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 959421 | AF2-233 C | 80/20 | 1.46 MW | 1.46 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 959431 | AF2-234 C | 80/20 | 2.92 MW | 2.92 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 960401 | AF2-331 C | 80/20 | 4.04 MW | 4.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 960411 | AF2-332 C | 80/20 | 4.04 MW | 4.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 960421 | AF2-333 C | 80/20 | 1.62 MW | 1.62 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 960431 | AF2-334 C | 80/20 | 1.62 MW | 1.62 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 961331 | AF2-424 C | 80/20 | 3.28 MW | 3.28 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 961341 | AF2-425 C | 80/20 | 3.28 MW | 3.28 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 961421 | AF2-433 C O1 | 80/20 | 2.36 MW | 2.36 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 961431 | AF2-434 C O1 | 80/20 | 2.36 MW | 2.36 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 961531 | AF2-444 C | 80/20 | 3.23 MW | 3.23 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 961541 | AF2-445AC | 80/20 | 4.1 MW | 4.1 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 962061 | AG1-050 | 80/20 | 2.55 MW | 2.55 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 962151 | AG1-060 C | 80/20 | 7.02 MW | 7.02 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 208911 | MONT G1 | 80/20 | 17.42 MW | 17.42 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 208912 | MONT G2 | 80/20 | 17.41 MW | 17.41 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 208941 | FISH CT | 80/20 | 1.66 MW | 1.66 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 208945 | LOHA CT | 80/20 | 0.31 MW | 0.31 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 208948 | WILL CT | 80/20 | 0.61 MW | 0.61 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 208981 | FOWH IPP | 80/20 | 1.99 MW | 1.99 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 208982 | GLBT IPP | 80/20 | 4.85 MW | 4.85 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 209013 | SCEN IPP | 80/20 | 5.09 MW | 5.09 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 209018 | SUNBIPCT | 80/20 | 0.74 MW | 0.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 209021 | WEST IPP | 80/20 | 1.51 MW | 1.51 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 209022 | WHFR IPP | 80/20 | 14.93 MW | 14.93 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 209027 | LOR2_Q27 | 80/20 | 0.67 MW | 0.67 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 212005 | ALWD | 80/20 | 0.07 MW | 0.07 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 212099 | COLA IPP | 80/20 | 0.37 MW | 0.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 212174 | INGE | 80/20 | 0.28 MW | 0.28 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 212266 | LOR1 | 80/20 | 0.21 MW | 0.21 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 938393 | AE1-058_GEN2 | 80/20 | 105.27 MW | 105.27 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 939891 | AE1-225 C O1 | 80/20 | 1.14 MW | 1.14 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 940561 | AE2-042 C | 80/20 | 5.97 MW | 5.97 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 940721 | AE2-059 C | 80/20 | 1.07 MW | 1.07 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 940941 | AE2-084 C | 80/20 | 1.07 MW | 1.07 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 941161 | AE2-110 C | 80/20 | 1.65 MW | 1.65 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 941371 | AE2-133 C | 80/20 | 1.02 MW | 1.02 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 946691 | AF1-333 C O1 | 80/20 | 1.49 MW | 1.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 946731 | AF1-337 C | 80/20 | 1.49 MW | 1.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 946741 | AF1-338 C | 80/20 | 1.49 MW | 1.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 946751 | AF1-339 C O1 | 80/20 | 1.49 MW | 1.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 946761 | AF1-271AC | 80/20 | 1.24 MW | 1.24 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 957621 | AF2-056 C | 80/20 | 11.46 MW | 11.46 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 964051 | AG1-259 C | 80/20 | 0.81 MW | 0.81 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 964061 | AG1-260 C | 80/20 | 0.81 MW | 0.81 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 212345 | PENS | 80/20 | 0.06 MW | 0.06 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 212369 | PATRIOT 1 | 80/20 | 8.63 MW | 8.63 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 212370 | PATRIOT 2 | 80/20 | 8.63 MW | 8.63 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 212435 | SMIL | 80/20 | 0.04 MW | 0.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 957881 | AF2-082 C | 80/20 | 4.01 MW | 4.01 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 957921 | AF2-086 C | 80/20 | 2.32 MW | 2.32 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 958461 | AF2-140 | 80/20 | 3.97 MW | 3.97 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | 938392 | AE1-058_GEN1 | 80/20 | 105.27 MW | 105.27 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.26 MW | 0.26 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.21 MW | 0.21 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.45 MW | 0.45 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.13 MW | 0.13 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.1 MW | 0.1 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.34 MW | 0.34 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.14 MW | 0.14 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.56 MW | 0.56 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.16 MW | 0.16 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.67 MW | 0.67 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P12:000083 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.14 MW | 0.14 MW |
| Details for AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 942281 | AE2-241 C | 50/50 | 1.74 MW | 1.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 942282 | AE2-241 E | 50/50 | 2.41 MW | 2.41 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 942561 | AE2-271 C | Adder | 8.92 MW | 7.58 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 942562 | AE2-271 E | Adder | 5.94 MW | 5.05 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 943721 | AF1-040 C | Adder | 0.14 MW | 0.12 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 943722 | AF1-040 E | Adder | 2.61 MW | 2.22 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 945611 | AF1-226 C | 50/50 | 3.05 MW | 3.05 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 945612 | AF1-226 E | 50/50 | 4.22 MW | 4.22 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 959421 | AF2-233 C | Adder | 1.65 MW | 1.4 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 959422 | AF2-233 E | Adder | 1.1 MW | 0.94 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 959431 | AF2-234 C | Adder | 3.3 MW | 2.81 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 959432 | AF2-234 E | Adder | 2.2 MW | 1.87 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 959932 | AF2-284 E | Adder | 0.29 MW | 0.25 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 959982 | AF2-289 E | Adder | 0.43 MW | 0.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 959992 | AF2-290 E | Adder | 0.28 MW | 0.24 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 960401 | AF2-331 C | Adder | 4.39 MW | 3.73 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 960402 | AF2-331 E | Adder | 2.92 MW | 2.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 960411 | AF2-332 C | Adder | 4.39 MW | 3.73 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 960412 | AF2-332 E | Adder | 2.92 MW | 2.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 960421 | AF2-333 C | Adder | 1.76 MW | 1.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 960422 | AF2-333 E | Adder | 1.17 MW | 0.99 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 960431 | AF2-334 C | Adder | 1.76 MW | 1.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 960432 | AF2-334 E | Adder | 1.17 MW | 0.99 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961331 | AF2-424 C | 50/50 | 3.43 MW | 3.43 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961332 | AF2-424 E | 50/50 | 2.29 MW | 2.29 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961341 | AF2-425 C | 50/50 | 3.43 MW | 3.43 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961342 | AF2-425 E | 50/50 | 2.29 MW | 2.29 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961362 | AF2-427 E | Adder | 0.43 MW | 0.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961412 | AF2-432 E | 50/50 | 0.41 MW | 0.41 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961421 | AF2-433 C O1 | 50/50 | 2.49 MW | 2.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961422 | AF2-433 E O1 | 50/50 | 1.66 MW | 1.66 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961431 | AF2-434 C O1 | 50/50 | 2.49 MW | 2.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961432 | AF2-434 E O1 | 50/50 | 1.66 MW | 1.66 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961531 | AF2-444 C | 50/50 | 3.37 MW | 3.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961532 | AF2-444 E | 50/50 | 2.29 MW | 2.29 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961541 | AF2-445AC | 50/50 | 4.22 MW | 4.22 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 961542 | AF2-445AE | 50/50 | 2.86 MW | 2.86 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 962061 | AG1-050 | Adder | 2.83 MW | 2.4 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 962151 | AG1-060 C | 50/50 | 7.34 MW | 7.34 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 962152 | AG1-060 E | 50/50 | 42.58 MW | 42.58 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 208941 | FISH CT | 50/50 | 1.71 MW | 1.71 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 208981 | FOWH IPP | 50/50 | 2.08 MW | 2.08 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 208982 | GLBT IPP | 50/50 | 5.0 MW | 5.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 209013 | SCEN IPP | 50/50 | 5.24 MW | 5.24 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 209021 | WEST IPP | 50/50 | 1.58 MW | 1.58 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 209022 | WHFR IPP | 50/50 | 15.38 MW | 15.38 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 209027 | LOR2_Q27 | 50/50 | 0.69 MW | 0.69 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 212099 | COLA IPP | 50/50 | 0.39 MW | 0.39 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 212174 | INGE | 50/50 | 0.3 MW | 0.3 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 212266 | LOR1 | 50/50 | 0.21 MW | 0.21 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 938393 | AE1-058_GEN2 | 50/50 | 107.62 MW | 107.62 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 939891 | AE1-225 C O1 | Adder | 1.29 MW | 1.1 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 939892 | AE1-225 E O1 | Adder | 1.43 MW | 1.22 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 940561 | AE2-042 C | Adder | 6.62 MW | 5.63 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 940562 | AE2-042 E | Adder | 3.28 MW | 2.79 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 940721 | AE2-059 C | Adder | 1.19 MW | 1.01 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 940722 | AE2-059 E | Adder | 1.64 MW | 1.4 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 940941 | AE2-084 C | Adder | 1.19 MW | 1.01 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 940942 | AE2-084 E | Adder | 1.64 MW | 1.4 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 941161 | AE2-110 C | 50/50 | 1.74 MW | 1.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 941162 | AE2-110 E | 50/50 | 2.41 MW | 2.41 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 941371 | AE2-133 C | Adder | 1.16 MW | 0.98 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 941372 | AE2-133 E | Adder | 1.6 MW | 1.36 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 946691 | AF1-333 C O1 | Adder | 1.67 MW | 1.42 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 946692 | AF1-333 E O1 | Adder | 1.11 MW | 0.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 946731 | AF1-337 C | Adder | 1.67 MW | 1.42 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 946732 | AF1-337 E | Adder | 1.11 MW | 0.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 946741 | AF1-338 C | Adder | 1.67 MW | 1.42 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 946742 | AF1-338 E | Adder | 1.11 MW | 0.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 946751 | AF1-339 C O1 | Adder | 1.67 MW | 1.42 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 946752 | AF1-339 E O1 | Adder | 1.11 MW | 0.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 946761 | AF1-271AC | Adder | 1.4 MW | 1.19 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 946762 | AF1-271AE | Adder | 0.94 MW | 0.8 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 957621 | AF2-056 C | 50/50 | 11.8 MW | 11.8 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 957622 | AF2-056 E | 50/50 | 6.08 MW | 6.08 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 964051 | AG1-259 C | Adder | 0.92 MW | 0.78 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 964052 | AG1-259 E | Adder | 1.26 MW | 1.07 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 964061 | AG1-260 C | Adder | 0.92 MW | 0.78 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 964062 | AG1-260 E | Adder | 1.26 MW | 1.07 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 957881 | AF2-082 C | Adder | 4.54 MW | 3.86 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 957882 | AF2-082 E | Adder | 3.02 MW | 2.57 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 957921 | AF2-086 C | 50/50 | 2.45 MW | 2.45 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 957922 | AF2-086 E | 50/50 | 1.62 MW | 1.62 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 958461 | AF2-140 | Adder | 4.34 MW | 3.69 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | 938392 | AE1-058_GEN1 | 50/50 | 107.62 MW | 107.62 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.27 MW | 0.27 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.23 MW | 0.23 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.47 MW | 0.47 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.14 MW | 0.14 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.1 MW | 0.1 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.33 MW | 0.33 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.14 MW | 0.14 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.59 MW | 0.59 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.67 MW | 0.67 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.15 MW | 0.15 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.17 MW | 0.17 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.2 MW | 5.2 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.71 MW | 0.71 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000923 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.15 MW | 0.15 MW |
| Details for AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 942281 | AE2-241 C | 50/50 | 1.74 MW | 1.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 942282 | AE2-241 E | 50/50 | 2.41 MW | 2.41 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 942561 | AE2-271 C | Adder | 8.91 MW | 7.58 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 942562 | AE2-271 E | Adder | 5.94 MW | 5.05 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 943721 | AF1-040 C | Adder | 0.14 MW | 0.12 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 943722 | AF1-040 E | Adder | 2.61 MW | 2.22 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 945611 | AF1-226 C | 50/50 | 3.05 MW | 3.05 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 945612 | AF1-226 E | 50/50 | 4.21 MW | 4.21 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 959421 | AF2-233 C | Adder | 1.65 MW | 1.4 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 959422 | AF2-233 E | Adder | 1.1 MW | 0.94 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 959431 | AF2-234 C | Adder | 3.3 MW | 2.8 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 959432 | AF2-234 E | Adder | 2.2 MW | 1.87 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 959932 | AF2-284 E | Adder | 0.29 MW | 0.24 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 959982 | AF2-289 E | Adder | 0.43 MW | 0.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 959992 | AF2-290 E | Adder | 0.28 MW | 0.24 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 960401 | AF2-331 C | Adder | 4.39 MW | 3.73 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 960402 | AF2-331 E | Adder | 2.92 MW | 2.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 960411 | AF2-332 C | Adder | 4.39 MW | 3.73 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 960412 | AF2-332 E | Adder | 2.92 MW | 2.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 960421 | AF2-333 C | Adder | 1.75 MW | 1.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 960422 | AF2-333 E | Adder | 1.17 MW | 0.99 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 960431 | AF2-334 C | Adder | 1.75 MW | 1.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 960432 | AF2-334 E | Adder | 1.17 MW | 0.99 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961331 | AF2-424 C | 50/50 | 3.43 MW | 3.43 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961332 | AF2-424 E | 50/50 | 2.28 MW | 2.28 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961341 | AF2-425 C | 50/50 | 3.43 MW | 3.43 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961342 | AF2-425 E | 50/50 | 2.28 MW | 2.28 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961362 | AF2-427 E | Adder | 0.43 MW | 0.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961412 | AF2-432 E | 50/50 | 0.41 MW | 0.41 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961421 | AF2-433 C O1 | 50/50 | 2.49 MW | 2.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961422 | AF2-433 E O1 | 50/50 | 1.66 MW | 1.66 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961431 | AF2-434 C O1 | 50/50 | 2.49 MW | 2.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961432 | AF2-434 E O1 | 50/50 | 1.66 MW | 1.66 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961531 | AF2-444 C | 50/50 | 3.37 MW | 3.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961532 | AF2-444 E | 50/50 | 2.28 MW | 2.28 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961541 | AF2-445AC | 50/50 | 4.22 MW | 4.22 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 961542 | AF2-445AE | 50/50 | 2.86 MW | 2.86 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 962061 | AG1-050 | Adder | 2.83 MW | 2.4 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 962151 | AG1-060 C | 50/50 | 7.34 MW | 7.34 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 962152 | AG1-060 E | 50/50 | 42.58 MW | 42.58 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 208941 | FISH CT | 50/50 | 1.71 MW | 1.71 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 208981 | FOWH IPP | 50/50 | 2.08 MW | 2.08 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 208982 | GLBT IPP | 50/50 | 5.0 MW | 5.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 209013 | SCEN IPP | 50/50 | 5.24 MW | 5.24 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 209021 | WEST IPP | 50/50 | 1.58 MW | 1.58 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 209022 | WHFR IPP | 50/50 | 15.38 MW | 15.38 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 209027 | LOR2_Q27 | 50/50 | 0.69 MW | 0.69 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 212099 | COLA IPP | 50/50 | 0.39 MW | 0.39 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 212174 | INGE | 50/50 | 0.3 MW | 0.3 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 212266 | LOR1 | 50/50 | 0.21 MW | 0.21 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 938393 | AE1-058_GEN2 | 50/50 | 107.61 MW | 107.61 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 939891 | AE1-225 C O1 | Adder | 1.29 MW | 1.1 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 939892 | AE1-225 E O1 | Adder | 1.43 MW | 1.22 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 940561 | AE2-042 C | Adder | 6.62 MW | 5.63 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 940562 | AE2-042 E | Adder | 3.28 MW | 2.79 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 940721 | AE2-059 C | Adder | 1.19 MW | 1.01 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 940722 | AE2-059 E | Adder | 1.64 MW | 1.39 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 940941 | AE2-084 C | Adder | 1.19 MW | 1.01 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 940942 | AE2-084 E | Adder | 1.64 MW | 1.39 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 941161 | AE2-110 C | 50/50 | 1.74 MW | 1.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 941162 | AE2-110 E | 50/50 | 2.41 MW | 2.41 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 941371 | AE2-133 C | Adder | 1.15 MW | 0.98 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 941372 | AE2-133 E | Adder | 1.59 MW | 1.35 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 946691 | AF1-333 C O1 | Adder | 1.67 MW | 1.42 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 946692 | AF1-333 E O1 | Adder | 1.11 MW | 0.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 946731 | AF1-337 C | Adder | 1.67 MW | 1.42 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 946732 | AF1-337 E | Adder | 1.11 MW | 0.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 946741 | AF1-338 C | Adder | 1.67 MW | 1.42 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 946742 | AF1-338 E | Adder | 1.11 MW | 0.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 946751 | AF1-339 C O1 | Adder | 1.67 MW | 1.42 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 946752 | AF1-339 E O1 | Adder | 1.11 MW | 0.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 946761 | AF1-271AC | Adder | 1.4 MW | 1.19 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 946762 | AF1-271AE | Adder | 0.94 MW | 0.8 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 957621 | AF2-056 C | 50/50 | 11.8 MW | 11.8 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 957622 | AF2-056 E | 50/50 | 6.08 MW | 6.08 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 964051 | AG1-259 C | Adder | 0.92 MW | 0.78 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 964052 | AG1-259 E | Adder | 1.26 MW | 1.07 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 964061 | AG1-260 C | Adder | 0.92 MW | 0.78 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 964062 | AG1-260 E | Adder | 1.26 MW | 1.07 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 957881 | AF2-082 C | Adder | 4.54 MW | 3.86 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 957882 | AF2-082 E | Adder | 3.02 MW | 2.57 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 957921 | AF2-086 C | 50/50 | 2.45 MW | 2.45 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 957922 | AF2-086 E | 50/50 | 1.62 MW | 1.62 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 958461 | AF2-140 | Adder | 4.34 MW | 3.69 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | 938392 | AE1-058_GEN1 | 50/50 | 107.61 MW | 107.61 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.27 MW | 0.27 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.23 MW | 0.23 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.47 MW | 0.47 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.14 MW | 0.14 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.1 MW | 0.1 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.33 MW | 0.33 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.14 MW | 0.14 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.59 MW | 0.59 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.67 MW | 0.67 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.15 MW | 0.15 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.17 MW | 0.17 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.2 MW | 5.2 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.71 MW | 0.71 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:18:P42:000922 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.15 MW | 0.15 MW |
| Details for JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 936991 | AD2-133 C | Adder | -1.23 MW | -1.05 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 942121 | AE2-224 C | Adder | -3.57 MW | -3.04 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 958871 | AF2-178 | Adder | -0.41 MW | -0.35 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 200852 | 26WARR RDG | Adder | -0.34 MW | -0.29 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 236828 | 01GRAYMONT | Adder | -0.65 MW | -0.55 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 941321 | AE2-126 C | Adder | -0.95 MW | -0.81 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 941331 | AE2-129 C | Adder | -1.0 MW | -0.85 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 205907 | AC1-048 C | Adder | -0.85 MW | -0.72 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 205909 | AC2-053 C | Adder | -0.48 MW | -0.41 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 933974 | AD1-020 C | Adder | -4.4 MW | -3.74 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 936921 | AD2-116 C O1 | Adder | -1.37 MW | -1.17 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 942281 | AE2-241 C | Adder | 0.57 MW | 0.48 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 942282 | AE2-241 E | Adder | 0.78 MW | 0.67 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 942561 | AE2-271 C | Adder | 4.24 MW | 3.6 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 942562 | AE2-271 E | Adder | 2.83 MW | 2.4 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 943721 | AF1-040 C | Adder | 0.08 MW | 0.07 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 943722 | AF1-040 E | Adder | 1.54 MW | 1.31 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 945611 | AF1-226 C | Adder | 0.99 MW | 0.84 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 945612 | AF1-226 E | Adder | 1.37 MW | 1.16 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959421 | AF2-233 C | Adder | 0.97 MW | 0.83 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959422 | AF2-233 E | Adder | 0.65 MW | 0.55 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959431 | AF2-234 C | Adder | 1.95 MW | 1.65 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959432 | AF2-234 E | Adder | 1.3 MW | 1.1 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959932 | AF2-284 E | Adder | 0.14 MW | 0.12 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959982 | AF2-289 E | Adder | 0.22 MW | 0.18 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959992 | AF2-290 E | Adder | 0.15 MW | 0.13 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 960401 | AF2-331 C | Adder | 2.09 MW | 1.77 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 960402 | AF2-331 E | Adder | 1.39 MW | 1.18 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 960411 | AF2-332 C | Adder | 2.09 MW | 1.77 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 960412 | AF2-332 E | Adder | 1.39 MW | 1.18 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 960421 | AF2-333 C | Adder | 0.84 MW | 0.71 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 960422 | AF2-333 E | Adder | 0.56 MW | 0.47 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 960431 | AF2-334 C | Adder | 0.84 MW | 0.71 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 960432 | AF2-334 E | Adder | 0.56 MW | 0.47 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961331 | AF2-424 C | Adder | 0.82 MW | 0.7 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961332 | AF2-424 E | Adder | 0.55 MW | 0.47 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961341 | AF2-425 C | Adder | 0.82 MW | 0.7 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961342 | AF2-425 E | Adder | 0.55 MW | 0.47 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961362 | AF2-427 E | Adder | 0.22 MW | 0.18 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961412 | AF2-432 E | Adder | 0.14 MW | 0.12 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961421 | AF2-433 C O1 | Adder | 0.81 MW | 0.69 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961422 | AF2-433 E O1 | Adder | 0.54 MW | 0.46 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961431 | AF2-434 C O1 | Adder | 0.81 MW | 0.69 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961432 | AF2-434 E O1 | Adder | 0.54 MW | 0.46 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961531 | AF2-444 C | Adder | 0.81 MW | 0.69 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961532 | AF2-444 E | Adder | 0.55 MW | 0.47 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961541 | AF2-445AC | Adder | 0.74 MW | 0.62 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 961542 | AF2-445AE | Adder | 0.5 MW | 0.42 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 962061 | AG1-050 | Adder | 1.52 MW | 1.29 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 962151 | AG1-060 C | Adder | 1.76 MW | 1.5 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 962152 | AG1-060 E | Adder | 10.23 MW | 8.7 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 208769 | SISO | Adder | -0.17 MW | -0.15 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 209022 | WHFR IPP | Adder | 2.68 MW | 2.28 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 939561 | AE1-185 C | Adder | -1.32 MW | -1.12 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 939661 | AE1-196 C | Adder | -1.33 MW | -1.13 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 939891 | AE1-225 C O1 | Adder | 0.76 MW | 0.65 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 939892 | AE1-225 E O1 | Adder | 0.84 MW | 0.72 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 940561 | AE2-042 C | Adder | 3.55 MW | 3.02 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 940562 | AE2-042 E | Adder | 1.76 MW | 1.5 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 940721 | AE2-059 C | Adder | 0.64 MW | 0.54 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 940722 | AE2-059 E | Adder | 0.88 MW | 0.75 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 940731 | AE2-060 C | Adder | -3.99 MW | -3.39 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 940941 | AE2-084 C | Adder | 0.64 MW | 0.54 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 940942 | AE2-084 E | Adder | 0.88 MW | 0.75 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 941161 | AE2-110 C | Adder | 0.57 MW | 0.48 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 941162 | AE2-110 E | Adder | 0.78 MW | 0.67 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 941371 | AE2-133 C | Adder | 0.68 MW | 0.58 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 941372 | AE2-133 E | Adder | 0.94 MW | 0.8 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 946691 | AF1-333 C O1 | Adder | 0.94 MW | 0.8 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 946692 | AF1-333 E O1 | Adder | 0.63 MW | 0.54 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 946731 | AF1-337 C | Adder | 0.94 MW | 0.8 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 946732 | AF1-337 E | Adder | 0.63 MW | 0.54 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 946741 | AF1-338 C | Adder | 0.94 MW | 0.8 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 946742 | AF1-338 E | Adder | 0.63 MW | 0.54 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 946751 | AF1-339 C O1 | Adder | 0.94 MW | 0.8 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 946752 | AF1-339 E O1 | Adder | 0.63 MW | 0.54 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 946761 | AF1-271AC | Adder | 0.83 MW | 0.7 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 946762 | AF1-271AE | Adder | 0.55 MW | 0.47 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 957621 | AF2-056 C | Adder | 2.06 MW | 1.75 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 957622 | AF2-056 E | Adder | 1.06 MW | 0.9 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 964051 | AG1-259 C | Adder | 0.54 MW | 0.46 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 964052 | AG1-259 E | Adder | 0.75 MW | 0.63 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 964061 | AG1-260 C | Adder | 0.54 MW | 0.46 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 964062 | AG1-260 E | Adder | 0.75 MW | 0.63 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 204784 | 27LMR_E02 | Adder | -0.14 MW | -0.12 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 957881 | AF2-082 C | Adder | 2.68 MW | 2.27 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 957882 | AF2-082 E | Adder | 1.78 MW | 1.52 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 957921 | AF2-086 C | Adder | 0.8 MW | 0.68 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 957922 | AF2-086 E | Adder | 0.53 MW | 0.45 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 958461 | AF2-140 | Adder | 2.15 MW | 1.83 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959973 | AF2-288 BAT | 50/50 | 0.71 MW | 0.71 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959963 | AF2-287 BAT | 50/50 | 0.71 MW | 0.71 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 960023 | AF2-293 BAT | 50/50 | 0.19 MW | 0.19 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 946423 | AF2-000A BAT | Adder | 18.49 MW | 15.72 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 235007 | AC1-025 BAT | 50/50 | 0.25 MW | 0.25 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 962413 | AG1-090 BAT | Adder | 4.91 MW | 4.18 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959803 | AF2-271 BAT | 50/50 | 0.18 MW | 0.18 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959873 | AF2-278 BAT | 50/50 | 0.41 MW | 0.41 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959773 | AF2-268 BAT | Adder | 0.14 MW | 0.12 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 966172 | AG1-486 BAT | Adder | 1.44 MW | 1.22 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 933977 | AD1-020 EBAT | Adder | 1.93 MW | 1.64 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 966132 | AG1-482 BAT | Adder | 1.98 MW | 1.68 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 962082 | AG1-052 BAT | 50/50 | 2.26 MW | 2.26 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 962092 | AG1-053 BAT | 50/50 | 2.27 MW | 2.27 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 960922 | AF2-383 BAT | 50/50 | 2.06 MW | 2.06 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959893 | AF2-280 BAT | Adder | 0.11 MW | 0.09 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959883 | AF2-279 BAT | Adder | 0.14 MW | 0.12 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 959813 | AF2-272 BAT | Adder | 0.12 MW | 0.1 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | 957363 | AF2-030 BAT | Adder | 1.48 MW | 1.25 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.25 MW | 0.25 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.07 MW | 0.07 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 1.07 MW | 1.07 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.03 MW | 0.03 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.03 MW | 3.03 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.92 MW | 0.92 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 2.53 MW | 2.53 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.16 MW | 0.16 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.09 MW | 0.09 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.12 MW | 0.12 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.26 MW | 0.26 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.06 MW | 0.06 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 8.1 MW | 8.1 MW |
| JUNIATA-JUNI BU2 500.0/230.0 kV Ckt 2 transformer l/o PL:11:P42:000140 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 942281 | AE2-241 C | Adder | 0.54 MW | 0.46 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 942282 | AE2-241 E | Adder | 0.74 MW | 0.63 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 942561 | AE2-271 C | Adder | 3.22 MW | 2.74 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 942562 | AE2-271 E | Adder | 2.15 MW | 1.82 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 945611 | AF1-226 C | Adder | 0.94 MW | 0.8 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 945612 | AF1-226 E | Adder | 1.3 MW | 1.11 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 959932 | AF2-284 E | Adder | 0.1 MW | 0.09 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 959982 | AF2-289 E | Adder | 0.15 MW | 0.13 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 960401 | AF2-331 C | Adder | 1.58 MW | 1.35 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 960402 | AF2-331 E | Adder | 1.06 MW | 0.9 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 960411 | AF2-332 C | Adder | 1.58 MW | 1.35 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 960412 | AF2-332 E | Adder | 1.06 MW | 0.9 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 960421 | AF2-333 C | Adder | 0.63 MW | 0.54 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 960422 | AF2-333 E | Adder | 0.42 MW | 0.36 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 960431 | AF2-334 C | Adder | 0.63 MW | 0.54 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 960432 | AF2-334 E | Adder | 0.42 MW | 0.36 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961301 | AF2-421 C | Adder | 1.13 MW | 0.96 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961302 | AF2-421 E | Adder | 0.75 MW | 0.64 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961331 | AF2-424 C | Adder | 0.89 MW | 0.76 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961332 | AF2-424 E | Adder | 0.6 MW | 0.51 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961341 | AF2-425 C | Adder | 0.89 MW | 0.76 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961342 | AF2-425 E | Adder | 0.6 MW | 0.51 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961362 | AF2-427 E | Adder | 0.15 MW | 0.13 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961412 | AF2-432 E | Adder | 0.13 MW | 0.11 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961421 | AF2-433 C O1 | Adder | 0.77 MW | 0.65 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961422 | AF2-433 E O1 | Adder | 0.51 MW | 0.44 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961431 | AF2-434 C O1 | Adder | 0.77 MW | 0.65 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961432 | AF2-434 E O1 | Adder | 0.51 MW | 0.44 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961531 | AF2-444 C | Adder | 0.88 MW | 0.75 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961532 | AF2-444 E | Adder | 0.6 MW | 0.51 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961541 | AF2-445AC | Adder | 1.08 MW | 0.92 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 961542 | AF2-445AE | Adder | 0.73 MW | 0.62 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 962151 | AG1-060 C | Adder | 1.91 MW | 1.63 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 962152 | AG1-060 E | Adder | 11.1 MW | 9.44 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 964171 | AG1-278 C | Adder | 1.45 MW | 1.23 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 964172 | AG1-278 E | Adder | 0.43 MW | 0.37 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 209006 | NEPC IPP | Adder | 2.26 MW | 1.92 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 209022 | WHFR IPP | Adder | 3.94 MW | 3.35 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 211065 | PSPA IPP | 50/50 | 2.0 MW | 2.0 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 211375 | BEAC | Adder | 1.88 MW | 1.6 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 938393 | AE1-058_GEN2 | 50/50 | 26.67 MW | 26.67 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 940592 | AE2-046 E | Adder | 2.45 MW | 2.08 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 941161 | AE2-110 C | Adder | 0.54 MW | 0.46 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 941162 | AE2-110 E | Adder | 0.74 MW | 0.63 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 957621 | AF2-056 C | Adder | 3.02 MW | 2.57 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 957622 | AF2-056 E | Adder | 1.56 MW | 1.32 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 963151 | AG1-164 C | Adder | 1.13 MW | 0.96 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 963152 | AG1-164 E | Adder | 0.75 MW | 0.64 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 963161 | AG1-165 C | Adder | 1.13 MW | 0.96 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 963162 | AG1-165 E | Adder | 0.75 MW | 0.64 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 964161 | AG1-277 C | Adder | 3.01 MW | 2.56 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 964162 | AG1-277 E | Adder | 0.75 MW | 0.64 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 964181 | AG1-279 C | Adder | 1.45 MW | 1.23 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 964182 | AG1-279 E | Adder | 0.43 MW | 0.37 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 957921 | AF2-086 C | Adder | 0.76 MW | 0.64 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 957922 | AF2-086 E | Adder | 0.5 MW | 0.42 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 958461 | AF2-140 | Adder | 1.51 MW | 1.29 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 966291 | AG1-498 C | Adder | 0.22 MW | 0.19 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 966292 | AG1-498 E | Adder | 0.31 MW | 0.26 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | 938392 | AE1-058_GEN1 | 50/50 | 26.67 MW | 26.67 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.08 MW | 0.08 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.1 MW | 0.1 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.14 MW | 0.14 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.05 MW | 0.05 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.1 MW | 0.1 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.58 MW | 0.58 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.07 MW | 0.07 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.11 MW | 2.11 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| SIEG-SIEG 230.0/138.0 kV Ckt 4 transformer l/o PL:20:P42:102406 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| Details for AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 942281 | AE2-241 C | 50/50 | 1.45 MW | 1.45 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 942282 | AE2-241 E | 50/50 | 2.01 MW | 2.01 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 942561 | AE2-271 C | Adder | 7.1 MW | 6.03 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 942562 | AE2-271 E | Adder | 4.73 MW | 4.02 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 943721 | AF1-040 C | Adder | 0.09 MW | 0.08 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 943722 | AF1-040 E | Adder | 1.77 MW | 1.5 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 945611 | AF1-226 C | 50/50 | 2.54 MW | 2.54 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 945612 | AF1-226 E | 50/50 | 3.51 MW | 3.51 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959421 | AF2-233 C | Adder | 1.12 MW | 0.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959422 | AF2-233 E | Adder | 0.74 MW | 0.63 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959431 | AF2-234 C | Adder | 2.23 MW | 1.9 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959432 | AF2-234 E | Adder | 1.49 MW | 1.26 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959932 | AF2-284 E | Adder | 0.22 MW | 0.19 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959982 | AF2-289 E | Adder | 0.33 MW | 0.28 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959992 | AF2-290 E | Adder | 0.21 MW | 0.18 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960401 | AF2-331 C | Adder | 3.49 MW | 2.97 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960402 | AF2-331 E | Adder | 2.33 MW | 1.98 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960411 | AF2-332 C | Adder | 3.49 MW | 2.97 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960412 | AF2-332 E | Adder | 2.33 MW | 1.98 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960421 | AF2-333 C | Adder | 1.4 MW | 1.19 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960422 | AF2-333 E | Adder | 0.93 MW | 0.79 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960431 | AF2-334 C | Adder | 1.4 MW | 1.19 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960432 | AF2-334 E | Adder | 0.93 MW | 0.79 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961331 | AF2-424 C | 50/50 | 2.87 MW | 2.87 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961332 | AF2-424 E | 50/50 | 1.92 MW | 1.92 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961341 | AF2-425 C | 50/50 | 2.87 MW | 2.87 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961342 | AF2-425 E | 50/50 | 1.92 MW | 1.92 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961362 | AF2-427 E | Adder | 0.33 MW | 0.28 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961412 | AF2-432 E | 50/50 | 0.35 MW | 0.35 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961421 | AF2-433 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961422 | AF2-433 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961431 | AF2-434 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961432 | AF2-434 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961531 | AF2-444 C | 50/50 | 2.82 MW | 2.82 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961532 | AF2-444 E | 50/50 | 1.92 MW | 1.92 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961541 | AF2-445AC | 50/50 | 3.67 MW | 3.67 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961542 | AF2-445AE | 50/50 | 2.49 MW | 2.49 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 962061 | AG1-050 | Adder | 2.07 MW | 1.76 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 962151 | AG1-060 C | 50/50 | 6.15 MW | 6.15 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 962152 | AG1-060 E | 50/50 | 35.68 MW | 35.68 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 208941 | FISH CT | 50/50 | 1.48 MW | 1.48 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 208981 | FOWH IPP | 50/50 | 1.74 MW | 1.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 208982 | GLBT IPP | 50/50 | 4.34 MW | 4.34 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 209013 | SCEN IPP | 50/50 | 4.55 MW | 4.55 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 209021 | WEST IPP | 50/50 | 1.32 MW | 1.32 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 209022 | WHFR IPP | 50/50 | 13.37 MW | 13.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 209027 | LOR2_Q27 | 50/50 | 0.6 MW | 0.6 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 211375 | BEAC | Adder | -3.3 MW | -2.81 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 212099 | COLA IPP | 50/50 | 0.33 MW | 0.33 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 212174 | INGE | 50/50 | 0.25 MW | 0.25 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 212266 | LOR1 | 50/50 | 0.19 MW | 0.19 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 938393 | AE1-058_GEN2 | 50/50 | 95.04 MW | 95.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 939891 | AE1-225 C O1 | Adder | 0.87 MW | 0.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 939892 | AE1-225 E O1 | Adder | 0.97 MW | 0.82 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940561 | AE2-042 C | Adder | 4.85 MW | 4.12 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940562 | AE2-042 E | Adder | 2.4 MW | 2.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940721 | AE2-059 C | Adder | 0.87 MW | 0.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940722 | AE2-059 E | Adder | 1.2 MW | 1.02 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940941 | AE2-084 C | Adder | 0.87 MW | 0.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940942 | AE2-084 E | Adder | 1.2 MW | 1.02 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 941161 | AE2-110 C | 50/50 | 1.45 MW | 1.45 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 941162 | AE2-110 E | 50/50 | 2.01 MW | 2.01 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 941371 | AE2-133 C | Adder | 0.78 MW | 0.66 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 941372 | AE2-133 E | Adder | 1.08 MW | 0.92 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946691 | AF1-333 C O1 | Adder | 1.17 MW | 1.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946692 | AF1-333 E O1 | Adder | 0.78 MW | 0.67 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946731 | AF1-337 C | Adder | 1.17 MW | 1.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946732 | AF1-337 E | Adder | 0.78 MW | 0.67 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946741 | AF1-338 C | Adder | 1.17 MW | 1.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946742 | AF1-338 E | Adder | 0.78 MW | 0.67 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946751 | AF1-339 C O1 | Adder | 1.17 MW | 1.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946752 | AF1-339 E O1 | Adder | 0.78 MW | 0.67 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946761 | AF1-271AC | Adder | 0.95 MW | 0.81 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946762 | AF1-271AE | Adder | 0.63 MW | 0.54 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957621 | AF2-056 C | 50/50 | 10.26 MW | 10.26 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957622 | AF2-056 E | 50/50 | 5.29 MW | 5.29 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964051 | AG1-259 C | Adder | 0.62 MW | 0.53 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964052 | AG1-259 E | Adder | 0.86 MW | 0.73 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964061 | AG1-260 C | Adder | 0.62 MW | 0.53 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964062 | AG1-260 E | Adder | 0.86 MW | 0.73 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957881 | AF2-082 C | Adder | 3.07 MW | 2.61 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957882 | AF2-082 E | Adder | 2.04 MW | 1.74 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957921 | AF2-086 C | 50/50 | 2.04 MW | 2.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957922 | AF2-086 E | 50/50 | 1.35 MW | 1.35 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 958461 | AF2-140 | Adder | 3.37 MW | 2.86 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 938392 | AE1-058_GEN1 | 50/50 | 95.04 MW | 95.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964183 | AG1-279 BAT | 50/50 | 0.56 MW | 0.56 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964173 | AG1-278 BAT | 50/50 | 0.56 MW | 0.56 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940593 | AE2-046 BAT | 50/50 | 4.95 MW | 4.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 211369 | W1-111 BAT | 50/50 | 3.3 MW | 3.3 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964163 | AG1-277 BAT | 50/50 | 3.3 MW | 3.3 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.21 MW | 1.21 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.83 MW | 2.83 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.58 MW | 1.58 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.05 MW | 2.05 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.29 MW | 0.29 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.12 MW | 0.12 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.3 MW | 0.3 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 15.68 MW | 15.68 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.23 MW | 0.23 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 942281 | AE2-241 C | 50/50 | 1.84 MW | 1.84 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 942282 | AE2-241 E | 50/50 | 2.54 MW | 2.54 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 942561 | AE2-271 C | Adder | 10.08 MW | 8.57 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 942562 | AE2-271 E | Adder | 6.72 MW | 5.71 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 943721 | AF1-040 C | Adder | 0.11 MW | 0.09 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 943722 | AF1-040 E | Adder | 2.09 MW | 1.78 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 945611 | AF1-226 C | 50/50 | 3.22 MW | 3.22 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 945612 | AF1-226 E | 50/50 | 4.44 MW | 4.44 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 959421 | AF2-233 C | Adder | 1.32 MW | 1.12 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 959422 | AF2-233 E | Adder | 0.88 MW | 0.75 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 959431 | AF2-234 C | Adder | 2.64 MW | 2.25 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 959432 | AF2-234 E | Adder | 1.76 MW | 1.5 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 959932 | AF2-284 E | Adder | 0.31 MW | 0.26 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 959982 | AF2-289 E | Adder | 0.46 MW | 0.39 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 959992 | AF2-290 E | Adder | 0.27 MW | 0.23 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 960401 | AF2-331 C | Adder | 4.96 MW | 4.22 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 960402 | AF2-331 E | Adder | 3.31 MW | 2.81 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 960411 | AF2-332 C | Adder | 4.96 MW | 4.22 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 960412 | AF2-332 E | Adder | 3.31 MW | 2.81 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 960421 | AF2-333 C | Adder | 1.98 MW | 1.69 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 960422 | AF2-333 E | Adder | 1.32 MW | 1.12 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 960431 | AF2-334 C | Adder | 1.98 MW | 1.69 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 960432 | AF2-334 E | Adder | 1.32 MW | 1.12 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961331 | AF2-424 C | 50/50 | 3.25 MW | 3.25 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961332 | AF2-424 E | 50/50 | 2.16 MW | 2.16 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961341 | AF2-425 C | 50/50 | 3.25 MW | 3.25 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961342 | AF2-425 E | 50/50 | 2.16 MW | 2.16 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961362 | AF2-427 E | Adder | 0.46 MW | 0.39 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961412 | AF2-432 E | 50/50 | 0.44 MW | 0.44 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961421 | AF2-433 C O1 | 50/50 | 2.63 MW | 2.63 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961422 | AF2-433 E O1 | 50/50 | 1.75 MW | 1.75 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961431 | AF2-434 C O1 | 50/50 | 2.63 MW | 2.63 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961432 | AF2-434 E O1 | 50/50 | 1.75 MW | 1.75 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961531 | AF2-444 C | 50/50 | 3.19 MW | 3.19 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961532 | AF2-444 E | 50/50 | 2.16 MW | 2.16 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961541 | AF2-445AC | 50/50 | 4.12 MW | 4.12 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 961542 | AF2-445AE | 50/50 | 2.79 MW | 2.79 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 962061 | AG1-050 | Adder | 2.7 MW | 2.3 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 962151 | AG1-060 C | 50/50 | 6.95 MW | 6.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 962152 | AG1-060 E | 50/50 | 40.31 MW | 40.31 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 208941 | FISH CT | 50/50 | 1.67 MW | 1.67 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 208981 | FOWH IPP | 50/50 | 1.97 MW | 1.97 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 208982 | GLBT IPP | 50/50 | 4.88 MW | 4.88 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 209013 | SCEN IPP | 50/50 | 5.12 MW | 5.12 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 209021 | WEST IPP | 50/50 | 1.5 MW | 1.5 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 209022 | WHFR IPP | 50/50 | 15.02 MW | 15.02 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 209027 | LOR2_Q27 | 50/50 | 0.68 MW | 0.68 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 212099 | COLA IPP | 50/50 | 0.37 MW | 0.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 212174 | INGE | 50/50 | 0.28 MW | 0.28 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 212266 | LOR1 | 50/50 | 0.21 MW | 0.21 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 938393 | AE1-058_GEN2 | 50/50 | 104.96 MW | 104.96 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 939891 | AE1-225 C O1 | Adder | 1.03 MW | 0.88 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 939892 | AE1-225 E O1 | Adder | 1.14 MW | 0.97 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 940561 | AE2-042 C | Adder | 6.32 MW | 5.37 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 940562 | AE2-042 E | Adder | 3.13 MW | 2.66 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 940721 | AE2-059 C | Adder | 1.14 MW | 0.96 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 940722 | AE2-059 E | Adder | 1.57 MW | 1.33 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 940941 | AE2-084 C | Adder | 1.14 MW | 0.96 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 940942 | AE2-084 E | Adder | 1.57 MW | 1.33 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 941161 | AE2-110 C | 50/50 | 1.84 MW | 1.84 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 941162 | AE2-110 E | 50/50 | 2.54 MW | 2.54 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 941371 | AE2-133 C | Adder | 0.92 MW | 0.79 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 941372 | AE2-133 E | Adder | 1.28 MW | 1.08 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 946691 | AF1-333 C O1 | Adder | 1.46 MW | 1.24 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 946692 | AF1-333 E O1 | Adder | 0.97 MW | 0.82 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 946731 | AF1-337 C | Adder | 1.46 MW | 1.24 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 946732 | AF1-337 E | Adder | 0.97 MW | 0.82 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 946741 | AF1-338 C | Adder | 1.46 MW | 1.24 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 946742 | AF1-338 E | Adder | 0.97 MW | 0.82 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 946751 | AF1-339 C O1 | Adder | 1.46 MW | 1.24 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 946752 | AF1-339 E O1 | Adder | 0.97 MW | 0.82 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 946761 | AF1-271AC | Adder | 1.12 MW | 0.95 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 946762 | AF1-271AE | Adder | 0.75 MW | 0.64 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 957621 | AF2-056 C | 50/50 | 11.53 MW | 11.53 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 957622 | AF2-056 E | 50/50 | 5.94 MW | 5.94 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 964051 | AG1-259 C | Adder | 0.74 MW | 0.63 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 964052 | AG1-259 E | Adder | 1.01 MW | 0.86 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 964061 | AG1-260 C | Adder | 0.74 MW | 0.63 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 964062 | AG1-260 E | Adder | 1.01 MW | 0.86 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 957881 | AF2-082 C | Adder | 3.63 MW | 3.09 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 957882 | AF2-082 E | Adder | 2.42 MW | 2.06 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 957921 | AF2-086 C | 50/50 | 2.58 MW | 2.58 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 957922 | AF2-086 E | 50/50 | 1.71 MW | 1.71 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 958461 | AF2-140 | Adder | 4.67 MW | 3.97 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | 938392 | AE1-058_GEN1 | 50/50 | 104.96 MW | 104.96 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.03 MW | 0.03 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.82 MW | 0.82 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.0 MW | 2.0 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.11 MW | 1.11 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.04 MW | 0.04 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.87 MW | 1.87 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.2 MW | 0.2 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.21 MW | 0.21 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.59 MW | 0.59 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 14.17 MW | 14.17 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.16 MW | 0.16 MW |
| AE1-058_TAP-SIEG 230.0 kV Ckt 1 line l/o PL:08:P71:101751 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 942281 | AE2-241 C | 50/50 | 2.52 MW | 2.52 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 942282 | AE2-241 E | 50/50 | 3.48 MW | 3.48 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 942561 | AE2-271 C | 50/50 | 21.17 MW | 21.17 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 942562 | AE2-271 E | 50/50 | 14.11 MW | 14.11 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 943721 | AF1-040 C | Adder | 0.16 MW | 0.13 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 943722 | AF1-040 E | Adder | 2.99 MW | 2.54 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 945611 | AF1-226 C | 50/50 | 4.4 MW | 4.4 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 945612 | AF1-226 E | 50/50 | 6.08 MW | 6.08 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959421 | AF2-233 C | Adder | 1.89 MW | 1.6 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959422 | AF2-233 E | Adder | 1.26 MW | 1.07 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959431 | AF2-234 C | Adder | 3.77 MW | 3.21 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959432 | AF2-234 E | Adder | 2.52 MW | 2.14 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959932 | AF2-284 E | 50/50 | 0.61 MW | 0.61 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959982 | AF2-289 E | 50/50 | 0.92 MW | 0.92 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959992 | AF2-290 E | 50/50 | 0.49 MW | 0.49 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960401 | AF2-331 C | 50/50 | 10.42 MW | 10.42 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960402 | AF2-331 E | 50/50 | 6.95 MW | 6.95 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960411 | AF2-332 C | 50/50 | 10.42 MW | 10.42 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960412 | AF2-332 E | 50/50 | 6.95 MW | 6.95 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960421 | AF2-333 C | 50/50 | 4.17 MW | 4.17 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960422 | AF2-333 E | 50/50 | 2.78 MW | 2.78 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960431 | AF2-334 C | 50/50 | 4.17 MW | 4.17 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960432 | AF2-334 E | 50/50 | 2.78 MW | 2.78 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961331 | AF2-424 C | Adder | 2.06 MW | 1.75 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961332 | AF2-424 E | Adder | 1.37 MW | 1.17 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961341 | AF2-425 C | Adder | 2.06 MW | 1.75 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961342 | AF2-425 E | Adder | 1.37 MW | 1.17 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961362 | AF2-427 E | 50/50 | 0.92 MW | 0.92 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961412 | AF2-432 E | 50/50 | 0.6 MW | 0.6 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961421 | AF2-433 C O1 | 50/50 | 3.6 MW | 3.6 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961422 | AF2-433 E O1 | 50/50 | 2.4 MW | 2.4 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961431 | AF2-434 C O1 | 50/50 | 3.6 MW | 3.6 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961432 | AF2-434 E O1 | 50/50 | 2.4 MW | 2.4 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961531 | AF2-444 C | Adder | 2.03 MW | 1.72 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961532 | AF2-444 E | Adder | 1.37 MW | 1.17 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961541 | AF2-445AC | Adder | 2.15 MW | 1.83 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961542 | AF2-445AE | Adder | 1.46 MW | 1.24 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 962061 | AG1-050 | 50/50 | 4.87 MW | 4.87 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 962151 | AG1-060 C | Adder | 4.41 MW | 3.75 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 962152 | AG1-060 E | Adder | 25.61 MW | 21.77 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 208911 | MONT G1 | 50/50 | 44.87 MW | 44.87 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 208912 | MONT G2 | 50/50 | 44.83 MW | 44.83 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 208945 | LOHA CT | 50/50 | 0.63 MW | 0.63 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 208948 | WILL CT | 50/50 | 1.32 MW | 1.32 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 209013 | SCEN IPP | 50/50 | 2.67 MW | 2.67 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 209022 | WHFR IPP | Adder | 7.85 MW | 6.67 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 211375 | BEAC | Adder | -2.46 MW | -2.09 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 212005 | ALWD | 50/50 | 0.15 MW | 0.15 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 938393 | AE1-058_GEN2 | Adder | 38.8 MW | 32.98 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 939891 | AE1-225 C O1 | Adder | 1.48 MW | 1.26 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 939892 | AE1-225 E O1 | Adder | 1.64 MW | 1.39 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940561 | AE2-042 C | 50/50 | 11.39 MW | 11.39 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940562 | AE2-042 E | 50/50 | 5.64 MW | 5.64 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940721 | AE2-059 C | 50/50 | 2.04 MW | 2.04 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940722 | AE2-059 E | 50/50 | 2.82 MW | 2.82 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940941 | AE2-084 C | 50/50 | 2.04 MW | 2.04 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940942 | AE2-084 E | 50/50 | 2.82 MW | 2.82 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 941161 | AE2-110 C | 50/50 | 2.52 MW | 2.52 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 941162 | AE2-110 E | 50/50 | 3.48 MW | 3.48 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 941371 | AE2-133 C | Adder | 1.32 MW | 1.12 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 941372 | AE2-133 E | Adder | 1.82 MW | 1.55 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946691 | AF1-333 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946692 | AF1-333 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946731 | AF1-337 C | 50/50 | 2.35 MW | 2.35 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946732 | AF1-337 E | 50/50 | 1.57 MW | 1.57 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946741 | AF1-338 C | 50/50 | 2.35 MW | 2.35 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946742 | AF1-338 E | 50/50 | 1.57 MW | 1.57 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946751 | AF1-339 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946752 | AF1-339 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946761 | AF1-271AC | Adder | 1.6 MW | 1.36 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946762 | AF1-271AE | Adder | 1.07 MW | 0.91 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957621 | AF2-056 C | Adder | 6.02 MW | 5.12 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957622 | AF2-056 E | Adder | 3.1 MW | 2.64 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964051 | AG1-259 C | Adder | 1.05 MW | 0.9 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964052 | AG1-259 E | Adder | 1.45 MW | 1.23 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964061 | AG1-260 C | Adder | 1.05 MW | 0.9 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964062 | AG1-260 E | Adder | 1.45 MW | 1.23 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 212369 | PATRIOT 1 | 50/50 | 20.43 MW | 20.43 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 212370 | PATRIOT 2 | 50/50 | 20.43 MW | 20.43 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 212435 | SMIL | 50/50 | 0.08 MW | 0.08 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957881 | AF2-082 C | Adder | 5.19 MW | 4.41 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957882 | AF2-082 E | Adder | 3.46 MW | 2.94 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957921 | AF2-086 C | 50/50 | 3.54 MW | 3.54 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957922 | AF2-086 E | 50/50 | 2.34 MW | 2.34 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 958461 | AF2-140 | 50/50 | 9.41 MW | 9.41 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 938392 | AE1-058_GEN1 | Adder | 38.8 MW | 32.98 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964183 | AG1-279 BAT | Adder | 0.49 MW | 0.42 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964173 | AG1-278 BAT | Adder | 0.49 MW | 0.42 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940593 | AE2-046 BAT | Adder | 4.33 MW | 3.68 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 211369 | W1-111 BAT | Adder | 2.89 MW | 2.46 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964163 | AG1-277 BAT | Adder | 2.89 MW | 2.46 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 923674 | AB1-182 BAT | Adder | 3.02 MW | 2.57 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959923 | AF2-283 BAT | Adder | 0.13 MW | 0.11 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959943 | AF2-285 BAT | Adder | 0.13 MW | 0.11 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.08 MW | 0.08 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.08 MW | 0.08 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.14 MW | 0.14 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.05 MW | 0.05 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.72 MW | 1.72 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.06 MW | 0.06 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.3 MW | 1.3 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 12.76 MW | 12.76 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.22 MW | 0.22 MW |
| GLBR-SU10 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| Details for SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 942281 | AE2-241 C | 50/50 | 2.01 MW | 2.01 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 942282 | AE2-241 E | 50/50 | 2.78 MW | 2.78 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 942561 | AE2-271 C | 50/50 | 17.18 MW | 17.18 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 942562 | AE2-271 E | 50/50 | 11.45 MW | 11.45 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 943721 | AF1-040 C | Adder | 0.12 MW | 0.1 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 943722 | AF1-040 E | Adder | 2.2 MW | 1.87 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 945611 | AF1-226 C | 50/50 | 3.52 MW | 3.52 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 945612 | AF1-226 E | 50/50 | 4.87 MW | 4.87 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959421 | AF2-233 C | Adder | 1.39 MW | 1.18 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959422 | AF2-233 E | Adder | 0.93 MW | 0.79 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959431 | AF2-234 C | Adder | 2.78 MW | 2.36 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959432 | AF2-234 E | Adder | 1.85 MW | 1.57 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959932 | AF2-284 E | 50/50 | 0.49 MW | 0.49 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959982 | AF2-289 E | 50/50 | 0.74 MW | 0.74 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 959992 | AF2-290 E | 50/50 | 0.38 MW | 0.38 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960401 | AF2-331 C | 50/50 | 8.45 MW | 8.45 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960402 | AF2-331 E | 50/50 | 5.64 MW | 5.64 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960411 | AF2-332 C | 50/50 | 8.45 MW | 8.45 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960412 | AF2-332 E | 50/50 | 5.64 MW | 5.64 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960421 | AF2-333 C | 50/50 | 3.38 MW | 3.38 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960422 | AF2-333 E | 50/50 | 2.25 MW | 2.25 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960431 | AF2-334 C | 50/50 | 3.38 MW | 3.38 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 960432 | AF2-334 E | 50/50 | 2.25 MW | 2.25 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961331 | AF2-424 C | Adder | 1.53 MW | 1.3 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961332 | AF2-424 E | Adder | 1.02 MW | 0.87 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961341 | AF2-425 C | Adder | 1.53 MW | 1.3 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961342 | AF2-425 E | Adder | 1.02 MW | 0.87 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961362 | AF2-427 E | 50/50 | 0.74 MW | 0.74 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961412 | AF2-432 E | 50/50 | 0.48 MW | 0.48 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961421 | AF2-433 C O1 | 50/50 | 2.88 MW | 2.88 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961422 | AF2-433 E O1 | 50/50 | 1.92 MW | 1.92 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961431 | AF2-434 C O1 | 50/50 | 2.88 MW | 2.88 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961432 | AF2-434 E O1 | 50/50 | 1.92 MW | 1.92 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961531 | AF2-444 C | Adder | 1.5 MW | 1.28 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961532 | AF2-444 E | Adder | 1.02 MW | 0.87 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961541 | AF2-445AC | Adder | 1.61 MW | 1.37 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 961542 | AF2-445AE | Adder | 1.09 MW | 0.93 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 962061 | AG1-050 | 50/50 | 3.82 MW | 3.82 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 962151 | AG1-060 C | Adder | 3.28 MW | 2.78 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 962152 | AG1-060 E | Adder | 19.0 MW | 16.15 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 208911 | MONT G1 | 50/50 | 36.4 MW | 36.4 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 208912 | MONT G2 | 50/50 | 36.38 MW | 36.38 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 208945 | LOHA CT | 50/50 | 0.5 MW | 0.5 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 208948 | WILL CT | 50/50 | 1.05 MW | 1.05 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 209013 | SCEN IPP | 50/50 | 2.0 MW | 2.0 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 209022 | WHFR IPP | Adder | 5.86 MW | 4.99 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 211375 | BEAC | Adder | -3.57 MW | -3.04 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 212005 | ALWD | 50/50 | 0.12 MW | 0.12 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 234311 | HUN GEN5 | 50/50 | 1.47 MW | 1.47 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 234312 | HUN GEN6 | 50/50 | 1.46 MW | 1.46 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 938393 | AE1-058_GEN2 | Adder | 28.02 MW | 23.81 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 939891 | AE1-225 C O1 | Adder | 1.09 MW | 0.93 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 939892 | AE1-225 E O1 | Adder | 1.2 MW | 1.02 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940561 | AE2-042 C | 50/50 | 8.94 MW | 8.94 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940562 | AE2-042 E | 50/50 | 4.43 MW | 4.43 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940721 | AE2-059 C | 50/50 | 1.6 MW | 1.6 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940722 | AE2-059 E | 50/50 | 2.21 MW | 2.21 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940941 | AE2-084 C | 50/50 | 1.6 MW | 1.6 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940942 | AE2-084 E | 50/50 | 2.21 MW | 2.21 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 941161 | AE2-110 C | 50/50 | 2.01 MW | 2.01 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 941162 | AE2-110 E | 50/50 | 2.78 MW | 2.78 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 941371 | AE2-133 C | Adder | 0.97 MW | 0.83 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 941372 | AE2-133 E | Adder | 1.34 MW | 1.14 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946691 | AF1-333 C O1 | 50/50 | 1.79 MW | 1.79 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946692 | AF1-333 E O1 | 50/50 | 1.2 MW | 1.2 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946731 | AF1-337 C | 50/50 | 1.79 MW | 1.79 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946732 | AF1-337 E | 50/50 | 1.2 MW | 1.2 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946741 | AF1-338 C | 50/50 | 1.79 MW | 1.79 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946742 | AF1-338 E | 50/50 | 1.2 MW | 1.2 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946751 | AF1-339 C O1 | 50/50 | 1.79 MW | 1.79 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946752 | AF1-339 E O1 | 50/50 | 1.2 MW | 1.2 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946761 | AF1-271AC | Adder | 1.18 MW | 1.0 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 946762 | AF1-271AE | Adder | 0.79 MW | 0.67 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957621 | AF2-056 C | Adder | 4.5 MW | 3.83 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957622 | AF2-056 E | Adder | 2.32 MW | 1.97 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964051 | AG1-259 C | Adder | 0.78 MW | 0.66 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964052 | AG1-259 E | Adder | 1.06 MW | 0.91 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964061 | AG1-260 C | Adder | 0.78 MW | 0.66 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964062 | AG1-260 E | Adder | 1.06 MW | 0.91 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 212369 | PATRIOT 1 | 50/50 | 16.44 MW | 16.44 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 212370 | PATRIOT 2 | 50/50 | 16.44 MW | 16.44 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 212435 | SMIL | 50/50 | 0.07 MW | 0.07 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957881 | AF2-082 C | Adder | 3.82 MW | 3.25 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957882 | AF2-082 E | Adder | 2.55 MW | 2.17 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957921 | AF2-086 C | 50/50 | 2.83 MW | 2.83 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 957922 | AF2-086 E | 50/50 | 1.87 MW | 1.87 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 958461 | AF2-140 | 50/50 | 7.57 MW | 7.57 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 938392 | AE1-058_GEN1 | Adder | 28.02 MW | 23.81 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964183 | AG1-279 BAT | 50/50 | 0.61 MW | 0.61 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964173 | AG1-278 BAT | 50/50 | 0.61 MW | 0.61 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 940593 | AE2-046 BAT | 50/50 | 5.36 MW | 5.36 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 211369 | W1-111 BAT | 50/50 | 3.57 MW | 3.57 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | 964163 | AG1-277 BAT | 50/50 | 3.57 MW | 3.57 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.07 MW | 0.07 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.1 MW | 0.1 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.12 MW | 0.12 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.05 MW | 0.05 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.04 MW | 0.04 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.18 MW | 0.18 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.55 MW | 1.55 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.08 MW | 0.08 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.46 MW | 0.46 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 10.84 MW | 10.84 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.2 MW | 0.2 MW |
| SU10-SUSQ 230.0 kV Ckt 1 line l/o PL:48:P71:102649 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| Details for FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 942281 | AE2-241 C | 50/50 | 1.45 MW | 1.45 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 942282 | AE2-241 E | 50/50 | 2.01 MW | 2.01 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 942561 | AE2-271 C | Adder | 7.1 MW | 6.03 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 942562 | AE2-271 E | Adder | 4.73 MW | 4.02 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 943721 | AF1-040 C | Adder | 0.09 MW | 0.08 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 943722 | AF1-040 E | Adder | 1.77 MW | 1.5 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 945611 | AF1-226 C | 50/50 | 2.54 MW | 2.54 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 945612 | AF1-226 E | 50/50 | 3.51 MW | 3.51 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959421 | AF2-233 C | Adder | 1.12 MW | 0.95 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959422 | AF2-233 E | Adder | 0.74 MW | 0.63 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959431 | AF2-234 C | Adder | 2.23 MW | 1.9 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959432 | AF2-234 E | Adder | 1.49 MW | 1.26 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959932 | AF2-284 E | Adder | 0.22 MW | 0.19 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959982 | AF2-289 E | Adder | 0.33 MW | 0.28 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 959992 | AF2-290 E | Adder | 0.21 MW | 0.18 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960401 | AF2-331 C | Adder | 3.49 MW | 2.97 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960402 | AF2-331 E | Adder | 2.33 MW | 1.98 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960411 | AF2-332 C | Adder | 3.49 MW | 2.97 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960412 | AF2-332 E | Adder | 2.33 MW | 1.98 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960421 | AF2-333 C | Adder | 1.4 MW | 1.19 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960422 | AF2-333 E | Adder | 0.93 MW | 0.79 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960431 | AF2-334 C | Adder | 1.4 MW | 1.19 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 960432 | AF2-334 E | Adder | 0.93 MW | 0.79 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961331 | AF2-424 C | 50/50 | 2.87 MW | 2.87 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961332 | AF2-424 E | 50/50 | 1.92 MW | 1.92 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961341 | AF2-425 C | 50/50 | 2.87 MW | 2.87 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961342 | AF2-425 E | 50/50 | 1.92 MW | 1.92 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961362 | AF2-427 E | Adder | 0.33 MW | 0.28 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961412 | AF2-432 E | 50/50 | 0.35 MW | 0.35 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961421 | AF2-433 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961422 | AF2-433 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961431 | AF2-434 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961432 | AF2-434 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961531 | AF2-444 C | 50/50 | 2.82 MW | 2.82 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961532 | AF2-444 E | 50/50 | 1.92 MW | 1.92 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961541 | AF2-445AC | 50/50 | 3.67 MW | 3.67 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 961542 | AF2-445AE | 50/50 | 2.49 MW | 2.49 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 962061 | AG1-050 | Adder | 2.07 MW | 1.76 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 962151 | AG1-060 C | 50/50 | 6.15 MW | 6.15 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 962152 | AG1-060 E | 50/50 | 35.68 MW | 35.68 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 208941 | FISH CT | 50/50 | 1.48 MW | 1.48 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 208981 | FOWH IPP | 50/50 | 1.74 MW | 1.74 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 208982 | GLBT IPP | 50/50 | 4.34 MW | 4.34 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 209013 | SCEN IPP | 50/50 | 4.55 MW | 4.55 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 209021 | WEST IPP | 50/50 | 1.32 MW | 1.32 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 209022 | WHFR IPP | 50/50 | 13.37 MW | 13.37 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 209027 | LOR2_Q27 | 50/50 | 0.6 MW | 0.6 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 211375 | BEAC | Adder | -3.3 MW | -2.81 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 212099 | COLA IPP | 50/50 | 0.33 MW | 0.33 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 212174 | INGE | 50/50 | 0.25 MW | 0.25 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 212266 | LOR1 | 50/50 | 0.19 MW | 0.19 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 939891 | AE1-225 C O1 | Adder | 0.87 MW | 0.74 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 939892 | AE1-225 E O1 | Adder | 0.97 MW | 0.82 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940561 | AE2-042 C | Adder | 4.85 MW | 4.12 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940562 | AE2-042 E | Adder | 2.4 MW | 2.04 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940721 | AE2-059 C | Adder | 0.87 MW | 0.74 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940722 | AE2-059 E | Adder | 1.2 MW | 1.02 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940941 | AE2-084 C | Adder | 0.87 MW | 0.74 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940942 | AE2-084 E | Adder | 1.2 MW | 1.02 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 941161 | AE2-110 C | 50/50 | 1.45 MW | 1.45 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 941162 | AE2-110 E | 50/50 | 2.01 MW | 2.01 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 941371 | AE2-133 C | Adder | 0.78 MW | 0.66 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 941372 | AE2-133 E | Adder | 1.08 MW | 0.92 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946691 | AF1-333 C O1 | Adder | 1.17 MW | 1.0 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946692 | AF1-333 E O1 | Adder | 0.78 MW | 0.67 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946731 | AF1-337 C | Adder | 1.17 MW | 1.0 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946732 | AF1-337 E | Adder | 0.78 MW | 0.67 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946741 | AF1-338 C | Adder | 1.17 MW | 1.0 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946742 | AF1-338 E | Adder | 0.78 MW | 0.67 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946751 | AF1-339 C O1 | Adder | 1.17 MW | 1.0 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946752 | AF1-339 E O1 | Adder | 0.78 MW | 0.67 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946761 | AF1-271AC | Adder | 0.95 MW | 0.81 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 946762 | AF1-271AE | Adder | 0.63 MW | 0.54 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957621 | AF2-056 C | 50/50 | 10.26 MW | 10.26 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957622 | AF2-056 E | 50/50 | 5.29 MW | 5.29 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964051 | AG1-259 C | Adder | 0.62 MW | 0.53 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964052 | AG1-259 E | Adder | 0.86 MW | 0.73 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964061 | AG1-260 C | Adder | 0.62 MW | 0.53 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964062 | AG1-260 E | Adder | 0.86 MW | 0.73 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957881 | AF2-082 C | Adder | 3.07 MW | 2.61 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957882 | AF2-082 E | Adder | 2.04 MW | 1.74 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957921 | AF2-086 C | 50/50 | 2.04 MW | 2.04 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 957922 | AF2-086 E | 50/50 | 1.35 MW | 1.35 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 958461 | AF2-140 | Adder | 3.37 MW | 2.86 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964183 | AG1-279 BAT | 50/50 | 0.56 MW | 0.56 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964173 | AG1-278 BAT | 50/50 | 0.56 MW | 0.56 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 940593 | AE2-046 BAT | 50/50 | 4.95 MW | 4.95 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 211369 | W1-111 BAT | 50/50 | 3.3 MW | 3.3 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | 964163 | AG1-277 BAT | 50/50 | 3.3 MW | 3.3 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.21 MW | 1.21 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.83 MW | 2.83 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.58 MW | 1.58 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.05 MW | 2.05 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.29 MW | 0.29 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.12 MW | 0.12 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.3 MW | 0.3 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 15.68 MW | 15.68 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.23 MW | 0.23 MW |
| FRAC-AE1-058_TAP 230.0 kV Ckt 1 line l/o PL:48:P71:102415 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n7562 | Break the SUSQ-WESC 500kV line at Siegfried substation. Build a new 500kV yard with one 500/230kV Transformer at Siegfried substation. | $40,300,000 | |
| n7260 | Rebuild Frackville - AE1-058 TAP 230kV Line | $16,571,069 | |
| n7564 | Construct a new (4 miles) 230kV single circuit line from GLBR - SU10 and rebuild GLBR - SUSQ. | $22,400,000 | |
| b3664 | Juniata: Upgrade T2 transformer leads, bay conductor, bus conductor and MODs. | $680,000 | |
| n6406 | Rebuild AE1-058 yard-SIEG 230kV line. | $76,200,000 | |
Attachments
Conclusion